Table of Contents

Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:43

Tabular Output Report in Format: HTML

Building: OfficeLarge

Environment: RUNPERIOD 1 ** Great Falls Intl Arpt MT USA TMY3 WMO#=727750

Simulation Timestamp: 2023-10-16 08:43:39


Table of Contents

Report: Annual Building Utility Performance Summary

For: Entire Facility

Timestamp: 2023-10-16 08:43:39

Values gathered over 8760.00 hours



Site and Source Energy

Total Energy [GJ] Energy Per Total Building Area [MJ/m2] Energy Per Conditioned Building Area [MJ/m2]
Total Site Energy 33097.28 714.53 714.53
Net Site Energy 33097.28 714.53 714.53
Total Source Energy 95530.49 2062.39 2062.39
Net Source Energy 95530.49 2062.39 2062.39


Site to Source Energy Conversion Factors

Site=>Source Conversion Factor
Electricity 3.167
Natural Gas 1.084
District Cooling 1.056
District Heating 3.613
Steam 1.200
Gasoline 1.050
Diesel 1.050
Coal 1.050
Fuel Oil No 1 1.050
Fuel Oil No 2 1.050
Propane 1.050
Other Fuel 1 1.000
Other Fuel 2 1.000


Building Area

Area [m2]
Total Building Area 46320.38
Net Conditioned Building Area 46320.38
Unconditioned Building Area 0.00


End Uses

Electricity [GJ] Natural Gas [GJ] Gasoline [GJ] Diesel [GJ] Coal [GJ] Fuel Oil No 1 [GJ] Fuel Oil No 2 [GJ] Propane [GJ] Other Fuel 1 [GJ] Other Fuel 2 [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating 0.00 3610.86 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 1480.31 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 3933.41 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 696.47 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 14676.40 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 1934.80 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 2717.83 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 326.28 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 437.48 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 3495.54
Humidification 2435.06 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 905.84
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 848.37 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 2280.17
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                           
Total End Uses 28638.04 4459.24 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 6681.55
Note: Natural gas appears to be the principal heating source based on energy usage.

End Uses By Subcategory

Subcategory Electricity [GJ] Natural Gas [GJ] Gasoline [GJ] Diesel [GJ] Coal [GJ] Fuel Oil No 1 [GJ] Fuel Oil No 2 [GJ] Propane [GJ] Other Fuel 1 [GJ] Other Fuel 2 [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Boiler 0.00 3610.86 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Boiler Parasitic 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling General 1480.31 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting LightsWired 3933.41 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting General 696.47 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment MiscPlug 5334.97 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  DataCenterPlugLoads 9341.42 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment Transformer 80.18 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  ElevatorLift 1848.78 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  ElevatorLightsFan 5.83 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans General 2717.83 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps General 326.28 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection General 437.48 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 3495.54
Humidification General 2435.06 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 905.84
Heat Recovery General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  WaterUse 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 2280.17
  Water Heater 0.00 848.37 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


End Uses By Space Type

Space Type Electricity [GJ] Natural Gas [GJ] Gasoline [GJ] Diesel [GJ] Coal [GJ] Fuel Oil No 1 [GJ] Fuel Oil No 2 [GJ] Propane [GJ] Other Fuel 1 [GJ] Other Fuel 2 [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating Unassigned 0.00 3610.86 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling Unassigned 1480.31 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting GENERAL 3933.41 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting Unassigned 696.47 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment GENERAL 14676.40 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment Unassigned 1934.80 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans Unassigned 2717.83 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps Unassigned 326.28 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection Unassigned 437.48 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 3495.54
Humidification Unassigned 2435.06 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 905.84
Heat Recovery Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems Unassigned 0.00 848.37 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 2280.17
Refrigeration Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Normalized Metrics

Utility Use Per Conditioned Floor Area

Electricity Intensity [MJ/m2] Natural Gas Intensity [MJ/m2] Gasoline Intensity [MJ/m2] Diesel Intensity [MJ/m2] Coal Intensity [MJ/m2] Fuel Oil No 1 Intensity [MJ/m2] Fuel Oil No 2 Intensity [MJ/m2] Propane Intensity [MJ/m2] Other Fuel 1 Intensity [MJ/m2] Other Fuel 2 Intensity [MJ/m2] District Cooling Intensity [MJ/m2] District Heating Intensity [MJ/m2] Water Intensity [m3/m2]
Lighting 99.95 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
HVAC 159.69 96.27 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.14
Other 358.62 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total 618.26 96.27 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.14


Utility Use Per Total Floor Area

Electricity Intensity [MJ/m2] Natural Gas Intensity [MJ/m2] Gasoline Intensity [MJ/m2] Diesel Intensity [MJ/m2] Coal Intensity [MJ/m2] Fuel Oil No 1 Intensity [MJ/m2] Fuel Oil No 2 Intensity [MJ/m2] Propane Intensity [MJ/m2] Other Fuel 1 Intensity [MJ/m2] Other Fuel 2 Intensity [MJ/m2] District Cooling Intensity [MJ/m2] District Heating Intensity [MJ/m2] Water Intensity [m3/m2]
Lighting 99.95 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
HVAC 159.69 96.27 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.14
Other 358.62 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total 618.26 96.27 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.14


Electric Loads Satisfied

Electricity [GJ] Percent Electricity [%]
Fuel-Fired Power Generation 0.000 0.00
High Temperature Geothermal* 0.000 0.00
Photovoltaic Power 0.000 0.00
Wind Power 0.000 0.00
Power Conversion 0.000 0.00
Net Decrease in On-Site Storage 0.000 0.00
Total On-Site Electric Sources 0.000 0.00
     
Electricity Coming From Utility 28638.043 100.00
Surplus Electricity Going To Utility 0.000 0.00
Net Electricity From Utility 28638.043 100.00
     
Total On-Site and Utility Electric Sources 28638.043 100.00
Total Electricity End Uses 28638.043 100.00


On-Site Thermal Sources

Heat [GJ] Percent Heat [%]
Water-Side Heat Recovery 0.00  
Air to Air Heat Recovery for Cooling 0.00  
Air to Air Heat Recovery for Heating 0.00  
High-Temperature Geothermal* 0.00  
Solar Water Thermal 0.00  
Solar Air Thermal 0.00  
Total On-Site Thermal Sources 0.00  


Water Source Summary

Water [m3] Percent Water [%]
Rainwater Collection 0.00 0.00
Condensate Collection 0.00 0.00
Groundwater Well 0.00 0.00
Total On Site Water Sources 0.00 0.00
- - -
Initial Storage 0.00 0.00
Final Storage 0.00 0.00
Change in Storage 0.00 0.00
- - -
Water Supplied by Utility 6681.55 100.00
- - -
Total On Site, Change in Storage, and Utility Water Sources 6681.55 100.00
Total Water End Uses 6681.55 100.00


Setpoint Not Met Criteria

Degrees [deltaC]
Tolerance for Zone Heating Setpoint Not Met Time 0.56
Tolerance for Zone Cooling Setpoint Not Met Time 0.56


Comfort and Setpoint Not Met Summary

Facility [Hours]
Time Setpoint Not Met During Occupied Heating 133.17
Time Setpoint Not Met During Occupied Cooling 247.83
Time Not Comfortable Based on Simple ASHRAE 55-2004 5938.00


Note 1: An asterisk (*) indicates that the feature is not yet implemented.

Table of Contents

Top
Annual Building Utility Performance Summary
Input Verification and Results Summary
Demand End Use Components Summary
Source Energy End Use Components Summary
Component Sizing Summary
Surface Shadowing Summary
Adaptive Comfort Summary
Initialization Summary
Annual Heat Emissions Summary
Climatic Data Summary
Envelope Summary
Shading Summary
Lighting Summary
Equipment Summary
HVAC Sizing Summary
Coil Sizing Details
System Summary
Outdoor Air Summary
Outdoor Air Details
Object Count Summary
Energy Meters
Sensible Heat Gain Summary
Standard 62.1 Summary
LEED Summary
Annual Thermal Resilience Summary
Annual CO2 Resilience Summary
Annual Visual Resilience Summary

NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR

| Environment |

NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901

| Environment |

NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2013

| Environment |

NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND

| Environment |

NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICELARGE

| Environment |

NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL

| Environment |

NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL

| Environment |

NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 6B

| Environment |

NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_MT_GREATFALLS

| Environment |

ZoneCoolingSummaryMonthly

| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |

ZoneHeatingSummaryMonthly

| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |

ZoneElectricSummaryMonthly

| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |

SpaceGainsMonthly

| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |

PeakSpaceGainsMonthly

| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |

SpaceGainComponentsAtCoolingPeakMonthly

| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |

EnergyConsumptionElectricityNaturalGasMonthly

| Meter |

EndUseEnergyConsumptionElectricityMonthly

| Meter |

EndUseEnergyConsumptionNaturalGasMonthly

| Meter |

PeakEnergyEndUseElectricityPart1Monthly

| Meter |

PeakEnergyEndUseElectricityPart2Monthly

| Meter |

ElectricComponentsOfPeakDemandMonthly

| Meter |

PeakEnergyEndUseNaturalGasMonthly

| Meter |

SetpointsNotMetWithTemperaturesMonthly

| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |

ComfortReportSimple55Monthly

| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |

OccupantComfortDataSummaryMonthly

| DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 | BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 |

ChillerReportMonthly

| COOLSYS1 CHILLER1 | COOLSYS1 CHILLER2 |

TowerReportMonthly

| CENTRAL TOWER | TOWERWATERSYS COOLTOWER 1 | TOWERWATERSYS COOLTOWER 2 |

BoilerReportMonthly

| HEATSYS1 BOILER | CENTRAL BOILER |

DXReportMonthly

| VAV_BOT WITH REHEAT COOLING COIL | VAV_MID WITH REHEAT COOLING COIL | VAV_TOP WITH REHEAT COOLING COIL | CAV_BAS COOLING COIL | AIRLOOP DATACENTER BASEMENT COOLING COIL | AIRLOOP DATACENTER BOT COOLING COIL | AIRLOOP DATACENTER MID COOLING COIL | AIRLOOP DATACENTER TOP COOLING COIL |

WindowReportMonthly

| PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW |

WindowEnergyReportMonthly

| PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW |

WindowZoneSummaryMonthly

| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |

WindowEnergyZoneSummaryMonthly

| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |

AverageOutdoorConditionsMonthly

| Environment |

OutdoorConditionsMaximumDryBulbMonthly

| Environment |

OutdoorConditionsMinimumDryBulbMonthly

| Environment |

OutdoorConditionsMaximumWetBulbMonthly

| Environment |

OutdoorConditionsMaximumDewPointMonthly

| Environment |

OutdoorGroundConditionsMonthly

| Environment |

WaterHeaterReportMonthly

| SWHSYS1 WATER HEATER |

DaylightingReportMonthly

| PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_4_DAYLCTRL |

CoilReportMonthly

| VAV_BOT WITH REHEAT HEATING COIL | CORE_BOTTOM VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | VAV_MID WITH REHEAT HEATING COIL | CORE_MID VAV BOX REHEAT COIL | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | VAV_TOP WITH REHEAT HEATING COIL | CORE_TOP VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | CAV_BAS HEATING COIL | AIRLOOP DATACENTER BASEMENT HEATING COIL | AIRLOOP DATACENTER BOT HEATING COIL | AIRLOOP DATACENTER MID HEATING COIL | AIRLOOP DATACENTER TOP HEATING COIL | AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | AIRLOOP DATACENTER BOT_SUPPHEATCOIL | AIRLOOP DATACENTER MID_SUPPHEATCOIL | AIRLOOP DATACENTER TOP_SUPPHEATCOIL | VAV_BOT WITH REHEAT COOLING COIL | VAV_MID WITH REHEAT COOLING COIL | VAV_TOP WITH REHEAT COOLING COIL | CAV_BAS COOLING COIL | AIRLOOP DATACENTER BASEMENT COOLING COIL | AIRLOOP DATACENTER BOT COOLING COIL | AIRLOOP DATACENTER MID COOLING COIL | AIRLOOP DATACENTER TOP COOLING COIL |

PlantLoopDemandReportMonthly

| HEATSYS1 | COOLSYS1_SUPPLY | COOLSYS1_DEMAND | SINGLE WATER PLANT LOOP | SWHSYS1 | TOWERWATERSYS |

FanReportMonthly

| CAV_BAS FAN | VAV_BOT WITH REHEAT FAN | VAV_MID WITH REHEAT FAN | VAV_TOP WITH REHEAT FAN | AIRLOOP DATACENTER BASEMENT SUPPLY FAN | AIRLOOP DATACENTER BOT SUPPLY FAN | AIRLOOP DATACENTER MID SUPPLY FAN | AIRLOOP DATACENTER TOP SUPPLY FAN |

PumpReportMonthly

| HEATSYS1 PUMP | COOLSYS1 PUMP SECONDARY | COOLSYS1 CHILLER1 PUMP | COOLSYS1 CHILLER2 PUMP | PLANT CIRC PUMP | SWHSYS1 PUMP | TOWERWATERSYS PUMP |

CondLoopDemandReportMonthly

| HEATSYS1 | COOLSYS1_SUPPLY | COOLSYS1_DEMAND | SINGLE WATER PLANT LOOP | SWHSYS1 | TOWERWATERSYS |

ZoneTemperatureOscillationReportMonthly

| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |

AirLoopSystemEnergyAndWaterUseMonthly

| VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | CAV_BAS | AIRLOOP DATACENTER BASEMENT | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |

AirLoopSystemComponentLoadsMonthly

| VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | CAV_BAS | AIRLOOP DATACENTER BASEMENT | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |

AirLoopSystemComponentEnergyUseMonthly

| VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | CAV_BAS | AIRLOOP DATACENTER BASEMENT | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |

MechanicalVentilationLoadsMonthly

| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |

HeatEmissionsReportMonthly

| Environment |

Table of Contents

Report: Input Verification and Results Summary

For: Entire Facility

Timestamp: 2023-10-16 08:43:39

General

Value
Program Version and Build EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:43
RunPeriod RUNPERIOD 1
Weather File Great Falls Intl Arpt MT USA TMY3 WMO#=727750
Latitude [deg] 47.47
Longitude [deg] -111.4
Elevation [m] 1117.00
Time Zone -7.0
North Axis Angle [deg] 0.00
Rotation for Appendix G [deg] 0.00
Hours Simulated [hrs] 8760.00


ENVELOPE

Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [m2] 12183.89 3655.17 2436.78 3655.17 2436.78
Above Ground Wall Area [m2] 11589.54 3476.86 2317.91 3476.86 2317.91
Window Opening Area [m2] 4635.80 1390.74 927.16 1390.74 927.16
Gross Window-Wall Ratio [%] 38.05 38.05 38.05 38.05 38.05
Above Ground Window-Wall Ratio [%] 40.00 40.00 40.00 40.00 40.00


Conditioned Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [m2] 12183.89 3655.17 2436.78 3655.17 2436.78
Above Ground Wall Area [m2] 11589.54 3476.86 2317.91 3476.86 2317.91
Window Opening Area [m2] 4635.80 1390.74 927.16 1390.74 927.16
Gross Window-Wall Ratio [%] 38.05 38.05 38.05 38.05 38.05
Above Ground Window-Wall Ratio [%] 40.00 40.00 40.00 40.00 40.00


Skylight-Roof Ratio

Total
Gross Roof Area [m2] 3563.11
Skylight Area [m2] 0.00
Skylight-Roof Ratio [%] 0.00


PERFORMANCE

Zone Summary

Area [m2] Conditioned (Y/N) Part of Total Floor Area (Y/N) Volume [m3] Multipliers Above Ground Gross Wall Area [m2] Underground Gross Wall Area [m2] Window Glass Area [m2] Opening Area [m2] Lighting [W/m2] People [m2 per person] Plug and Process [W/m2]
BASEMENT 2779.43 Yes Yes 6779.02 1.00 0.00 397.05 0.00 0.00 10.2732 18.58 4.8418
CORE_BOTTOM 2496.12 Yes Yes 6849.35 1.00 0.00 0.00 0.00 0.00 10.2732 18.58 8.0697
CORE_MID 2496.12 Yes Yes 6849.35 10.00 0.00 0.00 0.00 0.00 10.2732 18.58 8.0696
CORE_TOP 2496.12 Yes Yes 6849.35 1.00 0.00 0.00 0.00 0.00 10.2732 18.58 8.0696
PERIMETER_BOT_ZN_3 313.41 Yes Yes 860.00 1.00 200.61 0.00 115.90 115.90 10.2732 18.58 8.0700
PERIMETER_BOT_ZN_2 201.98 Yes Yes 554.22 1.00 133.74 0.00 77.26 77.26 10.2732 18.58 8.0700
PERIMETER_BOT_ZN_1 313.42 Yes Yes 860.02 1.00 200.61 0.00 115.90 115.90 10.2732 18.58 8.0699
PERIMETER_BOT_ZN_4 201.98 Yes Yes 554.22 1.00 133.74 0.00 77.26 77.26 10.2732 18.58 8.0699
PERIMETER_MID_ZN_3 313.41 Yes Yes 860.00 10.00 200.61 0.00 115.90 115.90 10.2732 18.58 8.0700
PERIMETER_MID_ZN_2 201.98 Yes Yes 554.22 10.00 133.74 0.00 77.26 77.26 10.2732 18.58 8.0700
PERIMETER_MID_ZN_1 313.42 Yes Yes 860.02 10.00 200.61 0.00 115.90 115.90 10.2732 18.58 8.0699
PERIMETER_MID_ZN_4 201.98 Yes Yes 554.22 10.00 133.74 0.00 77.26 77.26 10.2732 18.58 8.0699
PERIMETER_TOP_ZN_3 313.41 Yes Yes 860.00 1.00 200.61 0.00 115.90 115.90 10.2732 18.58 8.0700
PERIMETER_TOP_ZN_2 201.98 Yes Yes 554.22 1.00 133.74 0.00 77.26 77.26 10.2732 18.58 8.0700
PERIMETER_TOP_ZN_1 313.42 Yes Yes 860.02 1.00 200.61 0.00 115.90 115.90 10.2732 18.58 8.0699
PERIMETER_TOP_ZN_4 201.98 Yes Yes 554.22 1.00 133.74 0.00 77.26 77.26 10.2732 18.58 8.0699
GROUNDFLOOR_PLENUM 3563.11 Yes No 4344.14 1.00 297.11 0.00 0.00 0.00 0.0000   0.0000
MIDFLOOR_PLENUM 3563.11 Yes No 4344.14 10.00 297.11 0.00 0.00 0.00 0.0000   0.0000
TOPFLOOR_PLENUM 3563.11 Yes No 4344.14 1.00 297.11 0.00 0.00 0.00 0.0000   0.0000
DATACENTER_BOT_ZN_6 36.20 Yes Yes 99.34 1.00 0.00 0.00 0.00 0.00 17.8735 18.58 215.2992
DATACENTER_MID_ZN_6 36.20 Yes Yes 99.34 10.00 0.00 0.00 0.00 0.00 17.8735 18.58 215.2992
DATACENTER_TOP_ZN_6 36.20 Yes Yes 99.34 1.00 0.00 0.00 0.00 0.00 17.8735 18.58 215.2992
DATACENTER_BASEMENT_ZN_6 783.68 Yes Yes 1911.37 1.00 0.00 197.31 0.00 0.00 10.2732 18.58 484.4232
Total 46320.38     126016.35   8024.24 594.36 4635.80 4635.80 10.3445 18.58 17.8789
Conditioned Total 46320.38     126016.35   8024.24 594.36 4635.80 4635.80 10.3445 18.58 17.8789
Unconditioned Total 0.00     0.00   0.00 0.00 0.00 0.00      
Not Part of Total 42757.27     52129.67   3565.29 0.00 0.00 0.00 0.0000   0.0000


Space Summary

Area [m2] Conditioned (Y/N) Part of Total Floor Area (Y/N) Multipliers Zone Name Space Type Radiant/Solar Enclosure Name Lighting [W/m2] People [m2 per person] Plug and Process [W/m2] Tags
BASEMENT 2779.43 Yes Yes 1.00 BASEMENT GENERAL BASEMENT 10.2732 18.58 4.8418  
CORE_BOTTOM 2496.12 Yes Yes 1.00 CORE_BOTTOM GENERAL CORE_BOTTOM 10.2732 18.58 8.0697  
CORE_MID 2496.12 Yes Yes 10.00 CORE_MID GENERAL CORE_MID 10.2732 18.58 8.0696  
CORE_TOP 2496.12 Yes Yes 1.00 CORE_TOP GENERAL CORE_TOP 10.2732 18.58 8.0696  
PERIMETER_BOT_ZN_3 313.41 Yes Yes 1.00 PERIMETER_BOT_ZN_3 GENERAL PERIMETER_BOT_ZN_3 10.2732 18.58 8.0700  
PERIMETER_BOT_ZN_2 201.98 Yes Yes 1.00 PERIMETER_BOT_ZN_2 GENERAL PERIMETER_BOT_ZN_2 10.2732 18.58 8.0700  
PERIMETER_BOT_ZN_1 313.42 Yes Yes 1.00 PERIMETER_BOT_ZN_1 GENERAL PERIMETER_BOT_ZN_1 10.2732 18.58 8.0699  
PERIMETER_BOT_ZN_4 201.98 Yes Yes 1.00 PERIMETER_BOT_ZN_4 GENERAL PERIMETER_BOT_ZN_4 10.2732 18.58 8.0699  
PERIMETER_MID_ZN_3 313.41 Yes Yes 10.00 PERIMETER_MID_ZN_3 GENERAL PERIMETER_MID_ZN_3 10.2732 18.58 8.0700  
PERIMETER_MID_ZN_2 201.98 Yes Yes 10.00 PERIMETER_MID_ZN_2 GENERAL PERIMETER_MID_ZN_2 10.2732 18.58 8.0700  
PERIMETER_MID_ZN_1 313.42 Yes Yes 10.00 PERIMETER_MID_ZN_1 GENERAL PERIMETER_MID_ZN_1 10.2732 18.58 8.0699  
PERIMETER_MID_ZN_4 201.98 Yes Yes 10.00 PERIMETER_MID_ZN_4 GENERAL PERIMETER_MID_ZN_4 10.2732 18.58 8.0699  
PERIMETER_TOP_ZN_3 313.41 Yes Yes 1.00 PERIMETER_TOP_ZN_3 GENERAL PERIMETER_TOP_ZN_3 10.2732 18.58 8.0700  
PERIMETER_TOP_ZN_2 201.98 Yes Yes 1.00 PERIMETER_TOP_ZN_2 GENERAL PERIMETER_TOP_ZN_2 10.2732 18.58 8.0700  
PERIMETER_TOP_ZN_1 313.42 Yes Yes 1.00 PERIMETER_TOP_ZN_1 GENERAL PERIMETER_TOP_ZN_1 10.2732 18.58 8.0699  
PERIMETER_TOP_ZN_4 201.98 Yes Yes 1.00 PERIMETER_TOP_ZN_4 GENERAL PERIMETER_TOP_ZN_4 10.2732 18.58 8.0699  
GROUNDFLOOR_PLENUM 3563.11 Yes No 1.00 GROUNDFLOOR_PLENUM GENERAL GROUNDFLOOR_PLENUM 0.0000 0.00 0.0000  
MIDFLOOR_PLENUM 3563.11 Yes No 10.00 MIDFLOOR_PLENUM GENERAL MIDFLOOR_PLENUM 0.0000 0.00 0.0000  
TOPFLOOR_PLENUM 3563.11 Yes No 1.00 TOPFLOOR_PLENUM GENERAL TOPFLOOR_PLENUM 0.0000 0.00 0.0000  
DATACENTER_BOT_ZN_6 36.20 Yes Yes 1.00 DATACENTER_BOT_ZN_6 GENERAL DATACENTER_BOT_ZN_6 17.8735 18.58 215.2992  
DATACENTER_MID_ZN_6 36.20 Yes Yes 10.00 DATACENTER_MID_ZN_6 GENERAL DATACENTER_MID_ZN_6 17.8735 18.58 215.2992  
DATACENTER_TOP_ZN_6 36.20 Yes Yes 1.00 DATACENTER_TOP_ZN_6 GENERAL DATACENTER_TOP_ZN_6 17.8735 18.58 215.2992  
DATACENTER_BASEMENT_ZN_6 783.68 Yes Yes 1.00 DATACENTER_BASEMENT_ZN_6 GENERAL DATACENTER_BASEMENT_ZN_6 10.2732 18.58 484.4232  
Total 46320.38             10.3445 9.29 17.8789  
Conditioned Total 46320.38             10.3445 9.29 17.8789  
Unconditioned Total 0.00             0.0000 0.00 0.0000  
Not Part of Total 42757.27             0.0000 0.00 0.0000  


Space Type Summary

Total Area [m2] Conditioned Area [m2] Unconditioned Area [m2] Not Part of Total Area [m2] Lighting [W/m2] People [m2 per person] Plug and Process [W/m2]
GENERAL 46320.38 46320.38 0.00 42757.27 3.1788 60.38 10.8345
Total 46320.38 46320.38 0.00 42757.27      



Table of Contents

Report: Demand End Use Components Summary

For: Entire Facility

Timestamp: 2023-10-16 08:43:39

End Uses

Electricity [W] Natural Gas [W] Gasoline [W] Diesel [W] Coal [W] Fuel Oil No 1 [W] Fuel Oil No 2 [W] Propane [W] Other Fuel 1 [W] Other Fuel 2 [W] District Cooling [W] Steam [W] Water [m3/s]
Time of Peak 07-AUG-15:39 09-JAN-07:10 - - - - - - - - - - 17-JUL-15:00
Heating 0.00 2431734.33 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 446956.08 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 332294.83 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 778371.69 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 84450.25 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 351775.03 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 47934.78 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 83553.24 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 100000.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 33069.35 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                           
Total End Uses 2225335.88 2464803.67 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


End Uses By Subcategory

Subcategory Electricity [W] Natural Gas [W] Gasoline [W] Diesel [W] Coal [W] Fuel Oil No 1 [W] Fuel Oil No 2 [W] Propane [W] Other Fuel 1 [W] Other Fuel 2 [W] District Cooling [W] Steam [W] Water [m3/s]
Heating General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Boiler 0.00 2431734.33 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Boiler Parasitic 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling General 446956.08 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting LightsWired 332294.83 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment MiscPlug 305206.10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  DataCenterPlugLoads 473165.59 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment Transformer 5015.67 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  ElevatorLift 79171.38 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  ElevatorLightsFan 263.20 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans General 351775.03 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps General 47934.78 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection General 83553.24 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification General 100000.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  WaterUse 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Water Heater 0.00 33069.35 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: Source Energy End Use Components Summary

For: Entire Facility

Timestamp: 2023-10-16 08:43:39

Values gathered over 8760.00 hours



Source Energy End Use Components Summary

Source Electricity [GJ] Source Natural Gas [GJ] Source Gasoline [GJ] Source Diesel [GJ] Source Coal [GJ] Source Fuel Oil No 1 [GJ] Source Fuel Oil No 2 [GJ] Source Propane [GJ] Source Other Fuel 1 [GJ] Source Other Fuel 2 [GJ] Source District Cooling [GJ] Source District Heating [GJ]
Heating 0.00 3914.18 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 4688.13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 12457.12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 2205.72 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 46480.15 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 6127.50 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 8607.37 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 1033.34 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 1385.51 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 7711.84 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 919.64 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Total Source Energy End Use Components 90696.68 4833.81 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Normalized Metrics

Source Energy End Use Components Per Conditioned Floor Area

Source Electricity [MJ/m2] Source Natural Gas [MJ/m2] Source Gasoline [MJ/m2] Source Diesel [MJ/m2] Source Coal [MJ/m2] Source Fuel Oil No 1 [MJ/m2] Source Fuel Oil No 2 [MJ/m2] Source Propane [MJ/m2] Source Other Fuel 1 [MJ/m2] Source Other Fuel 2 [MJ/m2] Source District Cooling [MJ/m2] Source District Heating [MJ/m2]
Heating 0.00 84.50 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 101.21 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 268.93 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 47.62 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 1003.45 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 132.29 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 185.82 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 22.31 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 29.91 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 166.49 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 19.85 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Total Source Energy End Use Components 1958.03 104.36 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Source Energy End Use Components Per Total Floor Area

Source Electricity [MJ/m2] Source Natural Gas [MJ/m2] Source Gasoline [MJ/m2] Source Diesel [MJ/m2] Source Coal [MJ/m2] Source Fuel Oil No 1 [MJ/m2] Source Fuel Oil No 2 [MJ/m2] Source Propane [MJ/m2] Source Other Fuel 1 [MJ/m2] Source Other Fuel 2 [MJ/m2] Source District Cooling [MJ/m2] Source District Heating [MJ/m2]
Heating 0.00 84.50 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 101.21 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 268.93 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 47.62 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 1003.45 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 132.29 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 185.82 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 22.31 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 29.91 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 166.49 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 19.85 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Total Source Energy End Use Components 1958.03 104.36 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: Component Sizing Summary

For: Entire Facility

Timestamp: 2023-10-16 08:43:39

AirTerminal:SingleDuct:ConstantVolume:NoReheat

Design Size Maximum Air Flow Rate [m3/s]
BASEMENT DIRECT AIR 6.82
DATACENTER_BOT_ZN_6 DIRECT AIR 0.585375
DATACENTER_MID_ZN_6 DIRECT AIR 5.63
DATACENTER_TOP_ZN_6 DIRECT AIR 0.572441
DATACENTER_BASEMENT_ZN_6 DIRECT AIR 24.54
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

AirTerminal:SingleDuct:VAV:Reheat

Design Size Maximum Air Flow Rate [m3/s] Design Size Constant Minimum Air Flow Fraction User-Specified Constant Minimum Air Flow Fraction Design Size Minimum Air Flow Rate [m3/s] Design Size Maximum Flow Fraction during Reheat [] User-Specified Maximum Flow Fraction during Reheat [] Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] Design Size Maximum Reheat Water Flow Rate [m3/s] Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] Design Size Reheat Coil Sizing Inlet Air Temperature [C] Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir]
CORE_BOTTOM VAV BOX COMPONENT 7.06 0.269249 0.288000 2.03 0.717997 0.500000 0.001415 0.000226 2.03 12.80 0.008000
CORE_MID VAV BOX COMPONENT 66.53 0.285907 0.299000 19.89 0.762419 0.500000 0.001333 0.004509 19.89 12.80 0.008000
CORE_TOP VAV BOX COMPONENT 6.44 0.295559 0.320000 2.06 0.788158 0.500000 0.001289 0.000977 3.80 12.80 0.008000
PERIMETER_BOT_ZN_3 VAV BOX COMPONENT 1.20 0.199528 0.213000 0.254946 0.532075 0.500000 0.001910 0.000189 0.737784 12.80 0.008000
PERIMETER_BOT_ZN_2 VAV BOX COMPONENT 1.62 0.094848 0.200000 0.324529 0.300000 0.500000 0.004017 0.000129 0.504891 12.80 0.008000
PERIMETER_BOT_ZN_1 VAV BOX COMPONENT 2.01 0.118919 0.200000 0.401663 0.317116 0.500000 0.003204 0.000207 0.808359 12.80 0.008000
PERIMETER_BOT_ZN_4 VAV BOX COMPONENT 1.99 0.077342 0.200000 0.397984 0.300000 0.500000 0.004926 0.000110 0.429743 12.80 0.008000
PERIMETER_MID_ZN_3 VAV BOX COMPONENT 11.40 0.209513 0.219000 2.50 0.558701 0.500000 0.001819 0.002668 10.41 12.80 0.008000
PERIMETER_MID_ZN_2 VAV BOX COMPONENT 17.31 0.088910 0.200000 3.46 0.300000 0.500000 0.004285 0.001771 6.91 12.80 0.008000
PERIMETER_MID_ZN_1 VAV BOX COMPONENT 20.52 0.116409 0.200000 4.10 0.310424 0.500000 0.003273 0.002710 10.57 12.80 0.008000
PERIMETER_MID_ZN_4 VAV BOX COMPONENT 18.72 0.082227 0.200000 3.74 0.300000 0.500000 0.004634 0.001748 6.82 12.80 0.008000
PERIMETER_TOP_ZN_3 VAV BOX COMPONENT 1.31 0.181678 0.202000 0.265534 0.484475 0.500000 0.002097 0.000337 1.31 12.80 0.008000
PERIMETER_TOP_ZN_2 VAV BOX COMPONENT 1.73 0.088910 0.200000 0.346205 0.300000 0.500000 0.004285 0.000222 0.867809 12.80 0.008000
PERIMETER_TOP_ZN_1 VAV BOX COMPONENT 2.19 0.109258 0.200000 0.437176 0.300000 0.500000 0.003487 0.000341 1.33 12.80 0.008000
PERIMETER_TOP_ZN_4 VAV BOX COMPONENT 1.97 0.078291 0.200000 0.393162 0.300000 0.500000 0.004866 0.000223 0.868347 12.80 0.008000
User-Specified values were used. Design Size values were used if no User-Specified values were provided. Design Size values may be derived from alternate User-Specified values.

Coil:Heating:Water

Design Size Rated Capacity [W] Design Size Maximum Water Flow Rate [m3/s] Design Size U-Factor Times Area Value [W/K]
CORE_BOTTOM VAV BOX REHEAT COIL 25791.51 0.000226 543.51
CORE_MID VAV BOX REHEAT COIL 515371.91 0.004509 12910.42
CORE_TOP VAV BOX REHEAT COIL 111653.25 0.000977 2946.07
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL 21629.82 0.000189 570.40
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL 14800.43 0.000129 390.28
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL 23695.44 0.000207 624.83
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL 12601.41 0.000110 332.34
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL 305019.35 0.002668 8041.46
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL 202437.02 0.001771 5336.91
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL 309716.07 0.002710 8165.21
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL 199861.14 0.001748 5269.02
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL 38505.23 0.000337 1015.02
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL 25419.30 0.000222 670.06
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL 39023.78 0.000341 1028.69
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL 25434.92 0.000223 670.47
VAV_BOT WITH REHEAT HEATING COIL 101691.05 0.000890 1578.77
VAV_MID WITH REHEAT HEATING COIL 1044136.00 0.009135 15812.23
VAV_TOP WITH REHEAT HEATING COIL 102308.46 0.000895 1597.68
CAV_BAS HEATING COIL 323708.58 0.002832 6941.25
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

AirLoopHVAC

Sum of Air Terminal Maximum Heating Flow Rates [m3/s] Sum of Air Terminal Minimum Heating Flow Rates [m3/s] Sum of Air Terminal Maximum Flow Rates [m3/s] Adjusted Heating Design Air Flow Rate [m3/s] Adjusted Cooling Design Air Flow Rate [m3/s] Adjusted Main Design Air Flow Rate [m3/s] User Heating Air Flow Ratio [] Calculated Heating Air Flow Ratio [] Design Supply Air Flow Rate [m3/s]
VAV_BOT WITH REHEAT 6.94 3.41 13.88 3.56 11.66 11.66 0.300000 0.305310 11.66
VAV_MID WITH REHEAT 67.23 33.70 134.47 51.18 107.83 107.83 0.300000 0.474632 107.83
VAV_TOP WITH REHEAT 6.82 3.50 13.63 8.19 12.30 12.30 0.300000 0.665542 12.30
CAV_BAS 6.82 6.82 6.82 6.82 6.82 6.82 1.00 1.00 6.82
AIRLOOP DATACENTER BASEMENT 24.54 24.54 24.54 24.54 24.54 24.54 1.00 0.999996 24.54
AIRLOOP DATACENTER BOT 0.585375 0.585375 0.585375 0.585375 0.585375 0.585375 1.00 1.00 0.585375
AIRLOOP DATACENTER MID 5.63 5.63 5.63 5.63 5.63 5.63 1.00 1.00 5.63
AIRLOOP DATACENTER TOP 0.572441 0.572441 0.572441 0.572441 0.572441 0.572441 1.00 1.00 0.572441
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Controller:OutdoorAir

Maximum Outdoor Air Flow Rate [m3/s] Minimum Outdoor Air Flow Rate [m3/s]
VAV_BOT WITH REHEAT_OA_CONTROLLER 11.66  
VAV_MID WITH REHEAT_OA_CONTROLLER 107.83  
VAV_TOP WITH REHEAT_OA_CONTROLLER 12.30  
CAV_BAS_OA_CONTROLLER 6.82 1.20
AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER 24.54 0.338393
AIRLOOP DATACENTER BOT_OA_CONTROLLER 0.585375 0.015632
AIRLOOP DATACENTER MID_OA_CONTROLLER 5.63 0.156323
AIRLOOP DATACENTER TOP_OA_CONTROLLER 0.572441 0.015632
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Coil:Cooling:Water

Design Size Design Inlet Air Temperature [C] Design Size Design Inlet Water Temperature [C] Design Size Design Outlet Air Temperature [C] Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] Design Size Design Coil Load [W] Design Size Design Water Flow Rate [m3/s] Design Size Design Air Flow Rate [m3/s]
VAV_BOT WITH REHEAT COOLING COIL 26.05 6.67 10.68 0.007083 0.007000 194585.29 0.008278 11.66
VAV_MID WITH REHEAT COOLING COIL 26.21 6.67 10.68 0.007077 0.007000 1817578.77 0.077324 107.83
VAV_TOP WITH REHEAT COOLING COIL 25.95 6.67 10.68 0.007073 0.007000 203672.51 0.008665 12.30
CAV_BAS COOLING COIL 25.70 6.67 11.23 0.007235 0.007000 110073.14 0.004683 6.82
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Fan:VariableVolume

Design Size Maximum Flow Rate [m3/s]
VAV_BOT WITH REHEAT FAN 11.66
VAV_MID WITH REHEAT FAN 107.83
VAV_TOP WITH REHEAT FAN 12.30
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Controller:WaterCoil

Maximum Actuated Flow [m3/s] Controller Convergence Tolerance
VAV_BOT WITH REHEAT_COOLC_CONTROLLER 0.008278 0.000058
VAV_BOT WITH REHEAT_HEATC_CONTROLLER 0.000890  
VAV_MID WITH REHEAT_COOLC_CONTROLLER 0.077324 0.000006
VAV_MID WITH REHEAT_HEATC_CONTROLLER 0.009135  
VAV_TOP WITH REHEAT_COOLC_CONTROLLER 0.008665 0.000055
VAV_TOP WITH REHEAT_HEATC_CONTROLLER 0.000895  
CAV_BAS_COOLC_CONTROLLER 0.004683 0.000102
CAV_BAS_HEATC_CONTROLLER 0.002832  
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Fan:ConstantVolume

Design Size Maximum Flow Rate [m3/s]
CAV_BAS FAN 6.82
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT

Design Size Rated Air Flow Rate [m3/s] Design Size Rated Total Cooling Capacity [W] Design Size Rated Sensible Cooling Capacity [W] Design Size Rated Water Flow Rate [m3/s]
AIRLOOP DATACENTER BASEMENT COOLING COIL 24.54 466437.89 262502.94 0.011423
AIRLOOP DATACENTER BOT COOLING COIL 0.585375 10807.09 6147.89 0.000265
AIRLOOP DATACENTER MID COOLING COIL 5.63 103961.65 59130.97 0.002546
AIRLOOP DATACENTER TOP COOLING COIL 0.572441 10570.02 6012.39 0.000259
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

AirLoopHVAC:UnitaryHeatPump:WaterToAir

Supply Air Flow Rate [m3/s] Supply Air Flow Rate During Heating Operation [m3/s] Supply Air Flow Rate During Cooling Operation [m3/s] Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] Nominal Heating Capacity [W] Nominal Cooling Capacity [W] Supplemental Heating Coil Nominal Capacity [W] Fraction of Supply Air Flow That Goes Through the Controlling Zone
AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP 24.54 24.54 24.54 24.54 466437.89 466437.89 24207.99 1.00
AIRLOOP DATACENTER BOT DXAC HEAT PUMP 0.585375 0.585375 0.585375 0.585375 10807.09 10807.09 1118.31 1.00
AIRLOOP DATACENTER MID DXAC HEAT PUMP 5.63 5.63 5.63 5.63 103961.65 103961.65 11183.09 1.00
AIRLOOP DATACENTER TOP DXAC HEAT PUMP 0.572441 0.572441 0.572441 0.572441 10570.02 10570.02 1118.31 1.00
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Fan:OnOff

Design Size Maximum Flow Rate [m3/s]
AIRLOOP DATACENTER BASEMENT SUPPLY FAN 24.54
AIRLOOP DATACENTER BOT SUPPLY FAN 0.585375
AIRLOOP DATACENTER MID SUPPLY FAN 5.63
AIRLOOP DATACENTER TOP SUPPLY FAN 0.572441
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT

Design Size Rated Air Flow Rate [m3/s] Design Size Rated Heating Capacity [W] Design Size Rated Water Flow Rate [m3/s]
AIRLOOP DATACENTER BASEMENT HEATING COIL 24.54 466437.89 0.011423
AIRLOOP DATACENTER BOT HEATING COIL 0.585375 10807.09 0.000265
AIRLOOP DATACENTER MID HEATING COIL 5.63 103961.65 0.002546
AIRLOOP DATACENTER TOP HEATING COIL 0.572441 10570.02 0.000259
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Coil:Heating:Electric

Design Size Nominal Capacity [W]
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL 24207.99
AIRLOOP DATACENTER BOT_SUPPHEATCOIL 1118.31
AIRLOOP DATACENTER MID_SUPPHEATCOIL 11183.09
AIRLOOP DATACENTER TOP_SUPPHEATCOIL 1118.31
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Humidifier:Steam:Electric

Design Size Nominal Capacity Volume [m3/s] User-Specified Nominal Capacity Volume [m3/s] Design Size Rated Power [W] User-Specified Rated Power [W]
DATACENTER_BASEMENT_ZN_6 HUMIDIFIER 0.000191 0.000037 96450.70 100000.00
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Pump:VariableSpeed

Design Flow Rate [m3/s] Design Power Consumption [W] Design Minimum Flow Rate [m3/s]
COOLSYS1 PUMP SECONDARY 0.098950 16155.44  
HEATSYS1 PUMP 0.030119 9070.57 0.000000
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

PlantLoop

Maximum Loop Flow Rate [m3/s] Plant Loop Volume [m3]
COOLSYS1_DEMAND 0.098950 11.87
HEATSYS1 0.030119 3.61
COOLSYS1_SUPPLY 0.098950 11.87
SINGLE WATER PLANT LOOP 0.014493 1.74
SWHSYS1 0.000440 0.052800
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

HeatExchanger:FluidToFluid

Loop Supply Side Design Fluid Flow Rate [m3/s] Loop Demand Side Design Fluid Flow Rate [m3/s] Heat Exchanger U-Factor Times Area Value [W/C] Loop-to-loop Temperature Difference Used to Size Heat Exchanger U-Factor Times Area Value [C]
BYPASS HEAT EXCHANGER 0.098950 0.098950 415341.02 5.60
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Boiler:HotWater

Design Size Nominal Capacity [W] User-Specified Nominal Capacity [W] Design Size Design Water Flow Rate [m3/s]
HEATSYS1 BOILER 3442804.66 3442804.66 0.030119
CENTRAL BOILER 596969.72 584202.86 0.014493
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Pump:ConstantSpeed

Design Flow Rate [m3/s] Design Power Consumption [W]
COOLSYS1 CHILLER1 PUMP 0.049475 5592.48
COOLSYS1 CHILLER2 PUMP 0.049475 5592.48
PLANT CIRC PUMP 0.014493 3696.33
SWHSYS1 PUMP 0.000440 56.21
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Chiller:Electric:ReformulatedEIR

Design Size Reference Chilled Water Flow Rate [m3/s] User-Specified Reference Chilled Water Flow Rate [m3/s] Design Size Reference Capacity [W] User-Specified Reference Capacity [W] Design Size Reference Condenser Water Flow Rate [m3/s]
COOLSYS1 CHILLER1 0.098950 0.049851 1174674.23 1180245.77 0.058406
COOLSYS1 CHILLER2 0.098950 0.049851 1174674.23 1180245.77 0.058406
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

FluidCooler:TwoSpeed

Design Water Flow Rate [m3/s] Air Flow Rate at High Fan Speed [m3/s] Fluid cooler UA value at high fan speed based on nominal capacity input [W/K] Air Flow Rate at Low Fan Speed [m3/s] Fan Power at Low Fan Speed [W] U-factor Times Area Value at Low Fan Speed [W/C]
CENTRAL TOWER 0.014493 139666.47 55299.27 69833.23 7879.72 20993.04
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

WaterHeater:Mixed

Use Side Design Flow Rate [m3/s]
SWHSYS1 WATER HEATER 0.000440
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

CondenserLoop

Maximum Loop Flow Rate [m3/s] Condenser Loop Volume [m3]
TOWERWATERSYS 0.116812 14.02
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

HeaderedPumps:VariableSpeed

Design Flow Rate [m3/s] Design Power Consumption [W]
TOWERWATERSYS PUMP 0.116812 28920.06
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

CoolingTower:VariableSpeed

Design Air Flow Rate [m3/s] Nominal Capacity [W] Air Flow Rate in free convection regime [m3/s] Tower capacity in free convection regime at design conditions [W]
TOWERWATERSYS COOLTOWER 1 51.62 1402076.60 10.32 175259.57
TOWERWATERSYS COOLTOWER 2 51.62 1402076.60 10.32 175259.57
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

PlantEquipmentOperation:ComponentSetPoint

Design Water Flow Rate [m3/s] Equipment # 47
WSHPPLANT OPERATION SCHEME 0.060665
User-Specified values were used. Design Size values were used if no User-Specified values were provided.


Table of Contents

Report: Surface Shadowing Summary

For: Entire Facility

Timestamp: 2023-10-16 08:43:39

Surfaces (Walls, Roofs, etc) that may be Shadowed by Other Surfaces

None


Subsurfaces (Windows and Doors) that may be Shadowed by Surfaces

Possible Shadow Receivers
PERIMETER_BOT_ZN_3_WALL_NORTH PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 |
PERIMETER_BOT_ZN_2_WALL_EAST PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 |
PERIMETER_BOT_ZN_1_WALL_SOUTH PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 |
PERIMETER_BOT_ZN_4_WALL_WEST PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 |
PERIMETER_MID_ZN_3_WALL_NORTH PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW |
PERIMETER_MID_ZN_2_WALL_EAST PERIMETER_MID_ZN_2_WALL_EAST_WINDOW |
PERIMETER_MID_ZN_1_WALL_SOUTH PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW |
PERIMETER_MID_ZN_4_WALL_WEST PERIMETER_MID_ZN_4_WALL_WEST_WINDOW |
PERIMETER_TOP_ZN_3_WALL_NORTH PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW |
PERIMETER_TOP_ZN_2_WALL_EAST PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW |
PERIMETER_TOP_ZN_1_WALL_SOUTH PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW |
PERIMETER_TOP_ZN_4_WALL_WEST PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW |



Table of Contents

Report: Adaptive Comfort Summary

For: Entire Facility

Timestamp: 2023-10-16 08:43:39

Time Not Meeting the Adaptive Comfort Models during Occupied Hours

ASHRAE55 90% Acceptability Limits [Hours] ASHRAE55 80% Acceptability Limits [Hours] CEN15251 Category I Acceptability Limits [Hours] CEN15251 Category II Acceptability Limits [Hours] CEN15251 Category III Acceptability Limits [Hours]



Table of Contents

Report: Initialization Summary

For: Entire Facility

Timestamp: 2023-10-16 08:43:39

Version

Version ID
1 22.1.0


Timesteps per Hour

#TimeSteps Minutes per TimeStep {minutes}
1 6 10


System Convergence Limits

Minimum System TimeStep {minutes} Max HVAC Iterations Minimum Plant Iterations Maximum Plant Iterations
1 1 20 2 8


Simulation Control

Do Zone Sizing Do System Sizing Do Plant Sizing Do Design Days Do Weather Simulation Do HVAC Sizing Simulation
1 Yes Yes Yes No Yes No


Performance Precision Tradeoffs

Use Coil Direct Simulation Zone Radiant Exchange Algorithm Override Mode Number of Timestep In Hour Force Euler Method Minimum Number of Warmup Days Force Suppress All Begin Environment Resets Minimum System Timestep MaxZoneTempDiff MaxAllowedDelTemp
1 No ScriptF Normal 6 No 1 No 1.0 0.300 2.0000E-003


Output Reporting Tolerances

Tolerance for Time Heating Setpoint Not Met Tolerance for Zone Cooling Setpoint Not Met Time
1 0.556 0.556


Site:GroundTemperature:BuildingSurface

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00


Site:GroundTemperature:FCfactorMethod

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 8.60 2.80 -4.10 -8.80 -2.20 0.30 6.70 10.10 16.50 20.60 19.20 14.70


Site:GroundTemperature:Shallow

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00


Site:GroundTemperature:Deep

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00


Site:GroundReflectance

Jan{dimensionless} Feb{dimensionless} Mar{dimensionless} Apr{dimensionless} May{dimensionless} Jun{dimensionless} Jul{dimensionless} Aug{dimensionless} Sep{dimensionless} Oct{dimensionless} Nov{dimensionless} Dec{dimensionless}
1 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20


Site:GroundReflectance:SnowModifier

Normal Daylighting {dimensionless}
1 1.000 1.000


Site:GroundReflectance:Snow

Jan{dimensionless} Feb{dimensionless} Mar{dimensionless} Apr{dimensionless} May{dimensionless} Jun{dimensionless} Jul{dimensionless} Aug{dimensionless} Sep{dimensionless} Oct{dimensionless} Nov{dimensionless} Dec{dimensionless}
1 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20


Site:GroundReflectance:Snow:Daylighting

Jan{dimensionless} Feb{dimensionless} Mar{dimensionless} Apr{dimensionless} May{dimensionless} Jun{dimensionless} Jul{dimensionless} Aug{dimensionless} Sep{dimensionless} Oct{dimensionless} Nov{dimensionless} Dec{dimensionless}
1 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20


Environment:Weather Station

Wind Sensor Height Above Ground {m} Wind Speed Profile Exponent {} Wind Speed Profile Boundary Layer Thickness {m} Air Temperature Sensor Height Above Ground {m} Wind Speed Modifier Coefficient-Internal Temperature Modifier Coefficient-Internal
1 10.000 0.140 270.000 1.500 1.586 9.750E-003


Site:Location

Location Name Latitude {N+/S- Deg} Longitude {E+/W- Deg} Time Zone Number {GMT+/-} Elevation {m} Standard Pressure at Elevation {Pa} Standard RhoAir at Elevation
1 Great Falls Intl Arpt MT USA TMY3 WMO#=727750 47.47 -111.38 -7.00 1117.00 88606 1.0531


Site Water Mains Temperature Information

Calculation Method{} Water Mains Temperature Schedule Name{} Annual Average Outdoor Air Temperature{C} Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} Fixed Default Water Mains Temperature{C}
1 Correlation NA 7.03 29.40 NA


Building Information

Building Name North Axis {deg} Terrain Loads Convergence Tolerance Value Temperature Convergence Tolerance Value Solar Distribution Maximum Number of Warmup Days Minimum Number of Warmup Days
1 OfficeLarge 0.000 City 4.00000E-002 0.20000 FullInteriorAndExterior 25 6


Inside Convection Algorithm

Algorithm {Simple
TARP
CeilingDiffuser
AdaptiveConvectionAlgorithm}
1 TARP


Outside Convection Algorithm

Algorithm {SimpleCombined
TARP
MoWitt
DOE-2
AdaptiveConvectionAlgorithm}
1 TARP


Sky Radiance Distribution

Value {Anisotropic}
1 Anisotropic


Zone Air Solution Algorithm

Value {ThirdOrderBackwardDifference
AnalyticalSolution
EulerMethod}
1 ThirdOrderBackwardDifference


Zone Air Carbon Dioxide Balance Simulation

Simulation {Yes/No} Carbon Dioxide Concentration
1 No N/A


Zone Air Generic Contaminant Balance Simulation

Simulation {Yes/No} Generic Contaminant Concentration
1 No N/A


Zone Air Mass Flow Balance Simulation

Enforce Mass Balance



Adjust Zone Mixing and Return {AdjustMixingOnly
AdjustReturnOnly
AdjustMixingThenReturn
AdjustReturnThenMixing
None}
Adjust Zone Infiltration {AddInfiltration
AdjustInfiltration
None}

Infiltration Zones {MixingSourceZonesOnly
AllZones}


1 No N/A N/A N/A


HVACSystemRootFindingAlgorithm

Value {RegulaFalsi
Bisection
BisectionThenRegulaFalsi
RegulaFalsiThenBisection}
1 RegulaFalsi


Environment:Site Atmospheric Variation

Wind Speed Profile Exponent {} Wind Speed Profile Boundary Layer Thickness {m} Air Temperature Gradient Coefficient {K/m}
1 0.330 460.000 6.500000E-003


Surface Geometry

Starting Corner Vertex Input Direction Coordinate System Daylight Reference Point Coordinate System Rectangular (Simple) Surface Coordinate System
1 UpperLeftCorner Counterclockwise RelativeCoordinateSystem RelativeCoordinateSystem RelativeToZoneOrigin


Surface Heat Transfer Algorithm

Value {CTF - ConductionTransferFunction
EMPD - MoisturePenetrationDepthConductionTransferFunction
CondFD - ConductionFiniteDifference
HAMT - CombinedHeatAndMoistureFiniteElement} - Description
Inside Surface Max Temperature Limit{C}


Surface Convection Coefficient Lower Limit {W/m2-K}


Surface Convection Coefficient Upper Limit {W/m2-K}


1 CTF - ConductionTransferFunction 200 0.10 1000.0


Shading Summary

Number of Fixed Detached Shades Number of Building Detached Shades Number of Attached Shades
1 0 0 0


Zone Summary

Number of Zones Number of Zone Surfaces Number of SubSurfaces
1 23 221 36


Zone Information

Zone Name North Axis {deg} Origin X-Coordinate {m} Origin Y-Coordinate {m} Origin Z-Coordinate {m} Centroid X-Coordinate {m} Centroid Y-Coordinate {m} Centroid Z-Coordinate {m} Type Zone Multiplier Zone List Multiplier Minimum X {m} Maximum X {m} Minimum Y {m} Maximum Y {m} Minimum Z {m} Maximum Z {m} Ceiling Height {m} Volume {m3} Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} Floor Area {m2} Exterior Gross Wall Area {m2} Exterior Net Wall Area {m2} Exterior Window Area {m2} Number of Surfaces Number of SubSurfaces Number of Shading SubSurfaces Part of Total Building Area
1 BASEMENT 0.0 0.00 0.00 0.00 44.59 24.37 -1.22 1 1 1 16.08 73.11 0.00 48.74 -2.44 0.00 2.44 6779.02 TARP TARP 2779.43 0.00 0.00 0.00 9 0 0 Yes
2 CORE_BOTTOM 0.0 0.00 0.00 0.00 37.01 24.37 1.37 1 1 1 5.49 68.53 4.57 44.17 0.00 2.74 2.74 6849.35 TARP TARP 2496.12 0.00 0.00 0.00 7 0 0 Yes
3 CORE_MID 0.0 0.00 0.00 0.00 37.01 24.37 18.14 1 10 1 5.49 68.53 4.57 44.17 16.77 19.51 2.74 6849.35 TARP TARP 2496.12 0.00 0.00 0.00 6 0 0 Yes
4 CORE_TOP 0.0 0.00 0.00 0.00 37.01 24.37 34.91 1 1 1 5.49 68.53 4.57 44.17 33.54 36.28 2.74 6849.35 TARP TARP 2496.12 0.00 0.00 0.00 6 0 0 Yes
5 PERIMETER_BOT_ZN_3 0.0 0.00 0.00 0.00 36.55 46.54 1.37 1 1 1 0.00 73.11 44.17 48.74 0.00 2.74 2.74 860.00 TARP TARP 313.41 200.61 76.91 115.90 8 9 0 Yes
6 PERIMETER_BOT_ZN_2 0.0 0.00 0.00 0.00 70.95 24.37 1.37 1 1 1 68.53 73.11 0.00 48.74 0.00 2.74 2.74 554.22 TARP TARP 201.98 133.74 52.57 77.26 6 5 0 Yes
7 PERIMETER_BOT_ZN_1 0.0 0.00 0.00 0.00 36.55 2.20 1.37 1 1 1 0.00 73.11 0.00 4.57 0.00 2.74 2.74 860.02 TARP TARP 313.42 200.61 76.91 115.90 8 9 0 Yes
8 PERIMETER_BOT_ZN_4 0.0 0.00 0.00 0.00 2.16 24.37 1.37 1 1 1 0.00 4.57 0.00 48.74 0.00 2.74 2.74 554.22 TARP TARP 201.98 133.74 52.57 77.26 6 5 0 Yes
9 PERIMETER_MID_ZN_3 0.0 0.00 0.00 0.00 36.55 46.54 18.14 1 10 1 0.00 73.11 44.17 48.74 16.77 19.51 2.74 860.00 TARP TARP 313.41 200.61 84.71 115.90 7 1 0 Yes
10 PERIMETER_MID_ZN_2 0.0 0.00 0.00 0.00 70.95 24.37 18.14 1 10 1 68.53 73.11 0.00 48.74 16.77 19.51 2.74 554.22 TARP TARP 201.98 133.74 56.47 77.26 6 1 0 Yes
11 PERIMETER_MID_ZN_1 0.0 0.00 0.00 0.00 36.55 2.20 18.14 1 10 1 0.00 73.11 0.00 4.57 16.77 19.51 2.74 860.02 TARP TARP 313.42 200.61 84.71 115.90 7 1 0 Yes
12 PERIMETER_MID_ZN_4 0.0 0.00 0.00 0.00 2.16 24.37 18.14 1 10 1 0.00 4.57 0.00 48.74 16.77 19.51 2.74 554.22 TARP TARP 201.98 133.74 56.47 77.26 6 1 0 Yes
13 PERIMETER_TOP_ZN_3 0.0 0.00 0.00 0.00 36.55 46.54 34.91 1 1 1 0.00 73.11 44.17 48.74 33.54 36.28 2.74 860.00 TARP TARP 313.41 200.61 84.71 115.90 7 1 0 Yes
14 PERIMETER_TOP_ZN_2 0.0 0.00 0.00 0.00 70.95 24.37 34.91 1 1 1 68.53 73.11 0.00 48.74 33.54 36.28 2.74 554.22 TARP TARP 201.98 133.74 56.47 77.26 6 1 0 Yes
15 PERIMETER_TOP_ZN_1 0.0 0.00 0.00 0.00 36.55 2.20 34.91 1 1 1 0.00 73.11 0.00 4.57 33.54 36.28 2.74 860.02 TARP TARP 313.42 200.61 84.71 115.90 7 1 0 Yes
16 PERIMETER_TOP_ZN_4 0.0 0.00 0.00 0.00 2.16 24.37 34.91 1 1 1 0.00 4.57 0.00 48.74 33.54 36.28 2.74 554.22 TARP TARP 201.98 133.74 56.47 77.26 6 1 0 Yes
17 GROUNDFLOOR_PLENUM 0.0 0.00 0.00 0.00 36.55 24.37 3.35 1 1 1 0.00 73.11 0.00 48.74 2.74 3.96 1.22 4344.14 TARP TARP 3563.11 297.11 297.11 0.00 11 0 0 No
18 MIDFLOOR_PLENUM 0.0 0.00 0.00 0.00 36.55 24.37 20.12 1 10 1 0.00 73.11 0.00 48.74 19.51 20.73 1.22 4344.14 TARP TARP 3563.11 297.11 297.11 0.00 11 0 0 No
19 TOPFLOOR_PLENUM 0.0 0.00 0.00 0.00 36.55 24.37 36.89 1 1 1 0.00 73.11 0.00 48.74 36.28 37.50 1.22 4344.14 TARP TARP 3563.11 297.11 297.11 0.00 11 0 0 No
20 DATACENTER_BOT_ZN_6 0.0 5.49 44.17 0.00 5.03 24.37 1.37 1 1 1 4.57 5.49 4.57 44.17 0.00 2.74 2.74 99.34 TARP TARP 36.20 0.00 0.00 0.00 6 0 0 Yes
21 DATACENTER_MID_ZN_6 0.0 4.57 4.57 16.77 5.03 24.37 18.14 1 10 1 4.57 5.49 4.57 44.17 16.77 19.51 2.74 99.34 TARP TARP 36.20 0.00 0.00 0.00 6 0 0 Yes
22 DATACENTER_TOP_ZN_6 0.0 4.57 4.57 33.54 5.03 24.37 34.91 1 1 1 4.57 5.49 4.57 44.17 33.54 36.28 2.74 99.34 TARP TARP 36.20 0.00 0.00 0.00 6 0 0 Yes
23 DATACENTER_BASEMENT_ZN_6 0.0 16.08 0.00 -2.44 8.04 24.37 -1.22 1 1 1 0.00 16.08 0.00 48.74 -2.44 0.00 2.44 1911.37 TARP TARP 783.68 0.00 0.00 0.00 10 0 0 Yes


Zone Internal Gains Nominal

Zone Name Floor Area {m2} # Occupants Area per Occupant {m2/person} Occupant per Area {person/m2} Interior Lighting {W/m2} Electric Load {W/m2} Gas Load {W/m2} Other Load {W/m2} Hot Water Eq {W/m2} Steam Equipment {W/m2} Sum Loads per Area {W/m2} Outdoor Controlled Baseboard Heat
1 BASEMENT 2779.43 149.6 18.579 5.382E-002 10.273 4.842 0.000 0.000 0.000 0.000 15.115 No
2 CORE_BOTTOM 2496.12 134.4 18.579 5.382E-002 10.273 8.070 0.000 0.000 0.000 0.000 18.343 No
3 CORE_MID 2496.12 134.4 18.579 5.382E-002 10.273 8.070 0.000 0.000 0.000 0.000 18.343 No
4 CORE_TOP 2496.12 134.4 18.579 5.382E-002 10.273 8.070 0.000 0.000 0.000 0.000 18.343 No
5 PERIMETER_BOT_ZN_3 313.41 16.9 18.579 5.382E-002 10.273 8.070 0.000 0.000 0.000 0.000 18.343 No
6 PERIMETER_BOT_ZN_2 201.98 10.9 18.579 5.382E-002 10.273 8.070 0.000 0.000 0.000 0.000 18.343 No
7 PERIMETER_BOT_ZN_1 313.42 16.9 18.579 5.382E-002 10.273 8.070 0.000 0.000 0.000 0.000 18.343 No
8 PERIMETER_BOT_ZN_4 201.98 10.9 18.579 5.382E-002 10.273 8.070 0.000 0.000 0.000 0.000 18.343 No
9 PERIMETER_MID_ZN_3 313.41 16.9 18.579 5.382E-002 10.273 8.070 0.000 0.000 0.000 0.000 18.343 No
10 PERIMETER_MID_ZN_2 201.98 10.9 18.579 5.382E-002 10.273 8.070 0.000 0.000 0.000 0.000 18.343 No
11 PERIMETER_MID_ZN_1 313.42 16.9 18.579 5.382E-002 10.273 8.070 0.000 0.000 0.000 0.000 18.343 No
12 PERIMETER_MID_ZN_4 201.98 10.9 18.579 5.382E-002 10.273 8.070 0.000 0.000 0.000 0.000 18.343 No
13 PERIMETER_TOP_ZN_3 313.41 16.9 18.579 5.382E-002 10.273 8.070 0.000 0.000 0.000 0.000 18.343 No
14 PERIMETER_TOP_ZN_2 201.98 10.9 18.579 5.382E-002 10.273 8.070 0.000 0.000 0.000 0.000 18.343 No
15 PERIMETER_TOP_ZN_1 313.42 16.9 18.579 5.382E-002 10.273 8.070 0.000 0.000 0.000 0.000 18.343 No
16 PERIMETER_TOP_ZN_4 201.98 10.9 18.579 5.382E-002 10.273 8.070 0.000 0.000 0.000 0.000 18.343 No
17 GROUNDFLOOR_PLENUM 3563.11 0.0 N/A 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 No
18 MIDFLOOR_PLENUM 3563.11 0.0 N/A 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 No
19 TOPFLOOR_PLENUM 3563.11 0.0 N/A 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 No
20 DATACENTER_BOT_ZN_6 36.20 1.9 18.579 5.382E-002 17.873 215.299 0.000 0.000 0.000 0.000 233.173 No
21 DATACENTER_MID_ZN_6 36.20 1.9 18.579 5.382E-002 17.873 215.299 0.000 0.000 0.000 0.000 233.173 No
22 DATACENTER_TOP_ZN_6 36.20 1.9 18.579 5.382E-002 17.873 215.299 0.000 0.000 0.000 0.000 233.173 No
23 DATACENTER_BASEMENT_ZN_6 783.68 42.2 18.579 5.382E-002 10.273 484.423 0.000 0.000 0.000 0.000 494.696 No


People Internal Gains Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Number of People {} People/Floor Area {person/m2} Floor Area per person {m2/person} Fraction Radiant Fraction Convected Sensible Fraction Calculation Activity level ASHRAE 55 Warnings Carbon Dioxide Generation Rate Nominal Minimum Number of People Nominal Maximum Number of People MRT Calculation Type Work Efficiency Clothing Insulation Calculation Method Clothing Insulation Calculation Method Schedule Clothing Air Velocity Fanger Calculation Pierce Calculation KSU Calculation Cooling Effect Calculation Ankle Draft Calculation
1 DATACENTER_BOT_ZN_6 BLDG_OCC_SCH_WO_SB DATACENTER_BOT_ZN_6 36.20 1.9 1.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
2 DATACENTER_MID_ZN_6 BLDG_OCC_SCH_WO_SB DATACENTER_MID_ZN_6 36.20 1.9 1.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
3 DATACENTER_TOP_ZN_6 BLDG_OCC_SCH_WO_SB DATACENTER_TOP_ZN_6 36.20 1.9 1.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
4 DATACENTER_BASEMENT_ZN_6 BLDG_OCC_SCH_WO_SB DATACENTER_BASEMENT_ZN_6 783.68 42.2 42.2 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 42 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
5 BASEMENT BLDG_OCC_SCH_WO_SB BASEMENT 2779.43 149.6 149.6 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 150 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
6 CORE_BOTTOM BLDG_OCC_SCH_WO_SB CORE_BOTTOM 2496.12 134.4 134.4 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 134 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
7 CORE_MID BLDG_OCC_SCH_WO_SB CORE_MID 2496.12 134.4 134.4 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 134 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
8 CORE_TOP BLDG_OCC_SCH_WO_SB CORE_TOP 2496.12 134.4 134.4 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 134 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
9 PERIMETER_BOT_ZN_3 BLDG_OCC_SCH_WO_SB PERIMETER_BOT_ZN_3 313.41 16.9 16.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 17 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
10 PERIMETER_BOT_ZN_2 BLDG_OCC_SCH_WO_SB PERIMETER_BOT_ZN_2 201.98 10.9 10.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 11 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
11 PERIMETER_BOT_ZN_1 BLDG_OCC_SCH_WO_SB PERIMETER_BOT_ZN_1 313.42 16.9 16.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 17 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
12 PERIMETER_BOT_ZN_4 BLDG_OCC_SCH_WO_SB PERIMETER_BOT_ZN_4 201.98 10.9 10.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 11 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
13 PERIMETER_MID_ZN_3 BLDG_OCC_SCH_WO_SB PERIMETER_MID_ZN_3 313.41 16.9 16.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 17 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
14 PERIMETER_MID_ZN_2 BLDG_OCC_SCH_W_SB PERIMETER_MID_ZN_2 201.98 10.9 10.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 11 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
15 PERIMETER_MID_ZN_1 BLDG_OCC_SCH_WO_SB PERIMETER_MID_ZN_1 313.42 16.9 16.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 17 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
16 PERIMETER_MID_ZN_4 BLDG_OCC_SCH_WO_SB PERIMETER_MID_ZN_4 201.98 10.9 10.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 11 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
17 PERIMETER_TOP_ZN_3 BLDG_OCC_SCH_WO_SB PERIMETER_TOP_ZN_3 313.41 16.9 16.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 17 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
18 PERIMETER_TOP_ZN_2 BLDG_OCC_SCH_WO_SB PERIMETER_TOP_ZN_2 201.98 10.9 10.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 11 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
19 PERIMETER_TOP_ZN_1 BLDG_OCC_SCH_WO_SB PERIMETER_TOP_ZN_1 313.42 16.9 16.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 17 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
20 PERIMETER_TOP_ZN_4 BLDG_OCC_SCH_WO_SB PERIMETER_TOP_ZN_4 201.98 10.9 10.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 11 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No


Lights Internal Gains Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Lighting Level {W} Lights/Floor Area {W/m2} Lights per person {W/person} Fraction Return Air Fraction Radiant Fraction Short Wave Fraction Convected Fraction Replaceable End-Use Category Nominal Minimum Lighting Level {W} Nominal Maximum Lighting Level {W}
1 BASEMENT_LIGHTS LTG_SCH_OFFICE BASEMENT 2779.43 149.6 28553.717 10.273 190.864 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 28553.717
2 CORE_BOTTOM_LIGHTS LTG_SCH_OFFICE CORE_BOTTOM 2496.12 134.4 25643.245 10.273 190.864 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 25643.245
3 CORE_MID_LIGHTS LTG_SCH_OFFICE CORE_MID 2496.12 134.4 25643.245 10.273 190.864 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 25643.245
4 CORE_TOP_LIGHTS LTG_SCH_OFFICE CORE_TOP 2496.12 134.4 25643.245 10.273 190.864 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 25643.245
5 PERIMETER_BOT_ZN_3_LIGHTS LTG_SCH_OFFICE PERIMETER_BOT_ZN_3 313.41 16.9 3219.765 10.273 190.864 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 3219.765
6 PERIMETER_BOT_ZN_2_LIGHTS LTG_SCH_OFFICE PERIMETER_BOT_ZN_2 201.98 10.9 2074.939 10.273 190.864 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 2074.939
7 PERIMETER_BOT_ZN_1_LIGHTS LTG_SCH_OFFICE PERIMETER_BOT_ZN_1 313.42 16.9 3219.836 10.273 190.864 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 3219.836
8 PERIMETER_BOT_ZN_4_LIGHTS LTG_SCH_OFFICE PERIMETER_BOT_ZN_4 201.98 10.9 2074.939 10.273 190.864 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 2074.939
9 PERIMETER_MID_ZN_3_LIGHTS LTG_SCH_OFFICE PERIMETER_MID_ZN_3 313.41 16.9 3219.765 10.273 190.864 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 3219.765
10 PERIMETER_MID_ZN_2_LIGHTS LTG_SCH_OFFICE PERIMETER_MID_ZN_2 201.98 10.9 2074.939 10.273 190.864 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 2074.939
11 PERIMETER_MID_ZN_1_LIGHTS LTG_SCH_OFFICE PERIMETER_MID_ZN_1 313.42 16.9 3219.836 10.273 190.864 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 3219.836
12 PERIMETER_MID_ZN_4_LIGHTS LTG_SCH_OFFICE PERIMETER_MID_ZN_4 201.98 10.9 2074.939 10.273 190.864 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 2074.939
13 PERIMETER_TOP_ZN_3_LIGHTS LTG_SCH_OFFICE PERIMETER_TOP_ZN_3 313.41 16.9 3219.765 10.273 190.864 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 3219.765
14 PERIMETER_TOP_ZN_2_LIGHTS LTG_SCH_OFFICE PERIMETER_TOP_ZN_2 201.98 10.9 2074.939 10.273 190.864 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 2074.939
15 PERIMETER_TOP_ZN_1_LIGHTS LTG_SCH_OFFICE PERIMETER_TOP_ZN_1 313.42 16.9 3219.836 10.273 190.864 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 3219.836
16 PERIMETER_TOP_ZN_4_LIGHTS LTG_SCH_OFFICE PERIMETER_TOP_ZN_4 201.98 10.9 2074.939 10.273 190.864 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 2074.939
17 DATACENTER_BASEMENT_LIGHTS LTG_SCH_OFFICE DATACENTER_BASEMENT_ZN_6 783.68 42.2 8050.927 10.273 190.864 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 8050.927
18 DATACENTER_BOT_LIGHTS LTG_SCH_DATACENTER DATACENTER_BOT_ZN_6 36.20 1.9 647.068 17.873 332.067 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 647.068
19 DATACENTER_MID_LIGHTS LTG_SCH_DATACENTER DATACENTER_MID_ZN_6 36.20 1.9 647.068 17.873 332.067 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 647.068
20 DATACENTER_TOP_LIGHTS LTG_SCH_DATACENTER DATACENTER_TOP_ZN_6 36.20 1.9 647.068 17.873 332.067 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 647.068


ElectricEquipment Internal Gains Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Equipment Level {W} Equipment/Floor Area {W/m2} Equipment per person {W/person} Fraction Latent Fraction Radiant Fraction Lost Fraction Convected End-Use SubCategory Nominal Minimum Equipment Level {W} Nominal Maximum Equipment Level {W}
1 BASEMENT_MISCPLUG_EQUIP ALWAYS_ON BASEMENT 2779.43 149.6 13457.544 4.842 89.956 0.000 0.500 0.000 0.500 MiscPlug 13457.544 13457.544
2 CORE_BOTTOM_MISCPLUG_EQUIP BLDG_EQUIP_SCH CORE_BOTTOM 2496.12 134.4 20142.877 8.070 149.925 0.000 0.500 0.000 0.500 MiscPlug 0.000 20142.877
3 CORE_MID_MISCPLUG_EQUIP BLDG_EQUIP_SCH CORE_MID 2496.12 134.4 20142.800 8.070 149.924 0.000 0.500 0.000 0.500 MiscPlug 0.000 20142.800
4 CORE_TOP_MISCPLUG_EQUIP BLDG_EQUIP_SCH CORE_TOP 2496.12 134.4 20142.800 8.070 149.924 0.000 0.500 0.000 0.500 MiscPlug 0.000 20142.800
5 PERIMETER_BOT_ZN_3_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_BOT_ZN_3 313.41 16.9 2529.242 8.070 149.931 0.000 0.500 0.000 0.500 MiscPlug 0.000 2529.242
6 PERIMETER_BOT_ZN_2_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_BOT_ZN_2 201.98 10.9 1629.940 8.070 149.931 0.000 0.500 0.000 0.500 MiscPlug 0.000 1629.940
7 PERIMETER_BOT_ZN_1_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_BOT_ZN_1 313.42 16.9 2529.281 8.070 149.930 0.000 0.500 0.000 0.500 MiscPlug 0.000 2529.281
8 PERIMETER_BOT_ZN_4_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_BOT_ZN_4 201.98 10.9 1629.929 8.070 149.930 0.000 0.500 0.000 0.500 MiscPlug 0.000 1629.929
9 PERIMETER_MID_ZN_3_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_MID_ZN_3 313.41 16.9 2529.242 8.070 149.931 0.000 0.500 0.000 0.500 MiscPlug 0.000 2529.242
10 PERIMETER_MID_ZN_2_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_MID_ZN_2 201.98 10.9 1629.940 8.070 149.931 0.000 0.500 0.000 0.500 MiscPlug 0.000 1629.940
11 PERIMETER_MID_ZN_1_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_MID_ZN_1 313.42 16.9 2529.281 8.070 149.930 0.000 0.500 0.000 0.500 MiscPlug 0.000 2529.281
12 PERIMETER_MID_ZN_4_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_MID_ZN_4 201.98 10.9 1629.929 8.070 149.930 0.000 0.500 0.000 0.500 MiscPlug 0.000 1629.929
13 PERIMETER_TOP_ZN_3_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_TOP_ZN_3 313.41 16.9 2529.242 8.070 149.931 0.000 0.500 0.000 0.500 MiscPlug 0.000 2529.242
14 PERIMETER_TOP_ZN_2_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_TOP_ZN_2 201.98 10.9 1629.940 8.070 149.931 0.000 0.500 0.000 0.500 MiscPlug 0.000 1629.940
15 PERIMETER_TOP_ZN_1_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_TOP_ZN_1 313.42 16.9 2529.281 8.070 149.930 0.000 0.500 0.000 0.500 MiscPlug 0.000 2529.281
16 PERIMETER_TOP_ZN_4_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_TOP_ZN_4 201.98 10.9 1629.929 8.070 149.930 0.000 0.500 0.000 0.500 MiscPlug 0.000 1629.929
17 DATACENTER_BASEMENT_MISCPLUG_EQUIP DATACENTER_EQUIP_SCH DATACENTER_BASEMENT_ZN_6 783.68 42.2 379632.522 484.423 9000.000 0.000 0.100 0.000 0.900 DataCenterPlugLoads 94908.130 379632.522
18 DATACENTER_BOT_MISCPLUG_EQUIP DATACENTER_EQUIP_SCH DATACENTER_BOT_ZN_6 36.20 1.9 7794.422 215.299 4000.000 0.000 0.100 0.000 0.900 DataCenterPlugLoads 1948.606 7794.422
19 DATACENTER_MID_MISCPLUG_EQUIP DATACENTER_EQUIP_SCH DATACENTER_MID_ZN_6 36.20 1.9 7794.422 215.299 4000.000 0.000 0.100 0.000 0.900 DataCenterPlugLoads 1948.606 7794.422
20 DATACENTER_TOP_MISCPLUG_EQUIP DATACENTER_EQUIP_SCH DATACENTER_TOP_ZN_6 36.20 1.9 7794.422 215.299 4000.000 0.000 0.100 0.000 0.900 DataCenterPlugLoads 1948.606 7794.422


Construction CTF

Construction Name Index #Layers #CTFs Time Step {hours} ThermalConductance {w/m2-K} OuterThermalAbsorptance InnerThermalAbsorptance OuterSolarAbsorptance InnerSolarAbsorptance Roughness
1 SWINGING DOOR_CON 1 1 1 0.167 2.839 0.900 0.900 0.700 0.700 MediumRough
2 INTERIORFURNISHINGS 2 1 9 0.167 0.8000 0.900 0.900 0.700 0.700 MediumSmooth
3 DROPCEILING 4 1 3 0.167 4.488 0.900 0.900 0.700 0.700 MediumSmooth
4 INT_WALL 7 2 4 0.167 6.299 0.900 0.900 0.700 0.700 Smooth
5 EXT_SLAB_8IN_WITH_CARPET 8 2 7 0.167 3.285 0.900 0.900 0.700 0.700 MediumRough
6 INT_SLAB_FLOOR 12 2 7 0.167 3.839 0.900 0.900 0.700 0.700 MediumRough
7 INT_SLAB_CEILING 13 2 7 0.167 3.839 0.900 0.900 0.700 0.700 VeryRough
8 NONRES_ROOF 17 3 3 0.167 0.1864 0.900 0.900 0.700 0.700 Rough
9 NONRES_EXT_WALL_GRD 20 3 9 0.167 0.8952 0.900 0.900 0.700 0.700 MediumRough
10 NONRES_EXT_WALL_MID 21 3 9 0.167 0.8506 0.900 0.900 0.700 0.700 MediumRough
11 NONRES_EXT_WALL_TOP 22 3 9 0.167 1.077 0.900 0.900 0.700 0.700 MediumRough
12 BASEMENT_WALL_EAST_CFACTOR 39 2 7 0.167 0.3542 0.000 0.900 0.000 0.700 MediumRough
13 BASEMENT_WALL_SOUTH_CFACTOR 40 2 7 0.167 0.3542 0.000 0.900 0.000 0.700 MediumRough
14 BASEMENT_WALL_NORTH_CFACTOR 41 2 7 0.167 0.3542 0.000 0.900 0.000 0.700 MediumRough
15 DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR 42 2 7 0.167 0.3542 0.000 0.900 0.000 0.700 MediumRough
16 DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR 43 2 7 0.167 0.3542 0.000 0.900 0.000 0.700 MediumRough
17 DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR 44 2 7 0.167 0.3542 0.000 0.900 0.000 0.700 MediumRough


Material CTF Summary

Material Name Thickness {m} Conductivity {w/m-K} Density {kg/m3} Specific Heat {J/kg-K} ThermalResistance {m2-K/w}
1 OPAQUE DOOR PANEL_CON 0.0000 0.000 0.000 0.000 0.3522
2 STD WOOD 6INCH 0.1500 0.120 540.000 1210.000 1.250
3 AC02 ACOUSTIC CEILING 0.0127 0.057 288.000 1339.000 0.2228
4 G01 13MM GYPSUM BOARD 0.0127 0.160 800.000 1090.000 0.7937E-01
5 G01 13MM GYPSUM BOARD 0.0127 0.160 800.000 1090.000 0.7937E-01
6 200MM NORMALWEIGHT CONCRETE FLOOR 0.2032 2.310 2322.000 832.000 0.8797E-01
7 CP02 CARPET PAD 0.0000 0.000 0.000 0.000 0.2165
8 100MM NORMALWEIGHT CONCRETE FLOOR 0.1016 2.310 2322.000 832.000 0.4398E-01
9 CP02 CARPET PAD 0.0000 0.000 0.000 0.000 0.2165
10 CP02 CARPET PAD 0.0000 0.000 0.000 0.000 0.2165
11 100MM NORMALWEIGHT CONCRETE FLOOR 0.1016 2.310 2322.000 832.000 0.4398E-01
12 F13 BUILT-UP ROOFING 0.0095 0.160 1120.000 1460.000 0.5938E-01
13 NONRES_ROOF_INSULATION 0.0000 0.000 0.000 0.000 5.307
14 F08 METAL SURFACE 0.0008 45.280 7824.000 500.000 0.1767E-04
15 200MM NORMALWEIGHT CONCRETE WALL 0.2032 2.310 2322.000 832.000 0.8797E-01
16 NONRES_EXTERIOR_WALL_INSULATION_GRD 0.0000 0.000 0.000 0.000 0.9497
17 G01 13MM GYPSUM BOARD 0.0127 0.160 800.000 1090.000 0.7937E-01
18 200MM NORMALWEIGHT CONCRETE WALL 0.2032 2.310 2322.000 832.000 0.8797E-01
19 NONRES_EXTERIOR_WALL_INSULATION_MID 0.0000 0.000 0.000 0.000 1.008
20 G01 13MM GYPSUM BOARD 0.0127 0.160 800.000 1090.000 0.7937E-01
21 200MM NORMALWEIGHT CONCRETE WALL 0.2032 2.310 2322.000 832.000 0.8797E-01
22 NONRES_EXTERIOR_WALL_INSULATION_TOP 0.0000 0.000 0.000 0.000 0.7608
23 G01 13MM GYPSUM BOARD 0.0127 0.160 800.000 1090.000 0.7937E-01
24 ~FC_Insulation_1 0.0000 0.000 0.000 0.000 2.747
25 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
26 ~FC_Insulation_2 0.0000 0.000 0.000 0.000 2.747
27 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
28 ~FC_Insulation_3 0.0000 0.000 0.000 0.000 2.747
29 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
30 ~FC_Insulation_4 0.0000 0.000 0.000 0.000 2.747
31 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
32 ~FC_Insulation_5 0.0000 0.000 0.000 0.000 2.747
33 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
34 ~FC_Insulation_6 0.0000 0.000 0.000 0.000 2.747
35 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01


CTF

Time Outside Cross Inside Flux (except final one)
1 1 0.0000000 0.0000000 -0.0000000 -0.0000000
2 0 2.8391315 2.8391315 2.8391315  
3 9 -0.27580628E-02 0.97439125E-12 -0.27580628E-02 0.28516790E-03
4 8 0.73590997E-01 0.21837543E-08 0.73590997E-01 -0.77836043E-02
5 7 -0.82599318 0.23162835E-06 -0.82599318 0.89703933E-01
6 6 5.1113916 0.48671053E-05 5.1113916 -0.57224845
7 5 -19.214933 0.30163627E-04 -19.214933 2.2266322
8 4 45.557404 0.63181060E-04 45.557404 -5.4853312
9 3 -68.275533 0.44785456E-04 -68.275533 8.5710568
10 2 62.555368 0.93952058E-05 62.555368 -8.2111738
11 1 -31.904423 0.39200004E-06 -31.904423 4.3886678
12 0 6.9260389 0.77047546E-09 6.9260389  
13 3 -0.21589802E-09 0.15643069E-09 -0.21589802E-09 0.12999471E-21
14 2 0.50772448E-02 0.30006816E-02 0.50772448E-02 -0.13693132E-08
15 1 -2.5944910 1.4597758 -2.5944910 0.76344767E-02
16 0 7.0433378 2.9911476 7.0433378  
17 4 0.68458728E-09 0.26079551E-09 0.68458728E-09 -0.34507121E-18
18 3 -0.72180374E-03 0.24295686E-03 -0.72180374E-03 0.69691454E-09
19 2 0.83054762 0.27682775 0.83054762 -0.35168967E-03
20 1 -12.650482 3.3590720 -12.650482 0.19281313
21 0 16.907513 1.4507143 16.907513  
22 7 -0.18651654E-16 -0.16428647E-15 -0.26578847E-08 -0.25364002E-17
23 6 0.67402962E-01 0.99142722E-07 0.38101547E-02 -0.76639482E-03
24 5 -1.8580732 0.49502125E-04 -0.10651409 0.21891119E-01
25 4 18.220105 0.12801333E-02 1.0775450 -0.22586539
26 3 -79.928293 0.66708484E-02 -4.9803755 1.0625663
27 2 166.43177 0.75131194E-02 11.128837 -2.4125483
28 1 -159.97298 0.18548900E-02 -11.587784 2.5494418
29 0 57.057412 0.52755123E-04 4.4818272  
30 7 0.43260499E-16 0.34524919E-16 0.52793240E-17 0.0000000
31 6 0.69434179E-09 0.98085174E-11 0.18162501E-10 -0.40870994E-12
32 5 -0.12888762E-04 0.28373718E-06 -0.16918523E-06 0.92361873E-08
33 4 0.25174112E-01 0.33697681E-03 0.22646198E-03 -0.31467795E-04
34 3 -3.7600775 0.27170599E-01 -0.48495626E-01 0.94171705E-02
35 2 51.553741 0.22121684 1.2284947 -0.25833933
36 1 -128.86110 0.21944682 -5.1479470 1.1228340
37 0 81.526494 0.16043334E-01 4.4519351  
38 7 0.52793240E-17 0.34524919E-16 0.43260499E-16 0.0000000
39 6 0.18162501E-10 0.98085174E-11 0.69434179E-09 -0.40870994E-12
40 5 -0.16918523E-06 0.28373718E-06 -0.12888762E-04 0.92361873E-08
41 4 0.22646198E-03 0.33697681E-03 0.25174112E-01 -0.31467795E-04
42 3 -0.48495626E-01 0.27170599E-01 -3.7600775 0.94171705E-02
43 2 1.2284947 0.22121684 51.553741 -0.25833933
44 1 -5.1479470 0.21944682 -128.86110 1.1228340
45 0 4.4519351 0.16043334E-01 81.526494  
46 3 -0.62854340E-06 0.84784826E-09 -0.38512804E-05 0.91756347E-17
47 2 0.78257096 0.11428808E-02 1.0614277 -0.73836085E-06
48 1 -21.991499 0.76199851E-01 -6.3161914 0.20349372
49 0 21.357363 0.71091016E-01 5.4032014  
50 9 -0.25194710E-14 0.31545203E-16 -0.15133332E-09 0.44281407E-16
51 8 0.22101568E-07 0.12077324E-12 0.38017447E-03 -0.25130244E-09
52 7 -0.12312625E-01 0.62550027E-08 -0.23188143E-01 0.13999903E-03
53 6 0.40728147 0.21773539E-05 0.47373573 -0.47705255E-02
54 5 -5.2094091 0.81341902E-04 -4.4538940 0.63417525E-01
55 4 33.086216 0.66572093E-03 21.489723 -0.42322968
56 3 -111.40360 0.14515221E-02 -55.721658 1.5177572
57 2 197.30704 0.81680373E-03 77.964377 -2.9035099
58 1 -171.22951 0.87228510E-04 -55.280715 2.7467265
59 0 57.057407 0.49677855E-06 15.554344  
60 9 -0.24471812E-14 0.33150161E-16 -0.15341684E-09 0.41895861E-16
61 8 0.22394247E-07 0.11501389E-12 0.38323131E-03 -0.25463030E-09
62 7 -0.12403778E-01 0.59379868E-08 -0.23319368E-01 0.14103548E-03
63 6 0.40975819 0.20644311E-05 0.47584355 -0.47997200E-02
64 5 -5.2335779 0.77040749E-04 -4.4700764 0.63717207E-01
65 4 33.193114 0.62990908E-03 21.552961 -0.42464900
66 3 -111.63102 0.13722529E-02 -55.846672 1.5210429
67 2 197.53241 0.77160263E-03 78.079059 -2.9070889
68 1 -171.31275 0.82342669E-04 -55.314112 2.7481854
69 0 57.057407 0.46858505E-06 15.548868  
70 9 -0.15654789E-15 0.36780279E-16 -0.14275499E-09 -0.53833073E-18
71 8 0.20895136E-07 0.14393424E-12 0.36742668E-03 -0.23758489E-09
72 7 -0.11931991E-01 0.75543961E-08 -0.22640018E-01 0.13567108E-03
73 6 0.39693859 0.26436989E-05 0.46492102 -0.46486079E-02
74 5 -5.1084706 0.99216708E-04 -4.3861655 0.62165936E-01
75 4 32.639712 0.81537030E-03 21.224928 -0.41730137
76 3 -110.45353 0.17843548E-02 -55.198128 1.5040313
77 2 196.36533 0.10073836E-02 77.484335 -2.8885557
78 1 -170.88163 0.10790658E-03 -55.141337 2.7406295
79 0 57.057407 0.61658484E-06 15.577537  
80 7 -0.11729247E-08 -0.12287178E-15 0.68000855E-14 -0.85819789E-16
81 6 0.99010087E-05 0.68275672E-08 0.31776201E-02 -0.26656541E-04
82 5 -0.71743827E-03 0.40498262E-05 -0.22302824 0.19500041E-02
83 4 0.16534150E-01 0.18445051E-03 4.8179460 -0.45153479E-01
84 3 -0.14527752 0.14677644E-02 -37.955880 0.39792938
85 2 0.51595076 0.24428280E-02 116.35639 -1.4162330
86 1 -0.74475336 0.74501918E-03 -143.83221 2.0478056
87 0 0.36311555 0.17917760E-04 60.838472  
88 7 -0.11729247E-08 -0.12287178E-15 0.68000855E-14 -0.85819789E-16
89 6 0.99010087E-05 0.68275672E-08 0.31776201E-02 -0.26656541E-04
90 5 -0.71743827E-03 0.40498262E-05 -0.22302824 0.19500041E-02
91 4 0.16534150E-01 0.18445051E-03 4.8179460 -0.45153479E-01
92 3 -0.14527752 0.14677644E-02 -37.955880 0.39792938
93 2 0.51595076 0.24428280E-02 116.35639 -1.4162330
94 1 -0.74475336 0.74501918E-03 -143.83221 2.0478056
95 0 0.36311555 0.17917760E-04 60.838472  
96 7 -0.11729247E-08 -0.12287178E-15 0.68000855E-14 -0.85819789E-16
97 6 0.99010087E-05 0.68275672E-08 0.31776201E-02 -0.26656541E-04
98 5 -0.71743827E-03 0.40498262E-05 -0.22302824 0.19500041E-02
99 4 0.16534150E-01 0.18445051E-03 4.8179460 -0.45153479E-01
100 3 -0.14527752 0.14677644E-02 -37.955880 0.39792938
101 2 0.51595076 0.24428280E-02 116.35639 -1.4162330
102 1 -0.74475336 0.74501918E-03 -143.83221 2.0478056
103 0 0.36311555 0.17917760E-04 60.838472  
104 7 -0.11729247E-08 -0.12287178E-15 0.68000855E-14 -0.85819789E-16
105 6 0.99010087E-05 0.68275672E-08 0.31776201E-02 -0.26656541E-04
106 5 -0.71743827E-03 0.40498262E-05 -0.22302824 0.19500041E-02
107 4 0.16534150E-01 0.18445051E-03 4.8179460 -0.45153479E-01
108 3 -0.14527752 0.14677644E-02 -37.955880 0.39792938
109 2 0.51595076 0.24428280E-02 116.35639 -1.4162330
110 1 -0.74475336 0.74501918E-03 -143.83221 2.0478056
111 0 0.36311555 0.17917760E-04 60.838472  
112 7 -0.11729247E-08 -0.12287178E-15 0.68000855E-14 -0.85819789E-16
113 6 0.99010087E-05 0.68275672E-08 0.31776201E-02 -0.26656541E-04
114 5 -0.71743827E-03 0.40498262E-05 -0.22302824 0.19500041E-02
115 4 0.16534150E-01 0.18445051E-03 4.8179460 -0.45153479E-01
116 3 -0.14527752 0.14677644E-02 -37.955880 0.39792938
117 2 0.51595076 0.24428280E-02 116.35639 -1.4162330
118 1 -0.74475336 0.74501918E-03 -143.83221 2.0478056
119 0 0.36311555 0.17917760E-04 60.838472  
120 7 -0.11729247E-08 -0.12287178E-15 0.68000855E-14 -0.85819789E-16
121 6 0.99010087E-05 0.68275672E-08 0.31776201E-02 -0.26656541E-04
122 5 -0.71743827E-03 0.40498262E-05 -0.22302824 0.19500041E-02
123 4 0.16534150E-01 0.18445051E-03 4.8179460 -0.45153479E-01
124 3 -0.14527752 0.14677644E-02 -37.955880 0.39792938
125 2 0.51595076 0.24428280E-02 116.35639 -1.4162330
126 1 -0.74475336 0.74501918E-03 -143.83221 2.0478056
127 0 0.36311555 0.17917760E-04 60.838472  


WindowConstruction

Construction Name Index #Layers Roughness Conductance {W/m2-K} Conductance (Before Adjusted) {W/m2-K} Convection Coefficient Adjustment Ratio SHGC Solar Transmittance at Normal Incidence Visible Transmittance at Normal Incidence
1 WINDOW_U_0.419_SHGC_EAST_0.4 35 1 VerySmooth 2.381 2.381 1.000 0.401    
2 WINDOW_U_0.419_SHGC_SOUTH_0.4 36 1 VerySmooth 2.381 2.381 1.000 0.401    
3 WINDOW_U_0.419_SHGC_WEST_0.4 37 1 VerySmooth 2.381 2.381 1.000 0.401    
4 WINDOW_U_0.419_SHGC_NORTH_0.4 38 1 VerySmooth 2.381 2.381 1.000 0.401    


WindowMaterial:Glazing

Material Name Optical Data Type Spectral Data Set Name Thickness {m} Solar Transmittance Front Solar Reflectance Back Solar Reflectance Visible Transmittance Front Visible Reflectance Back Visible Reflectance Infrared Transmittance Front Thermal Emissivity Back Thermal Emissivity Conductivity {W/m-K} Dirt Factor Solar Diffusing
1 GLAZING LAYER EAST SpectralAverage   3.03930E-002 0.31435 0.47506 0.47506 0.44000 0.13397 0.17027 0.00000 0.84000 0.84000 0.12237 1.00000 No
2 GLAZING LAYER SOUTH SpectralAverage   3.03930E-002 0.31435 0.47506 0.47506 0.44000 0.13397 0.17027 0.00000 0.84000 0.84000 0.12237 1.00000 No
3 GLAZING LAYER WEST SpectralAverage   3.03930E-002 0.31435 0.47506 0.47506 0.44000 0.13397 0.17027 0.00000 0.84000 0.84000 0.12237 1.00000 No
4 GLAZING LAYER NORTH SpectralAverage   3.03930E-002 0.31435 0.47506 0.47506 0.44000 0.13397 0.17027 0.00000 0.84000 0.84000 0.12237 1.00000 No


Shadowing/Sun Position Calculations Annual Simulations

Shading Calculation Method Shading Calculation Update Frequency Method Shading Calculation Update Frequency {days} Maximum Figures in Shadow Overlap Calculations {} Polygon Clipping Algorithm Pixel Counting Resolution Sky Diffuse Modeling Algorithm Output External Shading Calculation Results Disable Self-Shading Within Shading Zone Groups Disable Self-Shading From Shading Zone Groups to Other Zones
1 PolygonClipping Periodic 30 15000 SutherlandHodgman 512 SimpleSkyDiffuseModeling No No No


Enclosure/Window Adjacency Daylighting Counts

Enclosure Name Number of Exterior Windows Number of Exterior Windows in Adjacent Enclosures
1 PERIMETER_BOT_ZN_3 5 0
2 PERIMETER_BOT_ZN_2 3 0
3 PERIMETER_BOT_ZN_1 5 0
4 PERIMETER_BOT_ZN_4 3 0
5 PERIMETER_MID_ZN_3 1 0
6 PERIMETER_MID_ZN_2 1 0
7 PERIMETER_MID_ZN_1 1 0
8 PERIMETER_MID_ZN_4 1 0
9 PERIMETER_TOP_ZN_3 1 0
10 PERIMETER_TOP_ZN_2 1 0
11 PERIMETER_TOP_ZN_1 1 0
12 PERIMETER_TOP_ZN_4 1 0


Enclosure/Window Adjacency Daylighting Matrix

Enclosure Name Number of Adjacent Enclosures with Windows Adjacent Enclosure Names - 1st 100 (max)
1 PERIMETER_BOT_ZN_3 0  
2 PERIMETER_BOT_ZN_2 0  
3 PERIMETER_BOT_ZN_1 0  
4 PERIMETER_BOT_ZN_4 0  
5 PERIMETER_MID_ZN_3 0  
6 PERIMETER_MID_ZN_2 0  
7 PERIMETER_MID_ZN_1 0  
8 PERIMETER_MID_ZN_4 0  
9 PERIMETER_TOP_ZN_3 0  
10 PERIMETER_TOP_ZN_2 0  
11 PERIMETER_TOP_ZN_1 0  
12 PERIMETER_TOP_ZN_4 0  


Water Heater Information

Type Name Volume {m3} Maximum Capacity {W} Standard Rated Recovery Efficiency Standard Rated Energy Factor
1 WaterHeater:Mixed SWHSYS1 WATER HEATER 1.1356 87921.3 0.481 5.5005E-002


Surface Convection Parameters

Surface Name Outside Model Assignment Outside Area [m2] Outside Perimeter [m] Outside Height [m] Inside Model Assignment Inside Height [m] Inside Perimeter Envelope [m] Inside Hydraulic Diameter [m] Window Wall Ratio Window Location Near Radiant {Yes/No} Has Active HVAC {Yes/No}
1 BASEMENT_WALL_EAST 0 0.00 0.00 0.00 0 2.44 0.00 52.56 -999.00 0 No No
2 BASEMENT_WALL_SOUTH 0 0.00 0.00 0.00 0 2.44 0.00 52.56 -999.00 0 No No
3 BASEMENT_WALL_NORTH 0 0.00 0.00 0.00 0 2.44 0.00 52.56 -999.00 0 No No
4 BASEMENT_WALL_WEST 0 0.00 0.00 0.00 0 2.44 0.00 52.56 -999.00 0 No No
5 BASEMENT_FLOOR 0 0.00 0.00 0.00 0 2.44 0.00 52.56 -999.00 0 No No
6 PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.44 0.00 52.56 -999.00 0 No No
7 PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.44 0.00 52.56 -999.00 0 No No
8 CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.44 0.00 52.56 -999.00 0 No No
9 PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.44 0.00 52.56 -999.00 0 No No
10 BASEMENT_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.44 0.00 52.56 -999.00 0 No No
11 CORE_BOT_ZN_5_WALL_SOUTH 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
12 CORE_BOT_ZN_5_WALL_WEST 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
13 CORE_BOT_ZN_5_WALL_NORTH 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
14 CORE_BOT_ZN_5_WALL_EAST 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
15 DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
16 CORE_BOT_ZN_5_FLOOR 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
17 CORE_BOT_ZN_5_CEILING 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
18 CORE_BOTTOM_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
19 CORE_MID_ZN_5_WALL_SOUTH 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
20 CORE_MID_ZN_5_WALL_WEST 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
21 CORE_MID_ZN_5_WALL_NORTH 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
22 CORE_MID_ZN_5_WALL_EAST 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
23 CORE_MID_ZN_5_FLOOR 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
24 CORE_MID_ZN_5_CEILING 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
25 CORE_MID_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
26 CORE_TOP_ZN_5_WALL_SOUTH 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
27 CORE_TOP_ZN_5_WALL_WEST 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
28 CORE_TOP_ZN_5_WALL_NORTH 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
29 CORE_TOP_ZN_5_WALL_EAST 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
30 CORE_TOP_ZN_5_FLOOR 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
31 CORE_TOP_ZN_5_CEILING 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
32 CORE_TOP_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
33 PERIMETER_BOT_ZN_3_WALL_NORTH 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.58 3 No No
34 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.58 5 No No
35 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.58 5 No No
36 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.58 5 No No
37 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.58 5 No No
38 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.58 5 No No
39 PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.58 0 No No
40 PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.58 0 No No
41 PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.58 0 No No
42 PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.58 0 No No
43 PERIMETER_BOT_ZN_3_WALL_WEST 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
44 CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
45 PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
46 DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
47 PERIMETER_BOT_ZN_3_FLOOR 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
48 DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
49 PERIMETER_BOT_ZN_3_CEILING 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
50 PERIMETER_BOT_ZN_3_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
51 PERIMETER_BOT_ZN_2_WALL_EAST 0 579.48 250.73 37.50 0 2.74 48.74 7.58 0.58 3 No No
52 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 0 579.48 250.73 37.50 0 2.74 48.74 7.58 0.58 5 No No
53 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 0 579.48 250.73 37.50 0 2.74 48.74 7.58 0.58 5 No No
54 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 0 579.48 250.73 37.50 0 2.74 48.74 7.58 0.58 5 No No
55 PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 0 579.48 250.73 37.50 0 2.74 48.74 7.58 0.58 0 No No
56 PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 0 579.48 250.73 37.50 0 2.74 48.74 7.58 0.58 0 No No
57 PERIMETER_BOT_ZN_2_WALL_NORTH 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
58 CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
59 PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
60 PERIMETER_BOT_ZN_2_FLOOR 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
61 PERIMETER_BOT_ZN_2_CEILING 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
62 PERIMETER_BOT_ZN_2_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
63 PERIMETER_BOT_ZN_1_WALL_SOUTH 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.58 3 No No
64 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.58 5 No No
65 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.58 5 No No
66 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.58 5 No No
67 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.58 5 No No
68 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.58 5 No No
69 PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.58 0 No No
70 PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.58 0 No No
71 PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.58 0 No No
72 PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.58 0 No No
73 PERIMETER_BOT_ZN_1_WALL_EAST 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
74 DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
75 PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
76 CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
77 DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
78 PERIMETER_BOT_ZN_1_FLOOR 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
79 PERIMETER_BOT_ZN_1_CEILING 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
80 PERIMETER_BOT_ZN_1_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
81 PERIMETER_BOT_ZN_4_WALL_WEST 0 579.48 172.48 37.50 0 2.74 48.74 7.58 0.58 3 No No
82 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 0 579.48 172.48 37.50 0 2.74 48.74 7.58 0.58 5 No No
83 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 0 579.48 172.48 37.50 0 2.74 48.74 7.58 0.58 5 No No
84 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 0 579.48 172.48 37.50 0 2.74 48.74 7.58 0.58 5 No No
85 PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 0 579.48 172.48 37.50 0 2.74 48.74 7.58 0.58 0 No No
86 PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 0 579.48 172.48 37.50 0 2.74 48.74 7.58 0.58 0 No No
87 PERIMETER_BOT_ZN_4_WALL_SOUTH 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
88 DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
89 PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
90 PERIMETER_BOT_ZN_4_FLOOR 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
91 PERIMETER_BOT_ZN_4_CEILING 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
92 PERIMETER_BOT_ZN_4_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
93 PERIMETER_MID_ZN_3_WALL_NORTH 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.58 3 No No
94 PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.58 5 No No
95 PERIMETER_MID_ZN_3_WALL_WEST 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
96 CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
97 PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
98 DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
99 PERIMETER_MID_ZN_3_FLOOR 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
100 PERIMETER_MID_ZN_3_CEILING 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
101 PERIMETER_MID_ZN_3_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
102 PERIMETER_MID_ZN_2_WALL_EAST 0 579.48 250.73 37.50 0 2.74 48.74 7.58 0.58 3 No No
103 PERIMETER_MID_ZN_2_WALL_EAST_WINDOW 0 579.48 250.73 37.50 0 2.74 48.74 7.58 0.58 5 No No
104 PERIMETER_MID_ZN_2_WALL_NORTH 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
105 CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
106 PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
107 PERIMETER_MID_ZN_2_FLOOR 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
108 PERIMETER_MID_ZN_2_CEILING 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
109 PERIMETER_MID_ZN_2_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
110 PERIMETER_MID_ZN_1_WALL_EAST 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
111 PERIMETER_MID_ZN_1_WALL_SOUTH 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.58 3 No No
112 PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.58 5 No No
113 DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
114 PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
115 CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
116 PERIMETER_MID_ZN_1_FLOOR 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
117 PERIMETER_MID_ZN_1_CEILING 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
118 PERIMETER_MID_ZN_1_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
119 PERIMETER_MID_ZN_4_WALL_WEST 0 579.48 172.48 37.50 0 2.74 48.74 7.58 0.58 3 No No
120 PERIMETER_MID_ZN_4_WALL_WEST_WINDOW 0 579.48 172.48 37.50 0 2.74 48.74 7.58 0.58 5 No No
121 PERIMETER_MID_ZN_4_WALL_SOUTH 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
122 DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
123 PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
124 PERIMETER_MID_ZN_4_FLOOR 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
125 PERIMETER_MID_ZN_4_CEILING 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
126 PERIMETER_MID_ZN_4_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
127 PERIMETER_TOP_ZN_3_WALL_NORTH 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.58 3 No No
128 PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.58 5 No No
129 PERIMETER_TOP_ZN_3_WALL_WEST 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
130 CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
131 PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
132 DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
133 PERIMETER_TOP_ZN_3_FLOOR 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
134 PERIMETER_TOP_ZN_3_CEILING 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
135 PERIMETER_TOP_ZN_3_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
136 PERIMETER_TOP_ZN_2_WALL_EAST 0 579.48 250.73 37.50 0 2.74 48.74 7.58 0.58 3 No No
137 PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW 0 579.48 250.73 37.50 0 2.74 48.74 7.58 0.58 5 No No
138 PERIMETER_TOP_ZN_2_WALL_NORTH 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
139 CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
140 INT-PER3S-NE-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
141 PERIMETER_TOP_ZN_2_FLOOR 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
142 PERIMETER_TOP_ZN_2_CEILING 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
143 PERIMETER_TOP_ZN_2_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
144 PERIMETER_TOP_ZN_1_WALL_SOUTH 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.58 3 No No
145 PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.58 5 No No
146 INT-PER3S-NE 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
147 DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
148 PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
149 CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
150 PERIMETER_TOP_ZN_1_FLOOR 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
151 PERIMETER_TOP_ZN_1_CEILING 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
152 PERIMETER_TOP_ZN_1_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
153 PERIMETER_TOP_ZN_4_WALL_WEST 0 579.48 172.48 37.50 0 2.74 48.74 7.58 0.58 3 No No
154 PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW 0 579.48 172.48 37.50 0 2.74 48.74 7.58 0.58 5 No No
155 PERIMETER_TOP_ZN_4_WALL_SOUTH 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
156 DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
157 PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
158 PERIMETER_TOP_ZN_4_FLOOR 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
159 PERIMETER_TOP_ZN_4_CEILING 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
160 PERIMETER_TOP_ZN_4_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
161 GROUNDFLOOR_PLENUM_WALL_NORTH 0 869.22 250.73 37.50 0 1.22 243.69 58.49 0.00 0 No No
162 GROUNDFLOOR_PLENUM_WEST 0 579.48 172.48 37.50 0 1.22 243.69 58.49 0.00 0 No No
163 GROUNDFLOOR_PLENUM_WALL_SOUTH 0 869.22 221.21 37.50 0 1.22 243.69 58.49 0.00 0 No No
164 GROUNDFLOOR_PLENUM_WALL_EAST 0 579.48 250.73 37.50 0 1.22 243.69 58.49 0.00 0 No No
165 iz-CORE_BOT_ZN_5_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
166 iz-PERIMETER_BOT_ZN_3_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
167 iz-PERIMETER_BOT_ZN_2_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
168 iz-PERIMETER_BOT_ZN_1_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
169 iz-PERIMETER_BOT_ZN_4_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
170 iz-DATACENTER_BOT_ZN_6_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
171 GROUNDFLOOR_PLENUM_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
172 MIDFLOOR_PLENUM_WALL_NORTH 0 869.22 250.73 37.50 0 1.22 243.69 58.49 0.00 0 No No
173 MIDFLOOR_PLENUM_WALL_WEST 0 579.48 172.48 37.50 0 1.22 243.69 58.49 0.00 0 No No
174 MIDFLOOR_PLENUM_WALL_SOUTH 0 869.22 221.21 37.50 0 1.22 243.69 58.49 0.00 0 No No
175 MIDFLOOR_PLENUM_WALL_EAST 0 579.48 250.73 37.50 0 1.22 243.69 58.49 0.00 0 No No
176 iz-CORE_MID_ZN_5_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
177 iz-PERIMETER_MID_ZN_3_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
178 iz-PERIMETER_MID_ZN_2_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
179 iz-PERIMETER_MID_ZN_1_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
180 iz-PERIMETER_MID_ZN_4_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
181 iz-DATACENTER_MID_ZN_6_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
182 MIDFLOOR_PLENUM_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
183 TOPFLOOR_PLENUM_WALL_NORTH 0 869.22 221.21 37.50 0 1.22 243.69 58.49 0.00 0 No No
184 TOPFLOOR_PLENUM_WALL_EAST 0 579.48 250.73 37.50 0 1.22 243.69 58.49 0.00 0 No No
185 TOPFLOOR_PLENUM_WALL_WEST 0 579.48 172.48 37.50 0 1.22 243.69 58.49 0.00 0 No No
186 TOPFLOOR_PLENUM_WALL_SOUTH 0 869.22 250.73 37.50 0 1.22 243.69 58.49 0.00 0 No No
187 iz-CORE_TOP_ZN_5_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
188 iz-PERIMETER_TOP_ZN_3_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
189 iz-PERIMETER_TOP_ZN_2_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
190 iz-PERIMETER_TOP_ZN_1_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
191 iz-PERIMETER_TOP_ZN_4_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
192 iz-DATACENTER_TOP_ZN_6_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
193 BUILDING_ROOF 0 3563.11 268.06 0.00 0 1.22 243.69 58.49 0.00 0 No No
194 DATACENTER_BOT_ZN_6_WALL_NORTH 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
195 DATACENTER_BOT_ZN_6_WALL_SOUTH 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
196 DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
197 DATACENTER_BOT_ZN_6_WALL_WEST 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
198 DATACENTER_BOT_ZN_6_FLOOR 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
199 DATACENTER_BOT_ZN_6_CEILING 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
200 DATACENTER_MID_ZN_6_WALL_WEST 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
201 DATACENTER_MID_ZN_6_WALL_SOUTH 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
202 DATACENTER_MID_ZN_6_WALL_EAST 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
203 DATACENTER_MID_ZN_6_WALL_NORTH 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
204 DATACENTER_MID_ZN_6_FLOOR 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
205 DATACENTER_MID_ZN_6_CEILING 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
206 DATACENTER_TOP_ZN_6_WALL_EAST 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
207 DATACENTER_TOP_ZN_6_WALL_WEST 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
208 DATACENTER_TOP_ZN_6_WALL_SOUTH 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
209 DATACENTER_TOP_ZN_6_WALL_NORTH 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
210 DATACENTER_TOP_ZN_6_FLOOR 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
211 DATACENTER_TOP_ZN_6_CEILING 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
212 DATACENTER_BASEMENT_ZN_6_WALL_NORTH 0 0.00 0.00 0.00 0 2.44 0.00 24.18 -999.00 0 No No
213 DATACENTER_BASEMENT_ZN_6_WALL_SOUTH 0 0.00 0.00 0.00 0 2.44 0.00 24.18 -999.00 0 No No
214 DATACENTER_BASEMENT_ZN_6_WALL_WEST 0 0.00 0.00 0.00 0 2.44 0.00 24.18 -999.00 0 No No
215 DATACENTER_BASEMENT_ZN_6_WALL_EAST 0 0.00 0.00 0.00 0 2.44 0.00 24.18 -999.00 0 No No
216 DATACENTER_BASEMENT_ZN_6_FLOOR 0 0.00 0.00 0.00 0 2.44 0.00 24.18 -999.00 0 No No
217 DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.44 0.00 24.18 -999.00 0 No No
218 DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 0 0.00 0.00 0.00 0 2.44 0.00 24.18 -999.00 0 No No
219 PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.44 0.00 24.18 -999.00 0 No No
220 DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 0 0.00 0.00 0.00 0 2.44 0.00 24.18 -999.00 0 No No
221 DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 0 0.00 0.00 0.00 0 2.44 0.00 24.18 -999.00 0 No No


ZoneInfiltration Airflow Stats Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Design Volume Flow Rate {m3/s} Volume Flow Rate/Floor Area {m3/s-m2} Volume Flow Rate/Exterior Surface Area {m3/s-m2} ACH - Air Changes per Hour Equation A - Constant Term Coefficient {} Equation B - Temperature Term Coefficient {1/C} Equation C - Velocity Term Coefficient {s/m} Equation D - Velocity Squared Term Coefficient {s2/m2}
1 PERIMETER_BOT_ZN_3_INFILTRATION INFIL_SCH_PNNL PERIMETER_BOT_ZN_3 313.41 16.9 0.114 3.646E-004 5.482E-004 0.478 0.000 0.000 0.224 0.000
2 PERIMETER_BOT_ZN_2_INFILTRATION INFIL_SCH_PNNL PERIMETER_BOT_ZN_2 201.98 10.9 7.617E-002 3.771E-004 5.534E-004 0.495 0.000 0.000 0.224 0.000
3 PERIMETER_BOT_ZN_1_INFILTRATION INFIL_SCH_PNNL PERIMETER_BOT_ZN_1 313.42 16.9 0.114 3.646E-004 5.482E-004 0.478 0.000 0.000 0.224 0.000
4 PERIMETER_BOT_ZN_4_INFILTRATION INFIL_SCH_PNNL PERIMETER_BOT_ZN_4 201.98 10.9 7.617E-002 3.771E-004 5.534E-004 0.495 0.000 0.000 0.224 0.000
5 PERIMETER_MID_ZN_3_INFILTRATION INFIL_SCH_PNNL PERIMETER_MID_ZN_3 313.41 16.9 0.114 3.646E-004 5.696E-004 0.478 0.000 0.000 0.224 0.000
6 PERIMETER_MID_ZN_2_INFILTRATION INFIL_SCH_PNNL PERIMETER_MID_ZN_2 201.98 10.9 7.617E-002 3.771E-004 5.696E-004 0.495 0.000 0.000 0.224 0.000
7 PERIMETER_MID_ZN_1_INFILTRATION INFIL_SCH_PNNL PERIMETER_MID_ZN_1 313.42 16.9 0.114 3.646E-004 5.696E-004 0.478 0.000 0.000 0.224 0.000
8 PERIMETER_MID_ZN_4_INFILTRATION INFIL_SCH_PNNL PERIMETER_MID_ZN_4 201.98 10.9 7.617E-002 3.771E-004 5.696E-004 0.495 0.000 0.000 0.224 0.000
9 PERIMETER_TOP_ZN_3_INFILTRATION INFIL_SCH_PNNL PERIMETER_TOP_ZN_3 313.41 16.9 0.114 3.646E-004 5.696E-004 0.478 0.000 0.000 0.224 0.000
10 PERIMETER_TOP_ZN_2_INFILTRATION INFIL_SCH_PNNL PERIMETER_TOP_ZN_2 201.98 10.9 7.617E-002 3.771E-004 5.696E-004 0.495 0.000 0.000 0.224 0.000
11 PERIMETER_TOP_ZN_1_INFILTRATION INFIL_SCH_PNNL PERIMETER_TOP_ZN_1 313.42 16.9 0.114 3.646E-004 5.696E-004 0.478 0.000 0.000 0.224 0.000
12 PERIMETER_TOP_ZN_4_INFILTRATION INFIL_SCH_PNNL PERIMETER_TOP_ZN_4 201.98 10.9 7.617E-002 3.771E-004 5.696E-004 0.495 0.000 0.000 0.224 0.000
13 GROUNDFLOOR_PLENUM_INFILTRATION INFIL_SCH_PNNL GROUNDFLOOR_PLENUM 3563.11 0.0 0.169 4.749E-005 5.696E-004 0.140 0.000 0.000 0.224 0.000
14 MIDFLOOR_PLENUM_INFILTRATION INFIL_SCH_PNNL MIDFLOOR_PLENUM 3563.11 0.0 0.169 4.749E-005 5.696E-004 0.140 0.000 0.000 0.224 0.000
15 TOPFLOOR_PLENUM_INFILTRATION INFIL_SCH_PNNL TOPFLOOR_PLENUM 3563.11 0.0 0.169 4.749E-005 4.384E-005 0.140 0.000 0.000 0.224 0.000


AirFlow Model

Simple
1 Simple


RoomAir Model

Zone Name Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined
1 BASEMENT Mixing/Well-Stirred
2 CORE_BOTTOM Mixing/Well-Stirred
3 CORE_MID Mixing/Well-Stirred
4 CORE_TOP Mixing/Well-Stirred
5 PERIMETER_BOT_ZN_3 Mixing/Well-Stirred
6 PERIMETER_BOT_ZN_2 Mixing/Well-Stirred
7 PERIMETER_BOT_ZN_1 Mixing/Well-Stirred
8 PERIMETER_BOT_ZN_4 Mixing/Well-Stirred
9 PERIMETER_MID_ZN_3 Mixing/Well-Stirred
10 PERIMETER_MID_ZN_2 Mixing/Well-Stirred
11 PERIMETER_MID_ZN_1 Mixing/Well-Stirred
12 PERIMETER_MID_ZN_4 Mixing/Well-Stirred
13 PERIMETER_TOP_ZN_3 Mixing/Well-Stirred
14 PERIMETER_TOP_ZN_2 Mixing/Well-Stirred
15 PERIMETER_TOP_ZN_1 Mixing/Well-Stirred
16 PERIMETER_TOP_ZN_4 Mixing/Well-Stirred
17 GROUNDFLOOR_PLENUM Mixing/Well-Stirred
18 MIDFLOOR_PLENUM Mixing/Well-Stirred
19 TOPFLOOR_PLENUM Mixing/Well-Stirred
20 DATACENTER_BOT_ZN_6 Mixing/Well-Stirred
21 DATACENTER_MID_ZN_6 Mixing/Well-Stirred
22 DATACENTER_TOP_ZN_6 Mixing/Well-Stirred
23 DATACENTER_BASEMENT_ZN_6 Mixing/Well-Stirred


AirflowNetwork Model:Control

No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation
1 NoMultizoneOrDistribution


Zone Volume Capacitance Multiplier

Sensible Heat Capacity Multiplier Moisture Capacity Multiplier Carbon Dioxide Capacity Multiplier Generic Contaminant Capacity Multiplier
1 1.000 1.000 1.000 1.000


Load Timesteps in Zone Design Calculation Averaging Window

Value
1 6


Heating Sizing Factor Information

Sizing Factor ID Value
1 Global 1.0000


Cooling Sizing Factor Information

Sizing Factor ID Value
1 Global 1.0000


Sky Daylight Factors

Sky Type MonthAndDay Daylighting Control Name Enclosure Name Window Name Reference Point Daylight Factor
1 Clear Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 PERIMETER_BOT_ZN_1_DAYLREFPT1 7.7114E-003
2 Clear Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 PERIMETER_BOT_ZN_1_DAYLREFPT2 7.7138E-003
3 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 PERIMETER_BOT_ZN_1_DAYLREFPT1 8.6318E-003
4 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 PERIMETER_BOT_ZN_1_DAYLREFPT2 8.6338E-003
5 Intermediate Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 PERIMETER_BOT_ZN_1_DAYLREFPT1 4.9702E-003
6 Intermediate Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 PERIMETER_BOT_ZN_1_DAYLREFPT2 4.9717E-003
7 Overcast Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 PERIMETER_BOT_ZN_1_DAYLREFPT1 2.7740E-003
8 Overcast Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 PERIMETER_BOT_ZN_1_DAYLREFPT2 2.7748E-003
9 Clear Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 PERIMETER_BOT_ZN_1_DAYLREFPT1 7.7655E-003
10 Clear Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 PERIMETER_BOT_ZN_1_DAYLREFPT2 7.9212E-003
11 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 PERIMETER_BOT_ZN_1_DAYLREFPT1 8.6773E-003
12 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 PERIMETER_BOT_ZN_1_DAYLREFPT2 8.8128E-003
13 Intermediate Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 PERIMETER_BOT_ZN_1_DAYLREFPT1 5.0080E-003
14 Intermediate Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 PERIMETER_BOT_ZN_1_DAYLREFPT2 5.1195E-003
15 Overcast Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 PERIMETER_BOT_ZN_1_DAYLREFPT1 2.7969E-003
16 Overcast Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 PERIMETER_BOT_ZN_1_DAYLREFPT2 2.8551E-003
17 Clear Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 PERIMETER_BOT_ZN_1_DAYLREFPT1 0.1825
18 Clear Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 PERIMETER_BOT_ZN_1_DAYLREFPT2 9.9759E-002
19 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 PERIMETER_BOT_ZN_1_DAYLREFPT1 0.2093
20 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 PERIMETER_BOT_ZN_1_DAYLREFPT2 0.1158
21 Intermediate Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 PERIMETER_BOT_ZN_1_DAYLREFPT1 0.1197
22 Intermediate Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 PERIMETER_BOT_ZN_1_DAYLREFPT2 4.9531E-002
23 Overcast Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 PERIMETER_BOT_ZN_1_DAYLREFPT1 5.0165E-002
24 Overcast Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 PERIMETER_BOT_ZN_1_DAYLREFPT2 1.7447E-002
25 Clear Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 PERIMETER_BOT_ZN_1_DAYLREFPT1 7.7778E-003
26 Clear Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 PERIMETER_BOT_ZN_1_DAYLREFPT2 7.9872E-003
27 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 PERIMETER_BOT_ZN_1_DAYLREFPT1 8.6910E-003
28 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 PERIMETER_BOT_ZN_1_DAYLREFPT2 8.8865E-003
29 Intermediate Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 PERIMETER_BOT_ZN_1_DAYLREFPT1 5.0181E-003
30 Intermediate Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 PERIMETER_BOT_ZN_1_DAYLREFPT2 5.1586E-003
31 Overcast Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 PERIMETER_BOT_ZN_1_DAYLREFPT1 2.7974E-003
32 Overcast Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 PERIMETER_BOT_ZN_1_DAYLREFPT2 2.8568E-003
33 Clear Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 PERIMETER_BOT_ZN_1_DAYLREFPT1 7.7112E-003
34 Clear Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 PERIMETER_BOT_ZN_1_DAYLREFPT2 7.7140E-003
35 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 PERIMETER_BOT_ZN_1_DAYLREFPT1 8.6316E-003
36 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 PERIMETER_BOT_ZN_1_DAYLREFPT2 8.6341E-003
37 Intermediate Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 PERIMETER_BOT_ZN_1_DAYLREFPT1 4.9701E-003
38 Intermediate Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 PERIMETER_BOT_ZN_1_DAYLREFPT2 4.9720E-003
39 Overcast Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 PERIMETER_BOT_ZN_1_DAYLREFPT1 2.7739E-003
40 Overcast Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 PERIMETER_BOT_ZN_1_DAYLREFPT2 2.7747E-003
41 Clear Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 PERIMETER_BOT_ZN_2_DAYLREFPT1 6.9174E-003
42 Clear Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 PERIMETER_BOT_ZN_2_DAYLREFPT2 7.4164E-003
43 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 PERIMETER_BOT_ZN_2_DAYLREFPT1 6.8025E-003
44 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 PERIMETER_BOT_ZN_2_DAYLREFPT2 7.3880E-003
45 Intermediate Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 PERIMETER_BOT_ZN_2_DAYLREFPT1 5.9588E-003
46 Intermediate Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 PERIMETER_BOT_ZN_2_DAYLREFPT2 6.1161E-003
47 Overcast Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 PERIMETER_BOT_ZN_2_DAYLREFPT1 4.7428E-003
48 Overcast Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 PERIMETER_BOT_ZN_2_DAYLREFPT2 4.7830E-003
49 Clear Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 PERIMETER_BOT_ZN_2_DAYLREFPT1 8.0221E-002
50 Clear Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 PERIMETER_BOT_ZN_2_DAYLREFPT2 3.8990E-002
51 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 PERIMETER_BOT_ZN_2_DAYLREFPT1 7.8391E-002
52 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 PERIMETER_BOT_ZN_2_DAYLREFPT2 3.7084E-002
53 Intermediate Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 PERIMETER_BOT_ZN_2_DAYLREFPT1 7.3623E-002
54 Intermediate Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 PERIMETER_BOT_ZN_2_DAYLREFPT2 3.0756E-002
55 Overcast Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 PERIMETER_BOT_ZN_2_DAYLREFPT1 5.2230E-002
56 Overcast Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 PERIMETER_BOT_ZN_2_DAYLREFPT2 1.9536E-002
57 Clear Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 PERIMETER_BOT_ZN_2_DAYLREFPT1 6.7592E-003
58 Clear Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 PERIMETER_BOT_ZN_2_DAYLREFPT2 6.8797E-003
59 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 PERIMETER_BOT_ZN_2_DAYLREFPT1 6.5933E-003
60 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 PERIMETER_BOT_ZN_2_DAYLREFPT2 6.6821E-003
61 Intermediate Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 PERIMETER_BOT_ZN_2_DAYLREFPT1 5.9106E-003
62 Intermediate Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 PERIMETER_BOT_ZN_2_DAYLREFPT2 5.9465E-003
63 Overcast Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 PERIMETER_BOT_ZN_2_DAYLREFPT1 4.7430E-003
64 Overcast Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 PERIMETER_BOT_ZN_2_DAYLREFPT2 4.7836E-003
65 Clear Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 PERIMETER_BOT_ZN_3_DAYLREFPT1 3.0492E-003
66 Clear Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 PERIMETER_BOT_ZN_3_DAYLREFPT2 3.0516E-003
67 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 PERIMETER_BOT_ZN_3_DAYLREFPT1 2.5843E-003
68 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 PERIMETER_BOT_ZN_3_DAYLREFPT2 2.5863E-003
69 Intermediate Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 PERIMETER_BOT_ZN_3_DAYLREFPT1 2.2615E-003
70 Intermediate Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 PERIMETER_BOT_ZN_3_DAYLREFPT2 2.2630E-003
71 Overcast Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 PERIMETER_BOT_ZN_3_DAYLREFPT1 2.7740E-003
72 Overcast Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 PERIMETER_BOT_ZN_3_DAYLREFPT2 2.7749E-003
73 Clear Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 PERIMETER_BOT_ZN_3_DAYLREFPT1 3.1042E-003
74 Clear Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 PERIMETER_BOT_ZN_3_DAYLREFPT2 3.2430E-003
75 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 PERIMETER_BOT_ZN_3_DAYLREFPT1 2.6306E-003
76 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 PERIMETER_BOT_ZN_3_DAYLREFPT2 2.7435E-003
77 Intermediate Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 PERIMETER_BOT_ZN_3_DAYLREFPT1 2.2998E-003
78 Intermediate Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 PERIMETER_BOT_ZN_3_DAYLREFPT2 2.3855E-003
79 Overcast Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 PERIMETER_BOT_ZN_3_DAYLREFPT1 2.7975E-003
80 Overcast Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 PERIMETER_BOT_ZN_3_DAYLREFPT2 2.8569E-003
81 Clear Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 PERIMETER_BOT_ZN_3_DAYLREFPT1 5.0464E-002
82 Clear Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 PERIMETER_BOT_ZN_3_DAYLREFPT2 2.6651E-002
83 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 PERIMETER_BOT_ZN_3_DAYLREFPT1 3.8839E-002
84 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 PERIMETER_BOT_ZN_3_DAYLREFPT2 2.0271E-002
85 Intermediate Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 PERIMETER_BOT_ZN_3_DAYLREFPT1 3.4674E-002
86 Intermediate Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 PERIMETER_BOT_ZN_3_DAYLREFPT2 1.3448E-002
87 Overcast Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 PERIMETER_BOT_ZN_3_DAYLREFPT1 5.0165E-002
88 Overcast Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 PERIMETER_BOT_ZN_3_DAYLREFPT2 1.7442E-002
89 Clear Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 PERIMETER_BOT_ZN_3_DAYLREFPT1 3.1014E-003
90 Clear Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 PERIMETER_BOT_ZN_3_DAYLREFPT2 3.2438E-003
91 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 PERIMETER_BOT_ZN_3_DAYLREFPT1 2.6261E-003
92 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 PERIMETER_BOT_ZN_3_DAYLREFPT2 2.7371E-003
93 Intermediate Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 PERIMETER_BOT_ZN_3_DAYLREFPT1 2.2918E-003
94 Intermediate Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 PERIMETER_BOT_ZN_3_DAYLREFPT2 2.3604E-003
95 Overcast Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 PERIMETER_BOT_ZN_3_DAYLREFPT1 2.7969E-003
96 Overcast Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 PERIMETER_BOT_ZN_3_DAYLREFPT2 2.8551E-003
97 Clear Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 PERIMETER_BOT_ZN_3_DAYLREFPT1 3.0490E-003
98 Clear Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 PERIMETER_BOT_ZN_3_DAYLREFPT2 3.0514E-003
99 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 PERIMETER_BOT_ZN_3_DAYLREFPT1 2.5841E-003
100 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 PERIMETER_BOT_ZN_3_DAYLREFPT2 2.5860E-003
101 Intermediate Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 PERIMETER_BOT_ZN_3_DAYLREFPT1 2.2613E-003
102 Intermediate Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 PERIMETER_BOT_ZN_3_DAYLREFPT2 2.2625E-003
103 Overcast Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 PERIMETER_BOT_ZN_3_DAYLREFPT1 2.7739E-003
104 Overcast Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 PERIMETER_BOT_ZN_3_DAYLREFPT2 2.7748E-003
105 Clear Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 PERIMETER_BOT_ZN_4_DAYLREFPT1 5.7277E-003
106 Clear Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 PERIMETER_BOT_ZN_4_DAYLREFPT2 5.8556E-003
107 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 PERIMETER_BOT_ZN_4_DAYLREFPT1 5.2654E-003
108 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 PERIMETER_BOT_ZN_4_DAYLREFPT2 5.3581E-003
109 Intermediate Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 PERIMETER_BOT_ZN_4_DAYLREFPT1 5.1943E-003
110 Intermediate Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 PERIMETER_BOT_ZN_4_DAYLREFPT2 5.2259E-003
111 Overcast Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 PERIMETER_BOT_ZN_4_DAYLREFPT1 4.7431E-003
112 Overcast Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 PERIMETER_BOT_ZN_4_DAYLREFPT2 4.7837E-003
113 Clear Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 PERIMETER_BOT_ZN_4_DAYLREFPT1 6.2155E-002
114 Clear Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 PERIMETER_BOT_ZN_4_DAYLREFPT2 3.1514E-002
115 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 PERIMETER_BOT_ZN_4_DAYLREFPT1 5.5261E-002
116 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 PERIMETER_BOT_ZN_4_DAYLREFPT2 2.7481E-002
117 Intermediate Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 PERIMETER_BOT_ZN_4_DAYLREFPT1 6.0374E-002
118 Intermediate Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 PERIMETER_BOT_ZN_4_DAYLREFPT2 2.5330E-002
119 Overcast Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 PERIMETER_BOT_ZN_4_DAYLREFPT1 5.2230E-002
120 Overcast Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 PERIMETER_BOT_ZN_4_DAYLREFPT2 1.9536E-002
121 Clear Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 PERIMETER_BOT_ZN_4_DAYLREFPT1 5.8323E-003
122 Clear Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 PERIMETER_BOT_ZN_4_DAYLREFPT2 6.1338E-003
123 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 PERIMETER_BOT_ZN_4_DAYLREFPT1 5.4051E-003
124 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 PERIMETER_BOT_ZN_4_DAYLREFPT2 5.7328E-003
125 Intermediate Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 PERIMETER_BOT_ZN_4_DAYLREFPT1 5.2377E-003
126 Intermediate Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 PERIMETER_BOT_ZN_4_DAYLREFPT2 5.3710E-003
127 Overcast Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 PERIMETER_BOT_ZN_4_DAYLREFPT1 4.7428E-003
128 Overcast Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 PERIMETER_BOT_ZN_4_DAYLREFPT2 4.7829E-003
129 Clear Sky 01/21 PERIMETER_MID_ZN_1_DAYLCTRL PERIMETER_MID_ZN_1 PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW PERIMETER_MID_ZN_1_DAYLREFPT1 0.1875
130 Clear Sky 01/21 PERIMETER_MID_ZN_1_DAYLCTRL PERIMETER_MID_ZN_1 PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW PERIMETER_MID_ZN_1_DAYLREFPT2 0.1380
131 Clear Turbid Sky 01/21 PERIMETER_MID_ZN_1_DAYLCTRL PERIMETER_MID_ZN_1 PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW PERIMETER_MID_ZN_1_DAYLREFPT1 0.2098
132 Clear Turbid Sky 01/21 PERIMETER_MID_ZN_1_DAYLCTRL PERIMETER_MID_ZN_1 PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW PERIMETER_MID_ZN_1_DAYLREFPT2 0.1587
133 Intermediate Sky 01/21 PERIMETER_MID_ZN_1_DAYLCTRL PERIMETER_MID_ZN_1 PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW PERIMETER_MID_ZN_1_DAYLREFPT1 0.1346
134 Intermediate Sky 01/21 PERIMETER_MID_ZN_1_DAYLCTRL PERIMETER_MID_ZN_1 PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW PERIMETER_MID_ZN_1_DAYLREFPT2 7.3171E-002
135 Overcast Sky 01/21 PERIMETER_MID_ZN_1_DAYLCTRL PERIMETER_MID_ZN_1 PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW PERIMETER_MID_ZN_1_DAYLREFPT1 6.1425E-002
136 Overcast Sky 01/21 PERIMETER_MID_ZN_1_DAYLCTRL PERIMETER_MID_ZN_1 PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW PERIMETER_MID_ZN_1_DAYLREFPT2 3.0380E-002
137 Clear Sky 01/21 PERIMETER_MID_ZN_2_DAYLCTRL PERIMETER_MID_ZN_2 PERIMETER_MID_ZN_2_WALL_EAST_WINDOW PERIMETER_MID_ZN_2_DAYLREFPT1 9.4930E-002
138 Clear Sky 01/21 PERIMETER_MID_ZN_2_DAYLCTRL PERIMETER_MID_ZN_2 PERIMETER_MID_ZN_2_WALL_EAST_WINDOW PERIMETER_MID_ZN_2_DAYLREFPT2 5.5725E-002
139 Clear Turbid Sky 01/21 PERIMETER_MID_ZN_2_DAYLCTRL PERIMETER_MID_ZN_2 PERIMETER_MID_ZN_2_WALL_EAST_WINDOW PERIMETER_MID_ZN_2_DAYLREFPT1 9.2936E-002
140 Clear Turbid Sky 01/21 PERIMETER_MID_ZN_2_DAYLCTRL PERIMETER_MID_ZN_2 PERIMETER_MID_ZN_2_WALL_EAST_WINDOW PERIMETER_MID_ZN_2_DAYLREFPT2 5.3636E-002
141 Intermediate Sky 01/21 PERIMETER_MID_ZN_2_DAYLCTRL PERIMETER_MID_ZN_2 PERIMETER_MID_ZN_2_WALL_EAST_WINDOW PERIMETER_MID_ZN_2_DAYLREFPT1 8.6873E-002
142 Intermediate Sky 01/21 PERIMETER_MID_ZN_2_DAYLCTRL PERIMETER_MID_ZN_2 PERIMETER_MID_ZN_2_WALL_EAST_WINDOW PERIMETER_MID_ZN_2_DAYLREFPT2 4.4880E-002
143 Overcast Sky 01/21 PERIMETER_MID_ZN_2_DAYLCTRL PERIMETER_MID_ZN_2 PERIMETER_MID_ZN_2_WALL_EAST_WINDOW PERIMETER_MID_ZN_2_DAYLREFPT1 6.2997E-002
144 Overcast Sky 01/21 PERIMETER_MID_ZN_2_DAYLCTRL PERIMETER_MID_ZN_2 PERIMETER_MID_ZN_2_WALL_EAST_WINDOW PERIMETER_MID_ZN_2_DAYLREFPT2 3.0728E-002
145 Clear Sky 01/21 PERIMETER_MID_ZN_3_DAYLCTRL PERIMETER_MID_ZN_3 PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW PERIMETER_MID_ZN_3_DAYLREFPT1 6.2218E-002
146 Clear Sky 01/21 PERIMETER_MID_ZN_3_DAYLCTRL PERIMETER_MID_ZN_3 PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW PERIMETER_MID_ZN_3_DAYLREFPT2 4.1364E-002
147 Clear Turbid Sky 01/21 PERIMETER_MID_ZN_3_DAYLCTRL PERIMETER_MID_ZN_3 PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW PERIMETER_MID_ZN_3_DAYLREFPT1 4.9075E-002
148 Clear Turbid Sky 01/21 PERIMETER_MID_ZN_3_DAYLCTRL PERIMETER_MID_ZN_3 PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW PERIMETER_MID_ZN_3_DAYLREFPT2 3.2665E-002
149 Intermediate Sky 01/21 PERIMETER_MID_ZN_3_DAYLCTRL PERIMETER_MID_ZN_3 PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW PERIMETER_MID_ZN_3_DAYLREFPT1 4.4534E-002
150 Intermediate Sky 01/21 PERIMETER_MID_ZN_3_DAYLCTRL PERIMETER_MID_ZN_3 PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW PERIMETER_MID_ZN_3_DAYLREFPT2 2.4117E-002
151 Overcast Sky 01/21 PERIMETER_MID_ZN_3_DAYLCTRL PERIMETER_MID_ZN_3 PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW PERIMETER_MID_ZN_3_DAYLREFPT1 6.1425E-002
152 Overcast Sky 01/21 PERIMETER_MID_ZN_3_DAYLCTRL PERIMETER_MID_ZN_3 PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW PERIMETER_MID_ZN_3_DAYLREFPT2 3.0375E-002
153 Clear Sky 01/21 PERIMETER_MID_ZN_4_DAYLCTRL PERIMETER_MID_ZN_4 PERIMETER_MID_ZN_4_WALL_WEST_WINDOW PERIMETER_MID_ZN_4_DAYLREFPT1 7.4507E-002
154 Clear Sky 01/21 PERIMETER_MID_ZN_4_DAYLCTRL PERIMETER_MID_ZN_4 PERIMETER_MID_ZN_4_WALL_WEST_WINDOW PERIMETER_MID_ZN_4_DAYLREFPT2 4.5428E-002
155 Clear Turbid Sky 01/21 PERIMETER_MID_ZN_4_DAYLCTRL PERIMETER_MID_ZN_4 PERIMETER_MID_ZN_4_WALL_WEST_WINDOW PERIMETER_MID_ZN_4_DAYLREFPT1 6.6773E-002
156 Clear Turbid Sky 01/21 PERIMETER_MID_ZN_4_DAYLCTRL PERIMETER_MID_ZN_4 PERIMETER_MID_ZN_4_WALL_WEST_WINDOW PERIMETER_MID_ZN_4_DAYLREFPT2 4.0389E-002
157 Intermediate Sky 01/21 PERIMETER_MID_ZN_4_DAYLCTRL PERIMETER_MID_ZN_4 PERIMETER_MID_ZN_4_WALL_WEST_WINDOW PERIMETER_MID_ZN_4_DAYLREFPT1 7.2041E-002
158 Intermediate Sky 01/21 PERIMETER_MID_ZN_4_DAYLCTRL PERIMETER_MID_ZN_4 PERIMETER_MID_ZN_4_WALL_WEST_WINDOW PERIMETER_MID_ZN_4_DAYLREFPT2 3.7716E-002
159 Overcast Sky 01/21 PERIMETER_MID_ZN_4_DAYLCTRL PERIMETER_MID_ZN_4 PERIMETER_MID_ZN_4_WALL_WEST_WINDOW PERIMETER_MID_ZN_4_DAYLREFPT1 6.2997E-002
160 Overcast Sky 01/21 PERIMETER_MID_ZN_4_DAYLCTRL PERIMETER_MID_ZN_4 PERIMETER_MID_ZN_4_WALL_WEST_WINDOW PERIMETER_MID_ZN_4_DAYLREFPT2 3.0728E-002
161 Clear Sky 01/21 PERIMETER_TOP_ZN_1_DAYLCTRL PERIMETER_TOP_ZN_1 PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW PERIMETER_TOP_ZN_1_DAYLREFPT1 0.1875
162 Clear Sky 01/21 PERIMETER_TOP_ZN_1_DAYLCTRL PERIMETER_TOP_ZN_1 PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW PERIMETER_TOP_ZN_1_DAYLREFPT2 0.1382
163 Clear Turbid Sky 01/21 PERIMETER_TOP_ZN_1_DAYLCTRL PERIMETER_TOP_ZN_1 PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW PERIMETER_TOP_ZN_1_DAYLREFPT1 0.2098
164 Clear Turbid Sky 01/21 PERIMETER_TOP_ZN_1_DAYLCTRL PERIMETER_TOP_ZN_1 PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW PERIMETER_TOP_ZN_1_DAYLREFPT2 0.1590
165 Intermediate Sky 01/21 PERIMETER_TOP_ZN_1_DAYLCTRL PERIMETER_TOP_ZN_1 PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW PERIMETER_TOP_ZN_1_DAYLREFPT1 0.1348
166 Intermediate Sky 01/21 PERIMETER_TOP_ZN_1_DAYLCTRL PERIMETER_TOP_ZN_1 PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW PERIMETER_TOP_ZN_1_DAYLREFPT2 7.3346E-002
167 Overcast Sky 01/21 PERIMETER_TOP_ZN_1_DAYLCTRL PERIMETER_TOP_ZN_1 PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW PERIMETER_TOP_ZN_1_DAYLREFPT1 6.1557E-002
168 Overcast Sky 01/21 PERIMETER_TOP_ZN_1_DAYLCTRL PERIMETER_TOP_ZN_1 PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW PERIMETER_TOP_ZN_1_DAYLREFPT2 3.0447E-002
169 Clear Sky 01/21 PERIMETER_TOP_ZN_2_DAYLCTRL PERIMETER_TOP_ZN_2 PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW PERIMETER_TOP_ZN_2_DAYLREFPT1 9.4994E-002
170 Clear Sky 01/21 PERIMETER_TOP_ZN_2_DAYLCTRL PERIMETER_TOP_ZN_2 PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW PERIMETER_TOP_ZN_2_DAYLREFPT2 5.5813E-002
171 Clear Turbid Sky 01/21 PERIMETER_TOP_ZN_2_DAYLCTRL PERIMETER_TOP_ZN_2 PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW PERIMETER_TOP_ZN_2_DAYLREFPT1 9.3010E-002
172 Clear Turbid Sky 01/21 PERIMETER_TOP_ZN_2_DAYLCTRL PERIMETER_TOP_ZN_2 PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW PERIMETER_TOP_ZN_2_DAYLREFPT2 5.3724E-002
173 Intermediate Sky 01/21 PERIMETER_TOP_ZN_2_DAYLCTRL PERIMETER_TOP_ZN_2 PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW PERIMETER_TOP_ZN_2_DAYLREFPT1 8.7004E-002
174 Intermediate Sky 01/21 PERIMETER_TOP_ZN_2_DAYLCTRL PERIMETER_TOP_ZN_2 PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW PERIMETER_TOP_ZN_2_DAYLREFPT2 4.4977E-002
175 Overcast Sky 01/21 PERIMETER_TOP_ZN_2_DAYLCTRL PERIMETER_TOP_ZN_2 PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW PERIMETER_TOP_ZN_2_DAYLREFPT1 6.3129E-002
176 Overcast Sky 01/21 PERIMETER_TOP_ZN_2_DAYLCTRL PERIMETER_TOP_ZN_2 PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW PERIMETER_TOP_ZN_2_DAYLREFPT2 3.0795E-002
177 Clear Sky 01/21 PERIMETER_TOP_ZN_3_DAYLCTRL PERIMETER_TOP_ZN_3 PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW PERIMETER_TOP_ZN_3_DAYLREFPT1 6.2221E-002
178 Clear Sky 01/21 PERIMETER_TOP_ZN_3_DAYLCTRL PERIMETER_TOP_ZN_3 PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW PERIMETER_TOP_ZN_3_DAYLREFPT2 4.1412E-002
179 Clear Turbid Sky 01/21 PERIMETER_TOP_ZN_3_DAYLCTRL PERIMETER_TOP_ZN_3 PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW PERIMETER_TOP_ZN_3_DAYLREFPT1 4.9082E-002
180 Clear Turbid Sky 01/21 PERIMETER_TOP_ZN_3_DAYLCTRL PERIMETER_TOP_ZN_3 PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW PERIMETER_TOP_ZN_3_DAYLREFPT2 3.2703E-002
181 Intermediate Sky 01/21 PERIMETER_TOP_ZN_3_DAYLCTRL PERIMETER_TOP_ZN_3 PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW PERIMETER_TOP_ZN_3_DAYLREFPT1 4.4605E-002
182 Intermediate Sky 01/21 PERIMETER_TOP_ZN_3_DAYLCTRL PERIMETER_TOP_ZN_3 PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW PERIMETER_TOP_ZN_3_DAYLREFPT2 2.4162E-002
183 Overcast Sky 01/21 PERIMETER_TOP_ZN_3_DAYLCTRL PERIMETER_TOP_ZN_3 PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW PERIMETER_TOP_ZN_3_DAYLREFPT1 6.1557E-002
184 Overcast Sky 01/21 PERIMETER_TOP_ZN_3_DAYLCTRL PERIMETER_TOP_ZN_3 PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW PERIMETER_TOP_ZN_3_DAYLREFPT2 3.0442E-002
185 Clear Sky 01/21 PERIMETER_TOP_ZN_4_DAYLCTRL PERIMETER_TOP_ZN_4 PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW PERIMETER_TOP_ZN_4_DAYLREFPT1 7.4543E-002
186 Clear Sky 01/21 PERIMETER_TOP_ZN_4_DAYLCTRL PERIMETER_TOP_ZN_4 PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW PERIMETER_TOP_ZN_4_DAYLREFPT2 4.5492E-002
187 Clear Turbid Sky 01/21 PERIMETER_TOP_ZN_4_DAYLCTRL PERIMETER_TOP_ZN_4 PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW PERIMETER_TOP_ZN_4_DAYLREFPT1 6.6813E-002
188 Clear Turbid Sky 01/21 PERIMETER_TOP_ZN_4_DAYLCTRL PERIMETER_TOP_ZN_4 PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW PERIMETER_TOP_ZN_4_DAYLREFPT2 4.0447E-002
189 Intermediate Sky 01/21 PERIMETER_TOP_ZN_4_DAYLCTRL PERIMETER_TOP_ZN_4 PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW PERIMETER_TOP_ZN_4_DAYLREFPT1 7.2149E-002
190 Intermediate Sky 01/21 PERIMETER_TOP_ZN_4_DAYLCTRL PERIMETER_TOP_ZN_4 PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW PERIMETER_TOP_ZN_4_DAYLREFPT2 3.7794E-002
191 Overcast Sky 01/21 PERIMETER_TOP_ZN_4_DAYLCTRL PERIMETER_TOP_ZN_4 PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW PERIMETER_TOP_ZN_4_DAYLREFPT1 6.3129E-002
192 Overcast Sky 01/21 PERIMETER_TOP_ZN_4_DAYLCTRL PERIMETER_TOP_ZN_4 PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW PERIMETER_TOP_ZN_4_DAYLREFPT2 3.0795E-002


Zone Sizing Information

Zone Name Load Type Calc Des Load {W} User Des Load {W} Calc Des Air Flow Rate {m3/s} User Des Air Flow Rate {m3/s} Design Day Name Date/Time of Peak Temperature at Peak {C} Humidity Ratio at Peak {kgWater/kgDryAir} Floor Area {m2} # Occupants Calc Outdoor Air Flow Rate {m3/s} Calc DOAS Heat Addition Rate {W}
1 BASEMENT Cooling 82553.07926 82553.07926 6.81911 6.81911 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 21.56000 6.28881E-003 2779.42662 149.60210 1.20016 0.00000
2 BASEMENT Heating 0.00000 0.00000 0.00000 1.20016 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -27.60000 3.41898E-004 2779.42662 149.60210 1.20016 0.00000
3 CORE_BOTTOM Cooling 85532.33398 85532.33398 7.06426 7.06426 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 21.56000 6.28881E-003 2496.12046 134.35320 1.07782 0.00000
4 CORE_BOTTOM Heating 7875.69982 7875.69982 0.38153 1.07782 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -27.60000 3.41898E-004 2496.12046 134.35320 1.07782 0.00000
5 CORE_MID Cooling 805659.30733 805659.30733 66.52664 66.52664 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 21.56000 6.28881E-003 2496.12046 134.35320 10.77825 0.00000
6 CORE_MID Heating 340208.23813 340208.23813 16.46825 16.46825 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -27.60000 3.41898E-004 2496.12046 134.35320 10.77825 0.00000
7 CORE_TOP Cooling 77939.31004 77939.31004 6.43541 6.43541 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 21.56000 6.28881E-003 2496.12046 134.35320 1.07782 0.00000
8 CORE_TOP Heating 78157.42200 78157.42200 3.80376 3.80376 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -27.60000 3.41898E-004 2496.12046 134.35320 1.07782 0.00000
9 PERIMETER_BOT_ZN_3 Cooling 14368.61633 14368.61633 1.19693 1.19693 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 14:20:00 33.40000 6.30683E-003 313.41284 16.86939 0.13533 0.00000
10 PERIMETER_BOT_ZN_3 Heating 15136.08931 15136.08931 0.73778 0.73778 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -27.60000 3.41898E-004 313.41284 16.86939 0.13533 0.00000
11 PERIMETER_BOT_ZN_2 Cooling 19479.38923 19479.38923 1.62265 1.62265 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 09:00:00 24.60000 6.29334E-003 201.97515 10.87127 8.72129E-002 0.00000
12 PERIMETER_BOT_ZN_2 Heating 10356.48416 10356.48416 0.50489 0.50489 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -27.60000 3.41898E-004 201.97515 10.87127 8.72129E-002 0.00000
13 PERIMETER_BOT_ZN_1 Cooling 24109.11167 24109.11167 2.00831 2.00831 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 13:30:00 33.00000 6.30621E-003 313.41969 16.86975 0.13533 0.00000
14 PERIMETER_BOT_ZN_1 Heating 16580.20921 16580.20921 0.80836 0.80836 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -27.60000 3.41898E-004 313.41969 16.86975 0.13533 0.00000
15 PERIMETER_BOT_ZN_4 Cooling 23888.41645 23888.41645 1.98992 1.98992 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 17:20:00 30.62667 6.30253E-003 201.97515 10.87127 8.72129E-002 0.00000
16 PERIMETER_BOT_ZN_4 Heating 8819.29622 8819.29622 0.42974 0.42974 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -27.60000 3.41898E-004 201.97515 10.87127 8.72129E-002 0.00000
17 PERIMETER_MID_ZN_3 Cooling 136839.93297 136839.93297 11.39885 11.39885 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 14:40:00 33.40000 6.30683E-003 313.41284 16.86939 1.35332 0.00000
18 PERIMETER_MID_ZN_3 Heating 213421.17092 213421.17092 10.41036 10.41036 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -27.60000 3.41898E-004 313.41284 16.86939 1.35332 0.00000
19 PERIMETER_MID_ZN_2 Cooling 207805.49354 207805.49354 17.31016 17.31016 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 09:20:00 25.50667 6.29470E-003 201.97515 10.87127 0.87213 0.00000
20 PERIMETER_MID_ZN_2 Heating 141642.71545 141642.71545 6.90947 6.90947 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -27.60000 3.41898E-004 201.97515 10.87127 0.87213 0.00000
21 PERIMETER_MID_ZN_1 Cooling 246290.66715 246290.66715 20.51606 20.51606 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 13:50:00 33.26667 6.30663E-003 313.41969 16.86975 1.35335 0.00000
22 PERIMETER_MID_ZN_1 Heating 216704.94510 216704.94510 10.57085 10.57085 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -27.60000 3.41898E-004 313.41969 16.86975 1.35335 0.00000
23 PERIMETER_MID_ZN_4 Cooling 224695.19226 224695.19226 18.71708 18.71708 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 17:30:00 30.36000 6.30211E-003 201.97515 10.87127 0.87213 0.00000
24 PERIMETER_MID_ZN_4 Heating 139841.48150 139841.48150 6.82149 6.82149 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -27.60000 3.41898E-004 201.97515 10.87127 0.87213 0.00000
25 PERIMETER_TOP_ZN_3 Cooling 15383.92302 15383.92302 1.28148 1.28148 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 15:10:00 33.24000 6.30658E-003 313.41284 16.86939 0.13533 0.00000
26 PERIMETER_TOP_ZN_3 Heating 26939.42523 26939.42523 1.31453 1.31453 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -27.60000 3.41898E-004 313.41284 16.86939 0.13533 0.00000
27 PERIMETER_TOP_ZN_2 Cooling 20780.73837 20780.73837 1.73102 1.73102 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 09:40:00 26.41333 6.29608E-003 201.97515 10.87127 8.72129E-002 0.00000
28 PERIMETER_TOP_ZN_2 Heating 17784.00962 17784.00962 0.86781 0.86781 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -27.60000 3.41898E-004 201.97515 10.87127 8.72129E-002 0.00000
29 PERIMETER_TOP_ZN_1 Cooling 26241.13139 26241.13139 2.18588 2.18588 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 13:50:00 33.26667 6.30663E-003 313.41969 16.86975 0.13533 0.00000
30 PERIMETER_TOP_ZN_1 Heating 27301.99408 27301.99408 1.33224 1.33224 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -27.60000 3.41898E-004 313.41969 16.86975 0.13533 0.00000
31 PERIMETER_TOP_ZN_4 Cooling 23599.30828 23599.30828 1.96581 1.96581 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 17:30:00 30.36000 6.30211E-003 201.97515 10.87127 8.72129E-002 0.00000
32 PERIMETER_TOP_ZN_4 Heating 17794.89717 17794.89717 0.86835 0.86835 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -27.60000 3.41898E-004 201.97515 10.87127 8.72129E-002 0.00000
33 DATACENTER_BOT_ZN_6 Cooling 8909.33644 8909.33644 0.58537 0.58537 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 19:30:00 26.28000 6.29588E-003 36.20274 1.94861 1.56323E-002 0.00000
34 DATACENTER_BOT_ZN_6 Heating 0.00000 0.00000 0.00000 1.56323E-002 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 05:30:00 -27.60000 3.41898E-004 36.20274 1.94861 1.56323E-002 0.00000
35 DATACENTER_MID_ZN_6 Cooling 85682.56024 85682.56024 5.62967 5.62967 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 19:30:00 26.28000 6.29588E-003 36.20274 1.94861 0.15632 0.00000
36 DATACENTER_MID_ZN_6 Heating 0.00000 0.00000 0.00000 0.15632 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 05:40:00 -27.60000 3.41898E-004 36.20274 1.94861 0.15632 0.00000
37 DATACENTER_TOP_ZN_6 Cooling 8712.46582 8712.46582 0.57244 0.57244 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 19:30:00 26.28000 6.29588E-003 36.20274 1.94861 1.56323E-002 0.00000
38 DATACENTER_TOP_ZN_6 Heating 0.00000 0.00000 0.00000 1.56323E-002 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 05:30:00 -27.60000 3.41898E-004 36.20274 1.94861 1.56323E-002 0.00000
39 DATACENTER_BASEMENT_ZN_6 Cooling 373481.81429 373481.81429 24.53881 24.53881 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 07:00:00 18.84000 6.28481E-003 783.67941 42.18139 0.33839 0.00000
40 DATACENTER_BASEMENT_ZN_6 Heating 0.00000 0.00000 0.00000 0.33839 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 00:40:00 -27.60000 3.41898E-004 783.67941 42.18139 0.33839 0.00000


System Sizing Information

System Name Load Type Peak Load Kind User Design Capacity Calc Des Air Flow Rate [m3/s] User Des Air Flow Rate [m3/s] Design Day Name Date/Time of Peak
1 VAV_BOT WITH REHEAT Cooling Sensible 163330.59 11.65570 11.65570 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 00:00:00
2 VAV_BOT WITH REHEAT Heating Sensible 108028.99 3.55860 3.55860 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 06:30:00
3 VAV_MID WITH REHEAT Cooling Sensible 1529352.26 107.83186 107.83186 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 00:00:00
4 VAV_MID WITH REHEAT Heating Sensible 1081058.86 51.18042 51.18042 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 05:30:00
5 VAV_TOP WITH REHEAT Cooling Sensible 170548.15 12.30079 12.30079 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 00:00:00
6 VAV_TOP WITH REHEAT Heating Sensible 108460.41 8.18669 8.18669 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 01:50:00
7 CAV_BAS Cooling Sensible 82824.94 6.81911 6.81911 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 05:00:00
8 CAV_BAS Heating Sensible 85856.97 1.20016 1.20016 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 00:10:00
9 AIRLOOP DATACENTER BASEMENT Cooling Sensible 370565.49 24.53890 24.53890 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 05:00:00
10 AIRLOOP DATACENTER BASEMENT Heating Sensible 24207.99 0.33839 0.33839 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 00:10:00
11 AIRLOOP DATACENTER BOT Cooling Sensible 8783.71 0.58537 0.58537 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 05:00:00
12 AIRLOOP DATACENTER BOT Heating Sensible 1118.31 1.56323E-002 1.56323E-002 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 00:10:00
13 AIRLOOP DATACENTER MID Cooling Sensible 84469.88 5.62967 5.62967 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 05:00:00
14 AIRLOOP DATACENTER MID Heating Sensible 11183.09 0.15632 0.15632 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 00:10:00
15 AIRLOOP DATACENTER TOP Cooling Sensible 8589.36 0.57244 0.57244 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 05:00:00
16 AIRLOOP DATACENTER TOP Heating Sensible 1118.31 1.56323E-002 1.56323E-002 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 00:10:00


Component Sizing Information

Component Type Component Name Input Field Description Value
1 AirTerminal:SingleDuct:ConstantVolume:NoReheat BASEMENT DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 6.81911
2 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 7.06426
3 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.26925
4 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.28800
5 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 2.03451
6 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.71800
7 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
8 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.41505E-003
9 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 2.25635E-004
10 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 2.03451
11 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
12 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
13 Coil:Heating:Water CORE_BOTTOM VAV BOX REHEAT COIL Design Size Rated Capacity [W] 25791.50526
14 Coil:Heating:Water CORE_BOTTOM VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 2.25635E-004
15 Coil:Heating:Water CORE_BOTTOM VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 543.50738
16 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 66.52664
17 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.28591
18 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.29900
19 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 19.89147
20 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.76242
21 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
22 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.33260E-003
23 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 4.50870E-003
24 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 19.89147
25 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
26 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
27 Coil:Heating:Water CORE_MID VAV BOX REHEAT COIL Design Size Rated Capacity [W] 515371.91356
28 Coil:Heating:Water CORE_MID VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 4.50870E-003
29 Coil:Heating:Water CORE_MID VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 12910.41781
30 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 6.43541
31 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.29556
32 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.32000
33 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 2.05933
34 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.78816
35 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
36 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.28908E-003
37 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 9.76791E-004
38 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 3.80376
39 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
40 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
41 Coil:Heating:Water CORE_TOP VAV BOX REHEAT COIL Design Size Rated Capacity [W] 111653.25213
42 Coil:Heating:Water CORE_TOP VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 9.76791E-004
43 Coil:Heating:Water CORE_TOP VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 2946.06819
44 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 1.19693
45 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.19953
46 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.21300
47 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.25495
48 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.53207
49 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
50 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.90951E-003
51 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.89227E-004
52 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.73778
53 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
54 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
55 Coil:Heating:Water PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 21629.81784
56 Coil:Heating:Water PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.89227E-004
57 Coil:Heating:Water PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 570.40028
58 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 1.62265
59 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 9.48482E-002
60 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.20000
61 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.32453
62 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.30000
63 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
64 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 4.01695E-003
65 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.29481E-004
66 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.50489
67 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
68 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
69 Coil:Heating:Water PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 14800.43298
70 Coil:Heating:Water PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.29481E-004
71 Coil:Heating:Water PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 390.28326
72 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 2.00831
73 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.11892
74 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.20000
75 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.40166
76 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.31712
77 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
78 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 3.20387E-003
79 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 2.07298E-004
80 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.80836
81 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
82 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
83 Coil:Heating:Water PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 23695.43660
84 Coil:Heating:Water PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 2.07298E-004
85 Coil:Heating:Water PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 624.83133
86 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 1.98992
87 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 7.73424E-002
88 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.20000
89 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.39798
90 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.30000
91 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
92 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 4.92615E-003
93 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.10243E-004
94 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.42974
95 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
96 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
97 Coil:Heating:Water PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 12601.40517
98 Coil:Heating:Water PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.10243E-004
99 Coil:Heating:Water PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 332.34214
100 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 11.39885
101 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.20951
102 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.21900
103 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 2.49635
104 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.55870
105 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
106 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.81850E-003
107 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 2.66844E-003
108 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 10.41036
109 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
110 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
111 Coil:Heating:Water PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 305019.34868
112 Coil:Heating:Water PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 2.66844E-003
113 Coil:Heating:Water PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 8041.45526
114 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_2 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 17.31016
115 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_2 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 8.89102E-002
116 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_2 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.20000
117 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_2 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 3.46203
118 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_2 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.30000
119 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_2 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
120 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_2 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 4.28522E-003
121 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_2 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.77101E-003
122 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 6.90947
123 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
124 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
125 Coil:Heating:Water PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 202437.02019
126 Coil:Heating:Water PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.77101E-003
127 Coil:Heating:Water PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 5336.90563
128 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 20.51606
129 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.11641
130 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.20000
131 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 4.10321
132 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.31042
133 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
134 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 3.27294E-003
135 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 2.70953E-003
136 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 10.57085
137 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
138 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
139 Coil:Heating:Water PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 309716.06669
140 Coil:Heating:Water PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 2.70953E-003
141 Coil:Heating:Water PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 8165.21188
142 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 18.71708
143 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 8.22270E-002
144 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.20000
145 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 3.74342
146 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.30000
147 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
148 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 4.63351E-003
149 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.74847E-003
150 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 6.82149
151 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
152 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
153 Coil:Heating:Water PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 199861.13769
154 Coil:Heating:Water PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.74847E-003
155 Coil:Heating:Water PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 5269.01877
156 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 1.31453
157 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.18168
158 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.20200
159 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.26553
160 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.48448
161 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
162 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 2.09712E-003
163 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 3.36861E-004
164 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 1.31453
165 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
166 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
167 Coil:Heating:Water PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 38505.23007
168 Coil:Heating:Water PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 3.36861E-004
169 Coil:Heating:Water PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 1015.02393
170 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 1.73102
171 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 8.89098E-002
172 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.20000
173 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.34620
174 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.30000
175 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
176 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 4.28524E-003
177 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 2.22379E-004
178 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.86781
179 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
180 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
181 Coil:Heating:Water PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 25419.30122
182 Coil:Heating:Water PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 2.22379E-004
183 Coil:Heating:Water PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 670.06202
184 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 2.18588
185 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.10926
186 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.20000
187 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.43718
188 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.30000
189 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
190 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 3.48715E-003
191 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 3.41397E-004
192 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 1.33224
193 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
194 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
195 Coil:Heating:Water PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 39023.78017
196 Coil:Heating:Water PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 3.41397E-004
197 Coil:Heating:Water PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 1028.68782
198 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 1.96581
199 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 7.82909E-002
200 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.20000
201 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.39316
202 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.30000
203 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
204 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 4.86647E-003
205 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 2.22516E-004
206 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.86835
207 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
208 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
209 Coil:Heating:Water PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 25434.92199
210 Coil:Heating:Water PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 2.22516E-004
211 Coil:Heating:Water PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 670.47207
212 AirTerminal:SingleDuct:ConstantVolume:NoReheat DATACENTER_BOT_ZN_6 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 0.58537
213 AirTerminal:SingleDuct:ConstantVolume:NoReheat DATACENTER_MID_ZN_6 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 5.62967
214 AirTerminal:SingleDuct:ConstantVolume:NoReheat DATACENTER_TOP_ZN_6 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 0.57244
215 AirTerminal:SingleDuct:ConstantVolume:NoReheat DATACENTER_BASEMENT_ZN_6 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 24.53881
216 AirLoopHVAC VAV_BOT WITH REHEAT Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 6.94103
217 AirLoopHVAC VAV_BOT WITH REHEAT Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 3.41363
218 AirLoopHVAC VAV_BOT WITH REHEAT Sum of Air Terminal Maximum Flow Rates [m3/s] 13.88207
219 AirLoopHVAC VAV_BOT WITH REHEAT Adjusted Heating Design Air Flow Rate [m3/s] 3.55860
220 AirLoopHVAC VAV_BOT WITH REHEAT Adjusted Cooling Design Air Flow Rate [m3/s] 11.65570
221 AirLoopHVAC VAV_BOT WITH REHEAT Adjusted Main Design Air Flow Rate [m3/s] 11.65570
222 AirLoopHVAC VAV_BOT WITH REHEAT User Heating Air Flow Ratio [] 0.30000
223 AirLoopHVAC VAV_BOT WITH REHEAT Calculated Heating Air Flow Ratio [] 0.30531
224 AirLoopHVAC VAV_MID WITH REHEAT Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 67.23440
225 AirLoopHVAC VAV_MID WITH REHEAT Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 33.69648
226 AirLoopHVAC VAV_MID WITH REHEAT Sum of Air Terminal Maximum Flow Rates [m3/s] 134.46880
227 AirLoopHVAC VAV_MID WITH REHEAT Adjusted Heating Design Air Flow Rate [m3/s] 51.18042
228 AirLoopHVAC VAV_MID WITH REHEAT Adjusted Cooling Design Air Flow Rate [m3/s] 107.83186
229 AirLoopHVAC VAV_MID WITH REHEAT Adjusted Main Design Air Flow Rate [m3/s] 107.83186
230 AirLoopHVAC VAV_MID WITH REHEAT User Heating Air Flow Ratio [] 0.30000
231 AirLoopHVAC VAV_MID WITH REHEAT Calculated Heating Air Flow Ratio [] 0.47463
232 AirLoopHVAC VAV_TOP WITH REHEAT Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 6.81632
233 AirLoopHVAC VAV_TOP WITH REHEAT Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 3.50141
234 AirLoopHVAC VAV_TOP WITH REHEAT Sum of Air Terminal Maximum Flow Rates [m3/s] 13.63265
235 AirLoopHVAC VAV_TOP WITH REHEAT Adjusted Heating Design Air Flow Rate [m3/s] 8.18669
236 AirLoopHVAC VAV_TOP WITH REHEAT Adjusted Cooling Design Air Flow Rate [m3/s] 12.30079
237 AirLoopHVAC VAV_TOP WITH REHEAT Adjusted Main Design Air Flow Rate [m3/s] 12.30079
238 AirLoopHVAC VAV_TOP WITH REHEAT User Heating Air Flow Ratio [] 0.30000
239 AirLoopHVAC VAV_TOP WITH REHEAT Calculated Heating Air Flow Ratio [] 0.66554
240 AirLoopHVAC CAV_BAS Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 6.81911
241 AirLoopHVAC CAV_BAS Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 6.81911
242 AirLoopHVAC CAV_BAS Sum of Air Terminal Maximum Flow Rates [m3/s] 6.81911
243 AirLoopHVAC CAV_BAS Adjusted Heating Design Air Flow Rate [m3/s] 6.81911
244 AirLoopHVAC CAV_BAS Adjusted Cooling Design Air Flow Rate [m3/s] 6.81911
245 AirLoopHVAC CAV_BAS Adjusted Main Design Air Flow Rate [m3/s] 6.81911
246 AirLoopHVAC CAV_BAS User Heating Air Flow Ratio [] 1.00000
247 AirLoopHVAC CAV_BAS Calculated Heating Air Flow Ratio [] 1.00000
248 AirLoopHVAC AIRLOOP DATACENTER BASEMENT Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 24.53881
249 AirLoopHVAC AIRLOOP DATACENTER BASEMENT Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 24.53881
250 AirLoopHVAC AIRLOOP DATACENTER BASEMENT Sum of Air Terminal Maximum Flow Rates [m3/s] 24.53881
251 AirLoopHVAC AIRLOOP DATACENTER BASEMENT Adjusted Heating Design Air Flow Rate [m3/s] 24.53881
252 AirLoopHVAC AIRLOOP DATACENTER BASEMENT Adjusted Cooling Design Air Flow Rate [m3/s] 24.53890
253 AirLoopHVAC AIRLOOP DATACENTER BASEMENT Adjusted Main Design Air Flow Rate [m3/s] 24.53890
254 AirLoopHVAC AIRLOOP DATACENTER BASEMENT User Heating Air Flow Ratio [] 1.00000
255 AirLoopHVAC AIRLOOP DATACENTER BASEMENT Calculated Heating Air Flow Ratio [] 1.00000
256 AirLoopHVAC AIRLOOP DATACENTER BOT Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 0.58537
257 AirLoopHVAC AIRLOOP DATACENTER BOT Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 0.58537
258 AirLoopHVAC AIRLOOP DATACENTER BOT Sum of Air Terminal Maximum Flow Rates [m3/s] 0.58537
259 AirLoopHVAC AIRLOOP DATACENTER BOT Adjusted Heating Design Air Flow Rate [m3/s] 0.58537
260 AirLoopHVAC AIRLOOP DATACENTER BOT Adjusted Cooling Design Air Flow Rate [m3/s] 0.58537
261 AirLoopHVAC AIRLOOP DATACENTER BOT Adjusted Main Design Air Flow Rate [m3/s] 0.58537
262 AirLoopHVAC AIRLOOP DATACENTER BOT User Heating Air Flow Ratio [] 1.00000
263 AirLoopHVAC AIRLOOP DATACENTER BOT Calculated Heating Air Flow Ratio [] 1.00000
264 AirLoopHVAC AIRLOOP DATACENTER MID Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 5.62967
265 AirLoopHVAC AIRLOOP DATACENTER MID Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 5.62967
266 AirLoopHVAC AIRLOOP DATACENTER MID Sum of Air Terminal Maximum Flow Rates [m3/s] 5.62967
267 AirLoopHVAC AIRLOOP DATACENTER MID Adjusted Heating Design Air Flow Rate [m3/s] 5.62967
268 AirLoopHVAC AIRLOOP DATACENTER MID Adjusted Cooling Design Air Flow Rate [m3/s] 5.62967
269 AirLoopHVAC AIRLOOP DATACENTER MID Adjusted Main Design Air Flow Rate [m3/s] 5.62967
270 AirLoopHVAC AIRLOOP DATACENTER MID User Heating Air Flow Ratio [] 1.00000
271 AirLoopHVAC AIRLOOP DATACENTER MID Calculated Heating Air Flow Ratio [] 1.00000
272 AirLoopHVAC AIRLOOP DATACENTER TOP Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 0.57244
273 AirLoopHVAC AIRLOOP DATACENTER TOP Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 0.57244
274 AirLoopHVAC AIRLOOP DATACENTER TOP Sum of Air Terminal Maximum Flow Rates [m3/s] 0.57244
275 AirLoopHVAC AIRLOOP DATACENTER TOP Adjusted Heating Design Air Flow Rate [m3/s] 0.57244
276 AirLoopHVAC AIRLOOP DATACENTER TOP Adjusted Cooling Design Air Flow Rate [m3/s] 0.57244
277 AirLoopHVAC AIRLOOP DATACENTER TOP Adjusted Main Design Air Flow Rate [m3/s] 0.57244
278 AirLoopHVAC AIRLOOP DATACENTER TOP User Heating Air Flow Ratio [] 1.00000
279 AirLoopHVAC AIRLOOP DATACENTER TOP Calculated Heating Air Flow Ratio [] 1.00000
280 AirLoopHVAC VAV_BOT WITH REHEAT Design Supply Air Flow Rate [m3/s] 11.65570
281 AirLoopHVAC VAV_MID WITH REHEAT Design Supply Air Flow Rate [m3/s] 107.83186
282 AirLoopHVAC VAV_TOP WITH REHEAT Design Supply Air Flow Rate [m3/s] 12.30079
283 AirLoopHVAC CAV_BAS Design Supply Air Flow Rate [m3/s] 6.81911
284 AirLoopHVAC AIRLOOP DATACENTER BASEMENT Design Supply Air Flow Rate [m3/s] 24.53890
285 AirLoopHVAC AIRLOOP DATACENTER BOT Design Supply Air Flow Rate [m3/s] 0.58537
286 AirLoopHVAC AIRLOOP DATACENTER MID Design Supply Air Flow Rate [m3/s] 5.62967
287 AirLoopHVAC AIRLOOP DATACENTER TOP Design Supply Air Flow Rate [m3/s] 0.57244
288 Controller:OutdoorAir VAV_BOT WITH REHEAT_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 11.65570
289 Coil:Cooling:Water VAV_BOT WITH REHEAT COOLING COIL Design Size Design Inlet Air Temperature [C] 26.04686
290 Coil:Cooling:Water VAV_BOT WITH REHEAT COOLING COIL Design Size Design Inlet Water Temperature [C] 6.67000
291 Coil:Cooling:Water VAV_BOT WITH REHEAT COOLING COIL Design Size Design Outlet Air Temperature [C] 10.68118
292 Coil:Cooling:Water VAV_BOT WITH REHEAT COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 7.08318E-003
293 Coil:Cooling:Water VAV_BOT WITH REHEAT COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 7.00000E-003
294 Coil:Cooling:Water VAV_BOT WITH REHEAT COOLING COIL Design Size Design Coil Load [W] 194585.28567
295 Coil:Cooling:Water VAV_BOT WITH REHEAT COOLING COIL Design Size Design Water Flow Rate [m3/s] 8.27811E-003
296 Coil:Cooling:Water VAV_BOT WITH REHEAT COOLING COIL Design Size Design Air Flow Rate [m3/s] 11.65570
297 Coil:Heating:Water VAV_BOT WITH REHEAT HEATING COIL Design Size Rated Capacity [W] 101691.05047
298 Coil:Heating:Water VAV_BOT WITH REHEAT HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 8.89638E-004
299 Coil:Heating:Water VAV_BOT WITH REHEAT HEATING COIL Design Size U-Factor Times Area Value [W/K] 1578.76896
300 Fan:VariableVolume VAV_BOT WITH REHEAT FAN Design Size Maximum Flow Rate [m3/s] 11.65570
301 Controller:WaterCoil VAV_BOT WITH REHEAT_COOLC_CONTROLLER Maximum Actuated Flow [m3/s] 8.27811E-003
302 Controller:WaterCoil VAV_BOT WITH REHEAT_COOLC_CONTROLLER Controller Convergence Tolerance 5.75241E-005
303 Controller:WaterCoil VAV_BOT WITH REHEAT_HEATC_CONTROLLER Maximum Actuated Flow [m3/s] 8.89638E-004
304 Controller:OutdoorAir VAV_MID WITH REHEAT_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 107.83186
305 Coil:Cooling:Water VAV_MID WITH REHEAT COOLING COIL Design Size Design Inlet Air Temperature [C] 26.21365
306 Coil:Cooling:Water VAV_MID WITH REHEAT COOLING COIL Design Size Design Inlet Water Temperature [C] 6.67000
307 Coil:Cooling:Water VAV_MID WITH REHEAT COOLING COIL Design Size Design Outlet Air Temperature [C] 10.68116
308 Coil:Cooling:Water VAV_MID WITH REHEAT COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 7.07663E-003
309 Coil:Cooling:Water VAV_MID WITH REHEAT COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 7.00000E-003
310 Coil:Cooling:Water VAV_MID WITH REHEAT COOLING COIL Design Size Design Coil Load [W] 1817578.77258
311 Coil:Cooling:Water VAV_MID WITH REHEAT COOLING COIL Design Size Design Water Flow Rate [m3/s] 7.73240E-002
312 Coil:Cooling:Water VAV_MID WITH REHEAT COOLING COIL Design Size Design Air Flow Rate [m3/s] 107.83186
313 Coil:Heating:Water VAV_MID WITH REHEAT HEATING COIL Design Size Rated Capacity [W] 1044136.00216
314 Coil:Heating:Water VAV_MID WITH REHEAT HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 9.13456E-003
315 Coil:Heating:Water VAV_MID WITH REHEAT HEATING COIL Design Size U-Factor Times Area Value [W/K] 15812.22590
316 Fan:VariableVolume VAV_MID WITH REHEAT FAN Design Size Maximum Flow Rate [m3/s] 107.83186
317 Controller:WaterCoil VAV_MID WITH REHEAT_COOLC_CONTROLLER Maximum Actuated Flow [m3/s] 7.73240E-002
318 Controller:WaterCoil VAV_MID WITH REHEAT_COOLC_CONTROLLER Controller Convergence Tolerance 6.15838E-006
319 Controller:WaterCoil VAV_MID WITH REHEAT_HEATC_CONTROLLER Maximum Actuated Flow [m3/s] 9.13456E-003
320 Controller:OutdoorAir VAV_TOP WITH REHEAT_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 12.30079
321 Coil:Cooling:Water VAV_TOP WITH REHEAT COOLING COIL Design Size Design Inlet Air Temperature [C] 25.94519
322 Coil:Cooling:Water VAV_TOP WITH REHEAT COOLING COIL Design Size Design Inlet Water Temperature [C] 6.67000
323 Coil:Cooling:Water VAV_TOP WITH REHEAT COOLING COIL Design Size Design Outlet Air Temperature [C] 10.68114
324 Coil:Cooling:Water VAV_TOP WITH REHEAT COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 7.07283E-003
325 Coil:Cooling:Water VAV_TOP WITH REHEAT COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 7.00000E-003
326 Coil:Cooling:Water VAV_TOP WITH REHEAT COOLING COIL Design Size Design Coil Load [W] 203672.51240
327 Coil:Cooling:Water VAV_TOP WITH REHEAT COOLING COIL Design Size Design Water Flow Rate [m3/s] 8.66470E-003
328 Coil:Cooling:Water VAV_TOP WITH REHEAT COOLING COIL Design Size Design Air Flow Rate [m3/s] 12.30079
329 Coil:Heating:Water VAV_TOP WITH REHEAT HEATING COIL Design Size Rated Capacity [W] 102308.45534
330 Coil:Heating:Water VAV_TOP WITH REHEAT HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 8.95039E-004
331 Coil:Heating:Water VAV_TOP WITH REHEAT HEATING COIL Design Size U-Factor Times Area Value [W/K] 1597.67593
332 Fan:VariableVolume VAV_TOP WITH REHEAT FAN Design Size Maximum Flow Rate [m3/s] 12.30079
333 Controller:WaterCoil VAV_TOP WITH REHEAT_COOLC_CONTROLLER Maximum Actuated Flow [m3/s] 8.66470E-003
334 Controller:WaterCoil VAV_TOP WITH REHEAT_COOLC_CONTROLLER Controller Convergence Tolerance 5.49575E-005
335 Controller:WaterCoil VAV_TOP WITH REHEAT_HEATC_CONTROLLER Maximum Actuated Flow [m3/s] 8.95039E-004
336 Controller:OutdoorAir CAV_BAS_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 6.81911
337 Controller:OutdoorAir CAV_BAS_OA_CONTROLLER Minimum Outdoor Air Flow Rate [m3/s] 1.20016
338 Coil:Cooling:Water CAV_BAS COOLING COIL Design Size Design Inlet Air Temperature [C] 25.70009
339 Coil:Cooling:Water CAV_BAS COOLING COIL Design Size Design Inlet Water Temperature [C] 6.67000
340 Coil:Cooling:Water CAV_BAS COOLING COIL Design Size Design Outlet Air Temperature [C] 11.22902
341 Coil:Cooling:Water CAV_BAS COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 7.23461E-003
342 Coil:Cooling:Water CAV_BAS COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 7.00000E-003
343 Coil:Cooling:Water CAV_BAS COOLING COIL Design Size Design Coil Load [W] 110073.14104
344 Coil:Cooling:Water CAV_BAS COOLING COIL Design Size Design Water Flow Rate [m3/s] 4.68277E-003
345 Coil:Cooling:Water CAV_BAS COOLING COIL Design Size Design Air Flow Rate [m3/s] 6.81911
346 Coil:Heating:Water CAV_BAS HEATING COIL Design Size Rated Capacity [W] 323708.58056
347 Coil:Heating:Water CAV_BAS HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 2.83194E-003
348 Coil:Heating:Water CAV_BAS HEATING COIL Design Size U-Factor Times Area Value [W/K] 6941.24521
349 Fan:ConstantVolume CAV_BAS FAN Design Size Maximum Flow Rate [m3/s] 6.81911
350 Controller:WaterCoil CAV_BAS_COOLC_CONTROLLER Maximum Actuated Flow [m3/s] 4.68277E-003
351 Controller:WaterCoil CAV_BAS_COOLC_CONTROLLER Controller Convergence Tolerance 1.01690E-004
352 Controller:WaterCoil CAV_BAS_HEATC_CONTROLLER Maximum Actuated Flow [m3/s] 2.83194E-003
353 Controller:OutdoorAir AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 24.53890
354 Controller:OutdoorAir AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER Minimum Outdoor Air Flow Rate [m3/s] 0.33839
355 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER BASEMENT COOLING COIL Design Size Rated Air Flow Rate [m3/s] 24.53890
356 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER BASEMENT COOLING COIL Design Size Rated Total Cooling Capacity [W] 466437.89347
357 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER BASEMENT COOLING COIL Design Size Rated Sensible Cooling Capacity [W] 262502.93893
358 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER BASEMENT COOLING COIL Design Size Rated Water Flow Rate [m3/s] 1.14230E-002
359 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP Supply Air Flow Rate [m3/s] 24.53890
360 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP Supply Air Flow Rate During Heating Operation [m3/s] 24.53890
361 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP Supply Air Flow Rate During Cooling Operation [m3/s] 24.53890
362 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] 24.53890
363 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP Nominal Heating Capacity [W] 466437.89347
364 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP Nominal Cooling Capacity [W] 466437.89347
365 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP Supplemental Heating Coil Nominal Capacity [W] 24207.99248
366 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
367 Fan:OnOff AIRLOOP DATACENTER BASEMENT SUPPLY FAN Design Size Maximum Flow Rate [m3/s] 24.53890
368 COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER BASEMENT HEATING COIL Design Size Rated Air Flow Rate [m3/s] 24.53890
369 COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER BASEMENT HEATING COIL Design Size Rated Heating Capacity [W] 466437.89347
370 COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER BASEMENT HEATING COIL Design Size Rated Water Flow Rate [m3/s] 1.14230E-002
371 Coil:Heating:Electric AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL Design Size Nominal Capacity [W] 24207.99248
372 Humidifier:Steam:Electric DATACENTER_BASEMENT_ZN_6 HUMIDIFIER Design Size Nominal Capacity Volume [m3/s] 1.91079E-004
373 Humidifier:Steam:Electric DATACENTER_BASEMENT_ZN_6 HUMIDIFIER User-Specified Nominal Capacity Volume [m3/s] 3.72000E-005
374 Humidifier:Steam:Electric DATACENTER_BASEMENT_ZN_6 HUMIDIFIER Design Size Rated Power [W] 96450.69782
375 Humidifier:Steam:Electric DATACENTER_BASEMENT_ZN_6 HUMIDIFIER User-Specified Rated Power [W] 100000.00000
376 Controller:OutdoorAir AIRLOOP DATACENTER BOT_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 0.58537
377 Controller:OutdoorAir AIRLOOP DATACENTER BOT_OA_CONTROLLER Minimum Outdoor Air Flow Rate [m3/s] 1.56323E-002
378 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER BOT COOLING COIL Design Size Rated Air Flow Rate [m3/s] 0.58537
379 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER BOT COOLING COIL Design Size Rated Total Cooling Capacity [W] 10807.08699
380 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER BOT COOLING COIL Design Size Rated Sensible Cooling Capacity [W] 6147.88501
381 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER BOT COOLING COIL Design Size Rated Water Flow Rate [m3/s] 2.64665E-004
382 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BOT DXAC HEAT PUMP Supply Air Flow Rate [m3/s] 0.58537
383 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BOT DXAC HEAT PUMP Supply Air Flow Rate During Heating Operation [m3/s] 0.58537
384 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BOT DXAC HEAT PUMP Supply Air Flow Rate During Cooling Operation [m3/s] 0.58537
385 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BOT DXAC HEAT PUMP Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] 0.58537
386 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BOT DXAC HEAT PUMP Nominal Heating Capacity [W] 10807.08699
387 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BOT DXAC HEAT PUMP Nominal Cooling Capacity [W] 10807.08699
388 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BOT DXAC HEAT PUMP Supplemental Heating Coil Nominal Capacity [W] 1118.30896
389 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BOT DXAC HEAT PUMP Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
390 Fan:OnOff AIRLOOP DATACENTER BOT SUPPLY FAN Design Size Maximum Flow Rate [m3/s] 0.58537
391 COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER BOT HEATING COIL Design Size Rated Air Flow Rate [m3/s] 0.58537
392 COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER BOT HEATING COIL Design Size Rated Heating Capacity [W] 10807.08699
393 COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER BOT HEATING COIL Design Size Rated Water Flow Rate [m3/s] 2.64665E-004
394 Coil:Heating:Electric AIRLOOP DATACENTER BOT_SUPPHEATCOIL Design Size Nominal Capacity [W] 1118.30896
395 Controller:OutdoorAir AIRLOOP DATACENTER MID_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 5.62967
396 Controller:OutdoorAir AIRLOOP DATACENTER MID_OA_CONTROLLER Minimum Outdoor Air Flow Rate [m3/s] 0.15632
397 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER MID COOLING COIL Design Size Rated Air Flow Rate [m3/s] 5.62967
398 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER MID COOLING COIL Design Size Rated Total Cooling Capacity [W] 103961.64942
399 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER MID COOLING COIL Design Size Rated Sensible Cooling Capacity [W] 59130.96952
400 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER MID COOLING COIL Design Size Rated Water Flow Rate [m3/s] 2.54601E-003
401 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER MID DXAC HEAT PUMP Supply Air Flow Rate [m3/s] 5.62967
402 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER MID DXAC HEAT PUMP Supply Air Flow Rate During Heating Operation [m3/s] 5.62967
403 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER MID DXAC HEAT PUMP Supply Air Flow Rate During Cooling Operation [m3/s] 5.62967
404 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER MID DXAC HEAT PUMP Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] 5.62967
405 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER MID DXAC HEAT PUMP Nominal Heating Capacity [W] 103961.64942
406 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER MID DXAC HEAT PUMP Nominal Cooling Capacity [W] 103961.64942
407 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER MID DXAC HEAT PUMP Supplemental Heating Coil Nominal Capacity [W] 11183.08965
408 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER MID DXAC HEAT PUMP Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
409 Fan:OnOff AIRLOOP DATACENTER MID SUPPLY FAN Design Size Maximum Flow Rate [m3/s] 5.62967
410 COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER MID HEATING COIL Design Size Rated Air Flow Rate [m3/s] 5.62967
411 COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER MID HEATING COIL Design Size Rated Heating Capacity [W] 103961.64942
412 COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER MID HEATING COIL Design Size Rated Water Flow Rate [m3/s] 2.54601E-003
413 Coil:Heating:Electric AIRLOOP DATACENTER MID_SUPPHEATCOIL Design Size Nominal Capacity [W] 11183.08965
414 Controller:OutdoorAir AIRLOOP DATACENTER TOP_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 0.57244
415 Controller:OutdoorAir AIRLOOP DATACENTER TOP_OA_CONTROLLER Minimum Outdoor Air Flow Rate [m3/s] 1.56323E-002
416 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER TOP COOLING COIL Design Size Rated Air Flow Rate [m3/s] 0.57244
417 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER TOP COOLING COIL Design Size Rated Total Cooling Capacity [W] 10570.01505
418 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER TOP COOLING COIL Design Size Rated Sensible Cooling Capacity [W] 6012.38874
419 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER TOP COOLING COIL Design Size Rated Water Flow Rate [m3/s] 2.58859E-004
420 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER TOP DXAC HEAT PUMP Supply Air Flow Rate [m3/s] 0.57244
421 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER TOP DXAC HEAT PUMP Supply Air Flow Rate During Heating Operation [m3/s] 0.57244
422 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER TOP DXAC HEAT PUMP Supply Air Flow Rate During Cooling Operation [m3/s] 0.57244
423 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER TOP DXAC HEAT PUMP Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] 0.57244
424 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER TOP DXAC HEAT PUMP Nominal Heating Capacity [W] 10570.01505
425 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER TOP DXAC HEAT PUMP Nominal Cooling Capacity [W] 10570.01505
426 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER TOP DXAC HEAT PUMP Supplemental Heating Coil Nominal Capacity [W] 1118.30896
427 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER TOP DXAC HEAT PUMP Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
428 Fan:OnOff AIRLOOP DATACENTER TOP SUPPLY FAN Design Size Maximum Flow Rate [m3/s] 0.57244
429 COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER TOP HEATING COIL Design Size Rated Air Flow Rate [m3/s] 0.57244
430 COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER TOP HEATING COIL Design Size Rated Heating Capacity [W] 10570.01505
431 COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER TOP HEATING COIL Design Size Rated Water Flow Rate [m3/s] 2.58859E-004
432 Coil:Heating:Electric AIRLOOP DATACENTER TOP_SUPPHEATCOIL Design Size Nominal Capacity [W] 1118.30896
433 Pump:VariableSpeed COOLSYS1 PUMP SECONDARY Design Flow Rate [m3/s] 9.89496E-002
434 Pump:VariableSpeed COOLSYS1 PUMP SECONDARY Design Power Consumption [W] 16155.44218
435 PlantLoop COOLSYS1_DEMAND Maximum Loop Flow Rate [m3/s] 9.89496E-002
436 PlantLoop COOLSYS1_DEMAND Plant Loop Volume [m3] 11.87395
437 HeatExchanger:FluidToFluid BYPASS HEAT EXCHANGER Loop Supply Side Design Fluid Flow Rate [m3/s] 9.89496E-002
438 HeatExchanger:FluidToFluid BYPASS HEAT EXCHANGER Loop Demand Side Design Fluid Flow Rate [m3/s] 9.89496E-002
439 HeatExchanger:FluidToFluid BYPASS HEAT EXCHANGER Heat Exchanger U-Factor Times Area Value [W/C] 415341.01994
440 HeatExchanger:FluidToFluid BYPASS HEAT EXCHANGER Loop-to-loop Temperature Difference Used to Size Heat Exchanger U-Factor Times Area Value [C] 5.60000
441 PlantLoop HEATSYS1 Maximum Loop Flow Rate [m3/s] 3.01192E-002
442 PlantLoop HEATSYS1 Plant Loop Volume [m3] 3.61430
443 Pump:VariableSpeed HEATSYS1 PUMP Design Flow Rate [m3/s] 3.01192E-002
444 Pump:VariableSpeed HEATSYS1 PUMP Design Power Consumption [W] 9070.56742
445 Pump:VariableSpeed HEATSYS1 PUMP Design Minimum Flow Rate [m3/s] 0.00000
446 Boiler:HotWater HEATSYS1 BOILER Design Size Nominal Capacity [W] 3442804.65879
447 Boiler:HotWater HEATSYS1 BOILER User-Specified Nominal Capacity [W] 3442804.66000
448 Boiler:HotWater HEATSYS1 BOILER Design Size Design Water Flow Rate [m3/s] 3.01192E-002
449 PlantLoop COOLSYS1_SUPPLY Maximum Loop Flow Rate [m3/s] 9.89496E-002
450 PlantLoop COOLSYS1_SUPPLY Plant Loop Volume [m3] 11.87395
451 Pump:ConstantSpeed COOLSYS1 CHILLER1 PUMP Design Flow Rate [m3/s] 4.94748E-002
452 Pump:ConstantSpeed COOLSYS1 CHILLER1 PUMP Design Power Consumption [W] 5592.47872
453 Pump:ConstantSpeed COOLSYS1 CHILLER2 PUMP Design Flow Rate [m3/s] 4.94748E-002
454 Pump:ConstantSpeed COOLSYS1 CHILLER2 PUMP Design Power Consumption [W] 5592.47872
455 Chiller:Electric:ReformulatedEIR COOLSYS1 CHILLER1 Design Size Reference Chilled Water Flow Rate [m3/s] 9.89496E-002
456 Chiller:Electric:ReformulatedEIR COOLSYS1 CHILLER1 User-Specified Reference Chilled Water Flow Rate [m3/s] 4.98509E-002
457 Chiller:Electric:ReformulatedEIR COOLSYS1 CHILLER1 Design Size Reference Capacity [W] 1174674.22862
458 Chiller:Electric:ReformulatedEIR COOLSYS1 CHILLER1 User-Specified Reference Capacity [W] 1180245.77000
459 Chiller:Electric:ReformulatedEIR COOLSYS1 CHILLER1 Design Size Reference Condenser Water Flow Rate [m3/s] 5.84060E-002
460 Chiller:Electric:ReformulatedEIR COOLSYS1 CHILLER2 Design Size Reference Chilled Water Flow Rate [m3/s] 9.89496E-002
461 Chiller:Electric:ReformulatedEIR COOLSYS1 CHILLER2 User-Specified Reference Chilled Water Flow Rate [m3/s] 4.98509E-002
462 Chiller:Electric:ReformulatedEIR COOLSYS1 CHILLER2 Design Size Reference Capacity [W] 1174674.22862
463 Chiller:Electric:ReformulatedEIR COOLSYS1 CHILLER2 User-Specified Reference Capacity [W] 1180245.77000
464 Chiller:Electric:ReformulatedEIR COOLSYS1 CHILLER2 Design Size Reference Condenser Water Flow Rate [m3/s] 5.84060E-002
465 PlantLoop SINGLE WATER PLANT LOOP Maximum Loop Flow Rate [m3/s] 1.44926E-002
466 PlantLoop SINGLE WATER PLANT LOOP Plant Loop Volume [m3] 1.73911
467 Pump:ConstantSpeed PLANT CIRC PUMP Design Flow Rate [m3/s] 1.44926E-002
468 Pump:ConstantSpeed PLANT CIRC PUMP Design Power Consumption [W] 3696.33058
469 FluidCooler:TwoSpeed CENTRAL TOWER Design Water Flow Rate [m3/s] 1.44926E-002
470 FluidCooler:TwoSpeed CENTRAL TOWER Air Flow Rate at High Fan Speed [m3/s] 139666.46671
471 FluidCooler:TwoSpeed CENTRAL TOWER Fluid cooler UA value at high fan speed based on nominal capacity input [W/K] 55299.26960
472 FluidCooler:TwoSpeed CENTRAL TOWER Air Flow Rate at Low Fan Speed [m3/s] 69833.23335
473 FluidCooler:TwoSpeed CENTRAL TOWER Fan Power at Low Fan Speed [W] 7879.72339
474 FluidCooler:TwoSpeed CENTRAL TOWER U-factor Times Area Value at Low Fan Speed [W/C] 20993.03634
475 Boiler:HotWater CENTRAL BOILER Design Size Nominal Capacity [W] 596969.71866
476 Boiler:HotWater CENTRAL BOILER User-Specified Nominal Capacity [W] 584202.86000
477 Boiler:HotWater CENTRAL BOILER Design Size Design Water Flow Rate [m3/s] 1.44926E-002
478 PlantLoop SWHSYS1 Maximum Loop Flow Rate [m3/s] 4.40000E-004
479 PlantLoop SWHSYS1 Plant Loop Volume [m3] 5.28000E-002
480 Pump:ConstantSpeed SWHSYS1 PUMP Design Flow Rate [m3/s] 4.40000E-004
481 Pump:ConstantSpeed SWHSYS1 PUMP Design Power Consumption [W] 56.20530
482 WaterHeater:Mixed SWHSYS1 WATER HEATER Use Side Design Flow Rate [m3/s] 4.40000E-004
483 CondenserLoop TOWERWATERSYS Maximum Loop Flow Rate [m3/s] 0.11681
484 CondenserLoop TOWERWATERSYS Condenser Loop Volume [m3] 14.01744
485 HeaderedPumps:VariableSpeed TOWERWATERSYS PUMP Design Flow Rate [m3/s] 0.11681
486 HeaderedPumps:VariableSpeed TOWERWATERSYS PUMP Design Power Consumption [W] 28920.06123
487 CoolingTower:VariableSpeed TOWERWATERSYS COOLTOWER 1 Design Air Flow Rate [m3/s] 51.61729
488 CoolingTower:VariableSpeed TOWERWATERSYS COOLTOWER 1 Nominal Capacity [W] 1402076.59805
489 CoolingTower:VariableSpeed TOWERWATERSYS COOLTOWER 1 Air Flow Rate in free convection regime [m3/s] 10.32346
490 CoolingTower:VariableSpeed TOWERWATERSYS COOLTOWER 1 Tower capacity in free convection regime at design conditions [W] 175259.57476
491 CoolingTower:VariableSpeed TOWERWATERSYS COOLTOWER 2 Design Air Flow Rate [m3/s] 51.61729
492 CoolingTower:VariableSpeed TOWERWATERSYS COOLTOWER 2 Nominal Capacity [W] 1402076.59805
493 CoolingTower:VariableSpeed TOWERWATERSYS COOLTOWER 2 Air Flow Rate in free convection regime [m3/s] 10.32346
494 CoolingTower:VariableSpeed TOWERWATERSYS COOLTOWER 2 Tower capacity in free convection regime at design conditions [W] 175259.57476
495 PlantEquipmentOperation:ComponentSetPoint WSHPPLANT OPERATION SCHEME Design Water Flow Rate [m3/s] Equipment # 47 6.06650E-002
496 PlantEquipmentOperation:ComponentSetPoint WSHPPLANT OPERATION SCHEME Design Water Flow Rate [m3/s] Equipment # 47 6.06650E-002


Water Heating Coil Capacity Information

Component Type Name Nominal Total Capacity {W}
1 Coil:Heating:Water CORE_BOTTOM VAV BOX REHEAT COIL 24454.28
2 Coil:Heating:Water CORE_MID VAV BOX REHEAT COIL 488267.08
3 Coil:Heating:Water CORE_TOP VAV BOX REHEAT COIL 105821.88
4 Coil:Heating:Water PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL 20497.98
5 Coil:Heating:Water PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL 14025.83
6 Coil:Heating:Water PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL 22455.23
7 Coil:Heating:Water PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL 11942.21
8 Coil:Heating:Water PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL 289043.43
9 Coil:Heating:Water PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL 191833.39
10 Coil:Heating:Water PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL 293493.70
11 Coil:Heating:Water PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL 189392.58
12 Coil:Heating:Water PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL 36487.65
13 Coil:Heating:Water PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL 24087.34
14 Coil:Heating:Water PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL 36978.99
15 Coil:Heating:Water PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL 24102.13
16 Coil:Heating:Water VAV_BOT WITH REHEAT HEATING COIL 69087.22
17 Coil:Heating:Water VAV_MID WITH REHEAT HEATING COIL 688507.71
18 Coil:Heating:Water VAV_TOP WITH REHEAT HEATING COIL 70434.50
19 Coil:Heating:Water CAV_BAS HEATING COIL 245432.64


Water Cooling Coil Capacity Information

Component Type Name Nominal Total Capacity {W} Nominal Sensible Capacity {W} Nominal Latent Capacity {W} Nominal Sensible Heat Ratio Nominal Coil UA Value {W/C} Nominal Coil Surface Area {m2}
1 Coil:Cooling:Water VAV_BOT WITH REHEAT COOLING COIL 328097.05 201626.38 126470.67 0.61 65619.45 665.55
2 Coil:Cooling:Water VAV_MID WITH REHEAT COOLING COIL 3043069.59 1868368.76 1174700.82 0.61 603136.28 6117.34
3 Coil:Cooling:Water VAV_TOP WITH REHEAT COOLING COIL 345420.29 212455.27 132965.02 0.62 69556.50 705.48
4 Coil:Cooling:Water CAV_BAS COOLING COIL 185004.23 115151.46 69852.76 0.62 33859.13 343.42


Chiller Standard Rating Information

Component Type Component Name IPLV in SI Units {W/W} IPLV in IP Units {Btu/W-h}
1 Chiller:Electric:ReformulatedEIR COOLSYS1 CHILLER1 6.84 23.33
2 Chiller:Electric:ReformulatedEIR COOLSYS1 CHILLER2 6.84 23.33


Zone Surfaces

Zone Name # Surfaces
1 BASEMENT 10
2 CORE_BOTTOM 8
3 CORE_MID 7
4 CORE_TOP 7
5 PERIMETER_BOT_ZN_3 18
6 PERIMETER_BOT_ZN_2 12
7 PERIMETER_BOT_ZN_1 18
8 PERIMETER_BOT_ZN_4 12
9 PERIMETER_MID_ZN_3 9
10 PERIMETER_MID_ZN_2 8
11 PERIMETER_MID_ZN_1 9
12 PERIMETER_MID_ZN_4 8
13 PERIMETER_TOP_ZN_3 9
14 PERIMETER_TOP_ZN_2 8
15 PERIMETER_TOP_ZN_1 9
16 PERIMETER_TOP_ZN_4 8
17 GROUNDFLOOR_PLENUM 11
18 MIDFLOOR_PLENUM 11
19 TOPFLOOR_PLENUM 11
20 DATACENTER_BOT_ZN_6 6
21 DATACENTER_MID_ZN_6 6
22 DATACENTER_TOP_ZN_6 6
23 DATACENTER_BASEMENT_ZN_6 10


HeatTransfer Surface

Surface Name Surface Class Base Surface Heat Transfer Algorithm Construction Nominal U (w/o film coefs) {W/m2-K} Nominal U (with film coefs) {W/m2-K} Solar Diffusing Area (Net) {m2} Area (Gross) {m2} Area (Sunlit Calc) {m2} Azimuth {deg} Tilt {deg} ~Width {m} ~Height {m} Reveal {m} ExtBoundCondition ExtConvCoeffCalc IntConvCoeffCalc SunExposure WindExposure ViewFactorToGround ViewFactorToSky ViewFactorToGround-IR ViewFactorToSky-IR #Sides
1 BASEMENT_WALL_EAST Wall   CTF - ConductionTransferFunction BASEMENT_WALL_EAST_CFACTOR 0.354 0.336   118.87 118.87 118.87 90.00 90.00 48.74 2.44 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
2 BASEMENT_WALL_SOUTH Wall   CTF - ConductionTransferFunction BASEMENT_WALL_SOUTH_CFACTOR 0.354 0.336   139.09 139.09 139.09 180.00 90.00 57.03 2.44 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
3 BASEMENT_WALL_NORTH Wall   CTF - ConductionTransferFunction BASEMENT_WALL_NORTH_CFACTOR 0.354 0.336   139.09 139.09 139.09 0.00 90.00 57.03 2.44 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
4 BASEMENT_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   118.87 118.87 118.87 270.00 90.00 48.74 2.44 0.00 DATACENTER_BASEMENT_ZN_6_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
5 BASEMENT_FLOOR Floor   CTF - ConductionTransferFunction EXT_SLAB_8IN_WITH_CARPET 3.285 1.827   2779.43 2779.43 2779.43 0.00 180.00 57.03 48.74 0.00 BASEMENT_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.00 1.00 0.00 4
6 PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   201.98 201.98 201.98 225.00 0.00 6.47 39.59 0.00 PERIMETER_BOT_ZN_2_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
7 PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   250.34 250.34 250.34 180.00 0.00 57.03 4.57 0.00 PERIMETER_BOT_ZN_1_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
8 CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   2076.77 2076.77 2076.77 180.00 0.00 52.45 39.59 0.00 CORE_BOT_ZN_5_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
9 PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   250.34 250.34 250.34 180.00 0.00 52.45 4.57 0.00 PERIMETER_BOT_ZN_3_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
10 BASEMENT_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   7126.21 7126.21 7126.21 0.00 90.00 7126.21 1.00 0.00 BASEMENT_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
11 CORE_BOT_ZN_5_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   173.00 173.00 173.00 180.00 90.00 63.05 2.74 0.00 CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
12 CORE_BOT_ZN_5_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 270.00 90.00 39.59 2.74 0.00 DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
13 CORE_BOT_ZN_5_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   173.00 173.00 173.00 0.00 90.00 63.05 2.74 0.00 CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
14 CORE_BOT_ZN_5_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 90.00 90.00 39.59 2.74 0.00 CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
15 DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   419.30 419.30 419.30 0.00 180.00 10.59 39.59 0.00 DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.00 1.00 0.00 4
16 CORE_BOT_ZN_5_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   2076.82 2076.82 2076.82 0.00 180.00 52.46 39.59 0.00 CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.00 1.00 0.00 4
17 CORE_BOT_ZN_5_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   2496.12 2496.12 2496.12 180.00 0.00 63.05 39.59 0.00 iz-CORE_BOT_ZN_5_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
18 CORE_BOTTOM_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   5064.65 5064.65 5064.65 0.00 90.00 5064.65 1.00 0.00 CORE_BOTTOM_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
19 CORE_MID_ZN_5_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   173.00 173.00 173.00 180.00 90.00 63.05 2.74 0.00 CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
20 CORE_MID_ZN_5_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 270.00 90.00 39.59 2.74 0.00 DATACENTER_MID_ZN_6_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
21 CORE_MID_ZN_5_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   173.00 173.00 173.00 0.00 90.00 63.05 2.74 0.00 CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
22 CORE_MID_ZN_5_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 90.00 90.00 39.59 2.74 0.00 CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
23 CORE_MID_ZN_5_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   2496.12 2496.12 2496.12 0.00 180.00 63.05 39.59 0.00 CORE_MID_ZN_5_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
24 CORE_MID_ZN_5_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   2496.12 2496.12 2496.12 180.00 0.00 63.05 39.59 0.00 iz-CORE_MID_ZN_5_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
25 CORE_MID_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   5064.65 5064.65 5064.65 0.00 90.00 5064.65 1.00 0.00 CORE_MID_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
26 CORE_TOP_ZN_5_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   173.00 173.00 173.00 180.00 90.00 63.05 2.74 0.00 CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
27 CORE_TOP_ZN_5_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 270.00 90.00 39.59 2.74 0.00 DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
28 CORE_TOP_ZN_5_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   173.00 173.00 173.00 0.00 90.00 63.05 2.74 0.00 CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
29 CORE_TOP_ZN_5_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 90.00 90.00 39.59 2.74 0.00 CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
30 CORE_TOP_ZN_5_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   2496.12 2496.12 2496.12 0.00 180.00 63.05 39.59 0.00 CORE_TOP_ZN_5_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
31 CORE_TOP_ZN_5_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   2496.12 2496.12 2496.12 180.00 0.00 63.05 39.59 0.00 iz-CORE_TOP_ZN_5_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
32 CORE_TOP_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   5064.65 5064.65 5064.65 0.00 90.00 5064.65 1.00 0.00 CORE_TOP_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
33 PERIMETER_BOT_ZN_3_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.895 0.789   76.91 200.61 76.91 0.00 90.00 73.11 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
34 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 Window PERIMETER_BOT_ZN_3_WALL_NORTH Window5 Detailed Fenestration WINDOW_U_0.419_SHGC_NORTH_0.4 N/A 2.381 No 23.18 23.18 23.18 0.00 90.00 13.65 1.70 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
35 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 Window PERIMETER_BOT_ZN_3_WALL_NORTH Window5 Detailed Fenestration WINDOW_U_0.419_SHGC_NORTH_0.4 N/A 2.381 No 23.18 23.18 23.18 0.00 90.00 13.65 1.70 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
36 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 Window PERIMETER_BOT_ZN_3_WALL_NORTH Window5 Detailed Fenestration WINDOW_U_0.419_SHGC_NORTH_0.4 N/A 2.381 No 23.18 23.18 23.18 0.00 90.00 13.65 1.70 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
37 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 Window PERIMETER_BOT_ZN_3_WALL_NORTH Window5 Detailed Fenestration WINDOW_U_0.419_SHGC_NORTH_0.4 N/A 2.381 No 23.18 23.18 23.18 0.00 90.00 13.65 1.70 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
38 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 Window PERIMETER_BOT_ZN_3_WALL_NORTH Window5 Detailed Fenestration WINDOW_U_0.419_SHGC_NORTH_0.4 N/A 2.381 No 23.18 23.18 23.18 0.00 90.00 13.65 1.70 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
39 PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 Door PERIMETER_BOT_ZN_3_WALL_NORTH CTF - ConductionTransferFunction SWINGING DOOR_CON 2.839 2.839   1.95 1.95 1.95 0.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
40 PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 Door PERIMETER_BOT_ZN_3_WALL_NORTH CTF - ConductionTransferFunction SWINGING DOOR_CON 2.839 2.839   1.95 1.95 1.95 0.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
41 PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 Door PERIMETER_BOT_ZN_3_WALL_NORTH CTF - ConductionTransferFunction SWINGING DOOR_CON 2.839 2.839   1.95 1.95 1.95 0.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
42 PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 Door PERIMETER_BOT_ZN_3_WALL_NORTH CTF - ConductionTransferFunction SWINGING DOOR_CON 2.839 2.839   1.95 1.95 1.95 0.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
43 PERIMETER_BOT_ZN_3_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 225.00 90.00 6.47 2.74 0.00 PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
44 CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   173.00 173.00 173.00 180.00 90.00 63.05 2.74 0.00 CORE_BOT_ZN_5_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
45 PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 135.00 90.00 6.47 2.74 0.00 PERIMETER_BOT_ZN_2_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
46 DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   2.51 2.51 2.51 180.00 90.00 0.91 2.74 0.00 DATACENTER_BOT_ZN_6_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
47 PERIMETER_BOT_ZN_3_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   250.34 250.34 250.34 0.00 180.00 52.46 6.47 0.00 PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
48 DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   63.07 63.07 63.07 0.00 180.00 11.51 4.57 0.00 DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.00 1.00 0.00 4
49 PERIMETER_BOT_ZN_3_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   313.41 313.41 313.41 180.00 0.00 63.96 6.47 0.00 iz-PERIMETER_BOT_ZN_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
50 PERIMETER_BOT_ZN_3_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   626.83 626.83 626.83 0.00 90.00 626.83 1.00 0.00 PERIMETER_BOT_ZN_3_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
51 PERIMETER_BOT_ZN_2_WALL_EAST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.895 0.789   52.57 133.74 52.57 90.00 90.00 48.74 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
52 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 Window PERIMETER_BOT_ZN_2_WALL_EAST Window5 Detailed Fenestration WINDOW_U_0.419_SHGC_EAST_0.4 N/A 2.381 No 25.75 25.75 25.75 90.00 90.00 15.43 1.67 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
53 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 Window PERIMETER_BOT_ZN_2_WALL_EAST Window5 Detailed Fenestration WINDOW_U_0.419_SHGC_EAST_0.4 N/A 2.381 No 25.75 25.75 25.75 90.00 90.00 15.43 1.67 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
54 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 Window PERIMETER_BOT_ZN_2_WALL_EAST Window5 Detailed Fenestration WINDOW_U_0.419_SHGC_EAST_0.4 N/A 2.381 No 25.75 25.75 25.75 90.00 90.00 15.43 1.67 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
55 PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 Door PERIMETER_BOT_ZN_2_WALL_EAST CTF - ConductionTransferFunction SWINGING DOOR_CON 2.839 2.839   1.95 1.95 1.95 90.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
56 PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 Door PERIMETER_BOT_ZN_2_WALL_EAST CTF - ConductionTransferFunction SWINGING DOOR_CON 2.839 2.839   1.95 1.95 1.95 90.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
57 PERIMETER_BOT_ZN_2_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 315.00 90.00 6.47 2.74 0.00 PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
58 CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 270.00 90.00 39.59 2.74 0.00 CORE_BOT_ZN_5_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
59 PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 225.00 90.00 6.47 2.74 0.00 PERIMETER_BOT_ZN_1_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
60 PERIMETER_BOT_ZN_2_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   201.98 201.98 201.98 45.00 180.00 6.47 48.74 0.00 PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
61 PERIMETER_BOT_ZN_2_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   201.98 201.98 201.98 225.00 0.00 6.47 39.59 0.00 iz-PERIMETER_BOT_ZN_2_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
62 PERIMETER_BOT_ZN_2_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   403.95 403.95 403.95 0.00 90.00 403.95 1.00 0.00 PERIMETER_BOT_ZN_2_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
63 PERIMETER_BOT_ZN_1_WALL_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.895 0.789   76.91 200.61 76.91 180.00 90.00 73.11 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
64 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 Window PERIMETER_BOT_ZN_1_WALL_SOUTH Window5 Detailed Fenestration WINDOW_U_0.419_SHGC_SOUTH_0.4 N/A 2.381 No 23.18 23.18 23.18 180.00 90.00 13.65 1.70 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
65 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 Window PERIMETER_BOT_ZN_1_WALL_SOUTH Window5 Detailed Fenestration WINDOW_U_0.419_SHGC_SOUTH_0.4 N/A 2.381 No 23.18 23.18 23.18 180.00 90.00 13.65 1.70 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
66 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 Window PERIMETER_BOT_ZN_1_WALL_SOUTH Window5 Detailed Fenestration WINDOW_U_0.419_SHGC_SOUTH_0.4 N/A 2.381 No 23.18 23.18 23.18 180.00 90.00 13.65 1.70 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
67 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 Window PERIMETER_BOT_ZN_1_WALL_SOUTH Window5 Detailed Fenestration WINDOW_U_0.419_SHGC_SOUTH_0.4 N/A 2.381 No 23.18 23.18 23.18 180.00 90.00 13.65 1.70 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
68 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 Window PERIMETER_BOT_ZN_1_WALL_SOUTH Window5 Detailed Fenestration WINDOW_U_0.419_SHGC_SOUTH_0.4 N/A 2.381 No 23.18 23.18 23.18 180.00 90.00 13.65 1.70 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
69 PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 Door PERIMETER_BOT_ZN_1_WALL_SOUTH CTF - ConductionTransferFunction SWINGING DOOR_CON 2.839 2.839   1.95 1.95 1.95 180.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
70 PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 Door PERIMETER_BOT_ZN_1_WALL_SOUTH CTF - ConductionTransferFunction SWINGING DOOR_CON 2.839 2.839   1.95 1.95 1.95 180.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
71 PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 Door PERIMETER_BOT_ZN_1_WALL_SOUTH CTF - ConductionTransferFunction SWINGING DOOR_CON 2.839 2.839   1.95 1.95 1.95 180.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
72 PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 Door PERIMETER_BOT_ZN_1_WALL_SOUTH CTF - ConductionTransferFunction SWINGING DOOR_CON 2.839 2.839   1.95 1.95 1.95 180.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
73 PERIMETER_BOT_ZN_1_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 45.00 90.00 6.47 2.74 0.00 PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
74 DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   2.51 2.51 2.51 0.00 90.00 0.91 2.74 0.00 DATACENTER_BOT_ZN_6_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
75 PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 315.00 90.00 6.47 2.74 0.00 PERIMETER_BOT_ZN_4_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
76 CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   173.00 173.00 173.00 0.00 90.00 63.05 2.74 0.00 CORE_BOT_ZN_5_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
77 DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   63.07 63.07 63.07 0.00 180.00 16.08 4.57 0.00 DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.00 1.00 0.00 4
78 PERIMETER_BOT_ZN_1_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   250.35 250.35 250.35 0.00 180.00 57.03 6.47 0.00 PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.00 1.00 0.00 4
79 PERIMETER_BOT_ZN_1_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   313.42 313.42 313.42 180.00 0.00 73.11 6.47 0.00 iz-PERIMETER_BOT_ZN_1_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
80 PERIMETER_BOT_ZN_1_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   626.84 626.84 626.84 0.00 90.00 626.84 1.00 0.00 PERIMETER_BOT_ZN_1_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
81 PERIMETER_BOT_ZN_4_WALL_WEST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.895 0.789   52.57 133.74 52.57 270.00 90.00 48.74 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
82 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 Window PERIMETER_BOT_ZN_4_WALL_WEST Window5 Detailed Fenestration WINDOW_U_0.419_SHGC_WEST_0.4 N/A 2.381 No 25.75 25.75 25.75 270.00 90.00 15.43 1.67 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
83 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 Window PERIMETER_BOT_ZN_4_WALL_WEST Window5 Detailed Fenestration WINDOW_U_0.419_SHGC_WEST_0.4 N/A 2.381 No 25.75 25.75 25.75 270.00 90.00 15.43 1.67 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
84 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 Window PERIMETER_BOT_ZN_4_WALL_WEST Window5 Detailed Fenestration WINDOW_U_0.419_SHGC_WEST_0.4 N/A 2.381 No 25.75 25.75 25.75 270.00 90.00 15.43 1.67 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
85 PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 Door PERIMETER_BOT_ZN_4_WALL_WEST CTF - ConductionTransferFunction SWINGING DOOR_CON 2.839 2.839   1.95 1.95 1.95 270.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
86 PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 Door PERIMETER_BOT_ZN_4_WALL_WEST CTF - ConductionTransferFunction SWINGING DOOR_CON 2.839 2.839   1.95 1.95 1.95 270.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
87 PERIMETER_BOT_ZN_4_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 135.00 90.00 6.47 2.74 0.00 PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
88 DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 90.00 90.00 39.59 2.74 0.00 DATACENTER_BOT_ZN_6_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
89 PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 45.00 90.00 6.47 2.74 0.00 PERIMETER_BOT_ZN_3_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
90 PERIMETER_BOT_ZN_4_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   201.98 201.98 201.98 315.00 180.00 6.47 39.59 0.00 PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.00 1.00 0.00 4
91 PERIMETER_BOT_ZN_4_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   201.98 201.98 201.98 135.00 0.00 6.47 48.74 0.00 iz-PERIMETER_BOT_ZN_4_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
92 PERIMETER_BOT_ZN_4_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   403.95 403.95 403.95 0.00 90.00 403.95 1.00 0.00 PERIMETER_BOT_ZN_4_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
93 PERIMETER_MID_ZN_3_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 0.851 0.755   84.71 200.61 84.71 0.00 90.00 73.11 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
94 PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW Window PERIMETER_MID_ZN_3_WALL_NORTH Window5 Detailed Fenestration WINDOW_U_0.419_SHGC_NORTH_0.4 N/A 2.381 No 115.90 115.90 115.90 0.00 90.00 73.11 1.59 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
95 PERIMETER_MID_ZN_3_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 225.00 90.00 6.47 2.74 0.00 PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
96 CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   173.00 173.00 173.00 180.00 90.00 63.05 2.74 0.00 CORE_MID_ZN_5_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
97 PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 135.00 90.00 6.47 2.74 0.00 PERIMETER_MID_ZN_2_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
98 DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   2.51 2.51 2.51 180.00 90.00 0.91 2.74 0.00 DATACENTER_MID_ZN_6_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
99 PERIMETER_MID_ZN_3_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   313.41 313.41 313.41 0.00 180.00 63.96 6.47 0.00 PERIMETER_MID_ZN_3_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
100 PERIMETER_MID_ZN_3_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   313.41 313.41 313.41 180.00 0.00 63.96 6.47 0.00 iz-PERIMETER_MID_ZN_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
101 PERIMETER_MID_ZN_3_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   626.83 626.83 626.83 0.00 90.00 626.83 1.00 0.00 PERIMETER_MID_ZN_3_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
102 PERIMETER_MID_ZN_2_WALL_EAST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 0.851 0.755   56.47 133.74 56.47 90.00 90.00 48.74 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
103 PERIMETER_MID_ZN_2_WALL_EAST_WINDOW Window PERIMETER_MID_ZN_2_WALL_EAST Window5 Detailed Fenestration WINDOW_U_0.419_SHGC_EAST_0.4 N/A 2.381 No 77.26 77.26 77.26 90.00 90.00 48.74 1.59 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
104 PERIMETER_MID_ZN_2_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 315.00 90.00 6.47 2.74 0.00 PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
105 CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 270.00 90.00 39.59 2.74 0.00 CORE_MID_ZN_5_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
106 PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 225.00 90.00 6.47 2.74 0.00 PERIMETER_MID_ZN_1_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
107 PERIMETER_MID_ZN_2_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   201.98 201.98 201.98 45.00 180.00 6.47 48.74 0.00 PERIMETER_MID_ZN_2_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
108 PERIMETER_MID_ZN_2_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   201.98 201.98 201.98 225.00 0.00 6.47 39.59 0.00 iz-PERIMETER_MID_ZN_2_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
109 PERIMETER_MID_ZN_2_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   403.95 403.95 403.95 0.00 90.00 403.95 1.00 0.00 PERIMETER_MID_ZN_2_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
110 PERIMETER_MID_ZN_1_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 45.00 90.00 6.47 2.74 0.00 PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
111 PERIMETER_MID_ZN_1_WALL_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 0.851 0.755   84.71 200.61 84.71 180.00 90.00 73.11 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
112 PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW Window PERIMETER_MID_ZN_1_WALL_SOUTH Window5 Detailed Fenestration WINDOW_U_0.419_SHGC_SOUTH_0.4 N/A 2.381 No 115.90 115.90 115.90 180.00 90.00 73.11 1.59 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
113 DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   2.51 2.51 2.51 0.00 90.00 0.91 2.74 0.00 DATACENTER_MID_ZN_6_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
114 PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 315.00 90.00 6.47 2.74 0.00 PERIMETER_MID_ZN_4_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
115 CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   173.00 173.00 173.00 0.00 90.00 63.05 2.74 0.00 CORE_MID_ZN_5_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
116 PERIMETER_MID_ZN_1_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   313.42 313.42 313.42 0.00 180.00 73.11 6.47 0.00 PERIMETER_MID_ZN_1_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
117 PERIMETER_MID_ZN_1_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   313.42 313.42 313.42 180.00 0.00 73.11 6.47 0.00 iz-PERIMETER_MID_ZN_1_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
118 PERIMETER_MID_ZN_1_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   626.84 626.84 626.84 0.00 90.00 626.84 1.00 0.00 PERIMETER_MID_ZN_1_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
119 PERIMETER_MID_ZN_4_WALL_WEST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 0.851 0.755   56.47 133.74 56.47 270.00 90.00 48.74 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
120 PERIMETER_MID_ZN_4_WALL_WEST_WINDOW Window PERIMETER_MID_ZN_4_WALL_WEST Window5 Detailed Fenestration WINDOW_U_0.419_SHGC_WEST_0.4 N/A 2.381 No 77.26 77.26 77.26 270.00 90.00 48.74 1.59 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
121 PERIMETER_MID_ZN_4_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 135.00 90.00 6.47 2.74 0.00 PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
122 DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 90.00 90.00 39.59 2.74 0.00 DATACENTER_MID_ZN_6_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
123 PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 45.00 90.00 6.47 2.74 0.00 PERIMETER_MID_ZN_3_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
124 PERIMETER_MID_ZN_4_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   201.98 201.98 201.98 315.00 180.00 6.47 39.59 0.00 PERIMETER_MID_ZN_4_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
125 PERIMETER_MID_ZN_4_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   201.98 201.98 201.98 135.00 0.00 6.47 48.74 0.00 iz-PERIMETER_MID_ZN_4_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
126 PERIMETER_MID_ZN_4_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   403.95 403.95 403.95 0.00 90.00 403.95 1.00 0.00 PERIMETER_MID_ZN_4_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
127 PERIMETER_TOP_ZN_3_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.077 0.928   84.71 200.61 84.71 0.00 90.00 73.11 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
128 PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW Window PERIMETER_TOP_ZN_3_WALL_NORTH Window5 Detailed Fenestration WINDOW_U_0.419_SHGC_NORTH_0.4 N/A 2.381 No 115.90 115.90 115.90 0.00 90.00 73.11 1.59 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
129 PERIMETER_TOP_ZN_3_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 225.00 90.00 6.47 2.74 0.00 PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
130 CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   173.00 173.00 173.00 180.00 90.00 63.05 2.74 0.00 CORE_TOP_ZN_5_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
131 PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 135.00 90.00 6.47 2.74 0.00 PERIMETER_TOP_ZN_2_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
132 DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   2.51 2.51 2.51 180.00 90.00 0.91 2.74 0.00 DATACENTER_TOP_ZN_6_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
133 PERIMETER_TOP_ZN_3_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   313.41 313.41 313.41 0.00 180.00 63.96 6.47 0.00 PERIMETER_TOP_ZN_3_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
134 PERIMETER_TOP_ZN_3_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   313.41 313.41 313.41 180.00 0.00 63.96 6.47 0.00 iz-PERIMETER_TOP_ZN_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
135 PERIMETER_TOP_ZN_3_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   626.83 626.83 626.83 0.00 90.00 626.83 1.00 0.00 PERIMETER_TOP_ZN_3_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
136 PERIMETER_TOP_ZN_2_WALL_EAST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.077 0.928   56.47 133.74 56.47 90.00 90.00 48.74 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
137 PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW Window PERIMETER_TOP_ZN_2_WALL_EAST Window5 Detailed Fenestration WINDOW_U_0.419_SHGC_EAST_0.4 N/A 2.381 No 77.26 77.26 77.26 90.00 90.00 48.74 1.59 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
138 PERIMETER_TOP_ZN_2_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 315.00 90.00 6.47 2.74 0.00 PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
139 CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 270.00 90.00 39.59 2.74 0.00 CORE_TOP_ZN_5_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
140 INT-PER3S-NE-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 225.00 90.00 6.47 2.74 0.00 INT-PER3S-NE Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
141 PERIMETER_TOP_ZN_2_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   201.98 201.98 201.98 45.00 180.00 6.47 48.74 0.00 PERIMETER_TOP_ZN_2_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
142 PERIMETER_TOP_ZN_2_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   201.98 201.98 201.98 225.00 0.00 6.47 39.59 0.00 iz-PERIMETER_TOP_ZN_2_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
143 PERIMETER_TOP_ZN_2_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   403.95 403.95 403.95 0.00 90.00 403.95 1.00 0.00 PERIMETER_TOP_ZN_2_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
144 PERIMETER_TOP_ZN_1_WALL_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.077 0.928   84.71 200.61 84.71 180.00 90.00 73.11 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
145 PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW Window PERIMETER_TOP_ZN_1_WALL_SOUTH Window5 Detailed Fenestration WINDOW_U_0.419_SHGC_SOUTH_0.4 N/A 2.381 No 115.90 115.90 115.90 180.00 90.00 73.11 1.59 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
146 INT-PER3S-NE Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 45.00 90.00 6.47 2.74 0.00 INT-PER3S-NE-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
147 DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   2.51 2.51 2.51 0.00 90.00 0.91 2.74 0.00 DATACENTER_TOP_ZN_6_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
148 PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 315.00 90.00 6.47 2.74 0.00 PERIMETER_TOP_ZN_4_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
149 CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   173.00 173.00 173.00 0.00 90.00 63.05 2.74 0.00 CORE_TOP_ZN_5_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
150 PERIMETER_TOP_ZN_1_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   313.42 313.42 313.42 0.00 180.00 73.11 6.47 0.00 PERIMETER_TOP_ZN_1_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
151 PERIMETER_TOP_ZN_1_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   313.42 313.42 313.42 180.00 0.00 73.11 6.47 0.00 iz-PERIMETER_TOP_ZN_1_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
152 PERIMETER_TOP_ZN_1_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   626.84 626.84 626.84 0.00 90.00 626.84 1.00 0.00 PERIMETER_TOP_ZN_1_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
153 PERIMETER_TOP_ZN_4_WALL_WEST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.077 0.928   56.47 133.74 56.47 270.00 90.00 48.74 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
154 PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW Window PERIMETER_TOP_ZN_4_WALL_WEST Window5 Detailed Fenestration WINDOW_U_0.419_SHGC_WEST_0.4 N/A 2.381 No 77.26 77.26 77.26 270.00 90.00 48.74 1.59 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
155 PERIMETER_TOP_ZN_4_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 135.00 90.00 6.47 2.74 0.00 PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
156 DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 90.00 90.00 39.59 2.74 0.00 DATACENTER_TOP_ZN_6_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
157 PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 45.00 90.00 6.47 2.74 0.00 PERIMETER_TOP_ZN_3_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
158 PERIMETER_TOP_ZN_4_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   201.98 201.98 201.98 315.00 180.00 6.47 39.59 0.00 PERIMETER_TOP_ZN_4_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
159 PERIMETER_TOP_ZN_4_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   201.98 201.98 201.98 135.00 0.00 6.47 48.74 0.00 iz-PERIMETER_TOP_ZN_4_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
160 PERIMETER_TOP_ZN_4_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   403.95 403.95 403.95 0.00 90.00 403.95 1.00 0.00 PERIMETER_TOP_ZN_4_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
161 GROUNDFLOOR_PLENUM_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.895 0.789   89.13 89.13 89.13 0.00 90.00 73.11 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
162 GROUNDFLOOR_PLENUM_WEST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.895 0.789   59.42 59.42 59.42 270.00 90.00 48.74 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
163 GROUNDFLOOR_PLENUM_WALL_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.895 0.789   89.13 89.13 89.13 180.00 90.00 73.11 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
164 GROUNDFLOOR_PLENUM_WALL_EAST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.895 0.789   59.42 59.42 59.42 90.00 90.00 48.74 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
165 iz-CORE_BOT_ZN_5_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   2496.12 2496.12 2496.12 0.00 180.00 63.05 39.59 0.00 CORE_BOT_ZN_5_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
166 iz-PERIMETER_BOT_ZN_3_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   313.41 313.41 313.41 0.00 180.00 63.96 6.47 0.00 PERIMETER_BOT_ZN_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
167 iz-PERIMETER_BOT_ZN_2_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   201.98 201.98 201.98 45.00 180.00 6.47 48.74 0.00 PERIMETER_BOT_ZN_2_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
168 iz-PERIMETER_BOT_ZN_1_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   313.42 313.42 313.42 0.00 180.00 73.11 6.47 0.00 PERIMETER_BOT_ZN_1_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
169 iz-PERIMETER_BOT_ZN_4_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   201.98 201.98 201.98 315.00 180.00 6.47 39.59 0.00 PERIMETER_BOT_ZN_4_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
170 iz-DATACENTER_BOT_ZN_6_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   36.20 36.20 36.20 0.00 180.00 0.91 39.59 0.00 DATACENTER_BOT_ZN_6_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
171 GROUNDFLOOR_PLENUM_CEILING Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   3563.11 3563.11 3563.11 180.00 0.00 73.11 48.74 0.00 GROUNDFLOOR_PLENUM_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
172 MIDFLOOR_PLENUM_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 0.851 0.755   89.13 89.13 89.13 0.00 90.00 73.11 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
173 MIDFLOOR_PLENUM_WALL_WEST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 0.851 0.755   59.42 59.42 59.42 270.00 90.00 48.74 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
174 MIDFLOOR_PLENUM_WALL_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 0.851 0.755   89.13 89.13 89.13 180.00 90.00 73.11 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
175 MIDFLOOR_PLENUM_WALL_EAST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 0.851 0.755   59.42 59.42 59.42 90.00 90.00 48.74 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
176 iz-CORE_MID_ZN_5_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   2496.12 2496.12 2496.12 0.00 180.00 63.05 39.59 0.00 CORE_MID_ZN_5_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
177 iz-PERIMETER_MID_ZN_3_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   313.41 313.41 313.41 0.00 180.00 63.96 6.47 0.00 PERIMETER_MID_ZN_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
178 iz-PERIMETER_MID_ZN_2_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   201.98 201.98 201.98 45.00 180.00 6.47 48.74 0.00 PERIMETER_MID_ZN_2_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
179 iz-PERIMETER_MID_ZN_1_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   313.42 313.42 313.42 0.00 180.00 73.11 6.47 0.00 PERIMETER_MID_ZN_1_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
180 iz-PERIMETER_MID_ZN_4_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   201.98 201.98 201.98 315.00 180.00 6.47 39.59 0.00 PERIMETER_MID_ZN_4_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
181 iz-DATACENTER_MID_ZN_6_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   36.20 36.20 36.20 0.00 180.00 0.91 39.59 0.00 DATACENTER_MID_ZN_6_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
182 MIDFLOOR_PLENUM_CEILING Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   3563.11 3563.11 3563.11 180.00 0.00 73.11 48.74 0.00 MIDFLOOR_PLENUM_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
183 TOPFLOOR_PLENUM_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.077 0.928   89.13 89.13 89.13 180.00 90.00 73.11 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
184 TOPFLOOR_PLENUM_WALL_EAST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.077 0.928   59.42 59.42 59.42 90.00 90.00 48.74 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
185 TOPFLOOR_PLENUM_WALL_WEST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.077 0.928   59.42 59.42 59.42 270.00 90.00 48.74 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
186 TOPFLOOR_PLENUM_WALL_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.077 0.928   89.13 89.13 89.13 0.00 90.00 73.11 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
187 iz-CORE_TOP_ZN_5_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   2496.12 2496.12 2496.12 0.00 180.00 63.05 39.59 0.00 CORE_TOP_ZN_5_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
188 iz-PERIMETER_TOP_ZN_3_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   313.41 313.41 313.41 0.00 180.00 63.96 6.47 0.00 PERIMETER_TOP_ZN_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
189 iz-PERIMETER_TOP_ZN_2_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   201.98 201.98 201.98 45.00 180.00 6.47 48.74 0.00 PERIMETER_TOP_ZN_2_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
190 iz-PERIMETER_TOP_ZN_1_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   313.42 313.42 313.42 0.00 180.00 73.11 6.47 0.00 PERIMETER_TOP_ZN_1_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
191 iz-PERIMETER_TOP_ZN_4_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   201.98 201.98 201.98 315.00 180.00 6.47 39.59 0.00 PERIMETER_TOP_ZN_4_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
192 iz-DATACENTER_TOP_ZN_6_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   36.20 36.20 36.20 0.00 180.00 0.91 39.59 0.00 DATACENTER_TOP_ZN_6_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
193 BUILDING_ROOF Roof   CTF - ConductionTransferFunction NONRES_ROOF 0.186 0.180   3563.11 3563.11 3563.11 180.00 0.00 73.11 48.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 4
194 DATACENTER_BOT_ZN_6_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   2.51 2.51 2.51 0.00 90.00 0.91 2.74 0.00 DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
195 DATACENTER_BOT_ZN_6_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   2.51 2.51 2.51 180.00 90.00 0.91 2.74 0.00 DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
196 DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 90.00 90.00 39.59 2.74 0.00 CORE_BOT_ZN_5_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
197 DATACENTER_BOT_ZN_6_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 270.00 90.00 39.59 2.74 0.00 DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
198 DATACENTER_BOT_ZN_6_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   36.20 36.20 36.20 0.00 180.00 0.91 39.59 0.00 DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.00 1.00 0.00 4
199 DATACENTER_BOT_ZN_6_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   36.20 36.20 36.20 180.00 0.00 0.91 39.59 0.00 iz-DATACENTER_BOT_ZN_6_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
200 DATACENTER_MID_ZN_6_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 270.00 90.00 39.59 2.74 0.00 DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
201 DATACENTER_MID_ZN_6_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   2.51 2.51 2.51 180.00 90.00 0.91 2.74 0.00 DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
202 DATACENTER_MID_ZN_6_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 90.00 90.00 39.59 2.74 0.00 CORE_MID_ZN_5_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
203 DATACENTER_MID_ZN_6_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   2.51 2.51 2.51 0.00 90.00 0.91 2.74 0.00 DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
204 DATACENTER_MID_ZN_6_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   36.20 36.20 36.20 0.00 180.00 0.91 39.59 0.00 DATACENTER_MID_ZN_6_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.00 1.00 0.00 4
205 DATACENTER_MID_ZN_6_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   36.20 36.20 36.20 180.00 0.00 0.91 39.59 0.00 iz-DATACENTER_MID_ZN_6_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
206 DATACENTER_TOP_ZN_6_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 90.00 90.00 39.59 2.74 0.00 CORE_TOP_ZN_5_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
207 DATACENTER_TOP_ZN_6_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 270.00 90.00 39.59 2.74 0.00 DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
208 DATACENTER_TOP_ZN_6_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   2.51 2.51 2.51 180.00 90.00 0.91 2.74 0.00 DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
209 DATACENTER_TOP_ZN_6_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   2.51 2.51 2.51 0.00 90.00 0.91 2.74 0.00 DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
210 DATACENTER_TOP_ZN_6_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   36.20 36.20 36.20 0.00 180.00 0.91 39.59 0.00 DATACENTER_TOP_ZN_6_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.00 1.00 0.00 4
211 DATACENTER_TOP_ZN_6_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   36.20 36.20 36.20 180.00 0.00 0.91 39.59 0.00 iz-DATACENTER_TOP_ZN_6_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
212 DATACENTER_BASEMENT_ZN_6_WALL_NORTH Wall   CTF - ConductionTransferFunction DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR 0.354 0.336   39.22 39.22 39.22 0.00 90.00 16.08 2.44 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
213 DATACENTER_BASEMENT_ZN_6_WALL_SOUTH Wall   CTF - ConductionTransferFunction DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR 0.354 0.336   39.22 39.22 39.22 180.00 90.00 16.08 2.44 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
214 DATACENTER_BASEMENT_ZN_6_WALL_WEST Wall   CTF - ConductionTransferFunction DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR 0.354 0.336   118.87 118.87 118.87 270.00 90.00 48.74 2.44 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
215 DATACENTER_BASEMENT_ZN_6_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   118.87 118.87 118.87 90.00 90.00 48.74 2.44 0.00 BASEMENT_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
216 DATACENTER_BASEMENT_ZN_6_FLOOR Floor   CTF - ConductionTransferFunction EXT_SLAB_8IN_WITH_CARPET 3.285 1.827   783.68 783.68 783.68 0.00 180.00 16.08 48.74 0.00 DATACENTER_BASEMENT_ZN_6_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.00 1.00 0.00 4
217 DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   36.20 36.20 36.20 180.00 0.00 0.91 39.59 0.00 DATACENTER_BOT_ZN_6_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
218 DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   419.35 419.35 419.35 180.00 0.00 10.59 39.59 0.00 DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
219 PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   201.98 201.98 201.98 135.00 0.00 6.47 48.74 0.00 PERIMETER_BOT_ZN_4_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
220 DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   63.08 63.08 63.08 180.00 0.00 16.08 6.47 0.00 DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
221 DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   63.07 63.07 63.07 180.00 0.00 11.51 6.47 0.00 DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4


Environment

Environment Name Environment Type Start Date End Date Start DayOfWeek Duration {#days} Source:Start DayOfWeek Use Daylight Saving Use Holidays Apply Weekend Holiday Rule Use Rain Values Use Snow Values Sky Temperature Model
1 RUNPERIOD 1 WeatherFileRunPeriod 01/01/2017 12/31/2017 Sunday 365 Use RunPeriod Specified Day No No No Yes Yes Clark and Allen


Environment:Special Days

Special Day Name Special Day Type Source Start Date Duration {#days}
1 NEW YEARS DAY Holiday InputFile 01/01 1Environment:Special Days


Environment:Daylight Saving

Daylight Saving Indicator Source Start Date End Date
1 Yes InputFile 03/12 11/05


Tabular Report

Style Unit Conversion
1 Commaandhtml commaandhtml


Warmup Convergence Information

Zone Name Environment Type/Name Average Warmup Temperature Difference {deltaC} Std Dev Warmup Temperature Difference {deltaC} Max Temperature Pass/Fail Convergence Min Temperature Pass/Fail Convergence Average Warmup Load Difference {W} Std Dev Warmup Load Difference {W} Heating Load Pass/Fail Convergence Cooling Load Pass/Fail Convergence
1 BASEMENT RunPeriod: RUNPERIOD 1 0.2284434347 0.1918042869 Pass Pass 2.4574607999 13.6409874921 Pass Pass
2 CORE_BOTTOM RunPeriod: RUNPERIOD 1 6.2995037480E-002 0.1451341063 Pass Pass 7.7054723230E-002 0.2666814641 Pass Pass
3 CORE_MID RunPeriod: RUNPERIOD 1 7.1076394341E-002 8.0176874940E-002 Pass Pass 0.2023766563 0.3964366777 Pass Pass
4 CORE_TOP RunPeriod: RUNPERIOD 1 4.1181842403E-002 3.2202471055E-002 Pass Pass 0.4915993766 0.4890627621 Pass Pass
5 PERIMETER_BOT_ZN_3 RunPeriod: RUNPERIOD 1 4.9042079981E-002 8.3355061249E-002 Pass Pass 7.6522343087E-002 0.2644141315 Pass Pass
6 PERIMETER_BOT_ZN_2 RunPeriod: RUNPERIOD 1 0.1191453281 0.2052028386 Pass Pass 7.8914603554E-002 0.2707357433 Pass Pass
7 PERIMETER_BOT_ZN_1 RunPeriod: RUNPERIOD 1 0.1945266806 0.3180208404 Pass Pass 9.0826651571E-002 0.3072594090 Pass Pass
8 PERIMETER_BOT_ZN_4 RunPeriod: RUNPERIOD 1 0.1088552533 0.2193171098 Pass Pass 7.7176768606E-002 0.2622648857 Pass Pass
9 PERIMETER_MID_ZN_3 RunPeriod: RUNPERIOD 1 0.1044272071 0.1636314827 Pass Pass 1.1709977008 5.1802011761 Fail Fail
10 PERIMETER_MID_ZN_2 RunPeriod: RUNPERIOD 1 0.1040141932 0.1367526534 Pass Pass 1.0198368582 4.9093570775 Fail Pass
11 PERIMETER_MID_ZN_1 RunPeriod: RUNPERIOD 1 0.1860254496 0.1822625765 Pass Pass 0.2495549848 0.5142906314 Pass Pass
12 PERIMETER_MID_ZN_4 RunPeriod: RUNPERIOD 1 7.4156215375E-002 7.9686648327E-002 Pass Pass 0.2695080965 0.5282673693 Fail Pass
13 PERIMETER_TOP_ZN_3 RunPeriod: RUNPERIOD 1 0.3707543499 0.3773095304 Pass Pass 7.8195085668 23.5866752734 Pass Pass
14 PERIMETER_TOP_ZN_2 RunPeriod: RUNPERIOD 1 0.2712586018 0.3651792840 Pass Pass 7.1903300608 22.5661590567 Pass Pass
15 PERIMETER_TOP_ZN_1 RunPeriod: RUNPERIOD 1 0.2802829366 0.2769108997 Pass Pass 1.6113199494 10.5500719000 Pass Pass
16 PERIMETER_TOP_ZN_4 RunPeriod: RUNPERIOD 1 0.2386581755 0.2933297070 Pass Pass 6.2745131317 31.7466545000 Pass Pass
17 GROUNDFLOOR_PLENUM RunPeriod: RUNPERIOD 1 1.6360176852E-002 2.5606812247E-002 Pass Pass 0.3459075519 1.5796655809 Pass Pass
18 MIDFLOOR_PLENUM RunPeriod: RUNPERIOD 1 2.4588472892E-002 2.8959098283E-002 Pass Pass 0.2687208395 0.5342077411 Pass Fail
19 TOPFLOOR_PLENUM RunPeriod: RUNPERIOD 1 0.1116309456 8.2310273635E-002 Pass Pass 0.5164437033 0.4906342006 Pass Pass
20 DATACENTER_BOT_ZN_6 RunPeriod: RUNPERIOD 1 4.2670057160E-006 5.3850544407E-006 Pass Pass 5.5371187690E-003 4.9528623021E-003 Pass Pass
21 DATACENTER_MID_ZN_6 RunPeriod: RUNPERIOD 1 2.7678690400E-002 2.0761137552E-002 Pass Pass 5.3309662283E-003 6.2517996652E-003 Pass Pass
22 DATACENTER_TOP_ZN_6 RunPeriod: RUNPERIOD 1 3.2181550134E-002 2.5480305862E-002 Pass Pass 6.1000679408E-003 6.9463610846E-003 Pass Pass
23 DATACENTER_BASEMENT_ZN_6 RunPeriod: RUNPERIOD 1 4.5912772406E-005 3.3245798527E-005 Pass Pass 5.8095351417E-005 1.0513439050E-004 Pass Pass



Table of Contents

Report: Annual Heat Emissions Summary

For: Entire Facility

Timestamp: 2023-10-16 08:43:39

Heat Emission by Components

Envelope Convection Zone Exfiltration Zone Exhaust Air HVAC Relief Air HVAC Reject Heat Total
Heat Emissions [GJ] 6766.42 305.20 0.00 31326.38 10118.18 48516.17



Table of Contents

Report: Climatic Data Summary

For: Entire Facility

Timestamp: 2023-10-16 08:43:39

SizingPeriod:DesignDay

Maximum Dry Bulb [C] Daily Temperature Range [deltaC] Humidity Value Humidity Type Wind Speed [m/s] Wind Direction
GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB -27.60 0.00 -27.60 Wetbulb [C] 2.70 230.00
GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 33.40 16.00 16.30 Wetbulb [C] 4.90 240.00


Monthly Precipitation Summary

Monthly Total Precipitation from .epw [mm] Monthly Total Hours of Rain from .epw Monthly Total Precipitation in Site:Precipitation [mm] Monthly Total Roof Irrigation Depth [mm] Monthly Total Rain Collection Volume [m3]
Jan 0.00 0      
Feb 0.00 0      
Mar 0.00 0      
Apr 11.00 18      
May 24.00 14      
Jun 29.00 21      
Jul 6.00 9      
Aug 0.00 0      
Sep 0.00 0      
Oct 0.00 0      
Nov 0.00 0      
Dec 0.00 0      


Weather Statistics File

Value
None  



Table of Contents

Report: Envelope Summary

For: Entire Facility

Timestamp: 2023-10-16 08:43:39

Opaque Exterior

Construction Reflectance U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Net Area [m2] Azimuth [deg] Tilt [deg] Cardinal Direction
BASEMENT_WALL_EAST BASEMENT_WALL_EAST_CFACTOR 1.00 0.340 0.354 118.87 118.87 90.00 90.00 E
BASEMENT_WALL_SOUTH BASEMENT_WALL_SOUTH_CFACTOR 1.00 0.340 0.354 139.09 139.09 180.00 90.00 S
BASEMENT_WALL_NORTH BASEMENT_WALL_NORTH_CFACTOR 1.00 0.340 0.354 139.09 139.09 0.00 90.00 N
PERIMETER_BOT_ZN_3_WALL_NORTH NONRES_EXT_WALL_GRD 0.30 0.789 0.895 200.61 76.91 0.00 90.00 N
PERIMETER_BOT_ZN_2_WALL_EAST NONRES_EXT_WALL_GRD 0.30 0.789 0.895 133.74 52.57 90.00 90.00 E
PERIMETER_BOT_ZN_1_WALL_SOUTH NONRES_EXT_WALL_GRD 0.30 0.789 0.895 200.61 76.91 180.00 90.00 S
PERIMETER_BOT_ZN_4_WALL_WEST NONRES_EXT_WALL_GRD 0.30 0.789 0.895 133.74 52.57 270.00 90.00 W
PERIMETER_MID_ZN_3_WALL_NORTH NONRES_EXT_WALL_MID 0.30 0.755 0.851 2006.06 847.11 0.00 90.00 N
PERIMETER_MID_ZN_2_WALL_EAST NONRES_EXT_WALL_MID 0.30 0.755 0.851 1337.37 564.74 90.00 90.00 E
PERIMETER_MID_ZN_1_WALL_SOUTH NONRES_EXT_WALL_MID 0.30 0.755 0.851 2006.06 847.11 180.00 90.00 S
PERIMETER_MID_ZN_4_WALL_WEST NONRES_EXT_WALL_MID 0.30 0.755 0.851 1337.37 564.74 270.00 90.00 W
PERIMETER_TOP_ZN_3_WALL_NORTH NONRES_EXT_WALL_TOP 0.30 0.928 1.077 200.61 84.71 0.00 90.00 N
PERIMETER_TOP_ZN_2_WALL_EAST NONRES_EXT_WALL_TOP 0.30 0.928 1.077 133.74 56.47 90.00 90.00 E
PERIMETER_TOP_ZN_1_WALL_SOUTH NONRES_EXT_WALL_TOP 0.30 0.928 1.077 200.61 84.71 180.00 90.00 S
PERIMETER_TOP_ZN_4_WALL_WEST NONRES_EXT_WALL_TOP 0.30 0.928 1.077 133.74 56.47 270.00 90.00 W
GROUNDFLOOR_PLENUM_WALL_NORTH NONRES_EXT_WALL_GRD 0.30 0.789 0.895 89.13 89.13 0.00 90.00 N
GROUNDFLOOR_PLENUM_WEST NONRES_EXT_WALL_GRD 0.30 0.789 0.895 59.42 59.42 270.00 90.00 W
GROUNDFLOOR_PLENUM_WALL_SOUTH NONRES_EXT_WALL_GRD 0.30 0.789 0.895 89.13 89.13 180.00 90.00 S
GROUNDFLOOR_PLENUM_WALL_EAST NONRES_EXT_WALL_GRD 0.30 0.789 0.895 59.42 59.42 90.00 90.00 E
MIDFLOOR_PLENUM_WALL_NORTH NONRES_EXT_WALL_MID 0.30 0.755 0.851 891.32 891.32 0.00 90.00 N
MIDFLOOR_PLENUM_WALL_WEST NONRES_EXT_WALL_MID 0.30 0.755 0.851 594.21 594.21 270.00 90.00 W
MIDFLOOR_PLENUM_WALL_SOUTH NONRES_EXT_WALL_MID 0.30 0.755 0.851 891.32 891.32 180.00 90.00 S
MIDFLOOR_PLENUM_WALL_EAST NONRES_EXT_WALL_MID 0.30 0.755 0.851 594.21 594.21 90.00 90.00 E
TOPFLOOR_PLENUM_WALL_NORTH NONRES_EXT_WALL_TOP 0.30 0.928 1.077 89.13 89.13 180.00 90.00 S
TOPFLOOR_PLENUM_WALL_EAST NONRES_EXT_WALL_TOP 0.30 0.928 1.077 59.42 59.42 90.00 90.00 E
TOPFLOOR_PLENUM_WALL_WEST NONRES_EXT_WALL_TOP 0.30 0.928 1.077 59.42 59.42 270.00 90.00 W
TOPFLOOR_PLENUM_WALL_SOUTH NONRES_EXT_WALL_TOP 0.30 0.928 1.077 89.13 89.13 0.00 90.00 N
BUILDING_ROOF NONRES_ROOF 0.30 0.182 0.186 3563.11 3563.11 180.00 0.00  
DATACENTER_BASEMENT_ZN_6_WALL_NORTH DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR 1.00 0.340 0.354 39.22 39.22 0.00 90.00 N
DATACENTER_BASEMENT_ZN_6_WALL_SOUTH DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR 1.00 0.340 0.354 39.22 39.22 180.00 90.00 S
DATACENTER_BASEMENT_ZN_6_WALL_WEST DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR 1.00 0.340 0.354 118.87 118.87 270.00 90.00 W


Opaque Interior

Construction Reflectance U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Net Area [m2] Azimuth [deg] Tilt [deg] Cardinal Direction
BASEMENT_WALL_WEST INT_WALL 0.30 2.511 6.299 118.87 118.87 270.00 90.00 W
BASEMENT_FLOOR EXT_SLAB_8IN_WITH_CARPET 0.30 1.591 3.285 2779.43 2779.43 0.00 180.00  
PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER INT_SLAB_CEILING 0.30 1.887 3.839 201.98 201.98 225.00 0.00  
PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER INT_SLAB_CEILING 0.30 1.887 3.839 250.34 250.34 180.00 0.00  
CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER INT_SLAB_CEILING 0.30 1.887 3.839 2076.77 2076.77 180.00 0.00  
PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER INT_SLAB_CEILING 0.30 1.887 3.839 250.34 250.34 180.00 0.00  
CORE_BOT_ZN_5_WALL_SOUTH INT_WALL 0.30 2.511 6.299 173.00 173.00 180.00 90.00 S
CORE_BOT_ZN_5_WALL_WEST INT_WALL 0.30 2.511 6.299 108.64 108.64 270.00 90.00 W
CORE_BOT_ZN_5_WALL_NORTH INT_WALL 0.30 2.511 6.299 173.00 173.00 0.00 90.00 N
CORE_BOT_ZN_5_WALL_EAST INT_WALL 0.30 2.511 6.299 108.64 108.64 90.00 90.00 E
DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER INT_SLAB_FLOOR 0.30 1.887 3.839 419.30 419.30 0.00 180.00  
CORE_BOT_ZN_5_FLOOR INT_SLAB_FLOOR 0.30 1.887 3.839 2076.82 2076.82 0.00 180.00  
CORE_BOT_ZN_5_CEILING DROPCEILING 0.30 2.031 4.488 2496.12 2496.12 180.00 0.00  
CORE_MID_ZN_5_WALL_SOUTH INT_WALL 0.30 2.511 6.299 1729.99 1729.99 180.00 90.00 S
CORE_MID_ZN_5_WALL_WEST INT_WALL 0.30 2.511 6.299 1086.40 1086.40 270.00 90.00 W
CORE_MID_ZN_5_WALL_NORTH INT_WALL 0.30 2.511 6.299 1729.99 1729.99 0.00 90.00 N
CORE_MID_ZN_5_WALL_EAST INT_WALL 0.30 2.511 6.299 1086.40 1086.40 90.00 90.00 E
CORE_MID_ZN_5_FLOOR INT_SLAB_FLOOR 0.30 1.711 3.839 24961.20 24961.20 0.00 180.00  
CORE_MID_ZN_5_CEILING DROPCEILING 0.30 2.031 4.488 24961.20 24961.20 180.00 0.00  
CORE_TOP_ZN_5_WALL_SOUTH INT_WALL 0.30 2.511 6.299 173.00 173.00 180.00 90.00 S
CORE_TOP_ZN_5_WALL_WEST INT_WALL 0.30 2.511 6.299 108.64 108.64 270.00 90.00 W
CORE_TOP_ZN_5_WALL_NORTH INT_WALL 0.30 2.511 6.299 173.00 173.00 0.00 90.00 N
CORE_TOP_ZN_5_WALL_EAST INT_WALL 0.30 2.511 6.299 108.64 108.64 90.00 90.00 E
CORE_TOP_ZN_5_FLOOR INT_SLAB_FLOOR 0.30 1.711 3.839 2496.12 2496.12 0.00 180.00  
CORE_TOP_ZN_5_CEILING DROPCEILING 0.30 2.031 4.488 2496.12 2496.12 180.00 0.00  
PERIMETER_BOT_ZN_3_WALL_WEST INT_WALL 0.30 2.511 6.299 17.75 17.75 225.00 90.00 W
CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 173.00 173.00 180.00 90.00 S
PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 17.75 17.75 135.00 90.00 S
DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 2.51 2.51 180.00 90.00 S
PERIMETER_BOT_ZN_3_FLOOR INT_SLAB_FLOOR 0.30 1.887 3.839 250.34 250.34 0.00 180.00  
DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER INT_SLAB_FLOOR 0.30 1.887 3.839 63.07 63.07 0.00 180.00  
PERIMETER_BOT_ZN_3_CEILING DROPCEILING 0.30 2.031 4.488 313.41 313.41 180.00 0.00  
PERIMETER_BOT_ZN_2_WALL_NORTH INT_WALL 0.30 2.511 6.299 17.75 17.75 315.00 90.00 N
CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 108.64 108.64 270.00 90.00 W
PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 17.75 17.75 225.00 90.00 W
PERIMETER_BOT_ZN_2_FLOOR INT_SLAB_FLOOR 0.30 1.887 3.839 201.98 201.98 45.00 180.00  
PERIMETER_BOT_ZN_2_CEILING DROPCEILING 0.30 2.031 4.488 201.98 201.98 225.00 0.00  
PERIMETER_BOT_ZN_1_WALL_EAST INT_WALL 0.30 2.511 6.299 17.75 17.75 45.00 90.00 E
DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 2.51 2.51 0.00 90.00 N
PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 17.75 17.75 315.00 90.00 N
CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 173.00 173.00 0.00 90.00 N
DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER INT_SLAB_FLOOR 0.30 1.887 3.839 63.07 63.07 0.00 180.00  
PERIMETER_BOT_ZN_1_FLOOR INT_SLAB_FLOOR 0.30 1.887 3.839 250.35 250.35 0.00 180.00  
PERIMETER_BOT_ZN_1_CEILING DROPCEILING 0.30 2.031 4.488 313.42 313.42 180.00 0.00  
PERIMETER_BOT_ZN_4_WALL_SOUTH INT_WALL 0.30 2.511 6.299 17.75 17.75 135.00 90.00 S
DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 108.64 108.64 90.00 90.00 E
PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 17.75 17.75 45.00 90.00 E
PERIMETER_BOT_ZN_4_FLOOR INT_SLAB_FLOOR 0.30 1.887 3.839 201.98 201.98 315.00 180.00  
PERIMETER_BOT_ZN_4_CEILING DROPCEILING 0.30 2.031 4.488 201.98 201.98 135.00 0.00  
PERIMETER_MID_ZN_3_WALL_WEST INT_WALL 0.30 2.511 6.299 177.47 177.47 225.00 90.00 W
CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 1729.99 1729.99 180.00 90.00 S
PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 177.47 177.47 135.00 90.00 S
DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 25.09 25.09 180.00 90.00 S
PERIMETER_MID_ZN_3_FLOOR INT_SLAB_FLOOR 0.30 1.711 3.839 3134.13 3134.13 0.00 180.00  
PERIMETER_MID_ZN_3_CEILING DROPCEILING 0.30 2.031 4.488 3134.13 3134.13 180.00 0.00  
PERIMETER_MID_ZN_2_WALL_NORTH INT_WALL 0.30 2.511 6.299 177.47 177.47 315.00 90.00 N
CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 1086.40 1086.40 270.00 90.00 W
PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 177.47 177.47 225.00 90.00 W
PERIMETER_MID_ZN_2_FLOOR INT_SLAB_FLOOR 0.30 1.711 3.839 2019.75 2019.75 45.00 180.00  
PERIMETER_MID_ZN_2_CEILING DROPCEILING 0.30 2.031 4.488 2019.75 2019.75 225.00 0.00  
PERIMETER_MID_ZN_1_WALL_EAST INT_WALL 0.30 2.511 6.299 177.47 177.47 45.00 90.00 E
DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 25.09 25.09 0.00 90.00 N
PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 177.47 177.47 315.00 90.00 N
CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 1729.99 1729.99 0.00 90.00 N
PERIMETER_MID_ZN_1_FLOOR INT_SLAB_FLOOR 0.30 1.711 3.839 3134.20 3134.20 0.00 180.00  
PERIMETER_MID_ZN_1_CEILING DROPCEILING 0.30 2.031 4.488 3134.20 3134.20 180.00 0.00  
PERIMETER_MID_ZN_4_WALL_SOUTH INT_WALL 0.30 2.511 6.299 177.47 177.47 135.00 90.00 S
DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 1086.40 1086.40 90.00 90.00 E
PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 177.47 177.47 45.00 90.00 E
PERIMETER_MID_ZN_4_FLOOR INT_SLAB_FLOOR 0.30 1.711 3.839 2019.75 2019.75 315.00 180.00  
PERIMETER_MID_ZN_4_CEILING DROPCEILING 0.30 2.031 4.488 2019.75 2019.75 135.00 0.00  
PERIMETER_TOP_ZN_3_WALL_WEST INT_WALL 0.30 2.511 6.299 17.75 17.75 225.00 90.00 W
CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 173.00 173.00 180.00 90.00 S
PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 17.75 17.75 135.00 90.00 S
DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 2.51 2.51 180.00 90.00 S
PERIMETER_TOP_ZN_3_FLOOR INT_SLAB_FLOOR 0.30 1.711 3.839 313.41 313.41 0.00 180.00  
PERIMETER_TOP_ZN_3_CEILING DROPCEILING 0.30 2.031 4.488 313.41 313.41 180.00 0.00  
PERIMETER_TOP_ZN_2_WALL_NORTH INT_WALL 0.30 2.511 6.299 17.75 17.75 315.00 90.00 N
CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 108.64 108.64 270.00 90.00 W
INT-PER3S-NE-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 17.75 17.75 225.00 90.00 W
PERIMETER_TOP_ZN_2_FLOOR INT_SLAB_FLOOR 0.30 1.711 3.839 201.98 201.98 45.00 180.00  
PERIMETER_TOP_ZN_2_CEILING DROPCEILING 0.30 2.031 4.488 201.98 201.98 225.00 0.00  
INT-PER3S-NE INT_WALL 0.30 2.511 6.299 17.75 17.75 45.00 90.00 E
DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 2.51 2.51 0.00 90.00 N
PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 17.75 17.75 315.00 90.00 N
CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 173.00 173.00 0.00 90.00 N
PERIMETER_TOP_ZN_1_FLOOR INT_SLAB_FLOOR 0.30 1.711 3.839 313.42 313.42 0.00 180.00  
PERIMETER_TOP_ZN_1_CEILING DROPCEILING 0.30 2.031 4.488 313.42 313.42 180.00 0.00  
PERIMETER_TOP_ZN_4_WALL_SOUTH INT_WALL 0.30 2.511 6.299 17.75 17.75 135.00 90.00 S
DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 108.64 108.64 90.00 90.00 E
PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 17.75 17.75 45.00 90.00 E
PERIMETER_TOP_ZN_4_FLOOR INT_SLAB_FLOOR 0.30 1.711 3.839 201.98 201.98 315.00 180.00  
PERIMETER_TOP_ZN_4_CEILING DROPCEILING 0.30 2.031 4.488 201.98 201.98 135.00 0.00  
iz-CORE_BOT_ZN_5_CEILING DROPCEILING 0.30 2.031 4.488 2496.12 2496.12 0.00 180.00  
iz-PERIMETER_BOT_ZN_3_CEILING DROPCEILING 0.30 2.031 4.488 313.41 313.41 0.00 180.00  
iz-PERIMETER_BOT_ZN_2_CEILING DROPCEILING 0.30 2.031 4.488 201.98 201.98 45.00 180.00  
iz-PERIMETER_BOT_ZN_1_CEILING DROPCEILING 0.30 2.031 4.488 313.42 313.42 0.00 180.00  
iz-PERIMETER_BOT_ZN_4_CEILING DROPCEILING 0.30 2.031 4.488 201.98 201.98 315.00 180.00  
iz-DATACENTER_BOT_ZN_6_CEILING DROPCEILING 0.30 2.031 4.488 36.20 36.20 0.00 180.00  
GROUNDFLOOR_PLENUM_CEILING INT_SLAB_CEILING 0.30 2.104 3.839 3563.11 3563.11 180.00 0.00  
iz-CORE_MID_ZN_5_CEILING DROPCEILING 0.30 2.031 4.488 24961.20 24961.20 0.00 180.00  
iz-PERIMETER_MID_ZN_3_CEILING DROPCEILING 0.30 2.031 4.488 3134.13 3134.13 0.00 180.00  
iz-PERIMETER_MID_ZN_2_CEILING DROPCEILING 0.30 2.031 4.488 2019.75 2019.75 45.00 180.00  
iz-PERIMETER_MID_ZN_1_CEILING DROPCEILING 0.30 2.031 4.488 3134.20 3134.20 0.00 180.00  
iz-PERIMETER_MID_ZN_4_CEILING DROPCEILING 0.30 2.031 4.488 2019.75 2019.75 315.00 180.00  
iz-DATACENTER_MID_ZN_6_CEILING DROPCEILING 0.30 2.031 4.488 362.03 362.03 0.00 180.00  
MIDFLOOR_PLENUM_CEILING INT_SLAB_CEILING 0.30 2.104 3.839 35631.06 35631.06 180.00 0.00  
iz-CORE_TOP_ZN_5_CEILING DROPCEILING 0.30 2.031 4.488 2496.12 2496.12 0.00 180.00  
iz-PERIMETER_TOP_ZN_3_CEILING DROPCEILING 0.30 2.031 4.488 313.41 313.41 0.00 180.00  
iz-PERIMETER_TOP_ZN_2_CEILING DROPCEILING 0.30 2.031 4.488 201.98 201.98 45.00 180.00  
iz-PERIMETER_TOP_ZN_1_CEILING DROPCEILING 0.30 2.031 4.488 313.42 313.42 0.00 180.00  
iz-PERIMETER_TOP_ZN_4_CEILING DROPCEILING 0.30 2.031 4.488 201.98 201.98 315.00 180.00  
iz-DATACENTER_TOP_ZN_6_CEILING DROPCEILING 0.30 2.031 4.488 36.20 36.20 0.00 180.00  
DATACENTER_BOT_ZN_6_WALL_NORTH INT_WALL 0.30 2.511 6.299 2.51 2.51 0.00 90.00 N
DATACENTER_BOT_ZN_6_WALL_SOUTH INT_WALL 0.30 2.511 6.299 2.51 2.51 180.00 90.00 S
DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 108.64 108.64 90.00 90.00 E
DATACENTER_BOT_ZN_6_WALL_WEST INT_WALL 0.30 2.511 6.299 108.64 108.64 270.00 90.00 W
DATACENTER_BOT_ZN_6_FLOOR INT_SLAB_FLOOR 0.30 1.887 3.839 36.20 36.20 0.00 180.00  
DATACENTER_BOT_ZN_6_CEILING DROPCEILING 0.30 2.031 4.488 36.20 36.20 180.00 0.00  
DATACENTER_MID_ZN_6_WALL_WEST INT_WALL 0.30 2.511 6.299 1086.40 1086.40 270.00 90.00 W
DATACENTER_MID_ZN_6_WALL_SOUTH INT_WALL 0.30 2.511 6.299 25.09 25.09 180.00 90.00 S
DATACENTER_MID_ZN_6_WALL_EAST INT_WALL 0.30 2.511 6.299 1086.40 1086.40 90.00 90.00 E
DATACENTER_MID_ZN_6_WALL_NORTH INT_WALL 0.30 2.511 6.299 25.09 25.09 0.00 90.00 N
DATACENTER_MID_ZN_6_FLOOR INT_SLAB_FLOOR 0.30 1.711 3.839 362.03 362.03 0.00 180.00  
DATACENTER_MID_ZN_6_CEILING DROPCEILING 0.30 2.031 4.488 362.03 362.03 180.00 0.00  
DATACENTER_TOP_ZN_6_WALL_EAST INT_WALL 0.30 2.511 6.299 108.64 108.64 90.00 90.00 E
DATACENTER_TOP_ZN_6_WALL_WEST INT_WALL 0.30 2.511 6.299 108.64 108.64 270.00 90.00 W
DATACENTER_TOP_ZN_6_WALL_SOUTH INT_WALL 0.30 2.511 6.299 2.51 2.51 180.00 90.00 S
DATACENTER_TOP_ZN_6_WALL_NORTH INT_WALL 0.30 2.511 6.299 2.51 2.51 0.00 90.00 N
DATACENTER_TOP_ZN_6_FLOOR INT_SLAB_FLOOR 0.30 1.711 3.839 36.20 36.20 0.00 180.00  
DATACENTER_TOP_ZN_6_CEILING DROPCEILING 0.30 2.031 4.488 36.20 36.20 180.00 0.00  
DATACENTER_BASEMENT_ZN_6_WALL_EAST INT_WALL 0.30 2.511 6.299 118.87 118.87 90.00 90.00 E
DATACENTER_BASEMENT_ZN_6_FLOOR EXT_SLAB_8IN_WITH_CARPET 0.30 1.591 3.285 783.68 783.68 0.00 180.00  
DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER INT_SLAB_CEILING 0.30 1.887 3.839 36.20 36.20 180.00 0.00  
DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 INT_SLAB_CEILING 0.30 1.887 3.839 419.35 419.35 180.00 0.00  
PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER INT_SLAB_CEILING 0.30 1.887 3.839 201.98 201.98 135.00 0.00  
DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 INT_SLAB_CEILING 0.30 1.887 3.839 63.08 63.08 180.00 0.00  
DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 INT_SLAB_CEILING 0.30 1.887 3.839 63.07 63.07 180.00 0.00  
BASEMENT_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 7126.21   0.00 90.00 N
CORE_BOTTOM_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 5064.65   0.00 90.00 N
CORE_MID_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 50646.53   0.00 90.00 N
CORE_TOP_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 5064.65   0.00 90.00 N
PERIMETER_BOT_ZN_3_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 626.83   0.00 90.00 N
PERIMETER_BOT_ZN_2_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 403.95   0.00 90.00 N
PERIMETER_BOT_ZN_1_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 626.84   0.00 90.00 N
PERIMETER_BOT_ZN_4_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 403.95   0.00 90.00 N
PERIMETER_MID_ZN_3_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 6268.26   0.00 90.00 N
PERIMETER_MID_ZN_2_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 4039.50   0.00 90.00 N
PERIMETER_MID_ZN_1_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 6268.35   0.00 90.00 N
PERIMETER_MID_ZN_4_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 4039.48   0.00 90.00 N
PERIMETER_TOP_ZN_3_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 626.83   0.00 90.00 N
PERIMETER_TOP_ZN_2_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 403.95   0.00 90.00 N
PERIMETER_TOP_ZN_1_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 626.84   0.00 90.00 N
PERIMETER_TOP_ZN_4_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 403.95   0.00 90.00 N


Exterior Fenestration

Construction Frame and Divider Glass Area [m2] Frame Area [m2] Divider Area [m2] Area of One Opening [m2] Area of Multiplied Openings [m2] Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance Frame Conductance [W/m2-K] Divider Conductance [W/m2-K] NFRC Product Type Assembly U-Factor [W/m2-K] Assembly SHGC Assembly Visible Transmittance Shade Control Parent Surface Azimuth [deg] Tilt [deg] Cardinal Direction
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 WINDOW_U_0.419_SHGC_NORTH_0.4   23.18 0.00 0.00 23.18 23.18 2.381 0.401 0.442             No PERIMETER_BOT_ZN_3_WALL_NORTH 0.00 90.00 N
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 WINDOW_U_0.419_SHGC_NORTH_0.4   23.18 0.00 0.00 23.18 23.18 2.381 0.401 0.442             No PERIMETER_BOT_ZN_3_WALL_NORTH 0.00 90.00 N
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 WINDOW_U_0.419_SHGC_NORTH_0.4   23.18 0.00 0.00 23.18 23.18 2.381 0.401 0.442             No PERIMETER_BOT_ZN_3_WALL_NORTH 0.00 90.00 N
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 WINDOW_U_0.419_SHGC_NORTH_0.4   23.18 0.00 0.00 23.18 23.18 2.381 0.401 0.442             No PERIMETER_BOT_ZN_3_WALL_NORTH 0.00 90.00 N
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 WINDOW_U_0.419_SHGC_NORTH_0.4   23.18 0.00 0.00 23.18 23.18 2.381 0.401 0.442             No PERIMETER_BOT_ZN_3_WALL_NORTH 0.00 90.00 N
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 WINDOW_U_0.419_SHGC_EAST_0.4   25.75 0.00 0.00 25.75 25.75 2.381 0.401 0.442             No PERIMETER_BOT_ZN_2_WALL_EAST 90.00 90.00 E
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 WINDOW_U_0.419_SHGC_EAST_0.4   25.75 0.00 0.00 25.75 25.75 2.381 0.401 0.442             No PERIMETER_BOT_ZN_2_WALL_EAST 90.00 90.00 E
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 WINDOW_U_0.419_SHGC_EAST_0.4   25.75 0.00 0.00 25.75 25.75 2.381 0.401 0.442             No PERIMETER_BOT_ZN_2_WALL_EAST 90.00 90.00 E
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 WINDOW_U_0.419_SHGC_SOUTH_0.4   23.18 0.00 0.00 23.18 23.18 2.381 0.401 0.442             No PERIMETER_BOT_ZN_1_WALL_SOUTH 180.00 90.00 S
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 WINDOW_U_0.419_SHGC_SOUTH_0.4   23.18 0.00 0.00 23.18 23.18 2.381 0.401 0.442             No PERIMETER_BOT_ZN_1_WALL_SOUTH 180.00 90.00 S
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 WINDOW_U_0.419_SHGC_SOUTH_0.4   23.18 0.00 0.00 23.18 23.18 2.381 0.401 0.442             No PERIMETER_BOT_ZN_1_WALL_SOUTH 180.00 90.00 S
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 WINDOW_U_0.419_SHGC_SOUTH_0.4   23.18 0.00 0.00 23.18 23.18 2.381 0.401 0.442             No PERIMETER_BOT_ZN_1_WALL_SOUTH 180.00 90.00 S
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 WINDOW_U_0.419_SHGC_SOUTH_0.4   23.18 0.00 0.00 23.18 23.18 2.381 0.401 0.442             No PERIMETER_BOT_ZN_1_WALL_SOUTH 180.00 90.00 S
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 WINDOW_U_0.419_SHGC_WEST_0.4   25.75 0.00 0.00 25.75 25.75 2.381 0.401 0.442             No PERIMETER_BOT_ZN_4_WALL_WEST 270.00 90.00 W
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 WINDOW_U_0.419_SHGC_WEST_0.4   25.75 0.00 0.00 25.75 25.75 2.381 0.401 0.442             No PERIMETER_BOT_ZN_4_WALL_WEST 270.00 90.00 W
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 WINDOW_U_0.419_SHGC_WEST_0.4   25.75 0.00 0.00 25.75 25.75 2.381 0.401 0.442             No PERIMETER_BOT_ZN_4_WALL_WEST 270.00 90.00 W
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW WINDOW_U_0.419_SHGC_NORTH_0.4   115.90 0.00 0.00 115.90 1158.95 2.381 0.401 0.442             No PERIMETER_MID_ZN_3_WALL_NORTH 0.00 90.00 N
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW WINDOW_U_0.419_SHGC_EAST_0.4   77.26 0.00 0.00 77.26 772.63 2.381 0.401 0.442             No PERIMETER_MID_ZN_2_WALL_EAST 90.00 90.00 E
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW WINDOW_U_0.419_SHGC_SOUTH_0.4   115.90 0.00 0.00 115.90 1158.95 2.381 0.401 0.442             No PERIMETER_MID_ZN_1_WALL_SOUTH 180.00 90.00 S
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW WINDOW_U_0.419_SHGC_WEST_0.4   77.26 0.00 0.00 77.26 772.63 2.381 0.401 0.442             No PERIMETER_MID_ZN_4_WALL_WEST 270.00 90.00 W
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW WINDOW_U_0.419_SHGC_NORTH_0.4   115.90 0.00 0.00 115.90 115.90 2.381 0.401 0.442             No PERIMETER_TOP_ZN_3_WALL_NORTH 0.00 90.00 N
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW WINDOW_U_0.419_SHGC_EAST_0.4   77.26 0.00 0.00 77.26 77.26 2.381 0.401 0.442             No PERIMETER_TOP_ZN_2_WALL_EAST 90.00 90.00 E
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW WINDOW_U_0.419_SHGC_SOUTH_0.4   115.90 0.00 0.00 115.90 115.90 2.381 0.401 0.442             No PERIMETER_TOP_ZN_1_WALL_SOUTH 180.00 90.00 S
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW WINDOW_U_0.419_SHGC_WEST_0.4   77.26 0.00 0.00 77.26 77.26 2.381 0.401 0.442             No PERIMETER_TOP_ZN_4_WALL_WEST 270.00 90.00 W
Total or Average             4635.80 2.381 0.401 0.442                      
North Total or Average             1390.74 2.381 0.401 0.442                      
Non-North Total or Average             3245.06 2.381 0.401 0.442                      


Exterior Fenestration Shaded State

Frame and Divider Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance NFRC Product Type Assembly U-Factor [W/m2-K] Assembly SHGC Assembly Visible Transmittance
None                


Interior Fenestration

Construction Area of One Opening [m2] Area of Openings [m2] Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance
Total or Average     0.00 - - -


Exterior Door

Construction U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Parent Surface
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 SWINGING DOOR_CON 1.992 2.839 1.95 PERIMETER_BOT_ZN_3_WALL_NORTH
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 SWINGING DOOR_CON 1.992 2.839 1.95 PERIMETER_BOT_ZN_3_WALL_NORTH
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 SWINGING DOOR_CON 1.992 2.839 1.95 PERIMETER_BOT_ZN_3_WALL_NORTH
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 SWINGING DOOR_CON 1.992 2.839 1.95 PERIMETER_BOT_ZN_3_WALL_NORTH
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 SWINGING DOOR_CON 1.992 2.839 1.95 PERIMETER_BOT_ZN_2_WALL_EAST
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 SWINGING DOOR_CON 1.992 2.839 1.95 PERIMETER_BOT_ZN_2_WALL_EAST
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 SWINGING DOOR_CON 1.992 2.839 1.95 PERIMETER_BOT_ZN_1_WALL_SOUTH
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 SWINGING DOOR_CON 1.992 2.839 1.95 PERIMETER_BOT_ZN_1_WALL_SOUTH
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 SWINGING DOOR_CON 1.992 2.839 1.95 PERIMETER_BOT_ZN_1_WALL_SOUTH
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 SWINGING DOOR_CON 1.992 2.839 1.95 PERIMETER_BOT_ZN_1_WALL_SOUTH
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 SWINGING DOOR_CON 1.992 2.839 1.95 PERIMETER_BOT_ZN_4_WALL_WEST
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 SWINGING DOOR_CON 1.992 2.839 1.95 PERIMETER_BOT_ZN_4_WALL_WEST


Interior Door

Construction U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Parent Surface
None          



Table of Contents

Report: Shading Summary

For: Entire Facility

Timestamp: 2023-10-16 08:43:39

Sunlit Fraction

March 21 9am March 21 noon March 21 3pm June 21 9am June 21 noon June 21 3pm December 21 9am December 21 noon December 21 3pm
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00


Window Control

Name Type Shaded Construction Control Glare Control
None          



Table of Contents

Report: Lighting Summary

For: Entire Facility

Timestamp: 2023-10-16 08:43:39

Interior Lighting

Zone Name Space Name Space Type Lighting Power Density [W/m2] Space Area [m2] Total Power [W] End Use Subcategory Schedule Name Scheduled Hours/Week [hr] Hours/Week > 1% [hr] Full Load Hours/Week [hr] Return Air Fraction Conditioned (Y/N) Consumption [GJ]
BASEMENT_LIGHTS BASEMENT BASEMENT GENERAL 10.2732 2779.43 28553.72 LightsWired LTG_SCH_OFFICE 50.34 168.00 49.04 0.0000 Y 262.84
CORE_BOTTOM_LIGHTS CORE_BOTTOM CORE_BOTTOM GENERAL 10.2732 2496.12 25643.24 LightsWired LTG_SCH_OFFICE 50.34 168.00 49.04 0.0000 Y 236.05
CORE_MID_LIGHTS CORE_MID CORE_MID GENERAL 10.2732 24961.20 256432.45 LightsWired LTG_SCH_OFFICE 50.34 168.00 49.04 0.0000 Y 2360.52
CORE_TOP_LIGHTS CORE_TOP CORE_TOP GENERAL 10.2732 2496.12 25643.24 LightsWired LTG_SCH_OFFICE 50.34 168.00 49.04 0.0000 Y 236.05
PERIMETER_BOT_ZN_3_LIGHTS PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3 GENERAL 10.2732 313.41 3219.77 LightsWired LTG_SCH_OFFICE 50.34 168.00 29.08 0.0000 Y 17.57
PERIMETER_BOT_ZN_2_LIGHTS PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2 GENERAL 10.2732 201.98 2074.94 LightsWired LTG_SCH_OFFICE 50.34 168.00 28.66 0.0000 Y 11.16
PERIMETER_BOT_ZN_1_LIGHTS PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1 GENERAL 10.2732 313.42 3219.84 LightsWired LTG_SCH_OFFICE 50.34 168.00 28.41 0.0000 Y 17.17
PERIMETER_BOT_ZN_4_LIGHTS PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4 GENERAL 10.2732 201.98 2074.94 LightsWired LTG_SCH_OFFICE 50.34 168.00 28.75 0.0000 Y 11.20
PERIMETER_MID_ZN_3_LIGHTS PERIMETER_MID_ZN_3 PERIMETER_MID_ZN_3 GENERAL 10.2732 3134.13 32197.65 LightsWired LTG_SCH_OFFICE 50.34 168.00 29.01 0.0000 Y 175.35
PERIMETER_MID_ZN_2_LIGHTS PERIMETER_MID_ZN_2 PERIMETER_MID_ZN_2 GENERAL 10.2732 2019.75 20749.39 LightsWired LTG_SCH_OFFICE 50.34 168.00 28.62 0.0000 Y 111.48
PERIMETER_MID_ZN_1_LIGHTS PERIMETER_MID_ZN_1 PERIMETER_MID_ZN_1 GENERAL 10.2732 3134.20 32198.36 LightsWired LTG_SCH_OFFICE 50.34 168.00 28.38 0.0000 Y 171.54
PERIMETER_MID_ZN_4_LIGHTS PERIMETER_MID_ZN_4 PERIMETER_MID_ZN_4 GENERAL 10.2732 2019.75 20749.39 LightsWired LTG_SCH_OFFICE 50.34 168.00 28.70 0.0000 Y 111.80
PERIMETER_TOP_ZN_3_LIGHTS PERIMETER_TOP_ZN_3 PERIMETER_TOP_ZN_3 GENERAL 10.2732 313.41 3219.77 LightsWired LTG_SCH_OFFICE 50.34 168.00 29.01 0.0000 Y 17.53
PERIMETER_TOP_ZN_2_LIGHTS PERIMETER_TOP_ZN_2 PERIMETER_TOP_ZN_2 GENERAL 10.2732 201.98 2074.94 LightsWired LTG_SCH_OFFICE 50.34 168.00 28.62 0.0000 Y 11.15
PERIMETER_TOP_ZN_1_LIGHTS PERIMETER_TOP_ZN_1 PERIMETER_TOP_ZN_1 GENERAL 10.2732 313.42 3219.84 LightsWired LTG_SCH_OFFICE 50.34 168.00 28.38 0.0000 Y 17.15
PERIMETER_TOP_ZN_4_LIGHTS PERIMETER_TOP_ZN_4 PERIMETER_TOP_ZN_4 GENERAL 10.2732 201.98 2074.94 LightsWired LTG_SCH_OFFICE 50.34 168.00 28.70 0.0000 Y 11.18
DATACENTER_BASEMENT_LIGHTS DATACENTER_BASEMENT_ZN_6 DATACENTER_BASEMENT_ZN_6 GENERAL 10.2732 783.68 8050.93 LightsWired LTG_SCH_OFFICE 50.34 168.00 49.04 0.0000 Y 74.11
DATACENTER_BOT_LIGHTS DATACENTER_BOT_ZN_6 DATACENTER_BOT_ZN_6 GENERAL 17.8735 36.20 647.07 LightsWired LTG_SCH_DATACENTER 56.02 168.00 54.57 0.0000 Y 6.63
DATACENTER_MID_LIGHTS DATACENTER_MID_ZN_6 DATACENTER_MID_ZN_6 GENERAL 17.8735 362.03 6470.68 LightsWired LTG_SCH_DATACENTER 56.02 168.00 54.57 0.0000 Y 66.28
DATACENTER_TOP_LIGHTS DATACENTER_TOP_ZN_6 DATACENTER_TOP_ZN_6 GENERAL 17.8735 36.20 647.07 LightsWired LTG_SCH_DATACENTER 56.02 168.00 54.57 0.0000 Y 6.63
Interior Lighting Total       10.3445 46320.38 479162.15               1236.13


Daylighting

Zone Control Name Daylighting Method Control Type Fraction Controlled Lighting Installed in Zone [W] Lighting Controlled [W]
PERIMETER_BOT_ZN_1_DAYLREFPT1 PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_DAYLCTRL SplitFlux Stepped 0.39 3219.84 1241.89
PERIMETER_BOT_ZN_1_DAYLREFPT2 PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_DAYLCTRL SplitFlux Stepped 0.14 3219.84 445.95
PERIMETER_BOT_ZN_2_DAYLREFPT1 PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_DAYLCTRL SplitFlux Stepped 0.39 2074.94 800.30
PERIMETER_BOT_ZN_2_DAYLREFPT2 PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_DAYLCTRL SplitFlux Stepped 0.14 2074.94 287.38
PERIMETER_BOT_ZN_3_DAYLREFPT1 PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_DAYLCTRL SplitFlux Stepped 0.39 3219.77 1241.86
PERIMETER_BOT_ZN_3_DAYLREFPT2 PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_DAYLCTRL SplitFlux Stepped 0.14 3219.77 445.94
PERIMETER_BOT_ZN_4_DAYLREFPT1 PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_DAYLCTRL SplitFlux Stepped 0.39 2074.94 800.30
PERIMETER_BOT_ZN_4_DAYLREFPT2 PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_DAYLCTRL SplitFlux Stepped 0.14 2074.94 287.38
PERIMETER_MID_ZN_1_DAYLREFPT1 PERIMETER_MID_ZN_1 PERIMETER_MID_ZN_1_DAYLCTRL SplitFlux Stepped 0.39 3219.84 1241.89
PERIMETER_MID_ZN_1_DAYLREFPT2 PERIMETER_MID_ZN_1 PERIMETER_MID_ZN_1_DAYLCTRL SplitFlux Stepped 0.14 3219.84 445.95
PERIMETER_MID_ZN_2_DAYLREFPT1 PERIMETER_MID_ZN_2 PERIMETER_MID_ZN_2_DAYLCTRL SplitFlux Stepped 0.39 2074.94 800.30
PERIMETER_MID_ZN_2_DAYLREFPT2 PERIMETER_MID_ZN_2 PERIMETER_MID_ZN_2_DAYLCTRL SplitFlux Stepped 0.14 2074.94 287.38
PERIMETER_MID_ZN_3_DAYLREFPT1 PERIMETER_MID_ZN_3 PERIMETER_MID_ZN_3_DAYLCTRL SplitFlux Stepped 0.39 3219.77 1241.86
PERIMETER_MID_ZN_3_DAYLREFPT2 PERIMETER_MID_ZN_3 PERIMETER_MID_ZN_3_DAYLCTRL SplitFlux Stepped 0.14 3219.77 445.94
PERIMETER_MID_ZN_4_DAYLREFPT1 PERIMETER_MID_ZN_4 PERIMETER_MID_ZN_4_DAYLCTRL SplitFlux Stepped 0.39 2074.94 800.30
PERIMETER_MID_ZN_4_DAYLREFPT2 PERIMETER_MID_ZN_4 PERIMETER_MID_ZN_4_DAYLCTRL SplitFlux Stepped 0.14 2074.94 287.38
PERIMETER_TOP_ZN_1_DAYLREFPT1 PERIMETER_TOP_ZN_1 PERIMETER_TOP_ZN_1_DAYLCTRL SplitFlux Stepped 0.39 3219.84 1241.89
PERIMETER_TOP_ZN_1_DAYLREFPT2 PERIMETER_TOP_ZN_1 PERIMETER_TOP_ZN_1_DAYLCTRL SplitFlux Stepped 0.14 3219.84 445.95
PERIMETER_TOP_ZN_2_DAYLREFPT1 PERIMETER_TOP_ZN_2 PERIMETER_TOP_ZN_2_DAYLCTRL SplitFlux Stepped 0.39 2074.94 800.30
PERIMETER_TOP_ZN_2_DAYLREFPT2 PERIMETER_TOP_ZN_2 PERIMETER_TOP_ZN_2_DAYLCTRL SplitFlux Stepped 0.14 2074.94 287.38
PERIMETER_TOP_ZN_3_DAYLREFPT1 PERIMETER_TOP_ZN_3 PERIMETER_TOP_ZN_3_DAYLCTRL SplitFlux Stepped 0.39 3219.77 1241.86
PERIMETER_TOP_ZN_3_DAYLREFPT2 PERIMETER_TOP_ZN_3 PERIMETER_TOP_ZN_3_DAYLCTRL SplitFlux Stepped 0.14 3219.77 445.94
PERIMETER_TOP_ZN_4_DAYLREFPT1 PERIMETER_TOP_ZN_4 PERIMETER_TOP_ZN_4_DAYLCTRL SplitFlux Stepped 0.39 2074.94 800.30
PERIMETER_TOP_ZN_4_DAYLREFPT2 PERIMETER_TOP_ZN_4 PERIMETER_TOP_ZN_4_DAYLCTRL SplitFlux Stepped 0.14 2074.94 287.38


Exterior Lighting

Total Watts Astronomical Clock/Schedule Schedule Name Scheduled Hours/Week [hr] Hours/Week > 1% [hr] Full Load Hours/Week [hr] Consumption [GJ]
EXTERIOR_LIGHTS_A 13279.00 AstronomicalClock -   42.11 42.11 104.95
EXTERIOR_LIGHTS_B 44301.60 AstronomicalClock -   83.57 71.13 591.52
Exterior Lighting Total 57580.60           696.47



Table of Contents

Report: Equipment Summary

For: Entire Facility

Timestamp: 2023-10-16 08:43:39

Central Plant

Type Reference Capacity [W] Reference Efficiency [W/W] Rated Capacity [W] Rated Efficiency [W/W] IPLV in SI Units [W/W] IPLV in IP Units [Btu/W-h]
BYPASS HEAT EXCHANGER HeatExchanger:FluidToFluid 2320560.81          
HEATSYS1 BOILER Boiler:HotWater 3442804.66 0.81        
COOLSYS1 CHILLER1 Chiller:Electric:ReformulatedEIR 1180245.77 6.28 1129649.87 5.98 6.84 23.33
COOLSYS1 CHILLER2 Chiller:Electric:ReformulatedEIR 1180245.77 6.28 1129649.87 5.98 6.84 23.33
CENTRAL TOWER FluidCooler:TwoSpeed 582060.00          
CENTRAL BOILER Boiler:HotWater 584202.86 0.80        
TOWERWATERSYS COOLTOWER 1 CoolingTower:VariableSpeed 1402076.60          
TOWERWATERSYS COOLTOWER 2 CoolingTower:VariableSpeed 1402076.60          


Cooling Coils

Type Design Coil Load [W] Nominal Total Capacity [W] Nominal Sensible Capacity [W] Nominal Latent Capacity [W] Nominal Sensible Heat Ratio Nominal Efficiency [W/W] Nominal Coil UA Value [W/C] Nominal Coil Surface Area [m2]
VAV_BOT WITH REHEAT COOLING COIL Coil:Cooling:Water 194585.29 328097.05 201626.38 126470.67 0.61 - 65619.45 665.55
VAV_MID WITH REHEAT COOLING COIL Coil:Cooling:Water 1817578.77 3043069.59 1868368.76 1174700.82 0.61 - 603136.28 6117.34
VAV_TOP WITH REHEAT COOLING COIL Coil:Cooling:Water 203672.51 345420.29 212455.27 132965.02 0.62 - 69556.50 705.48
CAV_BAS COOLING COIL Coil:Cooling:Water 110073.14 185004.23 115151.46 69852.76 0.62 - 33859.13 343.42
AIRLOOP DATACENTER BASEMENT COOLING COIL Coil:Cooling:WaterToAirHeatPump:EquationFit   466437.89 262502.94 203934.95 0.56 0.00    
AIRLOOP DATACENTER BOT COOLING COIL Coil:Cooling:WaterToAirHeatPump:EquationFit   10807.09 6147.89 4659.20 0.57 0.00    
AIRLOOP DATACENTER MID COOLING COIL Coil:Cooling:WaterToAirHeatPump:EquationFit   103961.65 59130.97 44830.68 0.57 0.00    
AIRLOOP DATACENTER TOP COOLING COIL Coil:Cooling:WaterToAirHeatPump:EquationFit   10570.02 6012.39 4557.63 0.57 0.00    
Nominal values are gross at rated conditions, i.e., the supply air fan heat and electric power NOT accounted for.

DX Cooling Coils

DX Cooling Coil Type Standard Rated Net Cooling Capacity [W] Standard Rated Net COP [W/W] EER [Btu/W-h] SEER User [Btu/W-h] SEER Standard [Btu/W-h] IEER [Btu/W-h]
None              


DX Cooling Coil ASHRAE 127 Standard Ratings Report

DX Cooling Coil Type Rated Net Cooling Capacity Test A [W] Rated Electric Power Test A [W] Rated Net Cooling Capacity Test B [W] Rated Electric Power Test B [W] Rated Net Cooling Capacity Test C [W] Rated Electric Power Test C [W] Rated Net Cooling Capacity Test D [W] Rated Electric Power Test D [W]
None                  


DX Heating Coils

DX Heating Coil Type High Temperature Heating (net) Rating Capacity [W] Low Temperature Heating (net) Rating Capacity [W] HSPF [Btu/W-h] Region Number
None          


Heating Coils

Type Design Coil Load [W] Nominal Total Capacity [W] Nominal Efficiency [W/W]
CORE_BOTTOM VAV BOX REHEAT COIL Coil:Heating:Water 25791.51 24454.28 -
CORE_MID VAV BOX REHEAT COIL Coil:Heating:Water 515371.91 488267.08 -
CORE_TOP VAV BOX REHEAT COIL Coil:Heating:Water 111653.25 105821.88 -
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL Coil:Heating:Water 21629.82 20497.98 -
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL Coil:Heating:Water 14800.43 14025.83 -
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL Coil:Heating:Water 23695.44 22455.23 -
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL Coil:Heating:Water 12601.41 11942.21 -
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL Coil:Heating:Water 305019.35 289043.43 -
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL Coil:Heating:Water 202437.02 191833.39 -
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL Coil:Heating:Water 309716.07 293493.70 -
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL Coil:Heating:Water 199861.14 189392.58 -
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL Coil:Heating:Water 38505.23 36487.65 -
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL Coil:Heating:Water 25419.30 24087.34 -
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL Coil:Heating:Water 39023.78 36978.99 -
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL Coil:Heating:Water 25434.92 24102.13 -
VAV_BOT WITH REHEAT HEATING COIL Coil:Heating:Water 101691.05 69087.22 -
VAV_MID WITH REHEAT HEATING COIL Coil:Heating:Water 1044136.00 688507.71 -
VAV_TOP WITH REHEAT HEATING COIL Coil:Heating:Water 102308.46 70434.50 -
CAV_BAS HEATING COIL Coil:Heating:Water 323708.58 245432.64 -
AIRLOOP DATACENTER BASEMENT HEATING COIL Coil:Heating:WaterToAirHeatPump:EquationFit   466437.89 0.00
AIRLOOP DATACENTER BOT HEATING COIL Coil:Heating:WaterToAirHeatPump:EquationFit   10807.09 0.00
AIRLOOP DATACENTER MID HEATING COIL Coil:Heating:WaterToAirHeatPump:EquationFit   103961.65 0.00
AIRLOOP DATACENTER TOP HEATING COIL Coil:Heating:WaterToAirHeatPump:EquationFit   10570.02 0.00
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL Coil:Heating:Electric   24207.99 1.00
AIRLOOP DATACENTER BOT_SUPPHEATCOIL Coil:Heating:Electric   1118.31 1.00
AIRLOOP DATACENTER MID_SUPPHEATCOIL Coil:Heating:Electric   11183.09 1.00
AIRLOOP DATACENTER TOP_SUPPHEATCOIL Coil:Heating:Electric   1118.31 1.00
Nominal values are gross at rated conditions, i.e., the supply air fan heat and electric power NOT accounted for.

Fans

Type Total Efficiency [W/W] Delta Pressure [pa] Max Air Flow Rate [m3/s] Rated Electricity Rate [W] Rated Power Per Max Air Flow Rate [W-s/m3] Motor Heat In Air Fraction Fan Energy Index End Use Subcategory Design Day Name for Fan Sizing Peak Date/Time for Fan Sizing Peak
VAV_BOT WITH REHEAT FAN Fan:VariableVolume 0.61 1389.42 11.66 26477.02 2271.59 1.00 1.11 General GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 15:10:00
VAV_MID WITH REHEAT FAN Fan:VariableVolume 0.61 1389.42 107.83 244950.13 2271.59 1.00 1.08 General GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 15:20:00
VAV_TOP WITH REHEAT FAN Fan:VariableVolume 0.61 1389.42 12.30 27942.39 2271.59 1.00 1.11 General GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 15:30:00
CAV_BAS FAN Fan:ConstantVolume 0.60 1018.41 6.82 11488.25 1684.71 1.00 1.15 General GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 00:10:00
AIRLOOP DATACENTER BASEMENT SUPPLY FAN Fan:OnOff 0.62 1018.41 24.54 40470.70 1649.25 1.00 1.14 General GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 07:10:00
AIRLOOP DATACENTER BOT SUPPLY FAN Fan:OnOff 0.56 622.50 0.59 655.68 1120.11 1.00 1.54 General GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 00:10:00
AIRLOOP DATACENTER MID SUPPLY FAN Fan:OnOff 0.56 622.50 5.63 6305.84 1120.11 1.00 1.15 General GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 00:10:00
AIRLOOP DATACENTER TOP SUPPLY FAN Fan:OnOff 0.56 622.50 0.57 641.20 1120.11 1.00 1.55 General GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 00:10:00


Pumps

Type Control Head [pa] Water Flow [m3/s] Electricity Rate [W] Power Per Water Flow Rate [W-s/m3] Motor Efficiency [W/W] End Use Subcategory
COOLSYS1 PUMP SECONDARY Pump:VariableSpeed Intermittent 105797.75 0.098950 16155.44 163269.45 0.90 General
HEATSYS1 PUMP Pump:VariableSpeed Intermittent 180705.70 0.030119 9070.57 301156.09 0.90 General
COOLSYS1 CHILLER1 PUMP Pump:ConstantSpeed Intermittent 73247.35 0.049475 5592.48 113036.94 0.90 General
COOLSYS1 CHILLER2 PUMP Pump:ConstantSpeed Intermittent 73247.35 0.049475 5592.48 113036.94 0.90 General
PLANT CIRC PUMP Pump:ConstantSpeed Intermittent 179045.11 0.014493 3696.33 255050.01 0.90 General
SWHSYS1 PUMP Pump:ConstantSpeed Intermittent 29891.00 0.000440 56.21 127739.32 0.30 General
TOWERWATERSYS PUMP HeaderedPumps:VariableSpeed Intermittent 148556.62 0.116812 28920.06 247577.87 0.90 General


Service Water Heating

Type Storage Volume [m3] Input [W] Thermal Efficiency [W/W] Recovery Efficiency [W/W] Energy Factor
SWHSYS1 WATER HEATER WaterHeater:Mixed 1.14 87921.32 0.80 0.48 0.06



Table of Contents

Report: HVAC Sizing Summary

For: Entire Facility

Timestamp: 2023-10-16 08:43:39

Zone Sensible Cooling

Calculated Design Load [W] User Design Load [W] User Design Load per Area [W/m2] Calculated Design Air Flow [m3/s] User Design Air Flow [m3/s] Design Day Name Date/Time Of Peak {TIMESTAMP} Thermostat Setpoint Temperature at Peak Load [C] Indoor Temperature at Peak Load [C] Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] Outdoor Temperature at Peak Load [C] Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] Minimum Outdoor Air Flow Rate [m3/s] Heat Gain Rate from DOAS [W]
BASEMENT 82553.08 82553.08 29.70 6.819 6.819 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 24.00 24.00 0.00742 21.56 0.00629 1.200 0.00
CORE_BOTTOM 85532.33 85532.33 34.27 7.064 7.064 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 24.00 24.00 0.00736 21.56 0.00629 1.078 0.00
CORE_MID 805659.31 805659.31 322.76 66.527 66.527 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 24.00 24.00 0.00739 21.56 0.00629 10.778 0.00
CORE_TOP 77939.31 77939.31 31.22 6.435 6.435 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 24.00 24.00 0.00740 21.56 0.00629 1.078 0.00
PERIMETER_BOT_ZN_3 14368.62 14368.62 45.85 1.197 1.197 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 14:20:00 24.00 24.00 0.00724 33.40 0.00631 0.135 0.00
PERIMETER_BOT_ZN_2 19479.39 19479.39 96.44 1.623 1.623 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 09:00:00 24.00 24.00 0.00712 24.60 0.00629 0.087 0.00
PERIMETER_BOT_ZN_1 24109.11 24109.11 76.92 2.008 2.008 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 13:30:00 24.00 24.00 0.00715 33.00 0.00631 0.135 0.00
PERIMETER_BOT_ZN_4 23888.42 23888.42 118.27 1.990 1.990 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 17:20:00 24.00 24.00 0.00709 30.63 0.00630 0.087 0.00
PERIMETER_MID_ZN_3 136839.93 136839.93 436.61 11.399 11.399 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 14:40:00 24.00 24.00 0.00723 33.40 0.00631 1.353 0.00
PERIMETER_MID_ZN_2 207805.49 207805.49 1028.87 17.310 17.310 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 09:20:00 24.00 24.00 0.00710 25.51 0.00629 0.872 0.00
PERIMETER_MID_ZN_1 246290.67 246290.67 785.82 20.516 20.516 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 13:50:00 24.00 24.00 0.00713 33.27 0.00631 1.353 0.00
PERIMETER_MID_ZN_4 224695.19 224695.19 1112.49 18.717 18.717 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 17:30:00 24.00 24.00 0.00709 30.36 0.00630 0.872 0.00
PERIMETER_TOP_ZN_3 15383.92 15383.92 49.09 1.281 1.281 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 15:10:00 24.00 24.00 0.00719 33.24 0.00631 0.135 0.00
PERIMETER_TOP_ZN_2 20780.74 20780.74 102.89 1.731 1.731 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 09:40:00 24.00 24.00 0.00709 26.41 0.00630 0.087 0.00
PERIMETER_TOP_ZN_1 26241.13 26241.13 83.73 2.186 2.186 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 13:50:00 24.00 24.00 0.00712 33.27 0.00631 0.135 0.00
PERIMETER_TOP_ZN_4 23599.31 23599.31 116.84 1.966 1.966 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 17:30:00 24.00 24.00 0.00708 30.36 0.00630 0.087 0.00
DATACENTER_BOT_ZN_6 8909.34 8909.34 246.10 0.585 0.585 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 19:30:00 27.00 27.00 0.00708 26.28 0.00630 0.016 0.00
DATACENTER_MID_ZN_6 85682.56 85682.56 2366.74 5.630 5.630 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 19:30:00 27.00 27.00 0.00708 26.28 0.00630 0.156 0.00
DATACENTER_TOP_ZN_6 8712.47 8712.47 240.66 0.572 0.572 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 19:30:00 27.00 27.00 0.00708 26.28 0.00630 0.016 0.00
DATACENTER_BASEMENT_ZN_6 373481.81 373481.81 476.57 24.539 24.539 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 07:00:00 27.00 27.00 0.00704 18.84 0.00628 0.338 0.00
The Design Load is the zone sensible load only. It does not include any system effects or ventilation loads.

Zone Sensible Heating

Calculated Design Load [W] User Design Load [W] User Design Load per Area [W/m2] Calculated Design Air Flow [m3/s] User Design Air Flow [m3/s] Design Day Name Date/Time Of Peak {TIMESTAMP} Thermostat Setpoint Temperature at Peak Load [C] Indoor Temperature at Peak Load [C] Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] Outdoor Temperature at Peak Load [C] Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] Minimum Outdoor Air Flow Rate [m3/s] Heat Gain Rate from DOAS [W]
BASEMENT 0.00 0.00 0.00 0.000 1.200 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 22.75 0.00034 -27.60 0.00034 1.200 0.00
CORE_BOTTOM 7875.70 7875.70 3.16 0.382 1.078 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00800 -27.60 0.00034 1.078 0.00
CORE_MID 340208.24 340208.24 136.29 16.468 16.468 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00800 -27.60 0.00034 10.778 0.00
CORE_TOP 78157.42 78157.42 31.31 3.804 3.804 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00800 -27.60 0.00034 1.078 0.00
PERIMETER_BOT_ZN_3 15136.09 15136.09 48.29 0.738 0.738 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00780 -27.60 0.00034 0.135 0.00
PERIMETER_BOT_ZN_2 10356.48 10356.48 51.28 0.505 0.505 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00780 -27.60 0.00034 0.087 0.00
PERIMETER_BOT_ZN_1 16580.21 16580.21 52.90 0.808 0.808 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00782 -27.60 0.00034 0.135 0.00
PERIMETER_BOT_ZN_4 8819.30 8819.30 43.67 0.430 0.430 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00775 -27.60 0.00034 0.087 0.00
PERIMETER_MID_ZN_3 213421.17 213421.17 680.96 10.410 10.410 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00768 -27.60 0.00034 1.353 0.00
PERIMETER_MID_ZN_2 141642.72 141642.72 701.29 6.909 6.909 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00768 -27.60 0.00034 0.872 0.00
PERIMETER_MID_ZN_1 216704.95 216704.95 691.42 10.571 10.571 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00768 -27.60 0.00034 1.353 0.00
PERIMETER_MID_ZN_4 139841.48 139841.48 692.37 6.821 6.821 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00767 -27.60 0.00034 0.872 0.00
PERIMETER_TOP_ZN_3 26939.43 26939.43 85.96 1.315 1.315 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00768 -27.60 0.00034 0.135 0.00
PERIMETER_TOP_ZN_2 17784.01 17784.01 88.05 0.868 0.868 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00768 -27.60 0.00034 0.087 0.00
PERIMETER_TOP_ZN_1 27301.99 27301.99 87.11 1.332 1.332 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00769 -27.60 0.00034 0.135 0.00
PERIMETER_TOP_ZN_4 17794.90 17794.90 88.10 0.868 0.868 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00768 -27.60 0.00034 0.087 0.00
DATACENTER_BOT_ZN_6 0.00 0.00 0.00 0.000 0.016 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 05:30:00 18.00 24.16 0.00098 -27.60 0.00034 0.016 0.00
DATACENTER_MID_ZN_6 0.00 0.00 0.00 0.000 0.156 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 05:40:00 18.00 22.16 0.00098 -27.60 0.00034 0.156 0.00
DATACENTER_TOP_ZN_6 0.00 0.00 0.00 0.000 0.016 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 05:30:00 18.00 19.70 0.00098 -27.60 0.00034 0.016 0.00
DATACENTER_BASEMENT_ZN_6 0.00 0.00 0.00 0.000 0.338 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 00:40:00 18.00 27.00 0.00700 -27.60 0.00034 0.338 0.00
The Design Load is the zone sensible load only. It does not include any system effects or ventilation loads.

System Design Air Flow Rates

Calculated cooling [m3/s] User cooling [m3/s] Calculated heating [m3/s] User heating [m3/s] Adjusted cooling [m3/s] Adjusted heating [m3/s] Adjusted main [m3/s] Calculated Heating Air Flow Ratio [] User Heating Air Flow Ratio []
VAV_BOT WITH REHEAT 11.66 11.66 3.56 3.56 11.6557 3.5586 11.6557 0.3053 0.3000
VAV_MID WITH REHEAT 107.83 107.83 51.18 51.18 107.8319 51.1804 107.8319 0.4746 0.3000
VAV_TOP WITH REHEAT 12.30 12.30 8.19 8.19 12.3008 8.1867 12.3008 0.6655 0.3000
CAV_BAS 6.82 6.82 1.20 1.20 6.8191 6.8191 6.8191 1.0000 1.0000
AIRLOOP DATACENTER BASEMENT 24.54 24.54 0.34 0.34 24.5389 24.5388 24.5389 1.0000 1.0000
AIRLOOP DATACENTER BOT 0.59 0.59 0.02 0.02 0.5854 0.5854 0.5854 1.0000 1.0000
AIRLOOP DATACENTER MID 5.63 5.63 0.16 0.16 5.6297 5.6297 5.6297 1.0000 1.0000
AIRLOOP DATACENTER TOP 0.57 0.57 0.02 0.02 0.5724 0.5724 0.5724 1.0000 1.0000


Plant Loop Coincident Design Fluid Flow Rate Adjustments

Previous Design Volume Flow Rate [m3/s] Algorithm Volume Flow Rate [m3/s] Coincident Design Volume Flow Rate [m3/s] Coincident Size Adjusted Peak Sizing Period Name Peak Day into Period {TIMESTAMP}[day] Peak Hour Of Day {TIMESTAMP}[hr] Peak Step Start Minute {TIMESTAMP}[min]
None                


Coil Sizing Summary

Coil Type HVAC Type HVAC Name Coil Final Gross Total Capacity [W] Coil Final Gross Sensible Capacity [W] Coil Final Reference Air Volume Flow Rate [m3/s] Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] Coil U-value Times Area Value [W/K] Design Day Name at Sensible Ideal Loads Peak Date/Time at Sensible Ideal Loads Peak Design Day Name at Air Flow Ideal Loads Peak Date/Time at Air Flow Ideal Loads Peak Coil Total Capacity at Ideal Loads Peak [W] Coil Sensible Capacity at Ideal Loads Peak [W] Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] Coil Entering Air Drybulb at Ideal Loads Peak [C] Coil Entering Air Wetbulb at Ideal Loads Peak [C] Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Coil Leaving Air Drybulb at Ideal Loads Peak [C] Coil Leaving Air Wetbulb at Ideal Loads Peak [C] Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Outdoor Air Drybulb at Ideal Loads Peak [C] Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Outdoor Air Wetbulb at Ideal Loads Peak [C] Outdoor Air Flow Percentage at Ideal Loads Peak [%] Zone Air Drybulb at Ideal Loads Peak [C] Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Zone Air Relative Humidity at Ideal Loads Peak [%] Zone Sensible Heat Gain at Ideal Loads Peak [W] Zone Latent Heat Gain at Ideal Loads Peak [W] Coil Total Capacity at Rating Conditions [W] Coil Sensible Capacity at Rating Conditions [W]
CORE_BOTTOM VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT CORE_BOTTOM VAV BOX 25791.505 25791.505 2.034507 0.00022564 543.507 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 25791.51 25791.51 2.034507 12.80 10.41 0.00800000 40.00 19.63 0.00800000 -27.60 0.00034190 -27.60 0.0000 21.00 0.00799972 45.2294 7875.70 0.00 25884.64 25884.64
CORE_MID VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT CORE_MID VAV BOX 515371.914 515371.914 19.891465 0.00450870 12910.418 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 515371.91 515371.91 19.891465 12.80 10.41 0.00800000 40.00 19.63 0.00800000 -27.60 0.00034190 -27.60 0.0000 21.00 0.00800000 45.2310 340208.24 0.00 516976.72 516976.72
CORE_TOP VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT CORE_TOP VAV BOX 111653.252 111653.252 3.803763 0.00097679 2946.068 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 111653.25 111653.25 3.803763 12.80 10.41 0.00800000 40.00 19.63 0.00800000 -27.60 0.00034190 -27.60 0.0000 21.00 0.00800000 45.2310 78157.42 0.00 112030.21 112030.21
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_BOT_ZN_3 VAV BOX 21629.818 21629.818 0.737784 0.00018923 570.400 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21629.82 21629.82 0.737784 12.80 10.41 0.00800000 40.00 19.63 0.00800000 -27.60 0.00034190 -27.60 0.0000 21.00 0.00779530 44.0905 15136.09 0.00 21700.53 21700.53
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_BOT_ZN_2 VAV BOX 14800.433 14800.433 0.504891 0.00012948 390.283 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 14800.43 14800.43 0.504891 12.80 10.41 0.00800000 40.00 19.63 0.00800000 -27.60 0.00034190 -27.60 0.0000 21.00 0.00780326 44.1350 10356.48 0.00 14848.68 14848.68
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_BOT_ZN_1 VAV BOX 23695.437 23695.437 0.808359 0.00020730 624.831 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 23695.44 23695.44 0.808359 12.80 10.41 0.00800000 40.00 19.63 0.00800000 -27.60 0.00034190 -27.60 0.0000 21.00 0.00781675 44.2102 16580.21 0.00 23772.60 23772.60
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_BOT_ZN_4 VAV BOX 12601.405 12601.405 0.429743 0.00011024 332.342 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 12601.41 12601.41 0.429743 12.80 10.41 0.00800000 40.00 19.63 0.00800000 -27.60 0.00034190 -27.60 0.0000 21.00 0.00775451 43.8630 8819.30 0.00 12642.82 12642.82
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_MID_ZN_3 VAV BOX 305019.349 305019.349 10.410358 0.00266844 8041.455 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 305019.35 305019.35 10.410358 12.80 10.41 0.00800000 40.00 19.63 0.00800000 -27.60 0.00034190 -27.60 0.0000 21.00 0.00767811 43.4383 213421.17 0.00 306000.54 306000.54
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_MID_ZN_2 VAV BOX 202437.020 202437.020 6.909475 0.00177101 5336.906 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 202437.02 202437.02 6.909475 12.80 10.41 0.00800000 40.00 19.63 0.00800000 -27.60 0.00034190 -27.60 0.0000 21.00 0.00767686 43.4315 141642.72 0.00 203087.54 203087.54
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_MID_ZN_1 VAV BOX 309716.067 309716.067 10.570846 0.00270953 8165.212 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 309716.07 309716.07 10.570846 12.80 10.41 0.00800000 40.00 19.63 0.00800000 -27.60 0.00034190 -27.60 0.0000 21.00 0.00768288 43.4650 216704.95 0.00 310711.88 310711.88
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_MID_ZN_4 VAV BOX 199861.138 199861.138 6.821494 0.00174847 5269.019 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 199861.14 199861.14 6.821494 12.80 10.41 0.00800000 40.00 19.63 0.00800000 -27.60 0.00034190 -27.60 0.0000 21.00 0.00767291 43.4094 139841.48 0.00 200503.54 200503.54
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_TOP_ZN_3 VAV BOX 38505.230 38505.230 1.314526 0.00033686 1015.024 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 38505.23 38397.36 1.314526 12.80 10.41 0.00800000 40.00 19.63 0.00800000 -27.60 0.00034190 -27.60 0.0000 21.00 0.00768303 43.4667 26939.43 0.00 38628.24 38628.24
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_TOP_ZN_2 VAV BOX 25419.301 25419.301 0.867809 0.00022238 670.062 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 25419.30 25419.30 0.867809 12.80 10.41 0.00800000 40.00 19.63 0.00800000 -27.60 0.00034190 -27.60 0.0000 21.00 0.00767995 43.4497 17784.01 0.00 25500.45 25500.45
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_TOP_ZN_1 VAV BOX 39023.780 39023.780 1.332244 0.00034140 1028.688 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 39023.78 39023.78 1.332244 12.80 10.41 0.00800000 40.00 19.63 0.00800000 -27.60 0.00034190 -27.60 0.0000 21.00 0.00768705 43.4892 27301.99 0.00 39148.41 39148.41
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_TOP_ZN_4 VAV BOX 25434.922 25434.922 0.868347 0.00022252 670.472 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 25434.92 25434.92 0.868347 12.80 10.41 0.00800000 40.00 19.63 0.00800000 -27.60 0.00034190 -27.60 0.0000 21.00 0.00768035 43.4519 17794.90 0.00 25516.11 25516.11
VAV_BOT WITH REHEAT COOLING COIL Coil:Cooling:Water AirLoopHVAC VAV_BOT WITH REHEAT 194585.286 -999.000 11.655704 0.00827811 -999.000 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 15:10:00 194585.29 192505.00 11.655704 26.05 14.53 0.00708318 10.68 8.51 0.00700000 33.40 0.00630683 16.37 21.7764 24.00 0.00729942 34.4333 139863.93 0.00 219574.77 216437.63
VAV_BOT WITH REHEAT HEATING COIL Coil:Heating:Water AirLoopHVAC VAV_BOT WITH REHEAT 101691.050 101691.050 3.496711 0.00088964 1578.769 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 06:30:00 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 101691.05 101691.05 3.496711 -14.68 -14.68 0.00237751 12.80 10.41 0.00800000 -27.60 0.00034190 -27.60 72.5879 19.81 0.00772998 47.0566 35041.96 0.00 83549.98 83549.98
VAV_MID WITH REHEAT COOLING COIL Coil:Cooling:Water AirLoopHVAC VAV_MID WITH REHEAT 1817578.773 -999.000 107.831862 0.07732400 -999.000 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 15:20:00 1817578.77 1799813.19 107.831862 26.21 14.59 0.00707663 10.68 8.51 0.00700000 33.40 0.00630683 16.37 23.5385 24.00 0.00731387 34.5006 1293342.28 0.00 2049140.46 2021722.57
VAV_MID WITH REHEAT HEATING COIL Coil:Heating:Water AirLoopHVAC VAV_MID WITH REHEAT 1044136.002 1044136.002 32.349559 0.00913456 15812.226 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 05:30:00 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 1044136.00 1044136.00 32.349559 -17.70 -17.70 0.00190076 12.80 10.41 0.00800000 -27.60 0.00034190 -27.60 78.4615 17.87 0.00757052 52.0491 383297.13 0.00 832607.55 832607.55
VAV_TOP WITH REHEAT COOLING COIL Coil:Cooling:Water AirLoopHVAC VAV_TOP WITH REHEAT 203672.512 -999.000 12.300790 0.00866470 -999.000 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 15:30:00 203672.51 201753.67 12.300790 25.95 14.49 0.00707283 10.68 8.51 0.00700000 33.40 0.00630683 16.37 20.6344 24.00 0.00727281 34.3091 147175.04 0.00 230005.32 227057.86
VAV_TOP WITH REHEAT HEATING COIL Coil:Heating:Water AirLoopHVAC VAV_TOP WITH REHEAT 102308.455 102308.455 3.690237 0.00089504 1597.676 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 01:50:00 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 102308.46 102308.46 3.690237 -13.40 -13.40 0.00257360 12.80 10.41 0.00800000 -27.60 0.00034190 -27.60 68.7812 15.98 0.00758254 58.7469 38237.25 0.00 85150.87 85150.87
CAV_BAS COOLING COIL Coil:Cooling:Water AirLoopHVAC CAV_BAS 110073.141 -999.000 6.819106 0.00468277 -999.000 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 13:00:00 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 110073.14 106760.32 6.819106 25.70 14.54 0.00723461 11.23 8.74 0.00700000 32.60 0.00630558 16.10 17.5999 24.00 0.00746371 35.1995 72830.29 0.00 124296.80 122031.40
CAV_BAS HEATING COIL Coil:Heating:Water AirLoopHVAC CAV_BAS 323708.581 323708.581 6.819106 0.00283194 6941.245 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 00:10:00 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 00:10:00 323708.58 323708.58 6.819106 -4.86 -9.35 0.00034190 40.00 19.63 0.00800000 -27.60 0.00034190 -27.60 17.5999 22.86 0.00034190 1.7470 0.00 0.00 258881.68 258881.68
AIRLOOP DATACENTER BASEMENT COOLING COIL COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoopHVAC AIRLOOP DATACENTER BASEMENT 466437.893 262502.939 24.538896 0.01142303 -999.000 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 07:10:00 405303.45 403832.34 -999.0 28.68 15.39 0.00703181 12.80 9.41 0.00700000 33.40 0.00630683 16.37 -999.0000 27.00 0.00704196 27.8114 373034.82 0.00 -999.00 -999.00
AIRLOOP DATACENTER BOT COOLING COIL COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoopHVAC AIRLOOP DATACENTER BOT 10807.087 6147.885 0.585375 0.00026466 -999.000 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 19:30:00 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 19:30:00 9339.78 9274.26 -999.0 28.06 15.21 0.00705998 12.80 9.41 0.00700000 26.28 0.00629588 13.94 -999.0000 27.00 0.00708094 27.9616 8909.34 0.00 -999.00 -999.00
AIRLOOP DATACENTER MID COOLING COIL COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoopHVAC AIRLOOP DATACENTER MID 103961.649 59130.970 5.629668 0.00254601 -999.000 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 19:30:00 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 19:30:00 89850.72 89196.79 -999.0 28.06 15.21 0.00706223 12.80 9.41 0.00700000 26.28 0.00629588 13.94 -999.0000 27.00 0.00708412 27.9741 85682.56 0.00 -999.00 -999.00
AIRLOOP DATACENTER TOP COOLING COIL COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoopHVAC AIRLOOP DATACENTER TOP 10570.015 6012.389 0.572441 0.00025886 -999.000 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 19:30:00 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 19:30:00 9135.16 9069.63 -999.0 28.06 15.21 0.00706134 12.80 9.41 0.00700000 26.28 0.00629588 13.94 -999.0000 27.00 0.00708283 27.9690 8712.47 0.00 -999.00 -999.00
AIRLOOP DATACENTER BASEMENT HEATING COIL COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoopHVAC AIRLOOP DATACENTER BASEMENT 466437.893 466437.893 24.538896 0.01142303 -999.000 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 00:10:00 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 00:10:00 466437.89 466437.89 24.538896 -27.60 -27.60 0.00034190 40.00 19.63 0.00800000 -27.60 0.00034190 -27.60 1.3790 27.00 0.00700000 27.6430 0.00 0.00 -999.00 -999.00
AIRLOOP DATACENTER BOT HEATING COIL COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoopHVAC AIRLOOP DATACENTER BOT 10807.087 10807.087 0.585375 0.00026466 -999.000 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 00:10:00 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 00:10:00 10807.09 10807.09 0.585375 -27.60 -27.60 0.00034190 40.00 19.63 0.00800000 -27.60 0.00034190 -27.60 2.6705 24.93 0.00098395 4.4353 0.00 0.00 -999.00 -999.00
AIRLOOP DATACENTER MID HEATING COIL COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoopHVAC AIRLOOP DATACENTER MID 103961.649 103961.649 5.629668 0.00254601 -999.000 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 00:10:00 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 00:10:00 103961.65 103961.65 5.629668 -27.60 -27.60 0.00034190 40.00 19.63 0.00800000 -27.60 0.00034190 -27.60 2.7768 23.40 0.00098397 4.8597 0.00 0.00 -999.00 -999.00
AIRLOOP DATACENTER TOP HEATING COIL COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoopHVAC AIRLOOP DATACENTER TOP 10570.015 10570.015 0.572441 0.00025886 -999.000 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 00:10:00 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 00:10:00 10570.02 10570.02 0.572441 -27.60 -27.60 0.00034190 40.00 19.63 0.00800000 -27.60 0.00034190 -27.60 2.7308 21.93 0.00098340 5.3102 0.00 0.00 -999.00 -999.00
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL Coil:Heating:Electric AirLoopHVAC AIRLOOP DATACENTER BASEMENT 24207.992 24207.992 -999.0 -999.0 -999.000 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 00:10:00 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 00:10:00 24207.99 24207.99 24.538896 -0.38 -0.38 0.00690818 40.00 19.63 0.00800000 -27.60 0.00034190 -27.60 1.3790 27.00 0.00700000 27.6430 0.00 0.00 -999.00 -999.00
AIRLOOP DATACENTER BOT_SUPPHEATCOIL Coil:Heating:Electric AirLoopHVAC AIRLOOP DATACENTER BOT 1118.309 1118.309 -999.0 -999.0 -999.000 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 00:10:00 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 00:10:00 1118.31 1118.31 0.585375 -0.74 -5.59 0.00096681 40.00 19.63 0.00800000 -27.60 0.00034190 -27.60 2.6705 24.93 0.00098395 4.4353 0.00 0.00 -999.00 -999.00
AIRLOOP DATACENTER MID_SUPPHEATCOIL Coil:Heating:Electric AirLoopHVAC AIRLOOP DATACENTER MID 11183.090 11183.090 -999.0 -999.0 -999.000 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 00:10:00 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 00:10:00 11183.09 11183.09 5.629668 -0.77 -5.61 0.00096614 40.00 19.63 0.00800000 -27.60 0.00034190 -27.60 2.7768 23.40 0.00098397 4.8597 0.00 0.00 -999.00 -999.00
AIRLOOP DATACENTER TOP_SUPPHEATCOIL Coil:Heating:Electric AirLoopHVAC AIRLOOP DATACENTER TOP 1118.309 1118.309 -999.0 -999.0 -999.000 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 00:10:00 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 00:10:00 1118.31 1118.31 0.572441 -0.75 -5.60 0.00096588 40.00 19.63 0.00800000 -27.60 0.00034190 -27.60 2.7308 21.93 0.00098340 5.3102 0.00 0.00 -999.00 -999.00



Table of Contents

Report: Coil Sizing Details

For: Entire Facility

Timestamp: 2023-10-16 08:43:39

Coils

Coil Type Coil Location HVAC Type HVAC Name Zone Name(s) System Sizing Method Concurrence System Sizing Method Capacity System Sizing Method Air Flow Autosized Coil Capacity? Autosized Coil Airflow? Autosized Coil Water Flow? OA Pretreated prior to coil inlet? Coil Final Gross Total Capacity [W] Coil Final Gross Sensible Capacity [W] Coil Final Reference Air Volume Flow Rate [m3/s] Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] Coil U-value Times Area Value [W/K] Terminal Unit Reheat Coil Multiplier DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio Moist Air Heat Capacity [J/kg-K] Dry Air Heat Capacity [J/kg-K] Standard Air Density Adjusted for Elevation [kg/m3] Supply Fan Name for Coil Supply Fan Type for Coil Supply Fan Maximum Air Volume Flow Rate [m3/s] Supply Fan Maximum Air Mass Flow Rate [kg/s] Plant Name for Coil Plant Fluid Specific Heat Capacity [J/kg-K] Plant Fluid Density [kg/m3] Plant Maximum Fluid Mass Flow Rate [kg/s] Plant Design Fluid Return Temperature [C] Plant Design Fluid Supply Temperature [C] Plant Design Fluid Temperature Difference [deltaC] Plant Design Capacity [W] Coil Capacity Percentage of Plant Design Capacity [%] Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] Design Day Name at Sensible Ideal Loads Peak Date/Time at Sensible Ideal Loads Peak Design Day Name at Total Ideal Loads Peak Date/Time at Total Ideal Loads Peak Design Day Name at Air Flow Ideal Loads Peak Date/Time at Air Flow Ideal Loads Peak Peak Load Type to Size On Coil Total Capacity at Ideal Loads Peak [W] Coil Sensible Capacity at Ideal Loads Peak [W] Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] Coil Entering Air Drybulb at Ideal Loads Peak [C] Coil Entering Air Wetbulb at Ideal Loads Peak [C] Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] Coil Leaving Air Drybulb at Ideal Loads Peak [C] Coil Leaving Air Wetbulb at Ideal Loads Peak [C] Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] Supply Fan Air Heat Gain at Ideal Loads Peak [W] Coil and Fan Net Total Capacity at Ideal Loads Peak [W] Outdoor Air Drybulb at Ideal Loads Peak [C] Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Outdoor Air Wetbulb at Ideal Loads Peak [C] Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] Outdoor Air Flow Percentage at Ideal Loads Peak [%] System Return Air Drybulb at Ideal Loads Peak [C] System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Zone Air Drybulb at Ideal Loads Peak [C] Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Zone Air Relative Humidity at Ideal Loads Peak [%] Zone Sensible Heat Gain at Ideal Loads Peak [W] Zone Latent Heat Gain at Ideal Loads Peak [W] Coil Total Capacity at Rating Conditions [W] Coil Sensible Capacity at Rating Conditions [W] Coil Air Mass Flow Rate at Rating Conditions [kg/s] Coil Entering Air Drybulb at Rating Conditions [C] Coil Entering Air Wetbulb at Rating Conditions [C] Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] Coil Leaving Air Drybulb at Rating Conditions [C] Coil Leaving Air Wetbulb at Rating Conditions [C] Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K]
CORE_BOTTOM VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT CORE_BOTTOM VAV BOX CORE_BOTTOM N/A N/A N/A Yes Yes Yes No 25791.505 25791.505 2.034507 0.00022564 543.507 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.0531 unknown unknown -999.0 -999.0   4197.9300 999.8980 30.11608457 54.44 82.22 27.78 3512092.47 0.7344 0.749142 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 25791.51 25791.51 1.0000 2.14262090 2.034507 12.80 10.41 0.00800000 33059.8 40.00 19.63 0.00800000 60796.0 0.22561232 60.00 32.22 27.78 0.000 25791.51 -27.60 0.00034190 -27.60 0.00000000 0.0000 20.80 0.00799972 21.00 0.00799972 45.2294 7875.70 0.00 25884.64 25884.64 2.14262090 12.80 11.60 0.00800000 33059.8 24.65 16.19 0.00800000 45140.7
CORE_MID VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT CORE_MID VAV BOX CORE_MID N/A N/A N/A Yes Yes Yes No 515371.914 515371.914 19.891465 0.00450870 12910.418 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.0531 unknown unknown -999.0 -999.0   4197.9300 999.8980 30.11608457 54.44 82.22 27.78 3512092.47 14.6742 14.969537 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 515371.91 515371.91 1.0000 20.94849547 19.891465 12.80 10.41 0.00800000 33059.8 40.00 19.63 0.00800000 60796.0 4.50823839 60.00 32.22 27.78 0.000 515371.91 -27.60 0.00034190 -27.60 0.00000000 0.0000 20.87 0.00800000 21.00 0.00800000 45.2310 340208.24 0.00 516976.72 516976.72 20.94849547 12.80 11.60 0.00800000 33059.8 37.00 20.28 0.00800000 57738.3
CORE_TOP VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT CORE_TOP VAV BOX CORE_TOP N/A N/A N/A Yes Yes Yes No 111653.252 111653.252 3.803763 0.00097679 2946.068 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.0531 unknown unknown -999.0 -999.0   4197.9300 999.8980 30.11608457 54.44 82.22 27.78 3512092.47 3.1791 3.243090 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 111653.25 111653.25 1.0000 4.00589474 3.803763 12.80 10.41 0.00800000 33059.8 40.00 19.63 0.00800000 60796.0 0.97669171 60.00 32.22 27.78 0.000 111653.25 -27.60 0.00034190 -27.60 0.00000000 0.0000 20.95 0.00800000 21.00 0.00800000 45.2310 78157.42 0.00 112030.21 112030.21 4.00589474 12.80 11.60 0.00800000 33059.8 40.23 21.25 0.00800000 61026.2
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_BOT_ZN_3 VAV BOX PERIMETER_BOT_ZN_3 N/A N/A N/A Yes Yes Yes No 21629.818 21629.818 0.737784 0.00018923 570.400 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.0531 unknown unknown -999.0 -999.0   4197.9300 999.8980 30.11608457 54.44 82.22 27.78 3512092.47 0.6159 0.628262 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 21629.82 21629.82 1.0000 0.77699003 0.737784 12.80 10.41 0.00800000 33059.8 40.00 19.63 0.00800000 60796.0 0.18920778 60.00 32.22 27.78 0.000 21629.82 -27.60 0.00034190 -27.60 0.00000000 0.0000 20.95 0.00779530 21.00 0.00779530 44.0905 15136.09 0.00 21700.53 21700.53 0.77699003 12.80 11.60 0.00800000 33059.8 40.19 21.24 0.00800000 60988.8
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_BOT_ZN_2 VAV BOX PERIMETER_BOT_ZN_2 N/A N/A N/A Yes Yes Yes No 14800.433 14800.433 0.504891 0.00012948 390.283 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.0531 unknown unknown -999.0 -999.0   4197.9300 999.8980 30.11608457 54.44 82.22 27.78 3512092.47 0.4214 0.429895 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 14800.43 14800.43 1.0000 0.53172091 0.504891 12.80 10.41 0.00800000 33059.8 40.00 19.63 0.00800000 60796.0 0.12946744 60.00 32.22 27.78 0.000 14800.43 -27.60 0.00034190 -27.60 0.00000000 0.0000 20.95 0.00780326 21.00 0.00780326 44.1350 10356.48 0.00 14848.68 14848.68 0.53172091 12.80 11.60 0.00800000 33059.8 40.19 21.24 0.00800000 60985.5
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_BOT_ZN_1 VAV BOX PERIMETER_BOT_ZN_1 N/A N/A N/A Yes Yes Yes No 23695.437 23695.437 0.808359 0.00020730 624.831 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.0531 unknown unknown -999.0 -999.0   4197.9300 999.8980 30.11608457 54.44 82.22 27.78 3512092.47 0.6747 0.688260 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 23695.44 23695.44 1.0000 0.85131496 0.808359 12.80 10.41 0.00800000 33059.8 40.00 19.63 0.00800000 60796.0 0.20727687 60.00 32.22 27.78 0.000 23695.44 -27.60 0.00034190 -27.60 0.00000000 0.0000 20.95 0.00781675 21.00 0.00781675 44.2102 16580.21 0.00 23772.60 23772.60 0.85131496 12.80 11.60 0.00800000 33059.8 40.18 21.24 0.00800000 60984.4
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_BOT_ZN_4 VAV BOX PERIMETER_BOT_ZN_4 N/A N/A N/A Yes Yes Yes No 12601.405 12601.405 0.429743 0.00011024 332.342 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.0531 unknown unknown -999.0 -999.0   4197.9300 999.8980 30.11608457 54.44 82.22 27.78 3512092.47 0.3588 0.366021 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 12601.41 12601.41 1.0000 0.45257965 0.429743 12.80 10.41 0.00800000 33059.8 40.00 19.63 0.00800000 60796.0 0.11023134 60.00 32.22 27.78 0.000 12601.41 -27.60 0.00034190 -27.60 0.00000000 0.0000 20.95 0.00775451 21.00 0.00775451 43.8630 8819.30 0.00 12642.82 12642.82 0.45257965 12.80 11.60 0.00800000 33059.8 40.20 21.24 0.00800000 60994.8
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_MID_ZN_3 VAV BOX PERIMETER_MID_ZN_3 N/A N/A N/A Yes Yes Yes No 305019.349 305019.349 10.410358 0.00266844 8041.455 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.0531 unknown unknown -999.0 -999.0   4197.9300 999.8980 30.11608457 54.44 82.22 27.78 3512092.47 8.6848 8.859618 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 305019.35 305019.35 1.0000 10.96356338 10.410358 12.80 10.41 0.00800000 33059.8 40.00 19.63 0.00800000 60796.0 2.66817011 60.00 32.22 27.78 0.000 305019.35 -27.60 0.00034190 -27.60 0.00000000 0.0000 20.95 0.00767811 21.00 0.00767811 43.4383 213421.17 0.00 306000.54 306000.54 10.96356338 12.80 11.60 0.00800000 33059.8 40.17 21.23 0.00800000 60970.5
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_MID_ZN_2 VAV BOX PERIMETER_MID_ZN_2 N/A N/A N/A Yes Yes Yes No 202437.020 202437.020 6.909475 0.00177101 5336.906 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.0531 unknown unknown -999.0 -999.0   4197.9300 999.8980 30.11608457 54.44 82.22 27.78 3512092.47 5.7640 5.880003 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 202437.02 202437.02 1.0000 7.27664319 6.909475 12.80 10.41 0.00800000 33059.8 40.00 19.63 0.00800000 60796.0 1.77082670 60.00 32.22 27.78 0.000 202437.02 -27.60 0.00034190 -27.60 0.00000000 0.0000 20.95 0.00767686 21.00 0.00767686 43.4315 141642.72 0.00 203087.54 203087.54 7.27664319 12.80 11.60 0.00800000 33059.8 40.17 21.23 0.00800000 60969.3
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_MID_ZN_1 VAV BOX PERIMETER_MID_ZN_1 N/A N/A N/A Yes Yes Yes No 309716.067 309716.067 10.570846 0.00270953 8165.212 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.0531 unknown unknown -999.0 -999.0   4197.9300 999.8980 30.11608457 54.44 82.22 27.78 3512092.47 8.8186 8.996039 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 309716.07 309716.07 1.0000 11.13257993 10.570846 12.80 10.41 0.00800000 33059.8 40.00 19.63 0.00800000 60796.0 2.70925486 60.00 32.22 27.78 0.000 309716.07 -27.60 0.00034190 -27.60 0.00000000 0.0000 20.95 0.00768288 21.00 0.00768288 43.4650 216704.95 0.00 310711.88 310711.88 11.13257993 12.80 11.60 0.00800000 33059.8 40.17 21.23 0.00800000 60970.0
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_MID_ZN_4 VAV BOX PERIMETER_MID_ZN_4 N/A N/A N/A Yes Yes Yes No 199861.138 199861.138 6.821494 0.00174847 5269.019 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.0531 unknown unknown -999.0 -999.0   4197.9300 999.8980 30.11608457 54.44 82.22 27.78 3512092.47 5.6907 5.805184 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 199861.14 199861.14 1.0000 7.18398720 6.821494 12.80 10.41 0.00800000 33059.8 40.00 19.63 0.00800000 60796.0 1.74829406 60.00 32.22 27.78 0.000 199861.14 -27.60 0.00034190 -27.60 0.00000000 0.0000 20.95 0.00767291 21.00 0.00767291 43.4094 139841.48 0.00 200503.54 200503.54 7.18398720 12.80 11.60 0.00800000 33059.8 40.17 21.23 0.00800000 60969.6
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_TOP_ZN_3 VAV BOX PERIMETER_TOP_ZN_3 N/A N/A N/A Yes Yes Yes No 38505.230 38505.230 1.314526 0.00033686 1015.024 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.0531 unknown unknown -999.0 -999.0   4197.9300 999.8980 30.11608457 54.44 82.22 27.78 3512092.47 1.0964 1.118426 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 38505.23 38397.36 1.0000 1.38437933 1.314526 12.80 10.41 0.00800000 33059.8 40.00 19.63 0.00800000 60796.0 0.33682619 60.00 32.22 27.78 0.000 38505.23 -27.60 0.00034190 -27.60 0.00000000 0.0000 20.95 0.00768303 21.00 0.00768303 43.4667 26939.43 0.00 38628.24 38628.24 1.38437933 12.80 11.60 0.00800000 33059.8 40.16 21.23 0.00800000 60962.8
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_TOP_ZN_2 VAV BOX PERIMETER_TOP_ZN_2 N/A N/A N/A Yes Yes Yes No 25419.301 25419.301 0.867809 0.00022238 670.062 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.0531 unknown unknown -999.0 -999.0   4197.9300 999.8980 30.11608457 54.44 82.22 27.78 3512092.47 0.7238 0.738331 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 25419.30 25419.30 1.0000 0.91392446 0.867809 12.80 10.41 0.00800000 33059.8 40.00 19.63 0.00800000 60796.0 0.22235645 60.00 32.22 27.78 0.000 25419.30 -27.60 0.00034190 -27.60 0.00000000 0.0000 20.95 0.00767995 21.00 0.00767995 43.4497 17784.01 0.00 25500.45 25500.45 0.91392446 12.80 11.60 0.00800000 33059.8 40.16 21.23 0.00800000 60962.0
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_TOP_ZN_1 VAV BOX PERIMETER_TOP_ZN_1 N/A N/A N/A Yes Yes Yes No 39023.780 39023.780 1.332244 0.00034140 1028.688 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.0531 unknown unknown -999.0 -999.0   4197.9300 999.8980 30.11608457 54.44 82.22 27.78 3512092.47 1.1111 1.133488 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 39023.78 39023.78 1.0000 1.40303902 1.332244 12.80 10.41 0.00800000 33059.8 40.00 19.63 0.00800000 60796.0 0.34136223 60.00 32.22 27.78 0.000 39023.78 -27.60 0.00034190 -27.60 0.00000000 0.0000 20.95 0.00768705 21.00 0.00768705 43.4892 27301.99 0.00 39148.41 39148.41 1.40303902 12.80 11.60 0.00800000 33059.8 40.16 21.23 0.00800000 60962.4
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_TOP_ZN_4 VAV BOX PERIMETER_TOP_ZN_4 N/A N/A N/A Yes Yes Yes No 25434.922 25434.922 0.868347 0.00022252 670.472 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.0531 unknown unknown -999.0 -999.0   4197.9300 999.8980 30.11608457 54.44 82.22 27.78 3512092.47 0.7242 0.738785 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 25434.92 25434.92 1.0000 0.91449123 0.868347 12.80 10.41 0.00800000 33059.8 40.00 19.63 0.00800000 60796.0 0.22249309 60.00 32.22 27.78 0.000 25434.92 -27.60 0.00034190 -27.60 0.00000000 0.0000 20.95 0.00768035 21.00 0.00768035 43.4519 17794.90 0.00 25516.11 25516.11 0.91449123 12.80 11.60 0.00800000 33059.8 40.16 21.23 0.00800000 60961.8
VAV_BOT WITH REHEAT COOLING COIL Coil:Cooling:Water AirLoop AirLoopHVAC VAV_BOT WITH REHEAT CORE_BOTTOM; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_4; Coincident CoolingDesignCapacity N/A Yes Yes Yes No 194585.286 -999.000 11.655704 0.00827811 -999.000 -999.0000 1.00000 1.00000 1018.0073 1004.8586 1.0531 VAV_BOT WITH REHEAT FAN Fan:VariableVolume 11.655704 12.27508703   4197.9300 999.8980 98.93948206 12.27 6.67 5.60 2325909.71 8.3660 8.365986 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 15:10:00 Sensible 194585.29 192505.00 1.0000 12.27508703 11.655704 26.05 14.53 0.00708318 44230.5 10.68 8.51 0.00700000 28378.4 8.27726342 6.67 12.27 5.60 26477.019 168108.27 33.40 0.00630683 16.37 2.53819000 21.7764 24.00 0.00729942 24.00 0.00729942 34.4333 139863.93 0.00 219574.77 216437.63 12.27508703 26.05 15.89 0.00708318 44230.5 8.73 8.71 0.00698165 26342.7
VAV_BOT WITH REHEAT HEATING COIL Coil:Heating:Water AirLoop AirLoopHVAC VAV_BOT WITH REHEAT CORE_BOTTOM; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_4; Coincident HeatingDesignCapacity N/A Yes Yes Yes No 101691.050 101691.050 3.496711 0.00088964 1578.769 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.0531 VAV_BOT WITH REHEAT FAN Fan:VariableVolume 11.655704 12.27508703   4197.9300 999.8980 30.11608457 54.44 82.22 27.78 3512092.47 2.8955 2.953727 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 06:30:00 unknown unknown GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 101691.05 101691.05 1.0000 3.68252611 3.496711 -14.68 -14.68 0.00237751 -8870.9 12.80 10.41 0.00800000 33059.8 0.88954692 60.00 32.22 27.78 0.000 101691.05 -27.60 0.00034190 -27.60 2.53819000 72.5879 19.53 0.00776786 19.81 0.00772998 47.0566 35041.96 0.00 83549.98 83549.98 3.68252611 2.80 -0.60 0.00237751 8771.9 25.28 11.04 0.00237751 31460.2
VAV_MID WITH REHEAT COOLING COIL Coil:Cooling:Water AirLoop AirLoopHVAC VAV_MID WITH REHEAT CORE_MID; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_4; Coincident CoolingDesignCapacity N/A Yes Yes Yes No 1817578.773 -999.000 107.831862 0.07732400 -999.000 -999.0000 1.00000 1.00000 1017.9951 1004.8586 1.0531 VAV_MID WITH REHEAT FAN Fan:VariableVolume 107.831862 113.56203407   4197.9300 999.8980 98.93948206 12.27 6.67 5.60 2325909.71 78.1449 78.144855 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 15:20:00 Sensible 1817578.77 1799813.19 1.0000 113.56203407 107.831862 26.21 14.59 0.00707663 44383.6 10.68 8.51 0.00700000 28378.4 77.31611484 6.67 12.27 5.60 244950.128 1572628.65 33.40 0.00630683 16.37 25.38195000 23.5385 24.00 0.00731387 24.00 0.00731387 34.5006 1293342.28 0.00 2049140.46 2021722.57 113.56203407 26.21 15.94 0.00707663 44383.6 8.73 8.71 0.00698071 26339.3
VAV_MID WITH REHEAT HEATING COIL Coil:Heating:Water AirLoop AirLoopHVAC VAV_MID WITH REHEAT CORE_MID; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_4; Coincident HeatingDesignCapacity N/A Yes Yes Yes No 1044136.002 1044136.002 32.349559 0.00913456 15812.226 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.0531 VAV_MID WITH REHEAT FAN Fan:VariableVolume 107.831862 113.56203407   4197.9300 999.8980 30.11608457 54.44 82.22 27.78 3512092.47 29.7297 30.328064 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 05:30:00 unknown unknown GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 1044136.00 1044136.00 1.0000 34.06861022 32.349559 -17.70 -17.70 0.00190076 -13094.4 12.80 10.41 0.00800000 33059.8 9.13362542 60.00 32.22 27.78 0.000 1044136.00 -27.60 0.00034190 -27.60 25.38195000 78.4615 18.36 0.00757945 17.87 0.00757052 52.0491 383297.13 0.00 832607.55 832607.55 34.06861022 2.80 -1.34 0.00190076 7577.1 27.04 11.29 0.00190076 32016.3
VAV_TOP WITH REHEAT COOLING COIL Coil:Cooling:Water AirLoop AirLoopHVAC VAV_TOP WITH REHEAT CORE_TOP; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_4; Coincident CoolingDesignCapacity N/A Yes Yes Yes No 203672.512 -999.000 12.300790 0.00866470 -999.000 -999.0000 1.00000 1.00000 1017.9880 1004.8586 1.0531 VAV_TOP WITH REHEAT FAN Fan:VariableVolume 12.300790 12.95445223   4197.9300 999.8980 98.93948206 12.27 6.67 5.60 2325909.71 8.7567 8.756682 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 15:30:00 Sensible 203672.51 201753.67 1.0000 12.95445223 12.300790 25.95 14.49 0.00707283 44100.6 10.68 8.51 0.00700000 28378.4 8.66381562 6.67 12.27 5.60 27942.391 175730.12 33.40 0.00630683 16.37 2.53819000 20.6344 24.00 0.00727281 24.00 0.00727281 34.3091 147175.04 0.00 230005.32 227057.86 12.95445223 25.95 15.84 0.00707283 44100.6 8.73 8.71 0.00698244 26345.7
VAV_TOP WITH REHEAT HEATING COIL Coil:Heating:Water AirLoop AirLoopHVAC VAV_TOP WITH REHEAT CORE_TOP; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_4; Coincident HeatingDesignCapacity N/A Yes Yes Yes No 102308.455 102308.455 3.690237 0.00089504 1597.676 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.0531 VAV_TOP WITH REHEAT FAN Fan:VariableVolume 12.300790 12.95445223   4197.9300 999.8980 30.11608457 54.44 82.22 27.78 3512092.47 2.9130 2.971660 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 01:50:00 unknown unknown GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 102308.46 102308.46 1.0000 3.88633567 3.690237 -13.40 -13.40 0.00257360 -7090.4 12.80 10.41 0.00800000 33059.8 0.89494769 60.00 32.22 27.78 0.000 102308.46 -27.60 0.00034190 -27.60 2.53819000 68.7812 17.89 0.00749047 15.98 0.00758254 58.7469 38237.25 0.00 85150.87 85150.87 3.88633567 2.80 -0.30 0.00257360 9263.4 24.50 10.92 0.00257360 31173.7
CAV_BAS COOLING COIL Coil:Cooling:Water AirLoop AirLoopHVAC CAV_BAS BASEMENT Coincident CoolingDesignCapacity N/A Yes Yes Yes No 110073.141 -999.000 6.819106 0.00468277 -999.000 -999.0000 1.00000 1.00000 1018.2888 1004.8586 1.0531 CAV_BAS FAN Fan:ConstantVolume 6.819106 7.18147197   4197.9300 999.8980 98.93948206 12.27 6.67 5.60 2325909.71 4.7325 4.732477 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 13:00:00 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 13:00:00 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 Sensible 110073.14 106760.32 1.0000 7.18147197 6.819106 25.70 14.54 0.00723461 44263.5 11.23 8.74 0.00700000 28936.1 4.68228819 6.67 12.27 5.60 11488.247 98584.89 32.60 0.00630558 16.10 1.20015641 17.5999 24.00 0.00746371 24.00 0.00746371 35.1995 72830.29 0.00 124296.80 122031.40 7.18147197 25.70 15.90 0.00723461 44263.5 9.01 8.98 0.00710932 26955.5
CAV_BAS HEATING COIL Coil:Heating:Water AirLoop AirLoopHVAC CAV_BAS BASEMENT Coincident HeatingDesignCapacity N/A Yes Yes Yes No 323708.581 323708.581 6.819106 0.00283194 6941.245 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.0531 CAV_BAS FAN Fan:ConstantVolume 6.819106 7.18147197   4197.9300 999.8980 30.11608457 54.44 82.22 27.78 3512092.47 9.2170 9.402467 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 00:10:00 unknown unknown GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 00:10:00 Sensible 323708.58 323708.58 1.0000 7.18147197 6.819106 -4.86 -9.35 0.00034190 -4029.1 40.00 19.63 0.00800000 60796.0 2.83165499 60.00 32.22 27.78 0.000 323708.58 -27.60 0.00034190 -27.60 1.20015641 17.5999 0.00 0.00034190 22.86 0.00034190 1.7470 0.00 0.00 258881.68 258881.68 7.18147197 12.80 2.46 0.00034190 13725.2 48.65 17.96 0.00034190 49773.7
AIRLOOP DATACENTER BASEMENT COOLING COIL COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoop AirLoopHVAC AIRLOOP DATACENTER BASEMENT DATACENTER_BASEMENT_ZN_6 Coincident CoolingDesignCapacity N/A Yes No unknown No 466437.893 262502.939 24.538896 0.01142303 -999.000 -999.0000 -999.00000 -999.00000 1017.9118 1004.8586 1.0531 unknown unknown -999.0 -999.0   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 07:10:00 Sensible 405303.45 403832.34 0.8689 -999.0 -999.0 28.68 15.39 0.00703181 46778.9 12.80 9.41 0.00700000 30535.1 -999.0 -999.00 -999.00 -999.00 0.000 405303.45 33.40 0.00630683 16.37 0.33839277 -999.0000 27.00 0.00704196 27.00 0.00704196 27.8114 373034.82 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
AIRLOOP DATACENTER BOT COOLING COIL COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoop AirLoopHVAC AIRLOOP DATACENTER BOT DATACENTER_BOT_ZN_6 Coincident CoolingDesignCapacity N/A Yes No unknown No 10807.087 6147.885 0.585375 0.00026466 -999.000 -999.0000 -999.00000 -999.00000 1017.9641 1004.8586 1.0531 unknown unknown -999.0 -999.0   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 19:30:00 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 19:30:00 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 19:30:00 Sensible 9339.78 9274.26 0.8642 -999.0 -999.0 28.06 15.21 0.00705998 46221.7 12.80 9.41 0.00700000 30535.1 -999.0 -999.00 -999.00 -999.00 0.000 9339.78 26.28 0.00629588 13.94 0.01563234 -999.0000 27.00 0.00708094 27.00 0.00708094 27.9616 8909.34 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
AIRLOOP DATACENTER MID COOLING COIL COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoop AirLoopHVAC AIRLOOP DATACENTER MID DATACENTER_MID_ZN_6 Coincident CoolingDesignCapacity N/A Yes No unknown No 103961.649 59130.970 5.629668 0.00254601 -999.000 -999.0000 -999.00000 -999.00000 1017.9683 1004.8586 1.0531 unknown unknown -999.0 -999.0   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 19:30:00 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 19:30:00 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 19:30:00 Sensible 89850.72 89196.79 0.8643 -999.0 -999.0 28.06 15.21 0.00706223 46226.7 12.80 9.41 0.00700000 30535.1 -999.0 -999.00 -999.00 -999.00 0.000 89850.72 26.28 0.00629588 13.94 0.15632344 -999.0000 27.00 0.00708412 27.00 0.00708412 27.9741 85682.56 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
AIRLOOP DATACENTER TOP COOLING COIL COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoop AirLoopHVAC AIRLOOP DATACENTER TOP DATACENTER_TOP_ZN_6 Coincident CoolingDesignCapacity N/A Yes No unknown No 10570.015 6012.389 0.572441 0.00025886 -999.000 -999.0000 -999.00000 -999.00000 1017.9667 1004.8586 1.0531 unknown unknown -999.0 -999.0   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 19:30:00 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 19:30:00 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 19:30:00 Sensible 9135.16 9069.63 0.8643 -999.0 -999.0 28.06 15.21 0.00706134 46224.7 12.80 9.41 0.00700000 30535.1 -999.0 -999.00 -999.00 -999.00 0.000 9135.16 26.28 0.00629588 13.94 0.01563234 -999.0000 27.00 0.00708283 27.00 0.00708283 27.9690 8712.47 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
AIRLOOP DATACENTER BASEMENT HEATING COIL COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoop AirLoopHVAC AIRLOOP DATACENTER BASEMENT DATACENTER_BASEMENT_ZN_6 Coincident HeatingDesignCapacity N/A Yes No unknown No 466437.893 466437.893 24.538896 0.01142303 -999.000 -999.0000 -999.00000 -999.00000 1019.7116 1004.8586 1.0531 unknown unknown -999.0 -999.0   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 00:10:00 unknown unknown GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 00:10:00 Sensible 466437.89 466437.89 1.0000 25.84289049 24.538896 -27.60 -27.60 0.00034190 -26896.1 40.00 19.63 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 466437.89 -27.60 0.00034190 -27.60 0.33839277 1.3790 0.00 0.00700000 27.00 0.00700000 27.6430 0.00 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
AIRLOOP DATACENTER BOT HEATING COIL COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoop AirLoopHVAC AIRLOOP DATACENTER BOT DATACENTER_BOT_ZN_6 Coincident HeatingDesignCapacity N/A Yes No unknown No 10807.087 10807.087 0.585375 0.00026466 -999.000 -999.0000 -999.00000 -999.00000 1019.7116 1004.8586 1.0531 unknown unknown -999.0 -999.0   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 00:10:00 unknown unknown GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 00:10:00 Sensible 10807.09 10807.09 1.0000 0.61648127 0.585375 -27.60 -27.60 0.00034190 -26896.1 40.00 19.63 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 10807.09 -27.60 0.00034190 -27.60 0.01563234 2.6705 0.00 0.00098395 24.93 0.00098395 4.4353 0.00 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
AIRLOOP DATACENTER MID HEATING COIL COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoop AirLoopHVAC AIRLOOP DATACENTER MID DATACENTER_MID_ZN_6 Coincident HeatingDesignCapacity N/A Yes No unknown No 103961.649 103961.649 5.629668 0.00254601 -999.000 -999.0000 -999.00000 -999.00000 1019.7116 1004.8586 1.0531 unknown unknown -999.0 -999.0   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 00:10:00 unknown unknown GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 00:10:00 Sensible 103961.65 103961.65 1.0000 5.92882784 5.629668 -27.60 -27.60 0.00034190 -26896.1 40.00 19.63 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 103961.65 -27.60 0.00034190 -27.60 0.15632344 2.7768 0.00 0.00098397 23.40 0.00098397 4.8597 0.00 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
AIRLOOP DATACENTER TOP HEATING COIL COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoop AirLoopHVAC AIRLOOP DATACENTER TOP DATACENTER_TOP_ZN_6 Coincident HeatingDesignCapacity N/A Yes No unknown No 10570.015 10570.015 0.572441 0.00025886 -999.000 -999.0000 -999.00000 -999.00000 1019.7116 1004.8586 1.0531 unknown unknown -999.0 -999.0   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 00:10:00 unknown unknown GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 00:10:00 Sensible 10570.02 10570.02 1.0000 0.60285998 0.572441 -27.60 -27.60 0.00034190 -26896.1 40.00 19.63 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 10570.02 -27.60 0.00034190 -27.60 0.01563234 2.7308 0.00 0.00098340 21.93 0.00098340 5.3102 0.00 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL Coil:Heating:Electric AirLoop AirLoopHVAC AIRLOOP DATACENTER BASEMENT DATACENTER_BASEMENT_ZN_6 Coincident HeatingDesignCapacity N/A Yes No unknown No 24207.992 24207.992 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.0531 AIRLOOP DATACENTER BASEMENT SUPPLY FAN Fan:OnOff 24.538896 25.84289049   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 00:10:00 unknown unknown GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 00:10:00 Sensible 24207.99 24207.99 1.0000 25.84289049 24.538896 -0.38 -0.38 0.00690818 16889.6 40.00 19.63 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 24207.99 -27.60 0.00034190 -27.60 0.33839277 1.3790 0.00 0.00700000 27.00 0.00700000 27.6430 0.00 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
AIRLOOP DATACENTER BOT_SUPPHEATCOIL Coil:Heating:Electric AirLoop AirLoopHVAC AIRLOOP DATACENTER BOT DATACENTER_BOT_ZN_6 Coincident HeatingDesignCapacity N/A Yes No unknown No 1118.309 1118.309 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.0531 AIRLOOP DATACENTER BOT SUPPLY FAN Fan:OnOff 0.585375 0.61648127   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 00:10:00 unknown unknown GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 00:10:00 Sensible 1118.31 1118.31 1.0000 0.61648127 0.585375 -0.74 -5.59 0.00096681 1676.0 40.00 19.63 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 1118.31 -27.60 0.00034190 -27.60 0.01563234 2.6705 0.00 0.00098395 24.93 0.00098395 4.4353 0.00 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
AIRLOOP DATACENTER MID_SUPPHEATCOIL Coil:Heating:Electric AirLoop AirLoopHVAC AIRLOOP DATACENTER MID DATACENTER_MID_ZN_6 Coincident HeatingDesignCapacity N/A Yes No unknown No 11183.090 11183.090 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.0531 AIRLOOP DATACENTER MID SUPPLY FAN Fan:OnOff 5.629668 5.92882784   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 00:10:00 unknown unknown GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 00:10:00 Sensible 11183.09 11183.09 1.0000 5.92882784 5.629668 -0.77 -5.61 0.00096614 1644.8 40.00 19.63 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 11183.09 -27.60 0.00034190 -27.60 0.15632344 2.7768 0.00 0.00098397 23.40 0.00098397 4.8597 0.00 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
AIRLOOP DATACENTER TOP_SUPPHEATCOIL Coil:Heating:Electric AirLoop AirLoopHVAC AIRLOOP DATACENTER TOP DATACENTER_TOP_ZN_6 Coincident HeatingDesignCapacity N/A Yes No unknown No 1118.309 1118.309 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.0531 AIRLOOP DATACENTER TOP SUPPLY FAN Fan:OnOff 0.572441 0.60285998   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 00:10:00 unknown unknown GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 00:10:00 Sensible 1118.31 1118.31 1.0000 0.60285998 0.572441 -0.75 -5.60 0.00096588 1656.9 40.00 19.63 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 1118.31 -27.60 0.00034190 -27.60 0.01563234 2.7308 0.00 0.00098340 21.93 0.00098340 5.3102 0.00 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0



Table of Contents

Report: System Summary

For: Entire Facility

Timestamp: 2023-10-16 08:43:39

Economizer

High Limit Shutoff Control Minimum Outdoor Air [m3/s] Maximum Outdoor Air [m3/s] Return Air Temp Limit Return Air Enthalpy Limit Outdoor Air Temperature Limit [C] Outdoor Air Enthalpy Limit [C]
VAV_BOT WITH REHEAT_OA_CONTROLLER DifferentialDryBulb 0.00 11.66 -      
VAV_MID WITH REHEAT_OA_CONTROLLER DifferentialDryBulb 0.00 107.83 -      
VAV_TOP WITH REHEAT_OA_CONTROLLER DifferentialDryBulb 0.00 12.30 -      
CAV_BAS_OA_CONTROLLER DifferentialDryBulb 1.20 6.82 -      
AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER DifferentialDryBulb 0.34 24.54 -      


Demand Controlled Ventilation using Controller:MechanicalVentilation

Controller:MechanicalVentilation Name Outdoor Air Per Person [m3/s-person] Outdoor Air Per Area [m3/s-m2] Outdoor Air Per Zone [m3/s] Outdoor Air ACH [ach] Outdoor Air Method Outdoor Air Schedule Name Air Distribution Effectiveness in Cooling Mode Air Distribution Effectiveness in Heating Mode Air Distribution Effectiveness Schedule Name
CORE_BOTTOM VAV_BOT WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
CORE_MID VAV_MID WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
CORE_TOP VAV_TOP WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_BOT_ZN_3 VAV_BOT WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_BOT_ZN_2 VAV_BOT WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_BOT_ZN_1 VAV_BOT WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_BOT_ZN_4 VAV_BOT WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_MID_ZN_3 VAV_MID WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_MID_ZN_2 VAV_MID WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_MID_ZN_1 VAV_MID WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_MID_ZN_4 VAV_MID WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_TOP_ZN_3 VAV_TOP WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_TOP_ZN_2 VAV_TOP WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_TOP_ZN_1 VAV_TOP WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_TOP_ZN_4 VAV_TOP WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  


Time Not Comfortable Based on Simple ASHRAE 55-2004

Winter Clothes [hr] Summer Clothes [hr] Summer or Winter Clothes [hr]
BASEMENT 1603.83 1464.67 35.67
CORE_BOTTOM 1428.67 1624.00 24.17
CORE_MID 1043.00 3492.50 279.50
CORE_TOP 1811.17 4127.83 1099.67
PERIMETER_BOT_ZN_3 1854.17 3872.67 824.67
PERIMETER_BOT_ZN_2 2307.67 3729.17 967.50
PERIMETER_BOT_ZN_1 2523.83 3195.67 851.00
PERIMETER_BOT_ZN_4 2519.17 2904.33 574.00
PERIMETER_MID_ZN_3 2897.33 4451.83 2186.67
PERIMETER_MID_ZN_2 2678.17 3625.83 1774.00
PERIMETER_MID_ZN_1 2891.67 3611.00 1426.50
PERIMETER_MID_ZN_4 2977.50 4240.67 1842.17
PERIMETER_TOP_ZN_3 3418.17 4632.17 2736.00
PERIMETER_TOP_ZN_2 3541.17 4262.67 2409.00
PERIMETER_TOP_ZN_1 3213.83 3890.83 1907.67
PERIMETER_TOP_ZN_4 3373.67 4433.33 2330.50
DATACENTER_BOT_ZN_6 5801.83 564.83 563.50
DATACENTER_MID_ZN_6 5201.17 291.50 137.33
DATACENTER_TOP_ZN_6 4561.83 649.00 239.33
DATACENTER_BASEMENT_ZN_6 5943.00 5705.33 5705.33
GROUNDFLOOR_PLENUM 0.00 0.00 0.00
MIDFLOOR_PLENUM 0.00 0.00 0.00
TOPFLOOR_PLENUM 0.00 0.00 0.00
Facility 5943.00 5943.00 5938.00
Aggregated over the RunPeriods for Weather

Time Setpoint Not Met

During Heating [hr] During Cooling [hr] During Occupied Heating [hr] During Occupied Cooling [hr]
BASEMENT 0.00 45.67 0.00 2.83
CORE_BOTTOM 0.00 2.17 0.00 0.00
CORE_MID 0.33 0.00 0.00 0.00
CORE_TOP 17.17 0.00 2.67 0.00
PERIMETER_BOT_ZN_3 9.67 7.17 1.00 5.17
PERIMETER_BOT_ZN_2 10.67 27.33 0.50 27.00
PERIMETER_BOT_ZN_1 12.00 45.83 0.67 43.50
PERIMETER_BOT_ZN_4 3.83 65.50 0.00 29.67
PERIMETER_MID_ZN_3 147.17 4.67 46.17 3.67
PERIMETER_MID_ZN_2 91.83 27.33 12.17 26.67
PERIMETER_MID_ZN_1 67.50 40.50 7.17 38.00
PERIMETER_MID_ZN_4 72.67 31.83 9.83 14.67
PERIMETER_TOP_ZN_3 332.33 7.17 115.33 5.00
PERIMETER_TOP_ZN_2 198.67 27.67 36.83 25.50
PERIMETER_TOP_ZN_1 158.00 31.83 22.67 28.33
PERIMETER_TOP_ZN_4 160.33 30.83 29.83 14.33
DATACENTER_BOT_ZN_6 0.00 9.00 0.00 4.67
DATACENTER_MID_ZN_6 0.00 5.00 0.00 2.67
DATACENTER_TOP_ZN_6 0.00 6.50 0.00 2.83
DATACENTER_BASEMENT_ZN_6 0.00 112.50 0.00 105.50
GROUNDFLOOR_PLENUM 0.00 0.00 0.00 0.00
MIDFLOOR_PLENUM 0.00 0.00 0.00 0.00
TOPFLOOR_PLENUM 0.00 0.00 0.00 0.00
Facility 407.33 344.50 133.17 247.83
Aggregated over the RunPeriods for Weather


Table of Contents

Report: Outdoor Air Summary

For: Entire Facility

Timestamp: 2023-10-16 08:43:39

Average Outdoor Air During Occupied Hours

Average Number of Occupants Nominal Number of Occupants Zone Volume [m3] Mechanical Ventilation [ach] Infiltration [ach] AFN Infiltration [ach] Simple Ventilation [ach]
BASEMENT 60.99 149.60 6779.02 1.395 0.000 0.000 0.000
CORE_BOTTOM 54.77 134.35 6849.35 1.024 0.000 0.000 0.000
CORE_MID 54.77 134.35 6849.35 0.760 0.000 0.000 0.000
CORE_TOP 54.77 134.35 6849.35 0.707 0.000 0.000 0.000
PERIMETER_BOT_ZN_3 6.88 16.87 860.00 0.894 0.059 0.000 0.000
PERIMETER_BOT_ZN_2 4.43 10.87 554.22 1.700 0.061 0.000 0.000
PERIMETER_BOT_ZN_1 6.88 16.87 860.02 1.704 0.059 0.000 0.000
PERIMETER_BOT_ZN_4 4.43 10.87 554.22 2.123 0.061 0.000 0.000
PERIMETER_MID_ZN_3 6.88 16.87 860.00 0.731 0.137 0.000 0.000
PERIMETER_MID_ZN_2 3.86 10.87 554.22 1.538 0.151 0.000 0.000
PERIMETER_MID_ZN_1 6.88 16.87 860.02 1.614 0.138 0.000 0.000
PERIMETER_MID_ZN_4 4.43 10.87 554.22 1.635 0.142 0.000 0.000
PERIMETER_TOP_ZN_3 6.88 16.87 860.00 0.757 0.170 0.000 0.000
PERIMETER_TOP_ZN_2 4.43 10.87 554.22 1.646 0.176 0.000 0.000
PERIMETER_TOP_ZN_1 6.88 16.87 860.02 1.591 0.171 0.000 0.000
PERIMETER_TOP_ZN_4 4.43 10.87 554.22 1.668 0.176 0.000 0.000
DATACENTER_BOT_ZN_6 0.79 1.95 99.34 0.426 0.000 0.000 0.000
DATACENTER_MID_ZN_6 0.79 1.95 99.34 0.426 0.000 0.000 0.000
DATACENTER_TOP_ZN_6 0.79 1.95 99.34 0.426 0.000 0.000 0.000
DATACENTER_BASEMENT_ZN_6 17.20 42.18 1911.37 26.939 0.000 0.000 0.000
Values shown for a single zone without multipliers

Minimum Outdoor Air During Occupied Hours

Average Number of Occupants Nominal Number of Occupants Zone Volume [m3] Mechanical Ventilation [ach] Infiltration [ach] AFN Infiltration [ach] Simple Ventilation [ach]
BASEMENT 60.99 149.60 6779.02 0.000 0.000 0.000 0.000
CORE_BOTTOM 54.77 134.35 6849.35 0.000 0.000 0.000 0.000
CORE_MID 54.77 134.35 6849.35 0.000 0.000 0.000 0.000
CORE_TOP 54.77 134.35 6849.35 0.000 0.000 0.000 0.000
PERIMETER_BOT_ZN_3 6.88 16.87 860.00 0.000 0.000 0.000 0.000
PERIMETER_BOT_ZN_2 4.43 10.87 554.22 0.000 0.000 0.000 0.000
PERIMETER_BOT_ZN_1 6.88 16.87 860.02 0.000 0.000 0.000 0.000
PERIMETER_BOT_ZN_4 4.43 10.87 554.22 0.000 0.000 0.000 0.000
PERIMETER_MID_ZN_3 6.88 16.87 860.00 0.000 0.000 0.000 0.000
PERIMETER_MID_ZN_2 3.86 10.87 554.22 0.000 0.000 0.000 0.000
PERIMETER_MID_ZN_1 6.88 16.87 860.02 0.000 0.000 0.000 0.000
PERIMETER_MID_ZN_4 4.43 10.87 554.22 0.000 0.000 0.000 0.000
PERIMETER_TOP_ZN_3 6.88 16.87 860.00 0.000 0.000 0.000 0.000
PERIMETER_TOP_ZN_2 4.43 10.87 554.22 0.000 0.000 0.000 0.000
PERIMETER_TOP_ZN_1 6.88 16.87 860.02 0.000 0.000 0.000 0.000
PERIMETER_TOP_ZN_4 4.43 10.87 554.22 0.000 0.000 0.000 0.000
DATACENTER_BOT_ZN_6 0.79 1.95 99.34 0.000 0.000 0.000 0.000
DATACENTER_MID_ZN_6 0.79 1.95 99.34 0.000 0.000 0.000 0.000
DATACENTER_TOP_ZN_6 0.79 1.95 99.34 0.000 0.000 0.000 0.000
DATACENTER_BASEMENT_ZN_6 17.20 42.18 1911.37 0.000 0.000 0.000 0.000
Values shown for a single zone without multipliers


Table of Contents

Report: Outdoor Air Details

For: Entire Facility

Timestamp: 2023-10-16 08:43:39

Mechanical Ventilation Parameters by Zone

AirLoop Name Average Number of Occupants Nominal Number of Occupants Zone Volume [m3] Zone Area [m2] Design Zone Outdoor Airflow - Voz [m3/s] Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s]
BASEMENT CAV_BAS 60.99 149.60 6779.02 2779.43 1.2002 1.200
CORE_BOTTOM VAV_BOT WITH REHEAT 54.77 134.35 6849.35 2496.12 0.0000 1.078
CORE_MID VAV_MID WITH REHEAT 54.77 134.35 6849.35 2496.12 0.0000 10.778
CORE_TOP VAV_TOP WITH REHEAT 54.77 134.35 6849.35 2496.12 0.0000 1.078
PERIMETER_BOT_ZN_3 VAV_BOT WITH REHEAT 6.88 16.87 860.00 313.41 0.0000 0.135
PERIMETER_BOT_ZN_2 VAV_BOT WITH REHEAT 4.43 10.87 554.22 201.98 0.0000 0.087
PERIMETER_BOT_ZN_1 VAV_BOT WITH REHEAT 6.88 16.87 860.02 313.42 0.0000 0.135
PERIMETER_BOT_ZN_4 VAV_BOT WITH REHEAT 4.43 10.87 554.22 201.98 0.0000 0.087
PERIMETER_MID_ZN_3 VAV_MID WITH REHEAT 6.88 16.87 860.00 313.41 0.0000 1.353
PERIMETER_MID_ZN_2 VAV_MID WITH REHEAT 3.86 10.87 554.22 201.98 0.0000 0.872
PERIMETER_MID_ZN_1 VAV_MID WITH REHEAT 6.88 16.87 860.02 313.42 0.0000 1.353
PERIMETER_MID_ZN_4 VAV_MID WITH REHEAT 4.43 10.87 554.22 201.98 0.0000 0.872
PERIMETER_TOP_ZN_3 VAV_TOP WITH REHEAT 6.88 16.87 860.00 313.41 0.0000 0.135
PERIMETER_TOP_ZN_2 VAV_TOP WITH REHEAT 4.43 10.87 554.22 201.98 0.0000 0.087
PERIMETER_TOP_ZN_1 VAV_TOP WITH REHEAT 6.88 16.87 860.02 313.42 0.0000 0.135
PERIMETER_TOP_ZN_4 VAV_TOP WITH REHEAT 4.43 10.87 554.22 201.98 0.0000 0.087
DATACENTER_BOT_ZN_6 AIRLOOP DATACENTER BOT 0.79 1.95 99.34 36.20 0.0156 0.016
DATACENTER_MID_ZN_6 AIRLOOP DATACENTER MID 0.79 1.95 99.34 36.20 0.1563 0.156
DATACENTER_TOP_ZN_6 AIRLOOP DATACENTER TOP 0.79 1.95 99.34 36.20 0.0156 0.016
DATACENTER_BASEMENT_ZN_6 AIRLOOP DATACENTER BASEMENT 17.20 42.18 1911.37 783.68 0.3384 0.338
Total Facility   1010.73 2493.19 126016.35 46320.38 1.7261 158.471


Total Outdoor Air by Zone

Mechanical Ventilation [m3] Natural Ventilation [m3] Total Ventilation [m3] Infiltration [m3] Total Ventilation and Infiltration [m3] Dynamic Target Ventilation - Voz-dyn [m3] Time Below Voz-dyn [hr] Time At Voz-dyn [hr] Time Above Voz-dyn [hr] Time Above Zero When Unoccupied [hr]
BASEMENT 57494912.73 0.00 57494912.73 0.00 57494912.73 37848132.68 3959.99 896.82 3903.19 332.29
CORE_BOTTOM 43160571.91 0.00 43160571.91 0.00 43160571.91 33990283.35 4681.30 48.68 4030.02 399.69
CORE_MID 0.31E+09 0.00 0.31E+09 0.00 0.31E+09 0.34E+09 6024.66 36.50 2698.84 414.77
CORE_TOP 29176249.77 0.00 29176249.77 0.00 29176249.77 33990283.35 6440.05 31.74 2288.21 445.71
PERIMETER_BOT_ZN_3 4752044.62 0.00 4752044.62 591585.02 5343629.63 4267819.30 5540.33 60.41 3159.26 399.69
PERIMETER_BOT_ZN_2 5838426.77 0.00 5838426.77 394389.74 6232816.52 2750345.05 3551.63 3.34 5205.03 399.69
PERIMETER_BOT_ZN_1 8970240.15 0.00 8970240.15 591585.02 9561825.16 4267912.63 3593.90 6.57 5159.53 399.69
PERIMETER_BOT_ZN_4 7320692.06 0.00 7320692.06 394389.74 7715081.80 2750345.05 3527.16 0.00 5232.84 399.69
PERIMETER_MID_ZN_3 38220727.13 0.00 38220727.13 1387434.57 39608161.70 42678193.03 5776.38 60.56 2923.06 414.77
PERIMETER_MID_ZN_2 56423681.78 0.00 56423681.78 924955.75 57348637.53 27503450.52 3836.69 4.59 4918.72 1323.77
PERIMETER_MID_ZN_1 83367049.12 0.00 83367049.12 1387434.57 84754483.69 42679126.28 3920.47 8.38 4831.15 414.77
PERIMETER_MID_ZN_4 55335610.26 0.00 55335610.26 924955.75 56260566.01 27503450.52 3826.60 5.08 4928.32 414.77
PERIMETER_TOP_ZN_3 3938203.88 0.00 3938203.88 1722650.34 5660854.22 4267819.30 5583.42 62.17 3114.41 445.71
PERIMETER_TOP_ZN_2 5486196.59 0.00 5486196.59 1148432.78 6634629.37 2750345.05 3996.72 4.80 4758.48 445.71
PERIMETER_TOP_ZN_1 8189431.26 0.00 8189431.26 1722650.34 9912081.60 4267912.63 4047.97 3.03 4709.00 445.71
PERIMETER_TOP_ZN_4 5607707.39 0.00 5607707.39 1148432.78 6756140.16 2750345.05 3967.34 8.09 4784.57 445.71
DATACENTER_BOT_ZN_6 244296.02 0.00 244296.02 0.00 244296.02 492981.60 4419.00 4341.00 0.00 0.00
DATACENTER_MID_ZN_6 2442960.18 0.00 2442960.18 0.00 2442960.18 4929815.99 4419.00 4341.00 0.00 0.00
DATACENTER_TOP_ZN_6 244296.02 0.00 244296.02 0.00 244296.02 492981.60 4419.00 4341.00 0.00 0.00
DATACENTER_BASEMENT_ZN_6 0.42E+09 0.00 0.42E+09 0.00 0.42E+09 10671554.30 51.83 192.83 8515.33 2801.17
Total Facility 0.61E+10 0.00 0.61E+10 53961922.12 0.62E+10 0.50E+10 6835.83 4403.28 8708.33 3710.17


Average Outdoor Air During Occupancy by Zone - Flow Rates

Mechanical Ventilation [m3/s] Natural Ventilation [m3/s] Total Ventilation [m3/s] Infiltration [m3/s] Total Ventilation and Infiltration [m3/s] Dynamic Target Ventilation - Voz-dyn [m3/s] Time Below Voz-dyn [hr] Time At Voz-dyn [hr] Time Above Voz-dyn [hr]
BASEMENT 2.5773 0.0000 2.5773 0.0000 2.5773 1.2002 1328.13 893.03 3721.84
CORE_BOTTOM 1.9121 0.0000 1.9121 0.0000 1.9121 1.0778 2134.76 46.43 3761.81
CORE_MID 14.1905 0.0000 14.1905 0.0000 14.1905 10.7782 3305.73 36.19 2601.09
CORE_TOP 1.3230 0.0000 1.3230 0.0000 1.3230 1.0778 3703.76 31.68 2207.56
PERIMETER_BOT_ZN_3 0.2099 0.0000 0.2099 0.0139 0.2237 0.1353 2988.61 57.96 2896.43
PERIMETER_BOT_ZN_2 0.2574 0.0000 0.2574 0.0092 0.2666 0.0872 1077.34 2.84 4862.82
PERIMETER_BOT_ZN_1 0.4000 0.0000 0.4000 0.0139 0.4139 0.1353 1107.76 4.93 4830.31
PERIMETER_BOT_ZN_4 0.3211 0.0000 0.3211 0.0092 0.3304 0.0872 1060.61 0.00 4882.39
PERIMETER_MID_ZN_3 1.7192 0.0000 1.7192 0.0325 1.7517 1.3533 3067.89 59.36 2815.75
PERIMETER_MID_ZN_2 2.3326 0.0000 2.3326 0.0230 2.3555 0.8721 1194.44 2.00 3837.55
PERIMETER_MID_ZN_1 3.7929 0.0000 3.7929 0.0325 3.8254 1.3533 1239.42 4.77 4698.81
PERIMETER_MID_ZN_4 2.4815 0.0000 2.4815 0.0217 2.5032 0.8721 1191.42 2.59 4748.99
PERIMETER_TOP_ZN_3 0.1783 0.0000 0.1783 0.0404 0.2187 0.1353 2854.49 61.35 3027.16
PERIMETER_TOP_ZN_2 0.2495 0.0000 0.2495 0.0269 0.2765 0.0872 1298.16 2.95 4641.89
PERIMETER_TOP_ZN_1 0.3740 0.0000 0.3740 0.0404 0.4144 0.1353 1329.73 2.10 4611.16
PERIMETER_TOP_ZN_4 0.2531 0.0000 0.2531 0.0269 0.2801 0.0872 1276.91 6.05 4660.04
DATACENTER_BOT_ZN_6 0.0114 0.0000 0.0114 0.0000 0.0114 0.0156 1602.00 4341.00 0.00
DATACENTER_MID_ZN_6 0.1142 0.0000 0.1142 0.0000 0.1142 0.1563 1602.00 4341.00 0.00
DATACENTER_TOP_ZN_6 0.0114 0.0000 0.0114 0.0000 0.0114 0.0156 1602.00 4341.00 0.00
DATACENTER_BASEMENT_ZN_6 13.8666 0.0000 13.8666 0.0000 13.8666 0.3384 36.00 192.83 5714.17
Total Facility 268.2529 0.0000 268.2529 1.2778 269.5307 158.4706 4018.83 4380.00 5907.17


Total Outdoor Air by AirLoop

Mechanical Ventilation [m3] Natural Ventilation [m3/s] Total Ventilation [m3/s] Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] Time Below Voz-sum-dyn [hr] Time At Voz-sum-dyn [hr] Time Above Voz-sum-dyn [hr] Time Above Zero When Unoccupied [hr]
VAV_BOT WITH REHEAT 77683824.34 0.00 77683824.34 48026705.38 3654.69 8.97 5096.34 399.69
VAV_MID WITH REHEAT 0.61E+09 0.00 0.61E+09 0.48E+09 4006.27 6.93 4746.80 414.77
VAV_TOP WITH REHEAT 58114575.87 0.00 58114575.87 48026705.38 4087.63 1.83 4670.54 445.37
CAV_BAS 63767815.09 0.00 63767815.09 37848132.68 3937.12 4.00 4818.88 332.29
AIRLOOP DATACENTER BASEMENT 0.47E+09 0.00 0.47E+09 10671554.30 51.83 0.00 8708.17 2801.17
AIRLOOP DATACENTER BOT 270949.60 0.00 270949.60 492981.60 4419.00 0.00 4341.00 0.00
AIRLOOP DATACENTER MID 2709495.95 0.00 2709495.95 4929815.99 4419.00 0.00 4341.00 0.00
AIRLOOP DATACENTER TOP 270949.60 0.00 270949.60 492981.60 4419.00 0.00 4341.00 0.00


Average Outdoor Air During Occupancy by AirLoop

Mechanical Ventilation [m3/s] Natural Ventilation [m3/s] Total Ventilation [m3/s] Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] Time Below Voz-sum-dyn [hr] Time At Voz-sum-dyn [hr] Time Above Voz-sum-dyn [hr]
VAV_BOT WITH REHEAT 3.4387 0.0000 3.4387 1.5229 1142.71 6.65 4793.64
VAV_MID WITH REHEAT 27.4331 0.0000 27.4331 15.2292 1298.37 5.58 4639.05
VAV_TOP WITH REHEAT 2.6374 0.0000 2.6374 1.5229 1356.92 0.92 4585.16
CAV_BAS 2.8584 0.0000 2.8584 1.2002 1318.90 1.57 4622.53
AIRLOOP DATACENTER BASEMENT 15.3795 0.0000 15.3795 0.3384 36.00 0.00 5907.00
AIRLOOP DATACENTER BOT 0.0127 0.0000 0.0127 0.0156 1602.00 0.00 4341.00
AIRLOOP DATACENTER MID 0.1266 0.0000 0.1266 0.1563 1602.00 0.00 4341.00
AIRLOOP DATACENTER TOP 0.0127 0.0000 0.0127 0.0156 1602.00 0.00 4341.00


Outdoor Air Controller Limiting Factors by AirLoop

No Limiting Factor [hr] Limits and Scheduled Limits [hr] Economizer [hr] Exhaust Flow [hr] Mixed Air Flow [hr] High Humidity [hr] Demand Controlled Ventilation [hr] Night Ventilation [hr] Demand Limiting [hr] Energy Management System [hr]
VAV_BOT WITH REHEAT 0.00 0.00 3917.15 0.00 0.00 0.00 1394.08 0.00 0.00 0.00
VAV_MID WITH REHEAT 0.00 0.00 3883.90 0.00 0.00 0.00 1409.14 0.00 0.00 0.00
VAV_TOP WITH REHEAT 0.00 0.00 3142.97 0.00 0.00 0.00 2162.22 0.00 0.00 0.00
CAV_BAS 0.00 885.42 4113.08 0.00 0.00 0.00 0.00 0.00 0.00 0.00
AIRLOOP DATACENTER BASEMENT 0.00 192.83 8515.33 0.00 0.00 0.00 0.00 0.00 0.00 0.00
AIRLOOP DATACENTER BOT 0.00 4341.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
AIRLOOP DATACENTER MID 0.00 4341.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
AIRLOOP DATACENTER TOP 0.00 4341.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Average Outdoor Air for Limiting Factors During Occupancy

No Limiting Factor [m3/s] Limits and Scheduled Limits [m3/s] Economizer [m3/s] Exhaust Flow [m3/s] Mixed Air Flow [m3/s] High Humidity [m3/s] Demand Controlled Ventilation [m3/s] Night Ventilation [m3/s] Demand Limiting [m3/s] Energy Management System [m3/s]
VAV_BOT WITH REHEAT 0.0000 0.0000 5.0401 0.0000 0.0000 0.0000 1.9442 0.0000 0.0000 0.0000
VAV_MID WITH REHEAT 0.0000 0.0000 39.2611 0.0000 0.0000 0.0000 19.0475 0.0000 0.0000 0.0000
VAV_TOP WITH REHEAT 0.0000 0.0000 4.3023 0.0000 0.0000 0.0000 1.8830 0.0000 0.0000 0.0000
CAV_BAS 0.0000 1.3317 4.1823 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
AIRLOOP DATACENTER BASEMENT 0.0000 0.3769 15.9832 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
AIRLOOP DATACENTER BOT 0.0000 0.0173 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
AIRLOOP DATACENTER MID 0.0000 0.1734 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
AIRLOOP DATACENTER TOP 0.0000 0.0173 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000



Table of Contents

Report: Object Count Summary

For: Entire Facility

Timestamp: 2023-10-16 08:43:39

Surfaces by Class

Total Outdoors
Wall 98 30
Floor 41 0
Roof 30 1
Internal Mass 16 0
Building Detached Shading 0 0
Fixed Detached Shading 0 0
Window 24 24
Door 12 12
Glass Door 0 0
Shading 0 0
Overhang 0 0
Fin 0 0
Tubular Daylighting Device Dome 0 0
Tubular Daylighting Device Diffuser 0 0


HVAC

Count
HVAC Air Loops 8
Conditioned Zones 23
Unconditioned Zones 0
Supply Plenums 0
Return Plenums 3


Input Fields

Count
IDF Objects 1395
Defaulted Fields 1182
Fields with Defaults 3867
Autosized Fields 332
Autosizable Fields 411
Autocalculated Fields 226
Autocalculatable Fields 473



Table of Contents

Report: Energy Meters

For: Entire Facility

Timestamp: 2023-10-16 08:43:39

Annual and Peak Values - Electricity

Electricity Annual Value [GJ] Electricity Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Electricity Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
Electricity:Facility 28638.04 343584.99 21-MAY-04:50 2225335.88 07-AUG-15:40
Electricity:Building 18609.81 225715.65 06-MAY-18:10 1164206.62 01-DEC-08:10
Electricity:Zone:BASEMENT 687.24 14732.47 01-JAN-00:10 36407.88 02-JAN-08:10
Electricity:SpaceType:GENERAL 18609.81 225715.65 06-MAY-18:10 1164206.62 01-DEC-08:10
InteriorLights:Electricity 3933.41 18459.50 01-JAN-10:30 385834.94 02-JAN-08:10
InteriorLights:Electricity:Zone:BASEMENT 262.84 1274.92 01-JAN-00:10 22950.34 02-JAN-08:10
InteriorLights:Electricity:SpaceType:GENERAL 3933.41 18459.50 01-JAN-10:30 385834.94 02-JAN-08:10
LightsWired:InteriorLights:Electricity 3933.41 18459.50 01-JAN-10:30 385834.94 02-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:BASEMENT 262.84 1274.92 01-JAN-00:10 22950.34 02-JAN-08:10
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL 3933.41 18459.50 01-JAN-10:30 385834.94 02-JAN-08:10
Electricity:Zone:CORE_BOTTOM 525.67 5598.20 01-JAN-00:10 37817.64 02-JAN-08:10
InteriorLights:Electricity:Zone:CORE_BOTTOM 236.05 1144.97 01-JAN-00:10 20611.01 02-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:CORE_BOTTOM 236.05 1144.97 01-JAN-00:10 20611.01 02-JAN-08:10
Electricity:Zone:CORE_MID 5256.66 55981.88 01-JAN-00:10 378175.77 02-JAN-08:10
InteriorLights:Electricity:Zone:CORE_MID 2360.53 11449.71 01-JAN-00:10 206110.14 02-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:CORE_MID 2360.53 11449.71 01-JAN-00:10 206110.14 02-JAN-08:10
Electricity:Zone:CORE_TOP 525.67 5598.19 01-JAN-00:10 37817.58 02-JAN-08:10
InteriorLights:Electricity:Zone:CORE_TOP 236.05 1144.97 01-JAN-00:10 20611.01 02-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:CORE_TOP 236.05 1144.97 01-JAN-00:10 20611.01 02-JAN-08:10
Electricity:Zone:PERIMETER_BOT_ZN_3 53.94 627.57 19-MAR-17:10 4748.47 02-JAN-08:10
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 17.57 68.40 01-JAN-10:30 2587.92 02-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 17.57 68.40 01-JAN-10:30 2587.92 02-JAN-08:10
Electricity:Zone:PERIMETER_BOT_ZN_2 34.60 404.43 26-MAR-17:10 3060.10 02-JAN-08:10
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 11.16 44.08 01-JAN-08:50 1667.75 02-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 11.16 44.08 01-JAN-08:50 1667.75 02-JAN-08:10
Electricity:Zone:PERIMETER_BOT_ZN_1 53.54 627.58 12-MAR-17:10 4748.56 02-JAN-08:10
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 17.17 68.40 01-JAN-08:50 2587.98 02-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 17.17 68.40 01-JAN-08:50 2587.98 02-JAN-08:10
Electricity:Zone:PERIMETER_BOT_ZN_4 34.63 404.43 12-MAR-17:10 3060.09 02-JAN-08:10
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 11.20 44.08 01-JAN-10:20 1667.75 02-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 11.20 44.08 01-JAN-10:20 1667.75 02-JAN-08:10
Electricity:Zone:PERIMETER_MID_ZN_3 539.00 6275.73 12-MAR-17:10 47484.70 02-JAN-08:10
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 175.35 684.02 01-JAN-10:20 25879.19 02-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 175.35 684.02 01-JAN-10:20 25879.19 02-JAN-08:10
Electricity:Zone:PERIMETER_MID_ZN_2 345.83 4044.32 26-MAR-17:10 30600.95 02-JAN-08:10
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 111.48 440.81 01-JAN-08:50 16677.53 02-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 111.48 440.81 01-JAN-08:50 16677.53 02-JAN-08:10
Electricity:Zone:PERIMETER_MID_ZN_1 535.20 6275.83 12-MAR-17:10 47485.60 02-JAN-08:10
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 171.54 684.04 01-JAN-08:50 25879.75 02-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 171.54 684.04 01-JAN-08:50 25879.75 02-JAN-08:10
Electricity:Zone:PERIMETER_MID_ZN_4 346.16 4044.30 12-MAR-17:10 30600.86 02-JAN-08:10
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 111.80 440.81 01-JAN-10:10 16677.53 02-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 111.80 440.81 01-JAN-10:10 16677.53 02-JAN-08:10
Electricity:Zone:PERIMETER_TOP_ZN_3 53.90 627.57 12-MAR-17:10 4748.47 02-JAN-08:10
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 17.53 68.40 01-JAN-10:20 2587.92 02-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 17.53 68.40 01-JAN-10:20 2587.92 02-JAN-08:10
Electricity:Zone:PERIMETER_TOP_ZN_2 34.58 404.43 26-MAR-17:10 3060.10 02-JAN-08:10
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 11.15 44.08 01-JAN-08:50 1667.75 02-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 11.15 44.08 01-JAN-08:50 1667.75 02-JAN-08:10
Electricity:Zone:PERIMETER_TOP_ZN_1 53.52 627.58 12-MAR-17:10 4748.56 02-JAN-08:10
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 17.15 68.40 01-JAN-08:50 2587.98 02-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 17.15 68.40 01-JAN-08:50 2587.98 02-JAN-08:10
Electricity:Zone:PERIMETER_TOP_ZN_4 34.62 404.43 12-MAR-17:10 3060.09 02-JAN-08:10
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 11.18 44.08 01-JAN-10:10 1667.75 02-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 11.18 44.08 01-JAN-10:10 1667.75 02-JAN-08:10
Electricity:Zone:DATACENTER_BASEMENT_ZN_6 7568.97 95267.60 01-JAN-00:10 386103.53 03-APR-07:10
InteriorLights:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 74.11 359.47 01-JAN-00:10 6471.01 02-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 74.11 359.47 01-JAN-00:10 6471.01 02-JAN-08:10
Electricity:Zone:DATACENTER_BOT_ZN_6 160.51 1980.76 01-JAN-00:10 8373.14 03-APR-07:10
InteriorLights:Electricity:Zone:DATACENTER_BOT_ZN_6 6.63 32.15 01-JAN-00:10 578.72 02-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_BOT_ZN_6 6.63 32.15 01-JAN-00:10 578.72 02-JAN-08:10
Electricity:Zone:DATACENTER_MID_ZN_6 1605.09 19807.58 01-JAN-00:10 83731.41 03-APR-07:10
InteriorLights:Electricity:Zone:DATACENTER_MID_ZN_6 66.28 321.53 01-JAN-00:10 5787.18 02-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_MID_ZN_6 66.28 321.53 01-JAN-00:10 5787.18 02-JAN-08:10
Electricity:Zone:DATACENTER_TOP_ZN_6 160.51 1980.76 01-JAN-00:10 8373.14 03-APR-07:10
InteriorLights:Electricity:Zone:DATACENTER_TOP_ZN_6 6.63 32.15 01-JAN-00:10 578.72 02-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_TOP_ZN_6 6.63 32.15 01-JAN-00:10 578.72 02-JAN-08:10
InteriorEquipment:Electricity 14676.40 207256.16 01-JAN-00:10 778371.69 03-APR-07:10
InteriorEquipment:Electricity:Zone:BASEMENT 424.40 13457.54 01-JAN-00:10 13457.54 01-JAN-00:10
InteriorEquipment:Electricity:SpaceType:GENERAL 14676.40 207256.16 01-JAN-00:10 778371.69 03-APR-07:10
MiscPlug:InteriorEquipment:Electricity 5334.97 88964.76 01-JAN-00:10 305206.10 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:BASEMENT 424.40 13457.54 01-JAN-00:10 13457.54 01-JAN-00:10
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL 5334.97 88964.76 01-JAN-00:10 305206.10 02-JAN-08:10
InteriorEquipment:Electricity:Zone:CORE_BOTTOM 289.61 4453.23 01-JAN-00:10 17206.63 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_BOTTOM 289.61 4453.23 01-JAN-00:10 17206.63 02-JAN-08:10
InteriorEquipment:Electricity:Zone:CORE_MID 2896.13 44532.17 01-JAN-00:10 172065.63 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_MID 2896.13 44532.17 01-JAN-00:10 172065.63 02-JAN-08:10
InteriorEquipment:Electricity:Zone:CORE_TOP 289.61 4453.22 01-JAN-00:10 17206.56 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_TOP 289.61 4453.22 01-JAN-00:10 17206.56 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 36.37 559.17 01-JAN-00:10 2160.55 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 36.37 559.17 01-JAN-00:10 2160.55 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 23.44 360.35 01-JAN-00:10 1392.34 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 23.44 360.35 01-JAN-00:10 1392.34 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 36.37 559.18 01-JAN-00:10 2160.58 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 36.37 559.18 01-JAN-00:10 2160.58 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 23.44 360.35 01-JAN-00:10 1392.33 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 23.44 360.35 01-JAN-00:10 1392.33 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 363.65 5591.71 01-JAN-00:10 21605.52 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 363.65 5591.71 01-JAN-00:10 21605.52 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 234.35 3603.51 01-JAN-00:10 13923.42 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 234.35 3603.51 01-JAN-00:10 13923.42 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 363.66 5591.79 01-JAN-00:10 21605.85 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 363.66 5591.79 01-JAN-00:10 21605.85 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 234.35 3603.49 01-JAN-00:10 13923.33 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 234.35 3603.49 01-JAN-00:10 13923.33 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 36.37 559.17 01-JAN-00:10 2160.55 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 36.37 559.17 01-JAN-00:10 2160.55 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 23.44 360.35 01-JAN-00:10 1392.34 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 23.44 360.35 01-JAN-00:10 1392.34 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 36.37 559.18 01-JAN-00:10 2160.58 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 36.37 559.18 01-JAN-00:10 2160.58 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 23.44 360.35 01-JAN-00:10 1392.33 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 23.44 360.35 01-JAN-00:10 1392.33 02-JAN-08:10
InteriorEquipment:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 7494.86 94908.13 01-JAN-00:10 379632.52 31-MAR-23:10
DataCenterPlugLoads:InteriorEquipment:Electricity 9341.42 118291.40 01-JAN-00:10 473165.59 31-MAR-23:10
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 7494.86 94908.13 01-JAN-00:10 379632.52 31-MAR-23:10
DataCenterPlugLoads:InteriorEquipment:Electricity:SpaceType:GENERAL 9341.42 118291.40 01-JAN-00:10 473165.59 31-MAR-23:10
InteriorEquipment:Electricity:Zone:DATACENTER_BOT_ZN_6 153.88 1948.61 01-JAN-00:10 7794.42 31-MAR-23:10
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_BOT_ZN_6 153.88 1948.61 01-JAN-00:10 7794.42 31-MAR-23:10
InteriorEquipment:Electricity:Zone:DATACENTER_MID_ZN_6 1538.81 19486.06 01-JAN-00:10 77944.22 31-MAR-23:10
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_MID_ZN_6 1538.81 19486.06 01-JAN-00:10 77944.22 31-MAR-23:10
InteriorEquipment:Electricity:Zone:DATACENTER_TOP_ZN_6 153.88 1948.61 01-JAN-00:10 7794.42 31-MAR-23:10
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_TOP_ZN_6 153.88 1948.61 01-JAN-00:10 7794.42 31-MAR-23:10
Electricity:Plant 1321.63 3797.96 07-JAN-05:20 465651.37 07-SEP-14:50
HeatRejection:Electricity 437.48 63.85 10-JAN-22:00 83553.24 06-JUN-14:40
General:HeatRejection:Electricity 437.48 63.85 10-JAN-22:00 83553.24 06-JUN-14:40
Electricity:HVAC 6155.52 55824.13 11-SEP-22:40 656255.75 07-AUG-15:40
ExteriorEquipment:Electricity 1934.80 28603.11 01-JAN-00:10 118535.44 02-JAN-08:20
Transformer:ExteriorEquipment:Electricity 80.18 1421.04 01-JAN-00:10 5057.48 01-DEC-08:20
ElectricityPurchased:Facility 28638.04 343584.99 21-MAY-04:50 2225335.88 07-AUG-15:40
ElectricityPurchased:Plant 28638.04 343584.99 21-MAY-04:50 2225335.88 07-AUG-15:40
Cogeneration:ElectricityPurchased 28638.04 343584.99 21-MAY-04:50 2225335.88 07-AUG-15:40
General:Cogeneration:ElectricityPurchased 28638.04 343584.99 21-MAY-04:50 2225335.88 07-AUG-15:40
ElectricitySurplusSold:Facility 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
ElectricitySurplusSold:Plant 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cogeneration:ElectricitySurplusSold 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Cogeneration:ElectricitySurplusSold 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
ElectricityNet:Facility 28638.04 343584.99 21-MAY-04:50 2225335.88 07-AUG-15:40
ElectricityNet:Plant 28638.04 343584.99 21-MAY-04:50 2225335.88 07-AUG-15:40
Cogeneration:ElectricityNet 28638.04 343584.99 21-MAY-04:50 2225335.88 07-AUG-15:40
General:Cogeneration:ElectricityNet 28638.04 343584.99 21-MAY-04:50 2225335.88 07-AUG-15:40
Fans:Electricity 2717.83 48073.41 01-JAN-21:50 358305.73 17-JUL-15:20
General:Fans:Electricity 2717.83 48073.41 01-JAN-21:50 358305.73 17-JUL-15:20
ExteriorLights:Electricity 696.47 0.00 01-JAN-08:20 57580.60 01-JAN-06:10
General:ExteriorLights:Electricity 696.47 0.00 01-JAN-08:20 57580.60 01-JAN-06:10
ElevatorLift:ExteriorEquipment:Electricity 1848.78 27144.47 01-JAN-00:10 113101.96 01-JAN-07:10
ElevatorLightsFan:ExteriorEquipment:Electricity 5.83 37.60 01-JAN-00:10 376.00 01-JAN-07:10
Cooling:Electricity 1480.31 1654.01 10-JAN-22:00 448448.23 17-JUL-15:30
General:Cooling:Electricity 1480.31 1654.01 10-JAN-22:00 448448.23 17-JUL-15:30
Heating:Electricity 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:Electricity 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Humidifier:Electricity 2435.06 0.00 02-MAY-11:50 100000.00 01-FEB-17:20
General:Humidifier:Electricity 2435.06 0.00 02-MAY-11:50 100000.00 01-FEB-17:20
Boiler Parasitic:Heating:Electricity 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Pumps:Electricity 326.28 3696.33 01-JAN-00:10 48286.92 07-AUG-13:20
General:Pumps:Electricity 326.28 3696.33 01-JAN-00:10 48286.92 07-AUG-13:20
WIRED_LTG_ELECTRICITY 110.53 0.00 01-JAN-00:10 10841.96 02-JAN-08:20
WIRED_INT_EQUIP 5334.97 88964.76 31-MAR-23:10 305206.10 03-APR-07:10


Annual and Peak Values - Natural Gas

Natural Gas Annual Value [GJ] Natural Gas Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Natural Gas Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
NaturalGas:Facility 4459.24 8146.58 05-JAN-22:20 2464803.67 09-JAN-07:10
NaturalGas:Plant 4459.24 8146.58 05-JAN-22:20 2464803.67 09-JAN-07:10
Heating:NaturalGas 3610.86 0.00 01-JAN-00:10 2431734.33 09-JAN-07:10
Boiler:Heating:NaturalGas 3610.86 0.00 01-JAN-00:10 2431734.33 09-JAN-07:10
WaterSystems:NaturalGas 848.37 8146.58 05-JAN-22:20 87976.46 17-FEB-12:40
Water Heater:WaterSystems:NaturalGas 848.37 8146.58 05-JAN-22:20 87976.46 17-FEB-12:40


Annual and Peak Values - Cooling

Cooling Annual Value [GJ] Cooling Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Cooling Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
PlantLoopCoolingDemand:Facility 7652.59 4036.87 10-JAN-22:00 2711241.58 07-SEP-15:00
PlantLoopCoolingDemand:HVAC 7652.59 4036.87 10-JAN-22:00 2711241.58 07-SEP-15:00
CoolingCoils:PlantLoopCoolingDemand 7652.59 4036.87 10-JAN-22:00 2711241.58 07-SEP-15:00


Annual and Peak Values - Water

Annual Value [m3] Minimum Value [m3/s] Timestamp of Minimum {TIMESTAMP} Maximum Value [m3/s] Timestamp of Maximum {TIMESTAMP}
Water:Facility 6681.55 0.00 20-MAY-23:10 0.00 17-JUL-16:00
Water:HVAC 905.84 0.00 02-MAY-11:50 0.00 01-FEB-22:10
Humidifier:Water 905.84 0.00 02-MAY-11:50 0.00 01-FEB-22:10
General:Humidifier:Water 905.84 0.00 02-MAY-11:50 0.00 01-FEB-22:10
MainsWater:Facility 6681.55 0.00 20-MAY-23:10 0.00 17-JUL-16:00
MainsWater:HVAC 905.84 0.00 02-MAY-11:50 0.00 01-FEB-22:10
Humidifier:MainsWater 905.84 0.00 02-MAY-11:50 0.00 01-FEB-22:10
General:Humidifier:MainsWater 905.84 0.00 02-MAY-11:50 0.00 01-FEB-22:10
Water:Plant 5775.71 0.00 01-JAN-00:10 0.00 17-JUL-16:00
WaterSystems:Water 2280.17 0.00 01-JAN-00:10 0.00 02-JAN-12:10
WaterUse:WaterSystems:Water 2280.17 0.00 01-JAN-00:10 0.00 02-JAN-12:10
MainsWater:Plant 5775.71 0.00 01-JAN-00:10 0.00 17-JUL-16:00
WaterSystems:MainsWater 2280.17 0.00 01-JAN-00:10 0.00 02-JAN-12:10
WaterUse:WaterSystems:MainsWater 2280.17 0.00 01-JAN-00:10 0.00 02-JAN-12:10
Water Heater:WaterSystems:Water 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Water Heater:WaterSystems:MainsWater 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
HeatRejection:Water 3495.54 0.00 01-JAN-00:10 0.00 17-JUL-16:00
General:HeatRejection:Water 3495.54 0.00 01-JAN-00:10 0.00 17-JUL-16:00
HeatRejection:MainsWater 3495.54 0.00 01-JAN-00:10 0.00 17-JUL-16:00
General:HeatRejection:MainsWater 3495.54 0.00 01-JAN-00:10 0.00 17-JUL-16:00


Annual and Peak Values - Other by Weight/Mass

Annual Value [kg] Minimum Value [kg/s] Timestamp of Minimum {TIMESTAMP} Maximum Value [kg/s] Timestamp of Maximum {TIMESTAMP}
Carbon Equivalent:Facility 0.00 0.000 01-JAN-00:10 0.000 01-JAN-00:10
CarbonEquivalentEmissions:Carbon Equivalent 0.00 0.000 01-JAN-00:10 0.000 01-JAN-00:10


Annual and Peak Values - Other Volumetric

Annual Value [m3] Minimum Value [m3/s] Timestamp of Minimum {TIMESTAMP} Maximum Value [m3/s] Timestamp of Maximum {TIMESTAMP}
None          


Annual and Peak Values - Other Liquid/Gas

Annual Value [L] Minimum Value [L] Timestamp of Minimum {TIMESTAMP} Maximum Value [L] Timestamp of Maximum {TIMESTAMP}
None          


Annual and Peak Values - Other

Annual Value [GJ] Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
EnergyTransfer:Facility 43952.80 96971.11 12-JAN-03:40 11435242.68 07-SEP-15:00
EnergyTransfer:Building 19207.79 88203.93 12-JAN-22:50 1834695.57 07-AUG-15:20
EnergyTransfer:Zone:BASEMENT 698.10 0.00 01-JAN-00:40 75312.76 05-SEP-05:10
Heating:EnergyTransfer 1122.53 0.00 13-JAN-22:10 1408471.26 09-JAN-06:10
Heating:EnergyTransfer:Zone:BASEMENT 2.83 0.00 01-JAN-00:20 22572.52 05-AUG-16:10
General:Heating:EnergyTransfer 1122.53 0.00 13-JAN-22:10 1408471.26 09-JAN-06:10
General:Heating:EnergyTransfer:Zone:BASEMENT 2.83 0.00 01-JAN-00:20 22572.52 05-AUG-16:10
Cooling:EnergyTransfer 18085.26 82921.39 09-JAN-05:40 1834695.57 07-AUG-15:20
Cooling:EnergyTransfer:Zone:BASEMENT 695.26 0.00 01-JAN-00:40 75312.76 05-SEP-05:10
General:Cooling:EnergyTransfer 18085.26 82921.39 09-JAN-05:40 1834695.57 07-AUG-15:20
General:Cooling:EnergyTransfer:Zone:BASEMENT 695.26 0.00 01-JAN-00:40 75312.76 05-SEP-05:10
EnergyTransfer:Zone:CORE_BOTTOM 610.52 0.00 01-JAN-00:10 57358.68 07-AUG-13:10
Heating:EnergyTransfer:Zone:CORE_BOTTOM 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:CORE_BOTTOM 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:CORE_BOTTOM 610.52 0.00 01-JAN-00:10 57358.68 07-AUG-13:10
General:Cooling:EnergyTransfer:Zone:CORE_BOTTOM 610.52 0.00 01-JAN-00:10 57358.68 07-AUG-13:10
EnergyTransfer:Zone:CORE_MID 4294.69 0.00 01-JAN-00:10 465142.92 10-AUG-15:50
Heating:EnergyTransfer:Zone:CORE_MID 10.25 0.00 01-JAN-00:10 379413.47 09-JAN-06:10
General:Heating:EnergyTransfer:Zone:CORE_MID 10.25 0.00 01-JAN-00:10 379413.47 09-JAN-06:10
Cooling:EnergyTransfer:Zone:CORE_MID 4284.45 0.00 01-JAN-00:10 465142.92 10-AUG-15:50
General:Cooling:EnergyTransfer:Zone:CORE_MID 4284.45 0.00 01-JAN-00:10 465142.92 10-AUG-15:50
EnergyTransfer:Zone:CORE_TOP 384.56 0.00 01-JAN-00:10 73874.39 09-JAN-05:30
Heating:EnergyTransfer:Zone:CORE_TOP 20.17 0.00 01-JAN-00:10 73874.39 09-JAN-05:30
General:Heating:EnergyTransfer:Zone:CORE_TOP 20.17 0.00 01-JAN-00:10 73874.39 09-JAN-05:30
Cooling:EnergyTransfer:Zone:CORE_TOP 364.38 0.00 01-JAN-00:10 54262.09 17-JUL-15:30
General:Cooling:EnergyTransfer:Zone:CORE_TOP 364.38 0.00 01-JAN-00:10 54262.09 17-JUL-15:30
EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 63.92 0.00 01-JAN-00:10 13555.60 09-JAN-05:10
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 4.49 0.00 01-JAN-00:10 13555.60 09-JAN-05:10
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 4.49 0.00 01-JAN-00:10 13555.60 09-JAN-05:10
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 59.43 0.00 01-JAN-00:10 11225.64 18-JUL-12:20
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 59.43 0.00 01-JAN-00:10 11225.64 18-JUL-12:20
EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 71.22 0.00 01-JAN-00:10 17608.79 07-AUG-08:30
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 3.27 0.00 01-JAN-00:10 11061.16 09-JAN-05:10
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 3.27 0.00 01-JAN-00:10 11061.16 09-JAN-05:10
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 67.95 0.00 01-JAN-00:10 17608.79 07-AUG-08:30
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 67.95 0.00 01-JAN-00:10 17608.79 07-AUG-08:30
EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 120.87 0.00 01-JAN-00:10 24881.14 18-OCT-13:20
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 4.61 0.00 01-JAN-00:10 16706.17 09-JAN-05:10
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 4.61 0.00 01-JAN-00:10 16706.17 09-JAN-05:10
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 116.26 0.00 01-JAN-00:10 24881.14 18-OCT-13:20
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 116.26 0.00 01-JAN-00:10 24881.14 18-OCT-13:20
EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 98.39 0.00 01-JAN-00:10 21356.88 07-AUG-16:40
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 1.14 0.00 01-JAN-00:10 8713.31 09-JAN-05:10
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 1.14 0.00 01-JAN-00:10 8713.31 09-JAN-05:10
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 97.25 0.00 01-JAN-00:10 21356.88 07-AUG-16:40
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 97.25 0.00 01-JAN-00:10 21356.88 07-AUG-16:40
EnergyTransfer:Zone:PERIMETER_MID_ZN_3 639.70 0.00 01-JAN-00:10 148412.29 09-JAN-04:40
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 256.28 0.00 01-JAN-00:10 148412.29 09-JAN-04:40
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 256.28 0.00 01-JAN-00:10 148412.29 09-JAN-04:40
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 383.42 0.00 01-JAN-00:10 105286.21 18-JUL-13:00
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 383.42 0.00 01-JAN-00:10 105286.21 18-JUL-13:00
EnergyTransfer:Zone:PERIMETER_MID_ZN_2 717.27 0.00 01-JAN-00:10 185197.36 07-AUG-09:00
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 151.32 0.00 01-JAN-00:10 165295.56 09-JAN-05:20
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 151.32 0.00 01-JAN-00:10 165295.56 09-JAN-05:20
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 565.95 0.00 01-JAN-00:10 185197.36 07-AUG-09:00
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 565.95 0.00 01-JAN-00:10 185197.36 07-AUG-09:00
EnergyTransfer:Zone:PERIMETER_MID_ZN_1 1177.43 0.00 01-JAN-00:10 262982.27 18-OCT-13:40
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 157.13 0.00 01-JAN-00:10 228934.78 09-JAN-05:20
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 157.13 0.00 01-JAN-00:10 228934.78 09-JAN-05:20
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 1020.30 0.00 01-JAN-00:10 262982.27 18-OCT-13:40
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 1020.30 0.00 01-JAN-00:10 262982.27 18-OCT-13:40
EnergyTransfer:Zone:PERIMETER_MID_ZN_4 707.89 0.00 01-JAN-00:10 198241.95 16-JUL-17:10
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 126.45 0.00 01-JAN-00:10 159075.34 09-JAN-05:20
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 126.45 0.00 01-JAN-00:10 159075.34 09-JAN-05:20
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 581.43 0.00 01-JAN-00:10 198241.95 16-JUL-17:10
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 581.43 0.00 01-JAN-00:10 198241.95 16-JUL-17:10
EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 86.88 0.00 01-JAN-00:10 18156.29 09-JAN-04:10
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 51.70 0.00 01-JAN-00:10 18156.29 09-JAN-04:10
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 51.70 0.00 01-JAN-00:10 18156.29 09-JAN-04:10
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 35.18 0.00 01-JAN-00:10 11604.44 17-JUL-16:00
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 35.18 0.00 01-JAN-00:10 11604.44 17-JUL-16:00
EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 82.37 0.00 01-JAN-00:10 19171.16 09-JAN-05:10
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 29.94 0.00 01-JAN-00:10 19171.16 09-JAN-05:10
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 29.94 0.00 01-JAN-00:10 19171.16 09-JAN-05:10
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 52.42 0.00 01-JAN-00:10 18684.57 07-AUG-09:10
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 52.42 0.00 01-JAN-00:10 18684.57 07-AUG-09:10
EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 128.34 0.00 01-JAN-00:10 27082.29 18-OCT-13:40
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 34.93 0.00 01-JAN-00:10 26059.64 09-JAN-05:30
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 34.93 0.00 01-JAN-00:10 26059.64 09-JAN-05:30
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 93.41 0.00 01-JAN-00:10 27082.29 18-OCT-13:40
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 93.41 0.00 01-JAN-00:10 27082.29 18-OCT-13:40
EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 80.07 0.00 01-JAN-00:10 20362.79 17-JUL-17:00
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 25.56 0.00 01-JAN-00:10 19802.88 09-JAN-05:10
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 25.56 0.00 01-JAN-00:10 19802.88 09-JAN-05:10
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 54.51 0.00 01-JAN-00:10 20362.79 17-JUL-17:00
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 54.51 0.00 01-JAN-00:10 20362.79 17-JUL-17:00
EnergyTransfer:Zone:GROUNDFLOOR_PLENUM 60.07 0.00 01-JAN-00:10 11095.22 07-AUG-15:20
Heating:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM 4.67 0.00 01-JAN-00:10 7265.74 30-JAN-13:30
General:Heating:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM 4.67 0.00 01-JAN-00:10 7265.74 30-JAN-13:30
Cooling:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM 55.40 0.00 01-JAN-00:10 11095.22 07-AUG-15:20
General:Cooling:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM 55.40 0.00 01-JAN-00:10 11095.22 07-AUG-15:20
EnergyTransfer:Zone:MIDFLOOR_PLENUM 498.63 0.00 01-JAN-00:10 128715.76 09-JAN-06:10
Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM 161.05 0.00 01-JAN-00:10 128715.76 09-JAN-06:10
General:Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM 161.05 0.00 01-JAN-00:10 128715.76 09-JAN-06:10
Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM 337.58 0.00 01-JAN-00:10 89916.40 17-JUL-15:30
General:Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM 337.58 0.00 01-JAN-00:10 89916.40 17-JUL-15:30
EnergyTransfer:Zone:TOPFLOOR_PLENUM 118.79 0.00 01-JAN-00:10 36246.05 09-JAN-05:10
Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM 68.58 0.00 01-JAN-00:10 36246.05 09-JAN-05:10
General:Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM 68.58 0.00 01-JAN-00:10 36246.05 09-JAN-05:10
Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM 50.21 0.00 01-JAN-00:10 24012.12 17-JUL-14:50
General:Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM 50.21 0.00 01-JAN-00:10 24012.12 17-JUL-14:50
EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 136.18 1.75 28-JAN-06:50 8528.18 03-AUG-18:50
Heating:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 0.11 0.00 01-JAN-00:10 658.59 08-JAN-22:20
General:Heating:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 0.11 0.00 01-JAN-00:10 658.59 08-JAN-22:20
Cooling:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 136.07 0.00 07-JAN-21:00 8528.18 03-AUG-18:50
General:Cooling:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 136.07 0.00 07-JAN-21:00 8528.18 03-AUG-18:50
EnergyTransfer:Zone:DATACENTER_MID_ZN_6 1156.67 6.99 01-MAY-04:50 81981.71 03-AUG-18:50
Heating:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 6.86 0.00 02-JAN-10:50 6777.33 29-JAN-18:20
General:Heating:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 6.86 0.00 02-JAN-10:50 6777.33 29-JAN-18:20
Cooling:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 1149.80 0.00 01-JAN-00:10 81981.71 03-AUG-18:50
General:Cooling:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 1149.80 0.00 01-JAN-00:10 81981.71 03-AUG-18:50
EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 105.07 0.11 18-JAN-11:00 8260.23 03-AUG-18:50
Heating:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 1.17 0.00 02-JAN-12:40 777.06 30-APR-23:10
General:Heating:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 1.17 0.00 02-JAN-12:40 777.06 30-APR-23:10
Cooling:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 103.90 0.00 01-JAN-00:10 8260.23 03-AUG-18:50
General:Cooling:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 103.90 0.00 01-JAN-00:10 8260.23 03-AUG-18:50
EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 7170.17 82876.72 09-JAN-05:00 376214.69 06-AUG-21:20
Heating:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 7170.17 82876.72 09-JAN-05:00 376214.69 06-AUG-21:20
General:Cooling:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 7170.17 82876.72 09-JAN-05:00 376214.69 06-AUG-21:20
PlantLoopHeatingDemand:Facility 3273.10 0.00 01-JAN-00:10 2087233.06 09-JAN-07:10
PlantLoopHeatingDemand:Plant 463.31 0.00 01-JAN-00:10 57406.13 17-FEB-12:20
WaterSystems:PlantLoopHeatingDemand 463.31 0.00 01-JAN-00:10 57406.13 17-FEB-12:20
General:WaterSystems:PlantLoopHeatingDemand 463.31 0.00 01-JAN-00:10 57406.13 17-FEB-12:20
EnergyTransfer:HVAC 9539.93 3107.13 10-JAN-22:10 2659470.77 07-SEP-15:00
HeatingCoils:EnergyTransfer 2809.79 0.00 01-JAN-00:10 2068657.57 09-JAN-07:10
PlantLoopHeatingDemand:HVAC 2809.79 0.00 01-JAN-00:10 2068657.57 09-JAN-07:10
HeatingCoils:PlantLoopHeatingDemand 2809.79 0.00 01-JAN-00:10 2068657.57 09-JAN-07:10
CoolingCoils:EnergyTransfer 6730.14 2382.86 10-JAN-22:00 2659470.77 07-SEP-15:00
EnergyTransfer:Plant 15205.08 0.00 01-JAN-00:10 7503699.18 07-SEP-15:00
LoopToLoop:EnergyTransfer 3809.76 0.00 01-JAN-00:10 2431950.32 07-SEP-15:00
WaterSystems:EnergyTransfer 463.31 0.00 01-JAN-00:10 57406.13 17-FEB-12:20
WaterUse:WaterSystems:EnergyTransfer 463.31 0.00 01-JAN-00:10 57406.13 17-FEB-12:20
Boilers:EnergyTransfer 2784.87 0.00 01-JAN-00:10 2020821.09 09-JAN-07:10
Chillers:EnergyTransfer 3794.64 0.00 01-JAN-00:10 2360491.54 07-SEP-14:50
HeatRejection:EnergyTransfer 4352.50 0.00 01-JAN-00:10 2695905.02 07-SEP-14:50
General:HeatRejection:EnergyTransfer 4352.50 0.00 01-JAN-00:10 2695905.02 07-SEP-14:50
Water Heater:WaterSystems:PlantLoopHeatingDemand 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10



Table of Contents

Report: Sensible Heat Gain Summary

For: Entire Facility

Timestamp: 2023-10-16 08:43:39

Annual Building Sensible Heat Gain Components

HVAC Zone Eq & Other Sensible Air Heating [GJ] HVAC Zone Eq & Other Sensible Air Cooling [GJ] HVAC Terminal Unit Sensible Air Heating [GJ] HVAC Terminal Unit Sensible Air Cooling [GJ] HVAC Input Heated Surface Heating [GJ] HVAC Input Cooled Surface Cooling [GJ] People Sensible Heat Addition [GJ] Lights Sensible Heat Addition [GJ] Equipment Sensible Heat Addition [GJ] Window Heat Addition [GJ] Interzone Air Transfer Heat Addition [GJ] Infiltration Heat Addition [GJ] Opaque Surface Conduction and Other Heat Addition [GJ] Equipment Sensible Heat Removal [GJ] Window Heat Removal [GJ] Interzone Air Transfer Heat Removal [GJ] Infiltration Heat Removal [GJ] Opaque Surface Conduction and Other Heat Removal [GJ]
BASEMENT 0.000 0.000 2.835 -695.261 0.000 0.000 93.142 262.844 424.397 0.000 0.000 0.000 0.001 0.000 0.000 0.000 0.000 -87.957
CORE_BOTTOM 0.000 0.000 0.000 -610.520 0.000 0.000 83.580 236.053 289.614 0.000 0.000 0.000 1.273 0.000 0.000 0.000 0.000 -0.004
CORE_MID 0.000 0.000 10.249 -4284.426 0.000 0.000 852.907 2360.527 2896.128 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 -1835.385
CORE_TOP 0.000 0.000 20.174 -364.380 0.000 0.000 88.485 236.053 289.613 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 -269.945
PERIMETER_BOT_ZN_3 0.000 0.000 4.495 -59.425 0.000 0.000 11.033 17.574 36.365 27.767 0.000 0.085 66.268 0.000 -93.931 0.000 -10.231 0.000
PERIMETER_BOT_ZN_2 0.000 0.000 3.267 -67.953 0.000 0.000 7.175 11.163 23.435 67.422 0.000 0.059 19.407 0.000 -57.246 0.000 -6.730 0.000
PERIMETER_BOT_ZN_1 0.000 0.000 4.608 -116.261 0.000 0.000 10.946 17.172 36.366 146.741 0.000 0.082 0.004 0.000 -84.929 0.000 -10.317 -4.408
PERIMETER_BOT_ZN_4 0.000 0.000 1.137 -97.249 0.000 0.000 7.038 11.198 23.435 63.150 0.000 0.054 64.117 0.000 -65.551 0.000 -7.329 0.000
PERIMETER_MID_ZN_3 0.000 0.000 256.278 -383.417 0.000 0.000 115.523 175.350 363.654 292.282 0.000 2.012 249.097 0.000 -858.388 0.000 -212.391 0.000
PERIMETER_MID_ZN_2 0.000 0.000 151.320 -565.952 0.000 0.000 54.440 111.478 234.352 677.818 0.000 1.326 16.884 0.000 -537.433 0.000 -144.233 -0.009
PERIMETER_MID_ZN_1 0.000 0.000 157.131 -1020.288 0.000 0.000 111.725 171.538 363.660 1462.779 0.000 1.868 0.030 0.000 -819.718 0.000 -227.712 -200.982
PERIMETER_MID_ZN_4 0.000 0.000 126.454 -581.423 0.000 0.000 74.808 111.805 234.351 648.280 0.000 1.306 113.195 0.000 -581.062 0.000 -147.714 0.000
PERIMETER_TOP_ZN_3 0.000 0.000 51.701 -35.176 0.000 0.000 11.728 17.533 36.365 29.915 0.000 0.244 0.000 0.000 -81.811 0.000 -25.024 -5.476
PERIMETER_TOP_ZN_2 0.000 0.000 29.944 -52.423 0.000 0.000 7.450 11.148 23.435 68.263 0.000 0.157 0.001 0.000 -51.476 0.000 -17.067 -19.430
PERIMETER_TOP_ZN_1 0.000 0.000 34.933 -93.405 0.000 0.000 11.346 17.153 36.366 147.088 0.000 0.224 0.005 0.000 -78.101 0.000 -26.752 -48.852
PERIMETER_TOP_ZN_4 0.000 0.000 25.559 -54.508 0.000 0.000 7.563 11.180 23.435 65.082 0.000 0.159 0.002 0.000 -55.822 0.000 -17.535 -5.112
DATACENTER_BOT_ZN_6 0.000 0.000 0.109 -136.069 0.000 0.000 0.950 6.628 153.881 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 -25.499
DATACENTER_MID_ZN_6 0.000 0.000 6.864 -1149.802 0.000 0.000 9.522 66.280 1538.806 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 -471.669
DATACENTER_TOP_ZN_6 0.000 0.000 1.169 -103.904 0.000 0.000 0.957 6.628 153.881 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 -58.730
DATACENTER_BASEMENT_ZN_6 0.000 0.000 0.000 -7170.174 0.000 0.000 20.391 74.111 7494.857 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 -419.184
GROUNDFLOOR_PLENUM 4.666 -55.403 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.157 72.706 0.000 0.000 0.000 -22.125 0.000
MIDFLOOR_PLENUM 161.054 -337.579 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 2.914 545.019 0.000 0.000 0.000 -371.409 -0.020
TOPFLOOR_PLENUM 68.581 -50.207 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.258 20.437 0.000 0.000 0.000 -39.070 -0.001
Total Facility 234.301 -443.189 888.227 -17642.017 0.000 0.000 1580.708 3933.414 14676.396 3696.585 0.000 10.906 1168.447 0.000 -3365.468 0.000 -1285.638 -3452.663


Peak Cooling Sensible Heat Gain Components

Time of Peak {TIMESTAMP} HVAC Zone Eq & Other Sensible Air Heating [W] HVAC Zone Eq & Other Sensible Air Cooling [W] HVAC Terminal Unit Sensible Air Heating [W] HVAC Terminal Unit Sensible Air Cooling [W] HVAC Input Heated Surface Heating [W] HVAC Input Cooled Surface Cooling [W] People Sensible Heat Addition [W] Lights Sensible Heat Addition [W] Equipment Sensible Heat Addition [W] Window Heat Addition [W] Interzone Air Transfer Heat Addition [W] Infiltration Heat Addition [W] Opaque Surface Conduction and Other Heat Addition [W] Equipment Sensible Heat Removal [W] Window Heat Removal [W] Interzone Air Transfer Heat Removal [W] Infiltration Heat Removal [W] Opaque Surface Conduction and Other Heat Removal [W]
BASEMENT 02-JUL-17:45 0.00 0.00 0.00 -122556.64 0.00 0.00 0.00 1274.92 13457.54 0.00 0.00 0.00 107824.17 0.00 -0.00 0.00 0.00 0.00
CORE_BOTTOM 05-SEP-04:13 0.00 0.00 0.00 -102156.29 0.00 0.00 0.00 2290.20 5937.65 0.00 0.00 0.00 93928.45 0.00 -0.00 0.00 0.00 0.00
CORE_MID 14-AUG-04:12 0.00 0.00 0.00 -879850.33 0.00 0.00 0.00 22901.98 59376.23 0.00 0.00 0.00 797572.12 0.00 -0.00 0.00 0.00 0.00
CORE_TOP 21-JUN-04:12 0.00 0.00 0.00 -86067.66 0.00 0.00 0.00 2290.20 5937.62 0.00 0.00 0.00 77839.84 0.00 -0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_3 16-JUL-18:31 0.00 0.00 0.00 -18010.42 0.00 0.00 0.00 68.40 559.17 7843.69 0.00 90.80 9448.36 0.00 -0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_2 04-SEP-08:41 0.00 0.00 0.00 -27686.67 0.00 0.00 18.64 44.08 464.11 17660.78 0.00 0.00 9547.47 0.00 -0.00 0.00 -48.43 0.00
PERIMETER_BOT_ZN_1 15-OCT-13:31 0.00 0.00 0.00 -36755.80 0.00 0.00 26.28 68.40 720.19 35315.42 0.00 0.00 1046.59 0.00 -0.00 0.00 -421.10 0.00
PERIMETER_BOT_ZN_4 04-SEP-16:01 0.00 0.00 0.00 -35973.63 0.00 0.00 13.91 44.08 464.11 22672.75 0.00 30.82 12747.95 0.00 -0.00 0.00 0.00 0.00
PERIMETER_MID_ZN_3 16-JUL-18:21 0.00 0.00 0.00 -172198.58 0.00 0.00 0.00 684.02 5591.71 82988.01 0.00 1805.88 81128.97 0.00 -0.00 0.00 0.00 0.00
PERIMETER_MID_ZN_2 02-JUL-09:01 0.00 0.00 0.00 -323747.38 0.00 0.00 147.88 440.81 4641.14 211123.50 0.00 0.00 110629.74 0.00 -0.00 0.00 -3235.70 0.00
PERIMETER_MID_ZN_1 04-SEP-15:31 0.00 0.00 0.00 -357466.27 0.00 0.00 276.96 684.04 7201.95 174466.76 0.00 1357.72 173478.85 0.00 -0.00 0.00 0.00 0.00
PERIMETER_MID_ZN_4 16-JUL-17:01 0.00 0.00 0.00 -357096.34 0.00 0.00 0.00 440.81 3603.49 247892.11 0.00 448.94 104711.00 0.00 -0.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_3 02-JUL-18:31 0.00 0.00 0.00 -19697.55 0.00 0.00 0.00 68.40 559.17 6530.18 0.00 0.00 12694.96 0.00 -0.00 0.00 -155.16 0.00
PERIMETER_TOP_ZN_2 02-JUL-08:31 0.00 0.00 0.00 -31920.71 0.00 0.00 15.74 44.08 464.11 22997.98 0.00 0.00 8883.17 0.00 -0.00 0.00 -484.37 0.00
PERIMETER_TOP_ZN_1 03-SEP-12:41 0.00 0.00 0.00 -37751.86 0.00 0.00 21.01 68.40 720.19 31880.39 0.00 561.01 4500.85 0.00 -0.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_4 02-JUL-17:51 0.00 0.00 0.00 -36675.69 0.00 0.00 0.00 44.08 360.35 23897.95 0.00 0.00 12578.66 0.00 -0.00 0.00 -205.36 0.00
DATACENTER_BOT_ZN_6 03-AUG-18:50 0.00 0.00 0.00 -8527.87 0.00 0.00 10.61 192.90 7794.42 0.00 0.00 0.00 529.94 0.00 -0.00 0.00 0.00 0.00
DATACENTER_MID_ZN_6 03-AUG-18:50 0.00 0.00 0.00 -81978.71 0.00 0.00 106.16 1929.04 77944.22 0.00 0.00 0.00 1999.29 0.00 -0.00 0.00 0.00 0.00
DATACENTER_TOP_ZN_6 03-AUG-18:50 0.00 0.00 0.00 -8259.93 0.00 0.00 10.62 192.90 7794.42 0.00 0.00 0.00 261.99 0.00 -0.00 0.00 0.00 0.00
DATACENTER_BASEMENT_ZN_6 06-AUG-19:52 0.00 0.00 0.00 -383639.25 0.00 0.00 0.00 359.47 379632.52 0.00 0.00 0.00 3647.25 0.00 -0.00 0.00 0.00 0.00
GROUNDFLOOR_PLENUM 05-SEP-05:03 0.00 -11998.83 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 12088.56 0.00 -0.00 0.00 -89.73 0.00
MIDFLOOR_PLENUM 04-MAR-04:01 0.00 -163313.27 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 194577.34 0.00 -0.00 0.00 -31264.07 0.00
TOPFLOOR_PLENUM 17-JUL-14:50 0.00 -24011.15 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 16.81 23994.35 0.00 -0.00 0.00 0.00 0.00
Total Facility 07-AUG-04:12 0.00 45212.96 0.00 -2019573.11 0.00 0.00 0.00 42872.09 587299.42 0.00 0.00 0.00 1449269.86 0.00 -85292.00 0.00 -19789.21 0.00


Peak Heating Sensible Heat Gain Components

Time of Peak {TIMESTAMP} HVAC Zone Eq & Other Sensible Air Heating [W] HVAC Zone Eq & Other Sensible Air Cooling [W] HVAC Terminal Unit Sensible Air Heating [W] HVAC Terminal Unit Sensible Air Cooling [W] HVAC Input Heated Surface Heating [W] HVAC Input Cooled Surface Cooling [W] People Sensible Heat Addition [W] Lights Sensible Heat Addition [W] Equipment Sensible Heat Addition [W] Window Heat Addition [W] Interzone Air Transfer Heat Addition [W] Infiltration Heat Addition [W] Opaque Surface Conduction and Other Heat Addition [W] Equipment Sensible Heat Removal [W] Window Heat Removal [W] Interzone Air Transfer Heat Removal [W] Infiltration Heat Removal [W] Opaque Surface Conduction and Other Heat Removal [W]
BASEMENT 05-AUG-16:01 0.00 0.00 24070.30 0.00 0.00 0.00 520.12 1274.92 13457.54 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 0.00 -39322.89
CORE_BOTTOM - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CORE_MID 09-JAN-05:11 0.00 0.00 535852.76 0.00 0.00 0.00 0.00 22901.98 59376.23 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 0.00 -618130.97
CORE_TOP 09-JAN-04:01 0.00 0.00 84608.20 0.00 0.00 0.00 0.00 1144.97 5937.62 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 0.00 -91690.79
PERIMETER_BOT_ZN_3 09-JAN-04:01 0.00 0.00 15183.82 0.00 0.00 0.00 0.00 143.76 745.56 0.00 0.00 0.00 0.00 0.00 -9731.46 0.00 -842.58 -5499.11
PERIMETER_BOT_ZN_2 09-JAN-04:01 0.00 0.00 17408.67 0.00 0.00 0.00 0.00 92.65 480.47 0.00 0.00 0.00 0.00 0.00 -6472.86 0.00 -566.51 -10942.41
PERIMETER_BOT_ZN_1 10-JAN-04:01 0.00 0.00 24930.20 0.00 0.00 0.00 0.00 143.77 745.57 0.00 0.00 0.00 0.00 0.00 -8783.13 0.00 -753.78 -16282.63
PERIMETER_BOT_ZN_4 09-JAN-04:01 0.00 0.00 16866.75 0.00 0.00 0.00 0.00 92.65 480.46 0.00 0.00 0.00 0.00 0.00 -6410.24 0.00 -567.59 -10462.03
PERIMETER_MID_ZN_3 09-JAN-04:31 0.00 0.00 160493.89 0.00 0.00 0.00 0.00 1437.63 7455.61 0.00 0.00 0.00 0.00 0.00 -94002.59 0.00 -18606.14 -56778.39
PERIMETER_MID_ZN_2 09-JAN-04:31 0.00 0.00 230598.33 0.00 0.00 0.00 0.00 926.46 4804.68 0.00 0.00 0.00 0.00 0.00 -63222.49 0.00 -12700.84 -160406.14
PERIMETER_MID_ZN_1 09-JAN-02:31 0.00 0.00 277596.02 0.00 0.00 0.00 0.00 1437.66 7455.72 0.00 0.00 0.00 0.00 0.00 -90994.77 0.00 -26456.46 -169038.17
PERIMETER_MID_ZN_4 09-JAN-02:31 0.00 0.00 235809.72 0.00 0.00 0.00 0.00 926.46 4804.65 0.00 0.00 0.00 0.00 0.00 -60762.70 0.00 -17754.90 -163023.22
PERIMETER_TOP_ZN_3 09-JAN-04:01 0.00 0.00 19801.78 0.00 0.00 0.00 0.00 143.76 745.56 0.00 0.00 0.00 0.00 0.00 -8994.74 0.00 -2210.94 -9485.43
PERIMETER_TOP_ZN_2 09-JAN-04:01 0.00 0.00 25428.78 0.00 0.00 0.00 0.00 92.65 480.47 0.00 0.00 0.00 0.00 0.00 -6014.47 0.00 -1501.08 -18486.34
PERIMETER_TOP_ZN_1 09-JAN-04:01 0.00 0.00 32105.14 0.00 0.00 0.00 0.00 143.77 745.57 0.00 0.00 0.00 0.00 0.00 -8762.00 0.00 -2253.33 -21979.15
PERIMETER_TOP_ZN_4 09-JAN-04:01 0.00 0.00 28459.63 0.00 0.00 0.00 0.00 92.65 480.46 0.00 0.00 0.00 0.00 0.00 -5858.13 0.00 -1518.24 -21656.38
DATACENTER_BOT_ZN_6 08-JAN-22:15 0.00 0.00 659.94 0.00 0.00 0.00 0.00 32.15 1948.61 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 0.00 -2640.70
DATACENTER_MID_ZN_6 29-JAN-18:20 0.00 0.00 6823.66 0.00 0.00 0.00 0.00 321.53 19486.06 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 0.00 -26631.25
DATACENTER_TOP_ZN_6 30-APR-23:05 0.00 0.00 785.14 0.00 0.00 0.00 0.00 32.15 1948.61 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 0.00 -2765.90
DATACENTER_BASEMENT_ZN_6 - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
GROUNDFLOOR_PLENUM 06-AUG-16:01 15402.29 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 570.95 0.00 0.00 -0.00 0.00 0.00 -15973.24
MIDFLOOR_PLENUM 16-APR-16:21 185004.79 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 -5295.36 -179709.44
TOPFLOOR_PLENUM 09-JAN-05:04 36992.61 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 -3462.08 -33530.53
Total Facility 09-JAN-06:02 78863.15 96418.93 1403392.83 -96418.93 0.00 0.00 21551.88 42872.09 261414.96 0.00 0.00 0.00 0.00 0.00 -393440.78 0.00 -30681.26 -1383972.87



Table of Contents

Report: Standard 62.1 Summary

For: Entire Facility

Timestamp: 2023-10-16 08:43:39

System Ventilation Requirements for Cooling

Sum of Zone Primary Air Flow - Vpz-sum [m3/s] System Population - Ps Sum of Zone Population - Pz-sum Occupant Diversity - D Origin of D Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] System Primary Airflow - Vps [m3/s] Average Outdoor Air Fraction - Xs System Ventilation Efficiency - Ev Calculation Method for Ev Outdoor Air Intake Flow - Vot [m3/s] Percent Outdoor Air - %OA Environment Name of Peak System Population - Ps Date and Time of Last Peak System Population - Ps
VAV_BOT WITH REHEAT 13.8821 0.0000 0.0000 1.0000 Calculated from schedules 0.0000 11.6557 0.0000 1.0000 Not calculated 0.0000 0.0000    
VAV_MID WITH REHEAT 134.4688 0.0000 0.0000 1.0000 Calculated from schedules 0.0000 107.8319 0.0000 1.0000 Not calculated 0.0000 0.0000    
VAV_TOP WITH REHEAT 13.6326 0.0000 0.0000 1.0000 Calculated from schedules 0.0000 12.3008 0.0000 1.0000 Not calculated 0.0000 0.0000    
CAV_BAS 6.8191 0.0000 149.6021 1.0000 Calculated from schedules 1.2002 6.8191 0.1760 1.0000 Not calculated 1.2002 0.1760    
AIRLOOP DATACENTER BASEMENT 24.5388 0.0000 42.1814 1.0000 Calculated from schedules 0.3384 24.5389 0.0138 1.0000 Not calculated 0.3384 0.0138    
AIRLOOP DATACENTER BOT 0.5854 0.0000 1.9486 1.0000 Calculated from schedules 0.0156 0.5854 0.0267 1.0000 Not calculated 0.0156 0.0267    
AIRLOOP DATACENTER MID 5.6297 0.0000 19.4861 1.0000 Calculated from schedules 0.1563 5.6297 0.0278 1.0000 Not calculated 0.1563 0.0278    
AIRLOOP DATACENTER TOP 0.5724 0.0000 1.9486 1.0000 Calculated from schedules 0.0156 0.5724 0.0273 1.0000 Not calculated 0.0156 0.0273    


System Ventilation Requirements for Heating

Sum of Zone Primary Air Flow - Vpz-sum [m3/s] System Population - Ps Sum of Zone Population - Pz-sum Occupant Diversity - D Origin of D Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] System Primary Airflow - Vps [m3/s] Average Outdoor Air Fraction - Xs System Ventilation Efficiency - Ev Calculation Method for Ev Outdoor Air Intake Flow Vot [m3/s] Percent Outdoor Air - %OA Environment Name of Peak System Population - Ps Date and Time of Last Peak System Population - Ps
VAV_BOT WITH REHEAT 6.9410 0.0000 0.0000 1.0000 Calculated from schedules 0.0000 3.4136 0.0000 1.0000 Not calculated 0.0000 0.0000    
VAV_MID WITH REHEAT 67.2344 0.0000 0.0000 1.0000 Calculated from schedules 0.0000 33.6965 0.0000 1.0000 Not calculated 0.0000 0.0000    
VAV_TOP WITH REHEAT 6.8163 0.0000 0.0000 1.0000 Calculated from schedules 0.0000 3.5014 0.0000 1.0000 Not calculated 0.0000 0.0000    
CAV_BAS 6.8191 0.0000 149.6021 1.0000 Calculated from schedules 1.2002 6.8191 1.0000 1.0000 Not calculated 1.2002 0.1760    
AIRLOOP DATACENTER BASEMENT 24.5388 0.0000 42.1814 1.0000 Calculated from schedules 0.3384 24.5388 1.0000 1.0000 Not calculated 0.3384 0.0138    
AIRLOOP DATACENTER BOT 0.5854 0.0000 1.9486 1.0000 Calculated from schedules 0.0156 0.5854 1.0000 1.0000 Not calculated 0.0156 0.0267    
AIRLOOP DATACENTER MID 5.6297 0.0000 19.4861 1.0000 Calculated from schedules 0.1563 5.6297 1.0000 1.0000 Not calculated 0.1563 0.0278    
AIRLOOP DATACENTER TOP 0.5724 0.0000 1.9486 1.0000 Calculated from schedules 0.0156 0.5724 1.0000 1.0000 Not calculated 0.0156 0.0273    


Zone Ventilation Parameters

AirLoop Name People Outdoor Air Rate - Rp [m3/s-person] Zone Population - Pz Area Outdoor Air Rate - Ra [m3/s-m2] Zone Floor Area - Az [m2] Breathing Zone Outdoor Airflow - Vbz [m3/s] Cooling Zone Air Distribution Effectiveness - Ez-clg Cooling Zone Outdoor Airflow - Voz-clg [m3/s] Heating Zone Air Distribution Effectiveness - Ez-htg Heating Zone Outdoor Airflow - Voz-htg [m3/s]
BASEMENT CAV_BAS 0.000000 149.6021 0.000432 2779.43 1.2002 1.0000 1.2002 1.000 1.2002
CORE_BOTTOM VAV_BOT WITH REHEAT 0.000000 134.3532 0.000432 2496.12 0.0000 1.0000 0.0000 1.000 0.0000
CORE_MID VAV_MID WITH REHEAT 0.000000 1343.5320 0.000432 24961.20 0.0000 1.0000 0.0000 1.000 0.0000
CORE_TOP VAV_TOP WITH REHEAT 0.000000 134.3532 0.000432 2496.12 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_BOT_ZN_3 VAV_BOT WITH REHEAT 0.000000 16.8694 0.000432 313.41 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_BOT_ZN_2 VAV_BOT WITH REHEAT 0.000000 10.8713 0.000432 201.98 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_BOT_ZN_1 VAV_BOT WITH REHEAT 0.000000 16.8698 0.000432 313.42 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_BOT_ZN_4 VAV_BOT WITH REHEAT 0.000000 10.8713 0.000432 201.98 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_MID_ZN_3 VAV_MID WITH REHEAT 0.000000 168.6939 0.000432 3134.13 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_MID_ZN_2 VAV_MID WITH REHEAT 0.000000 108.7127 0.000432 2019.75 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_MID_ZN_1 VAV_MID WITH REHEAT 0.000000 168.6975 0.000432 3134.20 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_MID_ZN_4 VAV_MID WITH REHEAT 0.000000 108.7127 0.000432 2019.75 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_TOP_ZN_3 VAV_TOP WITH REHEAT 0.000000 16.8694 0.000432 313.41 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_TOP_ZN_2 VAV_TOP WITH REHEAT 0.000000 10.8713 0.000432 201.98 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_TOP_ZN_1 VAV_TOP WITH REHEAT 0.000000 16.8698 0.000432 313.42 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_TOP_ZN_4 VAV_TOP WITH REHEAT 0.000000 10.8713 0.000432 201.98 0.0000 1.0000 0.0000 1.000 0.0000
DATACENTER_BOT_ZN_6 AIRLOOP DATACENTER BOT 0.000000 1.9486 0.000432 36.20 0.0156 1.0000 0.0156 1.000 0.0156
DATACENTER_MID_ZN_6 AIRLOOP DATACENTER MID 0.000000 19.4861 0.000432 362.03 0.1563 1.0000 0.1563 1.000 0.1563
DATACENTER_TOP_ZN_6 AIRLOOP DATACENTER TOP 0.000000 1.9486 0.000432 36.20 0.0156 1.0000 0.0156 1.000 0.0156
DATACENTER_BASEMENT_ZN_6 AIRLOOP DATACENTER BASEMENT 0.000000 42.1814 0.000432 783.68 0.3384 1.0000 0.3384 1.000 0.3384


System Ventilation Parameters

People Outdoor Air Rate - Rp [m3/s-person] Sum of Zone Population - Pz-sum Area Outdoor Air Rate - Ra [m3/s-m2] Sum of Zone Floor Area - Az-sum [m2] Breathing Zone Outdoor Airflow - Vbz [m3/s] Cooling Zone Outdoor Airflow - Voz-clg [m3/s] Heating Zone Outdoor Airflow - Voz-htg [m3/s]
VAV_BOT WITH REHEAT   0.00 0.000432 3526.9033 0.0000 0.0000 0.0000
VAV_MID WITH REHEAT   0.00 0.000432 35269.0328 0.0000 0.0000 0.0000
VAV_TOP WITH REHEAT   0.00 0.000432 3526.9033 0.0000 0.0000 0.0000
CAV_BAS 0.000000 149.60 0.000432 2779.4266 1.2002 1.2002 1.2002
AIRLOOP DATACENTER BASEMENT 0.000000 42.18 0.000432 783.6794 0.3384 0.3384 0.3384
AIRLOOP DATACENTER BOT 0.000000 1.95 0.000432 36.2027 0.0156 0.0156 0.0156
AIRLOOP DATACENTER MID 0.000000 19.49 0.000432 362.0274 0.1563 0.1563 0.1563
AIRLOOP DATACENTER TOP 0.000000 1.95 0.000432 36.2027 0.0156 0.0156 0.0156


Zone Ventilation Calculations for Cooling Design

AirLoop Name Box Type Zone Primary Airflow - Vpz [m3/s] Zone Discharge Airflow - Vdz [m3/s] Minimum Zone Primary Airflow - Vpz-min [m3/s] Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? Zone Outdoor Airflow Cooling - Voz-clg [m3/s] Primary Outdoor Air Fraction - Zpz Primary Air Fraction - Ep Secondary Recirculation Fraction- Er Supply Air Fraction- Fa Mixed Air Fraction - Fb Outdoor Air Fraction - Fc Zone Ventilation Efficiency - Evz
BASEMENT CAV_BAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 6.8191 6.8191 6.8191 No 1.2002 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CORE_BOTTOM VAV_BOT WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 7.0643 7.0643 2.0345 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CORE_MID VAV_MID WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 66.5266 66.5266 19.8915 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CORE_TOP VAV_TOP WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 6.4354 6.4354 2.0593 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_BOT_ZN_3 VAV_BOT WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.1969 1.1969 0.2549 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_BOT_ZN_2 VAV_BOT WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.6226 1.6226 0.3245 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_BOT_ZN_1 VAV_BOT WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 2.0083 2.0083 0.4017 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_BOT_ZN_4 VAV_BOT WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.9899 1.9899 0.3980 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_MID_ZN_3 VAV_MID WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 11.3989 11.3989 2.4963 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_MID_ZN_2 VAV_MID WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 17.3102 17.3102 3.4620 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_MID_ZN_1 VAV_MID WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 20.5161 20.5161 4.1032 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_MID_ZN_4 VAV_MID WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 18.7171 18.7171 3.7434 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_TOP_ZN_3 VAV_TOP WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.3145 1.3145 0.2655 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_TOP_ZN_2 VAV_TOP WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.7310 1.7310 0.3462 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_TOP_ZN_1 VAV_TOP WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 2.1859 2.1859 0.4372 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_TOP_ZN_4 VAV_TOP WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.9658 1.9658 0.3932 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
DATACENTER_BOT_ZN_6 AIRLOOP DATACENTER BOT AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.5854 0.5854 0.5854 No 0.0156 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
DATACENTER_MID_ZN_6 AIRLOOP DATACENTER MID AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 5.6297 5.6297 5.6297 No 0.1563 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
DATACENTER_TOP_ZN_6 AIRLOOP DATACENTER TOP AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.5724 0.5724 0.5724 No 0.0156 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
DATACENTER_BASEMENT_ZN_6 AIRLOOP DATACENTER BASEMENT AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 24.5388 24.5388 24.5388 No 0.3384 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000


System Ventilation Calculations for Cooling Design

Sum of Zone Primary Airflow - Vpz-sum [m3/s] System Primary Airflow - Vps [m3/s] Sum of Zone Discharge Airflow - Vdz-sum [m3/s] Sum of Min Zone Primary Airflow - Vpz-min [m3/s] Zone Outdoor Airflow Cooling - Voz-clg [m3/s] Zone Ventilation Efficiency - Evz-min
VAV_BOT WITH REHEAT 13.8821 11.6557 13.8821 3.4136 0.0000 1.0000
VAV_MID WITH REHEAT 134.4688 107.8319 134.4688 33.6965 0.0000 1.0000
VAV_TOP WITH REHEAT 13.6326 12.3008 13.6326 3.5014 0.0000 1.0000
CAV_BAS 6.8191 6.8191 6.8191 6.8191 1.2002 1.0000
AIRLOOP DATACENTER BASEMENT 24.5388 24.5389 24.5388 24.5388 0.3384 1.0000
AIRLOOP DATACENTER BOT 0.5854 0.5854 0.5854 0.5854 0.0156 1.0000
AIRLOOP DATACENTER MID 5.6297 5.6297 5.6297 5.6297 0.1563 1.0000
AIRLOOP DATACENTER TOP 0.5724 0.5724 0.5724 0.5724 0.0156 1.0000


Zone Ventilation Calculations for Heating Design

AirLoop Name Box Type Zone Primary Airflow - Vpz [m3/s] Zone Discharge Airflow - Vdz [m3/s] Minimum Zone Primary Airflow - Vpz-min [m3/s] Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? Zone Outdoor Airflow Heating - Voz-htg [m3/s] Primary Outdoor Air Fraction - Zpz Primary Air Fraction - Ep Secondary Recirculation Fraction- Er Supply Air Fraction- Fa Mixed Air Fraction - Fb Outdoor Air Fraction - Fc Zone Ventilation Efficiency - Evz
BASEMENT CAV_BAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 6.8191 6.8191 6.8191 No 1.2002 1.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CORE_BOTTOM VAV_BOT WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 3.5321 3.5321 2.0345 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CORE_MID VAV_MID WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 33.2633 33.2633 19.8915 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CORE_TOP VAV_TOP WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 3.2177 3.2177 2.0593 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_BOT_ZN_3 VAV_BOT WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.5985 0.5985 0.2549 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_BOT_ZN_2 VAV_BOT WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.8113 0.8113 0.3245 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_BOT_ZN_1 VAV_BOT WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.0042 1.0042 0.4017 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_BOT_ZN_4 VAV_BOT WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.9950 0.9950 0.3980 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_MID_ZN_3 VAV_MID WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 5.6994 5.6994 2.4963 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_MID_ZN_2 VAV_MID WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 8.6551 8.6551 3.4620 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_MID_ZN_1 VAV_MID WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 10.2580 10.2580 4.1032 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_MID_ZN_4 VAV_MID WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 9.3585 9.3585 3.7434 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_TOP_ZN_3 VAV_TOP WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.6573 0.6573 0.2655 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_TOP_ZN_2 VAV_TOP WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.8655 0.8655 0.3462 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_TOP_ZN_1 VAV_TOP WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.0929 1.0929 0.4372 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_TOP_ZN_4 VAV_TOP WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.9829 0.9829 0.3932 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
DATACENTER_BOT_ZN_6 AIRLOOP DATACENTER BOT AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.5854 0.5854 0.5854 No 0.0156 1.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
DATACENTER_MID_ZN_6 AIRLOOP DATACENTER MID AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 5.6297 5.6297 5.6297 No 0.1563 1.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
DATACENTER_TOP_ZN_6 AIRLOOP DATACENTER TOP AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.5724 0.5724 0.5724 No 0.0156 1.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
DATACENTER_BASEMENT_ZN_6 AIRLOOP DATACENTER BASEMENT AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 24.5388 24.5388 24.5388 No 0.3384 1.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000


System Ventilation Calculations for Heating Design

Sum of Zone Primary Airflow - Vpz-sum [m3/s] System Primary Airflow - Vps [m3/s] Sum of Zone Discharge Airflow - Vdz-sum [m3/s] Sum of Min Zone Primary Airflow - Vpz-min [m3/s] Zone Outdoor Airflow Heating - Voz-htg [m3/s] Zone Ventilation Efficiency - Evz-min
VAV_BOT WITH REHEAT 6.9410 3.4136 3.4136 3.4136 0.0000 1.0000
VAV_MID WITH REHEAT 67.2344 33.6965 33.6965 33.6965 0.0000 1.0000
VAV_TOP WITH REHEAT 6.8163 3.5014 3.5014 3.5014 0.0000 1.0000
CAV_BAS 6.8191 6.8191 6.8191 6.8191 1.2002 1.0000
AIRLOOP DATACENTER BASEMENT 24.5388 24.5388 24.5388 24.5388 0.3384 1.0000
AIRLOOP DATACENTER BOT 0.5854 0.5854 0.5854 0.5854 0.0156 1.0000
AIRLOOP DATACENTER MID 5.6297 5.6297 5.6297 5.6297 0.1563 1.0000
AIRLOOP DATACENTER TOP 0.5724 0.5724 0.5724 0.5724 0.0156 1.0000



Table of Contents

Report: LEED Summary

For: Entire Facility

Timestamp: 2023-10-16 08:43:39

Sec1.1A-General Information

Data
Weather File RUNPERIOD 1 ** Great Falls Intl Arpt MT USA TMY3 WMO#=727750
Total gross floor area [m2] 46320.38
Principal Heating Source Natural Gas


EAp2-1. Space Usage Type

Space Area [m2] Regularly Occupied Area [m2] Unconditioned Area [m2] Typical Hours/Week in Operation [hr/wk]
BASEMENT 2779.43 2779.43 0.00 113.98
CORE_BOTTOM 2496.12 2496.12 0.00 113.98
CORE_MID 2496.12 2496.12 0.00 113.98
CORE_TOP 2496.12 2496.12 0.00 113.98
PERIMETER_BOT_ZN_3 313.41 313.41 0.00 113.98
PERIMETER_BOT_ZN_2 201.98 201.98 0.00 113.98
PERIMETER_BOT_ZN_1 313.42 313.42 0.00 113.98
PERIMETER_BOT_ZN_4 201.98 201.98 0.00 113.98
PERIMETER_MID_ZN_3 313.41 313.41 0.00 113.98
PERIMETER_MID_ZN_2 201.98 201.98 0.00 96.54
PERIMETER_MID_ZN_1 313.42 313.42 0.00 113.98
PERIMETER_MID_ZN_4 201.98 201.98 0.00 113.98
PERIMETER_TOP_ZN_3 313.41 313.41 0.00 113.98
PERIMETER_TOP_ZN_2 201.98 201.98 0.00 113.98
PERIMETER_TOP_ZN_1 313.42 313.42 0.00 113.98
PERIMETER_TOP_ZN_4 201.98 201.98 0.00 113.98
DATACENTER_BOT_ZN_6 36.20 36.20 0.00 113.98
DATACENTER_MID_ZN_6 36.20 36.20 0.00 113.98
DATACENTER_TOP_ZN_6 36.20 36.20 0.00 113.98
DATACENTER_BASEMENT_ZN_6 783.68 783.68 0.00 113.98
GROUNDFLOOR_PLENUM 3563.11 3563.11 0.00 0.00
MIDFLOOR_PLENUM 3563.11 3563.11 0.00 0.00
TOPFLOOR_PLENUM 3563.11 3563.11 0.00 0.00
Totals 46320.38 46320.38 0.00  


EAp2-2. Advisory Messages

Data
Number of hours heating loads not met 133.17
Number of hours cooling loads not met 247.83
Number of hours not met 381.00


EAp2-3. Energy Type Summary

Utility Rate Virtual Rate [$/unit energy] Units of Energy Units of Demand
None        


EAp2-4/5. Performance Rating Method Compliance

Electricity Energy Use [GJ] Electricity Demand [W] Natural Gas Energy Use [GJ] Natural Gas Demand [W] Gasoline Use [GJ] Gasoline Demand [W] Diesel Use [GJ] Diesel Demand [W] Coal Use [GJ] Coal Demand [W] Fuel Oil No 1 Use [GJ] Fuel Oil No 1 Demand [W] Fuel Oil No 2 Use [GJ] Fuel Oil No 2 Demand [W] Propane Use [GJ] Propane Demand [W] Other Fuel 1 Use [GJ] Other Fuel 1 Demand [W] Other Fuel 2 Use [GJ] Other Fuel 2 Demand [W] District Cooling Use [GJ] District Cooling Demand [W] District Heating Use [GJ] District Heating Demand [W]
Heating -- General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heating -- Boiler 0.00 0.00 3610.86 2431734.33 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heating -- Boiler Parasitic 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling -- General 1480.31 448448.23 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting -- LightsWired 3933.41 385834.94 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting -- General 696.47 57580.60 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- MiscPlug 5334.97 305206.10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- DataCenterPlugLoads 9341.42 473165.59 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment -- Transformer 80.18 5057.48 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment -- ElevatorLift 1848.78 113101.96 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment -- ElevatorLightsFan 5.83 376.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans -- General 2717.83 358305.73 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps -- General 326.28 48286.92 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection -- General 437.48 83553.24 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification -- General 2435.06 100000.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery -- Not Subdivided 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems -- General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems -- WaterUse 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems -- Water Heater 0.00 0.00 848.37 87976.46 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration -- Not Subdivided 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators -- General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


EAp2-6. Energy Use Summary

Process Subtotal [GJ] Total Energy Use [GJ]
Electricity 14676.40 28638.04
Natural Gas 0.00 4459.24
Additional 0.00 0.00
Total 14676.40 33097.28


EAp2-7. Energy Cost Summary

Process Subtotal [$] Total Energy Cost [$]
Electricity 0.00  
Natural Gas 0.00  
Additional 0.00  
Total 0.00  
Process energy cost based on ratio of process to total energy.

L-1. Renewable Energy Source Summary

Rated Capacity [kW] Annual Energy Generated [GJ]
Photovoltaic 0.00 0.00
Wind 0.00 0.00


EAp2-17a. Energy Use Intensity - Electricity

Electricty [MJ/m2]
Interior Lighting (All) 84.92
Space Heating 0.00
Space Cooling 31.96
Fans (All) 58.67
Service Water Heating 0.00
Receptacle Equipment 316.85
Miscellaneous (All) 618.26
Subtotal 618.26


EAp2-17b. Energy Use Intensity - Natural Gas

Natural Gas [MJ/m2]
Space Heating 77.95
Service Water Heating 18.32
Miscellaneous (All) 96.27
Subtotal 96.27


EAp2-17c. Energy Use Intensity - Additional

Additional [MJ/m2]
Subtotal 0.00
Miscellaneous 0.00


EAp2-18. End Use Percentage

Percent [%]
Interior Lighting (All) 11.88
Space Heating 10.91
Space Cooling 4.47
Fans (All) 8.21
Service Water Heating 2.56
Receptacle Equipment 44.34
Miscellaneous 17.62


Schedules-Equivalent Full Load Hours (Schedule Type=Fraction)

Equivalent Full Load Hours of Operation Per Year [hr] Hours > 1% [hr]
EXTERIOR_LIGHTING_SCHEDULE_A 6570. 6570.
EXTERIOR_LIGHTING_SCHEDULE_B 8103. 8760.
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 4472. 4472.
EXTERIOR_LIGHTING_SCHEDULE_B_2016 7665. 8760.
EXTERIOR_LIGHTING_SCHEDULE_C_2016 6752. 8760.
ALWAYS_ON 8760. 8760.
EXTERIOR_LGT_ALWAYS_ON 8760. 8760.
EXTERIOR_LGT_189_1 6828. 8760.
ALWAYS_OFF 0. 0.
LTG_SCH_OFFICE 2625. 8760.
LTG_SCH_DATACENTER 2921. 8760.
EXTERIOR_LIGHT_SCH 4380. 4380.
BLDG_EQUIP_SCH 4049. 8760.
DATACENTER_EQUIP_SCH 5478. 8760.
BLDG_OCC_SCH 2528. 5992.
BLDG_OCC_SCH_W_SB 1878. 5056.
BLDG_OCC_SCH_WO_SB 2557. 5992.
BLDG_ELEVATORS 2270. 8760.
ELEV_LIGHT_FAN_SCH_24_7 8760. 8760.
ELEV_LIGHT_FAN_SCH_ADD_DF 2154. 8760.
BLDG_SWH_SCH 1474. 6570.
WORK_EFF_SCH 0. 0.
INFIL_SCH 3976. 3976.
INFIL_SCH_PNNL 5172. 8760.
INFIL_HALF_ON_SCH 6368. 8760.
FAN_SCH 8760. 8760.
REHEATCOILAVAILSCHED 8760. 8760.
COOLINGCOILAVAILSCHED 8760. 8760.
MINOA_MOTORIZEDDAMPER_SCHED 4472. 4472.
MINOA_SCHED 8760. 8760.
CORE_BOTTOM SUB CAT LATENT FRACT SCHED 438. 8760.
CORE_BOTTOM SUB CAT SENSIBLE FRACT SCHED 1752. 8760.
CORE_MID SUB CAT LATENT FRACT SCHED 438. 8760.
CORE_MID SUB CAT SENSIBLE FRACT SCHED 1752. 8760.
CORE_TOP SUB CAT LATENT FRACT SCHED 438. 8760.
CORE_TOP SUB CAT SENSIBLE FRACT SCHED 1752. 8760.
SUPPLYFANSCH 8760. 8760.
PERIMETER_MID_ZN_2_MDP_SCH 1565. 7824.


Schedules-SetPoints (Schedule Type=Temperature)

First Object Used Month Assumed 11am First Wednesday [C] Days with Same 11am Value 11pm First Wednesday [C] Days with Same 11pm Value
HTGSETP_DC_SCH DATACENTER COOLING SETPOINTS DUAL SP CONTROL January 18.00 365 18.00 365
CLGSETP_DC_SCH DATACENTER COOLING SETPOINTS DUAL SP CONTROL July 27.00 365 27.00 365
HTGSETP_SCH_YES_OPTIMUM CORE_BOTTOM DUAL SP CONTROL January 21.00 365 15.60 365
CLGSETP_SCH_YES_OPTIMUM CORE_BOTTOM DUAL SP CONTROL July 24.00 365 26.70 365



Table of Contents

Report: Annual Thermal Resilience Summary

For: Entire Facility

Timestamp: 2023-10-16 08:43:39

Heat Index Hours

Safe (≤ 26.7°C) [hr] Caution (> 26.7, ≤ 32.2°C) [hr] Extreme Caution (> 32.2, ≤ 39.4°C) [hr] Danger (> 39.4, ≤ 51.7°C) [hr] Extreme Danger (> 51.7°C) [hr]
BASEMENT 8722.00 38.00 0.00 0.00 0.00
CORE_BOTTOM 8755.50 4.50 0.00 0.00 0.00
CORE_MID 8760.00 0.00 0.00 0.00 0.00
CORE_TOP 8760.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_3 8757.67 2.33 0.00 0.00 0.00
PERIMETER_BOT_ZN_2 8735.67 24.33 0.00 0.00 0.00
PERIMETER_BOT_ZN_1 8729.50 30.50 0.00 0.00 0.00
PERIMETER_BOT_ZN_4 8683.83 76.17 0.00 0.00 0.00
PERIMETER_MID_ZN_3 8758.00 2.00 0.00 0.00 0.00
PERIMETER_MID_ZN_2 8733.17 26.83 0.00 0.00 0.00
PERIMETER_MID_ZN_1 8729.17 30.83 0.00 0.00 0.00
PERIMETER_MID_ZN_4 8728.00 32.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_3 8757.00 3.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_2 8734.33 25.67 0.00 0.00 0.00
PERIMETER_TOP_ZN_1 8733.00 27.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_4 8730.33 29.67 0.00 0.00 0.00
DATACENTER_BOT_ZN_6 8752.67 7.33 0.00 0.00 0.00
DATACENTER_MID_ZN_6 8756.17 3.83 0.00 0.00 0.00
DATACENTER_TOP_ZN_6 8754.50 5.50 0.00 0.00 0.00
DATACENTER_BASEMENT_ZN_6 8504.33 250.50 5.17 0.00 0.00
GROUNDFLOOR_PLENUM 8760.00 0.00 0.00 0.00 0.00
MIDFLOOR_PLENUM 8760.00 0.00 0.00 0.00 0.00
TOPFLOOR_PLENUM 8736.17 23.83 0.00 0.00 0.00
Min 8504.33 0.00 0.00 0.00 0.00
Max 8760.00 250.50 5.17 0.00 0.00
Average 8731.78 27.99 0.22 0.00 0.00
Sum 200831.00 643.83 5.17 0.00 0.00


Heat Index OccupantHours

Safe (≤ 26.7°C) [hr] Caution (> 26.7, ≤ 32.2°C) [hr] Extreme Caution (> 32.2, ≤ 39.4°C) [hr] Danger (> 39.4, ≤ 51.7°C) [hr] Extreme Danger (> 51.7°C) [hr]
BASEMENT 368421.17 194.83 0.00 0.00 0.00
CORE_BOTTOM 330790.00 23.00 0.00 0.00 0.00
CORE_MID 330813.00 0.00 0.00 0.00 0.00
CORE_TOP 330813.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_3 38925.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_2 24909.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_1 38925.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_4 24909.00 0.00 0.00 0.00 0.00
PERIMETER_MID_ZN_3 38925.00 0.00 0.00 0.00 0.00
PERIMETER_MID_ZN_2 18354.00 0.00 0.00 0.00 0.00
PERIMETER_MID_ZN_1 38925.00 0.00 0.00 0.00 0.00
PERIMETER_MID_ZN_4 24909.00 0.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_3 38925.00 0.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_2 24909.00 0.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_1 38925.00 0.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_4 24909.00 0.00 0.00 0.00 0.00
DATACENTER_BOT_ZN_6 2268.00 0.00 0.00 0.00 0.00
DATACENTER_MID_ZN_6 2268.00 0.00 0.00 0.00 0.00
DATACENTER_TOP_ZN_6 2268.00 0.00 0.00 0.00 0.00
DATACENTER_BASEMENT_ZN_6 99788.83 3584.50 21.67 0.00 0.00
GROUNDFLOOR_PLENUM 0.00 0.00 0.00 0.00 0.00
MIDFLOOR_PLENUM 0.00 0.00 0.00 0.00 0.00
TOPFLOOR_PLENUM 0.00 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00 0.00
Max 368421.17 3584.50 21.67 0.00 0.00
Average 80168.65 165.32 0.94 0.00 0.00
Sum 1843879.00 3802.33 21.67 0.00 0.00


Humidex Hours

Little to no Discomfort (≤ 29) [hr] Some Discomfort (> 29, ≤ 40) [hr] Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] Dangerous (> 45, ≤ 50) [hr] Heat Stroke Quite Possible (> 50) [hr]
BASEMENT 8690.67 69.33 0.00 0.00 0.00
CORE_BOTTOM 8720.67 39.33 0.00 0.00 0.00
CORE_MID 8717.00 43.00 0.00 0.00 0.00
CORE_TOP 8734.83 25.17 0.00 0.00 0.00
PERIMETER_BOT_ZN_3 8747.00 13.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_2 8745.50 14.50 0.00 0.00 0.00
PERIMETER_BOT_ZN_1 8739.50 20.50 0.00 0.00 0.00
PERIMETER_BOT_ZN_4 8696.33 63.67 0.00 0.00 0.00
PERIMETER_MID_ZN_3 8747.83 12.17 0.00 0.00 0.00
PERIMETER_MID_ZN_2 8735.67 24.33 0.00 0.00 0.00
PERIMETER_MID_ZN_1 8737.33 22.67 0.00 0.00 0.00
PERIMETER_MID_ZN_4 8730.17 29.83 0.00 0.00 0.00
PERIMETER_TOP_ZN_3 8748.50 11.50 0.00 0.00 0.00
PERIMETER_TOP_ZN_2 8737.67 22.33 0.00 0.00 0.00
PERIMETER_TOP_ZN_1 8740.17 19.83 0.00 0.00 0.00
PERIMETER_TOP_ZN_4 8732.33 27.67 0.00 0.00 0.00
DATACENTER_BOT_ZN_6 8760.00 0.00 0.00 0.00 0.00
DATACENTER_MID_ZN_6 8760.00 0.00 0.00 0.00 0.00
DATACENTER_TOP_ZN_6 8760.00 0.00 0.00 0.00 0.00
DATACENTER_BASEMENT_ZN_6 8563.17 196.83 0.00 0.00 0.00
GROUNDFLOOR_PLENUM 8742.67 17.33 0.00 0.00 0.00
MIDFLOOR_PLENUM 8750.83 9.17 0.00 0.00 0.00
TOPFLOOR_PLENUM 8724.00 36.00 0.00 0.00 0.00
Min 8563.17 0.00 0.00 0.00 0.00
Max 8760.00 196.83 0.00 0.00 0.00
Average 8728.78 31.22 0.00 0.00 0.00
Sum 200761.83 718.17 0.00 0.00 0.00


Humidex OccupantHours

Little to no Discomfort (≤ 29) [hr] Some Discomfort (> 29, ≤ 40) [hr] Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] Dangerous (> 45, ≤ 50) [hr] Heat Stroke Quite Possible (> 50) [hr]
BASEMENT 368333.00 283.00 0.00 0.00 0.00
CORE_BOTTOM 330729.00 84.00 0.00 0.00 0.00
CORE_MID 330709.00 104.00 0.00 0.00 0.00
CORE_TOP 330761.00 52.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_3 38925.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_2 24909.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_1 38925.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_4 24909.00 0.00 0.00 0.00 0.00
PERIMETER_MID_ZN_3 38925.00 0.00 0.00 0.00 0.00
PERIMETER_MID_ZN_2 18354.00 0.00 0.00 0.00 0.00
PERIMETER_MID_ZN_1 38925.00 0.00 0.00 0.00 0.00
PERIMETER_MID_ZN_4 24909.00 0.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_3 38925.00 0.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_2 24909.00 0.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_1 38925.00 0.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_4 24909.00 0.00 0.00 0.00 0.00
DATACENTER_BOT_ZN_6 2268.00 0.00 0.00 0.00 0.00
DATACENTER_MID_ZN_6 2268.00 0.00 0.00 0.00 0.00
DATACENTER_TOP_ZN_6 2268.00 0.00 0.00 0.00 0.00
DATACENTER_BASEMENT_ZN_6 100532.83 2862.17 0.00 0.00 0.00
GROUNDFLOOR_PLENUM 0.00 0.00 0.00 0.00 0.00
MIDFLOOR_PLENUM 0.00 0.00 0.00 0.00 0.00
TOPFLOOR_PLENUM 0.00 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00 0.00
Max 368333.00 2862.17 0.00 0.00 0.00
Average 80187.73 147.18 0.00 0.00 0.00
Sum 1844317.83 3385.17 0.00 0.00 0.00


Heating SET Hours

SET ≤ 12.2°C Hours (°C) SET ≤ 12.2°C OccupantHours (°C) Longest SET ≤ 12.2°C Duration [hr] Start Time of the Longest SET ≤ 12.2°C Duration
None        


Cooling SET Hours

SET > 30°C Hours (°C) SET > 30°C OccupantHours (°C) Longest SET > 30°C Duration [hr] Start Time of the Longest SET > 30°C Duration
None        



Table of Contents

Report: Annual CO2 Resilience Summary

For: Entire Facility

Timestamp: 2023-10-16 08:43:39

CO2 Level Hours

Safe (<= 1000 ppm) [hr] Caution (> 1000, <= 5000 ppm) [hr] Hazard (> 5000 ppm) [hr]
None      


CO2 Level OccupantHours

Safe (<= 1000 ppm) [hr] Caution (> 1000, <= 5000 ppm) [hr] Hazard (> 5000 ppm) [hr]
None      



Table of Contents

Report: Annual Visual Resilience Summary

For: Entire Facility

Timestamp: 2023-10-16 08:43:39

Illuminance Level Hours

A Bit Dark (<= 100 lux) [hr] Dim (> 100, <= 300 lux) [hr] Adequate (> 300, <= 500 lux) [hr] Bright (>500 lux) [hr]
BASEMENT 0.00 0.00 0.00 0.00
CORE_BOTTOM 0.00 0.00 0.00 0.00
CORE_MID 0.00 0.00 0.00 0.00
CORE_TOP 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_3 0.00 0.00 8760.00 0.00
PERIMETER_BOT_ZN_2 0.00 0.00 8760.00 0.00
PERIMETER_BOT_ZN_1 0.00 0.00 8760.00 0.00
PERIMETER_BOT_ZN_4 0.00 0.00 8760.00 0.00
PERIMETER_MID_ZN_3 0.00 0.00 8760.00 0.00
PERIMETER_MID_ZN_2 0.00 0.00 8760.00 0.00
PERIMETER_MID_ZN_1 0.00 0.00 8760.00 0.00
PERIMETER_MID_ZN_4 0.00 0.00 8760.00 0.00
PERIMETER_TOP_ZN_3 0.00 0.00 8760.00 0.00
PERIMETER_TOP_ZN_2 0.00 0.00 8760.00 0.00
PERIMETER_TOP_ZN_1 0.00 0.00 8760.00 0.00
PERIMETER_TOP_ZN_4 0.00 0.00 8760.00 0.00
DATACENTER_BOT_ZN_6 0.00 0.00 0.00 0.00
DATACENTER_MID_ZN_6 0.00 0.00 0.00 0.00
DATACENTER_TOP_ZN_6 0.00 0.00 0.00 0.00
DATACENTER_BASEMENT_ZN_6 0.00 0.00 0.00 0.00
GROUNDFLOOR_PLENUM 0.00 0.00 0.00 0.00
MIDFLOOR_PLENUM 0.00 0.00 0.00 0.00
TOPFLOOR_PLENUM 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00
Max 0.00 0.00 8760.00 0.00
Average 0.00 0.00 4570.43 0.00
Sum 0.00 0.00 105120.00 0.00


Illuminance Level OccupantHours

A Bit Dark (<= 100 lux) [hr] Dim (> 100, <= 300 lux) [hr] Adequate (> 300, <= 500 lux) [hr] Bright (>500 lux) [hr]
BASEMENT 0.00 0.00 0.00 0.00
CORE_BOTTOM 0.00 0.00 0.00 0.00
CORE_MID 0.00 0.00 0.00 0.00
CORE_TOP 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_3 0.00 0.00 38925.00 0.00
PERIMETER_BOT_ZN_2 0.00 0.00 24909.00 0.00
PERIMETER_BOT_ZN_1 0.00 0.00 38925.00 0.00
PERIMETER_BOT_ZN_4 0.00 0.00 24909.00 0.00
PERIMETER_MID_ZN_3 0.00 0.00 38925.00 0.00
PERIMETER_MID_ZN_2 0.00 0.00 18354.00 0.00
PERIMETER_MID_ZN_1 0.00 0.00 38925.00 0.00
PERIMETER_MID_ZN_4 0.00 0.00 24909.00 0.00
PERIMETER_TOP_ZN_3 0.00 0.00 38925.00 0.00
PERIMETER_TOP_ZN_2 0.00 0.00 24909.00 0.00
PERIMETER_TOP_ZN_1 0.00 0.00 38925.00 0.00
PERIMETER_TOP_ZN_4 0.00 0.00 24909.00 0.00
DATACENTER_BOT_ZN_6 0.00 0.00 0.00 0.00
DATACENTER_MID_ZN_6 0.00 0.00 0.00 0.00
DATACENTER_TOP_ZN_6 0.00 0.00 0.00 0.00
DATACENTER_BASEMENT_ZN_6 0.00 0.00 0.00 0.00
GROUNDFLOOR_PLENUM 0.00 0.00 0.00 0.00
MIDFLOOR_PLENUM 0.00 0.00 0.00 0.00
TOPFLOOR_PLENUM 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00
Max 0.00 0.00 38925.00 0.00
Average 0.00 0.00 16367.35 0.00
Sum 0.00 0.00 376449.00 0.00



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR

For: Environment

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January -8.80
February -2.17
March 0.301
April 6.668
May 10.099
June 16.456
July 20.571
August 19.174
September 14.689
October 8.635
November 2.839
December -4.07
   
Annual Sum or Average 7.074
Minimum of Months -8.80
Maximum of Months 20.571



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901

For: Environment

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January -8.80
February -2.17
March 0.301
April 6.668
May 10.099
June 16.456
July 20.571
August 19.174
September 14.689
October 8.635
November 2.839
December -4.07
   
Annual Sum or Average 7.074
Minimum of Months -8.80
Maximum of Months 20.571



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2013

For: Environment

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January -8.80
February -2.17
March 0.301
April 6.668
May 10.099
June 16.456
July 20.571
August 19.174
September 14.689
October 8.635
November 2.839
December -4.07
   
Annual Sum or Average 7.074
Minimum of Months -8.80
Maximum of Months 20.571



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND

For: Environment

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January -8.80
February -2.17
March 0.301
April 6.668
May 10.099
June 16.456
July 20.571
August 19.174
September 14.689
October 8.635
November 2.839
December -4.07
   
Annual Sum or Average 7.074
Minimum of Months -8.80
Maximum of Months 20.571



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICELARGE

For: Environment

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January -8.80
February -2.17
March 0.301
April 6.668
May 10.099
June 16.456
July 20.571
August 19.174
September 14.689
October 8.635
November 2.839
December -4.07
   
Annual Sum or Average 7.074
Minimum of Months -8.80
Maximum of Months 20.571



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL

For: Environment

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January -8.80
February -2.17
March 0.301
April 6.668
May 10.099
June 16.456
July 20.571
August 19.174
September 14.689
October 8.635
November 2.839
December -4.07
   
Annual Sum or Average 7.074
Minimum of Months -8.80
Maximum of Months 20.571



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL

For: Environment

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January -8.80
February -2.17
March 0.301
April 6.668
May 10.099
June 16.456
July 20.571
August 19.174
September 14.689
October 8.635
November 2.839
December -4.07
   
Annual Sum or Average 7.074
Minimum of Months -8.80
Maximum of Months 20.571



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 6B

For: Environment

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January -8.80
February -2.17
March 0.301
April 6.668
May 10.099
June 16.456
July 20.571
August 19.174
September 14.689
October 8.635
November 2.839
December -4.07
   
Annual Sum or Average 7.074
Minimum of Months -8.80
Maximum of Months 20.571



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_MT_GREATFALLS

For: Environment

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January -8.80
February -2.17
March 0.301
April 6.668
May 10.099
June 16.456
July 20.571
August 19.174
September 14.689
October 8.635
November 2.839
December -4.07
   
Annual Sum or Average 7.074
Minimum of Months -8.80
Maximum of Months 20.571



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: BASEMENT

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.491806E+11 119041.38 02-JAN-04:01 -0.5 -3.0 0.536735E+10 7499.19 12-JAN-10:09 6.78 3.19
February 0.448930E+11 119260.94 21-FEB-05:11 7.43 1.21 0.506392E+10 7499.23 06-FEB-10:20 7.43 1.21
March 0.562676E+11 115710.20 20-MAR-03:01 -1.6 -3.4 0.611862E+10 7499.16 06-MAR-10:39 -1.6 -3.4
April 0.544616E+11 120077.72 10-APR-04:11 4.23 0.21 0.544715E+10 7499.14 04-APR-09:09 4.23 0.21
May 0.573161E+11 119032.90 22-MAY-03:02 0.50 0.24 0.590084E+10 7499.77 02-MAY-13:20 0.50 0.24
June 0.622210E+11 118166.47 12-JUN-04:12 11.70 10.91 0.588224E+10 7499.11 20-JUN-13:20 27.77 18.21
July 0.647059E+11 122563.24 02-JUL-17:45 25.60 14.12 0.547499E+10 7499.22 03-JUL-13:09 19.07 14.10
August 0.711737E+11 119010.41 14-AUG-04:12 12.20 9.88 0.613846E+10 7499.15 24-AUG-13:30 27.20 14.80
September 0.612689E+11 122345.05 03-SEP-13:58 33.90 16.29 0.545281E+10 7499.35 07-SEP-09:00 16.70 15.61
October 0.620735E+11 121499.44 02-OCT-04:11 4.80 2.84 0.567044E+10 7499.21 18-OCT-13:39 24.80 11.21
November 0.572166E+11 120348.34 13-NOV-04:01 -6.2 -8.4 0.561303E+10 7499.07 03-NOV-09:09 -6.2 -8.4
December 0.544851E+11 117716.13 11-DEC-04:01 -2.6 -4.7 0.541548E+10 7499.18 07-DEC-10:20 -2.6 -4.7
                     
Annual Sum or Average 0.695264E+12         0.675453E+11        
Minimum of Months 0.448930E+11 115710.20   -6.2 -8.4 0.506392E+10 7499.07   -6.2 -8.4
Maximum of Months 0.711737E+11 122563.24   33.90 16.29 0.613846E+10 7499.77   27.77 18.21



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: CORE_BOTTOM

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.329882E+11 89272.35 02-JAN-05:01 -0.2 -2.7 0.495168E+10 6734.76 02-JAN-10:09 2.48 -0.4
February 0.351318E+11 90639.00 27-FEB-05:11 4.07 0.00 0.457262E+10 6734.76 23-FEB-10:39 4.07 0.00
March 0.486303E+11 90600.84 02-MAR-05:11 4.03 0.28 0.549166E+10 6734.76 01-MAR-10:09 4.03 0.28
April 0.526411E+11 98180.20 10-APR-04:11 4.23 0.21 0.488349E+10 6734.78 04-APR-09:09 4.23 0.21
May 0.499936E+11 97307.20 30-MAY-04:12 15.60 10.93 0.528915E+10 6735.17 02-MAY-13:09 15.60 10.93
June 0.604146E+11 96816.16 12-JUN-04:12 11.70 10.91 0.526928E+10 6734.78 20-JUN-09:00 21.10 12.64
July 0.664230E+11 100012.37 05-JUL-04:12 9.40 8.79 0.489782E+10 6734.97 03-JUL-13:09 9.40 8.79
August 0.732032E+11 98499.05 28-AUG-04:12 8.67 4.95 0.549786E+10 6734.80 01-AUG-13:09 8.67 4.95
September 0.524812E+11 102165.59 05-SEP-04:13 18.30 11.92 0.488214E+10 6735.18 07-SEP-09:00 16.70 15.61
October 0.503805E+11 96555.60 02-OCT-04:11 4.80 2.84 0.507897E+10 6734.75 18-OCT-13:39 24.80 11.21
November 0.458886E+11 94278.43 06-NOV-04:02 -2.8 -3.9 0.502697E+10 6734.75 03-NOV-09:09 -2.8 -3.9
December 0.423451E+11 90293.88 11-DEC-05:01 -1.6 -4.2 0.488653E+10 6734.81 07-DEC-10:20 -1.6 -4.2
                     
Annual Sum or Average 0.610521E+12         0.607282E+11        
Minimum of Months 0.329882E+11 89272.35   -2.8 -4.2 0.457262E+10 6734.75   -2.8 -4.2
Maximum of Months 0.732032E+11 102165.59   18.30 11.92 0.549786E+10 6735.18   24.80 15.61



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: CORE_MID

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.231322E+11 21440.08 19-JAN-16:57 -6.7 -8.2 0.445151E+10 6734.47 19-JAN-14:00 -6.7 -8.2
February 0.234199E+11 33650.96 28-FEB-17:00 10.00 4.31 0.428378E+10 6734.74 28-FEB-10:09 10.00 4.31
March 0.316579E+11 54523.91 24-MAR-05:03 -0.6 -2.5 0.531802E+10 6734.76 01-MAR-10:09 -0.6 -2.5
April 0.335799E+11 82168.51 26-APR-05:02 5.37 2.97 0.482557E+10 6734.75 04-APR-09:09 5.37 2.97
May 0.379012E+11 83821.63 30-MAY-04:12 15.60 10.93 0.524671E+10 6735.19 02-MAY-13:09 15.60 10.93
June 0.475157E+11 86818.05 23-JUN-04:12 18.13 11.74 0.525962E+10 6734.81 20-JUN-13:09 18.13 11.74
July 0.497318E+11 87730.75 19-JUL-04:12 20.20 16.41 0.489248E+10 6734.97 03-JUL-13:09 20.20 16.41
August 0.515852E+11 87988.60 14-AUG-04:12 12.20 9.88 0.549415E+10 6734.80 01-AUG-13:09 12.20 9.88
September 0.413228E+11 87336.45 11-SEP-04:12 11.10 10.17 0.486315E+10 6735.15 07-SEP-09:00 11.10 10.17
October 0.345829E+11 82679.86 19-OCT-05:02 12.20 5.54 0.502607E+10 6734.74 27-OCT-09:09 7.67 3.31
November 0.285199E+11 68451.95 04-NOV-05:02 9.43 5.60 0.483883E+10 6734.76 03-NOV-09:09 9.43 5.60
December 0.254953E+11 29509.55 07-DEC-16:30 5.55 1.71 0.451792E+10 6734.80 07-DEC-10:20 5.55 1.71
                     
Annual Sum or Average 0.428445E+12         0.590178E+11        
Minimum of Months 0.231322E+11 21440.08   -6.7 -8.2 0.428378E+10 6734.47   -6.7 -8.2
Maximum of Months 0.515852E+11 87988.60   20.20 16.41 0.549415E+10 6735.19   20.20 16.41



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: CORE_TOP

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.147795E+11 17906.48 13-JAN-17:00 7.80 3.93 0.398510E+10 6309.97 13-JAN-14:00 7.80 3.93
February 0.171018E+11 26715.50 28-FEB-17:00 10.00 4.31 0.384147E+10 6728.70 28-FEB-14:00 10.00 4.31
March 0.235149E+11 30930.16 23-MAR-15:20 7.60 1.00 0.488511E+10 6734.58 02-MAR-14:20 7.60 1.00
April 0.269417E+11 43015.26 25-APR-16:00 17.80 7.70 0.458877E+10 6734.68 25-APR-09:20 17.80 7.70
May 0.337702E+11 78372.42 20-MAY-05:02 11.47 8.41 0.505944E+10 6735.18 02-MAY-13:09 11.47 8.41
June 0.466636E+11 86102.43 21-JUN-04:12 17.40 12.31 0.523154E+10 6734.76 20-JUN-13:00 17.40 12.31
July 0.509002E+11 85269.20 19-JUL-04:12 20.20 16.41 0.488158E+10 6734.96 03-JUL-13:09 20.20 16.41
August 0.505142E+11 84133.76 08-AUG-04:12 17.97 11.68 0.547568E+10 6734.78 01-AUG-13:09 17.97 11.68
September 0.365520E+11 83269.40 05-SEP-04:12 18.30 11.92 0.475828E+10 6735.10 07-SEP-09:00 16.70 15.61
October 0.265000E+11 40540.77 18-OCT-16:00 24.40 11.02 0.474181E+10 6734.71 20-OCT-09:09 7.98 4.07
November 0.205018E+11 29073.16 03-NOV-16:00 14.30 7.69 0.436768E+10 6734.57 09-NOV-14:39 9.13 3.92
December 0.166432E+11 20914.22 06-DEC-17:00 6.70 2.38 0.400655E+10 6723.03 07-DEC-14:00 8.30 2.55
                     
Annual Sum or Average 0.364383E+12         0.558230E+11        
Minimum of Months 0.147795E+11 17906.48   6.70 1.00 0.384147E+10 6309.97   7.60 1.00
Maximum of Months 0.509002E+11 86102.43   24.40 16.41 0.547568E+10 6735.18   20.20 16.41



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.103986E+10 2364.60 02-JAN-06:02 -1.3 -3.4 0.490087E+09 787.48 02-JAN-14:50 6.20 1.19
February 0.176018E+10 4185.05 27-FEB-16:00 18.90 7.06 0.478944E+09 845.61 27-FEB-14:00 18.90 7.06
March 0.309440E+10 4747.51 27-MAR-14:00 8.90 2.28 0.628342E+09 845.61 21-MAR-13:00 8.90 2.28
April 0.441996E+10 7576.53 07-APR-14:00 23.30 9.68 0.590750E+09 845.62 13-APR-13:00 13.30 7.60
May 0.538365E+10 8402.39 30-MAY-15:00 19.40 10.86 0.645755E+09 845.68 02-MAY-13:09 19.40 10.86
June 0.885640E+10 13344.81 22-JUN-05:02 16.10 12.31 0.659633E+09 845.64 19-JUN-13:39 16.10 12.31
July 0.106331E+11 18010.64 16-JUL-18:31 32.40 17.11 0.615371E+09 846.79 18-JUL-13:20 33.17 17.33
August 0.101518E+11 17569.19 06-AUG-16:01 35.50 16.24 0.689554E+09 845.64 01-AUG-13:09 35.50 16.24
September 0.560633E+10 17927.78 04-SEP-14:41 31.83 16.52 0.601854E+09 845.68 07-SEP-09:00 16.70 15.61
October 0.390187E+10 6139.04 19-OCT-14:30 21.40 10.24 0.610196E+09 845.63 18-OCT-13:39 21.40 10.24
November 0.273425E+10 4052.13 08-NOV-13:30 13.80 7.89 0.565491E+09 845.62 16-NOV-14:09 10.63 6.46
December 0.184387E+10 2480.02 06-DEC-06:03 7.02 3.93 0.510216E+09 845.60 06-DEC-14:00 11.10 5.34
                     
Annual Sum or Average 0.594256E+11         0.708619E+10        
Minimum of Months 0.103986E+10 2364.60   -1.3 -3.4 0.478944E+09 787.48   6.20 1.19
Maximum of Months 0.106331E+11 18010.64   35.50 17.11 0.689554E+09 846.79   35.50 17.33



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.120553E+10 3197.97 15-JAN-10:53 3.30 -1.0 0.315280E+09 544.94 17-JAN-10:30 5.25 1.27
February 0.221488E+10 8066.26 27-FEB-09:55 11.70 4.23 0.310434E+09 544.95 23-FEB-10:39 11.70 4.23
March 0.392547E+10 11611.19 28-MAR-09:15 5.73 0.86 0.396953E+09 544.96 10-MAR-10:09 5.73 0.86
April 0.551872E+10 19149.25 16-APR-08:52 12.20 5.44 0.369191E+09 544.96 25-APR-09:09 9.87 4.86
May 0.664052E+10 14582.43 19-MAY-08:30 16.95 11.09 0.411695E+09 544.99 02-MAY-13:09 16.95 11.09
June 0.975783E+10 25209.95 25-JUN-08:22 16.15 11.58 0.422855E+09 547.19 23-JUN-09:00 16.15 11.58
July 0.117520E+11 26503.63 02-JUL-08:41 21.93 15.30 0.395929E+09 546.86 03-JUL-09:00 23.30 14.49
August 0.110012E+11 26729.74 06-AUG-09:21 28.60 14.63 0.441646E+09 546.58 04-AUG-09:00 28.60 14.63
September 0.665239E+10 27686.20 04-SEP-08:41 26.52 14.78 0.383804E+09 544.99 07-SEP-09:00 16.70 15.61
October 0.459855E+10 21438.06 15-OCT-09:32 15.40 7.79 0.387620E+09 544.96 18-OCT-13:39 24.80 11.21
November 0.292172E+10 7134.91 06-NOV-09:35 1.20 -1.1 0.350942E+09 544.95 03-NOV-09:09 1.20 -1.1
December 0.176443E+10 3280.92 20-DEC-10:05 3.48 -0.5 0.315719E+09 544.94 20-DEC-10:20 3.67 -0.4
                     
Annual Sum or Average 0.679533E+11         0.450207E+10        
Minimum of Months 0.120553E+10 3197.97   1.20 -1.1 0.310434E+09 544.94   1.20 -1.1
Maximum of Months 0.117520E+11 27686.20   28.60 15.30 0.441646E+09 547.19   28.60 15.61



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.355056E+10 26016.09 15-JAN-13:32 5.40 -0.5 0.529137E+09 845.64 13-JAN-14:00 5.40 -0.5
February 0.626462E+10 32274.02 26-FEB-13:42 15.50 5.72 0.521350E+09 847.57 27-FEB-14:39 18.70 7.17
March 0.850029E+10 32350.49 26-MAR-13:22 9.45 1.83 0.631862E+09 847.58 02-MAR-14:00 9.45 1.83
April 0.871792E+10 32419.28 16-APR-13:32 19.03 8.17 0.575488E+09 846.61 24-APR-13:00 17.80 9.82
May 0.880557E+10 18069.32 19-MAY-13:30 26.65 14.96 0.629807E+09 846.16 19-MAY-13:39 26.83 14.98
June 0.117947E+11 25882.45 11-JUN-12:23 25.00 12.98 0.653485E+09 845.70 19-JUN-13:39 24.80 12.00
July 0.150401E+11 30904.97 16-JUL-13:12 30.17 18.28 0.613984E+09 847.07 18-JUL-13:50 32.07 17.42
August 0.172227E+11 31750.73 06-AUG-13:21 34.15 15.08 0.686887E+09 855.24 30-AUG-13:30 26.15 14.29
September 0.128822E+11 34798.80 04-SEP-14:41 31.83 16.52 0.597226E+09 858.29 01-SEP-13:20 31.83 16.52
October 0.109329E+11 36754.57 15-OCT-13:31 22.93 11.00 0.612694E+09 880.09 18-OCT-13:20 24.60 11.01
November 0.754089E+10 29767.73 12-NOV-13:02 -1.4 -4.2 0.582012E+09 847.17 06-NOV-14:50 -1.4 -4.2
December 0.500899E+10 18278.95 17-DEC-13:43 -1.2 -3.8 0.539960E+09 845.64 07-DEC-10:20 -1.2 -3.8
                     
Annual Sum or Average 0.116261E+12         0.717389E+10        
Minimum of Months 0.355056E+10 18069.32   -1.4 -4.2 0.521350E+09 845.64   -1.4 -4.2
Maximum of Months 0.172227E+11 36754.57   34.15 18.28 0.686887E+09 880.09   32.07 17.42



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.204350E+10 5786.22 13-JAN-15:30 9.45 4.93 0.319273E+09 544.94 13-JAN-14:00 9.45 4.93
February 0.384989E+10 18839.92 26-FEB-16:22 15.85 6.07 0.321592E+09 544.94 23-FEB-14:00 15.85 6.07
March 0.634248E+10 16003.33 12-MAR-16:12 5.73 -0.9 0.417251E+09 544.95 21-MAR-13:50 2.25 0.50
April 0.877071E+10 33209.75 16-APR-16:51 20.00 8.97 0.390127E+09 544.96 13-APR-13:00 20.00 8.97
May 0.856485E+10 31612.32 28-MAY-17:21 20.55 10.38 0.411194E+09 544.99 02-MAY-13:09 20.55 10.38
June 0.120672E+11 32099.89 18-JUN-17:21 25.30 14.49 0.425290E+09 544.98 19-JUN-13:39 24.80 12.00
July 0.151262E+11 34439.99 16-JUL-17:11 33.13 17.22 0.397625E+09 544.98 13-JUL-09:00 33.13 17.22
August 0.158371E+11 33579.08 06-AUG-16:41 35.10 15.80 0.445802E+09 544.97 01-AUG-13:09 35.10 15.80
September 0.836389E+10 35973.69 04-SEP-16:01 32.80 16.54 0.383561E+09 544.99 07-SEP-09:00 16.70 15.61
October 0.666954E+10 32661.67 15-OCT-15:31 22.40 10.89 0.394742E+09 544.96 18-OCT-13:39 24.80 11.21
November 0.531862E+10 11155.76 03-NOV-15:30 14.45 7.69 0.378173E+09 544.96 16-NOV-14:09 10.63 6.46
December 0.429633E+10 9774.76 06-DEC-15:30 10.25 4.94 0.353779E+09 544.95 19-DEC-14:09 10.97 6.81
                     
Annual Sum or Average 0.972503E+11         0.463841E+10        
Minimum of Months 0.204350E+10 5786.22   5.73 -0.9 0.319273E+09 544.94   2.25 0.50
Maximum of Months 0.158371E+11 35973.69   35.10 17.22 0.445802E+09 544.99   35.10 17.22



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 58339450.55 1478.40 13-JAN-16:50 7.98 4.06 0.462315E+09 629.44 13-JAN-14:00 7.98 4.06
February 0.512927E+09 2528.75 27-FEB-14:00 18.30 7.03 0.428652E+09 749.94 27-FEB-16:19 16.67 6.71
March 0.140652E+10 2595.45 23-MAR-13:30 9.70 2.18 0.539910E+09 807.05 29-MAR-13:00 12.80 4.50
April 0.233564E+10 5651.22 07-APR-14:30 22.50 9.29 0.529028E+09 845.61 13-APR-13:00 13.30 7.60
May 0.375432E+10 7875.94 19-MAY-16:00 27.80 14.54 0.604972E+09 845.63 04-MAY-13:20 27.80 14.54
June 0.697464E+10 12171.82 21-JUN-05:02 15.87 11.84 0.652166E+09 845.64 20-JUN-13:09 15.87 11.84
July 0.835206E+10 17220.69 16-JUL-18:21 32.50 17.04 0.613208E+09 846.50 18-JUL-13:20 33.17 17.33
August 0.716456E+10 16463.47 06-AUG-16:01 35.50 16.24 0.681509E+09 845.64 01-AUG-13:09 35.50 16.24
September 0.413471E+10 16919.56 04-SEP-12:51 31.10 15.70 0.572265E+09 845.67 07-SEP-09:00 16.70 15.61
October 0.228156E+10 4564.13 19-OCT-14:30 21.40 10.24 0.546884E+09 845.62 18-OCT-13:39 21.40 10.24
November 0.109865E+10 2530.59 03-NOV-13:50 14.78 7.82 0.486339E+09 790.05 08-NOV-14:30 13.55 7.81
December 0.268104E+09 1649.57 06-DEC-16:20 8.50 3.80 0.449777E+09 676.00 06-DEC-14:00 8.50 3.80
                     
Annual Sum or Average 0.383420E+11         0.656703E+10        
Minimum of Months 58339450.55 1478.40   7.98 2.18 0.428652E+09 629.44   7.98 3.80
Maximum of Months 0.835206E+10 17220.69   35.50 17.04 0.681509E+09 846.50   35.50 17.33



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.248483E+09 2295.13 20-JAN-10:00 -3.3 -5.9 0.219632E+09 416.29 20-JAN-09:00 -3.3 -5.9
February 0.114167E+10 5562.18 28-FEB-09:55 1.10 -0.5 0.208990E+09 521.20 28-FEB-11:20 4.83 1.71
March 0.253587E+10 9474.68 28-MAR-10:10 7.38 1.58 0.265449E+09 521.21 01-MAR-11:09 7.38 1.58
April 0.425827E+10 13543.61 25-APR-09:00 9.40 4.65 0.255805E+09 521.21 13-APR-14:09 9.40 4.65
May 0.580433E+10 15345.69 19-MAY-08:50 17.52 11.29 0.290575E+09 521.27 02-MAY-12:09 17.52 11.29
June 0.946617E+10 30517.08 25-JUN-08:41 16.52 11.73 0.307437E+09 522.38 30-JUN-10:09 21.05 13.37
July 0.114741E+11 32371.57 02-JUL-09:01 22.48 15.33 0.290572E+09 523.45 26-JUL-10:30 29.80 14.14
August 0.101947E+11 29379.77 06-AUG-09:21 28.60 14.63 0.321767E+09 524.02 07-AUG-10:50 30.60 14.99
September 0.597138E+10 29008.65 04-SEP-08:51 26.70 14.88 0.270800E+09 521.22 06-SEP-10:20 18.17 15.15
October 0.343716E+10 9388.81 18-OCT-10:10 20.28 8.90 0.262836E+09 521.21 19-OCT-10:09 19.18 9.33
November 0.159934E+10 4996.49 03-NOV-10:10 9.10 5.57 0.231268E+09 521.20 03-NOV-10:20 9.50 5.81
December 0.463605E+09 2420.02 20-DEC-10:00 3.30 -0.6 0.212609E+09 430.48 20-DEC-09:00 3.30 -0.6
                     
Annual Sum or Average 0.565952E+11         0.313774E+10        
Minimum of Months 0.248483E+09 2295.13   -3.3 -5.9 0.208990E+09 416.29   -3.3 -5.9
Maximum of Months 0.114741E+11 32371.57   28.60 15.33 0.321767E+09 524.02   30.60 15.15



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.265637E+10 18766.20 15-JAN-13:13 5.20 -0.5 0.510405E+09 845.64 13-JAN-14:09 5.20 -0.5
February 0.545679E+10 34154.52 26-FEB-14:01 15.78 5.88 0.503805E+09 856.00 28-FEB-14:09 10.10 4.57
March 0.720360E+10 29922.34 26-MAR-13:32 9.63 1.94 0.600397E+09 872.67 01-MAR-14:09 9.63 1.94
April 0.706078E+10 32240.12 16-APR-15:02 19.50 8.48 0.545945E+09 846.17 24-APR-13:00 17.80 9.82
May 0.779906E+10 21763.26 14-MAY-13:52 16.70 6.76 0.608887E+09 846.32 19-MAY-13:50 27.02 15.00
June 0.106227E+11 30837.93 18-JUN-13:42 23.12 15.42 0.642259E+09 845.69 19-JUN-13:09 24.50 12.52
July 0.134815E+11 34159.40 16-JUL-13:41 31.32 18.41 0.609659E+09 846.56 14-JUL-13:00 31.32 18.41
August 0.152371E+11 33044.87 06-AUG-13:21 34.15 15.08 0.678307E+09 872.60 30-AUG-13:39 26.33 14.35
September 0.126458E+11 35746.86 04-SEP-15:31 32.60 16.55 0.582964E+09 885.68 01-SEP-13:39 32.60 16.55
October 0.102496E+11 34842.40 15-OCT-13:41 23.12 11.08 0.594862E+09 911.65 18-OCT-13:39 24.80 11.21
November 0.624833E+10 32522.56 12-NOV-12:12 -2.8 -5.1 0.558784E+09 858.63 03-NOV-13:39 -2.8 -5.1
December 0.336818E+10 16482.54 12-DEC-12:40 -2.8 -5.7 0.511034E+09 845.64 13-DEC-14:50 -5.6 -7.0
                     
Annual Sum or Average 0.102030E+12         0.694731E+10        
Minimum of Months 0.265637E+10 16482.54   -2.8 -5.7 0.503805E+09 845.64   -5.6 -7.0
Maximum of Months 0.152371E+11 35746.86   34.15 18.41 0.678307E+09 911.65   32.60 18.41



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.393672E+09 3192.61 13-JAN-15:50 9.08 4.76 0.302145E+09 500.82 13-JAN-15:00 8.90 4.67
February 0.138172E+10 9066.40 28-FEB-16:40 10.37 4.49 0.285400E+09 544.74 27-FEB-14:00 10.37 4.49
March 0.276437E+10 11796.90 28-MAR-17:00 10.60 2.97 0.350595E+09 544.94 02-MAR-14:30 10.60 2.97
April 0.448579E+10 30941.82 16-APR-16:21 20.00 8.89 0.332310E+09 544.94 07-APR-13:09 20.00 8.89
May 0.642962E+10 33753.22 28-MAY-17:51 20.00 10.33 0.378147E+09 544.95 25-MAY-13:09 20.00 10.33
June 0.909673E+10 33791.75 18-JUN-17:41 25.10 14.47 0.409424E+09 544.96 19-JUN-13:09 24.50 12.52
July 0.108232E+11 35712.50 16-JUL-17:01 33.22 17.33 0.391093E+09 544.97 03-JUL-13:09 33.22 17.33
August 0.977653E+10 30623.94 06-AUG-16:41 35.10 15.80 0.431044E+09 544.96 01-AUG-13:09 35.10 15.80
September 0.635390E+10 34085.64 04-SEP-16:11 32.80 16.58 0.355263E+09 544.95 05-SEP-09:09 17.20 11.96
October 0.389534E+10 18582.20 15-OCT-15:42 22.30 10.85 0.344047E+09 544.94 18-OCT-13:00 25.00 11.40
November 0.199588E+10 7009.89 03-NOV-15:40 14.40 7.69 0.320910E+09 544.92 09-NOV-14:00 9.00 3.82
December 0.746523E+09 3829.71 06-DEC-15:40 9.97 4.80 0.295631E+09 521.18 06-DEC-16:10 8.95 4.16
                     
Annual Sum or Average 0.581433E+11         0.419601E+10        
Minimum of Months 0.393672E+09 3192.61   9.08 2.97 0.285400E+09 500.82   8.90 2.97
Maximum of Months 0.108232E+11 35712.50   35.10 17.33 0.431044E+09 544.97   35.10 17.33



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 25518555.57 1450.96 14-JAN-17:03 8.90 4.06 0.458336E+09 626.08 10-JAN-10:20 8.90 4.06
February 0.229002E+09 2273.63 27-FEB-13:30 17.75 6.76 0.423050E+09 714.61 27-FEB-14:00 18.90 7.23
March 0.887839E+09 2389.61 23-MAR-13:30 9.70 2.18 0.520622E+09 763.30 29-MAR-13:00 12.80 4.50
April 0.181015E+10 5505.70 07-APR-14:30 22.50 9.29 0.502149E+09 845.60 07-APR-13:09 22.50 9.29
May 0.343357E+10 8656.06 19-MAY-16:00 27.80 14.54 0.583015E+09 845.63 19-MAY-13:09 27.80 14.54
June 0.689432E+10 11278.10 21-JUN-05:02 15.87 11.84 0.641949E+09 845.63 21-JUN-13:09 26.88 17.83
July 0.854724E+10 19700.34 02-JUL-18:31 24.47 14.35 0.609869E+09 845.65 03-JUL-13:09 19.07 14.10
August 0.716217E+10 19360.96 06-AUG-16:01 35.50 16.24 0.671277E+09 845.64 01-AUG-13:09 35.50 16.24
September 0.378423E+10 18687.42 04-SEP-16:21 32.80 16.63 0.550894E+09 845.66 07-SEP-09:00 16.70 15.61
October 0.168891E+10 4096.42 19-OCT-14:40 21.50 10.24 0.514818E+09 845.61 19-OCT-13:09 21.50 10.24
November 0.600605E+09 2254.93 03-NOV-13:30 14.35 7.74 0.468694E+09 736.38 08-NOV-14:00 13.20 7.65
December 0.112458E+09 1623.57 06-DEC-16:20 8.50 3.80 0.446401E+09 640.35 06-DEC-14:00 8.50 3.80
                     
Annual Sum or Average 0.351760E+11         0.639107E+10        
Minimum of Months 25518555.57 1450.96   8.50 2.18 0.423050E+09 626.08   8.50 3.80
Maximum of Months 0.854724E+10 19700.34   35.50 16.63 0.671277E+09 845.66   35.50 17.83



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.127990E+09 2108.18 31-JAN-10:30 -6.1 -8.7 0.298754E+09 418.04 31-JAN-10:39 -5.7 -8.4
February 0.778873E+09 3573.99 28-FEB-10:30 2.50 0.37 0.280225E+09 544.95 28-FEB-10:30 2.50 0.37
March 0.191966E+10 8055.75 28-MAR-09:35 6.47 1.20 0.356580E+09 544.95 22-MAR-09:50 6.47 1.20
April 0.356415E+10 12590.12 25-APR-09:30 10.80 5.26 0.342865E+09 544.95 25-APR-09:09 10.80 5.26
May 0.537440E+10 14852.45 19-MAY-08:50 17.52 11.29 0.392534E+09 544.99 02-MAY-13:09 17.52 11.29
June 0.933627E+10 29381.90 25-JUN-08:11 15.97 11.51 0.417392E+09 546.39 23-JUN-09:00 15.97 11.51
July 0.116011E+11 31924.14 02-JUL-08:31 21.67 15.15 0.393556E+09 546.08 03-JUL-09:00 23.30 14.49
August 0.101767E+11 29405.92 06-AUG-09:21 28.60 14.63 0.437135E+09 546.49 11-AUG-09:00 27.80 12.62
September 0.549260E+10 25792.94 04-SEP-09:02 26.88 14.90 0.364600E+09 544.97 14-SEP-13:00 21.70 13.42
October 0.274820E+10 8529.49 18-OCT-09:50 19.53 8.61 0.348817E+09 544.95 27-OCT-09:39 9.07 4.22
November 0.105714E+10 3263.16 03-NOV-10:00 8.70 5.33 0.305844E+09 544.51 03-NOV-09:00 8.70 5.33
December 0.246521E+09 2214.00 20-DEC-10:20 3.67 -0.4 0.288482E+09 429.95 20-DEC-10:30 3.85 -0.4
                     
Annual Sum or Average 0.524235E+11         0.422678E+10        
Minimum of Months 0.127990E+09 2108.18   -6.1 -8.7 0.280225E+09 418.04   -5.7 -8.4
Maximum of Months 0.116011E+11 31924.14   28.60 15.15 0.437135E+09 546.49   27.80 14.49



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.204816E+10 15198.02 31-JAN-13:30 -0.9 -4.5 0.499944E+09 845.64 13-JAN-14:00 -0.9 -4.5
February 0.442276E+10 34851.62 26-FEB-14:01 15.78 5.88 0.488886E+09 845.64 23-FEB-14:20 15.78 5.88
March 0.602314E+10 26175.23 26-MAR-14:02 10.00 2.16 0.582786E+09 846.10 23-MAR-13:50 10.00 2.16
April 0.602392E+10 21605.86 25-APR-13:30 16.40 7.12 0.528720E+09 846.26 24-APR-13:00 16.40 7.12
May 0.728350E+10 23409.43 14-MAY-14:22 16.70 6.45 0.593770E+09 845.72 02-MAY-13:09 16.70 6.45
June 0.105200E+11 32004.87 25-JUN-16:11 24.23 12.89 0.631647E+09 845.67 21-JUN-13:09 24.23 12.89
July 0.137313E+11 34557.39 02-JUL-13:12 25.53 14.08 0.603842E+09 846.84 18-JUL-13:00 31.70 17.43
August 0.152401E+11 35360.05 06-AUG-13:21 34.15 15.08 0.668880E+09 854.89 30-AUG-13:39 26.33 14.35
September 0.119193E+11 37751.71 03-SEP-12:41 33.22 15.94 0.568136E+09 867.56 01-SEP-13:39 33.22 15.94
October 0.872772E+10 35958.42 15-OCT-13:41 23.12 11.08 0.574280E+09 879.64 18-OCT-13:39 24.80 11.21
November 0.492728E+10 24041.73 03-NOV-13:30 14.35 7.74 0.538064E+09 845.73 03-NOV-13:50 14.78 7.82
December 0.253917E+10 13579.97 12-DEC-14:30 -2.2 -5.4 0.494790E+09 845.64 19-DEC-14:09 10.97 6.81
                     
Annual Sum or Average 0.934063E+11         0.677375E+10        
Minimum of Months 0.204816E+10 13579.97   -2.2 -5.4 0.488886E+09 845.64   -0.9 -4.5
Maximum of Months 0.152401E+11 37751.71   34.15 15.94 0.668880E+09 879.64   33.22 17.43



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.296884E+09 3219.23 13-JAN-15:50 9.08 4.76 0.300485E+09 486.01 13-JAN-15:00 8.90 4.67
February 0.105011E+10 8636.47 28-FEB-16:40 10.37 4.49 0.282126E+09 544.05 27-FEB-14:00 10.37 4.49
March 0.216651E+10 11585.26 28-MAR-17:00 10.60 2.97 0.344871E+09 544.93 02-MAR-14:00 10.60 2.97
April 0.390275E+10 29835.58 22-APR-17:41 16.10 8.34 0.322207E+09 544.94 07-APR-13:39 16.10 8.34
May 0.610009E+10 35270.52 28-MAY-17:51 20.00 10.33 0.368608E+09 544.96 19-MAY-13:09 20.00 10.33
June 0.905656E+10 35672.92 18-JUN-17:11 25.40 14.50 0.401811E+09 544.96 20-JUN-13:00 28.90 18.82
July 0.110031E+11 36675.62 02-JUL-17:51 25.60 14.12 0.386705E+09 544.97 03-JUL-13:09 19.07 14.10
August 0.979947E+10 32628.64 06-AUG-16:41 35.10 15.80 0.423487E+09 544.96 01-AUG-13:09 35.10 15.80
September 0.598612E+10 32623.29 04-SEP-16:21 32.80 16.63 0.345704E+09 544.94 05-SEP-13:00 24.40 15.14
October 0.320981E+10 15053.53 15-OCT-16:22 21.65 10.63 0.332483E+09 544.92 18-OCT-13:00 25.00 11.40
November 0.143432E+10 6512.30 03-NOV-15:40 14.40 7.69 0.313583E+09 544.62 09-NOV-14:00 9.00 3.82
December 0.503134E+09 3466.79 06-DEC-15:50 9.68 4.65 0.292219E+09 514.17 06-DEC-15:00 9.40 4.51
                     
Annual Sum or Average 0.545088E+11         0.411429E+10        
Minimum of Months 0.296884E+09 3219.23   9.08 2.97 0.282126E+09 486.01   8.90 2.97
Maximum of Months 0.110031E+11 36675.62   35.10 16.63 0.423487E+09 544.97   35.10 18.82



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: GROUNDFLOOR_PLENUM

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.750817E+09 10818.23 06-JAN-05:01 -24.5 -24.9 0.00 0.00 01-JAN-00:10 -24.5 -24.9
February 0.980988E+09 9873.44 04-FEB-05:01 -20.4 -20.8 0.00 0.00 01-FEB-00:10 -20.4 -20.8
March 0.253324E+10 8763.65 04-MAR-05:01 -19.1 -19.6 0.00 0.00 01-MAR-00:10 -19.1 -19.6
April 0.436717E+10 6567.84 24-APR-16:00 18.90 10.03 0.00 0.00 01-APR-00:10 18.90 10.03
May 0.438254E+10 8144.18 30-MAY-05:15 15.60 11.34 0.00 0.00 01-MAY-00:10 15.60 11.34
June 0.801561E+10 8570.88 26-JUN-05:15 10.33 9.12 0.00 0.00 01-JUN-00:10 10.33 9.12
July 0.100296E+11 10642.96 17-JUL-15:20 36.47 17.10 0.00 0.00 01-JUL-00:10 36.47 17.10
August 0.103131E+11 11652.63 07-AUG-05:15 17.77 10.09 0.00 0.00 01-AUG-00:10 17.77 10.09
September 0.602539E+10 11999.96 05-SEP-05:03 18.40 11.40 0.00 0.00 01-SEP-00:10 18.40 11.40
October 0.428965E+10 6145.43 16-OCT-15:50 19.68 8.22 0.00 0.00 01-OCT-00:10 19.68 8.22
November 0.249400E+10 10640.67 27-NOV-05:01 -15.4 -16.5 0.00 0.00 01-NOV-00:10 -15.4 -16.5
December 0.122146E+10 10127.31 28-DEC-05:01 -22.3 -22.7 0.00 0.00 01-DEC-00:10 -22.3 -22.7
                     
Annual Sum or Average 0.554036E+11         0.00        
Minimum of Months 0.750817E+09 6145.43   -24.5 -24.9 0.00 0.00   -24.5 -24.9
Maximum of Months 0.103131E+11 11999.96   36.47 17.10 0.00 0.00   36.47 17.10



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: MIDFLOOR_PLENUM

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.605877E+09 15039.52 06-JAN-04:01 -24.4 -24.9 0.00 0.00 01-JAN-00:10 -24.4 -24.9
February 0.408181E+09 13991.63 10-FEB-04:11 -19.4 -19.8 0.00 0.00 01-FEB-00:10 -19.4 -19.8
March 0.965889E+09 16331.48 04-MAR-04:01 -18.4 -18.9 0.00 0.00 01-MAR-00:10 -18.4 -18.9
April 0.154968E+10 12546.71 29-APR-04:01 -7.8 -8.7 0.00 0.00 01-APR-00:10 -7.8 -8.7
May 0.232745E+10 10814.91 22-MAY-04:42 -0.5 -0.5 0.00 0.00 01-MAY-00:10 -0.5 -0.5
June 0.561054E+10 7274.05 23-JUN-15:30 27.50 14.33 0.00 0.00 01-JUN-00:10 27.50 14.33
July 0.739381E+10 8991.64 17-JUL-15:30 36.65 17.14 0.00 0.00 01-JUL-00:10 36.65 17.14
August 0.716863E+10 8928.88 07-AUG-15:40 32.40 16.10 0.00 0.00 01-AUG-00:10 32.40 16.10
September 0.411136E+10 8477.26 05-SEP-14:40 24.40 14.90 0.00 0.00 01-SEP-00:10 24.40 14.90
October 0.189297E+10 9851.59 10-OCT-04:01 -5.2 -5.7 0.00 0.00 01-OCT-00:10 -5.2 -5.7
November 0.986147E+09 11302.21 27-NOV-02:21 -16.0 -16.8 0.00 0.00 01-NOV-00:10 -16.0 -16.8
December 0.737432E+09 14364.01 23-DEC-04:01 -11.7 -12.5 0.00 0.00 01-DEC-00:10 -11.7 -12.5
                     
Annual Sum or Average 0.337580E+11         0.00        
Minimum of Months 0.408181E+09 7274.05   -24.4 -24.9 0.00 0.00   -24.4 -24.9
Maximum of Months 0.739381E+10 16331.48   36.65 17.14 0.00 0.00   36.65 17.14



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: TOPFLOOR_PLENUM

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 631272.88 341.66 14-JAN-13:30 10.00 4.73 0.00 0.00 01-JAN-00:10 10.00 4.73
February 0.105315E+09 3278.14 26-FEB-14:44 16.52 6.36 0.00 0.00 01-FEB-00:10 16.52 6.36
March 0.678337E+09 5222.14 23-MAR-13:55 10.00 2.51 0.00 0.00 01-MAR-00:10 10.00 2.51
April 0.236677E+10 12276.06 25-APR-15:00 17.00 7.46 0.00 0.00 01-APR-00:10 17.00 7.46
May 0.503064E+10 17793.21 19-MAY-15:00 28.30 14.88 0.00 0.00 01-MAY-00:10 28.30 14.88
June 0.101589E+11 20243.87 23-JUN-13:30 31.40 15.21 0.00 0.00 01-JUN-00:10 31.40 15.21
July 0.133937E+11 24012.12 17-JUL-14:50 36.20 17.00 0.00 0.00 01-JUL-00:10 36.20 17.00
August 0.115055E+11 21733.44 07-AUG-15:40 32.40 16.10 0.00 0.00 01-AUG-00:10 32.40 16.10
September 0.542536E+10 16251.06 01-SEP-15:40 28.30 14.15 0.00 0.00 01-SEP-00:10 28.30 14.15
October 0.143985E+10 9811.65 18-OCT-15:20 24.80 11.42 0.00 0.00 01-OCT-00:10 24.80 11.42
November 0.102737E+09 2475.42 03-NOV-14:15 14.87 7.79 0.00 0.00 01-NOV-00:10 14.87 7.79
December 0.00 0.00 01-DEC-00:10 -2.1 -4.2 0.00 0.00 01-DEC-00:10 -2.1 -4.2
                     
Annual Sum or Average 0.502077E+11         0.00        
Minimum of Months 0.00 0.00   -2.1 -4.2 0.00 0.00   -2.1 -4.2
Maximum of Months 0.133937E+11 24012.12   36.20 17.00 0.00 0.00   36.20 17.00



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.201798E+10 2249.31 19-JAN-16:50 -6.4 -8.0 95176331.83 126.82 20-JAN-14:09 0.50 -3.2
February 0.725232E+10 4600.84 26-FEB-17:27 13.35 5.05 86396431.72 126.82 08-FEB-14:09 13.35 5.05
March 0.138113E+11 6810.82 31-MAR-24:00 2.50 0.99 0.103236E+09 126.82 07-MAR-14:09 2.50 0.99
April 0.188333E+11 8501.87 22-APR-18:10 15.63 8.19 91605262.18 126.82 21-APR-09:00 15.63 8.19
May 0.431845E+10 3508.69 31-MAY-24:00 15.50 10.27 99234994.00 126.84 30-MAY-09:39 15.50 10.27
June 0.948539E+10 5376.53 30-JUN-24:00 19.60 12.23 98962642.99 126.85 01-JUN-13:50 19.60 12.23
July 0.150153E+11 7270.88 31-JUL-23:45 19.48 11.61 91883798.14 126.84 03-JUL-13:09 19.48 11.61
August 0.200158E+11 8528.18 03-AUG-18:50 24.60 12.54 0.103324E+09 128.74 11-AUG-13:00 32.20 13.16
September 0.431671E+10 3303.90 30-SEP-24:00 11.80 6.26 91611062.85 126.85 06-SEP-13:00 11.80 6.26
October 0.921807E+10 4932.76 31-OCT-24:00 4.70 1.47 95230954.36 126.83 25-OCT-09:00 4.70 1.47
November 0.134220E+11 6340.38 13-NOV-16:30 3.15 -2.5 94300315.11 126.83 08-NOV-14:00 3.15 -2.5
December 0.183621E+11 8084.68 06-DEC-16:10 8.95 4.16 91880781.11 126.82 15-DEC-14:39 -10.6 -10.9
                     
Annual Sum or Average 0.136069E+12         0.114284E+10        
Minimum of Months 0.201798E+10 2249.31   -6.4 -8.0 86396431.72 126.82   -10.6 -10.9
Maximum of Months 0.200158E+11 8528.18   24.60 12.54 0.103324E+09 128.74   32.20 13.16



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: DATACENTER_MID_ZN_6

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.493958E+09 1867.81 19-JAN-16:50 -6.4 -8.0 93228851.76 126.82 02-JAN-14:09 -6.4 -8.0
February 0.494928E+10 4220.37 28-FEB-17:00 10.00 4.31 86396452.49 126.82 08-FEB-14:09 10.00 4.31
March 0.113505E+11 6212.16 28-MAR-17:50 9.18 2.32 0.103236E+09 126.82 07-MAR-14:09 9.18 2.32
April 0.167862E+11 8069.72 25-APR-18:10 16.73 7.64 91605312.34 126.82 24-APR-09:50 16.73 7.64
May 0.328297E+10 3302.64 31-MAY-24:00 15.50 10.27 99234860.93 126.84 30-MAY-09:39 15.50 10.27
June 0.864338E+10 5249.46 30-JUN-24:00 19.60 12.23 98962664.29 126.85 01-JUN-13:00 19.60 12.23
July 0.141120E+11 7065.97 31-JUL-23:53 19.20 11.32 91884196.64 126.84 03-JUL-13:09 19.20 11.32
August 0.188051E+11 8198.17 03-AUG-18:50 24.60 12.54 0.103253E+09 126.83 01-AUG-13:00 24.60 12.54
September 0.344794E+10 2873.68 30-SEP-23:30 12.50 6.83 91610048.27 126.85 06-SEP-13:20 12.50 6.83
October 0.749219E+10 4300.32 16-OCT-17:00 17.80 7.68 95230856.70 126.83 25-OCT-09:00 13.30 8.54
November 0.108683E+11 5750.11 10-NOV-16:30 4.70 0.35 94300349.32 126.83 08-NOV-14:00 4.70 0.35
December 0.147485E+11 7376.02 06-DEC-16:20 8.50 3.80 91880816.59 126.82 18-DEC-14:39 0.60 -2.8
                     
Annual Sum or Average 0.114980E+12         0.114082E+10        
Minimum of Months 0.493958E+09 1867.81   -6.4 -8.0 86396452.49 126.82   -6.4 -8.0
Maximum of Months 0.188051E+11 8198.17   24.60 12.54 0.103253E+09 126.85   24.60 12.54



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.242024E+09 1638.36 13-JAN-16:30 8.35 4.30 89022331.46 128.34 03-JAN-10:30 8.35 4.30
February 0.349029E+10 4162.72 28-FEB-17:00 10.00 4.31 86391338.42 126.82 08-FEB-14:09 10.00 4.31
March 0.979014E+10 6202.27 28-MAR-17:50 9.18 2.32 0.103236E+09 126.82 07-MAR-14:09 9.18 2.32
April 0.156570E+11 8133.73 25-APR-18:10 16.73 7.64 91605336.97 126.83 24-APR-09:50 16.73 7.64
May 0.273692E+10 3221.05 31-MAY-23:30 15.80 10.39 98965836.03 126.84 30-MAY-09:39 15.80 10.39
June 0.838846E+10 5234.38 30-JUN-23:33 19.90 12.27 98962650.69 126.85 01-JUN-13:00 19.90 12.27
July 0.140012E+11 7049.44 31-JUL-23:53 19.20 11.32 91884149.03 126.84 03-JUL-13:09 19.20 11.32
August 0.186206E+11 8260.23 03-AUG-18:50 24.60 12.54 0.103250E+09 126.83 01-AUG-13:00 24.60 12.54
September 0.291773E+10 3025.79 04-SEP-17:51 31.70 16.34 91607550.86 126.85 06-SEP-13:20 24.47 18.01
October 0.612501E+10 4327.09 18-OCT-17:00 21.70 10.27 95230841.27 126.83 25-OCT-09:00 13.30 8.54
November 0.908813E+10 5688.57 03-NOV-16:00 14.30 7.69 94300358.88 126.83 08-NOV-14:00 13.20 7.65
December 0.128471E+11 7310.22 06-DEC-16:20 8.50 3.80 91880826.60 126.82 27-DEC-10:50 -12.0 -12.5
                     
Annual Sum or Average 0.103905E+12         0.113634E+10        
Minimum of Months 0.242024E+09 1638.36   8.35 2.32 86391338.42 126.82   -12.0 -12.5
Maximum of Months 0.186206E+11 8260.23   31.70 16.34 0.103250E+09 128.34   24.60 18.01



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.234676E+12 92071.65 03-JAN-17:00 -1.7 -5.3 0.206152E+10 2745.44 02-JAN-14:00 -1.7 -5.3
February 0.434211E+12 184356.90 28-FEB-17:00 10.00 4.31 0.187032E+10 2745.68 24-FEB-10:20 10.00 4.31
March 0.728250E+12 358038.15 31-MAR-24:00 2.50 0.99 0.223481E+10 2745.70 23-MAR-09:50 2.50 0.99
April 0.942814E+12 368316.92 25-APR-16:00 17.80 7.70 0.198314E+10 2747.22 24-APR-09:00 17.80 7.70
May 0.241164E+12 176652.70 31-MAY-24:00 15.50 10.27 0.214819E+10 2747.28 19-MAY-13:09 15.50 10.27
June 0.471537E+12 268627.72 30-JUN-24:00 19.60 12.23 0.214264E+10 2749.43 23-JUN-09:30 19.60 12.23
July 0.734190E+12 360924.35 31-JUL-23:53 19.20 11.32 0.199035E+10 2752.56 03-JUL-09:39 19.20 11.32
August 0.977463E+12 383626.60 06-AUG-19:52 26.10 13.21 0.241039E+10 4572.62 10-AUG-15:09 33.53 14.51
September 0.236373E+12 176028.50 30-SEP-24:00 11.80 6.26 0.198308E+10 2746.95 05-SEP-13:39 11.80 6.26
October 0.487639E+12 267971.63 31-OCT-24:00 4.70 1.47 0.206154E+10 2745.56 30-OCT-09:00 4.70 1.47
November 0.707697E+12 277147.98 06-NOV-16:55 6.70 2.26 0.204138E+10 2745.54 16-NOV-14:00 10.80 6.43
December 0.974161E+12 368477.76 06-DEC-17:00 6.70 2.38 0.198899E+10 2746.00 19-DEC-14:00 12.80 7.62
                     
Annual Sum or Average 0.717017E+13         0.249164E+11        
Minimum of Months 0.234676E+12 92071.65   -1.7 -5.3 0.187032E+10 2745.44   -1.7 -5.3
Maximum of Months 0.977463E+12 383626.60   26.10 13.21 0.241039E+10 4572.62   33.53 14.51



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: BASEMENT

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.237691E+09 13365.94 05-JAN-05:03 -4.1
February 59529971.50 13613.47 10-FEB-06:05 -19.9
March 0.159987E+09 13499.41 13-MAR-03:03 0.10
April 0.101342E+09 13883.19 18-APR-04:15 1.83
May 0.285176E+09 16154.30 20-MAY-16:25 29.45
June 0.262545E+09 15410.00 24-JUN-16:01 28.22
July 0.399095E+09 20947.84 15-JUL-16:01 32.80
August 0.337112E+09 24070.36 05-AUG-16:01 35.22
September 0.367365E+09 22320.84 02-SEP-16:01 33.98
October 0.316927E+09 13871.72 14-OCT-04:05 1.70
November 0.198356E+09 15478.80 12-NOV-11:32 -3.9
December 0.109439E+09 13931.73 07-DEC-06:05 -1.2
         
Annual Sum or Average 0.283457E+10      
Minimum of Months 59529971.50 13365.94   -19.9
Maximum of Months 0.399095E+09 24070.36   35.22



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: CORE_BOTTOM

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:05 1.38
February 0.00 0.00 01-FEB-00:05 -12.4
March 0.00 0.00 01-MAR-00:10 -3.0
April 0.00 0.00 01-APR-00:10 2.68
May 0.00 0.00 01-MAY-00:10 -1.1
June 0.00 0.00 01-JUN-00:10 15.42
July 0.00 0.00 01-JUL-00:10 19.45
August 0.00 0.00 01-AUG-00:03 18.90
September 0.00 0.00 01-SEP-00:05 18.43
October 0.00 0.00 01-OCT-00:10 11.57
November 0.00 0.00 01-NOV-00:10 4.98
December 0.00 0.00 01-DEC-00:10 -2.1
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   -12.4
Maximum of Months 0.00 0.00   19.45



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: CORE_MID

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.596444E+09 53585.05 09-JAN-05:11 -27.2
February 0.162479E+09 52815.29 06-FEB-05:01 -0.4
March 55622030.11 50009.53 06-MAR-05:01 -18.4
April 0.00 0.00 01-APR-00:10 2.68
May 0.00 0.00 01-MAY-00:10 -1.1
June 0.00 0.00 01-JUN-00:10 15.42
July 0.00 0.00 01-JUL-00:10 19.45
August 0.00 0.00 01-AUG-00:03 18.90
September 0.00 0.00 01-SEP-00:05 18.43
October 0.00 0.00 01-OCT-00:10 11.57
November 30998000.89 47660.56 27-NOV-05:01 -15.4
December 0.179315E+09 52395.62 26-DEC-05:01 -7.3
         
Annual Sum or Average 0.102486E+10      
Minimum of Months 0.00 0.00   -27.2
Maximum of Months 0.596444E+09 53585.05   19.45



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: CORE_TOP

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.820224E+10 84607.38 09-JAN-04:01 -27.2
February 0.295635E+10 82281.39 06-FEB-04:01 -0.6
March 0.173399E+10 82611.75 06-MAR-04:01 -18.4
April 60375472.44 66706.02 10-APR-05:02 3.90
May 0.565857E+09 74648.15 08-MAY-04:01 -2.3
June 0.00 0.00 01-JUN-00:10 15.42
July 0.00 0.00 01-JUL-00:10 19.45
August 0.00 0.00 01-AUG-00:03 18.90
September 167449.50 1116.33 19-SEP-05:03 2.20
October 0.306777E+09 74973.45 10-OCT-04:11 -5.4
November 0.208201E+10 81740.31 27-NOV-04:01 -15.8
December 0.426630E+10 82569.82 26-DEC-04:11 -6.5
         
Annual Sum or Average 0.201741E+11      
Minimum of Months 0.00 0.00   -27.2
Maximum of Months 0.820224E+10 84607.38   19.45



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.293254E+10 15183.82 09-JAN-04:01 -27.2
February 0.757132E+09 13840.47 04-FEB-05:01 -20.4
March 0.164960E+09 13778.24 06-MAR-05:21 -17.2
April 716153.26 9407.36 29-APR-05:01 -7.7
May 2895801.48 12318.26 08-MAY-05:01 -2.8
June 0.00 0.00 01-JUN-00:10 15.42
July 0.00 0.00 01-JUL-00:10 19.45
August 0.00 0.00 01-AUG-00:03 18.90
September 0.00 0.00 01-SEP-00:05 18.43
October 0.00 0.00 01-OCT-00:10 11.57
November 77540214.63 13687.04 27-NOV-05:01 -15.4
December 0.559180E+09 13802.84 28-DEC-05:01 -22.3
         
Annual Sum or Average 0.449496E+10      
Minimum of Months 0.00 0.00   -27.2
Maximum of Months 0.293254E+10 15183.82   19.45



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.190460E+10 17408.63 09-JAN-04:01 -27.2
February 0.550639E+09 15578.39 04-FEB-05:01 -20.4
March 0.139626E+09 16255.78 06-MAR-04:01 -18.4
April 5083997.25 12395.49 29-APR-05:01 -7.7
May 3962684.24 12427.70 08-MAY-05:01 -2.8
June 0.00 0.00 01-JUN-00:10 15.42
July 0.00 0.00 01-JUL-00:10 19.45
August 0.00 0.00 01-AUG-00:03 18.90
September 0.00 0.00 01-SEP-00:05 18.43
October 832123.20 7143.81 10-OCT-05:01 -6.1
November 94265377.57 15527.87 27-NOV-05:01 -15.4
December 0.568463E+09 15571.38 30-DEC-05:21 -20.6
         
Annual Sum or Average 0.326747E+10      
Minimum of Months 0.00 0.00   -27.2
Maximum of Months 0.190460E+10 17408.63   19.45



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.267308E+10 24929.93 10-JAN-04:01 -23.9
February 0.678310E+09 23282.19 04-FEB-04:01 -21.9
March 0.240208E+09 24251.69 06-MAR-04:01 -18.4
April 12251235.24 18885.29 29-APR-05:01 -7.7
May 37366663.37 19983.05 08-MAY-04:01 -2.3
June 0.00 0.00 01-JUN-00:10 15.42
July 0.00 0.00 01-JUL-00:10 19.45
August 0.00 0.00 01-AUG-00:03 18.90
September 3958.48 26.39 19-SEP-05:05 2.20
October 13091515.01 18296.07 10-OCT-05:01 -6.1
November 0.189766E+09 22570.37 27-NOV-05:01 -15.4
December 0.763784E+09 23352.23 29-DEC-04:01 -24.5
         
Annual Sum or Average 0.460786E+10      
Minimum of Months 0.00 0.00   -24.5
Maximum of Months 0.267308E+10 24929.93   19.45



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.985730E+09 16866.71 09-JAN-04:01 -27.2
February 99757254.76 14241.44 04-FEB-05:01 -20.4
March 18667217.87 13519.14 06-MAR-05:01 -18.4
April 0.00 0.00 01-APR-00:10 2.68
May 1401631.37 10051.39 08-MAY-05:01 -2.8
June 0.00 0.00 01-JUN-00:10 15.42
July 0.00 0.00 01-JUL-00:10 19.45
August 0.00 0.00 01-AUG-00:03 18.90
September 0.00 0.00 01-SEP-00:05 18.43
October 0.00 0.00 01-OCT-00:10 11.57
November 6413183.08 13365.40 27-NOV-05:01 -15.4
December 24707559.00 12740.64 28-DEC-05:01 -22.3
         
Annual Sum or Average 0.113668E+10      
Minimum of Months 0.00 0.00   -27.2
Maximum of Months 0.985730E+09 16866.71   19.45



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.982734E+10 16049.48 09-JAN-04:31 -27.2
February 0.446945E+10 15096.67 06-FEB-04:11 -0.6
March 0.221635E+10 15656.36 05-MAR-23:21 -16.4
April 0.328610E+09 13239.00 29-APR-04:01 -7.8
May 0.282566E+09 13210.90 01-MAY-04:01 -0.6
June 131879.84 879.20 17-JUN-05:03 2.35
July 0.00 0.00 01-JUL-00:10 19.45
August 356582.95 2377.22 18-AUG-05:03 7.30
September 58765975.56 12435.94 19-SEP-04:11 2.20
October 0.293820E+09 13133.92 10-OCT-04:01 -5.2
November 0.217575E+10 15237.09 27-NOV-03:41 -15.8
December 0.597468E+10 15574.10 31-DEC-08:61 -27.6
         
Annual Sum or Average 0.256278E+11      
Minimum of Months 0.00 0.00   -27.6
Maximum of Months 0.982734E+10 16049.48   19.45



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.590355E+10 23060.02 09-JAN-04:31 -27.2
February 0.249773E+10 21864.16 06-FEB-04:11 -0.6
March 0.125398E+10 22591.87 05-MAR-23:21 -16.4
April 0.189335E+09 19214.68 29-APR-04:01 -7.8
May 0.182221E+09 19258.67 09-MAY-04:01 -1.8
June 356971.17 2033.67 17-JUN-05:03 2.35
July 0.00 0.00 01-JUL-00:10 19.45
August 843999.05 4128.38 18-AUG-05:03 7.30
September 32618872.28 16517.65 19-SEP-04:11 2.20
October 0.168971E+09 18853.14 10-OCT-04:01 -5.2
November 0.132012E+10 22122.22 27-NOV-03:41 -15.8
December 0.358235E+10 22722.53 31-DEC-08:61 -27.6
         
Annual Sum or Average 0.151321E+11      
Minimum of Months 0.00 0.00   -27.6
Maximum of Months 0.590355E+10 23060.02   19.45



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.637183E+10 27759.55 09-JAN-02:31 -27.2
February 0.236253E+10 26337.78 06-FEB-04:11 -0.6
March 0.138939E+10 27074.74 06-MAR-04:01 -18.4
April 0.256898E+09 23234.03 29-APR-04:01 -7.8
May 0.292058E+09 23403.08 09-MAY-04:01 -1.8
June 1928547.00 6678.64 17-JUN-05:03 2.35
July 0.00 0.00 01-JUL-00:10 19.45
August 670105.39 4164.38 18-AUG-05:03 7.30
September 36552767.05 16378.51 19-SEP-04:11 2.20
October 0.157863E+09 23175.06 10-OCT-04:01 -5.2
November 0.127731E+10 26739.92 27-NOV-03:41 -15.8
December 0.356609E+10 27562.41 31-DEC-08:61 -27.6
         
Annual Sum or Average 0.157131E+11      
Minimum of Months 0.00 0.00   -27.6
Maximum of Months 0.637183E+10 27759.55   19.45



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.536237E+10 23580.91 09-JAN-02:31 -27.2
February 0.202731E+10 22234.46 06-FEB-04:11 -0.6
March 0.102469E+10 22881.61 06-MAR-04:01 -18.4
April 0.121450E+09 18848.38 29-APR-04:01 -7.8
May 0.141689E+09 19594.01 22-MAY-04:01 -0.1
June 654883.22 2774.61 17-JUN-05:03 2.35
July 0.00 0.00 01-JUL-00:10 19.45
August 289821.70 1932.14 18-AUG-05:03 7.30
September 24316097.96 13239.73 19-SEP-04:11 2.20
October 0.122004E+09 19258.18 10-OCT-04:01 -5.2
November 0.985915E+09 21760.43 27-NOV-04:21 -15.7
December 0.283477E+10 23253.96 31-DEC-08:61 -27.6
         
Annual Sum or Average 0.126455E+11      
Minimum of Months 0.00 0.00   -27.6
Maximum of Months 0.536237E+10 23580.91   19.45



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.160589E+11 19801.96 09-JAN-04:01 -27.2
February 0.839900E+10 18529.54 05-FEB-00:02 -19.9
March 0.529715E+10 18938.38 05-MAR-23:21 -16.4
April 0.146555E+10 16537.95 29-APR-03:01 -6.9
May 0.115910E+10 17275.49 08-MAY-03:11 -2.6
June 30254036.91 14656.37 17-JUN-04:12 2.03
July 2060.86 10.30 08-JUL-05:03 6.23
August 21057357.84 13401.82 18-AUG-04:12 7.20
September 0.399335E+09 15839.30 19-SEP-04:11 2.20
October 0.147958E+10 16701.57 10-OCT-03:01 -4.1
November 0.562038E+10 18837.07 27-NOV-05:11 -15.3
December 0.117709E+11 18513.77 31-DEC-08:11 -27.4
         
Annual Sum or Average 0.517013E+11      
Minimum of Months 2060.86 10.30   -27.4
Maximum of Months 0.160589E+11 19801.96   7.20



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.971572E+10 25429.25 09-JAN-04:01 -27.2
February 0.467213E+10 23650.73 05-FEB-00:02 -19.9
March 0.291744E+10 24183.39 05-MAR-23:21 -16.4
April 0.753374E+09 21178.14 29-APR-03:01 -6.9
May 0.666279E+09 22224.25 08-MAY-03:11 -2.6
June 18129317.38 18841.65 17-JUN-04:12 2.03
July 13601.29 68.01 08-JUL-05:03 6.23
August 12127308.98 10222.89 18-AUG-04:12 7.20
September 0.210677E+09 20328.01 19-SEP-04:11 2.20
October 0.778202E+09 21301.34 10-OCT-03:01 -4.1
November 0.317877E+10 23793.40 27-NOV-05:11 -15.3
December 0.702099E+10 23781.87 31-DEC-07:31 -28.0
         
Annual Sum or Average 0.299438E+11      
Minimum of Months 13601.29 68.01   -28.0
Maximum of Months 0.971572E+10 25429.25   7.20



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.113646E+11 32105.65 09-JAN-04:01 -27.2
February 0.507273E+10 29877.52 05-FEB-00:02 -19.9
March 0.372123E+10 30455.95 05-MAR-23:21 -16.4
April 0.117755E+10 26866.81 29-APR-03:01 -6.9
May 0.114427E+10 28243.39 08-MAY-03:11 -2.6
June 58350574.39 24012.41 17-JUN-04:12 2.03
July 764356.25 3486.92 08-JUL-05:03 6.23
August 27551546.83 14481.75 18-AUG-04:12 7.20
September 0.275179E+09 25565.44 19-SEP-04:11 2.20
October 0.866386E+09 27147.32 10-OCT-03:01 -4.1
November 0.342548E+10 30033.40 27-NOV-05:11 -15.3
December 0.779858E+10 30182.68 31-DEC-08:11 -27.4
         
Annual Sum or Average 0.349326E+11      
Minimum of Months 764356.25 3486.92   -27.4
Maximum of Months 0.113646E+11 32105.65   7.20



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.911193E+10 28460.14 09-JAN-04:01 -27.2
February 0.391664E+10 25998.70 05-FEB-00:02 -19.9
March 0.246234E+10 26627.74 05-MAR-23:21 -16.4
April 0.579325E+09 22880.74 01-APR-04:11 6.33
May 0.532487E+09 24806.97 08-MAY-03:11 -2.6
June 19811610.61 16296.36 17-JUN-04:12 2.03
July 0.00 0.00 01-JUL-00:10 19.45
August 13694807.42 8546.53 18-AUG-05:03 7.30
September 0.163235E+09 22523.15 19-SEP-04:11 2.20
October 0.587955E+09 23828.79 10-OCT-03:01 -4.1
November 0.246998E+10 26473.91 27-NOV-05:11 -15.3
December 0.570177E+10 26466.83 31-DEC-08:11 -27.4
         
Annual Sum or Average 0.255592E+11      
Minimum of Months 0.00 0.00   -27.4
Maximum of Months 0.911193E+10 28460.14   19.45



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: GROUNDFLOOR_PLENUM

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.210506E+10 12390.51 24-JAN-06:02 8.22
February 0.874119E+09 12818.93 26-FEB-16:22 15.85
March 0.348802E+09 11892.19 09-MAR-06:03 2.30
April 0.139218E+09 15127.76 16-APR-15:31 19.80
May 74335535.86 10162.65 01-MAY-04:01 -0.6
June 90342864.91 10616.78 18-JUN-15:22 24.70
July 0.130746E+09 13630.25 16-JUL-15:51 32.80
August 0.107508E+09 15402.30 06-AUG-16:01 35.50
September 92597419.05 12488.04 03-SEP-15:41 34.03
October 97106586.40 15202.98 15-OCT-14:51 22.80
November 0.210368E+09 13031.96 24-NOV-05:11 12.20
December 0.395773E+09 13471.44 04-DEC-05:01 1.32
         
Annual Sum or Average 0.466597E+10      
Minimum of Months 74335535.86 10162.65   -0.6
Maximum of Months 0.210506E+10 15402.30   35.50



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: MIDFLOOR_PLENUM

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.553483E+10 15951.19 09-JAN-06:11 -27.2
February 0.300316E+10 13125.49 26-FEB-14:41 16.52
March 0.162936E+10 12331.88 26-MAR-13:32 9.63
April 0.212343E+09 18500.84 16-APR-16:21 20.00
May 0.447507E+09 9004.49 28-MAY-17:11 20.73
June 72682173.04 14248.40 18-JUN-15:41 24.90
July 0.103369E+09 15405.20 16-JUL-16:21 33.05
August 55308319.00 15767.48 06-AUG-16:01 35.50
September 0.102343E+09 15241.34 04-SEP-15:31 32.60
October 0.335508E+09 14082.83 15-OCT-15:42 22.30
November 0.149645E+10 11404.07 12-NOV-13:32 -0.6
December 0.311229E+10 12885.37 26-DEC-06:12 -8.0
         
Annual Sum or Average 0.161052E+11      
Minimum of Months 55308319.00 9004.49   -27.2
Maximum of Months 0.553483E+10 18500.84   35.50



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: TOPFLOOR_PLENUM

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.193915E+11 36992.62 09-JAN-05:04 -27.2
February 0.103311E+11 31340.76 04-FEB-05:22 -20.0
March 0.719700E+10 33475.51 06-MAR-05:09 -18.4
April 0.271619E+10 15472.75 29-APR-05:13 -7.6
May 0.212322E+10 23072.91 08-MAY-04:13 -2.4
June 0.402283E+09 16265.15 20-JUN-05:03 9.68
July 0.160093E+09 16891.30 12-JUL-05:03 6.85
August 0.289374E+09 16289.91 03-AUG-05:03 8.12
September 0.106465E+10 14921.24 27-SEP-05:03 8.95
October 0.278701E+10 23898.81 10-OCT-04:22 -5.5
November 0.759946E+10 33707.18 27-NOV-05:31 -15.0
December 0.145189E+11 34491.44 29-DEC-06:12 -25.2
         
Annual Sum or Average 0.685807E+11      
Minimum of Months 0.160093E+09 14921.24   -27.2
Maximum of Months 0.193915E+11 36992.62   9.68



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.108924E+09 659.94 08-JAN-22:15 -26.7
February 0.00 0.00 01-FEB-00:05 -12.4
March 0.00 0.00 01-MAR-00:10 -3.0
April 0.00 0.00 01-APR-00:10 2.68
May 0.00 0.00 01-MAY-00:10 -1.1
June 0.00 0.00 01-JUN-00:10 15.42
July 0.00 0.00 01-JUL-00:10 19.45
August 0.00 0.00 01-AUG-00:03 18.90
September 0.00 0.00 01-SEP-00:05 18.43
October 0.00 0.00 01-OCT-00:10 11.57
November 0.00 0.00 01-NOV-00:10 4.98
December 0.00 0.00 01-DEC-00:10 -2.1
         
Annual Sum or Average 0.108924E+09      
Minimum of Months 0.00 0.00   -26.7
Maximum of Months 0.108924E+09 659.94   19.45



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: DATACENTER_MID_ZN_6

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.678654E+09 682.37 29-JAN-18:20 -23.3
February 0.00 0.00 01-FEB-00:05 -12.4
March 0.00 0.00 01-MAR-00:10 -3.0
April 0.00 0.00 01-APR-00:10 2.68
May 7717239.95 348.70 08-MAY-04:20 -2.4
June 0.00 0.00 01-JUN-00:10 15.42
July 0.00 0.00 01-JUL-00:10 19.45
August 0.00 0.00 01-AUG-00:03 18.90
September 0.00 0.00 01-SEP-00:05 18.43
October 0.00 0.00 01-OCT-00:10 11.57
November 0.00 0.00 01-NOV-00:10 4.98
December 0.00 0.00 01-DEC-00:10 -2.1
         
Annual Sum or Average 0.686372E+09      
Minimum of Months 0.00 0.00   -23.3
Maximum of Months 0.678654E+09 682.37   19.45



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.918145E+09 732.67 29-JAN-17:40 -21.7
February 70718246.87 656.03 05-FEB-19:35 -18.0
March 0.00 0.00 01-MAR-00:10 -3.0
April 2580523.81 785.14 30-APR-23:05 -1.3
May 0.135846E+09 688.86 01-MAY-00:20 -1.1
June 0.00 0.00 01-JUN-00:10 15.42
July 0.00 0.00 01-JUL-00:10 19.45
August 0.00 0.00 01-AUG-00:03 18.90
September 40753706.54 628.88 19-SEP-04:23 2.20
October 869027.25 477.15 10-OCT-01:33 -2.9
November 0.00 0.00 01-NOV-00:10 4.98
December 0.00 0.00 01-DEC-00:10 -2.1
         
Annual Sum or Average 0.116891E+10      
Minimum of Months 0.00 0.00   -21.7
Maximum of Months 0.918145E+09 785.14   19.45



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:05 1.38
February 0.00 0.00 01-FEB-00:05 -12.4
March 0.00 0.00 01-MAR-00:10 -3.0
April 0.00 0.00 01-APR-00:10 2.68
May 0.00 0.00 01-MAY-00:10 -1.1
June 0.00 0.00 01-JUN-00:10 15.42
July 0.00 0.00 01-JUL-00:10 19.45
August 0.00 0.00 01-AUG-00:03 18.90
September 0.00 0.00 01-SEP-00:05 18.43
October 0.00 0.00 01-OCT-00:10 11.57
November 0.00 0.00 01-NOV-00:10 4.98
December 0.00 0.00 01-DEC-00:10 -2.1
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   -12.4
Maximum of Months 0.00 0.00   19.45



Table of Contents

Report: ZoneElectricSummaryMonthly

For: BASEMENT

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.219312E+11 22950.34 02-JAN-08:09 0.360447E+11 13457.54 01-JAN-00:10
February 0.198933E+11 22950.34 01-FEB-08:09 0.325565E+11 13457.54 01-FEB-00:10
March 0.236388E+11 22950.34 01-MAR-08:09 0.360447E+11 13457.54 01-MAR-00:10
April 0.211142E+11 22950.34 03-APR-07:10 0.348820E+11 13457.54 01-APR-00:10
May 0.227850E+11 22950.34 01-MAY-07:10 0.360447E+11 13457.54 01-MAY-00:10
June 0.226748E+11 22950.34 01-JUN-07:10 0.348820E+11 13457.54 01-JUN-00:10
July 0.212244E+11 22950.34 03-JUL-07:10 0.360447E+11 13457.54 01-JUL-00:10
August 0.236388E+11 22950.34 01-AUG-07:10 0.360447E+11 13457.54 01-AUG-00:10
September 0.211142E+11 22950.34 01-SEP-07:10 0.348820E+11 13457.54 01-SEP-00:10
October 0.219312E+11 22950.34 02-OCT-07:10 0.360447E+11 13457.54 01-OCT-00:10
November 0.216742E+11 22950.34 01-NOV-07:10 0.348820E+11 13457.54 01-NOV-00:10
December 0.212244E+11 22950.34 01-DEC-08:09 0.360447E+11 13457.54 01-DEC-00:10
             
Annual Sum or Average 0.262844E+12     0.424397E+12    
Minimum of Months 0.198933E+11 22950.34   0.325565E+11 13457.54  
Maximum of Months 0.236388E+11 22950.34   0.360447E+11 13457.54  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: CORE_BOTTOM

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.196958E+11 20611.01 02-JAN-08:09 0.243681E+11 17206.63 02-JAN-08:09
February 0.178655E+11 20611.01 01-FEB-08:09 0.220609E+11 17206.63 01-FEB-08:09
March 0.212293E+11 20611.01 01-MAR-08:09 0.253549E+11 17206.63 01-MAR-08:09
April 0.189620E+11 20611.01 03-APR-07:10 0.235306E+11 17206.63 03-APR-07:10
May 0.204625E+11 20611.01 01-MAY-07:10 0.248615E+11 17206.63 01-MAY-07:10
June 0.203636E+11 20611.01 01-JUN-07:10 0.244160E+11 17206.63 01-JUN-07:10
July 0.190610E+11 20611.01 03-JUL-07:10 0.239708E+11 17206.63 03-JUL-07:10
August 0.212293E+11 20611.01 01-AUG-07:10 0.253549E+11 17206.63 01-AUG-07:10
September 0.189620E+11 20611.01 01-SEP-07:10 0.235199E+11 17206.63 01-SEP-07:10
October 0.196958E+11 20611.01 02-OCT-07:10 0.243735E+11 17206.63 02-OCT-07:10
November 0.194649E+11 20611.01 01-NOV-07:10 0.238373E+11 17206.63 01-NOV-07:10
December 0.190610E+11 20611.01 01-DEC-08:09 0.239654E+11 17206.63 01-DEC-08:09
             
Annual Sum or Average 0.236053E+12     0.289614E+12    
Minimum of Months 0.178655E+11 20611.01   0.220609E+11 17206.63  
Maximum of Months 0.212293E+11 20611.01   0.253549E+11 17206.63  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: CORE_MID

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.196958E+11 20611.01 02-JAN-08:09 0.243680E+11 17206.56 02-JAN-08:09
February 0.178655E+11 20611.01 01-FEB-08:09 0.220609E+11 17206.56 01-FEB-08:09
March 0.212293E+11 20611.01 01-MAR-08:09 0.253548E+11 17206.56 01-MAR-08:09
April 0.189620E+11 20611.01 03-APR-07:10 0.235305E+11 17206.56 03-APR-07:10
May 0.204625E+11 20611.01 01-MAY-07:10 0.248614E+11 17206.56 01-MAY-07:10
June 0.203636E+11 20611.01 01-JUN-07:10 0.244159E+11 17206.56 01-JUN-07:10
July 0.190610E+11 20611.01 03-JUL-07:10 0.239707E+11 17206.56 03-JUL-07:10
August 0.212293E+11 20611.01 01-AUG-07:10 0.253548E+11 17206.56 01-AUG-07:10
September 0.189620E+11 20611.01 01-SEP-07:10 0.235198E+11 17206.56 01-SEP-07:10
October 0.196958E+11 20611.01 02-OCT-07:10 0.243734E+11 17206.56 02-OCT-07:10
November 0.194649E+11 20611.01 01-NOV-07:10 0.238372E+11 17206.56 01-NOV-07:10
December 0.190610E+11 20611.01 01-DEC-08:09 0.239653E+11 17206.56 01-DEC-08:09
             
Annual Sum or Average 0.236053E+12     0.289613E+12    
Minimum of Months 0.178655E+11 20611.01   0.220609E+11 17206.56  
Maximum of Months 0.212293E+11 20611.01   0.253548E+11 17206.56  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: CORE_TOP

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.196958E+11 20611.01 02-JAN-08:09 0.243680E+11 17206.56 02-JAN-08:09
February 0.178655E+11 20611.01 01-FEB-08:09 0.220609E+11 17206.56 01-FEB-08:09
March 0.212293E+11 20611.01 01-MAR-08:09 0.253548E+11 17206.56 01-MAR-08:09
April 0.189620E+11 20611.01 03-APR-07:10 0.235305E+11 17206.56 03-APR-07:10
May 0.204625E+11 20611.01 01-MAY-07:10 0.248614E+11 17206.56 01-MAY-07:10
June 0.203636E+11 20611.01 01-JUN-07:10 0.244159E+11 17206.56 01-JUN-07:10
July 0.190610E+11 20611.01 03-JUL-07:10 0.239707E+11 17206.56 03-JUL-07:10
August 0.212293E+11 20611.01 01-AUG-07:10 0.253548E+11 17206.56 01-AUG-07:10
September 0.189620E+11 20611.01 01-SEP-07:10 0.235198E+11 17206.56 01-SEP-07:10
October 0.196958E+11 20611.01 02-OCT-07:10 0.243734E+11 17206.56 02-OCT-07:10
November 0.194649E+11 20611.01 01-NOV-07:10 0.238372E+11 17206.56 01-NOV-07:10
December 0.190610E+11 20611.01 01-DEC-08:09 0.239653E+11 17206.56 01-DEC-08:09
             
Annual Sum or Average 0.236053E+12     0.289613E+12    
Minimum of Months 0.178655E+11 20611.01   0.220609E+11 17206.56  
Maximum of Months 0.212293E+11 20611.01   0.253548E+11 17206.56  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.174381E+10 2587.92 02-JAN-08:09 0.305979E+10 2160.55 02-JAN-08:09
February 0.139771E+10 2255.20 01-FEB-08:09 0.277008E+10 2160.55 01-FEB-08:09
March 0.154554E+10 2587.92 17-MAR-07:10 0.318369E+10 2160.55 01-MAR-08:09
April 0.131532E+10 1922.48 14-APR-07:10 0.295462E+10 2160.55 03-APR-07:10
May 0.136508E+10 1803.00 03-MAY-07:10 0.312174E+10 2160.55 01-MAY-07:10
June 0.132347E+10 1350.81 16-JUN-07:10 0.306580E+10 2160.55 01-JUN-07:10
July 0.126804E+10 1470.28 07-JUL-07:30 0.300989E+10 2160.55 03-JUL-07:10
August 0.142258E+10 1470.28 17-AUG-07:10 0.318369E+10 2160.55 01-AUG-07:10
September 0.135065E+10 2255.20 11-SEP-07:10 0.295328E+10 2160.55 01-SEP-07:10
October 0.150063E+10 2587.92 25-OCT-07:10 0.306046E+10 2160.55 02-OCT-07:10
November 0.163650E+10 2587.92 01-NOV-07:10 0.299314E+10 2160.55 01-NOV-07:10
December 0.170473E+10 2587.92 01-DEC-08:09 0.300922E+10 2160.55 01-DEC-08:09
             
Annual Sum or Average 0.175741E+11     0.363654E+11    
Minimum of Months 0.126804E+10 1350.81   0.277008E+10 2160.55  
Maximum of Months 0.174381E+10 2587.92   0.318369E+10 2160.55  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.108190E+10 1667.75 02-JAN-08:09 0.197184E+10 1392.34 02-JAN-08:09
February 0.881552E+09 1453.34 01-FEB-16:00 0.178515E+10 1392.34 01-FEB-08:09
March 0.984042E+09 1667.75 17-MAR-07:10 0.205169E+10 1392.34 01-MAR-08:09
April 0.843269E+09 1161.92 14-APR-07:10 0.190407E+10 1392.34 03-APR-07:10
May 0.881907E+09 947.51 03-MAY-07:10 0.201177E+10 1392.34 01-MAY-07:10
June 0.860755E+09 793.52 01-JUN-07:10 0.197572E+10 1392.34 01-JUN-07:10
July 0.819192E+09 870.51 07-JUL-07:19 0.193969E+10 1392.34 03-JUL-07:10
August 0.920811E+09 870.51 17-AUG-07:10 0.205169E+10 1392.34 01-AUG-07:10
September 0.863747E+09 1161.92 13-SEP-07:10 0.190321E+10 1392.34 01-SEP-07:10
October 0.943330E+09 1667.75 25-OCT-07:10 0.197228E+10 1392.34 02-OCT-07:10
November 0.102538E+10 1667.75 01-NOV-07:10 0.192889E+10 1392.34 01-NOV-07:10
December 0.105698E+10 1667.75 01-DEC-08:09 0.193926E+10 1392.34 01-DEC-08:09
             
Annual Sum or Average 0.111629E+11     0.234352E+11    
Minimum of Months 0.819192E+09 793.52   0.178515E+10 1392.34  
Maximum of Months 0.108190E+10 1667.75   0.205169E+10 1392.34  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.164382E+10 2587.98 02-JAN-08:09 0.305983E+10 2160.58 02-JAN-08:09
February 0.133999E+10 2255.25 02-FEB-08:09 0.277013E+10 2160.58 01-FEB-08:09
March 0.152355E+10 2587.98 17-MAR-07:10 0.318374E+10 2160.58 01-MAR-08:09
April 0.131605E+10 1922.52 14-APR-07:10 0.295467E+10 2160.58 03-APR-07:10
May 0.137335E+10 1803.04 03-MAY-07:10 0.312179E+10 2160.58 01-MAY-07:10
June 0.133953E+10 1350.84 16-JUN-07:10 0.306585E+10 2160.58 01-JUN-07:10
July 0.127798E+10 1470.31 07-JUL-07:30 0.300994E+10 2160.58 03-JUL-07:10
August 0.143269E+10 1470.31 17-AUG-07:10 0.318374E+10 2160.58 01-AUG-07:10
September 0.134306E+10 1803.04 11-SEP-07:10 0.295333E+10 2160.58 01-SEP-07:10
October 0.145065E+10 2587.98 25-OCT-07:10 0.306051E+10 2160.58 02-OCT-07:10
November 0.154327E+10 2587.98 01-NOV-07:10 0.299318E+10 2160.58 01-NOV-07:10
December 0.158769E+10 2587.98 01-DEC-08:09 0.300927E+10 2160.58 01-DEC-08:09
             
Annual Sum or Average 0.171716E+11     0.363660E+11    
Minimum of Months 0.127798E+10 1350.84   0.277013E+10 2160.58  
Maximum of Months 0.164382E+10 2587.98   0.318374E+10 2160.58  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.109494E+10 1667.75 02-JAN-08:09 0.197183E+10 1392.33 02-JAN-08:09
February 0.881197E+09 1667.75 02-FEB-08:09 0.178514E+10 1392.33 01-FEB-08:09
March 0.991184E+09 1667.75 17-MAR-07:10 0.205168E+10 1392.33 01-MAR-08:09
April 0.850687E+09 1453.34 14-APR-07:10 0.190406E+10 1392.33 03-APR-07:10
May 0.882212E+09 1161.92 03-MAY-07:10 0.201175E+10 1392.33 01-MAY-07:10
June 0.855951E+09 870.51 01-JUN-07:10 0.197570E+10 1392.33 01-JUN-07:10
July 0.820794E+09 947.51 07-JUL-07:10 0.193968E+10 1392.33 03-JUL-07:10
August 0.919730E+09 1161.92 17-AUG-07:10 0.205168E+10 1392.33 01-AUG-07:10
September 0.869326E+09 1453.34 11-SEP-07:10 0.190319E+10 1392.33 01-SEP-07:10
October 0.956001E+09 1667.75 25-OCT-07:10 0.197226E+10 1392.33 02-OCT-07:10
November 0.101877E+10 1667.75 01-NOV-07:10 0.192888E+10 1392.33 01-NOV-07:10
December 0.105701E+10 1667.75 01-DEC-08:09 0.193924E+10 1392.33 01-DEC-08:09
             
Annual Sum or Average 0.111978E+11     0.234351E+11    
Minimum of Months 0.820794E+09 870.51   0.178514E+10 1392.33  
Maximum of Months 0.109494E+10 1667.75   0.205168E+10 1392.33  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.173790E+10 2587.92 02-JAN-08:09 0.305979E+10 2160.55 02-JAN-08:09
February 0.139282E+10 2255.20 01-FEB-08:09 0.277008E+10 2160.55 01-FEB-08:09
March 0.154262E+10 2587.92 17-MAR-07:10 0.318369E+10 2160.55 01-MAR-08:09
April 0.131304E+10 1803.00 14-APR-07:10 0.295462E+10 2160.55 03-APR-07:10
May 0.136393E+10 1803.00 03-MAY-07:10 0.312174E+10 2160.55 01-MAY-07:10
June 0.132282E+10 1350.81 26-JUN-11:30 0.306580E+10 2160.55 01-JUN-07:10
July 0.126757E+10 1470.28 07-JUL-07:30 0.300989E+10 2160.55 03-JUL-07:10
August 0.142176E+10 1470.28 17-AUG-07:10 0.318369E+10 2160.55 01-AUG-07:10
September 0.134796E+10 2135.72 11-SEP-07:10 0.295328E+10 2160.55 01-SEP-07:10
October 0.149665E+10 2587.92 25-OCT-07:10 0.306046E+10 2160.55 02-OCT-07:10
November 0.163103E+10 2587.92 01-NOV-07:10 0.299314E+10 2160.55 01-NOV-07:10
December 0.169690E+10 2587.92 01-DEC-08:09 0.300922E+10 2160.55 01-DEC-08:09
             
Annual Sum or Average 0.175350E+11     0.363654E+11    
Minimum of Months 0.126757E+10 1350.81   0.277008E+10 2160.55  
Maximum of Months 0.173790E+10 2587.92   0.318369E+10 2160.55  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.108005E+10 1667.75 02-JAN-08:09 0.197184E+10 1392.34 02-JAN-08:09
February 0.880010E+09 1453.34 01-FEB-16:00 0.178515E+10 1392.34 01-FEB-08:09
March 0.983117E+09 1667.75 17-MAR-07:10 0.205169E+10 1392.34 01-MAR-08:09
April 0.842267E+09 1161.92 14-APR-07:10 0.190407E+10 1392.34 03-APR-07:10
May 0.881149E+09 947.51 03-MAY-07:10 0.201177E+10 1392.34 01-MAY-07:10
June 0.860164E+09 793.52 01-JUN-07:10 0.197572E+10 1392.34 01-JUN-07:10
July 0.818786E+09 870.51 07-JUL-07:19 0.193969E+10 1392.34 03-JUL-07:10
August 0.920152E+09 870.51 17-AUG-07:10 0.205169E+10 1392.34 01-AUG-07:10
September 0.863092E+09 1161.92 13-SEP-07:10 0.190321E+10 1392.34 01-SEP-07:10
October 0.941851E+09 1667.75 25-OCT-07:10 0.197228E+10 1392.34 02-OCT-07:10
November 0.102332E+10 1667.75 01-NOV-07:10 0.192889E+10 1392.34 01-NOV-07:10
December 0.105379E+10 1667.75 01-DEC-08:09 0.193926E+10 1392.34 01-DEC-08:09
             
Annual Sum or Average 0.111478E+11     0.234352E+11    
Minimum of Months 0.818786E+09 793.52   0.178515E+10 1392.34  
Maximum of Months 0.108005E+10 1667.75   0.205169E+10 1392.34  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.164230E+10 2587.98 02-JAN-08:09 0.305983E+10 2160.58 02-JAN-08:09
February 0.133845E+10 2135.77 02-FEB-08:09 0.277013E+10 2160.58 01-FEB-08:09
March 0.152209E+10 2587.98 17-MAR-07:10 0.318374E+10 2160.58 01-MAR-08:09
April 0.131450E+10 1803.04 14-APR-07:10 0.295467E+10 2160.58 03-APR-07:10
May 0.137194E+10 1803.04 03-MAY-07:10 0.312179E+10 2160.58 01-MAY-07:10
June 0.133817E+10 1350.84 16-JUN-07:10 0.306585E+10 2160.58 01-JUN-07:10
July 0.127704E+10 1470.31 07-JUL-07:30 0.300994E+10 2160.58 03-JUL-07:10
August 0.143133E+10 1470.31 17-AUG-07:10 0.318374E+10 2160.58 01-AUG-07:10
September 0.134179E+10 1803.04 11-SEP-07:10 0.295333E+10 2160.58 01-SEP-07:10
October 0.144782E+10 2587.98 25-OCT-07:10 0.306051E+10 2160.58 02-OCT-07:10
November 0.154216E+10 2587.98 01-NOV-07:10 0.299318E+10 2160.58 01-NOV-07:10
December 0.158618E+10 2587.98 01-DEC-08:09 0.300927E+10 2160.58 01-DEC-08:09
             
Annual Sum or Average 0.171538E+11     0.363660E+11    
Minimum of Months 0.127704E+10 1350.84   0.277013E+10 2160.58  
Maximum of Months 0.164230E+10 2587.98   0.318374E+10 2160.58  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.109244E+10 1667.75 02-JAN-08:09 0.197183E+10 1392.33 02-JAN-08:09
February 0.879043E+09 1667.75 02-FEB-08:09 0.178514E+10 1392.33 01-FEB-08:09
March 0.989598E+09 1667.75 17-MAR-07:10 0.205168E+10 1392.33 01-MAR-08:09
April 0.849759E+09 1453.34 14-APR-07:10 0.190406E+10 1392.33 03-APR-07:10
May 0.881584E+09 1161.92 03-MAY-07:10 0.201175E+10 1392.33 01-MAY-07:10
June 0.855318E+09 870.51 01-JUN-07:10 0.197570E+10 1392.33 01-JUN-07:10
July 0.820198E+09 947.51 07-JUL-07:19 0.193968E+10 1392.33 03-JUL-07:10
August 0.919058E+09 1161.92 17-AUG-07:10 0.205168E+10 1392.33 01-AUG-07:10
September 0.867819E+09 1453.34 11-SEP-07:10 0.190319E+10 1392.33 01-SEP-07:10
October 0.953826E+09 1667.75 25-OCT-07:10 0.197226E+10 1392.33 02-OCT-07:10
November 0.101719E+10 1667.75 01-NOV-07:10 0.192888E+10 1392.33 01-NOV-07:10
December 0.105466E+10 1667.75 01-DEC-08:09 0.193924E+10 1392.33 01-DEC-08:09
             
Annual Sum or Average 0.111805E+11     0.234351E+11    
Minimum of Months 0.820198E+09 870.51   0.178514E+10 1392.33  
Maximum of Months 0.109244E+10 1667.75   0.205168E+10 1392.33  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.173741E+10 2587.92 02-JAN-08:09 0.305979E+10 2160.55 02-JAN-08:09
February 0.139270E+10 2255.20 01-FEB-08:09 0.277008E+10 2160.55 01-FEB-08:09
March 0.154243E+10 2587.92 17-MAR-07:10 0.318369E+10 2160.55 01-MAR-08:09
April 0.131285E+10 1803.00 14-APR-07:10 0.295462E+10 2160.55 03-APR-07:10
May 0.136379E+10 1803.00 03-MAY-07:10 0.312174E+10 2160.55 01-MAY-07:10
June 0.132280E+10 1350.81 26-JUN-11:30 0.306580E+10 2160.55 01-JUN-07:10
July 0.126753E+10 1470.28 07-JUL-07:30 0.300989E+10 2160.55 03-JUL-07:10
August 0.142174E+10 1470.28 17-AUG-07:10 0.318369E+10 2160.55 01-AUG-07:10
September 0.134791E+10 2135.72 11-SEP-07:10 0.295328E+10 2160.55 01-SEP-07:10
October 0.149638E+10 2587.92 25-OCT-07:10 0.306046E+10 2160.55 02-OCT-07:10
November 0.163094E+10 2587.92 01-NOV-07:10 0.299314E+10 2160.55 01-NOV-07:10
December 0.169650E+10 2587.92 01-DEC-08:09 0.300922E+10 2160.55 01-DEC-08:09
             
Annual Sum or Average 0.175330E+11     0.363654E+11    
Minimum of Months 0.126753E+10 1350.81   0.277008E+10 2160.55  
Maximum of Months 0.173741E+10 2587.92   0.318369E+10 2160.55  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.108005E+10 1667.75 02-JAN-08:09 0.197184E+10 1392.34 02-JAN-08:09
February 0.879921E+09 1453.34 01-FEB-16:00 0.178515E+10 1392.34 01-FEB-08:09
March 0.983000E+09 1667.75 17-MAR-07:10 0.205169E+10 1392.34 01-MAR-08:09
April 0.842267E+09 1161.92 14-APR-07:10 0.190407E+10 1392.34 03-APR-07:10
May 0.881111E+09 947.51 03-MAY-07:10 0.201177E+10 1392.34 01-MAY-07:10
June 0.860144E+09 793.52 01-JUN-07:10 0.197572E+10 1392.34 01-JUN-07:10
July 0.818786E+09 870.51 07-JUL-07:19 0.193969E+10 1392.34 03-JUL-07:10
August 0.920121E+09 870.51 17-AUG-07:10 0.205169E+10 1392.34 01-AUG-07:10
September 0.863067E+09 1161.92 13-SEP-07:10 0.190321E+10 1392.34 01-SEP-07:10
October 0.942030E+09 1667.75 25-OCT-07:10 0.197228E+10 1392.34 02-OCT-07:10
November 0.102372E+10 1667.75 01-NOV-07:10 0.192889E+10 1392.34 01-NOV-07:10
December 0.105379E+10 1667.75 01-DEC-08:09 0.193926E+10 1392.34 01-DEC-08:09
             
Annual Sum or Average 0.111480E+11     0.234352E+11    
Minimum of Months 0.818786E+09 793.52   0.178515E+10 1392.34  
Maximum of Months 0.108005E+10 1667.75   0.205169E+10 1392.34  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.164223E+10 2587.98 02-JAN-08:09 0.305983E+10 2160.58 02-JAN-08:09
February 0.133845E+10 2135.77 02-FEB-08:09 0.277013E+10 2160.58 01-FEB-08:09
March 0.152206E+10 2587.98 17-MAR-07:10 0.318374E+10 2160.58 01-MAR-08:09
April 0.131444E+10 1803.04 14-APR-07:10 0.295467E+10 2160.58 03-APR-07:10
May 0.137194E+10 1803.04 03-MAY-07:10 0.312179E+10 2160.58 01-MAY-07:10
June 0.133817E+10 1350.84 16-JUN-07:10 0.306585E+10 2160.58 01-JUN-07:10
July 0.127701E+10 1470.31 07-JUL-07:30 0.300994E+10 2160.58 03-JUL-07:10
August 0.143131E+10 1470.31 17-AUG-07:10 0.318374E+10 2160.58 01-AUG-07:10
September 0.134174E+10 1803.04 11-SEP-07:10 0.295333E+10 2160.58 01-SEP-07:10
October 0.144782E+10 2587.98 25-OCT-07:10 0.306051E+10 2160.58 02-OCT-07:10
November 0.154216E+10 2587.98 01-NOV-07:10 0.299318E+10 2160.58 01-NOV-07:10
December 0.158598E+10 2587.98 01-DEC-08:09 0.300927E+10 2160.58 01-DEC-08:09
             
Annual Sum or Average 0.171533E+11     0.363660E+11    
Minimum of Months 0.127701E+10 1350.84   0.277013E+10 2160.58  
Maximum of Months 0.164223E+10 2587.98   0.318374E+10 2160.58  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.109232E+10 1667.75 02-JAN-08:09 0.197183E+10 1392.33 02-JAN-08:09
February 0.878986E+09 1667.75 02-FEB-08:09 0.178514E+10 1392.33 01-FEB-08:09
March 0.989552E+09 1667.75 17-MAR-07:10 0.205168E+10 1392.33 01-MAR-08:09
April 0.849759E+09 1453.34 14-APR-07:10 0.190406E+10 1392.33 03-APR-07:10
May 0.881564E+09 1161.92 03-MAY-07:10 0.201175E+10 1392.33 01-MAY-07:10
June 0.855305E+09 870.51 01-JUN-07:10 0.197570E+10 1392.33 01-JUN-07:10
July 0.820186E+09 947.51 07-JUL-07:19 0.193968E+10 1392.33 03-JUL-07:10
August 0.919058E+09 1161.92 17-AUG-07:10 0.205168E+10 1392.33 01-AUG-07:10
September 0.867727E+09 1453.34 11-SEP-07:10 0.190319E+10 1392.33 01-SEP-07:10
October 0.953817E+09 1667.75 25-OCT-07:10 0.197226E+10 1392.33 02-OCT-07:10
November 0.101714E+10 1667.75 01-NOV-07:10 0.192888E+10 1392.33 01-NOV-07:10
December 0.105461E+10 1667.75 01-DEC-08:09 0.193924E+10 1392.33 01-DEC-08:09
             
Annual Sum or Average 0.111800E+11     0.234351E+11    
Minimum of Months 0.820186E+09 870.51   0.178514E+10 1392.33  
Maximum of Months 0.109232E+10 1667.75   0.205168E+10 1392.33  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.553024E+09 578.72 02-JAN-08:09 0.521915E+10 1948.61 01-JAN-00:10
February 0.501634E+09 578.72 01-FEB-08:09 0.942813E+10 3897.21 01-FEB-00:10
March 0.596080E+09 578.72 01-MAR-08:09 0.156645E+11 7794.42 31-MAR-23:10
April 0.532421E+09 578.72 03-APR-07:10 0.201821E+11 7794.42 01-APR-00:10
May 0.574552E+09 578.72 01-MAY-07:10 0.522616E+10 3897.21 31-MAY-23:10
June 0.571774E+09 578.72 01-JUN-07:10 0.101086E+11 5845.82 30-JUN-23:10
July 0.535199E+09 578.72 03-JUL-07:10 0.156645E+11 7794.42 31-JUL-23:10
August 0.596080E+09 578.72 01-AUG-07:10 0.208555E+11 7794.42 01-AUG-00:10
September 0.532421E+09 578.72 01-SEP-07:10 0.505780E+10 3897.21 30-SEP-23:10
October 0.553024E+09 578.72 02-OCT-07:10 0.104453E+11 5845.82 31-OCT-23:10
November 0.546542E+09 578.72 01-NOV-07:10 0.151524E+11 5845.82 01-NOV-00:10
December 0.535199E+09 578.72 01-DEC-08:09 0.208766E+11 7794.42 01-DEC-00:10
             
Annual Sum or Average 0.662795E+10     0.153881E+12    
Minimum of Months 0.501634E+09 578.72   0.505780E+10 1948.61  
Maximum of Months 0.596080E+09 578.72   0.208766E+11 7794.42  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: DATACENTER_MID_ZN_6

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.553024E+09 578.72 02-JAN-08:09 0.521915E+10 1948.61 01-JAN-00:10
February 0.501634E+09 578.72 01-FEB-08:09 0.942813E+10 3897.21 01-FEB-00:10
March 0.596080E+09 578.72 01-MAR-08:09 0.156645E+11 7794.42 31-MAR-23:10
April 0.532421E+09 578.72 03-APR-07:10 0.201821E+11 7794.42 01-APR-00:10
May 0.574552E+09 578.72 01-MAY-07:10 0.522616E+10 3897.21 31-MAY-23:10
June 0.571774E+09 578.72 01-JUN-07:10 0.101086E+11 5845.82 30-JUN-23:10
July 0.535199E+09 578.72 03-JUL-07:10 0.156645E+11 7794.42 31-JUL-23:10
August 0.596080E+09 578.72 01-AUG-07:10 0.208555E+11 7794.42 01-AUG-00:10
September 0.532421E+09 578.72 01-SEP-07:10 0.505780E+10 3897.21 30-SEP-23:10
October 0.553024E+09 578.72 02-OCT-07:10 0.104453E+11 5845.82 31-OCT-23:10
November 0.546542E+09 578.72 01-NOV-07:10 0.151524E+11 5845.82 01-NOV-00:10
December 0.535199E+09 578.72 01-DEC-08:09 0.208766E+11 7794.42 01-DEC-00:10
             
Annual Sum or Average 0.662795E+10     0.153881E+12    
Minimum of Months 0.501634E+09 578.72   0.505780E+10 1948.61  
Maximum of Months 0.596080E+09 578.72   0.208766E+11 7794.42  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.553024E+09 578.72 02-JAN-08:09 0.521915E+10 1948.61 01-JAN-00:10
February 0.501634E+09 578.72 01-FEB-08:09 0.942813E+10 3897.21 01-FEB-00:10
March 0.596080E+09 578.72 01-MAR-08:09 0.156645E+11 7794.42 31-MAR-23:10
April 0.532421E+09 578.72 03-APR-07:10 0.201821E+11 7794.42 01-APR-00:10
May 0.574552E+09 578.72 01-MAY-07:10 0.522616E+10 3897.21 31-MAY-23:10
June 0.571774E+09 578.72 01-JUN-07:10 0.101086E+11 5845.82 30-JUN-23:10
July 0.535199E+09 578.72 03-JUL-07:10 0.156645E+11 7794.42 31-JUL-23:10
August 0.596080E+09 578.72 01-AUG-07:10 0.208555E+11 7794.42 01-AUG-00:10
September 0.532421E+09 578.72 01-SEP-07:10 0.505780E+10 3897.21 30-SEP-23:10
October 0.553024E+09 578.72 02-OCT-07:10 0.104453E+11 5845.82 31-OCT-23:10
November 0.546542E+09 578.72 01-NOV-07:10 0.151524E+11 5845.82 01-NOV-00:10
December 0.535199E+09 578.72 01-DEC-08:09 0.208766E+11 7794.42 01-DEC-00:10
             
Annual Sum or Average 0.662795E+10     0.153881E+12    
Minimum of Months 0.501634E+09 578.72   0.505780E+10 1948.61  
Maximum of Months 0.596080E+09 578.72   0.208766E+11 7794.42  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.618367E+10 6471.01 02-JAN-08:09 0.254202E+12 94908.13 01-JAN-00:10
February 0.560905E+10 6471.01 01-FEB-08:09 0.459203E+12 189816.26 01-FEB-00:10
March 0.666512E+10 6471.01 01-MAR-08:09 0.762947E+12 379632.52 31-MAR-23:10
April 0.595330E+10 6471.01 03-APR-07:10 0.982982E+12 379632.52 01-APR-00:10
May 0.642439E+10 6471.01 01-MAY-07:10 0.254544E+12 189816.26 31-MAY-23:10
June 0.639333E+10 6471.01 01-JUN-07:10 0.492345E+12 284724.39 30-JUN-23:10
July 0.598436E+10 6471.01 03-JUL-07:10 0.762947E+12 379632.52 31-JUL-23:10
August 0.666512E+10 6471.01 01-AUG-07:10 0.101578E+13 379632.52 01-AUG-00:10
September 0.595330E+10 6471.01 01-SEP-07:10 0.246344E+12 189816.26 30-SEP-23:10
October 0.618367E+10 6471.01 02-OCT-07:10 0.508746E+12 284724.39 31-OCT-23:10
November 0.611120E+10 6471.01 01-NOV-07:10 0.738006E+12 284724.39 01-NOV-00:10
December 0.598436E+10 6471.01 01-DEC-08:09 0.101681E+13 379632.52 01-DEC-00:10
             
Annual Sum or Average 0.741109E+11     0.749486E+13    
Minimum of Months 0.560905E+10 6471.01   0.246344E+12 94908.13  
Maximum of Months 0.666512E+10 6471.01   0.101681E+13 379632.52  



Table of Contents

Report: SpaceGainsMonthly

For: BASEMENT

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.133902E+11 0.219312E+11 0.360447E+11 0.00 0.00 0.00 0.00 0.00 0.00
February 0.121482E+11 0.198933E+11 0.325565E+11 0.00 0.00 0.00 0.00 0.00 0.00
March 0.145160E+11 0.236388E+11 0.360447E+11 0.00 0.00 0.00 0.00 0.00 0.00
April 0.128805E+11 0.211142E+11 0.348820E+11 0.00 0.00 0.00 0.00 0.00 0.00
May 0.139531E+11 0.227850E+11 0.360447E+11 0.00 0.00 0.00 0.00 0.00 0.00
June 0.139143E+11 0.226748E+11 0.348820E+11 0.00 0.00 0.00 0.00 0.00 0.00
July 0.129193E+11 0.212244E+11 0.360447E+11 0.00 0.00 0.00 0.00 0.00 0.00
August 0.145160E+11 0.236388E+11 0.360447E+11 0.00 0.00 0.00 0.00 0.00 0.00
September 0.128805E+11 0.211142E+11 0.348820E+11 0.00 0.00 0.00 0.00 0.00 0.00
October 0.133902E+11 0.219312E+11 0.360447E+11 0.00 0.00 0.00 0.00 0.00 0.00
November 0.132595E+11 0.216742E+11 0.348820E+11 0.00 0.00 0.00 0.00 0.00 0.00
December 0.129193E+11 0.212244E+11 0.360447E+11 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.160687E+12 0.262844E+12 0.424397E+12 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.121482E+11 0.198933E+11 0.325565E+11 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.145160E+11 0.236388E+11 0.360447E+11 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: CORE_BOTTOM

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.120254E+11 0.196958E+11 0.243681E+11 0.00 0.00 0.00 0.00 0.00 0.00
February 0.109099E+11 0.178655E+11 0.220609E+11 0.00 0.00 0.00 0.00 0.00 0.00
March 0.130364E+11 0.212293E+11 0.253549E+11 0.00 0.00 0.00 0.00 0.00 0.00
April 0.115676E+11 0.189620E+11 0.235306E+11 0.00 0.00 0.00 0.00 0.00 0.00
May 0.125309E+11 0.204625E+11 0.248615E+11 0.00 0.00 0.00 0.00 0.00 0.00
June 0.124961E+11 0.203636E+11 0.244160E+11 0.00 0.00 0.00 0.00 0.00 0.00
July 0.116025E+11 0.190610E+11 0.239708E+11 0.00 0.00 0.00 0.00 0.00 0.00
August 0.130364E+11 0.212293E+11 0.253549E+11 0.00 0.00 0.00 0.00 0.00 0.00
September 0.115676E+11 0.189620E+11 0.235199E+11 0.00 0.00 0.00 0.00 0.00 0.00
October 0.120254E+11 0.196958E+11 0.243735E+11 0.00 0.00 0.00 0.00 0.00 0.00
November 0.119080E+11 0.194649E+11 0.238373E+11 0.00 0.00 0.00 0.00 0.00 0.00
December 0.116025E+11 0.190610E+11 0.239654E+11 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.144308E+12 0.236053E+12 0.289614E+12 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.109099E+11 0.178655E+11 0.220609E+11 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.130364E+11 0.212293E+11 0.253549E+11 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: CORE_MID

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.120254E+11 0.196958E+11 0.243680E+11 0.00 0.00 0.00 0.00 0.00 0.00
February 0.109099E+11 0.178655E+11 0.220609E+11 0.00 0.00 0.00 0.00 0.00 0.00
March 0.130364E+11 0.212293E+11 0.253548E+11 0.00 0.00 0.00 0.00 0.00 0.00
April 0.115676E+11 0.189620E+11 0.235305E+11 0.00 0.00 0.00 0.00 0.00 0.00
May 0.125309E+11 0.204625E+11 0.248614E+11 0.00 0.00 0.00 0.00 0.00 0.00
June 0.124961E+11 0.203636E+11 0.244159E+11 0.00 0.00 0.00 0.00 0.00 0.00
July 0.116025E+11 0.190610E+11 0.239707E+11 0.00 0.00 0.00 0.00 0.00 0.00
August 0.130364E+11 0.212293E+11 0.253548E+11 0.00 0.00 0.00 0.00 0.00 0.00
September 0.115676E+11 0.189620E+11 0.235198E+11 0.00 0.00 0.00 0.00 0.00 0.00
October 0.120254E+11 0.196958E+11 0.243734E+11 0.00 0.00 0.00 0.00 0.00 0.00
November 0.119080E+11 0.194649E+11 0.238372E+11 0.00 0.00 0.00 0.00 0.00 0.00
December 0.116025E+11 0.190610E+11 0.239653E+11 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.144308E+12 0.236053E+12 0.289613E+12 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.109099E+11 0.178655E+11 0.220609E+11 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.130364E+11 0.212293E+11 0.253548E+11 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: CORE_TOP

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.120254E+11 0.196958E+11 0.243680E+11 0.00 0.00 0.00 0.00 0.00 0.00
February 0.109099E+11 0.178655E+11 0.220609E+11 0.00 0.00 0.00 0.00 0.00 0.00
March 0.130364E+11 0.212293E+11 0.253548E+11 0.00 0.00 0.00 0.00 0.00 0.00
April 0.115676E+11 0.189620E+11 0.235305E+11 0.00 0.00 0.00 0.00 0.00 0.00
May 0.125309E+11 0.204625E+11 0.248614E+11 0.00 0.00 0.00 0.00 0.00 0.00
June 0.124961E+11 0.203636E+11 0.244159E+11 0.00 0.00 0.00 0.00 0.00 0.00
July 0.116025E+11 0.190610E+11 0.239707E+11 0.00 0.00 0.00 0.00 0.00 0.00
August 0.130364E+11 0.212293E+11 0.253548E+11 0.00 0.00 0.00 0.00 0.00 0.00
September 0.115676E+11 0.189620E+11 0.235198E+11 0.00 0.00 0.00 0.00 0.00 0.00
October 0.120254E+11 0.196958E+11 0.243734E+11 0.00 0.00 0.00 0.00 0.00 0.00
November 0.119080E+11 0.194649E+11 0.238372E+11 0.00 0.00 0.00 0.00 0.00 0.00
December 0.116025E+11 0.190610E+11 0.239653E+11 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.144308E+12 0.236053E+12 0.289613E+12 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.109099E+11 0.178655E+11 0.220609E+11 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.130364E+11 0.212293E+11 0.253548E+11 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.150991E+10 0.174381E+10 0.305979E+10 0.00 0.00 0.00 0.00 0.00 0.152115E+10
February 0.136985E+10 0.139771E+10 0.277008E+10 0.00 0.00 0.00 0.00 0.00 0.121678E+10
March 0.163685E+10 0.154554E+10 0.318369E+10 0.00 0.00 0.00 0.00 0.00 0.111191E+10
April 0.145243E+10 0.131532E+10 0.295462E+10 0.00 0.00 0.00 0.00 0.00 0.810825E+09
May 0.157338E+10 0.136508E+10 0.312174E+10 0.00 0.00 0.00 0.00 1818243.10 0.792763E+09
June 0.156900E+10 0.132347E+10 0.306580E+10 0.00 0.00 0.00 0.00 9193449.60 0.396230E+09
July 0.145680E+10 0.126804E+10 0.300989E+10 0.00 0.00 0.00 0.00 30659230.45 0.263424E+09
August 0.163685E+10 0.142258E+10 0.318369E+10 0.00 0.00 0.00 0.00 26676437.67 0.288309E+09
September 0.145243E+10 0.135065E+10 0.295328E+10 0.00 0.00 0.00 0.00 16542544.96 0.522603E+09
October 0.150991E+10 0.150063E+10 0.306046E+10 0.00 0.00 0.00 0.00 108355.94 0.786286E+09
November 0.149516E+10 0.163650E+10 0.299314E+10 0.00 0.00 0.00 0.00 0.00 0.111126E+10
December 0.145680E+10 0.170473E+10 0.300922E+10 0.00 0.00 0.00 0.00 0.00 0.140923E+10
                   
Annual Sum or Average 0.181194E+11 0.175741E+11 0.363654E+11 0.00 0.00 0.00 0.00 84998261.72 0.102308E+11
Minimum of Months 0.136985E+10 0.126804E+10 0.277008E+10 0.00 0.00 0.00 0.00 0.00 0.263424E+09
Maximum of Months 0.163685E+10 0.174381E+10 0.318369E+10 0.00 0.00 0.00 0.00 30659230.45 0.152115E+10



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.973041E+09 0.108190E+10 0.197184E+10 0.00 0.00 0.00 0.00 0.00 0.101373E+10
February 0.882782E+09 0.881552E+09 0.178515E+10 0.00 0.00 0.00 0.00 0.00 0.812265E+09
March 0.105485E+10 0.984042E+09 0.205169E+10 0.00 0.00 0.00 0.00 0.00 0.733211E+09
April 0.936002E+09 0.843269E+09 0.190407E+10 0.00 0.00 0.00 0.00 0.00 0.531006E+09
May 0.101394E+10 0.881907E+09 0.201177E+10 0.00 0.00 0.00 0.00 1315871.88 0.518282E+09
June 0.101113E+10 0.860755E+09 0.197572E+10 0.00 0.00 0.00 0.00 6383166.77 0.258689E+09
July 0.938820E+09 0.819192E+09 0.193969E+10 0.00 0.00 0.00 0.00 21310335.14 0.167363E+09
August 0.105485E+10 0.920811E+09 0.205169E+10 0.00 0.00 0.00 0.00 18339200.58 0.180060E+09
September 0.936002E+09 0.863747E+09 0.190321E+10 0.00 0.00 0.00 0.00 11319925.98 0.346211E+09
October 0.973041E+09 0.943330E+09 0.197228E+10 0.00 0.00 0.00 0.00 72233.76 0.520469E+09
November 0.963541E+09 0.102538E+10 0.192889E+10 0.00 0.00 0.00 0.00 0.00 0.725637E+09
December 0.938820E+09 0.105698E+10 0.193926E+10 0.00 0.00 0.00 0.00 0.00 0.922594E+09
                   
Annual Sum or Average 0.116768E+11 0.111629E+11 0.234352E+11 0.00 0.00 0.00 0.00 58740734.11 0.672951E+10
Minimum of Months 0.882782E+09 0.819192E+09 0.178515E+10 0.00 0.00 0.00 0.00 0.00 0.167363E+09
Maximum of Months 0.105485E+10 0.108190E+10 0.205169E+10 0.00 0.00 0.00 0.00 21310335.14 0.101373E+10



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.150994E+10 0.164382E+10 0.305983E+10 0.00 0.00 0.00 0.00 0.00 0.153900E+10
February 0.136988E+10 0.133999E+10 0.277013E+10 0.00 0.00 0.00 0.00 0.00 0.125591E+10
March 0.163688E+10 0.152355E+10 0.318374E+10 0.00 0.00 0.00 0.00 0.00 0.112076E+10
April 0.145246E+10 0.131605E+10 0.295467E+10 0.00 0.00 0.00 0.00 0.00 0.808258E+09
May 0.157341E+10 0.137335E+10 0.312179E+10 0.00 0.00 0.00 0.00 1843279.71 0.779027E+09
June 0.156904E+10 0.133953E+10 0.306585E+10 0.00 0.00 0.00 0.00 9279748.04 0.389455E+09
July 0.145684E+10 0.127798E+10 0.300994E+10 0.00 0.00 0.00 0.00 30071179.22 0.258020E+09
August 0.163688E+10 0.143269E+10 0.318374E+10 0.00 0.00 0.00 0.00 26228098.57 0.286034E+09
September 0.145246E+10 0.134306E+10 0.295333E+10 0.00 0.00 0.00 0.00 14788518.76 0.530296E+09
October 0.150994E+10 0.145065E+10 0.306051E+10 0.00 0.00 0.00 0.00 82157.37 0.807247E+09
November 0.149520E+10 0.154327E+10 0.299318E+10 0.00 0.00 0.00 0.00 0.00 0.112042E+10
December 0.145684E+10 0.158769E+10 0.300927E+10 0.00 0.00 0.00 0.00 0.00 0.142237E+10
                   
Annual Sum or Average 0.181198E+11 0.171716E+11 0.363660E+11 0.00 0.00 0.00 0.00 82292981.68 0.103168E+11
Minimum of Months 0.136988E+10 0.127798E+10 0.277013E+10 0.00 0.00 0.00 0.00 0.00 0.258020E+09
Maximum of Months 0.163688E+10 0.164382E+10 0.318374E+10 0.00 0.00 0.00 0.00 30071179.22 0.153900E+10



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.973041E+09 0.109494E+10 0.197183E+10 0.00 0.00 0.00 0.00 0.00 0.104183E+10
February 0.882782E+09 0.881197E+09 0.178514E+10 0.00 0.00 0.00 0.00 0.00 0.866490E+09
March 0.105485E+10 0.991184E+09 0.205168E+10 0.00 0.00 0.00 0.00 0.00 0.794420E+09
April 0.936002E+09 0.850687E+09 0.190406E+10 0.00 0.00 0.00 0.00 0.00 0.601255E+09
May 0.101394E+10 0.882212E+09 0.201175E+10 0.00 0.00 0.00 0.00 1182335.55 0.560793E+09
June 0.101113E+10 0.855951E+09 0.197570E+10 0.00 0.00 0.00 0.00 6006741.86 0.288091E+09
July 0.938820E+09 0.820794E+09 0.193968E+10 0.00 0.00 0.00 0.00 19140872.83 0.200550E+09
August 0.105485E+10 0.919730E+09 0.205168E+10 0.00 0.00 0.00 0.00 17044531.44 0.217513E+09
September 0.936002E+09 0.869326E+09 0.190319E+10 0.00 0.00 0.00 0.00 10789051.44 0.369554E+09
October 0.973041E+09 0.956001E+09 0.197226E+10 0.00 0.00 0.00 0.00 72239.01 0.566747E+09
November 0.963541E+09 0.101877E+10 0.192888E+10 0.00 0.00 0.00 0.00 0.00 0.800068E+09
December 0.938820E+09 0.105701E+10 0.193924E+10 0.00 0.00 0.00 0.00 0.00 0.102144E+10
                   
Annual Sum or Average 0.116768E+11 0.111978E+11 0.234351E+11 0.00 0.00 0.00 0.00 54235772.13 0.732875E+10
Minimum of Months 0.882782E+09 0.820794E+09 0.178514E+10 0.00 0.00 0.00 0.00 0.00 0.200550E+09
Maximum of Months 0.105485E+10 0.109494E+10 0.205168E+10 0.00 0.00 0.00 0.00 19140872.83 0.104183E+10



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.150991E+10 0.173790E+10 0.305979E+10 0.00 0.00 0.00 0.00 0.00 0.323965E+10
February 0.136985E+10 0.139282E+10 0.277008E+10 0.00 0.00 0.00 0.00 0.00 0.248617E+10
March 0.163685E+10 0.154262E+10 0.318369E+10 0.00 0.00 0.00 0.00 0.00 0.231601E+10
April 0.145243E+10 0.131304E+10 0.295462E+10 0.00 0.00 0.00 0.00 0.00 0.165673E+10
May 0.157338E+10 0.136393E+10 0.312174E+10 0.00 0.00 0.00 0.00 4044207.35 0.168298E+10
June 0.156900E+10 0.132282E+10 0.306580E+10 0.00 0.00 0.00 0.00 21208525.06 0.869729E+09
July 0.145680E+10 0.126757E+10 0.300989E+10 0.00 0.00 0.00 0.00 73182266.22 0.588133E+09
August 0.163685E+10 0.142176E+10 0.318369E+10 0.00 0.00 0.00 0.00 62180245.36 0.636502E+09
September 0.145243E+10 0.134796E+10 0.295328E+10 0.00 0.00 0.00 0.00 39309179.35 0.110818E+10
October 0.150991E+10 0.149665E+10 0.306046E+10 0.00 0.00 0.00 0.00 1320989.74 0.157291E+10
November 0.149516E+10 0.163103E+10 0.299314E+10 0.00 0.00 0.00 0.00 0.00 0.224057E+10
December 0.145680E+10 0.169690E+10 0.300922E+10 0.00 0.00 0.00 0.00 0.00 0.284154E+10
                   
Annual Sum or Average 0.181194E+11 0.175350E+11 0.363654E+11 0.00 0.00 0.00 0.00 0.201245E+09 0.212391E+11
Minimum of Months 0.136985E+10 0.126757E+10 0.277008E+10 0.00 0.00 0.00 0.00 0.00 0.588133E+09
Maximum of Months 0.163685E+10 0.173790E+10 0.318369E+10 0.00 0.00 0.00 0.00 73182266.22 0.323965E+10



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.715730E+09 0.108005E+10 0.197184E+10 0.00 0.00 0.00 0.00 0.00 0.218346E+10
February 0.649041E+09 0.880010E+09 0.178515E+10 0.00 0.00 0.00 0.00 0.00 0.170600E+10
March 0.773965E+09 0.983117E+09 0.205169E+10 0.00 0.00 0.00 0.00 0.00 0.158184E+10
April 0.688021E+09 0.842267E+09 0.190407E+10 0.00 0.00 0.00 0.00 0.00 0.114438E+10
May 0.744847E+09 0.881149E+09 0.201177E+10 0.00 0.00 0.00 0.00 2939532.30 0.112176E+10
June 0.742030E+09 0.860164E+09 0.197572E+10 0.00 0.00 0.00 0.00 14457305.05 0.585978E+09
July 0.690839E+09 0.818786E+09 0.193969E+10 0.00 0.00 0.00 0.00 47988614.31 0.402024E+09
August 0.773965E+09 0.920152E+09 0.205169E+10 0.00 0.00 0.00 0.00 41465856.04 0.429706E+09
September 0.688021E+09 0.863092E+09 0.190321E+10 0.00 0.00 0.00 0.00 25595460.43 0.757548E+09
October 0.715730E+09 0.941851E+09 0.197228E+10 0.00 0.00 0.00 0.00 172655.26 0.108776E+10
November 0.708685E+09 0.102332E+10 0.192889E+10 0.00 0.00 0.00 0.00 0.00 0.150948E+10
December 0.690839E+09 0.105379E+10 0.193926E+10 0.00 0.00 0.00 0.00 0.00 0.191333E+10
                   
Annual Sum or Average 0.858171E+10 0.111478E+11 0.234352E+11 0.00 0.00 0.00 0.00 0.132619E+09 0.144233E+11
Minimum of Months 0.649041E+09 0.818786E+09 0.178515E+10 0.00 0.00 0.00 0.00 0.00 0.402024E+09
Maximum of Months 0.773965E+09 0.108005E+10 0.205169E+10 0.00 0.00 0.00 0.00 47988614.31 0.218346E+10



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.150994E+10 0.164230E+10 0.305983E+10 0.00 0.00 0.00 0.00 0.00 0.341893E+10
February 0.136988E+10 0.133845E+10 0.277013E+10 0.00 0.00 0.00 0.00 0.00 0.277128E+10
March 0.163688E+10 0.152209E+10 0.318374E+10 0.00 0.00 0.00 0.00 0.00 0.248729E+10
April 0.145246E+10 0.131450E+10 0.295467E+10 0.00 0.00 0.00 0.00 0.00 0.177488E+10
May 0.157341E+10 0.137194E+10 0.312179E+10 0.00 0.00 0.00 0.00 4048816.96 0.172157E+10
June 0.156904E+10 0.133817E+10 0.306585E+10 0.00 0.00 0.00 0.00 21048597.68 0.872877E+09
July 0.145684E+10 0.127704E+10 0.300994E+10 0.00 0.00 0.00 0.00 68603373.49 0.599782E+09
August 0.163688E+10 0.143133E+10 0.318374E+10 0.00 0.00 0.00 0.00 60092131.39 0.662642E+09
September 0.145246E+10 0.134179E+10 0.295333E+10 0.00 0.00 0.00 0.00 32956251.02 0.118771E+10
October 0.150994E+10 0.144782E+10 0.306051E+10 0.00 0.00 0.00 0.00 91518.85 0.178190E+10
November 0.149520E+10 0.154216E+10 0.299318E+10 0.00 0.00 0.00 0.00 0.00 0.243618E+10
December 0.145684E+10 0.158618E+10 0.300927E+10 0.00 0.00 0.00 0.00 0.00 0.305618E+10
                   
Annual Sum or Average 0.181198E+11 0.171538E+11 0.363660E+11 0.00 0.00 0.00 0.00 0.186841E+09 0.227712E+11
Minimum of Months 0.136988E+10 0.127704E+10 0.277013E+10 0.00 0.00 0.00 0.00 0.00 0.599782E+09
Maximum of Months 0.163688E+10 0.164230E+10 0.318374E+10 0.00 0.00 0.00 0.00 68603373.49 0.341893E+10



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.973041E+09 0.109244E+10 0.197183E+10 0.00 0.00 0.00 0.00 0.00 0.220139E+10
February 0.882782E+09 0.879043E+09 0.178514E+10 0.00 0.00 0.00 0.00 0.00 0.173883E+10
March 0.105485E+10 0.989598E+09 0.205168E+10 0.00 0.00 0.00 0.00 0.00 0.160580E+10
April 0.936002E+09 0.849759E+09 0.190406E+10 0.00 0.00 0.00 0.00 0.00 0.118345E+10
May 0.101394E+10 0.881584E+09 0.201175E+10 0.00 0.00 0.00 0.00 2649743.82 0.118627E+10
June 0.101113E+10 0.855318E+09 0.197570E+10 0.00 0.00 0.00 0.00 13851259.53 0.609574E+09
July 0.938820E+09 0.820198E+09 0.193968E+10 0.00 0.00 0.00 0.00 46930900.13 0.430341E+09
August 0.105485E+10 0.919058E+09 0.205168E+10 0.00 0.00 0.00 0.00 40823690.75 0.449994E+09
September 0.936002E+09 0.867819E+09 0.190319E+10 0.00 0.00 0.00 0.00 26036279.83 0.770974E+09
October 0.973041E+09 0.953826E+09 0.197226E+10 0.00 0.00 0.00 0.00 316759.30 0.110490E+10
November 0.963541E+09 0.101719E+10 0.192888E+10 0.00 0.00 0.00 0.00 0.00 0.154482E+10
December 0.938820E+09 0.105466E+10 0.193924E+10 0.00 0.00 0.00 0.00 0.00 0.194508E+10
                   
Annual Sum or Average 0.116768E+11 0.111805E+11 0.234351E+11 0.00 0.00 0.00 0.00 0.130609E+09 0.147714E+11
Minimum of Months 0.882782E+09 0.820198E+09 0.178514E+10 0.00 0.00 0.00 0.00 0.00 0.430341E+09
Maximum of Months 0.105485E+10 0.109244E+10 0.205168E+10 0.00 0.00 0.00 0.00 46930900.13 0.220139E+10



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.150991E+10 0.173741E+10 0.305979E+10 0.00 0.00 0.00 0.00 0.00 0.394040E+10
February 0.136985E+10 0.139270E+10 0.277008E+10 0.00 0.00 0.00 0.00 0.00 0.291436E+10
March 0.163685E+10 0.154243E+10 0.318369E+10 0.00 0.00 0.00 0.00 0.00 0.272350E+10
April 0.145243E+10 0.131285E+10 0.295462E+10 0.00 0.00 0.00 0.00 0.00 0.190017E+10
May 0.157338E+10 0.136379E+10 0.312174E+10 0.00 0.00 0.00 0.00 4712861.14 0.197793E+10
June 0.156900E+10 0.132280E+10 0.306580E+10 0.00 0.00 0.00 0.00 25297120.00 0.104676E+10
July 0.145680E+10 0.126753E+10 0.300989E+10 0.00 0.00 0.00 0.00 87717344.83 0.710824E+09
August 0.163685E+10 0.142174E+10 0.318369E+10 0.00 0.00 0.00 0.00 74689445.66 0.762621E+09
September 0.145243E+10 0.134791E+10 0.295328E+10 0.00 0.00 0.00 0.00 46990716.79 0.128935E+10
October 0.150991E+10 0.149638E+10 0.306046E+10 0.00 0.00 0.00 0.00 4507252.80 0.174505E+10
November 0.149516E+10 0.163094E+10 0.299314E+10 0.00 0.00 0.00 0.00 0.00 0.259307E+10
December 0.145680E+10 0.169650E+10 0.300922E+10 0.00 0.00 0.00 0.00 0.00 0.341998E+10
                   
Annual Sum or Average 0.181194E+11 0.175330E+11 0.363654E+11 0.00 0.00 0.00 0.00 0.243915E+09 0.250240E+11
Minimum of Months 0.136985E+10 0.126753E+10 0.277008E+10 0.00 0.00 0.00 0.00 0.00 0.710824E+09
Maximum of Months 0.163685E+10 0.173741E+10 0.318369E+10 0.00 0.00 0.00 0.00 87717344.83 0.394040E+10



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.973041E+09 0.108005E+10 0.197184E+10 0.00 0.00 0.00 0.00 0.00 0.265172E+10
February 0.882782E+09 0.879921E+09 0.178515E+10 0.00 0.00 0.00 0.00 0.00 0.199492E+10
March 0.105485E+10 0.983000E+09 0.205169E+10 0.00 0.00 0.00 0.00 0.00 0.186671E+10
April 0.936002E+09 0.842267E+09 0.190407E+10 0.00 0.00 0.00 0.00 0.00 0.133031E+10
May 0.101394E+10 0.881111E+09 0.201177E+10 0.00 0.00 0.00 0.00 3357503.38 0.132998E+10
June 0.101113E+10 0.860144E+09 0.197572E+10 0.00 0.00 0.00 0.00 17062471.02 0.713580E+09
July 0.938820E+09 0.818786E+09 0.193969E+10 0.00 0.00 0.00 0.00 56666124.36 0.491920E+09
August 0.105485E+10 0.920121E+09 0.205169E+10 0.00 0.00 0.00 0.00 49624123.39 0.522233E+09
September 0.936002E+09 0.863067E+09 0.190321E+10 0.00 0.00 0.00 0.00 29933806.55 0.898028E+09
October 0.973041E+09 0.942030E+09 0.197228E+10 0.00 0.00 0.00 0.00 497746.06 0.122435E+10
November 0.963541E+09 0.102372E+10 0.192889E+10 0.00 0.00 0.00 0.00 0.00 0.174955E+10
December 0.938820E+09 0.105379E+10 0.193926E+10 0.00 0.00 0.00 0.00 0.00 0.229378E+10
                   
Annual Sum or Average 0.116768E+11 0.111480E+11 0.234352E+11 0.00 0.00 0.00 0.00 0.157142E+09 0.170671E+11
Minimum of Months 0.882782E+09 0.818786E+09 0.178515E+10 0.00 0.00 0.00 0.00 0.00 0.491920E+09
Maximum of Months 0.105485E+10 0.108005E+10 0.205169E+10 0.00 0.00 0.00 0.00 56666124.36 0.265172E+10



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.150994E+10 0.164223E+10 0.305983E+10 0.00 0.00 0.00 0.00 0.00 0.409663E+10
February 0.136988E+10 0.133845E+10 0.277013E+10 0.00 0.00 0.00 0.00 0.00 0.322593E+10
March 0.163688E+10 0.152206E+10 0.318374E+10 0.00 0.00 0.00 0.00 0.00 0.293328E+10
April 0.145246E+10 0.131444E+10 0.295467E+10 0.00 0.00 0.00 0.00 0.00 0.206097E+10
May 0.157341E+10 0.137194E+10 0.312179E+10 0.00 0.00 0.00 0.00 4736867.71 0.203095E+10
June 0.156904E+10 0.133817E+10 0.306585E+10 0.00 0.00 0.00 0.00 25160296.06 0.105214E+10
July 0.145684E+10 0.127701E+10 0.300994E+10 0.00 0.00 0.00 0.00 82271066.22 0.724645E+09
August 0.163688E+10 0.143131E+10 0.318374E+10 0.00 0.00 0.00 0.00 72523953.38 0.798669E+09
September 0.145246E+10 0.134174E+10 0.295333E+10 0.00 0.00 0.00 0.00 39537873.37 0.140204E+10
October 0.150994E+10 0.144782E+10 0.306051E+10 0.00 0.00 0.00 0.00 147354.26 0.202736E+10
November 0.149520E+10 0.154216E+10 0.299318E+10 0.00 0.00 0.00 0.00 0.00 0.280696E+10
December 0.145684E+10 0.158598E+10 0.300927E+10 0.00 0.00 0.00 0.00 0.00 0.359254E+10
                   
Annual Sum or Average 0.181198E+11 0.171533E+11 0.363660E+11 0.00 0.00 0.00 0.00 0.224377E+09 0.267521E+11
Minimum of Months 0.136988E+10 0.127701E+10 0.277013E+10 0.00 0.00 0.00 0.00 0.00 0.724645E+09
Maximum of Months 0.163688E+10 0.164223E+10 0.318374E+10 0.00 0.00 0.00 0.00 82271066.22 0.409663E+10



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.973041E+09 0.109232E+10 0.197183E+10 0.00 0.00 0.00 0.00 0.00 0.266871E+10
February 0.882782E+09 0.878986E+09 0.178514E+10 0.00 0.00 0.00 0.00 0.00 0.204680E+10
March 0.105485E+10 0.989552E+09 0.205168E+10 0.00 0.00 0.00 0.00 0.00 0.190831E+10
April 0.936002E+09 0.849759E+09 0.190406E+10 0.00 0.00 0.00 0.00 0.00 0.138607E+10
May 0.101394E+10 0.881564E+09 0.201175E+10 0.00 0.00 0.00 0.00 3119246.60 0.140644E+10
June 0.101113E+10 0.855305E+09 0.197570E+10 0.00 0.00 0.00 0.00 16713609.40 0.737520E+09
July 0.938820E+09 0.820186E+09 0.193968E+10 0.00 0.00 0.00 0.00 56982235.11 0.522082E+09
August 0.105485E+10 0.919058E+09 0.205168E+10 0.00 0.00 0.00 0.00 49396256.49 0.543483E+09
September 0.936002E+09 0.867727E+09 0.190319E+10 0.00 0.00 0.00 0.00 31519229.64 0.913243E+09
October 0.973041E+09 0.953817E+09 0.197226E+10 0.00 0.00 0.00 0.00 848209.38 0.126423E+10
November 0.963541E+09 0.101714E+10 0.192888E+10 0.00 0.00 0.00 0.00 0.00 0.180620E+10
December 0.938820E+09 0.105461E+10 0.193924E+10 0.00 0.00 0.00 0.00 0.00 0.233178E+10
                   
Annual Sum or Average 0.116768E+11 0.111800E+11 0.234351E+11 0.00 0.00 0.00 0.00 0.158579E+09 0.175349E+11
Minimum of Months 0.882782E+09 0.820186E+09 0.178514E+10 0.00 0.00 0.00 0.00 0.00 0.522082E+09
Maximum of Months 0.105485E+10 0.109232E+10 0.205168E+10 0.00 0.00 0.00 0.00 56982235.11 0.266871E+10



Table of Contents

Report: SpaceGainsMonthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.174411E+09 0.553024E+09 0.521915E+10 0.00 0.00 0.00 0.00 0.00 0.00
February 0.158233E+09 0.501634E+09 0.942813E+10 0.00 0.00 0.00 0.00 0.00 0.00
March 0.189074E+09 0.596080E+09 0.156645E+11 0.00 0.00 0.00 0.00 0.00 0.00
April 0.167772E+09 0.532421E+09 0.201821E+11 0.00 0.00 0.00 0.00 0.00 0.00
May 0.181743E+09 0.574552E+09 0.522616E+10 0.00 0.00 0.00 0.00 0.00 0.00
June 0.181238E+09 0.571774E+09 0.101086E+11 0.00 0.00 0.00 0.00 0.00 0.00
July 0.168277E+09 0.535199E+09 0.156645E+11 0.00 0.00 0.00 0.00 0.00 0.00
August 0.189074E+09 0.596080E+09 0.208555E+11 0.00 0.00 0.00 0.00 0.00 0.00
September 0.167772E+09 0.532421E+09 0.505780E+10 0.00 0.00 0.00 0.00 0.00 0.00
October 0.174411E+09 0.553024E+09 0.104453E+11 0.00 0.00 0.00 0.00 0.00 0.00
November 0.172708E+09 0.546542E+09 0.151524E+11 0.00 0.00 0.00 0.00 0.00 0.00
December 0.168277E+09 0.535199E+09 0.208766E+11 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.209299E+10 0.662795E+10 0.153881E+12 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.158233E+09 0.501634E+09 0.505780E+10 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.189074E+09 0.596080E+09 0.208766E+11 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: DATACENTER_MID_ZN_6

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.174411E+09 0.553024E+09 0.521915E+10 0.00 0.00 0.00 0.00 0.00 0.00
February 0.158233E+09 0.501634E+09 0.942813E+10 0.00 0.00 0.00 0.00 0.00 0.00
March 0.189074E+09 0.596080E+09 0.156645E+11 0.00 0.00 0.00 0.00 0.00 0.00
April 0.167772E+09 0.532421E+09 0.201821E+11 0.00 0.00 0.00 0.00 0.00 0.00
May 0.181743E+09 0.574552E+09 0.522616E+10 0.00 0.00 0.00 0.00 0.00 0.00
June 0.181238E+09 0.571774E+09 0.101086E+11 0.00 0.00 0.00 0.00 0.00 0.00
July 0.168277E+09 0.535199E+09 0.156645E+11 0.00 0.00 0.00 0.00 0.00 0.00
August 0.189074E+09 0.596080E+09 0.208555E+11 0.00 0.00 0.00 0.00 0.00 0.00
September 0.167772E+09 0.532421E+09 0.505780E+10 0.00 0.00 0.00 0.00 0.00 0.00
October 0.174411E+09 0.553024E+09 0.104453E+11 0.00 0.00 0.00 0.00 0.00 0.00
November 0.172708E+09 0.546542E+09 0.151524E+11 0.00 0.00 0.00 0.00 0.00 0.00
December 0.168277E+09 0.535199E+09 0.208766E+11 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.209299E+10 0.662795E+10 0.153881E+12 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.158233E+09 0.501634E+09 0.505780E+10 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.189074E+09 0.596080E+09 0.208766E+11 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.174411E+09 0.553024E+09 0.521915E+10 0.00 0.00 0.00 0.00 0.00 0.00
February 0.158233E+09 0.501634E+09 0.942813E+10 0.00 0.00 0.00 0.00 0.00 0.00
March 0.189074E+09 0.596080E+09 0.156645E+11 0.00 0.00 0.00 0.00 0.00 0.00
April 0.167772E+09 0.532421E+09 0.201821E+11 0.00 0.00 0.00 0.00 0.00 0.00
May 0.181743E+09 0.574552E+09 0.522616E+10 0.00 0.00 0.00 0.00 0.00 0.00
June 0.181238E+09 0.571774E+09 0.101086E+11 0.00 0.00 0.00 0.00 0.00 0.00
July 0.168277E+09 0.535199E+09 0.156645E+11 0.00 0.00 0.00 0.00 0.00 0.00
August 0.189074E+09 0.596080E+09 0.208555E+11 0.00 0.00 0.00 0.00 0.00 0.00
September 0.167772E+09 0.532421E+09 0.505780E+10 0.00 0.00 0.00 0.00 0.00 0.00
October 0.174411E+09 0.553024E+09 0.104453E+11 0.00 0.00 0.00 0.00 0.00 0.00
November 0.172708E+09 0.546542E+09 0.151524E+11 0.00 0.00 0.00 0.00 0.00 0.00
December 0.168277E+09 0.535199E+09 0.208766E+11 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.209299E+10 0.662795E+10 0.153881E+12 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.158233E+09 0.501634E+09 0.505780E+10 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.189074E+09 0.596080E+09 0.208766E+11 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.377547E+10 0.618367E+10 0.254202E+12 0.00 0.00 0.00 0.00 0.00 0.00
February 0.342526E+10 0.560905E+10 0.459203E+12 0.00 0.00 0.00 0.00 0.00 0.00
March 0.409289E+10 0.666512E+10 0.762947E+12 0.00 0.00 0.00 0.00 0.00 0.00
April 0.363176E+10 0.595330E+10 0.982982E+12 0.00 0.00 0.00 0.00 0.00 0.00
May 0.393418E+10 0.642439E+10 0.254544E+12 0.00 0.00 0.00 0.00 0.00 0.00
June 0.392325E+10 0.639333E+10 0.492345E+12 0.00 0.00 0.00 0.00 0.00 0.00
July 0.364269E+10 0.598436E+10 0.762947E+12 0.00 0.00 0.00 0.00 0.00 0.00
August 0.409289E+10 0.666512E+10 0.101578E+13 0.00 0.00 0.00 0.00 0.00 0.00
September 0.363176E+10 0.595330E+10 0.246344E+12 0.00 0.00 0.00 0.00 0.00 0.00
October 0.377547E+10 0.618367E+10 0.508746E+12 0.00 0.00 0.00 0.00 0.00 0.00
November 0.373861E+10 0.611120E+10 0.738006E+12 0.00 0.00 0.00 0.00 0.00 0.00
December 0.364269E+10 0.598436E+10 0.101681E+13 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.453069E+11 0.741109E+11 0.749486E+13 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.342526E+10 0.560905E+10 0.246344E+12 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.409289E+10 0.666512E+10 0.101681E+13 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: GROUNDFLOOR_PLENUM

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.329618E+10
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.265704E+10
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.239618E+10
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.173599E+10
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 2845168.02 0.168630E+10
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 14984615.87 0.835195E+09
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 57171345.78 0.559611E+09
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 49317005.50 0.619774E+09
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 32238062.09 0.113169E+10
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 53315.18 0.170586E+10
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.242144E+10
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.307998E+10
                   
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.156610E+09 0.221252E+11
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.559611E+09
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 57171345.78 0.329618E+10



Table of Contents

Report: SpaceGainsMonthly

For: MIDFLOOR_PLENUM

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.548012E+10
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.439512E+10
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.404852E+10
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.293441E+10
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 5322703.80 0.290090E+10
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 27517720.69 0.145570E+10
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.107218E+09 0.979679E+09
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 90314998.10 0.108578E+10
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 60939692.69 0.196428E+10
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 124815.72 0.287072E+10
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.401593E+10
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.500976E+10
                   
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.291438E+09 0.371409E+11
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.979679E+09
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.107218E+09 0.548012E+10



Table of Contents

Report: SpaceGainsMonthly

For: TOPFLOOR_PLENUM

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.583293E+10
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.454420E+10
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.428613E+10
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.309000E+10
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 3356716.68 0.314763E+10
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 23125457.15 0.165020E+10
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 93196841.68 0.111268E+10
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 85480933.62 0.121197E+10
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 52772996.91 0.209942E+10
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.289095E+10
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.406089E+10
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.514260E+10
                   
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.257933E+09 0.390696E+11
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.111268E+10
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 93196841.68 0.583293E+10



Table of Contents

Report: PeakSpaceGainsMonthly

For: BASEMENT

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 17832.21 02-JAN-10:09 22950.34 02-JAN-08:09 13457.54 01-JAN-00:10 0.00 0.00 0.00 0.00 0.00 0.00
February 17832.21 01-FEB-10:09 22950.34 01-FEB-08:09 13457.54 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00 0.00
March 17832.21 01-MAR-10:09 22950.34 01-MAR-08:09 13457.54 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00 0.00
April 17832.21 03-APR-09:09 22950.34 03-APR-07:10 13457.54 01-APR-00:10 0.00 0.00 0.00 0.00 0.00 0.00
May 17832.21 01-MAY-09:09 22950.34 01-MAY-07:10 13457.54 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00 0.00
June 17832.21 01-JUN-09:09 22950.34 01-JUN-07:10 13457.54 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00 0.00
July 17832.21 03-JUL-09:09 22950.34 03-JUL-07:10 13457.54 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00 0.00
August 17832.21 01-AUG-09:09 22950.34 01-AUG-07:10 13457.54 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00 0.00
September 17832.21 01-SEP-09:09 22950.34 01-SEP-07:10 13457.54 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00 0.00
October 17832.21 02-OCT-09:09 22950.34 02-OCT-07:10 13457.54 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00 0.00
November 17832.21 01-NOV-09:09 22950.34 01-NOV-07:10 13457.54 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00 0.00
December 17832.21 01-DEC-10:09 22950.34 01-DEC-08:09 13457.54 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average             0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 17832.21   22950.34   13457.54   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 17832.21   22950.34   13457.54   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: CORE_BOTTOM

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 16014.58 02-JAN-10:09 20611.01 02-JAN-08:09 17206.63 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 0.00
February 16014.58 01-FEB-10:09 20611.01 01-FEB-08:09 17206.63 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 0.00
March 16014.58 01-MAR-10:09 20611.01 01-MAR-08:09 17206.63 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 0.00
April 16014.58 03-APR-09:09 20611.01 03-APR-07:10 17206.63 03-APR-07:10 0.00 0.00 0.00 0.00 0.00 0.00
May 16014.58 01-MAY-09:09 20611.01 01-MAY-07:10 17206.63 01-MAY-07:10 0.00 0.00 0.00 0.00 0.00 0.00
June 16014.58 01-JUN-09:09 20611.01 01-JUN-07:10 17206.63 01-JUN-07:10 0.00 0.00 0.00 0.00 0.00 0.00
July 16014.58 03-JUL-09:09 20611.01 03-JUL-07:10 17206.63 03-JUL-07:10 0.00 0.00 0.00 0.00 0.00 0.00
August 16014.58 01-AUG-09:09 20611.01 01-AUG-07:10 17206.63 01-AUG-07:10 0.00 0.00 0.00 0.00 0.00 0.00
September 16014.58 01-SEP-09:09 20611.01 01-SEP-07:10 17206.63 01-SEP-07:10 0.00 0.00 0.00 0.00 0.00 0.00
October 16014.58 02-OCT-09:09 20611.01 02-OCT-07:10 17206.63 02-OCT-07:10 0.00 0.00 0.00 0.00 0.00 0.00
November 16014.58 01-NOV-09:09 20611.01 01-NOV-07:10 17206.63 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 0.00
December 16014.58 01-DEC-10:09 20611.01 01-DEC-08:09 17206.63 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average             0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 16014.58   20611.01   17206.63   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 16014.58   20611.01   17206.63   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: CORE_MID

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 16014.58 02-JAN-10:09 20611.01 02-JAN-08:09 17206.56 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 0.00
February 16014.58 01-FEB-10:09 20611.01 01-FEB-08:09 17206.56 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 0.00
March 16014.58 01-MAR-10:09 20611.01 01-MAR-08:09 17206.56 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 0.00
April 16014.58 03-APR-09:09 20611.01 03-APR-07:10 17206.56 03-APR-07:10 0.00 0.00 0.00 0.00 0.00 0.00
May 16014.58 01-MAY-09:09 20611.01 01-MAY-07:10 17206.56 01-MAY-07:10 0.00 0.00 0.00 0.00 0.00 0.00
June 16014.58 01-JUN-09:09 20611.01 01-JUN-07:10 17206.56 01-JUN-07:10 0.00 0.00 0.00 0.00 0.00 0.00
July 16014.58 03-JUL-09:09 20611.01 03-JUL-07:10 17206.56 03-JUL-07:10 0.00 0.00 0.00 0.00 0.00 0.00
August 16014.58 01-AUG-09:09 20611.01 01-AUG-07:10 17206.56 01-AUG-07:10 0.00 0.00 0.00 0.00 0.00 0.00
September 16014.58 01-SEP-09:09 20611.01 01-SEP-07:10 17206.56 01-SEP-07:10 0.00 0.00 0.00 0.00 0.00 0.00
October 16014.58 02-OCT-09:09 20611.01 02-OCT-07:10 17206.56 02-OCT-07:10 0.00 0.00 0.00 0.00 0.00 0.00
November 16014.58 01-NOV-09:09 20611.01 01-NOV-07:10 17206.56 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 0.00
December 16014.58 01-DEC-10:09 20611.01 01-DEC-08:09 17206.56 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average             0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 16014.58   20611.01   17206.56   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 16014.58   20611.01   17206.56   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: CORE_TOP

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 16014.58 02-JAN-10:09 20611.01 02-JAN-08:09 17206.56 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 0.00
February 16014.58 01-FEB-10:09 20611.01 01-FEB-08:09 17206.56 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 0.00
March 16014.58 01-MAR-10:09 20611.01 01-MAR-08:09 17206.56 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 0.00
April 16014.58 03-APR-09:09 20611.01 03-APR-07:10 17206.56 03-APR-07:10 0.00 0.00 0.00 0.00 0.00 0.00
May 16014.58 01-MAY-09:09 20611.01 01-MAY-07:10 17206.56 01-MAY-07:10 0.00 0.00 0.00 0.00 0.00 0.00
June 16014.58 01-JUN-09:09 20611.01 01-JUN-07:10 17206.56 01-JUN-07:10 0.00 0.00 0.00 0.00 0.00 0.00
July 16014.58 03-JUL-09:09 20611.01 03-JUL-07:10 17206.56 03-JUL-07:10 0.00 0.00 0.00 0.00 0.00 0.00
August 16014.58 01-AUG-09:09 20611.01 01-AUG-07:10 17206.56 01-AUG-07:10 0.00 0.00 0.00 0.00 0.00 0.00
September 16014.58 01-SEP-09:09 20611.01 01-SEP-07:10 17206.56 01-SEP-07:10 0.00 0.00 0.00 0.00 0.00 0.00
October 16014.58 02-OCT-09:09 20611.01 02-OCT-07:10 17206.56 02-OCT-07:10 0.00 0.00 0.00 0.00 0.00 0.00
November 16014.58 01-NOV-09:09 20611.01 01-NOV-07:10 17206.56 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 0.00
December 16014.58 01-DEC-10:09 20611.01 01-DEC-08:09 17206.56 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average             0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 16014.58   20611.01   17206.56   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 16014.58   20611.01   17206.56   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 2010.79 02-JAN-10:09 2587.92 02-JAN-08:09 2160.55 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 2510.68 05-JAN-22:01
February 2010.79 01-FEB-10:09 2255.20 01-FEB-08:09 2160.55 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 01-FEB-00:05 1551.79 17-FEB-04:00
March 2010.79 01-MAR-10:09 2587.92 17-MAR-07:10 2160.55 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 1899.34 02-MAR-23:00
April 2010.79 03-APR-09:09 1922.48 14-APR-07:10 2160.55 03-APR-07:10 0.00 0.00 0.00 0.00 0.00 01-APR-00:10 1354.19 27-APR-02:00
May 2010.79 01-MAY-09:09 1803.00 03-MAY-07:10 2160.55 01-MAY-07:10 0.00 0.00 0.00 0.00 95.30 20-MAY-17:02 2569.98 22-MAY-04:00
June 2010.79 01-JUN-09:09 1350.81 16-JUN-07:10 2160.55 01-JUN-07:10 0.00 0.00 0.00 0.00 127.69 29-JUN-15:00 1081.55 14-JUN-02:00
July 2010.79 03-JUL-09:09 1470.28 07-JUL-07:30 2160.55 03-JUL-07:10 0.00 0.00 0.00 0.00 254.07 30-JUL-11:58 653.71 05-JUL-01:00
August 2010.79 01-AUG-09:09 1470.28 17-AUG-07:10 2160.55 01-AUG-07:10 0.00 0.00 0.00 0.00 323.02 06-AUG-17:24 828.37 23-AUG-03:00
September 2010.79 01-SEP-09:09 2255.20 11-SEP-07:10 2160.55 01-SEP-07:10 0.00 0.00 0.00 0.00 364.82 03-SEP-12:51 1442.05 12-SEP-03:00
October 2010.79 02-OCT-09:09 2587.92 25-OCT-07:10 2160.55 02-OCT-07:10 0.00 0.00 0.00 0.00 11.99 18-OCT-14:00 1244.55 30-OCT-22:00
November 2010.79 01-NOV-09:09 2587.92 01-NOV-07:10 2160.55 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 1505.87 28-NOV-05:51
December 2010.79 01-DEC-10:09 2587.92 01-DEC-08:09 2160.55 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 2297.01 01-DEC-04:55
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 2010.79   1350.81   2160.55   0.00 0.00 0.00 0.00 0.00   653.71  
Maximum of Months 2010.79   2587.92   2160.55   0.00 0.00 0.00 0.00 364.82   2569.98  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 1295.83 02-JAN-10:09 1667.75 02-JAN-08:09 1392.34 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 1673.43 05-JAN-22:01
February 1295.83 01-FEB-10:09 1453.34 01-FEB-16:00 1392.34 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 01-FEB-00:05 1015.48 17-FEB-04:00
March 1295.83 01-MAR-10:09 1667.75 17-MAR-07:10 1392.34 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 1242.25 02-MAR-23:00
April 1295.83 03-APR-09:09 1161.92 14-APR-07:10 1392.34 03-APR-07:10 0.00 0.00 0.00 0.00 0.00 01-APR-00:10 883.30 27-APR-02:00
May 1295.83 01-MAY-09:09 947.51 03-MAY-07:10 1392.34 01-MAY-07:10 0.00 0.00 0.00 0.00 85.49 20-MAY-17:20 1694.36 22-MAY-04:00
June 1295.83 01-JUN-09:09 793.52 01-JUN-07:10 1392.34 01-JUN-07:10 0.00 0.00 0.00 0.00 85.13 29-JUN-15:00 700.51 14-JUN-02:00
July 1295.83 03-JUL-09:09 870.51 07-JUL-07:19 1392.34 03-JUL-07:10 0.00 0.00 0.00 0.00 190.46 30-JUL-12:00 420.91 05-JUL-01:00
August 1295.83 01-AUG-09:09 870.51 17-AUG-07:10 1392.34 01-AUG-07:10 0.00 0.00 0.00 0.00 227.13 06-AUG-17:30 531.57 23-AUG-03:00
September 1295.83 01-SEP-09:09 1161.92 13-SEP-07:10 1392.34 01-SEP-07:10 0.00 0.00 0.00 0.00 254.71 03-SEP-13:10 944.17 12-SEP-03:00
October 1295.83 02-OCT-09:09 1667.75 25-OCT-07:10 1392.34 02-OCT-07:10 0.00 0.00 0.00 0.00 7.99 18-OCT-14:00 813.88 08-OCT-08:40
November 1295.83 01-NOV-09:09 1667.75 01-NOV-07:10 1392.34 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 1003.93 28-NOV-05:56
December 1295.83 01-DEC-10:09 1667.75 01-DEC-08:09 1392.34 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 1482.36 01-DEC-04:55
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 1295.83   793.52   1392.34   0.00 0.00 0.00 0.00 0.00   420.91  
Maximum of Months 1295.83   1667.75   1392.34   0.00 0.00 0.00 0.00 254.71   1694.36  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 2010.83 02-JAN-10:09 2587.98 02-JAN-08:09 2160.58 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 2509.79 05-JAN-22:01
February 2010.83 01-FEB-10:09 2255.25 02-FEB-08:09 2160.58 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 01-FEB-00:05 1619.04 19-FEB-12:20
March 2010.83 01-MAR-10:09 2587.98 17-MAR-07:10 2160.58 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 1927.92 02-MAR-23:00
April 2010.83 03-APR-09:09 1922.52 14-APR-07:10 2160.58 03-APR-07:10 0.00 0.00 0.00 0.00 0.00 01-APR-00:10 1335.86 27-APR-02:00
May 2010.83 01-MAY-09:09 1803.04 03-MAY-07:10 2160.58 01-MAY-07:10 0.00 0.00 0.00 0.00 100.30 20-MAY-17:02 2488.82 22-MAY-04:00
June 2010.83 01-JUN-09:09 1350.84 16-JUN-07:10 2160.58 01-JUN-07:10 0.00 0.00 0.00 0.00 127.69 29-JUN-15:00 1058.81 14-JUN-02:00
July 2010.83 03-JUL-09:09 1470.31 07-JUL-07:30 2160.58 03-JUL-07:10 0.00 0.00 0.00 0.00 262.44 30-JUL-11:58 637.61 05-JUL-01:00
August 2010.83 01-AUG-09:09 1470.31 17-AUG-07:10 2160.58 01-AUG-07:10 0.00 0.00 0.00 0.00 328.45 06-AUG-17:24 821.06 23-AUG-03:00
September 2010.83 01-SEP-09:09 1803.04 11-SEP-07:10 2160.58 01-SEP-07:10 0.00 0.00 0.00 0.00 333.32 03-SEP-13:04 1400.54 12-SEP-03:00
October 2010.83 02-OCT-09:09 2587.98 25-OCT-07:10 2160.58 02-OCT-07:10 0.00 0.00 0.00 0.00 11.77 18-OCT-15:00 1286.72 08-OCT-15:00
November 2010.83 01-NOV-09:09 2587.98 01-NOV-07:10 2160.58 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 1505.89 28-NOV-05:51
December 2010.83 01-DEC-10:09 2587.98 01-DEC-08:09 2160.58 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 2212.80 01-DEC-04:55
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 2010.83   1350.84   2160.58   0.00 0.00 0.00 0.00 0.00   637.61  
Maximum of Months 2010.83   2587.98   2160.58   0.00 0.00 0.00 0.00 333.32   2509.79  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 1295.83 02-JAN-10:09 1667.75 02-JAN-08:09 1392.33 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 1675.48 05-JAN-22:01
February 1295.83 01-FEB-10:09 1667.75 02-FEB-08:09 1392.33 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 01-FEB-00:05 1103.32 17-FEB-04:00
March 1295.83 01-MAR-10:09 1667.75 17-MAR-07:10 1392.33 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 1352.61 02-MAR-23:00
April 1295.83 03-APR-09:09 1453.34 14-APR-07:10 1392.33 03-APR-07:10 0.00 0.00 0.00 0.00 0.00 01-APR-00:10 988.83 27-APR-02:00
May 1295.83 01-MAY-09:09 1161.92 03-MAY-07:10 1392.33 01-MAY-07:10 0.00 0.00 0.00 0.00 59.46 20-MAY-17:20 1747.61 22-MAY-04:00
June 1295.83 01-JUN-09:09 870.51 01-JUN-07:10 1392.33 01-JUN-07:10 0.00 0.00 0.00 0.00 85.13 29-JUN-15:00 784.56 14-JUN-02:00
July 1295.83 03-JUL-09:09 947.51 07-JUL-07:10 1392.33 03-JUL-07:10 0.00 0.00 0.00 0.00 201.62 30-JUL-12:00 491.69 05-JUL-01:00
August 1295.83 01-AUG-09:09 1161.92 17-AUG-07:10 1392.33 01-AUG-07:10 0.00 0.00 0.00 0.00 209.43 06-AUG-17:24 642.99 23-AUG-03:00
September 1295.83 01-SEP-09:09 1453.34 11-SEP-07:10 1392.33 01-SEP-07:10 0.00 0.00 0.00 0.00 259.95 03-SEP-12:51 994.57 12-SEP-03:00
October 1295.83 02-OCT-09:09 1667.75 25-OCT-07:10 1392.33 02-OCT-07:10 0.00 0.00 0.00 0.00 7.99 18-OCT-14:00 885.78 30-OCT-22:10
November 1295.83 01-NOV-09:09 1667.75 01-NOV-07:10 1392.33 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 1042.92 26-NOV-19:52
December 1295.83 01-DEC-10:09 1667.75 01-DEC-08:09 1392.33 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 1673.65 01-DEC-04:55
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 1295.83   870.51   1392.33   0.00 0.00 0.00 0.00 0.00   491.69  
Maximum of Months 1295.83   1667.75   1392.33   0.00 0.00 0.00 0.00 259.95   1747.61  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 2010.79 02-JAN-10:09 2587.92 02-JAN-08:09 2160.55 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 5873.78 05-JAN-22:01
February 2010.79 01-FEB-10:09 2255.20 01-FEB-08:09 2160.55 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 01-FEB-00:05 3236.01 08-FEB-22:01
March 2010.79 01-MAR-10:09 2587.92 17-MAR-07:10 2160.55 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 4045.62 02-MAR-23:00
April 2010.79 03-APR-09:09 1803.00 14-APR-07:10 2160.55 03-APR-07:10 0.00 0.00 0.00 0.00 0.00 01-APR-00:10 2826.79 27-APR-02:00
May 2010.79 01-MAY-09:09 1803.00 03-MAY-07:10 2160.55 01-MAY-07:10 0.00 0.00 0.00 0.00 226.77 20-MAY-17:02 5691.68 22-MAY-04:57
June 2010.79 01-JUN-09:09 1350.81 26-JUN-11:30 2160.55 01-JUN-07:10 0.00 0.00 0.00 0.00 295.49 29-JUN-15:00 2262.57 14-JUN-02:00
July 2010.79 03-JUL-09:09 1470.28 07-JUL-07:30 2160.55 03-JUL-07:10 0.00 0.00 0.00 0.00 600.31 30-JUL-11:53 1360.85 05-JUL-01:00
August 2010.79 01-AUG-09:09 1470.28 17-AUG-07:10 2160.55 01-AUG-07:10 0.00 0.00 0.00 0.00 740.98 06-AUG-17:24 1663.66 23-AUG-03:00
September 2010.79 01-SEP-09:09 2135.72 11-SEP-07:10 2160.55 01-SEP-07:10 0.00 0.00 0.00 0.00 869.18 03-SEP-13:00 2933.28 12-SEP-03:00
October 2010.79 02-OCT-09:09 2587.92 25-OCT-07:10 2160.55 02-OCT-07:10 0.00 0.00 0.00 0.00 183.31 15-OCT-14:00 2567.27 30-OCT-21:03
November 2010.79 01-NOV-09:09 2587.92 01-NOV-07:10 2160.55 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 3546.95 28-NOV-06:00
December 2010.79 01-DEC-10:09 2587.92 01-DEC-08:09 2160.55 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 5043.14 01-DEC-05:09
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 2010.79   1350.81   2160.55   0.00 0.00 0.00 0.00 0.00   1360.85  
Maximum of Months 2010.79   2587.92   2160.55   0.00 0.00 0.00 0.00 869.18   5873.78  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 1239.33 02-JAN-08:09 1667.75 02-JAN-08:09 1392.34 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 3915.51 05-JAN-22:01
February 1239.33 01-FEB-08:09 1453.34 01-FEB-16:00 1392.34 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 01-FEB-00:05 2156.58 08-FEB-22:01
March 1239.33 01-MAR-08:09 1667.75 17-MAR-07:10 1392.34 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 2690.71 02-MAR-23:00
April 1239.33 03-APR-07:10 1161.92 14-APR-07:10 1392.34 03-APR-07:10 0.00 0.00 0.00 0.00 0.00 01-APR-00:10 1884.57 27-APR-02:00
May 1239.33 01-MAY-07:10 947.51 03-MAY-07:10 1392.34 01-MAY-07:10 0.00 0.00 0.00 0.00 186.52 20-MAY-17:02 3794.41 22-MAY-04:54
June 1239.33 01-JUN-07:10 793.52 01-JUN-07:10 1392.34 01-JUN-07:10 0.00 0.00 0.00 0.00 196.99 29-JUN-15:00 1544.69 04-JUN-13:55
July 1239.33 03-JUL-07:10 870.51 07-JUL-07:19 1392.34 03-JUL-07:10 0.00 0.00 0.00 0.00 423.41 30-JUL-14:57 903.89 05-JUL-01:00
August 1239.33 01-AUG-07:10 870.51 17-AUG-07:10 1392.34 01-AUG-07:10 0.00 0.00 0.00 0.00 523.68 06-AUG-17:30 1103.92 23-AUG-03:00
September 1239.33 01-SEP-07:10 1161.92 13-SEP-07:10 1392.34 01-SEP-07:10 0.00 0.00 0.00 0.00 589.33 03-SEP-12:51 1917.38 12-SEP-03:00
October 1239.33 02-OCT-07:10 1667.75 25-OCT-07:10 1392.34 02-OCT-07:10 0.00 0.00 0.00 0.00 21.58 18-OCT-14:00 1712.59 30-OCT-21:03
November 1239.33 01-NOV-07:10 1667.75 01-NOV-07:10 1392.34 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 2364.89 28-NOV-05:53
December 1239.33 01-DEC-08:09 1667.75 01-DEC-08:09 1392.34 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 3362.22 01-DEC-05:07
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 1239.33   793.52   1392.34   0.00 0.00 0.00 0.00 0.00   903.89  
Maximum of Months 1239.33   1667.75   1392.34   0.00 0.00 0.00 0.00 589.33   3915.51  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 2010.83 02-JAN-10:09 2587.98 02-JAN-08:09 2160.58 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 5876.26 05-JAN-22:01
February 2010.83 01-FEB-10:09 2135.77 02-FEB-08:09 2160.58 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 01-FEB-00:05 3682.07 19-FEB-12:50
March 2010.83 01-MAR-10:09 2587.98 17-MAR-07:10 2160.58 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 4227.74 02-MAR-23:00
April 2010.83 03-APR-09:09 1803.04 14-APR-07:10 2160.58 03-APR-07:10 0.00 0.00 0.00 0.00 0.00 01-APR-00:10 2860.98 27-APR-02:00
May 2010.83 01-MAY-09:09 1803.04 03-MAY-07:10 2160.58 01-MAY-07:10 0.00 0.00 0.00 0.00 229.87 20-MAY-17:02 5691.65 22-MAY-04:57
June 2010.83 01-JUN-09:09 1350.84 16-JUN-07:10 2160.58 01-JUN-07:10 0.00 0.00 0.00 0.00 295.49 29-JUN-15:00 2241.52 14-JUN-02:00
July 2010.83 03-JUL-09:09 1470.31 07-JUL-07:30 2160.58 03-JUL-07:10 0.00 0.00 0.00 0.00 595.97 30-JUL-14:16 1376.95 05-JUL-01:00
August 2010.83 01-AUG-09:09 1470.31 17-AUG-07:10 2160.58 01-AUG-07:10 0.00 0.00 0.00 0.00 760.66 06-AUG-17:24 1706.24 23-AUG-03:00
September 2010.83 01-SEP-09:09 1803.04 11-SEP-07:10 2160.58 01-SEP-07:10 0.00 0.00 0.00 0.00 810.14 03-SEP-12:57 2922.42 12-SEP-03:00
October 2010.83 02-OCT-09:09 2587.98 25-OCT-07:10 2160.58 02-OCT-07:10 0.00 0.00 0.00 0.00 18.98 18-OCT-15:10 2860.05 08-OCT-15:00
November 2010.83 01-NOV-09:09 2587.98 01-NOV-07:10 2160.58 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 3547.08 28-NOV-05:59
December 2010.83 01-DEC-10:09 2587.98 01-DEC-08:09 2160.58 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 5044.72 01-DEC-05:04
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 2010.83   1350.84   2160.58   0.00 0.00 0.00 0.00 0.00   1376.95  
Maximum of Months 2010.83   2587.98   2160.58   0.00 0.00 0.00 0.00 810.14   5876.26  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 1295.83 02-JAN-10:09 1667.75 02-JAN-08:09 1392.33 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 3915.47 05-JAN-22:01
February 1295.83 01-FEB-10:09 1667.75 02-FEB-08:09 1392.33 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 01-FEB-00:05 2161.14 08-FEB-22:01
March 1295.83 01-MAR-10:09 1667.75 17-MAR-07:10 1392.33 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 2784.24 02-MAR-23:00
April 1295.83 03-APR-09:09 1453.34 14-APR-07:10 1392.33 03-APR-07:10 0.00 0.00 0.00 0.00 0.00 01-APR-00:10 1918.61 27-APR-02:00
May 1295.83 01-MAY-09:09 1161.92 03-MAY-07:10 1392.33 01-MAY-07:10 0.00 0.00 0.00 0.00 152.40 20-MAY-17:02 3794.45 22-MAY-04:54
June 1295.83 01-JUN-09:09 870.51 01-JUN-07:10 1392.33 01-JUN-07:10 0.00 0.00 0.00 0.00 196.99 29-JUN-15:00 1541.08 14-JUN-02:00
July 1295.83 03-JUL-09:09 947.51 07-JUL-07:19 1392.33 03-JUL-07:10 0.00 0.00 0.00 0.00 499.37 30-JUL-11:53 980.66 05-JUL-01:00
August 1295.83 01-AUG-09:09 1161.92 17-AUG-07:10 1392.33 01-AUG-07:10 0.00 0.00 0.00 0.00 519.06 06-AUG-12:10 1154.08 23-AUG-03:00
September 1295.83 01-SEP-09:09 1453.34 11-SEP-07:10 1392.33 01-SEP-07:10 0.00 0.00 0.00 0.00 649.29 03-SEP-12:51 1922.40 12-SEP-03:00
October 1295.83 02-OCT-09:09 1667.75 25-OCT-07:10 1392.33 02-OCT-07:10 0.00 0.00 0.00 0.00 49.79 15-OCT-12:30 1739.01 30-OCT-22:00
November 1295.83 01-NOV-09:09 1667.75 01-NOV-07:10 1392.33 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 2364.75 28-NOV-06:00
December 1295.83 01-DEC-10:09 1667.75 01-DEC-08:09 1392.33 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 3362.26 01-DEC-05:10
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 1295.83   870.51   1392.33   0.00 0.00 0.00 0.00 0.00   980.66  
Maximum of Months 1295.83   1667.75   1392.33   0.00 0.00 0.00 0.00 649.29   3915.47  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 2010.79 02-JAN-10:09 2587.92 02-JAN-08:09 2160.55 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 7286.41 05-JAN-22:01
February 2010.79 01-FEB-10:09 2255.20 01-FEB-08:09 2160.55 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 01-FEB-00:05 4035.67 17-FEB-05:58
March 2010.79 01-MAR-10:09 2587.92 17-MAR-07:10 2160.55 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 4958.19 17-MAR-04:47
April 2010.79 03-APR-09:09 1803.00 14-APR-07:10 2160.55 03-APR-07:10 0.00 0.00 0.00 0.00 0.00 01-APR-00:10 3249.58 27-APR-02:00
May 2010.79 01-MAY-09:09 1803.00 03-MAY-07:10 2160.55 01-MAY-07:10 0.00 0.00 0.00 0.00 256.90 20-MAY-17:02 7102.39 22-MAY-04:46
June 2010.79 01-JUN-09:09 1350.81 26-JUN-11:30 2160.55 01-JUN-07:10 0.00 0.00 0.00 0.00 361.92 29-JUN-15:00 2617.18 14-JUN-02:00
July 2010.79 03-JUL-09:09 1470.28 07-JUL-07:30 2160.55 03-JUL-07:10 0.00 0.00 0.00 0.00 703.85 30-JUL-11:55 1556.26 05-JUL-01:00
August 2010.79 01-AUG-09:09 1470.28 17-AUG-07:10 2160.55 01-AUG-07:10 0.00 0.00 0.00 0.00 905.13 06-AUG-17:24 1998.78 22-AUG-21:10
September 2010.79 01-SEP-09:09 2135.72 11-SEP-07:10 2160.55 01-SEP-07:10 0.00 0.00 0.00 0.00 1026.03 03-SEP-12:52 3222.31 12-SEP-03:00
October 2010.79 02-OCT-09:09 2587.92 25-OCT-07:10 2160.55 02-OCT-07:10 0.00 0.00 0.00 0.00 395.95 15-OCT-14:00 3170.66 30-OCT-21:03
November 2010.79 01-NOV-09:09 2587.92 01-NOV-07:10 2160.55 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 4275.91 28-NOV-05:50
December 2010.79 01-DEC-10:09 2587.92 01-DEC-08:09 2160.55 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 6155.80 01-DEC-05:10
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 2010.79   1350.81   2160.55   0.00 0.00 0.00 0.00 0.00   1556.26  
Maximum of Months 2010.79   2587.92   2160.55   0.00 0.00 0.00 0.00 1026.03   7286.41  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 1295.83 02-JAN-10:09 1667.75 02-JAN-08:09 1392.34 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 4857.34 05-JAN-22:01
February 1295.83 01-FEB-10:09 1453.34 01-FEB-16:00 1392.34 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 01-FEB-00:05 2690.32 17-FEB-06:00
March 1295.83 01-MAR-10:09 1667.75 17-MAR-07:10 1392.34 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 3305.33 17-MAR-04:45
April 1295.83 03-APR-09:09 1161.92 14-APR-07:10 1392.34 03-APR-07:10 0.00 0.00 0.00 0.00 0.00 01-APR-00:10 2178.11 27-APR-02:00
May 1295.83 01-MAY-09:09 947.51 03-MAY-07:10 1392.34 01-MAY-07:10 0.00 0.00 0.00 0.00 210.96 20-MAY-17:02 4735.00 22-MAY-04:48
June 1295.83 01-JUN-09:09 793.52 01-JUN-07:10 1392.34 01-JUN-07:10 0.00 0.00 0.00 0.00 241.28 29-JUN-15:00 1886.97 04-JUN-14:00
July 1295.83 03-JUL-09:09 870.51 07-JUL-07:19 1392.34 03-JUL-07:10 0.00 0.00 0.00 0.00 527.85 30-JUL-11:46 1035.40 05-JUL-01:00
August 1295.83 01-AUG-09:09 870.51 17-AUG-07:10 1392.34 01-AUG-07:10 0.00 0.00 0.00 0.00 650.42 06-AUG-17:26 1303.63 22-AUG-21:10
September 1295.83 01-SEP-09:09 1161.92 13-SEP-07:10 1392.34 01-SEP-07:10 0.00 0.00 0.00 0.00 711.17 03-SEP-12:51 2120.24 12-SEP-03:00
October 1295.83 02-OCT-09:09 1667.75 25-OCT-07:10 1392.34 02-OCT-07:10 0.00 0.00 0.00 0.00 107.72 15-OCT-13:50 2115.55 30-OCT-21:03
November 1295.83 01-NOV-09:09 1667.75 01-NOV-07:10 1392.34 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 2933.79 28-NOV-05:49
December 1295.83 01-DEC-10:09 1667.75 01-DEC-08:09 1392.34 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 4198.79 01-DEC-05:07
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 1295.83   793.52   1392.34   0.00 0.00 0.00 0.00 0.00   1035.40  
Maximum of Months 1295.83   1667.75   1392.34   0.00 0.00 0.00 0.00 711.17   4857.34  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 2010.83 02-JAN-10:09 2587.98 02-JAN-08:09 2160.58 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 7289.96 05-JAN-22:01
February 2010.83 01-FEB-10:09 2135.77 02-FEB-08:09 2160.58 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 01-FEB-00:05 4051.59 19-FEB-13:00
March 2010.83 01-MAR-10:09 2587.98 17-MAR-07:10 2160.58 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 5019.19 02-MAR-23:00
April 2010.83 03-APR-09:09 1803.04 14-APR-07:10 2160.58 03-APR-07:10 0.00 0.00 0.00 0.00 0.00 01-APR-00:10 3300.48 27-APR-02:00
May 2010.83 01-MAY-09:09 1803.04 03-MAY-07:10 2160.58 01-MAY-07:10 0.00 0.00 0.00 0.00 263.46 20-MAY-17:02 7102.17 22-MAY-04:44
June 2010.83 01-JUN-09:09 1350.84 16-JUN-07:10 2160.58 01-JUN-07:10 0.00 0.00 0.00 0.00 361.92 29-JUN-15:00 2706.55 04-JUN-13:55
July 2010.83 03-JUL-09:09 1470.31 07-JUL-07:30 2160.58 03-JUL-07:10 0.00 0.00 0.00 0.00 727.66 30-JUL-11:46 1576.79 05-JUL-01:00
August 2010.83 01-AUG-09:09 1470.31 17-AUG-07:10 2160.58 01-AUG-07:10 0.00 0.00 0.00 0.00 935.38 06-AUG-17:24 2041.97 22-AUG-21:10
September 2010.83 01-SEP-09:09 1803.04 11-SEP-07:10 2160.58 01-SEP-07:10 0.00 0.00 0.00 0.00 988.95 03-SEP-12:57 3217.99 12-SEP-03:00
October 2010.83 02-OCT-09:09 2587.98 25-OCT-07:10 2160.58 02-OCT-07:10 0.00 0.00 0.00 0.00 26.60 18-OCT-15:00 3212.45 30-OCT-21:03
November 2010.83 01-NOV-09:09 2587.98 01-NOV-07:10 2160.58 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 4400.74 28-NOV-05:50
December 2010.83 01-DEC-10:09 2587.98 01-DEC-08:09 2160.58 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 6297.89 01-DEC-05:10
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 2010.83   1350.84   2160.58   0.00 0.00 0.00 0.00 0.00   1576.79  
Maximum of Months 2010.83   2587.98   2160.58   0.00 0.00 0.00 0.00 988.95   7289.96  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 1295.83 02-JAN-10:09 1667.75 02-JAN-08:09 1392.33 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 4858.13 05-JAN-22:01
February 1295.83 01-FEB-10:09 1667.75 02-FEB-08:09 1392.33 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 01-FEB-00:05 2690.59 17-FEB-06:00
March 1295.83 01-MAR-10:09 1667.75 17-MAR-07:10 1392.33 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 3319.64 02-MAR-23:00
April 1295.83 03-APR-09:09 1453.34 14-APR-07:10 1392.33 03-APR-07:10 0.00 0.00 0.00 0.00 0.00 01-APR-00:10 2221.58 27-APR-02:00
May 1295.83 01-MAY-09:09 1161.92 03-MAY-07:10 1392.33 01-MAY-07:10 0.00 0.00 0.00 0.00 175.64 20-MAY-17:02 4734.84 22-MAY-04:44
June 1295.83 01-JUN-09:09 870.51 01-JUN-07:10 1392.33 01-JUN-07:10 0.00 0.00 0.00 0.00 241.28 29-JUN-15:00 1789.88 14-JUN-02:00
July 1295.83 03-JUL-09:09 947.51 07-JUL-07:19 1392.33 03-JUL-07:10 0.00 0.00 0.00 0.00 580.63 30-JUL-11:50 1138.14 05-JUL-01:00
August 1295.83 01-AUG-09:09 1161.92 17-AUG-07:10 1392.33 01-AUG-07:10 0.00 0.00 0.00 0.00 620.77 06-AUG-12:10 1383.34 22-AUG-21:10
September 1295.83 01-SEP-09:09 1453.34 11-SEP-07:10 1392.33 01-SEP-07:10 0.00 0.00 0.00 0.00 774.51 03-SEP-12:51 2144.95 12-SEP-03:00
October 1295.83 02-OCT-09:09 1667.75 25-OCT-07:10 1392.33 02-OCT-07:10 0.00 0.00 0.00 0.00 129.76 15-OCT-12:41 2127.90 30-OCT-21:03
November 1295.83 01-NOV-09:09 1667.75 01-NOV-07:10 1392.33 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 2933.79 28-NOV-05:47
December 1295.83 01-DEC-10:09 1667.75 01-DEC-08:09 1392.33 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 4198.63 01-DEC-05:07
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 1295.83   870.51   1392.33   0.00 0.00 0.00 0.00 0.00   1138.14  
Maximum of Months 1295.83   1667.75   1392.33   0.00 0.00 0.00 0.00 774.51   4858.13  



Table of Contents

Report: PeakSpaceGainsMonthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 232.27 02-JAN-10:09 578.72 02-JAN-08:09 1948.61 01-JAN-00:10 0.00 0.00 0.00 0.00 0.00 0.00
February 232.27 01-FEB-10:09 578.72 01-FEB-08:09 3897.21 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00 0.00
March 232.27 01-MAR-10:09 578.72 01-MAR-08:09 7794.42 31-MAR-23:10 0.00 0.00 0.00 0.00 0.00 0.00
April 232.27 03-APR-09:09 578.72 03-APR-07:10 7794.42 01-APR-00:10 0.00 0.00 0.00 0.00 0.00 0.00
May 232.27 01-MAY-09:09 578.72 01-MAY-07:10 3897.21 31-MAY-23:10 0.00 0.00 0.00 0.00 0.00 0.00
June 232.27 01-JUN-09:09 578.72 01-JUN-07:10 5845.82 30-JUN-23:10 0.00 0.00 0.00 0.00 0.00 0.00
July 232.27 03-JUL-09:09 578.72 03-JUL-07:10 7794.42 31-JUL-23:10 0.00 0.00 0.00 0.00 0.00 0.00
August 232.27 01-AUG-09:09 578.72 01-AUG-07:10 7794.42 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00 0.00
September 232.27 01-SEP-09:09 578.72 01-SEP-07:10 3897.21 30-SEP-23:10 0.00 0.00 0.00 0.00 0.00 0.00
October 232.27 02-OCT-09:09 578.72 02-OCT-07:10 5845.82 31-OCT-23:10 0.00 0.00 0.00 0.00 0.00 0.00
November 232.27 01-NOV-09:09 578.72 01-NOV-07:10 5845.82 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00 0.00
December 232.27 01-DEC-10:09 578.72 01-DEC-08:09 7794.42 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average             0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 232.27   578.72   1948.61   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 232.27   578.72   7794.42   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: DATACENTER_MID_ZN_6

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 232.27 02-JAN-10:09 578.72 02-JAN-08:09 1948.61 01-JAN-00:10 0.00 0.00 0.00 0.00 0.00 0.00
February 232.27 01-FEB-10:09 578.72 01-FEB-08:09 3897.21 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00 0.00
March 232.27 01-MAR-10:09 578.72 01-MAR-08:09 7794.42 31-MAR-23:10 0.00 0.00 0.00 0.00 0.00 0.00
April 232.27 03-APR-09:09 578.72 03-APR-07:10 7794.42 01-APR-00:10 0.00 0.00 0.00 0.00 0.00 0.00
May 232.27 01-MAY-09:09 578.72 01-MAY-07:10 3897.21 31-MAY-23:10 0.00 0.00 0.00 0.00 0.00 0.00
June 232.27 01-JUN-09:09 578.72 01-JUN-07:10 5845.82 30-JUN-23:10 0.00 0.00 0.00 0.00 0.00 0.00
July 232.27 03-JUL-09:09 578.72 03-JUL-07:10 7794.42 31-JUL-23:10 0.00 0.00 0.00 0.00 0.00 0.00
August 232.27 01-AUG-09:09 578.72 01-AUG-07:10 7794.42 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00 0.00
September 232.27 01-SEP-09:09 578.72 01-SEP-07:10 3897.21 30-SEP-23:10 0.00 0.00 0.00 0.00 0.00 0.00
October 232.27 02-OCT-09:09 578.72 02-OCT-07:10 5845.82 31-OCT-23:10 0.00 0.00 0.00 0.00 0.00 0.00
November 232.27 01-NOV-09:09 578.72 01-NOV-07:10 5845.82 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00 0.00
December 232.27 01-DEC-10:09 578.72 01-DEC-08:09 7794.42 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average             0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 232.27   578.72   1948.61   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 232.27   578.72   7794.42   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 232.27 02-JAN-10:09 578.72 02-JAN-08:09 1948.61 01-JAN-00:10 0.00 0.00 0.00 0.00 0.00 0.00
February 232.27 01-FEB-10:09 578.72 01-FEB-08:09 3897.21 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00 0.00
March 232.27 01-MAR-10:09 578.72 01-MAR-08:09 7794.42 31-MAR-23:10 0.00 0.00 0.00 0.00 0.00 0.00
April 232.27 03-APR-09:09 578.72 03-APR-07:10 7794.42 01-APR-00:10 0.00 0.00 0.00 0.00 0.00 0.00
May 232.27 01-MAY-09:09 578.72 01-MAY-07:10 3897.21 31-MAY-23:10 0.00 0.00 0.00 0.00 0.00 0.00
June 232.27 01-JUN-09:09 578.72 01-JUN-07:10 5845.82 30-JUN-23:10 0.00 0.00 0.00 0.00 0.00 0.00
July 232.27 03-JUL-09:09 578.72 03-JUL-07:10 7794.42 31-JUL-23:10 0.00 0.00 0.00 0.00 0.00 0.00
August 232.27 01-AUG-09:09 578.72 01-AUG-07:10 7794.42 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00 0.00
September 232.27 01-SEP-09:09 578.72 01-SEP-07:10 3897.21 30-SEP-23:10 0.00 0.00 0.00 0.00 0.00 0.00
October 232.27 02-OCT-09:09 578.72 02-OCT-07:10 5845.82 31-OCT-23:10 0.00 0.00 0.00 0.00 0.00 0.00
November 232.27 01-NOV-09:09 578.72 01-NOV-07:10 5845.82 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00 0.00
December 232.27 01-DEC-10:09 578.72 01-DEC-08:09 7794.42 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average             0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 232.27   578.72   1948.61   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 232.27   578.72   7794.42   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 5027.92 02-JAN-10:09 6471.01 02-JAN-08:09 94908.13 01-JAN-00:10 0.00 0.00 0.00 0.00 0.00 0.00
February 5027.92 01-FEB-10:09 6471.01 01-FEB-08:09 189816.26 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00 0.00
March 5027.92 01-MAR-10:09 6471.01 01-MAR-08:09 379632.52 31-MAR-23:10 0.00 0.00 0.00 0.00 0.00 0.00
April 5027.92 03-APR-09:09 6471.01 03-APR-07:10 379632.52 01-APR-00:10 0.00 0.00 0.00 0.00 0.00 0.00
May 5027.92 01-MAY-09:09 6471.01 01-MAY-07:10 189816.26 31-MAY-23:10 0.00 0.00 0.00 0.00 0.00 0.00
June 5027.92 01-JUN-09:09 6471.01 01-JUN-07:10 284724.39 30-JUN-23:10 0.00 0.00 0.00 0.00 0.00 0.00
July 5027.92 03-JUL-09:09 6471.01 03-JUL-07:10 379632.52 31-JUL-23:10 0.00 0.00 0.00 0.00 0.00 0.00
August 5027.92 01-AUG-09:09 6471.01 01-AUG-07:10 379632.52 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00 0.00
September 5027.92 01-SEP-09:09 6471.01 01-SEP-07:10 189816.26 30-SEP-23:10 0.00 0.00 0.00 0.00 0.00 0.00
October 5027.92 02-OCT-09:09 6471.01 02-OCT-07:10 284724.39 31-OCT-23:10 0.00 0.00 0.00 0.00 0.00 0.00
November 5027.92 01-NOV-09:09 6471.01 01-NOV-07:10 284724.39 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00 0.00
December 5027.92 01-DEC-10:09 6471.01 01-DEC-08:09 379632.52 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average             0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 5027.92   6471.01   94908.13   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 5027.92   6471.01   379632.52   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: GROUNDFLOOR_PLENUM

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 5205.26 05-JAN-22:01
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-FEB-00:05 3478.81 17-FEB-04:00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 4117.91 02-MAR-23:00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-APR-00:10 2937.79 27-APR-02:00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 212.89 20-MAY-17:02 5832.21 22-MAY-04:03
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 231.55 29-JUN-15:00 2334.85 14-JUN-02:00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 551.61 30-JUL-12:00 1374.29 05-JUL-01:00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 651.14 06-AUG-17:51 1788.74 23-AUG-03:00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 768.46 03-SEP-12:51 3193.16 12-SEP-03:00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 9.56 18-OCT-15:00 2705.18 30-OCT-23:00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 3285.08 26-NOV-19:52
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 5155.16 01-DEC-04:55
                       
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00        
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00   1374.29  
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 768.46   5832.21  



Table of Contents

Report: PeakSpaceGainsMonthly

For: MIDFLOOR_PLENUM

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 9128.86 05-JAN-22:01
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-FEB-00:05 5863.52 17-FEB-04:00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 7163.37 02-MAR-23:00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-APR-00:10 5099.26 27-APR-02:00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 404.14 20-MAY-17:02 9976.64 22-MAY-04:00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 415.37 29-JUN-15:00 4049.48 14-JUN-02:00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1088.97 30-JUL-12:00 2372.95 05-JUL-01:00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1233.48 06-AUG-17:51 3064.05 23-AUG-03:00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1415.30 03-SEP-13:00 5533.20 12-SEP-03:00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 19.49 18-OCT-15:00 4590.66 30-OCT-22:00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 5362.05 26-NOV-19:52
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 8289.23 01-DEC-04:55
                       
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00        
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00   2372.95  
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1415.30   9976.64  



Table of Contents

Report: PeakSpaceGainsMonthly

For: TOPFLOOR_PLENUM

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 10323.26 05-JAN-22:01
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-FEB-00:05 5802.41 08-FEB-22:01
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 7777.17 02-MAR-23:00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-APR-00:10 5320.18 27-APR-02:00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 357.03 20-MAY-17:02 10017.52 22-MAY-04:10
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 432.29 29-JUN-15:00 4167.42 14-JUN-02:00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 970.20 30-JUL-12:00 2476.09 05-JUL-01:00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1141.87 06-AUG-17:50 3203.45 22-AUG-21:03
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1300.23 03-SEP-13:00 5422.31 12-SEP-03:00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 4884.98 30-OCT-21:03
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 5762.19 29-NOV-22:02
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 8311.35 01-DEC-05:00
                       
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00        
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00   2476.09  
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1300.23   10323.26  



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: BASEMENT

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 119041.38 02-JAN-04:01 0.00 10199.39 107660.35 0.00 0.00 0.00 0.00 0.00 0.00
February 119260.94 21-FEB-05:11 0.00 25501.32 134575.44 0.00 0.00 0.00 0.00 0.00 0.00
March 115710.20 20-MAR-03:01 0.00 8924.46 94202.81 0.00 0.00 0.00 0.00 0.00 0.00
April 120077.72 10-APR-04:11 0.00 25501.32 134575.44 0.00 0.00 0.00 0.00 0.00 0.00
May 119032.90 22-MAY-03:02 0.00 7649.54 80745.26 0.00 0.00 0.00 0.00 0.00 0.00
June 118166.47 12-JUN-04:12 0.00 15300.79 80745.26 0.00 0.00 0.00 0.00 0.00 0.00
July 122563.24 02-JUL-17:45 0.00 12749.23 134575.44 0.00 0.00 0.00 0.00 0.00 0.00
August 119010.41 14-AUG-04:12 0.00 12750.66 67287.72 0.00 0.00 0.00 0.00 0.00 0.00
September 122345.05 03-SEP-13:58 8976.13 12749.23 134575.44 0.00 0.00 0.00 0.00 0.00 0.00
October 121499.44 02-OCT-04:11 0.00 22951.19 121117.90 0.00 0.00 0.00 0.00 0.00 0.00
November 120348.34 13-NOV-04:01 0.00 11474.31 121117.90 0.00 0.00 0.00 0.00 0.00 0.00
December 117716.13 11-DEC-04:01 0.00 8924.46 94202.81 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 115710.20   0.00 7649.54 67287.72 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 122563.24   8976.13 25501.32 134575.44 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: CORE_BOTTOM

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 89272.35 02-JAN-05:01 0.00 16031.39 41563.52 0.00 0.00 0.00 0.00 0.00 0.00
February 90639.00 27-FEB-05:11 0.00 22901.98 59376.45 0.00 0.00 0.00 0.00 0.00 0.00
March 90600.84 02-MAR-05:11 0.00 20611.78 53438.81 0.00 0.00 0.00 0.00 0.00 0.00
April 98180.20 10-APR-04:11 0.00 22901.98 59376.45 0.00 0.00 0.00 0.00 0.00 0.00
May 97307.20 30-MAY-04:12 0.00 13741.19 35625.87 0.00 0.00 0.00 0.00 0.00 0.00
June 96816.16 12-JUN-04:12 0.00 13741.19 35625.87 0.00 0.00 0.00 0.00 0.00 0.00
July 100012.37 05-JUL-04:12 0.00 13741.19 35625.87 0.00 0.00 0.00 0.00 0.00 0.00
August 98499.05 28-AUG-04:12 0.00 13741.19 35625.87 0.00 0.00 0.00 0.00 0.00 0.00
September 102165.59 05-SEP-04:13 0.00 13741.19 35625.87 0.00 0.00 0.00 0.00 0.00 0.00
October 96555.60 02-OCT-04:11 0.00 20611.78 53438.81 0.00 0.00 0.00 0.00 0.00 0.00
November 94278.43 06-NOV-04:02 0.00 6869.83 35625.87 0.00 0.00 0.00 0.00 0.00 0.00
December 90293.88 11-DEC-05:01 0.00 16031.39 41563.52 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 89272.35   0.00 6869.83 35625.87 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 102165.59   0.00 22901.98 59376.45 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: CORE_MID

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 21440.08 19-JAN-16:57 45948.79 61833.04 51619.69 0.00 0.00 0.00 0.00 0.00 0.00
February 33650.96 28-FEB-17:00 15316.26 20611.01 17206.56 0.00 0.00 0.00 0.00 0.00 0.00
March 54523.91 24-MAR-05:03 6448.95 9160.79 30589.44 0.00 0.00 0.00 0.00 0.00 0.00
April 82168.51 26-APR-05:02 8061.19 11450.99 38236.81 0.00 0.00 0.00 0.00 0.00 0.00
May 83821.63 30-MAY-04:12 0.00 13741.19 35625.74 0.00 0.00 0.00 0.00 0.00 0.00
June 86818.05 23-JUN-04:12 0.00 13741.19 35625.74 0.00 0.00 0.00 0.00 0.00 0.00
July 87730.75 19-JUL-04:12 0.00 13741.19 35625.74 0.00 0.00 0.00 0.00 0.00 0.00
August 87988.60 14-AUG-04:12 0.00 11450.99 29688.11 0.00 0.00 0.00 0.00 0.00 0.00
September 87336.45 11-SEP-04:12 0.00 13741.19 35625.74 0.00 0.00 0.00 0.00 0.00 0.00
October 82679.86 19-OCT-05:02 8061.19 11450.99 38236.81 0.00 0.00 0.00 0.00 0.00 0.00
November 68451.95 04-NOV-05:02 8061.19 11450.99 38236.81 0.00 0.00 0.00 0.00 0.00 0.00
December 29509.55 07-DEC-16:30 30632.53 41222.03 34413.13 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 21440.08   0.00 9160.79 17206.56 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 87988.60   45948.79 61833.04 51619.69 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: CORE_TOP

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 17906.48 13-JAN-17:00 30632.53 41222.03 34413.13 0.00 0.00 0.00 0.00 0.00 0.00
February 26715.50 28-FEB-17:00 15316.26 20611.01 17206.56 0.00 0.00 0.00 0.00 0.00 0.00
March 30930.16 23-MAR-15:20 15316.26 20611.01 17206.56 0.00 0.00 0.00 0.00 0.00 0.00
April 43015.26 25-APR-16:00 15316.26 20611.01 17206.56 0.00 0.00 0.00 0.00 0.00 0.00
May 78372.42 20-MAY-05:02 8061.19 11450.99 38236.81 0.00 0.00 0.00 0.00 0.00 0.00
June 86102.43 21-JUN-04:12 0.00 13741.19 35625.74 0.00 0.00 0.00 0.00 0.00 0.00
July 85269.20 19-JUL-04:12 0.00 13741.19 35625.74 0.00 0.00 0.00 0.00 0.00 0.00
August 84133.76 08-AUG-04:12 0.00 13741.19 35625.74 0.00 0.00 0.00 0.00 0.00 0.00
September 83269.40 05-SEP-04:12 0.00 13741.19 35625.74 0.00 0.00 0.00 0.00 0.00 0.00
October 40540.77 18-OCT-16:00 15316.26 20611.01 17206.56 0.00 0.00 0.00 0.00 0.00 0.00
November 29073.16 03-NOV-16:00 15316.26 20611.01 17206.56 0.00 0.00 0.00 0.00 0.00 0.00
December 20914.22 06-DEC-17:00 15316.26 20611.01 17206.56 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 17906.48   0.00 11450.99 17206.56 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 86102.43   30632.53 41222.03 38236.81 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 2364.60 02-JAN-06:02 1619.46 2300.46 7681.96 0.00 0.00 0.00 0.00 0.00 82.06
February 4185.05 27-FEB-16:00 1923.11 1231.33 2160.55 0.00 0.00 0.00 0.00 0.00 46.22
March 4747.51 27-MAR-14:00 2010.79 1231.33 2160.55 0.00 0.00 0.00 0.00 0.00 76.82
April 7576.53 07-APR-14:00 2010.79 1231.33 2160.55 0.00 0.00 0.00 0.00 0.00 10.07
May 8402.39 30-MAY-15:00 1923.11 1231.33 2160.55 0.00 0.00 0.00 0.00 0.00 0.00
June 13344.81 22-JUN-05:02 1012.16 684.10 4801.23 0.00 0.00 0.00 0.00 0.00 26.91
July 18010.64 16-JUL-18:31 0.00 615.62 5032.54 0.00 0.00 0.00 0.00 90.80 0.00
August 17569.19 06-AUG-16:01 809.73 547.22 5761.47 0.00 0.00 0.00 0.00 272.49 0.00
September 17927.78 04-SEP-14:41 910.95 615.62 6481.66 0.00 0.00 0.00 0.00 120.92 0.00
October 6139.04 19-OCT-14:30 1923.11 1231.33 2160.55 0.00 0.00 0.00 0.00 0.00 29.32
November 4052.13 08-NOV-13:30 1923.11 1231.33 2160.55 0.00 0.00 0.00 0.00 0.00 150.57
December 2480.02 06-DEC-06:03 809.73 1150.23 3840.98 0.00 0.00 0.00 0.00 0.00 195.55
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 2364.60   0.00 547.22 2160.55 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 18010.64   2010.79 2300.46 7681.96 0.00 0.00 0.00 0.00 272.49 195.55



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 3197.97 15-JAN-10:53 260.91 176.32 1856.46 0.00 0.00 0.00 0.00 0.00 549.92
February 8066.26 27-FEB-09:55 2478.65 1587.03 2784.68 0.00 0.00 0.00 0.00 0.00 103.07
March 11611.19 28-MAR-09:15 2591.66 1587.03 2784.68 0.00 0.00 0.00 0.00 0.00 133.10
April 19149.25 16-APR-08:52 326.14 220.40 2320.57 0.00 0.00 0.00 0.00 0.00 463.02
May 14582.43 19-MAY-08:30 1239.33 793.52 1392.34 0.00 0.00 0.00 0.00 0.00 32.73
June 25209.95 25-JUN-08:22 391.37 264.49 2784.68 0.00 0.00 0.00 0.00 0.00 112.86
July 26503.63 02-JUL-08:41 456.59 308.57 3248.80 0.00 0.00 0.00 0.00 0.00 111.74
August 26729.74 06-AUG-09:21 521.82 352.65 3712.91 0.00 0.00 0.00 0.00 6.06 0.00
September 27686.20 04-SEP-08:41 521.82 352.65 3712.91 0.00 0.00 0.00 0.00 0.00 48.43
October 21438.06 15-OCT-09:32 326.14 220.40 2320.57 0.00 0.00 0.00 0.00 0.00 366.68
November 7134.91 06-NOV-09:35 2478.65 1587.03 2784.68 0.00 0.00 0.00 0.00 0.00 54.71
December 3280.92 20-DEC-10:05 2591.66 1587.03 2784.68 0.00 0.00 0.00 0.00 0.00 115.66
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 3197.97   260.91 176.32 1392.34 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 27686.20   2591.66 1587.03 3712.91 0.00 0.00 0.00 0.00 6.06 549.92



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 26016.09 15-JAN-13:32 506.09 342.02 3600.97 0.00 0.00 0.00 0.00 0.00 768.32
February 32274.02 26-FEB-13:42 607.31 410.42 4321.17 0.00 0.00 0.00 0.00 0.00 497.50
March 32350.49 26-MAR-13:22 607.31 410.42 4321.17 0.00 0.00 0.00 0.00 0.00 839.52
April 32419.28 16-APR-13:32 607.31 410.42 4321.17 0.00 0.00 0.00 0.00 0.00 413.54
May 18069.32 19-MAY-13:30 2010.83 1231.36 2160.58 0.00 0.00 0.00 0.00 33.82 0.00
June 25882.45 11-JUN-12:23 404.87 273.61 2880.78 0.00 0.00 0.00 0.00 0.00 48.86
July 30904.97 16-JUL-13:12 607.31 410.42 4321.17 0.00 0.00 0.00 0.00 41.40 0.00
August 31750.73 06-AUG-13:21 708.53 478.83 5041.36 0.00 0.00 0.00 0.00 194.62 0.00
September 34798.80 04-SEP-14:41 910.97 615.63 6481.75 0.00 0.00 0.00 0.00 61.75 0.00
October 36754.57 15-OCT-13:31 1012.19 684.04 7201.95 0.00 0.00 0.00 0.00 0.00 421.10
November 29767.73 12-NOV-13:02 506.09 342.02 3600.97 0.00 0.00 0.00 0.00 0.00 474.61
December 18278.95 17-DEC-13:43 404.87 273.61 2880.78 0.00 0.00 0.00 0.00 0.00 1320.46
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 18069.32   404.87 273.61 2160.58 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 36754.57   2010.83 1231.36 7201.95 0.00 0.00 0.00 0.00 194.62 1320.46



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 5786.22 13-JAN-15:30 1239.33 793.52 1392.33 0.00 0.00 0.00 0.00 0.00 152.78
February 18839.92 26-FEB-16:22 326.14 220.40 2320.55 0.00 0.00 0.00 0.00 0.00 234.14
March 16003.33 12-MAR-16:12 326.14 220.40 2320.55 0.00 0.00 0.00 0.00 0.00 914.32
April 33209.75 16-APR-16:51 587.05 396.73 4177.00 0.00 0.00 0.00 0.00 0.00 205.62
May 31612.32 28-MAY-17:21 0.00 308.57 2522.44 0.00 0.00 0.00 0.00 0.00 289.19
June 32099.89 18-JUN-17:21 0.00 308.57 2522.44 0.00 0.00 0.00 0.00 0.00 27.69
July 34439.99 16-JUL-17:11 0.00 396.73 3243.14 0.00 0.00 0.00 0.00 38.62 0.00
August 33579.08 06-AUG-16:41 521.82 352.65 3712.89 0.00 0.00 0.00 0.00 137.86 0.00
September 35973.69 04-SEP-16:01 652.28 440.81 4641.11 0.00 0.00 0.00 0.00 30.82 0.00
October 32661.67 15-OCT-15:31 521.82 352.65 3712.89 0.00 0.00 0.00 0.00 0.00 251.41
November 11155.76 03-NOV-15:30 1239.33 793.52 1392.33 0.00 0.00 0.00 0.00 0.00 61.79
December 9774.76 06-DEC-15:30 1239.33 793.52 1392.33 0.00 0.00 0.00 0.00 0.00 214.22
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 5786.22   0.00 220.40 1392.33 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 35973.69   1239.33 793.52 4641.11 0.00 0.00 0.00 0.00 137.86 914.32



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 1478.40 13-JAN-16:50 1923.11 2587.92 2160.55 0.00 0.00 0.00 0.00 0.00 392.39
February 2528.75 27-FEB-14:00 1923.11 1231.33 2160.55 0.00 0.00 0.00 0.00 0.00 112.03
March 2595.45 23-MAR-13:30 2010.79 1231.33 2160.55 0.00 0.00 0.00 0.00 0.00 551.73
April 5651.22 07-APR-14:30 1923.11 1231.33 2160.55 0.00 0.00 0.00 0.00 0.00 60.30
May 7875.94 19-MAY-16:00 1923.11 1231.33 2160.55 0.00 0.00 0.00 0.00 178.84 0.00
June 12171.82 21-JUN-05:02 1012.16 684.10 4801.23 0.00 0.00 0.00 0.00 0.00 165.23
July 17220.69 16-JUL-18:21 0.00 684.02 5591.71 0.00 0.00 0.00 0.00 180.59 0.00
August 16463.47 06-AUG-16:01 809.73 547.22 5761.47 0.00 0.00 0.00 0.00 638.46 0.00
September 16919.56 04-SEP-12:51 708.51 478.82 5041.29 0.00 0.00 0.00 0.00 440.82 0.00
October 4564.13 19-OCT-14:30 1923.11 1231.33 2160.55 0.00 0.00 0.00 0.00 0.00 71.64
November 2530.59 03-NOV-13:50 4021.58 2462.66 4321.10 0.00 0.00 0.00 0.00 0.00 180.30
December 1649.57 06-DEC-16:20 1923.11 2587.92 2160.55 0.00 0.00 0.00 0.00 0.00 537.11
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 1478.40   0.00 478.82 2160.55 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 17220.69   4021.58 2587.92 5761.47 0.00 0.00 0.00 0.00 638.46 551.73



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 2295.13 20-JAN-10:00 2478.65 1587.03 2784.68 0.00 0.00 0.00 0.00 0.00 635.97
February 5562.18 28-FEB-09:55 2478.65 1587.03 2784.68 0.00 0.00 0.00 0.00 0.00 159.69
March 9474.68 28-MAR-10:10 1239.33 793.52 1392.34 0.00 0.00 0.00 0.00 0.00 214.50
April 13543.61 25-APR-09:00 1239.33 793.52 1392.34 0.00 0.00 0.00 0.00 0.00 98.65
May 15345.69 19-MAY-08:50 1239.33 793.52 1392.34 0.00 0.00 0.00 0.00 0.00 74.37
June 30517.08 25-JUN-08:41 587.05 396.73 4177.03 0.00 0.00 0.00 0.00 0.00 283.16
July 32371.57 02-JUL-09:01 652.28 440.81 4641.14 0.00 0.00 0.00 0.00 0.00 323.57
August 29379.77 06-AUG-09:21 521.82 352.65 3712.91 0.00 0.00 0.00 0.00 0.00 7.69
September 29008.65 04-SEP-08:51 521.82 352.65 3712.91 0.00 0.00 0.00 0.00 0.00 93.50
October 9388.81 18-OCT-10:10 1239.33 793.52 1392.34 0.00 0.00 0.00 0.00 0.00 95.83
November 4996.49 03-NOV-10:10 1239.33 793.52 1392.34 0.00 0.00 0.00 0.00 0.00 226.46
December 2420.02 20-DEC-10:00 2478.65 1587.03 2784.68 0.00 0.00 0.00 0.00 0.00 225.61
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 2295.13   521.82 352.65 1392.34 0.00 0.00 0.00 0.00 0.00 7.69
Maximum of Months 32371.57   2478.65 1587.03 4641.14 0.00 0.00 0.00 0.00 0.00 635.97



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 18766.20 15-JAN-13:13 404.87 273.61 2880.78 0.00 0.00 0.00 0.00 0.00 1880.50
February 34154.52 26-FEB-14:01 708.53 478.83 5041.36 0.00 0.00 0.00 0.00 0.00 1166.22
March 29922.34 26-MAR-13:32 506.09 342.02 3600.97 0.00 0.00 0.00 0.00 0.00 1823.71
April 32240.12 16-APR-15:02 607.31 410.42 4321.17 0.00 0.00 0.00 0.00 0.00 880.13
May 21763.26 14-MAY-13:52 607.31 410.42 4321.17 0.00 0.00 0.00 0.00 0.00 1653.46
June 30837.93 18-JUN-13:42 506.09 342.02 3600.97 0.00 0.00 0.00 0.00 0.00 161.79
July 34159.40 16-JUL-13:41 809.75 547.23 5761.56 0.00 0.00 0.00 0.00 84.74 0.00
August 33044.87 06-AUG-13:21 708.53 478.83 5041.36 0.00 0.00 0.00 0.00 437.18 0.00
September 35746.86 04-SEP-15:31 1012.19 684.04 7201.95 0.00 0.00 0.00 0.00 135.77 0.00
October 34842.40 15-OCT-13:41 708.53 478.83 5041.36 0.00 0.00 0.00 0.00 0.00 791.18
November 32522.56 12-NOV-12:12 607.31 410.42 4321.17 0.00 0.00 0.00 0.00 0.00 1162.02
December 16482.54 12-DEC-12:40 1058.33 1231.36 1920.52 0.00 0.00 0.00 0.00 0.00 407.84
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 16482.54   404.87 273.61 1920.52 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 35746.86   1058.33 1231.36 7201.95 0.00 0.00 0.00 0.00 437.18 1880.50



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 3192.61 13-JAN-15:50 1239.33 793.52 1392.33 0.00 0.00 0.00 0.00 0.00 384.55
February 9066.40 28-FEB-16:40 1239.33 793.52 1392.33 0.00 0.00 0.00 0.00 0.00 156.78
March 11796.90 28-MAR-17:00 391.37 440.84 773.52 0.00 0.00 0.00 0.00 0.00 356.46
April 30941.82 16-APR-16:21 521.82 352.65 3712.89 0.00 0.00 0.00 0.00 0.00 536.20
May 33753.22 28-MAY-17:51 0.00 440.81 3603.49 0.00 0.00 0.00 0.00 0.00 907.34
June 33791.75 18-JUN-17:41 0.00 440.81 3603.49 0.00 0.00 0.00 0.00 0.00 132.69
July 35712.50 16-JUL-17:01 0.00 440.81 3603.49 0.00 0.00 0.00 0.00 44.89 0.00
August 30623.94 06-AUG-16:41 521.82 352.65 3712.89 0.00 0.00 0.00 0.00 335.58 0.00
September 34085.64 04-SEP-16:11 652.28 440.81 4641.11 0.00 0.00 0.00 0.00 61.53 0.00
October 18582.20 15-OCT-15:42 391.37 264.49 2784.67 0.00 0.00 0.00 0.00 0.00 465.78
November 7009.89 03-NOV-15:40 1239.33 793.52 1392.33 0.00 0.00 0.00 0.00 0.00 146.90
December 3829.71 06-DEC-15:40 1239.33 793.52 1392.33 0.00 0.00 0.00 0.00 0.00 492.95
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 3192.61   0.00 264.49 773.52 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 35712.50   1239.33 793.52 4641.11 0.00 0.00 0.00 0.00 335.58 907.34



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 1450.96 14-JAN-17:03 404.87 575.05 2880.74 0.00 0.00 0.00 0.00 0.00 452.82
February 2273.63 27-FEB-13:30 1923.11 1231.33 2160.55 0.00 0.00 0.00 0.00 0.00 143.85
March 2389.61 23-MAR-13:30 2010.79 1231.33 2160.55 0.00 0.00 0.00 0.00 0.00 673.87
April 5505.70 07-APR-14:30 1923.11 1231.33 2160.55 0.00 0.00 0.00 0.00 0.00 79.94
May 8656.06 19-MAY-16:00 1923.11 1231.33 2160.55 0.00 0.00 0.00 0.00 215.48 0.00
June 11278.10 21-JUN-05:02 1012.16 684.10 4801.23 0.00 0.00 0.00 0.00 0.00 207.59
July 19700.34 02-JUL-18:31 0.00 684.02 5591.71 0.00 0.00 0.00 0.00 0.00 155.16
August 19360.96 06-AUG-16:01 809.73 547.22 5761.47 0.00 0.00 0.00 0.00 762.55 0.00
September 18687.42 04-SEP-16:21 809.73 547.22 5761.47 0.00 0.00 0.00 0.00 292.92 0.00
October 4096.42 19-OCT-14:40 1923.11 1231.33 2160.55 0.00 0.00 0.00 0.00 0.00 89.21
November 2254.93 03-NOV-13:30 2010.79 1231.33 2160.55 0.00 0.00 0.00 0.00 0.00 221.46
December 1623.57 06-DEC-16:20 1923.11 2587.92 2160.55 0.00 0.00 0.00 0.00 0.00 649.73
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 1450.96   0.00 547.22 2160.55 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 19700.34   2010.79 2587.92 5761.47 0.00 0.00 0.00 0.00 762.55 673.87



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 2108.18 31-JAN-10:30 2591.66 1587.03 2784.68 0.00 0.00 0.00 0.00 0.00 605.40
February 3573.99 28-FEB-10:30 1295.83 793.52 1392.34 0.00 0.00 0.00 0.00 0.00 204.10
March 8055.75 28-MAR-09:35 2591.66 1587.03 2784.68 0.00 0.00 0.00 0.00 0.00 337.31
April 12590.12 25-APR-09:30 1295.83 793.52 1392.34 0.00 0.00 0.00 0.00 0.00 132.64
May 14852.45 19-MAY-08:50 1239.33 793.52 1392.34 0.00 0.00 0.00 0.00 0.00 93.86
June 29381.90 25-JUN-08:11 521.82 352.65 3712.91 0.00 0.00 0.00 0.00 0.00 393.61
July 31924.14 02-JUL-08:31 652.28 440.81 4641.14 0.00 0.00 0.00 0.00 0.00 484.37
August 29405.92 06-AUG-09:21 521.82 352.65 3712.91 0.00 0.00 0.00 0.00 0.00 15.40
September 25792.94 04-SEP-09:02 391.37 264.49 2784.68 0.00 0.00 0.00 0.00 0.00 19.51
October 8529.49 18-OCT-09:50 1295.83 793.52 1392.34 0.00 0.00 0.00 0.00 0.00 146.07
November 3263.16 03-NOV-10:00 1295.83 793.52 1392.34 0.00 0.00 0.00 0.00 0.00 286.90
December 2214.00 20-DEC-10:20 2591.66 1587.03 2784.68 0.00 0.00 0.00 0.00 0.00 327.84
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 2108.18   391.37 264.49 1392.34 0.00 0.00 0.00 0.00 0.00 15.40
Maximum of Months 31924.14   2591.66 1587.03 4641.14 0.00 0.00 0.00 0.00 0.00 605.40



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 15198.02 31-JAN-13:30 1923.15 1231.36 2160.58 0.00 0.00 0.00 0.00 0.00 836.36
February 34851.62 26-FEB-14:01 708.53 478.83 5041.36 0.00 0.00 0.00 0.00 0.00 1388.70
March 26175.23 26-MAR-14:02 607.31 410.42 4321.17 0.00 0.00 0.00 0.00 0.00 2129.58
April 21605.86 25-APR-13:30 2010.83 1231.36 2160.58 0.00 0.00 0.00 0.00 0.00 161.46
May 23409.43 14-MAY-14:22 506.09 342.02 3600.97 0.00 0.00 0.00 0.00 0.00 2227.56
June 32004.87 25-JUN-16:11 809.75 547.23 5761.56 0.00 0.00 0.00 0.00 0.00 269.69
July 34557.39 02-JUL-13:12 607.31 410.42 4321.17 0.00 0.00 0.00 0.00 0.00 158.77
August 35360.05 06-AUG-13:21 708.53 478.83 5041.36 0.00 0.00 0.00 0.00 522.30 0.00
September 37751.71 03-SEP-12:41 809.75 547.23 5761.56 0.00 0.00 0.00 0.00 561.01 0.00
October 35958.42 15-OCT-13:41 708.53 478.83 5041.36 0.00 0.00 0.00 0.00 0.00 918.59
November 24041.73 03-NOV-13:30 2010.83 1231.36 2160.58 0.00 0.00 0.00 0.00 0.00 291.02
December 13579.97 12-DEC-14:30 2010.83 1231.36 2160.58 0.00 0.00 0.00 0.00 0.00 579.99
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 13579.97   506.09 342.02 2160.58 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 37751.71   2010.83 1231.36 5761.56 0.00 0.00 0.00 0.00 561.01 2227.56



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 3219.23 13-JAN-15:50 1239.33 793.52 1392.33 0.00 0.00 0.00 0.00 0.00 470.77
February 8636.47 28-FEB-16:40 1239.33 793.52 1392.33 0.00 0.00 0.00 0.00 0.00 196.20
March 11585.26 28-MAR-17:00 391.37 440.84 773.52 0.00 0.00 0.00 0.00 0.00 446.15
April 29835.58 22-APR-17:41 456.59 308.57 3248.78 0.00 0.00 0.00 0.00 0.00 717.59
May 35270.52 28-MAY-17:51 0.00 440.81 3603.49 0.00 0.00 0.00 0.00 0.00 1127.34
June 35672.92 18-JUN-17:11 0.00 440.81 3603.49 0.00 0.00 0.00 0.00 0.00 135.77
July 36675.62 02-JUL-17:51 0.00 440.81 3603.49 0.00 0.00 0.00 0.00 0.00 205.36
August 32628.64 06-AUG-16:41 521.82 352.65 3712.89 0.00 0.00 0.00 0.00 398.88 0.00
September 32623.29 04-SEP-16:21 521.82 352.65 3712.89 0.00 0.00 0.00 0.00 129.37 0.00
October 15053.53 15-OCT-16:22 326.14 220.40 2320.55 0.00 0.00 0.00 0.00 0.00 599.88
November 6512.30 03-NOV-15:40 1239.33 793.52 1392.33 0.00 0.00 0.00 0.00 0.00 184.44
December 3466.79 06-DEC-15:50 1239.33 793.52 1392.33 0.00 0.00 0.00 0.00 0.00 592.70
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 3219.23   0.00 220.40 773.52 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 36675.62   1239.33 793.52 3712.89 0.00 0.00 0.00 0.00 398.88 1127.34



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: GROUNDFLOOR_PLENUM

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 10818.23 06-JAN-05:01 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 2601.67
February 9873.44 04-FEB-05:01 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1723.66
March 8763.65 04-MAR-05:01 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1640.95
April 6567.84 24-APR-16:00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 93.82
May 8144.18 30-MAY-05:15 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 172.21
June 8570.88 26-JUN-05:15 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 148.47
July 10642.96 17-JUL-15:20 0.00 0.00 0.00 0.00 0.00 0.00 0.00 53.42 0.00
August 11652.63 07-AUG-05:15 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 90.81
September 11999.96 05-SEP-05:03 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 89.73
October 6145.43 16-OCT-15:50 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 105.10
November 10640.67 27-NOV-05:01 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 3052.66
December 10127.31 28-DEC-05:01 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 2230.34
                       
Annual Sum or Average     0.00 0.00 0.00 0.00 0.00 0.00 0.00    
Minimum of Months 6145.43   0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 11999.96   0.00 0.00 0.00 0.00 0.00 0.00 0.00 53.42 3052.66



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: MIDFLOOR_PLENUM

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 15039.52 06-JAN-04:01 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 6364.47
February 13991.63 10-FEB-04:11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1583.09
March 16331.48 04-MAR-04:01 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 3126.41
April 12546.71 29-APR-04:01 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 3265.82
May 10814.91 22-MAY-04:42 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 9844.06
June 7274.05 23-JUN-15:30 0.00 0.00 0.00 0.00 0.00 0.00 0.00 76.55 0.00
July 8991.64 17-JUL-15:30 0.00 0.00 0.00 0.00 0.00 0.00 0.00 146.54 0.00
August 8928.88 07-AUG-15:40 0.00 0.00 0.00 0.00 0.00 0.00 0.00 134.57 0.00
September 8477.26 05-SEP-14:40 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 11.67
October 9851.59 10-OCT-04:01 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 2653.20
November 11302.21 27-NOV-02:21 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 4828.66
December 14364.01 23-DEC-04:01 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 3966.79
                       
Annual Sum or Average     0.00 0.00 0.00 0.00 0.00 0.00 0.00    
Minimum of Months 7274.05   0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 16331.48   0.00 0.00 0.00 0.00 0.00 0.00 0.00 146.54 9844.06



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: TOPFLOOR_PLENUM

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 341.66 14-JAN-13:30 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 514.03
February 3278.14 26-FEB-14:44 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 945.70
March 5222.14 23-MAR-13:55 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1198.69
April 12276.06 25-APR-15:00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 185.96
May 17793.21 19-MAY-15:00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 183.04 0.00
June 20243.87 23-JUN-13:30 0.00 0.00 0.00 0.00 0.00 0.00 0.00 94.43 0.00
July 24012.12 17-JUL-14:50 0.00 0.00 0.00 0.00 0.00 0.00 0.00 16.81 0.00
August 21733.44 07-AUG-15:40 0.00 0.00 0.00 0.00 0.00 0.00 0.00 142.35 0.00
September 16251.06 01-SEP-15:40 0.00 0.00 0.00 0.00 0.00 0.00 0.00 142.81 0.00
October 9811.65 18-OCT-15:20 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 32.86
November 2475.42 03-NOV-14:15 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 418.12
December 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 5183.63
                       
Annual Sum or Average     0.00 0.00 0.00 0.00 0.00 0.00 0.00    
Minimum of Months 0.00   0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 24012.12   0.00 0.00 0.00 0.00 0.00 0.00 0.00 183.04 5183.63



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 2249.31 19-JAN-16:50 222.14 578.72 1948.61 0.00 0.00 0.00 0.00 0.00 0.00
February 4600.84 26-FEB-17:27 35.07 96.46 11691.63 0.00 0.00 0.00 0.00 0.00 0.00
March 6810.82 31-MAR-24:00 0.00 32.15 7794.42 0.00 0.00 0.00 0.00 0.00 0.00
April 8501.87 22-APR-18:10 0.00 32.15 7794.42 0.00 0.00 0.00 0.00 0.00 0.00
May 3508.69 31-MAY-24:00 0.00 32.15 3897.21 0.00 0.00 0.00 0.00 0.00 0.00
June 5376.53 30-JUN-24:00 0.00 32.15 5845.82 0.00 0.00 0.00 0.00 0.00 0.00
July 7270.88 31-JUL-23:45 0.00 64.31 15588.84 0.00 0.00 0.00 0.00 0.00 0.00
August 8528.18 03-AUG-18:50 23.38 192.90 7794.42 0.00 0.00 0.00 0.00 0.00 0.00
September 3303.90 30-SEP-24:00 0.00 32.15 3897.21 0.00 0.00 0.00 0.00 0.00 0.00
October 4932.76 31-OCT-24:00 0.00 32.15 5845.82 0.00 0.00 0.00 0.00 0.00 0.00
November 6340.38 13-NOV-16:30 222.14 578.72 5845.82 0.00 0.00 0.00 0.00 0.00 0.00
December 8084.68 06-DEC-16:10 222.14 578.72 7794.42 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 2249.31   0.00 32.15 1948.61 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 8528.18   222.14 578.72 15588.84 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: DATACENTER_MID_ZN_6

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 1867.81 19-JAN-16:50 222.14 578.72 1948.61 0.00 0.00 0.00 0.00 0.00 0.00
February 4220.37 28-FEB-17:00 222.14 578.72 3897.21 0.00 0.00 0.00 0.00 0.00 0.00
March 6212.16 28-MAR-17:50 23.38 192.90 5845.82 0.00 0.00 0.00 0.00 0.00 0.00
April 8069.72 25-APR-18:10 23.38 192.90 7794.42 0.00 0.00 0.00 0.00 0.00 0.00
May 3302.64 31-MAY-24:00 0.00 32.15 3897.21 0.00 0.00 0.00 0.00 0.00 0.00
June 5249.46 30-JUN-24:00 0.00 32.15 5845.82 0.00 0.00 0.00 0.00 0.00 0.00
July 7065.97 31-JUL-23:53 0.00 128.61 31177.69 0.00 0.00 0.00 0.00 0.00 0.00
August 8198.17 03-AUG-18:50 23.38 192.90 7794.42 0.00 0.00 0.00 0.00 0.00 0.00
September 2873.68 30-SEP-23:30 0.00 32.15 3897.21 0.00 0.00 0.00 0.00 0.00 0.00
October 4300.32 16-OCT-17:00 70.15 321.51 3897.21 0.00 0.00 0.00 0.00 0.00 0.00
November 5750.11 10-NOV-16:30 222.14 578.72 5845.82 0.00 0.00 0.00 0.00 0.00 0.00
December 7376.02 06-DEC-16:20 222.14 578.72 7794.42 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 1867.81   0.00 32.15 1948.61 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 8198.17   222.14 578.72 31177.69 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 1638.36 13-JAN-16:30 222.14 578.72 1948.61 0.00 0.00 0.00 0.00 0.00 0.00
February 4162.72 28-FEB-17:00 222.14 578.72 3897.21 0.00 0.00 0.00 0.00 0.00 0.00
March 6202.27 28-MAR-17:50 23.38 192.90 5845.82 0.00 0.00 0.00 0.00 0.00 0.00
April 8133.73 25-APR-18:10 23.38 192.90 7794.42 0.00 0.00 0.00 0.00 0.00 0.00
May 3221.05 31-MAY-23:30 0.00 32.15 3897.21 0.00 0.00 0.00 0.00 0.00 0.00
June 5234.38 30-JUN-23:33 0.00 96.46 17537.45 0.00 0.00 0.00 0.00 0.00 0.00
July 7049.44 31-JUL-23:53 0.00 128.61 31177.69 0.00 0.00 0.00 0.00 0.00 0.00
August 8260.23 03-AUG-18:50 23.38 192.90 7794.42 0.00 0.00 0.00 0.00 0.00 0.00
September 3025.79 04-SEP-17:51 0.00 289.38 17537.45 0.00 0.00 0.00 0.00 0.00 0.00
October 4327.09 18-OCT-17:00 70.15 321.51 3897.21 0.00 0.00 0.00 0.00 0.00 0.00
November 5688.57 03-NOV-16:00 222.14 578.72 5845.82 0.00 0.00 0.00 0.00 0.00 0.00
December 7310.22 06-DEC-16:20 222.14 578.72 7794.42 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 1638.36   0.00 32.15 1948.61 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 8260.23   222.14 578.72 31177.69 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 92071.65 03-JAN-17:00 4808.68 6471.01 94908.13 0.00 0.00 0.00 0.00 0.00 0.00
February 184356.90 28-FEB-17:00 4808.68 6471.01 189816.26 0.00 0.00 0.00 0.00 0.00 0.00
March 358038.15 31-MAR-24:00 0.00 359.47 379632.52 0.00 0.00 0.00 0.00 0.00 0.00
April 368316.92 25-APR-16:00 4808.68 6471.01 379632.52 0.00 0.00 0.00 0.00 0.00 0.00
May 176652.70 31-MAY-24:00 0.00 359.47 189816.26 0.00 0.00 0.00 0.00 0.00 0.00
June 268627.72 30-JUN-24:00 0.00 359.47 284724.39 0.00 0.00 0.00 0.00 0.00 0.00
July 360924.35 31-JUL-23:53 0.00 1437.90 1518530.09 0.00 0.00 0.00 0.00 0.00 0.00
August 383626.60 06-AUG-19:52 0.00 2156.84 2277795.13 0.00 0.00 0.00 0.00 0.00 0.00
September 176028.50 30-SEP-24:00 0.00 359.47 189816.26 0.00 0.00 0.00 0.00 0.00 0.00
October 267971.63 31-OCT-24:00 0.00 359.47 284724.39 0.00 0.00 0.00 0.00 0.00 0.00
November 277147.98 06-NOV-16:55 9617.36 12942.03 569448.78 0.00 0.00 0.00 0.00 0.00 0.00
December 368477.76 06-DEC-17:00 4808.68 6471.01 379632.52 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 92071.65   0.00 359.47 94908.13 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 383626.60   9617.36 12942.03 2277795.13 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: EnergyConsumptionElectricityNaturalGasMonthly

For: Meter

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

ELECTRICITY:FACILITY [J] ELECTRICITY:FACILITY {Maximum} [W] ELECTRICITY:FACILITY {TIMESTAMP} NATURALGAS:FACILITY [J] NATURALGAS:FACILITY {Maximum} [W] NATURALGAS:FACILITY {TIMESTAMP}
January 0.173157E+13 1160969.06 03-JAN-08:09 0.127302E+13 2464803.67 09-JAN-07:10
February 0.194993E+13 1334684.76 27-FEB-16:10 0.691502E+12 1648555.87 01-FEB-07:10
March 0.253778E+13 1396861.56 16-MAR-15:50 0.467845E+12 1739588.17 06-MAR-07:10
April 0.278034E+13 1836569.20 06-APR-15:00 0.178186E+12 669964.85 29-APR-04:10
May 0.181348E+13 1499348.78 31-MAY-15:00 0.145447E+12 783422.13 08-MAY-04:10
June 0.229250E+13 1737970.09 23-JUN-15:50 0.717264E+11 246804.30 16-JUN-06:00
July 0.286898E+13 2012126.07 17-JUL-15:30 0.653639E+11 81333.28 03-JUL-11:39
August 0.338698E+13 2225335.88 07-AUG-15:39 0.691591E+11 199518.38 18-AUG-05:10
September 0.180038E+13 1568367.43 07-SEP-15:09 0.851136E+11 392322.07 20-SEP-05:10
October 0.220065E+13 1613674.06 18-OCT-15:00 0.152728E+12 820092.47 10-OCT-06:30
November 0.244813E+13 1545281.00 17-NOV-16:00 0.401268E+12 1519734.68 27-NOV-07:19
December 0.282731E+13 1562595.15 06-DEC-16:30 0.857882E+12 1780976.15 29-DEC-07:00
             
Annual Sum or Average 0.286380E+14     0.445924E+13    
Minimum of Months 0.173157E+13 1160969.06   0.653639E+11 81333.28  
Maximum of Months 0.338698E+13 2225335.88   0.127302E+13 2464803.67  



Table of Contents

Report: EndUseEnergyConsumptionElectricityMonthly

For: Meter

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

INTERIORLIGHTS:ELECTRICITY [J] EXTERIORLIGHTS:ELECTRICITY [J] INTERIOREQUIPMENT:ELECTRICITY [J] EXTERIOREQUIPMENT:ELECTRICITY [J] FANS:ELECTRICITY [J] PUMPS:ELECTRICITY [J] HEATING:ELECTRICITY [J] COOLING:ELECTRICITY [J] HEATREJECTION:ELECTRICITY [J] HUMIDIFIER:ELECTRICITY [J] HEATRECOVERY:ELECTRICITY [] WATERSYSTEMS:ELECTRICITY [] COGENERATION:ELECTRICITY []
January 0.337744E+12 0.801882E+11 0.766053E+12 0.164274E+12 0.199202E+12 0.144654E+11 0.00 0.848251E+10 0.850726E+09 0.160315E+12 0.00 0.00 0.00
February 0.299802E+12 0.648776E+11 0.978954E+12 0.148382E+12 0.179056E+12 0.143861E+11 0.00 0.271417E+11 0.402468E+10 0.233306E+12 0.00 0.00 0.00
March 0.352664E+12 0.612557E+11 0.141687E+13 0.164522E+12 0.207075E+12 0.158312E+11 0.00 0.457485E+11 0.597019E+10 0.267840E+12 0.00 0.00 0.00
April 0.312841E+12 0.485976E+11 0.165903E+13 0.158945E+12 0.206769E+12 0.195792E+11 0.00 0.909906E+11 0.255641E+11 0.258029E+12 0.00 0.00 0.00
May 0.335641E+12 0.412601E+11 0.774844E+12 0.164393E+12 0.224691E+12 0.254446E+11 0.00 0.585879E+11 0.288359E+11 0.159780E+12 0.00 0.00 0.00
June 0.332814E+12 0.359021E+11 0.106252E+13 0.159182E+12 0.266885E+12 0.410171E+11 0.00 0.187124E+12 0.687513E+11 0.138303E+12 0.00 0.00 0.00
July 0.312568E+12 0.386184E+11 0.139340E+13 0.164155E+12 0.299827E+12 0.558253E+11 0.00 0.384144E+12 0.108107E+12 0.112335E+12 0.00 0.00 0.00
August 0.348519E+12 0.459508E+11 0.173200E+13 0.164521E+12 0.296817E+12 0.529599E+11 0.00 0.413824E+12 0.109428E+12 0.222965E+12 0.00 0.00 0.00
September 0.314055E+12 0.546090E+11 0.740713E+12 0.158944E+12 0.232187E+12 0.336199E+11 0.00 0.106003E+12 0.514591E+11 0.108790E+12 0.00 0.00 0.00
October 0.329193E+12 0.674053E+11 0.108340E+13 0.164269E+12 0.212191E+12 0.217831E+11 0.00 0.566453E+11 0.194042E+11 0.246358E+12 0.00 0.00 0.00
November 0.330498E+12 0.748889E+11 0.135889E+13 0.159045E+12 0.195030E+12 0.160253E+11 0.00 0.456432E+11 0.891067E+10 0.259199E+12 0.00 0.00 0.00
December 0.327075E+12 0.829175E+11 0.170972E+13 0.164162E+12 0.198101E+12 0.153465E+11 0.00 0.559737E+11 0.617722E+10 0.267840E+12 0.00 0.00 0.00
                           
Annual Sum or Average 0.393341E+13 0.696471E+12 0.146764E+14 0.193480E+13 0.271783E+13 0.326284E+12 0.00 0.148031E+13 0.437484E+12 0.243506E+13 0.00 0.00 0.00
Minimum of Months 0.299802E+12 0.359021E+11 0.740713E+12 0.148382E+12 0.179056E+12 0.143861E+11 0.00 0.848251E+10 0.850726E+09 0.108790E+12 0.00 0.00 0.00
Maximum of Months 0.352664E+12 0.829175E+11 0.173200E+13 0.164522E+12 0.299827E+12 0.558253E+11 0.00 0.413824E+12 0.109428E+12 0.267840E+12 0.00 0.00 0.00



Table of Contents

Report: EndUseEnergyConsumptionNaturalGasMonthly

For: Meter

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

INTERIOREQUIPMENT:NATURALGAS [] EXTERIOREQUIPMENT:NATURALGAS [] HEATING:NATURALGAS [J] COOLING:NATURALGAS [] WATERSYSTEMS:NATURALGAS [J] COGENERATION:NATURALGAS [] HUMIDIFIER:NATURALGAS []
January 0.00 0.00 0.119686E+13 0.00 0.761577E+11 0.00 0.00
February 0.00 0.00 0.621599E+12 0.00 0.699027E+11 0.00 0.00
March 0.00 0.00 0.387646E+12 0.00 0.801989E+11 0.00 0.00
April 0.00 0.00 0.105967E+12 0.00 0.722184E+11 0.00 0.00
May 0.00 0.00 0.720158E+11 0.00 0.734310E+11 0.00 0.00
June 0.00 0.00 0.257300E+10 0.00 0.691534E+11 0.00 0.00
July 0.00 0.00 38294535.48 0.00 0.653256E+11 0.00 0.00
August 0.00 0.00 0.857104E+09 0.00 0.683020E+11 0.00 0.00
September 0.00 0.00 0.212011E+11 0.00 0.639125E+11 0.00 0.00
October 0.00 0.00 0.847521E+11 0.00 0.679759E+11 0.00 0.00
November 0.00 0.00 0.332071E+12 0.00 0.691966E+11 0.00 0.00
December 0.00 0.00 0.785284E+12 0.00 0.725979E+11 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.361086E+13 0.00 0.848373E+12 0.00 0.00
Minimum of Months 0.00 0.00 38294535.48 0.00 0.639125E+11 0.00 0.00
Maximum of Months 0.00 0.00 0.119686E+13 0.00 0.801989E+11 0.00 0.00



Table of Contents

Report: PeakEnergyEndUseElectricityPart1Monthly

For: Meter

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

INTERIORLIGHTS:ELECTRICITY {Maximum} [W] INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} EXTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] EXTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} FANS:ELECTRICITY {Maximum} [W] FANS:ELECTRICITY {TIMESTAMP} PUMPS:ELECTRICITY {Maximum} [W] PUMPS:ELECTRICITY {TIMESTAMP} HEATING:ELECTRICITY {Maximum} [W] HEATING:ELECTRICITY {TIMESTAMP}
January 385834.94 02-JAN-08:09 57580.60 01-JAN-06:10 423497.50 02-JAN-08:09 118535.44 02-JAN-08:20 123026.69 09-JAN-06:10 27151.97 25-JAN-06:10 0.00 01-JAN-00:10
February 370465.36 02-FEB-08:09 57580.60 01-FEB-06:10 541788.89 01-FEB-08:09 118523.41 02-FEB-08:20 163172.95 28-FEB-16:10 27546.67 01-FEB-06:10 0.00 01-FEB-00:10
March 385834.94 17-MAR-07:10 57580.60 01-MAR-06:10 660080.29 01-MAR-08:09 118535.44 17-MAR-07:19 177333.85 28-MAR-15:50 27160.21 04-MAR-06:10 0.00 01-MAR-00:10
April 358592.75 14-APR-07:10 57580.60 01-APR-05:10 778371.69 03-APR-07:10 118514.13 14-APR-07:19 233859.44 25-APR-15:39 25165.60 15-APR-05:10 0.00 01-APR-00:10
May 352283.84 03-MAY-07:10 57580.60 01-MAY-05:10 423497.50 01-MAY-07:10 118509.21 03-MAY-07:19 277619.55 19-MAY-15:30 45765.04 19-MAY-15:30 0.00 01-MAY-00:10
June 334771.98 16-JUN-07:10 57580.60 01-JUN-20:10 541788.89 01-JUN-07:10 118495.57 16-JUN-07:19 306567.18 29-JUN-14:30 46969.56 30-JUN-15:50 0.00 01-JUN-00:10
July 340801.53 07-JUL-07:30 57580.60 01-JUL-20:30 660080.29 03-JUL-07:10 118500.26 07-JUL-07:40 358305.73 17-JUL-15:20 48279.39 31-JUL-15:20 0.00 01-JUL-00:10
August 343374.53 17-AUG-07:10 57580.60 01-AUG-19:00 778371.69 01-AUG-07:10 118502.27 17-AUG-07:19 352785.87 10-AUG-15:39 48286.92 07-AUG-13:20 0.00 01-AUG-00:10
September 358968.96 11-SEP-07:10 57580.60 01-SEP-05:10 423497.50 01-SEP-07:10 118514.43 11-SEP-07:19 294719.39 01-SEP-15:00 47421.57 07-SEP-14:00 0.00 01-SEP-00:10
October 385834.94 25-OCT-07:10 57580.60 01-OCT-05:10 541788.89 02-OCT-07:10 118535.44 25-OCT-07:19 208982.75 18-OCT-15:00 44290.64 18-OCT-13:20 0.00 01-OCT-00:10
November 385834.94 01-NOV-07:10 57580.60 01-NOV-05:10 660080.29 01-NOV-07:10 118535.44 01-NOV-07:19 167349.98 03-NOV-15:30 26989.52 13-NOV-06:10 0.00 01-NOV-00:10
December 385834.94 01-DEC-08:09 57580.60 01-DEC-06:10 778371.69 01-DEC-08:09 118535.44 01-DEC-08:20 123406.52 07-DEC-14:09 26521.81 11-DEC-06:10 0.00 01-DEC-00:10
                             
Annual Sum or Average                            
Minimum of Months 334771.98   57580.60   423497.50   118495.57   123026.69   25165.60   0.00  
Maximum of Months 385834.94   57580.60   778371.69   118535.44   358305.73   48286.92   0.00  



Table of Contents

Report: PeakEnergyEndUseElectricityPart2Monthly

For: Meter

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

COOLING:ELECTRICITY {Maximum} [W] COOLING:ELECTRICITY {TIMESTAMP} HEATREJECTION:ELECTRICITY {Maximum} [W] HEATREJECTION:ELECTRICITY {TIMESTAMP} HUMIDIFIER:ELECTRICITY {Maximum} [W] HUMIDIFIER:ELECTRICITY {TIMESTAMP} HEATRECOVERY:ELECTRICITY [] WATERSYSTEMS:ELECTRICITY [] COGENERATION:ELECTRICITY []
January 8408.90 13-JAN-16:30 1716.10 13-JAN-15:00 97412.76 03-JAN-14:00 0.00 0.00 0.00
February 85887.58 27-FEB-15:30 49248.27 27-FEB-13:30 100000.00 01-FEB-17:19 0.00 0.00 0.00
March 41147.75 14-MAR-13:30 11190.33 14-MAR-13:00 100000.00 01-MAR-04:10 0.00 0.00 0.00
April 269885.17 07-APR-13:00 50766.61 06-APR-15:00 100000.00 01-APR-04:19 0.00 0.00 0.00
May 265413.90 19-MAY-15:30 66400.75 19-MAY-11:00 100000.00 02-MAY-21:10 0.00 0.00 0.00
June 339503.47 29-JUN-14:00 83553.24 06-JUN-14:39 100000.00 04-JUN-16:49 0.00 0.00 0.00
July 448448.23 17-JUL-15:30 83553.24 13-JUL-12:00 100000.00 08-JUL-04:30 0.00 0.00 0.00
August 446956.08 07-AUG-15:39 83553.24 05-AUG-12:50 100000.00 02-AUG-21:10 0.00 0.00 0.00
September 378086.63 07-SEP-14:50 83553.24 02-SEP-12:00 100000.00 02-SEP-19:10 0.00 0.00 0.00
October 266052.41 18-OCT-14:20 51333.11 18-OCT-14:09 100000.00 07-OCT-16:10 0.00 0.00 0.00
November 76731.40 17-NOV-16:00 49295.04 17-NOV-16:00 100000.00 01-NOV-04:30 0.00 0.00 0.00
December 41179.75 10-DEC-01:00 22855.07 10-DEC-01:00 100000.00 01-DEC-03:20 0.00 0.00 0.00
                   
Annual Sum or Average             0.00 0.00 0.00
Minimum of Months 8408.90   1716.10   97412.76   0.00 0.00 0.00
Maximum of Months 448448.23   83553.24   100000.00   0.00 0.00 0.00



Table of Contents

Report: ElectricComponentsOfPeakDemandMonthly

For: Meter

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

ELECTRICITY:FACILITY {Maximum} [W] ELECTRICITY:FACILITY {TIMESTAMP} INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] EXTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] FANS:ELECTRICITY {AT MAX/MIN} [W] PUMPS:ELECTRICITY {AT MAX/MIN} [W] HEATING:ELECTRICITY {AT MAX/MIN} [W] COOLING:ELECTRICITY {AT MAX/MIN} [W] HEATREJECTION:ELECTRICITY {AT MAX/MIN} [W]
January 1160969.06 03-JAN-08:09 385834.94 423497.50 57580.60 118337.19 87538.78 5301.22 0.00 2754.41 307.80
February 1334684.76 27-FEB-16:10 332294.83 541788.89 0.00 84450.25 134400.59 23760.06 0.00 68741.88 49248.27
March 1396861.56 16-MAR-15:50 332294.83 660080.29 0.00 84450.25 172719.07 23692.90 0.00 20733.40 2890.83
April 1836569.20 06-APR-15:00 332294.83 778371.69 0.00 84450.25 215312.90 24007.27 0.00 251365.65 50766.61
May 1499348.78 31-MAY-15:00 332294.83 423497.50 0.00 84450.25 241647.48 44167.09 0.00 223494.49 49797.15
June 1737970.09 23-JUN-15:50 332294.83 541788.89 0.00 84450.25 275635.58 45812.26 0.00 305548.44 52439.85
July 2012126.07 17-JUL-15:30 332294.83 660080.29 0.00 84450.25 355805.40 47493.83 0.00 448448.23 83553.24
August 2225335.88 07-AUG-15:39 332294.83 778371.69 0.00 84450.25 351775.03 47934.78 0.00 446956.08 83553.24
September 1568367.43 07-SEP-15:09 332294.83 423497.50 0.00 84450.25 258451.53 45452.26 0.00 340667.83 83553.24
October 1613674.06 18-OCT-15:00 334652.47 541788.89 0.00 84452.08 208982.75 44127.98 0.00 248336.76 51333.11
November 1545281.00 17-NOV-16:00 385834.94 660080.29 57580.60 84492.05 107537.83 23728.85 0.00 76731.40 49295.04
December 1562595.15 06-DEC-16:30 385834.94 778371.69 57580.60 84478.18 102727.81 23695.32 0.00 25361.68 4544.93
                       
Annual Sum or Average                      
Minimum of Months 1160969.06   332294.83 423497.50 0.00 84450.25 87538.78 5301.22 0.00 2754.41 307.80
Maximum of Months 2225335.88   385834.94 778371.69 57580.60 118337.19 355805.40 47934.78 0.00 448448.23 83553.24



Table of Contents

Report: PeakEnergyEndUseNaturalGasMonthly

For: Meter

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

INTERIOREQUIPMENT:NATURALGAS [] EXTERIOREQUIPMENT:NATURALGAS [] HEATING:NATURALGAS {Maximum} [W] HEATING:NATURALGAS {TIMESTAMP} COOLING:NATURALGAS [] WATERSYSTEMS:NATURALGAS {Maximum} [W] WATERSYSTEMS:NATURALGAS {TIMESTAMP} COGENERATION:NATURALGAS []
January 0.00 0.00 2431734.33 09-JAN-07:10 0.00 87810.35 31-JAN-12:20 0.00
February 0.00 0.00 1615427.92 01-FEB-07:10 0.00 87976.46 17-FEB-12:39 0.00
March 0.00 0.00 1707693.71 06-MAR-07:10 0.00 87918.14 01-MAR-12:20 0.00
April 0.00 0.00 661818.27 29-APR-04:10 0.00 87064.45 03-APR-11:00 0.00
May 0.00 0.00 775275.55 08-MAY-04:10 0.00 85654.71 01-MAY-11:30 0.00
June 0.00 0.00 214825.50 16-JUN-06:00 0.00 83510.85 01-JUN-11:39 0.00
July 0.00 0.00 7796.79 08-JUL-05:10 0.00 81333.28 03-JUL-11:39 0.00
August 0.00 0.00 191371.80 18-AUG-05:10 0.00 79980.28 02-AUG-11:50 0.00
September 0.00 0.00 383886.53 13-SEP-05:10 0.00 80853.17 28-SEP-11:00 0.00
October 0.00 0.00 788195.09 10-OCT-06:30 0.00 82955.71 31-OCT-11:50 0.00
November 0.00 0.00 1498613.25 27-NOV-07:19 0.00 85055.17 30-NOV-12:20 0.00
December 0.00 0.00 1748193.03 29-DEC-07:00 0.00 86717.44 29-DEC-12:50 0.00
                 
Annual Sum or Average 0.00 0.00     0.00     0.00
Minimum of Months 0.00 0.00 7796.79   0.00 79980.28   0.00
Maximum of Months 0.00 0.00 2431734.33   0.00 87976.46   0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: BASEMENT

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 3.83 27.02 0.83 27.08
February 0.00 0.00 0.00 0.00 0.67 25.83 0.00 25.83
March 0.00 0.00 0.00 0.00 2.33 26.09 0.00 26.09
April 0.00 0.00 0.00 0.00 1.17 25.78 0.00 25.78
May 0.00 0.00 0.00 0.00 2.17 26.50 0.50 26.67
June 0.00 0.00 0.00 0.00 3.50 26.68 0.00 26.68
July 0.00 0.00 0.00 0.00 5.50 26.19 0.00 26.19
August 0.00 0.00 0.00 0.00 5.67 26.08 0.17 26.11
September 0.00 0.00 0.00 0.00 4.67 26.70 0.33 26.75
October 0.00 0.00 0.00 0.00 9.50 26.70 0.83 26.76
November 0.00 0.00 0.00 0.00 5.17 26.44 0.17 26.47
December 0.00 0.00 0.00 0.00 1.50 25.99 0.00 25.99
                 
Annual Sum or Average 0.00   0.00   45.67 26.46 2.83 26.51
Minimum of Months 0.00 0.00 0.00 0.00 0.67 25.78 0.00 25.78
Maximum of Months 0.00 0.00 0.00 0.00 9.50 27.02 0.83 27.08



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: CORE_BOTTOM

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.33 25.87 0.00 25.87
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.67 25.59 0.00 25.59
August 0.00 0.00 0.00 0.00 0.67 25.62 0.00 25.62
September 0.00 0.00 0.00 0.00 0.17 25.66 0.00 25.66
October 0.00 0.00 0.00 0.00 0.17 25.67 0.00 25.67
November 0.00 0.00 0.00 0.00 0.17 25.56 0.00 25.56
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   2.17 25.65 0.00 25.65
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.67 25.87 0.00 25.87



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: CORE_MID

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.33 18.39 0.00 18.39 0.00 18.39 0.00 18.39
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.33 18.39 0.00 18.39 0.00 18.39 0.00 18.39
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.33 18.39 0.00 18.39 0.00 18.39 0.00 18.39



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: CORE_TOP

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 7.17 18.76 1.50 18.92 0.00 18.92 0.00 18.92
February 2.17 18.85 0.33 19.00 0.00 19.00 0.00 19.00
March 1.67 18.79 0.50 19.06 0.00 19.06 0.00 19.06
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.33 19.33 0.00 19.33 0.00 19.33 0.00 19.33
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.33 18.61 0.00 18.61 0.00 18.61 0.00 18.61
November 2.00 18.71 0.17 18.82 0.00 18.82 0.00 18.82
December 3.50 18.55 0.17 18.63 0.00 18.63 0.00 18.63
                 
Annual Sum or Average 17.17 18.73 2.67 18.88 0.00 18.88 0.00 18.88
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 7.17 19.33 1.50 19.33 0.00 19.33 0.00 19.33



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 6.50 18.37 1.00 18.61 0.00 18.61 0.00 18.61
February 1.33 19.13 0.00 19.13 0.00 19.13 0.00 19.13
March 0.50 18.92 0.00 18.92 0.00 18.92 0.00 18.92
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 2.83 27.43 1.67 27.42
August 0.00 0.00 0.00 0.00 2.00 27.53 1.33 27.55
September 0.00 0.00 0.00 0.00 2.33 27.42 2.17 27.43
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.33 19.17 0.00 19.17 0.00 19.17 0.00 19.17
December 1.00 18.92 0.00 18.92 0.00 18.92 0.00 18.92
                 
Annual Sum or Average 9.67 18.59 1.00 18.74 7.17 22.24 5.17 23.41
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 6.50 19.17 1.00 19.17 2.83 27.53 2.17 27.55



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 7.33 17.27 0.50 17.35 0.00 17.35 0.00 17.35
February 1.33 18.98 0.00 18.98 0.00 18.98 0.00 18.98
March 0.50 18.73 0.00 18.73 0.00 18.73 0.00 18.73
April 0.00 0.00 0.00 0.00 1.33 28.11 1.33 28.11
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 5.33 28.43 5.33 28.43
July 0.00 0.00 0.00 0.00 9.50 28.33 9.50 28.33
August 0.00 0.00 0.00 0.00 4.00 28.32 3.67 28.36
September 0.00 0.00 0.00 0.00 6.33 28.04 6.33 28.04
October 0.00 0.00 0.00 0.00 0.83 27.64 0.83 27.64
November 0.33 18.97 0.00 18.97 0.00 18.97 0.00 18.97
December 1.17 18.77 0.00 18.77 0.00 18.77 0.00 18.77
                 
Annual Sum or Average 10.67 17.77 0.50 17.81 27.33 25.22 27.00 26.47
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 7.33 18.98 0.50 18.98 9.50 28.43 9.50 28.43



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 8.17 17.18 0.67 17.22 1.50 18.77 1.50 19.93
February 1.33 18.98 0.00 18.98 3.17 25.51 3.17 26.64
March 0.67 18.15 0.00 18.15 1.67 25.17 1.67 26.34
April 0.00 0.00 0.00 0.00 3.17 27.96 3.17 27.96
May 0.00 0.00 0.00 0.00 1.50 27.78 1.50 27.78
June 0.00 0.00 0.00 0.00 4.00 27.79 4.00 27.79
July 0.00 0.00 0.00 0.00 9.00 28.00 8.17 28.02
August 0.00 0.00 0.00 0.00 5.33 28.23 4.67 28.26
September 0.00 0.00 0.00 0.00 8.33 28.36 7.50 28.40
October 0.00 0.00 0.00 0.00 4.50 28.37 4.50 28.37
November 0.50 18.89 0.00 18.89 2.83 26.70 2.83 27.34
December 1.33 18.82 0.00 18.82 0.83 22.12 0.83 23.59
                 
Annual Sum or Average 12.00 17.69 0.67 17.69 45.83 25.85 43.50 26.82
Minimum of Months 0.00 0.00 0.00 0.00 0.83 18.77 0.83 19.93
Maximum of Months 8.17 18.98 0.67 18.98 9.00 28.37 8.17 28.40



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 3.50 18.20 0.00 18.20 0.00 18.20 0.00 18.20
February 0.33 19.38 0.00 19.38 1.17 26.11 1.17 26.95
March 0.00 0.00 0.00 0.00 1.00 27.86 0.67 27.92
April 0.00 0.00 0.00 0.00 5.00 28.35 3.00 28.39
May 0.00 0.00 0.00 0.00 5.00 28.45 2.33 28.42
June 0.00 0.00 0.00 0.00 8.50 28.40 3.67 28.44
July 0.00 0.00 0.00 0.00 19.50 28.31 8.17 28.43
August 0.00 0.00 0.00 0.00 17.33 27.71 5.33 27.93
September 0.00 0.00 0.00 0.00 6.17 28.34 3.67 28.44
October 0.00 0.00 0.00 0.00 1.83 28.25 1.67 28.25
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 3.83 18.30 0.00 18.30 65.50 27.62 29.67 27.90
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 3.50 19.38 0.00 19.38 19.50 28.45 8.17 28.44



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 65.50 16.89 26.33 17.27 0.00 17.27 0.00 17.27
February 22.00 16.89 5.00 16.88 0.00 16.88 0.00 16.88
March 13.50 17.09 3.00 17.30 0.00 17.30 0.00 17.30
April 0.50 19.10 0.00 19.10 0.00 19.10 0.00 19.10
May 1.00 18.42 0.00 18.42 0.00 18.42 0.00 18.42
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 1.50 27.37 1.00 27.34
August 0.00 0.00 0.00 0.00 1.50 27.40 1.00 27.41
September 0.00 0.00 0.00 0.00 1.67 27.38 1.67 27.38
October 0.83 19.21 0.17 19.39 0.00 19.39 0.00 19.39
November 11.33 17.12 3.00 17.23 0.00 17.23 0.00 17.23
December 32.50 16.63 8.67 16.73 0.00 16.73 0.00 16.73
                 
Annual Sum or Average 147.17 16.90 46.17 17.13 4.67 17.37 3.67 17.55
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 65.50 19.21 26.33 19.39 1.67 27.40 1.67 27.41



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 34.00 15.32 5.67 15.22 0.00 15.22 0.00 15.22
February 14.17 16.09 1.00 15.99 0.00 15.99 0.00 15.99
March 9.67 16.41 0.83 16.37 0.00 16.37 0.00 16.37
April 0.50 19.02 0.00 19.02 0.83 24.59 0.83 25.87
May 1.00 18.40 0.00 18.40 0.00 18.40 0.00 18.40
June 0.00 0.00 0.00 0.00 5.50 28.50 5.50 28.50
July 0.00 0.00 0.00 0.00 11.00 28.43 10.67 28.45
August 0.00 0.00 0.00 0.00 4.00 28.57 3.67 28.60
September 0.00 0.00 0.00 0.00 6.00 28.10 6.00 28.10
October 0.67 18.97 0.00 18.97 0.00 18.97 0.00 18.97
November 7.50 16.59 0.50 16.49 0.00 16.49 0.00 16.49
December 24.33 15.77 4.17 15.61 0.00 15.61 0.00 15.61
                 
Annual Sum or Average 91.83 15.85 12.17 15.73 27.33 18.36 26.67 20.05
Minimum of Months 0.00 0.00 0.00 0.00 0.00 15.22 0.00 15.22
Maximum of Months 34.00 19.02 5.67 19.02 11.00 28.57 10.67 28.60



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 26.83 15.76 3.33 15.70 0.67 15.97 0.67 16.22
February 10.67 16.75 0.67 16.62 2.33 18.67 2.33 20.12
March 7.67 16.60 0.67 16.57 0.83 17.63 0.83 18.52
April 0.50 19.10 0.00 19.10 2.33 26.40 2.33 27.11
May 0.83 18.77 0.00 18.77 1.17 23.97 1.17 25.34
June 0.00 0.00 0.00 0.00 3.33 27.78 3.33 27.78
July 0.00 0.00 0.00 0.00 8.33 28.05 7.50 28.07
August 0.00 0.00 0.00 0.00 5.00 28.26 4.33 28.30
September 0.00 0.00 0.00 0.00 8.17 28.57 7.17 28.62
October 0.33 18.77 0.00 18.77 6.00 26.80 6.00 27.02
November 5.33 17.24 0.00 17.24 2.33 20.61 2.33 22.41
December 15.33 16.34 2.50 16.12 0.00 16.12 0.00 16.12
                 
Annual Sum or Average 67.50 16.34 7.17 16.22 40.50 20.39 38.00 22.30
Minimum of Months 0.00 0.00 0.00 0.00 0.00 15.97 0.00 16.12
Maximum of Months 26.83 19.10 3.33 19.10 8.33 28.57 7.50 28.62



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 30.17 15.45 5.17 15.34 0.00 15.34 0.00 15.34
February 12.67 16.45 1.17 16.31 0.00 16.31 0.00 16.31
March 7.83 16.59 0.50 16.61 0.00 16.61 0.00 16.61
April 0.50 19.27 0.00 19.27 1.33 26.15 0.67 26.92
May 0.67 18.74 0.00 18.74 3.83 27.06 1.33 27.37
June 0.00 0.00 0.00 0.00 5.33 28.56 2.00 28.61
July 0.00 0.00 0.00 0.00 11.33 28.75 5.00 28.80
August 0.00 0.00 0.00 0.00 4.83 28.54 2.50 28.56
September 0.00 0.00 0.00 0.00 4.67 28.56 2.67 28.65
October 0.50 18.98 0.00 18.98 0.50 23.69 0.50 25.27
November 6.17 16.82 0.00 16.82 0.00 16.82 0.00 16.82
December 14.17 16.33 3.00 16.00 0.00 16.00 0.00 16.00
                 
Annual Sum or Average 72.67 16.12 9.83 15.95 31.83 19.48 14.67 20.53
Minimum of Months 0.00 0.00 0.00 0.00 0.00 15.34 0.00 15.34
Maximum of Months 30.17 19.27 5.17 19.27 11.33 28.75 5.00 28.80



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 123.17 16.16 50.17 16.58 0.00 16.58 0.00 16.58
February 48.17 16.71 16.00 17.00 0.00 17.00 0.00 17.00
March 29.33 16.53 8.17 16.67 0.00 16.67 0.00 16.67
April 5.00 18.21 0.67 17.99 0.00 17.99 0.00 17.99
May 7.50 17.49 1.00 17.61 0.00 17.61 0.00 17.61
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 3.00 27.53 1.67 27.51
August 0.00 0.00 0.00 0.00 1.83 27.67 1.17 27.69
September 1.17 19.11 0.00 19.11 2.33 24.74 2.17 25.82
October 5.50 17.82 0.33 17.95 0.00 17.95 0.00 17.95
November 34.50 16.21 10.33 16.33 0.00 16.33 0.00 16.33
December 78.00 15.97 28.67 16.16 0.00 16.16 0.00 16.16
                 
Annual Sum or Average 332.33 16.33 115.33 16.58 7.17 16.76 5.00 16.88
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 123.17 19.11 50.17 19.11 3.00 27.67 2.17 27.69



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 60.67 14.81 12.33 14.78 0.00 14.78 0.00 14.78
February 27.83 15.45 3.83 15.35 0.00 15.35 0.00 15.35
March 20.50 15.91 3.50 15.76 0.00 15.76 0.00 15.76
April 3.67 18.56 0.00 18.56 0.00 18.56 0.00 18.56
May 4.67 16.82 0.00 16.82 0.00 16.82 0.00 16.82
June 0.00 0.00 0.00 0.00 5.83 28.26 5.83 28.26
July 0.00 0.00 0.00 0.00 12.17 28.37 11.00 28.40
August 0.17 19.40 0.00 19.40 4.00 28.28 3.33 28.51
September 1.00 19.11 0.00 19.11 5.67 26.84 5.33 27.47
October 4.33 17.41 0.00 17.41 0.00 17.41 0.00 17.41
November 21.83 15.42 3.50 15.27 0.00 15.27 0.00 15.27
December 54.00 14.93 13.67 14.85 0.00 14.85 0.00 14.85
                 
Annual Sum or Average 198.67 15.31 36.83 15.20 27.67 16.58 25.50 17.63
Minimum of Months 0.00 0.00 0.00 0.00 0.00 14.78 0.00 14.78
Maximum of Months 60.67 19.40 13.67 19.40 12.17 28.37 11.00 28.51



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 51.83 15.24 9.83 15.25 0.00 15.25 0.00 15.25
February 21.33 15.94 1.83 15.87 1.33 16.57 1.33 17.20
March 17.00 16.26 1.50 16.20 0.33 16.40 0.33 16.60
April 3.50 18.65 0.00 18.65 1.00 20.72 1.00 22.04
May 4.50 16.80 0.00 16.80 1.00 18.74 1.00 20.09
June 0.00 0.00 0.00 0.00 3.33 27.78 3.33 27.78
July 0.00 0.00 0.00 0.00 8.67 28.14 7.33 28.17
August 0.17 19.43 0.00 19.43 5.00 28.08 4.17 28.25
September 0.67 19.06 0.00 19.06 8.00 27.85 6.67 28.23
October 3.33 17.77 0.00 17.77 2.67 22.57 2.67 24.42
November 15.67 16.05 2.00 15.98 0.50 16.29 0.50 16.59
December 40.00 15.19 7.50 15.07 0.00 15.07 0.00 15.07
                 
Annual Sum or Average 158.00 15.71 22.67 15.62 31.83 17.52 28.33 18.79
Minimum of Months 0.00 0.00 0.00 0.00 0.00 15.07 0.00 15.07
Maximum of Months 51.83 19.43 9.83 19.43 8.67 28.14 7.33 28.25



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 54.33 14.80 11.83 14.77 0.00 14.77 0.00 14.77
February 21.67 15.72 2.83 15.61 0.00 15.61 0.00 15.61
March 16.00 16.16 1.83 16.04 0.00 16.04 0.00 16.04
April 2.33 18.66 0.00 18.66 1.17 21.99 0.50 22.84
May 3.33 16.72 0.00 16.72 3.67 22.90 1.50 23.86
June 0.00 0.00 0.00 0.00 5.00 28.71 1.83 28.73
July 0.00 0.00 0.00 0.00 10.83 28.92 4.83 28.95
August 0.00 0.00 0.00 0.00 4.67 28.72 2.33 28.74
September 0.67 19.14 0.00 19.14 5.00 27.48 2.83 27.95
October 2.67 18.57 0.00 18.57 0.50 20.05 0.50 21.12
November 17.00 15.73 3.33 15.53 0.00 15.53 0.00 15.53
December 42.33 15.16 10.00 15.03 0.00 15.03 0.00 15.03
                 
Annual Sum or Average 160.33 15.43 29.83 15.30 30.83 17.17 14.33 17.88
Minimum of Months 0.00 0.00 0.00 0.00 0.00 14.77 0.00 14.77
Maximum of Months 54.33 19.14 11.83 19.14 10.83 28.92 4.83 28.95



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: GROUNDFLOOR_PLENUM

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: MIDFLOOR_PLENUM

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: TOPFLOOR_PLENUM

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 9.00 28.06 4.67 28.05
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   9.00 28.06 4.67 28.05
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 9.00 28.06 4.67 28.05



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: DATACENTER_MID_ZN_6

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 5.00 27.86 2.67 27.86
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   5.00 27.86 2.67 27.86
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 5.00 27.86 2.67 27.86



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 6.50 27.93 2.83 27.92
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   6.50 27.93 2.83 27.92
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 6.50 27.93 2.83 27.92



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 112.50 30.84 105.50 30.84
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   112.50 30.84 105.50 30.84
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 112.50 30.84 105.50 30.84



Table of Contents

Report: ComfortReportSimple55Monthly

For: BASEMENT

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 387.17 23.34 35.67 23.60 0.00 23.60
February 287.67 23.79 41.50 24.10 0.00 24.10
March 246.17 23.97 46.17 24.31 0.00 24.31
April 77.50 24.01 84.33 25.16 0.00 25.16
May 74.83 24.00 111.83 25.19 0.00 25.19
June 8.50 24.45 227.83 24.97 8.50 24.95
July 10.67 25.11 349.17 24.89 10.67 24.90
August 0.00 0.00 229.50 25.09 0.00 25.09
September 23.50 24.00 219.17 25.09 16.50 25.02
October 13.33 24.00 112.67 26.24 0.00 26.24
November 104.67 24.00 93.67 25.17 0.00 25.17
December 230.67 23.82 52.33 24.28 0.00 24.28
             
Annual Sum or Average 1464.67 23.76 1603.83 24.66 35.67 24.66
Minimum of Months 0.00 0.00 35.67 23.60 0.00 23.60
Maximum of Months 387.17 25.11 349.17 26.24 16.50 26.24



Table of Contents

Report: ComfortReportSimple55Monthly

For: CORE_BOTTOM

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 427.83 23.50 10.00 23.54 1.83 23.53
February 309.83 23.81 2.50 23.82 0.00 23.82
March 233.67 23.97 20.83 24.12 0.00 24.12
April 70.17 23.99 59.67 24.91 0.00 24.91
May 86.17 23.97 91.33 24.71 0.00 24.71
June 6.00 24.45 239.50 24.48 5.00 24.49
July 3.33 24.97 370.33 24.42 3.33 24.42
August 0.00 0.00 286.67 24.44 0.00 24.44
September 35.00 24.05 206.33 24.57 14.00 24.55
October 43.00 23.98 79.67 25.26 0.00 25.26
November 146.17 23.97 47.67 24.46 0.00 24.46
December 262.83 23.92 14.17 24.01 0.00 24.01
             
Annual Sum or Average 1624.00 23.81 1428.67 24.26 24.17 24.26
Minimum of Months 0.00 0.00 2.50 23.54 0.00 23.53
Maximum of Months 427.83 24.97 370.33 25.26 14.00 25.26



Table of Contents

Report: ComfortReportSimple55Monthly

For: CORE_MID

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 502.00 22.07 119.83 21.78 119.83 21.58
February 449.50 22.77 32.00 22.61 32.00 22.47
March 496.33 23.34 17.33 23.26 17.33 23.18
April 328.33 23.59 0.00 23.59 0.00 23.59
May 229.83 23.69 52.33 23.98 0.00 23.98
June 73.50 23.79 156.00 24.19 6.00 24.20
July 31.50 24.20 278.67 24.36 7.83 24.39
August 16.83 23.74 162.33 24.50 0.00 24.50
September 135.00 23.72 138.33 24.13 14.50 24.13
October 297.33 23.67 4.17 23.69 0.00 23.69
November 435.33 23.31 11.50 23.25 11.50 23.19
December 497.00 22.57 70.50 22.30 70.50 22.08
             
Annual Sum or Average 3492.50 23.08 1043.00 23.19 279.50 23.06
Minimum of Months 16.83 22.07 0.00 21.78 0.00 21.58
Maximum of Months 502.00 24.20 278.67 24.50 119.83 24.50



Table of Contents

Report: ComfortReportSimple55Monthly

For: CORE_TOP

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 502.00 20.75 305.67 20.48 305.67 20.35
February 454.00 21.45 184.67 21.09 184.67 20.90
March 514.00 22.17 115.33 21.81 115.33 21.56
April 431.50 22.73 40.33 22.55 40.33 22.40
May 315.00 23.07 55.67 23.07 22.33 22.92
June 127.00 23.43 154.50 23.90 5.50 23.91
July 55.67 23.69 275.17 24.20 9.67 24.22
August 74.33 23.53 161.67 24.16 0.00 24.16
September 232.17 23.14 118.67 23.57 16.67 23.60
October 441.17 22.69 25.50 22.55 25.50 22.43
November 484.00 21.90 123.17 21.55 123.17 21.31
December 497.00 21.07 250.83 20.69 250.83 20.51
             
Annual Sum or Average 4127.83 22.08 1811.17 22.01 1099.67 21.73
Minimum of Months 55.67 20.75 25.50 20.48 0.00 20.35
Maximum of Months 514.00 23.69 305.67 24.20 305.67 24.22



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 502.00 20.85 319.83 20.65 319.83 20.56
February 454.00 21.61 159.50 21.33 159.50 21.17
March 511.50 22.49 58.33 22.29 58.33 22.12
April 393.00 23.23 4.50 23.24 0.83 23.24
May 280.67 23.24 59.17 23.53 0.50 23.53
June 61.00 23.71 241.00 24.22 4.00 24.23
July 13.83 25.25 376.50 24.49 7.50 24.53
August 36.83 23.83 237.50 24.34 1.67 24.36
September 220.33 23.31 134.67 23.82 13.17 23.85
October 422.33 23.14 3.83 23.15 0.00 23.15
November 480.17 22.39 57.17 22.20 57.17 22.05
December 497.00 21.49 202.17 21.20 202.17 21.04
             
Annual Sum or Average 3872.67 22.32 1854.17 22.46 824.67 22.23
Minimum of Months 13.83 20.85 3.83 20.65 0.00 20.56
Maximum of Months 511.50 25.25 376.50 24.49 319.83 24.53



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 498.33 20.87 312.00 20.68 312.00 20.59
February 425.67 21.49 170.67 21.30 163.33 21.15
March 445.67 21.94 86.50 21.86 67.83 21.71
April 323.33 22.50 67.00 22.83 7.83 22.85
May 230.33 22.63 128.83 23.26 1.00 23.26
June 109.33 23.86 292.50 24.27 24.17 24.41
July 63.50 25.40 395.83 24.60 37.67 24.77
August 101.00 23.65 312.17 24.14 14.00 24.23
September 215.83 23.13 193.17 23.83 28.67 23.98
October 354.17 22.55 36.33 22.75 1.00 22.76
November 466.67 21.95 81.33 21.78 78.67 21.64
December 495.33 21.17 231.33 20.95 231.33 20.84
             
Annual Sum or Average 3729.17 22.02 2307.67 22.39 967.50 22.22
Minimum of Months 63.50 20.87 36.33 20.68 1.00 20.59
Maximum of Months 498.33 25.40 395.83 24.60 312.00 24.77



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 433.17 21.13 284.83 21.01 262.67 20.86
February 336.33 21.80 179.17 21.87 131.00 21.68
March 378.33 22.11 140.67 22.24 70.50 22.07
April 303.83 22.65 90.00 23.00 19.17 23.02
May 254.33 22.62 139.67 23.18 17.33 23.12
June 136.50 23.60 248.50 24.12 19.00 24.22
July 67.50 24.97 377.00 24.55 31.33 24.70
August 83.00 24.06 320.00 24.32 17.83 24.43
September 183.67 23.40 247.83 24.12 32.83 24.29
October 271.50 22.88 143.67 23.43 17.00 23.52
November 340.67 22.22 142.50 22.46 66.00 22.31
December 406.83 21.48 210.00 21.41 166.33 21.19
             
Annual Sum or Average 3195.67 22.28 2523.83 22.78 851.00 22.62
Minimum of Months 67.50 21.13 90.00 21.01 17.00 20.86
Maximum of Months 433.17 24.97 377.00 24.55 262.67 24.70



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 494.17 21.13 237.67 20.92 237.67 20.81
February 394.00 21.99 105.00 21.91 86.17 21.75
March 358.33 22.78 67.17 22.88 22.17 22.79
April 130.83 23.56 149.17 24.28 10.00 24.38
May 181.33 22.96 193.17 23.87 8.83 23.94
June 54.50 24.55 376.83 24.50 24.17 24.60
July 59.00 26.10 475.83 24.77 58.83 24.90
August 36.33 25.77 469.00 24.59 34.00 24.67
September 174.00 23.29 234.33 24.08 24.67 24.19
October 248.17 23.08 94.83 23.54 4.33 23.59
November 340.33 22.69 53.17 22.93 7.17 22.90
December 433.33 22.31 63.00 22.16 56.00 22.00
             
Annual Sum or Average 2904.33 22.55 2519.17 23.21 574.00 23.12
Minimum of Months 36.33 21.13 53.17 20.92 4.33 20.81
Maximum of Months 494.17 26.10 475.83 24.77 237.67 24.90



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_MID_ZN_3

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 502.00 19.87 491.33 19.86 491.33 19.86
February 454.00 20.36 385.00 20.28 385.00 20.24
March 514.00 20.91 283.67 20.67 283.67 20.55
April 476.17 21.90 110.33 21.61 110.33 21.42
May 387.50 22.50 72.67 22.43 41.17 22.23
June 145.67 23.20 168.33 23.76 4.50 23.77
July 52.67 23.71 285.67 24.31 5.17 24.33
August 129.67 23.24 157.33 23.88 0.67 23.89
September 307.17 22.51 105.33 22.90 27.17 22.85
October 497.00 21.85 89.00 21.63 89.00 21.46
November 489.00 20.72 295.00 20.48 295.00 20.37
December 497.00 20.01 453.67 19.96 453.67 19.94
             
Annual Sum or Average 4451.83 21.25 2897.33 21.21 2186.67 20.96
Minimum of Months 52.67 19.87 72.67 19.86 0.67 19.86
Maximum of Months 514.00 23.71 491.33 24.31 491.33 24.33



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_MID_ZN_2

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 427.00 19.91 401.17 19.87 401.17 19.86
February 378.67 20.55 278.17 20.39 277.17 20.32
March 416.33 21.01 207.33 20.77 203.67 20.64
April 327.00 21.69 105.17 21.69 75.33 21.52
May 265.83 22.02 106.33 22.30 35.83 22.09
June 139.00 23.42 216.83 24.13 26.00 24.30
July 87.67 24.85 312.00 24.70 41.67 24.91
August 118.17 23.27 236.17 24.10 14.00 24.22
September 242.67 22.54 139.00 23.30 32.33 23.41
October 386.83 21.75 68.50 21.63 59.33 21.49
November 414.67 20.77 233.00 20.56 233.00 20.46
December 422.00 19.96 374.50 19.89 374.50 19.86
             
Annual Sum or Average 3625.83 21.26 2678.17 21.47 1774.00 21.24
Minimum of Months 87.67 19.91 68.50 19.87 14.00 19.86
Maximum of Months 427.00 24.85 401.17 24.70 401.17 24.91



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_MID_ZN_1

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 448.50 20.63 349.67 20.50 335.67 20.38
February 355.83 21.28 247.83 21.29 201.83 21.10
March 398.67 21.40 235.17 21.45 170.33 21.25
April 342.33 21.87 147.33 22.06 82.33 21.90
May 302.83 22.17 145.83 22.52 46.50 22.34
June 183.00 23.00 216.50 23.76 16.33 23.86
July 100.33 24.07 327.33 24.40 28.50 24.56
August 132.67 23.37 293.33 24.11 15.50 24.22
September 223.17 22.93 236.50 23.77 43.50 23.93
October 314.00 22.28 164.83 22.78 47.50 22.75
November 374.50 21.57 217.33 21.63 155.33 21.42
December 435.17 20.72 310.00 20.57 283.17 20.41
             
Annual Sum or Average 3611.00 21.74 2891.67 22.13 1426.50 21.89
Minimum of Months 100.33 20.63 145.83 20.50 15.50 20.38
Maximum of Months 448.50 24.07 349.67 24.40 335.67 24.56



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_MID_ZN_4

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 502.00 20.14 455.67 20.07 455.67 20.05
February 435.50 20.66 302.83 20.51 298.67 20.42
March 476.00 21.01 225.83 20.85 213.00 20.73
April 400.67 21.77 108.50 21.85 69.17 21.73
May 315.00 22.18 144.50 22.60 40.17 22.50
June 182.50 22.95 244.83 23.78 16.00 23.87
July 97.50 23.99 345.50 24.39 32.83 24.52
August 144.17 23.03 278.50 23.97 14.00 24.05
September 290.83 22.30 168.33 23.08 29.83 23.14
October 430.83 21.68 89.83 21.71 60.50 21.60
November 469.83 20.95 225.50 20.71 224.67 20.59
December 495.83 20.25 387.67 20.11 387.67 20.06
             
Annual Sum or Average 4240.67 21.31 2977.50 21.57 1842.17 21.34
Minimum of Months 97.50 20.14 89.83 20.07 14.00 20.05
Maximum of Months 502.00 23.99 455.67 24.39 455.67 24.52



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 502.00 19.62 495.33 19.61 495.33 19.61
February 454.00 20.00 427.83 19.96 427.83 19.95
March 514.00 20.44 363.17 20.26 363.17 20.18
April 477.67 21.26 200.00 20.89 200.00 20.69
May 403.83 22.04 125.67 21.84 96.00 21.58
June 183.83 22.79 168.17 23.47 5.50 23.47
July 94.50 23.37 276.50 24.13 8.17 24.18
August 169.17 22.92 154.67 23.60 4.33 23.62
September 346.67 22.14 138.50 22.39 67.33 22.26
October 500.50 21.11 208.67 20.78 208.67 20.60
November 489.00 20.17 380.83 20.02 380.83 19.96
December 497.00 19.79 478.83 19.76 478.83 19.75
             
Annual Sum or Average 4632.17 20.88 3418.17 20.84 2736.00 20.61
Minimum of Months 94.50 19.62 125.67 19.61 4.33 19.61
Maximum of Months 514.00 23.37 495.33 24.13 495.33 24.18



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 502.00 19.82 479.83 19.80 479.83 19.79
February 452.83 20.33 352.33 20.17 352.33 20.11
March 495.33 20.77 286.50 20.49 285.50 20.36
April 384.50 21.31 166.17 21.17 131.33 20.93
May 308.17 21.78 159.83 21.98 70.50 21.70
June 151.00 23.12 274.83 23.96 28.67 24.10
July 104.50 24.51 375.33 24.52 44.83 24.70
August 130.67 22.97 309.67 23.95 14.33 24.03
September 283.17 22.33 189.83 23.02 58.67 23.06
October 465.67 21.36 143.50 21.06 139.67 20.85
November 487.83 20.35 339.00 20.17 339.00 20.09
December 497.00 19.87 464.33 19.83 464.33 19.81
             
Annual Sum or Average 4262.67 20.99 3541.17 21.22 2409.00 20.98
Minimum of Months 104.50 19.82 143.50 19.80 14.33 19.79
Maximum of Months 502.00 24.51 479.83 24.52 479.83 24.70



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 469.00 20.33 383.67 20.15 379.33 20.06
February 374.83 20.86 274.83 20.74 246.50 20.58
March 410.67 20.86 290.50 20.86 235.50 20.65
April 360.50 21.31 200.50 21.35 142.33 21.10
May 322.83 21.75 182.83 22.01 86.67 21.74
June 203.67 22.62 212.67 23.48 21.50 23.56
July 137.67 23.59 310.33 24.20 29.83 24.36
August 158.33 22.98 287.17 23.89 18.50 23.98
September 244.50 22.48 237.50 23.29 64.67 23.33
October 345.33 21.62 216.33 21.85 118.00 21.63
November 406.50 20.98 270.83 20.91 225.00 20.69
December 457.00 20.34 346.67 20.12 339.83 20.01
             
Annual Sum or Average 3890.83 21.31 3213.83 21.60 1907.67 21.34
Minimum of Months 137.67 20.33 182.83 20.12 18.50 20.01
Maximum of Months 469.00 23.59 383.67 24.20 379.33 24.36



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 502.00 19.89 468.50 19.84 468.50 19.82
February 439.00 20.36 344.83 20.22 342.00 20.16
March 481.33 20.68 296.50 20.51 285.17 20.40
April 409.67 21.30 177.67 21.26 139.83 21.07
May 344.67 21.90 175.17 22.19 76.67 22.00
June 211.50 22.64 238.50 23.56 19.33 23.64
July 145.50 23.54 323.00 24.19 38.83 24.33
August 175.83 22.73 263.83 23.74 17.33 23.81
September 308.00 21.99 174.83 22.65 55.00 22.64
October 441.17 21.18 171.83 21.04 149.50 20.87
November 478.33 20.54 308.50 20.32 307.83 20.22
December 496.33 20.00 430.50 19.90 430.50 19.87
             
Annual Sum or Average 4433.33 21.03 3373.67 21.23 2330.50 21.00
Minimum of Months 145.50 19.89 171.83 19.84 17.33 19.82
Maximum of Months 502.00 23.54 468.50 24.19 468.50 24.33



Table of Contents

Report: ComfortReportSimple55Monthly

For: GROUNDFLOOR_PLENUM

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00
             
Annual Sum or Average 0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: ComfortReportSimple55Monthly

For: MIDFLOOR_PLENUM

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00
             
Annual Sum or Average 0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: ComfortReportSimple55Monthly

For: TOPFLOOR_PLENUM

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00
             
Annual Sum or Average 0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: ComfortReportSimple55Monthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 1.33 26.22 388.50 27.00 0.00 27.00
February 4.50 27.00 436.50 27.00 4.50 27.00
March 9.67 27.00 509.33 27.00 9.67 27.00
April 35.83 27.00 485.00 27.00 35.83 27.00
May 5.83 27.00 508.00 27.00 5.83 27.00
June 52.00 27.00 496.00 27.00 52.00 27.00
July 168.50 27.00 497.00 27.00 168.50 27.00
August 238.50 27.04 514.00 27.03 238.50 27.03
September 21.00 27.00 485.00 27.00 21.00 27.00
October 13.00 27.00 502.00 27.00 13.00 27.00
November 10.67 27.00 489.00 27.00 10.67 27.00
December 4.00 27.00 491.50 27.00 4.00 27.00
             
Annual Sum or Average 564.83 27.02 5801.83 27.00 563.50 27.00
Minimum of Months 1.33 26.22 388.50 27.00 0.00 27.00
Maximum of Months 238.50 27.04 514.00 27.03 238.50 27.03



Table of Contents

Report: ComfortReportSimple55Monthly

For: DATACENTER_MID_ZN_6

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 116.17 25.52 195.17 26.44 0.00 26.44
February 14.17 27.00 302.17 27.00 0.83 27.00
March 10.17 27.00 457.67 27.00 2.83 27.00
April 6.67 27.00 478.83 27.00 6.67 27.00
May 2.33 27.00 496.00 27.00 2.33 27.00
June 11.33 27.00 496.00 27.00 11.33 27.00
July 41.50 27.00 497.00 27.00 41.50 27.00
August 58.33 27.06 514.00 27.01 58.33 27.02
September 9.00 27.00 485.00 27.00 9.00 27.00
October 4.50 27.00 502.00 27.00 4.50 27.00
November 0.00 0.00 442.17 27.00 0.00 27.00
December 17.33 27.00 335.17 27.00 0.00 27.00
             
Annual Sum or Average 291.50 26.42 5201.17 26.97 137.33 26.97
Minimum of Months 0.00 0.00 195.17 26.44 0.00 26.44
Maximum of Months 116.17 27.06 514.00 27.01 58.33 27.02



Table of Contents

Report: ComfortReportSimple55Monthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 259.67 24.64 129.33 25.06 27.00 24.84
February 46.83 26.94 198.67 26.99 0.33 26.99
March 24.17 27.00 360.83 27.00 2.17 27.00
April 7.00 27.00 423.00 27.00 7.00 27.00
May 26.00 25.93 474.67 26.94 5.00 26.95
June 26.00 27.00 496.00 27.00 26.00 27.00
July 71.00 27.00 497.00 27.00 71.00 27.00
August 81.83 27.05 514.00 27.01 81.83 27.02
September 14.33 27.00 473.83 27.00 14.33 27.00
October 4.67 27.00 454.50 27.00 4.67 27.00
November 22.33 27.00 327.50 27.00 0.00 27.00
December 65.17 27.00 212.50 27.00 0.00 27.00
             
Annual Sum or Average 649.00 26.01 4561.83 26.85 239.33 26.83
Minimum of Months 4.67 24.64 129.33 25.06 0.00 24.84
Maximum of Months 259.67 27.05 514.00 27.01 81.83 27.02



Table of Contents

Report: ComfortReportSimple55Monthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 274.33 27.00 502.00 27.00 274.33 27.00
February 454.00 27.00 454.00 27.00 454.00 27.00
March 514.00 27.00 514.00 27.00 514.00 27.00
April 485.00 27.00 485.00 27.00 485.00 27.00
May 498.00 27.00 508.00 27.00 498.00 27.00
June 496.00 27.00 496.00 27.00 496.00 27.00
July 497.00 27.01 497.00 27.01 497.00 27.01
August 514.00 27.80 514.00 27.80 514.00 27.80
September 485.00 27.00 485.00 27.00 485.00 27.00
October 502.00 27.00 502.00 27.00 502.00 27.00
November 489.00 27.00 489.00 27.00 489.00 27.00
December 497.00 27.00 497.00 27.00 497.00 27.00
             
Annual Sum or Average 5705.33 27.07 5943.00 27.07 5705.33 27.07
Minimum of Months 274.33 27.00 454.00 27.00 274.33 27.00
Maximum of Months 514.00 27.80 514.00 27.80 514.00 27.80



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 26.99366 13.68642 0.61380 13.15168
February 454.00000 27.00000 14.93626 0.71183 15.86397
March 514.00000 26.99999 16.92967 0.79742 18.56317
April 485.00000 27.00001 20.00657 0.89497 22.01601
May 508.00000 27.00015 22.25770 0.16002 5.75064
June 496.00000 27.00044 25.63948 0.27856 6.74613
July 497.00000 27.00027 26.73265 0.35160 7.68742
August 514.00000 27.01980 26.18299 0.38997 8.34443
September 485.00000 27.00051 25.36576 0.19561 6.00081
October 502.00000 27.00006 22.40331 0.84585 20.18718
November 489.00000 27.00000 18.52049 0.81262 19.05892
December 497.00000 26.99999 14.86636 0.76942 17.66073
           
Annual Sum or Average 5943.00000 27.00129 20.66615 0.56691 13.38419
Minimum of Months 454.00000 26.99366 13.68642 0.16002 5.75064
Maximum of Months 514.00000 27.01980 26.73265 0.89497 22.01601



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: DATACENTER_MID_ZN_6

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 26.61949 14.28132 0.42316 9.72827
February 454.00000 27.00000 14.92795 0.57280 12.14888
March 514.00000 26.99999 16.91356 0.64822 14.08629
April 485.00000 27.00002 19.97985 0.74449 16.88147
May 508.00000 27.00014 22.27366 0.05804 5.45303
June 496.00000 27.00044 25.65531 0.17707 5.89284
July 497.00000 27.00029 26.73952 0.23990 6.40134
August 514.00000 27.00722 26.19603 0.24683 6.52232
September 485.00000 27.00043 25.46104 0.10105 5.53576
October 502.00000 27.00006 22.38861 0.73306 16.46798
November 489.00000 27.00000 18.49635 0.65384 14.21358
December 497.00000 26.99999 14.84141 0.56951 12.08890
           
Annual Sum or Average 5943.00000 26.96860 20.71904 0.42906 10.42645
Minimum of Months 454.00000 26.61949 14.28132 0.05804 5.45303
Maximum of Months 514.00000 27.00722 26.73952 0.74449 16.88147



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 25.74121 14.55867 0.19346 8.93895
February 454.00000 26.99403 14.93016 0.50562 10.75326
March 514.00000 26.99999 16.92045 0.58495 12.59478
April 485.00000 27.00002 19.99430 0.69033 15.42222
May 508.00000 26.94268 22.32890 -0.0017 6.15526
June 496.00000 27.00044 25.66708 0.16477 5.99295
July 497.00000 27.00029 26.74730 0.23773 6.53085
August 514.00000 27.00734 26.20321 0.23610 6.58317
September 485.00000 27.00013 25.53509 0.06281 5.66664
October 502.00000 27.00006 22.40905 0.67119 14.77282
November 489.00000 27.00000 18.50758 0.57697 12.34259
December 497.00000 27.00000 14.85231 0.49505 10.53076
           
Annual Sum or Average 5943.00000 26.88903 20.76099 0.36650 9.67279
Minimum of Months 454.00000 25.74121 14.55867 -0.0017 5.66664
Maximum of Months 514.00000 27.00734 26.74730 0.69033 15.42222



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 27.00044 30.00052 1.00083 26.19844
February 454.00000 27.00056 27.27741 1.16755 33.70395
March 514.00000 27.00025 22.26342 1.28766 39.64855
April 485.00000 27.00092 21.67948 1.42918 47.08530
May 508.00000 27.00053 29.12657 0.48120 9.89094
June 496.00000 27.00230 29.65981 0.72930 16.23169
July 497.00000 27.00687 30.17705 0.95216 24.17595
August 514.00000 27.80467 27.22763 1.33811 41.77133
September 485.00000 27.00064 31.09587 0.54616 11.34216
October 502.00000 27.00052 27.22089 1.22927 36.70064
November 489.00000 27.00028 22.62407 1.31641 41.12600
December 497.00000 27.00030 19.57038 1.40014 45.52933
           
Annual Sum or Average 5943.00000 27.07073 26.49146 1.07290 31.11118
Minimum of Months 454.00000 27.00025 19.57038 0.48120 9.89094
Maximum of Months 514.00000 27.80467 31.09587 1.42918 47.08530



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: BASEMENT

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 23.77324 12.27318 0.10996 6.75156
February 454.00000 24.20556 13.93910 0.22482 6.66284
March 514.00000 24.29978 14.94001 0.26598 6.78829
April 485.00000 24.46793 18.55649 0.33344 7.69292
May 508.00000 24.48387 22.27994 -0.4891 11.03118
June 496.00000 24.46063 31.01580 -0.4137 9.44693
July 497.00000 24.62577 35.45832 -0.3239 8.56093
August 514.00000 24.48908 30.62183 -0.3895 9.15033
September 485.00000 24.55174 30.19335 -0.3905 9.36885
October 502.00000 24.58344 20.75692 0.38774 8.72556
November 489.00000 24.55968 16.18378 0.34131 7.95228
December 497.00000 24.32434 13.30506 0.25928 6.96828
           
Annual Sum or Average 5943.00000 24.40258 21.67646 -0.0098 8.27159
Minimum of Months 454.00000 23.77324 12.27318 -0.4891 6.66284
Maximum of Months 514.00000 24.62577 35.45832 0.38774 11.03118



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: CORE_BOTTOM

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 23.66768 13.83982 0.06871 5.99840
February 454.00000 24.00084 15.34314 0.18010 6.02654
March 514.00000 24.19782 16.23991 0.25546 6.57039
April 485.00000 24.33213 19.64186 0.32931 7.52468
May 508.00000 24.32815 23.59173 -0.5196 11.28840
June 496.00000 24.24691 32.34513 -0.4413 9.43807
July 497.00000 24.31666 36.36704 -0.3761 8.43903
August 514.00000 24.25453 31.72794 -0.4182 8.97372
September 485.00000 24.30465 31.44746 -0.4508 9.84049
October 502.00000 24.36740 22.33253 0.34921 7.82842
November 489.00000 24.35119 17.68554 0.30045 7.14096
December 497.00000 24.19645 14.71725 0.23035 6.41446
           
Annual Sum or Average 5943.00000 24.21458 22.98889 -0.0436 7.97220
Minimum of Months 454.00000 23.66768 13.83982 -0.5196 5.99840
Maximum of Months 514.00000 24.36740 36.36704 0.34921 11.28840



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: CORE_MID

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 22.07471 15.20168 -0.3381 9.15737
February 454.00000 22.78068 17.32296 -0.1414 6.87486
March 514.00000 23.36802 18.09266 0.02132 6.04026
April 485.00000 23.79467 21.27668 0.16417 5.97431
May 508.00000 24.05046 24.53600 -0.6531 14.82213
June 496.00000 24.11534 32.92105 -0.5259 11.16139
July 497.00000 24.22468 36.90355 -0.4526 9.73168
August 514.00000 24.19819 32.14652 -0.4939 10.41013
September 485.00000 24.10450 32.18516 -0.5547 12.10324
October 502.00000 23.90234 23.98447 0.20727 6.15759
November 489.00000 23.40510 19.62266 0.03660 6.01004
December 497.00000 22.56913 16.81260 -0.1961 7.80427
           
Annual Sum or Average 5943.00000 23.55435 24.29304 -0.2456 8.87639
Minimum of Months 454.00000 22.07471 15.20168 -0.6531 5.97431
Maximum of Months 514.00000 24.22468 36.90355 0.20727 14.82213



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: CORE_TOP

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 20.75344 15.73703 -0.6869 17.95798
February 454.00000 21.44787 18.24518 -0.4853 12.63143
March 514.00000 22.16741 19.49370 -0.2859 9.58156
April 485.00000 22.88290 22.91534 -0.0669 7.01091
May 508.00000 23.52119 25.43831 -0.8457 22.67904
June 496.00000 23.96099 33.09811 -0.5770 12.86522
July 497.00000 24.14194 36.90921 -0.4717 10.19975
August 514.00000 24.10898 32.27599 -0.5254 11.32186
September 485.00000 23.71875 33.19162 -0.6994 17.35114
October 502.00000 22.84930 26.15360 -0.0608 6.74433
November 489.00000 21.92427 21.35827 -0.3395 10.36043
December 497.00000 21.06987 17.88001 -0.5845 15.86759
           
Annual Sum or Average 5943.00000 22.72227 25.26462 -0.4696 12.89231
Minimum of Months 454.00000 20.75344 15.73703 -0.8457 6.74433
Maximum of Months 514.00000 24.14194 36.90921 -0.0608 22.67904



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 20.84658 14.33971 -0.6618 16.53983
February 454.00000 21.61181 16.50782 -0.4286 10.92482
March 514.00000 22.50146 17.29336 -0.1892 7.54091
April 485.00000 23.39024 20.31777 0.06512 5.96234
May 508.00000 23.72694 23.92402 -0.7467 19.00358
June 496.00000 24.16353 31.81119 -0.4640 10.32046
July 497.00000 24.37482 35.45029 -0.3349 8.25228
August 514.00000 24.21157 31.22546 -0.4427 9.83485
September 485.00000 23.86219 31.80432 -0.6389 15.94272
October 502.00000 23.28867 23.34984 0.05019 5.86742
November 489.00000 22.42525 18.96714 -0.1997 7.53558
December 497.00000 21.48804 15.97694 -0.4570 11.39913
           
Annual Sum or Average 5943.00000 23.00080 23.45593 -0.3711 10.76692
Minimum of Months 454.00000 20.84658 14.33971 -0.7467 5.86742
Maximum of Months 514.00000 24.37482 35.45029 0.06512 19.00358



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 20.90037 13.40405 -0.6383 16.10586
February 454.00000 21.68130 15.49602 -0.3865 10.96282
March 514.00000 22.23934 16.55407 -0.2056 8.47293
April 485.00000 23.06895 20.06404 0.05611 7.42029
May 508.00000 23.49934 23.55495 -0.7188 19.62178
June 496.00000 24.09957 31.64410 -0.3605 10.78778
July 497.00000 24.33835 35.31686 -0.2069 8.53587
August 514.00000 24.02837 31.23849 -0.3755 10.35106
September 485.00000 23.73362 31.56750 -0.5771 16.39396
October 502.00000 23.03374 22.93449 0.04240 6.78962
November 489.00000 22.05543 18.42357 -0.2581 8.24324
December 497.00000 21.17689 15.33895 -0.5207 12.51387
           
Annual Sum or Average 5943.00000 22.82960 23.00694 -0.3462 11.35914
Minimum of Months 454.00000 20.90037 13.40405 -0.7188 6.78962
Maximum of Months 514.00000 24.33835 35.31686 0.05611 19.62178



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 21.59666 13.05950 -0.4481 14.79545
February 454.00000 22.46994 14.80137 -0.1597 11.00130
March 514.00000 22.65566 16.11682 -0.0818 9.03306
April 485.00000 23.22906 19.91468 0.09140 7.85712
May 508.00000 23.45009 23.71752 -0.7667 21.89243
June 496.00000 24.00564 31.89997 -0.4578 11.93896
July 497.00000 24.31213 35.41020 -0.2746 8.67744
August 514.00000 24.15955 30.98564 -0.3319 9.62075
September 485.00000 23.93813 31.11842 -0.4626 14.95272
October 502.00000 23.48901 22.17555 0.19602 8.69327
November 489.00000 22.87266 17.53918 -0.0286 9.05418
December 497.00000 22.01057 14.63755 -0.2944 11.73790
           
Annual Sum or Average 5943.00000 23.18694 22.66377 -0.2532 11.61934
Minimum of Months 454.00000 21.59666 13.05950 -0.7667 7.85712
Maximum of Months 514.00000 24.31213 35.41020 0.19602 21.89243



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 21.17971 13.02462 -0.5368 13.31125
February 454.00000 22.29664 14.70733 -0.1959 8.69434
March 514.00000 23.21231 15.43492 0.06390 7.03120
April 485.00000 24.15857 18.62131 0.36462 9.04135
May 508.00000 23.86853 23.00549 -0.5505 15.40753
June 496.00000 24.30887 31.21471 -0.2400 8.34796
July 497.00000 24.57905 34.77908 -0.0594 7.47018
August 514.00000 24.44547 30.35747 -0.1321 7.27496
September 485.00000 23.95638 31.00367 -0.4609 13.56581
October 502.00000 23.71431 21.80352 0.23714 7.53469
November 489.00000 23.22280 16.96397 0.06007 6.95093
December 497.00000 22.55936 13.93183 -0.1408 7.60956
           
Annual Sum or Average 5943.00000 23.46584 22.11682 -0.1329 9.35403
Minimum of Months 454.00000 21.17971 13.02462 -0.5505 6.95093
Maximum of Months 514.00000 24.57905 34.77908 0.36462 15.40753



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 19.87437 14.43245 -0.9891 27.93966
February 454.00000 20.36153 17.39970 -0.7958 20.23160
March 514.00000 20.90937 18.80336 -0.6019 14.78498
April 485.00000 21.93365 22.60563 -0.2970 9.00712
May 508.00000 22.91032 25.36512 -1.0430 31.15512
June 496.00000 23.86642 32.55758 -0.5950 13.92550
July 497.00000 24.21079 35.72444 -0.4292 9.90135
August 514.00000 23.96098 31.80717 -0.5738 13.27586
September 485.00000 23.17872 33.18732 -0.8893 25.82514
October 502.00000 21.87531 25.63358 -0.2973 8.63652
November 489.00000 20.71718 20.60721 -0.6457 16.29772
December 497.00000 20.01317 17.05672 -0.8966 24.49220
           
Annual Sum or Average 5943.00000 21.99757 24.63894 -0.6708 17.94722
Minimum of Months 454.00000 19.87437 14.43245 -1.0430 8.63652
Maximum of Months 514.00000 24.21079 35.72444 -0.2970 31.15512



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 427.00000 19.90659 13.25445 -0.9626 26.82436
February 385.00000 20.61550 15.91575 -0.7061 18.28350
March 433.00000 21.13535 17.14510 -0.5164 13.73953
April 410.00000 22.20392 21.00221 -0.1774 9.32500
May 430.00000 22.86859 24.33387 -0.9624 29.49608
June 418.00000 23.94713 31.70455 -0.4377 13.84503
July 422.00000 24.37342 34.88527 -0.2262 9.96901
August 433.00000 23.99163 30.84292 -0.4286 12.66123
September 410.00000 23.26871 32.21296 -0.7626 24.13284
October 427.00000 21.98296 24.12711 -0.2317 8.44162
November 417.00000 20.79273 19.09167 -0.6086 15.04137
December 422.00000 19.95795 15.74577 -0.8953 24.41386
           
Annual Sum or Average 5034.00000 22.09562 23.38699 -0.5761 17.18302
Minimum of Months 385.00000 19.90659 13.25445 -0.9626 8.44162
Maximum of Months 433.00000 24.37342 34.88527 -0.1774 29.49608



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 21.03350 13.00512 -0.6254 19.27081
February 454.00000 21.95323 15.15038 -0.3072 14.05273
March 514.00000 22.02398 16.79053 -0.2492 11.75607
April 485.00000 22.56726 20.95007 -0.0767 9.33806
May 508.00000 23.00783 24.45817 -0.9248 28.45904
June 496.00000 23.73780 32.45246 -0.5616 15.43218
July 497.00000 24.18105 35.58587 -0.3382 10.37405
August 514.00000 24.01101 31.16050 -0.4032 12.01030
September 485.00000 23.65346 31.62779 -0.5558 19.21207
October 502.00000 22.99972 23.00822 0.08041 9.62421
November 489.00000 22.21360 18.20414 -0.2049 11.72763
December 497.00000 21.15916 15.32030 -0.5400 17.26547
           
Annual Sum or Average 5943.00000 22.71730 23.19156 -0.3938 14.89672
Minimum of Months 454.00000 21.03350 13.00512 -0.9248 9.33806
Maximum of Months 514.00000 24.18105 35.58587 0.08041 28.45904



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 20.13810 13.46681 -0.8950 24.30917
February 454.00000 20.80581 16.01718 -0.6401 16.88144
March 514.00000 21.23666 17.45568 -0.4735 12.85044
April 485.00000 22.19274 21.32151 -0.1639 8.86156
May 508.00000 22.96072 24.46062 -0.9008 28.24505
June 496.00000 23.71320 32.49550 -0.5092 14.85682
July 497.00000 24.16321 35.66990 -0.2970 10.30513
August 514.00000 23.89946 31.44336 -0.4453 12.83028
September 485.00000 23.10856 32.58375 -0.7900 25.10541
October 502.00000 22.03362 24.31508 -0.2003 8.44077
November 489.00000 21.07259 19.24678 -0.5197 13.60324
December 497.00000 20.25876 15.94744 -0.8012 21.33720
           
Annual Sum or Average 5943.00000 22.14288 23.74655 -0.5528 16.46882
Minimum of Months 454.00000 20.13810 13.46681 -0.9008 8.44077
Maximum of Months 514.00000 24.16321 35.66990 -0.1639 28.24505



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 19.62008 14.42353 -1.1076 33.13303
February 454.00000 20.00283 17.58260 -0.9321 25.75859
March 514.00000 20.44131 19.22718 -0.7568 19.85474
April 485.00000 21.30479 23.36906 -0.4706 13.16920
May 508.00000 22.48692 25.92346 -1.2022 37.66138
June 496.00000 23.64041 32.90155 -0.6690 17.18033
July 497.00000 24.07606 35.92416 -0.4661 11.36593
August 514.00000 23.76655 32.12410 -0.6364 15.96088
September 485.00000 22.76011 33.98728 -1.0420 32.71167
October 502.00000 21.12181 26.77017 -0.5026 13.21289
November 489.00000 20.16887 21.28495 -0.8268 22.42018
December 497.00000 19.78559 17.04504 -1.0183 29.41448
           
Annual Sum or Average 5943.00000 21.61179 25.08774 -0.8019 22.63272
Minimum of Months 454.00000 19.62008 14.42353 -1.2022 11.36593
Maximum of Months 514.00000 24.07606 35.92416 -0.4661 37.66138



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 19.82465 13.87099 -1.0325 29.86467
February 454.00000 20.34063 16.58417 -0.8090 21.80319
March 514.00000 20.88733 18.00478 -0.6042 16.70665
April 485.00000 21.89423 21.75020 -0.2683 11.62837
May 508.00000 22.71640 24.78572 -1.0176 31.28629
June 496.00000 23.84883 31.96504 -0.4481 14.41813
July 497.00000 24.24967 35.24712 -0.2278 9.97151
August 514.00000 23.89794 31.27113 -0.4259 13.08160
September 485.00000 23.11096 32.80984 -0.8173 26.34606
October 502.00000 21.55176 25.31213 -0.3532 11.02499
November 489.00000 20.35849 20.31273 -0.7506 19.72080
December 497.00000 19.86570 16.37408 -0.9759 27.73608
           
Annual Sum or Average 5943.00000 21.89170 24.06580 -0.6433 19.44859
Minimum of Months 454.00000 19.82465 13.87099 -1.0325 9.97151
Maximum of Months 514.00000 24.24967 35.24712 -0.2278 31.28629



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 20.58785 13.35062 -0.7806 23.68211
February 454.00000 21.45039 15.61024 -0.4707 17.29854
March 514.00000 21.52399 17.35637 -0.4080 15.29747
April 485.00000 22.07753 21.63052 -0.2220 12.17750
May 508.00000 22.66682 24.95337 -1.0603 33.72513
June 496.00000 23.53291 32.74375 -0.6295 18.51629
July 497.00000 24.02029 35.84193 -0.3817 12.15250
August 514.00000 23.83657 31.45025 -0.4589 14.43616
September 485.00000 23.35861 32.27801 -0.6729 24.02366
October 502.00000 22.41544 24.00156 -0.0886 11.49117
November 489.00000 21.53228 19.05711 -0.4085 14.93784
December 497.00000 20.63481 15.72869 -0.7172 21.88014
           
Annual Sum or Average 5943.00000 22.30993 23.71476 -0.5261 18.32180
Minimum of Months 454.00000 20.58785 13.35062 -1.0603 11.49117
Maximum of Months 514.00000 24.02029 35.84193 -0.0886 33.72513



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 19.88837 13.73758 -1.0062 29.00279
February 454.00000 20.48764 16.33830 -0.7575 20.90662
March 514.00000 20.89275 17.87651 -0.5937 16.47873
April 485.00000 21.75528 21.91164 -0.2922 11.50861
May 508.00000 22.64413 24.89970 -1.0244 33.14192
June 496.00000 23.50962 32.76350 -0.5748 17.77666
July 497.00000 23.99903 35.92640 -0.3408 12.04184
August 514.00000 23.71637 31.73375 -0.5027 15.30747
September 485.00000 22.81830 33.20655 -0.9017 30.07660
October 502.00000 21.52955 25.18175 -0.3472 11.22284
November 489.00000 20.61825 19.91928 -0.6694 18.03117
December 497.00000 20.00426 16.14299 -0.9153 25.66096
           
Annual Sum or Average 5943.00000 21.83349 24.18069 -0.6601 20.09097
Minimum of Months 454.00000 19.88837 13.73758 -1.0244 11.22284
Maximum of Months 514.00000 23.99903 35.92640 -0.2922 33.14192



Table of Contents

Report: ChillerReportMonthly

For: COOLSYS1 CHILLER1

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

CHILLER ELECTRICITY ENERGY [J] CHILLER ELECTRICITY RATE {Maximum} [W] CHILLER ELECTRICITY RATE {TIMESTAMP} CHILLER ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] CHILLER EVAPORATOR COOLING ENERGY [J] CHILLER EVAPORATOR COOLING RATE [] CHILLER CONDENSER HEAT TRANSFER ENERGY [J] CHILLER COP [W/W] CHILLER COP {Maximum} [W/W] CHILLER COP {TIMESTAMP} CHILLER PART LOAD RATIO [] CHILLER PART LOAD RATIO []
January 18273799.18 1177.11 25-JAN-04:21 4.35 78217765.57 0.00 96491564.76 0.03 4.29 25-JAN-06:40 0.00 0.00
February 0.143497E+10 66128.62 27-FEB-15:30 45.31 0.776568E+10 0.00 0.920065E+10 0.30 6.54 27-FEB-15:30 0.00 0.00
March 0.355077E+09 22028.09 14-MAR-13:30 64.14 0.151985E+10 0.00 0.187493E+10 0.37 4.29 24-MAR-13:30 0.00 0.00
April 0.117660E+11 121946.72 06-APR-16:00 133.40 0.678267E+11 0.00 0.795927E+11 0.88 7.55 06-APR-16:00 0.00 0.00
May 0.326488E+11 154532.05 19-MAY-12:00 204.39 0.204291E+12 0.00 0.236940E+12 1.48 7.57 19-MAY-17:30 0.00 0.00
June 0.829297E+11 156542.91 23-JUN-08:40 364.21 0.551774E+12 0.00 0.634703E+12 3.00 7.57 19-JUN-12:40 0.00 0.00
July 0.124915E+12 156237.04 18-JUL-09:00 494.27 0.859517E+12 0.00 0.984432E+12 4.14 7.57 28-JUL-12:50 0.00 0.00
August 0.110163E+12 157787.67 05-AUG-12:30 473.24 0.757192E+12 0.00 0.867355E+12 3.84 7.57 29-AUG-16:10 0.00 0.00
September 0.596555E+11 167706.74 07-SEP-14:50 294.63 0.393393E+12 0.00 0.453048E+12 2.36 7.57 05-SEP-11:30 0.00 0.00
October 0.181489E+11 136643.66 18-OCT-13:00 157.20 0.111463E+12 0.00 0.129612E+12 1.06 7.57 18-OCT-12:10 0.00 0.00
November 0.161016E+10 48478.96 03-NOV-14:00 73.65 0.687386E+10 0.00 0.848401E+10 0.44 4.39 03-NOV-14:00 0.00 0.00
December 0.159675E+09 1232.47 28-DEC-00:33 37.71 0.683494E+09 0.00 0.843169E+09 0.22 4.29 20-DEC-11:50 0.00 0.00
                         
Annual Sum or Average 0.443805E+12     2346.50 0.296238E+13 0.00 0.340618E+13 1.52     0.00 0.00
Minimum of Months 18273799.18 1177.11   4.35 78217765.57 0.00 96491564.76 0.03 4.29   0.00 0.00
Maximum of Months 0.124915E+12 167706.74   494.27 0.859517E+12 0.00 0.984432E+12 4.14 7.57   0.00 0.00



Table of Contents

Report: ChillerReportMonthly

For: COOLSYS1 CHILLER2

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

CHILLER ELECTRICITY ENERGY [J] CHILLER ELECTRICITY RATE {Maximum} [W] CHILLER ELECTRICITY RATE {TIMESTAMP} CHILLER ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] CHILLER EVAPORATOR COOLING ENERGY [J] CHILLER EVAPORATOR COOLING RATE [] CHILLER CONDENSER HEAT TRANSFER ENERGY [J] CHILLER COP [W/W] CHILLER COP {Maximum} [W/W] CHILLER COP {TIMESTAMP} CHILLER PART LOAD RATIO [] CHILLER PART LOAD RATIO []
January 0.00 0.00 01-JAN-00:05 0.00 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 0.00 0.00
February 0.00 0.00 01-FEB-00:05 0.00 0.00 0.00 0.00 0.00 0.00 01-FEB-00:05 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00 0.00 01-APR-00:10 0.00 0.00
May 0.190259E+10 100899.13 19-MAY-15:30 5.83 0.138177E+11 0.00 0.157203E+11 0.06 7.40 19-MAY-15:30 0.00 0.00
June 0.207054E+11 111473.88 29-JUN-14:50 61.83 0.150388E+12 0.00 0.171094E+12 0.62 7.50 29-JUN-14:50 0.00 0.00
July 0.434963E+11 132003.26 17-JUL-15:30 124.33 0.318113E+12 0.00 0.361609E+12 1.21 7.55 25-JUL-15:20 0.00 0.00
August 0.366064E+11 127008.05 07-AUG-09:20 105.75 0.268150E+12 0.00 0.304756E+12 1.03 7.56 07-AUG-09:20 0.00 0.00
September 0.105502E+11 167706.74 07-SEP-14:50 31.17 0.761166E+11 0.00 0.866667E+11 0.31 7.49 02-SEP-10:50 0.00 0.00
October 0.791911E+09 105649.51 18-OCT-13:40 2.58 0.567913E+10 0.00 0.647105E+10 0.02 7.42 18-OCT-13:40 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 0.00 0.00
                         
Annual Sum or Average 0.114053E+12     331.50 0.832264E+12 0.00 0.946317E+12 0.27     0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00 0.00   0.00 0.00
Maximum of Months 0.434963E+11 167706.74   124.33 0.318113E+12 0.00 0.361609E+12 1.21 7.56   0.00 0.00



Table of Contents

Report: TowerReportMonthly

For: CENTRAL TOWER

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

COOLING TOWER FAN ELECTRICITY ENERGY [J] COOLING TOWER FAN ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] COOLING TOWER FAN ELECTRICITY RATE {Maximum} [W] COOLING TOWER FAN ELECTRICITY RATE {TIMESTAMP} COOLING TOWER HEAT TRANSFER RATE {Maximum} [W] COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} COOLING TOWER INLET TEMPERATURE [C] COOLING TOWER OUTLET TEMPERATURE [C] COOLING TOWER MASS FLOW RATE [kg/s]
January 0.850726E+09 744.00 1716.10 13-JAN-16:00 39733.81 13-JAN-16:30 18.59 18.33 15.44
February 0.402468E+10 672.00 49248.27 27-FEB-13:30 91207.22 27-FEB-16:00 19.26 18.33 15.44
March 0.597019E+10 744.00 11190.33 14-MAR-14:00 110181.10 31-MAR-23:30 19.87 18.33 15.44
April 0.255280E+11 720.00 49248.27 01-APR-13:10 563998.36 07-APR-14:00 21.42 18.68 15.44
May 0.285594E+11 744.00 49248.27 02-MAY-11:40 246286.35 20-MAY-17:02 19.71 18.96 15.44
June 0.648461E+11 720.00 49248.27 01-JUN-14:50 505783.32 20-JUN-19:00 23.80 21.27 15.44
July 0.100665E+12 744.00 49248.27 01-JUL-00:10 666193.86 19-JUL-10:50 31.30 25.31 15.44
August 0.106294E+12 744.00 49248.27 01-AUG-00:03 757163.23 05-AUG-19:01 32.42 24.85 15.44
September 0.489625E+11 720.00 49248.27 01-SEP-00:05 333573.02 07-SEP-16:00 21.29 20.22 15.44
October 0.193157E+11 744.00 49248.27 12-OCT-10:40 320530.93 18-OCT-15:00 19.84 18.60 15.44
November 0.891022E+10 720.00 49248.27 04-NOV-13:20 182604.51 17-NOV-17:00 19.88 18.33 15.44
December 0.617722E+10 744.00 22855.07 10-DEC-02:00 186302.37 10-DEC-02:00 20.24 18.33 15.44
                   
Annual Sum or Average 0.420104E+12 8760.00         22.33 19.98 15.44
Minimum of Months 0.850726E+09 672.00 1716.10   39733.81   18.59 18.33 15.44
Maximum of Months 0.106294E+12 744.00 49248.27   757163.23   32.42 25.31 15.44



Table of Contents

Report: TowerReportMonthly

For: TOWERWATERSYS COOLTOWER 1

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

COOLING TOWER FAN ELECTRICITY ENERGY [J] COOLING TOWER FAN ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] COOLING TOWER FAN ELECTRICITY RATE {Maximum} [W] COOLING TOWER FAN ELECTRICITY RATE {TIMESTAMP} COOLING TOWER HEAT TRANSFER RATE {Maximum} [W] COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} COOLING TOWER INLET TEMPERATURE [C] COOLING TOWER OUTLET TEMPERATURE [C] COOLING TOWER MASS FLOW RATE [kg/s]
January 0.00 0.00 0.00 01-JAN-00:05 230116.96 25-JAN-06:15 21.08 21.08 0.02
February 0.00 0.00 0.00 01-FEB-00:05 510389.08 27-FEB-15:30 20.87 20.85 0.88
March 0.00 0.00 0.00 01-MAR-00:10 230187.05 21-MAR-05:20 20.94 20.94 0.36
April 36139931.55 40.45 1518.34 06-APR-16:00 1049719.40 06-APR-16:00 21.13 20.99 5.57
May 0.256328E+09 129.67 17152.48 19-MAY-12:00 1314995.02 19-MAY-12:00 21.50 21.11 12.19
June 0.268633E+10 291.68 17152.48 06-JUN-14:40 1320852.70 23-JUN-16:10 22.24 21.14 26.84
July 0.492284E+10 414.15 17152.48 01-JUL-12:30 1315456.05 06-JUL-10:30 22.84 21.17 36.13
August 0.216831E+10 356.00 17152.48 05-AUG-10:55 1328338.77 01-AUG-12:00 22.56 21.09 32.19
September 0.175174E+10 217.70 17152.48 02-SEP-09:50 1344537.59 07-SEP-15:00 21.98 21.20 20.35
October 80406408.21 65.09 1652.21 18-OCT-12:20 1169560.22 18-OCT-13:00 21.19 20.97 7.69
November 448699.96 4.17 74.22 03-NOV-14:00 272973.97 03-NOV-14:00 20.94 20.92 1.31
December 0.00 0.00 0.00 01-DEC-00:10 230253.47 29-DEC-02:30 20.90 20.90 0.23
                   
Annual Sum or Average 0.119025E+11 1518.91         21.52 21.03 12.05
Minimum of Months 0.00 0.00 0.00   230116.96   20.87 20.85 0.02
Maximum of Months 0.492284E+10 414.15 17152.48   1344537.59   22.84 21.20 36.13



Table of Contents

Report: TowerReportMonthly

For: TOWERWATERSYS COOLTOWER 2

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

COOLING TOWER FAN ELECTRICITY ENERGY [J] COOLING TOWER FAN ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] COOLING TOWER FAN ELECTRICITY RATE {Maximum} [W] COOLING TOWER FAN ELECTRICITY RATE {TIMESTAMP} COOLING TOWER HEAT TRANSFER RATE {Maximum} [W] COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} COOLING TOWER INLET TEMPERATURE [C] COOLING TOWER OUTLET TEMPERATURE [C] COOLING TOWER MASS FLOW RATE [kg/s]
January 0.00 0.00 0.00 01-JAN-00:05 0.00 01-JAN-00:05 21.08 21.08 0.00
February 0.00 0.00 0.00 01-FEB-00:05 0.00 01-FEB-00:05 20.87 20.87 0.00
March 0.00 0.00 0.00 01-MAR-00:10 0.00 01-MAR-00:10 20.94 20.94 0.00
April 0.00 0.00 0.00 01-APR-00:10 0.00 01-APR-00:10 21.13 21.13 0.00
May 20098944.20 5.17 2453.88 19-MAY-16:40 1204920.68 19-MAY-14:30 21.50 21.47 0.40
June 0.121893E+10 54.17 17152.48 06-JUN-14:40 1213592.52 30-JUN-14:10 22.24 21.93 4.38
July 0.251931E+10 113.67 17152.48 13-JUL-13:00 1213138.55 20-JUL-14:10 22.84 22.19 8.89
August 0.965898E+09 96.67 17152.48 05-AUG-12:50 1213535.35 30-AUG-14:40 22.56 22.01 7.56
September 0.744876E+09 28.83 17152.48 02-SEP-13:00 1344537.59 07-SEP-15:00 21.98 21.81 2.33
October 8132835.80 2.33 1268.03 18-OCT-13:40 1115400.26 18-OCT-13:25 21.19 21.18 0.18
November 0.00 0.00 0.00 01-NOV-00:10 0.00 01-NOV-00:10 20.94 20.94 0.00
December 0.00 0.00 0.00 01-DEC-00:10 0.00 01-DEC-00:10 20.90 20.90 0.00
                   
Annual Sum or Average 0.547724E+10 300.83         21.52 21.37 2.00
Minimum of Months 0.00 0.00 0.00   0.00   20.87 20.87 0.00
Maximum of Months 0.251931E+10 113.67 17152.48   1344537.59   22.84 22.19 8.89



Table of Contents

Report: BoilerReportMonthly

For: HEATSYS1 BOILER

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

BOILER HEATING ENERGY [J] BOILER GAS CONSUMPTION [] BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] BOILER HEATING RATE {Maximum} [W] BOILER HEATING RATE {TIMESTAMP} BOILER GAS CONSUMPTION RATE [] BOILER INLET TEMPERATURE [C] BOILER OUTLET TEMPERATURE [C] BOILER MASS FLOW RATE [kg/s] BOILER ANCILLARY ELECTRICITY RATE [W] BOILER PART LOAD RATIO [] BOILER PART LOAD RATIO {Maximum} [] BOILER PART LOAD RATIO {TIMESTAMP}
January 0.957188E+12 0.00 619.25 2138250.95 23-JAN-05:11 0.00 33.51 73.00 2.00 0.00 0.10 0.62 23-JAN-05:11
February 0.484638E+12 0.00 462.71 2081493.97 07-FEB-06:01 0.00 29.37 64.57 1.03 0.00 0.06 0.60 07-FEB-06:01
March 0.286776E+12 0.00 428.84 1927328.50 06-MAR-05:01 0.00 26.30 57.53 0.52 0.00 0.03 0.56 06-MAR-05:01
April 0.723355E+11 0.00 225.53 1629520.69 01-APR-04:11 0.00 23.29 41.31 0.12 0.00 0.01 0.47 01-APR-04:11
May 0.505494E+11 0.00 152.60 1654154.34 09-MAY-04:01 0.00 23.69 35.31 0.09 0.00 0.01 0.48 09-MAY-04:01
June 0.167885E+10 0.00 31.36 370308.82 17-JUN-05:03 0.00 22.63 25.21 0.00 0.00 0.00 0.11 17-JUN-05:03
July 24860404.87 0.00 4.12 10059.99 08-JUL-05:03 0.00 22.24 22.58 0.00 0.00 0.00 0.00 08-JUL-05:03
August 0.565002E+09 0.00 13.38 372323.64 18-AUG-05:03 0.00 22.34 23.41 0.00 0.00 0.00 0.11 18-AUG-05:03
September 0.140707E+11 0.00 102.89 1439883.70 19-SEP-04:11 0.00 22.10 30.54 0.02 0.00 0.00 0.42 19-SEP-04:11
October 0.584272E+11 0.00 232.75 1521347.06 11-OCT-04:01 0.00 22.71 40.87 0.10 0.00 0.01 0.44 11-OCT-04:01
November 0.247229E+12 0.00 426.30 1867617.05 28-NOV-06:01 0.00 26.11 58.32 0.46 0.00 0.03 0.54 28-NOV-06:01
December 0.611389E+12 0.00 578.25 2050482.29 04-DEC-06:01 0.00 30.60 69.98 1.18 0.00 0.07 0.60 04-DEC-06:01
                           
Annual Sum or Average 0.278487E+13 0.00 3277.97     0.00 25.40 45.13 0.46 0.00 0.03    
Minimum of Months 24860404.87 0.00 4.12 10059.99   0.00 22.10 22.58 0.00 0.00 0.00 0.00  
Maximum of Months 0.957188E+12 0.00 619.25 2138250.95   0.00 33.51 73.00 2.00 0.00 0.10 0.62  



Table of Contents

Report: BoilerReportMonthly

For: CENTRAL BOILER

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

BOILER HEATING ENERGY [J] BOILER GAS CONSUMPTION [] BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] BOILER HEATING RATE {Maximum} [W] BOILER HEATING RATE {TIMESTAMP} BOILER GAS CONSUMPTION RATE [] BOILER INLET TEMPERATURE [C] BOILER OUTLET TEMPERATURE [C] BOILER MASS FLOW RATE [kg/s] BOILER ANCILLARY ELECTRICITY RATE [W] BOILER PART LOAD RATIO [] BOILER PART LOAD RATIO []
January 0.00 0.00 0.00 0.00 01-JAN-00:05 0.00 18.59 18.59 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 01-FEB-00:05 0.00 19.26 19.26 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 01-MAR-00:10 0.00 19.87 19.87 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 01-APR-00:10 0.00 21.42 21.42 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 01-MAY-00:10 0.00 19.71 19.71 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 01-JUN-00:10 0.00 23.80 23.80 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 01-JUL-00:10 0.00 31.30 31.30 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 01-AUG-00:03 0.00 32.42 32.42 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 01-SEP-00:05 0.00 21.29 21.29 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 01-OCT-00:10 0.00 19.84 19.84 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 01-NOV-00:10 0.00 19.88 19.88 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 01-DEC-00:10 0.00 20.24 20.24 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.00 0.00 0.00     0.00 22.33 22.33 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00   0.00 18.59 18.59 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00   0.00 32.42 32.42 0.00 0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: VAV_BOT WITH REHEAT COOLING COIL

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 0.00 01-JAN-00:05 0.00 0.00 0.00
February 0.736348E+09 0.00 12.23 0.736348E+09 0.00 0.00 0.00 0.00 46910.45 27-FEB-15:30 46910.45 27-FEB-15:30 0.00 0.00 0.00
March 64191064.87 0.00 4.89 64191064.87 0.00 0.00 0.00 0.00 12393.11 14-MAR-13:30 12393.11 14-MAR-13:30 0.00 0.00 0.00
April 0.713072E+10 0.00 78.89 0.713072E+10 0.00 0.00 0.00 0.00 90172.76 06-APR-16:00 90172.76 06-APR-16:00 0.00 0.00 0.00
May 0.195332E+11 0.00 171.23 0.195332E+11 0.00 0.00 0.00 0.00 121968.00 19-MAY-15:20 121968.00 19-MAY-15:20 0.00 0.00 0.00
June 0.638689E+11 0.00 343.89 0.638186E+11 0.00 0.00 0.00 0.00 138857.99 29-JUN-14:40 138857.99 29-JUN-14:40 0.00 0.00 0.00
July 0.108592E+12 0.00 471.45 0.108413E+12 0.00 0.00 0.00 0.00 165129.77 17-JUL-15:20 165129.77 17-JUL-15:20 0.00 0.00 0.00
August 0.991574E+11 0.00 458.79 0.991574E+11 0.00 0.00 0.00 0.00 164372.12 07-AUG-15:20 164372.12 07-AUG-15:20 0.00 0.00 0.00
September 0.413584E+11 0.00 254.00 0.400217E+11 0.00 0.00 0.00 0.00 214303.48 07-SEP-15:00 138433.67 04-SEP-15:21 0.00 0.00 0.00
October 0.112922E+11 0.00 112.26 0.112922E+11 0.00 0.00 0.00 0.00 112935.89 18-OCT-15:50 112935.89 18-OCT-15:50 0.00 0.00 0.00
November 0.616459E+09 0.00 22.88 0.616459E+09 0.00 0.00 0.00 0.00 20234.37 03-NOV-14:00 20234.37 03-NOV-14:00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 0.00 01-DEC-00:10 0.00 0.00 0.00
                               
Annual Sum or Average 0.352350E+12 0.00 1930.51 0.350784E+12 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00   0.00   0.00 0.00 0.00
Maximum of Months 0.108592E+12 0.00 471.45 0.108413E+12 0.00 0.00 0.00 0.00 214303.48   165129.77   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: VAV_MID WITH REHEAT COOLING COIL

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 31506.06 0.00 17.05 31506.06 0.00 0.00 0.00 0.00 3.41 03-JAN-06:00 3.41 03-JAN-06:00 0.00 0.00 0.00
February 0.582135E+10 0.00 42.46 0.582135E+10 0.00 0.00 0.00 0.00 343626.02 27-FEB-14:00 343626.02 27-FEB-14:00 0.00 0.00 0.00
March 0.247060E+09 0.00 62.40 0.247060E+09 0.00 0.00 0.00 0.00 68784.96 14-MAR-13:30 68784.96 14-MAR-13:30 0.00 0.00 0.00
April 0.511108E+11 0.00 123.85 0.511108E+11 0.00 0.00 0.00 0.00 720946.46 06-APR-16:00 720946.46 06-APR-16:00 0.00 0.00 0.00
May 0.167845E+12 0.00 191.02 0.167845E+12 0.00 0.00 0.00 0.00 1165675.81 19-MAY-15:30 1165675.81 19-MAY-15:30 0.00 0.00 0.00
June 0.544162E+12 0.00 332.48 0.543727E+12 0.00 0.00 0.00 0.00 1309120.82 29-JUN-14:50 1309120.82 29-JUN-14:50 0.00 0.00 0.00
July 0.910049E+12 0.00 416.68 0.908886E+12 0.00 0.00 0.00 0.00 1524359.19 17-JUL-15:30 1524359.19 17-JUL-15:30 0.00 0.00 0.00
August 0.790119E+12 0.00 385.49 0.790119E+12 0.00 0.00 0.00 0.00 1449182.73 07-AUG-15:40 1449182.73 07-AUG-15:40 0.00 0.00 0.00
September 0.364666E+12 0.00 271.61 0.352764E+12 0.00 0.00 0.00 0.00 2000275.77 07-SEP-15:00 1334679.36 04-SEP-15:31 0.00 0.00 0.00
October 0.893588E+11 0.00 146.24 0.893588E+11 0.00 0.00 0.00 0.00 956004.05 18-OCT-15:20 956004.05 18-OCT-15:20 0.00 0.00 0.00
November 0.448429E+10 0.00 69.70 0.448429E+10 0.00 0.00 0.00 0.00 187325.68 03-NOV-13:55 187325.68 03-NOV-13:55 0.00 0.00 0.00
December 64277.76 0.00 35.16 64277.76 0.00 0.00 0.00 0.00 3.26 17-DEC-15:55 3.26 17-DEC-15:55 0.00 0.00 0.00
                               
Annual Sum or Average 0.292786E+13 0.00 2094.14 0.291436E+13 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 31506.06 0.00 17.05 31506.06 0.00 0.00 0.00 0.00 3.26   3.26   0.00 0.00 0.00
Maximum of Months 0.910049E+12 0.00 416.68 0.908886E+12 0.00 0.00 0.00 0.00 2000275.77   1524359.19   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: VAV_TOP WITH REHEAT COOLING COIL

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 52824.02 0.00 2.98 52824.02 0.00 0.00 0.00 0.00 147.30 26-JAN-00:50 147.30 26-JAN-00:50 0.00 0.00 0.00
February 0.390482E+09 0.00 12.61 0.390482E+09 0.00 0.00 0.00 0.00 27817.44 27-FEB-13:40 27817.44 27-FEB-13:40 0.00 0.00 0.00
March 2331981.52 0.00 2.12 2331981.52 0.00 0.00 0.00 0.00 644.13 14-MAR-14:00 644.13 14-MAR-14:00 0.00 0.00 0.00
April 0.479342E+10 0.00 69.87 0.479342E+10 0.00 0.00 0.00 0.00 73320.21 06-APR-16:00 73320.21 06-APR-16:00 0.00 0.00 0.00
May 0.173282E+11 0.00 157.45 0.173282E+11 0.00 0.00 0.00 0.00 137325.88 19-MAY-15:30 137325.88 19-MAY-15:30 0.00 0.00 0.00
June 0.588673E+11 0.00 323.38 0.588156E+11 0.00 0.00 0.00 0.00 152417.15 29-JUN-14:50 152417.15 29-JUN-14:50 0.00 0.00 0.00
July 0.988626E+11 0.00 414.78 0.987638E+11 0.00 0.00 0.00 0.00 180544.94 17-JUL-15:30 180544.94 17-JUL-15:30 0.00 0.00 0.00
August 0.839504E+11 0.00 379.27 0.839504E+11 0.00 0.00 0.00 0.00 170583.07 07-AUG-15:40 170583.07 07-AUG-15:40 0.00 0.00 0.00
September 0.370519E+11 0.00 240.58 0.358533E+11 0.00 0.00 0.00 0.00 202482.58 07-SEP-15:20 147158.97 04-SEP-16:21 0.00 0.00 0.00
October 0.773586E+10 0.00 96.61 0.773586E+10 0.00 0.00 0.00 0.00 98579.15 18-OCT-15:10 98579.15 18-OCT-15:10 0.00 0.00 0.00
November 0.331261E+09 0.00 18.46 0.331261E+09 0.00 0.00 0.00 0.00 11249.30 04-NOV-14:00 11249.30 04-NOV-14:00 0.00 0.00 0.00
December 126715.88 0.00 2.54 126715.88 0.00 0.00 0.00 0.00 542.99 28-DEC-00:33 542.99 28-DEC-00:33 0.00 0.00 0.00
                               
Annual Sum or Average 0.309314E+12 0.00 1720.64 0.307965E+12 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 52824.02 0.00 2.12 52824.02 0.00 0.00 0.00 0.00 147.30   147.30   0.00 0.00 0.00
Maximum of Months 0.988626E+11 0.00 414.78 0.987638E+11 0.00 0.00 0.00 0.00 202482.58   180544.94   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: CAV_BAS COOLING COIL

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 430925.51 0.00 0.68 430925.51 0.00 0.00 0.00 0.00 4458.97 24-JAN-05:11 4458.97 24-JAN-05:11 0.00 0.00 0.00
February 0.282169E+09 0.00 5.17 0.282169E+09 0.00 0.00 0.00 0.00 25368.65 27-FEB-15:00 25368.65 27-FEB-15:00 0.00 0.00 0.00
March 36227.49 0.00 0.17 36227.49 0.00 0.00 0.00 0.00 60.38 01-MAR-08:00 60.38 01-MAR-08:00 0.00 0.00 0.00
April 0.252028E+10 0.00 37.91 0.252028E+10 0.00 0.00 0.00 0.00 52517.91 07-APR-14:00 52517.91 07-APR-14:00 0.00 0.00 0.00
May 0.934050E+10 0.00 105.45 0.934050E+10 0.00 0.00 0.00 0.00 64225.30 29-MAY-14:30 64225.30 29-MAY-14:30 0.00 0.00 0.00
June 0.331920E+11 0.00 232.04 0.331666E+11 0.00 0.00 0.00 0.00 72998.31 13-JUN-04:12 71737.87 26-JUN-11:00 0.00 0.00 0.00
July 0.565008E+11 0.00 329.52 0.564569E+11 0.00 0.00 0.00 0.00 150741.40 16-JUL-17:50 127813.02 16-JUL-19:08 0.00 0.00 0.00
August 0.517700E+11 0.00 316.90 0.517700E+11 0.00 0.00 0.00 0.00 126509.60 06-AUG-19:20 126509.60 06-AUG-19:20 0.00 0.00 0.00
September 0.214620E+11 0.00 181.97 0.210835E+11 0.00 0.00 0.00 0.00 137559.32 03-SEP-13:58 137559.32 03-SEP-13:58 0.00 0.00 0.00
October 0.593250E+10 0.00 59.18 0.593250E+10 0.00 0.00 0.00 0.00 62656.09 18-OCT-14:00 62656.09 18-OCT-14:00 0.00 0.00 0.00
November 75754208.78 0.00 4.07 75754208.78 0.00 0.00 0.00 0.00 29207.11 17-NOV-06:03 29207.11 17-NOV-06:03 0.00 0.00 0.00
December 22839.71 0.00 0.17 22839.71 0.00 0.00 0.00 0.00 38.07 15-DEC-18:10 38.07 15-DEC-18:10 0.00 0.00 0.00
                               
Annual Sum or Average 0.181077E+12 0.00 1273.21 0.180629E+12 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 22839.71 0.00 0.17 22839.71 0.00 0.00 0.00 0.00 38.07   38.07   0.00 0.00 0.00
Maximum of Months 0.565008E+11 0.00 329.52 0.564569E+11 0.00 0.00 0.00 0.00 150741.40   137559.32   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: AIRLOOP DATACENTER BASEMENT COOLING COIL

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [J] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [J] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION {Maximum} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL RUNTIME FRACTION {MINIMUM} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE {Maximum} [W] COOLING COIL LATENT COOLING RATE {TIMESTAMP} COOLING COIL ELECTRICITY RATE {Maximum} [W] COOLING COIL ELECTRICITY RATE {TIMESTAMP} COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.897821E+10 0.516233E+10 744.00 0.781808E+10 0.116013E+10 0.00 0.02 03-JAN-15:00 0.02 10-JAN-22:01 5237.54 03-JAN-15:00 4757.70 03-JAN-15:00 497.04 21-JAN-15:10 2469.57 03-JAN-15:00 0.00
February 0.135760E+11 0.640890E+10 672.00 0.120041E+11 0.157180E+10 0.00 0.07 27-FEB-16:00 0.02 01-FEB-08:10 17900.29 27-FEB-16:00 17900.29 27-FEB-16:00 979.42 08-FEB-04:01 7157.10 27-FEB-16:00 0.00
March 0.150884E+11 0.747561E+10 744.00 0.143569E+11 0.731513E+09 0.00 0.03 31-MAR-23:10 0.03 06-MAR-09:05 6752.56 31-MAR-23:10 6638.04 14-MAR-14:00 1151.38 01-MAR-00:10 3185.11 31-MAR-23:10 0.00
April 0.751158E+11 0.270907E+11 720.00 0.720706E+11 0.304515E+10 0.00 0.92 07-APR-14:00 0.02 30-APR-23:40 316261.64 07-APR-14:00 316261.64 07-APR-14:00 24651.14 24-APR-10:50 118255.94 07-APR-14:00 0.00
May 0.181394E+11 0.863402E+10 729.32 0.169445E+11 0.119492E+10 0.00 0.39 19-MAY-15:00 0.00 04-MAY-18:00 139501.15 19-MAY-13:50 134055.41 19-MAY-16:00 9499.44 19-MAY-12:20 52473.10 20-MAY-16:00 0.00
June 0.136834E+12 0.498434E+11 646.12 0.123616E+12 0.132178E+11 0.00 0.76 20-JUN-18:50 0.00 17-JUN-24:00 325811.76 20-JUN-18:50 229220.91 23-JUN-15:50 112608.92 20-JUN-20:00 105547.44 20-JUN-18:50 0.00
July 0.448356E+12 0.159087E+12 689.10 0.401143E+12 0.472134E+11 0.00 0.98 19-JUL-10:50 0.01 03-JUL-04:55 415623.81 19-JUL-10:50 321714.81 17-JUL-16:00 163854.82 01-JUL-00:53 151078.86 17-JUL-16:00 0.00
August 0.569901E+12 0.197142E+12 744.00 0.519336E+12 0.505649E+11 0.00 1.00 03-AUG-15:40 0.01 31-AUG-23:53 413350.51 08-AUG-12:00 398870.92 08-AUG-14:50 141367.22 01-AUG-00:53 168042.00 05-AUG-16:00 0.00
September 0.454441E+11 0.189391E+11 640.76 0.414243E+11 0.401971E+10 0.00 0.51 07-SEP-16:00 0.00 24-SEP-10:52 216458.25 07-SEP-16:00 139217.02 01-SEP-13:10 89362.03 07-SEP-15:50 68339.19 07-SEP-16:00 0.00
October 0.247462E+11 0.105224E+11 743.33 0.231347E+11 0.161152E+10 0.00 0.53 18-OCT-14:00 0.01 01-OCT-01:10 178394.39 18-OCT-15:00 178394.39 18-OCT-15:00 1376.77 12-OCT-12:00 66601.52 18-OCT-14:00 0.00
November 0.165686E+11 0.782664E+10 720.00 0.156691E+11 0.899448E+09 0.00 0.22 17-NOV-17:00 0.03 18-NOV-13:25 68223.84 17-NOV-17:00 65122.94 17-NOV-17:00 3100.90 17-NOV-17:00 21921.20 17-NOV-17:00 0.00
December 0.166132E+11 0.835927E+10 744.00 0.162722E+11 0.341006E+09 0.00 0.23 10-DEC-02:00 0.03 10-DEC-09:25 65679.09 10-DEC-02:00 65679.09 10-DEC-02:00 8995.62 19-DEC-15:00 22554.76 10-DEC-02:00 0.00
                                       
Annual Sum or Average 0.138936E+13 0.506492E+12 8536.64 0.126379E+13 0.125571E+12 0.00                         0.00
Minimum of Months 0.897821E+10 0.516233E+10 640.76 0.781808E+10 0.341006E+09 0.00 0.02   0.00   5237.54   4757.70   497.04   2469.57   0.00
Maximum of Months 0.569901E+12 0.197142E+12 744.00 0.519336E+12 0.505649E+11 0.00 1.00   0.03   415623.81   398870.92   163854.82   168042.00   0.00



Table of Contents

Report: DXReportMonthly

For: AIRLOOP DATACENTER BOT COOLING COIL

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [J] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [J] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION {Maximum} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL RUNTIME FRACTION {MINIMUM} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE {Maximum} [W] COOLING COIL LATENT COOLING RATE {TIMESTAMP} COOLING COIL ELECTRICITY RATE {Maximum} [W] COOLING COIL ELECTRICITY RATE {TIMESTAMP} COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.291329E+10 0.838011E+09 722.48 0.291296E+10 323353.20 0.00 0.29 19-JAN-16:50 0.00 07-JAN-20:32 2401.99 13-JAN-16:20 2401.99 13-JAN-16:20 12.07 02-JAN-07:10 640.41 19-JAN-16:50 0.00
February 0.827107E+10 0.217761E+10 672.00 0.827107E+10 -0.0 0.00 0.60 26-FEB-17:23 0.26 01-FEB-07:03 5256.52 26-FEB-17:27 5256.52 26-FEB-17:27 0.00 14-FEB-05:43 1335.65 26-FEB-17:23 0.00
March 0.149973E+11 0.372217E+10 744.00 0.149973E+11 -0.0 0.00 0.79 31-MAR-24:00 0.51 06-MAR-07:03 7466.50 31-MAR-24:00 7466.50 31-MAR-24:00 0.00 20-MAR-14:40 1765.45 31-MAR-24:00 0.00
April 0.201480E+11 0.478479E+10 720.00 0.201392E+11 8777649.46 0.00 1.00 16-APR-17:31 0.29 30-APR-23:55 9157.56 22-APR-18:10 9157.56 22-APR-18:10 135.33 24-APR-10:40 2654.76 07-APR-14:00 0.00
May 0.576652E+10 0.155625E+10 744.00 0.573886E+10 27662264.89 0.00 0.47 31-MAY-24:00 0.13 08-MAY-06:10 4164.37 31-MAY-24:00 4164.37 31-MAY-24:00 153.93 30-MAY-09:30 1057.73 19-MAY-16:00 0.00
June 0.111022E+11 0.301676E+10 720.00 0.110072E+11 95066120.60 0.00 0.66 30-JUN-23:13 0.38 17-JUN-06:20 6036.03 30-JUN-23:03 6032.22 30-JUN-24:00 364.39 06-JUN-16:40 1948.33 29-JUN-15:00 0.00
July 0.168060E+11 0.496792E+10 744.00 0.167039E+11 0.102137E+09 0.00 0.89 16-JUL-18:51 0.61 08-JUL-06:10 7926.56 31-JUL-23:45 7926.56 31-JUL-23:45 394.03 03-JUL-17:00 3162.60 17-JUL-16:00 0.00
August 0.217253E+11 0.613545E+10 744.00 0.216487E+11 76622641.11 0.00 1.00 03-AUG-18:40 0.30 31-AUG-24:00 9145.19 05-AUG-20:00 9145.19 05-AUG-20:00 448.36 22-AUG-16:00 3724.95 05-AUG-16:00 0.00
September 0.587028E+10 0.163597E+10 720.00 0.577824E+10 92045756.09 0.00 0.45 04-SEP-17:41 0.16 19-SEP-06:10 3959.58 30-SEP-24:00 3959.58 30-SEP-24:00 339.75 07-SEP-14:00 1461.34 04-SEP-17:31 0.00
October 0.106273E+11 0.267702E+10 744.00 0.106145E+11 12762379.54 0.00 0.63 31-OCT-24:00 0.35 10-OCT-06:10 5588.44 31-OCT-24:00 5588.44 31-OCT-24:00 113.23 25-OCT-11:00 1576.61 18-OCT-16:00 0.00
November 0.146614E+11 0.359442E+10 720.00 0.146588E+11 2579336.06 0.00 0.73 13-NOV-16:30 0.51 27-NOV-07:10 6736.38 03-NOV-16:00 6665.18 03-NOV-16:00 86.21 17-NOV-17:05 1608.38 13-NOV-16:30 0.00
December 0.194801E+11 0.473644E+10 744.00 0.194799E+11 190647.97 0.00 0.89 10-DEC-16:03 0.71 29-DEC-07:03 8462.04 06-DEC-16:10 8438.69 06-DEC-16:10 46.39 19-DEC-17:05 1971.18 10-DEC-16:03 0.00
                                       
Annual Sum or Average 0.152369E+12 0.398428E+11 8738.48 0.151951E+12 0.418167E+09 0.00                         0.00
Minimum of Months 0.291329E+10 0.838011E+09 672.00 0.291296E+10 -0.0 0.00 0.29   0.00   2401.99   2401.99   0.00   640.41   0.00
Maximum of Months 0.217253E+11 0.613545E+10 744.00 0.216487E+11 0.102137E+09 0.00 1.00   0.71   9157.56   9157.56   448.36   3724.95   0.00



Table of Contents

Report: DXReportMonthly

For: AIRLOOP DATACENTER MID COOLING COIL

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [J] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [J] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION {Maximum} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL RUNTIME FRACTION {MINIMUM} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE {Maximum} [W] COOLING COIL LATENT COOLING RATE {TIMESTAMP} COOLING COIL ELECTRICITY RATE {Maximum} [W] COOLING COIL ELECTRICITY RATE {TIMESTAMP} COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.756959E+10 0.236715E+10 418.40 0.756360E+10 5992254.67 0.00 0.25 19-JAN-16:50 0.00 01-JAN-00:05 20207.05 13-JAN-16:30 20207.05 13-JAN-16:30 420.69 02-JAN-12:00 5365.02 19-JAN-16:50 0.00
February 0.590737E+11 0.159134E+11 672.00 0.590737E+11 -0.0 0.00 0.55 26-FEB-17:32 0.11 06-FEB-03:52 45674.11 28-FEB-17:00 45674.11 28-FEB-17:00 0.00 24-FEB-12:20 11665.07 26-FEB-17:32 0.00
March 0.124694E+12 0.314076E+11 744.00 0.124694E+12 -0.0 0.00 0.74 28-MAR-17:50 0.35 06-MAR-07:03 65460.75 28-MAR-17:50 65460.75 28-MAR-17:50 0.00 12-MAR-13:57 15775.92 28-MAR-17:50 0.00
April 0.180360E+12 0.432501E+11 720.00 0.180271E+12 88561995.62 0.00 0.98 16-APR-17:52 0.13 30-APR-23:55 85319.65 22-APR-18:12 85319.65 22-APR-18:12 1315.47 24-APR-10:40 25131.74 07-APR-14:00 0.00
May 0.465520E+11 0.127395E+11 744.00 0.462846E+11 0.267373E+09 0.00 0.46 31-MAY-24:00 0.01 08-MAY-06:10 39332.27 31-MAY-24:00 39332.27 31-MAY-24:00 1477.92 30-MAY-09:30 10039.42 19-MAY-16:00 0.00
June 0.101940E+12 0.278842E+11 720.00 0.101001E+12 0.938781E+09 0.00 0.66 30-JUN-23:13 0.33 17-JUN-06:10 58852.63 30-JUN-23:03 58800.57 30-JUN-24:00 3557.39 06-JUN-16:40 18587.28 28-JUN-19:00 0.00
July 0.158348E+12 0.469787E+11 744.00 0.157333E+12 0.101494E+10 0.00 0.89 16-JUL-18:45 0.56 08-JUL-06:10 76965.51 31-JUL-23:53 76965.51 31-JUL-23:53 3852.46 03-JUL-17:00 30161.01 17-JUL-16:00 0.00
August 0.204472E+12 0.579903E+11 744.00 0.203711E+12 0.760977E+09 0.00 1.00 04-AUG-17:40 0.26 31-AUG-24:00 87881.53 03-AUG-18:50 87881.53 03-AUG-18:50 4385.02 22-AUG-16:00 35720.71 06-AUG-16:00 0.00
September 0.493391E+11 0.139589E+11 720.00 0.484440E+11 0.895103E+09 0.00 0.45 04-SEP-17:41 0.08 19-SEP-06:10 35042.68 30-SEP-23:30 35042.68 30-SEP-23:30 3385.55 07-SEP-14:10 13880.98 04-SEP-17:41 0.00
October 0.883410E+11 0.225627E+11 744.00 0.882148E+11 0.126249E+09 0.00 0.58 15-OCT-16:52 0.22 10-OCT-06:10 48655.50 15-OCT-17:06 48655.50 15-OCT-17:06 1110.68 25-OCT-11:00 14758.53 18-OCT-16:00 0.00
November 0.120428E+12 0.300096E+11 720.00 0.120401E+12 26190994.38 0.00 0.69 13-NOV-16:30 0.35 27-NOV-07:10 62335.05 03-NOV-16:00 61634.34 03-NOV-16:00 828.30 17-NOV-17:05 14646.35 13-NOV-16:30 0.00
December 0.157995E+12 0.392116E+11 744.00 0.157992E+12 2665291.23 0.00 0.82 06-DEC-16:10 0.53 31-DEC-23:45 77285.57 06-DEC-16:10 77011.85 06-DEC-16:10 498.24 19-DEC-17:05 17623.00 06-DEC-16:10 0.00
                                       
Annual Sum or Average 0.129911E+13 0.344274E+12 8434.40 0.129498E+13 0.412683E+10 0.00                         0.00
Minimum of Months 0.756959E+10 0.236715E+10 418.40 0.756360E+10 -0.0 0.00 0.25   0.00   20207.05   20207.05   0.00   5365.02   0.00
Maximum of Months 0.204472E+12 0.579903E+11 744.00 0.203711E+12 0.101494E+10 0.00 1.00   0.56   87881.53   87881.53   4385.02   35720.71   0.00



Table of Contents

Report: DXReportMonthly

For: AIRLOOP DATACENTER TOP COOLING COIL

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [J] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [J] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION {Maximum} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL RUNTIME FRACTION {MINIMUM} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE {Maximum} [W] COOLING COIL LATENT COOLING RATE {TIMESTAMP} COOLING COIL ELECTRICITY RATE {Maximum} [W] COOLING COIL ELECTRICITY RATE {TIMESTAMP} COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.304978E+09 96738080.66 189.75 0.304774E+09 203963.72 0.00 0.24 13-JAN-16:30 0.00 01-JAN-00:05 1968.42 13-JAN-16:30 1968.42 13-JAN-16:30 15.43 02-JAN-13:40 519.97 13-JAN-16:30 0.00
February 0.440339E+10 0.120682E+10 650.82 0.440339E+10 0.00 0.00 0.51 24-FEB-17:00 0.00 03-FEB-04:01 4520.39 28-FEB-17:00 4520.39 28-FEB-17:00 0.00 20-FEB-12:15 1113.76 24-FEB-17:00 0.00
March 0.109375E+11 0.278806E+10 744.00 0.109375E+11 -0.0 0.00 0.73 28-MAR-17:50 0.18 06-MAR-04:12 6546.80 28-MAR-17:50 6546.80 28-MAR-17:50 0.00 21-MAR-22:00 1580.84 28-MAR-17:50 0.00
April 0.169319E+11 0.409909E+10 719.00 0.169231E+11 8741370.46 0.00 0.95 16-APR-17:52 0.00 30-APR-23:05 8603.18 25-APR-18:10 8603.18 25-APR-18:10 131.23 24-APR-10:40 2524.00 07-APR-14:00 0.00
May 0.400971E+10 0.110670E+10 689.11 0.398330E+10 26414460.76 0.00 0.45 31-MAY-23:30 0.00 01-MAY-00:10 3862.25 31-MAY-23:30 3862.25 31-MAY-23:30 143.42 30-MAY-09:30 1042.15 19-MAY-16:00 0.00
June 0.996639E+10 0.274438E+10 720.00 0.987272E+10 93677562.00 0.00 0.65 30-JUN-23:13 0.24 17-JUN-06:10 5885.09 30-JUN-23:03 5875.57 30-JUN-23:33 358.44 06-JUN-16:40 1895.68 29-JUN-15:00 0.00
July 0.157522E+11 0.469814E+10 744.00 0.156509E+11 0.101297E+09 0.00 0.91 16-JUL-18:51 0.51 08-JUL-06:10 7690.64 31-JUL-23:53 7690.64 31-JUL-23:53 386.33 03-JUL-17:00 3082.14 17-JUL-16:00 0.00
August 0.202910E+11 0.578615E+10 744.00 0.202151E+11 75913729.55 0.00 1.00 04-AUG-17:40 0.25 31-AUG-24:00 8907.10 05-AUG-19:55 8907.10 05-AUG-19:55 440.37 22-AUG-16:00 3632.62 06-AUG-16:00 0.00
September 0.438949E+10 0.126365E+10 718.44 0.430110E+10 88390073.75 0.00 0.47 04-SEP-17:51 0.00 12-SEP-02:45 3666.99 04-SEP-17:51 3666.99 04-SEP-17:51 341.71 07-SEP-14:00 1473.83 04-SEP-17:31 0.00
October 0.749428E+10 0.194239E+10 743.86 0.748190E+10 12379813.15 0.00 0.57 18-OCT-16:50 0.00 10-OCT-01:15 4879.54 18-OCT-17:00 4879.54 18-OCT-17:00 110.50 25-OCT-11:00 1491.70 18-OCT-16:00 0.00
November 0.102901E+11 0.260241E+10 720.00 0.102875E+11 2549055.75 0.00 0.66 03-NOV-16:00 0.18 27-NOV-04:01 6187.49 03-NOV-16:00 6117.65 03-NOV-16:00 81.21 17-NOV-17:05 1448.32 03-NOV-16:00 0.00
December 0.139265E+11 0.350670E+10 744.00 0.139262E+11 229474.89 0.00 0.81 06-DEC-16:10 0.39 31-DEC-23:45 7669.92 06-DEC-16:10 7644.58 06-DEC-16:10 46.87 19-DEC-17:05 1754.48 06-DEC-16:10 0.00
                                       
Annual Sum or Average 0.118697E+12 0.318412E+11 8126.98 0.118288E+12 0.409796E+09 0.00                         0.00
Minimum of Months 0.304978E+09 96738080.66 189.75 0.304774E+09 -0.0 0.00 0.24   0.00   1968.42   1968.42   0.00   519.97   0.00
Maximum of Months 0.202910E+11 0.578615E+10 744.00 0.202151E+11 0.101297E+09 0.00 1.00   0.51   8907.10   8907.10   440.37   3632.62   0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 120.54 0.00 120.54 0.74 1193.10 0.00 0.00 0.00
February 170.20 0.00 170.20 12.90 904.60 0.00 0.00 0.00
March 276.48 0.00 276.48 61.67 737.92 0.00 0.00 0.00
April 315.24 1.84 313.40 129.47 532.65 0.00 0.00 0.00
May 413.99 24.53 389.45 270.33 383.26 0.00 0.00 0.00
June 482.06 55.41 426.65 461.64 239.11 0.00 0.00 0.00
July 440.39 41.25 399.14 513.78 196.78 0.00 0.00 0.00
August 352.89 9.46 343.43 369.24 229.53 0.00 0.00 0.00
September 264.29 0.09 264.19 207.86 354.43 0.00 0.00 0.00
October 192.78 0.00 192.78 62.99 542.58 0.00 0.00 0.00
November 131.06 0.00 131.06 9.88 786.72 0.00 0.00 0.00
December 101.08 0.00 101.08 0.24 1062.60 0.00 0.00 0.00
                 
Annual Sum or Average 272.29 11.10 261.19 176.10 595.71 0.00 0.00 0.00
Minimum of Months 101.08 0.00 101.08 0.24 196.78 0.00 0.00 0.00
Maximum of Months 482.06 55.41 426.65 513.78 1193.10 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 120.54 0.00 120.54 0.74 1193.10 0.00 0.00 0.00
February 170.20 0.00 170.20 12.90 904.60 0.00 0.00 0.00
March 276.47 0.00 276.47 61.67 737.92 0.00 0.00 0.00
April 315.24 1.84 313.40 129.47 532.65 0.00 0.00 0.00
May 413.99 24.53 389.45 270.33 383.26 0.00 0.00 0.00
June 482.06 55.41 426.65 461.64 239.11 0.00 0.00 0.00
July 440.39 41.25 399.14 513.78 196.78 0.00 0.00 0.00
August 352.89 9.46 343.43 369.24 229.53 0.00 0.00 0.00
September 264.29 0.09 264.19 207.86 354.43 0.00 0.00 0.00
October 192.78 0.00 192.78 62.99 542.58 0.00 0.00 0.00
November 131.06 0.00 131.06 9.88 786.72 0.00 0.00 0.00
December 101.08 0.00 101.08 0.24 1062.60 0.00 0.00 0.00
                 
Annual Sum or Average 272.29 11.10 261.19 176.10 595.71 0.00 0.00 0.00
Minimum of Months 101.08 0.00 101.08 0.24 196.78 0.00 0.00 0.00
Maximum of Months 482.06 55.41 426.65 513.78 1193.10 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 120.54 0.00 120.54 0.74 1193.10 0.00 0.00 0.00
February 170.20 0.00 170.20 12.90 904.60 0.00 0.00 0.00
March 276.48 0.00 276.48 61.67 737.92 0.00 0.00 0.00
April 315.24 1.84 313.40 129.47 532.65 0.00 0.00 0.00
May 413.99 24.53 389.45 270.33 383.26 0.00 0.00 0.00
June 482.06 55.41 426.65 461.64 239.11 0.00 0.00 0.00
July 440.39 41.25 399.14 513.78 196.78 0.00 0.00 0.00
August 352.89 9.46 343.43 369.24 229.53 0.00 0.00 0.00
September 264.29 0.09 264.19 207.86 354.43 0.00 0.00 0.00
October 192.78 0.00 192.78 62.99 542.58 0.00 0.00 0.00
November 131.06 0.00 131.06 9.88 786.72 0.00 0.00 0.00
December 101.08 0.00 101.08 0.24 1062.60 0.00 0.00 0.00
                 
Annual Sum or Average 272.29 11.10 261.19 176.10 595.71 0.00 0.00 0.00
Minimum of Months 101.08 0.00 101.08 0.24 196.78 0.00 0.00 0.00
Maximum of Months 482.06 55.41 426.65 513.78 1193.10 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 120.54 0.00 120.54 0.74 1193.10 0.00 0.00 0.00
February 170.20 0.00 170.20 12.90 904.60 0.00 0.00 0.00
March 276.47 0.00 276.47 61.67 737.92 0.00 0.00 0.00
April 315.24 1.84 313.40 129.47 532.65 0.00 0.00 0.00
May 413.99 24.53 389.45 270.33 383.26 0.00 0.00 0.00
June 482.06 55.41 426.65 461.64 239.11 0.00 0.00 0.00
July 440.39 41.25 399.14 513.78 196.78 0.00 0.00 0.00
August 352.89 9.46 343.43 369.24 229.53 0.00 0.00 0.00
September 264.29 0.09 264.19 207.86 354.43 0.00 0.00 0.00
October 192.78 0.00 192.78 62.99 542.58 0.00 0.00 0.00
November 131.06 0.00 131.06 9.88 786.72 0.00 0.00 0.00
December 101.08 0.00 101.08 0.24 1062.60 0.00 0.00 0.00
                 
Annual Sum or Average 272.29 11.10 261.19 176.10 595.71 0.00 0.00 0.00
Minimum of Months 101.08 0.00 101.08 0.24 196.78 0.00 0.00 0.00
Maximum of Months 482.06 55.41 426.65 513.78 1193.10 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 120.54 0.00 120.54 0.74 1193.06 0.00 0.00 0.00
February 170.19 0.00 170.19 12.90 904.56 0.00 0.00 0.00
March 276.46 0.00 276.46 61.67 737.89 0.00 0.00 0.00
April 315.23 1.84 313.39 129.47 532.63 0.00 0.00 0.00
May 413.97 24.53 389.44 270.32 383.24 0.00 0.00 0.00
June 482.04 55.41 426.64 461.62 239.10 0.00 0.00 0.00
July 440.37 41.25 399.13 513.76 196.77 0.00 0.00 0.00
August 352.87 9.46 343.41 369.23 229.52 0.00 0.00 0.00
September 264.28 0.09 264.18 207.85 354.42 0.00 0.00 0.00
October 192.78 0.00 192.78 62.99 542.56 0.00 0.00 0.00
November 131.05 0.00 131.05 9.88 786.69 0.00 0.00 0.00
December 101.08 0.00 101.08 0.24 1062.56 0.00 0.00 0.00
                 
Annual Sum or Average 272.28 11.10 261.18 176.09 595.69 0.00 0.00 0.00
Minimum of Months 101.08 0.00 101.08 0.24 196.77 0.00 0.00 0.00
Maximum of Months 482.04 55.41 426.64 513.76 1193.06 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 307.54 141.00 166.55 141.42 1209.05 0.00 0.00 0.00
February 481.03 238.82 242.21 324.72 906.54 0.00 0.00 0.00
March 646.78 267.62 379.16 480.18 747.66 0.00 0.00 0.00
April 825.23 408.98 416.25 753.51 540.74 0.00 0.00 0.00
May 911.58 405.59 505.98 904.93 419.30 0.00 0.00 0.00
June 1179.92 607.19 572.73 1376.15 266.67 0.00 0.00 0.00
July 1238.36 700.08 538.28 1573.20 210.73 0.00 0.00 0.00
August 1076.19 599.62 476.57 1332.10 237.09 0.00 0.00 0.00
September 761.30 392.98 368.32 840.88 361.10 0.00 0.00 0.00
October 546.19 277.35 268.84 481.22 546.40 0.00 0.00 0.00
November 346.17 161.61 184.55 210.00 771.60 0.00 0.00 0.00
December 255.32 109.66 145.66 106.63 1057.86 0.00 0.00 0.00
                 
Annual Sum or Average 715.86 359.83 356.03 712.65 605.09 0.00 0.00 0.00
Minimum of Months 255.32 109.66 145.66 106.63 210.73 0.00 0.00 0.00
Maximum of Months 1238.36 700.08 572.73 1573.20 1209.05 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 307.54 141.00 166.55 141.42 1209.05 0.00 0.00 0.00
February 481.03 238.82 242.21 324.72 906.54 0.00 0.00 0.00
March 646.78 267.62 379.16 480.18 747.66 0.00 0.00 0.00
April 825.23 408.98 416.25 753.51 540.74 0.00 0.00 0.00
May 911.58 405.59 505.98 904.93 419.30 0.00 0.00 0.00
June 1179.92 607.19 572.73 1376.15 266.67 0.00 0.00 0.00
July 1238.36 700.08 538.28 1573.20 210.73 0.00 0.00 0.00
August 1076.19 599.62 476.57 1332.10 237.09 0.00 0.00 0.00
September 761.30 392.98 368.32 840.88 361.10 0.00 0.00 0.00
October 546.19 277.35 268.84 481.22 546.40 0.00 0.00 0.00
November 346.17 161.61 184.55 210.00 771.60 0.00 0.00 0.00
December 255.32 109.66 145.66 106.63 1057.86 0.00 0.00 0.00
                 
Annual Sum or Average 715.86 359.83 356.03 712.65 605.09 0.00 0.00 0.00
Minimum of Months 255.32 109.66 145.66 106.63 210.73 0.00 0.00 0.00
Maximum of Months 1238.36 700.08 572.73 1573.20 1209.05 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 307.54 140.99 166.54 141.42 1209.03 0.00 0.00 0.00
February 481.02 238.81 242.20 324.71 906.52 0.00 0.00 0.00
March 646.77 267.62 379.16 480.17 747.65 0.00 0.00 0.00
April 825.22 408.97 416.25 753.49 540.73 0.00 0.00 0.00
May 911.56 405.59 505.97 904.91 419.29 0.00 0.00 0.00
June 1179.90 607.17 572.72 1376.12 266.67 0.00 0.00 0.00
July 1238.34 700.06 538.27 1573.17 210.73 0.00 0.00 0.00
August 1076.17 599.61 476.56 1332.08 237.09 0.00 0.00 0.00
September 761.28 392.97 368.31 840.87 361.09 0.00 0.00 0.00
October 546.18 277.34 268.84 481.21 546.39 0.00 0.00 0.00
November 346.16 161.61 184.55 210.00 771.59 0.00 0.00 0.00
December 255.31 109.66 145.66 106.63 1057.84 0.00 0.00 0.00
                 
Annual Sum or Average 715.84 359.82 356.02 712.64 605.08 0.00 0.00 0.00
Minimum of Months 255.31 109.66 145.66 106.63 210.73 0.00 0.00 0.00
Maximum of Months 1238.34 700.06 572.72 1573.17 1209.03 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 849.68 606.86 242.82 747.74 997.48 0.00 0.00 0.00
February 1082.05 778.25 303.80 1059.20 762.60 0.00 0.00 0.00
March 967.21 543.14 424.07 941.72 686.47 0.00 0.00 0.00
April 777.48 371.87 405.60 788.18 520.72 0.00 0.00 0.00
May 690.77 229.42 461.34 714.92 403.48 0.00 0.00 0.00
June 686.35 200.17 486.17 823.31 274.30 0.00 0.00 0.00
July 739.95 273.34 466.61 1002.09 215.13 0.00 0.00 0.00
August 879.38 443.37 436.01 1156.05 243.95 0.00 0.00 0.00
September 975.34 597.62 377.72 1183.34 350.02 0.00 0.00 0.00
October 1019.67 705.09 314.58 1121.63 499.68 0.00 0.00 0.00
November 929.63 673.39 256.24 917.20 649.56 0.00 0.00 0.00
December 807.99 583.45 224.54 724.29 870.13 0.00 0.00 0.00
                 
Annual Sum or Average 865.63 498.65 366.98 930.63 538.62 0.00 0.00 0.00
Minimum of Months 686.35 200.17 224.54 714.92 215.13 0.00 0.00 0.00
Maximum of Months 1082.05 778.25 486.17 1183.34 997.48 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 849.67 606.85 242.82 747.74 997.48 0.00 0.00 0.00
February 1082.05 778.25 303.80 1059.20 762.60 0.00 0.00 0.00
March 967.21 543.14 424.07 941.72 686.47 0.00 0.00 0.00
April 777.47 371.87 405.60 788.18 520.72 0.00 0.00 0.00
May 690.77 229.42 461.34 714.92 403.48 0.00 0.00 0.00
June 686.35 200.17 486.17 823.31 274.30 0.00 0.00 0.00
July 739.95 273.34 466.61 1002.09 215.13 0.00 0.00 0.00
August 879.38 443.37 436.01 1156.05 243.95 0.00 0.00 0.00
September 975.34 597.62 377.72 1183.34 350.02 0.00 0.00 0.00
October 1019.67 705.09 314.58 1121.63 499.68 0.00 0.00 0.00
November 929.63 673.39 256.24 917.20 649.56 0.00 0.00 0.00
December 807.99 583.45 224.54 724.29 870.13 0.00 0.00 0.00
                 
Annual Sum or Average 865.63 498.65 366.98 930.63 538.62 0.00 0.00 0.00
Minimum of Months 686.35 200.17 224.54 714.92 215.13 0.00 0.00 0.00
Maximum of Months 1082.05 778.25 486.17 1183.34 997.48 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 849.68 606.86 242.82 747.74 997.48 0.00 0.00 0.00
February 1082.05 778.25 303.80 1059.20 762.60 0.00 0.00 0.00
March 967.21 543.14 424.07 941.72 686.47 0.00 0.00 0.00
April 777.48 371.87 405.60 788.18 520.72 0.00 0.00 0.00
May 690.77 229.42 461.34 714.92 403.48 0.00 0.00 0.00
June 686.35 200.17 486.17 823.31 274.30 0.00 0.00 0.00
July 739.95 273.34 466.61 1002.09 215.13 0.00 0.00 0.00
August 879.38 443.37 436.01 1156.05 243.95 0.00 0.00 0.00
September 975.34 597.62 377.72 1183.34 350.02 0.00 0.00 0.00
October 1019.67 705.09 314.58 1121.63 499.68 0.00 0.00 0.00
November 929.63 673.39 256.24 917.20 649.56 0.00 0.00 0.00
December 807.99 583.45 224.54 724.29 870.13 0.00 0.00 0.00
                 
Annual Sum or Average 865.63 498.65 366.98 930.63 538.62 0.00 0.00 0.00
Minimum of Months 686.35 200.17 224.54 714.92 215.13 0.00 0.00 0.00
Maximum of Months 1082.05 778.25 486.17 1183.34 997.48 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 849.67 606.85 242.82 747.74 997.48 0.00 0.00 0.00
February 1082.05 778.25 303.80 1059.20 762.60 0.00 0.00 0.00
March 967.21 543.14 424.07 941.72 686.47 0.00 0.00 0.00
April 777.47 371.87 405.60 788.18 520.72 0.00 0.00 0.00
May 690.77 229.42 461.34 714.92 403.48 0.00 0.00 0.00
June 686.35 200.17 486.17 823.31 274.30 0.00 0.00 0.00
July 739.95 273.34 466.61 1002.09 215.13 0.00 0.00 0.00
August 879.38 443.37 436.01 1156.05 243.95 0.00 0.00 0.00
September 975.34 597.62 377.72 1183.34 350.02 0.00 0.00 0.00
October 1019.67 705.09 314.58 1121.63 499.68 0.00 0.00 0.00
November 929.63 673.39 256.24 917.20 649.56 0.00 0.00 0.00
December 807.99 583.45 224.54 724.29 870.13 0.00 0.00 0.00
                 
Annual Sum or Average 865.63 498.65 366.98 930.63 538.62 0.00 0.00 0.00
Minimum of Months 686.35 200.17 224.54 714.92 215.13 0.00 0.00 0.00
Maximum of Months 1082.05 778.25 486.17 1183.34 997.48 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 849.64 606.83 242.81 747.71 997.44 0.00 0.00 0.00
February 1082.01 778.22 303.79 1059.16 762.57 0.00 0.00 0.00
March 967.17 543.12 424.05 941.68 686.44 0.00 0.00 0.00
April 777.44 371.86 405.59 788.15 520.70 0.00 0.00 0.00
May 690.74 229.41 461.33 714.89 403.46 0.00 0.00 0.00
June 686.32 200.16 486.16 823.28 274.29 0.00 0.00 0.00
July 739.92 273.32 466.60 1002.05 215.12 0.00 0.00 0.00
August 879.35 443.35 436.00 1156.01 243.94 0.00 0.00 0.00
September 975.30 597.60 377.70 1183.29 350.00 0.00 0.00 0.00
October 1019.63 705.06 314.57 1121.58 499.66 0.00 0.00 0.00
November 929.60 673.36 256.23 917.17 649.53 0.00 0.00 0.00
December 807.96 583.43 224.53 724.26 870.09 0.00 0.00 0.00
                 
Annual Sum or Average 865.60 498.63 366.97 930.59 538.60 0.00 0.00 0.00
Minimum of Months 686.32 200.16 224.53 714.89 215.12 0.00 0.00 0.00
Maximum of Months 1082.01 778.22 486.16 1183.29 997.44 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 278.57 112.27 166.30 122.94 1300.63 0.00 0.00 0.00
February 475.48 233.72 241.76 320.67 991.31 0.00 0.00 0.00
March 608.49 222.96 385.53 424.22 857.08 0.00 0.00 0.00
April 794.39 351.95 442.44 705.96 651.98 0.00 0.00 0.00
May 982.61 448.12 534.49 998.34 475.74 0.00 0.00 0.00
June 1069.04 491.05 577.99 1231.22 329.65 0.00 0.00 0.00
July 1095.11 553.38 541.74 1383.49 277.84 0.00 0.00 0.00
August 929.90 456.37 473.52 1131.44 311.46 0.00 0.00 0.00
September 748.04 378.18 369.86 832.82 419.05 0.00 0.00 0.00
October 534.65 265.64 269.01 472.90 631.18 0.00 0.00 0.00
November 378.48 187.76 190.72 255.93 883.79 0.00 0.00 0.00
December 254.41 107.38 147.03 107.96 1198.00 0.00 0.00 0.00
                 
Annual Sum or Average 680.02 317.70 362.32 667.50 692.88 0.00 0.00 0.00
Minimum of Months 254.41 107.38 147.03 107.96 277.84 0.00 0.00 0.00
Maximum of Months 1095.11 553.38 577.99 1383.49 1300.63 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 278.57 112.27 166.30 122.94 1300.63 0.00 0.00 0.00
February 475.48 233.72 241.76 320.67 991.31 0.00 0.00 0.00
March 608.49 222.96 385.53 424.22 857.08 0.00 0.00 0.00
April 794.39 351.95 442.44 705.96 651.98 0.00 0.00 0.00
May 982.61 448.12 534.49 998.34 475.74 0.00 0.00 0.00
June 1069.04 491.05 577.99 1231.22 329.65 0.00 0.00 0.00
July 1095.11 553.38 541.74 1383.49 277.84 0.00 0.00 0.00
August 929.90 456.37 473.52 1131.44 311.46 0.00 0.00 0.00
September 748.04 378.18 369.86 832.82 419.05 0.00 0.00 0.00
October 534.65 265.64 269.01 472.90 631.18 0.00 0.00 0.00
November 378.48 187.76 190.72 255.93 883.79 0.00 0.00 0.00
December 254.41 107.38 147.03 107.96 1198.00 0.00 0.00 0.00
                 
Annual Sum or Average 680.02 317.70 362.32 667.50 692.88 0.00 0.00 0.00
Minimum of Months 254.41 107.38 147.03 107.96 277.84 0.00 0.00 0.00
Maximum of Months 1095.11 553.38 577.99 1383.49 1300.63 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 278.56 112.26 166.30 122.94 1300.61 0.00 0.00 0.00
February 475.47 233.72 241.75 320.66 991.29 0.00 0.00 0.00
March 608.48 222.96 385.53 424.21 857.06 0.00 0.00 0.00
April 794.38 351.95 442.43 705.95 651.97 0.00 0.00 0.00
May 982.59 448.11 534.48 998.32 475.73 0.00 0.00 0.00
June 1069.02 491.04 577.98 1231.20 329.64 0.00 0.00 0.00
July 1095.09 553.37 541.73 1383.47 277.84 0.00 0.00 0.00
August 929.88 456.37 473.51 1131.42 311.45 0.00 0.00 0.00
September 748.03 378.17 369.86 832.80 419.04 0.00 0.00 0.00
October 534.64 265.63 269.00 472.89 631.17 0.00 0.00 0.00
November 378.47 187.75 190.72 255.93 883.78 0.00 0.00 0.00
December 254.40 107.38 147.03 107.96 1197.98 0.00 0.00 0.00
                 
Annual Sum or Average 680.01 317.70 362.31 667.49 692.87 0.00 0.00 0.00
Minimum of Months 254.40 107.38 147.03 107.96 277.84 0.00 0.00 0.00
Maximum of Months 1095.09 553.37 577.98 1383.47 1300.61 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 602.69 0.00 602.69 13.23 5604.05 0.00 0.00 0.00
February 850.97 0.00 850.97 115.82 4157.24 0.00 0.00 0.00
March 1382.36 0.00 1382.36 394.42 3347.07 0.00 0.00 0.00
April 1576.18 9.20 1566.98 739.36 2376.23 0.00 0.00 0.00
May 2069.90 122.65 1947.25 1406.81 1768.68 0.00 0.00 0.00
June 2410.29 277.04 2133.25 2344.72 1136.48 0.00 0.00 0.00
July 2201.93 206.24 1995.69 2603.97 942.51 0.00 0.00 0.00
August 1764.42 47.29 1717.12 1884.60 1082.29 0.00 0.00 0.00
September 1321.43 0.47 1320.95 1082.17 1638.96 0.00 0.00 0.00
October 963.90 0.00 963.90 384.89 2416.79 0.00 0.00 0.00
November 655.27 0.00 655.27 85.52 3475.44 0.00 0.00 0.00
December 505.39 0.00 505.39 5.37 4783.41 0.00 0.00 0.00
                 
Annual Sum or Average 1361.45 55.52 1305.94 926.82 2721.93 0.00 0.00 0.00
Minimum of Months 505.39 0.00 505.39 5.37 942.51 0.00 0.00 0.00
Maximum of Months 2410.29 277.04 2133.25 2603.97 5604.05 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 922.62 422.99 499.64 448.91 3440.35 0.00 0.00 0.00
February 1443.07 716.45 726.62 1010.37 2551.21 0.00 0.00 0.00
March 1940.33 802.86 1137.48 1473.27 2097.69 0.00 0.00 0.00
April 2475.67 1226.93 1248.75 2277.67 1512.76 0.00 0.00 0.00
May 2734.70 1216.77 1517.93 2717.26 1180.19 0.00 0.00 0.00
June 3539.72 1821.54 1718.18 4109.45 776.49 0.00 0.00 0.00
July 3715.04 2100.21 1614.83 4694.01 631.00 0.00 0.00 0.00
August 3228.53 1798.84 1429.69 3973.97 712.08 0.00 0.00 0.00
September 2283.87 1178.92 1104.94 2521.40 1025.92 0.00 0.00 0.00
October 1638.56 832.03 806.52 1471.92 1511.19 0.00 0.00 0.00
November 1038.49 484.84 553.65 667.82 2117.05 0.00 0.00 0.00
December 765.94 328.97 436.97 347.46 2931.63 0.00 0.00 0.00
                 
Annual Sum or Average 2147.55 1079.48 1068.07 2149.35 1704.19 0.00 0.00 0.00
Minimum of Months 765.94 328.97 436.97 347.46 631.00 0.00 0.00 0.00
Maximum of Months 3715.04 2100.21 1718.18 4694.01 3440.35 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 4248.33 3034.24 1214.09 3729.86 4869.53 0.00 0.00 0.00
February 5410.18 3891.20 1518.98 5268.04 3699.49 0.00 0.00 0.00
March 4835.99 2715.67 2120.32 4688.36 3311.92 0.00 0.00 0.00
April 3887.33 1859.33 2027.99 3937.57 2474.77 0.00 0.00 0.00
May 3453.79 1147.10 2306.69 3562.72 1939.71 0.00 0.00 0.00
June 3431.69 1000.84 2430.85 4107.05 1326.93 0.00 0.00 0.00
July 3699.71 1366.66 2333.05 4999.33 1052.07 0.00 0.00 0.00
August 4396.86 2216.82 2180.04 5757.85 1194.48 0.00 0.00 0.00
September 4876.64 2988.08 1888.57 5868.35 1705.55 0.00 0.00 0.00
October 5098.27 3525.39 1572.88 5573.95 2411.40 0.00 0.00 0.00
November 4648.11 3366.91 1281.21 4584.00 3110.73 0.00 0.00 0.00
December 4039.92 2917.23 1122.69 3643.30 4144.21 0.00 0.00 0.00
                 
Annual Sum or Average 4328.10 2493.22 1834.88 4638.44 2599.31 0.00 0.00 0.00
Minimum of Months 3431.69 1000.84 1122.69 3562.72 1052.07 0.00 0.00 0.00
Maximum of Months 5410.18 3891.20 2430.85 5868.35 4869.53 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 835.70 336.79 498.91 390.87 3643.29 0.00 0.00 0.00
February 1426.42 701.16 725.26 1017.60 2675.64 0.00 0.00 0.00
March 1825.47 668.88 1156.59 1352.34 2252.05 0.00 0.00 0.00
April 2383.16 1055.85 1327.31 2212.20 1660.20 0.00 0.00 0.00
May 2947.79 1344.35 1603.44 3028.46 1307.39 0.00 0.00 0.00
June 3207.09 1473.13 1733.95 3733.50 900.79 0.00 0.00 0.00
July 3285.30 1660.11 1625.19 4194.63 755.55 0.00 0.00 0.00
August 2789.66 1369.11 1420.56 3454.39 815.85 0.00 0.00 0.00
September 2244.11 1134.53 1109.58 2530.14 1144.40 0.00 0.00 0.00
October 1603.92 796.90 807.02 1487.65 1644.96 0.00 0.00 0.00
November 1135.42 563.27 572.16 832.22 2262.20 0.00 0.00 0.00
December 763.21 322.13 441.08 368.74 3083.49 0.00 0.00 0.00
                 
Annual Sum or Average 2040.04 953.10 1086.94 2055.68 1842.54 0.00 0.00 0.00
Minimum of Months 763.21 322.13 441.08 368.74 755.55 0.00 0.00 0.00
Maximum of Months 3285.30 1660.11 1733.95 4194.63 3643.29 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 602.69 0.00 602.69 18.54 5455.76 0.00 0.00 0.00
February 850.97 0.00 850.97 140.81 3989.84 0.00 0.00 0.00
March 1382.36 0.00 1382.36 433.54 3172.67 0.00 0.00 0.00
April 1576.18 9.20 1566.98 790.45 2212.58 0.00 0.00 0.00
May 2069.90 122.65 1947.25 1436.62 1668.84 0.00 0.00 0.00
June 2410.29 277.04 2133.25 2355.46 1103.62 0.00 0.00 0.00
July 2201.93 206.24 1995.69 2600.79 925.86 0.00 0.00 0.00
August 1764.42 47.29 1717.12 1886.70 1048.91 0.00 0.00 0.00
September 1321.43 0.47 1320.95 1105.12 1547.72 0.00 0.00 0.00
October 963.90 0.00 963.90 439.62 2216.19 0.00 0.00 0.00
November 655.27 0.00 655.27 109.16 3247.39 0.00 0.00 0.00
December 505.39 0.00 505.39 6.54 4603.18 0.00 0.00 0.00
                 
Annual Sum or Average 1361.45 55.52 1305.94 948.61 2594.22 0.00 0.00 0.00
Minimum of Months 505.39 0.00 505.39 6.54 925.86 0.00 0.00 0.00
Maximum of Months 2410.29 277.04 2133.25 2600.79 5455.76 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 922.62 422.99 499.64 461.90 3352.65 0.00 0.00 0.00
February 1443.07 716.45 726.62 1040.74 2451.24 0.00 0.00 0.00
March 1940.33 802.86 1137.48 1505.45 1996.30 0.00 0.00 0.00
April 2475.67 1226.93 1248.75 2306.82 1423.40 0.00 0.00 0.00
May 2734.70 1216.77 1517.93 2727.23 1124.99 0.00 0.00 0.00
June 3539.72 1821.54 1718.18 4104.35 761.73 0.00 0.00 0.00
July 3715.04 2100.21 1614.83 4682.28 623.63 0.00 0.00 0.00
August 3228.53 1798.84 1429.69 3966.56 698.39 0.00 0.00 0.00
September 2283.87 1178.92 1104.94 2529.42 983.77 0.00 0.00 0.00
October 1638.56 832.03 806.52 1511.47 1401.36 0.00 0.00 0.00
November 1038.49 484.84 553.65 701.62 1983.92 0.00 0.00 0.00
December 765.94 328.97 436.97 360.27 2821.13 0.00 0.00 0.00
                 
Annual Sum or Average 2147.55 1079.48 1068.07 2164.60 1632.30 0.00 0.00 0.00
Minimum of Months 765.94 328.97 436.97 360.27 623.63 0.00 0.00 0.00
Maximum of Months 3715.04 2100.21 1718.18 4682.28 3352.65 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 4248.33 3034.24 1214.09 3765.06 4710.99 0.00 0.00 0.00
February 5410.18 3891.20 1518.98 5313.07 3529.05 0.00 0.00 0.00
March 4835.99 2715.67 2120.32 4728.59 3142.89 0.00 0.00 0.00
April 3887.33 1859.33 2027.99 3973.02 2324.24 0.00 0.00 0.00
May 3453.79 1147.10 2306.69 3577.36 1841.99 0.00 0.00 0.00
June 3431.69 1000.84 2430.85 4103.66 1289.41 0.00 0.00 0.00
July 3699.71 1366.66 2333.05 4987.78 1030.79 0.00 0.00 0.00
August 4396.86 2216.82 2180.04 5747.27 1162.31 0.00 0.00 0.00
September 4876.64 2988.08 1888.57 5872.71 1628.74 0.00 0.00 0.00
October 5098.27 3525.39 1572.88 5619.24 2240.01 0.00 0.00 0.00
November 4648.11 3366.91 1281.21 4650.88 2902.88 0.00 0.00 0.00
December 4039.92 2917.23 1122.69 3691.89 3960.48 0.00 0.00 0.00
                 
Annual Sum or Average 4328.10 2493.22 1834.88 4664.13 2476.56 0.00 0.00 0.00
Minimum of Months 3431.69 1000.84 1122.69 3577.36 1030.79 0.00 0.00 0.00
Maximum of Months 5410.18 3891.20 2430.85 5872.71 4710.99 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 835.70 336.79 498.91 398.08 3552.78 0.00 0.00 0.00
February 1426.42 701.16 725.26 1031.11 2577.63 0.00 0.00 0.00
March 1825.47 668.88 1156.59 1367.16 2155.03 0.00 0.00 0.00
April 2383.16 1055.85 1327.31 2231.21 1572.00 0.00 0.00 0.00
May 2947.79 1344.35 1603.44 3033.50 1246.72 0.00 0.00 0.00
June 3207.09 1473.13 1733.95 3729.16 877.94 0.00 0.00 0.00
July 3285.30 1660.11 1625.19 4186.69 742.01 0.00 0.00 0.00
August 2789.66 1369.11 1420.56 3449.92 795.63 0.00 0.00 0.00
September 2244.11 1134.53 1109.58 2534.93 1096.56 0.00 0.00 0.00
October 1603.92 796.90 807.02 1511.23 1540.24 0.00 0.00 0.00
November 1135.42 563.27 572.16 850.89 2137.49 0.00 0.00 0.00
December 763.21 322.13 441.08 376.10 2980.34 0.00 0.00 0.00
                 
Annual Sum or Average 2040.04 953.10 1086.94 2063.73 1770.11 0.00 0.00 0.00
Minimum of Months 763.21 322.13 441.08 376.10 742.01 0.00 0.00 0.00
Maximum of Months 3285.30 1660.11 1733.95 4186.69 3552.78 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.322855E+09 0.00 0.322855E+09 1993634.24 0.319561E+10
February 0.411737E+09 0.00 0.411737E+09 31199354.44 0.218841E+10
March 0.740511E+09 0.00 0.740511E+09 0.165190E+09 0.197645E+10
April 0.817102E+09 4768427.33 0.812334E+09 0.335588E+09 0.138063E+10
May 0.110882E+10 65704405.30 0.104311E+10 0.724053E+09 0.102651E+10
June 0.124951E+10 0.143620E+09 0.110589E+10 0.119658E+10 0.619763E+09
July 0.117954E+10 0.110478E+09 0.106907E+10 0.137612E+10 0.527045E+09
August 0.945175E+09 25335095.46 0.919840E+09 0.988982E+09 0.614774E+09
September 0.685036E+09 245828.01 0.684790E+09 0.538769E+09 0.918684E+09
October 0.516350E+09 0.00 0.516350E+09 0.168714E+09 0.145324E+10
November 0.339697E+09 0.00 0.339697E+09 25602539.88 0.203919E+10
December 0.270733E+09 0.00 0.270733E+09 635025.40 0.284608E+10
           
Annual Sum or Average 0.858707E+10 0.350153E+09 0.823692E+10 0.555342E+10 0.187864E+11
Minimum of Months 0.270733E+09 0.00 0.270733E+09 635025.40 0.527045E+09
Maximum of Months 0.124951E+10 0.143620E+09 0.110589E+10 0.137612E+10 0.319561E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.322855E+09 0.00 0.322855E+09 1993615.31 0.319561E+10
February 0.411736E+09 0.00 0.411736E+09 31199266.63 0.218841E+10
March 0.740511E+09 0.00 0.740511E+09 0.165189E+09 0.197645E+10
April 0.817102E+09 4768421.61 0.812333E+09 0.335588E+09 0.138063E+10
May 0.110882E+10 65704326.46 0.104311E+10 0.724052E+09 0.102651E+10
June 0.124951E+10 0.143620E+09 0.110589E+10 0.119658E+10 0.619763E+09
July 0.117954E+10 0.110478E+09 0.106906E+10 0.137612E+10 0.527045E+09
August 0.945174E+09 25335065.06 0.919839E+09 0.988981E+09 0.614774E+09
September 0.685035E+09 245827.72 0.684790E+09 0.538768E+09 0.918684E+09
October 0.516350E+09 0.00 0.516350E+09 0.168714E+09 0.145324E+10
November 0.339696E+09 0.00 0.339696E+09 25602449.24 0.203919E+10
December 0.270732E+09 0.00 0.270732E+09 635021.06 0.284608E+10
           
Annual Sum or Average 0.858706E+10 0.350152E+09 0.823691E+10 0.555342E+10 0.187864E+11
Minimum of Months 0.270732E+09 0.00 0.270732E+09 635021.06 0.527045E+09
Maximum of Months 0.124951E+10 0.143620E+09 0.110589E+10 0.137612E+10 0.319561E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.322855E+09 0.00 0.322855E+09 1993634.24 0.319561E+10
February 0.411737E+09 0.00 0.411737E+09 31199354.44 0.218841E+10
March 0.740511E+09 0.00 0.740511E+09 0.165190E+09 0.197645E+10
April 0.817102E+09 4768427.33 0.812334E+09 0.335588E+09 0.138063E+10
May 0.110882E+10 65704405.30 0.104311E+10 0.724053E+09 0.102651E+10
June 0.124951E+10 0.143620E+09 0.110589E+10 0.119658E+10 0.619763E+09
July 0.117954E+10 0.110478E+09 0.106907E+10 0.137612E+10 0.527045E+09
August 0.945175E+09 25335095.46 0.919840E+09 0.988982E+09 0.614774E+09
September 0.685036E+09 245828.01 0.684790E+09 0.538769E+09 0.918684E+09
October 0.516350E+09 0.00 0.516350E+09 0.168714E+09 0.145324E+10
November 0.339697E+09 0.00 0.339697E+09 25602539.88 0.203919E+10
December 0.270733E+09 0.00 0.270733E+09 635025.40 0.284608E+10
           
Annual Sum or Average 0.858707E+10 0.350153E+09 0.823692E+10 0.555342E+10 0.187864E+11
Minimum of Months 0.270733E+09 0.00 0.270733E+09 635025.40 0.527045E+09
Maximum of Months 0.124951E+10 0.143620E+09 0.110589E+10 0.137612E+10 0.319561E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.322855E+09 0.00 0.322855E+09 1993615.31 0.319561E+10
February 0.411736E+09 0.00 0.411736E+09 31199266.63 0.218841E+10
March 0.740511E+09 0.00 0.740511E+09 0.165189E+09 0.197645E+10
April 0.817102E+09 4768421.61 0.812333E+09 0.335588E+09 0.138063E+10
May 0.110882E+10 65704326.46 0.104311E+10 0.724052E+09 0.102651E+10
June 0.124951E+10 0.143620E+09 0.110589E+10 0.119658E+10 0.619763E+09
July 0.117954E+10 0.110478E+09 0.106906E+10 0.137612E+10 0.527045E+09
August 0.945174E+09 25335065.06 0.919839E+09 0.988981E+09 0.614774E+09
September 0.685035E+09 245827.72 0.684790E+09 0.538768E+09 0.918684E+09
October 0.516350E+09 0.00 0.516350E+09 0.168714E+09 0.145324E+10
November 0.339696E+09 0.00 0.339696E+09 25602449.24 0.203919E+10
December 0.270732E+09 0.00 0.270732E+09 635021.06 0.284608E+10
           
Annual Sum or Average 0.858706E+10 0.350152E+09 0.823691E+10 0.555342E+10 0.187864E+11
Minimum of Months 0.270732E+09 0.00 0.270732E+09 635021.06 0.527045E+09
Maximum of Months 0.124951E+10 0.143620E+09 0.110589E+10 0.137612E+10 0.319561E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.322842E+09 0.00 0.322842E+09 1993553.89 0.319548E+10
February 0.411720E+09 0.00 0.411720E+09 31198096.97 0.218832E+10
March 0.740481E+09 0.00 0.740481E+09 0.165183E+09 0.197637E+10
April 0.817070E+09 4768235.14 0.812301E+09 0.335575E+09 0.138057E+10
May 0.110877E+10 65701757.12 0.104307E+10 0.724023E+09 0.102647E+10
June 0.124946E+10 0.143615E+09 0.110584E+10 0.119653E+10 0.619738E+09
July 0.117950E+10 0.110474E+09 0.106902E+10 0.137606E+10 0.527024E+09
August 0.945137E+09 25334074.34 0.919803E+09 0.988942E+09 0.614749E+09
September 0.685008E+09 245818.10 0.684762E+09 0.538747E+09 0.918647E+09
October 0.516329E+09 0.00 0.516329E+09 0.168707E+09 0.145318E+10
November 0.339683E+09 0.00 0.339683E+09 25601507.99 0.203911E+10
December 0.270722E+09 0.00 0.270722E+09 634999.80 0.284596E+10
           
Annual Sum or Average 0.858672E+10 0.350138E+09 0.823658E+10 0.555320E+10 0.187856E+11
Minimum of Months 0.270722E+09 0.00 0.270722E+09 634999.80 0.527024E+09
Maximum of Months 0.124946E+10 0.143615E+09 0.110584E+10 0.137606E+10 0.319548E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.823727E+09 0.377645E+09 0.446082E+09 0.378781E+09 0.323831E+10
February 0.116370E+10 0.577749E+09 0.585951E+09 0.785555E+09 0.219310E+10
March 0.173235E+10 0.716797E+09 0.101555E+10 0.128610E+10 0.200254E+10
April 0.213900E+10 0.106007E+10 0.107893E+10 0.195309E+10 0.140159E+10
May 0.244157E+10 0.108635E+10 0.135522E+10 0.242376E+10 0.112306E+10
June 0.305835E+10 0.157382E+10 0.148453E+10 0.356698E+10 0.691213E+09
July 0.331682E+10 0.187509E+10 0.144173E+10 0.421365E+10 0.564431E+09
August 0.288246E+10 0.160602E+10 0.127644E+10 0.356790E+10 0.635020E+09
September 0.197328E+10 0.101860E+10 0.954682E+09 0.217957E+10 0.935961E+09
October 0.146292E+10 0.742847E+09 0.720071E+09 0.128891E+10 0.146348E+10
November 0.897261E+09 0.418903E+09 0.478358E+09 0.544321E+09 0.199999E+10
December 0.683841E+09 0.293711E+09 0.390130E+09 0.285593E+09 0.283336E+10
           
Annual Sum or Average 0.225753E+11 0.113476E+11 0.112277E+11 0.224742E+11 0.190820E+11
Minimum of Months 0.683841E+09 0.293711E+09 0.390130E+09 0.285593E+09 0.564431E+09
Maximum of Months 0.331682E+10 0.187509E+10 0.148453E+10 0.421365E+10 0.323831E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.823727E+09 0.377645E+09 0.446082E+09 0.378781E+09 0.323831E+10
February 0.116370E+10 0.577749E+09 0.585951E+09 0.785555E+09 0.219310E+10
March 0.173235E+10 0.716797E+09 0.101555E+10 0.128610E+10 0.200254E+10
April 0.213900E+10 0.106007E+10 0.107893E+10 0.195309E+10 0.140159E+10
May 0.244157E+10 0.108635E+10 0.135522E+10 0.242376E+10 0.112306E+10
June 0.305835E+10 0.157382E+10 0.148453E+10 0.356698E+10 0.691213E+09
July 0.331682E+10 0.187509E+10 0.144173E+10 0.421365E+10 0.564431E+09
August 0.288246E+10 0.160602E+10 0.127644E+10 0.356790E+10 0.635020E+09
September 0.197328E+10 0.101860E+10 0.954682E+09 0.217957E+10 0.935961E+09
October 0.146292E+10 0.742847E+09 0.720071E+09 0.128891E+10 0.146348E+10
November 0.897261E+09 0.418903E+09 0.478358E+09 0.544321E+09 0.199999E+10
December 0.683841E+09 0.293711E+09 0.390130E+09 0.285593E+09 0.283336E+10
           
Annual Sum or Average 0.225753E+11 0.113476E+11 0.112277E+11 0.224742E+11 0.190820E+11
Minimum of Months 0.683841E+09 0.293711E+09 0.390130E+09 0.285593E+09 0.564431E+09
Maximum of Months 0.331682E+10 0.187509E+10 0.148453E+10 0.421365E+10 0.323831E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.823712E+09 0.377639E+09 0.446073E+09 0.378774E+09 0.323825E+10
February 0.116368E+10 0.577739E+09 0.585940E+09 0.785541E+09 0.219306E+10
March 0.173232E+10 0.716784E+09 0.101553E+10 0.128608E+10 0.200250E+10
April 0.213897E+10 0.106006E+10 0.107891E+10 0.195306E+10 0.140156E+10
May 0.244152E+10 0.108633E+10 0.135520E+10 0.242372E+10 0.112304E+10
June 0.305829E+10 0.157380E+10 0.148450E+10 0.356691E+10 0.691200E+09
July 0.331676E+10 0.187505E+10 0.144171E+10 0.421357E+10 0.564420E+09
August 0.288241E+10 0.160599E+10 0.127642E+10 0.356784E+10 0.635009E+09
September 0.197325E+10 0.101858E+10 0.954664E+09 0.217953E+10 0.935944E+09
October 0.146289E+10 0.742834E+09 0.720058E+09 0.128888E+10 0.146345E+10
November 0.897244E+09 0.418895E+09 0.478349E+09 0.544311E+09 0.199996E+10
December 0.683829E+09 0.293706E+09 0.390123E+09 0.285588E+09 0.283331E+10
           
Annual Sum or Average 0.225749E+11 0.113474E+11 0.112275E+11 0.224738E+11 0.190817E+11
Minimum of Months 0.683829E+09 0.293706E+09 0.390123E+09 0.285588E+09 0.564420E+09
Maximum of Months 0.331676E+10 0.187505E+10 0.148450E+10 0.421357E+10 0.323825E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.227577E+10 0.162540E+10 0.650370E+09 0.200275E+10 0.267166E+10
February 0.261769E+10 0.188274E+10 0.734950E+09 0.256241E+10 0.184489E+10
March 0.259058E+10 0.145475E+10 0.113583E+10 0.252231E+10 0.183863E+10
April 0.201522E+10 0.963891E+09 0.105133E+10 0.204296E+10 0.134970E+10
May 0.185015E+10 0.614486E+09 0.123566E+10 0.191485E+10 0.108068E+10
June 0.177901E+10 0.518844E+09 0.126017E+10 0.213403E+10 0.710980E+09
July 0.198188E+10 0.732101E+09 0.124978E+10 0.268400E+10 0.576197E+09
August 0.235534E+10 0.118752E+10 0.116782E+10 0.309637E+10 0.653397E+09
September 0.252808E+10 0.154904E+10 0.979045E+09 0.306722E+10 0.907244E+09
October 0.273107E+10 0.188850E+10 0.842571E+09 0.300417E+10 0.133833E+10
November 0.240961E+10 0.174543E+10 0.664186E+09 0.237739E+10 0.168366E+10
December 0.216413E+10 0.156272E+10 0.601409E+09 0.193995E+10 0.233055E+10
           
Annual Sum or Average 0.272985E+11 0.157254E+11 0.115731E+11 0.293484E+11 0.169859E+11
Minimum of Months 0.177901E+10 0.518844E+09 0.601409E+09 0.191485E+10 0.576197E+09
Maximum of Months 0.273107E+10 0.188850E+10 0.126017E+10 0.309637E+10 0.267166E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.227577E+10 0.162540E+10 0.650369E+09 0.200275E+10 0.267166E+10
February 0.261769E+10 0.188274E+10 0.734950E+09 0.256241E+10 0.184489E+10
March 0.259057E+10 0.145475E+10 0.113583E+10 0.252230E+10 0.183863E+10
April 0.201521E+10 0.963890E+09 0.105132E+10 0.204296E+10 0.134970E+10
May 0.185015E+10 0.614485E+09 0.123566E+10 0.191485E+10 0.108068E+10
June 0.177901E+10 0.518843E+09 0.126016E+10 0.213403E+10 0.710980E+09
July 0.198188E+10 0.732101E+09 0.124978E+10 0.268400E+10 0.576197E+09
August 0.235534E+10 0.118752E+10 0.116782E+10 0.309637E+10 0.653397E+09
September 0.252808E+10 0.154904E+10 0.979044E+09 0.306722E+10 0.907244E+09
October 0.273107E+10 0.188850E+10 0.842571E+09 0.300417E+10 0.133833E+10
November 0.240961E+10 0.174542E+10 0.664185E+09 0.237739E+10 0.168366E+10
December 0.216413E+10 0.156272E+10 0.601409E+09 0.193994E+10 0.233055E+10
           
Annual Sum or Average 0.272985E+11 0.157254E+11 0.115731E+11 0.293484E+11 0.169859E+11
Minimum of Months 0.177901E+10 0.518843E+09 0.601409E+09 0.191485E+10 0.576197E+09
Maximum of Months 0.273107E+10 0.188850E+10 0.126016E+10 0.309637E+10 0.267166E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.227577E+10 0.162540E+10 0.650370E+09 0.200275E+10 0.267166E+10
February 0.261769E+10 0.188274E+10 0.734950E+09 0.256241E+10 0.184489E+10
March 0.259058E+10 0.145475E+10 0.113583E+10 0.252231E+10 0.183863E+10
April 0.201522E+10 0.963891E+09 0.105133E+10 0.204296E+10 0.134970E+10
May 0.185015E+10 0.614486E+09 0.123566E+10 0.191485E+10 0.108068E+10
June 0.177901E+10 0.518844E+09 0.126017E+10 0.213403E+10 0.710980E+09
July 0.198188E+10 0.732101E+09 0.124978E+10 0.268400E+10 0.576197E+09
August 0.235534E+10 0.118752E+10 0.116782E+10 0.309637E+10 0.653397E+09
September 0.252808E+10 0.154904E+10 0.979045E+09 0.306722E+10 0.907244E+09
October 0.273107E+10 0.188850E+10 0.842571E+09 0.300417E+10 0.133833E+10
November 0.240961E+10 0.174543E+10 0.664186E+09 0.237739E+10 0.168366E+10
December 0.216413E+10 0.156272E+10 0.601409E+09 0.193995E+10 0.233055E+10
           
Annual Sum or Average 0.272985E+11 0.157254E+11 0.115731E+11 0.293484E+11 0.169859E+11
Minimum of Months 0.177901E+10 0.518844E+09 0.601409E+09 0.191485E+10 0.576197E+09
Maximum of Months 0.273107E+10 0.188850E+10 0.126017E+10 0.309637E+10 0.267166E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.227577E+10 0.162540E+10 0.650369E+09 0.200275E+10 0.267166E+10
February 0.261769E+10 0.188274E+10 0.734950E+09 0.256241E+10 0.184489E+10
March 0.259057E+10 0.145475E+10 0.113583E+10 0.252230E+10 0.183863E+10
April 0.201521E+10 0.963890E+09 0.105132E+10 0.204296E+10 0.134970E+10
May 0.185015E+10 0.614485E+09 0.123566E+10 0.191485E+10 0.108068E+10
June 0.177901E+10 0.518843E+09 0.126016E+10 0.213403E+10 0.710980E+09
July 0.198188E+10 0.732101E+09 0.124978E+10 0.268400E+10 0.576197E+09
August 0.235534E+10 0.118752E+10 0.116782E+10 0.309637E+10 0.653397E+09
September 0.252808E+10 0.154904E+10 0.979044E+09 0.306722E+10 0.907244E+09
October 0.273107E+10 0.188850E+10 0.842571E+09 0.300417E+10 0.133833E+10
November 0.240961E+10 0.174542E+10 0.664185E+09 0.237739E+10 0.168366E+10
December 0.216413E+10 0.156272E+10 0.601409E+09 0.193994E+10 0.233055E+10
           
Annual Sum or Average 0.272985E+11 0.157254E+11 0.115731E+11 0.293484E+11 0.169859E+11
Minimum of Months 0.177901E+10 0.518843E+09 0.601409E+09 0.191485E+10 0.576197E+09
Maximum of Months 0.273107E+10 0.188850E+10 0.126016E+10 0.309637E+10 0.267166E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.227568E+10 0.162534E+10 0.650343E+09 0.200267E+10 0.267155E+10
February 0.261759E+10 0.188267E+10 0.734921E+09 0.256231E+10 0.184481E+10
March 0.259047E+10 0.145469E+10 0.113578E+10 0.252220E+10 0.183855E+10
April 0.201513E+10 0.963852E+09 0.105128E+10 0.204288E+10 0.134964E+10
May 0.185008E+10 0.614461E+09 0.123561E+10 0.191477E+10 0.108063E+10
June 0.177894E+10 0.518823E+09 0.126011E+10 0.213394E+10 0.710951E+09
July 0.198180E+10 0.732072E+09 0.124973E+10 0.268389E+10 0.576174E+09
August 0.235524E+10 0.118747E+10 0.116777E+10 0.309625E+10 0.653371E+09
September 0.252798E+10 0.154898E+10 0.979005E+09 0.306710E+10 0.907207E+09
October 0.273096E+10 0.188843E+10 0.842537E+09 0.300405E+10 0.133828E+10
November 0.240951E+10 0.174535E+10 0.664159E+09 0.237729E+10 0.168359E+10
December 0.216404E+10 0.156266E+10 0.601385E+09 0.193987E+10 0.233046E+10
           
Annual Sum or Average 0.272974E+11 0.157248E+11 0.115726E+11 0.293472E+11 0.169852E+11
Minimum of Months 0.177894E+10 0.518823E+09 0.601385E+09 0.191477E+10 0.576174E+09
Maximum of Months 0.273096E+10 0.188843E+10 0.126011E+10 0.309625E+10 0.267155E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.746122E+09 0.300693E+09 0.445429E+09 0.329295E+09 0.348362E+10
February 0.115027E+10 0.565418E+09 0.584856E+09 0.775758E+09 0.239817E+10
March 0.162979E+10 0.597181E+09 0.103261E+10 0.113622E+10 0.229560E+10
April 0.205907E+10 0.912262E+09 0.114681E+10 0.182985E+10 0.168994E+10
May 0.263182E+10 0.120025E+10 0.143157E+10 0.267396E+10 0.127421E+10
June 0.277095E+10 0.127280E+10 0.149815E+10 0.319132E+10 0.854449E+09
July 0.293315E+10 0.148216E+10 0.145098E+10 0.370555E+10 0.744180E+09
August 0.249064E+10 0.122235E+10 0.126829E+10 0.303045E+10 0.834207E+09
September 0.193893E+10 0.980245E+09 0.958686E+09 0.215866E+10 0.108617E+10
October 0.143200E+10 0.711482E+09 0.720515E+09 0.126661E+10 0.169055E+10
November 0.981017E+09 0.486668E+09 0.494349E+09 0.663380E+09 0.229080E+10
December 0.681403E+09 0.287601E+09 0.393802E+09 0.289158E+09 0.320873E+10
           
Annual Sum or Average 0.214452E+11 0.100191E+11 0.114260E+11 0.210502E+11 0.218506E+11
Minimum of Months 0.681403E+09 0.287601E+09 0.393802E+09 0.289158E+09 0.744180E+09
Maximum of Months 0.293315E+10 0.148216E+10 0.149815E+10 0.370555E+10 0.348362E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.746122E+09 0.300693E+09 0.445429E+09 0.329295E+09 0.348362E+10
February 0.115027E+10 0.565418E+09 0.584856E+09 0.775758E+09 0.239817E+10
March 0.162979E+10 0.597181E+09 0.103261E+10 0.113622E+10 0.229560E+10
April 0.205907E+10 0.912262E+09 0.114681E+10 0.182985E+10 0.168994E+10
May 0.263182E+10 0.120025E+10 0.143157E+10 0.267396E+10 0.127421E+10
June 0.277095E+10 0.127280E+10 0.149815E+10 0.319132E+10 0.854449E+09
July 0.293315E+10 0.148216E+10 0.145098E+10 0.370555E+10 0.744180E+09
August 0.249064E+10 0.122235E+10 0.126829E+10 0.303045E+10 0.834207E+09
September 0.193893E+10 0.980245E+09 0.958686E+09 0.215866E+10 0.108617E+10
October 0.143200E+10 0.711482E+09 0.720515E+09 0.126661E+10 0.169055E+10
November 0.981017E+09 0.486668E+09 0.494349E+09 0.663380E+09 0.229080E+10
December 0.681403E+09 0.287601E+09 0.393802E+09 0.289158E+09 0.320873E+10
           
Annual Sum or Average 0.214452E+11 0.100191E+11 0.114260E+11 0.210502E+11 0.218506E+11
Minimum of Months 0.681403E+09 0.287601E+09 0.393802E+09 0.289158E+09 0.744180E+09
Maximum of Months 0.293315E+10 0.148216E+10 0.149815E+10 0.370555E+10 0.348362E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.746108E+09 0.300687E+09 0.445421E+09 0.329289E+09 0.348355E+10
February 0.115025E+10 0.565408E+09 0.584845E+09 0.775744E+09 0.239812E+10
March 0.162976E+10 0.597170E+09 0.103259E+10 0.113620E+10 0.229555E+10
April 0.205903E+10 0.912245E+09 0.114678E+10 0.182981E+10 0.168991E+10
May 0.263177E+10 0.120023E+10 0.143154E+10 0.267391E+10 0.127419E+10
June 0.277090E+10 0.127278E+10 0.149812E+10 0.319126E+10 0.854433E+09
July 0.293309E+10 0.148214E+10 0.145096E+10 0.370548E+10 0.744166E+09
August 0.249059E+10 0.122233E+10 0.126826E+10 0.303040E+10 0.834191E+09
September 0.193890E+10 0.980227E+09 0.958669E+09 0.215863E+10 0.108615E+10
October 0.143197E+10 0.711469E+09 0.720502E+09 0.126658E+10 0.169052E+10
November 0.980999E+09 0.486659E+09 0.494340E+09 0.663368E+09 0.229075E+10
December 0.681391E+09 0.287596E+09 0.393795E+09 0.289153E+09 0.320867E+10
           
Annual Sum or Average 0.214448E+11 0.100189E+11 0.114258E+11 0.210498E+11 0.218502E+11
Minimum of Months 0.681391E+09 0.287596E+09 0.393795E+09 0.289153E+09 0.744166E+09
Maximum of Months 0.293309E+10 0.148214E+10 0.149812E+10 0.370548E+10 0.348355E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.161426E+10 0.00 0.161426E+10 35444382.29 0.150099E+11
February 0.205866E+10 0.00 0.205866E+10 0.280202E+09 0.100572E+11
March 0.370251E+10 0.00 0.370251E+10 0.105642E+10 0.896479E+10
April 0.408546E+10 23841848.37 0.406162E+10 0.191643E+10 0.615918E+10
May 0.554403E+10 0.328518E+09 0.521551E+10 0.376801E+10 0.473724E+10
June 0.624747E+10 0.718093E+09 0.552937E+10 0.607753E+10 0.294575E+10
July 0.589765E+10 0.552386E+09 0.534526E+10 0.697447E+10 0.252443E+10
August 0.472582E+10 0.126674E+09 0.459914E+10 0.504771E+10 0.289880E+10
September 0.342514E+10 1229125.19 0.342391E+10 0.280500E+10 0.424818E+10
October 0.258172E+10 0.00 0.258172E+10 0.103089E+10 0.647314E+10
November 0.169846E+10 0.00 0.169846E+10 0.221677E+09 0.900835E+10
December 0.135365E+10 0.00 0.135365E+10 14393576.88 0.128119E+11
           
Annual Sum or Average 0.429348E+11 0.175074E+10 0.411841E+11 0.292282E+11 0.858388E+11
Minimum of Months 0.135365E+10 0.00 0.135365E+10 14393576.88 0.252443E+10
Maximum of Months 0.624747E+10 0.718093E+09 0.552937E+10 0.697447E+10 0.150099E+11



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.247116E+10 0.113292E+10 0.133823E+10 0.120235E+10 0.921462E+10
February 0.349106E+10 0.173323E+10 0.175783E+10 0.244430E+10 0.617189E+10
March 0.519699E+10 0.215037E+10 0.304662E+10 0.394601E+10 0.561845E+10
April 0.641695E+10 0.318019E+10 0.323676E+10 0.590371E+10 0.392108E+10
May 0.732463E+10 0.325900E+10 0.406563E+10 0.727791E+10 0.316102E+10
June 0.917496E+10 0.472143E+10 0.445353E+10 0.106517E+11 0.201267E+10
July 0.995035E+10 0.562520E+10 0.432515E+10 0.125724E+11 0.169006E+10
August 0.864730E+10 0.481801E+10 0.382929E+10 0.106439E+11 0.190725E+10
September 0.591979E+10 0.305577E+10 0.286402E+10 0.653546E+10 0.265918E+10
October 0.438871E+10 0.222852E+10 0.216019E+10 0.394239E+10 0.404758E+10
November 0.269175E+10 0.125670E+10 0.143506E+10 0.173099E+10 0.548740E+10
December 0.205150E+10 0.881125E+09 0.117038E+10 0.930642E+09 0.785207E+10
           
Annual Sum or Average 0.677252E+11 0.340425E+11 0.336827E+11 0.677818E+11 0.537433E+11
Minimum of Months 0.205150E+10 0.881125E+09 0.117038E+10 0.930642E+09 0.169006E+10
Maximum of Months 0.995035E+10 0.562520E+10 0.445353E+10 0.125724E+11 0.921462E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.113787E+11 0.812691E+10 0.325181E+10 0.999006E+10 0.130426E+11
February 0.130883E+11 0.941360E+10 0.367471E+10 0.127444E+11 0.894980E+10
March 0.129527E+11 0.727366E+10 0.567907E+10 0.125573E+11 0.887065E+10
April 0.100760E+11 0.481940E+10 0.525656E+10 0.102062E+11 0.641459E+10
May 0.925064E+10 0.307239E+10 0.617825E+10 0.954239E+10 0.519532E+10
June 0.889494E+10 0.259419E+10 0.630075E+10 0.106455E+11 0.343940E+10
July 0.990930E+10 0.366046E+10 0.624883E+10 0.133902E+11 0.281787E+10
August 0.117765E+11 0.593752E+10 0.583902E+10 0.154218E+11 0.319929E+10
September 0.126403E+11 0.774510E+10 0.489516E+10 0.152108E+11 0.442079E+10
October 0.136552E+11 0.944240E+10 0.421281E+10 0.149293E+11 0.645869E+10
November 0.120479E+11 0.872702E+10 0.332089E+10 0.118817E+11 0.806301E+10
December 0.108205E+11 0.781351E+10 0.300701E+10 0.975821E+10 0.110999E+11
           
Annual Sum or Average 0.136491E+12 0.786262E+11 0.578649E+11 0.146278E+12 0.819718E+11
Minimum of Months 0.889494E+10 0.259419E+10 0.300701E+10 0.954239E+10 0.281787E+10
Maximum of Months 0.136552E+11 0.944240E+10 0.630075E+10 0.154218E+11 0.130426E+11



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.223834E+10 0.902069E+09 0.133627E+10 0.104690E+10 0.975818E+10
February 0.345079E+10 0.169624E+10 0.175455E+10 0.246178E+10 0.647291E+10
March 0.488933E+10 0.179152E+10 0.309780E+10 0.362210E+10 0.603190E+10
April 0.617714E+10 0.273676E+10 0.344038E+10 0.573403E+10 0.430323E+10
May 0.789537E+10 0.360071E+10 0.429466E+10 0.811144E+10 0.350171E+10
June 0.831276E+10 0.381836E+10 0.449440E+10 0.967724E+10 0.233485E+10
July 0.879935E+10 0.444644E+10 0.435291E+10 0.112349E+11 0.202367E+10
August 0.747184E+10 0.366702E+10 0.380482E+10 0.925223E+10 0.218518E+10
September 0.581673E+10 0.294070E+10 0.287603E+10 0.655812E+10 0.296628E+10
October 0.429595E+10 0.213442E+10 0.216152E+10 0.398451E+10 0.440586E+10
November 0.294302E+10 0.145999E+10 0.148303E+10 0.215712E+10 0.586361E+10
December 0.204419E+10 0.862794E+09 0.118139E+10 0.987624E+09 0.825883E+10
           
Annual Sum or Average 0.643348E+11 0.300570E+11 0.342778E+11 0.648280E+11 0.581062E+11
Minimum of Months 0.204419E+10 0.862794E+09 0.118139E+10 0.987624E+09 0.202367E+10
Maximum of Months 0.879935E+10 0.444644E+10 0.449440E+10 0.112349E+11 0.975818E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.161426E+10 0.00 0.161426E+10 49645873.01 0.146127E+11
February 0.205866E+10 0.00 0.205866E+10 0.340649E+09 0.965221E+10
March 0.370251E+10 0.00 0.370251E+10 0.116120E+10 0.849767E+10
April 0.408546E+10 23841848.37 0.406162E+10 0.204886E+10 0.573501E+10
May 0.554403E+10 0.328518E+09 0.521551E+10 0.384783E+10 0.446983E+10
June 0.624747E+10 0.718093E+09 0.552937E+10 0.610535E+10 0.286057E+10
July 0.589765E+10 0.552386E+09 0.534526E+10 0.696595E+10 0.247983E+10
August 0.472582E+10 0.126674E+09 0.459914E+10 0.505334E+10 0.280939E+10
September 0.342514E+10 1229125.19 0.342391E+10 0.286448E+10 0.401170E+10
October 0.258172E+10 0.00 0.258172E+10 0.117748E+10 0.593584E+10
November 0.169846E+10 0.00 0.169846E+10 0.282933E+09 0.841724E+10
December 0.135365E+10 0.00 0.135365E+10 17516774.46 0.123292E+11
           
Annual Sum or Average 0.429348E+11 0.175074E+10 0.411841E+11 0.299152E+11 0.818112E+11
Minimum of Months 0.135365E+10 0.00 0.135365E+10 17516774.46 0.247983E+10
Maximum of Months 0.624747E+10 0.718093E+09 0.552937E+10 0.696595E+10 0.146127E+11



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.247116E+10 0.113292E+10 0.133823E+10 0.123716E+10 0.897974E+10
February 0.349106E+10 0.173323E+10 0.175783E+10 0.251777E+10 0.593003E+10
March 0.519699E+10 0.215037E+10 0.304662E+10 0.403221E+10 0.534690E+10
April 0.641695E+10 0.318019E+10 0.323676E+10 0.597928E+10 0.368945E+10
May 0.732463E+10 0.325900E+10 0.406563E+10 0.730461E+10 0.301317E+10
June 0.917496E+10 0.472143E+10 0.445353E+10 0.106385E+11 0.197440E+10
July 0.995035E+10 0.562520E+10 0.432515E+10 0.125410E+11 0.167033E+10
August 0.864730E+10 0.481801E+10 0.382929E+10 0.106240E+11 0.187056E+10
September 0.591979E+10 0.305577E+10 0.286402E+10 0.655627E+10 0.254992E+10
October 0.438871E+10 0.222852E+10 0.216019E+10 0.404832E+10 0.375340E+10
November 0.269175E+10 0.125670E+10 0.143506E+10 0.181860E+10 0.514232E+10
December 0.205150E+10 0.881125E+09 0.117038E+10 0.964940E+09 0.755611E+10
           
Annual Sum or Average 0.677252E+11 0.340425E+11 0.336827E+11 0.682627E+11 0.514763E+11
Minimum of Months 0.205150E+10 0.881125E+09 0.117038E+10 0.964940E+09 0.167033E+10
Maximum of Months 0.995035E+10 0.562520E+10 0.445353E+10 0.125410E+11 0.897974E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.113787E+11 0.812691E+10 0.325181E+10 0.100843E+11 0.126179E+11
February 0.130883E+11 0.941360E+10 0.367471E+10 0.128534E+11 0.853748E+10
March 0.129527E+11 0.727366E+10 0.567907E+10 0.126651E+11 0.841790E+10
April 0.100760E+11 0.481940E+10 0.525656E+10 0.102981E+11 0.602444E+10
May 0.925064E+10 0.307239E+10 0.617825E+10 0.958160E+10 0.493359E+10
June 0.889494E+10 0.259419E+10 0.630075E+10 0.106367E+11 0.334216E+10
July 0.990930E+10 0.366046E+10 0.624883E+10 0.133593E+11 0.276087E+10
August 0.117765E+11 0.593752E+10 0.583902E+10 0.153935E+11 0.311312E+10
September 0.126403E+11 0.774510E+10 0.489516E+10 0.152221E+11 0.422168E+10
October 0.136552E+11 0.944240E+10 0.421281E+10 0.150506E+11 0.599964E+10
November 0.120479E+11 0.872702E+10 0.332089E+10 0.120551E+11 0.752427E+10
December 0.108205E+11 0.781351E+10 0.300701E+10 0.988835E+10 0.106078E+11
           
Annual Sum or Average 0.136491E+12 0.786262E+11 0.578649E+11 0.147088E+12 0.781008E+11
Minimum of Months 0.889494E+10 0.259419E+10 0.300701E+10 0.958160E+10 0.276087E+10
Maximum of Months 0.136552E+11 0.944240E+10 0.630075E+10 0.153935E+11 0.126179E+11



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.223834E+10 0.902069E+09 0.133627E+10 0.106621E+10 0.951577E+10
February 0.345079E+10 0.169624E+10 0.175455E+10 0.249445E+10 0.623581E+10
March 0.488933E+10 0.179152E+10 0.309780E+10 0.366181E+10 0.577203E+10
April 0.617714E+10 0.273676E+10 0.344038E+10 0.578330E+10 0.407461E+10
May 0.789537E+10 0.360071E+10 0.429466E+10 0.812493E+10 0.333921E+10
June 0.831276E+10 0.381836E+10 0.449440E+10 0.966599E+10 0.227562E+10
July 0.879935E+10 0.444644E+10 0.435291E+10 0.112136E+11 0.198739E+10
August 0.747184E+10 0.366702E+10 0.380482E+10 0.924027E+10 0.213103E+10
September 0.581673E+10 0.294070E+10 0.287603E+10 0.657055E+10 0.284228E+10
October 0.429595E+10 0.213442E+10 0.216152E+10 0.404768E+10 0.412537E+10
November 0.294302E+10 0.145999E+10 0.148303E+10 0.220551E+10 0.554038E+10
December 0.204419E+10 0.862794E+09 0.118139E+10 0.100735E+10 0.798254E+10
           
Annual Sum or Average 0.643348E+11 0.300570E+11 0.342778E+11 0.650817E+11 0.558221E+11
Minimum of Months 0.204419E+10 0.862794E+09 0.118139E+10 0.100735E+10 0.198739E+10
Maximum of Months 0.879935E+10 0.444644E+10 0.449440E+10 0.112136E+11 0.951577E+10



Table of Contents

Report: WindowZoneSummaryMonthly

For: BASEMENT

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: CORE_BOTTOM

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: CORE_MID

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: CORE_TOP

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 3.72 5965.47 602.70 0.00 602.70 0.00 0.00
February 64.48 4522.96 850.97 0.00 850.97 0.00 0.00
March 308.37 3689.58 1382.36 0.00 1382.36 0.00 0.00
April 647.35 2663.22 1576.19 9.20 1566.99 0.00 0.00
May 1351.64 1916.27 2069.91 122.66 1947.26 0.00 0.00
June 2308.19 1195.52 2410.30 277.04 2133.25 0.00 0.00
July 2568.90 983.87 2201.94 206.24 1995.70 0.00 0.00
August 1846.20 1147.64 1764.42 47.29 1717.13 0.00 0.00
September 1039.28 1772.14 1321.43 0.47 1320.96 0.00 0.00
October 314.95 2712.86 963.91 0.00 963.91 0.00 0.00
November 49.39 3933.59 655.27 0.00 655.27 0.00 0.00
December 1.19 5312.98 505.40 0.00 505.40 0.00 0.00
               
Annual Sum or Average 880.48 2978.54 1361.46 55.52 1305.94 0.00 0.00
Minimum of Months 1.19 983.87 505.40 0.00 505.40 0.00 0.00
Maximum of Months 2568.90 5965.47 2410.30 277.04 2133.25 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 424.26 3627.12 922.63 422.99 499.64 0.00 0.00
February 974.14 2719.60 1443.07 716.45 726.62 0.00 0.00
March 1440.52 2242.97 1940.34 802.86 1137.48 0.00 0.00
April 2260.51 1622.20 2475.68 1226.93 1248.75 0.00 0.00
May 2714.77 1257.90 2734.72 1216.78 1517.94 0.00 0.00
June 4128.42 800.01 3539.73 1821.55 1718.19 0.00 0.00
July 4719.56 632.20 3715.05 2100.22 1614.83 0.00 0.00
August 3996.28 711.26 3228.55 1798.85 1429.70 0.00 0.00
September 2522.64 1083.28 2283.88 1178.93 1104.95 0.00 0.00
October 1443.66 1639.19 1638.56 832.04 806.53 0.00 0.00
November 630.00 2314.79 1038.49 484.84 553.65 0.00 0.00
December 319.88 3173.55 765.95 328.98 436.97 0.00 0.00
               
Annual Sum or Average 2137.95 1815.25 2147.56 1079.48 1068.08 0.00 0.00
Minimum of Months 319.88 632.20 765.95 328.98 436.97 0.00 0.00
Maximum of Months 4719.56 3627.12 3715.05 2100.22 1718.19 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 3738.68 4987.38 4248.34 3034.25 1214.09 0.00 0.00
February 5295.95 3812.98 5410.20 3891.22 1518.98 0.00 0.00
March 4708.57 3432.30 4836.01 2715.68 2120.33 0.00 0.00
April 3940.86 2603.56 3887.34 1859.34 2028.00 0.00 0.00
May 3574.58 2017.38 3453.81 1147.10 2306.70 0.00 0.00
June 4116.53 1371.48 3431.70 1000.85 2430.85 0.00 0.00
July 5010.42 1075.63 3699.72 1366.67 2333.06 0.00 0.00
August 5780.21 1219.74 4396.87 2216.82 2180.05 0.00 0.00
September 5916.66 1750.07 4876.66 2988.09 1888.57 0.00 0.00
October 5608.10 2498.36 5098.29 3525.40 1572.89 0.00 0.00
November 4585.97 3247.78 4648.13 3366.92 1281.21 0.00 0.00
December 3621.44 4350.61 4039.93 2917.24 1122.69 0.00 0.00
               
Annual Sum or Average 4653.12 2693.08 4328.12 2493.23 1834.89 0.00 0.00
Minimum of Months 3574.58 1075.63 3431.70 1000.85 1122.69 0.00 0.00
Maximum of Months 5916.66 4987.38 5410.20 3891.22 2430.85 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 368.83 3901.88 835.70 336.80 498.91 0.00 0.00
February 962.00 2973.90 1426.42 701.16 725.26 0.00 0.00
March 1272.64 2571.22 1825.47 668.88 1156.59 0.00 0.00
April 2117.86 1955.94 2383.17 1055.85 1327.31 0.00 0.00
May 2995.00 1427.20 2947.80 1344.36 1603.45 0.00 0.00
June 3693.64 988.94 3207.10 1473.14 1733.96 0.00 0.00
July 4150.45 833.53 3285.32 1660.12 1625.20 0.00 0.00
August 3394.31 934.37 2789.68 1369.11 1420.56 0.00 0.00
September 2498.44 1257.13 2244.12 1134.54 1109.58 0.00 0.00
October 1418.68 1893.53 1603.93 796.91 807.02 0.00 0.00
November 767.80 2651.37 1135.43 563.27 572.16 0.00 0.00
December 323.88 3593.98 763.22 322.13 441.08 0.00 0.00
               
Annual Sum or Average 2002.48 2078.62 2040.05 953.11 1086.95 0.00 0.00
Minimum of Months 323.88 833.53 763.22 322.13 441.08 0.00 0.00
Maximum of Months 4150.45 3901.88 3285.32 1660.12 1733.96 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 13.23 5604.05 602.69 0.00 602.69 0.00 0.00
February 115.82 4157.24 850.97 0.00 850.97 0.00 0.00
March 394.42 3347.07 1382.36 0.00 1382.36 0.00 0.00
April 739.36 2376.23 1576.18 9.20 1566.98 0.00 0.00
May 1406.81 1768.68 2069.90 122.65 1947.25 0.00 0.00
June 2344.72 1136.48 2410.29 277.04 2133.25 0.00 0.00
July 2603.97 942.51 2201.93 206.24 1995.69 0.00 0.00
August 1884.60 1082.29 1764.42 47.29 1717.12 0.00 0.00
September 1082.17 1638.96 1321.43 0.47 1320.95 0.00 0.00
October 384.89 2416.79 963.90 0.00 963.90 0.00 0.00
November 85.52 3475.44 655.27 0.00 655.27 0.00 0.00
December 5.37 4783.41 505.39 0.00 505.39 0.00 0.00
               
Annual Sum or Average 926.82 2721.93 1361.45 55.52 1305.94 0.00 0.00
Minimum of Months 5.37 942.51 505.39 0.00 505.39 0.00 0.00
Maximum of Months 2603.97 5604.05 2410.29 277.04 2133.25 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 448.91 3440.35 922.62 422.99 499.64 0.00 0.00
February 1010.37 2551.21 1443.07 716.45 726.62 0.00 0.00
March 1473.27 2097.69 1940.33 802.86 1137.48 0.00 0.00
April 2277.67 1512.76 2475.67 1226.93 1248.75 0.00 0.00
May 2717.26 1180.19 2734.70 1216.77 1517.93 0.00 0.00
June 4109.45 776.49 3539.72 1821.54 1718.18 0.00 0.00
July 4694.01 631.00 3715.04 2100.21 1614.83 0.00 0.00
August 3973.97 712.08 3228.53 1798.84 1429.69 0.00 0.00
September 2521.40 1025.92 2283.87 1178.92 1104.94 0.00 0.00
October 1471.92 1511.19 1638.56 832.03 806.52 0.00 0.00
November 667.82 2117.05 1038.49 484.84 553.65 0.00 0.00
December 347.46 2931.63 765.94 328.97 436.97 0.00 0.00
               
Annual Sum or Average 2149.35 1704.19 2147.55 1079.48 1068.07 0.00 0.00
Minimum of Months 347.46 631.00 765.94 328.97 436.97 0.00 0.00
Maximum of Months 4694.01 3440.35 3715.04 2100.21 1718.18 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 3729.86 4869.53 4248.33 3034.24 1214.09 0.00 0.00
February 5268.04 3699.49 5410.18 3891.20 1518.98 0.00 0.00
March 4688.36 3311.92 4835.99 2715.67 2120.32 0.00 0.00
April 3937.57 2474.77 3887.33 1859.33 2027.99 0.00 0.00
May 3562.72 1939.71 3453.79 1147.10 2306.69 0.00 0.00
June 4107.05 1326.93 3431.69 1000.84 2430.85 0.00 0.00
July 4999.33 1052.07 3699.71 1366.66 2333.05 0.00 0.00
August 5757.85 1194.48 4396.86 2216.82 2180.04 0.00 0.00
September 5868.35 1705.55 4876.64 2988.08 1888.57 0.00 0.00
October 5573.95 2411.40 5098.27 3525.39 1572.88 0.00 0.00
November 4584.00 3110.73 4648.11 3366.91 1281.21 0.00 0.00
December 3643.30 4144.21 4039.92 2917.23 1122.69 0.00 0.00
               
Annual Sum or Average 4638.44 2599.31 4328.10 2493.22 1834.88 0.00 0.00
Minimum of Months 3562.72 1052.07 3431.69 1000.84 1122.69 0.00 0.00
Maximum of Months 5868.35 4869.53 5410.18 3891.20 2430.85 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 390.87 3643.29 835.70 336.79 498.91 0.00 0.00
February 1017.60 2675.64 1426.42 701.16 725.26 0.00 0.00
March 1352.34 2252.05 1825.47 668.88 1156.59 0.00 0.00
April 2212.20 1660.20 2383.16 1055.85 1327.31 0.00 0.00
May 3028.46 1307.39 2947.79 1344.35 1603.44 0.00 0.00
June 3733.50 900.79 3207.09 1473.13 1733.95 0.00 0.00
July 4194.63 755.55 3285.30 1660.11 1625.19 0.00 0.00
August 3454.39 815.85 2789.66 1369.11 1420.56 0.00 0.00
September 2530.14 1144.40 2244.11 1134.53 1109.58 0.00 0.00
October 1487.65 1644.96 1603.92 796.90 807.02 0.00 0.00
November 832.22 2262.20 1135.42 563.27 572.16 0.00 0.00
December 368.74 3083.49 763.21 322.13 441.08 0.00 0.00
               
Annual Sum or Average 2055.68 1842.54 2040.04 953.10 1086.94 0.00 0.00
Minimum of Months 368.74 755.55 763.21 322.13 441.08 0.00 0.00
Maximum of Months 4194.63 3643.29 3285.30 1660.11 1733.95 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 18.54 5455.76 602.69 0.00 602.69 0.00 0.00
February 140.81 3989.84 850.97 0.00 850.97 0.00 0.00
March 433.54 3172.67 1382.36 0.00 1382.36 0.00 0.00
April 790.45 2212.58 1576.18 9.20 1566.98 0.00 0.00
May 1436.62 1668.84 2069.90 122.65 1947.25 0.00 0.00
June 2355.46 1103.62 2410.29 277.04 2133.25 0.00 0.00
July 2600.79 925.86 2201.93 206.24 1995.69 0.00 0.00
August 1886.70 1048.91 1764.42 47.29 1717.12 0.00 0.00
September 1105.12 1547.72 1321.43 0.47 1320.95 0.00 0.00
October 439.62 2216.19 963.90 0.00 963.90 0.00 0.00
November 109.16 3247.39 655.27 0.00 655.27 0.00 0.00
December 6.54 4603.18 505.39 0.00 505.39 0.00 0.00
               
Annual Sum or Average 948.61 2594.22 1361.45 55.52 1305.94 0.00 0.00
Minimum of Months 6.54 925.86 505.39 0.00 505.39 0.00 0.00
Maximum of Months 2600.79 5455.76 2410.29 277.04 2133.25 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 461.90 3352.65 922.62 422.99 499.64 0.00 0.00
February 1040.74 2451.24 1443.07 716.45 726.62 0.00 0.00
March 1505.45 1996.30 1940.33 802.86 1137.48 0.00 0.00
April 2306.82 1423.40 2475.67 1226.93 1248.75 0.00 0.00
May 2727.23 1124.99 2734.70 1216.77 1517.93 0.00 0.00
June 4104.35 761.73 3539.72 1821.54 1718.18 0.00 0.00
July 4682.28 623.63 3715.04 2100.21 1614.83 0.00 0.00
August 3966.56 698.39 3228.53 1798.84 1429.69 0.00 0.00
September 2529.42 983.77 2283.87 1178.92 1104.94 0.00 0.00
October 1511.47 1401.36 1638.56 832.03 806.52 0.00 0.00
November 701.62 1983.92 1038.49 484.84 553.65 0.00 0.00
December 360.27 2821.13 765.94 328.97 436.97 0.00 0.00
               
Annual Sum or Average 2164.60 1632.30 2147.55 1079.48 1068.07 0.00 0.00
Minimum of Months 360.27 623.63 765.94 328.97 436.97 0.00 0.00
Maximum of Months 4682.28 3352.65 3715.04 2100.21 1718.18 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 3765.06 4710.99 4248.33 3034.24 1214.09 0.00 0.00
February 5313.07 3529.05 5410.18 3891.20 1518.98 0.00 0.00
March 4728.59 3142.89 4835.99 2715.67 2120.32 0.00 0.00
April 3973.02 2324.24 3887.33 1859.33 2027.99 0.00 0.00
May 3577.36 1841.99 3453.79 1147.10 2306.69 0.00 0.00
June 4103.66 1289.41 3431.69 1000.84 2430.85 0.00 0.00
July 4987.78 1030.79 3699.71 1366.66 2333.05 0.00 0.00
August 5747.27 1162.31 4396.86 2216.82 2180.04 0.00 0.00
September 5872.71 1628.74 4876.64 2988.08 1888.57 0.00 0.00
October 5619.24 2240.01 5098.27 3525.39 1572.88 0.00 0.00
November 4650.88 2902.88 4648.11 3366.91 1281.21 0.00 0.00
December 3691.89 3960.48 4039.92 2917.23 1122.69 0.00 0.00
               
Annual Sum or Average 4664.13 2476.56 4328.10 2493.22 1834.88 0.00 0.00
Minimum of Months 3577.36 1030.79 3431.69 1000.84 1122.69 0.00 0.00
Maximum of Months 5872.71 4710.99 5410.18 3891.20 2430.85 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 398.08 3552.78 835.70 336.79 498.91 0.00 0.00
February 1031.11 2577.63 1426.42 701.16 725.26 0.00 0.00
March 1367.16 2155.03 1825.47 668.88 1156.59 0.00 0.00
April 2231.21 1572.00 2383.16 1055.85 1327.31 0.00 0.00
May 3033.50 1246.72 2947.79 1344.35 1603.44 0.00 0.00
June 3729.16 877.94 3207.09 1473.13 1733.95 0.00 0.00
July 4186.69 742.01 3285.30 1660.11 1625.19 0.00 0.00
August 3449.92 795.63 2789.66 1369.11 1420.56 0.00 0.00
September 2534.93 1096.56 2244.11 1134.53 1109.58 0.00 0.00
October 1511.23 1540.24 1603.92 796.90 807.02 0.00 0.00
November 850.89 2137.49 1135.42 563.27 572.16 0.00 0.00
December 376.10 2980.34 763.21 322.13 441.08 0.00 0.00
               
Annual Sum or Average 2063.73 1770.11 2040.04 953.10 1086.94 0.00 0.00
Minimum of Months 376.10 742.01 763.21 322.13 441.08 0.00 0.00
Maximum of Months 4186.69 3552.78 3285.30 1660.11 1733.95 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: GROUNDFLOOR_PLENUM

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: MIDFLOOR_PLENUM

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: TOPFLOOR_PLENUM

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: DATACENTER_MID_ZN_6

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: BASEMENT

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: CORE_BOTTOM

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: CORE_MID

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: CORE_TOP

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 9968052.98 0.159779E+11 0.161426E+10 0.00 0.161426E+10 0.00 0.00
February 0.155995E+09 0.109420E+11 0.205867E+10 0.00 0.205867E+10 0.00 0.00
March 0.825940E+09 0.988218E+10 0.370252E+10 0.00 0.370252E+10 0.00 0.00
April 0.167793E+10 0.690308E+10 0.408548E+10 23841933.03 0.406164E+10 0.00 0.00
May 0.362023E+10 0.513253E+10 0.554405E+10 0.328519E+09 0.521553E+10 0.00 0.00
June 0.598283E+10 0.309879E+10 0.624749E+10 0.718096E+09 0.552939E+10 0.00 0.00
July 0.688054E+10 0.263521E+10 0.589767E+10 0.552388E+09 0.534528E+10 0.00 0.00
August 0.494487E+10 0.307385E+10 0.472583E+10 0.126674E+09 0.459916E+10 0.00 0.00
September 0.269382E+10 0.459338E+10 0.342515E+10 1229129.56 0.342392E+10 0.00 0.00
October 0.843563E+09 0.726614E+10 0.258173E+10 0.00 0.258173E+10 0.00 0.00
November 0.128011E+09 0.101959E+11 0.169847E+10 0.00 0.169847E+10 0.00 0.00
December 3175092.70 0.142303E+11 0.135365E+10 0.00 0.135365E+10 0.00 0.00
               
Annual Sum or Average 0.277669E+11 0.939311E+11 0.429350E+11 0.175075E+10 0.411842E+11 0.00 0.00
Minimum of Months 3175092.70 0.263521E+10 0.135365E+10 0.00 0.135365E+10 0.00 0.00
Maximum of Months 0.688054E+10 0.159779E+11 0.624749E+10 0.718096E+09 0.552939E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.113634E+10 0.971488E+10 0.247117E+10 0.113293E+10 0.133824E+10 0.00 0.00
February 0.235665E+10 0.657925E+10 0.349108E+10 0.173324E+10 0.175784E+10 0.00 0.00
March 0.385828E+10 0.600758E+10 0.519701E+10 0.215038E+10 0.304663E+10 0.00 0.00
April 0.585924E+10 0.420474E+10 0.641697E+10 0.318021E+10 0.323677E+10 0.00 0.00
May 0.727124E+10 0.336916E+10 0.732466E+10 0.325902E+10 0.406565E+10 0.00 0.00
June 0.107009E+11 0.207363E+10 0.917499E+10 0.472145E+10 0.445355E+10 0.00 0.00
July 0.126409E+11 0.169328E+10 0.995039E+10 0.562522E+10 0.432517E+10 0.00 0.00
August 0.107036E+11 0.190505E+10 0.864734E+10 0.481803E+10 0.382931E+10 0.00 0.00
September 0.653868E+10 0.280787E+10 0.591981E+10 0.305578E+10 0.286403E+10 0.00 0.00
October 0.386670E+10 0.439040E+10 0.438873E+10 0.222853E+10 0.216020E+10 0.00 0.00
November 0.163295E+10 0.599994E+10 0.269177E+10 0.125670E+10 0.143507E+10 0.00 0.00
December 0.856775E+09 0.850003E+10 0.205151E+10 0.881129E+09 0.117038E+10 0.00 0.00
               
Annual Sum or Average 0.674222E+11 0.572458E+11 0.677254E+11 0.340426E+11 0.336828E+11 0.00 0.00
Minimum of Months 0.856775E+09 0.169328E+10 0.205151E+10 0.881129E+09 0.117038E+10 0.00 0.00
Maximum of Months 0.126409E+11 0.971488E+10 0.995039E+10 0.562522E+10 0.445355E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.100137E+11 0.133582E+11 0.113788E+11 0.812693E+10 0.325182E+10 0.00 0.00
February 0.128120E+11 0.922436E+10 0.130884E+11 0.941363E+10 0.367472E+10 0.00 0.00
March 0.126114E+11 0.919307E+10 0.129528E+11 0.727368E+10 0.567909E+10 0.00 0.00
April 0.102147E+11 0.674843E+10 0.100760E+11 0.481941E+10 0.525658E+10 0.00 0.00
May 0.957416E+10 0.540334E+10 0.925067E+10 0.307240E+10 0.617827E+10 0.00 0.00
June 0.106700E+11 0.355487E+10 0.889497E+10 0.259420E+10 0.630078E+10 0.00 0.00
July 0.134199E+11 0.288096E+10 0.990933E+10 0.366048E+10 0.624886E+10 0.00 0.00
August 0.154817E+11 0.326696E+10 0.117766E+11 0.593754E+10 0.583905E+10 0.00 0.00
September 0.153360E+11 0.453618E+10 0.126403E+11 0.774513E+10 0.489518E+10 0.00 0.00
October 0.150207E+11 0.669160E+10 0.136553E+11 0.944244E+10 0.421282E+10 0.00 0.00
November 0.118868E+11 0.841824E+10 0.120480E+11 0.872705E+10 0.332090E+10 0.00 0.00
December 0.969966E+10 0.116527E+11 0.108206E+11 0.781354E+10 0.300702E+10 0.00 0.00
               
Annual Sum or Average 0.146741E+12 0.849289E+11 0.136492E+12 0.786264E+11 0.578651E+11 0.00 0.00
Minimum of Months 0.957416E+10 0.288096E+10 0.889497E+10 0.259420E+10 0.300702E+10 0.00 0.00
Maximum of Months 0.154817E+11 0.133582E+11 0.136553E+11 0.944244E+10 0.630078E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.987878E+09 0.104508E+11 0.223835E+10 0.902072E+09 0.133628E+10 0.00 0.00
February 0.232726E+10 0.719446E+10 0.345080E+10 0.169624E+10 0.175456E+10 0.00 0.00
March 0.340864E+10 0.688675E+10 0.488935E+10 0.179153E+10 0.309782E+10 0.00 0.00
April 0.548950E+10 0.506980E+10 0.617716E+10 0.273677E+10 0.344039E+10 0.00 0.00
May 0.802182E+10 0.382261E+10 0.789540E+10 0.360072E+10 0.429468E+10 0.00 0.00
June 0.957391E+10 0.256333E+10 0.831280E+10 0.381838E+10 0.449442E+10 0.00 0.00
July 0.111166E+11 0.223253E+10 0.879939E+10 0.444646E+10 0.435293E+10 0.00 0.00
August 0.909131E+10 0.250260E+10 0.747187E+10 0.366703E+10 0.380483E+10 0.00 0.00
September 0.647595E+10 0.325849E+10 0.581676E+10 0.294072E+10 0.287604E+10 0.00 0.00
October 0.379980E+10 0.507163E+10 0.429596E+10 0.213443E+10 0.216153E+10 0.00 0.00
November 0.199013E+10 0.687235E+10 0.294303E+10 0.146000E+10 0.148304E+10 0.00 0.00
December 0.867470E+09 0.962612E+10 0.204420E+10 0.862798E+09 0.118140E+10 0.00 0.00
               
Annual Sum or Average 0.631502E+11 0.655514E+11 0.643351E+11 0.300572E+11 0.342779E+11 0.00 0.00
Minimum of Months 0.867470E+09 0.223253E+10 0.204420E+10 0.862798E+09 0.118140E+10 0.00 0.00
Maximum of Months 0.111166E+11 0.104508E+11 0.879939E+10 0.444646E+10 0.449442E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 35444382.29 0.150099E+11 0.161426E+10 0.00 0.161426E+10 0.00 0.00
February 0.280202E+09 0.100572E+11 0.205866E+10 0.00 0.205866E+10 0.00 0.00
March 0.105642E+10 0.896479E+10 0.370251E+10 0.00 0.370251E+10 0.00 0.00
April 0.191643E+10 0.615918E+10 0.408546E+10 23841848.37 0.406162E+10 0.00 0.00
May 0.376801E+10 0.473724E+10 0.554403E+10 0.328518E+09 0.521551E+10 0.00 0.00
June 0.607753E+10 0.294575E+10 0.624747E+10 0.718093E+09 0.552937E+10 0.00 0.00
July 0.697447E+10 0.252443E+10 0.589765E+10 0.552386E+09 0.534526E+10 0.00 0.00
August 0.504771E+10 0.289880E+10 0.472582E+10 0.126674E+09 0.459914E+10 0.00 0.00
September 0.280500E+10 0.424818E+10 0.342514E+10 1229125.19 0.342391E+10 0.00 0.00
October 0.103089E+10 0.647314E+10 0.258172E+10 0.00 0.258172E+10 0.00 0.00
November 0.221677E+09 0.900835E+10 0.169846E+10 0.00 0.169846E+10 0.00 0.00
December 14393576.88 0.128119E+11 0.135365E+10 0.00 0.135365E+10 0.00 0.00
               
Annual Sum or Average 0.292282E+11 0.858388E+11 0.429348E+11 0.175074E+10 0.411841E+11 0.00 0.00
Minimum of Months 14393576.88 0.252443E+10 0.135365E+10 0.00 0.135365E+10 0.00 0.00
Maximum of Months 0.697447E+10 0.150099E+11 0.624747E+10 0.718093E+09 0.552937E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.120235E+10 0.921462E+10 0.247116E+10 0.113292E+10 0.133823E+10 0.00 0.00
February 0.244430E+10 0.617189E+10 0.349106E+10 0.173323E+10 0.175783E+10 0.00 0.00
March 0.394601E+10 0.561845E+10 0.519699E+10 0.215037E+10 0.304662E+10 0.00 0.00
April 0.590371E+10 0.392108E+10 0.641695E+10 0.318019E+10 0.323676E+10 0.00 0.00
May 0.727791E+10 0.316102E+10 0.732463E+10 0.325900E+10 0.406563E+10 0.00 0.00
June 0.106517E+11 0.201267E+10 0.917496E+10 0.472143E+10 0.445353E+10 0.00 0.00
July 0.125724E+11 0.169006E+10 0.995035E+10 0.562520E+10 0.432515E+10 0.00 0.00
August 0.106439E+11 0.190725E+10 0.864730E+10 0.481801E+10 0.382929E+10 0.00 0.00
September 0.653546E+10 0.265918E+10 0.591979E+10 0.305577E+10 0.286402E+10 0.00 0.00
October 0.394239E+10 0.404758E+10 0.438871E+10 0.222852E+10 0.216019E+10 0.00 0.00
November 0.173099E+10 0.548740E+10 0.269175E+10 0.125670E+10 0.143506E+10 0.00 0.00
December 0.930642E+09 0.785207E+10 0.205150E+10 0.881125E+09 0.117038E+10 0.00 0.00
               
Annual Sum or Average 0.677818E+11 0.537433E+11 0.677252E+11 0.340425E+11 0.336827E+11 0.00 0.00
Minimum of Months 0.930642E+09 0.169006E+10 0.205150E+10 0.881125E+09 0.117038E+10 0.00 0.00
Maximum of Months 0.125724E+11 0.921462E+10 0.995035E+10 0.562520E+10 0.445353E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.999006E+10 0.130426E+11 0.113787E+11 0.812691E+10 0.325181E+10 0.00 0.00
February 0.127444E+11 0.894980E+10 0.130883E+11 0.941360E+10 0.367471E+10 0.00 0.00
March 0.125573E+11 0.887065E+10 0.129527E+11 0.727366E+10 0.567907E+10 0.00 0.00
April 0.102062E+11 0.641459E+10 0.100760E+11 0.481940E+10 0.525656E+10 0.00 0.00
May 0.954239E+10 0.519532E+10 0.925064E+10 0.307239E+10 0.617825E+10 0.00 0.00
June 0.106455E+11 0.343940E+10 0.889494E+10 0.259419E+10 0.630075E+10 0.00 0.00
July 0.133902E+11 0.281787E+10 0.990930E+10 0.366046E+10 0.624883E+10 0.00 0.00
August 0.154218E+11 0.319929E+10 0.117765E+11 0.593752E+10 0.583902E+10 0.00 0.00
September 0.152108E+11 0.442079E+10 0.126403E+11 0.774510E+10 0.489516E+10 0.00 0.00
October 0.149293E+11 0.645869E+10 0.136552E+11 0.944240E+10 0.421281E+10 0.00 0.00
November 0.118817E+11 0.806301E+10 0.120479E+11 0.872702E+10 0.332089E+10 0.00 0.00
December 0.975821E+10 0.110999E+11 0.108205E+11 0.781351E+10 0.300701E+10 0.00 0.00
               
Annual Sum or Average 0.146278E+12 0.819718E+11 0.136491E+12 0.786262E+11 0.578649E+11 0.00 0.00
Minimum of Months 0.954239E+10 0.281787E+10 0.889494E+10 0.259419E+10 0.300701E+10 0.00 0.00
Maximum of Months 0.154218E+11 0.130426E+11 0.136552E+11 0.944240E+10 0.630075E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.104690E+10 0.975818E+10 0.223834E+10 0.902069E+09 0.133627E+10 0.00 0.00
February 0.246178E+10 0.647291E+10 0.345079E+10 0.169624E+10 0.175455E+10 0.00 0.00
March 0.362210E+10 0.603190E+10 0.488933E+10 0.179152E+10 0.309780E+10 0.00 0.00
April 0.573403E+10 0.430323E+10 0.617714E+10 0.273676E+10 0.344038E+10 0.00 0.00
May 0.811144E+10 0.350171E+10 0.789537E+10 0.360071E+10 0.429466E+10 0.00 0.00
June 0.967724E+10 0.233485E+10 0.831276E+10 0.381836E+10 0.449440E+10 0.00 0.00
July 0.112349E+11 0.202367E+10 0.879935E+10 0.444644E+10 0.435291E+10 0.00 0.00
August 0.925223E+10 0.218518E+10 0.747184E+10 0.366702E+10 0.380482E+10 0.00 0.00
September 0.655812E+10 0.296628E+10 0.581673E+10 0.294070E+10 0.287603E+10 0.00 0.00
October 0.398451E+10 0.440586E+10 0.429595E+10 0.213442E+10 0.216152E+10 0.00 0.00
November 0.215712E+10 0.586361E+10 0.294302E+10 0.145999E+10 0.148303E+10 0.00 0.00
December 0.987624E+09 0.825883E+10 0.204419E+10 0.862794E+09 0.118139E+10 0.00 0.00
               
Annual Sum or Average 0.648280E+11 0.581062E+11 0.643348E+11 0.300570E+11 0.342778E+11 0.00 0.00
Minimum of Months 0.987624E+09 0.202367E+10 0.204419E+10 0.862794E+09 0.118139E+10 0.00 0.00
Maximum of Months 0.112349E+11 0.975818E+10 0.879935E+10 0.444644E+10 0.449440E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 49645873.01 0.146127E+11 0.161426E+10 0.00 0.161426E+10 0.00 0.00
February 0.340649E+09 0.965221E+10 0.205866E+10 0.00 0.205866E+10 0.00 0.00
March 0.116120E+10 0.849767E+10 0.370251E+10 0.00 0.370251E+10 0.00 0.00
April 0.204886E+10 0.573501E+10 0.408546E+10 23841848.37 0.406162E+10 0.00 0.00
May 0.384783E+10 0.446983E+10 0.554403E+10 0.328518E+09 0.521551E+10 0.00 0.00
June 0.610535E+10 0.286057E+10 0.624747E+10 0.718093E+09 0.552937E+10 0.00 0.00
July 0.696595E+10 0.247983E+10 0.589765E+10 0.552386E+09 0.534526E+10 0.00 0.00
August 0.505334E+10 0.280939E+10 0.472582E+10 0.126674E+09 0.459914E+10 0.00 0.00
September 0.286448E+10 0.401170E+10 0.342514E+10 1229125.19 0.342391E+10 0.00 0.00
October 0.117748E+10 0.593584E+10 0.258172E+10 0.00 0.258172E+10 0.00 0.00
November 0.282933E+09 0.841724E+10 0.169846E+10 0.00 0.169846E+10 0.00 0.00
December 17516774.46 0.123292E+11 0.135365E+10 0.00 0.135365E+10 0.00 0.00
               
Annual Sum or Average 0.299152E+11 0.818112E+11 0.429348E+11 0.175074E+10 0.411841E+11 0.00 0.00
Minimum of Months 17516774.46 0.247983E+10 0.135365E+10 0.00 0.135365E+10 0.00 0.00
Maximum of Months 0.696595E+10 0.146127E+11 0.624747E+10 0.718093E+09 0.552937E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.123716E+10 0.897974E+10 0.247116E+10 0.113292E+10 0.133823E+10 0.00 0.00
February 0.251777E+10 0.593003E+10 0.349106E+10 0.173323E+10 0.175783E+10 0.00 0.00
March 0.403221E+10 0.534690E+10 0.519699E+10 0.215037E+10 0.304662E+10 0.00 0.00
April 0.597928E+10 0.368945E+10 0.641695E+10 0.318019E+10 0.323676E+10 0.00 0.00
May 0.730461E+10 0.301317E+10 0.732463E+10 0.325900E+10 0.406563E+10 0.00 0.00
June 0.106385E+11 0.197440E+10 0.917496E+10 0.472143E+10 0.445353E+10 0.00 0.00
July 0.125410E+11 0.167033E+10 0.995035E+10 0.562520E+10 0.432515E+10 0.00 0.00
August 0.106240E+11 0.187056E+10 0.864730E+10 0.481801E+10 0.382929E+10 0.00 0.00
September 0.655627E+10 0.254992E+10 0.591979E+10 0.305577E+10 0.286402E+10 0.00 0.00
October 0.404832E+10 0.375340E+10 0.438871E+10 0.222852E+10 0.216019E+10 0.00 0.00
November 0.181860E+10 0.514232E+10 0.269175E+10 0.125670E+10 0.143506E+10 0.00 0.00
December 0.964940E+09 0.755611E+10 0.205150E+10 0.881125E+09 0.117038E+10 0.00 0.00
               
Annual Sum or Average 0.682627E+11 0.514763E+11 0.677252E+11 0.340425E+11 0.336827E+11 0.00 0.00
Minimum of Months 0.964940E+09 0.167033E+10 0.205150E+10 0.881125E+09 0.117038E+10 0.00 0.00
Maximum of Months 0.125410E+11 0.897974E+10 0.995035E+10 0.562520E+10 0.445353E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.100843E+11 0.126179E+11 0.113787E+11 0.812691E+10 0.325181E+10 0.00 0.00
February 0.128534E+11 0.853748E+10 0.130883E+11 0.941360E+10 0.367471E+10 0.00 0.00
March 0.126651E+11 0.841790E+10 0.129527E+11 0.727366E+10 0.567907E+10 0.00 0.00
April 0.102981E+11 0.602444E+10 0.100760E+11 0.481940E+10 0.525656E+10 0.00 0.00
May 0.958160E+10 0.493359E+10 0.925064E+10 0.307239E+10 0.617825E+10 0.00 0.00
June 0.106367E+11 0.334216E+10 0.889494E+10 0.259419E+10 0.630075E+10 0.00 0.00
July 0.133593E+11 0.276087E+10 0.990930E+10 0.366046E+10 0.624883E+10 0.00 0.00
August 0.153935E+11 0.311312E+10 0.117765E+11 0.593752E+10 0.583902E+10 0.00 0.00
September 0.152221E+11 0.422168E+10 0.126403E+11 0.774510E+10 0.489516E+10 0.00 0.00
October 0.150506E+11 0.599964E+10 0.136552E+11 0.944240E+10 0.421281E+10 0.00 0.00
November 0.120551E+11 0.752427E+10 0.120479E+11 0.872702E+10 0.332089E+10 0.00 0.00
December 0.988835E+10 0.106078E+11 0.108205E+11 0.781351E+10 0.300701E+10 0.00 0.00
               
Annual Sum or Average 0.147088E+12 0.781008E+11 0.136491E+12 0.786262E+11 0.578649E+11 0.00 0.00
Minimum of Months 0.958160E+10 0.276087E+10 0.889494E+10 0.259419E+10 0.300701E+10 0.00 0.00
Maximum of Months 0.153935E+11 0.126179E+11 0.136552E+11 0.944240E+10 0.630075E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.106621E+10 0.951577E+10 0.223834E+10 0.902069E+09 0.133627E+10 0.00 0.00
February 0.249445E+10 0.623581E+10 0.345079E+10 0.169624E+10 0.175455E+10 0.00 0.00
March 0.366181E+10 0.577203E+10 0.488933E+10 0.179152E+10 0.309780E+10 0.00 0.00
April 0.578330E+10 0.407461E+10 0.617714E+10 0.273676E+10 0.344038E+10 0.00 0.00
May 0.812493E+10 0.333921E+10 0.789537E+10 0.360071E+10 0.429466E+10 0.00 0.00
June 0.966599E+10 0.227562E+10 0.831276E+10 0.381836E+10 0.449440E+10 0.00 0.00
July 0.112136E+11 0.198739E+10 0.879935E+10 0.444644E+10 0.435291E+10 0.00 0.00
August 0.924027E+10 0.213103E+10 0.747184E+10 0.366702E+10 0.380482E+10 0.00 0.00
September 0.657055E+10 0.284228E+10 0.581673E+10 0.294070E+10 0.287603E+10 0.00 0.00
October 0.404768E+10 0.412537E+10 0.429595E+10 0.213442E+10 0.216152E+10 0.00 0.00
November 0.220551E+10 0.554038E+10 0.294302E+10 0.145999E+10 0.148303E+10 0.00 0.00
December 0.100735E+10 0.798254E+10 0.204419E+10 0.862794E+09 0.118139E+10 0.00 0.00
               
Annual Sum or Average 0.650817E+11 0.558221E+11 0.643348E+11 0.300570E+11 0.342778E+11 0.00 0.00
Minimum of Months 0.100735E+10 0.198739E+10 0.204419E+10 0.862794E+09 0.118139E+10 0.00 0.00
Maximum of Months 0.112136E+11 0.951577E+10 0.879935E+10 0.444644E+10 0.449440E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: GROUNDFLOOR_PLENUM

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: MIDFLOOR_PLENUM

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: TOPFLOOR_PLENUM

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: DATACENTER_MID_ZN_6

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AverageOutdoorConditionsMonthly

For: Environment

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] SITE OUTDOOR AIR WETBULB TEMPERATURE [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] SITE WIND SPEED [m/s] SITE SKY TEMPERATURE [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] SITE RAIN STATUS []
January -8.8 -10.9 -16.1 5.70 -23.3 32.48 106.19 0.00
February -2.2 -5.0 -9.9 6.21 -16.1 41.31 158.25 0.00
March 0.30 -2.9 -8.4 5.38 -12.8 78.62 145.02 0.00
April 6.67 2.34 -2.9 4.89 -6.2 82.10 182.32 0.01
May 10.10 5.18 0.22 5.28 -1.1 102.67 205.47 0.01
June 16.46 10.06 4.91 4.56 5.05 103.05 264.47 0.02
July 20.57 12.46 6.56 4.24 8.00 89.47 301.47 0.00
August 19.17 11.04 4.61 4.29 7.19 78.96 261.05 0.00
September 14.69 9.08 4.37 5.43 3.42 63.03 204.21 0.00
October 8.64 4.13 -1.0 5.38 -4.2 47.64 162.42 0.00
November 2.84 -0.9 -6.9 5.91 -11.0 33.00 125.52 0.00
December -4.1 -6.5 -11.1 5.64 -18.2 26.54 97.81 0.00
                 
Annual Sum or Average 7.07 2.37 -2.9 5.23 -5.7 65.04 184.63 0.00
Minimum of Months -8.8 -10.9 -16.1 4.24 -23.3 26.54 97.81 0.00
Maximum of Months 20.57 12.46 6.56 6.21 8.00 103.05 301.47 0.02



Table of Contents

Report: OutdoorConditionsMaximumDryBulbMonthly

For: Environment

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] SITE WIND SPEED {AT MAX/MIN} [m/s] SITE SKY TEMPERATURE {AT MAX/MIN} [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2]
January 10.60 14-JAN-12:00 5.16 -1.1 8.20 -2.3 105.00 464.50
February 18.90 27-FEB-14:00 7.23 -7.8 5.20 1.37 76.00 634.50
March 15.00 14-MAR-13:20 6.67 -2.4 9.30 1.23 201.67 711.67
April 23.30 07-APR-13:00 9.68 -4.4 9.30 4.92 314.50 110.00
May 30.00 20-MAY-15:00 15.22 5.60 6.70 20.57 215.50 18.50
June 32.20 29-JUN-12:00 14.40 0.60 9.30 17.03 187.00 729.00
July 37.20 17-JUL-15:00 17.28 4.40 4.60 20.22 119.50 797.00
August 35.60 05-AUG-15:00 17.65 6.70 5.20 22.47 136.50 625.50
September 34.40 02-SEP-14:00 16.28 4.40 7.70 20.75 95.50 789.50
October 25.00 18-OCT-13:00 11.40 -1.1 7.70 7.35 48.00 913.00
November 17.20 04-NOV-13:00 8.18 -1.1 11.30 2.22 81.00 689.50
December 13.90 10-DEC-01:00 5.50 -5.0 13.90 5.74 0.00 0.00
                 
Annual Sum or Average                
Minimum of Months 10.60   5.16 -7.8 4.60 -2.3 0.00 0.00
Maximum of Months 37.20   17.65 6.70 13.90 22.47 314.50 913.00



Table of Contents

Report: OutdoorConditionsMinimumDryBulbMonthly

For: Environment

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] SITE WIND SPEED {AT MAX/MIN} [m/s] SITE SKY TEMPERATURE {AT MAX/MIN} [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2]
January -33.9 10-JAN-21:00 -34.1 -37.8 3.10 -54.3 0.00 0.00
February -25.0 01-FEB-03:00 -25.2 -27.8 2.10 -45.6 0.00 0.00
March -23.3 04-MAR-23:00 -23.8 -28.9 3.60 -44.5 0.00 0.00
April -7.8 29-APR-03:00 -8.7 -10.6 4.10 -25.6 0.00 0.00
May -2.8 08-MAY-00:10 -3.3 -3.9 6.18 -10.2 0.00 0.00
June 0.60 15-JUN-03:00 -0.5 -1.7 2.60 -15.7 0.00 0.00
July 5.60 08-JUL-03:00 2.99 0.00 4.10 -9.2 0.00 0.00
August 6.70 17-AUG-00:00 4.32 1.70 2.60 -7.1 0.00 0.00
September 0.00 17-SEP-02:00 -1.6 -3.9 4.10 -16.8 0.00 0.00
October -6.1 10-OCT-05:19 -6.6 -7.8 3.77 -20.6 0.00 0.00
November -16.7 26-NOV-07:00 -17.3 -20.6 4.60 -33.8 19.50 94.00
December -28.3 29-DEC-08:00 -28.6 -32.2 2.10 -48.7 69.50 0.00
                 
Annual Sum or Average                
Minimum of Months -33.9   -34.1 -37.8 2.10 -54.3 0.00 0.00
Maximum of Months 6.70   4.32 1.70 6.18 -7.1 69.50 94.00



Table of Contents

Report: OutdoorConditionsMaximumWetBulbMonthly

For: Environment

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

SITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] SITE WIND SPEED {AT MAX/MIN} [m/s] SITE SKY TEMPERATURE {AT MAX/MIN} [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2]
January 5.18 13-JAN-14:00 10.00 0.00 8.80 -3.0 40.00 694.00
February 7.23 27-FEB-14:00 18.90 -7.8 5.20 1.37 76.00 634.50
March 6.94 14-MAR-13:00 15.00 -1.7 10.30 1.80 241.00 538.00
April 11.02 06-APR-15:00 22.20 1.10 3.60 5.33 110.00 779.00
May 15.22 20-MAY-15:00 30.00 5.60 6.70 20.57 215.50 18.50
June 19.20 20-JUN-14:00 29.40 14.40 2.60 18.28 204.00 614.00
July 19.21 19-JUL-11:00 29.40 14.40 8.80 19.52 306.50 563.50
August 17.65 05-AUG-15:00 35.60 6.70 5.20 22.47 136.50 625.50
September 20.12 07-SEP-15:20 25.17 17.93 4.10 15.88 127.67 652.00
October 11.61 18-OCT-14:00 25.00 -0.6 7.70 7.55 40.50 852.00
November 8.89 17-NOV-16:00 17.20 1.10 11.30 4.10 0.00 0.00
December 7.62 19-DEC-14:00 12.80 2.80 8.20 1.37 74.00 138.50
                 
Annual Sum or Average                
Minimum of Months 5.18   10.00 -7.8 2.60 -3.0 0.00 0.00
Maximum of Months 20.12   35.60 17.93 11.30 22.47 306.50 852.00



Table of Contents

Report: OutdoorConditionsMaximumDewPointMonthly

For: Environment

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

SITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] SITE WIND SPEED {AT MAX/MIN} [m/s] SITE SKY TEMPERATURE {AT MAX/MIN} [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2]
January 1.70 12-JAN-14:00 7.20 4.48 5.20 -1.0 107.00 61.00
February -0.6 11-FEB-08:00 4.40 2.16 10.80 -5.7 69.50 50.50
March -0.6 10-MAR-12:00 8.90 4.51 10.30 -2.3 253.00 140.50
April 6.10 17-APR-16:19 7.97 6.96 4.50 0.87 201.50 117.50
May 12.20 02-MAY-12:00 18.90 14.61 12.90 14.84 108.50 934.50
June 15.60 20-JUN-19:00 25.60 18.76 3.60 20.22 17.50 17.00
July 16.70 18-JUL-21:00 19.40 17.51 4.10 16.49 0.00 0.00
August 11.10 08-AUG-11:00 26.70 16.75 2.60 12.03 134.50 869.00
September 18.30 07-SEP-14:00 24.40 20.10 4.10 15.57 111.00 720.00
October 6.70 01-OCT-14:09 9.08 7.78 2.10 4.07 260.33 0.33
November 3.30 16-NOV-19:00 10.60 6.88 9.80 -1.7 0.00 0.00
December 2.80 19-DEC-14:09 10.97 6.81 10.78 -1.0 95.00 292.00
                 
Annual Sum or Average                
Minimum of Months -0.6   4.40 2.16 2.10 -5.7 0.00 0.00
Maximum of Months 18.30   26.70 20.10 12.90 20.22 260.33 934.50



Table of Contents

Report: OutdoorGroundConditionsMonthly

For: Environment

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

SITE GROUND TEMPERATURE [C] SITE SURFACE GROUND TEMPERATURE [C] SITE DEEP GROUND TEMPERATURE [C] SITE MAINS WATER TEMPERATURE [C] SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] SITE SNOW ON GROUND STATUS []
January 18.00 13.00 16.00 5.41 12.59 0.00
February 18.00 13.00 16.00 4.46 20.37 0.00
March 18.00 13.00 16.00 5.03 30.19 0.00
April 18.00 13.00 16.00 7.01 37.07 0.00
May 18.00 13.00 16.00 9.90 46.35 0.00
June 18.00 13.00 16.00 12.91 55.45 0.00
July 18.00 13.00 16.00 15.24 57.38 0.00
August 18.00 13.00 16.00 16.26 48.01 0.00
September 18.00 13.00 16.00 15.67 34.51 0.00
October 18.00 13.00 16.00 13.64 22.84 0.00
November 18.00 13.00 16.00 10.74 14.52 0.00
December 18.00 13.00 16.00 7.74 10.24 0.00
             
Annual Sum or Average 18.00 13.00 16.00 10.37 32.53 0.00
Minimum of Months 18.00 13.00 16.00 4.46 10.24 0.00
Maximum of Months 18.00 13.00 16.00 16.26 57.38 0.00



Table of Contents

Report: WaterHeaterReportMonthly

For: SWHSYS1 WATER HEATER

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] WATER HEATER BURNER HEATING ENERGY [] WATER HEATER GAS CONSUMPTION [] WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] WATER HEATER LOSS DEMAND ENERGY [] WATER HEATER HEAT LOSS ENERGY [J] WATER HEATER TANK TEMPERATURE [C] WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] WATER HEATER SOURCE ENERGY []
January 0.436849E+11 -0.426371E+11 0.00 0.00 744.00 0.00 -0.104772E+10 58.99 0.00 0.00
February 0.403591E+11 -0.394249E+11 0.00 0.00 672.00 0.00 -934206830.8 58.98 0.00 0.00
March 0.469298E+11 -0.458985E+11 0.00 0.00 744.00 0.00 -0.103125E+10 58.98 0.00 0.00
April 0.410850E+11 -0.400938E+11 0.00 0.00 720.00 0.00 -991151940.4 58.98 0.00 0.00
May 0.414885E+11 -0.404645E+11 0.00 0.00 744.00 0.00 -0.102396E+10 58.98 0.00 0.00
June 0.386197E+11 -0.376295E+11 0.00 0.00 720.00 0.00 -990211275.2 58.98 0.00 0.00
July 0.349776E+11 -0.339604E+11 0.00 0.00 744.00 0.00 -0.101726E+10 58.97 0.00 0.00
August 0.373641E+11 -0.363424E+11 0.00 0.00 744.00 0.00 -0.102163E+10 58.98 0.00 0.00
September 0.344078E+11 -0.334209E+11 0.00 0.00 720.00 0.00 -986873290.4 58.97 0.00 0.00
October 0.371098E+11 -0.360907E+11 0.00 0.00 744.00 0.00 -0.101915E+10 58.97 0.00 0.00
November 0.386505E+11 -0.376623E+11 0.00 0.00 720.00 0.00 -988135958.0 58.97 0.00 0.00
December 0.408240E+11 -0.397946E+11 0.00 0.00 744.00 0.00 -0.102935E+10 58.98 0.00 0.00
                     
Annual Sum or Average 0.475501E+12 -0.463420E+12 0.00 0.00 8760.00 0.00 -0.120809E+11 58.98 0.00 0.00
Minimum of Months 0.344078E+11 -0.458985E+11 0.00 0.00 672.00 0.00 -0.104772E+10 58.97 0.00 0.00
Maximum of Months 0.469298E+11 -0.334209E+11 0.00 0.00 744.00 0.00 -934206830.8 58.99 0.00 0.00



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_BOT_ZN_1_DAYLCTRL

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 226.83 0.51 0.48 01-JAN-08:50 6268.52 37.11 219.83 232.50 5241.31 37.97 224.67 214.67
February 275.00 0.50 0.48 01-FEB-08:20 8484.48 37.44 268.67 259.67 3613.70 31.80 235.50 245.67
March 304.00 0.50 0.48 01-MAR-07:49 9903.93 33.46 272.17 324.17 2044.76 23.50 257.00 297.50
April 325.17 0.50 0.48 01-APR-08:50 2514.15 21.09 160.00 351.50 1434.51 22.54 240.17 318.17
May 385.83 0.51 0.48 01-MAY-06:30 2226.70 20.83 163.33 399.83 1248.17 22.26 279.83 360.17
June 434.17 0.52 0.48 01-JUN-13:39 1912.30 20.30 173.83 414.00 1108.82 21.75 288.33 368.17
July 417.33 0.50 0.48 01-JUL-06:40 2057.24 20.69 139.67 406.83 1227.05 22.16 277.17 373.33
August 421.33 0.51 0.48 01-AUG-06:40 2193.88 20.22 156.00 386.33 1309.39 21.66 246.33 351.17
September 352.17 0.52 0.48 01-SEP-06:00 3085.65 21.63 150.00 328.00 1532.49 21.86 218.50 300.50
October 317.67 0.50 0.48 01-OCT-08:39 8591.47 35.15 289.33 302.00 2349.71 24.42 214.50 282.33
November 269.50 0.50 0.48 01-NOV-07:00 6399.52 37.45 262.67 250.67 5632.23 38.62 264.17 241.17
December 236.83 0.51 0.48 01-DEC-08:50 4980.48 37.80 237.83 232.33 4337.08 38.97 241.17 219.67
                         
Annual Sum or Average 3965.83 0.51     4482.25 27.13 2493.33 3887.83 2301.83 26.06 2987.33 3572.50
Minimum of Months 226.83 0.50 0.48   1912.30 20.22 139.67 232.33 1108.82 21.66 214.50 214.67
Maximum of Months 434.17 0.52 0.48   9903.93 37.80 289.33 414.00 5632.23 38.97 288.33 373.33



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_BOT_ZN_2_DAYLCTRL

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 226.83 0.53 0.48 01-JAN-08:50 1982.29 25.53 106.50 218.67 1123.30 25.20 138.17 186.50
February 275.00 0.52 0.48 01-FEB-08:09 2220.78 24.62 120.67 248.67 1195.29 24.54 153.50 218.50
March 304.00 0.50 0.48 01-MAR-07:40 3488.50 25.83 153.83 321.00 1943.07 26.01 234.17 291.00
April 325.17 0.49 0.48 01-APR-08:39 3477.13 24.48 112.33 358.33 1928.14 24.85 186.33 325.33
May 385.83 0.50 0.48 01-MAY-05:40 3821.68 24.61 139.17 410.17 1674.31 24.08 226.33 373.50
June 434.17 0.51 0.48 01-JUN-13:39 4650.30 25.69 153.67 425.83 2016.91 25.02 271.83 394.00
July 417.33 0.49 0.48 01-JUL-06:40 5042.98 25.82 148.83 423.50 2158.28 24.93 220.67 397.17
August 421.33 0.51 0.48 01-AUG-05:30 4026.77 25.14 155.50 393.67 2311.46 25.41 219.17 363.33
September 352.17 0.51 0.48 01-SEP-06:19 3034.73 24.30 141.33 328.50 1679.31 24.60 190.33 300.67
October 317.67 0.52 0.48 01-OCT-08:20 2725.75 24.82 143.00 292.33 1547.48 24.99 181.17 258.50
November 269.50 0.53 0.48 01-NOV-07:49 1765.97 24.54 118.33 234.83 971.20 24.42 146.00 204.00
December 236.83 0.54 0.48 01-DEC-08:50 1542.15 25.46 109.67 211.83 910.02 25.23 133.00 173.83
                         
Annual Sum or Average 3965.83 0.51     3359.20 25.08 1602.83 3867.33 1703.98 24.93 2300.67 3486.33
Minimum of Months 226.83 0.49 0.48   1542.15 24.30 106.50 211.83 910.02 24.08 133.00 173.83
Maximum of Months 434.17 0.54 0.48   5042.98 25.83 155.50 425.83 2311.46 26.01 271.83 397.17



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_BOT_ZN_3_DAYLCTRL

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 226.83 0.57 0.48 01-JAN-10:30 656.31 16.83 0.00 196.67 385.79 18.47 7.50 134.00
February 275.00 0.54 0.48 01-FEB-10:50 721.92 17.82 0.00 234.83 442.01 19.47 18.00 182.00
March 304.00 0.51 0.48 01-MAR-08:09 1133.25 19.67 1.50 314.00 663.64 21.15 156.67 273.83
April 325.17 0.50 0.48 01-APR-08:00 1182.72 20.27 20.83 353.83 703.37 21.65 183.17 315.67
May 385.83 0.49 0.48 01-MAY-06:10 1458.10 22.11 109.33 413.17 851.19 23.32 289.00 380.83
June 434.17 0.49 0.48 01-JUN-13:39 1526.02 24.16 201.33 441.83 854.81 23.41 345.67 416.50
July 417.33 0.49 0.48 01-JUL-06:40 1490.02 23.12 147.50 427.33 857.59 22.40 290.50 401.00
August 421.33 0.50 0.48 01-AUG-05:49 1158.53 19.90 42.50 400.33 733.74 21.30 223.00 380.33
September 352.17 0.52 0.48 01-SEP-06:00 948.22 18.96 1.17 325.33 586.24 20.43 114.67 282.67
October 317.67 0.53 0.48 01-OCT-09:09 780.81 18.14 0.00 277.83 473.70 19.72 49.67 221.83
November 269.50 0.56 0.48 01-NOV-08:00 617.01 16.97 0.00 214.67 368.96 18.63 2.67 150.83
December 236.83 0.58 0.48 01-DEC-09:50 536.17 16.35 0.00 190.17 318.49 18.06 0.17 103.50
                         
Annual Sum or Average 3965.83 0.52     1080.94 19.98 524.17 3790.00 639.95 20.99 1680.67 3243.00
Minimum of Months 226.83 0.49 0.48   536.17 16.35 0.00 190.17 318.49 18.06 0.17 103.50
Maximum of Months 434.17 0.58 0.48   1526.02 24.16 201.33 441.83 857.59 23.41 345.67 416.50



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_BOT_ZN_4_DAYLCTRL

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 226.83 0.54 0.48 01-JAN-10:20 1845.49 24.30 99.33 212.67 1069.69 24.24 135.50 176.50
February 275.00 0.52 0.48 01-FEB-10:50 2381.76 25.30 125.83 246.17 1291.42 25.16 154.17 219.00
March 304.00 0.50 0.48 01-MAR-08:20 3275.84 25.59 152.33 319.50 1793.51 25.87 232.17 289.17
April 325.17 0.50 0.48 01-APR-08:00 3388.31 23.41 111.50 351.33 1891.65 23.94 191.00 317.83
May 385.83 0.50 0.48 01-MAY-06:49 3861.55 22.57 102.83 405.17 2261.87 23.39 222.17 372.17
June 434.17 0.51 0.48 01-JUN-13:39 3955.85 21.00 69.33 427.67 1784.18 21.37 235.33 395.00
July 417.33 0.50 0.48 01-JUL-06:00 4586.26 22.64 94.83 412.67 2071.17 21.66 195.83 385.17
August 421.33 0.51 0.48 01-AUG-06:49 3564.68 22.47 118.17 392.33 1965.18 23.05 196.50 363.50
September 352.17 0.51 0.48 01-SEP-07:10 3552.16 25.12 145.83 330.00 1484.89 24.15 189.83 301.17
October 317.67 0.52 0.48 01-OCT-09:20 2388.06 24.65 141.00 290.50 1314.10 24.76 184.67 257.67
November 269.50 0.53 0.48 01-NOV-08:00 2056.71 25.35 120.83 233.33 1161.83 25.19 149.00 201.67
December 236.83 0.54 0.48 01-DEC-09:50 1449.87 24.72 106.67 213.17 809.46 24.47 128.50 177.00
                         
Annual Sum or Average 3965.83 0.51     3202.80 23.69 1388.50 3834.50 1649.84 23.72 2214.67 3455.83
Minimum of Months 226.83 0.50 0.48   1449.87 21.00 69.33 212.67 809.46 21.37 128.50 176.50
Maximum of Months 434.17 0.54 0.48   4586.26 25.59 152.33 427.67 2261.87 25.87 235.33 395.00



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_MID_ZN_1_DAYLCTRL

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 226.83 0.51 0.48 01-JAN-08:50 6316.76 36.63 216.33 232.67 5372.66 37.50 215.33 216.00
February 275.00 0.50 0.48 01-FEB-08:20 8551.12 36.96 266.33 259.83 3787.62 30.09 179.83 248.17
March 304.00 0.50 0.48 01-MAR-07:49 9963.92 32.27 254.17 324.17 2182.62 18.77 14.00 299.83
April 325.17 0.50 0.48 01-APR-08:50 2562.85 14.74 0.00 351.67 1537.64 18.26 8.83 321.67
May 385.83 0.51 0.48 01-MAY-06:30 2263.57 14.70 0.00 399.83 1334.01 18.16 1.67 364.33
June 434.17 0.52 0.48 01-JUN-13:39 1948.85 14.32 0.00 415.00 1185.85 17.86 0.00 373.50
July 417.33 0.50 0.48 01-JUL-06:40 2102.54 14.69 0.00 407.00 1315.46 18.26 1.17 377.67
August 421.33 0.51 0.48 01-AUG-06:40 2248.43 13.95 0.00 386.67 1407.18 17.50 2.67 355.33
September 352.17 0.52 0.48 01-SEP-06:00 3150.88 15.53 29.50 328.17 1665.48 17.59 14.33 303.67
October 317.67 0.50 0.48 01-OCT-08:30 8650.58 34.24 283.00 302.00 2585.30 22.00 80.83 287.33
November 269.50 0.50 0.48 01-NOV-07:00 6453.29 36.99 262.00 251.00 5755.27 38.26 263.00 242.50
December 236.83 0.51 0.48 01-DEC-08:50 5018.36 37.38 231.33 232.50 4450.62 38.64 232.17 221.33
                         
Annual Sum or Average 3965.83 0.51     4532.81 23.23 1542.67 3890.50 2422.73 22.90 1013.83 3611.33
Minimum of Months 226.83 0.50 0.48   1948.85 13.95 0.00 232.50 1185.85 17.50 0.00 216.00
Maximum of Months 434.17 0.52 0.48   9963.92 37.38 283.00 415.00 5755.27 38.64 263.00 377.67



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_MID_ZN_2_DAYLCTRL

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 226.83 0.53 0.48 01-JAN-08:50 2014.10 23.38 89.67 219.67 1167.64 23.58 76.67 189.67
February 275.00 0.52 0.48 01-FEB-08:09 2216.52 20.72 75.00 248.67 1252.84 22.61 76.00 222.00
March 304.00 0.50 0.48 01-MAR-07:40 3520.40 22.27 94.67 321.17 2021.98 24.01 92.67 293.83
April 325.17 0.49 0.48 01-APR-08:39 3541.86 21.39 85.33 359.17 2011.14 22.44 60.17 328.83
May 385.83 0.50 0.48 01-MAY-05:40 3884.51 21.66 113.00 410.83 1758.21 21.48 57.83 377.17
June 434.17 0.51 0.48 01-JUN-13:39 4697.80 22.02 134.17 426.33 2112.82 22.53 89.50 397.33
July 417.33 0.49 0.48 01-JUL-06:40 5117.95 22.90 134.00 424.00 2264.13 22.31 75.50 399.00
August 421.33 0.51 0.48 01-AUG-05:30 4097.85 22.24 131.33 394.33 2403.42 23.13 101.17 367.50
September 352.17 0.51 0.48 01-SEP-06:19 3093.98 21.44 104.17 328.83 1752.31 22.36 78.33 303.50
October 317.67 0.52 0.48 01-OCT-08:20 2771.23 22.32 110.50 292.83 1604.65 23.09 101.50 262.00
November 269.50 0.53 0.48 01-NOV-07:49 1797.46 22.24 95.17 235.33 1014.20 22.70 82.00 208.50
December 236.83 0.54 0.48 01-DEC-08:50 1565.37 23.46 101.83 213.00 943.72 23.80 89.67 178.67
                         
Annual Sum or Average 3965.83 0.51     3407.66 22.13 1268.83 3874.17 1778.93 22.76 981.00 3528.00
Minimum of Months 226.83 0.49 0.48   1565.37 20.72 75.00 213.00 943.72 21.48 57.83 178.67
Maximum of Months 434.17 0.54 0.48   5117.95 23.46 134.17 426.33 2403.42 24.01 101.50 399.00



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_MID_ZN_3_DAYLCTRL

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 226.83 0.56 0.48 01-JAN-10:20 664.14 10.99 0.00 197.17 409.77 14.55 0.00 143.17
February 275.00 0.54 0.48 01-FEB-10:30 732.51 12.05 0.00 235.17 470.23 15.69 0.00 189.67
March 304.00 0.51 0.48 01-MAR-08:09 1150.69 14.08 0.00 314.50 705.90 17.54 0.00 279.17
April 325.17 0.50 0.48 01-APR-08:50 1203.56 14.86 0.00 354.50 749.30 18.34 4.00 321.67
May 385.83 0.49 0.48 01-MAY-05:00 1484.41 16.97 38.50 413.33 905.52 20.18 46.83 384.33
June 434.17 0.49 0.48 01-JUN-13:39 1556.24 19.85 107.67 442.50 912.32 20.13 44.00 419.33
July 417.33 0.49 0.48 01-JUL-06:40 1521.68 18.42 72.17 427.33 916.56 18.99 22.00 403.67
August 421.33 0.50 0.48 01-AUG-05:49 1182.13 14.42 0.00 400.67 780.92 17.99 5.83 381.83
September 352.17 0.52 0.48 01-SEP-06:00 965.37 13.54 0.00 326.33 624.75 17.02 0.00 288.67
October 317.67 0.53 0.48 01-OCT-08:00 792.49 12.49 0.00 278.33 504.04 16.07 0.00 230.00
November 269.50 0.56 0.48 01-NOV-08:50 624.96 11.07 0.00 215.50 392.11 14.73 0.00 162.17
December 236.83 0.58 0.48 01-DEC-09:50 541.36 10.27 0.00 190.83 338.01 13.97 0.00 121.00
                         
Annual Sum or Average 3965.83 0.52     1100.18 14.62 218.33 3796.17 681.67 17.48 122.67 3324.67
Minimum of Months 226.83 0.49 0.48   541.36 10.27 0.00 190.83 338.01 13.97 0.00 121.00
Maximum of Months 434.17 0.58 0.48   1556.24 19.85 107.67 442.50 916.56 20.18 46.83 419.33



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_MID_ZN_4_DAYLCTRL

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 226.83 0.54 0.48 01-JAN-10:09 1874.81 22.19 85.33 213.33 1110.77 22.66 72.33 180.00
February 275.00 0.52 0.48 01-FEB-10:30 2423.57 22.85 95.17 247.33 1346.94 23.32 88.17 222.67
March 304.00 0.50 0.48 01-MAR-08:20 3307.46 21.99 92.50 319.50 1866.31 23.87 92.00 292.67
April 325.17 0.50 0.48 01-APR-08:00 3451.55 20.09 75.83 351.33 1975.73 21.31 48.00 320.33
May 385.83 0.50 0.48 01-MAY-06:40 3921.55 18.98 75.00 405.67 2351.51 20.53 46.00 375.50
June 434.17 0.50 0.48 01-JUN-13:39 4011.29 17.03 52.00 428.17 1871.02 18.04 0.00 399.33
July 417.33 0.50 0.48 01-JUL-06:00 4652.50 19.08 79.67 413.00 2171.29 18.36 3.67 388.50
August 421.33 0.51 0.48 01-AUG-06:49 3628.80 19.06 91.00 392.67 2048.42 20.32 58.00 365.67
September 352.17 0.51 0.48 01-SEP-07:10 3611.41 22.47 116.83 331.17 1558.17 21.82 67.50 303.50
October 317.67 0.52 0.48 01-OCT-09:09 2434.21 22.01 100.67 291.50 1372.36 22.76 91.00 262.33
November 269.50 0.53 0.48 01-NOV-08:00 2087.75 22.89 102.83 233.17 1205.95 23.52 95.50 206.00
December 236.83 0.54 0.48 01-DEC-09:39 1434.08 20.93 79.33 214.00 844.09 22.95 86.83 182.50
                         
Annual Sum or Average 3965.83 0.51     3250.80 20.49 1046.17 3840.83 1722.37 21.28 749.00 3499.00
Minimum of Months 226.83 0.50 0.48   1434.08 17.03 52.00 213.33 844.09 18.04 0.00 180.00
Maximum of Months 434.17 0.54 0.48   4652.50 22.89 116.83 428.17 2351.51 23.87 95.50 399.33



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_TOP_ZN_1_DAYLCTRL

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 226.83 0.51 0.48 01-JAN-08:50 6317.94 36.62 216.33 232.67 5374.73 37.49 215.33 216.00
February 275.00 0.50 0.48 01-FEB-08:20 8552.79 36.96 266.33 259.83 3790.09 30.09 179.83 248.17
March 304.00 0.50 0.48 01-MAR-07:49 9967.73 32.26 254.17 324.17 2185.79 18.75 13.83 300.00
April 325.17 0.50 0.48 01-APR-08:50 2566.38 14.71 0.00 351.67 1539.90 18.25 8.50 321.83
May 385.83 0.51 0.48 01-MAY-06:30 2266.84 14.67 0.00 399.83 1336.01 18.15 1.67 364.33
June 434.17 0.52 0.48 01-JUN-13:39 1951.39 14.29 0.00 415.00 1187.47 17.84 0.00 373.50
July 417.33 0.50 0.48 01-JUL-06:40 2105.11 14.66 0.00 407.00 1317.13 18.24 1.17 377.83
August 421.33 0.51 0.48 01-AUG-06:40 2251.24 13.92 0.00 386.67 1409.00 17.48 2.67 355.50
September 352.17 0.52 0.48 01-SEP-06:00 3153.91 15.50 29.50 328.33 1667.66 17.57 14.17 303.67
October 317.67 0.50 0.48 01-OCT-08:30 8652.57 34.23 283.00 302.00 2587.72 21.99 80.67 287.33
November 269.50 0.50 0.48 01-NOV-07:00 6454.34 36.98 262.00 251.00 5757.37 38.26 263.00 242.50
December 236.83 0.51 0.48 01-DEC-08:50 5019.03 37.37 231.33 232.50 4452.28 38.64 232.17 221.33
                         
Annual Sum or Average 3965.83 0.51     4535.29 23.21 1542.67 3890.67 2424.82 22.89 1013.00 3612.00
Minimum of Months 226.83 0.50 0.48   1951.39 13.92 0.00 232.50 1187.47 17.48 0.00 216.00
Maximum of Months 434.17 0.52 0.48   9967.73 37.37 283.00 415.00 5757.37 38.64 263.00 377.83



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_TOP_ZN_2_DAYLCTRL

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 226.83 0.53 0.48 01-JAN-08:50 2015.13 23.36 89.67 219.67 1168.68 23.57 76.67 189.67
February 275.00 0.52 0.48 01-FEB-08:09 2217.52 20.69 75.00 248.83 1253.99 22.59 75.83 222.00
March 304.00 0.50 0.48 01-MAR-07:40 3522.52 22.24 94.50 321.33 2023.85 24.00 92.00 294.00
April 325.17 0.49 0.48 01-APR-08:39 3543.73 21.36 85.33 359.17 2012.86 22.42 60.17 328.83
May 385.83 0.50 0.48 01-MAY-05:40 3886.78 21.63 113.00 411.00 1760.04 21.46 57.83 377.33
June 434.17 0.51 0.48 01-JUN-13:39 4699.75 21.99 134.17 426.33 2114.65 22.52 89.50 397.33
July 417.33 0.49 0.48 01-JUL-06:40 5119.60 22.87 134.00 424.00 2265.82 22.29 75.50 399.00
August 421.33 0.51 0.48 01-AUG-05:30 4099.47 22.22 131.33 394.33 2405.03 23.11 101.00 367.67
September 352.17 0.51 0.48 01-SEP-06:19 3095.43 21.41 104.17 328.83 1753.78 22.34 78.33 303.50
October 317.67 0.52 0.48 01-OCT-08:20 2757.10 21.93 107.00 292.67 1605.88 23.08 101.17 262.00
November 269.50 0.53 0.48 01-NOV-07:49 1747.31 20.68 83.00 234.83 1015.16 22.69 82.00 208.50
December 236.83 0.54 0.48 01-DEC-08:50 1566.11 23.44 101.83 213.00 944.55 23.79 89.33 178.67
                         
Annual Sum or Average 3965.83 0.51     3404.52 21.97 1253.00 3874.00 1780.42 22.74 979.33 3528.50
Minimum of Months 226.83 0.49 0.48   1566.11 20.68 75.00 213.00 944.55 21.46 57.83 178.67
Maximum of Months 434.17 0.54 0.48   5119.60 23.44 134.17 426.33 2405.03 24.00 101.17 399.00



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_TOP_ZN_3_DAYLCTRL

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 226.83 0.56 0.48 01-JAN-10:20 664.79 10.96 0.00 197.33 410.34 14.54 0.00 143.83
February 275.00 0.54 0.48 01-FEB-10:30 733.10 12.02 0.00 235.17 470.82 15.67 0.00 189.83
March 304.00 0.51 0.48 01-MAR-08:09 1151.92 14.05 0.00 314.50 706.89 17.52 0.00 279.17
April 325.17 0.50 0.48 01-APR-08:50 1204.79 14.83 0.00 354.50 750.31 18.32 3.83 322.17
May 385.83 0.49 0.48 01-MAY-05:00 1485.90 16.94 38.50 413.33 906.71 20.16 46.67 384.83
June 434.17 0.49 0.48 01-JUN-13:39 1557.45 19.82 107.50 442.50 913.44 20.11 43.33 419.50
July 417.33 0.49 0.48 01-JUL-06:40 1522.76 18.39 72.17 427.33 917.61 18.98 21.33 403.83
August 421.33 0.50 0.48 01-AUG-05:49 1183.08 14.39 0.00 400.67 781.81 17.97 5.67 381.83
September 352.17 0.52 0.48 01-SEP-06:00 966.17 13.51 0.00 326.33 625.50 17.01 0.00 288.67
October 317.67 0.53 0.48 01-OCT-08:00 793.19 12.46 0.00 278.50 504.69 16.06 0.00 230.00
November 269.50 0.56 0.48 01-NOV-08:50 625.52 11.04 0.00 215.50 392.64 14.72 0.00 162.33
December 236.83 0.58 0.48 01-DEC-09:50 541.82 10.24 0.00 191.17 338.48 13.95 0.00 121.17
                         
Annual Sum or Average 3965.83 0.52     1101.14 14.59 218.17 3796.83 682.53 17.46 120.83 3327.17
Minimum of Months 226.83 0.49 0.48   541.82 10.24 0.00 191.17 338.48 13.95 0.00 121.17
Maximum of Months 434.17 0.58 0.48   1557.45 19.82 107.50 442.50 917.61 20.16 46.67 419.50



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_TOP_ZN_4_DAYLCTRL

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 226.83 0.54 0.48 01-JAN-10:09 1875.86 22.17 85.33 213.33 1111.81 22.65 72.17 180.00
February 275.00 0.52 0.48 01-FEB-10:30 2424.60 22.83 95.17 247.33 1348.08 23.31 87.67 222.67
March 304.00 0.50 0.48 01-MAR-08:20 3309.65 21.97 92.50 319.50 1868.19 23.86 90.67 292.83
April 325.17 0.50 0.48 01-APR-08:00 3453.56 20.06 75.83 351.33 1977.65 21.29 48.00 320.33
May 385.83 0.50 0.48 01-MAY-06:40 3923.82 18.95 75.00 405.67 2353.53 20.52 46.00 375.50
June 434.17 0.50 0.48 01-JUN-13:39 4013.35 17.00 52.00 428.33 1872.86 18.02 0.00 399.50
July 417.33 0.50 0.48 01-JUL-06:00 4654.34 19.04 79.67 413.00 2173.10 18.34 3.67 388.50
August 421.33 0.51 0.48 01-AUG-06:49 3630.51 19.03 91.00 392.67 2050.06 20.30 58.00 365.67
September 352.17 0.51 0.48 01-SEP-07:10 3612.83 22.45 116.83 331.17 1559.63 21.81 67.33 304.00
October 317.67 0.52 0.48 01-OCT-09:09 2435.34 21.99 100.67 291.50 1373.59 22.75 90.33 262.33
November 269.50 0.53 0.48 01-NOV-08:00 2088.64 22.86 102.83 233.17 1206.95 23.51 95.17 206.17
December 236.83 0.54 0.48 01-DEC-09:39 1434.81 20.90 79.17 214.00 844.92 22.94 86.83 182.50
                         
Annual Sum or Average 3965.83 0.51     3252.41 20.47 1046.00 3841.00 1723.91 21.27 745.83 3500.00
Minimum of Months 226.83 0.50 0.48   1434.81 17.00 52.00 213.33 844.92 18.02 0.00 180.00
Maximum of Months 434.17 0.54 0.48   4654.34 22.86 116.83 428.33 2353.53 23.86 95.17 399.50



Table of Contents

Report: CoilReportMonthly

For: VAV_BOT WITH REHEAT HEATING COIL

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.334272E+11 77068.73 10-JAN-22:00 0.00 0.00 0.00 0.00 0.00
February 0.168618E+11 58624.87 01-FEB-07:10 0.00 0.00 0.00 0.00 0.00
March 0.739902E+10 48836.56 06-MAR-07:10 0.00 0.00 0.00 0.00 0.00
April 0.926557E+09 23144.83 29-APR-06:05 0.00 0.00 0.00 0.00 0.00
May 0.646080E+09 16590.06 08-MAY-06:10 0.00 0.00 0.00 0.00 0.00
June 6526257.58 2522.90 16-JUN-07:00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 76527636.64 6285.01 19-SEP-06:10 0.00 0.00 0.00 0.00 0.00
October 0.735085E+09 20113.00 10-OCT-06:55 0.00 0.00 0.00 0.00 0.00
November 0.494349E+10 37057.99 27-NOV-07:10 0.00 0.00 0.00 0.00 0.00
December 0.179493E+11 62767.94 29-DEC-08:65 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.829716E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.334272E+11 77068.73   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: CORE_BOTTOM VAV BOX REHEAT COIL

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:05 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:05 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:05 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.424173E+10 16721.01 04-JAN-06:01 0.00 0.00 0.00 0.00 0.00
February 0.135167E+10 16767.52 24-FEB-06:01 0.00 0.00 0.00 0.00 0.00
March 0.338520E+09 16767.39 03-MAR-06:01 0.00 0.00 0.00 0.00 0.00
April 3448162.42 13067.64 29-APR-05:01 0.00 0.00 0.00 0.00 0.00
May 11586585.55 15538.97 08-MAY-05:01 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:05 0.00 0.00 0.00 0.00 0.00
October 579529.37 270.44 10-OCT-05:03 0.00 0.00 0.00 0.00 0.00
November 0.204542E+09 16816.45 13-NOV-06:01 0.00 0.00 0.00 0.00 0.00
December 0.112533E+10 16771.36 01-DEC-06:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.727740E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.424173E+10 16816.45   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.354685E+10 18501.61 04-JAN-06:01 0.00 0.00 0.00 0.00 0.00
February 0.144724E+10 18512.88 24-FEB-06:01 0.00 0.00 0.00 0.00 0.00
March 0.551942E+09 18512.15 03-MAR-06:01 0.00 0.00 0.00 0.00 0.00
April 71648919.56 18518.81 29-APR-05:01 0.00 0.00 0.00 0.00 0.00
May 47147263.65 18549.08 22-MAY-05:01 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 5900379.35 1445.08 19-SEP-05:08 0.00 0.00 0.00 0.00 0.00
October 57672043.45 10050.55 10-OCT-05:01 0.00 0.00 0.00 0.00 0.00
November 0.511152E+09 18528.61 13-NOV-06:01 0.00 0.00 0.00 0.00 0.00
December 0.168174E+10 18529.48 13-DEC-06:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.792130E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.354685E+10 18549.08   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.430851E+10 26230.81 04-JAN-06:01 0.00 0.00 0.00 0.00 0.00
February 0.146107E+10 26296.13 17-FEB-06:01 0.00 0.00 0.00 0.00 0.00
March 0.629086E+09 26246.99 03-MAR-06:01 0.00 0.00 0.00 0.00 0.00
April 89189676.76 26255.60 29-APR-05:01 0.00 0.00 0.00 0.00 0.00
May 0.148077E+09 26304.93 22-MAY-05:01 0.00 0.00 0.00 0.00 0.00
June 172832.15 942.24 17-JUN-05:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 16029585.76 2616.72 19-SEP-05:05 0.00 0.00 0.00 0.00 0.00
October 80464254.53 26395.38 10-OCT-05:01 0.00 0.00 0.00 0.00 0.00
November 0.552328E+09 26316.10 30-NOV-06:01 0.00 0.00 0.00 0.00 0.00
December 0.167070E+10 26365.91 11-DEC-06:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.895562E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.430851E+10 26395.38   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.253831E+10 17703.94 07-JAN-06:02 0.00 0.00 0.00 0.00 0.00
February 0.580641E+09 17681.21 07-FEB-06:01 0.00 0.00 0.00 0.00 0.00
March 90027798.23 17678.80 06-MAR-06:01 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 14552108.67 12859.79 08-MAY-05:01 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:05 0.00 0.00 0.00 0.00 0.00
October 201521.79 133.92 10-OCT-06:00 0.00 0.00 0.00 0.00 0.00
November 49231295.27 17680.08 27-NOV-06:01 0.00 0.00 0.00 0.00 0.00
December 0.245836E+09 17676.60 29-DEC-06:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.351880E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.253831E+10 17703.94   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: VAV_MID WITH REHEAT HEATING COIL

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.402079E+12 825840.54 10-JAN-22:00 0.00 0.00 0.00 0.00 0.00
February 0.219980E+12 643291.98 01-FEB-07:03 0.00 0.00 0.00 0.00 0.00
March 0.127331E+12 550592.71 06-MAR-07:10 0.00 0.00 0.00 0.00 0.00
April 0.297208E+11 259633.25 29-APR-06:10 0.00 0.00 0.00 0.00 0.00
May 0.185239E+11 201737.30 08-MAY-06:10 0.00 0.00 0.00 0.00 0.00
June 0.281312E+09 74287.97 16-JUN-07:00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.320123E+10 93711.58 19-SEP-06:30 0.00 0.00 0.00 0.00 0.00
October 0.214835E+11 264019.44 10-OCT-06:20 0.00 0.00 0.00 0.00 0.00
November 0.952097E+11 436528.98 27-NOV-07:10 0.00 0.00 0.00 0.00 0.00
December 0.258249E+12 701628.44 29-DEC-08:00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.117606E+13     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.402079E+12 825840.54   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: CORE_MID VAV BOX REHEAT COIL

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.159645E+11 635924.43 02-JAN-05:03 0.00 0.00 0.00 0.00 0.00
February 0.400998E+10 635392.73 06-FEB-05:04 0.00 0.00 0.00 0.00 0.00
March 0.174979E+10 633382.37 06-MAR-06:02 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:05 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.159917E+10 634800.03 27-NOV-06:03 0.00 0.00 0.00 0.00 0.00
December 0.620659E+10 634860.57 26-DEC-06:03 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.295300E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.159645E+11 635924.43   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.123651E+12 149980.49 12-JAN-06:04 0.00 0.00 0.00 0.00 0.00
February 0.614166E+11 149583.27 07-FEB-06:02 0.00 0.00 0.00 0.00 0.00
March 0.332930E+11 149057.07 06-MAR-06:04 0.00 0.00 0.00 0.00 0.00
April 0.688795E+10 160639.33 06-APR-05:03 0.00 0.00 0.00 0.00 0.00
May 0.490266E+10 160069.72 11-MAY-05:02 0.00 0.00 0.00 0.00 0.00
June 39760311.66 27805.98 17-JUN-05:03 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 17774225.34 44289.10 18-AUG-05:03 0.00 0.00 0.00 0.00 0.00
September 0.152028E+10 157430.37 12-SEP-05:03 0.00 0.00 0.00 0.00 0.00
October 0.652061E+10 161379.53 21-OCT-05:03 0.00 0.00 0.00 0.00 0.00
November 0.329568E+11 155721.13 04-NOV-05:02 0.00 0.00 0.00 0.00 0.00
December 0.799647E+11 150128.66 04-DEC-06:02 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.351171E+12     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.123651E+12 161379.53   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.864823E+11 219945.45 10-JAN-05:02 0.00 0.00 0.00 0.00 0.00
February 0.429988E+11 219823.93 21-FEB-05:12 0.00 0.00 0.00 0.00 0.00
March 0.259790E+11 220044.06 06-MAR-06:04 0.00 0.00 0.00 0.00 0.00
April 0.731352E+10 219069.17 15-APR-04:01 0.00 0.00 0.00 0.00 0.00
May 0.495026E+10 219243.96 22-MAY-04:42 0.00 0.00 0.00 0.00 0.00
June 0.190326E+09 46660.64 17-JUN-05:03 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 67900947.97 69673.03 18-AUG-05:03 0.00 0.00 0.00 0.00 0.00
September 0.203844E+10 200459.31 19-SEP-04:11 0.00 0.00 0.00 0.00 0.00
October 0.687602E+10 219290.33 31-OCT-04:11 0.00 0.00 0.00 0.00 0.00
November 0.276001E+11 219857.36 27-NOV-05:02 0.00 0.00 0.00 0.00 0.00
December 0.601194E+11 220052.46 26-DEC-05:22 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.264616E+12     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.864823E+11 220052.46   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.881079E+11 268780.94 31-JAN-06:03 0.00 0.00 0.00 0.00 0.00
February 0.376699E+11 269352.44 07-FEB-06:02 0.00 0.00 0.00 0.00 0.00
March 0.256481E+11 268470.61 06-MAR-06:04 0.00 0.00 0.00 0.00 0.00
April 0.802470E+10 266897.86 29-APR-04:02 0.00 0.00 0.00 0.00 0.00
May 0.694498E+10 267737.57 08-MAY-04:02 0.00 0.00 0.00 0.00 0.00
June 0.292990E+09 97948.49 17-JUN-05:03 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.121233E+09 75330.07 18-AUG-05:03 0.00 0.00 0.00 0.00 0.00
September 0.166331E+10 198964.40 19-SEP-04:11 0.00 0.00 0.00 0.00 0.00
October 0.466064E+10 267659.26 10-OCT-05:03 0.00 0.00 0.00 0.00 0.00
November 0.233642E+11 269397.98 28-NOV-06:02 0.00 0.00 0.00 0.00 0.00
December 0.539178E+11 268679.86 27-DEC-06:02 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.250416E+12     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.881079E+11 269397.98   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.820086E+11 227068.82 10-JAN-05:02 0.00 0.00 0.00 0.00 0.00
February 0.392534E+11 226594.27 11-FEB-05:12 0.00 0.00 0.00 0.00 0.00
March 0.247366E+11 226409.34 04-MAR-05:02 0.00 0.00 0.00 0.00 0.00
April 0.644097E+10 226025.42 01-APR-04:11 0.00 0.00 0.00 0.00 0.00
May 0.475551E+10 226310.45 22-MAY-04:42 0.00 0.00 0.00 0.00 0.00
June 0.230424E+09 56198.13 17-JUN-05:03 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.118340E+09 50047.47 18-AUG-05:03 0.00 0.00 0.00 0.00 0.00
September 0.209375E+10 160778.10 19-SEP-04:11 0.00 0.00 0.00 0.00 0.00
October 0.653854E+10 226234.94 10-OCT-05:01 0.00 0.00 0.00 0.00 0.00
November 0.241585E+11 226975.17 27-NOV-05:02 0.00 0.00 0.00 0.00 0.00
December 0.525056E+11 227171.75 26-DEC-05:22 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.242840E+12     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.820086E+11 227171.75   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: VAV_TOP WITH REHEAT HEATING COIL

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.457296E+11 88398.87 10-JAN-22:00 0.00 0.00 0.00 0.00 0.00
February 0.249631E+11 71199.26 01-FEB-07:03 0.00 0.00 0.00 0.00 0.00
March 0.160272E+11 62089.62 04-MAR-07:05 0.00 0.00 0.00 0.00 0.00
April 0.506221E+10 32546.57 29-APR-06:05 0.00 0.00 0.00 0.00 0.00
May 0.299226E+10 24941.02 08-MAY-06:10 0.00 0.00 0.00 0.00 0.00
June 0.154390E+09 10533.78 16-JUN-07:00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 1445068.90 1572.18 18-AUG-06:05 0.00 0.00 0.00 0.00 0.00
September 0.888322E+09 14415.99 19-SEP-06:10 0.00 0.00 0.00 0.00 0.00
October 0.375791E+10 31909.20 10-OCT-06:10 0.00 0.00 0.00 0.00 0.00
November 0.121933E+11 46658.20 27-NOV-07:50 0.00 0.00 0.00 0.00 0.00
December 0.308375E+11 77233.97 29-DEC-08:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.142607E+12     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.457296E+11 88398.87   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: CORE_TOP VAV BOX REHEAT COIL

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.148305E+11 84267.66 02-JAN-05:53 0.00 0.00 0.00 0.00 0.00
February 0.644804E+10 84239.88 07-FEB-06:02 0.00 0.00 0.00 0.00 0.00
March 0.368362E+10 84218.08 07-MAR-06:03 0.00 0.00 0.00 0.00 0.00
April 0.439733E+09 82983.11 10-APR-05:02 0.00 0.00 0.00 0.00 0.00
May 0.992832E+09 84224.35 08-MAY-05:03 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 25235879.51 12931.51 19-SEP-05:03 0.00 0.00 0.00 0.00 0.00
October 0.666311E+09 84223.88 10-OCT-05:03 0.00 0.00 0.00 0.00 0.00
November 0.406143E+10 83998.91 20-NOV-06:03 0.00 0.00 0.00 0.00 0.00
December 0.933647E+10 83985.14 11-DEC-06:03 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.404842E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.148305E+11 84267.66   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.191053E+11 17212.17 03-JAN-06:04 0.00 0.00 0.00 0.00 0.00
February 0.106925E+11 17217.14 21-FEB-05:53 0.00 0.00 0.00 0.00 0.00
March 0.713354E+10 17216.79 20-MAR-04:53 0.00 0.00 0.00 0.00 0.00
April 0.235713E+10 17207.09 10-APR-05:04 0.00 0.00 0.00 0.00 0.00
May 0.168875E+10 17215.88 01-MAY-04:33 0.00 0.00 0.00 0.00 0.00
June 67703078.23 17127.90 17-JUN-05:03 0.00 0.00 0.00 0.00 0.00
July 523741.49 1538.88 08-JUL-05:03 0.00 0.00 0.00 0.00 0.00
August 45012347.28 17126.60 18-AUG-05:03 0.00 0.00 0.00 0.00 0.00
September 0.725256E+09 17251.47 13-SEP-04:13 0.00 0.00 0.00 0.00 0.00
October 0.240377E+10 17264.12 10-OCT-04:53 0.00 0.00 0.00 0.00 0.00
November 0.740258E+10 17264.77 06-NOV-06:03 0.00 0.00 0.00 0.00 0.00
December 0.144232E+11 17217.90 09-DEC-06:03 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.660453E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 523741.49 1538.88   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.191053E+11 17264.77   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.127141E+11 22643.46 12-JAN-05:13 0.00 0.00 0.00 0.00 0.00
February 0.675374E+10 22641.50 11-FEB-05:13 0.00 0.00 0.00 0.00 0.00
March 0.464722E+10 22564.88 18-MAR-04:12 0.00 0.00 0.00 0.00 0.00
April 0.166610E+10 22584.51 29-APR-05:02 0.00 0.00 0.00 0.00 0.00
May 0.119995E+10 22590.47 08-MAY-04:32 0.00 0.00 0.00 0.00 0.00
June 74796860.42 22454.92 17-JUN-04:12 0.00 0.00 0.00 0.00 0.00
July 7273476.53 2056.48 08-JUL-05:03 0.00 0.00 0.00 0.00 0.00
August 48787752.53 12430.93 18-AUG-04:12 0.00 0.00 0.00 0.00 0.00
September 0.587613E+09 22572.32 19-SEP-04:12 0.00 0.00 0.00 0.00 0.00
October 0.167958E+10 22585.70 10-OCT-04:13 0.00 0.00 0.00 0.00 0.00
November 0.505885E+10 22594.67 29-NOV-05:02 0.00 0.00 0.00 0.00 0.00
December 0.973321E+10 22599.88 16-DEC-05:13 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.441712E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 7273476.53 2056.48   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.127141E+11 22643.46   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.144675E+11 28567.15 12-JAN-05:13 0.00 0.00 0.00 0.00 0.00
February 0.696235E+10 28579.12 08-FEB-06:02 0.00 0.00 0.00 0.00 0.00
March 0.554720E+10 28656.05 22-MAR-05:02 0.00 0.00 0.00 0.00 0.00
April 0.234381E+10 28547.65 29-APR-05:02 0.00 0.00 0.00 0.00 0.00
May 0.196172E+10 28657.66 09-MAY-04:02 0.00 0.00 0.00 0.00 0.00
June 0.219896E+09 28420.14 17-JUN-04:12 0.00 0.00 0.00 0.00 0.00
July 15718141.84 5997.03 08-JUL-05:03 0.00 0.00 0.00 0.00 0.00
August 82059590.59 18163.48 18-AUG-05:03 0.00 0.00 0.00 0.00 0.00
September 0.709444E+09 28539.44 20-SEP-04:12 0.00 0.00 0.00 0.00 0.00
October 0.172662E+10 28746.47 10-OCT-04:53 0.00 0.00 0.00 0.00 0.00
November 0.505166E+10 28568.89 21-NOV-05:03 0.00 0.00 0.00 0.00 0.00
December 0.102949E+11 28576.19 21-DEC-06:02 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.493828E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 15718141.84 5997.03   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.144675E+11 28746.47   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.122803E+11 25664.52 21-JAN-05:02 0.00 0.00 0.00 0.00 0.00
February 0.620394E+10 25579.32 09-FEB-05:02 0.00 0.00 0.00 0.00 0.00
March 0.454763E+10 25571.68 04-MAR-05:03 0.00 0.00 0.00 0.00 0.00
April 0.164952E+10 25524.91 19-APR-04:11 0.00 0.00 0.00 0.00 0.00
May 0.122146E+10 25651.98 22-MAY-05:02 0.00 0.00 0.00 0.00 0.00
June 0.139822E+09 19723.65 17-JUN-04:12 0.00 0.00 0.00 0.00 0.00
July 3089611.83 1164.81 08-JUL-05:10 0.00 0.00 0.00 0.00 0.00
August 65359417.18 10943.61 18-AUG-05:03 0.00 0.00 0.00 0.00 0.00
September 0.656127E+09 25535.74 13-SEP-04:11 0.00 0.00 0.00 0.00 0.00
October 0.171931E+10 25559.02 10-OCT-04:12 0.00 0.00 0.00 0.00 0.00
November 0.449263E+10 25678.25 29-NOV-05:02 0.00 0.00 0.00 0.00 0.00
December 0.853060E+10 25674.58 19-DEC-05:22 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.415098E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 3089611.83 1164.81   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.122803E+11 25678.25   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: CAV_BAS HEATING COIL

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.309488E+09 23134.85 10-JAN-22:00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:05 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:05 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.309488E+09     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.309488E+09 23134.85   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: AIRLOOP DATACENTER BASEMENT HEATING COIL

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:05 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:05 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:05 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: AIRLOOP DATACENTER BOT HEATING COIL

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:05 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:05 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:05 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: AIRLOOP DATACENTER MID HEATING COIL

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:05 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:05 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:05 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: AIRLOOP DATACENTER TOP HEATING COIL

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:05 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:05 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:05 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:05 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:05 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:05 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: AIRLOOP DATACENTER BOT_SUPPHEATCOIL

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:05 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:05 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:05 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: AIRLOOP DATACENTER MID_SUPPHEATCOIL

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:05 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:05 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:05 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: AIRLOOP DATACENTER TOP_SUPPHEATCOIL

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:05 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:05 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:05 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: VAV_BOT WITH REHEAT COOLING COIL

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 0.00 0.00
February 0.00 0.00 0.736348E+09 0.736348E+09 46910.45 27-FEB-15:30 46910.45 0.00
March 0.00 0.00 64191064.87 64191064.87 12393.11 14-MAR-13:30 12393.11 0.00
April 0.00 0.00 0.713072E+10 0.713072E+10 90172.76 06-APR-16:00 90172.76 0.00
May 0.00 0.00 0.195332E+11 0.195332E+11 121968.00 19-MAY-15:20 121968.00 0.04
June 0.00 0.00 0.638689E+11 0.638186E+11 138857.99 29-JUN-14:40 138857.99 0.22
July 0.00 0.00 0.108592E+12 0.108413E+12 165129.77 17-JUL-15:20 165129.77 0.37
August 0.00 0.00 0.991574E+11 0.991574E+11 164372.12 07-AUG-15:20 164372.12 0.20
September 0.00 0.00 0.413584E+11 0.400217E+11 214303.48 07-SEP-15:00 113475.06 0.16
October 0.00 0.00 0.112922E+11 0.112922E+11 112935.89 18-OCT-15:50 112935.89 0.00
November 0.00 0.00 0.616459E+09 0.616459E+09 20234.37 03-NOV-14:00 20234.37 0.00
December 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 0.00 0.00
                 
Annual Sum or Average 0.00 0.00 0.352350E+12 0.350784E+12       0.08
Minimum of Months 0.00 0.00 0.00 0.00 0.00   0.00 0.00
Maximum of Months 0.00 0.00 0.108592E+12 0.108413E+12 214303.48   165129.77 0.37



Table of Contents

Report: CoilReportMonthly

For: VAV_MID WITH REHEAT COOLING COIL

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 31506.06 31506.06 3.41 03-JAN-06:00 3.41 0.00
February 0.00 0.00 0.582135E+10 0.582135E+10 343626.02 27-FEB-14:00 343626.02 0.00
March 0.00 0.00 0.247060E+09 0.247060E+09 68784.96 14-MAR-13:30 68784.96 0.00
April 0.00 0.00 0.511108E+11 0.511108E+11 720946.46 06-APR-16:00 720946.46 0.00
May 0.00 0.00 0.167845E+12 0.167845E+12 1165675.81 19-MAY-15:30 1165675.81 0.04
June 0.00 0.00 0.544162E+12 0.543727E+12 1309120.82 29-JUN-14:50 1309120.82 0.20
July 0.00 0.00 0.910049E+12 0.908886E+12 1524359.19 17-JUL-15:30 1524359.19 0.32
August 0.00 0.00 0.790119E+12 0.790119E+12 1449182.73 07-AUG-15:40 1449182.73 0.18
September 0.00 0.00 0.364666E+12 0.352764E+12 2000275.77 07-SEP-15:00 1058588.83 0.16
October 0.00 0.00 0.893588E+11 0.893588E+11 956004.05 18-OCT-15:20 956004.05 0.00
November 0.00 0.00 0.448429E+10 0.448429E+10 187325.68 03-NOV-13:55 187325.68 0.00
December 0.00 0.00 64277.76 64277.76 3.26 17-DEC-15:55 3.26 0.00
                 
Annual Sum or Average 0.00 0.00 0.292786E+13 0.291436E+13       0.08
Minimum of Months 0.00 0.00 31506.06 31506.06 3.26   3.26 0.00
Maximum of Months 0.00 0.00 0.910049E+12 0.908886E+12 2000275.77   1524359.19 0.32



Table of Contents

Report: CoilReportMonthly

For: VAV_TOP WITH REHEAT COOLING COIL

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 52824.02 52824.02 147.30 26-JAN-00:50 147.30 0.00
February 0.00 0.00 0.390482E+09 0.390482E+09 27817.44 27-FEB-13:40 27817.44 0.00
March 0.00 0.00 2331981.52 2331981.52 644.13 14-MAR-14:00 644.13 0.00
April 0.00 0.00 0.479342E+10 0.479342E+10 73320.21 06-APR-16:00 73320.21 0.00
May 0.00 0.00 0.173282E+11 0.173282E+11 137325.88 19-MAY-15:30 137325.88 0.04
June 0.00 0.00 0.588673E+11 0.588156E+11 152417.15 29-JUN-14:50 152417.15 0.20
July 0.00 0.00 0.988626E+11 0.987638E+11 180544.94 17-JUL-15:30 180544.94 0.32
August 0.00 0.00 0.839504E+11 0.839504E+11 170583.07 07-AUG-15:40 170583.07 0.17
September 0.00 0.00 0.370519E+11 0.358533E+11 202482.58 07-SEP-15:20 116218.37 0.15
October 0.00 0.00 0.773586E+10 0.773586E+10 98579.15 18-OCT-15:10 98579.15 0.00
November 0.00 0.00 0.331261E+09 0.331261E+09 11249.30 04-NOV-14:00 11249.30 0.00
December 0.00 0.00 126715.88 126715.88 542.99 28-DEC-00:33 542.99 0.00
                 
Annual Sum or Average 0.00 0.00 0.309314E+12 0.307965E+12       0.07
Minimum of Months 0.00 0.00 52824.02 52824.02 147.30   147.30 0.00
Maximum of Months 0.00 0.00 0.988626E+11 0.987638E+11 202482.58   180544.94 0.32



Table of Contents

Report: CoilReportMonthly

For: CAV_BAS COOLING COIL

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 430925.51 430925.51 4458.97 24-JAN-05:11 4458.97 0.00
February 0.00 0.00 0.282169E+09 0.282169E+09 25368.65 27-FEB-15:00 25368.65 0.00
March 0.00 0.00 36227.49 36227.49 60.38 01-MAR-08:00 60.38 0.00
April 0.00 0.00 0.252028E+10 0.252028E+10 52517.91 07-APR-14:00 52517.91 0.00
May 0.00 0.00 0.934050E+10 0.934050E+10 64225.30 29-MAY-14:30 64225.30 0.03
June 0.00 0.00 0.331920E+11 0.331666E+11 72998.31 13-JUN-04:12 33354.29 0.15
July 0.00 0.00 0.565008E+11 0.564569E+11 150741.40 16-JUL-17:50 127736.43 0.27
August 0.00 0.00 0.517700E+11 0.517700E+11 126509.60 06-AUG-19:20 126509.60 0.16
September 0.00 0.00 0.214620E+11 0.210835E+11 137559.32 03-SEP-13:58 137559.32 0.13
October 0.00 0.00 0.593250E+10 0.593250E+10 62656.09 18-OCT-14:00 62656.09 0.00
November 0.00 0.00 75754208.78 75754208.78 29207.11 17-NOV-06:03 29207.11 0.00
December 0.00 0.00 22839.71 22839.71 38.07 15-DEC-18:10 38.07 0.00
                 
Annual Sum or Average 0.00 0.00 0.181077E+12 0.180629E+12       0.06
Minimum of Months 0.00 0.00 22839.71 22839.71 38.07   38.07 0.00
Maximum of Months 0.00 0.00 0.565008E+11 0.564569E+11 150741.40   137559.32 0.27



Table of Contents

Report: CoilReportMonthly

For: AIRLOOP DATACENTER BASEMENT COOLING COIL

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.897821E+10 0.781808E+10 5237.54 03-JAN-15:00 4757.70 0.00
February 0.00 0.00 0.135760E+11 0.120041E+11 17900.29 27-FEB-16:00 17900.29 0.00
March 0.00 0.00 0.150884E+11 0.143569E+11 6752.56 31-MAR-23:10 5614.25 0.00
April 0.00 0.00 0.751158E+11 0.720706E+11 316261.64 07-APR-14:00 316261.64 0.00
May 0.00 0.00 0.181394E+11 0.169445E+11 139501.15 19-MAY-13:50 133355.86 0.00
June 0.00 0.00 0.136834E+12 0.123616E+12 325811.76 20-JUN-18:50 221525.88 0.00
July 0.00 0.00 0.448356E+12 0.401143E+12 415623.81 19-JUL-10:50 315701.60 0.00
August 0.00 0.00 0.569901E+12 0.519336E+12 413350.51 08-AUG-12:00 346369.33 0.00
September 0.00 0.00 0.454441E+11 0.414243E+11 216458.25 07-SEP-16:00 127271.00 0.00
October 0.00 0.00 0.247462E+11 0.231347E+11 178394.39 18-OCT-15:00 178394.39 0.00
November 0.00 0.00 0.165686E+11 0.156691E+11 68223.84 17-NOV-17:00 65122.94 0.00
December 0.00 0.00 0.166132E+11 0.162722E+11 65679.09 10-DEC-02:00 65679.09 0.00
                 
Annual Sum or Average 0.00 0.00 0.138936E+13 0.126379E+13       0.00
Minimum of Months 0.00 0.00 0.897821E+10 0.781808E+10 5237.54   4757.70 0.00
Maximum of Months 0.00 0.00 0.569901E+12 0.519336E+12 415623.81   346369.33 0.00



Table of Contents

Report: CoilReportMonthly

For: AIRLOOP DATACENTER BOT COOLING COIL

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.291329E+10 0.291296E+10 2401.99 13-JAN-16:20 2401.99 0.00
February 0.00 0.00 0.827107E+10 0.827107E+10 5256.52 26-FEB-17:27 5256.52 0.00
March 0.00 0.00 0.149973E+11 0.149973E+11 7466.50 31-MAR-24:00 7466.50 0.00
April 0.00 0.00 0.201480E+11 0.201392E+11 9157.56 22-APR-18:10 9157.56 0.00
May 0.00 0.00 0.576652E+10 0.573886E+10 4164.37 31-MAY-24:00 4164.37 0.00
June 0.00 0.00 0.111022E+11 0.110072E+11 6036.03 30-JUN-23:03 6016.52 0.00
July 0.00 0.00 0.168060E+11 0.167039E+11 7926.56 31-JUL-23:45 7926.56 0.00
August 0.00 0.00 0.217253E+11 0.216487E+11 9145.19 05-AUG-20:00 9145.19 0.00
September 0.00 0.00 0.587028E+10 0.577824E+10 3959.58 30-SEP-24:00 3959.58 0.00
October 0.00 0.00 0.106273E+11 0.106145E+11 5588.44 31-OCT-24:00 5588.44 0.00
November 0.00 0.00 0.146614E+11 0.146588E+11 6736.38 03-NOV-16:00 6665.18 0.00
December 0.00 0.00 0.194801E+11 0.194799E+11 8462.04 06-DEC-16:10 8438.69 0.00
                 
Annual Sum or Average 0.00 0.00 0.152369E+12 0.151951E+12       0.00
Minimum of Months 0.00 0.00 0.291329E+10 0.291296E+10 2401.99   2401.99 0.00
Maximum of Months 0.00 0.00 0.217253E+11 0.216487E+11 9157.56   9157.56 0.00



Table of Contents

Report: CoilReportMonthly

For: AIRLOOP DATACENTER MID COOLING COIL

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.756959E+10 0.756360E+10 20207.05 13-JAN-16:30 20207.05 0.00
February 0.00 0.00 0.590737E+11 0.590737E+11 45674.11 28-FEB-17:00 45674.11 0.00
March 0.00 0.00 0.124694E+12 0.124694E+12 65460.75 28-MAR-17:50 65460.75 0.00
April 0.00 0.00 0.180360E+12 0.180271E+12 85319.65 22-APR-18:12 85319.65 0.00
May 0.00 0.00 0.465520E+11 0.462846E+11 39332.27 31-MAY-24:00 39332.27 0.00
June 0.00 0.00 0.101940E+12 0.101001E+12 58852.63 30-JUN-23:03 58655.87 0.00
July 0.00 0.00 0.158348E+12 0.157333E+12 76965.51 31-JUL-23:53 76965.51 0.00
August 0.00 0.00 0.204472E+12 0.203711E+12 87881.53 03-AUG-18:50 87881.53 0.00
September 0.00 0.00 0.493391E+11 0.484440E+11 35042.68 30-SEP-23:30 35042.68 0.00
October 0.00 0.00 0.883410E+11 0.882148E+11 48655.50 15-OCT-17:06 48655.50 0.00
November 0.00 0.00 0.120428E+12 0.120401E+12 62335.05 03-NOV-16:00 61634.34 0.00
December 0.00 0.00 0.157995E+12 0.157992E+12 77285.57 06-DEC-16:10 77011.85 0.00
                 
Annual Sum or Average 0.00 0.00 0.129911E+13 0.129498E+13       0.00
Minimum of Months 0.00 0.00 0.756959E+10 0.756360E+10 20207.05   20207.05 0.00
Maximum of Months 0.00 0.00 0.204472E+12 0.203711E+12 87881.53   87881.53 0.00



Table of Contents

Report: CoilReportMonthly

For: AIRLOOP DATACENTER TOP COOLING COIL

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.304978E+09 0.304774E+09 1968.42 13-JAN-16:30 1968.42 0.00
February 0.00 0.00 0.440339E+10 0.440339E+10 4520.39 28-FEB-17:00 4520.39 0.00
March 0.00 0.00 0.109375E+11 0.109375E+11 6546.80 28-MAR-17:50 6546.80 0.00
April 0.00 0.00 0.169319E+11 0.169231E+11 8603.18 25-APR-18:10 8603.18 0.00
May 0.00 0.00 0.400971E+10 0.398330E+10 3862.25 31-MAY-23:30 3862.25 0.00
June 0.00 0.00 0.996639E+10 0.987272E+10 5885.09 30-JUN-23:03 5865.18 0.00
July 0.00 0.00 0.157522E+11 0.156509E+11 7690.64 31-JUL-23:53 7690.64 0.00
August 0.00 0.00 0.202910E+11 0.202151E+11 8907.10 05-AUG-19:55 8907.10 0.00
September 0.00 0.00 0.438949E+10 0.430110E+10 3666.99 04-SEP-17:51 3666.99 0.00
October 0.00 0.00 0.749428E+10 0.748190E+10 4879.54 18-OCT-17:00 4879.54 0.00
November 0.00 0.00 0.102901E+11 0.102875E+11 6187.49 03-NOV-16:00 6117.65 0.00
December 0.00 0.00 0.139265E+11 0.139262E+11 7669.92 06-DEC-16:10 7644.58 0.00
                 
Annual Sum or Average 0.00 0.00 0.118697E+12 0.118288E+12       0.00
Minimum of Months 0.00 0.00 0.304978E+09 0.304774E+09 1968.42   1968.42 0.00
Maximum of Months 0.00 0.00 0.202910E+11 0.202151E+11 8907.10   8907.10 0.00



Table of Contents

Report: PlantLoopDemandReportMonthly

For: HEATSYS1

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 0.00 0.00 01-JAN-00:05 357372.88 2138250.95 23-JAN-05:11
February 0.00 0.00 01-FEB-00:05 200329.81 2081493.97 07-FEB-06:01
March 0.00 0.00 01-MAR-00:10 107069.79 1927328.50 06-MAR-05:01
April 0.00 0.00 01-APR-00:10 27907.21 1629520.69 01-APR-04:11
May 0.00 0.00 01-MAY-00:10 18872.98 1654154.34 09-MAY-04:01
June 0.00 0.00 01-JUN-00:10 647.71 370308.82 17-JUN-05:03
July 0.00 0.00 01-JUL-00:10 9.28 10059.99 08-JUL-05:03
August 0.00 0.00 01-AUG-00:03 210.95 372323.64 18-AUG-05:03
September 0.00 0.00 01-SEP-00:05 5428.51 1439883.70 19-SEP-04:11
October 0.00 0.00 01-OCT-00:10 21814.21 1521347.06 11-OCT-04:01
November 0.00 0.00 01-NOV-00:10 95381.58 1867617.05 28-NOV-06:01
December 0.00 0.00 01-DEC-00:10 228266.37 2050482.29 04-DEC-06:01
             
Annual Sum or Average 0.00     88307.66    
Minimum of Months 0.00 0.00   9.28 10059.99  
Maximum of Months 0.00 0.00   357372.88 2138250.95  



Table of Contents

Report: PlantLoopDemandReportMonthly

For: COOLSYS1_SUPPLY

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 29.20 5033.40 25-JAN-10:40 0.00 0.00 01-JAN-00:05
February 3210.02 432515.78 27-FEB-15:30 0.00 0.00 01-FEB-00:05
March 567.45 94270.74 14-MAR-13:30 0.00 0.00 01-MAR-00:10
April 26167.72 920492.44 06-APR-16:00 0.00 0.00 01-APR-00:10
May 82289.60 1494152.87 19-MAY-15:30 0.00 0.00 01-MAY-00:10
June 279040.04 1671563.59 29-JUN-14:50 0.00 0.00 01-JUN-00:10
July 450799.64 1958274.67 17-JUL-15:30 0.00 0.00 01-JUL-00:10
August 394445.08 1920661.72 07-AUG-09:20 0.00 0.00 01-AUG-00:03
September 184483.52 2896316.02 07-SEP-15:00 0.00 0.00 01-SEP-00:05
October 44322.24 1567281.43 18-OCT-13:40 0.00 0.00 01-OCT-00:10
November 2651.95 212763.59 03-NOV-14:00 0.00 0.00 01-NOV-00:10
December 255.19 5277.04 28-DEC-00:33 0.00 0.00 01-DEC-00:10
             
Annual Sum or Average 123326.40     0.00    
Minimum of Months 29.20 5033.40   0.00 0.00  
Maximum of Months 450799.64 2896316.02   0.00 0.00  



Table of Contents

Report: PlantLoopDemandReportMonthly

For: COOLSYS1_DEMAND

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 0.00 17.01 24-JAN-05:11 0.00 0.00 01-JAN-00:05
February 2872.13 428889.63 27-FEB-15:30 0.00 0.00 01-FEB-00:05
March 133.57 89789.35 14-MAR-13:30 0.00 0.00 01-MAR-00:10
April 25252.63 921422.88 06-APR-16:00 0.00 0.00 01-APR-00:10
May 80785.67 1485901.24 19-MAY-15:30 0.00 0.00 01-MAY-00:10
June 274664.54 1663765.26 29-JUN-14:50 0.00 0.00 01-JUN-00:10
July 445025.93 1952136.00 17-JUL-15:30 0.00 0.00 01-JUL-00:10
August 387869.83 2024175.58 07-AUG-09:20 0.00 0.00 01-AUG-00:03
September 181628.84 2702859.85 07-SEP-15:00 0.00 0.00 01-SEP-00:05
October 43084.78 1275970.05 18-OCT-13:20 0.00 0.00 01-OCT-00:10
November 2137.50 208240.74 03-NOV-14:00 0.00 0.00 01-NOV-00:10
December 0.08 567.73 28-DEC-00:33 0.00 0.00 01-DEC-00:10
             
Annual Sum or Average 121246.08     0.00    
Minimum of Months 0.00 17.01   0.00 0.00  
Maximum of Months 445025.93 2702859.85   0.00 0.00  



Table of Contents

Report: PlantLoopDemandReportMonthly

For: SINGLE WATER PLANT LOOP

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 13869.89 39733.81 13-JAN-16:30 0.00 0.00 01-JAN-00:05
February 49498.60 172318.16 27-FEB-16:00 0.00 0.00 01-FEB-00:05
March 82265.32 110181.10 31-MAR-23:30 0.00 0.00 01-MAR-00:10
April 166238.63 1156364.30 07-APR-14:00 0.00 0.00 01-APR-00:10
May 74231.07 989882.11 20-MAY-16:00 0.00 0.00 01-MAY-00:10
June 296393.79 1399626.97 29-JUN-15:00 0.00 0.00 01-JUN-00:10
July 707051.38 1987835.02 17-JUL-16:00 0.00 0.00 01-JUL-00:10
August 768815.98 2082790.46 05-AUG-16:00 0.00 0.00 01-AUG-00:03
September 159964.43 1264560.89 02-SEP-17:00 0.00 0.00 01-SEP-00:05
October 80970.24 863639.82 18-OCT-15:00 0.00 0.00 01-OCT-00:10
November 83026.07 223313.46 17-NOV-17:00 0.00 0.00 01-NOV-00:10
December 102015.30 186302.37 10-DEC-02:00 0.00 0.00 01-DEC-00:10
             
Annual Sum or Average 217151.90     0.00    
Minimum of Months 13869.89 39733.81   0.00 0.00  
Maximum of Months 768815.98 2082790.46   0.00 0.00  



Table of Contents

Report: PlantLoopDemandReportMonthly

For: SWHSYS1

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 0.00 0.00 01-JAN-00:05 17319.97 58842.16 31-JAN-12:50
February 0.00 0.00 01-FEB-00:05 17697.27 59153.14 14-FEB-12:50
March 0.00 0.00 01-MAR-00:10 18533.99 59067.02 01-MAR-12:20
April 0.00 0.00 01-APR-00:10 16872.11 57468.27 03-APR-11:20
May 0.00 0.00 01-MAY-00:10 16515.05 54989.08 01-MAY-11:45
June 0.00 0.00 01-JUN-00:10 15919.94 51669.30 01-JUN-11:30
July 0.00 0.00 01-JUL-00:10 14087.85 48632.98 03-JUL-12:00
August 0.00 0.00 01-AUG-00:03 14975.18 46956.51 01-AUG-11:40
September 0.00 0.00 01-SEP-00:05 14302.73 48059.10 29-SEP-11:30
October 0.00 0.00 01-OCT-00:10 14888.01 50853.81 31-OCT-11:40
November 0.00 0.00 01-NOV-00:10 15937.13 54092.96 30-NOV-12:55
December 0.00 0.00 01-DEC-00:10 16262.03 56856.24 29-DEC-12:40
             
Annual Sum or Average 0.00     16100.07    
Minimum of Months 0.00 0.00   14087.85 46956.51  
Maximum of Months 0.00 0.00   18533.99 59153.14  



Table of Contents

Report: PlantLoopDemandReportMonthly

For: TOWERWATERSYS

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 0.64 6505.81 25-JAN-06:15 193.14 130376.09 25-JAN-10:40
February 2944.00 510389.08 27-FEB-15:30 1971.61 152342.40 14-FEB-05:01
March 74.43 78424.69 14-MAR-13:10 3647.26 156290.06 04-MAR-05:01
April 28533.15 1049719.40 06-APR-16:00 3524.46 136059.22 28-APR-05:50
May 98501.24 2409841.37 19-MAY-14:30 2553.88 146820.80 06-MAY-04:42
June 354723.15 2760760.80 20-JUN-15:40 1073.96 98209.70 14-JUN-13:30
July 585407.06 2857509.96 17-JUL-15:30 654.22 76171.27 29-JUL-07:20
August 498869.94 2427070.71 30-AUG-14:40 1529.41 78898.82 03-AUG-08:20
September 240289.25 4764385.16 07-SEP-15:00 2081.17 117838.80 18-SEP-14:40
October 50693.02 2230800.52 18-OCT-13:25 2999.12 153018.03 10-OCT-03:01
November 1818.55 272973.97 03-NOV-14:00 3407.81 152343.87 13-NOV-05:01
December 15.52 9135.90 29-DEC-02:30 2091.51 142113.31 17-DEC-15:53
             
Annual Sum or Average 156393.90     2141.24    
Minimum of Months 0.64 6505.81   193.14 76171.27  
Maximum of Months 585407.06 4764385.16   3647.26 156290.06  



Table of Contents

Report: FanReportMonthly

For: CAV_BAS FAN

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.169075E+11 0.87 11488.25 01-JAN-00:05 1.58
February 0.150723E+11 0.86 11488.25 01-FEB-06:03 1.59
March 0.182976E+11 0.94 11488.25 01-MAR-04:03 1.58
April 0.166235E+11 0.88 11488.25 01-APR-04:11 1.58
May 0.179135E+11 0.92 11488.25 01-MAY-03:05 1.58
June 0.175566E+11 0.93 11488.25 01-JUN-04:12 1.57
July 0.180332E+11 0.92 11488.25 01-JUL-04:12 1.57
August 0.192064E+11 0.98 11488.25 01-AUG-04:12 1.57
September 0.179129E+11 0.95 11488.25 01-SEP-04:12 1.57
October 0.177643E+11 0.91 11488.25 01-OCT-22:50 1.57
November 0.169256E+11 0.90 11488.25 01-NOV-04:11 1.58
December 0.167469E+11 0.86 11488.25 01-DEC-05:01 1.59
           
Annual Sum or Average 0.208960E+12 0.91      
Minimum of Months 0.150723E+11 0.86 11488.25   1.57
Maximum of Months 0.192064E+11 0.98 11488.25   1.59



Table of Contents

Report: FanReportMonthly

For: VAV_BOT WITH REHEAT FAN

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.438646E+10 0.38 16869.15 04-JAN-06:01 1.61
February 0.489911E+10 0.40 16869.15 24-FEB-06:01 1.61
March 0.722759E+10 0.46 16869.15 03-MAR-06:01 1.61
April 0.909821E+10 0.51 21182.36 24-APR-14:50 1.84
May 0.856492E+10 0.49 18095.32 19-MAY-15:20 1.66
June 0.133429E+11 0.65 21386.73 29-JUN-14:30 1.85
July 0.165048E+11 0.74 26466.43 17-JUL-15:00 2.11
August 0.174860E+11 0.78 26466.43 07-AUG-10:20 2.12
September 0.946832E+10 0.53 26466.43 05-SEP-04:12 2.12
October 0.815085E+10 0.47 18556.64 16-OCT-15:50 1.70
November 0.662822E+10 0.43 16869.15 13-NOV-06:01 1.61
December 0.568093E+10 0.39 16869.15 01-DEC-06:01 1.61
           
Annual Sum or Average 0.111438E+12 0.52      
Minimum of Months 0.438646E+10 0.38 16869.15   1.61
Maximum of Months 0.174860E+11 0.78 26466.43   2.12



Table of Contents

Report: FanReportMonthly

For: VAV_MID WITH REHEAT FAN

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.437676E+11 0.43 72525.12 02-JAN-05:01 1.01
February 0.385300E+11 0.40 86198.98 28-FEB-16:10 1.12
March 0.482040E+11 0.41 123570.27 24-MAR-05:03 1.39
April 0.520516E+11 0.40 143913.34 20-APR-05:02 1.52
May 0.637400E+11 0.44 181050.48 19-MAY-15:30 1.74
June 0.102027E+12 0.58 204331.30 29-JUN-14:30 1.89
July 0.124742E+12 0.62 244852.15 17-JUL-15:30 2.11
August 0.120460E+12 0.62 244852.15 10-AUG-15:40 2.12
September 0.739176E+11 0.48 244852.15 05-SEP-04:12 2.12
October 0.532459E+11 0.39 138946.11 27-OCT-05:02 1.49
November 0.426892E+11 0.38 123442.37 04-NOV-05:02 1.38
December 0.420256E+11 0.41 72525.12 04-DEC-06:01 1.01
           
Annual Sum or Average 0.805401E+12 0.46      
Minimum of Months 0.385300E+11 0.38 72525.12   1.01
Maximum of Months 0.124742E+12 0.62 244852.15   2.12



Table of Contents

Report: FanReportMonthly

For: VAV_TOP WITH REHEAT FAN

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.538050E+10 0.50 6364.07 02-JAN-04:01 0.88
February 0.425532E+10 0.44 6364.07 01-FEB-05:11 0.88
March 0.458644E+10 0.42 6904.04 28-MAR-15:50 0.92
April 0.438980E+10 0.37 13235.98 25-APR-15:50 1.34
May 0.571234E+10 0.41 18962.96 19-MAY-15:30 1.65
June 0.935228E+10 0.52 21323.18 29-JUN-14:50 1.79
July 0.117868E+11 0.56 27425.49 17-JUL-15:20 2.09
August 0.109047E+11 0.54 27067.48 10-AUG-15:40 2.08
September 0.628180E+10 0.43 20448.39 01-SEP-16:00 1.74
October 0.427012E+10 0.36 11956.24 18-OCT-16:00 1.26
November 0.418037E+10 0.40 6364.07 06-NOV-06:01 0.88
December 0.488727E+10 0.46 6364.07 01-DEC-06:01 0.88
           
Annual Sum or Average 0.759878E+11 0.45      
Minimum of Months 0.418037E+10 0.36 6364.07   0.88
Maximum of Months 0.117868E+11 0.56 27425.49   2.09



Table of Contents

Report: FanReportMonthly

For: AIRLOOP DATACENTER BASEMENT SUPPLY FAN

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.108397E+12 1.54 40470.70 01-JAN-00:05 1.54
February 0.979067E+11 1.54 40470.70 01-FEB-00:05 1.54
March 0.108397E+12 1.55 40470.70 01-MAR-00:20 1.54
April 0.104900E+12 1.55 40470.70 01-APR-00:10 1.55
May 0.108397E+12 1.54 40470.70 01-MAY-00:10 1.54
June 0.104900E+12 1.54 40470.70 01-JUN-00:10 1.54
July 0.108397E+12 1.54 40470.70 01-JUL-00:10 1.53
August 0.108397E+12 1.54 40470.70 01-AUG-00:03 1.54
September 0.104900E+12 1.54 40470.70 01-SEP-00:05 1.54
October 0.108397E+12 1.54 40470.70 01-OCT-00:30 1.54
November 0.104900E+12 1.55 40470.70 01-NOV-00:10 1.55
December 0.108397E+12 1.55 40470.70 01-DEC-00:10 1.55
           
Annual Sum or Average 0.127628E+13 1.54      
Minimum of Months 0.979067E+11 1.54 40470.70   1.53
Maximum of Months 0.108397E+12 1.55 40470.70   1.55



Table of Contents

Report: FanReportMonthly

For: AIRLOOP DATACENTER BOT SUPPLY FAN

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.175618E+10 1.05 655.68 01-JAN-00:10 1.05
February 0.158623E+10 1.05 655.68 01-FEB-00:05 1.05
March 0.175618E+10 1.05 655.68 01-MAR-00:10 1.05
April 0.169953E+10 1.05 655.68 01-APR-00:10 1.05
May 0.175618E+10 1.05 655.68 01-MAY-00:10 1.05
June 0.169953E+10 1.05 655.68 01-JUN-00:10 1.05
July 0.175618E+10 1.05 655.68 01-JUL-00:10 1.05
August 0.175618E+10 1.05 655.68 01-AUG-00:03 1.05
September 0.169953E+10 1.05 655.68 01-SEP-00:05 1.05
October 0.175618E+10 1.05 655.68 01-OCT-00:10 1.05
November 0.169953E+10 1.05 655.68 01-NOV-00:10 1.05
December 0.175618E+10 1.05 655.68 01-DEC-00:10 1.05
           
Annual Sum or Average 0.206776E+11 1.05      
Minimum of Months 0.158623E+10 1.05 655.68   1.05
Maximum of Months 0.175618E+10 1.05 655.68   1.05



Table of Contents

Report: FanReportMonthly

For: AIRLOOP DATACENTER MID SUPPLY FAN

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.168896E+11 1.05 6305.84 01-JAN-00:05 1.04
February 0.152551E+11 1.05 6305.84 01-FEB-00:05 1.05
March 0.168896E+11 1.05 6305.84 01-MAR-00:10 1.05
April 0.163447E+11 1.05 6305.84 01-APR-00:10 1.05
May 0.168896E+11 1.05 6305.84 01-MAY-00:20 1.05
June 0.163447E+11 1.05 6305.84 01-JUN-00:10 1.05
July 0.168896E+11 1.05 6305.84 01-JUL-00:10 1.05
August 0.168896E+11 1.05 6305.84 01-AUG-00:03 1.05
September 0.163447E+11 1.05 6305.84 01-SEP-00:05 1.05
October 0.168896E+11 1.05 6305.84 01-OCT-00:10 1.05
November 0.163447E+11 1.05 6305.84 01-NOV-00:10 1.05
December 0.168896E+11 1.05 6305.84 01-DEC-00:10 1.05
           
Annual Sum or Average 0.198861E+12 1.05      
Minimum of Months 0.152551E+11 1.05 6305.84   1.04
Maximum of Months 0.168896E+11 1.05 6305.84   1.05



Table of Contents

Report: FanReportMonthly

For: AIRLOOP DATACENTER TOP SUPPLY FAN

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.171738E+10 1.05 641.20 01-JAN-00:05 1.04
February 0.155118E+10 1.05 641.20 01-FEB-00:05 1.05
March 0.171738E+10 1.05 641.20 01-MAR-00:10 1.05
April 0.166198E+10 1.05 641.20 01-APR-00:10 1.05
May 0.171738E+10 1.05 641.20 01-MAY-00:10 1.05
June 0.166198E+10 1.05 641.20 01-JUN-00:10 1.05
July 0.171738E+10 1.05 641.20 01-JUL-00:10 1.05
August 0.171738E+10 1.05 641.20 01-AUG-00:03 1.05
September 0.166198E+10 1.05 641.20 01-SEP-00:05 1.05
October 0.171738E+10 1.05 641.20 01-OCT-00:10 1.05
November 0.166198E+10 1.05 641.20 01-NOV-00:10 1.05
December 0.171738E+10 1.05 641.20 01-DEC-00:10 1.05
           
Annual Sum or Average 0.202207E+11 1.05      
Minimum of Months 0.155118E+10 1.05 641.20   1.04
Maximum of Months 0.171738E+10 1.05 641.20   1.05



Table of Contents

Report: PumpReportMonthly

For: HEATSYS1 PUMP

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

PUMP ELECTRICITY ENERGY [J] PUMP FLUID HEAT GAIN ENERGY [J] PUMP ELECTRICITY RATE {Maximum} [W] PUMP ELECTRICITY RATE {TIMESTAMP} PUMP SHAFT POWER {AT MAX/MIN} [W] PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s]
January 0.413992E+10 0.372593E+10 6662.84 09-JAN-07:02 5996.55 5996.55 47.49 13.58
February 0.208727E+10 0.187854E+10 6560.06 06-FEB-06:01 5904.05 5904.05 45.52 12.95
March 0.121297E+10 0.109168E+10 6570.14 06-MAR-06:02 5913.13 5913.13 48.64 12.99
April 0.294524E+09 0.265072E+09 5371.44 29-APR-05:01 4834.30 4834.30 40.87 8.34
May 0.211905E+09 0.190714E+09 5430.00 08-MAY-05:01 4887.00 4887.00 43.33 8.50
June 6570375.36 5913337.83 1400.21 17-JUN-05:03 1260.19 1260.19 24.43 1.54
July 97654.39 87888.95 39.46 08-JUL-05:03 35.52 35.52 22.31 0.04
August 2225141.13 2002627.02 1396.43 18-AUG-05:03 1256.78 1256.78 23.96 1.53
September 56214495.73 50593046.15 4388.63 19-SEP-04:11 3949.77 3949.77 25.26 6.07
October 0.238423E+09 0.214581E+09 5330.61 10-OCT-05:01 4797.55 4797.55 41.66 8.23
November 0.104621E+10 0.941591E+09 6562.28 27-NOV-06:01 5906.05 5906.05 48.35 12.95
December 0.262590E+10 0.236331E+10 6566.03 30-DEC-06:01 5909.42 5909.42 47.88 12.97
                 
Annual Sum or Average 0.119222E+11 0.107300E+11            
Minimum of Months 97654.39 87888.95 39.46   35.52 35.52 22.31 0.04
Maximum of Months 0.413992E+10 0.372593E+10 6662.84   5996.55 5996.55 48.64 13.58



Table of Contents

Report: PumpReportMonthly

For: COOLSYS1 PUMP SECONDARY

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

PUMP ELECTRICITY ENERGY [J] PUMP FLUID HEAT GAIN ENERGY [J] PUMP ELECTRICITY RATE {Maximum} [W] PUMP ELECTRICITY RATE {TIMESTAMP} PUMP SHAFT POWER {AT MAX/MIN} [W] PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s]
January 122.20 109.98 1.70 24-JAN-05:11 1.53 1.53 6.70 0.46
February 1413707.61 1272336.85 108.93 27-FEB-14:00 98.03 98.03 6.70 9.91
March 41241.00 37116.90 11.73 14-MAR-13:30 10.56 10.56 6.70 2.35
April 12596644.28 11336979.86 263.52 06-APR-16:00 237.17 237.17 6.70 15.92
May 83294236.68 74964813.01 2015.60 19-MAY-15:30 1814.04 1814.04 6.71 41.73
June 0.394715E+09 0.355243E+09 3245.96 30-JUN-15:50 2921.36 2921.36 6.71 51.28
July 0.886614E+09 0.797952E+09 4548.41 31-JUL-15:20 4093.57 4093.57 6.72 59.13
August 0.797810E+09 0.718029E+09 4560.69 07-AUG-13:20 4104.62 4104.62 6.72 59.19
September 0.314497E+09 0.283047E+09 4374.25 04-SEP-15:31 3936.83 3936.83 6.98 58.17
October 27596720.66 24837048.60 581.90 18-OCT-13:20 523.71 523.71 7.43 23.59
November 800792.24 720713.02 51.77 03-NOV-13:55 46.59 46.59 6.70 6.41
December 19.93 17.93 0.05 28-DEC-00:33 0.05 0.05 6.70 0.02
                 
Annual Sum or Average 0.251938E+10 0.226744E+10            
Minimum of Months 19.93 17.93 0.05   0.05 0.05 6.70 0.02
Maximum of Months 0.886614E+09 0.797952E+09 4560.69   4104.62 4104.62 7.43 59.19



Table of Contents

Report: PumpReportMonthly

For: COOLSYS1 CHILLER1 PUMP

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

PUMP ELECTRICITY ENERGY [J] PUMP FLUID HEAT GAIN ENERGY [J] PUMP ELECTRICITY RATE {Maximum} [W] PUMP ELECTRICITY RATE {TIMESTAMP} PUMP SHAFT POWER {AT MAX/MIN} [W] PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s]
January 87578216.81 78820395.13 5592.48 24-JAN-05:11 5033.23 5033.23 6.71 49.47
February 0.912125E+09 0.820913E+09 5592.48 01-FEB-01:35 5033.23 5033.23 6.72 49.47
March 0.129128E+10 0.116215E+10 5592.48 01-MAR-05:01 5033.23 5033.23 6.72 49.47
April 0.268583E+10 0.241725E+10 5592.48 01-APR-12:13 5033.23 5033.23 6.72 49.47
May 0.411496E+10 0.370347E+10 5592.48 01-MAY-12:10 5033.23 5033.23 6.72 49.47
June 0.733271E+10 0.659944E+10 5592.48 01-JUN-04:12 5033.23 5033.23 7.65 49.47
July 0.995112E+10 0.895601E+10 5592.48 01-JUL-00:12 5033.23 5033.23 6.84 49.47
August 0.952771E+10 0.857494E+10 5592.48 01-AUG-00:23 5033.23 5033.23 6.82 49.47
September 0.593182E+10 0.533864E+10 5592.48 01-SEP-00:42 5033.23 5033.23 6.79 49.47
October 0.316485E+10 0.284836E+10 5592.48 02-OCT-05:05 5033.23 5033.23 7.47 49.47
November 0.148274E+10 0.133447E+10 5592.48 01-NOV-04:11 5033.23 5033.23 6.81 49.47
December 0.759195E+09 0.683275E+09 5592.48 01-DEC-05:43 5033.23 5033.23 6.72 49.47
                 
Annual Sum or Average 0.472419E+11 0.425177E+11            
Minimum of Months 87578216.81 78820395.13 5592.48   5033.23 5033.23 6.71 49.47
Maximum of Months 0.995112E+10 0.895601E+10 5592.48   5033.23 5033.23 7.65 49.47



Table of Contents

Report: PumpReportMonthly

For: COOLSYS1 CHILLER2 PUMP

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

PUMP ELECTRICITY ENERGY [J] PUMP FLUID HEAT GAIN ENERGY [J] PUMP ELECTRICITY RATE {Maximum} [W] PUMP ELECTRICITY RATE {TIMESTAMP} PUMP SHAFT POWER {AT MAX/MIN} [W] PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s]
January 0.00 0.00 0.00 01-JAN-00:05 0.00 0.00 6.70 0.00
February 0.00 0.00 0.00 01-FEB-00:05 0.00 0.00 6.72 0.00
March 0.00 0.00 0.00 01-MAR-00:10 0.00 0.00 6.72 0.00
April 0.00 0.00 0.00 01-APR-00:10 0.00 0.00 6.72 0.00
May 0.147641E+09 0.132877E+09 5592.48 19-MAY-12:10 5033.23 5033.23 12.31 24.73
June 0.153010E+10 0.137709E+10 5592.48 05-JUN-13:10 5033.23 5033.23 11.72 24.73
July 0.289914E+10 0.260923E+10 5592.48 03-JUL-09:40 5033.23 5033.23 12.64 24.73
August 0.250194E+10 0.225174E+10 5592.48 01-AUG-12:10 5033.23 5033.23 13.06 24.73
September 0.731496E+09 0.658347E+09 5592.48 01-SEP-09:50 5033.23 5033.23 12.56 24.73
October 68787488.30 61908739.47 5592.48 18-OCT-12:30 5033.23 5033.23 12.38 24.73
November 0.00 0.00 0.00 01-NOV-00:10 0.00 0.00 6.72 0.00
December 0.00 0.00 0.00 01-DEC-00:10 0.00 0.00 6.72 0.00
                 
Annual Sum or Average 0.787910E+10 0.709119E+10            
Minimum of Months 0.00 0.00 0.00   0.00 0.00 6.70 0.00
Maximum of Months 0.289914E+10 0.260923E+10 5592.48   5033.23 5033.23 13.06 24.73



Table of Contents

Report: PumpReportMonthly

For: PLANT CIRC PUMP

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

PUMP ELECTRICITY ENERGY [J] PUMP FLUID HEAT GAIN ENERGY [J] PUMP ELECTRICITY RATE {Maximum} [W] PUMP ELECTRICITY RATE {TIMESTAMP} PUMP SHAFT POWER {AT MAX/MIN} [W] PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s]
January 0.990025E+10 0.891023E+10 3696.33 01-JAN-00:05 3326.70 3326.70 18.54 15.44
February 0.894216E+10 0.804795E+10 3696.33 01-FEB-00:05 3326.70 3326.70 19.02 15.44
March 0.990025E+10 0.891023E+10 3696.33 01-MAR-00:10 3326.70 3326.70 19.90 15.44
April 0.958089E+10 0.862280E+10 3696.33 01-APR-00:10 3326.70 3326.70 20.38 15.44
May 0.990025E+10 0.891023E+10 3696.33 01-MAY-00:10 3326.70 3326.70 18.77 15.44
June 0.958089E+10 0.862280E+10 3696.33 01-JUN-00:10 3326.70 3326.70 19.58 15.44
July 0.990025E+10 0.891023E+10 3696.33 01-JUL-00:10 3326.70 3326.70 28.12 15.44
August 0.990025E+10 0.891023E+10 3696.33 01-AUG-00:03 3326.70 3326.70 31.71 15.44
September 0.958089E+10 0.862280E+10 3696.33 01-SEP-00:05 3326.70 3326.70 19.63 15.44
October 0.990025E+10 0.891023E+10 3696.33 01-OCT-00:10 3326.70 3326.70 19.51 15.44
November 0.958089E+10 0.862280E+10 3696.33 01-NOV-00:10 3326.70 3326.70 19.88 15.44
December 0.990025E+10 0.891023E+10 3696.33 01-DEC-00:10 3326.70 3326.70 20.21 15.44
                 
Annual Sum or Average 0.116567E+12 0.104911E+12            
Minimum of Months 0.894216E+10 0.804795E+10 3696.33   3326.70 3326.70 18.54 15.44
Maximum of Months 0.990025E+10 0.891023E+10 3696.33   3326.70 3326.70 31.71 15.44



Table of Contents

Report: PumpReportMonthly

For: SWHSYS1 PUMP

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

PUMP ELECTRICITY ENERGY [J] PUMP FLUID HEAT GAIN ENERGY [J] PUMP ELECTRICITY RATE {Maximum} [W] PUMP ELECTRICITY RATE {TIMESTAMP} PUMP SHAFT POWER {AT MAX/MIN} [W] PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s]
January 0.112905E+09 33871561.48 56.21 01-JAN-06:03 16.86 16.86 55.98 0.44
February 0.101979E+09 30593668.43 56.21 01-FEB-06:03 16.86 16.86 55.56 0.44
March 0.112905E+09 33871561.48 56.21 01-MAR-06:01 16.86 16.86 55.13 0.44
April 0.109263E+09 32778930.46 56.21 01-APR-05:02 16.86 16.86 56.12 0.44
May 0.112905E+09 33871561.48 56.21 01-MAY-05:03 16.86 16.86 56.23 0.44
June 0.109263E+09 32778930.46 56.21 01-JUN-05:03 16.86 16.86 56.29 0.44
July 0.112905E+09 33871561.48 56.21 01-JUL-05:03 16.86 16.86 56.84 0.44
August 0.112905E+09 33871561.48 56.21 01-AUG-05:03 16.86 16.86 56.55 0.44
September 0.109263E+09 32778930.46 56.21 01-SEP-05:02 16.86 16.86 55.72 0.44
October 0.112905E+09 33871561.48 56.21 01-OCT-05:10 16.86 16.86 56.39 0.44
November 0.109263E+09 32778930.46 56.21 01-NOV-05:03 16.86 16.86 55.96 0.44
December 0.112905E+09 33871561.48 56.21 01-DEC-06:01 16.86 16.86 56.34 0.44
                 
Annual Sum or Average 0.132937E+10 0.398810E+09            
Minimum of Months 0.101979E+09 30593668.43 56.21   16.86 16.86 55.13 0.44
Maximum of Months 0.112905E+09 33871561.48 56.21   16.86 16.86 56.84 0.44



Table of Contents

Report: PumpReportMonthly

For: TOWERWATERSYS PUMP

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

PUMP ELECTRICITY ENERGY [J] PUMP FLUID HEAT GAIN ENERGY [J] PUMP ELECTRICITY RATE {Maximum} [W] PUMP ELECTRICITY RATE {TIMESTAMP} PUMP SHAFT POWER {AT MAX/MIN} [W] PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s]
January 0.224752E+09 0.202277E+09 14353.64 25-JAN-06:15 12918.28 12918.28 21.13 58.17
February 0.234111E+10 0.210700E+10 14375.05 27-FEB-15:30 12937.54 12937.54 23.20 58.17
March 0.331371E+10 0.298234E+10 14356.69 14-MAR-13:10 12921.02 12921.02 21.42 58.17
April 0.689606E+10 0.620646E+10 14398.74 06-APR-16:00 12958.86 12958.86 25.42 58.17
May 0.108737E+11 0.978629E+10 28812.96 19-MAY-14:30 25931.67 25931.67 26.06 116.34
June 0.220628E+11 0.198566E+11 28830.40 20-JUN-15:40 25947.36 25947.36 26.78 116.34
July 0.320752E+11 0.288677E+11 28835.22 17-JUL-15:30 25951.69 25951.69 26.98 116.34
August 0.301171E+11 0.271054E+11 28813.82 30-AUG-14:40 25932.44 25932.44 26.09 116.34
September 0.168958E+11 0.152062E+11 28879.57 07-SEP-14:30 25991.62 25991.62 28.83 116.34
October 0.827028E+10 0.744325E+10 28804.07 18-OCT-13:25 25923.66 25923.66 25.69 116.34
November 0.380535E+10 0.342481E+10 14364.95 03-NOV-14:00 12928.46 12928.46 22.22 58.17
December 0.194827E+10 0.175345E+10 14353.75 29-DEC-02:30 12918.38 12918.38 21.14 58.17
                 
Annual Sum or Average 0.138824E+12 0.124942E+12            
Minimum of Months 0.224752E+09 0.202277E+09 14353.64   12918.28 12918.28 21.13 58.17
Maximum of Months 0.320752E+11 0.288677E+11 28879.57   25991.62 25991.62 28.83 116.34



Table of Contents

Report: CondLoopDemandReportMonthly

For: HEATSYS1

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 0.00 0.00 01-JAN-00:05 32.81 32.81 357372.88 2138250.95 23-JAN-05:11
February 0.00 0.00 01-FEB-00:05 32.40 82.00 200329.81 2081493.97 07-FEB-06:01
March 0.00 0.00 01-MAR-00:10 24.26 24.26 107069.79 1927328.50 06-MAR-05:01
April 0.00 0.00 01-APR-00:10 25.68 25.68 27907.21 1629520.69 01-APR-04:11
May 0.00 0.00 01-MAY-00:10 22.93 82.00 18872.98 1654154.34 09-MAY-04:01
June 0.00 0.00 01-JUN-00:10 23.03 23.03 647.71 370308.82 17-JUN-05:03
July 0.00 0.00 01-JUL-00:10 22.41 22.41 9.28 10059.99 08-JUL-05:03
August 0.00 0.00 01-AUG-00:03 22.21 22.21 210.95 372323.64 18-AUG-05:03
September 0.00 0.00 01-SEP-00:05 22.47 22.47 5428.51 1439883.70 19-SEP-04:11
October 0.00 0.00 01-OCT-00:10 20.65 20.65 21814.21 1521347.06 11-OCT-04:01
November 0.00 0.00 01-NOV-00:10 25.54 25.54 95381.58 1867617.05 28-NOV-06:01
December 0.00 0.00 01-DEC-00:10 29.90 29.90 228266.37 2050482.29 04-DEC-06:01
                 
Annual Sum or Average 0.00         88307.66    
Minimum of Months 0.00 0.00   20.65 20.65 9.28 10059.99  
Maximum of Months 0.00 0.00   32.81 82.00 357372.88 2138250.95  



Table of Contents

Report: CondLoopDemandReportMonthly

For: COOLSYS1_SUPPLY

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 29.20 5033.40 25-JAN-10:40 6.72 6.70 0.00 0.00 01-JAN-00:05
February 3210.02 432515.78 27-FEB-15:30 8.79 6.70 0.00 0.00 01-FEB-00:05
March 567.45 94270.74 14-MAR-13:30 7.15 6.70 0.00 0.00 01-MAR-00:10
April 26167.72 920492.44 06-APR-16:00 11.14 6.70 0.00 0.00 01-APR-00:10
May 82289.60 1494152.87 19-MAY-15:30 10.30 6.70 0.00 0.00 01-MAY-00:10
June 279040.04 1671563.59 29-JUN-14:50 10.73 6.70 0.00 0.00 01-JUN-00:10
July 450799.64 1958274.67 17-JUL-15:30 11.42 6.70 0.00 0.00 01-JUL-00:10
August 394445.08 1920661.72 07-AUG-09:20 11.33 6.70 0.00 0.00 01-AUG-00:03
September 184483.52 2896316.02 07-SEP-15:00 13.69 7.99 0.00 0.00 01-SEP-00:05
October 44322.24 1567281.43 18-OCT-13:40 10.48 6.70 0.00 0.00 01-OCT-00:10
November 2651.95 212763.59 03-NOV-14:00 7.73 6.70 0.00 0.00 01-NOV-00:10
December 255.19 5277.04 28-DEC-00:33 6.73 6.70 0.00 0.00 01-DEC-00:10
                 
Annual Sum or Average 123326.40         0.00    
Minimum of Months 29.20 5033.40   6.72 6.70 0.00 0.00  
Maximum of Months 450799.64 2896316.02   13.69 7.99 0.00 0.00  



Table of Contents

Report: CondLoopDemandReportMonthly

For: COOLSYS1_DEMAND

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 0.00 17.01 24-JAN-05:11 6.71 6.70 0.00 0.00 01-JAN-00:05
February 2872.13 428889.63 27-FEB-15:30 18.30 6.70 0.00 0.00 01-FEB-00:05
March 133.57 89789.35 14-MAR-13:30 15.83 6.70 0.00 0.00 01-MAR-00:10
April 25252.63 921422.88 06-APR-16:00 20.55 6.70 0.00 0.00 01-APR-00:10
May 80785.67 1485901.24 19-MAY-15:30 15.21 6.70 0.00 0.00 01-MAY-00:10
June 274664.54 1663765.26 29-JUN-14:50 22.28 6.70 0.00 0.00 01-JUN-00:10
July 445025.93 1952136.00 17-JUL-15:30 15.28 6.70 0.00 0.00 01-JUL-00:10
August 387869.83 2024175.58 07-AUG-09:20 15.96 6.70 0.00 0.00 01-AUG-00:03
September 181628.84 2702859.85 07-SEP-15:00 18.76 7.94 0.00 0.00 01-SEP-00:05
October 43084.78 1275970.05 18-OCT-13:20 19.63 7.07 0.00 0.00 01-OCT-00:10
November 2137.50 208240.74 03-NOV-14:00 14.53 6.70 0.00 0.00 01-NOV-00:10
December 0.08 567.73 28-DEC-00:33 15.50 6.70 0.00 0.00 01-DEC-00:10
                 
Annual Sum or Average 121246.08         0.00    
Minimum of Months 0.00 17.01   6.71 6.70 0.00 0.00  
Maximum of Months 445025.93 2702859.85   22.28 7.94 0.00 0.00  



Table of Contents

Report: CondLoopDemandReportMonthly

For: SINGLE WATER PLANT LOOP

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 13869.89 39733.81 13-JAN-16:30 19.07 18.33 0.00 0.00 01-JAN-00:05
February 49498.60 172318.16 27-FEB-16:00 21.54 19.84 0.00 0.00 01-FEB-00:05
March 82265.32 110181.10 31-MAR-23:30 20.39 18.33 0.00 0.00 01-MAR-00:10
April 166238.63 1156364.30 07-APR-14:00 39.53 29.19 0.00 0.00 01-APR-00:10
May 74231.07 989882.11 20-MAY-16:00 36.53 32.36 0.00 0.00 01-MAY-00:10
June 296393.79 1399626.97 29-JUN-15:00 43.88 36.46 0.00 0.00 01-JUN-00:10
July 707051.38 1987835.02 17-JUL-16:00 54.27 43.48 0.00 0.00 01-JUL-00:10
August 768815.98 2082790.46 05-AUG-16:00 55.93 43.09 0.00 0.00 01-AUG-00:03
September 159964.43 1264560.89 02-SEP-17:00 41.47 36.97 0.00 0.00 01-SEP-00:05
October 80970.24 863639.82 18-OCT-15:00 34.24 28.34 0.00 0.00 01-OCT-00:10
November 83026.07 223313.46 17-NOV-17:00 22.49 19.09 0.00 0.00 01-NOV-00:10
December 102015.30 186302.37 10-DEC-02:00 21.80 18.33 0.00 0.00 01-DEC-00:10
                 
Annual Sum or Average 217151.90         0.00    
Minimum of Months 13869.89 39733.81   19.07 18.33 0.00 0.00  
Maximum of Months 768815.98 2082790.46   55.93 43.48 0.00 0.00  



Table of Contents

Report: CondLoopDemandReportMonthly

For: SWHSYS1

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 0.00 0.00 01-JAN-00:05 57.44 57.44 17319.97 58842.16 31-JAN-12:50
February 0.00 0.00 01-FEB-00:05 56.30 56.30 17697.27 59153.14 14-FEB-12:50
March 0.00 0.00 01-MAR-00:10 55.68 55.68 18533.99 59067.02 01-MAR-12:20
April 0.00 0.00 01-APR-00:10 56.58 56.58 16872.11 57468.27 03-APR-11:20
May 0.00 0.00 01-MAY-00:10 57.23 57.23 16515.05 54989.08 01-MAY-11:45
June 0.00 0.00 01-JUN-00:10 56.50 56.50 15919.94 51669.30 01-JUN-11:30
July 0.00 0.00 01-JUL-00:10 57.39 57.39 14087.85 48632.98 03-JUL-12:00
August 0.00 0.00 01-AUG-00:03 57.08 57.08 14975.18 46956.51 01-AUG-11:40
September 0.00 0.00 01-SEP-00:05 56.24 56.24 14302.73 48059.10 29-SEP-11:30
October 0.00 0.00 01-OCT-00:10 57.28 57.28 14888.01 50853.81 31-OCT-11:40
November 0.00 0.00 01-NOV-00:10 56.61 56.61 15937.13 54092.96 30-NOV-12:55
December 0.00 0.00 01-DEC-00:10 56.74 56.74 16262.03 56856.24 29-DEC-12:40
                 
Annual Sum or Average 0.00         16100.07    
Minimum of Months 0.00 0.00   55.68 55.68 14087.85 46956.51  
Maximum of Months 0.00 0.00   57.44 57.44 18533.99 59153.14  



Table of Contents

Report: CondLoopDemandReportMonthly

For: TOWERWATERSYS

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 0.64 6505.81 25-JAN-06:15 21.13 20.18 193.14 130376.09 25-JAN-10:40
February 2944.00 510389.08 27-FEB-15:30 23.20 21.10 1971.61 152342.40 14-FEB-05:01
March 74.43 78424.69 14-MAR-13:10 21.42 20.73 3647.26 156290.06 04-MAR-05:01
April 28533.15 1049719.40 06-APR-16:00 25.42 21.10 3524.46 136059.22 28-APR-05:50
May 98501.24 2409841.37 19-MAY-14:30 26.06 21.10 2553.88 146820.80 06-MAY-04:42
June 354723.15 2760760.80 20-JUN-15:40 26.78 23.03 1073.96 98209.70 14-JUN-13:30
July 585407.06 2857509.96 17-JUL-15:30 26.98 22.37 654.22 76171.27 29-JUL-07:20
August 498869.94 2427070.71 30-AUG-14:40 26.09 21.10 1529.41 78898.82 03-AUG-08:20
September 240289.25 4764385.16 07-SEP-15:00 30.90 25.37 2081.17 117838.80 18-SEP-14:40
October 50693.02 2230800.52 18-OCT-13:25 25.69 21.10 2999.12 153018.03 10-OCT-03:01
November 1818.55 272973.97 03-NOV-14:00 22.22 21.10 3407.81 152343.87 13-NOV-05:01
December 15.52 9135.90 29-DEC-02:30 21.14 20.19 2091.51 142113.31 17-DEC-15:53
                 
Annual Sum or Average 156393.90         2141.24    
Minimum of Months 0.64 6505.81   21.13 20.18 193.14 76171.27  
Maximum of Months 585407.06 4764385.16   30.90 25.37 3647.26 156290.06  



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: BASEMENT

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: CORE_BOTTOM

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: CORE_MID

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: CORE_TOP

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: GROUNDFLOOR_PLENUM

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00 0.00
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: MIDFLOOR_PLENUM

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00 0.00
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: TOPFLOOR_PLENUM

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00 0.00
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: DATACENTER_MID_ZN_6

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: VAV_BOT WITH REHEAT

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.480626E+11 0.00 0.00 0.438646E+10 0.00 0.00
February 0.217024E+11 0.00 0.736348E+09 0.489911E+10 0.00 0.00
March 0.900859E+10 0.00 64191064.87 0.722759E+10 0.00 0.00
April 0.109084E+10 0.00 0.713072E+10 0.909821E+10 0.00 0.00
May 0.867442E+09 0.00 0.195332E+11 0.856492E+10 0.00 0.00
June 6699089.73 0.00 0.638689E+11 0.133429E+11 0.00 0.00
July 0.00 0.00 0.108592E+12 0.165048E+11 0.00 0.00
August 0.00 0.00 0.991574E+11 0.174860E+11 0.00 0.00
September 98457601.75 0.00 0.413584E+11 0.946832E+10 0.00 0.00
October 0.874002E+09 0.00 0.112922E+11 0.815085E+10 0.00 0.00
November 0.626075E+10 0.00 0.616459E+09 0.662822E+10 0.00 0.00
December 0.226729E+11 0.00 0.00 0.568093E+10 0.00 0.00
             
Annual Sum or Average 0.110645E+12 0.00 0.352350E+12 0.111438E+12 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.438646E+10 0.00 0.00
Maximum of Months 0.480626E+11 0.00 0.108592E+12 0.174860E+11 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: VAV_MID WITH REHEAT

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.798293E+12 0.00 31506.06 0.437676E+11 0.00 0.00
February 0.405329E+12 0.00 0.582135E+10 0.385300E+11 0.00 0.00
March 0.238738E+12 0.00 0.247060E+09 0.482040E+11 0.00 0.00
April 0.583879E+11 0.00 0.511108E+11 0.520516E+11 0.00 0.00
May 0.400773E+11 0.00 0.167845E+12 0.637400E+11 0.00 0.00
June 0.103481E+10 0.00 0.544162E+12 0.102027E+12 0.00 0.00
July 0.00 0.00 0.910049E+12 0.124742E+12 0.00 0.00
August 0.325248E+09 0.00 0.790119E+12 0.120460E+12 0.00 0.00
September 0.105170E+11 0.00 0.364666E+12 0.739176E+11 0.00 0.00
October 0.460793E+11 0.00 0.893588E+11 0.532459E+11 0.00 0.00
November 0.204889E+12 0.00 0.448429E+10 0.426892E+11 0.00 0.00
December 0.510963E+12 0.00 64277.76 0.420256E+11 0.00 0.00
             
Annual Sum or Average 0.231463E+13 0.00 0.292786E+13 0.805401E+12 0.00 0.00
Minimum of Months 0.00 0.00 31506.06 0.385300E+11 0.00 0.00
Maximum of Months 0.798293E+12 0.00 0.910049E+12 0.124742E+12 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: VAV_TOP WITH REHEAT

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.119127E+12 0.00 52824.02 0.538050E+10 0.00 0.00
February 0.620237E+11 0.00 0.390482E+09 0.425532E+10 0.00 0.00
March 0.415864E+11 0.00 2331981.52 0.458644E+10 0.00 0.00
April 0.135185E+11 0.00 0.479342E+10 0.438980E+10 0.00 0.00
May 0.100570E+11 0.00 0.173282E+11 0.571234E+10 0.00 0.00
June 0.656607E+09 0.00 0.588673E+11 0.935228E+10 0.00 0.00
July 26604971.68 0.00 0.988626E+11 0.117868E+11 0.00 0.00
August 0.242664E+09 0.00 0.839504E+11 0.109047E+11 0.00 0.00
September 0.359200E+10 0.00 0.370519E+11 0.628180E+10 0.00 0.00
October 0.119535E+11 0.00 0.773586E+10 0.427012E+10 0.00 0.00
November 0.382604E+11 0.00 0.331261E+09 0.418037E+10 0.00 0.00
December 0.831558E+11 0.00 126715.88 0.488727E+10 0.00 0.00
             
Annual Sum or Average 0.384201E+12 0.00 0.309314E+12 0.759878E+11 0.00 0.00
Minimum of Months 26604971.68 0.00 52824.02 0.418037E+10 0.00 0.00
Maximum of Months 0.119127E+12 0.00 0.988626E+11 0.117868E+11 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: CAV_BAS

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.309488E+09 0.00 430925.51 0.169075E+11 0.00 0.00
February 0.00 0.00 0.282169E+09 0.150723E+11 0.00 0.00
March 0.00 0.00 36227.49 0.182976E+11 0.00 0.00
April 0.00 0.00 0.252028E+10 0.166235E+11 0.00 0.00
May 0.00 0.00 0.934050E+10 0.179135E+11 0.00 0.00
June 0.00 0.00 0.331920E+11 0.175566E+11 0.00 0.00
July 0.00 0.00 0.565008E+11 0.180332E+11 0.00 0.00
August 0.00 0.00 0.517700E+11 0.192064E+11 0.00 0.00
September 0.00 0.00 0.214620E+11 0.179129E+11 0.00 0.00
October 0.00 0.00 0.593250E+10 0.177643E+11 0.00 0.00
November 0.00 0.00 75754208.78 0.169256E+11 0.00 0.00
December 0.00 0.00 22839.71 0.167469E+11 0.00 0.00
             
Annual Sum or Average 0.309488E+09 0.00 0.181077E+12 0.208960E+12 0.00 0.00
Minimum of Months 0.00 0.00 22839.71 0.150723E+11 0.00 0.00
Maximum of Months 0.309488E+09 0.00 0.565008E+11 0.192064E+11 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: AIRLOOP DATACENTER BASEMENT

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.00 0.00 0.141405E+11 0.273874E+12 0.00 59.64
February 0.00 0.00 0.199849E+11 0.337621E+12 0.00 86.79
March 0.00 0.00 0.225640E+11 0.383712E+12 0.00 99.64
April 0.00 0.00 0.102206E+12 0.390020E+12 0.00 95.99
May 0.00 0.00 0.267735E+11 0.276811E+12 0.00 59.44
June 0.00 0.00 0.186677E+12 0.293047E+12 0.00 51.45
July 0.00 0.00 0.607444E+12 0.379819E+12 0.00 41.79
August 0.00 0.00 0.767043E+12 0.528504E+12 0.00 82.94
September 0.00 0.00 0.643832E+11 0.232630E+12 0.00 40.47
October 0.00 0.00 0.352686E+11 0.365277E+12 0.00 91.65
November 0.00 0.00 0.243952E+11 0.371926E+12 0.00 96.42
December 0.00 0.00 0.249724E+11 0.384596E+12 0.00 99.64
             
Annual Sum or Average 0.00 0.00 0.189585E+13 0.421784E+13 0.00 905.84
Minimum of Months 0.00 0.00 0.141405E+11 0.232630E+12 0.00 40.47
Maximum of Months 0.00 0.00 0.767043E+12 0.528504E+12 0.00 99.64



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: AIRLOOP DATACENTER BOT

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.00 0.00 0.375130E+10 0.259419E+10 0.00 0.00
February 0.00 0.00 0.104487E+11 0.376384E+10 0.00 0.00
March 0.00 0.00 0.187195E+11 0.547835E+10 0.00 0.00
April 0.00 0.00 0.249328E+11 0.648432E+10 0.00 0.00
May 0.00 0.00 0.732277E+10 0.331243E+10 0.00 0.00
June 0.00 0.00 0.141190E+11 0.471629E+10 0.00 0.00
July 0.00 0.00 0.217739E+11 0.672410E+10 0.00 0.00
August 0.00 0.00 0.278608E+11 0.789163E+10 0.00 0.00
September 0.00 0.00 0.750625E+10 0.333550E+10 0.00 0.00
October 0.00 0.00 0.133043E+11 0.443320E+10 0.00 0.00
November 0.00 0.00 0.182558E+11 0.529395E+10 0.00 0.00
December 0.00 0.00 0.242165E+11 0.649262E+10 0.00 0.00
             
Annual Sum or Average 0.00 0.00 0.192212E+12 0.605204E+11 0.00 0.00
Minimum of Months 0.00 0.00 0.375130E+10 0.259419E+10 0.00 0.00
Maximum of Months 0.00 0.00 0.278608E+11 0.789163E+10 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: AIRLOOP DATACENTER MID

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.00 0.00 0.993674E+10 0.192567E+11 0.00 0.00
February 0.00 0.00 0.749871E+11 0.311685E+11 0.00 0.00
March 0.00 0.00 0.156101E+12 0.482971E+11 0.00 0.00
April 0.00 0.00 0.223610E+12 0.595948E+11 0.00 0.00
May 0.00 0.00 0.592914E+11 0.296290E+11 0.00 0.00
June 0.00 0.00 0.129824E+12 0.442290E+11 0.00 0.00
July 0.00 0.00 0.205327E+12 0.638683E+11 0.00 0.00
August 0.00 0.00 0.262463E+12 0.748799E+11 0.00 0.00
September 0.00 0.00 0.632980E+11 0.303036E+11 0.00 0.00
October 0.00 0.00 0.110904E+12 0.394522E+11 0.00 0.00
November 0.00 0.00 0.150437E+12 0.463543E+11 0.00 0.00
December 0.00 0.00 0.197206E+12 0.561012E+11 0.00 0.00
             
Annual Sum or Average 0.00 0.00 0.164339E+13 0.543135E+12 0.00 0.00
Minimum of Months 0.00 0.00 0.993674E+10 0.192567E+11 0.00 0.00
Maximum of Months 0.00 0.00 0.262463E+12 0.748799E+11 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: AIRLOOP DATACENTER TOP

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.00 0.00 0.401716E+09 0.181412E+10 0.00 0.00
February 0.00 0.00 0.561021E+10 0.275800E+10 0.00 0.00
March 0.00 0.00 0.137256E+11 0.450544E+10 0.00 0.00
April 0.00 0.00 0.210309E+11 0.576107E+10 0.00 0.00
May 0.00 0.00 0.511642E+10 0.282408E+10 0.00 0.00
June 0.00 0.00 0.127108E+11 0.440635E+10 0.00 0.00
July 0.00 0.00 0.204504E+11 0.641552E+10 0.00 0.00
August 0.00 0.00 0.260772E+11 0.750352E+10 0.00 0.00
September 0.00 0.00 0.565314E+10 0.292563E+10 0.00 0.00
October 0.00 0.00 0.943667E+10 0.365977E+10 0.00 0.00
November 0.00 0.00 0.128925E+11 0.426439E+10 0.00 0.00
December 0.00 0.00 0.174332E+11 0.522407E+10 0.00 0.00
             
Annual Sum or Average 0.00 0.00 0.150539E+12 0.520620E+11 0.00 0.00
Minimum of Months 0.00 0.00 0.401716E+09 0.181412E+10 0.00 0.00
Maximum of Months 0.00 0.00 0.260772E+11 0.750352E+10 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: VAV_BOT WITH REHEAT

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.438646E+10 0.00 0.480626E+11 0.00 0.00 0.00 0.00 0.00
February 0.489911E+10 0.736348E+09 0.217024E+11 0.00 0.00 0.00 0.00 0.00
March 0.722759E+10 64191064.87 0.900859E+10 0.00 0.00 0.00 0.00 0.00
April 0.909821E+10 0.713072E+10 0.109084E+10 0.00 0.00 0.00 0.00 0.00
May 0.856492E+10 0.195332E+11 0.867442E+09 0.00 0.00 0.00 0.00 0.00
June 0.133429E+11 0.638689E+11 6699089.73 0.00 0.00 0.00 0.00 0.00
July 0.165048E+11 0.108592E+12 0.00 0.00 0.00 0.00 0.00 0.00
August 0.174860E+11 0.991574E+11 0.00 0.00 0.00 0.00 0.00 0.00
September 0.946832E+10 0.413584E+11 98457601.75 0.00 0.00 0.00 0.00 0.00
October 0.815085E+10 0.112922E+11 0.874002E+09 0.00 0.00 0.00 0.00 0.00
November 0.662822E+10 0.616459E+09 0.626075E+10 0.00 0.00 0.00 0.00 0.00
December 0.568093E+10 0.00 0.226729E+11 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.111438E+12 0.352350E+12 0.110645E+12 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.438646E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.174860E+11 0.108592E+12 0.480626E+11 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: VAV_MID WITH REHEAT

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.437676E+11 31506.06 0.798293E+12 0.00 0.00 0.00 0.00 0.00
February 0.385300E+11 0.582135E+10 0.405329E+12 0.00 0.00 0.00 0.00 0.00
March 0.482040E+11 0.247060E+09 0.238738E+12 0.00 0.00 0.00 0.00 0.00
April 0.520516E+11 0.511108E+11 0.583879E+11 0.00 0.00 0.00 0.00 0.00
May 0.637400E+11 0.167845E+12 0.400773E+11 0.00 0.00 0.00 0.00 0.00
June 0.102027E+12 0.544162E+12 0.103481E+10 0.00 0.00 0.00 0.00 0.00
July 0.124742E+12 0.910049E+12 0.00 0.00 0.00 0.00 0.00 0.00
August 0.120460E+12 0.790119E+12 0.325248E+09 0.00 0.00 0.00 0.00 0.00
September 0.739176E+11 0.364666E+12 0.105170E+11 0.00 0.00 0.00 0.00 0.00
October 0.532459E+11 0.893588E+11 0.460793E+11 0.00 0.00 0.00 0.00 0.00
November 0.426892E+11 0.448429E+10 0.204889E+12 0.00 0.00 0.00 0.00 0.00
December 0.420256E+11 64277.76 0.510963E+12 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.805401E+12 0.292786E+13 0.231463E+13 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.385300E+11 31506.06 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.124742E+12 0.910049E+12 0.798293E+12 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: VAV_TOP WITH REHEAT

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.538050E+10 52824.02 0.119127E+12 0.00 0.00 0.00 0.00 0.00
February 0.425532E+10 0.390482E+09 0.620237E+11 0.00 0.00 0.00 0.00 0.00
March 0.458644E+10 2331981.52 0.415864E+11 0.00 0.00 0.00 0.00 0.00
April 0.438980E+10 0.479342E+10 0.135185E+11 0.00 0.00 0.00 0.00 0.00
May 0.571234E+10 0.173282E+11 0.100570E+11 0.00 0.00 0.00 0.00 0.00
June 0.935228E+10 0.588673E+11 0.656607E+09 0.00 0.00 0.00 0.00 0.00
July 0.117868E+11 0.988626E+11 26604971.68 0.00 0.00 0.00 0.00 0.00
August 0.109047E+11 0.839504E+11 0.242664E+09 0.00 0.00 0.00 0.00 0.00
September 0.628180E+10 0.370519E+11 0.359200E+10 0.00 0.00 0.00 0.00 0.00
October 0.427012E+10 0.773586E+10 0.119535E+11 0.00 0.00 0.00 0.00 0.00
November 0.418037E+10 0.331261E+09 0.382604E+11 0.00 0.00 0.00 0.00 0.00
December 0.488727E+10 126715.88 0.831558E+11 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.759878E+11 0.309314E+12 0.384201E+12 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.418037E+10 52824.02 26604971.68 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.117868E+11 0.988626E+11 0.119127E+12 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: CAV_BAS

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.169075E+11 430925.51 0.309488E+09 0.00 0.00 0.00 0.00 0.00
February 0.150723E+11 0.282169E+09 0.00 0.00 0.00 0.00 0.00 0.00
March 0.182976E+11 36227.49 0.00 0.00 0.00 0.00 0.00 0.00
April 0.166235E+11 0.252028E+10 0.00 0.00 0.00 0.00 0.00 0.00
May 0.179135E+11 0.934050E+10 0.00 0.00 0.00 0.00 0.00 0.00
June 0.175566E+11 0.331920E+11 0.00 0.00 0.00 0.00 0.00 0.00
July 0.180332E+11 0.565008E+11 0.00 0.00 0.00 0.00 0.00 0.00
August 0.192064E+11 0.517700E+11 0.00 0.00 0.00 0.00 0.00 0.00
September 0.179129E+11 0.214620E+11 0.00 0.00 0.00 0.00 0.00 0.00
October 0.177643E+11 0.593250E+10 0.00 0.00 0.00 0.00 0.00 0.00
November 0.169256E+11 75754208.78 0.00 0.00 0.00 0.00 0.00 0.00
December 0.167469E+11 22839.71 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.208960E+12 0.181077E+12 0.309488E+09 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.150723E+11 22839.71 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.192064E+11 0.565008E+11 0.309488E+09 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: AIRLOOP DATACENTER BASEMENT

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.108397E+12 0.897821E+10 0.00 0.00 0.00 0.159597E+12 0.00 0.00
February 0.979067E+11 0.135760E+11 0.00 0.00 0.00 0.232260E+12 0.00 0.00
March 0.108397E+12 0.150884E+11 0.00 0.00 0.00 0.266640E+12 0.00 0.00
April 0.104900E+12 0.751158E+11 0.00 0.00 0.00 0.256873E+12 0.00 0.00
May 0.108397E+12 0.181394E+11 0.00 0.00 0.00 0.159064E+12 0.00 0.00
June 0.104900E+12 0.136834E+12 0.00 0.00 0.00 0.137683E+12 0.00 0.00
July 0.108397E+12 0.448356E+12 0.00 0.00 0.00 0.111831E+12 0.00 0.00
August 0.108397E+12 0.569901E+12 0.00 0.00 0.00 0.221966E+12 0.00 0.00
September 0.104900E+12 0.454441E+11 0.00 0.00 0.00 0.108303E+12 0.00 0.00
October 0.108397E+12 0.247462E+11 0.00 0.00 0.00 0.245254E+12 0.00 0.00
November 0.104900E+12 0.165686E+11 0.00 0.00 0.00 0.258037E+12 0.00 0.00
December 0.108397E+12 0.166132E+11 0.00 0.00 0.00 0.266640E+12 0.00 0.00
                 
Annual Sum or Average 0.127628E+13 0.138936E+13 0.00 0.00 0.00 0.242415E+13 0.00 0.00
Minimum of Months 0.979067E+11 0.897821E+10 0.00 0.00 0.00 0.108303E+12 0.00 0.00
Maximum of Months 0.108397E+12 0.569901E+12 0.00 0.00 0.00 0.266640E+12 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: AIRLOOP DATACENTER BOT

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.175618E+10 0.291329E+10 0.00 0.00 0.00 0.00 0.00 0.00
February 0.158623E+10 0.827107E+10 0.00 0.00 0.00 0.00 0.00 0.00
March 0.175618E+10 0.149973E+11 0.00 0.00 0.00 0.00 0.00 0.00
April 0.169953E+10 0.201480E+11 0.00 0.00 0.00 0.00 0.00 0.00
May 0.175618E+10 0.576652E+10 0.00 0.00 0.00 0.00 0.00 0.00
June 0.169953E+10 0.111022E+11 0.00 0.00 0.00 0.00 0.00 0.00
July 0.175618E+10 0.168060E+11 0.00 0.00 0.00 0.00 0.00 0.00
August 0.175618E+10 0.217253E+11 0.00 0.00 0.00 0.00 0.00 0.00
September 0.169953E+10 0.587028E+10 0.00 0.00 0.00 0.00 0.00 0.00
October 0.175618E+10 0.106273E+11 0.00 0.00 0.00 0.00 0.00 0.00
November 0.169953E+10 0.146614E+11 0.00 0.00 0.00 0.00 0.00 0.00
December 0.175618E+10 0.194801E+11 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.206776E+11 0.152369E+12 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.158623E+10 0.291329E+10 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.175618E+10 0.217253E+11 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: AIRLOOP DATACENTER MID

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.168896E+11 0.756959E+10 0.00 0.00 0.00 0.00 0.00 0.00
February 0.152551E+11 0.590737E+11 0.00 0.00 0.00 0.00 0.00 0.00
March 0.168896E+11 0.124694E+12 0.00 0.00 0.00 0.00 0.00 0.00
April 0.163447E+11 0.180360E+12 0.00 0.00 0.00 0.00 0.00 0.00
May 0.168896E+11 0.465520E+11 0.00 0.00 0.00 0.00 0.00 0.00
June 0.163447E+11 0.101940E+12 0.00 0.00 0.00 0.00 0.00 0.00
July 0.168896E+11 0.158348E+12 0.00 0.00 0.00 0.00 0.00 0.00
August 0.168896E+11 0.204472E+12 0.00 0.00 0.00 0.00 0.00 0.00
September 0.163447E+11 0.493391E+11 0.00 0.00 0.00 0.00 0.00 0.00
October 0.168896E+11 0.883410E+11 0.00 0.00 0.00 0.00 0.00 0.00
November 0.163447E+11 0.120428E+12 0.00 0.00 0.00 0.00 0.00 0.00
December 0.168896E+11 0.157995E+12 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.198861E+12 0.129911E+13 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.152551E+11 0.756959E+10 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.168896E+11 0.204472E+12 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: AIRLOOP DATACENTER TOP

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.171738E+10 0.304978E+09 0.00 0.00 0.00 0.00 0.00 0.00
February 0.155118E+10 0.440339E+10 0.00 0.00 0.00 0.00 0.00 0.00
March 0.171738E+10 0.109375E+11 0.00 0.00 0.00 0.00 0.00 0.00
April 0.166198E+10 0.169319E+11 0.00 0.00 0.00 0.00 0.00 0.00
May 0.171738E+10 0.400971E+10 0.00 0.00 0.00 0.00 0.00 0.00
June 0.166198E+10 0.996639E+10 0.00 0.00 0.00 0.00 0.00 0.00
July 0.171738E+10 0.157522E+11 0.00 0.00 0.00 0.00 0.00 0.00
August 0.171738E+10 0.202910E+11 0.00 0.00 0.00 0.00 0.00 0.00
September 0.166198E+10 0.438949E+10 0.00 0.00 0.00 0.00 0.00 0.00
October 0.171738E+10 0.749428E+10 0.00 0.00 0.00 0.00 0.00 0.00
November 0.166198E+10 0.102901E+11 0.00 0.00 0.00 0.00 0.00 0.00
December 0.171738E+10 0.139265E+11 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.202207E+11 0.118697E+12 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.155118E+10 0.304978E+09 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.171738E+10 0.202910E+11 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: VAV_BOT WITH REHEAT

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.438646E+10 0.480626E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.489911E+10 0.217024E+11 0.736348E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.722759E+10 0.900859E+10 64191064.87 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.909821E+10 0.109084E+10 0.713072E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.856492E+10 0.867442E+09 0.195332E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.133429E+11 6699089.73 0.638689E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.165048E+11 0.00 0.108592E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.174860E+11 0.00 0.991574E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.946832E+10 98457601.75 0.413584E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.815085E+10 0.874002E+09 0.112922E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.662822E+10 0.626075E+10 0.616459E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.568093E+10 0.226729E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.111438E+12 0.110645E+12 0.352350E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.438646E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.174860E+11 0.480626E+11 0.108592E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: VAV_MID WITH REHEAT

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.437676E+11 0.798293E+12 31506.06 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.385300E+11 0.405329E+12 0.582135E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.482040E+11 0.238738E+12 0.247060E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.520516E+11 0.583879E+11 0.511108E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.637400E+11 0.400773E+11 0.167845E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.102027E+12 0.103481E+10 0.544162E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.124742E+12 0.00 0.910049E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.120460E+12 0.325248E+09 0.790119E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.739176E+11 0.105170E+11 0.364666E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.532459E+11 0.460793E+11 0.893588E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.426892E+11 0.204889E+12 0.448429E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.420256E+11 0.510963E+12 64277.76 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.805401E+12 0.231463E+13 0.292786E+13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.385300E+11 0.00 31506.06 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.124742E+12 0.798293E+12 0.910049E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: VAV_TOP WITH REHEAT

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.538050E+10 0.119127E+12 52824.02 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.425532E+10 0.620237E+11 0.390482E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.458644E+10 0.415864E+11 2331981.52 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.438980E+10 0.135185E+11 0.479342E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.571234E+10 0.100570E+11 0.173282E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.935228E+10 0.656607E+09 0.588673E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.117868E+11 26604971.68 0.988626E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.109047E+11 0.242664E+09 0.839504E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.628180E+10 0.359200E+10 0.370519E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.427012E+10 0.119535E+11 0.773586E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.418037E+10 0.382604E+11 0.331261E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.488727E+10 0.831558E+11 126715.88 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.759878E+11 0.384201E+12 0.309314E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.418037E+10 26604971.68 52824.02 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.117868E+11 0.119127E+12 0.988626E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: CAV_BAS

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.169075E+11 0.309488E+09 430925.51 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.150723E+11 0.00 0.282169E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.182976E+11 0.00 36227.49 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.166235E+11 0.00 0.252028E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.179135E+11 0.00 0.934050E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.175566E+11 0.00 0.331920E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.180332E+11 0.00 0.565008E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.192064E+11 0.00 0.517700E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.179129E+11 0.00 0.214620E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.177643E+11 0.00 0.593250E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.169256E+11 0.00 75754208.78 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.167469E+11 0.00 22839.71 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.208960E+12 0.309488E+09 0.181077E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.150723E+11 0.00 22839.71 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.192064E+11 0.309488E+09 0.565008E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: AIRLOOP DATACENTER BASEMENT

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.108397E+12 0.00 0.141405E+11 0.00 0.516233E+10 0.00 0.00 0.00 0.160315E+12 0.00 0.00 0.00
February 0.979067E+11 0.00 0.199849E+11 0.00 0.640890E+10 0.00 0.00 0.00 0.233306E+12 0.00 0.00 0.00
March 0.108397E+12 0.00 0.225640E+11 0.00 0.747561E+10 0.00 0.00 0.00 0.267840E+12 0.00 0.00 0.00
April 0.104900E+12 0.00 0.102206E+12 0.00 0.270907E+11 0.00 0.00 0.00 0.258029E+12 0.00 0.00 0.00
May 0.108397E+12 0.00 0.267735E+11 0.00 0.863402E+10 0.00 0.00 0.00 0.159780E+12 0.00 0.00 0.00
June 0.104900E+12 0.00 0.186677E+12 0.00 0.498434E+11 0.00 0.00 0.00 0.138303E+12 0.00 0.00 0.00
July 0.108397E+12 0.00 0.607444E+12 0.00 0.159087E+12 0.00 0.00 0.00 0.112335E+12 0.00 0.00 0.00
August 0.108397E+12 0.00 0.767043E+12 0.00 0.197142E+12 0.00 0.00 0.00 0.222965E+12 0.00 0.00 0.00
September 0.104900E+12 0.00 0.643832E+11 0.00 0.189391E+11 0.00 0.00 0.00 0.108790E+12 0.00 0.00 0.00
October 0.108397E+12 0.00 0.352686E+11 0.00 0.105224E+11 0.00 0.00 0.00 0.246358E+12 0.00 0.00 0.00
November 0.104900E+12 0.00 0.243952E+11 0.00 0.782664E+10 0.00 0.00 0.00 0.259199E+12 0.00 0.00 0.00
December 0.108397E+12 0.00 0.249724E+11 0.00 0.835927E+10 0.00 0.00 0.00 0.267840E+12 0.00 0.00 0.00
                         
Annual Sum or Average 0.127628E+13 0.00 0.189585E+13 0.00 0.506492E+12 0.00 0.00 0.00 0.243506E+13 0.00 0.00 0.00
Minimum of Months 0.979067E+11 0.00 0.141405E+11 0.00 0.516233E+10 0.00 0.00 0.00 0.108790E+12 0.00 0.00 0.00
Maximum of Months 0.108397E+12 0.00 0.767043E+12 0.00 0.197142E+12 0.00 0.00 0.00 0.267840E+12 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: AIRLOOP DATACENTER BOT

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.175618E+10 0.00 0.375130E+10 0.00 0.838011E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.158623E+10 0.00 0.104487E+11 0.00 0.217761E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.175618E+10 0.00 0.187195E+11 0.00 0.372217E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.169953E+10 0.00 0.249328E+11 0.00 0.478479E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.175618E+10 0.00 0.732277E+10 0.00 0.155625E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.169953E+10 0.00 0.141190E+11 0.00 0.301676E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.175618E+10 0.00 0.217739E+11 0.00 0.496792E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.175618E+10 0.00 0.278608E+11 0.00 0.613545E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.169953E+10 0.00 0.750625E+10 0.00 0.163597E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.175618E+10 0.00 0.133043E+11 0.00 0.267702E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.169953E+10 0.00 0.182558E+11 0.00 0.359442E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.175618E+10 0.00 0.242165E+11 0.00 0.473644E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.206776E+11 0.00 0.192212E+12 0.00 0.398428E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.158623E+10 0.00 0.375130E+10 0.00 0.838011E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.175618E+10 0.00 0.278608E+11 0.00 0.613545E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: AIRLOOP DATACENTER MID

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.168896E+11 0.00 0.993674E+10 0.00 0.236715E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.152551E+11 0.00 0.749871E+11 0.00 0.159134E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.168896E+11 0.00 0.156101E+12 0.00 0.314076E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.163447E+11 0.00 0.223610E+12 0.00 0.432501E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.168896E+11 0.00 0.592914E+11 0.00 0.127395E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.163447E+11 0.00 0.129824E+12 0.00 0.278842E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.168896E+11 0.00 0.205327E+12 0.00 0.469787E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.168896E+11 0.00 0.262463E+12 0.00 0.579903E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.163447E+11 0.00 0.632980E+11 0.00 0.139589E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.168896E+11 0.00 0.110904E+12 0.00 0.225627E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.163447E+11 0.00 0.150437E+12 0.00 0.300096E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.168896E+11 0.00 0.197206E+12 0.00 0.392116E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.198861E+12 0.00 0.164339E+13 0.00 0.344274E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.152551E+11 0.00 0.993674E+10 0.00 0.236715E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.168896E+11 0.00 0.262463E+12 0.00 0.579903E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: AIRLOOP DATACENTER TOP

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.171738E+10 0.00 0.401716E+09 0.00 96738080.66 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.155118E+10 0.00 0.561021E+10 0.00 0.120682E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.171738E+10 0.00 0.137256E+11 0.00 0.278806E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.166198E+10 0.00 0.210309E+11 0.00 0.409909E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.171738E+10 0.00 0.511642E+10 0.00 0.110670E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.166198E+10 0.00 0.127108E+11 0.00 0.274438E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.171738E+10 0.00 0.204504E+11 0.00 0.469814E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.171738E+10 0.00 0.260772E+11 0.00 0.578615E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.166198E+10 0.00 0.565314E+10 0.00 0.126365E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.171738E+10 0.00 0.943667E+10 0.00 0.194239E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.166198E+10 0.00 0.128925E+11 0.00 0.260241E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.171738E+10 0.00 0.174332E+11 0.00 0.350670E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.202207E+11 0.00 0.150539E+12 0.00 0.318412E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.155118E+10 0.00 0.401716E+09 0.00 96738080.66 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.171738E+10 0.00 0.260772E+11 0.00 0.578615E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: BASEMENT

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.242628E+11 0.00 0.00 68328450.88 0.00 0.00 0.474001E+11 0.00 0.44
February 0.762923E+10 0.00 0.00 86246460.74 0.00 0.00 0.570366E+11 0.00 0.57
March 0.259465E+10 0.00 0.00 0.123857E+09 0.00 0.00 0.779824E+11 0.00 0.71
April 0.314953E+09 0.00 0.00 0.121134E+09 0.00 0.00 0.736489E+11 0.00 0.99
May 0.176535E+09 42293098.00 0.00 0.120844E+09 6069632.46 0.00 0.714017E+11 0.00 1.20
June 0.106828E+09 0.380351E+09 0.00 0.111142E+09 300251.34 0.00 0.524142E+11 0.00 1.39
July 0.156183E+09 0.131700E+10 0.00 0.108026E+09 31552912.32 0.00 0.325710E+11 0.00 1.18
August 0.111076E+09 0.929872E+09 0.00 0.125653E+09 50281458.78 0.00 0.452840E+11 0.00 1.41
September 0.191764E+09 0.362785E+09 0.00 0.124020E+09 37479593.69 0.00 0.631325E+11 0.00 1.38
October 0.399806E+09 0.00 0.00 0.138812E+09 0.00 0.00 0.790109E+11 0.00 1.15
November 0.332586E+09 0.00 0.00 0.133867E+09 0.00 0.00 0.791548E+11 0.00 0.84
December 0.574166E+10 0.00 0.00 0.116233E+09 0.00 0.00 0.708303E+11 0.00 0.56
                   
Annual Sum or Average 0.420181E+11 0.303230E+10 0.00 0.137816E+10 0.125684E+09 0.00 0.749867E+12 0.00 0.99
Minimum of Months 0.106828E+09 0.00 0.00 68328450.88 0.00 0.00 0.325710E+11 0.00 0.44
Maximum of Months 0.242628E+11 0.131700E+10 0.00 0.138812E+09 50281458.78 0.00 0.791548E+11 0.00 1.41



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: CORE_BOTTOM

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.204308E+11 0.00 0.00 39710581.72 0.00 0.00 0.368245E+11 0.00 0.33
February 0.801043E+10 0.00 0.00 61540079.66 0.00 0.00 0.432601E+11 0.00 0.44
March 0.337450E+10 0.00 0.00 97440921.09 0.00 0.00 0.601290E+11 0.00 0.55
April 0.356542E+10 0.00 0.00 0.103587E+09 0.00 0.00 0.587627E+11 0.00 0.79
May 0.238517E+10 16443182.28 0.00 91332120.29 7690058.98 0.00 0.502932E+11 0.00 0.81
June 0.330102E+10 0.212281E+09 0.00 97387895.69 15039556.30 0.00 0.403504E+11 0.00 1.05
July 0.539208E+10 0.561790E+09 0.00 87894514.90 58037428.51 0.00 0.230865E+11 0.00 0.95
August 0.684564E+10 0.399691E+09 0.00 0.107493E+09 48738978.96 0.00 0.347577E+11 0.00 1.15
September 0.214868E+10 0.390291E+09 0.00 90363303.30 36221782.49 0.00 0.426602E+11 0.00 0.90
October 0.230804E+10 0.00 0.00 0.100861E+09 0.00 0.00 0.548549E+11 0.00 0.79
November 0.228404E+10 0.00 0.00 90951686.42 0.00 0.00 0.561441E+11 0.00 0.60
December 0.431182E+10 0.00 0.00 80221576.72 0.00 0.00 0.569396E+11 0.00 0.43
                   
Annual Sum or Average 0.643576E+11 0.158050E+10 0.00 0.104878E+10 0.165728E+09 0.00 0.558063E+12 0.00 0.73
Minimum of Months 0.214868E+10 0.00 0.00 39710581.72 0.00 0.00 0.230865E+11 0.00 0.33
Maximum of Months 0.204308E+11 0.561790E+09 0.00 0.107493E+09 58037428.51 0.00 0.601290E+11 0.00 1.15



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: CORE_MID

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.403951E+12 0.00 0.00 31080698.44 0.00 0.822573E+10 0.645630E+11 0.00 0.28
February 0.261716E+12 0.00 0.00 0.134317E+09 0.00 0.117258E+10 0.122996E+12 0.00 0.32
March 0.185557E+12 0.00 0.00 0.329036E+09 0.00 0.177321E+10 0.253493E+12 0.00 0.38
April 0.814328E+11 0.00 0.00 0.466602E+09 0.00 0.00 0.315782E+12 0.00 0.52
May 0.529817E+11 0.181732E+09 0.00 0.555843E+09 88219000.22 0.00 0.338745E+12 0.00 0.63
June 0.247879E+11 0.224672E+10 0.00 0.709603E+09 99438370.68 0.00 0.304364E+12 0.00 0.82
July 0.213963E+11 0.607385E+10 0.00 0.654080E+09 0.284846E+09 0.00 0.168697E+12 0.00 0.69
August 0.186404E+11 0.421588E+10 0.00 0.775880E+09 0.482626E+09 0.00 0.251521E+12 0.00 0.80
September 0.289099E+11 0.370361E+10 0.00 0.615299E+09 0.373769E+09 0.00 0.308090E+12 0.00 0.70
October 0.694884E+11 0.00 0.00 0.504522E+09 0.00 0.00 0.317065E+12 0.00 0.56
November 0.171640E+12 0.00 0.00 0.292157E+09 0.00 0.577217E+09 0.211323E+12 0.00 0.40
December 0.303651E+12 0.00 0.00 0.133736E+09 0.00 0.225171E+10 0.126275E+12 0.00 0.30
                   
Annual Sum or Average 0.162415E+13 0.164218E+11 0.00 0.520215E+10 0.132890E+10 0.140005E+11 0.278291E+13 0.00 0.53
Minimum of Months 0.186404E+11 0.00 0.00 31080698.44 0.00 0.00 0.645630E+11 0.00 0.28
Maximum of Months 0.403951E+12 0.607385E+10 0.00 0.775880E+09 0.482626E+09 0.822573E+10 0.338745E+12 0.00 0.82



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: CORE_TOP

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.313572E+11 0.00 0.00 67742.10 0.00 0.925589E+10 0.133352E+09 0.00 0.26
February 0.280191E+11 0.00 0.00 1582299.46 0.00 0.322267E+10 0.206292E+10 0.00 0.30
March 0.250375E+11 0.00 0.00 8630451.09 0.00 0.209828E+10 0.899843E+10 0.00 0.32
April 0.152056E+11 0.00 0.00 22244139.00 0.00 82095570.93 0.177166E+11 0.00 0.45
May 0.106512E+11 10393691.53 0.00 37436203.10 5797241.03 0.281691E+09 0.245979E+11 0.00 0.59
June 0.470913E+10 0.131435E+09 0.00 62874636.24 13476320.29 0.00 0.262007E+11 0.00 0.83
July 0.307293E+10 0.408109E+09 0.00 61636673.51 24201817.52 0.00 0.147089E+11 0.00 0.70
August 0.331901E+10 0.266902E+09 0.00 69574148.64 40662045.35 0.00 0.206318E+11 0.00 0.77
September 0.746551E+10 0.334213E+09 0.00 40858645.43 29639576.22 1337623.30 0.205358E+11 0.00 0.64
October 0.154488E+11 0.00 0.00 20080317.38 0.00 0.183095E+09 0.143743E+11 0.00 0.46
November 0.223664E+11 0.00 0.00 6170690.33 0.00 0.162420E+10 0.589743E+10 0.00 0.33
December 0.294053E+11 0.00 0.00 1353324.57 0.00 0.473226E+10 0.158872E+10 0.00 0.27
                   
Annual Sum or Average 0.196058E+12 0.115105E+10 0.00 0.332509E+09 0.113777E+09 0.214815E+11 0.157447E+12 0.00 0.49
Minimum of Months 0.307293E+10 0.00 0.00 67742.10 0.00 0.00 0.133352E+09 0.00 0.26
Maximum of Months 0.313572E+11 0.408109E+09 0.00 69574148.64 40662045.35 0.925589E+10 0.262007E+11 0.00 0.83



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.230874E+10 0.00 0.00 0.00 0.00 0.390308E+10 0.00 0.00 0.27
February 0.302383E+10 0.00 0.00 300755.94 0.00 0.141369E+10 0.223453E+09 0.00 0.31
March 0.330751E+10 0.00 0.00 1666700.54 0.00 0.368131E+09 0.143696E+10 0.00 0.35
April 0.221574E+10 0.00 0.00 4756899.88 0.00 1053427.14 0.324423E+10 0.00 0.60
May 0.143231E+10 5077684.08 0.00 6790426.87 963647.00 6855163.28 0.392744E+10 0.00 0.75
June 0.696791E+09 40522279.14 0.00 12168412.93 1875072.30 0.00 0.482634E+10 0.00 1.19
July 0.776812E+09 0.125645E+09 0.00 12156776.99 7272713.24 0.00 0.294859E+10 0.00 1.10
August 0.110147E+10 88520321.93 0.00 12013611.27 6107517.63 0.00 0.362696E+10 0.00 1.19
September 0.133458E+10 70621974.19 0.00 6153094.05 4538978.45 0.00 0.288365E+10 0.00 0.76
October 0.236535E+10 0.00 0.00 3501563.12 0.00 0.00 0.229336E+10 0.00 0.54
November 0.324666E+10 0.00 0.00 1100811.65 0.00 0.182939E+09 0.986479E+09 0.00 0.36
December 0.337889E+10 0.00 0.00 145886.07 0.00 0.132290E+10 0.214413E+09 0.00 0.26
                   
Annual Sum or Average 0.251887E+11 0.330387E+09 0.00 60754939.30 20757928.61 0.719865E+10 0.266119E+11 0.00 0.64
Minimum of Months 0.696791E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.26
Maximum of Months 0.337889E+10 0.125645E+09 0.00 12168412.93 7272713.24 0.390308E+10 0.482634E+10 0.00 1.19



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.332696E+10 0.00 0.00 54166.28 0.00 0.416560E+10 60841149.08 0.00 0.52
February 0.370797E+10 0.00 0.00 1319422.05 0.00 0.158023E+10 0.806118E+09 0.00 0.63
March 0.400966E+10 0.00 0.00 3860806.50 0.00 0.566904E+09 0.238249E+10 0.00 0.72
April 0.302371E+10 0.00 0.00 7286841.02 0.00 15368425.99 0.428459E+10 0.00 1.17
May 0.200724E+10 3503758.11 0.00 8928721.58 1226660.06 15175414.45 0.525440E+10 0.00 1.44
June 0.109425E+10 34001771.36 0.00 15973650.28 2398996.30 0.00 0.563119E+10 0.00 2.15
July 0.107908E+10 94516713.53 0.00 18110159.21 9257691.77 0.00 0.395302E+10 0.00 2.15
August 0.174405E+10 76194524.99 0.00 12758018.51 7488012.10 0.00 0.436245E+10 0.00 2.19
September 0.186222E+10 56310558.52 0.00 8345113.29 5701892.02 0.00 0.371946E+10 0.00 1.46
October 0.297176E+10 0.00 0.00 5039382.27 0.00 2396808.59 0.292568E+10 0.00 1.02
November 0.400396E+10 0.00 0.00 1115950.38 0.00 0.431165E+09 0.111538E+10 0.00 0.68
December 0.406085E+10 0.00 0.00 145714.75 0.00 0.205499E+10 0.135090E+09 0.00 0.52
                   
Annual Sum or Average 0.328917E+11 0.264527E+09 0.00 82937946.11 26073252.26 0.883183E+10 0.346307E+11 0.00 1.22
Minimum of Months 0.107908E+10 0.00 0.00 54166.28 0.00 0.00 60841149.08 0.00 0.52
Maximum of Months 0.406085E+10 94516713.53 0.00 18110159.21 9257691.77 0.416560E+10 0.563119E+10 0.00 2.19



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.365166E+10 0.00 0.00 4703655.52 0.00 0.426354E+10 0.336817E+10 0.00 0.52
February 0.334113E+10 0.00 0.00 11831396.23 0.00 0.156402E+10 0.597716E+10 0.00 0.83
March 0.406222E+10 0.00 0.00 12567619.76 0.00 0.626781E+09 0.805168E+10 0.00 0.95
April 0.338627E+10 0.00 0.00 12778960.28 0.00 54602723.21 0.734062E+10 0.00 1.24
May 0.262915E+10 7205407.25 0.00 11480578.96 1518210.74 0.110643E+09 0.630141E+10 0.00 1.27
June 0.169896E+10 61072050.48 0.00 15342236.83 2954147.02 0.00 0.533698E+10 0.00 1.56
July 0.150953E+10 0.187970E+09 0.00 16399192.46 9888942.24 0.00 0.327898E+10 0.00 1.49
August 0.207457E+10 0.177484E+09 0.00 19818067.76 6951720.87 0.00 0.507669E+10 0.00 1.93
September 0.199488E+10 0.192599E+09 0.00 17476101.98 2144475.30 669280.39 0.680686E+10 0.00 1.72
October 0.263220E+10 0.00 0.00 20092152.27 0.00 50207458.29 0.933927E+10 0.00 1.51
November 0.340564E+10 0.00 0.00 11497239.16 0.00 0.505456E+09 0.709579E+10 0.00 0.92
December 0.396278E+10 0.00 0.00 5986202.70 0.00 0.192995E+10 0.423242E+10 0.00 0.58
                   
Annual Sum or Average 0.343490E+11 0.626330E+09 0.00 0.159973E+09 23457496.18 0.910586E+10 0.722060E+11 0.00 1.21
Minimum of Months 0.150953E+10 0.00 0.00 4703655.52 0.00 0.00 0.327898E+10 0.00 0.52
Maximum of Months 0.406222E+10 0.192599E+09 0.00 20092152.27 9888942.24 0.426354E+10 0.933927E+10 0.00 1.93



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.506871E+10 0.00 0.00 316768.83 0.00 0.385665E+10 0.338324E+09 0.00 0.64
February 0.502569E+10 0.00 0.00 2913513.37 0.00 0.716151E+09 0.201067E+10 0.00 0.83
March 0.371864E+10 0.00 0.00 6762676.47 0.00 88889288.95 0.543245E+10 0.00 1.01
April 0.138794E+10 0.00 0.00 15468901.62 0.00 0.00 0.870200E+10 0.00 1.79
May 0.196047E+10 5654081.17 0.00 13419652.50 1504304.35 1116436.04 0.652908E+10 0.00 1.80
June 0.832618E+09 59492957.89 0.00 19712577.55 696191.73 0.00 0.628534E+10 0.00 2.42
July 0.867338E+09 0.204511E+09 0.00 22000449.71 6029020.24 0.00 0.409571E+10 0.00 2.32
August 0.108578E+10 0.144985E+09 0.00 22866167.48 1784339.11 0.00 0.598395E+10 0.00 2.76
September 0.178668E+10 0.125309E+09 0.00 9384713.90 638955.95 0.00 0.435569E+10 0.00 1.72
October 0.238940E+10 0.00 0.00 8354332.27 0.00 0.00 0.530510E+10 0.00 1.41
November 0.361571E+10 0.00 0.00 4791381.34 0.00 45239114.67 0.399465E+10 0.00 0.98
December 0.552210E+10 0.00 0.00 2381408.14 0.00 0.222105E+09 0.231557E+10 0.00 0.68
                   
Annual Sum or Average 0.332611E+11 0.539953E+09 0.00 0.128373E+09 10652811.38 0.493015E+10 0.553485E+11 0.00 1.53
Minimum of Months 0.832618E+09 0.00 0.00 316768.83 0.00 0.00 0.338324E+09 0.00 0.64
Maximum of Months 0.552210E+10 0.204511E+09 0.00 22866167.48 6029020.24 0.385665E+10 0.870200E+10 0.00 2.76



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.278505E+10 0.00 0.00 0.00 0.00 0.762956E+11 0.00 0.00 0.35
February 0.118591E+11 0.00 0.00 0.00 0.00 0.397713E+11 0.00 0.00 0.33
March 0.276468E+11 0.00 0.00 79217.22 0.00 0.216568E+11 0.209000E+09 0.00 0.33
April 0.265357E+11 0.00 0.00 9220160.50 0.00 0.521957E+10 0.666571E+10 0.00 0.41
May 0.203766E+11 57693933.61 0.00 35107438.29 11437841.80 0.286699E+10 0.176815E+11 0.00 0.57
June 0.895678E+10 0.458219E+09 0.00 85382861.18 12479365.65 5191612.97 0.311395E+11 0.00 0.92
July 0.495020E+10 0.152748E+10 0.00 87389904.00 35747723.03 0.00 0.191957E+11 0.00 0.82
August 0.901603E+10 0.106492E+10 0.00 75848292.36 60568819.25 4992133.08 0.200783E+11 0.00 0.80
September 0.187275E+11 0.661048E+09 0.00 32090708.25 46907440.22 0.995008E+09 0.127707E+11 0.00 0.59
October 0.278999E+11 0.00 0.00 6619772.63 0.00 0.477412E+10 0.413130E+10 0.00 0.41
November 0.217527E+11 0.00 0.00 0.00 0.00 0.213508E+11 0.00 0.00 0.34
December 0.813763E+10 0.00 0.00 0.00 0.00 0.505295E+11 0.00 0.00 0.31
                   
Annual Sum or Average 0.188644E+12 0.376937E+10 0.00 0.331738E+09 0.167141E+09 0.223470E+12 0.111872E+12 0.00 0.51
Minimum of Months 0.278505E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.31
Maximum of Months 0.278999E+11 0.152748E+10 0.00 87389904.00 60568819.25 0.762956E+11 0.311395E+11 0.00 0.92



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.114713E+11 0.00 0.00 0.00 0.00 0.731477E+11 0.00 0.00 0.61
February 0.221677E+11 0.00 0.00 3442725.25 0.00 0.411604E+11 0.227886E+10 0.00 0.67
March 0.351287E+11 0.00 0.00 18249925.95 0.00 0.229226E+11 0.121065E+11 0.00 0.73
April 0.280080E+11 0.00 0.00 52103584.09 0.00 0.545969E+10 0.312887E+11 0.00 1.05
May 0.225540E+11 44442308.08 0.00 70911942.42 15354174.07 0.333094E+10 0.410972E+11 0.00 1.36
June 0.117465E+11 0.444432E+09 0.00 0.154954E+09 16526908.11 13993008.01 0.502557E+11 0.00 2.08
July 0.639058E+10 0.131524E+10 0.00 0.196362E+09 49576310.43 0.00 0.373315E+11 0.00 2.03
August 0.116055E+11 0.111522E+10 0.00 0.121241E+09 82825578.09 28279443.27 0.394828E+11 0.00 1.96
September 0.229071E+11 0.633453E+09 0.00 64619422.62 64877716.06 0.110603E+10 0.269993E+11 0.00 1.36
October 0.340083E+11 0.00 0.00 23220170.06 0.00 0.496647E+10 0.144153E+11 0.00 0.94
November 0.320828E+11 0.00 0.00 2031432.69 0.00 0.244644E+11 0.165864E+10 0.00 0.71
December 0.179539E+11 0.00 0.00 0.00 0.00 0.548226E+11 0.00 0.00 0.62
                   
Annual Sum or Average 0.256024E+12 0.355279E+10 0.00 0.707135E+09 0.229161E+09 0.231423E+12 0.256915E+12 0.00 1.18
Minimum of Months 0.639058E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.61
Maximum of Months 0.351287E+11 0.131524E+10 0.00 0.196362E+09 82825578.09 0.731477E+11 0.502557E+11 0.00 2.08



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.253124E+11 0.00 0.00 33573275.70 0.00 0.646259E+11 0.275663E+11 0.00 0.55
February 0.267312E+11 0.00 0.00 0.109052E+09 0.00 0.315263E+11 0.511005E+11 0.00 0.85
March 0.351632E+11 0.00 0.00 0.107247E+09 0.00 0.217387E+11 0.669663E+11 0.00 0.92
April 0.306982E+11 0.00 0.00 0.101932E+09 0.00 0.704610E+10 0.557103E+11 0.00 1.11
May 0.278135E+11 94951370.43 0.00 97404716.76 18197820.44 0.480187E+10 0.500422E+11 0.00 1.19
June 0.192389E+11 0.760417E+09 0.00 0.125753E+09 15106640.64 0.109961E+09 0.411528E+11 0.00 1.39
July 0.113790E+11 0.248550E+10 0.00 0.141653E+09 41808302.42 0.00 0.255084E+11 0.00 1.27
August 0.155131E+11 0.249147E+10 0.00 0.175594E+09 69204541.73 20834302.87 0.399000E+11 0.00 1.64
September 0.225051E+11 0.227222E+10 0.00 0.164144E+09 13567901.60 0.112166E+10 0.585387E+11 0.00 1.67
October 0.267198E+11 0.00 0.00 0.187843E+09 0.00 0.356301E+10 0.809203E+11 0.00 1.46
November 0.291540E+11 0.00 0.00 98325391.57 0.00 0.185366E+11 0.565214E+11 0.00 0.87
December 0.299912E+11 0.00 0.00 37033108.29 0.00 0.436657E+11 0.282761E+11 0.00 0.58
                   
Annual Sum or Average 0.300220E+12 0.810456E+10 0.00 0.137956E+10 0.157885E+09 0.196757E+12 0.582203E+12 0.00 1.12
Minimum of Months 0.113790E+11 0.00 0.00 33573275.70 0.00 0.00 0.255084E+11 0.00 0.55
Maximum of Months 0.351632E+11 0.249147E+10 0.00 0.187843E+09 69204541.73 0.646259E+11 0.809203E+11 0.00 1.67



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.147038E+11 0.00 0.00 118030.39 0.00 0.755867E+11 0.355954E+09 0.00 0.66
February 0.263771E+11 0.00 0.00 6411397.97 0.00 0.410340E+11 0.434508E+10 0.00 0.74
March 0.416954E+11 0.00 0.00 16245143.22 0.00 0.227436E+11 0.125181E+11 0.00 0.82
April 0.374863E+11 0.00 0.00 47897993.84 0.00 0.470434E+10 0.244967E+11 0.00 1.17
May 0.281887E+11 58165515.56 0.00 90508403.21 17316964.49 0.321862E+10 0.377565E+11 0.00 1.49
June 0.166385E+11 0.626241E+09 0.00 0.112271E+09 7139274.19 55525259.35 0.348406E+11 0.00 1.83
July 0.941912E+10 0.236020E+10 0.00 0.132648E+09 9037848.82 0.00 0.206538E+11 0.00 1.58
August 0.148091E+11 0.150217E+10 0.00 0.103543E+09 35573854.07 7485986.95 0.240377E+11 0.00 1.65
September 0.286572E+11 0.120433E+10 0.00 51390780.31 5719343.71 0.103183E+10 0.202651E+11 0.00 1.40
October 0.402793E+11 0.00 0.00 26684635.50 0.00 0.453190E+10 0.143758E+11 0.00 1.07
November 0.355145E+11 0.00 0.00 6706702.33 0.00 0.222910E+11 0.586903E+10 0.00 0.78
December 0.230672E+11 0.00 0.00 426885.28 0.00 0.548165E+11 0.501895E+09 0.00 0.66
                   
Annual Sum or Average 0.316836E+12 0.575111E+10 0.00 0.594852E+09 74787285.28 0.230021E+12 0.200016E+12 0.00 1.16
Minimum of Months 0.941912E+10 0.00 0.00 118030.39 0.00 0.00 0.355954E+09 0.00 0.66
Maximum of Months 0.416954E+11 0.236020E+10 0.00 0.132648E+09 35573854.07 0.755867E+11 0.377565E+11 0.00 1.83



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.135978E+09 0.00 0.00 0.00 0.00 0.802467E+10 0.00 0.00 0.38
February 0.692801E+09 0.00 0.00 0.00 0.00 0.457949E+10 0.00 0.00 0.35
March 0.194049E+10 0.00 0.00 0.00 0.00 0.299931E+10 0.00 0.00 0.34
April 0.231176E+10 0.00 0.00 625182.95 0.00 0.111452E+10 0.456071E+09 0.00 0.41
May 0.193150E+10 3386812.52 0.00 3042908.35 747508.04 0.671110E+09 0.160548E+10 0.00 0.59
June 0.103159E+10 25248696.77 0.00 8433698.20 1737664.13 33854049.90 0.286083E+10 0.00 0.94
July 0.612917E+09 95047802.10 0.00 9193246.60 3120631.55 344848.81 0.175262E+10 0.00 0.84
August 0.100397E+10 65492023.49 0.00 7859412.86 5243046.78 18960429.03 0.180155E+10 0.00 0.80
September 0.176483E+10 58272316.67 0.00 2725910.49 3937201.41 0.348572E+09 0.100608E+10 0.00 0.59
October 0.232580E+10 0.00 0.00 291580.00 0.00 0.110849E+10 0.165006E+09 0.00 0.42
November 0.124136E+10 0.00 0.00 0.00 0.00 0.285466E+10 0.00 0.00 0.35
December 0.375224E+09 0.00 0.00 0.00 0.00 0.556056E+10 0.00 0.00 0.33
                   
Annual Sum or Average 0.153682E+11 0.247448E+09 0.00 32171939.46 14786051.91 0.273145E+11 0.964762E+10 0.00 0.53
Minimum of Months 0.135978E+09 0.00 0.00 0.00 0.00 344848.81 0.00 0.00 0.33
Maximum of Months 0.232580E+10 95047802.10 0.00 9193246.60 5243046.78 0.802467E+10 0.286083E+10 0.00 0.94



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.600150E+09 0.00 0.00 0.00 0.00 0.655780E+10 0.00 0.00 0.55
February 0.165582E+10 0.00 0.00 93830.54 0.00 0.393033E+10 78122628.34 0.00 0.62
March 0.284951E+10 0.00 0.00 1084552.81 0.00 0.247868E+10 0.792584E+09 0.00 0.67
April 0.240635E+10 0.00 0.00 4027130.93 0.00 0.965820E+09 0.254393E+10 0.00 0.99
May 0.197942E+10 2534518.69 0.00 6395817.01 974605.13 0.611549E+09 0.382015E+10 0.00 1.34
June 0.105912E+10 23967149.98 0.00 15222897.84 2265576.13 32073191.47 0.488499E+10 0.00 2.10
July 0.594156E+09 80680526.18 0.00 19537182.17 4068696.71 449615.79 0.366734E+10 0.00 2.08
August 0.102088E+10 70134362.57 0.00 12530851.90 6687500.71 13125292.36 0.379829E+10 0.00 1.96
September 0.191041E+10 57088994.41 0.00 5662676.60 4950939.80 0.321208E+09 0.237714E+10 0.00 1.31
October 0.295575E+10 0.00 0.00 1386207.86 0.00 0.942875E+09 0.838969E+09 0.00 0.88
November 0.220142E+10 0.00 0.00 33151.85 0.00 0.273040E+10 31863439.15 0.00 0.67
December 0.913888E+09 0.00 0.00 0.00 0.00 0.518904E+10 0.00 0.00 0.56
                   
Annual Sum or Average 0.201469E+11 0.234406E+09 0.00 65974299.50 18947318.49 0.237734E+11 0.228334E+11 0.00 1.15
Minimum of Months 0.594156E+09 0.00 0.00 0.00 0.00 449615.79 0.00 0.00 0.55
Maximum of Months 0.295575E+10 80680526.18 0.00 19537182.17 6687500.71 0.655780E+10 0.488499E+10 0.00 2.10



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.166990E+10 0.00 0.00 2056226.55 0.00 0.660688E+10 0.187023E+10 0.00 0.51
February 0.212971E+10 0.00 0.00 8090513.95 0.00 0.350004E+10 0.394720E+10 0.00 0.77
March 0.283024E+10 0.00 0.00 8590720.19 0.00 0.270320E+10 0.584410E+10 0.00 0.86
April 0.267001E+10 0.00 0.00 8142190.29 0.00 0.129834E+10 0.511951E+10 0.00 1.06
May 0.253956E+10 5094884.99 0.00 8876950.82 1230699.90 0.959379E+09 0.499109E+10 0.00 1.21
June 0.195959E+10 39888751.85 0.00 13380077.90 2860896.40 99688138.48 0.416671E+10 0.00 1.46
July 0.121809E+10 0.147022E+09 0.00 15656370.42 3114386.37 2055099.14 0.268150E+10 0.00 1.35
August 0.157995E+10 0.149581E+09 0.00 18634212.46 5588850.44 30931856.27 0.409722E+10 0.00 1.70
September 0.196973E+10 0.190747E+09 0.00 15298582.42 1060866.11 0.375191E+09 0.568521E+10 0.00 1.65
October 0.240044E+10 0.00 0.00 14778317.90 0.00 0.915378E+09 0.673318E+10 0.00 1.37
November 0.245244E+10 0.00 0.00 6233048.40 0.00 0.228123E+10 0.401723E+10 0.00 0.78
December 0.220011E+10 0.00 0.00 2431251.16 0.00 0.463974E+10 0.187462E+10 0.00 0.53
                   
Annual Sum or Average 0.256198E+11 0.532334E+09 0.00 0.122168E+09 13855699.22 0.234121E+11 0.510278E+11 0.00 1.10
Minimum of Months 0.121809E+10 0.00 0.00 2056226.55 0.00 2055099.14 0.187023E+10 0.00 0.51
Maximum of Months 0.283024E+10 0.190747E+09 0.00 18634212.46 5588850.44 0.660688E+10 0.673318E+10 0.00 1.70



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.838133E+09 0.00 0.00 3325.29 0.00 0.707853E+10 13753839.29 0.00 0.62
February 0.191284E+10 0.00 0.00 507829.43 0.00 0.420917E+10 0.351597E+09 0.00 0.71
March 0.323696E+10 0.00 0.00 1395556.24 0.00 0.281903E+10 0.113171E+10 0.00 0.80
April 0.345067E+10 0.00 0.00 4196068.74 0.00 0.925223E+09 0.226499E+10 0.00 1.17
May 0.265987E+10 3306316.02 0.00 8676805.65 1106795.01 0.691439E+09 0.379662E+10 0.00 1.54
June 0.181989E+10 35502017.91 0.00 13796301.66 119677.14 36486392.39 0.344244E+10 0.00 1.95
July 0.104830E+10 0.140065E+09 0.00 14279825.25 1080991.78 0.00 0.204039E+10 0.00 1.65
August 0.154832E+10 88232235.23 0.00 11034688.81 2862530.30 23756758.54 0.231684E+10 0.00 1.70
September 0.258327E+10 0.103920E+09 0.00 4832985.26 1153525.24 0.340246E+09 0.195249E+10 0.00 1.42
October 0.331652E+10 0.00 0.00 2167402.33 0.00 0.103121E+10 0.126783E+10 0.00 1.07
November 0.253454E+10 0.00 0.00 434055.67 0.00 0.270035E+10 0.425186E+09 0.00 0.76
December 0.147609E+10 0.00 0.00 19503.11 0.00 0.533394E+10 30918612.53 0.00 0.63
                   
Annual Sum or Average 0.264254E+11 0.371025E+09 0.00 61344347.44 6323519.47 0.251894E+11 0.190348E+11 0.00 1.17
Minimum of Months 0.838133E+09 0.00 0.00 3325.29 0.00 0.00 13753839.29 0.00 0.62
Maximum of Months 0.345067E+10 0.140065E+09 0.00 14279825.25 2862530.30 0.707853E+10 0.379662E+10 0.00 1.95



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 17750309.59 0.00 0.00 2488290.78 0.00 0.00 0.832486E+09 0.00 0.28
February 0.00 0.00 0.00 7634538.68 0.00 0.00 0.645556E+09 0.00 0.28
March 0.00 0.00 0.00 14601312.95 0.00 0.00 0.661614E+09 0.00 0.31
April 0.00 0.00 0.00 18468304.80 0.00 0.00 0.461720E+09 0.00 0.29
May 0.00 153001.14 0.00 4171266.36 0.00 0.00 0.408421E+09 0.00 0.29
June 0.00 13317302.34 0.00 7658731.83 0.00 0.00 0.199993E+09 0.00 0.30
July 0.00 21213902.83 0.00 9094238.94 0.00 0.00 79937235.00 0.00 0.28
August 0.00 5912623.85 0.00 17153548.80 0.00 0.00 0.147379E+09 0.00 0.31
September 0.00 11479249.93 0.00 3720491.65 0.00 0.00 0.257750E+09 0.00 0.29
October 0.00 0.00 0.00 8863880.95 0.00 0.00 0.439715E+09 0.00 0.28
November 0.00 0.00 0.00 12658813.69 0.00 0.00 0.543613E+09 0.00 0.28
December 0.00 0.00 0.00 17307668.20 0.00 0.00 0.716687E+09 0.00 0.28
                   
Annual Sum or Average 17750309.59 52076080.09 0.00 0.123821E+09 0.00 0.00 0.539487E+10 0.00 0.29
Minimum of Months 0.00 0.00 0.00 2488290.78 0.00 0.00 79937235.00 0.00 0.28
Maximum of Months 17750309.59 21213902.83 0.00 18468304.80 0.00 0.00 0.832486E+09 0.00 0.31



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: DATACENTER_MID_ZN_6

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.303416E+10 0.00 0.00 8685900.15 0.00 0.00 0.543781E+10 0.00 0.28
February 0.00 0.00 0.00 58974633.49 0.00 0.00 0.647307E+10 0.00 0.28
March 0.00 0.00 0.00 0.125642E+09 0.00 0.00 0.663600E+10 0.00 0.31
April 0.00 0.00 0.00 0.167765E+09 0.00 0.00 0.463190E+10 0.00 0.29
May 18588329.52 1450962.40 0.00 33405635.79 0.00 0.00 0.407836E+10 0.00 0.29
June 0.00 0.131858E+09 0.00 70573667.39 0.00 0.00 0.200839E+10 0.00 0.30
July 0.00 0.211095E+09 0.00 85857905.69 0.00 0.00 0.805437E+09 0.00 0.28
August 0.00 59649360.84 0.00 0.161269E+09 0.00 0.00 0.148162E+10 0.00 0.31
September 0.00 0.112320E+09 0.00 30277161.32 0.00 0.00 0.259879E+10 0.00 0.29
October 0.00 0.00 0.00 75582679.01 0.00 0.00 0.440989E+10 0.00 0.28
November 0.00 0.00 0.00 0.108291E+09 0.00 0.00 0.545343E+10 0.00 0.28
December 0.00 0.00 0.00 0.148122E+09 0.00 0.00 0.718969E+10 0.00 0.28
                   
Annual Sum or Average 0.305275E+10 0.516373E+09 0.00 0.107445E+10 0.00 0.00 0.512044E+11 0.00 0.29
Minimum of Months 0.00 0.00 0.00 8685900.15 0.00 0.00 0.805437E+09 0.00 0.28
Maximum of Months 0.303416E+10 0.211095E+09 0.00 0.167765E+09 0.00 0.00 0.718969E+10 0.00 0.31



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.567837E+09 0.00 0.00 384867.62 0.00 0.00 0.263225E+09 0.00 0.28
February 0.00 0.00 0.00 4960722.52 0.00 0.00 0.648194E+09 0.00 0.28
March 0.00 0.00 0.00 11566459.16 0.00 0.00 0.664620E+09 0.00 0.31
April 0.00 0.00 0.00 16046435.29 0.00 0.00 0.464068E+09 0.00 0.29
May 28326643.91 147070.41 0.00 2917176.89 0.00 0.00 0.381122E+09 0.00 0.29
June 0.00 13221639.56 0.00 6910745.78 0.00 0.00 0.201172E+09 0.00 0.30
July 0.00 21119792.57 0.00 8548498.67 0.00 0.00 80683679.76 0.00 0.28
August 0.00 5980605.76 0.00 15995764.69 0.00 0.00 0.148380E+09 0.00 0.31
September 7481603.52 11218083.11 0.00 2612052.28 0.00 0.00 0.253936E+09 0.00 0.29
October 0.00 0.00 0.00 6712768.74 0.00 0.00 0.442064E+09 0.00 0.28
November 0.00 0.00 0.00 9834061.36 0.00 0.00 0.546395E+09 0.00 0.28
December 0.00 0.00 0.00 13734595.88 0.00 0.00 0.720142E+09 0.00 0.28
                   
Annual Sum or Average 0.603645E+09 51687191.41 0.00 0.100224E+09 0.00 0.00 0.481400E+10 0.00 0.29
Minimum of Months 0.00 0.00 0.00 384867.62 0.00 0.00 80683679.76 0.00 0.28
Maximum of Months 0.567837E+09 21119792.57 0.00 16046435.29 0.00 0.00 0.720142E+09 0.00 0.31



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.00 0.00 0.00 0.899342E+09 0.00 0.00 0.494851E+12 0.00 7.40
February 0.00 0.00 0.00 0.133243E+10 0.00 0.00 0.751252E+12 0.00 15.50
March 0.00 0.00 0.00 0.190649E+10 0.00 0.00 0.108849E+13 0.00 22.92
April 0.00 0.00 0.00 0.228178E+10 0.00 0.00 0.122917E+13 0.00 36.39
May 0.00 0.00 0.00 0.562634E+09 0.00 0.00 0.492113E+12 0.00 17.40
June 0.00 0.229975E+10 0.00 0.122370E+10 0.00 0.00 0.580708E+12 0.00 33.08
July 0.00 0.264912E+10 0.00 0.206998E+10 0.00 0.00 0.508942E+12 0.00 37.31
August 0.00 0.110654E+09 0.00 0.308767E+10 0.00 0.00 0.737617E+12 0.00 45.80
September 0.00 0.908784E+09 0.00 0.545810E+09 0.00 0.00 0.406497E+12 0.00 21.23
October 0.00 0.00 0.00 0.112197E+10 0.00 0.00 0.817469E+12 0.00 24.49
November 0.00 0.00 0.00 0.188347E+10 0.00 0.00 0.105421E+13 0.00 26.06
December 0.00 0.00 0.00 0.318159E+10 0.00 0.00 0.133143E+13 0.00 25.86
                   
Annual Sum or Average 0.00 0.596831E+10 0.00 0.200969E+11 0.00 0.00 0.949275E+13 0.00 26.17
Minimum of Months 0.00 0.00 0.00 0.545810E+09 0.00 0.00 0.406497E+12 0.00 7.40
Maximum of Months 0.00 0.264912E+10 0.00 0.318159E+10 0.00 0.00 0.133143E+13 0.00 45.80



Table of Contents

Report: HeatEmissionsReportMonthly

For: Environment

Timestamp: 2023-10-16 08:43:39

Custom Monthly Report

SITE TOTAL SURFACE HEAT EMISSION TO AIR [J] SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J]
January 0.265165E+12 0.461601E+11 0.00 0.213850E+13 0.277854E+12
February 0.354242E+12 0.360540E+11 0.00 0.236151E+13 0.270811E+12
March 0.611807E+12 0.337316E+11 0.00 0.304117E+13 0.330496E+12
April 0.656598E+12 0.240427E+11 0.00 0.332368E+13 0.525954E+12
May 0.868397E+12 0.236522E+11 0.00 0.255101E+13 0.430250E+12
June 0.948750E+12 0.122389E+11 0.00 0.235360E+13 0.131111E+13
July 0.939531E+12 0.804868E+10 0.00 0.196345E+13 0.248720E+13
August 0.779766E+12 0.871622E+10 0.00 0.236797E+13 0.253161E+13
September 0.585056E+12 0.157490E+11 0.00 0.222914E+13 0.804244E+12
October 0.380508E+12 0.230541E+11 0.00 0.300949E+13 0.373773E+12
November 0.206449E+12 0.324703E+11 0.00 0.295794E+13 0.319308E+12
December 0.170156E+12 0.412799E+11 0.00 0.302871E+13 0.455573E+12
           
Annual Sum or Average 0.676642E+13 0.305198E+12 0.00 0.313262E+14 0.101182E+14
Minimum of Months 0.170156E+12 0.804868E+10 0.00 0.196345E+13 0.270811E+12
Maximum of Months 0.948750E+12 0.461601E+11 0.00 0.332368E+13 0.253161E+13