Table of Contents

Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:43

Tabular Output Report in Format: HTML

Building: OfficeLarge

Environment: RUNPERIOD 1 ** Miami Intl Ap FL USA TMY3 WMO#=722020

Simulation Timestamp: 2023-10-16 08:43:45


Table of Contents

Report: Annual Building Utility Performance Summary

For: Entire Facility

Timestamp: 2023-10-16 08:43:45

Values gathered over 8760.00 hours



Site and Source Energy

Total Energy [GJ] Energy Per Total Building Area [MJ/m2] Energy Per Conditioned Building Area [MJ/m2]
Total Site Energy 34479.41 744.37 744.37
Net Site Energy 34479.41 744.37 744.37
Total Source Energy 107819.61 2327.69 2327.69
Net Source Energy 107819.61 2327.69 2327.69


Site to Source Energy Conversion Factors

Site=>Source Conversion Factor
Electricity 3.167
Natural Gas 1.084
District Cooling 1.056
District Heating 3.613
Steam 1.200
Gasoline 1.050
Diesel 1.050
Coal 1.050
Fuel Oil No 1 1.050
Fuel Oil No 2 1.050
Propane 1.050
Other Fuel 1 1.000
Other Fuel 2 1.000


Building Area

Area [m2]
Total Building Area 46320.38
Net Conditioned Building Area 46320.38
Unconditioned Building Area 0.00


End Uses

Electricity [GJ] Natural Gas [GJ] Gasoline [GJ] Diesel [GJ] Coal [GJ] Fuel Oil No 1 [GJ] Fuel Oil No 2 [GJ] Propane [GJ] Other Fuel 1 [GJ] Other Fuel 2 [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating 0.00 20.08 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 6915.41 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 3922.25 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 696.56 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 14676.40 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 1934.78 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 2279.76 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 978.88 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 2294.23 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 18531.59
Humidification 1.14 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.43
Heat Recovery 119.08 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 640.83 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 2280.17
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                           
Total End Uses 33818.50 660.92 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 20812.18
Note: Natural gas appears to be the principal heating source based on energy usage.

End Uses By Subcategory

Subcategory Electricity [GJ] Natural Gas [GJ] Gasoline [GJ] Diesel [GJ] Coal [GJ] Fuel Oil No 1 [GJ] Fuel Oil No 2 [GJ] Propane [GJ] Other Fuel 1 [GJ] Other Fuel 2 [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Boiler 0.00 20.08 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Boiler Parasitic 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling General 6915.41 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting LightsWired 3922.25 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting General 696.56 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment MiscPlug 5334.97 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  DataCenterPlugLoads 9341.42 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment Transformer 80.17 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  ElevatorLift 1848.78 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  ElevatorLightsFan 5.83 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans General 2279.76 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps General 978.88 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection General 2294.23 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 18531.59
Humidification General 1.14 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.43
Heat Recovery General 119.08 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  WaterUse 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 2280.17
  Water Heater 0.00 640.83 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


End Uses By Space Type

Space Type Electricity [GJ] Natural Gas [GJ] Gasoline [GJ] Diesel [GJ] Coal [GJ] Fuel Oil No 1 [GJ] Fuel Oil No 2 [GJ] Propane [GJ] Other Fuel 1 [GJ] Other Fuel 2 [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating Unassigned 0.00 20.08 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling Unassigned 6915.41 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting GENERAL 3922.25 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting Unassigned 696.56 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment GENERAL 14676.40 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment Unassigned 1934.78 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans Unassigned 2279.76 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps Unassigned 978.88 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection Unassigned 2294.23 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 18531.59
Humidification Unassigned 1.14 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.43
Heat Recovery Unassigned 119.08 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems Unassigned 0.00 640.83 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 2280.17
Refrigeration Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Normalized Metrics

Utility Use Per Conditioned Floor Area

Electricity Intensity [MJ/m2] Natural Gas Intensity [MJ/m2] Gasoline Intensity [MJ/m2] Diesel Intensity [MJ/m2] Coal Intensity [MJ/m2] Fuel Oil No 1 Intensity [MJ/m2] Fuel Oil No 2 Intensity [MJ/m2] Propane Intensity [MJ/m2] Other Fuel 1 Intensity [MJ/m2] Other Fuel 2 Intensity [MJ/m2] District Cooling Intensity [MJ/m2] District Heating Intensity [MJ/m2] Water Intensity [m3/m2]
Lighting 99.71 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
HVAC 269.20 14.27 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.45
Other 361.19 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total 730.10 14.27 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.45


Utility Use Per Total Floor Area

Electricity Intensity [MJ/m2] Natural Gas Intensity [MJ/m2] Gasoline Intensity [MJ/m2] Diesel Intensity [MJ/m2] Coal Intensity [MJ/m2] Fuel Oil No 1 Intensity [MJ/m2] Fuel Oil No 2 Intensity [MJ/m2] Propane Intensity [MJ/m2] Other Fuel 1 Intensity [MJ/m2] Other Fuel 2 Intensity [MJ/m2] District Cooling Intensity [MJ/m2] District Heating Intensity [MJ/m2] Water Intensity [m3/m2]
Lighting 99.71 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
HVAC 269.20 14.27 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.45
Other 361.19 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total 730.10 14.27 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.45


Electric Loads Satisfied

Electricity [GJ] Percent Electricity [%]
Fuel-Fired Power Generation 0.000 0.00
High Temperature Geothermal* 0.000 0.00
Photovoltaic Power 0.000 0.00
Wind Power 0.000 0.00
Power Conversion 0.000 0.00
Net Decrease in On-Site Storage 0.000 0.00
Total On-Site Electric Sources 0.000 0.00
     
Electricity Coming From Utility 33818.497 100.00
Surplus Electricity Going To Utility 0.000 0.00
Net Electricity From Utility 33818.497 100.00
     
Total On-Site and Utility Electric Sources 33818.497 100.00
Total Electricity End Uses 33818.497 100.00


On-Site Thermal Sources

Heat [GJ] Percent Heat [%]
Water-Side Heat Recovery 0.00 0.00
Air to Air Heat Recovery for Cooling 5918.09 99.77
Air to Air Heat Recovery for Heating 13.48 0.23
High-Temperature Geothermal* 0.00 0.00
Solar Water Thermal 0.00 0.00
Solar Air Thermal 0.00 0.00
Total On-Site Thermal Sources 5931.57 100.00


Water Source Summary

Water [m3] Percent Water [%]
Rainwater Collection 0.00 0.00
Condensate Collection 0.00 0.00
Groundwater Well 0.00 0.00
Total On Site Water Sources 0.00 0.00
- - -
Initial Storage 0.00 0.00
Final Storage 0.00 0.00
Change in Storage 0.00 0.00
- - -
Water Supplied by Utility 20812.18 100.00
- - -
Total On Site, Change in Storage, and Utility Water Sources 20812.18 100.00
Total Water End Uses 20812.18 100.00


Setpoint Not Met Criteria

Degrees [deltaC]
Tolerance for Zone Heating Setpoint Not Met Time 0.56
Tolerance for Zone Cooling Setpoint Not Met Time 0.56


Comfort and Setpoint Not Met Summary

Facility [Hours]
Time Setpoint Not Met During Occupied Heating 0.00
Time Setpoint Not Met During Occupied Cooling 1000.17
Time Not Comfortable Based on Simple ASHRAE 55-2004 5943.00


Note 1: An asterisk (*) indicates that the feature is not yet implemented.

Table of Contents

Top
Annual Building Utility Performance Summary
Input Verification and Results Summary
Demand End Use Components Summary
Source Energy End Use Components Summary
Component Sizing Summary
Surface Shadowing Summary
Adaptive Comfort Summary
Initialization Summary
Annual Heat Emissions Summary
Climatic Data Summary
Envelope Summary
Shading Summary
Lighting Summary
Equipment Summary
HVAC Sizing Summary
Coil Sizing Details
System Summary
Outdoor Air Summary
Outdoor Air Details
Object Count Summary
Energy Meters
Sensible Heat Gain Summary
Standard 62.1 Summary
LEED Summary
Annual Thermal Resilience Summary
Annual CO2 Resilience Summary
Annual Visual Resilience Summary

NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR

| Environment |

NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901

| Environment |

NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2013

| Environment |

NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND

| Environment |

NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICELARGE

| Environment |

NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL

| Environment |

NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL

| Environment |

NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 1A

| Environment |

NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_FL_MIAMI

| Environment |

ZoneCoolingSummaryMonthly

| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |

ZoneHeatingSummaryMonthly

| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |

ZoneElectricSummaryMonthly

| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |

SpaceGainsMonthly

| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |

PeakSpaceGainsMonthly

| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |

SpaceGainComponentsAtCoolingPeakMonthly

| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |

EnergyConsumptionElectricityNaturalGasMonthly

| Meter |

EndUseEnergyConsumptionElectricityMonthly

| Meter |

EndUseEnergyConsumptionNaturalGasMonthly

| Meter |

PeakEnergyEndUseElectricityPart1Monthly

| Meter |

PeakEnergyEndUseElectricityPart2Monthly

| Meter |

ElectricComponentsOfPeakDemandMonthly

| Meter |

PeakEnergyEndUseNaturalGasMonthly

| Meter |

SetpointsNotMetWithTemperaturesMonthly

| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |

ComfortReportSimple55Monthly

| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |

OccupantComfortDataSummaryMonthly

| DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 | BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 |

ChillerReportMonthly

| COOLSYS1 CHILLER1 | COOLSYS1 CHILLER2 |

TowerReportMonthly

| CENTRAL TOWER | TOWERWATERSYS COOLTOWER 1 | TOWERWATERSYS COOLTOWER 2 |

BoilerReportMonthly

| HEATSYS1 BOILER | CENTRAL BOILER |

DXReportMonthly

| VAV_BOT WITH REHEAT COOLING COIL | VAV_MID WITH REHEAT COOLING COIL | VAV_TOP WITH REHEAT COOLING COIL | CAV_BAS COOLING COIL | AIRLOOP DATACENTER BASEMENT COOLING COIL | AIRLOOP DATACENTER BOT COOLING COIL | AIRLOOP DATACENTER MID COOLING COIL | AIRLOOP DATACENTER TOP COOLING COIL |

WindowReportMonthly

| PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW |

WindowEnergyReportMonthly

| PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW |

WindowZoneSummaryMonthly

| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |

WindowEnergyZoneSummaryMonthly

| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |

AverageOutdoorConditionsMonthly

| Environment |

OutdoorConditionsMaximumDryBulbMonthly

| Environment |

OutdoorConditionsMinimumDryBulbMonthly

| Environment |

OutdoorConditionsMaximumWetBulbMonthly

| Environment |

OutdoorConditionsMaximumDewPointMonthly

| Environment |

OutdoorGroundConditionsMonthly

| Environment |

WaterHeaterReportMonthly

| SWHSYS1 WATER HEATER |

DaylightingReportMonthly

| PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_4_DAYLCTRL |

CoilReportMonthly

| VAV_BOT WITH REHEAT HEATING COIL | CORE_BOTTOM VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | VAV_MID WITH REHEAT HEATING COIL | CORE_MID VAV BOX REHEAT COIL | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | VAV_TOP WITH REHEAT HEATING COIL | CORE_TOP VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | CAV_BAS HEATING COIL | AIRLOOP DATACENTER BASEMENT HEATING COIL | AIRLOOP DATACENTER BOT HEATING COIL | AIRLOOP DATACENTER MID HEATING COIL | AIRLOOP DATACENTER TOP HEATING COIL | AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | AIRLOOP DATACENTER BOT_SUPPHEATCOIL | AIRLOOP DATACENTER MID_SUPPHEATCOIL | AIRLOOP DATACENTER TOP_SUPPHEATCOIL | VAV_BOT WITH REHEAT COOLING COIL | VAV_MID WITH REHEAT COOLING COIL | VAV_TOP WITH REHEAT COOLING COIL | CAV_BAS COOLING COIL | AIRLOOP DATACENTER BASEMENT COOLING COIL | AIRLOOP DATACENTER BOT COOLING COIL | AIRLOOP DATACENTER MID COOLING COIL | AIRLOOP DATACENTER TOP COOLING COIL |

PlantLoopDemandReportMonthly

| HEATSYS1 | COOLSYS1_SUPPLY | COOLSYS1_DEMAND | SINGLE WATER PLANT LOOP | SWHSYS1 | TOWERWATERSYS |

FanReportMonthly

| CAV_BAS FAN | VAV_BOT WITH REHEAT FAN | VAV_MID WITH REHEAT FAN | VAV_TOP WITH REHEAT FAN | AIRLOOP DATACENTER BASEMENT SUPPLY FAN | AIRLOOP DATACENTER BOT SUPPLY FAN | AIRLOOP DATACENTER MID SUPPLY FAN | AIRLOOP DATACENTER TOP SUPPLY FAN |

PumpReportMonthly

| HEATSYS1 PUMP | COOLSYS1 PUMP SECONDARY | COOLSYS1 CHILLER1 PUMP | COOLSYS1 CHILLER2 PUMP | PLANT CIRC PUMP | SWHSYS1 PUMP | TOWERWATERSYS PUMP |

CondLoopDemandReportMonthly

| HEATSYS1 | COOLSYS1_SUPPLY | COOLSYS1_DEMAND | SINGLE WATER PLANT LOOP | SWHSYS1 | TOWERWATERSYS |

ZoneTemperatureOscillationReportMonthly

| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |

AirLoopSystemEnergyAndWaterUseMonthly

| VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | CAV_BAS | AIRLOOP DATACENTER BASEMENT | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |

AirLoopSystemComponentLoadsMonthly

| VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | CAV_BAS | AIRLOOP DATACENTER BASEMENT | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |

AirLoopSystemComponentEnergyUseMonthly

| VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | CAV_BAS | AIRLOOP DATACENTER BASEMENT | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |

MechanicalVentilationLoadsMonthly

| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |

HeatEmissionsReportMonthly

| Environment |

Table of Contents

Report: Input Verification and Results Summary

For: Entire Facility

Timestamp: 2023-10-16 08:43:45

General

Value
Program Version and Build EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:43
RunPeriod RUNPERIOD 1
Weather File Miami Intl Ap FL USA TMY3 WMO#=722020
Latitude [deg] 25.82
Longitude [deg] -80.3
Elevation [m] 11.00
Time Zone -5.0
North Axis Angle [deg] 0.00
Rotation for Appendix G [deg] 0.00
Hours Simulated [hrs] 8760.00


ENVELOPE

Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [m2] 12183.89 3655.17 2436.78 3655.17 2436.78
Above Ground Wall Area [m2] 11589.54 3476.86 2317.91 3476.86 2317.91
Window Opening Area [m2] 4635.80 1390.74 927.16 1390.74 927.16
Gross Window-Wall Ratio [%] 38.05 38.05 38.05 38.05 38.05
Above Ground Window-Wall Ratio [%] 40.00 40.00 40.00 40.00 40.00


Conditioned Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [m2] 12183.89 3655.17 2436.78 3655.17 2436.78
Above Ground Wall Area [m2] 11589.54 3476.86 2317.91 3476.86 2317.91
Window Opening Area [m2] 4635.80 1390.74 927.16 1390.74 927.16
Gross Window-Wall Ratio [%] 38.05 38.05 38.05 38.05 38.05
Above Ground Window-Wall Ratio [%] 40.00 40.00 40.00 40.00 40.00


Skylight-Roof Ratio

Total
Gross Roof Area [m2] 3563.11
Skylight Area [m2] 0.00
Skylight-Roof Ratio [%] 0.00


PERFORMANCE

Zone Summary

Area [m2] Conditioned (Y/N) Part of Total Floor Area (Y/N) Volume [m3] Multipliers Above Ground Gross Wall Area [m2] Underground Gross Wall Area [m2] Window Glass Area [m2] Opening Area [m2] Lighting [W/m2] People [m2 per person] Plug and Process [W/m2]
BASEMENT 2779.43 Yes Yes 6779.02 1.00 0.00 397.05 0.00 0.00 10.2732 18.58 4.8418
CORE_BOTTOM 2496.12 Yes Yes 6849.35 1.00 0.00 0.00 0.00 0.00 10.2732 18.58 8.0697
CORE_MID 2496.12 Yes Yes 6849.35 10.00 0.00 0.00 0.00 0.00 10.2732 18.58 8.0696
CORE_TOP 2496.12 Yes Yes 6849.35 1.00 0.00 0.00 0.00 0.00 10.2732 18.58 8.0696
PERIMETER_BOT_ZN_3 313.41 Yes Yes 860.00 1.00 200.61 0.00 115.90 115.90 10.2732 18.58 8.0700
PERIMETER_BOT_ZN_2 201.98 Yes Yes 554.22 1.00 133.74 0.00 77.26 77.26 10.2732 18.58 8.0700
PERIMETER_BOT_ZN_1 313.42 Yes Yes 860.02 1.00 200.61 0.00 115.90 115.90 10.2732 18.58 8.0699
PERIMETER_BOT_ZN_4 201.98 Yes Yes 554.22 1.00 133.74 0.00 77.26 77.26 10.2732 18.58 8.0699
PERIMETER_MID_ZN_3 313.41 Yes Yes 860.00 10.00 200.61 0.00 115.90 115.90 10.2732 18.58 8.0700
PERIMETER_MID_ZN_2 201.98 Yes Yes 554.22 10.00 133.74 0.00 77.26 77.26 10.2732 18.58 8.0700
PERIMETER_MID_ZN_1 313.42 Yes Yes 860.02 10.00 200.61 0.00 115.90 115.90 10.2732 18.58 8.0699
PERIMETER_MID_ZN_4 201.98 Yes Yes 554.22 10.00 133.74 0.00 77.26 77.26 10.2732 18.58 8.0699
PERIMETER_TOP_ZN_3 313.41 Yes Yes 860.00 1.00 200.61 0.00 115.90 115.90 10.2732 18.58 8.0700
PERIMETER_TOP_ZN_2 201.98 Yes Yes 554.22 1.00 133.74 0.00 77.26 77.26 10.2732 18.58 8.0700
PERIMETER_TOP_ZN_1 313.42 Yes Yes 860.02 1.00 200.61 0.00 115.90 115.90 10.2732 18.58 8.0699
PERIMETER_TOP_ZN_4 201.98 Yes Yes 554.22 1.00 133.74 0.00 77.26 77.26 10.2732 18.58 8.0699
GROUNDFLOOR_PLENUM 3563.11 Yes No 4344.14 1.00 297.11 0.00 0.00 0.00 0.0000   0.0000
MIDFLOOR_PLENUM 3563.11 Yes No 4344.14 10.00 297.11 0.00 0.00 0.00 0.0000   0.0000
TOPFLOOR_PLENUM 3563.11 Yes No 4344.14 1.00 297.11 0.00 0.00 0.00 0.0000   0.0000
DATACENTER_BOT_ZN_6 36.20 Yes Yes 99.34 1.00 0.00 0.00 0.00 0.00 17.8735 18.58 215.2992
DATACENTER_MID_ZN_6 36.20 Yes Yes 99.34 10.00 0.00 0.00 0.00 0.00 17.8735 18.58 215.2992
DATACENTER_TOP_ZN_6 36.20 Yes Yes 99.34 1.00 0.00 0.00 0.00 0.00 17.8735 18.58 215.2992
DATACENTER_BASEMENT_ZN_6 783.68 Yes Yes 1911.37 1.00 0.00 197.31 0.00 0.00 10.2732 18.58 484.4232
Total 46320.38     126016.35   8024.24 594.36 4635.80 4635.80 10.3445 18.58 17.8789
Conditioned Total 46320.38     126016.35   8024.24 594.36 4635.80 4635.80 10.3445 18.58 17.8789
Unconditioned Total 0.00     0.00   0.00 0.00 0.00 0.00      
Not Part of Total 42757.27     52129.67   3565.29 0.00 0.00 0.00 0.0000   0.0000


Space Summary

Area [m2] Conditioned (Y/N) Part of Total Floor Area (Y/N) Multipliers Zone Name Space Type Radiant/Solar Enclosure Name Lighting [W/m2] People [m2 per person] Plug and Process [W/m2] Tags
BASEMENT 2779.43 Yes Yes 1.00 BASEMENT GENERAL BASEMENT 10.2732 18.58 4.8418  
CORE_BOTTOM 2496.12 Yes Yes 1.00 CORE_BOTTOM GENERAL CORE_BOTTOM 10.2732 18.58 8.0697  
CORE_MID 2496.12 Yes Yes 10.00 CORE_MID GENERAL CORE_MID 10.2732 18.58 8.0696  
CORE_TOP 2496.12 Yes Yes 1.00 CORE_TOP GENERAL CORE_TOP 10.2732 18.58 8.0696  
PERIMETER_BOT_ZN_3 313.41 Yes Yes 1.00 PERIMETER_BOT_ZN_3 GENERAL PERIMETER_BOT_ZN_3 10.2732 18.58 8.0700  
PERIMETER_BOT_ZN_2 201.98 Yes Yes 1.00 PERIMETER_BOT_ZN_2 GENERAL PERIMETER_BOT_ZN_2 10.2732 18.58 8.0700  
PERIMETER_BOT_ZN_1 313.42 Yes Yes 1.00 PERIMETER_BOT_ZN_1 GENERAL PERIMETER_BOT_ZN_1 10.2732 18.58 8.0699  
PERIMETER_BOT_ZN_4 201.98 Yes Yes 1.00 PERIMETER_BOT_ZN_4 GENERAL PERIMETER_BOT_ZN_4 10.2732 18.58 8.0699  
PERIMETER_MID_ZN_3 313.41 Yes Yes 10.00 PERIMETER_MID_ZN_3 GENERAL PERIMETER_MID_ZN_3 10.2732 18.58 8.0700  
PERIMETER_MID_ZN_2 201.98 Yes Yes 10.00 PERIMETER_MID_ZN_2 GENERAL PERIMETER_MID_ZN_2 10.2732 18.58 8.0700  
PERIMETER_MID_ZN_1 313.42 Yes Yes 10.00 PERIMETER_MID_ZN_1 GENERAL PERIMETER_MID_ZN_1 10.2732 18.58 8.0699  
PERIMETER_MID_ZN_4 201.98 Yes Yes 10.00 PERIMETER_MID_ZN_4 GENERAL PERIMETER_MID_ZN_4 10.2732 18.58 8.0699  
PERIMETER_TOP_ZN_3 313.41 Yes Yes 1.00 PERIMETER_TOP_ZN_3 GENERAL PERIMETER_TOP_ZN_3 10.2732 18.58 8.0700  
PERIMETER_TOP_ZN_2 201.98 Yes Yes 1.00 PERIMETER_TOP_ZN_2 GENERAL PERIMETER_TOP_ZN_2 10.2732 18.58 8.0700  
PERIMETER_TOP_ZN_1 313.42 Yes Yes 1.00 PERIMETER_TOP_ZN_1 GENERAL PERIMETER_TOP_ZN_1 10.2732 18.58 8.0699  
PERIMETER_TOP_ZN_4 201.98 Yes Yes 1.00 PERIMETER_TOP_ZN_4 GENERAL PERIMETER_TOP_ZN_4 10.2732 18.58 8.0699  
GROUNDFLOOR_PLENUM 3563.11 Yes No 1.00 GROUNDFLOOR_PLENUM GENERAL GROUNDFLOOR_PLENUM 0.0000 0.00 0.0000  
MIDFLOOR_PLENUM 3563.11 Yes No 10.00 MIDFLOOR_PLENUM GENERAL MIDFLOOR_PLENUM 0.0000 0.00 0.0000  
TOPFLOOR_PLENUM 3563.11 Yes No 1.00 TOPFLOOR_PLENUM GENERAL TOPFLOOR_PLENUM 0.0000 0.00 0.0000  
DATACENTER_BOT_ZN_6 36.20 Yes Yes 1.00 DATACENTER_BOT_ZN_6 GENERAL DATACENTER_BOT_ZN_6 17.8735 18.58 215.2992  
DATACENTER_MID_ZN_6 36.20 Yes Yes 10.00 DATACENTER_MID_ZN_6 GENERAL DATACENTER_MID_ZN_6 17.8735 18.58 215.2992  
DATACENTER_TOP_ZN_6 36.20 Yes Yes 1.00 DATACENTER_TOP_ZN_6 GENERAL DATACENTER_TOP_ZN_6 17.8735 18.58 215.2992  
DATACENTER_BASEMENT_ZN_6 783.68 Yes Yes 1.00 DATACENTER_BASEMENT_ZN_6 GENERAL DATACENTER_BASEMENT_ZN_6 10.2732 18.58 484.4232  
Total 46320.38             10.3445 9.29 17.8789  
Conditioned Total 46320.38             10.3445 9.29 17.8789  
Unconditioned Total 0.00             0.0000 0.00 0.0000  
Not Part of Total 42757.27             0.0000 0.00 0.0000  


Space Type Summary

Total Area [m2] Conditioned Area [m2] Unconditioned Area [m2] Not Part of Total Area [m2] Lighting [W/m2] People [m2 per person] Plug and Process [W/m2]
GENERAL 46320.38 46320.38 0.00 42757.27 3.1788 60.38 10.8345
Total 46320.38 46320.38 0.00 42757.27      



Table of Contents

Report: Demand End Use Components Summary

For: Entire Facility

Timestamp: 2023-10-16 08:43:45

End Uses

Electricity [W] Natural Gas [W] Gasoline [W] Diesel [W] Coal [W] Fuel Oil No 1 [W] Fuel Oil No 2 [W] Propane [W] Other Fuel 1 [W] Other Fuel 2 [W] District Cooling [W] Steam [W] Water [m3/s]
Time of Peak 23-AUG-15:09 04-FEB-06:10 - - - - - - - - - - 17-APR-15:09
Heating 0.00 404990.47 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 480054.41 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 332294.83 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 778371.69 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 84450.25 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 145084.46 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 65457.65 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 98044.59 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 5613.48 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 8146.58 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                           
Total End Uses 1989371.34 413137.05 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


End Uses By Subcategory

Subcategory Electricity [W] Natural Gas [W] Gasoline [W] Diesel [W] Coal [W] Fuel Oil No 1 [W] Fuel Oil No 2 [W] Propane [W] Other Fuel 1 [W] Other Fuel 2 [W] District Cooling [W] Steam [W] Water [m3/s]
Heating General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Boiler 0.00 404990.47 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Boiler Parasitic 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling General 480054.41 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting LightsWired 332294.83 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment MiscPlug 305206.10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  DataCenterPlugLoads 473165.59 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment Transformer 5015.67 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  ElevatorLift 79171.38 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  ElevatorLightsFan 263.20 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans General 145084.46 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps General 65457.65 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection General 98044.59 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery General 5613.48 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  WaterUse 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Water Heater 0.00 8146.58 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: Source Energy End Use Components Summary

For: Entire Facility

Timestamp: 2023-10-16 08:43:45

Values gathered over 8760.00 hours



Source Energy End Use Components Summary

Source Electricity [GJ] Source Natural Gas [GJ] Source Gasoline [GJ] Source Diesel [GJ] Source Coal [GJ] Source Fuel Oil No 1 [GJ] Source Fuel Oil No 2 [GJ] Source Propane [GJ] Source Other Fuel 1 [GJ] Source Other Fuel 2 [GJ] Source District Cooling [GJ] Source District Heating [GJ]
Heating 0.00 21.77 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 21901.10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 12421.77 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 2206.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 46480.15 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 6127.46 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 7219.99 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 3100.13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 7265.82 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 3.63 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 377.13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 694.66 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Total Source Energy End Use Components 107103.18 716.43 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Normalized Metrics

Source Energy End Use Components Per Conditioned Floor Area

Source Electricity [MJ/m2] Source Natural Gas [MJ/m2] Source Gasoline [MJ/m2] Source Diesel [MJ/m2] Source Coal [MJ/m2] Source Fuel Oil No 1 [MJ/m2] Source Fuel Oil No 2 [MJ/m2] Source Propane [MJ/m2] Source Other Fuel 1 [MJ/m2] Source Other Fuel 2 [MJ/m2] Source District Cooling [MJ/m2] Source District Heating [MJ/m2]
Heating 0.00 0.47 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 472.82 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 268.17 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 47.62 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 1003.45 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 132.28 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 155.87 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 66.93 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 156.86 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.08 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 8.14 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 15.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Total Source Energy End Use Components 2312.23 15.47 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Source Energy End Use Components Per Total Floor Area

Source Electricity [MJ/m2] Source Natural Gas [MJ/m2] Source Gasoline [MJ/m2] Source Diesel [MJ/m2] Source Coal [MJ/m2] Source Fuel Oil No 1 [MJ/m2] Source Fuel Oil No 2 [MJ/m2] Source Propane [MJ/m2] Source Other Fuel 1 [MJ/m2] Source Other Fuel 2 [MJ/m2] Source District Cooling [MJ/m2] Source District Heating [MJ/m2]
Heating 0.00 0.47 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 472.82 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 268.17 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 47.62 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 1003.45 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 132.28 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 155.87 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 66.93 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 156.86 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.08 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 8.14 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 15.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Total Source Energy End Use Components 2312.23 15.47 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: Component Sizing Summary

For: Entire Facility

Timestamp: 2023-10-16 08:43:45

AirTerminal:SingleDuct:ConstantVolume:NoReheat

Design Size Maximum Air Flow Rate [m3/s]
BASEMENT DIRECT AIR 6.09
DATACENTER_BOT_ZN_6 DIRECT AIR 0.480091
DATACENTER_MID_ZN_6 DIRECT AIR 4.58
DATACENTER_TOP_ZN_6 DIRECT AIR 0.466911
DATACENTER_BASEMENT_ZN_6 DIRECT AIR 21.43
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

AirTerminal:SingleDuct:VAV:Reheat

Design Size Maximum Air Flow Rate [m3/s] Design Size Constant Minimum Air Flow Fraction User-Specified Constant Minimum Air Flow Fraction Design Size Minimum Air Flow Rate [m3/s] Design Size Maximum Flow Fraction during Reheat [] User-Specified Maximum Flow Fraction during Reheat [] Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] Design Size Maximum Reheat Water Flow Rate [m3/s] Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] Design Size Reheat Coil Sizing Inlet Air Temperature [C] Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir]
CORE_BOTTOM VAV BOX COMPONENT 6.28 0.302768 0.312000 1.96 0.807382 0.500000 0.001258 0.000172 1.96 12.80 0.008000
CORE_MID VAV BOX COMPONENT 59.39 0.320280 0.324000 19.24 0.854079 0.500000 0.001190 0.003533 19.24 12.80 0.008000
CORE_TOP VAV BOX COMPONENT 5.83 0.325985 0.337000 1.97 0.869294 0.500000 0.001169 0.000547 1.97 12.80 0.008000
PERIMETER_BOT_ZN_3 VAV BOX COMPONENT 1.11 0.215499 0.222000 0.246025 0.574664 0.500000 0.001768 0.000059 0.246025 12.80 0.008000
PERIMETER_BOT_ZN_2 VAV BOX COMPONENT 1.11 0.138653 0.200000 0.222000 0.369742 0.500000 0.002748 0.000047 0.222000 12.80 0.008000
PERIMETER_BOT_ZN_1 VAV BOX COMPONENT 1.11 0.216124 0.223000 0.246424 0.576332 0.500000 0.001763 0.000073 0.248366 12.80 0.008000
PERIMETER_BOT_ZN_4 VAV BOX COMPONENT 1.44 0.107093 0.200000 0.287424 0.300000 0.500000 0.003558 0.000041 0.287424 12.80 0.008000
PERIMETER_MID_ZN_3 VAV BOX COMPONENT 10.63 0.224739 0.227000 2.41 0.599305 0.500000 0.001695 0.001416 4.83 12.80 0.008000
PERIMETER_MID_ZN_2 VAV BOX COMPONENT 11.48 0.134041 0.200000 2.30 0.357443 0.500000 0.002842 0.000933 3.18 12.80 0.008000
PERIMETER_MID_ZN_1 VAV BOX COMPONENT 10.54 0.226650 0.229000 2.41 0.604400 0.500000 0.001681 0.001403 4.78 12.80 0.008000
PERIMETER_MID_ZN_4 VAV BOX COMPONENT 12.73 0.120852 0.200000 2.55 0.322273 0.500000 0.003153 0.000858 2.93 12.80 0.008000
PERIMETER_TOP_ZN_3 VAV BOX COMPONENT 1.18 0.202679 0.210000 0.247447 0.540478 0.500000 0.001880 0.000174 0.592454 12.80 0.008000
PERIMETER_TOP_ZN_2 VAV BOX COMPONENT 1.16 0.132343 0.200000 0.232586 0.352914 0.500000 0.002879 0.000114 0.388388 12.80 0.008000
PERIMETER_TOP_ZN_1 VAV BOX COMPONENT 1.18 0.202542 0.209000 0.246440 0.540113 0.500000 0.001881 0.000172 0.588266 12.80 0.008000
PERIMETER_TOP_ZN_4 VAV BOX COMPONENT 1.35 0.113791 0.200000 0.270504 0.303443 0.500000 0.003348 0.000108 0.368907 12.80 0.008000
User-Specified values were used. Design Size values were used if no User-Specified values were provided. Design Size values may be derived from alternate User-Specified values.

Coil:Heating:Water

Design Size Rated Capacity [W] Design Size Maximum Water Flow Rate [m3/s] Design Size U-Factor Times Area Value [W/K]
CORE_BOTTOM VAV BOX REHEAT COIL 19711.84 0.000172 397.38
CORE_MID VAV BOX REHEAT COIL 403865.23 0.003533 9127.63
CORE_TOP VAV BOX REHEAT COIL 62558.34 0.000547 1613.27
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL 6789.76 0.000059 165.89
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL 5398.09 0.000047 126.75
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL 8348.41 0.000073 220.55
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL 4712.47 0.000041 101.30
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL 161898.76 0.001416 4271.51
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL 106699.93 0.000933 2815.07
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL 160348.89 0.001403 4230.68
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL 98090.89 0.000858 2588.18
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL 19847.35 0.000174 523.53
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL 13010.56 0.000114 343.18
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL 19707.40 0.000172 519.84
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL 12359.33 0.000108 326.02
VAV_BOT WITH REHEAT HEATING COIL 15573.04 0.000136 276.83
VAV_MID WITH REHEAT HEATING COIL 94643.34 0.000828 1701.61
VAV_TOP WITH REHEAT HEATING COIL 7127.01 0.000062 128.98
CAV_BAS HEATING COIL 281575.79 0.002463 6431.56
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

AirLoopHVAC

Sum of Air Terminal Maximum Heating Flow Rates [m3/s] Sum of Air Terminal Minimum Heating Flow Rates [m3/s] Sum of Air Terminal Maximum Flow Rates [m3/s] Adjusted Heating Design Air Flow Rate [m3/s] Adjusted Cooling Design Air Flow Rate [m3/s] Adjusted Main Design Air Flow Rate [m3/s] User Heating Air Flow Ratio [] Calculated Heating Air Flow Ratio [] Design Supply Air Flow Rate [m3/s]
VAV_BOT WITH REHEAT 5.52 2.96 11.04 2.96 10.14 10.14 0.300000 0.292144 10.14
VAV_MID WITH REHEAT 52.38 28.91 104.77 28.91 95.08 95.08 0.300000 0.304071 95.08
VAV_TOP WITH REHEAT 5.35 2.96 10.71 3.75 10.29 10.29 0.300000 0.364549 10.29
CAV_BAS 6.09 6.09 6.09 6.09 6.09 6.09 1.00 1.00 6.09
AIRLOOP DATACENTER BASEMENT 21.43 21.43 21.43 21.43 21.43 21.43 1.00 0.999993 21.43
AIRLOOP DATACENTER BOT 0.480091 0.480091 0.480091 0.480091 0.480091 0.480091 1.00 1.00 0.480091
AIRLOOP DATACENTER MID 4.58 4.58 4.58 4.58 4.58 4.58 1.00 1.00 4.58
AIRLOOP DATACENTER TOP 0.466911 0.466911 0.466911 0.466911 0.466911 0.466911 1.00 1.00 0.466911
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Controller:OutdoorAir

Maximum Outdoor Air Flow Rate [m3/s] Minimum Outdoor Air Flow Rate [m3/s]
VAV_BOT WITH REHEAT_OA_CONTROLLER 10.14 2.54
VAV_MID WITH REHEAT_OA_CONTROLLER 95.08 25.38
VAV_TOP WITH REHEAT_OA_CONTROLLER 10.29 2.54
CAV_BAS_OA_CONTROLLER 6.09 1.20
AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER 21.43 0.338393
AIRLOOP DATACENTER BOT_OA_CONTROLLER 0.480091 0.015632
AIRLOOP DATACENTER MID_OA_CONTROLLER 4.58 0.156323
AIRLOOP DATACENTER TOP_OA_CONTROLLER 0.466911 0.015632
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

HeatExchanger:AirToAir:SensibleAndLatent

Design Size Nominal Supply Air Flow Rate [m3/s]
VAV_BOT WITH REHEAT OA HEAT RECOVERY 2.54
VAV_MID WITH REHEAT OA HEAT RECOVERY 25.38
VAV_TOP WITH REHEAT OA HEAT RECOVERY 2.54
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Coil:Cooling:Water

Design Size Design Inlet Air Temperature [C] Design Size Design Inlet Water Temperature [C] Design Size Design Outlet Air Temperature [C] Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] Design Size Design Coil Load [W] Design Size Design Water Flow Rate [m3/s] Design Size Design Air Flow Rate [m3/s]
VAV_BOT WITH REHEAT COOLING COIL 26.38 6.67 11.06 0.011052 0.008500 270084.32 0.011490 10.14
VAV_MID WITH REHEAT COOLING COIL 26.57 6.67 11.05 0.011352 0.008500 2643274.95 0.112451 95.08
VAV_TOP WITH REHEAT COOLING COIL 26.22 6.67 11.06 0.011015 0.008500 271050.54 0.011531 10.29
CAV_BAS COOLING COIL 24.89 6.67 11.42 0.010539 0.008500 138576.71 0.005895 6.09
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Fan:VariableVolume

Design Size Maximum Flow Rate [m3/s]
VAV_BOT WITH REHEAT FAN 10.14
VAV_MID WITH REHEAT FAN 95.08
VAV_TOP WITH REHEAT FAN 10.29
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Controller:WaterCoil

Maximum Actuated Flow [m3/s] Controller Convergence Tolerance
VAV_BOT WITH REHEAT_COOLC_CONTROLLER 0.011490 0.000041
VAV_BOT WITH REHEAT_HEATC_CONTROLLER 0.000136  
VAV_MID WITH REHEAT_COOLC_CONTROLLER 0.112451 0.000004
VAV_MID WITH REHEAT_HEATC_CONTROLLER 0.000828  
VAV_TOP WITH REHEAT_COOLC_CONTROLLER 0.011531 0.000041
VAV_TOP WITH REHEAT_HEATC_CONTROLLER 0.000062  
CAV_BAS_COOLC_CONTROLLER 0.005895 0.000081
CAV_BAS_HEATC_CONTROLLER 0.002463  
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Fan:ConstantVolume

Design Size Maximum Flow Rate [m3/s]
CAV_BAS FAN 6.09
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT

Design Size Rated Air Flow Rate [m3/s] Design Size Rated Total Cooling Capacity [W] Design Size Rated Sensible Cooling Capacity [W] Design Size Rated Water Flow Rate [m3/s]
AIRLOOP DATACENTER BASEMENT COOLING COIL 21.43 436486.14 313639.03 0.010690
AIRLOOP DATACENTER BOT COOLING COIL 0.480091 9798.88 7029.32 0.000240
AIRLOOP DATACENTER MID COOLING COIL 4.58 93691.14 67117.65 0.002294
AIRLOOP DATACENTER TOP COOLING COIL 0.466911 9544.35 6841.26 0.000234
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

AirLoopHVAC:UnitaryHeatPump:WaterToAir

Supply Air Flow Rate [m3/s] Supply Air Flow Rate During Heating Operation [m3/s] Supply Air Flow Rate During Cooling Operation [m3/s] Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] Nominal Heating Capacity [W] Nominal Cooling Capacity [W] Supplemental Heating Coil Nominal Capacity [W] Fraction of Supply Air Flow That Goes Through the Controlling Zone
AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP 21.43 21.43 21.43 21.43 436486.14 436486.14 12800.94 1.00
AIRLOOP DATACENTER BOT DXAC HEAT PUMP 0.480091 0.480091 0.480091 0.480091 9798.88 9798.88 591.35 1.00
AIRLOOP DATACENTER MID DXAC HEAT PUMP 4.58 4.58 4.58 4.58 93691.14 93691.14 5913.50 1.00
AIRLOOP DATACENTER TOP DXAC HEAT PUMP 0.466911 0.466911 0.466911 0.466911 9544.35 9544.35 591.35 1.00
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Fan:OnOff

Design Size Maximum Flow Rate [m3/s]
AIRLOOP DATACENTER BASEMENT SUPPLY FAN 21.43
AIRLOOP DATACENTER BOT SUPPLY FAN 0.480091
AIRLOOP DATACENTER MID SUPPLY FAN 4.58
AIRLOOP DATACENTER TOP SUPPLY FAN 0.466911
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT

Design Size Rated Air Flow Rate [m3/s] Design Size Rated Heating Capacity [W] Design Size Rated Water Flow Rate [m3/s]
AIRLOOP DATACENTER BASEMENT HEATING COIL 21.43 436486.14 0.010690
AIRLOOP DATACENTER BOT HEATING COIL 0.480091 9798.88 0.000240
AIRLOOP DATACENTER MID HEATING COIL 4.58 93691.14 0.002294
AIRLOOP DATACENTER TOP HEATING COIL 0.466911 9544.35 0.000234
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Coil:Heating:Electric

Design Size Nominal Capacity [W]
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL 12800.94
AIRLOOP DATACENTER BOT_SUPPHEATCOIL 591.35
AIRLOOP DATACENTER MID_SUPPHEATCOIL 5913.50
AIRLOOP DATACENTER TOP_SUPPHEATCOIL 591.35
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Humidifier:Steam:Electric

Design Size Nominal Capacity Volume [m3/s] User-Specified Nominal Capacity Volume [m3/s] Design Size Rated Power [W] User-Specified Rated Power [W]
DATACENTER_BASEMENT_ZN_6 HUMIDIFIER 0.000037 0.000037 96450.70 100000.00
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Pump:VariableSpeed

Design Flow Rate [m3/s] Design Power Consumption [W] Design Minimum Flow Rate [m3/s]
COOLSYS1 PUMP SECONDARY 0.141368 23081.00  
HEATSYS1 PUMP 0.013142 3957.94 0.000000
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

PlantLoop

Maximum Loop Flow Rate [m3/s] Plant Loop Volume [m3]
COOLSYS1_DEMAND 0.141368 16.96
HEATSYS1 0.013142 1.58
COOLSYS1_SUPPLY 0.141368 16.96
SINGLE WATER PLANT LOOP 0.013458 1.61
SWHSYS1 0.000440 0.052800
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

HeatExchanger:FluidToFluid

Loop Supply Side Design Fluid Flow Rate [m3/s] Loop Demand Side Design Fluid Flow Rate [m3/s] Heat Exchanger U-Factor Times Area Value [W/C] Loop-to-loop Temperature Difference Used to Size Heat Exchanger U-Factor Times Area Value [C]
BYPASS HEAT EXCHANGER 0.141368 0.141368 593390.45 5.60
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Boiler:HotWater

Design Size Nominal Capacity [W] User-Specified Nominal Capacity [W] Design Size Design Water Flow Rate [m3/s]
HEATSYS1 BOILER 1502266.44 1502266.44 0.013142
CENTRAL BOILER 554342.78 543702.46 0.013458
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Pump:ConstantSpeed

Design Flow Rate [m3/s] Design Power Consumption [W]
COOLSYS1 CHILLER1 PUMP 0.070684 7989.88
COOLSYS1 CHILLER2 PUMP 0.070684 7989.88
PLANT CIRC PUMP 0.013458 3432.39
SWHSYS1 PUMP 0.000440 56.21
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Chiller:Electric:ReformulatedEIR

Design Size Reference Chilled Water Flow Rate [m3/s] User-Specified Reference Chilled Water Flow Rate [m3/s] Design Size Reference Capacity [W] User-Specified Reference Capacity [W] Design Size Reference Condenser Water Flow Rate [m3/s]
COOLSYS1 CHILLER1 0.141368 0.071290 1679859.86 1687769.75 0.083521
COOLSYS1 CHILLER2 0.141368 0.071290 1679859.86 1687769.75 0.083521
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

FluidCooler:TwoSpeed

Design Water Flow Rate [m3/s] Air Flow Rate at High Fan Speed [m3/s] Fluid cooler UA value at high fan speed based on nominal capacity input [W/K] Air Flow Rate at Low Fan Speed [m3/s] Fan Power at Low Fan Speed [W] U-factor Times Area Value at Low Fan Speed [W/C]
CENTRAL TOWER 0.013458 139666.47 58635.87 69833.23 7879.72 21351.27
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

WaterHeater:Mixed

Use Side Design Flow Rate [m3/s]
SWHSYS1 WATER HEATER 0.000440
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

CondenserLoop

Maximum Loop Flow Rate [m3/s] Condenser Loop Volume [m3]
TOWERWATERSYS 0.167043 20.05
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

HeaderedPumps:VariableSpeed

Design Flow Rate [m3/s] Design Power Consumption [W]
TOWERWATERSYS PUMP 0.167043 41356.14
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

CoolingTower:VariableSpeed

Design Air Flow Rate [m3/s] Nominal Capacity [W] Air Flow Rate in free convection regime [m3/s] Tower capacity in free convection regime at design conditions [W]
TOWERWATERSYS COOLTOWER 1 64.29 2002498.32 12.86 250312.29
TOWERWATERSYS COOLTOWER 2 64.29 2002498.32 12.86 250312.29
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

PlantEquipmentOperation:ComponentSetPoint

Design Water Flow Rate [m3/s] Equipment # 47
WSHPPLANT OPERATION SCHEME 0.086752
User-Specified values were used. Design Size values were used if no User-Specified values were provided.


Table of Contents

Report: Surface Shadowing Summary

For: Entire Facility

Timestamp: 2023-10-16 08:43:45

Surfaces (Walls, Roofs, etc) that may be Shadowed by Other Surfaces

None


Subsurfaces (Windows and Doors) that may be Shadowed by Surfaces

Possible Shadow Receivers
PERIMETER_BOT_ZN_3_WALL_NORTH PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 |
PERIMETER_BOT_ZN_2_WALL_EAST PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 |
PERIMETER_BOT_ZN_1_WALL_SOUTH PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 |
PERIMETER_BOT_ZN_4_WALL_WEST PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 |
PERIMETER_MID_ZN_3_WALL_NORTH PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW |
PERIMETER_MID_ZN_2_WALL_EAST PERIMETER_MID_ZN_2_WALL_EAST_WINDOW |
PERIMETER_MID_ZN_1_WALL_SOUTH PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW |
PERIMETER_MID_ZN_4_WALL_WEST PERIMETER_MID_ZN_4_WALL_WEST_WINDOW |
PERIMETER_TOP_ZN_3_WALL_NORTH PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW |
PERIMETER_TOP_ZN_2_WALL_EAST PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW |
PERIMETER_TOP_ZN_1_WALL_SOUTH PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW |
PERIMETER_TOP_ZN_4_WALL_WEST PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW |



Table of Contents

Report: Adaptive Comfort Summary

For: Entire Facility

Timestamp: 2023-10-16 08:43:45

Time Not Meeting the Adaptive Comfort Models during Occupied Hours

ASHRAE55 90% Acceptability Limits [Hours] ASHRAE55 80% Acceptability Limits [Hours] CEN15251 Category I Acceptability Limits [Hours] CEN15251 Category II Acceptability Limits [Hours] CEN15251 Category III Acceptability Limits [Hours]



Table of Contents

Report: Initialization Summary

For: Entire Facility

Timestamp: 2023-10-16 08:43:45

Version

Version ID
1 22.1.0


Timesteps per Hour

#TimeSteps Minutes per TimeStep {minutes}
1 6 10


System Convergence Limits

Minimum System TimeStep {minutes} Max HVAC Iterations Minimum Plant Iterations Maximum Plant Iterations
1 1 20 2 8


Simulation Control

Do Zone Sizing Do System Sizing Do Plant Sizing Do Design Days Do Weather Simulation Do HVAC Sizing Simulation
1 Yes Yes Yes No Yes No


Performance Precision Tradeoffs

Use Coil Direct Simulation Zone Radiant Exchange Algorithm Override Mode Number of Timestep In Hour Force Euler Method Minimum Number of Warmup Days Force Suppress All Begin Environment Resets Minimum System Timestep MaxZoneTempDiff MaxAllowedDelTemp
1 No ScriptF Normal 6 No 1 No 1.0 0.300 2.0000E-003


Output Reporting Tolerances

Tolerance for Time Heating Setpoint Not Met Tolerance for Zone Cooling Setpoint Not Met Time
1 0.556 0.556


Site:GroundTemperature:BuildingSurface

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00


Site:GroundTemperature:FCfactorMethod

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 26.30 23.60 20.30 19.40 20.90 21.60 24.10 26.40 27.70 28.10 28.00 27.50


Site:GroundTemperature:Shallow

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00


Site:GroundTemperature:Deep

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00


Site:GroundReflectance

Jan{dimensionless} Feb{dimensionless} Mar{dimensionless} Apr{dimensionless} May{dimensionless} Jun{dimensionless} Jul{dimensionless} Aug{dimensionless} Sep{dimensionless} Oct{dimensionless} Nov{dimensionless} Dec{dimensionless}
1 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20


Site:GroundReflectance:SnowModifier

Normal Daylighting {dimensionless}
1 1.000 1.000


Site:GroundReflectance:Snow

Jan{dimensionless} Feb{dimensionless} Mar{dimensionless} Apr{dimensionless} May{dimensionless} Jun{dimensionless} Jul{dimensionless} Aug{dimensionless} Sep{dimensionless} Oct{dimensionless} Nov{dimensionless} Dec{dimensionless}
1 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20


Site:GroundReflectance:Snow:Daylighting

Jan{dimensionless} Feb{dimensionless} Mar{dimensionless} Apr{dimensionless} May{dimensionless} Jun{dimensionless} Jul{dimensionless} Aug{dimensionless} Sep{dimensionless} Oct{dimensionless} Nov{dimensionless} Dec{dimensionless}
1 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20


Environment:Weather Station

Wind Sensor Height Above Ground {m} Wind Speed Profile Exponent {} Wind Speed Profile Boundary Layer Thickness {m} Air Temperature Sensor Height Above Ground {m} Wind Speed Modifier Coefficient-Internal Temperature Modifier Coefficient-Internal
1 10.000 0.140 270.000 1.500 1.586 9.750E-003


Site:Location

Location Name Latitude {N+/S- Deg} Longitude {E+/W- Deg} Time Zone Number {GMT+/-} Elevation {m} Standard Pressure at Elevation {Pa} Standard RhoAir at Elevation
1 Miami Intl Ap FL USA TMY3 WMO#=722020 25.82 -80.30 -5.00 11.00 101193 1.2027


Site Water Mains Temperature Information

Calculation Method{} Water Mains Temperature Schedule Name{} Annual Average Outdoor Air Temperature{C} Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} Fixed Default Water Mains Temperature{C}
1 Correlation NA 24.49 8.70 NA


Building Information

Building Name North Axis {deg} Terrain Loads Convergence Tolerance Value Temperature Convergence Tolerance Value Solar Distribution Maximum Number of Warmup Days Minimum Number of Warmup Days
1 OfficeLarge 0.000 City 4.00000E-002 0.20000 FullInteriorAndExterior 25 6


Inside Convection Algorithm

Algorithm {Simple
TARP
CeilingDiffuser
AdaptiveConvectionAlgorithm}
1 TARP


Outside Convection Algorithm

Algorithm {SimpleCombined
TARP
MoWitt
DOE-2
AdaptiveConvectionAlgorithm}
1 TARP


Sky Radiance Distribution

Value {Anisotropic}
1 Anisotropic


Zone Air Solution Algorithm

Value {ThirdOrderBackwardDifference
AnalyticalSolution
EulerMethod}
1 ThirdOrderBackwardDifference


Zone Air Carbon Dioxide Balance Simulation

Simulation {Yes/No} Carbon Dioxide Concentration
1 No N/A


Zone Air Generic Contaminant Balance Simulation

Simulation {Yes/No} Generic Contaminant Concentration
1 No N/A


Zone Air Mass Flow Balance Simulation

Enforce Mass Balance



Adjust Zone Mixing and Return {AdjustMixingOnly
AdjustReturnOnly
AdjustMixingThenReturn
AdjustReturnThenMixing
None}
Adjust Zone Infiltration {AddInfiltration
AdjustInfiltration
None}

Infiltration Zones {MixingSourceZonesOnly
AllZones}


1 No N/A N/A N/A


HVACSystemRootFindingAlgorithm

Value {RegulaFalsi
Bisection
BisectionThenRegulaFalsi
RegulaFalsiThenBisection}
1 RegulaFalsi


Environment:Site Atmospheric Variation

Wind Speed Profile Exponent {} Wind Speed Profile Boundary Layer Thickness {m} Air Temperature Gradient Coefficient {K/m}
1 0.330 460.000 6.500000E-003


Surface Geometry

Starting Corner Vertex Input Direction Coordinate System Daylight Reference Point Coordinate System Rectangular (Simple) Surface Coordinate System
1 UpperLeftCorner Counterclockwise RelativeCoordinateSystem RelativeCoordinateSystem RelativeToZoneOrigin


Surface Heat Transfer Algorithm

Value {CTF - ConductionTransferFunction
EMPD - MoisturePenetrationDepthConductionTransferFunction
CondFD - ConductionFiniteDifference
HAMT - CombinedHeatAndMoistureFiniteElement} - Description
Inside Surface Max Temperature Limit{C}


Surface Convection Coefficient Lower Limit {W/m2-K}


Surface Convection Coefficient Upper Limit {W/m2-K}


1 CTF - ConductionTransferFunction 200 0.10 1000.0


Shading Summary

Number of Fixed Detached Shades Number of Building Detached Shades Number of Attached Shades
1 0 0 0


Zone Summary

Number of Zones Number of Zone Surfaces Number of SubSurfaces
1 23 221 36


Zone Information

Zone Name North Axis {deg} Origin X-Coordinate {m} Origin Y-Coordinate {m} Origin Z-Coordinate {m} Centroid X-Coordinate {m} Centroid Y-Coordinate {m} Centroid Z-Coordinate {m} Type Zone Multiplier Zone List Multiplier Minimum X {m} Maximum X {m} Minimum Y {m} Maximum Y {m} Minimum Z {m} Maximum Z {m} Ceiling Height {m} Volume {m3} Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} Floor Area {m2} Exterior Gross Wall Area {m2} Exterior Net Wall Area {m2} Exterior Window Area {m2} Number of Surfaces Number of SubSurfaces Number of Shading SubSurfaces Part of Total Building Area
1 BASEMENT 0.0 0.00 0.00 0.00 44.59 24.37 -1.22 1 1 1 16.08 73.11 0.00 48.74 -2.44 0.00 2.44 6779.02 TARP TARP 2779.43 0.00 0.00 0.00 9 0 0 Yes
2 CORE_BOTTOM 0.0 0.00 0.00 0.00 37.01 24.37 1.37 1 1 1 5.49 68.53 4.57 44.17 0.00 2.74 2.74 6849.35 TARP TARP 2496.12 0.00 0.00 0.00 7 0 0 Yes
3 CORE_MID 0.0 0.00 0.00 0.00 37.01 24.37 18.14 1 10 1 5.49 68.53 4.57 44.17 16.77 19.51 2.74 6849.35 TARP TARP 2496.12 0.00 0.00 0.00 6 0 0 Yes
4 CORE_TOP 0.0 0.00 0.00 0.00 37.01 24.37 34.91 1 1 1 5.49 68.53 4.57 44.17 33.54 36.28 2.74 6849.35 TARP TARP 2496.12 0.00 0.00 0.00 6 0 0 Yes
5 PERIMETER_BOT_ZN_3 0.0 0.00 0.00 0.00 36.55 46.54 1.37 1 1 1 0.00 73.11 44.17 48.74 0.00 2.74 2.74 860.00 TARP TARP 313.41 200.61 76.91 115.90 8 9 0 Yes
6 PERIMETER_BOT_ZN_2 0.0 0.00 0.00 0.00 70.95 24.37 1.37 1 1 1 68.53 73.11 0.00 48.74 0.00 2.74 2.74 554.22 TARP TARP 201.98 133.74 52.57 77.26 6 5 0 Yes
7 PERIMETER_BOT_ZN_1 0.0 0.00 0.00 0.00 36.55 2.20 1.37 1 1 1 0.00 73.11 0.00 4.57 0.00 2.74 2.74 860.02 TARP TARP 313.42 200.61 76.91 115.90 8 9 0 Yes
8 PERIMETER_BOT_ZN_4 0.0 0.00 0.00 0.00 2.16 24.37 1.37 1 1 1 0.00 4.57 0.00 48.74 0.00 2.74 2.74 554.22 TARP TARP 201.98 133.74 52.57 77.26 6 5 0 Yes
9 PERIMETER_MID_ZN_3 0.0 0.00 0.00 0.00 36.55 46.54 18.14 1 10 1 0.00 73.11 44.17 48.74 16.77 19.51 2.74 860.00 TARP TARP 313.41 200.61 84.71 115.90 7 1 0 Yes
10 PERIMETER_MID_ZN_2 0.0 0.00 0.00 0.00 70.95 24.37 18.14 1 10 1 68.53 73.11 0.00 48.74 16.77 19.51 2.74 554.22 TARP TARP 201.98 133.74 56.47 77.26 6 1 0 Yes
11 PERIMETER_MID_ZN_1 0.0 0.00 0.00 0.00 36.55 2.20 18.14 1 10 1 0.00 73.11 0.00 4.57 16.77 19.51 2.74 860.02 TARP TARP 313.42 200.61 84.71 115.90 7 1 0 Yes
12 PERIMETER_MID_ZN_4 0.0 0.00 0.00 0.00 2.16 24.37 18.14 1 10 1 0.00 4.57 0.00 48.74 16.77 19.51 2.74 554.22 TARP TARP 201.98 133.74 56.47 77.26 6 1 0 Yes
13 PERIMETER_TOP_ZN_3 0.0 0.00 0.00 0.00 36.55 46.54 34.91 1 1 1 0.00 73.11 44.17 48.74 33.54 36.28 2.74 860.00 TARP TARP 313.41 200.61 84.71 115.90 7 1 0 Yes
14 PERIMETER_TOP_ZN_2 0.0 0.00 0.00 0.00 70.95 24.37 34.91 1 1 1 68.53 73.11 0.00 48.74 33.54 36.28 2.74 554.22 TARP TARP 201.98 133.74 56.47 77.26 6 1 0 Yes
15 PERIMETER_TOP_ZN_1 0.0 0.00 0.00 0.00 36.55 2.20 34.91 1 1 1 0.00 73.11 0.00 4.57 33.54 36.28 2.74 860.02 TARP TARP 313.42 200.61 84.71 115.90 7 1 0 Yes
16 PERIMETER_TOP_ZN_4 0.0 0.00 0.00 0.00 2.16 24.37 34.91 1 1 1 0.00 4.57 0.00 48.74 33.54 36.28 2.74 554.22 TARP TARP 201.98 133.74 56.47 77.26 6 1 0 Yes
17 GROUNDFLOOR_PLENUM 0.0 0.00 0.00 0.00 36.55 24.37 3.35 1 1 1 0.00 73.11 0.00 48.74 2.74 3.96 1.22 4344.14 TARP TARP 3563.11 297.11 297.11 0.00 11 0 0 No
18 MIDFLOOR_PLENUM 0.0 0.00 0.00 0.00 36.55 24.37 20.12 1 10 1 0.00 73.11 0.00 48.74 19.51 20.73 1.22 4344.14 TARP TARP 3563.11 297.11 297.11 0.00 11 0 0 No
19 TOPFLOOR_PLENUM 0.0 0.00 0.00 0.00 36.55 24.37 36.89 1 1 1 0.00 73.11 0.00 48.74 36.28 37.50 1.22 4344.14 TARP TARP 3563.11 297.11 297.11 0.00 11 0 0 No
20 DATACENTER_BOT_ZN_6 0.0 5.49 44.17 0.00 5.03 24.37 1.37 1 1 1 4.57 5.49 4.57 44.17 0.00 2.74 2.74 99.34 TARP TARP 36.20 0.00 0.00 0.00 6 0 0 Yes
21 DATACENTER_MID_ZN_6 0.0 4.57 4.57 16.77 5.03 24.37 18.14 1 10 1 4.57 5.49 4.57 44.17 16.77 19.51 2.74 99.34 TARP TARP 36.20 0.00 0.00 0.00 6 0 0 Yes
22 DATACENTER_TOP_ZN_6 0.0 4.57 4.57 33.54 5.03 24.37 34.91 1 1 1 4.57 5.49 4.57 44.17 33.54 36.28 2.74 99.34 TARP TARP 36.20 0.00 0.00 0.00 6 0 0 Yes
23 DATACENTER_BASEMENT_ZN_6 0.0 16.08 0.00 -2.44 8.04 24.37 -1.22 1 1 1 0.00 16.08 0.00 48.74 -2.44 0.00 2.44 1911.37 TARP TARP 783.68 0.00 0.00 0.00 10 0 0 Yes


Zone Internal Gains Nominal

Zone Name Floor Area {m2} # Occupants Area per Occupant {m2/person} Occupant per Area {person/m2} Interior Lighting {W/m2} Electric Load {W/m2} Gas Load {W/m2} Other Load {W/m2} Hot Water Eq {W/m2} Steam Equipment {W/m2} Sum Loads per Area {W/m2} Outdoor Controlled Baseboard Heat
1 BASEMENT 2779.43 149.6 18.579 5.382E-002 10.273 4.842 0.000 0.000 0.000 0.000 15.115 No
2 CORE_BOTTOM 2496.12 134.4 18.579 5.382E-002 10.273 8.070 0.000 0.000 0.000 0.000 18.343 No
3 CORE_MID 2496.12 134.4 18.579 5.382E-002 10.273 8.070 0.000 0.000 0.000 0.000 18.343 No
4 CORE_TOP 2496.12 134.4 18.579 5.382E-002 10.273 8.070 0.000 0.000 0.000 0.000 18.343 No
5 PERIMETER_BOT_ZN_3 313.41 16.9 18.579 5.382E-002 10.273 8.070 0.000 0.000 0.000 0.000 18.343 No
6 PERIMETER_BOT_ZN_2 201.98 10.9 18.579 5.382E-002 10.273 8.070 0.000 0.000 0.000 0.000 18.343 No
7 PERIMETER_BOT_ZN_1 313.42 16.9 18.579 5.382E-002 10.273 8.070 0.000 0.000 0.000 0.000 18.343 No
8 PERIMETER_BOT_ZN_4 201.98 10.9 18.579 5.382E-002 10.273 8.070 0.000 0.000 0.000 0.000 18.343 No
9 PERIMETER_MID_ZN_3 313.41 16.9 18.579 5.382E-002 10.273 8.070 0.000 0.000 0.000 0.000 18.343 No
10 PERIMETER_MID_ZN_2 201.98 10.9 18.579 5.382E-002 10.273 8.070 0.000 0.000 0.000 0.000 18.343 No
11 PERIMETER_MID_ZN_1 313.42 16.9 18.579 5.382E-002 10.273 8.070 0.000 0.000 0.000 0.000 18.343 No
12 PERIMETER_MID_ZN_4 201.98 10.9 18.579 5.382E-002 10.273 8.070 0.000 0.000 0.000 0.000 18.343 No
13 PERIMETER_TOP_ZN_3 313.41 16.9 18.579 5.382E-002 10.273 8.070 0.000 0.000 0.000 0.000 18.343 No
14 PERIMETER_TOP_ZN_2 201.98 10.9 18.579 5.382E-002 10.273 8.070 0.000 0.000 0.000 0.000 18.343 No
15 PERIMETER_TOP_ZN_1 313.42 16.9 18.579 5.382E-002 10.273 8.070 0.000 0.000 0.000 0.000 18.343 No
16 PERIMETER_TOP_ZN_4 201.98 10.9 18.579 5.382E-002 10.273 8.070 0.000 0.000 0.000 0.000 18.343 No
17 GROUNDFLOOR_PLENUM 3563.11 0.0 N/A 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 No
18 MIDFLOOR_PLENUM 3563.11 0.0 N/A 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 No
19 TOPFLOOR_PLENUM 3563.11 0.0 N/A 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 No
20 DATACENTER_BOT_ZN_6 36.20 1.9 18.579 5.382E-002 17.873 215.299 0.000 0.000 0.000 0.000 233.173 No
21 DATACENTER_MID_ZN_6 36.20 1.9 18.579 5.382E-002 17.873 215.299 0.000 0.000 0.000 0.000 233.173 No
22 DATACENTER_TOP_ZN_6 36.20 1.9 18.579 5.382E-002 17.873 215.299 0.000 0.000 0.000 0.000 233.173 No
23 DATACENTER_BASEMENT_ZN_6 783.68 42.2 18.579 5.382E-002 10.273 484.423 0.000 0.000 0.000 0.000 494.696 No


People Internal Gains Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Number of People {} People/Floor Area {person/m2} Floor Area per person {m2/person} Fraction Radiant Fraction Convected Sensible Fraction Calculation Activity level ASHRAE 55 Warnings Carbon Dioxide Generation Rate Nominal Minimum Number of People Nominal Maximum Number of People MRT Calculation Type Work Efficiency Clothing Insulation Calculation Method Clothing Insulation Calculation Method Schedule Clothing Air Velocity Fanger Calculation Pierce Calculation KSU Calculation Cooling Effect Calculation Ankle Draft Calculation
1 DATACENTER_BOT_ZN_6 BLDG_OCC_SCH_WO_SB DATACENTER_BOT_ZN_6 36.20 1.9 1.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
2 DATACENTER_MID_ZN_6 BLDG_OCC_SCH_WO_SB DATACENTER_MID_ZN_6 36.20 1.9 1.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
3 DATACENTER_TOP_ZN_6 BLDG_OCC_SCH_WO_SB DATACENTER_TOP_ZN_6 36.20 1.9 1.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
4 DATACENTER_BASEMENT_ZN_6 BLDG_OCC_SCH_WO_SB DATACENTER_BASEMENT_ZN_6 783.68 42.2 42.2 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 42 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
5 BASEMENT BLDG_OCC_SCH_WO_SB BASEMENT 2779.43 149.6 149.6 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 150 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
6 CORE_BOTTOM BLDG_OCC_SCH_WO_SB CORE_BOTTOM 2496.12 134.4 134.4 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 134 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
7 CORE_MID BLDG_OCC_SCH_WO_SB CORE_MID 2496.12 134.4 134.4 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 134 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
8 CORE_TOP BLDG_OCC_SCH_WO_SB CORE_TOP 2496.12 134.4 134.4 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 134 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
9 PERIMETER_BOT_ZN_3 BLDG_OCC_SCH_WO_SB PERIMETER_BOT_ZN_3 313.41 16.9 16.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 17 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
10 PERIMETER_BOT_ZN_2 BLDG_OCC_SCH_WO_SB PERIMETER_BOT_ZN_2 201.98 10.9 10.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 11 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
11 PERIMETER_BOT_ZN_1 BLDG_OCC_SCH_WO_SB PERIMETER_BOT_ZN_1 313.42 16.9 16.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 17 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
12 PERIMETER_BOT_ZN_4 BLDG_OCC_SCH_WO_SB PERIMETER_BOT_ZN_4 201.98 10.9 10.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 11 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
13 PERIMETER_MID_ZN_3 BLDG_OCC_SCH_WO_SB PERIMETER_MID_ZN_3 313.41 16.9 16.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 17 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
14 PERIMETER_MID_ZN_2 BLDG_OCC_SCH_W_SB PERIMETER_MID_ZN_2 201.98 10.9 10.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 11 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
15 PERIMETER_MID_ZN_1 BLDG_OCC_SCH_WO_SB PERIMETER_MID_ZN_1 313.42 16.9 16.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 17 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
16 PERIMETER_MID_ZN_4 BLDG_OCC_SCH_WO_SB PERIMETER_MID_ZN_4 201.98 10.9 10.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 11 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
17 PERIMETER_TOP_ZN_3 BLDG_OCC_SCH_WO_SB PERIMETER_TOP_ZN_3 313.41 16.9 16.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 17 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
18 PERIMETER_TOP_ZN_2 BLDG_OCC_SCH_WO_SB PERIMETER_TOP_ZN_2 201.98 10.9 10.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 11 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
19 PERIMETER_TOP_ZN_1 BLDG_OCC_SCH_WO_SB PERIMETER_TOP_ZN_1 313.42 16.9 16.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 17 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
20 PERIMETER_TOP_ZN_4 BLDG_OCC_SCH_WO_SB PERIMETER_TOP_ZN_4 201.98 10.9 10.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 11 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No


Lights Internal Gains Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Lighting Level {W} Lights/Floor Area {W/m2} Lights per person {W/person} Fraction Return Air Fraction Radiant Fraction Short Wave Fraction Convected Fraction Replaceable End-Use Category Nominal Minimum Lighting Level {W} Nominal Maximum Lighting Level {W}
1 BASEMENT_LIGHTS LTG_SCH_OFFICE BASEMENT 2779.43 149.6 28553.717 10.273 190.864 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 28553.717
2 CORE_BOTTOM_LIGHTS LTG_SCH_OFFICE CORE_BOTTOM 2496.12 134.4 25643.245 10.273 190.864 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 25643.245
3 CORE_MID_LIGHTS LTG_SCH_OFFICE CORE_MID 2496.12 134.4 25643.245 10.273 190.864 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 25643.245
4 CORE_TOP_LIGHTS LTG_SCH_OFFICE CORE_TOP 2496.12 134.4 25643.245 10.273 190.864 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 25643.245
5 PERIMETER_BOT_ZN_3_LIGHTS LTG_SCH_OFFICE PERIMETER_BOT_ZN_3 313.41 16.9 3219.765 10.273 190.864 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 3219.765
6 PERIMETER_BOT_ZN_2_LIGHTS LTG_SCH_OFFICE PERIMETER_BOT_ZN_2 201.98 10.9 2074.939 10.273 190.864 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 2074.939
7 PERIMETER_BOT_ZN_1_LIGHTS LTG_SCH_OFFICE PERIMETER_BOT_ZN_1 313.42 16.9 3219.836 10.273 190.864 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 3219.836
8 PERIMETER_BOT_ZN_4_LIGHTS LTG_SCH_OFFICE PERIMETER_BOT_ZN_4 201.98 10.9 2074.939 10.273 190.864 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 2074.939
9 PERIMETER_MID_ZN_3_LIGHTS LTG_SCH_OFFICE PERIMETER_MID_ZN_3 313.41 16.9 3219.765 10.273 190.864 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 3219.765
10 PERIMETER_MID_ZN_2_LIGHTS LTG_SCH_OFFICE PERIMETER_MID_ZN_2 201.98 10.9 2074.939 10.273 190.864 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 2074.939
11 PERIMETER_MID_ZN_1_LIGHTS LTG_SCH_OFFICE PERIMETER_MID_ZN_1 313.42 16.9 3219.836 10.273 190.864 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 3219.836
12 PERIMETER_MID_ZN_4_LIGHTS LTG_SCH_OFFICE PERIMETER_MID_ZN_4 201.98 10.9 2074.939 10.273 190.864 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 2074.939
13 PERIMETER_TOP_ZN_3_LIGHTS LTG_SCH_OFFICE PERIMETER_TOP_ZN_3 313.41 16.9 3219.765 10.273 190.864 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 3219.765
14 PERIMETER_TOP_ZN_2_LIGHTS LTG_SCH_OFFICE PERIMETER_TOP_ZN_2 201.98 10.9 2074.939 10.273 190.864 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 2074.939
15 PERIMETER_TOP_ZN_1_LIGHTS LTG_SCH_OFFICE PERIMETER_TOP_ZN_1 313.42 16.9 3219.836 10.273 190.864 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 3219.836
16 PERIMETER_TOP_ZN_4_LIGHTS LTG_SCH_OFFICE PERIMETER_TOP_ZN_4 201.98 10.9 2074.939 10.273 190.864 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 2074.939
17 DATACENTER_BASEMENT_LIGHTS LTG_SCH_OFFICE DATACENTER_BASEMENT_ZN_6 783.68 42.2 8050.927 10.273 190.864 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 8050.927
18 DATACENTER_BOT_LIGHTS LTG_SCH_DATACENTER DATACENTER_BOT_ZN_6 36.20 1.9 647.068 17.873 332.067 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 647.068
19 DATACENTER_MID_LIGHTS LTG_SCH_DATACENTER DATACENTER_MID_ZN_6 36.20 1.9 647.068 17.873 332.067 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 647.068
20 DATACENTER_TOP_LIGHTS LTG_SCH_DATACENTER DATACENTER_TOP_ZN_6 36.20 1.9 647.068 17.873 332.067 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 647.068


ElectricEquipment Internal Gains Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Equipment Level {W} Equipment/Floor Area {W/m2} Equipment per person {W/person} Fraction Latent Fraction Radiant Fraction Lost Fraction Convected End-Use SubCategory Nominal Minimum Equipment Level {W} Nominal Maximum Equipment Level {W}
1 BASEMENT_MISCPLUG_EQUIP ALWAYS_ON BASEMENT 2779.43 149.6 13457.544 4.842 89.956 0.000 0.500 0.000 0.500 MiscPlug 13457.544 13457.544
2 CORE_BOTTOM_MISCPLUG_EQUIP BLDG_EQUIP_SCH CORE_BOTTOM 2496.12 134.4 20142.877 8.070 149.925 0.000 0.500 0.000 0.500 MiscPlug 0.000 20142.877
3 CORE_MID_MISCPLUG_EQUIP BLDG_EQUIP_SCH CORE_MID 2496.12 134.4 20142.800 8.070 149.924 0.000 0.500 0.000 0.500 MiscPlug 0.000 20142.800
4 CORE_TOP_MISCPLUG_EQUIP BLDG_EQUIP_SCH CORE_TOP 2496.12 134.4 20142.800 8.070 149.924 0.000 0.500 0.000 0.500 MiscPlug 0.000 20142.800
5 PERIMETER_BOT_ZN_3_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_BOT_ZN_3 313.41 16.9 2529.242 8.070 149.931 0.000 0.500 0.000 0.500 MiscPlug 0.000 2529.242
6 PERIMETER_BOT_ZN_2_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_BOT_ZN_2 201.98 10.9 1629.940 8.070 149.931 0.000 0.500 0.000 0.500 MiscPlug 0.000 1629.940
7 PERIMETER_BOT_ZN_1_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_BOT_ZN_1 313.42 16.9 2529.281 8.070 149.930 0.000 0.500 0.000 0.500 MiscPlug 0.000 2529.281
8 PERIMETER_BOT_ZN_4_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_BOT_ZN_4 201.98 10.9 1629.929 8.070 149.930 0.000 0.500 0.000 0.500 MiscPlug 0.000 1629.929
9 PERIMETER_MID_ZN_3_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_MID_ZN_3 313.41 16.9 2529.242 8.070 149.931 0.000 0.500 0.000 0.500 MiscPlug 0.000 2529.242
10 PERIMETER_MID_ZN_2_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_MID_ZN_2 201.98 10.9 1629.940 8.070 149.931 0.000 0.500 0.000 0.500 MiscPlug 0.000 1629.940
11 PERIMETER_MID_ZN_1_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_MID_ZN_1 313.42 16.9 2529.281 8.070 149.930 0.000 0.500 0.000 0.500 MiscPlug 0.000 2529.281
12 PERIMETER_MID_ZN_4_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_MID_ZN_4 201.98 10.9 1629.929 8.070 149.930 0.000 0.500 0.000 0.500 MiscPlug 0.000 1629.929
13 PERIMETER_TOP_ZN_3_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_TOP_ZN_3 313.41 16.9 2529.242 8.070 149.931 0.000 0.500 0.000 0.500 MiscPlug 0.000 2529.242
14 PERIMETER_TOP_ZN_2_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_TOP_ZN_2 201.98 10.9 1629.940 8.070 149.931 0.000 0.500 0.000 0.500 MiscPlug 0.000 1629.940
15 PERIMETER_TOP_ZN_1_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_TOP_ZN_1 313.42 16.9 2529.281 8.070 149.930 0.000 0.500 0.000 0.500 MiscPlug 0.000 2529.281
16 PERIMETER_TOP_ZN_4_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_TOP_ZN_4 201.98 10.9 1629.929 8.070 149.930 0.000 0.500 0.000 0.500 MiscPlug 0.000 1629.929
17 DATACENTER_BASEMENT_MISCPLUG_EQUIP DATACENTER_EQUIP_SCH DATACENTER_BASEMENT_ZN_6 783.68 42.2 379632.522 484.423 9000.000 0.000 0.100 0.000 0.900 DataCenterPlugLoads 94908.130 379632.522
18 DATACENTER_BOT_MISCPLUG_EQUIP DATACENTER_EQUIP_SCH DATACENTER_BOT_ZN_6 36.20 1.9 7794.422 215.299 4000.000 0.000 0.100 0.000 0.900 DataCenterPlugLoads 1948.606 7794.422
19 DATACENTER_MID_MISCPLUG_EQUIP DATACENTER_EQUIP_SCH DATACENTER_MID_ZN_6 36.20 1.9 7794.422 215.299 4000.000 0.000 0.100 0.000 0.900 DataCenterPlugLoads 1948.606 7794.422
20 DATACENTER_TOP_MISCPLUG_EQUIP DATACENTER_EQUIP_SCH DATACENTER_TOP_ZN_6 36.20 1.9 7794.422 215.299 4000.000 0.000 0.100 0.000 0.900 DataCenterPlugLoads 1948.606 7794.422


Construction CTF

Construction Name Index #Layers #CTFs Time Step {hours} ThermalConductance {w/m2-K} OuterThermalAbsorptance InnerThermalAbsorptance OuterSolarAbsorptance InnerSolarAbsorptance Roughness
1 SWINGING DOOR_CON 1 1 1 0.167 3.975 0.900 0.900 0.700 0.700 MediumRough
2 INTERIORFURNISHINGS 2 1 9 0.167 0.8000 0.900 0.900 0.700 0.700 MediumSmooth
3 DROPCEILING 4 1 3 0.167 4.488 0.900 0.900 0.700 0.700 MediumSmooth
4 INT_WALL 7 2 4 0.167 6.299 0.900 0.900 0.700 0.700 Smooth
5 EXT_SLAB_8IN_WITH_CARPET 8 2 7 0.167 3.285 0.900 0.900 0.700 0.700 MediumRough
6 INT_SLAB_FLOOR 12 2 7 0.167 3.839 0.900 0.900 0.700 0.700 MediumRough
7 INT_SLAB_CEILING 13 2 7 0.167 3.839 0.900 0.900 0.700 0.700 VeryRough
8 NONRES_ROOF 17 3 3 0.167 0.2832 0.750 0.900 0.450 0.700 Rough
9 NONRES_EXT_WALL_GRD 20 3 9 0.167 5.069 0.900 0.900 0.700 0.700 MediumRough
10 NONRES_EXT_WALL_MID 21 3 9 0.167 5.069 0.900 0.900 0.700 0.700 MediumRough
11 NONRES_EXT_WALL_TOP 22 3 9 0.167 5.069 0.900 0.900 0.700 0.700 MediumRough
12 BASEMENT_WALL_EAST_CFACTOR 39 2 7 0.167 0.9401 0.000 0.900 0.000 0.700 MediumRough
13 BASEMENT_WALL_SOUTH_CFACTOR 40 2 7 0.167 0.9401 0.000 0.900 0.000 0.700 MediumRough
14 BASEMENT_WALL_NORTH_CFACTOR 41 2 7 0.167 0.9401 0.000 0.900 0.000 0.700 MediumRough
15 DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR 42 2 7 0.167 0.9401 0.000 0.900 0.000 0.700 MediumRough
16 DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR 43 2 7 0.167 0.9401 0.000 0.900 0.000 0.700 MediumRough
17 DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR 44 2 7 0.167 0.9401 0.000 0.900 0.000 0.700 MediumRough


Material CTF Summary

Material Name Thickness {m} Conductivity {w/m-K} Density {kg/m3} Specific Heat {J/kg-K} ThermalResistance {m2-K/w}
1 OPAQUE DOOR PANEL_CON 0.0000 0.000 0.000 0.000 0.2516
2 STD WOOD 6INCH 0.1500 0.120 540.000 1210.000 1.250
3 AC02 ACOUSTIC CEILING 0.0127 0.057 288.000 1339.000 0.2228
4 G01 13MM GYPSUM BOARD 0.0127 0.160 800.000 1090.000 0.7937E-01
5 G01 13MM GYPSUM BOARD 0.0127 0.160 800.000 1090.000 0.7937E-01
6 200MM NORMALWEIGHT CONCRETE FLOOR 0.2032 2.310 2322.000 832.000 0.8797E-01
7 CP02 CARPET PAD 0.0000 0.000 0.000 0.000 0.2165
8 100MM NORMALWEIGHT CONCRETE FLOOR 0.1016 2.310 2322.000 832.000 0.4398E-01
9 CP02 CARPET PAD 0.0000 0.000 0.000 0.000 0.2165
10 CP02 CARPET PAD 0.0000 0.000 0.000 0.000 0.2165
11 100MM NORMALWEIGHT CONCRETE FLOOR 0.1016 2.310 2322.000 832.000 0.4398E-01
12 F13 BUILT-UP ROOFING 0.0095 0.160 1120.000 1460.000 0.5938E-01
13 NONRES_ROOF_INSULATION 0.0000 0.000 0.000 0.000 3.472
14 F08 METAL SURFACE 0.0008 45.280 7824.000 500.000 0.1767E-04
15 200MM NORMALWEIGHT CONCRETE WALL 0.2032 2.310 2322.000 832.000 0.8797E-01
16 NONRES_EXTERIOR_WALL_INSULATION_GRD 0.0000 0.000 0.000 0.000 0.2994E-01
17 G01 13MM GYPSUM BOARD 0.0127 0.160 800.000 1090.000 0.7937E-01
18 200MM NORMALWEIGHT CONCRETE WALL 0.2032 2.310 2322.000 832.000 0.8797E-01
19 NONRES_EXTERIOR_WALL_INSULATION_MID 0.0000 0.000 0.000 0.000 0.2994E-01
20 G01 13MM GYPSUM BOARD 0.0127 0.160 800.000 1090.000 0.7937E-01
21 200MM NORMALWEIGHT CONCRETE WALL 0.2032 2.310 2322.000 832.000 0.8797E-01
22 NONRES_EXTERIOR_WALL_INSULATION_TOP 0.0000 0.000 0.000 0.000 0.2994E-01
23 G01 13MM GYPSUM BOARD 0.0127 0.160 800.000 1090.000 0.7937E-01
24 ~FC_Insulation_1 0.0000 0.000 0.000 0.000 0.9868
25 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
26 ~FC_Insulation_2 0.0000 0.000 0.000 0.000 0.9868
27 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
28 ~FC_Insulation_3 0.0000 0.000 0.000 0.000 0.9868
29 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
30 ~FC_Insulation_4 0.0000 0.000 0.000 0.000 0.9868
31 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
32 ~FC_Insulation_5 0.0000 0.000 0.000 0.000 0.9868
33 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
34 ~FC_Insulation_6 0.0000 0.000 0.000 0.000 0.9868
35 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01


CTF

Time Outside Cross Inside Flux (except final one)
1 1 0.0000000 0.0000000 -0.0000000 -0.0000000
2 0 3.9747841 3.9747841 3.9747841  
3 9 -0.27580628E-02 0.97439125E-12 -0.27580628E-02 0.28516790E-03
4 8 0.73590997E-01 0.21837543E-08 0.73590997E-01 -0.77836043E-02
5 7 -0.82599318 0.23162835E-06 -0.82599318 0.89703933E-01
6 6 5.1113916 0.48671053E-05 5.1113916 -0.57224845
7 5 -19.214933 0.30163627E-04 -19.214933 2.2266322
8 4 45.557404 0.63181060E-04 45.557404 -5.4853312
9 3 -68.275533 0.44785456E-04 -68.275533 8.5710568
10 2 62.555368 0.93952058E-05 62.555368 -8.2111738
11 1 -31.904423 0.39200004E-06 -31.904423 4.3886678
12 0 6.9260389 0.77047546E-09 6.9260389  
13 3 -0.21589802E-09 0.15643069E-09 -0.21589802E-09 0.12999471E-21
14 2 0.50772448E-02 0.30006816E-02 0.50772448E-02 -0.13693132E-08
15 1 -2.5944910 1.4597758 -2.5944910 0.76344767E-02
16 0 7.0433378 2.9911476 7.0433378  
17 4 0.68458728E-09 0.26079551E-09 0.68458728E-09 -0.34507121E-18
18 3 -0.72180374E-03 0.24295686E-03 -0.72180374E-03 0.69691454E-09
19 2 0.83054762 0.27682775 0.83054762 -0.35168967E-03
20 1 -12.650482 3.3590720 -12.650482 0.19281313
21 0 16.907513 1.4507143 16.907513  
22 7 -0.18651654E-16 -0.16428647E-15 -0.26578847E-08 -0.25364002E-17
23 6 0.67402962E-01 0.99142722E-07 0.38101547E-02 -0.76639482E-03
24 5 -1.8580732 0.49502125E-04 -0.10651409 0.21891119E-01
25 4 18.220105 0.12801333E-02 1.0775450 -0.22586539
26 3 -79.928293 0.66708484E-02 -4.9803755 1.0625663
27 2 166.43177 0.75131194E-02 11.128837 -2.4125483
28 1 -159.97298 0.18548900E-02 -11.587784 2.5494418
29 0 57.057412 0.52755123E-04 4.4818272  
30 7 0.43260499E-16 0.34524919E-16 0.52793240E-17 0.0000000
31 6 0.69434179E-09 0.98085174E-11 0.18162501E-10 -0.40870994E-12
32 5 -0.12888762E-04 0.28373718E-06 -0.16918523E-06 0.92361873E-08
33 4 0.25174112E-01 0.33697681E-03 0.22646198E-03 -0.31467795E-04
34 3 -3.7600775 0.27170599E-01 -0.48495626E-01 0.94171705E-02
35 2 51.553741 0.22121684 1.2284947 -0.25833933
36 1 -128.86110 0.21944682 -5.1479470 1.1228340
37 0 81.526494 0.16043334E-01 4.4519351  
38 7 0.52793240E-17 0.34524919E-16 0.43260499E-16 0.0000000
39 6 0.18162501E-10 0.98085174E-11 0.69434179E-09 -0.40870994E-12
40 5 -0.16918523E-06 0.28373718E-06 -0.12888762E-04 0.92361873E-08
41 4 0.22646198E-03 0.33697681E-03 0.25174112E-01 -0.31467795E-04
42 3 -0.48495626E-01 0.27170599E-01 -3.7600775 0.94171705E-02
43 2 1.2284947 0.22121684 51.553741 -0.25833933
44 1 -5.1479470 0.21944682 -128.86110 1.1228340
45 0 4.4519351 0.16043334E-01 81.526494  
46 3 -0.61927053E-06 0.12767249E-08 -0.37968499E-05 0.16832131E-17
47 2 0.77611055 0.17315568E-02 1.0534842 -0.72792597E-06
48 1 -21.915918 0.11588205 -6.3286394 0.20197014
49 0 21.365777 0.10835518 5.5011278  
50 9 -0.34109306E-14 0.24909287E-15 -0.70234472E-12 0.65513238E-16
51 8 0.13119258E-09 0.66225198E-13 0.25869970E-04 -0.14916918E-11
52 7 -0.11009939E-02 0.13568249E-07 -0.65256785E-02 0.12518681E-04
53 6 0.10140049 0.81303169E-05 0.18905580 -0.11654411E-02
54 5 -2.2086417 0.46066432E-03 -2.1793248 0.26223950E-01
55 4 19.715055 0.51780401E-02 12.415669 -0.24584718
56 3 -82.671456 0.14472115E-01 -37.782151 1.1032137
57 2 168.49726 0.99923307E-02 62.094262 -2.4465849
58 1 -160.45852 0.12849016E-02 -51.628788 2.5579517
59 0 57.057407 0.91053392E-05 16.929182  
60 9 -0.34109306E-14 0.24909287E-15 -0.70234472E-12 0.65513238E-16
61 8 0.13119258E-09 0.66225198E-13 0.25869970E-04 -0.14916918E-11
62 7 -0.11009939E-02 0.13568249E-07 -0.65256785E-02 0.12518681E-04
63 6 0.10140049 0.81303169E-05 0.18905580 -0.11654411E-02
64 5 -2.2086417 0.46066432E-03 -2.1793248 0.26223950E-01
65 4 19.715055 0.51780401E-02 12.415669 -0.24584718
66 3 -82.671456 0.14472115E-01 -37.782151 1.1032137
67 2 168.49726 0.99923307E-02 62.094262 -2.4465849
68 1 -160.45852 0.12849016E-02 -51.628788 2.5579517
69 0 57.057407 0.91053392E-05 16.929182  
70 9 -0.34109306E-14 0.24909287E-15 -0.70234472E-12 0.65513238E-16
71 8 0.13119258E-09 0.66225198E-13 0.25869970E-04 -0.14916918E-11
72 7 -0.11009939E-02 0.13568249E-07 -0.65256785E-02 0.12518681E-04
73 6 0.10140049 0.81303169E-05 0.18905580 -0.11654411E-02
74 5 -2.2086417 0.46066432E-03 -2.1793248 0.26223950E-01
75 4 19.715055 0.51780401E-02 12.415669 -0.24584718
76 3 -82.671456 0.14472115E-01 -37.782151 1.1032137
77 2 168.49726 0.99923307E-02 62.094262 -2.4465849
78 1 -160.45852 0.12849016E-02 -51.628788 2.5579517
79 0 57.057407 0.91053392E-05 16.929182  
80 7 -0.41493644E-09 0.26375357E-16 0.26213203E-14 -0.63268016E-17
81 6 0.27465604E-04 0.18700671E-07 0.31288692E-02 -0.26247577E-04
82 5 -0.19935291E-02 0.11146933E-04 -0.22025565 0.19255324E-02
83 4 0.45890804E-01 0.50864553E-03 4.7717348 -0.44709298E-01
84 3 -0.40280019 0.40571884E-02 -37.694667 0.39504237
85 2 1.4296488 0.67623010E-02 115.84777 -1.4094303
86 1 -2.0629154 0.20697549E-02 -143.53273 2.0428830
87 0 1.0055995 0.48413807E-04 60.838472  
88 7 -0.41493644E-09 0.26375357E-16 0.26213203E-14 -0.63268016E-17
89 6 0.27465604E-04 0.18700671E-07 0.31288692E-02 -0.26247577E-04
90 5 -0.19935291E-02 0.11146933E-04 -0.22025565 0.19255324E-02
91 4 0.45890804E-01 0.50864553E-03 4.7717348 -0.44709298E-01
92 3 -0.40280019 0.40571884E-02 -37.694667 0.39504237
93 2 1.4296488 0.67623010E-02 115.84777 -1.4094303
94 1 -2.0629154 0.20697549E-02 -143.53273 2.0428830
95 0 1.0055995 0.48413807E-04 60.838472  
96 7 -0.41493644E-09 0.26375357E-16 0.26213203E-14 -0.63268016E-17
97 6 0.27465604E-04 0.18700671E-07 0.31288692E-02 -0.26247577E-04
98 5 -0.19935291E-02 0.11146933E-04 -0.22025565 0.19255324E-02
99 4 0.45890804E-01 0.50864553E-03 4.7717348 -0.44709298E-01
100 3 -0.40280019 0.40571884E-02 -37.694667 0.39504237
101 2 1.4296488 0.67623010E-02 115.84777 -1.4094303
102 1 -2.0629154 0.20697549E-02 -143.53273 2.0428830
103 0 1.0055995 0.48413807E-04 60.838472  
104 7 -0.41493644E-09 0.26375357E-16 0.26213203E-14 -0.63268016E-17
105 6 0.27465604E-04 0.18700671E-07 0.31288692E-02 -0.26247577E-04
106 5 -0.19935291E-02 0.11146933E-04 -0.22025565 0.19255324E-02
107 4 0.45890804E-01 0.50864553E-03 4.7717348 -0.44709298E-01
108 3 -0.40280019 0.40571884E-02 -37.694667 0.39504237
109 2 1.4296488 0.67623010E-02 115.84777 -1.4094303
110 1 -2.0629154 0.20697549E-02 -143.53273 2.0428830
111 0 1.0055995 0.48413807E-04 60.838472  
112 7 -0.41493644E-09 0.26375357E-16 0.26213203E-14 -0.63268016E-17
113 6 0.27465604E-04 0.18700671E-07 0.31288692E-02 -0.26247577E-04
114 5 -0.19935291E-02 0.11146933E-04 -0.22025565 0.19255324E-02
115 4 0.45890804E-01 0.50864553E-03 4.7717348 -0.44709298E-01
116 3 -0.40280019 0.40571884E-02 -37.694667 0.39504237
117 2 1.4296488 0.67623010E-02 115.84777 -1.4094303
118 1 -2.0629154 0.20697549E-02 -143.53273 2.0428830
119 0 1.0055995 0.48413807E-04 60.838472  
120 7 -0.41493644E-09 0.26375357E-16 0.26213203E-14 -0.63268016E-17
121 6 0.27465604E-04 0.18700671E-07 0.31288692E-02 -0.26247577E-04
122 5 -0.19935291E-02 0.11146933E-04 -0.22025565 0.19255324E-02
123 4 0.45890804E-01 0.50864553E-03 4.7717348 -0.44709298E-01
124 3 -0.40280019 0.40571884E-02 -37.694667 0.39504237
125 2 1.4296488 0.67623010E-02 115.84777 -1.4094303
126 1 -2.0629154 0.20697549E-02 -143.53273 2.0428830
127 0 1.0055995 0.48413807E-04 60.838472  


WindowConstruction

Construction Name Index #Layers Roughness Conductance {W/m2-K} Conductance (Before Adjusted) {W/m2-K} Convection Coefficient Adjustment Ratio SHGC Solar Transmittance at Normal Incidence Visible Transmittance at Normal Incidence
1 WINDOW_U_0.57_SHGC_EAST_0.25 35 1 VerySmooth 3.241 3.241 1.000 0.251    
2 WINDOW_U_0.57_SHGC_SOUTH_0.25 36 1 VerySmooth 3.241 3.241 1.000 0.251    
3 WINDOW_U_0.57_SHGC_WEST_0.25 37 1 VerySmooth 3.241 3.241 1.000 0.251    
4 WINDOW_U_0.57_SHGC_NORTH_0.25 38 1 VerySmooth 3.241 3.241 1.000 0.251    


WindowMaterial:Glazing

Material Name Optical Data Type Spectral Data Set Name Thickness {m} Solar Transmittance Front Solar Reflectance Back Solar Reflectance Visible Transmittance Front Visible Reflectance Back Visible Reflectance Infrared Transmittance Front Thermal Emissivity Back Thermal Emissivity Conductivity {W/m-K} Dirt Factor Solar Diffusing
1 GLAZING LAYER EAST SpectralAverage   2.00000E-003 0.16139 0.60205 0.60205 0.27500 0.15630 0.22588 0.00000 0.84000 0.84000 1.43763E-002 1.00000 No
2 GLAZING LAYER SOUTH SpectralAverage   2.00000E-003 0.16139 0.60205 0.60205 0.27500 0.15630 0.22588 0.00000 0.84000 0.84000 1.43763E-002 1.00000 No
3 GLAZING LAYER WEST SpectralAverage   2.00000E-003 0.16139 0.60205 0.60205 0.27500 0.15630 0.22588 0.00000 0.84000 0.84000 1.43763E-002 1.00000 No
4 GLAZING LAYER NORTH SpectralAverage   2.00000E-003 0.16139 0.60205 0.60205 0.27500 0.15630 0.22588 0.00000 0.84000 0.84000 1.43763E-002 1.00000 No


Shadowing/Sun Position Calculations Annual Simulations

Shading Calculation Method Shading Calculation Update Frequency Method Shading Calculation Update Frequency {days} Maximum Figures in Shadow Overlap Calculations {} Polygon Clipping Algorithm Pixel Counting Resolution Sky Diffuse Modeling Algorithm Output External Shading Calculation Results Disable Self-Shading Within Shading Zone Groups Disable Self-Shading From Shading Zone Groups to Other Zones
1 PolygonClipping Periodic 30 15000 SutherlandHodgman 512 SimpleSkyDiffuseModeling No No No


Enclosure/Window Adjacency Daylighting Counts

Enclosure Name Number of Exterior Windows Number of Exterior Windows in Adjacent Enclosures
1 PERIMETER_BOT_ZN_3 5 0
2 PERIMETER_BOT_ZN_2 3 0
3 PERIMETER_BOT_ZN_1 5 0
4 PERIMETER_BOT_ZN_4 3 0
5 PERIMETER_MID_ZN_3 1 0
6 PERIMETER_MID_ZN_2 1 0
7 PERIMETER_MID_ZN_1 1 0
8 PERIMETER_MID_ZN_4 1 0
9 PERIMETER_TOP_ZN_3 1 0
10 PERIMETER_TOP_ZN_2 1 0
11 PERIMETER_TOP_ZN_1 1 0
12 PERIMETER_TOP_ZN_4 1 0


Enclosure/Window Adjacency Daylighting Matrix

Enclosure Name Number of Adjacent Enclosures with Windows Adjacent Enclosure Names - 1st 100 (max)
1 PERIMETER_BOT_ZN_3 0  
2 PERIMETER_BOT_ZN_2 0  
3 PERIMETER_BOT_ZN_1 0  
4 PERIMETER_BOT_ZN_4 0  
5 PERIMETER_MID_ZN_3 0  
6 PERIMETER_MID_ZN_2 0  
7 PERIMETER_MID_ZN_1 0  
8 PERIMETER_MID_ZN_4 0  
9 PERIMETER_TOP_ZN_3 0  
10 PERIMETER_TOP_ZN_2 0  
11 PERIMETER_TOP_ZN_1 0  
12 PERIMETER_TOP_ZN_4 0  


Water Heater Information

Type Name Volume {m3} Maximum Capacity {W} Standard Rated Recovery Efficiency Standard Rated Energy Factor
1 WaterHeater:Mixed SWHSYS1 WATER HEATER 1.1356 87921.3 0.481 5.5005E-002


Surface Convection Parameters

Surface Name Outside Model Assignment Outside Area [m2] Outside Perimeter [m] Outside Height [m] Inside Model Assignment Inside Height [m] Inside Perimeter Envelope [m] Inside Hydraulic Diameter [m] Window Wall Ratio Window Location Near Radiant {Yes/No} Has Active HVAC {Yes/No}
1 BASEMENT_WALL_EAST 0 0.00 0.00 0.00 0 2.44 0.00 52.56 -999.00 0 No No
2 BASEMENT_WALL_SOUTH 0 0.00 0.00 0.00 0 2.44 0.00 52.56 -999.00 0 No No
3 BASEMENT_WALL_NORTH 0 0.00 0.00 0.00 0 2.44 0.00 52.56 -999.00 0 No No
4 BASEMENT_WALL_WEST 0 0.00 0.00 0.00 0 2.44 0.00 52.56 -999.00 0 No No
5 BASEMENT_FLOOR 0 0.00 0.00 0.00 0 2.44 0.00 52.56 -999.00 0 No No
6 PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.44 0.00 52.56 -999.00 0 No No
7 PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.44 0.00 52.56 -999.00 0 No No
8 CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.44 0.00 52.56 -999.00 0 No No
9 PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.44 0.00 52.56 -999.00 0 No No
10 BASEMENT_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.44 0.00 52.56 -999.00 0 No No
11 CORE_BOT_ZN_5_WALL_SOUTH 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
12 CORE_BOT_ZN_5_WALL_WEST 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
13 CORE_BOT_ZN_5_WALL_NORTH 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
14 CORE_BOT_ZN_5_WALL_EAST 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
15 DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
16 CORE_BOT_ZN_5_FLOOR 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
17 CORE_BOT_ZN_5_CEILING 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
18 CORE_BOTTOM_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
19 CORE_MID_ZN_5_WALL_SOUTH 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
20 CORE_MID_ZN_5_WALL_WEST 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
21 CORE_MID_ZN_5_WALL_NORTH 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
22 CORE_MID_ZN_5_WALL_EAST 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
23 CORE_MID_ZN_5_FLOOR 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
24 CORE_MID_ZN_5_CEILING 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
25 CORE_MID_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
26 CORE_TOP_ZN_5_WALL_SOUTH 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
27 CORE_TOP_ZN_5_WALL_WEST 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
28 CORE_TOP_ZN_5_WALL_NORTH 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
29 CORE_TOP_ZN_5_WALL_EAST 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
30 CORE_TOP_ZN_5_FLOOR 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
31 CORE_TOP_ZN_5_CEILING 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
32 CORE_TOP_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
33 PERIMETER_BOT_ZN_3_WALL_NORTH 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.58 3 No No
34 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.58 5 No No
35 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.58 5 No No
36 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.58 5 No No
37 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.58 5 No No
38 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.58 5 No No
39 PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.58 0 No No
40 PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.58 0 No No
41 PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.58 0 No No
42 PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.58 0 No No
43 PERIMETER_BOT_ZN_3_WALL_WEST 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
44 CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
45 PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
46 DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
47 PERIMETER_BOT_ZN_3_FLOOR 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
48 DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
49 PERIMETER_BOT_ZN_3_CEILING 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
50 PERIMETER_BOT_ZN_3_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
51 PERIMETER_BOT_ZN_2_WALL_EAST 0 579.48 250.73 37.50 0 2.74 48.74 7.58 0.58 3 No No
52 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 0 579.48 250.73 37.50 0 2.74 48.74 7.58 0.58 5 No No
53 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 0 579.48 250.73 37.50 0 2.74 48.74 7.58 0.58 5 No No
54 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 0 579.48 250.73 37.50 0 2.74 48.74 7.58 0.58 5 No No
55 PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 0 579.48 250.73 37.50 0 2.74 48.74 7.58 0.58 0 No No
56 PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 0 579.48 250.73 37.50 0 2.74 48.74 7.58 0.58 0 No No
57 PERIMETER_BOT_ZN_2_WALL_NORTH 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
58 CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
59 PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
60 PERIMETER_BOT_ZN_2_FLOOR 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
61 PERIMETER_BOT_ZN_2_CEILING 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
62 PERIMETER_BOT_ZN_2_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
63 PERIMETER_BOT_ZN_1_WALL_SOUTH 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.58 3 No No
64 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.58 5 No No
65 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.58 5 No No
66 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.58 5 No No
67 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.58 5 No No
68 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.58 5 No No
69 PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.58 0 No No
70 PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.58 0 No No
71 PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.58 0 No No
72 PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.58 0 No No
73 PERIMETER_BOT_ZN_1_WALL_EAST 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
74 DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
75 PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
76 CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
77 DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
78 PERIMETER_BOT_ZN_1_FLOOR 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
79 PERIMETER_BOT_ZN_1_CEILING 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
80 PERIMETER_BOT_ZN_1_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
81 PERIMETER_BOT_ZN_4_WALL_WEST 0 579.48 172.48 37.50 0 2.74 48.74 7.58 0.58 3 No No
82 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 0 579.48 172.48 37.50 0 2.74 48.74 7.58 0.58 5 No No
83 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 0 579.48 172.48 37.50 0 2.74 48.74 7.58 0.58 5 No No
84 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 0 579.48 172.48 37.50 0 2.74 48.74 7.58 0.58 5 No No
85 PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 0 579.48 172.48 37.50 0 2.74 48.74 7.58 0.58 0 No No
86 PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 0 579.48 172.48 37.50 0 2.74 48.74 7.58 0.58 0 No No
87 PERIMETER_BOT_ZN_4_WALL_SOUTH 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
88 DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
89 PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
90 PERIMETER_BOT_ZN_4_FLOOR 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
91 PERIMETER_BOT_ZN_4_CEILING 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
92 PERIMETER_BOT_ZN_4_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
93 PERIMETER_MID_ZN_3_WALL_NORTH 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.58 3 No No
94 PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.58 5 No No
95 PERIMETER_MID_ZN_3_WALL_WEST 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
96 CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
97 PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
98 DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
99 PERIMETER_MID_ZN_3_FLOOR 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
100 PERIMETER_MID_ZN_3_CEILING 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
101 PERIMETER_MID_ZN_3_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
102 PERIMETER_MID_ZN_2_WALL_EAST 0 579.48 250.73 37.50 0 2.74 48.74 7.58 0.58 3 No No
103 PERIMETER_MID_ZN_2_WALL_EAST_WINDOW 0 579.48 250.73 37.50 0 2.74 48.74 7.58 0.58 5 No No
104 PERIMETER_MID_ZN_2_WALL_NORTH 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
105 CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
106 PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
107 PERIMETER_MID_ZN_2_FLOOR 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
108 PERIMETER_MID_ZN_2_CEILING 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
109 PERIMETER_MID_ZN_2_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
110 PERIMETER_MID_ZN_1_WALL_EAST 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
111 PERIMETER_MID_ZN_1_WALL_SOUTH 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.58 3 No No
112 PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.58 5 No No
113 DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
114 PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
115 CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
116 PERIMETER_MID_ZN_1_FLOOR 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
117 PERIMETER_MID_ZN_1_CEILING 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
118 PERIMETER_MID_ZN_1_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
119 PERIMETER_MID_ZN_4_WALL_WEST 0 579.48 172.48 37.50 0 2.74 48.74 7.58 0.58 3 No No
120 PERIMETER_MID_ZN_4_WALL_WEST_WINDOW 0 579.48 172.48 37.50 0 2.74 48.74 7.58 0.58 5 No No
121 PERIMETER_MID_ZN_4_WALL_SOUTH 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
122 DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
123 PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
124 PERIMETER_MID_ZN_4_FLOOR 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
125 PERIMETER_MID_ZN_4_CEILING 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
126 PERIMETER_MID_ZN_4_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
127 PERIMETER_TOP_ZN_3_WALL_NORTH 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.58 3 No No
128 PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.58 5 No No
129 PERIMETER_TOP_ZN_3_WALL_WEST 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
130 CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
131 PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
132 DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
133 PERIMETER_TOP_ZN_3_FLOOR 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
134 PERIMETER_TOP_ZN_3_CEILING 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
135 PERIMETER_TOP_ZN_3_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
136 PERIMETER_TOP_ZN_2_WALL_EAST 0 579.48 250.73 37.50 0 2.74 48.74 7.58 0.58 3 No No
137 PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW 0 579.48 250.73 37.50 0 2.74 48.74 7.58 0.58 5 No No
138 PERIMETER_TOP_ZN_2_WALL_NORTH 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
139 CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
140 INT-PER3S-NE-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
141 PERIMETER_TOP_ZN_2_FLOOR 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
142 PERIMETER_TOP_ZN_2_CEILING 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
143 PERIMETER_TOP_ZN_2_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
144 PERIMETER_TOP_ZN_1_WALL_SOUTH 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.58 3 No No
145 PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.58 5 No No
146 INT-PER3S-NE 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
147 DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
148 PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
149 CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
150 PERIMETER_TOP_ZN_1_FLOOR 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
151 PERIMETER_TOP_ZN_1_CEILING 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
152 PERIMETER_TOP_ZN_1_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
153 PERIMETER_TOP_ZN_4_WALL_WEST 0 579.48 172.48 37.50 0 2.74 48.74 7.58 0.58 3 No No
154 PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW 0 579.48 172.48 37.50 0 2.74 48.74 7.58 0.58 5 No No
155 PERIMETER_TOP_ZN_4_WALL_SOUTH 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
156 DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
157 PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
158 PERIMETER_TOP_ZN_4_FLOOR 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
159 PERIMETER_TOP_ZN_4_CEILING 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
160 PERIMETER_TOP_ZN_4_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
161 GROUNDFLOOR_PLENUM_WALL_NORTH 0 869.22 250.73 37.50 0 1.22 243.69 58.49 0.00 0 No No
162 GROUNDFLOOR_PLENUM_WEST 0 579.48 172.48 37.50 0 1.22 243.69 58.49 0.00 0 No No
163 GROUNDFLOOR_PLENUM_WALL_SOUTH 0 869.22 221.21 37.50 0 1.22 243.69 58.49 0.00 0 No No
164 GROUNDFLOOR_PLENUM_WALL_EAST 0 579.48 250.73 37.50 0 1.22 243.69 58.49 0.00 0 No No
165 iz-CORE_BOT_ZN_5_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
166 iz-PERIMETER_BOT_ZN_3_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
167 iz-PERIMETER_BOT_ZN_2_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
168 iz-PERIMETER_BOT_ZN_1_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
169 iz-PERIMETER_BOT_ZN_4_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
170 iz-DATACENTER_BOT_ZN_6_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
171 GROUNDFLOOR_PLENUM_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
172 MIDFLOOR_PLENUM_WALL_NORTH 0 869.22 250.73 37.50 0 1.22 243.69 58.49 0.00 0 No No
173 MIDFLOOR_PLENUM_WALL_WEST 0 579.48 172.48 37.50 0 1.22 243.69 58.49 0.00 0 No No
174 MIDFLOOR_PLENUM_WALL_SOUTH 0 869.22 221.21 37.50 0 1.22 243.69 58.49 0.00 0 No No
175 MIDFLOOR_PLENUM_WALL_EAST 0 579.48 250.73 37.50 0 1.22 243.69 58.49 0.00 0 No No
176 iz-CORE_MID_ZN_5_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
177 iz-PERIMETER_MID_ZN_3_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
178 iz-PERIMETER_MID_ZN_2_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
179 iz-PERIMETER_MID_ZN_1_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
180 iz-PERIMETER_MID_ZN_4_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
181 iz-DATACENTER_MID_ZN_6_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
182 MIDFLOOR_PLENUM_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
183 TOPFLOOR_PLENUM_WALL_NORTH 0 869.22 221.21 37.50 0 1.22 243.69 58.49 0.00 0 No No
184 TOPFLOOR_PLENUM_WALL_EAST 0 579.48 250.73 37.50 0 1.22 243.69 58.49 0.00 0 No No
185 TOPFLOOR_PLENUM_WALL_WEST 0 579.48 172.48 37.50 0 1.22 243.69 58.49 0.00 0 No No
186 TOPFLOOR_PLENUM_WALL_SOUTH 0 869.22 250.73 37.50 0 1.22 243.69 58.49 0.00 0 No No
187 iz-CORE_TOP_ZN_5_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
188 iz-PERIMETER_TOP_ZN_3_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
189 iz-PERIMETER_TOP_ZN_2_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
190 iz-PERIMETER_TOP_ZN_1_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
191 iz-PERIMETER_TOP_ZN_4_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
192 iz-DATACENTER_TOP_ZN_6_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
193 BUILDING_ROOF 0 3563.11 268.06 0.00 0 1.22 243.69 58.49 0.00 0 No No
194 DATACENTER_BOT_ZN_6_WALL_NORTH 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
195 DATACENTER_BOT_ZN_6_WALL_SOUTH 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
196 DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
197 DATACENTER_BOT_ZN_6_WALL_WEST 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
198 DATACENTER_BOT_ZN_6_FLOOR 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
199 DATACENTER_BOT_ZN_6_CEILING 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
200 DATACENTER_MID_ZN_6_WALL_WEST 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
201 DATACENTER_MID_ZN_6_WALL_SOUTH 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
202 DATACENTER_MID_ZN_6_WALL_EAST 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
203 DATACENTER_MID_ZN_6_WALL_NORTH 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
204 DATACENTER_MID_ZN_6_FLOOR 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
205 DATACENTER_MID_ZN_6_CEILING 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
206 DATACENTER_TOP_ZN_6_WALL_EAST 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
207 DATACENTER_TOP_ZN_6_WALL_WEST 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
208 DATACENTER_TOP_ZN_6_WALL_SOUTH 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
209 DATACENTER_TOP_ZN_6_WALL_NORTH 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
210 DATACENTER_TOP_ZN_6_FLOOR 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
211 DATACENTER_TOP_ZN_6_CEILING 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
212 DATACENTER_BASEMENT_ZN_6_WALL_NORTH 0 0.00 0.00 0.00 0 2.44 0.00 24.18 -999.00 0 No No
213 DATACENTER_BASEMENT_ZN_6_WALL_SOUTH 0 0.00 0.00 0.00 0 2.44 0.00 24.18 -999.00 0 No No
214 DATACENTER_BASEMENT_ZN_6_WALL_WEST 0 0.00 0.00 0.00 0 2.44 0.00 24.18 -999.00 0 No No
215 DATACENTER_BASEMENT_ZN_6_WALL_EAST 0 0.00 0.00 0.00 0 2.44 0.00 24.18 -999.00 0 No No
216 DATACENTER_BASEMENT_ZN_6_FLOOR 0 0.00 0.00 0.00 0 2.44 0.00 24.18 -999.00 0 No No
217 DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.44 0.00 24.18 -999.00 0 No No
218 DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 0 0.00 0.00 0.00 0 2.44 0.00 24.18 -999.00 0 No No
219 PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.44 0.00 24.18 -999.00 0 No No
220 DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 0 0.00 0.00 0.00 0 2.44 0.00 24.18 -999.00 0 No No
221 DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 0 0.00 0.00 0.00 0 2.44 0.00 24.18 -999.00 0 No No


ZoneInfiltration Airflow Stats Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Design Volume Flow Rate {m3/s} Volume Flow Rate/Floor Area {m3/s-m2} Volume Flow Rate/Exterior Surface Area {m3/s-m2} ACH - Air Changes per Hour Equation A - Constant Term Coefficient {} Equation B - Temperature Term Coefficient {1/C} Equation C - Velocity Term Coefficient {s/m} Equation D - Velocity Squared Term Coefficient {s2/m2}
1 PERIMETER_BOT_ZN_3_INFILTRATION INFIL_SCH_PNNL PERIMETER_BOT_ZN_3 313.41 16.9 0.114 3.646E-004 5.482E-004 0.478 0.000 0.000 0.224 0.000
2 PERIMETER_BOT_ZN_2_INFILTRATION INFIL_SCH_PNNL PERIMETER_BOT_ZN_2 201.98 10.9 7.617E-002 3.771E-004 5.534E-004 0.495 0.000 0.000 0.224 0.000
3 PERIMETER_BOT_ZN_1_INFILTRATION INFIL_SCH_PNNL PERIMETER_BOT_ZN_1 313.42 16.9 0.114 3.646E-004 5.482E-004 0.478 0.000 0.000 0.224 0.000
4 PERIMETER_BOT_ZN_4_INFILTRATION INFIL_SCH_PNNL PERIMETER_BOT_ZN_4 201.98 10.9 7.617E-002 3.771E-004 5.534E-004 0.495 0.000 0.000 0.224 0.000
5 PERIMETER_MID_ZN_3_INFILTRATION INFIL_SCH_PNNL PERIMETER_MID_ZN_3 313.41 16.9 0.114 3.646E-004 5.696E-004 0.478 0.000 0.000 0.224 0.000
6 PERIMETER_MID_ZN_2_INFILTRATION INFIL_SCH_PNNL PERIMETER_MID_ZN_2 201.98 10.9 7.617E-002 3.771E-004 5.696E-004 0.495 0.000 0.000 0.224 0.000
7 PERIMETER_MID_ZN_1_INFILTRATION INFIL_SCH_PNNL PERIMETER_MID_ZN_1 313.42 16.9 0.114 3.646E-004 5.696E-004 0.478 0.000 0.000 0.224 0.000
8 PERIMETER_MID_ZN_4_INFILTRATION INFIL_SCH_PNNL PERIMETER_MID_ZN_4 201.98 10.9 7.617E-002 3.771E-004 5.696E-004 0.495 0.000 0.000 0.224 0.000
9 PERIMETER_TOP_ZN_3_INFILTRATION INFIL_SCH_PNNL PERIMETER_TOP_ZN_3 313.41 16.9 0.114 3.646E-004 5.696E-004 0.478 0.000 0.000 0.224 0.000
10 PERIMETER_TOP_ZN_2_INFILTRATION INFIL_SCH_PNNL PERIMETER_TOP_ZN_2 201.98 10.9 7.617E-002 3.771E-004 5.696E-004 0.495 0.000 0.000 0.224 0.000
11 PERIMETER_TOP_ZN_1_INFILTRATION INFIL_SCH_PNNL PERIMETER_TOP_ZN_1 313.42 16.9 0.114 3.646E-004 5.696E-004 0.478 0.000 0.000 0.224 0.000
12 PERIMETER_TOP_ZN_4_INFILTRATION INFIL_SCH_PNNL PERIMETER_TOP_ZN_4 201.98 10.9 7.617E-002 3.771E-004 5.696E-004 0.495 0.000 0.000 0.224 0.000
13 GROUNDFLOOR_PLENUM_INFILTRATION INFIL_SCH_PNNL GROUNDFLOOR_PLENUM 3563.11 0.0 0.169 4.749E-005 5.696E-004 0.140 0.000 0.000 0.224 0.000
14 MIDFLOOR_PLENUM_INFILTRATION INFIL_SCH_PNNL MIDFLOOR_PLENUM 3563.11 0.0 0.169 4.749E-005 5.696E-004 0.140 0.000 0.000 0.224 0.000
15 TOPFLOOR_PLENUM_INFILTRATION INFIL_SCH_PNNL TOPFLOOR_PLENUM 3563.11 0.0 0.169 4.749E-005 4.384E-005 0.140 0.000 0.000 0.224 0.000


AirFlow Model

Simple
1 Simple


RoomAir Model

Zone Name Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined
1 BASEMENT Mixing/Well-Stirred
2 CORE_BOTTOM Mixing/Well-Stirred
3 CORE_MID Mixing/Well-Stirred
4 CORE_TOP Mixing/Well-Stirred
5 PERIMETER_BOT_ZN_3 Mixing/Well-Stirred
6 PERIMETER_BOT_ZN_2 Mixing/Well-Stirred
7 PERIMETER_BOT_ZN_1 Mixing/Well-Stirred
8 PERIMETER_BOT_ZN_4 Mixing/Well-Stirred
9 PERIMETER_MID_ZN_3 Mixing/Well-Stirred
10 PERIMETER_MID_ZN_2 Mixing/Well-Stirred
11 PERIMETER_MID_ZN_1 Mixing/Well-Stirred
12 PERIMETER_MID_ZN_4 Mixing/Well-Stirred
13 PERIMETER_TOP_ZN_3 Mixing/Well-Stirred
14 PERIMETER_TOP_ZN_2 Mixing/Well-Stirred
15 PERIMETER_TOP_ZN_1 Mixing/Well-Stirred
16 PERIMETER_TOP_ZN_4 Mixing/Well-Stirred
17 GROUNDFLOOR_PLENUM Mixing/Well-Stirred
18 MIDFLOOR_PLENUM Mixing/Well-Stirred
19 TOPFLOOR_PLENUM Mixing/Well-Stirred
20 DATACENTER_BOT_ZN_6 Mixing/Well-Stirred
21 DATACENTER_MID_ZN_6 Mixing/Well-Stirred
22 DATACENTER_TOP_ZN_6 Mixing/Well-Stirred
23 DATACENTER_BASEMENT_ZN_6 Mixing/Well-Stirred


AirflowNetwork Model:Control

No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation
1 NoMultizoneOrDistribution


Zone Volume Capacitance Multiplier

Sensible Heat Capacity Multiplier Moisture Capacity Multiplier Carbon Dioxide Capacity Multiplier Generic Contaminant Capacity Multiplier
1 1.000 1.000 1.000 1.000


Load Timesteps in Zone Design Calculation Averaging Window

Value
1 6


Heating Sizing Factor Information

Sizing Factor ID Value
1 Global 1.0000


Cooling Sizing Factor Information

Sizing Factor ID Value
1 Global 1.0000


Sky Daylight Factors

Sky Type MonthAndDay Daylighting Control Name Enclosure Name Window Name Reference Point Daylight Factor
1 Clear Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 PERIMETER_BOT_ZN_1_DAYLREFPT1 3.5981E-003
2 Clear Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 PERIMETER_BOT_ZN_1_DAYLREFPT2 3.5994E-003
3 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 PERIMETER_BOT_ZN_1_DAYLREFPT1 3.7702E-003
4 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 PERIMETER_BOT_ZN_1_DAYLREFPT2 3.7713E-003
5 Intermediate Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 PERIMETER_BOT_ZN_1_DAYLREFPT1 2.9649E-003
6 Intermediate Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 PERIMETER_BOT_ZN_1_DAYLREFPT2 2.9656E-003
7 Overcast Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 PERIMETER_BOT_ZN_1_DAYLREFPT1 1.7585E-003
8 Overcast Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 PERIMETER_BOT_ZN_1_DAYLREFPT2 1.7591E-003
9 Clear Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 PERIMETER_BOT_ZN_1_DAYLREFPT1 3.6289E-003
10 Clear Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 PERIMETER_BOT_ZN_1_DAYLREFPT2 3.7146E-003
11 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 PERIMETER_BOT_ZN_1_DAYLREFPT1 3.7953E-003
12 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 PERIMETER_BOT_ZN_1_DAYLREFPT2 3.8669E-003
13 Intermediate Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 PERIMETER_BOT_ZN_1_DAYLREFPT1 2.9842E-003
14 Intermediate Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 PERIMETER_BOT_ZN_1_DAYLREFPT2 3.0407E-003
15 Overcast Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 PERIMETER_BOT_ZN_1_DAYLREFPT1 1.7734E-003
16 Overcast Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 PERIMETER_BOT_ZN_1_DAYLREFPT2 1.8107E-003
17 Clear Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 PERIMETER_BOT_ZN_1_DAYLREFPT1 8.8257E-002
18 Clear Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 PERIMETER_BOT_ZN_1_DAYLREFPT2 3.4930E-002
19 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 PERIMETER_BOT_ZN_1_DAYLREFPT1 9.5831E-002
20 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 PERIMETER_BOT_ZN_1_DAYLREFPT2 3.6319E-002
21 Intermediate Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 PERIMETER_BOT_ZN_1_DAYLREFPT1 7.1582E-002
22 Intermediate Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 PERIMETER_BOT_ZN_1_DAYLREFPT2 2.5632E-002
23 Overcast Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 PERIMETER_BOT_ZN_1_DAYLREFPT1 3.1622E-002
24 Overcast Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 PERIMETER_BOT_ZN_1_DAYLREFPT2 1.0968E-002
25 Clear Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 PERIMETER_BOT_ZN_1_DAYLREFPT1 3.6351E-003
26 Clear Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 PERIMETER_BOT_ZN_1_DAYLREFPT2 3.7442E-003
27 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 PERIMETER_BOT_ZN_1_DAYLREFPT1 3.8020E-003
28 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 PERIMETER_BOT_ZN_1_DAYLREFPT2 3.8985E-003
29 Intermediate Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 PERIMETER_BOT_ZN_1_DAYLREFPT1 2.9904E-003
30 Intermediate Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 PERIMETER_BOT_ZN_1_DAYLREFPT2 3.0642E-003
31 Overcast Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 PERIMETER_BOT_ZN_1_DAYLREFPT1 1.7738E-003
32 Overcast Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 PERIMETER_BOT_ZN_1_DAYLREFPT2 1.8117E-003
33 Clear Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 PERIMETER_BOT_ZN_1_DAYLREFPT1 3.5980E-003
34 Clear Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 PERIMETER_BOT_ZN_1_DAYLREFPT2 3.5995E-003
35 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 PERIMETER_BOT_ZN_1_DAYLREFPT1 3.7701E-003
36 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 PERIMETER_BOT_ZN_1_DAYLREFPT2 3.7714E-003
37 Intermediate Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 PERIMETER_BOT_ZN_1_DAYLREFPT1 2.9648E-003
38 Intermediate Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 PERIMETER_BOT_ZN_1_DAYLREFPT2 2.9658E-003
39 Overcast Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 PERIMETER_BOT_ZN_1_DAYLREFPT1 1.7585E-003
40 Overcast Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 PERIMETER_BOT_ZN_1_DAYLREFPT2 1.7590E-003
41 Clear Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 PERIMETER_BOT_ZN_2_DAYLREFPT1 3.8568E-003
42 Clear Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 PERIMETER_BOT_ZN_2_DAYLREFPT2 3.9960E-003
43 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 PERIMETER_BOT_ZN_2_DAYLREFPT1 3.6744E-003
44 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 PERIMETER_BOT_ZN_2_DAYLREFPT2 3.8154E-003
45 Intermediate Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 PERIMETER_BOT_ZN_2_DAYLREFPT1 3.4874E-003
46 Intermediate Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 PERIMETER_BOT_ZN_2_DAYLREFPT2 3.5631E-003
47 Overcast Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 PERIMETER_BOT_ZN_2_DAYLREFPT1 3.0071E-003
48 Overcast Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 PERIMETER_BOT_ZN_2_DAYLREFPT2 3.0329E-003
49 Clear Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 PERIMETER_BOT_ZN_2_DAYLREFPT1 4.3047E-002
50 Clear Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 PERIMETER_BOT_ZN_2_DAYLREFPT2 2.0149E-002
51 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 PERIMETER_BOT_ZN_2_DAYLREFPT1 4.0248E-002
52 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 PERIMETER_BOT_ZN_2_DAYLREFPT2 1.8190E-002
53 Intermediate Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 PERIMETER_BOT_ZN_2_DAYLREFPT1 4.0940E-002
54 Intermediate Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 PERIMETER_BOT_ZN_2_DAYLREFPT2 1.6413E-002
55 Overcast Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 PERIMETER_BOT_ZN_2_DAYLREFPT1 3.2931E-002
56 Overcast Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 PERIMETER_BOT_ZN_2_DAYLREFPT2 1.2292E-002
57 Clear Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 PERIMETER_BOT_ZN_2_DAYLREFPT1 3.8263E-003
58 Clear Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 PERIMETER_BOT_ZN_2_DAYLREFPT2 3.8870E-003
59 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 PERIMETER_BOT_ZN_2_DAYLREFPT1 3.6367E-003
60 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 PERIMETER_BOT_ZN_2_DAYLREFPT2 3.6813E-003
61 Intermediate Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 PERIMETER_BOT_ZN_2_DAYLREFPT1 3.4650E-003
62 Intermediate Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 PERIMETER_BOT_ZN_2_DAYLREFPT2 3.4837E-003
63 Overcast Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 PERIMETER_BOT_ZN_2_DAYLREFPT1 3.0072E-003
64 Overcast Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 PERIMETER_BOT_ZN_2_DAYLREFPT2 3.0333E-003
65 Clear Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 PERIMETER_BOT_ZN_3_DAYLREFPT1 1.7049E-003
66 Clear Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 PERIMETER_BOT_ZN_3_DAYLREFPT2 1.7063E-003
67 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 PERIMETER_BOT_ZN_3_DAYLREFPT1 1.4715E-003
68 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 PERIMETER_BOT_ZN_3_DAYLREFPT2 1.4727E-003
69 Intermediate Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 PERIMETER_BOT_ZN_3_DAYLREFPT1 1.3035E-003
70 Intermediate Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 PERIMETER_BOT_ZN_3_DAYLREFPT2 1.3043E-003
71 Overcast Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 PERIMETER_BOT_ZN_3_DAYLREFPT1 1.7586E-003
72 Overcast Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 PERIMETER_BOT_ZN_3_DAYLREFPT2 1.7591E-003
73 Clear Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 PERIMETER_BOT_ZN_3_DAYLREFPT1 1.7367E-003
74 Clear Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 PERIMETER_BOT_ZN_3_DAYLREFPT2 1.8149E-003
75 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 PERIMETER_BOT_ZN_3_DAYLREFPT1 1.4975E-003
76 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 PERIMETER_BOT_ZN_3_DAYLREFPT2 1.5598E-003
77 Intermediate Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 PERIMETER_BOT_ZN_3_DAYLREFPT1 1.3236E-003
78 Intermediate Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 PERIMETER_BOT_ZN_3_DAYLREFPT2 1.3675E-003
79 Overcast Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 PERIMETER_BOT_ZN_3_DAYLREFPT1 1.7738E-003
80 Overcast Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 PERIMETER_BOT_ZN_3_DAYLREFPT2 1.8118E-003
81 Clear Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 PERIMETER_BOT_ZN_3_DAYLREFPT1 2.6013E-002
82 Clear Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 PERIMETER_BOT_ZN_3_DAYLREFPT2 1.3409E-002
83 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 PERIMETER_BOT_ZN_3_DAYLREFPT1 2.0222E-002
84 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 PERIMETER_BOT_ZN_3_DAYLREFPT2 1.0283E-002
85 Intermediate Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 PERIMETER_BOT_ZN_3_DAYLREFPT1 1.7815E-002
86 Intermediate Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 PERIMETER_BOT_ZN_3_DAYLREFPT2 6.9390E-003
87 Overcast Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 PERIMETER_BOT_ZN_3_DAYLREFPT1 3.1622E-002
88 Overcast Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 PERIMETER_BOT_ZN_3_DAYLREFPT2 1.0965E-002
89 Clear Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 PERIMETER_BOT_ZN_3_DAYLREFPT1 1.7344E-003
90 Clear Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 PERIMETER_BOT_ZN_3_DAYLREFPT2 1.8116E-003
91 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 PERIMETER_BOT_ZN_3_DAYLREFPT1 1.4946E-003
92 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 PERIMETER_BOT_ZN_3_DAYLREFPT2 1.5538E-003
93 Intermediate Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 PERIMETER_BOT_ZN_3_DAYLREFPT1 1.3188E-003
94 Intermediate Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 PERIMETER_BOT_ZN_3_DAYLREFPT2 1.3529E-003
95 Overcast Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 PERIMETER_BOT_ZN_3_DAYLREFPT1 1.7735E-003
96 Overcast Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 PERIMETER_BOT_ZN_3_DAYLREFPT2 1.8107E-003
97 Clear Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 PERIMETER_BOT_ZN_3_DAYLREFPT1 1.7048E-003
98 Clear Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 PERIMETER_BOT_ZN_3_DAYLREFPT2 1.7061E-003
99 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 PERIMETER_BOT_ZN_3_DAYLREFPT1 1.4714E-003
100 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 PERIMETER_BOT_ZN_3_DAYLREFPT2 1.4725E-003
101 Intermediate Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 PERIMETER_BOT_ZN_3_DAYLREFPT1 1.3034E-003
102 Intermediate Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 PERIMETER_BOT_ZN_3_DAYLREFPT2 1.3040E-003
103 Overcast Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 PERIMETER_BOT_ZN_3_DAYLREFPT1 1.7585E-003
104 Overcast Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 PERIMETER_BOT_ZN_3_DAYLREFPT2 1.7591E-003
105 Clear Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 PERIMETER_BOT_ZN_4_DAYLREFPT1 3.3109E-003
106 Clear Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 PERIMETER_BOT_ZN_4_DAYLREFPT2 3.3741E-003
107 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 PERIMETER_BOT_ZN_4_DAYLREFPT1 3.0170E-003
108 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 PERIMETER_BOT_ZN_4_DAYLREFPT2 3.0628E-003
109 Intermediate Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 PERIMETER_BOT_ZN_4_DAYLREFPT1 2.9686E-003
110 Intermediate Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 PERIMETER_BOT_ZN_4_DAYLREFPT2 2.9855E-003
111 Overcast Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 PERIMETER_BOT_ZN_4_DAYLREFPT1 3.0073E-003
112 Overcast Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 PERIMETER_BOT_ZN_4_DAYLREFPT2 3.0334E-003
113 Clear Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 PERIMETER_BOT_ZN_4_DAYLREFPT1 3.4211E-002
114 Clear Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 PERIMETER_BOT_ZN_4_DAYLREFPT2 1.6906E-002
115 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 PERIMETER_BOT_ZN_4_DAYLREFPT1 2.9738E-002
116 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 PERIMETER_BOT_ZN_4_DAYLREFPT2 1.4346E-002
117 Intermediate Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 PERIMETER_BOT_ZN_4_DAYLREFPT1 3.1967E-002
118 Intermediate Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 PERIMETER_BOT_ZN_4_DAYLREFPT2 1.3073E-002
119 Overcast Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 PERIMETER_BOT_ZN_4_DAYLREFPT1 3.2931E-002
120 Overcast Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 PERIMETER_BOT_ZN_4_DAYLREFPT2 1.2292E-002
121 Clear Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 PERIMETER_BOT_ZN_4_DAYLREFPT1 3.3353E-003
122 Clear Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 PERIMETER_BOT_ZN_4_DAYLREFPT2 3.4471E-003
123 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 PERIMETER_BOT_ZN_4_DAYLREFPT1 3.0477E-003
124 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 PERIMETER_BOT_ZN_4_DAYLREFPT2 3.1557E-003
125 Intermediate Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 PERIMETER_BOT_ZN_4_DAYLREFPT1 2.9895E-003
126 Intermediate Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 PERIMETER_BOT_ZN_4_DAYLREFPT2 3.0563E-003
127 Overcast Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 PERIMETER_BOT_ZN_4_DAYLREFPT1 3.0071E-003
128 Overcast Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 PERIMETER_BOT_ZN_4_DAYLREFPT2 3.0328E-003
129 Clear Sky 01/21 PERIMETER_MID_ZN_1_DAYLCTRL PERIMETER_MID_ZN_1 PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW PERIMETER_MID_ZN_1_DAYLREFPT1 9.3555E-002
130 Clear Sky 01/21 PERIMETER_MID_ZN_1_DAYLCTRL PERIMETER_MID_ZN_1 PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW PERIMETER_MID_ZN_1_DAYLREFPT2 5.2004E-002
131 Clear Turbid Sky 01/21 PERIMETER_MID_ZN_1_DAYLCTRL PERIMETER_MID_ZN_1 PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW PERIMETER_MID_ZN_1_DAYLREFPT1 9.9408E-002
132 Clear Turbid Sky 01/21 PERIMETER_MID_ZN_1_DAYLCTRL PERIMETER_MID_ZN_1 PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW PERIMETER_MID_ZN_1_DAYLREFPT2 5.4102E-002
133 Intermediate Sky 01/21 PERIMETER_MID_ZN_1_DAYLCTRL PERIMETER_MID_ZN_1 PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW PERIMETER_MID_ZN_1_DAYLREFPT1 7.9737E-002
134 Intermediate Sky 01/21 PERIMETER_MID_ZN_1_DAYLCTRL PERIMETER_MID_ZN_1 PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW PERIMETER_MID_ZN_1_DAYLREFPT2 3.9538E-002
135 Overcast Sky 01/21 PERIMETER_MID_ZN_1_DAYLCTRL PERIMETER_MID_ZN_1 PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW PERIMETER_MID_ZN_1_DAYLREFPT1 3.8788E-002
136 Overcast Sky 01/21 PERIMETER_MID_ZN_1_DAYLCTRL PERIMETER_MID_ZN_1 PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW PERIMETER_MID_ZN_1_DAYLREFPT2 1.9168E-002
137 Clear Sky 01/21 PERIMETER_MID_ZN_2_DAYLCTRL PERIMETER_MID_ZN_2 PERIMETER_MID_ZN_2_WALL_EAST_WINDOW PERIMETER_MID_ZN_2_DAYLREFPT1 5.1385E-002
138 Clear Sky 01/21 PERIMETER_MID_ZN_2_DAYLCTRL PERIMETER_MID_ZN_2 PERIMETER_MID_ZN_2_WALL_EAST_WINDOW PERIMETER_MID_ZN_2_DAYLREFPT2 2.9313E-002
139 Clear Turbid Sky 01/21 PERIMETER_MID_ZN_2_DAYLCTRL PERIMETER_MID_ZN_2 PERIMETER_MID_ZN_2_WALL_EAST_WINDOW PERIMETER_MID_ZN_2_DAYLREFPT1 4.8271E-002
140 Clear Turbid Sky 01/21 PERIMETER_MID_ZN_2_DAYLCTRL PERIMETER_MID_ZN_2 PERIMETER_MID_ZN_2_WALL_EAST_WINDOW PERIMETER_MID_ZN_2_DAYLREFPT2 2.6926E-002
141 Intermediate Sky 01/21 PERIMETER_MID_ZN_2_DAYLCTRL PERIMETER_MID_ZN_2 PERIMETER_MID_ZN_2_WALL_EAST_WINDOW PERIMETER_MID_ZN_2_DAYLREFPT1 4.8767E-002
142 Intermediate Sky 01/21 PERIMETER_MID_ZN_2_DAYLCTRL PERIMETER_MID_ZN_2 PERIMETER_MID_ZN_2_WALL_EAST_WINDOW PERIMETER_MID_ZN_2_DAYLREFPT2 2.4658E-002
143 Overcast Sky 01/21 PERIMETER_MID_ZN_2_DAYLCTRL PERIMETER_MID_ZN_2 PERIMETER_MID_ZN_2_WALL_EAST_WINDOW PERIMETER_MID_ZN_2_DAYLREFPT1 3.9762E-002
144 Overcast Sky 01/21 PERIMETER_MID_ZN_2_DAYLCTRL PERIMETER_MID_ZN_2 PERIMETER_MID_ZN_2_WALL_EAST_WINDOW PERIMETER_MID_ZN_2_DAYLREFPT2 1.9389E-002
145 Clear Sky 01/21 PERIMETER_MID_ZN_3_DAYLCTRL PERIMETER_MID_ZN_3 PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW PERIMETER_MID_ZN_3_DAYLREFPT1 3.2812E-002
146 Clear Sky 01/21 PERIMETER_MID_ZN_3_DAYLCTRL PERIMETER_MID_ZN_3 PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW PERIMETER_MID_ZN_3_DAYLREFPT2 2.1602E-002
147 Clear Turbid Sky 01/21 PERIMETER_MID_ZN_3_DAYLCTRL PERIMETER_MID_ZN_3 PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW PERIMETER_MID_ZN_3_DAYLREFPT1 2.6218E-002
148 Clear Turbid Sky 01/21 PERIMETER_MID_ZN_3_DAYLCTRL PERIMETER_MID_ZN_3 PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW PERIMETER_MID_ZN_3_DAYLREFPT2 1.7302E-002
149 Intermediate Sky 01/21 PERIMETER_MID_ZN_3_DAYLCTRL PERIMETER_MID_ZN_3 PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW PERIMETER_MID_ZN_3_DAYLREFPT1 2.3491E-002
150 Intermediate Sky 01/21 PERIMETER_MID_ZN_3_DAYLCTRL PERIMETER_MID_ZN_3 PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW PERIMETER_MID_ZN_3_DAYLREFPT2 1.3046E-002
151 Overcast Sky 01/21 PERIMETER_MID_ZN_3_DAYLCTRL PERIMETER_MID_ZN_3 PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW PERIMETER_MID_ZN_3_DAYLREFPT1 3.8788E-002
152 Overcast Sky 01/21 PERIMETER_MID_ZN_3_DAYLCTRL PERIMETER_MID_ZN_3 PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW PERIMETER_MID_ZN_3_DAYLREFPT2 1.9165E-002
153 Clear Sky 01/21 PERIMETER_MID_ZN_4_DAYLCTRL PERIMETER_MID_ZN_4 PERIMETER_MID_ZN_4_WALL_WEST_WINDOW PERIMETER_MID_ZN_4_DAYLREFPT1 4.1362E-002
154 Clear Sky 01/21 PERIMETER_MID_ZN_4_DAYLCTRL PERIMETER_MID_ZN_4 PERIMETER_MID_ZN_4_WALL_WEST_WINDOW PERIMETER_MID_ZN_4_DAYLREFPT2 2.4798E-002
155 Clear Turbid Sky 01/21 PERIMETER_MID_ZN_4_DAYLCTRL PERIMETER_MID_ZN_4 PERIMETER_MID_ZN_4_WALL_WEST_WINDOW PERIMETER_MID_ZN_4_DAYLREFPT1 3.6335E-002
156 Clear Turbid Sky 01/21 PERIMETER_MID_ZN_4_DAYLCTRL PERIMETER_MID_ZN_4 PERIMETER_MID_ZN_4_WALL_WEST_WINDOW PERIMETER_MID_ZN_4_DAYLREFPT2 2.1553E-002
157 Intermediate Sky 01/21 PERIMETER_MID_ZN_4_DAYLCTRL PERIMETER_MID_ZN_4 PERIMETER_MID_ZN_4_WALL_WEST_WINDOW PERIMETER_MID_ZN_4_DAYLREFPT1 3.8675E-002
158 Intermediate Sky 01/21 PERIMETER_MID_ZN_4_DAYLCTRL PERIMETER_MID_ZN_4 PERIMETER_MID_ZN_4_WALL_WEST_WINDOW PERIMETER_MID_ZN_4_DAYLREFPT2 2.0128E-002
159 Overcast Sky 01/21 PERIMETER_MID_ZN_4_DAYLCTRL PERIMETER_MID_ZN_4 PERIMETER_MID_ZN_4_WALL_WEST_WINDOW PERIMETER_MID_ZN_4_DAYLREFPT1 3.9762E-002
160 Overcast Sky 01/21 PERIMETER_MID_ZN_4_DAYLCTRL PERIMETER_MID_ZN_4 PERIMETER_MID_ZN_4_WALL_WEST_WINDOW PERIMETER_MID_ZN_4_DAYLREFPT2 1.9389E-002
161 Clear Sky 01/21 PERIMETER_TOP_ZN_1_DAYLCTRL PERIMETER_TOP_ZN_1 PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW PERIMETER_TOP_ZN_1_DAYLREFPT1 9.3681E-002
162 Clear Sky 01/21 PERIMETER_TOP_ZN_1_DAYLCTRL PERIMETER_TOP_ZN_1 PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW PERIMETER_TOP_ZN_1_DAYLREFPT2 5.2114E-002
163 Clear Turbid Sky 01/21 PERIMETER_TOP_ZN_1_DAYLCTRL PERIMETER_TOP_ZN_1 PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW PERIMETER_TOP_ZN_1_DAYLREFPT1 9.9560E-002
164 Clear Turbid Sky 01/21 PERIMETER_TOP_ZN_1_DAYLCTRL PERIMETER_TOP_ZN_1 PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW PERIMETER_TOP_ZN_1_DAYLREFPT2 5.4224E-002
165 Intermediate Sky 01/21 PERIMETER_TOP_ZN_1_DAYLCTRL PERIMETER_TOP_ZN_1 PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW PERIMETER_TOP_ZN_1_DAYLREFPT1 7.9889E-002
166 Intermediate Sky 01/21 PERIMETER_TOP_ZN_1_DAYLCTRL PERIMETER_TOP_ZN_1 PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW PERIMETER_TOP_ZN_1_DAYLREFPT2 3.9636E-002
167 Overcast Sky 01/21 PERIMETER_TOP_ZN_1_DAYLCTRL PERIMETER_TOP_ZN_1 PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW PERIMETER_TOP_ZN_1_DAYLREFPT1 3.8871E-002
168 Overcast Sky 01/21 PERIMETER_TOP_ZN_1_DAYLCTRL PERIMETER_TOP_ZN_1 PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW PERIMETER_TOP_ZN_1_DAYLREFPT2 1.9210E-002
169 Clear Sky 01/21 PERIMETER_TOP_ZN_2_DAYLCTRL PERIMETER_TOP_ZN_2 PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW PERIMETER_TOP_ZN_2_DAYLREFPT1 5.1435E-002
170 Clear Sky 01/21 PERIMETER_TOP_ZN_2_DAYLCTRL PERIMETER_TOP_ZN_2 PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW PERIMETER_TOP_ZN_2_DAYLREFPT2 2.9360E-002
171 Clear Turbid Sky 01/21 PERIMETER_TOP_ZN_2_DAYLCTRL PERIMETER_TOP_ZN_2 PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW PERIMETER_TOP_ZN_2_DAYLREFPT1 4.8328E-002
172 Clear Turbid Sky 01/21 PERIMETER_TOP_ZN_2_DAYLCTRL PERIMETER_TOP_ZN_2 PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW PERIMETER_TOP_ZN_2_DAYLREFPT2 2.6971E-002
173 Intermediate Sky 01/21 PERIMETER_TOP_ZN_2_DAYLCTRL PERIMETER_TOP_ZN_2 PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW PERIMETER_TOP_ZN_2_DAYLREFPT1 4.8852E-002
174 Intermediate Sky 01/21 PERIMETER_TOP_ZN_2_DAYLCTRL PERIMETER_TOP_ZN_2 PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW PERIMETER_TOP_ZN_2_DAYLREFPT2 2.4711E-002
175 Overcast Sky 01/21 PERIMETER_TOP_ZN_2_DAYLCTRL PERIMETER_TOP_ZN_2 PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW PERIMETER_TOP_ZN_2_DAYLREFPT1 3.9845E-002
176 Overcast Sky 01/21 PERIMETER_TOP_ZN_2_DAYLCTRL PERIMETER_TOP_ZN_2 PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW PERIMETER_TOP_ZN_2_DAYLREFPT2 1.9432E-002
177 Clear Sky 01/21 PERIMETER_TOP_ZN_3_DAYLCTRL PERIMETER_TOP_ZN_3 PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW PERIMETER_TOP_ZN_3_DAYLREFPT1 3.2819E-002
178 Clear Sky 01/21 PERIMETER_TOP_ZN_3_DAYLCTRL PERIMETER_TOP_ZN_3 PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW PERIMETER_TOP_ZN_3_DAYLREFPT2 2.1627E-002
179 Clear Turbid Sky 01/21 PERIMETER_TOP_ZN_3_DAYLCTRL PERIMETER_TOP_ZN_3 PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW PERIMETER_TOP_ZN_3_DAYLREFPT1 2.6227E-002
180 Clear Turbid Sky 01/21 PERIMETER_TOP_ZN_3_DAYLCTRL PERIMETER_TOP_ZN_3 PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW PERIMETER_TOP_ZN_3_DAYLREFPT2 1.7322E-002
181 Intermediate Sky 01/21 PERIMETER_TOP_ZN_3_DAYLCTRL PERIMETER_TOP_ZN_3 PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW PERIMETER_TOP_ZN_3_DAYLREFPT1 2.3529E-002
182 Intermediate Sky 01/21 PERIMETER_TOP_ZN_3_DAYLCTRL PERIMETER_TOP_ZN_3 PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW PERIMETER_TOP_ZN_3_DAYLREFPT2 1.3069E-002
183 Overcast Sky 01/21 PERIMETER_TOP_ZN_3_DAYLCTRL PERIMETER_TOP_ZN_3 PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW PERIMETER_TOP_ZN_3_DAYLREFPT1 3.8871E-002
184 Overcast Sky 01/21 PERIMETER_TOP_ZN_3_DAYLCTRL PERIMETER_TOP_ZN_3 PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW PERIMETER_TOP_ZN_3_DAYLREFPT2 1.9207E-002
185 Clear Sky 01/21 PERIMETER_TOP_ZN_4_DAYLCTRL PERIMETER_TOP_ZN_4 PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW PERIMETER_TOP_ZN_4_DAYLREFPT1 4.1391E-002
186 Clear Sky 01/21 PERIMETER_TOP_ZN_4_DAYLCTRL PERIMETER_TOP_ZN_4 PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW PERIMETER_TOP_ZN_4_DAYLREFPT2 2.4833E-002
187 Clear Turbid Sky 01/21 PERIMETER_TOP_ZN_4_DAYLCTRL PERIMETER_TOP_ZN_4 PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW PERIMETER_TOP_ZN_4_DAYLREFPT1 3.6366E-002
188 Clear Turbid Sky 01/21 PERIMETER_TOP_ZN_4_DAYLCTRL PERIMETER_TOP_ZN_4 PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW PERIMETER_TOP_ZN_4_DAYLREFPT2 2.1584E-002
189 Intermediate Sky 01/21 PERIMETER_TOP_ZN_4_DAYLCTRL PERIMETER_TOP_ZN_4 PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW PERIMETER_TOP_ZN_4_DAYLREFPT1 3.8739E-002
190 Intermediate Sky 01/21 PERIMETER_TOP_ZN_4_DAYLCTRL PERIMETER_TOP_ZN_4 PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW PERIMETER_TOP_ZN_4_DAYLREFPT2 2.0168E-002
191 Overcast Sky 01/21 PERIMETER_TOP_ZN_4_DAYLCTRL PERIMETER_TOP_ZN_4 PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW PERIMETER_TOP_ZN_4_DAYLREFPT1 3.9845E-002
192 Overcast Sky 01/21 PERIMETER_TOP_ZN_4_DAYLCTRL PERIMETER_TOP_ZN_4 PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW PERIMETER_TOP_ZN_4_DAYLREFPT2 1.9432E-002


Zone Sizing Information

Zone Name Load Type Calc Des Load {W} User Des Load {W} Calc Des Air Flow Rate {m3/s} User Des Air Flow Rate {m3/s} Design Day Name Date/Time of Peak Temperature at Peak {C} Humidity Ratio at Peak {kgWater/kgDryAir} Floor Area {m2} # Occupants Calc Outdoor Air Flow Rate {m3/s} Calc DOAS Heat Addition Rate {W}
1 BASEMENT Cooling 84401.13308 84401.13308 6.08554 6.08554 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 28.24200 1.71578E-002 2779.42662 149.60210 1.20016 0.00000
2 BASEMENT Heating 0.00000 0.00000 0.00000 1.20016   00:10:00 8.70000 6.99286E-003 2779.42662 149.60210 1.20016 0.00000
3 CORE_BOTTOM Cooling 87138.27798 87138.27798 6.28218 6.28218 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 28.24200 1.71578E-002 2496.12046 134.35320 1.07782 0.00000
4 CORE_BOTTOM Heating 0.00000 0.00000 0.00000 1.07782   00:10:00 8.70000 6.99286E-003 2496.12046 134.35320 1.07782 0.00000
5 CORE_MID Cooling 823926.45425 823926.45425 59.38696 59.38696 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 28.24200 1.71578E-002 2496.12046 134.35320 10.77825 0.00000
6 CORE_MID Heating 210357.20338 210357.20338 8.85854 10.77825 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 8.70000 6.99286E-003 2496.12046 134.35320 10.77825 0.00000
7 CORE_TOP Cooling 80953.61020 80953.61020 5.83476 5.83476 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 28.24200 1.71578E-002 2496.12046 134.35320 1.07782 0.00000
8 CORE_TOP Heating 42783.39819 42783.39819 1.81459 1.81459 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 8.70000 6.99286E-003 2496.12046 134.35320 1.07782 0.00000
9 PERIMETER_BOT_ZN_3 Cooling 15234.01961 15234.01961 1.10822 1.10822 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 17:30:00 31.92700 1.71648E-002 313.41284 16.86939 0.13533 0.00000
10 PERIMETER_BOT_ZN_3 Heating 4317.02215 4317.02215 0.18275 0.18275 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 8.70000 6.99286E-003 313.41284 16.86939 0.13533 0.00000
11 PERIMETER_BOT_ZN_2 Cooling 15258.57388 15258.57388 1.11000 1.11000 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 09:40:00 30.27433 1.71616E-002 201.97515 10.87127 8.72129E-002 0.00000
12 PERIMETER_BOT_ZN_2 Heating 3166.69443 3166.69443 0.13424 0.13424 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 8.70000 6.99286E-003 201.97515 10.87127 8.72129E-002 0.00000
13 PERIMETER_BOT_ZN_1 Cooling 15190.27594 15190.27594 1.10504 1.10504 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 14:10:00 33.20000 1.71672E-002 313.41969 16.86975 0.13533 0.00000
14 PERIMETER_BOT_ZN_1 Heating 5851.73878 5851.73878 0.24837 0.24837 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 8.70000 6.99286E-003 313.41969 16.86975 0.13533 0.00000
15 PERIMETER_BOT_ZN_4 Cooling 19755.40458 19755.40458 1.43712 1.43712 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 17:00:00 32.26200 1.71654E-002 201.97515 10.87127 8.72129E-002 0.00000
16 PERIMETER_BOT_ZN_4 Heating 1824.37840 1824.37840 7.69994E-002 8.72129E-002 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 8.70000 6.99286E-003 201.97515 10.87127 8.72129E-002 0.00000
17 PERIMETER_MID_ZN_3 Cooling 146063.19737 146063.19737 10.62656 10.62656 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 17:40:00 31.81533 1.71646E-002 313.41284 16.86939 1.35332 0.00000
18 PERIMETER_MID_ZN_3 Heating 113335.61067 113335.61067 4.83028 4.83028 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 8.70000 6.99286E-003 313.41284 16.86939 1.35332 0.00000
19 PERIMETER_MID_ZN_2 Cooling 157821.56589 157821.56589 11.48194 11.48194 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 09:50:00 30.46417 1.71620E-002 201.97515 10.87127 0.87213 0.00000
20 PERIMETER_MID_ZN_2 Heating 74692.14290 74692.14290 3.18361 3.18361 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 8.70000 6.99286E-003 201.97515 10.87127 0.87213 0.00000
21 PERIMETER_MID_ZN_1 Cooling 144835.12005 144835.12005 10.53721 10.53721 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 14:30:00 33.20000 1.71672E-002 313.41969 16.86975 1.35335 0.00000
22 PERIMETER_MID_ZN_1 Heating 112252.17766 112252.17766 4.78391 4.78391 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 8.70000 6.99286E-003 313.41969 16.86975 1.35335 0.00000
23 PERIMETER_MID_ZN_4 Cooling 175045.27115 175045.27115 12.73497 12.73497 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 17:10:00 32.15033 1.71652E-002 201.97515 10.87127 0.87213 0.00000
24 PERIMETER_MID_ZN_4 Heating 68672.55571 68672.55571 2.92617 2.92617 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 8.70000 6.99286E-003 201.97515 10.87127 0.87213 0.00000
25 PERIMETER_TOP_ZN_3 Cooling 16195.56100 16195.56100 1.17832 1.17832 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 17:00:00 32.26200 1.71654E-002 313.41284 16.86939 0.13533 0.00000
26 PERIMETER_TOP_ZN_3 Heating 13890.67886 13890.67886 0.59245 0.59245 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 8.70000 6.99286E-003 313.41284 16.86939 0.13533 0.00000
27 PERIMETER_TOP_ZN_2 Cooling 15984.07537 15984.07537 1.16293 1.16293 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 10:00:00 30.65400 1.71624E-002 201.97515 10.87127 8.72129E-002 0.00000
28 PERIMETER_TOP_ZN_2 Heating 9105.62901 9105.62901 0.38839 0.38839 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 8.70000 6.99286E-003 201.97515 10.87127 8.72129E-002 0.00000
29 PERIMETER_TOP_ZN_1 Cooling 16206.86265 16206.86265 1.17914 1.17914 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 14:40:00 33.20000 1.71672E-002 313.41969 16.86975 0.13533 0.00000
30 PERIMETER_TOP_ZN_1 Heating 13792.84855 13792.84855 0.58827 0.58827 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 8.70000 6.99286E-003 313.41969 16.86975 0.13533 0.00000
31 PERIMETER_TOP_ZN_4 Cooling 18590.08459 18590.08459 1.35252 1.35252 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 17:00:00 32.26200 1.71654E-002 201.97515 10.87127 8.72129E-002 0.00000
32 PERIMETER_TOP_ZN_4 Heating 8650.33248 8650.33248 0.36891 0.36891 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 8.70000 6.99286E-003 201.97515 10.87127 8.72129E-002 0.00000
33 DATACENTER_BOT_ZN_6 Cooling 8367.75144 8367.75144 0.48009 0.48009 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 18:50:00 30.75450 1.71626E-002 36.20274 1.94861 1.56323E-002 0.00000
34 DATACENTER_BOT_ZN_6 Heating 0.00000 0.00000 0.00000 1.56323E-002   00:10:00 8.70000 6.99286E-003 36.20274 1.94861 1.56323E-002 0.00000
35 DATACENTER_MID_ZN_6 Cooling 79797.70584 79797.70584 4.57834 4.57834 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 18:50:00 30.75450 1.71626E-002 36.20274 1.94861 0.15632 0.00000
36 DATACENTER_MID_ZN_6 Heating 0.00000 0.00000 0.00000 0.15632   00:10:00 8.70000 6.99286E-003 36.20274 1.94861 0.15632 0.00000
37 DATACENTER_TOP_ZN_6 Cooling 8138.00445 8138.00445 0.46691 0.46691 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 18:40:00 30.92200 1.71629E-002 36.20274 1.94861 1.56323E-002 0.00000
38 DATACENTER_TOP_ZN_6 Heating 0.00000 0.00000 0.00000 1.56323E-002   00:10:00 8.70000 6.99286E-003 36.20274 1.94861 1.56323E-002 0.00000
39 DATACENTER_BASEMENT_ZN_6 Cooling 373513.38396 373513.38396 21.42960 21.42960 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 07:00:00 27.10300 1.71556E-002 783.67941 42.18139 0.33839 0.00000
40 DATACENTER_BASEMENT_ZN_6 Heating 0.00000 0.00000 0.00000 0.33839   00:10:00 8.70000 6.99286E-003 783.67941 42.18139 0.33839 0.00000


System Sizing Information

System Name Load Type Peak Load Kind User Design Capacity Calc Des Air Flow Rate [m3/s] User Des Air Flow Rate [m3/s] Design Day Name Date/Time of Peak
1 VAV_BOT WITH REHEAT Cooling Sensible 159633.71 10.13854 10.13854 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 00:00:00
2 VAV_BOT WITH REHEAT Heating Sensible 8574.42 1.73039 1.73039 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00
3 VAV_MID WITH REHEAT Cooling Sensible 1478661.17 95.07637 95.07637 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 00:00:00
4 VAV_MID WITH REHEAT Heating Sensible 125073.25 26.50222 26.50222 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:30:00
5 VAV_TOP WITH REHEAT Cooling Sensible 166479.01 10.29385 10.29385 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 00:00:00
6 VAV_TOP WITH REHEAT Heating Sensible 12533.24 3.75261 3.75261 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 13:30:00
7 CAV_BAS Cooling Sensible 88889.27 6.08554 6.08554 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 05:00:00
8 CAV_BAS Heating Sensible 45400.28 1.20016 1.20016 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 00:10:00
9 AIRLOOP DATACENTER BASEMENT Cooling Sensible 369754.24 21.42976 21.42976 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 05:00:00
10 AIRLOOP DATACENTER BASEMENT Heating Sensible 12800.94 0.33839 0.33839 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 00:10:00
11 AIRLOOP DATACENTER BOT Cooling Sensible 8311.65 0.48009 0.48009 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 05:00:00
12 AIRLOOP DATACENTER BOT Heating Sensible 591.35 1.56323E-002 1.56323E-002 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 00:10:00
13 AIRLOOP DATACENTER MID Cooling Sensible 79277.73 4.57834 4.57834 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 05:00:00
14 AIRLOOP DATACENTER MID Heating Sensible 5913.50 0.15632 0.15632 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 00:10:00
15 AIRLOOP DATACENTER TOP Cooling Sensible 8086.29 0.46691 0.46691 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 05:00:00
16 AIRLOOP DATACENTER TOP Heating Sensible 591.35 1.56323E-002 1.56323E-002 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 00:10:00


Component Sizing Information

Component Type Component Name Input Field Description Value
1 AirTerminal:SingleDuct:ConstantVolume:NoReheat BASEMENT DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 6.08554
2 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 6.28218
3 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.30277
4 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.31200
5 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 1.96004
6 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.80738
7 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
8 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.25839E-003
9 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.72448E-004
10 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 1.96004
11 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
12 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
13 Coil:Heating:Water CORE_BOTTOM VAV BOX REHEAT COIL Design Size Rated Capacity [W] 19711.84217
14 Coil:Heating:Water CORE_BOTTOM VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.72448E-004
15 Coil:Heating:Water CORE_BOTTOM VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 397.37527
16 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 59.38696
17 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.32028
18 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.32400
19 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 19.24138
20 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.85408
21 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
22 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.18959E-003
23 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 3.53319E-003
24 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 19.24138
25 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
26 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
27 Coil:Heating:Water CORE_MID VAV BOX REHEAT COIL Design Size Rated Capacity [W] 403865.23068
28 Coil:Heating:Water CORE_MID VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 3.53319E-003
29 Coil:Heating:Water CORE_MID VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 9127.62730
30 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 5.83476
31 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.32599
32 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.33700
33 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 1.96631
34 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.86929
35 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
36 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.16876E-003
37 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 5.47288E-004
38 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 1.96631
39 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
40 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
41 Coil:Heating:Water CORE_TOP VAV BOX REHEAT COIL Design Size Rated Capacity [W] 62558.33989
42 Coil:Heating:Water CORE_TOP VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 5.47288E-004
43 Coil:Heating:Water CORE_TOP VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 1613.26821
44 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 1.10822
45 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.21550
46 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.22200
47 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.24602
48 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.57466
49 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
50 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.76799E-003
51 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 5.93998E-005
52 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.24602
53 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
54 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
55 Coil:Heating:Water PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 6789.76202
56 Coil:Heating:Water PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 5.93998E-005
57 Coil:Heating:Water PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 165.89050
58 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 1.11000
59 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.13865
60 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.20000
61 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.22200
62 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.36974
63 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
64 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 2.74786E-003
65 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 4.72248E-005
66 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.22200
67 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
68 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
69 Coil:Heating:Water PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 5398.09038
70 Coil:Heating:Water PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 4.72248E-005
71 Coil:Heating:Water PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 126.75300
72 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 1.10504
73 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.21612
74 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.22300
75 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.24642
76 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.57633
77 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
78 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.76287E-003
79 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 7.30355E-005
80 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.24837
81 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
82 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
83 Coil:Heating:Water PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 8348.40531
84 Coil:Heating:Water PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 7.30355E-005
85 Coil:Heating:Water PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 220.55220
86 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 1.43712
87 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.10709
88 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.20000
89 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.28742
90 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.30000
91 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
92 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 3.55766E-003
93 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 4.12268E-005
94 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.28742
95 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
96 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
97 Coil:Heating:Water PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 4712.47124
98 Coil:Heating:Water PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 4.12268E-005
99 Coil:Heating:Water PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 101.30302
100 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 10.62656
101 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.22474
102 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.22700
103 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 2.41223
104 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.59930
105 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
106 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.69530E-003
107 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.41636E-003
108 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 4.83028
109 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
110 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
111 Coil:Heating:Water PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 161898.76348
112 Coil:Heating:Water PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.41636E-003
113 Coil:Heating:Water PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 4271.51435
114 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_2 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 11.48194
115 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_2 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.13404
116 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_2 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.20000
117 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_2 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 2.29639
118 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_2 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.35744
119 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_2 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
120 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_2 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 2.84242E-003
121 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_2 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 9.33458E-004
122 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 3.18361
123 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
124 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
125 Coil:Heating:Water PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 106699.92874
126 Coil:Heating:Water PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 9.33458E-004
127 Coil:Heating:Water PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 2815.07494
128 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 10.53721
129 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.22665
130 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.22900
131 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 2.41302
132 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.60440
133 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
134 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.68101E-003
135 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.40280E-003
136 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 4.78391
137 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
138 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
139 Coil:Heating:Water PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 160348.88821
140 Coil:Heating:Water PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.40280E-003
141 Coil:Heating:Water PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 4230.67750
142 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 12.73497
143 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.12085
144 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.20000
145 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 2.54699
146 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.32227
147 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
148 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 3.15261E-003
149 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 8.58142E-004
150 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 2.92617
151 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
152 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
153 Coil:Heating:Water PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 98090.89339
154 Coil:Heating:Water PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 8.58142E-004
155 Coil:Heating:Water PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 2588.17575
156 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 1.17832
157 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.20268
158 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.21000
159 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.24745
160 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.54048
161 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
162 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.87982E-003
163 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.73633E-004
164 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.59245
165 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
166 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
167 Coil:Heating:Water PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 19847.34748
168 Coil:Heating:Water PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.73633E-004
169 Coil:Heating:Water PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 523.52648
170 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 1.16293
171 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.13234
172 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.20000
173 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.23259
174 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.35291
175 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
176 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 2.87889E-003
177 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.13822E-004
178 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.38839
179 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
180 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
181 Coil:Heating:Water PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 13010.56158
182 Coil:Heating:Water PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.13822E-004
183 Coil:Heating:Water PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 343.18180
184 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 1.17914
185 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.20254
186 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.20900
187 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.24644
188 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.54011
189 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
190 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.88109E-003
191 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.72409E-004
192 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.58827
193 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
194 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
195 Coil:Heating:Water PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 19707.39911
196 Coil:Heating:Water PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.72409E-004
197 Coil:Heating:Water PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 519.83915
198 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 1.35252
199 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.11379
200 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.20000
201 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.27050
202 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.30344
203 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
204 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 3.34824E-003
205 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.08125E-004
206 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.36891
207 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
208 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
209 Coil:Heating:Water PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 12359.32649
210 Coil:Heating:Water PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.08125E-004
211 Coil:Heating:Water PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 326.02045
212 AirTerminal:SingleDuct:ConstantVolume:NoReheat DATACENTER_BOT_ZN_6 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 0.48009
213 AirTerminal:SingleDuct:ConstantVolume:NoReheat DATACENTER_MID_ZN_6 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 4.57834
214 AirTerminal:SingleDuct:ConstantVolume:NoReheat DATACENTER_TOP_ZN_6 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 0.46691
215 AirTerminal:SingleDuct:ConstantVolume:NoReheat DATACENTER_BASEMENT_ZN_6 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 21.42960
216 AirLoopHVAC VAV_BOT WITH REHEAT Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 5.52128
217 AirLoopHVAC VAV_BOT WITH REHEAT Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 2.96191
218 AirLoopHVAC VAV_BOT WITH REHEAT Sum of Air Terminal Maximum Flow Rates [m3/s] 11.04255
219 AirLoopHVAC VAV_BOT WITH REHEAT Adjusted Heating Design Air Flow Rate [m3/s] 2.96191
220 AirLoopHVAC VAV_BOT WITH REHEAT Adjusted Cooling Design Air Flow Rate [m3/s] 10.13854
221 AirLoopHVAC VAV_BOT WITH REHEAT Adjusted Main Design Air Flow Rate [m3/s] 10.13854
222 AirLoopHVAC VAV_BOT WITH REHEAT User Heating Air Flow Ratio [] 0.30000
223 AirLoopHVAC VAV_BOT WITH REHEAT Calculated Heating Air Flow Ratio [] 0.29214
224 AirLoopHVAC VAV_MID WITH REHEAT Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 52.38383
225 AirLoopHVAC VAV_MID WITH REHEAT Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 28.91001
226 AirLoopHVAC VAV_MID WITH REHEAT Sum of Air Terminal Maximum Flow Rates [m3/s] 104.76765
227 AirLoopHVAC VAV_MID WITH REHEAT Adjusted Heating Design Air Flow Rate [m3/s] 28.91001
228 AirLoopHVAC VAV_MID WITH REHEAT Adjusted Cooling Design Air Flow Rate [m3/s] 95.07637
229 AirLoopHVAC VAV_MID WITH REHEAT Adjusted Main Design Air Flow Rate [m3/s] 95.07637
230 AirLoopHVAC VAV_MID WITH REHEAT User Heating Air Flow Ratio [] 0.30000
231 AirLoopHVAC VAV_MID WITH REHEAT Calculated Heating Air Flow Ratio [] 0.30407
232 AirLoopHVAC VAV_TOP WITH REHEAT Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 5.35383
233 AirLoopHVAC VAV_TOP WITH REHEAT Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 2.96329
234 AirLoopHVAC VAV_TOP WITH REHEAT Sum of Air Terminal Maximum Flow Rates [m3/s] 10.70767
235 AirLoopHVAC VAV_TOP WITH REHEAT Adjusted Heating Design Air Flow Rate [m3/s] 3.75261
236 AirLoopHVAC VAV_TOP WITH REHEAT Adjusted Cooling Design Air Flow Rate [m3/s] 10.29385
237 AirLoopHVAC VAV_TOP WITH REHEAT Adjusted Main Design Air Flow Rate [m3/s] 10.29385
238 AirLoopHVAC VAV_TOP WITH REHEAT User Heating Air Flow Ratio [] 0.30000
239 AirLoopHVAC VAV_TOP WITH REHEAT Calculated Heating Air Flow Ratio [] 0.36455
240 AirLoopHVAC CAV_BAS Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 6.08554
241 AirLoopHVAC CAV_BAS Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 6.08554
242 AirLoopHVAC CAV_BAS Sum of Air Terminal Maximum Flow Rates [m3/s] 6.08554
243 AirLoopHVAC CAV_BAS Adjusted Heating Design Air Flow Rate [m3/s] 6.08554
244 AirLoopHVAC CAV_BAS Adjusted Cooling Design Air Flow Rate [m3/s] 6.08554
245 AirLoopHVAC CAV_BAS Adjusted Main Design Air Flow Rate [m3/s] 6.08554
246 AirLoopHVAC CAV_BAS User Heating Air Flow Ratio [] 1.00000
247 AirLoopHVAC CAV_BAS Calculated Heating Air Flow Ratio [] 1.00000
248 AirLoopHVAC AIRLOOP DATACENTER BASEMENT Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 21.42960
249 AirLoopHVAC AIRLOOP DATACENTER BASEMENT Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 21.42960
250 AirLoopHVAC AIRLOOP DATACENTER BASEMENT Sum of Air Terminal Maximum Flow Rates [m3/s] 21.42960
251 AirLoopHVAC AIRLOOP DATACENTER BASEMENT Adjusted Heating Design Air Flow Rate [m3/s] 21.42960
252 AirLoopHVAC AIRLOOP DATACENTER BASEMENT Adjusted Cooling Design Air Flow Rate [m3/s] 21.42976
253 AirLoopHVAC AIRLOOP DATACENTER BASEMENT Adjusted Main Design Air Flow Rate [m3/s] 21.42976
254 AirLoopHVAC AIRLOOP DATACENTER BASEMENT User Heating Air Flow Ratio [] 1.00000
255 AirLoopHVAC AIRLOOP DATACENTER BASEMENT Calculated Heating Air Flow Ratio [] 0.99999
256 AirLoopHVAC AIRLOOP DATACENTER BOT Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 0.48009
257 AirLoopHVAC AIRLOOP DATACENTER BOT Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 0.48009
258 AirLoopHVAC AIRLOOP DATACENTER BOT Sum of Air Terminal Maximum Flow Rates [m3/s] 0.48009
259 AirLoopHVAC AIRLOOP DATACENTER BOT Adjusted Heating Design Air Flow Rate [m3/s] 0.48009
260 AirLoopHVAC AIRLOOP DATACENTER BOT Adjusted Cooling Design Air Flow Rate [m3/s] 0.48009
261 AirLoopHVAC AIRLOOP DATACENTER BOT Adjusted Main Design Air Flow Rate [m3/s] 0.48009
262 AirLoopHVAC AIRLOOP DATACENTER BOT User Heating Air Flow Ratio [] 1.00000
263 AirLoopHVAC AIRLOOP DATACENTER BOT Calculated Heating Air Flow Ratio [] 1.00000
264 AirLoopHVAC AIRLOOP DATACENTER MID Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 4.57834
265 AirLoopHVAC AIRLOOP DATACENTER MID Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 4.57834
266 AirLoopHVAC AIRLOOP DATACENTER MID Sum of Air Terminal Maximum Flow Rates [m3/s] 4.57834
267 AirLoopHVAC AIRLOOP DATACENTER MID Adjusted Heating Design Air Flow Rate [m3/s] 4.57834
268 AirLoopHVAC AIRLOOP DATACENTER MID Adjusted Cooling Design Air Flow Rate [m3/s] 4.57834
269 AirLoopHVAC AIRLOOP DATACENTER MID Adjusted Main Design Air Flow Rate [m3/s] 4.57834
270 AirLoopHVAC AIRLOOP DATACENTER MID User Heating Air Flow Ratio [] 1.00000
271 AirLoopHVAC AIRLOOP DATACENTER MID Calculated Heating Air Flow Ratio [] 1.00000
272 AirLoopHVAC AIRLOOP DATACENTER TOP Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 0.46691
273 AirLoopHVAC AIRLOOP DATACENTER TOP Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 0.46691
274 AirLoopHVAC AIRLOOP DATACENTER TOP Sum of Air Terminal Maximum Flow Rates [m3/s] 0.46691
275 AirLoopHVAC AIRLOOP DATACENTER TOP Adjusted Heating Design Air Flow Rate [m3/s] 0.46691
276 AirLoopHVAC AIRLOOP DATACENTER TOP Adjusted Cooling Design Air Flow Rate [m3/s] 0.46691
277 AirLoopHVAC AIRLOOP DATACENTER TOP Adjusted Main Design Air Flow Rate [m3/s] 0.46691
278 AirLoopHVAC AIRLOOP DATACENTER TOP User Heating Air Flow Ratio [] 1.00000
279 AirLoopHVAC AIRLOOP DATACENTER TOP Calculated Heating Air Flow Ratio [] 1.00000
280 AirLoopHVAC VAV_BOT WITH REHEAT Design Supply Air Flow Rate [m3/s] 10.13854
281 AirLoopHVAC VAV_MID WITH REHEAT Design Supply Air Flow Rate [m3/s] 95.07637
282 AirLoopHVAC VAV_TOP WITH REHEAT Design Supply Air Flow Rate [m3/s] 10.29385
283 AirLoopHVAC CAV_BAS Design Supply Air Flow Rate [m3/s] 6.08554
284 AirLoopHVAC AIRLOOP DATACENTER BASEMENT Design Supply Air Flow Rate [m3/s] 21.42976
285 AirLoopHVAC AIRLOOP DATACENTER BOT Design Supply Air Flow Rate [m3/s] 0.48009
286 AirLoopHVAC AIRLOOP DATACENTER MID Design Supply Air Flow Rate [m3/s] 4.57834
287 AirLoopHVAC AIRLOOP DATACENTER TOP Design Supply Air Flow Rate [m3/s] 0.46691
288 Controller:OutdoorAir VAV_BOT WITH REHEAT_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 10.13854
289 Controller:OutdoorAir VAV_BOT WITH REHEAT_OA_CONTROLLER Minimum Outdoor Air Flow Rate [m3/s] 2.53819
290 HeatExchanger:AirToAir:SensibleAndLatent VAV_BOT WITH REHEAT OA HEAT RECOVERY Design Size Nominal Supply Air Flow Rate [m3/s] 2.53819
291 Coil:Cooling:Water VAV_BOT WITH REHEAT COOLING COIL Design Size Design Inlet Air Temperature [C] 26.38270
292 Coil:Cooling:Water VAV_BOT WITH REHEAT COOLING COIL Design Size Design Inlet Water Temperature [C] 6.67000
293 Coil:Cooling:Water VAV_BOT WITH REHEAT COOLING COIL Design Size Design Outlet Air Temperature [C] 11.05710
294 Coil:Cooling:Water VAV_BOT WITH REHEAT COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 1.10518E-002
295 Coil:Cooling:Water VAV_BOT WITH REHEAT COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 8.50000E-003
296 Coil:Cooling:Water VAV_BOT WITH REHEAT COOLING COIL Design Size Design Coil Load [W] 270084.32047
297 Coil:Cooling:Water VAV_BOT WITH REHEAT COOLING COIL Design Size Design Water Flow Rate [m3/s] 1.14900E-002
298 Coil:Cooling:Water VAV_BOT WITH REHEAT COOLING COIL Design Size Design Air Flow Rate [m3/s] 10.13854
299 Coil:Heating:Water VAV_BOT WITH REHEAT HEATING COIL Design Size Rated Capacity [W] 15573.04163
300 Coil:Heating:Water VAV_BOT WITH REHEAT HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 1.36240E-004
301 Coil:Heating:Water VAV_BOT WITH REHEAT HEATING COIL Design Size U-Factor Times Area Value [W/K] 276.83179
302 Fan:VariableVolume VAV_BOT WITH REHEAT FAN Design Size Maximum Flow Rate [m3/s] 10.13854
303 Controller:WaterCoil VAV_BOT WITH REHEAT_COOLC_CONTROLLER Maximum Actuated Flow [m3/s] 1.14900E-002
304 Controller:WaterCoil VAV_BOT WITH REHEAT_COOLC_CONTROLLER Controller Convergence Tolerance 4.14439E-005
305 Controller:WaterCoil VAV_BOT WITH REHEAT_HEATC_CONTROLLER Maximum Actuated Flow [m3/s] 1.36240E-004
306 Controller:OutdoorAir VAV_MID WITH REHEAT_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 95.07637
307 Controller:OutdoorAir VAV_MID WITH REHEAT_OA_CONTROLLER Minimum Outdoor Air Flow Rate [m3/s] 25.38195
308 HeatExchanger:AirToAir:SensibleAndLatent VAV_MID WITH REHEAT OA HEAT RECOVERY Design Size Nominal Supply Air Flow Rate [m3/s] 25.38195
309 Coil:Cooling:Water VAV_MID WITH REHEAT COOLING COIL Design Size Design Inlet Air Temperature [C] 26.56914
310 Coil:Cooling:Water VAV_MID WITH REHEAT COOLING COIL Design Size Design Inlet Water Temperature [C] 6.67000
311 Coil:Cooling:Water VAV_MID WITH REHEAT COOLING COIL Design Size Design Outlet Air Temperature [C] 11.04875
312 Coil:Cooling:Water VAV_MID WITH REHEAT COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 1.13524E-002
313 Coil:Cooling:Water VAV_MID WITH REHEAT COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 8.50000E-003
314 Coil:Cooling:Water VAV_MID WITH REHEAT COOLING COIL Design Size Design Coil Load [W] 2643274.95203
315 Coil:Cooling:Water VAV_MID WITH REHEAT COOLING COIL Design Size Design Water Flow Rate [m3/s] 0.11245
316 Coil:Cooling:Water VAV_MID WITH REHEAT COOLING COIL Design Size Design Air Flow Rate [m3/s] 95.07637
317 Coil:Heating:Water VAV_MID WITH REHEAT HEATING COIL Design Size Rated Capacity [W] 94643.34428
318 Coil:Heating:Water VAV_MID WITH REHEAT HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 8.27981E-004
319 Coil:Heating:Water VAV_MID WITH REHEAT HEATING COIL Design Size U-Factor Times Area Value [W/K] 1701.60742
320 Fan:VariableVolume VAV_MID WITH REHEAT FAN Design Size Maximum Flow Rate [m3/s] 95.07637
321 Controller:WaterCoil VAV_MID WITH REHEAT_COOLC_CONTROLLER Maximum Actuated Flow [m3/s] 0.11245
322 Controller:WaterCoil VAV_MID WITH REHEAT_COOLC_CONTROLLER Controller Convergence Tolerance 4.23465E-006
323 Controller:WaterCoil VAV_MID WITH REHEAT_HEATC_CONTROLLER Maximum Actuated Flow [m3/s] 8.27981E-004
324 Controller:OutdoorAir VAV_TOP WITH REHEAT_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 10.29385
325 Controller:OutdoorAir VAV_TOP WITH REHEAT_OA_CONTROLLER Minimum Outdoor Air Flow Rate [m3/s] 2.53819
326 HeatExchanger:AirToAir:SensibleAndLatent VAV_TOP WITH REHEAT OA HEAT RECOVERY Design Size Nominal Supply Air Flow Rate [m3/s] 2.53819
327 Coil:Cooling:Water VAV_TOP WITH REHEAT COOLING COIL Design Size Design Inlet Air Temperature [C] 26.22441
328 Coil:Cooling:Water VAV_TOP WITH REHEAT COOLING COIL Design Size Design Inlet Water Temperature [C] 6.67000
329 Coil:Cooling:Water VAV_TOP WITH REHEAT COOLING COIL Design Size Design Outlet Air Temperature [C] 11.05699
330 Coil:Cooling:Water VAV_TOP WITH REHEAT COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 1.10149E-002
331 Coil:Cooling:Water VAV_TOP WITH REHEAT COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 8.50000E-003
332 Coil:Cooling:Water VAV_TOP WITH REHEAT COOLING COIL Design Size Design Coil Load [W] 271050.54438
333 Coil:Cooling:Water VAV_TOP WITH REHEAT COOLING COIL Design Size Design Water Flow Rate [m3/s] 1.15311E-002
334 Coil:Cooling:Water VAV_TOP WITH REHEAT COOLING COIL Design Size Design Air Flow Rate [m3/s] 10.29385
335 Coil:Heating:Water VAV_TOP WITH REHEAT HEATING COIL Design Size Rated Capacity [W] 7127.01262
336 Coil:Heating:Water VAV_TOP WITH REHEAT HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 6.23502E-005
337 Coil:Heating:Water VAV_TOP WITH REHEAT HEATING COIL Design Size U-Factor Times Area Value [W/K] 128.97735
338 Fan:VariableVolume VAV_TOP WITH REHEAT FAN Design Size Maximum Flow Rate [m3/s] 10.29385
339 Controller:WaterCoil VAV_TOP WITH REHEAT_COOLC_CONTROLLER Maximum Actuated Flow [m3/s] 1.15311E-002
340 Controller:WaterCoil VAV_TOP WITH REHEAT_COOLC_CONTROLLER Controller Convergence Tolerance 4.12961E-005
341 Controller:WaterCoil VAV_TOP WITH REHEAT_HEATC_CONTROLLER Maximum Actuated Flow [m3/s] 6.23502E-005
342 Controller:OutdoorAir CAV_BAS_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 6.08554
343 Controller:OutdoorAir CAV_BAS_OA_CONTROLLER Minimum Outdoor Air Flow Rate [m3/s] 1.20016
344 Coil:Cooling:Water CAV_BAS COOLING COIL Design Size Design Inlet Air Temperature [C] 24.88576
345 Coil:Cooling:Water CAV_BAS COOLING COIL Design Size Design Inlet Water Temperature [C] 6.67000
346 Coil:Cooling:Water CAV_BAS COOLING COIL Design Size Design Outlet Air Temperature [C] 11.42379
347 Coil:Cooling:Water CAV_BAS COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 1.05388E-002
348 Coil:Cooling:Water CAV_BAS COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 8.50000E-003
349 Coil:Cooling:Water CAV_BAS COOLING COIL Design Size Design Coil Load [W] 138576.71127
350 Coil:Cooling:Water CAV_BAS COOLING COIL Design Size Design Water Flow Rate [m3/s] 5.89537E-003
351 Coil:Cooling:Water CAV_BAS COOLING COIL Design Size Design Air Flow Rate [m3/s] 6.08554
352 Coil:Heating:Water CAV_BAS HEATING COIL Design Size Rated Capacity [W] 281575.79388
353 Coil:Heating:Water CAV_BAS HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 2.46335E-003
354 Coil:Heating:Water CAV_BAS HEATING COIL Design Size U-Factor Times Area Value [W/K] 6431.56288
355 Fan:ConstantVolume CAV_BAS FAN Design Size Maximum Flow Rate [m3/s] 6.08554
356 Controller:WaterCoil CAV_BAS_COOLC_CONTROLLER Maximum Actuated Flow [m3/s] 5.89537E-003
357 Controller:WaterCoil CAV_BAS_COOLC_CONTROLLER Controller Convergence Tolerance 8.07736E-005
358 Controller:WaterCoil CAV_BAS_HEATC_CONTROLLER Maximum Actuated Flow [m3/s] 2.46335E-003
359 Controller:OutdoorAir AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 21.42976
360 Controller:OutdoorAir AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER Minimum Outdoor Air Flow Rate [m3/s] 0.33839
361 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER BASEMENT COOLING COIL Design Size Rated Air Flow Rate [m3/s] 21.42976
362 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER BASEMENT COOLING COIL Design Size Rated Total Cooling Capacity [W] 436486.13566
363 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER BASEMENT COOLING COIL Design Size Rated Sensible Cooling Capacity [W] 313639.02907
364 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER BASEMENT COOLING COIL Design Size Rated Water Flow Rate [m3/s] 1.06895E-002
365 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP Supply Air Flow Rate [m3/s] 21.42976
366 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP Supply Air Flow Rate During Heating Operation [m3/s] 21.42976
367 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP Supply Air Flow Rate During Cooling Operation [m3/s] 21.42976
368 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] 21.42976
369 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP Nominal Heating Capacity [W] 436486.13566
370 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP Nominal Cooling Capacity [W] 436486.13566
371 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP Supplemental Heating Coil Nominal Capacity [W] 12800.93607
372 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
373 Fan:OnOff AIRLOOP DATACENTER BASEMENT SUPPLY FAN Design Size Maximum Flow Rate [m3/s] 21.42976
374 COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER BASEMENT HEATING COIL Design Size Rated Air Flow Rate [m3/s] 21.42976
375 COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER BASEMENT HEATING COIL Design Size Rated Heating Capacity [W] 436486.13566
376 COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER BASEMENT HEATING COIL Design Size Rated Water Flow Rate [m3/s] 1.06895E-002
377 Coil:Heating:Electric AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL Design Size Nominal Capacity [W] 12800.93607
378 Humidifier:Steam:Electric DATACENTER_BASEMENT_ZN_6 HUMIDIFIER Design Size Nominal Capacity Volume [m3/s] 3.74064E-005
379 Humidifier:Steam:Electric DATACENTER_BASEMENT_ZN_6 HUMIDIFIER User-Specified Nominal Capacity Volume [m3/s] 3.72000E-005
380 Humidifier:Steam:Electric DATACENTER_BASEMENT_ZN_6 HUMIDIFIER Design Size Rated Power [W] 96450.69782
381 Humidifier:Steam:Electric DATACENTER_BASEMENT_ZN_6 HUMIDIFIER User-Specified Rated Power [W] 100000.00000
382 Controller:OutdoorAir AIRLOOP DATACENTER BOT_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 0.48009
383 Controller:OutdoorAir AIRLOOP DATACENTER BOT_OA_CONTROLLER Minimum Outdoor Air Flow Rate [m3/s] 1.56323E-002
384 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER BOT COOLING COIL Design Size Rated Air Flow Rate [m3/s] 0.48009
385 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER BOT COOLING COIL Design Size Rated Total Cooling Capacity [W] 9798.88457
386 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER BOT COOLING COIL Design Size Rated Sensible Cooling Capacity [W] 7029.31531
387 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER BOT COOLING COIL Design Size Rated Water Flow Rate [m3/s] 2.39974E-004
388 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BOT DXAC HEAT PUMP Supply Air Flow Rate [m3/s] 0.48009
389 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BOT DXAC HEAT PUMP Supply Air Flow Rate During Heating Operation [m3/s] 0.48009
390 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BOT DXAC HEAT PUMP Supply Air Flow Rate During Cooling Operation [m3/s] 0.48009
391 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BOT DXAC HEAT PUMP Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] 0.48009
392 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BOT DXAC HEAT PUMP Nominal Heating Capacity [W] 9798.88457
393 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BOT DXAC HEAT PUMP Nominal Cooling Capacity [W] 9798.88457
394 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BOT DXAC HEAT PUMP Supplemental Heating Coil Nominal Capacity [W] 591.35022
395 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BOT DXAC HEAT PUMP Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
396 Fan:OnOff AIRLOOP DATACENTER BOT SUPPLY FAN Design Size Maximum Flow Rate [m3/s] 0.48009
397 COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER BOT HEATING COIL Design Size Rated Air Flow Rate [m3/s] 0.48009
398 COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER BOT HEATING COIL Design Size Rated Heating Capacity [W] 9798.88457
399 COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER BOT HEATING COIL Design Size Rated Water Flow Rate [m3/s] 2.39974E-004
400 Coil:Heating:Electric AIRLOOP DATACENTER BOT_SUPPHEATCOIL Design Size Nominal Capacity [W] 591.35022
401 Controller:OutdoorAir AIRLOOP DATACENTER MID_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 4.57834
402 Controller:OutdoorAir AIRLOOP DATACENTER MID_OA_CONTROLLER Minimum Outdoor Air Flow Rate [m3/s] 0.15632
403 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER MID COOLING COIL Design Size Rated Air Flow Rate [m3/s] 4.57834
404 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER MID COOLING COIL Design Size Rated Total Cooling Capacity [W] 93691.14456
405 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER MID COOLING COIL Design Size Rated Sensible Cooling Capacity [W] 67117.65119
406 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER MID COOLING COIL Design Size Rated Water Flow Rate [m3/s] 2.29449E-003
407 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER MID DXAC HEAT PUMP Supply Air Flow Rate [m3/s] 4.57834
408 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER MID DXAC HEAT PUMP Supply Air Flow Rate During Heating Operation [m3/s] 4.57834
409 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER MID DXAC HEAT PUMP Supply Air Flow Rate During Cooling Operation [m3/s] 4.57834
410 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER MID DXAC HEAT PUMP Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] 4.57834
411 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER MID DXAC HEAT PUMP Nominal Heating Capacity [W] 93691.14456
412 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER MID DXAC HEAT PUMP Nominal Cooling Capacity [W] 93691.14456
413 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER MID DXAC HEAT PUMP Supplemental Heating Coil Nominal Capacity [W] 5913.50215
414 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER MID DXAC HEAT PUMP Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
415 Fan:OnOff AIRLOOP DATACENTER MID SUPPLY FAN Design Size Maximum Flow Rate [m3/s] 4.57834
416 COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER MID HEATING COIL Design Size Rated Air Flow Rate [m3/s] 4.57834
417 COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER MID HEATING COIL Design Size Rated Heating Capacity [W] 93691.14456
418 COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER MID HEATING COIL Design Size Rated Water Flow Rate [m3/s] 2.29449E-003
419 Coil:Heating:Electric AIRLOOP DATACENTER MID_SUPPHEATCOIL Design Size Nominal Capacity [W] 5913.50215
420 Controller:OutdoorAir AIRLOOP DATACENTER TOP_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 0.46691
421 Controller:OutdoorAir AIRLOOP DATACENTER TOP_OA_CONTROLLER Minimum Outdoor Air Flow Rate [m3/s] 1.56323E-002
422 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER TOP COOLING COIL Design Size Rated Air Flow Rate [m3/s] 0.46691
423 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER TOP COOLING COIL Design Size Rated Total Cooling Capacity [W] 9544.35265
424 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER TOP COOLING COIL Design Size Rated Sensible Cooling Capacity [W] 6841.25799
425 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER TOP COOLING COIL Design Size Rated Water Flow Rate [m3/s] 2.33741E-004
426 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER TOP DXAC HEAT PUMP Supply Air Flow Rate [m3/s] 0.46691
427 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER TOP DXAC HEAT PUMP Supply Air Flow Rate During Heating Operation [m3/s] 0.46691
428 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER TOP DXAC HEAT PUMP Supply Air Flow Rate During Cooling Operation [m3/s] 0.46691
429 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER TOP DXAC HEAT PUMP Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] 0.46691
430 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER TOP DXAC HEAT PUMP Nominal Heating Capacity [W] 9544.35265
431 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER TOP DXAC HEAT PUMP Nominal Cooling Capacity [W] 9544.35265
432 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER TOP DXAC HEAT PUMP Supplemental Heating Coil Nominal Capacity [W] 591.35022
433 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER TOP DXAC HEAT PUMP Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
434 Fan:OnOff AIRLOOP DATACENTER TOP SUPPLY FAN Design Size Maximum Flow Rate [m3/s] 0.46691
435 COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER TOP HEATING COIL Design Size Rated Air Flow Rate [m3/s] 0.46691
436 COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER TOP HEATING COIL Design Size Rated Heating Capacity [W] 9544.35265
437 COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER TOP HEATING COIL Design Size Rated Water Flow Rate [m3/s] 2.33741E-004
438 Coil:Heating:Electric AIRLOOP DATACENTER TOP_SUPPHEATCOIL Design Size Nominal Capacity [W] 591.35022
439 Pump:VariableSpeed COOLSYS1 PUMP SECONDARY Design Flow Rate [m3/s] 0.14137
440 Pump:VariableSpeed COOLSYS1 PUMP SECONDARY Design Power Consumption [W] 23080.99771
441 PlantLoop COOLSYS1_DEMAND Maximum Loop Flow Rate [m3/s] 0.14137
442 PlantLoop COOLSYS1_DEMAND Plant Loop Volume [m3] 16.96410
443 HeatExchanger:FluidToFluid BYPASS HEAT EXCHANGER Loop Supply Side Design Fluid Flow Rate [m3/s] 0.14137
444 HeatExchanger:FluidToFluid BYPASS HEAT EXCHANGER Loop Demand Side Design Fluid Flow Rate [m3/s] 0.14137
445 HeatExchanger:FluidToFluid BYPASS HEAT EXCHANGER Heat Exchanger U-Factor Times Area Value [W/C] 593390.45145
446 HeatExchanger:FluidToFluid BYPASS HEAT EXCHANGER Loop-to-loop Temperature Difference Used to Size Heat Exchanger U-Factor Times Area Value [C] 5.60000
447 PlantLoop HEATSYS1 Maximum Loop Flow Rate [m3/s] 1.31425E-002
448 PlantLoop HEATSYS1 Plant Loop Volume [m3] 1.57710
449 Pump:VariableSpeed HEATSYS1 PUMP Design Flow Rate [m3/s] 1.31425E-002
450 Pump:VariableSpeed HEATSYS1 PUMP Design Power Consumption [W] 3957.93848
451 Pump:VariableSpeed HEATSYS1 PUMP Design Minimum Flow Rate [m3/s] 0.00000
452 Boiler:HotWater HEATSYS1 BOILER Design Size Nominal Capacity [W] 1502266.44258
453 Boiler:HotWater HEATSYS1 BOILER User-Specified Nominal Capacity [W] 1502266.44000
454 Boiler:HotWater HEATSYS1 BOILER Design Size Design Water Flow Rate [m3/s] 1.31425E-002
455 PlantLoop COOLSYS1_SUPPLY Maximum Loop Flow Rate [m3/s] 0.14137
456 PlantLoop COOLSYS1_SUPPLY Plant Loop Volume [m3] 16.96410
457 Pump:ConstantSpeed COOLSYS1 CHILLER1 PUMP Design Flow Rate [m3/s] 7.06838E-002
458 Pump:ConstantSpeed COOLSYS1 CHILLER1 PUMP Design Power Consumption [W] 7989.87655
459 Pump:ConstantSpeed COOLSYS1 CHILLER2 PUMP Design Flow Rate [m3/s] 7.06838E-002
460 Pump:ConstantSpeed COOLSYS1 CHILLER2 PUMP Design Power Consumption [W] 7989.87655
461 Chiller:Electric:ReformulatedEIR COOLSYS1 CHILLER1 Design Size Reference Chilled Water Flow Rate [m3/s] 0.14137
462 Chiller:Electric:ReformulatedEIR COOLSYS1 CHILLER1 User-Specified Reference Chilled Water Flow Rate [m3/s] 7.12900E-002
463 Chiller:Electric:ReformulatedEIR COOLSYS1 CHILLER1 Design Size Reference Capacity [W] 1679859.85726
464 Chiller:Electric:ReformulatedEIR COOLSYS1 CHILLER1 User-Specified Reference Capacity [W] 1687769.74500
465 Chiller:Electric:ReformulatedEIR COOLSYS1 CHILLER1 Design Size Reference Condenser Water Flow Rate [m3/s] 8.35215E-002
466 Chiller:Electric:ReformulatedEIR COOLSYS1 CHILLER2 Design Size Reference Chilled Water Flow Rate [m3/s] 0.14137
467 Chiller:Electric:ReformulatedEIR COOLSYS1 CHILLER2 User-Specified Reference Chilled Water Flow Rate [m3/s] 7.12900E-002
468 Chiller:Electric:ReformulatedEIR COOLSYS1 CHILLER2 Design Size Reference Capacity [W] 1679859.85726
469 Chiller:Electric:ReformulatedEIR COOLSYS1 CHILLER2 User-Specified Reference Capacity [W] 1687769.74500
470 Chiller:Electric:ReformulatedEIR COOLSYS1 CHILLER2 Design Size Reference Condenser Water Flow Rate [m3/s] 8.35215E-002
471 PlantLoop SINGLE WATER PLANT LOOP Maximum Loop Flow Rate [m3/s] 1.34577E-002
472 PlantLoop SINGLE WATER PLANT LOOP Plant Loop Volume [m3] 1.61493
473 Pump:ConstantSpeed PLANT CIRC PUMP Design Flow Rate [m3/s] 1.34577E-002
474 Pump:ConstantSpeed PLANT CIRC PUMP Design Power Consumption [W] 3432.39212
475 FluidCooler:TwoSpeed CENTRAL TOWER Design Water Flow Rate [m3/s] 1.34577E-002
476 FluidCooler:TwoSpeed CENTRAL TOWER Air Flow Rate at High Fan Speed [m3/s] 139666.46671
477 FluidCooler:TwoSpeed CENTRAL TOWER Fluid cooler UA value at high fan speed based on nominal capacity input [W/K] 58635.86744
478 FluidCooler:TwoSpeed CENTRAL TOWER Air Flow Rate at Low Fan Speed [m3/s] 69833.23335
479 FluidCooler:TwoSpeed CENTRAL TOWER Fan Power at Low Fan Speed [W] 7879.72339
480 FluidCooler:TwoSpeed CENTRAL TOWER U-factor Times Area Value at Low Fan Speed [W/C] 21351.26503
481 Boiler:HotWater CENTRAL BOILER Design Size Nominal Capacity [W] 554342.77698
482 Boiler:HotWater CENTRAL BOILER User-Specified Nominal Capacity [W] 543702.46000
483 Boiler:HotWater CENTRAL BOILER Design Size Design Water Flow Rate [m3/s] 1.34577E-002
484 PlantLoop SWHSYS1 Maximum Loop Flow Rate [m3/s] 4.40000E-004
485 PlantLoop SWHSYS1 Plant Loop Volume [m3] 5.28000E-002
486 Pump:ConstantSpeed SWHSYS1 PUMP Design Flow Rate [m3/s] 4.40000E-004
487 Pump:ConstantSpeed SWHSYS1 PUMP Design Power Consumption [W] 56.20530
488 WaterHeater:Mixed SWHSYS1 WATER HEATER Use Side Design Flow Rate [m3/s] 4.40000E-004
489 CondenserLoop TOWERWATERSYS Maximum Loop Flow Rate [m3/s] 0.16704
490 CondenserLoop TOWERWATERSYS Condenser Loop Volume [m3] 20.04515
491 HeaderedPumps:VariableSpeed TOWERWATERSYS PUMP Design Flow Rate [m3/s] 0.16704
492 HeaderedPumps:VariableSpeed TOWERWATERSYS PUMP Design Power Consumption [W] 41356.13583
493 CoolingTower:VariableSpeed TOWERWATERSYS COOLTOWER 1 Design Air Flow Rate [m3/s] 64.28948
494 CoolingTower:VariableSpeed TOWERWATERSYS COOLTOWER 1 Nominal Capacity [W] 2002498.31833
495 CoolingTower:VariableSpeed TOWERWATERSYS COOLTOWER 1 Air Flow Rate in free convection regime [m3/s] 12.85790
496 CoolingTower:VariableSpeed TOWERWATERSYS COOLTOWER 1 Tower capacity in free convection regime at design conditions [W] 250312.28979
497 CoolingTower:VariableSpeed TOWERWATERSYS COOLTOWER 2 Design Air Flow Rate [m3/s] 64.28948
498 CoolingTower:VariableSpeed TOWERWATERSYS COOLTOWER 2 Nominal Capacity [W] 2002498.31833
499 CoolingTower:VariableSpeed TOWERWATERSYS COOLTOWER 2 Air Flow Rate in free convection regime [m3/s] 12.85790
500 CoolingTower:VariableSpeed TOWERWATERSYS COOLTOWER 2 Tower capacity in free convection regime at design conditions [W] 250312.28979
501 PlantEquipmentOperation:ComponentSetPoint WSHPPLANT OPERATION SCHEME Design Water Flow Rate [m3/s] Equipment # 47 8.67525E-002
502 PlantEquipmentOperation:ComponentSetPoint WSHPPLANT OPERATION SCHEME Design Water Flow Rate [m3/s] Equipment # 47 8.67525E-002


Water Heating Coil Capacity Information

Component Type Name Nominal Total Capacity {W}
1 Coil:Heating:Water CORE_BOTTOM VAV BOX REHEAT COIL 18690.67
2 Coil:Heating:Water CORE_MID VAV BOX REHEAT COIL 382712.63
3 Coil:Heating:Water CORE_TOP VAV BOX REHEAT COIL 59240.46
4 Coil:Heating:Water PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL 6431.54
5 Coil:Heating:Water PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL 5114.14
6 Coil:Heating:Water PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL 7912.09
7 Coil:Heating:Water PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL 4466.68
8 Coil:Heating:Water PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL 153399.89
9 Coil:Heating:Water PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL 101098.18
10 Coil:Heating:Water PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL 151931.75
11 Coil:Heating:Water PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL 92942.68
12 Coil:Heating:Water PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL 18804.64
13 Coil:Heating:Water PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL 12326.99
14 Coil:Heating:Water PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL 18672.07
15 Coil:Heating:Water PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL 11710.08
16 Coil:Heating:Water VAV_BOT WITH REHEAT HEATING COIL 13918.06
17 Coil:Heating:Water VAV_MID WITH REHEAT HEATING COIL 86346.21
18 Coil:Heating:Water VAV_TOP WITH REHEAT HEATING COIL 6578.99
19 Coil:Heating:Water CAV_BAS HEATING COIL 230153.76


Water Cooling Coil Capacity Information

Component Type Name Nominal Total Capacity {W} Nominal Sensible Capacity {W} Nominal Latent Capacity {W} Nominal Sensible Heat Ratio Nominal Coil UA Value {W/C} Nominal Coil Surface Area {m2}
1 Coil:Cooling:Water VAV_BOT WITH REHEAT COOLING COIL 275418.77 186343.79 89074.99 0.68 28670.70 290.79
2 Coil:Cooling:Water VAV_MID WITH REHEAT COOLING COIL 2625714.47 1767845.58 857868.89 0.67 274315.81 2782.26
3 Coil:Cooling:Water VAV_TOP WITH REHEAT COOLING COIL 278474.70 188653.35 89821.35 0.68 28982.75 293.96
4 Coil:Cooling:Water CAV_BAS COOLING COIL 153793.86 106298.39 47495.47 0.69 15674.26 158.98


Chiller Standard Rating Information

Component Type Component Name IPLV in SI Units {W/W} IPLV in IP Units {Btu/W-h}
1 Chiller:Electric:ReformulatedEIR COOLSYS1 CHILLER1 6.84 23.33
2 Chiller:Electric:ReformulatedEIR COOLSYS1 CHILLER2 6.84 23.33


Zone Surfaces

Zone Name # Surfaces
1 BASEMENT 10
2 CORE_BOTTOM 8
3 CORE_MID 7
4 CORE_TOP 7
5 PERIMETER_BOT_ZN_3 18
6 PERIMETER_BOT_ZN_2 12
7 PERIMETER_BOT_ZN_1 18
8 PERIMETER_BOT_ZN_4 12
9 PERIMETER_MID_ZN_3 9
10 PERIMETER_MID_ZN_2 8
11 PERIMETER_MID_ZN_1 9
12 PERIMETER_MID_ZN_4 8
13 PERIMETER_TOP_ZN_3 9
14 PERIMETER_TOP_ZN_2 8
15 PERIMETER_TOP_ZN_1 9
16 PERIMETER_TOP_ZN_4 8
17 GROUNDFLOOR_PLENUM 11
18 MIDFLOOR_PLENUM 11
19 TOPFLOOR_PLENUM 11
20 DATACENTER_BOT_ZN_6 6
21 DATACENTER_MID_ZN_6 6
22 DATACENTER_TOP_ZN_6 6
23 DATACENTER_BASEMENT_ZN_6 10


HeatTransfer Surface

Surface Name Surface Class Base Surface Heat Transfer Algorithm Construction Nominal U (w/o film coefs) {W/m2-K} Nominal U (with film coefs) {W/m2-K} Solar Diffusing Area (Net) {m2} Area (Gross) {m2} Area (Sunlit Calc) {m2} Azimuth {deg} Tilt {deg} ~Width {m} ~Height {m} Reveal {m} ExtBoundCondition ExtConvCoeffCalc IntConvCoeffCalc SunExposure WindExposure ViewFactorToGround ViewFactorToSky ViewFactorToGround-IR ViewFactorToSky-IR #Sides
1 BASEMENT_WALL_EAST Wall   CTF - ConductionTransferFunction BASEMENT_WALL_EAST_CFACTOR 0.940 0.824   118.87 118.87 118.87 90.00 90.00 48.74 2.44 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
2 BASEMENT_WALL_SOUTH Wall   CTF - ConductionTransferFunction BASEMENT_WALL_SOUTH_CFACTOR 0.940 0.824   139.09 139.09 139.09 180.00 90.00 57.03 2.44 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
3 BASEMENT_WALL_NORTH Wall   CTF - ConductionTransferFunction BASEMENT_WALL_NORTH_CFACTOR 0.940 0.824   139.09 139.09 139.09 0.00 90.00 57.03 2.44 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
4 BASEMENT_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   118.87 118.87 118.87 270.00 90.00 48.74 2.44 0.00 DATACENTER_BASEMENT_ZN_6_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
5 BASEMENT_FLOOR Floor   CTF - ConductionTransferFunction EXT_SLAB_8IN_WITH_CARPET 3.285 1.827   2779.43 2779.43 2779.43 0.00 180.00 57.03 48.74 0.00 BASEMENT_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.00 1.00 0.00 4
6 PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   201.98 201.98 201.98 225.00 0.00 6.47 39.59 0.00 PERIMETER_BOT_ZN_2_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
7 PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   250.34 250.34 250.34 180.00 0.00 57.03 4.57 0.00 PERIMETER_BOT_ZN_1_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
8 CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   2076.77 2076.77 2076.77 180.00 0.00 52.45 39.59 0.00 CORE_BOT_ZN_5_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
9 PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   250.34 250.34 250.34 180.00 0.00 52.45 4.57 0.00 PERIMETER_BOT_ZN_3_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
10 BASEMENT_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   7126.21 7126.21 7126.21 0.00 90.00 7126.21 1.00 0.00 BASEMENT_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
11 CORE_BOT_ZN_5_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   173.00 173.00 173.00 180.00 90.00 63.05 2.74 0.00 CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
12 CORE_BOT_ZN_5_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 270.00 90.00 39.59 2.74 0.00 DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
13 CORE_BOT_ZN_5_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   173.00 173.00 173.00 0.00 90.00 63.05 2.74 0.00 CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
14 CORE_BOT_ZN_5_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 90.00 90.00 39.59 2.74 0.00 CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
15 DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   419.30 419.30 419.30 0.00 180.00 10.59 39.59 0.00 DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.00 1.00 0.00 4
16 CORE_BOT_ZN_5_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   2076.82 2076.82 2076.82 0.00 180.00 52.46 39.59 0.00 CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.00 1.00 0.00 4
17 CORE_BOT_ZN_5_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   2496.12 2496.12 2496.12 180.00 0.00 63.05 39.59 0.00 iz-CORE_BOT_ZN_5_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
18 CORE_BOTTOM_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   5064.65 5064.65 5064.65 0.00 90.00 5064.65 1.00 0.00 CORE_BOTTOM_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
19 CORE_MID_ZN_5_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   173.00 173.00 173.00 180.00 90.00 63.05 2.74 0.00 CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
20 CORE_MID_ZN_5_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 270.00 90.00 39.59 2.74 0.00 DATACENTER_MID_ZN_6_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
21 CORE_MID_ZN_5_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   173.00 173.00 173.00 0.00 90.00 63.05 2.74 0.00 CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
22 CORE_MID_ZN_5_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 90.00 90.00 39.59 2.74 0.00 CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
23 CORE_MID_ZN_5_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   2496.12 2496.12 2496.12 0.00 180.00 63.05 39.59 0.00 CORE_MID_ZN_5_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
24 CORE_MID_ZN_5_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   2496.12 2496.12 2496.12 180.00 0.00 63.05 39.59 0.00 iz-CORE_MID_ZN_5_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
25 CORE_MID_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   5064.65 5064.65 5064.65 0.00 90.00 5064.65 1.00 0.00 CORE_MID_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
26 CORE_TOP_ZN_5_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   173.00 173.00 173.00 180.00 90.00 63.05 2.74 0.00 CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
27 CORE_TOP_ZN_5_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 270.00 90.00 39.59 2.74 0.00 DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
28 CORE_TOP_ZN_5_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   173.00 173.00 173.00 0.00 90.00 63.05 2.74 0.00 CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
29 CORE_TOP_ZN_5_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 90.00 90.00 39.59 2.74 0.00 CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
30 CORE_TOP_ZN_5_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   2496.12 2496.12 2496.12 0.00 180.00 63.05 39.59 0.00 CORE_TOP_ZN_5_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
31 CORE_TOP_ZN_5_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   2496.12 2496.12 2496.12 180.00 0.00 63.05 39.59 0.00 iz-CORE_TOP_ZN_5_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
32 CORE_TOP_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   5064.65 5064.65 5064.65 0.00 90.00 5064.65 1.00 0.00 CORE_TOP_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
33 PERIMETER_BOT_ZN_3_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 5.069 2.882   76.91 200.61 76.91 0.00 90.00 73.11 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
34 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 Window PERIMETER_BOT_ZN_3_WALL_NORTH Window5 Detailed Fenestration WINDOW_U_0.57_SHGC_NORTH_0.25 N/A 3.241 No 23.18 23.18 23.18 0.00 90.00 13.65 1.70 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
35 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 Window PERIMETER_BOT_ZN_3_WALL_NORTH Window5 Detailed Fenestration WINDOW_U_0.57_SHGC_NORTH_0.25 N/A 3.241 No 23.18 23.18 23.18 0.00 90.00 13.65 1.70 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
36 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 Window PERIMETER_BOT_ZN_3_WALL_NORTH Window5 Detailed Fenestration WINDOW_U_0.57_SHGC_NORTH_0.25 N/A 3.241 No 23.18 23.18 23.18 0.00 90.00 13.65 1.70 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
37 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 Window PERIMETER_BOT_ZN_3_WALL_NORTH Window5 Detailed Fenestration WINDOW_U_0.57_SHGC_NORTH_0.25 N/A 3.241 No 23.18 23.18 23.18 0.00 90.00 13.65 1.70 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
38 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 Window PERIMETER_BOT_ZN_3_WALL_NORTH Window5 Detailed Fenestration WINDOW_U_0.57_SHGC_NORTH_0.25 N/A 3.241 No 23.18 23.18 23.18 0.00 90.00 13.65 1.70 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
39 PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 Door PERIMETER_BOT_ZN_3_WALL_NORTH CTF - ConductionTransferFunction SWINGING DOOR_CON 3.975 3.975   1.95 1.95 1.95 0.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
40 PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 Door PERIMETER_BOT_ZN_3_WALL_NORTH CTF - ConductionTransferFunction SWINGING DOOR_CON 3.975 3.975   1.95 1.95 1.95 0.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
41 PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 Door PERIMETER_BOT_ZN_3_WALL_NORTH CTF - ConductionTransferFunction SWINGING DOOR_CON 3.975 3.975   1.95 1.95 1.95 0.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
42 PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 Door PERIMETER_BOT_ZN_3_WALL_NORTH CTF - ConductionTransferFunction SWINGING DOOR_CON 3.975 3.975   1.95 1.95 1.95 0.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
43 PERIMETER_BOT_ZN_3_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 225.00 90.00 6.47 2.74 0.00 PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
44 CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   173.00 173.00 173.00 180.00 90.00 63.05 2.74 0.00 CORE_BOT_ZN_5_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
45 PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 135.00 90.00 6.47 2.74 0.00 PERIMETER_BOT_ZN_2_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
46 DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   2.51 2.51 2.51 180.00 90.00 0.91 2.74 0.00 DATACENTER_BOT_ZN_6_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
47 PERIMETER_BOT_ZN_3_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   250.34 250.34 250.34 0.00 180.00 52.46 6.47 0.00 PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
48 DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   63.07 63.07 63.07 0.00 180.00 11.51 4.57 0.00 DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.00 1.00 0.00 4
49 PERIMETER_BOT_ZN_3_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   313.41 313.41 313.41 180.00 0.00 63.96 6.47 0.00 iz-PERIMETER_BOT_ZN_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
50 PERIMETER_BOT_ZN_3_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   626.83 626.83 626.83 0.00 90.00 626.83 1.00 0.00 PERIMETER_BOT_ZN_3_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
51 PERIMETER_BOT_ZN_2_WALL_EAST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 5.069 2.882   52.57 133.74 52.57 90.00 90.00 48.74 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
52 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 Window PERIMETER_BOT_ZN_2_WALL_EAST Window5 Detailed Fenestration WINDOW_U_0.57_SHGC_EAST_0.25 N/A 3.241 No 25.75 25.75 25.75 90.00 90.00 15.43 1.67 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
53 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 Window PERIMETER_BOT_ZN_2_WALL_EAST Window5 Detailed Fenestration WINDOW_U_0.57_SHGC_EAST_0.25 N/A 3.241 No 25.75 25.75 25.75 90.00 90.00 15.43 1.67 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
54 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 Window PERIMETER_BOT_ZN_2_WALL_EAST Window5 Detailed Fenestration WINDOW_U_0.57_SHGC_EAST_0.25 N/A 3.241 No 25.75 25.75 25.75 90.00 90.00 15.43 1.67 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
55 PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 Door PERIMETER_BOT_ZN_2_WALL_EAST CTF - ConductionTransferFunction SWINGING DOOR_CON 3.975 3.975   1.95 1.95 1.95 90.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
56 PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 Door PERIMETER_BOT_ZN_2_WALL_EAST CTF - ConductionTransferFunction SWINGING DOOR_CON 3.975 3.975   1.95 1.95 1.95 90.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
57 PERIMETER_BOT_ZN_2_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 315.00 90.00 6.47 2.74 0.00 PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
58 CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 270.00 90.00 39.59 2.74 0.00 CORE_BOT_ZN_5_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
59 PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 225.00 90.00 6.47 2.74 0.00 PERIMETER_BOT_ZN_1_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
60 PERIMETER_BOT_ZN_2_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   201.98 201.98 201.98 45.00 180.00 6.47 48.74 0.00 PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
61 PERIMETER_BOT_ZN_2_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   201.98 201.98 201.98 225.00 0.00 6.47 39.59 0.00 iz-PERIMETER_BOT_ZN_2_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
62 PERIMETER_BOT_ZN_2_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   403.95 403.95 403.95 0.00 90.00 403.95 1.00 0.00 PERIMETER_BOT_ZN_2_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
63 PERIMETER_BOT_ZN_1_WALL_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 5.069 2.882   76.91 200.61 76.91 180.00 90.00 73.11 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
64 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 Window PERIMETER_BOT_ZN_1_WALL_SOUTH Window5 Detailed Fenestration WINDOW_U_0.57_SHGC_SOUTH_0.25 N/A 3.241 No 23.18 23.18 23.18 180.00 90.00 13.65 1.70 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
65 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 Window PERIMETER_BOT_ZN_1_WALL_SOUTH Window5 Detailed Fenestration WINDOW_U_0.57_SHGC_SOUTH_0.25 N/A 3.241 No 23.18 23.18 23.18 180.00 90.00 13.65 1.70 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
66 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 Window PERIMETER_BOT_ZN_1_WALL_SOUTH Window5 Detailed Fenestration WINDOW_U_0.57_SHGC_SOUTH_0.25 N/A 3.241 No 23.18 23.18 23.18 180.00 90.00 13.65 1.70 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
67 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 Window PERIMETER_BOT_ZN_1_WALL_SOUTH Window5 Detailed Fenestration WINDOW_U_0.57_SHGC_SOUTH_0.25 N/A 3.241 No 23.18 23.18 23.18 180.00 90.00 13.65 1.70 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
68 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 Window PERIMETER_BOT_ZN_1_WALL_SOUTH Window5 Detailed Fenestration WINDOW_U_0.57_SHGC_SOUTH_0.25 N/A 3.241 No 23.18 23.18 23.18 180.00 90.00 13.65 1.70 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
69 PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 Door PERIMETER_BOT_ZN_1_WALL_SOUTH CTF - ConductionTransferFunction SWINGING DOOR_CON 3.975 3.975   1.95 1.95 1.95 180.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
70 PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 Door PERIMETER_BOT_ZN_1_WALL_SOUTH CTF - ConductionTransferFunction SWINGING DOOR_CON 3.975 3.975   1.95 1.95 1.95 180.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
71 PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 Door PERIMETER_BOT_ZN_1_WALL_SOUTH CTF - ConductionTransferFunction SWINGING DOOR_CON 3.975 3.975   1.95 1.95 1.95 180.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
72 PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 Door PERIMETER_BOT_ZN_1_WALL_SOUTH CTF - ConductionTransferFunction SWINGING DOOR_CON 3.975 3.975   1.95 1.95 1.95 180.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
73 PERIMETER_BOT_ZN_1_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 45.00 90.00 6.47 2.74 0.00 PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
74 DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   2.51 2.51 2.51 0.00 90.00 0.91 2.74 0.00 DATACENTER_BOT_ZN_6_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
75 PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 315.00 90.00 6.47 2.74 0.00 PERIMETER_BOT_ZN_4_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
76 CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   173.00 173.00 173.00 0.00 90.00 63.05 2.74 0.00 CORE_BOT_ZN_5_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
77 DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   63.07 63.07 63.07 0.00 180.00 16.08 4.57 0.00 DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.00 1.00 0.00 4
78 PERIMETER_BOT_ZN_1_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   250.35 250.35 250.35 0.00 180.00 57.03 6.47 0.00 PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.00 1.00 0.00 4
79 PERIMETER_BOT_ZN_1_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   313.42 313.42 313.42 180.00 0.00 73.11 6.47 0.00 iz-PERIMETER_BOT_ZN_1_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
80 PERIMETER_BOT_ZN_1_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   626.84 626.84 626.84 0.00 90.00 626.84 1.00 0.00 PERIMETER_BOT_ZN_1_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
81 PERIMETER_BOT_ZN_4_WALL_WEST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 5.069 2.882   52.57 133.74 52.57 270.00 90.00 48.74 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
82 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 Window PERIMETER_BOT_ZN_4_WALL_WEST Window5 Detailed Fenestration WINDOW_U_0.57_SHGC_WEST_0.25 N/A 3.241 No 25.75 25.75 25.75 270.00 90.00 15.43 1.67 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
83 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 Window PERIMETER_BOT_ZN_4_WALL_WEST Window5 Detailed Fenestration WINDOW_U_0.57_SHGC_WEST_0.25 N/A 3.241 No 25.75 25.75 25.75 270.00 90.00 15.43 1.67 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
84 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 Window PERIMETER_BOT_ZN_4_WALL_WEST Window5 Detailed Fenestration WINDOW_U_0.57_SHGC_WEST_0.25 N/A 3.241 No 25.75 25.75 25.75 270.00 90.00 15.43 1.67 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
85 PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 Door PERIMETER_BOT_ZN_4_WALL_WEST CTF - ConductionTransferFunction SWINGING DOOR_CON 3.975 3.975   1.95 1.95 1.95 270.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
86 PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 Door PERIMETER_BOT_ZN_4_WALL_WEST CTF - ConductionTransferFunction SWINGING DOOR_CON 3.975 3.975   1.95 1.95 1.95 270.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
87 PERIMETER_BOT_ZN_4_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 135.00 90.00 6.47 2.74 0.00 PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
88 DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 90.00 90.00 39.59 2.74 0.00 DATACENTER_BOT_ZN_6_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
89 PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 45.00 90.00 6.47 2.74 0.00 PERIMETER_BOT_ZN_3_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
90 PERIMETER_BOT_ZN_4_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   201.98 201.98 201.98 315.00 180.00 6.47 39.59 0.00 PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.00 1.00 0.00 4
91 PERIMETER_BOT_ZN_4_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   201.98 201.98 201.98 135.00 0.00 6.47 48.74 0.00 iz-PERIMETER_BOT_ZN_4_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
92 PERIMETER_BOT_ZN_4_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   403.95 403.95 403.95 0.00 90.00 403.95 1.00 0.00 PERIMETER_BOT_ZN_4_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
93 PERIMETER_MID_ZN_3_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 5.069 2.882   84.71 200.61 84.71 0.00 90.00 73.11 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
94 PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW Window PERIMETER_MID_ZN_3_WALL_NORTH Window5 Detailed Fenestration WINDOW_U_0.57_SHGC_NORTH_0.25 N/A 3.241 No 115.90 115.90 115.90 0.00 90.00 73.11 1.59 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
95 PERIMETER_MID_ZN_3_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 225.00 90.00 6.47 2.74 0.00 PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
96 CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   173.00 173.00 173.00 180.00 90.00 63.05 2.74 0.00 CORE_MID_ZN_5_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
97 PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 135.00 90.00 6.47 2.74 0.00 PERIMETER_MID_ZN_2_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
98 DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   2.51 2.51 2.51 180.00 90.00 0.91 2.74 0.00 DATACENTER_MID_ZN_6_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
99 PERIMETER_MID_ZN_3_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   313.41 313.41 313.41 0.00 180.00 63.96 6.47 0.00 PERIMETER_MID_ZN_3_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
100 PERIMETER_MID_ZN_3_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   313.41 313.41 313.41 180.00 0.00 63.96 6.47 0.00 iz-PERIMETER_MID_ZN_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
101 PERIMETER_MID_ZN_3_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   626.83 626.83 626.83 0.00 90.00 626.83 1.00 0.00 PERIMETER_MID_ZN_3_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
102 PERIMETER_MID_ZN_2_WALL_EAST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 5.069 2.882   56.47 133.74 56.47 90.00 90.00 48.74 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
103 PERIMETER_MID_ZN_2_WALL_EAST_WINDOW Window PERIMETER_MID_ZN_2_WALL_EAST Window5 Detailed Fenestration WINDOW_U_0.57_SHGC_EAST_0.25 N/A 3.241 No 77.26 77.26 77.26 90.00 90.00 48.74 1.59 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
104 PERIMETER_MID_ZN_2_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 315.00 90.00 6.47 2.74 0.00 PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
105 CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 270.00 90.00 39.59 2.74 0.00 CORE_MID_ZN_5_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
106 PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 225.00 90.00 6.47 2.74 0.00 PERIMETER_MID_ZN_1_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
107 PERIMETER_MID_ZN_2_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   201.98 201.98 201.98 45.00 180.00 6.47 48.74 0.00 PERIMETER_MID_ZN_2_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
108 PERIMETER_MID_ZN_2_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   201.98 201.98 201.98 225.00 0.00 6.47 39.59 0.00 iz-PERIMETER_MID_ZN_2_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
109 PERIMETER_MID_ZN_2_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   403.95 403.95 403.95 0.00 90.00 403.95 1.00 0.00 PERIMETER_MID_ZN_2_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
110 PERIMETER_MID_ZN_1_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 45.00 90.00 6.47 2.74 0.00 PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
111 PERIMETER_MID_ZN_1_WALL_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 5.069 2.882   84.71 200.61 84.71 180.00 90.00 73.11 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
112 PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW Window PERIMETER_MID_ZN_1_WALL_SOUTH Window5 Detailed Fenestration WINDOW_U_0.57_SHGC_SOUTH_0.25 N/A 3.241 No 115.90 115.90 115.90 180.00 90.00 73.11 1.59 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
113 DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   2.51 2.51 2.51 0.00 90.00 0.91 2.74 0.00 DATACENTER_MID_ZN_6_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
114 PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 315.00 90.00 6.47 2.74 0.00 PERIMETER_MID_ZN_4_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
115 CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   173.00 173.00 173.00 0.00 90.00 63.05 2.74 0.00 CORE_MID_ZN_5_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
116 PERIMETER_MID_ZN_1_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   313.42 313.42 313.42 0.00 180.00 73.11 6.47 0.00 PERIMETER_MID_ZN_1_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
117 PERIMETER_MID_ZN_1_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   313.42 313.42 313.42 180.00 0.00 73.11 6.47 0.00 iz-PERIMETER_MID_ZN_1_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
118 PERIMETER_MID_ZN_1_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   626.84 626.84 626.84 0.00 90.00 626.84 1.00 0.00 PERIMETER_MID_ZN_1_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
119 PERIMETER_MID_ZN_4_WALL_WEST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 5.069 2.882   56.47 133.74 56.47 270.00 90.00 48.74 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
120 PERIMETER_MID_ZN_4_WALL_WEST_WINDOW Window PERIMETER_MID_ZN_4_WALL_WEST Window5 Detailed Fenestration WINDOW_U_0.57_SHGC_WEST_0.25 N/A 3.241 No 77.26 77.26 77.26 270.00 90.00 48.74 1.59 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
121 PERIMETER_MID_ZN_4_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 135.00 90.00 6.47 2.74 0.00 PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
122 DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 90.00 90.00 39.59 2.74 0.00 DATACENTER_MID_ZN_6_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
123 PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 45.00 90.00 6.47 2.74 0.00 PERIMETER_MID_ZN_3_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
124 PERIMETER_MID_ZN_4_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   201.98 201.98 201.98 315.00 180.00 6.47 39.59 0.00 PERIMETER_MID_ZN_4_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
125 PERIMETER_MID_ZN_4_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   201.98 201.98 201.98 135.00 0.00 6.47 48.74 0.00 iz-PERIMETER_MID_ZN_4_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
126 PERIMETER_MID_ZN_4_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   403.95 403.95 403.95 0.00 90.00 403.95 1.00 0.00 PERIMETER_MID_ZN_4_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
127 PERIMETER_TOP_ZN_3_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 5.069 2.882   84.71 200.61 84.71 0.00 90.00 73.11 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
128 PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW Window PERIMETER_TOP_ZN_3_WALL_NORTH Window5 Detailed Fenestration WINDOW_U_0.57_SHGC_NORTH_0.25 N/A 3.241 No 115.90 115.90 115.90 0.00 90.00 73.11 1.59 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
129 PERIMETER_TOP_ZN_3_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 225.00 90.00 6.47 2.74 0.00 PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
130 CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   173.00 173.00 173.00 180.00 90.00 63.05 2.74 0.00 CORE_TOP_ZN_5_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
131 PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 135.00 90.00 6.47 2.74 0.00 PERIMETER_TOP_ZN_2_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
132 DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   2.51 2.51 2.51 180.00 90.00 0.91 2.74 0.00 DATACENTER_TOP_ZN_6_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
133 PERIMETER_TOP_ZN_3_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   313.41 313.41 313.41 0.00 180.00 63.96 6.47 0.00 PERIMETER_TOP_ZN_3_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
134 PERIMETER_TOP_ZN_3_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   313.41 313.41 313.41 180.00 0.00 63.96 6.47 0.00 iz-PERIMETER_TOP_ZN_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
135 PERIMETER_TOP_ZN_3_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   626.83 626.83 626.83 0.00 90.00 626.83 1.00 0.00 PERIMETER_TOP_ZN_3_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
136 PERIMETER_TOP_ZN_2_WALL_EAST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 5.069 2.882   56.47 133.74 56.47 90.00 90.00 48.74 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
137 PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW Window PERIMETER_TOP_ZN_2_WALL_EAST Window5 Detailed Fenestration WINDOW_U_0.57_SHGC_EAST_0.25 N/A 3.241 No 77.26 77.26 77.26 90.00 90.00 48.74 1.59 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
138 PERIMETER_TOP_ZN_2_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 315.00 90.00 6.47 2.74 0.00 PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
139 CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 270.00 90.00 39.59 2.74 0.00 CORE_TOP_ZN_5_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
140 INT-PER3S-NE-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 225.00 90.00 6.47 2.74 0.00 INT-PER3S-NE Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
141 PERIMETER_TOP_ZN_2_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   201.98 201.98 201.98 45.00 180.00 6.47 48.74 0.00 PERIMETER_TOP_ZN_2_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
142 PERIMETER_TOP_ZN_2_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   201.98 201.98 201.98 225.00 0.00 6.47 39.59 0.00 iz-PERIMETER_TOP_ZN_2_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
143 PERIMETER_TOP_ZN_2_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   403.95 403.95 403.95 0.00 90.00 403.95 1.00 0.00 PERIMETER_TOP_ZN_2_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
144 PERIMETER_TOP_ZN_1_WALL_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 5.069 2.882   84.71 200.61 84.71 180.00 90.00 73.11 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
145 PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW Window PERIMETER_TOP_ZN_1_WALL_SOUTH Window5 Detailed Fenestration WINDOW_U_0.57_SHGC_SOUTH_0.25 N/A 3.241 No 115.90 115.90 115.90 180.00 90.00 73.11 1.59 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
146 INT-PER3S-NE Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 45.00 90.00 6.47 2.74 0.00 INT-PER3S-NE-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
147 DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   2.51 2.51 2.51 0.00 90.00 0.91 2.74 0.00 DATACENTER_TOP_ZN_6_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
148 PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 315.00 90.00 6.47 2.74 0.00 PERIMETER_TOP_ZN_4_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
149 CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   173.00 173.00 173.00 0.00 90.00 63.05 2.74 0.00 CORE_TOP_ZN_5_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
150 PERIMETER_TOP_ZN_1_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   313.42 313.42 313.42 0.00 180.00 73.11 6.47 0.00 PERIMETER_TOP_ZN_1_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
151 PERIMETER_TOP_ZN_1_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   313.42 313.42 313.42 180.00 0.00 73.11 6.47 0.00 iz-PERIMETER_TOP_ZN_1_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
152 PERIMETER_TOP_ZN_1_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   626.84 626.84 626.84 0.00 90.00 626.84 1.00 0.00 PERIMETER_TOP_ZN_1_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
153 PERIMETER_TOP_ZN_4_WALL_WEST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 5.069 2.882   56.47 133.74 56.47 270.00 90.00 48.74 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
154 PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW Window PERIMETER_TOP_ZN_4_WALL_WEST Window5 Detailed Fenestration WINDOW_U_0.57_SHGC_WEST_0.25 N/A 3.241 No 77.26 77.26 77.26 270.00 90.00 48.74 1.59 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
155 PERIMETER_TOP_ZN_4_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 135.00 90.00 6.47 2.74 0.00 PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
156 DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 90.00 90.00 39.59 2.74 0.00 DATACENTER_TOP_ZN_6_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
157 PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 45.00 90.00 6.47 2.74 0.00 PERIMETER_TOP_ZN_3_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
158 PERIMETER_TOP_ZN_4_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   201.98 201.98 201.98 315.00 180.00 6.47 39.59 0.00 PERIMETER_TOP_ZN_4_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
159 PERIMETER_TOP_ZN_4_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   201.98 201.98 201.98 135.00 0.00 6.47 48.74 0.00 iz-PERIMETER_TOP_ZN_4_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
160 PERIMETER_TOP_ZN_4_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   403.95 403.95 403.95 0.00 90.00 403.95 1.00 0.00 PERIMETER_TOP_ZN_4_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
161 GROUNDFLOOR_PLENUM_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 5.069 2.882   89.13 89.13 89.13 0.00 90.00 73.11 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
162 GROUNDFLOOR_PLENUM_WEST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 5.069 2.882   59.42 59.42 59.42 270.00 90.00 48.74 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
163 GROUNDFLOOR_PLENUM_WALL_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 5.069 2.882   89.13 89.13 89.13 180.00 90.00 73.11 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
164 GROUNDFLOOR_PLENUM_WALL_EAST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 5.069 2.882   59.42 59.42 59.42 90.00 90.00 48.74 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
165 iz-CORE_BOT_ZN_5_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   2496.12 2496.12 2496.12 0.00 180.00 63.05 39.59 0.00 CORE_BOT_ZN_5_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
166 iz-PERIMETER_BOT_ZN_3_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   313.41 313.41 313.41 0.00 180.00 63.96 6.47 0.00 PERIMETER_BOT_ZN_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
167 iz-PERIMETER_BOT_ZN_2_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   201.98 201.98 201.98 45.00 180.00 6.47 48.74 0.00 PERIMETER_BOT_ZN_2_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
168 iz-PERIMETER_BOT_ZN_1_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   313.42 313.42 313.42 0.00 180.00 73.11 6.47 0.00 PERIMETER_BOT_ZN_1_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
169 iz-PERIMETER_BOT_ZN_4_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   201.98 201.98 201.98 315.00 180.00 6.47 39.59 0.00 PERIMETER_BOT_ZN_4_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
170 iz-DATACENTER_BOT_ZN_6_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   36.20 36.20 36.20 0.00 180.00 0.91 39.59 0.00 DATACENTER_BOT_ZN_6_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
171 GROUNDFLOOR_PLENUM_CEILING Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   3563.11 3563.11 3563.11 180.00 0.00 73.11 48.74 0.00 GROUNDFLOOR_PLENUM_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
172 MIDFLOOR_PLENUM_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 5.069 2.882   89.13 89.13 89.13 0.00 90.00 73.11 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
173 MIDFLOOR_PLENUM_WALL_WEST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 5.069 2.882   59.42 59.42 59.42 270.00 90.00 48.74 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
174 MIDFLOOR_PLENUM_WALL_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 5.069 2.882   89.13 89.13 89.13 180.00 90.00 73.11 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
175 MIDFLOOR_PLENUM_WALL_EAST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 5.069 2.882   59.42 59.42 59.42 90.00 90.00 48.74 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
176 iz-CORE_MID_ZN_5_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   2496.12 2496.12 2496.12 0.00 180.00 63.05 39.59 0.00 CORE_MID_ZN_5_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
177 iz-PERIMETER_MID_ZN_3_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   313.41 313.41 313.41 0.00 180.00 63.96 6.47 0.00 PERIMETER_MID_ZN_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
178 iz-PERIMETER_MID_ZN_2_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   201.98 201.98 201.98 45.00 180.00 6.47 48.74 0.00 PERIMETER_MID_ZN_2_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
179 iz-PERIMETER_MID_ZN_1_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   313.42 313.42 313.42 0.00 180.00 73.11 6.47 0.00 PERIMETER_MID_ZN_1_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
180 iz-PERIMETER_MID_ZN_4_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   201.98 201.98 201.98 315.00 180.00 6.47 39.59 0.00 PERIMETER_MID_ZN_4_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
181 iz-DATACENTER_MID_ZN_6_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   36.20 36.20 36.20 0.00 180.00 0.91 39.59 0.00 DATACENTER_MID_ZN_6_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
182 MIDFLOOR_PLENUM_CEILING Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   3563.11 3563.11 3563.11 180.00 0.00 73.11 48.74 0.00 MIDFLOOR_PLENUM_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
183 TOPFLOOR_PLENUM_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 5.069 2.882   89.13 89.13 89.13 180.00 90.00 73.11 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
184 TOPFLOOR_PLENUM_WALL_EAST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 5.069 2.882   59.42 59.42 59.42 90.00 90.00 48.74 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
185 TOPFLOOR_PLENUM_WALL_WEST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 5.069 2.882   59.42 59.42 59.42 270.00 90.00 48.74 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
186 TOPFLOOR_PLENUM_WALL_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 5.069 2.882   89.13 89.13 89.13 0.00 90.00 73.11 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
187 iz-CORE_TOP_ZN_5_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   2496.12 2496.12 2496.12 0.00 180.00 63.05 39.59 0.00 CORE_TOP_ZN_5_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
188 iz-PERIMETER_TOP_ZN_3_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   313.41 313.41 313.41 0.00 180.00 63.96 6.47 0.00 PERIMETER_TOP_ZN_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
189 iz-PERIMETER_TOP_ZN_2_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   201.98 201.98 201.98 45.00 180.00 6.47 48.74 0.00 PERIMETER_TOP_ZN_2_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
190 iz-PERIMETER_TOP_ZN_1_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   313.42 313.42 313.42 0.00 180.00 73.11 6.47 0.00 PERIMETER_TOP_ZN_1_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
191 iz-PERIMETER_TOP_ZN_4_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   201.98 201.98 201.98 315.00 180.00 6.47 39.59 0.00 PERIMETER_TOP_ZN_4_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
192 iz-DATACENTER_TOP_ZN_6_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   36.20 36.20 36.20 0.00 180.00 0.91 39.59 0.00 DATACENTER_TOP_ZN_6_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
193 BUILDING_ROOF Roof   CTF - ConductionTransferFunction NONRES_ROOF 0.283 0.269   3563.11 3563.11 3563.11 180.00 0.00 73.11 48.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 4
194 DATACENTER_BOT_ZN_6_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   2.51 2.51 2.51 0.00 90.00 0.91 2.74 0.00 DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
195 DATACENTER_BOT_ZN_6_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   2.51 2.51 2.51 180.00 90.00 0.91 2.74 0.00 DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
196 DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 90.00 90.00 39.59 2.74 0.00 CORE_BOT_ZN_5_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
197 DATACENTER_BOT_ZN_6_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 270.00 90.00 39.59 2.74 0.00 DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
198 DATACENTER_BOT_ZN_6_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   36.20 36.20 36.20 0.00 180.00 0.91 39.59 0.00 DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.00 1.00 0.00 4
199 DATACENTER_BOT_ZN_6_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   36.20 36.20 36.20 180.00 0.00 0.91 39.59 0.00 iz-DATACENTER_BOT_ZN_6_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
200 DATACENTER_MID_ZN_6_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 270.00 90.00 39.59 2.74 0.00 DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
201 DATACENTER_MID_ZN_6_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   2.51 2.51 2.51 180.00 90.00 0.91 2.74 0.00 DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
202 DATACENTER_MID_ZN_6_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 90.00 90.00 39.59 2.74 0.00 CORE_MID_ZN_5_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
203 DATACENTER_MID_ZN_6_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   2.51 2.51 2.51 0.00 90.00 0.91 2.74 0.00 DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
204 DATACENTER_MID_ZN_6_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   36.20 36.20 36.20 0.00 180.00 0.91 39.59 0.00 DATACENTER_MID_ZN_6_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.00 1.00 0.00 4
205 DATACENTER_MID_ZN_6_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   36.20 36.20 36.20 180.00 0.00 0.91 39.59 0.00 iz-DATACENTER_MID_ZN_6_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
206 DATACENTER_TOP_ZN_6_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 90.00 90.00 39.59 2.74 0.00 CORE_TOP_ZN_5_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
207 DATACENTER_TOP_ZN_6_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 270.00 90.00 39.59 2.74 0.00 DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
208 DATACENTER_TOP_ZN_6_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   2.51 2.51 2.51 180.00 90.00 0.91 2.74 0.00 DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
209 DATACENTER_TOP_ZN_6_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   2.51 2.51 2.51 0.00 90.00 0.91 2.74 0.00 DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
210 DATACENTER_TOP_ZN_6_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   36.20 36.20 36.20 0.00 180.00 0.91 39.59 0.00 DATACENTER_TOP_ZN_6_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.00 1.00 0.00 4
211 DATACENTER_TOP_ZN_6_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   36.20 36.20 36.20 180.00 0.00 0.91 39.59 0.00 iz-DATACENTER_TOP_ZN_6_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
212 DATACENTER_BASEMENT_ZN_6_WALL_NORTH Wall   CTF - ConductionTransferFunction DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR 0.940 0.824   39.22 39.22 39.22 0.00 90.00 16.08 2.44 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
213 DATACENTER_BASEMENT_ZN_6_WALL_SOUTH Wall   CTF - ConductionTransferFunction DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR 0.940 0.824   39.22 39.22 39.22 180.00 90.00 16.08 2.44 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
214 DATACENTER_BASEMENT_ZN_6_WALL_WEST Wall   CTF - ConductionTransferFunction DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR 0.940 0.824   118.87 118.87 118.87 270.00 90.00 48.74 2.44 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
215 DATACENTER_BASEMENT_ZN_6_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   118.87 118.87 118.87 90.00 90.00 48.74 2.44 0.00 BASEMENT_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
216 DATACENTER_BASEMENT_ZN_6_FLOOR Floor   CTF - ConductionTransferFunction EXT_SLAB_8IN_WITH_CARPET 3.285 1.827   783.68 783.68 783.68 0.00 180.00 16.08 48.74 0.00 DATACENTER_BASEMENT_ZN_6_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.00 1.00 0.00 4
217 DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   36.20 36.20 36.20 180.00 0.00 0.91 39.59 0.00 DATACENTER_BOT_ZN_6_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
218 DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   419.35 419.35 419.35 180.00 0.00 10.59 39.59 0.00 DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
219 PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   201.98 201.98 201.98 135.00 0.00 6.47 48.74 0.00 PERIMETER_BOT_ZN_4_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
220 DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   63.08 63.08 63.08 180.00 0.00 16.08 6.47 0.00 DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
221 DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   63.07 63.07 63.07 180.00 0.00 11.51 6.47 0.00 DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4


Environment

Environment Name Environment Type Start Date End Date Start DayOfWeek Duration {#days} Source:Start DayOfWeek Use Daylight Saving Use Holidays Apply Weekend Holiday Rule Use Rain Values Use Snow Values Sky Temperature Model
1 RUNPERIOD 1 WeatherFileRunPeriod 01/01/2017 12/31/2017 Sunday 365 Use RunPeriod Specified Day No No No Yes Yes Clark and Allen


Environment:Special Days

Special Day Name Special Day Type Source Start Date Duration {#days}
1 NEW YEARS DAY Holiday InputFile 01/01 1Environment:Special Days


Environment:Daylight Saving

Daylight Saving Indicator Source Start Date End Date
1 Yes InputFile 03/12 11/05


Tabular Report

Style Unit Conversion
1 Commaandhtml commaandhtml


Warmup Convergence Information

Zone Name Environment Type/Name Average Warmup Temperature Difference {deltaC} Std Dev Warmup Temperature Difference {deltaC} Max Temperature Pass/Fail Convergence Min Temperature Pass/Fail Convergence Average Warmup Load Difference {W} Std Dev Warmup Load Difference {W} Heating Load Pass/Fail Convergence Cooling Load Pass/Fail Convergence
1 BASEMENT RunPeriod: RUNPERIOD 1 0.1965764643 0.1879990623 Pass Pass 10.9405376805 52.5359962997 Fail Fail
2 CORE_BOTTOM RunPeriod: RUNPERIOD 1 0.2469942880 0.2458563307 Pass Pass 0.2658762625 0.4401645654 Pass Fail
3 CORE_MID RunPeriod: RUNPERIOD 1 0.1722776462 0.2182970775 Pass Pass 0.2252021402 0.4167739800 Pass Pass
4 CORE_TOP RunPeriod: RUNPERIOD 1 0.1596079530 0.2259485400 Pass Pass 0.2167287868 0.4099113390 Pass Pass
5 PERIMETER_BOT_ZN_3 RunPeriod: RUNPERIOD 1 0.2233104807 0.2353060664 Pass Pass 0.2651338767 0.4388148866 Pass Pass
6 PERIMETER_BOT_ZN_2 RunPeriod: RUNPERIOD 1 0.3724366265 0.4415284065 Pass Pass 0.2744819168 0.4425758042 Pass Fail
7 PERIMETER_BOT_ZN_1 RunPeriod: RUNPERIOD 1 0.3760137065 0.4949899709 Pass Pass 0.3097110435 0.4973453577 Pass Fail
8 PERIMETER_BOT_ZN_4 RunPeriod: RUNPERIOD 1 0.3859746766 0.4282168533 Pass Pass 0.2694189702 0.4379826964 Pass Pass
9 PERIMETER_MID_ZN_3 RunPeriod: RUNPERIOD 1 0.1648464180 0.2110506725 Pass Pass 0.2235777907 0.4154179223 Pass Pass
10 PERIMETER_MID_ZN_2 RunPeriod: RUNPERIOD 1 0.2920433124 0.3825261230 Pass Pass 0.2252738429 0.4152628372 Pass Fail
11 PERIMETER_MID_ZN_1 RunPeriod: RUNPERIOD 1 0.3137077728 0.4790865164 Pass Pass 0.2536081777 0.4603684026 Pass Pass
12 PERIMETER_MID_ZN_4 RunPeriod: RUNPERIOD 1 0.2635868884 0.3382901701 Pass Pass 0.2253688571 0.4146073336 Pass Pass
13 PERIMETER_TOP_ZN_3 RunPeriod: RUNPERIOD 1 0.1615534918 0.2276556005 Pass Pass 0.2165434762 0.4086072433 Pass Pass
14 PERIMETER_TOP_ZN_2 RunPeriod: RUNPERIOD 1 0.2735978881 0.3539023030 Pass Pass 0.2173003321 0.4104958273 Pass Fail
15 PERIMETER_TOP_ZN_1 RunPeriod: RUNPERIOD 1 0.3044039165 0.4898290420 Pass Pass 0.2495221317 0.4575982198 Pass Pass
16 PERIMETER_TOP_ZN_4 RunPeriod: RUNPERIOD 1 0.2613458970 0.3816448902 Pass Pass 0.2179328133 0.4072918359 Pass Pass
17 GROUNDFLOOR_PLENUM RunPeriod: RUNPERIOD 1 6.2378540724E-002 5.5118770353E-002 Pass Pass 0.2904300150 0.4627411463 Pass Pass
18 MIDFLOOR_PLENUM RunPeriod: RUNPERIOD 1 5.4696368414E-002 5.9095607448E-002 Pass Pass 0.2260637544 0.4023077069 Fail Pass
19 TOPFLOOR_PLENUM RunPeriod: RUNPERIOD 1 7.1593282759E-002 7.8559132124E-002 Pass Pass 0.2256093402 0.4211591800 Fail Pass
20 DATACENTER_BOT_ZN_6 RunPeriod: RUNPERIOD 1 1.6300245107E-004 2.8117942959E-004 Pass Pass 2.7117362290E-003 2.3188789622E-003 Pass Pass
21 DATACENTER_MID_ZN_6 RunPeriod: RUNPERIOD 1 3.1384759662E-006 5.7460570759E-006 Pass Pass 3.9563352492E-003 4.0329396402E-003 Pass Pass
22 DATACENTER_TOP_ZN_6 RunPeriod: RUNPERIOD 1 2.6172133256E-006 4.6936045318E-006 Pass Pass 6.3218100801E-003 4.7252104119E-003 Pass Pass
23 DATACENTER_BASEMENT_ZN_6 RunPeriod: RUNPERIOD 1 2.4842893551E-004 2.3608527456E-004 Pass Pass 4.7334144199E-005 1.1087362835E-004 Pass Pass



Table of Contents

Report: Annual Heat Emissions Summary

For: Entire Facility

Timestamp: 2023-10-16 08:43:45

Heat Emission by Components

Envelope Convection Zone Exfiltration Zone Exhaust Air HVAC Relief Air HVAC Reject Heat Total
Heat Emissions [GJ] 5330.37 -141.1 0.00 -14566.7 45404.16 36026.74



Table of Contents

Report: Climatic Data Summary

For: Entire Facility

Timestamp: 2023-10-16 08:43:45

SizingPeriod:DesignDay

Maximum Dry Bulb [C] Daily Temperature Range [deltaC] Humidity Value Humidity Type Wind Speed [m/s] Wind Direction
MIAMI INTL AP ANN HTG 99.6% CONDNS DB 8.70 0.00 8.70 Wetbulb [C] 3.80 340.00
MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 33.20 6.70 25.30 Wetbulb [C] 4.50 140.00


Monthly Precipitation Summary

Monthly Total Precipitation from .epw [mm] Monthly Total Hours of Rain from .epw Monthly Total Precipitation in Site:Precipitation [mm] Monthly Total Roof Irrigation Depth [mm] Monthly Total Rain Collection Volume [m3]
Jan 65.00 29      
Feb 0.00 0      
Mar 0.00 0      
Apr 38.00 14      
May 0.00 0      
Jun 0.00 0      
Jul 0.00 0      
Aug 391.00 83      
Sep 0.00 0      
Oct 225.00 40      
Nov 0.00 0      
Dec 5.00 10      


Weather Statistics File

Value
None  



Table of Contents

Report: Envelope Summary

For: Entire Facility

Timestamp: 2023-10-16 08:43:45

Opaque Exterior

Construction Reflectance U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Net Area [m2] Azimuth [deg] Tilt [deg] Cardinal Direction
BASEMENT_WALL_EAST BASEMENT_WALL_EAST_CFACTOR 1.00 0.845 0.940 118.87 118.87 90.00 90.00 E
BASEMENT_WALL_SOUTH BASEMENT_WALL_SOUTH_CFACTOR 1.00 0.845 0.940 139.09 139.09 180.00 90.00 S
BASEMENT_WALL_NORTH BASEMENT_WALL_NORTH_CFACTOR 1.00 0.845 0.940 139.09 139.09 0.00 90.00 N
PERIMETER_BOT_ZN_3_WALL_NORTH NONRES_EXT_WALL_GRD 0.30 2.882 5.069 200.61 76.91 0.00 90.00 N
PERIMETER_BOT_ZN_2_WALL_EAST NONRES_EXT_WALL_GRD 0.30 2.882 5.069 133.74 52.57 90.00 90.00 E
PERIMETER_BOT_ZN_1_WALL_SOUTH NONRES_EXT_WALL_GRD 0.30 2.882 5.069 200.61 76.91 180.00 90.00 S
PERIMETER_BOT_ZN_4_WALL_WEST NONRES_EXT_WALL_GRD 0.30 2.882 5.069 133.74 52.57 270.00 90.00 W
PERIMETER_MID_ZN_3_WALL_NORTH NONRES_EXT_WALL_MID 0.30 2.882 5.069 2006.06 847.11 0.00 90.00 N
PERIMETER_MID_ZN_2_WALL_EAST NONRES_EXT_WALL_MID 0.30 2.882 5.069 1337.37 564.74 90.00 90.00 E
PERIMETER_MID_ZN_1_WALL_SOUTH NONRES_EXT_WALL_MID 0.30 2.882 5.069 2006.06 847.11 180.00 90.00 S
PERIMETER_MID_ZN_4_WALL_WEST NONRES_EXT_WALL_MID 0.30 2.882 5.069 1337.37 564.74 270.00 90.00 W
PERIMETER_TOP_ZN_3_WALL_NORTH NONRES_EXT_WALL_TOP 0.30 2.882 5.069 200.61 84.71 0.00 90.00 N
PERIMETER_TOP_ZN_2_WALL_EAST NONRES_EXT_WALL_TOP 0.30 2.882 5.069 133.74 56.47 90.00 90.00 E
PERIMETER_TOP_ZN_1_WALL_SOUTH NONRES_EXT_WALL_TOP 0.30 2.882 5.069 200.61 84.71 180.00 90.00 S
PERIMETER_TOP_ZN_4_WALL_WEST NONRES_EXT_WALL_TOP 0.30 2.882 5.069 133.74 56.47 270.00 90.00 W
GROUNDFLOOR_PLENUM_WALL_NORTH NONRES_EXT_WALL_GRD 0.30 2.882 5.069 89.13 89.13 0.00 90.00 N
GROUNDFLOOR_PLENUM_WEST NONRES_EXT_WALL_GRD 0.30 2.882 5.069 59.42 59.42 270.00 90.00 W
GROUNDFLOOR_PLENUM_WALL_SOUTH NONRES_EXT_WALL_GRD 0.30 2.882 5.069 89.13 89.13 180.00 90.00 S
GROUNDFLOOR_PLENUM_WALL_EAST NONRES_EXT_WALL_GRD 0.30 2.882 5.069 59.42 59.42 90.00 90.00 E
MIDFLOOR_PLENUM_WALL_NORTH NONRES_EXT_WALL_MID 0.30 2.882 5.069 891.32 891.32 0.00 90.00 N
MIDFLOOR_PLENUM_WALL_WEST NONRES_EXT_WALL_MID 0.30 2.882 5.069 594.21 594.21 270.00 90.00 W
MIDFLOOR_PLENUM_WALL_SOUTH NONRES_EXT_WALL_MID 0.30 2.882 5.069 891.32 891.32 180.00 90.00 S
MIDFLOOR_PLENUM_WALL_EAST NONRES_EXT_WALL_MID 0.30 2.882 5.069 594.21 594.21 90.00 90.00 E
TOPFLOOR_PLENUM_WALL_NORTH NONRES_EXT_WALL_TOP 0.30 2.882 5.069 89.13 89.13 180.00 90.00 S
TOPFLOOR_PLENUM_WALL_EAST NONRES_EXT_WALL_TOP 0.30 2.882 5.069 59.42 59.42 90.00 90.00 E
TOPFLOOR_PLENUM_WALL_WEST NONRES_EXT_WALL_TOP 0.30 2.882 5.069 59.42 59.42 270.00 90.00 W
TOPFLOOR_PLENUM_WALL_SOUTH NONRES_EXT_WALL_TOP 0.30 2.882 5.069 89.13 89.13 0.00 90.00 N
BUILDING_ROOF NONRES_ROOF 0.55 0.273 0.283 3563.11 3563.11 180.00 0.00  
DATACENTER_BASEMENT_ZN_6_WALL_NORTH DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR 1.00 0.845 0.940 39.22 39.22 0.00 90.00 N
DATACENTER_BASEMENT_ZN_6_WALL_SOUTH DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR 1.00 0.845 0.940 39.22 39.22 180.00 90.00 S
DATACENTER_BASEMENT_ZN_6_WALL_WEST DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR 1.00 0.845 0.940 118.87 118.87 270.00 90.00 W


Opaque Interior

Construction Reflectance U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Net Area [m2] Azimuth [deg] Tilt [deg] Cardinal Direction
BASEMENT_WALL_WEST INT_WALL 0.30 2.511 6.299 118.87 118.87 270.00 90.00 W
BASEMENT_FLOOR EXT_SLAB_8IN_WITH_CARPET 0.30 1.591 3.285 2779.43 2779.43 0.00 180.00  
PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER INT_SLAB_CEILING 0.30 1.887 3.839 201.98 201.98 225.00 0.00  
PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER INT_SLAB_CEILING 0.30 1.887 3.839 250.34 250.34 180.00 0.00  
CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER INT_SLAB_CEILING 0.30 1.887 3.839 2076.77 2076.77 180.00 0.00  
PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER INT_SLAB_CEILING 0.30 1.887 3.839 250.34 250.34 180.00 0.00  
CORE_BOT_ZN_5_WALL_SOUTH INT_WALL 0.30 2.511 6.299 173.00 173.00 180.00 90.00 S
CORE_BOT_ZN_5_WALL_WEST INT_WALL 0.30 2.511 6.299 108.64 108.64 270.00 90.00 W
CORE_BOT_ZN_5_WALL_NORTH INT_WALL 0.30 2.511 6.299 173.00 173.00 0.00 90.00 N
CORE_BOT_ZN_5_WALL_EAST INT_WALL 0.30 2.511 6.299 108.64 108.64 90.00 90.00 E
DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER INT_SLAB_FLOOR 0.30 1.887 3.839 419.30 419.30 0.00 180.00  
CORE_BOT_ZN_5_FLOOR INT_SLAB_FLOOR 0.30 1.887 3.839 2076.82 2076.82 0.00 180.00  
CORE_BOT_ZN_5_CEILING DROPCEILING 0.30 2.031 4.488 2496.12 2496.12 180.00 0.00  
CORE_MID_ZN_5_WALL_SOUTH INT_WALL 0.30 2.511 6.299 1729.99 1729.99 180.00 90.00 S
CORE_MID_ZN_5_WALL_WEST INT_WALL 0.30 2.511 6.299 1086.40 1086.40 270.00 90.00 W
CORE_MID_ZN_5_WALL_NORTH INT_WALL 0.30 2.511 6.299 1729.99 1729.99 0.00 90.00 N
CORE_MID_ZN_5_WALL_EAST INT_WALL 0.30 2.511 6.299 1086.40 1086.40 90.00 90.00 E
CORE_MID_ZN_5_FLOOR INT_SLAB_FLOOR 0.30 1.711 3.839 24961.20 24961.20 0.00 180.00  
CORE_MID_ZN_5_CEILING DROPCEILING 0.30 2.031 4.488 24961.20 24961.20 180.00 0.00  
CORE_TOP_ZN_5_WALL_SOUTH INT_WALL 0.30 2.511 6.299 173.00 173.00 180.00 90.00 S
CORE_TOP_ZN_5_WALL_WEST INT_WALL 0.30 2.511 6.299 108.64 108.64 270.00 90.00 W
CORE_TOP_ZN_5_WALL_NORTH INT_WALL 0.30 2.511 6.299 173.00 173.00 0.00 90.00 N
CORE_TOP_ZN_5_WALL_EAST INT_WALL 0.30 2.511 6.299 108.64 108.64 90.00 90.00 E
CORE_TOP_ZN_5_FLOOR INT_SLAB_FLOOR 0.30 1.711 3.839 2496.12 2496.12 0.00 180.00  
CORE_TOP_ZN_5_CEILING DROPCEILING 0.30 2.031 4.488 2496.12 2496.12 180.00 0.00  
PERIMETER_BOT_ZN_3_WALL_WEST INT_WALL 0.30 2.511 6.299 17.75 17.75 225.00 90.00 W
CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 173.00 173.00 180.00 90.00 S
PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 17.75 17.75 135.00 90.00 S
DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 2.51 2.51 180.00 90.00 S
PERIMETER_BOT_ZN_3_FLOOR INT_SLAB_FLOOR 0.30 1.887 3.839 250.34 250.34 0.00 180.00  
DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER INT_SLAB_FLOOR 0.30 1.887 3.839 63.07 63.07 0.00 180.00  
PERIMETER_BOT_ZN_3_CEILING DROPCEILING 0.30 2.031 4.488 313.41 313.41 180.00 0.00  
PERIMETER_BOT_ZN_2_WALL_NORTH INT_WALL 0.30 2.511 6.299 17.75 17.75 315.00 90.00 N
CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 108.64 108.64 270.00 90.00 W
PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 17.75 17.75 225.00 90.00 W
PERIMETER_BOT_ZN_2_FLOOR INT_SLAB_FLOOR 0.30 1.887 3.839 201.98 201.98 45.00 180.00  
PERIMETER_BOT_ZN_2_CEILING DROPCEILING 0.30 2.031 4.488 201.98 201.98 225.00 0.00  
PERIMETER_BOT_ZN_1_WALL_EAST INT_WALL 0.30 2.511 6.299 17.75 17.75 45.00 90.00 E
DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 2.51 2.51 0.00 90.00 N
PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 17.75 17.75 315.00 90.00 N
CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 173.00 173.00 0.00 90.00 N
DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER INT_SLAB_FLOOR 0.30 1.887 3.839 63.07 63.07 0.00 180.00  
PERIMETER_BOT_ZN_1_FLOOR INT_SLAB_FLOOR 0.30 1.887 3.839 250.35 250.35 0.00 180.00  
PERIMETER_BOT_ZN_1_CEILING DROPCEILING 0.30 2.031 4.488 313.42 313.42 180.00 0.00  
PERIMETER_BOT_ZN_4_WALL_SOUTH INT_WALL 0.30 2.511 6.299 17.75 17.75 135.00 90.00 S
DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 108.64 108.64 90.00 90.00 E
PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 17.75 17.75 45.00 90.00 E
PERIMETER_BOT_ZN_4_FLOOR INT_SLAB_FLOOR 0.30 1.887 3.839 201.98 201.98 315.00 180.00  
PERIMETER_BOT_ZN_4_CEILING DROPCEILING 0.30 2.031 4.488 201.98 201.98 135.00 0.00  
PERIMETER_MID_ZN_3_WALL_WEST INT_WALL 0.30 2.511 6.299 177.47 177.47 225.00 90.00 W
CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 1729.99 1729.99 180.00 90.00 S
PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 177.47 177.47 135.00 90.00 S
DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 25.09 25.09 180.00 90.00 S
PERIMETER_MID_ZN_3_FLOOR INT_SLAB_FLOOR 0.30 1.711 3.839 3134.13 3134.13 0.00 180.00  
PERIMETER_MID_ZN_3_CEILING DROPCEILING 0.30 2.031 4.488 3134.13 3134.13 180.00 0.00  
PERIMETER_MID_ZN_2_WALL_NORTH INT_WALL 0.30 2.511 6.299 177.47 177.47 315.00 90.00 N
CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 1086.40 1086.40 270.00 90.00 W
PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 177.47 177.47 225.00 90.00 W
PERIMETER_MID_ZN_2_FLOOR INT_SLAB_FLOOR 0.30 1.711 3.839 2019.75 2019.75 45.00 180.00  
PERIMETER_MID_ZN_2_CEILING DROPCEILING 0.30 2.031 4.488 2019.75 2019.75 225.00 0.00  
PERIMETER_MID_ZN_1_WALL_EAST INT_WALL 0.30 2.511 6.299 177.47 177.47 45.00 90.00 E
DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 25.09 25.09 0.00 90.00 N
PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 177.47 177.47 315.00 90.00 N
CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 1729.99 1729.99 0.00 90.00 N
PERIMETER_MID_ZN_1_FLOOR INT_SLAB_FLOOR 0.30 1.711 3.839 3134.20 3134.20 0.00 180.00  
PERIMETER_MID_ZN_1_CEILING DROPCEILING 0.30 2.031 4.488 3134.20 3134.20 180.00 0.00  
PERIMETER_MID_ZN_4_WALL_SOUTH INT_WALL 0.30 2.511 6.299 177.47 177.47 135.00 90.00 S
DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 1086.40 1086.40 90.00 90.00 E
PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 177.47 177.47 45.00 90.00 E
PERIMETER_MID_ZN_4_FLOOR INT_SLAB_FLOOR 0.30 1.711 3.839 2019.75 2019.75 315.00 180.00  
PERIMETER_MID_ZN_4_CEILING DROPCEILING 0.30 2.031 4.488 2019.75 2019.75 135.00 0.00  
PERIMETER_TOP_ZN_3_WALL_WEST INT_WALL 0.30 2.511 6.299 17.75 17.75 225.00 90.00 W
CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 173.00 173.00 180.00 90.00 S
PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 17.75 17.75 135.00 90.00 S
DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 2.51 2.51 180.00 90.00 S
PERIMETER_TOP_ZN_3_FLOOR INT_SLAB_FLOOR 0.30 1.711 3.839 313.41 313.41 0.00 180.00  
PERIMETER_TOP_ZN_3_CEILING DROPCEILING 0.30 2.031 4.488 313.41 313.41 180.00 0.00  
PERIMETER_TOP_ZN_2_WALL_NORTH INT_WALL 0.30 2.511 6.299 17.75 17.75 315.00 90.00 N
CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 108.64 108.64 270.00 90.00 W
INT-PER3S-NE-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 17.75 17.75 225.00 90.00 W
PERIMETER_TOP_ZN_2_FLOOR INT_SLAB_FLOOR 0.30 1.711 3.839 201.98 201.98 45.00 180.00  
PERIMETER_TOP_ZN_2_CEILING DROPCEILING 0.30 2.031 4.488 201.98 201.98 225.00 0.00  
INT-PER3S-NE INT_WALL 0.30 2.511 6.299 17.75 17.75 45.00 90.00 E
DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 2.51 2.51 0.00 90.00 N
PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 17.75 17.75 315.00 90.00 N
CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 173.00 173.00 0.00 90.00 N
PERIMETER_TOP_ZN_1_FLOOR INT_SLAB_FLOOR 0.30 1.711 3.839 313.42 313.42 0.00 180.00  
PERIMETER_TOP_ZN_1_CEILING DROPCEILING 0.30 2.031 4.488 313.42 313.42 180.00 0.00  
PERIMETER_TOP_ZN_4_WALL_SOUTH INT_WALL 0.30 2.511 6.299 17.75 17.75 135.00 90.00 S
DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 108.64 108.64 90.00 90.00 E
PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 17.75 17.75 45.00 90.00 E
PERIMETER_TOP_ZN_4_FLOOR INT_SLAB_FLOOR 0.30 1.711 3.839 201.98 201.98 315.00 180.00  
PERIMETER_TOP_ZN_4_CEILING DROPCEILING 0.30 2.031 4.488 201.98 201.98 135.00 0.00  
iz-CORE_BOT_ZN_5_CEILING DROPCEILING 0.30 2.031 4.488 2496.12 2496.12 0.00 180.00  
iz-PERIMETER_BOT_ZN_3_CEILING DROPCEILING 0.30 2.031 4.488 313.41 313.41 0.00 180.00  
iz-PERIMETER_BOT_ZN_2_CEILING DROPCEILING 0.30 2.031 4.488 201.98 201.98 45.00 180.00  
iz-PERIMETER_BOT_ZN_1_CEILING DROPCEILING 0.30 2.031 4.488 313.42 313.42 0.00 180.00  
iz-PERIMETER_BOT_ZN_4_CEILING DROPCEILING 0.30 2.031 4.488 201.98 201.98 315.00 180.00  
iz-DATACENTER_BOT_ZN_6_CEILING DROPCEILING 0.30 2.031 4.488 36.20 36.20 0.00 180.00  
GROUNDFLOOR_PLENUM_CEILING INT_SLAB_CEILING 0.30 2.104 3.839 3563.11 3563.11 180.00 0.00  
iz-CORE_MID_ZN_5_CEILING DROPCEILING 0.30 2.031 4.488 24961.20 24961.20 0.00 180.00  
iz-PERIMETER_MID_ZN_3_CEILING DROPCEILING 0.30 2.031 4.488 3134.13 3134.13 0.00 180.00  
iz-PERIMETER_MID_ZN_2_CEILING DROPCEILING 0.30 2.031 4.488 2019.75 2019.75 45.00 180.00  
iz-PERIMETER_MID_ZN_1_CEILING DROPCEILING 0.30 2.031 4.488 3134.20 3134.20 0.00 180.00  
iz-PERIMETER_MID_ZN_4_CEILING DROPCEILING 0.30 2.031 4.488 2019.75 2019.75 315.00 180.00  
iz-DATACENTER_MID_ZN_6_CEILING DROPCEILING 0.30 2.031 4.488 362.03 362.03 0.00 180.00  
MIDFLOOR_PLENUM_CEILING INT_SLAB_CEILING 0.30 2.104 3.839 35631.06 35631.06 180.00 0.00  
iz-CORE_TOP_ZN_5_CEILING DROPCEILING 0.30 2.031 4.488 2496.12 2496.12 0.00 180.00  
iz-PERIMETER_TOP_ZN_3_CEILING DROPCEILING 0.30 2.031 4.488 313.41 313.41 0.00 180.00  
iz-PERIMETER_TOP_ZN_2_CEILING DROPCEILING 0.30 2.031 4.488 201.98 201.98 45.00 180.00  
iz-PERIMETER_TOP_ZN_1_CEILING DROPCEILING 0.30 2.031 4.488 313.42 313.42 0.00 180.00  
iz-PERIMETER_TOP_ZN_4_CEILING DROPCEILING 0.30 2.031 4.488 201.98 201.98 315.00 180.00  
iz-DATACENTER_TOP_ZN_6_CEILING DROPCEILING 0.30 2.031 4.488 36.20 36.20 0.00 180.00  
DATACENTER_BOT_ZN_6_WALL_NORTH INT_WALL 0.30 2.511 6.299 2.51 2.51 0.00 90.00 N
DATACENTER_BOT_ZN_6_WALL_SOUTH INT_WALL 0.30 2.511 6.299 2.51 2.51 180.00 90.00 S
DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 108.64 108.64 90.00 90.00 E
DATACENTER_BOT_ZN_6_WALL_WEST INT_WALL 0.30 2.511 6.299 108.64 108.64 270.00 90.00 W
DATACENTER_BOT_ZN_6_FLOOR INT_SLAB_FLOOR 0.30 1.887 3.839 36.20 36.20 0.00 180.00  
DATACENTER_BOT_ZN_6_CEILING DROPCEILING 0.30 2.031 4.488 36.20 36.20 180.00 0.00  
DATACENTER_MID_ZN_6_WALL_WEST INT_WALL 0.30 2.511 6.299 1086.40 1086.40 270.00 90.00 W
DATACENTER_MID_ZN_6_WALL_SOUTH INT_WALL 0.30 2.511 6.299 25.09 25.09 180.00 90.00 S
DATACENTER_MID_ZN_6_WALL_EAST INT_WALL 0.30 2.511 6.299 1086.40 1086.40 90.00 90.00 E
DATACENTER_MID_ZN_6_WALL_NORTH INT_WALL 0.30 2.511 6.299 25.09 25.09 0.00 90.00 N
DATACENTER_MID_ZN_6_FLOOR INT_SLAB_FLOOR 0.30 1.711 3.839 362.03 362.03 0.00 180.00  
DATACENTER_MID_ZN_6_CEILING DROPCEILING 0.30 2.031 4.488 362.03 362.03 180.00 0.00  
DATACENTER_TOP_ZN_6_WALL_EAST INT_WALL 0.30 2.511 6.299 108.64 108.64 90.00 90.00 E
DATACENTER_TOP_ZN_6_WALL_WEST INT_WALL 0.30 2.511 6.299 108.64 108.64 270.00 90.00 W
DATACENTER_TOP_ZN_6_WALL_SOUTH INT_WALL 0.30 2.511 6.299 2.51 2.51 180.00 90.00 S
DATACENTER_TOP_ZN_6_WALL_NORTH INT_WALL 0.30 2.511 6.299 2.51 2.51 0.00 90.00 N
DATACENTER_TOP_ZN_6_FLOOR INT_SLAB_FLOOR 0.30 1.711 3.839 36.20 36.20 0.00 180.00  
DATACENTER_TOP_ZN_6_CEILING DROPCEILING 0.30 2.031 4.488 36.20 36.20 180.00 0.00  
DATACENTER_BASEMENT_ZN_6_WALL_EAST INT_WALL 0.30 2.511 6.299 118.87 118.87 90.00 90.00 E
DATACENTER_BASEMENT_ZN_6_FLOOR EXT_SLAB_8IN_WITH_CARPET 0.30 1.591 3.285 783.68 783.68 0.00 180.00  
DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER INT_SLAB_CEILING 0.30 1.887 3.839 36.20 36.20 180.00 0.00  
DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 INT_SLAB_CEILING 0.30 1.887 3.839 419.35 419.35 180.00 0.00  
PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER INT_SLAB_CEILING 0.30 1.887 3.839 201.98 201.98 135.00 0.00  
DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 INT_SLAB_CEILING 0.30 1.887 3.839 63.08 63.08 180.00 0.00  
DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 INT_SLAB_CEILING 0.30 1.887 3.839 63.07 63.07 180.00 0.00  
BASEMENT_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 7126.21   0.00 90.00 N
CORE_BOTTOM_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 5064.65   0.00 90.00 N
CORE_MID_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 50646.53   0.00 90.00 N
CORE_TOP_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 5064.65   0.00 90.00 N
PERIMETER_BOT_ZN_3_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 626.83   0.00 90.00 N
PERIMETER_BOT_ZN_2_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 403.95   0.00 90.00 N
PERIMETER_BOT_ZN_1_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 626.84   0.00 90.00 N
PERIMETER_BOT_ZN_4_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 403.95   0.00 90.00 N
PERIMETER_MID_ZN_3_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 6268.26   0.00 90.00 N
PERIMETER_MID_ZN_2_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 4039.50   0.00 90.00 N
PERIMETER_MID_ZN_1_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 6268.35   0.00 90.00 N
PERIMETER_MID_ZN_4_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 4039.48   0.00 90.00 N
PERIMETER_TOP_ZN_3_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 626.83   0.00 90.00 N
PERIMETER_TOP_ZN_2_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 403.95   0.00 90.00 N
PERIMETER_TOP_ZN_1_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 626.84   0.00 90.00 N
PERIMETER_TOP_ZN_4_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 403.95   0.00 90.00 N


Exterior Fenestration

Construction Frame and Divider Glass Area [m2] Frame Area [m2] Divider Area [m2] Area of One Opening [m2] Area of Multiplied Openings [m2] Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance Frame Conductance [W/m2-K] Divider Conductance [W/m2-K] NFRC Product Type Assembly U-Factor [W/m2-K] Assembly SHGC Assembly Visible Transmittance Shade Control Parent Surface Azimuth [deg] Tilt [deg] Cardinal Direction
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 WINDOW_U_0.57_SHGC_NORTH_0.25   23.18 0.00 0.00 23.18 23.18 3.241 0.251 0.276             No PERIMETER_BOT_ZN_3_WALL_NORTH 0.00 90.00 N
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 WINDOW_U_0.57_SHGC_NORTH_0.25   23.18 0.00 0.00 23.18 23.18 3.241 0.251 0.276             No PERIMETER_BOT_ZN_3_WALL_NORTH 0.00 90.00 N
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 WINDOW_U_0.57_SHGC_NORTH_0.25   23.18 0.00 0.00 23.18 23.18 3.241 0.251 0.276             No PERIMETER_BOT_ZN_3_WALL_NORTH 0.00 90.00 N
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 WINDOW_U_0.57_SHGC_NORTH_0.25   23.18 0.00 0.00 23.18 23.18 3.241 0.251 0.276             No PERIMETER_BOT_ZN_3_WALL_NORTH 0.00 90.00 N
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 WINDOW_U_0.57_SHGC_NORTH_0.25   23.18 0.00 0.00 23.18 23.18 3.241 0.251 0.276             No PERIMETER_BOT_ZN_3_WALL_NORTH 0.00 90.00 N
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 WINDOW_U_0.57_SHGC_EAST_0.25   25.75 0.00 0.00 25.75 25.75 3.241 0.251 0.276             No PERIMETER_BOT_ZN_2_WALL_EAST 90.00 90.00 E
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 WINDOW_U_0.57_SHGC_EAST_0.25   25.75 0.00 0.00 25.75 25.75 3.241 0.251 0.276             No PERIMETER_BOT_ZN_2_WALL_EAST 90.00 90.00 E
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 WINDOW_U_0.57_SHGC_EAST_0.25   25.75 0.00 0.00 25.75 25.75 3.241 0.251 0.276             No PERIMETER_BOT_ZN_2_WALL_EAST 90.00 90.00 E
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 WINDOW_U_0.57_SHGC_SOUTH_0.25   23.18 0.00 0.00 23.18 23.18 3.241 0.251 0.276             No PERIMETER_BOT_ZN_1_WALL_SOUTH 180.00 90.00 S
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 WINDOW_U_0.57_SHGC_SOUTH_0.25   23.18 0.00 0.00 23.18 23.18 3.241 0.251 0.276             No PERIMETER_BOT_ZN_1_WALL_SOUTH 180.00 90.00 S
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 WINDOW_U_0.57_SHGC_SOUTH_0.25   23.18 0.00 0.00 23.18 23.18 3.241 0.251 0.276             No PERIMETER_BOT_ZN_1_WALL_SOUTH 180.00 90.00 S
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 WINDOW_U_0.57_SHGC_SOUTH_0.25   23.18 0.00 0.00 23.18 23.18 3.241 0.251 0.276             No PERIMETER_BOT_ZN_1_WALL_SOUTH 180.00 90.00 S
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 WINDOW_U_0.57_SHGC_SOUTH_0.25   23.18 0.00 0.00 23.18 23.18 3.241 0.251 0.276             No PERIMETER_BOT_ZN_1_WALL_SOUTH 180.00 90.00 S
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 WINDOW_U_0.57_SHGC_WEST_0.25   25.75 0.00 0.00 25.75 25.75 3.241 0.251 0.276             No PERIMETER_BOT_ZN_4_WALL_WEST 270.00 90.00 W
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 WINDOW_U_0.57_SHGC_WEST_0.25   25.75 0.00 0.00 25.75 25.75 3.241 0.251 0.276             No PERIMETER_BOT_ZN_4_WALL_WEST 270.00 90.00 W
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 WINDOW_U_0.57_SHGC_WEST_0.25   25.75 0.00 0.00 25.75 25.75 3.241 0.251 0.276             No PERIMETER_BOT_ZN_4_WALL_WEST 270.00 90.00 W
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW WINDOW_U_0.57_SHGC_NORTH_0.25   115.90 0.00 0.00 115.90 1158.95 3.241 0.251 0.276             No PERIMETER_MID_ZN_3_WALL_NORTH 0.00 90.00 N
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW WINDOW_U_0.57_SHGC_EAST_0.25   77.26 0.00 0.00 77.26 772.63 3.241 0.251 0.276             No PERIMETER_MID_ZN_2_WALL_EAST 90.00 90.00 E
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW WINDOW_U_0.57_SHGC_SOUTH_0.25   115.90 0.00 0.00 115.90 1158.95 3.241 0.251 0.276             No PERIMETER_MID_ZN_1_WALL_SOUTH 180.00 90.00 S
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW WINDOW_U_0.57_SHGC_WEST_0.25   77.26 0.00 0.00 77.26 772.63 3.241 0.251 0.276             No PERIMETER_MID_ZN_4_WALL_WEST 270.00 90.00 W
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW WINDOW_U_0.57_SHGC_NORTH_0.25   115.90 0.00 0.00 115.90 115.90 3.241 0.251 0.276             No PERIMETER_TOP_ZN_3_WALL_NORTH 0.00 90.00 N
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW WINDOW_U_0.57_SHGC_EAST_0.25   77.26 0.00 0.00 77.26 77.26 3.241 0.251 0.276             No PERIMETER_TOP_ZN_2_WALL_EAST 90.00 90.00 E
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW WINDOW_U_0.57_SHGC_SOUTH_0.25   115.90 0.00 0.00 115.90 115.90 3.241 0.251 0.276             No PERIMETER_TOP_ZN_1_WALL_SOUTH 180.00 90.00 S
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW WINDOW_U_0.57_SHGC_WEST_0.25   77.26 0.00 0.00 77.26 77.26 3.241 0.251 0.276             No PERIMETER_TOP_ZN_4_WALL_WEST 270.00 90.00 W
Total or Average             4635.80 3.241 0.251 0.276                      
North Total or Average             1390.74 3.241 0.251 0.276                      
Non-North Total or Average             3245.06 3.241 0.251 0.276                      


Exterior Fenestration Shaded State

Frame and Divider Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance NFRC Product Type Assembly U-Factor [W/m2-K] Assembly SHGC Assembly Visible Transmittance
None                


Interior Fenestration

Construction Area of One Opening [m2] Area of Openings [m2] Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance
Total or Average     0.00 - - -


Exterior Door

Construction U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Parent Surface
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 SWINGING DOOR_CON 2.492 3.975 1.95 PERIMETER_BOT_ZN_3_WALL_NORTH
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 SWINGING DOOR_CON 2.492 3.975 1.95 PERIMETER_BOT_ZN_3_WALL_NORTH
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 SWINGING DOOR_CON 2.492 3.975 1.95 PERIMETER_BOT_ZN_3_WALL_NORTH
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 SWINGING DOOR_CON 2.492 3.975 1.95 PERIMETER_BOT_ZN_3_WALL_NORTH
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 SWINGING DOOR_CON 2.492 3.975 1.95 PERIMETER_BOT_ZN_2_WALL_EAST
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 SWINGING DOOR_CON 2.492 3.975 1.95 PERIMETER_BOT_ZN_2_WALL_EAST
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 SWINGING DOOR_CON 2.492 3.975 1.95 PERIMETER_BOT_ZN_1_WALL_SOUTH
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 SWINGING DOOR_CON 2.492 3.975 1.95 PERIMETER_BOT_ZN_1_WALL_SOUTH
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 SWINGING DOOR_CON 2.492 3.975 1.95 PERIMETER_BOT_ZN_1_WALL_SOUTH
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 SWINGING DOOR_CON 2.492 3.975 1.95 PERIMETER_BOT_ZN_1_WALL_SOUTH
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 SWINGING DOOR_CON 2.492 3.975 1.95 PERIMETER_BOT_ZN_4_WALL_WEST
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 SWINGING DOOR_CON 2.492 3.975 1.95 PERIMETER_BOT_ZN_4_WALL_WEST


Interior Door

Construction U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Parent Surface
None          



Table of Contents

Report: Shading Summary

For: Entire Facility

Timestamp: 2023-10-16 08:43:45

Sunlit Fraction

March 21 9am March 21 noon March 21 3pm June 21 9am June 21 noon June 21 3pm December 21 9am December 21 noon December 21 3pm
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 0.00 0.00 0.00 1.00 0.00 1.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 0.00 0.00 0.00 1.00 0.00 1.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 0.00 0.00 0.00 1.00 0.00 1.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 0.00 0.00 0.00 1.00 0.00 1.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 0.00 0.00 0.00 1.00 0.00 1.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 1.00 1.00 1.00 0.00 1.00 0.00 1.00 1.00 1.00
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 1.00 1.00 1.00 0.00 1.00 0.00 1.00 1.00 1.00
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 1.00 1.00 1.00 0.00 1.00 0.00 1.00 1.00 1.00
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 1.00 1.00 1.00 0.00 1.00 0.00 1.00 1.00 1.00
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 1.00 1.00 1.00 0.00 1.00 0.00 1.00 1.00 1.00
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW 0.00 0.00 0.00 1.00 0.00 1.00 0.00 0.00 0.00
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW 1.00 1.00 1.00 0.00 1.00 0.00 1.00 1.00 1.00
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW 0.00 0.00 0.00 1.00 0.00 1.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW 1.00 1.00 1.00 0.00 1.00 0.00 1.00 1.00 1.00
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00


Window Control

Name Type Shaded Construction Control Glare Control
None          



Table of Contents

Report: Lighting Summary

For: Entire Facility

Timestamp: 2023-10-16 08:43:45

Interior Lighting

Zone Name Space Name Space Type Lighting Power Density [W/m2] Space Area [m2] Total Power [W] End Use Subcategory Schedule Name Scheduled Hours/Week [hr] Hours/Week > 1% [hr] Full Load Hours/Week [hr] Return Air Fraction Conditioned (Y/N) Consumption [GJ]
BASEMENT_LIGHTS BASEMENT BASEMENT GENERAL 10.2732 2779.43 28553.72 LightsWired LTG_SCH_OFFICE 50.34 168.00 49.04 0.0000 Y 262.84
CORE_BOTTOM_LIGHTS CORE_BOTTOM CORE_BOTTOM GENERAL 10.2732 2496.12 25643.24 LightsWired LTG_SCH_OFFICE 50.34 168.00 49.04 0.0000 Y 236.05
CORE_MID_LIGHTS CORE_MID CORE_MID GENERAL 10.2732 24961.20 256432.45 LightsWired LTG_SCH_OFFICE 50.34 168.00 49.04 0.0000 Y 2360.52
CORE_TOP_LIGHTS CORE_TOP CORE_TOP GENERAL 10.2732 2496.12 25643.24 LightsWired LTG_SCH_OFFICE 50.34 168.00 49.04 0.0000 Y 236.05
PERIMETER_BOT_ZN_3_LIGHTS PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3 GENERAL 10.2732 313.41 3219.77 LightsWired LTG_SCH_OFFICE 50.34 168.00 28.47 0.0000 Y 17.21
PERIMETER_BOT_ZN_2_LIGHTS PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2 GENERAL 10.2732 201.98 2074.94 LightsWired LTG_SCH_OFFICE 50.34 168.00 28.31 0.0000 Y 11.02
PERIMETER_BOT_ZN_1_LIGHTS PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1 GENERAL 10.2732 313.42 3219.84 LightsWired LTG_SCH_OFFICE 50.34 168.00 28.05 0.0000 Y 16.96
PERIMETER_BOT_ZN_4_LIGHTS PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4 GENERAL 10.2732 201.98 2074.94 LightsWired LTG_SCH_OFFICE 50.34 168.00 28.26 0.0000 Y 11.01
PERIMETER_MID_ZN_3_LIGHTS PERIMETER_MID_ZN_3 PERIMETER_MID_ZN_3 GENERAL 10.2732 3134.13 32197.65 LightsWired LTG_SCH_OFFICE 50.34 168.00 28.40 0.0000 Y 171.63
PERIMETER_MID_ZN_2_LIGHTS PERIMETER_MID_ZN_2 PERIMETER_MID_ZN_2 GENERAL 10.2732 2019.75 20749.39 LightsWired LTG_SCH_OFFICE 50.34 168.00 28.26 0.0000 Y 110.06
PERIMETER_MID_ZN_1_LIGHTS PERIMETER_MID_ZN_1 PERIMETER_MID_ZN_1 GENERAL 10.2732 3134.20 32198.36 LightsWired LTG_SCH_OFFICE 50.34 168.00 28.01 0.0000 Y 169.31
PERIMETER_MID_ZN_4_LIGHTS PERIMETER_MID_ZN_4 PERIMETER_MID_ZN_4 GENERAL 10.2732 2019.75 20749.39 LightsWired LTG_SCH_OFFICE 50.34 168.00 28.20 0.0000 Y 109.84
PERIMETER_TOP_ZN_3_LIGHTS PERIMETER_TOP_ZN_3 PERIMETER_TOP_ZN_3 GENERAL 10.2732 313.41 3219.77 LightsWired LTG_SCH_OFFICE 50.34 168.00 28.39 0.0000 Y 17.16
PERIMETER_TOP_ZN_2_LIGHTS PERIMETER_TOP_ZN_2 PERIMETER_TOP_ZN_2 GENERAL 10.2732 201.98 2074.94 LightsWired LTG_SCH_OFFICE 50.34 168.00 28.26 0.0000 Y 11.01
PERIMETER_TOP_ZN_1_LIGHTS PERIMETER_TOP_ZN_1 PERIMETER_TOP_ZN_1 GENERAL 10.2732 313.42 3219.84 LightsWired LTG_SCH_OFFICE 50.34 168.00 28.01 0.0000 Y 16.93
PERIMETER_TOP_ZN_4_LIGHTS PERIMETER_TOP_ZN_4 PERIMETER_TOP_ZN_4 GENERAL 10.2732 201.98 2074.94 LightsWired LTG_SCH_OFFICE 50.34 168.00 28.20 0.0000 Y 10.98
DATACENTER_BASEMENT_LIGHTS DATACENTER_BASEMENT_ZN_6 DATACENTER_BASEMENT_ZN_6 GENERAL 10.2732 783.68 8050.93 LightsWired LTG_SCH_OFFICE 50.34 168.00 49.04 0.0000 Y 74.11
DATACENTER_BOT_LIGHTS DATACENTER_BOT_ZN_6 DATACENTER_BOT_ZN_6 GENERAL 17.8735 36.20 647.07 LightsWired LTG_SCH_DATACENTER 56.02 168.00 54.57 0.0000 Y 6.63
DATACENTER_MID_LIGHTS DATACENTER_MID_ZN_6 DATACENTER_MID_ZN_6 GENERAL 17.8735 362.03 6470.68 LightsWired LTG_SCH_DATACENTER 56.02 168.00 54.57 0.0000 Y 66.28
DATACENTER_TOP_LIGHTS DATACENTER_TOP_ZN_6 DATACENTER_TOP_ZN_6 GENERAL 17.8735 36.20 647.07 LightsWired LTG_SCH_DATACENTER 56.02 168.00 54.57 0.0000 Y 6.63
Interior Lighting Total       10.3445 46320.38 479162.15               1233.36


Daylighting

Zone Control Name Daylighting Method Control Type Fraction Controlled Lighting Installed in Zone [W] Lighting Controlled [W]
PERIMETER_BOT_ZN_1_DAYLREFPT1 PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_DAYLCTRL SplitFlux Stepped 0.39 3219.84 1241.89
PERIMETER_BOT_ZN_1_DAYLREFPT2 PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_DAYLCTRL SplitFlux Stepped 0.14 3219.84 445.95
PERIMETER_BOT_ZN_2_DAYLREFPT1 PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_DAYLCTRL SplitFlux Stepped 0.39 2074.94 800.30
PERIMETER_BOT_ZN_2_DAYLREFPT2 PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_DAYLCTRL SplitFlux Stepped 0.14 2074.94 287.38
PERIMETER_BOT_ZN_3_DAYLREFPT1 PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_DAYLCTRL SplitFlux Stepped 0.39 3219.77 1241.86
PERIMETER_BOT_ZN_3_DAYLREFPT2 PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_DAYLCTRL SplitFlux Stepped 0.14 3219.77 445.94
PERIMETER_BOT_ZN_4_DAYLREFPT1 PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_DAYLCTRL SplitFlux Stepped 0.39 2074.94 800.30
PERIMETER_BOT_ZN_4_DAYLREFPT2 PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_DAYLCTRL SplitFlux Stepped 0.14 2074.94 287.38
PERIMETER_MID_ZN_1_DAYLREFPT1 PERIMETER_MID_ZN_1 PERIMETER_MID_ZN_1_DAYLCTRL SplitFlux Stepped 0.39 3219.84 1241.89
PERIMETER_MID_ZN_1_DAYLREFPT2 PERIMETER_MID_ZN_1 PERIMETER_MID_ZN_1_DAYLCTRL SplitFlux Stepped 0.14 3219.84 445.95
PERIMETER_MID_ZN_2_DAYLREFPT1 PERIMETER_MID_ZN_2 PERIMETER_MID_ZN_2_DAYLCTRL SplitFlux Stepped 0.39 2074.94 800.30
PERIMETER_MID_ZN_2_DAYLREFPT2 PERIMETER_MID_ZN_2 PERIMETER_MID_ZN_2_DAYLCTRL SplitFlux Stepped 0.14 2074.94 287.38
PERIMETER_MID_ZN_3_DAYLREFPT1 PERIMETER_MID_ZN_3 PERIMETER_MID_ZN_3_DAYLCTRL SplitFlux Stepped 0.39 3219.77 1241.86
PERIMETER_MID_ZN_3_DAYLREFPT2 PERIMETER_MID_ZN_3 PERIMETER_MID_ZN_3_DAYLCTRL SplitFlux Stepped 0.14 3219.77 445.94
PERIMETER_MID_ZN_4_DAYLREFPT1 PERIMETER_MID_ZN_4 PERIMETER_MID_ZN_4_DAYLCTRL SplitFlux Stepped 0.39 2074.94 800.30
PERIMETER_MID_ZN_4_DAYLREFPT2 PERIMETER_MID_ZN_4 PERIMETER_MID_ZN_4_DAYLCTRL SplitFlux Stepped 0.14 2074.94 287.38
PERIMETER_TOP_ZN_1_DAYLREFPT1 PERIMETER_TOP_ZN_1 PERIMETER_TOP_ZN_1_DAYLCTRL SplitFlux Stepped 0.39 3219.84 1241.89
PERIMETER_TOP_ZN_1_DAYLREFPT2 PERIMETER_TOP_ZN_1 PERIMETER_TOP_ZN_1_DAYLCTRL SplitFlux Stepped 0.14 3219.84 445.95
PERIMETER_TOP_ZN_2_DAYLREFPT1 PERIMETER_TOP_ZN_2 PERIMETER_TOP_ZN_2_DAYLCTRL SplitFlux Stepped 0.39 2074.94 800.30
PERIMETER_TOP_ZN_2_DAYLREFPT2 PERIMETER_TOP_ZN_2 PERIMETER_TOP_ZN_2_DAYLCTRL SplitFlux Stepped 0.14 2074.94 287.38
PERIMETER_TOP_ZN_3_DAYLREFPT1 PERIMETER_TOP_ZN_3 PERIMETER_TOP_ZN_3_DAYLCTRL SplitFlux Stepped 0.39 3219.77 1241.86
PERIMETER_TOP_ZN_3_DAYLREFPT2 PERIMETER_TOP_ZN_3 PERIMETER_TOP_ZN_3_DAYLCTRL SplitFlux Stepped 0.14 3219.77 445.94
PERIMETER_TOP_ZN_4_DAYLREFPT1 PERIMETER_TOP_ZN_4 PERIMETER_TOP_ZN_4_DAYLCTRL SplitFlux Stepped 0.39 2074.94 800.30
PERIMETER_TOP_ZN_4_DAYLREFPT2 PERIMETER_TOP_ZN_4 PERIMETER_TOP_ZN_4_DAYLCTRL SplitFlux Stepped 0.14 2074.94 287.38


Exterior Lighting

Total Watts Astronomical Clock/Schedule Schedule Name Scheduled Hours/Week [hr] Hours/Week > 1% [hr] Full Load Hours/Week [hr] Consumption [GJ]
EXTERIOR_LIGHTS_A 13279.00 AstronomicalClock -   41.82 41.82 104.25
EXTERIOR_LIGHTS_B 44301.60 AstronomicalClock -   83.82 71.22 592.30
Exterior Lighting Total 57580.60           696.56



Table of Contents

Report: Equipment Summary

For: Entire Facility

Timestamp: 2023-10-16 08:43:45

Central Plant

Type Reference Capacity [W] Reference Efficiency [W/W] Rated Capacity [W] Rated Efficiency [W/W] IPLV in SI Units [W/W] IPLV in IP Units [Btu/W-h]
BYPASS HEAT EXCHANGER HeatExchanger:FluidToFluid 3315344.64          
HEATSYS1 BOILER Boiler:HotWater 1502266.44 0.81        
COOLSYS1 CHILLER1 Chiller:Electric:ReformulatedEIR 1687769.75 6.28 1615426.59 5.98 6.84 23.33
COOLSYS1 CHILLER2 Chiller:Electric:ReformulatedEIR 1687769.75 6.28 1615426.59 5.98 6.84 23.33
CENTRAL TOWER FluidCooler:TwoSpeed 582060.00          
CENTRAL BOILER Boiler:HotWater 543702.46 0.80        
TOWERWATERSYS COOLTOWER 1 CoolingTower:VariableSpeed 2002498.32          
TOWERWATERSYS COOLTOWER 2 CoolingTower:VariableSpeed 2002498.32          


Cooling Coils

Type Design Coil Load [W] Nominal Total Capacity [W] Nominal Sensible Capacity [W] Nominal Latent Capacity [W] Nominal Sensible Heat Ratio Nominal Efficiency [W/W] Nominal Coil UA Value [W/C] Nominal Coil Surface Area [m2]
VAV_BOT WITH REHEAT COOLING COIL Coil:Cooling:Water 270084.32 275418.77 186343.79 89074.99 0.68 - 28670.70 290.79
VAV_MID WITH REHEAT COOLING COIL Coil:Cooling:Water 2643274.95 2625714.47 1767845.58 857868.89 0.67 - 274315.81 2782.26
VAV_TOP WITH REHEAT COOLING COIL Coil:Cooling:Water 271050.54 278474.70 188653.35 89821.35 0.68 - 28982.75 293.96
CAV_BAS COOLING COIL Coil:Cooling:Water 138576.71 153793.86 106298.39 47495.47 0.69 - 15674.26 158.98
AIRLOOP DATACENTER BASEMENT COOLING COIL Coil:Cooling:WaterToAirHeatPump:EquationFit   436486.14 313639.03 122847.11 0.72 0.00    
AIRLOOP DATACENTER BOT COOLING COIL Coil:Cooling:WaterToAirHeatPump:EquationFit   9798.88 7029.32 2769.57 0.72 0.00    
AIRLOOP DATACENTER MID COOLING COIL Coil:Cooling:WaterToAirHeatPump:EquationFit   93691.14 67117.65 26573.49 0.72 0.00    
AIRLOOP DATACENTER TOP COOLING COIL Coil:Cooling:WaterToAirHeatPump:EquationFit   9544.35 6841.26 2703.09 0.72 0.00    
Nominal values are gross at rated conditions, i.e., the supply air fan heat and electric power NOT accounted for.

DX Cooling Coils

DX Cooling Coil Type Standard Rated Net Cooling Capacity [W] Standard Rated Net COP [W/W] EER [Btu/W-h] SEER User [Btu/W-h] SEER Standard [Btu/W-h] IEER [Btu/W-h]
None              


DX Cooling Coil ASHRAE 127 Standard Ratings Report

DX Cooling Coil Type Rated Net Cooling Capacity Test A [W] Rated Electric Power Test A [W] Rated Net Cooling Capacity Test B [W] Rated Electric Power Test B [W] Rated Net Cooling Capacity Test C [W] Rated Electric Power Test C [W] Rated Net Cooling Capacity Test D [W] Rated Electric Power Test D [W]
None                  


DX Heating Coils

DX Heating Coil Type High Temperature Heating (net) Rating Capacity [W] Low Temperature Heating (net) Rating Capacity [W] HSPF [Btu/W-h] Region Number
None          


Heating Coils

Type Design Coil Load [W] Nominal Total Capacity [W] Nominal Efficiency [W/W]
CORE_BOTTOM VAV BOX REHEAT COIL Coil:Heating:Water 19711.84 18690.67 -
CORE_MID VAV BOX REHEAT COIL Coil:Heating:Water 403865.23 382712.63 -
CORE_TOP VAV BOX REHEAT COIL Coil:Heating:Water 62558.34 59240.46 -
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL Coil:Heating:Water 6789.76 6431.54 -
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL Coil:Heating:Water 5398.09 5114.14 -
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL Coil:Heating:Water 8348.41 7912.09 -
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL Coil:Heating:Water 4712.47 4466.68 -
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL Coil:Heating:Water 161898.76 153399.89 -
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL Coil:Heating:Water 106699.93 101098.18 -
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL Coil:Heating:Water 160348.89 151931.75 -
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL Coil:Heating:Water 98090.89 92942.68 -
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL Coil:Heating:Water 19847.35 18804.64 -
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL Coil:Heating:Water 13010.56 12326.99 -
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL Coil:Heating:Water 19707.40 18672.07 -
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL Coil:Heating:Water 12359.33 11710.08 -
VAV_BOT WITH REHEAT HEATING COIL Coil:Heating:Water 15573.04 13918.06 -
VAV_MID WITH REHEAT HEATING COIL Coil:Heating:Water 94643.34 86346.21 -
VAV_TOP WITH REHEAT HEATING COIL Coil:Heating:Water 7127.01 6578.99 -
CAV_BAS HEATING COIL Coil:Heating:Water 281575.79 230153.76 -
AIRLOOP DATACENTER BASEMENT HEATING COIL Coil:Heating:WaterToAirHeatPump:EquationFit   436486.14 0.00
AIRLOOP DATACENTER BOT HEATING COIL Coil:Heating:WaterToAirHeatPump:EquationFit   9798.88 0.00
AIRLOOP DATACENTER MID HEATING COIL Coil:Heating:WaterToAirHeatPump:EquationFit   93691.14 0.00
AIRLOOP DATACENTER TOP HEATING COIL Coil:Heating:WaterToAirHeatPump:EquationFit   9544.35 0.00
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL Coil:Heating:Electric   12800.94 1.00
AIRLOOP DATACENTER BOT_SUPPHEATCOIL Coil:Heating:Electric   591.35 1.00
AIRLOOP DATACENTER MID_SUPPHEATCOIL Coil:Heating:Electric   5913.50 1.00
AIRLOOP DATACENTER TOP_SUPPHEATCOIL Coil:Heating:Electric   591.35 1.00
Nominal values are gross at rated conditions, i.e., the supply air fan heat and electric power NOT accounted for.

Fans

Type Total Efficiency [W/W] Delta Pressure [pa] Max Air Flow Rate [m3/s] Rated Electricity Rate [W] Rated Power Per Max Air Flow Rate [W-s/m3] Motor Heat In Air Fraction Fan Energy Index End Use Subcategory Design Day Name for Fan Sizing Peak Date/Time for Fan Sizing Peak
VAV_BOT WITH REHEAT FAN Fan:VariableVolume 0.61 1314.72 10.14 21792.44 2149.46 1.00 1.12 General MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00
VAV_MID WITH REHEAT FAN Fan:VariableVolume 0.61 1314.72 95.08 205454.97 2160.95 1.00 1.08 General MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00
VAV_TOP WITH REHEAT FAN Fan:VariableVolume 0.61 1314.72 10.29 22126.26 2149.46 1.00 1.12 General MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 16:10:00
CAV_BAS FAN Fan:ConstantVolume 0.60 1018.41 6.09 10318.97 1695.65 1.00 1.15 General MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 00:10:00
AIRLOOP DATACENTER BASEMENT SUPPLY FAN Fan:OnOff 0.61 1018.41 21.43 35529.97 1657.97 1.00 1.13 General MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 07:10:00
AIRLOOP DATACENTER BOT SUPPLY FAN Fan:OnOff 0.56 622.50 0.48 537.75 1120.11 1.00 1.62 General MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 00:10:00
AIRLOOP DATACENTER MID SUPPLY FAN Fan:OnOff 0.56 622.50 4.58 5128.23 1120.11 1.00 1.16 General MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 00:10:00
AIRLOOP DATACENTER TOP SUPPLY FAN Fan:OnOff 0.56 622.50 0.47 522.99 1120.11 1.00 1.64 General MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 00:10:00


Pumps

Type Control Head [pa] Water Flow [m3/s] Electricity Rate [W] Power Per Water Flow Rate [W-s/m3] Motor Efficiency [W/W] End Use Subcategory
COOLSYS1 PUMP SECONDARY Pump:VariableSpeed Intermittent 105797.75 0.141368 23081.00 163269.45 0.90 General
HEATSYS1 PUMP Pump:VariableSpeed Intermittent 180705.70 0.013142 3957.94 301156.09 0.90 General
COOLSYS1 CHILLER1 PUMP Pump:ConstantSpeed Intermittent 73247.35 0.070684 7989.88 113036.94 0.90 General
COOLSYS1 CHILLER2 PUMP Pump:ConstantSpeed Intermittent 73247.35 0.070684 7989.88 113036.94 0.90 General
PLANT CIRC PUMP Pump:ConstantSpeed Intermittent 179045.11 0.013458 3432.39 255050.01 0.90 General
SWHSYS1 PUMP Pump:ConstantSpeed Intermittent 29891.00 0.000440 56.21 127739.32 0.30 General
TOWERWATERSYS PUMP HeaderedPumps:VariableSpeed Intermittent 148556.62 0.167043 41356.14 247577.87 0.90 General


Service Water Heating

Type Storage Volume [m3] Input [W] Thermal Efficiency [W/W] Recovery Efficiency [W/W] Energy Factor
SWHSYS1 WATER HEATER WaterHeater:Mixed 1.14 87921.32 0.80 0.48 0.06



Table of Contents

Report: HVAC Sizing Summary

For: Entire Facility

Timestamp: 2023-10-16 08:43:45

Zone Sensible Cooling

Calculated Design Load [W] User Design Load [W] User Design Load per Area [W/m2] Calculated Design Air Flow [m3/s] User Design Air Flow [m3/s] Design Day Name Date/Time Of Peak {TIMESTAMP} Thermostat Setpoint Temperature at Peak Load [C] Indoor Temperature at Peak Load [C] Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] Outdoor Temperature at Peak Load [C] Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] Minimum Outdoor Air Flow Rate [m3/s] Heat Gain Rate from DOAS [W]
BASEMENT 84401.13 84401.13 30.37 6.086 6.086 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 24.00 24.00 0.00891 28.24 0.01716 1.200 0.00
CORE_BOTTOM 87138.28 87138.28 34.91 6.282 6.282 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 24.00 24.00 0.00886 28.24 0.01716 1.078 0.00
CORE_MID 823926.45 823926.45 330.08 59.387 59.387 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 24.00 24.00 0.00888 28.24 0.01716 10.778 0.00
CORE_TOP 80953.61 80953.61 32.43 5.835 5.835 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 24.00 24.00 0.00889 28.24 0.01716 1.078 0.00
PERIMETER_BOT_ZN_3 15234.02 15234.02 48.61 1.108 1.108 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 17:30:00 24.00 24.00 0.00894 31.93 0.01716 0.135 0.00
PERIMETER_BOT_ZN_2 15258.57 15258.57 75.55 1.110 1.110 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 09:40:00 24.00 24.00 0.00879 30.27 0.01716 0.087 0.00
PERIMETER_BOT_ZN_1 15190.28 15190.28 48.47 1.105 1.105 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 14:10:00 24.00 24.00 0.00894 33.20 0.01717 0.135 0.00
PERIMETER_BOT_ZN_4 19755.40 19755.40 97.81 1.437 1.437 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 17:00:00 24.00 24.00 0.00872 32.26 0.01717 0.087 0.00
PERIMETER_MID_ZN_3 146063.20 146063.20 466.04 10.627 10.627 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 17:40:00 24.00 24.00 0.00920 31.82 0.01716 1.353 0.00
PERIMETER_MID_ZN_2 157821.57 157821.57 781.39 11.482 11.482 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 09:50:00 24.00 24.00 0.00894 30.46 0.01716 0.872 0.00
PERIMETER_MID_ZN_1 144835.12 144835.12 462.11 10.537 10.537 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 14:30:00 24.00 24.00 0.00921 33.20 0.01717 1.353 0.00
PERIMETER_MID_ZN_4 175045.27 175045.27 866.67 12.735 12.735 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 17:10:00 24.00 24.00 0.00889 32.15 0.01717 0.872 0.00
PERIMETER_TOP_ZN_3 16195.56 16195.56 51.67 1.178 1.178 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 17:00:00 24.00 24.00 0.00923 32.26 0.01717 0.135 0.00
PERIMETER_TOP_ZN_2 15984.08 15984.08 79.14 1.163 1.163 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 10:00:00 24.00 24.00 0.00900 30.65 0.01716 0.087 0.00
PERIMETER_TOP_ZN_1 16206.86 16206.86 51.71 1.179 1.179 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 14:40:00 24.00 24.00 0.00922 33.20 0.01717 0.135 0.00
PERIMETER_TOP_ZN_4 18590.08 18590.08 92.04 1.353 1.353 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 17:00:00 24.00 24.00 0.00893 32.26 0.01717 0.087 0.00
DATACENTER_BOT_ZN_6 8367.75 8367.75 231.14 0.480 0.480 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 18:50:00 27.00 27.00 0.00859 30.75 0.01716 0.016 0.00
DATACENTER_MID_ZN_6 79797.71 79797.71 2204.19 4.578 4.578 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 18:50:00 27.00 27.00 0.00859 30.75 0.01716 0.156 0.00
DATACENTER_TOP_ZN_6 8138.00 8138.00 224.79 0.467 0.467 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 18:40:00 27.00 27.00 0.00859 30.92 0.01716 0.016 0.00
DATACENTER_BASEMENT_ZN_6 373513.38 373513.38 476.62 21.430 21.430 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 07:00:00 27.00 27.00 0.00854 27.10 0.01716 0.338 0.00
The Design Load is the zone sensible load only. It does not include any system effects or ventilation loads.

Zone Sensible Heating

Calculated Design Load [W] User Design Load [W] User Design Load per Area [W/m2] Calculated Design Air Flow [m3/s] User Design Air Flow [m3/s] Design Day Name Date/Time Of Peak {TIMESTAMP} Thermostat Setpoint Temperature at Peak Load [C] Indoor Temperature at Peak Load [C] Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] Outdoor Temperature at Peak Load [C] Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] Minimum Outdoor Air Flow Rate [m3/s] Heat Gain Rate from DOAS [W]
BASEMENT 0.00 0.00 0.00 0.000 1.200   00:10:00 15.60 25.07 0.00699 8.70 0.00699 1.200 0.00
CORE_BOTTOM 0.00 0.00 0.00 0.000 1.078   00:10:00 15.60 22.45 0.00699 8.70 0.00699 1.078 0.00
CORE_MID 210357.20 210357.20 84.27 8.859 10.778 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00800 8.70 0.00699 10.778 0.00
CORE_TOP 42783.40 42783.40 17.14 1.815 1.815 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00800 8.70 0.00699 1.078 0.00
PERIMETER_BOT_ZN_3 4317.02 4317.02 13.77 0.183 0.183 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00770 8.70 0.00699 0.135 0.00
PERIMETER_BOT_ZN_2 3166.69 3166.69 15.68 0.134 0.134 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00773 8.70 0.00699 0.087 0.00
PERIMETER_BOT_ZN_1 5851.74 5851.74 18.67 0.248 0.248 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00778 8.70 0.00699 0.135 0.00
PERIMETER_BOT_ZN_4 1824.38 1824.38 9.03 0.077 0.087 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00755 8.70 0.00699 0.087 0.00
PERIMETER_MID_ZN_3 113335.61 113335.61 361.62 4.830 4.830 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00787 8.70 0.00699 1.353 0.00
PERIMETER_MID_ZN_2 74692.14 74692.14 369.81 3.184 3.184 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00787 8.70 0.00699 0.872 0.00
PERIMETER_MID_ZN_1 112252.18 112252.18 358.15 4.784 4.784 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00787 8.70 0.00699 1.353 0.00
PERIMETER_MID_ZN_4 68672.56 68672.56 340.00 2.926 2.926 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00785 8.70 0.00699 0.872 0.00
PERIMETER_TOP_ZN_3 13890.68 13890.68 44.32 0.592 0.592 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00789 8.70 0.00699 0.135 0.00
PERIMETER_TOP_ZN_2 9105.63 9105.63 45.08 0.388 0.388 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00789 8.70 0.00699 0.087 0.00
PERIMETER_TOP_ZN_1 13792.85 13792.85 44.01 0.588 0.588 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00789 8.70 0.00699 0.135 0.00
PERIMETER_TOP_ZN_4 8650.33 8650.33 42.83 0.369 0.369 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00788 8.70 0.00699 0.087 0.00
DATACENTER_BOT_ZN_6 0.00 0.00 0.00 0.000 0.016   00:10:00 18.00 27.00 0.00850 8.70 0.00699 0.016 0.00
DATACENTER_MID_ZN_6 0.00 0.00 0.00 0.000 0.156   00:10:00 18.00 24.70 0.00782 8.70 0.00699 0.156 0.00
DATACENTER_TOP_ZN_6 0.00 0.00 0.00 0.000 0.016   00:10:00 18.00 23.98 0.00708 8.70 0.00699 0.016 0.00
DATACENTER_BASEMENT_ZN_6 0.00 0.00 0.00 0.000 0.338   00:10:00 18.00 27.00 0.00850 8.70 0.00699 0.338 0.00
The Design Load is the zone sensible load only. It does not include any system effects or ventilation loads.

System Design Air Flow Rates

Calculated cooling [m3/s] User cooling [m3/s] Calculated heating [m3/s] User heating [m3/s] Adjusted cooling [m3/s] Adjusted heating [m3/s] Adjusted main [m3/s] Calculated Heating Air Flow Ratio [] User Heating Air Flow Ratio []
VAV_BOT WITH REHEAT 10.14 10.14 1.73 1.73 10.1385 2.9619 10.1385 0.2921 0.3000
VAV_MID WITH REHEAT 95.08 95.08 26.50 26.50 95.0764 28.9100 95.0764 0.3041 0.3000
VAV_TOP WITH REHEAT 10.29 10.29 3.75 3.75 10.2938 3.7526 10.2938 0.3645 0.3000
CAV_BAS 6.09 6.09 1.20 1.20 6.0855 6.0855 6.0855 1.0000 1.0000
AIRLOOP DATACENTER BASEMENT 21.43 21.43 0.34 0.34 21.4298 21.4296 21.4298 1.0000 1.0000
AIRLOOP DATACENTER BOT 0.48 0.48 0.02 0.02 0.4801 0.4801 0.4801 1.0000 1.0000
AIRLOOP DATACENTER MID 4.58 4.58 0.16 0.16 4.5783 4.5783 4.5783 1.0000 1.0000
AIRLOOP DATACENTER TOP 0.47 0.47 0.02 0.02 0.4669 0.4669 0.4669 1.0000 1.0000


Plant Loop Coincident Design Fluid Flow Rate Adjustments

Previous Design Volume Flow Rate [m3/s] Algorithm Volume Flow Rate [m3/s] Coincident Design Volume Flow Rate [m3/s] Coincident Size Adjusted Peak Sizing Period Name Peak Day into Period {TIMESTAMP}[day] Peak Hour Of Day {TIMESTAMP}[hr] Peak Step Start Minute {TIMESTAMP}[min]
None                


Coil Sizing Summary

Coil Type HVAC Type HVAC Name Coil Final Gross Total Capacity [W] Coil Final Gross Sensible Capacity [W] Coil Final Reference Air Volume Flow Rate [m3/s] Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] Coil U-value Times Area Value [W/K] Design Day Name at Sensible Ideal Loads Peak Date/Time at Sensible Ideal Loads Peak Design Day Name at Air Flow Ideal Loads Peak Date/Time at Air Flow Ideal Loads Peak Coil Total Capacity at Ideal Loads Peak [W] Coil Sensible Capacity at Ideal Loads Peak [W] Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] Coil Entering Air Drybulb at Ideal Loads Peak [C] Coil Entering Air Wetbulb at Ideal Loads Peak [C] Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Coil Leaving Air Drybulb at Ideal Loads Peak [C] Coil Leaving Air Wetbulb at Ideal Loads Peak [C] Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Outdoor Air Drybulb at Ideal Loads Peak [C] Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Outdoor Air Wetbulb at Ideal Loads Peak [C] Outdoor Air Flow Percentage at Ideal Loads Peak [%] Zone Air Drybulb at Ideal Loads Peak [C] Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Zone Air Relative Humidity at Ideal Loads Peak [%] Zone Sensible Heat Gain at Ideal Loads Peak [W] Zone Latent Heat Gain at Ideal Loads Peak [W] Coil Total Capacity at Rating Conditions [W] Coil Sensible Capacity at Rating Conditions [W]
CORE_BOTTOM VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT CORE_BOTTOM VAV BOX 19711.842 19711.842 1.960039 0.00017245 397.375   1/21 00:10:00   1/21 00:10:00 19711.84 19711.84 1.960039 12.80 11.58 0.00800000 40.00 21.17 0.00800000 8.70 0.00699286 8.70 0.0000 21.00 0.00800000 51.6560 0.00 0.00 19784.52 19784.52
CORE_MID VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT CORE_MID VAV BOX 403865.231 403865.231 19.241376 0.00353319 9127.627 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 403865.23 403865.23 19.241376 12.80 11.58 0.00800000 40.00 21.17 0.00800000 8.70 0.00699286 8.70 0.0000 21.00 0.00800000 51.6560 210357.20 0.00 405243.14 405243.14
CORE_TOP VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT CORE_TOP VAV BOX 62558.340 62558.340 1.966313 0.00054729 1613.268 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 62558.34 62558.34 1.966313 12.80 11.58 0.00800000 40.00 21.17 0.00800000 8.70 0.00699286 8.70 0.0000 21.00 0.00800000 51.6560 42783.40 0.00 62750.43 62750.43
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_BOT_ZN_3 VAV BOX 6789.762 6789.762 0.246025 0.00005940 165.890 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 6789.76 6789.76 0.246025 12.80 11.58 0.00800000 40.00 21.17 0.00800000 8.70 0.00699286 8.70 0.0000 21.00 0.00769805 49.7316 4317.02 0.00 6811.63 6811.63
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_BOT_ZN_2 VAV BOX 5398.090 5398.090 0.222000 0.00004722 126.753 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 5398.09 5398.09 0.222000 12.80 11.58 0.00800000 40.00 21.17 0.00800000 8.70 0.00699286 8.70 0.0000 21.00 0.00772969 49.9335 3166.69 0.00 5415.79 5415.79
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_BOT_ZN_1 VAV BOX 8348.405 8348.405 0.248366 0.00007304 220.552 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 8348.41 8348.41 0.248366 12.80 11.58 0.00800000 40.00 21.17 0.00800000 8.70 0.00699286 8.70 0.0000 21.00 0.00778440 50.2825 5851.74 0.00 8378.54 8378.54
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_BOT_ZN_4 VAV BOX 4712.471 4712.471 0.287424 0.00004123 101.303 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 4712.47 4712.47 0.287424 12.80 11.58 0.00800000 40.00 21.17 0.00800000 8.70 0.00699286 8.70 0.0000 21.00 0.00755437 48.8143 1824.38 0.00 4728.97 4728.97
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_MID_ZN_3 VAV BOX 161898.763 161898.763 4.830283 0.00141636 4271.514 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 161898.76 161898.76 4.830283 12.80 11.58 0.00800000 40.00 21.17 0.00800000 8.70 0.00699286 8.70 0.0000 21.00 0.00786873 50.8205 113335.61 0.00 162443.01 162443.01
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_MID_ZN_2 VAV BOX 106699.929 106699.929 3.183614 0.00093346 2815.075 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 106699.93 106699.93 3.183614 12.80 11.58 0.00800000 40.00 21.17 0.00800000 8.70 0.00699286 8.70 0.0000 21.00 0.00786985 50.8276 74692.14 0.00 107058.04 107058.04
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_MID_ZN_1 VAV BOX 160348.888 160348.888 4.783906 0.00140280 4230.678 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 160348.89 160348.89 4.783906 12.80 11.58 0.00800000 40.00 21.17 0.00800000 8.70 0.00699286 8.70 0.0000 21.00 0.00786687 50.8086 112252.18 0.00 160888.32 160888.32
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_MID_ZN_4 VAV BOX 98090.893 98090.893 2.926168 0.00085814 2588.176 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 98090.89 98090.89 2.926168 12.80 11.58 0.00800000 40.00 21.17 0.00800000 8.70 0.00699286 8.70 0.0000 21.00 0.00785160 50.7113 68672.56 0.00 98421.79 98421.79
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_TOP_ZN_3 VAV BOX 19847.347 19847.347 0.592454 0.00017363 523.526 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 19847.35 19847.35 0.592454 12.80 11.58 0.00800000 40.00 21.17 0.00800000 8.70 0.00699286 8.70 0.0000 21.00 0.00788618 50.9317 13890.68 0.00 19913.18 19913.18
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_TOP_ZN_2 VAV BOX 13010.562 13010.562 0.388388 0.00011382 343.182 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 13010.56 13010.56 0.388388 12.80 11.58 0.00800000 40.00 21.17 0.00800000 8.70 0.00699286 8.70 0.0000 21.00 0.00788542 50.9269 9105.63 0.00 13053.67 13053.67
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_TOP_ZN_1 VAV BOX 19707.399 19707.399 0.588266 0.00017241 519.839 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 19707.40 19707.40 0.588266 12.80 11.58 0.00800000 40.00 21.17 0.00800000 8.70 0.00699286 8.70 0.0000 21.00 0.00788515 50.9251 13792.85 0.00 19772.80 19772.80
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_TOP_ZN_4 VAV BOX 12359.326 12359.326 0.368907 0.00010812 326.020 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 12359.33 12359.33 0.368907 12.80 11.58 0.00800000 40.00 21.17 0.00800000 8.70 0.00699286 8.70 0.0000 21.00 0.00787636 50.8692 8650.33 0.00 12400.40 12400.40
VAV_BOT WITH REHEAT COOLING COIL Coil:Cooling:Water AirLoopHVAC VAV_BOT WITH REHEAT 270084.320 -999.000 10.138544 0.01149001 -999.000 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 15:10:00 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 270084.32 188776.94 10.138544 26.38 19.25 0.01105177 11.06 11.06 0.00850000 33.13 0.01716709 25.31 25.0351 24.00 0.00889182 47.7834 133679.63 0.00 270539.32 184084.57
VAV_BOT WITH REHEAT HEATING COIL Coil:Heating:Water AirLoopHVAC VAV_BOT WITH REHEAT 15573.042 15573.042 3.041563 0.00013624 276.832 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 15573.04 15573.04 3.041563 8.56 8.56 0.00703813 12.80 11.58 0.00800000 8.70 0.00699286 8.70 83.4502 21.67 0.00737157 45.7419 15159.83 0.00 16851.43 16851.43
VAV_MID WITH REHEAT COOLING COIL Coil:Cooling:Water AirLoopHVAC VAV_MID WITH REHEAT 2643274.952 -999.000 95.076369 0.11245103 -999.000 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 15:30:00 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 2643274.95 1791421.16 95.076369 26.57 19.54 0.01135237 11.05 11.05 0.00850000 33.00 0.01716683 25.27 26.6964 24.00 0.00902728 48.5023 1221431.24 0.00 2646856.89 1752365.53
VAV_MID WITH REHEAT HEATING COIL Coil:Heating:Water AirLoopHVAC VAV_MID WITH REHEAT 94643.344 94643.344 28.522911 0.00082798 1701.607 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:30:00 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 94643.34 94643.34 28.522911 10.05 9.43 0.00709615 12.80 11.58 0.00800000 8.70 0.00699286 8.70 88.9879 21.00 0.00792390 51.1716 538946.73 0.00 104542.10 104542.10
VAV_TOP WITH REHEAT COOLING COIL Coil:Cooling:Water AirLoopHVAC VAV_TOP WITH REHEAT 271050.544 -999.000 10.293846 0.01153112 -999.000 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 15:30:00 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 16:10:00 271050.54 189674.88 10.293846 26.22 19.17 0.01101493 11.06 11.06 0.00850000 33.00 0.01716683 25.27 24.6574 24.00 0.00899303 48.3213 141048.04 0.00 271503.77 184865.10
VAV_TOP WITH REHEAT HEATING COIL Coil:Heating:Water AirLoopHVAC VAV_TOP WITH REHEAT 7127.013 7127.013 3.088154 0.00006235 128.977 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 13:30:00 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 7127.01 7127.01 3.088154 10.89 9.88 0.00715845 12.80 11.58 0.00800000 8.70 0.00699286 8.70 82.1912 21.00 0.00792272 51.1640 58940.06 0.00 7965.29 7965.29
CAV_BAS COOLING COIL Coil:Cooling:Water AirLoopHVAC CAV_BAS 138576.711 -999.000 6.085539 0.00589537 -999.000 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 138576.71 100242.30 6.085539 24.89 18.37 0.01053878 11.42 11.42 0.00850000 28.24 0.01715778 24.03 19.7214 24.00 0.00891274 47.8936 84401.13 0.00 138774.60 97461.15
CAV_BAS HEATING COIL Coil:Heating:Water AirLoopHVAC CAV_BAS 281575.794 281575.794 6.085539 0.00246335 6431.563 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 00:10:00 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 00:10:00 281575.79 281575.79 6.085539 1.72 1.72 0.00699286 40.00 21.17 0.00800000 8.70 0.00699286 8.70 19.7214 25.07 0.00699286 35.3535 0.00 0.00 243677.19 243677.19
AIRLOOP DATACENTER BASEMENT COOLING COIL COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoopHVAC AIRLOOP DATACENTER BASEMENT 436486.136 313639.029 21.429762 0.01068952 -999.000 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 14:00:00 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 07:10:00 408959.69 398442.16 -999.0 28.50 18.07 0.00867846 12.80 12.09 0.00850000 33.20 0.01716721 25.32 -999.0000 27.00 0.00854208 38.4360 372985.12 0.00 -999.00 -999.00
AIRLOOP DATACENTER BOT COOLING COIL COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoopHVAC AIRLOOP DATACENTER BOT 9798.885 7029.315 0.480091 0.00023997 -999.000 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 18:40:00 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 18:50:00 9183.41 8700.72 -999.0 28.07 18.08 0.00886577 12.80 12.09 0.00850000 30.92 0.01716288 24.74 -999.0000 27.00 0.00858649 38.6307 8366.90 0.00 -999.00 -999.00
AIRLOOP DATACENTER MID COOLING COIL COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoopHVAC AIRLOOP DATACENTER MID 93691.145 67117.651 4.578338 0.00229449 -999.000 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 18:40:00 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 18:50:00 87845.19 83018.63 -999.0 28.08 18.10 0.00888346 12.80 12.09 0.00850000 30.92 0.01716288 24.74 -999.0000 27.00 0.00859067 38.6495 79769.94 0.00 -999.00 -999.00
AIRLOOP DATACENTER TOP COOLING COIL COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoopHVAC AIRLOOP DATACENTER TOP 9544.353 6841.258 0.466911 0.00023374 -999.000 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 18:40:00 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 18:40:00 8947.16 8464.52 -999.0 28.08 18.09 0.00887602 12.80 12.09 0.00850000 30.92 0.01716288 24.74 -999.0000 27.00 0.00858896 38.6418 8138.00 0.00 -999.00 -999.00
AIRLOOP DATACENTER BASEMENT HEATING COIL COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoopHVAC AIRLOOP DATACENTER BASEMENT 436486.136 436486.136 21.429762 0.01068952 -999.000 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 00:10:00 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 00:10:00 436486.14 436486.14 21.429762 8.70 8.70 0.00699286 40.00 21.17 0.00800000 8.70 0.00699286 8.70 1.5791 27.00 0.00850000 38.2434 0.00 0.00 -999.00 -999.00
AIRLOOP DATACENTER BOT HEATING COIL COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoopHVAC AIRLOOP DATACENTER BOT 9798.885 9798.885 0.480091 0.00023997 -999.000 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 00:10:00 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 00:10:00 9798.88 9798.88 0.480091 8.70 8.70 0.00699286 40.00 21.17 0.00800000 8.70 0.00699286 8.70 3.2561 27.00 0.00850000 38.2434 0.00 0.00 -999.00 -999.00
AIRLOOP DATACENTER MID HEATING COIL COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoopHVAC AIRLOOP DATACENTER MID 93691.145 93691.145 4.578338 0.00229449 -999.000 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 00:10:00 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 00:10:00 93691.14 93691.14 4.578338 8.70 8.70 0.00699286 40.00 21.17 0.00800000 8.70 0.00699286 8.70 3.4144 24.70 0.00782254 40.3777 0.00 0.00 -999.00 -999.00
AIRLOOP DATACENTER TOP HEATING COIL COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoopHVAC AIRLOOP DATACENTER TOP 9544.353 9544.353 0.466911 0.00023374 -999.000 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 00:10:00 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 00:10:00 9544.35 9544.35 0.466911 8.70 8.70 0.00699286 40.00 21.17 0.00800000 8.70 0.00699286 8.70 3.3480 23.98 0.00707501 38.1638 0.00 0.00 -999.00 -999.00
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL Coil:Heating:Electric AirLoopHVAC AIRLOOP DATACENTER BASEMENT 12800.936 12800.936 -999.0 -999.0 -999.000 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 00:10:00 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 00:10:00 12800.94 12800.94 21.429762 0.14 0.14 0.00847620 40.00 21.17 0.00800000 8.70 0.00699286 8.70 1.5791 27.00 0.00850000 38.2434 0.00 0.00 -999.00 -999.00
AIRLOOP DATACENTER BOT_SUPPHEATCOIL Coil:Heating:Electric AirLoopHVAC AIRLOOP DATACENTER BOT 591.350 591.350 -999.0 -999.0 -999.000 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 00:10:00 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 00:10:00 591.35 591.35 0.480091 0.28 0.28 0.00845093 40.00 21.17 0.00800000 8.70 0.00699286 8.70 3.2561 27.00 0.00850000 38.2434 0.00 0.00 -999.00 -999.00
AIRLOOP DATACENTER MID_SUPPHEATCOIL Coil:Heating:Electric AirLoopHVAC AIRLOOP DATACENTER MID 5913.502 5913.502 -999.0 -999.0 -999.000 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 00:10:00 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 00:10:00 5913.50 5913.50 4.578338 0.30 0.30 0.00779421 40.00 21.17 0.00800000 8.70 0.00699286 8.70 3.4144 24.70 0.00782254 40.3777 0.00 0.00 -999.00 -999.00
AIRLOOP DATACENTER TOP_SUPPHEATCOIL Coil:Heating:Electric AirLoopHVAC AIRLOOP DATACENTER TOP 591.350 591.350 -999.0 -999.0 -999.000 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 00:10:00 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 00:10:00 591.35 591.35 0.466911 0.29 0.29 0.00707226 40.00 21.17 0.00800000 8.70 0.00699286 8.70 3.3480 23.98 0.00707501 38.1638 0.00 0.00 -999.00 -999.00



Table of Contents

Report: Coil Sizing Details

For: Entire Facility

Timestamp: 2023-10-16 08:43:45

Coils

Coil Type Coil Location HVAC Type HVAC Name Zone Name(s) System Sizing Method Concurrence System Sizing Method Capacity System Sizing Method Air Flow Autosized Coil Capacity? Autosized Coil Airflow? Autosized Coil Water Flow? OA Pretreated prior to coil inlet? Coil Final Gross Total Capacity [W] Coil Final Gross Sensible Capacity [W] Coil Final Reference Air Volume Flow Rate [m3/s] Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] Coil U-value Times Area Value [W/K] Terminal Unit Reheat Coil Multiplier DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio Moist Air Heat Capacity [J/kg-K] Dry Air Heat Capacity [J/kg-K] Standard Air Density Adjusted for Elevation [kg/m3] Supply Fan Name for Coil Supply Fan Type for Coil Supply Fan Maximum Air Volume Flow Rate [m3/s] Supply Fan Maximum Air Mass Flow Rate [kg/s] Plant Name for Coil Plant Fluid Specific Heat Capacity [J/kg-K] Plant Fluid Density [kg/m3] Plant Maximum Fluid Mass Flow Rate [kg/s] Plant Design Fluid Return Temperature [C] Plant Design Fluid Supply Temperature [C] Plant Design Fluid Temperature Difference [deltaC] Plant Design Capacity [W] Coil Capacity Percentage of Plant Design Capacity [%] Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] Design Day Name at Sensible Ideal Loads Peak Date/Time at Sensible Ideal Loads Peak Design Day Name at Total Ideal Loads Peak Date/Time at Total Ideal Loads Peak Design Day Name at Air Flow Ideal Loads Peak Date/Time at Air Flow Ideal Loads Peak Peak Load Type to Size On Coil Total Capacity at Ideal Loads Peak [W] Coil Sensible Capacity at Ideal Loads Peak [W] Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] Coil Entering Air Drybulb at Ideal Loads Peak [C] Coil Entering Air Wetbulb at Ideal Loads Peak [C] Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] Coil Leaving Air Drybulb at Ideal Loads Peak [C] Coil Leaving Air Wetbulb at Ideal Loads Peak [C] Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] Supply Fan Air Heat Gain at Ideal Loads Peak [W] Coil and Fan Net Total Capacity at Ideal Loads Peak [W] Outdoor Air Drybulb at Ideal Loads Peak [C] Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Outdoor Air Wetbulb at Ideal Loads Peak [C] Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] Outdoor Air Flow Percentage at Ideal Loads Peak [%] System Return Air Drybulb at Ideal Loads Peak [C] System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Zone Air Drybulb at Ideal Loads Peak [C] Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Zone Air Relative Humidity at Ideal Loads Peak [%] Zone Sensible Heat Gain at Ideal Loads Peak [W] Zone Latent Heat Gain at Ideal Loads Peak [W] Coil Total Capacity at Rating Conditions [W] Coil Sensible Capacity at Rating Conditions [W] Coil Air Mass Flow Rate at Rating Conditions [kg/s] Coil Entering Air Drybulb at Rating Conditions [C] Coil Entering Air Wetbulb at Rating Conditions [C] Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] Coil Leaving Air Drybulb at Rating Conditions [C] Coil Leaving Air Wetbulb at Rating Conditions [C] Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K]
CORE_BOTTOM VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT CORE_BOTTOM VAV BOX CORE_BOTTOM N/A N/A N/A Yes Yes Yes No 19711.842 19711.842 1.960039 0.00017245 397.375 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2027 unknown unknown -999.0 -999.0   4197.9300 999.8980 13.14114152 54.44 82.22 27.78 1532500.15 1.2863 1.312140   1/21 00:10:00 unknown unknown   1/21 00:10:00 Sensible 19711.84 19711.84 1.0000 2.35741477 1.960039 12.80 11.58 0.00800000 33059.8 40.00 21.17 0.00800000 60796.0 0.17243020 60.00 32.22 27.78 0.000 19711.84 8.70 0.00699286 8.70 0.00000000 0.0000 21.00 0.00800000 21.00 0.00800000 51.6560 0.00 0.00 19784.52 19784.52 2.35741477 12.80 11.60 0.00800000 33059.8 21.03 14.86 0.00800000 41452.3
CORE_MID VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT CORE_MID VAV BOX CORE_MID N/A N/A N/A Yes Yes Yes No 403865.231 403865.231 19.241376 0.00353319 9127.627 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2027 unknown unknown -999.0 -999.0   4197.9300 999.8980 13.14114152 54.44 82.22 27.78 1532500.15 26.3534 26.883728 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 403865.23 403865.23 1.0000 23.14235211 19.241376 12.80 11.58 0.00800000 33059.8 40.00 21.17 0.00800000 60796.0 3.53282880 60.00 32.22 27.78 0.000 403865.23 8.70 0.00699286 8.70 0.00000000 0.0000 20.91 0.00800000 21.00 0.00800000 51.6560 210357.20 0.00 405243.14 405243.14 23.14235211 12.80 11.60 0.00800000 33059.8 29.97 18.03 0.00800000 50570.7
CORE_TOP VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT CORE_TOP VAV BOX CORE_TOP N/A N/A N/A Yes Yes Yes No 62558.340 62558.340 1.966313 0.00054729 1613.268 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2027 unknown unknown -999.0 -999.0   4197.9300 999.8980 13.14114152 54.44 82.22 27.78 1532500.15 4.0821 4.164264 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 62558.34 62558.34 1.0000 2.36496109 1.966313 12.80 11.58 0.00800000 33059.8 40.00 21.17 0.00800000 60796.0 0.54723182 60.00 32.22 27.78 0.000 62558.34 8.70 0.00699286 8.70 0.00000000 0.0000 20.86 0.00800000 21.00 0.00800000 51.6560 42783.40 0.00 62750.43 62750.43 2.36496109 12.80 11.60 0.00800000 33059.8 38.82 20.83 0.00800000 59593.2
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_BOT_ZN_3 VAV BOX PERIMETER_BOT_ZN_3 N/A N/A N/A Yes Yes Yes No 6789.762 6789.762 0.246025 0.00005940 165.890 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2027 unknown unknown -999.0 -999.0   4197.9300 999.8980 13.14114152 54.44 82.22 27.78 1532500.15 0.4431 0.451968 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 6789.76 6789.76 1.0000 0.29590381 0.246025 12.80 11.58 0.00800000 33059.8 40.00 21.17 0.00800000 60796.0 0.05939374 60.00 32.22 27.78 0.000 6789.76 8.70 0.00699286 8.70 0.00000000 0.0000 20.87 0.00769805 21.00 0.00769805 49.7316 4317.02 0.00 6811.63 6811.63 0.29590381 12.80 11.60 0.00800000 33059.8 35.37 19.77 0.00800000 56079.6
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_BOT_ZN_2 VAV BOX PERIMETER_BOT_ZN_2 N/A N/A N/A Yes Yes Yes No 5398.090 5398.090 0.222000 0.00004722 126.753 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2027 unknown unknown -999.0 -999.0   4197.9300 999.8980 13.14114152 54.44 82.22 27.78 1532500.15 0.3522 0.359330 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 5398.09 5398.09 1.0000 0.26700808 0.222000 12.80 11.58 0.00800000 33059.8 40.00 21.17 0.00800000 60796.0 0.04722003 60.00 32.22 27.78 0.000 5398.09 8.70 0.00699286 8.70 0.00000000 0.0000 20.87 0.00772969 21.00 0.00772969 49.9335 3166.69 0.00 5415.79 5415.79 0.26700808 12.80 11.60 0.00800000 33059.8 32.69 18.92 0.00800000 53343.1
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_BOT_ZN_1 VAV BOX PERIMETER_BOT_ZN_1 N/A N/A N/A Yes Yes Yes No 8348.405 8348.405 0.248366 0.00007304 220.552 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2027 unknown unknown -999.0 -999.0   4197.9300 999.8980 13.14114152 54.44 82.22 27.78 1532500.15 0.5448 0.555721 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 8348.41 8348.41 1.0000 0.29871912 0.248366 12.80 11.58 0.00800000 33059.8 40.00 21.17 0.00800000 60796.0 0.07302804 60.00 32.22 27.78 0.000 8348.41 8.70 0.00699286 8.70 0.00000000 0.0000 20.92 0.00778440 21.00 0.00778440 50.2825 5851.74 0.00 8378.54 8378.54 0.29871912 12.80 11.60 0.00800000 33059.8 40.31 21.27 0.00800000 61108.1
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_BOT_ZN_4 VAV BOX PERIMETER_BOT_ZN_4 N/A N/A N/A Yes Yes Yes No 4712.471 4712.471 0.287424 0.00004123 101.303 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2027 unknown unknown -999.0 -999.0   4197.9300 999.8980 13.14114152 54.44 82.22 27.78 1532500.15 0.3075 0.313691 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 4712.47 4712.47 1.0000 0.34569551 0.287424 12.80 11.58 0.00800000 33059.8 40.00 21.17 0.00800000 60796.0 0.04122255 60.00 32.22 27.78 0.000 4712.47 8.70 0.00699286 8.70 0.00000000 0.0000 20.85 0.00755437 21.00 0.00755437 48.8143 1824.38 0.00 4728.97 4728.97 0.34569551 12.80 11.60 0.00800000 33059.8 26.22 16.74 0.00800000 46739.4
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_MID_ZN_3 VAV BOX PERIMETER_MID_ZN_3 N/A N/A N/A Yes Yes Yes No 161898.763 161898.763 4.830283 0.00141636 4271.514 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2027 unknown unknown -999.0 -999.0   4197.9300 999.8980 13.14114152 54.44 82.22 27.78 1532500.15 10.5644 10.776967 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 161898.76 161898.76 1.0000 5.80956903 4.830283 12.80 11.58 0.00800000 33059.8 40.00 21.17 0.00800000 60796.0 1.41621653 60.00 32.22 27.78 0.000 161898.76 8.70 0.00699286 8.70 0.00000000 0.0000 20.95 0.00786873 21.00 0.00786873 50.8205 113335.61 0.00 162443.01 162443.01 5.80956903 12.80 11.60 0.00800000 33059.8 40.22 21.25 0.00800000 61021.1
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_MID_ZN_2 VAV BOX PERIMETER_MID_ZN_2 N/A N/A N/A Yes Yes Yes No 106699.929 106699.929 3.183614 0.00093346 2815.075 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2027 unknown unknown -999.0 -999.0   4197.9300 999.8980 13.14114152 54.44 82.22 27.78 1532500.15 6.9625 7.102597 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 106699.93 106699.93 1.0000 3.82905697 3.183614 12.80 11.58 0.00800000 33059.8 40.00 21.17 0.00800000 60796.0 0.93336230 60.00 32.22 27.78 0.000 106699.93 8.70 0.00699286 8.70 0.00000000 0.0000 20.95 0.00786985 21.00 0.00786985 50.8276 74692.14 0.00 107058.04 107058.04 3.82905697 12.80 11.60 0.00800000 33059.8 40.22 21.25 0.00800000 61019.2
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_MID_ZN_1 VAV BOX PERIMETER_MID_ZN_1 N/A N/A N/A Yes Yes Yes No 160348.888 160348.888 4.783906 0.00140280 4230.678 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2027 unknown unknown -999.0 -999.0   4197.9300 999.8980 13.14114152 54.44 82.22 27.78 1532500.15 10.4632 10.673798 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 160348.89 160348.89 1.0000 5.75379050 4.783906 12.80 11.58 0.00800000 33059.8 40.00 21.17 0.00800000 60796.0 1.40265892 60.00 32.22 27.78 0.000 160348.89 8.70 0.00699286 8.70 0.00000000 0.0000 20.95 0.00786687 21.00 0.00786687 50.8086 112252.18 0.00 160888.32 160888.32 5.75379050 12.80 11.60 0.00800000 33059.8 40.22 21.25 0.00800000 61022.0
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_MID_ZN_4 VAV BOX PERIMETER_MID_ZN_4 N/A N/A N/A Yes Yes Yes No 98090.893 98090.893 2.926168 0.00085814 2588.176 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2027 unknown unknown -999.0 -999.0   4197.9300 999.8980 13.14114152 54.44 82.22 27.78 1532500.15 6.4007 6.529527 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 98090.89 98090.89 1.0000 3.51941676 2.926168 12.80 11.58 0.00800000 33059.8 40.00 21.17 0.00800000 60796.0 0.85805439 60.00 32.22 27.78 0.000 98090.89 8.70 0.00699286 8.70 0.00000000 0.0000 20.91 0.00785160 21.00 0.00785160 50.7113 68672.56 0.00 98421.79 98421.79 3.51941676 12.80 11.60 0.00800000 33059.8 40.22 21.25 0.00800000 61025.2
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_TOP_ZN_3 VAV BOX PERIMETER_TOP_ZN_3 N/A N/A N/A Yes Yes Yes No 19847.347 19847.347 0.592454 0.00017363 523.526 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2027 unknown unknown -999.0 -999.0   4197.9300 999.8980 13.14114152 54.44 82.22 27.78 1532500.15 1.2951 1.321160 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 19847.35 19847.35 1.0000 0.71256755 0.592454 12.80 11.58 0.00800000 33059.8 40.00 21.17 0.00800000 60796.0 0.17361554 60.00 32.22 27.78 0.000 19847.35 8.70 0.00699286 8.70 0.00000000 0.0000 20.95 0.00788618 21.00 0.00788618 50.9317 13890.68 0.00 19913.18 19913.18 0.71256755 12.80 11.60 0.00800000 33059.8 40.21 21.24 0.00800000 61005.5
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_TOP_ZN_2 VAV BOX PERIMETER_TOP_ZN_2 N/A N/A N/A Yes Yes Yes No 13010.562 13010.562 0.388388 0.00011382 343.182 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2027 unknown unknown -999.0 -999.0   4197.9300 999.8980 13.14114152 54.44 82.22 27.78 1532500.15 0.8490 0.866062 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 13010.56 13010.56 1.0000 0.46712921 0.388388 12.80 11.58 0.00800000 33059.8 40.00 21.17 0.00800000 60796.0 0.11381046 60.00 32.22 27.78 0.000 13010.56 8.70 0.00699286 8.70 0.00000000 0.0000 20.95 0.00788542 21.00 0.00788542 50.9269 9105.63 0.00 13053.67 13053.67 0.46712921 12.80 11.60 0.00800000 33059.8 40.20 21.24 0.00800000 61004.3
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_TOP_ZN_1 VAV BOX PERIMETER_TOP_ZN_1 N/A N/A N/A Yes Yes Yes No 19707.399 19707.399 0.588266 0.00017241 519.839 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2027 unknown unknown -999.0 -999.0   4197.9300 999.8980 13.14114152 54.44 82.22 27.78 1532500.15 1.2860 1.311844 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 19707.40 19707.40 1.0000 0.70753063 0.588266 12.80 11.58 0.00800000 33059.8 40.00 21.17 0.00800000 60796.0 0.17239134 60.00 32.22 27.78 0.000 19707.40 8.70 0.00699286 8.70 0.00000000 0.0000 20.95 0.00788515 21.00 0.00788515 50.9251 13792.85 0.00 19772.80 19772.80 0.70753063 12.80 11.60 0.00800000 33059.8 40.21 21.24 0.00800000 61006.0
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_TOP_ZN_4 VAV BOX PERIMETER_TOP_ZN_4 N/A N/A N/A Yes Yes Yes No 12359.326 12359.326 0.368907 0.00010812 326.020 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2027 unknown unknown -999.0 -999.0   4197.9300 999.8980 13.14114152 54.44 82.22 27.78 1532500.15 0.8065 0.822712 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 12359.33 12359.33 1.0000 0.44369863 0.368907 12.80 11.58 0.00800000 33059.8 40.00 21.17 0.00800000 60796.0 0.10811375 60.00 32.22 27.78 0.000 12359.33 8.70 0.00699286 8.70 0.00000000 0.0000 20.95 0.00787636 21.00 0.00787636 50.8692 8650.33 0.00 12400.40 12400.40 0.44369863 12.80 11.60 0.00800000 33059.8 40.21 21.24 0.00800000 61007.6
VAV_BOT WITH REHEAT COOLING COIL Coil:Cooling:Water AirLoop AirLoopHVAC VAV_BOT WITH REHEAT CORE_BOTTOM; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_4; Coincident CoolingDesignCapacity N/A Yes Yes Yes No 270084.320 -999.000 10.138544 0.01149001 -999.000 -999.0000 1.00000 1.00000 1025.3847 1004.8586 1.2027 VAV_BOT WITH REHEAT FAN Fan:VariableVolume 10.138544 12.19402185   4197.9300 999.8980 141.35310771 12.27 6.67 5.60 3322986.53 8.1278 8.127759 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 15:10:00 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 15:10:00 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 Sensible 270084.32 188776.94 1.0000 12.19402185 10.138544 26.38 19.25 0.01105177 54692.2 11.06 11.06 0.00850000 32543.3 11.48883925 6.67 12.27 5.60 21792.441 248291.88 33.13 0.01716709 25.31 2.53819000 25.0351 24.00 0.00889182 24.00 0.00889182 47.7834 133679.63 0.00 270539.32 184084.57 12.19402185 26.38 19.27 0.01105177 54692.2 11.66 11.36 0.00824123 32506.0
VAV_BOT WITH REHEAT HEATING COIL Coil:Heating:Water AirLoop AirLoopHVAC VAV_BOT WITH REHEAT CORE_BOTTOM; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_4; Coincident HeatingDesignCapacity N/A Yes Yes Yes No 15573.042 15573.042 3.041563 0.00013624 276.832 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.2027 VAV_BOT WITH REHEAT FAN Fan:VariableVolume 10.138544 12.19402185   4197.9300 999.8980 13.14114152 54.44 82.22 27.78 1532500.15 1.0162 1.036636 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 15573.04 15573.04 1.0000 3.65820656 3.041563 8.56 8.56 0.00703813 26319.0 12.80 11.58 0.00800000 33059.8 0.13622586 60.00 32.22 27.78 0.000 15573.04 8.70 0.00699286 8.70 2.53819000 83.4502 7.88 0.00726641 21.67 0.00737157 45.7419 15159.83 0.00 16851.43 16851.43 3.65820656 2.80 2.80 0.00703813 20452.1 7.33 7.33 0.00703813 25058.6
VAV_MID WITH REHEAT COOLING COIL Coil:Cooling:Water AirLoop AirLoopHVAC VAV_MID WITH REHEAT CORE_MID; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_4; Coincident CoolingDesignCapacity N/A Yes Yes Yes No 2643274.952 -999.000 95.076369 0.11245103 -999.000 -999.0000 1.00000 1.00000 1025.9435 1004.8586 1.2027 VAV_MID WITH REHEAT FAN Fan:VariableVolume 95.076369 114.35205095   4197.9300 999.8980 141.35310771 12.27 6.67 5.60 3322986.53 79.5452 79.545160 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 15:30:00 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 15:30:00 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 Sensible 2643274.95 1791421.16 1.0000 114.35205095 95.076369 26.57 19.54 0.01135237 55650.0 11.05 11.05 0.00850000 32534.8 112.43955575 6.67 12.27 5.60 205454.970 2437819.98 33.00 0.01716683 25.27 25.38195000 26.6964 24.00 0.00902728 24.00 0.00902728 48.5023 1221431.24 0.00 2646856.89 1752365.53 114.35205095 26.57 19.55 0.01135237 55650.0 11.63 11.36 0.00825145 32503.5
VAV_MID WITH REHEAT HEATING COIL Coil:Heating:Water AirLoop AirLoopHVAC VAV_MID WITH REHEAT CORE_MID; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_4; Coincident HeatingDesignCapacity N/A Yes Yes Yes No 94643.344 94643.344 28.522911 0.00082798 1701.607 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.2027 VAV_MID WITH REHEAT FAN Fan:VariableVolume 95.076369 114.35205095   4197.9300 999.8980 13.14114152 54.44 82.22 27.78 1532500.15 6.1757 6.300037 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:30:00 unknown unknown MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 94643.34 94643.34 1.0000 34.30561529 28.522911 10.05 9.43 0.00709615 27982.8 12.80 11.58 0.00800000 33059.8 0.82789680 60.00 32.22 27.78 0.000 94643.34 8.70 0.00699286 8.70 25.38195000 88.9879 21.00 0.00793085 21.00 0.00792390 51.1716 538946.73 0.00 104542.10 104542.10 34.30561529 2.80 2.80 0.00709615 20597.5 5.79 5.79 0.00709615 23644.9
VAV_TOP WITH REHEAT COOLING COIL Coil:Cooling:Water AirLoop AirLoopHVAC VAV_TOP WITH REHEAT CORE_TOP; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_4; Coincident CoolingDesignCapacity N/A Yes Yes Yes No 271050.544 -999.000 10.293846 0.01153112 -999.000 -999.0000 1.00000 1.00000 1025.3162 1004.8586 1.2027 VAV_TOP WITH REHEAT FAN Fan:VariableVolume 10.293846 12.38080936   4197.9300 999.8980 141.35310771 12.27 6.67 5.60 3322986.53 8.1568 8.156835 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 15:30:00 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 15:30:00 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 16:10:00 Sensible 271050.54 189674.88 1.0000 12.38080936 10.293846 26.22 19.17 0.01101493 54436.0 11.06 11.06 0.00850000 32543.2 11.52994045 6.67 12.27 5.60 22126.257 248924.29 33.00 0.01716683 25.27 2.53819000 24.6574 24.00 0.00899303 24.00 0.00899303 48.3213 141048.04 0.00 271503.77 184865.10 12.38080936 26.22 19.19 0.01101493 54436.0 11.66 11.36 0.00824090 32506.6
VAV_TOP WITH REHEAT HEATING COIL Coil:Heating:Water AirLoop AirLoopHVAC VAV_TOP WITH REHEAT CORE_TOP; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_4; Coincident HeatingDesignCapacity N/A Yes Yes Yes No 7127.013 7127.013 3.088154 0.00006235 128.977 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.2027 VAV_TOP WITH REHEAT FAN Fan:VariableVolume 10.293846 12.38080936   4197.9300 999.8980 13.14114152 54.44 82.22 27.78 1532500.15 0.4651 0.474417 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 13:30:00 unknown unknown MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 7127.01 7127.01 1.0000 3.71424281 3.088154 10.89 9.88 0.00715845 28990.9 12.80 11.58 0.00800000 33059.8 0.06234386 60.00 32.22 27.78 0.000 7127.01 8.70 0.00699286 8.70 2.53819000 82.1912 21.00 0.00792272 21.00 0.00792272 51.1640 58940.06 0.00 7965.29 7965.29 3.71424281 2.80 2.80 0.00715845 20753.7 4.91 4.91 0.00715845 22898.2
CAV_BAS COOLING COIL Coil:Cooling:Water AirLoop AirLoopHVAC CAV_BAS BASEMENT Coincident CoolingDesignCapacity N/A Yes Yes Yes No 138576.711 -999.000 6.085539 0.00589537 -999.000 -999.0000 1.00000 1.00000 1024.4311 1004.8586 1.2027 CAV_BAS FAN Fan:ConstantVolume 6.085539 7.31931446   4197.9300 999.8980 141.35310771 12.27 6.67 5.60 3322986.53 4.1702 4.170246 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 Sensible 138576.71 100242.30 1.0000 7.31931446 6.085539 24.89 18.37 0.01053878 51850.6 11.42 11.42 0.00850000 32917.6 5.89477226 6.67 12.27 5.60 10318.970 128257.74 28.24 0.01715778 24.03 1.20015641 19.7214 24.06 0.00891274 24.00 0.00891274 47.8936 84401.13 0.00 138774.60 97461.15 7.31931446 24.89 18.38 0.01053878 51850.6 11.89 11.52 0.00830162 32890.5
CAV_BAS HEATING COIL Coil:Heating:Water AirLoop AirLoopHVAC CAV_BAS BASEMENT Coincident HeatingDesignCapacity N/A Yes Yes Yes No 281575.794 281575.794 6.085539 0.00246335 6431.563 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.2027 CAV_BAS FAN Fan:ConstantVolume 6.085539 7.31931446   4197.9300 999.8980 13.14114152 54.44 82.22 27.78 1532500.15 18.3736 18.743399 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 00:10:00 unknown unknown MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 00:10:00 Sensible 281575.79 281575.79 1.0000 7.31931446 6.085539 1.72 1.72 0.00699286 19235.1 40.00 21.17 0.00800000 60796.0 2.46309659 60.00 32.22 27.78 0.000 281575.79 8.70 0.00699286 8.70 1.20015641 19.7214 0.00 0.00699286 25.07 0.00699286 35.3535 0.00 0.00 243677.19 243677.19 7.31931446 12.80 10.55 0.00699286 30517.1 45.51 22.07 0.00699286 63809.4
AIRLOOP DATACENTER BASEMENT COOLING COIL COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoop AirLoopHVAC AIRLOOP DATACENTER BASEMENT DATACENTER_BASEMENT_ZN_6 Coincident CoolingDesignCapacity N/A Yes No unknown No 436486.136 313639.029 21.429762 0.01068952 -999.000 -999.0000 -999.00000 -999.00000 1020.9728 1004.8586 1.2027 unknown unknown -999.0 -999.0   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 14:00:00 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 14:00:00 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 07:10:00 Sensible 408959.69 398442.16 0.9369 -999.0 -999.0 28.50 18.07 0.00867846 50799.6 12.80 12.09 0.00850000 34322.2 -999.0 -999.00 -999.00 -999.00 0.000 408959.69 33.20 0.01716721 25.32 0.33839277 -999.0000 27.00 0.00854208 27.00 0.00854208 38.4360 372985.12 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
AIRLOOP DATACENTER BOT COOLING COIL COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoop AirLoopHVAC AIRLOOP DATACENTER BOT DATACENTER_BOT_ZN_6 Coincident CoolingDesignCapacity N/A Yes No unknown No 9798.885 7029.315 0.480091 0.00023997 -999.000 -999.0000 -999.00000 -999.00000 1021.3210 1004.8586 1.2027 unknown unknown -999.0 -999.0   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 18:40:00 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 18:40:00 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 18:50:00 Sensible 9183.41 8700.72 0.9372 -999.0 -999.0 28.07 18.08 0.00886577 50844.9 12.80 12.09 0.00850000 34322.2 -999.0 -999.00 -999.00 -999.00 0.000 9183.41 30.92 0.01716288 24.74 0.01563234 -999.0000 27.00 0.00858649 27.00 0.00858649 38.6307 8366.90 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
AIRLOOP DATACENTER MID COOLING COIL COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoop AirLoopHVAC AIRLOOP DATACENTER MID DATACENTER_MID_ZN_6 Coincident CoolingDesignCapacity N/A Yes No unknown No 93691.145 67117.651 4.578338 0.00229449 -999.000 -999.0000 -999.00000 -999.00000 1021.3539 1004.8586 1.2027 unknown unknown -999.0 -999.0   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 18:40:00 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 18:40:00 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 18:50:00 Sensible 87845.19 83018.63 0.9376 -999.0 -999.0 28.08 18.10 0.00888346 50896.3 12.80 12.09 0.00850000 34322.2 -999.0 -999.00 -999.00 -999.00 0.000 87845.19 30.92 0.01716288 24.74 0.15632344 -999.0000 27.00 0.00859067 27.00 0.00859067 38.6495 79769.94 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
AIRLOOP DATACENTER TOP COOLING COIL COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoop AirLoopHVAC AIRLOOP DATACENTER TOP DATACENTER_TOP_ZN_6 Coincident CoolingDesignCapacity N/A Yes No unknown No 9544.353 6841.258 0.466911 0.00023374 -999.000 -999.0000 -999.00000 -999.00000 1021.3401 1004.8586 1.2027 unknown unknown -999.0 -999.0   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 18:40:00 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 18:40:00 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 18:40:00 Sensible 8947.16 8464.52 0.9374 -999.0 -999.0 28.08 18.09 0.00887602 50874.7 12.80 12.09 0.00850000 34322.2 -999.0 -999.00 -999.00 -999.00 0.000 8947.16 30.92 0.01716288 24.74 0.01563234 -999.0000 27.00 0.00858896 27.00 0.00858896 38.6418 8138.00 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
AIRLOOP DATACENTER BASEMENT HEATING COIL COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoop AirLoopHVAC AIRLOOP DATACENTER BASEMENT DATACENTER_BASEMENT_ZN_6 Coincident HeatingDesignCapacity N/A Yes No unknown No 436486.136 436486.136 21.429762 0.01068952 -999.000 -999.0000 -999.00000 -999.00000 1019.7116 1004.8586 1.2027 unknown unknown -999.0 -999.0   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 00:10:00 unknown unknown MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 00:10:00 Sensible 436486.14 436486.14 1.0000 25.77440968 21.429762 8.70 8.70 0.00699286 26343.9 40.00 21.17 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 436486.14 8.70 0.00699286 8.70 0.33839277 1.5791 0.00 0.00850000 27.00 0.00850000 38.2434 0.00 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
AIRLOOP DATACENTER BOT HEATING COIL COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoop AirLoopHVAC AIRLOOP DATACENTER BOT DATACENTER_BOT_ZN_6 Coincident HeatingDesignCapacity N/A Yes No unknown No 9798.885 9798.885 0.480091 0.00023997 -999.000 -999.0000 -999.00000 -999.00000 1019.7116 1004.8586 1.2027 unknown unknown -999.0 -999.0   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 00:10:00 unknown unknown MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 00:10:00 Sensible 9798.88 9798.88 1.0000 0.57742409 0.480091 8.70 8.70 0.00699286 26343.9 40.00 21.17 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 9798.88 8.70 0.00699286 8.70 0.01563234 3.2561 0.00 0.00850000 27.00 0.00850000 38.2434 0.00 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
AIRLOOP DATACENTER MID HEATING COIL COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoop AirLoopHVAC AIRLOOP DATACENTER MID DATACENTER_MID_ZN_6 Coincident HeatingDesignCapacity N/A Yes No unknown No 93691.145 93691.145 4.578338 0.00229449 -999.000 -999.0000 -999.00000 -999.00000 1019.7116 1004.8586 1.2027 unknown unknown -999.0 -999.0   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 00:10:00 unknown unknown MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 00:10:00 Sensible 93691.14 93691.14 1.0000 5.50654477 4.578338 8.70 8.70 0.00699286 26343.9 40.00 21.17 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 93691.14 8.70 0.00699286 8.70 0.15632344 3.4144 0.00 0.00782254 24.70 0.00782254 40.3777 0.00 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
AIRLOOP DATACENTER TOP HEATING COIL COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoop AirLoopHVAC AIRLOOP DATACENTER TOP DATACENTER_TOP_ZN_6 Coincident HeatingDesignCapacity N/A Yes No unknown No 9544.353 9544.353 0.466911 0.00023374 -999.000 -999.0000 -999.00000 -999.00000 1019.7116 1004.8586 1.2027 unknown unknown -999.0 -999.0   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 00:10:00 unknown unknown MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 00:10:00 Sensible 9544.35 9544.35 1.0000 0.56157192 0.466911 8.70 8.70 0.00699286 26343.9 40.00 21.17 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 9544.35 8.70 0.00699286 8.70 0.01563234 3.3480 0.00 0.00707501 23.98 0.00707501 38.1638 0.00 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL Coil:Heating:Electric AirLoop AirLoopHVAC AIRLOOP DATACENTER BASEMENT DATACENTER_BASEMENT_ZN_6 Coincident HeatingDesignCapacity N/A Yes No unknown No 12800.936 12800.936 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.2027 AIRLOOP DATACENTER BASEMENT SUPPLY FAN Fan:OnOff 21.429762 25.77440968   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 00:10:00 unknown unknown MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 00:10:00 Sensible 12800.94 12800.94 1.0000 25.77440968 21.429762 0.14 0.14 0.00847620 21338.7 40.00 21.17 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 12800.94 8.70 0.00699286 8.70 0.33839277 1.5791 0.00 0.00850000 27.00 0.00850000 38.2434 0.00 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
AIRLOOP DATACENTER BOT_SUPPHEATCOIL Coil:Heating:Electric AirLoop AirLoopHVAC AIRLOOP DATACENTER BOT DATACENTER_BOT_ZN_6 Coincident HeatingDesignCapacity N/A Yes No unknown No 591.350 591.350 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.2027 AIRLOOP DATACENTER BOT SUPPLY FAN Fan:OnOff 0.480091 0.57742409   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 00:10:00 unknown unknown MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 00:10:00 Sensible 591.35 591.35 1.0000 0.57742409 0.480091 0.28 0.28 0.00845093 21424.4 40.00 21.17 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 591.35 8.70 0.00699286 8.70 0.01563234 3.2561 0.00 0.00850000 27.00 0.00850000 38.2434 0.00 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
AIRLOOP DATACENTER MID_SUPPHEATCOIL Coil:Heating:Electric AirLoop AirLoopHVAC AIRLOOP DATACENTER MID DATACENTER_MID_ZN_6 Coincident HeatingDesignCapacity N/A Yes No unknown No 5913.502 5913.502 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.2027 AIRLOOP DATACENTER MID SUPPLY FAN Fan:OnOff 4.578338 5.50654477   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 00:10:00 unknown unknown MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 00:10:00 Sensible 5913.50 5913.50 1.0000 5.50654477 4.578338 0.30 0.30 0.00779421 19795.7 40.00 21.17 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 5913.50 8.70 0.00699286 8.70 0.15632344 3.4144 0.00 0.00782254 24.70 0.00782254 40.3777 0.00 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
AIRLOOP DATACENTER TOP_SUPPHEATCOIL Coil:Heating:Electric AirLoop AirLoopHVAC AIRLOOP DATACENTER TOP DATACENTER_TOP_ZN_6 Coincident HeatingDesignCapacity N/A Yes No unknown No 591.350 591.350 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.2027 AIRLOOP DATACENTER TOP SUPPLY FAN Fan:OnOff 0.466911 0.56157192   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 00:10:00 unknown unknown MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 00:10:00 Sensible 591.35 591.35 1.0000 0.56157192 0.466911 0.29 0.29 0.00707226 17983.8 40.00 21.17 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 591.35 8.70 0.00699286 8.70 0.01563234 3.3480 0.00 0.00707501 23.98 0.00707501 38.1638 0.00 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0



Table of Contents

Report: System Summary

For: Entire Facility

Timestamp: 2023-10-16 08:43:45

Economizer

High Limit Shutoff Control Minimum Outdoor Air [m3/s] Maximum Outdoor Air [m3/s] Return Air Temp Limit Return Air Enthalpy Limit Outdoor Air Temperature Limit [C] Outdoor Air Enthalpy Limit [C]
None              


Demand Controlled Ventilation using Controller:MechanicalVentilation

Controller:MechanicalVentilation Name Outdoor Air Per Person [m3/s-person] Outdoor Air Per Area [m3/s-m2] Outdoor Air Per Zone [m3/s] Outdoor Air ACH [ach] Outdoor Air Method Outdoor Air Schedule Name Air Distribution Effectiveness in Cooling Mode Air Distribution Effectiveness in Heating Mode Air Distribution Effectiveness Schedule Name
CORE_BOTTOM VAV_BOT WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
CORE_MID VAV_MID WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
CORE_TOP VAV_TOP WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_BOT_ZN_3 VAV_BOT WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_BOT_ZN_2 VAV_BOT WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_BOT_ZN_1 VAV_BOT WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_BOT_ZN_4 VAV_BOT WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_MID_ZN_3 VAV_MID WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_MID_ZN_2 VAV_MID WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_MID_ZN_1 VAV_MID WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_MID_ZN_4 VAV_MID WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_TOP_ZN_3 VAV_TOP WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_TOP_ZN_2 VAV_TOP WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_TOP_ZN_1 VAV_TOP WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_TOP_ZN_4 VAV_TOP WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  


Time Not Comfortable Based on Simple ASHRAE 55-2004

Winter Clothes [hr] Summer Clothes [hr] Summer or Winter Clothes [hr]
BASEMENT 5725.33 2349.00 2349.00
CORE_BOTTOM 5523.83 33.67 0.00
CORE_MID 3826.67 566.67 0.00
CORE_TOP 3895.50 853.50 0.00
PERIMETER_BOT_ZN_3 5063.33 551.83 77.83
PERIMETER_BOT_ZN_2 4844.17 731.00 212.33
PERIMETER_BOT_ZN_1 5513.33 494.00 308.33
PERIMETER_BOT_ZN_4 5554.67 589.50 397.83
PERIMETER_MID_ZN_3 4406.17 1400.50 309.50
PERIMETER_MID_ZN_2 3786.50 1223.17 417.33
PERIMETER_MID_ZN_1 5287.50 843.17 507.50
PERIMETER_MID_ZN_4 4624.33 1233.00 364.83
PERIMETER_TOP_ZN_3 4333.67 1661.17 455.17
PERIMETER_TOP_ZN_2 4492.17 1509.67 500.00
PERIMETER_TOP_ZN_1 5100.00 1087.17 592.00
PERIMETER_TOP_ZN_4 4394.83 1511.33 444.50
DATACENTER_BOT_ZN_6 5943.00 2865.00 2865.00
DATACENTER_MID_ZN_6 5943.00 577.67 577.67
DATACENTER_TOP_ZN_6 5931.33 1168.83 1168.83
DATACENTER_BASEMENT_ZN_6 5943.00 5943.00 5943.00
GROUNDFLOOR_PLENUM 0.00 0.00 0.00
MIDFLOOR_PLENUM 0.00 0.00 0.00
TOPFLOOR_PLENUM 0.00 0.00 0.00
Facility 5943.00 5943.00 5943.00
Aggregated over the RunPeriods for Weather

Time Setpoint Not Met

During Heating [hr] During Cooling [hr] During Occupied Heating [hr] During Occupied Cooling [hr]
BASEMENT 0.00 88.83 0.00 4.17
CORE_BOTTOM 0.00 0.17 0.00 0.00
CORE_MID 0.00 0.00 0.00 0.00
CORE_TOP 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_3 0.00 11.33 0.00 8.00
PERIMETER_BOT_ZN_2 0.00 40.17 0.00 39.83
PERIMETER_BOT_ZN_1 0.00 143.17 0.00 137.83
PERIMETER_BOT_ZN_4 0.00 182.50 0.00 71.33
PERIMETER_MID_ZN_3 0.00 5.67 0.00 4.50
PERIMETER_MID_ZN_2 0.00 46.67 0.00 45.83
PERIMETER_MID_ZN_1 0.00 191.33 0.00 186.50
PERIMETER_MID_ZN_4 0.00 44.33 0.00 29.33
PERIMETER_TOP_ZN_3 0.50 23.17 0.00 19.17
PERIMETER_TOP_ZN_2 0.17 57.83 0.00 52.67
PERIMETER_TOP_ZN_1 0.17 125.33 0.00 115.17
PERIMETER_TOP_ZN_4 0.17 51.50 0.00 34.33
DATACENTER_BOT_ZN_6 0.00 12.33 0.00 12.33
DATACENTER_MID_ZN_6 0.00 0.33 0.00 0.33
DATACENTER_TOP_ZN_6 0.00 0.00 0.00 0.00
DATACENTER_BASEMENT_ZN_6 0.00 878.83 0.00 678.33
GROUNDFLOOR_PLENUM 0.00 0.00 0.00 0.00
MIDFLOOR_PLENUM 0.00 0.00 0.00 0.00
TOPFLOOR_PLENUM 0.00 0.00 0.00 0.00
Facility 0.50 1369.83 0.00 1000.17
Aggregated over the RunPeriods for Weather


Table of Contents

Report: Outdoor Air Summary

For: Entire Facility

Timestamp: 2023-10-16 08:43:45

Average Outdoor Air During Occupied Hours

Average Number of Occupants Nominal Number of Occupants Zone Volume [m3] Mechanical Ventilation [ach] Infiltration [ach] AFN Infiltration [ach] Simple Ventilation [ach]
BASEMENT 60.99 149.60 6779.02 0.524 0.000 0.000 0.000
CORE_BOTTOM 54.77 134.35 6849.35 0.733 0.000 0.000 0.000
CORE_MID 54.77 134.35 6849.35 0.697 0.000 0.000 0.000
CORE_TOP 54.77 134.35 6849.35 0.698 0.000 0.000 0.000
PERIMETER_BOT_ZN_3 6.88 16.87 860.00 0.896 0.045 0.000 0.000
PERIMETER_BOT_ZN_2 4.43 10.87 554.22 1.166 0.046 0.000 0.000
PERIMETER_BOT_ZN_1 6.88 16.87 860.02 1.141 0.045 0.000 0.000
PERIMETER_BOT_ZN_4 4.43 10.87 554.22 1.627 0.047 0.000 0.000
PERIMETER_MID_ZN_3 6.88 16.87 860.00 0.871 0.105 0.000 0.000
PERIMETER_MID_ZN_2 3.86 10.87 554.22 1.207 0.115 0.000 0.000
PERIMETER_MID_ZN_1 6.88 16.87 860.02 1.172 0.106 0.000 0.000
PERIMETER_MID_ZN_4 4.43 10.87 554.22 1.337 0.109 0.000 0.000
PERIMETER_TOP_ZN_3 6.88 16.87 860.00 0.870 0.131 0.000 0.000
PERIMETER_TOP_ZN_2 4.43 10.87 554.22 1.261 0.135 0.000 0.000
PERIMETER_TOP_ZN_1 6.88 16.87 860.02 1.153 0.131 0.000 0.000
PERIMETER_TOP_ZN_4 4.43 10.87 554.22 1.339 0.135 0.000 0.000
DATACENTER_BOT_ZN_6 0.79 1.95 99.34 0.584 0.000 0.000 0.000
DATACENTER_MID_ZN_6 0.79 1.95 99.34 0.584 0.000 0.000 0.000
DATACENTER_TOP_ZN_6 0.79 1.95 99.34 0.584 0.000 0.000 0.000
DATACENTER_BASEMENT_ZN_6 17.20 42.18 1911.37 0.658 0.000 0.000 0.000
Values shown for a single zone without multipliers

Minimum Outdoor Air During Occupied Hours

Average Number of Occupants Nominal Number of Occupants Zone Volume [m3] Mechanical Ventilation [ach] Infiltration [ach] AFN Infiltration [ach] Simple Ventilation [ach]
BASEMENT 60.99 149.60 6779.02 0.000 0.000 0.000 0.000
CORE_BOTTOM 54.77 134.35 6849.35 0.000 0.000 0.000 0.000
CORE_MID 54.77 134.35 6849.35 0.000 0.000 0.000 0.000
CORE_TOP 54.77 134.35 6849.35 0.000 0.000 0.000 0.000
PERIMETER_BOT_ZN_3 6.88 16.87 860.00 0.000 0.000 0.000 0.000
PERIMETER_BOT_ZN_2 4.43 10.87 554.22 0.000 0.000 0.000 0.000
PERIMETER_BOT_ZN_1 6.88 16.87 860.02 0.000 0.000 0.000 0.000
PERIMETER_BOT_ZN_4 4.43 10.87 554.22 0.000 0.000 0.000 0.000
PERIMETER_MID_ZN_3 6.88 16.87 860.00 0.000 0.000 0.000 0.000
PERIMETER_MID_ZN_2 3.86 10.87 554.22 0.000 0.000 0.000 0.000
PERIMETER_MID_ZN_1 6.88 16.87 860.02 0.000 0.000 0.000 0.000
PERIMETER_MID_ZN_4 4.43 10.87 554.22 0.000 0.000 0.000 0.000
PERIMETER_TOP_ZN_3 6.88 16.87 860.00 0.000 0.000 0.000 0.000
PERIMETER_TOP_ZN_2 4.43 10.87 554.22 0.000 0.000 0.000 0.000
PERIMETER_TOP_ZN_1 6.88 16.87 860.02 0.000 0.000 0.000 0.000
PERIMETER_TOP_ZN_4 4.43 10.87 554.22 0.000 0.000 0.000 0.000
DATACENTER_BOT_ZN_6 0.79 1.95 99.34 0.572 0.000 0.000 0.000
DATACENTER_MID_ZN_6 0.79 1.95 99.34 0.572 0.000 0.000 0.000
DATACENTER_TOP_ZN_6 0.79 1.95 99.34 0.572 0.000 0.000 0.000
DATACENTER_BASEMENT_ZN_6 17.20 42.18 1911.37 0.644 0.000 0.000 0.000
Values shown for a single zone without multipliers


Table of Contents

Report: Outdoor Air Details

For: Entire Facility

Timestamp: 2023-10-16 08:43:45

Mechanical Ventilation Parameters by Zone

AirLoop Name Average Number of Occupants Nominal Number of Occupants Zone Volume [m3] Zone Area [m2] Design Zone Outdoor Airflow - Voz [m3/s] Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s]
BASEMENT CAV_BAS 60.99 149.60 6779.02 2779.43 1.2002 1.200
CORE_BOTTOM VAV_BOT WITH REHEAT 54.77 134.35 6849.35 2496.12 0.0000 1.078
CORE_MID VAV_MID WITH REHEAT 54.77 134.35 6849.35 2496.12 0.0000 10.778
CORE_TOP VAV_TOP WITH REHEAT 54.77 134.35 6849.35 2496.12 0.0000 1.078
PERIMETER_BOT_ZN_3 VAV_BOT WITH REHEAT 6.88 16.87 860.00 313.41 0.0000 0.135
PERIMETER_BOT_ZN_2 VAV_BOT WITH REHEAT 4.43 10.87 554.22 201.98 0.0000 0.087
PERIMETER_BOT_ZN_1 VAV_BOT WITH REHEAT 6.88 16.87 860.02 313.42 0.0000 0.135
PERIMETER_BOT_ZN_4 VAV_BOT WITH REHEAT 4.43 10.87 554.22 201.98 0.0000 0.087
PERIMETER_MID_ZN_3 VAV_MID WITH REHEAT 6.88 16.87 860.00 313.41 0.0000 1.353
PERIMETER_MID_ZN_2 VAV_MID WITH REHEAT 3.86 10.87 554.22 201.98 0.0000 0.872
PERIMETER_MID_ZN_1 VAV_MID WITH REHEAT 6.88 16.87 860.02 313.42 0.0000 1.353
PERIMETER_MID_ZN_4 VAV_MID WITH REHEAT 4.43 10.87 554.22 201.98 0.0000 0.872
PERIMETER_TOP_ZN_3 VAV_TOP WITH REHEAT 6.88 16.87 860.00 313.41 0.0000 0.135
PERIMETER_TOP_ZN_2 VAV_TOP WITH REHEAT 4.43 10.87 554.22 201.98 0.0000 0.087
PERIMETER_TOP_ZN_1 VAV_TOP WITH REHEAT 6.88 16.87 860.02 313.42 0.0000 0.135
PERIMETER_TOP_ZN_4 VAV_TOP WITH REHEAT 4.43 10.87 554.22 201.98 0.0000 0.087
DATACENTER_BOT_ZN_6 AIRLOOP DATACENTER BOT 0.79 1.95 99.34 36.20 0.0156 0.016
DATACENTER_MID_ZN_6 AIRLOOP DATACENTER MID 0.79 1.95 99.34 36.20 0.1563 0.156
DATACENTER_TOP_ZN_6 AIRLOOP DATACENTER TOP 0.79 1.95 99.34 36.20 0.0156 0.016
DATACENTER_BASEMENT_ZN_6 AIRLOOP DATACENTER BASEMENT 17.20 42.18 1911.37 783.68 0.3384 0.338
Total Facility   1010.73 2493.19 126016.35 46320.38 1.7261 158.471


Total Outdoor Air by Zone

Mechanical Ventilation [m3] Natural Ventilation [m3] Total Ventilation [m3] Infiltration [m3] Total Ventilation and Infiltration [m3] Dynamic Target Ventilation - Voz-dyn [m3] Time Below Voz-dyn [hr] Time At Voz-dyn [hr] Time Above Voz-dyn [hr] Time Above Zero When Unoccupied [hr]
BASEMENT 23373277.62 0.00 23373277.62 0.00 23373277.62 37848132.68 3350.22 5409.78 0.00 643.85
CORE_BOTTOM 36415928.59 0.00 36415928.59 0.00 36415928.59 33990283.35 2278.13 7.14 6474.73 1195.50
CORE_MID 0.31E+09 0.00 0.31E+09 0.00 0.31E+09 0.34E+09 3156.96 1.92 5601.12 532.18
CORE_TOP 30875374.01 0.00 30875374.01 0.00 30875374.01 33990283.35 3195.68 5.82 5558.50 507.41
PERIMETER_BOT_ZN_3 5383844.11 0.00 5383844.11 419809.91 5803654.02 4267819.30 2413.20 18.01 6328.80 1195.50
PERIMETER_BOT_ZN_2 4569298.95 0.00 4569298.95 279873.08 4849172.03 2750345.05 2278.83 0.21 6480.96 1195.50
PERIMETER_BOT_ZN_1 6612903.81 0.00 6612903.81 419809.91 7032713.72 4267912.63 2282.08 2.40 6475.52 1195.50
PERIMETER_BOT_ZN_4 6336696.92 0.00 6336696.92 279873.08 6616570.01 2750345.05 2268.23 0.00 6491.77 1195.50
PERIMETER_MID_ZN_3 47590834.79 0.00 47590834.79 984550.17 48575384.95 42678193.03 3208.03 18.58 5533.39 532.18
PERIMETER_MID_ZN_2 44533342.83 0.00 44533342.83 656366.33 45189709.16 27503450.52 3156.60 0.17 5603.22 1441.18
PERIMETER_MID_ZN_1 62723349.70 0.00 62723349.70 984550.17 63707899.87 42679126.28 3156.74 0.13 5603.13 532.18
PERIMETER_MID_ZN_4 47492185.41 0.00 47492185.41 656366.33 48148551.74 27503450.52 3150.99 0.13 5608.88 532.18
PERIMETER_TOP_ZN_3 4741175.66 0.00 4741175.66 1222397.02 5963572.69 4267819.30 3209.89 10.66 5539.45 507.41
PERIMETER_TOP_ZN_2 4427308.74 0.00 4427308.74 814930.79 5242239.53 2750345.05 3185.99 0.93 5573.08 507.41
PERIMETER_TOP_ZN_1 6159825.79 0.00 6159825.79 1222397.02 7382222.81 4267912.63 3186.34 0.22 5573.44 507.41
PERIMETER_TOP_ZN_4 4753435.58 0.00 4753435.58 814930.79 5568366.37 2750345.05 3183.29 0.00 5576.71 507.41
DATACENTER_BOT_ZN_6 492981.60 0.00 492981.60 0.00 492981.60 492981.60 0.00 8760.00 0.00 2817.00
DATACENTER_MID_ZN_6 4929815.99 0.00 4929815.99 0.00 4929815.99 4929815.99 0.00 8760.00 0.00 2817.00
DATACENTER_TOP_ZN_6 492981.60 0.00 492981.60 0.00 492981.60 492981.60 0.00 8760.00 0.00 2817.00
DATACENTER_BASEMENT_ZN_6 10671554.30 0.00 10671554.30 0.00 10671554.30 10671554.30 0.00 8760.00 0.00 2817.00
Total Facility 0.53E+10 0.00 0.53E+10 38292351.59 0.54E+10 0.50E+10 4075.75 8760.00 6768.74 3726.00


Average Outdoor Air During Occupancy by Zone - Flow Rates

Mechanical Ventilation [m3/s] Natural Ventilation [m3/s] Total Ventilation [m3/s] Infiltration [m3/s] Total Ventilation and Infiltration [m3/s] Dynamic Target Ventilation - Voz-dyn [m3/s] Time Below Voz-dyn [hr] Time At Voz-dyn [hr] Time Above Voz-dyn [hr]
BASEMENT 0.9625 0.0000 0.9625 0.0000 0.9625 1.2002 1177.07 4765.93 0.00
CORE_BOTTOM 1.3652 0.0000 1.3652 0.0000 1.3652 1.0778 655.81 6.85 5280.34
CORE_MID 12.9935 0.0000 12.9935 0.0000 12.9935 10.7782 870.80 1.82 5070.39
CORE_TOP 1.3003 0.0000 1.3003 0.0000 1.3003 1.0778 884.15 5.58 5053.27
PERIMETER_BOT_ZN_3 0.2095 0.0000 0.2095 0.0105 0.2199 0.1353 783.77 17.67 5141.56
PERIMETER_BOT_ZN_2 0.1757 0.0000 0.1757 0.0070 0.1826 0.0872 652.19 0.11 5290.70
PERIMETER_BOT_ZN_1 0.2666 0.0000 0.2666 0.0105 0.2771 0.1353 653.97 2.32 5286.71
PERIMETER_BOT_ZN_4 0.2450 0.0000 0.2450 0.0070 0.2520 0.0872 646.70 0.00 5296.30
PERIMETER_MID_ZN_3 2.0349 0.0000 2.0349 0.0246 2.0595 1.3533 918.83 18.46 5005.72
PERIMETER_MID_ZN_2 1.8196 0.0000 1.8196 0.0173 1.8369 0.8721 869.54 0.04 4164.42
PERIMETER_MID_ZN_1 2.7384 0.0000 2.7384 0.0246 2.7630 1.3533 869.59 0.10 5073.31
PERIMETER_MID_ZN_4 2.0145 0.0000 2.0145 0.0164 2.0309 0.8721 866.04 0.07 5076.89
PERIMETER_TOP_ZN_3 0.2034 0.0000 0.2034 0.0306 0.2340 0.1353 897.77 10.60 5034.63
PERIMETER_TOP_ZN_2 0.1900 0.0000 0.1900 0.0204 0.2104 0.0872 875.40 0.69 5066.91
PERIMETER_TOP_ZN_1 0.2694 0.0000 0.2694 0.0306 0.3000 0.1353 875.52 0.17 5067.31
PERIMETER_TOP_ZN_4 0.2019 0.0000 0.2019 0.0204 0.2223 0.0872 873.70 0.00 5069.30
DATACENTER_BOT_ZN_6 0.0156 0.0000 0.0156 0.0000 0.0156 0.0156 0.00 5943.00 0.00
DATACENTER_MID_ZN_6 0.1563 0.0000 0.1563 0.0000 0.1563 0.1563 0.00 5943.00 0.00
DATACENTER_TOP_ZN_6 0.0156 0.0000 0.0156 0.0000 0.0156 0.0156 0.00 5943.00 0.00
DATACENTER_BASEMENT_ZN_6 0.3384 0.0000 0.3384 0.0000 0.3384 0.3384 0.00 5943.00 0.00
Total Facility 223.3311 0.0000 223.3311 0.9663 224.2974 158.4706 1442.46 5943.00 5424.31


Total Outdoor Air by AirLoop

Mechanical Ventilation [m3] Natural Ventilation [m3/s] Total Ventilation [m3/s] Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] Time Below Voz-sum-dyn [hr] Time At Voz-sum-dyn [hr] Time Above Voz-sum-dyn [hr] Time Above Zero When Unoccupied [hr]
VAV_BOT WITH REHEAT 85809262.53 0.00 85809262.53 48026705.38 2268.20 0.00 6491.80 1195.50
VAV_MID WITH REHEAT 0.74E+09 0.00 0.74E+09 0.48E+09 3150.74 0.00 5609.26 532.18
VAV_TOP WITH REHEAT 73713598.01 0.00 73713598.01 48026705.38 3183.29 0.00 5576.71 507.41
CAV_BAS 33811338.05 0.00 33811338.05 37848132.68 3350.22 0.00 5409.78 643.85
AIRLOOP DATACENTER BASEMENT 15437267.12 0.00 15437267.12 10671554.30 0.00 0.00 8760.00 2817.00
AIRLOOP DATACENTER BOT 713137.79 0.00 713137.79 492981.60 0.00 0.00 8760.00 2817.00
AIRLOOP DATACENTER MID 7131377.88 0.00 7131377.88 4929815.99 0.00 0.00 8760.00 2817.00
AIRLOOP DATACENTER TOP 713137.79 0.00 713137.79 492981.60 0.00 0.00 8760.00 2817.00


Average Outdoor Air During Occupancy by AirLoop

Mechanical Ventilation [m3/s] Natural Ventilation [m3/s] Total Ventilation [m3/s] Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] Time Below Voz-sum-dyn [hr] Time At Voz-sum-dyn [hr] Time Above Voz-sum-dyn [hr]
VAV_BOT WITH REHEAT 3.2722 0.0000 3.2722 1.5229 646.70 0.00 5296.30
VAV_MID WITH REHEAT 31.3672 0.0000 31.3672 15.2292 865.92 0.00 5077.08
VAV_TOP WITH REHEAT 3.1319 0.0000 3.1319 1.5229 873.70 0.00 5069.30
CAV_BAS 1.3923 0.0000 1.3923 1.2002 1177.07 0.00 4765.93
AIRLOOP DATACENTER BASEMENT 0.4895 0.0000 0.4895 0.3384 0.00 0.00 5943.00
AIRLOOP DATACENTER BOT 0.0226 0.0000 0.0226 0.0156 0.00 0.00 5943.00
AIRLOOP DATACENTER MID 0.2261 0.0000 0.2261 0.1563 0.00 0.00 5943.00
AIRLOOP DATACENTER TOP 0.0226 0.0000 0.0226 0.0156 0.00 0.00 5943.00


Outdoor Air Controller Limiting Factors by AirLoop

No Limiting Factor [hr] Limits and Scheduled Limits [hr] Economizer [hr] Exhaust Flow [hr] Mixed Air Flow [hr] High Humidity [hr] Demand Controlled Ventilation [hr] Night Ventilation [hr] Demand Limiting [hr] Energy Management System [hr]
VAV_BOT WITH REHEAT 0.00 6491.80 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
VAV_MID WITH REHEAT 0.00 5609.26 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
VAV_TOP WITH REHEAT 0.00 5576.71 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CAV_BAS 0.00 5409.78 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
AIRLOOP DATACENTER BASEMENT 0.00 8760.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
AIRLOOP DATACENTER BOT 0.00 8760.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
AIRLOOP DATACENTER MID 0.00 8760.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
AIRLOOP DATACENTER TOP 0.00 8760.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Average Outdoor Air for Limiting Factors During Occupancy

No Limiting Factor [m3/s] Limits and Scheduled Limits [m3/s] Economizer [m3/s] Exhaust Flow [m3/s] Mixed Air Flow [m3/s] High Humidity [m3/s] Demand Controlled Ventilation [m3/s] Night Ventilation [m3/s] Demand Limiting [m3/s] Energy Management System [m3/s]
VAV_BOT WITH REHEAT 0.0000 3.6719 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
VAV_MID WITH REHEAT 0.0000 36.7176 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
VAV_TOP WITH REHEAT 0.0000 3.6719 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
CAV_BAS 0.0000 1.7365 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
AIRLOOP DATACENTER BASEMENT 0.0000 0.4895 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
AIRLOOP DATACENTER BOT 0.0000 0.0226 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
AIRLOOP DATACENTER MID 0.0000 0.2261 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
AIRLOOP DATACENTER TOP 0.0000 0.0226 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000



Table of Contents

Report: Object Count Summary

For: Entire Facility

Timestamp: 2023-10-16 08:43:45

Surfaces by Class

Total Outdoors
Wall 98 30
Floor 41 0
Roof 30 1
Internal Mass 16 0
Building Detached Shading 0 0
Fixed Detached Shading 0 0
Window 24 24
Door 12 12
Glass Door 0 0
Shading 0 0
Overhang 0 0
Fin 0 0
Tubular Daylighting Device Dome 0 0
Tubular Daylighting Device Diffuser 0 0


HVAC

Count
HVAC Air Loops 8
Conditioned Zones 23
Unconditioned Zones 0
Supply Plenums 0
Return Plenums 3


Input Fields

Count
IDF Objects 1404
Defaulted Fields 1182
Fields with Defaults 3915
Autosized Fields 338
Autosizable Fields 414
Autocalculated Fields 226
Autocalculatable Fields 473



Table of Contents

Report: Energy Meters

For: Entire Facility

Timestamp: 2023-10-16 08:43:45

Annual and Peak Values - Electricity

Electricity Annual Value [GJ] Electricity Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Electricity Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
Electricity:Facility 33818.50 377399.06 22-JAN-05:00 1989371.34 23-AUG-15:10
Electricity:Building 18598.65 225715.65 29-MAY-17:10 1164206.62 15-DEC-16:40
Electricity:Zone:BASEMENT 687.24 14732.47 01-JAN-00:10 36407.88 02-JAN-08:10
Electricity:SpaceType:GENERAL 18598.65 225715.65 29-MAY-17:10 1164206.62 15-DEC-16:40
InteriorLights:Electricity 3922.25 18459.50 01-JAN-09:50 385834.94 27-SEP-07:10
InteriorLights:Electricity:Zone:BASEMENT 262.84 1274.92 01-JAN-00:10 22950.34 02-JAN-08:10
InteriorLights:Electricity:SpaceType:GENERAL 3922.25 18459.50 01-JAN-09:50 385834.94 27-SEP-07:10
LightsWired:InteriorLights:Electricity 3922.25 18459.50 01-JAN-09:50 385834.94 27-SEP-07:10
LightsWired:InteriorLights:Electricity:Zone:BASEMENT 262.84 1274.92 01-JAN-00:10 22950.34 02-JAN-08:10
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL 3922.25 18459.50 01-JAN-09:50 385834.94 27-SEP-07:10
Electricity:Zone:CORE_BOTTOM 525.67 5598.20 01-JAN-00:10 37817.64 02-JAN-08:10
InteriorLights:Electricity:Zone:CORE_BOTTOM 236.05 1144.97 01-JAN-00:10 20611.01 02-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:CORE_BOTTOM 236.05 1144.97 01-JAN-00:10 20611.01 02-JAN-08:10
Electricity:Zone:CORE_MID 5256.66 55981.88 01-JAN-00:10 378175.77 02-JAN-08:10
InteriorLights:Electricity:Zone:CORE_MID 2360.53 11449.71 01-JAN-00:10 206110.14 02-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:CORE_MID 2360.53 11449.71 01-JAN-00:10 206110.14 02-JAN-08:10
Electricity:Zone:CORE_TOP 525.67 5598.19 01-JAN-00:10 37817.58 02-JAN-08:10
InteriorLights:Electricity:Zone:CORE_TOP 236.05 1144.97 01-JAN-00:10 20611.01 02-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:CORE_TOP 236.05 1144.97 01-JAN-00:10 20611.01 02-JAN-08:10
Electricity:Zone:PERIMETER_BOT_ZN_3 53.57 627.57 02-APR-17:10 4748.47 27-SEP-07:10
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 17.21 68.40 01-JAN-09:50 2587.92 27-SEP-07:10
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 17.21 68.40 01-JAN-09:50 2587.92 27-SEP-07:10
Electricity:Zone:PERIMETER_BOT_ZN_2 34.46 404.43 29-MAY-17:10 3060.10 27-SEP-07:10
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 11.02 44.08 01-JAN-07:40 1667.75 27-SEP-07:10
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 11.02 44.08 01-JAN-07:40 1667.75 27-SEP-07:10
Electricity:Zone:PERIMETER_BOT_ZN_1 53.32 627.58 19-MAR-17:10 4748.56 27-SEP-07:10
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 16.96 68.40 01-JAN-07:40 2587.98 27-SEP-07:10
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 16.96 68.40 01-JAN-07:40 2587.98 27-SEP-07:10
Electricity:Zone:PERIMETER_BOT_ZN_4 34.44 404.43 12-MAR-17:10 3060.09 15-JUN-07:10
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 11.01 44.08 01-JAN-09:40 1667.75 15-JUN-07:10
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 11.01 44.08 01-JAN-09:40 1667.75 15-JUN-07:10
Electricity:Zone:PERIMETER_MID_ZN_3 535.29 6275.73 02-APR-17:10 47484.70 27-SEP-07:10
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 171.63 684.02 01-JAN-09:40 25879.19 27-SEP-07:10
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 171.63 684.02 01-JAN-09:40 25879.19 27-SEP-07:10
Electricity:Zone:PERIMETER_MID_ZN_2 344.42 4044.32 29-MAY-17:10 30600.95 27-SEP-07:10
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 110.06 440.81 01-JAN-07:40 16677.53 27-SEP-07:10
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 110.06 440.81 01-JAN-07:40 16677.53 27-SEP-07:10
Electricity:Zone:PERIMETER_MID_ZN_1 532.97 6275.83 12-MAR-17:10 47485.60 27-SEP-07:10
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 169.32 684.04 01-JAN-07:40 25879.75 27-SEP-07:10
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 169.32 684.04 01-JAN-07:40 25879.75 27-SEP-07:10
Electricity:Zone:PERIMETER_MID_ZN_4 344.19 4044.30 12-MAR-17:10 30600.86 15-JUN-07:10
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 109.84 440.81 01-JAN-09:30 16677.53 15-JUN-07:10
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 109.84 440.81 01-JAN-09:30 16677.53 15-JUN-07:10
Electricity:Zone:PERIMETER_TOP_ZN_3 53.53 627.57 02-APR-17:10 4748.47 27-SEP-07:10
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 17.16 68.40 01-JAN-09:40 2587.92 27-SEP-07:10
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 17.16 68.40 01-JAN-09:40 2587.92 27-SEP-07:10
Electricity:Zone:PERIMETER_TOP_ZN_2 34.44 404.43 29-MAY-17:10 3060.10 27-SEP-07:10
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 11.01 44.08 01-JAN-07:40 1667.75 27-SEP-07:10
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 11.01 44.08 01-JAN-07:40 1667.75 27-SEP-07:10
Electricity:Zone:PERIMETER_TOP_ZN_1 53.30 627.58 12-MAR-17:10 4748.56 27-SEP-07:10
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 16.93 68.40 01-JAN-07:40 2587.98 27-SEP-07:10
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 16.93 68.40 01-JAN-07:40 2587.98 27-SEP-07:10
Electricity:Zone:PERIMETER_TOP_ZN_4 34.42 404.43 12-MAR-17:10 3060.09 15-JUN-07:10
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 10.98 44.08 01-JAN-09:30 1667.75 15-JUN-07:10
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 10.98 44.08 01-JAN-09:30 1667.75 15-JUN-07:10
Electricity:Zone:DATACENTER_BASEMENT_ZN_6 7568.97 95267.60 01-JAN-00:10 386103.53 03-APR-07:10
InteriorLights:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 74.11 359.47 01-JAN-00:10 6471.01 02-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 74.11 359.47 01-JAN-00:10 6471.01 02-JAN-08:10
Electricity:Zone:DATACENTER_BOT_ZN_6 160.51 1980.76 01-JAN-00:10 8373.14 03-APR-07:10
InteriorLights:Electricity:Zone:DATACENTER_BOT_ZN_6 6.63 32.15 01-JAN-00:10 578.72 02-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_BOT_ZN_6 6.63 32.15 01-JAN-00:10 578.72 02-JAN-08:10
Electricity:Zone:DATACENTER_MID_ZN_6 1605.09 19807.58 01-JAN-00:10 83731.41 03-APR-07:10
InteriorLights:Electricity:Zone:DATACENTER_MID_ZN_6 66.28 321.53 01-JAN-00:10 5787.18 02-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_MID_ZN_6 66.28 321.53 01-JAN-00:10 5787.18 02-JAN-08:10
Electricity:Zone:DATACENTER_TOP_ZN_6 160.51 1980.76 01-JAN-00:10 8373.14 03-APR-07:10
InteriorLights:Electricity:Zone:DATACENTER_TOP_ZN_6 6.63 32.15 01-JAN-00:10 578.72 02-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_TOP_ZN_6 6.63 32.15 01-JAN-00:10 578.72 02-JAN-08:10
InteriorEquipment:Electricity 14676.40 207256.16 01-JAN-00:10 778371.69 03-APR-07:10
InteriorEquipment:Electricity:Zone:BASEMENT 424.40 13457.54 01-JAN-00:10 13457.54 01-JAN-00:10
InteriorEquipment:Electricity:SpaceType:GENERAL 14676.40 207256.16 01-JAN-00:10 778371.69 03-APR-07:10
MiscPlug:InteriorEquipment:Electricity 5334.97 88964.76 01-JAN-00:10 305206.10 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:BASEMENT 424.40 13457.54 01-JAN-00:10 13457.54 01-JAN-00:10
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL 5334.97 88964.76 01-JAN-00:10 305206.10 02-JAN-08:10
InteriorEquipment:Electricity:Zone:CORE_BOTTOM 289.61 4453.23 01-JAN-00:10 17206.63 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_BOTTOM 289.61 4453.23 01-JAN-00:10 17206.63 02-JAN-08:10
InteriorEquipment:Electricity:Zone:CORE_MID 2896.13 44532.17 01-JAN-00:10 172065.63 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_MID 2896.13 44532.17 01-JAN-00:10 172065.63 02-JAN-08:10
InteriorEquipment:Electricity:Zone:CORE_TOP 289.61 4453.22 01-JAN-00:10 17206.56 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_TOP 289.61 4453.22 01-JAN-00:10 17206.56 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 36.37 559.17 01-JAN-00:10 2160.55 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 36.37 559.17 01-JAN-00:10 2160.55 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 23.44 360.35 01-JAN-00:10 1392.34 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 23.44 360.35 01-JAN-00:10 1392.34 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 36.37 559.18 01-JAN-00:10 2160.58 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 36.37 559.18 01-JAN-00:10 2160.58 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 23.44 360.35 01-JAN-00:10 1392.33 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 23.44 360.35 01-JAN-00:10 1392.33 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 363.65 5591.71 01-JAN-00:10 21605.52 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 363.65 5591.71 01-JAN-00:10 21605.52 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 234.35 3603.51 01-JAN-00:10 13923.42 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 234.35 3603.51 01-JAN-00:10 13923.42 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 363.66 5591.79 01-JAN-00:10 21605.85 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 363.66 5591.79 01-JAN-00:10 21605.85 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 234.35 3603.49 01-JAN-00:10 13923.33 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 234.35 3603.49 01-JAN-00:10 13923.33 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 36.37 559.17 01-JAN-00:10 2160.55 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 36.37 559.17 01-JAN-00:10 2160.55 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 23.44 360.35 01-JAN-00:10 1392.34 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 23.44 360.35 01-JAN-00:10 1392.34 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 36.37 559.18 01-JAN-00:10 2160.58 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 36.37 559.18 01-JAN-00:10 2160.58 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 23.44 360.35 01-JAN-00:10 1392.33 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 23.44 360.35 01-JAN-00:10 1392.33 02-JAN-08:10
InteriorEquipment:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 7494.86 94908.13 01-JAN-00:10 379632.52 31-MAR-23:10
DataCenterPlugLoads:InteriorEquipment:Electricity 9341.42 118291.40 01-JAN-00:10 473165.59 31-MAR-23:10
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 7494.86 94908.13 01-JAN-00:10 379632.52 31-MAR-23:10
DataCenterPlugLoads:InteriorEquipment:Electricity:SpaceType:GENERAL 9341.42 118291.40 01-JAN-00:10 473165.59 31-MAR-23:10
InteriorEquipment:Electricity:Zone:DATACENTER_BOT_ZN_6 153.88 1948.61 01-JAN-00:10 7794.42 31-MAR-23:10
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_BOT_ZN_6 153.88 1948.61 01-JAN-00:10 7794.42 31-MAR-23:10
InteriorEquipment:Electricity:Zone:DATACENTER_MID_ZN_6 1538.81 19486.06 01-JAN-00:10 77944.22 31-MAR-23:10
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_MID_ZN_6 1538.81 19486.06 01-JAN-00:10 77944.22 31-MAR-23:10
InteriorEquipment:Electricity:Zone:DATACENTER_TOP_ZN_6 153.88 1948.61 01-JAN-00:10 7794.42 31-MAR-23:10
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_TOP_ZN_6 153.88 1948.61 01-JAN-00:10 7794.42 31-MAR-23:10
Electricity:Plant 6974.13 9556.75 25-JAN-05:50 505361.23 23-JUN-14:00
HeatRejection:Electricity 2294.23 6093.49 25-JAN-07:00 98044.59 02-JAN-09:20
General:HeatRejection:Electricity 2294.23 6093.49 25-JAN-07:00 98044.59 02-JAN-09:20
Electricity:HVAC 5694.55 75729.65 22-JAN-06:00 341570.16 31-AUG-15:20
ExteriorEquipment:Electricity 1934.78 28603.11 01-JAN-00:10 118535.44 27-SEP-07:20
Transformer:ExteriorEquipment:Electricity 80.17 1421.04 01-JAN-00:10 5057.48 15-DEC-16:50
ElectricityPurchased:Facility 33818.50 377399.06 22-JAN-05:00 1989371.34 23-AUG-15:10
ElectricityPurchased:Plant 33818.50 377399.06 22-JAN-05:00 1989371.34 23-AUG-15:10
Cogeneration:ElectricityPurchased 33818.50 377399.06 22-JAN-05:00 1989371.34 23-AUG-15:10
General:Cogeneration:ElectricityPurchased 33818.50 377399.06 22-JAN-05:00 1989371.34 23-AUG-15:10
ElectricitySurplusSold:Facility 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
ElectricitySurplusSold:Plant 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cogeneration:ElectricitySurplusSold 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Cogeneration:ElectricitySurplusSold 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
ElectricityNet:Facility 33818.50 377399.06 22-JAN-05:00 1989371.34 23-AUG-15:10
ElectricityNet:Plant 33818.50 377399.06 22-JAN-05:00 1989371.34 23-AUG-15:10
Cogeneration:ElectricityNet 33818.50 377399.06 22-JAN-05:00 1989371.34 23-AUG-15:10
General:Cogeneration:ElectricityNet 33818.50 377399.06 22-JAN-05:00 1989371.34 23-AUG-15:10
Fans:Electricity 2279.76 41718.95 01-JAN-00:10 148849.04 31-AUG-15:20
General:Fans:Electricity 2279.76 41718.95 01-JAN-00:10 148849.04 31-AUG-15:20
ExteriorLights:Electricity 696.56 0.00 01-JAN-07:20 57580.60 01-JAN-06:10
General:ExteriorLights:Electricity 696.56 0.00 01-JAN-07:20 57580.60 01-JAN-06:10
ElevatorLift:ExteriorEquipment:Electricity 1848.78 27144.47 01-JAN-00:10 113101.96 01-JAN-07:10
ElevatorLightsFan:ExteriorEquipment:Electricity 5.83 37.60 01-JAN-00:10 376.00 01-JAN-07:10
HeatRecovery:Electricity 119.08 0.00 01-JAN-00:10 5613.48 01-JAN-08:40
General:HeatRecovery:Electricity 119.08 0.00 01-JAN-00:10 5613.48 01-JAN-08:40
Cooling:Electricity 6915.41 32568.33 22-JAN-07:20 495044.09 15-AUG-12:10
General:Cooling:Electricity 6915.41 32568.33 22-JAN-07:20 495044.09 15-AUG-12:10
Heating:Electricity 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:Electricity 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Humidifier:Electricity 1.14 0.00 01-JAN-00:10 4077.20 04-FEB-06:00
General:Humidifier:Electricity 1.14 0.00 01-JAN-00:10 4077.20 04-FEB-06:00
Boiler Parasitic:Heating:Electricity 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Pumps:Electricity 978.88 3432.39 03-JAN-05:50 69624.76 13-OCT-15:50
General:Pumps:Electricity 978.88 3432.39 03-JAN-05:50 69624.76 13-OCT-15:50
WIRED_LTG_ELECTRICITY 110.21 0.00 01-JAN-00:10 10841.96 27-SEP-07:20
WIRED_INT_EQUIP 5334.97 88964.76 31-MAR-23:10 305206.10 03-APR-07:10


Annual and Peak Values - Natural Gas

Natural Gas Annual Value [GJ] Natural Gas Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Natural Gas Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
NaturalGas:Facility 660.92 8146.58 09-APR-16:00 413137.05 04-FEB-06:10
NaturalGas:Plant 660.92 8146.58 09-APR-16:00 413137.05 04-FEB-06:10
Heating:NaturalGas 20.08 0.00 01-JAN-00:10 404990.47 04-FEB-06:10
Boiler:Heating:NaturalGas 20.08 0.00 01-JAN-00:10 404990.47 04-FEB-06:10
WaterSystems:NaturalGas 640.83 8146.58 04-FEB-05:20 70632.11 23-JAN-12:50
Water Heater:WaterSystems:NaturalGas 640.83 8146.58 04-FEB-05:20 70632.11 23-JAN-12:50


Annual and Peak Values - Cooling

Cooling Annual Value [GJ] Cooling Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Cooling Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
PlantLoopCoolingDemand:Facility 37176.94 161675.26 25-JAN-05:50 2672256.70 23-AUG-15:00
PlantLoopCoolingDemand:HVAC 37176.94 161675.26 25-JAN-05:50 2672256.70 23-AUG-15:00
CoolingCoils:PlantLoopCoolingDemand 37176.94 161675.26 25-JAN-05:50 2672256.70 23-AUG-15:00


Annual and Peak Values - Water

Annual Value [m3] Minimum Value [m3/s] Timestamp of Minimum {TIMESTAMP} Maximum Value [m3/s] Timestamp of Maximum {TIMESTAMP}
Water:Facility 20812.18 0.00 01-JAN-00:10 0.00 17-APR-15:10
Water:HVAC 0.43 0.00 01-JAN-00:10 0.00 04-FEB-06:00
Humidifier:Water 0.43 0.00 01-JAN-00:10 0.00 04-FEB-06:00
General:Humidifier:Water 0.43 0.00 01-JAN-00:10 0.00 04-FEB-06:00
MainsWater:Facility 20812.18 0.00 01-JAN-00:10 0.00 17-APR-15:10
MainsWater:HVAC 0.43 0.00 01-JAN-00:10 0.00 04-FEB-06:00
Humidifier:MainsWater 0.43 0.00 01-JAN-00:10 0.00 04-FEB-06:00
General:Humidifier:MainsWater 0.43 0.00 01-JAN-00:10 0.00 04-FEB-06:00
Water:Plant 20811.76 0.00 01-JAN-00:10 0.00 17-APR-15:10
WaterSystems:Water 2280.17 0.00 01-JAN-00:10 0.00 02-JAN-12:10
WaterUse:WaterSystems:Water 2280.17 0.00 01-JAN-00:10 0.00 02-JAN-12:10
MainsWater:Plant 20811.76 0.00 01-JAN-00:10 0.00 17-APR-15:10
WaterSystems:MainsWater 2280.17 0.00 01-JAN-00:10 0.00 02-JAN-12:10
WaterUse:WaterSystems:MainsWater 2280.17 0.00 01-JAN-00:10 0.00 02-JAN-12:10
Water Heater:WaterSystems:Water 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Water Heater:WaterSystems:MainsWater 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
HeatRejection:Water 18531.59 0.00 01-JAN-00:10 0.00 17-APR-15:10
General:HeatRejection:Water 18531.59 0.00 01-JAN-00:10 0.00 17-APR-15:10
HeatRejection:MainsWater 18531.59 0.00 01-JAN-00:10 0.00 17-APR-15:10
General:HeatRejection:MainsWater 18531.59 0.00 01-JAN-00:10 0.00 17-APR-15:10


Annual and Peak Values - Other by Weight/Mass

Annual Value [kg] Minimum Value [kg/s] Timestamp of Minimum {TIMESTAMP} Maximum Value [kg/s] Timestamp of Maximum {TIMESTAMP}
Carbon Equivalent:Facility 0.00 0.000 01-JAN-00:10 0.000 01-JAN-00:10
CarbonEquivalentEmissions:Carbon Equivalent 0.00 0.000 01-JAN-00:10 0.000 01-JAN-00:10


Annual and Peak Values - Other Volumetric

Annual Value [m3] Minimum Value [m3/s] Timestamp of Minimum {TIMESTAMP} Maximum Value [m3/s] Timestamp of Maximum {TIMESTAMP}
None          


Annual and Peak Values - Other Liquid/Gas

Annual Value [L] Minimum Value [L] Timestamp of Minimum {TIMESTAMP} Maximum Value [L] Timestamp of Maximum {TIMESTAMP}
None          


Annual and Peak Values - Other

Annual Value [GJ] Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
EnergyTransfer:Facility 143507.63 227193.65 25-JAN-05:50 11209242.41 21-AUG-16:00
EnergyTransfer:Building 24287.63 97224.06 22-JAN-07:50 1729464.06 31-AUG-15:20
EnergyTransfer:Zone:BASEMENT 809.27 0.00 01-JAN-00:10 75552.34 13-NOV-06:10
Heating:EnergyTransfer 11.79 0.00 01-JAN-00:10 162421.63 04-FEB-06:10
Heating:EnergyTransfer:Zone:BASEMENT 4.32 0.00 01-JAN-00:10 23466.30 29-JUL-16:10
General:Heating:EnergyTransfer 11.79 0.00 01-JAN-00:10 162421.63 04-FEB-06:10
General:Heating:EnergyTransfer:Zone:BASEMENT 4.32 0.00 01-JAN-00:10 23466.30 29-JUL-16:10
Cooling:EnergyTransfer 24275.85 97216.92 22-JAN-07:40 1729464.06 31-AUG-15:20
Cooling:EnergyTransfer:Zone:BASEMENT 804.95 0.00 01-JAN-00:10 75552.34 13-NOV-06:10
General:Cooling:EnergyTransfer 24275.85 97216.92 22-JAN-07:40 1729464.06 31-AUG-15:20
General:Cooling:EnergyTransfer:Zone:BASEMENT 804.95 0.00 01-JAN-00:10 75552.34 13-NOV-06:10
EnergyTransfer:Zone:CORE_BOTTOM 845.71 0.00 01-JAN-00:10 57304.82 21-AUG-13:10
Heating:EnergyTransfer:Zone:CORE_BOTTOM 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:CORE_BOTTOM 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:CORE_BOTTOM 845.71 0.00 01-JAN-00:10 57304.82 21-AUG-13:10
General:Cooling:EnergyTransfer:Zone:CORE_BOTTOM 845.71 0.00 01-JAN-00:10 57304.82 21-AUG-13:10
EnergyTransfer:Zone:CORE_MID 6472.66 0.00 01-JAN-00:10 476391.97 20-OCT-05:10
Heating:EnergyTransfer:Zone:CORE_MID 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:CORE_MID 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:CORE_MID 6472.66 0.00 01-JAN-00:10 476391.97 20-OCT-05:10
General:Cooling:EnergyTransfer:Zone:CORE_MID 6472.66 0.00 01-JAN-00:10 476391.97 20-OCT-05:10
EnergyTransfer:Zone:CORE_TOP 667.39 0.00 01-JAN-00:10 55401.22 28-JUL-16:00
Heating:EnergyTransfer:Zone:CORE_TOP 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:CORE_TOP 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:CORE_TOP 667.39 0.00 01-JAN-00:10 55401.22 28-JUL-16:00
General:Cooling:EnergyTransfer:Zone:CORE_TOP 667.39 0.00 01-JAN-00:10 55401.22 28-JUL-16:00
EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 129.67 0.00 01-JAN-00:10 12188.48 31-JUL-14:00
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 129.67 0.00 01-JAN-00:10 12188.48 31-JUL-14:00
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 129.67 0.00 01-JAN-00:10 12188.48 31-JUL-14:00
EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 108.30 0.00 01-JAN-00:10 12326.60 25-JUL-09:30
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 0.00 0.00 01-JAN-00:10 134.02 04-FEB-06:10
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 0.00 0.00 01-JAN-00:10 134.02 04-FEB-06:10
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 108.30 0.00 01-JAN-00:10 12326.60 25-JUL-09:30
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 108.30 0.00 01-JAN-00:10 12326.60 25-JUL-09:30
EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 165.62 0.00 01-JAN-00:10 17330.15 04-DEC-14:30
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 165.62 0.00 01-JAN-00:10 17330.15 04-DEC-14:30
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 165.62 0.00 01-JAN-00:10 17330.15 04-DEC-14:30
EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 152.26 0.00 01-JAN-00:10 16774.12 16-AUG-16:00
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 152.26 0.00 01-JAN-00:10 16774.12 16-AUG-16:00
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 152.26 0.00 01-JAN-00:10 16774.12 16-AUG-16:00
EnergyTransfer:Zone:PERIMETER_MID_ZN_3 1036.00 0.00 01-JAN-00:10 116104.13 01-JUN-14:40
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 0.71 0.00 01-JAN-00:10 46537.28 04-FEB-06:00
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 0.71 0.00 01-JAN-00:10 46537.28 04-FEB-06:00
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 1035.29 0.00 01-JAN-00:10 116104.13 01-JUN-14:40
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 1035.29 0.00 01-JAN-00:10 116104.13 01-JUN-14:40
EnergyTransfer:Zone:PERIMETER_MID_ZN_2 967.32 0.00 01-JAN-00:10 124967.64 25-JUL-09:00
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 0.21 0.00 01-JAN-00:10 30882.06 04-FEB-06:00
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 0.21 0.00 01-JAN-00:10 30882.06 04-FEB-06:00
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 967.11 0.00 01-JAN-00:10 124967.64 25-JUL-09:00
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 967.11 0.00 01-JAN-00:10 124967.64 25-JUL-09:00
EnergyTransfer:Zone:PERIMETER_MID_ZN_1 1428.49 0.00 01-JAN-00:10 170565.24 03-DEC-14:00
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 0.09 0.00 01-JAN-00:10 31658.30 04-FEB-06:10
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 0.09 0.00 01-JAN-00:10 31658.30 04-FEB-06:10
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 1428.40 0.00 01-JAN-00:10 170565.24 03-DEC-14:00
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 1428.40 0.00 01-JAN-00:10 170565.24 03-DEC-14:00
EnergyTransfer:Zone:PERIMETER_MID_ZN_4 1019.47 0.00 01-JAN-00:10 142020.25 17-MAY-16:00
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 0.15 0.00 01-JAN-00:10 24940.18 04-FEB-06:10
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 0.15 0.00 01-JAN-00:10 24940.18 04-FEB-06:10
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 1019.33 0.00 01-JAN-00:10 142020.25 17-MAY-16:00
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 1019.33 0.00 01-JAN-00:10 142020.25 17-MAY-16:00
EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 107.27 0.00 01-JAN-00:10 12683.56 27-JUL-16:00
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 0.44 0.00 01-JAN-00:10 10578.14 04-FEB-05:20
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 0.44 0.00 01-JAN-00:10 10578.14 04-FEB-05:20
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 106.82 0.00 01-JAN-00:10 12683.56 27-JUL-16:00
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 106.82 0.00 01-JAN-00:10 12683.56 27-JUL-16:00
EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 99.58 0.00 01-JAN-00:10 13192.77 25-JUL-09:30
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 0.16 0.00 01-JAN-00:10 6659.04 04-FEB-05:20
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 0.16 0.00 01-JAN-00:10 6659.04 04-FEB-05:20
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 99.42 0.00 01-JAN-00:10 13192.77 25-JUL-09:30
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 99.42 0.00 01-JAN-00:10 13192.77 25-JUL-09:30
EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 145.24 0.00 01-JAN-00:10 18314.98 07-NOV-14:20
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 0.11 0.00 01-JAN-00:10 7278.96 04-FEB-05:20
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 0.11 0.00 01-JAN-00:10 7278.96 04-FEB-05:20
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 145.13 0.00 01-JAN-00:10 18314.98 07-NOV-14:20
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 145.13 0.00 01-JAN-00:10 18314.98 07-NOV-14:20
EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 104.84 0.00 01-JAN-00:10 14943.29 17-MAY-16:00
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 0.12 0.00 01-JAN-00:10 5437.33 04-FEB-05:20
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 0.12 0.00 01-JAN-00:10 5437.33 04-FEB-05:20
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 104.72 0.00 01-JAN-00:10 14943.29 17-MAY-16:00
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 104.72 0.00 01-JAN-00:10 14943.29 17-MAY-16:00
EnergyTransfer:Zone:GROUNDFLOOR_PLENUM 119.93 0.00 01-JAN-00:10 11642.51 21-AUG-16:00
Heating:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM 0.50 0.00 01-JAN-00:10 3452.37 05-FEB-11:20
General:Heating:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM 0.50 0.00 01-JAN-00:10 3452.37 05-FEB-11:20
Cooling:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM 119.44 0.00 01-JAN-00:10 11642.51 21-AUG-16:00
General:Cooling:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM 119.44 0.00 01-JAN-00:10 11642.51 21-AUG-16:00
EnergyTransfer:Zone:MIDFLOOR_PLENUM 935.49 0.00 01-JAN-00:10 90492.44 28-JUL-16:00
Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM 2.93 0.00 01-JAN-00:10 21469.67 05-FEB-12:30
General:Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM 2.93 0.00 01-JAN-00:10 21469.67 05-FEB-12:30
Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM 932.56 0.00 01-JAN-00:10 90492.44 28-JUL-16:00
General:Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM 932.56 0.00 01-JAN-00:10 90492.44 28-JUL-16:00
EnergyTransfer:Zone:TOPFLOOR_PLENUM 144.41 0.00 01-JAN-00:10 23127.28 28-JUL-15:30
Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM 2.05 0.00 01-JAN-00:10 8454.16 04-FEB-06:10
General:Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM 2.05 0.00 01-JAN-00:10 8454.16 04-FEB-06:10
Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM 142.36 0.00 01-JAN-00:10 23127.28 28-JUL-15:30
General:Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM 142.36 0.00 01-JAN-00:10 23127.28 28-JUL-15:30
EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 144.58 1119.13 26-JAN-08:00 8056.14 06-DEC-17:00
Heating:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 144.58 1119.13 26-JAN-08:00 8056.14 06-DEC-17:00
General:Cooling:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 144.58 1119.13 26-JAN-08:00 8056.14 06-DEC-17:00
EnergyTransfer:Zone:DATACENTER_MID_ZN_6 1345.62 6409.66 26-JAN-08:00 76397.96 06-DEC-17:00
Heating:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 1345.62 6409.66 26-JAN-08:00 76397.96 06-DEC-17:00
General:Cooling:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 1345.62 6409.66 26-JAN-08:00 76397.96 06-DEC-17:00
EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 133.35 1.57 22-JAN-08:00 7704.53 06-DEC-17:00
Heating:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 0.00 0.00 01-JAN-00:10 192.10 22-JAN-08:30
General:Heating:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 0.00 0.00 01-JAN-00:10 192.10 22-JAN-08:30
Cooling:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 133.35 0.00 22-JAN-07:20 7704.53 06-DEC-17:00
General:Cooling:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 133.35 0.00 22-JAN-07:20 7704.53 06-DEC-17:00
EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 7205.17 88941.98 22-JAN-06:00 370406.01 28-AUG-12:20
Heating:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 7205.17 88941.98 22-JAN-06:00 370406.01 28-AUG-12:20
General:Cooling:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 7205.17 88941.98 22-JAN-06:00 370406.01 28-AUG-12:20
PlantLoopHeatingDemand:Facility 310.56 0.00 01-JAN-00:10 322467.67 04-FEB-06:10
PlantLoopHeatingDemand:Plant 296.73 0.00 01-JAN-00:10 36110.59 19-JAN-12:50
WaterSystems:PlantLoopHeatingDemand 296.73 0.00 01-JAN-00:10 36110.59 19-JAN-12:50
General:WaterSystems:PlantLoopHeatingDemand 296.73 0.00 01-JAN-00:10 36110.59 19-JAN-12:50
EnergyTransfer:HVAC 39907.95 128842.77 25-JAN-05:50 3254044.58 21-AUG-16:00
HeatingCoils:EnergyTransfer 13.83 0.00 01-JAN-00:10 318052.85 04-FEB-06:10
PlantLoopHeatingDemand:HVAC 13.83 0.00 01-JAN-00:10 318052.85 04-FEB-06:10
HeatingCoils:PlantLoopHeatingDemand 13.83 0.00 01-JAN-00:10 318052.85 04-FEB-06:10
CoolingCoils:EnergyTransfer 33962.54 128842.77 25-JAN-05:50 2491041.83 23-AUG-15:00
HeatRecoveryForHeating:EnergyTransfer 13.48 0.00 01-JAN-00:10 237161.82 04-FEB-07:00
HeatRecoveryForCooling:EnergyTransfer 5918.09 0.00 01-JAN-00:10 767781.45 21-AUG-16:00
EnergyTransfer:Plant 79312.05 0.00 01-JAN-00:10 7202518.97 23-JUN-14:00
LoopToLoop:EnergyTransfer 25215.79 0.00 01-JAN-00:10 2220868.97 22-JUN-05:10
WaterSystems:EnergyTransfer 296.73 0.00 01-JAN-00:10 36110.59 19-JAN-12:50
WaterUse:WaterSystems:EnergyTransfer 296.73 0.00 01-JAN-00:10 36110.59 19-JAN-12:50
Boilers:EnergyTransfer 13.51 0.00 01-JAN-00:10 325809.07 04-FEB-06:10
Chillers:EnergyTransfer 25042.50 0.00 01-JAN-00:10 2358594.86 23-JUN-14:00
HeatRejection:EnergyTransfer 28743.51 0.00 01-JAN-00:10 2700062.89 23-JUN-14:00
General:HeatRejection:EnergyTransfer 28743.51 0.00 01-JAN-00:10 2700062.89 23-JUN-14:00
Water Heater:WaterSystems:PlantLoopHeatingDemand 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10



Table of Contents

Report: Sensible Heat Gain Summary

For: Entire Facility

Timestamp: 2023-10-16 08:43:45

Annual Building Sensible Heat Gain Components

HVAC Zone Eq & Other Sensible Air Heating [GJ] HVAC Zone Eq & Other Sensible Air Cooling [GJ] HVAC Terminal Unit Sensible Air Heating [GJ] HVAC Terminal Unit Sensible Air Cooling [GJ] HVAC Input Heated Surface Heating [GJ] HVAC Input Cooled Surface Cooling [GJ] People Sensible Heat Addition [GJ] Lights Sensible Heat Addition [GJ] Equipment Sensible Heat Addition [GJ] Window Heat Addition [GJ] Interzone Air Transfer Heat Addition [GJ] Infiltration Heat Addition [GJ] Opaque Surface Conduction and Other Heat Addition [GJ] Equipment Sensible Heat Removal [GJ] Window Heat Removal [GJ] Interzone Air Transfer Heat Removal [GJ] Infiltration Heat Removal [GJ] Opaque Surface Conduction and Other Heat Removal [GJ]
BASEMENT 0.000 0.000 4.316 -804.952 0.000 0.000 92.650 262.844 424.397 0.000 0.000 0.000 20.744 0.000 0.000 0.000 0.000 -0.008
CORE_BOTTOM 0.000 0.000 0.000 -845.710 0.000 0.000 83.500 236.053 289.614 0.000 0.000 0.000 236.543 0.000 0.000 0.000 0.000 -0.001
CORE_MID 0.000 0.000 0.000 -6472.643 0.000 0.000 838.254 2360.527 2896.128 0.000 0.000 0.000 377.734 0.000 0.000 0.000 0.000 -0.013
CORE_TOP 0.000 0.000 0.000 -667.383 0.000 0.000 84.278 236.053 289.613 0.000 0.000 0.000 57.440 0.000 0.000 0.000 0.000 -0.002
PERIMETER_BOT_ZN_3 0.000 0.000 0.000 -129.665 0.000 0.000 10.516 17.208 36.365 47.833 0.000 0.657 38.412 0.000 -20.304 0.000 -1.022 0.000
PERIMETER_BOT_ZN_2 0.000 0.000 0.000 -108.300 0.000 0.000 6.777 11.025 23.435 64.864 0.000 0.471 14.491 0.000 -12.117 0.000 -0.647 -0.000
PERIMETER_BOT_ZN_1 0.000 0.000 0.000 -165.618 0.000 0.000 10.448 16.956 36.366 100.012 0.000 0.613 22.980 0.000 -20.598 0.000 -1.159 -0.000
PERIMETER_BOT_ZN_4 0.000 0.000 0.000 -152.260 0.000 0.000 6.757 11.007 23.435 60.627 0.000 0.390 68.112 0.000 -17.178 0.000 -0.891 0.000
PERIMETER_MID_ZN_3 0.000 0.000 0.713 -1035.257 0.000 0.000 106.438 171.634 363.654 488.869 0.000 14.553 92.768 0.000 -182.018 0.000 -21.354 -0.000
PERIMETER_MID_ZN_2 0.000 0.000 0.209 -967.086 0.000 0.000 50.094 110.065 234.352 643.417 0.000 9.561 53.981 0.000 -119.122 0.000 -15.470 -0.009
PERIMETER_MID_ZN_1 0.000 0.000 0.094 -1428.363 0.000 0.000 104.553 169.315 363.660 995.559 0.000 13.197 10.868 0.000 -201.374 0.000 -27.508 -0.004
PERIMETER_MID_ZN_4 0.000 0.000 0.148 -1019.296 0.000 0.000 68.678 109.838 234.351 622.053 0.000 9.124 133.358 0.000 -140.875 0.000 -17.379 -0.009
PERIMETER_TOP_ZN_3 0.000 0.000 0.442 -106.821 0.000 0.000 10.703 17.162 36.365 48.340 0.000 1.700 12.166 0.000 -17.544 0.000 -2.513 -0.000
PERIMETER_TOP_ZN_2 0.000 0.000 0.161 -99.414 0.000 0.000 6.833 11.006 23.435 63.870 0.000 1.120 6.396 0.000 -11.570 0.000 -1.839 -0.001
PERIMETER_TOP_ZN_1 0.000 0.000 0.114 -145.126 0.000 0.000 10.511 16.931 36.366 98.872 0.000 1.552 3.600 0.000 -19.541 0.000 -3.278 -0.002
PERIMETER_TOP_ZN_4 0.000 0.000 0.118 -104.715 0.000 0.000 6.914 10.983 23.435 61.832 0.000 1.104 15.999 0.000 -13.606 0.000 -2.065 -0.001
DATACENTER_BOT_ZN_6 0.000 0.000 0.000 -144.583 0.000 0.000 0.949 6.628 153.881 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 -16.875
DATACENTER_MID_ZN_6 0.000 0.000 0.000 -1345.617 0.000 0.000 9.495 66.280 1538.806 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 -268.963
DATACENTER_TOP_ZN_6 0.000 0.000 0.001 -133.347 0.000 0.000 0.950 6.628 153.881 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 -28.113
DATACENTER_BASEMENT_ZN_6 0.000 0.000 0.000 -7205.173 0.000 0.000 20.033 74.111 7494.857 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 -383.828
GROUNDFLOOR_PLENUM 0.497 -119.436 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 1.033 120.361 0.000 0.000 0.000 -2.455 -0.000
MIDFLOOR_PLENUM 2.926 -932.545 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 19.048 951.416 0.000 0.000 0.000 -40.846 -0.000
TOPFLOOR_PLENUM 2.047 -142.362 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 1.656 142.907 0.000 0.000 0.000 -4.248 -0.000
Total Facility 5.470 -1194.343 6.316 -23081.327 0.000 0.000 1529.332 3922.253 14676.396 3296.147 0.000 75.779 2380.274 0.000 -775.847 0.000 -142.673 -697.829


Peak Cooling Sensible Heat Gain Components

Time of Peak {TIMESTAMP} HVAC Zone Eq & Other Sensible Air Heating [W] HVAC Zone Eq & Other Sensible Air Cooling [W] HVAC Terminal Unit Sensible Air Heating [W] HVAC Terminal Unit Sensible Air Cooling [W] HVAC Input Heated Surface Heating [W] HVAC Input Cooled Surface Cooling [W] People Sensible Heat Addition [W] Lights Sensible Heat Addition [W] Equipment Sensible Heat Addition [W] Window Heat Addition [W] Interzone Air Transfer Heat Addition [W] Infiltration Heat Addition [W] Opaque Surface Conduction and Other Heat Addition [W] Equipment Sensible Heat Removal [W] Window Heat Removal [W] Interzone Air Transfer Heat Removal [W] Infiltration Heat Removal [W] Opaque Surface Conduction and Other Heat Removal [W]
BASEMENT 04-FEB-05:11 0.00 0.00 0.00 -109159.08 0.00 0.00 0.00 1274.92 13457.54 0.00 0.00 0.00 94426.61 0.00 -0.00 0.00 0.00 0.00
CORE_BOTTOM 21-FEB-05:13 0.00 0.00 0.00 -103174.29 0.00 0.00 0.00 2290.20 5937.65 0.00 0.00 0.00 94946.45 0.00 -0.00 0.00 0.00 0.00
CORE_MID 20-OCT-04:13 0.00 0.00 0.00 -914658.93 0.00 0.00 0.00 22901.98 59376.23 0.00 0.00 0.00 832380.72 0.00 -0.00 0.00 0.00 0.00
CORE_TOP 18-APR-04:12 0.00 0.00 0.00 -88082.82 0.00 0.00 0.00 2290.20 5937.62 0.00 0.00 0.00 79855.00 0.00 -0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_3 30-JUL-14:22 0.00 0.00 0.00 -19309.27 0.00 0.00 40.66 68.40 720.18 6263.67 0.00 156.24 12060.11 0.00 -0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_2 11-JUN-09:32 0.00 0.00 0.00 -20582.51 0.00 0.00 22.63 44.08 464.11 11865.42 0.00 37.20 8149.07 0.00 -0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_1 03-DEC-14:01 0.00 0.00 0.00 -22591.84 0.00 0.00 30.76 68.40 720.19 19863.39 0.00 0.00 2004.45 0.00 -0.00 0.00 -95.36 0.00
PERIMETER_BOT_ZN_4 03-DEC-15:21 0.00 0.00 0.00 -27150.88 0.00 0.00 21.06 44.08 464.11 11056.38 0.00 0.00 15613.11 0.00 -0.00 0.00 -47.87 0.00
PERIMETER_MID_ZN_3 29-MAY-15:41 0.00 0.00 0.00 -188565.13 0.00 0.00 405.73 684.02 7201.84 53695.78 0.00 7293.64 119284.13 0.00 -0.00 0.00 0.00 0.00
PERIMETER_MID_ZN_2 04-JUL-08:32 0.00 0.00 0.00 -217098.81 0.00 0.00 218.30 440.81 4641.14 137690.31 0.00 116.08 73992.17 0.00 -0.00 0.00 0.00 0.00
PERIMETER_MID_ZN_1 03-DEC-13:51 0.00 0.00 0.00 -220202.20 0.00 0.00 295.55 684.04 7201.95 201111.60 0.00 0.00 13312.03 0.00 -0.00 0.00 -2402.96 0.00
PERIMETER_MID_ZN_4 29-MAY-15:41 0.00 0.00 0.00 -247249.81 0.00 0.00 199.10 440.81 4641.11 133716.32 0.00 3651.06 104601.41 0.00 -0.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_3 29-MAY-15:41 0.00 0.00 0.00 -21491.35 0.00 0.00 38.43 68.40 720.18 5172.18 0.00 827.73 14664.43 0.00 -0.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_2 04-JUL-08:32 0.00 0.00 0.00 -21986.84 0.00 0.00 21.82 44.08 464.11 13706.36 0.00 12.04 7738.42 0.00 -0.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_1 10-DEC-15:01 0.00 0.00 0.00 -23691.38 0.00 0.00 31.64 68.40 720.19 14542.83 0.00 0.00 8427.50 0.00 -0.00 0.00 -99.19 0.00
PERIMETER_TOP_ZN_4 29-MAY-15:41 0.00 0.00 0.00 -26764.58 0.00 0.00 18.68 44.08 464.11 13198.31 0.00 412.54 12626.85 0.00 -0.00 0.00 0.00 0.00
DATACENTER_BOT_ZN_6 06-DEC-17:00 0.00 0.00 0.00 -8055.98 0.00 0.00 100.85 578.72 7794.42 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 0.00 -418.01
DATACENTER_MID_ZN_6 06-DEC-17:00 0.00 0.00 0.00 -76396.33 0.00 0.00 1008.49 5787.18 77944.22 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 0.00 -8343.57
DATACENTER_TOP_ZN_6 06-DEC-17:00 0.00 0.00 0.00 -7704.37 0.00 0.00 100.85 578.72 7794.42 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 0.00 -769.62
DATACENTER_BASEMENT_ZN_6 28-AUG-12:20 0.00 0.00 0.00 -370407.54 0.00 0.00 2173.86 6471.01 379632.52 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 0.00 -17869.85
GROUNDFLOOR_PLENUM 18-SEP-05:02 0.00 -14309.62 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 18.38 14291.24 0.00 -0.00 0.00 0.00 0.00
MIDFLOOR_PLENUM 06-JUL-05:02 0.00 -104650.07 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 104805.49 0.00 -0.00 0.00 -155.42 0.00
TOPFLOOR_PLENUM 28-JUL-15:30 0.00 -23126.83 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 162.35 22964.48 0.00 -0.00 0.00 0.00 0.00
Total Facility 01-DEC-05:11 0.00 61165.12 0.00 -2133141.31 0.00 0.00 0.00 42872.09 587299.42 0.00 0.00 0.00 1481618.45 0.00 -39813.77 0.00 0.00 0.00


Peak Heating Sensible Heat Gain Components

Time of Peak {TIMESTAMP} HVAC Zone Eq & Other Sensible Air Heating [W] HVAC Zone Eq & Other Sensible Air Cooling [W] HVAC Terminal Unit Sensible Air Heating [W] HVAC Terminal Unit Sensible Air Cooling [W] HVAC Input Heated Surface Heating [W] HVAC Input Cooled Surface Cooling [W] People Sensible Heat Addition [W] Lights Sensible Heat Addition [W] Equipment Sensible Heat Addition [W] Window Heat Addition [W] Interzone Air Transfer Heat Addition [W] Infiltration Heat Addition [W] Opaque Surface Conduction and Other Heat Addition [W] Equipment Sensible Heat Removal [W] Window Heat Removal [W] Interzone Air Transfer Heat Removal [W] Infiltration Heat Removal [W] Opaque Surface Conduction and Other Heat Removal [W]
BASEMENT 29-JUL-16:01 0.00 0.00 25124.34 0.00 0.00 0.00 520.12 1274.92 13457.54 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 0.00 -40376.93
CORE_BOTTOM - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CORE_MID - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CORE_TOP - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_3 - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_2 04-FEB-06:02 0.00 0.00 670.09 0.00 0.00 0.00 90.18 185.31 618.82 0.00 0.00 0.00 2055.72 0.00 -3498.57 0.00 -121.56 0.00
PERIMETER_BOT_ZN_1 - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_4 - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_MID_ZN_3 04-FEB-05:11 0.00 0.00 127902.97 0.00 0.00 0.00 0.00 1437.63 5591.71 0.00 0.00 0.00 0.00 0.00 -48244.43 0.00 -15958.67 -70729.21
PERIMETER_MID_ZN_2 04-FEB-05:11 0.00 0.00 94682.91 0.00 0.00 0.00 0.00 926.46 3603.51 0.00 0.00 0.00 0.00 0.00 -31547.99 0.00 -10793.89 -56871.00
PERIMETER_MID_ZN_1 04-FEB-06:02 0.00 0.00 118493.22 0.00 0.00 0.00 1460.98 2875.64 9602.60 0.00 0.00 0.00 0.00 0.00 -50644.38 0.00 -4219.26 -77568.79
PERIMETER_MID_ZN_4 04-FEB-05:11 0.00 0.00 85003.69 0.00 0.00 0.00 0.00 926.46 3603.49 0.00 0.00 0.00 0.00 0.00 -33425.30 0.00 -11088.53 -45019.81
PERIMETER_TOP_ZN_3 04-FEB-05:11 0.00 0.00 15960.60 0.00 0.00 0.00 0.00 143.76 559.17 0.00 0.00 0.00 0.00 0.00 -4300.30 0.00 -1756.38 -10606.86
PERIMETER_TOP_ZN_2 04-FEB-05:11 0.00 0.00 12305.61 0.00 0.00 0.00 0.00 92.65 360.35 0.00 0.00 0.00 0.00 0.00 -2823.52 0.00 -1195.36 -8739.73
PERIMETER_TOP_ZN_1 04-FEB-05:11 0.00 0.00 15247.51 0.00 0.00 0.00 0.00 143.77 559.18 0.00 0.00 0.00 0.00 0.00 -4497.55 0.00 -1901.26 -9551.65
PERIMETER_TOP_ZN_4 04-FEB-05:11 0.00 0.00 11831.77 0.00 0.00 0.00 0.00 92.65 360.35 0.00 0.00 0.00 0.00 0.00 -3030.93 0.00 -1250.32 -8003.52
DATACENTER_BOT_ZN_6 - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
DATACENTER_MID_ZN_6 - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
DATACENTER_TOP_ZN_6 22-JAN-08:30 0.00 0.00 192.10 0.00 0.00 0.00 5.27 32.15 1948.61 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 0.00 -2178.13
DATACENTER_BASEMENT_ZN_6 - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
GROUNDFLOOR_PLENUM 18-DEC-05:12 14389.07 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 -270.78 -14118.28
MIDFLOOR_PLENUM 13-NOV-05:12 80913.52 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 -18819.58 -62093.94
TOPFLOOR_PLENUM 28-FEB-06:03 14242.62 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 0.00 -14242.62
Total Facility 04-FEB-06:02 -710888.77 662518.78 455838.38 -662518.78 0.00 0.00 19092.75 42872.09 379706.36 0.00 0.00 0.00 40413.13 0.00 -202208.74 0.00 -24825.20 0.00



Table of Contents

Report: Standard 62.1 Summary

For: Entire Facility

Timestamp: 2023-10-16 08:43:45

System Ventilation Requirements for Cooling

Sum of Zone Primary Air Flow - Vpz-sum [m3/s] System Population - Ps Sum of Zone Population - Pz-sum Occupant Diversity - D Origin of D Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] System Primary Airflow - Vps [m3/s] Average Outdoor Air Fraction - Xs System Ventilation Efficiency - Ev Calculation Method for Ev Outdoor Air Intake Flow - Vot [m3/s] Percent Outdoor Air - %OA Environment Name of Peak System Population - Ps Date and Time of Last Peak System Population - Ps
VAV_BOT WITH REHEAT 11.0426 0.0000 0.0000 1.0000 Calculated from schedules 0.0000 10.1385 0.0000 1.0000 Not calculated 0.0000 0.0000    
VAV_MID WITH REHEAT 104.7677 0.0000 0.0000 1.0000 Calculated from schedules 0.0000 95.0764 0.0000 1.0000 Not calculated 0.0000 0.0000    
VAV_TOP WITH REHEAT 10.7077 0.0000 0.0000 1.0000 Calculated from schedules 0.0000 10.2938 0.0000 1.0000 Not calculated 0.0000 0.0000    
CAV_BAS 6.0855 0.0000 149.6021 1.0000 Calculated from schedules 1.2002 6.0855 0.1972 1.0000 Not calculated 1.2002 0.1972    
AIRLOOP DATACENTER BASEMENT 21.4296 0.0000 42.1814 1.0000 Calculated from schedules 0.3384 21.4298 0.0158 1.0000 Not calculated 0.3384 0.0158    
AIRLOOP DATACENTER BOT 0.4801 0.0000 1.9486 1.0000 Calculated from schedules 0.0156 0.4801 0.0326 1.0000 Not calculated 0.0156 0.0326    
AIRLOOP DATACENTER MID 4.5783 0.0000 19.4861 1.0000 Calculated from schedules 0.1563 4.5783 0.0341 1.0000 Not calculated 0.1563 0.0341    
AIRLOOP DATACENTER TOP 0.4669 0.0000 1.9486 1.0000 Calculated from schedules 0.0156 0.4669 0.0335 1.0000 Not calculated 0.0156 0.0335    


System Ventilation Requirements for Heating

Sum of Zone Primary Air Flow - Vpz-sum [m3/s] System Population - Ps Sum of Zone Population - Pz-sum Occupant Diversity - D Origin of D Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] System Primary Airflow - Vps [m3/s] Average Outdoor Air Fraction - Xs System Ventilation Efficiency - Ev Calculation Method for Ev Outdoor Air Intake Flow Vot [m3/s] Percent Outdoor Air - %OA Environment Name of Peak System Population - Ps Date and Time of Last Peak System Population - Ps
VAV_BOT WITH REHEAT 5.5213 0.0000 0.0000 1.0000 Calculated from schedules 0.0000 2.9619 0.0000 1.0000 Not calculated 0.0000 0.0000    
VAV_MID WITH REHEAT 52.3838 0.0000 0.0000 1.0000 Calculated from schedules 0.0000 28.9100 0.0000 1.0000 Not calculated 0.0000 0.0000    
VAV_TOP WITH REHEAT 5.3538 0.0000 0.0000 1.0000 Calculated from schedules 0.0000 2.9633 0.0000 1.0000 Not calculated 0.0000 0.0000    
CAV_BAS 6.0855 0.0000 149.6021 1.0000 Calculated from schedules 1.2002 6.0855 1.0000 1.0000 Not calculated 1.2002 0.1972    
AIRLOOP DATACENTER BASEMENT 21.4296 0.0000 42.1814 1.0000 Calculated from schedules 0.3384 21.4296 1.0000 1.0000 Not calculated 0.3384 0.0158    
AIRLOOP DATACENTER BOT 0.4801 0.0000 1.9486 1.0000 Calculated from schedules 0.0156 0.4801 1.0000 1.0000 Not calculated 0.0156 0.0326    
AIRLOOP DATACENTER MID 4.5783 0.0000 19.4861 1.0000 Calculated from schedules 0.1563 4.5783 1.0000 1.0000 Not calculated 0.1563 0.0341    
AIRLOOP DATACENTER TOP 0.4669 0.0000 1.9486 1.0000 Calculated from schedules 0.0156 0.4669 1.0000 1.0000 Not calculated 0.0156 0.0335    


Zone Ventilation Parameters

AirLoop Name People Outdoor Air Rate - Rp [m3/s-person] Zone Population - Pz Area Outdoor Air Rate - Ra [m3/s-m2] Zone Floor Area - Az [m2] Breathing Zone Outdoor Airflow - Vbz [m3/s] Cooling Zone Air Distribution Effectiveness - Ez-clg Cooling Zone Outdoor Airflow - Voz-clg [m3/s] Heating Zone Air Distribution Effectiveness - Ez-htg Heating Zone Outdoor Airflow - Voz-htg [m3/s]
BASEMENT CAV_BAS 0.000000 149.6021 0.000432 2779.43 1.2002 1.0000 1.2002 1.000 1.2002
CORE_BOTTOM VAV_BOT WITH REHEAT 0.000000 134.3532 0.000432 2496.12 0.0000 1.0000 0.0000 1.000 0.0000
CORE_MID VAV_MID WITH REHEAT 0.000000 1343.5320 0.000432 24961.20 0.0000 1.0000 0.0000 1.000 0.0000
CORE_TOP VAV_TOP WITH REHEAT 0.000000 134.3532 0.000432 2496.12 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_BOT_ZN_3 VAV_BOT WITH REHEAT 0.000000 16.8694 0.000432 313.41 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_BOT_ZN_2 VAV_BOT WITH REHEAT 0.000000 10.8713 0.000432 201.98 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_BOT_ZN_1 VAV_BOT WITH REHEAT 0.000000 16.8698 0.000432 313.42 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_BOT_ZN_4 VAV_BOT WITH REHEAT 0.000000 10.8713 0.000432 201.98 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_MID_ZN_3 VAV_MID WITH REHEAT 0.000000 168.6939 0.000432 3134.13 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_MID_ZN_2 VAV_MID WITH REHEAT 0.000000 108.7127 0.000432 2019.75 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_MID_ZN_1 VAV_MID WITH REHEAT 0.000000 168.6975 0.000432 3134.20 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_MID_ZN_4 VAV_MID WITH REHEAT 0.000000 108.7127 0.000432 2019.75 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_TOP_ZN_3 VAV_TOP WITH REHEAT 0.000000 16.8694 0.000432 313.41 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_TOP_ZN_2 VAV_TOP WITH REHEAT 0.000000 10.8713 0.000432 201.98 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_TOP_ZN_1 VAV_TOP WITH REHEAT 0.000000 16.8698 0.000432 313.42 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_TOP_ZN_4 VAV_TOP WITH REHEAT 0.000000 10.8713 0.000432 201.98 0.0000 1.0000 0.0000 1.000 0.0000
DATACENTER_BOT_ZN_6 AIRLOOP DATACENTER BOT 0.000000 1.9486 0.000432 36.20 0.0156 1.0000 0.0156 1.000 0.0156
DATACENTER_MID_ZN_6 AIRLOOP DATACENTER MID 0.000000 19.4861 0.000432 362.03 0.1563 1.0000 0.1563 1.000 0.1563
DATACENTER_TOP_ZN_6 AIRLOOP DATACENTER TOP 0.000000 1.9486 0.000432 36.20 0.0156 1.0000 0.0156 1.000 0.0156
DATACENTER_BASEMENT_ZN_6 AIRLOOP DATACENTER BASEMENT 0.000000 42.1814 0.000432 783.68 0.3384 1.0000 0.3384 1.000 0.3384


System Ventilation Parameters

People Outdoor Air Rate - Rp [m3/s-person] Sum of Zone Population - Pz-sum Area Outdoor Air Rate - Ra [m3/s-m2] Sum of Zone Floor Area - Az-sum [m2] Breathing Zone Outdoor Airflow - Vbz [m3/s] Cooling Zone Outdoor Airflow - Voz-clg [m3/s] Heating Zone Outdoor Airflow - Voz-htg [m3/s]
VAV_BOT WITH REHEAT   0.00 0.000432 3526.9033 0.0000 0.0000 0.0000
VAV_MID WITH REHEAT   0.00 0.000432 35269.0328 0.0000 0.0000 0.0000
VAV_TOP WITH REHEAT   0.00 0.000432 3526.9033 0.0000 0.0000 0.0000
CAV_BAS 0.000000 149.60 0.000432 2779.4266 1.2002 1.2002 1.2002
AIRLOOP DATACENTER BASEMENT 0.000000 42.18 0.000432 783.6794 0.3384 0.3384 0.3384
AIRLOOP DATACENTER BOT 0.000000 1.95 0.000432 36.2027 0.0156 0.0156 0.0156
AIRLOOP DATACENTER MID 0.000000 19.49 0.000432 362.0274 0.1563 0.1563 0.1563
AIRLOOP DATACENTER TOP 0.000000 1.95 0.000432 36.2027 0.0156 0.0156 0.0156


Zone Ventilation Calculations for Cooling Design

AirLoop Name Box Type Zone Primary Airflow - Vpz [m3/s] Zone Discharge Airflow - Vdz [m3/s] Minimum Zone Primary Airflow - Vpz-min [m3/s] Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? Zone Outdoor Airflow Cooling - Voz-clg [m3/s] Primary Outdoor Air Fraction - Zpz Primary Air Fraction - Ep Secondary Recirculation Fraction- Er Supply Air Fraction- Fa Mixed Air Fraction - Fb Outdoor Air Fraction - Fc Zone Ventilation Efficiency - Evz
BASEMENT CAV_BAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 6.0855 6.0855 6.0855 No 1.2002 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CORE_BOTTOM VAV_BOT WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 6.2822 6.2822 1.9600 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CORE_MID VAV_MID WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 59.3870 59.3870 19.2414 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CORE_TOP VAV_TOP WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 5.8348 5.8348 1.9663 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_BOT_ZN_3 VAV_BOT WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.1082 1.1082 0.2460 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_BOT_ZN_2 VAV_BOT WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.1100 1.1100 0.2220 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_BOT_ZN_1 VAV_BOT WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.1050 1.1050 0.2464 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_BOT_ZN_4 VAV_BOT WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.4371 1.4371 0.2874 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_MID_ZN_3 VAV_MID WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 10.6266 10.6266 2.4122 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_MID_ZN_2 VAV_MID WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 11.4819 11.4819 2.2964 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_MID_ZN_1 VAV_MID WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 10.5372 10.5372 2.4130 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_MID_ZN_4 VAV_MID WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 12.7350 12.7350 2.5470 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_TOP_ZN_3 VAV_TOP WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.1783 1.1783 0.2474 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_TOP_ZN_2 VAV_TOP WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.1629 1.1629 0.2326 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_TOP_ZN_1 VAV_TOP WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.1791 1.1791 0.2464 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_TOP_ZN_4 VAV_TOP WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.3525 1.3525 0.2705 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
DATACENTER_BOT_ZN_6 AIRLOOP DATACENTER BOT AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.4801 0.4801 0.4801 No 0.0156 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
DATACENTER_MID_ZN_6 AIRLOOP DATACENTER MID AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 4.5783 4.5783 4.5783 No 0.1563 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
DATACENTER_TOP_ZN_6 AIRLOOP DATACENTER TOP AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.4669 0.4669 0.4669 No 0.0156 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
DATACENTER_BASEMENT_ZN_6 AIRLOOP DATACENTER BASEMENT AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 21.4296 21.4296 21.4296 No 0.3384 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000


System Ventilation Calculations for Cooling Design

Sum of Zone Primary Airflow - Vpz-sum [m3/s] System Primary Airflow - Vps [m3/s] Sum of Zone Discharge Airflow - Vdz-sum [m3/s] Sum of Min Zone Primary Airflow - Vpz-min [m3/s] Zone Outdoor Airflow Cooling - Voz-clg [m3/s] Zone Ventilation Efficiency - Evz-min
VAV_BOT WITH REHEAT 11.0426 10.1385 11.0426 2.9619 0.0000 1.0000
VAV_MID WITH REHEAT 104.7677 95.0764 104.7677 28.9100 0.0000 1.0000
VAV_TOP WITH REHEAT 10.7077 10.2938 10.7077 2.9633 0.0000 1.0000
CAV_BAS 6.0855 6.0855 6.0855 6.0855 1.2002 1.0000
AIRLOOP DATACENTER BASEMENT 21.4296 21.4298 21.4296 21.4296 0.3384 1.0000
AIRLOOP DATACENTER BOT 0.4801 0.4801 0.4801 0.4801 0.0156 1.0000
AIRLOOP DATACENTER MID 4.5783 4.5783 4.5783 4.5783 0.1563 1.0000
AIRLOOP DATACENTER TOP 0.4669 0.4669 0.4669 0.4669 0.0156 1.0000


Zone Ventilation Calculations for Heating Design

AirLoop Name Box Type Zone Primary Airflow - Vpz [m3/s] Zone Discharge Airflow - Vdz [m3/s] Minimum Zone Primary Airflow - Vpz-min [m3/s] Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? Zone Outdoor Airflow Heating - Voz-htg [m3/s] Primary Outdoor Air Fraction - Zpz Primary Air Fraction - Ep Secondary Recirculation Fraction- Er Supply Air Fraction- Fa Mixed Air Fraction - Fb Outdoor Air Fraction - Fc Zone Ventilation Efficiency - Evz
BASEMENT CAV_BAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 6.0855 6.0855 6.0855 No 1.2002 1.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CORE_BOTTOM VAV_BOT WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 3.1411 3.1411 1.9600 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CORE_MID VAV_MID WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 29.6935 29.6935 19.2414 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CORE_TOP VAV_TOP WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 2.9174 2.9174 1.9663 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_BOT_ZN_3 VAV_BOT WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.5541 0.5541 0.2460 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_BOT_ZN_2 VAV_BOT WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.5550 0.5550 0.2220 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_BOT_ZN_1 VAV_BOT WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.5525 0.5525 0.2464 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_BOT_ZN_4 VAV_BOT WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.7186 0.7186 0.2874 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_MID_ZN_3 VAV_MID WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 5.3133 5.3133 2.4122 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_MID_ZN_2 VAV_MID WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 5.7410 5.7410 2.2964 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_MID_ZN_1 VAV_MID WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 5.2686 5.2686 2.4130 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_MID_ZN_4 VAV_MID WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 6.3675 6.3675 2.5470 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_TOP_ZN_3 VAV_TOP WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.5892 0.5892 0.2474 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_TOP_ZN_2 VAV_TOP WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.5815 0.5815 0.2326 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_TOP_ZN_1 VAV_TOP WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.5896 0.5896 0.2464 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_TOP_ZN_4 VAV_TOP WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.6763 0.6763 0.2705 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
DATACENTER_BOT_ZN_6 AIRLOOP DATACENTER BOT AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.4801 0.4801 0.4801 No 0.0156 1.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
DATACENTER_MID_ZN_6 AIRLOOP DATACENTER MID AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 4.5783 4.5783 4.5783 No 0.1563 1.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
DATACENTER_TOP_ZN_6 AIRLOOP DATACENTER TOP AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.4669 0.4669 0.4669 No 0.0156 1.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
DATACENTER_BASEMENT_ZN_6 AIRLOOP DATACENTER BASEMENT AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 21.4296 21.4296 21.4296 No 0.3384 1.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000


System Ventilation Calculations for Heating Design

Sum of Zone Primary Airflow - Vpz-sum [m3/s] System Primary Airflow - Vps [m3/s] Sum of Zone Discharge Airflow - Vdz-sum [m3/s] Sum of Min Zone Primary Airflow - Vpz-min [m3/s] Zone Outdoor Airflow Heating - Voz-htg [m3/s] Zone Ventilation Efficiency - Evz-min
VAV_BOT WITH REHEAT 5.5213 2.9619 2.9619 2.9619 0.0000 1.0000
VAV_MID WITH REHEAT 52.3838 28.9100 28.9100 28.9100 0.0000 1.0000
VAV_TOP WITH REHEAT 5.3538 2.9633 2.9633 2.9633 0.0000 1.0000
CAV_BAS 6.0855 6.0855 6.0855 6.0855 1.2002 1.0000
AIRLOOP DATACENTER BASEMENT 21.4296 21.4296 21.4296 21.4296 0.3384 1.0000
AIRLOOP DATACENTER BOT 0.4801 0.4801 0.4801 0.4801 0.0156 1.0000
AIRLOOP DATACENTER MID 4.5783 4.5783 4.5783 4.5783 0.1563 1.0000
AIRLOOP DATACENTER TOP 0.4669 0.4669 0.4669 0.4669 0.0156 1.0000



Table of Contents

Report: LEED Summary

For: Entire Facility

Timestamp: 2023-10-16 08:43:45

Sec1.1A-General Information

Data
Weather File RUNPERIOD 1 ** Miami Intl Ap FL USA TMY3 WMO#=722020
Total gross floor area [m2] 46320.38
Principal Heating Source Natural Gas


EAp2-1. Space Usage Type

Space Area [m2] Regularly Occupied Area [m2] Unconditioned Area [m2] Typical Hours/Week in Operation [hr/wk]
BASEMENT 2779.43 2779.43 0.00 113.98
CORE_BOTTOM 2496.12 2496.12 0.00 113.98
CORE_MID 2496.12 2496.12 0.00 113.98
CORE_TOP 2496.12 2496.12 0.00 113.98
PERIMETER_BOT_ZN_3 313.41 313.41 0.00 113.98
PERIMETER_BOT_ZN_2 201.98 201.98 0.00 113.98
PERIMETER_BOT_ZN_1 313.42 313.42 0.00 113.98
PERIMETER_BOT_ZN_4 201.98 201.98 0.00 113.98
PERIMETER_MID_ZN_3 313.41 313.41 0.00 113.98
PERIMETER_MID_ZN_2 201.98 201.98 0.00 96.54
PERIMETER_MID_ZN_1 313.42 313.42 0.00 113.98
PERIMETER_MID_ZN_4 201.98 201.98 0.00 113.98
PERIMETER_TOP_ZN_3 313.41 313.41 0.00 113.98
PERIMETER_TOP_ZN_2 201.98 201.98 0.00 113.98
PERIMETER_TOP_ZN_1 313.42 313.42 0.00 113.98
PERIMETER_TOP_ZN_4 201.98 201.98 0.00 113.98
DATACENTER_BOT_ZN_6 36.20 36.20 0.00 113.98
DATACENTER_MID_ZN_6 36.20 36.20 0.00 113.98
DATACENTER_TOP_ZN_6 36.20 36.20 0.00 113.98
DATACENTER_BASEMENT_ZN_6 783.68 783.68 0.00 113.98
GROUNDFLOOR_PLENUM 3563.11 3563.11 0.00 0.00
MIDFLOOR_PLENUM 3563.11 3563.11 0.00 0.00
TOPFLOOR_PLENUM 3563.11 3563.11 0.00 0.00
Totals 46320.38 46320.38 0.00  


EAp2-2. Advisory Messages

Data
Number of hours heating loads not met 0.00
Number of hours cooling loads not met 1000.17
Number of hours not met 1000.17


EAp2-3. Energy Type Summary

Utility Rate Virtual Rate [$/unit energy] Units of Energy Units of Demand
None        


EAp2-4/5. Performance Rating Method Compliance

Electricity Energy Use [GJ] Electricity Demand [W] Natural Gas Energy Use [GJ] Natural Gas Demand [W] Gasoline Use [GJ] Gasoline Demand [W] Diesel Use [GJ] Diesel Demand [W] Coal Use [GJ] Coal Demand [W] Fuel Oil No 1 Use [GJ] Fuel Oil No 1 Demand [W] Fuel Oil No 2 Use [GJ] Fuel Oil No 2 Demand [W] Propane Use [GJ] Propane Demand [W] Other Fuel 1 Use [GJ] Other Fuel 1 Demand [W] Other Fuel 2 Use [GJ] Other Fuel 2 Demand [W] District Cooling Use [GJ] District Cooling Demand [W] District Heating Use [GJ] District Heating Demand [W]
Heating -- General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heating -- Boiler 0.00 0.00 20.08 404990.47 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heating -- Boiler Parasitic 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling -- General 6915.41 495044.09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting -- LightsWired 3922.25 385834.94 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting -- General 696.56 57580.60 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- MiscPlug 5334.97 305206.10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- DataCenterPlugLoads 9341.42 473165.59 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment -- Transformer 80.17 5057.48 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment -- ElevatorLift 1848.78 113101.96 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment -- ElevatorLightsFan 5.83 376.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans -- General 2279.76 148849.04 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps -- General 978.88 69624.76 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection -- General 2294.23 98044.59 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification -- General 1.14 4077.20 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery -- General 119.08 5613.48 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems -- General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems -- WaterUse 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems -- Water Heater 0.00 0.00 640.83 70632.11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration -- Not Subdivided 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators -- General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


EAp2-6. Energy Use Summary

Process Subtotal [GJ] Total Energy Use [GJ]
Electricity 14676.40 33818.50
Natural Gas 0.00 660.92
Additional 0.00 0.00
Total 14676.40 34479.41


EAp2-7. Energy Cost Summary

Process Subtotal [$] Total Energy Cost [$]
Electricity 0.00  
Natural Gas 0.00  
Additional 0.00  
Total 0.00  
Process energy cost based on ratio of process to total energy.

L-1. Renewable Energy Source Summary

Rated Capacity [kW] Annual Energy Generated [GJ]
Photovoltaic 0.00 0.00
Wind 0.00 0.00


EAp2-17a. Energy Use Intensity - Electricity

Electricty [MJ/m2]
Interior Lighting (All) 84.68
Space Heating 0.00
Space Cooling 149.30
Fans (All) 49.22
Service Water Heating 0.00
Receptacle Equipment 316.85
Miscellaneous (All) 730.10
Subtotal 730.10


EAp2-17b. Energy Use Intensity - Natural Gas

Natural Gas [MJ/m2]
Space Heating 0.43
Service Water Heating 13.83
Miscellaneous (All) 14.27
Subtotal 14.27


EAp2-17c. Energy Use Intensity - Additional

Additional [MJ/m2]
Subtotal 0.00
Miscellaneous 0.00


EAp2-18. End Use Percentage

Percent [%]
Interior Lighting (All) 11.38
Space Heating 0.06
Space Cooling 20.06
Fans (All) 6.61
Service Water Heating 1.86
Receptacle Equipment 42.57
Miscellaneous 17.47


Schedules-Equivalent Full Load Hours (Schedule Type=Fraction)

Equivalent Full Load Hours of Operation Per Year [hr] Hours > 1% [hr]
EXTERIOR_LIGHTING_SCHEDULE_A 6570. 6570.
EXTERIOR_LIGHTING_SCHEDULE_B 8103. 8760.
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 4472. 4472.
EXTERIOR_LIGHTING_SCHEDULE_B_2016 7665. 8760.
EXTERIOR_LIGHTING_SCHEDULE_C_2016 6752. 8760.
ALWAYS_ON 8760. 8760.
EXTERIOR_LGT_ALWAYS_ON 8760. 8760.
EXTERIOR_LGT_189_1 6828. 8760.
ALWAYS_OFF 0. 0.
LTG_SCH_OFFICE 2625. 8760.
LTG_SCH_DATACENTER 2921. 8760.
EXTERIOR_LIGHT_SCH 4380. 4380.
BLDG_EQUIP_SCH 4049. 8760.
DATACENTER_EQUIP_SCH 5478. 8760.
BLDG_OCC_SCH 2528. 5992.
BLDG_OCC_SCH_W_SB 1878. 5056.
BLDG_OCC_SCH_WO_SB 2557. 5992.
BLDG_ELEVATORS 2270. 8760.
ELEV_LIGHT_FAN_SCH_24_7 8760. 8760.
ELEV_LIGHT_FAN_SCH_ADD_DF 2154. 8760.
BLDG_SWH_SCH 1474. 6570.
WORK_EFF_SCH 0. 0.
INFIL_SCH 3976. 3976.
INFIL_SCH_PNNL 5172. 8760.
INFIL_HALF_ON_SCH 6368. 8760.
FAN_SCH 8760. 8760.
REHEATCOILAVAILSCHED 8760. 8760.
COOLINGCOILAVAILSCHED 8760. 8760.
MINOA_MOTORIZEDDAMPER_SCHED 4472. 4472.
MINOA_SCHED 8760. 8760.
CORE_BOTTOM SUB CAT LATENT FRACT SCHED 438. 8760.
CORE_BOTTOM SUB CAT SENSIBLE FRACT SCHED 1752. 8760.
CORE_MID SUB CAT LATENT FRACT SCHED 438. 8760.
CORE_MID SUB CAT SENSIBLE FRACT SCHED 1752. 8760.
CORE_TOP SUB CAT LATENT FRACT SCHED 438. 8760.
CORE_TOP SUB CAT SENSIBLE FRACT SCHED 1752. 8760.
SUPPLYFANSCH 8760. 8760.
PERIMETER_MID_ZN_2_MDP_SCH 1565. 7824.


Schedules-SetPoints (Schedule Type=Temperature)

First Object Used Month Assumed 11am First Wednesday [C] Days with Same 11am Value 11pm First Wednesday [C] Days with Same 11pm Value
HTGSETP_DC_SCH DATACENTER COOLING SETPOINTS DUAL SP CONTROL January 18.00 365 18.00 365
CLGSETP_DC_SCH DATACENTER COOLING SETPOINTS DUAL SP CONTROL July 27.00 365 27.00 365
HTGSETP_SCH_YES_OPTIMUM CORE_BOTTOM DUAL SP CONTROL January 21.00 365 15.60 365
CLGSETP_SCH_YES_OPTIMUM CORE_BOTTOM DUAL SP CONTROL July 24.00 365 26.70 365



Table of Contents

Report: Annual Thermal Resilience Summary

For: Entire Facility

Timestamp: 2023-10-16 08:43:45

Heat Index Hours

Safe (≤ 26.7°C) [hr] Caution (> 26.7, ≤ 32.2°C) [hr] Extreme Caution (> 32.2, ≤ 39.4°C) [hr] Danger (> 39.4, ≤ 51.7°C) [hr] Extreme Danger (> 51.7°C) [hr]
BASEMENT 6515.17 2244.83 0.00 0.00 0.00
CORE_BOTTOM 8674.00 86.00 0.00 0.00 0.00
CORE_MID 8760.00 0.00 0.00 0.00 0.00
CORE_TOP 8757.00 3.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_3 8715.50 44.50 0.00 0.00 0.00
PERIMETER_BOT_ZN_2 8644.50 115.50 0.00 0.00 0.00
PERIMETER_BOT_ZN_1 8515.50 244.50 0.00 0.00 0.00
PERIMETER_BOT_ZN_4 7581.33 1178.67 0.00 0.00 0.00
PERIMETER_MID_ZN_3 8583.50 176.50 0.00 0.00 0.00
PERIMETER_MID_ZN_2 8386.33 373.67 0.00 0.00 0.00
PERIMETER_MID_ZN_1 8116.17 643.83 0.00 0.00 0.00
PERIMETER_MID_ZN_4 7728.00 1032.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_3 8488.83 271.17 0.00 0.00 0.00
PERIMETER_TOP_ZN_2 8322.17 437.83 0.00 0.00 0.00
PERIMETER_TOP_ZN_1 8077.00 683.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_4 7796.00 964.00 0.00 0.00 0.00
DATACENTER_BOT_ZN_6 1236.50 7523.50 0.00 0.00 0.00
DATACENTER_MID_ZN_6 1232.83 7527.17 0.00 0.00 0.00
DATACENTER_TOP_ZN_6 1188.83 7571.17 0.00 0.00 0.00
DATACENTER_BASEMENT_ZN_6 1046.33 7713.67 0.00 0.00 0.00
GROUNDFLOOR_PLENUM 8760.00 0.00 0.00 0.00 0.00
MIDFLOOR_PLENUM 8760.00 0.00 0.00 0.00 0.00
TOPFLOOR_PLENUM 8442.00 318.00 0.00 0.00 0.00
Min 1046.33 0.00 0.00 0.00 0.00
Max 8760.00 7713.67 0.00 0.00 0.00
Average 7057.72 1702.28 0.00 0.00 0.00
Sum 162327.50 39152.50 0.00 0.00 0.00


Heat Index OccupantHours

Safe (≤ 26.7°C) [hr] Caution (> 26.7, ≤ 32.2°C) [hr] Extreme Caution (> 32.2, ≤ 39.4°C) [hr] Danger (> 39.4, ≤ 51.7°C) [hr] Extreme Danger (> 51.7°C) [hr]
BASEMENT 363397.50 5218.50 0.00 0.00 0.00
CORE_BOTTOM 330733.00 80.00 0.00 0.00 0.00
CORE_MID 330813.00 0.00 0.00 0.00 0.00
CORE_TOP 330813.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_3 38925.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_2 24909.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_1 38925.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_4 24909.00 0.00 0.00 0.00 0.00
PERIMETER_MID_ZN_3 38925.00 0.00 0.00 0.00 0.00
PERIMETER_MID_ZN_2 18354.00 0.00 0.00 0.00 0.00
PERIMETER_MID_ZN_1 38925.00 0.00 0.00 0.00 0.00
PERIMETER_MID_ZN_4 24909.00 0.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_3 38925.00 0.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_2 24909.00 0.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_1 38925.00 0.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_4 24909.00 0.00 0.00 0.00 0.00
DATACENTER_BOT_ZN_6 208.50 2059.50 0.00 0.00 0.00
DATACENTER_MID_ZN_6 209.33 2058.67 0.00 0.00 0.00
DATACENTER_TOP_ZN_6 202.17 2065.83 0.00 0.00 0.00
DATACENTER_BASEMENT_ZN_6 9376.17 94018.83 0.00 0.00 0.00
GROUNDFLOOR_PLENUM 0.00 0.00 0.00 0.00 0.00
MIDFLOOR_PLENUM 0.00 0.00 0.00 0.00 0.00
TOPFLOOR_PLENUM 0.00 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00 0.00
Max 363397.50 94018.83 0.00 0.00 0.00
Average 75747.90 4587.01 0.00 0.00 0.00
Sum 1742201.67 105501.33 0.00 0.00 0.00


Humidex Hours

Little to no Discomfort (≤ 29) [hr] Some Discomfort (> 29, ≤ 40) [hr] Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] Dangerous (> 45, ≤ 50) [hr] Heat Stroke Quite Possible (> 50) [hr]
BASEMENT 3509.83 5250.17 0.00 0.00 0.00
CORE_BOTTOM 8411.67 348.33 0.00 0.00 0.00
CORE_MID 8689.33 70.67 0.00 0.00 0.00
CORE_TOP 8706.33 53.67 0.00 0.00 0.00
PERIMETER_BOT_ZN_3 7829.17 930.83 0.00 0.00 0.00
PERIMETER_BOT_ZN_2 8068.50 691.50 0.00 0.00 0.00
PERIMETER_BOT_ZN_1 7402.33 1357.67 0.00 0.00 0.00
PERIMETER_BOT_ZN_4 6952.00 1808.00 0.00 0.00 0.00
PERIMETER_MID_ZN_3 6277.00 2483.00 0.00 0.00 0.00
PERIMETER_MID_ZN_2 6398.67 2361.33 0.00 0.00 0.00
PERIMETER_MID_ZN_1 5892.83 2867.17 0.00 0.00 0.00
PERIMETER_MID_ZN_4 6140.00 2620.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_3 6169.50 2590.50 0.00 0.00 0.00
PERIMETER_TOP_ZN_2 6285.83 2474.17 0.00 0.00 0.00
PERIMETER_TOP_ZN_1 5831.00 2929.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_4 6113.17 2646.83 0.00 0.00 0.00
DATACENTER_BOT_ZN_6 2356.67 6403.33 0.00 0.00 0.00
DATACENTER_MID_ZN_6 2303.17 6456.83 0.00 0.00 0.00
DATACENTER_TOP_ZN_6 2214.67 6545.33 0.00 0.00 0.00
DATACENTER_BASEMENT_ZN_6 2429.67 6330.33 0.00 0.00 0.00
GROUNDFLOOR_PLENUM 8365.00 395.00 0.00 0.00 0.00
MIDFLOOR_PLENUM 7178.00 1582.00 0.00 0.00 0.00
TOPFLOOR_PLENUM 6876.67 1883.33 0.00 0.00 0.00
Min 2214.67 53.67 0.00 0.00 0.00
Max 8706.33 6545.33 0.00 0.00 0.00
Average 6104.39 2655.61 0.00 0.00 0.00
Sum 140401.00 61079.00 0.00 0.00 0.00


Humidex OccupantHours

Little to no Discomfort (≤ 29) [hr] Some Discomfort (> 29, ≤ 40) [hr] Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] Dangerous (> 45, ≤ 50) [hr] Heat Stroke Quite Possible (> 50) [hr]
BASEMENT 325708.17 42907.83 0.00 0.00 0.00
CORE_BOTTOM 330422.00 391.00 0.00 0.00 0.00
CORE_MID 330627.00 186.00 0.00 0.00 0.00
CORE_TOP 330709.00 104.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_3 38925.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_2 24909.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_1 38925.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_4 24909.00 0.00 0.00 0.00 0.00
PERIMETER_MID_ZN_3 38913.50 11.50 0.00 0.00 0.00
PERIMETER_MID_ZN_2 18351.50 2.50 0.00 0.00 0.00
PERIMETER_MID_ZN_1 38914.00 11.00 0.00 0.00 0.00
PERIMETER_MID_ZN_4 24908.00 1.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_3 38909.00 16.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_2 24905.00 4.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_1 38908.83 16.17 0.00 0.00 0.00
PERIMETER_TOP_ZN_4 24906.67 2.33 0.00 0.00 0.00
DATACENTER_BOT_ZN_6 380.50 1887.50 0.00 0.00 0.00
DATACENTER_MID_ZN_6 371.17 1896.83 0.00 0.00 0.00
DATACENTER_TOP_ZN_6 353.67 1914.33 0.00 0.00 0.00
DATACENTER_BASEMENT_ZN_6 19264.67 84130.33 0.00 0.00 0.00
GROUNDFLOOR_PLENUM 0.00 0.00 0.00 0.00 0.00
MIDFLOOR_PLENUM 0.00 0.00 0.00 0.00 0.00
TOPFLOOR_PLENUM 0.00 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00 0.00
Max 330709.00 84130.33 0.00 0.00 0.00
Average 74531.33 5803.58 0.00 0.00 0.00
Sum 1714220.67 133482.33 0.00 0.00 0.00


Heating SET Hours

SET ≤ 12.2°C Hours (°C) SET ≤ 12.2°C OccupantHours (°C) Longest SET ≤ 12.2°C Duration [hr] Start Time of the Longest SET ≤ 12.2°C Duration
None        


Cooling SET Hours

SET > 30°C Hours (°C) SET > 30°C OccupantHours (°C) Longest SET > 30°C Duration [hr] Start Time of the Longest SET > 30°C Duration
None        



Table of Contents

Report: Annual CO2 Resilience Summary

For: Entire Facility

Timestamp: 2023-10-16 08:43:45

CO2 Level Hours

Safe (<= 1000 ppm) [hr] Caution (> 1000, <= 5000 ppm) [hr] Hazard (> 5000 ppm) [hr]
None      


CO2 Level OccupantHours

Safe (<= 1000 ppm) [hr] Caution (> 1000, <= 5000 ppm) [hr] Hazard (> 5000 ppm) [hr]
None      



Table of Contents

Report: Annual Visual Resilience Summary

For: Entire Facility

Timestamp: 2023-10-16 08:43:45

Illuminance Level Hours

A Bit Dark (<= 100 lux) [hr] Dim (> 100, <= 300 lux) [hr] Adequate (> 300, <= 500 lux) [hr] Bright (>500 lux) [hr]
BASEMENT 0.00 0.00 0.00 0.00
CORE_BOTTOM 0.00 0.00 0.00 0.00
CORE_MID 0.00 0.00 0.00 0.00
CORE_TOP 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_3 0.00 0.00 8760.00 0.00
PERIMETER_BOT_ZN_2 0.00 0.00 8760.00 0.00
PERIMETER_BOT_ZN_1 0.00 0.00 8760.00 0.00
PERIMETER_BOT_ZN_4 0.00 0.00 8760.00 0.00
PERIMETER_MID_ZN_3 0.00 0.00 8760.00 0.00
PERIMETER_MID_ZN_2 0.00 0.00 8760.00 0.00
PERIMETER_MID_ZN_1 0.00 0.00 8760.00 0.00
PERIMETER_MID_ZN_4 0.00 0.00 8760.00 0.00
PERIMETER_TOP_ZN_3 0.00 0.00 8760.00 0.00
PERIMETER_TOP_ZN_2 0.00 0.00 8760.00 0.00
PERIMETER_TOP_ZN_1 0.00 0.00 8760.00 0.00
PERIMETER_TOP_ZN_4 0.00 0.00 8760.00 0.00
DATACENTER_BOT_ZN_6 0.00 0.00 0.00 0.00
DATACENTER_MID_ZN_6 0.00 0.00 0.00 0.00
DATACENTER_TOP_ZN_6 0.00 0.00 0.00 0.00
DATACENTER_BASEMENT_ZN_6 0.00 0.00 0.00 0.00
GROUNDFLOOR_PLENUM 0.00 0.00 0.00 0.00
MIDFLOOR_PLENUM 0.00 0.00 0.00 0.00
TOPFLOOR_PLENUM 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00
Max 0.00 0.00 8760.00 0.00
Average 0.00 0.00 4570.43 0.00
Sum 0.00 0.00 105120.00 0.00


Illuminance Level OccupantHours

A Bit Dark (<= 100 lux) [hr] Dim (> 100, <= 300 lux) [hr] Adequate (> 300, <= 500 lux) [hr] Bright (>500 lux) [hr]
BASEMENT 0.00 0.00 0.00 0.00
CORE_BOTTOM 0.00 0.00 0.00 0.00
CORE_MID 0.00 0.00 0.00 0.00
CORE_TOP 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_3 0.00 0.00 38925.00 0.00
PERIMETER_BOT_ZN_2 0.00 0.00 24909.00 0.00
PERIMETER_BOT_ZN_1 0.00 0.00 38925.00 0.00
PERIMETER_BOT_ZN_4 0.00 0.00 24909.00 0.00
PERIMETER_MID_ZN_3 0.00 0.00 38925.00 0.00
PERIMETER_MID_ZN_2 0.00 0.00 18354.00 0.00
PERIMETER_MID_ZN_1 0.00 0.00 38925.00 0.00
PERIMETER_MID_ZN_4 0.00 0.00 24909.00 0.00
PERIMETER_TOP_ZN_3 0.00 0.00 38925.00 0.00
PERIMETER_TOP_ZN_2 0.00 0.00 24909.00 0.00
PERIMETER_TOP_ZN_1 0.00 0.00 38925.00 0.00
PERIMETER_TOP_ZN_4 0.00 0.00 24909.00 0.00
DATACENTER_BOT_ZN_6 0.00 0.00 0.00 0.00
DATACENTER_MID_ZN_6 0.00 0.00 0.00 0.00
DATACENTER_TOP_ZN_6 0.00 0.00 0.00 0.00
DATACENTER_BASEMENT_ZN_6 0.00 0.00 0.00 0.00
GROUNDFLOOR_PLENUM 0.00 0.00 0.00 0.00
MIDFLOOR_PLENUM 0.00 0.00 0.00 0.00
TOPFLOOR_PLENUM 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00
Max 0.00 0.00 38925.00 0.00
Average 0.00 0.00 16367.35 0.00
Sum 0.00 0.00 376449.00 0.00



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR

For: Environment

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 19.420
February 20.868
March 21.567
April 24.112
May 26.413
June 27.683
July 28.127
August 27.974
September 27.493
October 26.347
November 23.587
December 20.295
   
Annual Sum or Average 24.507
Minimum of Months 19.420
Maximum of Months 28.127



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901

For: Environment

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 19.420
February 20.868
March 21.567
April 24.112
May 26.413
June 27.683
July 28.127
August 27.974
September 27.493
October 26.347
November 23.587
December 20.295
   
Annual Sum or Average 24.507
Minimum of Months 19.420
Maximum of Months 28.127



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2013

For: Environment

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 19.420
February 20.868
March 21.567
April 24.112
May 26.413
June 27.683
July 28.127
August 27.974
September 27.493
October 26.347
November 23.587
December 20.295
   
Annual Sum or Average 24.507
Minimum of Months 19.420
Maximum of Months 28.127



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND

For: Environment

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 19.420
February 20.868
March 21.567
April 24.112
May 26.413
June 27.683
July 28.127
August 27.974
September 27.493
October 26.347
November 23.587
December 20.295
   
Annual Sum or Average 24.507
Minimum of Months 19.420
Maximum of Months 28.127



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICELARGE

For: Environment

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 19.420
February 20.868
March 21.567
April 24.112
May 26.413
June 27.683
July 28.127
August 27.974
September 27.493
October 26.347
November 23.587
December 20.295
   
Annual Sum or Average 24.507
Minimum of Months 19.420
Maximum of Months 28.127



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL

For: Environment

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 19.420
February 20.868
March 21.567
April 24.112
May 26.413
June 27.683
July 28.127
August 27.974
September 27.493
October 26.347
November 23.587
December 20.295
   
Annual Sum or Average 24.507
Minimum of Months 19.420
Maximum of Months 28.127



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL

For: Environment

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 19.420
February 20.868
March 21.567
April 24.112
May 26.413
June 27.683
July 28.127
August 27.974
September 27.493
October 26.347
November 23.587
December 20.295
   
Annual Sum or Average 24.507
Minimum of Months 19.420
Maximum of Months 28.127



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 1A

For: Environment

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 19.420
February 20.868
March 21.567
April 24.112
May 26.413
June 27.683
July 28.127
August 27.974
September 27.493
October 26.347
November 23.587
December 20.295
   
Annual Sum or Average 24.507
Minimum of Months 19.420
Maximum of Months 28.127



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_FL_MIAMI

For: Environment

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 19.420
February 20.868
March 21.567
April 24.112
May 26.413
June 27.683
July 28.127
August 27.974
September 27.493
October 26.347
November 23.587
December 20.295
   
Annual Sum or Average 24.507
Minimum of Months 19.420
Maximum of Months 28.127



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: BASEMENT

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.664485E+11 105498.80 25-JAN-05:12 9.40 4.59 0.567191E+10 7499.12 27-JAN-10:00 21.70 15.05
February 0.597616E+11 109161.00 04-FEB-05:11 5.93 2.51 0.514395E+10 7499.11 23-FEB-10:09 23.07 17.34
March 0.677832E+11 106970.58 16-MAR-04:12 7.43 4.89 0.613701E+10 7499.08 17-MAR-13:09 21.20 14.87
April 0.618174E+11 104536.52 19-APR-04:12 15.00 11.82 0.545325E+10 7499.09 21-APR-09:20 25.40 18.57
May 0.661215E+11 89064.31 08-MAY-04:11 23.50 18.76 0.590485E+10 7498.82 25-MAY-09:20 24.23 23.36
June 0.660954E+11 85224.33 13-JUN-03:02 24.32 22.73 0.588466E+10 7498.81 28-JUN-09:20 26.30 24.72
July 0.668175E+11 87409.27 04-JUL-15:30 32.25 24.75 0.547656E+10 7498.80 07-JUL-13:20 32.03 25.28
August 0.747828E+11 86150.01 22-AUG-03:02 27.12 24.30 0.614004E+10 7498.78 04-AUG-13:20 27.12 24.30
September 0.670318E+11 85048.44 04-SEP-24:00 23.30 21.69 0.545560E+10 7498.79 15-SEP-09:20 27.40 24.40
October 0.704696E+11 91945.97 18-OCT-03:02 24.32 18.76 0.567472E+10 7498.78 18-OCT-09:20 26.70 18.90
November 0.696431E+11 108988.80 13-NOV-05:12 12.60 7.82 0.561876E+10 7499.12 13-NOV-10:09 19.68 13.91
December 0.681816E+11 107123.21 21-DEC-05:12 10.77 9.99 0.547557E+10 7499.18 21-DEC-10:09 19.08 15.38
                     
Annual Sum or Average 0.804954E+12         0.680369E+11        
Minimum of Months 0.597616E+11 85048.44   5.93 2.51 0.514395E+10 7498.78   19.08 13.91
Maximum of Months 0.747828E+11 109161.00   32.25 24.75 0.614004E+10 7499.18   32.03 25.28



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: CORE_BOTTOM

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.564758E+11 101591.23 30-JAN-05:13 20.73 20.35 0.506755E+10 6734.91 27-JAN-10:00 20.73 20.35
February 0.548811E+11 103182.26 21-FEB-05:13 16.33 15.55 0.460068E+10 6734.59 24-FEB-10:09 20.28 12.39
March 0.703668E+11 102435.06 07-MAR-05:13 20.40 19.02 0.549357E+10 6734.70 17-MAR-09:09 17.15 10.18
April 0.748647E+11 97200.94 19-APR-04:13 15.00 11.82 0.487226E+10 6734.50 18-APR-09:00 15.00 11.82
May 0.694836E+11 94217.47 26-MAY-03:02 23.90 22.01 0.527733E+10 6734.46 25-MAY-09:09 23.90 22.01
June 0.745290E+11 93484.24 13-JUN-03:02 24.32 22.73 0.526074E+10 6734.45 05-JUN-13:50 24.32 22.73
July 0.797098E+11 77512.77 14-JUL-05:02 27.20 25.17 0.488572E+10 6734.47 10-JUL-09:09 27.20 25.17
August 0.864309E+11 88363.86 21-AUG-05:03 27.20 24.67 0.548872E+10 6734.45 28-AUG-09:09 22.80 22.12
September 0.693658E+11 97920.21 06-SEP-04:13 23.13 22.53 0.487347E+10 6734.45 05-SEP-13:09 23.13 22.53
October 0.726477E+11 97025.17 20-OCT-04:13 21.70 19.53 0.506907E+10 6734.49 02-OCT-09:09 21.70 19.53
November 0.688409E+11 101674.97 27-NOV-05:11 10.00 8.82 0.502426E+10 6734.91 27-NOV-10:50 21.65 16.17
December 0.681145E+11 99972.90 18-DEC-05:12 17.20 17.20 0.489480E+10 6734.71 27-DEC-10:09 13.58 11.53
                     
Annual Sum or Average 0.845711E+12         0.608082E+11        
Minimum of Months 0.548811E+11 77512.77   10.00 8.82 0.460068E+10 6734.45   13.58 10.18
Maximum of Months 0.864309E+11 103182.26   27.20 25.17 0.549357E+10 6734.91   27.20 25.17



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: CORE_MID

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.452889E+11 88367.99 03-JAN-05:12 20.00 19.44 0.501797E+10 6734.88 27-JAN-10:00 21.70 15.05
February 0.427596E+11 91009.26 13-FEB-05:11 20.20 19.29 0.455424E+10 6734.58 24-FEB-10:09 20.28 12.39
March 0.519136E+11 89439.42 07-MAR-05:11 20.40 19.02 0.545977E+10 6734.69 17-MAR-09:09 17.15 10.18
April 0.525736E+11 89894.39 18-APR-04:12 19.03 14.99 0.485367E+10 6734.51 18-APR-13:09 22.38 14.69
May 0.588611E+11 89109.06 01-MAY-04:12 20.93 19.77 0.526150E+10 6734.46 25-MAY-09:09 24.32 23.32
June 0.604421E+11 85609.43 06-JUN-05:04 23.98 23.24 0.524467E+10 6734.47 05-JUN-13:50 23.98 23.24
July 0.608059E+11 84135.69 07-JUL-04:13 23.30 21.44 0.486451E+10 6734.45 07-JUL-13:09 32.12 25.32
August 0.620326E+11 87181.86 24-AUG-03:02 25.00 24.24 0.546916E+10 6734.45 28-AUG-13:09 22.30 22.22
September 0.585359E+11 85152.12 15-SEP-03:02 24.40 23.08 0.485448E+10 6734.45 06-SEP-13:09 24.40 23.08
October 0.571711E+11 91473.61 20-OCT-04:13 21.70 19.53 0.505577E+10 6734.50 10-OCT-13:09 21.70 19.53
November 0.507758E+11 89364.62 08-NOV-05:13 21.10 20.29 0.500412E+10 6734.89 27-NOV-10:50 21.65 16.17
December 0.461057E+11 88175.61 06-DEC-05:12 21.30 19.77 0.484321E+10 6734.71 15-DEC-14:09 19.08 14.19
                     
Annual Sum or Average 0.647266E+12         0.604831E+11        
Minimum of Months 0.427596E+11 84135.69   19.03 14.99 0.455424E+10 6734.45   17.15 10.18
Maximum of Months 0.620326E+11 91473.61   25.00 24.24 0.546916E+10 6734.89   32.12 25.32



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: CORE_TOP

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.417833E+11 85458.64 30-JAN-05:12 20.73 20.35 0.486488E+10 6734.49 20-JAN-14:09 20.73 20.35
February 0.413002E+11 86436.35 13-FEB-05:11 20.20 19.29 0.448580E+10 6734.51 21-FEB-14:00 26.10 13.62
March 0.517152E+11 86674.92 31-MAR-04:12 22.60 19.02 0.539756E+10 6734.59 17-MAR-13:09 22.60 19.02
April 0.547687E+11 88086.02 18-APR-04:12 19.03 14.99 0.484294E+10 6734.48 18-APR-09:00 20.60 14.15
May 0.633823E+11 87091.45 11-MAY-04:12 21.70 21.19 0.526441E+10 6734.47 30-MAY-13:09 25.97 24.15
June 0.657649E+11 85032.43 13-JUN-04:02 23.90 22.65 0.524981E+10 6734.45 05-JUN-13:00 23.90 22.65
July 0.668414E+11 84676.63 15-JUL-04:02 25.18 24.23 0.487278E+10 6734.43 14-JUL-13:00 25.18 24.23
August 0.669769E+11 85008.15 29-AUG-04:02 23.80 23.12 0.547151E+10 6734.45 07-AUG-13:00 23.80 23.12
September 0.625163E+11 85878.03 08-SEP-03:02 24.40 23.08 0.485747E+10 6734.43 11-SEP-13:00 27.80 24.12
October 0.588389E+11 85695.45 20-OCT-04:11 21.70 19.53 0.504773E+10 6734.48 26-OCT-13:00 21.70 20.88
November 0.500565E+11 86893.42 06-NOV-05:12 21.10 19.69 0.496108E+10 6734.42 24-NOV-10:09 21.70 21.35
December 0.434422E+11 85287.26 07-DEC-05:12 23.13 21.36 0.471430E+10 6734.58 13-DEC-14:00 21.70 13.99
                     
Annual Sum or Average 0.667387E+12         0.600303E+11        
Minimum of Months 0.413002E+11 84676.63   19.03 14.99 0.448580E+10 6734.42   20.60 13.62
Maximum of Months 0.669769E+11 88086.02   25.18 24.23 0.547151E+10 6734.59   27.80 24.23



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.607659E+10 14618.55 30-JAN-05:12 20.73 20.35 0.619504E+09 845.60 20-JAN-14:20 20.73 20.35
February 0.669087E+10 14664.89 17-FEB-05:11 22.80 20.75 0.570998E+09 845.61 21-FEB-14:09 25.68 14.65
March 0.901949E+10 15169.10 07-MAR-05:11 20.40 19.02 0.681492E+09 845.62 17-MAR-13:09 21.20 14.87
April 0.110655E+11 10831.86 17-APR-15:00 32.20 19.76 0.611931E+09 845.61 18-APR-13:09 22.38 14.69
May 0.122996E+11 17624.87 29-MAY-15:52 33.30 24.52 0.664515E+09 845.59 23-MAY-13:09 33.30 24.52
June 0.140977E+11 18923.30 11-JUN-16:11 30.93 24.21 0.662489E+09 845.59 21-JUN-13:20 29.40 23.58
July 0.149920E+11 19309.23 30-JUL-14:22 33.60 24.88 0.616039E+09 845.59 10-JUL-09:09 33.60 24.88
August 0.150686E+11 18834.32 20-AUG-11:42 32.12 26.12 0.690724E+09 845.59 07-AUG-13:30 32.12 26.12
September 0.121052E+11 18439.38 04-SEP-14:22 30.30 24.25 0.613695E+09 845.60 05-SEP-13:09 25.73 23.35
October 0.111289E+11 14807.71 19-OCT-04:11 23.30 18.68 0.637578E+09 845.60 10-OCT-13:09 23.30 18.68
November 0.934898E+10 14078.12 20-NOV-06:02 24.40 20.29 0.629138E+09 845.64 27-NOV-10:50 21.65 16.17
December 0.777355E+10 13837.07 01-DEC-05:11 22.57 18.22 0.605283E+09 845.62 15-DEC-14:30 19.45 14.42
                     
Annual Sum or Average 0.129667E+12         0.760339E+10        
Minimum of Months 0.607659E+10 10831.86   20.40 18.22 0.570998E+09 845.59   19.45 14.42
Maximum of Months 0.150686E+11 19309.23   33.60 26.12 0.690724E+09 845.64   33.60 26.12



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.566865E+10 19640.16 01-JAN-09:02 23.17 20.57 0.404211E+09 544.98 27-JAN-10:00 21.70 15.05
February 0.603970E+10 14796.86 20-FEB-09:23 19.45 16.01 0.368555E+09 544.95 21-FEB-14:09 25.68 14.65
March 0.827682E+10 10668.44 27-MAR-08:40 23.17 21.01 0.441595E+09 544.97 17-MAR-09:09 23.17 21.01
April 0.974997E+10 19906.07 09-APR-09:22 25.00 18.86 0.393337E+09 544.94 18-APR-09:00 20.60 14.15
May 0.104332E+11 19820.26 07-MAY-08:52 26.70 21.74 0.427825E+09 544.93 31-MAY-09:20 29.97 24.08
June 0.111761E+11 20583.32 11-JUN-09:32 30.40 23.99 0.426645E+09 544.93 14-JUN-09:39 28.53 23.70
July 0.118667E+11 20483.40 16-JUL-09:12 29.40 23.81 0.396820E+09 544.93 03-JUL-13:09 29.40 23.81
August 0.115443E+11 19040.36 20-AUG-11:42 32.12 26.12 0.444111E+09 544.93 08-AUG-09:39 32.12 26.12
September 0.102306E+11 17312.22 10-SEP-09:52 30.00 24.68 0.395394E+09 544.94 05-SEP-13:09 30.00 24.68
October 0.951963E+10 19895.32 09-OCT-08:42 28.12 24.23 0.410094E+09 544.94 10-OCT-13:09 23.77 22.52
November 0.757174E+10 9800.43 07-NOV-09:00 23.90 21.61 0.404661E+09 544.97 27-NOV-10:50 21.65 16.17
December 0.622347E+10 7948.88 03-DEC-10:02 21.28 17.34 0.386570E+09 544.95 27-DEC-10:09 13.58 11.53
                     
Annual Sum or Average 0.108301E+12         0.489982E+10        
Minimum of Months 0.566865E+10 7948.88   19.45 16.01 0.368555E+09 544.93   13.58 11.53
Maximum of Months 0.118667E+11 20583.32   32.12 26.12 0.444111E+09 544.98   32.12 26.12



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.119964E+11 21393.94 15-JAN-13:52 25.60 16.48 0.638860E+09 954.25 02-JAN-14:39 25.60 16.48
February 0.115473E+11 20967.20 20-FEB-12:02 23.98 17.32 0.581031E+09 930.59 21-FEB-14:30 25.85 14.25
March 0.130722E+11 19769.69 12-MAR-13:32 24.80 18.27 0.687327E+09 893.02 01-MAR-14:39 24.80 18.27
April 0.127593E+11 19073.57 09-APR-13:22 27.75 19.36 0.612643E+09 845.63 18-APR-13:09 22.38 14.69
May 0.122155E+11 17332.10 29-MAY-15:52 33.30 24.52 0.664411E+09 845.61 23-MAY-13:09 33.30 24.52
June 0.134009E+11 18467.82 11-JUN-16:11 30.93 24.21 0.662250E+09 845.61 21-JUN-13:20 29.40 23.58
July 0.145856E+11 19573.08 30-JUL-14:22 33.60 24.88 0.615838E+09 845.61 10-JUL-09:09 33.60 24.88
August 0.160098E+11 19470.38 20-AUG-12:22 32.20 25.83 0.690905E+09 850.39 31-AUG-13:20 31.70 24.32
September 0.149229E+11 19883.92 24-SEP-11:43 31.10 25.02 0.614688E+09 868.86 29-SEP-13:09 31.10 24.17
October 0.163470E+11 21938.18 29-OCT-12:41 30.10 25.68 0.643768E+09 908.01 25-OCT-13:20 30.10 25.68
November 0.149832E+11 21522.61 19-NOV-12:42 26.70 21.27 0.640824E+09 961.20 07-NOV-14:09 26.70 21.27
December 0.137795E+11 22594.59 03-DEC-14:01 24.40 18.40 0.618718E+09 974.34 04-DEC-14:39 25.93 17.99
                     
Annual Sum or Average 0.165620E+12         0.767126E+10        
Minimum of Months 0.115473E+11 17332.10   23.98 16.48 0.581031E+09 845.61   22.38 14.25
Maximum of Months 0.163470E+11 22594.59   33.60 25.83 0.690905E+09 974.34   33.60 25.68



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.719341E+10 18398.49 30-JAN-05:12 20.73 20.35 0.398711E+09 544.94 20-JAN-14:20 20.73 20.35
February 0.838537E+10 25330.25 19-FEB-16:12 27.03 21.82 0.370376E+09 544.95 21-FEB-14:09 25.68 14.65
March 0.123804E+11 25598.06 12-MAR-16:12 24.40 18.45 0.443882E+09 544.95 17-MAR-13:09 21.20 14.87
April 0.152838E+11 26855.61 09-APR-16:41 26.78 18.46 0.396132E+09 544.94 18-APR-13:09 22.38 14.69
May 0.127784E+11 25377.48 29-MAY-16:32 32.23 24.43 0.428614E+09 544.93 23-MAY-13:09 32.23 24.43
June 0.141317E+11 26623.32 11-JUN-14:51 31.10 24.60 0.427299E+09 544.93 21-JUN-13:30 29.40 23.64
July 0.163712E+11 26233.66 09-JUL-16:31 30.37 25.12 0.397585E+09 544.94 10-JUL-09:09 25.37 23.57
August 0.184203E+11 26423.02 20-AUG-16:21 30.60 24.86 0.446114E+09 544.93 07-AUG-13:30 30.60 24.86
September 0.122087E+11 25245.39 17-SEP-16:02 31.10 24.89 0.395821E+09 544.94 05-SEP-13:09 31.10 24.89
October 0.127318E+11 26315.95 09-OCT-15:22 30.00 23.98 0.411768E+09 544.94 26-OCT-13:50 22.98 21.43
November 0.114268E+11 25665.21 26-NOV-15:02 21.70 12.62 0.407280E+09 544.97 27-NOV-10:50 21.65 16.17
December 0.109498E+11 27154.46 03-DEC-15:21 24.40 18.03 0.396235E+09 544.96 15-DEC-14:09 19.08 14.19
                     
Annual Sum or Average 0.152262E+12         0.491982E+10        
Minimum of Months 0.719341E+10 18398.49   20.73 12.62 0.370376E+09 544.93   19.08 14.19
Maximum of Months 0.184203E+11 27154.46   32.23 25.12 0.446114E+09 544.97   32.23 24.89



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.474049E+10 9956.79 14-JAN-06:03 23.62 21.60 0.582500E+09 845.59 30-JAN-14:09 16.60 15.83
February 0.499241E+10 10552.93 18-FEB-06:03 23.40 20.68 0.551577E+09 845.60 21-FEB-14:09 25.68 14.65
March 0.652844E+10 11947.51 06-MAR-06:02 22.80 22.00 0.658292E+09 845.59 01-MAR-14:20 22.80 22.00
April 0.786852E+10 10901.71 15-APR-05:03 22.20 21.04 0.609076E+09 845.61 18-APR-13:09 22.38 14.69
May 0.109240E+11 18851.34 29-MAY-15:41 33.22 24.49 0.664467E+09 845.59 23-MAY-13:09 33.22 24.49
June 0.123578E+11 17974.34 25-JUN-14:32 30.37 24.89 0.662806E+09 845.59 21-JUN-13:30 30.37 24.89
July 0.126102E+11 18629.78 04-JUL-16:31 30.57 25.19 0.616310E+09 845.59 03-JUL-13:09 30.57 25.19
August 0.118397E+11 15928.24 20-AUG-12:22 32.20 25.83 0.690846E+09 845.59 08-AUG-09:00 32.20 25.83
September 0.107401E+11 17822.50 17-SEP-15:51 31.10 24.95 0.613606E+09 845.59 05-SEP-13:09 31.10 24.95
October 0.898929E+10 13687.13 19-OCT-04:11 23.30 18.68 0.636866E+09 845.59 06-OCT-13:20 23.30 18.68
November 0.683084E+10 13131.24 29-NOV-06:03 25.00 19.84 0.620607E+09 845.59 14-NOV-14:20 25.00 19.84
December 0.510698E+10 12997.27 09-DEC-06:02 24.90 22.63 0.568608E+09 845.59 26-DEC-14:00 19.40 13.57
                     
Annual Sum or Average 0.103529E+12         0.747556E+10        
Minimum of Months 0.474049E+10 9956.79   22.20 18.68 0.551577E+09 845.59   16.60 13.57
Maximum of Months 0.126102E+11 18851.34   33.22 25.83 0.690846E+09 845.61   33.22 25.83



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.482807E+10 19846.44 01-JAN-10:12 25.57 21.29 0.287075E+09 521.24 27-JAN-11:09 21.88 15.22
February 0.519864E+10 12432.78 26-FEB-10:02 22.48 16.09 0.265569E+09 521.21 21-FEB-13:30 22.48 16.09
March 0.693672E+10 10311.04 27-MAR-10:20 25.57 21.63 0.321205E+09 521.24 17-MAR-10:00 25.57 21.63
April 0.834985E+10 20784.34 09-APR-09:22 25.00 18.86 0.289188E+09 521.21 18-APR-10:09 20.78 14.20
May 0.994707E+10 20712.56 07-MAY-10:22 28.60 21.92 0.314651E+09 521.19 01-MAY-10:20 28.60 21.92
June 0.105459E+11 19920.43 11-JUN-09:42 30.50 23.90 0.313998E+09 521.19 20-JUN-10:20 26.70 24.08
July 0.110157E+11 21706.66 04-JUL-08:32 28.87 24.11 0.293158E+09 521.19 07-JUL-12:09 33.62 23.53
August 0.103741E+11 20468.26 27-AUG-09:32 30.53 25.44 0.326759E+09 521.20 08-AUG-10:20 30.53 25.44
September 0.977351E+10 20685.25 24-SEP-08:52 29.40 25.76 0.291209E+09 521.19 06-SEP-14:20 29.40 25.76
October 0.860037E+10 20544.24 09-OCT-08:52 28.30 24.27 0.302045E+09 521.19 17-OCT-10:20 27.20 18.83
November 0.636277E+10 9722.86 07-NOV-09:30 24.75 21.38 0.295880E+09 521.22 13-NOV-11:20 21.83 15.41
December 0.477849E+10 7788.98 08-DEC-10:00 26.10 22.56 0.271605E+09 521.19 04-DEC-11:20 26.10 22.56
                     
Annual Sum or Average 0.967112E+11         0.357234E+10        
Minimum of Months 0.477849E+10 7788.98   22.48 16.09 0.265569E+09 521.19   20.78 14.20
Maximum of Months 0.110157E+11 21706.66   30.53 25.76 0.326759E+09 521.24   33.62 25.76



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.111268E+11 20596.89 01-JAN-13:32 26.47 21.74 0.638180E+09 986.73 02-JAN-14:39 28.90 23.86
February 0.103116E+11 19973.65 26-FEB-12:42 24.82 16.09 0.579048E+09 950.88 21-FEB-14:50 24.82 16.09
March 0.107599E+11 19381.77 26-MAR-13:52 27.80 22.40 0.681612E+09 912.09 01-MAR-14:39 27.80 22.40
April 0.975925E+10 17771.51 16-APR-17:12 31.10 21.99 0.611332E+09 845.63 18-APR-13:09 22.38 14.69
May 0.108699E+11 18664.92 29-MAY-15:41 33.22 24.49 0.664288E+09 845.60 23-MAY-13:09 33.22 24.49
June 0.116306E+11 17585.42 25-JUN-14:32 30.37 24.89 0.662478E+09 845.61 21-JUN-13:30 30.37 24.89
July 0.122187E+11 18131.76 04-JUL-15:51 31.70 25.12 0.616060E+09 845.60 03-JUL-13:09 31.70 25.12
August 0.129467E+11 18500.46 20-AUG-12:22 32.20 25.83 0.691173E+09 851.43 31-AUG-13:20 31.70 24.32
September 0.138852E+11 19736.86 17-SEP-14:31 31.10 24.59 0.615253E+09 890.47 29-SEP-13:09 31.10 24.17
October 0.148179E+11 21080.94 29-OCT-12:11 30.40 25.20 0.647644E+09 939.36 25-OCT-13:00 30.40 25.20
November 0.130672E+11 20732.66 19-NOV-13:52 26.70 21.27 0.643589E+09 1002.64 07-NOV-14:20 26.70 21.27
December 0.114460E+11 22022.21 03-DEC-13:51 24.40 18.35 0.613774E+09 1006.19 04-DEC-14:39 25.93 17.99
                     
Annual Sum or Average 0.142840E+12         0.766443E+10        
Minimum of Months 0.975925E+10 17585.42   24.40 16.09 0.579048E+09 845.60   22.38 14.69
Maximum of Months 0.148179E+11 22022.21   33.22 25.83 0.691173E+09 1006.19   33.22 25.20



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.520608E+10 9761.42 14-JAN-06:03 23.62 21.60 0.372970E+09 544.93 09-JAN-14:00 23.62 21.60
February 0.562516E+10 22455.48 19-FEB-16:01 27.12 21.84 0.352861E+09 544.94 21-FEB-14:09 25.68 14.65
March 0.763035E+10 20505.92 12-MAR-16:22 24.40 18.50 0.425108E+09 544.93 22-MAR-13:39 23.30 17.33
April 0.898312E+10 24422.33 02-APR-16:41 25.78 18.10 0.392659E+09 544.94 18-APR-13:09 22.38 14.69
May 0.103640E+11 24716.95 29-MAY-15:41 33.22 24.49 0.427650E+09 544.93 23-MAY-13:09 33.22 24.49
June 0.103874E+11 21607.22 25-JUN-14:32 30.37 24.89 0.426818E+09 544.93 21-JUN-13:30 30.37 24.89
July 0.112948E+11 24581.35 04-JUL-16:31 30.57 25.19 0.397142E+09 544.93 03-JUL-13:09 30.57 25.19
August 0.111972E+11 22980.15 13-AUG-16:01 30.50 25.69 0.445182E+09 544.93 08-AUG-09:00 30.50 25.69
September 0.971491E+10 24642.79 17-SEP-15:51 31.10 24.95 0.394934E+09 544.93 05-SEP-13:09 31.10 24.95
October 0.890599E+10 23371.89 09-OCT-16:12 29.23 23.77 0.409891E+09 544.93 06-OCT-13:30 29.23 23.77
November 0.687947E+10 18263.68 19-NOV-15:12 26.70 20.63 0.397798E+09 544.93 14-NOV-14:00 26.70 20.63
December 0.574404E+10 23062.63 10-DEC-15:41 28.40 22.53 0.366025E+09 544.95 13-DEC-14:00 21.70 13.99
                     
Annual Sum or Average 0.101933E+12         0.480904E+10        
Minimum of Months 0.520608E+10 9761.42   23.62 18.10 0.352861E+09 544.93   21.70 13.99
Maximum of Months 0.112948E+11 24716.95   33.22 25.69 0.445182E+09 544.95   33.22 25.69



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.440025E+10 7913.15 14-JAN-06:03 23.62 21.60 0.566164E+09 845.59 30-JAN-14:09 16.60 15.83
February 0.486328E+10 8341.34 18-FEB-06:03 23.40 20.68 0.542239E+09 845.60 21-FEB-14:00 26.10 13.62
March 0.654972E+10 13423.55 06-MAR-06:02 22.80 22.00 0.650324E+09 845.59 22-MAR-13:09 23.30 16.73
April 0.818931E+10 13861.87 16-APR-17:12 31.10 21.99 0.606096E+09 845.61 18-APR-13:09 22.38 14.69
May 0.115326E+11 21484.45 29-MAY-15:41 33.22 24.49 0.664328E+09 845.58 23-MAY-13:09 33.22 24.49
June 0.130745E+11 20361.45 25-JUN-14:32 30.37 24.89 0.662937E+09 845.59 21-JUN-13:30 30.37 24.89
July 0.134778E+11 21255.36 04-JUL-16:31 30.57 25.19 0.616542E+09 845.58 03-JUL-13:09 30.57 25.19
August 0.125218E+11 20263.94 20-AUG-12:12 32.20 25.92 0.690674E+09 845.59 08-AUG-09:00 32.20 25.92
September 0.113008E+11 20626.91 17-SEP-15:51 31.10 24.95 0.613399E+09 845.60 05-SEP-13:09 31.10 24.95
October 0.921350E+10 15244.23 31-OCT-05:02 22.12 21.74 0.635665E+09 845.59 27-OCT-13:00 22.12 21.74
November 0.682939E+10 14840.62 10-NOV-06:02 22.70 22.40 0.613903E+09 845.59 14-NOV-14:09 23.90 15.88
December 0.487112E+10 10436.09 09-DEC-06:02 24.90 22.63 0.553739E+09 845.60 26-DEC-14:00 19.40 13.57
                     
Annual Sum or Average 0.106824E+12         0.741601E+10        
Minimum of Months 0.440025E+10 7913.15   22.12 20.68 0.542239E+09 845.58   16.60 13.57
Maximum of Months 0.134778E+11 21484.45   33.22 25.92 0.690674E+09 845.61   33.22 25.92



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.452996E+10 7564.00 01-JAN-10:32 26.13 21.45 0.386907E+09 544.98 27-JAN-10:00 21.70 15.05
February 0.508690E+10 8133.23 28-FEB-10:10 24.40 16.25 0.359919E+09 544.95 21-FEB-14:00 24.40 16.25
March 0.693404E+10 10632.57 31-MAR-09:30 24.15 19.41 0.437049E+09 544.97 17-MAR-09:09 24.15 19.41
April 0.859608E+10 20214.51 16-APR-09:52 27.20 21.71 0.392598E+09 544.95 18-APR-09:20 19.80 13.68
May 0.104318E+11 20989.69 07-MAY-10:32 28.70 21.94 0.427629E+09 544.93 23-MAY-13:09 29.60 23.18
June 0.111347E+11 20277.75 11-JUN-09:42 30.50 23.90 0.427129E+09 544.93 21-JUN-13:30 29.40 23.64
July 0.117141E+11 21982.11 04-JUL-08:32 28.87 24.11 0.397418E+09 544.93 03-JUL-13:09 28.87 24.11
August 0.109382E+11 20900.11 20-AUG-08:52 29.40 24.64 0.444627E+09 544.93 08-AUG-09:39 29.40 24.64
September 0.102485E+11 21008.81 24-SEP-08:52 29.40 25.76 0.395290E+09 544.94 05-SEP-13:09 29.40 25.76
October 0.881464E+10 17943.95 22-OCT-09:53 28.30 22.50 0.409767E+09 544.93 27-OCT-13:00 25.00 23.72
November 0.638248E+10 9934.87 10-NOV-06:02 22.70 22.40 0.400427E+09 544.96 13-NOV-10:20 19.97 14.10
December 0.460532E+10 7655.18 08-DEC-10:30 26.65 22.70 0.364616E+09 544.94 26-DEC-14:39 19.40 13.57
                     
Annual Sum or Average 0.994166E+11         0.484338E+10        
Minimum of Months 0.452996E+10 7564.00   22.70 16.25 0.359919E+09 544.93   19.40 13.57
Maximum of Months 0.117141E+11 21982.11   30.50 25.76 0.444627E+09 544.98   29.60 25.76



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.104896E+11 22811.27 15-JAN-14:22 25.60 16.75 0.624898E+09 948.63 02-JAN-14:39 25.60 16.75
February 0.100463E+11 22055.90 26-FEB-14:32 25.60 16.51 0.570968E+09 917.01 21-FEB-14:50 25.60 16.51
March 0.106659E+11 20939.05 12-MAR-14:12 24.80 18.16 0.674649E+09 876.50 01-MAR-14:39 24.80 18.16
April 0.100474E+11 20166.64 16-APR-17:12 31.10 21.99 0.608878E+09 845.63 18-APR-13:09 22.38 14.69
May 0.114759E+11 21453.44 29-MAY-15:41 33.22 24.49 0.663978E+09 845.60 23-MAY-13:09 33.22 24.49
June 0.123420E+11 20212.53 25-JUN-14:32 30.37 24.89 0.662587E+09 845.61 21-JUN-13:30 30.37 24.89
July 0.130751E+11 21039.89 04-JUL-15:51 31.70 25.12 0.616279E+09 845.60 03-JUL-13:09 31.70 25.12
August 0.136262E+11 20953.53 20-AUG-12:12 32.20 25.92 0.690932E+09 845.60 08-AUG-09:00 32.20 25.92
September 0.144683E+11 22485.72 17-SEP-14:31 31.10 24.59 0.614662E+09 870.69 29-SEP-13:09 31.10 24.17
October 0.150367E+11 22095.32 29-OCT-13:02 30.00 25.83 0.643201E+09 913.06 25-OCT-13:00 30.00 25.83
November 0.129250E+11 22011.74 19-NOV-15:32 26.70 20.63 0.635668E+09 964.02 07-NOV-14:20 26.70 20.63
December 0.109317E+11 23683.18 10-DEC-15:01 28.80 22.65 0.602162E+09 963.44 04-DEC-14:39 28.80 22.65
                     
Annual Sum or Average 0.145130E+12         0.760886E+10        
Minimum of Months 0.100463E+11 20166.64   24.80 16.51 0.570968E+09 845.60   22.38 14.69
Maximum of Months 0.150367E+11 23683.18   33.22 25.92 0.690932E+09 964.02   33.22 25.92



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.501375E+10 9285.15 03-JAN-15:40 26.70 20.74 0.363147E+09 544.93 04-JAN-14:39 25.20 21.01
February 0.559375E+10 23473.04 19-FEB-16:12 27.03 21.82 0.346075E+09 544.96 21-FEB-14:00 26.10 13.62
March 0.767558E+10 23511.09 12-MAR-16:52 24.40 18.65 0.419006E+09 544.93 02-MAR-14:00 24.40 18.65
April 0.924093E+10 24226.56 09-APR-16:12 27.03 18.57 0.389470E+09 544.94 18-APR-13:09 22.38 14.69
May 0.108197E+11 26754.78 29-MAY-15:41 33.22 24.49 0.426535E+09 544.93 23-MAY-13:09 33.22 24.49
June 0.109263E+11 23330.16 25-JUN-14:32 30.37 24.89 0.426231E+09 544.93 21-JUN-13:30 30.37 24.89
July 0.119327E+11 26630.39 04-JUL-16:31 30.57 25.19 0.396717E+09 544.93 10-JUL-09:09 25.37 23.57
August 0.117027E+11 24661.09 20-AUG-16:11 30.60 24.86 0.444516E+09 544.93 08-AUG-09:00 30.60 24.86
September 0.101604E+11 26631.76 17-SEP-15:51 31.10 24.95 0.393730E+09 544.93 05-SEP-13:09 31.10 24.95
October 0.911058E+10 23821.27 22-OCT-15:52 28.30 23.16 0.407794E+09 544.93 27-OCT-13:00 25.00 23.72
November 0.692110E+10 18059.14 19-NOV-15:32 26.70 20.63 0.392508E+09 544.93 14-NOV-14:00 26.70 20.63
December 0.562102E+10 24565.87 10-DEC-15:41 28.40 22.53 0.357130E+09 544.95 13-DEC-14:00 21.70 13.99
                     
Annual Sum or Average 0.104718E+12         0.476286E+10        
Minimum of Months 0.501375E+10 9285.15   24.40 18.57 0.346075E+09 544.93   21.70 13.62
Maximum of Months 0.119327E+11 26754.78   33.22 25.19 0.444516E+09 544.96   33.22 24.95



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: GROUNDFLOOR_PLENUM

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.602742E+10 11040.37 03-JAN-06:02 20.00 19.21 0.00 0.00 01-JAN-00:10 20.00 19.21
February 0.646212E+10 10035.15 13-FEB-06:02 20.60 19.45 0.00 0.00 01-FEB-00:10 20.60 19.45
March 0.838752E+10 9507.31 28-MAR-05:03 21.60 19.81 0.00 0.00 01-MAR-00:10 21.60 19.81
April 0.990445E+10 10494.56 17-APR-05:03 18.90 16.76 0.00 0.00 01-APR-00:10 18.90 16.76
May 0.108062E+11 11758.12 24-MAY-05:03 23.98 22.69 0.00 0.00 01-MAY-00:10 23.98 22.69
June 0.121077E+11 10096.38 06-JUN-05:02 23.98 23.24 0.00 0.00 01-JUN-00:10 23.98 23.24
July 0.132448E+11 12347.95 05-JUL-05:03 25.68 23.38 0.00 0.00 01-JUL-00:10 25.68 23.38
August 0.134536E+11 12447.08 21-AUG-05:15 27.20 24.60 0.00 0.00 01-AUG-00:10 27.20 24.60
September 0.116166E+11 14310.38 18-SEP-05:02 27.70 24.16 0.00 0.00 01-SEP-00:10 27.70 24.16
October 0.110153E+11 12409.81 16-OCT-05:02 22.20 20.71 0.00 0.00 01-OCT-00:10 22.20 20.71
November 0.910754E+10 10423.69 08-NOV-06:03 21.10 20.29 0.00 0.00 01-NOV-00:10 21.10 20.29
December 0.730306E+10 9783.35 11-DEC-06:03 22.20 21.65 0.00 0.00 01-DEC-00:10 22.20 21.65
                     
Annual Sum or Average 0.119436E+12         0.00        
Minimum of Months 0.602742E+10 9507.31   18.90 16.76 0.00 0.00   18.90 16.76
Maximum of Months 0.134536E+11 14310.38   27.70 24.60 0.00 0.00   27.70 24.60



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: MIDFLOOR_PLENUM

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.419608E+10 6538.48 02-JAN-17:00 25.00 20.39 0.00 0.00 01-JAN-00:10 25.00 20.39
February 0.439792E+10 6366.66 04-FEB-06:02 5.50 1.97 0.00 0.00 01-FEB-00:10 5.50 1.97
March 0.595769E+10 7436.76 30-MAR-16:00 26.10 19.47 0.00 0.00 01-MAR-00:10 26.10 19.47
April 0.732363E+10 7814.30 14-APR-16:00 29.40 24.14 0.00 0.00 01-APR-00:10 29.40 24.14
May 0.929655E+10 9792.34 20-MAY-05:03 26.02 22.19 0.00 0.00 01-MAY-00:10 26.02 22.19
June 0.102883E+11 9982.47 28-JUN-05:02 26.70 23.67 0.00 0.00 01-JUN-00:10 26.70 23.67
July 0.107883E+11 10465.30 06-JUL-05:02 23.90 22.23 0.00 0.00 01-JUL-00:10 23.90 22.23
August 0.103360E+11 8886.65 23-AUG-15:50 30.78 25.26 0.00 0.00 01-AUG-00:10 30.78 25.26
September 0.100871E+11 9964.79 30-SEP-05:03 24.40 22.82 0.00 0.00 01-SEP-00:10 24.40 22.82
October 0.906595E+10 9456.08 25-OCT-05:03 22.80 21.21 0.00 0.00 01-OCT-00:10 22.80 21.21
November 0.670488E+10 9858.52 10-NOV-06:02 22.70 22.40 0.00 0.00 01-NOV-00:10 22.70 22.40
December 0.481369E+10 6973.94 08-DEC-17:00 25.60 22.81 0.00 0.00 01-DEC-00:10 25.60 22.81
                     
Annual Sum or Average 0.932561E+11         0.00        
Minimum of Months 0.419608E+10 6366.66   5.50 1.97 0.00 0.00   5.50 1.97
Maximum of Months 0.107883E+11 10465.30   30.78 25.26 0.00 0.00   30.78 25.26



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: TOPFLOOR_PLENUM

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.508548E+10 13611.83 02-JAN-15:00 28.90 23.37 0.00 0.00 01-JAN-00:10 28.90 23.37
February 0.655184E+10 13649.34 17-FEB-14:10 26.70 21.67 0.00 0.00 01-FEB-00:10 26.70 21.67
March 0.906720E+10 17514.89 27-MAR-15:00 27.80 22.40 0.00 0.00 01-MAR-00:10 27.80 22.40
April 0.119933E+11 19786.67 13-APR-14:00 28.90 24.03 0.00 0.00 01-APR-00:10 28.90 24.03
May 0.155159E+11 20809.66 22-MAY-13:40 34.07 23.58 0.00 0.00 01-MAY-00:10 34.07 23.58
June 0.166559E+11 21707.51 09-JUN-14:00 31.10 24.95 0.00 0.00 01-JUN-00:10 31.10 24.95
July 0.181274E+11 23127.28 28-JUL-15:30 35.00 25.05 0.00 0.00 01-JUL-00:10 35.00 25.05
August 0.165188E+11 22275.12 23-AUG-14:00 32.20 25.37 0.00 0.00 01-AUG-00:10 32.20 25.37
September 0.154614E+11 20538.77 08-SEP-14:50 32.12 23.49 0.00 0.00 01-SEP-00:10 32.12 23.49
October 0.126882E+11 19845.84 06-OCT-13:10 29.82 23.71 0.00 0.00 01-OCT-00:10 29.82 23.71
November 0.896442E+10 16072.50 10-NOV-14:30 28.90 24.27 0.00 0.00 01-NOV-00:10 28.90 24.27
December 0.573406E+10 13910.53 08-DEC-14:40 27.40 22.79 0.00 0.00 01-DEC-00:10 27.40 22.79
                     
Annual Sum or Average 0.142364E+12         0.00        
Minimum of Months 0.508548E+10 13611.83   26.70 21.67 0.00 0.00   26.70 21.67
Maximum of Months 0.181274E+11 23127.28   35.00 25.37 0.00 0.00   35.00 25.37



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.434906E+10 2189.59 24-JAN-17:00 16.70 8.78 95235926.67 126.85 12-JAN-14:39 16.70 8.78
February 0.867792E+10 4316.70 20-FEB-17:50 25.28 17.48 86408514.34 126.86 02-FEB-10:39 25.28 17.48
March 0.147381E+11 7229.83 31-MAR-24:00 22.60 17.97 0.103245E+09 126.85 14-MAR-09:09 22.60 17.97
April 0.192051E+11 7964.60 09-APR-17:50 25.78 18.40 91622079.17 127.01 14-APR-13:00 30.60 24.51
May 0.478101E+10 3530.48 31-MAY-24:00 26.70 24.69 99234981.26 126.86 08-MAY-09:30 26.70 24.69
June 0.947800E+10 5370.69 30-JUN-23:47 26.95 23.78 98985433.77 126.87 06-JUN-09:09 26.95 23.78
July 0.148762E+11 7279.34 31-JUL-23:40 28.63 25.86 91894154.08 126.84 12-JUL-09:09 28.63 25.86
August 0.200303E+11 7840.71 20-AUG-18:10 29.82 24.37 0.104301E+09 133.60 23-AUG-13:00 32.20 25.37
September 0.464337E+10 3472.36 30-SEP-23:45 28.05 23.47 91605140.71 126.82 12-SEP-09:39 28.05 23.47
October 0.980162E+10 5409.42 31-OCT-24:00 22.50 21.29 95253679.10 126.88 02-OCT-09:09 22.50 21.29
November 0.143010E+11 6140.92 07-NOV-17:00 27.80 22.39 94311474.42 126.85 30-NOV-10:09 26.70 24.69
December 0.197011E+11 8056.14 06-DEC-17:00 25.60 21.66 91882994.15 126.83 29-DEC-10:09 19.27 17.74
                     
Annual Sum or Average 0.144583E+12         0.114398E+10        
Minimum of Months 0.434906E+10 2189.59   16.70 8.78 86408514.34 126.82   16.70 8.78
Maximum of Months 0.200303E+11 8056.14   29.82 25.86 0.104301E+09 133.60   32.20 25.86



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: DATACENTER_MID_ZN_6

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.334899E+10 1983.74 24-JAN-17:00 16.70 8.78 95232655.99 126.84 23-JAN-14:39 16.70 8.78
February 0.769381E+10 3948.68 21-FEB-17:50 24.60 13.54 86408170.10 126.86 02-FEB-10:00 24.60 13.54
March 0.137278E+11 6990.36 31-MAR-24:00 22.60 17.97 0.103246E+09 126.85 10-MAR-10:00 22.60 17.97
April 0.182487E+11 7474.09 09-APR-17:51 25.60 18.39 91614249.51 126.83 17-APR-09:20 22.60 19.95
May 0.441534E+10 3403.30 31-MAY-24:00 26.70 24.69 99233575.14 126.85 22-MAY-13:09 26.70 24.69
June 0.898309E+10 5192.07 30-JUN-23:53 26.90 23.74 98987483.74 126.87 23-JUN-13:00 26.90 23.74
July 0.141371E+11 7010.33 31-JUL-23:55 28.60 26.07 91895885.09 126.85 12-JUL-09:09 28.60 26.07
August 0.189326E+11 7417.31 30-AUG-16:00 29.40 23.81 0.103813E+09 132.40 23-AUG-13:50 29.40 23.81
September 0.425087E+10 3291.46 30-SEP-23:45 28.05 23.47 91605142.58 126.82 25-SEP-09:09 28.05 23.47
October 0.924208E+10 5094.44 31-OCT-24:00 22.50 21.29 95254864.81 126.87 04-OCT-13:09 22.50 21.29
November 0.133752E+11 5844.75 07-NOV-17:00 27.80 22.39 94312796.93 126.85 24-NOV-14:00 22.80 21.96
December 0.182062E+11 7639.80 06-DEC-17:00 25.60 21.66 91883478.21 126.83 29-DEC-10:09 19.27 17.74
                     
Annual Sum or Average 0.134562E+12         0.114349E+10        
Minimum of Months 0.334899E+10 1983.74   16.70 8.78 86408170.10 126.82   16.70 8.78
Maximum of Months 0.189326E+11 7639.80   29.40 26.07 0.103813E+09 132.40   29.40 26.07



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.279982E+10 2019.17 02-JAN-17:00 25.00 20.39 95232609.11 126.84 19-JAN-14:00 25.00 18.53
February 0.737174E+10 4005.86 21-FEB-17:50 24.60 13.54 86408481.68 126.86 02-FEB-14:00 24.60 13.54
March 0.135416E+11 6931.40 31-MAR-24:00 22.60 17.97 0.103246E+09 126.85 06-MAR-10:00 22.60 17.97
April 0.182359E+11 7692.92 09-APR-17:51 25.60 18.39 91611219.87 126.83 17-APR-09:50 23.95 20.74
May 0.449845E+10 3411.64 31-MAY-24:00 26.70 24.69 99234347.73 126.86 01-MAY-13:50 26.70 24.69
June 0.908762E+10 5181.81 30-JUN-23:15 27.10 23.92 98986558.31 126.87 28-JUN-09:00 27.10 23.92
July 0.142825E+11 7029.39 31-JUL-23:55 28.60 26.07 91895551.67 126.85 12-JUL-09:09 28.60 26.07
August 0.190268E+11 7584.15 20-AUG-18:11 29.63 24.40 0.103625E+09 131.41 23-AUG-13:00 32.20 25.37
September 0.432992E+10 3332.88 30-SEP-23:35 28.10 23.41 91605142.82 126.82 18-SEP-09:00 28.10 23.41
October 0.922665E+10 5006.95 31-OCT-24:00 22.50 21.29 95254607.96 126.87 04-OCT-13:09 22.50 21.29
November 0.131584E+11 5908.71 07-NOV-17:00 27.80 22.39 94312849.03 126.85 30-NOV-10:00 26.70 24.69
December 0.177874E+11 7704.53 06-DEC-17:00 25.60 21.66 91883891.36 126.83 29-DEC-10:09 19.27 17.74
                     
Annual Sum or Average 0.133347E+12         0.114330E+10        
Minimum of Months 0.279982E+10 2019.17   22.50 13.54 86408481.68 126.82   19.27 13.54
Maximum of Months 0.190268E+11 7704.53   29.63 26.07 0.103625E+09 131.41   32.20 26.07



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.243730E+12 94484.31 02-JAN-17:00 25.00 20.39 0.206189E+10 2746.78 30-JAN-14:09 16.60 15.83
February 0.440653E+12 185771.74 21-FEB-17:00 25.60 14.07 0.187055E+10 2746.27 02-FEB-10:39 25.60 14.07
March 0.732904E+12 360095.23 31-MAR-24:00 22.60 17.97 0.223501E+10 2746.80 16-MAR-13:09 22.60 17.97
April 0.943993E+12 370080.19 17-APR-21:02 23.22 17.86 0.207857E+10 3268.34 14-APR-13:00 23.22 17.86
May 0.244034E+12 177048.12 31-MAY-24:00 26.70 24.69 0.214908E+10 2747.15 24-MAY-09:00 26.70 24.69
June 0.472430E+12 268627.10 30-JUN-23:53 26.90 23.74 0.214292E+10 2746.67 05-JUN-13:00 26.90 23.74
July 0.734143E+12 357520.45 31-JUL-23:35 28.63 25.86 0.198925E+10 2745.88 10-JUL-09:09 28.63 25.86
August 0.972794E+12 370406.01 28-AUG-12:20 22.20 21.97 0.263707E+10 3590.13 23-AUG-13:39 22.20 21.97
September 0.238470E+12 176973.82 30-SEP-23:53 28.00 23.53 0.198407E+10 2747.16 18-SEP-09:39 28.00 23.53
October 0.490338E+12 269342.00 31-OCT-24:00 22.50 21.29 0.206208E+10 2746.71 04-OCT-09:09 22.50 21.29
November 0.711795E+12 278116.79 07-NOV-17:00 27.80 22.39 0.204157E+10 2745.87 29-NOV-10:00 26.10 24.93
December 0.979884E+12 369959.13 11-DEC-17:00 22.80 16.83 0.202207E+10 3079.95 08-DEC-14:00 22.80 16.83
                     
Annual Sum or Average 0.720517E+13         0.252741E+11        
Minimum of Months 0.238470E+12 94484.31   22.20 14.07 0.187055E+10 2745.87   16.60 14.07
Maximum of Months 0.979884E+12 370406.01   28.63 25.86 0.263707E+10 3590.13   28.63 25.86



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: BASEMENT

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.139622E+09 12164.12 01-JAN-12:53 27.20
February 0.169516E+09 12154.40 11-FEB-17:03 27.02
March 0.155598E+09 11090.56 04-MAR-17:12 25.93
April 0.281781E+09 20062.64 15-APR-16:01 31.70
May 0.495691E+09 19106.14 29-MAY-16:22 32.50
June 0.413692E+09 19653.25 10-JUN-16:01 31.52
July 0.586778E+09 25123.71 29-JUL-16:01 35.40
August 0.482727E+09 19847.55 19-AUG-16:01 31.60
September 0.570699E+09 18582.12 30-SEP-16:02 31.02
October 0.495156E+09 17925.83 14-OCT-16:03 31.23
November 0.309756E+09 15352.93 05-NOV-16:33 27.80
December 0.215025E+09 14507.84 10-DEC-15:03 28.80
         
Annual Sum or Average 0.431604E+10      
Minimum of Months 0.139622E+09 11090.56   25.93
Maximum of Months 0.586778E+09 25123.71   35.40



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: CORE_BOTTOM

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:05 20.40
February 0.00 0.00 01-FEB-00:10 16.65
March 0.00 0.00 01-MAR-00:10 17.32
April 0.00 0.00 01-APR-00:02 22.57
May 0.00 0.00 01-MAY-00:05 22.05
June 0.00 0.00 01-JUN-00:02 26.68
July 0.00 0.00 01-JUL-00:03 26.83
August 0.00 0.00 01-AUG-00:05 28.60
September 0.00 0.00 01-SEP-00:03 27.05
October 0.00 0.00 01-OCT-00:03 27.93
November 0.00 0.00 01-NOV-00:10 22.40
December 0.00 0.00 01-DEC-00:10 24.10
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   16.65
Maximum of Months 0.00 0.00   28.60



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: CORE_MID

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:05 20.40
February 0.00 0.00 01-FEB-00:10 16.65
March 0.00 0.00 01-MAR-00:10 17.32
April 0.00 0.00 01-APR-00:02 22.57
May 0.00 0.00 01-MAY-00:05 22.05
June 0.00 0.00 01-JUN-00:02 26.68
July 0.00 0.00 01-JUL-00:03 26.83
August 0.00 0.00 01-AUG-00:05 28.60
September 0.00 0.00 01-SEP-00:03 27.05
October 0.00 0.00 01-OCT-00:03 27.93
November 0.00 0.00 01-NOV-00:10 22.40
December 0.00 0.00 01-DEC-00:10 24.10
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   16.65
Maximum of Months 0.00 0.00   28.60



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: CORE_TOP

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:05 20.40
February 0.00 0.00 01-FEB-00:10 16.65
March 0.00 0.00 01-MAR-00:10 17.32
April 0.00 0.00 01-APR-00:02 22.57
May 0.00 0.00 01-MAY-00:05 22.05
June 0.00 0.00 01-JUN-00:02 26.68
July 0.00 0.00 01-JUL-00:03 26.83
August 0.00 0.00 01-AUG-00:05 28.60
September 0.00 0.00 01-SEP-00:03 27.05
October 0.00 0.00 01-OCT-00:03 27.93
November 0.00 0.00 01-NOV-00:10 22.40
December 0.00 0.00 01-DEC-00:10 24.10
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   16.65
Maximum of Months 0.00 0.00   28.60



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:05 20.40
February 0.00 0.00 01-FEB-00:10 16.65
March 0.00 0.00 01-MAR-00:10 17.32
April 0.00 0.00 01-APR-00:02 22.57
May 0.00 0.00 01-MAY-00:05 22.05
June 0.00 0.00 01-JUN-00:02 26.68
July 0.00 0.00 01-JUL-00:03 26.83
August 0.00 0.00 01-AUG-00:05 28.60
September 0.00 0.00 01-SEP-00:03 27.05
October 0.00 0.00 01-OCT-00:03 27.93
November 0.00 0.00 01-NOV-00:10 22.40
December 0.00 0.00 01-DEC-00:10 24.10
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   16.65
Maximum of Months 0.00 0.00   28.60



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:05 20.40
February 80410.95 670.09 04-FEB-06:02 5.50
March 0.00 0.00 01-MAR-00:10 17.32
April 0.00 0.00 01-APR-00:02 22.57
May 0.00 0.00 01-MAY-00:05 22.05
June 0.00 0.00 01-JUN-00:02 26.68
July 0.00 0.00 01-JUL-00:03 26.83
August 0.00 0.00 01-AUG-00:05 28.60
September 0.00 0.00 01-SEP-00:03 27.05
October 0.00 0.00 01-OCT-00:03 27.93
November 0.00 0.00 01-NOV-00:10 22.40
December 0.00 0.00 01-DEC-00:10 24.10
         
Annual Sum or Average 80410.95      
Minimum of Months 0.00 0.00   5.50
Maximum of Months 80410.95 670.09   28.60



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:05 20.40
February 0.00 0.00 01-FEB-00:10 16.65
March 0.00 0.00 01-MAR-00:10 17.32
April 0.00 0.00 01-APR-00:02 22.57
May 0.00 0.00 01-MAY-00:05 22.05
June 0.00 0.00 01-JUN-00:02 26.68
July 0.00 0.00 01-JUL-00:03 26.83
August 0.00 0.00 01-AUG-00:05 28.60
September 0.00 0.00 01-SEP-00:03 27.05
October 0.00 0.00 01-OCT-00:03 27.93
November 0.00 0.00 01-NOV-00:10 22.40
December 0.00 0.00 01-DEC-00:10 24.10
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   16.65
Maximum of Months 0.00 0.00   28.60



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:05 20.40
February 0.00 0.00 01-FEB-00:10 16.65
March 0.00 0.00 01-MAR-00:10 17.32
April 0.00 0.00 01-APR-00:02 22.57
May 0.00 0.00 01-MAY-00:05 22.05
June 0.00 0.00 01-JUN-00:02 26.68
July 0.00 0.00 01-JUL-00:03 26.83
August 0.00 0.00 01-AUG-00:05 28.60
September 0.00 0.00 01-SEP-00:03 27.05
October 0.00 0.00 01-OCT-00:03 27.93
November 0.00 0.00 01-NOV-00:10 22.40
December 0.00 0.00 01-DEC-00:10 24.10
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   16.65
Maximum of Months 0.00 0.00   28.60



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 11827241.48 12029.42 25-JAN-06:03 9.40
February 36516381.72 12790.35 04-FEB-05:11 5.93
March 10856006.76 12052.51 16-MAR-05:03 6.70
April 0.00 0.00 01-APR-00:02 22.57
May 0.00 0.00 01-MAY-00:05 22.05
June 0.00 0.00 01-JUN-00:02 26.68
July 0.00 0.00 01-JUL-00:03 26.83
August 0.00 0.00 01-AUG-00:05 28.60
September 0.00 0.00 01-SEP-00:03 27.05
October 0.00 0.00 01-OCT-00:03 27.93
November 0.00 0.00 01-NOV-00:10 22.40
December 12072729.10 12029.78 15-DEC-06:02 7.80
         
Annual Sum or Average 71272359.06      
Minimum of Months 0.00 0.00   5.93
Maximum of Months 36516381.72 12790.35   28.60



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 2234703.00 4154.93 25-JAN-06:03 9.40
February 13882295.37 9468.34 04-FEB-05:11 5.93
March 1757361.90 3283.26 16-MAR-05:03 6.70
April 0.00 0.00 01-APR-00:02 22.57
May 0.00 0.00 01-MAY-00:05 22.05
June 0.00 0.00 01-JUN-00:02 26.68
July 0.00 0.00 01-JUL-00:03 26.83
August 0.00 0.00 01-AUG-00:05 28.60
September 0.00 0.00 01-SEP-00:03 27.05
October 0.00 0.00 01-OCT-00:03 27.93
November 0.00 0.00 01-NOV-00:10 22.40
December 3074262.56 6196.29 15-DEC-06:02 7.80
         
Annual Sum or Average 20948622.84      
Minimum of Months 0.00 0.00   5.93
Maximum of Months 13882295.37 9468.34   28.60



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:05 20.40
February 9398262.05 11849.15 04-FEB-06:02 5.50
March 0.00 0.00 01-MAR-00:10 17.32
April 0.00 0.00 01-APR-00:02 22.57
May 0.00 0.00 01-MAY-00:05 22.05
June 0.00 0.00 01-JUN-00:02 26.68
July 0.00 0.00 01-JUL-00:03 26.83
August 0.00 0.00 01-AUG-00:05 28.60
September 0.00 0.00 01-SEP-00:03 27.05
October 0.00 0.00 01-OCT-00:03 27.93
November 0.00 0.00 01-NOV-00:10 22.40
December 0.00 0.00 01-DEC-00:10 24.10
         
Annual Sum or Average 9398262.05      
Minimum of Months 0.00 0.00   5.50
Maximum of Months 9398262.05 11849.15   28.60



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:05 20.40
February 14562054.90 8500.42 04-FEB-05:11 5.93
March 16332.91 108.89 16-MAR-05:05 6.70
April 0.00 0.00 01-APR-00:02 22.57
May 0.00 0.00 01-MAY-00:05 22.05
June 0.00 0.00 01-JUN-00:02 26.68
July 0.00 0.00 01-JUL-00:03 26.83
August 0.00 0.00 01-AUG-00:05 28.60
September 0.00 0.00 01-SEP-00:03 27.05
October 0.00 0.00 01-OCT-00:03 27.93
November 0.00 0.00 01-NOV-00:10 22.40
December 271503.84 2199.65 15-DEC-06:02 7.80
         
Annual Sum or Average 14849891.65      
Minimum of Months 0.00 0.00   5.93
Maximum of Months 14562054.90 8500.42   28.60



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.116626E+09 14571.43 25-JAN-05:12 9.40
February 0.109945E+09 15960.59 04-FEB-05:11 5.93
March 62554325.33 14736.16 16-MAR-04:12 7.43
April 0.00 0.00 01-APR-00:02 22.57
May 0.00 0.00 01-MAY-00:05 22.05
June 0.00 0.00 01-JUN-00:02 26.68
July 0.00 0.00 01-JUL-00:03 26.83
August 0.00 0.00 01-AUG-00:05 28.60
September 0.00 0.00 01-SEP-00:03 27.05
October 0.00 0.00 01-OCT-00:03 27.93
November 25323354.02 14095.52 13-NOV-06:02 12.20
December 0.127177E+09 14599.09 15-DEC-05:12 7.80
         
Annual Sum or Average 0.441626E+09      
Minimum of Months 0.00 0.00   5.93
Maximum of Months 0.127177E+09 15960.59   28.60



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 37849919.06 10333.25 26-JAN-06:02 10.60
February 37923622.83 12305.58 04-FEB-05:11 5.93
March 17223593.94 9887.13 16-MAR-05:03 6.70
April 0.00 0.00 01-APR-00:02 22.57
May 0.00 0.00 01-MAY-00:05 22.05
June 0.00 0.00 01-JUN-00:02 26.68
July 0.00 0.00 01-JUL-00:03 26.83
August 0.00 0.00 01-AUG-00:05 28.60
September 0.00 0.00 01-SEP-00:03 27.05
October 0.00 0.00 01-OCT-00:03 27.93
November 7297586.45 10405.62 13-NOV-06:02 12.20
December 60949340.07 10313.55 15-DEC-06:02 7.80
         
Annual Sum or Average 0.161244E+09      
Minimum of Months 0.00 0.00   5.93
Maximum of Months 60949340.07 12305.58   28.60



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 15236886.66 12936.15 25-JAN-06:03 9.40
February 47429219.74 15247.50 04-FEB-05:11 5.93
March 17566957.05 13721.06 16-MAR-05:03 6.70
April 0.00 0.00 01-APR-00:02 22.57
May 0.00 0.00 01-MAY-00:05 22.05
June 0.00 0.00 01-JUN-00:02 26.68
July 0.00 0.00 01-JUL-00:03 26.83
August 0.00 0.00 01-AUG-00:05 28.60
September 0.00 0.00 01-SEP-00:03 27.05
October 0.00 0.00 01-OCT-00:03 27.93
November 4305699.45 13721.65 13-NOV-06:02 12.20
December 29061242.91 13830.48 27-DEC-06:02 8.90
         
Annual Sum or Average 0.113600E+09      
Minimum of Months 0.00 0.00   5.93
Maximum of Months 47429219.74 15247.50   28.60



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 21460438.70 9878.91 26-JAN-06:02 10.60
February 46470083.55 11831.74 04-FEB-05:11 5.93
March 10391750.49 9056.07 16-MAR-05:03 6.70
April 0.00 0.00 01-APR-00:02 22.57
May 0.00 0.00 01-MAY-00:05 22.05
June 0.00 0.00 01-JUN-00:02 26.68
July 0.00 0.00 01-JUL-00:03 26.83
August 0.00 0.00 01-AUG-00:05 28.60
September 0.00 0.00 01-SEP-00:03 27.05
October 0.00 0.00 01-OCT-00:03 27.93
November 4580649.62 9892.14 13-NOV-06:02 12.20
December 35092558.68 9955.25 15-DEC-06:02 7.80
         
Annual Sum or Average 0.117995E+09      
Minimum of Months 0.00 0.00   5.93
Maximum of Months 46470083.55 11831.74   28.60



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: GROUNDFLOOR_PLENUM

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 58423693.81 9125.64 23-JAN-05:12 12.57
February 56039899.07 11054.87 06-FEB-05:12 17.97
March 57720025.92 11067.92 20-MAR-04:12 12.20
April 44534809.61 9160.13 19-APR-04:12 15.00
May 20113589.69 6884.24 08-MAY-04:11 23.50
June 12644417.26 4775.00 13-JUN-03:02 24.32
July 20642644.48 5433.23 09-JUL-16:31 30.37
August 23099247.13 6212.91 06-AUG-14:22 31.95
September 20922151.96 5290.41 26-SEP-04:12 23.30
October 35036162.80 7577.91 27-OCT-04:11 22.80
November 61292315.12 10250.25 28-NOV-05:12 20.93
December 86717644.91 14389.94 18-DEC-05:12 17.20
         
Annual Sum or Average 0.497187E+09      
Minimum of Months 12644417.26 4775.00   12.20
Maximum of Months 86717644.91 14389.94   31.95



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: MIDFLOOR_PLENUM

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 38309038.73 6699.57 24-JAN-06:02 12.12
February 41545436.66 7565.32 13-FEB-05:11 20.20
March 22672607.41 7292.75 20-MAR-04:17 12.20
April 22407593.62 5078.48 20-APR-04:11 20.77
May 17285828.96 5502.32 29-MAY-16:21 32.50
June 12977258.36 4821.03 20-JUN-03:02 25.50
July 18967497.63 5092.76 03-JUL-03:02 25.50
August 16833383.17 5928.05 28-AUG-03:02 25.68
September 19773433.84 5167.53 29-SEP-03:02 26.42
October 24558750.29 5363.68 02-OCT-03:02 26.70
November 23550116.46 8087.36 13-NOV-05:12 12.60
December 33734701.90 6762.48 22-DEC-06:03 17.80
         
Annual Sum or Average 0.292616E+09      
Minimum of Months 12977258.36 4821.03   12.12
Maximum of Months 41545436.66 8087.36   32.50



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: TOPFLOOR_PLENUM

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.538666E+09 12607.01 05-JAN-06:02 16.70
February 0.339709E+09 14241.91 28-FEB-06:03 16.88
March 0.363482E+09 12326.48 15-MAR-05:03 12.12
April 58782793.96 13790.66 19-APR-05:03 15.10
May 31908269.09 11181.69 01-MAY-04:12 20.93
June 20186400.90 8914.26 06-JUN-04:12 23.50
July 23253061.47 10355.83 07-JUL-04:12 23.30
August 20163129.58 7523.63 29-AUG-04:02 23.80
September 26533706.70 11836.88 05-SEP-04:11 23.30
October 36689275.11 11252.67 20-OCT-04:11 21.70
November 0.133408E+09 10798.41 15-NOV-06:03 18.80
December 0.453855E+09 12035.30 04-DEC-06:03 17.20
         
Annual Sum or Average 0.204664E+10      
Minimum of Months 20163129.58 7523.63   12.12
Maximum of Months 0.538666E+09 14241.91   23.80



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:05 20.40
February 0.00 0.00 01-FEB-00:10 16.65
March 0.00 0.00 01-MAR-00:10 17.32
April 0.00 0.00 01-APR-00:02 22.57
May 0.00 0.00 01-MAY-00:05 22.05
June 0.00 0.00 01-JUN-00:02 26.68
July 0.00 0.00 01-JUL-00:03 26.83
August 0.00 0.00 01-AUG-00:05 28.60
September 0.00 0.00 01-SEP-00:03 27.05
October 0.00 0.00 01-OCT-00:03 27.93
November 0.00 0.00 01-NOV-00:10 22.40
December 0.00 0.00 01-DEC-00:10 24.10
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   16.65
Maximum of Months 0.00 0.00   28.60



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: DATACENTER_MID_ZN_6

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:05 20.40
February 0.00 0.00 01-FEB-00:10 16.65
March 0.00 0.00 01-MAR-00:10 17.32
April 0.00 0.00 01-APR-00:02 22.57
May 0.00 0.00 01-MAY-00:05 22.05
June 0.00 0.00 01-JUN-00:02 26.68
July 0.00 0.00 01-JUL-00:03 26.83
August 0.00 0.00 01-AUG-00:05 28.60
September 0.00 0.00 01-SEP-00:03 27.05
October 0.00 0.00 01-OCT-00:03 27.93
November 0.00 0.00 01-NOV-00:10 22.40
December 0.00 0.00 01-DEC-00:10 24.10
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   16.65
Maximum of Months 0.00 0.00   28.60



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 1066349.13 192.10 22-JAN-08:30 13.85
February 0.00 0.00 01-FEB-00:10 16.65
March 0.00 0.00 01-MAR-00:10 17.32
April 0.00 0.00 01-APR-00:02 22.57
May 0.00 0.00 01-MAY-00:05 22.05
June 0.00 0.00 01-JUN-00:02 26.68
July 0.00 0.00 01-JUL-00:03 26.83
August 0.00 0.00 01-AUG-00:05 28.60
September 0.00 0.00 01-SEP-00:03 27.05
October 0.00 0.00 01-OCT-00:03 27.93
November 0.00 0.00 01-NOV-00:10 22.40
December 0.00 0.00 01-DEC-00:10 24.10
         
Annual Sum or Average 1066349.13      
Minimum of Months 0.00 0.00   13.85
Maximum of Months 1066349.13 192.10   28.60



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:05 20.40
February 0.00 0.00 01-FEB-00:10 16.65
March 0.00 0.00 01-MAR-00:10 17.32
April 0.00 0.00 01-APR-00:02 22.57
May 0.00 0.00 01-MAY-00:05 22.05
June 0.00 0.00 01-JUN-00:02 26.68
July 0.00 0.00 01-JUL-00:03 26.83
August 0.00 0.00 01-AUG-00:05 28.60
September 0.00 0.00 01-SEP-00:03 27.05
October 0.00 0.00 01-OCT-00:03 27.93
November 0.00 0.00 01-NOV-00:10 22.40
December 0.00 0.00 01-DEC-00:10 24.10
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   16.65
Maximum of Months 0.00 0.00   28.60



Table of Contents

Report: ZoneElectricSummaryMonthly

For: BASEMENT

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.219312E+11 22950.34 02-JAN-08:09 0.360447E+11 13457.54 01-JAN-00:10
February 0.198933E+11 22950.34 01-FEB-08:09 0.325565E+11 13457.54 01-FEB-00:10
March 0.236388E+11 22950.34 01-MAR-08:09 0.360447E+11 13457.54 01-MAR-00:10
April 0.211142E+11 22950.34 03-APR-07:10 0.348820E+11 13457.54 01-APR-00:10
May 0.227850E+11 22950.34 01-MAY-07:10 0.360447E+11 13457.54 01-MAY-00:10
June 0.226748E+11 22950.34 01-JUN-07:10 0.348820E+11 13457.54 01-JUN-00:10
July 0.212244E+11 22950.34 03-JUL-07:10 0.360447E+11 13457.54 01-JUL-00:10
August 0.236388E+11 22950.34 01-AUG-07:10 0.360447E+11 13457.54 01-AUG-00:10
September 0.211142E+11 22950.34 01-SEP-07:10 0.348820E+11 13457.54 01-SEP-00:10
October 0.219312E+11 22950.34 02-OCT-07:10 0.360447E+11 13457.54 01-OCT-00:10
November 0.216742E+11 22950.34 01-NOV-07:10 0.348820E+11 13457.54 01-NOV-00:10
December 0.212244E+11 22950.34 01-DEC-08:09 0.360447E+11 13457.54 01-DEC-00:10
             
Annual Sum or Average 0.262844E+12     0.424397E+12    
Minimum of Months 0.198933E+11 22950.34   0.325565E+11 13457.54  
Maximum of Months 0.236388E+11 22950.34   0.360447E+11 13457.54  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: CORE_BOTTOM

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.196958E+11 20611.01 02-JAN-08:09 0.243681E+11 17206.63 02-JAN-08:09
February 0.178655E+11 20611.01 01-FEB-08:09 0.220609E+11 17206.63 01-FEB-08:09
March 0.212293E+11 20611.01 01-MAR-08:09 0.253549E+11 17206.63 01-MAR-08:09
April 0.189620E+11 20611.01 03-APR-07:10 0.235306E+11 17206.63 03-APR-07:10
May 0.204625E+11 20611.01 01-MAY-07:10 0.248615E+11 17206.63 01-MAY-07:10
June 0.203636E+11 20611.01 01-JUN-07:10 0.244160E+11 17206.63 01-JUN-07:10
July 0.190610E+11 20611.01 03-JUL-07:10 0.239708E+11 17206.63 03-JUL-07:10
August 0.212293E+11 20611.01 01-AUG-07:10 0.253549E+11 17206.63 01-AUG-07:10
September 0.189620E+11 20611.01 01-SEP-07:10 0.235199E+11 17206.63 01-SEP-07:10
October 0.196958E+11 20611.01 02-OCT-07:10 0.243735E+11 17206.63 02-OCT-07:10
November 0.194649E+11 20611.01 01-NOV-07:10 0.238373E+11 17206.63 01-NOV-07:10
December 0.190610E+11 20611.01 01-DEC-08:09 0.239654E+11 17206.63 01-DEC-08:09
             
Annual Sum or Average 0.236053E+12     0.289614E+12    
Minimum of Months 0.178655E+11 20611.01   0.220609E+11 17206.63  
Maximum of Months 0.212293E+11 20611.01   0.253549E+11 17206.63  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: CORE_MID

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.196958E+11 20611.01 02-JAN-08:09 0.243680E+11 17206.56 02-JAN-08:09
February 0.178655E+11 20611.01 01-FEB-08:09 0.220609E+11 17206.56 01-FEB-08:09
March 0.212293E+11 20611.01 01-MAR-08:09 0.253548E+11 17206.56 01-MAR-08:09
April 0.189620E+11 20611.01 03-APR-07:10 0.235305E+11 17206.56 03-APR-07:10
May 0.204625E+11 20611.01 01-MAY-07:10 0.248614E+11 17206.56 01-MAY-07:10
June 0.203636E+11 20611.01 01-JUN-07:10 0.244159E+11 17206.56 01-JUN-07:10
July 0.190610E+11 20611.01 03-JUL-07:10 0.239707E+11 17206.56 03-JUL-07:10
August 0.212293E+11 20611.01 01-AUG-07:10 0.253548E+11 17206.56 01-AUG-07:10
September 0.189620E+11 20611.01 01-SEP-07:10 0.235198E+11 17206.56 01-SEP-07:10
October 0.196958E+11 20611.01 02-OCT-07:10 0.243734E+11 17206.56 02-OCT-07:10
November 0.194649E+11 20611.01 01-NOV-07:10 0.238372E+11 17206.56 01-NOV-07:10
December 0.190610E+11 20611.01 01-DEC-08:09 0.239653E+11 17206.56 01-DEC-08:09
             
Annual Sum or Average 0.236053E+12     0.289613E+12    
Minimum of Months 0.178655E+11 20611.01   0.220609E+11 17206.56  
Maximum of Months 0.212293E+11 20611.01   0.253548E+11 17206.56  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: CORE_TOP

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.196958E+11 20611.01 02-JAN-08:09 0.243680E+11 17206.56 02-JAN-08:09
February 0.178655E+11 20611.01 01-FEB-08:09 0.220609E+11 17206.56 01-FEB-08:09
March 0.212293E+11 20611.01 01-MAR-08:09 0.253548E+11 17206.56 01-MAR-08:09
April 0.189620E+11 20611.01 03-APR-07:10 0.235305E+11 17206.56 03-APR-07:10
May 0.204625E+11 20611.01 01-MAY-07:10 0.248614E+11 17206.56 01-MAY-07:10
June 0.203636E+11 20611.01 01-JUN-07:10 0.244159E+11 17206.56 01-JUN-07:10
July 0.190610E+11 20611.01 03-JUL-07:10 0.239707E+11 17206.56 03-JUL-07:10
August 0.212293E+11 20611.01 01-AUG-07:10 0.253548E+11 17206.56 01-AUG-07:10
September 0.189620E+11 20611.01 01-SEP-07:10 0.235198E+11 17206.56 01-SEP-07:10
October 0.196958E+11 20611.01 02-OCT-07:10 0.243734E+11 17206.56 02-OCT-07:10
November 0.194649E+11 20611.01 01-NOV-07:10 0.238372E+11 17206.56 01-NOV-07:10
December 0.190610E+11 20611.01 01-DEC-08:09 0.239653E+11 17206.56 01-DEC-08:09
             
Annual Sum or Average 0.236053E+12     0.289613E+12    
Minimum of Months 0.178655E+11 20611.01   0.220609E+11 17206.56  
Maximum of Months 0.212293E+11 20611.01   0.253548E+11 17206.56  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.155608E+10 2255.20 04-JAN-16:30 0.305979E+10 2160.55 02-JAN-08:09
February 0.134429E+10 1803.00 03-FEB-16:00 0.277008E+10 2160.55 01-FEB-08:09
March 0.152761E+10 2135.72 15-MAR-07:10 0.318369E+10 2160.55 01-MAR-08:09
April 0.133733E+10 1803.00 12-APR-07:10 0.295462E+10 2160.55 03-APR-07:10
May 0.140758E+10 1470.28 25-MAY-07:10 0.312174E+10 2160.55 01-MAY-07:10
June 0.139904E+10 2255.20 15-JUN-07:10 0.306580E+10 2160.55 01-JUN-07:10
July 0.130500E+10 1470.28 05-JUL-07:10 0.300989E+10 2160.55 03-JUL-07:10
August 0.147509E+10 1803.00 28-AUG-07:10 0.318369E+10 2160.55 01-AUG-07:10
September 0.136495E+10 2587.92 27-SEP-07:10 0.295328E+10 2160.55 01-SEP-07:10
October 0.146267E+10 2255.20 18-OCT-07:10 0.306046E+10 2160.55 02-OCT-07:10
November 0.150167E+10 2255.20 10-NOV-16:00 0.299314E+10 2160.55 01-NOV-07:10
December 0.152662E+10 2587.92 15-DEC-16:30 0.300922E+10 2160.55 01-DEC-08:09
             
Annual Sum or Average 0.172079E+11     0.363654E+11    
Minimum of Months 0.130500E+10 1470.28   0.277008E+10 2160.55  
Maximum of Months 0.155608E+10 2587.92   0.318369E+10 2160.55  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.978000E+09 1453.34 04-JAN-16:30 0.197184E+10 1392.34 02-JAN-08:09
February 0.856952E+09 1161.92 01-FEB-16:00 0.178515E+10 1392.34 01-FEB-08:09
March 0.972653E+09 947.51 06-MAR-16:00 0.205169E+10 1392.34 01-MAR-08:09
April 0.862224E+09 1161.92 12-APR-07:10 0.190407E+10 1392.34 03-APR-07:10
May 0.914164E+09 870.51 10-MAY-14:20 0.201177E+10 1392.34 01-MAY-07:10
June 0.910731E+09 1453.34 15-JUN-07:10 0.197572E+10 1392.34 01-JUN-07:10
July 0.848671E+09 870.51 05-JUL-07:10 0.193969E+10 1392.34 03-JUL-07:10
August 0.951322E+09 1161.92 28-AUG-07:10 0.205169E+10 1392.34 01-AUG-07:10
September 0.878172E+09 1667.75 27-SEP-07:10 0.190321E+10 1392.34 01-SEP-07:10
October 0.927004E+09 1453.34 18-OCT-07:10 0.197228E+10 1392.34 02-OCT-07:10
November 0.956291E+09 1453.34 10-NOV-16:49 0.192889E+10 1392.34 01-NOV-07:10
December 0.968600E+09 1667.75 15-DEC-16:30 0.193926E+10 1392.34 01-DEC-08:09
             
Annual Sum or Average 0.110248E+11     0.234352E+11    
Minimum of Months 0.848671E+09 870.51   0.178515E+10 1392.34  
Maximum of Months 0.978000E+09 1667.75   0.205169E+10 1392.34  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.146558E+10 2255.25 04-JAN-16:49 0.305983E+10 2160.58 02-JAN-08:09
February 0.130163E+10 1470.31 08-FEB-16:40 0.277013E+10 2160.58 01-FEB-08:09
March 0.150809E+10 1803.04 13-MAR-07:10 0.318374E+10 2160.58 01-MAR-08:09
April 0.134196E+10 1803.04 12-APR-07:10 0.295467E+10 2160.58 03-APR-07:10
May 0.142580E+10 1470.31 25-MAY-07:10 0.312179E+10 2160.58 01-MAY-07:10
June 0.142808E+10 2255.25 15-JUN-07:10 0.306585E+10 2160.58 01-JUN-07:10
July 0.132364E+10 1470.31 05-JUL-07:10 0.300994E+10 2160.58 03-JUL-07:10
August 0.148321E+10 1803.04 28-AUG-07:10 0.318374E+10 2160.58 01-AUG-07:10
September 0.135921E+10 2587.98 27-SEP-07:10 0.295333E+10 2160.58 01-SEP-07:10
October 0.142707E+10 2255.25 18-OCT-07:10 0.306051E+10 2160.58 02-OCT-07:10
November 0.144131E+10 2255.25 29-NOV-16:00 0.299318E+10 2160.58 01-NOV-07:10
December 0.145014E+10 2587.98 15-DEC-16:40 0.300927E+10 2160.58 01-DEC-08:09
             
Annual Sum or Average 0.169557E+11     0.363660E+11    
Minimum of Months 0.130163E+10 1470.31   0.277013E+10 2160.58  
Maximum of Months 0.150809E+10 2587.98   0.318374E+10 2160.58  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.966155E+09 1453.34 04-JAN-16:49 0.197183E+10 1392.33 02-JAN-08:09
February 0.848178E+09 1161.92 01-FEB-08:09 0.178514E+10 1392.33 01-FEB-08:09
March 0.982490E+09 1453.34 14-MAR-07:10 0.205168E+10 1392.33 01-MAR-08:09
April 0.861135E+09 1453.34 12-APR-07:10 0.190406E+10 1392.33 03-APR-07:10
May 0.917287E+09 1161.92 25-MAY-07:10 0.201175E+10 1392.33 01-MAY-07:10
June 0.915555E+09 1667.75 15-JUN-07:10 0.197570E+10 1392.33 01-JUN-07:10
July 0.851828E+09 1161.92 05-JUL-07:10 0.193968E+10 1392.33 03-JUL-07:10
August 0.959102E+09 1453.34 28-AUG-07:10 0.205168E+10 1392.33 01-AUG-07:10
September 0.880731E+09 1667.75 27-SEP-07:10 0.190319E+10 1392.33 01-SEP-07:10
October 0.935934E+09 1453.34 18-OCT-07:10 0.197226E+10 1392.33 02-OCT-07:10
November 0.941668E+09 1453.34 03-NOV-07:10 0.192888E+10 1392.33 01-NOV-07:10
December 0.947339E+09 1667.75 15-DEC-16:40 0.193924E+10 1392.33 01-DEC-08:09
             
Annual Sum or Average 0.110074E+11     0.234351E+11    
Minimum of Months 0.848178E+09 1161.92   0.178514E+10 1392.33  
Maximum of Months 0.982490E+09 1667.75   0.205168E+10 1392.33  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.154804E+10 2255.20 04-JAN-16:40 0.305979E+10 2160.55 02-JAN-08:09
February 0.133903E+10 1803.00 03-FEB-16:00 0.277008E+10 2160.55 01-FEB-08:09
March 0.152320E+10 2135.72 15-MAR-07:10 0.318369E+10 2160.55 01-MAR-08:09
April 0.133582E+10 1803.00 12-APR-07:10 0.295462E+10 2160.55 03-APR-07:10
May 0.140640E+10 1470.28 25-MAY-07:10 0.312174E+10 2160.55 01-MAY-07:10
June 0.139590E+10 2255.20 15-JUN-07:10 0.306580E+10 2160.55 01-JUN-07:10
July 0.130374E+10 1470.28 05-JUL-07:10 0.300989E+10 2160.55 03-JUL-07:10
August 0.147370E+10 1803.00 28-AUG-07:10 0.318369E+10 2160.55 01-AUG-07:10
September 0.136206E+10 2587.92 27-SEP-07:10 0.295328E+10 2160.55 01-SEP-07:10
October 0.145805E+10 2255.20 18-OCT-07:10 0.306046E+10 2160.55 02-OCT-07:10
November 0.149611E+10 2255.20 21-NOV-16:00 0.299314E+10 2160.55 01-NOV-07:10
December 0.152136E+10 2587.92 15-DEC-16:30 0.300922E+10 2160.55 01-DEC-08:09
             
Annual Sum or Average 0.171634E+11     0.363654E+11    
Minimum of Months 0.130374E+10 1470.28   0.277008E+10 2160.55  
Maximum of Months 0.154804E+10 2587.92   0.318369E+10 2160.55  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.975956E+09 1453.34 04-JAN-16:30 0.197184E+10 1392.34 02-JAN-08:09
February 0.854981E+09 1161.92 01-FEB-16:00 0.178515E+10 1392.34 01-FEB-08:09
March 0.971761E+09 947.51 14-MAR-07:10 0.205169E+10 1392.34 01-MAR-08:09
April 0.861606E+09 1161.92 12-APR-07:10 0.190407E+10 1392.34 03-APR-07:10
May 0.913092E+09 870.51 10-MAY-14:20 0.201177E+10 1392.34 01-MAY-07:10
June 0.909114E+09 1453.34 15-JUN-07:10 0.197572E+10 1392.34 01-JUN-07:10
July 0.847382E+09 870.51 05-JUL-07:10 0.193969E+10 1392.34 03-JUL-07:10
August 0.950134E+09 1161.92 28-AUG-07:10 0.205169E+10 1392.34 01-AUG-07:10
September 0.876986E+09 1667.75 27-SEP-07:10 0.190321E+10 1392.34 01-SEP-07:10
October 0.925803E+09 1453.34 18-OCT-07:10 0.197228E+10 1392.34 02-OCT-07:10
November 0.953715E+09 1453.34 10-NOV-16:00 0.192889E+10 1392.34 01-NOV-07:10
December 0.965929E+09 1667.75 15-DEC-16:30 0.193926E+10 1392.34 01-DEC-08:09
             
Annual Sum or Average 0.110065E+11     0.234352E+11    
Minimum of Months 0.847382E+09 870.51   0.178515E+10 1392.34  
Maximum of Months 0.975956E+09 1667.75   0.205169E+10 1392.34  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.146453E+10 2255.25 04-JAN-16:49 0.305983E+10 2160.58 02-JAN-08:09
February 0.130047E+10 1470.31 08-FEB-16:40 0.277013E+10 2160.58 01-FEB-08:09
March 0.150564E+10 1803.04 13-MAR-07:10 0.318374E+10 2160.58 01-MAR-08:09
April 0.134062E+10 1803.04 12-APR-07:10 0.295467E+10 2160.58 03-APR-07:10
May 0.142356E+10 1470.31 25-MAY-07:10 0.312179E+10 2160.58 01-MAY-07:10
June 0.142477E+10 2255.25 15-JUN-07:10 0.306585E+10 2160.58 01-JUN-07:10
July 0.132180E+10 1470.31 05-JUL-07:10 0.300994E+10 2160.58 03-JUL-07:10
August 0.148112E+10 1803.04 28-AUG-07:10 0.318374E+10 2160.58 01-AUG-07:10
September 0.135778E+10 2587.98 27-SEP-07:10 0.295333E+10 2160.58 01-SEP-07:10
October 0.142401E+10 2255.25 18-OCT-07:10 0.306051E+10 2160.58 02-OCT-07:10
November 0.143833E+10 2255.25 29-NOV-16:00 0.299318E+10 2160.58 01-NOV-07:10
December 0.144886E+10 2587.98 15-DEC-16:40 0.300927E+10 2160.58 01-DEC-08:09
             
Annual Sum or Average 0.169315E+11     0.363660E+11    
Minimum of Months 0.130047E+10 1470.31   0.277013E+10 2160.58  
Maximum of Months 0.150564E+10 2587.98   0.318374E+10 2160.58  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.964325E+09 1453.34 04-JAN-16:00 0.197183E+10 1392.33 02-JAN-08:09
February 0.846551E+09 1161.92 01-FEB-08:09 0.178514E+10 1392.33 01-FEB-08:09
March 0.980185E+09 1453.34 14-MAR-07:10 0.205168E+10 1392.33 01-MAR-08:09
April 0.860252E+09 1453.34 12-APR-07:10 0.190406E+10 1392.33 03-APR-07:10
May 0.915468E+09 1161.92 25-MAY-07:10 0.201175E+10 1392.33 01-MAY-07:10
June 0.913262E+09 1667.75 15-JUN-07:10 0.197570E+10 1392.33 01-JUN-07:10
July 0.849555E+09 1161.92 05-JUL-07:10 0.193968E+10 1392.33 03-JUL-07:10
August 0.957318E+09 1453.34 28-AUG-07:10 0.205168E+10 1392.33 01-AUG-07:10
September 0.878533E+09 1667.75 27-SEP-07:10 0.190319E+10 1392.33 01-SEP-07:10
October 0.934074E+09 1453.34 18-OCT-07:10 0.197226E+10 1392.33 02-OCT-07:10
November 0.939147E+09 1453.34 03-NOV-07:10 0.192888E+10 1392.33 01-NOV-07:10
December 0.945111E+09 1667.75 15-DEC-16:40 0.193924E+10 1392.33 01-DEC-08:09
             
Annual Sum or Average 0.109838E+11     0.234351E+11    
Minimum of Months 0.846551E+09 1161.92   0.178514E+10 1392.33  
Maximum of Months 0.980185E+09 1667.75   0.205168E+10 1392.33  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.154770E+10 2255.20 04-JAN-16:40 0.305979E+10 2160.55 02-JAN-08:09
February 0.133883E+10 1803.00 03-FEB-16:00 0.277008E+10 2160.55 01-FEB-08:09
March 0.152316E+10 2135.72 15-MAR-07:10 0.318369E+10 2160.55 01-MAR-08:09
April 0.133579E+10 1803.00 12-APR-07:10 0.295462E+10 2160.55 03-APR-07:10
May 0.140637E+10 1470.28 25-MAY-07:10 0.312174E+10 2160.55 01-MAY-07:10
June 0.139583E+10 2255.20 15-JUN-07:10 0.306580E+10 2160.55 01-JUN-07:10
July 0.130362E+10 1470.28 05-JUL-07:10 0.300989E+10 2160.55 03-JUL-07:10
August 0.147356E+10 1803.00 28-AUG-07:10 0.318369E+10 2160.55 01-AUG-07:10
September 0.136199E+10 2587.92 27-SEP-07:10 0.295328E+10 2160.55 01-SEP-07:10
October 0.145804E+10 2255.20 18-OCT-07:10 0.306046E+10 2160.55 02-OCT-07:10
November 0.149565E+10 2255.20 21-NOV-16:00 0.299314E+10 2160.55 01-NOV-07:10
December 0.152107E+10 2587.92 15-DEC-16:30 0.300922E+10 2160.55 01-DEC-08:09
             
Annual Sum or Average 0.171616E+11     0.363654E+11    
Minimum of Months 0.130362E+10 1470.28   0.277008E+10 2160.55  
Maximum of Months 0.154770E+10 2587.92   0.318369E+10 2160.55  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.975934E+09 1453.34 04-JAN-16:30 0.197184E+10 1392.34 02-JAN-08:09
February 0.854981E+09 1161.92 01-FEB-16:00 0.178515E+10 1392.34 01-FEB-08:09
March 0.971685E+09 947.51 14-MAR-07:10 0.205169E+10 1392.34 01-MAR-08:09
April 0.861606E+09 1161.92 12-APR-07:10 0.190407E+10 1392.34 03-APR-07:10
May 0.913051E+09 870.51 10-MAY-14:20 0.201177E+10 1392.34 01-MAY-07:10
June 0.909073E+09 1453.34 15-JUN-07:10 0.197572E+10 1392.34 01-JUN-07:10
July 0.847368E+09 870.51 05-JUL-07:10 0.193969E+10 1392.34 03-JUL-07:10
August 0.950111E+09 1161.92 28-AUG-07:10 0.205169E+10 1392.34 01-AUG-07:10
September 0.876980E+09 1667.75 27-SEP-07:10 0.190321E+10 1392.34 01-SEP-07:10
October 0.925731E+09 1453.34 18-OCT-07:10 0.197228E+10 1392.34 02-OCT-07:10
November 0.953537E+09 1453.34 10-NOV-16:00 0.192889E+10 1392.34 01-NOV-07:10
December 0.965911E+09 1667.75 15-DEC-16:30 0.193926E+10 1392.34 01-DEC-08:09
             
Annual Sum or Average 0.110060E+11     0.234352E+11    
Minimum of Months 0.847368E+09 870.51   0.178515E+10 1392.34  
Maximum of Months 0.975934E+09 1667.75   0.205169E+10 1392.34  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.146452E+10 2255.25 04-JAN-16:49 0.305983E+10 2160.58 02-JAN-08:09
February 0.130043E+10 1470.31 08-FEB-16:40 0.277013E+10 2160.58 01-FEB-08:09
March 0.150561E+10 1803.04 13-MAR-07:10 0.318374E+10 2160.58 01-MAR-08:09
April 0.134060E+10 1803.04 12-APR-07:10 0.295467E+10 2160.58 03-APR-07:10
May 0.142346E+10 1470.31 25-MAY-07:10 0.312179E+10 2160.58 01-MAY-07:10
June 0.142476E+10 2255.25 15-JUN-07:10 0.306585E+10 2160.58 01-JUN-07:10
July 0.132176E+10 1470.31 05-JUL-07:10 0.300994E+10 2160.58 03-JUL-07:10
August 0.148105E+10 1803.04 28-AUG-07:10 0.318374E+10 2160.58 01-AUG-07:10
September 0.135778E+10 2587.98 27-SEP-07:10 0.295333E+10 2160.58 01-SEP-07:10
October 0.142401E+10 2255.25 18-OCT-07:10 0.306051E+10 2160.58 02-OCT-07:10
November 0.143829E+10 2255.25 29-NOV-16:00 0.299318E+10 2160.58 01-NOV-07:10
December 0.144878E+10 2587.98 15-DEC-16:40 0.300927E+10 2160.58 01-DEC-08:09
             
Annual Sum or Average 0.169311E+11     0.363660E+11    
Minimum of Months 0.130043E+10 1470.31   0.277013E+10 2160.58  
Maximum of Months 0.150561E+10 2587.98   0.318374E+10 2160.58  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.964128E+09 1453.34 04-JAN-16:00 0.197183E+10 1392.33 02-JAN-08:09
February 0.846502E+09 1161.92 01-FEB-08:09 0.178514E+10 1392.33 01-FEB-08:09
March 0.980142E+09 1453.34 14-MAR-07:10 0.205168E+10 1392.33 01-MAR-08:09
April 0.860206E+09 1453.34 12-APR-07:10 0.190406E+10 1392.33 03-APR-07:10
May 0.915468E+09 1161.92 25-MAY-07:10 0.201175E+10 1392.33 01-MAY-07:10
June 0.913252E+09 1667.75 15-JUN-07:10 0.197570E+10 1392.33 01-JUN-07:10
July 0.849555E+09 1161.92 05-JUL-07:10 0.193968E+10 1392.33 03-JUL-07:10
August 0.957303E+09 1453.34 28-AUG-07:10 0.205168E+10 1392.33 01-AUG-07:10
September 0.878533E+09 1667.75 27-SEP-07:10 0.190319E+10 1392.33 01-SEP-07:10
October 0.934064E+09 1453.34 18-OCT-07:10 0.197226E+10 1392.33 02-OCT-07:10
November 0.939145E+09 1453.34 03-NOV-07:10 0.192888E+10 1392.33 01-NOV-07:10
December 0.945111E+09 1667.75 15-DEC-16:40 0.193924E+10 1392.33 01-DEC-08:09
             
Annual Sum or Average 0.109834E+11     0.234351E+11    
Minimum of Months 0.846502E+09 1161.92   0.178514E+10 1392.33  
Maximum of Months 0.980142E+09 1667.75   0.205168E+10 1392.33  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.553024E+09 578.72 02-JAN-08:09 0.521915E+10 1948.61 01-JAN-00:10
February 0.501634E+09 578.72 01-FEB-08:09 0.942813E+10 3897.21 01-FEB-00:10
March 0.596080E+09 578.72 01-MAR-08:09 0.156645E+11 7794.42 31-MAR-23:10
April 0.532421E+09 578.72 03-APR-07:10 0.201821E+11 7794.42 01-APR-00:10
May 0.574552E+09 578.72 01-MAY-07:10 0.522616E+10 3897.21 31-MAY-23:10
June 0.571774E+09 578.72 01-JUN-07:10 0.101086E+11 5845.82 30-JUN-23:10
July 0.535199E+09 578.72 03-JUL-07:10 0.156645E+11 7794.42 31-JUL-23:10
August 0.596080E+09 578.72 01-AUG-07:10 0.208555E+11 7794.42 01-AUG-00:10
September 0.532421E+09 578.72 01-SEP-07:10 0.505780E+10 3897.21 30-SEP-23:10
October 0.553024E+09 578.72 02-OCT-07:10 0.104453E+11 5845.82 31-OCT-23:10
November 0.546542E+09 578.72 01-NOV-07:10 0.151524E+11 5845.82 01-NOV-00:10
December 0.535199E+09 578.72 01-DEC-08:09 0.208766E+11 7794.42 01-DEC-00:10
             
Annual Sum or Average 0.662795E+10     0.153881E+12    
Minimum of Months 0.501634E+09 578.72   0.505780E+10 1948.61  
Maximum of Months 0.596080E+09 578.72   0.208766E+11 7794.42  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: DATACENTER_MID_ZN_6

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.553024E+09 578.72 02-JAN-08:09 0.521915E+10 1948.61 01-JAN-00:10
February 0.501634E+09 578.72 01-FEB-08:09 0.942813E+10 3897.21 01-FEB-00:10
March 0.596080E+09 578.72 01-MAR-08:09 0.156645E+11 7794.42 31-MAR-23:10
April 0.532421E+09 578.72 03-APR-07:10 0.201821E+11 7794.42 01-APR-00:10
May 0.574552E+09 578.72 01-MAY-07:10 0.522616E+10 3897.21 31-MAY-23:10
June 0.571774E+09 578.72 01-JUN-07:10 0.101086E+11 5845.82 30-JUN-23:10
July 0.535199E+09 578.72 03-JUL-07:10 0.156645E+11 7794.42 31-JUL-23:10
August 0.596080E+09 578.72 01-AUG-07:10 0.208555E+11 7794.42 01-AUG-00:10
September 0.532421E+09 578.72 01-SEP-07:10 0.505780E+10 3897.21 30-SEP-23:10
October 0.553024E+09 578.72 02-OCT-07:10 0.104453E+11 5845.82 31-OCT-23:10
November 0.546542E+09 578.72 01-NOV-07:10 0.151524E+11 5845.82 01-NOV-00:10
December 0.535199E+09 578.72 01-DEC-08:09 0.208766E+11 7794.42 01-DEC-00:10
             
Annual Sum or Average 0.662795E+10     0.153881E+12    
Minimum of Months 0.501634E+09 578.72   0.505780E+10 1948.61  
Maximum of Months 0.596080E+09 578.72   0.208766E+11 7794.42  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.553024E+09 578.72 02-JAN-08:09 0.521915E+10 1948.61 01-JAN-00:10
February 0.501634E+09 578.72 01-FEB-08:09 0.942813E+10 3897.21 01-FEB-00:10
March 0.596080E+09 578.72 01-MAR-08:09 0.156645E+11 7794.42 31-MAR-23:10
April 0.532421E+09 578.72 03-APR-07:10 0.201821E+11 7794.42 01-APR-00:10
May 0.574552E+09 578.72 01-MAY-07:10 0.522616E+10 3897.21 31-MAY-23:10
June 0.571774E+09 578.72 01-JUN-07:10 0.101086E+11 5845.82 30-JUN-23:10
July 0.535199E+09 578.72 03-JUL-07:10 0.156645E+11 7794.42 31-JUL-23:10
August 0.596080E+09 578.72 01-AUG-07:10 0.208555E+11 7794.42 01-AUG-00:10
September 0.532421E+09 578.72 01-SEP-07:10 0.505780E+10 3897.21 30-SEP-23:10
October 0.553024E+09 578.72 02-OCT-07:10 0.104453E+11 5845.82 31-OCT-23:10
November 0.546542E+09 578.72 01-NOV-07:10 0.151524E+11 5845.82 01-NOV-00:10
December 0.535199E+09 578.72 01-DEC-08:09 0.208766E+11 7794.42 01-DEC-00:10
             
Annual Sum or Average 0.662795E+10     0.153881E+12    
Minimum of Months 0.501634E+09 578.72   0.505780E+10 1948.61  
Maximum of Months 0.596080E+09 578.72   0.208766E+11 7794.42  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.618367E+10 6471.01 02-JAN-08:09 0.254202E+12 94908.13 01-JAN-00:10
February 0.560905E+10 6471.01 01-FEB-08:09 0.459203E+12 189816.26 01-FEB-00:10
March 0.666512E+10 6471.01 01-MAR-08:09 0.762947E+12 379632.52 31-MAR-23:10
April 0.595330E+10 6471.01 03-APR-07:10 0.982982E+12 379632.52 01-APR-00:10
May 0.642439E+10 6471.01 01-MAY-07:10 0.254544E+12 189816.26 31-MAY-23:10
June 0.639333E+10 6471.01 01-JUN-07:10 0.492345E+12 284724.39 30-JUN-23:10
July 0.598436E+10 6471.01 03-JUL-07:10 0.762947E+12 379632.52 31-JUL-23:10
August 0.666512E+10 6471.01 01-AUG-07:10 0.101578E+13 379632.52 01-AUG-00:10
September 0.595330E+10 6471.01 01-SEP-07:10 0.246344E+12 189816.26 30-SEP-23:10
October 0.618367E+10 6471.01 02-OCT-07:10 0.508746E+12 284724.39 31-OCT-23:10
November 0.611120E+10 6471.01 01-NOV-07:10 0.738006E+12 284724.39 01-NOV-00:10
December 0.598436E+10 6471.01 01-DEC-08:09 0.101681E+13 379632.52 01-DEC-00:10
             
Annual Sum or Average 0.741109E+11     0.749486E+13    
Minimum of Months 0.560905E+10 6471.01   0.246344E+12 94908.13  
Maximum of Months 0.666512E+10 6471.01   0.101681E+13 379632.52  



Table of Contents

Report: SpaceGainsMonthly

For: BASEMENT

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.133902E+11 0.219312E+11 0.360447E+11 0.00 0.00 0.00 0.00 0.00 0.00
February 0.121482E+11 0.198933E+11 0.325565E+11 0.00 0.00 0.00 0.00 0.00 0.00
March 0.145160E+11 0.236388E+11 0.360447E+11 0.00 0.00 0.00 0.00 0.00 0.00
April 0.128805E+11 0.211142E+11 0.348820E+11 0.00 0.00 0.00 0.00 0.00 0.00
May 0.139531E+11 0.227850E+11 0.360447E+11 0.00 0.00 0.00 0.00 0.00 0.00
June 0.139143E+11 0.226748E+11 0.348820E+11 0.00 0.00 0.00 0.00 0.00 0.00
July 0.129193E+11 0.212244E+11 0.360447E+11 0.00 0.00 0.00 0.00 0.00 0.00
August 0.145160E+11 0.236388E+11 0.360447E+11 0.00 0.00 0.00 0.00 0.00 0.00
September 0.128805E+11 0.211142E+11 0.348820E+11 0.00 0.00 0.00 0.00 0.00 0.00
October 0.133902E+11 0.219312E+11 0.360447E+11 0.00 0.00 0.00 0.00 0.00 0.00
November 0.132595E+11 0.216742E+11 0.348820E+11 0.00 0.00 0.00 0.00 0.00 0.00
December 0.129193E+11 0.212244E+11 0.360447E+11 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.160687E+12 0.262844E+12 0.424397E+12 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.121482E+11 0.198933E+11 0.325565E+11 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.145160E+11 0.236388E+11 0.360447E+11 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: CORE_BOTTOM

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.120254E+11 0.196958E+11 0.243681E+11 0.00 0.00 0.00 0.00 0.00 0.00
February 0.109099E+11 0.178655E+11 0.220609E+11 0.00 0.00 0.00 0.00 0.00 0.00
March 0.130364E+11 0.212293E+11 0.253549E+11 0.00 0.00 0.00 0.00 0.00 0.00
April 0.115676E+11 0.189620E+11 0.235306E+11 0.00 0.00 0.00 0.00 0.00 0.00
May 0.125309E+11 0.204625E+11 0.248615E+11 0.00 0.00 0.00 0.00 0.00 0.00
June 0.124961E+11 0.203636E+11 0.244160E+11 0.00 0.00 0.00 0.00 0.00 0.00
July 0.116025E+11 0.190610E+11 0.239708E+11 0.00 0.00 0.00 0.00 0.00 0.00
August 0.130364E+11 0.212293E+11 0.253549E+11 0.00 0.00 0.00 0.00 0.00 0.00
September 0.115676E+11 0.189620E+11 0.235199E+11 0.00 0.00 0.00 0.00 0.00 0.00
October 0.120254E+11 0.196958E+11 0.243735E+11 0.00 0.00 0.00 0.00 0.00 0.00
November 0.119080E+11 0.194649E+11 0.238373E+11 0.00 0.00 0.00 0.00 0.00 0.00
December 0.116025E+11 0.190610E+11 0.239654E+11 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.144308E+12 0.236053E+12 0.289614E+12 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.109099E+11 0.178655E+11 0.220609E+11 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.130364E+11 0.212293E+11 0.253549E+11 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: CORE_MID

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.120254E+11 0.196958E+11 0.243680E+11 0.00 0.00 0.00 0.00 0.00 0.00
February 0.109099E+11 0.178655E+11 0.220609E+11 0.00 0.00 0.00 0.00 0.00 0.00
March 0.130364E+11 0.212293E+11 0.253548E+11 0.00 0.00 0.00 0.00 0.00 0.00
April 0.115676E+11 0.189620E+11 0.235305E+11 0.00 0.00 0.00 0.00 0.00 0.00
May 0.125309E+11 0.204625E+11 0.248614E+11 0.00 0.00 0.00 0.00 0.00 0.00
June 0.124961E+11 0.203636E+11 0.244159E+11 0.00 0.00 0.00 0.00 0.00 0.00
July 0.116025E+11 0.190610E+11 0.239707E+11 0.00 0.00 0.00 0.00 0.00 0.00
August 0.130364E+11 0.212293E+11 0.253548E+11 0.00 0.00 0.00 0.00 0.00 0.00
September 0.115676E+11 0.189620E+11 0.235198E+11 0.00 0.00 0.00 0.00 0.00 0.00
October 0.120254E+11 0.196958E+11 0.243734E+11 0.00 0.00 0.00 0.00 0.00 0.00
November 0.119080E+11 0.194649E+11 0.238372E+11 0.00 0.00 0.00 0.00 0.00 0.00
December 0.116025E+11 0.190610E+11 0.239653E+11 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.144308E+12 0.236053E+12 0.289613E+12 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.109099E+11 0.178655E+11 0.220609E+11 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.130364E+11 0.212293E+11 0.253548E+11 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: CORE_TOP

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.120254E+11 0.196958E+11 0.243680E+11 0.00 0.00 0.00 0.00 0.00 0.00
February 0.109099E+11 0.178655E+11 0.220609E+11 0.00 0.00 0.00 0.00 0.00 0.00
March 0.130364E+11 0.212293E+11 0.253548E+11 0.00 0.00 0.00 0.00 0.00 0.00
April 0.115676E+11 0.189620E+11 0.235305E+11 0.00 0.00 0.00 0.00 0.00 0.00
May 0.125309E+11 0.204625E+11 0.248614E+11 0.00 0.00 0.00 0.00 0.00 0.00
June 0.124961E+11 0.203636E+11 0.244159E+11 0.00 0.00 0.00 0.00 0.00 0.00
July 0.116025E+11 0.190610E+11 0.239707E+11 0.00 0.00 0.00 0.00 0.00 0.00
August 0.130364E+11 0.212293E+11 0.253548E+11 0.00 0.00 0.00 0.00 0.00 0.00
September 0.115676E+11 0.189620E+11 0.235198E+11 0.00 0.00 0.00 0.00 0.00 0.00
October 0.120254E+11 0.196958E+11 0.243734E+11 0.00 0.00 0.00 0.00 0.00 0.00
November 0.119080E+11 0.194649E+11 0.238372E+11 0.00 0.00 0.00 0.00 0.00 0.00
December 0.116025E+11 0.190610E+11 0.239653E+11 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.144308E+12 0.236053E+12 0.289613E+12 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.109099E+11 0.178655E+11 0.220609E+11 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.130364E+11 0.212293E+11 0.253548E+11 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.150991E+10 0.155608E+10 0.305979E+10 0.00 0.00 0.00 0.00 6518922.91 0.167201E+09
February 0.136985E+10 0.134429E+10 0.277008E+10 0.00 0.00 0.00 0.00 12121136.24 0.228988E+09
March 0.163685E+10 0.152761E+10 0.318369E+10 0.00 0.00 0.00 0.00 14178398.75 0.191136E+09
April 0.145243E+10 0.133733E+10 0.295462E+10 0.00 0.00 0.00 0.00 32251929.27 66676320.90
May 0.157338E+10 0.140758E+10 0.312174E+10 0.00 0.00 0.00 0.00 81149542.44 28560070.58
June 0.156900E+10 0.139904E+10 0.306580E+10 0.00 0.00 0.00 0.00 0.100250E+09 5232548.32
July 0.145680E+10 0.130500E+10 0.300989E+10 0.00 0.00 0.00 0.00 90642330.73 4938790.75
August 0.163685E+10 0.147509E+10 0.318369E+10 0.00 0.00 0.00 0.00 0.109666E+09 2467993.83
September 0.145243E+10 0.136495E+10 0.295328E+10 0.00 0.00 0.00 0.00 0.100083E+09 8215917.51
October 0.150991E+10 0.146267E+10 0.306046E+10 0.00 0.00 0.00 0.00 68035670.34 15624242.47
November 0.149516E+10 0.150167E+10 0.299314E+10 0.00 0.00 0.00 0.00 31710884.13 0.134710E+09
December 0.145680E+10 0.152662E+10 0.300922E+10 0.00 0.00 0.00 0.00 9960208.59 0.167950E+09
                   
Annual Sum or Average 0.181194E+11 0.172079E+11 0.363654E+11 0.00 0.00 0.00 0.00 0.656568E+09 0.102170E+10
Minimum of Months 0.136985E+10 0.130500E+10 0.277008E+10 0.00 0.00 0.00 0.00 6518922.91 2467993.83
Maximum of Months 0.163685E+10 0.155608E+10 0.318369E+10 0.00 0.00 0.00 0.00 0.109666E+09 0.228988E+09



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.973041E+09 0.978000E+09 0.197184E+10 0.00 0.00 0.00 0.00 3910204.97 0.114114E+09
February 0.882782E+09 0.856952E+09 0.178515E+10 0.00 0.00 0.00 0.00 8136998.16 0.151873E+09
March 0.105485E+10 0.972653E+09 0.205169E+10 0.00 0.00 0.00 0.00 10186203.91 0.119781E+09
April 0.936002E+09 0.862224E+09 0.190407E+10 0.00 0.00 0.00 0.00 22037638.10 35781473.62
May 0.101394E+10 0.914164E+09 0.201177E+10 0.00 0.00 0.00 0.00 57654903.44 17503139.40
June 0.101113E+10 0.910731E+09 0.197572E+10 0.00 0.00 0.00 0.00 73149351.56 2388169.82
July 0.938820E+09 0.848671E+09 0.193969E+10 0.00 0.00 0.00 0.00 64803946.29 2320766.31
August 0.105485E+10 0.951322E+09 0.205169E+10 0.00 0.00 0.00 0.00 81460757.17 750835.08
September 0.936002E+09 0.878172E+09 0.190321E+10 0.00 0.00 0.00 0.00 67902590.63 4986636.19
October 0.973041E+09 0.927004E+09 0.197228E+10 0.00 0.00 0.00 0.00 48602966.38 8421116.93
November 0.963541E+09 0.956291E+09 0.192889E+10 0.00 0.00 0.00 0.00 25238952.87 87159551.35
December 0.938820E+09 0.968600E+09 0.193926E+10 0.00 0.00 0.00 0.00 8253414.68 0.101892E+09
                   
Annual Sum or Average 0.116768E+11 0.110248E+11 0.234352E+11 0.00 0.00 0.00 0.00 0.471338E+09 0.646973E+09
Minimum of Months 0.882782E+09 0.848671E+09 0.178515E+10 0.00 0.00 0.00 0.00 3910204.97 750835.08
Maximum of Months 0.105485E+10 0.978000E+09 0.205169E+10 0.00 0.00 0.00 0.00 81460757.17 0.151873E+09



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.150994E+10 0.146558E+10 0.305983E+10 0.00 0.00 0.00 0.00 4168855.18 0.193812E+09
February 0.136988E+10 0.130163E+10 0.277013E+10 0.00 0.00 0.00 0.00 9189368.39 0.260245E+09
March 0.163688E+10 0.150809E+10 0.318374E+10 0.00 0.00 0.00 0.00 12155062.41 0.210390E+09
April 0.145246E+10 0.134196E+10 0.295467E+10 0.00 0.00 0.00 0.00 27496760.66 72419279.04
May 0.157341E+10 0.142580E+10 0.312179E+10 0.00 0.00 0.00 0.00 81732397.41 28062617.25
June 0.156904E+10 0.142808E+10 0.306585E+10 0.00 0.00 0.00 0.00 0.102694E+09 5173047.08
July 0.145684E+10 0.132364E+10 0.300994E+10 0.00 0.00 0.00 0.00 92311140.32 4746861.16
August 0.163688E+10 0.148321E+10 0.318374E+10 0.00 0.00 0.00 0.00 0.108065E+09 2602699.89
September 0.145246E+10 0.135921E+10 0.295333E+10 0.00 0.00 0.00 0.00 91129905.19 9703692.51
October 0.150994E+10 0.142707E+10 0.306051E+10 0.00 0.00 0.00 0.00 54277303.62 22850734.62
November 0.149520E+10 0.144131E+10 0.299318E+10 0.00 0.00 0.00 0.00 23634148.56 0.159318E+09
December 0.145684E+10 0.145014E+10 0.300927E+10 0.00 0.00 0.00 0.00 5845584.74 0.189973E+09
                   
Annual Sum or Average 0.181198E+11 0.169557E+11 0.363660E+11 0.00 0.00 0.00 0.00 0.612700E+09 0.115930E+10
Minimum of Months 0.136988E+10 0.130163E+10 0.277013E+10 0.00 0.00 0.00 0.00 4168855.18 2602699.89
Maximum of Months 0.163688E+10 0.150809E+10 0.318374E+10 0.00 0.00 0.00 0.00 0.108065E+09 0.260245E+09



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.973041E+09 0.966155E+09 0.197183E+10 0.00 0.00 0.00 0.00 4077942.00 0.126279E+09
February 0.882782E+09 0.848178E+09 0.178514E+10 0.00 0.00 0.00 0.00 6631277.16 0.189408E+09
March 0.105485E+10 0.982490E+09 0.205168E+10 0.00 0.00 0.00 0.00 8396669.58 0.169806E+09
April 0.936002E+09 0.861135E+09 0.190406E+10 0.00 0.00 0.00 0.00 17034001.26 74147720.92
May 0.101394E+10 0.917287E+09 0.201175E+10 0.00 0.00 0.00 0.00 51411626.92 29257081.29
June 0.101113E+10 0.915555E+09 0.197570E+10 0.00 0.00 0.00 0.00 62143841.85 6122449.99
July 0.938820E+09 0.851828E+09 0.193968E+10 0.00 0.00 0.00 0.00 55196390.28 5857820.91
August 0.105485E+10 0.959102E+09 0.205168E+10 0.00 0.00 0.00 0.00 61755691.18 4112331.06
September 0.936002E+09 0.880731E+09 0.190319E+10 0.00 0.00 0.00 0.00 62169544.53 7841950.89
October 0.973041E+09 0.935934E+09 0.197226E+10 0.00 0.00 0.00 0.00 39651155.70 18644420.41
November 0.963541E+09 0.941668E+09 0.192888E+10 0.00 0.00 0.00 0.00 17112280.98 0.115341E+09
December 0.938820E+09 0.947339E+09 0.193924E+10 0.00 0.00 0.00 0.00 4788326.61 0.143710E+09
                   
Annual Sum or Average 0.116768E+11 0.110074E+11 0.234351E+11 0.00 0.00 0.00 0.00 0.390369E+09 0.890527E+09
Minimum of Months 0.882782E+09 0.848178E+09 0.178514E+10 0.00 0.00 0.00 0.00 4077942.00 4112331.06
Maximum of Months 0.105485E+10 0.982490E+09 0.205168E+10 0.00 0.00 0.00 0.00 62169544.53 0.189408E+09



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.150991E+10 0.154804E+10 0.305979E+10 0.00 0.00 0.00 0.00 21994527.05 0.319438E+09
February 0.136985E+10 0.133903E+10 0.277008E+10 0.00 0.00 0.00 0.00 33593334.12 0.432407E+09
March 0.163685E+10 0.152320E+10 0.318369E+10 0.00 0.00 0.00 0.00 34263294.61 0.401738E+09
April 0.145243E+10 0.133582E+10 0.295462E+10 0.00 0.00 0.00 0.00 76589436.83 0.181256E+09
May 0.157338E+10 0.140640E+10 0.312174E+10 0.00 0.00 0.00 0.00 0.176174E+09 77901498.97
June 0.156900E+10 0.139590E+10 0.306580E+10 0.00 0.00 0.00 0.00 0.210759E+09 23677840.91
July 0.145680E+10 0.130374E+10 0.300989E+10 0.00 0.00 0.00 0.00 0.199399E+09 20823702.30
August 0.163685E+10 0.147370E+10 0.318369E+10 0.00 0.00 0.00 0.00 0.238641E+09 11632300.67
September 0.145243E+10 0.136206E+10 0.295328E+10 0.00 0.00 0.00 0.00 0.222423E+09 23270582.78
October 0.150991E+10 0.145805E+10 0.306046E+10 0.00 0.00 0.00 0.00 0.147634E+09 48012954.19
November 0.149516E+10 0.149611E+10 0.299314E+10 0.00 0.00 0.00 0.00 66697822.62 0.270558E+09
December 0.145680E+10 0.152136E+10 0.300922E+10 0.00 0.00 0.00 0.00 27115234.79 0.324677E+09
                   
Annual Sum or Average 0.181194E+11 0.171634E+11 0.363654E+11 0.00 0.00 0.00 0.00 0.145529E+10 0.213539E+10
Minimum of Months 0.136985E+10 0.130374E+10 0.277008E+10 0.00 0.00 0.00 0.00 21994527.05 11632300.67
Maximum of Months 0.163685E+10 0.154804E+10 0.318369E+10 0.00 0.00 0.00 0.00 0.238641E+09 0.432407E+09



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.715730E+09 0.975956E+09 0.197184E+10 0.00 0.00 0.00 0.00 10372263.57 0.234717E+09
February 0.649041E+09 0.854981E+09 0.178515E+10 0.00 0.00 0.00 0.00 19280627.94 0.313120E+09
March 0.773965E+09 0.971761E+09 0.205169E+10 0.00 0.00 0.00 0.00 21170652.57 0.293369E+09
April 0.688021E+09 0.861606E+09 0.190407E+10 0.00 0.00 0.00 0.00 43570310.95 0.133508E+09
May 0.744847E+09 0.913092E+09 0.201177E+10 0.00 0.00 0.00 0.00 0.120133E+09 55185438.41
June 0.742030E+09 0.909114E+09 0.197572E+10 0.00 0.00 0.00 0.00 0.144553E+09 16944145.06
July 0.690839E+09 0.847382E+09 0.193969E+10 0.00 0.00 0.00 0.00 0.133086E+09 15341017.94
August 0.773965E+09 0.950134E+09 0.205169E+10 0.00 0.00 0.00 0.00 0.160310E+09 7975293.96
September 0.688021E+09 0.876986E+09 0.190321E+10 0.00 0.00 0.00 0.00 0.145911E+09 17104484.09
October 0.715730E+09 0.925803E+09 0.197228E+10 0.00 0.00 0.00 0.00 95516740.36 36050744.89
November 0.708685E+09 0.953715E+09 0.192889E+10 0.00 0.00 0.00 0.00 44322097.49 0.199461E+09
December 0.690839E+09 0.965929E+09 0.193926E+10 0.00 0.00 0.00 0.00 17842524.81 0.224259E+09
                   
Annual Sum or Average 0.858171E+10 0.110065E+11 0.234352E+11 0.00 0.00 0.00 0.00 0.956068E+09 0.154704E+10
Minimum of Months 0.649041E+09 0.847382E+09 0.178515E+10 0.00 0.00 0.00 0.00 10372263.57 7975293.96
Maximum of Months 0.773965E+09 0.975956E+09 0.205169E+10 0.00 0.00 0.00 0.00 0.160310E+09 0.313120E+09



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.150994E+10 0.146453E+10 0.305983E+10 0.00 0.00 0.00 0.00 8529479.93 0.434300E+09
February 0.136988E+10 0.130047E+10 0.277013E+10 0.00 0.00 0.00 0.00 19484452.18 0.569212E+09
March 0.163688E+10 0.150564E+10 0.318374E+10 0.00 0.00 0.00 0.00 26387445.24 0.491484E+09
April 0.145246E+10 0.134062E+10 0.295467E+10 0.00 0.00 0.00 0.00 62541358.17 0.206747E+09
May 0.157341E+10 0.142356E+10 0.312179E+10 0.00 0.00 0.00 0.00 0.178073E+09 77284155.47
June 0.156904E+10 0.142477E+10 0.306585E+10 0.00 0.00 0.00 0.00 0.217659E+09 22339490.46
July 0.145684E+10 0.132180E+10 0.300994E+10 0.00 0.00 0.00 0.00 0.204165E+09 19653089.31
August 0.163688E+10 0.148112E+10 0.318374E+10 0.00 0.00 0.00 0.00 0.232040E+09 12307962.72
September 0.145246E+10 0.135778E+10 0.295333E+10 0.00 0.00 0.00 0.00 0.198895E+09 28786973.16
October 0.150994E+10 0.142401E+10 0.306051E+10 0.00 0.00 0.00 0.00 0.113497E+09 77244415.82
November 0.149520E+10 0.143833E+10 0.299318E+10 0.00 0.00 0.00 0.00 46115660.51 0.375295E+09
December 0.145684E+10 0.144886E+10 0.300927E+10 0.00 0.00 0.00 0.00 12350305.43 0.436195E+09
                   
Annual Sum or Average 0.181198E+11 0.169315E+11 0.363660E+11 0.00 0.00 0.00 0.00 0.131974E+10 0.275085E+10
Minimum of Months 0.136988E+10 0.130047E+10 0.277013E+10 0.00 0.00 0.00 0.00 8529479.93 12307962.72
Maximum of Months 0.163688E+10 0.150564E+10 0.318374E+10 0.00 0.00 0.00 0.00 0.232040E+09 0.569212E+09



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.973041E+09 0.964325E+09 0.197183E+10 0.00 0.00 0.00 0.00 13981501.27 0.235560E+09
February 0.882782E+09 0.846551E+09 0.178514E+10 0.00 0.00 0.00 0.00 17893492.87 0.339479E+09
March 0.105485E+10 0.980185E+09 0.205168E+10 0.00 0.00 0.00 0.00 21381783.21 0.336083E+09
April 0.936002E+09 0.860252E+09 0.190406E+10 0.00 0.00 0.00 0.00 43654394.29 0.171591E+09
May 0.101394E+10 0.915468E+09 0.201175E+10 0.00 0.00 0.00 0.00 0.114307E+09 73811385.73
June 0.101113E+10 0.913262E+09 0.197570E+10 0.00 0.00 0.00 0.00 0.137287E+09 20895220.49
July 0.938820E+09 0.849555E+09 0.193968E+10 0.00 0.00 0.00 0.00 0.129299E+09 19035082.61
August 0.105485E+10 0.957318E+09 0.205168E+10 0.00 0.00 0.00 0.00 0.147916E+09 11358771.97
September 0.936002E+09 0.878533E+09 0.190319E+10 0.00 0.00 0.00 0.00 0.139017E+09 20267548.33
October 0.973041E+09 0.934074E+09 0.197226E+10 0.00 0.00 0.00 0.00 90293966.52 48671181.68
November 0.963541E+09 0.939147E+09 0.192888E+10 0.00 0.00 0.00 0.00 42092494.05 0.208390E+09
December 0.938820E+09 0.945111E+09 0.193924E+10 0.00 0.00 0.00 0.00 15314663.10 0.252719E+09
                   
Annual Sum or Average 0.116768E+11 0.109838E+11 0.234351E+11 0.00 0.00 0.00 0.00 0.912438E+09 0.173786E+10
Minimum of Months 0.882782E+09 0.846551E+09 0.178514E+10 0.00 0.00 0.00 0.00 13981501.27 11358771.97
Maximum of Months 0.105485E+10 0.980185E+09 0.205168E+10 0.00 0.00 0.00 0.00 0.147916E+09 0.339479E+09



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.150991E+10 0.154770E+10 0.305979E+10 0.00 0.00 0.00 0.00 27861666.31 0.361360E+09
February 0.136985E+10 0.133883E+10 0.277008E+10 0.00 0.00 0.00 0.00 40001160.58 0.497052E+09
March 0.163685E+10 0.152316E+10 0.318369E+10 0.00 0.00 0.00 0.00 38106744.98 0.479598E+09
April 0.145243E+10 0.133579E+10 0.295462E+10 0.00 0.00 0.00 0.00 86210663.39 0.223934E+09
May 0.157338E+10 0.140637E+10 0.312174E+10 0.00 0.00 0.00 0.00 0.204455E+09 0.105428E+09
June 0.156900E+10 0.139583E+10 0.306580E+10 0.00 0.00 0.00 0.00 0.247535E+09 33964221.20
July 0.145680E+10 0.130362E+10 0.300989E+10 0.00 0.00 0.00 0.00 0.233175E+09 29603356.97
August 0.163685E+10 0.147356E+10 0.318369E+10 0.00 0.00 0.00 0.00 0.281164E+09 15391684.94
September 0.145243E+10 0.136199E+10 0.295328E+10 0.00 0.00 0.00 0.00 0.259223E+09 30708830.48
October 0.150991E+10 0.145804E+10 0.306046E+10 0.00 0.00 0.00 0.00 0.172032E+09 60426189.69
November 0.149516E+10 0.149565E+10 0.299314E+10 0.00 0.00 0.00 0.00 77934961.07 0.303773E+09
December 0.145680E+10 0.152107E+10 0.300922E+10 0.00 0.00 0.00 0.00 31802465.19 0.371461E+09
                   
Annual Sum or Average 0.181194E+11 0.171616E+11 0.363654E+11 0.00 0.00 0.00 0.00 0.169950E+10 0.251270E+10
Minimum of Months 0.136985E+10 0.130362E+10 0.277008E+10 0.00 0.00 0.00 0.00 27861666.31 15391684.94
Maximum of Months 0.163685E+10 0.154770E+10 0.318369E+10 0.00 0.00 0.00 0.00 0.281164E+09 0.497052E+09



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.973041E+09 0.975934E+09 0.197184E+10 0.00 0.00 0.00 0.00 12465098.95 0.270672E+09
February 0.882782E+09 0.854981E+09 0.178515E+10 0.00 0.00 0.00 0.00 22174701.57 0.364364E+09
March 0.105485E+10 0.971685E+09 0.205169E+10 0.00 0.00 0.00 0.00 23520270.62 0.353978E+09
April 0.936002E+09 0.861606E+09 0.190407E+10 0.00 0.00 0.00 0.00 49483231.87 0.165714E+09
May 0.101394E+10 0.913051E+09 0.201177E+10 0.00 0.00 0.00 0.00 0.139556E+09 74511241.95
June 0.101113E+10 0.909073E+09 0.197572E+10 0.00 0.00 0.00 0.00 0.170998E+09 23729052.99
July 0.938820E+09 0.847368E+09 0.193969E+10 0.00 0.00 0.00 0.00 0.157106E+09 20849738.55
August 0.105485E+10 0.950111E+09 0.205169E+10 0.00 0.00 0.00 0.00 0.189752E+09 10329058.78
September 0.936002E+09 0.876980E+09 0.190321E+10 0.00 0.00 0.00 0.00 0.171972E+09 22351288.72
October 0.973041E+09 0.925731E+09 0.197228E+10 0.00 0.00 0.00 0.00 0.111107E+09 45330213.95
November 0.963541E+09 0.953537E+09 0.192889E+10 0.00 0.00 0.00 0.00 51371049.55 0.227652E+09
December 0.938820E+09 0.965911E+09 0.193926E+10 0.00 0.00 0.00 0.00 20584743.11 0.259280E+09
                   
Annual Sum or Average 0.116768E+11 0.110060E+11 0.234352E+11 0.00 0.00 0.00 0.00 0.112009E+10 0.183876E+10
Minimum of Months 0.882782E+09 0.847368E+09 0.178515E+10 0.00 0.00 0.00 0.00 12465098.95 10329058.78
Maximum of Months 0.105485E+10 0.975934E+09 0.205169E+10 0.00 0.00 0.00 0.00 0.189752E+09 0.364364E+09



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.150994E+10 0.146452E+10 0.305983E+10 0.00 0.00 0.00 0.00 10614308.59 0.505758E+09
February 0.136988E+10 0.130043E+10 0.277013E+10 0.00 0.00 0.00 0.00 23411171.93 0.665713E+09
March 0.163688E+10 0.150561E+10 0.318374E+10 0.00 0.00 0.00 0.00 30182738.20 0.588788E+09
April 0.145246E+10 0.134060E+10 0.295467E+10 0.00 0.00 0.00 0.00 71846668.10 0.256208E+09
May 0.157341E+10 0.142346E+10 0.312179E+10 0.00 0.00 0.00 0.00 0.206505E+09 0.104439E+09
June 0.156904E+10 0.142476E+10 0.306585E+10 0.00 0.00 0.00 0.00 0.254558E+09 32267576.24
July 0.145684E+10 0.132176E+10 0.300994E+10 0.00 0.00 0.00 0.00 0.237799E+09 28125139.90
August 0.163688E+10 0.148105E+10 0.318374E+10 0.00 0.00 0.00 0.00 0.274321E+09 16228686.39
September 0.145246E+10 0.135778E+10 0.295333E+10 0.00 0.00 0.00 0.00 0.235919E+09 37451296.83
October 0.150994E+10 0.142401E+10 0.306051E+10 0.00 0.00 0.00 0.00 0.136112E+09 96598565.63
November 0.149520E+10 0.143829E+10 0.299318E+10 0.00 0.00 0.00 0.00 55855449.09 0.436490E+09
December 0.145684E+10 0.144878E+10 0.300927E+10 0.00 0.00 0.00 0.00 15038783.08 0.510322E+09
                   
Annual Sum or Average 0.181198E+11 0.169311E+11 0.363660E+11 0.00 0.00 0.00 0.00 0.155216E+10 0.327839E+10
Minimum of Months 0.136988E+10 0.130043E+10 0.277013E+10 0.00 0.00 0.00 0.00 10614308.59 16228686.39
Maximum of Months 0.163688E+10 0.150561E+10 0.318374E+10 0.00 0.00 0.00 0.00 0.274321E+09 0.665713E+09



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.973041E+09 0.964128E+09 0.197183E+10 0.00 0.00 0.00 0.00 17908947.21 0.272873E+09
February 0.882782E+09 0.846502E+09 0.178514E+10 0.00 0.00 0.00 0.00 22674835.82 0.397941E+09
March 0.105485E+10 0.980142E+09 0.205168E+10 0.00 0.00 0.00 0.00 25295785.80 0.402648E+09
April 0.936002E+09 0.860206E+09 0.190406E+10 0.00 0.00 0.00 0.00 52231563.00 0.209093E+09
May 0.101394E+10 0.915468E+09 0.201175E+10 0.00 0.00 0.00 0.00 0.137901E+09 95609139.61
June 0.101113E+10 0.913252E+09 0.197570E+10 0.00 0.00 0.00 0.00 0.165786E+09 27866250.59
July 0.938820E+09 0.849555E+09 0.193968E+10 0.00 0.00 0.00 0.00 0.155827E+09 25001444.70
August 0.105485E+10 0.957303E+09 0.205168E+10 0.00 0.00 0.00 0.00 0.178924E+09 14300122.49
September 0.936002E+09 0.878533E+09 0.190319E+10 0.00 0.00 0.00 0.00 0.167714E+09 25686559.31
October 0.973041E+09 0.934064E+09 0.197226E+10 0.00 0.00 0.00 0.00 0.109478E+09 59871135.21
November 0.963541E+09 0.939145E+09 0.192888E+10 0.00 0.00 0.00 0.00 51046645.20 0.239911E+09
December 0.938820E+09 0.945111E+09 0.193924E+10 0.00 0.00 0.00 0.00 19013495.27 0.293884E+09
                   
Annual Sum or Average 0.116768E+11 0.109834E+11 0.234351E+11 0.00 0.00 0.00 0.00 0.110380E+10 0.206469E+10
Minimum of Months 0.882782E+09 0.846502E+09 0.178514E+10 0.00 0.00 0.00 0.00 17908947.21 14300122.49
Maximum of Months 0.105485E+10 0.980142E+09 0.205168E+10 0.00 0.00 0.00 0.00 0.178924E+09 0.402648E+09



Table of Contents

Report: SpaceGainsMonthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.174411E+09 0.553024E+09 0.521915E+10 0.00 0.00 0.00 0.00 0.00 0.00
February 0.158233E+09 0.501634E+09 0.942813E+10 0.00 0.00 0.00 0.00 0.00 0.00
March 0.189074E+09 0.596080E+09 0.156645E+11 0.00 0.00 0.00 0.00 0.00 0.00
April 0.167772E+09 0.532421E+09 0.201821E+11 0.00 0.00 0.00 0.00 0.00 0.00
May 0.181743E+09 0.574552E+09 0.522616E+10 0.00 0.00 0.00 0.00 0.00 0.00
June 0.181238E+09 0.571774E+09 0.101086E+11 0.00 0.00 0.00 0.00 0.00 0.00
July 0.168277E+09 0.535199E+09 0.156645E+11 0.00 0.00 0.00 0.00 0.00 0.00
August 0.189074E+09 0.596080E+09 0.208555E+11 0.00 0.00 0.00 0.00 0.00 0.00
September 0.167772E+09 0.532421E+09 0.505780E+10 0.00 0.00 0.00 0.00 0.00 0.00
October 0.174411E+09 0.553024E+09 0.104453E+11 0.00 0.00 0.00 0.00 0.00 0.00
November 0.172708E+09 0.546542E+09 0.151524E+11 0.00 0.00 0.00 0.00 0.00 0.00
December 0.168277E+09 0.535199E+09 0.208766E+11 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.209299E+10 0.662795E+10 0.153881E+12 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.158233E+09 0.501634E+09 0.505780E+10 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.189074E+09 0.596080E+09 0.208766E+11 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: DATACENTER_MID_ZN_6

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.174411E+09 0.553024E+09 0.521915E+10 0.00 0.00 0.00 0.00 0.00 0.00
February 0.158233E+09 0.501634E+09 0.942813E+10 0.00 0.00 0.00 0.00 0.00 0.00
March 0.189074E+09 0.596080E+09 0.156645E+11 0.00 0.00 0.00 0.00 0.00 0.00
April 0.167772E+09 0.532421E+09 0.201821E+11 0.00 0.00 0.00 0.00 0.00 0.00
May 0.181743E+09 0.574552E+09 0.522616E+10 0.00 0.00 0.00 0.00 0.00 0.00
June 0.181238E+09 0.571774E+09 0.101086E+11 0.00 0.00 0.00 0.00 0.00 0.00
July 0.168277E+09 0.535199E+09 0.156645E+11 0.00 0.00 0.00 0.00 0.00 0.00
August 0.189074E+09 0.596080E+09 0.208555E+11 0.00 0.00 0.00 0.00 0.00 0.00
September 0.167772E+09 0.532421E+09 0.505780E+10 0.00 0.00 0.00 0.00 0.00 0.00
October 0.174411E+09 0.553024E+09 0.104453E+11 0.00 0.00 0.00 0.00 0.00 0.00
November 0.172708E+09 0.546542E+09 0.151524E+11 0.00 0.00 0.00 0.00 0.00 0.00
December 0.168277E+09 0.535199E+09 0.208766E+11 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.209299E+10 0.662795E+10 0.153881E+12 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.158233E+09 0.501634E+09 0.505780E+10 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.189074E+09 0.596080E+09 0.208766E+11 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.174411E+09 0.553024E+09 0.521915E+10 0.00 0.00 0.00 0.00 0.00 0.00
February 0.158233E+09 0.501634E+09 0.942813E+10 0.00 0.00 0.00 0.00 0.00 0.00
March 0.189074E+09 0.596080E+09 0.156645E+11 0.00 0.00 0.00 0.00 0.00 0.00
April 0.167772E+09 0.532421E+09 0.201821E+11 0.00 0.00 0.00 0.00 0.00 0.00
May 0.181743E+09 0.574552E+09 0.522616E+10 0.00 0.00 0.00 0.00 0.00 0.00
June 0.181238E+09 0.571774E+09 0.101086E+11 0.00 0.00 0.00 0.00 0.00 0.00
July 0.168277E+09 0.535199E+09 0.156645E+11 0.00 0.00 0.00 0.00 0.00 0.00
August 0.189074E+09 0.596080E+09 0.208555E+11 0.00 0.00 0.00 0.00 0.00 0.00
September 0.167772E+09 0.532421E+09 0.505780E+10 0.00 0.00 0.00 0.00 0.00 0.00
October 0.174411E+09 0.553024E+09 0.104453E+11 0.00 0.00 0.00 0.00 0.00 0.00
November 0.172708E+09 0.546542E+09 0.151524E+11 0.00 0.00 0.00 0.00 0.00 0.00
December 0.168277E+09 0.535199E+09 0.208766E+11 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.209299E+10 0.662795E+10 0.153881E+12 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.158233E+09 0.501634E+09 0.505780E+10 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.189074E+09 0.596080E+09 0.208766E+11 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.377547E+10 0.618367E+10 0.254202E+12 0.00 0.00 0.00 0.00 0.00 0.00
February 0.342526E+10 0.560905E+10 0.459203E+12 0.00 0.00 0.00 0.00 0.00 0.00
March 0.409289E+10 0.666512E+10 0.762947E+12 0.00 0.00 0.00 0.00 0.00 0.00
April 0.363176E+10 0.595330E+10 0.982982E+12 0.00 0.00 0.00 0.00 0.00 0.00
May 0.393418E+10 0.642439E+10 0.254544E+12 0.00 0.00 0.00 0.00 0.00 0.00
June 0.392325E+10 0.639333E+10 0.492345E+12 0.00 0.00 0.00 0.00 0.00 0.00
July 0.364269E+10 0.598436E+10 0.762947E+12 0.00 0.00 0.00 0.00 0.00 0.00
August 0.409289E+10 0.666512E+10 0.101578E+13 0.00 0.00 0.00 0.00 0.00 0.00
September 0.363176E+10 0.595330E+10 0.246344E+12 0.00 0.00 0.00 0.00 0.00 0.00
October 0.377547E+10 0.618367E+10 0.508746E+12 0.00 0.00 0.00 0.00 0.00 0.00
November 0.373861E+10 0.611120E+10 0.738006E+12 0.00 0.00 0.00 0.00 0.00 0.00
December 0.364269E+10 0.598436E+10 0.101681E+13 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.453069E+11 0.741109E+11 0.749486E+13 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.342526E+10 0.560905E+10 0.246344E+12 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.409289E+10 0.666512E+10 0.101681E+13 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: GROUNDFLOOR_PLENUM

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 6556320.29 0.390470E+09
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 12169879.70 0.530009E+09
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 17160959.13 0.461472E+09
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 45262965.07 0.185600E+09
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.126653E+09 66890944.76
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.166625E+09 13001842.38
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.157125E+09 14622161.59
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.183616E+09 8979086.99
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.167917E+09 22805247.01
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.100073E+09 46650840.83
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 37321720.22 0.320300E+09
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 12575591.79 0.394518E+09
                   
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.103306E+10 0.245532E+10
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 6556320.29 8979086.99
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.183616E+09 0.530009E+09



Table of Contents

Report: SpaceGainsMonthly

For: MIDFLOOR_PLENUM

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 17854436.11 0.639593E+09
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 27618216.39 0.854211E+09
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 34748149.53 0.769730E+09
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 86910211.70 0.332703E+09
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.230550E+09 0.117850E+09
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.296201E+09 27189875.75
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.289270E+09 28547082.58
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.334762E+09 18297763.64
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.306808E+09 40044786.40
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.182613E+09 86978672.61
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 70407488.06 0.534910E+09
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 27105490.13 0.634497E+09
                   
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.190485E+10 0.408455E+10
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 17854436.11 18297763.64
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.334762E+09 0.854211E+09



Table of Contents

Report: SpaceGainsMonthly

For: TOPFLOOR_PLENUM

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 10295716.79 0.633424E+09
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 10122864.85 0.864042E+09
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 13477100.30 0.830841E+09
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 47599562.51 0.376676E+09
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.188148E+09 0.139234E+09
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.281053E+09 41250119.44
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.257232E+09 39656069.55
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.328706E+09 22971808.76
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.284063E+09 43365340.82
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.165024E+09 82485354.76
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 54680163.92 0.524639E+09
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 15549946.41 0.649260E+09
                   
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.165595E+10 0.424785E+10
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 10122864.85 22971808.76
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.328706E+09 0.864042E+09



Table of Contents

Report: PeakSpaceGainsMonthly

For: BASEMENT

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 17832.21 02-JAN-10:09 22950.34 02-JAN-08:09 13457.54 01-JAN-00:10 0.00 0.00 0.00 0.00 0.00 0.00
February 17832.21 01-FEB-10:09 22950.34 01-FEB-08:09 13457.54 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00 0.00
March 17832.21 01-MAR-10:09 22950.34 01-MAR-08:09 13457.54 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00 0.00
April 17832.21 03-APR-09:09 22950.34 03-APR-07:10 13457.54 01-APR-00:10 0.00 0.00 0.00 0.00 0.00 0.00
May 17832.21 01-MAY-09:09 22950.34 01-MAY-07:10 13457.54 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00 0.00
June 17832.21 01-JUN-09:09 22950.34 01-JUN-07:10 13457.54 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00 0.00
July 17832.21 03-JUL-09:09 22950.34 03-JUL-07:10 13457.54 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00 0.00
August 17832.21 01-AUG-09:09 22950.34 01-AUG-07:10 13457.54 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00 0.00
September 17832.21 01-SEP-09:09 22950.34 01-SEP-07:10 13457.54 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00 0.00
October 17832.21 02-OCT-09:09 22950.34 02-OCT-07:10 13457.54 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00 0.00
November 17832.21 01-NOV-09:09 22950.34 01-NOV-07:10 13457.54 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00 0.00
December 17832.21 01-DEC-10:09 22950.34 01-DEC-08:09 13457.54 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average             0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 17832.21   22950.34   13457.54   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 17832.21   22950.34   13457.54   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: CORE_BOTTOM

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 16014.58 02-JAN-10:09 20611.01 02-JAN-08:09 17206.63 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 0.00
February 16014.58 01-FEB-10:09 20611.01 01-FEB-08:09 17206.63 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 0.00
March 16014.58 01-MAR-10:09 20611.01 01-MAR-08:09 17206.63 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 0.00
April 16014.58 03-APR-09:09 20611.01 03-APR-07:10 17206.63 03-APR-07:10 0.00 0.00 0.00 0.00 0.00 0.00
May 16014.58 01-MAY-09:09 20611.01 01-MAY-07:10 17206.63 01-MAY-07:10 0.00 0.00 0.00 0.00 0.00 0.00
June 16014.58 01-JUN-09:09 20611.01 01-JUN-07:10 17206.63 01-JUN-07:10 0.00 0.00 0.00 0.00 0.00 0.00
July 16014.58 03-JUL-09:09 20611.01 03-JUL-07:10 17206.63 03-JUL-07:10 0.00 0.00 0.00 0.00 0.00 0.00
August 16014.58 01-AUG-09:09 20611.01 01-AUG-07:10 17206.63 01-AUG-07:10 0.00 0.00 0.00 0.00 0.00 0.00
September 16014.58 01-SEP-09:09 20611.01 01-SEP-07:10 17206.63 01-SEP-07:10 0.00 0.00 0.00 0.00 0.00 0.00
October 16014.58 02-OCT-09:09 20611.01 02-OCT-07:10 17206.63 02-OCT-07:10 0.00 0.00 0.00 0.00 0.00 0.00
November 16014.58 01-NOV-09:09 20611.01 01-NOV-07:10 17206.63 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 0.00
December 16014.58 01-DEC-10:09 20611.01 01-DEC-08:09 17206.63 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average             0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 16014.58   20611.01   17206.63   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 16014.58   20611.01   17206.63   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: CORE_MID

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 16014.58 02-JAN-10:09 20611.01 02-JAN-08:09 17206.56 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 0.00
February 16014.58 01-FEB-10:09 20611.01 01-FEB-08:09 17206.56 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 0.00
March 16014.58 01-MAR-10:09 20611.01 01-MAR-08:09 17206.56 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 0.00
April 16014.58 03-APR-09:09 20611.01 03-APR-07:10 17206.56 03-APR-07:10 0.00 0.00 0.00 0.00 0.00 0.00
May 16014.58 01-MAY-09:09 20611.01 01-MAY-07:10 17206.56 01-MAY-07:10 0.00 0.00 0.00 0.00 0.00 0.00
June 16014.58 01-JUN-09:09 20611.01 01-JUN-07:10 17206.56 01-JUN-07:10 0.00 0.00 0.00 0.00 0.00 0.00
July 16014.58 03-JUL-09:09 20611.01 03-JUL-07:10 17206.56 03-JUL-07:10 0.00 0.00 0.00 0.00 0.00 0.00
August 16014.58 01-AUG-09:09 20611.01 01-AUG-07:10 17206.56 01-AUG-07:10 0.00 0.00 0.00 0.00 0.00 0.00
September 16014.58 01-SEP-09:09 20611.01 01-SEP-07:10 17206.56 01-SEP-07:10 0.00 0.00 0.00 0.00 0.00 0.00
October 16014.58 02-OCT-09:09 20611.01 02-OCT-07:10 17206.56 02-OCT-07:10 0.00 0.00 0.00 0.00 0.00 0.00
November 16014.58 01-NOV-09:09 20611.01 01-NOV-07:10 17206.56 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 0.00
December 16014.58 01-DEC-10:09 20611.01 01-DEC-08:09 17206.56 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average             0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 16014.58   20611.01   17206.56   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 16014.58   20611.01   17206.56   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: CORE_TOP

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 16014.58 02-JAN-10:09 20611.01 02-JAN-08:09 17206.56 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 0.00
February 16014.58 01-FEB-10:09 20611.01 01-FEB-08:09 17206.56 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 0.00
March 16014.58 01-MAR-10:09 20611.01 01-MAR-08:09 17206.56 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 0.00
April 16014.58 03-APR-09:09 20611.01 03-APR-07:10 17206.56 03-APR-07:10 0.00 0.00 0.00 0.00 0.00 0.00
May 16014.58 01-MAY-09:09 20611.01 01-MAY-07:10 17206.56 01-MAY-07:10 0.00 0.00 0.00 0.00 0.00 0.00
June 16014.58 01-JUN-09:09 20611.01 01-JUN-07:10 17206.56 01-JUN-07:10 0.00 0.00 0.00 0.00 0.00 0.00
July 16014.58 03-JUL-09:09 20611.01 03-JUL-07:10 17206.56 03-JUL-07:10 0.00 0.00 0.00 0.00 0.00 0.00
August 16014.58 01-AUG-09:09 20611.01 01-AUG-07:10 17206.56 01-AUG-07:10 0.00 0.00 0.00 0.00 0.00 0.00
September 16014.58 01-SEP-09:09 20611.01 01-SEP-07:10 17206.56 01-SEP-07:10 0.00 0.00 0.00 0.00 0.00 0.00
October 16014.58 02-OCT-09:09 20611.01 02-OCT-07:10 17206.56 02-OCT-07:10 0.00 0.00 0.00 0.00 0.00 0.00
November 16014.58 01-NOV-09:09 20611.01 01-NOV-07:10 17206.56 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 0.00
December 16014.58 01-DEC-10:09 20611.01 01-DEC-08:09 17206.56 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average             0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 16014.58   20611.01   17206.56   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 16014.58   20611.01   17206.56   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 2010.79 02-JAN-10:09 2255.20 04-JAN-16:30 2160.55 02-JAN-08:09 0.00 0.00 0.00 0.00 102.94 15-JAN-14:00 473.41 24-JAN-03:00
February 2010.79 01-FEB-10:09 1803.00 03-FEB-16:00 2160.55 01-FEB-08:09 0.00 0.00 0.00 0.00 97.52 20-FEB-15:30 793.69 04-FEB-05:00
March 2010.79 01-MAR-10:09 2135.72 15-MAR-07:10 2160.55 01-MAR-08:09 0.00 0.00 0.00 0.00 117.23 05-MAR-13:43 779.35 16-MAR-02:00
April 2010.79 03-APR-09:09 1803.00 12-APR-07:10 2160.55 03-APR-07:10 0.00 0.00 0.00 0.00 266.96 15-APR-17:10 253.35 18-APR-24:00
May 2010.79 01-MAY-09:09 1470.28 25-MAY-07:10 2160.55 01-MAY-07:10 0.00 0.00 0.00 0.00 404.13 29-MAY-15:55 152.66 25-MAY-04:10
June 2010.79 01-JUN-09:09 2255.20 15-JUN-07:10 2160.55 01-JUN-07:10 0.00 0.00 0.00 0.00 250.58 25-JUN-14:00 146.25 18-JUN-20:00
July 2010.79 03-JUL-09:09 1470.28 05-JUL-07:10 2160.55 03-JUL-07:10 0.00 0.00 0.00 0.00 315.86 30-JUL-15:50 127.57 02-JUL-16:00
August 2010.79 01-AUG-09:09 1803.00 28-AUG-07:10 2160.55 01-AUG-07:10 0.00 0.00 0.00 0.00 278.39 13-AUG-13:00 142.57 14-AUG-03:30
September 2010.79 01-SEP-09:09 2587.92 27-SEP-07:10 2160.55 01-SEP-07:10 0.00 0.00 0.00 0.00 287.85 17-SEP-13:50 80.00 19-SEP-23:50
October 2010.79 02-OCT-09:09 2255.20 18-OCT-07:10 2160.55 02-OCT-07:10 0.00 0.00 0.00 0.00 225.37 29-OCT-14:10 135.77 16-OCT-03:00
November 2010.79 01-NOV-09:09 2255.20 10-NOV-16:00 2160.55 01-NOV-07:10 0.00 0.00 0.00 0.00 113.10 22-NOV-22:02 800.56 11-NOV-09:00
December 2010.79 01-DEC-10:09 2587.92 15-DEC-16:30 2160.55 01-DEC-08:09 0.00 0.00 0.00 0.00 203.65 10-DEC-14:40 741.13 15-DEC-04:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 2010.79   1470.28   2160.55   0.00 0.00 0.00 0.00 97.52   80.00  
Maximum of Months 2010.79   2587.92   2160.55   0.00 0.00 0.00 0.00 404.13   800.56  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 1295.83 02-JAN-10:09 1453.34 04-JAN-16:30 1392.34 02-JAN-08:09 0.00 0.00 0.00 0.00 63.11 29-JAN-12:15 320.87 08-JAN-10:00
February 1295.83 01-FEB-10:09 1161.92 01-FEB-16:00 1392.34 01-FEB-08:09 0.00 0.00 0.00 0.00 71.84 19-FEB-15:40 521.52 04-FEB-05:00
March 1295.83 01-MAR-10:09 947.51 06-MAR-16:00 1392.34 01-MAR-08:09 0.00 0.00 0.00 0.00 104.69 05-MAR-14:15 522.63 16-MAR-02:00
April 1295.83 03-APR-09:09 1161.92 12-APR-07:10 1392.34 03-APR-07:10 0.00 0.00 0.00 0.00 184.68 15-APR-17:10 165.30 18-APR-24:00
May 1295.83 01-MAY-09:09 870.51 10-MAY-14:20 1392.34 01-MAY-07:10 0.00 0.00 0.00 0.00 284.58 29-MAY-16:00 109.71 07-MAY-24:00
June 1295.83 01-JUN-09:09 1453.34 15-JUN-07:10 1392.34 01-JUN-07:10 0.00 0.00 0.00 0.00 183.06 17-JUN-18:30 81.35 18-JUN-20:00
July 1295.83 03-JUL-09:09 870.51 05-JUL-07:10 1392.34 03-JUL-07:10 0.00 0.00 0.00 0.00 217.73 30-JUL-15:50 88.85 02-JUL-16:00
August 1295.83 01-AUG-09:09 1161.92 28-AUG-07:10 1392.34 01-AUG-07:10 0.00 0.00 0.00 0.00 210.87 13-AUG-13:00 74.88 14-AUG-03:30
September 1295.83 01-SEP-09:09 1667.75 27-SEP-07:10 1392.34 01-SEP-07:10 0.00 0.00 0.00 0.00 193.50 17-SEP-16:50 50.56 19-SEP-23:50
October 1295.83 02-OCT-09:09 1453.34 18-OCT-07:10 1392.34 02-OCT-07:10 0.00 0.00 0.00 0.00 162.60 29-OCT-14:10 85.40 16-OCT-03:00
November 1295.83 01-NOV-09:09 1453.34 10-NOV-16:49 1392.34 01-NOV-07:10 0.00 0.00 0.00 0.00 88.43 23-NOV-12:20 618.76 11-NOV-09:00
December 1295.83 01-DEC-10:09 1667.75 15-DEC-16:30 1392.34 01-DEC-08:09 0.00 0.00 0.00 0.00 165.99 10-DEC-14:40 483.92 15-DEC-04:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 1295.83   870.51   1392.34   0.00 0.00 0.00 0.00 63.11   50.56  
Maximum of Months 1295.83   1667.75   1392.34   0.00 0.00 0.00 0.00 284.58   618.76  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 2010.83 02-JAN-10:09 2255.25 04-JAN-16:49 2160.58 02-JAN-08:09 0.00 0.00 0.00 0.00 58.48 07-JAN-13:00 502.07 24-JAN-03:00
February 2010.83 01-FEB-10:09 1470.31 08-FEB-16:40 2160.58 01-FEB-08:09 0.00 0.00 0.00 0.00 70.57 02-FEB-14:00 802.28 04-FEB-05:00
March 2010.83 01-MAR-10:09 1803.04 13-MAR-07:10 2160.58 01-MAR-08:09 0.00 0.00 0.00 0.00 87.80 05-MAR-13:45 809.28 16-MAR-02:00
April 2010.83 03-APR-09:09 1803.04 12-APR-07:10 2160.58 03-APR-07:10 0.00 0.00 0.00 0.00 249.15 15-APR-17:10 260.52 18-APR-24:00
May 2010.83 01-MAY-09:09 1470.31 25-MAY-07:10 2160.58 01-MAY-07:10 0.00 0.00 0.00 0.00 404.70 29-MAY-15:55 150.44 07-MAY-24:00
June 2010.83 01-JUN-09:09 2255.25 15-JUN-07:10 2160.58 01-JUN-07:10 0.00 0.00 0.00 0.00 250.38 25-JUN-14:00 152.80 18-JUN-20:00
July 2010.83 03-JUL-09:09 1470.31 05-JUL-07:10 2160.58 03-JUL-07:10 0.00 0.00 0.00 0.00 313.11 30-JUL-15:48 127.00 02-JUL-16:00
August 2010.83 01-AUG-09:09 1803.04 28-AUG-07:10 2160.58 01-AUG-07:10 0.00 0.00 0.00 0.00 269.75 13-AUG-12:20 141.91 14-AUG-03:30
September 2010.83 01-SEP-09:09 2587.98 27-SEP-07:10 2160.58 01-SEP-07:10 0.00 0.00 0.00 0.00 263.30 17-SEP-16:45 97.37 19-SEP-23:50
October 2010.83 02-OCT-09:09 2255.25 18-OCT-07:10 2160.58 02-OCT-07:10 0.00 0.00 0.00 0.00 184.58 29-OCT-14:06 160.29 16-OCT-03:00
November 2010.83 01-NOV-09:09 2255.25 29-NOV-16:00 2160.58 01-NOV-07:10 0.00 0.00 0.00 0.00 107.98 22-NOV-22:02 912.72 11-NOV-09:00
December 2010.83 01-DEC-10:09 2587.98 15-DEC-16:40 2160.58 01-DEC-08:09 0.00 0.00 0.00 0.00 127.83 10-DEC-14:36 769.83 15-DEC-04:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 2010.83   1470.31   2160.58   0.00 0.00 0.00 0.00 58.48   97.37  
Maximum of Months 2010.83   2587.98   2160.58   0.00 0.00 0.00 0.00 404.70   912.72  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 1295.83 02-JAN-10:09 1453.34 04-JAN-16:49 1392.33 02-JAN-08:09 0.00 0.00 0.00 0.00 74.55 29-JAN-12:15 351.89 24-JAN-03:00
February 1295.83 01-FEB-10:09 1161.92 01-FEB-08:09 1392.33 01-FEB-08:09 0.00 0.00 0.00 0.00 47.04 02-FEB-14:00 578.56 04-FEB-05:00
March 1295.83 01-MAR-10:09 1453.34 14-MAR-07:10 1392.33 01-MAR-08:09 0.00 0.00 0.00 0.00 71.48 05-MAR-13:43 605.95 16-MAR-02:00
April 1295.83 03-APR-09:09 1453.34 12-APR-07:10 1392.33 03-APR-07:10 0.00 0.00 0.00 0.00 142.61 15-APR-17:04 216.11 18-APR-24:00
May 1295.83 01-MAY-09:09 1161.92 25-MAY-07:10 1392.33 01-MAY-07:10 0.00 0.00 0.00 0.00 251.81 29-MAY-15:53 125.59 25-MAY-04:10
June 1295.83 01-JUN-09:09 1667.75 15-JUN-07:10 1392.33 01-JUN-07:10 0.00 0.00 0.00 0.00 168.71 25-JUN-13:58 134.23 18-JUN-20:00
July 1295.83 03-JUL-09:09 1161.92 05-JUL-07:10 1392.33 03-JUL-07:10 0.00 0.00 0.00 0.00 220.94 30-JUL-15:46 105.20 04-JUL-03:00
August 1295.83 01-AUG-09:09 1453.34 28-AUG-07:10 1392.33 01-AUG-07:10 0.00 0.00 0.00 0.00 200.57 13-AUG-12:20 145.08 14-AUG-03:30
September 1295.83 01-SEP-09:09 1667.75 27-SEP-07:10 1392.33 01-SEP-07:10 0.00 0.00 0.00 0.00 187.87 17-SEP-12:50 86.98 19-SEP-23:50
October 1295.83 02-OCT-09:09 1453.34 18-OCT-07:10 1392.33 02-OCT-07:10 0.00 0.00 0.00 0.00 153.58 29-OCT-12:10 119.21 16-OCT-03:00
November 1295.83 01-NOV-09:09 1453.34 03-NOV-07:10 1392.33 01-NOV-07:10 0.00 0.00 0.00 0.00 68.44 22-NOV-22:02 615.34 11-NOV-09:00
December 1295.83 01-DEC-10:09 1667.75 15-DEC-16:40 1392.33 01-DEC-08:09 0.00 0.00 0.00 0.00 100.14 10-DEC-13:56 568.04 15-DEC-04:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 1295.83   1161.92   1392.33   0.00 0.00 0.00 0.00 47.04   86.98  
Maximum of Months 1295.83   1667.75   1392.33   0.00 0.00 0.00 0.00 251.81   615.34  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 2010.79 02-JAN-10:09 2255.20 04-JAN-16:40 2160.55 02-JAN-08:09 0.00 0.00 0.00 0.00 419.00 15-JAN-14:10 945.10 24-JAN-03:00
February 2010.79 01-FEB-10:09 1803.00 03-FEB-16:00 2160.55 01-FEB-08:09 0.00 0.00 0.00 0.00 340.34 20-FEB-14:50 1680.36 04-FEB-05:13
March 2010.79 01-MAR-10:09 2135.72 15-MAR-07:10 2160.55 01-MAR-08:09 0.00 0.00 0.00 0.00 309.18 05-MAR-14:00 1564.17 16-MAR-02:00
April 2010.79 03-APR-09:09 1803.00 12-APR-07:10 2160.55 03-APR-07:10 0.00 0.00 0.00 0.00 642.87 15-APR-17:01 551.15 18-APR-23:53
May 2010.79 01-MAY-09:09 1470.28 25-MAY-07:10 2160.55 01-MAY-07:10 0.00 0.00 0.00 0.00 896.59 29-MAY-15:45 333.08 25-MAY-05:00
June 2010.79 01-JUN-09:09 2255.20 15-JUN-07:10 2160.55 01-JUN-07:10 0.00 0.00 0.00 0.00 568.26 25-JUN-14:00 367.13 18-JUN-20:00
July 2010.79 03-JUL-09:09 1470.28 05-JUL-07:10 2160.55 03-JUL-07:10 0.00 0.00 0.00 0.00 657.60 30-JUL-16:08 286.61 04-JUL-02:55
August 2010.79 01-AUG-09:09 1803.00 28-AUG-07:10 2160.55 01-AUG-07:10 0.00 0.00 0.00 0.00 674.59 13-AUG-12:50 413.06 14-AUG-02:55
September 2010.79 01-SEP-09:09 2587.92 27-SEP-07:10 2160.55 01-SEP-07:10 0.00 0.00 0.00 0.00 683.09 17-SEP-14:00 191.72 19-SEP-24:00
October 2010.79 02-OCT-09:09 2255.20 18-OCT-07:10 2160.55 02-OCT-07:10 0.00 0.00 0.00 0.00 510.30 29-OCT-14:00 300.19 01-OCT-07:00
November 2010.79 01-NOV-09:09 2255.20 21-NOV-16:00 2160.55 01-NOV-07:10 0.00 0.00 0.00 0.00 281.69 19-NOV-10:40 1616.65 11-NOV-09:00
December 2010.79 01-DEC-10:09 2587.92 15-DEC-16:30 2160.55 01-DEC-08:09 0.00 0.00 0.00 0.00 481.42 10-DEC-14:50 1490.69 15-DEC-05:55
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 2010.79   1470.28   2160.55   0.00 0.00 0.00 0.00 281.69   191.72  
Maximum of Months 2010.79   2587.92   2160.55   0.00 0.00 0.00 0.00 896.59   1680.36  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 1239.33 02-JAN-08:09 1453.34 04-JAN-16:30 1392.34 02-JAN-08:09 0.00 0.00 0.00 0.00 171.75 15-JAN-14:50 700.90 08-JAN-09:53
February 1239.33 01-FEB-08:09 1161.92 01-FEB-16:00 1392.34 01-FEB-08:09 0.00 0.00 0.00 0.00 182.76 19-FEB-16:10 1112.47 04-FEB-05:19
March 1239.33 01-MAR-08:09 947.51 14-MAR-07:10 1392.34 01-MAR-08:09 0.00 0.00 0.00 0.00 238.67 05-MAR-14:00 1101.52 16-MAR-02:00
April 1239.33 03-APR-07:10 1161.92 12-APR-07:10 1392.34 03-APR-07:10 0.00 0.00 0.00 0.00 415.50 15-APR-17:01 387.02 18-APR-23:53
May 1239.33 01-MAY-07:10 870.51 10-MAY-14:20 1392.34 01-MAY-07:10 0.00 0.00 0.00 0.00 610.55 29-MAY-16:25 239.92 07-MAY-18:20
June 1239.33 01-JUN-07:10 1453.34 15-JUN-07:10 1392.34 01-JUN-07:10 0.00 0.00 0.00 0.00 407.52 25-JUN-14:00 235.52 18-JUN-20:00
July 1239.33 03-JUL-07:10 870.51 05-JUL-07:10 1392.34 03-JUL-07:10 0.00 0.00 0.00 0.00 474.22 30-JUL-16:08 229.94 02-JUL-15:40
August 1239.33 01-AUG-07:10 1161.92 28-AUG-07:10 1392.34 01-AUG-07:10 0.00 0.00 0.00 0.00 444.67 13-AUG-12:50 274.70 14-AUG-02:55
September 1239.33 01-SEP-07:10 1667.75 27-SEP-07:10 1392.34 01-SEP-07:10 0.00 0.00 0.00 0.00 485.29 17-SEP-13:57 139.38 19-SEP-24:00
October 1239.33 02-OCT-07:10 1453.34 18-OCT-07:10 1392.34 02-OCT-07:10 0.00 0.00 0.00 0.00 369.84 29-OCT-14:20 206.40 01-OCT-07:00
November 1239.33 01-NOV-07:10 1453.34 10-NOV-16:00 1392.34 01-NOV-07:10 0.00 0.00 0.00 0.00 190.08 22-NOV-22:02 1314.55 11-NOV-09:00
December 1239.33 01-DEC-08:09 1667.75 15-DEC-16:30 1392.34 01-DEC-08:09 0.00 0.00 0.00 0.00 335.96 10-DEC-14:30 1013.39 15-DEC-05:55
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 1239.33   870.51   1392.34   0.00 0.00 0.00 0.00 171.75   139.38  
Maximum of Months 1239.33   1667.75   1392.34   0.00 0.00 0.00 0.00 610.55   1314.55  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 2010.83 02-JAN-10:09 2255.25 04-JAN-16:49 2160.58 02-JAN-08:09 0.00 0.00 0.00 0.00 133.67 07-JAN-13:00 1091.18 24-JAN-03:00
February 2010.83 01-FEB-10:09 1470.31 08-FEB-16:40 2160.58 01-FEB-08:09 0.00 0.00 0.00 0.00 161.31 02-FEB-14:00 1703.19 04-FEB-05:00
March 2010.83 01-MAR-10:09 1803.04 13-MAR-07:10 2160.58 01-MAR-08:09 0.00 0.00 0.00 0.00 229.20 05-MAR-14:00 1740.03 16-MAR-02:00
April 2010.83 03-APR-09:09 1803.04 12-APR-07:10 2160.58 03-APR-07:10 0.00 0.00 0.00 0.00 589.58 15-APR-17:01 587.07 18-APR-23:53
May 2010.83 01-MAY-09:09 1470.31 25-MAY-07:10 2160.58 01-MAY-07:10 0.00 0.00 0.00 0.00 896.41 29-MAY-15:45 333.41 25-MAY-05:00
June 2010.83 01-JUN-09:09 2255.25 15-JUN-07:10 2160.58 01-JUN-07:10 0.00 0.00 0.00 0.00 567.50 25-JUN-14:00 372.26 18-JUN-20:00
July 2010.83 03-JUL-09:09 1470.31 05-JUL-07:10 2160.58 03-JUL-07:10 0.00 0.00 0.00 0.00 645.63 30-JUL-16:08 276.85 04-JUL-02:55
August 2010.83 01-AUG-09:09 1803.04 28-AUG-07:10 2160.58 01-AUG-07:10 0.00 0.00 0.00 0.00 630.68 13-AUG-12:50 426.03 14-AUG-02:55
September 2010.83 01-SEP-09:09 2587.98 27-SEP-07:10 2160.58 01-SEP-07:10 0.00 0.00 0.00 0.00 581.67 17-SEP-13:55 240.07 19-SEP-23:20
October 2010.83 02-OCT-09:09 2255.25 18-OCT-07:10 2160.58 02-OCT-07:10 0.00 0.00 0.00 0.00 404.12 29-OCT-13:54 371.29 16-OCT-03:00
November 2010.83 01-NOV-09:09 2255.25 29-NOV-16:00 2160.58 01-NOV-07:10 0.00 0.00 0.00 0.00 244.30 22-NOV-22:02 1930.32 11-NOV-09:00
December 2010.83 01-DEC-10:09 2587.98 15-DEC-16:40 2160.58 01-DEC-08:09 0.00 0.00 0.00 0.00 279.11 10-DEC-14:50 1651.60 15-DEC-04:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 2010.83   1470.31   2160.58   0.00 0.00 0.00 0.00 133.67   240.07  
Maximum of Months 2010.83   2587.98   2160.58   0.00 0.00 0.00 0.00 896.41   1930.32  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 1295.83 02-JAN-10:09 1453.34 04-JAN-16:00 1392.33 02-JAN-08:09 0.00 0.00 0.00 0.00 297.58 15-JAN-12:10 685.36 24-JAN-03:00
February 1295.83 01-FEB-10:09 1161.92 01-FEB-08:09 1392.33 01-FEB-08:09 0.00 0.00 0.00 0.00 129.47 20-FEB-13:30 1115.93 04-FEB-05:12
March 1295.83 01-MAR-10:09 1453.34 14-MAR-07:10 1392.33 01-MAR-08:09 0.00 0.00 0.00 0.00 245.47 05-MAR-14:00 1162.97 16-MAR-02:00
April 1295.83 03-APR-09:09 1453.34 12-APR-07:10 1392.33 03-APR-07:10 0.00 0.00 0.00 0.00 354.81 16-APR-12:53 435.21 18-APR-23:53
May 1295.83 01-MAY-09:09 1161.92 25-MAY-07:10 1392.33 01-MAY-07:10 0.00 0.00 0.00 0.00 582.62 29-MAY-15:44 245.05 07-MAY-18:20
June 1295.83 01-JUN-09:09 1667.75 15-JUN-07:10 1392.33 01-JUN-07:10 0.00 0.00 0.00 0.00 389.37 25-JUN-14:00 284.64 18-JUN-20:00
July 1295.83 03-JUL-09:09 1161.92 05-JUL-07:10 1392.33 03-JUL-07:10 0.00 0.00 0.00 0.00 484.58 30-JUL-16:08 227.93 04-JUL-02:55
August 1295.83 01-AUG-09:09 1453.34 28-AUG-07:10 1392.33 01-AUG-07:10 0.00 0.00 0.00 0.00 538.23 13-AUG-12:50 345.80 14-AUG-02:55
September 1295.83 01-SEP-09:09 1667.75 27-SEP-07:10 1392.33 01-SEP-07:10 0.00 0.00 0.00 0.00 442.72 17-SEP-13:55 184.75 19-SEP-23:20
October 1295.83 02-OCT-09:09 1453.34 18-OCT-07:10 1392.33 02-OCT-07:10 0.00 0.00 0.00 0.00 362.79 29-OCT-12:00 242.80 01-OCT-07:00
November 1295.83 01-NOV-09:09 1453.34 03-NOV-07:10 1392.33 01-NOV-07:10 0.00 0.00 0.00 0.00 229.28 19-NOV-10:40 1114.65 11-NOV-09:00
December 1295.83 01-DEC-10:09 1667.75 15-DEC-16:40 1392.33 01-DEC-08:09 0.00 0.00 0.00 0.00 286.92 10-DEC-13:50 1041.31 15-DEC-05:55
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 1295.83   1161.92   1392.33   0.00 0.00 0.00 0.00 129.47   184.75  
Maximum of Months 1295.83   1667.75   1392.33   0.00 0.00 0.00 0.00 582.62   1162.97  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 2010.79 02-JAN-10:09 2255.20 04-JAN-16:40 2160.55 02-JAN-08:09 0.00 0.00 0.00 0.00 504.43 15-JAN-11:52 1093.56 24-JAN-03:00
February 2010.79 01-FEB-10:09 1803.00 03-FEB-16:00 2160.55 01-FEB-08:09 0.00 0.00 0.00 0.00 383.69 20-FEB-14:50 2087.82 04-FEB-05:20
March 2010.79 01-MAR-10:09 2135.72 15-MAR-07:10 2160.55 01-MAR-08:09 0.00 0.00 0.00 0.00 339.04 05-MAR-14:00 1766.35 16-MAR-02:00
April 2010.79 03-APR-09:09 1803.00 12-APR-07:10 2160.55 03-APR-07:10 0.00 0.00 0.00 0.00 736.82 15-APR-17:01 650.73 18-APR-23:53
May 2010.79 01-MAY-09:09 1470.28 25-MAY-07:10 2160.55 01-MAY-07:10 0.00 0.00 0.00 0.00 1104.60 29-MAY-15:45 473.37 07-MAY-18:53
June 2010.79 01-JUN-09:09 2255.20 15-JUN-07:10 2160.55 01-JUN-07:10 0.00 0.00 0.00 0.00 692.55 25-JUN-13:58 514.50 18-JUN-20:00
July 2010.79 03-JUL-09:09 1470.28 05-JUL-07:10 2160.55 03-JUL-07:10 0.00 0.00 0.00 0.00 856.23 30-JUL-16:00 405.85 02-JUL-16:00
August 2010.79 01-AUG-09:09 1803.00 28-AUG-07:10 2160.55 01-AUG-07:10 0.00 0.00 0.00 0.00 772.03 13-AUG-12:50 521.72 14-AUG-02:55
September 2010.79 01-SEP-09:09 2587.92 27-SEP-07:10 2160.55 01-SEP-07:10 0.00 0.00 0.00 0.00 796.91 17-SEP-13:57 251.05 19-SEP-23:20
October 2010.79 02-OCT-09:09 2255.20 18-OCT-07:10 2160.55 02-OCT-07:10 0.00 0.00 0.00 0.00 573.25 29-OCT-13:50 389.63 01-OCT-07:00
November 2010.79 01-NOV-09:09 2255.20 21-NOV-16:00 2160.55 01-NOV-07:10 0.00 0.00 0.00 0.00 336.67 19-NOV-11:40 1824.11 11-NOV-09:00
December 2010.79 01-DEC-10:09 2587.92 15-DEC-16:30 2160.55 01-DEC-08:09 0.00 0.00 0.00 0.00 536.78 10-DEC-14:50 1842.17 15-DEC-06:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 2010.79   1470.28   2160.55   0.00 0.00 0.00 0.00 336.67   251.05  
Maximum of Months 2010.79   2587.92   2160.55   0.00 0.00 0.00 0.00 1104.60   2087.82  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 1295.83 02-JAN-10:09 1453.34 04-JAN-16:30 1392.34 02-JAN-08:09 0.00 0.00 0.00 0.00 206.71 15-JAN-13:52 783.10 08-JAN-09:53
February 1295.83 01-FEB-10:09 1161.92 01-FEB-16:00 1392.34 01-FEB-08:09 0.00 0.00 0.00 0.00 206.72 19-FEB-15:40 1391.89 04-FEB-05:17
March 1295.83 01-MAR-10:09 947.51 14-MAR-07:10 1392.34 01-MAR-08:09 0.00 0.00 0.00 0.00 267.48 05-MAR-14:00 1252.75 16-MAR-02:00
April 1295.83 03-APR-09:09 1161.92 12-APR-07:10 1392.34 03-APR-07:10 0.00 0.00 0.00 0.00 476.58 15-APR-17:01 458.24 18-APR-23:53
May 1295.83 01-MAY-09:09 870.51 10-MAY-14:20 1392.34 01-MAY-07:10 0.00 0.00 0.00 0.00 741.13 29-MAY-15:45 405.84 07-MAY-18:53
June 1295.83 01-JUN-09:09 1453.34 15-JUN-07:10 1392.34 01-JUN-07:10 0.00 0.00 0.00 0.00 506.40 25-JUN-14:00 331.08 18-JUN-20:00
July 1295.83 03-JUL-09:09 870.51 05-JUL-07:10 1392.34 03-JUL-07:10 0.00 0.00 0.00 0.00 613.07 30-JUL-16:00 304.40 02-JUL-16:00
August 1295.83 01-AUG-09:09 1161.92 28-AUG-07:10 1392.34 01-AUG-07:10 0.00 0.00 0.00 0.00 530.92 20-AUG-12:16 340.91 14-AUG-02:55
September 1295.83 01-SEP-09:09 1667.75 27-SEP-07:10 1392.34 01-SEP-07:10 0.00 0.00 0.00 0.00 566.80 17-SEP-13:57 180.05 19-SEP-23:20
October 1295.83 02-OCT-09:09 1453.34 18-OCT-07:10 1392.34 02-OCT-07:10 0.00 0.00 0.00 0.00 435.46 29-OCT-13:50 265.72 01-OCT-07:00
November 1295.83 01-NOV-09:09 1453.34 10-NOV-16:00 1392.34 01-NOV-07:10 0.00 0.00 0.00 0.00 232.54 22-NOV-22:02 1503.61 11-NOV-09:00
December 1295.83 01-DEC-10:09 1667.75 15-DEC-16:30 1392.34 01-DEC-08:09 0.00 0.00 0.00 0.00 388.07 10-DEC-14:30 1228.14 15-DEC-06:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 1295.83   870.51   1392.34   0.00 0.00 0.00 0.00 206.71   180.05  
Maximum of Months 1295.83   1667.75   1392.34   0.00 0.00 0.00 0.00 741.13   1503.61  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 2010.83 02-JAN-10:09 2255.25 04-JAN-16:49 2160.58 02-JAN-08:09 0.00 0.00 0.00 0.00 161.65 07-JAN-13:00 1277.54 24-JAN-03:00
February 2010.83 01-FEB-10:09 1470.31 08-FEB-16:40 2160.58 01-FEB-08:09 0.00 0.00 0.00 0.00 195.07 02-FEB-14:00 2087.78 04-FEB-05:20
March 2010.83 01-MAR-10:09 1803.04 13-MAR-07:10 2160.58 01-MAR-08:09 0.00 0.00 0.00 0.00 278.78 05-MAR-14:00 1983.23 16-MAR-02:00
April 2010.83 03-APR-09:09 1803.04 12-APR-07:10 2160.58 03-APR-07:10 0.00 0.00 0.00 0.00 672.53 15-APR-17:01 695.66 18-APR-23:53
May 2010.83 01-MAY-09:09 1470.31 25-MAY-07:10 2160.58 01-MAY-07:10 0.00 0.00 0.00 0.00 1110.63 29-MAY-15:45 481.59 07-MAY-18:53
June 2010.83 01-JUN-09:09 2255.25 15-JUN-07:10 2160.58 01-JUN-07:10 0.00 0.00 0.00 0.00 690.90 25-JUN-13:58 522.50 18-JUN-20:00
July 2010.83 03-JUL-09:09 1470.31 05-JUL-07:10 2160.58 03-JUL-07:10 0.00 0.00 0.00 0.00 860.32 30-JUL-15:58 400.59 02-JUL-16:00
August 2010.83 01-AUG-09:09 1803.04 28-AUG-07:10 2160.58 01-AUG-07:10 0.00 0.00 0.00 0.00 719.63 20-AUG-11:55 536.09 14-AUG-02:55
September 2010.83 01-SEP-09:09 2587.98 27-SEP-07:10 2160.58 01-SEP-07:10 0.00 0.00 0.00 0.00 714.71 17-SEP-13:55 308.89 19-SEP-23:20
October 2010.83 02-OCT-09:09 2255.25 18-OCT-07:10 2160.58 02-OCT-07:10 0.00 0.00 0.00 0.00 484.64 29-OCT-13:56 455.06 16-OCT-05:00
November 2010.83 01-NOV-09:09 2255.25 29-NOV-16:00 2160.58 01-NOV-07:10 0.00 0.00 0.00 0.00 290.02 22-NOV-22:02 2198.02 11-NOV-09:00
December 2010.83 01-DEC-10:09 2587.98 15-DEC-16:40 2160.58 01-DEC-08:09 0.00 0.00 0.00 0.00 328.54 10-DEC-14:50 1868.90 15-DEC-04:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 2010.83   1470.31   2160.58   0.00 0.00 0.00 0.00 161.65   308.89  
Maximum of Months 2010.83   2587.98   2160.58   0.00 0.00 0.00 0.00 1110.63   2198.02  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 1295.83 02-JAN-10:09 1453.34 04-JAN-16:00 1392.33 02-JAN-08:09 0.00 0.00 0.00 0.00 404.33 15-JAN-11:52 805.62 24-JAN-03:00
February 1295.83 01-FEB-10:09 1161.92 01-FEB-08:09 1392.33 01-FEB-08:09 0.00 0.00 0.00 0.00 162.66 20-FEB-13:30 1391.86 04-FEB-05:16
March 1295.83 01-MAR-10:09 1453.34 14-MAR-07:10 1392.33 01-MAR-08:09 0.00 0.00 0.00 0.00 294.53 05-MAR-14:00 1332.01 16-MAR-02:00
April 1295.83 03-APR-09:09 1453.34 12-APR-07:10 1392.33 03-APR-07:10 0.00 0.00 0.00 0.00 419.25 16-APR-12:53 517.34 18-APR-23:53
May 1295.83 01-MAY-09:09 1161.92 25-MAY-07:10 1392.33 01-MAY-07:10 0.00 0.00 0.00 0.00 705.90 29-MAY-15:44 395.87 07-MAY-18:53
June 1295.83 01-JUN-09:09 1667.75 15-JUN-07:10 1392.33 01-JUN-07:10 0.00 0.00 0.00 0.00 486.00 25-JUN-14:00 382.88 18-JUN-20:00
July 1295.83 03-JUL-09:09 1161.92 05-JUL-07:10 1392.33 03-JUL-07:10 0.00 0.00 0.00 0.00 630.10 30-JUL-16:00 289.13 04-JUL-02:55
August 1295.83 01-AUG-09:09 1453.34 28-AUG-07:10 1392.33 01-AUG-07:10 0.00 0.00 0.00 0.00 601.89 13-AUG-12:30 415.39 14-AUG-02:55
September 1295.83 01-SEP-09:09 1667.75 27-SEP-07:10 1392.33 01-SEP-07:10 0.00 0.00 0.00 0.00 539.94 17-SEP-13:55 233.68 19-SEP-23:20
October 1295.83 02-OCT-09:09 1453.34 18-OCT-07:10 1392.33 02-OCT-07:10 0.00 0.00 0.00 0.00 465.30 29-OCT-11:50 304.73 01-OCT-07:00
November 1295.83 01-NOV-09:09 1453.34 03-NOV-07:10 1392.33 01-NOV-07:10 0.00 0.00 0.00 0.00 291.41 19-NOV-11:40 1267.43 11-NOV-09:00
December 1295.83 01-DEC-10:09 1667.75 15-DEC-16:40 1392.33 01-DEC-08:09 0.00 0.00 0.00 0.00 347.98 10-DEC-13:50 1228.16 15-DEC-06:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 1295.83   1161.92   1392.33   0.00 0.00 0.00 0.00 162.66   233.68  
Maximum of Months 1295.83   1667.75   1392.33   0.00 0.00 0.00 0.00 705.90   1391.86  



Table of Contents

Report: PeakSpaceGainsMonthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 232.27 02-JAN-10:09 578.72 02-JAN-08:09 1948.61 01-JAN-00:10 0.00 0.00 0.00 0.00 0.00 0.00
February 232.27 01-FEB-10:09 578.72 01-FEB-08:09 3897.21 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00 0.00
March 232.27 01-MAR-10:09 578.72 01-MAR-08:09 7794.42 31-MAR-23:10 0.00 0.00 0.00 0.00 0.00 0.00
April 232.27 03-APR-09:09 578.72 03-APR-07:10 7794.42 01-APR-00:10 0.00 0.00 0.00 0.00 0.00 0.00
May 232.27 01-MAY-09:09 578.72 01-MAY-07:10 3897.21 31-MAY-23:10 0.00 0.00 0.00 0.00 0.00 0.00
June 232.27 01-JUN-09:09 578.72 01-JUN-07:10 5845.82 30-JUN-23:10 0.00 0.00 0.00 0.00 0.00 0.00
July 232.27 03-JUL-09:09 578.72 03-JUL-07:10 7794.42 31-JUL-23:10 0.00 0.00 0.00 0.00 0.00 0.00
August 232.27 01-AUG-09:09 578.72 01-AUG-07:10 7794.42 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00 0.00
September 232.27 01-SEP-09:09 578.72 01-SEP-07:10 3897.21 30-SEP-23:10 0.00 0.00 0.00 0.00 0.00 0.00
October 232.27 02-OCT-09:09 578.72 02-OCT-07:10 5845.82 31-OCT-23:10 0.00 0.00 0.00 0.00 0.00 0.00
November 232.27 01-NOV-09:09 578.72 01-NOV-07:10 5845.82 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00 0.00
December 232.27 01-DEC-10:09 578.72 01-DEC-08:09 7794.42 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average             0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 232.27   578.72   1948.61   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 232.27   578.72   7794.42   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: DATACENTER_MID_ZN_6

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 232.27 02-JAN-10:09 578.72 02-JAN-08:09 1948.61 01-JAN-00:10 0.00 0.00 0.00 0.00 0.00 0.00
February 232.27 01-FEB-10:09 578.72 01-FEB-08:09 3897.21 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00 0.00
March 232.27 01-MAR-10:09 578.72 01-MAR-08:09 7794.42 31-MAR-23:10 0.00 0.00 0.00 0.00 0.00 0.00
April 232.27 03-APR-09:09 578.72 03-APR-07:10 7794.42 01-APR-00:10 0.00 0.00 0.00 0.00 0.00 0.00
May 232.27 01-MAY-09:09 578.72 01-MAY-07:10 3897.21 31-MAY-23:10 0.00 0.00 0.00 0.00 0.00 0.00
June 232.27 01-JUN-09:09 578.72 01-JUN-07:10 5845.82 30-JUN-23:10 0.00 0.00 0.00 0.00 0.00 0.00
July 232.27 03-JUL-09:09 578.72 03-JUL-07:10 7794.42 31-JUL-23:10 0.00 0.00 0.00 0.00 0.00 0.00
August 232.27 01-AUG-09:09 578.72 01-AUG-07:10 7794.42 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00 0.00
September 232.27 01-SEP-09:09 578.72 01-SEP-07:10 3897.21 30-SEP-23:10 0.00 0.00 0.00 0.00 0.00 0.00
October 232.27 02-OCT-09:09 578.72 02-OCT-07:10 5845.82 31-OCT-23:10 0.00 0.00 0.00 0.00 0.00 0.00
November 232.27 01-NOV-09:09 578.72 01-NOV-07:10 5845.82 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00 0.00
December 232.27 01-DEC-10:09 578.72 01-DEC-08:09 7794.42 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average             0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 232.27   578.72   1948.61   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 232.27   578.72   7794.42   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 232.27 02-JAN-10:09 578.72 02-JAN-08:09 1948.61 01-JAN-00:10 0.00 0.00 0.00 0.00 0.00 0.00
February 232.27 01-FEB-10:09 578.72 01-FEB-08:09 3897.21 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00 0.00
March 232.27 01-MAR-10:09 578.72 01-MAR-08:09 7794.42 31-MAR-23:10 0.00 0.00 0.00 0.00 0.00 0.00
April 232.27 03-APR-09:09 578.72 03-APR-07:10 7794.42 01-APR-00:10 0.00 0.00 0.00 0.00 0.00 0.00
May 232.27 01-MAY-09:09 578.72 01-MAY-07:10 3897.21 31-MAY-23:10 0.00 0.00 0.00 0.00 0.00 0.00
June 232.27 01-JUN-09:09 578.72 01-JUN-07:10 5845.82 30-JUN-23:10 0.00 0.00 0.00 0.00 0.00 0.00
July 232.27 03-JUL-09:09 578.72 03-JUL-07:10 7794.42 31-JUL-23:10 0.00 0.00 0.00 0.00 0.00 0.00
August 232.27 01-AUG-09:09 578.72 01-AUG-07:10 7794.42 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00 0.00
September 232.27 01-SEP-09:09 578.72 01-SEP-07:10 3897.21 30-SEP-23:10 0.00 0.00 0.00 0.00 0.00 0.00
October 232.27 02-OCT-09:09 578.72 02-OCT-07:10 5845.82 31-OCT-23:10 0.00 0.00 0.00 0.00 0.00 0.00
November 232.27 01-NOV-09:09 578.72 01-NOV-07:10 5845.82 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00 0.00
December 232.27 01-DEC-10:09 578.72 01-DEC-08:09 7794.42 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average             0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 232.27   578.72   1948.61   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 232.27   578.72   7794.42   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 5027.92 02-JAN-10:09 6471.01 02-JAN-08:09 94908.13 01-JAN-00:10 0.00 0.00 0.00 0.00 0.00 0.00
February 5027.92 01-FEB-10:09 6471.01 01-FEB-08:09 189816.26 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00 0.00
March 5027.92 01-MAR-10:09 6471.01 01-MAR-08:09 379632.52 31-MAR-23:10 0.00 0.00 0.00 0.00 0.00 0.00
April 5027.92 03-APR-09:09 6471.01 03-APR-07:10 379632.52 01-APR-00:10 0.00 0.00 0.00 0.00 0.00 0.00
May 5027.92 01-MAY-09:09 6471.01 01-MAY-07:10 189816.26 31-MAY-23:10 0.00 0.00 0.00 0.00 0.00 0.00
June 5027.92 01-JUN-09:09 6471.01 01-JUN-07:10 284724.39 30-JUN-23:10 0.00 0.00 0.00 0.00 0.00 0.00
July 5027.92 03-JUL-09:09 6471.01 03-JUL-07:10 379632.52 31-JUL-23:10 0.00 0.00 0.00 0.00 0.00 0.00
August 5027.92 01-AUG-09:09 6471.01 01-AUG-07:10 379632.52 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00 0.00
September 5027.92 01-SEP-09:09 6471.01 01-SEP-07:10 189816.26 30-SEP-23:10 0.00 0.00 0.00 0.00 0.00 0.00
October 5027.92 02-OCT-09:09 6471.01 02-OCT-07:10 284724.39 31-OCT-23:10 0.00 0.00 0.00 0.00 0.00 0.00
November 5027.92 01-NOV-09:09 6471.01 01-NOV-07:10 284724.39 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00 0.00
December 5027.92 01-DEC-10:09 6471.01 01-DEC-08:09 379632.52 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average             0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 5027.92   6471.01   94908.13   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 5027.92   6471.01   379632.52   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: GROUNDFLOOR_PLENUM

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 157.77 29-JAN-12:30 1045.13 24-JAN-03:00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 115.01 02-FEB-14:00 1837.14 04-FEB-05:00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 258.92 05-MAR-13:52 1791.29 16-MAR-02:00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 515.19 15-APR-17:01 569.19 18-APR-24:00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 787.33 29-MAY-16:00 319.94 25-MAY-04:12
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 510.79 25-JUN-14:00 237.17 18-JUN-20:00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 587.77 30-JUL-15:50 214.52 04-JUL-03:00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 601.59 13-AUG-13:00 322.09 14-AUG-02:55
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 585.31 17-SEP-13:52 165.16 19-SEP-23:20
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 416.86 29-OCT-13:51 314.48 16-OCT-04:53
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 161.98 23-NOV-12:00 1705.46 11-NOV-09:00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 344.95 10-DEC-15:00 1706.53 15-DEC-05:55
                       
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00        
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 115.01   165.16  
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 787.33   1837.14  



Table of Contents

Report: PeakSpaceGainsMonthly

For: MIDFLOOR_PLENUM

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 370.27 29-JAN-12:30 1733.67 24-JAN-03:00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 255.88 20-FEB-15:10 3156.23 04-FEB-05:00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 498.24 05-MAR-14:00 3089.94 16-MAR-02:00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 966.09 15-APR-17:01 1012.22 18-APR-23:53
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1450.33 29-MAY-16:00 561.32 25-MAY-05:00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 931.57 25-JUN-14:00 448.70 18-JUN-20:00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1163.21 30-JUL-15:50 404.73 04-JUL-02:55
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1151.80 13-AUG-13:00 569.20 14-AUG-02:55
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1055.40 17-SEP-13:42 289.77 19-SEP-23:20
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 813.94 29-OCT-14:00 546.51 16-OCT-04:53
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 308.44 04-NOV-17:03 2957.39 11-NOV-09:00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 638.38 10-DEC-14:50 2935.58 15-DEC-05:55
                       
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00        
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 255.88   289.77  
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1450.33   3156.23  



Table of Contents

Report: PeakSpaceGainsMonthly

For: TOPFLOOR_PLENUM

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 324.56 29-JAN-12:20 1809.13 24-JAN-03:00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 181.58 02-FEB-14:00 2893.73 04-FEB-05:20
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 278.68 05-MAR-14:00 2953.01 16-MAR-02:00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 844.77 15-APR-17:01 1005.58 18-APR-23:53
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1164.06 29-MAY-16:00 690.59 25-MAY-04:14
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 751.60 16-JUN-21:02 702.75 18-JUN-20:00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 901.19 29-JUL-18:00 622.12 02-JUL-16:00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 942.25 13-AUG-12:50 707.33 14-AUG-02:55
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 773.08 16-SEP-17:02 369.31 19-SEP-23:00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 635.26 29-OCT-11:32 556.96 01-OCT-07:00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 354.75 22-NOV-22:02 2978.65 11-NOV-09:00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 426.86 10-DEC-14:10 2780.13 15-DEC-06:00
                       
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00        
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 181.58   369.31  
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1164.06   2978.65  



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: BASEMENT

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 105498.80 25-JAN-05:12 0.00 10200.53 53830.18 0.00 0.00 0.00 0.00 0.00 0.00
February 109161.00 04-FEB-05:11 0.00 11474.31 121117.90 0.00 0.00 0.00 0.00 0.00 0.00
March 106970.58 16-MAR-04:12 0.00 12750.66 67287.72 0.00 0.00 0.00 0.00 0.00 0.00
April 104536.52 19-APR-04:12 0.00 15300.79 80745.26 0.00 0.00 0.00 0.00 0.00 0.00
May 89064.31 08-MAY-04:11 0.00 17850.93 94202.81 0.00 0.00 0.00 0.00 0.00 0.00
June 85224.33 13-JUN-03:02 0.00 6374.62 67287.72 0.00 0.00 0.00 0.00 0.00 0.00
July 87409.27 04-JUL-15:30 5385.68 7649.54 80745.26 0.00 0.00 0.00 0.00 0.00 0.00
August 86150.01 22-AUG-03:02 0.00 6374.62 67287.72 0.00 0.00 0.00 0.00 0.00 0.00
September 85048.44 04-SEP-24:00 0.00 6374.62 67287.72 0.00 0.00 0.00 0.00 0.00 0.00
October 91945.97 18-OCT-03:02 0.00 6374.62 67287.72 0.00 0.00 0.00 0.00 0.00 0.00
November 108988.80 13-NOV-05:12 0.00 15300.79 80745.26 0.00 0.00 0.00 0.00 0.00 0.00
December 107123.21 21-DEC-05:12 0.00 12750.66 67287.72 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 85048.44   0.00 6374.62 53830.18 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 109161.00   5385.68 17850.93 121117.90 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: CORE_BOTTOM

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 101591.23 30-JAN-05:13 0.00 13741.19 35625.87 0.00 0.00 0.00 0.00 0.00 0.00
February 103182.26 21-FEB-05:13 0.00 16031.39 41563.52 0.00 0.00 0.00 0.00 0.00 0.00
March 102435.06 07-MAR-05:13 0.00 16031.39 41563.52 0.00 0.00 0.00 0.00 0.00 0.00
April 97200.94 19-APR-04:13 0.00 13741.19 35625.87 0.00 0.00 0.00 0.00 0.00 0.00
May 94217.47 26-MAY-03:02 0.00 5724.85 29688.23 0.00 0.00 0.00 0.00 0.00 0.00
June 93484.24 13-JUN-03:02 0.00 5724.85 29688.23 0.00 0.00 0.00 0.00 0.00 0.00
July 77512.77 14-JUL-05:02 8061.19 11450.99 38236.95 0.00 0.00 0.00 0.00 0.00 0.00
August 88363.86 21-AUG-05:03 11285.67 16031.39 53531.73 0.00 0.00 0.00 0.00 0.00 0.00
September 97920.21 06-SEP-04:13 0.00 13741.19 35625.87 0.00 0.00 0.00 0.00 0.00 0.00
October 97025.17 20-OCT-04:13 0.00 16031.39 41563.52 0.00 0.00 0.00 0.00 0.00 0.00
November 101674.97 27-NOV-05:11 0.00 16031.39 41563.52 0.00 0.00 0.00 0.00 0.00 0.00
December 99972.90 18-DEC-05:12 0.00 13741.19 35625.87 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 77512.77   0.00 5724.85 29688.23 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 103182.26   11285.67 16031.39 53531.73 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: CORE_MID

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 88367.99 03-JAN-05:12 0.00 13741.19 35625.74 0.00 0.00 0.00 0.00 0.00 0.00
February 91009.26 13-FEB-05:11 0.00 16031.39 41563.36 0.00 0.00 0.00 0.00 0.00 0.00
March 89439.42 07-MAR-05:11 0.00 16031.39 41563.36 0.00 0.00 0.00 0.00 0.00 0.00
April 89894.39 18-APR-04:12 0.00 13741.19 35625.74 0.00 0.00 0.00 0.00 0.00 0.00
May 89109.06 01-MAY-04:12 0.00 11450.99 29688.11 0.00 0.00 0.00 0.00 0.00 0.00
June 85609.43 06-JUN-05:04 8061.19 11450.99 38236.81 0.00 0.00 0.00 0.00 0.00 0.00
July 84135.69 07-JUL-04:13 0.00 13741.19 35625.74 0.00 0.00 0.00 0.00 0.00 0.00
August 87181.86 24-AUG-03:02 0.00 5724.85 29688.11 0.00 0.00 0.00 0.00 0.00 0.00
September 85152.12 15-SEP-03:02 0.00 5724.85 29688.11 0.00 0.00 0.00 0.00 0.00 0.00
October 91473.61 20-OCT-04:13 0.00 16031.39 41563.36 0.00 0.00 0.00 0.00 0.00 0.00
November 89364.62 08-NOV-05:13 0.00 16031.39 41563.36 0.00 0.00 0.00 0.00 0.00 0.00
December 88175.61 06-DEC-05:12 0.00 13741.19 35625.74 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 84135.69   0.00 5724.85 29688.11 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 91473.61   8061.19 16031.39 41563.36 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: CORE_TOP

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 85458.64 30-JAN-05:12 0.00 13741.19 35625.74 0.00 0.00 0.00 0.00 0.00 0.00
February 86436.35 13-FEB-05:11 0.00 16031.39 41563.36 0.00 0.00 0.00 0.00 0.00 0.00
March 86674.92 31-MAR-04:12 0.00 13741.19 35625.74 0.00 0.00 0.00 0.00 0.00 0.00
April 88086.02 18-APR-04:12 0.00 13741.19 35625.74 0.00 0.00 0.00 0.00 0.00 0.00
May 87091.45 11-MAY-04:12 0.00 13741.19 35625.74 0.00 0.00 0.00 0.00 0.00 0.00
June 85032.43 13-JUN-04:02 0.00 11450.99 29688.11 0.00 0.00 0.00 0.00 0.00 0.00
July 84676.63 15-JUL-04:02 0.00 5724.85 22266.09 0.00 0.00 0.00 0.00 0.00 0.00
August 85008.15 29-AUG-04:02 0.00 11450.99 29688.11 0.00 0.00 0.00 0.00 0.00 0.00
September 85878.03 08-SEP-03:02 0.00 5724.85 29688.11 0.00 0.00 0.00 0.00 0.00 0.00
October 85695.45 20-OCT-04:11 0.00 16031.39 41563.36 0.00 0.00 0.00 0.00 0.00 0.00
November 86893.42 06-NOV-05:12 0.00 13741.19 35625.74 0.00 0.00 0.00 0.00 0.00 0.00
December 85287.26 07-DEC-05:12 0.00 13741.19 35625.74 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 84676.63   0.00 5724.85 22266.09 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 88086.02   0.00 16031.39 41563.36 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 14618.55 30-JAN-05:12 0.00 1725.34 4473.37 0.00 0.00 0.00 0.00 0.00 62.68
February 14664.89 17-FEB-05:11 0.00 2012.90 5218.93 0.00 0.00 0.00 0.00 0.00 121.21
March 15169.10 07-MAR-05:11 0.00 2012.90 5218.93 0.00 0.00 0.00 0.00 0.00 126.76
April 10831.86 17-APR-15:00 1923.11 1231.33 2160.55 0.00 0.00 0.00 0.00 73.88 0.00
May 17624.87 29-MAY-15:52 607.30 410.41 4321.10 0.00 0.00 0.00 0.00 370.60 0.00
June 18923.30 11-JUN-16:11 708.51 478.82 5041.29 0.00 0.00 0.00 0.00 158.82 0.00
July 19309.23 30-JUL-14:22 607.30 410.41 4321.10 0.00 0.00 0.00 0.00 156.24 0.00
August 18834.32 20-AUG-11:42 506.08 342.01 3600.92 0.00 0.00 0.00 0.00 231.54 0.00
September 18439.38 04-SEP-14:22 506.08 342.01 3600.92 0.00 0.00 0.00 0.00 103.39 0.00
October 14807.71 19-OCT-04:11 0.00 2012.90 5218.93 0.00 0.00 0.00 0.00 0.00 37.36
November 14078.12 20-NOV-06:02 1012.16 1437.79 4801.23 0.00 0.00 0.00 0.00 3.43 0.00
December 13837.07 01-DEC-05:11 0.00 2012.90 5218.93 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 10831.86   0.00 342.01 2160.55 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 19309.23   1923.11 2012.90 5218.93 0.00 0.00 0.00 0.00 370.60 126.76



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 19640.16 01-JAN-09:02 326.14 220.40 2320.57 0.00 0.00 0.00 0.00 0.00 61.36
February 14796.86 20-FEB-09:23 260.91 176.32 1856.46 0.00 0.00 0.00 0.00 0.00 211.24
March 10668.44 27-MAR-08:40 1239.33 793.52 1392.34 0.00 0.00 0.00 0.00 0.00 2.43
April 19906.07 09-APR-09:22 326.14 220.40 2320.57 0.00 0.00 0.00 0.00 0.00 33.06
May 19820.26 07-MAY-08:52 326.14 220.40 2320.57 0.00 0.00 0.00 0.00 0.00 12.49
June 20583.32 11-JUN-09:32 391.37 264.49 2784.68 0.00 0.00 0.00 0.00 37.20 0.00
July 20483.40 16-JUL-09:12 391.37 264.49 2784.68 0.00 0.00 0.00 0.00 17.17 0.00
August 19040.36 20-AUG-11:42 326.14 220.40 2320.57 0.00 0.00 0.00 0.00 150.15 0.00
September 17312.22 10-SEP-09:52 326.14 220.40 2320.57 0.00 0.00 0.00 0.00 53.00 0.00
October 19895.32 09-OCT-08:42 326.14 220.40 2320.57 0.00 0.00 0.00 0.00 10.67 0.00
November 9800.43 07-NOV-09:00 1239.33 793.52 1392.34 0.00 0.00 0.00 0.00 0.00 0.00
December 7948.88 03-DEC-10:02 260.91 176.32 1856.46 0.00 0.00 0.00 0.00 0.00 102.89
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 7948.88   260.91 176.32 1392.34 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 20583.32   1239.33 793.52 2784.68 0.00 0.00 0.00 0.00 150.15 211.24



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 21393.94 15-JAN-13:52 607.31 410.42 4321.17 0.00 0.00 0.00 0.00 0.00 195.45
February 20967.20 20-FEB-12:02 506.09 342.02 3600.97 0.00 0.00 0.00 0.00 0.00 234.93
March 19769.69 12-MAR-13:32 506.09 342.02 3600.97 0.00 0.00 0.00 0.00 0.00 109.80
April 19073.57 09-APR-13:22 506.09 342.02 3600.97 0.00 0.00 0.00 0.00 31.19 0.00
May 17332.10 29-MAY-15:52 607.31 410.42 4321.17 0.00 0.00 0.00 0.00 370.68 0.00
June 18467.82 11-JUN-16:11 708.53 478.83 5041.36 0.00 0.00 0.00 0.00 170.98 0.00
July 19573.08 30-JUL-14:22 607.31 410.42 4321.17 0.00 0.00 0.00 0.00 150.33 0.00
August 19470.38 20-AUG-12:22 506.09 342.02 3600.97 0.00 0.00 0.00 0.00 204.10 0.00
September 19883.92 24-SEP-11:43 404.87 273.61 2880.78 0.00 0.00 0.00 0.00 147.96 0.00
October 21938.18 29-OCT-12:41 708.53 478.83 5041.36 0.00 0.00 0.00 0.00 45.16 0.00
November 21522.61 19-NOV-12:42 607.31 410.42 4321.17 0.00 0.00 0.00 0.00 0.00 101.68
December 22594.59 03-DEC-14:01 809.75 547.23 5761.56 0.00 0.00 0.00 0.00 0.00 95.36
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 17332.10   404.87 273.61 2880.78 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 22594.59   809.75 547.23 5761.56 0.00 0.00 0.00 0.00 370.68 234.93



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 18398.49 30-JAN-05:12 0.00 1111.88 2882.79 0.00 0.00 0.00 0.00 0.00 40.94
February 25330.25 19-FEB-16:12 391.37 264.49 2784.67 0.00 0.00 0.00 0.00 0.00 4.80
March 25598.06 12-MAR-16:12 391.37 264.49 2784.67 0.00 0.00 0.00 0.00 0.00 78.96
April 26855.61 09-APR-16:41 521.82 352.65 3712.89 0.00 0.00 0.00 0.00 0.00 22.24
May 25377.48 29-MAY-16:32 391.37 264.49 2784.67 0.00 0.00 0.00 0.00 199.65 0.00
June 26623.32 11-JUN-14:51 456.59 308.57 3248.78 0.00 0.00 0.00 0.00 41.05 0.00
July 26233.66 09-JUL-16:31 456.59 308.57 3248.78 0.00 0.00 0.00 0.00 68.21 0.00
August 26423.02 20-AUG-16:21 456.59 308.57 3248.78 0.00 0.00 0.00 0.00 58.99 0.00
September 25245.39 17-SEP-16:02 391.37 264.49 2784.67 0.00 0.00 0.00 0.00 139.38 0.00
October 26315.95 09-OCT-15:22 391.37 264.49 2784.67 0.00 0.00 0.00 0.00 25.64 0.00
November 25665.21 26-NOV-15:02 391.37 264.49 2784.67 0.00 0.00 0.00 0.00 0.00 156.14
December 27154.46 03-DEC-15:21 456.59 308.57 3248.78 0.00 0.00 0.00 0.00 0.00 47.87
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 18398.49   0.00 264.49 2784.67 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 27154.46   521.82 1111.88 3712.89 0.00 0.00 0.00 0.00 199.65 156.14



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 9956.79 14-JAN-06:03 809.73 1150.23 3840.98 0.00 0.00 0.00 0.00 0.00 15.72
February 10552.93 18-FEB-06:03 809.73 1150.23 3840.98 0.00 0.00 0.00 0.00 0.00 21.63
March 11947.51 06-MAR-06:02 1012.16 1437.79 4801.23 0.00 0.00 0.00 0.00 0.00 34.25
April 10901.71 15-APR-05:03 809.73 1150.23 3840.98 0.00 0.00 0.00 0.00 0.00 10.29
May 18851.34 29-MAY-15:41 809.73 547.22 5761.47 0.00 0.00 0.00 0.00 729.36 0.00
June 17974.34 25-JUN-14:32 506.08 342.01 3600.92 0.00 0.00 0.00 0.00 263.00 0.00
July 18629.78 04-JUL-16:31 809.73 547.22 5761.47 0.00 0.00 0.00 0.00 223.97 0.00
August 15928.24 20-AUG-12:22 506.08 342.01 3600.92 0.00 0.00 0.00 0.00 544.95 0.00
September 17822.50 17-SEP-15:51 809.73 547.22 5761.47 0.00 0.00 0.00 0.00 531.87 0.00
October 13687.13 19-OCT-04:11 0.00 2012.90 5218.93 0.00 0.00 0.00 0.00 0.00 92.52
November 13131.24 29-NOV-06:03 809.73 1150.23 3840.98 0.00 0.00 0.00 0.00 19.30 0.00
December 12997.27 09-DEC-06:02 1012.16 1437.79 4801.23 0.00 0.00 0.00 0.00 11.51 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 9956.79   0.00 342.01 3600.92 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 18851.34   1012.16 2012.90 5761.47 0.00 0.00 0.00 0.00 729.36 92.52



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 19846.44 01-JAN-10:12 326.14 220.40 2320.57 0.00 0.00 0.00 0.00 0.00 39.98
February 12432.78 26-FEB-10:02 260.91 176.32 1856.46 0.00 0.00 0.00 0.00 0.00 181.49
March 10311.04 27-MAR-10:20 1239.33 793.52 1392.34 0.00 0.00 0.00 0.00 6.94 0.00
April 20784.34 09-APR-09:22 326.14 220.40 2320.57 0.00 0.00 0.00 0.00 0.00 85.01
May 20712.56 07-MAY-10:22 326.14 220.40 2320.57 0.00 0.00 0.00 0.00 53.39 0.00
June 19920.43 11-JUN-09:42 326.14 220.40 2320.57 0.00 0.00 0.00 0.00 120.77 0.00
July 21706.66 04-JUL-08:32 391.37 264.49 2784.68 0.00 0.00 0.00 0.00 11.61 0.00
August 20468.26 27-AUG-09:32 326.14 220.40 2320.57 0.00 0.00 0.00 0.00 160.28 0.00
September 20685.25 24-SEP-08:52 326.14 220.40 2320.57 0.00 0.00 0.00 0.00 71.90 0.00
October 20544.24 09-OCT-08:52 326.14 220.40 2320.57 0.00 0.00 0.00 0.00 29.54 0.00
November 9722.86 07-NOV-09:30 1239.33 793.52 1392.34 0.00 0.00 0.00 0.00 1.88 0.00
December 7788.98 08-DEC-10:00 1239.33 793.52 1392.34 0.00 0.00 0.00 0.00 25.62 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 7788.98   260.91 176.32 1392.34 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 21706.66   1239.33 793.52 2784.68 0.00 0.00 0.00 0.00 160.28 181.49



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 20596.89 01-JAN-13:32 607.31 410.42 4321.17 0.00 0.00 0.00 0.00 0.00 134.96
February 19973.65 26-FEB-12:42 506.09 342.02 3600.97 0.00 0.00 0.00 0.00 0.00 239.17
March 19381.77 26-MAR-13:52 506.09 342.02 3600.97 0.00 0.00 0.00 0.00 0.00 9.69
April 17771.51 16-APR-17:12 0.00 342.02 2795.90 0.00 0.00 0.00 0.00 263.73 0.00
May 18664.92 29-MAY-15:41 809.75 547.23 5761.56 0.00 0.00 0.00 0.00 732.18 0.00
June 17585.42 25-JUN-14:32 506.09 342.02 3600.97 0.00 0.00 0.00 0.00 277.56 0.00
July 18131.76 04-JUL-15:51 809.75 547.23 5761.56 0.00 0.00 0.00 0.00 379.22 0.00
August 18500.46 20-AUG-12:22 506.09 342.02 3600.97 0.00 0.00 0.00 0.00 484.65 0.00
September 19736.86 17-SEP-14:31 708.53 478.83 5041.36 0.00 0.00 0.00 0.00 308.76 0.00
October 21080.94 29-OCT-12:11 708.53 478.83 5041.36 0.00 0.00 0.00 0.00 121.83 0.00
November 20732.66 19-NOV-13:52 607.31 410.42 4321.17 0.00 0.00 0.00 0.00 0.00 284.94
December 22022.21 03-DEC-13:51 809.75 547.23 5761.56 0.00 0.00 0.00 0.00 0.00 240.30
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 17585.42   0.00 342.02 2795.90 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 22022.21   809.75 547.23 5761.56 0.00 0.00 0.00 0.00 732.18 284.94



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 9761.42 14-JAN-06:03 521.82 741.25 2475.26 0.00 0.00 0.00 0.00 0.00 11.67
February 22455.48 19-FEB-16:01 521.82 352.65 3712.89 0.00 0.00 0.00 0.00 0.00 12.10
March 20505.92 12-MAR-16:22 326.14 220.40 2320.55 0.00 0.00 0.00 0.00 0.00 166.53
April 24422.33 02-APR-16:41 456.59 308.57 3248.78 0.00 0.00 0.00 0.00 0.00 163.19
May 24716.95 29-MAY-15:41 521.82 352.65 3712.89 0.00 0.00 0.00 0.00 365.11 0.00
June 21607.22 25-JUN-14:32 326.14 220.40 2320.55 0.00 0.00 0.00 0.00 172.28 0.00
July 24581.35 04-JUL-16:31 521.82 352.65 3712.89 0.00 0.00 0.00 0.00 77.32 0.00
August 22980.15 13-AUG-16:01 587.05 396.73 4177.00 0.00 0.00 0.00 0.00 194.05 0.00
September 24642.79 17-SEP-15:51 521.82 352.65 3712.89 0.00 0.00 0.00 0.00 175.33 0.00
October 23371.89 09-OCT-16:12 391.37 264.49 2784.67 0.00 0.00 0.00 0.00 44.94 0.00
November 18263.68 19-NOV-15:12 391.37 264.49 2784.67 0.00 0.00 0.00 0.00 0.00 12.21
December 23062.63 10-DEC-15:41 456.59 308.57 3248.78 0.00 0.00 0.00 0.00 46.28 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 9761.42   326.14 220.40 2320.55 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 24716.95   587.05 741.25 4177.00 0.00 0.00 0.00 0.00 365.11 166.53



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 7913.15 14-JAN-06:03 809.73 1150.23 3840.98 0.00 0.00 0.00 0.00 0.00 22.75
February 8341.34 18-FEB-06:03 809.73 1150.23 3840.98 0.00 0.00 0.00 0.00 0.00 29.80
March 13423.55 06-MAR-06:02 1012.16 1437.79 4801.23 0.00 0.00 0.00 0.00 0.00 43.10
April 13861.87 16-APR-17:12 0.00 342.01 2795.85 0.00 0.00 0.00 0.00 320.71 0.00
May 21484.45 29-MAY-15:41 809.73 547.22 5761.47 0.00 0.00 0.00 0.00 827.73 0.00
June 20361.45 25-JUN-14:32 506.08 342.01 3600.92 0.00 0.00 0.00 0.00 288.88 0.00
July 21255.36 04-JUL-16:31 809.73 547.22 5761.47 0.00 0.00 0.00 0.00 233.36 0.00
August 20263.94 20-AUG-12:12 506.08 342.01 3600.92 0.00 0.00 0.00 0.00 639.63 0.00
September 20626.91 17-SEP-15:51 809.73 547.22 5761.47 0.00 0.00 0.00 0.00 556.02 0.00
October 15244.23 31-OCT-05:02 1012.16 1437.79 4801.23 0.00 0.00 0.00 0.00 0.00 52.12
November 14840.62 10-NOV-06:02 1012.16 1437.79 4801.23 0.00 0.00 0.00 0.00 0.00 13.47
December 10436.09 09-DEC-06:02 1012.16 1437.79 4801.23 0.00 0.00 0.00 0.00 12.75 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 7913.15   0.00 342.01 2795.85 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 21484.45   1012.16 1437.79 5761.47 0.00 0.00 0.00 0.00 827.73 52.12



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 7564.00 01-JAN-10:32 260.91 176.32 1856.46 0.00 0.00 0.00 0.00 0.00 19.44
February 8133.23 28-FEB-10:10 1295.83 793.52 1392.34 0.00 0.00 0.00 0.00 3.43 0.00
March 10632.57 31-MAR-09:30 1295.83 793.52 1392.34 0.00 0.00 0.00 0.00 0.00 1.43
April 20214.51 16-APR-09:52 326.14 220.40 2320.57 0.00 0.00 0.00 0.00 1.17 0.00
May 20989.69 07-MAY-10:32 326.14 220.40 2320.57 0.00 0.00 0.00 0.00 67.32 0.00
June 20277.75 11-JUN-09:42 326.14 220.40 2320.57 0.00 0.00 0.00 0.00 142.70 0.00
July 21982.11 04-JUL-08:32 391.37 264.49 2784.68 0.00 0.00 0.00 0.00 12.04 0.00
August 20900.11 20-AUG-08:52 326.14 220.40 2320.57 0.00 0.00 0.00 0.00 139.10 0.00
September 21008.81 24-SEP-08:52 326.14 220.40 2320.57 0.00 0.00 0.00 0.00 82.76 0.00
October 17943.95 22-OCT-09:53 260.91 176.32 1856.46 0.00 0.00 0.00 0.00 44.31 0.00
November 9934.87 10-NOV-06:02 652.28 926.56 3094.09 0.00 0.00 0.00 0.00 0.00 8.92
December 7655.18 08-DEC-10:30 1295.83 793.52 1392.34 0.00 0.00 0.00 0.00 36.66 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 7564.00   260.91 176.32 1392.34 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 21982.11   1295.83 926.56 3094.09 0.00 0.00 0.00 0.00 142.70 19.44



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 22811.27 15-JAN-14:22 607.31 410.42 4321.17 0.00 0.00 0.00 0.00 0.00 593.29
February 22055.90 26-FEB-14:32 506.09 342.02 3600.97 0.00 0.00 0.00 0.00 0.00 278.50
March 20939.05 12-MAR-14:12 506.09 342.02 3600.97 0.00 0.00 0.00 0.00 0.00 290.71
April 20166.64 16-APR-17:12 0.00 342.02 2795.90 0.00 0.00 0.00 0.00 296.23 0.00
May 21453.44 29-MAY-15:41 809.75 547.23 5761.56 0.00 0.00 0.00 0.00 832.88 0.00
June 20212.53 25-JUN-14:32 506.09 342.02 3600.97 0.00 0.00 0.00 0.00 300.12 0.00
July 21039.89 04-JUL-15:51 809.75 547.23 5761.56 0.00 0.00 0.00 0.00 408.33 0.00
August 20953.53 20-AUG-12:12 506.09 342.02 3600.97 0.00 0.00 0.00 0.00 578.33 0.00
September 22485.72 17-SEP-14:31 708.53 478.83 5041.36 0.00 0.00 0.00 0.00 329.50 0.00
October 22095.32 29-OCT-13:02 607.31 410.42 4321.17 0.00 0.00 0.00 0.00 245.18 0.00
November 22011.74 19-NOV-15:32 506.09 342.02 3600.97 0.00 0.00 0.00 0.00 0.00 207.47
December 23683.18 10-DEC-15:01 708.53 478.83 5041.36 0.00 0.00 0.00 0.00 0.00 99.19
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 20166.64   0.00 342.02 2795.90 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 23683.18   809.75 547.23 5761.56 0.00 0.00 0.00 0.00 832.88 593.29



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 9285.15 03-JAN-15:40 1239.33 793.52 1392.33 0.00 0.00 0.00 0.00 35.46 0.00
February 23473.04 19-FEB-16:12 391.37 264.49 2784.67 0.00 0.00 0.00 0.00 0.00 12.03
March 23511.09 12-MAR-16:52 391.37 264.49 2784.67 0.00 0.00 0.00 0.00 0.00 242.80
April 24226.56 09-APR-16:12 391.37 264.49 2784.67 0.00 0.00 0.00 0.00 0.00 33.66
May 26754.78 29-MAY-15:41 521.82 352.65 3712.89 0.00 0.00 0.00 0.00 412.54 0.00
June 23330.16 25-JUN-14:32 326.14 220.40 2320.55 0.00 0.00 0.00 0.00 193.31 0.00
July 26630.39 04-JUL-16:31 521.82 352.65 3712.89 0.00 0.00 0.00 0.00 72.35 0.00
August 24661.09 20-AUG-16:11 587.05 396.73 4177.00 0.00 0.00 0.00 0.00 163.07 0.00
September 26631.76 17-SEP-15:51 521.82 352.65 3712.89 0.00 0.00 0.00 0.00 181.55 0.00
October 23821.27 22-OCT-15:52 326.14 220.40 2320.55 0.00 0.00 0.00 0.00 50.64 0.00
November 18059.14 19-NOV-15:32 326.14 220.40 2320.55 0.00 0.00 0.00 0.00 0.00 26.66
December 24565.87 10-DEC-15:41 456.59 308.57 3248.78 0.00 0.00 0.00 0.00 45.24 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 9285.15   326.14 220.40 1392.33 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 26754.78   1239.33 793.52 4177.00 0.00 0.00 0.00 0.00 412.54 242.80



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: GROUNDFLOOR_PLENUM

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 11040.37 03-JAN-06:02 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 38.73
February 10035.15 13-FEB-06:02 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 101.75
March 9507.31 28-MAR-05:03 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 19.13
April 10494.56 17-APR-05:03 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 85.63
May 11758.12 24-MAY-05:03 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 15.06
June 10096.38 06-JUN-05:02 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 12347.95 05-JUL-05:03 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.34 0.00
August 12447.08 21-AUG-05:15 0.00 0.00 0.00 0.00 0.00 0.00 0.00 14.78 0.00
September 14310.38 18-SEP-05:02 0.00 0.00 0.00 0.00 0.00 0.00 0.00 18.38 0.00
October 12409.81 16-OCT-05:02 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 69.99
November 10423.69 08-NOV-06:03 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 25.24
December 9783.35 11-DEC-06:03 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 27.88
                       
Annual Sum or Average     0.00 0.00 0.00 0.00 0.00 0.00 0.00    
Minimum of Months 9507.31   0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 14310.38   0.00 0.00 0.00 0.00 0.00 0.00 0.00 18.38 101.75



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: MIDFLOOR_PLENUM

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 6538.48 02-JAN-17:00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 3.18
February 6366.66 04-FEB-06:02 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 734.73
March 7436.76 30-MAR-16:00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 39.63 0.00
April 7814.30 14-APR-16:00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 123.21 0.00
May 9792.34 20-MAY-05:03 0.00 0.00 0.00 0.00 0.00 0.00 0.00 24.22 0.00
June 9982.47 28-JUN-05:02 0.00 0.00 0.00 0.00 0.00 0.00 0.00 22.72 0.00
July 10465.30 06-JUL-05:02 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 15.54
August 8886.65 23-AUG-15:50 0.00 0.00 0.00 0.00 0.00 0.00 0.00 215.88 0.00
September 9964.79 30-SEP-05:03 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 12.67
October 9456.08 25-OCT-05:03 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 31.24
November 9858.52 10-NOV-06:02 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 28.69
December 6973.94 08-DEC-17:00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 17.23 0.00
                       
Annual Sum or Average     0.00 0.00 0.00 0.00 0.00 0.00 0.00    
Minimum of Months 6366.66   0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 10465.30   0.00 0.00 0.00 0.00 0.00 0.00 0.00 215.88 734.73



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: TOPFLOOR_PLENUM

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 13611.83 02-JAN-15:00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 84.88 0.00
February 13649.34 17-FEB-14:10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 44.69 0.00
March 17514.89 27-MAR-15:00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 53.62 0.00
April 19786.67 13-APR-14:00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 111.39 0.00
May 20809.66 22-MAY-13:40 0.00 0.00 0.00 0.00 0.00 0.00 0.00 320.84 0.00
June 21707.51 09-JUN-14:00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 119.61 0.00
July 23127.28 28-JUL-15:30 0.00 0.00 0.00 0.00 0.00 0.00 0.00 162.35 0.00
August 22275.12 23-AUG-14:00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 260.61 0.00
September 20538.77 08-SEP-14:50 0.00 0.00 0.00 0.00 0.00 0.00 0.00 111.75 0.00
October 19845.84 06-OCT-13:10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 60.94 0.00
November 16072.50 10-NOV-14:30 0.00 0.00 0.00 0.00 0.00 0.00 0.00 76.24 0.00
December 13910.53 08-DEC-14:40 0.00 0.00 0.00 0.00 0.00 0.00 0.00 36.99 0.00
                       
Annual Sum or Average     0.00 0.00 0.00 0.00 0.00 0.00 0.00    
Minimum of Months 13611.83   0.00 0.00 0.00 0.00 0.00 0.00 0.00 36.99 0.00
Maximum of Months 23127.28   0.00 0.00 0.00 0.00 0.00 0.00 0.00 320.84 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 2189.59 24-JAN-17:00 222.14 578.72 1948.61 0.00 0.00 0.00 0.00 0.00 0.00
February 4316.70 20-FEB-17:50 23.38 64.31 7794.42 0.00 0.00 0.00 0.00 0.00 0.00
March 7229.83 31-MAR-24:00 0.00 32.15 7794.42 0.00 0.00 0.00 0.00 0.00 0.00
April 7964.60 09-APR-17:50 0.00 64.31 15588.84 0.00 0.00 0.00 0.00 0.00 0.00
May 3530.48 31-MAY-24:00 0.00 32.15 3897.21 0.00 0.00 0.00 0.00 0.00 0.00
June 5370.69 30-JUN-23:47 0.00 96.46 17537.45 0.00 0.00 0.00 0.00 0.00 0.00
July 7279.34 31-JUL-23:40 0.00 64.31 15588.84 0.00 0.00 0.00 0.00 0.00 0.00
August 7840.71 20-AUG-18:10 0.00 192.92 46766.53 0.00 0.00 0.00 0.00 0.00 0.00
September 3472.36 30-SEP-23:45 0.00 128.61 15588.84 0.00 0.00 0.00 0.00 0.00 0.00
October 5409.42 31-OCT-24:00 0.00 32.15 5845.82 0.00 0.00 0.00 0.00 0.00 0.00
November 6140.92 07-NOV-17:00 222.14 578.72 5845.82 0.00 0.00 0.00 0.00 0.00 0.00
December 8056.14 06-DEC-17:00 222.14 578.72 7794.42 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 2189.59   0.00 32.15 1948.61 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 8056.14   222.14 578.72 46766.53 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: DATACENTER_MID_ZN_6

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 1983.74 24-JAN-17:00 222.14 578.72 1948.61 0.00 0.00 0.00 0.00 0.00 0.00
February 3948.68 21-FEB-17:50 70.15 321.51 3897.21 0.00 0.00 0.00 0.00 0.00 0.00
March 6990.36 31-MAR-24:00 0.00 32.15 7794.42 0.00 0.00 0.00 0.00 0.00 0.00
April 7474.09 09-APR-17:51 0.00 225.07 54560.95 0.00 0.00 0.00 0.00 0.00 0.00
May 3403.30 31-MAY-24:00 0.00 32.15 3897.21 0.00 0.00 0.00 0.00 0.00 0.00
June 5192.07 30-JUN-23:53 0.00 128.61 23383.27 0.00 0.00 0.00 0.00 0.00 0.00
July 7010.33 31-JUL-23:55 0.00 128.61 31177.69 0.00 0.00 0.00 0.00 0.00 0.00
August 7417.31 30-AUG-16:00 222.14 578.72 7794.42 0.00 0.00 0.00 0.00 0.00 0.00
September 3291.46 30-SEP-23:45 0.00 128.61 15588.84 0.00 0.00 0.00 0.00 0.00 0.00
October 5094.44 31-OCT-24:00 0.00 32.15 5845.82 0.00 0.00 0.00 0.00 0.00 0.00
November 5844.75 07-NOV-17:00 222.14 578.72 5845.82 0.00 0.00 0.00 0.00 0.00 0.00
December 7639.80 06-DEC-17:00 222.14 578.72 7794.42 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 1983.74   0.00 32.15 1948.61 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 7639.80   222.14 578.72 54560.95 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 2019.17 02-JAN-17:00 222.14 578.72 1948.61 0.00 0.00 0.00 0.00 0.00 0.00
February 4005.86 21-FEB-17:50 70.15 321.51 3897.21 0.00 0.00 0.00 0.00 0.00 0.00
March 6931.40 31-MAR-24:00 0.00 32.15 7794.42 0.00 0.00 0.00 0.00 0.00 0.00
April 7692.92 09-APR-17:51 0.00 225.07 54560.95 0.00 0.00 0.00 0.00 0.00 0.00
May 3411.64 31-MAY-24:00 0.00 32.15 3897.21 0.00 0.00 0.00 0.00 0.00 0.00
June 5181.81 30-JUN-23:15 0.00 128.61 23383.27 0.00 0.00 0.00 0.00 0.00 0.00
July 7029.39 31-JUL-23:55 0.00 128.61 31177.69 0.00 0.00 0.00 0.00 0.00 0.00
August 7584.15 20-AUG-18:11 0.00 225.07 54560.95 0.00 0.00 0.00 0.00 0.00 0.00
September 3332.88 30-SEP-23:35 0.00 128.61 15588.84 0.00 0.00 0.00 0.00 0.00 0.00
October 5006.95 31-OCT-24:00 0.00 32.15 5845.82 0.00 0.00 0.00 0.00 0.00 0.00
November 5908.71 07-NOV-17:00 222.14 578.72 5845.82 0.00 0.00 0.00 0.00 0.00 0.00
December 7704.53 06-DEC-17:00 222.14 578.72 7794.42 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 2019.17   0.00 32.15 1948.61 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 7704.53   222.14 578.72 54560.95 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 94484.31 02-JAN-17:00 4808.68 6471.01 94908.13 0.00 0.00 0.00 0.00 0.00 0.00
February 185771.74 21-FEB-17:00 4808.68 6471.01 189816.26 0.00 0.00 0.00 0.00 0.00 0.00
March 360095.23 31-MAR-24:00 0.00 359.47 379632.52 0.00 0.00 0.00 0.00 0.00 0.00
April 370080.19 17-APR-21:02 1518.53 4314.17 2277795.13 0.00 0.00 0.00 0.00 0.00 0.00
May 177048.12 31-MAY-24:00 0.00 359.47 189816.26 0.00 0.00 0.00 0.00 0.00 0.00
June 268627.10 30-JUN-23:53 0.00 1437.90 1138897.57 0.00 0.00 0.00 0.00 0.00 0.00
July 357520.45 31-JUL-23:35 0.00 718.95 759265.04 0.00 0.00 0.00 0.00 0.00 0.00
August 370406.01 28-AUG-12:20 4808.68 6471.01 379632.52 0.00 0.00 0.00 0.00 0.00 0.00
September 176973.82 30-SEP-23:53 0.00 1437.90 759265.04 0.00 0.00 0.00 0.00 0.00 0.00
October 269342.00 31-OCT-24:00 0.00 359.47 284724.39 0.00 0.00 0.00 0.00 0.00 0.00
November 278116.79 07-NOV-17:00 4808.68 6471.01 284724.39 0.00 0.00 0.00 0.00 0.00 0.00
December 369959.13 11-DEC-17:00 4808.68 6471.01 379632.52 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 94484.31   0.00 359.47 94908.13 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 370406.01   4808.68 6471.01 2277795.13 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: EnergyConsumptionElectricityNaturalGasMonthly

For: Meter

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

ELECTRICITY:FACILITY [J] ELECTRICITY:FACILITY {Maximum} [W] ELECTRICITY:FACILITY {TIMESTAMP} NATURALGAS:FACILITY [J] NATURALGAS:FACILITY {Maximum} [W] NATURALGAS:FACILITY {TIMESTAMP}
January 0.199516E+13 1472126.24 02-JAN-16:00 0.619201E+11 263713.89 25-JAN-06:10
February 0.221772E+13 1602858.54 16-FEB-16:30 0.566513E+11 413137.05 04-FEB-06:10
March 0.295963E+13 1776109.49 09-MAR-16:10 0.606891E+11 308995.19 16-MAR-05:10
April 0.330456E+13 1951409.77 11-APR-15:20 0.523973E+11 66510.97 13-APR-11:39
May 0.233595E+13 1496277.38 31-MAY-07:00 0.535886E+11 64736.63 03-MAY-11:39
June 0.277486E+13 1670454.92 08-JUN-15:00 0.513579E+11 62308.94 01-JUN-11:30
July 0.324339E+13 1852449.64 27-JUL-15:00 0.501750E+11 60509.37 03-JUL-11:39
August 0.372971E+13 1989371.34 23-AUG-15:09 0.531097E+11 61825.93 30-AUG-11:30
September 0.232772E+13 1514146.46 21-SEP-15:30 0.506204E+11 63559.74 22-SEP-11:00
October 0.274289E+13 1663923.92 03-OCT-15:09 0.537753E+11 66495.56 25-OCT-11:39
November 0.294189E+13 1806104.57 09-NOV-16:00 0.547747E+11 107544.13 13-NOV-06:10
December 0.324501E+13 1955321.76 08-DEC-16:00 0.618581E+11 277139.50 15-DEC-06:10
             
Annual Sum or Average 0.338185E+14     0.660918E+12    
Minimum of Months 0.199516E+13 1472126.24   0.501750E+11 60509.37  
Maximum of Months 0.372971E+13 1989371.34   0.619201E+11 413137.05  



Table of Contents

Report: EndUseEnergyConsumptionElectricityMonthly

For: Meter

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

INTERIORLIGHTS:ELECTRICITY [J] EXTERIORLIGHTS:ELECTRICITY [J] INTERIOREQUIPMENT:ELECTRICITY [J] EXTERIOREQUIPMENT:ELECTRICITY [J] FANS:ELECTRICITY [J] PUMPS:ELECTRICITY [J] HEATING:ELECTRICITY [J] COOLING:ELECTRICITY [J] HEATREJECTION:ELECTRICITY [J] HUMIDIFIER:ELECTRICITY [J] HEATRECOVERY:ELECTRICITY [J] WATERSYSTEMS:ELECTRICITY [] COGENERATION:ELECTRICITY []
January 0.330547E+12 0.686491E+11 0.766053E+12 0.164269E+12 0.174073E+12 0.597424E+11 0.00 0.289378E+12 0.133580E+12 0.336016E+09 0.853130E+10 0.00 0.00
February 0.298011E+12 0.585207E+11 0.978954E+12 0.148381E+12 0.161531E+12 0.548837E+11 0.00 0.372073E+12 0.137115E+12 0.352186E+09 0.789758E+10 0.00 0.00
March 0.351987E+12 0.600811E+11 0.141687E+13 0.164522E+12 0.185479E+12 0.722806E+11 0.00 0.532925E+12 0.165589E+12 0.294780E+09 0.960015E+10 0.00 0.00
April 0.313785E+12 0.535380E+11 0.165903E+13 0.158945E+12 0.184235E+12 0.792390E+11 0.00 0.669819E+12 0.175952E+12 0.00 0.100182E+11 0.00 0.00
May 0.337563E+12 0.511676E+11 0.774844E+12 0.164394E+12 0.199960E+12 0.864232E+11 0.00 0.499277E+12 0.211958E+12 0.00 0.103626E+11 0.00 0.00
June 0.336019E+12 0.476302E+11 0.106252E+13 0.159183E+12 0.199920E+12 0.958140E+11 0.00 0.638724E+12 0.224170E+12 0.00 0.108845E+11 0.00 0.00
July 0.314239E+12 0.498202E+11 0.139340E+13 0.164156E+12 0.205867E+12 0.101008E+12 0.00 0.770085E+12 0.233370E+12 0.00 0.114446E+11 0.00 0.00
August 0.350561E+12 0.534823E+11 0.173200E+13 0.164521E+12 0.208889E+12 0.104439E+12 0.00 0.867233E+12 0.237050E+12 0.00 0.115385E+11 0.00 0.00
September 0.314713E+12 0.561982E+11 0.740713E+12 0.158944E+12 0.198429E+12 0.929205E+11 0.00 0.534634E+12 0.220708E+12 0.00 0.104629E+11 0.00 0.00
October 0.328015E+12 0.628449E+11 0.108340E+13 0.164269E+12 0.200001E+12 0.885213E+11 0.00 0.593933E+12 0.211755E+12 0.00 0.101517E+11 0.00 0.00
November 0.325864E+12 0.650772E+11 0.135889E+13 0.159042E+12 0.183957E+12 0.759065E+11 0.00 0.581936E+12 0.182032E+12 89708180.50 0.909374E+10 0.00 0.00
December 0.320949E+12 0.695473E+11 0.170972E+13 0.164158E+12 0.177416E+12 0.677057E+11 0.00 0.565392E+12 0.160951E+12 72110416.25 0.909467E+10 0.00 0.00
                           
Annual Sum or Average 0.392225E+13 0.696557E+12 0.146764E+14 0.193478E+13 0.227976E+13 0.978884E+12 0.00 0.691541E+13 0.229423E+13 0.114480E+10 0.119080E+12 0.00 0.00
Minimum of Months 0.298011E+12 0.476302E+11 0.740713E+12 0.148381E+12 0.161531E+12 0.548837E+11 0.00 0.289378E+12 0.133580E+12 0.00 0.789758E+10 0.00 0.00
Maximum of Months 0.351987E+12 0.695473E+11 0.173200E+13 0.164522E+12 0.208889E+12 0.104439E+12 0.00 0.867233E+12 0.237050E+12 0.352186E+09 0.115385E+11 0.00 0.00



Table of Contents

Report: EndUseEnergyConsumptionNaturalGasMonthly

For: Meter

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

INTERIOREQUIPMENT:NATURALGAS [] EXTERIOREQUIPMENT:NATURALGAS [] HEATING:NATURALGAS [J] COOLING:NATURALGAS [] WATERSYSTEMS:NATURALGAS [J] COGENERATION:NATURALGAS [] HUMIDIFIER:NATURALGAS []
January 0.00 0.00 0.495670E+10 0.00 0.569634E+11 0.00 0.00
February 0.00 0.00 0.530566E+10 0.00 0.513456E+11 0.00 0.00
March 0.00 0.00 0.284004E+10 0.00 0.578491E+11 0.00 0.00
April 0.00 0.00 261102.97 0.00 0.523970E+11 0.00 0.00
May 0.00 0.00 0.00 0.00 0.535886E+11 0.00 0.00
June 0.00 0.00 0.00 0.00 0.513579E+11 0.00 0.00
July 0.00 0.00 0.00 0.00 0.501750E+11 0.00 0.00
August 0.00 0.00 0.00 0.00 0.531097E+11 0.00 0.00
September 0.00 0.00 0.00 0.00 0.506204E+11 0.00 0.00
October 0.00 0.00 0.00 0.00 0.537753E+11 0.00 0.00
November 0.00 0.00 0.824225E+09 0.00 0.539505E+11 0.00 0.00
December 0.00 0.00 0.615636E+10 0.00 0.557018E+11 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.200832E+11 0.00 0.640834E+12 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.501750E+11 0.00 0.00
Maximum of Months 0.00 0.00 0.615636E+10 0.00 0.578491E+11 0.00 0.00



Table of Contents

Report: PeakEnergyEndUseElectricityPart1Monthly

For: Meter

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

INTERIORLIGHTS:ELECTRICITY {Maximum} [W] INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} EXTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] EXTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} FANS:ELECTRICITY {Maximum} [W] FANS:ELECTRICITY {TIMESTAMP} PUMPS:ELECTRICITY {Maximum} [W] PUMPS:ELECTRICITY {TIMESTAMP} HEATING:ELECTRICITY {Maximum} [W] HEATING:ELECTRICITY {TIMESTAMP}
January 372703.55 04-JAN-16:00 57580.60 01-JAN-06:10 423497.50 02-JAN-08:09 118506.10 30-JAN-08:20 126664.49 14-JAN-06:10 65917.57 02-JAN-10:09 0.00 01-JAN-00:10
February 348291.11 08-FEB-16:00 57580.60 01-FEB-06:10 541788.89 01-FEB-08:09 118502.42 07-FEB-08:20 121028.21 02-FEB-06:10 65525.23 13-FEB-14:00 0.00 01-FEB-00:10
March 357001.62 15-MAR-07:10 57580.60 01-MAR-06:10 660080.29 01-MAR-08:09 118512.89 15-MAR-07:19 135604.69 30-MAR-15:30 66136.61 14-MAR-10:30 0.00 01-MAR-00:10
April 358353.79 12-APR-07:10 57580.60 01-APR-05:10 778371.69 03-APR-07:10 118513.95 12-APR-07:19 134528.35 14-APR-15:39 66647.50 17-APR-09:50 0.00 01-APR-00:10
May 343374.53 25-MAY-07:10 57580.60 01-MAY-05:10 423497.50 01-MAY-07:10 118502.27 25-MAY-07:19 142434.18 08-MAY-05:10 66399.77 30-MAY-09:39 0.00 01-MAY-00:10
June 375276.56 15-JUN-07:10 57580.60 01-JUN-05:10 541788.89 01-JUN-07:10 118527.17 15-JUN-07:19 141078.02 23-JUN-05:10 66165.94 12-JUN-14:50 0.00 01-JUN-00:10
July 343374.53 05-JUL-07:10 57580.60 01-JUL-05:10 660080.29 03-JUL-07:10 118502.27 05-JUL-07:19 148464.98 28-JUL-15:30 66952.05 31-JUL-12:09 0.00 01-JUL-00:10
August 358353.79 28-AUG-07:10 57580.60 01-AUG-05:10 778371.69 01-AUG-07:10 118513.95 28-AUG-07:19 148849.04 31-AUG-15:20 66337.41 11-AUG-09:09 0.00 01-AUG-00:10
September 385834.94 27-SEP-07:10 57580.60 01-SEP-05:10 423497.50 01-SEP-07:10 118535.44 27-SEP-07:19 145888.48 08-SEP-15:30 66357.57 25-SEP-09:30 0.00 01-SEP-00:10
October 372703.55 18-OCT-07:10 57580.60 01-OCT-05:10 541788.89 02-OCT-07:10 118525.16 18-OCT-07:19 144186.71 06-OCT-15:00 69624.76 13-OCT-15:50 0.00 01-OCT-00:10
November 369206.61 29-NOV-16:00 57580.60 01-NOV-05:10 660080.29 01-NOV-07:10 118518.28 24-NOV-08:20 137033.89 22-NOV-06:10 66231.16 01-NOV-10:09 0.00 01-NOV-00:10
December 385834.94 15-DEC-16:40 57580.60 01-DEC-06:10 778371.69 01-DEC-08:09 118525.16 29-DEC-08:20 128563.38 08-DEC-15:39 65176.82 08-DEC-14:39 0.00 01-DEC-00:10
                             
Annual Sum or Average                            
Minimum of Months 343374.53   57580.60   423497.50   118502.27   121028.21   65176.82   0.00  
Maximum of Months 385834.94   57580.60   778371.69   118535.44   148849.04   69624.76   0.00  



Table of Contents

Report: PeakEnergyEndUseElectricityPart2Monthly

For: Meter

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

COOLING:ELECTRICITY {Maximum} [W] COOLING:ELECTRICITY {TIMESTAMP} HEATREJECTION:ELECTRICITY {Maximum} [W] HEATREJECTION:ELECTRICITY {TIMESTAMP} HUMIDIFIER:ELECTRICITY {Maximum} [W] HUMIDIFIER:ELECTRICITY {TIMESTAMP} HEATRECOVERY:ELECTRICITY {Maximum} [W] HEATRECOVERY:ELECTRICITY {TIMESTAMP} WATERSYSTEMS:ELECTRICITY [] COGENERATION:ELECTRICITY []
January 341583.56 02-JAN-13:00 98044.59 02-JAN-09:20 3673.02 25-JAN-01:00 5613.48 01-JAN-08:39 0.00 0.00
February 368549.54 17-FEB-10:39 98044.59 02-FEB-08:20 4077.20 04-FEB-05:00 5613.48 01-FEB-06:10 0.00 0.00
March 418473.80 27-MAR-14:50 98044.59 03-MAR-11:39 2982.05 16-MAR-17:00 5613.48 01-MAR-06:10 0.00 0.00
April 469203.56 13-APR-13:09 98044.59 01-APR-13:50 0.00 01-APR-00:10 5613.48 01-APR-04:30 0.00 0.00
May 384970.84 24-MAY-14:39 98044.59 01-MAY-07:30 0.00 01-MAY-00:10 5613.48 01-MAY-04:30 0.00 0.00
June 432197.46 23-JUN-13:00 98044.59 01-JUN-05:30 0.00 01-JUN-00:10 5613.48 01-JUN-03:30 0.00 0.00
July 470364.74 31-JUL-12:20 98044.59 01-JUL-03:20 0.00 01-JUL-00:10 5613.48 01-JUL-03:20 0.00 0.00
August 495044.09 15-AUG-12:09 98044.59 01-AUG-00:10 0.00 01-AUG-00:10 5613.48 01-AUG-00:10 0.00 0.00
September 377532.81 19-SEP-12:09 98044.59 01-SEP-00:10 0.00 01-SEP-00:10 5613.48 01-SEP-00:10 0.00 0.00
October 404845.23 10-OCT-12:50 98044.59 01-OCT-00:40 0.00 01-OCT-00:10 5613.48 01-OCT-12:20 0.00 0.00
November 433914.55 30-NOV-16:40 98044.59 01-NOV-09:20 2342.50 13-NOV-05:00 5613.48 01-NOV-04:19 0.00 0.00
December 452063.24 08-DEC-14:50 98044.59 01-DEC-13:39 2548.03 20-DEC-19:19 5613.48 01-DEC-05:30 0.00 0.00
                     
Annual Sum or Average                 0.00 0.00
Minimum of Months 341583.56   98044.59   0.00   5613.48   0.00 0.00
Maximum of Months 495044.09   98044.59   4077.20   5613.48   0.00 0.00



Table of Contents

Report: ElectricComponentsOfPeakDemandMonthly

For: Meter

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

ELECTRICITY:FACILITY {Maximum} [W] ELECTRICITY:FACILITY {TIMESTAMP} INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] EXTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] FANS:ELECTRICITY {AT MAX/MIN} [W] PUMPS:ELECTRICITY {AT MAX/MIN} [W] HEATING:ELECTRICITY {AT MAX/MIN} [W] COOLING:ELECTRICITY {AT MAX/MIN} [W] HEATREJECTION:ELECTRICITY {AT MAX/MIN} [W]
January 1472126.24 02-JAN-16:00 350141.41 423497.50 0.00 84459.03 117386.25 63901.72 0.00 329082.26 98044.59
February 1602858.54 16-FEB-16:30 334652.47 541788.89 0.00 84451.06 112078.70 63962.94 0.00 362266.42 98044.59
March 1776109.49 09-MAR-16:10 332294.83 660080.29 0.00 84450.25 119560.02 63777.76 0.00 412288.28 98044.59
April 1951409.77 11-APR-15:20 332294.83 778371.69 0.00 84450.25 130240.92 64141.07 0.00 458252.96 98044.59
May 1496277.38 31-MAY-07:00 332294.83 423497.50 0.00 118493.64 106728.05 66037.32 0.00 345567.99 98044.59
June 1670454.92 08-JUN-15:00 332294.83 541788.89 0.00 84450.25 138515.25 65253.13 0.00 404494.50 98044.59
July 1852449.64 27-JUL-15:00 332294.83 660080.29 0.00 84450.25 147781.15 65410.86 0.00 458774.20 98044.59
August 1989371.34 23-AUG-15:09 332294.83 778371.69 0.00 84450.25 145084.46 65457.65 0.00 480054.41 98044.59
September 1514146.46 21-SEP-15:30 332294.83 423497.50 0.00 84450.25 143065.02 65317.65 0.00 361863.15 98044.59
October 1663923.92 03-OCT-15:09 332294.83 541788.89 0.00 84450.25 138827.55 65102.68 0.00 397801.67 98044.59
November 1806104.57 09-NOV-16:00 346052.92 660080.29 0.00 84457.04 113579.26 65058.31 0.00 433218.70 98044.59
December 1955321.76 08-DEC-16:00 352499.06 778371.69 0.00 84464.15 123815.22 64022.68 0.00 448490.91 98044.59
                       
Annual Sum or Average                      
Minimum of Months 1472126.24   332294.83 423497.50 0.00 84450.25 106728.05 63777.76 0.00 329082.26 98044.59
Maximum of Months 1989371.34   352499.06 778371.69 0.00 118493.64 147781.15 66037.32 0.00 480054.41 98044.59



Table of Contents

Report: PeakEnergyEndUseNaturalGasMonthly

For: Meter

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

INTERIOREQUIPMENT:NATURALGAS [] EXTERIOREQUIPMENT:NATURALGAS [] HEATING:NATURALGAS {Maximum} [W] HEATING:NATURALGAS {TIMESTAMP} COOLING:NATURALGAS [] WATERSYSTEMS:NATURALGAS {Maximum} [W] WATERSYSTEMS:NATURALGAS {TIMESTAMP} COGENERATION:NATURALGAS []
January 0.00 0.00 255567.31 25-JAN-06:10 0.00 70632.11 23-JAN-12:50 0.00
February 0.00 0.00 404990.47 04-FEB-06:10 0.00 70496.40 02-FEB-12:50 0.00
March 0.00 0.00 300848.61 16-MAR-05:10 0.00 69496.77 02-MAR-12:39 0.00
April 0.00 0.00 286.30 19-APR-05:00 0.00 66510.97 13-APR-11:39 0.00
May 0.00 0.00 0.00 01-MAY-00:10 0.00 64736.63 03-MAY-11:39 0.00
June 0.00 0.00 0.00 01-JUN-00:10 0.00 62308.94 01-JUN-11:30 0.00
July 0.00 0.00 0.00 01-JUL-00:10 0.00 60509.37 03-JUL-11:39 0.00
August 0.00 0.00 0.00 01-AUG-00:10 0.00 61825.93 30-AUG-11:30 0.00
September 0.00 0.00 0.00 01-SEP-00:10 0.00 63559.74 22-SEP-11:00 0.00
October 0.00 0.00 0.00 01-OCT-00:10 0.00 66495.56 25-OCT-11:39 0.00
November 0.00 0.00 99397.55 13-NOV-06:10 0.00 69182.43 30-NOV-12:20 0.00
December 0.00 0.00 268992.92 15-DEC-06:10 0.00 70387.05 29-DEC-12:50 0.00
                 
Annual Sum or Average 0.00 0.00     0.00     0.00
Minimum of Months 0.00 0.00 0.00   0.00 60509.37   0.00
Maximum of Months 0.00 0.00 404990.47   0.00 70632.11   0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: BASEMENT

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 9.50 26.95 0.33 26.91
February 0.00 0.00 0.00 0.00 7.67 27.03 0.33 27.04
March 0.00 0.00 0.00 0.00 2.17 26.03 0.00 26.03
April 0.00 0.00 0.00 0.00 2.67 26.22 0.00 26.22
May 0.00 0.00 0.00 0.00 7.83 26.69 0.17 26.71
June 0.00 0.00 0.00 0.00 4.33 25.98 0.17 25.93
July 0.00 0.00 0.00 0.00 6.83 26.06 0.17 26.09
August 0.00 0.00 0.00 0.00 9.83 25.97 0.17 25.95
September 0.00 0.00 0.00 0.00 9.00 26.24 0.33 26.28
October 0.00 0.00 0.00 0.00 9.33 26.17 0.17 26.15
November 0.00 0.00 0.00 0.00 11.83 26.63 1.83 26.70
December 0.00 0.00 0.00 0.00 7.83 26.48 0.50 26.53
                 
Annual Sum or Average 0.00   0.00   88.83 26.43 4.17 26.45
Minimum of Months 0.00 0.00 0.00 0.00 2.17 25.97 0.00 25.93
Maximum of Months 0.00 0.00 0.00 0.00 11.83 27.03 1.83 27.04



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: CORE_BOTTOM

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.17 25.57 0.00 25.57
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.17 25.57 0.00 25.57
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.17 25.57 0.00 25.57



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: CORE_MID

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: CORE_TOP

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 1.50 27.29 1.00 27.38
June 0.00 0.00 0.00 0.00 1.50 26.95 1.00 27.10
July 0.00 0.00 0.00 0.00 5.17 27.20 4.00 27.30
August 0.00 0.00 0.00 0.00 2.83 27.04 2.00 27.21
September 0.00 0.00 0.00 0.00 0.33 25.58 0.00 25.58
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   11.33 27.09 8.00 27.23
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 5.17 27.29 4.00 27.38



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.83 27.83 0.83 27.83
February 0.00 0.00 0.00 0.00 1.17 27.51 1.17 27.51
March 0.00 0.00 0.00 0.00 0.33 27.30 0.33 27.30
April 0.00 0.00 0.00 0.00 4.67 27.74 4.67 27.74
May 0.00 0.00 0.00 0.00 4.17 27.56 4.17 27.56
June 0.00 0.00 0.00 0.00 5.33 27.68 5.33 27.68
July 0.00 0.00 0.00 0.00 11.83 27.84 11.50 27.85
August 0.00 0.00 0.00 0.00 3.50 27.68 3.50 27.68
September 0.00 0.00 0.00 0.00 6.67 27.65 6.67 27.65
October 0.00 0.00 0.00 0.00 1.67 27.83 1.67 27.83
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   40.17 27.72 39.83 27.72
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 11.83 27.84 11.50 27.85



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 17.67 26.07 17.67 26.07
February 0.00 0.00 0.00 0.00 18.33 25.79 18.33 25.79
March 0.00 0.00 0.00 0.00 3.50 26.78 3.50 26.78
April 0.00 0.00 0.00 0.00 3.33 27.48 3.17 27.49
May 0.00 0.00 0.00 0.00 1.33 27.49 1.17 27.50
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 3.83 27.31 3.50 27.38
August 0.00 0.00 0.00 0.00 4.83 27.26 3.67 27.41
September 0.00 0.00 0.00 0.00 9.33 27.49 7.00 27.64
October 0.00 0.00 0.00 0.00 19.17 26.46 18.00 26.45
November 0.00 0.00 0.00 0.00 37.17 25.52 37.17 25.52
December 0.00 0.00 0.00 0.00 24.67 25.98 24.67 25.98
                 
Annual Sum or Average 0.00   0.00   143.17 26.16 137.83 26.15
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 37.17 27.49 37.17 27.64



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.50 27.30 0.50 27.30
February 0.00 0.00 0.00 0.00 4.33 27.93 3.50 28.06
March 0.00 0.00 0.00 0.00 12.83 27.14 4.67 27.31
April 0.00 0.00 0.00 0.00 22.00 27.52 7.33 27.70
May 0.00 0.00 0.00 0.00 9.67 27.61 4.33 27.69
June 0.00 0.00 0.00 0.00 16.67 27.06 5.17 27.24
July 0.00 0.00 0.00 0.00 28.17 27.37 10.00 27.56
August 0.00 0.00 0.00 0.00 35.33 27.40 10.67 27.55
September 0.00 0.00 0.00 0.00 11.33 27.50 5.83 27.66
October 0.00 0.00 0.00 0.00 15.67 27.37 7.50 27.55
November 0.00 0.00 0.00 0.00 12.50 27.18 5.17 27.36
December 0.00 0.00 0.00 0.00 13.50 27.37 6.67 27.55
                 
Annual Sum or Average 0.00   0.00   182.50 27.37 71.33 27.54
Minimum of Months 0.00 0.00 0.00 0.00 0.50 27.06 0.50 27.24
Maximum of Months 0.00 0.00 0.00 0.00 35.33 27.93 10.67 28.06



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 1.50 27.50 1.17 27.51
June 0.00 0.00 0.00 0.00 1.00 27.35 0.83 27.36
July 0.00 0.00 0.00 0.00 2.83 27.43 2.17 27.44
August 0.00 0.00 0.00 0.00 0.33 27.28 0.33 27.28
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   5.67 27.43 4.50 27.43
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 2.83 27.50 2.17 27.51



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.50 27.70 0.50 27.70
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.17 27.40 0.17 27.40
April 0.00 0.00 0.00 0.00 5.17 27.88 5.00 27.89
May 0.00 0.00 0.00 0.00 4.67 27.66 4.67 27.66
June 0.00 0.00 0.00 0.00 6.83 27.83 6.83 27.83
July 0.00 0.00 0.00 0.00 13.33 28.01 12.83 28.02
August 0.00 0.00 0.00 0.00 5.33 27.75 5.33 27.75
September 0.00 0.00 0.00 0.00 8.17 27.76 8.00 27.76
October 0.00 0.00 0.00 0.00 2.50 27.73 2.50 27.73
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   46.67 27.84 45.83 27.84
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 13.33 28.01 12.83 28.02



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 33.67 25.44 33.67 25.44
February 0.00 0.00 0.00 0.00 23.50 25.62 23.33 25.62
March 0.00 0.00 0.00 0.00 4.50 26.12 4.50 26.12
April 0.00 0.00 0.00 0.00 1.17 27.56 1.17 27.56
May 0.00 0.00 0.00 0.00 1.33 27.50 1.17 27.52
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 1.83 27.51 1.83 27.51
August 0.00 0.00 0.00 0.00 2.33 27.59 2.33 27.59
September 0.00 0.00 0.00 0.00 10.00 27.31 7.50 27.40
October 0.00 0.00 0.00 0.00 36.67 25.76 35.17 25.73
November 0.00 0.00 0.00 0.00 46.83 25.56 46.67 25.55
December 0.00 0.00 0.00 0.00 29.50 25.88 29.17 25.88
                 
Annual Sum or Average 0.00   0.00   191.33 25.81 186.50 25.79
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 46.83 27.59 46.67 27.59



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 1.83 28.13 1.83 28.13
March 0.00 0.00 0.00 0.00 1.50 28.00 1.17 27.99
April 0.00 0.00 0.00 0.00 6.17 28.13 3.33 28.17
May 0.00 0.00 0.00 0.00 4.67 28.01 2.83 28.04
June 0.00 0.00 0.00 0.00 3.17 28.01 2.17 28.05
July 0.00 0.00 0.00 0.00 9.33 27.94 5.33 28.01
August 0.00 0.00 0.00 0.00 5.50 27.89 3.00 28.03
September 0.00 0.00 0.00 0.00 6.17 27.96 4.00 28.02
October 0.00 0.00 0.00 0.00 4.33 28.00 4.00 28.01
November 0.00 0.00 0.00 0.00 0.67 27.63 0.67 27.63
December 0.00 0.00 0.00 0.00 1.00 27.81 1.00 27.81
                 
Annual Sum or Average 0.00   0.00   44.33 27.98 29.33 28.03
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 9.33 28.13 5.33 28.17



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.17 18.84 0.00 18.84 0.00 18.84 0.00 18.84
March 0.17 19.38 0.00 19.38 0.00 19.38 0.00 19.38
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 3.00 27.59 2.50 27.59
June 0.00 0.00 0.00 0.00 3.17 27.58 2.67 27.58
July 0.00 0.00 0.00 0.00 9.33 27.59 7.17 27.60
August 0.00 0.00 0.00 0.00 3.33 27.55 3.00 27.55
September 0.00 0.00 0.00 0.00 4.33 27.48 3.83 27.48
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.17 19.38 0.00 19.38 0.00 19.38 0.00 19.38
                 
Annual Sum or Average 0.50 19.20 0.00 19.20 23.17 27.38 19.17 27.47
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.17 19.38 0.00 19.38 9.33 27.59 7.17 27.60



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.33 27.43 0.33 27.43
February 0.17 18.89 0.00 18.89 0.00 18.89 0.00 18.89
March 0.00 0.00 0.00 0.00 0.33 27.35 0.33 27.35
April 0.00 0.00 0.00 0.00 6.00 27.85 5.67 27.85
May 0.00 0.00 0.00 0.00 6.67 27.76 6.33 27.76
June 0.00 0.00 0.00 0.00 8.00 27.94 7.17 27.96
July 0.00 0.00 0.00 0.00 15.67 28.13 13.33 28.17
August 0.00 0.00 0.00 0.00 7.33 27.83 7.00 27.83
September 0.00 0.00 0.00 0.00 9.33 27.92 8.33 27.95
October 0.00 0.00 0.00 0.00 4.17 27.61 4.17 27.61
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.17 18.89 0.00 18.89 57.83 27.89 52.67 27.92
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.17 18.89 0.00 18.89 15.67 28.13 13.33 28.17



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 10.83 26.35 10.83 26.35
February 0.17 19.16 0.00 19.16 11.33 26.12 11.00 26.15
March 0.00 0.00 0.00 0.00 2.67 27.65 2.67 27.65
April 0.00 0.00 0.00 0.00 3.33 27.59 3.00 27.59
May 0.00 0.00 0.00 0.00 2.83 27.61 2.33 27.62
June 0.00 0.00 0.00 0.00 2.67 27.48 2.33 27.48
July 0.00 0.00 0.00 0.00 7.83 27.60 6.50 27.62
August 0.00 0.00 0.00 0.00 4.83 27.61 4.00 27.66
September 0.00 0.00 0.00 0.00 11.67 27.67 8.00 27.80
October 0.00 0.00 0.00 0.00 19.67 26.66 17.50 26.62
November 0.00 0.00 0.00 0.00 31.33 25.60 31.00 25.59
December 0.00 0.00 0.00 0.00 16.33 26.28 16.00 26.27
                 
Annual Sum or Average 0.17 19.16 0.00 19.16 125.33 26.54 115.17 26.52
Minimum of Months 0.00 0.00 0.00 0.00 2.67 25.60 2.33 25.59
Maximum of Months 0.17 19.16 0.00 19.16 31.33 27.67 31.00 27.80



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.17 19.08 0.00 19.08 2.00 27.38 1.83 27.73
March 0.00 0.00 0.00 0.00 1.50 28.14 1.17 28.12
April 0.00 0.00 0.00 0.00 6.33 28.26 3.83 28.29
May 0.00 0.00 0.00 0.00 5.17 28.14 3.17 28.17
June 0.00 0.00 0.00 0.00 4.33 28.04 2.67 28.10
July 0.00 0.00 0.00 0.00 10.67 28.16 6.17 28.20
August 0.00 0.00 0.00 0.00 6.67 27.98 3.83 28.10
September 0.00 0.00 0.00 0.00 7.33 28.10 4.83 28.14
October 0.00 0.00 0.00 0.00 5.00 28.06 4.50 28.08
November 0.00 0.00 0.00 0.00 1.33 27.55 1.17 27.57
December 0.00 0.00 0.00 0.00 1.17 27.78 1.17 27.78
                 
Annual Sum or Average 0.17 19.08 0.00 19.08 51.50 28.06 34.33 28.11
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.17 19.08 0.00 19.08 10.67 28.26 6.17 28.29



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: GROUNDFLOOR_PLENUM

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: MIDFLOOR_PLENUM

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: TOPFLOOR_PLENUM

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 12.33 27.63 12.33 27.63
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   12.33 27.63 12.33 27.63
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 12.33 27.63 12.33 27.63



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: DATACENTER_MID_ZN_6

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.33 27.58 0.33 27.58
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.33 27.58 0.33 27.58
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.33 27.58 0.33 27.58



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 147.83 28.19 137.50 28.19
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.83 27.78 0.00 27.78
August 0.00 0.00 0.00 0.00 666.17 28.79 477.83 28.88
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 64.00 27.91 63.00 27.92
                 
Annual Sum or Average 0.00   0.00   878.83 28.63 678.33 28.68
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 666.17 28.79 477.83 28.88



Table of Contents

Report: ComfortReportSimple55Monthly

For: BASEMENT

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 121.83 25.49 435.50 24.87 121.83 24.98
February 101.67 25.19 391.83 24.78 101.67 24.85
March 133.50 25.19 451.00 24.68 133.50 24.78
April 195.17 25.21 481.33 24.75 195.17 24.85
May 268.00 25.02 508.00 24.70 268.00 24.78
June 264.33 24.92 496.00 24.64 264.33 24.71
July 260.17 25.23 497.00 24.84 260.17 24.94
August 222.83 25.14 514.00 24.69 222.83 24.80
September 247.83 25.14 485.00 24.77 247.83 24.87
October 219.83 25.43 502.00 24.88 219.83 25.01
November 173.50 25.42 487.50 24.85 173.50 24.97
December 140.33 25.59 476.17 24.87 140.33 25.01
             
Annual Sum or Average 2349.00 25.21 5725.33 24.77 2349.00 24.87
Minimum of Months 101.67 24.92 391.83 24.64 101.67 24.71
Maximum of Months 268.00 25.59 514.00 24.88 268.00 25.01



Table of Contents

Report: ComfortReportSimple55Monthly

For: CORE_BOTTOM

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 17.67 23.59 386.00 24.35 0.00 24.35
February 15.00 23.49 369.50 24.34 0.00 24.34
March 1.00 23.84 432.50 24.25 0.00 24.25
April 0.00 0.00 476.50 24.14 0.00 24.14
May 0.00 0.00 482.50 24.18 0.00 24.18
June 0.00 0.00 479.50 24.13 0.00 24.13
July 0.00 0.00 493.00 24.13 0.00 24.13
August 0.00 0.00 512.83 24.11 0.00 24.11
September 0.00 0.00 463.50 24.20 0.00 24.20
October 0.00 0.00 495.67 24.22 0.00 24.22
November 0.00 0.00 481.33 24.30 0.00 24.30
December 0.00 0.00 451.00 24.32 0.00 24.32
             
Annual Sum or Average 33.67 23.56 5523.83 24.22 0.00 24.22
Minimum of Months 0.00 0.00 369.50 24.11 0.00 24.11
Maximum of Months 17.67 23.84 512.83 24.35 0.00 24.35



Table of Contents

Report: ComfortReportSimple55Monthly

For: CORE_MID

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 125.33 23.13 213.33 23.85 0.00 23.85
February 92.50 23.06 229.17 23.97 0.00 23.97
March 77.33 23.19 286.00 24.05 0.00 24.05
April 26.83 23.15 315.33 24.18 0.00 24.18
May 17.50 23.17 370.50 24.15 0.00 24.15
June 20.67 23.14 370.17 24.11 0.00 24.11
July 26.33 23.19 330.33 24.08 0.00 24.08
August 22.17 23.15 359.17 24.11 0.00 24.11
September 19.50 23.18 348.33 24.14 0.00 24.14
October 10.17 23.17 399.67 24.22 0.00 24.22
November 24.00 23.20 356.00 24.27 0.00 24.27
December 104.33 23.04 248.67 23.91 0.00 23.91
             
Annual Sum or Average 566.67 23.12 3826.67 24.09 0.00 24.09
Minimum of Months 10.17 23.04 213.33 23.85 0.00 23.85
Maximum of Months 125.33 23.20 399.67 24.27 0.00 24.27



Table of Contents

Report: ComfortReportSimple55Monthly

For: CORE_TOP

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 260.33 22.85 138.50 23.29 0.00 23.29
February 146.67 22.66 205.00 23.60 0.00 23.60
March 111.83 22.94 279.00 23.88 0.00 23.88
April 32.67 23.15 331.33 24.15 0.00 24.15
May 4.50 23.15 420.67 24.21 0.00 24.21
June 2.00 23.22 415.67 24.18 0.00 24.18
July 3.33 23.24 423.50 24.17 0.00 24.17
August 8.17 22.87 419.33 24.14 0.00 24.14
September 0.33 23.28 395.17 24.21 0.00 24.21
October 15.33 23.20 385.50 24.24 0.00 24.24
November 67.33 22.93 307.83 24.04 0.00 24.04
December 201.00 22.77 174.00 23.44 0.00 23.44
             
Annual Sum or Average 853.50 22.84 3895.50 23.97 0.00 23.97
Minimum of Months 0.33 22.66 138.50 23.29 0.00 23.29
Maximum of Months 260.33 23.28 423.50 24.24 0.00 24.24



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 179.33 22.98 221.50 23.68 2.67 23.68
February 97.00 23.08 291.83 23.96 5.33 23.98
March 88.00 23.21 362.83 24.04 4.67 24.05
April 2.83 24.01 446.83 24.24 0.67 24.24
May 11.67 26.43 507.33 24.42 11.67 24.47
June 7.83 26.74 496.00 24.39 7.83 24.43
July 24.67 26.73 497.00 24.56 24.67 24.66
August 14.83 26.70 514.00 24.37 14.83 24.43
September 5.00 26.86 485.00 24.43 5.00 24.45
October 0.50 26.74 498.00 24.37 0.50 24.37
November 10.00 23.05 433.50 24.25 0.00 24.25
December 110.17 23.05 309.50 23.95 0.00 23.95
             
Annual Sum or Average 551.83 23.49 5063.33 24.24 77.83 24.27
Minimum of Months 0.50 22.98 221.50 23.68 0.00 23.68
Maximum of Months 179.33 26.86 514.00 24.56 24.67 24.66



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 158.33 22.94 257.17 23.83 8.83 23.88
February 90.17 23.19 289.50 24.06 10.17 24.11
March 71.00 23.06 364.50 24.02 5.17 24.04
April 50.50 24.48 407.83 24.30 19.33 24.40
May 28.00 26.44 489.00 24.49 27.00 24.59
June 24.00 26.75 488.67 24.44 24.00 24.54
July 50.33 26.81 489.67 24.66 50.33 24.85
August 24.17 26.09 481.50 24.33 20.00 24.42
September 32.33 26.72 473.67 24.58 32.33 24.71
October 15.00 26.25 458.33 24.44 12.83 24.50
November 30.67 23.20 403.00 24.17 2.00 24.18
December 156.50 22.68 241.33 23.62 0.33 23.62
             
Annual Sum or Average 731.00 23.91 4844.17 24.27 212.33 24.36
Minimum of Months 15.00 22.68 241.33 23.62 0.33 23.62
Maximum of Months 158.33 26.81 489.67 24.66 50.33 24.85



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 103.00 24.29 376.67 24.51 34.67 24.66
February 60.50 24.66 381.67 24.55 27.83 24.69
March 57.67 24.18 427.50 24.33 19.67 24.41
April 17.83 26.35 453.50 24.40 15.67 24.48
May 12.83 26.41 505.00 24.42 12.83 24.47
June 4.83 26.77 496.00 24.35 4.83 24.37
July 23.50 26.72 497.00 24.53 23.50 24.63
August 18.83 26.81 513.33 24.41 18.83 24.49
September 30.67 26.93 485.00 24.64 30.67 24.77
October 39.83 27.02 501.00 24.76 39.83 24.92
November 44.50 26.36 468.00 24.74 39.83 24.89
December 80.00 24.91 408.67 24.61 40.17 24.78
             
Annual Sum or Average 494.00 25.36 5513.33 24.52 308.33 24.63
Minimum of Months 4.83 24.18 376.67 24.33 4.83 24.37
Maximum of Months 103.00 27.02 513.33 24.76 40.17 24.92



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 116.83 22.90 300.17 23.98 4.50 24.00
February 60.17 24.37 379.17 24.49 22.17 24.60
March 48.00 25.28 457.00 24.57 27.50 24.69
April 42.00 26.94 485.00 24.71 42.00 24.87
May 29.67 26.89 508.00 24.59 29.67 24.71
June 29.83 26.81 496.00 24.56 29.83 24.68
July 57.67 26.81 497.00 24.80 57.67 24.99
August 58.50 26.80 514.00 24.72 58.50 24.91
September 30.50 26.84 485.00 24.62 30.50 24.74
October 36.17 26.92 502.00 24.69 36.17 24.83
November 31.33 26.28 481.17 24.63 26.50 24.74
December 48.83 25.65 450.17 24.69 32.83 24.83
             
Annual Sum or Average 589.50 25.56 5554.67 24.60 397.83 24.74
Minimum of Months 29.67 22.90 300.17 23.98 4.50 24.00
Maximum of Months 116.83 26.94 514.00 24.80 58.50 24.99



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_MID_ZN_3

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 344.50 22.40 110.50 22.79 8.83 22.79
February 218.83 22.59 179.83 23.21 22.67 23.20
March 197.83 22.74 275.67 23.59 25.00 23.64
April 53.33 24.00 384.67 24.24 18.83 24.29
May 36.17 25.96 505.83 24.49 36.17 24.59
June 25.83 26.38 496.00 24.50 25.83 24.59
July 27.17 26.55 497.00 24.60 27.17 24.69
August 35.50 26.02 500.50 24.47 35.50 24.57
September 18.33 26.11 481.67 24.47 18.33 24.53
October 38.17 25.70 468.50 24.51 36.00 24.60
November 117.17 23.44 334.50 24.06 26.17 24.12
December 287.67 22.51 171.50 23.13 29.00 23.19
             
Annual Sum or Average 1400.50 23.12 4406.17 24.04 309.50 24.11
Minimum of Months 18.33 22.40 110.50 22.79 8.83 22.79
Maximum of Months 344.50 26.55 505.83 24.60 36.17 24.69



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_MID_ZN_2

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 236.33 22.50 134.17 23.20 10.00 23.24
February 153.33 22.69 186.83 23.54 16.33 23.57
March 126.33 23.11 260.67 23.95 22.00 24.03
April 73.83 24.84 326.17 24.59 40.50 24.76
May 45.33 26.30 409.00 24.68 44.67 24.83
June 42.17 26.66 417.33 24.70 42.17 24.86
July 60.00 26.85 420.83 24.92 60.00 25.14
August 52.17 25.79 410.33 24.62 41.50 24.78
September 47.50 26.63 397.50 24.79 47.50 24.97
October 52.83 25.97 377.17 24.77 46.17 24.93
November 82.67 23.55 290.50 24.21 21.00 24.30
December 250.67 22.49 156.00 23.21 25.50 23.30
             
Annual Sum or Average 1223.17 23.74 3786.50 24.31 417.33 24.46
Minimum of Months 42.17 22.49 134.17 23.20 10.00 23.24
Maximum of Months 250.67 26.85 420.83 24.92 60.00 25.14



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_MID_ZN_1

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 133.17 23.84 346.33 24.39 39.33 24.54
February 92.33 23.98 344.00 24.39 35.50 24.52
March 97.50 23.81 385.83 24.25 35.17 24.36
April 41.17 25.21 421.83 24.45 29.17 24.55
May 36.17 25.89 503.17 24.48 36.17 24.57
June 21.50 26.19 496.00 24.44 21.50 24.51
July 24.33 26.50 497.00 24.55 24.33 24.64
August 39.50 26.21 501.83 24.52 39.50 24.64
September 45.33 26.72 485.00 24.72 45.33 24.88
October 70.33 26.78 497.50 24.94 69.83 25.14
November 87.17 25.59 451.50 24.81 66.83 24.98
December 154.67 24.24 357.50 24.50 64.83 24.70
             
Annual Sum or Average 843.17 24.91 5287.50 24.55 507.50 24.68
Minimum of Months 21.50 23.81 344.00 24.25 21.50 24.36
Maximum of Months 154.67 26.78 503.17 24.94 69.83 25.14



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_MID_ZN_4

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 292.50 22.31 145.83 22.94 5.00 22.95
February 176.50 22.70 225.83 23.59 24.83 23.65
March 136.17 22.93 342.83 23.97 26.00 24.07
April 55.50 25.37 422.00 24.56 38.00 24.71
May 42.67 26.38 487.67 24.61 41.50 24.75
June 30.50 26.67 492.00 24.54 30.50 24.66
July 36.17 26.84 494.67 24.67 36.17 24.81
August 33.33 26.47 501.00 24.56 32.17 24.67
September 33.17 26.64 467.00 24.62 32.00 24.75
October 51.17 26.06 460.83 24.68 43.50 24.83
November 97.17 23.46 357.00 24.17 24.83 24.26
December 248.17 22.60 227.67 23.46 30.33 23.57
             
Annual Sum or Average 1233.00 23.49 4624.33 24.23 364.83 24.35
Minimum of Months 30.50 22.31 145.83 22.94 5.00 22.95
Maximum of Months 292.50 26.84 501.00 24.68 43.50 24.83



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 376.83 22.11 114.50 22.42 29.83 22.37
February 241.50 22.35 176.67 22.93 32.33 22.88
March 220.00 22.55 275.33 23.43 31.50 23.46
April 78.00 23.62 366.17 24.17 21.33 24.23
May 53.00 25.95 501.83 24.55 51.33 24.68
June 39.33 26.45 496.00 24.57 39.33 24.70
July 47.33 26.58 497.00 24.70 47.33 24.85
August 46.50 25.90 497.67 24.51 42.83 24.63
September 37.67 26.19 474.67 24.56 37.33 24.68
October 56.33 25.15 448.67 24.51 43.50 24.61
November 150.50 23.08 317.33 23.87 33.33 23.92
December 314.17 22.21 167.83 22.81 45.17 22.86
             
Annual Sum or Average 1661.17 23.04 4333.67 23.96 455.17 24.03
Minimum of Months 37.67 22.11 114.50 22.42 21.33 22.37
Maximum of Months 376.83 26.58 501.83 24.70 51.33 24.85



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 283.33 22.29 165.33 22.97 17.83 22.99
February 180.83 22.48 229.17 23.37 22.17 23.36
March 157.83 23.01 319.67 23.85 27.17 23.91
April 95.17 24.50 392.00 24.45 46.00 24.62
May 57.83 26.09 479.50 24.62 53.67 24.78
June 46.00 26.70 493.83 24.63 46.00 24.79
July 66.00 26.86 492.00 24.84 66.00 25.05
August 59.33 25.60 483.50 24.54 44.67 24.69
September 53.83 26.46 463.67 24.71 50.67 24.88
October 86.67 25.45 444.17 24.67 65.17 24.84
November 118.50 23.26 337.83 24.04 25.17 24.12
December 304.33 22.27 191.50 22.99 35.50 23.06
             
Annual Sum or Average 1509.67 23.54 4492.17 24.18 500.00 24.32
Minimum of Months 46.00 22.27 165.33 22.97 17.83 22.99
Maximum of Months 304.33 26.86 493.83 24.84 66.00 25.05



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 168.17 23.31 304.33 24.07 41.00 24.22
February 117.33 23.47 324.50 24.13 41.17 24.23
March 125.67 23.47 364.00 24.10 40.83 24.21
April 72.83 24.55 399.00 24.41 36.33 24.53
May 53.50 25.91 495.83 24.55 51.83 24.67
June 34.33 26.30 493.33 24.51 34.33 24.62
July 45.00 26.52 495.83 24.66 45.00 24.80
August 46.50 26.09 498.50 24.55 44.17 24.67
September 53.50 26.65 479.83 24.75 53.50 24.92
October 79.00 26.50 489.67 24.90 74.83 25.10
November 95.33 25.01 425.83 24.65 62.17 24.83
December 196.00 23.67 329.33 24.20 66.83 24.40
             
Annual Sum or Average 1087.17 24.51 5100.00 24.47 592.00 24.62
Minimum of Months 34.33 23.31 304.33 24.07 34.33 24.21
Maximum of Months 196.00 26.65 498.50 24.90 74.83 25.10



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 328.67 22.05 134.33 22.61 15.50 22.60
February 209.17 22.45 208.33 23.29 32.00 23.33
March 161.17 22.68 317.00 23.77 30.67 23.86
April 84.33 24.49 387.17 24.47 40.17 24.62
May 55.83 26.01 468.83 24.63 50.00 24.78
June 36.67 26.51 481.50 24.56 35.50 24.69
July 46.67 26.79 486.83 24.72 46.67 24.88
August 48.17 25.67 492.33 24.53 37.00 24.66
September 45.33 26.06 448.50 24.63 38.17 24.78
October 73.67 25.28 435.17 24.64 50.00 24.80
November 140.17 23.14 329.67 23.98 30.50 24.07
December 281.50 22.33 205.17 23.16 38.33 23.28
             
Annual Sum or Average 1511.33 23.26 4394.83 24.11 444.50 24.24
Minimum of Months 36.67 22.05 134.33 22.61 15.50 22.60
Maximum of Months 328.67 26.79 492.33 24.72 50.00 24.88



Table of Contents

Report: ComfortReportSimple55Monthly

For: GROUNDFLOOR_PLENUM

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00
             
Annual Sum or Average 0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: ComfortReportSimple55Monthly

For: MIDFLOOR_PLENUM

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00
             
Annual Sum or Average 0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: ComfortReportSimple55Monthly

For: TOPFLOOR_PLENUM

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00
             
Annual Sum or Average 0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: ComfortReportSimple55Monthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 18.33 27.00 502.00 27.00 18.33 27.00
February 87.17 27.00 454.00 27.00 87.17 27.00
March 205.33 27.00 514.00 27.00 205.33 27.00
April 381.33 27.00 485.00 27.00 381.33 27.00
May 145.17 27.00 508.00 27.00 145.17 27.00
June 235.67 27.00 496.00 27.00 235.67 27.00
July 360.83 27.00 497.00 27.00 360.83 27.00
August 499.00 27.08 514.00 27.08 499.00 27.08
September 182.83 27.00 485.00 27.00 182.83 27.00
October 218.33 27.00 502.00 27.00 218.33 27.00
November 237.17 27.00 489.00 27.00 237.17 27.00
December 293.83 27.00 497.00 27.00 293.83 27.00
             
Annual Sum or Average 2865.00 27.01 5943.00 27.01 2865.00 27.01
Minimum of Months 18.33 27.00 454.00 27.00 18.33 27.00
Maximum of Months 499.00 27.08 514.00 27.08 499.00 27.08



Table of Contents

Report: ComfortReportSimple55Monthly

For: DATACENTER_MID_ZN_6

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.50 27.00 502.00 27.00 0.50 27.00
February 5.33 27.00 454.00 27.00 5.33 27.00
March 24.17 27.00 514.00 27.00 24.17 27.00
April 75.83 27.00 485.00 27.00 75.83 27.00
May 37.83 27.00 508.00 27.00 37.83 27.00
June 41.50 27.00 496.00 27.00 41.50 27.00
July 94.33 27.00 497.00 27.00 94.33 27.00
August 158.17 27.12 514.00 27.06 158.17 27.07
September 37.83 27.00 485.00 27.00 37.83 27.00
October 40.00 27.00 502.00 27.00 40.00 27.00
November 35.50 27.00 489.00 27.00 35.50 27.00
December 26.67 27.00 497.00 27.00 26.67 27.00
             
Annual Sum or Average 577.67 27.03 5943.00 27.01 577.67 27.01
Minimum of Months 0.50 27.00 454.00 27.00 0.50 27.00
Maximum of Months 158.17 27.12 514.00 27.06 158.17 27.07



Table of Contents

Report: ComfortReportSimple55Monthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 4.33 27.00 499.83 27.00 4.33 27.00
February 17.50 27.00 444.50 27.00 17.50 27.00
March 56.17 27.00 514.00 27.00 56.17 27.00
April 133.83 27.00 485.00 27.00 133.83 27.00
May 112.33 27.00 508.00 27.00 112.33 27.00
June 136.50 27.00 496.00 27.00 136.50 27.00
July 191.67 27.00 497.00 27.00 191.67 27.00
August 207.83 27.06 514.00 27.04 207.83 27.04
September 116.50 27.00 485.00 27.00 116.50 27.00
October 89.67 27.00 502.00 27.00 89.67 27.00
November 64.50 27.00 489.00 27.00 64.50 27.00
December 38.00 27.00 497.00 27.00 38.00 27.00
             
Annual Sum or Average 1168.83 27.01 5931.33 27.00 1168.83 27.01
Minimum of Months 4.33 27.00 444.50 27.00 4.33 27.00
Maximum of Months 207.83 27.06 514.00 27.04 207.83 27.04



Table of Contents

Report: ComfortReportSimple55Monthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 502.00 27.00 502.00 27.00 502.00 27.00
February 454.00 27.00 454.00 27.00 454.00 27.00
March 514.00 27.00 514.00 27.00 514.00 27.00
April 485.00 27.42 485.00 27.42 485.00 27.42
May 508.00 27.00 508.00 27.00 508.00 27.00
June 496.00 27.00 496.00 27.00 496.00 27.00
July 497.00 27.00 497.00 27.00 497.00 27.00
August 514.00 28.88 514.00 28.88 514.00 28.88
September 485.00 27.01 485.00 27.01 485.00 27.01
October 502.00 27.00 502.00 27.00 502.00 27.00
November 489.00 27.00 489.00 27.00 489.00 27.00
December 497.00 27.16 497.00 27.16 497.00 27.16
             
Annual Sum or Average 5943.00 27.21 5943.00 27.21 5943.00 27.21
Minimum of Months 454.00 27.00 454.00 27.00 454.00 27.00
Maximum of Months 514.00 28.88 514.00 28.88 514.00 28.88



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 27.00059 37.45426 0.95130 24.21221
February 454.00000 27.00140 36.31815 0.99175 25.88347
March 514.00000 27.00091 36.50348 1.03216 27.55770
April 485.00000 27.00132 38.14079 1.08488 29.85307
May 508.00000 27.00025 43.31497 0.38385 8.12235
June 496.00000 27.00300 41.66378 0.41521 8.64181
July 497.00000 27.00157 40.58876 0.45722 9.41211
August 514.00000 27.07481 39.79744 0.52425 10.87939
September 485.00000 27.00000 44.68871 0.39668 8.32782
October 502.00000 27.00257 40.90274 1.05062 28.32281
November 489.00000 27.00133 38.37584 1.05311 28.44347
December 497.00000 27.00030 36.66202 1.05482 28.53038
           
Annual Sum or Average 5943.00000 27.00757 39.54961 0.78095 19.78409
Minimum of Months 454.00000 27.00000 36.31815 0.38385 8.12235
Maximum of Months 514.00000 27.07481 44.68871 1.08488 29.85307



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: DATACENTER_MID_ZN_6

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 27.00028 37.84224 0.88326 21.60760
February 454.00000 27.00134 36.41240 0.90724 22.55113
March 514.00000 27.00096 36.51386 0.94486 23.97408
April 485.00000 27.00076 38.11900 0.99843 26.09783
May 508.00000 27.00008 43.62126 0.33367 7.38053
June 496.00000 27.00311 41.79544 0.34408 7.52194
July 497.00000 27.00168 40.64690 0.36146 7.78239
August 514.00000 27.03757 39.85854 0.38480 8.19882
September 485.00000 27.00000 45.09732 0.34246 7.49689
October 502.00000 27.00262 41.02548 0.99678 26.01633
November 489.00000 27.00139 38.41444 0.96890 24.90518
December 497.00000 27.00035 36.65022 0.93179 23.44278
           
Annual Sum or Average 5943.00000 27.00429 39.68191 0.69765 17.18887
Minimum of Months 454.00000 27.00000 36.41240 0.33367 7.38053
Maximum of Months 514.00000 27.03757 45.09732 0.99843 26.09783



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 27.00053 38.08443 0.85923 20.80865
February 454.00000 27.00137 36.46815 0.89390 22.14828
March 514.00000 27.00097 36.55152 0.93931 23.83257
April 485.00000 27.00058 38.15863 1.00281 26.32158
May 508.00000 27.00020 43.56551 0.35179 7.69474
June 496.00000 27.00307 41.78757 0.36529 7.87910
July 497.00000 27.00167 40.65966 0.38762 8.24553
August 514.00000 27.02648 39.90006 0.39942 8.49213
September 485.00000 27.00000 45.04295 0.35873 7.78377
October 502.00000 27.00261 41.06668 1.00067 26.20438
November 489.00000 27.00141 38.46761 0.96027 24.62085
December 497.00000 27.00040 36.70746 0.90964 22.66379
           
Annual Sum or Average 5943.00000 27.00335 39.72056 0.70035 17.16815
Minimum of Months 454.00000 27.00000 36.46815 0.35179 7.69474
Maximum of Months 514.00000 27.02648 45.04295 1.00281 26.32158



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 27.00237 36.96311 1.17174 33.90078
February 454.00000 27.00210 36.66654 1.31487 41.05456
March 514.00000 27.00137 36.95318 1.44967 48.18049
April 485.00000 27.41788 38.06951 1.67110 60.08625
May 508.00000 27.00480 40.73914 0.62792 13.31359
June 496.00000 27.00382 40.18535 0.82879 19.51009
July 497.00000 27.00159 39.90105 1.02998 27.41843
August 514.00000 28.87615 38.32777 1.76687 64.87990
September 485.00000 27.00572 41.50727 0.66718 14.40778
October 502.00000 27.00318 39.72867 1.35898 43.34406
November 489.00000 27.00136 38.20500 1.48299 49.98000
December 497.00000 27.15975 37.00081 1.62695 57.78130
           
Annual Sum or Average 5943.00000 27.21192 38.69509 1.25029 39.52265
Minimum of Months 454.00000 27.00136 36.66654 0.62792 13.31359
Maximum of Months 514.00000 28.87615 41.50727 1.76687 64.87990



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: BASEMENT

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 24.60445 52.93740 0.63388 14.41319
February 454.00000 24.58048 53.18276 0.62850 14.15155
March 514.00000 24.47074 54.92106 0.61615 13.73526
April 485.00000 24.55798 60.78160 0.67415 15.31150
May 508.00000 24.53605 63.72341 -0.1493 6.83729
June 496.00000 24.49079 63.68977 -0.1616 6.73915
July 497.00000 24.64227 62.61245 -0.1191 6.93282
August 514.00000 24.49955 62.21495 -0.1517 6.82502
September 485.00000 24.58323 62.74755 -0.1301 6.95919
October 502.00000 24.63727 61.52809 0.71002 16.56234
November 489.00000 24.64427 59.04061 0.69491 15.98128
December 497.00000 24.63544 55.04506 0.66092 15.20620
           
Annual Sum or Average 5943.00000 24.57293 59.40341 0.32234 11.60654
Minimum of Months 454.00000 24.47074 52.93740 -0.1616 6.73915
Maximum of Months 514.00000 24.64427 63.72341 0.71002 16.56234



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: CORE_BOTTOM

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 24.25306 45.44312 0.50289 10.64173
February 454.00000 24.28037 45.33734 0.51714 10.97705
March 514.00000 24.20200 45.64562 0.50954 10.63245
April 485.00000 24.13942 48.18204 0.52047 10.73465
May 508.00000 24.14905 48.79085 -0.3460 7.73409
June 496.00000 24.11214 48.77228 -0.3485 7.65627
July 497.00000 24.12322 48.44126 -0.3398 7.49434
August 514.00000 24.10746 48.41622 -0.3325 7.37139
September 485.00000 24.17331 48.52582 -0.3360 7.59921
October 502.00000 24.21274 48.25938 0.53531 11.12030
November 489.00000 24.29456 47.71190 0.55086 11.56933
December 497.00000 24.27966 46.48299 0.53268 11.16507
           
Annual Sum or Average 5943.00000 24.19308 47.51105 0.16036 9.54258
Minimum of Months 454.00000 24.10746 45.33734 -0.3485 7.37139
Maximum of Months 514.00000 24.29456 48.79085 0.55086 11.56933



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: CORE_MID

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 23.84860 47.00432 0.38690 8.49839
February 454.00000 23.89553 46.99994 0.40263 8.95102
March 514.00000 23.97148 46.86893 0.42873 9.19402
April 485.00000 24.02267 49.29628 0.46562 9.76074
May 508.00000 24.03402 49.45330 -0.4073 8.81379
June 496.00000 24.00762 49.50408 -0.4106 8.87188
July 497.00000 23.95401 49.50528 -0.4298 9.20049
August 514.00000 23.99234 49.61664 -0.4174 8.96848
September 485.00000 24.01747 49.32806 -0.4116 8.91602
October 502.00000 24.11901 49.00585 0.49201 10.26929
November 489.00000 24.13231 49.11630 0.48748 10.28644
December 497.00000 23.87673 48.38395 0.40625 8.81501
           
Annual Sum or Average 5943.00000 23.98971 48.68023 0.07944 9.21092
Minimum of Months 454.00000 23.84860 46.86893 -0.4298 8.49839
Maximum of Months 514.00000 24.13231 49.61664 0.49201 10.28644



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: CORE_TOP

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 23.39727 48.42277 0.27534 7.44545
February 454.00000 23.62675 47.70823 0.33860 8.58133
March 514.00000 23.83849 47.22844 0.39941 9.00274
April 485.00000 24.01305 49.21357 0.47111 9.88208
May 508.00000 24.11131 48.99137 -0.3643 8.11354
June 496.00000 24.09750 48.98899 -0.3616 8.04301
July 497.00000 24.09457 48.80579 -0.3623 8.03298
August 514.00000 24.05273 49.19764 -0.3796 8.34290
September 485.00000 24.09600 48.92886 -0.3702 8.19426
October 502.00000 24.10793 48.98937 0.49581 10.36291
November 489.00000 23.96020 49.73878 0.44841 9.63354
December 497.00000 23.50036 49.62284 0.31410 7.91494
           
Annual Sum or Average 5943.00000 23.90968 48.82214 0.07250 8.62634
Minimum of Months 454.00000 23.39727 47.22844 -0.3796 7.44545
Maximum of Months 514.00000 24.11131 49.73878 0.49581 10.36291



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 23.70305 46.88679 0.34310 8.39103
February 454.00000 23.92293 46.50794 0.41735 9.60841
March 514.00000 24.00937 46.46176 0.45118 10.02051
April 485.00000 24.20751 47.93600 0.54085 11.36854
May 508.00000 24.37614 48.75839 -0.2197 6.79532
June 496.00000 24.35578 48.07995 -0.1980 6.51829
July 497.00000 24.45596 47.35226 -0.1592 6.52473
August 514.00000 24.30233 47.85558 -0.2165 6.66417
September 485.00000 24.40104 48.05019 -0.2153 6.76654
October 502.00000 24.36156 48.35963 0.58248 12.48588
November 489.00000 24.21092 48.12116 0.52414 11.05754
December 497.00000 23.93851 47.84954 0.42464 9.49686
           
Annual Sum or Average 5943.00000 24.18838 47.69042 0.18695 8.79502
Minimum of Months 454.00000 23.70305 46.46176 -0.2197 6.51829
Maximum of Months 514.00000 24.45596 48.75839 0.58248 12.48588



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 23.77581 45.99462 0.39944 9.66795
February 454.00000 23.93277 45.96698 0.46124 10.51241
March 514.00000 23.95299 45.93721 0.48761 10.78054
April 485.00000 24.13081 47.67390 0.57339 12.62739
May 508.00000 24.34054 48.30970 -0.1691 6.69429
June 496.00000 24.31434 47.82595 -0.1627 6.53092
July 497.00000 24.42919 47.08916 -0.1173 6.90881
August 514.00000 24.18642 47.90350 -0.2141 6.98216
September 485.00000 24.41513 47.49391 -0.1480 6.73577
October 502.00000 24.29670 47.97575 0.60963 13.36401
November 489.00000 24.09548 47.98185 0.52845 11.28017
December 497.00000 23.62745 48.21060 0.37901 9.05771
           
Annual Sum or Average 5943.00000 24.12554 47.37048 0.21617 9.24571
Minimum of Months 454.00000 23.62745 45.93721 -0.2141 6.53092
Maximum of Months 514.00000 24.42919 48.30970 0.60963 13.36401



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 24.30044 44.37713 0.56202 13.15860
February 454.00000 24.36306 44.73301 0.59186 13.70605
March 514.00000 24.21957 45.35970 0.55411 12.31858
April 485.00000 24.29396 47.49833 0.58412 12.61091
May 508.00000 24.36469 48.82425 -0.2258 6.86272
June 496.00000 24.32343 48.26071 -0.2227 6.65325
July 497.00000 24.42823 47.47332 -0.1766 6.60258
August 514.00000 24.31834 47.71723 -0.1949 6.60761
September 485.00000 24.49856 47.43868 -0.1292 6.73796
October 502.00000 24.58288 47.14873 0.70165 16.25291
November 489.00000 24.55166 46.50159 0.67973 15.66978
December 497.00000 24.36724 45.83427 0.60579 14.15173
           
Annual Sum or Average 5943.00000 24.38363 46.77670 0.27409 10.91420
Minimum of Months 454.00000 24.21957 44.37713 -0.2258 6.60258
Maximum of Months 514.00000 24.58288 48.82425 0.70165 16.25291



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 23.90124 45.30058 0.45606 10.48293
February 454.00000 24.30713 44.50710 0.59452 13.74841
March 514.00000 24.39711 44.28346 0.65817 15.10269
April 485.00000 24.51633 46.20040 0.75467 17.79462
May 508.00000 24.45520 47.64089 -0.0764 6.42734
June 496.00000 24.42410 47.19717 -0.0595 6.21492
July 497.00000 24.56261 46.40594 0.02745 6.65301
August 514.00000 24.47990 46.51032 0.03674 6.51678
September 485.00000 24.47995 47.08933 -0.0814 6.53860
October 502.00000 24.52781 46.90653 0.71585 16.51463
November 489.00000 24.50192 46.28902 0.69037 15.68839
December 497.00000 24.49041 45.10074 0.66001 15.18974
           
Annual Sum or Average 5943.00000 24.42053 46.12708 0.36225 11.37199
Minimum of Months 454.00000 23.90124 44.28346 -0.0814 6.21492
Maximum of Months 514.00000 24.56261 47.64089 0.75467 17.79462



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 22.89354 50.00031 0.14403 7.09172
February 454.00000 23.31306 49.67402 0.26068 8.36221
March 514.00000 23.55699 49.73563 0.33505 9.18727
April 485.00000 24.11899 50.53198 0.50398 10.73620
May 508.00000 24.38642 51.26332 -0.2221 7.01005
June 496.00000 24.40400 50.24896 -0.1921 6.75286
July 497.00000 24.49026 49.29815 -0.1668 6.70875
August 514.00000 24.34589 50.60943 -0.2304 6.99846
September 485.00000 24.40507 50.26534 -0.2229 6.97089
October 502.00000 24.35649 51.34903 0.57855 12.58636
November 489.00000 23.94875 51.61359 0.45390 10.28685
December 497.00000 23.14195 52.63661 0.22956 7.93184
           
Annual Sum or Average 5943.00000 23.95032 50.60732 0.12051 8.37951
Minimum of Months 454.00000 22.89354 49.29815 -0.2304 6.70875
Maximum of Months 514.00000 24.49026 52.63661 0.57855 12.58636



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 427.00000 23.22362 47.89581 0.25391 8.43246
February 385.00000 23.53757 48.11445 0.35228 9.39693
March 433.00000 23.82464 48.23937 0.44376 10.68531
April 410.00000 24.27862 49.17604 0.59323 13.54682
May 430.00000 24.44450 50.43579 -0.1484 7.09371
June 418.00000 24.50008 49.48726 -0.1157 6.90730
July 422.00000 24.64353 48.20702 -0.0651 7.42181
August 433.00000 24.41104 49.76228 -0.1610 7.21149
September 410.00000 24.53979 49.08153 -0.1239 7.22279
October 427.00000 24.45209 50.22681 0.63950 14.62647
November 417.00000 24.03174 50.40663 0.50475 11.47311
December 422.00000 23.14759 51.68653 0.25916 8.65916
           
Annual Sum or Average 5034.00000 24.08867 49.40215 0.20107 9.38356
Minimum of Months 385.00000 23.14759 47.89581 -0.1610 6.90730
Maximum of Months 433.00000 24.64353 51.68653 0.63950 14.62647



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 24.16329 45.39252 0.52522 12.85339
February 454.00000 24.20590 46.24831 0.54742 13.12998
March 514.00000 24.09827 47.48478 0.51711 12.00339
April 485.00000 24.28155 49.64974 0.56775 12.36812
May 508.00000 24.37357 51.35296 -0.2277 7.06159
June 496.00000 24.36362 50.55217 -0.2196 6.85509
July 497.00000 24.45672 49.48856 -0.1856 6.75696
August 514.00000 24.37475 50.31328 -0.2010 6.90033
September 485.00000 24.53262 49.22769 -0.1218 6.96613
October 502.00000 24.66971 49.22502 0.72517 17.25949
November 489.00000 24.55531 48.56228 0.67817 16.09392
December 497.00000 24.19328 48.23573 0.55895 13.83318
           
Annual Sum or Average 5943.00000 24.35578 48.82982 0.26040 10.98131
Minimum of Months 454.00000 24.09827 45.39252 -0.2277 6.75696
Maximum of Months 514.00000 24.66971 51.35296 0.72517 17.25949



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 23.02125 48.51341 0.22042 7.79964
February 454.00000 23.51875 47.99654 0.36403 10.04732
March 514.00000 23.82574 47.75579 0.46519 11.66664
April 485.00000 24.30477 48.91136 0.62362 14.19492
May 508.00000 24.41214 50.03413 -0.1321 7.01094
June 496.00000 24.40138 49.49943 -0.1365 6.72993
July 497.00000 24.50730 48.40935 -0.0866 6.77237
August 514.00000 24.40011 49.35967 -0.1265 6.81300
September 485.00000 24.43667 49.12708 -0.1436 7.11526
October 502.00000 24.42475 49.83277 0.64944 14.86453
November 489.00000 24.01044 50.19796 0.51739 11.88394
December 497.00000 23.35018 50.61601 0.32922 9.61612
           
Annual Sum or Average 5943.00000 24.05415 49.19362 0.20993 9.52865
Minimum of Months 454.00000 23.02125 47.75579 -0.1436 6.72993
Maximum of Months 514.00000 24.50730 50.61601 0.64944 14.86453



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 22.57247 51.14675 0.06271 7.34787
February 454.00000 23.10661 50.33553 0.21105 8.60636
March 514.00000 23.42492 50.27540 0.30670 9.39214
April 485.00000 24.05845 50.91631 0.49890 10.85530
May 508.00000 24.39389 51.61880 -0.2009 7.06513
June 496.00000 24.42185 50.47703 -0.1668 6.76914
July 497.00000 24.52154 49.46208 -0.1337 6.85936
August 514.00000 24.34913 50.92090 -0.2110 7.07319
September 485.00000 24.41556 50.61676 -0.2023 7.08554
October 502.00000 24.32332 51.95176 0.57981 12.76228
November 489.00000 23.78621 52.55817 0.41994 10.20481
December 497.00000 22.86290 53.79250 0.16085 8.06144
           
Annual Sum or Average 5943.00000 23.85743 51.17679 0.10861 8.50066
Minimum of Months 454.00000 22.57247 49.46208 -0.2110 6.76914
Maximum of Months 514.00000 24.52154 53.79250 0.57981 12.76228



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 23.05045 48.85506 0.21355 8.39531
February 454.00000 23.41782 48.51472 0.33137 9.49395
March 514.00000 23.76187 48.34981 0.44110 10.80884
April 485.00000 24.18720 49.39823 0.59566 13.64147
May 508.00000 24.37984 50.55001 -0.1297 7.02273
June 496.00000 24.42820 49.59802 -0.0977 6.76156
July 497.00000 24.55542 48.41317 -0.0479 7.34764
August 514.00000 24.33705 49.97169 -0.1453 7.16755
September 485.00000 24.45538 49.30945 -0.1119 7.15373
October 502.00000 24.36231 50.53697 0.64087 14.67483
November 489.00000 23.89241 51.12691 0.48529 11.31847
December 497.00000 22.96558 52.44030 0.21760 8.63629
           
Annual Sum or Average 5943.00000 23.98621 49.76211 0.19743 9.35841
Minimum of Months 454.00000 22.96558 48.34981 -0.1453 6.76156
Maximum of Months 514.00000 24.55542 52.44030 0.64087 14.67483



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 23.87558 46.46929 0.45043 12.00569
February 454.00000 23.99822 46.94893 0.49677 12.63915
March 514.00000 23.96429 48.08269 0.48796 11.92132
April 485.00000 24.21844 50.07067 0.56184 12.44942
May 508.00000 24.37782 51.72972 -0.2076 7.14427
June 496.00000 24.38485 50.78827 -0.1930 6.85304
July 497.00000 24.49087 49.65938 -0.1515 6.89519
August 514.00000 24.37351 50.64349 -0.1834 7.00125
September 485.00000 24.52495 49.61389 -0.1074 7.13812
October 502.00000 24.60965 49.87929 0.71979 17.16848
November 489.00000 24.40077 49.44138 0.64450 15.46495
December 497.00000 23.94371 49.34933 0.49589 13.12288
           
Annual Sum or Average 5943.00000 24.26447 49.40735 0.24820 10.79413
Minimum of Months 454.00000 23.87558 46.46929 -0.2076 6.85304
Maximum of Months 514.00000 24.60965 51.72972 0.71979 17.16848



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 22.71710 49.54774 0.14624 7.76533
February 454.00000 23.28660 48.68028 0.31134 9.93128
March 514.00000 23.65993 48.34505 0.43079 11.58471
April 485.00000 24.19422 49.37004 0.60769 14.06065
May 508.00000 24.36820 50.44917 -0.1275 7.30177
June 496.00000 24.37770 49.77292 -0.1251 6.88175
July 497.00000 24.49313 48.63690 -0.0693 7.05296
August 514.00000 24.36739 49.69861 -0.1197 7.05214
September 485.00000 24.39416 49.51269 -0.1403 7.41992
October 502.00000 24.34043 50.44890 0.63928 14.76470
November 489.00000 23.82387 51.10328 0.47931 11.58097
December 497.00000 23.06876 51.68985 0.26271 9.39411
           
Annual Sum or Average 5943.00000 23.92814 49.77607 0.18945 9.55346
Minimum of Months 454.00000 22.71710 48.34505 -0.1403 6.88175
Maximum of Months 514.00000 24.49313 51.68985 0.63928 14.76470



Table of Contents

Report: ChillerReportMonthly

For: COOLSYS1 CHILLER1

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

CHILLER ELECTRICITY ENERGY [J] CHILLER ELECTRICITY RATE {Maximum} [W] CHILLER ELECTRICITY RATE {TIMESTAMP} CHILLER ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] CHILLER EVAPORATOR COOLING ENERGY [J] CHILLER EVAPORATOR COOLING RATE [] CHILLER CONDENSER HEAT TRANSFER ENERGY [J] CHILLER COP [W/W] CHILLER COP {Maximum} [W/W] CHILLER COP {TIMESTAMP} CHILLER PART LOAD RATIO [] CHILLER PART LOAD RATIO []
January 0.173485E+12 242682.81 06-JAN-13:50 464.47 0.116101E+13 0.00 0.133449E+13 3.83 7.56 04-JAN-06:04 0.00 0.00
February 0.185583E+12 241829.61 10-FEB-14:40 424.83 0.128597E+13 0.00 0.147155E+13 4.07 7.57 28-FEB-16:00 0.00 0.00
March 0.220555E+12 239765.65 13-MAR-11:10 542.96 0.151094E+13 0.00 0.173149E+13 4.56 7.57 29-MAR-05:04 0.00 0.00
April 0.257832E+12 245795.95 13-APR-08:20 608.00 0.179355E+13 0.00 0.205139E+13 5.35 7.57 05-APR-05:04 0.00 0.00
May 0.299857E+12 247901.50 31-MAY-04:10 583.01 0.206566E+13 0.00 0.236551E+13 5.15 7.57 08-MAY-04:13 0.00 0.00
June 0.317124E+12 253330.73 08-JUN-17:40 627.44 0.212134E+13 0.00 0.243846E+13 5.52 7.42 17-JUN-03:03 0.00 0.00
July 0.331857E+12 256818.25 29-JUL-10:30 677.75 0.219814E+13 0.00 0.253000E+13 5.67 7.50 07-JUL-04:13 0.00 0.00
August 0.332770E+12 256606.96 03-AUG-12:00 691.16 0.220452E+13 0.00 0.253729E+13 5.73 7.37 14-AUG-04:14 0.00 0.00
September 0.309191E+12 252504.56 11-SEP-07:30 595.12 0.207495E+13 0.00 0.238414E+13 5.30 7.50 05-SEP-04:13 0.00 0.00
October 0.291905E+12 258446.94 04-OCT-07:10 595.39 0.198927E+13 0.00 0.228117E+13 5.12 7.56 19-OCT-04:14 0.00 0.00
November 0.241476E+12 248532.47 30-NOV-11:20 532.24 0.165975E+13 0.00 0.190123E+13 4.71 7.57 06-NOV-05:13 0.00 0.00
December 0.193765E+12 239037.88 07-DEC-14:20 532.71 0.129752E+13 0.00 0.149128E+13 4.31 7.56 26-DEC-06:05 0.00 0.00
                         
Annual Sum or Average 0.315540E+13     6875.08 0.213626E+14 0.00 0.245180E+14 4.95     0.00 0.00
Minimum of Months 0.173485E+12 239037.88   424.83 0.116101E+13 0.00 0.133449E+13 3.83 7.37   0.00 0.00
Maximum of Months 0.332770E+12 258446.94   691.16 0.220452E+13 0.00 0.253729E+13 5.73 7.57   0.00 0.00



Table of Contents

Report: ChillerReportMonthly

For: COOLSYS1 CHILLER2

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

CHILLER ELECTRICITY ENERGY [J] CHILLER ELECTRICITY RATE {Maximum} [W] CHILLER ELECTRICITY RATE {TIMESTAMP} CHILLER ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] CHILLER EVAPORATOR COOLING ENERGY [J] CHILLER EVAPORATOR COOLING RATE [] CHILLER CONDENSER HEAT TRANSFER ENERGY [J] CHILLER COP [W/W] CHILLER COP {Maximum} [W/W] CHILLER COP {TIMESTAMP} CHILLER PART LOAD RATIO [] CHILLER PART LOAD RATIO []
January 0.632974E+10 148725.77 14-JAN-06:08 14.15 0.443030E+11 0.00 0.506327E+11 0.13 7.25 12-JAN-16:50 0.00 0.00
February 0.566931E+10 162211.28 13-FEB-05:16 12.56 0.398274E+11 0.00 0.454967E+11 0.13 7.37 13-FEB-05:16 0.00 0.00
March 0.210922E+11 197647.01 06-MAR-06:06 46.18 0.147004E+12 0.00 0.168096E+12 0.43 7.24 07-MAR-16:10 0.00 0.00
April 0.217140E+11 179974.18 15-APR-05:03 47.48 0.149959E+12 0.00 0.171673E+12 0.45 7.35 15-APR-05:03 0.00 0.00
May 0.559559E+11 237991.85 24-MAY-05:03 117.32 0.383078E+12 0.00 0.439034E+12 1.08 7.42 22-MAY-05:02 0.00 0.00
June 0.778848E+11 221810.32 06-JUN-05:04 160.32 0.521576E+12 0.00 0.599460E+12 1.49 7.28 24-JUN-05:02 0.00 0.00
July 0.805302E+11 202449.49 03-JUL-03:06 163.30 0.533445E+12 0.00 0.613975E+12 1.45 7.29 07-JUL-04:17 0.00 0.00
August 0.879660E+11 208775.71 28-AUG-03:06 178.43 0.585326E+12 0.00 0.673292E+12 1.59 7.08 26-AUG-05:08 0.00 0.00
September 0.794670E+11 240624.35 06-SEP-04:13 163.49 0.532114E+12 0.00 0.611581E+12 1.52 7.33 05-SEP-04:16 0.00 0.00
October 0.607791E+11 213761.03 31-OCT-05:02 127.59 0.412025E+12 0.00 0.472804E+12 1.16 7.30 25-OCT-04:17 0.00 0.00
November 0.391923E+11 178839.43 04-NOV-03:08 83.45 0.268901E+12 0.00 0.308093E+12 0.79 7.38 09-NOV-06:02 0.00 0.00
December 0.903255E+10 193029.47 09-DEC-06:02 19.57 0.623425E+11 0.00 0.713751E+11 0.18 7.26 09-DEC-06:02 0.00 0.00
                         
Annual Sum or Average 0.545613E+12     1133.85 0.367990E+13 0.00 0.422551E+13 0.87     0.00 0.00
Minimum of Months 0.566931E+10 148725.77   12.56 0.398274E+11 0.00 0.454967E+11 0.13 7.08   0.00 0.00
Maximum of Months 0.879660E+11 240624.35   178.43 0.585326E+12 0.00 0.673292E+12 1.59 7.42   0.00 0.00



Table of Contents

Report: TowerReportMonthly

For: CENTRAL TOWER

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

COOLING TOWER FAN ELECTRICITY ENERGY [J] COOLING TOWER FAN ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] COOLING TOWER FAN ELECTRICITY RATE {Maximum} [W] COOLING TOWER FAN ELECTRICITY RATE {TIMESTAMP} COOLING TOWER HEAT TRANSFER RATE {Maximum} [W] COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} COOLING TOWER INLET TEMPERATURE [C] COOLING TOWER OUTLET TEMPERATURE [C] COOLING TOWER MASS FLOW RATE [kg/s]
January 0.113003E+12 744.00 49248.27 01-JAN-00:05 244609.28 02-JAN-15:10 25.76 21.89 14.34
February 0.113327E+12 672.00 49248.27 01-FEB-00:10 390997.08 02-FEB-15:10 31.26 24.38 14.34
March 0.129353E+12 744.00 49248.27 01-MAR-00:10 641082.66 31-MAR-24:00 36.13 26.26 14.34
April 0.127652E+12 720.00 49248.27 01-APR-00:02 699307.15 14-APR-15:50 43.04 30.08 14.34
May 0.131907E+12 744.00 49248.27 01-MAY-00:05 378582.55 31-MAY-23:17 32.85 28.42 14.34
June 0.127652E+12 720.00 49248.27 01-JUN-00:02 524558.40 30-JUN-23:12 38.71 31.15 14.34
July 0.131907E+12 744.00 49248.27 01-JUL-00:03 679977.10 31-JUL-24:00 43.61 33.01 14.34
August 0.131907E+12 744.00 49248.27 01-AUG-00:05 716579.80 23-AUG-16:20 47.59 34.20 14.34
September 0.127652E+12 720.00 49248.27 01-SEP-00:03 372631.02 30-SEP-23:12 34.13 29.57 14.34
October 0.131907E+12 744.00 49248.27 01-OCT-00:03 504750.78 31-OCT-23:30 37.20 29.75 14.34
November 0.126831E+12 720.00 49248.27 01-NOV-00:10 557543.96 03-NOV-14:10 38.40 28.28 14.34
December 0.129842E+12 744.00 49248.27 01-DEC-00:10 693282.99 08-DEC-16:50 38.87 26.26 14.34
                   
Annual Sum or Average 0.152294E+13 8760.00         37.33 28.62 14.34
Minimum of Months 0.113003E+12 672.00 49248.27   244609.28   25.76 21.89 14.34
Maximum of Months 0.131907E+12 744.00 49248.27   716579.80   47.59 34.20 14.34



Table of Contents

Report: TowerReportMonthly

For: TOWERWATERSYS COOLTOWER 1

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

COOLING TOWER FAN ELECTRICITY ENERGY [J] COOLING TOWER FAN ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] COOLING TOWER FAN ELECTRICITY RATE {Maximum} [W] COOLING TOWER FAN ELECTRICITY RATE {TIMESTAMP} COOLING TOWER HEAT TRANSFER RATE {Maximum} [W] COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} COOLING TOWER INLET TEMPERATURE [C] COOLING TOWER OUTLET TEMPERATURE [C] COOLING TOWER MASS FLOW RATE [kg/s]
January 0.161628E+11 412.83 24398.16 01-JAN-08:23 1737946.14 12-JAN-15:20 23.74 22.28 48.12
February 0.180947E+11 386.65 24398.16 01-FEB-10:30 1861047.82 15-FEB-15:20 24.06 22.29 47.25
March 0.269320E+11 505.16 24398.16 03-MAR-08:30 1919753.24 31-MAR-14:10 24.04 22.17 55.90
April 0.358335E+11 587.40 24398.16 01-APR-01:22 1852739.26 27-APR-16:00 24.71 22.42 64.44
May 0.499254E+11 580.91 24398.16 01-MAY-04:14 1648702.60 24-MAY-05:03 26.96 24.44 53.10
June 0.551104E+11 627.44 24398.16 01-JUN-00:02 1469169.80 06-JUN-05:04 28.31 25.62 55.35
July 0.591121E+11 677.75 24398.16 01-JUL-00:08 1503840.62 14-JUL-17:40 28.45 25.73 58.43
August 0.607067E+11 691.16 24398.16 01-AUG-00:05 1408282.48 10-AUG-05:03 28.49 25.76 59.63
September 0.522713E+11 595.12 24398.16 01-SEP-00:03 1646207.87 26-SEP-04:15 28.37 25.73 52.19
October 0.496961E+11 593.96 24398.16 01-OCT-00:03 1816224.69 17-OCT-10:40 27.01 24.57 54.97
November 0.363564E+11 509.68 24398.16 01-NOV-04:12 2032239.01 01-NOV-04:12 25.45 23.34 52.89
December 0.232126E+11 488.13 24398.16 01-DEC-00:12 1892099.89 11-DEC-15:20 23.77 22.14 53.90
                   
Annual Sum or Average 0.483414E+12 6656.17         26.12 23.88 54.73
Minimum of Months 0.161628E+11 386.65 24398.16   1408282.48   23.74 22.14 47.25
Maximum of Months 0.607067E+11 691.16 24398.16   2032239.01   28.49 25.76 64.44



Table of Contents

Report: TowerReportMonthly

For: TOWERWATERSYS COOLTOWER 2

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

COOLING TOWER FAN ELECTRICITY ENERGY [J] COOLING TOWER FAN ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] COOLING TOWER FAN ELECTRICITY RATE {Maximum} [W] COOLING TOWER FAN ELECTRICITY RATE {TIMESTAMP} COOLING TOWER HEAT TRANSFER RATE {Maximum} [W] COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} COOLING TOWER INLET TEMPERATURE [C] COOLING TOWER OUTLET TEMPERATURE [C] COOLING TOWER MASS FLOW RATE [kg/s]
January 0.441363E+10 50.25 24398.16 02-JAN-09:20 1403297.41 07-JAN-05:14 23.74 23.45 3.62
February 0.569321E+10 64.82 24398.16 02-FEB-06:06 1243554.98 14-FEB-15:30 24.06 23.63 4.80
March 0.930424E+10 105.93 24398.16 03-MAR-11:40 1366800.78 31-MAR-15:00 24.04 23.47 8.57
April 0.124667E+11 141.94 24398.16 01-APR-13:50 1311143.63 10-APR-15:20 24.71 23.91 11.15
May 0.301256E+11 342.99 24398.16 01-MAY-07:30 1648702.60 24-MAY-05:03 26.96 25.21 26.30
June 0.414076E+11 471.43 24398.16 01-JUN-00:02 1469169.80 06-JUN-05:04 28.31 25.91 37.33
July 0.423516E+11 482.18 24398.16 01-JUL-03:06 1481334.23 03-JUL-05:03 28.45 26.08 36.57
August 0.444367E+11 505.92 24398.16 01-AUG-00:05 1408282.48 10-AUG-05:03 28.49 26.01 38.92
September 0.407851E+11 464.35 24398.16 01-SEP-00:03 1646207.87 26-SEP-04:15 28.37 26.00 37.09
October 0.301520E+11 343.29 24398.16 01-OCT-00:33 1522436.33 31-OCT-05:04 27.01 25.29 26.79
November 0.188446E+11 214.55 24398.16 01-NOV-04:12 2032239.01 01-NOV-04:12 25.45 24.32 17.52
December 0.789639E+10 89.90 24398.16 01-DEC-13:40 1232604.18 06-DEC-08:15 23.77 23.28 6.20
                   
Annual Sum or Average 0.287878E+12 3277.54         26.12 24.72 21.32
Minimum of Months 0.441363E+10 50.25 24398.16   1232604.18   23.74 23.28 3.62
Maximum of Months 0.444367E+11 505.92 24398.16   2032239.01   28.49 26.08 38.92



Table of Contents

Report: BoilerReportMonthly

For: HEATSYS1 BOILER

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

BOILER HEATING ENERGY [J] BOILER GAS CONSUMPTION [] BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] BOILER HEATING RATE {Maximum} [W] BOILER HEATING RATE {TIMESTAMP} BOILER GAS CONSUMPTION RATE [] BOILER INLET TEMPERATURE [C] BOILER OUTLET TEMPERATURE [C] BOILER MASS FLOW RATE [kg/s] BOILER ANCILLARY ELECTRICITY RATE [W] BOILER PART LOAD RATIO [] BOILER PART LOAD RATIO {Maximum} [] BOILER PART LOAD RATIO {TIMESTAMP}
January 0.324353E+10 0.00 71.03 554039.54 25-JAN-06:03 0.00 38.09 43.58 0.01 0.00 0.00 0.37 25-JAN-06:03
February 0.376807E+10 0.00 38.31 944505.66 04-FEB-05:11 0.00 17.90 21.44 0.01 0.00 0.00 0.63 04-FEB-05:11
March 0.190593E+10 0.00 36.36 524303.31 16-MAR-05:03 0.00 18.37 21.42 0.00 0.00 0.00 0.35 16-MAR-05:03
April 167289.28 0.00 0.50 183.43 19-APR-06:00 0.00 18.86 18.90 0.00 0.00 0.00 0.00 19-APR-06:00
May 0.00 0.00 0.00 0.00 01-MAY-00:05 0.00 18.85 18.85 0.00 0.00 0.00 0.00 01-MAY-00:05
June 0.00 0.00 0.00 0.00 01-JUN-00:02 0.00 18.85 18.85 0.00 0.00 0.00 0.00 01-JUN-00:02
July 0.00 0.00 0.00 0.00 01-JUL-00:03 0.00 18.85 18.85 0.00 0.00 0.00 0.00 01-JUL-00:03
August 0.00 0.00 0.00 0.00 01-AUG-00:05 0.00 18.85 18.85 0.00 0.00 0.00 0.00 01-AUG-00:05
September 0.00 0.00 0.00 0.00 01-SEP-00:03 0.00 18.85 18.85 0.00 0.00 0.00 0.00 01-SEP-00:03
October 0.00 0.00 0.00 0.00 01-OCT-00:03 0.00 18.85 18.85 0.00 0.00 0.00 0.00 01-OCT-00:03
November 0.530454E+09 0.00 8.11 144269.74 13-NOV-06:02 0.00 19.61 20.30 0.00 0.00 0.00 0.10 13-NOV-06:02
December 0.406462E+10 0.00 66.84 650634.63 15-DEC-06:02 0.00 20.11 25.62 0.01 0.00 0.00 0.43 15-DEC-06:02
                           
Annual Sum or Average 0.135128E+11 0.00 221.16     0.00 20.54 22.07 0.00 0.00 0.00    
Minimum of Months 0.00 0.00 0.00 0.00   0.00 17.90 18.85 0.00 0.00 0.00 0.00  
Maximum of Months 0.406462E+10 0.00 71.03 944505.66   0.00 38.09 43.58 0.01 0.00 0.00 0.63  



Table of Contents

Report: BoilerReportMonthly

For: CENTRAL BOILER

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

BOILER HEATING ENERGY [J] BOILER GAS CONSUMPTION [] BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] BOILER HEATING RATE {Maximum} [W] BOILER HEATING RATE {TIMESTAMP} BOILER GAS CONSUMPTION RATE [] BOILER INLET TEMPERATURE [C] BOILER OUTLET TEMPERATURE [C] BOILER MASS FLOW RATE [kg/s] BOILER ANCILLARY ELECTRICITY RATE [W] BOILER PART LOAD RATIO [] BOILER PART LOAD RATIO []
January 0.00 0.00 0.00 0.00 01-JAN-00:05 0.00 25.76 25.76 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 01-FEB-00:10 0.00 31.26 31.26 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 01-MAR-00:10 0.00 36.13 36.13 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 01-APR-00:02 0.00 43.04 43.04 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 01-MAY-00:05 0.00 32.85 32.85 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 01-JUN-00:02 0.00 38.71 38.71 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 01-JUL-00:03 0.00 43.61 43.61 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 01-AUG-00:05 0.00 47.59 47.59 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 01-SEP-00:03 0.00 34.13 34.13 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 01-OCT-00:03 0.00 37.20 37.20 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 01-NOV-00:10 0.00 38.40 38.40 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 01-DEC-00:10 0.00 38.87 38.87 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.00 0.00 0.00     0.00 37.33 37.33 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00   0.00 25.76 25.76 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00   0.00 47.59 47.59 0.00 0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: VAV_BOT WITH REHEAT COOLING COIL

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.103057E+12 0.00 434.42 0.767359E+11 0.00 0.00 0.00 0.00 241912.22 07-JAN-06:02 155774.36 30-JAN-05:12 0.00 0.00 0.00
February 0.114866E+12 0.00 406.61 0.862004E+11 0.00 0.00 0.00 0.00 252536.30 17-FEB-05:11 160162.16 18-FEB-05:11 0.00 0.00 0.00
March 0.157143E+12 0.00 527.78 0.111667E+12 0.00 0.00 0.00 0.00 221732.08 06-MAR-06:02 152154.89 07-MAR-05:11 0.00 0.00 0.00
April 0.188351E+12 0.00 585.24 0.133487E+12 0.00 0.00 0.00 0.00 204683.79 29-APR-05:02 147264.74 29-APR-05:02 0.00 0.00 0.00
May 0.203682E+12 0.00 545.73 0.136977E+12 0.00 0.00 0.00 0.00 280113.08 27-MAY-03:02 167538.26 30-MAY-05:03 0.00 0.00 0.00
June 0.229803E+12 0.00 586.38 0.151900E+12 0.00 0.00 0.00 0.00 257703.84 22-JUN-05:03 169643.94 05-JUN-05:03 0.00 0.00 0.00
July 0.248806E+12 0.00 630.13 0.164825E+12 0.00 0.00 0.00 0.00 232474.94 05-JUL-05:03 170148.22 14-JUL-05:02 0.00 0.00 0.00
August 0.264772E+12 0.00 651.47 0.175992E+12 0.00 0.00 0.00 0.00 246334.87 21-AUG-05:03 181250.81 21-AUG-05:03 0.00 0.00 0.00
September 0.218780E+12 0.00 545.74 0.141572E+12 0.00 0.00 0.00 0.00 252578.13 25-SEP-05:02 171692.71 19-SEP-05:03 0.00 0.00 0.00
October 0.213335E+12 0.00 557.03 0.142294E+12 0.00 0.00 0.00 0.00 250915.59 07-OCT-05:03 167355.17 03-OCT-05:03 0.00 0.00 0.00
November 0.179437E+12 0.00 504.89 0.121853E+12 0.00 0.00 0.00 0.00 232125.28 03-NOV-05:02 163808.74 20-NOV-06:02 0.00 0.00 0.00
December 0.142038E+12 0.00 507.96 0.982195E+11 0.00 0.00 0.00 0.00 241236.47 09-DEC-06:02 161975.68 09-DEC-06:02 0.00 0.00 0.00
                               
Annual Sum or Average 0.226407E+13 0.00 6483.37 0.154172E+13 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 0.103057E+12 0.00 406.61 0.767359E+11 0.00 0.00 0.00 0.00 204683.79   147264.74   0.00 0.00 0.00
Maximum of Months 0.264772E+12 0.00 651.47 0.175992E+12 0.00 0.00 0.00 0.00 280113.08   181250.81   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: VAV_MID WITH REHEAT COOLING COIL

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.851841E+12 0.00 416.08 0.613380E+12 0.00 0.00 0.00 0.00 2265835.08 14-JAN-06:03 1318272.13 14-JAN-06:03 0.00 0.00 0.00
February 0.925583E+12 0.00 382.83 0.672573E+12 0.00 0.00 0.00 0.00 2197607.77 02-FEB-06:02 1339389.52 18-FEB-06:03 0.00 0.00 0.00
March 0.115938E+13 0.00 446.96 0.822038E+12 0.00 0.00 0.00 0.00 2511423.65 06-MAR-05:12 1450370.14 29-MAR-05:02 0.00 0.00 0.00
April 0.136184E+13 0.00 453.06 0.966134E+12 0.00 0.00 0.00 0.00 2290829.39 25-APR-04:12 1453473.38 15-APR-04:12 0.00 0.00 0.00
May 0.177990E+13 0.00 497.31 0.118850E+13 0.00 0.00 0.00 0.00 2737993.20 27-MAY-04:02 1542666.96 24-MAY-05:03 0.00 0.00 0.00
June 0.194752E+13 0.00 513.72 0.126781E+13 0.00 0.00 0.00 0.00 2679608.50 22-JUN-05:03 1598029.98 02-JUN-03:02 0.00 0.00 0.00
July 0.200966E+13 0.00 533.39 0.131269E+13 0.00 0.00 0.00 0.00 2612954.09 03-JUL-03:02 1597402.97 14-JUL-03:02 0.00 0.00 0.00
August 0.202869E+13 0.00 531.05 0.130845E+13 0.00 0.00 0.00 0.00 2443424.97 28-AUG-03:02 1538943.93 07-AUG-05:02 0.00 0.00 0.00
September 0.194079E+13 0.00 503.37 0.123304E+13 0.00 0.00 0.00 0.00 2541612.10 20-SEP-03:02 1589263.55 29-SEP-03:02 0.00 0.00 0.00
October 0.174324E+13 0.00 476.64 0.115719E+13 0.00 0.00 0.00 0.00 2586583.56 31-OCT-05:02 1515039.44 19-OCT-04:11 0.00 0.00 0.00
November 0.137180E+13 0.00 424.24 0.918690E+12 0.00 0.00 0.00 0.00 2430527.12 04-NOV-03:02 1484055.49 29-NOV-06:03 0.00 0.00 0.00
December 0.943657E+12 0.00 416.44 0.660792E+12 0.00 0.00 0.00 0.00 2590196.06 09-DEC-06:02 1528722.24 09-DEC-06:02 0.00 0.00 0.00
                               
Annual Sum or Average 0.180639E+14 0.00 5595.08 0.121213E+14 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 0.851841E+12 0.00 382.83 0.613380E+12 0.00 0.00 0.00 0.00 2197607.77   1318272.13   0.00 0.00 0.00
Maximum of Months 0.202869E+13 0.00 533.39 0.131269E+13 0.00 0.00 0.00 0.00 2737993.20   1598029.98   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: VAV_TOP WITH REHEAT COOLING COIL

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.826114E+11 0.00 409.26 0.593342E+11 0.00 0.00 0.00 0.00 230893.82 07-JAN-06:02 124461.79 14-JAN-06:03 0.00 0.00 0.00
February 0.946209E+11 0.00 373.47 0.688229E+11 0.00 0.00 0.00 0.00 210453.09 18-FEB-06:03 123339.36 18-FEB-06:03 0.00 0.00 0.00
March 0.121313E+12 0.00 440.73 0.856662E+11 0.00 0.00 0.00 0.00 254188.10 06-MAR-05:12 136365.04 14-MAR-05:02 0.00 0.00 0.00
April 0.146014E+12 0.00 448.93 0.104605E+12 0.00 0.00 0.00 0.00 226343.37 25-APR-04:12 138731.98 24-APR-04:11 0.00 0.00 0.00
May 0.191148E+12 0.00 495.32 0.131569E+12 0.00 0.00 0.00 0.00 289128.25 27-MAY-04:02 158745.78 30-MAY-05:03 0.00 0.00 0.00
June 0.210404E+12 0.00 515.74 0.140753E+12 0.00 0.00 0.00 0.00 279339.85 22-JUN-05:03 169889.41 02-JUN-03:02 0.00 0.00 0.00
July 0.218686E+12 0.00 535.46 0.147312E+12 0.00 0.00 0.00 0.00 275993.92 03-JUL-03:02 172678.84 14-JUL-03:02 0.00 0.00 0.00
August 0.217048E+12 0.00 530.40 0.144277E+12 0.00 0.00 0.00 0.00 268365.47 10-AUG-05:03 156897.17 07-AUG-05:02 0.00 0.00 0.00
September 0.205579E+12 0.00 504.14 0.134604E+12 0.00 0.00 0.00 0.00 262470.00 20-SEP-03:02 170852.64 30-SEP-03:02 0.00 0.00 0.00
October 0.179149E+12 0.00 473.37 0.121988E+12 0.00 0.00 0.00 0.00 274620.40 31-OCT-05:02 159961.45 13-OCT-05:02 0.00 0.00 0.00
November 0.138899E+12 0.00 418.49 0.941951E+11 0.00 0.00 0.00 0.00 267967.67 04-NOV-03:02 148408.01 10-NOV-06:02 0.00 0.00 0.00
December 0.937344E+11 0.00 415.44 0.651613E+11 0.00 0.00 0.00 0.00 229057.86 26-DEC-05:12 142293.06 09-DEC-06:02 0.00 0.00 0.00
                               
Annual Sum or Average 0.189920E+13 0.00 5560.73 0.129829E+13 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 0.826114E+11 0.00 373.47 0.593342E+11 0.00 0.00 0.00 0.00 210453.09   123339.36   0.00 0.00 0.00
Maximum of Months 0.218686E+12 0.00 535.46 0.147312E+12 0.00 0.00 0.00 0.00 289128.25   172678.84   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: CAV_BAS COOLING COIL

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.798334E+11 0.00 423.59 0.730627E+11 0.00 0.00 0.00 0.00 178340.03 30-JAN-05:23 104309.25 01-JAN-12:52 0.00 0.00 0.00
February 0.770349E+11 0.00 378.33 0.696599E+11 0.00 0.00 0.00 0.00 167398.03 02-FEB-05:12 114396.53 20-FEB-16:39 0.00 0.00 0.00
March 0.892622E+11 0.00 436.18 0.793095E+11 0.00 0.00 0.00 0.00 190167.97 06-MAR-05:23 103582.35 18-MAR-04:12 0.00 0.00 0.00
April 0.900736E+11 0.00 404.18 0.783108E+11 0.00 0.00 0.00 0.00 177868.78 16-APR-23:22 106188.11 20-APR-04:11 0.00 0.00 0.00
May 0.114136E+12 0.00 446.08 0.897917E+11 0.00 0.00 0.00 0.00 214542.07 29-MAY-13:06 102908.59 29-MAY-15:41 0.00 0.00 0.00
June 0.127747E+12 0.00 444.19 0.918875E+11 0.00 0.00 0.00 0.00 206064.21 26-JUN-03:02 99855.34 25-JUN-19:02 0.00 0.00 0.00
July 0.132089E+12 0.00 442.58 0.942425E+11 0.00 0.00 0.00 0.00 204674.87 31-JUL-03:13 108874.08 04-JUL-15:30 0.00 0.00 0.00
August 0.145293E+12 0.00 479.84 0.103598E+12 0.00 0.00 0.00 0.00 206792.12 13-AUG-15:20 103653.43 06-AUG-14:38 0.00 0.00 0.00
September 0.127968E+12 0.00 449.94 0.925391E+11 0.00 0.00 0.00 0.00 205716.93 10-SEP-18:38 104263.55 17-SEP-14:30 0.00 0.00 0.00
October 0.122846E+12 0.00 459.84 0.939972E+11 0.00 0.00 0.00 0.00 215765.13 30-OCT-03:02 105346.23 15-OCT-15:17 0.00 0.00 0.00
November 0.107035E+12 0.00 429.51 0.859328E+11 0.00 0.00 0.00 0.00 202051.78 05-NOV-14:28 104681.53 15-NOV-05:12 0.00 0.00 0.00
December 0.853396E+11 0.00 433.20 0.762988E+11 0.00 0.00 0.00 0.00 190678.03 10-DEC-12:51 106645.12 03-DEC-15:56 0.00 0.00 0.00
                               
Annual Sum or Average 0.129866E+13 0.00 5227.46 0.102863E+13 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 0.770349E+11 0.00 378.33 0.696599E+11 0.00 0.00 0.00 0.00 167398.03   99855.34   0.00 0.00 0.00
Maximum of Months 0.145293E+12 0.00 479.84 0.103598E+12 0.00 0.00 0.00 0.00 215765.13   114396.53   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: AIRLOOP DATACENTER BASEMENT COOLING COIL

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [J] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [J] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION {Maximum} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL RUNTIME FRACTION {MINIMUM} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE {Maximum} [W] COOLING COIL LATENT COOLING RATE {TIMESTAMP} COOLING COIL ELECTRICITY RATE {Maximum} [W] COOLING COIL ELECTRICITY RATE {TIMESTAMP} COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.340157E+12 0.937524E+11 744.00 0.330546E+12 0.961073E+10 0.00 0.39 02-JAN-15:00 0.31 23-JAN-05:00 140394.43 02-JAN-15:00 130674.34 02-JAN-15:00 10240.55 06-JAN-17:00 49044.63 02-JAN-15:00 0.00
February 0.530443E+12 0.150039E+12 672.00 0.520529E+12 0.991434E+10 0.00 0.61 02-FEB-14:00 0.52 01-FEB-00:10 231075.54 10-FEB-17:00 221312.91 22-FEB-16:00 11353.21 02-FEB-15:30 79448.16 11-FEB-14:00 0.00
March 0.834877E+12 0.238828E+12 744.00 0.822125E+12 0.127521E+11 0.00 0.97 31-MAR-23:30 0.72 01-MAR-04:20 396647.92 31-MAR-24:00 393817.22 31-MAR-24:00 12538.70 13-MAR-10:00 116268.17 31-MAR-23:20 0.00
April 0.104574E+13 0.317757E+12 720.00 0.103269E+13 0.130430E+11 0.00 1.00 01-APR-13:10 0.37 30-APR-23:53 425402.70 25-APR-16:00 407141.49 25-APR-16:00 18261.21 25-APR-16:00 145712.47 17-APR-15:00 0.00
May 0.360308E+12 0.118038E+12 744.00 0.338716E+12 0.215913E+11 0.00 0.59 31-MAY-23:03 0.34 07-MAY-05:00 229271.31 31-MAY-23:03 212541.04 31-MAY-24:00 17212.48 31-MAY-23:03 73890.32 31-MAY-23:13 0.00
June 0.592182E+12 0.198689E+12 720.00 0.565497E+12 0.266848E+11 0.00 0.80 30-JUN-23:12 0.58 01-JUN-06:00 316724.06 30-JUN-23:03 304204.07 30-JUN-23:53 16213.36 23-JUN-14:00 103517.43 30-JUN-23:12 0.00
July 0.858013E+12 0.290949E+12 744.00 0.830811E+12 0.272026E+11 0.00 1.00 31-JUL-23:03 0.78 04-JUL-04:40 402259.48 31-JUL-24:00 392007.36 31-JUL-24:00 16557.68 25-JUL-15:00 136188.76 31-JUL-24:00 0.00
August 0.109298E+13 0.360792E+12 744.00 0.106733E+13 0.256534E+11 0.00 1.00 01-AUG-00:05 0.42 31-AUG-23:17 425831.11 23-AUG-17:00 407321.10 23-AUG-17:00 18510.01 23-AUG-17:00 150599.23 23-AUG-13:00 0.00
September 0.356542E+12 0.119969E+12 720.00 0.331317E+12 0.252252E+11 0.00 0.59 30-SEP-23:12 0.35 05-SEP-06:00 224750.41 30-SEP-23:03 213001.49 30-SEP-23:57 13651.51 07-SEP-14:00 75684.69 30-SEP-23:12 0.00
October 0.608741E+12 0.197222E+12 744.00 0.584968E+12 0.237727E+11 0.00 0.78 31-OCT-23:10 0.57 16-OCT-01:00 313228.93 31-OCT-23:10 303056.80 31-OCT-24:00 15476.97 04-OCT-08:30 91497.76 31-OCT-23:20 0.00
November 0.818361E+12 0.246553E+12 720.00 0.800352E+12 0.180096E+11 0.00 0.84 03-NOV-14:00 0.73 11-NOV-07:30 326897.81 30-NOV-17:00 314523.92 17-NOV-15:00 14024.90 29-NOV-11:00 114651.88 17-NOV-15:00 0.00
December 0.107957E+13 0.297260E+12 744.00 0.106754E+13 0.120308E+11 0.00 1.00 01-DEC-09:20 0.91 16-DEC-04:00 413874.72 08-DEC-17:10 404691.34 11-DEC-16:20 11987.81 08-DEC-17:10 136982.51 10-DEC-15:00 0.00
                                       
Annual Sum or Average 0.851791E+13 0.262985E+13 8760.00 0.829242E+13 0.225491E+12 0.00                         0.00
Minimum of Months 0.340157E+12 0.937524E+11 672.00 0.330546E+12 0.961073E+10 0.00 0.39   0.31   140394.43   130674.34   10240.55   49044.63   0.00
Maximum of Months 0.109298E+13 0.360792E+12 744.00 0.106754E+13 0.272026E+11 0.00 1.00   0.91   425831.11   407321.10   18510.01   150599.23   0.00



Table of Contents

Report: DXReportMonthly

For: AIRLOOP DATACENTER BOT COOLING COIL

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [J] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [J] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION {Maximum} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL RUNTIME FRACTION {MINIMUM} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE {Maximum} [W] COOLING COIL LATENT COOLING RATE {TIMESTAMP} COOLING COIL ELECTRICITY RATE {Maximum} [W] COOLING COIL ELECTRICITY RATE {TIMESTAMP} COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.577985E+10 0.158096E+10 744.00 0.540323E+10 0.376614E+09 0.00 0.37 02-JAN-15:00 0.18 26-JAN-08:00 3009.79 02-JAN-15:00 2640.99 02-JAN-17:00 410.32 02-JAN-15:20 1006.47 02-JAN-15:00 0.00
February 0.101074E+11 0.282012E+10 672.00 0.969739E+10 0.410009E+09 0.00 0.58 19-FEB-17:12 0.38 04-FEB-08:00 4956.49 19-FEB-17:23 4822.03 20-FEB-17:50 443.46 02-FEB-15:20 1566.52 02-FEB-14:00 0.00
March 0.164577E+11 0.463512E+10 744.00 0.159034E+11 0.554314E+09 0.00 0.87 31-MAR-24:00 0.61 11-MAR-08:00 7836.51 31-MAR-23:05 7684.14 31-MAR-24:00 527.91 13-MAR-10:00 2319.88 13-MAR-16:00 0.00
April 0.210775E+11 0.631793E+10 720.00 0.204599E+11 0.617658E+09 0.00 1.00 12-APR-15:50 0.30 30-APR-23:53 8893.44 13-APR-16:00 8479.83 09-APR-17:50 551.30 25-APR-15:30 3133.70 17-APR-15:00 0.00
May 0.707565E+10 0.224273E+10 744.00 0.619899E+10 0.876661E+09 0.00 0.55 31-MAY-23:03 0.27 09-MAY-06:00 4798.65 31-MAY-23:03 4066.74 31-MAY-24:00 752.12 31-MAY-23:03 1474.06 31-MAY-23:13 0.00
June 0.120593E+11 0.391807E+10 720.00 0.109164E+11 0.114290E+10 0.00 0.74 30-JUN-23:05 0.50 14-JUN-06:00 6490.05 30-JUN-23:03 5911.44 30-JUN-23:47 636.14 23-JUN-14:00 2049.56 30-JUN-23:12 0.00
July 0.175933E+11 0.580287E+10 744.00 0.163862E+11 0.120707E+10 0.00 0.95 31-JUL-23:35 0.70 04-JUL-04:40 8457.32 31-JUL-23:03 7854.20 31-JUL-23:40 688.74 25-JUL-15:00 2797.30 31-JUL-23:25 0.00
August 0.227726E+11 0.748039E+10 744.00 0.215299E+11 0.124270E+10 0.00 1.00 01-AUG-10:50 0.36 31-AUG-23:52 9038.20 21-AUG-13:00 8431.75 20-AUG-18:10 662.84 21-AUG-12:50 3241.43 23-AUG-13:00 0.00
September 0.710388E+10 0.230253E+10 720.00 0.607154E+10 0.103234E+10 0.00 0.54 30-SEP-23:05 0.28 27-SEP-06:00 4557.11 30-SEP-23:03 4034.86 30-SEP-23:35 559.60 22-SEP-08:00 1475.49 30-SEP-23:12 0.00
October 0.122284E+11 0.384932E+10 744.00 0.112170E+11 0.101145E+10 0.00 0.71 31-OCT-23:10 0.48 28-OCT-06:55 6304.64 31-OCT-23:10 5863.25 31-OCT-24:00 657.61 04-OCT-08:20 1825.91 03-OCT-15:00 0.00
November 0.163215E+11 0.481807E+10 720.00 0.155313E+11 0.790194E+09 0.00 0.82 07-NOV-17:00 0.62 27-NOV-07:00 7113.10 07-NOV-17:00 6697.22 07-NOV-17:00 618.77 29-NOV-11:00 2338.84 17-NOV-15:00 0.00
December 0.213617E+11 0.581142E+10 744.00 0.208009E+11 0.560852E+09 0.00 1.00 08-DEC-16:50 0.77 16-DEC-08:00 9030.43 08-DEC-17:00 8569.60 06-DEC-17:00 505.33 08-DEC-16:50 2857.98 10-DEC-14:51 0.00
                                       
Annual Sum or Average 0.169939E+12 0.515795E+11 8760.00 0.160116E+12 0.982276E+10 0.00                         0.00
Minimum of Months 0.577985E+10 0.158096E+10 672.00 0.540323E+10 0.376614E+09 0.00 0.37   0.18   3009.79   2640.99   410.32   1006.47   0.00
Maximum of Months 0.227726E+11 0.748039E+10 744.00 0.215299E+11 0.124270E+10 0.00 1.00   0.77   9038.20   8569.60   752.12   3241.43   0.00



Table of Contents

Report: DXReportMonthly

For: AIRLOOP DATACENTER MID COOLING COIL

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [J] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [J] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION {Maximum} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL RUNTIME FRACTION {MINIMUM} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE {Maximum} [W] COOLING COIL LATENT COOLING RATE {TIMESTAMP} COOLING COIL ELECTRICITY RATE {Maximum} [W] COOLING COIL ELECTRICITY RATE {TIMESTAMP} COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.469627E+11 0.130534E+11 744.00 0.433608E+11 0.360195E+10 0.00 0.36 02-JAN-15:00 0.12 26-JAN-07:00 28172.61 02-JAN-15:00 24546.05 02-JAN-17:00 4059.18 06-JAN-17:00 9423.41 02-JAN-15:00 0.00
February 0.905764E+11 0.254800E+11 672.00 0.865296E+11 0.404674E+10 0.00 0.57 19-FEB-17:22 0.31 05-FEB-07:00 46440.11 10-FEB-17:00 44150.71 21-FEB-17:50 4399.41 02-FEB-15:20 14853.64 02-FEB-14:00 0.00
March 0.153790E+12 0.434901E+11 744.00 0.148264E+12 0.552557E+10 0.00 0.88 31-MAR-24:00 0.56 20-MAR-06:55 75628.50 31-MAR-23:05 74197.60 31-MAR-24:00 5268.98 14-MAR-09:00 22015.13 13-MAR-16:00 0.00
April 0.200571E+12 0.601605E+11 720.00 0.194389E+12 0.618287E+10 0.00 1.00 14-APR-14:00 0.29 30-APR-23:53 84825.00 13-APR-16:00 80146.67 12-APR-16:00 5481.56 25-APR-15:30 29762.92 17-APR-15:00 0.00
May 0.663207E+11 0.210401E+11 744.00 0.576629E+11 0.865779E+10 0.00 0.56 31-MAY-23:03 0.25 01-MAY-06:00 46802.87 31-MAY-23:03 39146.40 31-MAY-24:00 7718.93 31-MAY-23:03 14299.63 31-MAY-23:13 0.00
June 0.114946E+12 0.373289E+11 720.00 0.103568E+12 0.113771E+11 0.00 0.75 30-JUN-23:05 0.49 13-JUN-06:00 62898.67 30-JUN-23:03 57070.02 30-JUN-23:53 6314.09 23-JUN-14:00 19806.86 30-JUN-23:12 0.00
July 0.167848E+12 0.553454E+11 744.00 0.155803E+12 0.120451E+11 0.00 0.96 31-JUL-23:53 0.69 14-JUL-21:20 81590.71 31-JUL-23:03 75597.66 31-JUL-23:55 6853.98 25-JUL-15:00 26936.07 31-JUL-23:53 0.00
August 0.216094E+12 0.710614E+11 744.00 0.203669E+12 0.124255E+11 0.00 1.00 01-AUG-11:50 0.32 31-AUG-23:23 85762.22 08-AUG-15:00 79732.35 30-AUG-16:00 6640.74 22-AUG-15:00 30988.54 23-AUG-13:00 0.00
September 0.663314E+11 0.215141E+11 720.00 0.561424E+11 0.101890E+11 0.00 0.53 30-SEP-23:05 0.26 16-SEP-07:00 43543.41 30-SEP-23:03 38282.04 30-SEP-23:45 5572.98 30-SEP-23:03 14054.33 30-SEP-23:12 0.00
October 0.115966E+12 0.365144E+11 744.00 0.105906E+12 0.100601E+11 0.00 0.70 31-OCT-23:10 0.45 28-OCT-06:55 59698.63 31-OCT-23:10 55233.18 31-OCT-24:00 6572.54 04-OCT-08:20 17412.19 03-OCT-15:00 0.00
November 0.153287E+12 0.453920E+11 720.00 0.145409E+12 0.787795E+10 0.00 0.81 07-NOV-17:00 0.56 27-NOV-08:00 67912.56 07-NOV-17:00 63761.19 07-NOV-17:00 6175.07 29-NOV-11:00 22250.07 03-NOV-14:00 0.00
December 0.197998E+12 0.541774E+11 744.00 0.192392E+12 0.560589E+10 0.00 0.99 08-DEC-16:50 0.71 16-DEC-08:00 85929.10 08-DEC-17:00 81283.36 06-DEC-17:00 5047.58 08-DEC-16:50 26960.38 08-DEC-16:00 0.00
                                       
Annual Sum or Average 0.159069E+13 0.484558E+12 8760.00 0.149310E+13 0.975956E+11 0.00                         0.00
Minimum of Months 0.469627E+11 0.130534E+11 672.00 0.433608E+11 0.360195E+10 0.00 0.36   0.12   28172.61   24546.05   4059.18   9423.41   0.00
Maximum of Months 0.216094E+12 0.710614E+11 744.00 0.203669E+12 0.124255E+11 0.00 1.00   0.71   85929.10   81283.36   7718.93   30988.54   0.00



Table of Contents

Report: DXReportMonthly

For: AIRLOOP DATACENTER TOP COOLING COIL

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [J] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [J] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION {Maximum} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL RUNTIME FRACTION {MINIMUM} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE {Maximum} [W] COOLING COIL LATENT COOLING RATE {TIMESTAMP} COOLING COIL ELECTRICITY RATE {Maximum} [W] COOLING COIL ELECTRICITY RATE {TIMESTAMP} COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.416360E+10 0.117662E+10 743.21 0.381303E+10 0.350569E+09 0.00 0.36 02-JAN-15:00 0.00 22-JAN-07:20 2874.43 02-JAN-15:00 2506.47 02-JAN-17:00 408.51 02-JAN-15:20 961.62 02-JAN-15:00 0.00
February 0.875792E+10 0.248185E+10 672.00 0.835548E+10 0.402444E+09 0.00 0.57 19-FEB-17:12 0.19 05-FEB-07:35 4720.78 19-FEB-17:22 4484.51 21-FEB-17:40 442.76 02-FEB-10:50 1510.51 02-FEB-14:00 0.00
March 0.152186E+11 0.432443E+10 744.00 0.146674E+11 0.551185E+09 0.00 0.86 31-MAR-24:00 0.48 16-MAR-06:00 7516.99 31-MAR-23:05 7370.96 31-MAR-24:00 527.00 14-MAR-09:00 2239.91 13-MAR-16:00 0.00
April 0.200696E+11 0.603746E+10 720.00 0.194525E+11 0.617130E+09 0.00 1.00 14-APR-14:30 0.28 30-APR-23:53 8628.56 13-APR-16:00 8189.90 09-APR-17:51 547.97 25-APR-15:30 3022.60 17-APR-15:00 0.00
May 0.674479E+10 0.214281E+10 744.00 0.587676E+10 0.868039E+09 0.00 0.55 31-MAY-23:03 0.23 01-MAY-07:00 4699.24 31-MAY-23:03 3933.14 31-MAY-24:00 766.65 31-MAY-23:03 1438.52 31-MAY-23:08 0.00
June 0.116261E+11 0.378024E+10 720.00 0.104877E+11 0.113838E+10 0.00 0.74 30-JUN-23:05 0.48 13-JUN-07:00 6306.21 30-JUN-23:03 5711.11 30-JUN-23:15 632.77 23-JUN-14:00 1990.15 30-JUN-23:12 0.00
July 0.169573E+11 0.559969E+10 744.00 0.157529E+11 0.120435E+10 0.00 0.95 31-JUL-23:53 0.68 14-JUL-21:30 8187.98 31-JUL-23:03 7588.98 31-JUL-23:55 686.29 25-JUL-15:00 2708.96 31-JUL-23:53 0.00
August 0.217303E+11 0.716188E+10 744.00 0.204887E+11 0.124169E+10 0.00 1.00 01-AUG-12:20 0.31 31-AUG-23:23 8722.45 23-AUG-16:20 8167.03 20-AUG-18:00 661.56 22-AUG-15:00 3156.35 23-AUG-13:00 0.00
September 0.674099E+10 0.219007E+10 720.00 0.571967E+10 0.102132E+10 0.00 0.53 30-SEP-23:05 0.24 26-SEP-06:55 4405.03 30-SEP-23:03 3880.97 30-SEP-23:25 558.26 22-SEP-08:70 1428.04 30-SEP-23:12 0.00
October 0.116072E+11 0.366310E+10 744.00 0.106024E+11 0.100477E+10 0.00 0.68 31-OCT-23:10 0.43 28-OCT-06:55 5896.06 31-OCT-23:10 5446.00 31-OCT-24:00 658.21 04-OCT-08:20 1780.38 03-OCT-15:00 0.00
November 0.151363E+11 0.450538E+10 720.00 0.143505E+11 0.785877E+09 0.00 0.81 07-NOV-17:00 0.49 27-NOV-07:00 6864.96 07-NOV-17:00 6450.25 07-NOV-17:00 618.03 29-NOV-11:00 2257.87 17-NOV-15:00 0.00
December 0.194063E+11 0.534562E+10 744.00 0.188476E+11 0.558659E+09 0.00 0.99 08-DEC-16:50 0.64 16-DEC-07:40 8668.24 08-DEC-17:00 8203.24 06-DEC-17:00 504.42 08-DEC-16:50 2726.32 08-DEC-16:00 0.00
                                       
Annual Sum or Average 0.158159E+12 0.484091E+11 8759.21 0.148415E+12 0.974441E+10 0.00                         0.00
Minimum of Months 0.416360E+10 0.117662E+10 672.00 0.381303E+10 0.350569E+09 0.00 0.36   0.00   2874.43   2506.47   408.51   961.62   0.00
Maximum of Months 0.217303E+11 0.716188E+10 744.00 0.204887E+11 0.124169E+10 0.00 1.00   0.68   8722.45   8203.24   766.65   3156.35   0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 117.58 0.00 117.58 114.59 291.77 0.00 0.00 0.00
February 139.17 0.00 139.17 174.40 245.17 0.00 0.00 0.00
March 165.97 0.00 165.97 210.57 200.91 0.00 0.00 0.00
April 185.98 0.84 185.14 297.22 124.11 0.00 0.00 0.00
May 212.38 9.50 202.88 415.96 65.15 0.00 0.00 0.00
June 226.86 16.33 210.53 479.04 27.60 0.00 0.00 0.00
July 229.58 11.25 218.33 506.74 39.85 0.00 0.00 0.00
August 203.18 1.87 201.31 422.85 26.88 0.00 0.00 0.00
September 180.25 0.01 180.23 394.43 47.40 0.00 0.00 0.00
October 151.00 0.00 151.00 289.32 75.49 0.00 0.00 0.00
November 131.30 0.00 131.30 200.32 152.37 0.00 0.00 0.00
December 116.30 0.00 116.30 127.48 254.47 0.00 0.00 0.00
                 
Annual Sum or Average 171.79 3.33 168.46 303.36 128.77 0.00 0.00 0.00
Minimum of Months 116.30 0.00 116.30 114.59 26.88 0.00 0.00 0.00
Maximum of Months 229.58 16.33 218.33 506.74 291.77 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 117.58 0.00 117.58 114.59 291.77 0.00 0.00 0.00
February 139.17 0.00 139.17 174.40 245.17 0.00 0.00 0.00
March 165.97 0.00 165.97 210.57 200.91 0.00 0.00 0.00
April 185.98 0.84 185.14 297.22 124.11 0.00 0.00 0.00
May 212.38 9.50 202.88 415.96 65.15 0.00 0.00 0.00
June 226.86 16.33 210.53 479.04 27.60 0.00 0.00 0.00
July 229.58 11.25 218.33 506.74 39.85 0.00 0.00 0.00
August 203.18 1.87 201.31 422.85 26.88 0.00 0.00 0.00
September 180.24 0.01 180.23 394.43 47.40 0.00 0.00 0.00
October 151.00 0.00 151.00 289.32 75.49 0.00 0.00 0.00
November 131.30 0.00 131.30 200.31 152.37 0.00 0.00 0.00
December 116.30 0.00 116.30 127.48 254.47 0.00 0.00 0.00
                 
Annual Sum or Average 171.79 3.33 168.46 303.36 128.77 0.00 0.00 0.00
Minimum of Months 116.30 0.00 116.30 114.59 26.88 0.00 0.00 0.00
Maximum of Months 229.58 16.33 218.33 506.74 291.77 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 117.58 0.00 117.58 114.59 291.77 0.00 0.00 0.00
February 139.17 0.00 139.17 174.40 245.17 0.00 0.00 0.00
March 165.97 0.00 165.97 210.57 200.91 0.00 0.00 0.00
April 185.98 0.84 185.14 297.22 124.11 0.00 0.00 0.00
May 212.38 9.50 202.88 415.96 65.15 0.00 0.00 0.00
June 226.86 16.33 210.53 479.04 27.60 0.00 0.00 0.00
July 229.58 11.25 218.33 506.74 39.85 0.00 0.00 0.00
August 203.18 1.87 201.31 422.85 26.88 0.00 0.00 0.00
September 180.25 0.01 180.23 394.43 47.40 0.00 0.00 0.00
October 151.00 0.00 151.00 289.32 75.49 0.00 0.00 0.00
November 131.30 0.00 131.30 200.32 152.37 0.00 0.00 0.00
December 116.30 0.00 116.30 127.48 254.47 0.00 0.00 0.00
                 
Annual Sum or Average 171.79 3.33 168.46 303.36 128.77 0.00 0.00 0.00
Minimum of Months 116.30 0.00 116.30 114.59 26.88 0.00 0.00 0.00
Maximum of Months 229.58 16.33 218.33 506.74 291.77 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 117.58 0.00 117.58 114.59 291.77 0.00 0.00 0.00
February 139.17 0.00 139.17 174.40 245.17 0.00 0.00 0.00
March 165.97 0.00 165.97 210.57 200.91 0.00 0.00 0.00
April 185.98 0.84 185.14 297.22 124.11 0.00 0.00 0.00
May 212.38 9.50 202.88 415.96 65.15 0.00 0.00 0.00
June 226.86 16.33 210.53 479.04 27.60 0.00 0.00 0.00
July 229.58 11.25 218.33 506.74 39.85 0.00 0.00 0.00
August 203.18 1.87 201.31 422.85 26.88 0.00 0.00 0.00
September 180.24 0.01 180.23 394.43 47.40 0.00 0.00 0.00
October 151.00 0.00 151.00 289.32 75.49 0.00 0.00 0.00
November 131.30 0.00 131.30 200.31 152.37 0.00 0.00 0.00
December 116.30 0.00 116.30 127.48 254.47 0.00 0.00 0.00
                 
Annual Sum or Average 171.79 3.33 168.46 303.36 128.77 0.00 0.00 0.00
Minimum of Months 116.30 0.00 116.30 114.59 26.88 0.00 0.00 0.00
Maximum of Months 229.58 16.33 218.33 506.74 291.77 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 117.57 0.00 117.57 114.58 291.76 0.00 0.00 0.00
February 139.16 0.00 139.16 174.40 245.16 0.00 0.00 0.00
March 165.96 0.00 165.96 210.56 200.91 0.00 0.00 0.00
April 185.97 0.84 185.13 297.21 124.10 0.00 0.00 0.00
May 212.37 9.50 202.87 415.95 65.15 0.00 0.00 0.00
June 226.85 16.33 210.52 479.02 27.60 0.00 0.00 0.00
July 229.57 11.25 218.32 506.72 39.85 0.00 0.00 0.00
August 203.17 1.87 201.30 422.83 26.88 0.00 0.00 0.00
September 180.24 0.01 180.22 394.41 47.40 0.00 0.00 0.00
October 151.00 0.00 151.00 289.30 75.49 0.00 0.00 0.00
November 131.29 0.00 131.29 200.31 152.37 0.00 0.00 0.00
December 116.29 0.00 116.29 127.47 254.46 0.00 0.00 0.00
                 
Annual Sum or Average 171.78 3.33 168.45 303.35 128.76 0.00 0.00 0.00
Minimum of Months 116.29 0.00 116.29 114.58 26.88 0.00 0.00 0.00
Maximum of Months 229.57 16.33 218.32 506.72 291.76 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 314.56 150.69 163.86 426.90 299.22 0.00 0.00 0.00
February 363.21 168.13 195.08 536.72 249.27 0.00 0.00 0.00
March 443.45 209.64 233.81 661.52 197.03 0.00 0.00 0.00
April 481.26 214.73 266.52 807.51 126.12 0.00 0.00 0.00
May 455.29 181.31 273.98 836.84 66.58 0.00 0.00 0.00
June 449.38 172.60 276.77 872.36 25.31 0.00 0.00 0.00
July 461.74 166.51 295.23 925.35 36.56 0.00 0.00 0.00
August 422.22 141.18 281.04 824.68 18.62 0.00 0.00 0.00
September 407.05 147.15 259.90 803.42 50.27 0.00 0.00 0.00
October 374.67 161.36 213.31 685.59 75.72 0.00 0.00 0.00
November 304.09 121.25 182.84 495.98 148.32 0.00 0.00 0.00
December 245.64 86.72 158.92 343.66 250.37 0.00 0.00 0.00
                 
Annual Sum or Average 393.61 160.00 233.61 685.61 128.07 0.00 0.00 0.00
Minimum of Months 245.64 86.72 158.92 343.66 18.62 0.00 0.00 0.00
Maximum of Months 481.26 214.73 295.23 925.35 299.22 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 314.56 150.69 163.86 426.90 299.22 0.00 0.00 0.00
February 363.21 168.13 195.08 536.72 249.27 0.00 0.00 0.00
March 443.45 209.64 233.81 661.52 197.03 0.00 0.00 0.00
April 481.26 214.73 266.52 807.51 126.12 0.00 0.00 0.00
May 455.29 181.31 273.98 836.84 66.58 0.00 0.00 0.00
June 449.38 172.60 276.77 872.36 25.31 0.00 0.00 0.00
July 461.74 166.51 295.23 925.35 36.56 0.00 0.00 0.00
August 422.22 141.18 281.04 824.68 18.62 0.00 0.00 0.00
September 407.05 147.15 259.90 803.42 50.27 0.00 0.00 0.00
October 374.67 161.36 213.31 685.59 75.72 0.00 0.00 0.00
November 304.09 121.25 182.84 495.98 148.32 0.00 0.00 0.00
December 245.64 86.72 158.92 343.66 250.37 0.00 0.00 0.00
                 
Annual Sum or Average 393.61 160.00 233.61 685.61 128.07 0.00 0.00 0.00
Minimum of Months 245.64 86.72 158.92 343.66 18.62 0.00 0.00 0.00
Maximum of Months 481.26 214.73 295.23 925.35 299.22 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 314.55 150.69 163.86 426.89 299.22 0.00 0.00 0.00
February 363.20 168.13 195.08 536.71 249.27 0.00 0.00 0.00
March 443.44 209.64 233.80 661.51 197.02 0.00 0.00 0.00
April 481.25 214.73 266.52 807.50 126.12 0.00 0.00 0.00
May 455.28 181.30 273.98 836.83 66.58 0.00 0.00 0.00
June 449.37 172.60 276.77 872.34 25.31 0.00 0.00 0.00
July 461.73 166.51 295.22 925.33 36.56 0.00 0.00 0.00
August 422.21 141.18 281.03 824.67 18.62 0.00 0.00 0.00
September 407.04 147.15 259.89 803.41 50.27 0.00 0.00 0.00
October 374.66 161.35 213.31 685.58 75.72 0.00 0.00 0.00
November 304.09 121.25 182.84 495.97 148.31 0.00 0.00 0.00
December 245.64 86.72 158.92 343.66 250.36 0.00 0.00 0.00
                 
Annual Sum or Average 393.60 160.00 233.61 685.60 128.07 0.00 0.00 0.00
Minimum of Months 245.64 86.72 158.92 343.66 18.62 0.00 0.00 0.00
Maximum of Months 481.25 214.73 295.22 925.33 299.22 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 552.60 359.01 193.59 837.38 285.20 0.00 0.00 0.00
February 499.91 289.26 210.65 799.77 244.42 0.00 0.00 0.00
March 383.82 162.27 221.54 621.19 200.54 0.00 0.00 0.00
April 260.99 45.77 215.22 465.41 131.26 0.00 0.00 0.00
May 209.14 4.52 204.61 411.36 64.23 0.00 0.00 0.00
June 199.40 0.38 199.02 423.10 27.73 0.00 0.00 0.00
July 213.50 1.98 211.52 473.97 39.52 0.00 0.00 0.00
August 242.31 20.45 221.87 508.66 28.01 0.00 0.00 0.00
September 310.19 76.01 234.18 651.55 51.89 0.00 0.00 0.00
October 426.58 200.14 226.44 794.25 88.61 0.00 0.00 0.00
November 485.35 270.88 214.47 809.58 157.65 0.00 0.00 0.00
December 532.55 335.90 196.65 825.08 254.59 0.00 0.00 0.00
                 
Annual Sum or Average 359.04 146.58 212.46 634.28 130.63 0.00 0.00 0.00
Minimum of Months 199.40 0.38 193.59 411.36 27.73 0.00 0.00 0.00
Maximum of Months 552.60 359.01 234.18 837.38 285.20 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 552.60 359.01 193.59 837.38 285.20 0.00 0.00 0.00
February 499.91 289.26 210.65 799.77 244.42 0.00 0.00 0.00
March 383.81 162.27 221.54 621.18 200.54 0.00 0.00 0.00
April 260.99 45.77 215.22 465.41 131.26 0.00 0.00 0.00
May 209.14 4.52 204.61 411.36 64.23 0.00 0.00 0.00
June 199.40 0.38 199.02 423.10 27.73 0.00 0.00 0.00
July 213.50 1.98 211.52 473.97 39.52 0.00 0.00 0.00
August 242.31 20.45 221.87 508.66 28.01 0.00 0.00 0.00
September 310.19 76.01 234.18 651.55 51.89 0.00 0.00 0.00
October 426.58 200.14 226.44 794.25 88.61 0.00 0.00 0.00
November 485.35 270.88 214.47 809.58 157.65 0.00 0.00 0.00
December 532.55 335.90 196.65 825.08 254.59 0.00 0.00 0.00
                 
Annual Sum or Average 359.04 146.58 212.46 634.28 130.63 0.00 0.00 0.00
Minimum of Months 199.40 0.38 193.59 411.36 27.73 0.00 0.00 0.00
Maximum of Months 552.60 359.01 234.18 837.38 285.20 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 552.60 359.01 193.59 837.38 285.20 0.00 0.00 0.00
February 499.91 289.26 210.65 799.77 244.42 0.00 0.00 0.00
March 383.82 162.27 221.54 621.19 200.54 0.00 0.00 0.00
April 260.99 45.77 215.22 465.41 131.26 0.00 0.00 0.00
May 209.14 4.52 204.61 411.36 64.23 0.00 0.00 0.00
June 199.40 0.38 199.02 423.10 27.73 0.00 0.00 0.00
July 213.50 1.98 211.52 473.97 39.52 0.00 0.00 0.00
August 242.31 20.45 221.87 508.66 28.01 0.00 0.00 0.00
September 310.19 76.01 234.18 651.55 51.89 0.00 0.00 0.00
October 426.58 200.14 226.44 794.25 88.61 0.00 0.00 0.00
November 485.35 270.88 214.47 809.58 157.65 0.00 0.00 0.00
December 532.55 335.90 196.65 825.08 254.59 0.00 0.00 0.00
                 
Annual Sum or Average 359.04 146.58 212.46 634.28 130.63 0.00 0.00 0.00
Minimum of Months 199.40 0.38 193.59 411.36 27.73 0.00 0.00 0.00
Maximum of Months 552.60 359.01 234.18 837.38 285.20 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 552.60 359.01 193.59 837.38 285.20 0.00 0.00 0.00
February 499.91 289.26 210.65 799.77 244.42 0.00 0.00 0.00
March 383.81 162.27 221.54 621.18 200.54 0.00 0.00 0.00
April 260.99 45.77 215.22 465.41 131.26 0.00 0.00 0.00
May 209.14 4.52 204.61 411.36 64.23 0.00 0.00 0.00
June 199.40 0.38 199.02 423.10 27.73 0.00 0.00 0.00
July 213.50 1.98 211.52 473.97 39.52 0.00 0.00 0.00
August 242.31 20.45 221.87 508.66 28.01 0.00 0.00 0.00
September 310.19 76.01 234.18 651.55 51.89 0.00 0.00 0.00
October 426.58 200.14 226.44 794.25 88.61 0.00 0.00 0.00
November 485.35 270.88 214.47 809.58 157.65 0.00 0.00 0.00
December 532.55 335.90 196.65 825.08 254.59 0.00 0.00 0.00
                 
Annual Sum or Average 359.04 146.58 212.46 634.28 130.63 0.00 0.00 0.00
Minimum of Months 199.40 0.38 193.59 411.36 27.73 0.00 0.00 0.00
Maximum of Months 552.60 359.01 234.18 837.38 285.20 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 552.58 359.00 193.58 837.35 285.19 0.00 0.00 0.00
February 499.89 289.25 210.64 799.74 244.41 0.00 0.00 0.00
March 383.80 162.27 221.53 621.16 200.53 0.00 0.00 0.00
April 260.98 45.77 215.21 465.39 131.25 0.00 0.00 0.00
May 209.13 4.52 204.61 411.34 64.23 0.00 0.00 0.00
June 199.39 0.38 199.01 423.09 27.73 0.00 0.00 0.00
July 213.49 1.98 211.51 473.95 39.52 0.00 0.00 0.00
August 242.30 20.45 221.86 508.64 28.01 0.00 0.00 0.00
September 310.18 76.01 234.17 651.53 51.89 0.00 0.00 0.00
October 426.56 200.13 226.43 794.22 88.60 0.00 0.00 0.00
November 485.33 270.87 214.46 809.55 157.65 0.00 0.00 0.00
December 532.53 335.89 196.64 825.05 254.58 0.00 0.00 0.00
                 
Annual Sum or Average 359.03 146.58 212.45 634.25 130.63 0.00 0.00 0.00
Minimum of Months 199.39 0.38 193.58 411.34 27.73 0.00 0.00 0.00
Maximum of Months 552.58 359.00 234.17 837.35 285.19 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 282.58 121.82 160.75 381.03 352.14 0.00 0.00 0.00
February 353.35 159.91 193.44 526.01 319.06 0.00 0.00 0.00
March 440.03 200.94 239.09 656.92 276.30 0.00 0.00 0.00
April 484.35 224.27 260.08 790.90 194.07 0.00 0.00 0.00
May 441.55 169.98 271.57 808.05 98.65 0.00 0.00 0.00
June 374.13 104.95 269.18 718.09 50.64 0.00 0.00 0.00
July 418.12 129.35 288.77 822.58 72.67 0.00 0.00 0.00
August 417.17 135.95 281.21 773.09 70.45 0.00 0.00 0.00
September 355.87 104.93 250.93 698.45 69.34 0.00 0.00 0.00
October 354.02 138.01 216.01 635.99 119.64 0.00 0.00 0.00
November 292.03 107.12 184.91 465.94 217.31 0.00 0.00 0.00
December 292.55 130.80 161.76 405.37 345.65 0.00 0.00 0.00
                 
Annual Sum or Average 375.65 143.97 231.68 640.83 181.57 0.00 0.00 0.00
Minimum of Months 282.58 104.93 160.75 381.03 50.64 0.00 0.00 0.00
Maximum of Months 484.35 224.27 288.77 822.58 352.14 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 282.58 121.82 160.75 381.03 352.14 0.00 0.00 0.00
February 353.35 159.91 193.44 526.01 319.06 0.00 0.00 0.00
March 440.03 200.94 239.09 656.92 276.30 0.00 0.00 0.00
April 484.35 224.27 260.08 790.90 194.07 0.00 0.00 0.00
May 441.55 169.98 271.57 808.05 98.65 0.00 0.00 0.00
June 374.13 104.95 269.18 718.09 50.64 0.00 0.00 0.00
July 418.12 129.35 288.77 822.58 72.67 0.00 0.00 0.00
August 417.17 135.95 281.21 773.09 70.45 0.00 0.00 0.00
September 355.87 104.93 250.93 698.45 69.34 0.00 0.00 0.00
October 354.02 138.01 216.01 635.99 119.64 0.00 0.00 0.00
November 292.03 107.12 184.91 465.94 217.31 0.00 0.00 0.00
December 292.55 130.80 161.76 405.37 345.65 0.00 0.00 0.00
                 
Annual Sum or Average 375.65 143.97 231.68 640.83 181.57 0.00 0.00 0.00
Minimum of Months 282.58 104.93 160.75 381.03 50.64 0.00 0.00 0.00
Maximum of Months 484.35 224.27 288.77 822.58 352.14 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 282.57 121.82 160.75 381.02 352.14 0.00 0.00 0.00
February 353.35 159.91 193.44 526.01 319.05 0.00 0.00 0.00
March 440.03 200.94 239.09 656.91 276.30 0.00 0.00 0.00
April 484.34 224.27 260.08 790.88 194.06 0.00 0.00 0.00
May 441.54 169.97 271.57 808.03 98.65 0.00 0.00 0.00
June 374.12 104.94 269.18 718.08 50.64 0.00 0.00 0.00
July 418.11 129.35 288.76 822.56 72.67 0.00 0.00 0.00
August 417.16 135.95 281.21 773.07 70.45 0.00 0.00 0.00
September 355.86 104.93 250.93 698.43 69.34 0.00 0.00 0.00
October 354.02 138.01 216.01 635.98 119.63 0.00 0.00 0.00
November 292.03 107.12 184.91 465.93 217.30 0.00 0.00 0.00
December 292.55 130.80 161.75 405.36 345.64 0.00 0.00 0.00
                 
Annual Sum or Average 375.64 143.97 231.68 640.82 181.57 0.00 0.00 0.00
Minimum of Months 282.57 104.93 160.75 381.02 50.64 0.00 0.00 0.00
Maximum of Months 484.34 224.27 288.76 822.56 352.14 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 587.87 0.00 587.87 639.84 1260.10 0.00 0.00 0.00
February 695.84 0.00 695.84 937.53 1054.24 0.00 0.00 0.00
March 829.84 0.00 829.84 1098.61 892.77 0.00 0.00 0.00
April 929.87 4.18 925.70 1512.59 592.70 0.00 0.00 0.00
May 1061.87 47.50 1014.37 2081.17 319.65 0.00 0.00 0.00
June 1134.30 81.67 1052.63 2396.32 148.70 0.00 0.00 0.00
July 1147.88 56.25 1091.63 2549.95 205.76 0.00 0.00 0.00
August 1015.89 9.34 1006.54 2150.60 135.19 0.00 0.00 0.00
September 901.21 0.07 901.14 1987.96 231.36 0.00 0.00 0.00
October 755.00 0.00 755.00 1465.97 359.79 0.00 0.00 0.00
November 656.47 0.00 656.47 1040.00 672.69 0.00 0.00 0.00
December 581.48 0.00 581.48 706.24 1077.92 0.00 0.00 0.00
                 
Annual Sum or Average 858.94 16.67 842.28 1550.19 577.17 0.00 0.00 0.00
Minimum of Months 581.48 0.00 581.48 639.84 135.19 0.00 0.00 0.00
Maximum of Months 1147.88 81.67 1091.63 2549.95 1260.10 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 943.66 452.07 491.59 1297.76 814.69 0.00 0.00 0.00
February 1089.62 504.38 585.23 1617.16 681.43 0.00 0.00 0.00
March 1330.34 628.93 701.41 1962.76 574.51 0.00 0.00 0.00
April 1443.75 644.20 799.56 2384.44 410.09 0.00 0.00 0.00
May 1365.85 543.91 821.93 2481.08 208.73 0.00 0.00 0.00
June 1348.11 517.80 830.31 2579.83 98.56 0.00 0.00 0.00
July 1385.20 499.53 885.67 2746.27 139.89 0.00 0.00 0.00
August 1266.64 423.54 843.11 2445.81 89.15 0.00 0.00 0.00
September 1221.13 441.44 779.69 2387.38 160.10 0.00 0.00 0.00
October 1124.00 484.06 639.94 2035.17 246.43 0.00 0.00 0.00
November 912.27 363.76 548.51 1479.81 432.40 0.00 0.00 0.00
December 736.92 260.17 476.75 1046.35 693.02 0.00 0.00 0.00
                 
Annual Sum or Average 1180.82 479.99 700.82 2040.26 377.73 0.00 0.00 0.00
Minimum of Months 736.92 260.17 476.75 1046.35 89.15 0.00 0.00 0.00
Maximum of Months 1443.75 644.20 885.67 2746.27 814.69 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 2762.96 1795.04 967.93 4146.37 1382.58 0.00 0.00 0.00
February 2499.51 1446.27 1053.23 3965.20 1168.28 0.00 0.00 0.00
March 1919.05 811.36 1107.69 3081.30 966.07 0.00 0.00 0.00
April 1304.92 228.83 1076.09 2322.76 648.64 0.00 0.00 0.00
May 1045.68 22.62 1023.06 2057.79 311.99 0.00 0.00 0.00
June 996.97 1.88 995.09 2127.18 145.99 0.00 0.00 0.00
July 1067.48 9.89 1057.59 2390.15 201.44 0.00 0.00 0.00
August 1211.56 102.24 1109.32 2566.86 144.33 0.00 0.00 0.00
September 1550.96 380.07 1170.89 3239.22 263.49 0.00 0.00 0.00
October 2132.87 1000.68 1132.20 3931.72 458.35 0.00 0.00 0.00
November 2426.74 1354.39 1072.35 4007.88 774.21 0.00 0.00 0.00
December 2662.72 1679.50 983.23 4094.51 1225.25 0.00 0.00 0.00
                 
Annual Sum or Average 1795.20 732.91 1062.29 3156.90 638.55 0.00 0.00 0.00
Minimum of Months 996.97 1.88 967.93 2057.79 144.33 0.00 0.00 0.00
Maximum of Months 2762.96 1795.04 1170.89 4146.37 1382.58 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 847.72 365.47 482.26 1196.97 895.15 0.00 0.00 0.00
February 1060.05 479.73 580.32 1640.56 788.16 0.00 0.00 0.00
March 1320.09 602.82 717.27 2024.27 692.23 0.00 0.00 0.00
April 1453.04 672.80 780.23 2427.21 499.73 0.00 0.00 0.00
May 1324.63 509.92 814.71 2433.83 270.81 0.00 0.00 0.00
June 1122.37 314.83 807.53 2191.36 127.10 0.00 0.00 0.00
July 1254.35 388.06 866.29 2519.62 177.37 0.00 0.00 0.00
August 1251.50 407.86 843.64 2400.44 134.44 0.00 0.00 0.00
September 1067.59 314.80 752.79 2116.92 183.97 0.00 0.00 0.00
October 1062.06 414.02 648.03 1939.20 305.66 0.00 0.00 0.00
November 876.09 321.35 554.73 1457.50 512.20 0.00 0.00 0.00
December 877.65 392.39 485.26 1299.97 791.80 0.00 0.00 0.00
                 
Annual Sum or Average 1126.94 431.90 695.04 1972.52 446.71 0.00 0.00 0.00
Minimum of Months 847.72 314.80 482.26 1196.97 127.10 0.00 0.00 0.00
Maximum of Months 1453.04 672.80 866.29 2519.62 895.15 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 587.87 0.00 587.87 663.20 1170.67 0.00 0.00 0.00
February 695.84 0.00 695.84 945.67 996.66 0.00 0.00 0.00
March 829.84 0.00 829.84 1090.17 860.88 0.00 0.00 0.00
April 929.87 4.18 925.70 1489.72 586.87 0.00 0.00 0.00
May 1061.87 47.50 1014.37 2045.63 331.08 0.00 0.00 0.00
June 1134.30 81.67 1052.63 2351.30 157.14 0.00 0.00 0.00
July 1147.88 56.25 1091.63 2503.66 219.85 0.00 0.00 0.00
August 1015.89 9.34 1006.54 2115.08 144.01 0.00 0.00 0.00
September 901.21 0.07 901.14 1946.84 235.92 0.00 0.00 0.00
October 755.00 0.00 755.00 1445.53 357.58 0.00 0.00 0.00
November 656.47 0.00 656.47 1041.27 630.33 0.00 0.00 0.00
December 581.48 0.00 581.48 721.69 1007.44 0.00 0.00 0.00
                 
Annual Sum or Average 858.94 16.67 842.28 1532.84 556.30 0.00 0.00 0.00
Minimum of Months 581.48 0.00 581.48 663.20 144.01 0.00 0.00 0.00
Maximum of Months 1147.88 81.67 1091.63 2503.66 1170.67 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 943.66 452.07 491.59 1312.31 767.41 0.00 0.00 0.00
February 1089.62 504.38 585.23 1619.20 650.49 0.00 0.00 0.00
March 1330.34 628.93 701.41 1951.14 559.27 0.00 0.00 0.00
April 1443.75 644.20 799.56 2363.34 407.39 0.00 0.00 0.00
May 1365.85 543.91 821.93 2452.29 216.01 0.00 0.00 0.00
June 1348.11 517.80 830.31 2547.19 103.32 0.00 0.00 0.00
July 1385.20 499.53 885.67 2714.07 147.91 0.00 0.00 0.00
August 1266.64 423.54 843.11 2418.34 93.94 0.00 0.00 0.00
September 1221.13 441.44 779.69 2358.03 162.66 0.00 0.00 0.00
October 1124.00 484.06 639.94 2017.30 245.53 0.00 0.00 0.00
November 912.27 363.76 548.51 1477.50 409.52 0.00 0.00 0.00
December 736.92 260.17 476.75 1054.48 654.21 0.00 0.00 0.00
                 
Annual Sum or Average 1180.82 479.99 700.82 2025.31 366.89 0.00 0.00 0.00
Minimum of Months 736.92 260.17 476.75 1054.48 93.94 0.00 0.00 0.00
Maximum of Months 1443.75 644.20 885.67 2714.07 767.41 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 2762.96 1795.04 967.93 4162.65 1303.82 0.00 0.00 0.00
February 2499.51 1446.27 1053.23 3965.27 1114.30 0.00 0.00 0.00
March 1919.05 811.36 1107.69 3065.10 935.04 0.00 0.00 0.00
April 1304.92 228.83 1076.09 2296.07 641.81 0.00 0.00 0.00
May 1045.68 22.62 1023.06 2020.69 322.68 0.00 0.00 0.00
June 996.97 1.88 995.09 2081.90 154.69 0.00 0.00 0.00
July 1067.48 9.89 1057.59 2343.04 216.19 0.00 0.00 0.00
August 1211.56 102.24 1109.32 2529.12 152.50 0.00 0.00 0.00
September 1550.96 380.07 1170.89 3198.79 268.19 0.00 0.00 0.00
October 2132.87 1000.68 1132.20 3907.69 454.54 0.00 0.00 0.00
November 2426.74 1354.39 1072.35 4002.58 737.51 0.00 0.00 0.00
December 2662.72 1679.50 983.23 4098.89 1160.59 0.00 0.00 0.00
                 
Annual Sum or Average 1795.20 732.91 1062.29 3135.21 619.65 0.00 0.00 0.00
Minimum of Months 996.97 1.88 967.93 2020.69 152.50 0.00 0.00 0.00
Maximum of Months 2762.96 1795.04 1170.89 4162.65 1303.82 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 847.72 365.47 482.26 1205.43 842.53 0.00 0.00 0.00
February 1060.05 479.73 580.32 1640.74 751.82 0.00 0.00 0.00
March 1320.09 602.82 717.27 2014.07 669.18 0.00 0.00 0.00
April 1453.04 672.80 780.23 2411.12 490.96 0.00 0.00 0.00
May 1324.63 509.92 814.71 2411.55 273.15 0.00 0.00 0.00
June 1122.37 314.83 807.53 2167.01 129.66 0.00 0.00 0.00
July 1254.35 388.06 866.29 2493.09 180.89 0.00 0.00 0.00
August 1251.50 407.86 843.64 2379.69 137.17 0.00 0.00 0.00
September 1067.59 314.80 752.79 2095.80 183.88 0.00 0.00 0.00
October 1062.06 414.02 648.03 1926.73 300.36 0.00 0.00 0.00
November 876.09 321.35 554.73 1456.19 485.44 0.00 0.00 0.00
December 877.65 392.39 485.26 1305.08 749.05 0.00 0.00 0.00
                 
Annual Sum or Average 1126.94 431.90 695.04 1960.68 431.43 0.00 0.00 0.00
Minimum of Months 847.72 314.80 482.26 1205.43 129.66 0.00 0.00 0.00
Maximum of Months 1453.04 672.80 866.29 2493.09 842.53 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.314915E+09 0.00 0.314915E+09 0.306906E+09 0.781471E+09
February 0.336680E+09 0.00 0.336680E+09 0.421919E+09 0.593118E+09
March 0.444534E+09 0.00 0.444534E+09 0.563986E+09 0.538129E+09
April 0.482052E+09 2165433.05 0.479887E+09 0.770400E+09 0.321687E+09
May 0.568829E+09 25445025.49 0.543384E+09 0.111411E+10 0.174509E+09
June 0.588030E+09 42339934.97 0.545690E+09 0.124168E+10 71537105.68
July 0.614902E+09 30131377.07 0.584770E+09 0.135725E+10 0.106731E+09
August 0.544197E+09 5005113.25 0.539191E+09 0.113256E+10 71992447.19
September 0.467195E+09 36959.50 0.467158E+09 0.102236E+10 0.122870E+09
October 0.404442E+09 0.00 0.404442E+09 0.774903E+09 0.202206E+09
November 0.340321E+09 0.00 0.340321E+09 0.519217E+09 0.394948E+09
December 0.311491E+09 0.00 0.311491E+09 0.341437E+09 0.681561E+09
           
Annual Sum or Average 0.541759E+10 0.105124E+09 0.531246E+10 0.956673E+10 0.406076E+10
Minimum of Months 0.311491E+09 0.00 0.311491E+09 0.306906E+09 71537105.68
Maximum of Months 0.614902E+09 42339934.97 0.584770E+09 0.135725E+10 0.781471E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.314915E+09 0.00 0.314915E+09 0.306906E+09 0.781471E+09
February 0.336679E+09 0.00 0.336679E+09 0.421919E+09 0.593118E+09
March 0.444533E+09 0.00 0.444533E+09 0.563985E+09 0.538128E+09
April 0.482052E+09 2165430.45 0.479887E+09 0.770400E+09 0.321687E+09
May 0.568828E+09 25444994.96 0.543383E+09 0.111411E+10 0.174508E+09
June 0.588030E+09 42339884.17 0.545690E+09 0.124168E+10 71537019.57
July 0.614901E+09 30131340.91 0.584770E+09 0.135725E+10 0.106731E+09
August 0.544196E+09 5005107.25 0.539191E+09 0.113255E+10 71992342.29
September 0.467195E+09 36959.46 0.467158E+09 0.102236E+10 0.122870E+09
October 0.404442E+09 0.00 0.404442E+09 0.774903E+09 0.202205E+09
November 0.340320E+09 0.00 0.340320E+09 0.519216E+09 0.394948E+09
December 0.311490E+09 0.00 0.311490E+09 0.341436E+09 0.681561E+09
           
Annual Sum or Average 0.541758E+10 0.105124E+09 0.531246E+10 0.956672E+10 0.406076E+10
Minimum of Months 0.311490E+09 0.00 0.311490E+09 0.306906E+09 71537019.57
Maximum of Months 0.614901E+09 42339884.17 0.584770E+09 0.135725E+10 0.781471E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.314915E+09 0.00 0.314915E+09 0.306906E+09 0.781471E+09
February 0.336680E+09 0.00 0.336680E+09 0.421919E+09 0.593118E+09
March 0.444534E+09 0.00 0.444534E+09 0.563986E+09 0.538129E+09
April 0.482052E+09 2165433.05 0.479887E+09 0.770400E+09 0.321687E+09
May 0.568829E+09 25445025.49 0.543384E+09 0.111411E+10 0.174509E+09
June 0.588030E+09 42339934.97 0.545690E+09 0.124168E+10 71537105.68
July 0.614902E+09 30131377.07 0.584770E+09 0.135725E+10 0.106731E+09
August 0.544197E+09 5005113.25 0.539191E+09 0.113256E+10 71992447.19
September 0.467195E+09 36959.50 0.467158E+09 0.102236E+10 0.122870E+09
October 0.404442E+09 0.00 0.404442E+09 0.774903E+09 0.202206E+09
November 0.340321E+09 0.00 0.340321E+09 0.519217E+09 0.394948E+09
December 0.311491E+09 0.00 0.311491E+09 0.341437E+09 0.681561E+09
           
Annual Sum or Average 0.541759E+10 0.105124E+09 0.531246E+10 0.956673E+10 0.406076E+10
Minimum of Months 0.311491E+09 0.00 0.311491E+09 0.306906E+09 71537105.68
Maximum of Months 0.614902E+09 42339934.97 0.584770E+09 0.135725E+10 0.781471E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.314915E+09 0.00 0.314915E+09 0.306906E+09 0.781471E+09
February 0.336679E+09 0.00 0.336679E+09 0.421919E+09 0.593118E+09
March 0.444533E+09 0.00 0.444533E+09 0.563985E+09 0.538128E+09
April 0.482052E+09 2165430.45 0.479887E+09 0.770400E+09 0.321687E+09
May 0.568828E+09 25444994.96 0.543383E+09 0.111411E+10 0.174508E+09
June 0.588030E+09 42339884.17 0.545690E+09 0.124168E+10 71537019.57
July 0.614901E+09 30131340.91 0.584770E+09 0.135725E+10 0.106731E+09
August 0.544196E+09 5005107.25 0.539191E+09 0.113255E+10 71992342.29
September 0.467195E+09 36959.46 0.467158E+09 0.102236E+10 0.122870E+09
October 0.404442E+09 0.00 0.404442E+09 0.774903E+09 0.202205E+09
November 0.340320E+09 0.00 0.340320E+09 0.519216E+09 0.394948E+09
December 0.311490E+09 0.00 0.311490E+09 0.341436E+09 0.681561E+09
           
Annual Sum or Average 0.541758E+10 0.105124E+09 0.531246E+10 0.956672E+10 0.406076E+10
Minimum of Months 0.311490E+09 0.00 0.311490E+09 0.306906E+09 71537019.57
Maximum of Months 0.614901E+09 42339884.17 0.584770E+09 0.135725E+10 0.781471E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.314903E+09 0.00 0.314903E+09 0.306894E+09 0.781440E+09
February 0.336666E+09 0.00 0.336666E+09 0.421902E+09 0.593094E+09
March 0.444516E+09 0.00 0.444516E+09 0.563963E+09 0.538107E+09
April 0.482033E+09 2165345.78 0.479868E+09 0.770369E+09 0.321674E+09
May 0.568806E+09 25443999.94 0.543362E+09 0.111407E+10 0.174502E+09
June 0.588006E+09 42338228.49 0.545668E+09 0.124163E+10 71534222.42
July 0.614877E+09 30130162.64 0.584747E+09 0.135719E+10 0.106727E+09
August 0.544175E+09 5004911.53 0.539170E+09 0.113251E+10 71989545.58
September 0.467177E+09 36958.01 0.467140E+09 0.102232E+10 0.122865E+09
October 0.404426E+09 0.00 0.404426E+09 0.774872E+09 0.202197E+09
November 0.340307E+09 0.00 0.340307E+09 0.519196E+09 0.394932E+09
December 0.311478E+09 0.00 0.311478E+09 0.341423E+09 0.681534E+09
           
Annual Sum or Average 0.541737E+10 0.105120E+09 0.531225E+10 0.956634E+10 0.406060E+10
Minimum of Months 0.311478E+09 0.00 0.311478E+09 0.306894E+09 71534222.42
Maximum of Months 0.614877E+09 42338228.49 0.584747E+09 0.135719E+10 0.781440E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.842508E+09 0.403614E+09 0.438895E+09 0.114341E+10 0.801433E+09
February 0.878675E+09 0.406740E+09 0.471934E+09 0.129844E+10 0.603038E+09
March 0.118774E+10 0.561511E+09 0.626226E+09 0.177183E+10 0.527716E+09
April 0.124741E+10 0.556591E+09 0.690824E+09 0.209307E+10 0.326915E+09
May 0.121944E+10 0.485610E+09 0.733831E+09 0.224140E+10 0.178322E+09
June 0.116478E+10 0.447385E+09 0.717397E+09 0.226115E+10 65600567.29
July 0.123672E+10 0.445986E+09 0.790732E+09 0.247845E+10 97934529.55
August 0.113087E+10 0.378140E+09 0.752732E+09 0.220883E+10 49883216.16
September 0.105506E+10 0.381410E+09 0.673655E+09 0.208248E+10 0.130308E+09
October 0.100352E+10 0.432175E+09 0.571340E+09 0.183629E+10 0.202805E+09
November 0.788211E+09 0.314290E+09 0.473921E+09 0.128558E+10 0.384437E+09
December 0.657926E+09 0.232280E+09 0.425647E+09 0.920464E+09 0.670579E+09
           
Annual Sum or Average 0.124129E+11 0.504573E+10 0.736713E+10 0.216214E+11 0.403897E+10
Minimum of Months 0.657926E+09 0.232280E+09 0.425647E+09 0.920464E+09 49883216.16
Maximum of Months 0.124741E+10 0.561511E+09 0.790732E+09 0.247845E+10 0.801433E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.842508E+09 0.403614E+09 0.438895E+09 0.114341E+10 0.801433E+09
February 0.878675E+09 0.406740E+09 0.471934E+09 0.129844E+10 0.603038E+09
March 0.118774E+10 0.561511E+09 0.626226E+09 0.177183E+10 0.527716E+09
April 0.124741E+10 0.556591E+09 0.690824E+09 0.209307E+10 0.326915E+09
May 0.121944E+10 0.485610E+09 0.733831E+09 0.224140E+10 0.178322E+09
June 0.116478E+10 0.447385E+09 0.717397E+09 0.226115E+10 65600567.29
July 0.123672E+10 0.445986E+09 0.790732E+09 0.247845E+10 97934529.55
August 0.113087E+10 0.378140E+09 0.752732E+09 0.220883E+10 49883216.16
September 0.105506E+10 0.381410E+09 0.673655E+09 0.208248E+10 0.130308E+09
October 0.100352E+10 0.432175E+09 0.571340E+09 0.183629E+10 0.202805E+09
November 0.788211E+09 0.314290E+09 0.473921E+09 0.128558E+10 0.384437E+09
December 0.657926E+09 0.232280E+09 0.425647E+09 0.920464E+09 0.670579E+09
           
Annual Sum or Average 0.124129E+11 0.504573E+10 0.736713E+10 0.216214E+11 0.403897E+10
Minimum of Months 0.657926E+09 0.232280E+09 0.425647E+09 0.920464E+09 49883216.16
Maximum of Months 0.124741E+10 0.561511E+09 0.790732E+09 0.247845E+10 0.801433E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.842493E+09 0.403606E+09 0.438887E+09 0.114338E+10 0.801418E+09
February 0.878658E+09 0.406733E+09 0.471926E+09 0.129842E+10 0.603027E+09
March 0.118772E+10 0.561501E+09 0.626214E+09 0.177179E+10 0.527706E+09
April 0.124739E+10 0.556581E+09 0.690811E+09 0.209303E+10 0.326909E+09
May 0.121942E+10 0.485601E+09 0.733818E+09 0.224136E+10 0.178319E+09
June 0.116476E+10 0.447377E+09 0.717384E+09 0.226111E+10 65599368.62
July 0.123670E+10 0.445978E+09 0.790718E+09 0.247840E+10 97932740.08
August 0.113085E+10 0.378133E+09 0.752719E+09 0.220879E+10 49882304.68
September 0.105505E+10 0.381403E+09 0.673642E+09 0.208244E+10 0.130305E+09
October 0.100350E+10 0.432167E+09 0.571330E+09 0.183626E+10 0.202802E+09
November 0.788197E+09 0.314285E+09 0.473912E+09 0.128556E+10 0.384430E+09
December 0.657914E+09 0.232276E+09 0.425639E+09 0.920448E+09 0.670567E+09
           
Annual Sum or Average 0.124126E+11 0.504564E+10 0.736700E+10 0.216210E+11 0.403890E+10
Minimum of Months 0.657914E+09 0.232276E+09 0.425639E+09 0.920448E+09 49882304.68
Maximum of Months 0.124739E+10 0.561501E+09 0.790718E+09 0.247840E+10 0.801418E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.148008E+10 0.961576E+09 0.518506E+09 0.224285E+10 0.763886E+09
February 0.120938E+10 0.699773E+09 0.509603E+09 0.193481E+10 0.591303E+09
March 0.102801E+10 0.434635E+09 0.593376E+09 0.166378E+10 0.537131E+09
April 0.676479E+09 0.118628E+09 0.557851E+09 0.120634E+10 0.340219E+09
May 0.560158E+09 12118894.79 0.548040E+09 0.110179E+10 0.172041E+09
June 0.516835E+09 975353.64 0.515859E+09 0.109669E+10 71875439.93
July 0.571836E+09 5300419.95 0.566536E+09 0.126949E+10 0.105846E+09
August 0.649016E+09 54767479.38 0.594248E+09 0.136240E+10 75018245.26
September 0.804025E+09 0.197028E+09 0.606997E+09 0.168882E+10 0.134499E+09
October 0.114255E+10 0.536050E+09 0.606502E+09 0.212732E+10 0.237320E+09
November 0.125804E+10 0.702124E+09 0.555914E+09 0.209844E+10 0.408638E+09
December 0.142639E+10 0.899683E+09 0.526702E+09 0.220991E+10 0.681890E+09
           
Annual Sum or Average 0.113228E+11 0.462266E+10 0.670013E+10 0.200026E+11 0.411967E+10
Minimum of Months 0.516835E+09 975353.64 0.509603E+09 0.109669E+10 71875439.93
Maximum of Months 0.148008E+10 0.961576E+09 0.606997E+09 0.224285E+10 0.763886E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.148008E+10 0.961575E+09 0.518506E+09 0.224284E+10 0.763886E+09
February 0.120937E+10 0.699772E+09 0.509603E+09 0.193480E+10 0.591303E+09
March 0.102801E+10 0.434634E+09 0.593375E+09 0.166378E+10 0.537131E+09
April 0.676479E+09 0.118628E+09 0.557850E+09 0.120633E+10 0.340219E+09
May 0.560158E+09 12118880.25 0.548039E+09 0.110179E+10 0.172041E+09
June 0.516834E+09 975352.47 0.515859E+09 0.109669E+10 71875354.45
July 0.571836E+09 5300413.59 0.566535E+09 0.126949E+10 0.105846E+09
August 0.649015E+09 54767413.66 0.594248E+09 0.136239E+10 75018144.76
September 0.804025E+09 0.197028E+09 0.606997E+09 0.168882E+10 0.134499E+09
October 0.114255E+10 0.536050E+09 0.606501E+09 0.212732E+10 0.237320E+09
November 0.125804E+10 0.702124E+09 0.555913E+09 0.209844E+10 0.408637E+09
December 0.142638E+10 0.899682E+09 0.526702E+09 0.220990E+10 0.681890E+09
           
Annual Sum or Average 0.113228E+11 0.462265E+10 0.670013E+10 0.200026E+11 0.411967E+10
Minimum of Months 0.516834E+09 975352.47 0.509603E+09 0.109669E+10 71875354.45
Maximum of Months 0.148008E+10 0.961575E+09 0.606997E+09 0.224284E+10 0.763886E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.148008E+10 0.961576E+09 0.518506E+09 0.224285E+10 0.763886E+09
February 0.120938E+10 0.699773E+09 0.509603E+09 0.193481E+10 0.591303E+09
March 0.102801E+10 0.434635E+09 0.593376E+09 0.166378E+10 0.537131E+09
April 0.676479E+09 0.118628E+09 0.557851E+09 0.120634E+10 0.340219E+09
May 0.560158E+09 12118894.79 0.548040E+09 0.110179E+10 0.172041E+09
June 0.516835E+09 975353.64 0.515859E+09 0.109669E+10 71875439.93
July 0.571836E+09 5300419.95 0.566536E+09 0.126949E+10 0.105846E+09
August 0.649016E+09 54767479.38 0.594248E+09 0.136240E+10 75018245.26
September 0.804025E+09 0.197028E+09 0.606997E+09 0.168882E+10 0.134499E+09
October 0.114255E+10 0.536050E+09 0.606502E+09 0.212732E+10 0.237320E+09
November 0.125804E+10 0.702124E+09 0.555914E+09 0.209844E+10 0.408638E+09
December 0.142639E+10 0.899683E+09 0.526702E+09 0.220991E+10 0.681890E+09
           
Annual Sum or Average 0.113228E+11 0.462266E+10 0.670013E+10 0.200026E+11 0.411967E+10
Minimum of Months 0.516835E+09 975353.64 0.509603E+09 0.109669E+10 71875439.93
Maximum of Months 0.148008E+10 0.961576E+09 0.606997E+09 0.224285E+10 0.763886E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.148008E+10 0.961575E+09 0.518506E+09 0.224284E+10 0.763886E+09
February 0.120937E+10 0.699772E+09 0.509603E+09 0.193480E+10 0.591303E+09
March 0.102801E+10 0.434634E+09 0.593375E+09 0.166378E+10 0.537131E+09
April 0.676479E+09 0.118628E+09 0.557850E+09 0.120633E+10 0.340219E+09
May 0.560158E+09 12118880.25 0.548039E+09 0.110179E+10 0.172041E+09
June 0.516834E+09 975352.47 0.515859E+09 0.109669E+10 71875354.45
July 0.571836E+09 5300413.59 0.566535E+09 0.126949E+10 0.105846E+09
August 0.649015E+09 54767413.66 0.594248E+09 0.136239E+10 75018144.76
September 0.804025E+09 0.197028E+09 0.606997E+09 0.168882E+10 0.134499E+09
October 0.114255E+10 0.536050E+09 0.606501E+09 0.212732E+10 0.237320E+09
November 0.125804E+10 0.702124E+09 0.555913E+09 0.209844E+10 0.408637E+09
December 0.142638E+10 0.899682E+09 0.526702E+09 0.220990E+10 0.681890E+09
           
Annual Sum or Average 0.113228E+11 0.462265E+10 0.670013E+10 0.200026E+11 0.411967E+10
Minimum of Months 0.516834E+09 975352.47 0.509603E+09 0.109669E+10 71875354.45
Maximum of Months 0.148008E+10 0.961575E+09 0.606997E+09 0.224284E+10 0.763886E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.148002E+10 0.961538E+09 0.518485E+09 0.224276E+10 0.763855E+09
February 0.120933E+10 0.699744E+09 0.509583E+09 0.193473E+10 0.591279E+09
March 0.102797E+10 0.434617E+09 0.593352E+09 0.166372E+10 0.537110E+09
April 0.676452E+09 0.118624E+09 0.557828E+09 0.120629E+10 0.340206E+09
May 0.560136E+09 12118406.35 0.548018E+09 0.110175E+10 0.172034E+09
June 0.516814E+09 975314.33 0.515838E+09 0.109664E+10 71872543.03
July 0.571813E+09 5300206.32 0.566513E+09 0.126943E+10 0.105842E+09
August 0.648989E+09 54765272.00 0.594224E+09 0.136234E+10 75015221.69
September 0.803993E+09 0.197020E+09 0.606973E+09 0.168875E+10 0.134493E+09
October 0.114251E+10 0.536029E+09 0.606477E+09 0.212723E+10 0.237311E+09
November 0.125799E+10 0.702096E+09 0.555891E+09 0.209835E+10 0.408621E+09
December 0.142633E+10 0.899647E+09 0.526681E+09 0.220982E+10 0.681862E+09
           
Annual Sum or Average 0.113223E+11 0.462247E+10 0.669986E+10 0.200018E+11 0.411950E+10
Minimum of Months 0.516814E+09 975314.33 0.509583E+09 0.109664E+10 71872543.03
Maximum of Months 0.148002E+10 0.961538E+09 0.606973E+09 0.224276E+10 0.763855E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.756854E+09 0.326291E+09 0.430563E+09 0.102055E+10 0.943184E+09
February 0.854836E+09 0.386862E+09 0.467974E+09 0.127253E+10 0.771858E+09
March 0.117859E+10 0.538206E+09 0.640384E+09 0.175950E+10 0.740054E+09
April 0.125544E+10 0.581308E+09 0.674128E+09 0.205000E+10 0.503017E+09
May 0.118264E+10 0.455262E+09 0.727381E+09 0.216428E+10 0.264227E+09
June 0.969736E+09 0.272020E+09 0.697717E+09 0.186130E+10 0.131261E+09
July 0.111989E+10 0.346460E+09 0.773433E+09 0.220319E+10 0.194644E+09
August 0.111735E+10 0.364142E+09 0.753205E+09 0.207064E+10 0.188687E+09
September 0.922410E+09 0.271989E+09 0.650420E+09 0.181038E+10 0.179720E+09
October 0.948215E+09 0.369644E+09 0.578571E+09 0.170345E+10 0.320434E+09
November 0.756947E+09 0.277652E+09 0.479294E+09 0.120771E+10 0.563255E+09
December 0.783578E+09 0.350332E+09 0.433246E+09 0.108573E+10 0.925781E+09
           
Annual Sum or Average 0.118465E+11 0.454017E+10 0.730632E+10 0.202093E+11 0.572612E+10
Minimum of Months 0.756854E+09 0.271989E+09 0.430563E+09 0.102055E+10 0.131261E+09
Maximum of Months 0.125544E+10 0.581308E+09 0.773433E+09 0.220319E+10 0.943184E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.756854E+09 0.326291E+09 0.430563E+09 0.102055E+10 0.943184E+09
February 0.854836E+09 0.386862E+09 0.467974E+09 0.127253E+10 0.771858E+09
March 0.117859E+10 0.538206E+09 0.640384E+09 0.175950E+10 0.740054E+09
April 0.125544E+10 0.581308E+09 0.674128E+09 0.205000E+10 0.503017E+09
May 0.118264E+10 0.455262E+09 0.727381E+09 0.216428E+10 0.264227E+09
June 0.969736E+09 0.272020E+09 0.697717E+09 0.186130E+10 0.131261E+09
July 0.111989E+10 0.346460E+09 0.773433E+09 0.220319E+10 0.194644E+09
August 0.111735E+10 0.364142E+09 0.753205E+09 0.207064E+10 0.188687E+09
September 0.922410E+09 0.271989E+09 0.650420E+09 0.181038E+10 0.179720E+09
October 0.948215E+09 0.369644E+09 0.578571E+09 0.170345E+10 0.320434E+09
November 0.756947E+09 0.277652E+09 0.479294E+09 0.120771E+10 0.563255E+09
December 0.783578E+09 0.350332E+09 0.433246E+09 0.108573E+10 0.925781E+09
           
Annual Sum or Average 0.118465E+11 0.454017E+10 0.730632E+10 0.202093E+11 0.572612E+10
Minimum of Months 0.756854E+09 0.271989E+09 0.430563E+09 0.102055E+10 0.131261E+09
Maximum of Months 0.125544E+10 0.581308E+09 0.773433E+09 0.220319E+10 0.943184E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.756840E+09 0.326285E+09 0.430555E+09 0.102053E+10 0.943167E+09
February 0.854820E+09 0.386855E+09 0.467965E+09 0.127251E+10 0.771844E+09
March 0.117857E+10 0.538196E+09 0.640372E+09 0.175947E+10 0.740041E+09
April 0.125541E+10 0.581297E+09 0.674116E+09 0.204996E+10 0.503008E+09
May 0.118262E+10 0.455254E+09 0.727367E+09 0.216424E+10 0.264222E+09
June 0.969719E+09 0.272015E+09 0.697704E+09 0.186127E+10 0.131258E+09
July 0.111987E+10 0.346454E+09 0.773419E+09 0.220315E+10 0.194641E+09
August 0.111733E+10 0.364135E+09 0.753192E+09 0.207060E+10 0.188684E+09
September 0.922393E+09 0.271985E+09 0.650408E+09 0.181034E+10 0.179717E+09
October 0.948198E+09 0.369637E+09 0.578561E+09 0.170342E+10 0.320428E+09
November 0.756933E+09 0.277647E+09 0.479285E+09 0.120768E+10 0.563244E+09
December 0.783563E+09 0.350325E+09 0.433238E+09 0.108571E+10 0.925764E+09
           
Annual Sum or Average 0.118463E+11 0.454008E+10 0.730618E+10 0.202089E+11 0.572602E+10
Minimum of Months 0.756840E+09 0.271985E+09 0.430555E+09 0.102053E+10 0.131258E+09
Maximum of Months 0.125541E+10 0.581297E+09 0.773419E+09 0.220315E+10 0.943167E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.157456E+10 0.00 0.157456E+10 0.171375E+10 0.337504E+10
February 0.168338E+10 0.00 0.168338E+10 0.226806E+10 0.255041E+10
March 0.222264E+10 0.00 0.222264E+10 0.294253E+10 0.239119E+10
April 0.241023E+10 10827034.34 0.239941E+10 0.392063E+10 0.153628E+10
May 0.284411E+10 0.127224E+09 0.271689E+10 0.557420E+10 0.856139E+09
June 0.294012E+10 0.211697E+09 0.272842E+10 0.621127E+10 0.385428E+09
July 0.307447E+10 0.150655E+09 0.292382E+10 0.682978E+10 0.551109E+09
August 0.272095E+10 25025263.67 0.269592E+10 0.576016E+10 0.362091E+09
September 0.233595E+10 184795.28 0.233576E+10 0.515278E+10 0.599685E+09
October 0.202218E+10 0.00 0.202218E+10 0.392644E+10 0.963650E+09
November 0.170158E+10 0.00 0.170158E+10 0.269569E+10 0.174362E+10
December 0.155743E+10 0.00 0.155743E+10 0.189159E+10 0.288711E+10
           
Annual Sum or Average 0.270876E+11 0.525613E+09 0.265620E+11 0.488869E+11 0.182018E+11
Minimum of Months 0.155743E+10 0.00 0.155743E+10 0.171375E+10 0.362091E+09
Maximum of Months 0.307447E+10 0.211697E+09 0.292382E+10 0.682978E+10 0.337504E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.252750E+10 0.121083E+10 0.131667E+10 0.347592E+10 0.218205E+10
February 0.263600E+10 0.122021E+10 0.141579E+10 0.391223E+10 0.164851E+10
March 0.356317E+10 0.168452E+10 0.187866E+10 0.525706E+10 0.153878E+10
April 0.374221E+10 0.166976E+10 0.207245E+10 0.618047E+10 0.106295E+10
May 0.365829E+10 0.145681E+10 0.220147E+10 0.664533E+10 0.559058E+09
June 0.349431E+10 0.134214E+10 0.215217E+10 0.668691E+10 0.255455E+09
July 0.371012E+10 0.133795E+10 0.237217E+10 0.735562E+10 0.374687E+09
August 0.339258E+10 0.113441E+10 0.225817E+10 0.655085E+10 0.238772E+09
September 0.316516E+10 0.114422E+10 0.202094E+10 0.618809E+10 0.414983E+09
October 0.301052E+10 0.129651E+10 0.171400E+10 0.545099E+10 0.660029E+09
November 0.236461E+10 0.942862E+09 0.142175E+10 0.383566E+10 0.112077E+10
December 0.197376E+10 0.696833E+09 0.127693E+10 0.280254E+10 0.185617E+10
           
Annual Sum or Average 0.372382E+11 0.151370E+11 0.221012E+11 0.643417E+11 0.119122E+11
Minimum of Months 0.197376E+10 0.696833E+09 0.127693E+10 0.280254E+10 0.238772E+09
Maximum of Months 0.374221E+10 0.168452E+10 0.237217E+10 0.735562E+10 0.218205E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.740032E+10 0.480782E+10 0.259250E+10 0.111056E+11 0.370309E+10
February 0.604681E+10 0.349882E+10 0.254799E+10 0.959262E+10 0.282631E+10
March 0.513999E+10 0.217315E+10 0.296684E+10 0.825295E+10 0.258753E+10
April 0.338236E+10 0.593135E+09 0.278922E+10 0.602060E+10 0.168127E+10
May 0.280076E+10 60593741.27 0.274016E+10 0.551160E+10 0.835622E+09
June 0.258414E+10 4876709.21 0.257927E+10 0.551365E+10 0.378408E+09
July 0.285915E+10 26501779.27 0.283264E+10 0.640179E+10 0.539539E+09
August 0.324504E+10 0.273834E+09 0.297120E+10 0.687509E+10 0.386579E+09
September 0.402008E+10 0.985129E+09 0.303495E+10 0.839606E+10 0.682975E+09
October 0.571269E+10 0.268022E+10 0.303247E+10 0.105307E+11 0.122765E+10
November 0.629012E+10 0.351058E+10 0.277954E+10 0.103884E+11 0.200676E+10
December 0.713184E+10 0.449836E+10 0.263348E+10 0.109667E+11 0.328171E+10
           
Annual Sum or Average 0.566133E+11 0.231130E+11 0.335003E+11 0.995559E+11 0.201374E+11
Minimum of Months 0.258414E+10 4876709.21 0.254799E+10 0.551160E+10 0.378408E+09
Maximum of Months 0.740032E+10 0.480782E+10 0.303495E+10 0.111056E+11 0.370309E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.227054E+10 0.978862E+09 0.129168E+10 0.320596E+10 0.239757E+10
February 0.256448E+10 0.116057E+10 0.140391E+10 0.396884E+10 0.190672E+10
March 0.353573E+10 0.161460E+10 0.192113E+10 0.542180E+10 0.185408E+10
April 0.376627E+10 0.174391E+10 0.202236E+10 0.629133E+10 0.129529E+10
May 0.354789E+10 0.136577E+10 0.218212E+10 0.651876E+10 0.725334E+09
June 0.290918E+10 0.816051E+09 0.209313E+10 0.568001E+10 0.329439E+09
July 0.335965E+10 0.103937E+10 0.232028E+10 0.674855E+10 0.475073E+09
August 0.335201E+10 0.109241E+10 0.225959E+10 0.642935E+10 0.360078E+09
September 0.276720E+10 0.815960E+09 0.195124E+10 0.548706E+10 0.476855E+09
October 0.284462E+10 0.110892E+10 0.173570E+10 0.519394E+10 0.818686E+09
November 0.227082E+10 0.832949E+09 0.143787E+10 0.377784E+10 0.132762E+10
December 0.235071E+10 0.105098E+10 0.129972E+10 0.348183E+10 0.212075E+10
           
Annual Sum or Average 0.355391E+11 0.136204E+11 0.219187E+11 0.622053E+11 0.140875E+11
Minimum of Months 0.227054E+10 0.815960E+09 0.129168E+10 0.320596E+10 0.329439E+09
Maximum of Months 0.376627E+10 0.174391E+10 0.232028E+10 0.674855E+10 0.239757E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.157456E+10 0.00 0.157456E+10 0.177632E+10 0.313552E+10
February 0.168338E+10 0.00 0.168338E+10 0.228777E+10 0.241113E+10
March 0.222264E+10 0.00 0.222264E+10 0.291990E+10 0.230579E+10
April 0.241023E+10 10827034.34 0.239941E+10 0.386135E+10 0.152115E+10
May 0.284411E+10 0.127224E+09 0.271689E+10 0.547901E+10 0.886756E+09
June 0.294012E+10 0.211697E+09 0.272842E+10 0.609458E+10 0.407307E+09
July 0.307447E+10 0.150655E+09 0.292382E+10 0.670581E+10 0.588859E+09
August 0.272095E+10 25025263.67 0.269592E+10 0.566503E+10 0.385718E+09
September 0.233595E+10 184795.28 0.233576E+10 0.504620E+10 0.611508E+09
October 0.202218E+10 0.00 0.202218E+10 0.387172E+10 0.957734E+09
November 0.170158E+10 0.00 0.170158E+10 0.269897E+10 0.163382E+10
December 0.155743E+10 0.00 0.155743E+10 0.193296E+10 0.269833E+10
           
Annual Sum or Average 0.270876E+11 0.525613E+09 0.265620E+11 0.483396E+11 0.175436E+11
Minimum of Months 0.155743E+10 0.00 0.155743E+10 0.177632E+10 0.385718E+09
Maximum of Months 0.307447E+10 0.211697E+09 0.292382E+10 0.670581E+10 0.313552E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.252750E+10 0.121083E+10 0.131667E+10 0.351489E+10 0.205543E+10
February 0.263600E+10 0.122021E+10 0.141579E+10 0.391716E+10 0.157366E+10
March 0.356317E+10 0.168452E+10 0.187866E+10 0.522593E+10 0.149796E+10
April 0.374221E+10 0.166976E+10 0.207245E+10 0.612577E+10 0.105597E+10
May 0.365829E+10 0.145681E+10 0.220147E+10 0.656821E+10 0.578567E+09
June 0.349431E+10 0.134214E+10 0.215217E+10 0.660232E+10 0.267818E+09
July 0.371012E+10 0.133795E+10 0.237217E+10 0.726936E+10 0.396159E+09
August 0.339258E+10 0.113441E+10 0.225817E+10 0.647728E+10 0.251597E+09
September 0.316516E+10 0.114422E+10 0.202094E+10 0.611200E+10 0.421624E+09
October 0.301052E+10 0.129651E+10 0.171400E+10 0.540312E+10 0.657640E+09
November 0.236461E+10 0.942862E+09 0.142175E+10 0.382968E+10 0.106148E+10
December 0.197376E+10 0.696833E+09 0.127693E+10 0.282433E+10 0.175223E+10
           
Annual Sum or Average 0.372382E+11 0.151370E+11 0.221012E+11 0.638700E+11 0.115701E+11
Minimum of Months 0.197376E+10 0.696833E+09 0.127693E+10 0.282433E+10 0.251597E+09
Maximum of Months 0.374221E+10 0.168452E+10 0.237217E+10 0.726936E+10 0.205543E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.740032E+10 0.480782E+10 0.259250E+10 0.111492E+11 0.349215E+10
February 0.604681E+10 0.349882E+10 0.254799E+10 0.959277E+10 0.269570E+10
March 0.513999E+10 0.217315E+10 0.296684E+10 0.820956E+10 0.250442E+10
April 0.338236E+10 0.593135E+09 0.278922E+10 0.595141E+10 0.166358E+10
May 0.280076E+10 60593741.27 0.274016E+10 0.541222E+10 0.864262E+09
June 0.258414E+10 4876709.21 0.257927E+10 0.539628E+10 0.400947E+09
July 0.285915E+10 26501779.27 0.283264E+10 0.627559E+10 0.579044E+09
August 0.324504E+10 0.273834E+09 0.297120E+10 0.677400E+10 0.408464E+09
September 0.402008E+10 0.985129E+09 0.303495E+10 0.829126E+10 0.695148E+09
October 0.571269E+10 0.268022E+10 0.303247E+10 0.104664E+11 0.121743E+10
November 0.629012E+10 0.351058E+10 0.277954E+10 0.103747E+11 0.191161E+10
December 0.713184E+10 0.449836E+10 0.263348E+10 0.109785E+11 0.310853E+10
           
Annual Sum or Average 0.566133E+11 0.231130E+11 0.335003E+11 0.988719E+11 0.195413E+11
Minimum of Months 0.258414E+10 4876709.21 0.254799E+10 0.539628E+10 0.400947E+09
Maximum of Months 0.740032E+10 0.480782E+10 0.303495E+10 0.111492E+11 0.349215E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.227054E+10 0.978862E+09 0.129168E+10 0.322863E+10 0.225664E+10
February 0.256448E+10 0.116057E+10 0.140391E+10 0.396928E+10 0.181880E+10
March 0.353573E+10 0.161460E+10 0.192113E+10 0.539449E+10 0.179233E+10
April 0.376627E+10 0.174391E+10 0.202236E+10 0.624963E+10 0.127257E+10
May 0.354789E+10 0.136577E+10 0.218212E+10 0.645911E+10 0.731598E+09
June 0.290918E+10 0.816051E+09 0.209313E+10 0.561688E+10 0.336078E+09
July 0.335965E+10 0.103937E+10 0.232028E+10 0.667748E+10 0.484503E+09
August 0.335201E+10 0.109241E+10 0.225959E+10 0.637376E+10 0.367383E+09
September 0.276720E+10 0.815960E+09 0.195124E+10 0.543231E+10 0.476606E+09
October 0.284462E+10 0.110892E+10 0.173570E+10 0.516054E+10 0.804489E+09
November 0.227082E+10 0.832949E+09 0.143787E+10 0.377445E+10 0.125826E+10
December 0.235071E+10 0.105098E+10 0.129972E+10 0.349553E+10 0.200625E+10
           
Annual Sum or Average 0.355391E+11 0.136204E+11 0.219187E+11 0.618321E+11 0.136055E+11
Minimum of Months 0.227054E+10 0.815960E+09 0.129168E+10 0.322863E+10 0.336078E+09
Maximum of Months 0.376627E+10 0.174391E+10 0.232028E+10 0.667748E+10 0.225664E+10



Table of Contents

Report: WindowZoneSummaryMonthly

For: BASEMENT

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: CORE_BOTTOM

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: CORE_MID

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: CORE_TOP

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 572.92 1458.83 587.87 0.00 587.87 0.00 0.00
February 872.01 1225.85 695.84 0.00 695.84 0.00 0.00
March 1052.83 1004.56 829.84 0.00 829.84 0.00 0.00
April 1486.10 620.53 929.88 4.18 925.70 0.00 0.00
May 2079.79 325.77 1061.87 47.50 1014.37 0.00 0.00
June 2395.20 137.99 1134.31 81.67 1052.63 0.00 0.00
July 2533.67 199.24 1147.88 56.25 1091.63 0.00 0.00
August 2114.22 134.39 1015.89 9.34 1006.55 0.00 0.00
September 1972.13 237.02 901.22 0.07 901.15 0.00 0.00
October 1446.57 377.47 755.00 0.00 755.00 0.00 0.00
November 1001.57 761.85 656.48 0.00 656.48 0.00 0.00
December 637.38 1272.32 581.48 0.00 581.48 0.00 0.00
               
Annual Sum or Average 1516.78 643.82 858.95 16.67 842.28 0.00 0.00
Minimum of Months 572.92 134.39 581.48 0.00 581.48 0.00 0.00
Maximum of Months 2533.67 1458.83 1147.88 81.67 1091.63 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 1280.69 897.66 943.66 452.07 491.59 0.00 0.00
February 1610.16 747.81 1089.62 504.39 585.23 0.00 0.00
March 1984.56 591.08 1330.34 628.93 701.41 0.00 0.00
April 2422.52 378.37 1443.76 644.20 799.56 0.00 0.00
May 2510.51 199.73 1365.85 543.91 821.94 0.00 0.00
June 2617.05 75.93 1348.12 517.80 830.32 0.00 0.00
July 2776.02 109.69 1385.20 499.53 885.67 0.00 0.00
August 2474.03 55.87 1266.65 423.54 843.11 0.00 0.00
September 2410.26 150.82 1221.13 441.44 779.69 0.00 0.00
October 2056.76 227.16 1124.00 484.06 639.94 0.00 0.00
November 1487.93 444.95 912.28 363.76 548.52 0.00 0.00
December 1030.98 751.09 736.92 260.17 476.75 0.00 0.00
               
Annual Sum or Average 2056.82 384.22 1180.82 479.99 700.83 0.00 0.00
Minimum of Months 1030.98 55.87 736.92 260.17 476.75 0.00 0.00
Maximum of Months 2776.02 897.66 1443.76 644.20 885.67 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 4186.88 1426.00 2762.97 1795.04 967.93 0.00 0.00
February 3998.82 1222.09 2499.52 1446.28 1053.24 0.00 0.00
March 3105.90 1002.70 1919.06 811.36 1107.70 0.00 0.00
April 2327.02 656.28 1304.93 228.83 1076.09 0.00 0.00
May 2056.79 321.16 1045.69 22.62 1023.06 0.00 0.00
June 2115.51 138.65 996.97 1.88 995.09 0.00 0.00
July 2369.84 197.59 1067.49 9.89 1057.59 0.00 0.00
August 2543.28 140.04 1211.56 102.24 1109.32 0.00 0.00
September 3257.73 259.45 1550.96 380.07 1170.90 0.00 0.00
October 3971.22 443.02 2132.88 1000.68 1132.20 0.00 0.00
November 4047.88 788.26 2426.75 1354.40 1072.36 0.00 0.00
December 4125.39 1272.93 2662.73 1679.50 983.23 0.00 0.00
               
Annual Sum or Average 3171.37 653.16 1795.20 732.91 1062.29 0.00 0.00
Minimum of Months 2056.79 138.65 996.97 1.88 967.93 0.00 0.00
Maximum of Months 4186.88 1426.00 2762.97 1795.04 1170.90 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 1143.08 1056.43 847.73 365.47 482.26 0.00 0.00
February 1578.03 957.16 1060.06 479.74 580.32 0.00 0.00
March 1970.76 828.91 1320.10 602.83 717.27 0.00 0.00
April 2372.67 582.19 1453.04 672.81 780.24 0.00 0.00
May 2424.13 295.95 1324.64 509.92 814.71 0.00 0.00
June 2154.27 151.92 1122.37 314.84 807.54 0.00 0.00
July 2467.72 218.01 1254.35 388.06 866.30 0.00 0.00
August 2319.25 211.34 1251.50 407.86 843.64 0.00 0.00
September 2095.33 208.01 1067.60 314.80 752.80 0.00 0.00
October 1907.97 358.91 1062.06 414.02 648.04 0.00 0.00
November 1397.80 651.91 876.09 321.36 554.74 0.00 0.00
December 1216.09 1036.93 877.66 392.39 485.26 0.00 0.00
               
Annual Sum or Average 1922.48 544.72 1126.94 431.90 695.04 0.00 0.00
Minimum of Months 1143.08 151.92 847.73 314.80 482.26 0.00 0.00
Maximum of Months 2467.72 1056.43 1453.04 672.81 866.30 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 639.84 1260.10 587.87 0.00 587.87 0.00 0.00
February 937.53 1054.24 695.84 0.00 695.84 0.00 0.00
March 1098.61 892.77 829.84 0.00 829.84 0.00 0.00
April 1512.59 592.70 929.87 4.18 925.70 0.00 0.00
May 2081.17 319.65 1061.87 47.50 1014.37 0.00 0.00
June 2396.32 148.70 1134.30 81.67 1052.63 0.00 0.00
July 2549.95 205.76 1147.88 56.25 1091.63 0.00 0.00
August 2150.60 135.19 1015.89 9.34 1006.54 0.00 0.00
September 1987.96 231.36 901.21 0.07 901.14 0.00 0.00
October 1465.97 359.79 755.00 0.00 755.00 0.00 0.00
November 1040.00 672.69 656.47 0.00 656.47 0.00 0.00
December 706.24 1077.92 581.48 0.00 581.48 0.00 0.00
               
Annual Sum or Average 1550.19 577.17 858.94 16.67 842.28 0.00 0.00
Minimum of Months 639.84 135.19 581.48 0.00 581.48 0.00 0.00
Maximum of Months 2549.95 1260.10 1147.88 81.67 1091.63 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 1297.76 814.69 943.66 452.07 491.59 0.00 0.00
February 1617.16 681.43 1089.62 504.38 585.23 0.00 0.00
March 1962.76 574.51 1330.34 628.93 701.41 0.00 0.00
April 2384.44 410.09 1443.75 644.20 799.56 0.00 0.00
May 2481.08 208.73 1365.85 543.91 821.93 0.00 0.00
June 2579.83 98.56 1348.11 517.80 830.31 0.00 0.00
July 2746.27 139.89 1385.20 499.53 885.67 0.00 0.00
August 2445.81 89.15 1266.64 423.54 843.11 0.00 0.00
September 2387.38 160.10 1221.13 441.44 779.69 0.00 0.00
October 2035.17 246.43 1124.00 484.06 639.94 0.00 0.00
November 1479.81 432.40 912.27 363.76 548.51 0.00 0.00
December 1046.35 693.02 736.92 260.17 476.75 0.00 0.00
               
Annual Sum or Average 2040.26 377.73 1180.82 479.99 700.82 0.00 0.00
Minimum of Months 1046.35 89.15 736.92 260.17 476.75 0.00 0.00
Maximum of Months 2746.27 814.69 1443.75 644.20 885.67 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 4146.37 1382.58 2762.96 1795.04 967.93 0.00 0.00
February 3965.20 1168.28 2499.51 1446.27 1053.23 0.00 0.00
March 3081.30 966.07 1919.05 811.36 1107.69 0.00 0.00
April 2322.76 648.64 1304.92 228.83 1076.09 0.00 0.00
May 2057.79 311.99 1045.68 22.62 1023.06 0.00 0.00
June 2127.18 145.99 996.97 1.88 995.09 0.00 0.00
July 2390.15 201.44 1067.48 9.89 1057.59 0.00 0.00
August 2566.86 144.33 1211.56 102.24 1109.32 0.00 0.00
September 3239.22 263.49 1550.96 380.07 1170.89 0.00 0.00
October 3931.72 458.35 2132.87 1000.68 1132.20 0.00 0.00
November 4007.88 774.21 2426.74 1354.39 1072.35 0.00 0.00
December 4094.51 1225.25 2662.72 1679.50 983.23 0.00 0.00
               
Annual Sum or Average 3156.90 638.55 1795.20 732.91 1062.29 0.00 0.00
Minimum of Months 2057.79 144.33 996.97 1.88 967.93 0.00 0.00
Maximum of Months 4146.37 1382.58 2762.96 1795.04 1170.89 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 1196.97 895.15 847.72 365.47 482.26 0.00 0.00
February 1640.56 788.16 1060.05 479.73 580.32 0.00 0.00
March 2024.27 692.23 1320.09 602.82 717.27 0.00 0.00
April 2427.21 499.73 1453.04 672.80 780.23 0.00 0.00
May 2433.83 270.81 1324.63 509.92 814.71 0.00 0.00
June 2191.36 127.10 1122.37 314.83 807.53 0.00 0.00
July 2519.62 177.37 1254.35 388.06 866.29 0.00 0.00
August 2400.44 134.44 1251.50 407.86 843.64 0.00 0.00
September 2116.92 183.97 1067.59 314.80 752.79 0.00 0.00
October 1939.20 305.66 1062.06 414.02 648.03 0.00 0.00
November 1457.50 512.20 876.09 321.35 554.73 0.00 0.00
December 1299.97 791.80 877.65 392.39 485.26 0.00 0.00
               
Annual Sum or Average 1972.52 446.71 1126.94 431.90 695.04 0.00 0.00
Minimum of Months 1196.97 127.10 847.72 314.80 482.26 0.00 0.00
Maximum of Months 2519.62 895.15 1453.04 672.80 866.29 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 663.20 1170.67 587.87 0.00 587.87 0.00 0.00
February 945.67 996.66 695.84 0.00 695.84 0.00 0.00
March 1090.17 860.88 829.84 0.00 829.84 0.00 0.00
April 1489.72 586.87 929.87 4.18 925.70 0.00 0.00
May 2045.63 331.08 1061.87 47.50 1014.37 0.00 0.00
June 2351.30 157.14 1134.30 81.67 1052.63 0.00 0.00
July 2503.66 219.85 1147.88 56.25 1091.63 0.00 0.00
August 2115.08 144.01 1015.89 9.34 1006.54 0.00 0.00
September 1946.84 235.92 901.21 0.07 901.14 0.00 0.00
October 1445.53 357.58 755.00 0.00 755.00 0.00 0.00
November 1041.27 630.33 656.47 0.00 656.47 0.00 0.00
December 721.69 1007.44 581.48 0.00 581.48 0.00 0.00
               
Annual Sum or Average 1532.84 556.30 858.94 16.67 842.28 0.00 0.00
Minimum of Months 663.20 144.01 581.48 0.00 581.48 0.00 0.00
Maximum of Months 2503.66 1170.67 1147.88 81.67 1091.63 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 1312.31 767.41 943.66 452.07 491.59 0.00 0.00
February 1619.20 650.49 1089.62 504.38 585.23 0.00 0.00
March 1951.14 559.27 1330.34 628.93 701.41 0.00 0.00
April 2363.34 407.39 1443.75 644.20 799.56 0.00 0.00
May 2452.29 216.01 1365.85 543.91 821.93 0.00 0.00
June 2547.19 103.32 1348.11 517.80 830.31 0.00 0.00
July 2714.07 147.91 1385.20 499.53 885.67 0.00 0.00
August 2418.34 93.94 1266.64 423.54 843.11 0.00 0.00
September 2358.03 162.66 1221.13 441.44 779.69 0.00 0.00
October 2017.30 245.53 1124.00 484.06 639.94 0.00 0.00
November 1477.50 409.52 912.27 363.76 548.51 0.00 0.00
December 1054.48 654.21 736.92 260.17 476.75 0.00 0.00
               
Annual Sum or Average 2025.31 366.89 1180.82 479.99 700.82 0.00 0.00
Minimum of Months 1054.48 93.94 736.92 260.17 476.75 0.00 0.00
Maximum of Months 2714.07 767.41 1443.75 644.20 885.67 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 4162.65 1303.82 2762.96 1795.04 967.93 0.00 0.00
February 3965.27 1114.30 2499.51 1446.27 1053.23 0.00 0.00
March 3065.10 935.04 1919.05 811.36 1107.69 0.00 0.00
April 2296.07 641.81 1304.92 228.83 1076.09 0.00 0.00
May 2020.69 322.68 1045.68 22.62 1023.06 0.00 0.00
June 2081.90 154.69 996.97 1.88 995.09 0.00 0.00
July 2343.04 216.19 1067.48 9.89 1057.59 0.00 0.00
August 2529.12 152.50 1211.56 102.24 1109.32 0.00 0.00
September 3198.79 268.19 1550.96 380.07 1170.89 0.00 0.00
October 3907.69 454.54 2132.87 1000.68 1132.20 0.00 0.00
November 4002.58 737.51 2426.74 1354.39 1072.35 0.00 0.00
December 4098.89 1160.59 2662.72 1679.50 983.23 0.00 0.00
               
Annual Sum or Average 3135.21 619.65 1795.20 732.91 1062.29 0.00 0.00
Minimum of Months 2020.69 152.50 996.97 1.88 967.93 0.00 0.00
Maximum of Months 4162.65 1303.82 2762.96 1795.04 1170.89 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 1205.43 842.53 847.72 365.47 482.26 0.00 0.00
February 1640.74 751.82 1060.05 479.73 580.32 0.00 0.00
March 2014.07 669.18 1320.09 602.82 717.27 0.00 0.00
April 2411.12 490.96 1453.04 672.80 780.23 0.00 0.00
May 2411.55 273.15 1324.63 509.92 814.71 0.00 0.00
June 2167.01 129.66 1122.37 314.83 807.53 0.00 0.00
July 2493.09 180.89 1254.35 388.06 866.29 0.00 0.00
August 2379.69 137.17 1251.50 407.86 843.64 0.00 0.00
September 2095.80 183.88 1067.59 314.80 752.79 0.00 0.00
October 1926.73 300.36 1062.06 414.02 648.03 0.00 0.00
November 1456.19 485.44 876.09 321.35 554.73 0.00 0.00
December 1305.08 749.05 877.65 392.39 485.26 0.00 0.00
               
Annual Sum or Average 1960.68 431.43 1126.94 431.90 695.04 0.00 0.00
Minimum of Months 1205.43 129.66 847.72 314.80 482.26 0.00 0.00
Maximum of Months 2493.09 842.53 1453.04 672.80 866.29 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: GROUNDFLOOR_PLENUM

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: MIDFLOOR_PLENUM

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: TOPFLOOR_PLENUM

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: DATACENTER_MID_ZN_6

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: BASEMENT

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: CORE_BOTTOM

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: CORE_MID

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: CORE_TOP

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.153452E+10 0.390732E+10 0.157456E+10 0.00 0.157456E+10 0.00 0.00
February 0.210958E+10 0.296556E+10 0.168338E+10 0.00 0.168338E+10 0.00 0.00
March 0.281990E+10 0.269062E+10 0.222265E+10 0.00 0.222265E+10 0.00 0.00
April 0.385197E+10 0.160842E+10 0.241024E+10 10827072.79 0.239941E+10 0.00 0.00
May 0.557052E+10 0.872536E+09 0.284412E+10 0.127224E+09 0.271690E+10 0.00 0.00
June 0.620836E+10 0.357682E+09 0.294013E+10 0.211698E+09 0.272843E+10 0.00 0.00
July 0.678619E+10 0.533651E+09 0.307448E+10 0.150656E+09 0.292383E+10 0.00 0.00
August 0.566273E+10 0.359959E+09 0.272096E+10 25025352.54 0.269593E+10 0.00 0.00
September 0.511177E+10 0.614346E+09 0.233596E+10 184795.93 0.233577E+10 0.00 0.00
October 0.387449E+10 0.101102E+10 0.202219E+10 0.00 0.202219E+10 0.00 0.00
November 0.259606E+10 0.197472E+10 0.170159E+10 0.00 0.170159E+10 0.00 0.00
December 0.170717E+10 0.340778E+10 0.155744E+10 0.00 0.155744E+10 0.00 0.00
               
Annual Sum or Average 0.478332E+11 0.203036E+11 0.270877E+11 0.525615E+09 0.265621E+11 0.00 0.00
Minimum of Months 0.153452E+10 0.357682E+09 0.155744E+10 0.00 0.155744E+10 0.00 0.00
Maximum of Months 0.678619E+10 0.390732E+10 0.307448E+10 0.211698E+09 0.292383E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.343020E+10 0.240428E+10 0.252751E+10 0.121083E+10 0.131668E+10 0.00 0.00
February 0.389530E+10 0.180910E+10 0.263601E+10 0.122021E+10 0.141579E+10 0.00 0.00
March 0.531545E+10 0.158314E+10 0.356319E+10 0.168452E+10 0.187867E+10 0.00 0.00
April 0.627917E+10 0.980740E+09 0.374222E+10 0.166976E+10 0.207246E+10 0.00 0.00
May 0.672416E+10 0.534964E+09 0.365830E+10 0.145682E+10 0.220148E+10 0.00 0.00
June 0.678340E+10 0.196801E+09 0.349432E+10 0.134215E+10 0.215218E+10 0.00 0.00
July 0.743530E+10 0.293802E+09 0.371013E+10 0.133795E+10 0.237218E+10 0.00 0.00
August 0.662644E+10 0.149649E+09 0.339260E+10 0.113441E+10 0.225818E+10 0.00 0.00
September 0.624739E+10 0.390921E+09 0.316518E+10 0.114422E+10 0.202095E+10 0.00 0.00
October 0.550884E+10 0.608412E+09 0.301053E+10 0.129652E+10 0.171401E+10 0.00 0.00
November 0.385671E+10 0.115330E+10 0.236462E+10 0.942866E+09 0.142175E+10 0.00 0.00
December 0.276138E+10 0.201173E+10 0.197377E+10 0.696836E+09 0.127693E+10 0.00 0.00
               
Annual Sum or Average 0.648637E+11 0.121168E+11 0.372384E+11 0.151371E+11 0.221013E+11 0.00 0.00
Minimum of Months 0.276138E+10 0.149649E+09 0.197377E+10 0.696836E+09 0.127693E+10 0.00 0.00
Maximum of Months 0.743530E+10 0.240428E+10 0.374222E+10 0.168452E+10 0.237218E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.112141E+11 0.381940E+10 0.740035E+10 0.480784E+10 0.259251E+10 0.00 0.00
February 0.967394E+10 0.295649E+10 0.604683E+10 0.349883E+10 0.254799E+10 0.00 0.00
March 0.831884E+10 0.268563E+10 0.514001E+10 0.217315E+10 0.296685E+10 0.00 0.00
April 0.603163E+10 0.170108E+10 0.338237E+10 0.593137E+09 0.278923E+10 0.00 0.00
May 0.550891E+10 0.860199E+09 0.280077E+10 60593956.44 0.274018E+10 0.00 0.00
June 0.548339E+10 0.359374E+09 0.258415E+10 4876726.53 0.257927E+10 0.00 0.00
July 0.634738E+10 0.529226E+09 0.285916E+10 26501873.38 0.283265E+10 0.00 0.00
August 0.681192E+10 0.375088E+09 0.324505E+10 0.273835E+09 0.297122E+10 0.00 0.00
September 0.844404E+10 0.672488E+09 0.402009E+10 0.985132E+09 0.303496E+10 0.00 0.00
October 0.106365E+11 0.118659E+10 0.571271E+10 0.268023E+10 0.303248E+10 0.00 0.00
November 0.104921E+11 0.204317E+10 0.629014E+10 0.351059E+10 0.277955E+10 0.00 0.00
December 0.110494E+11 0.340942E+10 0.713187E+10 0.449838E+10 0.263349E+10 0.00 0.00
               
Annual Sum or Average 0.100012E+12 0.205982E+11 0.566135E+11 0.231131E+11 0.335004E+11 0.00 0.00
Minimum of Months 0.548339E+10 0.359374E+09 0.258415E+10 4876726.53 0.254799E+10 0.00 0.00
Maximum of Months 0.112141E+11 0.381940E+10 0.740035E+10 0.480784E+10 0.303496E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.306162E+10 0.282954E+10 0.227055E+10 0.978866E+09 0.129168E+10 0.00 0.00
February 0.381758E+10 0.231556E+10 0.256449E+10 0.116058E+10 0.140391E+10 0.00 0.00
March 0.527848E+10 0.222015E+10 0.353575E+10 0.161461E+10 0.192114E+10 0.00 0.00
April 0.614996E+10 0.150904E+10 0.376629E+10 0.174391E+10 0.202237E+10 0.00 0.00
May 0.649279E+10 0.792676E+09 0.354791E+10 0.136578E+10 0.218213E+10 0.00 0.00
June 0.558387E+10 0.393780E+09 0.290919E+10 0.816055E+09 0.209314E+10 0.00 0.00
July 0.660954E+10 0.583929E+09 0.335966E+10 0.103937E+10 0.232029E+10 0.00 0.00
August 0.621187E+10 0.566059E+09 0.335202E+10 0.109242E+10 0.225960E+10 0.00 0.00
September 0.543109E+10 0.539157E+09 0.276721E+10 0.815963E+09 0.195125E+10 0.00 0.00
October 0.511031E+10 0.961297E+09 0.284463E+10 0.110892E+10 0.173570E+10 0.00 0.00
November 0.362310E+10 0.168975E+10 0.227083E+10 0.832952E+09 0.143787E+10 0.00 0.00
December 0.325718E+10 0.277733E+10 0.235072E+10 0.105099E+10 0.129973E+10 0.00 0.00
               
Annual Sum or Average 0.606274E+11 0.171783E+11 0.355392E+11 0.136204E+11 0.219188E+11 0.00 0.00
Minimum of Months 0.306162E+10 0.393780E+09 0.227055E+10 0.815963E+09 0.129168E+10 0.00 0.00
Maximum of Months 0.660954E+10 0.282954E+10 0.376629E+10 0.174391E+10 0.232029E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.171375E+10 0.337504E+10 0.157456E+10 0.00 0.157456E+10 0.00 0.00
February 0.226806E+10 0.255041E+10 0.168338E+10 0.00 0.168338E+10 0.00 0.00
March 0.294253E+10 0.239119E+10 0.222264E+10 0.00 0.222264E+10 0.00 0.00
April 0.392063E+10 0.153628E+10 0.241023E+10 10827034.34 0.239941E+10 0.00 0.00
May 0.557420E+10 0.856139E+09 0.284411E+10 0.127224E+09 0.271689E+10 0.00 0.00
June 0.621127E+10 0.385428E+09 0.294012E+10 0.211697E+09 0.272842E+10 0.00 0.00
July 0.682978E+10 0.551109E+09 0.307447E+10 0.150655E+09 0.292382E+10 0.00 0.00
August 0.576016E+10 0.362091E+09 0.272095E+10 25025263.67 0.269592E+10 0.00 0.00
September 0.515278E+10 0.599685E+09 0.233595E+10 184795.28 0.233576E+10 0.00 0.00
October 0.392644E+10 0.963650E+09 0.202218E+10 0.00 0.202218E+10 0.00 0.00
November 0.269569E+10 0.174362E+10 0.170158E+10 0.00 0.170158E+10 0.00 0.00
December 0.189159E+10 0.288711E+10 0.155743E+10 0.00 0.155743E+10 0.00 0.00
               
Annual Sum or Average 0.488869E+11 0.182018E+11 0.270876E+11 0.525613E+09 0.265620E+11 0.00 0.00
Minimum of Months 0.171375E+10 0.362091E+09 0.155743E+10 0.00 0.155743E+10 0.00 0.00
Maximum of Months 0.682978E+10 0.337504E+10 0.307447E+10 0.211697E+09 0.292382E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.347592E+10 0.218205E+10 0.252750E+10 0.121083E+10 0.131667E+10 0.00 0.00
February 0.391223E+10 0.164851E+10 0.263600E+10 0.122021E+10 0.141579E+10 0.00 0.00
March 0.525706E+10 0.153878E+10 0.356317E+10 0.168452E+10 0.187866E+10 0.00 0.00
April 0.618047E+10 0.106295E+10 0.374221E+10 0.166976E+10 0.207245E+10 0.00 0.00
May 0.664533E+10 0.559058E+09 0.365829E+10 0.145681E+10 0.220147E+10 0.00 0.00
June 0.668691E+10 0.255455E+09 0.349431E+10 0.134214E+10 0.215217E+10 0.00 0.00
July 0.735562E+10 0.374687E+09 0.371012E+10 0.133795E+10 0.237217E+10 0.00 0.00
August 0.655085E+10 0.238772E+09 0.339258E+10 0.113441E+10 0.225817E+10 0.00 0.00
September 0.618809E+10 0.414983E+09 0.316516E+10 0.114422E+10 0.202094E+10 0.00 0.00
October 0.545099E+10 0.660029E+09 0.301052E+10 0.129651E+10 0.171400E+10 0.00 0.00
November 0.383566E+10 0.112077E+10 0.236461E+10 0.942862E+09 0.142175E+10 0.00 0.00
December 0.280254E+10 0.185617E+10 0.197376E+10 0.696833E+09 0.127693E+10 0.00 0.00
               
Annual Sum or Average 0.643417E+11 0.119122E+11 0.372382E+11 0.151370E+11 0.221012E+11 0.00 0.00
Minimum of Months 0.280254E+10 0.238772E+09 0.197376E+10 0.696833E+09 0.127693E+10 0.00 0.00
Maximum of Months 0.735562E+10 0.218205E+10 0.374221E+10 0.168452E+10 0.237217E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.111056E+11 0.370309E+10 0.740032E+10 0.480782E+10 0.259250E+10 0.00 0.00
February 0.959262E+10 0.282631E+10 0.604681E+10 0.349882E+10 0.254799E+10 0.00 0.00
March 0.825295E+10 0.258753E+10 0.513999E+10 0.217315E+10 0.296684E+10 0.00 0.00
April 0.602060E+10 0.168127E+10 0.338236E+10 0.593135E+09 0.278922E+10 0.00 0.00
May 0.551160E+10 0.835622E+09 0.280076E+10 60593741.27 0.274016E+10 0.00 0.00
June 0.551365E+10 0.378408E+09 0.258414E+10 4876709.21 0.257927E+10 0.00 0.00
July 0.640179E+10 0.539539E+09 0.285915E+10 26501779.27 0.283264E+10 0.00 0.00
August 0.687509E+10 0.386579E+09 0.324504E+10 0.273834E+09 0.297120E+10 0.00 0.00
September 0.839606E+10 0.682975E+09 0.402008E+10 0.985129E+09 0.303495E+10 0.00 0.00
October 0.105307E+11 0.122765E+10 0.571269E+10 0.268022E+10 0.303247E+10 0.00 0.00
November 0.103884E+11 0.200676E+10 0.629012E+10 0.351058E+10 0.277954E+10 0.00 0.00
December 0.109667E+11 0.328171E+10 0.713184E+10 0.449836E+10 0.263348E+10 0.00 0.00
               
Annual Sum or Average 0.995559E+11 0.201374E+11 0.566133E+11 0.231130E+11 0.335003E+11 0.00 0.00
Minimum of Months 0.551160E+10 0.378408E+09 0.258414E+10 4876709.21 0.254799E+10 0.00 0.00
Maximum of Months 0.111056E+11 0.370309E+10 0.740032E+10 0.480782E+10 0.303495E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.320596E+10 0.239757E+10 0.227054E+10 0.978862E+09 0.129168E+10 0.00 0.00
February 0.396884E+10 0.190672E+10 0.256448E+10 0.116057E+10 0.140391E+10 0.00 0.00
March 0.542180E+10 0.185408E+10 0.353573E+10 0.161460E+10 0.192113E+10 0.00 0.00
April 0.629133E+10 0.129529E+10 0.376627E+10 0.174391E+10 0.202236E+10 0.00 0.00
May 0.651876E+10 0.725334E+09 0.354789E+10 0.136577E+10 0.218212E+10 0.00 0.00
June 0.568001E+10 0.329439E+09 0.290918E+10 0.816051E+09 0.209313E+10 0.00 0.00
July 0.674855E+10 0.475073E+09 0.335965E+10 0.103937E+10 0.232028E+10 0.00 0.00
August 0.642935E+10 0.360078E+09 0.335201E+10 0.109241E+10 0.225959E+10 0.00 0.00
September 0.548706E+10 0.476855E+09 0.276720E+10 0.815960E+09 0.195124E+10 0.00 0.00
October 0.519394E+10 0.818686E+09 0.284462E+10 0.110892E+10 0.173570E+10 0.00 0.00
November 0.377784E+10 0.132762E+10 0.227082E+10 0.832949E+09 0.143787E+10 0.00 0.00
December 0.348183E+10 0.212075E+10 0.235071E+10 0.105098E+10 0.129972E+10 0.00 0.00
               
Annual Sum or Average 0.622053E+11 0.140875E+11 0.355391E+11 0.136204E+11 0.219187E+11 0.00 0.00
Minimum of Months 0.320596E+10 0.329439E+09 0.227054E+10 0.815960E+09 0.129168E+10 0.00 0.00
Maximum of Months 0.674855E+10 0.239757E+10 0.376627E+10 0.174391E+10 0.232028E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.177632E+10 0.313552E+10 0.157456E+10 0.00 0.157456E+10 0.00 0.00
February 0.228777E+10 0.241113E+10 0.168338E+10 0.00 0.168338E+10 0.00 0.00
March 0.291990E+10 0.230579E+10 0.222264E+10 0.00 0.222264E+10 0.00 0.00
April 0.386135E+10 0.152115E+10 0.241023E+10 10827034.34 0.239941E+10 0.00 0.00
May 0.547901E+10 0.886756E+09 0.284411E+10 0.127224E+09 0.271689E+10 0.00 0.00
June 0.609458E+10 0.407307E+09 0.294012E+10 0.211697E+09 0.272842E+10 0.00 0.00
July 0.670581E+10 0.588859E+09 0.307447E+10 0.150655E+09 0.292382E+10 0.00 0.00
August 0.566503E+10 0.385718E+09 0.272095E+10 25025263.67 0.269592E+10 0.00 0.00
September 0.504620E+10 0.611508E+09 0.233595E+10 184795.28 0.233576E+10 0.00 0.00
October 0.387172E+10 0.957734E+09 0.202218E+10 0.00 0.202218E+10 0.00 0.00
November 0.269897E+10 0.163382E+10 0.170158E+10 0.00 0.170158E+10 0.00 0.00
December 0.193296E+10 0.269833E+10 0.155743E+10 0.00 0.155743E+10 0.00 0.00
               
Annual Sum or Average 0.483396E+11 0.175436E+11 0.270876E+11 0.525613E+09 0.265620E+11 0.00 0.00
Minimum of Months 0.177632E+10 0.385718E+09 0.155743E+10 0.00 0.155743E+10 0.00 0.00
Maximum of Months 0.670581E+10 0.313552E+10 0.307447E+10 0.211697E+09 0.292382E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.351489E+10 0.205543E+10 0.252750E+10 0.121083E+10 0.131667E+10 0.00 0.00
February 0.391716E+10 0.157366E+10 0.263600E+10 0.122021E+10 0.141579E+10 0.00 0.00
March 0.522593E+10 0.149796E+10 0.356317E+10 0.168452E+10 0.187866E+10 0.00 0.00
April 0.612577E+10 0.105597E+10 0.374221E+10 0.166976E+10 0.207245E+10 0.00 0.00
May 0.656821E+10 0.578567E+09 0.365829E+10 0.145681E+10 0.220147E+10 0.00 0.00
June 0.660232E+10 0.267818E+09 0.349431E+10 0.134214E+10 0.215217E+10 0.00 0.00
July 0.726936E+10 0.396159E+09 0.371012E+10 0.133795E+10 0.237217E+10 0.00 0.00
August 0.647728E+10 0.251597E+09 0.339258E+10 0.113441E+10 0.225817E+10 0.00 0.00
September 0.611200E+10 0.421624E+09 0.316516E+10 0.114422E+10 0.202094E+10 0.00 0.00
October 0.540312E+10 0.657640E+09 0.301052E+10 0.129651E+10 0.171400E+10 0.00 0.00
November 0.382968E+10 0.106148E+10 0.236461E+10 0.942862E+09 0.142175E+10 0.00 0.00
December 0.282433E+10 0.175223E+10 0.197376E+10 0.696833E+09 0.127693E+10 0.00 0.00
               
Annual Sum or Average 0.638700E+11 0.115701E+11 0.372382E+11 0.151370E+11 0.221012E+11 0.00 0.00
Minimum of Months 0.282433E+10 0.251597E+09 0.197376E+10 0.696833E+09 0.127693E+10 0.00 0.00
Maximum of Months 0.726936E+10 0.205543E+10 0.374221E+10 0.168452E+10 0.237217E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.111492E+11 0.349215E+10 0.740032E+10 0.480782E+10 0.259250E+10 0.00 0.00
February 0.959277E+10 0.269570E+10 0.604681E+10 0.349882E+10 0.254799E+10 0.00 0.00
March 0.820956E+10 0.250442E+10 0.513999E+10 0.217315E+10 0.296684E+10 0.00 0.00
April 0.595141E+10 0.166358E+10 0.338236E+10 0.593135E+09 0.278922E+10 0.00 0.00
May 0.541222E+10 0.864262E+09 0.280076E+10 60593741.27 0.274016E+10 0.00 0.00
June 0.539628E+10 0.400947E+09 0.258414E+10 4876709.21 0.257927E+10 0.00 0.00
July 0.627559E+10 0.579044E+09 0.285915E+10 26501779.27 0.283264E+10 0.00 0.00
August 0.677400E+10 0.408464E+09 0.324504E+10 0.273834E+09 0.297120E+10 0.00 0.00
September 0.829126E+10 0.695148E+09 0.402008E+10 0.985129E+09 0.303495E+10 0.00 0.00
October 0.104664E+11 0.121743E+10 0.571269E+10 0.268022E+10 0.303247E+10 0.00 0.00
November 0.103747E+11 0.191161E+10 0.629012E+10 0.351058E+10 0.277954E+10 0.00 0.00
December 0.109785E+11 0.310853E+10 0.713184E+10 0.449836E+10 0.263348E+10 0.00 0.00
               
Annual Sum or Average 0.988719E+11 0.195413E+11 0.566133E+11 0.231130E+11 0.335003E+11 0.00 0.00
Minimum of Months 0.539628E+10 0.400947E+09 0.258414E+10 4876709.21 0.254799E+10 0.00 0.00
Maximum of Months 0.111492E+11 0.349215E+10 0.740032E+10 0.480782E+10 0.303495E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.322863E+10 0.225664E+10 0.227054E+10 0.978862E+09 0.129168E+10 0.00 0.00
February 0.396928E+10 0.181880E+10 0.256448E+10 0.116057E+10 0.140391E+10 0.00 0.00
March 0.539449E+10 0.179233E+10 0.353573E+10 0.161460E+10 0.192113E+10 0.00 0.00
April 0.624963E+10 0.127257E+10 0.376627E+10 0.174391E+10 0.202236E+10 0.00 0.00
May 0.645911E+10 0.731598E+09 0.354789E+10 0.136577E+10 0.218212E+10 0.00 0.00
June 0.561688E+10 0.336078E+09 0.290918E+10 0.816051E+09 0.209313E+10 0.00 0.00
July 0.667748E+10 0.484503E+09 0.335965E+10 0.103937E+10 0.232028E+10 0.00 0.00
August 0.637376E+10 0.367383E+09 0.335201E+10 0.109241E+10 0.225959E+10 0.00 0.00
September 0.543231E+10 0.476606E+09 0.276720E+10 0.815960E+09 0.195124E+10 0.00 0.00
October 0.516054E+10 0.804489E+09 0.284462E+10 0.110892E+10 0.173570E+10 0.00 0.00
November 0.377445E+10 0.125826E+10 0.227082E+10 0.832949E+09 0.143787E+10 0.00 0.00
December 0.349553E+10 0.200625E+10 0.235071E+10 0.105098E+10 0.129972E+10 0.00 0.00
               
Annual Sum or Average 0.618321E+11 0.136055E+11 0.355391E+11 0.136204E+11 0.219187E+11 0.00 0.00
Minimum of Months 0.322863E+10 0.336078E+09 0.227054E+10 0.815960E+09 0.129168E+10 0.00 0.00
Maximum of Months 0.667748E+10 0.225664E+10 0.376627E+10 0.174391E+10 0.232028E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: GROUNDFLOOR_PLENUM

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: MIDFLOOR_PLENUM

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: TOPFLOOR_PLENUM

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: DATACENTER_MID_ZN_6

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AverageOutdoorConditionsMonthly

For: Environment

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] SITE OUTDOOR AIR WETBULB TEMPERATURE [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] SITE WIND SPEED [m/s] SITE SKY TEMPERATURE [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] SITE RAIN STATUS []
January 19.42 15.96 13.59 3.30 9.49 57.21 169.93 0.03
February 20.87 16.70 13.89 5.53 11.19 68.99 182.59 0.00
March 21.57 17.63 15.09 5.59 12.13 85.97 199.13 0.00
April 24.11 19.68 17.40 4.69 15.31 97.05 212.67 0.01
May 26.41 22.40 20.67 5.05 18.50 110.67 177.92 0.00
June 27.68 24.06 22.67 3.87 20.33 120.35 147.07 0.00
July 28.13 24.25 22.77 2.86 20.30 124.71 163.26 0.00
August 27.97 24.38 23.03 3.45 20.36 120.27 145.14 0.08
September 27.49 23.91 22.56 3.39 20.13 107.67 134.94 0.00
October 26.35 22.68 21.10 3.72 17.49 81.44 160.40 0.04
November 23.59 20.24 18.46 4.39 14.74 70.67 140.11 0.00
December 20.30 17.47 15.75 3.70 12.21 59.50 147.31 0.00
                 
Annual Sum or Average 24.51 20.80 18.94 4.12 16.04 92.16 164.97 0.01
Minimum of Months 19.42 15.96 13.59 2.86 9.49 57.21 134.94 0.00
Maximum of Months 28.13 24.38 23.03 5.59 20.36 124.71 212.67 0.08



Table of Contents

Report: OutdoorConditionsMaximumDryBulbMonthly

For: Environment

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] SITE WIND SPEED {AT MAX/MIN} [m/s] SITE SKY TEMPERATURE {AT MAX/MIN} [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2]
January 28.90 02-JAN-14:20 24.35 22.57 2.37 19.46 142.33 666.50
February 29.40 11-FEB-13:00 24.15 22.20 4.60 20.75 178.50 682.00
March 29.40 13-MAR-15:00 22.41 19.40 6.20 21.27 178.00 499.00
April 32.20 17-APR-14:00 19.76 12.80 5.20 21.27 367.00 219.50
May 34.40 22-MAY-12:00 23.24 18.30 5.70 25.99 382.50 457.50
June 32.20 11-JUN-12:00 23.83 20.60 3.60 23.15 181.50 762.50
July 35.60 29-JUL-15:00 24.39 20.00 3.60 25.66 281.50 374.50
August 33.90 23-AUG-12:00 25.44 22.20 5.70 24.50 261.50 640.00
September 32.20 08-SEP-14:00 23.42 20.00 2.10 21.61 221.50 576.00
October 32.20 09-OCT-10:00 23.83 20.60 3.10 25.16 286.50 457.50
November 30.00 17-NOV-14:00 22.20 18.90 4.10 19.35 178.50 412.50
December 28.90 10-DEC-14:20 22.91 20.40 7.87 19.82 162.67 585.17
                 
Annual Sum or Average                
Minimum of Months 28.90   19.76 12.80 2.10 19.35 142.33 219.50
Maximum of Months 35.60   25.44 22.57 7.87 25.99 382.50 762.50



Table of Contents

Report: OutdoorConditionsMinimumDryBulbMonthly

For: Environment

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] SITE WIND SPEED {AT MAX/MIN} [m/s] SITE SKY TEMPERATURE {AT MAX/MIN} [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2]
January 9.40 25-JAN-04:00 4.59 -1.7 3.10 -7.3 0.00 0.00
February 5.00 04-FEB-06:00 1.99 -2.8 5.70 -11.9 0.00 0.00
March 6.70 16-MAR-04:00 4.49 1.70 4.60 -9.2 0.00 0.00
April 14.40 02-APR-05:49 13.38 12.70 1.60 0.69 0.00 0.00
May 20.60 01-MAY-04:00 19.45 18.90 1.00 7.95 0.00 0.00
June 22.80 05-JUN-14:00 20.57 19.40 2.10 18.46 245.00 55.00
July 22.80 02-JUL-15:00 21.59 21.10 4.60 20.92 155.00 8.50
August 22.20 12-AUG-06:00 21.85 21.70 2.60 20.40 65.50 0.00
September 22.20 05-SEP-05:00 21.37 21.10 2.60 13.54 0.00 0.00
October 21.10 28-OCT-02:00 20.29 20.00 2.60 8.54 0.00 0.00
November 10.00 27-NOV-02:00 8.82 7.80 3.10 -4.6 0.00 0.00
December 7.80 15-DEC-05:40 5.61 3.13 6.37 -7.8 0.00 0.00
                 
Annual Sum or Average                
Minimum of Months 5.00   1.99 -2.8 1.00 -11.9 0.00 0.00
Maximum of Months 22.80   21.85 21.70 6.37 20.92 245.00 55.00



Table of Contents

Report: OutdoorConditionsMaximumWetBulbMonthly

For: Environment

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

SITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] SITE WIND SPEED {AT MAX/MIN} [m/s] SITE SKY TEMPERATURE {AT MAX/MIN} [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2]
January 24.83 02-JAN-13:00 28.90 23.30 1.50 19.87 151.00 613.50
February 24.15 11-FEB-13:00 29.40 22.20 4.60 20.75 178.50 682.00
March 23.83 14-MAR-09:00 26.70 22.80 11.30 19.52 243.50 478.00
April 24.58 01-APR-15:00 28.30 23.30 3.60 16.30 93.50 759.50
May 26.05 28-MAY-14:00 28.90 25.00 5.20 25.66 289.00 98.50
June 26.06 28-JUN-11:00 28.90 25.00 1.50 22.98 404.50 373.50
July 26.39 12-JUL-10:00 30.60 25.00 4.60 23.82 287.50 574.00
August 26.46 21-AUG-15:00 32.20 24.40 3.60 24.50 205.50 366.00
September 26.31 22-SEP-16:00 30.00 25.00 6.20 28.91 54.00 21.00
October 26.52 01-OCT-11:00 29.40 25.60 6.20 28.43 283.50 0.00
November 25.31 04-NOV-13:00 27.80 24.40 2.10 26.48 199.00 3.00
December 24.31 24-DEC-14:00 27.20 23.30 2.10 23.66 201.50 114.50
                 
Annual Sum or Average                
Minimum of Months 23.83   26.70 22.20 1.50 16.30 54.00 0.00
Maximum of Months 26.52   32.20 25.60 11.30 28.91 404.50 759.50



Table of Contents

Report: OutdoorConditionsMaximumDewPointMonthly

For: Environment

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

SITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] SITE WIND SPEED {AT MAX/MIN} [m/s] SITE SKY TEMPERATURE {AT MAX/MIN} [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2]
January 23.30 02-JAN-13:00 28.90 24.83 1.50 19.87 151.00 613.50
February 22.80 11-FEB-16:19 27.60 24.09 5.70 18.94 101.33 565.33
March 22.80 14-MAR-09:20 25.57 23.60 9.63 22.18 176.17 527.17
April 23.30 01-APR-14:00 27.80 24.57 5.70 15.76 108.00 831.00
May 25.00 28-MAY-12:00 27.80 25.74 6.70 22.98 249.50 244.50
June 25.00 06-JUN-18:00 27.20 25.59 3.60 23.99 17.50 0.00
July 25.00 12-JUL-03:00 27.20 25.59 1.50 19.70 0.00 0.00
August 25.60 21-AUG-11:00 28.90 26.35 2.60 23.15 567.00 173.50
September 25.00 22-SEP-00:00 27.80 25.31 3.60 20.92 0.00 0.00
October 25.60 01-OCT-11:00 29.40 26.52 6.20 28.43 283.50 0.00
November 24.40 05-NOV-01:19 26.10 24.93 2.03 16.37 0.00 0.00
December 23.90 24-DEC-08:00 23.90 23.90 2.60 17.75 168.50 167.00
                 
Annual Sum or Average                
Minimum of Months 22.80   23.90 23.60 1.50 15.76 0.00 0.00
Maximum of Months 25.60   29.40 26.52 9.63 28.43 567.00 831.00



Table of Contents

Report: OutdoorGroundConditionsMonthly

For: Environment

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

SITE GROUND TEMPERATURE [C] SITE SURFACE GROUND TEMPERATURE [C] SITE DEEP GROUND TEMPERATURE [C] SITE MAINS WATER TEMPERATURE [C] SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] SITE SNOW ON GROUND STATUS []
January 18.00 13.00 16.00 24.73 28.77 0.00
February 18.00 13.00 16.00 25.06 35.04 0.00
March 18.00 13.00 16.00 26.11 42.49 0.00
April 18.00 13.00 16.00 27.63 49.05 0.00
May 18.00 13.00 16.00 29.20 48.15 0.00
June 18.00 13.00 16.00 30.41 45.99 0.00
July 18.00 13.00 16.00 30.92 49.88 0.00
August 18.00 13.00 16.00 30.58 45.60 0.00
September 18.00 13.00 16.00 29.50 40.49 0.00
October 18.00 13.00 16.00 27.97 35.89 0.00
November 18.00 13.00 16.00 26.40 29.31 0.00
December 18.00 13.00 16.00 25.21 26.63 0.00
             
Annual Sum or Average 18.00 13.00 16.00 27.83 39.80 0.00
Minimum of Months 18.00 13.00 16.00 24.73 26.63 0.00
Maximum of Months 18.00 13.00 16.00 30.92 49.88 0.00



Table of Contents

Report: WaterHeaterReportMonthly

For: SWHSYS1 WATER HEATER

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] WATER HEATER BURNER HEATING ENERGY [] WATER HEATER GAS CONSUMPTION [] WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] WATER HEATER LOSS DEMAND ENERGY [] WATER HEATER HEAT LOSS ENERGY [J] WATER HEATER TANK TEMPERATURE [C] WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] WATER HEATER SOURCE ENERGY []
January 0.282564E+11 -0.272387E+11 0.00 0.00 744.00 0.00 -0.101766E+10 58.96 0.00 0.00
February 0.254352E+11 -0.245153E+11 0.00 0.00 672.00 0.00 -919936965.6 58.97 0.00 0.00
March 0.289648E+11 -0.279426E+11 0.00 0.00 744.00 0.00 -0.102216E+10 58.97 0.00 0.00
April 0.251499E+11 -0.241638E+11 0.00 0.00 720.00 0.00 -986074246.1 58.96 0.00 0.00
May 0.255373E+11 -0.245164E+11 0.00 0.00 744.00 0.00 -0.102086E+10 58.97 0.00 0.00
June 0.243111E+11 -0.233216E+11 0.00 0.00 720.00 0.00 -989542560.2 58.97 0.00 0.00
July 0.227962E+11 -0.217790E+11 0.00 0.00 744.00 0.00 -0.101722E+10 58.97 0.00 0.00
August 0.251586E+11 -0.241368E+11 0.00 0.00 744.00 0.00 -0.102178E+10 58.97 0.00 0.00
September 0.237193E+11 -0.227333E+11 0.00 0.00 720.00 0.00 -986076280.2 58.97 0.00 0.00
October 0.256825E+11 -0.246653E+11 0.00 0.00 744.00 0.00 -0.101715E+10 58.98 0.00 0.00
November 0.264029E+11 -0.254192E+11 0.00 0.00 720.00 0.00 -983760075.2 58.97 0.00 0.00
December 0.272330E+11 -0.262166E+11 0.00 0.00 744.00 0.00 -0.101644E+10 58.98 0.00 0.00
                     
Annual Sum or Average 0.308647E+12 -0.296649E+12 0.00 0.00 8760.00 0.00 -0.119987E+11 58.97 0.00 0.00
Minimum of Months 0.227962E+11 -0.279426E+11 0.00 0.00 672.00 0.00 -0.102216E+10 58.96 0.00 0.00
Maximum of Months 0.289648E+11 -0.217790E+11 0.00 0.00 744.00 0.00 -919936965.6 58.98 0.00 0.00



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_BOT_ZN_1_DAYLCTRL

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 287.00 0.51 0.48 01-JAN-07:40 7161.55 36.22 275.17 293.50 1394.33 25.80 233.33 277.33
February 304.33 0.51 0.48 01-FEB-08:20 2666.09 26.24 165.33 279.00 1088.36 21.44 176.67 252.33
March 362.67 0.51 0.48 01-MAR-07:49 1652.04 20.40 91.33 329.50 903.41 21.46 215.83 295.17
April 357.50 0.52 0.48 01-APR-07:30 1293.64 19.78 35.83 327.67 729.79 21.06 192.67 295.00
May 389.00 0.52 0.48 01-MAY-07:19 1111.29 19.31 3.00 350.00 619.38 20.63 172.83 302.17
June 388.17 0.54 0.48 01-JUN-07:19 1049.10 18.70 4.83 327.67 579.43 20.02 151.67 279.33
July 403.83 0.52 0.48 01-JUL-06:00 1175.57 19.53 8.33 357.33 649.74 20.87 227.33 307.17
August 348.33 0.52 0.48 01-AUG-07:40 1393.72 19.98 58.00 346.00 754.55 21.31 239.67 306.00
September 349.67 0.52 0.48 01-SEP-07:19 1667.06 20.24 106.50 316.83 878.36 21.58 242.67 282.33
October 323.50 0.52 0.48 02-OCT-08:09 2190.69 21.96 137.00 314.50 1079.65 22.13 247.00 288.33
November 314.83 0.50 0.48 01-NOV-07:10 4093.04 31.76 262.00 293.50 1197.96 23.77 248.00 269.67
December 282.67 0.50 0.48 01-DEC-08:39 6808.91 36.48 279.00 280.17 1622.00 27.14 243.67 262.17
                         
Annual Sum or Average 4111.50 0.52     2488.87 23.58 1426.33 3815.67 924.98 22.07 2591.33 3417.00
Minimum of Months 282.67 0.50 0.48   1049.10 18.70 3.00 279.00 579.43 20.02 151.67 252.33
Maximum of Months 403.83 0.54 0.48   7161.55 36.48 279.00 357.33 1622.00 27.14 248.00 307.17



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_BOT_ZN_2_DAYLCTRL

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 287.00 0.54 0.48 01-JAN-07:40 2282.88 24.59 106.33 272.00 1198.72 24.41 145.33 232.83
February 304.33 0.53 0.48 01-FEB-07:49 2387.49 23.90 101.83 263.67 901.86 22.55 128.50 230.83
March 362.67 0.52 0.48 01-MAR-07:19 2273.94 23.34 99.50 326.00 1194.14 23.59 154.00 293.67
April 357.50 0.52 0.48 01-APR-06:00 2639.95 23.13 100.00 327.50 1405.20 23.52 133.50 296.00
May 389.00 0.51 0.48 01-MAY-06:10 2441.36 23.15 113.17 360.83 1030.63 22.64 137.17 315.17
June 388.17 0.52 0.48 01-JUN-05:00 2373.38 23.62 122.83 345.17 1007.17 22.92 151.17 303.83
July 403.83 0.51 0.48 01-JUL-06:19 2347.74 23.63 123.67 365.17 1033.39 23.07 188.00 323.67
August 348.33 0.52 0.48 01-AUG-06:40 2307.73 23.22 97.83 348.83 1217.12 23.70 163.17 311.50
September 349.67 0.52 0.48 01-SEP-06:49 2263.46 23.81 105.67 313.67 1166.57 24.04 184.33 275.00
October 323.50 0.52 0.48 02-OCT-07:10 2236.51 23.93 98.50 306.00 1176.96 24.07 178.67 272.17
November 314.83 0.52 0.48 01-NOV-06:00 1796.43 23.60 100.00 276.67 908.13 23.57 164.00 237.83
December 282.67 0.53 0.48 01-DEC-08:39 1927.54 23.44 91.00 258.83 790.49 22.30 129.83 218.00
                         
Annual Sum or Average 4111.50 0.52     2285.92 23.59 1260.33 3764.33 1090.87 23.36 1857.67 3310.50
Minimum of Months 282.67 0.51 0.48   1796.43 23.13 91.00 258.83 790.49 22.30 128.50 218.00
Maximum of Months 403.83 0.54 0.48   2639.95 24.59 123.67 365.17 1405.20 24.41 188.00 323.67



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_BOT_ZN_3_DAYLCTRL

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 287.00 0.57 0.48 01-JAN-09:50 589.89 16.73 0.00 253.17 372.69 18.34 0.00 168.83
February 304.33 0.55 0.48 01-FEB-09:20 670.73 17.53 0.00 254.83 412.88 18.98 0.67 191.50
March 362.67 0.52 0.48 01-MAR-09:30 801.16 18.66 0.00 319.00 483.27 20.02 29.00 265.00
April 357.50 0.52 0.48 01-APR-07:30 955.86 19.47 0.00 332.67 567.68 20.73 115.67 299.83
May 389.00 0.50 0.48 01-MAY-06:40 1131.37 20.85 64.17 369.00 629.95 22.00 205.50 336.83
June 388.17 0.51 0.48 01-JUN-06:40 1201.87 22.15 115.00 358.67 642.65 21.05 196.67 309.33
July 403.83 0.50 0.48 01-JUL-06:40 1262.13 21.15 100.83 376.17 689.64 22.44 283.50 341.00
August 348.33 0.51 0.48 01-AUG-07:19 1139.26 19.94 23.50 351.83 641.91 21.24 202.67 317.00
September 349.67 0.52 0.48 01-SEP-07:19 958.43 19.15 0.00 314.83 546.88 20.46 129.50 269.00
October 323.50 0.54 0.48 02-OCT-11:39 767.08 18.30 0.00 297.83 466.25 19.72 25.50 236.33
November 314.83 0.55 0.48 01-NOV-08:09 674.35 17.71 0.00 262.00 402.45 19.15 3.17 191.00
December 282.67 0.54 0.48 01-DEC-09:09 641.79 17.44 0.00 247.50 392.96 19.01 0.00 176.33
                         
Annual Sum or Average 4111.50 0.53     923.23 19.26 303.50 3737.50 531.99 20.39 1191.83 3102.00
Minimum of Months 282.67 0.50 0.48   589.89 16.73 0.00 247.50 372.69 18.34 0.00 168.83
Maximum of Months 403.83 0.57 0.48   1262.13 22.15 115.00 376.17 689.64 22.44 283.50 341.00



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_BOT_ZN_4_DAYLCTRL

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 287.00 0.54 0.48 01-JAN-09:39 1971.28 23.64 95.33 274.00 1067.92 23.80 141.33 232.00
February 304.33 0.53 0.48 01-FEB-09:20 1815.94 22.10 75.50 270.17 920.95 22.31 129.17 234.67
March 362.67 0.52 0.48 01-MAR-09:30 2217.25 23.39 100.00 324.67 1142.26 23.66 161.17 292.33
April 357.50 0.51 0.48 01-APR-08:00 2416.70 22.07 81.00 336.67 1293.14 22.62 105.17 305.50
May 389.00 0.52 0.48 01-MAY-07:40 2179.90 18.14 0.00 353.33 1128.18 20.22 97.33 315.33
June 388.17 0.53 0.48 01-JUN-07:30 1833.92 17.81 4.83 337.17 826.03 19.81 105.83 296.17
July 403.83 0.52 0.48 01-JUL-07:19 2075.19 18.69 3.83 361.17 930.90 20.56 140.17 323.33
August 348.33 0.52 0.48 01-AUG-08:09 2235.96 21.01 58.17 345.17 1152.50 20.93 146.50 310.33
September 349.67 0.52 0.48 01-SEP-07:49 1857.20 22.07 84.50 317.17 954.62 22.55 164.67 282.00
October 323.50 0.52 0.48 02-OCT-11:39 2218.74 24.26 109.00 304.67 1165.73 24.48 180.00 270.00
November 314.83 0.52 0.48 01-NOV-08:20 1756.25 23.64 107.17 276.67 907.03 23.81 172.17 241.50
December 282.67 0.51 0.48 01-DEC-09:09 2015.96 25.13 109.00 268.67 1058.42 24.95 152.33 235.00
                         
Annual Sum or Average 4111.50 0.52     2055.98 21.61 828.33 3769.50 1044.84 22.33 1695.83 3338.17
Minimum of Months 282.67 0.51 0.48   1756.25 17.81 0.00 268.67 826.03 19.81 97.33 232.00
Maximum of Months 403.83 0.54 0.48   2416.70 25.13 109.00 361.17 1293.14 24.95 180.00 323.33



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_MID_ZN_1_DAYLCTRL

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 287.00 0.51 0.48 01-JAN-07:40 7215.63 35.67 274.83 293.67 1489.43 21.63 81.17 279.83
February 304.33 0.51 0.48 01-FEB-08:20 2709.03 22.17 135.00 279.17 1168.77 16.67 0.00 255.17
March 362.67 0.51 0.48 01-MAR-07:49 1684.87 14.27 5.67 330.33 967.29 17.43 0.00 298.67
April 357.50 0.52 0.48 01-APR-07:30 1316.36 14.03 0.00 328.17 778.57 17.45 0.00 300.00
May 389.00 0.52 0.48 01-MAY-07:19 1127.81 13.49 0.00 350.00 659.22 16.87 0.00 308.50
June 388.17 0.54 0.48 01-JUN-07:19 1063.90 12.74 0.00 328.83 616.40 16.15 0.00 286.00
July 403.83 0.52 0.48 01-JUL-06:00 1192.07 13.62 0.00 357.33 691.01 17.04 0.00 312.83
August 348.33 0.52 0.48 01-AUG-07:30 1412.81 14.13 0.00 346.33 802.61 17.51 0.00 310.17
September 349.67 0.52 0.48 01-SEP-07:10 1689.10 14.00 0.00 316.83 934.71 17.40 0.00 287.00
October 323.50 0.51 0.48 02-OCT-07:49 2239.53 16.06 31.67 316.50 1155.56 18.14 9.17 292.83
November 314.83 0.50 0.48 01-NOV-07:10 4123.66 29.93 245.17 293.83 1292.42 21.00 71.33 276.33
December 282.67 0.50 0.48 01-DEC-08:39 6852.13 36.06 278.50 280.67 1717.86 23.14 92.67 263.67
                         
Annual Sum or Average 4111.50 0.52     2517.92 18.85 970.83 3821.67 987.42 18.18 254.33 3471.00
Minimum of Months 282.67 0.50 0.48   1063.90 12.74 0.00 279.17 616.40 16.15 0.00 255.17
Maximum of Months 403.83 0.54 0.48   7215.63 36.06 278.50 357.33 1717.86 23.14 92.67 312.83



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_MID_ZN_2_DAYLCTRL

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 287.00 0.53 0.48 01-JAN-07:40 2319.05 22.16 102.67 272.50 1245.71 22.53 74.17 237.67
February 304.33 0.53 0.48 01-FEB-07:49 2430.43 21.20 100.67 264.33 950.43 20.12 45.67 235.67
March 362.67 0.51 0.48 01-MAR-07:19 2326.74 20.28 98.83 326.33 1251.14 21.17 67.67 297.17
April 357.50 0.52 0.48 01-APR-06:00 2664.75 20.09 99.83 328.17 1463.68 21.09 70.67 299.33
May 389.00 0.51 0.48 01-MAY-06:10 2458.01 19.45 103.83 361.83 1085.31 20.00 57.83 320.17
June 388.17 0.52 0.48 01-JUN-05:00 2410.49 20.63 122.00 346.83 1059.44 20.33 65.17 309.00
July 403.83 0.51 0.48 01-JUL-06:19 2373.93 19.96 115.67 365.67 1087.86 20.48 63.67 328.67
August 348.33 0.52 0.48 01-AUG-06:40 2328.66 20.24 97.17 350.00 1271.65 21.38 71.17 316.00
September 349.67 0.52 0.48 01-SEP-06:49 2301.15 20.86 104.00 314.83 1219.43 21.74 74.83 278.00
October 323.50 0.52 0.48 02-OCT-07:10 2283.83 21.02 94.50 307.00 1228.65 21.90 67.33 275.00
November 314.83 0.52 0.48 01-NOV-06:00 1812.05 19.90 84.67 278.50 952.32 21.40 59.33 243.00
December 282.67 0.53 0.48 01-DEC-08:39 1956.05 20.86 87.17 260.00 831.14 20.08 34.50 224.17
                         
Annual Sum or Average 4111.50 0.52     2317.94 20.50 1211.00 3776.00 1142.67 20.99 752.00 3363.83
Minimum of Months 282.67 0.51 0.48   1812.05 19.45 84.67 260.00 831.14 20.00 34.50 224.17
Maximum of Months 403.83 0.53 0.48   2664.75 22.16 122.00 365.67 1463.68 22.53 74.83 328.67



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_MID_ZN_3_DAYLCTRL

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 287.00 0.56 0.48 01-JAN-09:39 600.35 11.12 0.00 254.33 397.08 14.73 0.00 182.33
February 304.33 0.54 0.48 01-FEB-09:09 682.98 11.94 0.00 255.33 439.97 15.45 0.00 203.83
March 362.67 0.52 0.48 01-MAR-09:09 816.22 13.25 0.00 320.17 515.09 16.71 0.00 272.67
April 357.50 0.51 0.48 01-APR-07:30 974.38 14.10 0.00 332.67 605.26 17.53 0.00 304.33
May 389.00 0.50 0.48 01-MAY-06:40 1150.51 15.41 26.83 369.17 671.12 18.61 25.83 341.17
June 388.17 0.51 0.48 01-JUN-06:10 1222.07 17.22 66.17 359.00 695.51 18.73 33.00 323.83
July 403.83 0.50 0.48 01-JUL-06:40 1314.18 15.58 26.17 376.17 733.52 18.89 26.17 347.50
August 348.33 0.51 0.48 01-AUG-07:10 1157.95 14.31 0.00 351.83 682.97 17.72 0.00 320.83
September 349.67 0.52 0.48 01-SEP-07:10 973.98 13.51 0.00 315.17 581.81 16.88 0.00 276.50
October 323.50 0.54 0.48 02-OCT-11:39 780.36 12.95 0.00 298.33 496.51 16.40 0.00 246.50
November 314.83 0.54 0.48 01-NOV-08:09 685.12 11.97 0.00 262.67 428.24 15.49 0.00 203.50
December 282.67 0.54 0.48 01-DEC-09:09 651.91 11.74 0.00 248.00 418.23 15.34 0.00 188.67
                         
Annual Sum or Average 4111.50 0.52     942.11 13.77 119.17 3742.83 567.51 17.02 85.00 3211.67
Minimum of Months 282.67 0.50 0.48   600.35 11.12 0.00 248.00 397.08 14.73 0.00 182.33
Maximum of Months 403.83 0.56 0.48   1314.18 17.22 66.17 376.17 733.52 18.89 33.00 347.50



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_MID_ZN_4_DAYLCTRL

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 287.00 0.54 0.48 01-JAN-09:30 2004.06 21.08 91.50 274.67 1111.12 21.86 65.83 237.17
February 304.33 0.52 0.48 01-FEB-09:09 1856.42 19.05 71.17 270.83 967.96 19.92 46.50 239.00
March 362.67 0.52 0.48 01-MAR-09:09 2271.36 20.31 99.17 325.00 1198.64 21.21 69.17 297.17
April 357.50 0.51 0.48 01-APR-08:50 2442.84 18.70 80.67 336.67 1350.56 19.91 51.83 309.33
May 389.00 0.51 0.48 01-MAY-07:40 2207.83 13.58 0.00 354.33 1182.01 16.94 0.00 320.00
June 388.17 0.53 0.48 01-JUN-07:30 1865.64 13.32 0.00 338.33 871.86 16.60 0.00 301.33
July 403.83 0.51 0.48 01-JUL-07:19 2104.90 14.27 3.67 362.17 981.75 17.39 0.00 329.00
August 348.33 0.52 0.48 01-AUG-07:00 2258.00 17.35 56.83 346.33 1207.43 17.80 5.50 313.67
September 349.67 0.52 0.48 01-SEP-07:49 1891.79 18.88 80.67 318.00 1002.47 20.05 51.83 286.67
October 323.50 0.52 0.48 02-OCT-11:39 2264.75 21.59 105.33 305.17 1215.06 22.39 76.50 274.17
November 314.83 0.52 0.48 01-NOV-08:09 1787.24 20.89 96.83 278.17 949.47 21.72 67.50 246.67
December 282.67 0.51 0.48 01-DEC-09:09 2049.74 22.63 96.50 270.17 1104.38 23.04 67.17 238.67
                         
Annual Sum or Average 4111.50 0.52     2089.99 18.17 782.33 3779.83 1094.73 19.70 501.83 3392.83
Minimum of Months 282.67 0.51 0.48   1787.24 13.32 0.00 270.17 871.86 16.60 0.00 237.17
Maximum of Months 403.83 0.54 0.48   2442.84 22.63 105.33 362.17 1350.56 23.04 76.50 329.00



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_TOP_ZN_1_DAYLCTRL

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 287.00 0.51 0.48 01-JAN-07:40 7217.67 35.66 274.83 293.67 1491.28 21.62 81.17 279.83
February 304.33 0.51 0.48 01-FEB-08:20 2711.56 22.15 135.00 279.17 1170.43 16.66 0.00 255.17
March 362.67 0.51 0.48 01-MAR-07:49 1687.17 14.24 5.67 330.33 968.71 17.42 0.00 298.83
April 357.50 0.52 0.48 01-APR-07:30 1318.16 14.00 0.00 328.17 779.71 17.43 0.00 300.00
May 389.00 0.52 0.48 01-MAY-07:19 1129.39 13.46 0.00 350.17 660.20 16.86 0.00 308.67
June 388.17 0.54 0.48 01-JUN-07:19 1065.44 12.71 0.00 328.83 617.34 16.13 0.00 286.00
July 403.83 0.52 0.48 01-JUL-06:00 1193.75 13.59 0.00 357.50 692.07 17.02 0.00 313.00
August 348.33 0.52 0.48 01-AUG-07:30 1414.92 14.10 0.00 346.33 803.89 17.49 0.00 310.17
September 349.67 0.52 0.48 01-SEP-07:10 1691.82 13.97 0.00 316.83 936.31 17.39 0.00 287.00
October 323.50 0.51 0.48 02-OCT-07:49 2242.40 16.03 31.67 316.50 1157.39 18.12 9.17 292.83
November 314.83 0.50 0.48 01-NOV-07:10 4126.42 29.92 245.17 293.83 1294.45 20.99 71.33 276.33
December 282.67 0.50 0.48 01-DEC-08:39 6854.47 36.05 278.50 280.67 1720.03 23.13 92.67 263.83
                         
Annual Sum or Average 4111.50 0.52     2520.08 18.82 970.83 3822.00 988.87 18.17 254.33 3471.67
Minimum of Months 282.67 0.50 0.48   1065.44 12.71 0.00 279.17 617.34 16.13 0.00 255.17
Maximum of Months 403.83 0.54 0.48   7217.67 36.05 278.50 357.50 1720.03 23.13 92.67 313.00



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_TOP_ZN_2_DAYLCTRL

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 287.00 0.53 0.48 01-JAN-07:40 2319.98 22.14 102.67 272.67 1246.70 22.51 74.17 237.67
February 304.33 0.53 0.48 01-FEB-07:49 2431.68 21.17 100.67 264.33 951.53 20.11 45.67 235.67
March 362.67 0.51 0.48 01-MAR-07:19 2328.00 20.25 98.83 326.50 1252.32 21.16 67.67 297.17
April 357.50 0.52 0.48 01-APR-06:00 2666.38 20.06 99.83 328.17 1465.04 21.07 70.67 299.33
May 389.00 0.51 0.48 01-MAY-06:10 2459.76 19.42 103.83 361.83 1086.65 19.98 57.83 320.33
June 388.17 0.52 0.48 01-JUN-05:00 2412.39 20.61 122.00 346.83 1060.77 20.32 65.17 309.33
July 403.83 0.51 0.48 01-JUL-06:19 2375.96 19.93 115.67 365.83 1089.34 20.47 63.67 328.67
August 348.33 0.52 0.48 01-AUG-06:40 2330.71 20.22 97.17 350.00 1273.19 21.37 71.17 316.00
September 349.67 0.52 0.48 01-SEP-06:49 2303.20 20.83 104.00 314.83 1220.98 21.73 74.83 278.17
October 323.50 0.52 0.48 02-OCT-07:10 2285.10 20.99 94.50 307.00 1229.92 21.89 67.33 275.17
November 314.83 0.52 0.48 01-NOV-06:00 1813.35 19.87 84.67 278.67 953.46 21.39 59.33 243.00
December 282.67 0.53 0.48 01-DEC-08:39 1957.19 20.83 87.17 260.00 832.21 20.07 34.50 224.33
                         
Annual Sum or Average 4111.50 0.52     2319.52 20.47 1211.00 3776.67 1143.97 20.98 752.00 3364.83
Minimum of Months 282.67 0.51 0.48   1813.35 19.42 84.67 260.00 832.21 19.98 34.50 224.33
Maximum of Months 403.83 0.53 0.48   2666.38 22.14 122.00 365.83 1465.04 22.51 74.83 328.67



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_TOP_ZN_3_DAYLCTRL

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 287.00 0.56 0.48 01-JAN-09:39 600.78 11.09 0.00 254.50 397.53 14.71 0.00 182.50
February 304.33 0.54 0.48 01-FEB-09:09 683.57 11.91 0.00 255.50 440.51 15.44 0.00 204.17
March 362.67 0.52 0.48 01-MAR-09:09 817.02 13.22 0.00 320.17 515.75 16.70 0.00 272.67
April 357.50 0.51 0.48 01-APR-07:30 975.41 14.06 0.00 332.67 606.06 17.52 0.00 304.50
May 389.00 0.50 0.48 01-MAY-06:40 1151.95 15.39 26.83 369.17 672.11 18.60 25.83 341.33
June 388.17 0.51 0.48 01-JUN-06:10 1223.77 17.19 66.17 359.00 696.58 18.72 33.00 324.00
July 403.83 0.50 0.48 01-JUL-06:40 1315.88 15.55 26.17 376.33 734.65 18.88 26.17 347.67
August 348.33 0.51 0.48 01-AUG-07:10 1159.40 14.28 0.00 351.83 683.99 17.70 0.00 320.83
September 349.67 0.52 0.48 01-SEP-07:10 975.15 13.48 0.00 315.17 582.66 16.87 0.00 276.50
October 323.50 0.54 0.48 02-OCT-11:39 781.04 12.92 0.00 298.33 497.13 16.38 0.00 246.50
November 314.83 0.54 0.48 01-NOV-08:09 685.78 11.94 0.00 262.83 428.81 15.48 0.00 204.00
December 282.67 0.54 0.48 01-DEC-09:09 652.45 11.71 0.00 248.17 418.75 15.32 0.00 189.00
                         
Annual Sum or Average 4111.50 0.52     943.17 13.74 119.17 3743.67 568.30 17.01 85.00 3213.67
Minimum of Months 282.67 0.50 0.48   600.78 11.09 0.00 248.17 397.53 14.71 0.00 182.50
Maximum of Months 403.83 0.56 0.48   1315.88 17.19 66.17 376.33 734.65 18.88 33.00 347.67



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_TOP_ZN_4_DAYLCTRL

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 287.00 0.54 0.48 01-JAN-09:30 2005.00 21.06 91.50 275.00 1112.08 21.85 65.83 237.50
February 304.33 0.52 0.48 01-FEB-09:09 1857.61 19.02 71.17 270.83 969.04 19.91 46.50 239.17
March 362.67 0.52 0.48 01-MAR-09:09 2272.68 20.28 99.17 325.00 1199.87 21.20 69.17 297.17
April 357.50 0.51 0.48 01-APR-08:50 2444.35 18.67 80.67 336.67 1351.83 19.89 51.83 309.50
May 389.00 0.51 0.48 01-MAY-07:40 2209.59 13.55 0.00 354.33 1183.35 16.93 0.00 320.00
June 388.17 0.53 0.48 01-JUN-07:30 1867.60 13.29 0.00 338.50 873.15 16.58 0.00 301.50
July 403.83 0.51 0.48 01-JUL-07:19 2106.95 14.23 3.67 362.17 983.19 17.38 0.00 329.00
August 348.33 0.52 0.48 01-AUG-07:00 2260.13 17.32 56.83 346.33 1208.99 17.78 5.50 313.67
September 349.67 0.52 0.48 01-SEP-07:49 1893.82 18.85 80.67 318.00 1003.90 20.04 51.83 286.67
October 323.50 0.52 0.48 02-OCT-11:39 2266.31 21.56 105.33 305.17 1216.37 22.37 76.50 274.33
November 314.83 0.52 0.48 01-NOV-08:09 1788.55 20.86 96.83 278.17 950.63 21.71 67.50 246.67
December 282.67 0.51 0.48 01-DEC-09:09 2050.86 22.61 96.50 270.17 1105.47 23.03 67.17 238.67
                         
Annual Sum or Average 4111.50 0.52     2091.60 18.14 782.33 3780.33 1096.01 19.69 501.83 3393.83
Minimum of Months 282.67 0.51 0.48   1788.55 13.29 0.00 270.17 873.15 16.58 0.00 237.50
Maximum of Months 403.83 0.54 0.48   2444.35 22.61 105.33 362.17 1351.83 23.03 76.50 329.00



Table of Contents

Report: CoilReportMonthly

For: VAV_BOT WITH REHEAT HEATING COIL

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 1012693.02 885.77 25-JAN-06:40 0.00 0.00 0.00 0.00 0.00
February 2461801.29 13072.80 04-FEB-06:04 0.00 0.00 0.00 0.00 0.00
March 6088703.96 10733.24 16-MAR-05:17 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:02 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:05 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:02 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:03 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:05 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:03 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:03 0.00 0.00 0.00 0.00 0.00
November 164352.20 326.52 27-NOV-06:00 0.00 0.00 0.00 0.00 0.00
December 11035239.70 7313.96 15-DEC-06:17 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 20762790.18     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 11035239.70 13072.80   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: CORE_BOTTOM VAV BOX REHEAT COIL

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:05 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:02 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:05 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:02 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:03 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:05 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:03 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:03 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:05 0.00 0.00 0.00 0.00 0.00
February 8216307.19 1747.67 04-FEB-06:06 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:02 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:05 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:02 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:03 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:05 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:03 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:03 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 8216307.19     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 8216307.19 1747.67   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 1349751.26 522.94 25-JAN-06:40 0.00 0.00 0.00 0.00 0.00
February 7443846.50 2766.42 04-FEB-06:02 0.00 0.00 0.00 0.00 0.00
March 1431749.96 457.83 16-MAR-06:00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:02 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:05 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:02 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:03 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:05 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:03 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:03 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 476363.46 213.08 15-DEC-06:50 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 10701711.17     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 7443846.50 2766.42   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:05 0.00 0.00 0.00 0.00 0.00
February 4697781.17 1329.81 04-FEB-06:20 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:02 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:05 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:02 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:03 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:05 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:03 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:03 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 4697781.17     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 4697781.17 1329.81   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:05 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:02 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:05 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:02 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:03 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:05 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:03 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:03 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: VAV_MID WITH REHEAT HEATING COIL

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 5339979.81 19354.28 25-JAN-06:05 0.00 0.00 0.00 0.00 0.00
February 31808327.05 99565.91 04-FEB-06:04 0.00 0.00 0.00 0.00 0.00
March 31937293.99 98250.28 16-MAR-05:05 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:02 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:05 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:02 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:03 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:05 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:03 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:03 0.00 0.00 0.00 0.00 0.00
November 3198701.82 12787.07 27-NOV-06:06 0.00 0.00 0.00 0.00 0.00
December 23960842.26 86818.40 15-DEC-06:06 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 96245144.94     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 31937293.99 99565.91   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: CORE_MID VAV BOX REHEAT COIL

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:05 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:02 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:05 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:02 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:03 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:05 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:03 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:03 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.106461E+10 168955.37 25-JAN-06:03 0.00 0.00 0.00 0.00 0.00
February 0.119196E+10 170276.32 04-FEB-05:12 0.00 0.00 0.00 0.00 0.00
March 0.591823E+09 169085.46 16-MAR-05:03 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:02 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:05 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:02 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:03 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:05 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:03 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:03 0.00 0.00 0.00 0.00 0.00
November 0.160687E+09 23691.78 27-NOV-06:06 0.00 0.00 0.00 0.00 0.00
December 0.112225E+10 169121.97 15-DEC-06:02 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.413132E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.119196E+10 170276.32   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.568362E+09 62799.34 25-JAN-06:03 0.00 0.00 0.00 0.00 0.00
February 0.511151E+09 141647.76 04-FEB-05:11 0.00 0.00 0.00 0.00 0.00
March 0.295745E+09 54231.26 16-MAR-05:03 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:02 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:05 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:02 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:03 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:05 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:03 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:03 0.00 0.00 0.00 0.00 0.00
November 66835954.43 21257.46 27-NOV-06:08 0.00 0.00 0.00 0.00 0.00
December 0.928782E+09 86930.00 15-DEC-06:02 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.237088E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.928782E+09 141647.76   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 36203118.69 8220.11 31-JAN-07:00 0.00 0.00 0.00 0.00 0.00
February 0.336123E+09 168506.36 04-FEB-06:02 0.00 0.00 0.00 0.00 0.00
March 0.112553E+09 17466.26 16-MAR-06:00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:02 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:05 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:02 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:03 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:05 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:03 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:03 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 52765428.68 6459.01 15-DEC-07:00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.537645E+09     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.336123E+09 168506.36   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.704042E+09 24455.13 26-JAN-06:06 0.00 0.00 0.00 0.00 0.00
February 0.822726E+09 140004.52 04-FEB-05:11 0.00 0.00 0.00 0.00 0.00
March 0.315554E+09 28706.99 16-MAR-05:05 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:02 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:05 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:02 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:03 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:05 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:03 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:03 0.00 0.00 0.00 0.00 0.00
November 0.123282E+09 17249.48 13-NOV-06:04 0.00 0.00 0.00 0.00 0.00
December 0.773732E+09 45764.06 15-DEC-06:02 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.273934E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.822726E+09 140004.52   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: VAV_TOP WITH REHEAT HEATING COIL

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 1901636.92 4921.58 25-JAN-06:05 0.00 0.00 0.00 0.00 0.00
February 5804143.03 7566.21 04-FEB-06:04 0.00 0.00 0.00 0.00 0.00
March 1868710.56 7263.68 16-MAR-05:05 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:02 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:05 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:02 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:03 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:05 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:03 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:03 0.00 0.00 0.00 0.00 0.00
November 395820.08 2902.83 27-NOV-06:04 0.00 0.00 0.00 0.00 0.00
December 2459876.86 7253.45 15-DEC-06:04 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 12430187.44     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 5804143.03 7566.21   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: CORE_TOP VAV BOX REHEAT COIL

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 19480764.41 4957.60 23-JAN-06:50 0.00 0.00 0.00 0.00 0.00
February 96044060.08 8070.04 04-FEB-08:00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:02 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:05 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:02 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:03 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:05 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:03 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:03 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 5602629.27 2641.66 16-DEC-08:00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.121127E+09     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 96044060.08 8070.04   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.452535E+09 19614.80 23-JAN-06:02 0.00 0.00 0.00 0.00 0.00
February 0.331432E+09 19533.98 04-FEB-05:13 0.00 0.00 0.00 0.00 0.00
March 0.226775E+09 19529.91 16-MAR-04:12 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:02 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:05 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:02 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:03 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:05 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:03 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:03 0.00 0.00 0.00 0.00 0.00
November 71057010.87 19603.27 27-NOV-06:02 0.00 0.00 0.00 0.00 0.00
December 0.439335E+09 19612.09 13-DEC-06:02 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.152113E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.452535E+09 19614.80   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.226323E+09 15967.42 23-JAN-06:02 0.00 0.00 0.00 0.00 0.00
February 0.145957E+09 15953.62 04-FEB-05:13 0.00 0.00 0.00 0.00 0.00
March 99850652.10 14790.48 16-MAR-05:03 0.00 0.00 0.00 0.00 0.00
April 182403.44 199.40 19-APR-06:00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:05 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:02 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:03 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:05 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:03 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:03 0.00 0.00 0.00 0.00 0.00
November 31530593.90 15940.65 13-NOV-06:02 0.00 0.00 0.00 0.00 0.00
December 0.303500E+09 15951.00 27-DEC-06:02 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.807343E+09     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.303500E+09 15967.42   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 93840368.87 18446.77 25-JAN-06:03 0.00 0.00 0.00 0.00 0.00
February 98664761.83 19524.38 04-FEB-05:12 0.00 0.00 0.00 0.00 0.00
March 92333132.69 19521.61 16-MAR-05:03 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:02 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:05 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:02 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:03 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:05 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:03 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:03 0.00 0.00 0.00 0.00 0.00
November 22541113.66 19522.03 13-NOV-06:02 0.00 0.00 0.00 0.00 0.00
December 0.133193E+09 19591.68 27-DEC-06:02 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.440572E+09     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.133193E+09 19591.68   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.305667E+09 16523.15 26-JAN-06:02 0.00 0.00 0.00 0.00 0.00
February 0.209953E+09 16527.94 04-FEB-05:12 0.00 0.00 0.00 0.00 0.00
March 0.142364E+09 13169.95 16-MAR-05:03 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:02 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:05 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:02 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:03 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:05 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:03 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:03 0.00 0.00 0.00 0.00 0.00
November 51515770.96 16521.23 13-NOV-06:02 0.00 0.00 0.00 0.00 0.00
December 0.300573E+09 16530.32 27-DEC-06:02 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.101007E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.305667E+09 16530.32   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: CAV_BAS HEATING COIL

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:05 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:02 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:05 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:02 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:03 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:05 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:03 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:03 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: AIRLOOP DATACENTER BASEMENT HEATING COIL

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:05 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:02 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:05 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:02 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:03 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:05 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:03 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:03 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: AIRLOOP DATACENTER BOT HEATING COIL

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:05 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:02 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:05 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:02 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:03 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:05 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:03 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:03 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: AIRLOOP DATACENTER MID HEATING COIL

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:05 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:02 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:05 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:02 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:03 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:05 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:03 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:03 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: AIRLOOP DATACENTER TOP HEATING COIL

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:05 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:02 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:05 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:02 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:03 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:05 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:03 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:03 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:05 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:02 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:05 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:02 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:03 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:05 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:03 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:03 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: AIRLOOP DATACENTER BOT_SUPPHEATCOIL

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:05 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:02 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:05 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:02 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:03 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:05 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:03 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:03 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: AIRLOOP DATACENTER MID_SUPPHEATCOIL

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:05 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:02 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:05 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:02 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:03 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:05 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:03 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:03 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: AIRLOOP DATACENTER TOP_SUPPHEATCOIL

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:05 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:02 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:05 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:02 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:03 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:05 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:03 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:03 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: VAV_BOT WITH REHEAT COOLING COIL

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.103057E+12 0.767359E+11 241912.22 07-JAN-06:02 149529.28 0.52
February 0.00 0.00 0.114866E+12 0.862004E+11 252536.30 17-FEB-05:11 158745.24 0.54
March 0.00 0.00 0.157143E+12 0.111667E+12 221732.08 06-MAR-06:02 149723.12 0.64
April 0.00 0.00 0.188351E+12 0.133487E+12 204683.79 29-APR-05:02 147264.74 0.81
May 0.00 0.00 0.203682E+12 0.136977E+12 280113.08 27-MAY-03:02 149040.64 0.73
June 0.00 0.00 0.229803E+12 0.151900E+12 257703.84 22-JUN-05:03 164623.69 0.81
July 0.00 0.00 0.248806E+12 0.164825E+12 232474.94 05-JUL-05:03 156480.04 0.85
August 0.00 0.00 0.264772E+12 0.175992E+12 246334.87 21-AUG-05:03 181250.81 0.88
September 0.00 0.00 0.218780E+12 0.141572E+12 252578.13 25-SEP-05:02 167093.23 0.76
October 0.00 0.00 0.213335E+12 0.142294E+12 250915.59 07-OCT-05:03 165013.30 0.75
November 0.00 0.00 0.179437E+12 0.121853E+12 232125.28 03-NOV-05:02 157464.09 0.69
December 0.00 0.00 0.142038E+12 0.982195E+11 241236.47 09-DEC-06:02 161975.68 0.66
                 
Annual Sum or Average 0.00 0.00 0.226407E+13 0.154172E+13       0.72
Minimum of Months 0.00 0.00 0.103057E+12 0.767359E+11 204683.79   147264.74 0.52
Maximum of Months 0.00 0.00 0.264772E+12 0.175992E+12 280113.08   181250.81 0.88



Table of Contents

Report: CoilReportMonthly

For: VAV_MID WITH REHEAT COOLING COIL

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.851841E+12 0.613380E+12 2265835.08 14-JAN-06:03 1318272.13 0.49
February 0.00 0.00 0.925583E+12 0.672573E+12 2197607.77 02-FEB-06:02 1243663.12 0.51
March 0.00 0.00 0.115938E+13 0.822038E+12 2511423.65 06-MAR-05:12 1300303.25 0.53
April 0.00 0.00 0.136184E+13 0.966134E+12 2290829.39 25-APR-04:12 1438289.45 0.63
May 0.00 0.00 0.177990E+13 0.118850E+13 2737993.20 27-MAY-04:02 1322778.78 0.67
June 0.00 0.00 0.194752E+13 0.126781E+13 2679608.50 22-JUN-05:03 1558144.00 0.71
July 0.00 0.00 0.200966E+13 0.131269E+13 2612954.09 03-JUL-03:02 1424032.23 0.72
August 0.00 0.00 0.202869E+13 0.130845E+13 2443424.97 28-AUG-03:02 1410767.24 0.71
September 0.00 0.00 0.194079E+13 0.123304E+13 2541612.10 20-SEP-03:02 1481898.29 0.70
October 0.00 0.00 0.174324E+13 0.115719E+13 2586583.56 31-OCT-05:02 1482704.87 0.64
November 0.00 0.00 0.137180E+13 0.918690E+12 2430527.12 04-NOV-03:02 1269984.38 0.58
December 0.00 0.00 0.943657E+12 0.660792E+12 2590196.06 09-DEC-06:02 1528722.24 0.53
                 
Annual Sum or Average 0.00 0.00 0.180639E+14 0.121213E+14       0.62
Minimum of Months 0.00 0.00 0.851841E+12 0.613380E+12 2197607.77   1243663.12 0.49
Maximum of Months 0.00 0.00 0.202869E+13 0.131269E+13 2737993.20   1558144.00 0.72



Table of Contents

Report: CoilReportMonthly

For: VAV_TOP WITH REHEAT COOLING COIL

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.826114E+11 0.593342E+11 230893.82 07-JAN-06:02 115018.35 0.48
February 0.00 0.00 0.946209E+11 0.688229E+11 210453.09 18-FEB-06:03 123339.36 0.49
March 0.00 0.00 0.121313E+12 0.856662E+11 254188.10 06-MAR-05:12 125543.73 0.53
April 0.00 0.00 0.146014E+12 0.104605E+12 226343.37 25-APR-04:12 135051.87 0.62
May 0.00 0.00 0.191148E+12 0.131569E+12 289128.25 27-MAY-04:02 134702.05 0.67
June 0.00 0.00 0.210404E+12 0.140753E+12 279339.85 22-JUN-05:03 160446.83 0.72
July 0.00 0.00 0.218686E+12 0.147312E+12 275993.92 03-JUL-03:02 153738.71 0.72
August 0.00 0.00 0.217048E+12 0.144277E+12 268365.47 10-AUG-05:03 154859.54 0.71
September 0.00 0.00 0.205579E+12 0.134604E+12 262470.00 20-SEP-03:02 148269.44 0.70
October 0.00 0.00 0.179149E+12 0.121988E+12 274620.40 31-OCT-05:02 154021.96 0.64
November 0.00 0.00 0.138899E+12 0.941951E+11 267967.67 04-NOV-03:02 141082.43 0.57
December 0.00 0.00 0.937344E+11 0.651613E+11 229057.86 26-DEC-05:12 114773.78 0.53
                 
Annual Sum or Average 0.00 0.00 0.189920E+13 0.129829E+13       0.62
Minimum of Months 0.00 0.00 0.826114E+11 0.593342E+11 210453.09   114773.78 0.48
Maximum of Months 0.00 0.00 0.218686E+12 0.147312E+12 289128.25   160446.83 0.72



Table of Contents

Report: CoilReportMonthly

For: CAV_BAS COOLING COIL

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.798334E+11 0.730627E+11 178340.03 30-JAN-05:23 90771.06 0.52
February 0.00 0.00 0.770349E+11 0.696599E+11 167398.03 02-FEB-05:12 95708.68 0.51
March 0.00 0.00 0.892622E+11 0.793095E+11 190167.97 06-MAR-05:23 89868.79 0.53
April 0.00 0.00 0.900736E+11 0.783108E+11 177868.78 16-APR-23:22 96972.63 0.56
May 0.00 0.00 0.114136E+12 0.897917E+11 214542.07 29-MAY-13:06 101858.85 0.60
June 0.00 0.00 0.127747E+12 0.918875E+11 206064.21 26-JUN-03:02 90196.06 0.62
July 0.00 0.00 0.132089E+12 0.942425E+11 204674.87 31-JUL-03:13 91666.71 0.59
August 0.00 0.00 0.145293E+12 0.103598E+12 206792.12 13-AUG-15:20 99481.53 0.64
September 0.00 0.00 0.127968E+12 0.925391E+11 205716.93 10-SEP-18:38 99674.30 0.62
October 0.00 0.00 0.122846E+12 0.939972E+11 215765.13 30-OCT-03:02 88844.81 0.62
November 0.00 0.00 0.107035E+12 0.859328E+11 202051.78 05-NOV-14:28 96590.10 0.59
December 0.00 0.00 0.853396E+11 0.762988E+11 190678.03 10-DEC-12:51 100856.03 0.57
                 
Annual Sum or Average 0.00 0.00 0.129866E+13 0.102863E+13       0.58
Minimum of Months 0.00 0.00 0.770349E+11 0.696599E+11 167398.03   88844.81 0.51
Maximum of Months 0.00 0.00 0.145293E+12 0.103598E+12 215765.13   101858.85 0.64



Table of Contents

Report: CoilReportMonthly

For: AIRLOOP DATACENTER BASEMENT COOLING COIL

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.340157E+12 0.330546E+12 140394.43 02-JAN-15:00 130674.34 0.00
February 0.00 0.00 0.530443E+12 0.520529E+12 231075.54 10-FEB-17:00 220537.38 0.00
March 0.00 0.00 0.834877E+12 0.822125E+12 396647.92 31-MAR-24:00 393817.22 0.00
April 0.00 0.00 0.104574E+13 0.103269E+13 425402.70 25-APR-16:00 407141.49 0.00
May 0.00 0.00 0.360308E+12 0.338716E+12 229271.31 31-MAY-23:03 212058.83 0.00
June 0.00 0.00 0.592182E+12 0.565497E+12 316724.06 30-JUN-23:03 303677.67 0.00
July 0.00 0.00 0.858013E+12 0.830811E+12 402259.48 31-JUL-24:00 392007.36 0.00
August 0.00 0.00 0.109298E+13 0.106733E+13 425831.11 23-AUG-17:00 407321.10 0.00
September 0.00 0.00 0.356542E+12 0.331317E+12 224750.41 30-SEP-23:03 212478.14 0.00
October 0.00 0.00 0.608741E+12 0.584968E+12 313228.93 31-OCT-23:10 302564.80 0.00
November 0.00 0.00 0.818361E+12 0.800352E+12 326897.81 30-NOV-17:00 313706.89 0.00
December 0.00 0.00 0.107957E+13 0.106754E+13 413874.72 08-DEC-17:10 401886.92 0.00
                 
Annual Sum or Average 0.00 0.00 0.851791E+13 0.829242E+13       0.00
Minimum of Months 0.00 0.00 0.340157E+12 0.330546E+12 140394.43   130674.34 0.00
Maximum of Months 0.00 0.00 0.109298E+13 0.106754E+13 425831.11   407321.10 0.00



Table of Contents

Report: CoilReportMonthly

For: AIRLOOP DATACENTER BOT COOLING COIL

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.577985E+10 0.540323E+10 3009.79 02-JAN-15:00 2604.40 0.00
February 0.00 0.00 0.101074E+11 0.969739E+10 4956.49 19-FEB-17:23 4657.67 0.00
March 0.00 0.00 0.164577E+11 0.159034E+11 7836.51 31-MAR-23:05 7659.78 0.00
April 0.00 0.00 0.210775E+11 0.204599E+11 8893.44 13-APR-16:00 8415.86 0.00
May 0.00 0.00 0.707565E+10 0.619899E+10 4798.65 31-MAY-23:03 4046.53 0.00
June 0.00 0.00 0.120593E+11 0.109164E+11 6490.05 30-JUN-23:03 5897.74 0.00
July 0.00 0.00 0.175933E+11 0.163862E+11 8457.32 31-JUL-23:03 7831.30 0.00
August 0.00 0.00 0.227726E+11 0.215299E+11 9038.20 21-AUG-13:00 8378.55 0.00
September 0.00 0.00 0.710388E+10 0.607154E+10 4557.11 30-SEP-23:03 4014.71 0.00
October 0.00 0.00 0.122284E+11 0.112170E+11 6304.64 31-OCT-23:10 5825.29 0.00
November 0.00 0.00 0.163215E+11 0.155313E+11 7113.10 07-NOV-17:00 6697.22 0.00
December 0.00 0.00 0.213617E+11 0.208009E+11 9030.43 08-DEC-17:00 8525.37 0.00
                 
Annual Sum or Average 0.00 0.00 0.169939E+12 0.160116E+12       0.00
Minimum of Months 0.00 0.00 0.577985E+10 0.540323E+10 3009.79   2604.40 0.00
Maximum of Months 0.00 0.00 0.227726E+11 0.215299E+11 9038.20   8525.37 0.00



Table of Contents

Report: CoilReportMonthly

For: AIRLOOP DATACENTER MID COOLING COIL

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.469627E+11 0.433608E+11 28172.61 02-JAN-15:00 24163.67 0.00
February 0.00 0.00 0.905764E+11 0.865296E+11 46440.11 10-FEB-17:00 42055.61 0.00
March 0.00 0.00 0.153790E+12 0.148264E+12 75628.50 31-MAR-23:05 73825.83 0.00
April 0.00 0.00 0.200571E+12 0.194389E+12 84825.00 13-APR-16:00 80013.92 0.00
May 0.00 0.00 0.663207E+11 0.576629E+11 46802.87 31-MAY-23:03 39083.95 0.00
June 0.00 0.00 0.114946E+12 0.103568E+12 62898.67 30-JUN-23:03 56876.02 0.00
July 0.00 0.00 0.167848E+12 0.155803E+12 81590.71 31-JUL-23:03 75276.94 0.00
August 0.00 0.00 0.216094E+12 0.203669E+12 85762.22 08-AUG-15:00 79326.95 0.00
September 0.00 0.00 0.663314E+11 0.561424E+11 43543.41 30-SEP-23:03 37970.43 0.00
October 0.00 0.00 0.115966E+12 0.105906E+12 59698.63 31-OCT-23:10 54795.65 0.00
November 0.00 0.00 0.153287E+12 0.145409E+12 67912.56 07-NOV-17:00 63761.19 0.00
December 0.00 0.00 0.197998E+12 0.192392E+12 85929.10 08-DEC-17:00 80884.40 0.00
                 
Annual Sum or Average 0.00 0.00 0.159069E+13 0.149310E+13       0.00
Minimum of Months 0.00 0.00 0.469627E+11 0.433608E+11 28172.61   24163.67 0.00
Maximum of Months 0.00 0.00 0.216094E+12 0.203669E+12 85929.10   80884.40 0.00



Table of Contents

Report: CoilReportMonthly

For: AIRLOOP DATACENTER TOP COOLING COIL

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.416360E+10 0.381303E+10 2874.43 02-JAN-15:00 2470.20 0.00
February 0.00 0.00 0.875792E+10 0.835548E+10 4720.78 19-FEB-17:22 4423.05 0.00
March 0.00 0.00 0.152186E+11 0.146674E+11 7516.99 31-MAR-23:05 7336.96 0.00
April 0.00 0.00 0.200696E+11 0.194525E+11 8628.56 13-APR-16:00 8147.54 0.00
May 0.00 0.00 0.674479E+10 0.587676E+10 4699.24 31-MAY-23:03 3932.59 0.00
June 0.00 0.00 0.116261E+11 0.104877E+11 6306.21 30-JUN-23:03 5705.52 0.00
July 0.00 0.00 0.169573E+11 0.157529E+11 8187.98 31-JUL-23:03 7558.46 0.00
August 0.00 0.00 0.217303E+11 0.204887E+11 8722.45 23-AUG-16:20 8107.94 0.00
September 0.00 0.00 0.674099E+10 0.571967E+10 4405.03 30-SEP-23:03 3853.82 0.00
October 0.00 0.00 0.116072E+11 0.106024E+11 5896.06 31-OCT-23:10 5403.90 0.00
November 0.00 0.00 0.151363E+11 0.143505E+11 6864.96 07-NOV-17:00 6450.25 0.00
December 0.00 0.00 0.194063E+11 0.188476E+11 8668.24 08-DEC-17:00 8164.18 0.00
                 
Annual Sum or Average 0.00 0.00 0.158159E+12 0.148415E+12       0.00
Minimum of Months 0.00 0.00 0.416360E+10 0.381303E+10 2874.43   2470.20 0.00
Maximum of Months 0.00 0.00 0.217303E+11 0.204887E+11 8722.45   8164.18 0.00



Table of Contents

Report: PlantLoopDemandReportMonthly

For: HEATSYS1

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 0.00 0.00 01-JAN-00:05 1210.99 554039.54 25-JAN-06:03
February 0.00 0.00 01-FEB-00:10 1557.57 944505.66 04-FEB-05:11
March 0.00 0.00 01-MAR-00:10 711.59 524303.31 16-MAR-05:03
April 0.00 0.00 01-APR-00:02 0.06 183.43 19-APR-06:00
May 0.00 0.00 01-MAY-00:05 0.00 0.00 01-MAY-00:05
June 0.00 0.00 01-JUN-00:02 0.00 0.00 01-JUN-00:02
July 0.00 0.00 01-JUL-00:03 0.00 0.00 01-JUL-00:03
August 0.00 0.00 01-AUG-00:05 0.00 0.00 01-AUG-00:05
September 0.00 0.00 01-SEP-00:03 0.00 0.00 01-SEP-00:03
October 0.00 0.00 01-OCT-00:03 0.00 0.00 01-OCT-00:03
November 0.00 0.00 01-NOV-00:10 204.65 144269.74 13-NOV-06:02
December 0.00 0.00 01-DEC-00:10 1517.56 650634.63 15-DEC-06:02
             
Annual Sum or Average 0.00     428.49    
Minimum of Months 0.00 0.00   0.00 0.00  
Maximum of Months 0.00 0.00   1557.57 944505.66  



Table of Contents

Report: PlantLoopDemandReportMonthly

For: COOLSYS1_SUPPLY

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 451952.03 2136733.98 14-JAN-06:08 0.00 0.00 01-JAN-00:05
February 550111.34 2390541.02 13-FEB-05:16 0.00 0.00 01-FEB-00:10
March 626999.83 2854610.24 06-MAR-06:06 0.00 0.00 01-MAR-00:10
April 758483.76 2644326.91 15-APR-05:03 0.00 0.00 01-APR-00:02
May 939271.84 3299070.62 24-MAY-05:03 0.00 0.00 01-MAY-00:05
June 1045976.96 3132395.78 06-JUN-05:02 0.00 0.00 01-JUN-00:02
July 1039435.34 2794448.37 03-JUL-03:06 0.00 0.00 01-JUL-00:03
August 1063127.68 2896488.04 28-AUG-03:06 0.00 0.00 01-AUG-00:05
September 1034197.87 3989796.57 26-SEP-04:13 0.00 0.00 01-SEP-00:03
October 917337.33 3081188.63 31-OCT-05:02 0.00 0.00 01-OCT-00:03
November 761486.22 2496461.24 01-NOV-04:13 0.00 0.00 01-NOV-00:10
December 511314.59 2804504.34 09-DEC-06:02 0.00 0.00 01-DEC-00:10
             
Annual Sum or Average 809424.82     0.00    
Minimum of Months 451952.03 2136733.98   0.00 0.00  
Maximum of Months 1063127.68 3989796.57   0.00 0.00  



Table of Contents

Report: PlantLoopDemandReportMonthly

For: COOLSYS1_DEMAND

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 448270.53 4354311.47 14-JAN-06:03 0.00 0.00 01-JAN-00:05
February 547017.72 4165590.38 11-FEB-06:03 0.00 0.00 01-FEB-00:10
March 623184.89 4442981.74 06-MAR-06:02 0.00 0.00 01-MAR-00:10
April 753529.00 3936953.05 25-APR-04:12 0.00 0.00 01-APR-00:02
May 936512.16 4656771.68 27-MAY-05:04 0.00 0.00 01-MAY-00:05
June 1041267.13 4491770.56 19-JUN-03:02 0.00 0.00 01-JUN-00:02
July 1034547.20 4493990.89 03-JUL-03:02 0.00 0.00 01-JUL-00:03
August 1057289.28 4412459.63 28-AUG-03:02 0.00 0.00 01-AUG-00:05
September 1031151.82 4842844.12 05-SEP-04:11 0.00 0.00 01-SEP-00:03
October 915252.02 4395379.57 02-OCT-04:03 0.00 0.00 01-OCT-00:03
November 757978.32 4347265.94 22-NOV-06:03 0.00 0.00 01-NOV-00:10
December 507198.89 4288194.02 11-DEC-05:12 0.00 0.00 01-DEC-00:10
             
Annual Sum or Average 805545.72     0.00    
Minimum of Months 448270.53 3936953.05   0.00 0.00  
Maximum of Months 1057289.28 4842844.12   0.00 0.00  



Table of Contents

Report: PlantLoopDemandReportMonthly

For: SINGLE WATER PLANT LOOP

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 372092.91 883334.89 02-JAN-15:00 0.00 0.00 01-JAN-00:05
February 650404.24 1112972.66 11-FEB-14:00 0.00 0.00 01-FEB-00:10
March 899452.20 1365517.88 13-MAR-16:00 0.00 0.00 01-MAR-00:10
April 1256394.82 1720219.78 17-APR-15:00 0.00 0.00 01-APR-00:02
May 731222.96 1172860.69 22-MAY-13:10 0.00 0.00 01-MAY-00:05
June 1031768.97 1268882.83 11-JUN-13:00 0.00 0.00 01-JUN-00:02
July 1285738.76 1708633.03 29-JUL-16:00 0.00 0.00 01-JUL-00:03
August 1493976.77 1828218.94 23-AUG-13:00 0.00 0.00 01-AUG-00:05
September 796325.86 1072559.21 20-SEP-16:00 0.00 0.00 01-SEP-00:03
October 953733.98 1278582.14 03-OCT-15:00 0.00 0.00 01-OCT-00:03
November 1016281.13 1397194.29 17-NOV-15:00 0.00 0.00 01-NOV-00:10
December 1040701.27 1535257.57 10-DEC-14:59 0.00 0.00 01-DEC-00:10
             
Annual Sum or Average 962517.61     0.00    
Minimum of Months 372092.91 883334.89   0.00 0.00  
Maximum of Months 1493976.77 1828218.94   0.00 0.00  



Table of Contents

Report: PlantLoopDemandReportMonthly

For: SWHSYS1

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 0.00 0.00 01-JAN-00:05 11593.96 37891.82 18-JAN-13:00
February 0.00 0.00 01-FEB-00:10 11557.11 37783.78 01-FEB-12:40
March 0.00 0.00 01-MAR-00:10 11853.01 37047.62 01-MAR-12:20
April 0.00 0.00 01-APR-00:02 10743.33 35478.89 03-APR-11:30
May 0.00 0.00 01-MAY-00:05 10579.74 33923.17 01-MAY-11:50
June 0.00 0.00 01-JUN-00:02 10423.15 32401.89 01-JUN-12:00
July 0.00 0.00 01-JUL-00:03 9558.97 31450.61 03-JUL-11:30
August 0.00 0.00 01-AUG-00:05 10438.09 32163.19 31-AUG-11:20
September 0.00 0.00 01-SEP-00:03 10197.47 33515.92 29-SEP-11:40
October 0.00 0.00 01-OCT-00:03 10635.55 35244.88 31-OCT-11:30
November 0.00 0.00 01-NOV-00:10 11229.96 36773.88 30-NOV-12:40
December 0.00 0.00 01-DEC-00:10 11211.50 37678.73 28-DEC-13:00
             
Annual Sum or Average 0.00     10831.26    
Minimum of Months 0.00 0.00   9558.97 31450.61  
Maximum of Months 0.00 0.00   11853.01 37891.82  



Table of Contents

Report: PlantLoopDemandReportMonthly

For: TOWERWATERSYS

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 692442.13 5768476.73 02-JAN-14:00 504.78 101845.20 25-JAN-09:00
February 856310.44 4457955.46 10-FEB-16:20 1008.39 171917.84 04-FEB-08:50
March 1050581.82 5376060.16 14-MAR-09:50 577.17 175626.41 16-MAR-05:40
April 1358338.36 5659709.06 14-APR-15:00 52.63 27656.03 02-APR-02:20
May 2175610.71 6442500.31 31-MAY-13:00 5.39 22654.81 07-MAY-24:00
June 2972889.95 6694093.39 28-JUN-11:50 0.00 0.00 01-JUN-00:02
July 3112700.34 7034522.74 25-JUL-16:00 0.00 0.00 01-JUL-00:03
August 3204280.14 7111879.69 21-AUG-16:00 0.00 0.00 01-AUG-00:05
September 2892129.02 6684830.96 22-SEP-17:00 0.00 0.00 01-SEP-00:03
October 2261221.20 7417011.64 04-OCT-05:04 0.17 1506.02 16-OCT-00:50
November 1612596.45 6272718.88 29-NOV-12:00 375.46 104778.24 12-NOV-23:10
December 881662.20 5026791.32 07-DEC-15:00 845.92 166847.41 15-DEC-07:00
             
Annual Sum or Average 1928188.38     276.75    
Minimum of Months 692442.13 4457955.46   0.00 0.00  
Maximum of Months 3204280.14 7417011.64   1008.39 175626.41  



Table of Contents

Report: FanReportMonthly

For: CAV_BAS FAN

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.168521E+11 0.84 10318.97 01-JAN-00:15 1.37
February 0.149587E+11 0.83 10318.97 01-FEB-05:12 1.38
March 0.165852E+11 0.83 10318.97 01-MAR-05:12 1.38
April 0.153607E+11 0.79 10318.97 01-APR-04:12 1.38
May 0.170495E+11 0.85 10318.97 01-MAY-00:43 1.37
June 0.167602E+11 0.86 10318.97 01-JUN-03:02 1.38
July 0.168016E+11 0.83 10318.97 01-JUL-03:02 1.38
August 0.181435E+11 0.90 10318.97 01-AUG-03:02 1.38
September 0.170742E+11 0.88 10318.97 01-SEP-03:02 1.38
October 0.174756E+11 0.87 10318.97 01-OCT-13:55 1.36
November 0.169946E+11 0.87 10318.97 01-NOV-04:12 1.38
December 0.169079E+11 0.84 10318.97 01-DEC-05:11 1.38
           
Annual Sum or Average 0.200964E+12 0.85      
Minimum of Months 0.149587E+11 0.79 10318.97   1.36
Maximum of Months 0.181435E+11 0.90 10318.97   1.38



Table of Contents

Report: FanReportMonthly

For: VAV_BOT WITH REHEAT FAN

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.476305E+10 0.34 21783.72 07-JAN-06:02 1.75
February 0.503206E+10 0.37 21783.72 18-FEB-05:11 1.75
March 0.646833E+10 0.43 21783.72 06-MAR-06:02 1.75
April 0.707909E+10 0.49 18680.68 29-APR-05:02 1.59
May 0.671205E+10 0.45 21783.72 16-MAY-05:03 1.75
June 0.736381E+10 0.50 21783.72 09-JUN-05:02 1.75
July 0.808964E+10 0.53 21783.72 01-JUL-05:02 1.75
August 0.907733E+10 0.56 21783.72 28-AUG-05:02 1.75
September 0.692893E+10 0.47 21783.72 06-SEP-04:12 1.75
October 0.719731E+10 0.47 21783.72 04-OCT-05:02 1.75
November 0.662022E+10 0.44 21783.72 29-NOV-06:03 1.75
December 0.600621E+10 0.41 21349.64 01-DEC-05:11 1.73
           
Annual Sum or Average 0.813380E+11 0.45      
Minimum of Months 0.476305E+10 0.34 18680.68   1.59
Maximum of Months 0.907733E+10 0.56 21783.72   1.75



Table of Contents

Report: FanReportMonthly

For: VAV_MID WITH REHEAT FAN

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.372713E+11 0.31 196129.34 14-JAN-06:03 1.71
February 0.370415E+11 0.33 182062.82 18-FEB-06:03 1.63
March 0.461309E+11 0.35 205372.79 06-MAR-06:02 1.76
April 0.486238E+11 0.37 205372.79 25-APR-04:12 1.76
May 0.581987E+11 0.41 205372.79 03-MAY-05:03 1.76
June 0.610592E+11 0.44 205372.79 01-JUN-03:02 1.76
July 0.623808E+11 0.44 205372.79 06-JUL-04:02 1.76
August 0.631200E+11 0.44 205372.79 12-AUG-05:03 1.76
September 0.599828E+11 0.43 205372.79 06-SEP-05:02 1.76
October 0.577734E+11 0.40 205372.79 03-OCT-03:02 1.76
November 0.476024E+11 0.35 205372.79 24-NOV-06:03 1.76
December 0.390899E+11 0.32 204471.34 09-DEC-06:02 1.75
           
Annual Sum or Average 0.618275E+12 0.38      
Minimum of Months 0.370415E+11 0.31 182062.82   1.63
Maximum of Months 0.631200E+11 0.44 205372.79   1.76



Table of Contents

Report: FanReportMonthly

For: VAV_TOP WITH REHEAT FAN

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.344603E+10 0.29 14581.22 14-JAN-06:03 1.34
February 0.357265E+10 0.31 12635.80 18-FEB-06:03 1.23
March 0.455441E+10 0.34 19330.22 06-MAR-06:02 1.60
April 0.503629E+10 0.36 16878.25 24-APR-04:11 1.47
May 0.625942E+10 0.41 22117.41 22-MAY-04:11 1.75
June 0.660097E+10 0.44 22117.41 17-JUN-03:02 1.75
July 0.685507E+10 0.44 22117.41 03-JUL-03:02 1.75
August 0.680805E+10 0.44 21898.95 28-AUG-03:02 1.74
September 0.630795E+10 0.43 22117.41 05-SEP-04:11 1.75
October 0.581501E+10 0.38 20894.84 13-OCT-05:02 1.69
November 0.460452E+10 0.34 20594.90 10-NOV-06:02 1.67
December 0.367236E+10 0.30 16054.49 09-DEC-06:02 1.43
           
Annual Sum or Average 0.635327E+11 0.37      
Minimum of Months 0.344603E+10 0.29 12635.80   1.23
Maximum of Months 0.685507E+10 0.44 22117.41   1.75



Table of Contents

Report: FanReportMonthly

For: AIRLOOP DATACENTER BASEMENT SUPPLY FAN

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.951635E+11 1.35 35529.97 01-JAN-00:05 1.35
February 0.859541E+11 1.35 35529.97 01-FEB-00:10 1.35
March 0.951635E+11 1.35 35529.97 01-MAR-00:10 1.35
April 0.920937E+11 1.35 35529.97 01-APR-00:02 1.35
May 0.951635E+11 1.35 35529.97 01-MAY-00:05 1.35
June 0.920937E+11 1.35 35529.97 01-JUN-00:02 1.35
July 0.951635E+11 1.35 35529.97 01-JUL-00:03 1.35
August 0.951635E+11 1.35 35529.97 01-AUG-00:05 1.35
September 0.920937E+11 1.35 35529.97 01-SEP-00:03 1.35
October 0.951635E+11 1.35 35529.97 01-OCT-00:03 1.35
November 0.920937E+11 1.35 35529.97 01-NOV-00:10 1.35
December 0.951635E+11 1.35 35529.97 01-DEC-00:10 1.35
           
Annual Sum or Average 0.112047E+13 1.35      
Minimum of Months 0.859541E+11 1.35 35529.97   1.35
Maximum of Months 0.951635E+11 1.35 35529.97   1.35



Table of Contents

Report: FanReportMonthly

For: AIRLOOP DATACENTER BOT SUPPLY FAN

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.144032E+10 0.91 537.75 01-JAN-00:05 0.91
February 0.130093E+10 0.91 537.75 01-FEB-00:10 0.91
March 0.144032E+10 0.91 537.75 01-MAR-00:10 0.91
April 0.139386E+10 0.91 537.75 01-APR-00:02 0.91
May 0.144032E+10 0.91 537.75 01-MAY-00:05 0.91
June 0.139386E+10 0.91 537.75 01-JUN-00:02 0.91
July 0.144032E+10 0.91 537.75 01-JUL-00:03 0.91
August 0.144032E+10 0.91 537.75 01-AUG-00:05 0.91
September 0.139386E+10 0.91 537.75 01-SEP-00:03 0.91
October 0.144032E+10 0.91 537.75 01-OCT-00:03 0.91
November 0.139386E+10 0.91 537.75 01-NOV-00:10 0.91
December 0.144032E+10 0.91 537.75 01-DEC-00:10 0.91
           
Annual Sum or Average 0.169586E+11 0.91      
Minimum of Months 0.130093E+10 0.91 537.75   0.91
Maximum of Months 0.144032E+10 0.91 537.75   0.91



Table of Contents

Report: FanReportMonthly

For: AIRLOOP DATACENTER MID SUPPLY FAN

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.137355E+11 0.91 5128.23 01-JAN-00:05 0.91
February 0.124062E+11 0.91 5128.23 01-FEB-00:10 0.91
March 0.137355E+11 0.91 5128.23 01-MAR-00:10 0.91
April 0.132924E+11 0.91 5128.23 01-APR-00:02 0.91
May 0.137355E+11 0.91 5128.23 01-MAY-00:15 0.91
June 0.132924E+11 0.91 5128.23 01-JUN-00:02 0.91
July 0.137355E+11 0.91 5128.23 01-JUL-00:03 0.91
August 0.137355E+11 0.91 5128.23 01-AUG-00:05 0.91
September 0.132924E+11 0.91 5128.23 01-SEP-00:03 0.91
October 0.137355E+11 0.91 5128.23 01-OCT-00:03 0.91
November 0.132924E+11 0.91 5128.23 01-NOV-00:10 0.91
December 0.137355E+11 0.91 5128.23 01-DEC-00:10 0.91
           
Annual Sum or Average 0.161724E+12 0.91      
Minimum of Months 0.124062E+11 0.91 5128.23   0.91
Maximum of Months 0.137355E+11 0.91 5128.23   0.91



Table of Contents

Report: FanReportMonthly

For: AIRLOOP DATACENTER TOP SUPPLY FAN

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.140078E+10 0.91 522.99 01-JAN-00:05 0.91
February 0.126522E+10 0.91 522.99 01-FEB-00:10 0.91
March 0.140078E+10 0.91 522.99 01-MAR-00:10 0.91
April 0.135559E+10 0.91 522.99 01-APR-00:02 0.91
May 0.140078E+10 0.91 522.99 01-MAY-00:05 0.91
June 0.135559E+10 0.91 522.99 01-JUN-00:02 0.91
July 0.140078E+10 0.91 522.99 01-JUL-00:03 0.91
August 0.140078E+10 0.91 522.99 01-AUG-00:05 0.91
September 0.135559E+10 0.91 522.99 01-SEP-00:03 0.91
October 0.140078E+10 0.91 522.99 01-OCT-00:03 0.91
November 0.135559E+10 0.91 522.99 01-NOV-00:10 0.91
December 0.140078E+10 0.91 522.99 01-DEC-00:10 0.91
           
Annual Sum or Average 0.164930E+11 0.91      
Minimum of Months 0.126522E+10 0.91 522.99   0.91
Maximum of Months 0.140078E+10 0.91 522.99   0.91



Table of Contents

Report: PumpReportMonthly

For: HEATSYS1 PUMP

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

PUMP ELECTRICITY ENERGY [J] PUMP FLUID HEAT GAIN ENERGY [J] PUMP ELECTRICITY RATE {Maximum} [W] PUMP ELECTRICITY RATE {TIMESTAMP} PUMP SHAFT POWER {AT MAX/MIN} [W] PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s]
January 13213156.14 11891840.53 1809.10 25-JAN-06:03 1628.19 1628.19 27.69 2.44
February 15260941.51 13734847.36 2772.94 04-FEB-06:02 2495.65 2495.65 42.45 5.18
March 7383552.09 6645196.88 1720.29 16-MAR-05:03 1548.26 1548.26 26.90 2.28
April 620.73 558.65 0.68 19-APR-06:00 0.61 0.61 18.85 0.00
May 0.00 0.00 0.00 01-MAY-00:05 0.00 0.00 18.85 0.00
June 0.00 0.00 0.00 01-JUN-00:02 0.00 0.00 18.85 0.00
July 0.00 0.00 0.00 01-JUL-00:03 0.00 0.00 18.85 0.00
August 0.00 0.00 0.00 01-AUG-00:05 0.00 0.00 18.85 0.00
September 0.00 0.00 0.00 01-SEP-00:03 0.00 0.00 18.85 0.00
October 0.00 0.00 0.00 01-OCT-00:03 0.00 0.00 18.85 0.00
November 2006207.02 1805586.32 514.10 13-NOV-06:02 462.69 462.69 20.21 0.56
December 15681840.50 14113656.45 2033.07 15-DEC-06:02 1829.76 1829.76 28.22 2.89
                 
Annual Sum or Average 53546318.00 48191686.20            
Minimum of Months 0.00 0.00 0.00   0.00 0.00 18.85 0.00
Maximum of Months 15681840.50 14113656.45 2772.94   2495.65 2495.65 42.45 5.18



Table of Contents

Report: PumpReportMonthly

For: COOLSYS1 PUMP SECONDARY

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

PUMP ELECTRICITY ENERGY [J] PUMP FLUID HEAT GAIN ENERGY [J] PUMP ELECTRICITY RATE {Maximum} [W] PUMP ELECTRICITY RATE {TIMESTAMP} PUMP SHAFT POWER {AT MAX/MIN} [W] PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s]
January 0.111910E+10 0.100719E+10 23217.18 14-JAN-06:03 20895.46 20895.46 9.05 141.35
February 0.139908E+10 0.125918E+10 23217.18 18-FEB-06:03 20895.46 20895.46 8.93 141.35
March 0.193530E+10 0.174177E+10 23217.18 06-MAR-06:02 20895.46 20895.46 8.85 141.35
April 0.227867E+10 0.205080E+10 20444.15 25-APR-04:12 18399.73 18399.73 8.37 134.44
May 0.340401E+10 0.306361E+10 23217.18 08-MAY-04:13 20895.46 20895.46 9.67 141.35
June 0.372574E+10 0.335316E+10 23217.18 13-JUN-05:03 20895.46 20895.46 9.04 141.35
July 0.376039E+10 0.338435E+10 23217.18 18-JUL-05:03 20895.46 20895.46 9.02 141.35
August 0.393810E+10 0.354429E+10 23214.77 24-AUG-05:03 20893.30 20893.30 9.07 141.32
September 0.380236E+10 0.342212E+10 23217.18 05-SEP-04:11 20895.46 20895.46 8.63 141.35
October 0.341555E+10 0.307399E+10 23217.18 04-OCT-05:02 20895.46 20895.46 8.77 141.35
November 0.253808E+10 0.228427E+10 23217.18 22-NOV-06:03 20895.46 20895.46 9.04 141.35
December 0.136291E+10 0.122662E+10 23035.26 23-DEC-06:03 20731.74 20731.74 8.94 140.90
                 
Annual Sum or Average 0.326793E+11 0.294114E+11            
Minimum of Months 0.111910E+10 0.100719E+10 20444.15   18399.73 18399.73 8.37 134.44
Maximum of Months 0.393810E+10 0.354429E+10 23217.18   20895.46 20895.46 9.67 141.35



Table of Contents

Report: PumpReportMonthly

For: COOLSYS1 CHILLER1 PUMP

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

PUMP ELECTRICITY ENERGY [J] PUMP FLUID HEAT GAIN ENERGY [J] PUMP ELECTRICITY RATE {Maximum} [W] PUMP ELECTRICITY RATE {TIMESTAMP} PUMP SHAFT POWER {AT MAX/MIN} [W] PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s]
January 0.133599E+11 0.120239E+11 7989.88 01-JAN-00:15 7190.89 7190.89 6.79 70.68
February 0.122195E+11 0.109976E+11 7989.88 01-FEB-05:12 7190.89 7190.89 7.35 70.68
March 0.156174E+11 0.140557E+11 7989.88 01-MAR-05:12 7190.89 7190.89 8.78 70.68
April 0.174881E+11 0.157393E+11 7989.88 01-APR-00:02 7190.89 7190.89 6.93 70.68
May 0.167695E+11 0.150925E+11 7989.88 01-MAY-00:20 7190.89 7190.89 6.88 70.68
June 0.180475E+11 0.162427E+11 7989.88 01-JUN-00:02 7190.89 7190.89 9.04 70.68
July 0.194946E+11 0.175451E+11 7989.88 01-JUL-00:08 7190.89 7190.89 6.98 70.68
August 0.198801E+11 0.178921E+11 7989.88 01-AUG-00:05 7190.89 7190.89 10.37 70.68
September 0.171178E+11 0.154060E+11 7989.88 01-SEP-00:03 7190.89 7190.89 10.11 70.68
October 0.171256E+11 0.154130E+11 7989.88 01-OCT-00:03 7190.89 7190.89 7.35 70.68
November 0.153092E+11 0.137783E+11 7989.88 01-NOV-04:12 7190.89 7190.89 12.46 35.34
December 0.153227E+11 0.137904E+11 7989.88 01-DEC-00:12 7190.89 7190.89 7.04 70.68
                 
Annual Sum or Average 0.197752E+12 0.177977E+12            
Minimum of Months 0.122195E+11 0.109976E+11 7989.88   7190.89 7190.89 6.79 35.34
Maximum of Months 0.198801E+11 0.178921E+11 7989.88   7190.89 7190.89 12.46 70.68



Table of Contents

Report: PumpReportMonthly

For: COOLSYS1 CHILLER2 PUMP

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

PUMP ELECTRICITY ENERGY [J] PUMP FLUID HEAT GAIN ENERGY [J] PUMP ELECTRICITY RATE {Maximum} [W] PUMP ELECTRICITY RATE {TIMESTAMP} PUMP SHAFT POWER {AT MAX/MIN} [W] PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s]
January 0.459737E+09 0.413764E+09 7989.88 02-JAN-09:30 7190.89 7190.89 12.51 35.34
February 0.410371E+09 0.369334E+09 7989.88 02-FEB-06:06 7190.89 7190.89 12.61 35.34
March 0.157289E+10 0.141560E+10 7989.88 03-MAR-14:10 7190.89 7190.89 12.50 35.34
April 0.160549E+10 0.144494E+10 7989.88 03-APR-14:30 7190.89 7190.89 12.64 35.34
May 0.418843E+10 0.376959E+10 7989.88 01-MAY-07:50 7190.89 7190.89 12.43 35.34
June 0.543503E+10 0.489153E+10 7989.88 01-JUN-05:05 7190.89 7190.89 12.45 35.34
July 0.532501E+10 0.479251E+10 7989.88 03-JUL-03:04 7190.89 7190.89 12.57 35.34
August 0.583708E+10 0.525338E+10 7989.88 01-AUG-07:30 7190.89 7190.89 12.48 35.34
September 0.557987E+10 0.502188E+10 7989.88 01-SEP-07:50 7190.89 7190.89 12.40 35.34
October 0.434113E+10 0.390702E+10 7989.88 02-OCT-03:04 7190.89 7190.89 12.60 35.34
November 0.293252E+10 0.263927E+10 7989.88 01-NOV-04:12 7190.89 7190.89 12.46 35.34
December 0.675464E+09 0.607918E+09 7989.88 01-DEC-14:40 7190.89 7190.89 12.64 35.34
                 
Annual Sum or Average 0.383630E+11 0.345267E+11            
Minimum of Months 0.410371E+09 0.369334E+09 7989.88   7190.89 7190.89 12.40 35.34
Maximum of Months 0.583708E+10 0.525338E+10 7989.88   7190.89 7190.89 12.64 35.34



Table of Contents

Report: PumpReportMonthly

For: PLANT CIRC PUMP

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

PUMP ELECTRICITY ENERGY [J] PUMP FLUID HEAT GAIN ENERGY [J] PUMP ELECTRICITY RATE {Maximum} [W] PUMP ELECTRICITY RATE {TIMESTAMP} PUMP SHAFT POWER {AT MAX/MIN} [W] PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s]
January 0.919332E+10 0.827399E+10 3432.39 01-JAN-00:05 3089.15 3089.15 26.37 14.34
February 0.830364E+10 0.747328E+10 3432.39 01-FEB-00:10 3089.15 3089.15 24.96 14.34
March 0.919332E+10 0.827399E+10 3432.39 01-MAR-00:10 3089.15 3089.15 30.12 14.34
April 0.889676E+10 0.800708E+10 3432.39 01-APR-00:02 3089.15 3089.15 41.03 14.34
May 0.919332E+10 0.827399E+10 3432.39 01-MAY-00:05 3089.15 3089.15 28.47 14.34
June 0.889676E+10 0.800708E+10 3432.39 01-JUN-00:02 3089.15 3089.15 37.49 14.34
July 0.919332E+10 0.827399E+10 3432.39 01-JUL-00:03 3089.15 3089.15 41.88 14.34
August 0.919332E+10 0.827399E+10 3432.39 01-AUG-00:05 3089.15 3089.15 48.10 14.34
September 0.889676E+10 0.800708E+10 3432.39 01-SEP-00:03 3089.15 3089.15 34.28 14.34
October 0.919332E+10 0.827399E+10 3432.39 01-OCT-00:03 3089.15 3089.15 38.61 14.34
November 0.889676E+10 0.800708E+10 3432.39 01-NOV-00:10 3089.15 3089.15 36.89 14.34
December 0.919332E+10 0.827399E+10 3432.39 01-DEC-00:10 3089.15 3089.15 42.29 14.34
                 
Annual Sum or Average 0.108244E+12 0.974195E+11            
Minimum of Months 0.830364E+10 0.747328E+10 3432.39   3089.15 3089.15 24.96 14.34
Maximum of Months 0.919332E+10 0.827399E+10 3432.39   3089.15 3089.15 48.10 14.34



Table of Contents

Report: PumpReportMonthly

For: SWHSYS1 PUMP

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

PUMP ELECTRICITY ENERGY [J] PUMP FLUID HEAT GAIN ENERGY [J] PUMP ELECTRICITY RATE {Maximum} [W] PUMP ELECTRICITY RATE {TIMESTAMP} PUMP SHAFT POWER {AT MAX/MIN} [W] PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s]
January 0.112905E+09 33871561.48 56.21 01-JAN-06:05 16.86 16.86 56.41 0.44
February 0.101979E+09 30593668.43 56.21 01-FEB-06:03 16.86 16.86 57.25 0.44
March 0.112905E+09 33871561.48 56.21 01-MAR-06:03 16.86 16.86 56.99 0.44
April 0.109263E+09 32778930.46 56.21 01-APR-05:03 16.86 16.86 57.32 0.44
May 0.112905E+09 33871561.48 56.21 01-MAY-05:03 16.86 16.86 57.05 0.44
June 0.109263E+09 32778930.46 56.21 01-JUN-05:03 16.86 16.86 57.51 0.44
July 0.112905E+09 33871561.48 56.21 01-JUL-05:02 16.86 16.86 57.84 0.44
August 0.112905E+09 33871561.48 56.21 01-AUG-05:03 16.86 16.86 57.64 0.44
September 0.109263E+09 32778930.46 56.21 01-SEP-05:03 16.86 16.86 56.73 0.44
October 0.112905E+09 33871561.48 56.21 01-OCT-05:03 16.86 16.86 56.67 0.44
November 0.109263E+09 32778930.46 56.21 01-NOV-05:03 16.86 16.86 56.38 0.44
December 0.112905E+09 33871561.48 56.21 01-DEC-06:03 16.86 16.86 56.43 0.44
                 
Annual Sum or Average 0.132937E+10 0.398810E+09            
Minimum of Months 0.101979E+09 30593668.43 56.21   16.86 16.86 56.38 0.44
Maximum of Months 0.112905E+09 33871561.48 56.21   16.86 16.86 57.84 0.44



Table of Contents

Report: PumpReportMonthly

For: TOWERWATERSYS PUMP

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

PUMP ELECTRICITY ENERGY [J] PUMP FLUID HEAT GAIN ENERGY [J] PUMP ELECTRICITY RATE {Maximum} [W] PUMP ELECTRICITY RATE {TIMESTAMP} PUMP SHAFT POWER {AT MAX/MIN} [W] PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s]
January 0.354843E+11 0.319358E+11 41298.24 02-JAN-14:00 37168.41 37168.41 29.40 166.36
February 0.324338E+11 0.291904E+11 41253.30 10-FEB-16:20 37127.97 37127.97 27.51 166.36
March 0.438414E+11 0.394573E+11 41298.24 14-MAR-09:50 37168.41 37168.41 28.83 166.36
April 0.488607E+11 0.439746E+11 41298.24 13-APR-12:10 37168.41 37168.41 28.92 166.36
May 0.527551E+11 0.474796E+11 41298.24 10-MAY-09:20 37168.41 37168.41 28.81 166.36
June 0.595997E+11 0.536398E+11 41298.24 01-JUN-12:10 37168.41 37168.41 29.04 166.36
July 0.631222E+11 0.568100E+11 41298.24 03-JUL-03:06 37168.41 37168.41 29.61 166.36
August 0.654775E+11 0.589298E+11 41298.24 01-AUG-07:30 37168.41 37168.41 29.96 166.36
September 0.574145E+11 0.516730E+11 41298.24 01-SEP-08:70 37168.41 37168.41 29.23 166.36
October 0.543328E+11 0.488996E+11 41298.24 02-OCT-03:06 37168.41 37168.41 29.68 166.36
November 0.461186E+11 0.415067E+11 41298.24 01-NOV-04:12 37168.41 37168.41 28.84 166.36
December 0.410227E+11 0.369205E+11 41281.65 07-DEC-15:00 37153.48 37153.48 28.33 166.36
                 
Annual Sum or Average 0.600463E+12 0.540417E+12            
Minimum of Months 0.324338E+11 0.291904E+11 41253.30   37127.97 37127.97 27.51 166.36
Maximum of Months 0.654775E+11 0.589298E+11 41298.24   37168.41 37168.41 29.96 166.36



Table of Contents

Report: CondLoopDemandReportMonthly

For: HEATSYS1

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 0.00 0.00 01-JAN-00:05 82.00 82.00 1210.99 554039.54 25-JAN-06:03
February 0.00 0.00 01-FEB-00:10 18.92 18.92 1557.57 944505.66 04-FEB-05:11
March 0.00 0.00 01-MAR-00:10 17.74 17.74 711.59 524303.31 16-MAR-05:03
April 0.00 0.00 01-APR-00:02 18.86 18.86 0.06 183.43 19-APR-06:00
May 0.00 0.00 01-MAY-00:05 18.85 18.85 0.00 0.00 01-MAY-00:05
June 0.00 0.00 01-JUN-00:02 18.85 18.85 0.00 0.00 01-JUN-00:02
July 0.00 0.00 01-JUL-00:03 18.85 18.85 0.00 0.00 01-JUL-00:03
August 0.00 0.00 01-AUG-00:05 18.85 18.85 0.00 0.00 01-AUG-00:05
September 0.00 0.00 01-SEP-00:03 18.85 18.85 0.00 0.00 01-SEP-00:03
October 0.00 0.00 01-OCT-00:03 18.85 18.85 0.00 0.00 01-OCT-00:03
November 0.00 0.00 01-NOV-00:10 18.85 18.85 204.65 144269.74 13-NOV-06:02
December 0.00 0.00 01-DEC-00:10 19.96 19.96 1517.56 650634.63 15-DEC-06:02
                 
Annual Sum or Average 0.00         428.49    
Minimum of Months 0.00 0.00   17.74 17.74 0.00 0.00  
Maximum of Months 0.00 0.00   82.00 82.00 1557.57 944505.66  



Table of Contents

Report: CondLoopDemandReportMonthly

For: COOLSYS1_SUPPLY

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 451952.03 2136733.98 14-JAN-06:08 10.31 6.70 0.00 0.00 01-JAN-00:05
February 550111.34 2390541.02 13-FEB-05:16 10.74 6.70 0.00 0.00 01-FEB-00:10
March 626999.83 2854610.24 06-MAR-06:06 11.52 6.70 0.00 0.00 01-MAR-00:10
April 758483.76 2644326.91 15-APR-05:03 11.17 6.70 0.00 0.00 01-APR-00:02
May 939271.84 3299070.62 24-MAY-05:03 12.27 6.70 0.00 0.00 01-MAY-00:05
June 1045976.96 3132395.78 06-JUN-05:02 11.99 6.70 0.00 0.00 01-JUN-00:02
July 1039435.34 2794448.37 03-JUL-03:06 11.42 6.70 0.00 0.00 01-JUL-00:03
August 1063127.68 2896488.04 28-AUG-03:06 11.59 6.70 0.00 0.00 01-AUG-00:05
September 1034197.87 3989796.57 26-SEP-04:13 13.44 7.74 0.00 0.00 01-SEP-00:03
October 917337.33 3081188.63 31-OCT-05:02 11.90 6.70 0.00 0.00 01-OCT-00:03
November 761486.22 2496461.24 01-NOV-04:13 10.92 6.70 0.00 0.00 01-NOV-00:10
December 511314.59 2804504.34 09-DEC-06:02 11.44 6.70 0.00 0.00 01-DEC-00:10
                 
Annual Sum or Average 809424.82         0.00    
Minimum of Months 451952.03 2136733.98   10.31 6.70 0.00 0.00  
Maximum of Months 1063127.68 3989796.57   13.44 7.74 0.00 0.00  



Table of Contents

Report: CondLoopDemandReportMonthly

For: COOLSYS1_DEMAND

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 448270.53 4354311.47 14-JAN-06:03 14.06 10.37 0.00 0.00 01-JAN-00:05
February 547017.72 4165590.38 11-FEB-06:03 13.91 10.21 0.00 0.00 01-FEB-00:10
March 623184.89 4442981.74 06-MAR-06:02 14.21 10.45 0.00 0.00 01-MAR-00:10
April 753529.00 3936953.05 25-APR-04:12 13.69 10.01 0.00 0.00 01-APR-00:02
May 936512.16 4656771.68 27-MAY-05:04 14.57 10.63 0.00 0.00 01-MAY-00:05
June 1041267.13 4491770.56 19-JUN-03:02 14.65 10.48 0.00 0.00 01-JUN-00:02
July 1034547.20 4493990.89 03-JUL-03:02 14.60 10.48 0.00 0.00 01-JUL-00:03
August 1057289.28 4412459.63 28-AUG-03:02 14.44 10.41 0.00 0.00 01-AUG-00:05
September 1031151.82 4842844.12 05-SEP-04:11 14.89 10.78 0.00 0.00 01-SEP-00:03
October 915252.02 4395379.57 02-OCT-04:03 14.52 10.39 0.00 0.00 01-OCT-00:03
November 757978.32 4347265.94 22-NOV-06:03 14.05 10.37 0.00 0.00 01-NOV-00:10
December 507198.89 4288194.02 11-DEC-05:12 14.27 10.31 0.00 0.00 01-DEC-00:10
                 
Annual Sum or Average 805545.72         0.00    
Minimum of Months 448270.53 3936953.05   13.69 10.01 0.00 0.00  
Maximum of Months 1057289.28 4842844.12   14.89 10.78 0.00 0.00  



Table of Contents

Report: CondLoopDemandReportMonthly

For: SINGLE WATER PLANT LOOP

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 372092.91 883334.89 02-JAN-15:00 35.83 31.07 0.00 0.00 01-JAN-00:05
February 650404.24 1112972.66 11-FEB-14:00 40.29 32.82 0.00 0.00 01-FEB-00:10
March 899452.20 1365517.88 13-MAR-16:00 45.14 34.38 0.00 0.00 01-MAR-00:10
April 1256394.82 1720219.78 17-APR-15:00 51.90 38.47 0.00 0.00 01-APR-00:02
May 731222.96 1172860.69 22-MAY-13:10 41.44 36.56 0.00 0.00 01-MAY-00:05
June 1031768.97 1268882.83 11-JUN-13:00 43.29 35.70 0.00 0.00 01-JUN-00:02
July 1285738.76 1708633.03 29-JUL-16:00 51.68 40.72 0.00 0.00 01-JUL-00:03
August 1493976.77 1828218.94 23-AUG-13:00 53.94 40.30 0.00 0.00 01-AUG-00:05
September 796325.86 1072559.21 20-SEP-16:00 39.51 34.50 0.00 0.00 01-SEP-00:03
October 953733.98 1278582.14 03-OCT-15:00 43.48 35.42 0.00 0.00 01-OCT-00:03
November 1016281.13 1397194.29 17-NOV-15:00 45.75 34.98 0.00 0.00 01-NOV-00:10
December 1040701.27 1535257.57 10-DEC-14:59 48.38 35.08 0.00 0.00 01-DEC-00:10
                 
Annual Sum or Average 962517.61         0.00    
Minimum of Months 372092.91 883334.89   35.83 31.07 0.00 0.00  
Maximum of Months 1493976.77 1828218.94   53.94 40.72 0.00 0.00  



Table of Contents

Report: CondLoopDemandReportMonthly

For: SWHSYS1

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 0.00 0.00 01-JAN-00:05 57.80 57.80 11593.96 37891.82 18-JAN-13:00
February 0.00 0.00 01-FEB-00:10 57.67 57.67 11557.11 37783.78 01-FEB-12:40
March 0.00 0.00 01-MAR-00:10 57.50 57.50 11853.01 37047.62 01-MAR-12:20
April 0.00 0.00 01-APR-00:02 57.68 57.68 10743.33 35478.89 03-APR-11:30
May 0.00 0.00 01-MAY-00:05 57.56 57.56 10579.74 33923.17 01-MAY-11:50
June 0.00 0.00 01-JUN-00:02 57.83 57.83 10423.15 32401.89 01-JUN-12:00
July 0.00 0.00 01-JUL-00:03 58.12 58.12 9558.97 31450.61 03-JUL-11:30
August 0.00 0.00 01-AUG-00:05 57.96 57.96 10438.09 32163.19 31-AUG-11:20
September 0.00 0.00 01-SEP-00:03 57.09 57.09 10197.47 33515.92 29-SEP-11:40
October 0.00 0.00 01-OCT-00:03 57.00 57.00 10635.55 35244.88 31-OCT-11:30
November 0.00 0.00 01-NOV-00:10 56.86 56.86 11229.96 36773.88 30-NOV-12:40
December 0.00 0.00 01-DEC-00:10 56.86 56.86 11211.50 37678.73 28-DEC-13:00
                 
Annual Sum or Average 0.00         10831.26    
Minimum of Months 0.00 0.00   56.86 56.86 9558.97 31450.61  
Maximum of Months 0.00 0.00   58.12 58.12 11853.01 37891.82  



Table of Contents

Report: CondLoopDemandReportMonthly

For: TOWERWATERSYS

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 692442.13 5768476.73 02-JAN-14:00 29.40 26.39 504.78 101845.20 25-JAN-09:00
February 856310.44 4457955.46 10-FEB-16:20 27.51 24.25 1008.39 171917.84 04-FEB-08:50
March 1050581.82 5376060.16 14-MAR-09:50 28.83 25.60 577.17 175626.41 16-MAR-05:40
April 1358338.36 5659709.06 14-APR-15:00 29.24 26.16 52.63 27656.03 02-APR-02:20
May 2175610.71 6442500.31 31-MAY-13:00 30.36 27.32 5.39 22654.81 07-MAY-24:00
June 2972889.95 6694093.39 28-JUN-11:50 30.73 27.55 0.00 0.00 01-JUN-00:02
July 3112700.34 7034522.74 25-JUL-16:00 31.22 27.94 0.00 0.00 01-JUL-00:03
August 3204280.14 7111879.69 21-AUG-16:00 31.33 28.02 0.00 0.00 01-AUG-00:05
September 2892129.02 6684830.96 22-SEP-17:00 30.71 27.72 0.00 0.00 01-SEP-00:03
October 2261221.20 7417011.64 04-OCT-05:04 31.77 27.75 0.17 1506.02 16-OCT-00:50
November 1612596.45 6272718.88 29-NOV-12:00 30.12 26.82 375.46 104778.24 12-NOV-23:10
December 881662.20 5026791.32 07-DEC-15:00 28.33 25.13 845.92 166847.41 15-DEC-07:00
                 
Annual Sum or Average 1928188.38         276.75    
Minimum of Months 692442.13 4457955.46   27.51 24.25 0.00 0.00  
Maximum of Months 3204280.14 7417011.64   31.77 28.02 1008.39 175626.41  



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: BASEMENT

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: CORE_BOTTOM

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: CORE_MID

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: CORE_TOP

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: GROUNDFLOOR_PLENUM

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00 0.00
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: MIDFLOOR_PLENUM

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00 0.00
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: TOPFLOOR_PLENUM

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00 0.00
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: DATACENTER_MID_ZN_6

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: VAV_BOT WITH REHEAT

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 2362444.28 0.00 0.103057E+12 0.476305E+10 0.00 0.00
February 22819736.14 0.00 0.114866E+12 0.503206E+10 0.00 0.00
March 7520453.92 0.00 0.157143E+12 0.646833E+10 0.00 0.00
April 0.00 0.00 0.188351E+12 0.707909E+10 0.00 0.00
May 0.00 0.00 0.203682E+12 0.671205E+10 0.00 0.00
June 0.00 0.00 0.229803E+12 0.736381E+10 0.00 0.00
July 0.00 0.00 0.248806E+12 0.808964E+10 0.00 0.00
August 0.00 0.00 0.264772E+12 0.907733E+10 0.00 0.00
September 0.00 0.00 0.218780E+12 0.692893E+10 0.00 0.00
October 0.00 0.00 0.213335E+12 0.719731E+10 0.00 0.00
November 164352.20 0.00 0.179437E+12 0.662022E+10 0.00 0.00
December 11511603.16 0.00 0.142038E+12 0.600621E+10 0.00 0.00
             
Annual Sum or Average 44378589.71 0.00 0.226407E+13 0.813380E+11 0.00 0.00
Minimum of Months 0.00 0.00 0.103057E+12 0.476305E+10 0.00 0.00
Maximum of Months 22819736.14 0.00 0.264772E+12 0.907733E+10 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: VAV_MID WITH REHEAT

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.237855E+10 0.00 0.851841E+12 0.372713E+11 0.00 0.00
February 0.289377E+10 0.00 0.925583E+12 0.370415E+11 0.00 0.00
March 0.134761E+10 0.00 0.115938E+13 0.461309E+11 0.00 0.00
April 0.00 0.00 0.136184E+13 0.486238E+11 0.00 0.00
May 0.00 0.00 0.177990E+13 0.581987E+11 0.00 0.00
June 0.00 0.00 0.194752E+13 0.610592E+11 0.00 0.00
July 0.00 0.00 0.200966E+13 0.623808E+11 0.00 0.00
August 0.00 0.00 0.202869E+13 0.631200E+11 0.00 0.00
September 0.00 0.00 0.194079E+13 0.599828E+11 0.00 0.00
October 0.00 0.00 0.174324E+13 0.577734E+11 0.00 0.00
November 0.354004E+09 0.00 0.137180E+13 0.476024E+11 0.00 0.00
December 0.290149E+10 0.00 0.943657E+12 0.390899E+11 0.00 0.00
             
Annual Sum or Average 0.987543E+10 0.00 0.180639E+14 0.618275E+12 0.00 0.00
Minimum of Months 0.00 0.00 0.851841E+12 0.370415E+11 0.00 0.00
Maximum of Months 0.290149E+10 0.00 0.202869E+13 0.631200E+11 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: VAV_TOP WITH REHEAT

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.109975E+10 0.00 0.826114E+11 0.344603E+10 0.00 0.00
February 0.887856E+09 0.00 0.946209E+11 0.357265E+10 0.00 0.00
March 0.563192E+09 0.00 0.121313E+12 0.455441E+10 0.00 0.00
April 182403.44 0.00 0.146014E+12 0.503629E+10 0.00 0.00
May 0.00 0.00 0.191148E+12 0.625942E+10 0.00 0.00
June 0.00 0.00 0.210404E+12 0.660097E+10 0.00 0.00
July 0.00 0.00 0.218686E+12 0.685507E+10 0.00 0.00
August 0.00 0.00 0.217048E+12 0.680805E+10 0.00 0.00
September 0.00 0.00 0.205579E+12 0.630795E+10 0.00 0.00
October 0.00 0.00 0.179149E+12 0.581501E+10 0.00 0.00
November 0.177040E+09 0.00 0.138899E+12 0.460452E+10 0.00 0.00
December 0.118466E+10 0.00 0.937344E+11 0.367236E+10 0.00 0.00
             
Annual Sum or Average 0.391268E+10 0.00 0.189920E+13 0.635327E+11 0.00 0.00
Minimum of Months 0.00 0.00 0.826114E+11 0.344603E+10 0.00 0.00
Maximum of Months 0.118466E+10 0.00 0.218686E+12 0.685507E+10 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: CAV_BAS

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.00 0.00 0.798334E+11 0.168521E+11 0.00 0.00
February 0.00 0.00 0.770349E+11 0.149587E+11 0.00 0.00
March 0.00 0.00 0.892622E+11 0.165852E+11 0.00 0.00
April 0.00 0.00 0.900736E+11 0.153607E+11 0.00 0.00
May 0.00 0.00 0.114136E+12 0.170495E+11 0.00 0.00
June 0.00 0.00 0.127747E+12 0.167602E+11 0.00 0.00
July 0.00 0.00 0.132089E+12 0.168016E+11 0.00 0.00
August 0.00 0.00 0.145293E+12 0.181435E+11 0.00 0.00
September 0.00 0.00 0.127968E+12 0.170742E+11 0.00 0.00
October 0.00 0.00 0.122846E+12 0.174756E+11 0.00 0.00
November 0.00 0.00 0.107035E+12 0.169946E+11 0.00 0.00
December 0.00 0.00 0.853396E+11 0.169079E+11 0.00 0.00
             
Annual Sum or Average 0.00 0.00 0.129866E+13 0.200964E+12 0.00 0.00
Minimum of Months 0.00 0.00 0.770349E+11 0.149587E+11 0.00 0.00
Maximum of Months 0.00 0.00 0.145293E+12 0.181435E+11 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: AIRLOOP DATACENTER BASEMENT

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.00 0.00 0.433909E+12 0.189252E+12 0.00 0.12
February 0.00 0.00 0.680482E+12 0.236345E+12 0.00 0.13
March 0.00 0.00 0.107371E+13 0.334287E+12 0.00 0.11
April 0.00 0.00 0.136349E+13 0.409850E+12 0.00 0.00
May 0.00 0.00 0.478346E+12 0.213202E+12 0.00 0.00
June 0.00 0.00 0.790871E+12 0.290782E+12 0.00 0.00
July 0.00 0.00 0.114896E+13 0.386113E+12 0.00 0.00
August 0.00 0.00 0.145377E+13 0.455956E+12 0.00 0.00
September 0.00 0.00 0.476511E+12 0.212063E+12 0.00 0.00
October 0.00 0.00 0.805963E+12 0.292386E+12 0.00 0.00
November 0.00 0.00 0.106491E+13 0.338736E+12 0.00 0.03
December 0.00 0.00 0.137683E+13 0.392496E+12 0.00 0.03
             
Annual Sum or Average 0.00 0.00 0.111478E+14 0.375147E+13 0.00 0.43
Minimum of Months 0.00 0.00 0.433909E+12 0.189252E+12 0.00 0.00
Maximum of Months 0.00 0.00 0.145377E+13 0.455956E+12 0.00 0.13



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: AIRLOOP DATACENTER BOT

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.00 0.00 0.736081E+10 0.302128E+10 0.00 0.00
February 0.00 0.00 0.129275E+11 0.412105E+10 0.00 0.00
March 0.00 0.00 0.210929E+11 0.607544E+10 0.00 0.00
April 0.00 0.00 0.273954E+11 0.771179E+10 0.00 0.00
May 0.00 0.00 0.931838E+10 0.368305E+10 0.00 0.00
June 0.00 0.00 0.159774E+11 0.531193E+10 0.00 0.00
July 0.00 0.00 0.233961E+11 0.724319E+10 0.00 0.00
August 0.00 0.00 0.302530E+11 0.892071E+10 0.00 0.00
September 0.00 0.00 0.940641E+10 0.369638E+10 0.00 0.00
October 0.00 0.00 0.160777E+11 0.528964E+10 0.00 0.00
November 0.00 0.00 0.211396E+11 0.621192E+10 0.00 0.00
December 0.00 0.00 0.271732E+11 0.725174E+10 0.00 0.00
             
Annual Sum or Average 0.00 0.00 0.221518E+12 0.685381E+11 0.00 0.00
Minimum of Months 0.00 0.00 0.736081E+10 0.302128E+10 0.00 0.00
Maximum of Months 0.00 0.00 0.302530E+11 0.892071E+10 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: AIRLOOP DATACENTER MID

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.00 0.00 0.600162E+11 0.267889E+11 0.00 0.00
February 0.00 0.00 0.116056E+12 0.378862E+11 0.00 0.00
March 0.00 0.00 0.197280E+12 0.572255E+11 0.00 0.00
April 0.00 0.00 0.260732E+12 0.734528E+11 0.00 0.00
May 0.00 0.00 0.873608E+11 0.347756E+11 0.00 0.00
June 0.00 0.00 0.152274E+12 0.506213E+11 0.00 0.00
July 0.00 0.00 0.223193E+12 0.690809E+11 0.00 0.00
August 0.00 0.00 0.287156E+12 0.847969E+11 0.00 0.00
September 0.00 0.00 0.878455E+11 0.348065E+11 0.00 0.00
October 0.00 0.00 0.152481E+12 0.502499E+11 0.00 0.00
November 0.00 0.00 0.198679E+12 0.586843E+11 0.00 0.00
December 0.00 0.00 0.252176E+12 0.679129E+11 0.00 0.00
             
Annual Sum or Average 0.00 0.00 0.207525E+13 0.646282E+12 0.00 0.00
Minimum of Months 0.00 0.00 0.600162E+11 0.267889E+11 0.00 0.00
Maximum of Months 0.00 0.00 0.287156E+12 0.847969E+11 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: AIRLOOP DATACENTER TOP

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.00 0.00 0.534022E+10 0.257740E+10 0.00 0.00
February 0.00 0.00 0.112398E+11 0.374706E+10 0.00 0.00
March 0.00 0.00 0.195430E+11 0.572520E+10 0.00 0.00
April 0.00 0.00 0.261071E+11 0.739305E+10 0.00 0.00
May 0.00 0.00 0.888761E+10 0.354359E+10 0.00 0.00
June 0.00 0.00 0.154063E+11 0.513584E+10 0.00 0.00
July 0.00 0.00 0.225570E+11 0.700047E+10 0.00 0.00
August 0.00 0.00 0.288922E+11 0.856265E+10 0.00 0.00
September 0.00 0.00 0.893106E+10 0.354566E+10 0.00 0.00
October 0.00 0.00 0.152703E+11 0.506388E+10 0.00 0.00
November 0.00 0.00 0.196417E+11 0.586097E+10 0.00 0.00
December 0.00 0.00 0.247519E+11 0.674640E+10 0.00 0.00
             
Annual Sum or Average 0.00 0.00 0.206568E+12 0.649022E+11 0.00 0.00
Minimum of Months 0.00 0.00 0.534022E+10 0.257740E+10 0.00 0.00
Maximum of Months 0.00 0.00 0.288922E+11 0.856265E+10 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: VAV_BOT WITH REHEAT

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.476305E+10 0.103057E+12 2362444.28 35237215.19 0.492381E+10 0.00 0.00 0.00
February 0.503206E+10 0.114866E+12 22819736.14 0.705324E+09 0.624516E+10 0.00 0.00 0.00
March 0.646833E+10 0.157143E+12 7520453.92 0.106256E+09 0.976400E+10 0.00 0.00 0.00
April 0.707909E+10 0.188351E+12 0.00 0.00 0.205083E+11 0.00 0.00 0.00
May 0.671205E+10 0.203682E+12 0.00 0.00 0.494915E+11 0.00 0.00 0.00
June 0.736381E+10 0.229803E+12 0.00 0.00 0.827486E+11 0.00 0.00 0.00
July 0.808964E+10 0.248806E+12 0.00 0.00 0.937386E+11 0.00 0.00 0.00
August 0.907733E+10 0.264772E+12 0.00 0.00 0.984822E+11 0.00 0.00 0.00
September 0.692893E+10 0.218780E+12 0.00 0.00 0.716548E+11 0.00 0.00 0.00
October 0.719731E+10 0.213335E+12 0.00 0.00 0.549662E+11 0.00 0.00 0.00
November 0.662022E+10 0.179437E+12 164352.20 4960881.93 0.326405E+11 0.00 0.00 0.00
December 0.600621E+10 0.142038E+12 11511603.16 60326906.27 0.930091E+10 0.00 0.00 0.00
                 
Annual Sum or Average 0.813380E+11 0.226407E+13 44378589.71 0.912105E+09 0.534465E+12 0.00 0.00 0.00
Minimum of Months 0.476305E+10 0.103057E+12 0.00 0.00 0.492381E+10 0.00 0.00 0.00
Maximum of Months 0.907733E+10 0.264772E+12 22819736.14 0.705324E+09 0.984822E+11 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: VAV_MID WITH REHEAT

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.372713E+11 0.851841E+12 0.237855E+10 0.370783E+09 0.569078E+11 0.00 0.00 0.00
February 0.370415E+11 0.925583E+12 0.289377E+10 0.787084E+10 0.666160E+11 0.00 0.00 0.00
March 0.461309E+11 0.115938E+13 0.134761E+10 0.183987E+10 0.100608E+12 0.00 0.00 0.00
April 0.486238E+11 0.136184E+13 0.00 0.00 0.199628E+12 0.00 0.00 0.00
May 0.581987E+11 0.177990E+13 0.00 0.00 0.479713E+12 0.00 0.00 0.00
June 0.610592E+11 0.194752E+13 0.00 0.00 0.745201E+12 0.00 0.00 0.00
July 0.623808E+11 0.200966E+13 0.00 0.00 0.846333E+12 0.00 0.00 0.00
August 0.631200E+11 0.202869E+13 0.00 0.00 0.831854E+12 0.00 0.00 0.00
September 0.599828E+11 0.194079E+13 0.00 0.00 0.681736E+12 0.00 0.00 0.00
October 0.577734E+11 0.174324E+13 0.00 0.00 0.505366E+12 0.00 0.00 0.00
November 0.476024E+11 0.137180E+13 0.354004E+09 0.164878E+09 0.297263E+12 0.00 0.00 0.00
December 0.390899E+11 0.943657E+12 0.290149E+10 0.116203E+10 0.977172E+11 0.00 0.00 0.00
                 
Annual Sum or Average 0.618275E+12 0.180639E+14 0.987543E+10 0.114084E+11 0.490894E+13 0.00 0.00 0.00
Minimum of Months 0.370415E+11 0.851841E+12 0.00 0.00 0.569078E+11 0.00 0.00 0.00
Maximum of Months 0.631200E+11 0.202869E+13 0.290149E+10 0.787084E+10 0.846333E+12 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: VAV_TOP WITH REHEAT

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.344603E+10 0.826114E+11 0.109975E+10 75819374.44 0.525047E+10 0.00 0.00 0.00
February 0.357265E+10 0.946209E+11 0.887856E+09 0.672974E+09 0.540355E+10 0.00 0.00 0.00
March 0.455441E+10 0.121313E+12 0.563192E+09 0.197508E+09 0.757496E+10 0.00 0.00 0.00
April 0.503629E+10 0.146014E+12 182403.44 0.00 0.167917E+11 0.00 0.00 0.00
May 0.625942E+10 0.191148E+12 0.00 0.00 0.464404E+11 0.00 0.00 0.00
June 0.660097E+10 0.210404E+12 0.00 0.00 0.726883E+11 0.00 0.00 0.00
July 0.685507E+10 0.218686E+12 0.00 0.00 0.822588E+11 0.00 0.00 0.00
August 0.680805E+10 0.217048E+12 0.00 0.00 0.817653E+11 0.00 0.00 0.00
September 0.630795E+10 0.205579E+12 0.00 0.00 0.673682E+11 0.00 0.00 0.00
October 0.581501E+10 0.179149E+12 0.00 0.00 0.508731E+11 0.00 0.00 0.00
November 0.460452E+10 0.138899E+12 0.177040E+09 39845714.58 0.295018E+11 0.00 0.00 0.00
December 0.367236E+10 0.937344E+11 0.118466E+10 0.175504E+09 0.876651E+10 0.00 0.00 0.00
                 
Annual Sum or Average 0.635327E+11 0.189920E+13 0.391268E+10 0.116165E+10 0.474683E+12 0.00 0.00 0.00
Minimum of Months 0.344603E+10 0.826114E+11 0.00 0.00 0.525047E+10 0.00 0.00 0.00
Maximum of Months 0.685507E+10 0.218686E+12 0.118466E+10 0.672974E+09 0.822588E+11 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: CAV_BAS

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.168521E+11 0.798334E+11 0.00 0.00 0.00 0.00 0.00 0.00
February 0.149587E+11 0.770349E+11 0.00 0.00 0.00 0.00 0.00 0.00
March 0.165852E+11 0.892622E+11 0.00 0.00 0.00 0.00 0.00 0.00
April 0.153607E+11 0.900736E+11 0.00 0.00 0.00 0.00 0.00 0.00
May 0.170495E+11 0.114136E+12 0.00 0.00 0.00 0.00 0.00 0.00
June 0.167602E+11 0.127747E+12 0.00 0.00 0.00 0.00 0.00 0.00
July 0.168016E+11 0.132089E+12 0.00 0.00 0.00 0.00 0.00 0.00
August 0.181435E+11 0.145293E+12 0.00 0.00 0.00 0.00 0.00 0.00
September 0.170742E+11 0.127968E+12 0.00 0.00 0.00 0.00 0.00 0.00
October 0.174756E+11 0.122846E+12 0.00 0.00 0.00 0.00 0.00 0.00
November 0.169946E+11 0.107035E+12 0.00 0.00 0.00 0.00 0.00 0.00
December 0.169079E+11 0.853396E+11 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.200964E+12 0.129866E+13 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.149587E+11 0.770349E+11 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.181435E+11 0.145293E+12 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: AIRLOOP DATACENTER BASEMENT

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.951635E+11 0.340157E+12 0.00 0.00 0.00 0.334510E+09 0.00 0.00
February 0.859541E+11 0.530443E+12 0.00 0.00 0.00 0.350608E+09 0.00 0.00
March 0.951635E+11 0.834877E+12 0.00 0.00 0.00 0.293459E+09 0.00 0.00
April 0.920937E+11 0.104574E+13 0.00 0.00 0.00 0.00 0.00 0.00
May 0.951635E+11 0.360308E+12 0.00 0.00 0.00 0.00 0.00 0.00
June 0.920937E+11 0.592182E+12 0.00 0.00 0.00 0.00 0.00 0.00
July 0.951635E+11 0.858013E+12 0.00 0.00 0.00 0.00 0.00 0.00
August 0.951635E+11 0.109298E+13 0.00 0.00 0.00 0.00 0.00 0.00
September 0.920937E+11 0.356542E+12 0.00 0.00 0.00 0.00 0.00 0.00
October 0.951635E+11 0.608741E+12 0.00 0.00 0.00 0.00 0.00 0.00
November 0.920937E+11 0.818361E+12 0.00 0.00 0.00 89306177.20 0.00 0.00
December 0.951635E+11 0.107957E+13 0.00 0.00 0.00 71787272.63 0.00 0.00
                 
Annual Sum or Average 0.112047E+13 0.851791E+13 0.00 0.00 0.00 0.113967E+10 0.00 0.00
Minimum of Months 0.859541E+11 0.340157E+12 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.951635E+11 0.109298E+13 0.00 0.00 0.00 0.350608E+09 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: AIRLOOP DATACENTER BOT

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.144032E+10 0.577985E+10 0.00 0.00 0.00 0.00 0.00 0.00
February 0.130093E+10 0.101074E+11 0.00 0.00 0.00 0.00 0.00 0.00
March 0.144032E+10 0.164577E+11 0.00 0.00 0.00 0.00 0.00 0.00
April 0.139386E+10 0.210775E+11 0.00 0.00 0.00 0.00 0.00 0.00
May 0.144032E+10 0.707565E+10 0.00 0.00 0.00 0.00 0.00 0.00
June 0.139386E+10 0.120593E+11 0.00 0.00 0.00 0.00 0.00 0.00
July 0.144032E+10 0.175933E+11 0.00 0.00 0.00 0.00 0.00 0.00
August 0.144032E+10 0.227726E+11 0.00 0.00 0.00 0.00 0.00 0.00
September 0.139386E+10 0.710388E+10 0.00 0.00 0.00 0.00 0.00 0.00
October 0.144032E+10 0.122284E+11 0.00 0.00 0.00 0.00 0.00 0.00
November 0.139386E+10 0.163215E+11 0.00 0.00 0.00 0.00 0.00 0.00
December 0.144032E+10 0.213617E+11 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.169586E+11 0.169939E+12 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.130093E+10 0.577985E+10 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.144032E+10 0.227726E+11 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: AIRLOOP DATACENTER MID

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.137355E+11 0.469627E+11 0.00 0.00 0.00 0.00 0.00 0.00
February 0.124062E+11 0.905764E+11 0.00 0.00 0.00 0.00 0.00 0.00
March 0.137355E+11 0.153790E+12 0.00 0.00 0.00 0.00 0.00 0.00
April 0.132924E+11 0.200571E+12 0.00 0.00 0.00 0.00 0.00 0.00
May 0.137355E+11 0.663207E+11 0.00 0.00 0.00 0.00 0.00 0.00
June 0.132924E+11 0.114946E+12 0.00 0.00 0.00 0.00 0.00 0.00
July 0.137355E+11 0.167848E+12 0.00 0.00 0.00 0.00 0.00 0.00
August 0.137355E+11 0.216094E+12 0.00 0.00 0.00 0.00 0.00 0.00
September 0.132924E+11 0.663314E+11 0.00 0.00 0.00 0.00 0.00 0.00
October 0.137355E+11 0.115966E+12 0.00 0.00 0.00 0.00 0.00 0.00
November 0.132924E+11 0.153287E+12 0.00 0.00 0.00 0.00 0.00 0.00
December 0.137355E+11 0.197998E+12 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.161724E+12 0.159069E+13 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.124062E+11 0.469627E+11 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.137355E+11 0.216094E+12 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: AIRLOOP DATACENTER TOP

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.140078E+10 0.416360E+10 0.00 0.00 0.00 0.00 0.00 0.00
February 0.126522E+10 0.875792E+10 0.00 0.00 0.00 0.00 0.00 0.00
March 0.140078E+10 0.152186E+11 0.00 0.00 0.00 0.00 0.00 0.00
April 0.135559E+10 0.200696E+11 0.00 0.00 0.00 0.00 0.00 0.00
May 0.140078E+10 0.674479E+10 0.00 0.00 0.00 0.00 0.00 0.00
June 0.135559E+10 0.116261E+11 0.00 0.00 0.00 0.00 0.00 0.00
July 0.140078E+10 0.169573E+11 0.00 0.00 0.00 0.00 0.00 0.00
August 0.140078E+10 0.217303E+11 0.00 0.00 0.00 0.00 0.00 0.00
September 0.135559E+10 0.674099E+10 0.00 0.00 0.00 0.00 0.00 0.00
October 0.140078E+10 0.116072E+11 0.00 0.00 0.00 0.00 0.00 0.00
November 0.135559E+10 0.151363E+11 0.00 0.00 0.00 0.00 0.00 0.00
December 0.140078E+10 0.194063E+11 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.164930E+11 0.158159E+12 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.126522E+10 0.416360E+10 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.140078E+10 0.217303E+11 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: VAV_BOT WITH REHEAT

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.476305E+10 2362444.28 0.103057E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.503206E+10 22819736.14 0.114866E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.646833E+10 7520453.92 0.157143E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.707909E+10 0.00 0.188351E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.671205E+10 0.00 0.203682E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.736381E+10 0.00 0.229803E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.808964E+10 0.00 0.248806E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.907733E+10 0.00 0.264772E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.692893E+10 0.00 0.218780E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.719731E+10 0.00 0.213335E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.662022E+10 164352.20 0.179437E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.600621E+10 11511603.16 0.142038E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.813380E+11 44378589.71 0.226407E+13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.476305E+10 0.00 0.103057E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.907733E+10 22819736.14 0.264772E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: VAV_MID WITH REHEAT

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.372713E+11 0.237855E+10 0.851841E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.370415E+11 0.289377E+10 0.925583E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.461309E+11 0.134761E+10 0.115938E+13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.486238E+11 0.00 0.136184E+13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.581987E+11 0.00 0.177990E+13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.610592E+11 0.00 0.194752E+13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.623808E+11 0.00 0.200966E+13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.631200E+11 0.00 0.202869E+13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.599828E+11 0.00 0.194079E+13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.577734E+11 0.00 0.174324E+13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.476024E+11 0.354004E+09 0.137180E+13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.390899E+11 0.290149E+10 0.943657E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.618275E+12 0.987543E+10 0.180639E+14 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.370415E+11 0.00 0.851841E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.631200E+11 0.290149E+10 0.202869E+13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: VAV_TOP WITH REHEAT

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.344603E+10 0.109975E+10 0.826114E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.357265E+10 0.887856E+09 0.946209E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.455441E+10 0.563192E+09 0.121313E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.503629E+10 182403.44 0.146014E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.625942E+10 0.00 0.191148E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.660097E+10 0.00 0.210404E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.685507E+10 0.00 0.218686E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.680805E+10 0.00 0.217048E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.630795E+10 0.00 0.205579E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.581501E+10 0.00 0.179149E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.460452E+10 0.177040E+09 0.138899E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.367236E+10 0.118466E+10 0.937344E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.635327E+11 0.391268E+10 0.189920E+13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.344603E+10 0.00 0.826114E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.685507E+10 0.118466E+10 0.218686E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: CAV_BAS

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.168521E+11 0.00 0.798334E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.149587E+11 0.00 0.770349E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.165852E+11 0.00 0.892622E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.153607E+11 0.00 0.900736E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.170495E+11 0.00 0.114136E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.167602E+11 0.00 0.127747E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.168016E+11 0.00 0.132089E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.181435E+11 0.00 0.145293E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.170742E+11 0.00 0.127968E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.174756E+11 0.00 0.122846E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.169946E+11 0.00 0.107035E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.169079E+11 0.00 0.853396E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.200964E+12 0.00 0.129866E+13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.149587E+11 0.00 0.770349E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.181435E+11 0.00 0.145293E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: AIRLOOP DATACENTER BASEMENT

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.951635E+11 0.00 0.433909E+12 0.00 0.937524E+11 0.00 0.00 0.00 0.336016E+09 0.00 0.00 0.00
February 0.859541E+11 0.00 0.680482E+12 0.00 0.150039E+12 0.00 0.00 0.00 0.352186E+09 0.00 0.00 0.00
March 0.951635E+11 0.00 0.107371E+13 0.00 0.238828E+12 0.00 0.00 0.00 0.294780E+09 0.00 0.00 0.00
April 0.920937E+11 0.00 0.136349E+13 0.00 0.317757E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.951635E+11 0.00 0.478346E+12 0.00 0.118038E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.920937E+11 0.00 0.790871E+12 0.00 0.198689E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.951635E+11 0.00 0.114896E+13 0.00 0.290949E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.951635E+11 0.00 0.145377E+13 0.00 0.360792E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.920937E+11 0.00 0.476511E+12 0.00 0.119969E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.951635E+11 0.00 0.805963E+12 0.00 0.197222E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.920937E+11 0.00 0.106491E+13 0.00 0.246553E+12 0.00 0.00 0.00 89708180.50 0.00 0.00 0.00
December 0.951635E+11 0.00 0.137683E+13 0.00 0.297260E+12 0.00 0.00 0.00 72110416.25 0.00 0.00 0.00
                         
Annual Sum or Average 0.112047E+13 0.00 0.111478E+14 0.00 0.262985E+13 0.00 0.00 0.00 0.114480E+10 0.00 0.00 0.00
Minimum of Months 0.859541E+11 0.00 0.433909E+12 0.00 0.937524E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.951635E+11 0.00 0.145377E+13 0.00 0.360792E+12 0.00 0.00 0.00 0.352186E+09 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: AIRLOOP DATACENTER BOT

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.144032E+10 0.00 0.736081E+10 0.00 0.158096E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.130093E+10 0.00 0.129275E+11 0.00 0.282012E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.144032E+10 0.00 0.210929E+11 0.00 0.463512E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.139386E+10 0.00 0.273954E+11 0.00 0.631793E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.144032E+10 0.00 0.931838E+10 0.00 0.224273E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.139386E+10 0.00 0.159774E+11 0.00 0.391807E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.144032E+10 0.00 0.233961E+11 0.00 0.580287E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.144032E+10 0.00 0.302530E+11 0.00 0.748039E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.139386E+10 0.00 0.940641E+10 0.00 0.230253E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.144032E+10 0.00 0.160777E+11 0.00 0.384932E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.139386E+10 0.00 0.211396E+11 0.00 0.481807E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.144032E+10 0.00 0.271732E+11 0.00 0.581142E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.169586E+11 0.00 0.221518E+12 0.00 0.515795E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.130093E+10 0.00 0.736081E+10 0.00 0.158096E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.144032E+10 0.00 0.302530E+11 0.00 0.748039E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: AIRLOOP DATACENTER MID

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.137355E+11 0.00 0.600162E+11 0.00 0.130534E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.124062E+11 0.00 0.116056E+12 0.00 0.254800E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.137355E+11 0.00 0.197280E+12 0.00 0.434901E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.132924E+11 0.00 0.260732E+12 0.00 0.601605E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.137355E+11 0.00 0.873608E+11 0.00 0.210401E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.132924E+11 0.00 0.152274E+12 0.00 0.373289E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.137355E+11 0.00 0.223193E+12 0.00 0.553454E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.137355E+11 0.00 0.287156E+12 0.00 0.710614E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.132924E+11 0.00 0.878455E+11 0.00 0.215141E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.137355E+11 0.00 0.152481E+12 0.00 0.365144E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.132924E+11 0.00 0.198679E+12 0.00 0.453920E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.137355E+11 0.00 0.252176E+12 0.00 0.541774E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.161724E+12 0.00 0.207525E+13 0.00 0.484558E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.124062E+11 0.00 0.600162E+11 0.00 0.130534E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.137355E+11 0.00 0.287156E+12 0.00 0.710614E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: AIRLOOP DATACENTER TOP

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.140078E+10 0.00 0.534022E+10 0.00 0.117662E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.126522E+10 0.00 0.112398E+11 0.00 0.248185E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.140078E+10 0.00 0.195430E+11 0.00 0.432443E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.135559E+10 0.00 0.261071E+11 0.00 0.603746E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.140078E+10 0.00 0.888761E+10 0.00 0.214281E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.135559E+10 0.00 0.154063E+11 0.00 0.378024E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.140078E+10 0.00 0.225570E+11 0.00 0.559969E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.140078E+10 0.00 0.288922E+11 0.00 0.716188E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.135559E+10 0.00 0.893106E+10 0.00 0.219007E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.140078E+10 0.00 0.152703E+11 0.00 0.366310E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.135559E+10 0.00 0.196417E+11 0.00 0.450538E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.140078E+10 0.00 0.247519E+11 0.00 0.534562E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.164930E+11 0.00 0.206568E+12 0.00 0.484091E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.126522E+10 0.00 0.534022E+10 0.00 0.117662E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.140078E+10 0.00 0.288922E+11 0.00 0.716188E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: BASEMENT

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.102473E+10 0.420849E+10 0.00 99770668.37 25854211.25 0.00 0.126333E+11 0.00 0.40
February 0.681977E+09 0.464362E+10 0.00 82632080.72 75904071.23 0.00 0.668461E+10 0.00 0.39
March 0.141482E+09 0.709588E+10 0.00 75866858.59 69043224.13 0.00 0.793133E+10 0.00 0.39
April 0.117770E+09 0.100487E+11 0.00 41500994.92 0.155738E+09 0.00 0.210780E+10 0.00 0.38
May 91514295.39 0.258436E+11 0.00 5535093.64 0.429142E+09 0.00 0.174818E+09 0.00 0.40
June 0.00 0.396609E+11 0.00 0.00 0.594467E+09 0.00 0.00 0.00 0.41
July 473253.27 0.436971E+11 0.00 622886.17 0.781116E+09 0.00 3164782.96 0.00 0.40
August 427902.60 0.471247E+11 0.00 318410.45 0.781396E+09 0.00 4521322.15 0.00 0.43
September 3900344.96 0.392044E+11 0.00 2443626.88 0.749344E+09 0.00 45661228.52 0.00 0.42
October 16831771.29 0.299027E+11 0.00 8876922.21 0.485664E+09 0.00 0.123894E+09 0.00 0.42
November 0.955550E+09 0.190291E+11 0.00 50912314.65 0.251638E+09 0.00 0.327382E+10 0.00 0.42
December 0.456493E+09 0.607679E+10 0.00 99920133.87 0.139925E+09 0.00 0.106272E+11 0.00 0.40
                   
Annual Sum or Average 0.349115E+10 0.276536E+12 0.00 0.468400E+09 0.453923E+10 0.00 0.436101E+11 0.00 0.40
Minimum of Months 0.00 0.420849E+10 0.00 0.00 25854211.25 0.00 0.00 0.00 0.38
Maximum of Months 0.102473E+10 0.471247E+11 0.00 99920133.87 0.781396E+09 0.00 0.126333E+11 0.00 0.43



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: CORE_BOTTOM

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.157228E+10 0.813587E+10 0.00 49808943.69 0.124320E+10 0.00 0.117741E+11 0.00 0.51
February 0.913977E+09 0.935037E+10 0.00 39507029.04 0.119260E+10 0.00 0.632252E+10 0.00 0.52
March 0.603912E+09 0.127637E+11 0.00 45028117.02 0.651907E+10 0.00 0.883446E+10 0.00 0.61
April 0.529646E+09 0.139557E+11 0.00 13125074.21 0.104753E+11 0.00 0.163008E+10 0.00 0.68
May 0.00 0.221029E+11 0.00 0.00 0.114298E+11 0.00 0.00 0.00 0.60
June 0.00 0.260468E+11 0.00 0.00 0.155661E+11 0.00 0.00 0.00 0.66
July 0.00 0.249689E+11 0.00 0.00 0.214146E+11 0.00 0.00 0.00 0.69
August 0.00 0.285087E+11 0.00 0.00 0.203901E+11 0.00 0.00 0.00 0.72
September 0.00 0.274837E+11 0.00 0.00 0.139101E+11 0.00 0.00 0.00 0.62
October 0.00 0.228148E+11 0.00 0.00 0.139218E+11 0.00 0.00 0.00 0.62
November 0.957533E+09 0.178193E+11 0.00 14676404.19 0.898139E+10 0.00 0.154786E+10 0.00 0.60
December 0.521695E+09 0.908293E+10 0.00 54121420.06 0.903047E+10 0.00 0.115112E+11 0.00 0.60
                   
Annual Sum or Average 0.509904E+10 0.223034E+12 0.00 0.216267E+09 0.134075E+12 0.00 0.416202E+11 0.00 0.62
Minimum of Months 0.00 0.813587E+10 0.00 0.00 0.119260E+10 0.00 0.00 0.00 0.51
Maximum of Months 0.157228E+10 0.285087E+11 0.00 54121420.06 0.214146E+11 0.00 0.117741E+11 0.00 0.72



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: CORE_MID

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.437959E+11 0.641975E+11 0.00 0.263131E+09 0.199212E+11 0.00 0.704733E+11 0.00 0.48
February 0.231958E+11 0.732835E+11 0.00 0.192276E+09 0.191958E+11 0.00 0.381735E+11 0.00 0.49
March 0.218132E+11 0.109478E+12 0.00 0.226286E+09 0.232271E+11 0.00 0.595067E+11 0.00 0.51
April 0.126221E+10 0.124066E+12 0.00 92573245.86 0.419878E+11 0.00 0.155810E+11 0.00 0.52
May 0.00 0.198054E+12 0.00 33772.60 0.736087E+11 0.00 0.00 0.00 0.54
June 0.00 0.241493E+12 0.00 0.00 0.907175E+11 0.00 0.00 0.00 0.57
July 0.00 0.228818E+12 0.00 0.00 0.126098E+12 0.00 0.00 0.00 0.57
August 0.00 0.259184E+12 0.00 0.00 0.101213E+12 0.00 0.00 0.00 0.57
September 0.00 0.252091E+12 0.00 0.00 0.101782E+12 0.00 0.00 0.00 0.56
October 0.00 0.209880E+12 0.00 0.00 0.658481E+11 0.00 0.00 0.00 0.52
November 0.800012E+10 0.162733E+12 0.00 82995059.85 0.305251E+11 0.00 0.102932E+11 0.00 0.49
December 0.282399E+11 0.664498E+11 0.00 0.256540E+09 0.390249E+11 0.00 0.754536E+11 0.00 0.48
                   
Annual Sum or Average 0.126307E+12 0.198973E+13 0.00 0.111383E+10 0.733150E+12 0.00 0.269481E+12 0.00 0.53
Minimum of Months 0.00 0.641975E+11 0.00 0.00 0.191958E+11 0.00 0.00 0.00 0.48
Maximum of Months 0.437959E+11 0.259184E+12 0.00 0.263131E+09 0.126098E+12 0.00 0.754536E+11 0.00 0.57



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: CORE_TOP

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.602214E+10 0.470779E+10 0.00 13692712.46 0.347875E+10 0.00 0.408862E+10 0.00 0.47
February 0.265568E+10 0.665788E+10 0.00 13206028.96 0.271477E+10 0.00 0.253419E+10 0.00 0.47
March 0.331447E+10 0.109209E+11 0.00 15856473.84 0.300419E+10 0.00 0.407310E+10 0.00 0.51
April 0.234169E+09 0.120194E+11 0.00 7415349.60 0.510905E+10 0.00 0.132864E+10 0.00 0.52
May 0.00 0.197135E+11 0.00 54587.26 0.652822E+10 0.00 0.00 0.00 0.55
June 0.00 0.245903E+11 0.00 0.00 0.842483E+10 0.00 0.00 0.00 0.58
July 0.00 0.234565E+11 0.00 0.00 0.117024E+11 0.00 0.00 0.00 0.58
August 0.00 0.259404E+11 0.00 0.00 0.931836E+10 0.00 0.00 0.00 0.58
September 0.00 0.249751E+11 0.00 0.00 0.936906E+10 0.00 0.00 0.00 0.57
October 0.00 0.189051E+11 0.00 0.00 0.712391E+10 0.00 0.00 0.00 0.52
November 0.106327E+10 0.144014E+11 0.00 4924943.70 0.443345E+10 0.00 0.467358E+09 0.00 0.49
December 0.458790E+10 0.578836E+10 0.00 13025853.27 0.484052E+10 0.00 0.452869E+10 0.00 0.48
                   
Annual Sum or Average 0.178776E+11 0.192077E+12 0.00 68175949.09 0.760475E+11 0.00 0.170206E+11 0.00 0.53
Minimum of Months 0.00 0.470779E+10 0.00 0.00 0.271477E+10 0.00 0.00 0.00 0.47
Maximum of Months 0.602214E+10 0.259404E+11 0.00 15856473.84 0.117024E+11 0.00 0.452869E+10 0.00 0.58



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.104172E+10 0.972827E+09 0.00 1506208.53 0.190579E+09 0.00 0.345559E+09 0.00 0.46
February 0.508199E+09 0.124141E+10 0.00 2108671.86 0.170791E+09 0.00 0.277056E+09 0.00 0.51
March 0.561680E+09 0.181448E+10 0.00 2083526.89 0.837056E+09 0.00 0.378036E+09 0.00 0.62
April 88547271.98 0.214781E+10 0.00 1292275.11 0.132530E+10 0.00 0.172658E+09 0.00 0.77
May 0.00 0.407869E+10 0.00 0.00 0.137106E+10 0.00 0.00 0.00 0.81
June 0.00 0.543213E+10 0.00 0.00 0.183182E+10 0.00 0.00 0.00 0.94
July 0.00 0.546766E+10 0.00 0.00 0.246374E+10 0.00 0.00 0.00 0.95
August 0.00 0.543084E+10 0.00 0.00 0.241094E+10 0.00 0.00 0.00 0.93
September 0.00 0.499337E+10 0.00 0.00 0.166647E+10 0.00 0.00 0.00 0.81
October 0.00 0.348708E+10 0.00 0.00 0.177341E+10 0.00 0.00 0.00 0.73
November 0.198759E+09 0.253642E+10 0.00 814144.96 0.115153E+10 0.00 71191640.06 0.00 0.64
December 0.699708E+09 0.118541E+10 0.00 2179551.94 0.115048E+10 0.00 0.487326E+09 0.00 0.56
                   
Annual Sum or Average 0.309861E+10 0.387881E+11 0.00 9984379.29 0.163432E+11 0.00 0.173183E+10 0.00 0.73
Minimum of Months 0.00 0.972827E+09 0.00 0.00 0.170791E+09 0.00 0.00 0.00 0.46
Maximum of Months 0.104172E+10 0.546766E+10 0.00 2179551.94 0.246374E+10 0.00 0.487326E+09 0.00 0.95



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.773462E+09 0.792881E+09 0.00 2631284.97 0.237332E+09 0.00 0.589775E+09 0.00 0.67
February 0.381172E+09 0.960506E+09 0.00 2934343.37 0.223307E+09 244080.06 0.402316E+09 0.00 0.72
March 0.383116E+09 0.145770E+10 0.00 3281331.89 0.831902E+09 0.00 0.690698E+09 0.00 0.89
April 94372460.30 0.176349E+10 0.00 1111773.39 0.130668E+10 0.00 0.162458E+09 0.00 1.07
May 0.00 0.330893E+10 0.00 0.00 0.125009E+10 0.00 0.00 0.00 1.07
June 0.00 0.418043E+10 0.00 0.00 0.165898E+10 0.00 0.00 0.00 1.17
July 0.00 0.418602E+10 0.00 0.00 0.222105E+10 0.00 0.00 0.00 1.19
August 0.00 0.386483E+10 0.00 0.00 0.232970E+10 0.00 0.00 0.00 1.14
September 0.00 0.418725E+10 0.00 0.00 0.145544E+10 0.00 0.00 0.00 1.07
October 0.00 0.290352E+10 0.00 0.00 0.164271E+10 0.00 0.00 0.00 0.98
November 0.177560E+09 0.190446E+10 0.00 858750.26 0.113192E+10 0.00 75606375.70 0.00 0.82
December 0.659397E+09 0.760294E+09 0.00 1660822.60 0.121706E+10 0.00 0.395138E+09 0.00 0.73
                   
Annual Sum or Average 0.246908E+10 0.302703E+11 0.00 12478306.47 0.155062E+11 244080.06 0.231599E+10 0.00 0.96
Minimum of Months 0.00 0.760294E+09 0.00 0.00 0.223307E+09 0.00 0.00 0.00 0.67
Maximum of Months 0.773462E+09 0.418725E+10 0.00 3281331.89 0.232970E+10 244080.06 0.690698E+09 0.00 1.19



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.525858E+09 0.175492E+10 0.00 11153752.73 0.104572E+09 0.00 0.192307E+10 0.00 0.81
February 0.332224E+09 0.186272E+10 0.00 8777390.90 0.136047E+09 0.00 0.847184E+09 0.00 0.81
March 0.379173E+09 0.245025E+10 0.00 5764944.85 0.773755E+09 0.00 0.982475E+09 0.00 0.84
April 88202854.69 0.251878E+10 0.00 1586521.55 0.128970E+10 0.00 0.207102E+09 0.00 0.87
May 0.00 0.399399E+10 0.00 0.00 0.137890E+10 0.00 0.00 0.00 0.80
June 0.00 0.505882E+10 0.00 0.00 0.186625E+10 0.00 0.00 0.00 0.90
July 0.00 0.522776E+10 0.00 0.00 0.250597E+10 0.00 0.00 0.00 0.93
August 0.00 0.581917E+10 0.00 0.00 0.235193E+10 0.00 0.00 0.00 0.98
September 0.00 0.646202E+10 0.00 0.00 0.139466E+10 0.00 0.00 0.00 0.98
October 0.00 0.549833E+10 0.00 0.00 0.144281E+10 0.00 0.00 0.00 1.01
November 0.125930E+09 0.413896E+10 0.00 3870568.87 0.991680E+09 0.00 0.251310E+09 0.00 0.94
December 0.344958E+09 0.230806E+10 0.00 8104211.54 0.959980E+09 0.00 0.167800E+10 0.00 0.89
                   
Annual Sum or Average 0.179635E+10 0.470938E+11 0.00 39257390.44 0.151963E+11 0.00 0.588914E+10 0.00 0.90
Minimum of Months 0.00 0.175492E+10 0.00 0.00 0.104572E+09 0.00 0.00 0.00 0.80
Maximum of Months 0.525858E+09 0.646202E+10 0.00 11153752.73 0.250597E+10 0.00 0.192307E+10 0.00 1.01



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.935824E+09 0.110207E+10 0.00 2932680.61 0.197979E+09 0.00 0.794461E+09 0.00 0.85
February 0.407314E+09 0.150475E+10 0.00 4473735.77 0.146532E+09 0.00 0.591172E+09 0.00 0.98
March 0.291691E+09 0.256875E+10 0.00 5614089.69 0.751238E+09 0.00 0.104024E+10 0.00 1.30
April 64940333.91 0.364669E+10 0.00 2615837.69 0.101965E+10 0.00 0.304198E+09 0.00 1.63
May 0.00 0.432110E+10 0.00 0.00 0.138105E+10 0.00 0.00 0.00 1.33
June 0.00 0.569977E+10 0.00 0.00 0.174905E+10 0.00 0.00 0.00 1.50
July 0.00 0.667586E+10 0.00 0.00 0.211689E+10 0.00 0.00 0.00 1.64
August 0.00 0.788079E+10 0.00 0.00 0.172066E+10 0.00 0.00 0.00 1.78
September 0.00 0.520874E+10 0.00 0.00 0.164053E+10 0.00 0.00 0.00 1.30
October 0.00 0.433786E+10 0.00 0.00 0.168321E+10 0.00 0.00 0.00 1.30
November 0.187502E+09 0.337755E+10 0.00 1649407.92 0.104566E+10 0.00 0.146351E+09 0.00 1.20
December 0.228970E+09 0.204870E+10 0.00 6210160.06 0.103399E+10 0.00 0.136773E+10 0.00 1.17
                   
Annual Sum or Average 0.211624E+10 0.483726E+11 0.00 23495911.74 0.144864E+11 0.00 0.424415E+10 0.00 1.33
Minimum of Months 0.00 0.110207E+10 0.00 0.00 0.146532E+09 0.00 0.00 0.00 0.85
Maximum of Months 0.935824E+09 0.788079E+10 0.00 6210160.06 0.211689E+10 0.00 0.136773E+10 0.00 1.78



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.120841E+11 0.578495E+10 0.00 2339928.51 0.440837E+10 0.417461E+09 0.577779E+09 0.00 0.45
February 0.574097E+10 0.862408E+10 0.00 7945853.21 0.322473E+10 0.542165E+09 0.825579E+09 0.00 0.48
March 0.781346E+10 0.145903E+11 0.00 6103417.59 0.351182E+10 0.230784E+09 0.103447E+10 0.00 0.52
April 0.748545E+09 0.186530E+11 0.00 7028425.47 0.524757E+10 0.00 0.121588E+10 0.00 0.60
May 0.00 0.389303E+11 0.00 6043.19 0.722271E+10 0.00 0.00 0.00 0.76
June 0.00 0.540989E+11 0.00 0.00 0.909382E+10 0.00 0.00 0.00 0.87
July 0.00 0.547116E+11 0.00 0.00 0.126685E+11 0.00 0.00 0.00 0.86
August 0.00 0.534851E+11 0.00 0.00 0.100703E+11 0.00 0.00 0.00 0.81
September 0.00 0.483711E+11 0.00 0.00 0.107023E+11 0.00 0.00 0.00 0.77
October 0.00 0.325698E+11 0.00 0.00 0.814969E+10 0.00 0.00 0.00 0.62
November 0.185902E+10 0.219461E+11 0.00 3207532.31 0.465841E+10 0.00 0.300314E+09 0.00 0.53
December 0.993921E+10 0.782934E+10 0.00 3496448.16 0.560462E+10 0.560721E+09 0.112045E+10 0.00 0.46
                   
Annual Sum or Average 0.381853E+11 0.359595E+12 0.00 30127648.43 0.845629E+11 0.175113E+10 0.507447E+10 0.00 0.65
Minimum of Months 0.00 0.578495E+10 0.00 0.00 0.322473E+10 0.00 0.00 0.00 0.45
Maximum of Months 0.120841E+11 0.547116E+11 0.00 7945853.21 0.126685E+11 0.560721E+09 0.121588E+10 0.00 0.87



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.841713E+10 0.588384E+10 0.00 13112847.65 0.399055E+10 0.140111E+09 0.427181E+10 0.00 0.68
February 0.469323E+10 0.776796E+10 0.00 19953135.73 0.359742E+10 0.283149E+09 0.247256E+10 0.00 0.75
March 0.389360E+10 0.147439E+11 0.00 24277787.36 0.311060E+10 0.158519E+09 0.630792E+10 0.00 0.84
April 0.550378E+09 0.196618E+11 0.00 10290781.23 0.520562E+10 0.00 0.179509E+10 0.00 0.98
May 0.00 0.345035E+11 0.00 6018.58 0.684719E+10 0.00 0.00 0.00 1.07
June 0.00 0.462571E+11 0.00 0.00 0.795780E+10 0.00 0.00 0.00 1.16
July 0.00 0.482785E+11 0.00 0.00 0.106020E+11 0.00 0.00 0.00 1.18
August 0.00 0.448837E+11 0.00 0.00 0.110107E+11 0.00 0.00 0.00 1.11
September 0.00 0.446604E+11 0.00 0.00 0.926748E+10 0.00 0.00 0.00 1.08
October 0.00 0.305696E+11 0.00 0.00 0.826724E+10 0.00 0.00 0.00 0.93
November 0.154023E+10 0.196455E+11 0.00 5933077.73 0.498184E+10 0.00 0.565199E+09 0.00 0.76
December 0.881608E+10 0.673140E+10 0.00 5098336.04 0.604262E+10 0.174563E+09 0.205080E+10 0.00 0.68
                   
Annual Sum or Average 0.279106E+11 0.323587E+12 0.00 78671984.33 0.808810E+11 0.756343E+09 0.174634E+11 0.00 0.94
Minimum of Months 0.00 0.588384E+10 0.00 0.00 0.311060E+10 0.00 0.00 0.00 0.68
Maximum of Months 0.881608E+10 0.482785E+11 0.00 24277787.36 0.110107E+11 0.283149E+09 0.630792E+10 0.00 1.18



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.502765E+10 0.164047E+11 0.00 0.101606E+09 0.111718E+10 0.00 0.191062E+11 0.00 0.86
February 0.331607E+10 0.175960E+11 0.00 77936792.28 0.105526E+10 0.291102E+09 0.737895E+10 0.00 0.85
March 0.448829E+10 0.230564E+11 0.00 46646312.97 0.173101E+10 0.00 0.841676E+10 0.00 0.79
April 0.515697E+09 0.236525E+11 0.00 11557443.02 0.442293E+10 0.00 0.187436E+10 0.00 0.72
May 0.00 0.383043E+11 0.00 5992.38 0.730535E+10 0.00 0.00 0.00 0.75
June 0.00 0.499492E+11 0.00 0.00 0.948800E+10 0.00 0.00 0.00 0.82
July 0.00 0.522568E+11 0.00 0.00 0.129891E+11 0.00 0.00 0.00 0.84
August 0.00 0.587076E+11 0.00 0.00 0.954397E+10 0.00 0.00 0.00 0.88
September 0.00 0.655550E+11 0.00 0.00 0.784199E+10 0.00 0.00 0.00 0.96
October 0.00 0.564011E+11 0.00 0.00 0.457190E+10 0.00 0.00 0.00 0.98
November 0.925594E+09 0.420029E+11 0.00 34627514.66 0.217054E+10 0.00 0.233461E+10 0.00 0.92
December 0.402482E+10 0.219372E+11 0.00 68062039.69 0.207376E+10 0.00 0.163938E+11 0.00 0.86
                   
Annual Sum or Average 0.182981E+11 0.465824E+12 0.00 0.340442E+09 0.643110E+11 0.291102E+09 0.555047E+11 0.00 0.85
Minimum of Months 0.00 0.164047E+11 0.00 0.00 0.105526E+10 0.00 0.00 0.00 0.72
Maximum of Months 0.502765E+10 0.655550E+11 0.00 0.101606E+09 0.129891E+11 0.291102E+09 0.191062E+11 0.00 0.98



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.114896E+11 0.593714E+10 0.00 10815013.74 0.469505E+10 0.00 0.299442E+10 0.00 0.75
February 0.521509E+10 0.931851E+10 0.00 17967717.56 0.302690E+10 0.486311E+09 0.228337E+10 0.00 0.81
March 0.675972E+10 0.164036E+11 0.00 21453770.55 0.285049E+10 6968774.32 0.401370E+10 0.00 0.94
April 0.650791E+09 0.229562E+11 0.00 10443351.58 0.407853E+10 0.00 0.168931E+10 0.00 1.07
May 0.00 0.368719E+11 0.00 6136.45 0.679255E+10 0.00 0.00 0.00 1.13
June 0.00 0.450662E+11 0.00 0.00 0.885047E+10 0.00 0.00 0.00 1.16
July 0.00 0.494743E+11 0.00 0.00 0.115188E+11 0.00 0.00 0.00 1.22
August 0.00 0.514252E+11 0.00 0.00 0.935887E+10 0.00 0.00 0.00 1.21
September 0.00 0.442464E+11 0.00 0.00 0.101456E+11 0.00 0.00 0.00 1.10
October 0.00 0.324226E+11 0.00 0.00 0.795144E+10 0.00 0.00 0.00 0.97
November 0.185392E+10 0.213653E+11 0.00 4338889.61 0.480281E+10 0.00 0.491594E+09 0.00 0.83
December 0.989307E+10 0.925065E+10 0.00 10379937.78 0.534062E+10 15686339.90 0.274412E+10 0.00 0.78
                   
Annual Sum or Average 0.358622E+11 0.344738E+12 0.00 75404817.26 0.794121E+11 0.508966E+09 0.142165E+11 0.00 1.00
Minimum of Months 0.00 0.593714E+10 0.00 0.00 0.285049E+10 0.00 0.00 0.00 0.75
Maximum of Months 0.114896E+11 0.514252E+11 0.00 21453770.55 0.115188E+11 0.486311E+09 0.401370E+10 0.00 1.22



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.101376E+10 0.493798E+09 0.00 222932.26 0.519113E+09 0.151905E+09 58427712.05 0.00 0.46
February 0.437055E+09 0.821029E+09 226022.27 773829.78 0.390762E+09 0.100050E+09 95538539.02 12209.96 0.48
March 0.663971E+09 0.145389E+10 0.00 687803.47 0.452347E+09 99514837.54 0.117102E+09 0.00 0.53
April 66220912.58 0.179495E+10 0.00 648430.18 0.664061E+09 0.00 0.120497E+09 0.00 0.60
May 870.38 0.372931E+10 0.00 6218.80 0.675744E+09 0.00 0.00 0.00 0.75
June 0.00 0.530202E+10 0.00 0.00 0.840221E+09 0.00 0.00 0.00 0.87
July 0.00 0.540583E+10 0.00 0.00 0.113860E+10 0.00 0.00 0.00 0.86
August 0.00 0.512384E+10 0.00 0.00 0.101185E+10 0.00 0.00 0.00 0.81
September 0.00 0.465425E+10 0.00 0.00 0.104758E+10 0.00 0.00 0.00 0.76
October 0.00 0.293411E+10 0.00 0.00 0.912990E+09 0.00 0.00 0.00 0.62
November 0.112482E+09 0.195091E+10 0.00 269710.38 0.640347E+09 40325554.66 35814243.93 0.00 0.52
December 0.875719E+09 0.691130E+09 10149.74 310478.34 0.673719E+09 0.139864E+09 83261770.61 45.26 0.47
                   
Annual Sum or Average 0.316921E+10 0.343551E+11 236172.01 2919403.22 0.896733E+10 0.531659E+09 0.510642E+09 12255.22 0.64
Minimum of Months 0.00 0.493798E+09 0.00 0.00 0.390762E+09 0.00 0.00 0.00 0.46
Maximum of Months 0.101376E+10 0.540583E+10 226022.27 773829.78 0.113860E+10 0.151905E+09 0.120497E+09 12209.96 0.87



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.744998E+09 0.552933E+09 0.00 1035220.78 0.414257E+09 73655638.82 0.338514E+09 0.00 0.68
February 0.382594E+09 0.764654E+09 105135.18 1758965.88 0.394764E+09 32497324.34 0.231794E+09 221.30 0.74
March 0.324419E+09 0.146124E+10 0.00 2268706.23 0.414582E+09 32346269.59 0.596576E+09 0.00 0.84
April 44247634.27 0.190520E+10 0.00 946858.94 0.616223E+09 0.00 0.179273E+09 0.00 0.97
May 818.11 0.326359E+10 0.00 6032.45 0.669722E+09 0.00 0.00 0.00 1.06
June 0.00 0.451686E+10 0.00 0.00 0.753913E+09 0.00 0.00 0.00 1.15
July 0.00 0.472231E+10 0.00 0.00 0.998724E+09 0.00 0.00 0.00 1.17
August 0.00 0.437766E+10 0.00 0.00 0.101652E+10 0.00 0.00 0.00 1.10
September 0.00 0.424091E+10 0.00 0.00 0.950939E+09 0.00 0.00 0.00 1.08
October 0.00 0.281058E+10 0.00 0.00 0.855105E+09 0.00 0.00 0.00 0.92
November 0.111043E+09 0.181939E+10 0.00 515950.28 0.585965E+09 16716768.39 51363420.36 0.00 0.76
December 0.808631E+09 0.628525E+09 0.00 332004.63 0.653143E+09 93638782.30 0.128350E+09 0.00 0.69
                   
Annual Sum or Average 0.241593E+10 0.310639E+11 105135.18 6863739.17 0.832386E+10 0.248855E+09 0.152587E+10 221.30 0.93
Minimum of Months 0.00 0.552933E+09 0.00 0.00 0.394764E+09 0.00 0.00 0.00 0.68
Maximum of Months 0.808631E+09 0.472231E+10 105135.18 2268706.23 0.101652E+10 93638782.30 0.596576E+09 221.30 1.17



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.452607E+09 0.157248E+10 0.00 9254538.96 0.164157E+09 40026715.49 0.179821E+10 0.00 0.84
February 0.262923E+09 0.168826E+10 0.00 7128492.00 0.161008E+09 30450522.62 0.738256E+09 0.00 0.82
March 0.410283E+09 0.231572E+10 0.00 4426809.47 0.255268E+09 21950092.92 0.857596E+09 0.00 0.77
April 51316417.44 0.230777E+10 0.00 1065898.77 0.552382E+09 0.00 0.180945E+09 0.00 0.71
May 866.84 0.363909E+10 0.00 6869.54 0.711683E+09 0.00 0.00 0.00 0.74
June 0.00 0.490673E+10 0.00 0.00 0.887491E+09 0.00 0.00 0.00 0.82
July 0.00 0.515619E+10 0.00 0.00 0.118098E+10 0.00 0.00 0.00 0.83
August 0.00 0.560651E+10 0.00 0.00 0.943708E+09 0.00 0.00 0.00 0.86
September 0.00 0.628455E+10 0.00 0.00 0.731049E+09 0.00 0.00 0.00 0.95
October 0.00 0.520439E+10 0.00 0.00 0.480446E+09 0.00 0.00 0.00 0.95
November 61918654.77 0.391163E+10 0.00 3071805.22 0.283184E+09 11325116.98 0.226641E+09 0.00 0.90
December 0.372712E+09 0.210751E+10 0.00 5611042.37 0.274881E+09 61900568.18 0.147393E+10 0.00 0.85
                   
Annual Sum or Average 0.161176E+10 0.447008E+11 0.00 30565456.33 0.662624E+10 0.165653E+09 0.527557E+10 0.00 0.84
Minimum of Months 0.00 0.157248E+10 0.00 0.00 0.161008E+09 0.00 0.00 0.00 0.71
Maximum of Months 0.452607E+09 0.628455E+10 0.00 9254538.96 0.118098E+10 61900568.18 0.179821E+10 0.00 0.95



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.102601E+10 0.542700E+09 0.00 998607.91 0.550631E+09 65975307.68 0.308684E+09 0.00 0.79
February 0.459880E+09 0.846157E+09 0.00 1709588.70 0.443618E+09 47021542.72 0.231477E+09 0.00 0.82
March 0.640437E+09 0.162424E+10 0.00 2154500.70 0.416986E+09 24551584.53 0.422845E+09 0.00 0.94
April 61448656.06 0.220478E+10 0.00 937030.99 0.576791E+09 0.00 0.168247E+09 0.00 1.05
May 951.48 0.341566E+10 0.00 5909.40 0.756604E+09 0.00 0.00 0.00 1.11
June 0.00 0.431613E+10 0.00 0.00 0.938681E+09 0.00 0.00 0.00 1.15
July 0.00 0.473748E+10 0.00 0.00 0.116811E+10 0.00 0.00 0.00 1.21
August 0.00 0.475496E+10 0.00 0.00 0.107846E+10 0.00 0.00 0.00 1.19
September 0.00 0.416210E+10 0.00 0.00 0.111748E+10 0.00 0.00 0.00 1.09
October 0.00 0.288979E+10 0.00 0.00 0.953434E+09 0.00 0.00 0.00 0.97
November 0.133014E+09 0.188940E+10 0.00 447559.57 0.708349E+09 25149341.46 55492304.52 0.00 0.84
December 0.894651E+09 0.863314E+09 0.00 874318.05 0.655969E+09 92131957.16 0.243548E+09 0.00 0.82
                   
Annual Sum or Average 0.321544E+10 0.322467E+11 0.00 7127515.32 0.936510E+10 0.254830E+09 0.143029E+10 0.00 1.00
Minimum of Months 0.00 0.542700E+09 0.00 0.00 0.416986E+09 0.00 0.00 0.00 0.79
Maximum of Months 0.102601E+10 0.475496E+10 0.00 2154500.70 0.116811E+10 92131957.16 0.422845E+09 0.00 1.21



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.00 0.144588E+09 0.00 5657537.29 0.00 0.00 0.271222E+09 0.00 0.58
February 0.00 0.191144E+09 0.00 9478571.80 0.00 0.00 0.171279E+09 0.00 0.58
March 0.00 0.323575E+09 0.00 11752112.65 0.00 0.00 0.163566E+09 0.00 0.58
April 0.00 0.421750E+09 0.00 6456460.61 0.00 0.00 30317529.31 0.00 0.58
May 0.00 0.723930E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.59
June 0.00 0.105277E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.58
July 0.00 0.116103E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.58
August 0.00 0.119884E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.58
September 0.00 0.945171E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.59
October 0.00 0.852101E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.59
November 0.00 0.574656E+09 0.00 7566149.43 0.00 0.00 61106940.48 0.00 0.58
December 0.00 0.314114E+09 0.00 16752170.12 0.00 0.00 0.177045E+09 0.00 0.58
                   
Annual Sum or Average 0.00 0.790367E+10 0.00 57663001.91 0.00 0.00 0.874536E+09 0.00 0.58
Minimum of Months 0.00 0.144588E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.58
Maximum of Months 0.00 0.119884E+10 0.00 16752170.12 0.00 0.00 0.271222E+09 0.00 0.59



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: DATACENTER_MID_ZN_6

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.00 0.136417E+10 0.00 41694259.93 0.00 0.00 0.276835E+10 0.00 0.58
February 0.00 0.188701E+10 0.00 81899671.65 0.00 0.00 0.172547E+10 0.00 0.58
March 0.00 0.323113E+10 0.00 0.107296E+09 0.00 0.00 0.164191E+10 0.00 0.58
April 0.00 0.422370E+10 0.00 61230032.26 0.00 0.00 0.304312E+09 0.00 0.58
May 0.00 0.715198E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.59
June 0.00 0.104938E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.58
July 0.00 0.115961E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.58
August 0.00 0.120068E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.58
September 0.00 0.933770E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.59
October 0.00 0.848802E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.59
November 0.00 0.573675E+10 0.00 68489910.55 0.00 0.00 0.616712E+09 0.00 0.58
December 0.00 0.313906E+10 0.00 0.152626E+09 0.00 0.00 0.177935E+10 0.00 0.58
                   
Annual Sum or Average 0.00 0.786562E+11 0.00 0.513236E+09 0.00 0.00 0.883611E+10 0.00 0.58
Minimum of Months 0.00 0.136417E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.58
Maximum of Months 0.00 0.120068E+11 0.00 0.152626E+09 0.00 0.00 0.276835E+10 0.00 0.59



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 5380825.09 0.132840E+09 0.00 3161044.85 0.00 0.00 0.276854E+09 0.00 0.58
February 0.00 0.187646E+09 0.00 7556484.52 0.00 0.00 0.173770E+09 0.00 0.58
March 0.00 0.322283E+09 0.00 10348100.18 0.00 0.00 0.164952E+09 0.00 0.58
April 0.00 0.421340E+09 0.00 6069137.17 0.00 0.00 30609924.59 0.00 0.58
May 0.00 0.716744E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.59
June 0.00 0.104952E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.58
July 0.00 0.115915E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.58
August 0.00 0.120033E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.58
September 0.00 0.935454E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.59
October 0.00 0.847510E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.59
November 0.00 0.572222E+09 0.00 6493413.98 0.00 0.00 62218279.63 0.00 0.58
December 0.00 0.312758E+09 0.00 14624178.46 0.00 0.00 0.179201E+09 0.00 0.58
                   
Annual Sum or Average 5380825.09 0.785779E+10 0.00 48252359.17 0.00 0.00 0.887605E+09 0.00 0.58
Minimum of Months 0.00 0.132840E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.58
Maximum of Months 5380825.09 0.120033E+10 0.00 14624178.46 0.00 0.00 0.276854E+09 0.00 0.59



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.00 0.367710E+10 0.00 0.314715E+09 0.00 0.00 0.596285E+10 0.00 0.66
February 0.00 0.433511E+10 0.00 0.473673E+09 0.00 0.00 0.386412E+10 0.00 0.66
March 0.00 0.707376E+10 0.00 0.569453E+09 0.00 0.00 0.361485E+10 0.00 0.66
April 0.00 0.839958E+10 0.00 0.288788E+09 0.00 0.00 0.564704E+09 0.00 0.66
May 0.00 0.172426E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.66
June 0.00 0.236596E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.66
July 0.00 0.255256E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.66
August 0.00 0.226445E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.66
September 0.00 0.223388E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.66
October 0.00 0.191624E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.66
November 0.00 0.126235E+11 0.00 0.355008E+09 0.00 0.00 0.126093E+10 0.00 0.66
December 0.00 0.650347E+10 0.00 0.811366E+09 0.00 0.00 0.362894E+10 0.00 0.66
                   
Annual Sum or Average 0.00 0.173186E+12 0.00 0.281300E+10 0.00 0.00 0.188964E+11 0.00 0.66
Minimum of Months 0.00 0.367710E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.66
Maximum of Months 0.00 0.255256E+11 0.00 0.811366E+09 0.00 0.00 0.596285E+10 0.00 0.66



Table of Contents

Report: HeatEmissionsReportMonthly

For: Environment

Timestamp: 2023-10-16 08:43:45

Custom Monthly Report

SITE TOTAL SURFACE HEAT EMISSION TO AIR [J] SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J]
January 0.352691E+12 0.119974E+10 0.00 0.129438E+12 0.206715E+13
February 0.373864E+12 0.847869E+09 0.00 -0.379286E+11 0.251564E+13
March 0.516659E+12 -0.330377E+10 0.00 -0.263783E+12 0.342800E+13
April 0.557538E+12 -0.784151E+10 0.00 -0.707739E+12 0.414339E+13
May 0.525424E+12 -0.205424E+11 0.00 -0.158710E+13 0.364604E+13
June 0.466439E+12 -0.214978E+11 0.00 -0.219701E+13 0.430652E+13
July 0.508762E+12 -0.194485E+11 0.00 -0.239390E+13 0.487197E+13
August 0.558667E+12 -0.222294E+11 0.00 -0.242630E+13 0.533441E+13
September 0.412657E+12 -0.204694E+11 0.00 -0.216256E+13 0.386257E+13
October 0.413813E+12 -0.174439E+11 0.00 -0.174526E+13 0.401104E+13
November 0.306111E+12 -0.774379E+10 0.00 -0.964243E+12 0.374806E+13
December 0.337740E+12 -0.257792E+10 0.00 -0.210288E+12 0.346929E+13
           
Annual Sum or Average 0.533037E+13 -0.141051E+12 0.00 -0.145667E+14 0.454041E+14
Minimum of Months 0.306111E+12 -0.222294E+11 0.00 -0.242630E+13 0.206715E+13
Maximum of Months 0.558667E+12 0.119974E+10 0.00 0.129438E+12 0.533441E+13