Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:43
Tabular Output Report in Format: HTML
Building: OfficeLarge
Environment: RUNPERIOD 1 ** Great Falls Intl Arpt MT USA TMY3 WMO#=727750
Simulation Timestamp: 2023-10-16 08:43:39
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 08:43:39
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 33097.28 | 714.53 | 714.53 |
Net Site Energy | 33097.28 | 714.53 | 714.53 |
Total Source Energy | 95530.49 | 2062.39 | 2062.39 |
Net Source Energy | 95530.49 | 2062.39 | 2062.39 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 46320.38 |
Net Conditioned Building Area | 46320.38 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 3610.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 1480.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 3933.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 696.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 14676.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 1934.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 2717.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 326.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 437.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3495.54 |
Humidification | 2435.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 905.84 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 848.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2280.17 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 28638.04 | 4459.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6681.55 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler | 0.00 | 3610.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 1480.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 3933.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 696.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 5334.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DataCenterPlugLoads | 9341.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 80.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 1848.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 5.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | General | 2717.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 326.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 437.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3495.54 |
Humidification | General | 2435.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 905.84 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2280.17 | |
Water Heater | 0.00 | 848.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 3610.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 1480.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 3933.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 696.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 14676.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 1934.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 2717.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 326.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 437.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3495.54 |
Humidification | Unassigned | 2435.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 905.84 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 0.00 | 848.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2280.17 |
Refrigeration | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 99.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 159.69 | 96.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.14 |
Other | 358.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 618.26 | 96.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.14 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 99.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 159.69 | 96.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.14 |
Other | 358.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 618.26 | 96.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.14 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 28638.043 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 28638.043 | 100.00 |
Total On-Site and Utility Electric Sources | 28638.043 | 100.00 |
Total Electricity End Uses | 28638.043 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 6681.55 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 6681.55 | 100.00 |
Total Water End Uses | 6681.55 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 133.17 |
Time Setpoint Not Met During Occupied Cooling | 247.83 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 5938.00 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2013
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICELARGE
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 6B
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_MT_GREATFALLS
| Environment |ZoneCoolingSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |ZoneHeatingSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |ZoneElectricSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |SpaceGainsMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |PeakSpaceGainsMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |SpaceGainComponentsAtCoolingPeakMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |ComfortReportSimple55Monthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |OccupantComfortDataSummaryMonthly
| DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 | BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 |ChillerReportMonthly
| COOLSYS1 CHILLER1 | COOLSYS1 CHILLER2 |TowerReportMonthly
| CENTRAL TOWER | TOWERWATERSYS COOLTOWER 1 | TOWERWATERSYS COOLTOWER 2 |BoilerReportMonthly
| HEATSYS1 BOILER | CENTRAL BOILER |DXReportMonthly
| VAV_BOT WITH REHEAT COOLING COIL | VAV_MID WITH REHEAT COOLING COIL | VAV_TOP WITH REHEAT COOLING COIL | CAV_BAS COOLING COIL | AIRLOOP DATACENTER BASEMENT COOLING COIL | AIRLOOP DATACENTER BOT COOLING COIL | AIRLOOP DATACENTER MID COOLING COIL | AIRLOOP DATACENTER TOP COOLING COIL |WindowReportMonthly
| PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW |WindowEnergyReportMonthly
| PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW |WindowZoneSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |WindowEnergyZoneSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWHSYS1 WATER HEATER |DaylightingReportMonthly
| PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_4_DAYLCTRL |CoilReportMonthly
| VAV_BOT WITH REHEAT HEATING COIL | CORE_BOTTOM VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | VAV_MID WITH REHEAT HEATING COIL | CORE_MID VAV BOX REHEAT COIL | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | VAV_TOP WITH REHEAT HEATING COIL | CORE_TOP VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | CAV_BAS HEATING COIL | AIRLOOP DATACENTER BASEMENT HEATING COIL | AIRLOOP DATACENTER BOT HEATING COIL | AIRLOOP DATACENTER MID HEATING COIL | AIRLOOP DATACENTER TOP HEATING COIL | AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | AIRLOOP DATACENTER BOT_SUPPHEATCOIL | AIRLOOP DATACENTER MID_SUPPHEATCOIL | AIRLOOP DATACENTER TOP_SUPPHEATCOIL | VAV_BOT WITH REHEAT COOLING COIL | VAV_MID WITH REHEAT COOLING COIL | VAV_TOP WITH REHEAT COOLING COIL | CAV_BAS COOLING COIL | AIRLOOP DATACENTER BASEMENT COOLING COIL | AIRLOOP DATACENTER BOT COOLING COIL | AIRLOOP DATACENTER MID COOLING COIL | AIRLOOP DATACENTER TOP COOLING COIL |PlantLoopDemandReportMonthly
| HEATSYS1 | COOLSYS1_SUPPLY | COOLSYS1_DEMAND | SINGLE WATER PLANT LOOP | SWHSYS1 | TOWERWATERSYS |FanReportMonthly
| CAV_BAS FAN | VAV_BOT WITH REHEAT FAN | VAV_MID WITH REHEAT FAN | VAV_TOP WITH REHEAT FAN | AIRLOOP DATACENTER BASEMENT SUPPLY FAN | AIRLOOP DATACENTER BOT SUPPLY FAN | AIRLOOP DATACENTER MID SUPPLY FAN | AIRLOOP DATACENTER TOP SUPPLY FAN |PumpReportMonthly
| HEATSYS1 PUMP | COOLSYS1 PUMP SECONDARY | COOLSYS1 CHILLER1 PUMP | COOLSYS1 CHILLER2 PUMP | PLANT CIRC PUMP | SWHSYS1 PUMP | TOWERWATERSYS PUMP |CondLoopDemandReportMonthly
| HEATSYS1 | COOLSYS1_SUPPLY | COOLSYS1_DEMAND | SINGLE WATER PLANT LOOP | SWHSYS1 | TOWERWATERSYS |ZoneTemperatureOscillationReportMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |AirLoopSystemEnergyAndWaterUseMonthly
| VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | CAV_BAS | AIRLOOP DATACENTER BASEMENT | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |AirLoopSystemComponentLoadsMonthly
| VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | CAV_BAS | AIRLOOP DATACENTER BASEMENT | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |AirLoopSystemComponentEnergyUseMonthly
| VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | CAV_BAS | AIRLOOP DATACENTER BASEMENT | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |MechanicalVentilationLoadsMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 08:43:39
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:43 |
RunPeriod | RUNPERIOD 1 |
Weather File | Great Falls Intl Arpt MT USA TMY3 WMO#=727750 |
Latitude [deg] | 47.47 |
Longitude [deg] | -111.4 |
Elevation [m] | 1117.00 |
Time Zone | -7.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 12183.89 | 3655.17 | 2436.78 | 3655.17 | 2436.78 |
Above Ground Wall Area [m2] | 11589.54 | 3476.86 | 2317.91 | 3476.86 | 2317.91 |
Window Opening Area [m2] | 4635.80 | 1390.74 | 927.16 | 1390.74 | 927.16 |
Gross Window-Wall Ratio [%] | 38.05 | 38.05 | 38.05 | 38.05 | 38.05 |
Above Ground Window-Wall Ratio [%] | 40.00 | 40.00 | 40.00 | 40.00 | 40.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 12183.89 | 3655.17 | 2436.78 | 3655.17 | 2436.78 |
Above Ground Wall Area [m2] | 11589.54 | 3476.86 | 2317.91 | 3476.86 | 2317.91 |
Window Opening Area [m2] | 4635.80 | 1390.74 | 927.16 | 1390.74 | 927.16 |
Gross Window-Wall Ratio [%] | 38.05 | 38.05 | 38.05 | 38.05 | 38.05 |
Above Ground Window-Wall Ratio [%] | 40.00 | 40.00 | 40.00 | 40.00 | 40.00 |
Total | |
Gross Roof Area [m2] | 3563.11 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
BASEMENT | 2779.43 | Yes | Yes | 6779.02 | 1.00 | 0.00 | 397.05 | 0.00 | 0.00 | 10.2732 | 18.58 | 4.8418 |
CORE_BOTTOM | 2496.12 | Yes | Yes | 6849.35 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.2732 | 18.58 | 8.0697 |
CORE_MID | 2496.12 | Yes | Yes | 6849.35 | 10.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.2732 | 18.58 | 8.0696 |
CORE_TOP | 2496.12 | Yes | Yes | 6849.35 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.2732 | 18.58 | 8.0696 |
PERIMETER_BOT_ZN_3 | 313.41 | Yes | Yes | 860.00 | 1.00 | 200.61 | 0.00 | 115.90 | 115.90 | 10.2732 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_2 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 77.26 | 77.26 | 10.2732 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_1 | 313.42 | Yes | Yes | 860.02 | 1.00 | 200.61 | 0.00 | 115.90 | 115.90 | 10.2732 | 18.58 | 8.0699 |
PERIMETER_BOT_ZN_4 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 77.26 | 77.26 | 10.2732 | 18.58 | 8.0699 |
PERIMETER_MID_ZN_3 | 313.41 | Yes | Yes | 860.00 | 10.00 | 200.61 | 0.00 | 115.90 | 115.90 | 10.2732 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_2 | 201.98 | Yes | Yes | 554.22 | 10.00 | 133.74 | 0.00 | 77.26 | 77.26 | 10.2732 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_1 | 313.42 | Yes | Yes | 860.02 | 10.00 | 200.61 | 0.00 | 115.90 | 115.90 | 10.2732 | 18.58 | 8.0699 |
PERIMETER_MID_ZN_4 | 201.98 | Yes | Yes | 554.22 | 10.00 | 133.74 | 0.00 | 77.26 | 77.26 | 10.2732 | 18.58 | 8.0699 |
PERIMETER_TOP_ZN_3 | 313.41 | Yes | Yes | 860.00 | 1.00 | 200.61 | 0.00 | 115.90 | 115.90 | 10.2732 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_2 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 77.26 | 77.26 | 10.2732 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_1 | 313.42 | Yes | Yes | 860.02 | 1.00 | 200.61 | 0.00 | 115.90 | 115.90 | 10.2732 | 18.58 | 8.0699 |
PERIMETER_TOP_ZN_4 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 77.26 | 77.26 | 10.2732 | 18.58 | 8.0699 |
GROUNDFLOOR_PLENUM | 3563.11 | Yes | No | 4344.14 | 1.00 | 297.11 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
MIDFLOOR_PLENUM | 3563.11 | Yes | No | 4344.14 | 10.00 | 297.11 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
TOPFLOOR_PLENUM | 3563.11 | Yes | No | 4344.14 | 1.00 | 297.11 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
DATACENTER_BOT_ZN_6 | 36.20 | Yes | Yes | 99.34 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.8735 | 18.58 | 215.2992 |
DATACENTER_MID_ZN_6 | 36.20 | Yes | Yes | 99.34 | 10.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.8735 | 18.58 | 215.2992 |
DATACENTER_TOP_ZN_6 | 36.20 | Yes | Yes | 99.34 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.8735 | 18.58 | 215.2992 |
DATACENTER_BASEMENT_ZN_6 | 783.68 | Yes | Yes | 1911.37 | 1.00 | 0.00 | 197.31 | 0.00 | 0.00 | 10.2732 | 18.58 | 484.4232 |
Total | 46320.38 | 126016.35 | 8024.24 | 594.36 | 4635.80 | 4635.80 | 10.3445 | 18.58 | 17.8789 | |||
Conditioned Total | 46320.38 | 126016.35 | 8024.24 | 594.36 | 4635.80 | 4635.80 | 10.3445 | 18.58 | 17.8789 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 42757.27 | 52129.67 | 3565.29 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
BASEMENT | 2779.43 | Yes | Yes | 1.00 | BASEMENT | GENERAL | BASEMENT | 10.2732 | 18.58 | 4.8418 | |
CORE_BOTTOM | 2496.12 | Yes | Yes | 1.00 | CORE_BOTTOM | GENERAL | CORE_BOTTOM | 10.2732 | 18.58 | 8.0697 | |
CORE_MID | 2496.12 | Yes | Yes | 10.00 | CORE_MID | GENERAL | CORE_MID | 10.2732 | 18.58 | 8.0696 | |
CORE_TOP | 2496.12 | Yes | Yes | 1.00 | CORE_TOP | GENERAL | CORE_TOP | 10.2732 | 18.58 | 8.0696 | |
PERIMETER_BOT_ZN_3 | 313.41 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_3 | GENERAL | PERIMETER_BOT_ZN_3 | 10.2732 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_2 | 201.98 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_2 | GENERAL | PERIMETER_BOT_ZN_2 | 10.2732 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_1 | 313.42 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_1 | GENERAL | PERIMETER_BOT_ZN_1 | 10.2732 | 18.58 | 8.0699 | |
PERIMETER_BOT_ZN_4 | 201.98 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_4 | GENERAL | PERIMETER_BOT_ZN_4 | 10.2732 | 18.58 | 8.0699 | |
PERIMETER_MID_ZN_3 | 313.41 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_3 | GENERAL | PERIMETER_MID_ZN_3 | 10.2732 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_2 | 201.98 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_2 | GENERAL | PERIMETER_MID_ZN_2 | 10.2732 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_1 | 313.42 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_1 | GENERAL | PERIMETER_MID_ZN_1 | 10.2732 | 18.58 | 8.0699 | |
PERIMETER_MID_ZN_4 | 201.98 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_4 | GENERAL | PERIMETER_MID_ZN_4 | 10.2732 | 18.58 | 8.0699 | |
PERIMETER_TOP_ZN_3 | 313.41 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_3 | GENERAL | PERIMETER_TOP_ZN_3 | 10.2732 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_2 | 201.98 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_2 | GENERAL | PERIMETER_TOP_ZN_2 | 10.2732 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_1 | 313.42 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_1 | GENERAL | PERIMETER_TOP_ZN_1 | 10.2732 | 18.58 | 8.0699 | |
PERIMETER_TOP_ZN_4 | 201.98 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_4 | GENERAL | PERIMETER_TOP_ZN_4 | 10.2732 | 18.58 | 8.0699 | |
GROUNDFLOOR_PLENUM | 3563.11 | Yes | No | 1.00 | GROUNDFLOOR_PLENUM | GENERAL | GROUNDFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
MIDFLOOR_PLENUM | 3563.11 | Yes | No | 10.00 | MIDFLOOR_PLENUM | GENERAL | MIDFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
TOPFLOOR_PLENUM | 3563.11 | Yes | No | 1.00 | TOPFLOOR_PLENUM | GENERAL | TOPFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
DATACENTER_BOT_ZN_6 | 36.20 | Yes | Yes | 1.00 | DATACENTER_BOT_ZN_6 | GENERAL | DATACENTER_BOT_ZN_6 | 17.8735 | 18.58 | 215.2992 | |
DATACENTER_MID_ZN_6 | 36.20 | Yes | Yes | 10.00 | DATACENTER_MID_ZN_6 | GENERAL | DATACENTER_MID_ZN_6 | 17.8735 | 18.58 | 215.2992 | |
DATACENTER_TOP_ZN_6 | 36.20 | Yes | Yes | 1.00 | DATACENTER_TOP_ZN_6 | GENERAL | DATACENTER_TOP_ZN_6 | 17.8735 | 18.58 | 215.2992 | |
DATACENTER_BASEMENT_ZN_6 | 783.68 | Yes | Yes | 1.00 | DATACENTER_BASEMENT_ZN_6 | GENERAL | DATACENTER_BASEMENT_ZN_6 | 10.2732 | 18.58 | 484.4232 | |
Total | 46320.38 | 10.3445 | 9.29 | 17.8789 | |||||||
Conditioned Total | 46320.38 | 10.3445 | 9.29 | 17.8789 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 42757.27 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 46320.38 | 46320.38 | 0.00 | 42757.27 | 3.1788 | 60.38 | 10.8345 |
Total | 46320.38 | 46320.38 | 0.00 | 42757.27 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:43:39
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 07-AUG-15:39 | 09-JAN-07:10 | - | - | - | - | - | - | - | - | - | - | 17-JUL-15:00 |
Heating | 0.00 | 2431734.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 446956.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 332294.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 778371.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 84450.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 351775.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 47934.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 83553.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 100000.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 33069.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 2225335.88 | 2464803.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler | 0.00 | 2431734.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 446956.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 332294.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 305206.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DataCenterPlugLoads | 473165.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 5015.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 79171.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 263.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | General | 351775.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 47934.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 83553.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 100000.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Water Heater | 0.00 | 33069.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:43:39
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 3914.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 4688.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 12457.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 2205.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 46480.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 6127.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 8607.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 1033.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 1385.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 7711.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 919.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 90696.68 | 4833.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 84.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 101.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 268.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 47.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1003.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 132.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 185.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 22.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 29.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 166.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 19.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1958.03 | 104.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 84.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 101.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 268.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 47.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1003.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 132.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 185.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 22.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 29.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 166.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 19.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1958.03 | 104.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:43:39
AirTerminal:SingleDuct:ConstantVolume:NoReheatDesign Size Maximum Air Flow Rate [m3/s] | |
BASEMENT DIRECT AIR | 6.82 |
DATACENTER_BOT_ZN_6 DIRECT AIR | 0.585375 |
DATACENTER_MID_ZN_6 DIRECT AIR | 5.63 |
DATACENTER_TOP_ZN_6 DIRECT AIR | 0.572441 |
DATACENTER_BASEMENT_ZN_6 DIRECT AIR | 24.54 |
Design Size Maximum Air Flow Rate [m3/s] | Design Size Constant Minimum Air Flow Fraction | User-Specified Constant Minimum Air Flow Fraction | Design Size Minimum Air Flow Rate [m3/s] | Design Size Maximum Flow Fraction during Reheat [] | User-Specified Maximum Flow Fraction during Reheat [] | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | Design Size Maximum Reheat Water Flow Rate [m3/s] | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | |
CORE_BOTTOM VAV BOX COMPONENT | 7.06 | 0.269249 | 0.288000 | 2.03 | 0.717997 | 0.500000 | 0.001415 | 0.000226 | 2.03 | 12.80 | 0.008000 |
CORE_MID VAV BOX COMPONENT | 66.53 | 0.285907 | 0.299000 | 19.89 | 0.762419 | 0.500000 | 0.001333 | 0.004509 | 19.89 | 12.80 | 0.008000 |
CORE_TOP VAV BOX COMPONENT | 6.44 | 0.295559 | 0.320000 | 2.06 | 0.788158 | 0.500000 | 0.001289 | 0.000977 | 3.80 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | 1.20 | 0.199528 | 0.213000 | 0.254946 | 0.532075 | 0.500000 | 0.001910 | 0.000189 | 0.737784 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | 1.62 | 0.094848 | 0.200000 | 0.324529 | 0.300000 | 0.500000 | 0.004017 | 0.000129 | 0.504891 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | 2.01 | 0.118919 | 0.200000 | 0.401663 | 0.317116 | 0.500000 | 0.003204 | 0.000207 | 0.808359 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | 1.99 | 0.077342 | 0.200000 | 0.397984 | 0.300000 | 0.500000 | 0.004926 | 0.000110 | 0.429743 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_3 VAV BOX COMPONENT | 11.40 | 0.209513 | 0.219000 | 2.50 | 0.558701 | 0.500000 | 0.001819 | 0.002668 | 10.41 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_2 VAV BOX COMPONENT | 17.31 | 0.088910 | 0.200000 | 3.46 | 0.300000 | 0.500000 | 0.004285 | 0.001771 | 6.91 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_1 VAV BOX COMPONENT | 20.52 | 0.116409 | 0.200000 | 4.10 | 0.310424 | 0.500000 | 0.003273 | 0.002710 | 10.57 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_4 VAV BOX COMPONENT | 18.72 | 0.082227 | 0.200000 | 3.74 | 0.300000 | 0.500000 | 0.004634 | 0.001748 | 6.82 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | 1.31 | 0.181678 | 0.202000 | 0.265534 | 0.484475 | 0.500000 | 0.002097 | 0.000337 | 1.31 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | 1.73 | 0.088910 | 0.200000 | 0.346205 | 0.300000 | 0.500000 | 0.004285 | 0.000222 | 0.867809 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | 2.19 | 0.109258 | 0.200000 | 0.437176 | 0.300000 | 0.500000 | 0.003487 | 0.000341 | 1.33 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | 1.97 | 0.078291 | 0.200000 | 0.393162 | 0.300000 | 0.500000 | 0.004866 | 0.000223 | 0.868347 | 12.80 | 0.008000 |
Design Size Rated Capacity [W] | Design Size Maximum Water Flow Rate [m3/s] | Design Size U-Factor Times Area Value [W/K] | |
CORE_BOTTOM VAV BOX REHEAT COIL | 25791.51 | 0.000226 | 543.51 |
CORE_MID VAV BOX REHEAT COIL | 515371.91 | 0.004509 | 12910.42 |
CORE_TOP VAV BOX REHEAT COIL | 111653.25 | 0.000977 | 2946.07 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | 21629.82 | 0.000189 | 570.40 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | 14800.43 | 0.000129 | 390.28 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | 23695.44 | 0.000207 | 624.83 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | 12601.41 | 0.000110 | 332.34 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | 305019.35 | 0.002668 | 8041.46 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | 202437.02 | 0.001771 | 5336.91 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | 309716.07 | 0.002710 | 8165.21 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | 199861.14 | 0.001748 | 5269.02 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | 38505.23 | 0.000337 | 1015.02 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | 25419.30 | 0.000222 | 670.06 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | 39023.78 | 0.000341 | 1028.69 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | 25434.92 | 0.000223 | 670.47 |
VAV_BOT WITH REHEAT HEATING COIL | 101691.05 | 0.000890 | 1578.77 |
VAV_MID WITH REHEAT HEATING COIL | 1044136.00 | 0.009135 | 15812.23 |
VAV_TOP WITH REHEAT HEATING COIL | 102308.46 | 0.000895 | 1597.68 |
CAV_BAS HEATING COIL | 323708.58 | 0.002832 | 6941.25 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT | 6.94 | 3.41 | 13.88 | 3.56 | 11.66 | 11.66 | 0.300000 | 0.305310 | 11.66 |
VAV_MID WITH REHEAT | 67.23 | 33.70 | 134.47 | 51.18 | 107.83 | 107.83 | 0.300000 | 0.474632 | 107.83 |
VAV_TOP WITH REHEAT | 6.82 | 3.50 | 13.63 | 8.19 | 12.30 | 12.30 | 0.300000 | 0.665542 | 12.30 |
CAV_BAS | 6.82 | 6.82 | 6.82 | 6.82 | 6.82 | 6.82 | 1.00 | 1.00 | 6.82 |
AIRLOOP DATACENTER BASEMENT | 24.54 | 24.54 | 24.54 | 24.54 | 24.54 | 24.54 | 1.00 | 0.999996 | 24.54 |
AIRLOOP DATACENTER BOT | 0.585375 | 0.585375 | 0.585375 | 0.585375 | 0.585375 | 0.585375 | 1.00 | 1.00 | 0.585375 |
AIRLOOP DATACENTER MID | 5.63 | 5.63 | 5.63 | 5.63 | 5.63 | 5.63 | 1.00 | 1.00 | 5.63 |
AIRLOOP DATACENTER TOP | 0.572441 | 0.572441 | 0.572441 | 0.572441 | 0.572441 | 0.572441 | 1.00 | 1.00 | 0.572441 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT_OA_CONTROLLER | 11.66 | |
VAV_MID WITH REHEAT_OA_CONTROLLER | 107.83 | |
VAV_TOP WITH REHEAT_OA_CONTROLLER | 12.30 | |
CAV_BAS_OA_CONTROLLER | 6.82 | 1.20 |
AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER | 24.54 | 0.338393 |
AIRLOOP DATACENTER BOT_OA_CONTROLLER | 0.585375 | 0.015632 |
AIRLOOP DATACENTER MID_OA_CONTROLLER | 5.63 | 0.156323 |
AIRLOOP DATACENTER TOP_OA_CONTROLLER | 0.572441 | 0.015632 |
Design Size Design Inlet Air Temperature [C] | Design Size Design Inlet Water Temperature [C] | Design Size Design Outlet Air Temperature [C] | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | Design Size Design Coil Load [W] | Design Size Design Water Flow Rate [m3/s] | Design Size Design Air Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT COOLING COIL | 26.05 | 6.67 | 10.68 | 0.007083 | 0.007000 | 194585.29 | 0.008278 | 11.66 |
VAV_MID WITH REHEAT COOLING COIL | 26.21 | 6.67 | 10.68 | 0.007077 | 0.007000 | 1817578.77 | 0.077324 | 107.83 |
VAV_TOP WITH REHEAT COOLING COIL | 25.95 | 6.67 | 10.68 | 0.007073 | 0.007000 | 203672.51 | 0.008665 | 12.30 |
CAV_BAS COOLING COIL | 25.70 | 6.67 | 11.23 | 0.007235 | 0.007000 | 110073.14 | 0.004683 | 6.82 |
Design Size Maximum Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT FAN | 11.66 |
VAV_MID WITH REHEAT FAN | 107.83 |
VAV_TOP WITH REHEAT FAN | 12.30 |
Maximum Actuated Flow [m3/s] | Controller Convergence Tolerance | |
VAV_BOT WITH REHEAT_COOLC_CONTROLLER | 0.008278 | 0.000058 |
VAV_BOT WITH REHEAT_HEATC_CONTROLLER | 0.000890 | |
VAV_MID WITH REHEAT_COOLC_CONTROLLER | 0.077324 | 0.000006 |
VAV_MID WITH REHEAT_HEATC_CONTROLLER | 0.009135 | |
VAV_TOP WITH REHEAT_COOLC_CONTROLLER | 0.008665 | 0.000055 |
VAV_TOP WITH REHEAT_HEATC_CONTROLLER | 0.000895 | |
CAV_BAS_COOLC_CONTROLLER | 0.004683 | 0.000102 |
CAV_BAS_HEATC_CONTROLLER | 0.002832 |
Design Size Maximum Flow Rate [m3/s] | |
CAV_BAS FAN | 6.82 |
Design Size Rated Air Flow Rate [m3/s] | Design Size Rated Total Cooling Capacity [W] | Design Size Rated Sensible Cooling Capacity [W] | Design Size Rated Water Flow Rate [m3/s] | |
AIRLOOP DATACENTER BASEMENT COOLING COIL | 24.54 | 466437.89 | 262502.94 | 0.011423 |
AIRLOOP DATACENTER BOT COOLING COIL | 0.585375 | 10807.09 | 6147.89 | 0.000265 |
AIRLOOP DATACENTER MID COOLING COIL | 5.63 | 103961.65 | 59130.97 | 0.002546 |
AIRLOOP DATACENTER TOP COOLING COIL | 0.572441 | 10570.02 | 6012.39 | 0.000259 |
Supply Air Flow Rate [m3/s] | Supply Air Flow Rate During Heating Operation [m3/s] | Supply Air Flow Rate During Cooling Operation [m3/s] | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | Nominal Heating Capacity [W] | Nominal Cooling Capacity [W] | Supplemental Heating Coil Nominal Capacity [W] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | 24.54 | 24.54 | 24.54 | 24.54 | 466437.89 | 466437.89 | 24207.99 | 1.00 |
AIRLOOP DATACENTER BOT DXAC HEAT PUMP | 0.585375 | 0.585375 | 0.585375 | 0.585375 | 10807.09 | 10807.09 | 1118.31 | 1.00 |
AIRLOOP DATACENTER MID DXAC HEAT PUMP | 5.63 | 5.63 | 5.63 | 5.63 | 103961.65 | 103961.65 | 11183.09 | 1.00 |
AIRLOOP DATACENTER TOP DXAC HEAT PUMP | 0.572441 | 0.572441 | 0.572441 | 0.572441 | 10570.02 | 10570.02 | 1118.31 | 1.00 |
Design Size Maximum Flow Rate [m3/s] | |
AIRLOOP DATACENTER BASEMENT SUPPLY FAN | 24.54 |
AIRLOOP DATACENTER BOT SUPPLY FAN | 0.585375 |
AIRLOOP DATACENTER MID SUPPLY FAN | 5.63 |
AIRLOOP DATACENTER TOP SUPPLY FAN | 0.572441 |
Design Size Rated Air Flow Rate [m3/s] | Design Size Rated Heating Capacity [W] | Design Size Rated Water Flow Rate [m3/s] | |
AIRLOOP DATACENTER BASEMENT HEATING COIL | 24.54 | 466437.89 | 0.011423 |
AIRLOOP DATACENTER BOT HEATING COIL | 0.585375 | 10807.09 | 0.000265 |
AIRLOOP DATACENTER MID HEATING COIL | 5.63 | 103961.65 | 0.002546 |
AIRLOOP DATACENTER TOP HEATING COIL | 0.572441 | 10570.02 | 0.000259 |
Design Size Nominal Capacity [W] | |
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | 24207.99 |
AIRLOOP DATACENTER BOT_SUPPHEATCOIL | 1118.31 |
AIRLOOP DATACENTER MID_SUPPHEATCOIL | 11183.09 |
AIRLOOP DATACENTER TOP_SUPPHEATCOIL | 1118.31 |
Design Size Nominal Capacity Volume [m3/s] | User-Specified Nominal Capacity Volume [m3/s] | Design Size Rated Power [W] | User-Specified Rated Power [W] | |
DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | 0.000191 | 0.000037 | 96450.70 | 100000.00 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | Design Minimum Flow Rate [m3/s] | |
COOLSYS1 PUMP SECONDARY | 0.098950 | 16155.44 | |
HEATSYS1 PUMP | 0.030119 | 9070.57 | 0.000000 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
COOLSYS1_DEMAND | 0.098950 | 11.87 |
HEATSYS1 | 0.030119 | 3.61 |
COOLSYS1_SUPPLY | 0.098950 | 11.87 |
SINGLE WATER PLANT LOOP | 0.014493 | 1.74 |
SWHSYS1 | 0.000440 | 0.052800 |
Loop Supply Side Design Fluid Flow Rate [m3/s] | Loop Demand Side Design Fluid Flow Rate [m3/s] | Heat Exchanger U-Factor Times Area Value [W/C] | Loop-to-loop Temperature Difference Used to Size Heat Exchanger U-Factor Times Area Value [C] | |
BYPASS HEAT EXCHANGER | 0.098950 | 0.098950 | 415341.02 | 5.60 |
Design Size Nominal Capacity [W] | User-Specified Nominal Capacity [W] | Design Size Design Water Flow Rate [m3/s] | |
HEATSYS1 BOILER | 3442804.66 | 3442804.66 | 0.030119 |
CENTRAL BOILER | 596969.72 | 584202.86 | 0.014493 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
COOLSYS1 CHILLER1 PUMP | 0.049475 | 5592.48 |
COOLSYS1 CHILLER2 PUMP | 0.049475 | 5592.48 |
PLANT CIRC PUMP | 0.014493 | 3696.33 |
SWHSYS1 PUMP | 0.000440 | 56.21 |
Design Size Reference Chilled Water Flow Rate [m3/s] | User-Specified Reference Chilled Water Flow Rate [m3/s] | Design Size Reference Capacity [W] | User-Specified Reference Capacity [W] | Design Size Reference Condenser Water Flow Rate [m3/s] | |
COOLSYS1 CHILLER1 | 0.098950 | 0.049851 | 1174674.23 | 1180245.77 | 0.058406 |
COOLSYS1 CHILLER2 | 0.098950 | 0.049851 | 1174674.23 | 1180245.77 | 0.058406 |
Design Water Flow Rate [m3/s] | Air Flow Rate at High Fan Speed [m3/s] | Fluid cooler UA value at high fan speed based on nominal capacity input [W/K] | Air Flow Rate at Low Fan Speed [m3/s] | Fan Power at Low Fan Speed [W] | U-factor Times Area Value at Low Fan Speed [W/C] | |
CENTRAL TOWER | 0.014493 | 139666.47 | 55299.27 | 69833.23 | 7879.72 | 20993.04 |
Use Side Design Flow Rate [m3/s] | |
SWHSYS1 WATER HEATER | 0.000440 |
Maximum Loop Flow Rate [m3/s] | Condenser Loop Volume [m3] | |
TOWERWATERSYS | 0.116812 | 14.02 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
TOWERWATERSYS PUMP | 0.116812 | 28920.06 |
Design Air Flow Rate [m3/s] | Nominal Capacity [W] | Air Flow Rate in free convection regime [m3/s] | Tower capacity in free convection regime at design conditions [W] | |
TOWERWATERSYS COOLTOWER 1 | 51.62 | 1402076.60 | 10.32 | 175259.57 |
TOWERWATERSYS COOLTOWER 2 | 51.62 | 1402076.60 | 10.32 | 175259.57 |
Design Water Flow Rate [m3/s] Equipment # 47 | |
WSHPPLANT OPERATION SCHEME | 0.060665 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:43:39
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
PERIMETER_BOT_ZN_3_WALL_NORTH | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | |
PERIMETER_BOT_ZN_2_WALL_EAST | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | |
PERIMETER_BOT_ZN_1_WALL_SOUTH | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | |
PERIMETER_BOT_ZN_4_WALL_WEST | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | |
PERIMETER_MID_ZN_3_WALL_NORTH | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_MID_ZN_2_WALL_EAST | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_MID_ZN_1_WALL_SOUTH | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_MID_ZN_4_WALL_WEST | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | |
PERIMETER_TOP_ZN_3_WALL_NORTH | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_TOP_ZN_2_WALL_EAST | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_TOP_ZN_1_WALL_SOUTH | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_TOP_ZN_4_WALL_WEST | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 08:43:39
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 08:43:39
VersionVersion ID | |
1 | 22.1.0 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 8.60 | 2.80 | -4.10 | -8.80 | -2.20 | 0.30 | 6.70 | 10.10 | 16.50 | 20.60 | 19.20 | 14.70 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Great Falls Intl Arpt MT USA TMY3 WMO#=727750 | 47.47 | -111.38 | -7.00 | 1117.00 | 88606 | 1.0531 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 7.03 | 29.40 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | OfficeLarge | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 23 | 221 | 36 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | BASEMENT | 0.0 | 0.00 | 0.00 | 0.00 | 44.59 | 24.37 | -1.22 | 1 | 1 | 1 | 16.08 | 73.11 | 0.00 | 48.74 | -2.44 | 0.00 | 2.44 | 6779.02 | TARP | TARP | 2779.43 | 0.00 | 0.00 | 0.00 | 9 | 0 | 0 | Yes |
2 | CORE_BOTTOM | 0.0 | 0.00 | 0.00 | 0.00 | 37.01 | 24.37 | 1.37 | 1 | 1 | 1 | 5.49 | 68.53 | 4.57 | 44.17 | 0.00 | 2.74 | 2.74 | 6849.35 | TARP | TARP | 2496.12 | 0.00 | 0.00 | 0.00 | 7 | 0 | 0 | Yes |
3 | CORE_MID | 0.0 | 0.00 | 0.00 | 0.00 | 37.01 | 24.37 | 18.14 | 1 | 10 | 1 | 5.49 | 68.53 | 4.57 | 44.17 | 16.77 | 19.51 | 2.74 | 6849.35 | TARP | TARP | 2496.12 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
4 | CORE_TOP | 0.0 | 0.00 | 0.00 | 0.00 | 37.01 | 24.37 | 34.91 | 1 | 1 | 1 | 5.49 | 68.53 | 4.57 | 44.17 | 33.54 | 36.28 | 2.74 | 6849.35 | TARP | TARP | 2496.12 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
5 | PERIMETER_BOT_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 46.54 | 1.37 | 1 | 1 | 1 | 0.00 | 73.11 | 44.17 | 48.74 | 0.00 | 2.74 | 2.74 | 860.00 | TARP | TARP | 313.41 | 200.61 | 76.91 | 115.90 | 8 | 9 | 0 | Yes |
6 | PERIMETER_BOT_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 70.95 | 24.37 | 1.37 | 1 | 1 | 1 | 68.53 | 73.11 | 0.00 | 48.74 | 0.00 | 2.74 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 52.57 | 77.26 | 6 | 5 | 0 | Yes |
7 | PERIMETER_BOT_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 2.20 | 1.37 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 4.57 | 0.00 | 2.74 | 2.74 | 860.02 | TARP | TARP | 313.42 | 200.61 | 76.91 | 115.90 | 8 | 9 | 0 | Yes |
8 | PERIMETER_BOT_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.16 | 24.37 | 1.37 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 48.74 | 0.00 | 2.74 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 52.57 | 77.26 | 6 | 5 | 0 | Yes |
9 | PERIMETER_MID_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 46.54 | 18.14 | 1 | 10 | 1 | 0.00 | 73.11 | 44.17 | 48.74 | 16.77 | 19.51 | 2.74 | 860.00 | TARP | TARP | 313.41 | 200.61 | 84.71 | 115.90 | 7 | 1 | 0 | Yes |
10 | PERIMETER_MID_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 70.95 | 24.37 | 18.14 | 1 | 10 | 1 | 68.53 | 73.11 | 0.00 | 48.74 | 16.77 | 19.51 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 56.47 | 77.26 | 6 | 1 | 0 | Yes |
11 | PERIMETER_MID_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 2.20 | 18.14 | 1 | 10 | 1 | 0.00 | 73.11 | 0.00 | 4.57 | 16.77 | 19.51 | 2.74 | 860.02 | TARP | TARP | 313.42 | 200.61 | 84.71 | 115.90 | 7 | 1 | 0 | Yes |
12 | PERIMETER_MID_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.16 | 24.37 | 18.14 | 1 | 10 | 1 | 0.00 | 4.57 | 0.00 | 48.74 | 16.77 | 19.51 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 56.47 | 77.26 | 6 | 1 | 0 | Yes |
13 | PERIMETER_TOP_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 46.54 | 34.91 | 1 | 1 | 1 | 0.00 | 73.11 | 44.17 | 48.74 | 33.54 | 36.28 | 2.74 | 860.00 | TARP | TARP | 313.41 | 200.61 | 84.71 | 115.90 | 7 | 1 | 0 | Yes |
14 | PERIMETER_TOP_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 70.95 | 24.37 | 34.91 | 1 | 1 | 1 | 68.53 | 73.11 | 0.00 | 48.74 | 33.54 | 36.28 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 56.47 | 77.26 | 6 | 1 | 0 | Yes |
15 | PERIMETER_TOP_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 2.20 | 34.91 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 4.57 | 33.54 | 36.28 | 2.74 | 860.02 | TARP | TARP | 313.42 | 200.61 | 84.71 | 115.90 | 7 | 1 | 0 | Yes |
16 | PERIMETER_TOP_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.16 | 24.37 | 34.91 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 48.74 | 33.54 | 36.28 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 56.47 | 77.26 | 6 | 1 | 0 | Yes |
17 | GROUNDFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 24.37 | 3.35 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 48.74 | 2.74 | 3.96 | 1.22 | 4344.14 | TARP | TARP | 3563.11 | 297.11 | 297.11 | 0.00 | 11 | 0 | 0 | No |
18 | MIDFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 24.37 | 20.12 | 1 | 10 | 1 | 0.00 | 73.11 | 0.00 | 48.74 | 19.51 | 20.73 | 1.22 | 4344.14 | TARP | TARP | 3563.11 | 297.11 | 297.11 | 0.00 | 11 | 0 | 0 | No |
19 | TOPFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 24.37 | 36.89 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 48.74 | 36.28 | 37.50 | 1.22 | 4344.14 | TARP | TARP | 3563.11 | 297.11 | 297.11 | 0.00 | 11 | 0 | 0 | No |
20 | DATACENTER_BOT_ZN_6 | 0.0 | 5.49 | 44.17 | 0.00 | 5.03 | 24.37 | 1.37 | 1 | 1 | 1 | 4.57 | 5.49 | 4.57 | 44.17 | 0.00 | 2.74 | 2.74 | 99.34 | TARP | TARP | 36.20 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
21 | DATACENTER_MID_ZN_6 | 0.0 | 4.57 | 4.57 | 16.77 | 5.03 | 24.37 | 18.14 | 1 | 10 | 1 | 4.57 | 5.49 | 4.57 | 44.17 | 16.77 | 19.51 | 2.74 | 99.34 | TARP | TARP | 36.20 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
22 | DATACENTER_TOP_ZN_6 | 0.0 | 4.57 | 4.57 | 33.54 | 5.03 | 24.37 | 34.91 | 1 | 1 | 1 | 4.57 | 5.49 | 4.57 | 44.17 | 33.54 | 36.28 | 2.74 | 99.34 | TARP | TARP | 36.20 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
23 | DATACENTER_BASEMENT_ZN_6 | 0.0 | 16.08 | 0.00 | -2.44 | 8.04 | 24.37 | -1.22 | 1 | 1 | 1 | 0.00 | 16.08 | 0.00 | 48.74 | -2.44 | 0.00 | 2.44 | 1911.37 | TARP | TARP | 783.68 | 0.00 | 0.00 | 0.00 | 10 | 0 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | BASEMENT | 2779.43 | 149.6 | 18.579 | 5.382E-002 | 10.273 | 4.842 | 0.000 | 0.000 | 0.000 | 0.000 | 15.115 | No |
2 | CORE_BOTTOM | 2496.12 | 134.4 | 18.579 | 5.382E-002 | 10.273 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 18.343 | No |
3 | CORE_MID | 2496.12 | 134.4 | 18.579 | 5.382E-002 | 10.273 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 18.343 | No |
4 | CORE_TOP | 2496.12 | 134.4 | 18.579 | 5.382E-002 | 10.273 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 18.343 | No |
5 | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 18.579 | 5.382E-002 | 10.273 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 18.343 | No |
6 | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 10.273 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 18.343 | No |
7 | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 18.579 | 5.382E-002 | 10.273 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 18.343 | No |
8 | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 10.273 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 18.343 | No |
9 | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 18.579 | 5.382E-002 | 10.273 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 18.343 | No |
10 | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 10.273 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 18.343 | No |
11 | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 18.579 | 5.382E-002 | 10.273 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 18.343 | No |
12 | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 10.273 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 18.343 | No |
13 | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 18.579 | 5.382E-002 | 10.273 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 18.343 | No |
14 | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 10.273 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 18.343 | No |
15 | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 18.579 | 5.382E-002 | 10.273 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 18.343 | No |
16 | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 10.273 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 18.343 | No |
17 | GROUNDFLOOR_PLENUM | 3563.11 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
18 | MIDFLOOR_PLENUM | 3563.11 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
19 | TOPFLOOR_PLENUM | 3563.11 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
20 | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 18.579 | 5.382E-002 | 17.873 | 215.299 | 0.000 | 0.000 | 0.000 | 0.000 | 233.173 | No |
21 | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 18.579 | 5.382E-002 | 17.873 | 215.299 | 0.000 | 0.000 | 0.000 | 0.000 | 233.173 | No |
22 | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 18.579 | 5.382E-002 | 17.873 | 215.299 | 0.000 | 0.000 | 0.000 | 0.000 | 233.173 | No |
23 | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 18.579 | 5.382E-002 | 10.273 | 484.423 | 0.000 | 0.000 | 0.000 | 0.000 | 494.696 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | DATACENTER_BOT_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 1.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | DATACENTER_MID_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 1.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
3 | DATACENTER_TOP_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 1.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
4 | DATACENTER_BASEMENT_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 42.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 42 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
5 | BASEMENT | BLDG_OCC_SCH_WO_SB | BASEMENT | 2779.43 | 149.6 | 149.6 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 150 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
6 | CORE_BOTTOM | BLDG_OCC_SCH_WO_SB | CORE_BOTTOM | 2496.12 | 134.4 | 134.4 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 134 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
7 | CORE_MID | BLDG_OCC_SCH_WO_SB | CORE_MID | 2496.12 | 134.4 | 134.4 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 134 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
8 | CORE_TOP | BLDG_OCC_SCH_WO_SB | CORE_TOP | 2496.12 | 134.4 | 134.4 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 134 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
9 | PERIMETER_BOT_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
10 | PERIMETER_BOT_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
11 | PERIMETER_BOT_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
12 | PERIMETER_BOT_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
13 | PERIMETER_MID_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
14 | PERIMETER_MID_ZN_2 | BLDG_OCC_SCH_W_SB | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
15 | PERIMETER_MID_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
16 | PERIMETER_MID_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
17 | PERIMETER_TOP_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
18 | PERIMETER_TOP_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
19 | PERIMETER_TOP_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
20 | PERIMETER_TOP_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | BASEMENT_LIGHTS | LTG_SCH_OFFICE | BASEMENT | 2779.43 | 149.6 | 28553.717 | 10.273 | 190.864 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 28553.717 |
2 | CORE_BOTTOM_LIGHTS | LTG_SCH_OFFICE | CORE_BOTTOM | 2496.12 | 134.4 | 25643.245 | 10.273 | 190.864 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 25643.245 |
3 | CORE_MID_LIGHTS | LTG_SCH_OFFICE | CORE_MID | 2496.12 | 134.4 | 25643.245 | 10.273 | 190.864 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 25643.245 |
4 | CORE_TOP_LIGHTS | LTG_SCH_OFFICE | CORE_TOP | 2496.12 | 134.4 | 25643.245 | 10.273 | 190.864 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 25643.245 |
5 | PERIMETER_BOT_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 3219.765 | 10.273 | 190.864 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3219.765 |
6 | PERIMETER_BOT_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 2074.939 | 10.273 | 190.864 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2074.939 |
7 | PERIMETER_BOT_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 3219.836 | 10.273 | 190.864 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3219.836 |
8 | PERIMETER_BOT_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 2074.939 | 10.273 | 190.864 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2074.939 |
9 | PERIMETER_MID_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 3219.765 | 10.273 | 190.864 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3219.765 |
10 | PERIMETER_MID_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 2074.939 | 10.273 | 190.864 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2074.939 |
11 | PERIMETER_MID_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 3219.836 | 10.273 | 190.864 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3219.836 |
12 | PERIMETER_MID_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 2074.939 | 10.273 | 190.864 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2074.939 |
13 | PERIMETER_TOP_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 3219.765 | 10.273 | 190.864 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3219.765 |
14 | PERIMETER_TOP_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 2074.939 | 10.273 | 190.864 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2074.939 |
15 | PERIMETER_TOP_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 3219.836 | 10.273 | 190.864 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3219.836 |
16 | PERIMETER_TOP_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 2074.939 | 10.273 | 190.864 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2074.939 |
17 | DATACENTER_BASEMENT_LIGHTS | LTG_SCH_OFFICE | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 8050.927 | 10.273 | 190.864 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 8050.927 |
18 | DATACENTER_BOT_LIGHTS | LTG_SCH_DATACENTER | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 647.068 | 17.873 | 332.067 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 647.068 |
19 | DATACENTER_MID_LIGHTS | LTG_SCH_DATACENTER | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 647.068 | 17.873 | 332.067 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 647.068 |
20 | DATACENTER_TOP_LIGHTS | LTG_SCH_DATACENTER | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 647.068 | 17.873 | 332.067 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 647.068 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | BASEMENT_MISCPLUG_EQUIP | ALWAYS_ON | BASEMENT | 2779.43 | 149.6 | 13457.544 | 4.842 | 89.956 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 13457.544 | 13457.544 |
2 | CORE_BOTTOM_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_BOTTOM | 2496.12 | 134.4 | 20142.877 | 8.070 | 149.925 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 20142.877 |
3 | CORE_MID_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_MID | 2496.12 | 134.4 | 20142.800 | 8.070 | 149.924 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 20142.800 |
4 | CORE_TOP_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_TOP | 2496.12 | 134.4 | 20142.800 | 8.070 | 149.924 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 20142.800 |
5 | PERIMETER_BOT_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 2529.242 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.242 |
6 | PERIMETER_BOT_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 1629.940 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.940 |
7 | PERIMETER_BOT_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 2529.281 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.281 |
8 | PERIMETER_BOT_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 1629.929 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.929 |
9 | PERIMETER_MID_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 2529.242 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.242 |
10 | PERIMETER_MID_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 1629.940 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.940 |
11 | PERIMETER_MID_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 2529.281 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.281 |
12 | PERIMETER_MID_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 1629.929 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.929 |
13 | PERIMETER_TOP_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 2529.242 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.242 |
14 | PERIMETER_TOP_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 1629.940 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.940 |
15 | PERIMETER_TOP_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 2529.281 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.281 |
16 | PERIMETER_TOP_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 1629.929 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.929 |
17 | DATACENTER_BASEMENT_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 379632.522 | 484.423 | 9000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 94908.130 | 379632.522 |
18 | DATACENTER_BOT_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 7794.422 | 215.299 | 4000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 1948.606 | 7794.422 |
19 | DATACENTER_MID_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 7794.422 | 215.299 | 4000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 1948.606 | 7794.422 |
20 | DATACENTER_TOP_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 7794.422 | 215.299 | 4000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 1948.606 | 7794.422 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 2.839 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | INTERIORFURNISHINGS | 2 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
3 | DROPCEILING | 4 | 1 | 3 | 0.167 | 4.488 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
4 | INT_WALL | 7 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | EXT_SLAB_8IN_WITH_CARPET | 8 | 2 | 7 | 0.167 | 3.285 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
6 | INT_SLAB_FLOOR | 12 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
7 | INT_SLAB_CEILING | 13 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | VeryRough |
8 | NONRES_ROOF | 17 | 3 | 3 | 0.167 | 0.1864 | 0.900 | 0.900 | 0.700 | 0.700 | Rough |
9 | NONRES_EXT_WALL_GRD | 20 | 3 | 9 | 0.167 | 0.8952 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
10 | NONRES_EXT_WALL_MID | 21 | 3 | 9 | 0.167 | 0.8506 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
11 | NONRES_EXT_WALL_TOP | 22 | 3 | 9 | 0.167 | 1.077 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
12 | BASEMENT_WALL_EAST_CFACTOR | 39 | 2 | 7 | 0.167 | 0.3542 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | BASEMENT_WALL_SOUTH_CFACTOR | 40 | 2 | 7 | 0.167 | 0.3542 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | BASEMENT_WALL_NORTH_CFACTOR | 41 | 2 | 7 | 0.167 | 0.3542 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR | 42 | 2 | 7 | 0.167 | 0.3542 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
16 | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR | 43 | 2 | 7 | 0.167 | 0.3542 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
17 | DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR | 44 | 2 | 7 | 0.167 | 0.3542 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.3522 |
2 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
3 | AC02 ACOUSTIC CEILING | 0.0127 | 0.057 | 288.000 | 1339.000 | 0.2228 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | 200MM NORMALWEIGHT CONCRETE FLOOR | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
7 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
8 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
9 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
10 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
11 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
12 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
13 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 5.307 |
14 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
15 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
16 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9497 |
17 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
18 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
19 | NONRES_EXTERIOR_WALL_INSULATION_MID | 0.0000 | 0.000 | 0.000 | 0.000 | 1.008 |
20 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
21 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
22 | NONRES_EXTERIOR_WALL_INSULATION_TOP | 0.0000 | 0.000 | 0.000 | 0.000 | 0.7608 |
23 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
24 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.747 |
25 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
26 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.747 |
27 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
28 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.747 |
29 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
30 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.747 |
31 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
32 | ~FC_Insulation_5 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.747 |
33 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
34 | ~FC_Insulation_6 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.747 |
35 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 2.8391315 | 2.8391315 | 2.8391315 | |
3 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
4 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
5 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
6 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
7 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
8 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
9 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
10 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
11 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
12 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
13 | 3 | -0.21589802E-09 | 0.15643069E-09 | -0.21589802E-09 | 0.12999471E-21 |
14 | 2 | 0.50772448E-02 | 0.30006816E-02 | 0.50772448E-02 | -0.13693132E-08 |
15 | 1 | -2.5944910 | 1.4597758 | -2.5944910 | 0.76344767E-02 |
16 | 0 | 7.0433378 | 2.9911476 | 7.0433378 | |
17 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
18 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
19 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
20 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
21 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
22 | 7 | -0.18651654E-16 | -0.16428647E-15 | -0.26578847E-08 | -0.25364002E-17 |
23 | 6 | 0.67402962E-01 | 0.99142722E-07 | 0.38101547E-02 | -0.76639482E-03 |
24 | 5 | -1.8580732 | 0.49502125E-04 | -0.10651409 | 0.21891119E-01 |
25 | 4 | 18.220105 | 0.12801333E-02 | 1.0775450 | -0.22586539 |
26 | 3 | -79.928293 | 0.66708484E-02 | -4.9803755 | 1.0625663 |
27 | 2 | 166.43177 | 0.75131194E-02 | 11.128837 | -2.4125483 |
28 | 1 | -159.97298 | 0.18548900E-02 | -11.587784 | 2.5494418 |
29 | 0 | 57.057412 | 0.52755123E-04 | 4.4818272 | |
30 | 7 | 0.43260499E-16 | 0.34524919E-16 | 0.52793240E-17 | 0.0000000 |
31 | 6 | 0.69434179E-09 | 0.98085174E-11 | 0.18162501E-10 | -0.40870994E-12 |
32 | 5 | -0.12888762E-04 | 0.28373718E-06 | -0.16918523E-06 | 0.92361873E-08 |
33 | 4 | 0.25174112E-01 | 0.33697681E-03 | 0.22646198E-03 | -0.31467795E-04 |
34 | 3 | -3.7600775 | 0.27170599E-01 | -0.48495626E-01 | 0.94171705E-02 |
35 | 2 | 51.553741 | 0.22121684 | 1.2284947 | -0.25833933 |
36 | 1 | -128.86110 | 0.21944682 | -5.1479470 | 1.1228340 |
37 | 0 | 81.526494 | 0.16043334E-01 | 4.4519351 | |
38 | 7 | 0.52793240E-17 | 0.34524919E-16 | 0.43260499E-16 | 0.0000000 |
39 | 6 | 0.18162501E-10 | 0.98085174E-11 | 0.69434179E-09 | -0.40870994E-12 |
40 | 5 | -0.16918523E-06 | 0.28373718E-06 | -0.12888762E-04 | 0.92361873E-08 |
41 | 4 | 0.22646198E-03 | 0.33697681E-03 | 0.25174112E-01 | -0.31467795E-04 |
42 | 3 | -0.48495626E-01 | 0.27170599E-01 | -3.7600775 | 0.94171705E-02 |
43 | 2 | 1.2284947 | 0.22121684 | 51.553741 | -0.25833933 |
44 | 1 | -5.1479470 | 0.21944682 | -128.86110 | 1.1228340 |
45 | 0 | 4.4519351 | 0.16043334E-01 | 81.526494 | |
46 | 3 | -0.62854340E-06 | 0.84784826E-09 | -0.38512804E-05 | 0.91756347E-17 |
47 | 2 | 0.78257096 | 0.11428808E-02 | 1.0614277 | -0.73836085E-06 |
48 | 1 | -21.991499 | 0.76199851E-01 | -6.3161914 | 0.20349372 |
49 | 0 | 21.357363 | 0.71091016E-01 | 5.4032014 | |
50 | 9 | -0.25194710E-14 | 0.31545203E-16 | -0.15133332E-09 | 0.44281407E-16 |
51 | 8 | 0.22101568E-07 | 0.12077324E-12 | 0.38017447E-03 | -0.25130244E-09 |
52 | 7 | -0.12312625E-01 | 0.62550027E-08 | -0.23188143E-01 | 0.13999903E-03 |
53 | 6 | 0.40728147 | 0.21773539E-05 | 0.47373573 | -0.47705255E-02 |
54 | 5 | -5.2094091 | 0.81341902E-04 | -4.4538940 | 0.63417525E-01 |
55 | 4 | 33.086216 | 0.66572093E-03 | 21.489723 | -0.42322968 |
56 | 3 | -111.40360 | 0.14515221E-02 | -55.721658 | 1.5177572 |
57 | 2 | 197.30704 | 0.81680373E-03 | 77.964377 | -2.9035099 |
58 | 1 | -171.22951 | 0.87228510E-04 | -55.280715 | 2.7467265 |
59 | 0 | 57.057407 | 0.49677855E-06 | 15.554344 | |
60 | 9 | -0.24471812E-14 | 0.33150161E-16 | -0.15341684E-09 | 0.41895861E-16 |
61 | 8 | 0.22394247E-07 | 0.11501389E-12 | 0.38323131E-03 | -0.25463030E-09 |
62 | 7 | -0.12403778E-01 | 0.59379868E-08 | -0.23319368E-01 | 0.14103548E-03 |
63 | 6 | 0.40975819 | 0.20644311E-05 | 0.47584355 | -0.47997200E-02 |
64 | 5 | -5.2335779 | 0.77040749E-04 | -4.4700764 | 0.63717207E-01 |
65 | 4 | 33.193114 | 0.62990908E-03 | 21.552961 | -0.42464900 |
66 | 3 | -111.63102 | 0.13722529E-02 | -55.846672 | 1.5210429 |
67 | 2 | 197.53241 | 0.77160263E-03 | 78.079059 | -2.9070889 |
68 | 1 | -171.31275 | 0.82342669E-04 | -55.314112 | 2.7481854 |
69 | 0 | 57.057407 | 0.46858505E-06 | 15.548868 | |
70 | 9 | -0.15654789E-15 | 0.36780279E-16 | -0.14275499E-09 | -0.53833073E-18 |
71 | 8 | 0.20895136E-07 | 0.14393424E-12 | 0.36742668E-03 | -0.23758489E-09 |
72 | 7 | -0.11931991E-01 | 0.75543961E-08 | -0.22640018E-01 | 0.13567108E-03 |
73 | 6 | 0.39693859 | 0.26436989E-05 | 0.46492102 | -0.46486079E-02 |
74 | 5 | -5.1084706 | 0.99216708E-04 | -4.3861655 | 0.62165936E-01 |
75 | 4 | 32.639712 | 0.81537030E-03 | 21.224928 | -0.41730137 |
76 | 3 | -110.45353 | 0.17843548E-02 | -55.198128 | 1.5040313 |
77 | 2 | 196.36533 | 0.10073836E-02 | 77.484335 | -2.8885557 |
78 | 1 | -170.88163 | 0.10790658E-03 | -55.141337 | 2.7406295 |
79 | 0 | 57.057407 | 0.61658484E-06 | 15.577537 | |
80 | 7 | -0.11729247E-08 | -0.12287178E-15 | 0.68000855E-14 | -0.85819789E-16 |
81 | 6 | 0.99010087E-05 | 0.68275672E-08 | 0.31776201E-02 | -0.26656541E-04 |
82 | 5 | -0.71743827E-03 | 0.40498262E-05 | -0.22302824 | 0.19500041E-02 |
83 | 4 | 0.16534150E-01 | 0.18445051E-03 | 4.8179460 | -0.45153479E-01 |
84 | 3 | -0.14527752 | 0.14677644E-02 | -37.955880 | 0.39792938 |
85 | 2 | 0.51595076 | 0.24428280E-02 | 116.35639 | -1.4162330 |
86 | 1 | -0.74475336 | 0.74501918E-03 | -143.83221 | 2.0478056 |
87 | 0 | 0.36311555 | 0.17917760E-04 | 60.838472 | |
88 | 7 | -0.11729247E-08 | -0.12287178E-15 | 0.68000855E-14 | -0.85819789E-16 |
89 | 6 | 0.99010087E-05 | 0.68275672E-08 | 0.31776201E-02 | -0.26656541E-04 |
90 | 5 | -0.71743827E-03 | 0.40498262E-05 | -0.22302824 | 0.19500041E-02 |
91 | 4 | 0.16534150E-01 | 0.18445051E-03 | 4.8179460 | -0.45153479E-01 |
92 | 3 | -0.14527752 | 0.14677644E-02 | -37.955880 | 0.39792938 |
93 | 2 | 0.51595076 | 0.24428280E-02 | 116.35639 | -1.4162330 |
94 | 1 | -0.74475336 | 0.74501918E-03 | -143.83221 | 2.0478056 |
95 | 0 | 0.36311555 | 0.17917760E-04 | 60.838472 | |
96 | 7 | -0.11729247E-08 | -0.12287178E-15 | 0.68000855E-14 | -0.85819789E-16 |
97 | 6 | 0.99010087E-05 | 0.68275672E-08 | 0.31776201E-02 | -0.26656541E-04 |
98 | 5 | -0.71743827E-03 | 0.40498262E-05 | -0.22302824 | 0.19500041E-02 |
99 | 4 | 0.16534150E-01 | 0.18445051E-03 | 4.8179460 | -0.45153479E-01 |
100 | 3 | -0.14527752 | 0.14677644E-02 | -37.955880 | 0.39792938 |
101 | 2 | 0.51595076 | 0.24428280E-02 | 116.35639 | -1.4162330 |
102 | 1 | -0.74475336 | 0.74501918E-03 | -143.83221 | 2.0478056 |
103 | 0 | 0.36311555 | 0.17917760E-04 | 60.838472 | |
104 | 7 | -0.11729247E-08 | -0.12287178E-15 | 0.68000855E-14 | -0.85819789E-16 |
105 | 6 | 0.99010087E-05 | 0.68275672E-08 | 0.31776201E-02 | -0.26656541E-04 |
106 | 5 | -0.71743827E-03 | 0.40498262E-05 | -0.22302824 | 0.19500041E-02 |
107 | 4 | 0.16534150E-01 | 0.18445051E-03 | 4.8179460 | -0.45153479E-01 |
108 | 3 | -0.14527752 | 0.14677644E-02 | -37.955880 | 0.39792938 |
109 | 2 | 0.51595076 | 0.24428280E-02 | 116.35639 | -1.4162330 |
110 | 1 | -0.74475336 | 0.74501918E-03 | -143.83221 | 2.0478056 |
111 | 0 | 0.36311555 | 0.17917760E-04 | 60.838472 | |
112 | 7 | -0.11729247E-08 | -0.12287178E-15 | 0.68000855E-14 | -0.85819789E-16 |
113 | 6 | 0.99010087E-05 | 0.68275672E-08 | 0.31776201E-02 | -0.26656541E-04 |
114 | 5 | -0.71743827E-03 | 0.40498262E-05 | -0.22302824 | 0.19500041E-02 |
115 | 4 | 0.16534150E-01 | 0.18445051E-03 | 4.8179460 | -0.45153479E-01 |
116 | 3 | -0.14527752 | 0.14677644E-02 | -37.955880 | 0.39792938 |
117 | 2 | 0.51595076 | 0.24428280E-02 | 116.35639 | -1.4162330 |
118 | 1 | -0.74475336 | 0.74501918E-03 | -143.83221 | 2.0478056 |
119 | 0 | 0.36311555 | 0.17917760E-04 | 60.838472 | |
120 | 7 | -0.11729247E-08 | -0.12287178E-15 | 0.68000855E-14 | -0.85819789E-16 |
121 | 6 | 0.99010087E-05 | 0.68275672E-08 | 0.31776201E-02 | -0.26656541E-04 |
122 | 5 | -0.71743827E-03 | 0.40498262E-05 | -0.22302824 | 0.19500041E-02 |
123 | 4 | 0.16534150E-01 | 0.18445051E-03 | 4.8179460 | -0.45153479E-01 |
124 | 3 | -0.14527752 | 0.14677644E-02 | -37.955880 | 0.39792938 |
125 | 2 | 0.51595076 | 0.24428280E-02 | 116.35639 | -1.4162330 |
126 | 1 | -0.74475336 | 0.74501918E-03 | -143.83221 | 2.0478056 |
127 | 0 | 0.36311555 | 0.17917760E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | WINDOW_U_0.419_SHGC_EAST_0.4 | 35 | 1 | VerySmooth | 2.381 | 2.381 | 1.000 | 0.401 | ||
2 | WINDOW_U_0.419_SHGC_SOUTH_0.4 | 36 | 1 | VerySmooth | 2.381 | 2.381 | 1.000 | 0.401 | ||
3 | WINDOW_U_0.419_SHGC_WEST_0.4 | 37 | 1 | VerySmooth | 2.381 | 2.381 | 1.000 | 0.401 | ||
4 | WINDOW_U_0.419_SHGC_NORTH_0.4 | 38 | 1 | VerySmooth | 2.381 | 2.381 | 1.000 | 0.401 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | GLAZING LAYER EAST | SpectralAverage | 3.03930E-002 | 0.31435 | 0.47506 | 0.47506 | 0.44000 | 0.13397 | 0.17027 | 0.00000 | 0.84000 | 0.84000 | 0.12237 | 1.00000 | No | |
2 | GLAZING LAYER SOUTH | SpectralAverage | 3.03930E-002 | 0.31435 | 0.47506 | 0.47506 | 0.44000 | 0.13397 | 0.17027 | 0.00000 | 0.84000 | 0.84000 | 0.12237 | 1.00000 | No | |
3 | GLAZING LAYER WEST | SpectralAverage | 3.03930E-002 | 0.31435 | 0.47506 | 0.47506 | 0.44000 | 0.13397 | 0.17027 | 0.00000 | 0.84000 | 0.84000 | 0.12237 | 1.00000 | No | |
4 | GLAZING LAYER NORTH | SpectralAverage | 3.03930E-002 | 0.31435 | 0.47506 | 0.47506 | 0.44000 | 0.13397 | 0.17027 | 0.00000 | 0.84000 | 0.84000 | 0.12237 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 30 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Enclosure Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Enclosures | |
1 | PERIMETER_BOT_ZN_3 | 5 | 0 |
2 | PERIMETER_BOT_ZN_2 | 3 | 0 |
3 | PERIMETER_BOT_ZN_1 | 5 | 0 |
4 | PERIMETER_BOT_ZN_4 | 3 | 0 |
5 | PERIMETER_MID_ZN_3 | 1 | 0 |
6 | PERIMETER_MID_ZN_2 | 1 | 0 |
7 | PERIMETER_MID_ZN_1 | 1 | 0 |
8 | PERIMETER_MID_ZN_4 | 1 | 0 |
9 | PERIMETER_TOP_ZN_3 | 1 | 0 |
10 | PERIMETER_TOP_ZN_2 | 1 | 0 |
11 | PERIMETER_TOP_ZN_1 | 1 | 0 |
12 | PERIMETER_TOP_ZN_4 | 1 | 0 |
Enclosure Name | Number of Adjacent Enclosures with Windows | Adjacent Enclosure Names - 1st 100 (max) | |
1 | PERIMETER_BOT_ZN_3 | 0 | |
2 | PERIMETER_BOT_ZN_2 | 0 | |
3 | PERIMETER_BOT_ZN_1 | 0 | |
4 | PERIMETER_BOT_ZN_4 | 0 | |
5 | PERIMETER_MID_ZN_3 | 0 | |
6 | PERIMETER_MID_ZN_2 | 0 | |
7 | PERIMETER_MID_ZN_1 | 0 | |
8 | PERIMETER_MID_ZN_4 | 0 | |
9 | PERIMETER_TOP_ZN_3 | 0 | |
10 | PERIMETER_TOP_ZN_2 | 0 | |
11 | PERIMETER_TOP_ZN_1 | 0 | |
12 | PERIMETER_TOP_ZN_4 | 0 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 1.1356 | 87921.3 | 0.481 | 5.5005E-002 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | BASEMENT_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
2 | BASEMENT_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
3 | BASEMENT_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
4 | BASEMENT_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
5 | BASEMENT_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
6 | PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
7 | PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
8 | CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
9 | PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
10 | BASEMENT_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
11 | CORE_BOT_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
12 | CORE_BOT_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
13 | CORE_BOT_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
14 | CORE_BOT_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
15 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
16 | CORE_BOT_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
17 | CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
18 | CORE_BOTTOM_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
19 | CORE_MID_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
20 | CORE_MID_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
21 | CORE_MID_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
22 | CORE_MID_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
23 | CORE_MID_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
24 | CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
25 | CORE_MID_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
26 | CORE_TOP_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
27 | CORE_TOP_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
28 | CORE_TOP_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
29 | CORE_TOP_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
30 | CORE_TOP_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
31 | CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
32 | CORE_TOP_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
33 | PERIMETER_BOT_ZN_3_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
34 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
35 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
36 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
37 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
38 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
39 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
40 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
41 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
42 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
43 | PERIMETER_BOT_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
44 | CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
45 | PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
46 | DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
47 | PERIMETER_BOT_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
48 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
49 | PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
50 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
51 | PERIMETER_BOT_ZN_2_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
52 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
53 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
54 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
55 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
56 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
57 | PERIMETER_BOT_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
58 | CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
59 | PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
60 | PERIMETER_BOT_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
61 | PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
62 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
63 | PERIMETER_BOT_ZN_1_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
64 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
65 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
66 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
67 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
68 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
69 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
70 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
71 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
72 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
73 | PERIMETER_BOT_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
74 | DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
75 | PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
76 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
77 | DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
78 | PERIMETER_BOT_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
79 | PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
80 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
81 | PERIMETER_BOT_ZN_4_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
82 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
83 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
84 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
85 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
86 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
87 | PERIMETER_BOT_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
88 | DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
89 | PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
90 | PERIMETER_BOT_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
91 | PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
92 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
93 | PERIMETER_MID_ZN_3_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
94 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
95 | PERIMETER_MID_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
96 | CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
97 | PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
98 | DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
99 | PERIMETER_MID_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
100 | PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
101 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
102 | PERIMETER_MID_ZN_2_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
103 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
104 | PERIMETER_MID_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
105 | CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
106 | PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
107 | PERIMETER_MID_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
108 | PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
109 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
110 | PERIMETER_MID_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
111 | PERIMETER_MID_ZN_1_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
112 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
113 | DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
114 | PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
115 | CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
116 | PERIMETER_MID_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
117 | PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
118 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
119 | PERIMETER_MID_ZN_4_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
120 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
121 | PERIMETER_MID_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
122 | DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
123 | PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
124 | PERIMETER_MID_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
125 | PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
126 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
127 | PERIMETER_TOP_ZN_3_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
128 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
129 | PERIMETER_TOP_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
130 | CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
131 | PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
132 | DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
133 | PERIMETER_TOP_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
134 | PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
135 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
136 | PERIMETER_TOP_ZN_2_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
137 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
138 | PERIMETER_TOP_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
139 | CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
140 | INT-PER3S-NE-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
141 | PERIMETER_TOP_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
142 | PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
143 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
144 | PERIMETER_TOP_ZN_1_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
145 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
146 | INT-PER3S-NE | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
147 | DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
148 | PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
149 | CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
150 | PERIMETER_TOP_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
151 | PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
152 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
153 | PERIMETER_TOP_ZN_4_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
154 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
155 | PERIMETER_TOP_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
156 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
157 | PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
158 | PERIMETER_TOP_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
159 | PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
160 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
161 | GROUNDFLOOR_PLENUM_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
162 | GROUNDFLOOR_PLENUM_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
163 | GROUNDFLOOR_PLENUM_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
164 | GROUNDFLOOR_PLENUM_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
165 | iz-CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
166 | iz-PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
167 | iz-PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
168 | iz-PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
169 | iz-PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
170 | iz-DATACENTER_BOT_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
171 | GROUNDFLOOR_PLENUM_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
172 | MIDFLOOR_PLENUM_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
173 | MIDFLOOR_PLENUM_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
174 | MIDFLOOR_PLENUM_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
175 | MIDFLOOR_PLENUM_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
176 | iz-CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
177 | iz-PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
178 | iz-PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
179 | iz-PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
180 | iz-PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
181 | iz-DATACENTER_MID_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
182 | MIDFLOOR_PLENUM_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
183 | TOPFLOOR_PLENUM_WALL_NORTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
184 | TOPFLOOR_PLENUM_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
185 | TOPFLOOR_PLENUM_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
186 | TOPFLOOR_PLENUM_WALL_SOUTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
187 | iz-CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
188 | iz-PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
189 | iz-PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
190 | iz-PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
191 | iz-PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
192 | iz-DATACENTER_TOP_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
193 | BUILDING_ROOF | 0 | 3563.11 | 268.06 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
194 | DATACENTER_BOT_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
195 | DATACENTER_BOT_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
196 | DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
197 | DATACENTER_BOT_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
198 | DATACENTER_BOT_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
199 | DATACENTER_BOT_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
200 | DATACENTER_MID_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
201 | DATACENTER_MID_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
202 | DATACENTER_MID_ZN_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
203 | DATACENTER_MID_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
204 | DATACENTER_MID_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
205 | DATACENTER_MID_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
206 | DATACENTER_TOP_ZN_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
207 | DATACENTER_TOP_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
208 | DATACENTER_TOP_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
209 | DATACENTER_TOP_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
210 | DATACENTER_TOP_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
211 | DATACENTER_TOP_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
212 | DATACENTER_BASEMENT_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
213 | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
214 | DATACENTER_BASEMENT_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
215 | DATACENTER_BASEMENT_ZN_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
216 | DATACENTER_BASEMENT_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
217 | DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
218 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
219 | PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
220 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
221 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | PERIMETER_BOT_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 0.114 | 3.646E-004 | 5.482E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | PERIMETER_BOT_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 7.617E-002 | 3.771E-004 | 5.534E-004 | 0.495 | 0.000 | 0.000 | 0.224 | 0.000 |
3 | PERIMETER_BOT_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 0.114 | 3.646E-004 | 5.482E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | PERIMETER_BOT_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 7.617E-002 | 3.771E-004 | 5.534E-004 | 0.495 | 0.000 | 0.000 | 0.224 | 0.000 |
5 | PERIMETER_MID_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 0.114 | 3.646E-004 | 5.696E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
6 | PERIMETER_MID_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 7.617E-002 | 3.771E-004 | 5.696E-004 | 0.495 | 0.000 | 0.000 | 0.224 | 0.000 |
7 | PERIMETER_MID_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 0.114 | 3.646E-004 | 5.696E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
8 | PERIMETER_MID_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 7.617E-002 | 3.771E-004 | 5.696E-004 | 0.495 | 0.000 | 0.000 | 0.224 | 0.000 |
9 | PERIMETER_TOP_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 0.114 | 3.646E-004 | 5.696E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
10 | PERIMETER_TOP_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 7.617E-002 | 3.771E-004 | 5.696E-004 | 0.495 | 0.000 | 0.000 | 0.224 | 0.000 |
11 | PERIMETER_TOP_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 0.114 | 3.646E-004 | 5.696E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
12 | PERIMETER_TOP_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 7.617E-002 | 3.771E-004 | 5.696E-004 | 0.495 | 0.000 | 0.000 | 0.224 | 0.000 |
13 | GROUNDFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | GROUNDFLOOR_PLENUM | 3563.11 | 0.0 | 0.169 | 4.749E-005 | 5.696E-004 | 0.140 | 0.000 | 0.000 | 0.224 | 0.000 |
14 | MIDFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | MIDFLOOR_PLENUM | 3563.11 | 0.0 | 0.169 | 4.749E-005 | 5.696E-004 | 0.140 | 0.000 | 0.000 | 0.224 | 0.000 |
15 | TOPFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | TOPFLOOR_PLENUM | 3563.11 | 0.0 | 0.169 | 4.749E-005 | 4.384E-005 | 0.140 | 0.000 | 0.000 | 0.224 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | BASEMENT | Mixing/Well-Stirred |
2 | CORE_BOTTOM | Mixing/Well-Stirred |
3 | CORE_MID | Mixing/Well-Stirred |
4 | CORE_TOP | Mixing/Well-Stirred |
5 | PERIMETER_BOT_ZN_3 | Mixing/Well-Stirred |
6 | PERIMETER_BOT_ZN_2 | Mixing/Well-Stirred |
7 | PERIMETER_BOT_ZN_1 | Mixing/Well-Stirred |
8 | PERIMETER_BOT_ZN_4 | Mixing/Well-Stirred |
9 | PERIMETER_MID_ZN_3 | Mixing/Well-Stirred |
10 | PERIMETER_MID_ZN_2 | Mixing/Well-Stirred |
11 | PERIMETER_MID_ZN_1 | Mixing/Well-Stirred |
12 | PERIMETER_MID_ZN_4 | Mixing/Well-Stirred |
13 | PERIMETER_TOP_ZN_3 | Mixing/Well-Stirred |
14 | PERIMETER_TOP_ZN_2 | Mixing/Well-Stirred |
15 | PERIMETER_TOP_ZN_1 | Mixing/Well-Stirred |
16 | PERIMETER_TOP_ZN_4 | Mixing/Well-Stirred |
17 | GROUNDFLOOR_PLENUM | Mixing/Well-Stirred |
18 | MIDFLOOR_PLENUM | Mixing/Well-Stirred |
19 | TOPFLOOR_PLENUM | Mixing/Well-Stirred |
20 | DATACENTER_BOT_ZN_6 | Mixing/Well-Stirred |
21 | DATACENTER_MID_ZN_6 | Mixing/Well-Stirred |
22 | DATACENTER_TOP_ZN_6 | Mixing/Well-Stirred |
23 | DATACENTER_BASEMENT_ZN_6 | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sky Type | MonthAndDay | Daylighting Control Name | Enclosure Name | Window Name | Reference Point | Daylight Factor | |
1 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 7.7114E-003 |
2 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 7.7138E-003 |
3 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 8.6318E-003 |
4 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 8.6338E-003 |
5 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.9702E-003 |
6 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.9717E-003 |
7 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.7740E-003 |
8 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.7748E-003 |
9 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 7.7655E-003 |
10 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 7.9212E-003 |
11 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 8.6773E-003 |
12 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 8.8128E-003 |
13 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 5.0080E-003 |
14 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 5.1195E-003 |
15 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.7969E-003 |
16 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.8551E-003 |
17 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 0.1825 |
18 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 9.9759E-002 |
19 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 0.2093 |
20 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 0.1158 |
21 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 0.1197 |
22 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.9531E-002 |
23 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 5.0165E-002 |
24 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.7447E-002 |
25 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 7.7778E-003 |
26 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 7.9872E-003 |
27 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 8.6910E-003 |
28 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 8.8865E-003 |
29 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 5.0181E-003 |
30 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 5.1586E-003 |
31 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.7974E-003 |
32 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.8568E-003 |
33 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 7.7112E-003 |
34 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 7.7140E-003 |
35 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 8.6316E-003 |
36 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 8.6341E-003 |
37 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.9701E-003 |
38 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.9720E-003 |
39 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.7739E-003 |
40 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.7747E-003 |
41 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 6.9174E-003 |
42 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 7.4164E-003 |
43 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 6.8025E-003 |
44 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 7.3880E-003 |
45 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 5.9588E-003 |
46 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 6.1161E-003 |
47 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 4.7428E-003 |
48 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 4.7830E-003 |
49 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 8.0221E-002 |
50 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.8990E-002 |
51 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 7.8391E-002 |
52 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.7084E-002 |
53 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 7.3623E-002 |
54 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.0756E-002 |
55 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 5.2230E-002 |
56 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 1.9536E-002 |
57 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 6.7592E-003 |
58 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 6.8797E-003 |
59 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 6.5933E-003 |
60 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 6.6821E-003 |
61 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 5.9106E-003 |
62 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 5.9465E-003 |
63 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 4.7430E-003 |
64 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 4.7836E-003 |
65 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.0492E-003 |
66 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 3.0516E-003 |
67 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.5843E-003 |
68 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.5863E-003 |
69 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.2615E-003 |
70 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.2630E-003 |
71 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.7740E-003 |
72 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.7749E-003 |
73 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.1042E-003 |
74 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 3.2430E-003 |
75 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.6306E-003 |
76 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.7435E-003 |
77 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.2998E-003 |
78 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.3855E-003 |
79 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.7975E-003 |
80 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.8569E-003 |
81 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 5.0464E-002 |
82 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.6651E-002 |
83 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.8839E-002 |
84 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.0271E-002 |
85 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.4674E-002 |
86 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.3448E-002 |
87 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 5.0165E-002 |
88 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.7442E-002 |
89 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.1014E-003 |
90 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 3.2438E-003 |
91 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.6261E-003 |
92 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.7371E-003 |
93 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.2918E-003 |
94 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.3604E-003 |
95 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.7969E-003 |
96 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.8551E-003 |
97 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.0490E-003 |
98 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 3.0514E-003 |
99 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.5841E-003 |
100 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.5860E-003 |
101 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.2613E-003 |
102 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.2625E-003 |
103 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.7739E-003 |
104 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.7748E-003 |
105 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 5.7277E-003 |
106 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 5.8556E-003 |
107 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 5.2654E-003 |
108 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 5.3581E-003 |
109 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 5.1943E-003 |
110 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 5.2259E-003 |
111 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 4.7431E-003 |
112 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 4.7837E-003 |
113 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 6.2155E-002 |
114 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.1514E-002 |
115 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 5.5261E-002 |
116 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.7481E-002 |
117 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 6.0374E-002 |
118 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.5330E-002 |
119 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 5.2230E-002 |
120 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 1.9536E-002 |
121 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 5.8323E-003 |
122 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 6.1338E-003 |
123 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 5.4051E-003 |
124 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 5.7328E-003 |
125 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 5.2377E-003 |
126 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 5.3710E-003 |
127 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 4.7428E-003 |
128 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 4.7829E-003 |
129 | Clear Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 0.1875 |
130 | Clear Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 0.1380 |
131 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 0.2098 |
132 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 0.1587 |
133 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 0.1346 |
134 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 7.3171E-002 |
135 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 6.1425E-002 |
136 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 3.0380E-002 |
137 | Clear Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 9.4930E-002 |
138 | Clear Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 5.5725E-002 |
139 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 9.2936E-002 |
140 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 5.3636E-002 |
141 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 8.6873E-002 |
142 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 4.4880E-002 |
143 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 6.2997E-002 |
144 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 3.0728E-002 |
145 | Clear Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 6.2218E-002 |
146 | Clear Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 4.1364E-002 |
147 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 4.9075E-002 |
148 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 3.2665E-002 |
149 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 4.4534E-002 |
150 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 2.4117E-002 |
151 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 6.1425E-002 |
152 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 3.0375E-002 |
153 | Clear Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 7.4507E-002 |
154 | Clear Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 4.5428E-002 |
155 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 6.6773E-002 |
156 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 4.0389E-002 |
157 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 7.2041E-002 |
158 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 3.7716E-002 |
159 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 6.2997E-002 |
160 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 3.0728E-002 |
161 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 0.1875 |
162 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 0.1382 |
163 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 0.2098 |
164 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 0.1590 |
165 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 0.1348 |
166 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 7.3346E-002 |
167 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 6.1557E-002 |
168 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 3.0447E-002 |
169 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 9.4994E-002 |
170 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 5.5813E-002 |
171 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 9.3010E-002 |
172 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 5.3724E-002 |
173 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 8.7004E-002 |
174 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 4.4977E-002 |
175 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 6.3129E-002 |
176 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 3.0795E-002 |
177 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 6.2221E-002 |
178 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 4.1412E-002 |
179 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 4.9082E-002 |
180 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 3.2703E-002 |
181 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 4.4605E-002 |
182 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 2.4162E-002 |
183 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 6.1557E-002 |
184 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 3.0442E-002 |
185 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 7.4543E-002 |
186 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 4.5492E-002 |
187 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 6.6813E-002 |
188 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 4.0447E-002 |
189 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 7.2149E-002 |
190 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 3.7794E-002 |
191 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 6.3129E-002 |
192 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 3.0795E-002 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | BASEMENT | Cooling | 82553.07926 | 82553.07926 | 6.81911 | 6.81911 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 21.56000 | 6.28881E-003 | 2779.42662 | 149.60210 | 1.20016 | 0.00000 |
2 | BASEMENT | Heating | 0.00000 | 0.00000 | 0.00000 | 1.20016 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -27.60000 | 3.41898E-004 | 2779.42662 | 149.60210 | 1.20016 | 0.00000 |
3 | CORE_BOTTOM | Cooling | 85532.33398 | 85532.33398 | 7.06426 | 7.06426 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 21.56000 | 6.28881E-003 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 |
4 | CORE_BOTTOM | Heating | 7875.69982 | 7875.69982 | 0.38153 | 1.07782 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -27.60000 | 3.41898E-004 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 |
5 | CORE_MID | Cooling | 805659.30733 | 805659.30733 | 66.52664 | 66.52664 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 21.56000 | 6.28881E-003 | 2496.12046 | 134.35320 | 10.77825 | 0.00000 |
6 | CORE_MID | Heating | 340208.23813 | 340208.23813 | 16.46825 | 16.46825 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -27.60000 | 3.41898E-004 | 2496.12046 | 134.35320 | 10.77825 | 0.00000 |
7 | CORE_TOP | Cooling | 77939.31004 | 77939.31004 | 6.43541 | 6.43541 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 21.56000 | 6.28881E-003 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 |
8 | CORE_TOP | Heating | 78157.42200 | 78157.42200 | 3.80376 | 3.80376 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -27.60000 | 3.41898E-004 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 |
9 | PERIMETER_BOT_ZN_3 | Cooling | 14368.61633 | 14368.61633 | 1.19693 | 1.19693 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 | 33.40000 | 6.30683E-003 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
10 | PERIMETER_BOT_ZN_3 | Heating | 15136.08931 | 15136.08931 | 0.73778 | 0.73778 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -27.60000 | 3.41898E-004 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
11 | PERIMETER_BOT_ZN_2 | Cooling | 19479.38923 | 19479.38923 | 1.62265 | 1.62265 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | 24.60000 | 6.29334E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
12 | PERIMETER_BOT_ZN_2 | Heating | 10356.48416 | 10356.48416 | 0.50489 | 0.50489 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -27.60000 | 3.41898E-004 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
13 | PERIMETER_BOT_ZN_1 | Cooling | 24109.11167 | 24109.11167 | 2.00831 | 2.00831 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 33.00000 | 6.30621E-003 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
14 | PERIMETER_BOT_ZN_1 | Heating | 16580.20921 | 16580.20921 | 0.80836 | 0.80836 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -27.60000 | 3.41898E-004 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
15 | PERIMETER_BOT_ZN_4 | Cooling | 23888.41645 | 23888.41645 | 1.98992 | 1.98992 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:20:00 | 30.62667 | 6.30253E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
16 | PERIMETER_BOT_ZN_4 | Heating | 8819.29622 | 8819.29622 | 0.42974 | 0.42974 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -27.60000 | 3.41898E-004 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
17 | PERIMETER_MID_ZN_3 | Cooling | 136839.93297 | 136839.93297 | 11.39885 | 11.39885 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | 33.40000 | 6.30683E-003 | 313.41284 | 16.86939 | 1.35332 | 0.00000 |
18 | PERIMETER_MID_ZN_3 | Heating | 213421.17092 | 213421.17092 | 10.41036 | 10.41036 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -27.60000 | 3.41898E-004 | 313.41284 | 16.86939 | 1.35332 | 0.00000 |
19 | PERIMETER_MID_ZN_2 | Cooling | 207805.49354 | 207805.49354 | 17.31016 | 17.31016 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:20:00 | 25.50667 | 6.29470E-003 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
20 | PERIMETER_MID_ZN_2 | Heating | 141642.71545 | 141642.71545 | 6.90947 | 6.90947 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -27.60000 | 3.41898E-004 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
21 | PERIMETER_MID_ZN_1 | Cooling | 246290.66715 | 246290.66715 | 20.51606 | 20.51606 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | 33.26667 | 6.30663E-003 | 313.41969 | 16.86975 | 1.35335 | 0.00000 |
22 | PERIMETER_MID_ZN_1 | Heating | 216704.94510 | 216704.94510 | 10.57085 | 10.57085 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -27.60000 | 3.41898E-004 | 313.41969 | 16.86975 | 1.35335 | 0.00000 |
23 | PERIMETER_MID_ZN_4 | Cooling | 224695.19226 | 224695.19226 | 18.71708 | 18.71708 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:30:00 | 30.36000 | 6.30211E-003 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
24 | PERIMETER_MID_ZN_4 | Heating | 139841.48150 | 139841.48150 | 6.82149 | 6.82149 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -27.60000 | 3.41898E-004 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
25 | PERIMETER_TOP_ZN_3 | Cooling | 15383.92302 | 15383.92302 | 1.28148 | 1.28148 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 33.24000 | 6.30658E-003 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
26 | PERIMETER_TOP_ZN_3 | Heating | 26939.42523 | 26939.42523 | 1.31453 | 1.31453 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -27.60000 | 3.41898E-004 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
27 | PERIMETER_TOP_ZN_2 | Cooling | 20780.73837 | 20780.73837 | 1.73102 | 1.73102 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:40:00 | 26.41333 | 6.29608E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
28 | PERIMETER_TOP_ZN_2 | Heating | 17784.00962 | 17784.00962 | 0.86781 | 0.86781 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -27.60000 | 3.41898E-004 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
29 | PERIMETER_TOP_ZN_1 | Cooling | 26241.13139 | 26241.13139 | 2.18588 | 2.18588 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | 33.26667 | 6.30663E-003 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
30 | PERIMETER_TOP_ZN_1 | Heating | 27301.99408 | 27301.99408 | 1.33224 | 1.33224 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -27.60000 | 3.41898E-004 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
31 | PERIMETER_TOP_ZN_4 | Cooling | 23599.30828 | 23599.30828 | 1.96581 | 1.96581 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:30:00 | 30.36000 | 6.30211E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
32 | PERIMETER_TOP_ZN_4 | Heating | 17794.89717 | 17794.89717 | 0.86835 | 0.86835 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -27.60000 | 3.41898E-004 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
33 | DATACENTER_BOT_ZN_6 | Cooling | 8909.33644 | 8909.33644 | 0.58537 | 0.58537 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:30:00 | 26.28000 | 6.29588E-003 | 36.20274 | 1.94861 | 1.56323E-002 | 0.00000 |
34 | DATACENTER_BOT_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 1.56323E-002 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 05:30:00 | -27.60000 | 3.41898E-004 | 36.20274 | 1.94861 | 1.56323E-002 | 0.00000 |
35 | DATACENTER_MID_ZN_6 | Cooling | 85682.56024 | 85682.56024 | 5.62967 | 5.62967 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:30:00 | 26.28000 | 6.29588E-003 | 36.20274 | 1.94861 | 0.15632 | 0.00000 |
36 | DATACENTER_MID_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 0.15632 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 05:40:00 | -27.60000 | 3.41898E-004 | 36.20274 | 1.94861 | 0.15632 | 0.00000 |
37 | DATACENTER_TOP_ZN_6 | Cooling | 8712.46582 | 8712.46582 | 0.57244 | 0.57244 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:30:00 | 26.28000 | 6.29588E-003 | 36.20274 | 1.94861 | 1.56323E-002 | 0.00000 |
38 | DATACENTER_TOP_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 1.56323E-002 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 05:30:00 | -27.60000 | 3.41898E-004 | 36.20274 | 1.94861 | 1.56323E-002 | 0.00000 |
39 | DATACENTER_BASEMENT_ZN_6 | Cooling | 373481.81429 | 373481.81429 | 24.53881 | 24.53881 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 07:00:00 | 18.84000 | 6.28481E-003 | 783.67941 | 42.18139 | 0.33839 | 0.00000 |
40 | DATACENTER_BASEMENT_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 0.33839 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:40:00 | -27.60000 | 3.41898E-004 | 783.67941 | 42.18139 | 0.33839 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | VAV_BOT WITH REHEAT | Cooling | Sensible | 163330.59 | 11.65570 | 11.65570 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
2 | VAV_BOT WITH REHEAT | Heating | Sensible | 108028.99 | 3.55860 | 3.55860 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 06:30:00 |
3 | VAV_MID WITH REHEAT | Cooling | Sensible | 1529352.26 | 107.83186 | 107.83186 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
4 | VAV_MID WITH REHEAT | Heating | Sensible | 1081058.86 | 51.18042 | 51.18042 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 05:30:00 |
5 | VAV_TOP WITH REHEAT | Cooling | Sensible | 170548.15 | 12.30079 | 12.30079 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
6 | VAV_TOP WITH REHEAT | Heating | Sensible | 108460.41 | 8.18669 | 8.18669 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 01:50:00 |
7 | CAV_BAS | Cooling | Sensible | 82824.94 | 6.81911 | 6.81911 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
8 | CAV_BAS | Heating | Sensible | 85856.97 | 1.20016 | 1.20016 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
9 | AIRLOOP DATACENTER BASEMENT | Cooling | Sensible | 370565.49 | 24.53890 | 24.53890 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
10 | AIRLOOP DATACENTER BASEMENT | Heating | Sensible | 24207.99 | 0.33839 | 0.33839 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
11 | AIRLOOP DATACENTER BOT | Cooling | Sensible | 8783.71 | 0.58537 | 0.58537 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
12 | AIRLOOP DATACENTER BOT | Heating | Sensible | 1118.31 | 1.56323E-002 | 1.56323E-002 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
13 | AIRLOOP DATACENTER MID | Cooling | Sensible | 84469.88 | 5.62967 | 5.62967 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
14 | AIRLOOP DATACENTER MID | Heating | Sensible | 11183.09 | 0.15632 | 0.15632 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
15 | AIRLOOP DATACENTER TOP | Cooling | Sensible | 8589.36 | 0.57244 | 0.57244 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
16 | AIRLOOP DATACENTER TOP | Heating | Sensible | 1118.31 | 1.56323E-002 | 1.56323E-002 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | BASEMENT DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 6.81911 |
2 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 7.06426 |
3 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.26925 |
4 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.28800 |
5 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.03451 |
6 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.71800 |
7 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
8 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.41505E-003 |
9 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.25635E-004 |
10 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 2.03451 |
11 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
12 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
13 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 25791.50526 |
14 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.25635E-004 |
15 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 543.50738 |
16 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 66.52664 |
17 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.28591 |
18 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.29900 |
19 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 19.89147 |
20 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.76242 |
21 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
22 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.33260E-003 |
23 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 4.50870E-003 |
24 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 19.89147 |
25 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
26 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
27 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 515371.91356 |
28 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 4.50870E-003 |
29 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 12910.41781 |
30 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 6.43541 |
31 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.29556 |
32 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.32000 |
33 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.05933 |
34 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.78816 |
35 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
36 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.28908E-003 |
37 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 9.76791E-004 |
38 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 3.80376 |
39 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
40 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
41 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 111653.25213 |
42 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 9.76791E-004 |
43 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 2946.06819 |
44 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.19693 |
45 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.19953 |
46 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.21300 |
47 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.25495 |
48 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.53207 |
49 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
50 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.90951E-003 |
51 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.89227E-004 |
52 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.73778 |
53 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
54 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
55 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 21629.81784 |
56 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.89227E-004 |
57 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 570.40028 |
58 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.62265 |
59 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 9.48482E-002 |
60 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
61 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.32453 |
62 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
63 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
64 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 4.01695E-003 |
65 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.29481E-004 |
66 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.50489 |
67 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
68 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
69 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 14800.43298 |
70 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.29481E-004 |
71 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 390.28326 |
72 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.00831 |
73 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.11892 |
74 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
75 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.40166 |
76 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.31712 |
77 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
78 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.20387E-003 |
79 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.07298E-004 |
80 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.80836 |
81 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
82 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
83 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 23695.43660 |
84 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.07298E-004 |
85 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 624.83133 |
86 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.98992 |
87 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 7.73424E-002 |
88 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
89 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.39798 |
90 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
91 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
92 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 4.92615E-003 |
93 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.10243E-004 |
94 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.42974 |
95 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
96 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
97 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 12601.40517 |
98 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.10243E-004 |
99 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 332.34214 |
100 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 11.39885 |
101 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.20951 |
102 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.21900 |
103 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.49635 |
104 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.55870 |
105 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
106 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.81850E-003 |
107 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.66844E-003 |
108 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 10.41036 |
109 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
110 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
111 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 305019.34868 |
112 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.66844E-003 |
113 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 8041.45526 |
114 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 17.31016 |
115 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 8.89102E-002 |
116 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
117 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 3.46203 |
118 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
119 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
120 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 4.28522E-003 |
121 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.77101E-003 |
122 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 6.90947 |
123 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
124 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
125 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 202437.02019 |
126 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.77101E-003 |
127 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 5336.90563 |
128 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 20.51606 |
129 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.11641 |
130 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
131 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 4.10321 |
132 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.31042 |
133 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
134 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.27294E-003 |
135 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.70953E-003 |
136 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 10.57085 |
137 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
138 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
139 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 309716.06669 |
140 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.70953E-003 |
141 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 8165.21188 |
142 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 18.71708 |
143 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 8.22270E-002 |
144 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
145 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 3.74342 |
146 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
147 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
148 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 4.63351E-003 |
149 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.74847E-003 |
150 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 6.82149 |
151 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
152 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
153 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 199861.13769 |
154 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.74847E-003 |
155 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 5269.01877 |
156 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.31453 |
157 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.18168 |
158 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20200 |
159 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.26553 |
160 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.48448 |
161 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
162 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.09712E-003 |
163 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 3.36861E-004 |
164 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.31453 |
165 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
166 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
167 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 38505.23007 |
168 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.36861E-004 |
169 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 1015.02393 |
170 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.73102 |
171 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 8.89098E-002 |
172 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
173 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.34620 |
174 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
175 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
176 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 4.28524E-003 |
177 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.22379E-004 |
178 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.86781 |
179 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
180 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
181 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 25419.30122 |
182 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.22379E-004 |
183 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 670.06202 |
184 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.18588 |
185 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.10926 |
186 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
187 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.43718 |
188 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
189 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
190 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.48715E-003 |
191 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 3.41397E-004 |
192 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.33224 |
193 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
194 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
195 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 39023.78017 |
196 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.41397E-004 |
197 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 1028.68782 |
198 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.96581 |
199 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 7.82909E-002 |
200 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
201 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.39316 |
202 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
203 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
204 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 4.86647E-003 |
205 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.22516E-004 |
206 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.86835 |
207 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
208 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
209 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 25434.92199 |
210 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.22516E-004 |
211 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 670.47207 |
212 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DATACENTER_BOT_ZN_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.58537 |
213 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DATACENTER_MID_ZN_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 5.62967 |
214 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DATACENTER_TOP_ZN_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.57244 |
215 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DATACENTER_BASEMENT_ZN_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 24.53881 |
216 | AirLoopHVAC | VAV_BOT WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 6.94103 |
217 | AirLoopHVAC | VAV_BOT WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 3.41363 |
218 | AirLoopHVAC | VAV_BOT WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 13.88207 |
219 | AirLoopHVAC | VAV_BOT WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 3.55860 |
220 | AirLoopHVAC | VAV_BOT WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 11.65570 |
221 | AirLoopHVAC | VAV_BOT WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 11.65570 |
222 | AirLoopHVAC | VAV_BOT WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
223 | AirLoopHVAC | VAV_BOT WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.30531 |
224 | AirLoopHVAC | VAV_MID WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 67.23440 |
225 | AirLoopHVAC | VAV_MID WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 33.69648 |
226 | AirLoopHVAC | VAV_MID WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 134.46880 |
227 | AirLoopHVAC | VAV_MID WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 51.18042 |
228 | AirLoopHVAC | VAV_MID WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 107.83186 |
229 | AirLoopHVAC | VAV_MID WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 107.83186 |
230 | AirLoopHVAC | VAV_MID WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
231 | AirLoopHVAC | VAV_MID WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.47463 |
232 | AirLoopHVAC | VAV_TOP WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 6.81632 |
233 | AirLoopHVAC | VAV_TOP WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 3.50141 |
234 | AirLoopHVAC | VAV_TOP WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 13.63265 |
235 | AirLoopHVAC | VAV_TOP WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 8.18669 |
236 | AirLoopHVAC | VAV_TOP WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 12.30079 |
237 | AirLoopHVAC | VAV_TOP WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 12.30079 |
238 | AirLoopHVAC | VAV_TOP WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
239 | AirLoopHVAC | VAV_TOP WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.66554 |
240 | AirLoopHVAC | CAV_BAS | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 6.81911 |
241 | AirLoopHVAC | CAV_BAS | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 6.81911 |
242 | AirLoopHVAC | CAV_BAS | Sum of Air Terminal Maximum Flow Rates [m3/s] | 6.81911 |
243 | AirLoopHVAC | CAV_BAS | Adjusted Heating Design Air Flow Rate [m3/s] | 6.81911 |
244 | AirLoopHVAC | CAV_BAS | Adjusted Cooling Design Air Flow Rate [m3/s] | 6.81911 |
245 | AirLoopHVAC | CAV_BAS | Adjusted Main Design Air Flow Rate [m3/s] | 6.81911 |
246 | AirLoopHVAC | CAV_BAS | User Heating Air Flow Ratio [] | 1.00000 |
247 | AirLoopHVAC | CAV_BAS | Calculated Heating Air Flow Ratio [] | 1.00000 |
248 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 24.53881 |
249 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 24.53881 |
250 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 24.53881 |
251 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Adjusted Heating Design Air Flow Rate [m3/s] | 24.53881 |
252 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Adjusted Cooling Design Air Flow Rate [m3/s] | 24.53890 |
253 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Adjusted Main Design Air Flow Rate [m3/s] | 24.53890 |
254 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | User Heating Air Flow Ratio [] | 1.00000 |
255 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Calculated Heating Air Flow Ratio [] | 1.00000 |
256 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.58537 |
257 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.58537 |
258 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.58537 |
259 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Adjusted Heating Design Air Flow Rate [m3/s] | 0.58537 |
260 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.58537 |
261 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Adjusted Main Design Air Flow Rate [m3/s] | 0.58537 |
262 | AirLoopHVAC | AIRLOOP DATACENTER BOT | User Heating Air Flow Ratio [] | 1.00000 |
263 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Calculated Heating Air Flow Ratio [] | 1.00000 |
264 | AirLoopHVAC | AIRLOOP DATACENTER MID | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 5.62967 |
265 | AirLoopHVAC | AIRLOOP DATACENTER MID | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 5.62967 |
266 | AirLoopHVAC | AIRLOOP DATACENTER MID | Sum of Air Terminal Maximum Flow Rates [m3/s] | 5.62967 |
267 | AirLoopHVAC | AIRLOOP DATACENTER MID | Adjusted Heating Design Air Flow Rate [m3/s] | 5.62967 |
268 | AirLoopHVAC | AIRLOOP DATACENTER MID | Adjusted Cooling Design Air Flow Rate [m3/s] | 5.62967 |
269 | AirLoopHVAC | AIRLOOP DATACENTER MID | Adjusted Main Design Air Flow Rate [m3/s] | 5.62967 |
270 | AirLoopHVAC | AIRLOOP DATACENTER MID | User Heating Air Flow Ratio [] | 1.00000 |
271 | AirLoopHVAC | AIRLOOP DATACENTER MID | Calculated Heating Air Flow Ratio [] | 1.00000 |
272 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.57244 |
273 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.57244 |
274 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.57244 |
275 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Adjusted Heating Design Air Flow Rate [m3/s] | 0.57244 |
276 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.57244 |
277 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Adjusted Main Design Air Flow Rate [m3/s] | 0.57244 |
278 | AirLoopHVAC | AIRLOOP DATACENTER TOP | User Heating Air Flow Ratio [] | 1.00000 |
279 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Calculated Heating Air Flow Ratio [] | 1.00000 |
280 | AirLoopHVAC | VAV_BOT WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 11.65570 |
281 | AirLoopHVAC | VAV_MID WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 107.83186 |
282 | AirLoopHVAC | VAV_TOP WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 12.30079 |
283 | AirLoopHVAC | CAV_BAS | Design Supply Air Flow Rate [m3/s] | 6.81911 |
284 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Design Supply Air Flow Rate [m3/s] | 24.53890 |
285 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Design Supply Air Flow Rate [m3/s] | 0.58537 |
286 | AirLoopHVAC | AIRLOOP DATACENTER MID | Design Supply Air Flow Rate [m3/s] | 5.62967 |
287 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Design Supply Air Flow Rate [m3/s] | 0.57244 |
288 | Controller:OutdoorAir | VAV_BOT WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 11.65570 |
289 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Inlet Air Temperature [C] | 26.04686 |
290 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
291 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Outlet Air Temperature [C] | 10.68118 |
292 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 7.08318E-003 |
293 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 7.00000E-003 |
294 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Coil Load [W] | 194585.28567 |
295 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 8.27811E-003 |
296 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 11.65570 |
297 | Coil:Heating:Water | VAV_BOT WITH REHEAT HEATING COIL | Design Size Rated Capacity [W] | 101691.05047 |
298 | Coil:Heating:Water | VAV_BOT WITH REHEAT HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 8.89638E-004 |
299 | Coil:Heating:Water | VAV_BOT WITH REHEAT HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 1578.76896 |
300 | Fan:VariableVolume | VAV_BOT WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 11.65570 |
301 | Controller:WaterCoil | VAV_BOT WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 8.27811E-003 |
302 | Controller:WaterCoil | VAV_BOT WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 5.75241E-005 |
303 | Controller:WaterCoil | VAV_BOT WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 8.89638E-004 |
304 | Controller:OutdoorAir | VAV_MID WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 107.83186 |
305 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Inlet Air Temperature [C] | 26.21365 |
306 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
307 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Outlet Air Temperature [C] | 10.68116 |
308 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 7.07663E-003 |
309 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 7.00000E-003 |
310 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Coil Load [W] | 1817578.77258 |
311 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 7.73240E-002 |
312 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 107.83186 |
313 | Coil:Heating:Water | VAV_MID WITH REHEAT HEATING COIL | Design Size Rated Capacity [W] | 1044136.00216 |
314 | Coil:Heating:Water | VAV_MID WITH REHEAT HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 9.13456E-003 |
315 | Coil:Heating:Water | VAV_MID WITH REHEAT HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 15812.22590 |
316 | Fan:VariableVolume | VAV_MID WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 107.83186 |
317 | Controller:WaterCoil | VAV_MID WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 7.73240E-002 |
318 | Controller:WaterCoil | VAV_MID WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 6.15838E-006 |
319 | Controller:WaterCoil | VAV_MID WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 9.13456E-003 |
320 | Controller:OutdoorAir | VAV_TOP WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 12.30079 |
321 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Inlet Air Temperature [C] | 25.94519 |
322 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
323 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Outlet Air Temperature [C] | 10.68114 |
324 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 7.07283E-003 |
325 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 7.00000E-003 |
326 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Coil Load [W] | 203672.51240 |
327 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 8.66470E-003 |
328 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 12.30079 |
329 | Coil:Heating:Water | VAV_TOP WITH REHEAT HEATING COIL | Design Size Rated Capacity [W] | 102308.45534 |
330 | Coil:Heating:Water | VAV_TOP WITH REHEAT HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 8.95039E-004 |
331 | Coil:Heating:Water | VAV_TOP WITH REHEAT HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 1597.67593 |
332 | Fan:VariableVolume | VAV_TOP WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 12.30079 |
333 | Controller:WaterCoil | VAV_TOP WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 8.66470E-003 |
334 | Controller:WaterCoil | VAV_TOP WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 5.49575E-005 |
335 | Controller:WaterCoil | VAV_TOP WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 8.95039E-004 |
336 | Controller:OutdoorAir | CAV_BAS_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 6.81911 |
337 | Controller:OutdoorAir | CAV_BAS_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.20016 |
338 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Inlet Air Temperature [C] | 25.70009 |
339 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
340 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Outlet Air Temperature [C] | 11.22902 |
341 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 7.23461E-003 |
342 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 7.00000E-003 |
343 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Coil Load [W] | 110073.14104 |
344 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 4.68277E-003 |
345 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 6.81911 |
346 | Coil:Heating:Water | CAV_BAS HEATING COIL | Design Size Rated Capacity [W] | 323708.58056 |
347 | Coil:Heating:Water | CAV_BAS HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.83194E-003 |
348 | Coil:Heating:Water | CAV_BAS HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 6941.24521 |
349 | Fan:ConstantVolume | CAV_BAS FAN | Design Size Maximum Flow Rate [m3/s] | 6.81911 |
350 | Controller:WaterCoil | CAV_BAS_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 4.68277E-003 |
351 | Controller:WaterCoil | CAV_BAS_COOLC_CONTROLLER | Controller Convergence Tolerance | 1.01690E-004 |
352 | Controller:WaterCoil | CAV_BAS_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 2.83194E-003 |
353 | Controller:OutdoorAir | AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 24.53890 |
354 | Controller:OutdoorAir | AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.33839 |
355 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 24.53890 |
356 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Rated Total Cooling Capacity [W] | 466437.89347 |
357 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Rated Sensible Cooling Capacity [W] | 262502.93893 |
358 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Rated Water Flow Rate [m3/s] | 1.14230E-002 |
359 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 24.53890 |
360 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 24.53890 |
361 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 24.53890 |
362 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 24.53890 |
363 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Nominal Heating Capacity [W] | 466437.89347 |
364 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 466437.89347 |
365 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 24207.99248 |
366 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
367 | Fan:OnOff | AIRLOOP DATACENTER BASEMENT SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 24.53890 |
368 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 24.53890 |
369 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT HEATING COIL | Design Size Rated Heating Capacity [W] | 466437.89347 |
370 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT HEATING COIL | Design Size Rated Water Flow Rate [m3/s] | 1.14230E-002 |
371 | Coil:Heating:Electric | AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 24207.99248 |
372 | Humidifier:Steam:Electric | DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | Design Size Nominal Capacity Volume [m3/s] | 1.91079E-004 |
373 | Humidifier:Steam:Electric | DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | User-Specified Nominal Capacity Volume [m3/s] | 3.72000E-005 |
374 | Humidifier:Steam:Electric | DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | Design Size Rated Power [W] | 96450.69782 |
375 | Humidifier:Steam:Electric | DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | User-Specified Rated Power [W] | 100000.00000 |
376 | Controller:OutdoorAir | AIRLOOP DATACENTER BOT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.58537 |
377 | Controller:OutdoorAir | AIRLOOP DATACENTER BOT_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.56323E-002 |
378 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.58537 |
379 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT COOLING COIL | Design Size Rated Total Cooling Capacity [W] | 10807.08699 |
380 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT COOLING COIL | Design Size Rated Sensible Cooling Capacity [W] | 6147.88501 |
381 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT COOLING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.64665E-004 |
382 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 0.58537 |
383 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 0.58537 |
384 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 0.58537 |
385 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 0.58537 |
386 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Nominal Heating Capacity [W] | 10807.08699 |
387 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 10807.08699 |
388 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 1118.30896 |
389 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
390 | Fan:OnOff | AIRLOOP DATACENTER BOT SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.58537 |
391 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.58537 |
392 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT HEATING COIL | Design Size Rated Heating Capacity [W] | 10807.08699 |
393 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT HEATING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.64665E-004 |
394 | Coil:Heating:Electric | AIRLOOP DATACENTER BOT_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 1118.30896 |
395 | Controller:OutdoorAir | AIRLOOP DATACENTER MID_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 5.62967 |
396 | Controller:OutdoorAir | AIRLOOP DATACENTER MID_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.15632 |
397 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 5.62967 |
398 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID COOLING COIL | Design Size Rated Total Cooling Capacity [W] | 103961.64942 |
399 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID COOLING COIL | Design Size Rated Sensible Cooling Capacity [W] | 59130.96952 |
400 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID COOLING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.54601E-003 |
401 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 5.62967 |
402 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 5.62967 |
403 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 5.62967 |
404 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 5.62967 |
405 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Nominal Heating Capacity [W] | 103961.64942 |
406 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 103961.64942 |
407 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 11183.08965 |
408 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
409 | Fan:OnOff | AIRLOOP DATACENTER MID SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 5.62967 |
410 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 5.62967 |
411 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID HEATING COIL | Design Size Rated Heating Capacity [W] | 103961.64942 |
412 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID HEATING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.54601E-003 |
413 | Coil:Heating:Electric | AIRLOOP DATACENTER MID_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 11183.08965 |
414 | Controller:OutdoorAir | AIRLOOP DATACENTER TOP_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.57244 |
415 | Controller:OutdoorAir | AIRLOOP DATACENTER TOP_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.56323E-002 |
416 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.57244 |
417 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP COOLING COIL | Design Size Rated Total Cooling Capacity [W] | 10570.01505 |
418 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP COOLING COIL | Design Size Rated Sensible Cooling Capacity [W] | 6012.38874 |
419 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP COOLING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.58859E-004 |
420 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 0.57244 |
421 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 0.57244 |
422 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 0.57244 |
423 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 0.57244 |
424 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Nominal Heating Capacity [W] | 10570.01505 |
425 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 10570.01505 |
426 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 1118.30896 |
427 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
428 | Fan:OnOff | AIRLOOP DATACENTER TOP SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.57244 |
429 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.57244 |
430 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP HEATING COIL | Design Size Rated Heating Capacity [W] | 10570.01505 |
431 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP HEATING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.58859E-004 |
432 | Coil:Heating:Electric | AIRLOOP DATACENTER TOP_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 1118.30896 |
433 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Flow Rate [m3/s] | 9.89496E-002 |
434 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Power Consumption [W] | 16155.44218 |
435 | PlantLoop | COOLSYS1_DEMAND | Maximum Loop Flow Rate [m3/s] | 9.89496E-002 |
436 | PlantLoop | COOLSYS1_DEMAND | Plant Loop Volume [m3] | 11.87395 |
437 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Loop Supply Side Design Fluid Flow Rate [m3/s] | 9.89496E-002 |
438 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Loop Demand Side Design Fluid Flow Rate [m3/s] | 9.89496E-002 |
439 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Heat Exchanger U-Factor Times Area Value [W/C] | 415341.01994 |
440 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Loop-to-loop Temperature Difference Used to Size Heat Exchanger U-Factor Times Area Value [C] | 5.60000 |
441 | PlantLoop | HEATSYS1 | Maximum Loop Flow Rate [m3/s] | 3.01192E-002 |
442 | PlantLoop | HEATSYS1 | Plant Loop Volume [m3] | 3.61430 |
443 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Flow Rate [m3/s] | 3.01192E-002 |
444 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Power Consumption [W] | 9070.56742 |
445 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Minimum Flow Rate [m3/s] | 0.00000 |
446 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Nominal Capacity [W] | 3442804.65879 |
447 | Boiler:HotWater | HEATSYS1 BOILER | User-Specified Nominal Capacity [W] | 3442804.66000 |
448 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Design Water Flow Rate [m3/s] | 3.01192E-002 |
449 | PlantLoop | COOLSYS1_SUPPLY | Maximum Loop Flow Rate [m3/s] | 9.89496E-002 |
450 | PlantLoop | COOLSYS1_SUPPLY | Plant Loop Volume [m3] | 11.87395 |
451 | Pump:ConstantSpeed | COOLSYS1 CHILLER1 PUMP | Design Flow Rate [m3/s] | 4.94748E-002 |
452 | Pump:ConstantSpeed | COOLSYS1 CHILLER1 PUMP | Design Power Consumption [W] | 5592.47872 |
453 | Pump:ConstantSpeed | COOLSYS1 CHILLER2 PUMP | Design Flow Rate [m3/s] | 4.94748E-002 |
454 | Pump:ConstantSpeed | COOLSYS1 CHILLER2 PUMP | Design Power Consumption [W] | 5592.47872 |
455 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | Design Size Reference Chilled Water Flow Rate [m3/s] | 9.89496E-002 |
456 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | User-Specified Reference Chilled Water Flow Rate [m3/s] | 4.98509E-002 |
457 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | Design Size Reference Capacity [W] | 1174674.22862 |
458 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | User-Specified Reference Capacity [W] | 1180245.77000 |
459 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | Design Size Reference Condenser Water Flow Rate [m3/s] | 5.84060E-002 |
460 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | Design Size Reference Chilled Water Flow Rate [m3/s] | 9.89496E-002 |
461 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | User-Specified Reference Chilled Water Flow Rate [m3/s] | 4.98509E-002 |
462 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | Design Size Reference Capacity [W] | 1174674.22862 |
463 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | User-Specified Reference Capacity [W] | 1180245.77000 |
464 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | Design Size Reference Condenser Water Flow Rate [m3/s] | 5.84060E-002 |
465 | PlantLoop | SINGLE WATER PLANT LOOP | Maximum Loop Flow Rate [m3/s] | 1.44926E-002 |
466 | PlantLoop | SINGLE WATER PLANT LOOP | Plant Loop Volume [m3] | 1.73911 |
467 | Pump:ConstantSpeed | PLANT CIRC PUMP | Design Flow Rate [m3/s] | 1.44926E-002 |
468 | Pump:ConstantSpeed | PLANT CIRC PUMP | Design Power Consumption [W] | 3696.33058 |
469 | FluidCooler:TwoSpeed | CENTRAL TOWER | Design Water Flow Rate [m3/s] | 1.44926E-002 |
470 | FluidCooler:TwoSpeed | CENTRAL TOWER | Air Flow Rate at High Fan Speed [m3/s] | 139666.46671 |
471 | FluidCooler:TwoSpeed | CENTRAL TOWER | Fluid cooler UA value at high fan speed based on nominal capacity input [W/K] | 55299.26960 |
472 | FluidCooler:TwoSpeed | CENTRAL TOWER | Air Flow Rate at Low Fan Speed [m3/s] | 69833.23335 |
473 | FluidCooler:TwoSpeed | CENTRAL TOWER | Fan Power at Low Fan Speed [W] | 7879.72339 |
474 | FluidCooler:TwoSpeed | CENTRAL TOWER | U-factor Times Area Value at Low Fan Speed [W/C] | 20993.03634 |
475 | Boiler:HotWater | CENTRAL BOILER | Design Size Nominal Capacity [W] | 596969.71866 |
476 | Boiler:HotWater | CENTRAL BOILER | User-Specified Nominal Capacity [W] | 584202.86000 |
477 | Boiler:HotWater | CENTRAL BOILER | Design Size Design Water Flow Rate [m3/s] | 1.44926E-002 |
478 | PlantLoop | SWHSYS1 | Maximum Loop Flow Rate [m3/s] | 4.40000E-004 |
479 | PlantLoop | SWHSYS1 | Plant Loop Volume [m3] | 5.28000E-002 |
480 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Flow Rate [m3/s] | 4.40000E-004 |
481 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Power Consumption [W] | 56.20530 |
482 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | Use Side Design Flow Rate [m3/s] | 4.40000E-004 |
483 | CondenserLoop | TOWERWATERSYS | Maximum Loop Flow Rate [m3/s] | 0.11681 |
484 | CondenserLoop | TOWERWATERSYS | Condenser Loop Volume [m3] | 14.01744 |
485 | HeaderedPumps:VariableSpeed | TOWERWATERSYS PUMP | Design Flow Rate [m3/s] | 0.11681 |
486 | HeaderedPumps:VariableSpeed | TOWERWATERSYS PUMP | Design Power Consumption [W] | 28920.06123 |
487 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Design Air Flow Rate [m3/s] | 51.61729 |
488 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Nominal Capacity [W] | 1402076.59805 |
489 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Air Flow Rate in free convection regime [m3/s] | 10.32346 |
490 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Tower capacity in free convection regime at design conditions [W] | 175259.57476 |
491 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Design Air Flow Rate [m3/s] | 51.61729 |
492 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Nominal Capacity [W] | 1402076.59805 |
493 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Air Flow Rate in free convection regime [m3/s] | 10.32346 |
494 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Tower capacity in free convection regime at design conditions [W] | 175259.57476 |
495 | PlantEquipmentOperation:ComponentSetPoint | WSHPPLANT OPERATION SCHEME | Design Water Flow Rate [m3/s] Equipment # 47 | 6.06650E-002 |
496 | PlantEquipmentOperation:ComponentSetPoint | WSHPPLANT OPERATION SCHEME | Design Water Flow Rate [m3/s] Equipment # 47 | 6.06650E-002 |
Component Type | Name | Nominal Total Capacity {W} | |
1 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | 24454.28 |
2 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | 488267.08 |
3 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | 105821.88 |
4 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | 20497.98 |
5 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | 14025.83 |
6 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | 22455.23 |
7 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | 11942.21 |
8 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | 289043.43 |
9 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | 191833.39 |
10 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | 293493.70 |
11 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | 189392.58 |
12 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | 36487.65 |
13 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | 24087.34 |
14 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | 36978.99 |
15 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | 24102.13 |
16 | Coil:Heating:Water | VAV_BOT WITH REHEAT HEATING COIL | 69087.22 |
17 | Coil:Heating:Water | VAV_MID WITH REHEAT HEATING COIL | 688507.71 |
18 | Coil:Heating:Water | VAV_TOP WITH REHEAT HEATING COIL | 70434.50 |
19 | Coil:Heating:Water | CAV_BAS HEATING COIL | 245432.64 |
Component Type | Name | Nominal Total Capacity {W} | Nominal Sensible Capacity {W} | Nominal Latent Capacity {W} | Nominal Sensible Heat Ratio | Nominal Coil UA Value {W/C} | Nominal Coil Surface Area {m2} | |
1 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | 328097.05 | 201626.38 | 126470.67 | 0.61 | 65619.45 | 665.55 |
2 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | 3043069.59 | 1868368.76 | 1174700.82 | 0.61 | 603136.28 | 6117.34 |
3 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | 345420.29 | 212455.27 | 132965.02 | 0.62 | 69556.50 | 705.48 |
4 | Coil:Cooling:Water | CAV_BAS COOLING COIL | 185004.23 | 115151.46 | 69852.76 | 0.62 | 33859.13 | 343.42 |
Component Type | Component Name | IPLV in SI Units {W/W} | IPLV in IP Units {Btu/W-h} | |
1 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | 6.84 | 23.33 |
2 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | 6.84 | 23.33 |
Zone Name | # Surfaces | |
1 | BASEMENT | 10 |
2 | CORE_BOTTOM | 8 |
3 | CORE_MID | 7 |
4 | CORE_TOP | 7 |
5 | PERIMETER_BOT_ZN_3 | 18 |
6 | PERIMETER_BOT_ZN_2 | 12 |
7 | PERIMETER_BOT_ZN_1 | 18 |
8 | PERIMETER_BOT_ZN_4 | 12 |
9 | PERIMETER_MID_ZN_3 | 9 |
10 | PERIMETER_MID_ZN_2 | 8 |
11 | PERIMETER_MID_ZN_1 | 9 |
12 | PERIMETER_MID_ZN_4 | 8 |
13 | PERIMETER_TOP_ZN_3 | 9 |
14 | PERIMETER_TOP_ZN_2 | 8 |
15 | PERIMETER_TOP_ZN_1 | 9 |
16 | PERIMETER_TOP_ZN_4 | 8 |
17 | GROUNDFLOOR_PLENUM | 11 |
18 | MIDFLOOR_PLENUM | 11 |
19 | TOPFLOOR_PLENUM | 11 |
20 | DATACENTER_BOT_ZN_6 | 6 |
21 | DATACENTER_MID_ZN_6 | 6 |
22 | DATACENTER_TOP_ZN_6 | 6 |
23 | DATACENTER_BASEMENT_ZN_6 | 10 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | BASEMENT_WALL_EAST | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_EAST_CFACTOR | 0.354 | 0.336 | 118.87 | 118.87 | 118.87 | 90.00 | 90.00 | 48.74 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | BASEMENT_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_SOUTH_CFACTOR | 0.354 | 0.336 | 139.09 | 139.09 | 139.09 | 180.00 | 90.00 | 57.03 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
3 | BASEMENT_WALL_NORTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_NORTH_CFACTOR | 0.354 | 0.336 | 139.09 | 139.09 | 139.09 | 0.00 | 90.00 | 57.03 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | BASEMENT_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.87 | 118.87 | 118.87 | 270.00 | 90.00 | 48.74 | 2.44 | 0.00 | DATACENTER_BASEMENT_ZN_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
5 | BASEMENT_FLOOR | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 2779.43 | 2779.43 | 2779.43 | 0.00 | 180.00 | 57.03 | 48.74 | 0.00 | BASEMENT_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
6 | PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | PERIMETER_BOT_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
7 | PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 250.34 | 250.34 | 250.34 | 180.00 | 0.00 | 57.03 | 4.57 | 0.00 | PERIMETER_BOT_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
8 | CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 2076.77 | 2076.77 | 2076.77 | 180.00 | 0.00 | 52.45 | 39.59 | 0.00 | CORE_BOT_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
9 | PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 250.34 | 250.34 | 250.34 | 180.00 | 0.00 | 52.45 | 4.57 | 0.00 | PERIMETER_BOT_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
10 | BASEMENT_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 7126.21 | 7126.21 | 7126.21 | 0.00 | 90.00 | 7126.21 | 1.00 | 0.00 | BASEMENT_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
11 | CORE_BOT_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
12 | CORE_BOT_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
13 | CORE_BOT_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
14 | CORE_BOT_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
15 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 419.30 | 419.30 | 419.30 | 0.00 | 180.00 | 10.59 | 39.59 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
16 | CORE_BOT_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 2076.82 | 2076.82 | 2076.82 | 0.00 | 180.00 | 52.46 | 39.59 | 0.00 | CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
17 | CORE_BOT_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 2496.12 | 2496.12 | 2496.12 | 180.00 | 0.00 | 63.05 | 39.59 | 0.00 | iz-CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
18 | CORE_BOTTOM_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 5064.65 | 5064.65 | 5064.65 | 0.00 | 90.00 | 5064.65 | 1.00 | 0.00 | CORE_BOTTOM_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
19 | CORE_MID_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
20 | CORE_MID_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
21 | CORE_MID_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
22 | CORE_MID_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
23 | CORE_MID_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_MID_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
24 | CORE_MID_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 2496.12 | 2496.12 | 2496.12 | 180.00 | 0.00 | 63.05 | 39.59 | 0.00 | iz-CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
25 | CORE_MID_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 5064.65 | 5064.65 | 5064.65 | 0.00 | 90.00 | 5064.65 | 1.00 | 0.00 | CORE_MID_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
26 | CORE_TOP_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
27 | CORE_TOP_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
28 | CORE_TOP_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
29 | CORE_TOP_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
30 | CORE_TOP_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_TOP_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
31 | CORE_TOP_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 2496.12 | 2496.12 | 2496.12 | 180.00 | 0.00 | 63.05 | 39.59 | 0.00 | iz-CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
32 | CORE_TOP_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 5064.65 | 5064.65 | 5064.65 | 0.00 | 90.00 | 5064.65 | 1.00 | 0.00 | CORE_TOP_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
33 | PERIMETER_BOT_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.895 | 0.789 | 76.91 | 200.61 | 76.91 | 0.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
34 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.419_SHGC_NORTH_0.4 | N/A | 2.381 | No | 23.18 | 23.18 | 23.18 | 0.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
35 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.419_SHGC_NORTH_0.4 | N/A | 2.381 | No | 23.18 | 23.18 | 23.18 | 0.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
36 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.419_SHGC_NORTH_0.4 | N/A | 2.381 | No | 23.18 | 23.18 | 23.18 | 0.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
37 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.419_SHGC_NORTH_0.4 | N/A | 2.381 | No | 23.18 | 23.18 | 23.18 | 0.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
38 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.419_SHGC_NORTH_0.4 | N/A | 2.381 | No | 23.18 | 23.18 | 23.18 | 0.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
39 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.839 | 2.839 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
40 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.839 | 2.839 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
41 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.839 | 2.839 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
42 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.839 | 2.839 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
43 | PERIMETER_BOT_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
44 | CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
45 | PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
46 | DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
47 | PERIMETER_BOT_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 250.34 | 250.34 | 250.34 | 0.00 | 180.00 | 52.46 | 6.47 | 0.00 | PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
48 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 63.07 | 63.07 | 63.07 | 0.00 | 180.00 | 11.51 | 4.57 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
49 | PERIMETER_BOT_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.41 | 313.41 | 313.41 | 180.00 | 0.00 | 63.96 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
50 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.83 | 626.83 | 626.83 | 0.00 | 90.00 | 626.83 | 1.00 | 0.00 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
51 | PERIMETER_BOT_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.895 | 0.789 | 52.57 | 133.74 | 52.57 | 90.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
52 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.419_SHGC_EAST_0.4 | N/A | 2.381 | No | 25.75 | 25.75 | 25.75 | 90.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
53 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.419_SHGC_EAST_0.4 | N/A | 2.381 | No | 25.75 | 25.75 | 25.75 | 90.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
54 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.419_SHGC_EAST_0.4 | N/A | 2.381 | No | 25.75 | 25.75 | 25.75 | 90.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
55 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | Door | PERIMETER_BOT_ZN_2_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.839 | 2.839 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
56 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | Door | PERIMETER_BOT_ZN_2_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.839 | 2.839 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
57 | PERIMETER_BOT_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
58 | CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
59 | PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
60 | PERIMETER_BOT_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
61 | PERIMETER_BOT_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | iz-PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
62 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
63 | PERIMETER_BOT_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.895 | 0.789 | 76.91 | 200.61 | 76.91 | 180.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
64 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.419_SHGC_SOUTH_0.4 | N/A | 2.381 | No | 23.18 | 23.18 | 23.18 | 180.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
65 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.419_SHGC_SOUTH_0.4 | N/A | 2.381 | No | 23.18 | 23.18 | 23.18 | 180.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
66 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.419_SHGC_SOUTH_0.4 | N/A | 2.381 | No | 23.18 | 23.18 | 23.18 | 180.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
67 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.419_SHGC_SOUTH_0.4 | N/A | 2.381 | No | 23.18 | 23.18 | 23.18 | 180.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
68 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.419_SHGC_SOUTH_0.4 | N/A | 2.381 | No | 23.18 | 23.18 | 23.18 | 180.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
69 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.839 | 2.839 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
70 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.839 | 2.839 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
71 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.839 | 2.839 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
72 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.839 | 2.839 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
73 | PERIMETER_BOT_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
74 | DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
75 | PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
76 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
77 | DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 63.07 | 63.07 | 63.07 | 0.00 | 180.00 | 16.08 | 4.57 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
78 | PERIMETER_BOT_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 250.35 | 250.35 | 250.35 | 0.00 | 180.00 | 57.03 | 6.47 | 0.00 | PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
79 | PERIMETER_BOT_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.42 | 313.42 | 313.42 | 180.00 | 0.00 | 73.11 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
80 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.84 | 626.84 | 626.84 | 0.00 | 90.00 | 626.84 | 1.00 | 0.00 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
81 | PERIMETER_BOT_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.895 | 0.789 | 52.57 | 133.74 | 52.57 | 270.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
82 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.419_SHGC_WEST_0.4 | N/A | 2.381 | No | 25.75 | 25.75 | 25.75 | 270.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
83 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.419_SHGC_WEST_0.4 | N/A | 2.381 | No | 25.75 | 25.75 | 25.75 | 270.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
84 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.419_SHGC_WEST_0.4 | N/A | 2.381 | No | 25.75 | 25.75 | 25.75 | 270.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
85 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | Door | PERIMETER_BOT_ZN_4_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.839 | 2.839 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
86 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | Door | PERIMETER_BOT_ZN_4_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.839 | 2.839 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
87 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
88 | DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
89 | PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
90 | PERIMETER_BOT_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
91 | PERIMETER_BOT_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | iz-PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
92 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
93 | PERIMETER_MID_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.851 | 0.755 | 84.71 | 200.61 | 84.71 | 0.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
94 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_MID_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.419_SHGC_NORTH_0.4 | N/A | 2.381 | No | 115.90 | 115.90 | 115.90 | 0.00 | 90.00 | 73.11 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
95 | PERIMETER_MID_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
96 | CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
97 | PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
98 | DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
99 | PERIMETER_MID_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
100 | PERIMETER_MID_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.41 | 313.41 | 313.41 | 180.00 | 0.00 | 63.96 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
101 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.83 | 626.83 | 626.83 | 0.00 | 90.00 | 626.83 | 1.00 | 0.00 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
102 | PERIMETER_MID_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.851 | 0.755 | 56.47 | 133.74 | 56.47 | 90.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
103 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_MID_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.419_SHGC_EAST_0.4 | N/A | 2.381 | No | 77.26 | 77.26 | 77.26 | 90.00 | 90.00 | 48.74 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
104 | PERIMETER_MID_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
105 | CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
106 | PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
107 | PERIMETER_MID_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_MID_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
108 | PERIMETER_MID_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | iz-PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
109 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
110 | PERIMETER_MID_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
111 | PERIMETER_MID_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.851 | 0.755 | 84.71 | 200.61 | 84.71 | 180.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
112 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_MID_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.419_SHGC_SOUTH_0.4 | N/A | 2.381 | No | 115.90 | 115.90 | 115.90 | 180.00 | 90.00 | 73.11 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
113 | DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
114 | PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
115 | CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
116 | PERIMETER_MID_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
117 | PERIMETER_MID_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.42 | 313.42 | 313.42 | 180.00 | 0.00 | 73.11 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
118 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.84 | 626.84 | 626.84 | 0.00 | 90.00 | 626.84 | 1.00 | 0.00 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
119 | PERIMETER_MID_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.851 | 0.755 | 56.47 | 133.74 | 56.47 | 270.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
120 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_MID_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.419_SHGC_WEST_0.4 | N/A | 2.381 | No | 77.26 | 77.26 | 77.26 | 270.00 | 90.00 | 48.74 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
121 | PERIMETER_MID_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
122 | DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
123 | PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
124 | PERIMETER_MID_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_MID_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
125 | PERIMETER_MID_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | iz-PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
126 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
127 | PERIMETER_TOP_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.077 | 0.928 | 84.71 | 200.61 | 84.71 | 0.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
128 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_TOP_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.419_SHGC_NORTH_0.4 | N/A | 2.381 | No | 115.90 | 115.90 | 115.90 | 0.00 | 90.00 | 73.11 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
129 | PERIMETER_TOP_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
130 | CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
131 | PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
132 | DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
133 | PERIMETER_TOP_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_TOP_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
134 | PERIMETER_TOP_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.41 | 313.41 | 313.41 | 180.00 | 0.00 | 63.96 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
135 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.83 | 626.83 | 626.83 | 0.00 | 90.00 | 626.83 | 1.00 | 0.00 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
136 | PERIMETER_TOP_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.077 | 0.928 | 56.47 | 133.74 | 56.47 | 90.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
137 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_TOP_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.419_SHGC_EAST_0.4 | N/A | 2.381 | No | 77.26 | 77.26 | 77.26 | 90.00 | 90.00 | 48.74 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
138 | PERIMETER_TOP_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
139 | CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
140 | INT-PER3S-NE-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | INT-PER3S-NE | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
141 | PERIMETER_TOP_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_TOP_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
142 | PERIMETER_TOP_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | iz-PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
143 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
144 | PERIMETER_TOP_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.077 | 0.928 | 84.71 | 200.61 | 84.71 | 180.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
145 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_TOP_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.419_SHGC_SOUTH_0.4 | N/A | 2.381 | No | 115.90 | 115.90 | 115.90 | 180.00 | 90.00 | 73.11 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
146 | INT-PER3S-NE | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | INT-PER3S-NE-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
147 | DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
148 | PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
149 | CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
150 | PERIMETER_TOP_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_TOP_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
151 | PERIMETER_TOP_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.42 | 313.42 | 313.42 | 180.00 | 0.00 | 73.11 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
152 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.84 | 626.84 | 626.84 | 0.00 | 90.00 | 626.84 | 1.00 | 0.00 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
153 | PERIMETER_TOP_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.077 | 0.928 | 56.47 | 133.74 | 56.47 | 270.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
154 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_TOP_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.419_SHGC_WEST_0.4 | N/A | 2.381 | No | 77.26 | 77.26 | 77.26 | 270.00 | 90.00 | 48.74 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
155 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
156 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
157 | PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
158 | PERIMETER_TOP_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_TOP_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
159 | PERIMETER_TOP_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | iz-PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
160 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
161 | GROUNDFLOOR_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.895 | 0.789 | 89.13 | 89.13 | 89.13 | 0.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
162 | GROUNDFLOOR_PLENUM_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.895 | 0.789 | 59.42 | 59.42 | 59.42 | 270.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
163 | GROUNDFLOOR_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.895 | 0.789 | 89.13 | 89.13 | 89.13 | 180.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
164 | GROUNDFLOOR_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.895 | 0.789 | 59.42 | 59.42 | 59.42 | 90.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
165 | iz-CORE_BOT_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
166 | iz-PERIMETER_BOT_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
167 | iz-PERIMETER_BOT_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
168 | iz-PERIMETER_BOT_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
169 | iz-PERIMETER_BOT_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
170 | iz-DATACENTER_BOT_ZN_6_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_BOT_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
171 | GROUNDFLOOR_PLENUM_CEILING | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 3563.11 | 3563.11 | 3563.11 | 180.00 | 0.00 | 73.11 | 48.74 | 0.00 | GROUNDFLOOR_PLENUM_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
172 | MIDFLOOR_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.851 | 0.755 | 89.13 | 89.13 | 89.13 | 0.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
173 | MIDFLOOR_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.851 | 0.755 | 59.42 | 59.42 | 59.42 | 270.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
174 | MIDFLOOR_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.851 | 0.755 | 89.13 | 89.13 | 89.13 | 180.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
175 | MIDFLOOR_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.851 | 0.755 | 59.42 | 59.42 | 59.42 | 90.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
176 | iz-CORE_MID_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
177 | iz-PERIMETER_MID_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
178 | iz-PERIMETER_MID_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
179 | iz-PERIMETER_MID_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
180 | iz-PERIMETER_MID_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
181 | iz-DATACENTER_MID_ZN_6_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_MID_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
182 | MIDFLOOR_PLENUM_CEILING | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 3563.11 | 3563.11 | 3563.11 | 180.00 | 0.00 | 73.11 | 48.74 | 0.00 | MIDFLOOR_PLENUM_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
183 | TOPFLOOR_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.077 | 0.928 | 89.13 | 89.13 | 89.13 | 180.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
184 | TOPFLOOR_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.077 | 0.928 | 59.42 | 59.42 | 59.42 | 90.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
185 | TOPFLOOR_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.077 | 0.928 | 59.42 | 59.42 | 59.42 | 270.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
186 | TOPFLOOR_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.077 | 0.928 | 89.13 | 89.13 | 89.13 | 0.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
187 | iz-CORE_TOP_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
188 | iz-PERIMETER_TOP_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
189 | iz-PERIMETER_TOP_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
190 | iz-PERIMETER_TOP_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
191 | iz-PERIMETER_TOP_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
192 | iz-DATACENTER_TOP_ZN_6_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_TOP_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
193 | BUILDING_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 3563.11 | 3563.11 | 3563.11 | 180.00 | 0.00 | 73.11 | 48.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
194 | DATACENTER_BOT_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
195 | DATACENTER_BOT_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
196 | DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
197 | DATACENTER_BOT_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
198 | DATACENTER_BOT_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
199 | DATACENTER_BOT_ZN_6_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | iz-DATACENTER_BOT_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
200 | DATACENTER_MID_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
201 | DATACENTER_MID_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
202 | DATACENTER_MID_ZN_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
203 | DATACENTER_MID_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
204 | DATACENTER_MID_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_MID_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
205 | DATACENTER_MID_ZN_6_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | iz-DATACENTER_MID_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
206 | DATACENTER_TOP_ZN_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
207 | DATACENTER_TOP_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
208 | DATACENTER_TOP_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
209 | DATACENTER_TOP_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
210 | DATACENTER_TOP_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_TOP_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
211 | DATACENTER_TOP_ZN_6_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | iz-DATACENTER_TOP_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
212 | DATACENTER_BASEMENT_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR | 0.354 | 0.336 | 39.22 | 39.22 | 39.22 | 0.00 | 90.00 | 16.08 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
213 | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR | 0.354 | 0.336 | 39.22 | 39.22 | 39.22 | 180.00 | 90.00 | 16.08 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
214 | DATACENTER_BASEMENT_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR | 0.354 | 0.336 | 118.87 | 118.87 | 118.87 | 270.00 | 90.00 | 48.74 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
215 | DATACENTER_BASEMENT_ZN_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.87 | 118.87 | 118.87 | 90.00 | 90.00 | 48.74 | 2.44 | 0.00 | BASEMENT_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
216 | DATACENTER_BASEMENT_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 783.68 | 783.68 | 783.68 | 0.00 | 180.00 | 16.08 | 48.74 | 0.00 | DATACENTER_BASEMENT_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
217 | DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | DATACENTER_BOT_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
218 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 419.35 | 419.35 | 419.35 | 180.00 | 0.00 | 10.59 | 39.59 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
219 | PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | PERIMETER_BOT_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
220 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 63.08 | 63.08 | 63.08 | 180.00 | 0.00 | 16.08 | 6.47 | 0.00 | DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
221 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 63.07 | 63.07 | 63.07 | 180.00 | 0.00 | 11.51 | 6.47 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | BASEMENT | RunPeriod: RUNPERIOD 1 | 0.2284434347 | 0.1918042869 | Pass | Pass | 2.4574607999 | 13.6409874921 | Pass | Pass |
2 | CORE_BOTTOM | RunPeriod: RUNPERIOD 1 | 6.2995037480E-002 | 0.1451341063 | Pass | Pass | 7.7054723230E-002 | 0.2666814641 | Pass | Pass |
3 | CORE_MID | RunPeriod: RUNPERIOD 1 | 7.1076394341E-002 | 8.0176874940E-002 | Pass | Pass | 0.2023766563 | 0.3964366777 | Pass | Pass |
4 | CORE_TOP | RunPeriod: RUNPERIOD 1 | 4.1181842403E-002 | 3.2202471055E-002 | Pass | Pass | 0.4915993766 | 0.4890627621 | Pass | Pass |
5 | PERIMETER_BOT_ZN_3 | RunPeriod: RUNPERIOD 1 | 4.9042079981E-002 | 8.3355061249E-002 | Pass | Pass | 7.6522343087E-002 | 0.2644141315 | Pass | Pass |
6 | PERIMETER_BOT_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.1191453281 | 0.2052028386 | Pass | Pass | 7.8914603554E-002 | 0.2707357433 | Pass | Pass |
7 | PERIMETER_BOT_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.1945266806 | 0.3180208404 | Pass | Pass | 9.0826651571E-002 | 0.3072594090 | Pass | Pass |
8 | PERIMETER_BOT_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.1088552533 | 0.2193171098 | Pass | Pass | 7.7176768606E-002 | 0.2622648857 | Pass | Pass |
9 | PERIMETER_MID_ZN_3 | RunPeriod: RUNPERIOD 1 | 0.1044272071 | 0.1636314827 | Pass | Pass | 1.1709977008 | 5.1802011761 | Fail | Fail |
10 | PERIMETER_MID_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.1040141932 | 0.1367526534 | Pass | Pass | 1.0198368582 | 4.9093570775 | Fail | Pass |
11 | PERIMETER_MID_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.1860254496 | 0.1822625765 | Pass | Pass | 0.2495549848 | 0.5142906314 | Pass | Pass |
12 | PERIMETER_MID_ZN_4 | RunPeriod: RUNPERIOD 1 | 7.4156215375E-002 | 7.9686648327E-002 | Pass | Pass | 0.2695080965 | 0.5282673693 | Fail | Pass |
13 | PERIMETER_TOP_ZN_3 | RunPeriod: RUNPERIOD 1 | 0.3707543499 | 0.3773095304 | Pass | Pass | 7.8195085668 | 23.5866752734 | Pass | Pass |
14 | PERIMETER_TOP_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.2712586018 | 0.3651792840 | Pass | Pass | 7.1903300608 | 22.5661590567 | Pass | Pass |
15 | PERIMETER_TOP_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.2802829366 | 0.2769108997 | Pass | Pass | 1.6113199494 | 10.5500719000 | Pass | Pass |
16 | PERIMETER_TOP_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.2386581755 | 0.2933297070 | Pass | Pass | 6.2745131317 | 31.7466545000 | Pass | Pass |
17 | GROUNDFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 1.6360176852E-002 | 2.5606812247E-002 | Pass | Pass | 0.3459075519 | 1.5796655809 | Pass | Pass |
18 | MIDFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 2.4588472892E-002 | 2.8959098283E-002 | Pass | Pass | 0.2687208395 | 0.5342077411 | Pass | Fail |
19 | TOPFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 0.1116309456 | 8.2310273635E-002 | Pass | Pass | 0.5164437033 | 0.4906342006 | Pass | Pass |
20 | DATACENTER_BOT_ZN_6 | RunPeriod: RUNPERIOD 1 | 4.2670057160E-006 | 5.3850544407E-006 | Pass | Pass | 5.5371187690E-003 | 4.9528623021E-003 | Pass | Pass |
21 | DATACENTER_MID_ZN_6 | RunPeriod: RUNPERIOD 1 | 2.7678690400E-002 | 2.0761137552E-002 | Pass | Pass | 5.3309662283E-003 | 6.2517996652E-003 | Pass | Pass |
22 | DATACENTER_TOP_ZN_6 | RunPeriod: RUNPERIOD 1 | 3.2181550134E-002 | 2.5480305862E-002 | Pass | Pass | 6.1000679408E-003 | 6.9463610846E-003 | Pass | Pass |
23 | DATACENTER_BASEMENT_ZN_6 | RunPeriod: RUNPERIOD 1 | 4.5912772406E-005 | 3.3245798527E-005 | Pass | Pass | 5.8095351417E-005 | 1.0513439050E-004 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 08:43:39
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 6766.42 | 305.20 | 0.00 | 31326.38 | 10118.18 | 48516.17 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 08:43:39
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | -27.60 | 0.00 | -27.60 | Wetbulb [C] | 2.70 | 230.00 |
GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 33.40 | 16.00 | 16.30 | Wetbulb [C] | 4.90 | 240.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 0.00 | 0 | |||
Feb | 0.00 | 0 | |||
Mar | 0.00 | 0 | |||
Apr | 11.00 | 18 | |||
May | 24.00 | 14 | |||
Jun | 29.00 | 21 | |||
Jul | 6.00 | 9 | |||
Aug | 0.00 | 0 | |||
Sep | 0.00 | 0 | |||
Oct | 0.00 | 0 | |||
Nov | 0.00 | 0 | |||
Dec | 0.00 | 0 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 08:43:39
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BASEMENT_WALL_EAST | BASEMENT_WALL_EAST_CFACTOR | 1.00 | 0.340 | 0.354 | 118.87 | 118.87 | 90.00 | 90.00 | E |
BASEMENT_WALL_SOUTH | BASEMENT_WALL_SOUTH_CFACTOR | 1.00 | 0.340 | 0.354 | 139.09 | 139.09 | 180.00 | 90.00 | S |
BASEMENT_WALL_NORTH | BASEMENT_WALL_NORTH_CFACTOR | 1.00 | 0.340 | 0.354 | 139.09 | 139.09 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_3_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.789 | 0.895 | 200.61 | 76.91 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_2_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.789 | 0.895 | 133.74 | 52.57 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.789 | 0.895 | 200.61 | 76.91 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_4_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.789 | 0.895 | 133.74 | 52.57 | 270.00 | 90.00 | W |
PERIMETER_MID_ZN_3_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.755 | 0.851 | 2006.06 | 847.11 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_2_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 0.755 | 0.851 | 1337.37 | 564.74 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.755 | 0.851 | 2006.06 | 847.11 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_4_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 0.755 | 0.851 | 1337.37 | 564.74 | 270.00 | 90.00 | W |
PERIMETER_TOP_ZN_3_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 0.928 | 1.077 | 200.61 | 84.71 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_2_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 0.928 | 1.077 | 133.74 | 56.47 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 0.928 | 1.077 | 200.61 | 84.71 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_4_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 0.928 | 1.077 | 133.74 | 56.47 | 270.00 | 90.00 | W |
GROUNDFLOOR_PLENUM_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.789 | 0.895 | 89.13 | 89.13 | 0.00 | 90.00 | N |
GROUNDFLOOR_PLENUM_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.789 | 0.895 | 59.42 | 59.42 | 270.00 | 90.00 | W |
GROUNDFLOOR_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.789 | 0.895 | 89.13 | 89.13 | 180.00 | 90.00 | S |
GROUNDFLOOR_PLENUM_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.789 | 0.895 | 59.42 | 59.42 | 90.00 | 90.00 | E |
MIDFLOOR_PLENUM_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.755 | 0.851 | 891.32 | 891.32 | 0.00 | 90.00 | N |
MIDFLOOR_PLENUM_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 0.755 | 0.851 | 594.21 | 594.21 | 270.00 | 90.00 | W |
MIDFLOOR_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.755 | 0.851 | 891.32 | 891.32 | 180.00 | 90.00 | S |
MIDFLOOR_PLENUM_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 0.755 | 0.851 | 594.21 | 594.21 | 90.00 | 90.00 | E |
TOPFLOOR_PLENUM_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 0.928 | 1.077 | 89.13 | 89.13 | 180.00 | 90.00 | S |
TOPFLOOR_PLENUM_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 0.928 | 1.077 | 59.42 | 59.42 | 90.00 | 90.00 | E |
TOPFLOOR_PLENUM_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 0.928 | 1.077 | 59.42 | 59.42 | 270.00 | 90.00 | W |
TOPFLOOR_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 0.928 | 1.077 | 89.13 | 89.13 | 0.00 | 90.00 | N |
BUILDING_ROOF | NONRES_ROOF | 0.30 | 0.182 | 0.186 | 3563.11 | 3563.11 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_WALL_NORTH | DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR | 1.00 | 0.340 | 0.354 | 39.22 | 39.22 | 0.00 | 90.00 | N |
DATACENTER_BASEMENT_ZN_6_WALL_SOUTH | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR | 1.00 | 0.340 | 0.354 | 39.22 | 39.22 | 180.00 | 90.00 | S |
DATACENTER_BASEMENT_ZN_6_WALL_WEST | DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR | 1.00 | 0.340 | 0.354 | 118.87 | 118.87 | 270.00 | 90.00 | W |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BASEMENT_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 118.87 | 118.87 | 270.00 | 90.00 | W |
BASEMENT_FLOOR | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 2779.43 | 2779.43 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 225.00 | 0.00 | |
PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 250.34 | 250.34 | 180.00 | 0.00 | |
CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 2076.77 | 2076.77 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 250.34 | 250.34 | 180.00 | 0.00 | |
CORE_BOT_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
CORE_BOT_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
CORE_BOT_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 419.30 | 419.30 | 0.00 | 180.00 | |
CORE_BOT_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 2076.82 | 2076.82 | 0.00 | 180.00 | |
CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 180.00 | 0.00 | |
CORE_MID_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 180.00 | 90.00 | S |
CORE_MID_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 270.00 | 90.00 | W |
CORE_MID_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 0.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 90.00 | 90.00 | E |
CORE_MID_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 24961.20 | 24961.20 | 0.00 | 180.00 | |
CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 24961.20 | 24961.20 | 180.00 | 0.00 | |
CORE_TOP_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
CORE_TOP_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
CORE_TOP_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
CORE_TOP_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 2496.12 | 2496.12 | 0.00 | 180.00 | |
CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 250.34 | 250.34 | 0.00 | 180.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 63.07 | 63.07 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
PERIMETER_BOT_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 45.00 | 180.00 | |
PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 225.00 | 0.00 | |
PERIMETER_BOT_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 63.07 | 63.07 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 250.35 | 250.35 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
PERIMETER_BOT_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 315.00 | 180.00 | |
PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 135.00 | 0.00 | |
PERIMETER_MID_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 225.00 | 90.00 | W |
CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 135.00 | 90.00 | S |
DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 3134.13 | 3134.13 | 0.00 | 180.00 | |
PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.13 | 3134.13 | 180.00 | 0.00 | |
PERIMETER_MID_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 315.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 270.00 | 90.00 | W |
PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 225.00 | 90.00 | W |
PERIMETER_MID_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 2019.75 | 2019.75 | 45.00 | 180.00 | |
PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 225.00 | 0.00 | |
PERIMETER_MID_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 45.00 | 90.00 | E |
DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 315.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 3134.20 | 3134.20 | 0.00 | 180.00 | |
PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.20 | 3134.20 | 180.00 | 0.00 | |
PERIMETER_MID_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 135.00 | 90.00 | S |
DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 45.00 | 90.00 | E |
PERIMETER_MID_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 2019.75 | 2019.75 | 315.00 | 180.00 | |
PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 135.00 | 0.00 | |
PERIMETER_TOP_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 313.41 | 313.41 | 0.00 | 180.00 | |
PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 180.00 | 0.00 | |
PERIMETER_TOP_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
INT-PER3S-NE-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
PERIMETER_TOP_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 201.98 | 201.98 | 45.00 | 180.00 | |
PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 225.00 | 0.00 | |
INT-PER3S-NE | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 313.42 | 313.42 | 0.00 | 180.00 | |
PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 180.00 | 0.00 | |
PERIMETER_TOP_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
PERIMETER_TOP_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 201.98 | 201.98 | 315.00 | 180.00 | |
PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 135.00 | 0.00 | |
iz-CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 45.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 315.00 | 180.00 | |
iz-DATACENTER_BOT_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 0.00 | 180.00 | |
GROUNDFLOOR_PLENUM_CEILING | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 3563.11 | 3563.11 | 180.00 | 0.00 | |
iz-CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 24961.20 | 24961.20 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.13 | 3134.13 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 45.00 | 180.00 | |
iz-PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.20 | 3134.20 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 315.00 | 180.00 | |
iz-DATACENTER_MID_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 362.03 | 362.03 | 0.00 | 180.00 | |
MIDFLOOR_PLENUM_CEILING | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 35631.06 | 35631.06 | 180.00 | 0.00 | |
iz-CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 45.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 315.00 | 180.00 | |
iz-DATACENTER_TOP_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 0.00 | 180.00 | |
DATACENTER_BOT_ZN_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
DATACENTER_BOT_ZN_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
DATACENTER_BOT_ZN_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
DATACENTER_BOT_ZN_6_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 36.20 | 36.20 | 0.00 | 180.00 | |
DATACENTER_BOT_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 180.00 | 0.00 | |
DATACENTER_MID_ZN_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 270.00 | 90.00 | W |
DATACENTER_MID_ZN_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 180.00 | 90.00 | S |
DATACENTER_MID_ZN_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 90.00 | 90.00 | E |
DATACENTER_MID_ZN_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 0.00 | 90.00 | N |
DATACENTER_MID_ZN_6_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 362.03 | 362.03 | 0.00 | 180.00 | |
DATACENTER_MID_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 362.03 | 362.03 | 180.00 | 0.00 | |
DATACENTER_TOP_ZN_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
DATACENTER_TOP_ZN_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
DATACENTER_TOP_ZN_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
DATACENTER_TOP_ZN_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
DATACENTER_TOP_ZN_6_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 36.20 | 36.20 | 0.00 | 180.00 | |
DATACENTER_TOP_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 118.87 | 118.87 | 90.00 | 90.00 | E |
DATACENTER_BASEMENT_ZN_6_FLOOR | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 783.68 | 783.68 | 0.00 | 180.00 | |
DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 36.20 | 36.20 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 419.35 | 419.35 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 135.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 63.08 | 63.08 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 63.07 | 63.07 | 180.00 | 0.00 | |
BASEMENT_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 7126.21 | 0.00 | 90.00 | N | ||
CORE_BOTTOM_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 5064.65 | 0.00 | 90.00 | N | ||
CORE_MID_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 50646.53 | 0.00 | 90.00 | N | ||
CORE_TOP_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 5064.65 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.83 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.84 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 6268.26 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 4039.50 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 6268.35 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 4039.48 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.83 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.84 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | WINDOW_U_0.419_SHGC_NORTH_0.4 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.381 | 0.401 | 0.442 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | WINDOW_U_0.419_SHGC_NORTH_0.4 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.381 | 0.401 | 0.442 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | WINDOW_U_0.419_SHGC_NORTH_0.4 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.381 | 0.401 | 0.442 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | WINDOW_U_0.419_SHGC_NORTH_0.4 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.381 | 0.401 | 0.442 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | WINDOW_U_0.419_SHGC_NORTH_0.4 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.381 | 0.401 | 0.442 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | WINDOW_U_0.419_SHGC_EAST_0.4 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 2.381 | 0.401 | 0.442 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | WINDOW_U_0.419_SHGC_EAST_0.4 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 2.381 | 0.401 | 0.442 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | WINDOW_U_0.419_SHGC_EAST_0.4 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 2.381 | 0.401 | 0.442 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | WINDOW_U_0.419_SHGC_SOUTH_0.4 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.381 | 0.401 | 0.442 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | WINDOW_U_0.419_SHGC_SOUTH_0.4 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.381 | 0.401 | 0.442 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | WINDOW_U_0.419_SHGC_SOUTH_0.4 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.381 | 0.401 | 0.442 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | WINDOW_U_0.419_SHGC_SOUTH_0.4 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.381 | 0.401 | 0.442 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | WINDOW_U_0.419_SHGC_SOUTH_0.4 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.381 | 0.401 | 0.442 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | WINDOW_U_0.419_SHGC_WEST_0.4 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 2.381 | 0.401 | 0.442 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | WINDOW_U_0.419_SHGC_WEST_0.4 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 2.381 | 0.401 | 0.442 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | WINDOW_U_0.419_SHGC_WEST_0.4 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 2.381 | 0.401 | 0.442 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.419_SHGC_NORTH_0.4 | 115.90 | 0.00 | 0.00 | 115.90 | 1158.95 | 2.381 | 0.401 | 0.442 | No | PERIMETER_MID_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.419_SHGC_EAST_0.4 | 77.26 | 0.00 | 0.00 | 77.26 | 772.63 | 2.381 | 0.401 | 0.442 | No | PERIMETER_MID_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.419_SHGC_SOUTH_0.4 | 115.90 | 0.00 | 0.00 | 115.90 | 1158.95 | 2.381 | 0.401 | 0.442 | No | PERIMETER_MID_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.419_SHGC_WEST_0.4 | 77.26 | 0.00 | 0.00 | 77.26 | 772.63 | 2.381 | 0.401 | 0.442 | No | PERIMETER_MID_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.419_SHGC_NORTH_0.4 | 115.90 | 0.00 | 0.00 | 115.90 | 115.90 | 2.381 | 0.401 | 0.442 | No | PERIMETER_TOP_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.419_SHGC_EAST_0.4 | 77.26 | 0.00 | 0.00 | 77.26 | 77.26 | 2.381 | 0.401 | 0.442 | No | PERIMETER_TOP_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.419_SHGC_SOUTH_0.4 | 115.90 | 0.00 | 0.00 | 115.90 | 115.90 | 2.381 | 0.401 | 0.442 | No | PERIMETER_TOP_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.419_SHGC_WEST_0.4 | 77.26 | 0.00 | 0.00 | 77.26 | 77.26 | 2.381 | 0.401 | 0.442 | No | PERIMETER_TOP_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
Total or Average | 4635.80 | 2.381 | 0.401 | 0.442 | |||||||||||||||||
North Total or Average | 1390.74 | 2.381 | 0.401 | 0.442 | |||||||||||||||||
Non-North Total or Average | 3245.06 | 2.381 | 0.401 | 0.442 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | SWINGING DOOR_CON | 1.992 | 2.839 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | SWINGING DOOR_CON | 1.992 | 2.839 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | SWINGING DOOR_CON | 1.992 | 2.839 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | SWINGING DOOR_CON | 1.992 | 2.839 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | SWINGING DOOR_CON | 1.992 | 2.839 | 1.95 | PERIMETER_BOT_ZN_2_WALL_EAST |
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | SWINGING DOOR_CON | 1.992 | 2.839 | 1.95 | PERIMETER_BOT_ZN_2_WALL_EAST |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | SWINGING DOOR_CON | 1.992 | 2.839 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | SWINGING DOOR_CON | 1.992 | 2.839 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | SWINGING DOOR_CON | 1.992 | 2.839 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | SWINGING DOOR_CON | 1.992 | 2.839 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | SWINGING DOOR_CON | 1.992 | 2.839 | 1.95 | PERIMETER_BOT_ZN_4_WALL_WEST |
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | SWINGING DOOR_CON | 1.992 | 2.839 | 1.95 | PERIMETER_BOT_ZN_4_WALL_WEST |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 08:43:39
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 08:43:39
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
BASEMENT_LIGHTS | BASEMENT | BASEMENT | GENERAL | 10.2732 | 2779.43 | 28553.72 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 49.04 | 0.0000 | Y | 262.84 |
CORE_BOTTOM_LIGHTS | CORE_BOTTOM | CORE_BOTTOM | GENERAL | 10.2732 | 2496.12 | 25643.24 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 49.04 | 0.0000 | Y | 236.05 |
CORE_MID_LIGHTS | CORE_MID | CORE_MID | GENERAL | 10.2732 | 24961.20 | 256432.45 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 49.04 | 0.0000 | Y | 2360.52 |
CORE_TOP_LIGHTS | CORE_TOP | CORE_TOP | GENERAL | 10.2732 | 2496.12 | 25643.24 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 49.04 | 0.0000 | Y | 236.05 |
PERIMETER_BOT_ZN_3_LIGHTS | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3 | GENERAL | 10.2732 | 313.41 | 3219.77 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 29.08 | 0.0000 | Y | 17.57 |
PERIMETER_BOT_ZN_2_LIGHTS | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2 | GENERAL | 10.2732 | 201.98 | 2074.94 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 28.66 | 0.0000 | Y | 11.16 |
PERIMETER_BOT_ZN_1_LIGHTS | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1 | GENERAL | 10.2732 | 313.42 | 3219.84 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 28.41 | 0.0000 | Y | 17.17 |
PERIMETER_BOT_ZN_4_LIGHTS | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4 | GENERAL | 10.2732 | 201.98 | 2074.94 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 28.75 | 0.0000 | Y | 11.20 |
PERIMETER_MID_ZN_3_LIGHTS | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3 | GENERAL | 10.2732 | 3134.13 | 32197.65 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 29.01 | 0.0000 | Y | 175.35 |
PERIMETER_MID_ZN_2_LIGHTS | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2 | GENERAL | 10.2732 | 2019.75 | 20749.39 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 28.62 | 0.0000 | Y | 111.48 |
PERIMETER_MID_ZN_1_LIGHTS | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1 | GENERAL | 10.2732 | 3134.20 | 32198.36 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 28.38 | 0.0000 | Y | 171.54 |
PERIMETER_MID_ZN_4_LIGHTS | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4 | GENERAL | 10.2732 | 2019.75 | 20749.39 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 28.70 | 0.0000 | Y | 111.80 |
PERIMETER_TOP_ZN_3_LIGHTS | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3 | GENERAL | 10.2732 | 313.41 | 3219.77 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 29.01 | 0.0000 | Y | 17.53 |
PERIMETER_TOP_ZN_2_LIGHTS | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2 | GENERAL | 10.2732 | 201.98 | 2074.94 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 28.62 | 0.0000 | Y | 11.15 |
PERIMETER_TOP_ZN_1_LIGHTS | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1 | GENERAL | 10.2732 | 313.42 | 3219.84 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 28.38 | 0.0000 | Y | 17.15 |
PERIMETER_TOP_ZN_4_LIGHTS | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4 | GENERAL | 10.2732 | 201.98 | 2074.94 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 28.70 | 0.0000 | Y | 11.18 |
DATACENTER_BASEMENT_LIGHTS | DATACENTER_BASEMENT_ZN_6 | DATACENTER_BASEMENT_ZN_6 | GENERAL | 10.2732 | 783.68 | 8050.93 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 49.04 | 0.0000 | Y | 74.11 |
DATACENTER_BOT_LIGHTS | DATACENTER_BOT_ZN_6 | DATACENTER_BOT_ZN_6 | GENERAL | 17.8735 | 36.20 | 647.07 | LightsWired | LTG_SCH_DATACENTER | 56.02 | 168.00 | 54.57 | 0.0000 | Y | 6.63 |
DATACENTER_MID_LIGHTS | DATACENTER_MID_ZN_6 | DATACENTER_MID_ZN_6 | GENERAL | 17.8735 | 362.03 | 6470.68 | LightsWired | LTG_SCH_DATACENTER | 56.02 | 168.00 | 54.57 | 0.0000 | Y | 66.28 |
DATACENTER_TOP_LIGHTS | DATACENTER_TOP_ZN_6 | DATACENTER_TOP_ZN_6 | GENERAL | 17.8735 | 36.20 | 647.07 | LightsWired | LTG_SCH_DATACENTER | 56.02 | 168.00 | 54.57 | 0.0000 | Y | 6.63 |
Interior Lighting Total | 10.3445 | 46320.38 | 479162.15 | 1236.13 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
PERIMETER_BOT_ZN_1_DAYLREFPT1 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_DAYLCTRL | SplitFlux | Stepped | 0.39 | 3219.84 | 1241.89 |
PERIMETER_BOT_ZN_1_DAYLREFPT2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_DAYLCTRL | SplitFlux | Stepped | 0.14 | 3219.84 | 445.95 |
PERIMETER_BOT_ZN_2_DAYLREFPT1 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_DAYLCTRL | SplitFlux | Stepped | 0.39 | 2074.94 | 800.30 |
PERIMETER_BOT_ZN_2_DAYLREFPT2 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_DAYLCTRL | SplitFlux | Stepped | 0.14 | 2074.94 | 287.38 |
PERIMETER_BOT_ZN_3_DAYLREFPT1 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_DAYLCTRL | SplitFlux | Stepped | 0.39 | 3219.77 | 1241.86 |
PERIMETER_BOT_ZN_3_DAYLREFPT2 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_DAYLCTRL | SplitFlux | Stepped | 0.14 | 3219.77 | 445.94 |
PERIMETER_BOT_ZN_4_DAYLREFPT1 | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_DAYLCTRL | SplitFlux | Stepped | 0.39 | 2074.94 | 800.30 |
PERIMETER_BOT_ZN_4_DAYLREFPT2 | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_DAYLCTRL | SplitFlux | Stepped | 0.14 | 2074.94 | 287.38 |
PERIMETER_MID_ZN_1_DAYLREFPT1 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_DAYLCTRL | SplitFlux | Stepped | 0.39 | 3219.84 | 1241.89 |
PERIMETER_MID_ZN_1_DAYLREFPT2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_DAYLCTRL | SplitFlux | Stepped | 0.14 | 3219.84 | 445.95 |
PERIMETER_MID_ZN_2_DAYLREFPT1 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_DAYLCTRL | SplitFlux | Stepped | 0.39 | 2074.94 | 800.30 |
PERIMETER_MID_ZN_2_DAYLREFPT2 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_DAYLCTRL | SplitFlux | Stepped | 0.14 | 2074.94 | 287.38 |
PERIMETER_MID_ZN_3_DAYLREFPT1 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_DAYLCTRL | SplitFlux | Stepped | 0.39 | 3219.77 | 1241.86 |
PERIMETER_MID_ZN_3_DAYLREFPT2 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_DAYLCTRL | SplitFlux | Stepped | 0.14 | 3219.77 | 445.94 |
PERIMETER_MID_ZN_4_DAYLREFPT1 | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_DAYLCTRL | SplitFlux | Stepped | 0.39 | 2074.94 | 800.30 |
PERIMETER_MID_ZN_4_DAYLREFPT2 | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_DAYLCTRL | SplitFlux | Stepped | 0.14 | 2074.94 | 287.38 |
PERIMETER_TOP_ZN_1_DAYLREFPT1 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_DAYLCTRL | SplitFlux | Stepped | 0.39 | 3219.84 | 1241.89 |
PERIMETER_TOP_ZN_1_DAYLREFPT2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_DAYLCTRL | SplitFlux | Stepped | 0.14 | 3219.84 | 445.95 |
PERIMETER_TOP_ZN_2_DAYLREFPT1 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_DAYLCTRL | SplitFlux | Stepped | 0.39 | 2074.94 | 800.30 |
PERIMETER_TOP_ZN_2_DAYLREFPT2 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_DAYLCTRL | SplitFlux | Stepped | 0.14 | 2074.94 | 287.38 |
PERIMETER_TOP_ZN_3_DAYLREFPT1 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_DAYLCTRL | SplitFlux | Stepped | 0.39 | 3219.77 | 1241.86 |
PERIMETER_TOP_ZN_3_DAYLREFPT2 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_DAYLCTRL | SplitFlux | Stepped | 0.14 | 3219.77 | 445.94 |
PERIMETER_TOP_ZN_4_DAYLREFPT1 | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_DAYLCTRL | SplitFlux | Stepped | 0.39 | 2074.94 | 800.30 |
PERIMETER_TOP_ZN_4_DAYLREFPT2 | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_DAYLCTRL | SplitFlux | Stepped | 0.14 | 2074.94 | 287.38 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS_A | 13279.00 | AstronomicalClock | - | 42.11 | 42.11 | 104.95 | |
EXTERIOR_LIGHTS_B | 44301.60 | AstronomicalClock | - | 83.57 | 71.13 | 591.52 | |
Exterior Lighting Total | 57580.60 | 696.47 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 08:43:39
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
BYPASS HEAT EXCHANGER | HeatExchanger:FluidToFluid | 2320560.81 | |||||
HEATSYS1 BOILER | Boiler:HotWater | 3442804.66 | 0.81 | ||||
COOLSYS1 CHILLER1 | Chiller:Electric:ReformulatedEIR | 1180245.77 | 6.28 | 1129649.87 | 5.98 | 6.84 | 23.33 |
COOLSYS1 CHILLER2 | Chiller:Electric:ReformulatedEIR | 1180245.77 | 6.28 | 1129649.87 | 5.98 | 6.84 | 23.33 |
CENTRAL TOWER | FluidCooler:TwoSpeed | 582060.00 | |||||
CENTRAL BOILER | Boiler:HotWater | 584202.86 | 0.80 | ||||
TOWERWATERSYS COOLTOWER 1 | CoolingTower:VariableSpeed | 1402076.60 | |||||
TOWERWATERSYS COOLTOWER 2 | CoolingTower:VariableSpeed | 1402076.60 |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
VAV_BOT WITH REHEAT COOLING COIL | Coil:Cooling:Water | 194585.29 | 328097.05 | 201626.38 | 126470.67 | 0.61 | - | 65619.45 | 665.55 |
VAV_MID WITH REHEAT COOLING COIL | Coil:Cooling:Water | 1817578.77 | 3043069.59 | 1868368.76 | 1174700.82 | 0.61 | - | 603136.28 | 6117.34 |
VAV_TOP WITH REHEAT COOLING COIL | Coil:Cooling:Water | 203672.51 | 345420.29 | 212455.27 | 132965.02 | 0.62 | - | 69556.50 | 705.48 |
CAV_BAS COOLING COIL | Coil:Cooling:Water | 110073.14 | 185004.23 | 115151.46 | 69852.76 | 0.62 | - | 33859.13 | 343.42 |
AIRLOOP DATACENTER BASEMENT COOLING COIL | Coil:Cooling:WaterToAirHeatPump:EquationFit | 466437.89 | 262502.94 | 203934.95 | 0.56 | 0.00 | |||
AIRLOOP DATACENTER BOT COOLING COIL | Coil:Cooling:WaterToAirHeatPump:EquationFit | 10807.09 | 6147.89 | 4659.20 | 0.57 | 0.00 | |||
AIRLOOP DATACENTER MID COOLING COIL | Coil:Cooling:WaterToAirHeatPump:EquationFit | 103961.65 | 59130.97 | 44830.68 | 0.57 | 0.00 | |||
AIRLOOP DATACENTER TOP COOLING COIL | Coil:Cooling:WaterToAirHeatPump:EquationFit | 10570.02 | 6012.39 | 4557.63 | 0.57 | 0.00 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
None |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
None |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Water | 25791.51 | 24454.28 | - |
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Water | 515371.91 | 488267.08 | - |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Water | 111653.25 | 105821.88 | - |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 21629.82 | 20497.98 | - |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 14800.43 | 14025.83 | - |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 23695.44 | 22455.23 | - |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 12601.41 | 11942.21 | - |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 305019.35 | 289043.43 | - |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 202437.02 | 191833.39 | - |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 309716.07 | 293493.70 | - |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 199861.14 | 189392.58 | - |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 38505.23 | 36487.65 | - |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 25419.30 | 24087.34 | - |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 39023.78 | 36978.99 | - |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 25434.92 | 24102.13 | - |
VAV_BOT WITH REHEAT HEATING COIL | Coil:Heating:Water | 101691.05 | 69087.22 | - |
VAV_MID WITH REHEAT HEATING COIL | Coil:Heating:Water | 1044136.00 | 688507.71 | - |
VAV_TOP WITH REHEAT HEATING COIL | Coil:Heating:Water | 102308.46 | 70434.50 | - |
CAV_BAS HEATING COIL | Coil:Heating:Water | 323708.58 | 245432.64 | - |
AIRLOOP DATACENTER BASEMENT HEATING COIL | Coil:Heating:WaterToAirHeatPump:EquationFit | 466437.89 | 0.00 | |
AIRLOOP DATACENTER BOT HEATING COIL | Coil:Heating:WaterToAirHeatPump:EquationFit | 10807.09 | 0.00 | |
AIRLOOP DATACENTER MID HEATING COIL | Coil:Heating:WaterToAirHeatPump:EquationFit | 103961.65 | 0.00 | |
AIRLOOP DATACENTER TOP HEATING COIL | Coil:Heating:WaterToAirHeatPump:EquationFit | 10570.02 | 0.00 | |
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | Coil:Heating:Electric | 24207.99 | 1.00 | |
AIRLOOP DATACENTER BOT_SUPPHEATCOIL | Coil:Heating:Electric | 1118.31 | 1.00 | |
AIRLOOP DATACENTER MID_SUPPHEATCOIL | Coil:Heating:Electric | 11183.09 | 1.00 | |
AIRLOOP DATACENTER TOP_SUPPHEATCOIL | Coil:Heating:Electric | 1118.31 | 1.00 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
VAV_BOT WITH REHEAT FAN | Fan:VariableVolume | 0.61 | 1389.42 | 11.66 | 26477.02 | 2271.59 | 1.00 | 1.11 | General | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 |
VAV_MID WITH REHEAT FAN | Fan:VariableVolume | 0.61 | 1389.42 | 107.83 | 244950.13 | 2271.59 | 1.00 | 1.08 | General | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 |
VAV_TOP WITH REHEAT FAN | Fan:VariableVolume | 0.61 | 1389.42 | 12.30 | 27942.39 | 2271.59 | 1.00 | 1.11 | General | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 |
CAV_BAS FAN | Fan:ConstantVolume | 0.60 | 1018.41 | 6.82 | 11488.25 | 1684.71 | 1.00 | 1.15 | General | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
AIRLOOP DATACENTER BASEMENT SUPPLY FAN | Fan:OnOff | 0.62 | 1018.41 | 24.54 | 40470.70 | 1649.25 | 1.00 | 1.14 | General | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 07:10:00 |
AIRLOOP DATACENTER BOT SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.59 | 655.68 | 1120.11 | 1.00 | 1.54 | General | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
AIRLOOP DATACENTER MID SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 5.63 | 6305.84 | 1120.11 | 1.00 | 1.15 | General | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
AIRLOOP DATACENTER TOP SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.57 | 641.20 | 1120.11 | 1.00 | 1.55 | General | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
COOLSYS1 PUMP SECONDARY | Pump:VariableSpeed | Intermittent | 105797.75 | 0.098950 | 16155.44 | 163269.45 | 0.90 | General |
HEATSYS1 PUMP | Pump:VariableSpeed | Intermittent | 180705.70 | 0.030119 | 9070.57 | 301156.09 | 0.90 | General |
COOLSYS1 CHILLER1 PUMP | Pump:ConstantSpeed | Intermittent | 73247.35 | 0.049475 | 5592.48 | 113036.94 | 0.90 | General |
COOLSYS1 CHILLER2 PUMP | Pump:ConstantSpeed | Intermittent | 73247.35 | 0.049475 | 5592.48 | 113036.94 | 0.90 | General |
PLANT CIRC PUMP | Pump:ConstantSpeed | Intermittent | 179045.11 | 0.014493 | 3696.33 | 255050.01 | 0.90 | General |
SWHSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 29891.00 | 0.000440 | 56.21 | 127739.32 | 0.30 | General |
TOWERWATERSYS PUMP | HeaderedPumps:VariableSpeed | Intermittent | 148556.62 | 0.116812 | 28920.06 | 247577.87 | 0.90 | General |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 1.14 | 87921.32 | 0.80 | 0.48 | 0.06 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:43:39
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 82553.08 | 82553.08 | 29.70 | 6.819 | 6.819 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 24.00 | 24.00 | 0.00742 | 21.56 | 0.00629 | 1.200 | 0.00 |
CORE_BOTTOM | 85532.33 | 85532.33 | 34.27 | 7.064 | 7.064 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 24.00 | 24.00 | 0.00736 | 21.56 | 0.00629 | 1.078 | 0.00 |
CORE_MID | 805659.31 | 805659.31 | 322.76 | 66.527 | 66.527 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 24.00 | 24.00 | 0.00739 | 21.56 | 0.00629 | 10.778 | 0.00 |
CORE_TOP | 77939.31 | 77939.31 | 31.22 | 6.435 | 6.435 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 24.00 | 24.00 | 0.00740 | 21.56 | 0.00629 | 1.078 | 0.00 |
PERIMETER_BOT_ZN_3 | 14368.62 | 14368.62 | 45.85 | 1.197 | 1.197 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 | 24.00 | 24.00 | 0.00724 | 33.40 | 0.00631 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_2 | 19479.39 | 19479.39 | 96.44 | 1.623 | 1.623 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | 24.00 | 24.00 | 0.00712 | 24.60 | 0.00629 | 0.087 | 0.00 |
PERIMETER_BOT_ZN_1 | 24109.11 | 24109.11 | 76.92 | 2.008 | 2.008 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 24.00 | 24.00 | 0.00715 | 33.00 | 0.00631 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_4 | 23888.42 | 23888.42 | 118.27 | 1.990 | 1.990 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:20:00 | 24.00 | 24.00 | 0.00709 | 30.63 | 0.00630 | 0.087 | 0.00 |
PERIMETER_MID_ZN_3 | 136839.93 | 136839.93 | 436.61 | 11.399 | 11.399 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | 24.00 | 24.00 | 0.00723 | 33.40 | 0.00631 | 1.353 | 0.00 |
PERIMETER_MID_ZN_2 | 207805.49 | 207805.49 | 1028.87 | 17.310 | 17.310 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:20:00 | 24.00 | 24.00 | 0.00710 | 25.51 | 0.00629 | 0.872 | 0.00 |
PERIMETER_MID_ZN_1 | 246290.67 | 246290.67 | 785.82 | 20.516 | 20.516 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | 24.00 | 24.00 | 0.00713 | 33.27 | 0.00631 | 1.353 | 0.00 |
PERIMETER_MID_ZN_4 | 224695.19 | 224695.19 | 1112.49 | 18.717 | 18.717 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:30:00 | 24.00 | 24.00 | 0.00709 | 30.36 | 0.00630 | 0.872 | 0.00 |
PERIMETER_TOP_ZN_3 | 15383.92 | 15383.92 | 49.09 | 1.281 | 1.281 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 24.00 | 24.00 | 0.00719 | 33.24 | 0.00631 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_2 | 20780.74 | 20780.74 | 102.89 | 1.731 | 1.731 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:40:00 | 24.00 | 24.00 | 0.00709 | 26.41 | 0.00630 | 0.087 | 0.00 |
PERIMETER_TOP_ZN_1 | 26241.13 | 26241.13 | 83.73 | 2.186 | 2.186 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | 24.00 | 24.00 | 0.00712 | 33.27 | 0.00631 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_4 | 23599.31 | 23599.31 | 116.84 | 1.966 | 1.966 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:30:00 | 24.00 | 24.00 | 0.00708 | 30.36 | 0.00630 | 0.087 | 0.00 |
DATACENTER_BOT_ZN_6 | 8909.34 | 8909.34 | 246.10 | 0.585 | 0.585 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:30:00 | 27.00 | 27.00 | 0.00708 | 26.28 | 0.00630 | 0.016 | 0.00 |
DATACENTER_MID_ZN_6 | 85682.56 | 85682.56 | 2366.74 | 5.630 | 5.630 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:30:00 | 27.00 | 27.00 | 0.00708 | 26.28 | 0.00630 | 0.156 | 0.00 |
DATACENTER_TOP_ZN_6 | 8712.47 | 8712.47 | 240.66 | 0.572 | 0.572 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:30:00 | 27.00 | 27.00 | 0.00708 | 26.28 | 0.00630 | 0.016 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 373481.81 | 373481.81 | 476.57 | 24.539 | 24.539 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 07:00:00 | 27.00 | 27.00 | 0.00704 | 18.84 | 0.00628 | 0.338 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.000 | 1.200 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 22.75 | 0.00034 | -27.60 | 0.00034 | 1.200 | 0.00 |
CORE_BOTTOM | 7875.70 | 7875.70 | 3.16 | 0.382 | 1.078 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00800 | -27.60 | 0.00034 | 1.078 | 0.00 |
CORE_MID | 340208.24 | 340208.24 | 136.29 | 16.468 | 16.468 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00800 | -27.60 | 0.00034 | 10.778 | 0.00 |
CORE_TOP | 78157.42 | 78157.42 | 31.31 | 3.804 | 3.804 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00800 | -27.60 | 0.00034 | 1.078 | 0.00 |
PERIMETER_BOT_ZN_3 | 15136.09 | 15136.09 | 48.29 | 0.738 | 0.738 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00780 | -27.60 | 0.00034 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_2 | 10356.48 | 10356.48 | 51.28 | 0.505 | 0.505 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00780 | -27.60 | 0.00034 | 0.087 | 0.00 |
PERIMETER_BOT_ZN_1 | 16580.21 | 16580.21 | 52.90 | 0.808 | 0.808 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00782 | -27.60 | 0.00034 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_4 | 8819.30 | 8819.30 | 43.67 | 0.430 | 0.430 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00775 | -27.60 | 0.00034 | 0.087 | 0.00 |
PERIMETER_MID_ZN_3 | 213421.17 | 213421.17 | 680.96 | 10.410 | 10.410 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00768 | -27.60 | 0.00034 | 1.353 | 0.00 |
PERIMETER_MID_ZN_2 | 141642.72 | 141642.72 | 701.29 | 6.909 | 6.909 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00768 | -27.60 | 0.00034 | 0.872 | 0.00 |
PERIMETER_MID_ZN_1 | 216704.95 | 216704.95 | 691.42 | 10.571 | 10.571 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00768 | -27.60 | 0.00034 | 1.353 | 0.00 |
PERIMETER_MID_ZN_4 | 139841.48 | 139841.48 | 692.37 | 6.821 | 6.821 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00767 | -27.60 | 0.00034 | 0.872 | 0.00 |
PERIMETER_TOP_ZN_3 | 26939.43 | 26939.43 | 85.96 | 1.315 | 1.315 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00768 | -27.60 | 0.00034 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_2 | 17784.01 | 17784.01 | 88.05 | 0.868 | 0.868 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00768 | -27.60 | 0.00034 | 0.087 | 0.00 |
PERIMETER_TOP_ZN_1 | 27301.99 | 27301.99 | 87.11 | 1.332 | 1.332 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00769 | -27.60 | 0.00034 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_4 | 17794.90 | 17794.90 | 88.10 | 0.868 | 0.868 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00768 | -27.60 | 0.00034 | 0.087 | 0.00 |
DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.016 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 05:30:00 | 18.00 | 24.16 | 0.00098 | -27.60 | 0.00034 | 0.016 | 0.00 |
DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.156 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 05:40:00 | 18.00 | 22.16 | 0.00098 | -27.60 | 0.00034 | 0.156 | 0.00 |
DATACENTER_TOP_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.016 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 05:30:00 | 18.00 | 19.70 | 0.00098 | -27.60 | 0.00034 | 0.016 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.338 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:40:00 | 18.00 | 27.00 | 0.00700 | -27.60 | 0.00034 | 0.338 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
VAV_BOT WITH REHEAT | 11.66 | 11.66 | 3.56 | 3.56 | 11.6557 | 3.5586 | 11.6557 | 0.3053 | 0.3000 |
VAV_MID WITH REHEAT | 107.83 | 107.83 | 51.18 | 51.18 | 107.8319 | 51.1804 | 107.8319 | 0.4746 | 0.3000 |
VAV_TOP WITH REHEAT | 12.30 | 12.30 | 8.19 | 8.19 | 12.3008 | 8.1867 | 12.3008 | 0.6655 | 0.3000 |
CAV_BAS | 6.82 | 6.82 | 1.20 | 1.20 | 6.8191 | 6.8191 | 6.8191 | 1.0000 | 1.0000 |
AIRLOOP DATACENTER BASEMENT | 24.54 | 24.54 | 0.34 | 0.34 | 24.5389 | 24.5388 | 24.5389 | 1.0000 | 1.0000 |
AIRLOOP DATACENTER BOT | 0.59 | 0.59 | 0.02 | 0.02 | 0.5854 | 0.5854 | 0.5854 | 1.0000 | 1.0000 |
AIRLOOP DATACENTER MID | 5.63 | 5.63 | 0.16 | 0.16 | 5.6297 | 5.6297 | 5.6297 | 1.0000 | 1.0000 |
AIRLOOP DATACENTER TOP | 0.57 | 0.57 | 0.02 | 0.02 | 0.5724 | 0.5724 | 0.5724 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | 25791.505 | 25791.505 | 2.034507 | 0.00022564 | 543.507 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 25791.51 | 25791.51 | 2.034507 | 12.80 | 10.41 | 0.00800000 | 40.00 | 19.63 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 0.0000 | 21.00 | 0.00799972 | 45.2294 | 7875.70 | 0.00 | 25884.64 | 25884.64 |
CORE_MID VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | 515371.914 | 515371.914 | 19.891465 | 0.00450870 | 12910.418 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 515371.91 | 515371.91 | 19.891465 | 12.80 | 10.41 | 0.00800000 | 40.00 | 19.63 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 0.0000 | 21.00 | 0.00800000 | 45.2310 | 340208.24 | 0.00 | 516976.72 | 516976.72 |
CORE_TOP VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | 111653.252 | 111653.252 | 3.803763 | 0.00097679 | 2946.068 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 111653.25 | 111653.25 | 3.803763 | 12.80 | 10.41 | 0.00800000 | 40.00 | 19.63 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 0.0000 | 21.00 | 0.00800000 | 45.2310 | 78157.42 | 0.00 | 112030.21 | 112030.21 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | 21629.818 | 21629.818 | 0.737784 | 0.00018923 | 570.400 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21629.82 | 21629.82 | 0.737784 | 12.80 | 10.41 | 0.00800000 | 40.00 | 19.63 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 0.0000 | 21.00 | 0.00779530 | 44.0905 | 15136.09 | 0.00 | 21700.53 | 21700.53 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | 14800.433 | 14800.433 | 0.504891 | 0.00012948 | 390.283 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 14800.43 | 14800.43 | 0.504891 | 12.80 | 10.41 | 0.00800000 | 40.00 | 19.63 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 0.0000 | 21.00 | 0.00780326 | 44.1350 | 10356.48 | 0.00 | 14848.68 | 14848.68 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | 23695.437 | 23695.437 | 0.808359 | 0.00020730 | 624.831 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 23695.44 | 23695.44 | 0.808359 | 12.80 | 10.41 | 0.00800000 | 40.00 | 19.63 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 0.0000 | 21.00 | 0.00781675 | 44.2102 | 16580.21 | 0.00 | 23772.60 | 23772.60 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | 12601.405 | 12601.405 | 0.429743 | 0.00011024 | 332.342 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 12601.41 | 12601.41 | 0.429743 | 12.80 | 10.41 | 0.00800000 | 40.00 | 19.63 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 0.0000 | 21.00 | 0.00775451 | 43.8630 | 8819.30 | 0.00 | 12642.82 | 12642.82 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | 305019.349 | 305019.349 | 10.410358 | 0.00266844 | 8041.455 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 305019.35 | 305019.35 | 10.410358 | 12.80 | 10.41 | 0.00800000 | 40.00 | 19.63 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 0.0000 | 21.00 | 0.00767811 | 43.4383 | 213421.17 | 0.00 | 306000.54 | 306000.54 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | 202437.020 | 202437.020 | 6.909475 | 0.00177101 | 5336.906 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 202437.02 | 202437.02 | 6.909475 | 12.80 | 10.41 | 0.00800000 | 40.00 | 19.63 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 0.0000 | 21.00 | 0.00767686 | 43.4315 | 141642.72 | 0.00 | 203087.54 | 203087.54 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | 309716.067 | 309716.067 | 10.570846 | 0.00270953 | 8165.212 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 309716.07 | 309716.07 | 10.570846 | 12.80 | 10.41 | 0.00800000 | 40.00 | 19.63 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 0.0000 | 21.00 | 0.00768288 | 43.4650 | 216704.95 | 0.00 | 310711.88 | 310711.88 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | 199861.138 | 199861.138 | 6.821494 | 0.00174847 | 5269.019 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 199861.14 | 199861.14 | 6.821494 | 12.80 | 10.41 | 0.00800000 | 40.00 | 19.63 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 0.0000 | 21.00 | 0.00767291 | 43.4094 | 139841.48 | 0.00 | 200503.54 | 200503.54 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | 38505.230 | 38505.230 | 1.314526 | 0.00033686 | 1015.024 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 38505.23 | 38397.36 | 1.314526 | 12.80 | 10.41 | 0.00800000 | 40.00 | 19.63 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 0.0000 | 21.00 | 0.00768303 | 43.4667 | 26939.43 | 0.00 | 38628.24 | 38628.24 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | 25419.301 | 25419.301 | 0.867809 | 0.00022238 | 670.062 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 25419.30 | 25419.30 | 0.867809 | 12.80 | 10.41 | 0.00800000 | 40.00 | 19.63 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 0.0000 | 21.00 | 0.00767995 | 43.4497 | 17784.01 | 0.00 | 25500.45 | 25500.45 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | 39023.780 | 39023.780 | 1.332244 | 0.00034140 | 1028.688 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 39023.78 | 39023.78 | 1.332244 | 12.80 | 10.41 | 0.00800000 | 40.00 | 19.63 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 0.0000 | 21.00 | 0.00768705 | 43.4892 | 27301.99 | 0.00 | 39148.41 | 39148.41 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | 25434.922 | 25434.922 | 0.868347 | 0.00022252 | 670.472 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 25434.92 | 25434.92 | 0.868347 | 12.80 | 10.41 | 0.00800000 | 40.00 | 19.63 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 0.0000 | 21.00 | 0.00768035 | 43.4519 | 17794.90 | 0.00 | 25516.11 | 25516.11 |
VAV_BOT WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | VAV_BOT WITH REHEAT | 194585.286 | -999.000 | 11.655704 | 0.00827811 | -999.000 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 194585.29 | 192505.00 | 11.655704 | 26.05 | 14.53 | 0.00708318 | 10.68 | 8.51 | 0.00700000 | 33.40 | 0.00630683 | 16.37 | 21.7764 | 24.00 | 0.00729942 | 34.4333 | 139863.93 | 0.00 | 219574.77 | 216437.63 |
VAV_BOT WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoopHVAC | VAV_BOT WITH REHEAT | 101691.050 | 101691.050 | 3.496711 | 0.00088964 | 1578.769 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 06:30:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 101691.05 | 101691.05 | 3.496711 | -14.68 | -14.68 | 0.00237751 | 12.80 | 10.41 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 72.5879 | 19.81 | 0.00772998 | 47.0566 | 35041.96 | 0.00 | 83549.98 | 83549.98 |
VAV_MID WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | VAV_MID WITH REHEAT | 1817578.773 | -999.000 | 107.831862 | 0.07732400 | -999.000 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | 1817578.77 | 1799813.19 | 107.831862 | 26.21 | 14.59 | 0.00707663 | 10.68 | 8.51 | 0.00700000 | 33.40 | 0.00630683 | 16.37 | 23.5385 | 24.00 | 0.00731387 | 34.5006 | 1293342.28 | 0.00 | 2049140.46 | 2021722.57 |
VAV_MID WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoopHVAC | VAV_MID WITH REHEAT | 1044136.002 | 1044136.002 | 32.349559 | 0.00913456 | 15812.226 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 05:30:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 1044136.00 | 1044136.00 | 32.349559 | -17.70 | -17.70 | 0.00190076 | 12.80 | 10.41 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 78.4615 | 17.87 | 0.00757052 | 52.0491 | 383297.13 | 0.00 | 832607.55 | 832607.55 |
VAV_TOP WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | VAV_TOP WITH REHEAT | 203672.512 | -999.000 | 12.300790 | 0.00866470 | -999.000 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 | 203672.51 | 201753.67 | 12.300790 | 25.95 | 14.49 | 0.00707283 | 10.68 | 8.51 | 0.00700000 | 33.40 | 0.00630683 | 16.37 | 20.6344 | 24.00 | 0.00727281 | 34.3091 | 147175.04 | 0.00 | 230005.32 | 227057.86 |
VAV_TOP WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoopHVAC | VAV_TOP WITH REHEAT | 102308.455 | 102308.455 | 3.690237 | 0.00089504 | 1597.676 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 01:50:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 102308.46 | 102308.46 | 3.690237 | -13.40 | -13.40 | 0.00257360 | 12.80 | 10.41 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 68.7812 | 15.98 | 0.00758254 | 58.7469 | 38237.25 | 0.00 | 85150.87 | 85150.87 |
CAV_BAS COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | CAV_BAS | 110073.141 | -999.000 | 6.819106 | 0.00468277 | -999.000 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:00:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 110073.14 | 106760.32 | 6.819106 | 25.70 | 14.54 | 0.00723461 | 11.23 | 8.74 | 0.00700000 | 32.60 | 0.00630558 | 16.10 | 17.5999 | 24.00 | 0.00746371 | 35.1995 | 72830.29 | 0.00 | 124296.80 | 122031.40 |
CAV_BAS HEATING COIL | Coil:Heating:Water | AirLoopHVAC | CAV_BAS | 323708.581 | 323708.581 | 6.819106 | 0.00283194 | 6941.245 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 323708.58 | 323708.58 | 6.819106 | -4.86 | -9.35 | 0.00034190 | 40.00 | 19.63 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 17.5999 | 22.86 | 0.00034190 | 1.7470 | 0.00 | 0.00 | 258881.68 | 258881.68 |
AIRLOOP DATACENTER BASEMENT COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | 466437.893 | 262502.939 | 24.538896 | 0.01142303 | -999.000 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 07:10:00 | 405303.45 | 403832.34 | -999.0 | 28.68 | 15.39 | 0.00703181 | 12.80 | 9.41 | 0.00700000 | 33.40 | 0.00630683 | 16.37 | -999.0000 | 27.00 | 0.00704196 | 27.8114 | 373034.82 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BOT COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER BOT | 10807.087 | 6147.885 | 0.585375 | 0.00026466 | -999.000 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:30:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:30:00 | 9339.78 | 9274.26 | -999.0 | 28.06 | 15.21 | 0.00705998 | 12.80 | 9.41 | 0.00700000 | 26.28 | 0.00629588 | 13.94 | -999.0000 | 27.00 | 0.00708094 | 27.9616 | 8909.34 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER MID COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER MID | 103961.649 | 59130.970 | 5.629668 | 0.00254601 | -999.000 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:30:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:30:00 | 89850.72 | 89196.79 | -999.0 | 28.06 | 15.21 | 0.00706223 | 12.80 | 9.41 | 0.00700000 | 26.28 | 0.00629588 | 13.94 | -999.0000 | 27.00 | 0.00708412 | 27.9741 | 85682.56 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER TOP COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER TOP | 10570.015 | 6012.389 | 0.572441 | 0.00025886 | -999.000 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:30:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:30:00 | 9135.16 | 9069.63 | -999.0 | 28.06 | 15.21 | 0.00706134 | 12.80 | 9.41 | 0.00700000 | 26.28 | 0.00629588 | 13.94 | -999.0000 | 27.00 | 0.00708283 | 27.9690 | 8712.47 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BASEMENT HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | 466437.893 | 466437.893 | 24.538896 | 0.01142303 | -999.000 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 466437.89 | 466437.89 | 24.538896 | -27.60 | -27.60 | 0.00034190 | 40.00 | 19.63 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 1.3790 | 27.00 | 0.00700000 | 27.6430 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BOT HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER BOT | 10807.087 | 10807.087 | 0.585375 | 0.00026466 | -999.000 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 10807.09 | 10807.09 | 0.585375 | -27.60 | -27.60 | 0.00034190 | 40.00 | 19.63 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 2.6705 | 24.93 | 0.00098395 | 4.4353 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER MID HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER MID | 103961.649 | 103961.649 | 5.629668 | 0.00254601 | -999.000 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 103961.65 | 103961.65 | 5.629668 | -27.60 | -27.60 | 0.00034190 | 40.00 | 19.63 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 2.7768 | 23.40 | 0.00098397 | 4.8597 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER TOP HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER TOP | 10570.015 | 10570.015 | 0.572441 | 0.00025886 | -999.000 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 10570.02 | 10570.02 | 0.572441 | -27.60 | -27.60 | 0.00034190 | 40.00 | 19.63 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 2.7308 | 21.93 | 0.00098340 | 5.3102 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | 24207.992 | 24207.992 | -999.0 | -999.0 | -999.000 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 24207.99 | 24207.99 | 24.538896 | -0.38 | -0.38 | 0.00690818 | 40.00 | 19.63 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 1.3790 | 27.00 | 0.00700000 | 27.6430 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BOT_SUPPHEATCOIL | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER BOT | 1118.309 | 1118.309 | -999.0 | -999.0 | -999.000 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 1118.31 | 1118.31 | 0.585375 | -0.74 | -5.59 | 0.00096681 | 40.00 | 19.63 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 2.6705 | 24.93 | 0.00098395 | 4.4353 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER MID_SUPPHEATCOIL | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER MID | 11183.090 | 11183.090 | -999.0 | -999.0 | -999.000 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 11183.09 | 11183.09 | 5.629668 | -0.77 | -5.61 | 0.00096614 | 40.00 | 19.63 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 2.7768 | 23.40 | 0.00098397 | 4.8597 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER TOP_SUPPHEATCOIL | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER TOP | 1118.309 | 1118.309 | -999.0 | -999.0 | -999.000 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 1118.31 | 1118.31 | 0.572441 | -0.75 | -5.60 | 0.00096588 | 40.00 | 19.63 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 2.7308 | 21.93 | 0.00098340 | 5.3102 | 0.00 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 08:43:39
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
CORE_BOTTOM VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | CORE_BOTTOM | N/A | N/A | N/A | Yes | Yes | Yes | No | 25791.505 | 25791.505 | 2.034507 | 0.00022564 | 543.507 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 30.11608457 | 54.44 | 82.22 | 27.78 | 3512092.47 | 0.7344 | 0.749142 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 25791.51 | 25791.51 | 1.0000 | 2.14262090 | 2.034507 | 12.80 | 10.41 | 0.00800000 | 33059.8 | 40.00 | 19.63 | 0.00800000 | 60796.0 | 0.22561232 | 60.00 | 32.22 | 27.78 | 0.000 | 25791.51 | -27.60 | 0.00034190 | -27.60 | 0.00000000 | 0.0000 | 20.80 | 0.00799972 | 21.00 | 0.00799972 | 45.2294 | 7875.70 | 0.00 | 25884.64 | 25884.64 | 2.14262090 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 24.65 | 16.19 | 0.00800000 | 45140.7 | |
CORE_MID VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | CORE_MID | N/A | N/A | N/A | Yes | Yes | Yes | No | 515371.914 | 515371.914 | 19.891465 | 0.00450870 | 12910.418 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 30.11608457 | 54.44 | 82.22 | 27.78 | 3512092.47 | 14.6742 | 14.969537 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 515371.91 | 515371.91 | 1.0000 | 20.94849547 | 19.891465 | 12.80 | 10.41 | 0.00800000 | 33059.8 | 40.00 | 19.63 | 0.00800000 | 60796.0 | 4.50823839 | 60.00 | 32.22 | 27.78 | 0.000 | 515371.91 | -27.60 | 0.00034190 | -27.60 | 0.00000000 | 0.0000 | 20.87 | 0.00800000 | 21.00 | 0.00800000 | 45.2310 | 340208.24 | 0.00 | 516976.72 | 516976.72 | 20.94849547 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 37.00 | 20.28 | 0.00800000 | 57738.3 | |
CORE_TOP VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | CORE_TOP | N/A | N/A | N/A | Yes | Yes | Yes | No | 111653.252 | 111653.252 | 3.803763 | 0.00097679 | 2946.068 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 30.11608457 | 54.44 | 82.22 | 27.78 | 3512092.47 | 3.1791 | 3.243090 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 111653.25 | 111653.25 | 1.0000 | 4.00589474 | 3.803763 | 12.80 | 10.41 | 0.00800000 | 33059.8 | 40.00 | 19.63 | 0.00800000 | 60796.0 | 0.97669171 | 60.00 | 32.22 | 27.78 | 0.000 | 111653.25 | -27.60 | 0.00034190 | -27.60 | 0.00000000 | 0.0000 | 20.95 | 0.00800000 | 21.00 | 0.00800000 | 45.2310 | 78157.42 | 0.00 | 112030.21 | 112030.21 | 4.00589474 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.23 | 21.25 | 0.00800000 | 61026.2 | |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | PERIMETER_BOT_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 21629.818 | 21629.818 | 0.737784 | 0.00018923 | 570.400 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 30.11608457 | 54.44 | 82.22 | 27.78 | 3512092.47 | 0.6159 | 0.628262 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 21629.82 | 21629.82 | 1.0000 | 0.77699003 | 0.737784 | 12.80 | 10.41 | 0.00800000 | 33059.8 | 40.00 | 19.63 | 0.00800000 | 60796.0 | 0.18920778 | 60.00 | 32.22 | 27.78 | 0.000 | 21629.82 | -27.60 | 0.00034190 | -27.60 | 0.00000000 | 0.0000 | 20.95 | 0.00779530 | 21.00 | 0.00779530 | 44.0905 | 15136.09 | 0.00 | 21700.53 | 21700.53 | 0.77699003 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.19 | 21.24 | 0.00800000 | 60988.8 | |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | PERIMETER_BOT_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 14800.433 | 14800.433 | 0.504891 | 0.00012948 | 390.283 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 30.11608457 | 54.44 | 82.22 | 27.78 | 3512092.47 | 0.4214 | 0.429895 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 14800.43 | 14800.43 | 1.0000 | 0.53172091 | 0.504891 | 12.80 | 10.41 | 0.00800000 | 33059.8 | 40.00 | 19.63 | 0.00800000 | 60796.0 | 0.12946744 | 60.00 | 32.22 | 27.78 | 0.000 | 14800.43 | -27.60 | 0.00034190 | -27.60 | 0.00000000 | 0.0000 | 20.95 | 0.00780326 | 21.00 | 0.00780326 | 44.1350 | 10356.48 | 0.00 | 14848.68 | 14848.68 | 0.53172091 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.19 | 21.24 | 0.00800000 | 60985.5 | |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | PERIMETER_BOT_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 23695.437 | 23695.437 | 0.808359 | 0.00020730 | 624.831 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 30.11608457 | 54.44 | 82.22 | 27.78 | 3512092.47 | 0.6747 | 0.688260 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 23695.44 | 23695.44 | 1.0000 | 0.85131496 | 0.808359 | 12.80 | 10.41 | 0.00800000 | 33059.8 | 40.00 | 19.63 | 0.00800000 | 60796.0 | 0.20727687 | 60.00 | 32.22 | 27.78 | 0.000 | 23695.44 | -27.60 | 0.00034190 | -27.60 | 0.00000000 | 0.0000 | 20.95 | 0.00781675 | 21.00 | 0.00781675 | 44.2102 | 16580.21 | 0.00 | 23772.60 | 23772.60 | 0.85131496 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.18 | 21.24 | 0.00800000 | 60984.4 | |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | PERIMETER_BOT_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 12601.405 | 12601.405 | 0.429743 | 0.00011024 | 332.342 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 30.11608457 | 54.44 | 82.22 | 27.78 | 3512092.47 | 0.3588 | 0.366021 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 12601.41 | 12601.41 | 1.0000 | 0.45257965 | 0.429743 | 12.80 | 10.41 | 0.00800000 | 33059.8 | 40.00 | 19.63 | 0.00800000 | 60796.0 | 0.11023134 | 60.00 | 32.22 | 27.78 | 0.000 | 12601.41 | -27.60 | 0.00034190 | -27.60 | 0.00000000 | 0.0000 | 20.95 | 0.00775451 | 21.00 | 0.00775451 | 43.8630 | 8819.30 | 0.00 | 12642.82 | 12642.82 | 0.45257965 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.20 | 21.24 | 0.00800000 | 60994.8 | |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | PERIMETER_MID_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 305019.349 | 305019.349 | 10.410358 | 0.00266844 | 8041.455 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 30.11608457 | 54.44 | 82.22 | 27.78 | 3512092.47 | 8.6848 | 8.859618 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 305019.35 | 305019.35 | 1.0000 | 10.96356338 | 10.410358 | 12.80 | 10.41 | 0.00800000 | 33059.8 | 40.00 | 19.63 | 0.00800000 | 60796.0 | 2.66817011 | 60.00 | 32.22 | 27.78 | 0.000 | 305019.35 | -27.60 | 0.00034190 | -27.60 | 0.00000000 | 0.0000 | 20.95 | 0.00767811 | 21.00 | 0.00767811 | 43.4383 | 213421.17 | 0.00 | 306000.54 | 306000.54 | 10.96356338 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.17 | 21.23 | 0.00800000 | 60970.5 | |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | PERIMETER_MID_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 202437.020 | 202437.020 | 6.909475 | 0.00177101 | 5336.906 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 30.11608457 | 54.44 | 82.22 | 27.78 | 3512092.47 | 5.7640 | 5.880003 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 202437.02 | 202437.02 | 1.0000 | 7.27664319 | 6.909475 | 12.80 | 10.41 | 0.00800000 | 33059.8 | 40.00 | 19.63 | 0.00800000 | 60796.0 | 1.77082670 | 60.00 | 32.22 | 27.78 | 0.000 | 202437.02 | -27.60 | 0.00034190 | -27.60 | 0.00000000 | 0.0000 | 20.95 | 0.00767686 | 21.00 | 0.00767686 | 43.4315 | 141642.72 | 0.00 | 203087.54 | 203087.54 | 7.27664319 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.17 | 21.23 | 0.00800000 | 60969.3 | |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | PERIMETER_MID_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 309716.067 | 309716.067 | 10.570846 | 0.00270953 | 8165.212 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 30.11608457 | 54.44 | 82.22 | 27.78 | 3512092.47 | 8.8186 | 8.996039 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 309716.07 | 309716.07 | 1.0000 | 11.13257993 | 10.570846 | 12.80 | 10.41 | 0.00800000 | 33059.8 | 40.00 | 19.63 | 0.00800000 | 60796.0 | 2.70925486 | 60.00 | 32.22 | 27.78 | 0.000 | 309716.07 | -27.60 | 0.00034190 | -27.60 | 0.00000000 | 0.0000 | 20.95 | 0.00768288 | 21.00 | 0.00768288 | 43.4650 | 216704.95 | 0.00 | 310711.88 | 310711.88 | 11.13257993 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.17 | 21.23 | 0.00800000 | 60970.0 | |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | PERIMETER_MID_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 199861.138 | 199861.138 | 6.821494 | 0.00174847 | 5269.019 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 30.11608457 | 54.44 | 82.22 | 27.78 | 3512092.47 | 5.6907 | 5.805184 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 199861.14 | 199861.14 | 1.0000 | 7.18398720 | 6.821494 | 12.80 | 10.41 | 0.00800000 | 33059.8 | 40.00 | 19.63 | 0.00800000 | 60796.0 | 1.74829406 | 60.00 | 32.22 | 27.78 | 0.000 | 199861.14 | -27.60 | 0.00034190 | -27.60 | 0.00000000 | 0.0000 | 20.95 | 0.00767291 | 21.00 | 0.00767291 | 43.4094 | 139841.48 | 0.00 | 200503.54 | 200503.54 | 7.18398720 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.17 | 21.23 | 0.00800000 | 60969.6 | |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | PERIMETER_TOP_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 38505.230 | 38505.230 | 1.314526 | 0.00033686 | 1015.024 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 30.11608457 | 54.44 | 82.22 | 27.78 | 3512092.47 | 1.0964 | 1.118426 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 38505.23 | 38397.36 | 1.0000 | 1.38437933 | 1.314526 | 12.80 | 10.41 | 0.00800000 | 33059.8 | 40.00 | 19.63 | 0.00800000 | 60796.0 | 0.33682619 | 60.00 | 32.22 | 27.78 | 0.000 | 38505.23 | -27.60 | 0.00034190 | -27.60 | 0.00000000 | 0.0000 | 20.95 | 0.00768303 | 21.00 | 0.00768303 | 43.4667 | 26939.43 | 0.00 | 38628.24 | 38628.24 | 1.38437933 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.16 | 21.23 | 0.00800000 | 60962.8 | |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | PERIMETER_TOP_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 25419.301 | 25419.301 | 0.867809 | 0.00022238 | 670.062 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 30.11608457 | 54.44 | 82.22 | 27.78 | 3512092.47 | 0.7238 | 0.738331 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 25419.30 | 25419.30 | 1.0000 | 0.91392446 | 0.867809 | 12.80 | 10.41 | 0.00800000 | 33059.8 | 40.00 | 19.63 | 0.00800000 | 60796.0 | 0.22235645 | 60.00 | 32.22 | 27.78 | 0.000 | 25419.30 | -27.60 | 0.00034190 | -27.60 | 0.00000000 | 0.0000 | 20.95 | 0.00767995 | 21.00 | 0.00767995 | 43.4497 | 17784.01 | 0.00 | 25500.45 | 25500.45 | 0.91392446 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.16 | 21.23 | 0.00800000 | 60962.0 | |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | PERIMETER_TOP_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 39023.780 | 39023.780 | 1.332244 | 0.00034140 | 1028.688 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 30.11608457 | 54.44 | 82.22 | 27.78 | 3512092.47 | 1.1111 | 1.133488 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 39023.78 | 39023.78 | 1.0000 | 1.40303902 | 1.332244 | 12.80 | 10.41 | 0.00800000 | 33059.8 | 40.00 | 19.63 | 0.00800000 | 60796.0 | 0.34136223 | 60.00 | 32.22 | 27.78 | 0.000 | 39023.78 | -27.60 | 0.00034190 | -27.60 | 0.00000000 | 0.0000 | 20.95 | 0.00768705 | 21.00 | 0.00768705 | 43.4892 | 27301.99 | 0.00 | 39148.41 | 39148.41 | 1.40303902 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.16 | 21.23 | 0.00800000 | 60962.4 | |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | PERIMETER_TOP_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 25434.922 | 25434.922 | 0.868347 | 0.00022252 | 670.472 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 30.11608457 | 54.44 | 82.22 | 27.78 | 3512092.47 | 0.7242 | 0.738785 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 25434.92 | 25434.92 | 1.0000 | 0.91449123 | 0.868347 | 12.80 | 10.41 | 0.00800000 | 33059.8 | 40.00 | 19.63 | 0.00800000 | 60796.0 | 0.22249309 | 60.00 | 32.22 | 27.78 | 0.000 | 25434.92 | -27.60 | 0.00034190 | -27.60 | 0.00000000 | 0.0000 | 20.95 | 0.00768035 | 21.00 | 0.00768035 | 43.4519 | 17794.90 | 0.00 | 25516.11 | 25516.11 | 0.91449123 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.16 | 21.23 | 0.00800000 | 60961.8 | |
VAV_BOT WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV_BOT WITH REHEAT | CORE_BOTTOM; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 194585.286 | -999.000 | 11.655704 | 0.00827811 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1018.0073 | 1004.8586 | 1.0531 | VAV_BOT WITH REHEAT FAN | Fan:VariableVolume | 11.655704 | 12.27508703 | 4197.9300 | 999.8980 | 98.93948206 | 12.27 | 6.67 | 5.60 | 2325909.71 | 8.3660 | 8.365986 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | Sensible | 194585.29 | 192505.00 | 1.0000 | 12.27508703 | 11.655704 | 26.05 | 14.53 | 0.00708318 | 44230.5 | 10.68 | 8.51 | 0.00700000 | 28378.4 | 8.27726342 | 6.67 | 12.27 | 5.60 | 26477.019 | 168108.27 | 33.40 | 0.00630683 | 16.37 | 2.53819000 | 21.7764 | 24.00 | 0.00729942 | 24.00 | 0.00729942 | 34.4333 | 139863.93 | 0.00 | 219574.77 | 216437.63 | 12.27508703 | 26.05 | 15.89 | 0.00708318 | 44230.5 | 8.73 | 8.71 | 0.00698165 | 26342.7 | |
VAV_BOT WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV_BOT WITH REHEAT | CORE_BOTTOM; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 101691.050 | 101691.050 | 3.496711 | 0.00088964 | 1578.769 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | VAV_BOT WITH REHEAT FAN | Fan:VariableVolume | 11.655704 | 12.27508703 | 4197.9300 | 999.8980 | 30.11608457 | 54.44 | 82.22 | 27.78 | 3512092.47 | 2.8955 | 2.953727 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 06:30:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 101691.05 | 101691.05 | 1.0000 | 3.68252611 | 3.496711 | -14.68 | -14.68 | 0.00237751 | -8870.9 | 12.80 | 10.41 | 0.00800000 | 33059.8 | 0.88954692 | 60.00 | 32.22 | 27.78 | 0.000 | 101691.05 | -27.60 | 0.00034190 | -27.60 | 2.53819000 | 72.5879 | 19.53 | 0.00776786 | 19.81 | 0.00772998 | 47.0566 | 35041.96 | 0.00 | 83549.98 | 83549.98 | 3.68252611 | 2.80 | -0.60 | 0.00237751 | 8771.9 | 25.28 | 11.04 | 0.00237751 | 31460.2 | |
VAV_MID WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV_MID WITH REHEAT | CORE_MID; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 1817578.773 | -999.000 | 107.831862 | 0.07732400 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1017.9951 | 1004.8586 | 1.0531 | VAV_MID WITH REHEAT FAN | Fan:VariableVolume | 107.831862 | 113.56203407 | 4197.9300 | 999.8980 | 98.93948206 | 12.27 | 6.67 | 5.60 | 2325909.71 | 78.1449 | 78.144855 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | Sensible | 1817578.77 | 1799813.19 | 1.0000 | 113.56203407 | 107.831862 | 26.21 | 14.59 | 0.00707663 | 44383.6 | 10.68 | 8.51 | 0.00700000 | 28378.4 | 77.31611484 | 6.67 | 12.27 | 5.60 | 244950.128 | 1572628.65 | 33.40 | 0.00630683 | 16.37 | 25.38195000 | 23.5385 | 24.00 | 0.00731387 | 24.00 | 0.00731387 | 34.5006 | 1293342.28 | 0.00 | 2049140.46 | 2021722.57 | 113.56203407 | 26.21 | 15.94 | 0.00707663 | 44383.6 | 8.73 | 8.71 | 0.00698071 | 26339.3 | |
VAV_MID WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV_MID WITH REHEAT | CORE_MID; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 1044136.002 | 1044136.002 | 32.349559 | 0.00913456 | 15812.226 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | VAV_MID WITH REHEAT FAN | Fan:VariableVolume | 107.831862 | 113.56203407 | 4197.9300 | 999.8980 | 30.11608457 | 54.44 | 82.22 | 27.78 | 3512092.47 | 29.7297 | 30.328064 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 05:30:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 1044136.00 | 1044136.00 | 1.0000 | 34.06861022 | 32.349559 | -17.70 | -17.70 | 0.00190076 | -13094.4 | 12.80 | 10.41 | 0.00800000 | 33059.8 | 9.13362542 | 60.00 | 32.22 | 27.78 | 0.000 | 1044136.00 | -27.60 | 0.00034190 | -27.60 | 25.38195000 | 78.4615 | 18.36 | 0.00757945 | 17.87 | 0.00757052 | 52.0491 | 383297.13 | 0.00 | 832607.55 | 832607.55 | 34.06861022 | 2.80 | -1.34 | 0.00190076 | 7577.1 | 27.04 | 11.29 | 0.00190076 | 32016.3 | |
VAV_TOP WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV_TOP WITH REHEAT | CORE_TOP; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 203672.512 | -999.000 | 12.300790 | 0.00866470 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1017.9880 | 1004.8586 | 1.0531 | VAV_TOP WITH REHEAT FAN | Fan:VariableVolume | 12.300790 | 12.95445223 | 4197.9300 | 999.8980 | 98.93948206 | 12.27 | 6.67 | 5.60 | 2325909.71 | 8.7567 | 8.756682 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 | Sensible | 203672.51 | 201753.67 | 1.0000 | 12.95445223 | 12.300790 | 25.95 | 14.49 | 0.00707283 | 44100.6 | 10.68 | 8.51 | 0.00700000 | 28378.4 | 8.66381562 | 6.67 | 12.27 | 5.60 | 27942.391 | 175730.12 | 33.40 | 0.00630683 | 16.37 | 2.53819000 | 20.6344 | 24.00 | 0.00727281 | 24.00 | 0.00727281 | 34.3091 | 147175.04 | 0.00 | 230005.32 | 227057.86 | 12.95445223 | 25.95 | 15.84 | 0.00707283 | 44100.6 | 8.73 | 8.71 | 0.00698244 | 26345.7 | |
VAV_TOP WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV_TOP WITH REHEAT | CORE_TOP; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 102308.455 | 102308.455 | 3.690237 | 0.00089504 | 1597.676 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | VAV_TOP WITH REHEAT FAN | Fan:VariableVolume | 12.300790 | 12.95445223 | 4197.9300 | 999.8980 | 30.11608457 | 54.44 | 82.22 | 27.78 | 3512092.47 | 2.9130 | 2.971660 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 01:50:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 102308.46 | 102308.46 | 1.0000 | 3.88633567 | 3.690237 | -13.40 | -13.40 | 0.00257360 | -7090.4 | 12.80 | 10.41 | 0.00800000 | 33059.8 | 0.89494769 | 60.00 | 32.22 | 27.78 | 0.000 | 102308.46 | -27.60 | 0.00034190 | -27.60 | 2.53819000 | 68.7812 | 17.89 | 0.00749047 | 15.98 | 0.00758254 | 58.7469 | 38237.25 | 0.00 | 85150.87 | 85150.87 | 3.88633567 | 2.80 | -0.30 | 0.00257360 | 9263.4 | 24.50 | 10.92 | 0.00257360 | 31173.7 | |
CAV_BAS COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | CAV_BAS | BASEMENT | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 110073.141 | -999.000 | 6.819106 | 0.00468277 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1018.2888 | 1004.8586 | 1.0531 | CAV_BAS FAN | Fan:ConstantVolume | 6.819106 | 7.18147197 | 4197.9300 | 999.8980 | 98.93948206 | 12.27 | 6.67 | 5.60 | 2325909.71 | 4.7325 | 4.732477 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:00:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:00:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | Sensible | 110073.14 | 106760.32 | 1.0000 | 7.18147197 | 6.819106 | 25.70 | 14.54 | 0.00723461 | 44263.5 | 11.23 | 8.74 | 0.00700000 | 28936.1 | 4.68228819 | 6.67 | 12.27 | 5.60 | 11488.247 | 98584.89 | 32.60 | 0.00630558 | 16.10 | 1.20015641 | 17.5999 | 24.00 | 0.00746371 | 24.00 | 0.00746371 | 35.1995 | 72830.29 | 0.00 | 124296.80 | 122031.40 | 7.18147197 | 25.70 | 15.90 | 0.00723461 | 44263.5 | 9.01 | 8.98 | 0.00710932 | 26955.5 | |
CAV_BAS HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | CAV_BAS | BASEMENT | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 323708.581 | 323708.581 | 6.819106 | 0.00283194 | 6941.245 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | CAV_BAS FAN | Fan:ConstantVolume | 6.819106 | 7.18147197 | 4197.9300 | 999.8980 | 30.11608457 | 54.44 | 82.22 | 27.78 | 3512092.47 | 9.2170 | 9.402467 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 323708.58 | 323708.58 | 1.0000 | 7.18147197 | 6.819106 | -4.86 | -9.35 | 0.00034190 | -4029.1 | 40.00 | 19.63 | 0.00800000 | 60796.0 | 2.83165499 | 60.00 | 32.22 | 27.78 | 0.000 | 323708.58 | -27.60 | 0.00034190 | -27.60 | 1.20015641 | 17.5999 | 0.00 | 0.00034190 | 22.86 | 0.00034190 | 1.7470 | 0.00 | 0.00 | 258881.68 | 258881.68 | 7.18147197 | 12.80 | 2.46 | 0.00034190 | 13725.2 | 48.65 | 17.96 | 0.00034190 | 49773.7 | |
AIRLOOP DATACENTER BASEMENT COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | DATACENTER_BASEMENT_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 466437.893 | 262502.939 | 24.538896 | 0.01142303 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1017.9118 | 1004.8586 | 1.0531 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 07:10:00 | Sensible | 405303.45 | 403832.34 | 0.8689 | -999.0 | -999.0 | 28.68 | 15.39 | 0.00703181 | 46778.9 | 12.80 | 9.41 | 0.00700000 | 30535.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 405303.45 | 33.40 | 0.00630683 | 16.37 | 0.33839277 | -999.0000 | 27.00 | 0.00704196 | 27.00 | 0.00704196 | 27.8114 | 373034.82 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BOT COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BOT | DATACENTER_BOT_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 10807.087 | 6147.885 | 0.585375 | 0.00026466 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1017.9641 | 1004.8586 | 1.0531 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:30:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:30:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:30:00 | Sensible | 9339.78 | 9274.26 | 0.8642 | -999.0 | -999.0 | 28.06 | 15.21 | 0.00705998 | 46221.7 | 12.80 | 9.41 | 0.00700000 | 30535.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9339.78 | 26.28 | 0.00629588 | 13.94 | 0.01563234 | -999.0000 | 27.00 | 0.00708094 | 27.00 | 0.00708094 | 27.9616 | 8909.34 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER MID COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER MID | DATACENTER_MID_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 103961.649 | 59130.970 | 5.629668 | 0.00254601 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1017.9683 | 1004.8586 | 1.0531 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:30:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:30:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:30:00 | Sensible | 89850.72 | 89196.79 | 0.8643 | -999.0 | -999.0 | 28.06 | 15.21 | 0.00706223 | 46226.7 | 12.80 | 9.41 | 0.00700000 | 30535.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 89850.72 | 26.28 | 0.00629588 | 13.94 | 0.15632344 | -999.0000 | 27.00 | 0.00708412 | 27.00 | 0.00708412 | 27.9741 | 85682.56 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER TOP COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER TOP | DATACENTER_TOP_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 10570.015 | 6012.389 | 0.572441 | 0.00025886 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1017.9667 | 1004.8586 | 1.0531 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:30:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:30:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:30:00 | Sensible | 9135.16 | 9069.63 | 0.8643 | -999.0 | -999.0 | 28.06 | 15.21 | 0.00706134 | 46224.7 | 12.80 | 9.41 | 0.00700000 | 30535.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9135.16 | 26.28 | 0.00629588 | 13.94 | 0.01563234 | -999.0000 | 27.00 | 0.00708283 | 27.00 | 0.00708283 | 27.9690 | 8712.47 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BASEMENT HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | DATACENTER_BASEMENT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 466437.893 | 466437.893 | 24.538896 | 0.01142303 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 1.0531 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 466437.89 | 466437.89 | 1.0000 | 25.84289049 | 24.538896 | -27.60 | -27.60 | 0.00034190 | -26896.1 | 40.00 | 19.63 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 466437.89 | -27.60 | 0.00034190 | -27.60 | 0.33839277 | 1.3790 | 0.00 | 0.00700000 | 27.00 | 0.00700000 | 27.6430 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BOT HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BOT | DATACENTER_BOT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 10807.087 | 10807.087 | 0.585375 | 0.00026466 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 1.0531 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 10807.09 | 10807.09 | 1.0000 | 0.61648127 | 0.585375 | -27.60 | -27.60 | 0.00034190 | -26896.1 | 40.00 | 19.63 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 10807.09 | -27.60 | 0.00034190 | -27.60 | 0.01563234 | 2.6705 | 0.00 | 0.00098395 | 24.93 | 0.00098395 | 4.4353 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER MID HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER MID | DATACENTER_MID_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 103961.649 | 103961.649 | 5.629668 | 0.00254601 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 1.0531 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 103961.65 | 103961.65 | 1.0000 | 5.92882784 | 5.629668 | -27.60 | -27.60 | 0.00034190 | -26896.1 | 40.00 | 19.63 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 103961.65 | -27.60 | 0.00034190 | -27.60 | 0.15632344 | 2.7768 | 0.00 | 0.00098397 | 23.40 | 0.00098397 | 4.8597 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER TOP HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER TOP | DATACENTER_TOP_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 10570.015 | 10570.015 | 0.572441 | 0.00025886 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 1.0531 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 10570.02 | 10570.02 | 1.0000 | 0.60285998 | 0.572441 | -27.60 | -27.60 | 0.00034190 | -26896.1 | 40.00 | 19.63 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 10570.02 | -27.60 | 0.00034190 | -27.60 | 0.01563234 | 2.7308 | 0.00 | 0.00098340 | 21.93 | 0.00098340 | 5.3102 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | DATACENTER_BASEMENT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 24207.992 | 24207.992 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | AIRLOOP DATACENTER BASEMENT SUPPLY FAN | Fan:OnOff | 24.538896 | 25.84289049 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 24207.99 | 24207.99 | 1.0000 | 25.84289049 | 24.538896 | -0.38 | -0.38 | 0.00690818 | 16889.6 | 40.00 | 19.63 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 24207.99 | -27.60 | 0.00034190 | -27.60 | 0.33839277 | 1.3790 | 0.00 | 0.00700000 | 27.00 | 0.00700000 | 27.6430 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BOT_SUPPHEATCOIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BOT | DATACENTER_BOT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 1118.309 | 1118.309 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | AIRLOOP DATACENTER BOT SUPPLY FAN | Fan:OnOff | 0.585375 | 0.61648127 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 1118.31 | 1118.31 | 1.0000 | 0.61648127 | 0.585375 | -0.74 | -5.59 | 0.00096681 | 1676.0 | 40.00 | 19.63 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 1118.31 | -27.60 | 0.00034190 | -27.60 | 0.01563234 | 2.6705 | 0.00 | 0.00098395 | 24.93 | 0.00098395 | 4.4353 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER MID_SUPPHEATCOIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER MID | DATACENTER_MID_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 11183.090 | 11183.090 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | AIRLOOP DATACENTER MID SUPPLY FAN | Fan:OnOff | 5.629668 | 5.92882784 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 11183.09 | 11183.09 | 1.0000 | 5.92882784 | 5.629668 | -0.77 | -5.61 | 0.00096614 | 1644.8 | 40.00 | 19.63 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 11183.09 | -27.60 | 0.00034190 | -27.60 | 0.15632344 | 2.7768 | 0.00 | 0.00098397 | 23.40 | 0.00098397 | 4.8597 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER TOP_SUPPHEATCOIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER TOP | DATACENTER_TOP_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 1118.309 | 1118.309 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | AIRLOOP DATACENTER TOP SUPPLY FAN | Fan:OnOff | 0.572441 | 0.60285998 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 1118.31 | 1118.31 | 1.0000 | 0.60285998 | 0.572441 | -0.75 | -5.60 | 0.00096588 | 1656.9 | 40.00 | 19.63 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 1118.31 | -27.60 | 0.00034190 | -27.60 | 0.01563234 | 2.7308 | 0.00 | 0.00098340 | 21.93 | 0.00098340 | 5.3102 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 08:43:39
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
VAV_BOT WITH REHEAT_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 11.66 | - | |||
VAV_MID WITH REHEAT_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 107.83 | - | |||
VAV_TOP WITH REHEAT_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 12.30 | - | |||
CAV_BAS_OA_CONTROLLER | DifferentialDryBulb | 1.20 | 6.82 | - | |||
AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER | DifferentialDryBulb | 0.34 | 24.54 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
CORE_BOTTOM | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_MID | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_TOP | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
BASEMENT | 1603.83 | 1464.67 | 35.67 |
CORE_BOTTOM | 1428.67 | 1624.00 | 24.17 |
CORE_MID | 1043.00 | 3492.50 | 279.50 |
CORE_TOP | 1811.17 | 4127.83 | 1099.67 |
PERIMETER_BOT_ZN_3 | 1854.17 | 3872.67 | 824.67 |
PERIMETER_BOT_ZN_2 | 2307.67 | 3729.17 | 967.50 |
PERIMETER_BOT_ZN_1 | 2523.83 | 3195.67 | 851.00 |
PERIMETER_BOT_ZN_4 | 2519.17 | 2904.33 | 574.00 |
PERIMETER_MID_ZN_3 | 2897.33 | 4451.83 | 2186.67 |
PERIMETER_MID_ZN_2 | 2678.17 | 3625.83 | 1774.00 |
PERIMETER_MID_ZN_1 | 2891.67 | 3611.00 | 1426.50 |
PERIMETER_MID_ZN_4 | 2977.50 | 4240.67 | 1842.17 |
PERIMETER_TOP_ZN_3 | 3418.17 | 4632.17 | 2736.00 |
PERIMETER_TOP_ZN_2 | 3541.17 | 4262.67 | 2409.00 |
PERIMETER_TOP_ZN_1 | 3213.83 | 3890.83 | 1907.67 |
PERIMETER_TOP_ZN_4 | 3373.67 | 4433.33 | 2330.50 |
DATACENTER_BOT_ZN_6 | 5801.83 | 564.83 | 563.50 |
DATACENTER_MID_ZN_6 | 5201.17 | 291.50 | 137.33 |
DATACENTER_TOP_ZN_6 | 4561.83 | 649.00 | 239.33 |
DATACENTER_BASEMENT_ZN_6 | 5943.00 | 5705.33 | 5705.33 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
Facility | 5943.00 | 5943.00 | 5938.00 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
BASEMENT | 0.00 | 45.67 | 0.00 | 2.83 |
CORE_BOTTOM | 0.00 | 2.17 | 0.00 | 0.00 |
CORE_MID | 0.33 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 17.17 | 0.00 | 2.67 | 0.00 |
PERIMETER_BOT_ZN_3 | 9.67 | 7.17 | 1.00 | 5.17 |
PERIMETER_BOT_ZN_2 | 10.67 | 27.33 | 0.50 | 27.00 |
PERIMETER_BOT_ZN_1 | 12.00 | 45.83 | 0.67 | 43.50 |
PERIMETER_BOT_ZN_4 | 3.83 | 65.50 | 0.00 | 29.67 |
PERIMETER_MID_ZN_3 | 147.17 | 4.67 | 46.17 | 3.67 |
PERIMETER_MID_ZN_2 | 91.83 | 27.33 | 12.17 | 26.67 |
PERIMETER_MID_ZN_1 | 67.50 | 40.50 | 7.17 | 38.00 |
PERIMETER_MID_ZN_4 | 72.67 | 31.83 | 9.83 | 14.67 |
PERIMETER_TOP_ZN_3 | 332.33 | 7.17 | 115.33 | 5.00 |
PERIMETER_TOP_ZN_2 | 198.67 | 27.67 | 36.83 | 25.50 |
PERIMETER_TOP_ZN_1 | 158.00 | 31.83 | 22.67 | 28.33 |
PERIMETER_TOP_ZN_4 | 160.33 | 30.83 | 29.83 | 14.33 |
DATACENTER_BOT_ZN_6 | 0.00 | 9.00 | 0.00 | 4.67 |
DATACENTER_MID_ZN_6 | 0.00 | 5.00 | 0.00 | 2.67 |
DATACENTER_TOP_ZN_6 | 0.00 | 6.50 | 0.00 | 2.83 |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 112.50 | 0.00 | 105.50 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 407.33 | 344.50 | 133.17 | 247.83 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 08:43:39
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 60.99 | 149.60 | 6779.02 | 1.395 | 0.000 | 0.000 | 0.000 |
CORE_BOTTOM | 54.77 | 134.35 | 6849.35 | 1.024 | 0.000 | 0.000 | 0.000 |
CORE_MID | 54.77 | 134.35 | 6849.35 | 0.760 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 54.77 | 134.35 | 6849.35 | 0.707 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 6.88 | 16.87 | 860.00 | 0.894 | 0.059 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 4.43 | 10.87 | 554.22 | 1.700 | 0.061 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 6.88 | 16.87 | 860.02 | 1.704 | 0.059 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 4.43 | 10.87 | 554.22 | 2.123 | 0.061 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 6.88 | 16.87 | 860.00 | 0.731 | 0.137 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 3.86 | 10.87 | 554.22 | 1.538 | 0.151 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 6.88 | 16.87 | 860.02 | 1.614 | 0.138 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 4.43 | 10.87 | 554.22 | 1.635 | 0.142 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 6.88 | 16.87 | 860.00 | 0.757 | 0.170 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 4.43 | 10.87 | 554.22 | 1.646 | 0.176 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 6.88 | 16.87 | 860.02 | 1.591 | 0.171 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 4.43 | 10.87 | 554.22 | 1.668 | 0.176 | 0.000 | 0.000 |
DATACENTER_BOT_ZN_6 | 0.79 | 1.95 | 99.34 | 0.426 | 0.000 | 0.000 | 0.000 |
DATACENTER_MID_ZN_6 | 0.79 | 1.95 | 99.34 | 0.426 | 0.000 | 0.000 | 0.000 |
DATACENTER_TOP_ZN_6 | 0.79 | 1.95 | 99.34 | 0.426 | 0.000 | 0.000 | 0.000 |
DATACENTER_BASEMENT_ZN_6 | 17.20 | 42.18 | 1911.37 | 26.939 | 0.000 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 60.99 | 149.60 | 6779.02 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_BOTTOM | 54.77 | 134.35 | 6849.35 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_MID | 54.77 | 134.35 | 6849.35 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 54.77 | 134.35 | 6849.35 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 6.88 | 16.87 | 860.00 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 4.43 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 6.88 | 16.87 | 860.02 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 4.43 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 6.88 | 16.87 | 860.00 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 3.86 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 6.88 | 16.87 | 860.02 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 4.43 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 6.88 | 16.87 | 860.00 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 4.43 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 6.88 | 16.87 | 860.02 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 4.43 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
DATACENTER_BOT_ZN_6 | 0.79 | 1.95 | 99.34 | 0.000 | 0.000 | 0.000 | 0.000 |
DATACENTER_MID_ZN_6 | 0.79 | 1.95 | 99.34 | 0.000 | 0.000 | 0.000 | 0.000 |
DATACENTER_TOP_ZN_6 | 0.79 | 1.95 | 99.34 | 0.000 | 0.000 | 0.000 | 0.000 |
DATACENTER_BASEMENT_ZN_6 | 17.20 | 42.18 | 1911.37 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 08:43:39
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
BASEMENT | CAV_BAS | 60.99 | 149.60 | 6779.02 | 2779.43 | 1.2002 | 1.200 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | 54.77 | 134.35 | 6849.35 | 2496.12 | 0.0000 | 1.078 |
CORE_MID | VAV_MID WITH REHEAT | 54.77 | 134.35 | 6849.35 | 2496.12 | 0.0000 | 10.778 |
CORE_TOP | VAV_TOP WITH REHEAT | 54.77 | 134.35 | 6849.35 | 2496.12 | 0.0000 | 1.078 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | 6.88 | 16.87 | 860.00 | 313.41 | 0.0000 | 0.135 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | 4.43 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | 6.88 | 16.87 | 860.02 | 313.42 | 0.0000 | 0.135 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | 4.43 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | 6.88 | 16.87 | 860.00 | 313.41 | 0.0000 | 1.353 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | 3.86 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.872 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | 6.88 | 16.87 | 860.02 | 313.42 | 0.0000 | 1.353 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | 4.43 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.872 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | 6.88 | 16.87 | 860.00 | 313.41 | 0.0000 | 0.135 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | 4.43 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | 6.88 | 16.87 | 860.02 | 313.42 | 0.0000 | 0.135 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | 4.43 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | 0.79 | 1.95 | 99.34 | 36.20 | 0.0156 | 0.016 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | 0.79 | 1.95 | 99.34 | 36.20 | 0.1563 | 0.156 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | 0.79 | 1.95 | 99.34 | 36.20 | 0.0156 | 0.016 |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | 17.20 | 42.18 | 1911.37 | 783.68 | 0.3384 | 0.338 |
Total Facility | 1010.73 | 2493.19 | 126016.35 | 46320.38 | 1.7261 | 158.471 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
BASEMENT | 57494912.73 | 0.00 | 57494912.73 | 0.00 | 57494912.73 | 37848132.68 | 3959.99 | 896.82 | 3903.19 | 332.29 |
CORE_BOTTOM | 43160571.91 | 0.00 | 43160571.91 | 0.00 | 43160571.91 | 33990283.35 | 4681.30 | 48.68 | 4030.02 | 399.69 |
CORE_MID | 0.31E+09 | 0.00 | 0.31E+09 | 0.00 | 0.31E+09 | 0.34E+09 | 6024.66 | 36.50 | 2698.84 | 414.77 |
CORE_TOP | 29176249.77 | 0.00 | 29176249.77 | 0.00 | 29176249.77 | 33990283.35 | 6440.05 | 31.74 | 2288.21 | 445.71 |
PERIMETER_BOT_ZN_3 | 4752044.62 | 0.00 | 4752044.62 | 591585.02 | 5343629.63 | 4267819.30 | 5540.33 | 60.41 | 3159.26 | 399.69 |
PERIMETER_BOT_ZN_2 | 5838426.77 | 0.00 | 5838426.77 | 394389.74 | 6232816.52 | 2750345.05 | 3551.63 | 3.34 | 5205.03 | 399.69 |
PERIMETER_BOT_ZN_1 | 8970240.15 | 0.00 | 8970240.15 | 591585.02 | 9561825.16 | 4267912.63 | 3593.90 | 6.57 | 5159.53 | 399.69 |
PERIMETER_BOT_ZN_4 | 7320692.06 | 0.00 | 7320692.06 | 394389.74 | 7715081.80 | 2750345.05 | 3527.16 | 0.00 | 5232.84 | 399.69 |
PERIMETER_MID_ZN_3 | 38220727.13 | 0.00 | 38220727.13 | 1387434.57 | 39608161.70 | 42678193.03 | 5776.38 | 60.56 | 2923.06 | 414.77 |
PERIMETER_MID_ZN_2 | 56423681.78 | 0.00 | 56423681.78 | 924955.75 | 57348637.53 | 27503450.52 | 3836.69 | 4.59 | 4918.72 | 1323.77 |
PERIMETER_MID_ZN_1 | 83367049.12 | 0.00 | 83367049.12 | 1387434.57 | 84754483.69 | 42679126.28 | 3920.47 | 8.38 | 4831.15 | 414.77 |
PERIMETER_MID_ZN_4 | 55335610.26 | 0.00 | 55335610.26 | 924955.75 | 56260566.01 | 27503450.52 | 3826.60 | 5.08 | 4928.32 | 414.77 |
PERIMETER_TOP_ZN_3 | 3938203.88 | 0.00 | 3938203.88 | 1722650.34 | 5660854.22 | 4267819.30 | 5583.42 | 62.17 | 3114.41 | 445.71 |
PERIMETER_TOP_ZN_2 | 5486196.59 | 0.00 | 5486196.59 | 1148432.78 | 6634629.37 | 2750345.05 | 3996.72 | 4.80 | 4758.48 | 445.71 |
PERIMETER_TOP_ZN_1 | 8189431.26 | 0.00 | 8189431.26 | 1722650.34 | 9912081.60 | 4267912.63 | 4047.97 | 3.03 | 4709.00 | 445.71 |
PERIMETER_TOP_ZN_4 | 5607707.39 | 0.00 | 5607707.39 | 1148432.78 | 6756140.16 | 2750345.05 | 3967.34 | 8.09 | 4784.57 | 445.71 |
DATACENTER_BOT_ZN_6 | 244296.02 | 0.00 | 244296.02 | 0.00 | 244296.02 | 492981.60 | 4419.00 | 4341.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 2442960.18 | 0.00 | 2442960.18 | 0.00 | 2442960.18 | 4929815.99 | 4419.00 | 4341.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 244296.02 | 0.00 | 244296.02 | 0.00 | 244296.02 | 492981.60 | 4419.00 | 4341.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.42E+09 | 0.00 | 0.42E+09 | 0.00 | 0.42E+09 | 10671554.30 | 51.83 | 192.83 | 8515.33 | 2801.17 |
Total Facility | 0.61E+10 | 0.00 | 0.61E+10 | 53961922.12 | 0.62E+10 | 0.50E+10 | 6835.83 | 4403.28 | 8708.33 | 3710.17 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
BASEMENT | 2.5773 | 0.0000 | 2.5773 | 0.0000 | 2.5773 | 1.2002 | 1328.13 | 893.03 | 3721.84 |
CORE_BOTTOM | 1.9121 | 0.0000 | 1.9121 | 0.0000 | 1.9121 | 1.0778 | 2134.76 | 46.43 | 3761.81 |
CORE_MID | 14.1905 | 0.0000 | 14.1905 | 0.0000 | 14.1905 | 10.7782 | 3305.73 | 36.19 | 2601.09 |
CORE_TOP | 1.3230 | 0.0000 | 1.3230 | 0.0000 | 1.3230 | 1.0778 | 3703.76 | 31.68 | 2207.56 |
PERIMETER_BOT_ZN_3 | 0.2099 | 0.0000 | 0.2099 | 0.0139 | 0.2237 | 0.1353 | 2988.61 | 57.96 | 2896.43 |
PERIMETER_BOT_ZN_2 | 0.2574 | 0.0000 | 0.2574 | 0.0092 | 0.2666 | 0.0872 | 1077.34 | 2.84 | 4862.82 |
PERIMETER_BOT_ZN_1 | 0.4000 | 0.0000 | 0.4000 | 0.0139 | 0.4139 | 0.1353 | 1107.76 | 4.93 | 4830.31 |
PERIMETER_BOT_ZN_4 | 0.3211 | 0.0000 | 0.3211 | 0.0092 | 0.3304 | 0.0872 | 1060.61 | 0.00 | 4882.39 |
PERIMETER_MID_ZN_3 | 1.7192 | 0.0000 | 1.7192 | 0.0325 | 1.7517 | 1.3533 | 3067.89 | 59.36 | 2815.75 |
PERIMETER_MID_ZN_2 | 2.3326 | 0.0000 | 2.3326 | 0.0230 | 2.3555 | 0.8721 | 1194.44 | 2.00 | 3837.55 |
PERIMETER_MID_ZN_1 | 3.7929 | 0.0000 | 3.7929 | 0.0325 | 3.8254 | 1.3533 | 1239.42 | 4.77 | 4698.81 |
PERIMETER_MID_ZN_4 | 2.4815 | 0.0000 | 2.4815 | 0.0217 | 2.5032 | 0.8721 | 1191.42 | 2.59 | 4748.99 |
PERIMETER_TOP_ZN_3 | 0.1783 | 0.0000 | 0.1783 | 0.0404 | 0.2187 | 0.1353 | 2854.49 | 61.35 | 3027.16 |
PERIMETER_TOP_ZN_2 | 0.2495 | 0.0000 | 0.2495 | 0.0269 | 0.2765 | 0.0872 | 1298.16 | 2.95 | 4641.89 |
PERIMETER_TOP_ZN_1 | 0.3740 | 0.0000 | 0.3740 | 0.0404 | 0.4144 | 0.1353 | 1329.73 | 2.10 | 4611.16 |
PERIMETER_TOP_ZN_4 | 0.2531 | 0.0000 | 0.2531 | 0.0269 | 0.2801 | 0.0872 | 1276.91 | 6.05 | 4660.04 |
DATACENTER_BOT_ZN_6 | 0.0114 | 0.0000 | 0.0114 | 0.0000 | 0.0114 | 0.0156 | 1602.00 | 4341.00 | 0.00 |
DATACENTER_MID_ZN_6 | 0.1142 | 0.0000 | 0.1142 | 0.0000 | 0.1142 | 0.1563 | 1602.00 | 4341.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 0.0114 | 0.0000 | 0.0114 | 0.0000 | 0.0114 | 0.0156 | 1602.00 | 4341.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 13.8666 | 0.0000 | 13.8666 | 0.0000 | 13.8666 | 0.3384 | 36.00 | 192.83 | 5714.17 |
Total Facility | 268.2529 | 0.0000 | 268.2529 | 1.2778 | 269.5307 | 158.4706 | 4018.83 | 4380.00 | 5907.17 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
VAV_BOT WITH REHEAT | 77683824.34 | 0.00 | 77683824.34 | 48026705.38 | 3654.69 | 8.97 | 5096.34 | 399.69 |
VAV_MID WITH REHEAT | 0.61E+09 | 0.00 | 0.61E+09 | 0.48E+09 | 4006.27 | 6.93 | 4746.80 | 414.77 |
VAV_TOP WITH REHEAT | 58114575.87 | 0.00 | 58114575.87 | 48026705.38 | 4087.63 | 1.83 | 4670.54 | 445.37 |
CAV_BAS | 63767815.09 | 0.00 | 63767815.09 | 37848132.68 | 3937.12 | 4.00 | 4818.88 | 332.29 |
AIRLOOP DATACENTER BASEMENT | 0.47E+09 | 0.00 | 0.47E+09 | 10671554.30 | 51.83 | 0.00 | 8708.17 | 2801.17 |
AIRLOOP DATACENTER BOT | 270949.60 | 0.00 | 270949.60 | 492981.60 | 4419.00 | 0.00 | 4341.00 | 0.00 |
AIRLOOP DATACENTER MID | 2709495.95 | 0.00 | 2709495.95 | 4929815.99 | 4419.00 | 0.00 | 4341.00 | 0.00 |
AIRLOOP DATACENTER TOP | 270949.60 | 0.00 | 270949.60 | 492981.60 | 4419.00 | 0.00 | 4341.00 | 0.00 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
VAV_BOT WITH REHEAT | 3.4387 | 0.0000 | 3.4387 | 1.5229 | 1142.71 | 6.65 | 4793.64 |
VAV_MID WITH REHEAT | 27.4331 | 0.0000 | 27.4331 | 15.2292 | 1298.37 | 5.58 | 4639.05 |
VAV_TOP WITH REHEAT | 2.6374 | 0.0000 | 2.6374 | 1.5229 | 1356.92 | 0.92 | 4585.16 |
CAV_BAS | 2.8584 | 0.0000 | 2.8584 | 1.2002 | 1318.90 | 1.57 | 4622.53 |
AIRLOOP DATACENTER BASEMENT | 15.3795 | 0.0000 | 15.3795 | 0.3384 | 36.00 | 0.00 | 5907.00 |
AIRLOOP DATACENTER BOT | 0.0127 | 0.0000 | 0.0127 | 0.0156 | 1602.00 | 0.00 | 4341.00 |
AIRLOOP DATACENTER MID | 0.1266 | 0.0000 | 0.1266 | 0.1563 | 1602.00 | 0.00 | 4341.00 |
AIRLOOP DATACENTER TOP | 0.0127 | 0.0000 | 0.0127 | 0.0156 | 1602.00 | 0.00 | 4341.00 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
VAV_BOT WITH REHEAT | 0.00 | 0.00 | 3917.15 | 0.00 | 0.00 | 0.00 | 1394.08 | 0.00 | 0.00 | 0.00 |
VAV_MID WITH REHEAT | 0.00 | 0.00 | 3883.90 | 0.00 | 0.00 | 0.00 | 1409.14 | 0.00 | 0.00 | 0.00 |
VAV_TOP WITH REHEAT | 0.00 | 0.00 | 3142.97 | 0.00 | 0.00 | 0.00 | 2162.22 | 0.00 | 0.00 | 0.00 |
CAV_BAS | 0.00 | 885.42 | 4113.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER BASEMENT | 0.00 | 192.83 | 8515.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER BOT | 0.00 | 4341.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER MID | 0.00 | 4341.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER TOP | 0.00 | 4341.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
VAV_BOT WITH REHEAT | 0.0000 | 0.0000 | 5.0401 | 0.0000 | 0.0000 | 0.0000 | 1.9442 | 0.0000 | 0.0000 | 0.0000 |
VAV_MID WITH REHEAT | 0.0000 | 0.0000 | 39.2611 | 0.0000 | 0.0000 | 0.0000 | 19.0475 | 0.0000 | 0.0000 | 0.0000 |
VAV_TOP WITH REHEAT | 0.0000 | 0.0000 | 4.3023 | 0.0000 | 0.0000 | 0.0000 | 1.8830 | 0.0000 | 0.0000 | 0.0000 |
CAV_BAS | 0.0000 | 1.3317 | 4.1823 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
AIRLOOP DATACENTER BASEMENT | 0.0000 | 0.3769 | 15.9832 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
AIRLOOP DATACENTER BOT | 0.0000 | 0.0173 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
AIRLOOP DATACENTER MID | 0.0000 | 0.1734 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
AIRLOOP DATACENTER TOP | 0.0000 | 0.0173 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 08:43:39
Surfaces by ClassTotal | Outdoors | |
Wall | 98 | 30 |
Floor | 41 | 0 |
Roof | 30 | 1 |
Internal Mass | 16 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 24 | 24 |
Door | 12 | 12 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 8 |
Conditioned Zones | 23 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 3 |
Count | |
IDF Objects | 1395 |
Defaulted Fields | 1182 |
Fields with Defaults | 3867 |
Autosized Fields | 332 |
Autosizable Fields | 411 |
Autocalculated Fields | 226 |
Autocalculatable Fields | 473 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 08:43:39
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 28638.04 | 343584.99 | 21-MAY-04:50 | 2225335.88 | 07-AUG-15:40 |
Electricity:Building | 18609.81 | 225715.65 | 06-MAY-18:10 | 1164206.62 | 01-DEC-08:10 |
Electricity:Zone:BASEMENT | 687.24 | 14732.47 | 01-JAN-00:10 | 36407.88 | 02-JAN-08:10 |
Electricity:SpaceType:GENERAL | 18609.81 | 225715.65 | 06-MAY-18:10 | 1164206.62 | 01-DEC-08:10 |
InteriorLights:Electricity | 3933.41 | 18459.50 | 01-JAN-10:30 | 385834.94 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:BASEMENT | 262.84 | 1274.92 | 01-JAN-00:10 | 22950.34 | 02-JAN-08:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 3933.41 | 18459.50 | 01-JAN-10:30 | 385834.94 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity | 3933.41 | 18459.50 | 01-JAN-10:30 | 385834.94 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:BASEMENT | 262.84 | 1274.92 | 01-JAN-00:10 | 22950.34 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 3933.41 | 18459.50 | 01-JAN-10:30 | 385834.94 | 02-JAN-08:10 |
Electricity:Zone:CORE_BOTTOM | 525.67 | 5598.20 | 01-JAN-00:10 | 37817.64 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_BOTTOM | 236.05 | 1144.97 | 01-JAN-00:10 | 20611.01 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_BOTTOM | 236.05 | 1144.97 | 01-JAN-00:10 | 20611.01 | 02-JAN-08:10 |
Electricity:Zone:CORE_MID | 5256.66 | 55981.88 | 01-JAN-00:10 | 378175.77 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_MID | 2360.53 | 11449.71 | 01-JAN-00:10 | 206110.14 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_MID | 2360.53 | 11449.71 | 01-JAN-00:10 | 206110.14 | 02-JAN-08:10 |
Electricity:Zone:CORE_TOP | 525.67 | 5598.19 | 01-JAN-00:10 | 37817.58 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_TOP | 236.05 | 1144.97 | 01-JAN-00:10 | 20611.01 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_TOP | 236.05 | 1144.97 | 01-JAN-00:10 | 20611.01 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_3 | 53.94 | 627.57 | 19-MAR-17:10 | 4748.47 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 17.57 | 68.40 | 01-JAN-10:30 | 2587.92 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 17.57 | 68.40 | 01-JAN-10:30 | 2587.92 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_2 | 34.60 | 404.43 | 26-MAR-17:10 | 3060.10 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 11.16 | 44.08 | 01-JAN-08:50 | 1667.75 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 11.16 | 44.08 | 01-JAN-08:50 | 1667.75 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_1 | 53.54 | 627.58 | 12-MAR-17:10 | 4748.56 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 17.17 | 68.40 | 01-JAN-08:50 | 2587.98 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 17.17 | 68.40 | 01-JAN-08:50 | 2587.98 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_4 | 34.63 | 404.43 | 12-MAR-17:10 | 3060.09 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 11.20 | 44.08 | 01-JAN-10:20 | 1667.75 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 11.20 | 44.08 | 01-JAN-10:20 | 1667.75 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_MID_ZN_3 | 539.00 | 6275.73 | 12-MAR-17:10 | 47484.70 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 175.35 | 684.02 | 01-JAN-10:20 | 25879.19 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 175.35 | 684.02 | 01-JAN-10:20 | 25879.19 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_MID_ZN_2 | 345.83 | 4044.32 | 26-MAR-17:10 | 30600.95 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 111.48 | 440.81 | 01-JAN-08:50 | 16677.53 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 111.48 | 440.81 | 01-JAN-08:50 | 16677.53 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_MID_ZN_1 | 535.20 | 6275.83 | 12-MAR-17:10 | 47485.60 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 171.54 | 684.04 | 01-JAN-08:50 | 25879.75 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 171.54 | 684.04 | 01-JAN-08:50 | 25879.75 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_MID_ZN_4 | 346.16 | 4044.30 | 12-MAR-17:10 | 30600.86 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 111.80 | 440.81 | 01-JAN-10:10 | 16677.53 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 111.80 | 440.81 | 01-JAN-10:10 | 16677.53 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_3 | 53.90 | 627.57 | 12-MAR-17:10 | 4748.47 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 17.53 | 68.40 | 01-JAN-10:20 | 2587.92 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 17.53 | 68.40 | 01-JAN-10:20 | 2587.92 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_2 | 34.58 | 404.43 | 26-MAR-17:10 | 3060.10 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 11.15 | 44.08 | 01-JAN-08:50 | 1667.75 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 11.15 | 44.08 | 01-JAN-08:50 | 1667.75 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_1 | 53.52 | 627.58 | 12-MAR-17:10 | 4748.56 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 17.15 | 68.40 | 01-JAN-08:50 | 2587.98 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 17.15 | 68.40 | 01-JAN-08:50 | 2587.98 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_4 | 34.62 | 404.43 | 12-MAR-17:10 | 3060.09 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 11.18 | 44.08 | 01-JAN-10:10 | 1667.75 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 11.18 | 44.08 | 01-JAN-10:10 | 1667.75 | 02-JAN-08:10 |
Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 7568.97 | 95267.60 | 01-JAN-00:10 | 386103.53 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 74.11 | 359.47 | 01-JAN-00:10 | 6471.01 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 74.11 | 359.47 | 01-JAN-00:10 | 6471.01 | 02-JAN-08:10 |
Electricity:Zone:DATACENTER_BOT_ZN_6 | 160.51 | 1980.76 | 01-JAN-00:10 | 8373.14 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_BOT_ZN_6 | 6.63 | 32.15 | 01-JAN-00:10 | 578.72 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_BOT_ZN_6 | 6.63 | 32.15 | 01-JAN-00:10 | 578.72 | 02-JAN-08:10 |
Electricity:Zone:DATACENTER_MID_ZN_6 | 1605.09 | 19807.58 | 01-JAN-00:10 | 83731.41 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_MID_ZN_6 | 66.28 | 321.53 | 01-JAN-00:10 | 5787.18 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_MID_ZN_6 | 66.28 | 321.53 | 01-JAN-00:10 | 5787.18 | 02-JAN-08:10 |
Electricity:Zone:DATACENTER_TOP_ZN_6 | 160.51 | 1980.76 | 01-JAN-00:10 | 8373.14 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_TOP_ZN_6 | 6.63 | 32.15 | 01-JAN-00:10 | 578.72 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_TOP_ZN_6 | 6.63 | 32.15 | 01-JAN-00:10 | 578.72 | 02-JAN-08:10 |
InteriorEquipment:Electricity | 14676.40 | 207256.16 | 01-JAN-00:10 | 778371.69 | 03-APR-07:10 |
InteriorEquipment:Electricity:Zone:BASEMENT | 424.40 | 13457.54 | 01-JAN-00:10 | 13457.54 | 01-JAN-00:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 14676.40 | 207256.16 | 01-JAN-00:10 | 778371.69 | 03-APR-07:10 |
MiscPlug:InteriorEquipment:Electricity | 5334.97 | 88964.76 | 01-JAN-00:10 | 305206.10 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:BASEMENT | 424.40 | 13457.54 | 01-JAN-00:10 | 13457.54 | 01-JAN-00:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 5334.97 | 88964.76 | 01-JAN-00:10 | 305206.10 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 289.61 | 4453.23 | 01-JAN-00:10 | 17206.63 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 289.61 | 4453.23 | 01-JAN-00:10 | 17206.63 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_MID | 2896.13 | 44532.17 | 01-JAN-00:10 | 172065.63 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_MID | 2896.13 | 44532.17 | 01-JAN-00:10 | 172065.63 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_TOP | 289.61 | 4453.22 | 01-JAN-00:10 | 17206.56 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_TOP | 289.61 | 4453.22 | 01-JAN-00:10 | 17206.56 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 36.37 | 559.17 | 01-JAN-00:10 | 2160.55 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 36.37 | 559.17 | 01-JAN-00:10 | 2160.55 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.34 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.34 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 36.37 | 559.18 | 01-JAN-00:10 | 2160.58 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 36.37 | 559.18 | 01-JAN-00:10 | 2160.58 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.33 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.33 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 363.65 | 5591.71 | 01-JAN-00:10 | 21605.52 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 363.65 | 5591.71 | 01-JAN-00:10 | 21605.52 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 234.35 | 3603.51 | 01-JAN-00:10 | 13923.42 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 234.35 | 3603.51 | 01-JAN-00:10 | 13923.42 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 363.66 | 5591.79 | 01-JAN-00:10 | 21605.85 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 363.66 | 5591.79 | 01-JAN-00:10 | 21605.85 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 234.35 | 3603.49 | 01-JAN-00:10 | 13923.33 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 234.35 | 3603.49 | 01-JAN-00:10 | 13923.33 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 36.37 | 559.17 | 01-JAN-00:10 | 2160.55 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 36.37 | 559.17 | 01-JAN-00:10 | 2160.55 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.34 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.34 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 36.37 | 559.18 | 01-JAN-00:10 | 2160.58 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 36.37 | 559.18 | 01-JAN-00:10 | 2160.58 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.33 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.33 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 7494.86 | 94908.13 | 01-JAN-00:10 | 379632.52 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity | 9341.42 | 118291.40 | 01-JAN-00:10 | 473165.59 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 7494.86 | 94908.13 | 01-JAN-00:10 | 379632.52 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:SpaceType:GENERAL | 9341.42 | 118291.40 | 01-JAN-00:10 | 473165.59 | 31-MAR-23:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_BOT_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_BOT_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_MID_ZN_6 | 1538.81 | 19486.06 | 01-JAN-00:10 | 77944.22 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_MID_ZN_6 | 1538.81 | 19486.06 | 01-JAN-00:10 | 77944.22 | 31-MAR-23:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_TOP_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_TOP_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
Electricity:Plant | 1321.63 | 3797.96 | 07-JAN-05:20 | 465651.37 | 07-SEP-14:50 |
HeatRejection:Electricity | 437.48 | 63.85 | 10-JAN-22:00 | 83553.24 | 06-JUN-14:40 |
General:HeatRejection:Electricity | 437.48 | 63.85 | 10-JAN-22:00 | 83553.24 | 06-JUN-14:40 |
Electricity:HVAC | 6155.52 | 55824.13 | 11-SEP-22:40 | 656255.75 | 07-AUG-15:40 |
ExteriorEquipment:Electricity | 1934.80 | 28603.11 | 01-JAN-00:10 | 118535.44 | 02-JAN-08:20 |
Transformer:ExteriorEquipment:Electricity | 80.18 | 1421.04 | 01-JAN-00:10 | 5057.48 | 01-DEC-08:20 |
ElectricityPurchased:Facility | 28638.04 | 343584.99 | 21-MAY-04:50 | 2225335.88 | 07-AUG-15:40 |
ElectricityPurchased:Plant | 28638.04 | 343584.99 | 21-MAY-04:50 | 2225335.88 | 07-AUG-15:40 |
Cogeneration:ElectricityPurchased | 28638.04 | 343584.99 | 21-MAY-04:50 | 2225335.88 | 07-AUG-15:40 |
General:Cogeneration:ElectricityPurchased | 28638.04 | 343584.99 | 21-MAY-04:50 | 2225335.88 | 07-AUG-15:40 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 28638.04 | 343584.99 | 21-MAY-04:50 | 2225335.88 | 07-AUG-15:40 |
ElectricityNet:Plant | 28638.04 | 343584.99 | 21-MAY-04:50 | 2225335.88 | 07-AUG-15:40 |
Cogeneration:ElectricityNet | 28638.04 | 343584.99 | 21-MAY-04:50 | 2225335.88 | 07-AUG-15:40 |
General:Cogeneration:ElectricityNet | 28638.04 | 343584.99 | 21-MAY-04:50 | 2225335.88 | 07-AUG-15:40 |
Fans:Electricity | 2717.83 | 48073.41 | 01-JAN-21:50 | 358305.73 | 17-JUL-15:20 |
General:Fans:Electricity | 2717.83 | 48073.41 | 01-JAN-21:50 | 358305.73 | 17-JUL-15:20 |
ExteriorLights:Electricity | 696.47 | 0.00 | 01-JAN-08:20 | 57580.60 | 01-JAN-06:10 |
General:ExteriorLights:Electricity | 696.47 | 0.00 | 01-JAN-08:20 | 57580.60 | 01-JAN-06:10 |
ElevatorLift:ExteriorEquipment:Electricity | 1848.78 | 27144.47 | 01-JAN-00:10 | 113101.96 | 01-JAN-07:10 |
ElevatorLightsFan:ExteriorEquipment:Electricity | 5.83 | 37.60 | 01-JAN-00:10 | 376.00 | 01-JAN-07:10 |
Cooling:Electricity | 1480.31 | 1654.01 | 10-JAN-22:00 | 448448.23 | 17-JUL-15:30 |
General:Cooling:Electricity | 1480.31 | 1654.01 | 10-JAN-22:00 | 448448.23 | 17-JUL-15:30 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Humidifier:Electricity | 2435.06 | 0.00 | 02-MAY-11:50 | 100000.00 | 01-FEB-17:20 |
General:Humidifier:Electricity | 2435.06 | 0.00 | 02-MAY-11:50 | 100000.00 | 01-FEB-17:20 |
Boiler Parasitic:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Pumps:Electricity | 326.28 | 3696.33 | 01-JAN-00:10 | 48286.92 | 07-AUG-13:20 |
General:Pumps:Electricity | 326.28 | 3696.33 | 01-JAN-00:10 | 48286.92 | 07-AUG-13:20 |
WIRED_LTG_ELECTRICITY | 110.53 | 0.00 | 01-JAN-00:10 | 10841.96 | 02-JAN-08:20 |
WIRED_INT_EQUIP | 5334.97 | 88964.76 | 31-MAR-23:10 | 305206.10 | 03-APR-07:10 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 4459.24 | 8146.58 | 05-JAN-22:20 | 2464803.67 | 09-JAN-07:10 |
NaturalGas:Plant | 4459.24 | 8146.58 | 05-JAN-22:20 | 2464803.67 | 09-JAN-07:10 |
Heating:NaturalGas | 3610.86 | 0.00 | 01-JAN-00:10 | 2431734.33 | 09-JAN-07:10 |
Boiler:Heating:NaturalGas | 3610.86 | 0.00 | 01-JAN-00:10 | 2431734.33 | 09-JAN-07:10 |
WaterSystems:NaturalGas | 848.37 | 8146.58 | 05-JAN-22:20 | 87976.46 | 17-FEB-12:40 |
Water Heater:WaterSystems:NaturalGas | 848.37 | 8146.58 | 05-JAN-22:20 | 87976.46 | 17-FEB-12:40 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
PlantLoopCoolingDemand:Facility | 7652.59 | 4036.87 | 10-JAN-22:00 | 2711241.58 | 07-SEP-15:00 |
PlantLoopCoolingDemand:HVAC | 7652.59 | 4036.87 | 10-JAN-22:00 | 2711241.58 | 07-SEP-15:00 |
CoolingCoils:PlantLoopCoolingDemand | 7652.59 | 4036.87 | 10-JAN-22:00 | 2711241.58 | 07-SEP-15:00 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 6681.55 | 0.00 | 20-MAY-23:10 | 0.00 | 17-JUL-16:00 |
Water:HVAC | 905.84 | 0.00 | 02-MAY-11:50 | 0.00 | 01-FEB-22:10 |
Humidifier:Water | 905.84 | 0.00 | 02-MAY-11:50 | 0.00 | 01-FEB-22:10 |
General:Humidifier:Water | 905.84 | 0.00 | 02-MAY-11:50 | 0.00 | 01-FEB-22:10 |
MainsWater:Facility | 6681.55 | 0.00 | 20-MAY-23:10 | 0.00 | 17-JUL-16:00 |
MainsWater:HVAC | 905.84 | 0.00 | 02-MAY-11:50 | 0.00 | 01-FEB-22:10 |
Humidifier:MainsWater | 905.84 | 0.00 | 02-MAY-11:50 | 0.00 | 01-FEB-22:10 |
General:Humidifier:MainsWater | 905.84 | 0.00 | 02-MAY-11:50 | 0.00 | 01-FEB-22:10 |
Water:Plant | 5775.71 | 0.00 | 01-JAN-00:10 | 0.00 | 17-JUL-16:00 |
WaterSystems:Water | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterUse:WaterSystems:Water | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
MainsWater:Plant | 5775.71 | 0.00 | 01-JAN-00:10 | 0.00 | 17-JUL-16:00 |
WaterSystems:MainsWater | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterUse:WaterSystems:MainsWater | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water Heater:WaterSystems:Water | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:MainsWater | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
HeatRejection:Water | 3495.54 | 0.00 | 01-JAN-00:10 | 0.00 | 17-JUL-16:00 |
General:HeatRejection:Water | 3495.54 | 0.00 | 01-JAN-00:10 | 0.00 | 17-JUL-16:00 |
HeatRejection:MainsWater | 3495.54 | 0.00 | 01-JAN-00:10 | 0.00 | 17-JUL-16:00 |
General:HeatRejection:MainsWater | 3495.54 | 0.00 | 01-JAN-00:10 | 0.00 | 17-JUL-16:00 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 43952.80 | 96971.11 | 12-JAN-03:40 | 11435242.68 | 07-SEP-15:00 |
EnergyTransfer:Building | 19207.79 | 88203.93 | 12-JAN-22:50 | 1834695.57 | 07-AUG-15:20 |
EnergyTransfer:Zone:BASEMENT | 698.10 | 0.00 | 01-JAN-00:40 | 75312.76 | 05-SEP-05:10 |
Heating:EnergyTransfer | 1122.53 | 0.00 | 13-JAN-22:10 | 1408471.26 | 09-JAN-06:10 |
Heating:EnergyTransfer:Zone:BASEMENT | 2.83 | 0.00 | 01-JAN-00:20 | 22572.52 | 05-AUG-16:10 |
General:Heating:EnergyTransfer | 1122.53 | 0.00 | 13-JAN-22:10 | 1408471.26 | 09-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:BASEMENT | 2.83 | 0.00 | 01-JAN-00:20 | 22572.52 | 05-AUG-16:10 |
Cooling:EnergyTransfer | 18085.26 | 82921.39 | 09-JAN-05:40 | 1834695.57 | 07-AUG-15:20 |
Cooling:EnergyTransfer:Zone:BASEMENT | 695.26 | 0.00 | 01-JAN-00:40 | 75312.76 | 05-SEP-05:10 |
General:Cooling:EnergyTransfer | 18085.26 | 82921.39 | 09-JAN-05:40 | 1834695.57 | 07-AUG-15:20 |
General:Cooling:EnergyTransfer:Zone:BASEMENT | 695.26 | 0.00 | 01-JAN-00:40 | 75312.76 | 05-SEP-05:10 |
EnergyTransfer:Zone:CORE_BOTTOM | 610.52 | 0.00 | 01-JAN-00:10 | 57358.68 | 07-AUG-13:10 |
Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 610.52 | 0.00 | 01-JAN-00:10 | 57358.68 | 07-AUG-13:10 |
General:Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 610.52 | 0.00 | 01-JAN-00:10 | 57358.68 | 07-AUG-13:10 |
EnergyTransfer:Zone:CORE_MID | 4294.69 | 0.00 | 01-JAN-00:10 | 465142.92 | 10-AUG-15:50 |
Heating:EnergyTransfer:Zone:CORE_MID | 10.25 | 0.00 | 01-JAN-00:10 | 379413.47 | 09-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:CORE_MID | 10.25 | 0.00 | 01-JAN-00:10 | 379413.47 | 09-JAN-06:10 |
Cooling:EnergyTransfer:Zone:CORE_MID | 4284.45 | 0.00 | 01-JAN-00:10 | 465142.92 | 10-AUG-15:50 |
General:Cooling:EnergyTransfer:Zone:CORE_MID | 4284.45 | 0.00 | 01-JAN-00:10 | 465142.92 | 10-AUG-15:50 |
EnergyTransfer:Zone:CORE_TOP | 384.56 | 0.00 | 01-JAN-00:10 | 73874.39 | 09-JAN-05:30 |
Heating:EnergyTransfer:Zone:CORE_TOP | 20.17 | 0.00 | 01-JAN-00:10 | 73874.39 | 09-JAN-05:30 |
General:Heating:EnergyTransfer:Zone:CORE_TOP | 20.17 | 0.00 | 01-JAN-00:10 | 73874.39 | 09-JAN-05:30 |
Cooling:EnergyTransfer:Zone:CORE_TOP | 364.38 | 0.00 | 01-JAN-00:10 | 54262.09 | 17-JUL-15:30 |
General:Cooling:EnergyTransfer:Zone:CORE_TOP | 364.38 | 0.00 | 01-JAN-00:10 | 54262.09 | 17-JUL-15:30 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 63.92 | 0.00 | 01-JAN-00:10 | 13555.60 | 09-JAN-05:10 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 4.49 | 0.00 | 01-JAN-00:10 | 13555.60 | 09-JAN-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 4.49 | 0.00 | 01-JAN-00:10 | 13555.60 | 09-JAN-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 59.43 | 0.00 | 01-JAN-00:10 | 11225.64 | 18-JUL-12:20 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 59.43 | 0.00 | 01-JAN-00:10 | 11225.64 | 18-JUL-12:20 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 71.22 | 0.00 | 01-JAN-00:10 | 17608.79 | 07-AUG-08:30 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 3.27 | 0.00 | 01-JAN-00:10 | 11061.16 | 09-JAN-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 3.27 | 0.00 | 01-JAN-00:10 | 11061.16 | 09-JAN-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 67.95 | 0.00 | 01-JAN-00:10 | 17608.79 | 07-AUG-08:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 67.95 | 0.00 | 01-JAN-00:10 | 17608.79 | 07-AUG-08:30 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 120.87 | 0.00 | 01-JAN-00:10 | 24881.14 | 18-OCT-13:20 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 4.61 | 0.00 | 01-JAN-00:10 | 16706.17 | 09-JAN-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 4.61 | 0.00 | 01-JAN-00:10 | 16706.17 | 09-JAN-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 116.26 | 0.00 | 01-JAN-00:10 | 24881.14 | 18-OCT-13:20 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 116.26 | 0.00 | 01-JAN-00:10 | 24881.14 | 18-OCT-13:20 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 98.39 | 0.00 | 01-JAN-00:10 | 21356.88 | 07-AUG-16:40 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 1.14 | 0.00 | 01-JAN-00:10 | 8713.31 | 09-JAN-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 1.14 | 0.00 | 01-JAN-00:10 | 8713.31 | 09-JAN-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 97.25 | 0.00 | 01-JAN-00:10 | 21356.88 | 07-AUG-16:40 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 97.25 | 0.00 | 01-JAN-00:10 | 21356.88 | 07-AUG-16:40 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 639.70 | 0.00 | 01-JAN-00:10 | 148412.29 | 09-JAN-04:40 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 256.28 | 0.00 | 01-JAN-00:10 | 148412.29 | 09-JAN-04:40 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 256.28 | 0.00 | 01-JAN-00:10 | 148412.29 | 09-JAN-04:40 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 383.42 | 0.00 | 01-JAN-00:10 | 105286.21 | 18-JUL-13:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 383.42 | 0.00 | 01-JAN-00:10 | 105286.21 | 18-JUL-13:00 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 717.27 | 0.00 | 01-JAN-00:10 | 185197.36 | 07-AUG-09:00 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 151.32 | 0.00 | 01-JAN-00:10 | 165295.56 | 09-JAN-05:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 151.32 | 0.00 | 01-JAN-00:10 | 165295.56 | 09-JAN-05:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 565.95 | 0.00 | 01-JAN-00:10 | 185197.36 | 07-AUG-09:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 565.95 | 0.00 | 01-JAN-00:10 | 185197.36 | 07-AUG-09:00 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 1177.43 | 0.00 | 01-JAN-00:10 | 262982.27 | 18-OCT-13:40 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 157.13 | 0.00 | 01-JAN-00:10 | 228934.78 | 09-JAN-05:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 157.13 | 0.00 | 01-JAN-00:10 | 228934.78 | 09-JAN-05:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 1020.30 | 0.00 | 01-JAN-00:10 | 262982.27 | 18-OCT-13:40 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 1020.30 | 0.00 | 01-JAN-00:10 | 262982.27 | 18-OCT-13:40 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 707.89 | 0.00 | 01-JAN-00:10 | 198241.95 | 16-JUL-17:10 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 126.45 | 0.00 | 01-JAN-00:10 | 159075.34 | 09-JAN-05:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 126.45 | 0.00 | 01-JAN-00:10 | 159075.34 | 09-JAN-05:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 581.43 | 0.00 | 01-JAN-00:10 | 198241.95 | 16-JUL-17:10 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 581.43 | 0.00 | 01-JAN-00:10 | 198241.95 | 16-JUL-17:10 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 86.88 | 0.00 | 01-JAN-00:10 | 18156.29 | 09-JAN-04:10 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 51.70 | 0.00 | 01-JAN-00:10 | 18156.29 | 09-JAN-04:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 51.70 | 0.00 | 01-JAN-00:10 | 18156.29 | 09-JAN-04:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 35.18 | 0.00 | 01-JAN-00:10 | 11604.44 | 17-JUL-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 35.18 | 0.00 | 01-JAN-00:10 | 11604.44 | 17-JUL-16:00 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 82.37 | 0.00 | 01-JAN-00:10 | 19171.16 | 09-JAN-05:10 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 29.94 | 0.00 | 01-JAN-00:10 | 19171.16 | 09-JAN-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 29.94 | 0.00 | 01-JAN-00:10 | 19171.16 | 09-JAN-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 52.42 | 0.00 | 01-JAN-00:10 | 18684.57 | 07-AUG-09:10 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 52.42 | 0.00 | 01-JAN-00:10 | 18684.57 | 07-AUG-09:10 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 128.34 | 0.00 | 01-JAN-00:10 | 27082.29 | 18-OCT-13:40 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 34.93 | 0.00 | 01-JAN-00:10 | 26059.64 | 09-JAN-05:30 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 34.93 | 0.00 | 01-JAN-00:10 | 26059.64 | 09-JAN-05:30 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 93.41 | 0.00 | 01-JAN-00:10 | 27082.29 | 18-OCT-13:40 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 93.41 | 0.00 | 01-JAN-00:10 | 27082.29 | 18-OCT-13:40 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 80.07 | 0.00 | 01-JAN-00:10 | 20362.79 | 17-JUL-17:00 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 25.56 | 0.00 | 01-JAN-00:10 | 19802.88 | 09-JAN-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 25.56 | 0.00 | 01-JAN-00:10 | 19802.88 | 09-JAN-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 54.51 | 0.00 | 01-JAN-00:10 | 20362.79 | 17-JUL-17:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 54.51 | 0.00 | 01-JAN-00:10 | 20362.79 | 17-JUL-17:00 |
EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 60.07 | 0.00 | 01-JAN-00:10 | 11095.22 | 07-AUG-15:20 |
Heating:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 4.67 | 0.00 | 01-JAN-00:10 | 7265.74 | 30-JAN-13:30 |
General:Heating:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 4.67 | 0.00 | 01-JAN-00:10 | 7265.74 | 30-JAN-13:30 |
Cooling:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 55.40 | 0.00 | 01-JAN-00:10 | 11095.22 | 07-AUG-15:20 |
General:Cooling:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 55.40 | 0.00 | 01-JAN-00:10 | 11095.22 | 07-AUG-15:20 |
EnergyTransfer:Zone:MIDFLOOR_PLENUM | 498.63 | 0.00 | 01-JAN-00:10 | 128715.76 | 09-JAN-06:10 |
Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 161.05 | 0.00 | 01-JAN-00:10 | 128715.76 | 09-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 161.05 | 0.00 | 01-JAN-00:10 | 128715.76 | 09-JAN-06:10 |
Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 337.58 | 0.00 | 01-JAN-00:10 | 89916.40 | 17-JUL-15:30 |
General:Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 337.58 | 0.00 | 01-JAN-00:10 | 89916.40 | 17-JUL-15:30 |
EnergyTransfer:Zone:TOPFLOOR_PLENUM | 118.79 | 0.00 | 01-JAN-00:10 | 36246.05 | 09-JAN-05:10 |
Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 68.58 | 0.00 | 01-JAN-00:10 | 36246.05 | 09-JAN-05:10 |
General:Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 68.58 | 0.00 | 01-JAN-00:10 | 36246.05 | 09-JAN-05:10 |
Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 50.21 | 0.00 | 01-JAN-00:10 | 24012.12 | 17-JUL-14:50 |
General:Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 50.21 | 0.00 | 01-JAN-00:10 | 24012.12 | 17-JUL-14:50 |
EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 136.18 | 1.75 | 28-JAN-06:50 | 8528.18 | 03-AUG-18:50 |
Heating:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 0.11 | 0.00 | 01-JAN-00:10 | 658.59 | 08-JAN-22:20 |
General:Heating:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 0.11 | 0.00 | 01-JAN-00:10 | 658.59 | 08-JAN-22:20 |
Cooling:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 136.07 | 0.00 | 07-JAN-21:00 | 8528.18 | 03-AUG-18:50 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 136.07 | 0.00 | 07-JAN-21:00 | 8528.18 | 03-AUG-18:50 |
EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 1156.67 | 6.99 | 01-MAY-04:50 | 81981.71 | 03-AUG-18:50 |
Heating:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 6.86 | 0.00 | 02-JAN-10:50 | 6777.33 | 29-JAN-18:20 |
General:Heating:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 6.86 | 0.00 | 02-JAN-10:50 | 6777.33 | 29-JAN-18:20 |
Cooling:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 1149.80 | 0.00 | 01-JAN-00:10 | 81981.71 | 03-AUG-18:50 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 1149.80 | 0.00 | 01-JAN-00:10 | 81981.71 | 03-AUG-18:50 |
EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 105.07 | 0.11 | 18-JAN-11:00 | 8260.23 | 03-AUG-18:50 |
Heating:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 1.17 | 0.00 | 02-JAN-12:40 | 777.06 | 30-APR-23:10 |
General:Heating:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 1.17 | 0.00 | 02-JAN-12:40 | 777.06 | 30-APR-23:10 |
Cooling:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 103.90 | 0.00 | 01-JAN-00:10 | 8260.23 | 03-AUG-18:50 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 103.90 | 0.00 | 01-JAN-00:10 | 8260.23 | 03-AUG-18:50 |
EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 7170.17 | 82876.72 | 09-JAN-05:00 | 376214.69 | 06-AUG-21:20 |
Heating:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 7170.17 | 82876.72 | 09-JAN-05:00 | 376214.69 | 06-AUG-21:20 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 7170.17 | 82876.72 | 09-JAN-05:00 | 376214.69 | 06-AUG-21:20 |
PlantLoopHeatingDemand:Facility | 3273.10 | 0.00 | 01-JAN-00:10 | 2087233.06 | 09-JAN-07:10 |
PlantLoopHeatingDemand:Plant | 463.31 | 0.00 | 01-JAN-00:10 | 57406.13 | 17-FEB-12:20 |
WaterSystems:PlantLoopHeatingDemand | 463.31 | 0.00 | 01-JAN-00:10 | 57406.13 | 17-FEB-12:20 |
General:WaterSystems:PlantLoopHeatingDemand | 463.31 | 0.00 | 01-JAN-00:10 | 57406.13 | 17-FEB-12:20 |
EnergyTransfer:HVAC | 9539.93 | 3107.13 | 10-JAN-22:10 | 2659470.77 | 07-SEP-15:00 |
HeatingCoils:EnergyTransfer | 2809.79 | 0.00 | 01-JAN-00:10 | 2068657.57 | 09-JAN-07:10 |
PlantLoopHeatingDemand:HVAC | 2809.79 | 0.00 | 01-JAN-00:10 | 2068657.57 | 09-JAN-07:10 |
HeatingCoils:PlantLoopHeatingDemand | 2809.79 | 0.00 | 01-JAN-00:10 | 2068657.57 | 09-JAN-07:10 |
CoolingCoils:EnergyTransfer | 6730.14 | 2382.86 | 10-JAN-22:00 | 2659470.77 | 07-SEP-15:00 |
EnergyTransfer:Plant | 15205.08 | 0.00 | 01-JAN-00:10 | 7503699.18 | 07-SEP-15:00 |
LoopToLoop:EnergyTransfer | 3809.76 | 0.00 | 01-JAN-00:10 | 2431950.32 | 07-SEP-15:00 |
WaterSystems:EnergyTransfer | 463.31 | 0.00 | 01-JAN-00:10 | 57406.13 | 17-FEB-12:20 |
WaterUse:WaterSystems:EnergyTransfer | 463.31 | 0.00 | 01-JAN-00:10 | 57406.13 | 17-FEB-12:20 |
Boilers:EnergyTransfer | 2784.87 | 0.00 | 01-JAN-00:10 | 2020821.09 | 09-JAN-07:10 |
Chillers:EnergyTransfer | 3794.64 | 0.00 | 01-JAN-00:10 | 2360491.54 | 07-SEP-14:50 |
HeatRejection:EnergyTransfer | 4352.50 | 0.00 | 01-JAN-00:10 | 2695905.02 | 07-SEP-14:50 |
General:HeatRejection:EnergyTransfer | 4352.50 | 0.00 | 01-JAN-00:10 | 2695905.02 | 07-SEP-14:50 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 08:43:39
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
BASEMENT | 0.000 | 0.000 | 2.835 | -695.261 | 0.000 | 0.000 | 93.142 | 262.844 | 424.397 | 0.000 | 0.000 | 0.000 | 0.001 | 0.000 | 0.000 | 0.000 | 0.000 | -87.957 |
CORE_BOTTOM | 0.000 | 0.000 | 0.000 | -610.520 | 0.000 | 0.000 | 83.580 | 236.053 | 289.614 | 0.000 | 0.000 | 0.000 | 1.273 | 0.000 | 0.000 | 0.000 | 0.000 | -0.004 |
CORE_MID | 0.000 | 0.000 | 10.249 | -4284.426 | 0.000 | 0.000 | 852.907 | 2360.527 | 2896.128 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -1835.385 |
CORE_TOP | 0.000 | 0.000 | 20.174 | -364.380 | 0.000 | 0.000 | 88.485 | 236.053 | 289.613 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -269.945 |
PERIMETER_BOT_ZN_3 | 0.000 | 0.000 | 4.495 | -59.425 | 0.000 | 0.000 | 11.033 | 17.574 | 36.365 | 27.767 | 0.000 | 0.085 | 66.268 | 0.000 | -93.931 | 0.000 | -10.231 | 0.000 |
PERIMETER_BOT_ZN_2 | 0.000 | 0.000 | 3.267 | -67.953 | 0.000 | 0.000 | 7.175 | 11.163 | 23.435 | 67.422 | 0.000 | 0.059 | 19.407 | 0.000 | -57.246 | 0.000 | -6.730 | 0.000 |
PERIMETER_BOT_ZN_1 | 0.000 | 0.000 | 4.608 | -116.261 | 0.000 | 0.000 | 10.946 | 17.172 | 36.366 | 146.741 | 0.000 | 0.082 | 0.004 | 0.000 | -84.929 | 0.000 | -10.317 | -4.408 |
PERIMETER_BOT_ZN_4 | 0.000 | 0.000 | 1.137 | -97.249 | 0.000 | 0.000 | 7.038 | 11.198 | 23.435 | 63.150 | 0.000 | 0.054 | 64.117 | 0.000 | -65.551 | 0.000 | -7.329 | 0.000 |
PERIMETER_MID_ZN_3 | 0.000 | 0.000 | 256.278 | -383.417 | 0.000 | 0.000 | 115.523 | 175.350 | 363.654 | 292.282 | 0.000 | 2.012 | 249.097 | 0.000 | -858.388 | 0.000 | -212.391 | 0.000 |
PERIMETER_MID_ZN_2 | 0.000 | 0.000 | 151.320 | -565.952 | 0.000 | 0.000 | 54.440 | 111.478 | 234.352 | 677.818 | 0.000 | 1.326 | 16.884 | 0.000 | -537.433 | 0.000 | -144.233 | -0.009 |
PERIMETER_MID_ZN_1 | 0.000 | 0.000 | 157.131 | -1020.288 | 0.000 | 0.000 | 111.725 | 171.538 | 363.660 | 1462.779 | 0.000 | 1.868 | 0.030 | 0.000 | -819.718 | 0.000 | -227.712 | -200.982 |
PERIMETER_MID_ZN_4 | 0.000 | 0.000 | 126.454 | -581.423 | 0.000 | 0.000 | 74.808 | 111.805 | 234.351 | 648.280 | 0.000 | 1.306 | 113.195 | 0.000 | -581.062 | 0.000 | -147.714 | 0.000 |
PERIMETER_TOP_ZN_3 | 0.000 | 0.000 | 51.701 | -35.176 | 0.000 | 0.000 | 11.728 | 17.533 | 36.365 | 29.915 | 0.000 | 0.244 | 0.000 | 0.000 | -81.811 | 0.000 | -25.024 | -5.476 |
PERIMETER_TOP_ZN_2 | 0.000 | 0.000 | 29.944 | -52.423 | 0.000 | 0.000 | 7.450 | 11.148 | 23.435 | 68.263 | 0.000 | 0.157 | 0.001 | 0.000 | -51.476 | 0.000 | -17.067 | -19.430 |
PERIMETER_TOP_ZN_1 | 0.000 | 0.000 | 34.933 | -93.405 | 0.000 | 0.000 | 11.346 | 17.153 | 36.366 | 147.088 | 0.000 | 0.224 | 0.005 | 0.000 | -78.101 | 0.000 | -26.752 | -48.852 |
PERIMETER_TOP_ZN_4 | 0.000 | 0.000 | 25.559 | -54.508 | 0.000 | 0.000 | 7.563 | 11.180 | 23.435 | 65.082 | 0.000 | 0.159 | 0.002 | 0.000 | -55.822 | 0.000 | -17.535 | -5.112 |
DATACENTER_BOT_ZN_6 | 0.000 | 0.000 | 0.109 | -136.069 | 0.000 | 0.000 | 0.950 | 6.628 | 153.881 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -25.499 |
DATACENTER_MID_ZN_6 | 0.000 | 0.000 | 6.864 | -1149.802 | 0.000 | 0.000 | 9.522 | 66.280 | 1538.806 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -471.669 |
DATACENTER_TOP_ZN_6 | 0.000 | 0.000 | 1.169 | -103.904 | 0.000 | 0.000 | 0.957 | 6.628 | 153.881 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -58.730 |
DATACENTER_BASEMENT_ZN_6 | 0.000 | 0.000 | 0.000 | -7170.174 | 0.000 | 0.000 | 20.391 | 74.111 | 7494.857 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -419.184 |
GROUNDFLOOR_PLENUM | 4.666 | -55.403 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.157 | 72.706 | 0.000 | 0.000 | 0.000 | -22.125 | 0.000 |
MIDFLOOR_PLENUM | 161.054 | -337.579 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 2.914 | 545.019 | 0.000 | 0.000 | 0.000 | -371.409 | -0.020 |
TOPFLOOR_PLENUM | 68.581 | -50.207 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.258 | 20.437 | 0.000 | 0.000 | 0.000 | -39.070 | -0.001 |
Total Facility | 234.301 | -443.189 | 888.227 | -17642.017 | 0.000 | 0.000 | 1580.708 | 3933.414 | 14676.396 | 3696.585 | 0.000 | 10.906 | 1168.447 | 0.000 | -3365.468 | 0.000 | -1285.638 | -3452.663 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | 02-JUL-17:45 | 0.00 | 0.00 | 0.00 | -122556.64 | 0.00 | 0.00 | 0.00 | 1274.92 | 13457.54 | 0.00 | 0.00 | 0.00 | 107824.17 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 05-SEP-04:13 | 0.00 | 0.00 | 0.00 | -102156.29 | 0.00 | 0.00 | 0.00 | 2290.20 | 5937.65 | 0.00 | 0.00 | 0.00 | 93928.45 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 14-AUG-04:12 | 0.00 | 0.00 | 0.00 | -879850.33 | 0.00 | 0.00 | 0.00 | 22901.98 | 59376.23 | 0.00 | 0.00 | 0.00 | 797572.12 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 21-JUN-04:12 | 0.00 | 0.00 | 0.00 | -86067.66 | 0.00 | 0.00 | 0.00 | 2290.20 | 5937.62 | 0.00 | 0.00 | 0.00 | 77839.84 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 16-JUL-18:31 | 0.00 | 0.00 | 0.00 | -18010.42 | 0.00 | 0.00 | 0.00 | 68.40 | 559.17 | 7843.69 | 0.00 | 90.80 | 9448.36 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 04-SEP-08:41 | 0.00 | 0.00 | 0.00 | -27686.67 | 0.00 | 0.00 | 18.64 | 44.08 | 464.11 | 17660.78 | 0.00 | 0.00 | 9547.47 | 0.00 | -0.00 | 0.00 | -48.43 | 0.00 |
PERIMETER_BOT_ZN_1 | 15-OCT-13:31 | 0.00 | 0.00 | 0.00 | -36755.80 | 0.00 | 0.00 | 26.28 | 68.40 | 720.19 | 35315.42 | 0.00 | 0.00 | 1046.59 | 0.00 | -0.00 | 0.00 | -421.10 | 0.00 |
PERIMETER_BOT_ZN_4 | 04-SEP-16:01 | 0.00 | 0.00 | 0.00 | -35973.63 | 0.00 | 0.00 | 13.91 | 44.08 | 464.11 | 22672.75 | 0.00 | 30.82 | 12747.95 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 16-JUL-18:21 | 0.00 | 0.00 | 0.00 | -172198.58 | 0.00 | 0.00 | 0.00 | 684.02 | 5591.71 | 82988.01 | 0.00 | 1805.88 | 81128.97 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 02-JUL-09:01 | 0.00 | 0.00 | 0.00 | -323747.38 | 0.00 | 0.00 | 147.88 | 440.81 | 4641.14 | 211123.50 | 0.00 | 0.00 | 110629.74 | 0.00 | -0.00 | 0.00 | -3235.70 | 0.00 |
PERIMETER_MID_ZN_1 | 04-SEP-15:31 | 0.00 | 0.00 | 0.00 | -357466.27 | 0.00 | 0.00 | 276.96 | 684.04 | 7201.95 | 174466.76 | 0.00 | 1357.72 | 173478.85 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 16-JUL-17:01 | 0.00 | 0.00 | 0.00 | -357096.34 | 0.00 | 0.00 | 0.00 | 440.81 | 3603.49 | 247892.11 | 0.00 | 448.94 | 104711.00 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 02-JUL-18:31 | 0.00 | 0.00 | 0.00 | -19697.55 | 0.00 | 0.00 | 0.00 | 68.40 | 559.17 | 6530.18 | 0.00 | 0.00 | 12694.96 | 0.00 | -0.00 | 0.00 | -155.16 | 0.00 |
PERIMETER_TOP_ZN_2 | 02-JUL-08:31 | 0.00 | 0.00 | 0.00 | -31920.71 | 0.00 | 0.00 | 15.74 | 44.08 | 464.11 | 22997.98 | 0.00 | 0.00 | 8883.17 | 0.00 | -0.00 | 0.00 | -484.37 | 0.00 |
PERIMETER_TOP_ZN_1 | 03-SEP-12:41 | 0.00 | 0.00 | 0.00 | -37751.86 | 0.00 | 0.00 | 21.01 | 68.40 | 720.19 | 31880.39 | 0.00 | 561.01 | 4500.85 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 02-JUL-17:51 | 0.00 | 0.00 | 0.00 | -36675.69 | 0.00 | 0.00 | 0.00 | 44.08 | 360.35 | 23897.95 | 0.00 | 0.00 | 12578.66 | 0.00 | -0.00 | 0.00 | -205.36 | 0.00 |
DATACENTER_BOT_ZN_6 | 03-AUG-18:50 | 0.00 | 0.00 | 0.00 | -8527.87 | 0.00 | 0.00 | 10.61 | 192.90 | 7794.42 | 0.00 | 0.00 | 0.00 | 529.94 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 03-AUG-18:50 | 0.00 | 0.00 | 0.00 | -81978.71 | 0.00 | 0.00 | 106.16 | 1929.04 | 77944.22 | 0.00 | 0.00 | 0.00 | 1999.29 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 03-AUG-18:50 | 0.00 | 0.00 | 0.00 | -8259.93 | 0.00 | 0.00 | 10.62 | 192.90 | 7794.42 | 0.00 | 0.00 | 0.00 | 261.99 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 06-AUG-19:52 | 0.00 | 0.00 | 0.00 | -383639.25 | 0.00 | 0.00 | 0.00 | 359.47 | 379632.52 | 0.00 | 0.00 | 0.00 | 3647.25 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 05-SEP-05:03 | 0.00 | -11998.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12088.56 | 0.00 | -0.00 | 0.00 | -89.73 | 0.00 |
MIDFLOOR_PLENUM | 04-MAR-04:01 | 0.00 | -163313.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 194577.34 | 0.00 | -0.00 | 0.00 | -31264.07 | 0.00 |
TOPFLOOR_PLENUM | 17-JUL-14:50 | 0.00 | -24011.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.81 | 23994.35 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 07-AUG-04:12 | 0.00 | 45212.96 | 0.00 | -2019573.11 | 0.00 | 0.00 | 0.00 | 42872.09 | 587299.42 | 0.00 | 0.00 | 0.00 | 1449269.86 | 0.00 | -85292.00 | 0.00 | -19789.21 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | 05-AUG-16:01 | 0.00 | 0.00 | 24070.30 | 0.00 | 0.00 | 0.00 | 520.12 | 1274.92 | 13457.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -39322.89 |
CORE_BOTTOM | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 09-JAN-05:11 | 0.00 | 0.00 | 535852.76 | 0.00 | 0.00 | 0.00 | 0.00 | 22901.98 | 59376.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -618130.97 |
CORE_TOP | 09-JAN-04:01 | 0.00 | 0.00 | 84608.20 | 0.00 | 0.00 | 0.00 | 0.00 | 1144.97 | 5937.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -91690.79 |
PERIMETER_BOT_ZN_3 | 09-JAN-04:01 | 0.00 | 0.00 | 15183.82 | 0.00 | 0.00 | 0.00 | 0.00 | 143.76 | 745.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -9731.46 | 0.00 | -842.58 | -5499.11 |
PERIMETER_BOT_ZN_2 | 09-JAN-04:01 | 0.00 | 0.00 | 17408.67 | 0.00 | 0.00 | 0.00 | 0.00 | 92.65 | 480.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -6472.86 | 0.00 | -566.51 | -10942.41 |
PERIMETER_BOT_ZN_1 | 10-JAN-04:01 | 0.00 | 0.00 | 24930.20 | 0.00 | 0.00 | 0.00 | 0.00 | 143.77 | 745.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -8783.13 | 0.00 | -753.78 | -16282.63 |
PERIMETER_BOT_ZN_4 | 09-JAN-04:01 | 0.00 | 0.00 | 16866.75 | 0.00 | 0.00 | 0.00 | 0.00 | 92.65 | 480.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -6410.24 | 0.00 | -567.59 | -10462.03 |
PERIMETER_MID_ZN_3 | 09-JAN-04:31 | 0.00 | 0.00 | 160493.89 | 0.00 | 0.00 | 0.00 | 0.00 | 1437.63 | 7455.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -94002.59 | 0.00 | -18606.14 | -56778.39 |
PERIMETER_MID_ZN_2 | 09-JAN-04:31 | 0.00 | 0.00 | 230598.33 | 0.00 | 0.00 | 0.00 | 0.00 | 926.46 | 4804.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -63222.49 | 0.00 | -12700.84 | -160406.14 |
PERIMETER_MID_ZN_1 | 09-JAN-02:31 | 0.00 | 0.00 | 277596.02 | 0.00 | 0.00 | 0.00 | 0.00 | 1437.66 | 7455.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -90994.77 | 0.00 | -26456.46 | -169038.17 |
PERIMETER_MID_ZN_4 | 09-JAN-02:31 | 0.00 | 0.00 | 235809.72 | 0.00 | 0.00 | 0.00 | 0.00 | 926.46 | 4804.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -60762.70 | 0.00 | -17754.90 | -163023.22 |
PERIMETER_TOP_ZN_3 | 09-JAN-04:01 | 0.00 | 0.00 | 19801.78 | 0.00 | 0.00 | 0.00 | 0.00 | 143.76 | 745.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -8994.74 | 0.00 | -2210.94 | -9485.43 |
PERIMETER_TOP_ZN_2 | 09-JAN-04:01 | 0.00 | 0.00 | 25428.78 | 0.00 | 0.00 | 0.00 | 0.00 | 92.65 | 480.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -6014.47 | 0.00 | -1501.08 | -18486.34 |
PERIMETER_TOP_ZN_1 | 09-JAN-04:01 | 0.00 | 0.00 | 32105.14 | 0.00 | 0.00 | 0.00 | 0.00 | 143.77 | 745.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -8762.00 | 0.00 | -2253.33 | -21979.15 |
PERIMETER_TOP_ZN_4 | 09-JAN-04:01 | 0.00 | 0.00 | 28459.63 | 0.00 | 0.00 | 0.00 | 0.00 | 92.65 | 480.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -5858.13 | 0.00 | -1518.24 | -21656.38 |
DATACENTER_BOT_ZN_6 | 08-JAN-22:15 | 0.00 | 0.00 | 659.94 | 0.00 | 0.00 | 0.00 | 0.00 | 32.15 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -2640.70 |
DATACENTER_MID_ZN_6 | 29-JAN-18:20 | 0.00 | 0.00 | 6823.66 | 0.00 | 0.00 | 0.00 | 0.00 | 321.53 | 19486.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -26631.25 |
DATACENTER_TOP_ZN_6 | 30-APR-23:05 | 0.00 | 0.00 | 785.14 | 0.00 | 0.00 | 0.00 | 0.00 | 32.15 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -2765.90 |
DATACENTER_BASEMENT_ZN_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 06-AUG-16:01 | 15402.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 570.95 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -15973.24 |
MIDFLOOR_PLENUM | 16-APR-16:21 | 185004.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -5295.36 | -179709.44 |
TOPFLOOR_PLENUM | 09-JAN-05:04 | 36992.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -3462.08 | -33530.53 |
Total Facility | 09-JAN-06:02 | 78863.15 | 96418.93 | 1403392.83 | -96418.93 | 0.00 | 0.00 | 21551.88 | 42872.09 | 261414.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -393440.78 | 0.00 | -30681.26 | -1383972.87 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 08:43:39
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
VAV_BOT WITH REHEAT | 13.8821 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 11.6557 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_MID WITH REHEAT | 134.4688 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 107.8319 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_TOP WITH REHEAT | 13.6326 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 12.3008 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
CAV_BAS | 6.8191 | 0.0000 | 149.6021 | 1.0000 | Calculated from schedules | 1.2002 | 6.8191 | 0.1760 | 1.0000 | Not calculated | 1.2002 | 0.1760 | ||
AIRLOOP DATACENTER BASEMENT | 24.5388 | 0.0000 | 42.1814 | 1.0000 | Calculated from schedules | 0.3384 | 24.5389 | 0.0138 | 1.0000 | Not calculated | 0.3384 | 0.0138 | ||
AIRLOOP DATACENTER BOT | 0.5854 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.5854 | 0.0267 | 1.0000 | Not calculated | 0.0156 | 0.0267 | ||
AIRLOOP DATACENTER MID | 5.6297 | 0.0000 | 19.4861 | 1.0000 | Calculated from schedules | 0.1563 | 5.6297 | 0.0278 | 1.0000 | Not calculated | 0.1563 | 0.0278 | ||
AIRLOOP DATACENTER TOP | 0.5724 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.5724 | 0.0273 | 1.0000 | Not calculated | 0.0156 | 0.0273 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
VAV_BOT WITH REHEAT | 6.9410 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 3.4136 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_MID WITH REHEAT | 67.2344 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 33.6965 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_TOP WITH REHEAT | 6.8163 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 3.5014 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
CAV_BAS | 6.8191 | 0.0000 | 149.6021 | 1.0000 | Calculated from schedules | 1.2002 | 6.8191 | 1.0000 | 1.0000 | Not calculated | 1.2002 | 0.1760 | ||
AIRLOOP DATACENTER BASEMENT | 24.5388 | 0.0000 | 42.1814 | 1.0000 | Calculated from schedules | 0.3384 | 24.5388 | 1.0000 | 1.0000 | Not calculated | 0.3384 | 0.0138 | ||
AIRLOOP DATACENTER BOT | 0.5854 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.5854 | 1.0000 | 1.0000 | Not calculated | 0.0156 | 0.0267 | ||
AIRLOOP DATACENTER MID | 5.6297 | 0.0000 | 19.4861 | 1.0000 | Calculated from schedules | 0.1563 | 5.6297 | 1.0000 | 1.0000 | Not calculated | 0.1563 | 0.0278 | ||
AIRLOOP DATACENTER TOP | 0.5724 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.5724 | 1.0000 | 1.0000 | Not calculated | 0.0156 | 0.0273 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
BASEMENT | CAV_BAS | 0.000000 | 149.6021 | 0.000432 | 2779.43 | 1.2002 | 1.0000 | 1.2002 | 1.000 | 1.2002 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | 0.000000 | 134.3532 | 0.000432 | 2496.12 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_MID | VAV_MID WITH REHEAT | 0.000000 | 1343.5320 | 0.000432 | 24961.20 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_TOP | VAV_TOP WITH REHEAT | 0.000000 | 134.3532 | 0.000432 | 2496.12 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | 0.000000 | 16.8694 | 0.000432 | 313.41 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | 0.000000 | 16.8698 | 0.000432 | 313.42 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | 0.000000 | 168.6939 | 0.000432 | 3134.13 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | 0.000000 | 108.7127 | 0.000432 | 2019.75 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | 0.000000 | 168.6975 | 0.000432 | 3134.20 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | 0.000000 | 108.7127 | 0.000432 | 2019.75 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | 0.000000 | 16.8694 | 0.000432 | 313.41 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | 0.000000 | 16.8698 | 0.000432 | 313.42 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | 0.000000 | 1.9486 | 0.000432 | 36.20 | 0.0156 | 1.0000 | 0.0156 | 1.000 | 0.0156 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | 0.000000 | 19.4861 | 0.000432 | 362.03 | 0.1563 | 1.0000 | 0.1563 | 1.000 | 0.1563 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | 0.000000 | 1.9486 | 0.000432 | 36.20 | 0.0156 | 1.0000 | 0.0156 | 1.000 | 0.0156 |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | 0.000000 | 42.1814 | 0.000432 | 783.68 | 0.3384 | 1.0000 | 0.3384 | 1.000 | 0.3384 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
VAV_BOT WITH REHEAT | 0.00 | 0.000432 | 3526.9033 | 0.0000 | 0.0000 | 0.0000 | |
VAV_MID WITH REHEAT | 0.00 | 0.000432 | 35269.0328 | 0.0000 | 0.0000 | 0.0000 | |
VAV_TOP WITH REHEAT | 0.00 | 0.000432 | 3526.9033 | 0.0000 | 0.0000 | 0.0000 | |
CAV_BAS | 0.000000 | 149.60 | 0.000432 | 2779.4266 | 1.2002 | 1.2002 | 1.2002 |
AIRLOOP DATACENTER BASEMENT | 0.000000 | 42.18 | 0.000432 | 783.6794 | 0.3384 | 0.3384 | 0.3384 |
AIRLOOP DATACENTER BOT | 0.000000 | 1.95 | 0.000432 | 36.2027 | 0.0156 | 0.0156 | 0.0156 |
AIRLOOP DATACENTER MID | 0.000000 | 19.49 | 0.000432 | 362.0274 | 0.1563 | 0.1563 | 0.1563 |
AIRLOOP DATACENTER TOP | 0.000000 | 1.95 | 0.000432 | 36.2027 | 0.0156 | 0.0156 | 0.0156 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | CAV_BAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 6.8191 | 6.8191 | 6.8191 | No | 1.2002 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 7.0643 | 7.0643 | 2.0345 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 66.5266 | 66.5266 | 19.8915 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 6.4354 | 6.4354 | 2.0593 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.1969 | 1.1969 | 0.2549 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.6226 | 1.6226 | 0.3245 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.0083 | 2.0083 | 0.4017 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.9899 | 1.9899 | 0.3980 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 11.3989 | 11.3989 | 2.4963 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 17.3102 | 17.3102 | 3.4620 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 20.5161 | 20.5161 | 4.1032 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 18.7171 | 18.7171 | 3.7434 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.3145 | 1.3145 | 0.2655 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.7310 | 1.7310 | 0.3462 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.1859 | 2.1859 | 0.4372 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.9658 | 1.9658 | 0.3932 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.5854 | 0.5854 | 0.5854 | No | 0.0156 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 5.6297 | 5.6297 | 5.6297 | No | 0.1563 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.5724 | 0.5724 | 0.5724 | No | 0.0156 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 24.5388 | 24.5388 | 24.5388 | No | 0.3384 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
VAV_BOT WITH REHEAT | 13.8821 | 11.6557 | 13.8821 | 3.4136 | 0.0000 | 1.0000 |
VAV_MID WITH REHEAT | 134.4688 | 107.8319 | 134.4688 | 33.6965 | 0.0000 | 1.0000 |
VAV_TOP WITH REHEAT | 13.6326 | 12.3008 | 13.6326 | 3.5014 | 0.0000 | 1.0000 |
CAV_BAS | 6.8191 | 6.8191 | 6.8191 | 6.8191 | 1.2002 | 1.0000 |
AIRLOOP DATACENTER BASEMENT | 24.5388 | 24.5389 | 24.5388 | 24.5388 | 0.3384 | 1.0000 |
AIRLOOP DATACENTER BOT | 0.5854 | 0.5854 | 0.5854 | 0.5854 | 0.0156 | 1.0000 |
AIRLOOP DATACENTER MID | 5.6297 | 5.6297 | 5.6297 | 5.6297 | 0.1563 | 1.0000 |
AIRLOOP DATACENTER TOP | 0.5724 | 0.5724 | 0.5724 | 0.5724 | 0.0156 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | CAV_BAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 6.8191 | 6.8191 | 6.8191 | No | 1.2002 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 3.5321 | 3.5321 | 2.0345 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 33.2633 | 33.2633 | 19.8915 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 3.2177 | 3.2177 | 2.0593 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5985 | 0.5985 | 0.2549 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8113 | 0.8113 | 0.3245 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.0042 | 1.0042 | 0.4017 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.9950 | 0.9950 | 0.3980 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 5.6994 | 5.6994 | 2.4963 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 8.6551 | 8.6551 | 3.4620 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 10.2580 | 10.2580 | 4.1032 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 9.3585 | 9.3585 | 3.7434 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6573 | 0.6573 | 0.2655 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8655 | 0.8655 | 0.3462 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.0929 | 1.0929 | 0.4372 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.9829 | 0.9829 | 0.3932 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.5854 | 0.5854 | 0.5854 | No | 0.0156 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 5.6297 | 5.6297 | 5.6297 | No | 0.1563 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.5724 | 0.5724 | 0.5724 | No | 0.0156 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 24.5388 | 24.5388 | 24.5388 | No | 0.3384 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
VAV_BOT WITH REHEAT | 6.9410 | 3.4136 | 3.4136 | 3.4136 | 0.0000 | 1.0000 |
VAV_MID WITH REHEAT | 67.2344 | 33.6965 | 33.6965 | 33.6965 | 0.0000 | 1.0000 |
VAV_TOP WITH REHEAT | 6.8163 | 3.5014 | 3.5014 | 3.5014 | 0.0000 | 1.0000 |
CAV_BAS | 6.8191 | 6.8191 | 6.8191 | 6.8191 | 1.2002 | 1.0000 |
AIRLOOP DATACENTER BASEMENT | 24.5388 | 24.5388 | 24.5388 | 24.5388 | 0.3384 | 1.0000 |
AIRLOOP DATACENTER BOT | 0.5854 | 0.5854 | 0.5854 | 0.5854 | 0.0156 | 1.0000 |
AIRLOOP DATACENTER MID | 5.6297 | 5.6297 | 5.6297 | 5.6297 | 0.1563 | 1.0000 |
AIRLOOP DATACENTER TOP | 0.5724 | 0.5724 | 0.5724 | 0.5724 | 0.0156 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 08:43:39
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Great Falls Intl Arpt MT USA TMY3 WMO#=727750 |
Total gross floor area [m2] | 46320.38 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
BASEMENT | 2779.43 | 2779.43 | 0.00 | 113.98 |
CORE_BOTTOM | 2496.12 | 2496.12 | 0.00 | 113.98 |
CORE_MID | 2496.12 | 2496.12 | 0.00 | 113.98 |
CORE_TOP | 2496.12 | 2496.12 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_3 | 313.41 | 313.41 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_2 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_1 | 313.42 | 313.42 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_4 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_MID_ZN_3 | 313.41 | 313.41 | 0.00 | 113.98 |
PERIMETER_MID_ZN_2 | 201.98 | 201.98 | 0.00 | 96.54 |
PERIMETER_MID_ZN_1 | 313.42 | 313.42 | 0.00 | 113.98 |
PERIMETER_MID_ZN_4 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_3 | 313.41 | 313.41 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_2 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_1 | 313.42 | 313.42 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_4 | 201.98 | 201.98 | 0.00 | 113.98 |
DATACENTER_BOT_ZN_6 | 36.20 | 36.20 | 0.00 | 113.98 |
DATACENTER_MID_ZN_6 | 36.20 | 36.20 | 0.00 | 113.98 |
DATACENTER_TOP_ZN_6 | 36.20 | 36.20 | 0.00 | 113.98 |
DATACENTER_BASEMENT_ZN_6 | 783.68 | 783.68 | 0.00 | 113.98 |
GROUNDFLOOR_PLENUM | 3563.11 | 3563.11 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 3563.11 | 3563.11 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 3563.11 | 3563.11 | 0.00 | 0.00 |
Totals | 46320.38 | 46320.38 | 0.00 |
Data | |
Number of hours heating loads not met | 133.17 |
Number of hours cooling loads not met | 247.83 |
Number of hours not met | 381.00 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler | 0.00 | 0.00 | 3610.86 | 2431734.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 1480.31 | 448448.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 3933.41 | 385834.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 696.47 | 57580.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 5334.97 | 305206.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- DataCenterPlugLoads | 9341.42 | 473165.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Transformer | 80.18 | 5057.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLift | 1848.78 | 113101.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLightsFan | 5.83 | 376.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 2717.83 | 358305.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 326.28 | 48286.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- General | 437.48 | 83553.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- General | 2435.06 | 100000.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 0.00 | 0.00 | 848.37 | 87976.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 14676.40 | 28638.04 |
Natural Gas | 0.00 | 4459.24 |
Additional | 0.00 | 0.00 |
Total | 14676.40 | 33097.28 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 84.92 |
Space Heating | 0.00 |
Space Cooling | 31.96 |
Fans (All) | 58.67 |
Service Water Heating | 0.00 |
Receptacle Equipment | 316.85 |
Miscellaneous (All) | 618.26 |
Subtotal | 618.26 |
Natural Gas [MJ/m2] | |
Space Heating | 77.95 |
Service Water Heating | 18.32 |
Miscellaneous (All) | 96.27 |
Subtotal | 96.27 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 11.88 |
Space Heating | 10.91 |
Space Cooling | 4.47 |
Fans (All) | 8.21 |
Service Water Heating | 2.56 |
Receptacle Equipment | 44.34 |
Miscellaneous | 17.62 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 4472. | 4472. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 6752. | 8760. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 6828. | 8760. |
ALWAYS_OFF | 0. | 0. |
LTG_SCH_OFFICE | 2625. | 8760. |
LTG_SCH_DATACENTER | 2921. | 8760. |
EXTERIOR_LIGHT_SCH | 4380. | 4380. |
BLDG_EQUIP_SCH | 4049. | 8760. |
DATACENTER_EQUIP_SCH | 5478. | 8760. |
BLDG_OCC_SCH | 2528. | 5992. |
BLDG_OCC_SCH_W_SB | 1878. | 5056. |
BLDG_OCC_SCH_WO_SB | 2557. | 5992. |
BLDG_ELEVATORS | 2270. | 8760. |
ELEV_LIGHT_FAN_SCH_24_7 | 8760. | 8760. |
ELEV_LIGHT_FAN_SCH_ADD_DF | 2154. | 8760. |
BLDG_SWH_SCH | 1474. | 6570. |
WORK_EFF_SCH | 0. | 0. |
INFIL_SCH | 3976. | 3976. |
INFIL_SCH_PNNL | 5172. | 8760. |
INFIL_HALF_ON_SCH | 6368. | 8760. |
FAN_SCH | 8760. | 8760. |
REHEATCOILAVAILSCHED | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
MINOA_MOTORIZEDDAMPER_SCHED | 4472. | 4472. |
MINOA_SCHED | 8760. | 8760. |
CORE_BOTTOM SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_BOTTOM SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_MID SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_MID SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_TOP SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_TOP SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
SUPPLYFANSCH | 8760. | 8760. |
PERIMETER_MID_ZN_2_MDP_SCH | 1565. | 7824. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
HTGSETP_DC_SCH | DATACENTER COOLING SETPOINTS DUAL SP CONTROL | January | 18.00 | 365 | 18.00 | 365 |
CLGSETP_DC_SCH | DATACENTER COOLING SETPOINTS DUAL SP CONTROL | July | 27.00 | 365 | 27.00 | 365 |
HTGSETP_SCH_YES_OPTIMUM | CORE_BOTTOM DUAL SP CONTROL | January | 21.00 | 365 | 15.60 | 365 |
CLGSETP_SCH_YES_OPTIMUM | CORE_BOTTOM DUAL SP CONTROL | July | 24.00 | 365 | 26.70 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:43:39
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
BASEMENT | 8722.00 | 38.00 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 8755.50 | 4.50 | 0.00 | 0.00 | 0.00 |
CORE_MID | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 8757.67 | 2.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 8735.67 | 24.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 8729.50 | 30.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 8683.83 | 76.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 8758.00 | 2.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 8733.17 | 26.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 8729.17 | 30.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 8728.00 | 32.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 8757.00 | 3.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 8734.33 | 25.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 8733.00 | 27.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 8730.33 | 29.67 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 8752.67 | 7.33 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 8756.17 | 3.83 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 8754.50 | 5.50 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 8504.33 | 250.50 | 5.17 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 8736.17 | 23.83 | 0.00 | 0.00 | 0.00 |
Min | 8504.33 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 250.50 | 5.17 | 0.00 | 0.00 |
Average | 8731.78 | 27.99 | 0.22 | 0.00 | 0.00 |
Sum | 200831.00 | 643.83 | 5.17 | 0.00 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
BASEMENT | 368421.17 | 194.83 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 330790.00 | 23.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 330813.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 330813.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 18354.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 2268.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 2268.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 2268.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 99788.83 | 3584.50 | 21.67 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 368421.17 | 3584.50 | 21.67 | 0.00 | 0.00 |
Average | 80168.65 | 165.32 | 0.94 | 0.00 | 0.00 |
Sum | 1843879.00 | 3802.33 | 21.67 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
BASEMENT | 8690.67 | 69.33 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 8720.67 | 39.33 | 0.00 | 0.00 | 0.00 |
CORE_MID | 8717.00 | 43.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 8734.83 | 25.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 8747.00 | 13.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 8745.50 | 14.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 8739.50 | 20.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 8696.33 | 63.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 8747.83 | 12.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 8735.67 | 24.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 8737.33 | 22.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 8730.17 | 29.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 8748.50 | 11.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 8737.67 | 22.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 8740.17 | 19.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 8732.33 | 27.67 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 8563.17 | 196.83 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 8742.67 | 17.33 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 8750.83 | 9.17 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 8724.00 | 36.00 | 0.00 | 0.00 | 0.00 |
Min | 8563.17 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 196.83 | 0.00 | 0.00 | 0.00 |
Average | 8728.78 | 31.22 | 0.00 | 0.00 | 0.00 |
Sum | 200761.83 | 718.17 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
BASEMENT | 368333.00 | 283.00 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 330729.00 | 84.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 330709.00 | 104.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 330761.00 | 52.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 18354.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 2268.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 2268.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 2268.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 100532.83 | 2862.17 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 368333.00 | 2862.17 | 0.00 | 0.00 | 0.00 |
Average | 80187.73 | 147.18 | 0.00 | 0.00 | 0.00 |
Sum | 1844317.83 | 3385.17 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:43:39
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:43:39
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 0.00 | 8760.00 | 0.00 |
Average | 0.00 | 0.00 | 4570.43 | 0.00 |
Sum | 0.00 | 0.00 | 105120.00 | 0.00 |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 18354.00 | 0.00 |
PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 24909.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 0.00 | 38925.00 | 0.00 |
Average | 0.00 | 0.00 | 16367.35 | 0.00 |
Sum | 0.00 | 0.00 | 376449.00 | 0.00 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -8.80 |
February | -2.17 |
March | 0.301 |
April | 6.668 |
May | 10.099 |
June | 16.456 |
July | 20.571 |
August | 19.174 |
September | 14.689 |
October | 8.635 |
November | 2.839 |
December | -4.07 |
Annual Sum or Average | 7.074 |
Minimum of Months | -8.80 |
Maximum of Months | 20.571 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Environment
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -8.80 |
February | -2.17 |
March | 0.301 |
April | 6.668 |
May | 10.099 |
June | 16.456 |
July | 20.571 |
August | 19.174 |
September | 14.689 |
October | 8.635 |
November | 2.839 |
December | -4.07 |
Annual Sum or Average | 7.074 |
Minimum of Months | -8.80 |
Maximum of Months | 20.571 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2013
For: Environment
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -8.80 |
February | -2.17 |
March | 0.301 |
April | 6.668 |
May | 10.099 |
June | 16.456 |
July | 20.571 |
August | 19.174 |
September | 14.689 |
October | 8.635 |
November | 2.839 |
December | -4.07 |
Annual Sum or Average | 7.074 |
Minimum of Months | -8.80 |
Maximum of Months | 20.571 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -8.80 |
February | -2.17 |
March | 0.301 |
April | 6.668 |
May | 10.099 |
June | 16.456 |
July | 20.571 |
August | 19.174 |
September | 14.689 |
October | 8.635 |
November | 2.839 |
December | -4.07 |
Annual Sum or Average | 7.074 |
Minimum of Months | -8.80 |
Maximum of Months | 20.571 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICELARGE
For: Environment
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -8.80 |
February | -2.17 |
March | 0.301 |
April | 6.668 |
May | 10.099 |
June | 16.456 |
July | 20.571 |
August | 19.174 |
September | 14.689 |
October | 8.635 |
November | 2.839 |
December | -4.07 |
Annual Sum or Average | 7.074 |
Minimum of Months | -8.80 |
Maximum of Months | 20.571 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -8.80 |
February | -2.17 |
March | 0.301 |
April | 6.668 |
May | 10.099 |
June | 16.456 |
July | 20.571 |
August | 19.174 |
September | 14.689 |
October | 8.635 |
November | 2.839 |
December | -4.07 |
Annual Sum or Average | 7.074 |
Minimum of Months | -8.80 |
Maximum of Months | 20.571 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -8.80 |
February | -2.17 |
March | 0.301 |
April | 6.668 |
May | 10.099 |
June | 16.456 |
July | 20.571 |
August | 19.174 |
September | 14.689 |
October | 8.635 |
November | 2.839 |
December | -4.07 |
Annual Sum or Average | 7.074 |
Minimum of Months | -8.80 |
Maximum of Months | 20.571 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 6B
For: Environment
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -8.80 |
February | -2.17 |
March | 0.301 |
April | 6.668 |
May | 10.099 |
June | 16.456 |
July | 20.571 |
August | 19.174 |
September | 14.689 |
October | 8.635 |
November | 2.839 |
December | -4.07 |
Annual Sum or Average | 7.074 |
Minimum of Months | -8.80 |
Maximum of Months | 20.571 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_MT_GREATFALLS
For: Environment
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -8.80 |
February | -2.17 |
March | 0.301 |
April | 6.668 |
May | 10.099 |
June | 16.456 |
July | 20.571 |
August | 19.174 |
September | 14.689 |
October | 8.635 |
November | 2.839 |
December | -4.07 |
Annual Sum or Average | 7.074 |
Minimum of Months | -8.80 |
Maximum of Months | 20.571 |
Report: ZoneCoolingSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.491806E+11 | 119041.38 | 02-JAN-04:01 | -0.5 | -3.0 | 0.536735E+10 | 7499.19 | 12-JAN-10:09 | 6.78 | 3.19 |
February | 0.448930E+11 | 119260.94 | 21-FEB-05:11 | 7.43 | 1.21 | 0.506392E+10 | 7499.23 | 06-FEB-10:20 | 7.43 | 1.21 |
March | 0.562676E+11 | 115710.20 | 20-MAR-03:01 | -1.6 | -3.4 | 0.611862E+10 | 7499.16 | 06-MAR-10:39 | -1.6 | -3.4 |
April | 0.544616E+11 | 120077.72 | 10-APR-04:11 | 4.23 | 0.21 | 0.544715E+10 | 7499.14 | 04-APR-09:09 | 4.23 | 0.21 |
May | 0.573161E+11 | 119032.90 | 22-MAY-03:02 | 0.50 | 0.24 | 0.590084E+10 | 7499.77 | 02-MAY-13:20 | 0.50 | 0.24 |
June | 0.622210E+11 | 118166.47 | 12-JUN-04:12 | 11.70 | 10.91 | 0.588224E+10 | 7499.11 | 20-JUN-13:20 | 27.77 | 18.21 |
July | 0.647059E+11 | 122563.24 | 02-JUL-17:45 | 25.60 | 14.12 | 0.547499E+10 | 7499.22 | 03-JUL-13:09 | 19.07 | 14.10 |
August | 0.711737E+11 | 119010.41 | 14-AUG-04:12 | 12.20 | 9.88 | 0.613846E+10 | 7499.15 | 24-AUG-13:30 | 27.20 | 14.80 |
September | 0.612689E+11 | 122345.05 | 03-SEP-13:58 | 33.90 | 16.29 | 0.545281E+10 | 7499.35 | 07-SEP-09:00 | 16.70 | 15.61 |
October | 0.620735E+11 | 121499.44 | 02-OCT-04:11 | 4.80 | 2.84 | 0.567044E+10 | 7499.21 | 18-OCT-13:39 | 24.80 | 11.21 |
November | 0.572166E+11 | 120348.34 | 13-NOV-04:01 | -6.2 | -8.4 | 0.561303E+10 | 7499.07 | 03-NOV-09:09 | -6.2 | -8.4 |
December | 0.544851E+11 | 117716.13 | 11-DEC-04:01 | -2.6 | -4.7 | 0.541548E+10 | 7499.18 | 07-DEC-10:20 | -2.6 | -4.7 |
Annual Sum or Average | 0.695264E+12 | 0.675453E+11 | ||||||||
Minimum of Months | 0.448930E+11 | 115710.20 | -6.2 | -8.4 | 0.506392E+10 | 7499.07 | -6.2 | -8.4 | ||
Maximum of Months | 0.711737E+11 | 122563.24 | 33.90 | 16.29 | 0.613846E+10 | 7499.77 | 27.77 | 18.21 |
Report: ZoneCoolingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.329882E+11 | 89272.35 | 02-JAN-05:01 | -0.2 | -2.7 | 0.495168E+10 | 6734.76 | 02-JAN-10:09 | 2.48 | -0.4 |
February | 0.351318E+11 | 90639.00 | 27-FEB-05:11 | 4.07 | 0.00 | 0.457262E+10 | 6734.76 | 23-FEB-10:39 | 4.07 | 0.00 |
March | 0.486303E+11 | 90600.84 | 02-MAR-05:11 | 4.03 | 0.28 | 0.549166E+10 | 6734.76 | 01-MAR-10:09 | 4.03 | 0.28 |
April | 0.526411E+11 | 98180.20 | 10-APR-04:11 | 4.23 | 0.21 | 0.488349E+10 | 6734.78 | 04-APR-09:09 | 4.23 | 0.21 |
May | 0.499936E+11 | 97307.20 | 30-MAY-04:12 | 15.60 | 10.93 | 0.528915E+10 | 6735.17 | 02-MAY-13:09 | 15.60 | 10.93 |
June | 0.604146E+11 | 96816.16 | 12-JUN-04:12 | 11.70 | 10.91 | 0.526928E+10 | 6734.78 | 20-JUN-09:00 | 21.10 | 12.64 |
July | 0.664230E+11 | 100012.37 | 05-JUL-04:12 | 9.40 | 8.79 | 0.489782E+10 | 6734.97 | 03-JUL-13:09 | 9.40 | 8.79 |
August | 0.732032E+11 | 98499.05 | 28-AUG-04:12 | 8.67 | 4.95 | 0.549786E+10 | 6734.80 | 01-AUG-13:09 | 8.67 | 4.95 |
September | 0.524812E+11 | 102165.59 | 05-SEP-04:13 | 18.30 | 11.92 | 0.488214E+10 | 6735.18 | 07-SEP-09:00 | 16.70 | 15.61 |
October | 0.503805E+11 | 96555.60 | 02-OCT-04:11 | 4.80 | 2.84 | 0.507897E+10 | 6734.75 | 18-OCT-13:39 | 24.80 | 11.21 |
November | 0.458886E+11 | 94278.43 | 06-NOV-04:02 | -2.8 | -3.9 | 0.502697E+10 | 6734.75 | 03-NOV-09:09 | -2.8 | -3.9 |
December | 0.423451E+11 | 90293.88 | 11-DEC-05:01 | -1.6 | -4.2 | 0.488653E+10 | 6734.81 | 07-DEC-10:20 | -1.6 | -4.2 |
Annual Sum or Average | 0.610521E+12 | 0.607282E+11 | ||||||||
Minimum of Months | 0.329882E+11 | 89272.35 | -2.8 | -4.2 | 0.457262E+10 | 6734.75 | -2.8 | -4.2 | ||
Maximum of Months | 0.732032E+11 | 102165.59 | 18.30 | 11.92 | 0.549786E+10 | 6735.18 | 24.80 | 15.61 |
Report: ZoneCoolingSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.231322E+11 | 21440.08 | 19-JAN-16:57 | -6.7 | -8.2 | 0.445151E+10 | 6734.47 | 19-JAN-14:00 | -6.7 | -8.2 |
February | 0.234199E+11 | 33650.96 | 28-FEB-17:00 | 10.00 | 4.31 | 0.428378E+10 | 6734.74 | 28-FEB-10:09 | 10.00 | 4.31 |
March | 0.316579E+11 | 54523.91 | 24-MAR-05:03 | -0.6 | -2.5 | 0.531802E+10 | 6734.76 | 01-MAR-10:09 | -0.6 | -2.5 |
April | 0.335799E+11 | 82168.51 | 26-APR-05:02 | 5.37 | 2.97 | 0.482557E+10 | 6734.75 | 04-APR-09:09 | 5.37 | 2.97 |
May | 0.379012E+11 | 83821.63 | 30-MAY-04:12 | 15.60 | 10.93 | 0.524671E+10 | 6735.19 | 02-MAY-13:09 | 15.60 | 10.93 |
June | 0.475157E+11 | 86818.05 | 23-JUN-04:12 | 18.13 | 11.74 | 0.525962E+10 | 6734.81 | 20-JUN-13:09 | 18.13 | 11.74 |
July | 0.497318E+11 | 87730.75 | 19-JUL-04:12 | 20.20 | 16.41 | 0.489248E+10 | 6734.97 | 03-JUL-13:09 | 20.20 | 16.41 |
August | 0.515852E+11 | 87988.60 | 14-AUG-04:12 | 12.20 | 9.88 | 0.549415E+10 | 6734.80 | 01-AUG-13:09 | 12.20 | 9.88 |
September | 0.413228E+11 | 87336.45 | 11-SEP-04:12 | 11.10 | 10.17 | 0.486315E+10 | 6735.15 | 07-SEP-09:00 | 11.10 | 10.17 |
October | 0.345829E+11 | 82679.86 | 19-OCT-05:02 | 12.20 | 5.54 | 0.502607E+10 | 6734.74 | 27-OCT-09:09 | 7.67 | 3.31 |
November | 0.285199E+11 | 68451.95 | 04-NOV-05:02 | 9.43 | 5.60 | 0.483883E+10 | 6734.76 | 03-NOV-09:09 | 9.43 | 5.60 |
December | 0.254953E+11 | 29509.55 | 07-DEC-16:30 | 5.55 | 1.71 | 0.451792E+10 | 6734.80 | 07-DEC-10:20 | 5.55 | 1.71 |
Annual Sum or Average | 0.428445E+12 | 0.590178E+11 | ||||||||
Minimum of Months | 0.231322E+11 | 21440.08 | -6.7 | -8.2 | 0.428378E+10 | 6734.47 | -6.7 | -8.2 | ||
Maximum of Months | 0.515852E+11 | 87988.60 | 20.20 | 16.41 | 0.549415E+10 | 6735.19 | 20.20 | 16.41 |
Report: ZoneCoolingSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.147795E+11 | 17906.48 | 13-JAN-17:00 | 7.80 | 3.93 | 0.398510E+10 | 6309.97 | 13-JAN-14:00 | 7.80 | 3.93 |
February | 0.171018E+11 | 26715.50 | 28-FEB-17:00 | 10.00 | 4.31 | 0.384147E+10 | 6728.70 | 28-FEB-14:00 | 10.00 | 4.31 |
March | 0.235149E+11 | 30930.16 | 23-MAR-15:20 | 7.60 | 1.00 | 0.488511E+10 | 6734.58 | 02-MAR-14:20 | 7.60 | 1.00 |
April | 0.269417E+11 | 43015.26 | 25-APR-16:00 | 17.80 | 7.70 | 0.458877E+10 | 6734.68 | 25-APR-09:20 | 17.80 | 7.70 |
May | 0.337702E+11 | 78372.42 | 20-MAY-05:02 | 11.47 | 8.41 | 0.505944E+10 | 6735.18 | 02-MAY-13:09 | 11.47 | 8.41 |
June | 0.466636E+11 | 86102.43 | 21-JUN-04:12 | 17.40 | 12.31 | 0.523154E+10 | 6734.76 | 20-JUN-13:00 | 17.40 | 12.31 |
July | 0.509002E+11 | 85269.20 | 19-JUL-04:12 | 20.20 | 16.41 | 0.488158E+10 | 6734.96 | 03-JUL-13:09 | 20.20 | 16.41 |
August | 0.505142E+11 | 84133.76 | 08-AUG-04:12 | 17.97 | 11.68 | 0.547568E+10 | 6734.78 | 01-AUG-13:09 | 17.97 | 11.68 |
September | 0.365520E+11 | 83269.40 | 05-SEP-04:12 | 18.30 | 11.92 | 0.475828E+10 | 6735.10 | 07-SEP-09:00 | 16.70 | 15.61 |
October | 0.265000E+11 | 40540.77 | 18-OCT-16:00 | 24.40 | 11.02 | 0.474181E+10 | 6734.71 | 20-OCT-09:09 | 7.98 | 4.07 |
November | 0.205018E+11 | 29073.16 | 03-NOV-16:00 | 14.30 | 7.69 | 0.436768E+10 | 6734.57 | 09-NOV-14:39 | 9.13 | 3.92 |
December | 0.166432E+11 | 20914.22 | 06-DEC-17:00 | 6.70 | 2.38 | 0.400655E+10 | 6723.03 | 07-DEC-14:00 | 8.30 | 2.55 |
Annual Sum or Average | 0.364383E+12 | 0.558230E+11 | ||||||||
Minimum of Months | 0.147795E+11 | 17906.48 | 6.70 | 1.00 | 0.384147E+10 | 6309.97 | 7.60 | 1.00 | ||
Maximum of Months | 0.509002E+11 | 86102.43 | 24.40 | 16.41 | 0.547568E+10 | 6735.18 | 20.20 | 16.41 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.103986E+10 | 2364.60 | 02-JAN-06:02 | -1.3 | -3.4 | 0.490087E+09 | 787.48 | 02-JAN-14:50 | 6.20 | 1.19 |
February | 0.176018E+10 | 4185.05 | 27-FEB-16:00 | 18.90 | 7.06 | 0.478944E+09 | 845.61 | 27-FEB-14:00 | 18.90 | 7.06 |
March | 0.309440E+10 | 4747.51 | 27-MAR-14:00 | 8.90 | 2.28 | 0.628342E+09 | 845.61 | 21-MAR-13:00 | 8.90 | 2.28 |
April | 0.441996E+10 | 7576.53 | 07-APR-14:00 | 23.30 | 9.68 | 0.590750E+09 | 845.62 | 13-APR-13:00 | 13.30 | 7.60 |
May | 0.538365E+10 | 8402.39 | 30-MAY-15:00 | 19.40 | 10.86 | 0.645755E+09 | 845.68 | 02-MAY-13:09 | 19.40 | 10.86 |
June | 0.885640E+10 | 13344.81 | 22-JUN-05:02 | 16.10 | 12.31 | 0.659633E+09 | 845.64 | 19-JUN-13:39 | 16.10 | 12.31 |
July | 0.106331E+11 | 18010.64 | 16-JUL-18:31 | 32.40 | 17.11 | 0.615371E+09 | 846.79 | 18-JUL-13:20 | 33.17 | 17.33 |
August | 0.101518E+11 | 17569.19 | 06-AUG-16:01 | 35.50 | 16.24 | 0.689554E+09 | 845.64 | 01-AUG-13:09 | 35.50 | 16.24 |
September | 0.560633E+10 | 17927.78 | 04-SEP-14:41 | 31.83 | 16.52 | 0.601854E+09 | 845.68 | 07-SEP-09:00 | 16.70 | 15.61 |
October | 0.390187E+10 | 6139.04 | 19-OCT-14:30 | 21.40 | 10.24 | 0.610196E+09 | 845.63 | 18-OCT-13:39 | 21.40 | 10.24 |
November | 0.273425E+10 | 4052.13 | 08-NOV-13:30 | 13.80 | 7.89 | 0.565491E+09 | 845.62 | 16-NOV-14:09 | 10.63 | 6.46 |
December | 0.184387E+10 | 2480.02 | 06-DEC-06:03 | 7.02 | 3.93 | 0.510216E+09 | 845.60 | 06-DEC-14:00 | 11.10 | 5.34 |
Annual Sum or Average | 0.594256E+11 | 0.708619E+10 | ||||||||
Minimum of Months | 0.103986E+10 | 2364.60 | -1.3 | -3.4 | 0.478944E+09 | 787.48 | 6.20 | 1.19 | ||
Maximum of Months | 0.106331E+11 | 18010.64 | 35.50 | 17.11 | 0.689554E+09 | 846.79 | 35.50 | 17.33 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.120553E+10 | 3197.97 | 15-JAN-10:53 | 3.30 | -1.0 | 0.315280E+09 | 544.94 | 17-JAN-10:30 | 5.25 | 1.27 |
February | 0.221488E+10 | 8066.26 | 27-FEB-09:55 | 11.70 | 4.23 | 0.310434E+09 | 544.95 | 23-FEB-10:39 | 11.70 | 4.23 |
March | 0.392547E+10 | 11611.19 | 28-MAR-09:15 | 5.73 | 0.86 | 0.396953E+09 | 544.96 | 10-MAR-10:09 | 5.73 | 0.86 |
April | 0.551872E+10 | 19149.25 | 16-APR-08:52 | 12.20 | 5.44 | 0.369191E+09 | 544.96 | 25-APR-09:09 | 9.87 | 4.86 |
May | 0.664052E+10 | 14582.43 | 19-MAY-08:30 | 16.95 | 11.09 | 0.411695E+09 | 544.99 | 02-MAY-13:09 | 16.95 | 11.09 |
June | 0.975783E+10 | 25209.95 | 25-JUN-08:22 | 16.15 | 11.58 | 0.422855E+09 | 547.19 | 23-JUN-09:00 | 16.15 | 11.58 |
July | 0.117520E+11 | 26503.63 | 02-JUL-08:41 | 21.93 | 15.30 | 0.395929E+09 | 546.86 | 03-JUL-09:00 | 23.30 | 14.49 |
August | 0.110012E+11 | 26729.74 | 06-AUG-09:21 | 28.60 | 14.63 | 0.441646E+09 | 546.58 | 04-AUG-09:00 | 28.60 | 14.63 |
September | 0.665239E+10 | 27686.20 | 04-SEP-08:41 | 26.52 | 14.78 | 0.383804E+09 | 544.99 | 07-SEP-09:00 | 16.70 | 15.61 |
October | 0.459855E+10 | 21438.06 | 15-OCT-09:32 | 15.40 | 7.79 | 0.387620E+09 | 544.96 | 18-OCT-13:39 | 24.80 | 11.21 |
November | 0.292172E+10 | 7134.91 | 06-NOV-09:35 | 1.20 | -1.1 | 0.350942E+09 | 544.95 | 03-NOV-09:09 | 1.20 | -1.1 |
December | 0.176443E+10 | 3280.92 | 20-DEC-10:05 | 3.48 | -0.5 | 0.315719E+09 | 544.94 | 20-DEC-10:20 | 3.67 | -0.4 |
Annual Sum or Average | 0.679533E+11 | 0.450207E+10 | ||||||||
Minimum of Months | 0.120553E+10 | 3197.97 | 1.20 | -1.1 | 0.310434E+09 | 544.94 | 1.20 | -1.1 | ||
Maximum of Months | 0.117520E+11 | 27686.20 | 28.60 | 15.30 | 0.441646E+09 | 547.19 | 28.60 | 15.61 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.355056E+10 | 26016.09 | 15-JAN-13:32 | 5.40 | -0.5 | 0.529137E+09 | 845.64 | 13-JAN-14:00 | 5.40 | -0.5 |
February | 0.626462E+10 | 32274.02 | 26-FEB-13:42 | 15.50 | 5.72 | 0.521350E+09 | 847.57 | 27-FEB-14:39 | 18.70 | 7.17 |
March | 0.850029E+10 | 32350.49 | 26-MAR-13:22 | 9.45 | 1.83 | 0.631862E+09 | 847.58 | 02-MAR-14:00 | 9.45 | 1.83 |
April | 0.871792E+10 | 32419.28 | 16-APR-13:32 | 19.03 | 8.17 | 0.575488E+09 | 846.61 | 24-APR-13:00 | 17.80 | 9.82 |
May | 0.880557E+10 | 18069.32 | 19-MAY-13:30 | 26.65 | 14.96 | 0.629807E+09 | 846.16 | 19-MAY-13:39 | 26.83 | 14.98 |
June | 0.117947E+11 | 25882.45 | 11-JUN-12:23 | 25.00 | 12.98 | 0.653485E+09 | 845.70 | 19-JUN-13:39 | 24.80 | 12.00 |
July | 0.150401E+11 | 30904.97 | 16-JUL-13:12 | 30.17 | 18.28 | 0.613984E+09 | 847.07 | 18-JUL-13:50 | 32.07 | 17.42 |
August | 0.172227E+11 | 31750.73 | 06-AUG-13:21 | 34.15 | 15.08 | 0.686887E+09 | 855.24 | 30-AUG-13:30 | 26.15 | 14.29 |
September | 0.128822E+11 | 34798.80 | 04-SEP-14:41 | 31.83 | 16.52 | 0.597226E+09 | 858.29 | 01-SEP-13:20 | 31.83 | 16.52 |
October | 0.109329E+11 | 36754.57 | 15-OCT-13:31 | 22.93 | 11.00 | 0.612694E+09 | 880.09 | 18-OCT-13:20 | 24.60 | 11.01 |
November | 0.754089E+10 | 29767.73 | 12-NOV-13:02 | -1.4 | -4.2 | 0.582012E+09 | 847.17 | 06-NOV-14:50 | -1.4 | -4.2 |
December | 0.500899E+10 | 18278.95 | 17-DEC-13:43 | -1.2 | -3.8 | 0.539960E+09 | 845.64 | 07-DEC-10:20 | -1.2 | -3.8 |
Annual Sum or Average | 0.116261E+12 | 0.717389E+10 | ||||||||
Minimum of Months | 0.355056E+10 | 18069.32 | -1.4 | -4.2 | 0.521350E+09 | 845.64 | -1.4 | -4.2 | ||
Maximum of Months | 0.172227E+11 | 36754.57 | 34.15 | 18.28 | 0.686887E+09 | 880.09 | 32.07 | 17.42 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.204350E+10 | 5786.22 | 13-JAN-15:30 | 9.45 | 4.93 | 0.319273E+09 | 544.94 | 13-JAN-14:00 | 9.45 | 4.93 |
February | 0.384989E+10 | 18839.92 | 26-FEB-16:22 | 15.85 | 6.07 | 0.321592E+09 | 544.94 | 23-FEB-14:00 | 15.85 | 6.07 |
March | 0.634248E+10 | 16003.33 | 12-MAR-16:12 | 5.73 | -0.9 | 0.417251E+09 | 544.95 | 21-MAR-13:50 | 2.25 | 0.50 |
April | 0.877071E+10 | 33209.75 | 16-APR-16:51 | 20.00 | 8.97 | 0.390127E+09 | 544.96 | 13-APR-13:00 | 20.00 | 8.97 |
May | 0.856485E+10 | 31612.32 | 28-MAY-17:21 | 20.55 | 10.38 | 0.411194E+09 | 544.99 | 02-MAY-13:09 | 20.55 | 10.38 |
June | 0.120672E+11 | 32099.89 | 18-JUN-17:21 | 25.30 | 14.49 | 0.425290E+09 | 544.98 | 19-JUN-13:39 | 24.80 | 12.00 |
July | 0.151262E+11 | 34439.99 | 16-JUL-17:11 | 33.13 | 17.22 | 0.397625E+09 | 544.98 | 13-JUL-09:00 | 33.13 | 17.22 |
August | 0.158371E+11 | 33579.08 | 06-AUG-16:41 | 35.10 | 15.80 | 0.445802E+09 | 544.97 | 01-AUG-13:09 | 35.10 | 15.80 |
September | 0.836389E+10 | 35973.69 | 04-SEP-16:01 | 32.80 | 16.54 | 0.383561E+09 | 544.99 | 07-SEP-09:00 | 16.70 | 15.61 |
October | 0.666954E+10 | 32661.67 | 15-OCT-15:31 | 22.40 | 10.89 | 0.394742E+09 | 544.96 | 18-OCT-13:39 | 24.80 | 11.21 |
November | 0.531862E+10 | 11155.76 | 03-NOV-15:30 | 14.45 | 7.69 | 0.378173E+09 | 544.96 | 16-NOV-14:09 | 10.63 | 6.46 |
December | 0.429633E+10 | 9774.76 | 06-DEC-15:30 | 10.25 | 4.94 | 0.353779E+09 | 544.95 | 19-DEC-14:09 | 10.97 | 6.81 |
Annual Sum or Average | 0.972503E+11 | 0.463841E+10 | ||||||||
Minimum of Months | 0.204350E+10 | 5786.22 | 5.73 | -0.9 | 0.319273E+09 | 544.94 | 2.25 | 0.50 | ||
Maximum of Months | 0.158371E+11 | 35973.69 | 35.10 | 17.22 | 0.445802E+09 | 544.99 | 35.10 | 17.22 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 58339450.55 | 1478.40 | 13-JAN-16:50 | 7.98 | 4.06 | 0.462315E+09 | 629.44 | 13-JAN-14:00 | 7.98 | 4.06 |
February | 0.512927E+09 | 2528.75 | 27-FEB-14:00 | 18.30 | 7.03 | 0.428652E+09 | 749.94 | 27-FEB-16:19 | 16.67 | 6.71 |
March | 0.140652E+10 | 2595.45 | 23-MAR-13:30 | 9.70 | 2.18 | 0.539910E+09 | 807.05 | 29-MAR-13:00 | 12.80 | 4.50 |
April | 0.233564E+10 | 5651.22 | 07-APR-14:30 | 22.50 | 9.29 | 0.529028E+09 | 845.61 | 13-APR-13:00 | 13.30 | 7.60 |
May | 0.375432E+10 | 7875.94 | 19-MAY-16:00 | 27.80 | 14.54 | 0.604972E+09 | 845.63 | 04-MAY-13:20 | 27.80 | 14.54 |
June | 0.697464E+10 | 12171.82 | 21-JUN-05:02 | 15.87 | 11.84 | 0.652166E+09 | 845.64 | 20-JUN-13:09 | 15.87 | 11.84 |
July | 0.835206E+10 | 17220.69 | 16-JUL-18:21 | 32.50 | 17.04 | 0.613208E+09 | 846.50 | 18-JUL-13:20 | 33.17 | 17.33 |
August | 0.716456E+10 | 16463.47 | 06-AUG-16:01 | 35.50 | 16.24 | 0.681509E+09 | 845.64 | 01-AUG-13:09 | 35.50 | 16.24 |
September | 0.413471E+10 | 16919.56 | 04-SEP-12:51 | 31.10 | 15.70 | 0.572265E+09 | 845.67 | 07-SEP-09:00 | 16.70 | 15.61 |
October | 0.228156E+10 | 4564.13 | 19-OCT-14:30 | 21.40 | 10.24 | 0.546884E+09 | 845.62 | 18-OCT-13:39 | 21.40 | 10.24 |
November | 0.109865E+10 | 2530.59 | 03-NOV-13:50 | 14.78 | 7.82 | 0.486339E+09 | 790.05 | 08-NOV-14:30 | 13.55 | 7.81 |
December | 0.268104E+09 | 1649.57 | 06-DEC-16:20 | 8.50 | 3.80 | 0.449777E+09 | 676.00 | 06-DEC-14:00 | 8.50 | 3.80 |
Annual Sum or Average | 0.383420E+11 | 0.656703E+10 | ||||||||
Minimum of Months | 58339450.55 | 1478.40 | 7.98 | 2.18 | 0.428652E+09 | 629.44 | 7.98 | 3.80 | ||
Maximum of Months | 0.835206E+10 | 17220.69 | 35.50 | 17.04 | 0.681509E+09 | 846.50 | 35.50 | 17.33 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.248483E+09 | 2295.13 | 20-JAN-10:00 | -3.3 | -5.9 | 0.219632E+09 | 416.29 | 20-JAN-09:00 | -3.3 | -5.9 |
February | 0.114167E+10 | 5562.18 | 28-FEB-09:55 | 1.10 | -0.5 | 0.208990E+09 | 521.20 | 28-FEB-11:20 | 4.83 | 1.71 |
March | 0.253587E+10 | 9474.68 | 28-MAR-10:10 | 7.38 | 1.58 | 0.265449E+09 | 521.21 | 01-MAR-11:09 | 7.38 | 1.58 |
April | 0.425827E+10 | 13543.61 | 25-APR-09:00 | 9.40 | 4.65 | 0.255805E+09 | 521.21 | 13-APR-14:09 | 9.40 | 4.65 |
May | 0.580433E+10 | 15345.69 | 19-MAY-08:50 | 17.52 | 11.29 | 0.290575E+09 | 521.27 | 02-MAY-12:09 | 17.52 | 11.29 |
June | 0.946617E+10 | 30517.08 | 25-JUN-08:41 | 16.52 | 11.73 | 0.307437E+09 | 522.38 | 30-JUN-10:09 | 21.05 | 13.37 |
July | 0.114741E+11 | 32371.57 | 02-JUL-09:01 | 22.48 | 15.33 | 0.290572E+09 | 523.45 | 26-JUL-10:30 | 29.80 | 14.14 |
August | 0.101947E+11 | 29379.77 | 06-AUG-09:21 | 28.60 | 14.63 | 0.321767E+09 | 524.02 | 07-AUG-10:50 | 30.60 | 14.99 |
September | 0.597138E+10 | 29008.65 | 04-SEP-08:51 | 26.70 | 14.88 | 0.270800E+09 | 521.22 | 06-SEP-10:20 | 18.17 | 15.15 |
October | 0.343716E+10 | 9388.81 | 18-OCT-10:10 | 20.28 | 8.90 | 0.262836E+09 | 521.21 | 19-OCT-10:09 | 19.18 | 9.33 |
November | 0.159934E+10 | 4996.49 | 03-NOV-10:10 | 9.10 | 5.57 | 0.231268E+09 | 521.20 | 03-NOV-10:20 | 9.50 | 5.81 |
December | 0.463605E+09 | 2420.02 | 20-DEC-10:00 | 3.30 | -0.6 | 0.212609E+09 | 430.48 | 20-DEC-09:00 | 3.30 | -0.6 |
Annual Sum or Average | 0.565952E+11 | 0.313774E+10 | ||||||||
Minimum of Months | 0.248483E+09 | 2295.13 | -3.3 | -5.9 | 0.208990E+09 | 416.29 | -3.3 | -5.9 | ||
Maximum of Months | 0.114741E+11 | 32371.57 | 28.60 | 15.33 | 0.321767E+09 | 524.02 | 30.60 | 15.15 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.265637E+10 | 18766.20 | 15-JAN-13:13 | 5.20 | -0.5 | 0.510405E+09 | 845.64 | 13-JAN-14:09 | 5.20 | -0.5 |
February | 0.545679E+10 | 34154.52 | 26-FEB-14:01 | 15.78 | 5.88 | 0.503805E+09 | 856.00 | 28-FEB-14:09 | 10.10 | 4.57 |
March | 0.720360E+10 | 29922.34 | 26-MAR-13:32 | 9.63 | 1.94 | 0.600397E+09 | 872.67 | 01-MAR-14:09 | 9.63 | 1.94 |
April | 0.706078E+10 | 32240.12 | 16-APR-15:02 | 19.50 | 8.48 | 0.545945E+09 | 846.17 | 24-APR-13:00 | 17.80 | 9.82 |
May | 0.779906E+10 | 21763.26 | 14-MAY-13:52 | 16.70 | 6.76 | 0.608887E+09 | 846.32 | 19-MAY-13:50 | 27.02 | 15.00 |
June | 0.106227E+11 | 30837.93 | 18-JUN-13:42 | 23.12 | 15.42 | 0.642259E+09 | 845.69 | 19-JUN-13:09 | 24.50 | 12.52 |
July | 0.134815E+11 | 34159.40 | 16-JUL-13:41 | 31.32 | 18.41 | 0.609659E+09 | 846.56 | 14-JUL-13:00 | 31.32 | 18.41 |
August | 0.152371E+11 | 33044.87 | 06-AUG-13:21 | 34.15 | 15.08 | 0.678307E+09 | 872.60 | 30-AUG-13:39 | 26.33 | 14.35 |
September | 0.126458E+11 | 35746.86 | 04-SEP-15:31 | 32.60 | 16.55 | 0.582964E+09 | 885.68 | 01-SEP-13:39 | 32.60 | 16.55 |
October | 0.102496E+11 | 34842.40 | 15-OCT-13:41 | 23.12 | 11.08 | 0.594862E+09 | 911.65 | 18-OCT-13:39 | 24.80 | 11.21 |
November | 0.624833E+10 | 32522.56 | 12-NOV-12:12 | -2.8 | -5.1 | 0.558784E+09 | 858.63 | 03-NOV-13:39 | -2.8 | -5.1 |
December | 0.336818E+10 | 16482.54 | 12-DEC-12:40 | -2.8 | -5.7 | 0.511034E+09 | 845.64 | 13-DEC-14:50 | -5.6 | -7.0 |
Annual Sum or Average | 0.102030E+12 | 0.694731E+10 | ||||||||
Minimum of Months | 0.265637E+10 | 16482.54 | -2.8 | -5.7 | 0.503805E+09 | 845.64 | -5.6 | -7.0 | ||
Maximum of Months | 0.152371E+11 | 35746.86 | 34.15 | 18.41 | 0.678307E+09 | 911.65 | 32.60 | 18.41 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.393672E+09 | 3192.61 | 13-JAN-15:50 | 9.08 | 4.76 | 0.302145E+09 | 500.82 | 13-JAN-15:00 | 8.90 | 4.67 |
February | 0.138172E+10 | 9066.40 | 28-FEB-16:40 | 10.37 | 4.49 | 0.285400E+09 | 544.74 | 27-FEB-14:00 | 10.37 | 4.49 |
March | 0.276437E+10 | 11796.90 | 28-MAR-17:00 | 10.60 | 2.97 | 0.350595E+09 | 544.94 | 02-MAR-14:30 | 10.60 | 2.97 |
April | 0.448579E+10 | 30941.82 | 16-APR-16:21 | 20.00 | 8.89 | 0.332310E+09 | 544.94 | 07-APR-13:09 | 20.00 | 8.89 |
May | 0.642962E+10 | 33753.22 | 28-MAY-17:51 | 20.00 | 10.33 | 0.378147E+09 | 544.95 | 25-MAY-13:09 | 20.00 | 10.33 |
June | 0.909673E+10 | 33791.75 | 18-JUN-17:41 | 25.10 | 14.47 | 0.409424E+09 | 544.96 | 19-JUN-13:09 | 24.50 | 12.52 |
July | 0.108232E+11 | 35712.50 | 16-JUL-17:01 | 33.22 | 17.33 | 0.391093E+09 | 544.97 | 03-JUL-13:09 | 33.22 | 17.33 |
August | 0.977653E+10 | 30623.94 | 06-AUG-16:41 | 35.10 | 15.80 | 0.431044E+09 | 544.96 | 01-AUG-13:09 | 35.10 | 15.80 |
September | 0.635390E+10 | 34085.64 | 04-SEP-16:11 | 32.80 | 16.58 | 0.355263E+09 | 544.95 | 05-SEP-09:09 | 17.20 | 11.96 |
October | 0.389534E+10 | 18582.20 | 15-OCT-15:42 | 22.30 | 10.85 | 0.344047E+09 | 544.94 | 18-OCT-13:00 | 25.00 | 11.40 |
November | 0.199588E+10 | 7009.89 | 03-NOV-15:40 | 14.40 | 7.69 | 0.320910E+09 | 544.92 | 09-NOV-14:00 | 9.00 | 3.82 |
December | 0.746523E+09 | 3829.71 | 06-DEC-15:40 | 9.97 | 4.80 | 0.295631E+09 | 521.18 | 06-DEC-16:10 | 8.95 | 4.16 |
Annual Sum or Average | 0.581433E+11 | 0.419601E+10 | ||||||||
Minimum of Months | 0.393672E+09 | 3192.61 | 9.08 | 2.97 | 0.285400E+09 | 500.82 | 8.90 | 2.97 | ||
Maximum of Months | 0.108232E+11 | 35712.50 | 35.10 | 17.33 | 0.431044E+09 | 544.97 | 35.10 | 17.33 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 25518555.57 | 1450.96 | 14-JAN-17:03 | 8.90 | 4.06 | 0.458336E+09 | 626.08 | 10-JAN-10:20 | 8.90 | 4.06 |
February | 0.229002E+09 | 2273.63 | 27-FEB-13:30 | 17.75 | 6.76 | 0.423050E+09 | 714.61 | 27-FEB-14:00 | 18.90 | 7.23 |
March | 0.887839E+09 | 2389.61 | 23-MAR-13:30 | 9.70 | 2.18 | 0.520622E+09 | 763.30 | 29-MAR-13:00 | 12.80 | 4.50 |
April | 0.181015E+10 | 5505.70 | 07-APR-14:30 | 22.50 | 9.29 | 0.502149E+09 | 845.60 | 07-APR-13:09 | 22.50 | 9.29 |
May | 0.343357E+10 | 8656.06 | 19-MAY-16:00 | 27.80 | 14.54 | 0.583015E+09 | 845.63 | 19-MAY-13:09 | 27.80 | 14.54 |
June | 0.689432E+10 | 11278.10 | 21-JUN-05:02 | 15.87 | 11.84 | 0.641949E+09 | 845.63 | 21-JUN-13:09 | 26.88 | 17.83 |
July | 0.854724E+10 | 19700.34 | 02-JUL-18:31 | 24.47 | 14.35 | 0.609869E+09 | 845.65 | 03-JUL-13:09 | 19.07 | 14.10 |
August | 0.716217E+10 | 19360.96 | 06-AUG-16:01 | 35.50 | 16.24 | 0.671277E+09 | 845.64 | 01-AUG-13:09 | 35.50 | 16.24 |
September | 0.378423E+10 | 18687.42 | 04-SEP-16:21 | 32.80 | 16.63 | 0.550894E+09 | 845.66 | 07-SEP-09:00 | 16.70 | 15.61 |
October | 0.168891E+10 | 4096.42 | 19-OCT-14:40 | 21.50 | 10.24 | 0.514818E+09 | 845.61 | 19-OCT-13:09 | 21.50 | 10.24 |
November | 0.600605E+09 | 2254.93 | 03-NOV-13:30 | 14.35 | 7.74 | 0.468694E+09 | 736.38 | 08-NOV-14:00 | 13.20 | 7.65 |
December | 0.112458E+09 | 1623.57 | 06-DEC-16:20 | 8.50 | 3.80 | 0.446401E+09 | 640.35 | 06-DEC-14:00 | 8.50 | 3.80 |
Annual Sum or Average | 0.351760E+11 | 0.639107E+10 | ||||||||
Minimum of Months | 25518555.57 | 1450.96 | 8.50 | 2.18 | 0.423050E+09 | 626.08 | 8.50 | 3.80 | ||
Maximum of Months | 0.854724E+10 | 19700.34 | 35.50 | 16.63 | 0.671277E+09 | 845.66 | 35.50 | 17.83 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.127990E+09 | 2108.18 | 31-JAN-10:30 | -6.1 | -8.7 | 0.298754E+09 | 418.04 | 31-JAN-10:39 | -5.7 | -8.4 |
February | 0.778873E+09 | 3573.99 | 28-FEB-10:30 | 2.50 | 0.37 | 0.280225E+09 | 544.95 | 28-FEB-10:30 | 2.50 | 0.37 |
March | 0.191966E+10 | 8055.75 | 28-MAR-09:35 | 6.47 | 1.20 | 0.356580E+09 | 544.95 | 22-MAR-09:50 | 6.47 | 1.20 |
April | 0.356415E+10 | 12590.12 | 25-APR-09:30 | 10.80 | 5.26 | 0.342865E+09 | 544.95 | 25-APR-09:09 | 10.80 | 5.26 |
May | 0.537440E+10 | 14852.45 | 19-MAY-08:50 | 17.52 | 11.29 | 0.392534E+09 | 544.99 | 02-MAY-13:09 | 17.52 | 11.29 |
June | 0.933627E+10 | 29381.90 | 25-JUN-08:11 | 15.97 | 11.51 | 0.417392E+09 | 546.39 | 23-JUN-09:00 | 15.97 | 11.51 |
July | 0.116011E+11 | 31924.14 | 02-JUL-08:31 | 21.67 | 15.15 | 0.393556E+09 | 546.08 | 03-JUL-09:00 | 23.30 | 14.49 |
August | 0.101767E+11 | 29405.92 | 06-AUG-09:21 | 28.60 | 14.63 | 0.437135E+09 | 546.49 | 11-AUG-09:00 | 27.80 | 12.62 |
September | 0.549260E+10 | 25792.94 | 04-SEP-09:02 | 26.88 | 14.90 | 0.364600E+09 | 544.97 | 14-SEP-13:00 | 21.70 | 13.42 |
October | 0.274820E+10 | 8529.49 | 18-OCT-09:50 | 19.53 | 8.61 | 0.348817E+09 | 544.95 | 27-OCT-09:39 | 9.07 | 4.22 |
November | 0.105714E+10 | 3263.16 | 03-NOV-10:00 | 8.70 | 5.33 | 0.305844E+09 | 544.51 | 03-NOV-09:00 | 8.70 | 5.33 |
December | 0.246521E+09 | 2214.00 | 20-DEC-10:20 | 3.67 | -0.4 | 0.288482E+09 | 429.95 | 20-DEC-10:30 | 3.85 | -0.4 |
Annual Sum or Average | 0.524235E+11 | 0.422678E+10 | ||||||||
Minimum of Months | 0.127990E+09 | 2108.18 | -6.1 | -8.7 | 0.280225E+09 | 418.04 | -5.7 | -8.4 | ||
Maximum of Months | 0.116011E+11 | 31924.14 | 28.60 | 15.15 | 0.437135E+09 | 546.49 | 27.80 | 14.49 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.204816E+10 | 15198.02 | 31-JAN-13:30 | -0.9 | -4.5 | 0.499944E+09 | 845.64 | 13-JAN-14:00 | -0.9 | -4.5 |
February | 0.442276E+10 | 34851.62 | 26-FEB-14:01 | 15.78 | 5.88 | 0.488886E+09 | 845.64 | 23-FEB-14:20 | 15.78 | 5.88 |
March | 0.602314E+10 | 26175.23 | 26-MAR-14:02 | 10.00 | 2.16 | 0.582786E+09 | 846.10 | 23-MAR-13:50 | 10.00 | 2.16 |
April | 0.602392E+10 | 21605.86 | 25-APR-13:30 | 16.40 | 7.12 | 0.528720E+09 | 846.26 | 24-APR-13:00 | 16.40 | 7.12 |
May | 0.728350E+10 | 23409.43 | 14-MAY-14:22 | 16.70 | 6.45 | 0.593770E+09 | 845.72 | 02-MAY-13:09 | 16.70 | 6.45 |
June | 0.105200E+11 | 32004.87 | 25-JUN-16:11 | 24.23 | 12.89 | 0.631647E+09 | 845.67 | 21-JUN-13:09 | 24.23 | 12.89 |
July | 0.137313E+11 | 34557.39 | 02-JUL-13:12 | 25.53 | 14.08 | 0.603842E+09 | 846.84 | 18-JUL-13:00 | 31.70 | 17.43 |
August | 0.152401E+11 | 35360.05 | 06-AUG-13:21 | 34.15 | 15.08 | 0.668880E+09 | 854.89 | 30-AUG-13:39 | 26.33 | 14.35 |
September | 0.119193E+11 | 37751.71 | 03-SEP-12:41 | 33.22 | 15.94 | 0.568136E+09 | 867.56 | 01-SEP-13:39 | 33.22 | 15.94 |
October | 0.872772E+10 | 35958.42 | 15-OCT-13:41 | 23.12 | 11.08 | 0.574280E+09 | 879.64 | 18-OCT-13:39 | 24.80 | 11.21 |
November | 0.492728E+10 | 24041.73 | 03-NOV-13:30 | 14.35 | 7.74 | 0.538064E+09 | 845.73 | 03-NOV-13:50 | 14.78 | 7.82 |
December | 0.253917E+10 | 13579.97 | 12-DEC-14:30 | -2.2 | -5.4 | 0.494790E+09 | 845.64 | 19-DEC-14:09 | 10.97 | 6.81 |
Annual Sum or Average | 0.934063E+11 | 0.677375E+10 | ||||||||
Minimum of Months | 0.204816E+10 | 13579.97 | -2.2 | -5.4 | 0.488886E+09 | 845.64 | -0.9 | -4.5 | ||
Maximum of Months | 0.152401E+11 | 37751.71 | 34.15 | 15.94 | 0.668880E+09 | 879.64 | 33.22 | 17.43 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.296884E+09 | 3219.23 | 13-JAN-15:50 | 9.08 | 4.76 | 0.300485E+09 | 486.01 | 13-JAN-15:00 | 8.90 | 4.67 |
February | 0.105011E+10 | 8636.47 | 28-FEB-16:40 | 10.37 | 4.49 | 0.282126E+09 | 544.05 | 27-FEB-14:00 | 10.37 | 4.49 |
March | 0.216651E+10 | 11585.26 | 28-MAR-17:00 | 10.60 | 2.97 | 0.344871E+09 | 544.93 | 02-MAR-14:00 | 10.60 | 2.97 |
April | 0.390275E+10 | 29835.58 | 22-APR-17:41 | 16.10 | 8.34 | 0.322207E+09 | 544.94 | 07-APR-13:39 | 16.10 | 8.34 |
May | 0.610009E+10 | 35270.52 | 28-MAY-17:51 | 20.00 | 10.33 | 0.368608E+09 | 544.96 | 19-MAY-13:09 | 20.00 | 10.33 |
June | 0.905656E+10 | 35672.92 | 18-JUN-17:11 | 25.40 | 14.50 | 0.401811E+09 | 544.96 | 20-JUN-13:00 | 28.90 | 18.82 |
July | 0.110031E+11 | 36675.62 | 02-JUL-17:51 | 25.60 | 14.12 | 0.386705E+09 | 544.97 | 03-JUL-13:09 | 19.07 | 14.10 |
August | 0.979947E+10 | 32628.64 | 06-AUG-16:41 | 35.10 | 15.80 | 0.423487E+09 | 544.96 | 01-AUG-13:09 | 35.10 | 15.80 |
September | 0.598612E+10 | 32623.29 | 04-SEP-16:21 | 32.80 | 16.63 | 0.345704E+09 | 544.94 | 05-SEP-13:00 | 24.40 | 15.14 |
October | 0.320981E+10 | 15053.53 | 15-OCT-16:22 | 21.65 | 10.63 | 0.332483E+09 | 544.92 | 18-OCT-13:00 | 25.00 | 11.40 |
November | 0.143432E+10 | 6512.30 | 03-NOV-15:40 | 14.40 | 7.69 | 0.313583E+09 | 544.62 | 09-NOV-14:00 | 9.00 | 3.82 |
December | 0.503134E+09 | 3466.79 | 06-DEC-15:50 | 9.68 | 4.65 | 0.292219E+09 | 514.17 | 06-DEC-15:00 | 9.40 | 4.51 |
Annual Sum or Average | 0.545088E+11 | 0.411429E+10 | ||||||||
Minimum of Months | 0.296884E+09 | 3219.23 | 9.08 | 2.97 | 0.282126E+09 | 486.01 | 8.90 | 2.97 | ||
Maximum of Months | 0.110031E+11 | 36675.62 | 35.10 | 16.63 | 0.423487E+09 | 544.97 | 35.10 | 18.82 |
Report: ZoneCoolingSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.750817E+09 | 10818.23 | 06-JAN-05:01 | -24.5 | -24.9 | 0.00 | 0.00 | 01-JAN-00:10 | -24.5 | -24.9 |
February | 0.980988E+09 | 9873.44 | 04-FEB-05:01 | -20.4 | -20.8 | 0.00 | 0.00 | 01-FEB-00:10 | -20.4 | -20.8 |
March | 0.253324E+10 | 8763.65 | 04-MAR-05:01 | -19.1 | -19.6 | 0.00 | 0.00 | 01-MAR-00:10 | -19.1 | -19.6 |
April | 0.436717E+10 | 6567.84 | 24-APR-16:00 | 18.90 | 10.03 | 0.00 | 0.00 | 01-APR-00:10 | 18.90 | 10.03 |
May | 0.438254E+10 | 8144.18 | 30-MAY-05:15 | 15.60 | 11.34 | 0.00 | 0.00 | 01-MAY-00:10 | 15.60 | 11.34 |
June | 0.801561E+10 | 8570.88 | 26-JUN-05:15 | 10.33 | 9.12 | 0.00 | 0.00 | 01-JUN-00:10 | 10.33 | 9.12 |
July | 0.100296E+11 | 10642.96 | 17-JUL-15:20 | 36.47 | 17.10 | 0.00 | 0.00 | 01-JUL-00:10 | 36.47 | 17.10 |
August | 0.103131E+11 | 11652.63 | 07-AUG-05:15 | 17.77 | 10.09 | 0.00 | 0.00 | 01-AUG-00:10 | 17.77 | 10.09 |
September | 0.602539E+10 | 11999.96 | 05-SEP-05:03 | 18.40 | 11.40 | 0.00 | 0.00 | 01-SEP-00:10 | 18.40 | 11.40 |
October | 0.428965E+10 | 6145.43 | 16-OCT-15:50 | 19.68 | 8.22 | 0.00 | 0.00 | 01-OCT-00:10 | 19.68 | 8.22 |
November | 0.249400E+10 | 10640.67 | 27-NOV-05:01 | -15.4 | -16.5 | 0.00 | 0.00 | 01-NOV-00:10 | -15.4 | -16.5 |
December | 0.122146E+10 | 10127.31 | 28-DEC-05:01 | -22.3 | -22.7 | 0.00 | 0.00 | 01-DEC-00:10 | -22.3 | -22.7 |
Annual Sum or Average | 0.554036E+11 | 0.00 | ||||||||
Minimum of Months | 0.750817E+09 | 6145.43 | -24.5 | -24.9 | 0.00 | 0.00 | -24.5 | -24.9 | ||
Maximum of Months | 0.103131E+11 | 11999.96 | 36.47 | 17.10 | 0.00 | 0.00 | 36.47 | 17.10 |
Report: ZoneCoolingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.605877E+09 | 15039.52 | 06-JAN-04:01 | -24.4 | -24.9 | 0.00 | 0.00 | 01-JAN-00:10 | -24.4 | -24.9 |
February | 0.408181E+09 | 13991.63 | 10-FEB-04:11 | -19.4 | -19.8 | 0.00 | 0.00 | 01-FEB-00:10 | -19.4 | -19.8 |
March | 0.965889E+09 | 16331.48 | 04-MAR-04:01 | -18.4 | -18.9 | 0.00 | 0.00 | 01-MAR-00:10 | -18.4 | -18.9 |
April | 0.154968E+10 | 12546.71 | 29-APR-04:01 | -7.8 | -8.7 | 0.00 | 0.00 | 01-APR-00:10 | -7.8 | -8.7 |
May | 0.232745E+10 | 10814.91 | 22-MAY-04:42 | -0.5 | -0.5 | 0.00 | 0.00 | 01-MAY-00:10 | -0.5 | -0.5 |
June | 0.561054E+10 | 7274.05 | 23-JUN-15:30 | 27.50 | 14.33 | 0.00 | 0.00 | 01-JUN-00:10 | 27.50 | 14.33 |
July | 0.739381E+10 | 8991.64 | 17-JUL-15:30 | 36.65 | 17.14 | 0.00 | 0.00 | 01-JUL-00:10 | 36.65 | 17.14 |
August | 0.716863E+10 | 8928.88 | 07-AUG-15:40 | 32.40 | 16.10 | 0.00 | 0.00 | 01-AUG-00:10 | 32.40 | 16.10 |
September | 0.411136E+10 | 8477.26 | 05-SEP-14:40 | 24.40 | 14.90 | 0.00 | 0.00 | 01-SEP-00:10 | 24.40 | 14.90 |
October | 0.189297E+10 | 9851.59 | 10-OCT-04:01 | -5.2 | -5.7 | 0.00 | 0.00 | 01-OCT-00:10 | -5.2 | -5.7 |
November | 0.986147E+09 | 11302.21 | 27-NOV-02:21 | -16.0 | -16.8 | 0.00 | 0.00 | 01-NOV-00:10 | -16.0 | -16.8 |
December | 0.737432E+09 | 14364.01 | 23-DEC-04:01 | -11.7 | -12.5 | 0.00 | 0.00 | 01-DEC-00:10 | -11.7 | -12.5 |
Annual Sum or Average | 0.337580E+11 | 0.00 | ||||||||
Minimum of Months | 0.408181E+09 | 7274.05 | -24.4 | -24.9 | 0.00 | 0.00 | -24.4 | -24.9 | ||
Maximum of Months | 0.739381E+10 | 16331.48 | 36.65 | 17.14 | 0.00 | 0.00 | 36.65 | 17.14 |
Report: ZoneCoolingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 631272.88 | 341.66 | 14-JAN-13:30 | 10.00 | 4.73 | 0.00 | 0.00 | 01-JAN-00:10 | 10.00 | 4.73 |
February | 0.105315E+09 | 3278.14 | 26-FEB-14:44 | 16.52 | 6.36 | 0.00 | 0.00 | 01-FEB-00:10 | 16.52 | 6.36 |
March | 0.678337E+09 | 5222.14 | 23-MAR-13:55 | 10.00 | 2.51 | 0.00 | 0.00 | 01-MAR-00:10 | 10.00 | 2.51 |
April | 0.236677E+10 | 12276.06 | 25-APR-15:00 | 17.00 | 7.46 | 0.00 | 0.00 | 01-APR-00:10 | 17.00 | 7.46 |
May | 0.503064E+10 | 17793.21 | 19-MAY-15:00 | 28.30 | 14.88 | 0.00 | 0.00 | 01-MAY-00:10 | 28.30 | 14.88 |
June | 0.101589E+11 | 20243.87 | 23-JUN-13:30 | 31.40 | 15.21 | 0.00 | 0.00 | 01-JUN-00:10 | 31.40 | 15.21 |
July | 0.133937E+11 | 24012.12 | 17-JUL-14:50 | 36.20 | 17.00 | 0.00 | 0.00 | 01-JUL-00:10 | 36.20 | 17.00 |
August | 0.115055E+11 | 21733.44 | 07-AUG-15:40 | 32.40 | 16.10 | 0.00 | 0.00 | 01-AUG-00:10 | 32.40 | 16.10 |
September | 0.542536E+10 | 16251.06 | 01-SEP-15:40 | 28.30 | 14.15 | 0.00 | 0.00 | 01-SEP-00:10 | 28.30 | 14.15 |
October | 0.143985E+10 | 9811.65 | 18-OCT-15:20 | 24.80 | 11.42 | 0.00 | 0.00 | 01-OCT-00:10 | 24.80 | 11.42 |
November | 0.102737E+09 | 2475.42 | 03-NOV-14:15 | 14.87 | 7.79 | 0.00 | 0.00 | 01-NOV-00:10 | 14.87 | 7.79 |
December | 0.00 | 0.00 | 01-DEC-00:10 | -2.1 | -4.2 | 0.00 | 0.00 | 01-DEC-00:10 | -2.1 | -4.2 |
Annual Sum or Average | 0.502077E+11 | 0.00 | ||||||||
Minimum of Months | 0.00 | 0.00 | -2.1 | -4.2 | 0.00 | 0.00 | -2.1 | -4.2 | ||
Maximum of Months | 0.133937E+11 | 24012.12 | 36.20 | 17.00 | 0.00 | 0.00 | 36.20 | 17.00 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.201798E+10 | 2249.31 | 19-JAN-16:50 | -6.4 | -8.0 | 95176331.83 | 126.82 | 20-JAN-14:09 | 0.50 | -3.2 |
February | 0.725232E+10 | 4600.84 | 26-FEB-17:27 | 13.35 | 5.05 | 86396431.72 | 126.82 | 08-FEB-14:09 | 13.35 | 5.05 |
March | 0.138113E+11 | 6810.82 | 31-MAR-24:00 | 2.50 | 0.99 | 0.103236E+09 | 126.82 | 07-MAR-14:09 | 2.50 | 0.99 |
April | 0.188333E+11 | 8501.87 | 22-APR-18:10 | 15.63 | 8.19 | 91605262.18 | 126.82 | 21-APR-09:00 | 15.63 | 8.19 |
May | 0.431845E+10 | 3508.69 | 31-MAY-24:00 | 15.50 | 10.27 | 99234994.00 | 126.84 | 30-MAY-09:39 | 15.50 | 10.27 |
June | 0.948539E+10 | 5376.53 | 30-JUN-24:00 | 19.60 | 12.23 | 98962642.99 | 126.85 | 01-JUN-13:50 | 19.60 | 12.23 |
July | 0.150153E+11 | 7270.88 | 31-JUL-23:45 | 19.48 | 11.61 | 91883798.14 | 126.84 | 03-JUL-13:09 | 19.48 | 11.61 |
August | 0.200158E+11 | 8528.18 | 03-AUG-18:50 | 24.60 | 12.54 | 0.103324E+09 | 128.74 | 11-AUG-13:00 | 32.20 | 13.16 |
September | 0.431671E+10 | 3303.90 | 30-SEP-24:00 | 11.80 | 6.26 | 91611062.85 | 126.85 | 06-SEP-13:00 | 11.80 | 6.26 |
October | 0.921807E+10 | 4932.76 | 31-OCT-24:00 | 4.70 | 1.47 | 95230954.36 | 126.83 | 25-OCT-09:00 | 4.70 | 1.47 |
November | 0.134220E+11 | 6340.38 | 13-NOV-16:30 | 3.15 | -2.5 | 94300315.11 | 126.83 | 08-NOV-14:00 | 3.15 | -2.5 |
December | 0.183621E+11 | 8084.68 | 06-DEC-16:10 | 8.95 | 4.16 | 91880781.11 | 126.82 | 15-DEC-14:39 | -10.6 | -10.9 |
Annual Sum or Average | 0.136069E+12 | 0.114284E+10 | ||||||||
Minimum of Months | 0.201798E+10 | 2249.31 | -6.4 | -8.0 | 86396431.72 | 126.82 | -10.6 | -10.9 | ||
Maximum of Months | 0.200158E+11 | 8528.18 | 24.60 | 12.54 | 0.103324E+09 | 128.74 | 32.20 | 13.16 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.493958E+09 | 1867.81 | 19-JAN-16:50 | -6.4 | -8.0 | 93228851.76 | 126.82 | 02-JAN-14:09 | -6.4 | -8.0 |
February | 0.494928E+10 | 4220.37 | 28-FEB-17:00 | 10.00 | 4.31 | 86396452.49 | 126.82 | 08-FEB-14:09 | 10.00 | 4.31 |
March | 0.113505E+11 | 6212.16 | 28-MAR-17:50 | 9.18 | 2.32 | 0.103236E+09 | 126.82 | 07-MAR-14:09 | 9.18 | 2.32 |
April | 0.167862E+11 | 8069.72 | 25-APR-18:10 | 16.73 | 7.64 | 91605312.34 | 126.82 | 24-APR-09:50 | 16.73 | 7.64 |
May | 0.328297E+10 | 3302.64 | 31-MAY-24:00 | 15.50 | 10.27 | 99234860.93 | 126.84 | 30-MAY-09:39 | 15.50 | 10.27 |
June | 0.864338E+10 | 5249.46 | 30-JUN-24:00 | 19.60 | 12.23 | 98962664.29 | 126.85 | 01-JUN-13:00 | 19.60 | 12.23 |
July | 0.141120E+11 | 7065.97 | 31-JUL-23:53 | 19.20 | 11.32 | 91884196.64 | 126.84 | 03-JUL-13:09 | 19.20 | 11.32 |
August | 0.188051E+11 | 8198.17 | 03-AUG-18:50 | 24.60 | 12.54 | 0.103253E+09 | 126.83 | 01-AUG-13:00 | 24.60 | 12.54 |
September | 0.344794E+10 | 2873.68 | 30-SEP-23:30 | 12.50 | 6.83 | 91610048.27 | 126.85 | 06-SEP-13:20 | 12.50 | 6.83 |
October | 0.749219E+10 | 4300.32 | 16-OCT-17:00 | 17.80 | 7.68 | 95230856.70 | 126.83 | 25-OCT-09:00 | 13.30 | 8.54 |
November | 0.108683E+11 | 5750.11 | 10-NOV-16:30 | 4.70 | 0.35 | 94300349.32 | 126.83 | 08-NOV-14:00 | 4.70 | 0.35 |
December | 0.147485E+11 | 7376.02 | 06-DEC-16:20 | 8.50 | 3.80 | 91880816.59 | 126.82 | 18-DEC-14:39 | 0.60 | -2.8 |
Annual Sum or Average | 0.114980E+12 | 0.114082E+10 | ||||||||
Minimum of Months | 0.493958E+09 | 1867.81 | -6.4 | -8.0 | 86396452.49 | 126.82 | -6.4 | -8.0 | ||
Maximum of Months | 0.188051E+11 | 8198.17 | 24.60 | 12.54 | 0.103253E+09 | 126.85 | 24.60 | 12.54 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.242024E+09 | 1638.36 | 13-JAN-16:30 | 8.35 | 4.30 | 89022331.46 | 128.34 | 03-JAN-10:30 | 8.35 | 4.30 |
February | 0.349029E+10 | 4162.72 | 28-FEB-17:00 | 10.00 | 4.31 | 86391338.42 | 126.82 | 08-FEB-14:09 | 10.00 | 4.31 |
March | 0.979014E+10 | 6202.27 | 28-MAR-17:50 | 9.18 | 2.32 | 0.103236E+09 | 126.82 | 07-MAR-14:09 | 9.18 | 2.32 |
April | 0.156570E+11 | 8133.73 | 25-APR-18:10 | 16.73 | 7.64 | 91605336.97 | 126.83 | 24-APR-09:50 | 16.73 | 7.64 |
May | 0.273692E+10 | 3221.05 | 31-MAY-23:30 | 15.80 | 10.39 | 98965836.03 | 126.84 | 30-MAY-09:39 | 15.80 | 10.39 |
June | 0.838846E+10 | 5234.38 | 30-JUN-23:33 | 19.90 | 12.27 | 98962650.69 | 126.85 | 01-JUN-13:00 | 19.90 | 12.27 |
July | 0.140012E+11 | 7049.44 | 31-JUL-23:53 | 19.20 | 11.32 | 91884149.03 | 126.84 | 03-JUL-13:09 | 19.20 | 11.32 |
August | 0.186206E+11 | 8260.23 | 03-AUG-18:50 | 24.60 | 12.54 | 0.103250E+09 | 126.83 | 01-AUG-13:00 | 24.60 | 12.54 |
September | 0.291773E+10 | 3025.79 | 04-SEP-17:51 | 31.70 | 16.34 | 91607550.86 | 126.85 | 06-SEP-13:20 | 24.47 | 18.01 |
October | 0.612501E+10 | 4327.09 | 18-OCT-17:00 | 21.70 | 10.27 | 95230841.27 | 126.83 | 25-OCT-09:00 | 13.30 | 8.54 |
November | 0.908813E+10 | 5688.57 | 03-NOV-16:00 | 14.30 | 7.69 | 94300358.88 | 126.83 | 08-NOV-14:00 | 13.20 | 7.65 |
December | 0.128471E+11 | 7310.22 | 06-DEC-16:20 | 8.50 | 3.80 | 91880826.60 | 126.82 | 27-DEC-10:50 | -12.0 | -12.5 |
Annual Sum or Average | 0.103905E+12 | 0.113634E+10 | ||||||||
Minimum of Months | 0.242024E+09 | 1638.36 | 8.35 | 2.32 | 86391338.42 | 126.82 | -12.0 | -12.5 | ||
Maximum of Months | 0.186206E+11 | 8260.23 | 31.70 | 16.34 | 0.103250E+09 | 128.34 | 24.60 | 18.01 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.234676E+12 | 92071.65 | 03-JAN-17:00 | -1.7 | -5.3 | 0.206152E+10 | 2745.44 | 02-JAN-14:00 | -1.7 | -5.3 |
February | 0.434211E+12 | 184356.90 | 28-FEB-17:00 | 10.00 | 4.31 | 0.187032E+10 | 2745.68 | 24-FEB-10:20 | 10.00 | 4.31 |
March | 0.728250E+12 | 358038.15 | 31-MAR-24:00 | 2.50 | 0.99 | 0.223481E+10 | 2745.70 | 23-MAR-09:50 | 2.50 | 0.99 |
April | 0.942814E+12 | 368316.92 | 25-APR-16:00 | 17.80 | 7.70 | 0.198314E+10 | 2747.22 | 24-APR-09:00 | 17.80 | 7.70 |
May | 0.241164E+12 | 176652.70 | 31-MAY-24:00 | 15.50 | 10.27 | 0.214819E+10 | 2747.28 | 19-MAY-13:09 | 15.50 | 10.27 |
June | 0.471537E+12 | 268627.72 | 30-JUN-24:00 | 19.60 | 12.23 | 0.214264E+10 | 2749.43 | 23-JUN-09:30 | 19.60 | 12.23 |
July | 0.734190E+12 | 360924.35 | 31-JUL-23:53 | 19.20 | 11.32 | 0.199035E+10 | 2752.56 | 03-JUL-09:39 | 19.20 | 11.32 |
August | 0.977463E+12 | 383626.60 | 06-AUG-19:52 | 26.10 | 13.21 | 0.241039E+10 | 4572.62 | 10-AUG-15:09 | 33.53 | 14.51 |
September | 0.236373E+12 | 176028.50 | 30-SEP-24:00 | 11.80 | 6.26 | 0.198308E+10 | 2746.95 | 05-SEP-13:39 | 11.80 | 6.26 |
October | 0.487639E+12 | 267971.63 | 31-OCT-24:00 | 4.70 | 1.47 | 0.206154E+10 | 2745.56 | 30-OCT-09:00 | 4.70 | 1.47 |
November | 0.707697E+12 | 277147.98 | 06-NOV-16:55 | 6.70 | 2.26 | 0.204138E+10 | 2745.54 | 16-NOV-14:00 | 10.80 | 6.43 |
December | 0.974161E+12 | 368477.76 | 06-DEC-17:00 | 6.70 | 2.38 | 0.198899E+10 | 2746.00 | 19-DEC-14:00 | 12.80 | 7.62 |
Annual Sum or Average | 0.717017E+13 | 0.249164E+11 | ||||||||
Minimum of Months | 0.234676E+12 | 92071.65 | -1.7 | -5.3 | 0.187032E+10 | 2745.44 | -1.7 | -5.3 | ||
Maximum of Months | 0.977463E+12 | 383626.60 | 26.10 | 13.21 | 0.241039E+10 | 4572.62 | 33.53 | 14.51 |
Report: ZoneHeatingSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.237691E+09 | 13365.94 | 05-JAN-05:03 | -4.1 |
February | 59529971.50 | 13613.47 | 10-FEB-06:05 | -19.9 |
March | 0.159987E+09 | 13499.41 | 13-MAR-03:03 | 0.10 |
April | 0.101342E+09 | 13883.19 | 18-APR-04:15 | 1.83 |
May | 0.285176E+09 | 16154.30 | 20-MAY-16:25 | 29.45 |
June | 0.262545E+09 | 15410.00 | 24-JUN-16:01 | 28.22 |
July | 0.399095E+09 | 20947.84 | 15-JUL-16:01 | 32.80 |
August | 0.337112E+09 | 24070.36 | 05-AUG-16:01 | 35.22 |
September | 0.367365E+09 | 22320.84 | 02-SEP-16:01 | 33.98 |
October | 0.316927E+09 | 13871.72 | 14-OCT-04:05 | 1.70 |
November | 0.198356E+09 | 15478.80 | 12-NOV-11:32 | -3.9 |
December | 0.109439E+09 | 13931.73 | 07-DEC-06:05 | -1.2 |
Annual Sum or Average | 0.283457E+10 | |||
Minimum of Months | 59529971.50 | 13365.94 | -19.9 | |
Maximum of Months | 0.399095E+09 | 24070.36 | 35.22 |
Report: ZoneHeatingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 1.38 |
February | 0.00 | 0.00 | 01-FEB-00:05 | -12.4 |
March | 0.00 | 0.00 | 01-MAR-00:10 | -3.0 |
April | 0.00 | 0.00 | 01-APR-00:10 | 2.68 |
May | 0.00 | 0.00 | 01-MAY-00:10 | -1.1 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 15.42 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 19.45 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 18.90 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 18.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 11.57 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 4.98 |
December | 0.00 | 0.00 | 01-DEC-00:10 | -2.1 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | -12.4 | |
Maximum of Months | 0.00 | 0.00 | 19.45 |
Report: ZoneHeatingSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.596444E+09 | 53585.05 | 09-JAN-05:11 | -27.2 |
February | 0.162479E+09 | 52815.29 | 06-FEB-05:01 | -0.4 |
March | 55622030.11 | 50009.53 | 06-MAR-05:01 | -18.4 |
April | 0.00 | 0.00 | 01-APR-00:10 | 2.68 |
May | 0.00 | 0.00 | 01-MAY-00:10 | -1.1 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 15.42 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 19.45 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 18.90 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 18.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 11.57 |
November | 30998000.89 | 47660.56 | 27-NOV-05:01 | -15.4 |
December | 0.179315E+09 | 52395.62 | 26-DEC-05:01 | -7.3 |
Annual Sum or Average | 0.102486E+10 | |||
Minimum of Months | 0.00 | 0.00 | -27.2 | |
Maximum of Months | 0.596444E+09 | 53585.05 | 19.45 |
Report: ZoneHeatingSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.820224E+10 | 84607.38 | 09-JAN-04:01 | -27.2 |
February | 0.295635E+10 | 82281.39 | 06-FEB-04:01 | -0.6 |
March | 0.173399E+10 | 82611.75 | 06-MAR-04:01 | -18.4 |
April | 60375472.44 | 66706.02 | 10-APR-05:02 | 3.90 |
May | 0.565857E+09 | 74648.15 | 08-MAY-04:01 | -2.3 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 15.42 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 19.45 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 18.90 |
September | 167449.50 | 1116.33 | 19-SEP-05:03 | 2.20 |
October | 0.306777E+09 | 74973.45 | 10-OCT-04:11 | -5.4 |
November | 0.208201E+10 | 81740.31 | 27-NOV-04:01 | -15.8 |
December | 0.426630E+10 | 82569.82 | 26-DEC-04:11 | -6.5 |
Annual Sum or Average | 0.201741E+11 | |||
Minimum of Months | 0.00 | 0.00 | -27.2 | |
Maximum of Months | 0.820224E+10 | 84607.38 | 19.45 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.293254E+10 | 15183.82 | 09-JAN-04:01 | -27.2 |
February | 0.757132E+09 | 13840.47 | 04-FEB-05:01 | -20.4 |
March | 0.164960E+09 | 13778.24 | 06-MAR-05:21 | -17.2 |
April | 716153.26 | 9407.36 | 29-APR-05:01 | -7.7 |
May | 2895801.48 | 12318.26 | 08-MAY-05:01 | -2.8 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 15.42 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 19.45 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 18.90 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 18.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 11.57 |
November | 77540214.63 | 13687.04 | 27-NOV-05:01 | -15.4 |
December | 0.559180E+09 | 13802.84 | 28-DEC-05:01 | -22.3 |
Annual Sum or Average | 0.449496E+10 | |||
Minimum of Months | 0.00 | 0.00 | -27.2 | |
Maximum of Months | 0.293254E+10 | 15183.82 | 19.45 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.190460E+10 | 17408.63 | 09-JAN-04:01 | -27.2 |
February | 0.550639E+09 | 15578.39 | 04-FEB-05:01 | -20.4 |
March | 0.139626E+09 | 16255.78 | 06-MAR-04:01 | -18.4 |
April | 5083997.25 | 12395.49 | 29-APR-05:01 | -7.7 |
May | 3962684.24 | 12427.70 | 08-MAY-05:01 | -2.8 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 15.42 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 19.45 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 18.90 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 18.43 |
October | 832123.20 | 7143.81 | 10-OCT-05:01 | -6.1 |
November | 94265377.57 | 15527.87 | 27-NOV-05:01 | -15.4 |
December | 0.568463E+09 | 15571.38 | 30-DEC-05:21 | -20.6 |
Annual Sum or Average | 0.326747E+10 | |||
Minimum of Months | 0.00 | 0.00 | -27.2 | |
Maximum of Months | 0.190460E+10 | 17408.63 | 19.45 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.267308E+10 | 24929.93 | 10-JAN-04:01 | -23.9 |
February | 0.678310E+09 | 23282.19 | 04-FEB-04:01 | -21.9 |
March | 0.240208E+09 | 24251.69 | 06-MAR-04:01 | -18.4 |
April | 12251235.24 | 18885.29 | 29-APR-05:01 | -7.7 |
May | 37366663.37 | 19983.05 | 08-MAY-04:01 | -2.3 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 15.42 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 19.45 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 18.90 |
September | 3958.48 | 26.39 | 19-SEP-05:05 | 2.20 |
October | 13091515.01 | 18296.07 | 10-OCT-05:01 | -6.1 |
November | 0.189766E+09 | 22570.37 | 27-NOV-05:01 | -15.4 |
December | 0.763784E+09 | 23352.23 | 29-DEC-04:01 | -24.5 |
Annual Sum or Average | 0.460786E+10 | |||
Minimum of Months | 0.00 | 0.00 | -24.5 | |
Maximum of Months | 0.267308E+10 | 24929.93 | 19.45 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.985730E+09 | 16866.71 | 09-JAN-04:01 | -27.2 |
February | 99757254.76 | 14241.44 | 04-FEB-05:01 | -20.4 |
March | 18667217.87 | 13519.14 | 06-MAR-05:01 | -18.4 |
April | 0.00 | 0.00 | 01-APR-00:10 | 2.68 |
May | 1401631.37 | 10051.39 | 08-MAY-05:01 | -2.8 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 15.42 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 19.45 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 18.90 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 18.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 11.57 |
November | 6413183.08 | 13365.40 | 27-NOV-05:01 | -15.4 |
December | 24707559.00 | 12740.64 | 28-DEC-05:01 | -22.3 |
Annual Sum or Average | 0.113668E+10 | |||
Minimum of Months | 0.00 | 0.00 | -27.2 | |
Maximum of Months | 0.985730E+09 | 16866.71 | 19.45 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.982734E+10 | 16049.48 | 09-JAN-04:31 | -27.2 |
February | 0.446945E+10 | 15096.67 | 06-FEB-04:11 | -0.6 |
March | 0.221635E+10 | 15656.36 | 05-MAR-23:21 | -16.4 |
April | 0.328610E+09 | 13239.00 | 29-APR-04:01 | -7.8 |
May | 0.282566E+09 | 13210.90 | 01-MAY-04:01 | -0.6 |
June | 131879.84 | 879.20 | 17-JUN-05:03 | 2.35 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 19.45 |
August | 356582.95 | 2377.22 | 18-AUG-05:03 | 7.30 |
September | 58765975.56 | 12435.94 | 19-SEP-04:11 | 2.20 |
October | 0.293820E+09 | 13133.92 | 10-OCT-04:01 | -5.2 |
November | 0.217575E+10 | 15237.09 | 27-NOV-03:41 | -15.8 |
December | 0.597468E+10 | 15574.10 | 31-DEC-08:61 | -27.6 |
Annual Sum or Average | 0.256278E+11 | |||
Minimum of Months | 0.00 | 0.00 | -27.6 | |
Maximum of Months | 0.982734E+10 | 16049.48 | 19.45 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.590355E+10 | 23060.02 | 09-JAN-04:31 | -27.2 |
February | 0.249773E+10 | 21864.16 | 06-FEB-04:11 | -0.6 |
March | 0.125398E+10 | 22591.87 | 05-MAR-23:21 | -16.4 |
April | 0.189335E+09 | 19214.68 | 29-APR-04:01 | -7.8 |
May | 0.182221E+09 | 19258.67 | 09-MAY-04:01 | -1.8 |
June | 356971.17 | 2033.67 | 17-JUN-05:03 | 2.35 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 19.45 |
August | 843999.05 | 4128.38 | 18-AUG-05:03 | 7.30 |
September | 32618872.28 | 16517.65 | 19-SEP-04:11 | 2.20 |
October | 0.168971E+09 | 18853.14 | 10-OCT-04:01 | -5.2 |
November | 0.132012E+10 | 22122.22 | 27-NOV-03:41 | -15.8 |
December | 0.358235E+10 | 22722.53 | 31-DEC-08:61 | -27.6 |
Annual Sum or Average | 0.151321E+11 | |||
Minimum of Months | 0.00 | 0.00 | -27.6 | |
Maximum of Months | 0.590355E+10 | 23060.02 | 19.45 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.637183E+10 | 27759.55 | 09-JAN-02:31 | -27.2 |
February | 0.236253E+10 | 26337.78 | 06-FEB-04:11 | -0.6 |
March | 0.138939E+10 | 27074.74 | 06-MAR-04:01 | -18.4 |
April | 0.256898E+09 | 23234.03 | 29-APR-04:01 | -7.8 |
May | 0.292058E+09 | 23403.08 | 09-MAY-04:01 | -1.8 |
June | 1928547.00 | 6678.64 | 17-JUN-05:03 | 2.35 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 19.45 |
August | 670105.39 | 4164.38 | 18-AUG-05:03 | 7.30 |
September | 36552767.05 | 16378.51 | 19-SEP-04:11 | 2.20 |
October | 0.157863E+09 | 23175.06 | 10-OCT-04:01 | -5.2 |
November | 0.127731E+10 | 26739.92 | 27-NOV-03:41 | -15.8 |
December | 0.356609E+10 | 27562.41 | 31-DEC-08:61 | -27.6 |
Annual Sum or Average | 0.157131E+11 | |||
Minimum of Months | 0.00 | 0.00 | -27.6 | |
Maximum of Months | 0.637183E+10 | 27759.55 | 19.45 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.536237E+10 | 23580.91 | 09-JAN-02:31 | -27.2 |
February | 0.202731E+10 | 22234.46 | 06-FEB-04:11 | -0.6 |
March | 0.102469E+10 | 22881.61 | 06-MAR-04:01 | -18.4 |
April | 0.121450E+09 | 18848.38 | 29-APR-04:01 | -7.8 |
May | 0.141689E+09 | 19594.01 | 22-MAY-04:01 | -0.1 |
June | 654883.22 | 2774.61 | 17-JUN-05:03 | 2.35 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 19.45 |
August | 289821.70 | 1932.14 | 18-AUG-05:03 | 7.30 |
September | 24316097.96 | 13239.73 | 19-SEP-04:11 | 2.20 |
October | 0.122004E+09 | 19258.18 | 10-OCT-04:01 | -5.2 |
November | 0.985915E+09 | 21760.43 | 27-NOV-04:21 | -15.7 |
December | 0.283477E+10 | 23253.96 | 31-DEC-08:61 | -27.6 |
Annual Sum or Average | 0.126455E+11 | |||
Minimum of Months | 0.00 | 0.00 | -27.6 | |
Maximum of Months | 0.536237E+10 | 23580.91 | 19.45 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.160589E+11 | 19801.96 | 09-JAN-04:01 | -27.2 |
February | 0.839900E+10 | 18529.54 | 05-FEB-00:02 | -19.9 |
March | 0.529715E+10 | 18938.38 | 05-MAR-23:21 | -16.4 |
April | 0.146555E+10 | 16537.95 | 29-APR-03:01 | -6.9 |
May | 0.115910E+10 | 17275.49 | 08-MAY-03:11 | -2.6 |
June | 30254036.91 | 14656.37 | 17-JUN-04:12 | 2.03 |
July | 2060.86 | 10.30 | 08-JUL-05:03 | 6.23 |
August | 21057357.84 | 13401.82 | 18-AUG-04:12 | 7.20 |
September | 0.399335E+09 | 15839.30 | 19-SEP-04:11 | 2.20 |
October | 0.147958E+10 | 16701.57 | 10-OCT-03:01 | -4.1 |
November | 0.562038E+10 | 18837.07 | 27-NOV-05:11 | -15.3 |
December | 0.117709E+11 | 18513.77 | 31-DEC-08:11 | -27.4 |
Annual Sum or Average | 0.517013E+11 | |||
Minimum of Months | 2060.86 | 10.30 | -27.4 | |
Maximum of Months | 0.160589E+11 | 19801.96 | 7.20 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.971572E+10 | 25429.25 | 09-JAN-04:01 | -27.2 |
February | 0.467213E+10 | 23650.73 | 05-FEB-00:02 | -19.9 |
March | 0.291744E+10 | 24183.39 | 05-MAR-23:21 | -16.4 |
April | 0.753374E+09 | 21178.14 | 29-APR-03:01 | -6.9 |
May | 0.666279E+09 | 22224.25 | 08-MAY-03:11 | -2.6 |
June | 18129317.38 | 18841.65 | 17-JUN-04:12 | 2.03 |
July | 13601.29 | 68.01 | 08-JUL-05:03 | 6.23 |
August | 12127308.98 | 10222.89 | 18-AUG-04:12 | 7.20 |
September | 0.210677E+09 | 20328.01 | 19-SEP-04:11 | 2.20 |
October | 0.778202E+09 | 21301.34 | 10-OCT-03:01 | -4.1 |
November | 0.317877E+10 | 23793.40 | 27-NOV-05:11 | -15.3 |
December | 0.702099E+10 | 23781.87 | 31-DEC-07:31 | -28.0 |
Annual Sum or Average | 0.299438E+11 | |||
Minimum of Months | 13601.29 | 68.01 | -28.0 | |
Maximum of Months | 0.971572E+10 | 25429.25 | 7.20 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.113646E+11 | 32105.65 | 09-JAN-04:01 | -27.2 |
February | 0.507273E+10 | 29877.52 | 05-FEB-00:02 | -19.9 |
March | 0.372123E+10 | 30455.95 | 05-MAR-23:21 | -16.4 |
April | 0.117755E+10 | 26866.81 | 29-APR-03:01 | -6.9 |
May | 0.114427E+10 | 28243.39 | 08-MAY-03:11 | -2.6 |
June | 58350574.39 | 24012.41 | 17-JUN-04:12 | 2.03 |
July | 764356.25 | 3486.92 | 08-JUL-05:03 | 6.23 |
August | 27551546.83 | 14481.75 | 18-AUG-04:12 | 7.20 |
September | 0.275179E+09 | 25565.44 | 19-SEP-04:11 | 2.20 |
October | 0.866386E+09 | 27147.32 | 10-OCT-03:01 | -4.1 |
November | 0.342548E+10 | 30033.40 | 27-NOV-05:11 | -15.3 |
December | 0.779858E+10 | 30182.68 | 31-DEC-08:11 | -27.4 |
Annual Sum or Average | 0.349326E+11 | |||
Minimum of Months | 764356.25 | 3486.92 | -27.4 | |
Maximum of Months | 0.113646E+11 | 32105.65 | 7.20 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.911193E+10 | 28460.14 | 09-JAN-04:01 | -27.2 |
February | 0.391664E+10 | 25998.70 | 05-FEB-00:02 | -19.9 |
March | 0.246234E+10 | 26627.74 | 05-MAR-23:21 | -16.4 |
April | 0.579325E+09 | 22880.74 | 01-APR-04:11 | 6.33 |
May | 0.532487E+09 | 24806.97 | 08-MAY-03:11 | -2.6 |
June | 19811610.61 | 16296.36 | 17-JUN-04:12 | 2.03 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 19.45 |
August | 13694807.42 | 8546.53 | 18-AUG-05:03 | 7.30 |
September | 0.163235E+09 | 22523.15 | 19-SEP-04:11 | 2.20 |
October | 0.587955E+09 | 23828.79 | 10-OCT-03:01 | -4.1 |
November | 0.246998E+10 | 26473.91 | 27-NOV-05:11 | -15.3 |
December | 0.570177E+10 | 26466.83 | 31-DEC-08:11 | -27.4 |
Annual Sum or Average | 0.255592E+11 | |||
Minimum of Months | 0.00 | 0.00 | -27.4 | |
Maximum of Months | 0.911193E+10 | 28460.14 | 19.45 |
Report: ZoneHeatingSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.210506E+10 | 12390.51 | 24-JAN-06:02 | 8.22 |
February | 0.874119E+09 | 12818.93 | 26-FEB-16:22 | 15.85 |
March | 0.348802E+09 | 11892.19 | 09-MAR-06:03 | 2.30 |
April | 0.139218E+09 | 15127.76 | 16-APR-15:31 | 19.80 |
May | 74335535.86 | 10162.65 | 01-MAY-04:01 | -0.6 |
June | 90342864.91 | 10616.78 | 18-JUN-15:22 | 24.70 |
July | 0.130746E+09 | 13630.25 | 16-JUL-15:51 | 32.80 |
August | 0.107508E+09 | 15402.30 | 06-AUG-16:01 | 35.50 |
September | 92597419.05 | 12488.04 | 03-SEP-15:41 | 34.03 |
October | 97106586.40 | 15202.98 | 15-OCT-14:51 | 22.80 |
November | 0.210368E+09 | 13031.96 | 24-NOV-05:11 | 12.20 |
December | 0.395773E+09 | 13471.44 | 04-DEC-05:01 | 1.32 |
Annual Sum or Average | 0.466597E+10 | |||
Minimum of Months | 74335535.86 | 10162.65 | -0.6 | |
Maximum of Months | 0.210506E+10 | 15402.30 | 35.50 |
Report: ZoneHeatingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.553483E+10 | 15951.19 | 09-JAN-06:11 | -27.2 |
February | 0.300316E+10 | 13125.49 | 26-FEB-14:41 | 16.52 |
March | 0.162936E+10 | 12331.88 | 26-MAR-13:32 | 9.63 |
April | 0.212343E+09 | 18500.84 | 16-APR-16:21 | 20.00 |
May | 0.447507E+09 | 9004.49 | 28-MAY-17:11 | 20.73 |
June | 72682173.04 | 14248.40 | 18-JUN-15:41 | 24.90 |
July | 0.103369E+09 | 15405.20 | 16-JUL-16:21 | 33.05 |
August | 55308319.00 | 15767.48 | 06-AUG-16:01 | 35.50 |
September | 0.102343E+09 | 15241.34 | 04-SEP-15:31 | 32.60 |
October | 0.335508E+09 | 14082.83 | 15-OCT-15:42 | 22.30 |
November | 0.149645E+10 | 11404.07 | 12-NOV-13:32 | -0.6 |
December | 0.311229E+10 | 12885.37 | 26-DEC-06:12 | -8.0 |
Annual Sum or Average | 0.161052E+11 | |||
Minimum of Months | 55308319.00 | 9004.49 | -27.2 | |
Maximum of Months | 0.553483E+10 | 18500.84 | 35.50 |
Report: ZoneHeatingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.193915E+11 | 36992.62 | 09-JAN-05:04 | -27.2 |
February | 0.103311E+11 | 31340.76 | 04-FEB-05:22 | -20.0 |
March | 0.719700E+10 | 33475.51 | 06-MAR-05:09 | -18.4 |
April | 0.271619E+10 | 15472.75 | 29-APR-05:13 | -7.6 |
May | 0.212322E+10 | 23072.91 | 08-MAY-04:13 | -2.4 |
June | 0.402283E+09 | 16265.15 | 20-JUN-05:03 | 9.68 |
July | 0.160093E+09 | 16891.30 | 12-JUL-05:03 | 6.85 |
August | 0.289374E+09 | 16289.91 | 03-AUG-05:03 | 8.12 |
September | 0.106465E+10 | 14921.24 | 27-SEP-05:03 | 8.95 |
October | 0.278701E+10 | 23898.81 | 10-OCT-04:22 | -5.5 |
November | 0.759946E+10 | 33707.18 | 27-NOV-05:31 | -15.0 |
December | 0.145189E+11 | 34491.44 | 29-DEC-06:12 | -25.2 |
Annual Sum or Average | 0.685807E+11 | |||
Minimum of Months | 0.160093E+09 | 14921.24 | -27.2 | |
Maximum of Months | 0.193915E+11 | 36992.62 | 9.68 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.108924E+09 | 659.94 | 08-JAN-22:15 | -26.7 |
February | 0.00 | 0.00 | 01-FEB-00:05 | -12.4 |
March | 0.00 | 0.00 | 01-MAR-00:10 | -3.0 |
April | 0.00 | 0.00 | 01-APR-00:10 | 2.68 |
May | 0.00 | 0.00 | 01-MAY-00:10 | -1.1 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 15.42 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 19.45 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 18.90 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 18.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 11.57 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 4.98 |
December | 0.00 | 0.00 | 01-DEC-00:10 | -2.1 |
Annual Sum or Average | 0.108924E+09 | |||
Minimum of Months | 0.00 | 0.00 | -26.7 | |
Maximum of Months | 0.108924E+09 | 659.94 | 19.45 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.678654E+09 | 682.37 | 29-JAN-18:20 | -23.3 |
February | 0.00 | 0.00 | 01-FEB-00:05 | -12.4 |
March | 0.00 | 0.00 | 01-MAR-00:10 | -3.0 |
April | 0.00 | 0.00 | 01-APR-00:10 | 2.68 |
May | 7717239.95 | 348.70 | 08-MAY-04:20 | -2.4 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 15.42 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 19.45 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 18.90 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 18.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 11.57 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 4.98 |
December | 0.00 | 0.00 | 01-DEC-00:10 | -2.1 |
Annual Sum or Average | 0.686372E+09 | |||
Minimum of Months | 0.00 | 0.00 | -23.3 | |
Maximum of Months | 0.678654E+09 | 682.37 | 19.45 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.918145E+09 | 732.67 | 29-JAN-17:40 | -21.7 |
February | 70718246.87 | 656.03 | 05-FEB-19:35 | -18.0 |
March | 0.00 | 0.00 | 01-MAR-00:10 | -3.0 |
April | 2580523.81 | 785.14 | 30-APR-23:05 | -1.3 |
May | 0.135846E+09 | 688.86 | 01-MAY-00:20 | -1.1 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 15.42 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 19.45 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 18.90 |
September | 40753706.54 | 628.88 | 19-SEP-04:23 | 2.20 |
October | 869027.25 | 477.15 | 10-OCT-01:33 | -2.9 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 4.98 |
December | 0.00 | 0.00 | 01-DEC-00:10 | -2.1 |
Annual Sum or Average | 0.116891E+10 | |||
Minimum of Months | 0.00 | 0.00 | -21.7 | |
Maximum of Months | 0.918145E+09 | 785.14 | 19.45 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 1.38 |
February | 0.00 | 0.00 | 01-FEB-00:05 | -12.4 |
March | 0.00 | 0.00 | 01-MAR-00:10 | -3.0 |
April | 0.00 | 0.00 | 01-APR-00:10 | 2.68 |
May | 0.00 | 0.00 | 01-MAY-00:10 | -1.1 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 15.42 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 19.45 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 18.90 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 18.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 11.57 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 4.98 |
December | 0.00 | 0.00 | 01-DEC-00:10 | -2.1 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | -12.4 | |
Maximum of Months | 0.00 | 0.00 | 19.45 |
Report: ZoneElectricSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.219312E+11 | 22950.34 | 02-JAN-08:09 | 0.360447E+11 | 13457.54 | 01-JAN-00:10 |
February | 0.198933E+11 | 22950.34 | 01-FEB-08:09 | 0.325565E+11 | 13457.54 | 01-FEB-00:10 |
March | 0.236388E+11 | 22950.34 | 01-MAR-08:09 | 0.360447E+11 | 13457.54 | 01-MAR-00:10 |
April | 0.211142E+11 | 22950.34 | 03-APR-07:10 | 0.348820E+11 | 13457.54 | 01-APR-00:10 |
May | 0.227850E+11 | 22950.34 | 01-MAY-07:10 | 0.360447E+11 | 13457.54 | 01-MAY-00:10 |
June | 0.226748E+11 | 22950.34 | 01-JUN-07:10 | 0.348820E+11 | 13457.54 | 01-JUN-00:10 |
July | 0.212244E+11 | 22950.34 | 03-JUL-07:10 | 0.360447E+11 | 13457.54 | 01-JUL-00:10 |
August | 0.236388E+11 | 22950.34 | 01-AUG-07:10 | 0.360447E+11 | 13457.54 | 01-AUG-00:10 |
September | 0.211142E+11 | 22950.34 | 01-SEP-07:10 | 0.348820E+11 | 13457.54 | 01-SEP-00:10 |
October | 0.219312E+11 | 22950.34 | 02-OCT-07:10 | 0.360447E+11 | 13457.54 | 01-OCT-00:10 |
November | 0.216742E+11 | 22950.34 | 01-NOV-07:10 | 0.348820E+11 | 13457.54 | 01-NOV-00:10 |
December | 0.212244E+11 | 22950.34 | 01-DEC-08:09 | 0.360447E+11 | 13457.54 | 01-DEC-00:10 |
Annual Sum or Average | 0.262844E+12 | 0.424397E+12 | ||||
Minimum of Months | 0.198933E+11 | 22950.34 | 0.325565E+11 | 13457.54 | ||
Maximum of Months | 0.236388E+11 | 22950.34 | 0.360447E+11 | 13457.54 |
Report: ZoneElectricSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.196958E+11 | 20611.01 | 02-JAN-08:09 | 0.243681E+11 | 17206.63 | 02-JAN-08:09 |
February | 0.178655E+11 | 20611.01 | 01-FEB-08:09 | 0.220609E+11 | 17206.63 | 01-FEB-08:09 |
March | 0.212293E+11 | 20611.01 | 01-MAR-08:09 | 0.253549E+11 | 17206.63 | 01-MAR-08:09 |
April | 0.189620E+11 | 20611.01 | 03-APR-07:10 | 0.235306E+11 | 17206.63 | 03-APR-07:10 |
May | 0.204625E+11 | 20611.01 | 01-MAY-07:10 | 0.248615E+11 | 17206.63 | 01-MAY-07:10 |
June | 0.203636E+11 | 20611.01 | 01-JUN-07:10 | 0.244160E+11 | 17206.63 | 01-JUN-07:10 |
July | 0.190610E+11 | 20611.01 | 03-JUL-07:10 | 0.239708E+11 | 17206.63 | 03-JUL-07:10 |
August | 0.212293E+11 | 20611.01 | 01-AUG-07:10 | 0.253549E+11 | 17206.63 | 01-AUG-07:10 |
September | 0.189620E+11 | 20611.01 | 01-SEP-07:10 | 0.235199E+11 | 17206.63 | 01-SEP-07:10 |
October | 0.196958E+11 | 20611.01 | 02-OCT-07:10 | 0.243735E+11 | 17206.63 | 02-OCT-07:10 |
November | 0.194649E+11 | 20611.01 | 01-NOV-07:10 | 0.238373E+11 | 17206.63 | 01-NOV-07:10 |
December | 0.190610E+11 | 20611.01 | 01-DEC-08:09 | 0.239654E+11 | 17206.63 | 01-DEC-08:09 |
Annual Sum or Average | 0.236053E+12 | 0.289614E+12 | ||||
Minimum of Months | 0.178655E+11 | 20611.01 | 0.220609E+11 | 17206.63 | ||
Maximum of Months | 0.212293E+11 | 20611.01 | 0.253549E+11 | 17206.63 |
Report: ZoneElectricSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.196958E+11 | 20611.01 | 02-JAN-08:09 | 0.243680E+11 | 17206.56 | 02-JAN-08:09 |
February | 0.178655E+11 | 20611.01 | 01-FEB-08:09 | 0.220609E+11 | 17206.56 | 01-FEB-08:09 |
March | 0.212293E+11 | 20611.01 | 01-MAR-08:09 | 0.253548E+11 | 17206.56 | 01-MAR-08:09 |
April | 0.189620E+11 | 20611.01 | 03-APR-07:10 | 0.235305E+11 | 17206.56 | 03-APR-07:10 |
May | 0.204625E+11 | 20611.01 | 01-MAY-07:10 | 0.248614E+11 | 17206.56 | 01-MAY-07:10 |
June | 0.203636E+11 | 20611.01 | 01-JUN-07:10 | 0.244159E+11 | 17206.56 | 01-JUN-07:10 |
July | 0.190610E+11 | 20611.01 | 03-JUL-07:10 | 0.239707E+11 | 17206.56 | 03-JUL-07:10 |
August | 0.212293E+11 | 20611.01 | 01-AUG-07:10 | 0.253548E+11 | 17206.56 | 01-AUG-07:10 |
September | 0.189620E+11 | 20611.01 | 01-SEP-07:10 | 0.235198E+11 | 17206.56 | 01-SEP-07:10 |
October | 0.196958E+11 | 20611.01 | 02-OCT-07:10 | 0.243734E+11 | 17206.56 | 02-OCT-07:10 |
November | 0.194649E+11 | 20611.01 | 01-NOV-07:10 | 0.238372E+11 | 17206.56 | 01-NOV-07:10 |
December | 0.190610E+11 | 20611.01 | 01-DEC-08:09 | 0.239653E+11 | 17206.56 | 01-DEC-08:09 |
Annual Sum or Average | 0.236053E+12 | 0.289613E+12 | ||||
Minimum of Months | 0.178655E+11 | 20611.01 | 0.220609E+11 | 17206.56 | ||
Maximum of Months | 0.212293E+11 | 20611.01 | 0.253548E+11 | 17206.56 |
Report: ZoneElectricSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.196958E+11 | 20611.01 | 02-JAN-08:09 | 0.243680E+11 | 17206.56 | 02-JAN-08:09 |
February | 0.178655E+11 | 20611.01 | 01-FEB-08:09 | 0.220609E+11 | 17206.56 | 01-FEB-08:09 |
March | 0.212293E+11 | 20611.01 | 01-MAR-08:09 | 0.253548E+11 | 17206.56 | 01-MAR-08:09 |
April | 0.189620E+11 | 20611.01 | 03-APR-07:10 | 0.235305E+11 | 17206.56 | 03-APR-07:10 |
May | 0.204625E+11 | 20611.01 | 01-MAY-07:10 | 0.248614E+11 | 17206.56 | 01-MAY-07:10 |
June | 0.203636E+11 | 20611.01 | 01-JUN-07:10 | 0.244159E+11 | 17206.56 | 01-JUN-07:10 |
July | 0.190610E+11 | 20611.01 | 03-JUL-07:10 | 0.239707E+11 | 17206.56 | 03-JUL-07:10 |
August | 0.212293E+11 | 20611.01 | 01-AUG-07:10 | 0.253548E+11 | 17206.56 | 01-AUG-07:10 |
September | 0.189620E+11 | 20611.01 | 01-SEP-07:10 | 0.235198E+11 | 17206.56 | 01-SEP-07:10 |
October | 0.196958E+11 | 20611.01 | 02-OCT-07:10 | 0.243734E+11 | 17206.56 | 02-OCT-07:10 |
November | 0.194649E+11 | 20611.01 | 01-NOV-07:10 | 0.238372E+11 | 17206.56 | 01-NOV-07:10 |
December | 0.190610E+11 | 20611.01 | 01-DEC-08:09 | 0.239653E+11 | 17206.56 | 01-DEC-08:09 |
Annual Sum or Average | 0.236053E+12 | 0.289613E+12 | ||||
Minimum of Months | 0.178655E+11 | 20611.01 | 0.220609E+11 | 17206.56 | ||
Maximum of Months | 0.212293E+11 | 20611.01 | 0.253548E+11 | 17206.56 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.174381E+10 | 2587.92 | 02-JAN-08:09 | 0.305979E+10 | 2160.55 | 02-JAN-08:09 |
February | 0.139771E+10 | 2255.20 | 01-FEB-08:09 | 0.277008E+10 | 2160.55 | 01-FEB-08:09 |
March | 0.154554E+10 | 2587.92 | 17-MAR-07:10 | 0.318369E+10 | 2160.55 | 01-MAR-08:09 |
April | 0.131532E+10 | 1922.48 | 14-APR-07:10 | 0.295462E+10 | 2160.55 | 03-APR-07:10 |
May | 0.136508E+10 | 1803.00 | 03-MAY-07:10 | 0.312174E+10 | 2160.55 | 01-MAY-07:10 |
June | 0.132347E+10 | 1350.81 | 16-JUN-07:10 | 0.306580E+10 | 2160.55 | 01-JUN-07:10 |
July | 0.126804E+10 | 1470.28 | 07-JUL-07:30 | 0.300989E+10 | 2160.55 | 03-JUL-07:10 |
August | 0.142258E+10 | 1470.28 | 17-AUG-07:10 | 0.318369E+10 | 2160.55 | 01-AUG-07:10 |
September | 0.135065E+10 | 2255.20 | 11-SEP-07:10 | 0.295328E+10 | 2160.55 | 01-SEP-07:10 |
October | 0.150063E+10 | 2587.92 | 25-OCT-07:10 | 0.306046E+10 | 2160.55 | 02-OCT-07:10 |
November | 0.163650E+10 | 2587.92 | 01-NOV-07:10 | 0.299314E+10 | 2160.55 | 01-NOV-07:10 |
December | 0.170473E+10 | 2587.92 | 01-DEC-08:09 | 0.300922E+10 | 2160.55 | 01-DEC-08:09 |
Annual Sum or Average | 0.175741E+11 | 0.363654E+11 | ||||
Minimum of Months | 0.126804E+10 | 1350.81 | 0.277008E+10 | 2160.55 | ||
Maximum of Months | 0.174381E+10 | 2587.92 | 0.318369E+10 | 2160.55 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.108190E+10 | 1667.75 | 02-JAN-08:09 | 0.197184E+10 | 1392.34 | 02-JAN-08:09 |
February | 0.881552E+09 | 1453.34 | 01-FEB-16:00 | 0.178515E+10 | 1392.34 | 01-FEB-08:09 |
March | 0.984042E+09 | 1667.75 | 17-MAR-07:10 | 0.205169E+10 | 1392.34 | 01-MAR-08:09 |
April | 0.843269E+09 | 1161.92 | 14-APR-07:10 | 0.190407E+10 | 1392.34 | 03-APR-07:10 |
May | 0.881907E+09 | 947.51 | 03-MAY-07:10 | 0.201177E+10 | 1392.34 | 01-MAY-07:10 |
June | 0.860755E+09 | 793.52 | 01-JUN-07:10 | 0.197572E+10 | 1392.34 | 01-JUN-07:10 |
July | 0.819192E+09 | 870.51 | 07-JUL-07:19 | 0.193969E+10 | 1392.34 | 03-JUL-07:10 |
August | 0.920811E+09 | 870.51 | 17-AUG-07:10 | 0.205169E+10 | 1392.34 | 01-AUG-07:10 |
September | 0.863747E+09 | 1161.92 | 13-SEP-07:10 | 0.190321E+10 | 1392.34 | 01-SEP-07:10 |
October | 0.943330E+09 | 1667.75 | 25-OCT-07:10 | 0.197228E+10 | 1392.34 | 02-OCT-07:10 |
November | 0.102538E+10 | 1667.75 | 01-NOV-07:10 | 0.192889E+10 | 1392.34 | 01-NOV-07:10 |
December | 0.105698E+10 | 1667.75 | 01-DEC-08:09 | 0.193926E+10 | 1392.34 | 01-DEC-08:09 |
Annual Sum or Average | 0.111629E+11 | 0.234352E+11 | ||||
Minimum of Months | 0.819192E+09 | 793.52 | 0.178515E+10 | 1392.34 | ||
Maximum of Months | 0.108190E+10 | 1667.75 | 0.205169E+10 | 1392.34 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.164382E+10 | 2587.98 | 02-JAN-08:09 | 0.305983E+10 | 2160.58 | 02-JAN-08:09 |
February | 0.133999E+10 | 2255.25 | 02-FEB-08:09 | 0.277013E+10 | 2160.58 | 01-FEB-08:09 |
March | 0.152355E+10 | 2587.98 | 17-MAR-07:10 | 0.318374E+10 | 2160.58 | 01-MAR-08:09 |
April | 0.131605E+10 | 1922.52 | 14-APR-07:10 | 0.295467E+10 | 2160.58 | 03-APR-07:10 |
May | 0.137335E+10 | 1803.04 | 03-MAY-07:10 | 0.312179E+10 | 2160.58 | 01-MAY-07:10 |
June | 0.133953E+10 | 1350.84 | 16-JUN-07:10 | 0.306585E+10 | 2160.58 | 01-JUN-07:10 |
July | 0.127798E+10 | 1470.31 | 07-JUL-07:30 | 0.300994E+10 | 2160.58 | 03-JUL-07:10 |
August | 0.143269E+10 | 1470.31 | 17-AUG-07:10 | 0.318374E+10 | 2160.58 | 01-AUG-07:10 |
September | 0.134306E+10 | 1803.04 | 11-SEP-07:10 | 0.295333E+10 | 2160.58 | 01-SEP-07:10 |
October | 0.145065E+10 | 2587.98 | 25-OCT-07:10 | 0.306051E+10 | 2160.58 | 02-OCT-07:10 |
November | 0.154327E+10 | 2587.98 | 01-NOV-07:10 | 0.299318E+10 | 2160.58 | 01-NOV-07:10 |
December | 0.158769E+10 | 2587.98 | 01-DEC-08:09 | 0.300927E+10 | 2160.58 | 01-DEC-08:09 |
Annual Sum or Average | 0.171716E+11 | 0.363660E+11 | ||||
Minimum of Months | 0.127798E+10 | 1350.84 | 0.277013E+10 | 2160.58 | ||
Maximum of Months | 0.164382E+10 | 2587.98 | 0.318374E+10 | 2160.58 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.109494E+10 | 1667.75 | 02-JAN-08:09 | 0.197183E+10 | 1392.33 | 02-JAN-08:09 |
February | 0.881197E+09 | 1667.75 | 02-FEB-08:09 | 0.178514E+10 | 1392.33 | 01-FEB-08:09 |
March | 0.991184E+09 | 1667.75 | 17-MAR-07:10 | 0.205168E+10 | 1392.33 | 01-MAR-08:09 |
April | 0.850687E+09 | 1453.34 | 14-APR-07:10 | 0.190406E+10 | 1392.33 | 03-APR-07:10 |
May | 0.882212E+09 | 1161.92 | 03-MAY-07:10 | 0.201175E+10 | 1392.33 | 01-MAY-07:10 |
June | 0.855951E+09 | 870.51 | 01-JUN-07:10 | 0.197570E+10 | 1392.33 | 01-JUN-07:10 |
July | 0.820794E+09 | 947.51 | 07-JUL-07:10 | 0.193968E+10 | 1392.33 | 03-JUL-07:10 |
August | 0.919730E+09 | 1161.92 | 17-AUG-07:10 | 0.205168E+10 | 1392.33 | 01-AUG-07:10 |
September | 0.869326E+09 | 1453.34 | 11-SEP-07:10 | 0.190319E+10 | 1392.33 | 01-SEP-07:10 |
October | 0.956001E+09 | 1667.75 | 25-OCT-07:10 | 0.197226E+10 | 1392.33 | 02-OCT-07:10 |
November | 0.101877E+10 | 1667.75 | 01-NOV-07:10 | 0.192888E+10 | 1392.33 | 01-NOV-07:10 |
December | 0.105701E+10 | 1667.75 | 01-DEC-08:09 | 0.193924E+10 | 1392.33 | 01-DEC-08:09 |
Annual Sum or Average | 0.111978E+11 | 0.234351E+11 | ||||
Minimum of Months | 0.820794E+09 | 870.51 | 0.178514E+10 | 1392.33 | ||
Maximum of Months | 0.109494E+10 | 1667.75 | 0.205168E+10 | 1392.33 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.173790E+10 | 2587.92 | 02-JAN-08:09 | 0.305979E+10 | 2160.55 | 02-JAN-08:09 |
February | 0.139282E+10 | 2255.20 | 01-FEB-08:09 | 0.277008E+10 | 2160.55 | 01-FEB-08:09 |
March | 0.154262E+10 | 2587.92 | 17-MAR-07:10 | 0.318369E+10 | 2160.55 | 01-MAR-08:09 |
April | 0.131304E+10 | 1803.00 | 14-APR-07:10 | 0.295462E+10 | 2160.55 | 03-APR-07:10 |
May | 0.136393E+10 | 1803.00 | 03-MAY-07:10 | 0.312174E+10 | 2160.55 | 01-MAY-07:10 |
June | 0.132282E+10 | 1350.81 | 26-JUN-11:30 | 0.306580E+10 | 2160.55 | 01-JUN-07:10 |
July | 0.126757E+10 | 1470.28 | 07-JUL-07:30 | 0.300989E+10 | 2160.55 | 03-JUL-07:10 |
August | 0.142176E+10 | 1470.28 | 17-AUG-07:10 | 0.318369E+10 | 2160.55 | 01-AUG-07:10 |
September | 0.134796E+10 | 2135.72 | 11-SEP-07:10 | 0.295328E+10 | 2160.55 | 01-SEP-07:10 |
October | 0.149665E+10 | 2587.92 | 25-OCT-07:10 | 0.306046E+10 | 2160.55 | 02-OCT-07:10 |
November | 0.163103E+10 | 2587.92 | 01-NOV-07:10 | 0.299314E+10 | 2160.55 | 01-NOV-07:10 |
December | 0.169690E+10 | 2587.92 | 01-DEC-08:09 | 0.300922E+10 | 2160.55 | 01-DEC-08:09 |
Annual Sum or Average | 0.175350E+11 | 0.363654E+11 | ||||
Minimum of Months | 0.126757E+10 | 1350.81 | 0.277008E+10 | 2160.55 | ||
Maximum of Months | 0.173790E+10 | 2587.92 | 0.318369E+10 | 2160.55 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.108005E+10 | 1667.75 | 02-JAN-08:09 | 0.197184E+10 | 1392.34 | 02-JAN-08:09 |
February | 0.880010E+09 | 1453.34 | 01-FEB-16:00 | 0.178515E+10 | 1392.34 | 01-FEB-08:09 |
March | 0.983117E+09 | 1667.75 | 17-MAR-07:10 | 0.205169E+10 | 1392.34 | 01-MAR-08:09 |
April | 0.842267E+09 | 1161.92 | 14-APR-07:10 | 0.190407E+10 | 1392.34 | 03-APR-07:10 |
May | 0.881149E+09 | 947.51 | 03-MAY-07:10 | 0.201177E+10 | 1392.34 | 01-MAY-07:10 |
June | 0.860164E+09 | 793.52 | 01-JUN-07:10 | 0.197572E+10 | 1392.34 | 01-JUN-07:10 |
July | 0.818786E+09 | 870.51 | 07-JUL-07:19 | 0.193969E+10 | 1392.34 | 03-JUL-07:10 |
August | 0.920152E+09 | 870.51 | 17-AUG-07:10 | 0.205169E+10 | 1392.34 | 01-AUG-07:10 |
September | 0.863092E+09 | 1161.92 | 13-SEP-07:10 | 0.190321E+10 | 1392.34 | 01-SEP-07:10 |
October | 0.941851E+09 | 1667.75 | 25-OCT-07:10 | 0.197228E+10 | 1392.34 | 02-OCT-07:10 |
November | 0.102332E+10 | 1667.75 | 01-NOV-07:10 | 0.192889E+10 | 1392.34 | 01-NOV-07:10 |
December | 0.105379E+10 | 1667.75 | 01-DEC-08:09 | 0.193926E+10 | 1392.34 | 01-DEC-08:09 |
Annual Sum or Average | 0.111478E+11 | 0.234352E+11 | ||||
Minimum of Months | 0.818786E+09 | 793.52 | 0.178515E+10 | 1392.34 | ||
Maximum of Months | 0.108005E+10 | 1667.75 | 0.205169E+10 | 1392.34 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.164230E+10 | 2587.98 | 02-JAN-08:09 | 0.305983E+10 | 2160.58 | 02-JAN-08:09 |
February | 0.133845E+10 | 2135.77 | 02-FEB-08:09 | 0.277013E+10 | 2160.58 | 01-FEB-08:09 |
March | 0.152209E+10 | 2587.98 | 17-MAR-07:10 | 0.318374E+10 | 2160.58 | 01-MAR-08:09 |
April | 0.131450E+10 | 1803.04 | 14-APR-07:10 | 0.295467E+10 | 2160.58 | 03-APR-07:10 |
May | 0.137194E+10 | 1803.04 | 03-MAY-07:10 | 0.312179E+10 | 2160.58 | 01-MAY-07:10 |
June | 0.133817E+10 | 1350.84 | 16-JUN-07:10 | 0.306585E+10 | 2160.58 | 01-JUN-07:10 |
July | 0.127704E+10 | 1470.31 | 07-JUL-07:30 | 0.300994E+10 | 2160.58 | 03-JUL-07:10 |
August | 0.143133E+10 | 1470.31 | 17-AUG-07:10 | 0.318374E+10 | 2160.58 | 01-AUG-07:10 |
September | 0.134179E+10 | 1803.04 | 11-SEP-07:10 | 0.295333E+10 | 2160.58 | 01-SEP-07:10 |
October | 0.144782E+10 | 2587.98 | 25-OCT-07:10 | 0.306051E+10 | 2160.58 | 02-OCT-07:10 |
November | 0.154216E+10 | 2587.98 | 01-NOV-07:10 | 0.299318E+10 | 2160.58 | 01-NOV-07:10 |
December | 0.158618E+10 | 2587.98 | 01-DEC-08:09 | 0.300927E+10 | 2160.58 | 01-DEC-08:09 |
Annual Sum or Average | 0.171538E+11 | 0.363660E+11 | ||||
Minimum of Months | 0.127704E+10 | 1350.84 | 0.277013E+10 | 2160.58 | ||
Maximum of Months | 0.164230E+10 | 2587.98 | 0.318374E+10 | 2160.58 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.109244E+10 | 1667.75 | 02-JAN-08:09 | 0.197183E+10 | 1392.33 | 02-JAN-08:09 |
February | 0.879043E+09 | 1667.75 | 02-FEB-08:09 | 0.178514E+10 | 1392.33 | 01-FEB-08:09 |
March | 0.989598E+09 | 1667.75 | 17-MAR-07:10 | 0.205168E+10 | 1392.33 | 01-MAR-08:09 |
April | 0.849759E+09 | 1453.34 | 14-APR-07:10 | 0.190406E+10 | 1392.33 | 03-APR-07:10 |
May | 0.881584E+09 | 1161.92 | 03-MAY-07:10 | 0.201175E+10 | 1392.33 | 01-MAY-07:10 |
June | 0.855318E+09 | 870.51 | 01-JUN-07:10 | 0.197570E+10 | 1392.33 | 01-JUN-07:10 |
July | 0.820198E+09 | 947.51 | 07-JUL-07:19 | 0.193968E+10 | 1392.33 | 03-JUL-07:10 |
August | 0.919058E+09 | 1161.92 | 17-AUG-07:10 | 0.205168E+10 | 1392.33 | 01-AUG-07:10 |
September | 0.867819E+09 | 1453.34 | 11-SEP-07:10 | 0.190319E+10 | 1392.33 | 01-SEP-07:10 |
October | 0.953826E+09 | 1667.75 | 25-OCT-07:10 | 0.197226E+10 | 1392.33 | 02-OCT-07:10 |
November | 0.101719E+10 | 1667.75 | 01-NOV-07:10 | 0.192888E+10 | 1392.33 | 01-NOV-07:10 |
December | 0.105466E+10 | 1667.75 | 01-DEC-08:09 | 0.193924E+10 | 1392.33 | 01-DEC-08:09 |
Annual Sum or Average | 0.111805E+11 | 0.234351E+11 | ||||
Minimum of Months | 0.820198E+09 | 870.51 | 0.178514E+10 | 1392.33 | ||
Maximum of Months | 0.109244E+10 | 1667.75 | 0.205168E+10 | 1392.33 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.173741E+10 | 2587.92 | 02-JAN-08:09 | 0.305979E+10 | 2160.55 | 02-JAN-08:09 |
February | 0.139270E+10 | 2255.20 | 01-FEB-08:09 | 0.277008E+10 | 2160.55 | 01-FEB-08:09 |
March | 0.154243E+10 | 2587.92 | 17-MAR-07:10 | 0.318369E+10 | 2160.55 | 01-MAR-08:09 |
April | 0.131285E+10 | 1803.00 | 14-APR-07:10 | 0.295462E+10 | 2160.55 | 03-APR-07:10 |
May | 0.136379E+10 | 1803.00 | 03-MAY-07:10 | 0.312174E+10 | 2160.55 | 01-MAY-07:10 |
June | 0.132280E+10 | 1350.81 | 26-JUN-11:30 | 0.306580E+10 | 2160.55 | 01-JUN-07:10 |
July | 0.126753E+10 | 1470.28 | 07-JUL-07:30 | 0.300989E+10 | 2160.55 | 03-JUL-07:10 |
August | 0.142174E+10 | 1470.28 | 17-AUG-07:10 | 0.318369E+10 | 2160.55 | 01-AUG-07:10 |
September | 0.134791E+10 | 2135.72 | 11-SEP-07:10 | 0.295328E+10 | 2160.55 | 01-SEP-07:10 |
October | 0.149638E+10 | 2587.92 | 25-OCT-07:10 | 0.306046E+10 | 2160.55 | 02-OCT-07:10 |
November | 0.163094E+10 | 2587.92 | 01-NOV-07:10 | 0.299314E+10 | 2160.55 | 01-NOV-07:10 |
December | 0.169650E+10 | 2587.92 | 01-DEC-08:09 | 0.300922E+10 | 2160.55 | 01-DEC-08:09 |
Annual Sum or Average | 0.175330E+11 | 0.363654E+11 | ||||
Minimum of Months | 0.126753E+10 | 1350.81 | 0.277008E+10 | 2160.55 | ||
Maximum of Months | 0.173741E+10 | 2587.92 | 0.318369E+10 | 2160.55 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.108005E+10 | 1667.75 | 02-JAN-08:09 | 0.197184E+10 | 1392.34 | 02-JAN-08:09 |
February | 0.879921E+09 | 1453.34 | 01-FEB-16:00 | 0.178515E+10 | 1392.34 | 01-FEB-08:09 |
March | 0.983000E+09 | 1667.75 | 17-MAR-07:10 | 0.205169E+10 | 1392.34 | 01-MAR-08:09 |
April | 0.842267E+09 | 1161.92 | 14-APR-07:10 | 0.190407E+10 | 1392.34 | 03-APR-07:10 |
May | 0.881111E+09 | 947.51 | 03-MAY-07:10 | 0.201177E+10 | 1392.34 | 01-MAY-07:10 |
June | 0.860144E+09 | 793.52 | 01-JUN-07:10 | 0.197572E+10 | 1392.34 | 01-JUN-07:10 |
July | 0.818786E+09 | 870.51 | 07-JUL-07:19 | 0.193969E+10 | 1392.34 | 03-JUL-07:10 |
August | 0.920121E+09 | 870.51 | 17-AUG-07:10 | 0.205169E+10 | 1392.34 | 01-AUG-07:10 |
September | 0.863067E+09 | 1161.92 | 13-SEP-07:10 | 0.190321E+10 | 1392.34 | 01-SEP-07:10 |
October | 0.942030E+09 | 1667.75 | 25-OCT-07:10 | 0.197228E+10 | 1392.34 | 02-OCT-07:10 |
November | 0.102372E+10 | 1667.75 | 01-NOV-07:10 | 0.192889E+10 | 1392.34 | 01-NOV-07:10 |
December | 0.105379E+10 | 1667.75 | 01-DEC-08:09 | 0.193926E+10 | 1392.34 | 01-DEC-08:09 |
Annual Sum or Average | 0.111480E+11 | 0.234352E+11 | ||||
Minimum of Months | 0.818786E+09 | 793.52 | 0.178515E+10 | 1392.34 | ||
Maximum of Months | 0.108005E+10 | 1667.75 | 0.205169E+10 | 1392.34 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.164223E+10 | 2587.98 | 02-JAN-08:09 | 0.305983E+10 | 2160.58 | 02-JAN-08:09 |
February | 0.133845E+10 | 2135.77 | 02-FEB-08:09 | 0.277013E+10 | 2160.58 | 01-FEB-08:09 |
March | 0.152206E+10 | 2587.98 | 17-MAR-07:10 | 0.318374E+10 | 2160.58 | 01-MAR-08:09 |
April | 0.131444E+10 | 1803.04 | 14-APR-07:10 | 0.295467E+10 | 2160.58 | 03-APR-07:10 |
May | 0.137194E+10 | 1803.04 | 03-MAY-07:10 | 0.312179E+10 | 2160.58 | 01-MAY-07:10 |
June | 0.133817E+10 | 1350.84 | 16-JUN-07:10 | 0.306585E+10 | 2160.58 | 01-JUN-07:10 |
July | 0.127701E+10 | 1470.31 | 07-JUL-07:30 | 0.300994E+10 | 2160.58 | 03-JUL-07:10 |
August | 0.143131E+10 | 1470.31 | 17-AUG-07:10 | 0.318374E+10 | 2160.58 | 01-AUG-07:10 |
September | 0.134174E+10 | 1803.04 | 11-SEP-07:10 | 0.295333E+10 | 2160.58 | 01-SEP-07:10 |
October | 0.144782E+10 | 2587.98 | 25-OCT-07:10 | 0.306051E+10 | 2160.58 | 02-OCT-07:10 |
November | 0.154216E+10 | 2587.98 | 01-NOV-07:10 | 0.299318E+10 | 2160.58 | 01-NOV-07:10 |
December | 0.158598E+10 | 2587.98 | 01-DEC-08:09 | 0.300927E+10 | 2160.58 | 01-DEC-08:09 |
Annual Sum or Average | 0.171533E+11 | 0.363660E+11 | ||||
Minimum of Months | 0.127701E+10 | 1350.84 | 0.277013E+10 | 2160.58 | ||
Maximum of Months | 0.164223E+10 | 2587.98 | 0.318374E+10 | 2160.58 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.109232E+10 | 1667.75 | 02-JAN-08:09 | 0.197183E+10 | 1392.33 | 02-JAN-08:09 |
February | 0.878986E+09 | 1667.75 | 02-FEB-08:09 | 0.178514E+10 | 1392.33 | 01-FEB-08:09 |
March | 0.989552E+09 | 1667.75 | 17-MAR-07:10 | 0.205168E+10 | 1392.33 | 01-MAR-08:09 |
April | 0.849759E+09 | 1453.34 | 14-APR-07:10 | 0.190406E+10 | 1392.33 | 03-APR-07:10 |
May | 0.881564E+09 | 1161.92 | 03-MAY-07:10 | 0.201175E+10 | 1392.33 | 01-MAY-07:10 |
June | 0.855305E+09 | 870.51 | 01-JUN-07:10 | 0.197570E+10 | 1392.33 | 01-JUN-07:10 |
July | 0.820186E+09 | 947.51 | 07-JUL-07:19 | 0.193968E+10 | 1392.33 | 03-JUL-07:10 |
August | 0.919058E+09 | 1161.92 | 17-AUG-07:10 | 0.205168E+10 | 1392.33 | 01-AUG-07:10 |
September | 0.867727E+09 | 1453.34 | 11-SEP-07:10 | 0.190319E+10 | 1392.33 | 01-SEP-07:10 |
October | 0.953817E+09 | 1667.75 | 25-OCT-07:10 | 0.197226E+10 | 1392.33 | 02-OCT-07:10 |
November | 0.101714E+10 | 1667.75 | 01-NOV-07:10 | 0.192888E+10 | 1392.33 | 01-NOV-07:10 |
December | 0.105461E+10 | 1667.75 | 01-DEC-08:09 | 0.193924E+10 | 1392.33 | 01-DEC-08:09 |
Annual Sum or Average | 0.111800E+11 | 0.234351E+11 | ||||
Minimum of Months | 0.820186E+09 | 870.51 | 0.178514E+10 | 1392.33 | ||
Maximum of Months | 0.109232E+10 | 1667.75 | 0.205168E+10 | 1392.33 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.553024E+09 | 578.72 | 02-JAN-08:09 | 0.521915E+10 | 1948.61 | 01-JAN-00:10 |
February | 0.501634E+09 | 578.72 | 01-FEB-08:09 | 0.942813E+10 | 3897.21 | 01-FEB-00:10 |
March | 0.596080E+09 | 578.72 | 01-MAR-08:09 | 0.156645E+11 | 7794.42 | 31-MAR-23:10 |
April | 0.532421E+09 | 578.72 | 03-APR-07:10 | 0.201821E+11 | 7794.42 | 01-APR-00:10 |
May | 0.574552E+09 | 578.72 | 01-MAY-07:10 | 0.522616E+10 | 3897.21 | 31-MAY-23:10 |
June | 0.571774E+09 | 578.72 | 01-JUN-07:10 | 0.101086E+11 | 5845.82 | 30-JUN-23:10 |
July | 0.535199E+09 | 578.72 | 03-JUL-07:10 | 0.156645E+11 | 7794.42 | 31-JUL-23:10 |
August | 0.596080E+09 | 578.72 | 01-AUG-07:10 | 0.208555E+11 | 7794.42 | 01-AUG-00:10 |
September | 0.532421E+09 | 578.72 | 01-SEP-07:10 | 0.505780E+10 | 3897.21 | 30-SEP-23:10 |
October | 0.553024E+09 | 578.72 | 02-OCT-07:10 | 0.104453E+11 | 5845.82 | 31-OCT-23:10 |
November | 0.546542E+09 | 578.72 | 01-NOV-07:10 | 0.151524E+11 | 5845.82 | 01-NOV-00:10 |
December | 0.535199E+09 | 578.72 | 01-DEC-08:09 | 0.208766E+11 | 7794.42 | 01-DEC-00:10 |
Annual Sum or Average | 0.662795E+10 | 0.153881E+12 | ||||
Minimum of Months | 0.501634E+09 | 578.72 | 0.505780E+10 | 1948.61 | ||
Maximum of Months | 0.596080E+09 | 578.72 | 0.208766E+11 | 7794.42 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.553024E+09 | 578.72 | 02-JAN-08:09 | 0.521915E+10 | 1948.61 | 01-JAN-00:10 |
February | 0.501634E+09 | 578.72 | 01-FEB-08:09 | 0.942813E+10 | 3897.21 | 01-FEB-00:10 |
March | 0.596080E+09 | 578.72 | 01-MAR-08:09 | 0.156645E+11 | 7794.42 | 31-MAR-23:10 |
April | 0.532421E+09 | 578.72 | 03-APR-07:10 | 0.201821E+11 | 7794.42 | 01-APR-00:10 |
May | 0.574552E+09 | 578.72 | 01-MAY-07:10 | 0.522616E+10 | 3897.21 | 31-MAY-23:10 |
June | 0.571774E+09 | 578.72 | 01-JUN-07:10 | 0.101086E+11 | 5845.82 | 30-JUN-23:10 |
July | 0.535199E+09 | 578.72 | 03-JUL-07:10 | 0.156645E+11 | 7794.42 | 31-JUL-23:10 |
August | 0.596080E+09 | 578.72 | 01-AUG-07:10 | 0.208555E+11 | 7794.42 | 01-AUG-00:10 |
September | 0.532421E+09 | 578.72 | 01-SEP-07:10 | 0.505780E+10 | 3897.21 | 30-SEP-23:10 |
October | 0.553024E+09 | 578.72 | 02-OCT-07:10 | 0.104453E+11 | 5845.82 | 31-OCT-23:10 |
November | 0.546542E+09 | 578.72 | 01-NOV-07:10 | 0.151524E+11 | 5845.82 | 01-NOV-00:10 |
December | 0.535199E+09 | 578.72 | 01-DEC-08:09 | 0.208766E+11 | 7794.42 | 01-DEC-00:10 |
Annual Sum or Average | 0.662795E+10 | 0.153881E+12 | ||||
Minimum of Months | 0.501634E+09 | 578.72 | 0.505780E+10 | 1948.61 | ||
Maximum of Months | 0.596080E+09 | 578.72 | 0.208766E+11 | 7794.42 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.553024E+09 | 578.72 | 02-JAN-08:09 | 0.521915E+10 | 1948.61 | 01-JAN-00:10 |
February | 0.501634E+09 | 578.72 | 01-FEB-08:09 | 0.942813E+10 | 3897.21 | 01-FEB-00:10 |
March | 0.596080E+09 | 578.72 | 01-MAR-08:09 | 0.156645E+11 | 7794.42 | 31-MAR-23:10 |
April | 0.532421E+09 | 578.72 | 03-APR-07:10 | 0.201821E+11 | 7794.42 | 01-APR-00:10 |
May | 0.574552E+09 | 578.72 | 01-MAY-07:10 | 0.522616E+10 | 3897.21 | 31-MAY-23:10 |
June | 0.571774E+09 | 578.72 | 01-JUN-07:10 | 0.101086E+11 | 5845.82 | 30-JUN-23:10 |
July | 0.535199E+09 | 578.72 | 03-JUL-07:10 | 0.156645E+11 | 7794.42 | 31-JUL-23:10 |
August | 0.596080E+09 | 578.72 | 01-AUG-07:10 | 0.208555E+11 | 7794.42 | 01-AUG-00:10 |
September | 0.532421E+09 | 578.72 | 01-SEP-07:10 | 0.505780E+10 | 3897.21 | 30-SEP-23:10 |
October | 0.553024E+09 | 578.72 | 02-OCT-07:10 | 0.104453E+11 | 5845.82 | 31-OCT-23:10 |
November | 0.546542E+09 | 578.72 | 01-NOV-07:10 | 0.151524E+11 | 5845.82 | 01-NOV-00:10 |
December | 0.535199E+09 | 578.72 | 01-DEC-08:09 | 0.208766E+11 | 7794.42 | 01-DEC-00:10 |
Annual Sum or Average | 0.662795E+10 | 0.153881E+12 | ||||
Minimum of Months | 0.501634E+09 | 578.72 | 0.505780E+10 | 1948.61 | ||
Maximum of Months | 0.596080E+09 | 578.72 | 0.208766E+11 | 7794.42 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.618367E+10 | 6471.01 | 02-JAN-08:09 | 0.254202E+12 | 94908.13 | 01-JAN-00:10 |
February | 0.560905E+10 | 6471.01 | 01-FEB-08:09 | 0.459203E+12 | 189816.26 | 01-FEB-00:10 |
March | 0.666512E+10 | 6471.01 | 01-MAR-08:09 | 0.762947E+12 | 379632.52 | 31-MAR-23:10 |
April | 0.595330E+10 | 6471.01 | 03-APR-07:10 | 0.982982E+12 | 379632.52 | 01-APR-00:10 |
May | 0.642439E+10 | 6471.01 | 01-MAY-07:10 | 0.254544E+12 | 189816.26 | 31-MAY-23:10 |
June | 0.639333E+10 | 6471.01 | 01-JUN-07:10 | 0.492345E+12 | 284724.39 | 30-JUN-23:10 |
July | 0.598436E+10 | 6471.01 | 03-JUL-07:10 | 0.762947E+12 | 379632.52 | 31-JUL-23:10 |
August | 0.666512E+10 | 6471.01 | 01-AUG-07:10 | 0.101578E+13 | 379632.52 | 01-AUG-00:10 |
September | 0.595330E+10 | 6471.01 | 01-SEP-07:10 | 0.246344E+12 | 189816.26 | 30-SEP-23:10 |
October | 0.618367E+10 | 6471.01 | 02-OCT-07:10 | 0.508746E+12 | 284724.39 | 31-OCT-23:10 |
November | 0.611120E+10 | 6471.01 | 01-NOV-07:10 | 0.738006E+12 | 284724.39 | 01-NOV-00:10 |
December | 0.598436E+10 | 6471.01 | 01-DEC-08:09 | 0.101681E+13 | 379632.52 | 01-DEC-00:10 |
Annual Sum or Average | 0.741109E+11 | 0.749486E+13 | ||||
Minimum of Months | 0.560905E+10 | 6471.01 | 0.246344E+12 | 94908.13 | ||
Maximum of Months | 0.666512E+10 | 6471.01 | 0.101681E+13 | 379632.52 |
Report: SpaceGainsMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.133902E+11 | 0.219312E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.121482E+11 | 0.198933E+11 | 0.325565E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.145160E+11 | 0.236388E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.128805E+11 | 0.211142E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.139531E+11 | 0.227850E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.139143E+11 | 0.226748E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.129193E+11 | 0.212244E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.145160E+11 | 0.236388E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.128805E+11 | 0.211142E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.133902E+11 | 0.219312E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.132595E+11 | 0.216742E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.129193E+11 | 0.212244E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.160687E+12 | 0.262844E+12 | 0.424397E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.121482E+11 | 0.198933E+11 | 0.325565E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.145160E+11 | 0.236388E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.120254E+11 | 0.196958E+11 | 0.243681E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.109099E+11 | 0.178655E+11 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.130364E+11 | 0.212293E+11 | 0.253549E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.115676E+11 | 0.189620E+11 | 0.235306E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.125309E+11 | 0.204625E+11 | 0.248615E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.124961E+11 | 0.203636E+11 | 0.244160E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.116025E+11 | 0.190610E+11 | 0.239708E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.130364E+11 | 0.212293E+11 | 0.253549E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.115676E+11 | 0.189620E+11 | 0.235199E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.120254E+11 | 0.196958E+11 | 0.243735E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.119080E+11 | 0.194649E+11 | 0.238373E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.116025E+11 | 0.190610E+11 | 0.239654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.144308E+12 | 0.236053E+12 | 0.289614E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.109099E+11 | 0.178655E+11 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.130364E+11 | 0.212293E+11 | 0.253549E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.120254E+11 | 0.196958E+11 | 0.243680E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.109099E+11 | 0.178655E+11 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.130364E+11 | 0.212293E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.115676E+11 | 0.189620E+11 | 0.235305E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.125309E+11 | 0.204625E+11 | 0.248614E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.124961E+11 | 0.203636E+11 | 0.244159E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.116025E+11 | 0.190610E+11 | 0.239707E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.130364E+11 | 0.212293E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.115676E+11 | 0.189620E+11 | 0.235198E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.120254E+11 | 0.196958E+11 | 0.243734E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.119080E+11 | 0.194649E+11 | 0.238372E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.116025E+11 | 0.190610E+11 | 0.239653E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.144308E+12 | 0.236053E+12 | 0.289613E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.109099E+11 | 0.178655E+11 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.130364E+11 | 0.212293E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.120254E+11 | 0.196958E+11 | 0.243680E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.109099E+11 | 0.178655E+11 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.130364E+11 | 0.212293E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.115676E+11 | 0.189620E+11 | 0.235305E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.125309E+11 | 0.204625E+11 | 0.248614E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.124961E+11 | 0.203636E+11 | 0.244159E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.116025E+11 | 0.190610E+11 | 0.239707E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.130364E+11 | 0.212293E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.115676E+11 | 0.189620E+11 | 0.235198E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.120254E+11 | 0.196958E+11 | 0.243734E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.119080E+11 | 0.194649E+11 | 0.238372E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.116025E+11 | 0.190610E+11 | 0.239653E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.144308E+12 | 0.236053E+12 | 0.289613E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.109099E+11 | 0.178655E+11 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.130364E+11 | 0.212293E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150991E+10 | 0.174381E+10 | 0.305979E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.152115E+10 |
February | 0.136985E+10 | 0.139771E+10 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.121678E+10 |
March | 0.163685E+10 | 0.154554E+10 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.111191E+10 |
April | 0.145243E+10 | 0.131532E+10 | 0.295462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.810825E+09 |
May | 0.157338E+10 | 0.136508E+10 | 0.312174E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1818243.10 | 0.792763E+09 |
June | 0.156900E+10 | 0.132347E+10 | 0.306580E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9193449.60 | 0.396230E+09 |
July | 0.145680E+10 | 0.126804E+10 | 0.300989E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 30659230.45 | 0.263424E+09 |
August | 0.163685E+10 | 0.142258E+10 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 26676437.67 | 0.288309E+09 |
September | 0.145243E+10 | 0.135065E+10 | 0.295328E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16542544.96 | 0.522603E+09 |
October | 0.150991E+10 | 0.150063E+10 | 0.306046E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 108355.94 | 0.786286E+09 |
November | 0.149516E+10 | 0.163650E+10 | 0.299314E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.111126E+10 |
December | 0.145680E+10 | 0.170473E+10 | 0.300922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.140923E+10 |
Annual Sum or Average | 0.181194E+11 | 0.175741E+11 | 0.363654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 84998261.72 | 0.102308E+11 |
Minimum of Months | 0.136985E+10 | 0.126804E+10 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.263424E+09 |
Maximum of Months | 0.163685E+10 | 0.174381E+10 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 30659230.45 | 0.152115E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.108190E+10 | 0.197184E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.101373E+10 |
February | 0.882782E+09 | 0.881552E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.812265E+09 |
March | 0.105485E+10 | 0.984042E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.733211E+09 |
April | 0.936002E+09 | 0.843269E+09 | 0.190407E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.531006E+09 |
May | 0.101394E+10 | 0.881907E+09 | 0.201177E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1315871.88 | 0.518282E+09 |
June | 0.101113E+10 | 0.860755E+09 | 0.197572E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6383166.77 | 0.258689E+09 |
July | 0.938820E+09 | 0.819192E+09 | 0.193969E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21310335.14 | 0.167363E+09 |
August | 0.105485E+10 | 0.920811E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18339200.58 | 0.180060E+09 |
September | 0.936002E+09 | 0.863747E+09 | 0.190321E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11319925.98 | 0.346211E+09 |
October | 0.973041E+09 | 0.943330E+09 | 0.197228E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 72233.76 | 0.520469E+09 |
November | 0.963541E+09 | 0.102538E+10 | 0.192889E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.725637E+09 |
December | 0.938820E+09 | 0.105698E+10 | 0.193926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.922594E+09 |
Annual Sum or Average | 0.116768E+11 | 0.111629E+11 | 0.234352E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 58740734.11 | 0.672951E+10 |
Minimum of Months | 0.882782E+09 | 0.819192E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.167363E+09 |
Maximum of Months | 0.105485E+10 | 0.108190E+10 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21310335.14 | 0.101373E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150994E+10 | 0.164382E+10 | 0.305983E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.153900E+10 |
February | 0.136988E+10 | 0.133999E+10 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.125591E+10 |
March | 0.163688E+10 | 0.152355E+10 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.112076E+10 |
April | 0.145246E+10 | 0.131605E+10 | 0.295467E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.808258E+09 |
May | 0.157341E+10 | 0.137335E+10 | 0.312179E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1843279.71 | 0.779027E+09 |
June | 0.156904E+10 | 0.133953E+10 | 0.306585E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9279748.04 | 0.389455E+09 |
July | 0.145684E+10 | 0.127798E+10 | 0.300994E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 30071179.22 | 0.258020E+09 |
August | 0.163688E+10 | 0.143269E+10 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 26228098.57 | 0.286034E+09 |
September | 0.145246E+10 | 0.134306E+10 | 0.295333E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14788518.76 | 0.530296E+09 |
October | 0.150994E+10 | 0.145065E+10 | 0.306051E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 82157.37 | 0.807247E+09 |
November | 0.149520E+10 | 0.154327E+10 | 0.299318E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.112042E+10 |
December | 0.145684E+10 | 0.158769E+10 | 0.300927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.142237E+10 |
Annual Sum or Average | 0.181198E+11 | 0.171716E+11 | 0.363660E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 82292981.68 | 0.103168E+11 |
Minimum of Months | 0.136988E+10 | 0.127798E+10 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.258020E+09 |
Maximum of Months | 0.163688E+10 | 0.164382E+10 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 30071179.22 | 0.153900E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.109494E+10 | 0.197183E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.104183E+10 |
February | 0.882782E+09 | 0.881197E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.866490E+09 |
March | 0.105485E+10 | 0.991184E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.794420E+09 |
April | 0.936002E+09 | 0.850687E+09 | 0.190406E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.601255E+09 |
May | 0.101394E+10 | 0.882212E+09 | 0.201175E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1182335.55 | 0.560793E+09 |
June | 0.101113E+10 | 0.855951E+09 | 0.197570E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6006741.86 | 0.288091E+09 |
July | 0.938820E+09 | 0.820794E+09 | 0.193968E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19140872.83 | 0.200550E+09 |
August | 0.105485E+10 | 0.919730E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17044531.44 | 0.217513E+09 |
September | 0.936002E+09 | 0.869326E+09 | 0.190319E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10789051.44 | 0.369554E+09 |
October | 0.973041E+09 | 0.956001E+09 | 0.197226E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 72239.01 | 0.566747E+09 |
November | 0.963541E+09 | 0.101877E+10 | 0.192888E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.800068E+09 |
December | 0.938820E+09 | 0.105701E+10 | 0.193924E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.102144E+10 |
Annual Sum or Average | 0.116768E+11 | 0.111978E+11 | 0.234351E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 54235772.13 | 0.732875E+10 |
Minimum of Months | 0.882782E+09 | 0.820794E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.200550E+09 |
Maximum of Months | 0.105485E+10 | 0.109494E+10 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19140872.83 | 0.104183E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150991E+10 | 0.173790E+10 | 0.305979E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.323965E+10 |
February | 0.136985E+10 | 0.139282E+10 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.248617E+10 |
March | 0.163685E+10 | 0.154262E+10 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.231601E+10 |
April | 0.145243E+10 | 0.131304E+10 | 0.295462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.165673E+10 |
May | 0.157338E+10 | 0.136393E+10 | 0.312174E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4044207.35 | 0.168298E+10 |
June | 0.156900E+10 | 0.132282E+10 | 0.306580E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21208525.06 | 0.869729E+09 |
July | 0.145680E+10 | 0.126757E+10 | 0.300989E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 73182266.22 | 0.588133E+09 |
August | 0.163685E+10 | 0.142176E+10 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 62180245.36 | 0.636502E+09 |
September | 0.145243E+10 | 0.134796E+10 | 0.295328E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 39309179.35 | 0.110818E+10 |
October | 0.150991E+10 | 0.149665E+10 | 0.306046E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1320989.74 | 0.157291E+10 |
November | 0.149516E+10 | 0.163103E+10 | 0.299314E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.224057E+10 |
December | 0.145680E+10 | 0.169690E+10 | 0.300922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.284154E+10 |
Annual Sum or Average | 0.181194E+11 | 0.175350E+11 | 0.363654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.201245E+09 | 0.212391E+11 |
Minimum of Months | 0.136985E+10 | 0.126757E+10 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.588133E+09 |
Maximum of Months | 0.163685E+10 | 0.173790E+10 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 73182266.22 | 0.323965E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.715730E+09 | 0.108005E+10 | 0.197184E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.218346E+10 |
February | 0.649041E+09 | 0.880010E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.170600E+10 |
March | 0.773965E+09 | 0.983117E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.158184E+10 |
April | 0.688021E+09 | 0.842267E+09 | 0.190407E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.114438E+10 |
May | 0.744847E+09 | 0.881149E+09 | 0.201177E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2939532.30 | 0.112176E+10 |
June | 0.742030E+09 | 0.860164E+09 | 0.197572E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14457305.05 | 0.585978E+09 |
July | 0.690839E+09 | 0.818786E+09 | 0.193969E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 47988614.31 | 0.402024E+09 |
August | 0.773965E+09 | 0.920152E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 41465856.04 | 0.429706E+09 |
September | 0.688021E+09 | 0.863092E+09 | 0.190321E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 25595460.43 | 0.757548E+09 |
October | 0.715730E+09 | 0.941851E+09 | 0.197228E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 172655.26 | 0.108776E+10 |
November | 0.708685E+09 | 0.102332E+10 | 0.192889E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.150948E+10 |
December | 0.690839E+09 | 0.105379E+10 | 0.193926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.191333E+10 |
Annual Sum or Average | 0.858171E+10 | 0.111478E+11 | 0.234352E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.132619E+09 | 0.144233E+11 |
Minimum of Months | 0.649041E+09 | 0.818786E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.402024E+09 |
Maximum of Months | 0.773965E+09 | 0.108005E+10 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 47988614.31 | 0.218346E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150994E+10 | 0.164230E+10 | 0.305983E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.341893E+10 |
February | 0.136988E+10 | 0.133845E+10 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.277128E+10 |
March | 0.163688E+10 | 0.152209E+10 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.248729E+10 |
April | 0.145246E+10 | 0.131450E+10 | 0.295467E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.177488E+10 |
May | 0.157341E+10 | 0.137194E+10 | 0.312179E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4048816.96 | 0.172157E+10 |
June | 0.156904E+10 | 0.133817E+10 | 0.306585E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21048597.68 | 0.872877E+09 |
July | 0.145684E+10 | 0.127704E+10 | 0.300994E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 68603373.49 | 0.599782E+09 |
August | 0.163688E+10 | 0.143133E+10 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 60092131.39 | 0.662642E+09 |
September | 0.145246E+10 | 0.134179E+10 | 0.295333E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 32956251.02 | 0.118771E+10 |
October | 0.150994E+10 | 0.144782E+10 | 0.306051E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 91518.85 | 0.178190E+10 |
November | 0.149520E+10 | 0.154216E+10 | 0.299318E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.243618E+10 |
December | 0.145684E+10 | 0.158618E+10 | 0.300927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.305618E+10 |
Annual Sum or Average | 0.181198E+11 | 0.171538E+11 | 0.363660E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.186841E+09 | 0.227712E+11 |
Minimum of Months | 0.136988E+10 | 0.127704E+10 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.599782E+09 |
Maximum of Months | 0.163688E+10 | 0.164230E+10 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 68603373.49 | 0.341893E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.109244E+10 | 0.197183E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.220139E+10 |
February | 0.882782E+09 | 0.879043E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.173883E+10 |
March | 0.105485E+10 | 0.989598E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.160580E+10 |
April | 0.936002E+09 | 0.849759E+09 | 0.190406E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.118345E+10 |
May | 0.101394E+10 | 0.881584E+09 | 0.201175E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2649743.82 | 0.118627E+10 |
June | 0.101113E+10 | 0.855318E+09 | 0.197570E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13851259.53 | 0.609574E+09 |
July | 0.938820E+09 | 0.820198E+09 | 0.193968E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 46930900.13 | 0.430341E+09 |
August | 0.105485E+10 | 0.919058E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 40823690.75 | 0.449994E+09 |
September | 0.936002E+09 | 0.867819E+09 | 0.190319E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 26036279.83 | 0.770974E+09 |
October | 0.973041E+09 | 0.953826E+09 | 0.197226E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 316759.30 | 0.110490E+10 |
November | 0.963541E+09 | 0.101719E+10 | 0.192888E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.154482E+10 |
December | 0.938820E+09 | 0.105466E+10 | 0.193924E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.194508E+10 |
Annual Sum or Average | 0.116768E+11 | 0.111805E+11 | 0.234351E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.130609E+09 | 0.147714E+11 |
Minimum of Months | 0.882782E+09 | 0.820198E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.430341E+09 |
Maximum of Months | 0.105485E+10 | 0.109244E+10 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 46930900.13 | 0.220139E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150991E+10 | 0.173741E+10 | 0.305979E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.394040E+10 |
February | 0.136985E+10 | 0.139270E+10 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.291436E+10 |
March | 0.163685E+10 | 0.154243E+10 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.272350E+10 |
April | 0.145243E+10 | 0.131285E+10 | 0.295462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.190017E+10 |
May | 0.157338E+10 | 0.136379E+10 | 0.312174E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4712861.14 | 0.197793E+10 |
June | 0.156900E+10 | 0.132280E+10 | 0.306580E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 25297120.00 | 0.104676E+10 |
July | 0.145680E+10 | 0.126753E+10 | 0.300989E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 87717344.83 | 0.710824E+09 |
August | 0.163685E+10 | 0.142174E+10 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 74689445.66 | 0.762621E+09 |
September | 0.145243E+10 | 0.134791E+10 | 0.295328E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 46990716.79 | 0.128935E+10 |
October | 0.150991E+10 | 0.149638E+10 | 0.306046E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4507252.80 | 0.174505E+10 |
November | 0.149516E+10 | 0.163094E+10 | 0.299314E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.259307E+10 |
December | 0.145680E+10 | 0.169650E+10 | 0.300922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.341998E+10 |
Annual Sum or Average | 0.181194E+11 | 0.175330E+11 | 0.363654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.243915E+09 | 0.250240E+11 |
Minimum of Months | 0.136985E+10 | 0.126753E+10 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.710824E+09 |
Maximum of Months | 0.163685E+10 | 0.173741E+10 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 87717344.83 | 0.394040E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.108005E+10 | 0.197184E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.265172E+10 |
February | 0.882782E+09 | 0.879921E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.199492E+10 |
March | 0.105485E+10 | 0.983000E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.186671E+10 |
April | 0.936002E+09 | 0.842267E+09 | 0.190407E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.133031E+10 |
May | 0.101394E+10 | 0.881111E+09 | 0.201177E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3357503.38 | 0.132998E+10 |
June | 0.101113E+10 | 0.860144E+09 | 0.197572E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17062471.02 | 0.713580E+09 |
July | 0.938820E+09 | 0.818786E+09 | 0.193969E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 56666124.36 | 0.491920E+09 |
August | 0.105485E+10 | 0.920121E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 49624123.39 | 0.522233E+09 |
September | 0.936002E+09 | 0.863067E+09 | 0.190321E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 29933806.55 | 0.898028E+09 |
October | 0.973041E+09 | 0.942030E+09 | 0.197228E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 497746.06 | 0.122435E+10 |
November | 0.963541E+09 | 0.102372E+10 | 0.192889E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.174955E+10 |
December | 0.938820E+09 | 0.105379E+10 | 0.193926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.229378E+10 |
Annual Sum or Average | 0.116768E+11 | 0.111480E+11 | 0.234352E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.157142E+09 | 0.170671E+11 |
Minimum of Months | 0.882782E+09 | 0.818786E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.491920E+09 |
Maximum of Months | 0.105485E+10 | 0.108005E+10 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 56666124.36 | 0.265172E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150994E+10 | 0.164223E+10 | 0.305983E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.409663E+10 |
February | 0.136988E+10 | 0.133845E+10 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.322593E+10 |
March | 0.163688E+10 | 0.152206E+10 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.293328E+10 |
April | 0.145246E+10 | 0.131444E+10 | 0.295467E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.206097E+10 |
May | 0.157341E+10 | 0.137194E+10 | 0.312179E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4736867.71 | 0.203095E+10 |
June | 0.156904E+10 | 0.133817E+10 | 0.306585E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 25160296.06 | 0.105214E+10 |
July | 0.145684E+10 | 0.127701E+10 | 0.300994E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 82271066.22 | 0.724645E+09 |
August | 0.163688E+10 | 0.143131E+10 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 72523953.38 | 0.798669E+09 |
September | 0.145246E+10 | 0.134174E+10 | 0.295333E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 39537873.37 | 0.140204E+10 |
October | 0.150994E+10 | 0.144782E+10 | 0.306051E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 147354.26 | 0.202736E+10 |
November | 0.149520E+10 | 0.154216E+10 | 0.299318E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.280696E+10 |
December | 0.145684E+10 | 0.158598E+10 | 0.300927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.359254E+10 |
Annual Sum or Average | 0.181198E+11 | 0.171533E+11 | 0.363660E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.224377E+09 | 0.267521E+11 |
Minimum of Months | 0.136988E+10 | 0.127701E+10 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.724645E+09 |
Maximum of Months | 0.163688E+10 | 0.164223E+10 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 82271066.22 | 0.409663E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.109232E+10 | 0.197183E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.266871E+10 |
February | 0.882782E+09 | 0.878986E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.204680E+10 |
March | 0.105485E+10 | 0.989552E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.190831E+10 |
April | 0.936002E+09 | 0.849759E+09 | 0.190406E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.138607E+10 |
May | 0.101394E+10 | 0.881564E+09 | 0.201175E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3119246.60 | 0.140644E+10 |
June | 0.101113E+10 | 0.855305E+09 | 0.197570E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16713609.40 | 0.737520E+09 |
July | 0.938820E+09 | 0.820186E+09 | 0.193968E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 56982235.11 | 0.522082E+09 |
August | 0.105485E+10 | 0.919058E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 49396256.49 | 0.543483E+09 |
September | 0.936002E+09 | 0.867727E+09 | 0.190319E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 31519229.64 | 0.913243E+09 |
October | 0.973041E+09 | 0.953817E+09 | 0.197226E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 848209.38 | 0.126423E+10 |
November | 0.963541E+09 | 0.101714E+10 | 0.192888E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.180620E+10 |
December | 0.938820E+09 | 0.105461E+10 | 0.193924E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.233178E+10 |
Annual Sum or Average | 0.116768E+11 | 0.111800E+11 | 0.234351E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.158579E+09 | 0.175349E+11 |
Minimum of Months | 0.882782E+09 | 0.820186E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.522082E+09 |
Maximum of Months | 0.105485E+10 | 0.109232E+10 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 56982235.11 | 0.266871E+10 |
Report: SpaceGainsMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.174411E+09 | 0.553024E+09 | 0.521915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.158233E+09 | 0.501634E+09 | 0.942813E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.189074E+09 | 0.596080E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.167772E+09 | 0.532421E+09 | 0.201821E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.181743E+09 | 0.574552E+09 | 0.522616E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.181238E+09 | 0.571774E+09 | 0.101086E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.168277E+09 | 0.535199E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.189074E+09 | 0.596080E+09 | 0.208555E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.167772E+09 | 0.532421E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.174411E+09 | 0.553024E+09 | 0.104453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.172708E+09 | 0.546542E+09 | 0.151524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.168277E+09 | 0.535199E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.209299E+10 | 0.662795E+10 | 0.153881E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.158233E+09 | 0.501634E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.189074E+09 | 0.596080E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.174411E+09 | 0.553024E+09 | 0.521915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.158233E+09 | 0.501634E+09 | 0.942813E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.189074E+09 | 0.596080E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.167772E+09 | 0.532421E+09 | 0.201821E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.181743E+09 | 0.574552E+09 | 0.522616E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.181238E+09 | 0.571774E+09 | 0.101086E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.168277E+09 | 0.535199E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.189074E+09 | 0.596080E+09 | 0.208555E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.167772E+09 | 0.532421E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.174411E+09 | 0.553024E+09 | 0.104453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.172708E+09 | 0.546542E+09 | 0.151524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.168277E+09 | 0.535199E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.209299E+10 | 0.662795E+10 | 0.153881E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.158233E+09 | 0.501634E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.189074E+09 | 0.596080E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.174411E+09 | 0.553024E+09 | 0.521915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.158233E+09 | 0.501634E+09 | 0.942813E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.189074E+09 | 0.596080E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.167772E+09 | 0.532421E+09 | 0.201821E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.181743E+09 | 0.574552E+09 | 0.522616E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.181238E+09 | 0.571774E+09 | 0.101086E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.168277E+09 | 0.535199E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.189074E+09 | 0.596080E+09 | 0.208555E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.167772E+09 | 0.532421E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.174411E+09 | 0.553024E+09 | 0.104453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.172708E+09 | 0.546542E+09 | 0.151524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.168277E+09 | 0.535199E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.209299E+10 | 0.662795E+10 | 0.153881E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.158233E+09 | 0.501634E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.189074E+09 | 0.596080E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.377547E+10 | 0.618367E+10 | 0.254202E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.342526E+10 | 0.560905E+10 | 0.459203E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.409289E+10 | 0.666512E+10 | 0.762947E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.363176E+10 | 0.595330E+10 | 0.982982E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.393418E+10 | 0.642439E+10 | 0.254544E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.392325E+10 | 0.639333E+10 | 0.492345E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.364269E+10 | 0.598436E+10 | 0.762947E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.409289E+10 | 0.666512E+10 | 0.101578E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.363176E+10 | 0.595330E+10 | 0.246344E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.377547E+10 | 0.618367E+10 | 0.508746E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.373861E+10 | 0.611120E+10 | 0.738006E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.364269E+10 | 0.598436E+10 | 0.101681E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.453069E+11 | 0.741109E+11 | 0.749486E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.342526E+10 | 0.560905E+10 | 0.246344E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.409289E+10 | 0.666512E+10 | 0.101681E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.329618E+10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.265704E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.239618E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.173599E+10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2845168.02 | 0.168630E+10 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14984615.87 | 0.835195E+09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57171345.78 | 0.559611E+09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 49317005.50 | 0.619774E+09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32238062.09 | 0.113169E+10 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 53315.18 | 0.170586E+10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.242144E+10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.307998E+10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.156610E+09 | 0.221252E+11 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.559611E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57171345.78 | 0.329618E+10 |
Report: SpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.548012E+10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.439512E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.404852E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.293441E+10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5322703.80 | 0.290090E+10 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27517720.69 | 0.145570E+10 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.107218E+09 | 0.979679E+09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 90314998.10 | 0.108578E+10 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 60939692.69 | 0.196428E+10 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 124815.72 | 0.287072E+10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.401593E+10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.500976E+10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.291438E+09 | 0.371409E+11 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.979679E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.107218E+09 | 0.548012E+10 |
Report: SpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.583293E+10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.454420E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.428613E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.309000E+10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3356716.68 | 0.314763E+10 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23125457.15 | 0.165020E+10 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 93196841.68 | 0.111268E+10 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 85480933.62 | 0.121197E+10 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 52772996.91 | 0.209942E+10 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.289095E+10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.406089E+10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.514260E+10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.257933E+09 | 0.390696E+11 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.111268E+10 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 93196841.68 | 0.583293E+10 |
Report: PeakSpaceGainsMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 17832.21 | 02-JAN-10:09 | 22950.34 | 02-JAN-08:09 | 13457.54 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 17832.21 | 01-FEB-10:09 | 22950.34 | 01-FEB-08:09 | 13457.54 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 17832.21 | 01-MAR-10:09 | 22950.34 | 01-MAR-08:09 | 13457.54 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 17832.21 | 03-APR-09:09 | 22950.34 | 03-APR-07:10 | 13457.54 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 17832.21 | 01-MAY-09:09 | 22950.34 | 01-MAY-07:10 | 13457.54 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 17832.21 | 01-JUN-09:09 | 22950.34 | 01-JUN-07:10 | 13457.54 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 17832.21 | 03-JUL-09:09 | 22950.34 | 03-JUL-07:10 | 13457.54 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 17832.21 | 01-AUG-09:09 | 22950.34 | 01-AUG-07:10 | 13457.54 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 17832.21 | 01-SEP-09:09 | 22950.34 | 01-SEP-07:10 | 13457.54 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 17832.21 | 02-OCT-09:09 | 22950.34 | 02-OCT-07:10 | 13457.54 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 17832.21 | 01-NOV-09:09 | 22950.34 | 01-NOV-07:10 | 13457.54 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 17832.21 | 01-DEC-10:09 | 22950.34 | 01-DEC-08:09 | 13457.54 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 17832.21 | 22950.34 | 13457.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 17832.21 | 22950.34 | 13457.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 16014.58 | 02-JAN-10:09 | 20611.01 | 02-JAN-08:09 | 17206.63 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 16014.58 | 01-FEB-10:09 | 20611.01 | 01-FEB-08:09 | 17206.63 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 16014.58 | 01-MAR-10:09 | 20611.01 | 01-MAR-08:09 | 17206.63 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 16014.58 | 03-APR-09:09 | 20611.01 | 03-APR-07:10 | 17206.63 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 16014.58 | 01-MAY-09:09 | 20611.01 | 01-MAY-07:10 | 17206.63 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 16014.58 | 01-JUN-09:09 | 20611.01 | 01-JUN-07:10 | 17206.63 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 16014.58 | 03-JUL-09:09 | 20611.01 | 03-JUL-07:10 | 17206.63 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 16014.58 | 01-AUG-09:09 | 20611.01 | 01-AUG-07:10 | 17206.63 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 16014.58 | 01-SEP-09:09 | 20611.01 | 01-SEP-07:10 | 17206.63 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 16014.58 | 02-OCT-09:09 | 20611.01 | 02-OCT-07:10 | 17206.63 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 16014.58 | 01-NOV-09:09 | 20611.01 | 01-NOV-07:10 | 17206.63 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 16014.58 | 01-DEC-10:09 | 20611.01 | 01-DEC-08:09 | 17206.63 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 16014.58 | 20611.01 | 17206.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 16014.58 | 20611.01 | 17206.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 16014.58 | 02-JAN-10:09 | 20611.01 | 02-JAN-08:09 | 17206.56 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 16014.58 | 01-FEB-10:09 | 20611.01 | 01-FEB-08:09 | 17206.56 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 16014.58 | 01-MAR-10:09 | 20611.01 | 01-MAR-08:09 | 17206.56 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 16014.58 | 03-APR-09:09 | 20611.01 | 03-APR-07:10 | 17206.56 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 16014.58 | 01-MAY-09:09 | 20611.01 | 01-MAY-07:10 | 17206.56 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 16014.58 | 01-JUN-09:09 | 20611.01 | 01-JUN-07:10 | 17206.56 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 16014.58 | 03-JUL-09:09 | 20611.01 | 03-JUL-07:10 | 17206.56 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 16014.58 | 01-AUG-09:09 | 20611.01 | 01-AUG-07:10 | 17206.56 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 16014.58 | 01-SEP-09:09 | 20611.01 | 01-SEP-07:10 | 17206.56 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 16014.58 | 02-OCT-09:09 | 20611.01 | 02-OCT-07:10 | 17206.56 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 16014.58 | 01-NOV-09:09 | 20611.01 | 01-NOV-07:10 | 17206.56 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 16014.58 | 01-DEC-10:09 | 20611.01 | 01-DEC-08:09 | 17206.56 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 16014.58 | 20611.01 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 16014.58 | 20611.01 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 16014.58 | 02-JAN-10:09 | 20611.01 | 02-JAN-08:09 | 17206.56 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 16014.58 | 01-FEB-10:09 | 20611.01 | 01-FEB-08:09 | 17206.56 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 16014.58 | 01-MAR-10:09 | 20611.01 | 01-MAR-08:09 | 17206.56 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 16014.58 | 03-APR-09:09 | 20611.01 | 03-APR-07:10 | 17206.56 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 16014.58 | 01-MAY-09:09 | 20611.01 | 01-MAY-07:10 | 17206.56 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 16014.58 | 01-JUN-09:09 | 20611.01 | 01-JUN-07:10 | 17206.56 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 16014.58 | 03-JUL-09:09 | 20611.01 | 03-JUL-07:10 | 17206.56 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 16014.58 | 01-AUG-09:09 | 20611.01 | 01-AUG-07:10 | 17206.56 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 16014.58 | 01-SEP-09:09 | 20611.01 | 01-SEP-07:10 | 17206.56 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 16014.58 | 02-OCT-09:09 | 20611.01 | 02-OCT-07:10 | 17206.56 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 16014.58 | 01-NOV-09:09 | 20611.01 | 01-NOV-07:10 | 17206.56 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 16014.58 | 01-DEC-10:09 | 20611.01 | 01-DEC-08:09 | 17206.56 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 16014.58 | 20611.01 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 16014.58 | 20611.01 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.79 | 02-JAN-10:09 | 2587.92 | 02-JAN-08:09 | 2160.55 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 2510.68 | 05-JAN-22:01 |
February | 2010.79 | 01-FEB-10:09 | 2255.20 | 01-FEB-08:09 | 2160.55 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 1551.79 | 17-FEB-04:00 |
March | 2010.79 | 01-MAR-10:09 | 2587.92 | 17-MAR-07:10 | 2160.55 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1899.34 | 02-MAR-23:00 |
April | 2010.79 | 03-APR-09:09 | 1922.48 | 14-APR-07:10 | 2160.55 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 1354.19 | 27-APR-02:00 |
May | 2010.79 | 01-MAY-09:09 | 1803.00 | 03-MAY-07:10 | 2160.55 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 95.30 | 20-MAY-17:02 | 2569.98 | 22-MAY-04:00 |
June | 2010.79 | 01-JUN-09:09 | 1350.81 | 16-JUN-07:10 | 2160.55 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 127.69 | 29-JUN-15:00 | 1081.55 | 14-JUN-02:00 |
July | 2010.79 | 03-JUL-09:09 | 1470.28 | 07-JUL-07:30 | 2160.55 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 254.07 | 30-JUL-11:58 | 653.71 | 05-JUL-01:00 |
August | 2010.79 | 01-AUG-09:09 | 1470.28 | 17-AUG-07:10 | 2160.55 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 323.02 | 06-AUG-17:24 | 828.37 | 23-AUG-03:00 |
September | 2010.79 | 01-SEP-09:09 | 2255.20 | 11-SEP-07:10 | 2160.55 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 364.82 | 03-SEP-12:51 | 1442.05 | 12-SEP-03:00 |
October | 2010.79 | 02-OCT-09:09 | 2587.92 | 25-OCT-07:10 | 2160.55 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11.99 | 18-OCT-14:00 | 1244.55 | 30-OCT-22:00 |
November | 2010.79 | 01-NOV-09:09 | 2587.92 | 01-NOV-07:10 | 2160.55 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1505.87 | 28-NOV-05:51 |
December | 2010.79 | 01-DEC-10:09 | 2587.92 | 01-DEC-08:09 | 2160.55 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 2297.01 | 01-DEC-04:55 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.79 | 1350.81 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 653.71 | |||||
Maximum of Months | 2010.79 | 2587.92 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 364.82 | 2569.98 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 1667.75 | 02-JAN-08:09 | 1392.34 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 1673.43 | 05-JAN-22:01 |
February | 1295.83 | 01-FEB-10:09 | 1453.34 | 01-FEB-16:00 | 1392.34 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 1015.48 | 17-FEB-04:00 |
March | 1295.83 | 01-MAR-10:09 | 1667.75 | 17-MAR-07:10 | 1392.34 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1242.25 | 02-MAR-23:00 |
April | 1295.83 | 03-APR-09:09 | 1161.92 | 14-APR-07:10 | 1392.34 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 883.30 | 27-APR-02:00 |
May | 1295.83 | 01-MAY-09:09 | 947.51 | 03-MAY-07:10 | 1392.34 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 85.49 | 20-MAY-17:20 | 1694.36 | 22-MAY-04:00 |
June | 1295.83 | 01-JUN-09:09 | 793.52 | 01-JUN-07:10 | 1392.34 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 85.13 | 29-JUN-15:00 | 700.51 | 14-JUN-02:00 |
July | 1295.83 | 03-JUL-09:09 | 870.51 | 07-JUL-07:19 | 1392.34 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 190.46 | 30-JUL-12:00 | 420.91 | 05-JUL-01:00 |
August | 1295.83 | 01-AUG-09:09 | 870.51 | 17-AUG-07:10 | 1392.34 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 227.13 | 06-AUG-17:30 | 531.57 | 23-AUG-03:00 |
September | 1295.83 | 01-SEP-09:09 | 1161.92 | 13-SEP-07:10 | 1392.34 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 254.71 | 03-SEP-13:10 | 944.17 | 12-SEP-03:00 |
October | 1295.83 | 02-OCT-09:09 | 1667.75 | 25-OCT-07:10 | 1392.34 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7.99 | 18-OCT-14:00 | 813.88 | 08-OCT-08:40 |
November | 1295.83 | 01-NOV-09:09 | 1667.75 | 01-NOV-07:10 | 1392.34 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1003.93 | 28-NOV-05:56 |
December | 1295.83 | 01-DEC-10:09 | 1667.75 | 01-DEC-08:09 | 1392.34 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1482.36 | 01-DEC-04:55 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 793.52 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 420.91 | |||||
Maximum of Months | 1295.83 | 1667.75 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 254.71 | 1694.36 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.83 | 02-JAN-10:09 | 2587.98 | 02-JAN-08:09 | 2160.58 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 2509.79 | 05-JAN-22:01 |
February | 2010.83 | 01-FEB-10:09 | 2255.25 | 02-FEB-08:09 | 2160.58 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 1619.04 | 19-FEB-12:20 |
March | 2010.83 | 01-MAR-10:09 | 2587.98 | 17-MAR-07:10 | 2160.58 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1927.92 | 02-MAR-23:00 |
April | 2010.83 | 03-APR-09:09 | 1922.52 | 14-APR-07:10 | 2160.58 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 1335.86 | 27-APR-02:00 |
May | 2010.83 | 01-MAY-09:09 | 1803.04 | 03-MAY-07:10 | 2160.58 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 100.30 | 20-MAY-17:02 | 2488.82 | 22-MAY-04:00 |
June | 2010.83 | 01-JUN-09:09 | 1350.84 | 16-JUN-07:10 | 2160.58 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 127.69 | 29-JUN-15:00 | 1058.81 | 14-JUN-02:00 |
July | 2010.83 | 03-JUL-09:09 | 1470.31 | 07-JUL-07:30 | 2160.58 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 262.44 | 30-JUL-11:58 | 637.61 | 05-JUL-01:00 |
August | 2010.83 | 01-AUG-09:09 | 1470.31 | 17-AUG-07:10 | 2160.58 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 328.45 | 06-AUG-17:24 | 821.06 | 23-AUG-03:00 |
September | 2010.83 | 01-SEP-09:09 | 1803.04 | 11-SEP-07:10 | 2160.58 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 333.32 | 03-SEP-13:04 | 1400.54 | 12-SEP-03:00 |
October | 2010.83 | 02-OCT-09:09 | 2587.98 | 25-OCT-07:10 | 2160.58 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11.77 | 18-OCT-15:00 | 1286.72 | 08-OCT-15:00 |
November | 2010.83 | 01-NOV-09:09 | 2587.98 | 01-NOV-07:10 | 2160.58 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1505.89 | 28-NOV-05:51 |
December | 2010.83 | 01-DEC-10:09 | 2587.98 | 01-DEC-08:09 | 2160.58 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 2212.80 | 01-DEC-04:55 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.83 | 1350.84 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 637.61 | |||||
Maximum of Months | 2010.83 | 2587.98 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 333.32 | 2509.79 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 1667.75 | 02-JAN-08:09 | 1392.33 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 1675.48 | 05-JAN-22:01 |
February | 1295.83 | 01-FEB-10:09 | 1667.75 | 02-FEB-08:09 | 1392.33 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 1103.32 | 17-FEB-04:00 |
March | 1295.83 | 01-MAR-10:09 | 1667.75 | 17-MAR-07:10 | 1392.33 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1352.61 | 02-MAR-23:00 |
April | 1295.83 | 03-APR-09:09 | 1453.34 | 14-APR-07:10 | 1392.33 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 988.83 | 27-APR-02:00 |
May | 1295.83 | 01-MAY-09:09 | 1161.92 | 03-MAY-07:10 | 1392.33 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 59.46 | 20-MAY-17:20 | 1747.61 | 22-MAY-04:00 |
June | 1295.83 | 01-JUN-09:09 | 870.51 | 01-JUN-07:10 | 1392.33 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 85.13 | 29-JUN-15:00 | 784.56 | 14-JUN-02:00 |
July | 1295.83 | 03-JUL-09:09 | 947.51 | 07-JUL-07:10 | 1392.33 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 201.62 | 30-JUL-12:00 | 491.69 | 05-JUL-01:00 |
August | 1295.83 | 01-AUG-09:09 | 1161.92 | 17-AUG-07:10 | 1392.33 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 209.43 | 06-AUG-17:24 | 642.99 | 23-AUG-03:00 |
September | 1295.83 | 01-SEP-09:09 | 1453.34 | 11-SEP-07:10 | 1392.33 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 259.95 | 03-SEP-12:51 | 994.57 | 12-SEP-03:00 |
October | 1295.83 | 02-OCT-09:09 | 1667.75 | 25-OCT-07:10 | 1392.33 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7.99 | 18-OCT-14:00 | 885.78 | 30-OCT-22:10 |
November | 1295.83 | 01-NOV-09:09 | 1667.75 | 01-NOV-07:10 | 1392.33 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1042.92 | 26-NOV-19:52 |
December | 1295.83 | 01-DEC-10:09 | 1667.75 | 01-DEC-08:09 | 1392.33 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1673.65 | 01-DEC-04:55 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 870.51 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 491.69 | |||||
Maximum of Months | 1295.83 | 1667.75 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 259.95 | 1747.61 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.79 | 02-JAN-10:09 | 2587.92 | 02-JAN-08:09 | 2160.55 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 5873.78 | 05-JAN-22:01 |
February | 2010.79 | 01-FEB-10:09 | 2255.20 | 01-FEB-08:09 | 2160.55 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 3236.01 | 08-FEB-22:01 |
March | 2010.79 | 01-MAR-10:09 | 2587.92 | 17-MAR-07:10 | 2160.55 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 4045.62 | 02-MAR-23:00 |
April | 2010.79 | 03-APR-09:09 | 1803.00 | 14-APR-07:10 | 2160.55 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 2826.79 | 27-APR-02:00 |
May | 2010.79 | 01-MAY-09:09 | 1803.00 | 03-MAY-07:10 | 2160.55 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 226.77 | 20-MAY-17:02 | 5691.68 | 22-MAY-04:57 |
June | 2010.79 | 01-JUN-09:09 | 1350.81 | 26-JUN-11:30 | 2160.55 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 295.49 | 29-JUN-15:00 | 2262.57 | 14-JUN-02:00 |
July | 2010.79 | 03-JUL-09:09 | 1470.28 | 07-JUL-07:30 | 2160.55 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 600.31 | 30-JUL-11:53 | 1360.85 | 05-JUL-01:00 |
August | 2010.79 | 01-AUG-09:09 | 1470.28 | 17-AUG-07:10 | 2160.55 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 740.98 | 06-AUG-17:24 | 1663.66 | 23-AUG-03:00 |
September | 2010.79 | 01-SEP-09:09 | 2135.72 | 11-SEP-07:10 | 2160.55 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 869.18 | 03-SEP-13:00 | 2933.28 | 12-SEP-03:00 |
October | 2010.79 | 02-OCT-09:09 | 2587.92 | 25-OCT-07:10 | 2160.55 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 183.31 | 15-OCT-14:00 | 2567.27 | 30-OCT-21:03 |
November | 2010.79 | 01-NOV-09:09 | 2587.92 | 01-NOV-07:10 | 2160.55 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 3546.95 | 28-NOV-06:00 |
December | 2010.79 | 01-DEC-10:09 | 2587.92 | 01-DEC-08:09 | 2160.55 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 5043.14 | 01-DEC-05:09 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.79 | 1350.81 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1360.85 | |||||
Maximum of Months | 2010.79 | 2587.92 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 869.18 | 5873.78 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1239.33 | 02-JAN-08:09 | 1667.75 | 02-JAN-08:09 | 1392.34 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 3915.51 | 05-JAN-22:01 |
February | 1239.33 | 01-FEB-08:09 | 1453.34 | 01-FEB-16:00 | 1392.34 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 2156.58 | 08-FEB-22:01 |
March | 1239.33 | 01-MAR-08:09 | 1667.75 | 17-MAR-07:10 | 1392.34 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 2690.71 | 02-MAR-23:00 |
April | 1239.33 | 03-APR-07:10 | 1161.92 | 14-APR-07:10 | 1392.34 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 1884.57 | 27-APR-02:00 |
May | 1239.33 | 01-MAY-07:10 | 947.51 | 03-MAY-07:10 | 1392.34 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 186.52 | 20-MAY-17:02 | 3794.41 | 22-MAY-04:54 |
June | 1239.33 | 01-JUN-07:10 | 793.52 | 01-JUN-07:10 | 1392.34 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 196.99 | 29-JUN-15:00 | 1544.69 | 04-JUN-13:55 |
July | 1239.33 | 03-JUL-07:10 | 870.51 | 07-JUL-07:19 | 1392.34 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 423.41 | 30-JUL-14:57 | 903.89 | 05-JUL-01:00 |
August | 1239.33 | 01-AUG-07:10 | 870.51 | 17-AUG-07:10 | 1392.34 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 523.68 | 06-AUG-17:30 | 1103.92 | 23-AUG-03:00 |
September | 1239.33 | 01-SEP-07:10 | 1161.92 | 13-SEP-07:10 | 1392.34 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 589.33 | 03-SEP-12:51 | 1917.38 | 12-SEP-03:00 |
October | 1239.33 | 02-OCT-07:10 | 1667.75 | 25-OCT-07:10 | 1392.34 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 21.58 | 18-OCT-14:00 | 1712.59 | 30-OCT-21:03 |
November | 1239.33 | 01-NOV-07:10 | 1667.75 | 01-NOV-07:10 | 1392.34 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 2364.89 | 28-NOV-05:53 |
December | 1239.33 | 01-DEC-08:09 | 1667.75 | 01-DEC-08:09 | 1392.34 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 3362.22 | 01-DEC-05:07 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1239.33 | 793.52 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 903.89 | |||||
Maximum of Months | 1239.33 | 1667.75 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 589.33 | 3915.51 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.83 | 02-JAN-10:09 | 2587.98 | 02-JAN-08:09 | 2160.58 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 5876.26 | 05-JAN-22:01 |
February | 2010.83 | 01-FEB-10:09 | 2135.77 | 02-FEB-08:09 | 2160.58 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 3682.07 | 19-FEB-12:50 |
March | 2010.83 | 01-MAR-10:09 | 2587.98 | 17-MAR-07:10 | 2160.58 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 4227.74 | 02-MAR-23:00 |
April | 2010.83 | 03-APR-09:09 | 1803.04 | 14-APR-07:10 | 2160.58 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 2860.98 | 27-APR-02:00 |
May | 2010.83 | 01-MAY-09:09 | 1803.04 | 03-MAY-07:10 | 2160.58 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 229.87 | 20-MAY-17:02 | 5691.65 | 22-MAY-04:57 |
June | 2010.83 | 01-JUN-09:09 | 1350.84 | 16-JUN-07:10 | 2160.58 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 295.49 | 29-JUN-15:00 | 2241.52 | 14-JUN-02:00 |
July | 2010.83 | 03-JUL-09:09 | 1470.31 | 07-JUL-07:30 | 2160.58 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 595.97 | 30-JUL-14:16 | 1376.95 | 05-JUL-01:00 |
August | 2010.83 | 01-AUG-09:09 | 1470.31 | 17-AUG-07:10 | 2160.58 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 760.66 | 06-AUG-17:24 | 1706.24 | 23-AUG-03:00 |
September | 2010.83 | 01-SEP-09:09 | 1803.04 | 11-SEP-07:10 | 2160.58 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 810.14 | 03-SEP-12:57 | 2922.42 | 12-SEP-03:00 |
October | 2010.83 | 02-OCT-09:09 | 2587.98 | 25-OCT-07:10 | 2160.58 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 18.98 | 18-OCT-15:10 | 2860.05 | 08-OCT-15:00 |
November | 2010.83 | 01-NOV-09:09 | 2587.98 | 01-NOV-07:10 | 2160.58 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 3547.08 | 28-NOV-05:59 |
December | 2010.83 | 01-DEC-10:09 | 2587.98 | 01-DEC-08:09 | 2160.58 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 5044.72 | 01-DEC-05:04 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.83 | 1350.84 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1376.95 | |||||
Maximum of Months | 2010.83 | 2587.98 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 810.14 | 5876.26 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 1667.75 | 02-JAN-08:09 | 1392.33 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 3915.47 | 05-JAN-22:01 |
February | 1295.83 | 01-FEB-10:09 | 1667.75 | 02-FEB-08:09 | 1392.33 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 2161.14 | 08-FEB-22:01 |
March | 1295.83 | 01-MAR-10:09 | 1667.75 | 17-MAR-07:10 | 1392.33 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 2784.24 | 02-MAR-23:00 |
April | 1295.83 | 03-APR-09:09 | 1453.34 | 14-APR-07:10 | 1392.33 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 1918.61 | 27-APR-02:00 |
May | 1295.83 | 01-MAY-09:09 | 1161.92 | 03-MAY-07:10 | 1392.33 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 152.40 | 20-MAY-17:02 | 3794.45 | 22-MAY-04:54 |
June | 1295.83 | 01-JUN-09:09 | 870.51 | 01-JUN-07:10 | 1392.33 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 196.99 | 29-JUN-15:00 | 1541.08 | 14-JUN-02:00 |
July | 1295.83 | 03-JUL-09:09 | 947.51 | 07-JUL-07:19 | 1392.33 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 499.37 | 30-JUL-11:53 | 980.66 | 05-JUL-01:00 |
August | 1295.83 | 01-AUG-09:09 | 1161.92 | 17-AUG-07:10 | 1392.33 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 519.06 | 06-AUG-12:10 | 1154.08 | 23-AUG-03:00 |
September | 1295.83 | 01-SEP-09:09 | 1453.34 | 11-SEP-07:10 | 1392.33 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 649.29 | 03-SEP-12:51 | 1922.40 | 12-SEP-03:00 |
October | 1295.83 | 02-OCT-09:09 | 1667.75 | 25-OCT-07:10 | 1392.33 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 49.79 | 15-OCT-12:30 | 1739.01 | 30-OCT-22:00 |
November | 1295.83 | 01-NOV-09:09 | 1667.75 | 01-NOV-07:10 | 1392.33 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 2364.75 | 28-NOV-06:00 |
December | 1295.83 | 01-DEC-10:09 | 1667.75 | 01-DEC-08:09 | 1392.33 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 3362.26 | 01-DEC-05:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 870.51 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 980.66 | |||||
Maximum of Months | 1295.83 | 1667.75 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 649.29 | 3915.47 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.79 | 02-JAN-10:09 | 2587.92 | 02-JAN-08:09 | 2160.55 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 7286.41 | 05-JAN-22:01 |
February | 2010.79 | 01-FEB-10:09 | 2255.20 | 01-FEB-08:09 | 2160.55 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 4035.67 | 17-FEB-05:58 |
March | 2010.79 | 01-MAR-10:09 | 2587.92 | 17-MAR-07:10 | 2160.55 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 4958.19 | 17-MAR-04:47 |
April | 2010.79 | 03-APR-09:09 | 1803.00 | 14-APR-07:10 | 2160.55 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 3249.58 | 27-APR-02:00 |
May | 2010.79 | 01-MAY-09:09 | 1803.00 | 03-MAY-07:10 | 2160.55 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 256.90 | 20-MAY-17:02 | 7102.39 | 22-MAY-04:46 |
June | 2010.79 | 01-JUN-09:09 | 1350.81 | 26-JUN-11:30 | 2160.55 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 361.92 | 29-JUN-15:00 | 2617.18 | 14-JUN-02:00 |
July | 2010.79 | 03-JUL-09:09 | 1470.28 | 07-JUL-07:30 | 2160.55 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 703.85 | 30-JUL-11:55 | 1556.26 | 05-JUL-01:00 |
August | 2010.79 | 01-AUG-09:09 | 1470.28 | 17-AUG-07:10 | 2160.55 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 905.13 | 06-AUG-17:24 | 1998.78 | 22-AUG-21:10 |
September | 2010.79 | 01-SEP-09:09 | 2135.72 | 11-SEP-07:10 | 2160.55 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1026.03 | 03-SEP-12:52 | 3222.31 | 12-SEP-03:00 |
October | 2010.79 | 02-OCT-09:09 | 2587.92 | 25-OCT-07:10 | 2160.55 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 395.95 | 15-OCT-14:00 | 3170.66 | 30-OCT-21:03 |
November | 2010.79 | 01-NOV-09:09 | 2587.92 | 01-NOV-07:10 | 2160.55 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 4275.91 | 28-NOV-05:50 |
December | 2010.79 | 01-DEC-10:09 | 2587.92 | 01-DEC-08:09 | 2160.55 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 6155.80 | 01-DEC-05:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.79 | 1350.81 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1556.26 | |||||
Maximum of Months | 2010.79 | 2587.92 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 1026.03 | 7286.41 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 1667.75 | 02-JAN-08:09 | 1392.34 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 4857.34 | 05-JAN-22:01 |
February | 1295.83 | 01-FEB-10:09 | 1453.34 | 01-FEB-16:00 | 1392.34 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 2690.32 | 17-FEB-06:00 |
March | 1295.83 | 01-MAR-10:09 | 1667.75 | 17-MAR-07:10 | 1392.34 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 3305.33 | 17-MAR-04:45 |
April | 1295.83 | 03-APR-09:09 | 1161.92 | 14-APR-07:10 | 1392.34 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 2178.11 | 27-APR-02:00 |
May | 1295.83 | 01-MAY-09:09 | 947.51 | 03-MAY-07:10 | 1392.34 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 210.96 | 20-MAY-17:02 | 4735.00 | 22-MAY-04:48 |
June | 1295.83 | 01-JUN-09:09 | 793.52 | 01-JUN-07:10 | 1392.34 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 241.28 | 29-JUN-15:00 | 1886.97 | 04-JUN-14:00 |
July | 1295.83 | 03-JUL-09:09 | 870.51 | 07-JUL-07:19 | 1392.34 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 527.85 | 30-JUL-11:46 | 1035.40 | 05-JUL-01:00 |
August | 1295.83 | 01-AUG-09:09 | 870.51 | 17-AUG-07:10 | 1392.34 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 650.42 | 06-AUG-17:26 | 1303.63 | 22-AUG-21:10 |
September | 1295.83 | 01-SEP-09:09 | 1161.92 | 13-SEP-07:10 | 1392.34 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 711.17 | 03-SEP-12:51 | 2120.24 | 12-SEP-03:00 |
October | 1295.83 | 02-OCT-09:09 | 1667.75 | 25-OCT-07:10 | 1392.34 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 107.72 | 15-OCT-13:50 | 2115.55 | 30-OCT-21:03 |
November | 1295.83 | 01-NOV-09:09 | 1667.75 | 01-NOV-07:10 | 1392.34 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 2933.79 | 28-NOV-05:49 |
December | 1295.83 | 01-DEC-10:09 | 1667.75 | 01-DEC-08:09 | 1392.34 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 4198.79 | 01-DEC-05:07 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 793.52 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1035.40 | |||||
Maximum of Months | 1295.83 | 1667.75 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 711.17 | 4857.34 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.83 | 02-JAN-10:09 | 2587.98 | 02-JAN-08:09 | 2160.58 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 7289.96 | 05-JAN-22:01 |
February | 2010.83 | 01-FEB-10:09 | 2135.77 | 02-FEB-08:09 | 2160.58 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 4051.59 | 19-FEB-13:00 |
March | 2010.83 | 01-MAR-10:09 | 2587.98 | 17-MAR-07:10 | 2160.58 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 5019.19 | 02-MAR-23:00 |
April | 2010.83 | 03-APR-09:09 | 1803.04 | 14-APR-07:10 | 2160.58 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 3300.48 | 27-APR-02:00 |
May | 2010.83 | 01-MAY-09:09 | 1803.04 | 03-MAY-07:10 | 2160.58 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 263.46 | 20-MAY-17:02 | 7102.17 | 22-MAY-04:44 |
June | 2010.83 | 01-JUN-09:09 | 1350.84 | 16-JUN-07:10 | 2160.58 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 361.92 | 29-JUN-15:00 | 2706.55 | 04-JUN-13:55 |
July | 2010.83 | 03-JUL-09:09 | 1470.31 | 07-JUL-07:30 | 2160.58 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 727.66 | 30-JUL-11:46 | 1576.79 | 05-JUL-01:00 |
August | 2010.83 | 01-AUG-09:09 | 1470.31 | 17-AUG-07:10 | 2160.58 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 935.38 | 06-AUG-17:24 | 2041.97 | 22-AUG-21:10 |
September | 2010.83 | 01-SEP-09:09 | 1803.04 | 11-SEP-07:10 | 2160.58 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 988.95 | 03-SEP-12:57 | 3217.99 | 12-SEP-03:00 |
October | 2010.83 | 02-OCT-09:09 | 2587.98 | 25-OCT-07:10 | 2160.58 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 26.60 | 18-OCT-15:00 | 3212.45 | 30-OCT-21:03 |
November | 2010.83 | 01-NOV-09:09 | 2587.98 | 01-NOV-07:10 | 2160.58 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 4400.74 | 28-NOV-05:50 |
December | 2010.83 | 01-DEC-10:09 | 2587.98 | 01-DEC-08:09 | 2160.58 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 6297.89 | 01-DEC-05:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.83 | 1350.84 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1576.79 | |||||
Maximum of Months | 2010.83 | 2587.98 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 988.95 | 7289.96 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 1667.75 | 02-JAN-08:09 | 1392.33 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 4858.13 | 05-JAN-22:01 |
February | 1295.83 | 01-FEB-10:09 | 1667.75 | 02-FEB-08:09 | 1392.33 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 2690.59 | 17-FEB-06:00 |
March | 1295.83 | 01-MAR-10:09 | 1667.75 | 17-MAR-07:10 | 1392.33 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 3319.64 | 02-MAR-23:00 |
April | 1295.83 | 03-APR-09:09 | 1453.34 | 14-APR-07:10 | 1392.33 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 2221.58 | 27-APR-02:00 |
May | 1295.83 | 01-MAY-09:09 | 1161.92 | 03-MAY-07:10 | 1392.33 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 175.64 | 20-MAY-17:02 | 4734.84 | 22-MAY-04:44 |
June | 1295.83 | 01-JUN-09:09 | 870.51 | 01-JUN-07:10 | 1392.33 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 241.28 | 29-JUN-15:00 | 1789.88 | 14-JUN-02:00 |
July | 1295.83 | 03-JUL-09:09 | 947.51 | 07-JUL-07:19 | 1392.33 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 580.63 | 30-JUL-11:50 | 1138.14 | 05-JUL-01:00 |
August | 1295.83 | 01-AUG-09:09 | 1161.92 | 17-AUG-07:10 | 1392.33 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 620.77 | 06-AUG-12:10 | 1383.34 | 22-AUG-21:10 |
September | 1295.83 | 01-SEP-09:09 | 1453.34 | 11-SEP-07:10 | 1392.33 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 774.51 | 03-SEP-12:51 | 2144.95 | 12-SEP-03:00 |
October | 1295.83 | 02-OCT-09:09 | 1667.75 | 25-OCT-07:10 | 1392.33 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 129.76 | 15-OCT-12:41 | 2127.90 | 30-OCT-21:03 |
November | 1295.83 | 01-NOV-09:09 | 1667.75 | 01-NOV-07:10 | 1392.33 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 2933.79 | 28-NOV-05:47 |
December | 1295.83 | 01-DEC-10:09 | 1667.75 | 01-DEC-08:09 | 1392.33 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 4198.63 | 01-DEC-05:07 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 870.51 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1138.14 | |||||
Maximum of Months | 1295.83 | 1667.75 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 774.51 | 4858.13 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 232.27 | 02-JAN-10:09 | 578.72 | 02-JAN-08:09 | 1948.61 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 232.27 | 01-FEB-10:09 | 578.72 | 01-FEB-08:09 | 3897.21 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 232.27 | 01-MAR-10:09 | 578.72 | 01-MAR-08:09 | 7794.42 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 232.27 | 03-APR-09:09 | 578.72 | 03-APR-07:10 | 7794.42 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 232.27 | 01-MAY-09:09 | 578.72 | 01-MAY-07:10 | 3897.21 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 232.27 | 01-JUN-09:09 | 578.72 | 01-JUN-07:10 | 5845.82 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 232.27 | 03-JUL-09:09 | 578.72 | 03-JUL-07:10 | 7794.42 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 232.27 | 01-AUG-09:09 | 578.72 | 01-AUG-07:10 | 7794.42 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 232.27 | 01-SEP-09:09 | 578.72 | 01-SEP-07:10 | 3897.21 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 232.27 | 02-OCT-09:09 | 578.72 | 02-OCT-07:10 | 5845.82 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 232.27 | 01-NOV-09:09 | 578.72 | 01-NOV-07:10 | 5845.82 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 232.27 | 01-DEC-10:09 | 578.72 | 01-DEC-08:09 | 7794.42 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 232.27 | 578.72 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 232.27 | 578.72 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 232.27 | 02-JAN-10:09 | 578.72 | 02-JAN-08:09 | 1948.61 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 232.27 | 01-FEB-10:09 | 578.72 | 01-FEB-08:09 | 3897.21 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 232.27 | 01-MAR-10:09 | 578.72 | 01-MAR-08:09 | 7794.42 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 232.27 | 03-APR-09:09 | 578.72 | 03-APR-07:10 | 7794.42 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 232.27 | 01-MAY-09:09 | 578.72 | 01-MAY-07:10 | 3897.21 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 232.27 | 01-JUN-09:09 | 578.72 | 01-JUN-07:10 | 5845.82 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 232.27 | 03-JUL-09:09 | 578.72 | 03-JUL-07:10 | 7794.42 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 232.27 | 01-AUG-09:09 | 578.72 | 01-AUG-07:10 | 7794.42 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 232.27 | 01-SEP-09:09 | 578.72 | 01-SEP-07:10 | 3897.21 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 232.27 | 02-OCT-09:09 | 578.72 | 02-OCT-07:10 | 5845.82 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 232.27 | 01-NOV-09:09 | 578.72 | 01-NOV-07:10 | 5845.82 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 232.27 | 01-DEC-10:09 | 578.72 | 01-DEC-08:09 | 7794.42 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 232.27 | 578.72 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 232.27 | 578.72 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 232.27 | 02-JAN-10:09 | 578.72 | 02-JAN-08:09 | 1948.61 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 232.27 | 01-FEB-10:09 | 578.72 | 01-FEB-08:09 | 3897.21 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 232.27 | 01-MAR-10:09 | 578.72 | 01-MAR-08:09 | 7794.42 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 232.27 | 03-APR-09:09 | 578.72 | 03-APR-07:10 | 7794.42 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 232.27 | 01-MAY-09:09 | 578.72 | 01-MAY-07:10 | 3897.21 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 232.27 | 01-JUN-09:09 | 578.72 | 01-JUN-07:10 | 5845.82 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 232.27 | 03-JUL-09:09 | 578.72 | 03-JUL-07:10 | 7794.42 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 232.27 | 01-AUG-09:09 | 578.72 | 01-AUG-07:10 | 7794.42 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 232.27 | 01-SEP-09:09 | 578.72 | 01-SEP-07:10 | 3897.21 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 232.27 | 02-OCT-09:09 | 578.72 | 02-OCT-07:10 | 5845.82 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 232.27 | 01-NOV-09:09 | 578.72 | 01-NOV-07:10 | 5845.82 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 232.27 | 01-DEC-10:09 | 578.72 | 01-DEC-08:09 | 7794.42 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 232.27 | 578.72 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 232.27 | 578.72 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 5027.92 | 02-JAN-10:09 | 6471.01 | 02-JAN-08:09 | 94908.13 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 5027.92 | 01-FEB-10:09 | 6471.01 | 01-FEB-08:09 | 189816.26 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 5027.92 | 01-MAR-10:09 | 6471.01 | 01-MAR-08:09 | 379632.52 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 5027.92 | 03-APR-09:09 | 6471.01 | 03-APR-07:10 | 379632.52 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 5027.92 | 01-MAY-09:09 | 6471.01 | 01-MAY-07:10 | 189816.26 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5027.92 | 01-JUN-09:09 | 6471.01 | 01-JUN-07:10 | 284724.39 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 5027.92 | 03-JUL-09:09 | 6471.01 | 03-JUL-07:10 | 379632.52 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 5027.92 | 01-AUG-09:09 | 6471.01 | 01-AUG-07:10 | 379632.52 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 5027.92 | 01-SEP-09:09 | 6471.01 | 01-SEP-07:10 | 189816.26 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 5027.92 | 02-OCT-09:09 | 6471.01 | 02-OCT-07:10 | 284724.39 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5027.92 | 01-NOV-09:09 | 6471.01 | 01-NOV-07:10 | 284724.39 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 5027.92 | 01-DEC-10:09 | 6471.01 | 01-DEC-08:09 | 379632.52 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 5027.92 | 6471.01 | 94908.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 5027.92 | 6471.01 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 5205.26 | 05-JAN-22:01 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 3478.81 | 17-FEB-04:00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 4117.91 | 02-MAR-23:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 2937.79 | 27-APR-02:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 212.89 | 20-MAY-17:02 | 5832.21 | 22-MAY-04:03 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 231.55 | 29-JUN-15:00 | 2334.85 | 14-JUN-02:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 551.61 | 30-JUL-12:00 | 1374.29 | 05-JUL-01:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 651.14 | 06-AUG-17:51 | 1788.74 | 23-AUG-03:00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 768.46 | 03-SEP-12:51 | 3193.16 | 12-SEP-03:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.56 | 18-OCT-15:00 | 2705.18 | 30-OCT-23:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 3285.08 | 26-NOV-19:52 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 5155.16 | 01-DEC-04:55 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1374.29 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 768.46 | 5832.21 |
Report: PeakSpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 9128.86 | 05-JAN-22:01 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 5863.52 | 17-FEB-04:00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 7163.37 | 02-MAR-23:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 5099.26 | 27-APR-02:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 404.14 | 20-MAY-17:02 | 9976.64 | 22-MAY-04:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 415.37 | 29-JUN-15:00 | 4049.48 | 14-JUN-02:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1088.97 | 30-JUL-12:00 | 2372.95 | 05-JUL-01:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1233.48 | 06-AUG-17:51 | 3064.05 | 23-AUG-03:00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1415.30 | 03-SEP-13:00 | 5533.20 | 12-SEP-03:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.49 | 18-OCT-15:00 | 4590.66 | 30-OCT-22:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 5362.05 | 26-NOV-19:52 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 8289.23 | 01-DEC-04:55 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2372.95 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1415.30 | 9976.64 |
Report: PeakSpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 10323.26 | 05-JAN-22:01 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 5802.41 | 08-FEB-22:01 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 7777.17 | 02-MAR-23:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 5320.18 | 27-APR-02:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 357.03 | 20-MAY-17:02 | 10017.52 | 22-MAY-04:10 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 432.29 | 29-JUN-15:00 | 4167.42 | 14-JUN-02:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 970.20 | 30-JUL-12:00 | 2476.09 | 05-JUL-01:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1141.87 | 06-AUG-17:50 | 3203.45 | 22-AUG-21:03 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1300.23 | 03-SEP-13:00 | 5422.31 | 12-SEP-03:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 4884.98 | 30-OCT-21:03 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 5762.19 | 29-NOV-22:02 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 8311.35 | 01-DEC-05:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2476.09 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1300.23 | 10323.26 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 119041.38 | 02-JAN-04:01 | 0.00 | 10199.39 | 107660.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 119260.94 | 21-FEB-05:11 | 0.00 | 25501.32 | 134575.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 115710.20 | 20-MAR-03:01 | 0.00 | 8924.46 | 94202.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 120077.72 | 10-APR-04:11 | 0.00 | 25501.32 | 134575.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 119032.90 | 22-MAY-03:02 | 0.00 | 7649.54 | 80745.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 118166.47 | 12-JUN-04:12 | 0.00 | 15300.79 | 80745.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 122563.24 | 02-JUL-17:45 | 0.00 | 12749.23 | 134575.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 119010.41 | 14-AUG-04:12 | 0.00 | 12750.66 | 67287.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 122345.05 | 03-SEP-13:58 | 8976.13 | 12749.23 | 134575.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 121499.44 | 02-OCT-04:11 | 0.00 | 22951.19 | 121117.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 120348.34 | 13-NOV-04:01 | 0.00 | 11474.31 | 121117.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 117716.13 | 11-DEC-04:01 | 0.00 | 8924.46 | 94202.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 115710.20 | 0.00 | 7649.54 | 67287.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 122563.24 | 8976.13 | 25501.32 | 134575.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 89272.35 | 02-JAN-05:01 | 0.00 | 16031.39 | 41563.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 90639.00 | 27-FEB-05:11 | 0.00 | 22901.98 | 59376.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 90600.84 | 02-MAR-05:11 | 0.00 | 20611.78 | 53438.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 98180.20 | 10-APR-04:11 | 0.00 | 22901.98 | 59376.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 97307.20 | 30-MAY-04:12 | 0.00 | 13741.19 | 35625.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 96816.16 | 12-JUN-04:12 | 0.00 | 13741.19 | 35625.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 100012.37 | 05-JUL-04:12 | 0.00 | 13741.19 | 35625.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 98499.05 | 28-AUG-04:12 | 0.00 | 13741.19 | 35625.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 102165.59 | 05-SEP-04:13 | 0.00 | 13741.19 | 35625.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 96555.60 | 02-OCT-04:11 | 0.00 | 20611.78 | 53438.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 94278.43 | 06-NOV-04:02 | 0.00 | 6869.83 | 35625.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 90293.88 | 11-DEC-05:01 | 0.00 | 16031.39 | 41563.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 89272.35 | 0.00 | 6869.83 | 35625.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 102165.59 | 0.00 | 22901.98 | 59376.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 21440.08 | 19-JAN-16:57 | 45948.79 | 61833.04 | 51619.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 33650.96 | 28-FEB-17:00 | 15316.26 | 20611.01 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 54523.91 | 24-MAR-05:03 | 6448.95 | 9160.79 | 30589.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 82168.51 | 26-APR-05:02 | 8061.19 | 11450.99 | 38236.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 83821.63 | 30-MAY-04:12 | 0.00 | 13741.19 | 35625.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 86818.05 | 23-JUN-04:12 | 0.00 | 13741.19 | 35625.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 87730.75 | 19-JUL-04:12 | 0.00 | 13741.19 | 35625.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 87988.60 | 14-AUG-04:12 | 0.00 | 11450.99 | 29688.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 87336.45 | 11-SEP-04:12 | 0.00 | 13741.19 | 35625.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 82679.86 | 19-OCT-05:02 | 8061.19 | 11450.99 | 38236.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 68451.95 | 04-NOV-05:02 | 8061.19 | 11450.99 | 38236.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 29509.55 | 07-DEC-16:30 | 30632.53 | 41222.03 | 34413.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 21440.08 | 0.00 | 9160.79 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 87988.60 | 45948.79 | 61833.04 | 51619.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 17906.48 | 13-JAN-17:00 | 30632.53 | 41222.03 | 34413.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 26715.50 | 28-FEB-17:00 | 15316.26 | 20611.01 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 30930.16 | 23-MAR-15:20 | 15316.26 | 20611.01 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 43015.26 | 25-APR-16:00 | 15316.26 | 20611.01 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 78372.42 | 20-MAY-05:02 | 8061.19 | 11450.99 | 38236.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 86102.43 | 21-JUN-04:12 | 0.00 | 13741.19 | 35625.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 85269.20 | 19-JUL-04:12 | 0.00 | 13741.19 | 35625.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 84133.76 | 08-AUG-04:12 | 0.00 | 13741.19 | 35625.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 83269.40 | 05-SEP-04:12 | 0.00 | 13741.19 | 35625.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 40540.77 | 18-OCT-16:00 | 15316.26 | 20611.01 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 29073.16 | 03-NOV-16:00 | 15316.26 | 20611.01 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 20914.22 | 06-DEC-17:00 | 15316.26 | 20611.01 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 17906.48 | 0.00 | 11450.99 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 86102.43 | 30632.53 | 41222.03 | 38236.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2364.60 | 02-JAN-06:02 | 1619.46 | 2300.46 | 7681.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 82.06 |
February | 4185.05 | 27-FEB-16:00 | 1923.11 | 1231.33 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46.22 |
March | 4747.51 | 27-MAR-14:00 | 2010.79 | 1231.33 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 76.82 |
April | 7576.53 | 07-APR-14:00 | 2010.79 | 1231.33 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.07 |
May | 8402.39 | 30-MAY-15:00 | 1923.11 | 1231.33 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 13344.81 | 22-JUN-05:02 | 1012.16 | 684.10 | 4801.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.91 |
July | 18010.64 | 16-JUL-18:31 | 0.00 | 615.62 | 5032.54 | 0.00 | 0.00 | 0.00 | 0.00 | 90.80 | 0.00 |
August | 17569.19 | 06-AUG-16:01 | 809.73 | 547.22 | 5761.47 | 0.00 | 0.00 | 0.00 | 0.00 | 272.49 | 0.00 |
September | 17927.78 | 04-SEP-14:41 | 910.95 | 615.62 | 6481.66 | 0.00 | 0.00 | 0.00 | 0.00 | 120.92 | 0.00 |
October | 6139.04 | 19-OCT-14:30 | 1923.11 | 1231.33 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.32 |
November | 4052.13 | 08-NOV-13:30 | 1923.11 | 1231.33 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 150.57 |
December | 2480.02 | 06-DEC-06:03 | 809.73 | 1150.23 | 3840.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 195.55 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2364.60 | 0.00 | 547.22 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 18010.64 | 2010.79 | 2300.46 | 7681.96 | 0.00 | 0.00 | 0.00 | 0.00 | 272.49 | 195.55 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3197.97 | 15-JAN-10:53 | 260.91 | 176.32 | 1856.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 549.92 |
February | 8066.26 | 27-FEB-09:55 | 2478.65 | 1587.03 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 103.07 |
March | 11611.19 | 28-MAR-09:15 | 2591.66 | 1587.03 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 133.10 |
April | 19149.25 | 16-APR-08:52 | 326.14 | 220.40 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 463.02 |
May | 14582.43 | 19-MAY-08:30 | 1239.33 | 793.52 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.73 |
June | 25209.95 | 25-JUN-08:22 | 391.37 | 264.49 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 112.86 |
July | 26503.63 | 02-JUL-08:41 | 456.59 | 308.57 | 3248.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 111.74 |
August | 26729.74 | 06-AUG-09:21 | 521.82 | 352.65 | 3712.91 | 0.00 | 0.00 | 0.00 | 0.00 | 6.06 | 0.00 |
September | 27686.20 | 04-SEP-08:41 | 521.82 | 352.65 | 3712.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 48.43 |
October | 21438.06 | 15-OCT-09:32 | 326.14 | 220.40 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 366.68 |
November | 7134.91 | 06-NOV-09:35 | 2478.65 | 1587.03 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 54.71 |
December | 3280.92 | 20-DEC-10:05 | 2591.66 | 1587.03 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 115.66 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3197.97 | 260.91 | 176.32 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 27686.20 | 2591.66 | 1587.03 | 3712.91 | 0.00 | 0.00 | 0.00 | 0.00 | 6.06 | 549.92 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 26016.09 | 15-JAN-13:32 | 506.09 | 342.02 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 768.32 |
February | 32274.02 | 26-FEB-13:42 | 607.31 | 410.42 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 497.50 |
March | 32350.49 | 26-MAR-13:22 | 607.31 | 410.42 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 839.52 |
April | 32419.28 | 16-APR-13:32 | 607.31 | 410.42 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 413.54 |
May | 18069.32 | 19-MAY-13:30 | 2010.83 | 1231.36 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 33.82 | 0.00 |
June | 25882.45 | 11-JUN-12:23 | 404.87 | 273.61 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 48.86 |
July | 30904.97 | 16-JUL-13:12 | 607.31 | 410.42 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 41.40 | 0.00 |
August | 31750.73 | 06-AUG-13:21 | 708.53 | 478.83 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 194.62 | 0.00 |
September | 34798.80 | 04-SEP-14:41 | 910.97 | 615.63 | 6481.75 | 0.00 | 0.00 | 0.00 | 0.00 | 61.75 | 0.00 |
October | 36754.57 | 15-OCT-13:31 | 1012.19 | 684.04 | 7201.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 421.10 |
November | 29767.73 | 12-NOV-13:02 | 506.09 | 342.02 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 474.61 |
December | 18278.95 | 17-DEC-13:43 | 404.87 | 273.61 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1320.46 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 18069.32 | 404.87 | 273.61 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 36754.57 | 2010.83 | 1231.36 | 7201.95 | 0.00 | 0.00 | 0.00 | 0.00 | 194.62 | 1320.46 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 5786.22 | 13-JAN-15:30 | 1239.33 | 793.52 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 152.78 |
February | 18839.92 | 26-FEB-16:22 | 326.14 | 220.40 | 2320.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 234.14 |
March | 16003.33 | 12-MAR-16:12 | 326.14 | 220.40 | 2320.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 914.32 |
April | 33209.75 | 16-APR-16:51 | 587.05 | 396.73 | 4177.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 205.62 |
May | 31612.32 | 28-MAY-17:21 | 0.00 | 308.57 | 2522.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 289.19 |
June | 32099.89 | 18-JUN-17:21 | 0.00 | 308.57 | 2522.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.69 |
July | 34439.99 | 16-JUL-17:11 | 0.00 | 396.73 | 3243.14 | 0.00 | 0.00 | 0.00 | 0.00 | 38.62 | 0.00 |
August | 33579.08 | 06-AUG-16:41 | 521.82 | 352.65 | 3712.89 | 0.00 | 0.00 | 0.00 | 0.00 | 137.86 | 0.00 |
September | 35973.69 | 04-SEP-16:01 | 652.28 | 440.81 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 30.82 | 0.00 |
October | 32661.67 | 15-OCT-15:31 | 521.82 | 352.65 | 3712.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 251.41 |
November | 11155.76 | 03-NOV-15:30 | 1239.33 | 793.52 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 61.79 |
December | 9774.76 | 06-DEC-15:30 | 1239.33 | 793.52 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 214.22 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 5786.22 | 0.00 | 220.40 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 35973.69 | 1239.33 | 793.52 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 137.86 | 914.32 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1478.40 | 13-JAN-16:50 | 1923.11 | 2587.92 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 392.39 |
February | 2528.75 | 27-FEB-14:00 | 1923.11 | 1231.33 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 112.03 |
March | 2595.45 | 23-MAR-13:30 | 2010.79 | 1231.33 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 551.73 |
April | 5651.22 | 07-APR-14:30 | 1923.11 | 1231.33 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 60.30 |
May | 7875.94 | 19-MAY-16:00 | 1923.11 | 1231.33 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 178.84 | 0.00 |
June | 12171.82 | 21-JUN-05:02 | 1012.16 | 684.10 | 4801.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 165.23 |
July | 17220.69 | 16-JUL-18:21 | 0.00 | 684.02 | 5591.71 | 0.00 | 0.00 | 0.00 | 0.00 | 180.59 | 0.00 |
August | 16463.47 | 06-AUG-16:01 | 809.73 | 547.22 | 5761.47 | 0.00 | 0.00 | 0.00 | 0.00 | 638.46 | 0.00 |
September | 16919.56 | 04-SEP-12:51 | 708.51 | 478.82 | 5041.29 | 0.00 | 0.00 | 0.00 | 0.00 | 440.82 | 0.00 |
October | 4564.13 | 19-OCT-14:30 | 1923.11 | 1231.33 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 71.64 |
November | 2530.59 | 03-NOV-13:50 | 4021.58 | 2462.66 | 4321.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 180.30 |
December | 1649.57 | 06-DEC-16:20 | 1923.11 | 2587.92 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 537.11 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1478.40 | 0.00 | 478.82 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 17220.69 | 4021.58 | 2587.92 | 5761.47 | 0.00 | 0.00 | 0.00 | 0.00 | 638.46 | 551.73 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2295.13 | 20-JAN-10:00 | 2478.65 | 1587.03 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 635.97 |
February | 5562.18 | 28-FEB-09:55 | 2478.65 | 1587.03 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 159.69 |
March | 9474.68 | 28-MAR-10:10 | 1239.33 | 793.52 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 214.50 |
April | 13543.61 | 25-APR-09:00 | 1239.33 | 793.52 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 98.65 |
May | 15345.69 | 19-MAY-08:50 | 1239.33 | 793.52 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 74.37 |
June | 30517.08 | 25-JUN-08:41 | 587.05 | 396.73 | 4177.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 283.16 |
July | 32371.57 | 02-JUL-09:01 | 652.28 | 440.81 | 4641.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 323.57 |
August | 29379.77 | 06-AUG-09:21 | 521.82 | 352.65 | 3712.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.69 |
September | 29008.65 | 04-SEP-08:51 | 521.82 | 352.65 | 3712.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 93.50 |
October | 9388.81 | 18-OCT-10:10 | 1239.33 | 793.52 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 95.83 |
November | 4996.49 | 03-NOV-10:10 | 1239.33 | 793.52 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 226.46 |
December | 2420.02 | 20-DEC-10:00 | 2478.65 | 1587.03 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 225.61 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2295.13 | 521.82 | 352.65 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.69 | |
Maximum of Months | 32371.57 | 2478.65 | 1587.03 | 4641.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 635.97 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 18766.20 | 15-JAN-13:13 | 404.87 | 273.61 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1880.50 |
February | 34154.52 | 26-FEB-14:01 | 708.53 | 478.83 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1166.22 |
March | 29922.34 | 26-MAR-13:32 | 506.09 | 342.02 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1823.71 |
April | 32240.12 | 16-APR-15:02 | 607.31 | 410.42 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 880.13 |
May | 21763.26 | 14-MAY-13:52 | 607.31 | 410.42 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1653.46 |
June | 30837.93 | 18-JUN-13:42 | 506.09 | 342.02 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 161.79 |
July | 34159.40 | 16-JUL-13:41 | 809.75 | 547.23 | 5761.56 | 0.00 | 0.00 | 0.00 | 0.00 | 84.74 | 0.00 |
August | 33044.87 | 06-AUG-13:21 | 708.53 | 478.83 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 437.18 | 0.00 |
September | 35746.86 | 04-SEP-15:31 | 1012.19 | 684.04 | 7201.95 | 0.00 | 0.00 | 0.00 | 0.00 | 135.77 | 0.00 |
October | 34842.40 | 15-OCT-13:41 | 708.53 | 478.83 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 791.18 |
November | 32522.56 | 12-NOV-12:12 | 607.31 | 410.42 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1162.02 |
December | 16482.54 | 12-DEC-12:40 | 1058.33 | 1231.36 | 1920.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 407.84 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 16482.54 | 404.87 | 273.61 | 1920.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 35746.86 | 1058.33 | 1231.36 | 7201.95 | 0.00 | 0.00 | 0.00 | 0.00 | 437.18 | 1880.50 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3192.61 | 13-JAN-15:50 | 1239.33 | 793.52 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 384.55 |
February | 9066.40 | 28-FEB-16:40 | 1239.33 | 793.52 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 156.78 |
March | 11796.90 | 28-MAR-17:00 | 391.37 | 440.84 | 773.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 356.46 |
April | 30941.82 | 16-APR-16:21 | 521.82 | 352.65 | 3712.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 536.20 |
May | 33753.22 | 28-MAY-17:51 | 0.00 | 440.81 | 3603.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 907.34 |
June | 33791.75 | 18-JUN-17:41 | 0.00 | 440.81 | 3603.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 132.69 |
July | 35712.50 | 16-JUL-17:01 | 0.00 | 440.81 | 3603.49 | 0.00 | 0.00 | 0.00 | 0.00 | 44.89 | 0.00 |
August | 30623.94 | 06-AUG-16:41 | 521.82 | 352.65 | 3712.89 | 0.00 | 0.00 | 0.00 | 0.00 | 335.58 | 0.00 |
September | 34085.64 | 04-SEP-16:11 | 652.28 | 440.81 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 61.53 | 0.00 |
October | 18582.20 | 15-OCT-15:42 | 391.37 | 264.49 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 465.78 |
November | 7009.89 | 03-NOV-15:40 | 1239.33 | 793.52 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 146.90 |
December | 3829.71 | 06-DEC-15:40 | 1239.33 | 793.52 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 492.95 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3192.61 | 0.00 | 264.49 | 773.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 35712.50 | 1239.33 | 793.52 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 335.58 | 907.34 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1450.96 | 14-JAN-17:03 | 404.87 | 575.05 | 2880.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 452.82 |
February | 2273.63 | 27-FEB-13:30 | 1923.11 | 1231.33 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 143.85 |
March | 2389.61 | 23-MAR-13:30 | 2010.79 | 1231.33 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 673.87 |
April | 5505.70 | 07-APR-14:30 | 1923.11 | 1231.33 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 79.94 |
May | 8656.06 | 19-MAY-16:00 | 1923.11 | 1231.33 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 215.48 | 0.00 |
June | 11278.10 | 21-JUN-05:02 | 1012.16 | 684.10 | 4801.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 207.59 |
July | 19700.34 | 02-JUL-18:31 | 0.00 | 684.02 | 5591.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 155.16 |
August | 19360.96 | 06-AUG-16:01 | 809.73 | 547.22 | 5761.47 | 0.00 | 0.00 | 0.00 | 0.00 | 762.55 | 0.00 |
September | 18687.42 | 04-SEP-16:21 | 809.73 | 547.22 | 5761.47 | 0.00 | 0.00 | 0.00 | 0.00 | 292.92 | 0.00 |
October | 4096.42 | 19-OCT-14:40 | 1923.11 | 1231.33 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 89.21 |
November | 2254.93 | 03-NOV-13:30 | 2010.79 | 1231.33 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 221.46 |
December | 1623.57 | 06-DEC-16:20 | 1923.11 | 2587.92 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 649.73 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1450.96 | 0.00 | 547.22 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 19700.34 | 2010.79 | 2587.92 | 5761.47 | 0.00 | 0.00 | 0.00 | 0.00 | 762.55 | 673.87 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2108.18 | 31-JAN-10:30 | 2591.66 | 1587.03 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 605.40 |
February | 3573.99 | 28-FEB-10:30 | 1295.83 | 793.52 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 204.10 |
March | 8055.75 | 28-MAR-09:35 | 2591.66 | 1587.03 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 337.31 |
April | 12590.12 | 25-APR-09:30 | 1295.83 | 793.52 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 132.64 |
May | 14852.45 | 19-MAY-08:50 | 1239.33 | 793.52 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 93.86 |
June | 29381.90 | 25-JUN-08:11 | 521.82 | 352.65 | 3712.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 393.61 |
July | 31924.14 | 02-JUL-08:31 | 652.28 | 440.81 | 4641.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 484.37 |
August | 29405.92 | 06-AUG-09:21 | 521.82 | 352.65 | 3712.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.40 |
September | 25792.94 | 04-SEP-09:02 | 391.37 | 264.49 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.51 |
October | 8529.49 | 18-OCT-09:50 | 1295.83 | 793.52 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 146.07 |
November | 3263.16 | 03-NOV-10:00 | 1295.83 | 793.52 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 286.90 |
December | 2214.00 | 20-DEC-10:20 | 2591.66 | 1587.03 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 327.84 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2108.18 | 391.37 | 264.49 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.40 | |
Maximum of Months | 31924.14 | 2591.66 | 1587.03 | 4641.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 605.40 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 15198.02 | 31-JAN-13:30 | 1923.15 | 1231.36 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 836.36 |
February | 34851.62 | 26-FEB-14:01 | 708.53 | 478.83 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1388.70 |
March | 26175.23 | 26-MAR-14:02 | 607.31 | 410.42 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2129.58 |
April | 21605.86 | 25-APR-13:30 | 2010.83 | 1231.36 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 161.46 |
May | 23409.43 | 14-MAY-14:22 | 506.09 | 342.02 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2227.56 |
June | 32004.87 | 25-JUN-16:11 | 809.75 | 547.23 | 5761.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 269.69 |
July | 34557.39 | 02-JUL-13:12 | 607.31 | 410.42 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 158.77 |
August | 35360.05 | 06-AUG-13:21 | 708.53 | 478.83 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 522.30 | 0.00 |
September | 37751.71 | 03-SEP-12:41 | 809.75 | 547.23 | 5761.56 | 0.00 | 0.00 | 0.00 | 0.00 | 561.01 | 0.00 |
October | 35958.42 | 15-OCT-13:41 | 708.53 | 478.83 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 918.59 |
November | 24041.73 | 03-NOV-13:30 | 2010.83 | 1231.36 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 291.02 |
December | 13579.97 | 12-DEC-14:30 | 2010.83 | 1231.36 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 579.99 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 13579.97 | 506.09 | 342.02 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 37751.71 | 2010.83 | 1231.36 | 5761.56 | 0.00 | 0.00 | 0.00 | 0.00 | 561.01 | 2227.56 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3219.23 | 13-JAN-15:50 | 1239.33 | 793.52 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 470.77 |
February | 8636.47 | 28-FEB-16:40 | 1239.33 | 793.52 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 196.20 |
March | 11585.26 | 28-MAR-17:00 | 391.37 | 440.84 | 773.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 446.15 |
April | 29835.58 | 22-APR-17:41 | 456.59 | 308.57 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 717.59 |
May | 35270.52 | 28-MAY-17:51 | 0.00 | 440.81 | 3603.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1127.34 |
June | 35672.92 | 18-JUN-17:11 | 0.00 | 440.81 | 3603.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 135.77 |
July | 36675.62 | 02-JUL-17:51 | 0.00 | 440.81 | 3603.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 205.36 |
August | 32628.64 | 06-AUG-16:41 | 521.82 | 352.65 | 3712.89 | 0.00 | 0.00 | 0.00 | 0.00 | 398.88 | 0.00 |
September | 32623.29 | 04-SEP-16:21 | 521.82 | 352.65 | 3712.89 | 0.00 | 0.00 | 0.00 | 0.00 | 129.37 | 0.00 |
October | 15053.53 | 15-OCT-16:22 | 326.14 | 220.40 | 2320.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 599.88 |
November | 6512.30 | 03-NOV-15:40 | 1239.33 | 793.52 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 184.44 |
December | 3466.79 | 06-DEC-15:50 | 1239.33 | 793.52 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 592.70 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3219.23 | 0.00 | 220.40 | 773.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 36675.62 | 1239.33 | 793.52 | 3712.89 | 0.00 | 0.00 | 0.00 | 0.00 | 398.88 | 1127.34 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 10818.23 | 06-JAN-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2601.67 |
February | 9873.44 | 04-FEB-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1723.66 |
March | 8763.65 | 04-MAR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1640.95 |
April | 6567.84 | 24-APR-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 93.82 |
May | 8144.18 | 30-MAY-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 172.21 |
June | 8570.88 | 26-JUN-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 148.47 |
July | 10642.96 | 17-JUL-15:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 53.42 | 0.00 |
August | 11652.63 | 07-AUG-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 90.81 |
September | 11999.96 | 05-SEP-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 89.73 |
October | 6145.43 | 16-OCT-15:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 105.10 |
November | 10640.67 | 27-NOV-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3052.66 |
December | 10127.31 | 28-DEC-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2230.34 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 6145.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 11999.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 53.42 | 3052.66 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 15039.52 | 06-JAN-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6364.47 |
February | 13991.63 | 10-FEB-04:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1583.09 |
March | 16331.48 | 04-MAR-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3126.41 |
April | 12546.71 | 29-APR-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3265.82 |
May | 10814.91 | 22-MAY-04:42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9844.06 |
June | 7274.05 | 23-JUN-15:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 76.55 | 0.00 |
July | 8991.64 | 17-JUL-15:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 146.54 | 0.00 |
August | 8928.88 | 07-AUG-15:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 134.57 | 0.00 |
September | 8477.26 | 05-SEP-14:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.67 |
October | 9851.59 | 10-OCT-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2653.20 |
November | 11302.21 | 27-NOV-02:21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4828.66 |
December | 14364.01 | 23-DEC-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3966.79 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 7274.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 16331.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 146.54 | 9844.06 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 341.66 | 14-JAN-13:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 514.03 |
February | 3278.14 | 26-FEB-14:44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 945.70 |
March | 5222.14 | 23-MAR-13:55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1198.69 |
April | 12276.06 | 25-APR-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 185.96 |
May | 17793.21 | 19-MAY-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 183.04 | 0.00 |
June | 20243.87 | 23-JUN-13:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 94.43 | 0.00 |
July | 24012.12 | 17-JUL-14:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.81 | 0.00 |
August | 21733.44 | 07-AUG-15:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 142.35 | 0.00 |
September | 16251.06 | 01-SEP-15:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 142.81 | 0.00 |
October | 9811.65 | 18-OCT-15:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.86 |
November | 2475.42 | 03-NOV-14:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 418.12 |
December | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5183.63 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 24012.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 183.04 | 5183.63 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 2249.31 | 19-JAN-16:50 | 222.14 | 578.72 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 4600.84 | 26-FEB-17:27 | 35.07 | 96.46 | 11691.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6810.82 | 31-MAR-24:00 | 0.00 | 32.15 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 8501.87 | 22-APR-18:10 | 0.00 | 32.15 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 3508.69 | 31-MAY-24:00 | 0.00 | 32.15 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5376.53 | 30-JUN-24:00 | 0.00 | 32.15 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 7270.88 | 31-JUL-23:45 | 0.00 | 64.31 | 15588.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 8528.18 | 03-AUG-18:50 | 23.38 | 192.90 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 3303.90 | 30-SEP-24:00 | 0.00 | 32.15 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 4932.76 | 31-OCT-24:00 | 0.00 | 32.15 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6340.38 | 13-NOV-16:30 | 222.14 | 578.72 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 8084.68 | 06-DEC-16:10 | 222.14 | 578.72 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 2249.31 | 0.00 | 32.15 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 8528.18 | 222.14 | 578.72 | 15588.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 1867.81 | 19-JAN-16:50 | 222.14 | 578.72 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 4220.37 | 28-FEB-17:00 | 222.14 | 578.72 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6212.16 | 28-MAR-17:50 | 23.38 | 192.90 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 8069.72 | 25-APR-18:10 | 23.38 | 192.90 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 3302.64 | 31-MAY-24:00 | 0.00 | 32.15 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5249.46 | 30-JUN-24:00 | 0.00 | 32.15 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 7065.97 | 31-JUL-23:53 | 0.00 | 128.61 | 31177.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 8198.17 | 03-AUG-18:50 | 23.38 | 192.90 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 2873.68 | 30-SEP-23:30 | 0.00 | 32.15 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 4300.32 | 16-OCT-17:00 | 70.15 | 321.51 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5750.11 | 10-NOV-16:30 | 222.14 | 578.72 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 7376.02 | 06-DEC-16:20 | 222.14 | 578.72 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 1867.81 | 0.00 | 32.15 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 8198.17 | 222.14 | 578.72 | 31177.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 1638.36 | 13-JAN-16:30 | 222.14 | 578.72 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 4162.72 | 28-FEB-17:00 | 222.14 | 578.72 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6202.27 | 28-MAR-17:50 | 23.38 | 192.90 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 8133.73 | 25-APR-18:10 | 23.38 | 192.90 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 3221.05 | 31-MAY-23:30 | 0.00 | 32.15 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5234.38 | 30-JUN-23:33 | 0.00 | 96.46 | 17537.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 7049.44 | 31-JUL-23:53 | 0.00 | 128.61 | 31177.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 8260.23 | 03-AUG-18:50 | 23.38 | 192.90 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 3025.79 | 04-SEP-17:51 | 0.00 | 289.38 | 17537.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 4327.09 | 18-OCT-17:00 | 70.15 | 321.51 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5688.57 | 03-NOV-16:00 | 222.14 | 578.72 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 7310.22 | 06-DEC-16:20 | 222.14 | 578.72 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 1638.36 | 0.00 | 32.15 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 8260.23 | 222.14 | 578.72 | 31177.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 92071.65 | 03-JAN-17:00 | 4808.68 | 6471.01 | 94908.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 184356.90 | 28-FEB-17:00 | 4808.68 | 6471.01 | 189816.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 358038.15 | 31-MAR-24:00 | 0.00 | 359.47 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 368316.92 | 25-APR-16:00 | 4808.68 | 6471.01 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 176652.70 | 31-MAY-24:00 | 0.00 | 359.47 | 189816.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 268627.72 | 30-JUN-24:00 | 0.00 | 359.47 | 284724.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 360924.35 | 31-JUL-23:53 | 0.00 | 1437.90 | 1518530.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 383626.60 | 06-AUG-19:52 | 0.00 | 2156.84 | 2277795.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 176028.50 | 30-SEP-24:00 | 0.00 | 359.47 | 189816.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 267971.63 | 31-OCT-24:00 | 0.00 | 359.47 | 284724.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 277147.98 | 06-NOV-16:55 | 9617.36 | 12942.03 | 569448.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 368477.76 | 06-DEC-17:00 | 4808.68 | 6471.01 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 92071.65 | 0.00 | 359.47 | 94908.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 383626.60 | 9617.36 | 12942.03 | 2277795.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.173157E+13 | 1160969.06 | 03-JAN-08:09 | 0.127302E+13 | 2464803.67 | 09-JAN-07:10 |
February | 0.194993E+13 | 1334684.76 | 27-FEB-16:10 | 0.691502E+12 | 1648555.87 | 01-FEB-07:10 |
March | 0.253778E+13 | 1396861.56 | 16-MAR-15:50 | 0.467845E+12 | 1739588.17 | 06-MAR-07:10 |
April | 0.278034E+13 | 1836569.20 | 06-APR-15:00 | 0.178186E+12 | 669964.85 | 29-APR-04:10 |
May | 0.181348E+13 | 1499348.78 | 31-MAY-15:00 | 0.145447E+12 | 783422.13 | 08-MAY-04:10 |
June | 0.229250E+13 | 1737970.09 | 23-JUN-15:50 | 0.717264E+11 | 246804.30 | 16-JUN-06:00 |
July | 0.286898E+13 | 2012126.07 | 17-JUL-15:30 | 0.653639E+11 | 81333.28 | 03-JUL-11:39 |
August | 0.338698E+13 | 2225335.88 | 07-AUG-15:39 | 0.691591E+11 | 199518.38 | 18-AUG-05:10 |
September | 0.180038E+13 | 1568367.43 | 07-SEP-15:09 | 0.851136E+11 | 392322.07 | 20-SEP-05:10 |
October | 0.220065E+13 | 1613674.06 | 18-OCT-15:00 | 0.152728E+12 | 820092.47 | 10-OCT-06:30 |
November | 0.244813E+13 | 1545281.00 | 17-NOV-16:00 | 0.401268E+12 | 1519734.68 | 27-NOV-07:19 |
December | 0.282731E+13 | 1562595.15 | 06-DEC-16:30 | 0.857882E+12 | 1780976.15 | 29-DEC-07:00 |
Annual Sum or Average | 0.286380E+14 | 0.445924E+13 | ||||
Minimum of Months | 0.173157E+13 | 1160969.06 | 0.653639E+11 | 81333.28 | ||
Maximum of Months | 0.338698E+13 | 2225335.88 | 0.127302E+13 | 2464803.67 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [J] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [J] | HUMIDIFIER:ELECTRICITY [J] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 0.337744E+12 | 0.801882E+11 | 0.766053E+12 | 0.164274E+12 | 0.199202E+12 | 0.144654E+11 | 0.00 | 0.848251E+10 | 0.850726E+09 | 0.160315E+12 | 0.00 | 0.00 | 0.00 |
February | 0.299802E+12 | 0.648776E+11 | 0.978954E+12 | 0.148382E+12 | 0.179056E+12 | 0.143861E+11 | 0.00 | 0.271417E+11 | 0.402468E+10 | 0.233306E+12 | 0.00 | 0.00 | 0.00 |
March | 0.352664E+12 | 0.612557E+11 | 0.141687E+13 | 0.164522E+12 | 0.207075E+12 | 0.158312E+11 | 0.00 | 0.457485E+11 | 0.597019E+10 | 0.267840E+12 | 0.00 | 0.00 | 0.00 |
April | 0.312841E+12 | 0.485976E+11 | 0.165903E+13 | 0.158945E+12 | 0.206769E+12 | 0.195792E+11 | 0.00 | 0.909906E+11 | 0.255641E+11 | 0.258029E+12 | 0.00 | 0.00 | 0.00 |
May | 0.335641E+12 | 0.412601E+11 | 0.774844E+12 | 0.164393E+12 | 0.224691E+12 | 0.254446E+11 | 0.00 | 0.585879E+11 | 0.288359E+11 | 0.159780E+12 | 0.00 | 0.00 | 0.00 |
June | 0.332814E+12 | 0.359021E+11 | 0.106252E+13 | 0.159182E+12 | 0.266885E+12 | 0.410171E+11 | 0.00 | 0.187124E+12 | 0.687513E+11 | 0.138303E+12 | 0.00 | 0.00 | 0.00 |
July | 0.312568E+12 | 0.386184E+11 | 0.139340E+13 | 0.164155E+12 | 0.299827E+12 | 0.558253E+11 | 0.00 | 0.384144E+12 | 0.108107E+12 | 0.112335E+12 | 0.00 | 0.00 | 0.00 |
August | 0.348519E+12 | 0.459508E+11 | 0.173200E+13 | 0.164521E+12 | 0.296817E+12 | 0.529599E+11 | 0.00 | 0.413824E+12 | 0.109428E+12 | 0.222965E+12 | 0.00 | 0.00 | 0.00 |
September | 0.314055E+12 | 0.546090E+11 | 0.740713E+12 | 0.158944E+12 | 0.232187E+12 | 0.336199E+11 | 0.00 | 0.106003E+12 | 0.514591E+11 | 0.108790E+12 | 0.00 | 0.00 | 0.00 |
October | 0.329193E+12 | 0.674053E+11 | 0.108340E+13 | 0.164269E+12 | 0.212191E+12 | 0.217831E+11 | 0.00 | 0.566453E+11 | 0.194042E+11 | 0.246358E+12 | 0.00 | 0.00 | 0.00 |
November | 0.330498E+12 | 0.748889E+11 | 0.135889E+13 | 0.159045E+12 | 0.195030E+12 | 0.160253E+11 | 0.00 | 0.456432E+11 | 0.891067E+10 | 0.259199E+12 | 0.00 | 0.00 | 0.00 |
December | 0.327075E+12 | 0.829175E+11 | 0.170972E+13 | 0.164162E+12 | 0.198101E+12 | 0.153465E+11 | 0.00 | 0.559737E+11 | 0.617722E+10 | 0.267840E+12 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.393341E+13 | 0.696471E+12 | 0.146764E+14 | 0.193480E+13 | 0.271783E+13 | 0.326284E+12 | 0.00 | 0.148031E+13 | 0.437484E+12 | 0.243506E+13 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.299802E+12 | 0.359021E+11 | 0.740713E+12 | 0.148382E+12 | 0.179056E+12 | 0.143861E+11 | 0.00 | 0.848251E+10 | 0.850726E+09 | 0.108790E+12 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.352664E+12 | 0.829175E+11 | 0.173200E+13 | 0.164522E+12 | 0.299827E+12 | 0.558253E+11 | 0.00 | 0.413824E+12 | 0.109428E+12 | 0.267840E+12 | 0.00 | 0.00 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [J] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.00 | 0.00 | 0.119686E+13 | 0.00 | 0.761577E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.621599E+12 | 0.00 | 0.699027E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.387646E+12 | 0.00 | 0.801989E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.105967E+12 | 0.00 | 0.722184E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.720158E+11 | 0.00 | 0.734310E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.257300E+10 | 0.00 | 0.691534E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 38294535.48 | 0.00 | 0.653256E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.857104E+09 | 0.00 | 0.683020E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.212011E+11 | 0.00 | 0.639125E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.847521E+11 | 0.00 | 0.679759E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.332071E+12 | 0.00 | 0.691966E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.785284E+12 | 0.00 | 0.725979E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.361086E+13 | 0.00 | 0.848373E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 38294535.48 | 0.00 | 0.639125E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.119686E+13 | 0.00 | 0.801989E+11 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | EXTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum} [W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 385834.94 | 02-JAN-08:09 | 57580.60 | 01-JAN-06:10 | 423497.50 | 02-JAN-08:09 | 118535.44 | 02-JAN-08:20 | 123026.69 | 09-JAN-06:10 | 27151.97 | 25-JAN-06:10 | 0.00 | 01-JAN-00:10 |
February | 370465.36 | 02-FEB-08:09 | 57580.60 | 01-FEB-06:10 | 541788.89 | 01-FEB-08:09 | 118523.41 | 02-FEB-08:20 | 163172.95 | 28-FEB-16:10 | 27546.67 | 01-FEB-06:10 | 0.00 | 01-FEB-00:10 |
March | 385834.94 | 17-MAR-07:10 | 57580.60 | 01-MAR-06:10 | 660080.29 | 01-MAR-08:09 | 118535.44 | 17-MAR-07:19 | 177333.85 | 28-MAR-15:50 | 27160.21 | 04-MAR-06:10 | 0.00 | 01-MAR-00:10 |
April | 358592.75 | 14-APR-07:10 | 57580.60 | 01-APR-05:10 | 778371.69 | 03-APR-07:10 | 118514.13 | 14-APR-07:19 | 233859.44 | 25-APR-15:39 | 25165.60 | 15-APR-05:10 | 0.00 | 01-APR-00:10 |
May | 352283.84 | 03-MAY-07:10 | 57580.60 | 01-MAY-05:10 | 423497.50 | 01-MAY-07:10 | 118509.21 | 03-MAY-07:19 | 277619.55 | 19-MAY-15:30 | 45765.04 | 19-MAY-15:30 | 0.00 | 01-MAY-00:10 |
June | 334771.98 | 16-JUN-07:10 | 57580.60 | 01-JUN-20:10 | 541788.89 | 01-JUN-07:10 | 118495.57 | 16-JUN-07:19 | 306567.18 | 29-JUN-14:30 | 46969.56 | 30-JUN-15:50 | 0.00 | 01-JUN-00:10 |
July | 340801.53 | 07-JUL-07:30 | 57580.60 | 01-JUL-20:30 | 660080.29 | 03-JUL-07:10 | 118500.26 | 07-JUL-07:40 | 358305.73 | 17-JUL-15:20 | 48279.39 | 31-JUL-15:20 | 0.00 | 01-JUL-00:10 |
August | 343374.53 | 17-AUG-07:10 | 57580.60 | 01-AUG-19:00 | 778371.69 | 01-AUG-07:10 | 118502.27 | 17-AUG-07:19 | 352785.87 | 10-AUG-15:39 | 48286.92 | 07-AUG-13:20 | 0.00 | 01-AUG-00:10 |
September | 358968.96 | 11-SEP-07:10 | 57580.60 | 01-SEP-05:10 | 423497.50 | 01-SEP-07:10 | 118514.43 | 11-SEP-07:19 | 294719.39 | 01-SEP-15:00 | 47421.57 | 07-SEP-14:00 | 0.00 | 01-SEP-00:10 |
October | 385834.94 | 25-OCT-07:10 | 57580.60 | 01-OCT-05:10 | 541788.89 | 02-OCT-07:10 | 118535.44 | 25-OCT-07:19 | 208982.75 | 18-OCT-15:00 | 44290.64 | 18-OCT-13:20 | 0.00 | 01-OCT-00:10 |
November | 385834.94 | 01-NOV-07:10 | 57580.60 | 01-NOV-05:10 | 660080.29 | 01-NOV-07:10 | 118535.44 | 01-NOV-07:19 | 167349.98 | 03-NOV-15:30 | 26989.52 | 13-NOV-06:10 | 0.00 | 01-NOV-00:10 |
December | 385834.94 | 01-DEC-08:09 | 57580.60 | 01-DEC-06:10 | 778371.69 | 01-DEC-08:09 | 118535.44 | 01-DEC-08:20 | 123406.52 | 07-DEC-14:09 | 26521.81 | 11-DEC-06:10 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 334771.98 | 57580.60 | 423497.50 | 118495.57 | 123026.69 | 25165.60 | 0.00 | |||||||
Maximum of Months | 385834.94 | 57580.60 | 778371.69 | 118535.44 | 358305.73 | 48286.92 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY {Maximum} [W] | HEATREJECTION:ELECTRICITY {TIMESTAMP} | HUMIDIFIER:ELECTRICITY {Maximum} [W] | HUMIDIFIER:ELECTRICITY {TIMESTAMP} | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 8408.90 | 13-JAN-16:30 | 1716.10 | 13-JAN-15:00 | 97412.76 | 03-JAN-14:00 | 0.00 | 0.00 | 0.00 |
February | 85887.58 | 27-FEB-15:30 | 49248.27 | 27-FEB-13:30 | 100000.00 | 01-FEB-17:19 | 0.00 | 0.00 | 0.00 |
March | 41147.75 | 14-MAR-13:30 | 11190.33 | 14-MAR-13:00 | 100000.00 | 01-MAR-04:10 | 0.00 | 0.00 | 0.00 |
April | 269885.17 | 07-APR-13:00 | 50766.61 | 06-APR-15:00 | 100000.00 | 01-APR-04:19 | 0.00 | 0.00 | 0.00 |
May | 265413.90 | 19-MAY-15:30 | 66400.75 | 19-MAY-11:00 | 100000.00 | 02-MAY-21:10 | 0.00 | 0.00 | 0.00 |
June | 339503.47 | 29-JUN-14:00 | 83553.24 | 06-JUN-14:39 | 100000.00 | 04-JUN-16:49 | 0.00 | 0.00 | 0.00 |
July | 448448.23 | 17-JUL-15:30 | 83553.24 | 13-JUL-12:00 | 100000.00 | 08-JUL-04:30 | 0.00 | 0.00 | 0.00 |
August | 446956.08 | 07-AUG-15:39 | 83553.24 | 05-AUG-12:50 | 100000.00 | 02-AUG-21:10 | 0.00 | 0.00 | 0.00 |
September | 378086.63 | 07-SEP-14:50 | 83553.24 | 02-SEP-12:00 | 100000.00 | 02-SEP-19:10 | 0.00 | 0.00 | 0.00 |
October | 266052.41 | 18-OCT-14:20 | 51333.11 | 18-OCT-14:09 | 100000.00 | 07-OCT-16:10 | 0.00 | 0.00 | 0.00 |
November | 76731.40 | 17-NOV-16:00 | 49295.04 | 17-NOV-16:00 | 100000.00 | 01-NOV-04:30 | 0.00 | 0.00 | 0.00 |
December | 41179.75 | 10-DEC-01:00 | 22855.07 | 10-DEC-01:00 | 100000.00 | 01-DEC-03:20 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 8408.90 | 1716.10 | 97412.76 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 448448.23 | 83553.24 | 100000.00 | 0.00 | 0.00 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY {AT MAX/MIN} [W] | |
January | 1160969.06 | 03-JAN-08:09 | 385834.94 | 423497.50 | 57580.60 | 118337.19 | 87538.78 | 5301.22 | 0.00 | 2754.41 | 307.80 |
February | 1334684.76 | 27-FEB-16:10 | 332294.83 | 541788.89 | 0.00 | 84450.25 | 134400.59 | 23760.06 | 0.00 | 68741.88 | 49248.27 |
March | 1396861.56 | 16-MAR-15:50 | 332294.83 | 660080.29 | 0.00 | 84450.25 | 172719.07 | 23692.90 | 0.00 | 20733.40 | 2890.83 |
April | 1836569.20 | 06-APR-15:00 | 332294.83 | 778371.69 | 0.00 | 84450.25 | 215312.90 | 24007.27 | 0.00 | 251365.65 | 50766.61 |
May | 1499348.78 | 31-MAY-15:00 | 332294.83 | 423497.50 | 0.00 | 84450.25 | 241647.48 | 44167.09 | 0.00 | 223494.49 | 49797.15 |
June | 1737970.09 | 23-JUN-15:50 | 332294.83 | 541788.89 | 0.00 | 84450.25 | 275635.58 | 45812.26 | 0.00 | 305548.44 | 52439.85 |
July | 2012126.07 | 17-JUL-15:30 | 332294.83 | 660080.29 | 0.00 | 84450.25 | 355805.40 | 47493.83 | 0.00 | 448448.23 | 83553.24 |
August | 2225335.88 | 07-AUG-15:39 | 332294.83 | 778371.69 | 0.00 | 84450.25 | 351775.03 | 47934.78 | 0.00 | 446956.08 | 83553.24 |
September | 1568367.43 | 07-SEP-15:09 | 332294.83 | 423497.50 | 0.00 | 84450.25 | 258451.53 | 45452.26 | 0.00 | 340667.83 | 83553.24 |
October | 1613674.06 | 18-OCT-15:00 | 334652.47 | 541788.89 | 0.00 | 84452.08 | 208982.75 | 44127.98 | 0.00 | 248336.76 | 51333.11 |
November | 1545281.00 | 17-NOV-16:00 | 385834.94 | 660080.29 | 57580.60 | 84492.05 | 107537.83 | 23728.85 | 0.00 | 76731.40 | 49295.04 |
December | 1562595.15 | 06-DEC-16:30 | 385834.94 | 778371.69 | 57580.60 | 84478.18 | 102727.81 | 23695.32 | 0.00 | 25361.68 | 4544.93 |
Annual Sum or Average | |||||||||||
Minimum of Months | 1160969.06 | 332294.83 | 423497.50 | 0.00 | 84450.25 | 87538.78 | 5301.22 | 0.00 | 2754.41 | 307.80 | |
Maximum of Months | 2225335.88 | 385834.94 | 778371.69 | 57580.60 | 118337.19 | 355805.40 | 47934.78 | 0.00 | 448448.23 | 83553.24 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS {Maximum} [W] | WATERSYSTEMS:NATURALGAS {TIMESTAMP} | COGENERATION:NATURALGAS [] | |
January | 0.00 | 0.00 | 2431734.33 | 09-JAN-07:10 | 0.00 | 87810.35 | 31-JAN-12:20 | 0.00 |
February | 0.00 | 0.00 | 1615427.92 | 01-FEB-07:10 | 0.00 | 87976.46 | 17-FEB-12:39 | 0.00 |
March | 0.00 | 0.00 | 1707693.71 | 06-MAR-07:10 | 0.00 | 87918.14 | 01-MAR-12:20 | 0.00 |
April | 0.00 | 0.00 | 661818.27 | 29-APR-04:10 | 0.00 | 87064.45 | 03-APR-11:00 | 0.00 |
May | 0.00 | 0.00 | 775275.55 | 08-MAY-04:10 | 0.00 | 85654.71 | 01-MAY-11:30 | 0.00 |
June | 0.00 | 0.00 | 214825.50 | 16-JUN-06:00 | 0.00 | 83510.85 | 01-JUN-11:39 | 0.00 |
July | 0.00 | 0.00 | 7796.79 | 08-JUL-05:10 | 0.00 | 81333.28 | 03-JUL-11:39 | 0.00 |
August | 0.00 | 0.00 | 191371.80 | 18-AUG-05:10 | 0.00 | 79980.28 | 02-AUG-11:50 | 0.00 |
September | 0.00 | 0.00 | 383886.53 | 13-SEP-05:10 | 0.00 | 80853.17 | 28-SEP-11:00 | 0.00 |
October | 0.00 | 0.00 | 788195.09 | 10-OCT-06:30 | 0.00 | 82955.71 | 31-OCT-11:50 | 0.00 |
November | 0.00 | 0.00 | 1498613.25 | 27-NOV-07:19 | 0.00 | 85055.17 | 30-NOV-12:20 | 0.00 |
December | 0.00 | 0.00 | 1748193.03 | 29-DEC-07:00 | 0.00 | 86717.44 | 29-DEC-12:50 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 7796.79 | 0.00 | 79980.28 | 0.00 | ||
Maximum of Months | 0.00 | 0.00 | 2431734.33 | 0.00 | 87976.46 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 3.83 | 27.02 | 0.83 | 27.08 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 25.83 | 0.00 | 25.83 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 26.09 | 0.00 | 26.09 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 25.78 | 0.00 | 25.78 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 26.50 | 0.50 | 26.67 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 26.68 | 0.00 | 26.68 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 5.50 | 26.19 | 0.00 | 26.19 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 5.67 | 26.08 | 0.17 | 26.11 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 4.67 | 26.70 | 0.33 | 26.75 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 9.50 | 26.70 | 0.83 | 26.76 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 26.44 | 0.17 | 26.47 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 25.99 | 0.00 | 25.99 |
Annual Sum or Average | 0.00 | 0.00 | 45.67 | 26.46 | 2.83 | 26.51 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 25.78 | 0.00 | 25.78 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 9.50 | 27.02 | 0.83 | 27.08 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 25.87 | 0.00 | 25.87 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 25.59 | 0.00 | 25.59 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 25.62 | 0.00 | 25.62 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 25.66 | 0.00 | 25.66 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 25.67 | 0.00 | 25.67 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 25.56 | 0.00 | 25.56 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 2.17 | 25.65 | 0.00 | 25.65 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 25.87 | 0.00 | 25.87 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.33 | 18.39 | 0.00 | 18.39 | 0.00 | 18.39 | 0.00 | 18.39 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.33 | 18.39 | 0.00 | 18.39 | 0.00 | 18.39 | 0.00 | 18.39 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.33 | 18.39 | 0.00 | 18.39 | 0.00 | 18.39 | 0.00 | 18.39 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 7.17 | 18.76 | 1.50 | 18.92 | 0.00 | 18.92 | 0.00 | 18.92 |
February | 2.17 | 18.85 | 0.33 | 19.00 | 0.00 | 19.00 | 0.00 | 19.00 |
March | 1.67 | 18.79 | 0.50 | 19.06 | 0.00 | 19.06 | 0.00 | 19.06 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.33 | 19.33 | 0.00 | 19.33 | 0.00 | 19.33 | 0.00 | 19.33 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.33 | 18.61 | 0.00 | 18.61 | 0.00 | 18.61 | 0.00 | 18.61 |
November | 2.00 | 18.71 | 0.17 | 18.82 | 0.00 | 18.82 | 0.00 | 18.82 |
December | 3.50 | 18.55 | 0.17 | 18.63 | 0.00 | 18.63 | 0.00 | 18.63 |
Annual Sum or Average | 17.17 | 18.73 | 2.67 | 18.88 | 0.00 | 18.88 | 0.00 | 18.88 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 7.17 | 19.33 | 1.50 | 19.33 | 0.00 | 19.33 | 0.00 | 19.33 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 6.50 | 18.37 | 1.00 | 18.61 | 0.00 | 18.61 | 0.00 | 18.61 |
February | 1.33 | 19.13 | 0.00 | 19.13 | 0.00 | 19.13 | 0.00 | 19.13 |
March | 0.50 | 18.92 | 0.00 | 18.92 | 0.00 | 18.92 | 0.00 | 18.92 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 27.43 | 1.67 | 27.42 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 27.53 | 1.33 | 27.55 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 27.42 | 2.17 | 27.43 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.33 | 19.17 | 0.00 | 19.17 | 0.00 | 19.17 | 0.00 | 19.17 |
December | 1.00 | 18.92 | 0.00 | 18.92 | 0.00 | 18.92 | 0.00 | 18.92 |
Annual Sum or Average | 9.67 | 18.59 | 1.00 | 18.74 | 7.17 | 22.24 | 5.17 | 23.41 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 6.50 | 19.17 | 1.00 | 19.17 | 2.83 | 27.53 | 2.17 | 27.55 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 7.33 | 17.27 | 0.50 | 17.35 | 0.00 | 17.35 | 0.00 | 17.35 |
February | 1.33 | 18.98 | 0.00 | 18.98 | 0.00 | 18.98 | 0.00 | 18.98 |
March | 0.50 | 18.73 | 0.00 | 18.73 | 0.00 | 18.73 | 0.00 | 18.73 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 28.11 | 1.33 | 28.11 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 5.33 | 28.43 | 5.33 | 28.43 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 9.50 | 28.33 | 9.50 | 28.33 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 4.00 | 28.32 | 3.67 | 28.36 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 6.33 | 28.04 | 6.33 | 28.04 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.64 | 0.83 | 27.64 |
November | 0.33 | 18.97 | 0.00 | 18.97 | 0.00 | 18.97 | 0.00 | 18.97 |
December | 1.17 | 18.77 | 0.00 | 18.77 | 0.00 | 18.77 | 0.00 | 18.77 |
Annual Sum or Average | 10.67 | 17.77 | 0.50 | 17.81 | 27.33 | 25.22 | 27.00 | 26.47 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 7.33 | 18.98 | 0.50 | 18.98 | 9.50 | 28.43 | 9.50 | 28.43 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 8.17 | 17.18 | 0.67 | 17.22 | 1.50 | 18.77 | 1.50 | 19.93 |
February | 1.33 | 18.98 | 0.00 | 18.98 | 3.17 | 25.51 | 3.17 | 26.64 |
March | 0.67 | 18.15 | 0.00 | 18.15 | 1.67 | 25.17 | 1.67 | 26.34 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 27.96 | 3.17 | 27.96 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 27.78 | 1.50 | 27.78 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 4.00 | 27.79 | 4.00 | 27.79 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 9.00 | 28.00 | 8.17 | 28.02 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 5.33 | 28.23 | 4.67 | 28.26 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 8.33 | 28.36 | 7.50 | 28.40 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 4.50 | 28.37 | 4.50 | 28.37 |
November | 0.50 | 18.89 | 0.00 | 18.89 | 2.83 | 26.70 | 2.83 | 27.34 |
December | 1.33 | 18.82 | 0.00 | 18.82 | 0.83 | 22.12 | 0.83 | 23.59 |
Annual Sum or Average | 12.00 | 17.69 | 0.67 | 17.69 | 45.83 | 25.85 | 43.50 | 26.82 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 18.77 | 0.83 | 19.93 |
Maximum of Months | 8.17 | 18.98 | 0.67 | 18.98 | 9.00 | 28.37 | 8.17 | 28.40 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 3.50 | 18.20 | 0.00 | 18.20 | 0.00 | 18.20 | 0.00 | 18.20 |
February | 0.33 | 19.38 | 0.00 | 19.38 | 1.17 | 26.11 | 1.17 | 26.95 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 27.86 | 0.67 | 27.92 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 28.35 | 3.00 | 28.39 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 28.45 | 2.33 | 28.42 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 8.50 | 28.40 | 3.67 | 28.44 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 19.50 | 28.31 | 8.17 | 28.43 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 17.33 | 27.71 | 5.33 | 27.93 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 6.17 | 28.34 | 3.67 | 28.44 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 28.25 | 1.67 | 28.25 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 3.83 | 18.30 | 0.00 | 18.30 | 65.50 | 27.62 | 29.67 | 27.90 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 3.50 | 19.38 | 0.00 | 19.38 | 19.50 | 28.45 | 8.17 | 28.44 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 65.50 | 16.89 | 26.33 | 17.27 | 0.00 | 17.27 | 0.00 | 17.27 |
February | 22.00 | 16.89 | 5.00 | 16.88 | 0.00 | 16.88 | 0.00 | 16.88 |
March | 13.50 | 17.09 | 3.00 | 17.30 | 0.00 | 17.30 | 0.00 | 17.30 |
April | 0.50 | 19.10 | 0.00 | 19.10 | 0.00 | 19.10 | 0.00 | 19.10 |
May | 1.00 | 18.42 | 0.00 | 18.42 | 0.00 | 18.42 | 0.00 | 18.42 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 27.37 | 1.00 | 27.34 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 27.40 | 1.00 | 27.41 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 27.38 | 1.67 | 27.38 |
October | 0.83 | 19.21 | 0.17 | 19.39 | 0.00 | 19.39 | 0.00 | 19.39 |
November | 11.33 | 17.12 | 3.00 | 17.23 | 0.00 | 17.23 | 0.00 | 17.23 |
December | 32.50 | 16.63 | 8.67 | 16.73 | 0.00 | 16.73 | 0.00 | 16.73 |
Annual Sum or Average | 147.17 | 16.90 | 46.17 | 17.13 | 4.67 | 17.37 | 3.67 | 17.55 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 65.50 | 19.21 | 26.33 | 19.39 | 1.67 | 27.40 | 1.67 | 27.41 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 34.00 | 15.32 | 5.67 | 15.22 | 0.00 | 15.22 | 0.00 | 15.22 |
February | 14.17 | 16.09 | 1.00 | 15.99 | 0.00 | 15.99 | 0.00 | 15.99 |
March | 9.67 | 16.41 | 0.83 | 16.37 | 0.00 | 16.37 | 0.00 | 16.37 |
April | 0.50 | 19.02 | 0.00 | 19.02 | 0.83 | 24.59 | 0.83 | 25.87 |
May | 1.00 | 18.40 | 0.00 | 18.40 | 0.00 | 18.40 | 0.00 | 18.40 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 5.50 | 28.50 | 5.50 | 28.50 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 11.00 | 28.43 | 10.67 | 28.45 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 4.00 | 28.57 | 3.67 | 28.60 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 6.00 | 28.10 | 6.00 | 28.10 |
October | 0.67 | 18.97 | 0.00 | 18.97 | 0.00 | 18.97 | 0.00 | 18.97 |
November | 7.50 | 16.59 | 0.50 | 16.49 | 0.00 | 16.49 | 0.00 | 16.49 |
December | 24.33 | 15.77 | 4.17 | 15.61 | 0.00 | 15.61 | 0.00 | 15.61 |
Annual Sum or Average | 91.83 | 15.85 | 12.17 | 15.73 | 27.33 | 18.36 | 26.67 | 20.05 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.22 | 0.00 | 15.22 |
Maximum of Months | 34.00 | 19.02 | 5.67 | 19.02 | 11.00 | 28.57 | 10.67 | 28.60 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 26.83 | 15.76 | 3.33 | 15.70 | 0.67 | 15.97 | 0.67 | 16.22 |
February | 10.67 | 16.75 | 0.67 | 16.62 | 2.33 | 18.67 | 2.33 | 20.12 |
March | 7.67 | 16.60 | 0.67 | 16.57 | 0.83 | 17.63 | 0.83 | 18.52 |
April | 0.50 | 19.10 | 0.00 | 19.10 | 2.33 | 26.40 | 2.33 | 27.11 |
May | 0.83 | 18.77 | 0.00 | 18.77 | 1.17 | 23.97 | 1.17 | 25.34 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 27.78 | 3.33 | 27.78 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 8.33 | 28.05 | 7.50 | 28.07 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 28.26 | 4.33 | 28.30 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 8.17 | 28.57 | 7.17 | 28.62 |
October | 0.33 | 18.77 | 0.00 | 18.77 | 6.00 | 26.80 | 6.00 | 27.02 |
November | 5.33 | 17.24 | 0.00 | 17.24 | 2.33 | 20.61 | 2.33 | 22.41 |
December | 15.33 | 16.34 | 2.50 | 16.12 | 0.00 | 16.12 | 0.00 | 16.12 |
Annual Sum or Average | 67.50 | 16.34 | 7.17 | 16.22 | 40.50 | 20.39 | 38.00 | 22.30 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.97 | 0.00 | 16.12 |
Maximum of Months | 26.83 | 19.10 | 3.33 | 19.10 | 8.33 | 28.57 | 7.50 | 28.62 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 30.17 | 15.45 | 5.17 | 15.34 | 0.00 | 15.34 | 0.00 | 15.34 |
February | 12.67 | 16.45 | 1.17 | 16.31 | 0.00 | 16.31 | 0.00 | 16.31 |
March | 7.83 | 16.59 | 0.50 | 16.61 | 0.00 | 16.61 | 0.00 | 16.61 |
April | 0.50 | 19.27 | 0.00 | 19.27 | 1.33 | 26.15 | 0.67 | 26.92 |
May | 0.67 | 18.74 | 0.00 | 18.74 | 3.83 | 27.06 | 1.33 | 27.37 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 5.33 | 28.56 | 2.00 | 28.61 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 11.33 | 28.75 | 5.00 | 28.80 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 4.83 | 28.54 | 2.50 | 28.56 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 4.67 | 28.56 | 2.67 | 28.65 |
October | 0.50 | 18.98 | 0.00 | 18.98 | 0.50 | 23.69 | 0.50 | 25.27 |
November | 6.17 | 16.82 | 0.00 | 16.82 | 0.00 | 16.82 | 0.00 | 16.82 |
December | 14.17 | 16.33 | 3.00 | 16.00 | 0.00 | 16.00 | 0.00 | 16.00 |
Annual Sum or Average | 72.67 | 16.12 | 9.83 | 15.95 | 31.83 | 19.48 | 14.67 | 20.53 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.34 | 0.00 | 15.34 |
Maximum of Months | 30.17 | 19.27 | 5.17 | 19.27 | 11.33 | 28.75 | 5.00 | 28.80 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 123.17 | 16.16 | 50.17 | 16.58 | 0.00 | 16.58 | 0.00 | 16.58 |
February | 48.17 | 16.71 | 16.00 | 17.00 | 0.00 | 17.00 | 0.00 | 17.00 |
March | 29.33 | 16.53 | 8.17 | 16.67 | 0.00 | 16.67 | 0.00 | 16.67 |
April | 5.00 | 18.21 | 0.67 | 17.99 | 0.00 | 17.99 | 0.00 | 17.99 |
May | 7.50 | 17.49 | 1.00 | 17.61 | 0.00 | 17.61 | 0.00 | 17.61 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 27.53 | 1.67 | 27.51 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 27.67 | 1.17 | 27.69 |
September | 1.17 | 19.11 | 0.00 | 19.11 | 2.33 | 24.74 | 2.17 | 25.82 |
October | 5.50 | 17.82 | 0.33 | 17.95 | 0.00 | 17.95 | 0.00 | 17.95 |
November | 34.50 | 16.21 | 10.33 | 16.33 | 0.00 | 16.33 | 0.00 | 16.33 |
December | 78.00 | 15.97 | 28.67 | 16.16 | 0.00 | 16.16 | 0.00 | 16.16 |
Annual Sum or Average | 332.33 | 16.33 | 115.33 | 16.58 | 7.17 | 16.76 | 5.00 | 16.88 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 123.17 | 19.11 | 50.17 | 19.11 | 3.00 | 27.67 | 2.17 | 27.69 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 60.67 | 14.81 | 12.33 | 14.78 | 0.00 | 14.78 | 0.00 | 14.78 |
February | 27.83 | 15.45 | 3.83 | 15.35 | 0.00 | 15.35 | 0.00 | 15.35 |
March | 20.50 | 15.91 | 3.50 | 15.76 | 0.00 | 15.76 | 0.00 | 15.76 |
April | 3.67 | 18.56 | 0.00 | 18.56 | 0.00 | 18.56 | 0.00 | 18.56 |
May | 4.67 | 16.82 | 0.00 | 16.82 | 0.00 | 16.82 | 0.00 | 16.82 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 5.83 | 28.26 | 5.83 | 28.26 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 12.17 | 28.37 | 11.00 | 28.40 |
August | 0.17 | 19.40 | 0.00 | 19.40 | 4.00 | 28.28 | 3.33 | 28.51 |
September | 1.00 | 19.11 | 0.00 | 19.11 | 5.67 | 26.84 | 5.33 | 27.47 |
October | 4.33 | 17.41 | 0.00 | 17.41 | 0.00 | 17.41 | 0.00 | 17.41 |
November | 21.83 | 15.42 | 3.50 | 15.27 | 0.00 | 15.27 | 0.00 | 15.27 |
December | 54.00 | 14.93 | 13.67 | 14.85 | 0.00 | 14.85 | 0.00 | 14.85 |
Annual Sum or Average | 198.67 | 15.31 | 36.83 | 15.20 | 27.67 | 16.58 | 25.50 | 17.63 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.78 | 0.00 | 14.78 |
Maximum of Months | 60.67 | 19.40 | 13.67 | 19.40 | 12.17 | 28.37 | 11.00 | 28.51 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 51.83 | 15.24 | 9.83 | 15.25 | 0.00 | 15.25 | 0.00 | 15.25 |
February | 21.33 | 15.94 | 1.83 | 15.87 | 1.33 | 16.57 | 1.33 | 17.20 |
March | 17.00 | 16.26 | 1.50 | 16.20 | 0.33 | 16.40 | 0.33 | 16.60 |
April | 3.50 | 18.65 | 0.00 | 18.65 | 1.00 | 20.72 | 1.00 | 22.04 |
May | 4.50 | 16.80 | 0.00 | 16.80 | 1.00 | 18.74 | 1.00 | 20.09 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 27.78 | 3.33 | 27.78 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 8.67 | 28.14 | 7.33 | 28.17 |
August | 0.17 | 19.43 | 0.00 | 19.43 | 5.00 | 28.08 | 4.17 | 28.25 |
September | 0.67 | 19.06 | 0.00 | 19.06 | 8.00 | 27.85 | 6.67 | 28.23 |
October | 3.33 | 17.77 | 0.00 | 17.77 | 2.67 | 22.57 | 2.67 | 24.42 |
November | 15.67 | 16.05 | 2.00 | 15.98 | 0.50 | 16.29 | 0.50 | 16.59 |
December | 40.00 | 15.19 | 7.50 | 15.07 | 0.00 | 15.07 | 0.00 | 15.07 |
Annual Sum or Average | 158.00 | 15.71 | 22.67 | 15.62 | 31.83 | 17.52 | 28.33 | 18.79 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.07 | 0.00 | 15.07 |
Maximum of Months | 51.83 | 19.43 | 9.83 | 19.43 | 8.67 | 28.14 | 7.33 | 28.25 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 54.33 | 14.80 | 11.83 | 14.77 | 0.00 | 14.77 | 0.00 | 14.77 |
February | 21.67 | 15.72 | 2.83 | 15.61 | 0.00 | 15.61 | 0.00 | 15.61 |
March | 16.00 | 16.16 | 1.83 | 16.04 | 0.00 | 16.04 | 0.00 | 16.04 |
April | 2.33 | 18.66 | 0.00 | 18.66 | 1.17 | 21.99 | 0.50 | 22.84 |
May | 3.33 | 16.72 | 0.00 | 16.72 | 3.67 | 22.90 | 1.50 | 23.86 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 28.71 | 1.83 | 28.73 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 10.83 | 28.92 | 4.83 | 28.95 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 4.67 | 28.72 | 2.33 | 28.74 |
September | 0.67 | 19.14 | 0.00 | 19.14 | 5.00 | 27.48 | 2.83 | 27.95 |
October | 2.67 | 18.57 | 0.00 | 18.57 | 0.50 | 20.05 | 0.50 | 21.12 |
November | 17.00 | 15.73 | 3.33 | 15.53 | 0.00 | 15.53 | 0.00 | 15.53 |
December | 42.33 | 15.16 | 10.00 | 15.03 | 0.00 | 15.03 | 0.00 | 15.03 |
Annual Sum or Average | 160.33 | 15.43 | 29.83 | 15.30 | 30.83 | 17.17 | 14.33 | 17.88 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.77 | 0.00 | 14.77 |
Maximum of Months | 54.33 | 19.14 | 11.83 | 19.14 | 10.83 | 28.92 | 4.83 | 28.95 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 9.00 | 28.06 | 4.67 | 28.05 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 9.00 | 28.06 | 4.67 | 28.05 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 9.00 | 28.06 | 4.67 | 28.05 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 27.86 | 2.67 | 27.86 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 5.00 | 27.86 | 2.67 | 27.86 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 27.86 | 2.67 | 27.86 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 6.50 | 27.93 | 2.83 | 27.92 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 6.50 | 27.93 | 2.83 | 27.92 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 6.50 | 27.93 | 2.83 | 27.92 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 112.50 | 30.84 | 105.50 | 30.84 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 112.50 | 30.84 | 105.50 | 30.84 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 112.50 | 30.84 | 105.50 | 30.84 |
Report: ComfortReportSimple55Monthly
For: BASEMENT
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 387.17 | 23.34 | 35.67 | 23.60 | 0.00 | 23.60 |
February | 287.67 | 23.79 | 41.50 | 24.10 | 0.00 | 24.10 |
March | 246.17 | 23.97 | 46.17 | 24.31 | 0.00 | 24.31 |
April | 77.50 | 24.01 | 84.33 | 25.16 | 0.00 | 25.16 |
May | 74.83 | 24.00 | 111.83 | 25.19 | 0.00 | 25.19 |
June | 8.50 | 24.45 | 227.83 | 24.97 | 8.50 | 24.95 |
July | 10.67 | 25.11 | 349.17 | 24.89 | 10.67 | 24.90 |
August | 0.00 | 0.00 | 229.50 | 25.09 | 0.00 | 25.09 |
September | 23.50 | 24.00 | 219.17 | 25.09 | 16.50 | 25.02 |
October | 13.33 | 24.00 | 112.67 | 26.24 | 0.00 | 26.24 |
November | 104.67 | 24.00 | 93.67 | 25.17 | 0.00 | 25.17 |
December | 230.67 | 23.82 | 52.33 | 24.28 | 0.00 | 24.28 |
Annual Sum or Average | 1464.67 | 23.76 | 1603.83 | 24.66 | 35.67 | 24.66 |
Minimum of Months | 0.00 | 0.00 | 35.67 | 23.60 | 0.00 | 23.60 |
Maximum of Months | 387.17 | 25.11 | 349.17 | 26.24 | 16.50 | 26.24 |
Report: ComfortReportSimple55Monthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 427.83 | 23.50 | 10.00 | 23.54 | 1.83 | 23.53 |
February | 309.83 | 23.81 | 2.50 | 23.82 | 0.00 | 23.82 |
March | 233.67 | 23.97 | 20.83 | 24.12 | 0.00 | 24.12 |
April | 70.17 | 23.99 | 59.67 | 24.91 | 0.00 | 24.91 |
May | 86.17 | 23.97 | 91.33 | 24.71 | 0.00 | 24.71 |
June | 6.00 | 24.45 | 239.50 | 24.48 | 5.00 | 24.49 |
July | 3.33 | 24.97 | 370.33 | 24.42 | 3.33 | 24.42 |
August | 0.00 | 0.00 | 286.67 | 24.44 | 0.00 | 24.44 |
September | 35.00 | 24.05 | 206.33 | 24.57 | 14.00 | 24.55 |
October | 43.00 | 23.98 | 79.67 | 25.26 | 0.00 | 25.26 |
November | 146.17 | 23.97 | 47.67 | 24.46 | 0.00 | 24.46 |
December | 262.83 | 23.92 | 14.17 | 24.01 | 0.00 | 24.01 |
Annual Sum or Average | 1624.00 | 23.81 | 1428.67 | 24.26 | 24.17 | 24.26 |
Minimum of Months | 0.00 | 0.00 | 2.50 | 23.54 | 0.00 | 23.53 |
Maximum of Months | 427.83 | 24.97 | 370.33 | 25.26 | 14.00 | 25.26 |
Report: ComfortReportSimple55Monthly
For: CORE_MID
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 22.07 | 119.83 | 21.78 | 119.83 | 21.58 |
February | 449.50 | 22.77 | 32.00 | 22.61 | 32.00 | 22.47 |
March | 496.33 | 23.34 | 17.33 | 23.26 | 17.33 | 23.18 |
April | 328.33 | 23.59 | 0.00 | 23.59 | 0.00 | 23.59 |
May | 229.83 | 23.69 | 52.33 | 23.98 | 0.00 | 23.98 |
June | 73.50 | 23.79 | 156.00 | 24.19 | 6.00 | 24.20 |
July | 31.50 | 24.20 | 278.67 | 24.36 | 7.83 | 24.39 |
August | 16.83 | 23.74 | 162.33 | 24.50 | 0.00 | 24.50 |
September | 135.00 | 23.72 | 138.33 | 24.13 | 14.50 | 24.13 |
October | 297.33 | 23.67 | 4.17 | 23.69 | 0.00 | 23.69 |
November | 435.33 | 23.31 | 11.50 | 23.25 | 11.50 | 23.19 |
December | 497.00 | 22.57 | 70.50 | 22.30 | 70.50 | 22.08 |
Annual Sum or Average | 3492.50 | 23.08 | 1043.00 | 23.19 | 279.50 | 23.06 |
Minimum of Months | 16.83 | 22.07 | 0.00 | 21.78 | 0.00 | 21.58 |
Maximum of Months | 502.00 | 24.20 | 278.67 | 24.50 | 119.83 | 24.50 |
Report: ComfortReportSimple55Monthly
For: CORE_TOP
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.75 | 305.67 | 20.48 | 305.67 | 20.35 |
February | 454.00 | 21.45 | 184.67 | 21.09 | 184.67 | 20.90 |
March | 514.00 | 22.17 | 115.33 | 21.81 | 115.33 | 21.56 |
April | 431.50 | 22.73 | 40.33 | 22.55 | 40.33 | 22.40 |
May | 315.00 | 23.07 | 55.67 | 23.07 | 22.33 | 22.92 |
June | 127.00 | 23.43 | 154.50 | 23.90 | 5.50 | 23.91 |
July | 55.67 | 23.69 | 275.17 | 24.20 | 9.67 | 24.22 |
August | 74.33 | 23.53 | 161.67 | 24.16 | 0.00 | 24.16 |
September | 232.17 | 23.14 | 118.67 | 23.57 | 16.67 | 23.60 |
October | 441.17 | 22.69 | 25.50 | 22.55 | 25.50 | 22.43 |
November | 484.00 | 21.90 | 123.17 | 21.55 | 123.17 | 21.31 |
December | 497.00 | 21.07 | 250.83 | 20.69 | 250.83 | 20.51 |
Annual Sum or Average | 4127.83 | 22.08 | 1811.17 | 22.01 | 1099.67 | 21.73 |
Minimum of Months | 55.67 | 20.75 | 25.50 | 20.48 | 0.00 | 20.35 |
Maximum of Months | 514.00 | 23.69 | 305.67 | 24.20 | 305.67 | 24.22 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.85 | 319.83 | 20.65 | 319.83 | 20.56 |
February | 454.00 | 21.61 | 159.50 | 21.33 | 159.50 | 21.17 |
March | 511.50 | 22.49 | 58.33 | 22.29 | 58.33 | 22.12 |
April | 393.00 | 23.23 | 4.50 | 23.24 | 0.83 | 23.24 |
May | 280.67 | 23.24 | 59.17 | 23.53 | 0.50 | 23.53 |
June | 61.00 | 23.71 | 241.00 | 24.22 | 4.00 | 24.23 |
July | 13.83 | 25.25 | 376.50 | 24.49 | 7.50 | 24.53 |
August | 36.83 | 23.83 | 237.50 | 24.34 | 1.67 | 24.36 |
September | 220.33 | 23.31 | 134.67 | 23.82 | 13.17 | 23.85 |
October | 422.33 | 23.14 | 3.83 | 23.15 | 0.00 | 23.15 |
November | 480.17 | 22.39 | 57.17 | 22.20 | 57.17 | 22.05 |
December | 497.00 | 21.49 | 202.17 | 21.20 | 202.17 | 21.04 |
Annual Sum or Average | 3872.67 | 22.32 | 1854.17 | 22.46 | 824.67 | 22.23 |
Minimum of Months | 13.83 | 20.85 | 3.83 | 20.65 | 0.00 | 20.56 |
Maximum of Months | 511.50 | 25.25 | 376.50 | 24.49 | 319.83 | 24.53 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 498.33 | 20.87 | 312.00 | 20.68 | 312.00 | 20.59 |
February | 425.67 | 21.49 | 170.67 | 21.30 | 163.33 | 21.15 |
March | 445.67 | 21.94 | 86.50 | 21.86 | 67.83 | 21.71 |
April | 323.33 | 22.50 | 67.00 | 22.83 | 7.83 | 22.85 |
May | 230.33 | 22.63 | 128.83 | 23.26 | 1.00 | 23.26 |
June | 109.33 | 23.86 | 292.50 | 24.27 | 24.17 | 24.41 |
July | 63.50 | 25.40 | 395.83 | 24.60 | 37.67 | 24.77 |
August | 101.00 | 23.65 | 312.17 | 24.14 | 14.00 | 24.23 |
September | 215.83 | 23.13 | 193.17 | 23.83 | 28.67 | 23.98 |
October | 354.17 | 22.55 | 36.33 | 22.75 | 1.00 | 22.76 |
November | 466.67 | 21.95 | 81.33 | 21.78 | 78.67 | 21.64 |
December | 495.33 | 21.17 | 231.33 | 20.95 | 231.33 | 20.84 |
Annual Sum or Average | 3729.17 | 22.02 | 2307.67 | 22.39 | 967.50 | 22.22 |
Minimum of Months | 63.50 | 20.87 | 36.33 | 20.68 | 1.00 | 20.59 |
Maximum of Months | 498.33 | 25.40 | 395.83 | 24.60 | 312.00 | 24.77 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 433.17 | 21.13 | 284.83 | 21.01 | 262.67 | 20.86 |
February | 336.33 | 21.80 | 179.17 | 21.87 | 131.00 | 21.68 |
March | 378.33 | 22.11 | 140.67 | 22.24 | 70.50 | 22.07 |
April | 303.83 | 22.65 | 90.00 | 23.00 | 19.17 | 23.02 |
May | 254.33 | 22.62 | 139.67 | 23.18 | 17.33 | 23.12 |
June | 136.50 | 23.60 | 248.50 | 24.12 | 19.00 | 24.22 |
July | 67.50 | 24.97 | 377.00 | 24.55 | 31.33 | 24.70 |
August | 83.00 | 24.06 | 320.00 | 24.32 | 17.83 | 24.43 |
September | 183.67 | 23.40 | 247.83 | 24.12 | 32.83 | 24.29 |
October | 271.50 | 22.88 | 143.67 | 23.43 | 17.00 | 23.52 |
November | 340.67 | 22.22 | 142.50 | 22.46 | 66.00 | 22.31 |
December | 406.83 | 21.48 | 210.00 | 21.41 | 166.33 | 21.19 |
Annual Sum or Average | 3195.67 | 22.28 | 2523.83 | 22.78 | 851.00 | 22.62 |
Minimum of Months | 67.50 | 21.13 | 90.00 | 21.01 | 17.00 | 20.86 |
Maximum of Months | 433.17 | 24.97 | 377.00 | 24.55 | 262.67 | 24.70 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 494.17 | 21.13 | 237.67 | 20.92 | 237.67 | 20.81 |
February | 394.00 | 21.99 | 105.00 | 21.91 | 86.17 | 21.75 |
March | 358.33 | 22.78 | 67.17 | 22.88 | 22.17 | 22.79 |
April | 130.83 | 23.56 | 149.17 | 24.28 | 10.00 | 24.38 |
May | 181.33 | 22.96 | 193.17 | 23.87 | 8.83 | 23.94 |
June | 54.50 | 24.55 | 376.83 | 24.50 | 24.17 | 24.60 |
July | 59.00 | 26.10 | 475.83 | 24.77 | 58.83 | 24.90 |
August | 36.33 | 25.77 | 469.00 | 24.59 | 34.00 | 24.67 |
September | 174.00 | 23.29 | 234.33 | 24.08 | 24.67 | 24.19 |
October | 248.17 | 23.08 | 94.83 | 23.54 | 4.33 | 23.59 |
November | 340.33 | 22.69 | 53.17 | 22.93 | 7.17 | 22.90 |
December | 433.33 | 22.31 | 63.00 | 22.16 | 56.00 | 22.00 |
Annual Sum or Average | 2904.33 | 22.55 | 2519.17 | 23.21 | 574.00 | 23.12 |
Minimum of Months | 36.33 | 21.13 | 53.17 | 20.92 | 4.33 | 20.81 |
Maximum of Months | 494.17 | 26.10 | 475.83 | 24.77 | 237.67 | 24.90 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.87 | 491.33 | 19.86 | 491.33 | 19.86 |
February | 454.00 | 20.36 | 385.00 | 20.28 | 385.00 | 20.24 |
March | 514.00 | 20.91 | 283.67 | 20.67 | 283.67 | 20.55 |
April | 476.17 | 21.90 | 110.33 | 21.61 | 110.33 | 21.42 |
May | 387.50 | 22.50 | 72.67 | 22.43 | 41.17 | 22.23 |
June | 145.67 | 23.20 | 168.33 | 23.76 | 4.50 | 23.77 |
July | 52.67 | 23.71 | 285.67 | 24.31 | 5.17 | 24.33 |
August | 129.67 | 23.24 | 157.33 | 23.88 | 0.67 | 23.89 |
September | 307.17 | 22.51 | 105.33 | 22.90 | 27.17 | 22.85 |
October | 497.00 | 21.85 | 89.00 | 21.63 | 89.00 | 21.46 |
November | 489.00 | 20.72 | 295.00 | 20.48 | 295.00 | 20.37 |
December | 497.00 | 20.01 | 453.67 | 19.96 | 453.67 | 19.94 |
Annual Sum or Average | 4451.83 | 21.25 | 2897.33 | 21.21 | 2186.67 | 20.96 |
Minimum of Months | 52.67 | 19.87 | 72.67 | 19.86 | 0.67 | 19.86 |
Maximum of Months | 514.00 | 23.71 | 491.33 | 24.31 | 491.33 | 24.33 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 427.00 | 19.91 | 401.17 | 19.87 | 401.17 | 19.86 |
February | 378.67 | 20.55 | 278.17 | 20.39 | 277.17 | 20.32 |
March | 416.33 | 21.01 | 207.33 | 20.77 | 203.67 | 20.64 |
April | 327.00 | 21.69 | 105.17 | 21.69 | 75.33 | 21.52 |
May | 265.83 | 22.02 | 106.33 | 22.30 | 35.83 | 22.09 |
June | 139.00 | 23.42 | 216.83 | 24.13 | 26.00 | 24.30 |
July | 87.67 | 24.85 | 312.00 | 24.70 | 41.67 | 24.91 |
August | 118.17 | 23.27 | 236.17 | 24.10 | 14.00 | 24.22 |
September | 242.67 | 22.54 | 139.00 | 23.30 | 32.33 | 23.41 |
October | 386.83 | 21.75 | 68.50 | 21.63 | 59.33 | 21.49 |
November | 414.67 | 20.77 | 233.00 | 20.56 | 233.00 | 20.46 |
December | 422.00 | 19.96 | 374.50 | 19.89 | 374.50 | 19.86 |
Annual Sum or Average | 3625.83 | 21.26 | 2678.17 | 21.47 | 1774.00 | 21.24 |
Minimum of Months | 87.67 | 19.91 | 68.50 | 19.87 | 14.00 | 19.86 |
Maximum of Months | 427.00 | 24.85 | 401.17 | 24.70 | 401.17 | 24.91 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 448.50 | 20.63 | 349.67 | 20.50 | 335.67 | 20.38 |
February | 355.83 | 21.28 | 247.83 | 21.29 | 201.83 | 21.10 |
March | 398.67 | 21.40 | 235.17 | 21.45 | 170.33 | 21.25 |
April | 342.33 | 21.87 | 147.33 | 22.06 | 82.33 | 21.90 |
May | 302.83 | 22.17 | 145.83 | 22.52 | 46.50 | 22.34 |
June | 183.00 | 23.00 | 216.50 | 23.76 | 16.33 | 23.86 |
July | 100.33 | 24.07 | 327.33 | 24.40 | 28.50 | 24.56 |
August | 132.67 | 23.37 | 293.33 | 24.11 | 15.50 | 24.22 |
September | 223.17 | 22.93 | 236.50 | 23.77 | 43.50 | 23.93 |
October | 314.00 | 22.28 | 164.83 | 22.78 | 47.50 | 22.75 |
November | 374.50 | 21.57 | 217.33 | 21.63 | 155.33 | 21.42 |
December | 435.17 | 20.72 | 310.00 | 20.57 | 283.17 | 20.41 |
Annual Sum or Average | 3611.00 | 21.74 | 2891.67 | 22.13 | 1426.50 | 21.89 |
Minimum of Months | 100.33 | 20.63 | 145.83 | 20.50 | 15.50 | 20.38 |
Maximum of Months | 448.50 | 24.07 | 349.67 | 24.40 | 335.67 | 24.56 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.14 | 455.67 | 20.07 | 455.67 | 20.05 |
February | 435.50 | 20.66 | 302.83 | 20.51 | 298.67 | 20.42 |
March | 476.00 | 21.01 | 225.83 | 20.85 | 213.00 | 20.73 |
April | 400.67 | 21.77 | 108.50 | 21.85 | 69.17 | 21.73 |
May | 315.00 | 22.18 | 144.50 | 22.60 | 40.17 | 22.50 |
June | 182.50 | 22.95 | 244.83 | 23.78 | 16.00 | 23.87 |
July | 97.50 | 23.99 | 345.50 | 24.39 | 32.83 | 24.52 |
August | 144.17 | 23.03 | 278.50 | 23.97 | 14.00 | 24.05 |
September | 290.83 | 22.30 | 168.33 | 23.08 | 29.83 | 23.14 |
October | 430.83 | 21.68 | 89.83 | 21.71 | 60.50 | 21.60 |
November | 469.83 | 20.95 | 225.50 | 20.71 | 224.67 | 20.59 |
December | 495.83 | 20.25 | 387.67 | 20.11 | 387.67 | 20.06 |
Annual Sum or Average | 4240.67 | 21.31 | 2977.50 | 21.57 | 1842.17 | 21.34 |
Minimum of Months | 97.50 | 20.14 | 89.83 | 20.07 | 14.00 | 20.05 |
Maximum of Months | 502.00 | 23.99 | 455.67 | 24.39 | 455.67 | 24.52 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.62 | 495.33 | 19.61 | 495.33 | 19.61 |
February | 454.00 | 20.00 | 427.83 | 19.96 | 427.83 | 19.95 |
March | 514.00 | 20.44 | 363.17 | 20.26 | 363.17 | 20.18 |
April | 477.67 | 21.26 | 200.00 | 20.89 | 200.00 | 20.69 |
May | 403.83 | 22.04 | 125.67 | 21.84 | 96.00 | 21.58 |
June | 183.83 | 22.79 | 168.17 | 23.47 | 5.50 | 23.47 |
July | 94.50 | 23.37 | 276.50 | 24.13 | 8.17 | 24.18 |
August | 169.17 | 22.92 | 154.67 | 23.60 | 4.33 | 23.62 |
September | 346.67 | 22.14 | 138.50 | 22.39 | 67.33 | 22.26 |
October | 500.50 | 21.11 | 208.67 | 20.78 | 208.67 | 20.60 |
November | 489.00 | 20.17 | 380.83 | 20.02 | 380.83 | 19.96 |
December | 497.00 | 19.79 | 478.83 | 19.76 | 478.83 | 19.75 |
Annual Sum or Average | 4632.17 | 20.88 | 3418.17 | 20.84 | 2736.00 | 20.61 |
Minimum of Months | 94.50 | 19.62 | 125.67 | 19.61 | 4.33 | 19.61 |
Maximum of Months | 514.00 | 23.37 | 495.33 | 24.13 | 495.33 | 24.18 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.82 | 479.83 | 19.80 | 479.83 | 19.79 |
February | 452.83 | 20.33 | 352.33 | 20.17 | 352.33 | 20.11 |
March | 495.33 | 20.77 | 286.50 | 20.49 | 285.50 | 20.36 |
April | 384.50 | 21.31 | 166.17 | 21.17 | 131.33 | 20.93 |
May | 308.17 | 21.78 | 159.83 | 21.98 | 70.50 | 21.70 |
June | 151.00 | 23.12 | 274.83 | 23.96 | 28.67 | 24.10 |
July | 104.50 | 24.51 | 375.33 | 24.52 | 44.83 | 24.70 |
August | 130.67 | 22.97 | 309.67 | 23.95 | 14.33 | 24.03 |
September | 283.17 | 22.33 | 189.83 | 23.02 | 58.67 | 23.06 |
October | 465.67 | 21.36 | 143.50 | 21.06 | 139.67 | 20.85 |
November | 487.83 | 20.35 | 339.00 | 20.17 | 339.00 | 20.09 |
December | 497.00 | 19.87 | 464.33 | 19.83 | 464.33 | 19.81 |
Annual Sum or Average | 4262.67 | 20.99 | 3541.17 | 21.22 | 2409.00 | 20.98 |
Minimum of Months | 104.50 | 19.82 | 143.50 | 19.80 | 14.33 | 19.79 |
Maximum of Months | 502.00 | 24.51 | 479.83 | 24.52 | 479.83 | 24.70 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 469.00 | 20.33 | 383.67 | 20.15 | 379.33 | 20.06 |
February | 374.83 | 20.86 | 274.83 | 20.74 | 246.50 | 20.58 |
March | 410.67 | 20.86 | 290.50 | 20.86 | 235.50 | 20.65 |
April | 360.50 | 21.31 | 200.50 | 21.35 | 142.33 | 21.10 |
May | 322.83 | 21.75 | 182.83 | 22.01 | 86.67 | 21.74 |
June | 203.67 | 22.62 | 212.67 | 23.48 | 21.50 | 23.56 |
July | 137.67 | 23.59 | 310.33 | 24.20 | 29.83 | 24.36 |
August | 158.33 | 22.98 | 287.17 | 23.89 | 18.50 | 23.98 |
September | 244.50 | 22.48 | 237.50 | 23.29 | 64.67 | 23.33 |
October | 345.33 | 21.62 | 216.33 | 21.85 | 118.00 | 21.63 |
November | 406.50 | 20.98 | 270.83 | 20.91 | 225.00 | 20.69 |
December | 457.00 | 20.34 | 346.67 | 20.12 | 339.83 | 20.01 |
Annual Sum or Average | 3890.83 | 21.31 | 3213.83 | 21.60 | 1907.67 | 21.34 |
Minimum of Months | 137.67 | 20.33 | 182.83 | 20.12 | 18.50 | 20.01 |
Maximum of Months | 469.00 | 23.59 | 383.67 | 24.20 | 379.33 | 24.36 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.89 | 468.50 | 19.84 | 468.50 | 19.82 |
February | 439.00 | 20.36 | 344.83 | 20.22 | 342.00 | 20.16 |
March | 481.33 | 20.68 | 296.50 | 20.51 | 285.17 | 20.40 |
April | 409.67 | 21.30 | 177.67 | 21.26 | 139.83 | 21.07 |
May | 344.67 | 21.90 | 175.17 | 22.19 | 76.67 | 22.00 |
June | 211.50 | 22.64 | 238.50 | 23.56 | 19.33 | 23.64 |
July | 145.50 | 23.54 | 323.00 | 24.19 | 38.83 | 24.33 |
August | 175.83 | 22.73 | 263.83 | 23.74 | 17.33 | 23.81 |
September | 308.00 | 21.99 | 174.83 | 22.65 | 55.00 | 22.64 |
October | 441.17 | 21.18 | 171.83 | 21.04 | 149.50 | 20.87 |
November | 478.33 | 20.54 | 308.50 | 20.32 | 307.83 | 20.22 |
December | 496.33 | 20.00 | 430.50 | 19.90 | 430.50 | 19.87 |
Annual Sum or Average | 4433.33 | 21.03 | 3373.67 | 21.23 | 2330.50 | 21.00 |
Minimum of Months | 145.50 | 19.89 | 171.83 | 19.84 | 17.33 | 19.82 |
Maximum of Months | 502.00 | 23.54 | 468.50 | 24.19 | 468.50 | 24.33 |
Report: ComfortReportSimple55Monthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 1.33 | 26.22 | 388.50 | 27.00 | 0.00 | 27.00 |
February | 4.50 | 27.00 | 436.50 | 27.00 | 4.50 | 27.00 |
March | 9.67 | 27.00 | 509.33 | 27.00 | 9.67 | 27.00 |
April | 35.83 | 27.00 | 485.00 | 27.00 | 35.83 | 27.00 |
May | 5.83 | 27.00 | 508.00 | 27.00 | 5.83 | 27.00 |
June | 52.00 | 27.00 | 496.00 | 27.00 | 52.00 | 27.00 |
July | 168.50 | 27.00 | 497.00 | 27.00 | 168.50 | 27.00 |
August | 238.50 | 27.04 | 514.00 | 27.03 | 238.50 | 27.03 |
September | 21.00 | 27.00 | 485.00 | 27.00 | 21.00 | 27.00 |
October | 13.00 | 27.00 | 502.00 | 27.00 | 13.00 | 27.00 |
November | 10.67 | 27.00 | 489.00 | 27.00 | 10.67 | 27.00 |
December | 4.00 | 27.00 | 491.50 | 27.00 | 4.00 | 27.00 |
Annual Sum or Average | 564.83 | 27.02 | 5801.83 | 27.00 | 563.50 | 27.00 |
Minimum of Months | 1.33 | 26.22 | 388.50 | 27.00 | 0.00 | 27.00 |
Maximum of Months | 238.50 | 27.04 | 514.00 | 27.03 | 238.50 | 27.03 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 116.17 | 25.52 | 195.17 | 26.44 | 0.00 | 26.44 |
February | 14.17 | 27.00 | 302.17 | 27.00 | 0.83 | 27.00 |
March | 10.17 | 27.00 | 457.67 | 27.00 | 2.83 | 27.00 |
April | 6.67 | 27.00 | 478.83 | 27.00 | 6.67 | 27.00 |
May | 2.33 | 27.00 | 496.00 | 27.00 | 2.33 | 27.00 |
June | 11.33 | 27.00 | 496.00 | 27.00 | 11.33 | 27.00 |
July | 41.50 | 27.00 | 497.00 | 27.00 | 41.50 | 27.00 |
August | 58.33 | 27.06 | 514.00 | 27.01 | 58.33 | 27.02 |
September | 9.00 | 27.00 | 485.00 | 27.00 | 9.00 | 27.00 |
October | 4.50 | 27.00 | 502.00 | 27.00 | 4.50 | 27.00 |
November | 0.00 | 0.00 | 442.17 | 27.00 | 0.00 | 27.00 |
December | 17.33 | 27.00 | 335.17 | 27.00 | 0.00 | 27.00 |
Annual Sum or Average | 291.50 | 26.42 | 5201.17 | 26.97 | 137.33 | 26.97 |
Minimum of Months | 0.00 | 0.00 | 195.17 | 26.44 | 0.00 | 26.44 |
Maximum of Months | 116.17 | 27.06 | 514.00 | 27.01 | 58.33 | 27.02 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 259.67 | 24.64 | 129.33 | 25.06 | 27.00 | 24.84 |
February | 46.83 | 26.94 | 198.67 | 26.99 | 0.33 | 26.99 |
March | 24.17 | 27.00 | 360.83 | 27.00 | 2.17 | 27.00 |
April | 7.00 | 27.00 | 423.00 | 27.00 | 7.00 | 27.00 |
May | 26.00 | 25.93 | 474.67 | 26.94 | 5.00 | 26.95 |
June | 26.00 | 27.00 | 496.00 | 27.00 | 26.00 | 27.00 |
July | 71.00 | 27.00 | 497.00 | 27.00 | 71.00 | 27.00 |
August | 81.83 | 27.05 | 514.00 | 27.01 | 81.83 | 27.02 |
September | 14.33 | 27.00 | 473.83 | 27.00 | 14.33 | 27.00 |
October | 4.67 | 27.00 | 454.50 | 27.00 | 4.67 | 27.00 |
November | 22.33 | 27.00 | 327.50 | 27.00 | 0.00 | 27.00 |
December | 65.17 | 27.00 | 212.50 | 27.00 | 0.00 | 27.00 |
Annual Sum or Average | 649.00 | 26.01 | 4561.83 | 26.85 | 239.33 | 26.83 |
Minimum of Months | 4.67 | 24.64 | 129.33 | 25.06 | 0.00 | 24.84 |
Maximum of Months | 259.67 | 27.05 | 514.00 | 27.01 | 81.83 | 27.02 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 274.33 | 27.00 | 502.00 | 27.00 | 274.33 | 27.00 |
February | 454.00 | 27.00 | 454.00 | 27.00 | 454.00 | 27.00 |
March | 514.00 | 27.00 | 514.00 | 27.00 | 514.00 | 27.00 |
April | 485.00 | 27.00 | 485.00 | 27.00 | 485.00 | 27.00 |
May | 498.00 | 27.00 | 508.00 | 27.00 | 498.00 | 27.00 |
June | 496.00 | 27.00 | 496.00 | 27.00 | 496.00 | 27.00 |
July | 497.00 | 27.01 | 497.00 | 27.01 | 497.00 | 27.01 |
August | 514.00 | 27.80 | 514.00 | 27.80 | 514.00 | 27.80 |
September | 485.00 | 27.00 | 485.00 | 27.00 | 485.00 | 27.00 |
October | 502.00 | 27.00 | 502.00 | 27.00 | 502.00 | 27.00 |
November | 489.00 | 27.00 | 489.00 | 27.00 | 489.00 | 27.00 |
December | 497.00 | 27.00 | 497.00 | 27.00 | 497.00 | 27.00 |
Annual Sum or Average | 5705.33 | 27.07 | 5943.00 | 27.07 | 5705.33 | 27.07 |
Minimum of Months | 274.33 | 27.00 | 454.00 | 27.00 | 274.33 | 27.00 |
Maximum of Months | 514.00 | 27.80 | 514.00 | 27.80 | 514.00 | 27.80 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 26.99366 | 13.68642 | 0.61380 | 13.15168 |
February | 454.00000 | 27.00000 | 14.93626 | 0.71183 | 15.86397 |
March | 514.00000 | 26.99999 | 16.92967 | 0.79742 | 18.56317 |
April | 485.00000 | 27.00001 | 20.00657 | 0.89497 | 22.01601 |
May | 508.00000 | 27.00015 | 22.25770 | 0.16002 | 5.75064 |
June | 496.00000 | 27.00044 | 25.63948 | 0.27856 | 6.74613 |
July | 497.00000 | 27.00027 | 26.73265 | 0.35160 | 7.68742 |
August | 514.00000 | 27.01980 | 26.18299 | 0.38997 | 8.34443 |
September | 485.00000 | 27.00051 | 25.36576 | 0.19561 | 6.00081 |
October | 502.00000 | 27.00006 | 22.40331 | 0.84585 | 20.18718 |
November | 489.00000 | 27.00000 | 18.52049 | 0.81262 | 19.05892 |
December | 497.00000 | 26.99999 | 14.86636 | 0.76942 | 17.66073 |
Annual Sum or Average | 5943.00000 | 27.00129 | 20.66615 | 0.56691 | 13.38419 |
Minimum of Months | 454.00000 | 26.99366 | 13.68642 | 0.16002 | 5.75064 |
Maximum of Months | 514.00000 | 27.01980 | 26.73265 | 0.89497 | 22.01601 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 26.61949 | 14.28132 | 0.42316 | 9.72827 |
February | 454.00000 | 27.00000 | 14.92795 | 0.57280 | 12.14888 |
March | 514.00000 | 26.99999 | 16.91356 | 0.64822 | 14.08629 |
April | 485.00000 | 27.00002 | 19.97985 | 0.74449 | 16.88147 |
May | 508.00000 | 27.00014 | 22.27366 | 0.05804 | 5.45303 |
June | 496.00000 | 27.00044 | 25.65531 | 0.17707 | 5.89284 |
July | 497.00000 | 27.00029 | 26.73952 | 0.23990 | 6.40134 |
August | 514.00000 | 27.00722 | 26.19603 | 0.24683 | 6.52232 |
September | 485.00000 | 27.00043 | 25.46104 | 0.10105 | 5.53576 |
October | 502.00000 | 27.00006 | 22.38861 | 0.73306 | 16.46798 |
November | 489.00000 | 27.00000 | 18.49635 | 0.65384 | 14.21358 |
December | 497.00000 | 26.99999 | 14.84141 | 0.56951 | 12.08890 |
Annual Sum or Average | 5943.00000 | 26.96860 | 20.71904 | 0.42906 | 10.42645 |
Minimum of Months | 454.00000 | 26.61949 | 14.28132 | 0.05804 | 5.45303 |
Maximum of Months | 514.00000 | 27.00722 | 26.73952 | 0.74449 | 16.88147 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 25.74121 | 14.55867 | 0.19346 | 8.93895 |
February | 454.00000 | 26.99403 | 14.93016 | 0.50562 | 10.75326 |
March | 514.00000 | 26.99999 | 16.92045 | 0.58495 | 12.59478 |
April | 485.00000 | 27.00002 | 19.99430 | 0.69033 | 15.42222 |
May | 508.00000 | 26.94268 | 22.32890 | -0.0017 | 6.15526 |
June | 496.00000 | 27.00044 | 25.66708 | 0.16477 | 5.99295 |
July | 497.00000 | 27.00029 | 26.74730 | 0.23773 | 6.53085 |
August | 514.00000 | 27.00734 | 26.20321 | 0.23610 | 6.58317 |
September | 485.00000 | 27.00013 | 25.53509 | 0.06281 | 5.66664 |
October | 502.00000 | 27.00006 | 22.40905 | 0.67119 | 14.77282 |
November | 489.00000 | 27.00000 | 18.50758 | 0.57697 | 12.34259 |
December | 497.00000 | 27.00000 | 14.85231 | 0.49505 | 10.53076 |
Annual Sum or Average | 5943.00000 | 26.88903 | 20.76099 | 0.36650 | 9.67279 |
Minimum of Months | 454.00000 | 25.74121 | 14.55867 | -0.0017 | 5.66664 |
Maximum of Months | 514.00000 | 27.00734 | 26.74730 | 0.69033 | 15.42222 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 27.00044 | 30.00052 | 1.00083 | 26.19844 |
February | 454.00000 | 27.00056 | 27.27741 | 1.16755 | 33.70395 |
March | 514.00000 | 27.00025 | 22.26342 | 1.28766 | 39.64855 |
April | 485.00000 | 27.00092 | 21.67948 | 1.42918 | 47.08530 |
May | 508.00000 | 27.00053 | 29.12657 | 0.48120 | 9.89094 |
June | 496.00000 | 27.00230 | 29.65981 | 0.72930 | 16.23169 |
July | 497.00000 | 27.00687 | 30.17705 | 0.95216 | 24.17595 |
August | 514.00000 | 27.80467 | 27.22763 | 1.33811 | 41.77133 |
September | 485.00000 | 27.00064 | 31.09587 | 0.54616 | 11.34216 |
October | 502.00000 | 27.00052 | 27.22089 | 1.22927 | 36.70064 |
November | 489.00000 | 27.00028 | 22.62407 | 1.31641 | 41.12600 |
December | 497.00000 | 27.00030 | 19.57038 | 1.40014 | 45.52933 |
Annual Sum or Average | 5943.00000 | 27.07073 | 26.49146 | 1.07290 | 31.11118 |
Minimum of Months | 454.00000 | 27.00025 | 19.57038 | 0.48120 | 9.89094 |
Maximum of Months | 514.00000 | 27.80467 | 31.09587 | 1.42918 | 47.08530 |
Report: OccupantComfortDataSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.77324 | 12.27318 | 0.10996 | 6.75156 |
February | 454.00000 | 24.20556 | 13.93910 | 0.22482 | 6.66284 |
March | 514.00000 | 24.29978 | 14.94001 | 0.26598 | 6.78829 |
April | 485.00000 | 24.46793 | 18.55649 | 0.33344 | 7.69292 |
May | 508.00000 | 24.48387 | 22.27994 | -0.4891 | 11.03118 |
June | 496.00000 | 24.46063 | 31.01580 | -0.4137 | 9.44693 |
July | 497.00000 | 24.62577 | 35.45832 | -0.3239 | 8.56093 |
August | 514.00000 | 24.48908 | 30.62183 | -0.3895 | 9.15033 |
September | 485.00000 | 24.55174 | 30.19335 | -0.3905 | 9.36885 |
October | 502.00000 | 24.58344 | 20.75692 | 0.38774 | 8.72556 |
November | 489.00000 | 24.55968 | 16.18378 | 0.34131 | 7.95228 |
December | 497.00000 | 24.32434 | 13.30506 | 0.25928 | 6.96828 |
Annual Sum or Average | 5943.00000 | 24.40258 | 21.67646 | -0.0098 | 8.27159 |
Minimum of Months | 454.00000 | 23.77324 | 12.27318 | -0.4891 | 6.66284 |
Maximum of Months | 514.00000 | 24.62577 | 35.45832 | 0.38774 | 11.03118 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.66768 | 13.83982 | 0.06871 | 5.99840 |
February | 454.00000 | 24.00084 | 15.34314 | 0.18010 | 6.02654 |
March | 514.00000 | 24.19782 | 16.23991 | 0.25546 | 6.57039 |
April | 485.00000 | 24.33213 | 19.64186 | 0.32931 | 7.52468 |
May | 508.00000 | 24.32815 | 23.59173 | -0.5196 | 11.28840 |
June | 496.00000 | 24.24691 | 32.34513 | -0.4413 | 9.43807 |
July | 497.00000 | 24.31666 | 36.36704 | -0.3761 | 8.43903 |
August | 514.00000 | 24.25453 | 31.72794 | -0.4182 | 8.97372 |
September | 485.00000 | 24.30465 | 31.44746 | -0.4508 | 9.84049 |
October | 502.00000 | 24.36740 | 22.33253 | 0.34921 | 7.82842 |
November | 489.00000 | 24.35119 | 17.68554 | 0.30045 | 7.14096 |
December | 497.00000 | 24.19645 | 14.71725 | 0.23035 | 6.41446 |
Annual Sum or Average | 5943.00000 | 24.21458 | 22.98889 | -0.0436 | 7.97220 |
Minimum of Months | 454.00000 | 23.66768 | 13.83982 | -0.5196 | 5.99840 |
Maximum of Months | 514.00000 | 24.36740 | 36.36704 | 0.34921 | 11.28840 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.07471 | 15.20168 | -0.3381 | 9.15737 |
February | 454.00000 | 22.78068 | 17.32296 | -0.1414 | 6.87486 |
March | 514.00000 | 23.36802 | 18.09266 | 0.02132 | 6.04026 |
April | 485.00000 | 23.79467 | 21.27668 | 0.16417 | 5.97431 |
May | 508.00000 | 24.05046 | 24.53600 | -0.6531 | 14.82213 |
June | 496.00000 | 24.11534 | 32.92105 | -0.5259 | 11.16139 |
July | 497.00000 | 24.22468 | 36.90355 | -0.4526 | 9.73168 |
August | 514.00000 | 24.19819 | 32.14652 | -0.4939 | 10.41013 |
September | 485.00000 | 24.10450 | 32.18516 | -0.5547 | 12.10324 |
October | 502.00000 | 23.90234 | 23.98447 | 0.20727 | 6.15759 |
November | 489.00000 | 23.40510 | 19.62266 | 0.03660 | 6.01004 |
December | 497.00000 | 22.56913 | 16.81260 | -0.1961 | 7.80427 |
Annual Sum or Average | 5943.00000 | 23.55435 | 24.29304 | -0.2456 | 8.87639 |
Minimum of Months | 454.00000 | 22.07471 | 15.20168 | -0.6531 | 5.97431 |
Maximum of Months | 514.00000 | 24.22468 | 36.90355 | 0.20727 | 14.82213 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.75344 | 15.73703 | -0.6869 | 17.95798 |
February | 454.00000 | 21.44787 | 18.24518 | -0.4853 | 12.63143 |
March | 514.00000 | 22.16741 | 19.49370 | -0.2859 | 9.58156 |
April | 485.00000 | 22.88290 | 22.91534 | -0.0669 | 7.01091 |
May | 508.00000 | 23.52119 | 25.43831 | -0.8457 | 22.67904 |
June | 496.00000 | 23.96099 | 33.09811 | -0.5770 | 12.86522 |
July | 497.00000 | 24.14194 | 36.90921 | -0.4717 | 10.19975 |
August | 514.00000 | 24.10898 | 32.27599 | -0.5254 | 11.32186 |
September | 485.00000 | 23.71875 | 33.19162 | -0.6994 | 17.35114 |
October | 502.00000 | 22.84930 | 26.15360 | -0.0608 | 6.74433 |
November | 489.00000 | 21.92427 | 21.35827 | -0.3395 | 10.36043 |
December | 497.00000 | 21.06987 | 17.88001 | -0.5845 | 15.86759 |
Annual Sum or Average | 5943.00000 | 22.72227 | 25.26462 | -0.4696 | 12.89231 |
Minimum of Months | 454.00000 | 20.75344 | 15.73703 | -0.8457 | 6.74433 |
Maximum of Months | 514.00000 | 24.14194 | 36.90921 | -0.0608 | 22.67904 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.84658 | 14.33971 | -0.6618 | 16.53983 |
February | 454.00000 | 21.61181 | 16.50782 | -0.4286 | 10.92482 |
March | 514.00000 | 22.50146 | 17.29336 | -0.1892 | 7.54091 |
April | 485.00000 | 23.39024 | 20.31777 | 0.06512 | 5.96234 |
May | 508.00000 | 23.72694 | 23.92402 | -0.7467 | 19.00358 |
June | 496.00000 | 24.16353 | 31.81119 | -0.4640 | 10.32046 |
July | 497.00000 | 24.37482 | 35.45029 | -0.3349 | 8.25228 |
August | 514.00000 | 24.21157 | 31.22546 | -0.4427 | 9.83485 |
September | 485.00000 | 23.86219 | 31.80432 | -0.6389 | 15.94272 |
October | 502.00000 | 23.28867 | 23.34984 | 0.05019 | 5.86742 |
November | 489.00000 | 22.42525 | 18.96714 | -0.1997 | 7.53558 |
December | 497.00000 | 21.48804 | 15.97694 | -0.4570 | 11.39913 |
Annual Sum or Average | 5943.00000 | 23.00080 | 23.45593 | -0.3711 | 10.76692 |
Minimum of Months | 454.00000 | 20.84658 | 14.33971 | -0.7467 | 5.86742 |
Maximum of Months | 514.00000 | 24.37482 | 35.45029 | 0.06512 | 19.00358 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.90037 | 13.40405 | -0.6383 | 16.10586 |
February | 454.00000 | 21.68130 | 15.49602 | -0.3865 | 10.96282 |
March | 514.00000 | 22.23934 | 16.55407 | -0.2056 | 8.47293 |
April | 485.00000 | 23.06895 | 20.06404 | 0.05611 | 7.42029 |
May | 508.00000 | 23.49934 | 23.55495 | -0.7188 | 19.62178 |
June | 496.00000 | 24.09957 | 31.64410 | -0.3605 | 10.78778 |
July | 497.00000 | 24.33835 | 35.31686 | -0.2069 | 8.53587 |
August | 514.00000 | 24.02837 | 31.23849 | -0.3755 | 10.35106 |
September | 485.00000 | 23.73362 | 31.56750 | -0.5771 | 16.39396 |
October | 502.00000 | 23.03374 | 22.93449 | 0.04240 | 6.78962 |
November | 489.00000 | 22.05543 | 18.42357 | -0.2581 | 8.24324 |
December | 497.00000 | 21.17689 | 15.33895 | -0.5207 | 12.51387 |
Annual Sum or Average | 5943.00000 | 22.82960 | 23.00694 | -0.3462 | 11.35914 |
Minimum of Months | 454.00000 | 20.90037 | 13.40405 | -0.7188 | 6.78962 |
Maximum of Months | 514.00000 | 24.33835 | 35.31686 | 0.05611 | 19.62178 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.59666 | 13.05950 | -0.4481 | 14.79545 |
February | 454.00000 | 22.46994 | 14.80137 | -0.1597 | 11.00130 |
March | 514.00000 | 22.65566 | 16.11682 | -0.0818 | 9.03306 |
April | 485.00000 | 23.22906 | 19.91468 | 0.09140 | 7.85712 |
May | 508.00000 | 23.45009 | 23.71752 | -0.7667 | 21.89243 |
June | 496.00000 | 24.00564 | 31.89997 | -0.4578 | 11.93896 |
July | 497.00000 | 24.31213 | 35.41020 | -0.2746 | 8.67744 |
August | 514.00000 | 24.15955 | 30.98564 | -0.3319 | 9.62075 |
September | 485.00000 | 23.93813 | 31.11842 | -0.4626 | 14.95272 |
October | 502.00000 | 23.48901 | 22.17555 | 0.19602 | 8.69327 |
November | 489.00000 | 22.87266 | 17.53918 | -0.0286 | 9.05418 |
December | 497.00000 | 22.01057 | 14.63755 | -0.2944 | 11.73790 |
Annual Sum or Average | 5943.00000 | 23.18694 | 22.66377 | -0.2532 | 11.61934 |
Minimum of Months | 454.00000 | 21.59666 | 13.05950 | -0.7667 | 7.85712 |
Maximum of Months | 514.00000 | 24.31213 | 35.41020 | 0.19602 | 21.89243 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.17971 | 13.02462 | -0.5368 | 13.31125 |
February | 454.00000 | 22.29664 | 14.70733 | -0.1959 | 8.69434 |
March | 514.00000 | 23.21231 | 15.43492 | 0.06390 | 7.03120 |
April | 485.00000 | 24.15857 | 18.62131 | 0.36462 | 9.04135 |
May | 508.00000 | 23.86853 | 23.00549 | -0.5505 | 15.40753 |
June | 496.00000 | 24.30887 | 31.21471 | -0.2400 | 8.34796 |
July | 497.00000 | 24.57905 | 34.77908 | -0.0594 | 7.47018 |
August | 514.00000 | 24.44547 | 30.35747 | -0.1321 | 7.27496 |
September | 485.00000 | 23.95638 | 31.00367 | -0.4609 | 13.56581 |
October | 502.00000 | 23.71431 | 21.80352 | 0.23714 | 7.53469 |
November | 489.00000 | 23.22280 | 16.96397 | 0.06007 | 6.95093 |
December | 497.00000 | 22.55936 | 13.93183 | -0.1408 | 7.60956 |
Annual Sum or Average | 5943.00000 | 23.46584 | 22.11682 | -0.1329 | 9.35403 |
Minimum of Months | 454.00000 | 21.17971 | 13.02462 | -0.5505 | 6.95093 |
Maximum of Months | 514.00000 | 24.57905 | 34.77908 | 0.36462 | 15.40753 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.87437 | 14.43245 | -0.9891 | 27.93966 |
February | 454.00000 | 20.36153 | 17.39970 | -0.7958 | 20.23160 |
March | 514.00000 | 20.90937 | 18.80336 | -0.6019 | 14.78498 |
April | 485.00000 | 21.93365 | 22.60563 | -0.2970 | 9.00712 |
May | 508.00000 | 22.91032 | 25.36512 | -1.0430 | 31.15512 |
June | 496.00000 | 23.86642 | 32.55758 | -0.5950 | 13.92550 |
July | 497.00000 | 24.21079 | 35.72444 | -0.4292 | 9.90135 |
August | 514.00000 | 23.96098 | 31.80717 | -0.5738 | 13.27586 |
September | 485.00000 | 23.17872 | 33.18732 | -0.8893 | 25.82514 |
October | 502.00000 | 21.87531 | 25.63358 | -0.2973 | 8.63652 |
November | 489.00000 | 20.71718 | 20.60721 | -0.6457 | 16.29772 |
December | 497.00000 | 20.01317 | 17.05672 | -0.8966 | 24.49220 |
Annual Sum or Average | 5943.00000 | 21.99757 | 24.63894 | -0.6708 | 17.94722 |
Minimum of Months | 454.00000 | 19.87437 | 14.43245 | -1.0430 | 8.63652 |
Maximum of Months | 514.00000 | 24.21079 | 35.72444 | -0.2970 | 31.15512 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 427.00000 | 19.90659 | 13.25445 | -0.9626 | 26.82436 |
February | 385.00000 | 20.61550 | 15.91575 | -0.7061 | 18.28350 |
March | 433.00000 | 21.13535 | 17.14510 | -0.5164 | 13.73953 |
April | 410.00000 | 22.20392 | 21.00221 | -0.1774 | 9.32500 |
May | 430.00000 | 22.86859 | 24.33387 | -0.9624 | 29.49608 |
June | 418.00000 | 23.94713 | 31.70455 | -0.4377 | 13.84503 |
July | 422.00000 | 24.37342 | 34.88527 | -0.2262 | 9.96901 |
August | 433.00000 | 23.99163 | 30.84292 | -0.4286 | 12.66123 |
September | 410.00000 | 23.26871 | 32.21296 | -0.7626 | 24.13284 |
October | 427.00000 | 21.98296 | 24.12711 | -0.2317 | 8.44162 |
November | 417.00000 | 20.79273 | 19.09167 | -0.6086 | 15.04137 |
December | 422.00000 | 19.95795 | 15.74577 | -0.8953 | 24.41386 |
Annual Sum or Average | 5034.00000 | 22.09562 | 23.38699 | -0.5761 | 17.18302 |
Minimum of Months | 385.00000 | 19.90659 | 13.25445 | -0.9626 | 8.44162 |
Maximum of Months | 433.00000 | 24.37342 | 34.88527 | -0.1774 | 29.49608 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.03350 | 13.00512 | -0.6254 | 19.27081 |
February | 454.00000 | 21.95323 | 15.15038 | -0.3072 | 14.05273 |
March | 514.00000 | 22.02398 | 16.79053 | -0.2492 | 11.75607 |
April | 485.00000 | 22.56726 | 20.95007 | -0.0767 | 9.33806 |
May | 508.00000 | 23.00783 | 24.45817 | -0.9248 | 28.45904 |
June | 496.00000 | 23.73780 | 32.45246 | -0.5616 | 15.43218 |
July | 497.00000 | 24.18105 | 35.58587 | -0.3382 | 10.37405 |
August | 514.00000 | 24.01101 | 31.16050 | -0.4032 | 12.01030 |
September | 485.00000 | 23.65346 | 31.62779 | -0.5558 | 19.21207 |
October | 502.00000 | 22.99972 | 23.00822 | 0.08041 | 9.62421 |
November | 489.00000 | 22.21360 | 18.20414 | -0.2049 | 11.72763 |
December | 497.00000 | 21.15916 | 15.32030 | -0.5400 | 17.26547 |
Annual Sum or Average | 5943.00000 | 22.71730 | 23.19156 | -0.3938 | 14.89672 |
Minimum of Months | 454.00000 | 21.03350 | 13.00512 | -0.9248 | 9.33806 |
Maximum of Months | 514.00000 | 24.18105 | 35.58587 | 0.08041 | 28.45904 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.13810 | 13.46681 | -0.8950 | 24.30917 |
February | 454.00000 | 20.80581 | 16.01718 | -0.6401 | 16.88144 |
March | 514.00000 | 21.23666 | 17.45568 | -0.4735 | 12.85044 |
April | 485.00000 | 22.19274 | 21.32151 | -0.1639 | 8.86156 |
May | 508.00000 | 22.96072 | 24.46062 | -0.9008 | 28.24505 |
June | 496.00000 | 23.71320 | 32.49550 | -0.5092 | 14.85682 |
July | 497.00000 | 24.16321 | 35.66990 | -0.2970 | 10.30513 |
August | 514.00000 | 23.89946 | 31.44336 | -0.4453 | 12.83028 |
September | 485.00000 | 23.10856 | 32.58375 | -0.7900 | 25.10541 |
October | 502.00000 | 22.03362 | 24.31508 | -0.2003 | 8.44077 |
November | 489.00000 | 21.07259 | 19.24678 | -0.5197 | 13.60324 |
December | 497.00000 | 20.25876 | 15.94744 | -0.8012 | 21.33720 |
Annual Sum or Average | 5943.00000 | 22.14288 | 23.74655 | -0.5528 | 16.46882 |
Minimum of Months | 454.00000 | 20.13810 | 13.46681 | -0.9008 | 8.44077 |
Maximum of Months | 514.00000 | 24.16321 | 35.66990 | -0.1639 | 28.24505 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.62008 | 14.42353 | -1.1076 | 33.13303 |
February | 454.00000 | 20.00283 | 17.58260 | -0.9321 | 25.75859 |
March | 514.00000 | 20.44131 | 19.22718 | -0.7568 | 19.85474 |
April | 485.00000 | 21.30479 | 23.36906 | -0.4706 | 13.16920 |
May | 508.00000 | 22.48692 | 25.92346 | -1.2022 | 37.66138 |
June | 496.00000 | 23.64041 | 32.90155 | -0.6690 | 17.18033 |
July | 497.00000 | 24.07606 | 35.92416 | -0.4661 | 11.36593 |
August | 514.00000 | 23.76655 | 32.12410 | -0.6364 | 15.96088 |
September | 485.00000 | 22.76011 | 33.98728 | -1.0420 | 32.71167 |
October | 502.00000 | 21.12181 | 26.77017 | -0.5026 | 13.21289 |
November | 489.00000 | 20.16887 | 21.28495 | -0.8268 | 22.42018 |
December | 497.00000 | 19.78559 | 17.04504 | -1.0183 | 29.41448 |
Annual Sum or Average | 5943.00000 | 21.61179 | 25.08774 | -0.8019 | 22.63272 |
Minimum of Months | 454.00000 | 19.62008 | 14.42353 | -1.2022 | 11.36593 |
Maximum of Months | 514.00000 | 24.07606 | 35.92416 | -0.4661 | 37.66138 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.82465 | 13.87099 | -1.0325 | 29.86467 |
February | 454.00000 | 20.34063 | 16.58417 | -0.8090 | 21.80319 |
March | 514.00000 | 20.88733 | 18.00478 | -0.6042 | 16.70665 |
April | 485.00000 | 21.89423 | 21.75020 | -0.2683 | 11.62837 |
May | 508.00000 | 22.71640 | 24.78572 | -1.0176 | 31.28629 |
June | 496.00000 | 23.84883 | 31.96504 | -0.4481 | 14.41813 |
July | 497.00000 | 24.24967 | 35.24712 | -0.2278 | 9.97151 |
August | 514.00000 | 23.89794 | 31.27113 | -0.4259 | 13.08160 |
September | 485.00000 | 23.11096 | 32.80984 | -0.8173 | 26.34606 |
October | 502.00000 | 21.55176 | 25.31213 | -0.3532 | 11.02499 |
November | 489.00000 | 20.35849 | 20.31273 | -0.7506 | 19.72080 |
December | 497.00000 | 19.86570 | 16.37408 | -0.9759 | 27.73608 |
Annual Sum or Average | 5943.00000 | 21.89170 | 24.06580 | -0.6433 | 19.44859 |
Minimum of Months | 454.00000 | 19.82465 | 13.87099 | -1.0325 | 9.97151 |
Maximum of Months | 514.00000 | 24.24967 | 35.24712 | -0.2278 | 31.28629 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.58785 | 13.35062 | -0.7806 | 23.68211 |
February | 454.00000 | 21.45039 | 15.61024 | -0.4707 | 17.29854 |
March | 514.00000 | 21.52399 | 17.35637 | -0.4080 | 15.29747 |
April | 485.00000 | 22.07753 | 21.63052 | -0.2220 | 12.17750 |
May | 508.00000 | 22.66682 | 24.95337 | -1.0603 | 33.72513 |
June | 496.00000 | 23.53291 | 32.74375 | -0.6295 | 18.51629 |
July | 497.00000 | 24.02029 | 35.84193 | -0.3817 | 12.15250 |
August | 514.00000 | 23.83657 | 31.45025 | -0.4589 | 14.43616 |
September | 485.00000 | 23.35861 | 32.27801 | -0.6729 | 24.02366 |
October | 502.00000 | 22.41544 | 24.00156 | -0.0886 | 11.49117 |
November | 489.00000 | 21.53228 | 19.05711 | -0.4085 | 14.93784 |
December | 497.00000 | 20.63481 | 15.72869 | -0.7172 | 21.88014 |
Annual Sum or Average | 5943.00000 | 22.30993 | 23.71476 | -0.5261 | 18.32180 |
Minimum of Months | 454.00000 | 20.58785 | 13.35062 | -1.0603 | 11.49117 |
Maximum of Months | 514.00000 | 24.02029 | 35.84193 | -0.0886 | 33.72513 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.88837 | 13.73758 | -1.0062 | 29.00279 |
February | 454.00000 | 20.48764 | 16.33830 | -0.7575 | 20.90662 |
March | 514.00000 | 20.89275 | 17.87651 | -0.5937 | 16.47873 |
April | 485.00000 | 21.75528 | 21.91164 | -0.2922 | 11.50861 |
May | 508.00000 | 22.64413 | 24.89970 | -1.0244 | 33.14192 |
June | 496.00000 | 23.50962 | 32.76350 | -0.5748 | 17.77666 |
July | 497.00000 | 23.99903 | 35.92640 | -0.3408 | 12.04184 |
August | 514.00000 | 23.71637 | 31.73375 | -0.5027 | 15.30747 |
September | 485.00000 | 22.81830 | 33.20655 | -0.9017 | 30.07660 |
October | 502.00000 | 21.52955 | 25.18175 | -0.3472 | 11.22284 |
November | 489.00000 | 20.61825 | 19.91928 | -0.6694 | 18.03117 |
December | 497.00000 | 20.00426 | 16.14299 | -0.9153 | 25.66096 |
Annual Sum or Average | 5943.00000 | 21.83349 | 24.18069 | -0.6601 | 20.09097 |
Minimum of Months | 454.00000 | 19.88837 | 13.73758 | -1.0244 | 11.22284 |
Maximum of Months | 514.00000 | 23.99903 | 35.92640 | -0.2922 | 33.14192 |
Report: ChillerReportMonthly
For: COOLSYS1 CHILLER1
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportCHILLER ELECTRICITY ENERGY [J] | CHILLER ELECTRICITY RATE {Maximum} [W] | CHILLER ELECTRICITY RATE {TIMESTAMP} | CHILLER ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | CHILLER EVAPORATOR COOLING ENERGY [J] | CHILLER EVAPORATOR COOLING RATE [] | CHILLER CONDENSER HEAT TRANSFER ENERGY [J] | CHILLER COP [W/W] | CHILLER COP {Maximum} [W/W] | CHILLER COP {TIMESTAMP} | CHILLER PART LOAD RATIO [] | CHILLER PART LOAD RATIO [] | |
January | 18273799.18 | 1177.11 | 25-JAN-04:21 | 4.35 | 78217765.57 | 0.00 | 96491564.76 | 0.03 | 4.29 | 25-JAN-06:40 | 0.00 | 0.00 |
February | 0.143497E+10 | 66128.62 | 27-FEB-15:30 | 45.31 | 0.776568E+10 | 0.00 | 0.920065E+10 | 0.30 | 6.54 | 27-FEB-15:30 | 0.00 | 0.00 |
March | 0.355077E+09 | 22028.09 | 14-MAR-13:30 | 64.14 | 0.151985E+10 | 0.00 | 0.187493E+10 | 0.37 | 4.29 | 24-MAR-13:30 | 0.00 | 0.00 |
April | 0.117660E+11 | 121946.72 | 06-APR-16:00 | 133.40 | 0.678267E+11 | 0.00 | 0.795927E+11 | 0.88 | 7.55 | 06-APR-16:00 | 0.00 | 0.00 |
May | 0.326488E+11 | 154532.05 | 19-MAY-12:00 | 204.39 | 0.204291E+12 | 0.00 | 0.236940E+12 | 1.48 | 7.57 | 19-MAY-17:30 | 0.00 | 0.00 |
June | 0.829297E+11 | 156542.91 | 23-JUN-08:40 | 364.21 | 0.551774E+12 | 0.00 | 0.634703E+12 | 3.00 | 7.57 | 19-JUN-12:40 | 0.00 | 0.00 |
July | 0.124915E+12 | 156237.04 | 18-JUL-09:00 | 494.27 | 0.859517E+12 | 0.00 | 0.984432E+12 | 4.14 | 7.57 | 28-JUL-12:50 | 0.00 | 0.00 |
August | 0.110163E+12 | 157787.67 | 05-AUG-12:30 | 473.24 | 0.757192E+12 | 0.00 | 0.867355E+12 | 3.84 | 7.57 | 29-AUG-16:10 | 0.00 | 0.00 |
September | 0.596555E+11 | 167706.74 | 07-SEP-14:50 | 294.63 | 0.393393E+12 | 0.00 | 0.453048E+12 | 2.36 | 7.57 | 05-SEP-11:30 | 0.00 | 0.00 |
October | 0.181489E+11 | 136643.66 | 18-OCT-13:00 | 157.20 | 0.111463E+12 | 0.00 | 0.129612E+12 | 1.06 | 7.57 | 18-OCT-12:10 | 0.00 | 0.00 |
November | 0.161016E+10 | 48478.96 | 03-NOV-14:00 | 73.65 | 0.687386E+10 | 0.00 | 0.848401E+10 | 0.44 | 4.39 | 03-NOV-14:00 | 0.00 | 0.00 |
December | 0.159675E+09 | 1232.47 | 28-DEC-00:33 | 37.71 | 0.683494E+09 | 0.00 | 0.843169E+09 | 0.22 | 4.29 | 20-DEC-11:50 | 0.00 | 0.00 |
Annual Sum or Average | 0.443805E+12 | 2346.50 | 0.296238E+13 | 0.00 | 0.340618E+13 | 1.52 | 0.00 | 0.00 | ||||
Minimum of Months | 18273799.18 | 1177.11 | 4.35 | 78217765.57 | 0.00 | 96491564.76 | 0.03 | 4.29 | 0.00 | 0.00 | ||
Maximum of Months | 0.124915E+12 | 167706.74 | 494.27 | 0.859517E+12 | 0.00 | 0.984432E+12 | 4.14 | 7.57 | 0.00 | 0.00 |
Report: ChillerReportMonthly
For: COOLSYS1 CHILLER2
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportCHILLER ELECTRICITY ENERGY [J] | CHILLER ELECTRICITY RATE {Maximum} [W] | CHILLER ELECTRICITY RATE {TIMESTAMP} | CHILLER ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | CHILLER EVAPORATOR COOLING ENERGY [J] | CHILLER EVAPORATOR COOLING RATE [] | CHILLER CONDENSER HEAT TRANSFER ENERGY [J] | CHILLER COP [W/W] | CHILLER COP {Maximum} [W/W] | CHILLER COP {TIMESTAMP} | CHILLER PART LOAD RATIO [] | CHILLER PART LOAD RATIO [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 |
May | 0.190259E+10 | 100899.13 | 19-MAY-15:30 | 5.83 | 0.138177E+11 | 0.00 | 0.157203E+11 | 0.06 | 7.40 | 19-MAY-15:30 | 0.00 | 0.00 |
June | 0.207054E+11 | 111473.88 | 29-JUN-14:50 | 61.83 | 0.150388E+12 | 0.00 | 0.171094E+12 | 0.62 | 7.50 | 29-JUN-14:50 | 0.00 | 0.00 |
July | 0.434963E+11 | 132003.26 | 17-JUL-15:30 | 124.33 | 0.318113E+12 | 0.00 | 0.361609E+12 | 1.21 | 7.55 | 25-JUL-15:20 | 0.00 | 0.00 |
August | 0.366064E+11 | 127008.05 | 07-AUG-09:20 | 105.75 | 0.268150E+12 | 0.00 | 0.304756E+12 | 1.03 | 7.56 | 07-AUG-09:20 | 0.00 | 0.00 |
September | 0.105502E+11 | 167706.74 | 07-SEP-14:50 | 31.17 | 0.761166E+11 | 0.00 | 0.866667E+11 | 0.31 | 7.49 | 02-SEP-10:50 | 0.00 | 0.00 |
October | 0.791911E+09 | 105649.51 | 18-OCT-13:40 | 2.58 | 0.567913E+10 | 0.00 | 0.647105E+10 | 0.02 | 7.42 | 18-OCT-13:40 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.114053E+12 | 331.50 | 0.832264E+12 | 0.00 | 0.946317E+12 | 0.27 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.434963E+11 | 167706.74 | 124.33 | 0.318113E+12 | 0.00 | 0.361609E+12 | 1.21 | 7.56 | 0.00 | 0.00 |
Report: TowerReportMonthly
For: CENTRAL TOWER
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportCOOLING TOWER FAN ELECTRICITY ENERGY [J] | COOLING TOWER FAN ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | COOLING TOWER FAN ELECTRICITY RATE {Maximum} [W] | COOLING TOWER FAN ELECTRICITY RATE {TIMESTAMP} | COOLING TOWER HEAT TRANSFER RATE {Maximum} [W] | COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} | COOLING TOWER INLET TEMPERATURE [C] | COOLING TOWER OUTLET TEMPERATURE [C] | COOLING TOWER MASS FLOW RATE [kg/s] | |
January | 0.850726E+09 | 744.00 | 1716.10 | 13-JAN-16:00 | 39733.81 | 13-JAN-16:30 | 18.59 | 18.33 | 15.44 |
February | 0.402468E+10 | 672.00 | 49248.27 | 27-FEB-13:30 | 91207.22 | 27-FEB-16:00 | 19.26 | 18.33 | 15.44 |
March | 0.597019E+10 | 744.00 | 11190.33 | 14-MAR-14:00 | 110181.10 | 31-MAR-23:30 | 19.87 | 18.33 | 15.44 |
April | 0.255280E+11 | 720.00 | 49248.27 | 01-APR-13:10 | 563998.36 | 07-APR-14:00 | 21.42 | 18.68 | 15.44 |
May | 0.285594E+11 | 744.00 | 49248.27 | 02-MAY-11:40 | 246286.35 | 20-MAY-17:02 | 19.71 | 18.96 | 15.44 |
June | 0.648461E+11 | 720.00 | 49248.27 | 01-JUN-14:50 | 505783.32 | 20-JUN-19:00 | 23.80 | 21.27 | 15.44 |
July | 0.100665E+12 | 744.00 | 49248.27 | 01-JUL-00:10 | 666193.86 | 19-JUL-10:50 | 31.30 | 25.31 | 15.44 |
August | 0.106294E+12 | 744.00 | 49248.27 | 01-AUG-00:03 | 757163.23 | 05-AUG-19:01 | 32.42 | 24.85 | 15.44 |
September | 0.489625E+11 | 720.00 | 49248.27 | 01-SEP-00:05 | 333573.02 | 07-SEP-16:00 | 21.29 | 20.22 | 15.44 |
October | 0.193157E+11 | 744.00 | 49248.27 | 12-OCT-10:40 | 320530.93 | 18-OCT-15:00 | 19.84 | 18.60 | 15.44 |
November | 0.891022E+10 | 720.00 | 49248.27 | 04-NOV-13:20 | 182604.51 | 17-NOV-17:00 | 19.88 | 18.33 | 15.44 |
December | 0.617722E+10 | 744.00 | 22855.07 | 10-DEC-02:00 | 186302.37 | 10-DEC-02:00 | 20.24 | 18.33 | 15.44 |
Annual Sum or Average | 0.420104E+12 | 8760.00 | 22.33 | 19.98 | 15.44 | ||||
Minimum of Months | 0.850726E+09 | 672.00 | 1716.10 | 39733.81 | 18.59 | 18.33 | 15.44 | ||
Maximum of Months | 0.106294E+12 | 744.00 | 49248.27 | 757163.23 | 32.42 | 25.31 | 15.44 |
Report: TowerReportMonthly
For: TOWERWATERSYS COOLTOWER 1
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportCOOLING TOWER FAN ELECTRICITY ENERGY [J] | COOLING TOWER FAN ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | COOLING TOWER FAN ELECTRICITY RATE {Maximum} [W] | COOLING TOWER FAN ELECTRICITY RATE {TIMESTAMP} | COOLING TOWER HEAT TRANSFER RATE {Maximum} [W] | COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} | COOLING TOWER INLET TEMPERATURE [C] | COOLING TOWER OUTLET TEMPERATURE [C] | COOLING TOWER MASS FLOW RATE [kg/s] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 230116.96 | 25-JAN-06:15 | 21.08 | 21.08 | 0.02 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 510389.08 | 27-FEB-15:30 | 20.87 | 20.85 | 0.88 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 230187.05 | 21-MAR-05:20 | 20.94 | 20.94 | 0.36 |
April | 36139931.55 | 40.45 | 1518.34 | 06-APR-16:00 | 1049719.40 | 06-APR-16:00 | 21.13 | 20.99 | 5.57 |
May | 0.256328E+09 | 129.67 | 17152.48 | 19-MAY-12:00 | 1314995.02 | 19-MAY-12:00 | 21.50 | 21.11 | 12.19 |
June | 0.268633E+10 | 291.68 | 17152.48 | 06-JUN-14:40 | 1320852.70 | 23-JUN-16:10 | 22.24 | 21.14 | 26.84 |
July | 0.492284E+10 | 414.15 | 17152.48 | 01-JUL-12:30 | 1315456.05 | 06-JUL-10:30 | 22.84 | 21.17 | 36.13 |
August | 0.216831E+10 | 356.00 | 17152.48 | 05-AUG-10:55 | 1328338.77 | 01-AUG-12:00 | 22.56 | 21.09 | 32.19 |
September | 0.175174E+10 | 217.70 | 17152.48 | 02-SEP-09:50 | 1344537.59 | 07-SEP-15:00 | 21.98 | 21.20 | 20.35 |
October | 80406408.21 | 65.09 | 1652.21 | 18-OCT-12:20 | 1169560.22 | 18-OCT-13:00 | 21.19 | 20.97 | 7.69 |
November | 448699.96 | 4.17 | 74.22 | 03-NOV-14:00 | 272973.97 | 03-NOV-14:00 | 20.94 | 20.92 | 1.31 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 230253.47 | 29-DEC-02:30 | 20.90 | 20.90 | 0.23 |
Annual Sum or Average | 0.119025E+11 | 1518.91 | 21.52 | 21.03 | 12.05 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 230116.96 | 20.87 | 20.85 | 0.02 | ||
Maximum of Months | 0.492284E+10 | 414.15 | 17152.48 | 1344537.59 | 22.84 | 21.20 | 36.13 |
Report: TowerReportMonthly
For: TOWERWATERSYS COOLTOWER 2
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportCOOLING TOWER FAN ELECTRICITY ENERGY [J] | COOLING TOWER FAN ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | COOLING TOWER FAN ELECTRICITY RATE {Maximum} [W] | COOLING TOWER FAN ELECTRICITY RATE {TIMESTAMP} | COOLING TOWER HEAT TRANSFER RATE {Maximum} [W] | COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} | COOLING TOWER INLET TEMPERATURE [C] | COOLING TOWER OUTLET TEMPERATURE [C] | COOLING TOWER MASS FLOW RATE [kg/s] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 21.08 | 21.08 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 20.87 | 20.87 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 20.94 | 20.94 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 21.13 | 21.13 | 0.00 |
May | 20098944.20 | 5.17 | 2453.88 | 19-MAY-16:40 | 1204920.68 | 19-MAY-14:30 | 21.50 | 21.47 | 0.40 |
June | 0.121893E+10 | 54.17 | 17152.48 | 06-JUN-14:40 | 1213592.52 | 30-JUN-14:10 | 22.24 | 21.93 | 4.38 |
July | 0.251931E+10 | 113.67 | 17152.48 | 13-JUL-13:00 | 1213138.55 | 20-JUL-14:10 | 22.84 | 22.19 | 8.89 |
August | 0.965898E+09 | 96.67 | 17152.48 | 05-AUG-12:50 | 1213535.35 | 30-AUG-14:40 | 22.56 | 22.01 | 7.56 |
September | 0.744876E+09 | 28.83 | 17152.48 | 02-SEP-13:00 | 1344537.59 | 07-SEP-15:00 | 21.98 | 21.81 | 2.33 |
October | 8132835.80 | 2.33 | 1268.03 | 18-OCT-13:40 | 1115400.26 | 18-OCT-13:25 | 21.19 | 21.18 | 0.18 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 20.94 | 20.94 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 20.90 | 20.90 | 0.00 |
Annual Sum or Average | 0.547724E+10 | 300.83 | 21.52 | 21.37 | 2.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 20.87 | 20.87 | 0.00 | ||
Maximum of Months | 0.251931E+10 | 113.67 | 17152.48 | 1344537.59 | 22.84 | 22.19 | 8.89 |
Report: BoilerReportMonthly
For: HEATSYS1 BOILER
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportBOILER HEATING ENERGY [J] | BOILER GAS CONSUMPTION [] | BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] | BOILER HEATING RATE {Maximum} [W] | BOILER HEATING RATE {TIMESTAMP} | BOILER GAS CONSUMPTION RATE [] | BOILER INLET TEMPERATURE [C] | BOILER OUTLET TEMPERATURE [C] | BOILER MASS FLOW RATE [kg/s] | BOILER ANCILLARY ELECTRICITY RATE [W] | BOILER PART LOAD RATIO [] | BOILER PART LOAD RATIO {Maximum} [] | BOILER PART LOAD RATIO {TIMESTAMP} | |
January | 0.957188E+12 | 0.00 | 619.25 | 2138250.95 | 23-JAN-05:11 | 0.00 | 33.51 | 73.00 | 2.00 | 0.00 | 0.10 | 0.62 | 23-JAN-05:11 |
February | 0.484638E+12 | 0.00 | 462.71 | 2081493.97 | 07-FEB-06:01 | 0.00 | 29.37 | 64.57 | 1.03 | 0.00 | 0.06 | 0.60 | 07-FEB-06:01 |
March | 0.286776E+12 | 0.00 | 428.84 | 1927328.50 | 06-MAR-05:01 | 0.00 | 26.30 | 57.53 | 0.52 | 0.00 | 0.03 | 0.56 | 06-MAR-05:01 |
April | 0.723355E+11 | 0.00 | 225.53 | 1629520.69 | 01-APR-04:11 | 0.00 | 23.29 | 41.31 | 0.12 | 0.00 | 0.01 | 0.47 | 01-APR-04:11 |
May | 0.505494E+11 | 0.00 | 152.60 | 1654154.34 | 09-MAY-04:01 | 0.00 | 23.69 | 35.31 | 0.09 | 0.00 | 0.01 | 0.48 | 09-MAY-04:01 |
June | 0.167885E+10 | 0.00 | 31.36 | 370308.82 | 17-JUN-05:03 | 0.00 | 22.63 | 25.21 | 0.00 | 0.00 | 0.00 | 0.11 | 17-JUN-05:03 |
July | 24860404.87 | 0.00 | 4.12 | 10059.99 | 08-JUL-05:03 | 0.00 | 22.24 | 22.58 | 0.00 | 0.00 | 0.00 | 0.00 | 08-JUL-05:03 |
August | 0.565002E+09 | 0.00 | 13.38 | 372323.64 | 18-AUG-05:03 | 0.00 | 22.34 | 23.41 | 0.00 | 0.00 | 0.00 | 0.11 | 18-AUG-05:03 |
September | 0.140707E+11 | 0.00 | 102.89 | 1439883.70 | 19-SEP-04:11 | 0.00 | 22.10 | 30.54 | 0.02 | 0.00 | 0.00 | 0.42 | 19-SEP-04:11 |
October | 0.584272E+11 | 0.00 | 232.75 | 1521347.06 | 11-OCT-04:01 | 0.00 | 22.71 | 40.87 | 0.10 | 0.00 | 0.01 | 0.44 | 11-OCT-04:01 |
November | 0.247229E+12 | 0.00 | 426.30 | 1867617.05 | 28-NOV-06:01 | 0.00 | 26.11 | 58.32 | 0.46 | 0.00 | 0.03 | 0.54 | 28-NOV-06:01 |
December | 0.611389E+12 | 0.00 | 578.25 | 2050482.29 | 04-DEC-06:01 | 0.00 | 30.60 | 69.98 | 1.18 | 0.00 | 0.07 | 0.60 | 04-DEC-06:01 |
Annual Sum or Average | 0.278487E+13 | 0.00 | 3277.97 | 0.00 | 25.40 | 45.13 | 0.46 | 0.00 | 0.03 | ||||
Minimum of Months | 24860404.87 | 0.00 | 4.12 | 10059.99 | 0.00 | 22.10 | 22.58 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.957188E+12 | 0.00 | 619.25 | 2138250.95 | 0.00 | 33.51 | 73.00 | 2.00 | 0.00 | 0.10 | 0.62 |
Report: BoilerReportMonthly
For: CENTRAL BOILER
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportBOILER HEATING ENERGY [J] | BOILER GAS CONSUMPTION [] | BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] | BOILER HEATING RATE {Maximum} [W] | BOILER HEATING RATE {TIMESTAMP} | BOILER GAS CONSUMPTION RATE [] | BOILER INLET TEMPERATURE [C] | BOILER OUTLET TEMPERATURE [C] | BOILER MASS FLOW RATE [kg/s] | BOILER ANCILLARY ELECTRICITY RATE [W] | BOILER PART LOAD RATIO [] | BOILER PART LOAD RATIO [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 18.59 | 18.59 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 19.26 | 19.26 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 19.87 | 19.87 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 21.42 | 21.42 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 19.71 | 19.71 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 23.80 | 23.80 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 31.30 | 31.30 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 32.42 | 32.42 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 21.29 | 21.29 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 19.84 | 19.84 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 19.88 | 19.88 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 20.24 | 20.24 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 22.33 | 22.33 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.59 | 18.59 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.42 | 32.42 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: VAV_BOT WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 |
February | 0.736348E+09 | 0.00 | 12.23 | 0.736348E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 46910.45 | 27-FEB-15:30 | 46910.45 | 27-FEB-15:30 | 0.00 | 0.00 | 0.00 |
March | 64191064.87 | 0.00 | 4.89 | 64191064.87 | 0.00 | 0.00 | 0.00 | 0.00 | 12393.11 | 14-MAR-13:30 | 12393.11 | 14-MAR-13:30 | 0.00 | 0.00 | 0.00 |
April | 0.713072E+10 | 0.00 | 78.89 | 0.713072E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 90172.76 | 06-APR-16:00 | 90172.76 | 06-APR-16:00 | 0.00 | 0.00 | 0.00 |
May | 0.195332E+11 | 0.00 | 171.23 | 0.195332E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 121968.00 | 19-MAY-15:20 | 121968.00 | 19-MAY-15:20 | 0.00 | 0.00 | 0.00 |
June | 0.638689E+11 | 0.00 | 343.89 | 0.638186E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 138857.99 | 29-JUN-14:40 | 138857.99 | 29-JUN-14:40 | 0.00 | 0.00 | 0.00 |
July | 0.108592E+12 | 0.00 | 471.45 | 0.108413E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 165129.77 | 17-JUL-15:20 | 165129.77 | 17-JUL-15:20 | 0.00 | 0.00 | 0.00 |
August | 0.991574E+11 | 0.00 | 458.79 | 0.991574E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 164372.12 | 07-AUG-15:20 | 164372.12 | 07-AUG-15:20 | 0.00 | 0.00 | 0.00 |
September | 0.413584E+11 | 0.00 | 254.00 | 0.400217E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 214303.48 | 07-SEP-15:00 | 138433.67 | 04-SEP-15:21 | 0.00 | 0.00 | 0.00 |
October | 0.112922E+11 | 0.00 | 112.26 | 0.112922E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 112935.89 | 18-OCT-15:50 | 112935.89 | 18-OCT-15:50 | 0.00 | 0.00 | 0.00 |
November | 0.616459E+09 | 0.00 | 22.88 | 0.616459E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 20234.37 | 03-NOV-14:00 | 20234.37 | 03-NOV-14:00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.352350E+12 | 0.00 | 1930.51 | 0.350784E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.108592E+12 | 0.00 | 471.45 | 0.108413E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 214303.48 | 165129.77 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: VAV_MID WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 31506.06 | 0.00 | 17.05 | 31506.06 | 0.00 | 0.00 | 0.00 | 0.00 | 3.41 | 03-JAN-06:00 | 3.41 | 03-JAN-06:00 | 0.00 | 0.00 | 0.00 |
February | 0.582135E+10 | 0.00 | 42.46 | 0.582135E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 343626.02 | 27-FEB-14:00 | 343626.02 | 27-FEB-14:00 | 0.00 | 0.00 | 0.00 |
March | 0.247060E+09 | 0.00 | 62.40 | 0.247060E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 68784.96 | 14-MAR-13:30 | 68784.96 | 14-MAR-13:30 | 0.00 | 0.00 | 0.00 |
April | 0.511108E+11 | 0.00 | 123.85 | 0.511108E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 720946.46 | 06-APR-16:00 | 720946.46 | 06-APR-16:00 | 0.00 | 0.00 | 0.00 |
May | 0.167845E+12 | 0.00 | 191.02 | 0.167845E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1165675.81 | 19-MAY-15:30 | 1165675.81 | 19-MAY-15:30 | 0.00 | 0.00 | 0.00 |
June | 0.544162E+12 | 0.00 | 332.48 | 0.543727E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1309120.82 | 29-JUN-14:50 | 1309120.82 | 29-JUN-14:50 | 0.00 | 0.00 | 0.00 |
July | 0.910049E+12 | 0.00 | 416.68 | 0.908886E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1524359.19 | 17-JUL-15:30 | 1524359.19 | 17-JUL-15:30 | 0.00 | 0.00 | 0.00 |
August | 0.790119E+12 | 0.00 | 385.49 | 0.790119E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1449182.73 | 07-AUG-15:40 | 1449182.73 | 07-AUG-15:40 | 0.00 | 0.00 | 0.00 |
September | 0.364666E+12 | 0.00 | 271.61 | 0.352764E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 2000275.77 | 07-SEP-15:00 | 1334679.36 | 04-SEP-15:31 | 0.00 | 0.00 | 0.00 |
October | 0.893588E+11 | 0.00 | 146.24 | 0.893588E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 956004.05 | 18-OCT-15:20 | 956004.05 | 18-OCT-15:20 | 0.00 | 0.00 | 0.00 |
November | 0.448429E+10 | 0.00 | 69.70 | 0.448429E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 187325.68 | 03-NOV-13:55 | 187325.68 | 03-NOV-13:55 | 0.00 | 0.00 | 0.00 |
December | 64277.76 | 0.00 | 35.16 | 64277.76 | 0.00 | 0.00 | 0.00 | 0.00 | 3.26 | 17-DEC-15:55 | 3.26 | 17-DEC-15:55 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.292786E+13 | 0.00 | 2094.14 | 0.291436E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 31506.06 | 0.00 | 17.05 | 31506.06 | 0.00 | 0.00 | 0.00 | 0.00 | 3.26 | 3.26 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.910049E+12 | 0.00 | 416.68 | 0.908886E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 2000275.77 | 1524359.19 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: VAV_TOP WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 52824.02 | 0.00 | 2.98 | 52824.02 | 0.00 | 0.00 | 0.00 | 0.00 | 147.30 | 26-JAN-00:50 | 147.30 | 26-JAN-00:50 | 0.00 | 0.00 | 0.00 |
February | 0.390482E+09 | 0.00 | 12.61 | 0.390482E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 27817.44 | 27-FEB-13:40 | 27817.44 | 27-FEB-13:40 | 0.00 | 0.00 | 0.00 |
March | 2331981.52 | 0.00 | 2.12 | 2331981.52 | 0.00 | 0.00 | 0.00 | 0.00 | 644.13 | 14-MAR-14:00 | 644.13 | 14-MAR-14:00 | 0.00 | 0.00 | 0.00 |
April | 0.479342E+10 | 0.00 | 69.87 | 0.479342E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 73320.21 | 06-APR-16:00 | 73320.21 | 06-APR-16:00 | 0.00 | 0.00 | 0.00 |
May | 0.173282E+11 | 0.00 | 157.45 | 0.173282E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 137325.88 | 19-MAY-15:30 | 137325.88 | 19-MAY-15:30 | 0.00 | 0.00 | 0.00 |
June | 0.588673E+11 | 0.00 | 323.38 | 0.588156E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 152417.15 | 29-JUN-14:50 | 152417.15 | 29-JUN-14:50 | 0.00 | 0.00 | 0.00 |
July | 0.988626E+11 | 0.00 | 414.78 | 0.987638E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 180544.94 | 17-JUL-15:30 | 180544.94 | 17-JUL-15:30 | 0.00 | 0.00 | 0.00 |
August | 0.839504E+11 | 0.00 | 379.27 | 0.839504E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 170583.07 | 07-AUG-15:40 | 170583.07 | 07-AUG-15:40 | 0.00 | 0.00 | 0.00 |
September | 0.370519E+11 | 0.00 | 240.58 | 0.358533E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 202482.58 | 07-SEP-15:20 | 147158.97 | 04-SEP-16:21 | 0.00 | 0.00 | 0.00 |
October | 0.773586E+10 | 0.00 | 96.61 | 0.773586E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 98579.15 | 18-OCT-15:10 | 98579.15 | 18-OCT-15:10 | 0.00 | 0.00 | 0.00 |
November | 0.331261E+09 | 0.00 | 18.46 | 0.331261E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 11249.30 | 04-NOV-14:00 | 11249.30 | 04-NOV-14:00 | 0.00 | 0.00 | 0.00 |
December | 126715.88 | 0.00 | 2.54 | 126715.88 | 0.00 | 0.00 | 0.00 | 0.00 | 542.99 | 28-DEC-00:33 | 542.99 | 28-DEC-00:33 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.309314E+12 | 0.00 | 1720.64 | 0.307965E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 52824.02 | 0.00 | 2.12 | 52824.02 | 0.00 | 0.00 | 0.00 | 0.00 | 147.30 | 147.30 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.988626E+11 | 0.00 | 414.78 | 0.987638E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 202482.58 | 180544.94 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: CAV_BAS COOLING COIL
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 430925.51 | 0.00 | 0.68 | 430925.51 | 0.00 | 0.00 | 0.00 | 0.00 | 4458.97 | 24-JAN-05:11 | 4458.97 | 24-JAN-05:11 | 0.00 | 0.00 | 0.00 |
February | 0.282169E+09 | 0.00 | 5.17 | 0.282169E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 25368.65 | 27-FEB-15:00 | 25368.65 | 27-FEB-15:00 | 0.00 | 0.00 | 0.00 |
March | 36227.49 | 0.00 | 0.17 | 36227.49 | 0.00 | 0.00 | 0.00 | 0.00 | 60.38 | 01-MAR-08:00 | 60.38 | 01-MAR-08:00 | 0.00 | 0.00 | 0.00 |
April | 0.252028E+10 | 0.00 | 37.91 | 0.252028E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 52517.91 | 07-APR-14:00 | 52517.91 | 07-APR-14:00 | 0.00 | 0.00 | 0.00 |
May | 0.934050E+10 | 0.00 | 105.45 | 0.934050E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 64225.30 | 29-MAY-14:30 | 64225.30 | 29-MAY-14:30 | 0.00 | 0.00 | 0.00 |
June | 0.331920E+11 | 0.00 | 232.04 | 0.331666E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 72998.31 | 13-JUN-04:12 | 71737.87 | 26-JUN-11:00 | 0.00 | 0.00 | 0.00 |
July | 0.565008E+11 | 0.00 | 329.52 | 0.564569E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 150741.40 | 16-JUL-17:50 | 127813.02 | 16-JUL-19:08 | 0.00 | 0.00 | 0.00 |
August | 0.517700E+11 | 0.00 | 316.90 | 0.517700E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 126509.60 | 06-AUG-19:20 | 126509.60 | 06-AUG-19:20 | 0.00 | 0.00 | 0.00 |
September | 0.214620E+11 | 0.00 | 181.97 | 0.210835E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 137559.32 | 03-SEP-13:58 | 137559.32 | 03-SEP-13:58 | 0.00 | 0.00 | 0.00 |
October | 0.593250E+10 | 0.00 | 59.18 | 0.593250E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 62656.09 | 18-OCT-14:00 | 62656.09 | 18-OCT-14:00 | 0.00 | 0.00 | 0.00 |
November | 75754208.78 | 0.00 | 4.07 | 75754208.78 | 0.00 | 0.00 | 0.00 | 0.00 | 29207.11 | 17-NOV-06:03 | 29207.11 | 17-NOV-06:03 | 0.00 | 0.00 | 0.00 |
December | 22839.71 | 0.00 | 0.17 | 22839.71 | 0.00 | 0.00 | 0.00 | 0.00 | 38.07 | 15-DEC-18:10 | 38.07 | 15-DEC-18:10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.181077E+12 | 0.00 | 1273.21 | 0.180629E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 22839.71 | 0.00 | 0.17 | 22839.71 | 0.00 | 0.00 | 0.00 | 0.00 | 38.07 | 38.07 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.565008E+11 | 0.00 | 329.52 | 0.564569E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 150741.40 | 137559.32 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: AIRLOOP DATACENTER BASEMENT COOLING COIL
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.897821E+10 | 0.516233E+10 | 744.00 | 0.781808E+10 | 0.116013E+10 | 0.00 | 0.02 | 03-JAN-15:00 | 0.02 | 10-JAN-22:01 | 5237.54 | 03-JAN-15:00 | 4757.70 | 03-JAN-15:00 | 497.04 | 21-JAN-15:10 | 2469.57 | 03-JAN-15:00 | 0.00 |
February | 0.135760E+11 | 0.640890E+10 | 672.00 | 0.120041E+11 | 0.157180E+10 | 0.00 | 0.07 | 27-FEB-16:00 | 0.02 | 01-FEB-08:10 | 17900.29 | 27-FEB-16:00 | 17900.29 | 27-FEB-16:00 | 979.42 | 08-FEB-04:01 | 7157.10 | 27-FEB-16:00 | 0.00 |
March | 0.150884E+11 | 0.747561E+10 | 744.00 | 0.143569E+11 | 0.731513E+09 | 0.00 | 0.03 | 31-MAR-23:10 | 0.03 | 06-MAR-09:05 | 6752.56 | 31-MAR-23:10 | 6638.04 | 14-MAR-14:00 | 1151.38 | 01-MAR-00:10 | 3185.11 | 31-MAR-23:10 | 0.00 |
April | 0.751158E+11 | 0.270907E+11 | 720.00 | 0.720706E+11 | 0.304515E+10 | 0.00 | 0.92 | 07-APR-14:00 | 0.02 | 30-APR-23:40 | 316261.64 | 07-APR-14:00 | 316261.64 | 07-APR-14:00 | 24651.14 | 24-APR-10:50 | 118255.94 | 07-APR-14:00 | 0.00 |
May | 0.181394E+11 | 0.863402E+10 | 729.32 | 0.169445E+11 | 0.119492E+10 | 0.00 | 0.39 | 19-MAY-15:00 | 0.00 | 04-MAY-18:00 | 139501.15 | 19-MAY-13:50 | 134055.41 | 19-MAY-16:00 | 9499.44 | 19-MAY-12:20 | 52473.10 | 20-MAY-16:00 | 0.00 |
June | 0.136834E+12 | 0.498434E+11 | 646.12 | 0.123616E+12 | 0.132178E+11 | 0.00 | 0.76 | 20-JUN-18:50 | 0.00 | 17-JUN-24:00 | 325811.76 | 20-JUN-18:50 | 229220.91 | 23-JUN-15:50 | 112608.92 | 20-JUN-20:00 | 105547.44 | 20-JUN-18:50 | 0.00 |
July | 0.448356E+12 | 0.159087E+12 | 689.10 | 0.401143E+12 | 0.472134E+11 | 0.00 | 0.98 | 19-JUL-10:50 | 0.01 | 03-JUL-04:55 | 415623.81 | 19-JUL-10:50 | 321714.81 | 17-JUL-16:00 | 163854.82 | 01-JUL-00:53 | 151078.86 | 17-JUL-16:00 | 0.00 |
August | 0.569901E+12 | 0.197142E+12 | 744.00 | 0.519336E+12 | 0.505649E+11 | 0.00 | 1.00 | 03-AUG-15:40 | 0.01 | 31-AUG-23:53 | 413350.51 | 08-AUG-12:00 | 398870.92 | 08-AUG-14:50 | 141367.22 | 01-AUG-00:53 | 168042.00 | 05-AUG-16:00 | 0.00 |
September | 0.454441E+11 | 0.189391E+11 | 640.76 | 0.414243E+11 | 0.401971E+10 | 0.00 | 0.51 | 07-SEP-16:00 | 0.00 | 24-SEP-10:52 | 216458.25 | 07-SEP-16:00 | 139217.02 | 01-SEP-13:10 | 89362.03 | 07-SEP-15:50 | 68339.19 | 07-SEP-16:00 | 0.00 |
October | 0.247462E+11 | 0.105224E+11 | 743.33 | 0.231347E+11 | 0.161152E+10 | 0.00 | 0.53 | 18-OCT-14:00 | 0.01 | 01-OCT-01:10 | 178394.39 | 18-OCT-15:00 | 178394.39 | 18-OCT-15:00 | 1376.77 | 12-OCT-12:00 | 66601.52 | 18-OCT-14:00 | 0.00 |
November | 0.165686E+11 | 0.782664E+10 | 720.00 | 0.156691E+11 | 0.899448E+09 | 0.00 | 0.22 | 17-NOV-17:00 | 0.03 | 18-NOV-13:25 | 68223.84 | 17-NOV-17:00 | 65122.94 | 17-NOV-17:00 | 3100.90 | 17-NOV-17:00 | 21921.20 | 17-NOV-17:00 | 0.00 |
December | 0.166132E+11 | 0.835927E+10 | 744.00 | 0.162722E+11 | 0.341006E+09 | 0.00 | 0.23 | 10-DEC-02:00 | 0.03 | 10-DEC-09:25 | 65679.09 | 10-DEC-02:00 | 65679.09 | 10-DEC-02:00 | 8995.62 | 19-DEC-15:00 | 22554.76 | 10-DEC-02:00 | 0.00 |
Annual Sum or Average | 0.138936E+13 | 0.506492E+12 | 8536.64 | 0.126379E+13 | 0.125571E+12 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.897821E+10 | 0.516233E+10 | 640.76 | 0.781808E+10 | 0.341006E+09 | 0.00 | 0.02 | 0.00 | 5237.54 | 4757.70 | 497.04 | 2469.57 | 0.00 | ||||||
Maximum of Months | 0.569901E+12 | 0.197142E+12 | 744.00 | 0.519336E+12 | 0.505649E+11 | 0.00 | 1.00 | 0.03 | 415623.81 | 398870.92 | 163854.82 | 168042.00 | 0.00 |
Report: DXReportMonthly
For: AIRLOOP DATACENTER BOT COOLING COIL
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.291329E+10 | 0.838011E+09 | 722.48 | 0.291296E+10 | 323353.20 | 0.00 | 0.29 | 19-JAN-16:50 | 0.00 | 07-JAN-20:32 | 2401.99 | 13-JAN-16:20 | 2401.99 | 13-JAN-16:20 | 12.07 | 02-JAN-07:10 | 640.41 | 19-JAN-16:50 | 0.00 |
February | 0.827107E+10 | 0.217761E+10 | 672.00 | 0.827107E+10 | -0.0 | 0.00 | 0.60 | 26-FEB-17:23 | 0.26 | 01-FEB-07:03 | 5256.52 | 26-FEB-17:27 | 5256.52 | 26-FEB-17:27 | 0.00 | 14-FEB-05:43 | 1335.65 | 26-FEB-17:23 | 0.00 |
March | 0.149973E+11 | 0.372217E+10 | 744.00 | 0.149973E+11 | -0.0 | 0.00 | 0.79 | 31-MAR-24:00 | 0.51 | 06-MAR-07:03 | 7466.50 | 31-MAR-24:00 | 7466.50 | 31-MAR-24:00 | 0.00 | 20-MAR-14:40 | 1765.45 | 31-MAR-24:00 | 0.00 |
April | 0.201480E+11 | 0.478479E+10 | 720.00 | 0.201392E+11 | 8777649.46 | 0.00 | 1.00 | 16-APR-17:31 | 0.29 | 30-APR-23:55 | 9157.56 | 22-APR-18:10 | 9157.56 | 22-APR-18:10 | 135.33 | 24-APR-10:40 | 2654.76 | 07-APR-14:00 | 0.00 |
May | 0.576652E+10 | 0.155625E+10 | 744.00 | 0.573886E+10 | 27662264.89 | 0.00 | 0.47 | 31-MAY-24:00 | 0.13 | 08-MAY-06:10 | 4164.37 | 31-MAY-24:00 | 4164.37 | 31-MAY-24:00 | 153.93 | 30-MAY-09:30 | 1057.73 | 19-MAY-16:00 | 0.00 |
June | 0.111022E+11 | 0.301676E+10 | 720.00 | 0.110072E+11 | 95066120.60 | 0.00 | 0.66 | 30-JUN-23:13 | 0.38 | 17-JUN-06:20 | 6036.03 | 30-JUN-23:03 | 6032.22 | 30-JUN-24:00 | 364.39 | 06-JUN-16:40 | 1948.33 | 29-JUN-15:00 | 0.00 |
July | 0.168060E+11 | 0.496792E+10 | 744.00 | 0.167039E+11 | 0.102137E+09 | 0.00 | 0.89 | 16-JUL-18:51 | 0.61 | 08-JUL-06:10 | 7926.56 | 31-JUL-23:45 | 7926.56 | 31-JUL-23:45 | 394.03 | 03-JUL-17:00 | 3162.60 | 17-JUL-16:00 | 0.00 |
August | 0.217253E+11 | 0.613545E+10 | 744.00 | 0.216487E+11 | 76622641.11 | 0.00 | 1.00 | 03-AUG-18:40 | 0.30 | 31-AUG-24:00 | 9145.19 | 05-AUG-20:00 | 9145.19 | 05-AUG-20:00 | 448.36 | 22-AUG-16:00 | 3724.95 | 05-AUG-16:00 | 0.00 |
September | 0.587028E+10 | 0.163597E+10 | 720.00 | 0.577824E+10 | 92045756.09 | 0.00 | 0.45 | 04-SEP-17:41 | 0.16 | 19-SEP-06:10 | 3959.58 | 30-SEP-24:00 | 3959.58 | 30-SEP-24:00 | 339.75 | 07-SEP-14:00 | 1461.34 | 04-SEP-17:31 | 0.00 |
October | 0.106273E+11 | 0.267702E+10 | 744.00 | 0.106145E+11 | 12762379.54 | 0.00 | 0.63 | 31-OCT-24:00 | 0.35 | 10-OCT-06:10 | 5588.44 | 31-OCT-24:00 | 5588.44 | 31-OCT-24:00 | 113.23 | 25-OCT-11:00 | 1576.61 | 18-OCT-16:00 | 0.00 |
November | 0.146614E+11 | 0.359442E+10 | 720.00 | 0.146588E+11 | 2579336.06 | 0.00 | 0.73 | 13-NOV-16:30 | 0.51 | 27-NOV-07:10 | 6736.38 | 03-NOV-16:00 | 6665.18 | 03-NOV-16:00 | 86.21 | 17-NOV-17:05 | 1608.38 | 13-NOV-16:30 | 0.00 |
December | 0.194801E+11 | 0.473644E+10 | 744.00 | 0.194799E+11 | 190647.97 | 0.00 | 0.89 | 10-DEC-16:03 | 0.71 | 29-DEC-07:03 | 8462.04 | 06-DEC-16:10 | 8438.69 | 06-DEC-16:10 | 46.39 | 19-DEC-17:05 | 1971.18 | 10-DEC-16:03 | 0.00 |
Annual Sum or Average | 0.152369E+12 | 0.398428E+11 | 8738.48 | 0.151951E+12 | 0.418167E+09 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.291329E+10 | 0.838011E+09 | 672.00 | 0.291296E+10 | -0.0 | 0.00 | 0.29 | 0.00 | 2401.99 | 2401.99 | 0.00 | 640.41 | 0.00 | ||||||
Maximum of Months | 0.217253E+11 | 0.613545E+10 | 744.00 | 0.216487E+11 | 0.102137E+09 | 0.00 | 1.00 | 0.71 | 9157.56 | 9157.56 | 448.36 | 3724.95 | 0.00 |
Report: DXReportMonthly
For: AIRLOOP DATACENTER MID COOLING COIL
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.756959E+10 | 0.236715E+10 | 418.40 | 0.756360E+10 | 5992254.67 | 0.00 | 0.25 | 19-JAN-16:50 | 0.00 | 01-JAN-00:05 | 20207.05 | 13-JAN-16:30 | 20207.05 | 13-JAN-16:30 | 420.69 | 02-JAN-12:00 | 5365.02 | 19-JAN-16:50 | 0.00 |
February | 0.590737E+11 | 0.159134E+11 | 672.00 | 0.590737E+11 | -0.0 | 0.00 | 0.55 | 26-FEB-17:32 | 0.11 | 06-FEB-03:52 | 45674.11 | 28-FEB-17:00 | 45674.11 | 28-FEB-17:00 | 0.00 | 24-FEB-12:20 | 11665.07 | 26-FEB-17:32 | 0.00 |
March | 0.124694E+12 | 0.314076E+11 | 744.00 | 0.124694E+12 | -0.0 | 0.00 | 0.74 | 28-MAR-17:50 | 0.35 | 06-MAR-07:03 | 65460.75 | 28-MAR-17:50 | 65460.75 | 28-MAR-17:50 | 0.00 | 12-MAR-13:57 | 15775.92 | 28-MAR-17:50 | 0.00 |
April | 0.180360E+12 | 0.432501E+11 | 720.00 | 0.180271E+12 | 88561995.62 | 0.00 | 0.98 | 16-APR-17:52 | 0.13 | 30-APR-23:55 | 85319.65 | 22-APR-18:12 | 85319.65 | 22-APR-18:12 | 1315.47 | 24-APR-10:40 | 25131.74 | 07-APR-14:00 | 0.00 |
May | 0.465520E+11 | 0.127395E+11 | 744.00 | 0.462846E+11 | 0.267373E+09 | 0.00 | 0.46 | 31-MAY-24:00 | 0.01 | 08-MAY-06:10 | 39332.27 | 31-MAY-24:00 | 39332.27 | 31-MAY-24:00 | 1477.92 | 30-MAY-09:30 | 10039.42 | 19-MAY-16:00 | 0.00 |
June | 0.101940E+12 | 0.278842E+11 | 720.00 | 0.101001E+12 | 0.938781E+09 | 0.00 | 0.66 | 30-JUN-23:13 | 0.33 | 17-JUN-06:10 | 58852.63 | 30-JUN-23:03 | 58800.57 | 30-JUN-24:00 | 3557.39 | 06-JUN-16:40 | 18587.28 | 28-JUN-19:00 | 0.00 |
July | 0.158348E+12 | 0.469787E+11 | 744.00 | 0.157333E+12 | 0.101494E+10 | 0.00 | 0.89 | 16-JUL-18:45 | 0.56 | 08-JUL-06:10 | 76965.51 | 31-JUL-23:53 | 76965.51 | 31-JUL-23:53 | 3852.46 | 03-JUL-17:00 | 30161.01 | 17-JUL-16:00 | 0.00 |
August | 0.204472E+12 | 0.579903E+11 | 744.00 | 0.203711E+12 | 0.760977E+09 | 0.00 | 1.00 | 04-AUG-17:40 | 0.26 | 31-AUG-24:00 | 87881.53 | 03-AUG-18:50 | 87881.53 | 03-AUG-18:50 | 4385.02 | 22-AUG-16:00 | 35720.71 | 06-AUG-16:00 | 0.00 |
September | 0.493391E+11 | 0.139589E+11 | 720.00 | 0.484440E+11 | 0.895103E+09 | 0.00 | 0.45 | 04-SEP-17:41 | 0.08 | 19-SEP-06:10 | 35042.68 | 30-SEP-23:30 | 35042.68 | 30-SEP-23:30 | 3385.55 | 07-SEP-14:10 | 13880.98 | 04-SEP-17:41 | 0.00 |
October | 0.883410E+11 | 0.225627E+11 | 744.00 | 0.882148E+11 | 0.126249E+09 | 0.00 | 0.58 | 15-OCT-16:52 | 0.22 | 10-OCT-06:10 | 48655.50 | 15-OCT-17:06 | 48655.50 | 15-OCT-17:06 | 1110.68 | 25-OCT-11:00 | 14758.53 | 18-OCT-16:00 | 0.00 |
November | 0.120428E+12 | 0.300096E+11 | 720.00 | 0.120401E+12 | 26190994.38 | 0.00 | 0.69 | 13-NOV-16:30 | 0.35 | 27-NOV-07:10 | 62335.05 | 03-NOV-16:00 | 61634.34 | 03-NOV-16:00 | 828.30 | 17-NOV-17:05 | 14646.35 | 13-NOV-16:30 | 0.00 |
December | 0.157995E+12 | 0.392116E+11 | 744.00 | 0.157992E+12 | 2665291.23 | 0.00 | 0.82 | 06-DEC-16:10 | 0.53 | 31-DEC-23:45 | 77285.57 | 06-DEC-16:10 | 77011.85 | 06-DEC-16:10 | 498.24 | 19-DEC-17:05 | 17623.00 | 06-DEC-16:10 | 0.00 |
Annual Sum or Average | 0.129911E+13 | 0.344274E+12 | 8434.40 | 0.129498E+13 | 0.412683E+10 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.756959E+10 | 0.236715E+10 | 418.40 | 0.756360E+10 | -0.0 | 0.00 | 0.25 | 0.00 | 20207.05 | 20207.05 | 0.00 | 5365.02 | 0.00 | ||||||
Maximum of Months | 0.204472E+12 | 0.579903E+11 | 744.00 | 0.203711E+12 | 0.101494E+10 | 0.00 | 1.00 | 0.56 | 87881.53 | 87881.53 | 4385.02 | 35720.71 | 0.00 |
Report: DXReportMonthly
For: AIRLOOP DATACENTER TOP COOLING COIL
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.304978E+09 | 96738080.66 | 189.75 | 0.304774E+09 | 203963.72 | 0.00 | 0.24 | 13-JAN-16:30 | 0.00 | 01-JAN-00:05 | 1968.42 | 13-JAN-16:30 | 1968.42 | 13-JAN-16:30 | 15.43 | 02-JAN-13:40 | 519.97 | 13-JAN-16:30 | 0.00 |
February | 0.440339E+10 | 0.120682E+10 | 650.82 | 0.440339E+10 | 0.00 | 0.00 | 0.51 | 24-FEB-17:00 | 0.00 | 03-FEB-04:01 | 4520.39 | 28-FEB-17:00 | 4520.39 | 28-FEB-17:00 | 0.00 | 20-FEB-12:15 | 1113.76 | 24-FEB-17:00 | 0.00 |
March | 0.109375E+11 | 0.278806E+10 | 744.00 | 0.109375E+11 | -0.0 | 0.00 | 0.73 | 28-MAR-17:50 | 0.18 | 06-MAR-04:12 | 6546.80 | 28-MAR-17:50 | 6546.80 | 28-MAR-17:50 | 0.00 | 21-MAR-22:00 | 1580.84 | 28-MAR-17:50 | 0.00 |
April | 0.169319E+11 | 0.409909E+10 | 719.00 | 0.169231E+11 | 8741370.46 | 0.00 | 0.95 | 16-APR-17:52 | 0.00 | 30-APR-23:05 | 8603.18 | 25-APR-18:10 | 8603.18 | 25-APR-18:10 | 131.23 | 24-APR-10:40 | 2524.00 | 07-APR-14:00 | 0.00 |
May | 0.400971E+10 | 0.110670E+10 | 689.11 | 0.398330E+10 | 26414460.76 | 0.00 | 0.45 | 31-MAY-23:30 | 0.00 | 01-MAY-00:10 | 3862.25 | 31-MAY-23:30 | 3862.25 | 31-MAY-23:30 | 143.42 | 30-MAY-09:30 | 1042.15 | 19-MAY-16:00 | 0.00 |
June | 0.996639E+10 | 0.274438E+10 | 720.00 | 0.987272E+10 | 93677562.00 | 0.00 | 0.65 | 30-JUN-23:13 | 0.24 | 17-JUN-06:10 | 5885.09 | 30-JUN-23:03 | 5875.57 | 30-JUN-23:33 | 358.44 | 06-JUN-16:40 | 1895.68 | 29-JUN-15:00 | 0.00 |
July | 0.157522E+11 | 0.469814E+10 | 744.00 | 0.156509E+11 | 0.101297E+09 | 0.00 | 0.91 | 16-JUL-18:51 | 0.51 | 08-JUL-06:10 | 7690.64 | 31-JUL-23:53 | 7690.64 | 31-JUL-23:53 | 386.33 | 03-JUL-17:00 | 3082.14 | 17-JUL-16:00 | 0.00 |
August | 0.202910E+11 | 0.578615E+10 | 744.00 | 0.202151E+11 | 75913729.55 | 0.00 | 1.00 | 04-AUG-17:40 | 0.25 | 31-AUG-24:00 | 8907.10 | 05-AUG-19:55 | 8907.10 | 05-AUG-19:55 | 440.37 | 22-AUG-16:00 | 3632.62 | 06-AUG-16:00 | 0.00 |
September | 0.438949E+10 | 0.126365E+10 | 718.44 | 0.430110E+10 | 88390073.75 | 0.00 | 0.47 | 04-SEP-17:51 | 0.00 | 12-SEP-02:45 | 3666.99 | 04-SEP-17:51 | 3666.99 | 04-SEP-17:51 | 341.71 | 07-SEP-14:00 | 1473.83 | 04-SEP-17:31 | 0.00 |
October | 0.749428E+10 | 0.194239E+10 | 743.86 | 0.748190E+10 | 12379813.15 | 0.00 | 0.57 | 18-OCT-16:50 | 0.00 | 10-OCT-01:15 | 4879.54 | 18-OCT-17:00 | 4879.54 | 18-OCT-17:00 | 110.50 | 25-OCT-11:00 | 1491.70 | 18-OCT-16:00 | 0.00 |
November | 0.102901E+11 | 0.260241E+10 | 720.00 | 0.102875E+11 | 2549055.75 | 0.00 | 0.66 | 03-NOV-16:00 | 0.18 | 27-NOV-04:01 | 6187.49 | 03-NOV-16:00 | 6117.65 | 03-NOV-16:00 | 81.21 | 17-NOV-17:05 | 1448.32 | 03-NOV-16:00 | 0.00 |
December | 0.139265E+11 | 0.350670E+10 | 744.00 | 0.139262E+11 | 229474.89 | 0.00 | 0.81 | 06-DEC-16:10 | 0.39 | 31-DEC-23:45 | 7669.92 | 06-DEC-16:10 | 7644.58 | 06-DEC-16:10 | 46.87 | 19-DEC-17:05 | 1754.48 | 06-DEC-16:10 | 0.00 |
Annual Sum or Average | 0.118697E+12 | 0.318412E+11 | 8126.98 | 0.118288E+12 | 0.409796E+09 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.304978E+09 | 96738080.66 | 189.75 | 0.304774E+09 | -0.0 | 0.00 | 0.24 | 0.00 | 1968.42 | 1968.42 | 0.00 | 519.97 | 0.00 | ||||||
Maximum of Months | 0.202910E+11 | 0.578615E+10 | 744.00 | 0.202151E+11 | 0.101297E+09 | 0.00 | 1.00 | 0.51 | 8907.10 | 8907.10 | 440.37 | 3632.62 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 120.54 | 0.00 | 120.54 | 0.74 | 1193.10 | 0.00 | 0.00 | 0.00 |
February | 170.20 | 0.00 | 170.20 | 12.90 | 904.60 | 0.00 | 0.00 | 0.00 |
March | 276.48 | 0.00 | 276.48 | 61.67 | 737.92 | 0.00 | 0.00 | 0.00 |
April | 315.24 | 1.84 | 313.40 | 129.47 | 532.65 | 0.00 | 0.00 | 0.00 |
May | 413.99 | 24.53 | 389.45 | 270.33 | 383.26 | 0.00 | 0.00 | 0.00 |
June | 482.06 | 55.41 | 426.65 | 461.64 | 239.11 | 0.00 | 0.00 | 0.00 |
July | 440.39 | 41.25 | 399.14 | 513.78 | 196.78 | 0.00 | 0.00 | 0.00 |
August | 352.89 | 9.46 | 343.43 | 369.24 | 229.53 | 0.00 | 0.00 | 0.00 |
September | 264.29 | 0.09 | 264.19 | 207.86 | 354.43 | 0.00 | 0.00 | 0.00 |
October | 192.78 | 0.00 | 192.78 | 62.99 | 542.58 | 0.00 | 0.00 | 0.00 |
November | 131.06 | 0.00 | 131.06 | 9.88 | 786.72 | 0.00 | 0.00 | 0.00 |
December | 101.08 | 0.00 | 101.08 | 0.24 | 1062.60 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 272.29 | 11.10 | 261.19 | 176.10 | 595.71 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 101.08 | 0.00 | 101.08 | 0.24 | 196.78 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 482.06 | 55.41 | 426.65 | 513.78 | 1193.10 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 120.54 | 0.00 | 120.54 | 0.74 | 1193.10 | 0.00 | 0.00 | 0.00 |
February | 170.20 | 0.00 | 170.20 | 12.90 | 904.60 | 0.00 | 0.00 | 0.00 |
March | 276.47 | 0.00 | 276.47 | 61.67 | 737.92 | 0.00 | 0.00 | 0.00 |
April | 315.24 | 1.84 | 313.40 | 129.47 | 532.65 | 0.00 | 0.00 | 0.00 |
May | 413.99 | 24.53 | 389.45 | 270.33 | 383.26 | 0.00 | 0.00 | 0.00 |
June | 482.06 | 55.41 | 426.65 | 461.64 | 239.11 | 0.00 | 0.00 | 0.00 |
July | 440.39 | 41.25 | 399.14 | 513.78 | 196.78 | 0.00 | 0.00 | 0.00 |
August | 352.89 | 9.46 | 343.43 | 369.24 | 229.53 | 0.00 | 0.00 | 0.00 |
September | 264.29 | 0.09 | 264.19 | 207.86 | 354.43 | 0.00 | 0.00 | 0.00 |
October | 192.78 | 0.00 | 192.78 | 62.99 | 542.58 | 0.00 | 0.00 | 0.00 |
November | 131.06 | 0.00 | 131.06 | 9.88 | 786.72 | 0.00 | 0.00 | 0.00 |
December | 101.08 | 0.00 | 101.08 | 0.24 | 1062.60 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 272.29 | 11.10 | 261.19 | 176.10 | 595.71 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 101.08 | 0.00 | 101.08 | 0.24 | 196.78 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 482.06 | 55.41 | 426.65 | 513.78 | 1193.10 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 120.54 | 0.00 | 120.54 | 0.74 | 1193.10 | 0.00 | 0.00 | 0.00 |
February | 170.20 | 0.00 | 170.20 | 12.90 | 904.60 | 0.00 | 0.00 | 0.00 |
March | 276.48 | 0.00 | 276.48 | 61.67 | 737.92 | 0.00 | 0.00 | 0.00 |
April | 315.24 | 1.84 | 313.40 | 129.47 | 532.65 | 0.00 | 0.00 | 0.00 |
May | 413.99 | 24.53 | 389.45 | 270.33 | 383.26 | 0.00 | 0.00 | 0.00 |
June | 482.06 | 55.41 | 426.65 | 461.64 | 239.11 | 0.00 | 0.00 | 0.00 |
July | 440.39 | 41.25 | 399.14 | 513.78 | 196.78 | 0.00 | 0.00 | 0.00 |
August | 352.89 | 9.46 | 343.43 | 369.24 | 229.53 | 0.00 | 0.00 | 0.00 |
September | 264.29 | 0.09 | 264.19 | 207.86 | 354.43 | 0.00 | 0.00 | 0.00 |
October | 192.78 | 0.00 | 192.78 | 62.99 | 542.58 | 0.00 | 0.00 | 0.00 |
November | 131.06 | 0.00 | 131.06 | 9.88 | 786.72 | 0.00 | 0.00 | 0.00 |
December | 101.08 | 0.00 | 101.08 | 0.24 | 1062.60 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 272.29 | 11.10 | 261.19 | 176.10 | 595.71 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 101.08 | 0.00 | 101.08 | 0.24 | 196.78 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 482.06 | 55.41 | 426.65 | 513.78 | 1193.10 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 120.54 | 0.00 | 120.54 | 0.74 | 1193.10 | 0.00 | 0.00 | 0.00 |
February | 170.20 | 0.00 | 170.20 | 12.90 | 904.60 | 0.00 | 0.00 | 0.00 |
March | 276.47 | 0.00 | 276.47 | 61.67 | 737.92 | 0.00 | 0.00 | 0.00 |
April | 315.24 | 1.84 | 313.40 | 129.47 | 532.65 | 0.00 | 0.00 | 0.00 |
May | 413.99 | 24.53 | 389.45 | 270.33 | 383.26 | 0.00 | 0.00 | 0.00 |
June | 482.06 | 55.41 | 426.65 | 461.64 | 239.11 | 0.00 | 0.00 | 0.00 |
July | 440.39 | 41.25 | 399.14 | 513.78 | 196.78 | 0.00 | 0.00 | 0.00 |
August | 352.89 | 9.46 | 343.43 | 369.24 | 229.53 | 0.00 | 0.00 | 0.00 |
September | 264.29 | 0.09 | 264.19 | 207.86 | 354.43 | 0.00 | 0.00 | 0.00 |
October | 192.78 | 0.00 | 192.78 | 62.99 | 542.58 | 0.00 | 0.00 | 0.00 |
November | 131.06 | 0.00 | 131.06 | 9.88 | 786.72 | 0.00 | 0.00 | 0.00 |
December | 101.08 | 0.00 | 101.08 | 0.24 | 1062.60 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 272.29 | 11.10 | 261.19 | 176.10 | 595.71 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 101.08 | 0.00 | 101.08 | 0.24 | 196.78 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 482.06 | 55.41 | 426.65 | 513.78 | 1193.10 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 120.54 | 0.00 | 120.54 | 0.74 | 1193.06 | 0.00 | 0.00 | 0.00 |
February | 170.19 | 0.00 | 170.19 | 12.90 | 904.56 | 0.00 | 0.00 | 0.00 |
March | 276.46 | 0.00 | 276.46 | 61.67 | 737.89 | 0.00 | 0.00 | 0.00 |
April | 315.23 | 1.84 | 313.39 | 129.47 | 532.63 | 0.00 | 0.00 | 0.00 |
May | 413.97 | 24.53 | 389.44 | 270.32 | 383.24 | 0.00 | 0.00 | 0.00 |
June | 482.04 | 55.41 | 426.64 | 461.62 | 239.10 | 0.00 | 0.00 | 0.00 |
July | 440.37 | 41.25 | 399.13 | 513.76 | 196.77 | 0.00 | 0.00 | 0.00 |
August | 352.87 | 9.46 | 343.41 | 369.23 | 229.52 | 0.00 | 0.00 | 0.00 |
September | 264.28 | 0.09 | 264.18 | 207.85 | 354.42 | 0.00 | 0.00 | 0.00 |
October | 192.78 | 0.00 | 192.78 | 62.99 | 542.56 | 0.00 | 0.00 | 0.00 |
November | 131.05 | 0.00 | 131.05 | 9.88 | 786.69 | 0.00 | 0.00 | 0.00 |
December | 101.08 | 0.00 | 101.08 | 0.24 | 1062.56 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 272.28 | 11.10 | 261.18 | 176.09 | 595.69 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 101.08 | 0.00 | 101.08 | 0.24 | 196.77 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 482.04 | 55.41 | 426.64 | 513.76 | 1193.06 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 307.54 | 141.00 | 166.55 | 141.42 | 1209.05 | 0.00 | 0.00 | 0.00 |
February | 481.03 | 238.82 | 242.21 | 324.72 | 906.54 | 0.00 | 0.00 | 0.00 |
March | 646.78 | 267.62 | 379.16 | 480.18 | 747.66 | 0.00 | 0.00 | 0.00 |
April | 825.23 | 408.98 | 416.25 | 753.51 | 540.74 | 0.00 | 0.00 | 0.00 |
May | 911.58 | 405.59 | 505.98 | 904.93 | 419.30 | 0.00 | 0.00 | 0.00 |
June | 1179.92 | 607.19 | 572.73 | 1376.15 | 266.67 | 0.00 | 0.00 | 0.00 |
July | 1238.36 | 700.08 | 538.28 | 1573.20 | 210.73 | 0.00 | 0.00 | 0.00 |
August | 1076.19 | 599.62 | 476.57 | 1332.10 | 237.09 | 0.00 | 0.00 | 0.00 |
September | 761.30 | 392.98 | 368.32 | 840.88 | 361.10 | 0.00 | 0.00 | 0.00 |
October | 546.19 | 277.35 | 268.84 | 481.22 | 546.40 | 0.00 | 0.00 | 0.00 |
November | 346.17 | 161.61 | 184.55 | 210.00 | 771.60 | 0.00 | 0.00 | 0.00 |
December | 255.32 | 109.66 | 145.66 | 106.63 | 1057.86 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 715.86 | 359.83 | 356.03 | 712.65 | 605.09 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 255.32 | 109.66 | 145.66 | 106.63 | 210.73 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1238.36 | 700.08 | 572.73 | 1573.20 | 1209.05 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 307.54 | 141.00 | 166.55 | 141.42 | 1209.05 | 0.00 | 0.00 | 0.00 |
February | 481.03 | 238.82 | 242.21 | 324.72 | 906.54 | 0.00 | 0.00 | 0.00 |
March | 646.78 | 267.62 | 379.16 | 480.18 | 747.66 | 0.00 | 0.00 | 0.00 |
April | 825.23 | 408.98 | 416.25 | 753.51 | 540.74 | 0.00 | 0.00 | 0.00 |
May | 911.58 | 405.59 | 505.98 | 904.93 | 419.30 | 0.00 | 0.00 | 0.00 |
June | 1179.92 | 607.19 | 572.73 | 1376.15 | 266.67 | 0.00 | 0.00 | 0.00 |
July | 1238.36 | 700.08 | 538.28 | 1573.20 | 210.73 | 0.00 | 0.00 | 0.00 |
August | 1076.19 | 599.62 | 476.57 | 1332.10 | 237.09 | 0.00 | 0.00 | 0.00 |
September | 761.30 | 392.98 | 368.32 | 840.88 | 361.10 | 0.00 | 0.00 | 0.00 |
October | 546.19 | 277.35 | 268.84 | 481.22 | 546.40 | 0.00 | 0.00 | 0.00 |
November | 346.17 | 161.61 | 184.55 | 210.00 | 771.60 | 0.00 | 0.00 | 0.00 |
December | 255.32 | 109.66 | 145.66 | 106.63 | 1057.86 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 715.86 | 359.83 | 356.03 | 712.65 | 605.09 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 255.32 | 109.66 | 145.66 | 106.63 | 210.73 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1238.36 | 700.08 | 572.73 | 1573.20 | 1209.05 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 307.54 | 140.99 | 166.54 | 141.42 | 1209.03 | 0.00 | 0.00 | 0.00 |
February | 481.02 | 238.81 | 242.20 | 324.71 | 906.52 | 0.00 | 0.00 | 0.00 |
March | 646.77 | 267.62 | 379.16 | 480.17 | 747.65 | 0.00 | 0.00 | 0.00 |
April | 825.22 | 408.97 | 416.25 | 753.49 | 540.73 | 0.00 | 0.00 | 0.00 |
May | 911.56 | 405.59 | 505.97 | 904.91 | 419.29 | 0.00 | 0.00 | 0.00 |
June | 1179.90 | 607.17 | 572.72 | 1376.12 | 266.67 | 0.00 | 0.00 | 0.00 |
July | 1238.34 | 700.06 | 538.27 | 1573.17 | 210.73 | 0.00 | 0.00 | 0.00 |
August | 1076.17 | 599.61 | 476.56 | 1332.08 | 237.09 | 0.00 | 0.00 | 0.00 |
September | 761.28 | 392.97 | 368.31 | 840.87 | 361.09 | 0.00 | 0.00 | 0.00 |
October | 546.18 | 277.34 | 268.84 | 481.21 | 546.39 | 0.00 | 0.00 | 0.00 |
November | 346.16 | 161.61 | 184.55 | 210.00 | 771.59 | 0.00 | 0.00 | 0.00 |
December | 255.31 | 109.66 | 145.66 | 106.63 | 1057.84 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 715.84 | 359.82 | 356.02 | 712.64 | 605.08 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 255.31 | 109.66 | 145.66 | 106.63 | 210.73 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1238.34 | 700.06 | 572.72 | 1573.17 | 1209.03 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 849.68 | 606.86 | 242.82 | 747.74 | 997.48 | 0.00 | 0.00 | 0.00 |
February | 1082.05 | 778.25 | 303.80 | 1059.20 | 762.60 | 0.00 | 0.00 | 0.00 |
March | 967.21 | 543.14 | 424.07 | 941.72 | 686.47 | 0.00 | 0.00 | 0.00 |
April | 777.48 | 371.87 | 405.60 | 788.18 | 520.72 | 0.00 | 0.00 | 0.00 |
May | 690.77 | 229.42 | 461.34 | 714.92 | 403.48 | 0.00 | 0.00 | 0.00 |
June | 686.35 | 200.17 | 486.17 | 823.31 | 274.30 | 0.00 | 0.00 | 0.00 |
July | 739.95 | 273.34 | 466.61 | 1002.09 | 215.13 | 0.00 | 0.00 | 0.00 |
August | 879.38 | 443.37 | 436.01 | 1156.05 | 243.95 | 0.00 | 0.00 | 0.00 |
September | 975.34 | 597.62 | 377.72 | 1183.34 | 350.02 | 0.00 | 0.00 | 0.00 |
October | 1019.67 | 705.09 | 314.58 | 1121.63 | 499.68 | 0.00 | 0.00 | 0.00 |
November | 929.63 | 673.39 | 256.24 | 917.20 | 649.56 | 0.00 | 0.00 | 0.00 |
December | 807.99 | 583.45 | 224.54 | 724.29 | 870.13 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 865.63 | 498.65 | 366.98 | 930.63 | 538.62 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 686.35 | 200.17 | 224.54 | 714.92 | 215.13 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1082.05 | 778.25 | 486.17 | 1183.34 | 997.48 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 849.67 | 606.85 | 242.82 | 747.74 | 997.48 | 0.00 | 0.00 | 0.00 |
February | 1082.05 | 778.25 | 303.80 | 1059.20 | 762.60 | 0.00 | 0.00 | 0.00 |
March | 967.21 | 543.14 | 424.07 | 941.72 | 686.47 | 0.00 | 0.00 | 0.00 |
April | 777.47 | 371.87 | 405.60 | 788.18 | 520.72 | 0.00 | 0.00 | 0.00 |
May | 690.77 | 229.42 | 461.34 | 714.92 | 403.48 | 0.00 | 0.00 | 0.00 |
June | 686.35 | 200.17 | 486.17 | 823.31 | 274.30 | 0.00 | 0.00 | 0.00 |
July | 739.95 | 273.34 | 466.61 | 1002.09 | 215.13 | 0.00 | 0.00 | 0.00 |
August | 879.38 | 443.37 | 436.01 | 1156.05 | 243.95 | 0.00 | 0.00 | 0.00 |
September | 975.34 | 597.62 | 377.72 | 1183.34 | 350.02 | 0.00 | 0.00 | 0.00 |
October | 1019.67 | 705.09 | 314.58 | 1121.63 | 499.68 | 0.00 | 0.00 | 0.00 |
November | 929.63 | 673.39 | 256.24 | 917.20 | 649.56 | 0.00 | 0.00 | 0.00 |
December | 807.99 | 583.45 | 224.54 | 724.29 | 870.13 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 865.63 | 498.65 | 366.98 | 930.63 | 538.62 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 686.35 | 200.17 | 224.54 | 714.92 | 215.13 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1082.05 | 778.25 | 486.17 | 1183.34 | 997.48 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 849.68 | 606.86 | 242.82 | 747.74 | 997.48 | 0.00 | 0.00 | 0.00 |
February | 1082.05 | 778.25 | 303.80 | 1059.20 | 762.60 | 0.00 | 0.00 | 0.00 |
March | 967.21 | 543.14 | 424.07 | 941.72 | 686.47 | 0.00 | 0.00 | 0.00 |
April | 777.48 | 371.87 | 405.60 | 788.18 | 520.72 | 0.00 | 0.00 | 0.00 |
May | 690.77 | 229.42 | 461.34 | 714.92 | 403.48 | 0.00 | 0.00 | 0.00 |
June | 686.35 | 200.17 | 486.17 | 823.31 | 274.30 | 0.00 | 0.00 | 0.00 |
July | 739.95 | 273.34 | 466.61 | 1002.09 | 215.13 | 0.00 | 0.00 | 0.00 |
August | 879.38 | 443.37 | 436.01 | 1156.05 | 243.95 | 0.00 | 0.00 | 0.00 |
September | 975.34 | 597.62 | 377.72 | 1183.34 | 350.02 | 0.00 | 0.00 | 0.00 |
October | 1019.67 | 705.09 | 314.58 | 1121.63 | 499.68 | 0.00 | 0.00 | 0.00 |
November | 929.63 | 673.39 | 256.24 | 917.20 | 649.56 | 0.00 | 0.00 | 0.00 |
December | 807.99 | 583.45 | 224.54 | 724.29 | 870.13 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 865.63 | 498.65 | 366.98 | 930.63 | 538.62 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 686.35 | 200.17 | 224.54 | 714.92 | 215.13 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1082.05 | 778.25 | 486.17 | 1183.34 | 997.48 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 849.67 | 606.85 | 242.82 | 747.74 | 997.48 | 0.00 | 0.00 | 0.00 |
February | 1082.05 | 778.25 | 303.80 | 1059.20 | 762.60 | 0.00 | 0.00 | 0.00 |
March | 967.21 | 543.14 | 424.07 | 941.72 | 686.47 | 0.00 | 0.00 | 0.00 |
April | 777.47 | 371.87 | 405.60 | 788.18 | 520.72 | 0.00 | 0.00 | 0.00 |
May | 690.77 | 229.42 | 461.34 | 714.92 | 403.48 | 0.00 | 0.00 | 0.00 |
June | 686.35 | 200.17 | 486.17 | 823.31 | 274.30 | 0.00 | 0.00 | 0.00 |
July | 739.95 | 273.34 | 466.61 | 1002.09 | 215.13 | 0.00 | 0.00 | 0.00 |
August | 879.38 | 443.37 | 436.01 | 1156.05 | 243.95 | 0.00 | 0.00 | 0.00 |
September | 975.34 | 597.62 | 377.72 | 1183.34 | 350.02 | 0.00 | 0.00 | 0.00 |
October | 1019.67 | 705.09 | 314.58 | 1121.63 | 499.68 | 0.00 | 0.00 | 0.00 |
November | 929.63 | 673.39 | 256.24 | 917.20 | 649.56 | 0.00 | 0.00 | 0.00 |
December | 807.99 | 583.45 | 224.54 | 724.29 | 870.13 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 865.63 | 498.65 | 366.98 | 930.63 | 538.62 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 686.35 | 200.17 | 224.54 | 714.92 | 215.13 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1082.05 | 778.25 | 486.17 | 1183.34 | 997.48 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 849.64 | 606.83 | 242.81 | 747.71 | 997.44 | 0.00 | 0.00 | 0.00 |
February | 1082.01 | 778.22 | 303.79 | 1059.16 | 762.57 | 0.00 | 0.00 | 0.00 |
March | 967.17 | 543.12 | 424.05 | 941.68 | 686.44 | 0.00 | 0.00 | 0.00 |
April | 777.44 | 371.86 | 405.59 | 788.15 | 520.70 | 0.00 | 0.00 | 0.00 |
May | 690.74 | 229.41 | 461.33 | 714.89 | 403.46 | 0.00 | 0.00 | 0.00 |
June | 686.32 | 200.16 | 486.16 | 823.28 | 274.29 | 0.00 | 0.00 | 0.00 |
July | 739.92 | 273.32 | 466.60 | 1002.05 | 215.12 | 0.00 | 0.00 | 0.00 |
August | 879.35 | 443.35 | 436.00 | 1156.01 | 243.94 | 0.00 | 0.00 | 0.00 |
September | 975.30 | 597.60 | 377.70 | 1183.29 | 350.00 | 0.00 | 0.00 | 0.00 |
October | 1019.63 | 705.06 | 314.57 | 1121.58 | 499.66 | 0.00 | 0.00 | 0.00 |
November | 929.60 | 673.36 | 256.23 | 917.17 | 649.53 | 0.00 | 0.00 | 0.00 |
December | 807.96 | 583.43 | 224.53 | 724.26 | 870.09 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 865.60 | 498.63 | 366.97 | 930.59 | 538.60 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 686.32 | 200.16 | 224.53 | 714.89 | 215.12 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1082.01 | 778.22 | 486.16 | 1183.29 | 997.44 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 278.57 | 112.27 | 166.30 | 122.94 | 1300.63 | 0.00 | 0.00 | 0.00 |
February | 475.48 | 233.72 | 241.76 | 320.67 | 991.31 | 0.00 | 0.00 | 0.00 |
March | 608.49 | 222.96 | 385.53 | 424.22 | 857.08 | 0.00 | 0.00 | 0.00 |
April | 794.39 | 351.95 | 442.44 | 705.96 | 651.98 | 0.00 | 0.00 | 0.00 |
May | 982.61 | 448.12 | 534.49 | 998.34 | 475.74 | 0.00 | 0.00 | 0.00 |
June | 1069.04 | 491.05 | 577.99 | 1231.22 | 329.65 | 0.00 | 0.00 | 0.00 |
July | 1095.11 | 553.38 | 541.74 | 1383.49 | 277.84 | 0.00 | 0.00 | 0.00 |
August | 929.90 | 456.37 | 473.52 | 1131.44 | 311.46 | 0.00 | 0.00 | 0.00 |
September | 748.04 | 378.18 | 369.86 | 832.82 | 419.05 | 0.00 | 0.00 | 0.00 |
October | 534.65 | 265.64 | 269.01 | 472.90 | 631.18 | 0.00 | 0.00 | 0.00 |
November | 378.48 | 187.76 | 190.72 | 255.93 | 883.79 | 0.00 | 0.00 | 0.00 |
December | 254.41 | 107.38 | 147.03 | 107.96 | 1198.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 680.02 | 317.70 | 362.32 | 667.50 | 692.88 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 254.41 | 107.38 | 147.03 | 107.96 | 277.84 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1095.11 | 553.38 | 577.99 | 1383.49 | 1300.63 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 278.57 | 112.27 | 166.30 | 122.94 | 1300.63 | 0.00 | 0.00 | 0.00 |
February | 475.48 | 233.72 | 241.76 | 320.67 | 991.31 | 0.00 | 0.00 | 0.00 |
March | 608.49 | 222.96 | 385.53 | 424.22 | 857.08 | 0.00 | 0.00 | 0.00 |
April | 794.39 | 351.95 | 442.44 | 705.96 | 651.98 | 0.00 | 0.00 | 0.00 |
May | 982.61 | 448.12 | 534.49 | 998.34 | 475.74 | 0.00 | 0.00 | 0.00 |
June | 1069.04 | 491.05 | 577.99 | 1231.22 | 329.65 | 0.00 | 0.00 | 0.00 |
July | 1095.11 | 553.38 | 541.74 | 1383.49 | 277.84 | 0.00 | 0.00 | 0.00 |
August | 929.90 | 456.37 | 473.52 | 1131.44 | 311.46 | 0.00 | 0.00 | 0.00 |
September | 748.04 | 378.18 | 369.86 | 832.82 | 419.05 | 0.00 | 0.00 | 0.00 |
October | 534.65 | 265.64 | 269.01 | 472.90 | 631.18 | 0.00 | 0.00 | 0.00 |
November | 378.48 | 187.76 | 190.72 | 255.93 | 883.79 | 0.00 | 0.00 | 0.00 |
December | 254.41 | 107.38 | 147.03 | 107.96 | 1198.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 680.02 | 317.70 | 362.32 | 667.50 | 692.88 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 254.41 | 107.38 | 147.03 | 107.96 | 277.84 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1095.11 | 553.38 | 577.99 | 1383.49 | 1300.63 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 278.56 | 112.26 | 166.30 | 122.94 | 1300.61 | 0.00 | 0.00 | 0.00 |
February | 475.47 | 233.72 | 241.75 | 320.66 | 991.29 | 0.00 | 0.00 | 0.00 |
March | 608.48 | 222.96 | 385.53 | 424.21 | 857.06 | 0.00 | 0.00 | 0.00 |
April | 794.38 | 351.95 | 442.43 | 705.95 | 651.97 | 0.00 | 0.00 | 0.00 |
May | 982.59 | 448.11 | 534.48 | 998.32 | 475.73 | 0.00 | 0.00 | 0.00 |
June | 1069.02 | 491.04 | 577.98 | 1231.20 | 329.64 | 0.00 | 0.00 | 0.00 |
July | 1095.09 | 553.37 | 541.73 | 1383.47 | 277.84 | 0.00 | 0.00 | 0.00 |
August | 929.88 | 456.37 | 473.51 | 1131.42 | 311.45 | 0.00 | 0.00 | 0.00 |
September | 748.03 | 378.17 | 369.86 | 832.80 | 419.04 | 0.00 | 0.00 | 0.00 |
October | 534.64 | 265.63 | 269.00 | 472.89 | 631.17 | 0.00 | 0.00 | 0.00 |
November | 378.47 | 187.75 | 190.72 | 255.93 | 883.78 | 0.00 | 0.00 | 0.00 |
December | 254.40 | 107.38 | 147.03 | 107.96 | 1197.98 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 680.01 | 317.70 | 362.31 | 667.49 | 692.87 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 254.40 | 107.38 | 147.03 | 107.96 | 277.84 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1095.09 | 553.37 | 577.98 | 1383.47 | 1300.61 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 602.69 | 0.00 | 602.69 | 13.23 | 5604.05 | 0.00 | 0.00 | 0.00 |
February | 850.97 | 0.00 | 850.97 | 115.82 | 4157.24 | 0.00 | 0.00 | 0.00 |
March | 1382.36 | 0.00 | 1382.36 | 394.42 | 3347.07 | 0.00 | 0.00 | 0.00 |
April | 1576.18 | 9.20 | 1566.98 | 739.36 | 2376.23 | 0.00 | 0.00 | 0.00 |
May | 2069.90 | 122.65 | 1947.25 | 1406.81 | 1768.68 | 0.00 | 0.00 | 0.00 |
June | 2410.29 | 277.04 | 2133.25 | 2344.72 | 1136.48 | 0.00 | 0.00 | 0.00 |
July | 2201.93 | 206.24 | 1995.69 | 2603.97 | 942.51 | 0.00 | 0.00 | 0.00 |
August | 1764.42 | 47.29 | 1717.12 | 1884.60 | 1082.29 | 0.00 | 0.00 | 0.00 |
September | 1321.43 | 0.47 | 1320.95 | 1082.17 | 1638.96 | 0.00 | 0.00 | 0.00 |
October | 963.90 | 0.00 | 963.90 | 384.89 | 2416.79 | 0.00 | 0.00 | 0.00 |
November | 655.27 | 0.00 | 655.27 | 85.52 | 3475.44 | 0.00 | 0.00 | 0.00 |
December | 505.39 | 0.00 | 505.39 | 5.37 | 4783.41 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1361.45 | 55.52 | 1305.94 | 926.82 | 2721.93 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 505.39 | 0.00 | 505.39 | 5.37 | 942.51 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2410.29 | 277.04 | 2133.25 | 2603.97 | 5604.05 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 922.62 | 422.99 | 499.64 | 448.91 | 3440.35 | 0.00 | 0.00 | 0.00 |
February | 1443.07 | 716.45 | 726.62 | 1010.37 | 2551.21 | 0.00 | 0.00 | 0.00 |
March | 1940.33 | 802.86 | 1137.48 | 1473.27 | 2097.69 | 0.00 | 0.00 | 0.00 |
April | 2475.67 | 1226.93 | 1248.75 | 2277.67 | 1512.76 | 0.00 | 0.00 | 0.00 |
May | 2734.70 | 1216.77 | 1517.93 | 2717.26 | 1180.19 | 0.00 | 0.00 | 0.00 |
June | 3539.72 | 1821.54 | 1718.18 | 4109.45 | 776.49 | 0.00 | 0.00 | 0.00 |
July | 3715.04 | 2100.21 | 1614.83 | 4694.01 | 631.00 | 0.00 | 0.00 | 0.00 |
August | 3228.53 | 1798.84 | 1429.69 | 3973.97 | 712.08 | 0.00 | 0.00 | 0.00 |
September | 2283.87 | 1178.92 | 1104.94 | 2521.40 | 1025.92 | 0.00 | 0.00 | 0.00 |
October | 1638.56 | 832.03 | 806.52 | 1471.92 | 1511.19 | 0.00 | 0.00 | 0.00 |
November | 1038.49 | 484.84 | 553.65 | 667.82 | 2117.05 | 0.00 | 0.00 | 0.00 |
December | 765.94 | 328.97 | 436.97 | 347.46 | 2931.63 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 2147.55 | 1079.48 | 1068.07 | 2149.35 | 1704.19 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 765.94 | 328.97 | 436.97 | 347.46 | 631.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 3715.04 | 2100.21 | 1718.18 | 4694.01 | 3440.35 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 4248.33 | 3034.24 | 1214.09 | 3729.86 | 4869.53 | 0.00 | 0.00 | 0.00 |
February | 5410.18 | 3891.20 | 1518.98 | 5268.04 | 3699.49 | 0.00 | 0.00 | 0.00 |
March | 4835.99 | 2715.67 | 2120.32 | 4688.36 | 3311.92 | 0.00 | 0.00 | 0.00 |
April | 3887.33 | 1859.33 | 2027.99 | 3937.57 | 2474.77 | 0.00 | 0.00 | 0.00 |
May | 3453.79 | 1147.10 | 2306.69 | 3562.72 | 1939.71 | 0.00 | 0.00 | 0.00 |
June | 3431.69 | 1000.84 | 2430.85 | 4107.05 | 1326.93 | 0.00 | 0.00 | 0.00 |
July | 3699.71 | 1366.66 | 2333.05 | 4999.33 | 1052.07 | 0.00 | 0.00 | 0.00 |
August | 4396.86 | 2216.82 | 2180.04 | 5757.85 | 1194.48 | 0.00 | 0.00 | 0.00 |
September | 4876.64 | 2988.08 | 1888.57 | 5868.35 | 1705.55 | 0.00 | 0.00 | 0.00 |
October | 5098.27 | 3525.39 | 1572.88 | 5573.95 | 2411.40 | 0.00 | 0.00 | 0.00 |
November | 4648.11 | 3366.91 | 1281.21 | 4584.00 | 3110.73 | 0.00 | 0.00 | 0.00 |
December | 4039.92 | 2917.23 | 1122.69 | 3643.30 | 4144.21 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 4328.10 | 2493.22 | 1834.88 | 4638.44 | 2599.31 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 3431.69 | 1000.84 | 1122.69 | 3562.72 | 1052.07 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 5410.18 | 3891.20 | 2430.85 | 5868.35 | 4869.53 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 835.70 | 336.79 | 498.91 | 390.87 | 3643.29 | 0.00 | 0.00 | 0.00 |
February | 1426.42 | 701.16 | 725.26 | 1017.60 | 2675.64 | 0.00 | 0.00 | 0.00 |
March | 1825.47 | 668.88 | 1156.59 | 1352.34 | 2252.05 | 0.00 | 0.00 | 0.00 |
April | 2383.16 | 1055.85 | 1327.31 | 2212.20 | 1660.20 | 0.00 | 0.00 | 0.00 |
May | 2947.79 | 1344.35 | 1603.44 | 3028.46 | 1307.39 | 0.00 | 0.00 | 0.00 |
June | 3207.09 | 1473.13 | 1733.95 | 3733.50 | 900.79 | 0.00 | 0.00 | 0.00 |
July | 3285.30 | 1660.11 | 1625.19 | 4194.63 | 755.55 | 0.00 | 0.00 | 0.00 |
August | 2789.66 | 1369.11 | 1420.56 | 3454.39 | 815.85 | 0.00 | 0.00 | 0.00 |
September | 2244.11 | 1134.53 | 1109.58 | 2530.14 | 1144.40 | 0.00 | 0.00 | 0.00 |
October | 1603.92 | 796.90 | 807.02 | 1487.65 | 1644.96 | 0.00 | 0.00 | 0.00 |
November | 1135.42 | 563.27 | 572.16 | 832.22 | 2262.20 | 0.00 | 0.00 | 0.00 |
December | 763.21 | 322.13 | 441.08 | 368.74 | 3083.49 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 2040.04 | 953.10 | 1086.94 | 2055.68 | 1842.54 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 763.21 | 322.13 | 441.08 | 368.74 | 755.55 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 3285.30 | 1660.11 | 1733.95 | 4194.63 | 3643.29 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 602.69 | 0.00 | 602.69 | 18.54 | 5455.76 | 0.00 | 0.00 | 0.00 |
February | 850.97 | 0.00 | 850.97 | 140.81 | 3989.84 | 0.00 | 0.00 | 0.00 |
March | 1382.36 | 0.00 | 1382.36 | 433.54 | 3172.67 | 0.00 | 0.00 | 0.00 |
April | 1576.18 | 9.20 | 1566.98 | 790.45 | 2212.58 | 0.00 | 0.00 | 0.00 |
May | 2069.90 | 122.65 | 1947.25 | 1436.62 | 1668.84 | 0.00 | 0.00 | 0.00 |
June | 2410.29 | 277.04 | 2133.25 | 2355.46 | 1103.62 | 0.00 | 0.00 | 0.00 |
July | 2201.93 | 206.24 | 1995.69 | 2600.79 | 925.86 | 0.00 | 0.00 | 0.00 |
August | 1764.42 | 47.29 | 1717.12 | 1886.70 | 1048.91 | 0.00 | 0.00 | 0.00 |
September | 1321.43 | 0.47 | 1320.95 | 1105.12 | 1547.72 | 0.00 | 0.00 | 0.00 |
October | 963.90 | 0.00 | 963.90 | 439.62 | 2216.19 | 0.00 | 0.00 | 0.00 |
November | 655.27 | 0.00 | 655.27 | 109.16 | 3247.39 | 0.00 | 0.00 | 0.00 |
December | 505.39 | 0.00 | 505.39 | 6.54 | 4603.18 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1361.45 | 55.52 | 1305.94 | 948.61 | 2594.22 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 505.39 | 0.00 | 505.39 | 6.54 | 925.86 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2410.29 | 277.04 | 2133.25 | 2600.79 | 5455.76 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 922.62 | 422.99 | 499.64 | 461.90 | 3352.65 | 0.00 | 0.00 | 0.00 |
February | 1443.07 | 716.45 | 726.62 | 1040.74 | 2451.24 | 0.00 | 0.00 | 0.00 |
March | 1940.33 | 802.86 | 1137.48 | 1505.45 | 1996.30 | 0.00 | 0.00 | 0.00 |
April | 2475.67 | 1226.93 | 1248.75 | 2306.82 | 1423.40 | 0.00 | 0.00 | 0.00 |
May | 2734.70 | 1216.77 | 1517.93 | 2727.23 | 1124.99 | 0.00 | 0.00 | 0.00 |
June | 3539.72 | 1821.54 | 1718.18 | 4104.35 | 761.73 | 0.00 | 0.00 | 0.00 |
July | 3715.04 | 2100.21 | 1614.83 | 4682.28 | 623.63 | 0.00 | 0.00 | 0.00 |
August | 3228.53 | 1798.84 | 1429.69 | 3966.56 | 698.39 | 0.00 | 0.00 | 0.00 |
September | 2283.87 | 1178.92 | 1104.94 | 2529.42 | 983.77 | 0.00 | 0.00 | 0.00 |
October | 1638.56 | 832.03 | 806.52 | 1511.47 | 1401.36 | 0.00 | 0.00 | 0.00 |
November | 1038.49 | 484.84 | 553.65 | 701.62 | 1983.92 | 0.00 | 0.00 | 0.00 |
December | 765.94 | 328.97 | 436.97 | 360.27 | 2821.13 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 2147.55 | 1079.48 | 1068.07 | 2164.60 | 1632.30 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 765.94 | 328.97 | 436.97 | 360.27 | 623.63 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 3715.04 | 2100.21 | 1718.18 | 4682.28 | 3352.65 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 4248.33 | 3034.24 | 1214.09 | 3765.06 | 4710.99 | 0.00 | 0.00 | 0.00 |
February | 5410.18 | 3891.20 | 1518.98 | 5313.07 | 3529.05 | 0.00 | 0.00 | 0.00 |
March | 4835.99 | 2715.67 | 2120.32 | 4728.59 | 3142.89 | 0.00 | 0.00 | 0.00 |
April | 3887.33 | 1859.33 | 2027.99 | 3973.02 | 2324.24 | 0.00 | 0.00 | 0.00 |
May | 3453.79 | 1147.10 | 2306.69 | 3577.36 | 1841.99 | 0.00 | 0.00 | 0.00 |
June | 3431.69 | 1000.84 | 2430.85 | 4103.66 | 1289.41 | 0.00 | 0.00 | 0.00 |
July | 3699.71 | 1366.66 | 2333.05 | 4987.78 | 1030.79 | 0.00 | 0.00 | 0.00 |
August | 4396.86 | 2216.82 | 2180.04 | 5747.27 | 1162.31 | 0.00 | 0.00 | 0.00 |
September | 4876.64 | 2988.08 | 1888.57 | 5872.71 | 1628.74 | 0.00 | 0.00 | 0.00 |
October | 5098.27 | 3525.39 | 1572.88 | 5619.24 | 2240.01 | 0.00 | 0.00 | 0.00 |
November | 4648.11 | 3366.91 | 1281.21 | 4650.88 | 2902.88 | 0.00 | 0.00 | 0.00 |
December | 4039.92 | 2917.23 | 1122.69 | 3691.89 | 3960.48 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 4328.10 | 2493.22 | 1834.88 | 4664.13 | 2476.56 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 3431.69 | 1000.84 | 1122.69 | 3577.36 | 1030.79 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 5410.18 | 3891.20 | 2430.85 | 5872.71 | 4710.99 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 835.70 | 336.79 | 498.91 | 398.08 | 3552.78 | 0.00 | 0.00 | 0.00 |
February | 1426.42 | 701.16 | 725.26 | 1031.11 | 2577.63 | 0.00 | 0.00 | 0.00 |
March | 1825.47 | 668.88 | 1156.59 | 1367.16 | 2155.03 | 0.00 | 0.00 | 0.00 |
April | 2383.16 | 1055.85 | 1327.31 | 2231.21 | 1572.00 | 0.00 | 0.00 | 0.00 |
May | 2947.79 | 1344.35 | 1603.44 | 3033.50 | 1246.72 | 0.00 | 0.00 | 0.00 |
June | 3207.09 | 1473.13 | 1733.95 | 3729.16 | 877.94 | 0.00 | 0.00 | 0.00 |
July | 3285.30 | 1660.11 | 1625.19 | 4186.69 | 742.01 | 0.00 | 0.00 | 0.00 |
August | 2789.66 | 1369.11 | 1420.56 | 3449.92 | 795.63 | 0.00 | 0.00 | 0.00 |
September | 2244.11 | 1134.53 | 1109.58 | 2534.93 | 1096.56 | 0.00 | 0.00 | 0.00 |
October | 1603.92 | 796.90 | 807.02 | 1511.23 | 1540.24 | 0.00 | 0.00 | 0.00 |
November | 1135.42 | 563.27 | 572.16 | 850.89 | 2137.49 | 0.00 | 0.00 | 0.00 |
December | 763.21 | 322.13 | 441.08 | 376.10 | 2980.34 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 2040.04 | 953.10 | 1086.94 | 2063.73 | 1770.11 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 763.21 | 322.13 | 441.08 | 376.10 | 742.01 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 3285.30 | 1660.11 | 1733.95 | 4186.69 | 3552.78 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.322855E+09 | 0.00 | 0.322855E+09 | 1993634.24 | 0.319561E+10 |
February | 0.411737E+09 | 0.00 | 0.411737E+09 | 31199354.44 | 0.218841E+10 |
March | 0.740511E+09 | 0.00 | 0.740511E+09 | 0.165190E+09 | 0.197645E+10 |
April | 0.817102E+09 | 4768427.33 | 0.812334E+09 | 0.335588E+09 | 0.138063E+10 |
May | 0.110882E+10 | 65704405.30 | 0.104311E+10 | 0.724053E+09 | 0.102651E+10 |
June | 0.124951E+10 | 0.143620E+09 | 0.110589E+10 | 0.119658E+10 | 0.619763E+09 |
July | 0.117954E+10 | 0.110478E+09 | 0.106907E+10 | 0.137612E+10 | 0.527045E+09 |
August | 0.945175E+09 | 25335095.46 | 0.919840E+09 | 0.988982E+09 | 0.614774E+09 |
September | 0.685036E+09 | 245828.01 | 0.684790E+09 | 0.538769E+09 | 0.918684E+09 |
October | 0.516350E+09 | 0.00 | 0.516350E+09 | 0.168714E+09 | 0.145324E+10 |
November | 0.339697E+09 | 0.00 | 0.339697E+09 | 25602539.88 | 0.203919E+10 |
December | 0.270733E+09 | 0.00 | 0.270733E+09 | 635025.40 | 0.284608E+10 |
Annual Sum or Average | 0.858707E+10 | 0.350153E+09 | 0.823692E+10 | 0.555342E+10 | 0.187864E+11 |
Minimum of Months | 0.270733E+09 | 0.00 | 0.270733E+09 | 635025.40 | 0.527045E+09 |
Maximum of Months | 0.124951E+10 | 0.143620E+09 | 0.110589E+10 | 0.137612E+10 | 0.319561E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.322855E+09 | 0.00 | 0.322855E+09 | 1993615.31 | 0.319561E+10 |
February | 0.411736E+09 | 0.00 | 0.411736E+09 | 31199266.63 | 0.218841E+10 |
March | 0.740511E+09 | 0.00 | 0.740511E+09 | 0.165189E+09 | 0.197645E+10 |
April | 0.817102E+09 | 4768421.61 | 0.812333E+09 | 0.335588E+09 | 0.138063E+10 |
May | 0.110882E+10 | 65704326.46 | 0.104311E+10 | 0.724052E+09 | 0.102651E+10 |
June | 0.124951E+10 | 0.143620E+09 | 0.110589E+10 | 0.119658E+10 | 0.619763E+09 |
July | 0.117954E+10 | 0.110478E+09 | 0.106906E+10 | 0.137612E+10 | 0.527045E+09 |
August | 0.945174E+09 | 25335065.06 | 0.919839E+09 | 0.988981E+09 | 0.614774E+09 |
September | 0.685035E+09 | 245827.72 | 0.684790E+09 | 0.538768E+09 | 0.918684E+09 |
October | 0.516350E+09 | 0.00 | 0.516350E+09 | 0.168714E+09 | 0.145324E+10 |
November | 0.339696E+09 | 0.00 | 0.339696E+09 | 25602449.24 | 0.203919E+10 |
December | 0.270732E+09 | 0.00 | 0.270732E+09 | 635021.06 | 0.284608E+10 |
Annual Sum or Average | 0.858706E+10 | 0.350152E+09 | 0.823691E+10 | 0.555342E+10 | 0.187864E+11 |
Minimum of Months | 0.270732E+09 | 0.00 | 0.270732E+09 | 635021.06 | 0.527045E+09 |
Maximum of Months | 0.124951E+10 | 0.143620E+09 | 0.110589E+10 | 0.137612E+10 | 0.319561E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.322855E+09 | 0.00 | 0.322855E+09 | 1993634.24 | 0.319561E+10 |
February | 0.411737E+09 | 0.00 | 0.411737E+09 | 31199354.44 | 0.218841E+10 |
March | 0.740511E+09 | 0.00 | 0.740511E+09 | 0.165190E+09 | 0.197645E+10 |
April | 0.817102E+09 | 4768427.33 | 0.812334E+09 | 0.335588E+09 | 0.138063E+10 |
May | 0.110882E+10 | 65704405.30 | 0.104311E+10 | 0.724053E+09 | 0.102651E+10 |
June | 0.124951E+10 | 0.143620E+09 | 0.110589E+10 | 0.119658E+10 | 0.619763E+09 |
July | 0.117954E+10 | 0.110478E+09 | 0.106907E+10 | 0.137612E+10 | 0.527045E+09 |
August | 0.945175E+09 | 25335095.46 | 0.919840E+09 | 0.988982E+09 | 0.614774E+09 |
September | 0.685036E+09 | 245828.01 | 0.684790E+09 | 0.538769E+09 | 0.918684E+09 |
October | 0.516350E+09 | 0.00 | 0.516350E+09 | 0.168714E+09 | 0.145324E+10 |
November | 0.339697E+09 | 0.00 | 0.339697E+09 | 25602539.88 | 0.203919E+10 |
December | 0.270733E+09 | 0.00 | 0.270733E+09 | 635025.40 | 0.284608E+10 |
Annual Sum or Average | 0.858707E+10 | 0.350153E+09 | 0.823692E+10 | 0.555342E+10 | 0.187864E+11 |
Minimum of Months | 0.270733E+09 | 0.00 | 0.270733E+09 | 635025.40 | 0.527045E+09 |
Maximum of Months | 0.124951E+10 | 0.143620E+09 | 0.110589E+10 | 0.137612E+10 | 0.319561E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.322855E+09 | 0.00 | 0.322855E+09 | 1993615.31 | 0.319561E+10 |
February | 0.411736E+09 | 0.00 | 0.411736E+09 | 31199266.63 | 0.218841E+10 |
March | 0.740511E+09 | 0.00 | 0.740511E+09 | 0.165189E+09 | 0.197645E+10 |
April | 0.817102E+09 | 4768421.61 | 0.812333E+09 | 0.335588E+09 | 0.138063E+10 |
May | 0.110882E+10 | 65704326.46 | 0.104311E+10 | 0.724052E+09 | 0.102651E+10 |
June | 0.124951E+10 | 0.143620E+09 | 0.110589E+10 | 0.119658E+10 | 0.619763E+09 |
July | 0.117954E+10 | 0.110478E+09 | 0.106906E+10 | 0.137612E+10 | 0.527045E+09 |
August | 0.945174E+09 | 25335065.06 | 0.919839E+09 | 0.988981E+09 | 0.614774E+09 |
September | 0.685035E+09 | 245827.72 | 0.684790E+09 | 0.538768E+09 | 0.918684E+09 |
October | 0.516350E+09 | 0.00 | 0.516350E+09 | 0.168714E+09 | 0.145324E+10 |
November | 0.339696E+09 | 0.00 | 0.339696E+09 | 25602449.24 | 0.203919E+10 |
December | 0.270732E+09 | 0.00 | 0.270732E+09 | 635021.06 | 0.284608E+10 |
Annual Sum or Average | 0.858706E+10 | 0.350152E+09 | 0.823691E+10 | 0.555342E+10 | 0.187864E+11 |
Minimum of Months | 0.270732E+09 | 0.00 | 0.270732E+09 | 635021.06 | 0.527045E+09 |
Maximum of Months | 0.124951E+10 | 0.143620E+09 | 0.110589E+10 | 0.137612E+10 | 0.319561E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.322842E+09 | 0.00 | 0.322842E+09 | 1993553.89 | 0.319548E+10 |
February | 0.411720E+09 | 0.00 | 0.411720E+09 | 31198096.97 | 0.218832E+10 |
March | 0.740481E+09 | 0.00 | 0.740481E+09 | 0.165183E+09 | 0.197637E+10 |
April | 0.817070E+09 | 4768235.14 | 0.812301E+09 | 0.335575E+09 | 0.138057E+10 |
May | 0.110877E+10 | 65701757.12 | 0.104307E+10 | 0.724023E+09 | 0.102647E+10 |
June | 0.124946E+10 | 0.143615E+09 | 0.110584E+10 | 0.119653E+10 | 0.619738E+09 |
July | 0.117950E+10 | 0.110474E+09 | 0.106902E+10 | 0.137606E+10 | 0.527024E+09 |
August | 0.945137E+09 | 25334074.34 | 0.919803E+09 | 0.988942E+09 | 0.614749E+09 |
September | 0.685008E+09 | 245818.10 | 0.684762E+09 | 0.538747E+09 | 0.918647E+09 |
October | 0.516329E+09 | 0.00 | 0.516329E+09 | 0.168707E+09 | 0.145318E+10 |
November | 0.339683E+09 | 0.00 | 0.339683E+09 | 25601507.99 | 0.203911E+10 |
December | 0.270722E+09 | 0.00 | 0.270722E+09 | 634999.80 | 0.284596E+10 |
Annual Sum or Average | 0.858672E+10 | 0.350138E+09 | 0.823658E+10 | 0.555320E+10 | 0.187856E+11 |
Minimum of Months | 0.270722E+09 | 0.00 | 0.270722E+09 | 634999.80 | 0.527024E+09 |
Maximum of Months | 0.124946E+10 | 0.143615E+09 | 0.110584E+10 | 0.137606E+10 | 0.319548E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.823727E+09 | 0.377645E+09 | 0.446082E+09 | 0.378781E+09 | 0.323831E+10 |
February | 0.116370E+10 | 0.577749E+09 | 0.585951E+09 | 0.785555E+09 | 0.219310E+10 |
March | 0.173235E+10 | 0.716797E+09 | 0.101555E+10 | 0.128610E+10 | 0.200254E+10 |
April | 0.213900E+10 | 0.106007E+10 | 0.107893E+10 | 0.195309E+10 | 0.140159E+10 |
May | 0.244157E+10 | 0.108635E+10 | 0.135522E+10 | 0.242376E+10 | 0.112306E+10 |
June | 0.305835E+10 | 0.157382E+10 | 0.148453E+10 | 0.356698E+10 | 0.691213E+09 |
July | 0.331682E+10 | 0.187509E+10 | 0.144173E+10 | 0.421365E+10 | 0.564431E+09 |
August | 0.288246E+10 | 0.160602E+10 | 0.127644E+10 | 0.356790E+10 | 0.635020E+09 |
September | 0.197328E+10 | 0.101860E+10 | 0.954682E+09 | 0.217957E+10 | 0.935961E+09 |
October | 0.146292E+10 | 0.742847E+09 | 0.720071E+09 | 0.128891E+10 | 0.146348E+10 |
November | 0.897261E+09 | 0.418903E+09 | 0.478358E+09 | 0.544321E+09 | 0.199999E+10 |
December | 0.683841E+09 | 0.293711E+09 | 0.390130E+09 | 0.285593E+09 | 0.283336E+10 |
Annual Sum or Average | 0.225753E+11 | 0.113476E+11 | 0.112277E+11 | 0.224742E+11 | 0.190820E+11 |
Minimum of Months | 0.683841E+09 | 0.293711E+09 | 0.390130E+09 | 0.285593E+09 | 0.564431E+09 |
Maximum of Months | 0.331682E+10 | 0.187509E+10 | 0.148453E+10 | 0.421365E+10 | 0.323831E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.823727E+09 | 0.377645E+09 | 0.446082E+09 | 0.378781E+09 | 0.323831E+10 |
February | 0.116370E+10 | 0.577749E+09 | 0.585951E+09 | 0.785555E+09 | 0.219310E+10 |
March | 0.173235E+10 | 0.716797E+09 | 0.101555E+10 | 0.128610E+10 | 0.200254E+10 |
April | 0.213900E+10 | 0.106007E+10 | 0.107893E+10 | 0.195309E+10 | 0.140159E+10 |
May | 0.244157E+10 | 0.108635E+10 | 0.135522E+10 | 0.242376E+10 | 0.112306E+10 |
June | 0.305835E+10 | 0.157382E+10 | 0.148453E+10 | 0.356698E+10 | 0.691213E+09 |
July | 0.331682E+10 | 0.187509E+10 | 0.144173E+10 | 0.421365E+10 | 0.564431E+09 |
August | 0.288246E+10 | 0.160602E+10 | 0.127644E+10 | 0.356790E+10 | 0.635020E+09 |
September | 0.197328E+10 | 0.101860E+10 | 0.954682E+09 | 0.217957E+10 | 0.935961E+09 |
October | 0.146292E+10 | 0.742847E+09 | 0.720071E+09 | 0.128891E+10 | 0.146348E+10 |
November | 0.897261E+09 | 0.418903E+09 | 0.478358E+09 | 0.544321E+09 | 0.199999E+10 |
December | 0.683841E+09 | 0.293711E+09 | 0.390130E+09 | 0.285593E+09 | 0.283336E+10 |
Annual Sum or Average | 0.225753E+11 | 0.113476E+11 | 0.112277E+11 | 0.224742E+11 | 0.190820E+11 |
Minimum of Months | 0.683841E+09 | 0.293711E+09 | 0.390130E+09 | 0.285593E+09 | 0.564431E+09 |
Maximum of Months | 0.331682E+10 | 0.187509E+10 | 0.148453E+10 | 0.421365E+10 | 0.323831E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.823712E+09 | 0.377639E+09 | 0.446073E+09 | 0.378774E+09 | 0.323825E+10 |
February | 0.116368E+10 | 0.577739E+09 | 0.585940E+09 | 0.785541E+09 | 0.219306E+10 |
March | 0.173232E+10 | 0.716784E+09 | 0.101553E+10 | 0.128608E+10 | 0.200250E+10 |
April | 0.213897E+10 | 0.106006E+10 | 0.107891E+10 | 0.195306E+10 | 0.140156E+10 |
May | 0.244152E+10 | 0.108633E+10 | 0.135520E+10 | 0.242372E+10 | 0.112304E+10 |
June | 0.305829E+10 | 0.157380E+10 | 0.148450E+10 | 0.356691E+10 | 0.691200E+09 |
July | 0.331676E+10 | 0.187505E+10 | 0.144171E+10 | 0.421357E+10 | 0.564420E+09 |
August | 0.288241E+10 | 0.160599E+10 | 0.127642E+10 | 0.356784E+10 | 0.635009E+09 |
September | 0.197325E+10 | 0.101858E+10 | 0.954664E+09 | 0.217953E+10 | 0.935944E+09 |
October | 0.146289E+10 | 0.742834E+09 | 0.720058E+09 | 0.128888E+10 | 0.146345E+10 |
November | 0.897244E+09 | 0.418895E+09 | 0.478349E+09 | 0.544311E+09 | 0.199996E+10 |
December | 0.683829E+09 | 0.293706E+09 | 0.390123E+09 | 0.285588E+09 | 0.283331E+10 |
Annual Sum or Average | 0.225749E+11 | 0.113474E+11 | 0.112275E+11 | 0.224738E+11 | 0.190817E+11 |
Minimum of Months | 0.683829E+09 | 0.293706E+09 | 0.390123E+09 | 0.285588E+09 | 0.564420E+09 |
Maximum of Months | 0.331676E+10 | 0.187505E+10 | 0.148450E+10 | 0.421357E+10 | 0.323825E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.227577E+10 | 0.162540E+10 | 0.650370E+09 | 0.200275E+10 | 0.267166E+10 |
February | 0.261769E+10 | 0.188274E+10 | 0.734950E+09 | 0.256241E+10 | 0.184489E+10 |
March | 0.259058E+10 | 0.145475E+10 | 0.113583E+10 | 0.252231E+10 | 0.183863E+10 |
April | 0.201522E+10 | 0.963891E+09 | 0.105133E+10 | 0.204296E+10 | 0.134970E+10 |
May | 0.185015E+10 | 0.614486E+09 | 0.123566E+10 | 0.191485E+10 | 0.108068E+10 |
June | 0.177901E+10 | 0.518844E+09 | 0.126017E+10 | 0.213403E+10 | 0.710980E+09 |
July | 0.198188E+10 | 0.732101E+09 | 0.124978E+10 | 0.268400E+10 | 0.576197E+09 |
August | 0.235534E+10 | 0.118752E+10 | 0.116782E+10 | 0.309637E+10 | 0.653397E+09 |
September | 0.252808E+10 | 0.154904E+10 | 0.979045E+09 | 0.306722E+10 | 0.907244E+09 |
October | 0.273107E+10 | 0.188850E+10 | 0.842571E+09 | 0.300417E+10 | 0.133833E+10 |
November | 0.240961E+10 | 0.174543E+10 | 0.664186E+09 | 0.237739E+10 | 0.168366E+10 |
December | 0.216413E+10 | 0.156272E+10 | 0.601409E+09 | 0.193995E+10 | 0.233055E+10 |
Annual Sum or Average | 0.272985E+11 | 0.157254E+11 | 0.115731E+11 | 0.293484E+11 | 0.169859E+11 |
Minimum of Months | 0.177901E+10 | 0.518844E+09 | 0.601409E+09 | 0.191485E+10 | 0.576197E+09 |
Maximum of Months | 0.273107E+10 | 0.188850E+10 | 0.126017E+10 | 0.309637E+10 | 0.267166E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.227577E+10 | 0.162540E+10 | 0.650369E+09 | 0.200275E+10 | 0.267166E+10 |
February | 0.261769E+10 | 0.188274E+10 | 0.734950E+09 | 0.256241E+10 | 0.184489E+10 |
March | 0.259057E+10 | 0.145475E+10 | 0.113583E+10 | 0.252230E+10 | 0.183863E+10 |
April | 0.201521E+10 | 0.963890E+09 | 0.105132E+10 | 0.204296E+10 | 0.134970E+10 |
May | 0.185015E+10 | 0.614485E+09 | 0.123566E+10 | 0.191485E+10 | 0.108068E+10 |
June | 0.177901E+10 | 0.518843E+09 | 0.126016E+10 | 0.213403E+10 | 0.710980E+09 |
July | 0.198188E+10 | 0.732101E+09 | 0.124978E+10 | 0.268400E+10 | 0.576197E+09 |
August | 0.235534E+10 | 0.118752E+10 | 0.116782E+10 | 0.309637E+10 | 0.653397E+09 |
September | 0.252808E+10 | 0.154904E+10 | 0.979044E+09 | 0.306722E+10 | 0.907244E+09 |
October | 0.273107E+10 | 0.188850E+10 | 0.842571E+09 | 0.300417E+10 | 0.133833E+10 |
November | 0.240961E+10 | 0.174542E+10 | 0.664185E+09 | 0.237739E+10 | 0.168366E+10 |
December | 0.216413E+10 | 0.156272E+10 | 0.601409E+09 | 0.193994E+10 | 0.233055E+10 |
Annual Sum or Average | 0.272985E+11 | 0.157254E+11 | 0.115731E+11 | 0.293484E+11 | 0.169859E+11 |
Minimum of Months | 0.177901E+10 | 0.518843E+09 | 0.601409E+09 | 0.191485E+10 | 0.576197E+09 |
Maximum of Months | 0.273107E+10 | 0.188850E+10 | 0.126016E+10 | 0.309637E+10 | 0.267166E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.227577E+10 | 0.162540E+10 | 0.650370E+09 | 0.200275E+10 | 0.267166E+10 |
February | 0.261769E+10 | 0.188274E+10 | 0.734950E+09 | 0.256241E+10 | 0.184489E+10 |
March | 0.259058E+10 | 0.145475E+10 | 0.113583E+10 | 0.252231E+10 | 0.183863E+10 |
April | 0.201522E+10 | 0.963891E+09 | 0.105133E+10 | 0.204296E+10 | 0.134970E+10 |
May | 0.185015E+10 | 0.614486E+09 | 0.123566E+10 | 0.191485E+10 | 0.108068E+10 |
June | 0.177901E+10 | 0.518844E+09 | 0.126017E+10 | 0.213403E+10 | 0.710980E+09 |
July | 0.198188E+10 | 0.732101E+09 | 0.124978E+10 | 0.268400E+10 | 0.576197E+09 |
August | 0.235534E+10 | 0.118752E+10 | 0.116782E+10 | 0.309637E+10 | 0.653397E+09 |
September | 0.252808E+10 | 0.154904E+10 | 0.979045E+09 | 0.306722E+10 | 0.907244E+09 |
October | 0.273107E+10 | 0.188850E+10 | 0.842571E+09 | 0.300417E+10 | 0.133833E+10 |
November | 0.240961E+10 | 0.174543E+10 | 0.664186E+09 | 0.237739E+10 | 0.168366E+10 |
December | 0.216413E+10 | 0.156272E+10 | 0.601409E+09 | 0.193995E+10 | 0.233055E+10 |
Annual Sum or Average | 0.272985E+11 | 0.157254E+11 | 0.115731E+11 | 0.293484E+11 | 0.169859E+11 |
Minimum of Months | 0.177901E+10 | 0.518844E+09 | 0.601409E+09 | 0.191485E+10 | 0.576197E+09 |
Maximum of Months | 0.273107E+10 | 0.188850E+10 | 0.126017E+10 | 0.309637E+10 | 0.267166E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.227577E+10 | 0.162540E+10 | 0.650369E+09 | 0.200275E+10 | 0.267166E+10 |
February | 0.261769E+10 | 0.188274E+10 | 0.734950E+09 | 0.256241E+10 | 0.184489E+10 |
March | 0.259057E+10 | 0.145475E+10 | 0.113583E+10 | 0.252230E+10 | 0.183863E+10 |
April | 0.201521E+10 | 0.963890E+09 | 0.105132E+10 | 0.204296E+10 | 0.134970E+10 |
May | 0.185015E+10 | 0.614485E+09 | 0.123566E+10 | 0.191485E+10 | 0.108068E+10 |
June | 0.177901E+10 | 0.518843E+09 | 0.126016E+10 | 0.213403E+10 | 0.710980E+09 |
July | 0.198188E+10 | 0.732101E+09 | 0.124978E+10 | 0.268400E+10 | 0.576197E+09 |
August | 0.235534E+10 | 0.118752E+10 | 0.116782E+10 | 0.309637E+10 | 0.653397E+09 |
September | 0.252808E+10 | 0.154904E+10 | 0.979044E+09 | 0.306722E+10 | 0.907244E+09 |
October | 0.273107E+10 | 0.188850E+10 | 0.842571E+09 | 0.300417E+10 | 0.133833E+10 |
November | 0.240961E+10 | 0.174542E+10 | 0.664185E+09 | 0.237739E+10 | 0.168366E+10 |
December | 0.216413E+10 | 0.156272E+10 | 0.601409E+09 | 0.193994E+10 | 0.233055E+10 |
Annual Sum or Average | 0.272985E+11 | 0.157254E+11 | 0.115731E+11 | 0.293484E+11 | 0.169859E+11 |
Minimum of Months | 0.177901E+10 | 0.518843E+09 | 0.601409E+09 | 0.191485E+10 | 0.576197E+09 |
Maximum of Months | 0.273107E+10 | 0.188850E+10 | 0.126016E+10 | 0.309637E+10 | 0.267166E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.227568E+10 | 0.162534E+10 | 0.650343E+09 | 0.200267E+10 | 0.267155E+10 |
February | 0.261759E+10 | 0.188267E+10 | 0.734921E+09 | 0.256231E+10 | 0.184481E+10 |
March | 0.259047E+10 | 0.145469E+10 | 0.113578E+10 | 0.252220E+10 | 0.183855E+10 |
April | 0.201513E+10 | 0.963852E+09 | 0.105128E+10 | 0.204288E+10 | 0.134964E+10 |
May | 0.185008E+10 | 0.614461E+09 | 0.123561E+10 | 0.191477E+10 | 0.108063E+10 |
June | 0.177894E+10 | 0.518823E+09 | 0.126011E+10 | 0.213394E+10 | 0.710951E+09 |
July | 0.198180E+10 | 0.732072E+09 | 0.124973E+10 | 0.268389E+10 | 0.576174E+09 |
August | 0.235524E+10 | 0.118747E+10 | 0.116777E+10 | 0.309625E+10 | 0.653371E+09 |
September | 0.252798E+10 | 0.154898E+10 | 0.979005E+09 | 0.306710E+10 | 0.907207E+09 |
October | 0.273096E+10 | 0.188843E+10 | 0.842537E+09 | 0.300405E+10 | 0.133828E+10 |
November | 0.240951E+10 | 0.174535E+10 | 0.664159E+09 | 0.237729E+10 | 0.168359E+10 |
December | 0.216404E+10 | 0.156266E+10 | 0.601385E+09 | 0.193987E+10 | 0.233046E+10 |
Annual Sum or Average | 0.272974E+11 | 0.157248E+11 | 0.115726E+11 | 0.293472E+11 | 0.169852E+11 |
Minimum of Months | 0.177894E+10 | 0.518823E+09 | 0.601385E+09 | 0.191477E+10 | 0.576174E+09 |
Maximum of Months | 0.273096E+10 | 0.188843E+10 | 0.126011E+10 | 0.309625E+10 | 0.267155E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.746122E+09 | 0.300693E+09 | 0.445429E+09 | 0.329295E+09 | 0.348362E+10 |
February | 0.115027E+10 | 0.565418E+09 | 0.584856E+09 | 0.775758E+09 | 0.239817E+10 |
March | 0.162979E+10 | 0.597181E+09 | 0.103261E+10 | 0.113622E+10 | 0.229560E+10 |
April | 0.205907E+10 | 0.912262E+09 | 0.114681E+10 | 0.182985E+10 | 0.168994E+10 |
May | 0.263182E+10 | 0.120025E+10 | 0.143157E+10 | 0.267396E+10 | 0.127421E+10 |
June | 0.277095E+10 | 0.127280E+10 | 0.149815E+10 | 0.319132E+10 | 0.854449E+09 |
July | 0.293315E+10 | 0.148216E+10 | 0.145098E+10 | 0.370555E+10 | 0.744180E+09 |
August | 0.249064E+10 | 0.122235E+10 | 0.126829E+10 | 0.303045E+10 | 0.834207E+09 |
September | 0.193893E+10 | 0.980245E+09 | 0.958686E+09 | 0.215866E+10 | 0.108617E+10 |
October | 0.143200E+10 | 0.711482E+09 | 0.720515E+09 | 0.126661E+10 | 0.169055E+10 |
November | 0.981017E+09 | 0.486668E+09 | 0.494349E+09 | 0.663380E+09 | 0.229080E+10 |
December | 0.681403E+09 | 0.287601E+09 | 0.393802E+09 | 0.289158E+09 | 0.320873E+10 |
Annual Sum or Average | 0.214452E+11 | 0.100191E+11 | 0.114260E+11 | 0.210502E+11 | 0.218506E+11 |
Minimum of Months | 0.681403E+09 | 0.287601E+09 | 0.393802E+09 | 0.289158E+09 | 0.744180E+09 |
Maximum of Months | 0.293315E+10 | 0.148216E+10 | 0.149815E+10 | 0.370555E+10 | 0.348362E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.746122E+09 | 0.300693E+09 | 0.445429E+09 | 0.329295E+09 | 0.348362E+10 |
February | 0.115027E+10 | 0.565418E+09 | 0.584856E+09 | 0.775758E+09 | 0.239817E+10 |
March | 0.162979E+10 | 0.597181E+09 | 0.103261E+10 | 0.113622E+10 | 0.229560E+10 |
April | 0.205907E+10 | 0.912262E+09 | 0.114681E+10 | 0.182985E+10 | 0.168994E+10 |
May | 0.263182E+10 | 0.120025E+10 | 0.143157E+10 | 0.267396E+10 | 0.127421E+10 |
June | 0.277095E+10 | 0.127280E+10 | 0.149815E+10 | 0.319132E+10 | 0.854449E+09 |
July | 0.293315E+10 | 0.148216E+10 | 0.145098E+10 | 0.370555E+10 | 0.744180E+09 |
August | 0.249064E+10 | 0.122235E+10 | 0.126829E+10 | 0.303045E+10 | 0.834207E+09 |
September | 0.193893E+10 | 0.980245E+09 | 0.958686E+09 | 0.215866E+10 | 0.108617E+10 |
October | 0.143200E+10 | 0.711482E+09 | 0.720515E+09 | 0.126661E+10 | 0.169055E+10 |
November | 0.981017E+09 | 0.486668E+09 | 0.494349E+09 | 0.663380E+09 | 0.229080E+10 |
December | 0.681403E+09 | 0.287601E+09 | 0.393802E+09 | 0.289158E+09 | 0.320873E+10 |
Annual Sum or Average | 0.214452E+11 | 0.100191E+11 | 0.114260E+11 | 0.210502E+11 | 0.218506E+11 |
Minimum of Months | 0.681403E+09 | 0.287601E+09 | 0.393802E+09 | 0.289158E+09 | 0.744180E+09 |
Maximum of Months | 0.293315E+10 | 0.148216E+10 | 0.149815E+10 | 0.370555E+10 | 0.348362E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.746108E+09 | 0.300687E+09 | 0.445421E+09 | 0.329289E+09 | 0.348355E+10 |
February | 0.115025E+10 | 0.565408E+09 | 0.584845E+09 | 0.775744E+09 | 0.239812E+10 |
March | 0.162976E+10 | 0.597170E+09 | 0.103259E+10 | 0.113620E+10 | 0.229555E+10 |
April | 0.205903E+10 | 0.912245E+09 | 0.114678E+10 | 0.182981E+10 | 0.168991E+10 |
May | 0.263177E+10 | 0.120023E+10 | 0.143154E+10 | 0.267391E+10 | 0.127419E+10 |
June | 0.277090E+10 | 0.127278E+10 | 0.149812E+10 | 0.319126E+10 | 0.854433E+09 |
July | 0.293309E+10 | 0.148214E+10 | 0.145096E+10 | 0.370548E+10 | 0.744166E+09 |
August | 0.249059E+10 | 0.122233E+10 | 0.126826E+10 | 0.303040E+10 | 0.834191E+09 |
September | 0.193890E+10 | 0.980227E+09 | 0.958669E+09 | 0.215863E+10 | 0.108615E+10 |
October | 0.143197E+10 | 0.711469E+09 | 0.720502E+09 | 0.126658E+10 | 0.169052E+10 |
November | 0.980999E+09 | 0.486659E+09 | 0.494340E+09 | 0.663368E+09 | 0.229075E+10 |
December | 0.681391E+09 | 0.287596E+09 | 0.393795E+09 | 0.289153E+09 | 0.320867E+10 |
Annual Sum or Average | 0.214448E+11 | 0.100189E+11 | 0.114258E+11 | 0.210498E+11 | 0.218502E+11 |
Minimum of Months | 0.681391E+09 | 0.287596E+09 | 0.393795E+09 | 0.289153E+09 | 0.744166E+09 |
Maximum of Months | 0.293309E+10 | 0.148214E+10 | 0.149812E+10 | 0.370548E+10 | 0.348355E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.161426E+10 | 0.00 | 0.161426E+10 | 35444382.29 | 0.150099E+11 |
February | 0.205866E+10 | 0.00 | 0.205866E+10 | 0.280202E+09 | 0.100572E+11 |
March | 0.370251E+10 | 0.00 | 0.370251E+10 | 0.105642E+10 | 0.896479E+10 |
April | 0.408546E+10 | 23841848.37 | 0.406162E+10 | 0.191643E+10 | 0.615918E+10 |
May | 0.554403E+10 | 0.328518E+09 | 0.521551E+10 | 0.376801E+10 | 0.473724E+10 |
June | 0.624747E+10 | 0.718093E+09 | 0.552937E+10 | 0.607753E+10 | 0.294575E+10 |
July | 0.589765E+10 | 0.552386E+09 | 0.534526E+10 | 0.697447E+10 | 0.252443E+10 |
August | 0.472582E+10 | 0.126674E+09 | 0.459914E+10 | 0.504771E+10 | 0.289880E+10 |
September | 0.342514E+10 | 1229125.19 | 0.342391E+10 | 0.280500E+10 | 0.424818E+10 |
October | 0.258172E+10 | 0.00 | 0.258172E+10 | 0.103089E+10 | 0.647314E+10 |
November | 0.169846E+10 | 0.00 | 0.169846E+10 | 0.221677E+09 | 0.900835E+10 |
December | 0.135365E+10 | 0.00 | 0.135365E+10 | 14393576.88 | 0.128119E+11 |
Annual Sum or Average | 0.429348E+11 | 0.175074E+10 | 0.411841E+11 | 0.292282E+11 | 0.858388E+11 |
Minimum of Months | 0.135365E+10 | 0.00 | 0.135365E+10 | 14393576.88 | 0.252443E+10 |
Maximum of Months | 0.624747E+10 | 0.718093E+09 | 0.552937E+10 | 0.697447E+10 | 0.150099E+11 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.247116E+10 | 0.113292E+10 | 0.133823E+10 | 0.120235E+10 | 0.921462E+10 |
February | 0.349106E+10 | 0.173323E+10 | 0.175783E+10 | 0.244430E+10 | 0.617189E+10 |
March | 0.519699E+10 | 0.215037E+10 | 0.304662E+10 | 0.394601E+10 | 0.561845E+10 |
April | 0.641695E+10 | 0.318019E+10 | 0.323676E+10 | 0.590371E+10 | 0.392108E+10 |
May | 0.732463E+10 | 0.325900E+10 | 0.406563E+10 | 0.727791E+10 | 0.316102E+10 |
June | 0.917496E+10 | 0.472143E+10 | 0.445353E+10 | 0.106517E+11 | 0.201267E+10 |
July | 0.995035E+10 | 0.562520E+10 | 0.432515E+10 | 0.125724E+11 | 0.169006E+10 |
August | 0.864730E+10 | 0.481801E+10 | 0.382929E+10 | 0.106439E+11 | 0.190725E+10 |
September | 0.591979E+10 | 0.305577E+10 | 0.286402E+10 | 0.653546E+10 | 0.265918E+10 |
October | 0.438871E+10 | 0.222852E+10 | 0.216019E+10 | 0.394239E+10 | 0.404758E+10 |
November | 0.269175E+10 | 0.125670E+10 | 0.143506E+10 | 0.173099E+10 | 0.548740E+10 |
December | 0.205150E+10 | 0.881125E+09 | 0.117038E+10 | 0.930642E+09 | 0.785207E+10 |
Annual Sum or Average | 0.677252E+11 | 0.340425E+11 | 0.336827E+11 | 0.677818E+11 | 0.537433E+11 |
Minimum of Months | 0.205150E+10 | 0.881125E+09 | 0.117038E+10 | 0.930642E+09 | 0.169006E+10 |
Maximum of Months | 0.995035E+10 | 0.562520E+10 | 0.445353E+10 | 0.125724E+11 | 0.921462E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.113787E+11 | 0.812691E+10 | 0.325181E+10 | 0.999006E+10 | 0.130426E+11 |
February | 0.130883E+11 | 0.941360E+10 | 0.367471E+10 | 0.127444E+11 | 0.894980E+10 |
March | 0.129527E+11 | 0.727366E+10 | 0.567907E+10 | 0.125573E+11 | 0.887065E+10 |
April | 0.100760E+11 | 0.481940E+10 | 0.525656E+10 | 0.102062E+11 | 0.641459E+10 |
May | 0.925064E+10 | 0.307239E+10 | 0.617825E+10 | 0.954239E+10 | 0.519532E+10 |
June | 0.889494E+10 | 0.259419E+10 | 0.630075E+10 | 0.106455E+11 | 0.343940E+10 |
July | 0.990930E+10 | 0.366046E+10 | 0.624883E+10 | 0.133902E+11 | 0.281787E+10 |
August | 0.117765E+11 | 0.593752E+10 | 0.583902E+10 | 0.154218E+11 | 0.319929E+10 |
September | 0.126403E+11 | 0.774510E+10 | 0.489516E+10 | 0.152108E+11 | 0.442079E+10 |
October | 0.136552E+11 | 0.944240E+10 | 0.421281E+10 | 0.149293E+11 | 0.645869E+10 |
November | 0.120479E+11 | 0.872702E+10 | 0.332089E+10 | 0.118817E+11 | 0.806301E+10 |
December | 0.108205E+11 | 0.781351E+10 | 0.300701E+10 | 0.975821E+10 | 0.110999E+11 |
Annual Sum or Average | 0.136491E+12 | 0.786262E+11 | 0.578649E+11 | 0.146278E+12 | 0.819718E+11 |
Minimum of Months | 0.889494E+10 | 0.259419E+10 | 0.300701E+10 | 0.954239E+10 | 0.281787E+10 |
Maximum of Months | 0.136552E+11 | 0.944240E+10 | 0.630075E+10 | 0.154218E+11 | 0.130426E+11 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.223834E+10 | 0.902069E+09 | 0.133627E+10 | 0.104690E+10 | 0.975818E+10 |
February | 0.345079E+10 | 0.169624E+10 | 0.175455E+10 | 0.246178E+10 | 0.647291E+10 |
March | 0.488933E+10 | 0.179152E+10 | 0.309780E+10 | 0.362210E+10 | 0.603190E+10 |
April | 0.617714E+10 | 0.273676E+10 | 0.344038E+10 | 0.573403E+10 | 0.430323E+10 |
May | 0.789537E+10 | 0.360071E+10 | 0.429466E+10 | 0.811144E+10 | 0.350171E+10 |
June | 0.831276E+10 | 0.381836E+10 | 0.449440E+10 | 0.967724E+10 | 0.233485E+10 |
July | 0.879935E+10 | 0.444644E+10 | 0.435291E+10 | 0.112349E+11 | 0.202367E+10 |
August | 0.747184E+10 | 0.366702E+10 | 0.380482E+10 | 0.925223E+10 | 0.218518E+10 |
September | 0.581673E+10 | 0.294070E+10 | 0.287603E+10 | 0.655812E+10 | 0.296628E+10 |
October | 0.429595E+10 | 0.213442E+10 | 0.216152E+10 | 0.398451E+10 | 0.440586E+10 |
November | 0.294302E+10 | 0.145999E+10 | 0.148303E+10 | 0.215712E+10 | 0.586361E+10 |
December | 0.204419E+10 | 0.862794E+09 | 0.118139E+10 | 0.987624E+09 | 0.825883E+10 |
Annual Sum or Average | 0.643348E+11 | 0.300570E+11 | 0.342778E+11 | 0.648280E+11 | 0.581062E+11 |
Minimum of Months | 0.204419E+10 | 0.862794E+09 | 0.118139E+10 | 0.987624E+09 | 0.202367E+10 |
Maximum of Months | 0.879935E+10 | 0.444644E+10 | 0.449440E+10 | 0.112349E+11 | 0.975818E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.161426E+10 | 0.00 | 0.161426E+10 | 49645873.01 | 0.146127E+11 |
February | 0.205866E+10 | 0.00 | 0.205866E+10 | 0.340649E+09 | 0.965221E+10 |
March | 0.370251E+10 | 0.00 | 0.370251E+10 | 0.116120E+10 | 0.849767E+10 |
April | 0.408546E+10 | 23841848.37 | 0.406162E+10 | 0.204886E+10 | 0.573501E+10 |
May | 0.554403E+10 | 0.328518E+09 | 0.521551E+10 | 0.384783E+10 | 0.446983E+10 |
June | 0.624747E+10 | 0.718093E+09 | 0.552937E+10 | 0.610535E+10 | 0.286057E+10 |
July | 0.589765E+10 | 0.552386E+09 | 0.534526E+10 | 0.696595E+10 | 0.247983E+10 |
August | 0.472582E+10 | 0.126674E+09 | 0.459914E+10 | 0.505334E+10 | 0.280939E+10 |
September | 0.342514E+10 | 1229125.19 | 0.342391E+10 | 0.286448E+10 | 0.401170E+10 |
October | 0.258172E+10 | 0.00 | 0.258172E+10 | 0.117748E+10 | 0.593584E+10 |
November | 0.169846E+10 | 0.00 | 0.169846E+10 | 0.282933E+09 | 0.841724E+10 |
December | 0.135365E+10 | 0.00 | 0.135365E+10 | 17516774.46 | 0.123292E+11 |
Annual Sum or Average | 0.429348E+11 | 0.175074E+10 | 0.411841E+11 | 0.299152E+11 | 0.818112E+11 |
Minimum of Months | 0.135365E+10 | 0.00 | 0.135365E+10 | 17516774.46 | 0.247983E+10 |
Maximum of Months | 0.624747E+10 | 0.718093E+09 | 0.552937E+10 | 0.696595E+10 | 0.146127E+11 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.247116E+10 | 0.113292E+10 | 0.133823E+10 | 0.123716E+10 | 0.897974E+10 |
February | 0.349106E+10 | 0.173323E+10 | 0.175783E+10 | 0.251777E+10 | 0.593003E+10 |
March | 0.519699E+10 | 0.215037E+10 | 0.304662E+10 | 0.403221E+10 | 0.534690E+10 |
April | 0.641695E+10 | 0.318019E+10 | 0.323676E+10 | 0.597928E+10 | 0.368945E+10 |
May | 0.732463E+10 | 0.325900E+10 | 0.406563E+10 | 0.730461E+10 | 0.301317E+10 |
June | 0.917496E+10 | 0.472143E+10 | 0.445353E+10 | 0.106385E+11 | 0.197440E+10 |
July | 0.995035E+10 | 0.562520E+10 | 0.432515E+10 | 0.125410E+11 | 0.167033E+10 |
August | 0.864730E+10 | 0.481801E+10 | 0.382929E+10 | 0.106240E+11 | 0.187056E+10 |
September | 0.591979E+10 | 0.305577E+10 | 0.286402E+10 | 0.655627E+10 | 0.254992E+10 |
October | 0.438871E+10 | 0.222852E+10 | 0.216019E+10 | 0.404832E+10 | 0.375340E+10 |
November | 0.269175E+10 | 0.125670E+10 | 0.143506E+10 | 0.181860E+10 | 0.514232E+10 |
December | 0.205150E+10 | 0.881125E+09 | 0.117038E+10 | 0.964940E+09 | 0.755611E+10 |
Annual Sum or Average | 0.677252E+11 | 0.340425E+11 | 0.336827E+11 | 0.682627E+11 | 0.514763E+11 |
Minimum of Months | 0.205150E+10 | 0.881125E+09 | 0.117038E+10 | 0.964940E+09 | 0.167033E+10 |
Maximum of Months | 0.995035E+10 | 0.562520E+10 | 0.445353E+10 | 0.125410E+11 | 0.897974E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.113787E+11 | 0.812691E+10 | 0.325181E+10 | 0.100843E+11 | 0.126179E+11 |
February | 0.130883E+11 | 0.941360E+10 | 0.367471E+10 | 0.128534E+11 | 0.853748E+10 |
March | 0.129527E+11 | 0.727366E+10 | 0.567907E+10 | 0.126651E+11 | 0.841790E+10 |
April | 0.100760E+11 | 0.481940E+10 | 0.525656E+10 | 0.102981E+11 | 0.602444E+10 |
May | 0.925064E+10 | 0.307239E+10 | 0.617825E+10 | 0.958160E+10 | 0.493359E+10 |
June | 0.889494E+10 | 0.259419E+10 | 0.630075E+10 | 0.106367E+11 | 0.334216E+10 |
July | 0.990930E+10 | 0.366046E+10 | 0.624883E+10 | 0.133593E+11 | 0.276087E+10 |
August | 0.117765E+11 | 0.593752E+10 | 0.583902E+10 | 0.153935E+11 | 0.311312E+10 |
September | 0.126403E+11 | 0.774510E+10 | 0.489516E+10 | 0.152221E+11 | 0.422168E+10 |
October | 0.136552E+11 | 0.944240E+10 | 0.421281E+10 | 0.150506E+11 | 0.599964E+10 |
November | 0.120479E+11 | 0.872702E+10 | 0.332089E+10 | 0.120551E+11 | 0.752427E+10 |
December | 0.108205E+11 | 0.781351E+10 | 0.300701E+10 | 0.988835E+10 | 0.106078E+11 |
Annual Sum or Average | 0.136491E+12 | 0.786262E+11 | 0.578649E+11 | 0.147088E+12 | 0.781008E+11 |
Minimum of Months | 0.889494E+10 | 0.259419E+10 | 0.300701E+10 | 0.958160E+10 | 0.276087E+10 |
Maximum of Months | 0.136552E+11 | 0.944240E+10 | 0.630075E+10 | 0.153935E+11 | 0.126179E+11 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.223834E+10 | 0.902069E+09 | 0.133627E+10 | 0.106621E+10 | 0.951577E+10 |
February | 0.345079E+10 | 0.169624E+10 | 0.175455E+10 | 0.249445E+10 | 0.623581E+10 |
March | 0.488933E+10 | 0.179152E+10 | 0.309780E+10 | 0.366181E+10 | 0.577203E+10 |
April | 0.617714E+10 | 0.273676E+10 | 0.344038E+10 | 0.578330E+10 | 0.407461E+10 |
May | 0.789537E+10 | 0.360071E+10 | 0.429466E+10 | 0.812493E+10 | 0.333921E+10 |
June | 0.831276E+10 | 0.381836E+10 | 0.449440E+10 | 0.966599E+10 | 0.227562E+10 |
July | 0.879935E+10 | 0.444644E+10 | 0.435291E+10 | 0.112136E+11 | 0.198739E+10 |
August | 0.747184E+10 | 0.366702E+10 | 0.380482E+10 | 0.924027E+10 | 0.213103E+10 |
September | 0.581673E+10 | 0.294070E+10 | 0.287603E+10 | 0.657055E+10 | 0.284228E+10 |
October | 0.429595E+10 | 0.213442E+10 | 0.216152E+10 | 0.404768E+10 | 0.412537E+10 |
November | 0.294302E+10 | 0.145999E+10 | 0.148303E+10 | 0.220551E+10 | 0.554038E+10 |
December | 0.204419E+10 | 0.862794E+09 | 0.118139E+10 | 0.100735E+10 | 0.798254E+10 |
Annual Sum or Average | 0.643348E+11 | 0.300570E+11 | 0.342778E+11 | 0.650817E+11 | 0.558221E+11 |
Minimum of Months | 0.204419E+10 | 0.862794E+09 | 0.118139E+10 | 0.100735E+10 | 0.198739E+10 |
Maximum of Months | 0.879935E+10 | 0.444644E+10 | 0.449440E+10 | 0.112136E+11 | 0.951577E+10 |
Report: WindowZoneSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 3.72 | 5965.47 | 602.70 | 0.00 | 602.70 | 0.00 | 0.00 |
February | 64.48 | 4522.96 | 850.97 | 0.00 | 850.97 | 0.00 | 0.00 |
March | 308.37 | 3689.58 | 1382.36 | 0.00 | 1382.36 | 0.00 | 0.00 |
April | 647.35 | 2663.22 | 1576.19 | 9.20 | 1566.99 | 0.00 | 0.00 |
May | 1351.64 | 1916.27 | 2069.91 | 122.66 | 1947.26 | 0.00 | 0.00 |
June | 2308.19 | 1195.52 | 2410.30 | 277.04 | 2133.25 | 0.00 | 0.00 |
July | 2568.90 | 983.87 | 2201.94 | 206.24 | 1995.70 | 0.00 | 0.00 |
August | 1846.20 | 1147.64 | 1764.42 | 47.29 | 1717.13 | 0.00 | 0.00 |
September | 1039.28 | 1772.14 | 1321.43 | 0.47 | 1320.96 | 0.00 | 0.00 |
October | 314.95 | 2712.86 | 963.91 | 0.00 | 963.91 | 0.00 | 0.00 |
November | 49.39 | 3933.59 | 655.27 | 0.00 | 655.27 | 0.00 | 0.00 |
December | 1.19 | 5312.98 | 505.40 | 0.00 | 505.40 | 0.00 | 0.00 |
Annual Sum or Average | 880.48 | 2978.54 | 1361.46 | 55.52 | 1305.94 | 0.00 | 0.00 |
Minimum of Months | 1.19 | 983.87 | 505.40 | 0.00 | 505.40 | 0.00 | 0.00 |
Maximum of Months | 2568.90 | 5965.47 | 2410.30 | 277.04 | 2133.25 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 424.26 | 3627.12 | 922.63 | 422.99 | 499.64 | 0.00 | 0.00 |
February | 974.14 | 2719.60 | 1443.07 | 716.45 | 726.62 | 0.00 | 0.00 |
March | 1440.52 | 2242.97 | 1940.34 | 802.86 | 1137.48 | 0.00 | 0.00 |
April | 2260.51 | 1622.20 | 2475.68 | 1226.93 | 1248.75 | 0.00 | 0.00 |
May | 2714.77 | 1257.90 | 2734.72 | 1216.78 | 1517.94 | 0.00 | 0.00 |
June | 4128.42 | 800.01 | 3539.73 | 1821.55 | 1718.19 | 0.00 | 0.00 |
July | 4719.56 | 632.20 | 3715.05 | 2100.22 | 1614.83 | 0.00 | 0.00 |
August | 3996.28 | 711.26 | 3228.55 | 1798.85 | 1429.70 | 0.00 | 0.00 |
September | 2522.64 | 1083.28 | 2283.88 | 1178.93 | 1104.95 | 0.00 | 0.00 |
October | 1443.66 | 1639.19 | 1638.56 | 832.04 | 806.53 | 0.00 | 0.00 |
November | 630.00 | 2314.79 | 1038.49 | 484.84 | 553.65 | 0.00 | 0.00 |
December | 319.88 | 3173.55 | 765.95 | 328.98 | 436.97 | 0.00 | 0.00 |
Annual Sum or Average | 2137.95 | 1815.25 | 2147.56 | 1079.48 | 1068.08 | 0.00 | 0.00 |
Minimum of Months | 319.88 | 632.20 | 765.95 | 328.98 | 436.97 | 0.00 | 0.00 |
Maximum of Months | 4719.56 | 3627.12 | 3715.05 | 2100.22 | 1718.19 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 3738.68 | 4987.38 | 4248.34 | 3034.25 | 1214.09 | 0.00 | 0.00 |
February | 5295.95 | 3812.98 | 5410.20 | 3891.22 | 1518.98 | 0.00 | 0.00 |
March | 4708.57 | 3432.30 | 4836.01 | 2715.68 | 2120.33 | 0.00 | 0.00 |
April | 3940.86 | 2603.56 | 3887.34 | 1859.34 | 2028.00 | 0.00 | 0.00 |
May | 3574.58 | 2017.38 | 3453.81 | 1147.10 | 2306.70 | 0.00 | 0.00 |
June | 4116.53 | 1371.48 | 3431.70 | 1000.85 | 2430.85 | 0.00 | 0.00 |
July | 5010.42 | 1075.63 | 3699.72 | 1366.67 | 2333.06 | 0.00 | 0.00 |
August | 5780.21 | 1219.74 | 4396.87 | 2216.82 | 2180.05 | 0.00 | 0.00 |
September | 5916.66 | 1750.07 | 4876.66 | 2988.09 | 1888.57 | 0.00 | 0.00 |
October | 5608.10 | 2498.36 | 5098.29 | 3525.40 | 1572.89 | 0.00 | 0.00 |
November | 4585.97 | 3247.78 | 4648.13 | 3366.92 | 1281.21 | 0.00 | 0.00 |
December | 3621.44 | 4350.61 | 4039.93 | 2917.24 | 1122.69 | 0.00 | 0.00 |
Annual Sum or Average | 4653.12 | 2693.08 | 4328.12 | 2493.23 | 1834.89 | 0.00 | 0.00 |
Minimum of Months | 3574.58 | 1075.63 | 3431.70 | 1000.85 | 1122.69 | 0.00 | 0.00 |
Maximum of Months | 5916.66 | 4987.38 | 5410.20 | 3891.22 | 2430.85 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 368.83 | 3901.88 | 835.70 | 336.80 | 498.91 | 0.00 | 0.00 |
February | 962.00 | 2973.90 | 1426.42 | 701.16 | 725.26 | 0.00 | 0.00 |
March | 1272.64 | 2571.22 | 1825.47 | 668.88 | 1156.59 | 0.00 | 0.00 |
April | 2117.86 | 1955.94 | 2383.17 | 1055.85 | 1327.31 | 0.00 | 0.00 |
May | 2995.00 | 1427.20 | 2947.80 | 1344.36 | 1603.45 | 0.00 | 0.00 |
June | 3693.64 | 988.94 | 3207.10 | 1473.14 | 1733.96 | 0.00 | 0.00 |
July | 4150.45 | 833.53 | 3285.32 | 1660.12 | 1625.20 | 0.00 | 0.00 |
August | 3394.31 | 934.37 | 2789.68 | 1369.11 | 1420.56 | 0.00 | 0.00 |
September | 2498.44 | 1257.13 | 2244.12 | 1134.54 | 1109.58 | 0.00 | 0.00 |
October | 1418.68 | 1893.53 | 1603.93 | 796.91 | 807.02 | 0.00 | 0.00 |
November | 767.80 | 2651.37 | 1135.43 | 563.27 | 572.16 | 0.00 | 0.00 |
December | 323.88 | 3593.98 | 763.22 | 322.13 | 441.08 | 0.00 | 0.00 |
Annual Sum or Average | 2002.48 | 2078.62 | 2040.05 | 953.11 | 1086.95 | 0.00 | 0.00 |
Minimum of Months | 323.88 | 833.53 | 763.22 | 322.13 | 441.08 | 0.00 | 0.00 |
Maximum of Months | 4150.45 | 3901.88 | 3285.32 | 1660.12 | 1733.96 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 13.23 | 5604.05 | 602.69 | 0.00 | 602.69 | 0.00 | 0.00 |
February | 115.82 | 4157.24 | 850.97 | 0.00 | 850.97 | 0.00 | 0.00 |
March | 394.42 | 3347.07 | 1382.36 | 0.00 | 1382.36 | 0.00 | 0.00 |
April | 739.36 | 2376.23 | 1576.18 | 9.20 | 1566.98 | 0.00 | 0.00 |
May | 1406.81 | 1768.68 | 2069.90 | 122.65 | 1947.25 | 0.00 | 0.00 |
June | 2344.72 | 1136.48 | 2410.29 | 277.04 | 2133.25 | 0.00 | 0.00 |
July | 2603.97 | 942.51 | 2201.93 | 206.24 | 1995.69 | 0.00 | 0.00 |
August | 1884.60 | 1082.29 | 1764.42 | 47.29 | 1717.12 | 0.00 | 0.00 |
September | 1082.17 | 1638.96 | 1321.43 | 0.47 | 1320.95 | 0.00 | 0.00 |
October | 384.89 | 2416.79 | 963.90 | 0.00 | 963.90 | 0.00 | 0.00 |
November | 85.52 | 3475.44 | 655.27 | 0.00 | 655.27 | 0.00 | 0.00 |
December | 5.37 | 4783.41 | 505.39 | 0.00 | 505.39 | 0.00 | 0.00 |
Annual Sum or Average | 926.82 | 2721.93 | 1361.45 | 55.52 | 1305.94 | 0.00 | 0.00 |
Minimum of Months | 5.37 | 942.51 | 505.39 | 0.00 | 505.39 | 0.00 | 0.00 |
Maximum of Months | 2603.97 | 5604.05 | 2410.29 | 277.04 | 2133.25 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 448.91 | 3440.35 | 922.62 | 422.99 | 499.64 | 0.00 | 0.00 |
February | 1010.37 | 2551.21 | 1443.07 | 716.45 | 726.62 | 0.00 | 0.00 |
March | 1473.27 | 2097.69 | 1940.33 | 802.86 | 1137.48 | 0.00 | 0.00 |
April | 2277.67 | 1512.76 | 2475.67 | 1226.93 | 1248.75 | 0.00 | 0.00 |
May | 2717.26 | 1180.19 | 2734.70 | 1216.77 | 1517.93 | 0.00 | 0.00 |
June | 4109.45 | 776.49 | 3539.72 | 1821.54 | 1718.18 | 0.00 | 0.00 |
July | 4694.01 | 631.00 | 3715.04 | 2100.21 | 1614.83 | 0.00 | 0.00 |
August | 3973.97 | 712.08 | 3228.53 | 1798.84 | 1429.69 | 0.00 | 0.00 |
September | 2521.40 | 1025.92 | 2283.87 | 1178.92 | 1104.94 | 0.00 | 0.00 |
October | 1471.92 | 1511.19 | 1638.56 | 832.03 | 806.52 | 0.00 | 0.00 |
November | 667.82 | 2117.05 | 1038.49 | 484.84 | 553.65 | 0.00 | 0.00 |
December | 347.46 | 2931.63 | 765.94 | 328.97 | 436.97 | 0.00 | 0.00 |
Annual Sum or Average | 2149.35 | 1704.19 | 2147.55 | 1079.48 | 1068.07 | 0.00 | 0.00 |
Minimum of Months | 347.46 | 631.00 | 765.94 | 328.97 | 436.97 | 0.00 | 0.00 |
Maximum of Months | 4694.01 | 3440.35 | 3715.04 | 2100.21 | 1718.18 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 3729.86 | 4869.53 | 4248.33 | 3034.24 | 1214.09 | 0.00 | 0.00 |
February | 5268.04 | 3699.49 | 5410.18 | 3891.20 | 1518.98 | 0.00 | 0.00 |
March | 4688.36 | 3311.92 | 4835.99 | 2715.67 | 2120.32 | 0.00 | 0.00 |
April | 3937.57 | 2474.77 | 3887.33 | 1859.33 | 2027.99 | 0.00 | 0.00 |
May | 3562.72 | 1939.71 | 3453.79 | 1147.10 | 2306.69 | 0.00 | 0.00 |
June | 4107.05 | 1326.93 | 3431.69 | 1000.84 | 2430.85 | 0.00 | 0.00 |
July | 4999.33 | 1052.07 | 3699.71 | 1366.66 | 2333.05 | 0.00 | 0.00 |
August | 5757.85 | 1194.48 | 4396.86 | 2216.82 | 2180.04 | 0.00 | 0.00 |
September | 5868.35 | 1705.55 | 4876.64 | 2988.08 | 1888.57 | 0.00 | 0.00 |
October | 5573.95 | 2411.40 | 5098.27 | 3525.39 | 1572.88 | 0.00 | 0.00 |
November | 4584.00 | 3110.73 | 4648.11 | 3366.91 | 1281.21 | 0.00 | 0.00 |
December | 3643.30 | 4144.21 | 4039.92 | 2917.23 | 1122.69 | 0.00 | 0.00 |
Annual Sum or Average | 4638.44 | 2599.31 | 4328.10 | 2493.22 | 1834.88 | 0.00 | 0.00 |
Minimum of Months | 3562.72 | 1052.07 | 3431.69 | 1000.84 | 1122.69 | 0.00 | 0.00 |
Maximum of Months | 5868.35 | 4869.53 | 5410.18 | 3891.20 | 2430.85 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 390.87 | 3643.29 | 835.70 | 336.79 | 498.91 | 0.00 | 0.00 |
February | 1017.60 | 2675.64 | 1426.42 | 701.16 | 725.26 | 0.00 | 0.00 |
March | 1352.34 | 2252.05 | 1825.47 | 668.88 | 1156.59 | 0.00 | 0.00 |
April | 2212.20 | 1660.20 | 2383.16 | 1055.85 | 1327.31 | 0.00 | 0.00 |
May | 3028.46 | 1307.39 | 2947.79 | 1344.35 | 1603.44 | 0.00 | 0.00 |
June | 3733.50 | 900.79 | 3207.09 | 1473.13 | 1733.95 | 0.00 | 0.00 |
July | 4194.63 | 755.55 | 3285.30 | 1660.11 | 1625.19 | 0.00 | 0.00 |
August | 3454.39 | 815.85 | 2789.66 | 1369.11 | 1420.56 | 0.00 | 0.00 |
September | 2530.14 | 1144.40 | 2244.11 | 1134.53 | 1109.58 | 0.00 | 0.00 |
October | 1487.65 | 1644.96 | 1603.92 | 796.90 | 807.02 | 0.00 | 0.00 |
November | 832.22 | 2262.20 | 1135.42 | 563.27 | 572.16 | 0.00 | 0.00 |
December | 368.74 | 3083.49 | 763.21 | 322.13 | 441.08 | 0.00 | 0.00 |
Annual Sum or Average | 2055.68 | 1842.54 | 2040.04 | 953.10 | 1086.94 | 0.00 | 0.00 |
Minimum of Months | 368.74 | 755.55 | 763.21 | 322.13 | 441.08 | 0.00 | 0.00 |
Maximum of Months | 4194.63 | 3643.29 | 3285.30 | 1660.11 | 1733.95 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 18.54 | 5455.76 | 602.69 | 0.00 | 602.69 | 0.00 | 0.00 |
February | 140.81 | 3989.84 | 850.97 | 0.00 | 850.97 | 0.00 | 0.00 |
March | 433.54 | 3172.67 | 1382.36 | 0.00 | 1382.36 | 0.00 | 0.00 |
April | 790.45 | 2212.58 | 1576.18 | 9.20 | 1566.98 | 0.00 | 0.00 |
May | 1436.62 | 1668.84 | 2069.90 | 122.65 | 1947.25 | 0.00 | 0.00 |
June | 2355.46 | 1103.62 | 2410.29 | 277.04 | 2133.25 | 0.00 | 0.00 |
July | 2600.79 | 925.86 | 2201.93 | 206.24 | 1995.69 | 0.00 | 0.00 |
August | 1886.70 | 1048.91 | 1764.42 | 47.29 | 1717.12 | 0.00 | 0.00 |
September | 1105.12 | 1547.72 | 1321.43 | 0.47 | 1320.95 | 0.00 | 0.00 |
October | 439.62 | 2216.19 | 963.90 | 0.00 | 963.90 | 0.00 | 0.00 |
November | 109.16 | 3247.39 | 655.27 | 0.00 | 655.27 | 0.00 | 0.00 |
December | 6.54 | 4603.18 | 505.39 | 0.00 | 505.39 | 0.00 | 0.00 |
Annual Sum or Average | 948.61 | 2594.22 | 1361.45 | 55.52 | 1305.94 | 0.00 | 0.00 |
Minimum of Months | 6.54 | 925.86 | 505.39 | 0.00 | 505.39 | 0.00 | 0.00 |
Maximum of Months | 2600.79 | 5455.76 | 2410.29 | 277.04 | 2133.25 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 461.90 | 3352.65 | 922.62 | 422.99 | 499.64 | 0.00 | 0.00 |
February | 1040.74 | 2451.24 | 1443.07 | 716.45 | 726.62 | 0.00 | 0.00 |
March | 1505.45 | 1996.30 | 1940.33 | 802.86 | 1137.48 | 0.00 | 0.00 |
April | 2306.82 | 1423.40 | 2475.67 | 1226.93 | 1248.75 | 0.00 | 0.00 |
May | 2727.23 | 1124.99 | 2734.70 | 1216.77 | 1517.93 | 0.00 | 0.00 |
June | 4104.35 | 761.73 | 3539.72 | 1821.54 | 1718.18 | 0.00 | 0.00 |
July | 4682.28 | 623.63 | 3715.04 | 2100.21 | 1614.83 | 0.00 | 0.00 |
August | 3966.56 | 698.39 | 3228.53 | 1798.84 | 1429.69 | 0.00 | 0.00 |
September | 2529.42 | 983.77 | 2283.87 | 1178.92 | 1104.94 | 0.00 | 0.00 |
October | 1511.47 | 1401.36 | 1638.56 | 832.03 | 806.52 | 0.00 | 0.00 |
November | 701.62 | 1983.92 | 1038.49 | 484.84 | 553.65 | 0.00 | 0.00 |
December | 360.27 | 2821.13 | 765.94 | 328.97 | 436.97 | 0.00 | 0.00 |
Annual Sum or Average | 2164.60 | 1632.30 | 2147.55 | 1079.48 | 1068.07 | 0.00 | 0.00 |
Minimum of Months | 360.27 | 623.63 | 765.94 | 328.97 | 436.97 | 0.00 | 0.00 |
Maximum of Months | 4682.28 | 3352.65 | 3715.04 | 2100.21 | 1718.18 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 3765.06 | 4710.99 | 4248.33 | 3034.24 | 1214.09 | 0.00 | 0.00 |
February | 5313.07 | 3529.05 | 5410.18 | 3891.20 | 1518.98 | 0.00 | 0.00 |
March | 4728.59 | 3142.89 | 4835.99 | 2715.67 | 2120.32 | 0.00 | 0.00 |
April | 3973.02 | 2324.24 | 3887.33 | 1859.33 | 2027.99 | 0.00 | 0.00 |
May | 3577.36 | 1841.99 | 3453.79 | 1147.10 | 2306.69 | 0.00 | 0.00 |
June | 4103.66 | 1289.41 | 3431.69 | 1000.84 | 2430.85 | 0.00 | 0.00 |
July | 4987.78 | 1030.79 | 3699.71 | 1366.66 | 2333.05 | 0.00 | 0.00 |
August | 5747.27 | 1162.31 | 4396.86 | 2216.82 | 2180.04 | 0.00 | 0.00 |
September | 5872.71 | 1628.74 | 4876.64 | 2988.08 | 1888.57 | 0.00 | 0.00 |
October | 5619.24 | 2240.01 | 5098.27 | 3525.39 | 1572.88 | 0.00 | 0.00 |
November | 4650.88 | 2902.88 | 4648.11 | 3366.91 | 1281.21 | 0.00 | 0.00 |
December | 3691.89 | 3960.48 | 4039.92 | 2917.23 | 1122.69 | 0.00 | 0.00 |
Annual Sum or Average | 4664.13 | 2476.56 | 4328.10 | 2493.22 | 1834.88 | 0.00 | 0.00 |
Minimum of Months | 3577.36 | 1030.79 | 3431.69 | 1000.84 | 1122.69 | 0.00 | 0.00 |
Maximum of Months | 5872.71 | 4710.99 | 5410.18 | 3891.20 | 2430.85 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 398.08 | 3552.78 | 835.70 | 336.79 | 498.91 | 0.00 | 0.00 |
February | 1031.11 | 2577.63 | 1426.42 | 701.16 | 725.26 | 0.00 | 0.00 |
March | 1367.16 | 2155.03 | 1825.47 | 668.88 | 1156.59 | 0.00 | 0.00 |
April | 2231.21 | 1572.00 | 2383.16 | 1055.85 | 1327.31 | 0.00 | 0.00 |
May | 3033.50 | 1246.72 | 2947.79 | 1344.35 | 1603.44 | 0.00 | 0.00 |
June | 3729.16 | 877.94 | 3207.09 | 1473.13 | 1733.95 | 0.00 | 0.00 |
July | 4186.69 | 742.01 | 3285.30 | 1660.11 | 1625.19 | 0.00 | 0.00 |
August | 3449.92 | 795.63 | 2789.66 | 1369.11 | 1420.56 | 0.00 | 0.00 |
September | 2534.93 | 1096.56 | 2244.11 | 1134.53 | 1109.58 | 0.00 | 0.00 |
October | 1511.23 | 1540.24 | 1603.92 | 796.90 | 807.02 | 0.00 | 0.00 |
November | 850.89 | 2137.49 | 1135.42 | 563.27 | 572.16 | 0.00 | 0.00 |
December | 376.10 | 2980.34 | 763.21 | 322.13 | 441.08 | 0.00 | 0.00 |
Annual Sum or Average | 2063.73 | 1770.11 | 2040.04 | 953.10 | 1086.94 | 0.00 | 0.00 |
Minimum of Months | 376.10 | 742.01 | 763.21 | 322.13 | 441.08 | 0.00 | 0.00 |
Maximum of Months | 4186.69 | 3552.78 | 3285.30 | 1660.11 | 1733.95 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 9968052.98 | 0.159779E+11 | 0.161426E+10 | 0.00 | 0.161426E+10 | 0.00 | 0.00 |
February | 0.155995E+09 | 0.109420E+11 | 0.205867E+10 | 0.00 | 0.205867E+10 | 0.00 | 0.00 |
March | 0.825940E+09 | 0.988218E+10 | 0.370252E+10 | 0.00 | 0.370252E+10 | 0.00 | 0.00 |
April | 0.167793E+10 | 0.690308E+10 | 0.408548E+10 | 23841933.03 | 0.406164E+10 | 0.00 | 0.00 |
May | 0.362023E+10 | 0.513253E+10 | 0.554405E+10 | 0.328519E+09 | 0.521553E+10 | 0.00 | 0.00 |
June | 0.598283E+10 | 0.309879E+10 | 0.624749E+10 | 0.718096E+09 | 0.552939E+10 | 0.00 | 0.00 |
July | 0.688054E+10 | 0.263521E+10 | 0.589767E+10 | 0.552388E+09 | 0.534528E+10 | 0.00 | 0.00 |
August | 0.494487E+10 | 0.307385E+10 | 0.472583E+10 | 0.126674E+09 | 0.459916E+10 | 0.00 | 0.00 |
September | 0.269382E+10 | 0.459338E+10 | 0.342515E+10 | 1229129.56 | 0.342392E+10 | 0.00 | 0.00 |
October | 0.843563E+09 | 0.726614E+10 | 0.258173E+10 | 0.00 | 0.258173E+10 | 0.00 | 0.00 |
November | 0.128011E+09 | 0.101959E+11 | 0.169847E+10 | 0.00 | 0.169847E+10 | 0.00 | 0.00 |
December | 3175092.70 | 0.142303E+11 | 0.135365E+10 | 0.00 | 0.135365E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.277669E+11 | 0.939311E+11 | 0.429350E+11 | 0.175075E+10 | 0.411842E+11 | 0.00 | 0.00 |
Minimum of Months | 3175092.70 | 0.263521E+10 | 0.135365E+10 | 0.00 | 0.135365E+10 | 0.00 | 0.00 |
Maximum of Months | 0.688054E+10 | 0.159779E+11 | 0.624749E+10 | 0.718096E+09 | 0.552939E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.113634E+10 | 0.971488E+10 | 0.247117E+10 | 0.113293E+10 | 0.133824E+10 | 0.00 | 0.00 |
February | 0.235665E+10 | 0.657925E+10 | 0.349108E+10 | 0.173324E+10 | 0.175784E+10 | 0.00 | 0.00 |
March | 0.385828E+10 | 0.600758E+10 | 0.519701E+10 | 0.215038E+10 | 0.304663E+10 | 0.00 | 0.00 |
April | 0.585924E+10 | 0.420474E+10 | 0.641697E+10 | 0.318021E+10 | 0.323677E+10 | 0.00 | 0.00 |
May | 0.727124E+10 | 0.336916E+10 | 0.732466E+10 | 0.325902E+10 | 0.406565E+10 | 0.00 | 0.00 |
June | 0.107009E+11 | 0.207363E+10 | 0.917499E+10 | 0.472145E+10 | 0.445355E+10 | 0.00 | 0.00 |
July | 0.126409E+11 | 0.169328E+10 | 0.995039E+10 | 0.562522E+10 | 0.432517E+10 | 0.00 | 0.00 |
August | 0.107036E+11 | 0.190505E+10 | 0.864734E+10 | 0.481803E+10 | 0.382931E+10 | 0.00 | 0.00 |
September | 0.653868E+10 | 0.280787E+10 | 0.591981E+10 | 0.305578E+10 | 0.286403E+10 | 0.00 | 0.00 |
October | 0.386670E+10 | 0.439040E+10 | 0.438873E+10 | 0.222853E+10 | 0.216020E+10 | 0.00 | 0.00 |
November | 0.163295E+10 | 0.599994E+10 | 0.269177E+10 | 0.125670E+10 | 0.143507E+10 | 0.00 | 0.00 |
December | 0.856775E+09 | 0.850003E+10 | 0.205151E+10 | 0.881129E+09 | 0.117038E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.674222E+11 | 0.572458E+11 | 0.677254E+11 | 0.340426E+11 | 0.336828E+11 | 0.00 | 0.00 |
Minimum of Months | 0.856775E+09 | 0.169328E+10 | 0.205151E+10 | 0.881129E+09 | 0.117038E+10 | 0.00 | 0.00 |
Maximum of Months | 0.126409E+11 | 0.971488E+10 | 0.995039E+10 | 0.562522E+10 | 0.445355E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.100137E+11 | 0.133582E+11 | 0.113788E+11 | 0.812693E+10 | 0.325182E+10 | 0.00 | 0.00 |
February | 0.128120E+11 | 0.922436E+10 | 0.130884E+11 | 0.941363E+10 | 0.367472E+10 | 0.00 | 0.00 |
March | 0.126114E+11 | 0.919307E+10 | 0.129528E+11 | 0.727368E+10 | 0.567909E+10 | 0.00 | 0.00 |
April | 0.102147E+11 | 0.674843E+10 | 0.100760E+11 | 0.481941E+10 | 0.525658E+10 | 0.00 | 0.00 |
May | 0.957416E+10 | 0.540334E+10 | 0.925067E+10 | 0.307240E+10 | 0.617827E+10 | 0.00 | 0.00 |
June | 0.106700E+11 | 0.355487E+10 | 0.889497E+10 | 0.259420E+10 | 0.630078E+10 | 0.00 | 0.00 |
July | 0.134199E+11 | 0.288096E+10 | 0.990933E+10 | 0.366048E+10 | 0.624886E+10 | 0.00 | 0.00 |
August | 0.154817E+11 | 0.326696E+10 | 0.117766E+11 | 0.593754E+10 | 0.583905E+10 | 0.00 | 0.00 |
September | 0.153360E+11 | 0.453618E+10 | 0.126403E+11 | 0.774513E+10 | 0.489518E+10 | 0.00 | 0.00 |
October | 0.150207E+11 | 0.669160E+10 | 0.136553E+11 | 0.944244E+10 | 0.421282E+10 | 0.00 | 0.00 |
November | 0.118868E+11 | 0.841824E+10 | 0.120480E+11 | 0.872705E+10 | 0.332090E+10 | 0.00 | 0.00 |
December | 0.969966E+10 | 0.116527E+11 | 0.108206E+11 | 0.781354E+10 | 0.300702E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.146741E+12 | 0.849289E+11 | 0.136492E+12 | 0.786264E+11 | 0.578651E+11 | 0.00 | 0.00 |
Minimum of Months | 0.957416E+10 | 0.288096E+10 | 0.889497E+10 | 0.259420E+10 | 0.300702E+10 | 0.00 | 0.00 |
Maximum of Months | 0.154817E+11 | 0.133582E+11 | 0.136553E+11 | 0.944244E+10 | 0.630078E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.987878E+09 | 0.104508E+11 | 0.223835E+10 | 0.902072E+09 | 0.133628E+10 | 0.00 | 0.00 |
February | 0.232726E+10 | 0.719446E+10 | 0.345080E+10 | 0.169624E+10 | 0.175456E+10 | 0.00 | 0.00 |
March | 0.340864E+10 | 0.688675E+10 | 0.488935E+10 | 0.179153E+10 | 0.309782E+10 | 0.00 | 0.00 |
April | 0.548950E+10 | 0.506980E+10 | 0.617716E+10 | 0.273677E+10 | 0.344039E+10 | 0.00 | 0.00 |
May | 0.802182E+10 | 0.382261E+10 | 0.789540E+10 | 0.360072E+10 | 0.429468E+10 | 0.00 | 0.00 |
June | 0.957391E+10 | 0.256333E+10 | 0.831280E+10 | 0.381838E+10 | 0.449442E+10 | 0.00 | 0.00 |
July | 0.111166E+11 | 0.223253E+10 | 0.879939E+10 | 0.444646E+10 | 0.435293E+10 | 0.00 | 0.00 |
August | 0.909131E+10 | 0.250260E+10 | 0.747187E+10 | 0.366703E+10 | 0.380483E+10 | 0.00 | 0.00 |
September | 0.647595E+10 | 0.325849E+10 | 0.581676E+10 | 0.294072E+10 | 0.287604E+10 | 0.00 | 0.00 |
October | 0.379980E+10 | 0.507163E+10 | 0.429596E+10 | 0.213443E+10 | 0.216153E+10 | 0.00 | 0.00 |
November | 0.199013E+10 | 0.687235E+10 | 0.294303E+10 | 0.146000E+10 | 0.148304E+10 | 0.00 | 0.00 |
December | 0.867470E+09 | 0.962612E+10 | 0.204420E+10 | 0.862798E+09 | 0.118140E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.631502E+11 | 0.655514E+11 | 0.643351E+11 | 0.300572E+11 | 0.342779E+11 | 0.00 | 0.00 |
Minimum of Months | 0.867470E+09 | 0.223253E+10 | 0.204420E+10 | 0.862798E+09 | 0.118140E+10 | 0.00 | 0.00 |
Maximum of Months | 0.111166E+11 | 0.104508E+11 | 0.879939E+10 | 0.444646E+10 | 0.449442E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 35444382.29 | 0.150099E+11 | 0.161426E+10 | 0.00 | 0.161426E+10 | 0.00 | 0.00 |
February | 0.280202E+09 | 0.100572E+11 | 0.205866E+10 | 0.00 | 0.205866E+10 | 0.00 | 0.00 |
March | 0.105642E+10 | 0.896479E+10 | 0.370251E+10 | 0.00 | 0.370251E+10 | 0.00 | 0.00 |
April | 0.191643E+10 | 0.615918E+10 | 0.408546E+10 | 23841848.37 | 0.406162E+10 | 0.00 | 0.00 |
May | 0.376801E+10 | 0.473724E+10 | 0.554403E+10 | 0.328518E+09 | 0.521551E+10 | 0.00 | 0.00 |
June | 0.607753E+10 | 0.294575E+10 | 0.624747E+10 | 0.718093E+09 | 0.552937E+10 | 0.00 | 0.00 |
July | 0.697447E+10 | 0.252443E+10 | 0.589765E+10 | 0.552386E+09 | 0.534526E+10 | 0.00 | 0.00 |
August | 0.504771E+10 | 0.289880E+10 | 0.472582E+10 | 0.126674E+09 | 0.459914E+10 | 0.00 | 0.00 |
September | 0.280500E+10 | 0.424818E+10 | 0.342514E+10 | 1229125.19 | 0.342391E+10 | 0.00 | 0.00 |
October | 0.103089E+10 | 0.647314E+10 | 0.258172E+10 | 0.00 | 0.258172E+10 | 0.00 | 0.00 |
November | 0.221677E+09 | 0.900835E+10 | 0.169846E+10 | 0.00 | 0.169846E+10 | 0.00 | 0.00 |
December | 14393576.88 | 0.128119E+11 | 0.135365E+10 | 0.00 | 0.135365E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.292282E+11 | 0.858388E+11 | 0.429348E+11 | 0.175074E+10 | 0.411841E+11 | 0.00 | 0.00 |
Minimum of Months | 14393576.88 | 0.252443E+10 | 0.135365E+10 | 0.00 | 0.135365E+10 | 0.00 | 0.00 |
Maximum of Months | 0.697447E+10 | 0.150099E+11 | 0.624747E+10 | 0.718093E+09 | 0.552937E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.120235E+10 | 0.921462E+10 | 0.247116E+10 | 0.113292E+10 | 0.133823E+10 | 0.00 | 0.00 |
February | 0.244430E+10 | 0.617189E+10 | 0.349106E+10 | 0.173323E+10 | 0.175783E+10 | 0.00 | 0.00 |
March | 0.394601E+10 | 0.561845E+10 | 0.519699E+10 | 0.215037E+10 | 0.304662E+10 | 0.00 | 0.00 |
April | 0.590371E+10 | 0.392108E+10 | 0.641695E+10 | 0.318019E+10 | 0.323676E+10 | 0.00 | 0.00 |
May | 0.727791E+10 | 0.316102E+10 | 0.732463E+10 | 0.325900E+10 | 0.406563E+10 | 0.00 | 0.00 |
June | 0.106517E+11 | 0.201267E+10 | 0.917496E+10 | 0.472143E+10 | 0.445353E+10 | 0.00 | 0.00 |
July | 0.125724E+11 | 0.169006E+10 | 0.995035E+10 | 0.562520E+10 | 0.432515E+10 | 0.00 | 0.00 |
August | 0.106439E+11 | 0.190725E+10 | 0.864730E+10 | 0.481801E+10 | 0.382929E+10 | 0.00 | 0.00 |
September | 0.653546E+10 | 0.265918E+10 | 0.591979E+10 | 0.305577E+10 | 0.286402E+10 | 0.00 | 0.00 |
October | 0.394239E+10 | 0.404758E+10 | 0.438871E+10 | 0.222852E+10 | 0.216019E+10 | 0.00 | 0.00 |
November | 0.173099E+10 | 0.548740E+10 | 0.269175E+10 | 0.125670E+10 | 0.143506E+10 | 0.00 | 0.00 |
December | 0.930642E+09 | 0.785207E+10 | 0.205150E+10 | 0.881125E+09 | 0.117038E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.677818E+11 | 0.537433E+11 | 0.677252E+11 | 0.340425E+11 | 0.336827E+11 | 0.00 | 0.00 |
Minimum of Months | 0.930642E+09 | 0.169006E+10 | 0.205150E+10 | 0.881125E+09 | 0.117038E+10 | 0.00 | 0.00 |
Maximum of Months | 0.125724E+11 | 0.921462E+10 | 0.995035E+10 | 0.562520E+10 | 0.445353E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.999006E+10 | 0.130426E+11 | 0.113787E+11 | 0.812691E+10 | 0.325181E+10 | 0.00 | 0.00 |
February | 0.127444E+11 | 0.894980E+10 | 0.130883E+11 | 0.941360E+10 | 0.367471E+10 | 0.00 | 0.00 |
March | 0.125573E+11 | 0.887065E+10 | 0.129527E+11 | 0.727366E+10 | 0.567907E+10 | 0.00 | 0.00 |
April | 0.102062E+11 | 0.641459E+10 | 0.100760E+11 | 0.481940E+10 | 0.525656E+10 | 0.00 | 0.00 |
May | 0.954239E+10 | 0.519532E+10 | 0.925064E+10 | 0.307239E+10 | 0.617825E+10 | 0.00 | 0.00 |
June | 0.106455E+11 | 0.343940E+10 | 0.889494E+10 | 0.259419E+10 | 0.630075E+10 | 0.00 | 0.00 |
July | 0.133902E+11 | 0.281787E+10 | 0.990930E+10 | 0.366046E+10 | 0.624883E+10 | 0.00 | 0.00 |
August | 0.154218E+11 | 0.319929E+10 | 0.117765E+11 | 0.593752E+10 | 0.583902E+10 | 0.00 | 0.00 |
September | 0.152108E+11 | 0.442079E+10 | 0.126403E+11 | 0.774510E+10 | 0.489516E+10 | 0.00 | 0.00 |
October | 0.149293E+11 | 0.645869E+10 | 0.136552E+11 | 0.944240E+10 | 0.421281E+10 | 0.00 | 0.00 |
November | 0.118817E+11 | 0.806301E+10 | 0.120479E+11 | 0.872702E+10 | 0.332089E+10 | 0.00 | 0.00 |
December | 0.975821E+10 | 0.110999E+11 | 0.108205E+11 | 0.781351E+10 | 0.300701E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.146278E+12 | 0.819718E+11 | 0.136491E+12 | 0.786262E+11 | 0.578649E+11 | 0.00 | 0.00 |
Minimum of Months | 0.954239E+10 | 0.281787E+10 | 0.889494E+10 | 0.259419E+10 | 0.300701E+10 | 0.00 | 0.00 |
Maximum of Months | 0.154218E+11 | 0.130426E+11 | 0.136552E+11 | 0.944240E+10 | 0.630075E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.104690E+10 | 0.975818E+10 | 0.223834E+10 | 0.902069E+09 | 0.133627E+10 | 0.00 | 0.00 |
February | 0.246178E+10 | 0.647291E+10 | 0.345079E+10 | 0.169624E+10 | 0.175455E+10 | 0.00 | 0.00 |
March | 0.362210E+10 | 0.603190E+10 | 0.488933E+10 | 0.179152E+10 | 0.309780E+10 | 0.00 | 0.00 |
April | 0.573403E+10 | 0.430323E+10 | 0.617714E+10 | 0.273676E+10 | 0.344038E+10 | 0.00 | 0.00 |
May | 0.811144E+10 | 0.350171E+10 | 0.789537E+10 | 0.360071E+10 | 0.429466E+10 | 0.00 | 0.00 |
June | 0.967724E+10 | 0.233485E+10 | 0.831276E+10 | 0.381836E+10 | 0.449440E+10 | 0.00 | 0.00 |
July | 0.112349E+11 | 0.202367E+10 | 0.879935E+10 | 0.444644E+10 | 0.435291E+10 | 0.00 | 0.00 |
August | 0.925223E+10 | 0.218518E+10 | 0.747184E+10 | 0.366702E+10 | 0.380482E+10 | 0.00 | 0.00 |
September | 0.655812E+10 | 0.296628E+10 | 0.581673E+10 | 0.294070E+10 | 0.287603E+10 | 0.00 | 0.00 |
October | 0.398451E+10 | 0.440586E+10 | 0.429595E+10 | 0.213442E+10 | 0.216152E+10 | 0.00 | 0.00 |
November | 0.215712E+10 | 0.586361E+10 | 0.294302E+10 | 0.145999E+10 | 0.148303E+10 | 0.00 | 0.00 |
December | 0.987624E+09 | 0.825883E+10 | 0.204419E+10 | 0.862794E+09 | 0.118139E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.648280E+11 | 0.581062E+11 | 0.643348E+11 | 0.300570E+11 | 0.342778E+11 | 0.00 | 0.00 |
Minimum of Months | 0.987624E+09 | 0.202367E+10 | 0.204419E+10 | 0.862794E+09 | 0.118139E+10 | 0.00 | 0.00 |
Maximum of Months | 0.112349E+11 | 0.975818E+10 | 0.879935E+10 | 0.444644E+10 | 0.449440E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 49645873.01 | 0.146127E+11 | 0.161426E+10 | 0.00 | 0.161426E+10 | 0.00 | 0.00 |
February | 0.340649E+09 | 0.965221E+10 | 0.205866E+10 | 0.00 | 0.205866E+10 | 0.00 | 0.00 |
March | 0.116120E+10 | 0.849767E+10 | 0.370251E+10 | 0.00 | 0.370251E+10 | 0.00 | 0.00 |
April | 0.204886E+10 | 0.573501E+10 | 0.408546E+10 | 23841848.37 | 0.406162E+10 | 0.00 | 0.00 |
May | 0.384783E+10 | 0.446983E+10 | 0.554403E+10 | 0.328518E+09 | 0.521551E+10 | 0.00 | 0.00 |
June | 0.610535E+10 | 0.286057E+10 | 0.624747E+10 | 0.718093E+09 | 0.552937E+10 | 0.00 | 0.00 |
July | 0.696595E+10 | 0.247983E+10 | 0.589765E+10 | 0.552386E+09 | 0.534526E+10 | 0.00 | 0.00 |
August | 0.505334E+10 | 0.280939E+10 | 0.472582E+10 | 0.126674E+09 | 0.459914E+10 | 0.00 | 0.00 |
September | 0.286448E+10 | 0.401170E+10 | 0.342514E+10 | 1229125.19 | 0.342391E+10 | 0.00 | 0.00 |
October | 0.117748E+10 | 0.593584E+10 | 0.258172E+10 | 0.00 | 0.258172E+10 | 0.00 | 0.00 |
November | 0.282933E+09 | 0.841724E+10 | 0.169846E+10 | 0.00 | 0.169846E+10 | 0.00 | 0.00 |
December | 17516774.46 | 0.123292E+11 | 0.135365E+10 | 0.00 | 0.135365E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.299152E+11 | 0.818112E+11 | 0.429348E+11 | 0.175074E+10 | 0.411841E+11 | 0.00 | 0.00 |
Minimum of Months | 17516774.46 | 0.247983E+10 | 0.135365E+10 | 0.00 | 0.135365E+10 | 0.00 | 0.00 |
Maximum of Months | 0.696595E+10 | 0.146127E+11 | 0.624747E+10 | 0.718093E+09 | 0.552937E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.123716E+10 | 0.897974E+10 | 0.247116E+10 | 0.113292E+10 | 0.133823E+10 | 0.00 | 0.00 |
February | 0.251777E+10 | 0.593003E+10 | 0.349106E+10 | 0.173323E+10 | 0.175783E+10 | 0.00 | 0.00 |
March | 0.403221E+10 | 0.534690E+10 | 0.519699E+10 | 0.215037E+10 | 0.304662E+10 | 0.00 | 0.00 |
April | 0.597928E+10 | 0.368945E+10 | 0.641695E+10 | 0.318019E+10 | 0.323676E+10 | 0.00 | 0.00 |
May | 0.730461E+10 | 0.301317E+10 | 0.732463E+10 | 0.325900E+10 | 0.406563E+10 | 0.00 | 0.00 |
June | 0.106385E+11 | 0.197440E+10 | 0.917496E+10 | 0.472143E+10 | 0.445353E+10 | 0.00 | 0.00 |
July | 0.125410E+11 | 0.167033E+10 | 0.995035E+10 | 0.562520E+10 | 0.432515E+10 | 0.00 | 0.00 |
August | 0.106240E+11 | 0.187056E+10 | 0.864730E+10 | 0.481801E+10 | 0.382929E+10 | 0.00 | 0.00 |
September | 0.655627E+10 | 0.254992E+10 | 0.591979E+10 | 0.305577E+10 | 0.286402E+10 | 0.00 | 0.00 |
October | 0.404832E+10 | 0.375340E+10 | 0.438871E+10 | 0.222852E+10 | 0.216019E+10 | 0.00 | 0.00 |
November | 0.181860E+10 | 0.514232E+10 | 0.269175E+10 | 0.125670E+10 | 0.143506E+10 | 0.00 | 0.00 |
December | 0.964940E+09 | 0.755611E+10 | 0.205150E+10 | 0.881125E+09 | 0.117038E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.682627E+11 | 0.514763E+11 | 0.677252E+11 | 0.340425E+11 | 0.336827E+11 | 0.00 | 0.00 |
Minimum of Months | 0.964940E+09 | 0.167033E+10 | 0.205150E+10 | 0.881125E+09 | 0.117038E+10 | 0.00 | 0.00 |
Maximum of Months | 0.125410E+11 | 0.897974E+10 | 0.995035E+10 | 0.562520E+10 | 0.445353E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.100843E+11 | 0.126179E+11 | 0.113787E+11 | 0.812691E+10 | 0.325181E+10 | 0.00 | 0.00 |
February | 0.128534E+11 | 0.853748E+10 | 0.130883E+11 | 0.941360E+10 | 0.367471E+10 | 0.00 | 0.00 |
March | 0.126651E+11 | 0.841790E+10 | 0.129527E+11 | 0.727366E+10 | 0.567907E+10 | 0.00 | 0.00 |
April | 0.102981E+11 | 0.602444E+10 | 0.100760E+11 | 0.481940E+10 | 0.525656E+10 | 0.00 | 0.00 |
May | 0.958160E+10 | 0.493359E+10 | 0.925064E+10 | 0.307239E+10 | 0.617825E+10 | 0.00 | 0.00 |
June | 0.106367E+11 | 0.334216E+10 | 0.889494E+10 | 0.259419E+10 | 0.630075E+10 | 0.00 | 0.00 |
July | 0.133593E+11 | 0.276087E+10 | 0.990930E+10 | 0.366046E+10 | 0.624883E+10 | 0.00 | 0.00 |
August | 0.153935E+11 | 0.311312E+10 | 0.117765E+11 | 0.593752E+10 | 0.583902E+10 | 0.00 | 0.00 |
September | 0.152221E+11 | 0.422168E+10 | 0.126403E+11 | 0.774510E+10 | 0.489516E+10 | 0.00 | 0.00 |
October | 0.150506E+11 | 0.599964E+10 | 0.136552E+11 | 0.944240E+10 | 0.421281E+10 | 0.00 | 0.00 |
November | 0.120551E+11 | 0.752427E+10 | 0.120479E+11 | 0.872702E+10 | 0.332089E+10 | 0.00 | 0.00 |
December | 0.988835E+10 | 0.106078E+11 | 0.108205E+11 | 0.781351E+10 | 0.300701E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.147088E+12 | 0.781008E+11 | 0.136491E+12 | 0.786262E+11 | 0.578649E+11 | 0.00 | 0.00 |
Minimum of Months | 0.958160E+10 | 0.276087E+10 | 0.889494E+10 | 0.259419E+10 | 0.300701E+10 | 0.00 | 0.00 |
Maximum of Months | 0.153935E+11 | 0.126179E+11 | 0.136552E+11 | 0.944240E+10 | 0.630075E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.106621E+10 | 0.951577E+10 | 0.223834E+10 | 0.902069E+09 | 0.133627E+10 | 0.00 | 0.00 |
February | 0.249445E+10 | 0.623581E+10 | 0.345079E+10 | 0.169624E+10 | 0.175455E+10 | 0.00 | 0.00 |
March | 0.366181E+10 | 0.577203E+10 | 0.488933E+10 | 0.179152E+10 | 0.309780E+10 | 0.00 | 0.00 |
April | 0.578330E+10 | 0.407461E+10 | 0.617714E+10 | 0.273676E+10 | 0.344038E+10 | 0.00 | 0.00 |
May | 0.812493E+10 | 0.333921E+10 | 0.789537E+10 | 0.360071E+10 | 0.429466E+10 | 0.00 | 0.00 |
June | 0.966599E+10 | 0.227562E+10 | 0.831276E+10 | 0.381836E+10 | 0.449440E+10 | 0.00 | 0.00 |
July | 0.112136E+11 | 0.198739E+10 | 0.879935E+10 | 0.444644E+10 | 0.435291E+10 | 0.00 | 0.00 |
August | 0.924027E+10 | 0.213103E+10 | 0.747184E+10 | 0.366702E+10 | 0.380482E+10 | 0.00 | 0.00 |
September | 0.657055E+10 | 0.284228E+10 | 0.581673E+10 | 0.294070E+10 | 0.287603E+10 | 0.00 | 0.00 |
October | 0.404768E+10 | 0.412537E+10 | 0.429595E+10 | 0.213442E+10 | 0.216152E+10 | 0.00 | 0.00 |
November | 0.220551E+10 | 0.554038E+10 | 0.294302E+10 | 0.145999E+10 | 0.148303E+10 | 0.00 | 0.00 |
December | 0.100735E+10 | 0.798254E+10 | 0.204419E+10 | 0.862794E+09 | 0.118139E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.650817E+11 | 0.558221E+11 | 0.643348E+11 | 0.300570E+11 | 0.342778E+11 | 0.00 | 0.00 |
Minimum of Months | 0.100735E+10 | 0.198739E+10 | 0.204419E+10 | 0.862794E+09 | 0.118139E+10 | 0.00 | 0.00 |
Maximum of Months | 0.112136E+11 | 0.951577E+10 | 0.879935E+10 | 0.444644E+10 | 0.449440E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | -8.8 | -10.9 | -16.1 | 5.70 | -23.3 | 32.48 | 106.19 | 0.00 |
February | -2.2 | -5.0 | -9.9 | 6.21 | -16.1 | 41.31 | 158.25 | 0.00 |
March | 0.30 | -2.9 | -8.4 | 5.38 | -12.8 | 78.62 | 145.02 | 0.00 |
April | 6.67 | 2.34 | -2.9 | 4.89 | -6.2 | 82.10 | 182.32 | 0.01 |
May | 10.10 | 5.18 | 0.22 | 5.28 | -1.1 | 102.67 | 205.47 | 0.01 |
June | 16.46 | 10.06 | 4.91 | 4.56 | 5.05 | 103.05 | 264.47 | 0.02 |
July | 20.57 | 12.46 | 6.56 | 4.24 | 8.00 | 89.47 | 301.47 | 0.00 |
August | 19.17 | 11.04 | 4.61 | 4.29 | 7.19 | 78.96 | 261.05 | 0.00 |
September | 14.69 | 9.08 | 4.37 | 5.43 | 3.42 | 63.03 | 204.21 | 0.00 |
October | 8.64 | 4.13 | -1.0 | 5.38 | -4.2 | 47.64 | 162.42 | 0.00 |
November | 2.84 | -0.9 | -6.9 | 5.91 | -11.0 | 33.00 | 125.52 | 0.00 |
December | -4.1 | -6.5 | -11.1 | 5.64 | -18.2 | 26.54 | 97.81 | 0.00 |
Annual Sum or Average | 7.07 | 2.37 | -2.9 | 5.23 | -5.7 | 65.04 | 184.63 | 0.00 |
Minimum of Months | -8.8 | -10.9 | -16.1 | 4.24 | -23.3 | 26.54 | 97.81 | 0.00 |
Maximum of Months | 20.57 | 12.46 | 6.56 | 6.21 | 8.00 | 103.05 | 301.47 | 0.02 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 10.60 | 14-JAN-12:00 | 5.16 | -1.1 | 8.20 | -2.3 | 105.00 | 464.50 |
February | 18.90 | 27-FEB-14:00 | 7.23 | -7.8 | 5.20 | 1.37 | 76.00 | 634.50 |
March | 15.00 | 14-MAR-13:20 | 6.67 | -2.4 | 9.30 | 1.23 | 201.67 | 711.67 |
April | 23.30 | 07-APR-13:00 | 9.68 | -4.4 | 9.30 | 4.92 | 314.50 | 110.00 |
May | 30.00 | 20-MAY-15:00 | 15.22 | 5.60 | 6.70 | 20.57 | 215.50 | 18.50 |
June | 32.20 | 29-JUN-12:00 | 14.40 | 0.60 | 9.30 | 17.03 | 187.00 | 729.00 |
July | 37.20 | 17-JUL-15:00 | 17.28 | 4.40 | 4.60 | 20.22 | 119.50 | 797.00 |
August | 35.60 | 05-AUG-15:00 | 17.65 | 6.70 | 5.20 | 22.47 | 136.50 | 625.50 |
September | 34.40 | 02-SEP-14:00 | 16.28 | 4.40 | 7.70 | 20.75 | 95.50 | 789.50 |
October | 25.00 | 18-OCT-13:00 | 11.40 | -1.1 | 7.70 | 7.35 | 48.00 | 913.00 |
November | 17.20 | 04-NOV-13:00 | 8.18 | -1.1 | 11.30 | 2.22 | 81.00 | 689.50 |
December | 13.90 | 10-DEC-01:00 | 5.50 | -5.0 | 13.90 | 5.74 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 10.60 | 5.16 | -7.8 | 4.60 | -2.3 | 0.00 | 0.00 | |
Maximum of Months | 37.20 | 17.65 | 6.70 | 13.90 | 22.47 | 314.50 | 913.00 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -33.9 | 10-JAN-21:00 | -34.1 | -37.8 | 3.10 | -54.3 | 0.00 | 0.00 |
February | -25.0 | 01-FEB-03:00 | -25.2 | -27.8 | 2.10 | -45.6 | 0.00 | 0.00 |
March | -23.3 | 04-MAR-23:00 | -23.8 | -28.9 | 3.60 | -44.5 | 0.00 | 0.00 |
April | -7.8 | 29-APR-03:00 | -8.7 | -10.6 | 4.10 | -25.6 | 0.00 | 0.00 |
May | -2.8 | 08-MAY-00:10 | -3.3 | -3.9 | 6.18 | -10.2 | 0.00 | 0.00 |
June | 0.60 | 15-JUN-03:00 | -0.5 | -1.7 | 2.60 | -15.7 | 0.00 | 0.00 |
July | 5.60 | 08-JUL-03:00 | 2.99 | 0.00 | 4.10 | -9.2 | 0.00 | 0.00 |
August | 6.70 | 17-AUG-00:00 | 4.32 | 1.70 | 2.60 | -7.1 | 0.00 | 0.00 |
September | 0.00 | 17-SEP-02:00 | -1.6 | -3.9 | 4.10 | -16.8 | 0.00 | 0.00 |
October | -6.1 | 10-OCT-05:19 | -6.6 | -7.8 | 3.77 | -20.6 | 0.00 | 0.00 |
November | -16.7 | 26-NOV-07:00 | -17.3 | -20.6 | 4.60 | -33.8 | 19.50 | 94.00 |
December | -28.3 | 29-DEC-08:00 | -28.6 | -32.2 | 2.10 | -48.7 | 69.50 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -33.9 | -34.1 | -37.8 | 2.10 | -54.3 | 0.00 | 0.00 | |
Maximum of Months | 6.70 | 4.32 | 1.70 | 6.18 | -7.1 | 69.50 | 94.00 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 5.18 | 13-JAN-14:00 | 10.00 | 0.00 | 8.80 | -3.0 | 40.00 | 694.00 |
February | 7.23 | 27-FEB-14:00 | 18.90 | -7.8 | 5.20 | 1.37 | 76.00 | 634.50 |
March | 6.94 | 14-MAR-13:00 | 15.00 | -1.7 | 10.30 | 1.80 | 241.00 | 538.00 |
April | 11.02 | 06-APR-15:00 | 22.20 | 1.10 | 3.60 | 5.33 | 110.00 | 779.00 |
May | 15.22 | 20-MAY-15:00 | 30.00 | 5.60 | 6.70 | 20.57 | 215.50 | 18.50 |
June | 19.20 | 20-JUN-14:00 | 29.40 | 14.40 | 2.60 | 18.28 | 204.00 | 614.00 |
July | 19.21 | 19-JUL-11:00 | 29.40 | 14.40 | 8.80 | 19.52 | 306.50 | 563.50 |
August | 17.65 | 05-AUG-15:00 | 35.60 | 6.70 | 5.20 | 22.47 | 136.50 | 625.50 |
September | 20.12 | 07-SEP-15:20 | 25.17 | 17.93 | 4.10 | 15.88 | 127.67 | 652.00 |
October | 11.61 | 18-OCT-14:00 | 25.00 | -0.6 | 7.70 | 7.55 | 40.50 | 852.00 |
November | 8.89 | 17-NOV-16:00 | 17.20 | 1.10 | 11.30 | 4.10 | 0.00 | 0.00 |
December | 7.62 | 19-DEC-14:00 | 12.80 | 2.80 | 8.20 | 1.37 | 74.00 | 138.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 5.18 | 10.00 | -7.8 | 2.60 | -3.0 | 0.00 | 0.00 | |
Maximum of Months | 20.12 | 35.60 | 17.93 | 11.30 | 22.47 | 306.50 | 852.00 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 1.70 | 12-JAN-14:00 | 7.20 | 4.48 | 5.20 | -1.0 | 107.00 | 61.00 |
February | -0.6 | 11-FEB-08:00 | 4.40 | 2.16 | 10.80 | -5.7 | 69.50 | 50.50 |
March | -0.6 | 10-MAR-12:00 | 8.90 | 4.51 | 10.30 | -2.3 | 253.00 | 140.50 |
April | 6.10 | 17-APR-16:19 | 7.97 | 6.96 | 4.50 | 0.87 | 201.50 | 117.50 |
May | 12.20 | 02-MAY-12:00 | 18.90 | 14.61 | 12.90 | 14.84 | 108.50 | 934.50 |
June | 15.60 | 20-JUN-19:00 | 25.60 | 18.76 | 3.60 | 20.22 | 17.50 | 17.00 |
July | 16.70 | 18-JUL-21:00 | 19.40 | 17.51 | 4.10 | 16.49 | 0.00 | 0.00 |
August | 11.10 | 08-AUG-11:00 | 26.70 | 16.75 | 2.60 | 12.03 | 134.50 | 869.00 |
September | 18.30 | 07-SEP-14:00 | 24.40 | 20.10 | 4.10 | 15.57 | 111.00 | 720.00 |
October | 6.70 | 01-OCT-14:09 | 9.08 | 7.78 | 2.10 | 4.07 | 260.33 | 0.33 |
November | 3.30 | 16-NOV-19:00 | 10.60 | 6.88 | 9.80 | -1.7 | 0.00 | 0.00 |
December | 2.80 | 19-DEC-14:09 | 10.97 | 6.81 | 10.78 | -1.0 | 95.00 | 292.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -0.6 | 4.40 | 2.16 | 2.10 | -5.7 | 0.00 | 0.00 | |
Maximum of Months | 18.30 | 26.70 | 20.10 | 12.90 | 20.22 | 260.33 | 934.50 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 5.41 | 12.59 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 4.46 | 20.37 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 5.03 | 30.19 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 7.01 | 37.07 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 9.90 | 46.35 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 12.91 | 55.45 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 15.24 | 57.38 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 16.26 | 48.01 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 15.67 | 34.51 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 13.64 | 22.84 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 10.74 | 14.52 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 7.74 | 10.24 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 10.37 | 32.53 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 4.46 | 10.24 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 16.26 | 57.38 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.436849E+11 | -0.426371E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.104772E+10 | 58.99 | 0.00 | 0.00 |
February | 0.403591E+11 | -0.394249E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -934206830.8 | 58.98 | 0.00 | 0.00 |
March | 0.469298E+11 | -0.458985E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.103125E+10 | 58.98 | 0.00 | 0.00 |
April | 0.410850E+11 | -0.400938E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -991151940.4 | 58.98 | 0.00 | 0.00 |
May | 0.414885E+11 | -0.404645E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.102396E+10 | 58.98 | 0.00 | 0.00 |
June | 0.386197E+11 | -0.376295E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -990211275.2 | 58.98 | 0.00 | 0.00 |
July | 0.349776E+11 | -0.339604E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.101726E+10 | 58.97 | 0.00 | 0.00 |
August | 0.373641E+11 | -0.363424E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.102163E+10 | 58.98 | 0.00 | 0.00 |
September | 0.344078E+11 | -0.334209E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -986873290.4 | 58.97 | 0.00 | 0.00 |
October | 0.371098E+11 | -0.360907E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.101915E+10 | 58.97 | 0.00 | 0.00 |
November | 0.386505E+11 | -0.376623E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -988135958.0 | 58.97 | 0.00 | 0.00 |
December | 0.408240E+11 | -0.397946E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.102935E+10 | 58.98 | 0.00 | 0.00 |
Annual Sum or Average | 0.475501E+12 | -0.463420E+12 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.120809E+11 | 58.98 | 0.00 | 0.00 |
Minimum of Months | 0.344078E+11 | -0.458985E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -0.104772E+10 | 58.97 | 0.00 | 0.00 |
Maximum of Months | 0.469298E+11 | -0.334209E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -934206830.8 | 58.99 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_1_DAYLCTRL
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 226.83 | 0.51 | 0.48 | 01-JAN-08:50 | 6268.52 | 37.11 | 219.83 | 232.50 | 5241.31 | 37.97 | 224.67 | 214.67 |
February | 275.00 | 0.50 | 0.48 | 01-FEB-08:20 | 8484.48 | 37.44 | 268.67 | 259.67 | 3613.70 | 31.80 | 235.50 | 245.67 |
March | 304.00 | 0.50 | 0.48 | 01-MAR-07:49 | 9903.93 | 33.46 | 272.17 | 324.17 | 2044.76 | 23.50 | 257.00 | 297.50 |
April | 325.17 | 0.50 | 0.48 | 01-APR-08:50 | 2514.15 | 21.09 | 160.00 | 351.50 | 1434.51 | 22.54 | 240.17 | 318.17 |
May | 385.83 | 0.51 | 0.48 | 01-MAY-06:30 | 2226.70 | 20.83 | 163.33 | 399.83 | 1248.17 | 22.26 | 279.83 | 360.17 |
June | 434.17 | 0.52 | 0.48 | 01-JUN-13:39 | 1912.30 | 20.30 | 173.83 | 414.00 | 1108.82 | 21.75 | 288.33 | 368.17 |
July | 417.33 | 0.50 | 0.48 | 01-JUL-06:40 | 2057.24 | 20.69 | 139.67 | 406.83 | 1227.05 | 22.16 | 277.17 | 373.33 |
August | 421.33 | 0.51 | 0.48 | 01-AUG-06:40 | 2193.88 | 20.22 | 156.00 | 386.33 | 1309.39 | 21.66 | 246.33 | 351.17 |
September | 352.17 | 0.52 | 0.48 | 01-SEP-06:00 | 3085.65 | 21.63 | 150.00 | 328.00 | 1532.49 | 21.86 | 218.50 | 300.50 |
October | 317.67 | 0.50 | 0.48 | 01-OCT-08:39 | 8591.47 | 35.15 | 289.33 | 302.00 | 2349.71 | 24.42 | 214.50 | 282.33 |
November | 269.50 | 0.50 | 0.48 | 01-NOV-07:00 | 6399.52 | 37.45 | 262.67 | 250.67 | 5632.23 | 38.62 | 264.17 | 241.17 |
December | 236.83 | 0.51 | 0.48 | 01-DEC-08:50 | 4980.48 | 37.80 | 237.83 | 232.33 | 4337.08 | 38.97 | 241.17 | 219.67 |
Annual Sum or Average | 3965.83 | 0.51 | 4482.25 | 27.13 | 2493.33 | 3887.83 | 2301.83 | 26.06 | 2987.33 | 3572.50 | ||
Minimum of Months | 226.83 | 0.50 | 0.48 | 1912.30 | 20.22 | 139.67 | 232.33 | 1108.82 | 21.66 | 214.50 | 214.67 | |
Maximum of Months | 434.17 | 0.52 | 0.48 | 9903.93 | 37.80 | 289.33 | 414.00 | 5632.23 | 38.97 | 288.33 | 373.33 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_2_DAYLCTRL
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 226.83 | 0.53 | 0.48 | 01-JAN-08:50 | 1982.29 | 25.53 | 106.50 | 218.67 | 1123.30 | 25.20 | 138.17 | 186.50 |
February | 275.00 | 0.52 | 0.48 | 01-FEB-08:09 | 2220.78 | 24.62 | 120.67 | 248.67 | 1195.29 | 24.54 | 153.50 | 218.50 |
March | 304.00 | 0.50 | 0.48 | 01-MAR-07:40 | 3488.50 | 25.83 | 153.83 | 321.00 | 1943.07 | 26.01 | 234.17 | 291.00 |
April | 325.17 | 0.49 | 0.48 | 01-APR-08:39 | 3477.13 | 24.48 | 112.33 | 358.33 | 1928.14 | 24.85 | 186.33 | 325.33 |
May | 385.83 | 0.50 | 0.48 | 01-MAY-05:40 | 3821.68 | 24.61 | 139.17 | 410.17 | 1674.31 | 24.08 | 226.33 | 373.50 |
June | 434.17 | 0.51 | 0.48 | 01-JUN-13:39 | 4650.30 | 25.69 | 153.67 | 425.83 | 2016.91 | 25.02 | 271.83 | 394.00 |
July | 417.33 | 0.49 | 0.48 | 01-JUL-06:40 | 5042.98 | 25.82 | 148.83 | 423.50 | 2158.28 | 24.93 | 220.67 | 397.17 |
August | 421.33 | 0.51 | 0.48 | 01-AUG-05:30 | 4026.77 | 25.14 | 155.50 | 393.67 | 2311.46 | 25.41 | 219.17 | 363.33 |
September | 352.17 | 0.51 | 0.48 | 01-SEP-06:19 | 3034.73 | 24.30 | 141.33 | 328.50 | 1679.31 | 24.60 | 190.33 | 300.67 |
October | 317.67 | 0.52 | 0.48 | 01-OCT-08:20 | 2725.75 | 24.82 | 143.00 | 292.33 | 1547.48 | 24.99 | 181.17 | 258.50 |
November | 269.50 | 0.53 | 0.48 | 01-NOV-07:49 | 1765.97 | 24.54 | 118.33 | 234.83 | 971.20 | 24.42 | 146.00 | 204.00 |
December | 236.83 | 0.54 | 0.48 | 01-DEC-08:50 | 1542.15 | 25.46 | 109.67 | 211.83 | 910.02 | 25.23 | 133.00 | 173.83 |
Annual Sum or Average | 3965.83 | 0.51 | 3359.20 | 25.08 | 1602.83 | 3867.33 | 1703.98 | 24.93 | 2300.67 | 3486.33 | ||
Minimum of Months | 226.83 | 0.49 | 0.48 | 1542.15 | 24.30 | 106.50 | 211.83 | 910.02 | 24.08 | 133.00 | 173.83 | |
Maximum of Months | 434.17 | 0.54 | 0.48 | 5042.98 | 25.83 | 155.50 | 425.83 | 2311.46 | 26.01 | 271.83 | 397.17 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_3_DAYLCTRL
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 226.83 | 0.57 | 0.48 | 01-JAN-10:30 | 656.31 | 16.83 | 0.00 | 196.67 | 385.79 | 18.47 | 7.50 | 134.00 |
February | 275.00 | 0.54 | 0.48 | 01-FEB-10:50 | 721.92 | 17.82 | 0.00 | 234.83 | 442.01 | 19.47 | 18.00 | 182.00 |
March | 304.00 | 0.51 | 0.48 | 01-MAR-08:09 | 1133.25 | 19.67 | 1.50 | 314.00 | 663.64 | 21.15 | 156.67 | 273.83 |
April | 325.17 | 0.50 | 0.48 | 01-APR-08:00 | 1182.72 | 20.27 | 20.83 | 353.83 | 703.37 | 21.65 | 183.17 | 315.67 |
May | 385.83 | 0.49 | 0.48 | 01-MAY-06:10 | 1458.10 | 22.11 | 109.33 | 413.17 | 851.19 | 23.32 | 289.00 | 380.83 |
June | 434.17 | 0.49 | 0.48 | 01-JUN-13:39 | 1526.02 | 24.16 | 201.33 | 441.83 | 854.81 | 23.41 | 345.67 | 416.50 |
July | 417.33 | 0.49 | 0.48 | 01-JUL-06:40 | 1490.02 | 23.12 | 147.50 | 427.33 | 857.59 | 22.40 | 290.50 | 401.00 |
August | 421.33 | 0.50 | 0.48 | 01-AUG-05:49 | 1158.53 | 19.90 | 42.50 | 400.33 | 733.74 | 21.30 | 223.00 | 380.33 |
September | 352.17 | 0.52 | 0.48 | 01-SEP-06:00 | 948.22 | 18.96 | 1.17 | 325.33 | 586.24 | 20.43 | 114.67 | 282.67 |
October | 317.67 | 0.53 | 0.48 | 01-OCT-09:09 | 780.81 | 18.14 | 0.00 | 277.83 | 473.70 | 19.72 | 49.67 | 221.83 |
November | 269.50 | 0.56 | 0.48 | 01-NOV-08:00 | 617.01 | 16.97 | 0.00 | 214.67 | 368.96 | 18.63 | 2.67 | 150.83 |
December | 236.83 | 0.58 | 0.48 | 01-DEC-09:50 | 536.17 | 16.35 | 0.00 | 190.17 | 318.49 | 18.06 | 0.17 | 103.50 |
Annual Sum or Average | 3965.83 | 0.52 | 1080.94 | 19.98 | 524.17 | 3790.00 | 639.95 | 20.99 | 1680.67 | 3243.00 | ||
Minimum of Months | 226.83 | 0.49 | 0.48 | 536.17 | 16.35 | 0.00 | 190.17 | 318.49 | 18.06 | 0.17 | 103.50 | |
Maximum of Months | 434.17 | 0.58 | 0.48 | 1526.02 | 24.16 | 201.33 | 441.83 | 857.59 | 23.41 | 345.67 | 416.50 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_4_DAYLCTRL
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 226.83 | 0.54 | 0.48 | 01-JAN-10:20 | 1845.49 | 24.30 | 99.33 | 212.67 | 1069.69 | 24.24 | 135.50 | 176.50 |
February | 275.00 | 0.52 | 0.48 | 01-FEB-10:50 | 2381.76 | 25.30 | 125.83 | 246.17 | 1291.42 | 25.16 | 154.17 | 219.00 |
March | 304.00 | 0.50 | 0.48 | 01-MAR-08:20 | 3275.84 | 25.59 | 152.33 | 319.50 | 1793.51 | 25.87 | 232.17 | 289.17 |
April | 325.17 | 0.50 | 0.48 | 01-APR-08:00 | 3388.31 | 23.41 | 111.50 | 351.33 | 1891.65 | 23.94 | 191.00 | 317.83 |
May | 385.83 | 0.50 | 0.48 | 01-MAY-06:49 | 3861.55 | 22.57 | 102.83 | 405.17 | 2261.87 | 23.39 | 222.17 | 372.17 |
June | 434.17 | 0.51 | 0.48 | 01-JUN-13:39 | 3955.85 | 21.00 | 69.33 | 427.67 | 1784.18 | 21.37 | 235.33 | 395.00 |
July | 417.33 | 0.50 | 0.48 | 01-JUL-06:00 | 4586.26 | 22.64 | 94.83 | 412.67 | 2071.17 | 21.66 | 195.83 | 385.17 |
August | 421.33 | 0.51 | 0.48 | 01-AUG-06:49 | 3564.68 | 22.47 | 118.17 | 392.33 | 1965.18 | 23.05 | 196.50 | 363.50 |
September | 352.17 | 0.51 | 0.48 | 01-SEP-07:10 | 3552.16 | 25.12 | 145.83 | 330.00 | 1484.89 | 24.15 | 189.83 | 301.17 |
October | 317.67 | 0.52 | 0.48 | 01-OCT-09:20 | 2388.06 | 24.65 | 141.00 | 290.50 | 1314.10 | 24.76 | 184.67 | 257.67 |
November | 269.50 | 0.53 | 0.48 | 01-NOV-08:00 | 2056.71 | 25.35 | 120.83 | 233.33 | 1161.83 | 25.19 | 149.00 | 201.67 |
December | 236.83 | 0.54 | 0.48 | 01-DEC-09:50 | 1449.87 | 24.72 | 106.67 | 213.17 | 809.46 | 24.47 | 128.50 | 177.00 |
Annual Sum or Average | 3965.83 | 0.51 | 3202.80 | 23.69 | 1388.50 | 3834.50 | 1649.84 | 23.72 | 2214.67 | 3455.83 | ||
Minimum of Months | 226.83 | 0.50 | 0.48 | 1449.87 | 21.00 | 69.33 | 212.67 | 809.46 | 21.37 | 128.50 | 176.50 | |
Maximum of Months | 434.17 | 0.54 | 0.48 | 4586.26 | 25.59 | 152.33 | 427.67 | 2261.87 | 25.87 | 235.33 | 395.00 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_1_DAYLCTRL
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 226.83 | 0.51 | 0.48 | 01-JAN-08:50 | 6316.76 | 36.63 | 216.33 | 232.67 | 5372.66 | 37.50 | 215.33 | 216.00 |
February | 275.00 | 0.50 | 0.48 | 01-FEB-08:20 | 8551.12 | 36.96 | 266.33 | 259.83 | 3787.62 | 30.09 | 179.83 | 248.17 |
March | 304.00 | 0.50 | 0.48 | 01-MAR-07:49 | 9963.92 | 32.27 | 254.17 | 324.17 | 2182.62 | 18.77 | 14.00 | 299.83 |
April | 325.17 | 0.50 | 0.48 | 01-APR-08:50 | 2562.85 | 14.74 | 0.00 | 351.67 | 1537.64 | 18.26 | 8.83 | 321.67 |
May | 385.83 | 0.51 | 0.48 | 01-MAY-06:30 | 2263.57 | 14.70 | 0.00 | 399.83 | 1334.01 | 18.16 | 1.67 | 364.33 |
June | 434.17 | 0.52 | 0.48 | 01-JUN-13:39 | 1948.85 | 14.32 | 0.00 | 415.00 | 1185.85 | 17.86 | 0.00 | 373.50 |
July | 417.33 | 0.50 | 0.48 | 01-JUL-06:40 | 2102.54 | 14.69 | 0.00 | 407.00 | 1315.46 | 18.26 | 1.17 | 377.67 |
August | 421.33 | 0.51 | 0.48 | 01-AUG-06:40 | 2248.43 | 13.95 | 0.00 | 386.67 | 1407.18 | 17.50 | 2.67 | 355.33 |
September | 352.17 | 0.52 | 0.48 | 01-SEP-06:00 | 3150.88 | 15.53 | 29.50 | 328.17 | 1665.48 | 17.59 | 14.33 | 303.67 |
October | 317.67 | 0.50 | 0.48 | 01-OCT-08:30 | 8650.58 | 34.24 | 283.00 | 302.00 | 2585.30 | 22.00 | 80.83 | 287.33 |
November | 269.50 | 0.50 | 0.48 | 01-NOV-07:00 | 6453.29 | 36.99 | 262.00 | 251.00 | 5755.27 | 38.26 | 263.00 | 242.50 |
December | 236.83 | 0.51 | 0.48 | 01-DEC-08:50 | 5018.36 | 37.38 | 231.33 | 232.50 | 4450.62 | 38.64 | 232.17 | 221.33 |
Annual Sum or Average | 3965.83 | 0.51 | 4532.81 | 23.23 | 1542.67 | 3890.50 | 2422.73 | 22.90 | 1013.83 | 3611.33 | ||
Minimum of Months | 226.83 | 0.50 | 0.48 | 1948.85 | 13.95 | 0.00 | 232.50 | 1185.85 | 17.50 | 0.00 | 216.00 | |
Maximum of Months | 434.17 | 0.52 | 0.48 | 9963.92 | 37.38 | 283.00 | 415.00 | 5755.27 | 38.64 | 263.00 | 377.67 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_2_DAYLCTRL
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 226.83 | 0.53 | 0.48 | 01-JAN-08:50 | 2014.10 | 23.38 | 89.67 | 219.67 | 1167.64 | 23.58 | 76.67 | 189.67 |
February | 275.00 | 0.52 | 0.48 | 01-FEB-08:09 | 2216.52 | 20.72 | 75.00 | 248.67 | 1252.84 | 22.61 | 76.00 | 222.00 |
March | 304.00 | 0.50 | 0.48 | 01-MAR-07:40 | 3520.40 | 22.27 | 94.67 | 321.17 | 2021.98 | 24.01 | 92.67 | 293.83 |
April | 325.17 | 0.49 | 0.48 | 01-APR-08:39 | 3541.86 | 21.39 | 85.33 | 359.17 | 2011.14 | 22.44 | 60.17 | 328.83 |
May | 385.83 | 0.50 | 0.48 | 01-MAY-05:40 | 3884.51 | 21.66 | 113.00 | 410.83 | 1758.21 | 21.48 | 57.83 | 377.17 |
June | 434.17 | 0.51 | 0.48 | 01-JUN-13:39 | 4697.80 | 22.02 | 134.17 | 426.33 | 2112.82 | 22.53 | 89.50 | 397.33 |
July | 417.33 | 0.49 | 0.48 | 01-JUL-06:40 | 5117.95 | 22.90 | 134.00 | 424.00 | 2264.13 | 22.31 | 75.50 | 399.00 |
August | 421.33 | 0.51 | 0.48 | 01-AUG-05:30 | 4097.85 | 22.24 | 131.33 | 394.33 | 2403.42 | 23.13 | 101.17 | 367.50 |
September | 352.17 | 0.51 | 0.48 | 01-SEP-06:19 | 3093.98 | 21.44 | 104.17 | 328.83 | 1752.31 | 22.36 | 78.33 | 303.50 |
October | 317.67 | 0.52 | 0.48 | 01-OCT-08:20 | 2771.23 | 22.32 | 110.50 | 292.83 | 1604.65 | 23.09 | 101.50 | 262.00 |
November | 269.50 | 0.53 | 0.48 | 01-NOV-07:49 | 1797.46 | 22.24 | 95.17 | 235.33 | 1014.20 | 22.70 | 82.00 | 208.50 |
December | 236.83 | 0.54 | 0.48 | 01-DEC-08:50 | 1565.37 | 23.46 | 101.83 | 213.00 | 943.72 | 23.80 | 89.67 | 178.67 |
Annual Sum or Average | 3965.83 | 0.51 | 3407.66 | 22.13 | 1268.83 | 3874.17 | 1778.93 | 22.76 | 981.00 | 3528.00 | ||
Minimum of Months | 226.83 | 0.49 | 0.48 | 1565.37 | 20.72 | 75.00 | 213.00 | 943.72 | 21.48 | 57.83 | 178.67 | |
Maximum of Months | 434.17 | 0.54 | 0.48 | 5117.95 | 23.46 | 134.17 | 426.33 | 2403.42 | 24.01 | 101.50 | 399.00 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_3_DAYLCTRL
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 226.83 | 0.56 | 0.48 | 01-JAN-10:20 | 664.14 | 10.99 | 0.00 | 197.17 | 409.77 | 14.55 | 0.00 | 143.17 |
February | 275.00 | 0.54 | 0.48 | 01-FEB-10:30 | 732.51 | 12.05 | 0.00 | 235.17 | 470.23 | 15.69 | 0.00 | 189.67 |
March | 304.00 | 0.51 | 0.48 | 01-MAR-08:09 | 1150.69 | 14.08 | 0.00 | 314.50 | 705.90 | 17.54 | 0.00 | 279.17 |
April | 325.17 | 0.50 | 0.48 | 01-APR-08:50 | 1203.56 | 14.86 | 0.00 | 354.50 | 749.30 | 18.34 | 4.00 | 321.67 |
May | 385.83 | 0.49 | 0.48 | 01-MAY-05:00 | 1484.41 | 16.97 | 38.50 | 413.33 | 905.52 | 20.18 | 46.83 | 384.33 |
June | 434.17 | 0.49 | 0.48 | 01-JUN-13:39 | 1556.24 | 19.85 | 107.67 | 442.50 | 912.32 | 20.13 | 44.00 | 419.33 |
July | 417.33 | 0.49 | 0.48 | 01-JUL-06:40 | 1521.68 | 18.42 | 72.17 | 427.33 | 916.56 | 18.99 | 22.00 | 403.67 |
August | 421.33 | 0.50 | 0.48 | 01-AUG-05:49 | 1182.13 | 14.42 | 0.00 | 400.67 | 780.92 | 17.99 | 5.83 | 381.83 |
September | 352.17 | 0.52 | 0.48 | 01-SEP-06:00 | 965.37 | 13.54 | 0.00 | 326.33 | 624.75 | 17.02 | 0.00 | 288.67 |
October | 317.67 | 0.53 | 0.48 | 01-OCT-08:00 | 792.49 | 12.49 | 0.00 | 278.33 | 504.04 | 16.07 | 0.00 | 230.00 |
November | 269.50 | 0.56 | 0.48 | 01-NOV-08:50 | 624.96 | 11.07 | 0.00 | 215.50 | 392.11 | 14.73 | 0.00 | 162.17 |
December | 236.83 | 0.58 | 0.48 | 01-DEC-09:50 | 541.36 | 10.27 | 0.00 | 190.83 | 338.01 | 13.97 | 0.00 | 121.00 |
Annual Sum or Average | 3965.83 | 0.52 | 1100.18 | 14.62 | 218.33 | 3796.17 | 681.67 | 17.48 | 122.67 | 3324.67 | ||
Minimum of Months | 226.83 | 0.49 | 0.48 | 541.36 | 10.27 | 0.00 | 190.83 | 338.01 | 13.97 | 0.00 | 121.00 | |
Maximum of Months | 434.17 | 0.58 | 0.48 | 1556.24 | 19.85 | 107.67 | 442.50 | 916.56 | 20.18 | 46.83 | 419.33 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_4_DAYLCTRL
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 226.83 | 0.54 | 0.48 | 01-JAN-10:09 | 1874.81 | 22.19 | 85.33 | 213.33 | 1110.77 | 22.66 | 72.33 | 180.00 |
February | 275.00 | 0.52 | 0.48 | 01-FEB-10:30 | 2423.57 | 22.85 | 95.17 | 247.33 | 1346.94 | 23.32 | 88.17 | 222.67 |
March | 304.00 | 0.50 | 0.48 | 01-MAR-08:20 | 3307.46 | 21.99 | 92.50 | 319.50 | 1866.31 | 23.87 | 92.00 | 292.67 |
April | 325.17 | 0.50 | 0.48 | 01-APR-08:00 | 3451.55 | 20.09 | 75.83 | 351.33 | 1975.73 | 21.31 | 48.00 | 320.33 |
May | 385.83 | 0.50 | 0.48 | 01-MAY-06:40 | 3921.55 | 18.98 | 75.00 | 405.67 | 2351.51 | 20.53 | 46.00 | 375.50 |
June | 434.17 | 0.50 | 0.48 | 01-JUN-13:39 | 4011.29 | 17.03 | 52.00 | 428.17 | 1871.02 | 18.04 | 0.00 | 399.33 |
July | 417.33 | 0.50 | 0.48 | 01-JUL-06:00 | 4652.50 | 19.08 | 79.67 | 413.00 | 2171.29 | 18.36 | 3.67 | 388.50 |
August | 421.33 | 0.51 | 0.48 | 01-AUG-06:49 | 3628.80 | 19.06 | 91.00 | 392.67 | 2048.42 | 20.32 | 58.00 | 365.67 |
September | 352.17 | 0.51 | 0.48 | 01-SEP-07:10 | 3611.41 | 22.47 | 116.83 | 331.17 | 1558.17 | 21.82 | 67.50 | 303.50 |
October | 317.67 | 0.52 | 0.48 | 01-OCT-09:09 | 2434.21 | 22.01 | 100.67 | 291.50 | 1372.36 | 22.76 | 91.00 | 262.33 |
November | 269.50 | 0.53 | 0.48 | 01-NOV-08:00 | 2087.75 | 22.89 | 102.83 | 233.17 | 1205.95 | 23.52 | 95.50 | 206.00 |
December | 236.83 | 0.54 | 0.48 | 01-DEC-09:39 | 1434.08 | 20.93 | 79.33 | 214.00 | 844.09 | 22.95 | 86.83 | 182.50 |
Annual Sum or Average | 3965.83 | 0.51 | 3250.80 | 20.49 | 1046.17 | 3840.83 | 1722.37 | 21.28 | 749.00 | 3499.00 | ||
Minimum of Months | 226.83 | 0.50 | 0.48 | 1434.08 | 17.03 | 52.00 | 213.33 | 844.09 | 18.04 | 0.00 | 180.00 | |
Maximum of Months | 434.17 | 0.54 | 0.48 | 4652.50 | 22.89 | 116.83 | 428.17 | 2351.51 | 23.87 | 95.50 | 399.33 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_1_DAYLCTRL
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 226.83 | 0.51 | 0.48 | 01-JAN-08:50 | 6317.94 | 36.62 | 216.33 | 232.67 | 5374.73 | 37.49 | 215.33 | 216.00 |
February | 275.00 | 0.50 | 0.48 | 01-FEB-08:20 | 8552.79 | 36.96 | 266.33 | 259.83 | 3790.09 | 30.09 | 179.83 | 248.17 |
March | 304.00 | 0.50 | 0.48 | 01-MAR-07:49 | 9967.73 | 32.26 | 254.17 | 324.17 | 2185.79 | 18.75 | 13.83 | 300.00 |
April | 325.17 | 0.50 | 0.48 | 01-APR-08:50 | 2566.38 | 14.71 | 0.00 | 351.67 | 1539.90 | 18.25 | 8.50 | 321.83 |
May | 385.83 | 0.51 | 0.48 | 01-MAY-06:30 | 2266.84 | 14.67 | 0.00 | 399.83 | 1336.01 | 18.15 | 1.67 | 364.33 |
June | 434.17 | 0.52 | 0.48 | 01-JUN-13:39 | 1951.39 | 14.29 | 0.00 | 415.00 | 1187.47 | 17.84 | 0.00 | 373.50 |
July | 417.33 | 0.50 | 0.48 | 01-JUL-06:40 | 2105.11 | 14.66 | 0.00 | 407.00 | 1317.13 | 18.24 | 1.17 | 377.83 |
August | 421.33 | 0.51 | 0.48 | 01-AUG-06:40 | 2251.24 | 13.92 | 0.00 | 386.67 | 1409.00 | 17.48 | 2.67 | 355.50 |
September | 352.17 | 0.52 | 0.48 | 01-SEP-06:00 | 3153.91 | 15.50 | 29.50 | 328.33 | 1667.66 | 17.57 | 14.17 | 303.67 |
October | 317.67 | 0.50 | 0.48 | 01-OCT-08:30 | 8652.57 | 34.23 | 283.00 | 302.00 | 2587.72 | 21.99 | 80.67 | 287.33 |
November | 269.50 | 0.50 | 0.48 | 01-NOV-07:00 | 6454.34 | 36.98 | 262.00 | 251.00 | 5757.37 | 38.26 | 263.00 | 242.50 |
December | 236.83 | 0.51 | 0.48 | 01-DEC-08:50 | 5019.03 | 37.37 | 231.33 | 232.50 | 4452.28 | 38.64 | 232.17 | 221.33 |
Annual Sum or Average | 3965.83 | 0.51 | 4535.29 | 23.21 | 1542.67 | 3890.67 | 2424.82 | 22.89 | 1013.00 | 3612.00 | ||
Minimum of Months | 226.83 | 0.50 | 0.48 | 1951.39 | 13.92 | 0.00 | 232.50 | 1187.47 | 17.48 | 0.00 | 216.00 | |
Maximum of Months | 434.17 | 0.52 | 0.48 | 9967.73 | 37.37 | 283.00 | 415.00 | 5757.37 | 38.64 | 263.00 | 377.83 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_2_DAYLCTRL
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 226.83 | 0.53 | 0.48 | 01-JAN-08:50 | 2015.13 | 23.36 | 89.67 | 219.67 | 1168.68 | 23.57 | 76.67 | 189.67 |
February | 275.00 | 0.52 | 0.48 | 01-FEB-08:09 | 2217.52 | 20.69 | 75.00 | 248.83 | 1253.99 | 22.59 | 75.83 | 222.00 |
March | 304.00 | 0.50 | 0.48 | 01-MAR-07:40 | 3522.52 | 22.24 | 94.50 | 321.33 | 2023.85 | 24.00 | 92.00 | 294.00 |
April | 325.17 | 0.49 | 0.48 | 01-APR-08:39 | 3543.73 | 21.36 | 85.33 | 359.17 | 2012.86 | 22.42 | 60.17 | 328.83 |
May | 385.83 | 0.50 | 0.48 | 01-MAY-05:40 | 3886.78 | 21.63 | 113.00 | 411.00 | 1760.04 | 21.46 | 57.83 | 377.33 |
June | 434.17 | 0.51 | 0.48 | 01-JUN-13:39 | 4699.75 | 21.99 | 134.17 | 426.33 | 2114.65 | 22.52 | 89.50 | 397.33 |
July | 417.33 | 0.49 | 0.48 | 01-JUL-06:40 | 5119.60 | 22.87 | 134.00 | 424.00 | 2265.82 | 22.29 | 75.50 | 399.00 |
August | 421.33 | 0.51 | 0.48 | 01-AUG-05:30 | 4099.47 | 22.22 | 131.33 | 394.33 | 2405.03 | 23.11 | 101.00 | 367.67 |
September | 352.17 | 0.51 | 0.48 | 01-SEP-06:19 | 3095.43 | 21.41 | 104.17 | 328.83 | 1753.78 | 22.34 | 78.33 | 303.50 |
October | 317.67 | 0.52 | 0.48 | 01-OCT-08:20 | 2757.10 | 21.93 | 107.00 | 292.67 | 1605.88 | 23.08 | 101.17 | 262.00 |
November | 269.50 | 0.53 | 0.48 | 01-NOV-07:49 | 1747.31 | 20.68 | 83.00 | 234.83 | 1015.16 | 22.69 | 82.00 | 208.50 |
December | 236.83 | 0.54 | 0.48 | 01-DEC-08:50 | 1566.11 | 23.44 | 101.83 | 213.00 | 944.55 | 23.79 | 89.33 | 178.67 |
Annual Sum or Average | 3965.83 | 0.51 | 3404.52 | 21.97 | 1253.00 | 3874.00 | 1780.42 | 22.74 | 979.33 | 3528.50 | ||
Minimum of Months | 226.83 | 0.49 | 0.48 | 1566.11 | 20.68 | 75.00 | 213.00 | 944.55 | 21.46 | 57.83 | 178.67 | |
Maximum of Months | 434.17 | 0.54 | 0.48 | 5119.60 | 23.44 | 134.17 | 426.33 | 2405.03 | 24.00 | 101.17 | 399.00 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_3_DAYLCTRL
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 226.83 | 0.56 | 0.48 | 01-JAN-10:20 | 664.79 | 10.96 | 0.00 | 197.33 | 410.34 | 14.54 | 0.00 | 143.83 |
February | 275.00 | 0.54 | 0.48 | 01-FEB-10:30 | 733.10 | 12.02 | 0.00 | 235.17 | 470.82 | 15.67 | 0.00 | 189.83 |
March | 304.00 | 0.51 | 0.48 | 01-MAR-08:09 | 1151.92 | 14.05 | 0.00 | 314.50 | 706.89 | 17.52 | 0.00 | 279.17 |
April | 325.17 | 0.50 | 0.48 | 01-APR-08:50 | 1204.79 | 14.83 | 0.00 | 354.50 | 750.31 | 18.32 | 3.83 | 322.17 |
May | 385.83 | 0.49 | 0.48 | 01-MAY-05:00 | 1485.90 | 16.94 | 38.50 | 413.33 | 906.71 | 20.16 | 46.67 | 384.83 |
June | 434.17 | 0.49 | 0.48 | 01-JUN-13:39 | 1557.45 | 19.82 | 107.50 | 442.50 | 913.44 | 20.11 | 43.33 | 419.50 |
July | 417.33 | 0.49 | 0.48 | 01-JUL-06:40 | 1522.76 | 18.39 | 72.17 | 427.33 | 917.61 | 18.98 | 21.33 | 403.83 |
August | 421.33 | 0.50 | 0.48 | 01-AUG-05:49 | 1183.08 | 14.39 | 0.00 | 400.67 | 781.81 | 17.97 | 5.67 | 381.83 |
September | 352.17 | 0.52 | 0.48 | 01-SEP-06:00 | 966.17 | 13.51 | 0.00 | 326.33 | 625.50 | 17.01 | 0.00 | 288.67 |
October | 317.67 | 0.53 | 0.48 | 01-OCT-08:00 | 793.19 | 12.46 | 0.00 | 278.50 | 504.69 | 16.06 | 0.00 | 230.00 |
November | 269.50 | 0.56 | 0.48 | 01-NOV-08:50 | 625.52 | 11.04 | 0.00 | 215.50 | 392.64 | 14.72 | 0.00 | 162.33 |
December | 236.83 | 0.58 | 0.48 | 01-DEC-09:50 | 541.82 | 10.24 | 0.00 | 191.17 | 338.48 | 13.95 | 0.00 | 121.17 |
Annual Sum or Average | 3965.83 | 0.52 | 1101.14 | 14.59 | 218.17 | 3796.83 | 682.53 | 17.46 | 120.83 | 3327.17 | ||
Minimum of Months | 226.83 | 0.49 | 0.48 | 541.82 | 10.24 | 0.00 | 191.17 | 338.48 | 13.95 | 0.00 | 121.17 | |
Maximum of Months | 434.17 | 0.58 | 0.48 | 1557.45 | 19.82 | 107.50 | 442.50 | 917.61 | 20.16 | 46.67 | 419.50 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_4_DAYLCTRL
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 226.83 | 0.54 | 0.48 | 01-JAN-10:09 | 1875.86 | 22.17 | 85.33 | 213.33 | 1111.81 | 22.65 | 72.17 | 180.00 |
February | 275.00 | 0.52 | 0.48 | 01-FEB-10:30 | 2424.60 | 22.83 | 95.17 | 247.33 | 1348.08 | 23.31 | 87.67 | 222.67 |
March | 304.00 | 0.50 | 0.48 | 01-MAR-08:20 | 3309.65 | 21.97 | 92.50 | 319.50 | 1868.19 | 23.86 | 90.67 | 292.83 |
April | 325.17 | 0.50 | 0.48 | 01-APR-08:00 | 3453.56 | 20.06 | 75.83 | 351.33 | 1977.65 | 21.29 | 48.00 | 320.33 |
May | 385.83 | 0.50 | 0.48 | 01-MAY-06:40 | 3923.82 | 18.95 | 75.00 | 405.67 | 2353.53 | 20.52 | 46.00 | 375.50 |
June | 434.17 | 0.50 | 0.48 | 01-JUN-13:39 | 4013.35 | 17.00 | 52.00 | 428.33 | 1872.86 | 18.02 | 0.00 | 399.50 |
July | 417.33 | 0.50 | 0.48 | 01-JUL-06:00 | 4654.34 | 19.04 | 79.67 | 413.00 | 2173.10 | 18.34 | 3.67 | 388.50 |
August | 421.33 | 0.51 | 0.48 | 01-AUG-06:49 | 3630.51 | 19.03 | 91.00 | 392.67 | 2050.06 | 20.30 | 58.00 | 365.67 |
September | 352.17 | 0.51 | 0.48 | 01-SEP-07:10 | 3612.83 | 22.45 | 116.83 | 331.17 | 1559.63 | 21.81 | 67.33 | 304.00 |
October | 317.67 | 0.52 | 0.48 | 01-OCT-09:09 | 2435.34 | 21.99 | 100.67 | 291.50 | 1373.59 | 22.75 | 90.33 | 262.33 |
November | 269.50 | 0.53 | 0.48 | 01-NOV-08:00 | 2088.64 | 22.86 | 102.83 | 233.17 | 1206.95 | 23.51 | 95.17 | 206.17 |
December | 236.83 | 0.54 | 0.48 | 01-DEC-09:39 | 1434.81 | 20.90 | 79.17 | 214.00 | 844.92 | 22.94 | 86.83 | 182.50 |
Annual Sum or Average | 3965.83 | 0.51 | 3252.41 | 20.47 | 1046.00 | 3841.00 | 1723.91 | 21.27 | 745.83 | 3500.00 | ||
Minimum of Months | 226.83 | 0.50 | 0.48 | 1434.81 | 17.00 | 52.00 | 213.33 | 844.92 | 18.02 | 0.00 | 180.00 | |
Maximum of Months | 434.17 | 0.54 | 0.48 | 4654.34 | 22.86 | 116.83 | 428.33 | 2353.53 | 23.86 | 95.17 | 399.50 |
Report: CoilReportMonthly
For: VAV_BOT WITH REHEAT HEATING COIL
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.334272E+11 | 77068.73 | 10-JAN-22:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.168618E+11 | 58624.87 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.739902E+10 | 48836.56 | 06-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.926557E+09 | 23144.83 | 29-APR-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.646080E+09 | 16590.06 | 08-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 6526257.58 | 2522.90 | 16-JUN-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 76527636.64 | 6285.01 | 19-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.735085E+09 | 20113.00 | 10-OCT-06:55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.494349E+10 | 37057.99 | 27-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.179493E+11 | 62767.94 | 29-DEC-08:65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.829716E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.334272E+11 | 77068.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_BOTTOM VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.424173E+10 | 16721.01 | 04-JAN-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.135167E+10 | 16767.52 | 24-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.338520E+09 | 16767.39 | 03-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 3448162.42 | 13067.64 | 29-APR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 11586585.55 | 15538.97 | 08-MAY-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 579529.37 | 270.44 | 10-OCT-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.204542E+09 | 16816.45 | 13-NOV-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.112533E+10 | 16771.36 | 01-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.727740E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.424173E+10 | 16816.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.354685E+10 | 18501.61 | 04-JAN-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.144724E+10 | 18512.88 | 24-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.551942E+09 | 18512.15 | 03-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 71648919.56 | 18518.81 | 29-APR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 47147263.65 | 18549.08 | 22-MAY-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 5900379.35 | 1445.08 | 19-SEP-05:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 57672043.45 | 10050.55 | 10-OCT-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.511152E+09 | 18528.61 | 13-NOV-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.168174E+10 | 18529.48 | 13-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.792130E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.354685E+10 | 18549.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.430851E+10 | 26230.81 | 04-JAN-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.146107E+10 | 26296.13 | 17-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.629086E+09 | 26246.99 | 03-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 89189676.76 | 26255.60 | 29-APR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.148077E+09 | 26304.93 | 22-MAY-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 172832.15 | 942.24 | 17-JUN-05:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 16029585.76 | 2616.72 | 19-SEP-05:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 80464254.53 | 26395.38 | 10-OCT-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.552328E+09 | 26316.10 | 30-NOV-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.167070E+10 | 26365.91 | 11-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.895562E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.430851E+10 | 26395.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.253831E+10 | 17703.94 | 07-JAN-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.580641E+09 | 17681.21 | 07-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 90027798.23 | 17678.80 | 06-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 14552108.67 | 12859.79 | 08-MAY-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 201521.79 | 133.92 | 10-OCT-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 49231295.27 | 17680.08 | 27-NOV-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.245836E+09 | 17676.60 | 29-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.351880E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.253831E+10 | 17703.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV_MID WITH REHEAT HEATING COIL
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.402079E+12 | 825840.54 | 10-JAN-22:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.219980E+12 | 643291.98 | 01-FEB-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.127331E+12 | 550592.71 | 06-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.297208E+11 | 259633.25 | 29-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.185239E+11 | 201737.30 | 08-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.281312E+09 | 74287.97 | 16-JUN-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.320123E+10 | 93711.58 | 19-SEP-06:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.214835E+11 | 264019.44 | 10-OCT-06:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.952097E+11 | 436528.98 | 27-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.258249E+12 | 701628.44 | 29-DEC-08:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.117606E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.402079E+12 | 825840.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_MID VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.159645E+11 | 635924.43 | 02-JAN-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.400998E+10 | 635392.73 | 06-FEB-05:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.174979E+10 | 633382.37 | 06-MAR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.159917E+10 | 634800.03 | 27-NOV-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.620659E+10 | 634860.57 | 26-DEC-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.295300E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.159645E+11 | 635924.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.123651E+12 | 149980.49 | 12-JAN-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.614166E+11 | 149583.27 | 07-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.332930E+11 | 149057.07 | 06-MAR-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.688795E+10 | 160639.33 | 06-APR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.490266E+10 | 160069.72 | 11-MAY-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 39760311.66 | 27805.98 | 17-JUN-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 17774225.34 | 44289.10 | 18-AUG-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.152028E+10 | 157430.37 | 12-SEP-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.652061E+10 | 161379.53 | 21-OCT-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.329568E+11 | 155721.13 | 04-NOV-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.799647E+11 | 150128.66 | 04-DEC-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.351171E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.123651E+12 | 161379.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.864823E+11 | 219945.45 | 10-JAN-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.429988E+11 | 219823.93 | 21-FEB-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.259790E+11 | 220044.06 | 06-MAR-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.731352E+10 | 219069.17 | 15-APR-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.495026E+10 | 219243.96 | 22-MAY-04:42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.190326E+09 | 46660.64 | 17-JUN-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 67900947.97 | 69673.03 | 18-AUG-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.203844E+10 | 200459.31 | 19-SEP-04:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.687602E+10 | 219290.33 | 31-OCT-04:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.276001E+11 | 219857.36 | 27-NOV-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.601194E+11 | 220052.46 | 26-DEC-05:22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.264616E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.864823E+11 | 220052.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.881079E+11 | 268780.94 | 31-JAN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.376699E+11 | 269352.44 | 07-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.256481E+11 | 268470.61 | 06-MAR-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.802470E+10 | 266897.86 | 29-APR-04:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.694498E+10 | 267737.57 | 08-MAY-04:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.292990E+09 | 97948.49 | 17-JUN-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.121233E+09 | 75330.07 | 18-AUG-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.166331E+10 | 198964.40 | 19-SEP-04:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.466064E+10 | 267659.26 | 10-OCT-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.233642E+11 | 269397.98 | 28-NOV-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.539178E+11 | 268679.86 | 27-DEC-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.250416E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.881079E+11 | 269397.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.820086E+11 | 227068.82 | 10-JAN-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.392534E+11 | 226594.27 | 11-FEB-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.247366E+11 | 226409.34 | 04-MAR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.644097E+10 | 226025.42 | 01-APR-04:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.475551E+10 | 226310.45 | 22-MAY-04:42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.230424E+09 | 56198.13 | 17-JUN-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.118340E+09 | 50047.47 | 18-AUG-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.209375E+10 | 160778.10 | 19-SEP-04:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.653854E+10 | 226234.94 | 10-OCT-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.241585E+11 | 226975.17 | 27-NOV-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.525056E+11 | 227171.75 | 26-DEC-05:22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.242840E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.820086E+11 | 227171.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV_TOP WITH REHEAT HEATING COIL
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.457296E+11 | 88398.87 | 10-JAN-22:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.249631E+11 | 71199.26 | 01-FEB-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.160272E+11 | 62089.62 | 04-MAR-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.506221E+10 | 32546.57 | 29-APR-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.299226E+10 | 24941.02 | 08-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.154390E+09 | 10533.78 | 16-JUN-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 1445068.90 | 1572.18 | 18-AUG-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.888322E+09 | 14415.99 | 19-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.375791E+10 | 31909.20 | 10-OCT-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.121933E+11 | 46658.20 | 27-NOV-07:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.308375E+11 | 77233.97 | 29-DEC-08:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.142607E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.457296E+11 | 88398.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_TOP VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.148305E+11 | 84267.66 | 02-JAN-05:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.644804E+10 | 84239.88 | 07-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.368362E+10 | 84218.08 | 07-MAR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.439733E+09 | 82983.11 | 10-APR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.992832E+09 | 84224.35 | 08-MAY-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 25235879.51 | 12931.51 | 19-SEP-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.666311E+09 | 84223.88 | 10-OCT-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.406143E+10 | 83998.91 | 20-NOV-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.933647E+10 | 83985.14 | 11-DEC-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.404842E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.148305E+11 | 84267.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.191053E+11 | 17212.17 | 03-JAN-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.106925E+11 | 17217.14 | 21-FEB-05:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.713354E+10 | 17216.79 | 20-MAR-04:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.235713E+10 | 17207.09 | 10-APR-05:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.168875E+10 | 17215.88 | 01-MAY-04:33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 67703078.23 | 17127.90 | 17-JUN-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 523741.49 | 1538.88 | 08-JUL-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 45012347.28 | 17126.60 | 18-AUG-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.725256E+09 | 17251.47 | 13-SEP-04:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.240377E+10 | 17264.12 | 10-OCT-04:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.740258E+10 | 17264.77 | 06-NOV-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.144232E+11 | 17217.90 | 09-DEC-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.660453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 523741.49 | 1538.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.191053E+11 | 17264.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.127141E+11 | 22643.46 | 12-JAN-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.675374E+10 | 22641.50 | 11-FEB-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.464722E+10 | 22564.88 | 18-MAR-04:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.166610E+10 | 22584.51 | 29-APR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.119995E+10 | 22590.47 | 08-MAY-04:32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 74796860.42 | 22454.92 | 17-JUN-04:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 7273476.53 | 2056.48 | 08-JUL-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 48787752.53 | 12430.93 | 18-AUG-04:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.587613E+09 | 22572.32 | 19-SEP-04:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.167958E+10 | 22585.70 | 10-OCT-04:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.505885E+10 | 22594.67 | 29-NOV-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.973321E+10 | 22599.88 | 16-DEC-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.441712E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 7273476.53 | 2056.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.127141E+11 | 22643.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.144675E+11 | 28567.15 | 12-JAN-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.696235E+10 | 28579.12 | 08-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.554720E+10 | 28656.05 | 22-MAR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.234381E+10 | 28547.65 | 29-APR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.196172E+10 | 28657.66 | 09-MAY-04:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.219896E+09 | 28420.14 | 17-JUN-04:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 15718141.84 | 5997.03 | 08-JUL-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 82059590.59 | 18163.48 | 18-AUG-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.709444E+09 | 28539.44 | 20-SEP-04:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.172662E+10 | 28746.47 | 10-OCT-04:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.505166E+10 | 28568.89 | 21-NOV-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.102949E+11 | 28576.19 | 21-DEC-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.493828E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 15718141.84 | 5997.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.144675E+11 | 28746.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.122803E+11 | 25664.52 | 21-JAN-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.620394E+10 | 25579.32 | 09-FEB-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.454763E+10 | 25571.68 | 04-MAR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.164952E+10 | 25524.91 | 19-APR-04:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.122146E+10 | 25651.98 | 22-MAY-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.139822E+09 | 19723.65 | 17-JUN-04:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 3089611.83 | 1164.81 | 08-JUL-05:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 65359417.18 | 10943.61 | 18-AUG-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.656127E+09 | 25535.74 | 13-SEP-04:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.171931E+10 | 25559.02 | 10-OCT-04:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.449263E+10 | 25678.25 | 29-NOV-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.853060E+10 | 25674.58 | 19-DEC-05:22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.415098E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 3089611.83 | 1164.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.122803E+11 | 25678.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CAV_BAS HEATING COIL
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.309488E+09 | 23134.85 | 10-JAN-22:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.309488E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.309488E+09 | 23134.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BASEMENT HEATING COIL
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BOT HEATING COIL
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER MID HEATING COIL
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER TOP HEATING COIL
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BOT_SUPPHEATCOIL
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER MID_SUPPHEATCOIL
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER TOP_SUPPHEATCOIL
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV_BOT WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.736348E+09 | 0.736348E+09 | 46910.45 | 27-FEB-15:30 | 46910.45 | 0.00 |
March | 0.00 | 0.00 | 64191064.87 | 64191064.87 | 12393.11 | 14-MAR-13:30 | 12393.11 | 0.00 |
April | 0.00 | 0.00 | 0.713072E+10 | 0.713072E+10 | 90172.76 | 06-APR-16:00 | 90172.76 | 0.00 |
May | 0.00 | 0.00 | 0.195332E+11 | 0.195332E+11 | 121968.00 | 19-MAY-15:20 | 121968.00 | 0.04 |
June | 0.00 | 0.00 | 0.638689E+11 | 0.638186E+11 | 138857.99 | 29-JUN-14:40 | 138857.99 | 0.22 |
July | 0.00 | 0.00 | 0.108592E+12 | 0.108413E+12 | 165129.77 | 17-JUL-15:20 | 165129.77 | 0.37 |
August | 0.00 | 0.00 | 0.991574E+11 | 0.991574E+11 | 164372.12 | 07-AUG-15:20 | 164372.12 | 0.20 |
September | 0.00 | 0.00 | 0.413584E+11 | 0.400217E+11 | 214303.48 | 07-SEP-15:00 | 113475.06 | 0.16 |
October | 0.00 | 0.00 | 0.112922E+11 | 0.112922E+11 | 112935.89 | 18-OCT-15:50 | 112935.89 | 0.00 |
November | 0.00 | 0.00 | 0.616459E+09 | 0.616459E+09 | 20234.37 | 03-NOV-14:00 | 20234.37 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.352350E+12 | 0.350784E+12 | 0.08 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.108592E+12 | 0.108413E+12 | 214303.48 | 165129.77 | 0.37 |
Report: CoilReportMonthly
For: VAV_MID WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 31506.06 | 31506.06 | 3.41 | 03-JAN-06:00 | 3.41 | 0.00 |
February | 0.00 | 0.00 | 0.582135E+10 | 0.582135E+10 | 343626.02 | 27-FEB-14:00 | 343626.02 | 0.00 |
March | 0.00 | 0.00 | 0.247060E+09 | 0.247060E+09 | 68784.96 | 14-MAR-13:30 | 68784.96 | 0.00 |
April | 0.00 | 0.00 | 0.511108E+11 | 0.511108E+11 | 720946.46 | 06-APR-16:00 | 720946.46 | 0.00 |
May | 0.00 | 0.00 | 0.167845E+12 | 0.167845E+12 | 1165675.81 | 19-MAY-15:30 | 1165675.81 | 0.04 |
June | 0.00 | 0.00 | 0.544162E+12 | 0.543727E+12 | 1309120.82 | 29-JUN-14:50 | 1309120.82 | 0.20 |
July | 0.00 | 0.00 | 0.910049E+12 | 0.908886E+12 | 1524359.19 | 17-JUL-15:30 | 1524359.19 | 0.32 |
August | 0.00 | 0.00 | 0.790119E+12 | 0.790119E+12 | 1449182.73 | 07-AUG-15:40 | 1449182.73 | 0.18 |
September | 0.00 | 0.00 | 0.364666E+12 | 0.352764E+12 | 2000275.77 | 07-SEP-15:00 | 1058588.83 | 0.16 |
October | 0.00 | 0.00 | 0.893588E+11 | 0.893588E+11 | 956004.05 | 18-OCT-15:20 | 956004.05 | 0.00 |
November | 0.00 | 0.00 | 0.448429E+10 | 0.448429E+10 | 187325.68 | 03-NOV-13:55 | 187325.68 | 0.00 |
December | 0.00 | 0.00 | 64277.76 | 64277.76 | 3.26 | 17-DEC-15:55 | 3.26 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.292786E+13 | 0.291436E+13 | 0.08 | |||
Minimum of Months | 0.00 | 0.00 | 31506.06 | 31506.06 | 3.26 | 3.26 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.910049E+12 | 0.908886E+12 | 2000275.77 | 1524359.19 | 0.32 |
Report: CoilReportMonthly
For: VAV_TOP WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 52824.02 | 52824.02 | 147.30 | 26-JAN-00:50 | 147.30 | 0.00 |
February | 0.00 | 0.00 | 0.390482E+09 | 0.390482E+09 | 27817.44 | 27-FEB-13:40 | 27817.44 | 0.00 |
March | 0.00 | 0.00 | 2331981.52 | 2331981.52 | 644.13 | 14-MAR-14:00 | 644.13 | 0.00 |
April | 0.00 | 0.00 | 0.479342E+10 | 0.479342E+10 | 73320.21 | 06-APR-16:00 | 73320.21 | 0.00 |
May | 0.00 | 0.00 | 0.173282E+11 | 0.173282E+11 | 137325.88 | 19-MAY-15:30 | 137325.88 | 0.04 |
June | 0.00 | 0.00 | 0.588673E+11 | 0.588156E+11 | 152417.15 | 29-JUN-14:50 | 152417.15 | 0.20 |
July | 0.00 | 0.00 | 0.988626E+11 | 0.987638E+11 | 180544.94 | 17-JUL-15:30 | 180544.94 | 0.32 |
August | 0.00 | 0.00 | 0.839504E+11 | 0.839504E+11 | 170583.07 | 07-AUG-15:40 | 170583.07 | 0.17 |
September | 0.00 | 0.00 | 0.370519E+11 | 0.358533E+11 | 202482.58 | 07-SEP-15:20 | 116218.37 | 0.15 |
October | 0.00 | 0.00 | 0.773586E+10 | 0.773586E+10 | 98579.15 | 18-OCT-15:10 | 98579.15 | 0.00 |
November | 0.00 | 0.00 | 0.331261E+09 | 0.331261E+09 | 11249.30 | 04-NOV-14:00 | 11249.30 | 0.00 |
December | 0.00 | 0.00 | 126715.88 | 126715.88 | 542.99 | 28-DEC-00:33 | 542.99 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.309314E+12 | 0.307965E+12 | 0.07 | |||
Minimum of Months | 0.00 | 0.00 | 52824.02 | 52824.02 | 147.30 | 147.30 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.988626E+11 | 0.987638E+11 | 202482.58 | 180544.94 | 0.32 |
Report: CoilReportMonthly
For: CAV_BAS COOLING COIL
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 430925.51 | 430925.51 | 4458.97 | 24-JAN-05:11 | 4458.97 | 0.00 |
February | 0.00 | 0.00 | 0.282169E+09 | 0.282169E+09 | 25368.65 | 27-FEB-15:00 | 25368.65 | 0.00 |
March | 0.00 | 0.00 | 36227.49 | 36227.49 | 60.38 | 01-MAR-08:00 | 60.38 | 0.00 |
April | 0.00 | 0.00 | 0.252028E+10 | 0.252028E+10 | 52517.91 | 07-APR-14:00 | 52517.91 | 0.00 |
May | 0.00 | 0.00 | 0.934050E+10 | 0.934050E+10 | 64225.30 | 29-MAY-14:30 | 64225.30 | 0.03 |
June | 0.00 | 0.00 | 0.331920E+11 | 0.331666E+11 | 72998.31 | 13-JUN-04:12 | 33354.29 | 0.15 |
July | 0.00 | 0.00 | 0.565008E+11 | 0.564569E+11 | 150741.40 | 16-JUL-17:50 | 127736.43 | 0.27 |
August | 0.00 | 0.00 | 0.517700E+11 | 0.517700E+11 | 126509.60 | 06-AUG-19:20 | 126509.60 | 0.16 |
September | 0.00 | 0.00 | 0.214620E+11 | 0.210835E+11 | 137559.32 | 03-SEP-13:58 | 137559.32 | 0.13 |
October | 0.00 | 0.00 | 0.593250E+10 | 0.593250E+10 | 62656.09 | 18-OCT-14:00 | 62656.09 | 0.00 |
November | 0.00 | 0.00 | 75754208.78 | 75754208.78 | 29207.11 | 17-NOV-06:03 | 29207.11 | 0.00 |
December | 0.00 | 0.00 | 22839.71 | 22839.71 | 38.07 | 15-DEC-18:10 | 38.07 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.181077E+12 | 0.180629E+12 | 0.06 | |||
Minimum of Months | 0.00 | 0.00 | 22839.71 | 22839.71 | 38.07 | 38.07 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.565008E+11 | 0.564569E+11 | 150741.40 | 137559.32 | 0.27 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BASEMENT COOLING COIL
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.897821E+10 | 0.781808E+10 | 5237.54 | 03-JAN-15:00 | 4757.70 | 0.00 |
February | 0.00 | 0.00 | 0.135760E+11 | 0.120041E+11 | 17900.29 | 27-FEB-16:00 | 17900.29 | 0.00 |
March | 0.00 | 0.00 | 0.150884E+11 | 0.143569E+11 | 6752.56 | 31-MAR-23:10 | 5614.25 | 0.00 |
April | 0.00 | 0.00 | 0.751158E+11 | 0.720706E+11 | 316261.64 | 07-APR-14:00 | 316261.64 | 0.00 |
May | 0.00 | 0.00 | 0.181394E+11 | 0.169445E+11 | 139501.15 | 19-MAY-13:50 | 133355.86 | 0.00 |
June | 0.00 | 0.00 | 0.136834E+12 | 0.123616E+12 | 325811.76 | 20-JUN-18:50 | 221525.88 | 0.00 |
July | 0.00 | 0.00 | 0.448356E+12 | 0.401143E+12 | 415623.81 | 19-JUL-10:50 | 315701.60 | 0.00 |
August | 0.00 | 0.00 | 0.569901E+12 | 0.519336E+12 | 413350.51 | 08-AUG-12:00 | 346369.33 | 0.00 |
September | 0.00 | 0.00 | 0.454441E+11 | 0.414243E+11 | 216458.25 | 07-SEP-16:00 | 127271.00 | 0.00 |
October | 0.00 | 0.00 | 0.247462E+11 | 0.231347E+11 | 178394.39 | 18-OCT-15:00 | 178394.39 | 0.00 |
November | 0.00 | 0.00 | 0.165686E+11 | 0.156691E+11 | 68223.84 | 17-NOV-17:00 | 65122.94 | 0.00 |
December | 0.00 | 0.00 | 0.166132E+11 | 0.162722E+11 | 65679.09 | 10-DEC-02:00 | 65679.09 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.138936E+13 | 0.126379E+13 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.897821E+10 | 0.781808E+10 | 5237.54 | 4757.70 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.569901E+12 | 0.519336E+12 | 415623.81 | 346369.33 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BOT COOLING COIL
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.291329E+10 | 0.291296E+10 | 2401.99 | 13-JAN-16:20 | 2401.99 | 0.00 |
February | 0.00 | 0.00 | 0.827107E+10 | 0.827107E+10 | 5256.52 | 26-FEB-17:27 | 5256.52 | 0.00 |
March | 0.00 | 0.00 | 0.149973E+11 | 0.149973E+11 | 7466.50 | 31-MAR-24:00 | 7466.50 | 0.00 |
April | 0.00 | 0.00 | 0.201480E+11 | 0.201392E+11 | 9157.56 | 22-APR-18:10 | 9157.56 | 0.00 |
May | 0.00 | 0.00 | 0.576652E+10 | 0.573886E+10 | 4164.37 | 31-MAY-24:00 | 4164.37 | 0.00 |
June | 0.00 | 0.00 | 0.111022E+11 | 0.110072E+11 | 6036.03 | 30-JUN-23:03 | 6016.52 | 0.00 |
July | 0.00 | 0.00 | 0.168060E+11 | 0.167039E+11 | 7926.56 | 31-JUL-23:45 | 7926.56 | 0.00 |
August | 0.00 | 0.00 | 0.217253E+11 | 0.216487E+11 | 9145.19 | 05-AUG-20:00 | 9145.19 | 0.00 |
September | 0.00 | 0.00 | 0.587028E+10 | 0.577824E+10 | 3959.58 | 30-SEP-24:00 | 3959.58 | 0.00 |
October | 0.00 | 0.00 | 0.106273E+11 | 0.106145E+11 | 5588.44 | 31-OCT-24:00 | 5588.44 | 0.00 |
November | 0.00 | 0.00 | 0.146614E+11 | 0.146588E+11 | 6736.38 | 03-NOV-16:00 | 6665.18 | 0.00 |
December | 0.00 | 0.00 | 0.194801E+11 | 0.194799E+11 | 8462.04 | 06-DEC-16:10 | 8438.69 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.152369E+12 | 0.151951E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.291329E+10 | 0.291296E+10 | 2401.99 | 2401.99 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.217253E+11 | 0.216487E+11 | 9157.56 | 9157.56 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER MID COOLING COIL
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.756959E+10 | 0.756360E+10 | 20207.05 | 13-JAN-16:30 | 20207.05 | 0.00 |
February | 0.00 | 0.00 | 0.590737E+11 | 0.590737E+11 | 45674.11 | 28-FEB-17:00 | 45674.11 | 0.00 |
March | 0.00 | 0.00 | 0.124694E+12 | 0.124694E+12 | 65460.75 | 28-MAR-17:50 | 65460.75 | 0.00 |
April | 0.00 | 0.00 | 0.180360E+12 | 0.180271E+12 | 85319.65 | 22-APR-18:12 | 85319.65 | 0.00 |
May | 0.00 | 0.00 | 0.465520E+11 | 0.462846E+11 | 39332.27 | 31-MAY-24:00 | 39332.27 | 0.00 |
June | 0.00 | 0.00 | 0.101940E+12 | 0.101001E+12 | 58852.63 | 30-JUN-23:03 | 58655.87 | 0.00 |
July | 0.00 | 0.00 | 0.158348E+12 | 0.157333E+12 | 76965.51 | 31-JUL-23:53 | 76965.51 | 0.00 |
August | 0.00 | 0.00 | 0.204472E+12 | 0.203711E+12 | 87881.53 | 03-AUG-18:50 | 87881.53 | 0.00 |
September | 0.00 | 0.00 | 0.493391E+11 | 0.484440E+11 | 35042.68 | 30-SEP-23:30 | 35042.68 | 0.00 |
October | 0.00 | 0.00 | 0.883410E+11 | 0.882148E+11 | 48655.50 | 15-OCT-17:06 | 48655.50 | 0.00 |
November | 0.00 | 0.00 | 0.120428E+12 | 0.120401E+12 | 62335.05 | 03-NOV-16:00 | 61634.34 | 0.00 |
December | 0.00 | 0.00 | 0.157995E+12 | 0.157992E+12 | 77285.57 | 06-DEC-16:10 | 77011.85 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.129911E+13 | 0.129498E+13 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.756959E+10 | 0.756360E+10 | 20207.05 | 20207.05 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.204472E+12 | 0.203711E+12 | 87881.53 | 87881.53 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER TOP COOLING COIL
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.304978E+09 | 0.304774E+09 | 1968.42 | 13-JAN-16:30 | 1968.42 | 0.00 |
February | 0.00 | 0.00 | 0.440339E+10 | 0.440339E+10 | 4520.39 | 28-FEB-17:00 | 4520.39 | 0.00 |
March | 0.00 | 0.00 | 0.109375E+11 | 0.109375E+11 | 6546.80 | 28-MAR-17:50 | 6546.80 | 0.00 |
April | 0.00 | 0.00 | 0.169319E+11 | 0.169231E+11 | 8603.18 | 25-APR-18:10 | 8603.18 | 0.00 |
May | 0.00 | 0.00 | 0.400971E+10 | 0.398330E+10 | 3862.25 | 31-MAY-23:30 | 3862.25 | 0.00 |
June | 0.00 | 0.00 | 0.996639E+10 | 0.987272E+10 | 5885.09 | 30-JUN-23:03 | 5865.18 | 0.00 |
July | 0.00 | 0.00 | 0.157522E+11 | 0.156509E+11 | 7690.64 | 31-JUL-23:53 | 7690.64 | 0.00 |
August | 0.00 | 0.00 | 0.202910E+11 | 0.202151E+11 | 8907.10 | 05-AUG-19:55 | 8907.10 | 0.00 |
September | 0.00 | 0.00 | 0.438949E+10 | 0.430110E+10 | 3666.99 | 04-SEP-17:51 | 3666.99 | 0.00 |
October | 0.00 | 0.00 | 0.749428E+10 | 0.748190E+10 | 4879.54 | 18-OCT-17:00 | 4879.54 | 0.00 |
November | 0.00 | 0.00 | 0.102901E+11 | 0.102875E+11 | 6187.49 | 03-NOV-16:00 | 6117.65 | 0.00 |
December | 0.00 | 0.00 | 0.139265E+11 | 0.139262E+11 | 7669.92 | 06-DEC-16:10 | 7644.58 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.118697E+12 | 0.118288E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.304978E+09 | 0.304774E+09 | 1968.42 | 1968.42 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.202910E+11 | 0.202151E+11 | 8907.10 | 8907.10 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 357372.88 | 2138250.95 | 23-JAN-05:11 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 200329.81 | 2081493.97 | 07-FEB-06:01 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 107069.79 | 1927328.50 | 06-MAR-05:01 |
April | 0.00 | 0.00 | 01-APR-00:10 | 27907.21 | 1629520.69 | 01-APR-04:11 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 18872.98 | 1654154.34 | 09-MAY-04:01 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 647.71 | 370308.82 | 17-JUN-05:03 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 9.28 | 10059.99 | 08-JUL-05:03 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 210.95 | 372323.64 | 18-AUG-05:03 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 5428.51 | 1439883.70 | 19-SEP-04:11 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 21814.21 | 1521347.06 | 11-OCT-04:01 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 95381.58 | 1867617.05 | 28-NOV-06:01 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 228266.37 | 2050482.29 | 04-DEC-06:01 |
Annual Sum or Average | 0.00 | 88307.66 | ||||
Minimum of Months | 0.00 | 0.00 | 9.28 | 10059.99 | ||
Maximum of Months | 0.00 | 0.00 | 357372.88 | 2138250.95 |
Report: PlantLoopDemandReportMonthly
For: COOLSYS1_SUPPLY
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 29.20 | 5033.40 | 25-JAN-10:40 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 3210.02 | 432515.78 | 27-FEB-15:30 | 0.00 | 0.00 | 01-FEB-00:05 |
March | 567.45 | 94270.74 | 14-MAR-13:30 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 26167.72 | 920492.44 | 06-APR-16:00 | 0.00 | 0.00 | 01-APR-00:10 |
May | 82289.60 | 1494152.87 | 19-MAY-15:30 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 279040.04 | 1671563.59 | 29-JUN-14:50 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 450799.64 | 1958274.67 | 17-JUL-15:30 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 394445.08 | 1920661.72 | 07-AUG-09:20 | 0.00 | 0.00 | 01-AUG-00:03 |
September | 184483.52 | 2896316.02 | 07-SEP-15:00 | 0.00 | 0.00 | 01-SEP-00:05 |
October | 44322.24 | 1567281.43 | 18-OCT-13:40 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 2651.95 | 212763.59 | 03-NOV-14:00 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 255.19 | 5277.04 | 28-DEC-00:33 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 123326.40 | 0.00 | ||||
Minimum of Months | 29.20 | 5033.40 | 0.00 | 0.00 | ||
Maximum of Months | 450799.64 | 2896316.02 | 0.00 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: COOLSYS1_DEMAND
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 17.01 | 24-JAN-05:11 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 2872.13 | 428889.63 | 27-FEB-15:30 | 0.00 | 0.00 | 01-FEB-00:05 |
March | 133.57 | 89789.35 | 14-MAR-13:30 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 25252.63 | 921422.88 | 06-APR-16:00 | 0.00 | 0.00 | 01-APR-00:10 |
May | 80785.67 | 1485901.24 | 19-MAY-15:30 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 274664.54 | 1663765.26 | 29-JUN-14:50 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 445025.93 | 1952136.00 | 17-JUL-15:30 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 387869.83 | 2024175.58 | 07-AUG-09:20 | 0.00 | 0.00 | 01-AUG-00:03 |
September | 181628.84 | 2702859.85 | 07-SEP-15:00 | 0.00 | 0.00 | 01-SEP-00:05 |
October | 43084.78 | 1275970.05 | 18-OCT-13:20 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 2137.50 | 208240.74 | 03-NOV-14:00 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 0.08 | 567.73 | 28-DEC-00:33 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 121246.08 | 0.00 | ||||
Minimum of Months | 0.00 | 17.01 | 0.00 | 0.00 | ||
Maximum of Months | 445025.93 | 2702859.85 | 0.00 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SINGLE WATER PLANT LOOP
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 13869.89 | 39733.81 | 13-JAN-16:30 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 49498.60 | 172318.16 | 27-FEB-16:00 | 0.00 | 0.00 | 01-FEB-00:05 |
March | 82265.32 | 110181.10 | 31-MAR-23:30 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 166238.63 | 1156364.30 | 07-APR-14:00 | 0.00 | 0.00 | 01-APR-00:10 |
May | 74231.07 | 989882.11 | 20-MAY-16:00 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 296393.79 | 1399626.97 | 29-JUN-15:00 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 707051.38 | 1987835.02 | 17-JUL-16:00 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 768815.98 | 2082790.46 | 05-AUG-16:00 | 0.00 | 0.00 | 01-AUG-00:03 |
September | 159964.43 | 1264560.89 | 02-SEP-17:00 | 0.00 | 0.00 | 01-SEP-00:05 |
October | 80970.24 | 863639.82 | 18-OCT-15:00 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 83026.07 | 223313.46 | 17-NOV-17:00 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 102015.30 | 186302.37 | 10-DEC-02:00 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 217151.90 | 0.00 | ||||
Minimum of Months | 13869.89 | 39733.81 | 0.00 | 0.00 | ||
Maximum of Months | 768815.98 | 2082790.46 | 0.00 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 17319.97 | 58842.16 | 31-JAN-12:50 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 17697.27 | 59153.14 | 14-FEB-12:50 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 18533.99 | 59067.02 | 01-MAR-12:20 |
April | 0.00 | 0.00 | 01-APR-00:10 | 16872.11 | 57468.27 | 03-APR-11:20 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 16515.05 | 54989.08 | 01-MAY-11:45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 15919.94 | 51669.30 | 01-JUN-11:30 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 14087.85 | 48632.98 | 03-JUL-12:00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 14975.18 | 46956.51 | 01-AUG-11:40 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 14302.73 | 48059.10 | 29-SEP-11:30 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 14888.01 | 50853.81 | 31-OCT-11:40 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 15937.13 | 54092.96 | 30-NOV-12:55 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 16262.03 | 56856.24 | 29-DEC-12:40 |
Annual Sum or Average | 0.00 | 16100.07 | ||||
Minimum of Months | 0.00 | 0.00 | 14087.85 | 46956.51 | ||
Maximum of Months | 0.00 | 0.00 | 18533.99 | 59153.14 |
Report: PlantLoopDemandReportMonthly
For: TOWERWATERSYS
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.64 | 6505.81 | 25-JAN-06:15 | 193.14 | 130376.09 | 25-JAN-10:40 |
February | 2944.00 | 510389.08 | 27-FEB-15:30 | 1971.61 | 152342.40 | 14-FEB-05:01 |
March | 74.43 | 78424.69 | 14-MAR-13:10 | 3647.26 | 156290.06 | 04-MAR-05:01 |
April | 28533.15 | 1049719.40 | 06-APR-16:00 | 3524.46 | 136059.22 | 28-APR-05:50 |
May | 98501.24 | 2409841.37 | 19-MAY-14:30 | 2553.88 | 146820.80 | 06-MAY-04:42 |
June | 354723.15 | 2760760.80 | 20-JUN-15:40 | 1073.96 | 98209.70 | 14-JUN-13:30 |
July | 585407.06 | 2857509.96 | 17-JUL-15:30 | 654.22 | 76171.27 | 29-JUL-07:20 |
August | 498869.94 | 2427070.71 | 30-AUG-14:40 | 1529.41 | 78898.82 | 03-AUG-08:20 |
September | 240289.25 | 4764385.16 | 07-SEP-15:00 | 2081.17 | 117838.80 | 18-SEP-14:40 |
October | 50693.02 | 2230800.52 | 18-OCT-13:25 | 2999.12 | 153018.03 | 10-OCT-03:01 |
November | 1818.55 | 272973.97 | 03-NOV-14:00 | 3407.81 | 152343.87 | 13-NOV-05:01 |
December | 15.52 | 9135.90 | 29-DEC-02:30 | 2091.51 | 142113.31 | 17-DEC-15:53 |
Annual Sum or Average | 156393.90 | 2141.24 | ||||
Minimum of Months | 0.64 | 6505.81 | 193.14 | 76171.27 | ||
Maximum of Months | 585407.06 | 4764385.16 | 3647.26 | 156290.06 |
Report: FanReportMonthly
For: CAV_BAS FAN
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.169075E+11 | 0.87 | 11488.25 | 01-JAN-00:05 | 1.58 |
February | 0.150723E+11 | 0.86 | 11488.25 | 01-FEB-06:03 | 1.59 |
March | 0.182976E+11 | 0.94 | 11488.25 | 01-MAR-04:03 | 1.58 |
April | 0.166235E+11 | 0.88 | 11488.25 | 01-APR-04:11 | 1.58 |
May | 0.179135E+11 | 0.92 | 11488.25 | 01-MAY-03:05 | 1.58 |
June | 0.175566E+11 | 0.93 | 11488.25 | 01-JUN-04:12 | 1.57 |
July | 0.180332E+11 | 0.92 | 11488.25 | 01-JUL-04:12 | 1.57 |
August | 0.192064E+11 | 0.98 | 11488.25 | 01-AUG-04:12 | 1.57 |
September | 0.179129E+11 | 0.95 | 11488.25 | 01-SEP-04:12 | 1.57 |
October | 0.177643E+11 | 0.91 | 11488.25 | 01-OCT-22:50 | 1.57 |
November | 0.169256E+11 | 0.90 | 11488.25 | 01-NOV-04:11 | 1.58 |
December | 0.167469E+11 | 0.86 | 11488.25 | 01-DEC-05:01 | 1.59 |
Annual Sum or Average | 0.208960E+12 | 0.91 | |||
Minimum of Months | 0.150723E+11 | 0.86 | 11488.25 | 1.57 | |
Maximum of Months | 0.192064E+11 | 0.98 | 11488.25 | 1.59 |
Report: FanReportMonthly
For: VAV_BOT WITH REHEAT FAN
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.438646E+10 | 0.38 | 16869.15 | 04-JAN-06:01 | 1.61 |
February | 0.489911E+10 | 0.40 | 16869.15 | 24-FEB-06:01 | 1.61 |
March | 0.722759E+10 | 0.46 | 16869.15 | 03-MAR-06:01 | 1.61 |
April | 0.909821E+10 | 0.51 | 21182.36 | 24-APR-14:50 | 1.84 |
May | 0.856492E+10 | 0.49 | 18095.32 | 19-MAY-15:20 | 1.66 |
June | 0.133429E+11 | 0.65 | 21386.73 | 29-JUN-14:30 | 1.85 |
July | 0.165048E+11 | 0.74 | 26466.43 | 17-JUL-15:00 | 2.11 |
August | 0.174860E+11 | 0.78 | 26466.43 | 07-AUG-10:20 | 2.12 |
September | 0.946832E+10 | 0.53 | 26466.43 | 05-SEP-04:12 | 2.12 |
October | 0.815085E+10 | 0.47 | 18556.64 | 16-OCT-15:50 | 1.70 |
November | 0.662822E+10 | 0.43 | 16869.15 | 13-NOV-06:01 | 1.61 |
December | 0.568093E+10 | 0.39 | 16869.15 | 01-DEC-06:01 | 1.61 |
Annual Sum or Average | 0.111438E+12 | 0.52 | |||
Minimum of Months | 0.438646E+10 | 0.38 | 16869.15 | 1.61 | |
Maximum of Months | 0.174860E+11 | 0.78 | 26466.43 | 2.12 |
Report: FanReportMonthly
For: VAV_MID WITH REHEAT FAN
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.437676E+11 | 0.43 | 72525.12 | 02-JAN-05:01 | 1.01 |
February | 0.385300E+11 | 0.40 | 86198.98 | 28-FEB-16:10 | 1.12 |
March | 0.482040E+11 | 0.41 | 123570.27 | 24-MAR-05:03 | 1.39 |
April | 0.520516E+11 | 0.40 | 143913.34 | 20-APR-05:02 | 1.52 |
May | 0.637400E+11 | 0.44 | 181050.48 | 19-MAY-15:30 | 1.74 |
June | 0.102027E+12 | 0.58 | 204331.30 | 29-JUN-14:30 | 1.89 |
July | 0.124742E+12 | 0.62 | 244852.15 | 17-JUL-15:30 | 2.11 |
August | 0.120460E+12 | 0.62 | 244852.15 | 10-AUG-15:40 | 2.12 |
September | 0.739176E+11 | 0.48 | 244852.15 | 05-SEP-04:12 | 2.12 |
October | 0.532459E+11 | 0.39 | 138946.11 | 27-OCT-05:02 | 1.49 |
November | 0.426892E+11 | 0.38 | 123442.37 | 04-NOV-05:02 | 1.38 |
December | 0.420256E+11 | 0.41 | 72525.12 | 04-DEC-06:01 | 1.01 |
Annual Sum or Average | 0.805401E+12 | 0.46 | |||
Minimum of Months | 0.385300E+11 | 0.38 | 72525.12 | 1.01 | |
Maximum of Months | 0.124742E+12 | 0.62 | 244852.15 | 2.12 |
Report: FanReportMonthly
For: VAV_TOP WITH REHEAT FAN
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.538050E+10 | 0.50 | 6364.07 | 02-JAN-04:01 | 0.88 |
February | 0.425532E+10 | 0.44 | 6364.07 | 01-FEB-05:11 | 0.88 |
March | 0.458644E+10 | 0.42 | 6904.04 | 28-MAR-15:50 | 0.92 |
April | 0.438980E+10 | 0.37 | 13235.98 | 25-APR-15:50 | 1.34 |
May | 0.571234E+10 | 0.41 | 18962.96 | 19-MAY-15:30 | 1.65 |
June | 0.935228E+10 | 0.52 | 21323.18 | 29-JUN-14:50 | 1.79 |
July | 0.117868E+11 | 0.56 | 27425.49 | 17-JUL-15:20 | 2.09 |
August | 0.109047E+11 | 0.54 | 27067.48 | 10-AUG-15:40 | 2.08 |
September | 0.628180E+10 | 0.43 | 20448.39 | 01-SEP-16:00 | 1.74 |
October | 0.427012E+10 | 0.36 | 11956.24 | 18-OCT-16:00 | 1.26 |
November | 0.418037E+10 | 0.40 | 6364.07 | 06-NOV-06:01 | 0.88 |
December | 0.488727E+10 | 0.46 | 6364.07 | 01-DEC-06:01 | 0.88 |
Annual Sum or Average | 0.759878E+11 | 0.45 | |||
Minimum of Months | 0.418037E+10 | 0.36 | 6364.07 | 0.88 | |
Maximum of Months | 0.117868E+11 | 0.56 | 27425.49 | 2.09 |
Report: FanReportMonthly
For: AIRLOOP DATACENTER BASEMENT SUPPLY FAN
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.108397E+12 | 1.54 | 40470.70 | 01-JAN-00:05 | 1.54 |
February | 0.979067E+11 | 1.54 | 40470.70 | 01-FEB-00:05 | 1.54 |
March | 0.108397E+12 | 1.55 | 40470.70 | 01-MAR-00:20 | 1.54 |
April | 0.104900E+12 | 1.55 | 40470.70 | 01-APR-00:10 | 1.55 |
May | 0.108397E+12 | 1.54 | 40470.70 | 01-MAY-00:10 | 1.54 |
June | 0.104900E+12 | 1.54 | 40470.70 | 01-JUN-00:10 | 1.54 |
July | 0.108397E+12 | 1.54 | 40470.70 | 01-JUL-00:10 | 1.53 |
August | 0.108397E+12 | 1.54 | 40470.70 | 01-AUG-00:03 | 1.54 |
September | 0.104900E+12 | 1.54 | 40470.70 | 01-SEP-00:05 | 1.54 |
October | 0.108397E+12 | 1.54 | 40470.70 | 01-OCT-00:30 | 1.54 |
November | 0.104900E+12 | 1.55 | 40470.70 | 01-NOV-00:10 | 1.55 |
December | 0.108397E+12 | 1.55 | 40470.70 | 01-DEC-00:10 | 1.55 |
Annual Sum or Average | 0.127628E+13 | 1.54 | |||
Minimum of Months | 0.979067E+11 | 1.54 | 40470.70 | 1.53 | |
Maximum of Months | 0.108397E+12 | 1.55 | 40470.70 | 1.55 |
Report: FanReportMonthly
For: AIRLOOP DATACENTER BOT SUPPLY FAN
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.175618E+10 | 1.05 | 655.68 | 01-JAN-00:10 | 1.05 |
February | 0.158623E+10 | 1.05 | 655.68 | 01-FEB-00:05 | 1.05 |
March | 0.175618E+10 | 1.05 | 655.68 | 01-MAR-00:10 | 1.05 |
April | 0.169953E+10 | 1.05 | 655.68 | 01-APR-00:10 | 1.05 |
May | 0.175618E+10 | 1.05 | 655.68 | 01-MAY-00:10 | 1.05 |
June | 0.169953E+10 | 1.05 | 655.68 | 01-JUN-00:10 | 1.05 |
July | 0.175618E+10 | 1.05 | 655.68 | 01-JUL-00:10 | 1.05 |
August | 0.175618E+10 | 1.05 | 655.68 | 01-AUG-00:03 | 1.05 |
September | 0.169953E+10 | 1.05 | 655.68 | 01-SEP-00:05 | 1.05 |
October | 0.175618E+10 | 1.05 | 655.68 | 01-OCT-00:10 | 1.05 |
November | 0.169953E+10 | 1.05 | 655.68 | 01-NOV-00:10 | 1.05 |
December | 0.175618E+10 | 1.05 | 655.68 | 01-DEC-00:10 | 1.05 |
Annual Sum or Average | 0.206776E+11 | 1.05 | |||
Minimum of Months | 0.158623E+10 | 1.05 | 655.68 | 1.05 | |
Maximum of Months | 0.175618E+10 | 1.05 | 655.68 | 1.05 |
Report: FanReportMonthly
For: AIRLOOP DATACENTER MID SUPPLY FAN
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.168896E+11 | 1.05 | 6305.84 | 01-JAN-00:05 | 1.04 |
February | 0.152551E+11 | 1.05 | 6305.84 | 01-FEB-00:05 | 1.05 |
March | 0.168896E+11 | 1.05 | 6305.84 | 01-MAR-00:10 | 1.05 |
April | 0.163447E+11 | 1.05 | 6305.84 | 01-APR-00:10 | 1.05 |
May | 0.168896E+11 | 1.05 | 6305.84 | 01-MAY-00:20 | 1.05 |
June | 0.163447E+11 | 1.05 | 6305.84 | 01-JUN-00:10 | 1.05 |
July | 0.168896E+11 | 1.05 | 6305.84 | 01-JUL-00:10 | 1.05 |
August | 0.168896E+11 | 1.05 | 6305.84 | 01-AUG-00:03 | 1.05 |
September | 0.163447E+11 | 1.05 | 6305.84 | 01-SEP-00:05 | 1.05 |
October | 0.168896E+11 | 1.05 | 6305.84 | 01-OCT-00:10 | 1.05 |
November | 0.163447E+11 | 1.05 | 6305.84 | 01-NOV-00:10 | 1.05 |
December | 0.168896E+11 | 1.05 | 6305.84 | 01-DEC-00:10 | 1.05 |
Annual Sum or Average | 0.198861E+12 | 1.05 | |||
Minimum of Months | 0.152551E+11 | 1.05 | 6305.84 | 1.04 | |
Maximum of Months | 0.168896E+11 | 1.05 | 6305.84 | 1.05 |
Report: FanReportMonthly
For: AIRLOOP DATACENTER TOP SUPPLY FAN
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.171738E+10 | 1.05 | 641.20 | 01-JAN-00:05 | 1.04 |
February | 0.155118E+10 | 1.05 | 641.20 | 01-FEB-00:05 | 1.05 |
March | 0.171738E+10 | 1.05 | 641.20 | 01-MAR-00:10 | 1.05 |
April | 0.166198E+10 | 1.05 | 641.20 | 01-APR-00:10 | 1.05 |
May | 0.171738E+10 | 1.05 | 641.20 | 01-MAY-00:10 | 1.05 |
June | 0.166198E+10 | 1.05 | 641.20 | 01-JUN-00:10 | 1.05 |
July | 0.171738E+10 | 1.05 | 641.20 | 01-JUL-00:10 | 1.05 |
August | 0.171738E+10 | 1.05 | 641.20 | 01-AUG-00:03 | 1.05 |
September | 0.166198E+10 | 1.05 | 641.20 | 01-SEP-00:05 | 1.05 |
October | 0.171738E+10 | 1.05 | 641.20 | 01-OCT-00:10 | 1.05 |
November | 0.166198E+10 | 1.05 | 641.20 | 01-NOV-00:10 | 1.05 |
December | 0.171738E+10 | 1.05 | 641.20 | 01-DEC-00:10 | 1.05 |
Annual Sum or Average | 0.202207E+11 | 1.05 | |||
Minimum of Months | 0.155118E+10 | 1.05 | 641.20 | 1.04 | |
Maximum of Months | 0.171738E+10 | 1.05 | 641.20 | 1.05 |
Report: PumpReportMonthly
For: HEATSYS1 PUMP
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.413992E+10 | 0.372593E+10 | 6662.84 | 09-JAN-07:02 | 5996.55 | 5996.55 | 47.49 | 13.58 |
February | 0.208727E+10 | 0.187854E+10 | 6560.06 | 06-FEB-06:01 | 5904.05 | 5904.05 | 45.52 | 12.95 |
March | 0.121297E+10 | 0.109168E+10 | 6570.14 | 06-MAR-06:02 | 5913.13 | 5913.13 | 48.64 | 12.99 |
April | 0.294524E+09 | 0.265072E+09 | 5371.44 | 29-APR-05:01 | 4834.30 | 4834.30 | 40.87 | 8.34 |
May | 0.211905E+09 | 0.190714E+09 | 5430.00 | 08-MAY-05:01 | 4887.00 | 4887.00 | 43.33 | 8.50 |
June | 6570375.36 | 5913337.83 | 1400.21 | 17-JUN-05:03 | 1260.19 | 1260.19 | 24.43 | 1.54 |
July | 97654.39 | 87888.95 | 39.46 | 08-JUL-05:03 | 35.52 | 35.52 | 22.31 | 0.04 |
August | 2225141.13 | 2002627.02 | 1396.43 | 18-AUG-05:03 | 1256.78 | 1256.78 | 23.96 | 1.53 |
September | 56214495.73 | 50593046.15 | 4388.63 | 19-SEP-04:11 | 3949.77 | 3949.77 | 25.26 | 6.07 |
October | 0.238423E+09 | 0.214581E+09 | 5330.61 | 10-OCT-05:01 | 4797.55 | 4797.55 | 41.66 | 8.23 |
November | 0.104621E+10 | 0.941591E+09 | 6562.28 | 27-NOV-06:01 | 5906.05 | 5906.05 | 48.35 | 12.95 |
December | 0.262590E+10 | 0.236331E+10 | 6566.03 | 30-DEC-06:01 | 5909.42 | 5909.42 | 47.88 | 12.97 |
Annual Sum or Average | 0.119222E+11 | 0.107300E+11 | ||||||
Minimum of Months | 97654.39 | 87888.95 | 39.46 | 35.52 | 35.52 | 22.31 | 0.04 | |
Maximum of Months | 0.413992E+10 | 0.372593E+10 | 6662.84 | 5996.55 | 5996.55 | 48.64 | 13.58 |
Report: PumpReportMonthly
For: COOLSYS1 PUMP SECONDARY
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 122.20 | 109.98 | 1.70 | 24-JAN-05:11 | 1.53 | 1.53 | 6.70 | 0.46 |
February | 1413707.61 | 1272336.85 | 108.93 | 27-FEB-14:00 | 98.03 | 98.03 | 6.70 | 9.91 |
March | 41241.00 | 37116.90 | 11.73 | 14-MAR-13:30 | 10.56 | 10.56 | 6.70 | 2.35 |
April | 12596644.28 | 11336979.86 | 263.52 | 06-APR-16:00 | 237.17 | 237.17 | 6.70 | 15.92 |
May | 83294236.68 | 74964813.01 | 2015.60 | 19-MAY-15:30 | 1814.04 | 1814.04 | 6.71 | 41.73 |
June | 0.394715E+09 | 0.355243E+09 | 3245.96 | 30-JUN-15:50 | 2921.36 | 2921.36 | 6.71 | 51.28 |
July | 0.886614E+09 | 0.797952E+09 | 4548.41 | 31-JUL-15:20 | 4093.57 | 4093.57 | 6.72 | 59.13 |
August | 0.797810E+09 | 0.718029E+09 | 4560.69 | 07-AUG-13:20 | 4104.62 | 4104.62 | 6.72 | 59.19 |
September | 0.314497E+09 | 0.283047E+09 | 4374.25 | 04-SEP-15:31 | 3936.83 | 3936.83 | 6.98 | 58.17 |
October | 27596720.66 | 24837048.60 | 581.90 | 18-OCT-13:20 | 523.71 | 523.71 | 7.43 | 23.59 |
November | 800792.24 | 720713.02 | 51.77 | 03-NOV-13:55 | 46.59 | 46.59 | 6.70 | 6.41 |
December | 19.93 | 17.93 | 0.05 | 28-DEC-00:33 | 0.05 | 0.05 | 6.70 | 0.02 |
Annual Sum or Average | 0.251938E+10 | 0.226744E+10 | ||||||
Minimum of Months | 19.93 | 17.93 | 0.05 | 0.05 | 0.05 | 6.70 | 0.02 | |
Maximum of Months | 0.886614E+09 | 0.797952E+09 | 4560.69 | 4104.62 | 4104.62 | 7.43 | 59.19 |
Report: PumpReportMonthly
For: COOLSYS1 CHILLER1 PUMP
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 87578216.81 | 78820395.13 | 5592.48 | 24-JAN-05:11 | 5033.23 | 5033.23 | 6.71 | 49.47 |
February | 0.912125E+09 | 0.820913E+09 | 5592.48 | 01-FEB-01:35 | 5033.23 | 5033.23 | 6.72 | 49.47 |
March | 0.129128E+10 | 0.116215E+10 | 5592.48 | 01-MAR-05:01 | 5033.23 | 5033.23 | 6.72 | 49.47 |
April | 0.268583E+10 | 0.241725E+10 | 5592.48 | 01-APR-12:13 | 5033.23 | 5033.23 | 6.72 | 49.47 |
May | 0.411496E+10 | 0.370347E+10 | 5592.48 | 01-MAY-12:10 | 5033.23 | 5033.23 | 6.72 | 49.47 |
June | 0.733271E+10 | 0.659944E+10 | 5592.48 | 01-JUN-04:12 | 5033.23 | 5033.23 | 7.65 | 49.47 |
July | 0.995112E+10 | 0.895601E+10 | 5592.48 | 01-JUL-00:12 | 5033.23 | 5033.23 | 6.84 | 49.47 |
August | 0.952771E+10 | 0.857494E+10 | 5592.48 | 01-AUG-00:23 | 5033.23 | 5033.23 | 6.82 | 49.47 |
September | 0.593182E+10 | 0.533864E+10 | 5592.48 | 01-SEP-00:42 | 5033.23 | 5033.23 | 6.79 | 49.47 |
October | 0.316485E+10 | 0.284836E+10 | 5592.48 | 02-OCT-05:05 | 5033.23 | 5033.23 | 7.47 | 49.47 |
November | 0.148274E+10 | 0.133447E+10 | 5592.48 | 01-NOV-04:11 | 5033.23 | 5033.23 | 6.81 | 49.47 |
December | 0.759195E+09 | 0.683275E+09 | 5592.48 | 01-DEC-05:43 | 5033.23 | 5033.23 | 6.72 | 49.47 |
Annual Sum or Average | 0.472419E+11 | 0.425177E+11 | ||||||
Minimum of Months | 87578216.81 | 78820395.13 | 5592.48 | 5033.23 | 5033.23 | 6.71 | 49.47 | |
Maximum of Months | 0.995112E+10 | 0.895601E+10 | 5592.48 | 5033.23 | 5033.23 | 7.65 | 49.47 |
Report: PumpReportMonthly
For: COOLSYS1 CHILLER2 PUMP
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 6.70 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 | 6.72 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 6.72 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 6.72 | 0.00 |
May | 0.147641E+09 | 0.132877E+09 | 5592.48 | 19-MAY-12:10 | 5033.23 | 5033.23 | 12.31 | 24.73 |
June | 0.153010E+10 | 0.137709E+10 | 5592.48 | 05-JUN-13:10 | 5033.23 | 5033.23 | 11.72 | 24.73 |
July | 0.289914E+10 | 0.260923E+10 | 5592.48 | 03-JUL-09:40 | 5033.23 | 5033.23 | 12.64 | 24.73 |
August | 0.250194E+10 | 0.225174E+10 | 5592.48 | 01-AUG-12:10 | 5033.23 | 5033.23 | 13.06 | 24.73 |
September | 0.731496E+09 | 0.658347E+09 | 5592.48 | 01-SEP-09:50 | 5033.23 | 5033.23 | 12.56 | 24.73 |
October | 68787488.30 | 61908739.47 | 5592.48 | 18-OCT-12:30 | 5033.23 | 5033.23 | 12.38 | 24.73 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 6.72 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 6.72 | 0.00 |
Annual Sum or Average | 0.787910E+10 | 0.709119E+10 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.70 | 0.00 | |
Maximum of Months | 0.289914E+10 | 0.260923E+10 | 5592.48 | 5033.23 | 5033.23 | 13.06 | 24.73 |
Report: PumpReportMonthly
For: PLANT CIRC PUMP
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.990025E+10 | 0.891023E+10 | 3696.33 | 01-JAN-00:05 | 3326.70 | 3326.70 | 18.54 | 15.44 |
February | 0.894216E+10 | 0.804795E+10 | 3696.33 | 01-FEB-00:05 | 3326.70 | 3326.70 | 19.02 | 15.44 |
March | 0.990025E+10 | 0.891023E+10 | 3696.33 | 01-MAR-00:10 | 3326.70 | 3326.70 | 19.90 | 15.44 |
April | 0.958089E+10 | 0.862280E+10 | 3696.33 | 01-APR-00:10 | 3326.70 | 3326.70 | 20.38 | 15.44 |
May | 0.990025E+10 | 0.891023E+10 | 3696.33 | 01-MAY-00:10 | 3326.70 | 3326.70 | 18.77 | 15.44 |
June | 0.958089E+10 | 0.862280E+10 | 3696.33 | 01-JUN-00:10 | 3326.70 | 3326.70 | 19.58 | 15.44 |
July | 0.990025E+10 | 0.891023E+10 | 3696.33 | 01-JUL-00:10 | 3326.70 | 3326.70 | 28.12 | 15.44 |
August | 0.990025E+10 | 0.891023E+10 | 3696.33 | 01-AUG-00:03 | 3326.70 | 3326.70 | 31.71 | 15.44 |
September | 0.958089E+10 | 0.862280E+10 | 3696.33 | 01-SEP-00:05 | 3326.70 | 3326.70 | 19.63 | 15.44 |
October | 0.990025E+10 | 0.891023E+10 | 3696.33 | 01-OCT-00:10 | 3326.70 | 3326.70 | 19.51 | 15.44 |
November | 0.958089E+10 | 0.862280E+10 | 3696.33 | 01-NOV-00:10 | 3326.70 | 3326.70 | 19.88 | 15.44 |
December | 0.990025E+10 | 0.891023E+10 | 3696.33 | 01-DEC-00:10 | 3326.70 | 3326.70 | 20.21 | 15.44 |
Annual Sum or Average | 0.116567E+12 | 0.104911E+12 | ||||||
Minimum of Months | 0.894216E+10 | 0.804795E+10 | 3696.33 | 3326.70 | 3326.70 | 18.54 | 15.44 | |
Maximum of Months | 0.990025E+10 | 0.891023E+10 | 3696.33 | 3326.70 | 3326.70 | 31.71 | 15.44 |
Report: PumpReportMonthly
For: SWHSYS1 PUMP
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.112905E+09 | 33871561.48 | 56.21 | 01-JAN-06:03 | 16.86 | 16.86 | 55.98 | 0.44 |
February | 0.101979E+09 | 30593668.43 | 56.21 | 01-FEB-06:03 | 16.86 | 16.86 | 55.56 | 0.44 |
March | 0.112905E+09 | 33871561.48 | 56.21 | 01-MAR-06:01 | 16.86 | 16.86 | 55.13 | 0.44 |
April | 0.109263E+09 | 32778930.46 | 56.21 | 01-APR-05:02 | 16.86 | 16.86 | 56.12 | 0.44 |
May | 0.112905E+09 | 33871561.48 | 56.21 | 01-MAY-05:03 | 16.86 | 16.86 | 56.23 | 0.44 |
June | 0.109263E+09 | 32778930.46 | 56.21 | 01-JUN-05:03 | 16.86 | 16.86 | 56.29 | 0.44 |
July | 0.112905E+09 | 33871561.48 | 56.21 | 01-JUL-05:03 | 16.86 | 16.86 | 56.84 | 0.44 |
August | 0.112905E+09 | 33871561.48 | 56.21 | 01-AUG-05:03 | 16.86 | 16.86 | 56.55 | 0.44 |
September | 0.109263E+09 | 32778930.46 | 56.21 | 01-SEP-05:02 | 16.86 | 16.86 | 55.72 | 0.44 |
October | 0.112905E+09 | 33871561.48 | 56.21 | 01-OCT-05:10 | 16.86 | 16.86 | 56.39 | 0.44 |
November | 0.109263E+09 | 32778930.46 | 56.21 | 01-NOV-05:03 | 16.86 | 16.86 | 55.96 | 0.44 |
December | 0.112905E+09 | 33871561.48 | 56.21 | 01-DEC-06:01 | 16.86 | 16.86 | 56.34 | 0.44 |
Annual Sum or Average | 0.132937E+10 | 0.398810E+09 | ||||||
Minimum of Months | 0.101979E+09 | 30593668.43 | 56.21 | 16.86 | 16.86 | 55.13 | 0.44 | |
Maximum of Months | 0.112905E+09 | 33871561.48 | 56.21 | 16.86 | 16.86 | 56.84 | 0.44 |
Report: PumpReportMonthly
For: TOWERWATERSYS PUMP
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.224752E+09 | 0.202277E+09 | 14353.64 | 25-JAN-06:15 | 12918.28 | 12918.28 | 21.13 | 58.17 |
February | 0.234111E+10 | 0.210700E+10 | 14375.05 | 27-FEB-15:30 | 12937.54 | 12937.54 | 23.20 | 58.17 |
March | 0.331371E+10 | 0.298234E+10 | 14356.69 | 14-MAR-13:10 | 12921.02 | 12921.02 | 21.42 | 58.17 |
April | 0.689606E+10 | 0.620646E+10 | 14398.74 | 06-APR-16:00 | 12958.86 | 12958.86 | 25.42 | 58.17 |
May | 0.108737E+11 | 0.978629E+10 | 28812.96 | 19-MAY-14:30 | 25931.67 | 25931.67 | 26.06 | 116.34 |
June | 0.220628E+11 | 0.198566E+11 | 28830.40 | 20-JUN-15:40 | 25947.36 | 25947.36 | 26.78 | 116.34 |
July | 0.320752E+11 | 0.288677E+11 | 28835.22 | 17-JUL-15:30 | 25951.69 | 25951.69 | 26.98 | 116.34 |
August | 0.301171E+11 | 0.271054E+11 | 28813.82 | 30-AUG-14:40 | 25932.44 | 25932.44 | 26.09 | 116.34 |
September | 0.168958E+11 | 0.152062E+11 | 28879.57 | 07-SEP-14:30 | 25991.62 | 25991.62 | 28.83 | 116.34 |
October | 0.827028E+10 | 0.744325E+10 | 28804.07 | 18-OCT-13:25 | 25923.66 | 25923.66 | 25.69 | 116.34 |
November | 0.380535E+10 | 0.342481E+10 | 14364.95 | 03-NOV-14:00 | 12928.46 | 12928.46 | 22.22 | 58.17 |
December | 0.194827E+10 | 0.175345E+10 | 14353.75 | 29-DEC-02:30 | 12918.38 | 12918.38 | 21.14 | 58.17 |
Annual Sum or Average | 0.138824E+12 | 0.124942E+12 | ||||||
Minimum of Months | 0.224752E+09 | 0.202277E+09 | 14353.64 | 12918.28 | 12918.28 | 21.13 | 58.17 | |
Maximum of Months | 0.320752E+11 | 0.288677E+11 | 28879.57 | 25991.62 | 25991.62 | 28.83 | 116.34 |
Report: CondLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 32.81 | 32.81 | 357372.88 | 2138250.95 | 23-JAN-05:11 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 32.40 | 82.00 | 200329.81 | 2081493.97 | 07-FEB-06:01 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 24.26 | 24.26 | 107069.79 | 1927328.50 | 06-MAR-05:01 |
April | 0.00 | 0.00 | 01-APR-00:10 | 25.68 | 25.68 | 27907.21 | 1629520.69 | 01-APR-04:11 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 22.93 | 82.00 | 18872.98 | 1654154.34 | 09-MAY-04:01 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 23.03 | 23.03 | 647.71 | 370308.82 | 17-JUN-05:03 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.41 | 22.41 | 9.28 | 10059.99 | 08-JUL-05:03 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 22.21 | 22.21 | 210.95 | 372323.64 | 18-AUG-05:03 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 22.47 | 22.47 | 5428.51 | 1439883.70 | 19-SEP-04:11 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 20.65 | 20.65 | 21814.21 | 1521347.06 | 11-OCT-04:01 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 25.54 | 25.54 | 95381.58 | 1867617.05 | 28-NOV-06:01 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 29.90 | 29.90 | 228266.37 | 2050482.29 | 04-DEC-06:01 |
Annual Sum or Average | 0.00 | 88307.66 | ||||||
Minimum of Months | 0.00 | 0.00 | 20.65 | 20.65 | 9.28 | 10059.99 | ||
Maximum of Months | 0.00 | 0.00 | 32.81 | 82.00 | 357372.88 | 2138250.95 |
Report: CondLoopDemandReportMonthly
For: COOLSYS1_SUPPLY
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 29.20 | 5033.40 | 25-JAN-10:40 | 6.72 | 6.70 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 3210.02 | 432515.78 | 27-FEB-15:30 | 8.79 | 6.70 | 0.00 | 0.00 | 01-FEB-00:05 |
March | 567.45 | 94270.74 | 14-MAR-13:30 | 7.15 | 6.70 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 26167.72 | 920492.44 | 06-APR-16:00 | 11.14 | 6.70 | 0.00 | 0.00 | 01-APR-00:10 |
May | 82289.60 | 1494152.87 | 19-MAY-15:30 | 10.30 | 6.70 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 279040.04 | 1671563.59 | 29-JUN-14:50 | 10.73 | 6.70 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 450799.64 | 1958274.67 | 17-JUL-15:30 | 11.42 | 6.70 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 394445.08 | 1920661.72 | 07-AUG-09:20 | 11.33 | 6.70 | 0.00 | 0.00 | 01-AUG-00:03 |
September | 184483.52 | 2896316.02 | 07-SEP-15:00 | 13.69 | 7.99 | 0.00 | 0.00 | 01-SEP-00:05 |
October | 44322.24 | 1567281.43 | 18-OCT-13:40 | 10.48 | 6.70 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 2651.95 | 212763.59 | 03-NOV-14:00 | 7.73 | 6.70 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 255.19 | 5277.04 | 28-DEC-00:33 | 6.73 | 6.70 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 123326.40 | 0.00 | ||||||
Minimum of Months | 29.20 | 5033.40 | 6.72 | 6.70 | 0.00 | 0.00 | ||
Maximum of Months | 450799.64 | 2896316.02 | 13.69 | 7.99 | 0.00 | 0.00 |
Report: CondLoopDemandReportMonthly
For: COOLSYS1_DEMAND
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 17.01 | 24-JAN-05:11 | 6.71 | 6.70 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 2872.13 | 428889.63 | 27-FEB-15:30 | 18.30 | 6.70 | 0.00 | 0.00 | 01-FEB-00:05 |
March | 133.57 | 89789.35 | 14-MAR-13:30 | 15.83 | 6.70 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 25252.63 | 921422.88 | 06-APR-16:00 | 20.55 | 6.70 | 0.00 | 0.00 | 01-APR-00:10 |
May | 80785.67 | 1485901.24 | 19-MAY-15:30 | 15.21 | 6.70 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 274664.54 | 1663765.26 | 29-JUN-14:50 | 22.28 | 6.70 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 445025.93 | 1952136.00 | 17-JUL-15:30 | 15.28 | 6.70 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 387869.83 | 2024175.58 | 07-AUG-09:20 | 15.96 | 6.70 | 0.00 | 0.00 | 01-AUG-00:03 |
September | 181628.84 | 2702859.85 | 07-SEP-15:00 | 18.76 | 7.94 | 0.00 | 0.00 | 01-SEP-00:05 |
October | 43084.78 | 1275970.05 | 18-OCT-13:20 | 19.63 | 7.07 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 2137.50 | 208240.74 | 03-NOV-14:00 | 14.53 | 6.70 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 0.08 | 567.73 | 28-DEC-00:33 | 15.50 | 6.70 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 121246.08 | 0.00 | ||||||
Minimum of Months | 0.00 | 17.01 | 6.71 | 6.70 | 0.00 | 0.00 | ||
Maximum of Months | 445025.93 | 2702859.85 | 22.28 | 7.94 | 0.00 | 0.00 |
Report: CondLoopDemandReportMonthly
For: SINGLE WATER PLANT LOOP
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 13869.89 | 39733.81 | 13-JAN-16:30 | 19.07 | 18.33 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 49498.60 | 172318.16 | 27-FEB-16:00 | 21.54 | 19.84 | 0.00 | 0.00 | 01-FEB-00:05 |
March | 82265.32 | 110181.10 | 31-MAR-23:30 | 20.39 | 18.33 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 166238.63 | 1156364.30 | 07-APR-14:00 | 39.53 | 29.19 | 0.00 | 0.00 | 01-APR-00:10 |
May | 74231.07 | 989882.11 | 20-MAY-16:00 | 36.53 | 32.36 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 296393.79 | 1399626.97 | 29-JUN-15:00 | 43.88 | 36.46 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 707051.38 | 1987835.02 | 17-JUL-16:00 | 54.27 | 43.48 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 768815.98 | 2082790.46 | 05-AUG-16:00 | 55.93 | 43.09 | 0.00 | 0.00 | 01-AUG-00:03 |
September | 159964.43 | 1264560.89 | 02-SEP-17:00 | 41.47 | 36.97 | 0.00 | 0.00 | 01-SEP-00:05 |
October | 80970.24 | 863639.82 | 18-OCT-15:00 | 34.24 | 28.34 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 83026.07 | 223313.46 | 17-NOV-17:00 | 22.49 | 19.09 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 102015.30 | 186302.37 | 10-DEC-02:00 | 21.80 | 18.33 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 217151.90 | 0.00 | ||||||
Minimum of Months | 13869.89 | 39733.81 | 19.07 | 18.33 | 0.00 | 0.00 | ||
Maximum of Months | 768815.98 | 2082790.46 | 55.93 | 43.48 | 0.00 | 0.00 |
Report: CondLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 57.44 | 57.44 | 17319.97 | 58842.16 | 31-JAN-12:50 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 56.30 | 56.30 | 17697.27 | 59153.14 | 14-FEB-12:50 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 55.68 | 55.68 | 18533.99 | 59067.02 | 01-MAR-12:20 |
April | 0.00 | 0.00 | 01-APR-00:10 | 56.58 | 56.58 | 16872.11 | 57468.27 | 03-APR-11:20 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 57.23 | 57.23 | 16515.05 | 54989.08 | 01-MAY-11:45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 56.50 | 56.50 | 15919.94 | 51669.30 | 01-JUN-11:30 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 57.39 | 57.39 | 14087.85 | 48632.98 | 03-JUL-12:00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 57.08 | 57.08 | 14975.18 | 46956.51 | 01-AUG-11:40 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 56.24 | 56.24 | 14302.73 | 48059.10 | 29-SEP-11:30 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 57.28 | 57.28 | 14888.01 | 50853.81 | 31-OCT-11:40 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 56.61 | 56.61 | 15937.13 | 54092.96 | 30-NOV-12:55 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 56.74 | 56.74 | 16262.03 | 56856.24 | 29-DEC-12:40 |
Annual Sum or Average | 0.00 | 16100.07 | ||||||
Minimum of Months | 0.00 | 0.00 | 55.68 | 55.68 | 14087.85 | 46956.51 | ||
Maximum of Months | 0.00 | 0.00 | 57.44 | 57.44 | 18533.99 | 59153.14 |
Report: CondLoopDemandReportMonthly
For: TOWERWATERSYS
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.64 | 6505.81 | 25-JAN-06:15 | 21.13 | 20.18 | 193.14 | 130376.09 | 25-JAN-10:40 |
February | 2944.00 | 510389.08 | 27-FEB-15:30 | 23.20 | 21.10 | 1971.61 | 152342.40 | 14-FEB-05:01 |
March | 74.43 | 78424.69 | 14-MAR-13:10 | 21.42 | 20.73 | 3647.26 | 156290.06 | 04-MAR-05:01 |
April | 28533.15 | 1049719.40 | 06-APR-16:00 | 25.42 | 21.10 | 3524.46 | 136059.22 | 28-APR-05:50 |
May | 98501.24 | 2409841.37 | 19-MAY-14:30 | 26.06 | 21.10 | 2553.88 | 146820.80 | 06-MAY-04:42 |
June | 354723.15 | 2760760.80 | 20-JUN-15:40 | 26.78 | 23.03 | 1073.96 | 98209.70 | 14-JUN-13:30 |
July | 585407.06 | 2857509.96 | 17-JUL-15:30 | 26.98 | 22.37 | 654.22 | 76171.27 | 29-JUL-07:20 |
August | 498869.94 | 2427070.71 | 30-AUG-14:40 | 26.09 | 21.10 | 1529.41 | 78898.82 | 03-AUG-08:20 |
September | 240289.25 | 4764385.16 | 07-SEP-15:00 | 30.90 | 25.37 | 2081.17 | 117838.80 | 18-SEP-14:40 |
October | 50693.02 | 2230800.52 | 18-OCT-13:25 | 25.69 | 21.10 | 2999.12 | 153018.03 | 10-OCT-03:01 |
November | 1818.55 | 272973.97 | 03-NOV-14:00 | 22.22 | 21.10 | 3407.81 | 152343.87 | 13-NOV-05:01 |
December | 15.52 | 9135.90 | 29-DEC-02:30 | 21.14 | 20.19 | 2091.51 | 142113.31 | 17-DEC-15:53 |
Annual Sum or Average | 156393.90 | 2141.24 | ||||||
Minimum of Months | 0.64 | 6505.81 | 21.13 | 20.18 | 193.14 | 76171.27 | ||
Maximum of Months | 585407.06 | 4764385.16 | 30.90 | 25.37 | 3647.26 | 156290.06 |
Report: ZoneTemperatureOscillationReportMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV_BOT WITH REHEAT
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.480626E+11 | 0.00 | 0.00 | 0.438646E+10 | 0.00 | 0.00 |
February | 0.217024E+11 | 0.00 | 0.736348E+09 | 0.489911E+10 | 0.00 | 0.00 |
March | 0.900859E+10 | 0.00 | 64191064.87 | 0.722759E+10 | 0.00 | 0.00 |
April | 0.109084E+10 | 0.00 | 0.713072E+10 | 0.909821E+10 | 0.00 | 0.00 |
May | 0.867442E+09 | 0.00 | 0.195332E+11 | 0.856492E+10 | 0.00 | 0.00 |
June | 6699089.73 | 0.00 | 0.638689E+11 | 0.133429E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.108592E+12 | 0.165048E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.991574E+11 | 0.174860E+11 | 0.00 | 0.00 |
September | 98457601.75 | 0.00 | 0.413584E+11 | 0.946832E+10 | 0.00 | 0.00 |
October | 0.874002E+09 | 0.00 | 0.112922E+11 | 0.815085E+10 | 0.00 | 0.00 |
November | 0.626075E+10 | 0.00 | 0.616459E+09 | 0.662822E+10 | 0.00 | 0.00 |
December | 0.226729E+11 | 0.00 | 0.00 | 0.568093E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.110645E+12 | 0.00 | 0.352350E+12 | 0.111438E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.438646E+10 | 0.00 | 0.00 |
Maximum of Months | 0.480626E+11 | 0.00 | 0.108592E+12 | 0.174860E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV_MID WITH REHEAT
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.798293E+12 | 0.00 | 31506.06 | 0.437676E+11 | 0.00 | 0.00 |
February | 0.405329E+12 | 0.00 | 0.582135E+10 | 0.385300E+11 | 0.00 | 0.00 |
March | 0.238738E+12 | 0.00 | 0.247060E+09 | 0.482040E+11 | 0.00 | 0.00 |
April | 0.583879E+11 | 0.00 | 0.511108E+11 | 0.520516E+11 | 0.00 | 0.00 |
May | 0.400773E+11 | 0.00 | 0.167845E+12 | 0.637400E+11 | 0.00 | 0.00 |
June | 0.103481E+10 | 0.00 | 0.544162E+12 | 0.102027E+12 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.910049E+12 | 0.124742E+12 | 0.00 | 0.00 |
August | 0.325248E+09 | 0.00 | 0.790119E+12 | 0.120460E+12 | 0.00 | 0.00 |
September | 0.105170E+11 | 0.00 | 0.364666E+12 | 0.739176E+11 | 0.00 | 0.00 |
October | 0.460793E+11 | 0.00 | 0.893588E+11 | 0.532459E+11 | 0.00 | 0.00 |
November | 0.204889E+12 | 0.00 | 0.448429E+10 | 0.426892E+11 | 0.00 | 0.00 |
December | 0.510963E+12 | 0.00 | 64277.76 | 0.420256E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.231463E+13 | 0.00 | 0.292786E+13 | 0.805401E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 31506.06 | 0.385300E+11 | 0.00 | 0.00 |
Maximum of Months | 0.798293E+12 | 0.00 | 0.910049E+12 | 0.124742E+12 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV_TOP WITH REHEAT
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.119127E+12 | 0.00 | 52824.02 | 0.538050E+10 | 0.00 | 0.00 |
February | 0.620237E+11 | 0.00 | 0.390482E+09 | 0.425532E+10 | 0.00 | 0.00 |
March | 0.415864E+11 | 0.00 | 2331981.52 | 0.458644E+10 | 0.00 | 0.00 |
April | 0.135185E+11 | 0.00 | 0.479342E+10 | 0.438980E+10 | 0.00 | 0.00 |
May | 0.100570E+11 | 0.00 | 0.173282E+11 | 0.571234E+10 | 0.00 | 0.00 |
June | 0.656607E+09 | 0.00 | 0.588673E+11 | 0.935228E+10 | 0.00 | 0.00 |
July | 26604971.68 | 0.00 | 0.988626E+11 | 0.117868E+11 | 0.00 | 0.00 |
August | 0.242664E+09 | 0.00 | 0.839504E+11 | 0.109047E+11 | 0.00 | 0.00 |
September | 0.359200E+10 | 0.00 | 0.370519E+11 | 0.628180E+10 | 0.00 | 0.00 |
October | 0.119535E+11 | 0.00 | 0.773586E+10 | 0.427012E+10 | 0.00 | 0.00 |
November | 0.382604E+11 | 0.00 | 0.331261E+09 | 0.418037E+10 | 0.00 | 0.00 |
December | 0.831558E+11 | 0.00 | 126715.88 | 0.488727E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.384201E+12 | 0.00 | 0.309314E+12 | 0.759878E+11 | 0.00 | 0.00 |
Minimum of Months | 26604971.68 | 0.00 | 52824.02 | 0.418037E+10 | 0.00 | 0.00 |
Maximum of Months | 0.119127E+12 | 0.00 | 0.988626E+11 | 0.117868E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: CAV_BAS
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.309488E+09 | 0.00 | 430925.51 | 0.169075E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.282169E+09 | 0.150723E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 36227.49 | 0.182976E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.252028E+10 | 0.166235E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.934050E+10 | 0.179135E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.331920E+11 | 0.175566E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.565008E+11 | 0.180332E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.517700E+11 | 0.192064E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.214620E+11 | 0.179129E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.593250E+10 | 0.177643E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 75754208.78 | 0.169256E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 22839.71 | 0.167469E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.309488E+09 | 0.00 | 0.181077E+12 | 0.208960E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 22839.71 | 0.150723E+11 | 0.00 | 0.00 |
Maximum of Months | 0.309488E+09 | 0.00 | 0.565008E+11 | 0.192064E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER BASEMENT
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.141405E+11 | 0.273874E+12 | 0.00 | 59.64 |
February | 0.00 | 0.00 | 0.199849E+11 | 0.337621E+12 | 0.00 | 86.79 |
March | 0.00 | 0.00 | 0.225640E+11 | 0.383712E+12 | 0.00 | 99.64 |
April | 0.00 | 0.00 | 0.102206E+12 | 0.390020E+12 | 0.00 | 95.99 |
May | 0.00 | 0.00 | 0.267735E+11 | 0.276811E+12 | 0.00 | 59.44 |
June | 0.00 | 0.00 | 0.186677E+12 | 0.293047E+12 | 0.00 | 51.45 |
July | 0.00 | 0.00 | 0.607444E+12 | 0.379819E+12 | 0.00 | 41.79 |
August | 0.00 | 0.00 | 0.767043E+12 | 0.528504E+12 | 0.00 | 82.94 |
September | 0.00 | 0.00 | 0.643832E+11 | 0.232630E+12 | 0.00 | 40.47 |
October | 0.00 | 0.00 | 0.352686E+11 | 0.365277E+12 | 0.00 | 91.65 |
November | 0.00 | 0.00 | 0.243952E+11 | 0.371926E+12 | 0.00 | 96.42 |
December | 0.00 | 0.00 | 0.249724E+11 | 0.384596E+12 | 0.00 | 99.64 |
Annual Sum or Average | 0.00 | 0.00 | 0.189585E+13 | 0.421784E+13 | 0.00 | 905.84 |
Minimum of Months | 0.00 | 0.00 | 0.141405E+11 | 0.232630E+12 | 0.00 | 40.47 |
Maximum of Months | 0.00 | 0.00 | 0.767043E+12 | 0.528504E+12 | 0.00 | 99.64 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER BOT
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.375130E+10 | 0.259419E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.104487E+11 | 0.376384E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.187195E+11 | 0.547835E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.249328E+11 | 0.648432E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.732277E+10 | 0.331243E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.141190E+11 | 0.471629E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.217739E+11 | 0.672410E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.278608E+11 | 0.789163E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.750625E+10 | 0.333550E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.133043E+11 | 0.443320E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.182558E+11 | 0.529395E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.242165E+11 | 0.649262E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.192212E+12 | 0.605204E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.375130E+10 | 0.259419E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.278608E+11 | 0.789163E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER MID
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.993674E+10 | 0.192567E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.749871E+11 | 0.311685E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.156101E+12 | 0.482971E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.223610E+12 | 0.595948E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.592914E+11 | 0.296290E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.129824E+12 | 0.442290E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.205327E+12 | 0.638683E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.262463E+12 | 0.748799E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.632980E+11 | 0.303036E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.110904E+12 | 0.394522E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.150437E+12 | 0.463543E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.197206E+12 | 0.561012E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.164339E+13 | 0.543135E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.993674E+10 | 0.192567E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.262463E+12 | 0.748799E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER TOP
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.401716E+09 | 0.181412E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.561021E+10 | 0.275800E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.137256E+11 | 0.450544E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.210309E+11 | 0.576107E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.511642E+10 | 0.282408E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.127108E+11 | 0.440635E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.204504E+11 | 0.641552E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.260772E+11 | 0.750352E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.565314E+10 | 0.292563E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.943667E+10 | 0.365977E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.128925E+11 | 0.426439E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.174332E+11 | 0.522407E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.150539E+12 | 0.520620E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.401716E+09 | 0.181412E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.260772E+11 | 0.750352E+10 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV_BOT WITH REHEAT
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.438646E+10 | 0.00 | 0.480626E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.489911E+10 | 0.736348E+09 | 0.217024E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.722759E+10 | 64191064.87 | 0.900859E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.909821E+10 | 0.713072E+10 | 0.109084E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.856492E+10 | 0.195332E+11 | 0.867442E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.133429E+11 | 0.638689E+11 | 6699089.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.165048E+11 | 0.108592E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.174860E+11 | 0.991574E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.946832E+10 | 0.413584E+11 | 98457601.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.815085E+10 | 0.112922E+11 | 0.874002E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.662822E+10 | 0.616459E+09 | 0.626075E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.568093E+10 | 0.00 | 0.226729E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.111438E+12 | 0.352350E+12 | 0.110645E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.438646E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.174860E+11 | 0.108592E+12 | 0.480626E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV_MID WITH REHEAT
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.437676E+11 | 31506.06 | 0.798293E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.385300E+11 | 0.582135E+10 | 0.405329E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.482040E+11 | 0.247060E+09 | 0.238738E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.520516E+11 | 0.511108E+11 | 0.583879E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.637400E+11 | 0.167845E+12 | 0.400773E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.102027E+12 | 0.544162E+12 | 0.103481E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.124742E+12 | 0.910049E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.120460E+12 | 0.790119E+12 | 0.325248E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.739176E+11 | 0.364666E+12 | 0.105170E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.532459E+11 | 0.893588E+11 | 0.460793E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.426892E+11 | 0.448429E+10 | 0.204889E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.420256E+11 | 64277.76 | 0.510963E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.805401E+12 | 0.292786E+13 | 0.231463E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.385300E+11 | 31506.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.124742E+12 | 0.910049E+12 | 0.798293E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV_TOP WITH REHEAT
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.538050E+10 | 52824.02 | 0.119127E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.425532E+10 | 0.390482E+09 | 0.620237E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.458644E+10 | 2331981.52 | 0.415864E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.438980E+10 | 0.479342E+10 | 0.135185E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.571234E+10 | 0.173282E+11 | 0.100570E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.935228E+10 | 0.588673E+11 | 0.656607E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.117868E+11 | 0.988626E+11 | 26604971.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.109047E+11 | 0.839504E+11 | 0.242664E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.628180E+10 | 0.370519E+11 | 0.359200E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.427012E+10 | 0.773586E+10 | 0.119535E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.418037E+10 | 0.331261E+09 | 0.382604E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.488727E+10 | 126715.88 | 0.831558E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.759878E+11 | 0.309314E+12 | 0.384201E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.418037E+10 | 52824.02 | 26604971.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.117868E+11 | 0.988626E+11 | 0.119127E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: CAV_BAS
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.169075E+11 | 430925.51 | 0.309488E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.150723E+11 | 0.282169E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.182976E+11 | 36227.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.166235E+11 | 0.252028E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.179135E+11 | 0.934050E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.175566E+11 | 0.331920E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.180332E+11 | 0.565008E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.192064E+11 | 0.517700E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.179129E+11 | 0.214620E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.177643E+11 | 0.593250E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.169256E+11 | 75754208.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.167469E+11 | 22839.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.208960E+12 | 0.181077E+12 | 0.309488E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.150723E+11 | 22839.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.192064E+11 | 0.565008E+11 | 0.309488E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER BASEMENT
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.108397E+12 | 0.897821E+10 | 0.00 | 0.00 | 0.00 | 0.159597E+12 | 0.00 | 0.00 |
February | 0.979067E+11 | 0.135760E+11 | 0.00 | 0.00 | 0.00 | 0.232260E+12 | 0.00 | 0.00 |
March | 0.108397E+12 | 0.150884E+11 | 0.00 | 0.00 | 0.00 | 0.266640E+12 | 0.00 | 0.00 |
April | 0.104900E+12 | 0.751158E+11 | 0.00 | 0.00 | 0.00 | 0.256873E+12 | 0.00 | 0.00 |
May | 0.108397E+12 | 0.181394E+11 | 0.00 | 0.00 | 0.00 | 0.159064E+12 | 0.00 | 0.00 |
June | 0.104900E+12 | 0.136834E+12 | 0.00 | 0.00 | 0.00 | 0.137683E+12 | 0.00 | 0.00 |
July | 0.108397E+12 | 0.448356E+12 | 0.00 | 0.00 | 0.00 | 0.111831E+12 | 0.00 | 0.00 |
August | 0.108397E+12 | 0.569901E+12 | 0.00 | 0.00 | 0.00 | 0.221966E+12 | 0.00 | 0.00 |
September | 0.104900E+12 | 0.454441E+11 | 0.00 | 0.00 | 0.00 | 0.108303E+12 | 0.00 | 0.00 |
October | 0.108397E+12 | 0.247462E+11 | 0.00 | 0.00 | 0.00 | 0.245254E+12 | 0.00 | 0.00 |
November | 0.104900E+12 | 0.165686E+11 | 0.00 | 0.00 | 0.00 | 0.258037E+12 | 0.00 | 0.00 |
December | 0.108397E+12 | 0.166132E+11 | 0.00 | 0.00 | 0.00 | 0.266640E+12 | 0.00 | 0.00 |
Annual Sum or Average | 0.127628E+13 | 0.138936E+13 | 0.00 | 0.00 | 0.00 | 0.242415E+13 | 0.00 | 0.00 |
Minimum of Months | 0.979067E+11 | 0.897821E+10 | 0.00 | 0.00 | 0.00 | 0.108303E+12 | 0.00 | 0.00 |
Maximum of Months | 0.108397E+12 | 0.569901E+12 | 0.00 | 0.00 | 0.00 | 0.266640E+12 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER BOT
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.175618E+10 | 0.291329E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.158623E+10 | 0.827107E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.175618E+10 | 0.149973E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.169953E+10 | 0.201480E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.175618E+10 | 0.576652E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.169953E+10 | 0.111022E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.175618E+10 | 0.168060E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.175618E+10 | 0.217253E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.169953E+10 | 0.587028E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.175618E+10 | 0.106273E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.169953E+10 | 0.146614E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.175618E+10 | 0.194801E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.206776E+11 | 0.152369E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.158623E+10 | 0.291329E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.175618E+10 | 0.217253E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER MID
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.168896E+11 | 0.756959E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.152551E+11 | 0.590737E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.168896E+11 | 0.124694E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.163447E+11 | 0.180360E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.168896E+11 | 0.465520E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.163447E+11 | 0.101940E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.168896E+11 | 0.158348E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.168896E+11 | 0.204472E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.163447E+11 | 0.493391E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.168896E+11 | 0.883410E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.163447E+11 | 0.120428E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.168896E+11 | 0.157995E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.198861E+12 | 0.129911E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.152551E+11 | 0.756959E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.168896E+11 | 0.204472E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER TOP
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.171738E+10 | 0.304978E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.155118E+10 | 0.440339E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.171738E+10 | 0.109375E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.166198E+10 | 0.169319E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.171738E+10 | 0.400971E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.166198E+10 | 0.996639E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.171738E+10 | 0.157522E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.171738E+10 | 0.202910E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.166198E+10 | 0.438949E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.171738E+10 | 0.749428E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.166198E+10 | 0.102901E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.171738E+10 | 0.139265E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.202207E+11 | 0.118697E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.155118E+10 | 0.304978E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.171738E+10 | 0.202910E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV_BOT WITH REHEAT
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.438646E+10 | 0.480626E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.489911E+10 | 0.217024E+11 | 0.736348E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.722759E+10 | 0.900859E+10 | 64191064.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.909821E+10 | 0.109084E+10 | 0.713072E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.856492E+10 | 0.867442E+09 | 0.195332E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.133429E+11 | 6699089.73 | 0.638689E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.165048E+11 | 0.00 | 0.108592E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.174860E+11 | 0.00 | 0.991574E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.946832E+10 | 98457601.75 | 0.413584E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.815085E+10 | 0.874002E+09 | 0.112922E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.662822E+10 | 0.626075E+10 | 0.616459E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.568093E+10 | 0.226729E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.111438E+12 | 0.110645E+12 | 0.352350E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.438646E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.174860E+11 | 0.480626E+11 | 0.108592E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV_MID WITH REHEAT
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.437676E+11 | 0.798293E+12 | 31506.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.385300E+11 | 0.405329E+12 | 0.582135E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.482040E+11 | 0.238738E+12 | 0.247060E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.520516E+11 | 0.583879E+11 | 0.511108E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.637400E+11 | 0.400773E+11 | 0.167845E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.102027E+12 | 0.103481E+10 | 0.544162E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.124742E+12 | 0.00 | 0.910049E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.120460E+12 | 0.325248E+09 | 0.790119E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.739176E+11 | 0.105170E+11 | 0.364666E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.532459E+11 | 0.460793E+11 | 0.893588E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.426892E+11 | 0.204889E+12 | 0.448429E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.420256E+11 | 0.510963E+12 | 64277.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.805401E+12 | 0.231463E+13 | 0.292786E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.385300E+11 | 0.00 | 31506.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.124742E+12 | 0.798293E+12 | 0.910049E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV_TOP WITH REHEAT
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.538050E+10 | 0.119127E+12 | 52824.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.425532E+10 | 0.620237E+11 | 0.390482E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.458644E+10 | 0.415864E+11 | 2331981.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.438980E+10 | 0.135185E+11 | 0.479342E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.571234E+10 | 0.100570E+11 | 0.173282E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.935228E+10 | 0.656607E+09 | 0.588673E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.117868E+11 | 26604971.68 | 0.988626E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.109047E+11 | 0.242664E+09 | 0.839504E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.628180E+10 | 0.359200E+10 | 0.370519E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.427012E+10 | 0.119535E+11 | 0.773586E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.418037E+10 | 0.382604E+11 | 0.331261E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.488727E+10 | 0.831558E+11 | 126715.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.759878E+11 | 0.384201E+12 | 0.309314E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.418037E+10 | 26604971.68 | 52824.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.117868E+11 | 0.119127E+12 | 0.988626E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: CAV_BAS
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.169075E+11 | 0.309488E+09 | 430925.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.150723E+11 | 0.00 | 0.282169E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.182976E+11 | 0.00 | 36227.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.166235E+11 | 0.00 | 0.252028E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.179135E+11 | 0.00 | 0.934050E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.175566E+11 | 0.00 | 0.331920E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.180332E+11 | 0.00 | 0.565008E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.192064E+11 | 0.00 | 0.517700E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.179129E+11 | 0.00 | 0.214620E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.177643E+11 | 0.00 | 0.593250E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.169256E+11 | 0.00 | 75754208.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.167469E+11 | 0.00 | 22839.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.208960E+12 | 0.309488E+09 | 0.181077E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.150723E+11 | 0.00 | 22839.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.192064E+11 | 0.309488E+09 | 0.565008E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER BASEMENT
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.108397E+12 | 0.00 | 0.141405E+11 | 0.00 | 0.516233E+10 | 0.00 | 0.00 | 0.00 | 0.160315E+12 | 0.00 | 0.00 | 0.00 |
February | 0.979067E+11 | 0.00 | 0.199849E+11 | 0.00 | 0.640890E+10 | 0.00 | 0.00 | 0.00 | 0.233306E+12 | 0.00 | 0.00 | 0.00 |
March | 0.108397E+12 | 0.00 | 0.225640E+11 | 0.00 | 0.747561E+10 | 0.00 | 0.00 | 0.00 | 0.267840E+12 | 0.00 | 0.00 | 0.00 |
April | 0.104900E+12 | 0.00 | 0.102206E+12 | 0.00 | 0.270907E+11 | 0.00 | 0.00 | 0.00 | 0.258029E+12 | 0.00 | 0.00 | 0.00 |
May | 0.108397E+12 | 0.00 | 0.267735E+11 | 0.00 | 0.863402E+10 | 0.00 | 0.00 | 0.00 | 0.159780E+12 | 0.00 | 0.00 | 0.00 |
June | 0.104900E+12 | 0.00 | 0.186677E+12 | 0.00 | 0.498434E+11 | 0.00 | 0.00 | 0.00 | 0.138303E+12 | 0.00 | 0.00 | 0.00 |
July | 0.108397E+12 | 0.00 | 0.607444E+12 | 0.00 | 0.159087E+12 | 0.00 | 0.00 | 0.00 | 0.112335E+12 | 0.00 | 0.00 | 0.00 |
August | 0.108397E+12 | 0.00 | 0.767043E+12 | 0.00 | 0.197142E+12 | 0.00 | 0.00 | 0.00 | 0.222965E+12 | 0.00 | 0.00 | 0.00 |
September | 0.104900E+12 | 0.00 | 0.643832E+11 | 0.00 | 0.189391E+11 | 0.00 | 0.00 | 0.00 | 0.108790E+12 | 0.00 | 0.00 | 0.00 |
October | 0.108397E+12 | 0.00 | 0.352686E+11 | 0.00 | 0.105224E+11 | 0.00 | 0.00 | 0.00 | 0.246358E+12 | 0.00 | 0.00 | 0.00 |
November | 0.104900E+12 | 0.00 | 0.243952E+11 | 0.00 | 0.782664E+10 | 0.00 | 0.00 | 0.00 | 0.259199E+12 | 0.00 | 0.00 | 0.00 |
December | 0.108397E+12 | 0.00 | 0.249724E+11 | 0.00 | 0.835927E+10 | 0.00 | 0.00 | 0.00 | 0.267840E+12 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.127628E+13 | 0.00 | 0.189585E+13 | 0.00 | 0.506492E+12 | 0.00 | 0.00 | 0.00 | 0.243506E+13 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.979067E+11 | 0.00 | 0.141405E+11 | 0.00 | 0.516233E+10 | 0.00 | 0.00 | 0.00 | 0.108790E+12 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.108397E+12 | 0.00 | 0.767043E+12 | 0.00 | 0.197142E+12 | 0.00 | 0.00 | 0.00 | 0.267840E+12 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER BOT
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.175618E+10 | 0.00 | 0.375130E+10 | 0.00 | 0.838011E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.158623E+10 | 0.00 | 0.104487E+11 | 0.00 | 0.217761E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.175618E+10 | 0.00 | 0.187195E+11 | 0.00 | 0.372217E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.169953E+10 | 0.00 | 0.249328E+11 | 0.00 | 0.478479E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.175618E+10 | 0.00 | 0.732277E+10 | 0.00 | 0.155625E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.169953E+10 | 0.00 | 0.141190E+11 | 0.00 | 0.301676E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.175618E+10 | 0.00 | 0.217739E+11 | 0.00 | 0.496792E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.175618E+10 | 0.00 | 0.278608E+11 | 0.00 | 0.613545E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.169953E+10 | 0.00 | 0.750625E+10 | 0.00 | 0.163597E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.175618E+10 | 0.00 | 0.133043E+11 | 0.00 | 0.267702E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.169953E+10 | 0.00 | 0.182558E+11 | 0.00 | 0.359442E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.175618E+10 | 0.00 | 0.242165E+11 | 0.00 | 0.473644E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.206776E+11 | 0.00 | 0.192212E+12 | 0.00 | 0.398428E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.158623E+10 | 0.00 | 0.375130E+10 | 0.00 | 0.838011E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.175618E+10 | 0.00 | 0.278608E+11 | 0.00 | 0.613545E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER MID
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.168896E+11 | 0.00 | 0.993674E+10 | 0.00 | 0.236715E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.152551E+11 | 0.00 | 0.749871E+11 | 0.00 | 0.159134E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.168896E+11 | 0.00 | 0.156101E+12 | 0.00 | 0.314076E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.163447E+11 | 0.00 | 0.223610E+12 | 0.00 | 0.432501E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.168896E+11 | 0.00 | 0.592914E+11 | 0.00 | 0.127395E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.163447E+11 | 0.00 | 0.129824E+12 | 0.00 | 0.278842E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.168896E+11 | 0.00 | 0.205327E+12 | 0.00 | 0.469787E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.168896E+11 | 0.00 | 0.262463E+12 | 0.00 | 0.579903E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.163447E+11 | 0.00 | 0.632980E+11 | 0.00 | 0.139589E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.168896E+11 | 0.00 | 0.110904E+12 | 0.00 | 0.225627E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.163447E+11 | 0.00 | 0.150437E+12 | 0.00 | 0.300096E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.168896E+11 | 0.00 | 0.197206E+12 | 0.00 | 0.392116E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.198861E+12 | 0.00 | 0.164339E+13 | 0.00 | 0.344274E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.152551E+11 | 0.00 | 0.993674E+10 | 0.00 | 0.236715E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.168896E+11 | 0.00 | 0.262463E+12 | 0.00 | 0.579903E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER TOP
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.171738E+10 | 0.00 | 0.401716E+09 | 0.00 | 96738080.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.155118E+10 | 0.00 | 0.561021E+10 | 0.00 | 0.120682E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.171738E+10 | 0.00 | 0.137256E+11 | 0.00 | 0.278806E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.166198E+10 | 0.00 | 0.210309E+11 | 0.00 | 0.409909E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.171738E+10 | 0.00 | 0.511642E+10 | 0.00 | 0.110670E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.166198E+10 | 0.00 | 0.127108E+11 | 0.00 | 0.274438E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.171738E+10 | 0.00 | 0.204504E+11 | 0.00 | 0.469814E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.171738E+10 | 0.00 | 0.260772E+11 | 0.00 | 0.578615E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.166198E+10 | 0.00 | 0.565314E+10 | 0.00 | 0.126365E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.171738E+10 | 0.00 | 0.943667E+10 | 0.00 | 0.194239E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.166198E+10 | 0.00 | 0.128925E+11 | 0.00 | 0.260241E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.171738E+10 | 0.00 | 0.174332E+11 | 0.00 | 0.350670E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.202207E+11 | 0.00 | 0.150539E+12 | 0.00 | 0.318412E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.155118E+10 | 0.00 | 0.401716E+09 | 0.00 | 96738080.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.171738E+10 | 0.00 | 0.260772E+11 | 0.00 | 0.578615E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.242628E+11 | 0.00 | 0.00 | 68328450.88 | 0.00 | 0.00 | 0.474001E+11 | 0.00 | 0.44 |
February | 0.762923E+10 | 0.00 | 0.00 | 86246460.74 | 0.00 | 0.00 | 0.570366E+11 | 0.00 | 0.57 |
March | 0.259465E+10 | 0.00 | 0.00 | 0.123857E+09 | 0.00 | 0.00 | 0.779824E+11 | 0.00 | 0.71 |
April | 0.314953E+09 | 0.00 | 0.00 | 0.121134E+09 | 0.00 | 0.00 | 0.736489E+11 | 0.00 | 0.99 |
May | 0.176535E+09 | 42293098.00 | 0.00 | 0.120844E+09 | 6069632.46 | 0.00 | 0.714017E+11 | 0.00 | 1.20 |
June | 0.106828E+09 | 0.380351E+09 | 0.00 | 0.111142E+09 | 300251.34 | 0.00 | 0.524142E+11 | 0.00 | 1.39 |
July | 0.156183E+09 | 0.131700E+10 | 0.00 | 0.108026E+09 | 31552912.32 | 0.00 | 0.325710E+11 | 0.00 | 1.18 |
August | 0.111076E+09 | 0.929872E+09 | 0.00 | 0.125653E+09 | 50281458.78 | 0.00 | 0.452840E+11 | 0.00 | 1.41 |
September | 0.191764E+09 | 0.362785E+09 | 0.00 | 0.124020E+09 | 37479593.69 | 0.00 | 0.631325E+11 | 0.00 | 1.38 |
October | 0.399806E+09 | 0.00 | 0.00 | 0.138812E+09 | 0.00 | 0.00 | 0.790109E+11 | 0.00 | 1.15 |
November | 0.332586E+09 | 0.00 | 0.00 | 0.133867E+09 | 0.00 | 0.00 | 0.791548E+11 | 0.00 | 0.84 |
December | 0.574166E+10 | 0.00 | 0.00 | 0.116233E+09 | 0.00 | 0.00 | 0.708303E+11 | 0.00 | 0.56 |
Annual Sum or Average | 0.420181E+11 | 0.303230E+10 | 0.00 | 0.137816E+10 | 0.125684E+09 | 0.00 | 0.749867E+12 | 0.00 | 0.99 |
Minimum of Months | 0.106828E+09 | 0.00 | 0.00 | 68328450.88 | 0.00 | 0.00 | 0.325710E+11 | 0.00 | 0.44 |
Maximum of Months | 0.242628E+11 | 0.131700E+10 | 0.00 | 0.138812E+09 | 50281458.78 | 0.00 | 0.791548E+11 | 0.00 | 1.41 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.204308E+11 | 0.00 | 0.00 | 39710581.72 | 0.00 | 0.00 | 0.368245E+11 | 0.00 | 0.33 |
February | 0.801043E+10 | 0.00 | 0.00 | 61540079.66 | 0.00 | 0.00 | 0.432601E+11 | 0.00 | 0.44 |
March | 0.337450E+10 | 0.00 | 0.00 | 97440921.09 | 0.00 | 0.00 | 0.601290E+11 | 0.00 | 0.55 |
April | 0.356542E+10 | 0.00 | 0.00 | 0.103587E+09 | 0.00 | 0.00 | 0.587627E+11 | 0.00 | 0.79 |
May | 0.238517E+10 | 16443182.28 | 0.00 | 91332120.29 | 7690058.98 | 0.00 | 0.502932E+11 | 0.00 | 0.81 |
June | 0.330102E+10 | 0.212281E+09 | 0.00 | 97387895.69 | 15039556.30 | 0.00 | 0.403504E+11 | 0.00 | 1.05 |
July | 0.539208E+10 | 0.561790E+09 | 0.00 | 87894514.90 | 58037428.51 | 0.00 | 0.230865E+11 | 0.00 | 0.95 |
August | 0.684564E+10 | 0.399691E+09 | 0.00 | 0.107493E+09 | 48738978.96 | 0.00 | 0.347577E+11 | 0.00 | 1.15 |
September | 0.214868E+10 | 0.390291E+09 | 0.00 | 90363303.30 | 36221782.49 | 0.00 | 0.426602E+11 | 0.00 | 0.90 |
October | 0.230804E+10 | 0.00 | 0.00 | 0.100861E+09 | 0.00 | 0.00 | 0.548549E+11 | 0.00 | 0.79 |
November | 0.228404E+10 | 0.00 | 0.00 | 90951686.42 | 0.00 | 0.00 | 0.561441E+11 | 0.00 | 0.60 |
December | 0.431182E+10 | 0.00 | 0.00 | 80221576.72 | 0.00 | 0.00 | 0.569396E+11 | 0.00 | 0.43 |
Annual Sum or Average | 0.643576E+11 | 0.158050E+10 | 0.00 | 0.104878E+10 | 0.165728E+09 | 0.00 | 0.558063E+12 | 0.00 | 0.73 |
Minimum of Months | 0.214868E+10 | 0.00 | 0.00 | 39710581.72 | 0.00 | 0.00 | 0.230865E+11 | 0.00 | 0.33 |
Maximum of Months | 0.204308E+11 | 0.561790E+09 | 0.00 | 0.107493E+09 | 58037428.51 | 0.00 | 0.601290E+11 | 0.00 | 1.15 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.403951E+12 | 0.00 | 0.00 | 31080698.44 | 0.00 | 0.822573E+10 | 0.645630E+11 | 0.00 | 0.28 |
February | 0.261716E+12 | 0.00 | 0.00 | 0.134317E+09 | 0.00 | 0.117258E+10 | 0.122996E+12 | 0.00 | 0.32 |
March | 0.185557E+12 | 0.00 | 0.00 | 0.329036E+09 | 0.00 | 0.177321E+10 | 0.253493E+12 | 0.00 | 0.38 |
April | 0.814328E+11 | 0.00 | 0.00 | 0.466602E+09 | 0.00 | 0.00 | 0.315782E+12 | 0.00 | 0.52 |
May | 0.529817E+11 | 0.181732E+09 | 0.00 | 0.555843E+09 | 88219000.22 | 0.00 | 0.338745E+12 | 0.00 | 0.63 |
June | 0.247879E+11 | 0.224672E+10 | 0.00 | 0.709603E+09 | 99438370.68 | 0.00 | 0.304364E+12 | 0.00 | 0.82 |
July | 0.213963E+11 | 0.607385E+10 | 0.00 | 0.654080E+09 | 0.284846E+09 | 0.00 | 0.168697E+12 | 0.00 | 0.69 |
August | 0.186404E+11 | 0.421588E+10 | 0.00 | 0.775880E+09 | 0.482626E+09 | 0.00 | 0.251521E+12 | 0.00 | 0.80 |
September | 0.289099E+11 | 0.370361E+10 | 0.00 | 0.615299E+09 | 0.373769E+09 | 0.00 | 0.308090E+12 | 0.00 | 0.70 |
October | 0.694884E+11 | 0.00 | 0.00 | 0.504522E+09 | 0.00 | 0.00 | 0.317065E+12 | 0.00 | 0.56 |
November | 0.171640E+12 | 0.00 | 0.00 | 0.292157E+09 | 0.00 | 0.577217E+09 | 0.211323E+12 | 0.00 | 0.40 |
December | 0.303651E+12 | 0.00 | 0.00 | 0.133736E+09 | 0.00 | 0.225171E+10 | 0.126275E+12 | 0.00 | 0.30 |
Annual Sum or Average | 0.162415E+13 | 0.164218E+11 | 0.00 | 0.520215E+10 | 0.132890E+10 | 0.140005E+11 | 0.278291E+13 | 0.00 | 0.53 |
Minimum of Months | 0.186404E+11 | 0.00 | 0.00 | 31080698.44 | 0.00 | 0.00 | 0.645630E+11 | 0.00 | 0.28 |
Maximum of Months | 0.403951E+12 | 0.607385E+10 | 0.00 | 0.775880E+09 | 0.482626E+09 | 0.822573E+10 | 0.338745E+12 | 0.00 | 0.82 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.313572E+11 | 0.00 | 0.00 | 67742.10 | 0.00 | 0.925589E+10 | 0.133352E+09 | 0.00 | 0.26 |
February | 0.280191E+11 | 0.00 | 0.00 | 1582299.46 | 0.00 | 0.322267E+10 | 0.206292E+10 | 0.00 | 0.30 |
March | 0.250375E+11 | 0.00 | 0.00 | 8630451.09 | 0.00 | 0.209828E+10 | 0.899843E+10 | 0.00 | 0.32 |
April | 0.152056E+11 | 0.00 | 0.00 | 22244139.00 | 0.00 | 82095570.93 | 0.177166E+11 | 0.00 | 0.45 |
May | 0.106512E+11 | 10393691.53 | 0.00 | 37436203.10 | 5797241.03 | 0.281691E+09 | 0.245979E+11 | 0.00 | 0.59 |
June | 0.470913E+10 | 0.131435E+09 | 0.00 | 62874636.24 | 13476320.29 | 0.00 | 0.262007E+11 | 0.00 | 0.83 |
July | 0.307293E+10 | 0.408109E+09 | 0.00 | 61636673.51 | 24201817.52 | 0.00 | 0.147089E+11 | 0.00 | 0.70 |
August | 0.331901E+10 | 0.266902E+09 | 0.00 | 69574148.64 | 40662045.35 | 0.00 | 0.206318E+11 | 0.00 | 0.77 |
September | 0.746551E+10 | 0.334213E+09 | 0.00 | 40858645.43 | 29639576.22 | 1337623.30 | 0.205358E+11 | 0.00 | 0.64 |
October | 0.154488E+11 | 0.00 | 0.00 | 20080317.38 | 0.00 | 0.183095E+09 | 0.143743E+11 | 0.00 | 0.46 |
November | 0.223664E+11 | 0.00 | 0.00 | 6170690.33 | 0.00 | 0.162420E+10 | 0.589743E+10 | 0.00 | 0.33 |
December | 0.294053E+11 | 0.00 | 0.00 | 1353324.57 | 0.00 | 0.473226E+10 | 0.158872E+10 | 0.00 | 0.27 |
Annual Sum or Average | 0.196058E+12 | 0.115105E+10 | 0.00 | 0.332509E+09 | 0.113777E+09 | 0.214815E+11 | 0.157447E+12 | 0.00 | 0.49 |
Minimum of Months | 0.307293E+10 | 0.00 | 0.00 | 67742.10 | 0.00 | 0.00 | 0.133352E+09 | 0.00 | 0.26 |
Maximum of Months | 0.313572E+11 | 0.408109E+09 | 0.00 | 69574148.64 | 40662045.35 | 0.925589E+10 | 0.262007E+11 | 0.00 | 0.83 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.230874E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.390308E+10 | 0.00 | 0.00 | 0.27 |
February | 0.302383E+10 | 0.00 | 0.00 | 300755.94 | 0.00 | 0.141369E+10 | 0.223453E+09 | 0.00 | 0.31 |
March | 0.330751E+10 | 0.00 | 0.00 | 1666700.54 | 0.00 | 0.368131E+09 | 0.143696E+10 | 0.00 | 0.35 |
April | 0.221574E+10 | 0.00 | 0.00 | 4756899.88 | 0.00 | 1053427.14 | 0.324423E+10 | 0.00 | 0.60 |
May | 0.143231E+10 | 5077684.08 | 0.00 | 6790426.87 | 963647.00 | 6855163.28 | 0.392744E+10 | 0.00 | 0.75 |
June | 0.696791E+09 | 40522279.14 | 0.00 | 12168412.93 | 1875072.30 | 0.00 | 0.482634E+10 | 0.00 | 1.19 |
July | 0.776812E+09 | 0.125645E+09 | 0.00 | 12156776.99 | 7272713.24 | 0.00 | 0.294859E+10 | 0.00 | 1.10 |
August | 0.110147E+10 | 88520321.93 | 0.00 | 12013611.27 | 6107517.63 | 0.00 | 0.362696E+10 | 0.00 | 1.19 |
September | 0.133458E+10 | 70621974.19 | 0.00 | 6153094.05 | 4538978.45 | 0.00 | 0.288365E+10 | 0.00 | 0.76 |
October | 0.236535E+10 | 0.00 | 0.00 | 3501563.12 | 0.00 | 0.00 | 0.229336E+10 | 0.00 | 0.54 |
November | 0.324666E+10 | 0.00 | 0.00 | 1100811.65 | 0.00 | 0.182939E+09 | 0.986479E+09 | 0.00 | 0.36 |
December | 0.337889E+10 | 0.00 | 0.00 | 145886.07 | 0.00 | 0.132290E+10 | 0.214413E+09 | 0.00 | 0.26 |
Annual Sum or Average | 0.251887E+11 | 0.330387E+09 | 0.00 | 60754939.30 | 20757928.61 | 0.719865E+10 | 0.266119E+11 | 0.00 | 0.64 |
Minimum of Months | 0.696791E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.26 |
Maximum of Months | 0.337889E+10 | 0.125645E+09 | 0.00 | 12168412.93 | 7272713.24 | 0.390308E+10 | 0.482634E+10 | 0.00 | 1.19 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.332696E+10 | 0.00 | 0.00 | 54166.28 | 0.00 | 0.416560E+10 | 60841149.08 | 0.00 | 0.52 |
February | 0.370797E+10 | 0.00 | 0.00 | 1319422.05 | 0.00 | 0.158023E+10 | 0.806118E+09 | 0.00 | 0.63 |
March | 0.400966E+10 | 0.00 | 0.00 | 3860806.50 | 0.00 | 0.566904E+09 | 0.238249E+10 | 0.00 | 0.72 |
April | 0.302371E+10 | 0.00 | 0.00 | 7286841.02 | 0.00 | 15368425.99 | 0.428459E+10 | 0.00 | 1.17 |
May | 0.200724E+10 | 3503758.11 | 0.00 | 8928721.58 | 1226660.06 | 15175414.45 | 0.525440E+10 | 0.00 | 1.44 |
June | 0.109425E+10 | 34001771.36 | 0.00 | 15973650.28 | 2398996.30 | 0.00 | 0.563119E+10 | 0.00 | 2.15 |
July | 0.107908E+10 | 94516713.53 | 0.00 | 18110159.21 | 9257691.77 | 0.00 | 0.395302E+10 | 0.00 | 2.15 |
August | 0.174405E+10 | 76194524.99 | 0.00 | 12758018.51 | 7488012.10 | 0.00 | 0.436245E+10 | 0.00 | 2.19 |
September | 0.186222E+10 | 56310558.52 | 0.00 | 8345113.29 | 5701892.02 | 0.00 | 0.371946E+10 | 0.00 | 1.46 |
October | 0.297176E+10 | 0.00 | 0.00 | 5039382.27 | 0.00 | 2396808.59 | 0.292568E+10 | 0.00 | 1.02 |
November | 0.400396E+10 | 0.00 | 0.00 | 1115950.38 | 0.00 | 0.431165E+09 | 0.111538E+10 | 0.00 | 0.68 |
December | 0.406085E+10 | 0.00 | 0.00 | 145714.75 | 0.00 | 0.205499E+10 | 0.135090E+09 | 0.00 | 0.52 |
Annual Sum or Average | 0.328917E+11 | 0.264527E+09 | 0.00 | 82937946.11 | 26073252.26 | 0.883183E+10 | 0.346307E+11 | 0.00 | 1.22 |
Minimum of Months | 0.107908E+10 | 0.00 | 0.00 | 54166.28 | 0.00 | 0.00 | 60841149.08 | 0.00 | 0.52 |
Maximum of Months | 0.406085E+10 | 94516713.53 | 0.00 | 18110159.21 | 9257691.77 | 0.416560E+10 | 0.563119E+10 | 0.00 | 2.19 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.365166E+10 | 0.00 | 0.00 | 4703655.52 | 0.00 | 0.426354E+10 | 0.336817E+10 | 0.00 | 0.52 |
February | 0.334113E+10 | 0.00 | 0.00 | 11831396.23 | 0.00 | 0.156402E+10 | 0.597716E+10 | 0.00 | 0.83 |
March | 0.406222E+10 | 0.00 | 0.00 | 12567619.76 | 0.00 | 0.626781E+09 | 0.805168E+10 | 0.00 | 0.95 |
April | 0.338627E+10 | 0.00 | 0.00 | 12778960.28 | 0.00 | 54602723.21 | 0.734062E+10 | 0.00 | 1.24 |
May | 0.262915E+10 | 7205407.25 | 0.00 | 11480578.96 | 1518210.74 | 0.110643E+09 | 0.630141E+10 | 0.00 | 1.27 |
June | 0.169896E+10 | 61072050.48 | 0.00 | 15342236.83 | 2954147.02 | 0.00 | 0.533698E+10 | 0.00 | 1.56 |
July | 0.150953E+10 | 0.187970E+09 | 0.00 | 16399192.46 | 9888942.24 | 0.00 | 0.327898E+10 | 0.00 | 1.49 |
August | 0.207457E+10 | 0.177484E+09 | 0.00 | 19818067.76 | 6951720.87 | 0.00 | 0.507669E+10 | 0.00 | 1.93 |
September | 0.199488E+10 | 0.192599E+09 | 0.00 | 17476101.98 | 2144475.30 | 669280.39 | 0.680686E+10 | 0.00 | 1.72 |
October | 0.263220E+10 | 0.00 | 0.00 | 20092152.27 | 0.00 | 50207458.29 | 0.933927E+10 | 0.00 | 1.51 |
November | 0.340564E+10 | 0.00 | 0.00 | 11497239.16 | 0.00 | 0.505456E+09 | 0.709579E+10 | 0.00 | 0.92 |
December | 0.396278E+10 | 0.00 | 0.00 | 5986202.70 | 0.00 | 0.192995E+10 | 0.423242E+10 | 0.00 | 0.58 |
Annual Sum or Average | 0.343490E+11 | 0.626330E+09 | 0.00 | 0.159973E+09 | 23457496.18 | 0.910586E+10 | 0.722060E+11 | 0.00 | 1.21 |
Minimum of Months | 0.150953E+10 | 0.00 | 0.00 | 4703655.52 | 0.00 | 0.00 | 0.327898E+10 | 0.00 | 0.52 |
Maximum of Months | 0.406222E+10 | 0.192599E+09 | 0.00 | 20092152.27 | 9888942.24 | 0.426354E+10 | 0.933927E+10 | 0.00 | 1.93 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.506871E+10 | 0.00 | 0.00 | 316768.83 | 0.00 | 0.385665E+10 | 0.338324E+09 | 0.00 | 0.64 |
February | 0.502569E+10 | 0.00 | 0.00 | 2913513.37 | 0.00 | 0.716151E+09 | 0.201067E+10 | 0.00 | 0.83 |
March | 0.371864E+10 | 0.00 | 0.00 | 6762676.47 | 0.00 | 88889288.95 | 0.543245E+10 | 0.00 | 1.01 |
April | 0.138794E+10 | 0.00 | 0.00 | 15468901.62 | 0.00 | 0.00 | 0.870200E+10 | 0.00 | 1.79 |
May | 0.196047E+10 | 5654081.17 | 0.00 | 13419652.50 | 1504304.35 | 1116436.04 | 0.652908E+10 | 0.00 | 1.80 |
June | 0.832618E+09 | 59492957.89 | 0.00 | 19712577.55 | 696191.73 | 0.00 | 0.628534E+10 | 0.00 | 2.42 |
July | 0.867338E+09 | 0.204511E+09 | 0.00 | 22000449.71 | 6029020.24 | 0.00 | 0.409571E+10 | 0.00 | 2.32 |
August | 0.108578E+10 | 0.144985E+09 | 0.00 | 22866167.48 | 1784339.11 | 0.00 | 0.598395E+10 | 0.00 | 2.76 |
September | 0.178668E+10 | 0.125309E+09 | 0.00 | 9384713.90 | 638955.95 | 0.00 | 0.435569E+10 | 0.00 | 1.72 |
October | 0.238940E+10 | 0.00 | 0.00 | 8354332.27 | 0.00 | 0.00 | 0.530510E+10 | 0.00 | 1.41 |
November | 0.361571E+10 | 0.00 | 0.00 | 4791381.34 | 0.00 | 45239114.67 | 0.399465E+10 | 0.00 | 0.98 |
December | 0.552210E+10 | 0.00 | 0.00 | 2381408.14 | 0.00 | 0.222105E+09 | 0.231557E+10 | 0.00 | 0.68 |
Annual Sum or Average | 0.332611E+11 | 0.539953E+09 | 0.00 | 0.128373E+09 | 10652811.38 | 0.493015E+10 | 0.553485E+11 | 0.00 | 1.53 |
Minimum of Months | 0.832618E+09 | 0.00 | 0.00 | 316768.83 | 0.00 | 0.00 | 0.338324E+09 | 0.00 | 0.64 |
Maximum of Months | 0.552210E+10 | 0.204511E+09 | 0.00 | 22866167.48 | 6029020.24 | 0.385665E+10 | 0.870200E+10 | 0.00 | 2.76 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.278505E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.762956E+11 | 0.00 | 0.00 | 0.35 |
February | 0.118591E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.397713E+11 | 0.00 | 0.00 | 0.33 |
March | 0.276468E+11 | 0.00 | 0.00 | 79217.22 | 0.00 | 0.216568E+11 | 0.209000E+09 | 0.00 | 0.33 |
April | 0.265357E+11 | 0.00 | 0.00 | 9220160.50 | 0.00 | 0.521957E+10 | 0.666571E+10 | 0.00 | 0.41 |
May | 0.203766E+11 | 57693933.61 | 0.00 | 35107438.29 | 11437841.80 | 0.286699E+10 | 0.176815E+11 | 0.00 | 0.57 |
June | 0.895678E+10 | 0.458219E+09 | 0.00 | 85382861.18 | 12479365.65 | 5191612.97 | 0.311395E+11 | 0.00 | 0.92 |
July | 0.495020E+10 | 0.152748E+10 | 0.00 | 87389904.00 | 35747723.03 | 0.00 | 0.191957E+11 | 0.00 | 0.82 |
August | 0.901603E+10 | 0.106492E+10 | 0.00 | 75848292.36 | 60568819.25 | 4992133.08 | 0.200783E+11 | 0.00 | 0.80 |
September | 0.187275E+11 | 0.661048E+09 | 0.00 | 32090708.25 | 46907440.22 | 0.995008E+09 | 0.127707E+11 | 0.00 | 0.59 |
October | 0.278999E+11 | 0.00 | 0.00 | 6619772.63 | 0.00 | 0.477412E+10 | 0.413130E+10 | 0.00 | 0.41 |
November | 0.217527E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.213508E+11 | 0.00 | 0.00 | 0.34 |
December | 0.813763E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.505295E+11 | 0.00 | 0.00 | 0.31 |
Annual Sum or Average | 0.188644E+12 | 0.376937E+10 | 0.00 | 0.331738E+09 | 0.167141E+09 | 0.223470E+12 | 0.111872E+12 | 0.00 | 0.51 |
Minimum of Months | 0.278505E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.31 |
Maximum of Months | 0.278999E+11 | 0.152748E+10 | 0.00 | 87389904.00 | 60568819.25 | 0.762956E+11 | 0.311395E+11 | 0.00 | 0.92 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.114713E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.731477E+11 | 0.00 | 0.00 | 0.61 |
February | 0.221677E+11 | 0.00 | 0.00 | 3442725.25 | 0.00 | 0.411604E+11 | 0.227886E+10 | 0.00 | 0.67 |
March | 0.351287E+11 | 0.00 | 0.00 | 18249925.95 | 0.00 | 0.229226E+11 | 0.121065E+11 | 0.00 | 0.73 |
April | 0.280080E+11 | 0.00 | 0.00 | 52103584.09 | 0.00 | 0.545969E+10 | 0.312887E+11 | 0.00 | 1.05 |
May | 0.225540E+11 | 44442308.08 | 0.00 | 70911942.42 | 15354174.07 | 0.333094E+10 | 0.410972E+11 | 0.00 | 1.36 |
June | 0.117465E+11 | 0.444432E+09 | 0.00 | 0.154954E+09 | 16526908.11 | 13993008.01 | 0.502557E+11 | 0.00 | 2.08 |
July | 0.639058E+10 | 0.131524E+10 | 0.00 | 0.196362E+09 | 49576310.43 | 0.00 | 0.373315E+11 | 0.00 | 2.03 |
August | 0.116055E+11 | 0.111522E+10 | 0.00 | 0.121241E+09 | 82825578.09 | 28279443.27 | 0.394828E+11 | 0.00 | 1.96 |
September | 0.229071E+11 | 0.633453E+09 | 0.00 | 64619422.62 | 64877716.06 | 0.110603E+10 | 0.269993E+11 | 0.00 | 1.36 |
October | 0.340083E+11 | 0.00 | 0.00 | 23220170.06 | 0.00 | 0.496647E+10 | 0.144153E+11 | 0.00 | 0.94 |
November | 0.320828E+11 | 0.00 | 0.00 | 2031432.69 | 0.00 | 0.244644E+11 | 0.165864E+10 | 0.00 | 0.71 |
December | 0.179539E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.548226E+11 | 0.00 | 0.00 | 0.62 |
Annual Sum or Average | 0.256024E+12 | 0.355279E+10 | 0.00 | 0.707135E+09 | 0.229161E+09 | 0.231423E+12 | 0.256915E+12 | 0.00 | 1.18 |
Minimum of Months | 0.639058E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.61 |
Maximum of Months | 0.351287E+11 | 0.131524E+10 | 0.00 | 0.196362E+09 | 82825578.09 | 0.731477E+11 | 0.502557E+11 | 0.00 | 2.08 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.253124E+11 | 0.00 | 0.00 | 33573275.70 | 0.00 | 0.646259E+11 | 0.275663E+11 | 0.00 | 0.55 |
February | 0.267312E+11 | 0.00 | 0.00 | 0.109052E+09 | 0.00 | 0.315263E+11 | 0.511005E+11 | 0.00 | 0.85 |
March | 0.351632E+11 | 0.00 | 0.00 | 0.107247E+09 | 0.00 | 0.217387E+11 | 0.669663E+11 | 0.00 | 0.92 |
April | 0.306982E+11 | 0.00 | 0.00 | 0.101932E+09 | 0.00 | 0.704610E+10 | 0.557103E+11 | 0.00 | 1.11 |
May | 0.278135E+11 | 94951370.43 | 0.00 | 97404716.76 | 18197820.44 | 0.480187E+10 | 0.500422E+11 | 0.00 | 1.19 |
June | 0.192389E+11 | 0.760417E+09 | 0.00 | 0.125753E+09 | 15106640.64 | 0.109961E+09 | 0.411528E+11 | 0.00 | 1.39 |
July | 0.113790E+11 | 0.248550E+10 | 0.00 | 0.141653E+09 | 41808302.42 | 0.00 | 0.255084E+11 | 0.00 | 1.27 |
August | 0.155131E+11 | 0.249147E+10 | 0.00 | 0.175594E+09 | 69204541.73 | 20834302.87 | 0.399000E+11 | 0.00 | 1.64 |
September | 0.225051E+11 | 0.227222E+10 | 0.00 | 0.164144E+09 | 13567901.60 | 0.112166E+10 | 0.585387E+11 | 0.00 | 1.67 |
October | 0.267198E+11 | 0.00 | 0.00 | 0.187843E+09 | 0.00 | 0.356301E+10 | 0.809203E+11 | 0.00 | 1.46 |
November | 0.291540E+11 | 0.00 | 0.00 | 98325391.57 | 0.00 | 0.185366E+11 | 0.565214E+11 | 0.00 | 0.87 |
December | 0.299912E+11 | 0.00 | 0.00 | 37033108.29 | 0.00 | 0.436657E+11 | 0.282761E+11 | 0.00 | 0.58 |
Annual Sum or Average | 0.300220E+12 | 0.810456E+10 | 0.00 | 0.137956E+10 | 0.157885E+09 | 0.196757E+12 | 0.582203E+12 | 0.00 | 1.12 |
Minimum of Months | 0.113790E+11 | 0.00 | 0.00 | 33573275.70 | 0.00 | 0.00 | 0.255084E+11 | 0.00 | 0.55 |
Maximum of Months | 0.351632E+11 | 0.249147E+10 | 0.00 | 0.187843E+09 | 69204541.73 | 0.646259E+11 | 0.809203E+11 | 0.00 | 1.67 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.147038E+11 | 0.00 | 0.00 | 118030.39 | 0.00 | 0.755867E+11 | 0.355954E+09 | 0.00 | 0.66 |
February | 0.263771E+11 | 0.00 | 0.00 | 6411397.97 | 0.00 | 0.410340E+11 | 0.434508E+10 | 0.00 | 0.74 |
March | 0.416954E+11 | 0.00 | 0.00 | 16245143.22 | 0.00 | 0.227436E+11 | 0.125181E+11 | 0.00 | 0.82 |
April | 0.374863E+11 | 0.00 | 0.00 | 47897993.84 | 0.00 | 0.470434E+10 | 0.244967E+11 | 0.00 | 1.17 |
May | 0.281887E+11 | 58165515.56 | 0.00 | 90508403.21 | 17316964.49 | 0.321862E+10 | 0.377565E+11 | 0.00 | 1.49 |
June | 0.166385E+11 | 0.626241E+09 | 0.00 | 0.112271E+09 | 7139274.19 | 55525259.35 | 0.348406E+11 | 0.00 | 1.83 |
July | 0.941912E+10 | 0.236020E+10 | 0.00 | 0.132648E+09 | 9037848.82 | 0.00 | 0.206538E+11 | 0.00 | 1.58 |
August | 0.148091E+11 | 0.150217E+10 | 0.00 | 0.103543E+09 | 35573854.07 | 7485986.95 | 0.240377E+11 | 0.00 | 1.65 |
September | 0.286572E+11 | 0.120433E+10 | 0.00 | 51390780.31 | 5719343.71 | 0.103183E+10 | 0.202651E+11 | 0.00 | 1.40 |
October | 0.402793E+11 | 0.00 | 0.00 | 26684635.50 | 0.00 | 0.453190E+10 | 0.143758E+11 | 0.00 | 1.07 |
November | 0.355145E+11 | 0.00 | 0.00 | 6706702.33 | 0.00 | 0.222910E+11 | 0.586903E+10 | 0.00 | 0.78 |
December | 0.230672E+11 | 0.00 | 0.00 | 426885.28 | 0.00 | 0.548165E+11 | 0.501895E+09 | 0.00 | 0.66 |
Annual Sum or Average | 0.316836E+12 | 0.575111E+10 | 0.00 | 0.594852E+09 | 74787285.28 | 0.230021E+12 | 0.200016E+12 | 0.00 | 1.16 |
Minimum of Months | 0.941912E+10 | 0.00 | 0.00 | 118030.39 | 0.00 | 0.00 | 0.355954E+09 | 0.00 | 0.66 |
Maximum of Months | 0.416954E+11 | 0.236020E+10 | 0.00 | 0.132648E+09 | 35573854.07 | 0.755867E+11 | 0.377565E+11 | 0.00 | 1.83 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.135978E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.802467E+10 | 0.00 | 0.00 | 0.38 |
February | 0.692801E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.457949E+10 | 0.00 | 0.00 | 0.35 |
March | 0.194049E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.299931E+10 | 0.00 | 0.00 | 0.34 |
April | 0.231176E+10 | 0.00 | 0.00 | 625182.95 | 0.00 | 0.111452E+10 | 0.456071E+09 | 0.00 | 0.41 |
May | 0.193150E+10 | 3386812.52 | 0.00 | 3042908.35 | 747508.04 | 0.671110E+09 | 0.160548E+10 | 0.00 | 0.59 |
June | 0.103159E+10 | 25248696.77 | 0.00 | 8433698.20 | 1737664.13 | 33854049.90 | 0.286083E+10 | 0.00 | 0.94 |
July | 0.612917E+09 | 95047802.10 | 0.00 | 9193246.60 | 3120631.55 | 344848.81 | 0.175262E+10 | 0.00 | 0.84 |
August | 0.100397E+10 | 65492023.49 | 0.00 | 7859412.86 | 5243046.78 | 18960429.03 | 0.180155E+10 | 0.00 | 0.80 |
September | 0.176483E+10 | 58272316.67 | 0.00 | 2725910.49 | 3937201.41 | 0.348572E+09 | 0.100608E+10 | 0.00 | 0.59 |
October | 0.232580E+10 | 0.00 | 0.00 | 291580.00 | 0.00 | 0.110849E+10 | 0.165006E+09 | 0.00 | 0.42 |
November | 0.124136E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.285466E+10 | 0.00 | 0.00 | 0.35 |
December | 0.375224E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.556056E+10 | 0.00 | 0.00 | 0.33 |
Annual Sum or Average | 0.153682E+11 | 0.247448E+09 | 0.00 | 32171939.46 | 14786051.91 | 0.273145E+11 | 0.964762E+10 | 0.00 | 0.53 |
Minimum of Months | 0.135978E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 344848.81 | 0.00 | 0.00 | 0.33 |
Maximum of Months | 0.232580E+10 | 95047802.10 | 0.00 | 9193246.60 | 5243046.78 | 0.802467E+10 | 0.286083E+10 | 0.00 | 0.94 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.600150E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.655780E+10 | 0.00 | 0.00 | 0.55 |
February | 0.165582E+10 | 0.00 | 0.00 | 93830.54 | 0.00 | 0.393033E+10 | 78122628.34 | 0.00 | 0.62 |
March | 0.284951E+10 | 0.00 | 0.00 | 1084552.81 | 0.00 | 0.247868E+10 | 0.792584E+09 | 0.00 | 0.67 |
April | 0.240635E+10 | 0.00 | 0.00 | 4027130.93 | 0.00 | 0.965820E+09 | 0.254393E+10 | 0.00 | 0.99 |
May | 0.197942E+10 | 2534518.69 | 0.00 | 6395817.01 | 974605.13 | 0.611549E+09 | 0.382015E+10 | 0.00 | 1.34 |
June | 0.105912E+10 | 23967149.98 | 0.00 | 15222897.84 | 2265576.13 | 32073191.47 | 0.488499E+10 | 0.00 | 2.10 |
July | 0.594156E+09 | 80680526.18 | 0.00 | 19537182.17 | 4068696.71 | 449615.79 | 0.366734E+10 | 0.00 | 2.08 |
August | 0.102088E+10 | 70134362.57 | 0.00 | 12530851.90 | 6687500.71 | 13125292.36 | 0.379829E+10 | 0.00 | 1.96 |
September | 0.191041E+10 | 57088994.41 | 0.00 | 5662676.60 | 4950939.80 | 0.321208E+09 | 0.237714E+10 | 0.00 | 1.31 |
October | 0.295575E+10 | 0.00 | 0.00 | 1386207.86 | 0.00 | 0.942875E+09 | 0.838969E+09 | 0.00 | 0.88 |
November | 0.220142E+10 | 0.00 | 0.00 | 33151.85 | 0.00 | 0.273040E+10 | 31863439.15 | 0.00 | 0.67 |
December | 0.913888E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.518904E+10 | 0.00 | 0.00 | 0.56 |
Annual Sum or Average | 0.201469E+11 | 0.234406E+09 | 0.00 | 65974299.50 | 18947318.49 | 0.237734E+11 | 0.228334E+11 | 0.00 | 1.15 |
Minimum of Months | 0.594156E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 449615.79 | 0.00 | 0.00 | 0.55 |
Maximum of Months | 0.295575E+10 | 80680526.18 | 0.00 | 19537182.17 | 6687500.71 | 0.655780E+10 | 0.488499E+10 | 0.00 | 2.10 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.166990E+10 | 0.00 | 0.00 | 2056226.55 | 0.00 | 0.660688E+10 | 0.187023E+10 | 0.00 | 0.51 |
February | 0.212971E+10 | 0.00 | 0.00 | 8090513.95 | 0.00 | 0.350004E+10 | 0.394720E+10 | 0.00 | 0.77 |
March | 0.283024E+10 | 0.00 | 0.00 | 8590720.19 | 0.00 | 0.270320E+10 | 0.584410E+10 | 0.00 | 0.86 |
April | 0.267001E+10 | 0.00 | 0.00 | 8142190.29 | 0.00 | 0.129834E+10 | 0.511951E+10 | 0.00 | 1.06 |
May | 0.253956E+10 | 5094884.99 | 0.00 | 8876950.82 | 1230699.90 | 0.959379E+09 | 0.499109E+10 | 0.00 | 1.21 |
June | 0.195959E+10 | 39888751.85 | 0.00 | 13380077.90 | 2860896.40 | 99688138.48 | 0.416671E+10 | 0.00 | 1.46 |
July | 0.121809E+10 | 0.147022E+09 | 0.00 | 15656370.42 | 3114386.37 | 2055099.14 | 0.268150E+10 | 0.00 | 1.35 |
August | 0.157995E+10 | 0.149581E+09 | 0.00 | 18634212.46 | 5588850.44 | 30931856.27 | 0.409722E+10 | 0.00 | 1.70 |
September | 0.196973E+10 | 0.190747E+09 | 0.00 | 15298582.42 | 1060866.11 | 0.375191E+09 | 0.568521E+10 | 0.00 | 1.65 |
October | 0.240044E+10 | 0.00 | 0.00 | 14778317.90 | 0.00 | 0.915378E+09 | 0.673318E+10 | 0.00 | 1.37 |
November | 0.245244E+10 | 0.00 | 0.00 | 6233048.40 | 0.00 | 0.228123E+10 | 0.401723E+10 | 0.00 | 0.78 |
December | 0.220011E+10 | 0.00 | 0.00 | 2431251.16 | 0.00 | 0.463974E+10 | 0.187462E+10 | 0.00 | 0.53 |
Annual Sum or Average | 0.256198E+11 | 0.532334E+09 | 0.00 | 0.122168E+09 | 13855699.22 | 0.234121E+11 | 0.510278E+11 | 0.00 | 1.10 |
Minimum of Months | 0.121809E+10 | 0.00 | 0.00 | 2056226.55 | 0.00 | 2055099.14 | 0.187023E+10 | 0.00 | 0.51 |
Maximum of Months | 0.283024E+10 | 0.190747E+09 | 0.00 | 18634212.46 | 5588850.44 | 0.660688E+10 | 0.673318E+10 | 0.00 | 1.70 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.838133E+09 | 0.00 | 0.00 | 3325.29 | 0.00 | 0.707853E+10 | 13753839.29 | 0.00 | 0.62 |
February | 0.191284E+10 | 0.00 | 0.00 | 507829.43 | 0.00 | 0.420917E+10 | 0.351597E+09 | 0.00 | 0.71 |
March | 0.323696E+10 | 0.00 | 0.00 | 1395556.24 | 0.00 | 0.281903E+10 | 0.113171E+10 | 0.00 | 0.80 |
April | 0.345067E+10 | 0.00 | 0.00 | 4196068.74 | 0.00 | 0.925223E+09 | 0.226499E+10 | 0.00 | 1.17 |
May | 0.265987E+10 | 3306316.02 | 0.00 | 8676805.65 | 1106795.01 | 0.691439E+09 | 0.379662E+10 | 0.00 | 1.54 |
June | 0.181989E+10 | 35502017.91 | 0.00 | 13796301.66 | 119677.14 | 36486392.39 | 0.344244E+10 | 0.00 | 1.95 |
July | 0.104830E+10 | 0.140065E+09 | 0.00 | 14279825.25 | 1080991.78 | 0.00 | 0.204039E+10 | 0.00 | 1.65 |
August | 0.154832E+10 | 88232235.23 | 0.00 | 11034688.81 | 2862530.30 | 23756758.54 | 0.231684E+10 | 0.00 | 1.70 |
September | 0.258327E+10 | 0.103920E+09 | 0.00 | 4832985.26 | 1153525.24 | 0.340246E+09 | 0.195249E+10 | 0.00 | 1.42 |
October | 0.331652E+10 | 0.00 | 0.00 | 2167402.33 | 0.00 | 0.103121E+10 | 0.126783E+10 | 0.00 | 1.07 |
November | 0.253454E+10 | 0.00 | 0.00 | 434055.67 | 0.00 | 0.270035E+10 | 0.425186E+09 | 0.00 | 0.76 |
December | 0.147609E+10 | 0.00 | 0.00 | 19503.11 | 0.00 | 0.533394E+10 | 30918612.53 | 0.00 | 0.63 |
Annual Sum or Average | 0.264254E+11 | 0.371025E+09 | 0.00 | 61344347.44 | 6323519.47 | 0.251894E+11 | 0.190348E+11 | 0.00 | 1.17 |
Minimum of Months | 0.838133E+09 | 0.00 | 0.00 | 3325.29 | 0.00 | 0.00 | 13753839.29 | 0.00 | 0.62 |
Maximum of Months | 0.345067E+10 | 0.140065E+09 | 0.00 | 14279825.25 | 2862530.30 | 0.707853E+10 | 0.379662E+10 | 0.00 | 1.95 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 17750309.59 | 0.00 | 0.00 | 2488290.78 | 0.00 | 0.00 | 0.832486E+09 | 0.00 | 0.28 |
February | 0.00 | 0.00 | 0.00 | 7634538.68 | 0.00 | 0.00 | 0.645556E+09 | 0.00 | 0.28 |
March | 0.00 | 0.00 | 0.00 | 14601312.95 | 0.00 | 0.00 | 0.661614E+09 | 0.00 | 0.31 |
April | 0.00 | 0.00 | 0.00 | 18468304.80 | 0.00 | 0.00 | 0.461720E+09 | 0.00 | 0.29 |
May | 0.00 | 153001.14 | 0.00 | 4171266.36 | 0.00 | 0.00 | 0.408421E+09 | 0.00 | 0.29 |
June | 0.00 | 13317302.34 | 0.00 | 7658731.83 | 0.00 | 0.00 | 0.199993E+09 | 0.00 | 0.30 |
July | 0.00 | 21213902.83 | 0.00 | 9094238.94 | 0.00 | 0.00 | 79937235.00 | 0.00 | 0.28 |
August | 0.00 | 5912623.85 | 0.00 | 17153548.80 | 0.00 | 0.00 | 0.147379E+09 | 0.00 | 0.31 |
September | 0.00 | 11479249.93 | 0.00 | 3720491.65 | 0.00 | 0.00 | 0.257750E+09 | 0.00 | 0.29 |
October | 0.00 | 0.00 | 0.00 | 8863880.95 | 0.00 | 0.00 | 0.439715E+09 | 0.00 | 0.28 |
November | 0.00 | 0.00 | 0.00 | 12658813.69 | 0.00 | 0.00 | 0.543613E+09 | 0.00 | 0.28 |
December | 0.00 | 0.00 | 0.00 | 17307668.20 | 0.00 | 0.00 | 0.716687E+09 | 0.00 | 0.28 |
Annual Sum or Average | 17750309.59 | 52076080.09 | 0.00 | 0.123821E+09 | 0.00 | 0.00 | 0.539487E+10 | 0.00 | 0.29 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 2488290.78 | 0.00 | 0.00 | 79937235.00 | 0.00 | 0.28 |
Maximum of Months | 17750309.59 | 21213902.83 | 0.00 | 18468304.80 | 0.00 | 0.00 | 0.832486E+09 | 0.00 | 0.31 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.303416E+10 | 0.00 | 0.00 | 8685900.15 | 0.00 | 0.00 | 0.543781E+10 | 0.00 | 0.28 |
February | 0.00 | 0.00 | 0.00 | 58974633.49 | 0.00 | 0.00 | 0.647307E+10 | 0.00 | 0.28 |
March | 0.00 | 0.00 | 0.00 | 0.125642E+09 | 0.00 | 0.00 | 0.663600E+10 | 0.00 | 0.31 |
April | 0.00 | 0.00 | 0.00 | 0.167765E+09 | 0.00 | 0.00 | 0.463190E+10 | 0.00 | 0.29 |
May | 18588329.52 | 1450962.40 | 0.00 | 33405635.79 | 0.00 | 0.00 | 0.407836E+10 | 0.00 | 0.29 |
June | 0.00 | 0.131858E+09 | 0.00 | 70573667.39 | 0.00 | 0.00 | 0.200839E+10 | 0.00 | 0.30 |
July | 0.00 | 0.211095E+09 | 0.00 | 85857905.69 | 0.00 | 0.00 | 0.805437E+09 | 0.00 | 0.28 |
August | 0.00 | 59649360.84 | 0.00 | 0.161269E+09 | 0.00 | 0.00 | 0.148162E+10 | 0.00 | 0.31 |
September | 0.00 | 0.112320E+09 | 0.00 | 30277161.32 | 0.00 | 0.00 | 0.259879E+10 | 0.00 | 0.29 |
October | 0.00 | 0.00 | 0.00 | 75582679.01 | 0.00 | 0.00 | 0.440989E+10 | 0.00 | 0.28 |
November | 0.00 | 0.00 | 0.00 | 0.108291E+09 | 0.00 | 0.00 | 0.545343E+10 | 0.00 | 0.28 |
December | 0.00 | 0.00 | 0.00 | 0.148122E+09 | 0.00 | 0.00 | 0.718969E+10 | 0.00 | 0.28 |
Annual Sum or Average | 0.305275E+10 | 0.516373E+09 | 0.00 | 0.107445E+10 | 0.00 | 0.00 | 0.512044E+11 | 0.00 | 0.29 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 8685900.15 | 0.00 | 0.00 | 0.805437E+09 | 0.00 | 0.28 |
Maximum of Months | 0.303416E+10 | 0.211095E+09 | 0.00 | 0.167765E+09 | 0.00 | 0.00 | 0.718969E+10 | 0.00 | 0.31 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.567837E+09 | 0.00 | 0.00 | 384867.62 | 0.00 | 0.00 | 0.263225E+09 | 0.00 | 0.28 |
February | 0.00 | 0.00 | 0.00 | 4960722.52 | 0.00 | 0.00 | 0.648194E+09 | 0.00 | 0.28 |
March | 0.00 | 0.00 | 0.00 | 11566459.16 | 0.00 | 0.00 | 0.664620E+09 | 0.00 | 0.31 |
April | 0.00 | 0.00 | 0.00 | 16046435.29 | 0.00 | 0.00 | 0.464068E+09 | 0.00 | 0.29 |
May | 28326643.91 | 147070.41 | 0.00 | 2917176.89 | 0.00 | 0.00 | 0.381122E+09 | 0.00 | 0.29 |
June | 0.00 | 13221639.56 | 0.00 | 6910745.78 | 0.00 | 0.00 | 0.201172E+09 | 0.00 | 0.30 |
July | 0.00 | 21119792.57 | 0.00 | 8548498.67 | 0.00 | 0.00 | 80683679.76 | 0.00 | 0.28 |
August | 0.00 | 5980605.76 | 0.00 | 15995764.69 | 0.00 | 0.00 | 0.148380E+09 | 0.00 | 0.31 |
September | 7481603.52 | 11218083.11 | 0.00 | 2612052.28 | 0.00 | 0.00 | 0.253936E+09 | 0.00 | 0.29 |
October | 0.00 | 0.00 | 0.00 | 6712768.74 | 0.00 | 0.00 | 0.442064E+09 | 0.00 | 0.28 |
November | 0.00 | 0.00 | 0.00 | 9834061.36 | 0.00 | 0.00 | 0.546395E+09 | 0.00 | 0.28 |
December | 0.00 | 0.00 | 0.00 | 13734595.88 | 0.00 | 0.00 | 0.720142E+09 | 0.00 | 0.28 |
Annual Sum or Average | 0.603645E+09 | 51687191.41 | 0.00 | 0.100224E+09 | 0.00 | 0.00 | 0.481400E+10 | 0.00 | 0.29 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 384867.62 | 0.00 | 0.00 | 80683679.76 | 0.00 | 0.28 |
Maximum of Months | 0.567837E+09 | 21119792.57 | 0.00 | 16046435.29 | 0.00 | 0.00 | 0.720142E+09 | 0.00 | 0.31 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.899342E+09 | 0.00 | 0.00 | 0.494851E+12 | 0.00 | 7.40 |
February | 0.00 | 0.00 | 0.00 | 0.133243E+10 | 0.00 | 0.00 | 0.751252E+12 | 0.00 | 15.50 |
March | 0.00 | 0.00 | 0.00 | 0.190649E+10 | 0.00 | 0.00 | 0.108849E+13 | 0.00 | 22.92 |
April | 0.00 | 0.00 | 0.00 | 0.228178E+10 | 0.00 | 0.00 | 0.122917E+13 | 0.00 | 36.39 |
May | 0.00 | 0.00 | 0.00 | 0.562634E+09 | 0.00 | 0.00 | 0.492113E+12 | 0.00 | 17.40 |
June | 0.00 | 0.229975E+10 | 0.00 | 0.122370E+10 | 0.00 | 0.00 | 0.580708E+12 | 0.00 | 33.08 |
July | 0.00 | 0.264912E+10 | 0.00 | 0.206998E+10 | 0.00 | 0.00 | 0.508942E+12 | 0.00 | 37.31 |
August | 0.00 | 0.110654E+09 | 0.00 | 0.308767E+10 | 0.00 | 0.00 | 0.737617E+12 | 0.00 | 45.80 |
September | 0.00 | 0.908784E+09 | 0.00 | 0.545810E+09 | 0.00 | 0.00 | 0.406497E+12 | 0.00 | 21.23 |
October | 0.00 | 0.00 | 0.00 | 0.112197E+10 | 0.00 | 0.00 | 0.817469E+12 | 0.00 | 24.49 |
November | 0.00 | 0.00 | 0.00 | 0.188347E+10 | 0.00 | 0.00 | 0.105421E+13 | 0.00 | 26.06 |
December | 0.00 | 0.00 | 0.00 | 0.318159E+10 | 0.00 | 0.00 | 0.133143E+13 | 0.00 | 25.86 |
Annual Sum or Average | 0.00 | 0.596831E+10 | 0.00 | 0.200969E+11 | 0.00 | 0.00 | 0.949275E+13 | 0.00 | 26.17 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.545810E+09 | 0.00 | 0.00 | 0.406497E+12 | 0.00 | 7.40 |
Maximum of Months | 0.00 | 0.264912E+10 | 0.00 | 0.318159E+10 | 0.00 | 0.00 | 0.133143E+13 | 0.00 | 45.80 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 08:43:39
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.265165E+12 | 0.461601E+11 | 0.00 | 0.213850E+13 | 0.277854E+12 |
February | 0.354242E+12 | 0.360540E+11 | 0.00 | 0.236151E+13 | 0.270811E+12 |
March | 0.611807E+12 | 0.337316E+11 | 0.00 | 0.304117E+13 | 0.330496E+12 |
April | 0.656598E+12 | 0.240427E+11 | 0.00 | 0.332368E+13 | 0.525954E+12 |
May | 0.868397E+12 | 0.236522E+11 | 0.00 | 0.255101E+13 | 0.430250E+12 |
June | 0.948750E+12 | 0.122389E+11 | 0.00 | 0.235360E+13 | 0.131111E+13 |
July | 0.939531E+12 | 0.804868E+10 | 0.00 | 0.196345E+13 | 0.248720E+13 |
August | 0.779766E+12 | 0.871622E+10 | 0.00 | 0.236797E+13 | 0.253161E+13 |
September | 0.585056E+12 | 0.157490E+11 | 0.00 | 0.222914E+13 | 0.804244E+12 |
October | 0.380508E+12 | 0.230541E+11 | 0.00 | 0.300949E+13 | 0.373773E+12 |
November | 0.206449E+12 | 0.324703E+11 | 0.00 | 0.295794E+13 | 0.319308E+12 |
December | 0.170156E+12 | 0.412799E+11 | 0.00 | 0.302871E+13 | 0.455573E+12 |
Annual Sum or Average | 0.676642E+13 | 0.305198E+12 | 0.00 | 0.313262E+14 | 0.101182E+14 |
Minimum of Months | 0.170156E+12 | 0.804868E+10 | 0.00 | 0.196345E+13 | 0.270811E+12 |
Maximum of Months | 0.948750E+12 | 0.461601E+11 | 0.00 | 0.332368E+13 | 0.253161E+13 |