Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:43
Tabular Output Report in Format: HTML
Building: OfficeLarge
Environment: RUNPERIOD 1 ** Seattle Seattle Tacoma Intl A WA USA TMY3 WMO#=727930
Simulation Timestamp: 2023-10-16 08:44:06
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 08:44:06
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 28344.37 | 611.92 | 611.92 |
Net Site Energy | 28344.37 | 611.92 | 611.92 |
Total Source Energy | 85789.93 | 1852.10 | 1852.10 |
Net Source Energy | 85789.93 | 1852.10 | 1852.10 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 46320.38 |
Net Conditioned Building Area | 46320.38 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 1110.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 1136.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 3944.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 698.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 14676.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 1934.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 2326.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 274.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 413.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2003.73 |
Humidification | 1029.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 383.16 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 798.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2280.17 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 26435.25 | 1909.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4667.06 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler | 0.00 | 1110.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 1136.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 3944.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 698.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 5334.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DataCenterPlugLoads | 9341.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 80.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 1848.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 5.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | General | 2326.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 274.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 413.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2003.73 |
Humidification | General | 1029.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 383.16 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2280.17 | |
Water Heater | 0.00 | 798.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 1110.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 1136.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 3944.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 698.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 14676.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 1934.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 2326.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 274.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 413.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2003.73 |
Humidification | Unassigned | 1029.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 383.16 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 0.00 | 798.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2280.17 |
Refrigeration | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 100.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 111.86 | 41.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.10 |
Other | 358.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 570.70 | 41.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.10 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 100.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 111.86 | 41.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.10 |
Other | 358.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 570.70 | 41.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.10 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 26435.252 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 26435.252 | 100.00 |
Total On-Site and Utility Electric Sources | 26435.252 | 100.00 |
Total Electricity End Uses | 26435.252 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 4667.06 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 4667.06 | 100.00 |
Total Water End Uses | 4667.06 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 15.67 |
Time Setpoint Not Met During Occupied Cooling | 182.00 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 5943.00 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2013
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICELARGE
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 4C
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_WA_SEATTLE
| Environment |ZoneCoolingSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |ZoneHeatingSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |ZoneElectricSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |SpaceGainsMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |PeakSpaceGainsMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |SpaceGainComponentsAtCoolingPeakMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |ComfortReportSimple55Monthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |OccupantComfortDataSummaryMonthly
| DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 | BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 |ChillerReportMonthly
| COOLSYS1 CHILLER1 | COOLSYS1 CHILLER2 |TowerReportMonthly
| CENTRAL TOWER | TOWERWATERSYS COOLTOWER 1 | TOWERWATERSYS COOLTOWER 2 |BoilerReportMonthly
| HEATSYS1 BOILER | CENTRAL BOILER |DXReportMonthly
| VAV_BOT WITH REHEAT COOLING COIL | VAV_MID WITH REHEAT COOLING COIL | VAV_TOP WITH REHEAT COOLING COIL | CAV_BAS COOLING COIL | AIRLOOP DATACENTER BASEMENT COOLING COIL | AIRLOOP DATACENTER BOT COOLING COIL | AIRLOOP DATACENTER MID COOLING COIL | AIRLOOP DATACENTER TOP COOLING COIL |WindowReportMonthly
| PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW |WindowEnergyReportMonthly
| PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW |WindowZoneSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |WindowEnergyZoneSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWHSYS1 WATER HEATER |DaylightingReportMonthly
| PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_4_DAYLCTRL |CoilReportMonthly
| VAV_BOT WITH REHEAT HEATING COIL | CORE_BOTTOM VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | VAV_MID WITH REHEAT HEATING COIL | CORE_MID VAV BOX REHEAT COIL | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | VAV_TOP WITH REHEAT HEATING COIL | CORE_TOP VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | CAV_BAS HEATING COIL | AIRLOOP DATACENTER BASEMENT HEATING COIL | AIRLOOP DATACENTER BOT HEATING COIL | AIRLOOP DATACENTER MID HEATING COIL | AIRLOOP DATACENTER TOP HEATING COIL | AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | AIRLOOP DATACENTER BOT_SUPPHEATCOIL | AIRLOOP DATACENTER MID_SUPPHEATCOIL | AIRLOOP DATACENTER TOP_SUPPHEATCOIL | VAV_BOT WITH REHEAT COOLING COIL | VAV_MID WITH REHEAT COOLING COIL | VAV_TOP WITH REHEAT COOLING COIL | CAV_BAS COOLING COIL | AIRLOOP DATACENTER BASEMENT COOLING COIL | AIRLOOP DATACENTER BOT COOLING COIL | AIRLOOP DATACENTER MID COOLING COIL | AIRLOOP DATACENTER TOP COOLING COIL |PlantLoopDemandReportMonthly
| HEATSYS1 | COOLSYS1_SUPPLY | COOLSYS1_DEMAND | SINGLE WATER PLANT LOOP | SWHSYS1 | TOWERWATERSYS |FanReportMonthly
| CAV_BAS FAN | VAV_BOT WITH REHEAT FAN | VAV_MID WITH REHEAT FAN | VAV_TOP WITH REHEAT FAN | AIRLOOP DATACENTER BASEMENT SUPPLY FAN | AIRLOOP DATACENTER BOT SUPPLY FAN | AIRLOOP DATACENTER MID SUPPLY FAN | AIRLOOP DATACENTER TOP SUPPLY FAN |PumpReportMonthly
| HEATSYS1 PUMP | COOLSYS1 PUMP SECONDARY | COOLSYS1 CHILLER1 PUMP | COOLSYS1 CHILLER2 PUMP | PLANT CIRC PUMP | SWHSYS1 PUMP | TOWERWATERSYS PUMP |CondLoopDemandReportMonthly
| HEATSYS1 | COOLSYS1_SUPPLY | COOLSYS1_DEMAND | SINGLE WATER PLANT LOOP | SWHSYS1 | TOWERWATERSYS |ZoneTemperatureOscillationReportMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |AirLoopSystemEnergyAndWaterUseMonthly
| VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | CAV_BAS | AIRLOOP DATACENTER BASEMENT | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |AirLoopSystemComponentLoadsMonthly
| VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | CAV_BAS | AIRLOOP DATACENTER BASEMENT | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |AirLoopSystemComponentEnergyUseMonthly
| VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | CAV_BAS | AIRLOOP DATACENTER BASEMENT | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |MechanicalVentilationLoadsMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 08:44:06
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:43 |
RunPeriod | RUNPERIOD 1 |
Weather File | Seattle Seattle Tacoma Intl A WA USA TMY3 WMO#=727930 |
Latitude [deg] | 47.47 |
Longitude [deg] | -122.3 |
Elevation [m] | 122.00 |
Time Zone | -8.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 12183.89 | 3655.17 | 2436.78 | 3655.17 | 2436.78 |
Above Ground Wall Area [m2] | 11589.54 | 3476.86 | 2317.91 | 3476.86 | 2317.91 |
Window Opening Area [m2] | 4635.80 | 1390.74 | 927.16 | 1390.74 | 927.16 |
Gross Window-Wall Ratio [%] | 38.05 | 38.05 | 38.05 | 38.05 | 38.05 |
Above Ground Window-Wall Ratio [%] | 40.00 | 40.00 | 40.00 | 40.00 | 40.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 12183.89 | 3655.17 | 2436.78 | 3655.17 | 2436.78 |
Above Ground Wall Area [m2] | 11589.54 | 3476.86 | 2317.91 | 3476.86 | 2317.91 |
Window Opening Area [m2] | 4635.80 | 1390.74 | 927.16 | 1390.74 | 927.16 |
Gross Window-Wall Ratio [%] | 38.05 | 38.05 | 38.05 | 38.05 | 38.05 |
Above Ground Window-Wall Ratio [%] | 40.00 | 40.00 | 40.00 | 40.00 | 40.00 |
Total | |
Gross Roof Area [m2] | 3563.11 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
BASEMENT | 2779.43 | Yes | Yes | 6779.02 | 1.00 | 0.00 | 397.05 | 0.00 | 0.00 | 10.2732 | 18.58 | 4.8418 |
CORE_BOTTOM | 2496.12 | Yes | Yes | 6849.35 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.2732 | 18.58 | 8.0697 |
CORE_MID | 2496.12 | Yes | Yes | 6849.35 | 10.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.2732 | 18.58 | 8.0696 |
CORE_TOP | 2496.12 | Yes | Yes | 6849.35 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.2732 | 18.58 | 8.0696 |
PERIMETER_BOT_ZN_3 | 313.41 | Yes | Yes | 860.00 | 1.00 | 200.61 | 0.00 | 115.90 | 115.90 | 10.2732 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_2 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 77.26 | 77.26 | 10.2732 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_1 | 313.42 | Yes | Yes | 860.02 | 1.00 | 200.61 | 0.00 | 115.90 | 115.90 | 10.2732 | 18.58 | 8.0699 |
PERIMETER_BOT_ZN_4 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 77.26 | 77.26 | 10.2732 | 18.58 | 8.0699 |
PERIMETER_MID_ZN_3 | 313.41 | Yes | Yes | 860.00 | 10.00 | 200.61 | 0.00 | 115.90 | 115.90 | 10.2732 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_2 | 201.98 | Yes | Yes | 554.22 | 10.00 | 133.74 | 0.00 | 77.26 | 77.26 | 10.2732 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_1 | 313.42 | Yes | Yes | 860.02 | 10.00 | 200.61 | 0.00 | 115.90 | 115.90 | 10.2732 | 18.58 | 8.0699 |
PERIMETER_MID_ZN_4 | 201.98 | Yes | Yes | 554.22 | 10.00 | 133.74 | 0.00 | 77.26 | 77.26 | 10.2732 | 18.58 | 8.0699 |
PERIMETER_TOP_ZN_3 | 313.41 | Yes | Yes | 860.00 | 1.00 | 200.61 | 0.00 | 115.90 | 115.90 | 10.2732 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_2 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 77.26 | 77.26 | 10.2732 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_1 | 313.42 | Yes | Yes | 860.02 | 1.00 | 200.61 | 0.00 | 115.90 | 115.90 | 10.2732 | 18.58 | 8.0699 |
PERIMETER_TOP_ZN_4 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 77.26 | 77.26 | 10.2732 | 18.58 | 8.0699 |
GROUNDFLOOR_PLENUM | 3563.11 | Yes | No | 4344.14 | 1.00 | 297.11 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
MIDFLOOR_PLENUM | 3563.11 | Yes | No | 4344.14 | 10.00 | 297.11 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
TOPFLOOR_PLENUM | 3563.11 | Yes | No | 4344.14 | 1.00 | 297.11 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
DATACENTER_BOT_ZN_6 | 36.20 | Yes | Yes | 99.34 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.8735 | 18.58 | 215.2992 |
DATACENTER_MID_ZN_6 | 36.20 | Yes | Yes | 99.34 | 10.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.8735 | 18.58 | 215.2992 |
DATACENTER_TOP_ZN_6 | 36.20 | Yes | Yes | 99.34 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.8735 | 18.58 | 215.2992 |
DATACENTER_BASEMENT_ZN_6 | 783.68 | Yes | Yes | 1911.37 | 1.00 | 0.00 | 197.31 | 0.00 | 0.00 | 10.2732 | 18.58 | 484.4232 |
Total | 46320.38 | 126016.35 | 8024.24 | 594.36 | 4635.80 | 4635.80 | 10.3445 | 18.58 | 17.8789 | |||
Conditioned Total | 46320.38 | 126016.35 | 8024.24 | 594.36 | 4635.80 | 4635.80 | 10.3445 | 18.58 | 17.8789 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 42757.27 | 52129.67 | 3565.29 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
BASEMENT | 2779.43 | Yes | Yes | 1.00 | BASEMENT | GENERAL | BASEMENT | 10.2732 | 18.58 | 4.8418 | |
CORE_BOTTOM | 2496.12 | Yes | Yes | 1.00 | CORE_BOTTOM | GENERAL | CORE_BOTTOM | 10.2732 | 18.58 | 8.0697 | |
CORE_MID | 2496.12 | Yes | Yes | 10.00 | CORE_MID | GENERAL | CORE_MID | 10.2732 | 18.58 | 8.0696 | |
CORE_TOP | 2496.12 | Yes | Yes | 1.00 | CORE_TOP | GENERAL | CORE_TOP | 10.2732 | 18.58 | 8.0696 | |
PERIMETER_BOT_ZN_3 | 313.41 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_3 | GENERAL | PERIMETER_BOT_ZN_3 | 10.2732 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_2 | 201.98 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_2 | GENERAL | PERIMETER_BOT_ZN_2 | 10.2732 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_1 | 313.42 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_1 | GENERAL | PERIMETER_BOT_ZN_1 | 10.2732 | 18.58 | 8.0699 | |
PERIMETER_BOT_ZN_4 | 201.98 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_4 | GENERAL | PERIMETER_BOT_ZN_4 | 10.2732 | 18.58 | 8.0699 | |
PERIMETER_MID_ZN_3 | 313.41 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_3 | GENERAL | PERIMETER_MID_ZN_3 | 10.2732 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_2 | 201.98 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_2 | GENERAL | PERIMETER_MID_ZN_2 | 10.2732 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_1 | 313.42 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_1 | GENERAL | PERIMETER_MID_ZN_1 | 10.2732 | 18.58 | 8.0699 | |
PERIMETER_MID_ZN_4 | 201.98 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_4 | GENERAL | PERIMETER_MID_ZN_4 | 10.2732 | 18.58 | 8.0699 | |
PERIMETER_TOP_ZN_3 | 313.41 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_3 | GENERAL | PERIMETER_TOP_ZN_3 | 10.2732 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_2 | 201.98 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_2 | GENERAL | PERIMETER_TOP_ZN_2 | 10.2732 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_1 | 313.42 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_1 | GENERAL | PERIMETER_TOP_ZN_1 | 10.2732 | 18.58 | 8.0699 | |
PERIMETER_TOP_ZN_4 | 201.98 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_4 | GENERAL | PERIMETER_TOP_ZN_4 | 10.2732 | 18.58 | 8.0699 | |
GROUNDFLOOR_PLENUM | 3563.11 | Yes | No | 1.00 | GROUNDFLOOR_PLENUM | GENERAL | GROUNDFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
MIDFLOOR_PLENUM | 3563.11 | Yes | No | 10.00 | MIDFLOOR_PLENUM | GENERAL | MIDFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
TOPFLOOR_PLENUM | 3563.11 | Yes | No | 1.00 | TOPFLOOR_PLENUM | GENERAL | TOPFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
DATACENTER_BOT_ZN_6 | 36.20 | Yes | Yes | 1.00 | DATACENTER_BOT_ZN_6 | GENERAL | DATACENTER_BOT_ZN_6 | 17.8735 | 18.58 | 215.2992 | |
DATACENTER_MID_ZN_6 | 36.20 | Yes | Yes | 10.00 | DATACENTER_MID_ZN_6 | GENERAL | DATACENTER_MID_ZN_6 | 17.8735 | 18.58 | 215.2992 | |
DATACENTER_TOP_ZN_6 | 36.20 | Yes | Yes | 1.00 | DATACENTER_TOP_ZN_6 | GENERAL | DATACENTER_TOP_ZN_6 | 17.8735 | 18.58 | 215.2992 | |
DATACENTER_BASEMENT_ZN_6 | 783.68 | Yes | Yes | 1.00 | DATACENTER_BASEMENT_ZN_6 | GENERAL | DATACENTER_BASEMENT_ZN_6 | 10.2732 | 18.58 | 484.4232 | |
Total | 46320.38 | 10.3445 | 9.29 | 17.8789 | |||||||
Conditioned Total | 46320.38 | 10.3445 | 9.29 | 17.8789 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 42757.27 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 46320.38 | 46320.38 | 0.00 | 42757.27 | 3.1788 | 60.38 | 10.8345 |
Total | 46320.38 | 46320.38 | 0.00 | 42757.27 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:44:06
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 29-AUG-15:09 | 02-JAN-05:19 | - | - | - | - | - | - | - | - | - | - | 10-AUG-15:00 |
Heating | 0.00 | 1635223.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 425212.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 332294.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 778371.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 84450.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 281451.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 45738.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 82535.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 8146.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 2030054.14 | 1643369.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler | 0.00 | 1635223.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 425212.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 332294.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 305206.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DataCenterPlugLoads | 473165.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 5015.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 79171.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 263.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | General | 281451.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 45738.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 82535.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Water Heater | 0.00 | 8146.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:44:06
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 1203.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 3598.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 12490.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 2212.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 46480.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 6127.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 7369.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 868.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 1310.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 3261.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 865.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 83720.44 | 2069.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 25.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 77.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 269.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 47.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1003.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 132.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 159.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 18.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 28.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 70.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 18.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1807.42 | 44.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 25.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 77.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 269.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 47.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1003.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 132.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 159.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 18.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 28.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 70.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 18.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1807.42 | 44.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:44:06
AirTerminal:SingleDuct:ConstantVolume:NoReheatDesign Size Maximum Air Flow Rate [m3/s] | |
BASEMENT DIRECT AIR | 6.07 |
DATACENTER_BOT_ZN_6 DIRECT AIR | 0.528855 |
DATACENTER_MID_ZN_6 DIRECT AIR | 5.09 |
DATACENTER_TOP_ZN_6 DIRECT AIR | 0.515849 |
DATACENTER_BASEMENT_ZN_6 DIRECT AIR | 21.72 |
Design Size Maximum Air Flow Rate [m3/s] | Design Size Constant Minimum Air Flow Fraction | User-Specified Constant Minimum Air Flow Fraction | Design Size Minimum Air Flow Rate [m3/s] | Design Size Maximum Flow Fraction during Reheat [] | User-Specified Maximum Flow Fraction during Reheat [] | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | Design Size Maximum Reheat Water Flow Rate [m3/s] | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | |
CORE_BOTTOM VAV BOX COMPONENT | 6.25 | 0.304324 | 0.315000 | 1.97 | 0.811532 | 0.500000 | 0.001252 | 0.000171 | 1.97 | 12.80 | 0.008000 |
CORE_MID VAV BOX COMPONENT | 58.77 | 0.323662 | 0.327000 | 19.22 | 0.863098 | 0.500000 | 0.001177 | 0.003689 | 19.22 | 12.80 | 0.008000 |
CORE_TOP VAV BOX COMPONENT | 5.68 | 0.335006 | 0.349000 | 1.98 | 0.893350 | 0.500000 | 0.001137 | 0.000651 | 2.24 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | 0.953723 | 0.250409 | 0.259000 | 0.247014 | 0.667757 | 0.500000 | 0.001522 | 0.000089 | 0.307305 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | 1.43 | 0.107270 | 0.200000 | 0.286949 | 0.300000 | 0.500000 | 0.003552 | 0.000069 | 0.286949 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | 1.99 | 0.119786 | 0.200000 | 0.398753 | 0.319430 | 0.500000 | 0.003181 | 0.000110 | 0.398753 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | 1.70 | 0.090361 | 0.200000 | 0.340644 | 0.300000 | 0.500000 | 0.004216 | 0.000059 | 0.340644 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_3 VAV BOX COMPONENT | 8.85 | 0.269899 | 0.273000 | 2.42 | 0.719731 | 0.500000 | 0.001412 | 0.001804 | 6.24 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_2 VAV BOX COMPONENT | 14.99 | 0.102645 | 0.200000 | 3.00 | 0.300000 | 0.500000 | 0.003712 | 0.001197 | 4.14 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_1 VAV BOX COMPONENT | 20.76 | 0.115046 | 0.200000 | 4.15 | 0.306789 | 0.500000 | 0.003312 | 0.001786 | 6.18 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_4 VAV BOX COMPONENT | 15.85 | 0.097072 | 0.200000 | 3.17 | 0.300000 | 0.500000 | 0.003925 | 0.001121 | 3.88 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | 0.982508 | 0.243072 | 0.253000 | 0.248574 | 0.648193 | 0.500000 | 0.001567 | 0.000228 | 0.788691 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | 1.49 | 0.103494 | 0.200000 | 0.297418 | 0.300000 | 0.500000 | 0.003681 | 0.000151 | 0.520858 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | 2.17 | 0.109904 | 0.200000 | 0.434608 | 0.300000 | 0.500000 | 0.003467 | 0.000226 | 0.782039 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | 1.65 | 0.093285 | 0.200000 | 0.329969 | 0.300000 | 0.500000 | 0.004084 | 0.000144 | 0.497590 | 12.80 | 0.008000 |
Design Size Rated Capacity [W] | Design Size Maximum Water Flow Rate [m3/s] | Design Size U-Factor Times Area Value [W/K] | |
CORE_BOTTOM VAV BOX REHEAT COIL | 19540.37 | 0.000171 | 393.92 |
CORE_MID VAV BOX REHEAT COIL | 421720.92 | 0.003689 | 9666.13 |
CORE_TOP VAV BOX REHEAT COIL | 74373.80 | 0.000651 | 1964.25 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | 10177.09 | 0.000089 | 268.65 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | 7893.08 | 0.000069 | 193.49 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | 12555.12 | 0.000110 | 324.16 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | 6740.40 | 0.000059 | 150.75 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | 206186.70 | 0.001804 | 5437.81 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | 136866.05 | 0.001197 | 3609.50 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | 204190.01 | 0.001786 | 5385.20 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | 128100.02 | 0.001121 | 3378.50 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | 26054.26 | 0.000228 | 687.00 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | 17205.69 | 0.000151 | 453.67 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | 25834.86 | 0.000226 | 681.22 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | 16438.09 | 0.000144 | 433.44 |
VAV_BOT WITH REHEAT HEATING COIL | 53123.51 | 0.000465 | 882.85 |
VAV_MID WITH REHEAT HEATING COIL | 483782.73 | 0.004232 | 8049.85 |
VAV_TOP WITH REHEAT HEATING COIL | 45185.73 | 0.000395 | 762.45 |
CAV_BAS HEATING COIL | 295455.45 | 0.002585 | 6586.60 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT | 6.17 | 3.24 | 12.34 | 3.24 | 10.29 | 10.29 | 0.300000 | 0.315056 | 10.29 |
VAV_MID WITH REHEAT | 59.61 | 31.95 | 119.22 | 31.95 | 95.13 | 95.13 | 0.300000 | 0.335883 | 95.13 |
VAV_TOP WITH REHEAT | 5.99 | 3.29 | 11.97 | 4.83 | 10.60 | 10.60 | 0.300000 | 0.455841 | 10.60 |
CAV_BAS | 6.07 | 6.07 | 6.07 | 6.07 | 6.07 | 6.07 | 1.00 | 1.00 | 6.07 |
AIRLOOP DATACENTER BASEMENT | 21.72 | 21.72 | 21.72 | 21.72 | 21.72 | 21.72 | 1.00 | 1.000000 | 21.72 |
AIRLOOP DATACENTER BOT | 0.528855 | 0.528855 | 0.528855 | 0.528855 | 0.528855 | 0.528855 | 1.00 | 1.00 | 0.528855 |
AIRLOOP DATACENTER MID | 5.09 | 5.09 | 5.09 | 5.09 | 5.09 | 5.09 | 1.00 | 1.00 | 5.09 |
AIRLOOP DATACENTER TOP | 0.515849 | 0.515849 | 0.515849 | 0.515849 | 0.515849 | 0.515849 | 1.00 | 1.00 | 0.515849 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT_OA_CONTROLLER | 10.29 | |
VAV_MID WITH REHEAT_OA_CONTROLLER | 95.13 | |
VAV_TOP WITH REHEAT_OA_CONTROLLER | 10.60 | |
CAV_BAS_OA_CONTROLLER | 6.07 | 1.20 |
AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER | 21.72 | 0.338393 |
AIRLOOP DATACENTER BOT_OA_CONTROLLER | 0.528855 | 0.015632 |
AIRLOOP DATACENTER MID_OA_CONTROLLER | 5.09 | 0.156323 |
AIRLOOP DATACENTER TOP_OA_CONTROLLER | 0.515849 | 0.015632 |
Design Size Design Inlet Air Temperature [C] | Design Size Design Inlet Water Temperature [C] | Design Size Design Outlet Air Temperature [C] | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | Design Size Design Coil Load [W] | Design Size Design Water Flow Rate [m3/s] | Design Size Design Air Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT COOLING COIL | 25.33 | 6.67 | 11.03 | 0.008812 | 0.008500 | 188034.13 | 0.007999 | 10.29 |
VAV_MID WITH REHEAT COOLING COIL | 25.44 | 6.67 | 11.02 | 0.008831 | 0.008500 | 1757522.92 | 0.074769 | 95.13 |
VAV_TOP WITH REHEAT COOLING COIL | 25.29 | 6.67 | 11.03 | 0.008806 | 0.008500 | 193036.61 | 0.008212 | 10.60 |
CAV_BAS COOLING COIL | 24.88 | 6.67 | 11.40 | 0.008924 | 0.008500 | 106856.93 | 0.004546 | 6.07 |
Design Size Maximum Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT FAN | 10.29 |
VAV_MID WITH REHEAT FAN | 95.13 |
VAV_TOP WITH REHEAT FAN | 10.60 |
Maximum Actuated Flow [m3/s] | Controller Convergence Tolerance | |
VAV_BOT WITH REHEAT_COOLC_CONTROLLER | 0.007999 | 0.000060 |
VAV_BOT WITH REHEAT_HEATC_CONTROLLER | 0.000465 | |
VAV_MID WITH REHEAT_COOLC_CONTROLLER | 0.074769 | 0.000006 |
VAV_MID WITH REHEAT_HEATC_CONTROLLER | 0.004232 | |
VAV_TOP WITH REHEAT_COOLC_CONTROLLER | 0.008212 | 0.000058 |
VAV_TOP WITH REHEAT_HEATC_CONTROLLER | 0.000395 | |
CAV_BAS_COOLC_CONTROLLER | 0.004546 | 0.000105 |
CAV_BAS_HEATC_CONTROLLER | 0.002585 |
Design Size Maximum Flow Rate [m3/s] | |
CAV_BAS FAN | 6.07 |
Design Size Rated Air Flow Rate [m3/s] | Design Size Rated Total Cooling Capacity [W] | Design Size Rated Sensible Cooling Capacity [W] | Design Size Rated Water Flow Rate [m3/s] | |
AIRLOOP DATACENTER BASEMENT COOLING COIL | 21.72 | 429490.73 | 307640.14 | 0.010518 |
AIRLOOP DATACENTER BOT COOLING COIL | 0.528855 | 10216.00 | 7404.55 | 0.000250 |
AIRLOOP DATACENTER MID COOLING COIL | 5.09 | 98317.41 | 71245.34 | 0.002408 |
AIRLOOP DATACENTER TOP COOLING COIL | 0.515849 | 9970.91 | 7224.48 | 0.000244 |
Supply Air Flow Rate [m3/s] | Supply Air Flow Rate During Heating Operation [m3/s] | Supply Air Flow Rate During Cooling Operation [m3/s] | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | Nominal Heating Capacity [W] | Nominal Cooling Capacity [W] | Supplemental Heating Coil Nominal Capacity [W] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | 21.72 | 21.72 | 21.72 | 21.72 | 429490.73 | 429490.73 | 17840.03 | 1.00 |
AIRLOOP DATACENTER BOT DXAC HEAT PUMP | 0.528855 | 0.528855 | 0.528855 | 0.528855 | 10216.00 | 10216.00 | 824.14 | 1.00 |
AIRLOOP DATACENTER MID DXAC HEAT PUMP | 5.09 | 5.09 | 5.09 | 5.09 | 98317.41 | 98317.41 | 8241.36 | 1.00 |
AIRLOOP DATACENTER TOP DXAC HEAT PUMP | 0.515849 | 0.515849 | 0.515849 | 0.515849 | 9970.91 | 9970.91 | 824.14 | 1.00 |
Design Size Maximum Flow Rate [m3/s] | |
AIRLOOP DATACENTER BASEMENT SUPPLY FAN | 21.72 |
AIRLOOP DATACENTER BOT SUPPLY FAN | 0.528855 |
AIRLOOP DATACENTER MID SUPPLY FAN | 5.09 |
AIRLOOP DATACENTER TOP SUPPLY FAN | 0.515849 |
Design Size Rated Air Flow Rate [m3/s] | Design Size Rated Heating Capacity [W] | Design Size Rated Water Flow Rate [m3/s] | |
AIRLOOP DATACENTER BASEMENT HEATING COIL | 21.72 | 429490.73 | 0.010518 |
AIRLOOP DATACENTER BOT HEATING COIL | 0.528855 | 10216.00 | 0.000250 |
AIRLOOP DATACENTER MID HEATING COIL | 5.09 | 98317.41 | 0.002408 |
AIRLOOP DATACENTER TOP HEATING COIL | 0.515849 | 9970.91 | 0.000244 |
Design Size Nominal Capacity [W] | |
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | 17840.03 |
AIRLOOP DATACENTER BOT_SUPPHEATCOIL | 824.14 |
AIRLOOP DATACENTER MID_SUPPHEATCOIL | 8241.36 |
AIRLOOP DATACENTER TOP_SUPPHEATCOIL | 824.14 |
Design Size Nominal Capacity Volume [m3/s] | User-Specified Nominal Capacity Volume [m3/s] | Design Size Rated Power [W] | User-Specified Rated Power [W] | |
DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | 0.000144 | 0.000037 | 96450.70 | 100000.00 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | Design Minimum Flow Rate [m3/s] | |
COOLSYS1 PUMP SECONDARY | 0.095527 | 15596.58 | |
HEATSYS1 PUMP | 0.019172 | 5773.62 | 0.000000 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
COOLSYS1_DEMAND | 0.095527 | 11.46 |
HEATSYS1 | 0.019172 | 2.30 |
COOLSYS1_SUPPLY | 0.095527 | 11.46 |
SINGLE WATER PLANT LOOP | 0.013420 | 1.61 |
SWHSYS1 | 0.000440 | 0.052800 |
Loop Supply Side Design Fluid Flow Rate [m3/s] | Loop Demand Side Design Fluid Flow Rate [m3/s] | Heat Exchanger U-Factor Times Area Value [W/C] | Loop-to-loop Temperature Difference Used to Size Heat Exchanger U-Factor Times Area Value [C] | |
BYPASS HEAT EXCHANGER | 0.095527 | 0.095527 | 400973.32 | 5.60 |
Design Size Nominal Capacity [W] | User-Specified Nominal Capacity [W] | Design Size Design Water Flow Rate [m3/s] | |
HEATSYS1 BOILER | 2191423.88 | 2191423.88 | 0.019172 |
CENTRAL BOILER | 552803.92 | 542091.38 | 0.013420 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
COOLSYS1 CHILLER1 PUMP | 0.047763 | 5399.02 |
COOLSYS1 CHILLER2 PUMP | 0.047763 | 5399.02 |
PLANT CIRC PUMP | 0.013420 | 3422.86 |
SWHSYS1 PUMP | 0.000440 | 56.21 |
Design Size Reference Chilled Water Flow Rate [m3/s] | User-Specified Reference Chilled Water Flow Rate [m3/s] | Design Size Reference Capacity [W] | User-Specified Reference Capacity [W] | Design Size Reference Condenser Water Flow Rate [m3/s] | |
COOLSYS1 CHILLER1 | 0.095527 | 0.048372 | 1139822.26 | 1145228.26 | 0.056673 |
COOLSYS1 CHILLER2 | 0.095527 | 0.048372 | 1139822.26 | 1145228.26 | 0.056673 |
Design Water Flow Rate [m3/s] | Air Flow Rate at High Fan Speed [m3/s] | Fluid cooler UA value at high fan speed based on nominal capacity input [W/K] | Air Flow Rate at Low Fan Speed [m3/s] | Fan Power at Low Fan Speed [W] | U-factor Times Area Value at Low Fan Speed [W/C] | |
CENTRAL TOWER | 0.013420 | 139666.47 | 58779.20 | 69833.23 | 7879.72 | 21365.65 |
Use Side Design Flow Rate [m3/s] | |
SWHSYS1 WATER HEATER | 0.000440 |
Maximum Loop Flow Rate [m3/s] | Condenser Loop Volume [m3] | |
TOWERWATERSYS | 0.113346 | 13.60 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
TOWERWATERSYS PUMP | 0.113346 | 28062.01 |
Design Air Flow Rate [m3/s] | Nominal Capacity [W] | Air Flow Rate in free convection regime [m3/s] | Tower capacity in free convection regime at design conditions [W] | |
TOWERWATERSYS COOLTOWER 1 | 44.44 | 1360475.38 | 8.89 | 170059.42 |
TOWERWATERSYS COOLTOWER 2 | 44.44 | 1360475.38 | 8.89 | 170059.42 |
Design Water Flow Rate [m3/s] Equipment # 47 | |
WSHPPLANT OPERATION SCHEME | 0.058865 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:44:06
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
PERIMETER_BOT_ZN_3_WALL_NORTH | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | |
PERIMETER_BOT_ZN_2_WALL_EAST | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | |
PERIMETER_BOT_ZN_1_WALL_SOUTH | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | |
PERIMETER_BOT_ZN_4_WALL_WEST | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | |
PERIMETER_MID_ZN_3_WALL_NORTH | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_MID_ZN_2_WALL_EAST | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_MID_ZN_1_WALL_SOUTH | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_MID_ZN_4_WALL_WEST | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | |
PERIMETER_TOP_ZN_3_WALL_NORTH | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_TOP_ZN_2_WALL_EAST | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_TOP_ZN_1_WALL_SOUTH | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_TOP_ZN_4_WALL_WEST | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 08:44:06
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 08:44:06
VersionVersion ID | |
1 | 22.1.0 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 11.40 | 8.10 | 5.40 | 4.50 | 5.80 | 8.30 | 10.90 | 13.00 | 15.60 | 17.70 | 18.80 | 15.10 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Seattle Seattle Tacoma Intl A WA USA TMY3 WMO#=727930 | 47.47 | -122.32 | -8.00 | 122.00 | 99868 | 1.1870 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 11.22 | 14.30 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | OfficeLarge | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 23 | 221 | 36 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | BASEMENT | 0.0 | 0.00 | 0.00 | 0.00 | 44.59 | 24.37 | -1.22 | 1 | 1 | 1 | 16.08 | 73.11 | 0.00 | 48.74 | -2.44 | 0.00 | 2.44 | 6779.02 | TARP | TARP | 2779.43 | 0.00 | 0.00 | 0.00 | 9 | 0 | 0 | Yes |
2 | CORE_BOTTOM | 0.0 | 0.00 | 0.00 | 0.00 | 37.01 | 24.37 | 1.37 | 1 | 1 | 1 | 5.49 | 68.53 | 4.57 | 44.17 | 0.00 | 2.74 | 2.74 | 6849.35 | TARP | TARP | 2496.12 | 0.00 | 0.00 | 0.00 | 7 | 0 | 0 | Yes |
3 | CORE_MID | 0.0 | 0.00 | 0.00 | 0.00 | 37.01 | 24.37 | 18.14 | 1 | 10 | 1 | 5.49 | 68.53 | 4.57 | 44.17 | 16.77 | 19.51 | 2.74 | 6849.35 | TARP | TARP | 2496.12 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
4 | CORE_TOP | 0.0 | 0.00 | 0.00 | 0.00 | 37.01 | 24.37 | 34.91 | 1 | 1 | 1 | 5.49 | 68.53 | 4.57 | 44.17 | 33.54 | 36.28 | 2.74 | 6849.35 | TARP | TARP | 2496.12 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
5 | PERIMETER_BOT_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 46.54 | 1.37 | 1 | 1 | 1 | 0.00 | 73.11 | 44.17 | 48.74 | 0.00 | 2.74 | 2.74 | 860.00 | TARP | TARP | 313.41 | 200.61 | 76.91 | 115.90 | 8 | 9 | 0 | Yes |
6 | PERIMETER_BOT_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 70.95 | 24.37 | 1.37 | 1 | 1 | 1 | 68.53 | 73.11 | 0.00 | 48.74 | 0.00 | 2.74 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 52.57 | 77.26 | 6 | 5 | 0 | Yes |
7 | PERIMETER_BOT_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 2.20 | 1.37 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 4.57 | 0.00 | 2.74 | 2.74 | 860.02 | TARP | TARP | 313.42 | 200.61 | 76.91 | 115.90 | 8 | 9 | 0 | Yes |
8 | PERIMETER_BOT_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.16 | 24.37 | 1.37 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 48.74 | 0.00 | 2.74 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 52.57 | 77.26 | 6 | 5 | 0 | Yes |
9 | PERIMETER_MID_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 46.54 | 18.14 | 1 | 10 | 1 | 0.00 | 73.11 | 44.17 | 48.74 | 16.77 | 19.51 | 2.74 | 860.00 | TARP | TARP | 313.41 | 200.61 | 84.71 | 115.90 | 7 | 1 | 0 | Yes |
10 | PERIMETER_MID_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 70.95 | 24.37 | 18.14 | 1 | 10 | 1 | 68.53 | 73.11 | 0.00 | 48.74 | 16.77 | 19.51 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 56.47 | 77.26 | 6 | 1 | 0 | Yes |
11 | PERIMETER_MID_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 2.20 | 18.14 | 1 | 10 | 1 | 0.00 | 73.11 | 0.00 | 4.57 | 16.77 | 19.51 | 2.74 | 860.02 | TARP | TARP | 313.42 | 200.61 | 84.71 | 115.90 | 7 | 1 | 0 | Yes |
12 | PERIMETER_MID_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.16 | 24.37 | 18.14 | 1 | 10 | 1 | 0.00 | 4.57 | 0.00 | 48.74 | 16.77 | 19.51 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 56.47 | 77.26 | 6 | 1 | 0 | Yes |
13 | PERIMETER_TOP_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 46.54 | 34.91 | 1 | 1 | 1 | 0.00 | 73.11 | 44.17 | 48.74 | 33.54 | 36.28 | 2.74 | 860.00 | TARP | TARP | 313.41 | 200.61 | 84.71 | 115.90 | 7 | 1 | 0 | Yes |
14 | PERIMETER_TOP_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 70.95 | 24.37 | 34.91 | 1 | 1 | 1 | 68.53 | 73.11 | 0.00 | 48.74 | 33.54 | 36.28 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 56.47 | 77.26 | 6 | 1 | 0 | Yes |
15 | PERIMETER_TOP_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 2.20 | 34.91 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 4.57 | 33.54 | 36.28 | 2.74 | 860.02 | TARP | TARP | 313.42 | 200.61 | 84.71 | 115.90 | 7 | 1 | 0 | Yes |
16 | PERIMETER_TOP_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.16 | 24.37 | 34.91 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 48.74 | 33.54 | 36.28 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 56.47 | 77.26 | 6 | 1 | 0 | Yes |
17 | GROUNDFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 24.37 | 3.35 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 48.74 | 2.74 | 3.96 | 1.22 | 4344.14 | TARP | TARP | 3563.11 | 297.11 | 297.11 | 0.00 | 11 | 0 | 0 | No |
18 | MIDFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 24.37 | 20.12 | 1 | 10 | 1 | 0.00 | 73.11 | 0.00 | 48.74 | 19.51 | 20.73 | 1.22 | 4344.14 | TARP | TARP | 3563.11 | 297.11 | 297.11 | 0.00 | 11 | 0 | 0 | No |
19 | TOPFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 24.37 | 36.89 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 48.74 | 36.28 | 37.50 | 1.22 | 4344.14 | TARP | TARP | 3563.11 | 297.11 | 297.11 | 0.00 | 11 | 0 | 0 | No |
20 | DATACENTER_BOT_ZN_6 | 0.0 | 5.49 | 44.17 | 0.00 | 5.03 | 24.37 | 1.37 | 1 | 1 | 1 | 4.57 | 5.49 | 4.57 | 44.17 | 0.00 | 2.74 | 2.74 | 99.34 | TARP | TARP | 36.20 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
21 | DATACENTER_MID_ZN_6 | 0.0 | 4.57 | 4.57 | 16.77 | 5.03 | 24.37 | 18.14 | 1 | 10 | 1 | 4.57 | 5.49 | 4.57 | 44.17 | 16.77 | 19.51 | 2.74 | 99.34 | TARP | TARP | 36.20 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
22 | DATACENTER_TOP_ZN_6 | 0.0 | 4.57 | 4.57 | 33.54 | 5.03 | 24.37 | 34.91 | 1 | 1 | 1 | 4.57 | 5.49 | 4.57 | 44.17 | 33.54 | 36.28 | 2.74 | 99.34 | TARP | TARP | 36.20 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
23 | DATACENTER_BASEMENT_ZN_6 | 0.0 | 16.08 | 0.00 | -2.44 | 8.04 | 24.37 | -1.22 | 1 | 1 | 1 | 0.00 | 16.08 | 0.00 | 48.74 | -2.44 | 0.00 | 2.44 | 1911.37 | TARP | TARP | 783.68 | 0.00 | 0.00 | 0.00 | 10 | 0 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | BASEMENT | 2779.43 | 149.6 | 18.579 | 5.382E-002 | 10.273 | 4.842 | 0.000 | 0.000 | 0.000 | 0.000 | 15.115 | No |
2 | CORE_BOTTOM | 2496.12 | 134.4 | 18.579 | 5.382E-002 | 10.273 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 18.343 | No |
3 | CORE_MID | 2496.12 | 134.4 | 18.579 | 5.382E-002 | 10.273 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 18.343 | No |
4 | CORE_TOP | 2496.12 | 134.4 | 18.579 | 5.382E-002 | 10.273 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 18.343 | No |
5 | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 18.579 | 5.382E-002 | 10.273 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 18.343 | No |
6 | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 10.273 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 18.343 | No |
7 | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 18.579 | 5.382E-002 | 10.273 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 18.343 | No |
8 | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 10.273 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 18.343 | No |
9 | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 18.579 | 5.382E-002 | 10.273 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 18.343 | No |
10 | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 10.273 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 18.343 | No |
11 | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 18.579 | 5.382E-002 | 10.273 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 18.343 | No |
12 | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 10.273 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 18.343 | No |
13 | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 18.579 | 5.382E-002 | 10.273 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 18.343 | No |
14 | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 10.273 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 18.343 | No |
15 | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 18.579 | 5.382E-002 | 10.273 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 18.343 | No |
16 | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 10.273 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 18.343 | No |
17 | GROUNDFLOOR_PLENUM | 3563.11 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
18 | MIDFLOOR_PLENUM | 3563.11 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
19 | TOPFLOOR_PLENUM | 3563.11 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
20 | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 18.579 | 5.382E-002 | 17.873 | 215.299 | 0.000 | 0.000 | 0.000 | 0.000 | 233.173 | No |
21 | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 18.579 | 5.382E-002 | 17.873 | 215.299 | 0.000 | 0.000 | 0.000 | 0.000 | 233.173 | No |
22 | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 18.579 | 5.382E-002 | 17.873 | 215.299 | 0.000 | 0.000 | 0.000 | 0.000 | 233.173 | No |
23 | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 18.579 | 5.382E-002 | 10.273 | 484.423 | 0.000 | 0.000 | 0.000 | 0.000 | 494.696 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | DATACENTER_BOT_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 1.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | DATACENTER_MID_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 1.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
3 | DATACENTER_TOP_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 1.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
4 | DATACENTER_BASEMENT_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 42.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 42 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
5 | BASEMENT | BLDG_OCC_SCH_WO_SB | BASEMENT | 2779.43 | 149.6 | 149.6 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 150 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
6 | CORE_BOTTOM | BLDG_OCC_SCH_WO_SB | CORE_BOTTOM | 2496.12 | 134.4 | 134.4 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 134 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
7 | CORE_MID | BLDG_OCC_SCH_WO_SB | CORE_MID | 2496.12 | 134.4 | 134.4 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 134 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
8 | CORE_TOP | BLDG_OCC_SCH_WO_SB | CORE_TOP | 2496.12 | 134.4 | 134.4 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 134 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
9 | PERIMETER_BOT_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
10 | PERIMETER_BOT_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
11 | PERIMETER_BOT_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
12 | PERIMETER_BOT_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
13 | PERIMETER_MID_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
14 | PERIMETER_MID_ZN_2 | BLDG_OCC_SCH_W_SB | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
15 | PERIMETER_MID_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
16 | PERIMETER_MID_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
17 | PERIMETER_TOP_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
18 | PERIMETER_TOP_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
19 | PERIMETER_TOP_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
20 | PERIMETER_TOP_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | BASEMENT_LIGHTS | LTG_SCH_OFFICE | BASEMENT | 2779.43 | 149.6 | 28553.717 | 10.273 | 190.864 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 28553.717 |
2 | CORE_BOTTOM_LIGHTS | LTG_SCH_OFFICE | CORE_BOTTOM | 2496.12 | 134.4 | 25643.245 | 10.273 | 190.864 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 25643.245 |
3 | CORE_MID_LIGHTS | LTG_SCH_OFFICE | CORE_MID | 2496.12 | 134.4 | 25643.245 | 10.273 | 190.864 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 25643.245 |
4 | CORE_TOP_LIGHTS | LTG_SCH_OFFICE | CORE_TOP | 2496.12 | 134.4 | 25643.245 | 10.273 | 190.864 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 25643.245 |
5 | PERIMETER_BOT_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 3219.765 | 10.273 | 190.864 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3219.765 |
6 | PERIMETER_BOT_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 2074.939 | 10.273 | 190.864 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2074.939 |
7 | PERIMETER_BOT_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 3219.836 | 10.273 | 190.864 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3219.836 |
8 | PERIMETER_BOT_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 2074.939 | 10.273 | 190.864 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2074.939 |
9 | PERIMETER_MID_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 3219.765 | 10.273 | 190.864 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3219.765 |
10 | PERIMETER_MID_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 2074.939 | 10.273 | 190.864 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2074.939 |
11 | PERIMETER_MID_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 3219.836 | 10.273 | 190.864 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3219.836 |
12 | PERIMETER_MID_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 2074.939 | 10.273 | 190.864 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2074.939 |
13 | PERIMETER_TOP_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 3219.765 | 10.273 | 190.864 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3219.765 |
14 | PERIMETER_TOP_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 2074.939 | 10.273 | 190.864 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2074.939 |
15 | PERIMETER_TOP_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 3219.836 | 10.273 | 190.864 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3219.836 |
16 | PERIMETER_TOP_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 2074.939 | 10.273 | 190.864 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2074.939 |
17 | DATACENTER_BASEMENT_LIGHTS | LTG_SCH_OFFICE | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 8050.927 | 10.273 | 190.864 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 8050.927 |
18 | DATACENTER_BOT_LIGHTS | LTG_SCH_DATACENTER | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 647.068 | 17.873 | 332.067 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 647.068 |
19 | DATACENTER_MID_LIGHTS | LTG_SCH_DATACENTER | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 647.068 | 17.873 | 332.067 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 647.068 |
20 | DATACENTER_TOP_LIGHTS | LTG_SCH_DATACENTER | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 647.068 | 17.873 | 332.067 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 647.068 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | BASEMENT_MISCPLUG_EQUIP | ALWAYS_ON | BASEMENT | 2779.43 | 149.6 | 13457.544 | 4.842 | 89.956 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 13457.544 | 13457.544 |
2 | CORE_BOTTOM_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_BOTTOM | 2496.12 | 134.4 | 20142.877 | 8.070 | 149.925 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 20142.877 |
3 | CORE_MID_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_MID | 2496.12 | 134.4 | 20142.800 | 8.070 | 149.924 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 20142.800 |
4 | CORE_TOP_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_TOP | 2496.12 | 134.4 | 20142.800 | 8.070 | 149.924 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 20142.800 |
5 | PERIMETER_BOT_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 2529.242 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.242 |
6 | PERIMETER_BOT_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 1629.940 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.940 |
7 | PERIMETER_BOT_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 2529.281 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.281 |
8 | PERIMETER_BOT_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 1629.929 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.929 |
9 | PERIMETER_MID_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 2529.242 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.242 |
10 | PERIMETER_MID_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 1629.940 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.940 |
11 | PERIMETER_MID_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 2529.281 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.281 |
12 | PERIMETER_MID_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 1629.929 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.929 |
13 | PERIMETER_TOP_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 2529.242 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.242 |
14 | PERIMETER_TOP_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 1629.940 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.940 |
15 | PERIMETER_TOP_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 2529.281 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.281 |
16 | PERIMETER_TOP_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 1629.929 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.929 |
17 | DATACENTER_BASEMENT_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 379632.522 | 484.423 | 9000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 94908.130 | 379632.522 |
18 | DATACENTER_BOT_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 7794.422 | 215.299 | 4000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 1948.606 | 7794.422 |
19 | DATACENTER_MID_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 7794.422 | 215.299 | 4000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 1948.606 | 7794.422 |
20 | DATACENTER_TOP_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 7794.422 | 215.299 | 4000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 1948.606 | 7794.422 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 2.839 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | INTERIORFURNISHINGS | 2 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
3 | DROPCEILING | 4 | 1 | 3 | 0.167 | 4.488 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
4 | INT_WALL | 7 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | EXT_SLAB_8IN_WITH_CARPET | 8 | 2 | 7 | 0.167 | 3.285 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
6 | INT_SLAB_FLOOR | 12 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
7 | INT_SLAB_CEILING | 13 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | VeryRough |
8 | NONRES_ROOF | 17 | 3 | 3 | 0.167 | 0.1864 | 0.900 | 0.900 | 0.700 | 0.700 | Rough |
9 | NONRES_EXT_WALL_GRD | 20 | 3 | 9 | 0.167 | 1.075 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
10 | NONRES_EXT_WALL_MID | 21 | 3 | 9 | 0.167 | 1.028 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
11 | NONRES_EXT_WALL_TOP | 22 | 3 | 9 | 0.167 | 1.266 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
12 | BASEMENT_WALL_EAST_CFACTOR | 39 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | BASEMENT_WALL_SOUTH_CFACTOR | 40 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | BASEMENT_WALL_NORTH_CFACTOR | 41 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR | 42 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
16 | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR | 43 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
17 | DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR | 44 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.3522 |
2 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
3 | AC02 ACOUSTIC CEILING | 0.0127 | 0.057 | 288.000 | 1339.000 | 0.2228 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | 200MM NORMALWEIGHT CONCRETE FLOOR | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
7 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
8 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
9 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
10 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
11 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
12 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
13 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 5.307 |
14 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
15 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
16 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.7632 |
17 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
18 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
19 | NONRES_EXTERIOR_WALL_INSULATION_MID | 0.0000 | 0.000 | 0.000 | 0.000 | 0.8055 |
20 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
21 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
22 | NONRES_EXTERIOR_WALL_INSULATION_TOP | 0.0000 | 0.000 | 0.000 | 0.000 | 0.6228 |
23 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
24 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
25 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
26 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
27 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
28 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
29 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
30 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
31 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
32 | ~FC_Insulation_5 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
33 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
34 | ~FC_Insulation_6 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
35 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 2.8391315 | 2.8391315 | 2.8391315 | |
3 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
4 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
5 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
6 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
7 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
8 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
9 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
10 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
11 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
12 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
13 | 3 | -0.21589802E-09 | 0.15643069E-09 | -0.21589802E-09 | 0.12999471E-21 |
14 | 2 | 0.50772448E-02 | 0.30006816E-02 | 0.50772448E-02 | -0.13693132E-08 |
15 | 1 | -2.5944910 | 1.4597758 | -2.5944910 | 0.76344767E-02 |
16 | 0 | 7.0433378 | 2.9911476 | 7.0433378 | |
17 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
18 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
19 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
20 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
21 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
22 | 7 | -0.18651654E-16 | -0.16428647E-15 | -0.26578847E-08 | -0.25364002E-17 |
23 | 6 | 0.67402962E-01 | 0.99142722E-07 | 0.38101547E-02 | -0.76639482E-03 |
24 | 5 | -1.8580732 | 0.49502125E-04 | -0.10651409 | 0.21891119E-01 |
25 | 4 | 18.220105 | 0.12801333E-02 | 1.0775450 | -0.22586539 |
26 | 3 | -79.928293 | 0.66708484E-02 | -4.9803755 | 1.0625663 |
27 | 2 | 166.43177 | 0.75131194E-02 | 11.128837 | -2.4125483 |
28 | 1 | -159.97298 | 0.18548900E-02 | -11.587784 | 2.5494418 |
29 | 0 | 57.057412 | 0.52755123E-04 | 4.4818272 | |
30 | 7 | 0.43260499E-16 | 0.34524919E-16 | 0.52793240E-17 | 0.0000000 |
31 | 6 | 0.69434179E-09 | 0.98085174E-11 | 0.18162501E-10 | -0.40870994E-12 |
32 | 5 | -0.12888762E-04 | 0.28373718E-06 | -0.16918523E-06 | 0.92361873E-08 |
33 | 4 | 0.25174112E-01 | 0.33697681E-03 | 0.22646198E-03 | -0.31467795E-04 |
34 | 3 | -3.7600775 | 0.27170599E-01 | -0.48495626E-01 | 0.94171705E-02 |
35 | 2 | 51.553741 | 0.22121684 | 1.2284947 | -0.25833933 |
36 | 1 | -128.86110 | 0.21944682 | -5.1479470 | 1.1228340 |
37 | 0 | 81.526494 | 0.16043334E-01 | 4.4519351 | |
38 | 7 | 0.52793240E-17 | 0.34524919E-16 | 0.43260499E-16 | 0.0000000 |
39 | 6 | 0.18162501E-10 | 0.98085174E-11 | 0.69434179E-09 | -0.40870994E-12 |
40 | 5 | -0.16918523E-06 | 0.28373718E-06 | -0.12888762E-04 | 0.92361873E-08 |
41 | 4 | 0.22646198E-03 | 0.33697681E-03 | 0.25174112E-01 | -0.31467795E-04 |
42 | 3 | -0.48495626E-01 | 0.27170599E-01 | -3.7600775 | 0.94171705E-02 |
43 | 2 | 1.2284947 | 0.22121684 | 51.553741 | -0.25833933 |
44 | 1 | -5.1479470 | 0.21944682 | -128.86110 | 1.1228340 |
45 | 0 | 4.4519351 | 0.16043334E-01 | 81.526494 | |
46 | 3 | -0.62854340E-06 | 0.84784826E-09 | -0.38512804E-05 | 0.91756347E-17 |
47 | 2 | 0.78257096 | 0.11428808E-02 | 1.0614277 | -0.73836085E-06 |
48 | 1 | -21.991499 | 0.76199851E-01 | -6.3161914 | 0.20349372 |
49 | 0 | 21.357363 | 0.71091016E-01 | 5.4032014 | |
50 | 9 | -0.34463022E-15 | 0.36894385E-16 | -0.14288780E-09 | 0.12757077E-17 |
51 | 8 | 0.20913840E-07 | 0.14359092E-12 | 0.36762620E-03 | -0.23779757E-09 |
52 | 7 | -0.11937955E-01 | 0.75343451E-08 | -0.22648608E-01 | 0.13573889E-03 |
53 | 6 | 0.39710065 | 0.26364580E-05 | 0.46505929 | -0.46505182E-02 |
54 | 5 | -5.1100523 | 0.98937734E-04 | -4.3872286 | 0.62185548E-01 |
55 | 4 | 32.646709 | 0.81302423E-03 | 21.229086 | -0.41739428 |
56 | 3 | -110.46842 | 0.17791168E-02 | -55.206350 | 1.5042464 |
57 | 2 | 196.38009 | 0.10043743E-02 | 77.491871 | -2.8887901 |
58 | 1 | -170.88709 | 0.10757908E-03 | -55.143519 | 2.7407251 |
59 | 0 | 57.057407 | 0.61468164E-06 | 15.577169 | |
60 | 9 | -0.22955380E-15 | 0.37743381E-16 | -0.14509256E-09 | 0.32676096E-18 |
61 | 8 | 0.21224167E-07 | 0.13772622E-12 | 0.37092755E-03 | -0.24132609E-09 |
62 | 7 | -0.12036605E-01 | 0.72012381E-08 | -0.22790691E-01 | 0.13686058E-03 |
63 | 6 | 0.39978134 | 0.25163753E-05 | 0.46734577 | -0.46821170E-02 |
64 | 5 | -5.1362151 | 0.94318005E-04 | -4.4048053 | 0.62509952E-01 |
65 | 4 | 32.762449 | 0.77422319E-03 | 21.297824 | -0.41893096 |
66 | 3 | -110.71472 | 0.16925811E-02 | -55.342260 | 1.5078047 |
67 | 2 | 196.62425 | 0.95470525E-03 | 77.616458 | -2.8926672 |
68 | 1 | -170.97729 | 0.10217823E-03 | -55.179630 | 2.7423060 |
69 | 0 | 57.057407 | 0.58332056E-06 | 15.571109 | |
70 | 9 | 0.11276195E-14 | 0.47405760E-16 | -0.13382366E-09 | -0.64614724E-17 |
71 | 8 | 0.19634610E-07 | 0.16705312E-12 | 0.35383761E-03 | -0.22325229E-09 |
72 | 7 | -0.11525316E-01 | 0.88979655E-08 | -0.22054087E-01 | 0.13104703E-03 |
73 | 6 | 0.38588679 | 0.31323747E-05 | 0.45547913 | -0.45183345E-02 |
74 | 5 | -5.0005974 | 0.11815564E-03 | -4.3135163 | 0.60828376E-01 |
75 | 4 | 32.162433 | 0.97545471E-03 | 20.940665 | -0.41096462 |
76 | 3 | -109.43770 | 0.21433374E-02 | -54.636007 | 1.4893559 |
77 | 2 | 195.35810 | 0.12144036E-02 | 76.969321 | -2.8725616 |
78 | 1 | -170.50942 | 0.13051365E-03 | -54.992579 | 2.7341060 |
79 | 0 | 57.057407 | 0.74839837E-06 | 15.602923 | |
80 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
81 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
82 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
83 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
84 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
85 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
86 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
87 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 | |
88 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
89 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
90 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
91 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
92 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
93 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
94 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
95 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 | |
96 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
97 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
98 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
99 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
100 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
101 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
102 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
103 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 | |
104 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
105 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
106 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
107 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
108 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
109 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
110 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
111 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 | |
112 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
113 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
114 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
115 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
116 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
117 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
118 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
119 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 | |
120 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
121 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
122 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
123 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
124 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
125 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
126 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
127 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | WINDOW_U_0.42_SHGC_EAST_0.4 | 35 | 1 | VerySmooth | 2.387 | 2.387 | 1.000 | 0.401 | ||
2 | WINDOW_U_0.42_SHGC_SOUTH_0.4 | 36 | 1 | VerySmooth | 2.387 | 2.387 | 1.000 | 0.401 | ||
3 | WINDOW_U_0.42_SHGC_WEST_0.4 | 37 | 1 | VerySmooth | 2.387 | 2.387 | 1.000 | 0.401 | ||
4 | WINDOW_U_0.42_SHGC_NORTH_0.4 | 38 | 1 | VerySmooth | 2.387 | 2.387 | 1.000 | 0.401 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | GLAZING LAYER EAST | SpectralAverage | 3.02786E-002 | 0.31435 | 0.47495 | 0.47495 | 0.44000 | 0.13397 | 0.17027 | 0.00000 | 0.84000 | 0.84000 | 0.12239 | 1.00000 | No | |
2 | GLAZING LAYER SOUTH | SpectralAverage | 3.02786E-002 | 0.31435 | 0.47495 | 0.47495 | 0.44000 | 0.13397 | 0.17027 | 0.00000 | 0.84000 | 0.84000 | 0.12239 | 1.00000 | No | |
3 | GLAZING LAYER WEST | SpectralAverage | 3.02786E-002 | 0.31435 | 0.47495 | 0.47495 | 0.44000 | 0.13397 | 0.17027 | 0.00000 | 0.84000 | 0.84000 | 0.12239 | 1.00000 | No | |
4 | GLAZING LAYER NORTH | SpectralAverage | 3.02786E-002 | 0.31435 | 0.47495 | 0.47495 | 0.44000 | 0.13397 | 0.17027 | 0.00000 | 0.84000 | 0.84000 | 0.12239 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 30 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Enclosure Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Enclosures | |
1 | PERIMETER_BOT_ZN_3 | 5 | 0 |
2 | PERIMETER_BOT_ZN_2 | 3 | 0 |
3 | PERIMETER_BOT_ZN_1 | 5 | 0 |
4 | PERIMETER_BOT_ZN_4 | 3 | 0 |
5 | PERIMETER_MID_ZN_3 | 1 | 0 |
6 | PERIMETER_MID_ZN_2 | 1 | 0 |
7 | PERIMETER_MID_ZN_1 | 1 | 0 |
8 | PERIMETER_MID_ZN_4 | 1 | 0 |
9 | PERIMETER_TOP_ZN_3 | 1 | 0 |
10 | PERIMETER_TOP_ZN_2 | 1 | 0 |
11 | PERIMETER_TOP_ZN_1 | 1 | 0 |
12 | PERIMETER_TOP_ZN_4 | 1 | 0 |
Enclosure Name | Number of Adjacent Enclosures with Windows | Adjacent Enclosure Names - 1st 100 (max) | |
1 | PERIMETER_BOT_ZN_3 | 0 | |
2 | PERIMETER_BOT_ZN_2 | 0 | |
3 | PERIMETER_BOT_ZN_1 | 0 | |
4 | PERIMETER_BOT_ZN_4 | 0 | |
5 | PERIMETER_MID_ZN_3 | 0 | |
6 | PERIMETER_MID_ZN_2 | 0 | |
7 | PERIMETER_MID_ZN_1 | 0 | |
8 | PERIMETER_MID_ZN_4 | 0 | |
9 | PERIMETER_TOP_ZN_3 | 0 | |
10 | PERIMETER_TOP_ZN_2 | 0 | |
11 | PERIMETER_TOP_ZN_1 | 0 | |
12 | PERIMETER_TOP_ZN_4 | 0 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 1.1356 | 87921.3 | 0.481 | 5.5005E-002 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | BASEMENT_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
2 | BASEMENT_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
3 | BASEMENT_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
4 | BASEMENT_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
5 | BASEMENT_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
6 | PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
7 | PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
8 | CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
9 | PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
10 | BASEMENT_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
11 | CORE_BOT_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
12 | CORE_BOT_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
13 | CORE_BOT_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
14 | CORE_BOT_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
15 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
16 | CORE_BOT_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
17 | CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
18 | CORE_BOTTOM_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
19 | CORE_MID_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
20 | CORE_MID_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
21 | CORE_MID_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
22 | CORE_MID_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
23 | CORE_MID_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
24 | CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
25 | CORE_MID_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
26 | CORE_TOP_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
27 | CORE_TOP_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
28 | CORE_TOP_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
29 | CORE_TOP_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
30 | CORE_TOP_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
31 | CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
32 | CORE_TOP_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
33 | PERIMETER_BOT_ZN_3_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
34 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
35 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
36 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
37 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
38 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
39 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
40 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
41 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
42 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
43 | PERIMETER_BOT_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
44 | CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
45 | PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
46 | DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
47 | PERIMETER_BOT_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
48 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
49 | PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
50 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
51 | PERIMETER_BOT_ZN_2_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
52 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
53 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
54 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
55 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
56 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
57 | PERIMETER_BOT_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
58 | CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
59 | PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
60 | PERIMETER_BOT_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
61 | PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
62 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
63 | PERIMETER_BOT_ZN_1_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
64 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
65 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
66 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
67 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
68 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
69 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
70 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
71 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
72 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
73 | PERIMETER_BOT_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
74 | DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
75 | PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
76 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
77 | DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
78 | PERIMETER_BOT_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
79 | PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
80 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
81 | PERIMETER_BOT_ZN_4_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
82 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
83 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
84 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
85 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
86 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
87 | PERIMETER_BOT_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
88 | DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
89 | PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
90 | PERIMETER_BOT_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
91 | PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
92 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
93 | PERIMETER_MID_ZN_3_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
94 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
95 | PERIMETER_MID_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
96 | CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
97 | PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
98 | DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
99 | PERIMETER_MID_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
100 | PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
101 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
102 | PERIMETER_MID_ZN_2_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
103 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
104 | PERIMETER_MID_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
105 | CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
106 | PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
107 | PERIMETER_MID_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
108 | PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
109 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
110 | PERIMETER_MID_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
111 | PERIMETER_MID_ZN_1_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
112 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
113 | DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
114 | PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
115 | CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
116 | PERIMETER_MID_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
117 | PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
118 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
119 | PERIMETER_MID_ZN_4_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
120 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
121 | PERIMETER_MID_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
122 | DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
123 | PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
124 | PERIMETER_MID_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
125 | PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
126 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
127 | PERIMETER_TOP_ZN_3_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
128 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
129 | PERIMETER_TOP_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
130 | CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
131 | PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
132 | DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
133 | PERIMETER_TOP_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
134 | PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
135 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
136 | PERIMETER_TOP_ZN_2_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
137 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
138 | PERIMETER_TOP_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
139 | CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
140 | INT-PER3S-NE-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
141 | PERIMETER_TOP_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
142 | PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
143 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
144 | PERIMETER_TOP_ZN_1_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
145 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
146 | INT-PER3S-NE | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
147 | DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
148 | PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
149 | CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
150 | PERIMETER_TOP_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
151 | PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
152 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
153 | PERIMETER_TOP_ZN_4_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
154 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
155 | PERIMETER_TOP_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
156 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
157 | PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
158 | PERIMETER_TOP_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
159 | PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
160 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
161 | GROUNDFLOOR_PLENUM_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
162 | GROUNDFLOOR_PLENUM_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
163 | GROUNDFLOOR_PLENUM_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
164 | GROUNDFLOOR_PLENUM_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
165 | iz-CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
166 | iz-PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
167 | iz-PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
168 | iz-PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
169 | iz-PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
170 | iz-DATACENTER_BOT_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
171 | GROUNDFLOOR_PLENUM_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
172 | MIDFLOOR_PLENUM_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
173 | MIDFLOOR_PLENUM_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
174 | MIDFLOOR_PLENUM_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
175 | MIDFLOOR_PLENUM_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
176 | iz-CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
177 | iz-PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
178 | iz-PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
179 | iz-PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
180 | iz-PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
181 | iz-DATACENTER_MID_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
182 | MIDFLOOR_PLENUM_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
183 | TOPFLOOR_PLENUM_WALL_NORTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
184 | TOPFLOOR_PLENUM_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
185 | TOPFLOOR_PLENUM_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
186 | TOPFLOOR_PLENUM_WALL_SOUTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
187 | iz-CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
188 | iz-PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
189 | iz-PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
190 | iz-PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
191 | iz-PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
192 | iz-DATACENTER_TOP_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
193 | BUILDING_ROOF | 0 | 3563.11 | 268.06 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
194 | DATACENTER_BOT_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
195 | DATACENTER_BOT_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
196 | DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
197 | DATACENTER_BOT_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
198 | DATACENTER_BOT_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
199 | DATACENTER_BOT_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
200 | DATACENTER_MID_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
201 | DATACENTER_MID_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
202 | DATACENTER_MID_ZN_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
203 | DATACENTER_MID_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
204 | DATACENTER_MID_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
205 | DATACENTER_MID_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
206 | DATACENTER_TOP_ZN_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
207 | DATACENTER_TOP_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
208 | DATACENTER_TOP_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
209 | DATACENTER_TOP_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
210 | DATACENTER_TOP_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
211 | DATACENTER_TOP_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
212 | DATACENTER_BASEMENT_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
213 | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
214 | DATACENTER_BASEMENT_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
215 | DATACENTER_BASEMENT_ZN_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
216 | DATACENTER_BASEMENT_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
217 | DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
218 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
219 | PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
220 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
221 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | PERIMETER_BOT_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 0.114 | 3.646E-004 | 5.482E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | PERIMETER_BOT_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 7.617E-002 | 3.771E-004 | 5.534E-004 | 0.495 | 0.000 | 0.000 | 0.224 | 0.000 |
3 | PERIMETER_BOT_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 0.114 | 3.646E-004 | 5.482E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | PERIMETER_BOT_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 7.617E-002 | 3.771E-004 | 5.534E-004 | 0.495 | 0.000 | 0.000 | 0.224 | 0.000 |
5 | PERIMETER_MID_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 0.114 | 3.646E-004 | 5.696E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
6 | PERIMETER_MID_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 7.617E-002 | 3.771E-004 | 5.696E-004 | 0.495 | 0.000 | 0.000 | 0.224 | 0.000 |
7 | PERIMETER_MID_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 0.114 | 3.646E-004 | 5.696E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
8 | PERIMETER_MID_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 7.617E-002 | 3.771E-004 | 5.696E-004 | 0.495 | 0.000 | 0.000 | 0.224 | 0.000 |
9 | PERIMETER_TOP_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 0.114 | 3.646E-004 | 5.696E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
10 | PERIMETER_TOP_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 7.617E-002 | 3.771E-004 | 5.696E-004 | 0.495 | 0.000 | 0.000 | 0.224 | 0.000 |
11 | PERIMETER_TOP_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 0.114 | 3.646E-004 | 5.696E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
12 | PERIMETER_TOP_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 7.617E-002 | 3.771E-004 | 5.696E-004 | 0.495 | 0.000 | 0.000 | 0.224 | 0.000 |
13 | GROUNDFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | GROUNDFLOOR_PLENUM | 3563.11 | 0.0 | 0.169 | 4.749E-005 | 5.696E-004 | 0.140 | 0.000 | 0.000 | 0.224 | 0.000 |
14 | MIDFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | MIDFLOOR_PLENUM | 3563.11 | 0.0 | 0.169 | 4.749E-005 | 5.696E-004 | 0.140 | 0.000 | 0.000 | 0.224 | 0.000 |
15 | TOPFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | TOPFLOOR_PLENUM | 3563.11 | 0.0 | 0.169 | 4.749E-005 | 4.384E-005 | 0.140 | 0.000 | 0.000 | 0.224 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | BASEMENT | Mixing/Well-Stirred |
2 | CORE_BOTTOM | Mixing/Well-Stirred |
3 | CORE_MID | Mixing/Well-Stirred |
4 | CORE_TOP | Mixing/Well-Stirred |
5 | PERIMETER_BOT_ZN_3 | Mixing/Well-Stirred |
6 | PERIMETER_BOT_ZN_2 | Mixing/Well-Stirred |
7 | PERIMETER_BOT_ZN_1 | Mixing/Well-Stirred |
8 | PERIMETER_BOT_ZN_4 | Mixing/Well-Stirred |
9 | PERIMETER_MID_ZN_3 | Mixing/Well-Stirred |
10 | PERIMETER_MID_ZN_2 | Mixing/Well-Stirred |
11 | PERIMETER_MID_ZN_1 | Mixing/Well-Stirred |
12 | PERIMETER_MID_ZN_4 | Mixing/Well-Stirred |
13 | PERIMETER_TOP_ZN_3 | Mixing/Well-Stirred |
14 | PERIMETER_TOP_ZN_2 | Mixing/Well-Stirred |
15 | PERIMETER_TOP_ZN_1 | Mixing/Well-Stirred |
16 | PERIMETER_TOP_ZN_4 | Mixing/Well-Stirred |
17 | GROUNDFLOOR_PLENUM | Mixing/Well-Stirred |
18 | MIDFLOOR_PLENUM | Mixing/Well-Stirred |
19 | TOPFLOOR_PLENUM | Mixing/Well-Stirred |
20 | DATACENTER_BOT_ZN_6 | Mixing/Well-Stirred |
21 | DATACENTER_MID_ZN_6 | Mixing/Well-Stirred |
22 | DATACENTER_TOP_ZN_6 | Mixing/Well-Stirred |
23 | DATACENTER_BASEMENT_ZN_6 | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sky Type | MonthAndDay | Daylighting Control Name | Enclosure Name | Window Name | Reference Point | Daylight Factor | |
1 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 7.9692E-003 |
2 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 7.9717E-003 |
3 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 8.9889E-003 |
4 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 8.9911E-003 |
5 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.9362E-003 |
6 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.9379E-003 |
7 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.7740E-003 |
8 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.7748E-003 |
9 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 8.0272E-003 |
10 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 8.2015E-003 |
11 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 9.0391E-003 |
12 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 9.1955E-003 |
13 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.9781E-003 |
14 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 5.1011E-003 |
15 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.7969E-003 |
16 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.8551E-003 |
17 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 0.1845 |
18 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 0.1051 |
19 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 0.2124 |
20 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 0.1231 |
21 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 0.1178 |
22 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.9362E-002 |
23 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 5.0165E-002 |
24 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.7447E-002 |
25 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 8.0305E-003 |
26 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 8.2175E-003 |
27 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 9.0425E-003 |
28 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 9.2125E-003 |
29 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.9807E-003 |
30 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 5.1109E-003 |
31 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.7974E-003 |
32 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.8568E-003 |
33 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 7.9689E-003 |
34 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 7.9715E-003 |
35 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 8.9886E-003 |
36 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 8.9909E-003 |
37 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.9360E-003 |
38 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.9378E-003 |
39 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.7739E-003 |
40 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.7747E-003 |
41 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 6.4710E-003 |
42 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 6.9182E-003 |
43 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 6.2240E-003 |
44 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 6.7426E-003 |
45 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 5.6744E-003 |
46 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 5.8233E-003 |
47 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 4.7428E-003 |
48 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 4.7830E-003 |
49 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 7.1891E-002 |
50 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.5745E-002 |
51 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 6.7622E-002 |
52 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.2865E-002 |
53 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 6.8267E-002 |
54 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 2.8661E-002 |
55 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 5.2230E-002 |
56 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 1.9536E-002 |
57 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 6.3009E-003 |
58 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 6.4289E-003 |
59 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 5.9968E-003 |
60 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 6.0904E-003 |
61 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 5.6264E-003 |
62 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 5.6611E-003 |
63 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 4.7430E-003 |
64 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 4.7836E-003 |
65 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.1083E-003 |
66 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 3.1107E-003 |
67 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.6275E-003 |
68 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.6294E-003 |
69 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.2865E-003 |
70 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.2880E-003 |
71 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.7740E-003 |
72 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.7749E-003 |
73 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.1626E-003 |
74 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 3.3051E-003 |
75 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.6724E-003 |
76 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.7867E-003 |
77 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.3225E-003 |
78 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.4032E-003 |
79 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.7975E-003 |
80 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.8569E-003 |
81 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 5.2021E-002 |
82 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.7517E-002 |
83 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.9974E-002 |
84 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.0906E-002 |
85 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.5424E-002 |
86 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.3698E-002 |
87 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 5.0165E-002 |
88 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.7442E-002 |
89 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.1612E-003 |
90 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 3.3023E-003 |
91 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.6709E-003 |
92 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.7832E-003 |
93 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.3204E-003 |
94 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.3969E-003 |
95 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.7969E-003 |
96 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.8551E-003 |
97 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.1081E-003 |
98 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 3.1105E-003 |
99 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.6273E-003 |
100 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.6293E-003 |
101 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.2864E-003 |
102 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.2878E-003 |
103 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.7739E-003 |
104 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.7748E-003 |
105 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 6.1160E-003 |
106 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 6.2453E-003 |
107 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 5.7565E-003 |
108 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 5.8509E-003 |
109 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 5.5026E-003 |
110 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 5.5365E-003 |
111 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 4.7431E-003 |
112 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 4.7837E-003 |
113 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 6.8690E-002 |
114 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.4397E-002 |
115 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 6.3487E-002 |
116 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.1117E-002 |
117 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 6.5983E-002 |
118 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.7714E-002 |
119 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 5.2230E-002 |
120 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 1.9536E-002 |
121 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 6.2707E-003 |
122 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 6.6738E-003 |
123 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 5.9636E-003 |
124 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 6.4242E-003 |
125 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 5.5494E-003 |
126 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 5.6937E-003 |
127 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 4.7428E-003 |
128 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 4.7829E-003 |
129 | Clear Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 0.1808 |
130 | Clear Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 0.1379 |
131 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 0.2012 |
132 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 0.1588 |
133 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 0.1318 |
134 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 7.2292E-002 |
135 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 6.1425E-002 |
136 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 3.0380E-002 |
137 | Clear Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 8.5590E-002 |
138 | Clear Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 5.1322E-002 |
139 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 8.0854E-002 |
140 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 4.7907E-002 |
141 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 8.0880E-002 |
142 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 4.2098E-002 |
143 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 6.2997E-002 |
144 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 3.0728E-002 |
145 | Clear Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 6.3937E-002 |
146 | Clear Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 4.2515E-002 |
147 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 5.0333E-002 |
148 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 3.3510E-002 |
149 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 4.5400E-002 |
150 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 2.4490E-002 |
151 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 6.1425E-002 |
152 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 3.0375E-002 |
153 | Clear Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 8.1959E-002 |
154 | Clear Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 4.9449E-002 |
155 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 7.6161E-002 |
156 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 4.5474E-002 |
157 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 7.8323E-002 |
158 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 4.0849E-002 |
159 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 6.2997E-002 |
160 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 3.0728E-002 |
161 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 0.1808 |
162 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 0.1381 |
163 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 0.2012 |
164 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 0.1591 |
165 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 0.1320 |
166 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 7.2460E-002 |
167 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 6.1557E-002 |
168 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 3.0447E-002 |
169 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 8.5637E-002 |
170 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 5.1399E-002 |
171 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 8.0907E-002 |
172 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 4.7981E-002 |
173 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 8.1001E-002 |
174 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 4.2186E-002 |
175 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 6.3129E-002 |
176 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 3.0795E-002 |
177 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 6.3940E-002 |
178 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 4.2565E-002 |
179 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 5.0340E-002 |
180 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 3.3549E-002 |
181 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 4.5473E-002 |
182 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 2.4537E-002 |
183 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 6.1557E-002 |
184 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 3.0442E-002 |
185 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 8.2002E-002 |
186 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 4.9521E-002 |
187 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 7.6208E-002 |
188 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 4.5543E-002 |
189 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 7.8440E-002 |
190 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 4.0935E-002 |
191 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 6.3129E-002 |
192 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 3.0795E-002 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | BASEMENT | Cooling | 83038.28755 | 83038.28755 | 6.06668 | 6.06668 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 21.70400 | 8.80930E-003 | 2779.42662 | 149.60210 | 1.20016 | 0.00000 |
2 | BASEMENT | Heating | 0.00000 | 0.00000 | 0.00000 | 1.20016 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:10:00 | -4.20000 | 2.69032E-003 | 2779.42662 | 149.60210 | 1.20016 | 0.00000 |
3 | CORE_BOTTOM | Cooling | 85559.31587 | 85559.31587 | 6.25005 | 6.25005 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 21.70400 | 8.80930E-003 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 |
4 | CORE_BOTTOM | Heating | 0.00000 | 0.00000 | 0.00000 | 1.07782 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 06:20:00 | -4.20000 | 2.69032E-003 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 |
5 | CORE_MID | Cooling | 804673.19333 | 804673.19333 | 58.76641 | 58.76641 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 21.70400 | 8.80930E-003 | 2496.12046 | 134.35320 | 10.77825 | 0.00000 |
6 | CORE_MID | Heating | 230992.37949 | 230992.37949 | 9.86860 | 10.77825 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -4.20000 | 2.69032E-003 | 2496.12046 | 134.35320 | 10.77825 | 0.00000 |
7 | CORE_TOP | Cooling | 77748.93123 | 77748.93123 | 5.67764 | 5.67764 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 21.70400 | 8.80930E-003 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 |
8 | CORE_TOP | Heating | 52106.99791 | 52106.99791 | 2.24346 | 2.24346 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -4.20000 | 2.69032E-003 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 |
9 | PERIMETER_BOT_ZN_3 | Cooling | 12939.47873 | 12939.47873 | 0.95372 | 0.95372 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:20:00 | 29.40000 | 8.82150E-003 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
10 | PERIMETER_BOT_ZN_3 | Heating | 7133.15046 | 7133.15046 | 0.30731 | 0.30731 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -4.20000 | 2.69032E-003 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
11 | PERIMETER_BOT_ZN_2 | Cooling | 19465.85101 | 19465.85101 | 1.43474 | 1.43474 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 08:40:00 | 23.02133 | 8.81136E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
12 | PERIMETER_BOT_ZN_2 | Heating | 5049.98525 | 5049.98525 | 0.21771 | 0.21771 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -4.20000 | 2.69032E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
13 | PERIMETER_BOT_ZN_1 | Cooling | 27050.33081 | 27050.33081 | 1.99377 | 1.99377 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:10:00 | 28.96667 | 8.82080E-003 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
14 | PERIMETER_BOT_ZN_1 | Heating | 8603.05287 | 8603.05287 | 0.37106 | 0.37106 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -4.20000 | 2.69032E-003 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
15 | PERIMETER_BOT_ZN_4 | Cooling | 23108.40820 | 23108.40820 | 1.70322 | 1.70322 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 17:00:00 | 27.94400 | 8.81916E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
16 | PERIMETER_BOT_ZN_4 | Heating | 3369.66237 | 3369.66237 | 0.14482 | 0.14482 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -4.20000 | 2.69032E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
17 | PERIMETER_MID_ZN_3 | Cooling | 120050.68420 | 120050.68420 | 8.84851 | 8.84851 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:30:00 | 29.40000 | 8.82150E-003 | 313.41284 | 16.86939 | 1.35332 | 0.00000 |
18 | PERIMETER_MID_ZN_3 | Heating | 144343.03425 | 144343.03425 | 6.23872 | 6.23872 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -4.20000 | 2.69032E-003 | 313.41284 | 16.86939 | 1.35332 | 0.00000 |
19 | PERIMETER_MID_ZN_2 | Cooling | 203428.72643 | 203428.72643 | 14.99387 | 14.99387 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 09:00:00 | 23.68000 | 8.81240E-003 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
20 | PERIMETER_MID_ZN_2 | Heating | 95811.74046 | 95811.74046 | 4.14151 | 4.14151 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -4.20000 | 2.69032E-003 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
21 | PERIMETER_MID_ZN_1 | Cooling | 281649.18348 | 281649.18348 | 20.75920 | 20.75920 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:30:00 | 29.14000 | 8.82108E-003 | 313.41969 | 16.86975 | 1.35335 | 0.00000 |
22 | PERIMETER_MID_ZN_1 | Heating | 142947.17452 | 142947.17452 | 6.17818 | 6.17818 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -4.20000 | 2.69032E-003 | 313.41969 | 16.86975 | 1.35335 | 0.00000 |
23 | PERIMETER_MID_ZN_4 | Cooling | 215108.96545 | 215108.96545 | 15.85477 | 15.85477 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 17:10:00 | 27.77067 | 8.81889E-003 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
24 | PERIMETER_MID_ZN_4 | Heating | 89683.27469 | 89683.27469 | 3.87578 | 3.87578 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -4.20000 | 2.69032E-003 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
25 | PERIMETER_TOP_ZN_3 | Cooling | 13330.01877 | 13330.01877 | 0.98251 | 0.98251 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | 29.40000 | 8.82150E-003 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
26 | PERIMETER_TOP_ZN_3 | Heating | 18235.88972 | 18235.88972 | 0.78869 | 0.78869 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -4.20000 | 2.69032E-003 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
27 | PERIMETER_TOP_ZN_2 | Cooling | 20176.04070 | 20176.04070 | 1.48709 | 1.48709 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 09:00:00 | 23.68000 | 8.81240E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
28 | PERIMETER_TOP_ZN_2 | Heating | 12042.43055 | 12042.43055 | 0.52086 | 0.52086 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -4.20000 | 2.69032E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
29 | PERIMETER_TOP_ZN_1 | Cooling | 29482.61083 | 29482.61083 | 2.17304 | 2.17304 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:30:00 | 29.14000 | 8.82108E-003 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
30 | PERIMETER_TOP_ZN_1 | Heating | 18082.49640 | 18082.49640 | 0.78204 | 0.78204 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -4.20000 | 2.69032E-003 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
31 | PERIMETER_TOP_ZN_4 | Cooling | 22384.18870 | 22384.18870 | 1.64984 | 1.64984 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 17:00:00 | 27.94400 | 8.81916E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
32 | PERIMETER_TOP_ZN_4 | Heating | 11505.72119 | 11505.72119 | 0.49759 | 0.49759 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -4.20000 | 2.69032E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
33 | DATACENTER_BOT_ZN_6 | Cooling | 9097.05078 | 9097.05078 | 0.52886 | 0.52886 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 18:50:00 | 25.60400 | 8.81543E-003 | 36.20274 | 1.94861 | 1.56323E-002 | 0.00000 |
34 | DATACENTER_BOT_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 1.56323E-002 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 06:20:00 | -4.20000 | 2.69032E-003 | 36.20274 | 1.94861 | 1.56323E-002 | 0.00000 |
35 | DATACENTER_MID_ZN_6 | Cooling | 87515.71214 | 87515.71214 | 5.08773 | 5.08773 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 18:50:00 | 25.60400 | 8.81543E-003 | 36.20274 | 1.94861 | 0.15632 | 0.00000 |
36 | DATACENTER_MID_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 0.15632 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 05:40:00 | -4.20000 | 2.69032E-003 | 36.20274 | 1.94861 | 0.15632 | 0.00000 |
37 | DATACENTER_TOP_ZN_6 | Cooling | 8873.29262 | 8873.29262 | 0.51585 | 0.51585 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 18:40:00 | 25.86400 | 8.81585E-003 | 36.20274 | 1.94861 | 1.56323E-002 | 0.00000 |
38 | DATACENTER_TOP_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 1.56323E-002 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 05:40:00 | -4.20000 | 2.69032E-003 | 36.20274 | 1.94861 | 1.56323E-002 | 0.00000 |
39 | DATACENTER_BASEMENT_ZN_6 | Cooling | 373551.44505 | 373551.44505 | 21.71614 | 21.71614 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 07:00:00 | 19.93600 | 8.80655E-003 | 783.67941 | 42.18139 | 0.33839 | 0.00000 |
40 | DATACENTER_BASEMENT_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 0.33839 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | -4.20000 | 2.69032E-003 | 783.67941 | 42.18139 | 0.33839 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | VAV_BOT WITH REHEAT | Cooling | Sensible | 153808.76 | 10.29064 | 10.29064 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 00:00:00 |
2 | VAV_BOT WITH REHEAT | Heating | Sensible | 42961.01 | 2.11872 | 2.11872 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 |
3 | VAV_MID WITH REHEAT | Cooling | Sensible | 1434263.66 | 95.13370 | 95.13370 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 00:00:00 |
4 | VAV_MID WITH REHEAT | Heating | Sensible | 514599.05 | 31.21243 | 31.21243 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 19:20:00 |
5 | VAV_TOP WITH REHEAT | Cooling | Sensible | 157951.95 | 10.60160 | 10.60160 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 00:00:00 |
6 | VAV_TOP WITH REHEAT | Heating | Sensible | 51294.55 | 4.83264 | 4.83264 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 22:10:00 |
7 | CAV_BAS | Cooling | Sensible | 79297.93 | 6.06668 | 6.06668 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
8 | CAV_BAS | Heating | Sensible | 63272.12 | 1.20016 | 1.20016 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
9 | AIRLOOP DATACENTER BASEMENT | Cooling | Sensible | 368406.07 | 21.71615 | 21.71615 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
10 | AIRLOOP DATACENTER BASEMENT | Heating | Sensible | 17840.03 | 0.33839 | 0.33839 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
11 | AIRLOOP DATACENTER BOT | Cooling | Sensible | 8930.38 | 0.52886 | 0.52886 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
12 | AIRLOOP DATACENTER BOT | Heating | Sensible | 824.14 | 1.56323E-002 | 1.56323E-002 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
13 | AIRLOOP DATACENTER MID | Cooling | Sensible | 85902.42 | 5.08773 | 5.08773 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
14 | AIRLOOP DATACENTER MID | Heating | Sensible | 8241.36 | 0.15632 | 0.15632 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
15 | AIRLOOP DATACENTER TOP | Cooling | Sensible | 8714.93 | 0.51585 | 0.51585 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
16 | AIRLOOP DATACENTER TOP | Heating | Sensible | 824.14 | 1.56323E-002 | 1.56323E-002 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | BASEMENT DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 6.06668 |
2 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 6.25005 |
3 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.30432 |
4 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.31500 |
5 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.96877 |
6 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.81153 |
7 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
8 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.25195E-003 |
9 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.70948E-004 |
10 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.96877 |
11 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
12 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
13 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 19540.37069 |
14 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.70948E-004 |
15 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 393.91853 |
16 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 58.76641 |
17 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.32366 |
18 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.32700 |
19 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 19.21662 |
20 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.86310 |
21 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
22 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.17715E-003 |
23 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 3.68940E-003 |
24 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 19.21662 |
25 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
26 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
27 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 421720.92440 |
28 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.68940E-003 |
29 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 9666.13269 |
30 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 5.67764 |
31 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.33501 |
32 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.34900 |
33 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.98150 |
34 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.89335 |
35 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
36 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.13729E-003 |
37 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 6.50654E-004 |
38 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 2.24346 |
39 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
40 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
41 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 74373.79604 |
42 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 6.50654E-004 |
43 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 1964.24566 |
44 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.95372 |
45 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.25041 |
46 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.25900 |
47 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.24701 |
48 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.66776 |
49 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
50 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.52151E-003 |
51 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 8.90336E-005 |
52 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.30731 |
53 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
54 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
55 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 10177.09156 |
56 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 8.90336E-005 |
57 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 268.65453 |
58 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.43474 |
59 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.10727 |
60 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
61 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.28695 |
62 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
63 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
64 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.55178E-003 |
65 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 6.90521E-005 |
66 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.28695 |
67 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
68 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
69 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 7893.07990 |
70 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 6.90521E-005 |
71 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 193.48590 |
72 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.99377 |
73 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.11979 |
74 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
75 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.39875 |
76 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.31943 |
77 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
78 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.18067E-003 |
79 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.09838E-004 |
80 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.39875 |
81 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
82 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
83 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 12555.11625 |
84 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.09838E-004 |
85 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 324.15572 |
86 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.70322 |
87 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 9.03614E-002 |
88 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
89 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.34064 |
90 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
91 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
92 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 4.21640E-003 |
93 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 5.89680E-005 |
94 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.34064 |
95 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
96 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
97 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 6740.40112 |
98 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 5.89680E-005 |
99 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 150.74572 |
100 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 8.84851 |
101 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.26990 |
102 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.27300 |
103 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.41564 |
104 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.71973 |
105 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
106 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.41164E-003 |
107 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.80381E-003 |
108 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 6.23872 |
109 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
110 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
111 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 206186.69562 |
112 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.80381E-003 |
113 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 5437.81377 |
114 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 14.99387 |
115 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.10265 |
116 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
117 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.99877 |
118 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
119 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
120 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.71181E-003 |
121 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.19736E-003 |
122 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 4.14151 |
123 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
124 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
125 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 136866.04638 |
126 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.19736E-003 |
127 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 3609.49525 |
128 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 20.75920 |
129 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.11505 |
130 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
131 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 4.15184 |
132 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30679 |
133 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
134 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.31173E-003 |
135 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.78634E-003 |
136 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 6.17818 |
137 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
138 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
139 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 204190.01051 |
140 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.78634E-003 |
141 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 5385.20362 |
142 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 15.85477 |
143 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 9.70718E-002 |
144 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
145 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 3.17095 |
146 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
147 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
148 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.92493E-003 |
149 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.12067E-003 |
150 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 3.87578 |
151 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
152 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
153 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 128100.01992 |
154 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.12067E-003 |
155 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 3378.50341 |
156 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.98251 |
157 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.24307 |
158 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.25300 |
159 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.24857 |
160 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.64819 |
161 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
162 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.56743E-003 |
163 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.27934E-004 |
164 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.78869 |
165 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
166 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
167 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 26054.26170 |
168 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.27934E-004 |
169 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 686.99580 |
170 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.48709 |
171 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.10349 |
172 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
173 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.29742 |
174 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
175 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
176 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.68137E-003 |
177 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.50523E-004 |
178 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.52086 |
179 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
180 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
181 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 17205.68624 |
182 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.50523E-004 |
183 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 453.66817 |
184 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.17304 |
185 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.10990 |
186 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
187 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.43461 |
188 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
189 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
190 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.46666E-003 |
191 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.26015E-004 |
192 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.78204 |
193 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
194 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
195 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 25834.86471 |
196 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.26015E-004 |
197 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 681.21502 |
198 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.64984 |
199 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 9.32846E-002 |
200 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
201 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.32997 |
202 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
203 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
204 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 4.08428E-003 |
205 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.43808E-004 |
206 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.49759 |
207 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
208 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
209 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 16438.08862 |
210 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.43808E-004 |
211 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 433.44111 |
212 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DATACENTER_BOT_ZN_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.52886 |
213 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DATACENTER_MID_ZN_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 5.08773 |
214 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DATACENTER_TOP_ZN_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.51585 |
215 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DATACENTER_BASEMENT_ZN_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 21.71614 |
216 | AirLoopHVAC | VAV_BOT WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 6.16775 |
217 | AirLoopHVAC | VAV_BOT WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 3.24213 |
218 | AirLoopHVAC | VAV_BOT WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 12.33550 |
219 | AirLoopHVAC | VAV_BOT WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 3.24213 |
220 | AirLoopHVAC | VAV_BOT WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 10.29064 |
221 | AirLoopHVAC | VAV_BOT WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 10.29064 |
222 | AirLoopHVAC | VAV_BOT WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
223 | AirLoopHVAC | VAV_BOT WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.31506 |
224 | AirLoopHVAC | VAV_MID WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 59.61138 |
225 | AirLoopHVAC | VAV_MID WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 31.95383 |
226 | AirLoopHVAC | VAV_MID WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 119.22275 |
227 | AirLoopHVAC | VAV_MID WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 31.95383 |
228 | AirLoopHVAC | VAV_MID WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 95.13370 |
229 | AirLoopHVAC | VAV_MID WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 95.13370 |
230 | AirLoopHVAC | VAV_MID WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
231 | AirLoopHVAC | VAV_MID WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.33588 |
232 | AirLoopHVAC | VAV_TOP WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 5.98506 |
233 | AirLoopHVAC | VAV_TOP WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 3.29207 |
234 | AirLoopHVAC | VAV_TOP WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 11.97012 |
235 | AirLoopHVAC | VAV_TOP WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 4.83264 |
236 | AirLoopHVAC | VAV_TOP WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 10.60160 |
237 | AirLoopHVAC | VAV_TOP WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 10.60160 |
238 | AirLoopHVAC | VAV_TOP WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
239 | AirLoopHVAC | VAV_TOP WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.45584 |
240 | AirLoopHVAC | CAV_BAS | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 6.06668 |
241 | AirLoopHVAC | CAV_BAS | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 6.06668 |
242 | AirLoopHVAC | CAV_BAS | Sum of Air Terminal Maximum Flow Rates [m3/s] | 6.06668 |
243 | AirLoopHVAC | CAV_BAS | Adjusted Heating Design Air Flow Rate [m3/s] | 6.06668 |
244 | AirLoopHVAC | CAV_BAS | Adjusted Cooling Design Air Flow Rate [m3/s] | 6.06668 |
245 | AirLoopHVAC | CAV_BAS | Adjusted Main Design Air Flow Rate [m3/s] | 6.06668 |
246 | AirLoopHVAC | CAV_BAS | User Heating Air Flow Ratio [] | 1.00000 |
247 | AirLoopHVAC | CAV_BAS | Calculated Heating Air Flow Ratio [] | 1.00000 |
248 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 21.71614 |
249 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 21.71614 |
250 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 21.71614 |
251 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Adjusted Heating Design Air Flow Rate [m3/s] | 21.71614 |
252 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Adjusted Cooling Design Air Flow Rate [m3/s] | 21.71615 |
253 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Adjusted Main Design Air Flow Rate [m3/s] | 21.71615 |
254 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | User Heating Air Flow Ratio [] | 1.00000 |
255 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Calculated Heating Air Flow Ratio [] | 1.00000 |
256 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.52886 |
257 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.52886 |
258 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.52886 |
259 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Adjusted Heating Design Air Flow Rate [m3/s] | 0.52886 |
260 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.52886 |
261 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Adjusted Main Design Air Flow Rate [m3/s] | 0.52886 |
262 | AirLoopHVAC | AIRLOOP DATACENTER BOT | User Heating Air Flow Ratio [] | 1.00000 |
263 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Calculated Heating Air Flow Ratio [] | 1.00000 |
264 | AirLoopHVAC | AIRLOOP DATACENTER MID | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 5.08773 |
265 | AirLoopHVAC | AIRLOOP DATACENTER MID | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 5.08773 |
266 | AirLoopHVAC | AIRLOOP DATACENTER MID | Sum of Air Terminal Maximum Flow Rates [m3/s] | 5.08773 |
267 | AirLoopHVAC | AIRLOOP DATACENTER MID | Adjusted Heating Design Air Flow Rate [m3/s] | 5.08773 |
268 | AirLoopHVAC | AIRLOOP DATACENTER MID | Adjusted Cooling Design Air Flow Rate [m3/s] | 5.08773 |
269 | AirLoopHVAC | AIRLOOP DATACENTER MID | Adjusted Main Design Air Flow Rate [m3/s] | 5.08773 |
270 | AirLoopHVAC | AIRLOOP DATACENTER MID | User Heating Air Flow Ratio [] | 1.00000 |
271 | AirLoopHVAC | AIRLOOP DATACENTER MID | Calculated Heating Air Flow Ratio [] | 1.00000 |
272 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.51585 |
273 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.51585 |
274 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.51585 |
275 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Adjusted Heating Design Air Flow Rate [m3/s] | 0.51585 |
276 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.51585 |
277 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Adjusted Main Design Air Flow Rate [m3/s] | 0.51585 |
278 | AirLoopHVAC | AIRLOOP DATACENTER TOP | User Heating Air Flow Ratio [] | 1.00000 |
279 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Calculated Heating Air Flow Ratio [] | 1.00000 |
280 | AirLoopHVAC | VAV_BOT WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 10.29064 |
281 | AirLoopHVAC | VAV_MID WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 95.13370 |
282 | AirLoopHVAC | VAV_TOP WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 10.60160 |
283 | AirLoopHVAC | CAV_BAS | Design Supply Air Flow Rate [m3/s] | 6.06668 |
284 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Design Supply Air Flow Rate [m3/s] | 21.71615 |
285 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Design Supply Air Flow Rate [m3/s] | 0.52886 |
286 | AirLoopHVAC | AIRLOOP DATACENTER MID | Design Supply Air Flow Rate [m3/s] | 5.08773 |
287 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Design Supply Air Flow Rate [m3/s] | 0.51585 |
288 | Controller:OutdoorAir | VAV_BOT WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 10.29064 |
289 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Inlet Air Temperature [C] | 25.33103 |
290 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
291 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Outlet Air Temperature [C] | 11.02678 |
292 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.81175E-003 |
293 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
294 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Coil Load [W] | 188034.13142 |
295 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 7.99941E-003 |
296 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 10.29064 |
297 | Coil:Heating:Water | VAV_BOT WITH REHEAT HEATING COIL | Design Size Rated Capacity [W] | 53123.51149 |
298 | Coil:Heating:Water | VAV_BOT WITH REHEAT HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 4.64748E-004 |
299 | Coil:Heating:Water | VAV_BOT WITH REHEAT HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 882.84710 |
300 | Fan:VariableVolume | VAV_BOT WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 10.29064 |
301 | Controller:WaterCoil | VAV_BOT WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 7.99941E-003 |
302 | Controller:WaterCoil | VAV_BOT WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 5.95282E-005 |
303 | Controller:WaterCoil | VAV_BOT WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 4.64748E-004 |
304 | Controller:OutdoorAir | VAV_MID WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 95.13370 |
305 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Inlet Air Temperature [C] | 25.43986 |
306 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
307 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Outlet Air Temperature [C] | 11.01737 |
308 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.83111E-003 |
309 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
310 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Coil Load [W] | 1757522.91998 |
311 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 7.47691E-002 |
312 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 95.13370 |
313 | Coil:Heating:Water | VAV_MID WITH REHEAT HEATING COIL | Design Size Rated Capacity [W] | 483782.72748 |
314 | Coil:Heating:Water | VAV_MID WITH REHEAT HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 4.23234E-003 |
315 | Coil:Heating:Water | VAV_MID WITH REHEAT HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 8049.84658 |
316 | Fan:VariableVolume | VAV_MID WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 95.13370 |
317 | Controller:WaterCoil | VAV_MID WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 7.47691E-002 |
318 | Controller:WaterCoil | VAV_MID WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 6.36881E-006 |
319 | Controller:WaterCoil | VAV_MID WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 4.23234E-003 |
320 | Controller:OutdoorAir | VAV_TOP WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 10.60160 |
321 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Inlet Air Temperature [C] | 25.29204 |
322 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
323 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Outlet Air Temperature [C] | 11.02676 |
324 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.80617E-003 |
325 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
326 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Coil Load [W] | 193036.60598 |
327 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 8.21222E-003 |
328 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 10.60160 |
329 | Coil:Heating:Water | VAV_TOP WITH REHEAT HEATING COIL | Design Size Rated Capacity [W] | 45185.73389 |
330 | Coil:Heating:Water | VAV_TOP WITH REHEAT HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.95305E-004 |
331 | Coil:Heating:Water | VAV_TOP WITH REHEAT HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 762.44980 |
332 | Fan:VariableVolume | VAV_TOP WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 10.60160 |
333 | Controller:WaterCoil | VAV_TOP WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 8.21222E-003 |
334 | Controller:WaterCoil | VAV_TOP WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 5.79856E-005 |
335 | Controller:WaterCoil | VAV_TOP WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 3.95305E-004 |
336 | Controller:OutdoorAir | CAV_BAS_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 6.06668 |
337 | Controller:OutdoorAir | CAV_BAS_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.20016 |
338 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Inlet Air Temperature [C] | 24.88186 |
339 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
340 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Outlet Air Temperature [C] | 11.40144 |
341 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.92412E-003 |
342 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
343 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Coil Load [W] | 106856.93371 |
344 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 4.54594E-003 |
345 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 6.06668 |
346 | Coil:Heating:Water | CAV_BAS HEATING COIL | Design Size Rated Capacity [W] | 295455.44940 |
347 | Coil:Heating:Water | CAV_BAS HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.58477E-003 |
348 | Coil:Heating:Water | CAV_BAS HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 6586.60173 |
349 | Fan:ConstantVolume | CAV_BAS FAN | Design Size Maximum Flow Rate [m3/s] | 6.06668 |
350 | Controller:WaterCoil | CAV_BAS_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 4.54594E-003 |
351 | Controller:WaterCoil | CAV_BAS_COOLC_CONTROLLER | Controller Convergence Tolerance | 1.04751E-004 |
352 | Controller:WaterCoil | CAV_BAS_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 2.58477E-003 |
353 | Controller:OutdoorAir | AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 21.71615 |
354 | Controller:OutdoorAir | AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.33839 |
355 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 21.71615 |
356 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Rated Total Cooling Capacity [W] | 429490.73254 |
357 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Rated Sensible Cooling Capacity [W] | 307640.14185 |
358 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Rated Water Flow Rate [m3/s] | 1.05182E-002 |
359 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 21.71615 |
360 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 21.71615 |
361 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 21.71615 |
362 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 21.71615 |
363 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Nominal Heating Capacity [W] | 429490.73254 |
364 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 429490.73254 |
365 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 17840.03233 |
366 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
367 | Fan:OnOff | AIRLOOP DATACENTER BASEMENT SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 21.71615 |
368 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 21.71615 |
369 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT HEATING COIL | Design Size Rated Heating Capacity [W] | 429490.73254 |
370 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT HEATING COIL | Design Size Rated Water Flow Rate [m3/s] | 1.05182E-002 |
371 | Coil:Heating:Electric | AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 17840.03233 |
372 | Humidifier:Steam:Electric | DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | Design Size Nominal Capacity Volume [m3/s] | 1.44266E-004 |
373 | Humidifier:Steam:Electric | DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | User-Specified Nominal Capacity Volume [m3/s] | 3.72000E-005 |
374 | Humidifier:Steam:Electric | DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | Design Size Rated Power [W] | 96450.69782 |
375 | Humidifier:Steam:Electric | DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | User-Specified Rated Power [W] | 100000.00000 |
376 | Controller:OutdoorAir | AIRLOOP DATACENTER BOT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.52886 |
377 | Controller:OutdoorAir | AIRLOOP DATACENTER BOT_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.56323E-002 |
378 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.52886 |
379 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT COOLING COIL | Design Size Rated Total Cooling Capacity [W] | 10215.99736 |
380 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT COOLING COIL | Design Size Rated Sensible Cooling Capacity [W] | 7404.55345 |
381 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT COOLING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.50189E-004 |
382 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 0.52886 |
383 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 0.52886 |
384 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 0.52886 |
385 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 0.52886 |
386 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Nominal Heating Capacity [W] | 10215.99736 |
387 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 10215.99736 |
388 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 824.13559 |
389 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
390 | Fan:OnOff | AIRLOOP DATACENTER BOT SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.52886 |
391 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.52886 |
392 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT HEATING COIL | Design Size Rated Heating Capacity [W] | 10215.99736 |
393 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT HEATING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.50189E-004 |
394 | Coil:Heating:Electric | AIRLOOP DATACENTER BOT_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 824.13559 |
395 | Controller:OutdoorAir | AIRLOOP DATACENTER MID_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 5.08773 |
396 | Controller:OutdoorAir | AIRLOOP DATACENTER MID_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.15632 |
397 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 5.08773 |
398 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID COOLING COIL | Design Size Rated Total Cooling Capacity [W] | 98317.41239 |
399 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID COOLING COIL | Design Size Rated Sensible Cooling Capacity [W] | 71245.33815 |
400 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID COOLING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.40779E-003 |
401 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 5.08773 |
402 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 5.08773 |
403 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 5.08773 |
404 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 5.08773 |
405 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Nominal Heating Capacity [W] | 98317.41239 |
406 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 98317.41239 |
407 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 8241.35587 |
408 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
409 | Fan:OnOff | AIRLOOP DATACENTER MID SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 5.08773 |
410 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 5.08773 |
411 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID HEATING COIL | Design Size Rated Heating Capacity [W] | 98317.41239 |
412 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID HEATING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.40779E-003 |
413 | Coil:Heating:Electric | AIRLOOP DATACENTER MID_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 8241.35587 |
414 | Controller:OutdoorAir | AIRLOOP DATACENTER TOP_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.51585 |
415 | Controller:OutdoorAir | AIRLOOP DATACENTER TOP_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.56323E-002 |
416 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.51585 |
417 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP COOLING COIL | Design Size Rated Total Cooling Capacity [W] | 9970.90576 |
418 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP COOLING COIL | Design Size Rated Sensible Cooling Capacity [W] | 7224.47915 |
419 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP COOLING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.44187E-004 |
420 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 0.51585 |
421 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 0.51585 |
422 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 0.51585 |
423 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 0.51585 |
424 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Nominal Heating Capacity [W] | 9970.90576 |
425 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 9970.90576 |
426 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 824.13559 |
427 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
428 | Fan:OnOff | AIRLOOP DATACENTER TOP SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.51585 |
429 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.51585 |
430 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP HEATING COIL | Design Size Rated Heating Capacity [W] | 9970.90576 |
431 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP HEATING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.44187E-004 |
432 | Coil:Heating:Electric | AIRLOOP DATACENTER TOP_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 824.13559 |
433 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Flow Rate [m3/s] | 9.55267E-002 |
434 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Power Consumption [W] | 15596.58443 |
435 | PlantLoop | COOLSYS1_DEMAND | Maximum Loop Flow Rate [m3/s] | 9.55267E-002 |
436 | PlantLoop | COOLSYS1_DEMAND | Plant Loop Volume [m3] | 11.46320 |
437 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Loop Supply Side Design Fluid Flow Rate [m3/s] | 9.55267E-002 |
438 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Loop Demand Side Design Fluid Flow Rate [m3/s] | 9.55267E-002 |
439 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Heat Exchanger U-Factor Times Area Value [W/C] | 400973.31984 |
440 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Loop-to-loop Temperature Difference Used to Size Heat Exchanger U-Factor Times Area Value [C] | 5.60000 |
441 | PlantLoop | HEATSYS1 | Maximum Loop Flow Rate [m3/s] | 1.91715E-002 |
442 | PlantLoop | HEATSYS1 | Plant Loop Volume [m3] | 2.30058 |
443 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Flow Rate [m3/s] | 1.91715E-002 |
444 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Power Consumption [W] | 5773.62354 |
445 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Minimum Flow Rate [m3/s] | 0.00000 |
446 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Nominal Capacity [W] | 2191423.87591 |
447 | Boiler:HotWater | HEATSYS1 BOILER | User-Specified Nominal Capacity [W] | 2191423.88000 |
448 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Design Water Flow Rate [m3/s] | 1.91715E-002 |
449 | PlantLoop | COOLSYS1_SUPPLY | Maximum Loop Flow Rate [m3/s] | 9.55267E-002 |
450 | PlantLoop | COOLSYS1_SUPPLY | Plant Loop Volume [m3] | 11.46320 |
451 | Pump:ConstantSpeed | COOLSYS1 CHILLER1 PUMP | Design Flow Rate [m3/s] | 4.77633E-002 |
452 | Pump:ConstantSpeed | COOLSYS1 CHILLER1 PUMP | Design Power Consumption [W] | 5399.02069 |
453 | Pump:ConstantSpeed | COOLSYS1 CHILLER2 PUMP | Design Flow Rate [m3/s] | 4.77633E-002 |
454 | Pump:ConstantSpeed | COOLSYS1 CHILLER2 PUMP | Design Power Consumption [W] | 5399.02069 |
455 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | Design Size Reference Chilled Water Flow Rate [m3/s] | 9.55267E-002 |
456 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | User-Specified Reference Chilled Water Flow Rate [m3/s] | 4.83719E-002 |
457 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | Design Size Reference Capacity [W] | 1139822.26170 |
458 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | User-Specified Reference Capacity [W] | 1145228.26000 |
459 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | Design Size Reference Condenser Water Flow Rate [m3/s] | 5.66731E-002 |
460 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | Design Size Reference Chilled Water Flow Rate [m3/s] | 9.55267E-002 |
461 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | User-Specified Reference Chilled Water Flow Rate [m3/s] | 4.83719E-002 |
462 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | Design Size Reference Capacity [W] | 1139822.26170 |
463 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | User-Specified Reference Capacity [W] | 1145228.26000 |
464 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | Design Size Reference Condenser Water Flow Rate [m3/s] | 5.66731E-002 |
465 | PlantLoop | SINGLE WATER PLANT LOOP | Maximum Loop Flow Rate [m3/s] | 1.34204E-002 |
466 | PlantLoop | SINGLE WATER PLANT LOOP | Plant Loop Volume [m3] | 1.61044 |
467 | Pump:ConstantSpeed | PLANT CIRC PUMP | Design Flow Rate [m3/s] | 1.34204E-002 |
468 | Pump:ConstantSpeed | PLANT CIRC PUMP | Design Power Consumption [W] | 3422.86380 |
469 | FluidCooler:TwoSpeed | CENTRAL TOWER | Design Water Flow Rate [m3/s] | 1.34204E-002 |
470 | FluidCooler:TwoSpeed | CENTRAL TOWER | Air Flow Rate at High Fan Speed [m3/s] | 139666.46671 |
471 | FluidCooler:TwoSpeed | CENTRAL TOWER | Fluid cooler UA value at high fan speed based on nominal capacity input [W/K] | 58779.19929 |
472 | FluidCooler:TwoSpeed | CENTRAL TOWER | Air Flow Rate at Low Fan Speed [m3/s] | 69833.23335 |
473 | FluidCooler:TwoSpeed | CENTRAL TOWER | Fan Power at Low Fan Speed [W] | 7879.72339 |
474 | FluidCooler:TwoSpeed | CENTRAL TOWER | U-factor Times Area Value at Low Fan Speed [W/C] | 21365.64625 |
475 | Boiler:HotWater | CENTRAL BOILER | Design Size Nominal Capacity [W] | 552803.92099 |
476 | Boiler:HotWater | CENTRAL BOILER | User-Specified Nominal Capacity [W] | 542091.38000 |
477 | Boiler:HotWater | CENTRAL BOILER | Design Size Design Water Flow Rate [m3/s] | 1.34204E-002 |
478 | PlantLoop | SWHSYS1 | Maximum Loop Flow Rate [m3/s] | 4.40000E-004 |
479 | PlantLoop | SWHSYS1 | Plant Loop Volume [m3] | 5.28000E-002 |
480 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Flow Rate [m3/s] | 4.40000E-004 |
481 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Power Consumption [W] | 56.20530 |
482 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | Use Side Design Flow Rate [m3/s] | 4.40000E-004 |
483 | CondenserLoop | TOWERWATERSYS | Maximum Loop Flow Rate [m3/s] | 0.11335 |
484 | CondenserLoop | TOWERWATERSYS | Condenser Loop Volume [m3] | 13.60154 |
485 | HeaderedPumps:VariableSpeed | TOWERWATERSYS PUMP | Design Flow Rate [m3/s] | 0.11335 |
486 | HeaderedPumps:VariableSpeed | TOWERWATERSYS PUMP | Design Power Consumption [W] | 28062.01238 |
487 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Design Air Flow Rate [m3/s] | 44.43783 |
488 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Nominal Capacity [W] | 1360475.38027 |
489 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Air Flow Rate in free convection regime [m3/s] | 8.88757 |
490 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Tower capacity in free convection regime at design conditions [W] | 170059.42253 |
491 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Design Air Flow Rate [m3/s] | 44.43783 |
492 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Nominal Capacity [W] | 1360475.38027 |
493 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Air Flow Rate in free convection regime [m3/s] | 8.88757 |
494 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Tower capacity in free convection regime at design conditions [W] | 170059.42253 |
495 | PlantEquipmentOperation:ComponentSetPoint | WSHPPLANT OPERATION SCHEME | Design Water Flow Rate [m3/s] Equipment # 47 | 5.88650E-002 |
496 | PlantEquipmentOperation:ComponentSetPoint | WSHPPLANT OPERATION SCHEME | Design Water Flow Rate [m3/s] Equipment # 47 | 5.88650E-002 |
Component Type | Name | Nominal Total Capacity {W} | |
1 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | 18528.27 |
2 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | 399592.39 |
3 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | 70484.53 |
4 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | 9644.05 |
5 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | 7476.31 |
6 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | 11889.60 |
7 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | 6387.79 |
8 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | 195353.15 |
9 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | 129674.06 |
10 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | 193461.71 |
11 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | 121369.94 |
12 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | 24684.37 |
13 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | 16300.98 |
14 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | 24476.54 |
15 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | 15573.82 |
16 | Coil:Heating:Water | VAV_BOT WITH REHEAT HEATING COIL | 41703.09 |
17 | Coil:Heating:Water | VAV_MID WITH REHEAT HEATING COIL | 380747.50 |
18 | Coil:Heating:Water | VAV_TOP WITH REHEAT HEATING COIL | 36567.91 |
19 | Coil:Heating:Water | CAV_BAS HEATING COIL | 234517.25 |
Component Type | Name | Nominal Total Capacity {W} | Nominal Sensible Capacity {W} | Nominal Latent Capacity {W} | Nominal Sensible Heat Ratio | Nominal Coil UA Value {W/C} | Nominal Coil Surface Area {m2} | |
1 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | 238129.38 | 168337.49 | 69791.89 | 0.71 | 24761.38 | 251.14 |
2 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | 2213068.07 | 1561632.52 | 651435.55 | 0.71 | 230025.16 | 2333.04 |
3 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | 244942.10 | 173249.82 | 71692.28 | 0.71 | 25478.65 | 258.42 |
4 | Coil:Cooling:Water | CAV_BAS COOLING COIL | 136322.46 | 97170.93 | 39151.54 | 0.71 | 13946.66 | 141.45 |
Component Type | Component Name | IPLV in SI Units {W/W} | IPLV in IP Units {Btu/W-h} | |
1 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | 6.84 | 23.33 |
2 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | 6.84 | 23.33 |
Zone Name | # Surfaces | |
1 | BASEMENT | 10 |
2 | CORE_BOTTOM | 8 |
3 | CORE_MID | 7 |
4 | CORE_TOP | 7 |
5 | PERIMETER_BOT_ZN_3 | 18 |
6 | PERIMETER_BOT_ZN_2 | 12 |
7 | PERIMETER_BOT_ZN_1 | 18 |
8 | PERIMETER_BOT_ZN_4 | 12 |
9 | PERIMETER_MID_ZN_3 | 9 |
10 | PERIMETER_MID_ZN_2 | 8 |
11 | PERIMETER_MID_ZN_1 | 9 |
12 | PERIMETER_MID_ZN_4 | 8 |
13 | PERIMETER_TOP_ZN_3 | 9 |
14 | PERIMETER_TOP_ZN_2 | 8 |
15 | PERIMETER_TOP_ZN_1 | 9 |
16 | PERIMETER_TOP_ZN_4 | 8 |
17 | GROUNDFLOOR_PLENUM | 11 |
18 | MIDFLOOR_PLENUM | 11 |
19 | TOPFLOOR_PLENUM | 11 |
20 | DATACENTER_BOT_ZN_6 | 6 |
21 | DATACENTER_MID_ZN_6 | 6 |
22 | DATACENTER_TOP_ZN_6 | 6 |
23 | DATACENTER_BASEMENT_ZN_6 | 10 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | BASEMENT_WALL_EAST | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_EAST_CFACTOR | 0.419 | 0.394 | 118.87 | 118.87 | 118.87 | 90.00 | 90.00 | 48.74 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | BASEMENT_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_SOUTH_CFACTOR | 0.419 | 0.394 | 139.09 | 139.09 | 139.09 | 180.00 | 90.00 | 57.03 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
3 | BASEMENT_WALL_NORTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_NORTH_CFACTOR | 0.419 | 0.394 | 139.09 | 139.09 | 139.09 | 0.00 | 90.00 | 57.03 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | BASEMENT_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.87 | 118.87 | 118.87 | 270.00 | 90.00 | 48.74 | 2.44 | 0.00 | DATACENTER_BASEMENT_ZN_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
5 | BASEMENT_FLOOR | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 2779.43 | 2779.43 | 2779.43 | 0.00 | 180.00 | 57.03 | 48.74 | 0.00 | BASEMENT_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
6 | PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | PERIMETER_BOT_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
7 | PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 250.34 | 250.34 | 250.34 | 180.00 | 0.00 | 57.03 | 4.57 | 0.00 | PERIMETER_BOT_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
8 | CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 2076.77 | 2076.77 | 2076.77 | 180.00 | 0.00 | 52.45 | 39.59 | 0.00 | CORE_BOT_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
9 | PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 250.34 | 250.34 | 250.34 | 180.00 | 0.00 | 52.45 | 4.57 | 0.00 | PERIMETER_BOT_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
10 | BASEMENT_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 7126.21 | 7126.21 | 7126.21 | 0.00 | 90.00 | 7126.21 | 1.00 | 0.00 | BASEMENT_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
11 | CORE_BOT_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
12 | CORE_BOT_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
13 | CORE_BOT_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
14 | CORE_BOT_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
15 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 419.30 | 419.30 | 419.30 | 0.00 | 180.00 | 10.59 | 39.59 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
16 | CORE_BOT_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 2076.82 | 2076.82 | 2076.82 | 0.00 | 180.00 | 52.46 | 39.59 | 0.00 | CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
17 | CORE_BOT_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 2496.12 | 2496.12 | 2496.12 | 180.00 | 0.00 | 63.05 | 39.59 | 0.00 | iz-CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
18 | CORE_BOTTOM_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 5064.65 | 5064.65 | 5064.65 | 0.00 | 90.00 | 5064.65 | 1.00 | 0.00 | CORE_BOTTOM_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
19 | CORE_MID_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
20 | CORE_MID_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
21 | CORE_MID_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
22 | CORE_MID_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
23 | CORE_MID_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_MID_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
24 | CORE_MID_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 2496.12 | 2496.12 | 2496.12 | 180.00 | 0.00 | 63.05 | 39.59 | 0.00 | iz-CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
25 | CORE_MID_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 5064.65 | 5064.65 | 5064.65 | 0.00 | 90.00 | 5064.65 | 1.00 | 0.00 | CORE_MID_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
26 | CORE_TOP_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
27 | CORE_TOP_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
28 | CORE_TOP_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
29 | CORE_TOP_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
30 | CORE_TOP_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_TOP_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
31 | CORE_TOP_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 2496.12 | 2496.12 | 2496.12 | 180.00 | 0.00 | 63.05 | 39.59 | 0.00 | iz-CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
32 | CORE_TOP_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 5064.65 | 5064.65 | 5064.65 | 0.00 | 90.00 | 5064.65 | 1.00 | 0.00 | CORE_TOP_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
33 | PERIMETER_BOT_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.075 | 0.926 | 76.91 | 200.61 | 76.91 | 0.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
34 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.42_SHGC_NORTH_0.4 | N/A | 2.387 | No | 23.18 | 23.18 | 23.18 | 0.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
35 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.42_SHGC_NORTH_0.4 | N/A | 2.387 | No | 23.18 | 23.18 | 23.18 | 0.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
36 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.42_SHGC_NORTH_0.4 | N/A | 2.387 | No | 23.18 | 23.18 | 23.18 | 0.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
37 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.42_SHGC_NORTH_0.4 | N/A | 2.387 | No | 23.18 | 23.18 | 23.18 | 0.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
38 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.42_SHGC_NORTH_0.4 | N/A | 2.387 | No | 23.18 | 23.18 | 23.18 | 0.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
39 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.839 | 2.839 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
40 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.839 | 2.839 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
41 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.839 | 2.839 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
42 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.839 | 2.839 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
43 | PERIMETER_BOT_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
44 | CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
45 | PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
46 | DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
47 | PERIMETER_BOT_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 250.34 | 250.34 | 250.34 | 0.00 | 180.00 | 52.46 | 6.47 | 0.00 | PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
48 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 63.07 | 63.07 | 63.07 | 0.00 | 180.00 | 11.51 | 4.57 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
49 | PERIMETER_BOT_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.41 | 313.41 | 313.41 | 180.00 | 0.00 | 63.96 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
50 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.83 | 626.83 | 626.83 | 0.00 | 90.00 | 626.83 | 1.00 | 0.00 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
51 | PERIMETER_BOT_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.075 | 0.926 | 52.57 | 133.74 | 52.57 | 90.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
52 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.42_SHGC_EAST_0.4 | N/A | 2.387 | No | 25.75 | 25.75 | 25.75 | 90.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
53 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.42_SHGC_EAST_0.4 | N/A | 2.387 | No | 25.75 | 25.75 | 25.75 | 90.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
54 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.42_SHGC_EAST_0.4 | N/A | 2.387 | No | 25.75 | 25.75 | 25.75 | 90.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
55 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | Door | PERIMETER_BOT_ZN_2_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.839 | 2.839 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
56 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | Door | PERIMETER_BOT_ZN_2_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.839 | 2.839 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
57 | PERIMETER_BOT_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
58 | CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
59 | PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
60 | PERIMETER_BOT_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
61 | PERIMETER_BOT_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | iz-PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
62 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
63 | PERIMETER_BOT_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.075 | 0.926 | 76.91 | 200.61 | 76.91 | 180.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
64 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.42_SHGC_SOUTH_0.4 | N/A | 2.387 | No | 23.18 | 23.18 | 23.18 | 180.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
65 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.42_SHGC_SOUTH_0.4 | N/A | 2.387 | No | 23.18 | 23.18 | 23.18 | 180.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
66 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.42_SHGC_SOUTH_0.4 | N/A | 2.387 | No | 23.18 | 23.18 | 23.18 | 180.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
67 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.42_SHGC_SOUTH_0.4 | N/A | 2.387 | No | 23.18 | 23.18 | 23.18 | 180.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
68 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.42_SHGC_SOUTH_0.4 | N/A | 2.387 | No | 23.18 | 23.18 | 23.18 | 180.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
69 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.839 | 2.839 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
70 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.839 | 2.839 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
71 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.839 | 2.839 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
72 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.839 | 2.839 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
73 | PERIMETER_BOT_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
74 | DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
75 | PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
76 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
77 | DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 63.07 | 63.07 | 63.07 | 0.00 | 180.00 | 16.08 | 4.57 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
78 | PERIMETER_BOT_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 250.35 | 250.35 | 250.35 | 0.00 | 180.00 | 57.03 | 6.47 | 0.00 | PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
79 | PERIMETER_BOT_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.42 | 313.42 | 313.42 | 180.00 | 0.00 | 73.11 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
80 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.84 | 626.84 | 626.84 | 0.00 | 90.00 | 626.84 | 1.00 | 0.00 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
81 | PERIMETER_BOT_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.075 | 0.926 | 52.57 | 133.74 | 52.57 | 270.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
82 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.42_SHGC_WEST_0.4 | N/A | 2.387 | No | 25.75 | 25.75 | 25.75 | 270.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
83 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.42_SHGC_WEST_0.4 | N/A | 2.387 | No | 25.75 | 25.75 | 25.75 | 270.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
84 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.42_SHGC_WEST_0.4 | N/A | 2.387 | No | 25.75 | 25.75 | 25.75 | 270.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
85 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | Door | PERIMETER_BOT_ZN_4_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.839 | 2.839 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
86 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | Door | PERIMETER_BOT_ZN_4_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.839 | 2.839 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
87 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
88 | DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
89 | PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
90 | PERIMETER_BOT_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
91 | PERIMETER_BOT_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | iz-PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
92 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
93 | PERIMETER_MID_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.028 | 0.891 | 84.71 | 200.61 | 84.71 | 0.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
94 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_MID_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.42_SHGC_NORTH_0.4 | N/A | 2.387 | No | 115.90 | 115.90 | 115.90 | 0.00 | 90.00 | 73.11 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
95 | PERIMETER_MID_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
96 | CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
97 | PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
98 | DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
99 | PERIMETER_MID_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
100 | PERIMETER_MID_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.41 | 313.41 | 313.41 | 180.00 | 0.00 | 63.96 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
101 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.83 | 626.83 | 626.83 | 0.00 | 90.00 | 626.83 | 1.00 | 0.00 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
102 | PERIMETER_MID_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.028 | 0.891 | 56.47 | 133.74 | 56.47 | 90.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
103 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_MID_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.42_SHGC_EAST_0.4 | N/A | 2.387 | No | 77.26 | 77.26 | 77.26 | 90.00 | 90.00 | 48.74 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
104 | PERIMETER_MID_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
105 | CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
106 | PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
107 | PERIMETER_MID_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_MID_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
108 | PERIMETER_MID_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | iz-PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
109 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
110 | PERIMETER_MID_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
111 | PERIMETER_MID_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.028 | 0.891 | 84.71 | 200.61 | 84.71 | 180.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
112 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_MID_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.42_SHGC_SOUTH_0.4 | N/A | 2.387 | No | 115.90 | 115.90 | 115.90 | 180.00 | 90.00 | 73.11 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
113 | DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
114 | PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
115 | CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
116 | PERIMETER_MID_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
117 | PERIMETER_MID_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.42 | 313.42 | 313.42 | 180.00 | 0.00 | 73.11 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
118 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.84 | 626.84 | 626.84 | 0.00 | 90.00 | 626.84 | 1.00 | 0.00 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
119 | PERIMETER_MID_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.028 | 0.891 | 56.47 | 133.74 | 56.47 | 270.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
120 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_MID_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.42_SHGC_WEST_0.4 | N/A | 2.387 | No | 77.26 | 77.26 | 77.26 | 270.00 | 90.00 | 48.74 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
121 | PERIMETER_MID_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
122 | DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
123 | PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
124 | PERIMETER_MID_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_MID_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
125 | PERIMETER_MID_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | iz-PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
126 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
127 | PERIMETER_TOP_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.266 | 1.064 | 84.71 | 200.61 | 84.71 | 0.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
128 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_TOP_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.42_SHGC_NORTH_0.4 | N/A | 2.387 | No | 115.90 | 115.90 | 115.90 | 0.00 | 90.00 | 73.11 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
129 | PERIMETER_TOP_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
130 | CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
131 | PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
132 | DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
133 | PERIMETER_TOP_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_TOP_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
134 | PERIMETER_TOP_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.41 | 313.41 | 313.41 | 180.00 | 0.00 | 63.96 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
135 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.83 | 626.83 | 626.83 | 0.00 | 90.00 | 626.83 | 1.00 | 0.00 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
136 | PERIMETER_TOP_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.266 | 1.064 | 56.47 | 133.74 | 56.47 | 90.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
137 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_TOP_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.42_SHGC_EAST_0.4 | N/A | 2.387 | No | 77.26 | 77.26 | 77.26 | 90.00 | 90.00 | 48.74 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
138 | PERIMETER_TOP_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
139 | CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
140 | INT-PER3S-NE-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | INT-PER3S-NE | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
141 | PERIMETER_TOP_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_TOP_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
142 | PERIMETER_TOP_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | iz-PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
143 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
144 | PERIMETER_TOP_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.266 | 1.064 | 84.71 | 200.61 | 84.71 | 180.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
145 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_TOP_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.42_SHGC_SOUTH_0.4 | N/A | 2.387 | No | 115.90 | 115.90 | 115.90 | 180.00 | 90.00 | 73.11 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
146 | INT-PER3S-NE | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | INT-PER3S-NE-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
147 | DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
148 | PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
149 | CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
150 | PERIMETER_TOP_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_TOP_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
151 | PERIMETER_TOP_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.42 | 313.42 | 313.42 | 180.00 | 0.00 | 73.11 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
152 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.84 | 626.84 | 626.84 | 0.00 | 90.00 | 626.84 | 1.00 | 0.00 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
153 | PERIMETER_TOP_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.266 | 1.064 | 56.47 | 133.74 | 56.47 | 270.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
154 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_TOP_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.42_SHGC_WEST_0.4 | N/A | 2.387 | No | 77.26 | 77.26 | 77.26 | 270.00 | 90.00 | 48.74 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
155 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
156 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
157 | PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
158 | PERIMETER_TOP_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_TOP_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
159 | PERIMETER_TOP_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | iz-PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
160 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
161 | GROUNDFLOOR_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.075 | 0.926 | 89.13 | 89.13 | 89.13 | 0.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
162 | GROUNDFLOOR_PLENUM_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.075 | 0.926 | 59.42 | 59.42 | 59.42 | 270.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
163 | GROUNDFLOOR_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.075 | 0.926 | 89.13 | 89.13 | 89.13 | 180.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
164 | GROUNDFLOOR_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.075 | 0.926 | 59.42 | 59.42 | 59.42 | 90.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
165 | iz-CORE_BOT_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
166 | iz-PERIMETER_BOT_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
167 | iz-PERIMETER_BOT_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
168 | iz-PERIMETER_BOT_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
169 | iz-PERIMETER_BOT_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
170 | iz-DATACENTER_BOT_ZN_6_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_BOT_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
171 | GROUNDFLOOR_PLENUM_CEILING | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 3563.11 | 3563.11 | 3563.11 | 180.00 | 0.00 | 73.11 | 48.74 | 0.00 | GROUNDFLOOR_PLENUM_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
172 | MIDFLOOR_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.028 | 0.891 | 89.13 | 89.13 | 89.13 | 0.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
173 | MIDFLOOR_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.028 | 0.891 | 59.42 | 59.42 | 59.42 | 270.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
174 | MIDFLOOR_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.028 | 0.891 | 89.13 | 89.13 | 89.13 | 180.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
175 | MIDFLOOR_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.028 | 0.891 | 59.42 | 59.42 | 59.42 | 90.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
176 | iz-CORE_MID_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
177 | iz-PERIMETER_MID_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
178 | iz-PERIMETER_MID_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
179 | iz-PERIMETER_MID_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
180 | iz-PERIMETER_MID_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
181 | iz-DATACENTER_MID_ZN_6_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_MID_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
182 | MIDFLOOR_PLENUM_CEILING | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 3563.11 | 3563.11 | 3563.11 | 180.00 | 0.00 | 73.11 | 48.74 | 0.00 | MIDFLOOR_PLENUM_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
183 | TOPFLOOR_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.266 | 1.064 | 89.13 | 89.13 | 89.13 | 180.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
184 | TOPFLOOR_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.266 | 1.064 | 59.42 | 59.42 | 59.42 | 90.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
185 | TOPFLOOR_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.266 | 1.064 | 59.42 | 59.42 | 59.42 | 270.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
186 | TOPFLOOR_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.266 | 1.064 | 89.13 | 89.13 | 89.13 | 0.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
187 | iz-CORE_TOP_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
188 | iz-PERIMETER_TOP_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
189 | iz-PERIMETER_TOP_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
190 | iz-PERIMETER_TOP_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
191 | iz-PERIMETER_TOP_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
192 | iz-DATACENTER_TOP_ZN_6_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_TOP_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
193 | BUILDING_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 3563.11 | 3563.11 | 3563.11 | 180.00 | 0.00 | 73.11 | 48.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
194 | DATACENTER_BOT_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
195 | DATACENTER_BOT_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
196 | DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
197 | DATACENTER_BOT_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
198 | DATACENTER_BOT_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
199 | DATACENTER_BOT_ZN_6_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | iz-DATACENTER_BOT_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
200 | DATACENTER_MID_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
201 | DATACENTER_MID_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
202 | DATACENTER_MID_ZN_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
203 | DATACENTER_MID_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
204 | DATACENTER_MID_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_MID_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
205 | DATACENTER_MID_ZN_6_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | iz-DATACENTER_MID_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
206 | DATACENTER_TOP_ZN_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
207 | DATACENTER_TOP_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
208 | DATACENTER_TOP_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
209 | DATACENTER_TOP_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
210 | DATACENTER_TOP_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_TOP_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
211 | DATACENTER_TOP_ZN_6_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | iz-DATACENTER_TOP_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
212 | DATACENTER_BASEMENT_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR | 0.419 | 0.394 | 39.22 | 39.22 | 39.22 | 0.00 | 90.00 | 16.08 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
213 | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR | 0.419 | 0.394 | 39.22 | 39.22 | 39.22 | 180.00 | 90.00 | 16.08 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
214 | DATACENTER_BASEMENT_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR | 0.419 | 0.394 | 118.87 | 118.87 | 118.87 | 270.00 | 90.00 | 48.74 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
215 | DATACENTER_BASEMENT_ZN_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.87 | 118.87 | 118.87 | 90.00 | 90.00 | 48.74 | 2.44 | 0.00 | BASEMENT_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
216 | DATACENTER_BASEMENT_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 783.68 | 783.68 | 783.68 | 0.00 | 180.00 | 16.08 | 48.74 | 0.00 | DATACENTER_BASEMENT_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
217 | DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | DATACENTER_BOT_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
218 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 419.35 | 419.35 | 419.35 | 180.00 | 0.00 | 10.59 | 39.59 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
219 | PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | PERIMETER_BOT_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
220 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 63.08 | 63.08 | 63.08 | 180.00 | 0.00 | 16.08 | 6.47 | 0.00 | DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
221 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 63.07 | 63.07 | 63.07 | 180.00 | 0.00 | 11.51 | 6.47 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | BASEMENT | RunPeriod: RUNPERIOD 1 | 0.1102015413 | 0.1824533808 | Pass | Pass | 0.2410308768 | 0.7063382766 | Pass | Pass |
2 | CORE_BOTTOM | RunPeriod: RUNPERIOD 1 | 2.9279483425E-003 | 5.6812253923E-003 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
3 | CORE_MID | RunPeriod: RUNPERIOD 1 | 5.0089859471E-002 | 3.5150555255E-002 | Pass | Pass | 0.3710620970 | 0.4767938690 | Pass | Pass |
4 | CORE_TOP | RunPeriod: RUNPERIOD 1 | 1.5160065108E-002 | 1.1569776224E-002 | Pass | Pass | 0.5279925783 | 0.6902722094 | Pass | Pass |
5 | PERIMETER_BOT_ZN_3 | RunPeriod: RUNPERIOD 1 | 1.6754192345E-002 | 1.5951347605E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
6 | PERIMETER_BOT_ZN_2 | RunPeriod: RUNPERIOD 1 | 1.8349080395E-002 | 1.7503462178E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
7 | PERIMETER_BOT_ZN_1 | RunPeriod: RUNPERIOD 1 | 1.7138033417E-002 | 1.8314890314E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
8 | PERIMETER_BOT_ZN_4 | RunPeriod: RUNPERIOD 1 | 1.7369348771E-002 | 1.6386419899E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
9 | PERIMETER_MID_ZN_3 | RunPeriod: RUNPERIOD 1 | 0.1682649738 | 0.1854242020 | Pass | Fail | 2.3599860910 | 9.5632546060 | Pass | Pass |
10 | PERIMETER_MID_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.1784410638 | 0.1970904980 | Pass | Fail | 1.7228242987 | 6.1589817836 | Pass | Pass |
11 | PERIMETER_MID_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.1608808515 | 0.1819562537 | Pass | Fail | 1.8055232620 | 6.7173971487 | Pass | Pass |
12 | PERIMETER_MID_ZN_4 | RunPeriod: RUNPERIOD 1 | 7.8668273793E-002 | 9.7778367787E-002 | Pass | Fail | 1.8962604557 | 7.1116720829 | Fail | Pass |
13 | PERIMETER_TOP_ZN_3 | RunPeriod: RUNPERIOD 1 | 0.3020959872 | 0.2950856865 | Pass | Pass | 16.3646070900 | 78.2912733480 | Pass | Pass |
14 | PERIMETER_TOP_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.3098839718 | 0.3063719022 | Pass | Pass | 7.7721441664 | 23.8422118758 | Pass | Pass |
15 | PERIMETER_TOP_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.2938074002 | 0.2944128347 | Pass | Pass | 7.7713180954 | 21.6292647570 | Pass | Pass |
16 | PERIMETER_TOP_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.1961480164 | 0.2149099173 | Pass | Pass | 34.4266777654 | 289.7714853275 | Pass | Pass |
17 | GROUNDFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 6.1785043786E-003 | 4.4005904026E-003 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
18 | MIDFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 2.9553867941E-002 | 2.3710153164E-002 | Pass | Pass | 0.3846276050 | 0.4626766852 | Pass | Pass |
19 | TOPFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 8.9885257175E-002 | 5.8080457881E-002 | Pass | Pass | 0.4832343418 | 0.4755970803 | Pass | Pass |
20 | DATACENTER_BOT_ZN_6 | RunPeriod: RUNPERIOD 1 | 5.1811334450E-006 | 6.0658726043E-006 | Pass | Pass | 2.0035335138E-003 | 1.6264125824E-003 | Pass | Pass |
21 | DATACENTER_MID_ZN_6 | RunPeriod: RUNPERIOD 1 | 5.9035675119E-003 | 4.0259440463E-003 | Pass | Pass | 1.2819194357E-003 | 1.2843232893E-003 | Pass | Pass |
22 | DATACENTER_TOP_ZN_6 | RunPeriod: RUNPERIOD 1 | 7.0026392348E-003 | 4.3973901530E-003 | Pass | Pass | 2.0115616886E-003 | 1.6464451005E-003 | Pass | Pass |
23 | DATACENTER_BASEMENT_ZN_6 | RunPeriod: RUNPERIOD 1 | 1.8042364362E-006 | 1.9947933032E-006 | Pass | Pass | 3.1888705954E-005 | 1.0907535774E-004 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 08:44:06
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 5787.58 | 191.28 | 0.00 | 32602.15 | 7432.88 | 46013.90 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 08:44:06
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | -4.20 | 0.00 | -4.20 | Wetbulb [C] | 4.30 | 20.00 |
SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 29.40 | 10.40 | 18.30 | Wetbulb [C] | 4.20 | 350.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 0.00 | 0 | |||
Feb | 0.00 | 0 | |||
Mar | 22.00 | 23 | |||
Apr | 0.00 | 0 | |||
May | 0.00 | 0 | |||
Jun | 16.00 | 20 | |||
Jul | 0.00 | 0 | |||
Aug | 24.00 | 18 | |||
Sep | 12.00 | 15 | |||
Oct | 61.00 | 41 | |||
Nov | 0.00 | 0 | |||
Dec | 45.00 | 41 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 08:44:06
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BASEMENT_WALL_EAST | BASEMENT_WALL_EAST_CFACTOR | 1.00 | 0.399 | 0.419 | 118.87 | 118.87 | 90.00 | 90.00 | E |
BASEMENT_WALL_SOUTH | BASEMENT_WALL_SOUTH_CFACTOR | 1.00 | 0.399 | 0.419 | 139.09 | 139.09 | 180.00 | 90.00 | S |
BASEMENT_WALL_NORTH | BASEMENT_WALL_NORTH_CFACTOR | 1.00 | 0.399 | 0.419 | 139.09 | 139.09 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_3_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.926 | 1.075 | 200.61 | 76.91 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_2_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.926 | 1.075 | 133.74 | 52.57 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.926 | 1.075 | 200.61 | 76.91 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_4_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.926 | 1.075 | 133.74 | 52.57 | 270.00 | 90.00 | W |
PERIMETER_MID_ZN_3_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.891 | 1.028 | 2006.06 | 847.11 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_2_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 0.891 | 1.028 | 1337.37 | 564.74 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.891 | 1.028 | 2006.06 | 847.11 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_4_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 0.891 | 1.028 | 1337.37 | 564.74 | 270.00 | 90.00 | W |
PERIMETER_TOP_ZN_3_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 1.064 | 1.266 | 200.61 | 84.71 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_2_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 1.064 | 1.266 | 133.74 | 56.47 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 1.064 | 1.266 | 200.61 | 84.71 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_4_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 1.064 | 1.266 | 133.74 | 56.47 | 270.00 | 90.00 | W |
GROUNDFLOOR_PLENUM_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.926 | 1.075 | 89.13 | 89.13 | 0.00 | 90.00 | N |
GROUNDFLOOR_PLENUM_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.926 | 1.075 | 59.42 | 59.42 | 270.00 | 90.00 | W |
GROUNDFLOOR_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.926 | 1.075 | 89.13 | 89.13 | 180.00 | 90.00 | S |
GROUNDFLOOR_PLENUM_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.926 | 1.075 | 59.42 | 59.42 | 90.00 | 90.00 | E |
MIDFLOOR_PLENUM_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.891 | 1.028 | 891.32 | 891.32 | 0.00 | 90.00 | N |
MIDFLOOR_PLENUM_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 0.891 | 1.028 | 594.21 | 594.21 | 270.00 | 90.00 | W |
MIDFLOOR_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.891 | 1.028 | 891.32 | 891.32 | 180.00 | 90.00 | S |
MIDFLOOR_PLENUM_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 0.891 | 1.028 | 594.21 | 594.21 | 90.00 | 90.00 | E |
TOPFLOOR_PLENUM_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 1.064 | 1.266 | 89.13 | 89.13 | 180.00 | 90.00 | S |
TOPFLOOR_PLENUM_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 1.064 | 1.266 | 59.42 | 59.42 | 90.00 | 90.00 | E |
TOPFLOOR_PLENUM_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 1.064 | 1.266 | 59.42 | 59.42 | 270.00 | 90.00 | W |
TOPFLOOR_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 1.064 | 1.266 | 89.13 | 89.13 | 0.00 | 90.00 | N |
BUILDING_ROOF | NONRES_ROOF | 0.30 | 0.182 | 0.186 | 3563.11 | 3563.11 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_WALL_NORTH | DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR | 1.00 | 0.399 | 0.419 | 39.22 | 39.22 | 0.00 | 90.00 | N |
DATACENTER_BASEMENT_ZN_6_WALL_SOUTH | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR | 1.00 | 0.399 | 0.419 | 39.22 | 39.22 | 180.00 | 90.00 | S |
DATACENTER_BASEMENT_ZN_6_WALL_WEST | DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR | 1.00 | 0.399 | 0.419 | 118.87 | 118.87 | 270.00 | 90.00 | W |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BASEMENT_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 118.87 | 118.87 | 270.00 | 90.00 | W |
BASEMENT_FLOOR | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 2779.43 | 2779.43 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 225.00 | 0.00 | |
PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 250.34 | 250.34 | 180.00 | 0.00 | |
CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 2076.77 | 2076.77 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 250.34 | 250.34 | 180.00 | 0.00 | |
CORE_BOT_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
CORE_BOT_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
CORE_BOT_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 419.30 | 419.30 | 0.00 | 180.00 | |
CORE_BOT_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 2076.82 | 2076.82 | 0.00 | 180.00 | |
CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 180.00 | 0.00 | |
CORE_MID_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 180.00 | 90.00 | S |
CORE_MID_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 270.00 | 90.00 | W |
CORE_MID_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 0.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 90.00 | 90.00 | E |
CORE_MID_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 24961.20 | 24961.20 | 0.00 | 180.00 | |
CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 24961.20 | 24961.20 | 180.00 | 0.00 | |
CORE_TOP_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
CORE_TOP_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
CORE_TOP_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
CORE_TOP_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 2496.12 | 2496.12 | 0.00 | 180.00 | |
CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 250.34 | 250.34 | 0.00 | 180.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 63.07 | 63.07 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
PERIMETER_BOT_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 45.00 | 180.00 | |
PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 225.00 | 0.00 | |
PERIMETER_BOT_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 63.07 | 63.07 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 250.35 | 250.35 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
PERIMETER_BOT_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 315.00 | 180.00 | |
PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 135.00 | 0.00 | |
PERIMETER_MID_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 225.00 | 90.00 | W |
CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 135.00 | 90.00 | S |
DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 3134.13 | 3134.13 | 0.00 | 180.00 | |
PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.13 | 3134.13 | 180.00 | 0.00 | |
PERIMETER_MID_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 315.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 270.00 | 90.00 | W |
PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 225.00 | 90.00 | W |
PERIMETER_MID_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 2019.75 | 2019.75 | 45.00 | 180.00 | |
PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 225.00 | 0.00 | |
PERIMETER_MID_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 45.00 | 90.00 | E |
DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 315.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 3134.20 | 3134.20 | 0.00 | 180.00 | |
PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.20 | 3134.20 | 180.00 | 0.00 | |
PERIMETER_MID_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 135.00 | 90.00 | S |
DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 45.00 | 90.00 | E |
PERIMETER_MID_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 2019.75 | 2019.75 | 315.00 | 180.00 | |
PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 135.00 | 0.00 | |
PERIMETER_TOP_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 313.41 | 313.41 | 0.00 | 180.00 | |
PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 180.00 | 0.00 | |
PERIMETER_TOP_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
INT-PER3S-NE-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
PERIMETER_TOP_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 201.98 | 201.98 | 45.00 | 180.00 | |
PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 225.00 | 0.00 | |
INT-PER3S-NE | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 313.42 | 313.42 | 0.00 | 180.00 | |
PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 180.00 | 0.00 | |
PERIMETER_TOP_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
PERIMETER_TOP_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 201.98 | 201.98 | 315.00 | 180.00 | |
PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 135.00 | 0.00 | |
iz-CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 45.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 315.00 | 180.00 | |
iz-DATACENTER_BOT_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 0.00 | 180.00 | |
GROUNDFLOOR_PLENUM_CEILING | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 3563.11 | 3563.11 | 180.00 | 0.00 | |
iz-CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 24961.20 | 24961.20 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.13 | 3134.13 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 45.00 | 180.00 | |
iz-PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.20 | 3134.20 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 315.00 | 180.00 | |
iz-DATACENTER_MID_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 362.03 | 362.03 | 0.00 | 180.00 | |
MIDFLOOR_PLENUM_CEILING | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 35631.06 | 35631.06 | 180.00 | 0.00 | |
iz-CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 45.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 315.00 | 180.00 | |
iz-DATACENTER_TOP_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 0.00 | 180.00 | |
DATACENTER_BOT_ZN_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
DATACENTER_BOT_ZN_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
DATACENTER_BOT_ZN_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
DATACENTER_BOT_ZN_6_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 36.20 | 36.20 | 0.00 | 180.00 | |
DATACENTER_BOT_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 180.00 | 0.00 | |
DATACENTER_MID_ZN_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 270.00 | 90.00 | W |
DATACENTER_MID_ZN_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 180.00 | 90.00 | S |
DATACENTER_MID_ZN_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 90.00 | 90.00 | E |
DATACENTER_MID_ZN_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 0.00 | 90.00 | N |
DATACENTER_MID_ZN_6_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 362.03 | 362.03 | 0.00 | 180.00 | |
DATACENTER_MID_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 362.03 | 362.03 | 180.00 | 0.00 | |
DATACENTER_TOP_ZN_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
DATACENTER_TOP_ZN_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
DATACENTER_TOP_ZN_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
DATACENTER_TOP_ZN_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
DATACENTER_TOP_ZN_6_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 36.20 | 36.20 | 0.00 | 180.00 | |
DATACENTER_TOP_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 118.87 | 118.87 | 90.00 | 90.00 | E |
DATACENTER_BASEMENT_ZN_6_FLOOR | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 783.68 | 783.68 | 0.00 | 180.00 | |
DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 36.20 | 36.20 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 419.35 | 419.35 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 135.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 63.08 | 63.08 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 63.07 | 63.07 | 180.00 | 0.00 | |
BASEMENT_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 7126.21 | 0.00 | 90.00 | N | ||
CORE_BOTTOM_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 5064.65 | 0.00 | 90.00 | N | ||
CORE_MID_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 50646.53 | 0.00 | 90.00 | N | ||
CORE_TOP_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 5064.65 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.83 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.84 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 6268.26 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 4039.50 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 6268.35 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 4039.48 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.83 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.84 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | WINDOW_U_0.42_SHGC_NORTH_0.4 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.387 | 0.401 | 0.442 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | WINDOW_U_0.42_SHGC_NORTH_0.4 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.387 | 0.401 | 0.442 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | WINDOW_U_0.42_SHGC_NORTH_0.4 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.387 | 0.401 | 0.442 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | WINDOW_U_0.42_SHGC_NORTH_0.4 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.387 | 0.401 | 0.442 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | WINDOW_U_0.42_SHGC_NORTH_0.4 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.387 | 0.401 | 0.442 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | WINDOW_U_0.42_SHGC_EAST_0.4 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 2.387 | 0.401 | 0.442 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | WINDOW_U_0.42_SHGC_EAST_0.4 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 2.387 | 0.401 | 0.442 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | WINDOW_U_0.42_SHGC_EAST_0.4 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 2.387 | 0.401 | 0.442 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | WINDOW_U_0.42_SHGC_SOUTH_0.4 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.387 | 0.401 | 0.442 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | WINDOW_U_0.42_SHGC_SOUTH_0.4 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.387 | 0.401 | 0.442 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | WINDOW_U_0.42_SHGC_SOUTH_0.4 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.387 | 0.401 | 0.442 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | WINDOW_U_0.42_SHGC_SOUTH_0.4 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.387 | 0.401 | 0.442 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | WINDOW_U_0.42_SHGC_SOUTH_0.4 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.387 | 0.401 | 0.442 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | WINDOW_U_0.42_SHGC_WEST_0.4 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 2.387 | 0.401 | 0.442 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | WINDOW_U_0.42_SHGC_WEST_0.4 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 2.387 | 0.401 | 0.442 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | WINDOW_U_0.42_SHGC_WEST_0.4 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 2.387 | 0.401 | 0.442 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.42_SHGC_NORTH_0.4 | 115.90 | 0.00 | 0.00 | 115.90 | 1158.95 | 2.387 | 0.401 | 0.442 | No | PERIMETER_MID_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.42_SHGC_EAST_0.4 | 77.26 | 0.00 | 0.00 | 77.26 | 772.63 | 2.387 | 0.401 | 0.442 | No | PERIMETER_MID_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.42_SHGC_SOUTH_0.4 | 115.90 | 0.00 | 0.00 | 115.90 | 1158.95 | 2.387 | 0.401 | 0.442 | No | PERIMETER_MID_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.42_SHGC_WEST_0.4 | 77.26 | 0.00 | 0.00 | 77.26 | 772.63 | 2.387 | 0.401 | 0.442 | No | PERIMETER_MID_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.42_SHGC_NORTH_0.4 | 115.90 | 0.00 | 0.00 | 115.90 | 115.90 | 2.387 | 0.401 | 0.442 | No | PERIMETER_TOP_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.42_SHGC_EAST_0.4 | 77.26 | 0.00 | 0.00 | 77.26 | 77.26 | 2.387 | 0.401 | 0.442 | No | PERIMETER_TOP_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.42_SHGC_SOUTH_0.4 | 115.90 | 0.00 | 0.00 | 115.90 | 115.90 | 2.387 | 0.401 | 0.442 | No | PERIMETER_TOP_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.42_SHGC_WEST_0.4 | 77.26 | 0.00 | 0.00 | 77.26 | 77.26 | 2.387 | 0.401 | 0.442 | No | PERIMETER_TOP_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
Total or Average | 4635.80 | 2.387 | 0.401 | 0.442 | |||||||||||||||||
North Total or Average | 1390.74 | 2.387 | 0.401 | 0.442 | |||||||||||||||||
Non-North Total or Average | 3245.06 | 2.387 | 0.401 | 0.442 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | SWINGING DOOR_CON | 1.992 | 2.839 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | SWINGING DOOR_CON | 1.992 | 2.839 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | SWINGING DOOR_CON | 1.992 | 2.839 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | SWINGING DOOR_CON | 1.992 | 2.839 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | SWINGING DOOR_CON | 1.992 | 2.839 | 1.95 | PERIMETER_BOT_ZN_2_WALL_EAST |
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | SWINGING DOOR_CON | 1.992 | 2.839 | 1.95 | PERIMETER_BOT_ZN_2_WALL_EAST |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | SWINGING DOOR_CON | 1.992 | 2.839 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | SWINGING DOOR_CON | 1.992 | 2.839 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | SWINGING DOOR_CON | 1.992 | 2.839 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | SWINGING DOOR_CON | 1.992 | 2.839 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | SWINGING DOOR_CON | 1.992 | 2.839 | 1.95 | PERIMETER_BOT_ZN_4_WALL_WEST |
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | SWINGING DOOR_CON | 1.992 | 2.839 | 1.95 | PERIMETER_BOT_ZN_4_WALL_WEST |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 08:44:06
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 08:44:06
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
BASEMENT_LIGHTS | BASEMENT | BASEMENT | GENERAL | 10.2732 | 2779.43 | 28553.72 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 49.04 | 0.0000 | Y | 262.84 |
CORE_BOTTOM_LIGHTS | CORE_BOTTOM | CORE_BOTTOM | GENERAL | 10.2732 | 2496.12 | 25643.24 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 49.04 | 0.0000 | Y | 236.05 |
CORE_MID_LIGHTS | CORE_MID | CORE_MID | GENERAL | 10.2732 | 24961.20 | 256432.45 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 49.04 | 0.0000 | Y | 2360.52 |
CORE_TOP_LIGHTS | CORE_TOP | CORE_TOP | GENERAL | 10.2732 | 2496.12 | 25643.24 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 49.04 | 0.0000 | Y | 236.05 |
PERIMETER_BOT_ZN_3_LIGHTS | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3 | GENERAL | 10.2732 | 313.41 | 3219.77 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 29.56 | 0.0000 | Y | 17.87 |
PERIMETER_BOT_ZN_2_LIGHTS | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2 | GENERAL | 10.2732 | 201.98 | 2074.94 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 29.18 | 0.0000 | Y | 11.37 |
PERIMETER_BOT_ZN_1_LIGHTS | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1 | GENERAL | 10.2732 | 313.42 | 3219.84 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 28.86 | 0.0000 | Y | 17.44 |
PERIMETER_BOT_ZN_4_LIGHTS | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4 | GENERAL | 10.2732 | 201.98 | 2074.94 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 29.13 | 0.0000 | Y | 11.35 |
PERIMETER_MID_ZN_3_LIGHTS | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3 | GENERAL | 10.2732 | 3134.13 | 32197.65 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 29.47 | 0.0000 | Y | 178.14 |
PERIMETER_MID_ZN_2_LIGHTS | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2 | GENERAL | 10.2732 | 2019.75 | 20749.39 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 29.12 | 0.0000 | Y | 113.43 |
PERIMETER_MID_ZN_1_LIGHTS | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1 | GENERAL | 10.2732 | 3134.20 | 32198.36 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 28.82 | 0.0000 | Y | 174.19 |
PERIMETER_MID_ZN_4_LIGHTS | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4 | GENERAL | 10.2732 | 2019.75 | 20749.39 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 29.08 | 0.0000 | Y | 113.26 |
PERIMETER_TOP_ZN_3_LIGHTS | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3 | GENERAL | 10.2732 | 313.41 | 3219.77 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 29.47 | 0.0000 | Y | 17.81 |
PERIMETER_TOP_ZN_2_LIGHTS | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2 | GENERAL | 10.2732 | 201.98 | 2074.94 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 29.12 | 0.0000 | Y | 11.34 |
PERIMETER_TOP_ZN_1_LIGHTS | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1 | GENERAL | 10.2732 | 313.42 | 3219.84 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 28.82 | 0.0000 | Y | 17.42 |
PERIMETER_TOP_ZN_4_LIGHTS | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4 | GENERAL | 10.2732 | 201.98 | 2074.94 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 29.07 | 0.0000 | Y | 11.32 |
DATACENTER_BASEMENT_LIGHTS | DATACENTER_BASEMENT_ZN_6 | DATACENTER_BASEMENT_ZN_6 | GENERAL | 10.2732 | 783.68 | 8050.93 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 49.04 | 0.0000 | Y | 74.11 |
DATACENTER_BOT_LIGHTS | DATACENTER_BOT_ZN_6 | DATACENTER_BOT_ZN_6 | GENERAL | 17.8735 | 36.20 | 647.07 | LightsWired | LTG_SCH_DATACENTER | 56.02 | 168.00 | 54.57 | 0.0000 | Y | 6.63 |
DATACENTER_MID_LIGHTS | DATACENTER_MID_ZN_6 | DATACENTER_MID_ZN_6 | GENERAL | 17.8735 | 362.03 | 6470.68 | LightsWired | LTG_SCH_DATACENTER | 56.02 | 168.00 | 54.57 | 0.0000 | Y | 66.28 |
DATACENTER_TOP_LIGHTS | DATACENTER_TOP_ZN_6 | DATACENTER_TOP_ZN_6 | GENERAL | 17.8735 | 36.20 | 647.07 | LightsWired | LTG_SCH_DATACENTER | 56.02 | 168.00 | 54.57 | 0.0000 | Y | 6.63 |
Interior Lighting Total | 10.3445 | 46320.38 | 479162.15 | 1238.81 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
PERIMETER_BOT_ZN_1_DAYLREFPT1 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_DAYLCTRL | SplitFlux | Stepped | 0.39 | 3219.84 | 1241.89 |
PERIMETER_BOT_ZN_1_DAYLREFPT2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_DAYLCTRL | SplitFlux | Stepped | 0.14 | 3219.84 | 445.95 |
PERIMETER_BOT_ZN_2_DAYLREFPT1 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_DAYLCTRL | SplitFlux | Stepped | 0.39 | 2074.94 | 800.30 |
PERIMETER_BOT_ZN_2_DAYLREFPT2 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_DAYLCTRL | SplitFlux | Stepped | 0.14 | 2074.94 | 287.38 |
PERIMETER_BOT_ZN_3_DAYLREFPT1 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_DAYLCTRL | SplitFlux | Stepped | 0.39 | 3219.77 | 1241.86 |
PERIMETER_BOT_ZN_3_DAYLREFPT2 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_DAYLCTRL | SplitFlux | Stepped | 0.14 | 3219.77 | 445.94 |
PERIMETER_BOT_ZN_4_DAYLREFPT1 | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_DAYLCTRL | SplitFlux | Stepped | 0.39 | 2074.94 | 800.30 |
PERIMETER_BOT_ZN_4_DAYLREFPT2 | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_DAYLCTRL | SplitFlux | Stepped | 0.14 | 2074.94 | 287.38 |
PERIMETER_MID_ZN_1_DAYLREFPT1 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_DAYLCTRL | SplitFlux | Stepped | 0.39 | 3219.84 | 1241.89 |
PERIMETER_MID_ZN_1_DAYLREFPT2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_DAYLCTRL | SplitFlux | Stepped | 0.14 | 3219.84 | 445.95 |
PERIMETER_MID_ZN_2_DAYLREFPT1 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_DAYLCTRL | SplitFlux | Stepped | 0.39 | 2074.94 | 800.30 |
PERIMETER_MID_ZN_2_DAYLREFPT2 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_DAYLCTRL | SplitFlux | Stepped | 0.14 | 2074.94 | 287.38 |
PERIMETER_MID_ZN_3_DAYLREFPT1 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_DAYLCTRL | SplitFlux | Stepped | 0.39 | 3219.77 | 1241.86 |
PERIMETER_MID_ZN_3_DAYLREFPT2 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_DAYLCTRL | SplitFlux | Stepped | 0.14 | 3219.77 | 445.94 |
PERIMETER_MID_ZN_4_DAYLREFPT1 | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_DAYLCTRL | SplitFlux | Stepped | 0.39 | 2074.94 | 800.30 |
PERIMETER_MID_ZN_4_DAYLREFPT2 | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_DAYLCTRL | SplitFlux | Stepped | 0.14 | 2074.94 | 287.38 |
PERIMETER_TOP_ZN_1_DAYLREFPT1 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_DAYLCTRL | SplitFlux | Stepped | 0.39 | 3219.84 | 1241.89 |
PERIMETER_TOP_ZN_1_DAYLREFPT2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_DAYLCTRL | SplitFlux | Stepped | 0.14 | 3219.84 | 445.95 |
PERIMETER_TOP_ZN_2_DAYLREFPT1 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_DAYLCTRL | SplitFlux | Stepped | 0.39 | 2074.94 | 800.30 |
PERIMETER_TOP_ZN_2_DAYLREFPT2 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_DAYLCTRL | SplitFlux | Stepped | 0.14 | 2074.94 | 287.38 |
PERIMETER_TOP_ZN_3_DAYLREFPT1 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_DAYLCTRL | SplitFlux | Stepped | 0.39 | 3219.77 | 1241.86 |
PERIMETER_TOP_ZN_3_DAYLREFPT2 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_DAYLCTRL | SplitFlux | Stepped | 0.14 | 3219.77 | 445.94 |
PERIMETER_TOP_ZN_4_DAYLREFPT1 | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_DAYLCTRL | SplitFlux | Stepped | 0.39 | 2074.94 | 800.30 |
PERIMETER_TOP_ZN_4_DAYLREFPT2 | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_DAYLCTRL | SplitFlux | Stepped | 0.14 | 2074.94 | 287.38 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS_A | 13279.00 | AstronomicalClock | - | 42.59 | 42.59 | 106.17 | |
EXTERIOR_LIGHTS_B | 44301.60 | AstronomicalClock | - | 83.55 | 71.26 | 592.60 | |
Exterior Lighting Total | 57580.60 | 698.76 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 08:44:06
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
BYPASS HEAT EXCHANGER | HeatExchanger:FluidToFluid | 2240286.72 | |||||
HEATSYS1 BOILER | Boiler:HotWater | 2191423.88 | 0.81 | ||||
COOLSYS1 CHILLER1 | Chiller:Electric:ReformulatedEIR | 1145228.26 | 6.28 | 1096133.56 | 5.98 | 6.84 | 23.33 |
COOLSYS1 CHILLER2 | Chiller:Electric:ReformulatedEIR | 1145228.26 | 6.28 | 1096133.56 | 5.98 | 6.84 | 23.33 |
CENTRAL TOWER | FluidCooler:TwoSpeed | 582060.00 | |||||
CENTRAL BOILER | Boiler:HotWater | 542091.38 | 0.80 | ||||
TOWERWATERSYS COOLTOWER 1 | CoolingTower:VariableSpeed | 1360475.38 | |||||
TOWERWATERSYS COOLTOWER 2 | CoolingTower:VariableSpeed | 1360475.38 |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
VAV_BOT WITH REHEAT COOLING COIL | Coil:Cooling:Water | 188034.13 | 238129.38 | 168337.49 | 69791.89 | 0.71 | - | 24761.38 | 251.14 |
VAV_MID WITH REHEAT COOLING COIL | Coil:Cooling:Water | 1757522.92 | 2213068.07 | 1561632.52 | 651435.55 | 0.71 | - | 230025.16 | 2333.04 |
VAV_TOP WITH REHEAT COOLING COIL | Coil:Cooling:Water | 193036.61 | 244942.10 | 173249.82 | 71692.28 | 0.71 | - | 25478.65 | 258.42 |
CAV_BAS COOLING COIL | Coil:Cooling:Water | 106856.93 | 136322.46 | 97170.93 | 39151.54 | 0.71 | - | 13946.66 | 141.45 |
AIRLOOP DATACENTER BASEMENT COOLING COIL | Coil:Cooling:WaterToAirHeatPump:EquationFit | 429490.73 | 307640.14 | 121850.59 | 0.72 | 0.00 | |||
AIRLOOP DATACENTER BOT COOLING COIL | Coil:Cooling:WaterToAirHeatPump:EquationFit | 10216.00 | 7404.55 | 2811.44 | 0.72 | 0.00 | |||
AIRLOOP DATACENTER MID COOLING COIL | Coil:Cooling:WaterToAirHeatPump:EquationFit | 98317.41 | 71245.34 | 27072.07 | 0.72 | 0.00 | |||
AIRLOOP DATACENTER TOP COOLING COIL | Coil:Cooling:WaterToAirHeatPump:EquationFit | 9970.91 | 7224.48 | 2746.43 | 0.72 | 0.00 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
None |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
None |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Water | 19540.37 | 18528.27 | - |
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Water | 421720.92 | 399592.39 | - |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Water | 74373.80 | 70484.53 | - |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 10177.09 | 9644.05 | - |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 7893.08 | 7476.31 | - |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 12555.12 | 11889.60 | - |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 6740.40 | 6387.79 | - |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 206186.70 | 195353.15 | - |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 136866.05 | 129674.06 | - |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 204190.01 | 193461.71 | - |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 128100.02 | 121369.94 | - |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 26054.26 | 24684.37 | - |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 17205.69 | 16300.98 | - |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 25834.86 | 24476.54 | - |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 16438.09 | 15573.82 | - |
VAV_BOT WITH REHEAT HEATING COIL | Coil:Heating:Water | 53123.51 | 41703.09 | - |
VAV_MID WITH REHEAT HEATING COIL | Coil:Heating:Water | 483782.73 | 380747.50 | - |
VAV_TOP WITH REHEAT HEATING COIL | Coil:Heating:Water | 45185.73 | 36567.91 | - |
CAV_BAS HEATING COIL | Coil:Heating:Water | 295455.45 | 234517.25 | - |
AIRLOOP DATACENTER BASEMENT HEATING COIL | Coil:Heating:WaterToAirHeatPump:EquationFit | 429490.73 | 0.00 | |
AIRLOOP DATACENTER BOT HEATING COIL | Coil:Heating:WaterToAirHeatPump:EquationFit | 10216.00 | 0.00 | |
AIRLOOP DATACENTER MID HEATING COIL | Coil:Heating:WaterToAirHeatPump:EquationFit | 98317.41 | 0.00 | |
AIRLOOP DATACENTER TOP HEATING COIL | Coil:Heating:WaterToAirHeatPump:EquationFit | 9970.91 | 0.00 | |
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | Coil:Heating:Electric | 17840.03 | 1.00 | |
AIRLOOP DATACENTER BOT_SUPPHEATCOIL | Coil:Heating:Electric | 824.14 | 1.00 | |
AIRLOOP DATACENTER MID_SUPPHEATCOIL | Coil:Heating:Electric | 8241.36 | 1.00 | |
AIRLOOP DATACENTER TOP_SUPPHEATCOIL | Coil:Heating:Electric | 824.14 | 1.00 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
VAV_BOT WITH REHEAT FAN | Fan:VariableVolume | 0.61 | 1314.72 | 10.29 | 22119.36 | 2149.46 | 1.00 | 1.12 | General | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 |
VAV_MID WITH REHEAT FAN | Fan:VariableVolume | 0.61 | 1314.72 | 95.13 | 205578.86 | 2160.95 | 1.00 | 1.08 | General | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 |
VAV_TOP WITH REHEAT FAN | Fan:VariableVolume | 0.61 | 1314.72 | 10.60 | 22787.76 | 2149.46 | 1.00 | 1.12 | General | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:10:00 |
CAV_BAS FAN | Fan:ConstantVolume | 0.60 | 1018.41 | 6.07 | 10286.99 | 1695.65 | 1.00 | 1.15 | General | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
AIRLOOP DATACENTER BASEMENT SUPPLY FAN | Fan:OnOff | 0.62 | 1018.41 | 21.72 | 35815.29 | 1649.25 | 1.00 | 1.14 | General | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 07:10:00 |
AIRLOOP DATACENTER BOT SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.53 | 592.38 | 1120.11 | 1.00 | 1.58 | General | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
AIRLOOP DATACENTER MID SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 5.09 | 5698.80 | 1120.11 | 1.00 | 1.15 | General | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
AIRLOOP DATACENTER TOP SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.52 | 577.81 | 1120.11 | 1.00 | 1.59 | General | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
COOLSYS1 PUMP SECONDARY | Pump:VariableSpeed | Intermittent | 105797.75 | 0.095527 | 15596.58 | 163269.45 | 0.90 | General |
HEATSYS1 PUMP | Pump:VariableSpeed | Intermittent | 180705.70 | 0.019172 | 5773.62 | 301156.09 | 0.90 | General |
COOLSYS1 CHILLER1 PUMP | Pump:ConstantSpeed | Intermittent | 73247.35 | 0.047763 | 5399.02 | 113036.94 | 0.90 | General |
COOLSYS1 CHILLER2 PUMP | Pump:ConstantSpeed | Intermittent | 73247.35 | 0.047763 | 5399.02 | 113036.94 | 0.90 | General |
PLANT CIRC PUMP | Pump:ConstantSpeed | Intermittent | 179045.11 | 0.013420 | 3422.86 | 255050.01 | 0.90 | General |
SWHSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 29891.00 | 0.000440 | 56.21 | 127739.32 | 0.30 | General |
TOWERWATERSYS PUMP | HeaderedPumps:VariableSpeed | Intermittent | 148556.62 | 0.113346 | 28062.01 | 247577.87 | 0.90 | General |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 1.14 | 87921.32 | 0.80 | 0.48 | 0.06 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:44:06
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 83038.29 | 83038.29 | 29.88 | 6.067 | 6.067 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 24.00 | 24.00 | 0.00892 | 21.70 | 0.00881 | 1.200 | 0.00 |
CORE_BOTTOM | 85559.32 | 85559.32 | 34.28 | 6.250 | 6.250 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 24.00 | 24.00 | 0.00887 | 21.70 | 0.00881 | 1.078 | 0.00 |
CORE_MID | 804673.19 | 804673.19 | 322.37 | 58.766 | 58.766 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 24.00 | 24.00 | 0.00889 | 21.70 | 0.00881 | 10.778 | 0.00 |
CORE_TOP | 77748.93 | 77748.93 | 31.15 | 5.678 | 5.678 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 24.00 | 24.00 | 0.00890 | 21.70 | 0.00881 | 1.078 | 0.00 |
PERIMETER_BOT_ZN_3 | 12939.48 | 12939.48 | 41.29 | 0.954 | 0.954 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:20:00 | 24.00 | 24.00 | 0.00880 | 29.40 | 0.00882 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_2 | 19465.85 | 19465.85 | 96.38 | 1.435 | 1.435 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 08:40:00 | 24.00 | 24.00 | 0.00863 | 23.02 | 0.00881 | 0.087 | 0.00 |
PERIMETER_BOT_ZN_1 | 27050.33 | 27050.33 | 86.31 | 1.994 | 1.994 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:10:00 | 24.00 | 24.00 | 0.00864 | 28.97 | 0.00882 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_4 | 23108.41 | 23108.41 | 114.41 | 1.703 | 1.703 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 17:00:00 | 24.00 | 24.00 | 0.00861 | 27.94 | 0.00882 | 0.087 | 0.00 |
PERIMETER_MID_ZN_3 | 120050.68 | 120050.68 | 383.04 | 8.849 | 8.849 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:30:00 | 24.00 | 24.00 | 0.00882 | 29.40 | 0.00882 | 1.353 | 0.00 |
PERIMETER_MID_ZN_2 | 203428.73 | 203428.73 | 1007.20 | 14.994 | 14.994 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 09:00:00 | 24.00 | 24.00 | 0.00863 | 23.68 | 0.00881 | 0.872 | 0.00 |
PERIMETER_MID_ZN_1 | 281649.18 | 281649.18 | 898.63 | 20.759 | 20.759 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:30:00 | 24.00 | 24.00 | 0.00864 | 29.14 | 0.00882 | 1.353 | 0.00 |
PERIMETER_MID_ZN_4 | 215108.97 | 215108.97 | 1065.03 | 15.855 | 15.855 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 17:10:00 | 24.00 | 24.00 | 0.00862 | 27.77 | 0.00882 | 0.872 | 0.00 |
PERIMETER_TOP_ZN_3 | 13330.02 | 13330.02 | 42.53 | 0.983 | 0.983 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | 24.00 | 24.00 | 0.00879 | 29.40 | 0.00882 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_2 | 20176.04 | 20176.04 | 99.89 | 1.487 | 1.487 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 09:00:00 | 24.00 | 24.00 | 0.00863 | 23.68 | 0.00881 | 0.087 | 0.00 |
PERIMETER_TOP_ZN_1 | 29482.61 | 29482.61 | 94.07 | 2.173 | 2.173 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:30:00 | 24.00 | 24.00 | 0.00864 | 29.14 | 0.00882 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_4 | 22384.19 | 22384.19 | 110.83 | 1.650 | 1.650 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 17:00:00 | 24.00 | 24.00 | 0.00862 | 27.94 | 0.00882 | 0.087 | 0.00 |
DATACENTER_BOT_ZN_6 | 9097.05 | 9097.05 | 251.28 | 0.529 | 0.529 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 18:50:00 | 27.00 | 27.00 | 0.00858 | 25.60 | 0.00882 | 0.016 | 0.00 |
DATACENTER_MID_ZN_6 | 87515.71 | 87515.71 | 2417.38 | 5.088 | 5.088 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 18:50:00 | 27.00 | 27.00 | 0.00858 | 25.60 | 0.00882 | 0.156 | 0.00 |
DATACENTER_TOP_ZN_6 | 8873.29 | 8873.29 | 245.10 | 0.516 | 0.516 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 18:40:00 | 27.00 | 27.00 | 0.00858 | 25.86 | 0.00882 | 0.016 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 373551.45 | 373551.45 | 476.66 | 21.716 | 21.716 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 07:00:00 | 27.00 | 27.00 | 0.00854 | 19.94 | 0.00881 | 0.338 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.000 | 1.200 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:10:00 | 21.00 | 24.30 | 0.00269 | -4.20 | 0.00269 | 1.200 | 0.00 |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.000 | 1.078 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 06:20:00 | 19.60 | 21.91 | 0.00269 | -4.20 | 0.00269 | 1.078 | 0.00 |
CORE_MID | 230992.38 | 230992.38 | 92.54 | 9.869 | 10.778 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00800 | -4.20 | 0.00269 | 10.778 | 0.00 |
CORE_TOP | 52107.00 | 52107.00 | 20.88 | 2.243 | 2.243 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00800 | -4.20 | 0.00269 | 1.078 | 0.00 |
PERIMETER_BOT_ZN_3 | 7133.15 | 7133.15 | 22.76 | 0.307 | 0.307 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00706 | -4.20 | 0.00269 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_2 | 5049.99 | 5049.99 | 25.00 | 0.218 | 0.218 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00720 | -4.20 | 0.00269 | 0.087 | 0.00 |
PERIMETER_BOT_ZN_1 | 8603.05 | 8603.05 | 27.45 | 0.371 | 0.371 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00735 | -4.20 | 0.00269 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_4 | 3369.66 | 3369.66 | 16.68 | 0.145 | 0.145 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00652 | -4.20 | 0.00269 | 0.087 | 0.00 |
PERIMETER_MID_ZN_3 | 144343.03 | 144343.03 | 460.55 | 6.239 | 6.239 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00747 | -4.20 | 0.00269 | 1.353 | 0.00 |
PERIMETER_MID_ZN_2 | 95811.74 | 95811.74 | 474.37 | 4.142 | 4.142 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00747 | -4.20 | 0.00269 | 0.872 | 0.00 |
PERIMETER_MID_ZN_1 | 142947.17 | 142947.17 | 456.09 | 6.178 | 6.178 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00746 | -4.20 | 0.00269 | 1.353 | 0.00 |
PERIMETER_MID_ZN_4 | 89683.27 | 89683.27 | 444.03 | 3.876 | 3.876 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00743 | -4.20 | 0.00269 | 0.872 | 0.00 |
PERIMETER_TOP_ZN_3 | 18235.89 | 18235.89 | 58.18 | 0.789 | 0.789 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00750 | -4.20 | 0.00269 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_2 | 12042.43 | 12042.43 | 59.62 | 0.521 | 0.521 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00749 | -4.20 | 0.00269 | 0.087 | 0.00 |
PERIMETER_TOP_ZN_1 | 18082.50 | 18082.50 | 57.69 | 0.782 | 0.782 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00749 | -4.20 | 0.00269 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_4 | 11505.72 | 11505.72 | 56.97 | 0.498 | 0.498 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00747 | -4.20 | 0.00269 | 0.087 | 0.00 |
DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.016 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 06:20:00 | 18.00 | 26.32 | 0.00850 | -4.20 | 0.00269 | 0.016 | 0.00 |
DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.156 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 05:40:00 | 18.00 | 23.21 | 0.00418 | -4.20 | 0.00269 | 0.156 | 0.00 |
DATACENTER_TOP_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.016 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 05:40:00 | 18.00 | 21.61 | 0.00310 | -4.20 | 0.00269 | 0.016 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.338 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | 18.00 | 27.00 | 0.00850 | -4.20 | 0.00269 | 0.338 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
VAV_BOT WITH REHEAT | 10.29 | 10.29 | 2.12 | 2.12 | 10.2906 | 3.2421 | 10.2906 | 0.3151 | 0.3000 |
VAV_MID WITH REHEAT | 95.13 | 95.13 | 31.21 | 31.21 | 95.1337 | 31.9538 | 95.1337 | 0.3359 | 0.3000 |
VAV_TOP WITH REHEAT | 10.60 | 10.60 | 4.83 | 4.83 | 10.6016 | 4.8326 | 10.6016 | 0.4558 | 0.3000 |
CAV_BAS | 6.07 | 6.07 | 1.20 | 1.20 | 6.0667 | 6.0667 | 6.0667 | 1.0000 | 1.0000 |
AIRLOOP DATACENTER BASEMENT | 21.72 | 21.72 | 0.34 | 0.34 | 21.7161 | 21.7161 | 21.7161 | 1.0000 | 1.0000 |
AIRLOOP DATACENTER BOT | 0.53 | 0.53 | 0.02 | 0.02 | 0.5289 | 0.5289 | 0.5289 | 1.0000 | 1.0000 |
AIRLOOP DATACENTER MID | 5.09 | 5.09 | 0.16 | 0.16 | 5.0877 | 5.0877 | 5.0877 | 1.0000 | 1.0000 |
AIRLOOP DATACENTER TOP | 0.52 | 0.52 | 0.02 | 0.02 | 0.5158 | 0.5158 | 0.5158 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | 19540.371 | 19540.371 | 1.968767 | 0.00017095 | 393.919 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 06:20:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 06:20:00 | 19540.37 | 19540.37 | 1.968767 | 12.80 | 11.47 | 0.00800000 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.00 | 0.00800000 | 50.9797 | 0.00 | 0.00 | 19612.42 | 19612.42 |
CORE_MID VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | 421720.924 | 421720.924 | 19.216616 | 0.00368940 | 9666.133 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 421720.92 | 421720.92 | 19.216616 | 12.80 | 11.47 | 0.00800000 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.00 | 0.00800000 | 50.9797 | 230992.38 | 0.00 | 423123.28 | 423123.28 |
CORE_TOP VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | 74373.796 | 74373.796 | 2.243465 | 0.00065065 | 1964.246 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 74373.80 | 74373.80 | 2.243465 | 12.80 | 11.47 | 0.00800000 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.00 | 0.00800000 | 50.9797 | 52107.00 | 0.00 | 74638.01 | 74638.01 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | 10177.092 | 10177.092 | 0.307305 | 0.00008903 | 268.655 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 10177.09 | 10177.09 | 0.307305 | 12.80 | 11.47 | 0.00800000 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.00 | 0.00705722 | 45.0458 | 7133.15 | 0.00 | 10212.33 | 10212.33 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | 7893.080 | 7893.080 | 0.286949 | 0.00006905 | 193.486 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 7893.08 | 7893.08 | 0.286949 | 12.80 | 11.47 | 0.00800000 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.00 | 0.00719852 | 45.9369 | 5049.99 | 0.00 | 7917.97 | 7917.97 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | 12555.116 | 12555.116 | 0.398753 | 0.00010984 | 324.156 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 12555.12 | 12555.12 | 0.398753 | 12.80 | 11.47 | 0.00800000 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.00 | 0.00734592 | 46.8657 | 8603.05 | 0.00 | 12593.65 | 12593.65 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | 6740.401 | 6740.401 | 0.340644 | 0.00005897 | 150.746 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 6740.40 | 6740.40 | 0.340644 | 12.80 | 11.47 | 0.00800000 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.00 | 0.00651991 | 41.6525 | 3369.66 | 0.00 | 6763.50 | 6763.50 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | 206186.696 | 206186.696 | 6.238718 | 0.00180381 | 5437.814 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 206186.70 | 206186.70 | 6.238718 | 12.80 | 11.47 | 0.00800000 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.00 | 0.00746600 | 47.6235 | 144343.03 | 0.00 | 206864.08 | 206864.08 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | 136866.046 | 136866.046 | 4.141510 | 0.00119736 | 3609.495 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 136866.05 | 136866.05 | 4.141510 | 12.80 | 11.47 | 0.00800000 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.00 | 0.00746804 | 47.6365 | 95811.74 | 0.00 | 137314.92 | 137314.92 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | 204190.011 | 204190.011 | 6.178180 | 0.00178634 | 5385.204 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 204190.01 | 204190.01 | 6.178180 | 12.80 | 11.47 | 0.00800000 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.00 | 0.00746002 | 47.5859 | 142947.17 | 0.00 | 204861.19 | 204861.19 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | 128100.020 | 128100.020 | 3.875777 | 0.00112067 | 3378.503 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 128100.02 | 128100.02 | 3.875777 | 12.80 | 11.47 | 0.00800000 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.00 | 0.00742507 | 47.3659 | 89683.27 | 0.00 | 128521.51 | 128521.51 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | 26054.262 | 26054.262 | 0.788691 | 0.00022793 | 686.996 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 26054.26 | 26054.26 | 0.788691 | 12.80 | 11.47 | 0.00800000 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.00 | 0.00749508 | 47.8076 | 18235.89 | 0.00 | 26138.85 | 26138.85 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | 17205.686 | 17205.686 | 0.520858 | 0.00015052 | 453.668 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 17205.69 | 17205.69 | 0.520858 | 12.80 | 11.47 | 0.00800000 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.00 | 0.00749155 | 47.7855 | 12042.43 | 0.00 | 17261.48 | 17261.48 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | 25834.865 | 25834.865 | 0.782039 | 0.00022601 | 681.215 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 25834.86 | 25834.86 | 0.782039 | 12.80 | 11.47 | 0.00800000 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.00 | 0.00749092 | 47.7813 | 18082.50 | 0.00 | 25918.77 | 25918.77 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | 16438.089 | 16438.089 | 0.497590 | 0.00014381 | 433.441 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 16438.09 | 16438.09 | 0.497590 | 12.80 | 11.47 | 0.00800000 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.00 | 0.00746827 | 47.6389 | 11505.72 | 0.00 | 16491.48 | 16491.48 |
VAV_BOT WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | VAV_BOT WITH REHEAT | 188034.131 | -999.000 | 10.290635 | 0.00799941 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | 188034.13 | 178097.63 | 10.290635 | 25.33 | 16.97 | 0.00881175 | 11.03 | 11.03 | 0.00850000 | 29.40 | 0.00882150 | 18.34 | 24.6650 | 24.00 | 0.00880856 | 46.7213 | 139615.92 | 0.00 | 190231.12 | 167981.06 |
VAV_BOT WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoopHVAC | VAV_BOT WITH REHEAT | 53123.511 | 53123.511 | 3.087191 | 0.00046475 | 882.847 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 53123.51 | 53123.51 | 3.087191 | -1.63 | -2.05 | 0.00307688 | 12.80 | 11.47 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 82.2168 | 21.36 | 0.00541660 | 33.8949 | 24155.85 | 0.00 | 50459.55 | 50459.55 |
VAV_MID WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | VAV_MID WITH REHEAT | 1757522.920 | -999.000 | 95.133698 | 0.07476909 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | 1757522.92 | 1659914.78 | 95.133698 | 25.44 | 17.02 | 0.00883111 | 11.02 | 11.02 | 0.00850000 | 29.40 | 0.00882150 | 18.34 | 26.6803 | 24.00 | 0.00883460 | 46.8576 | 1290703.72 | 0.00 | 1777964.54 | 1566511.33 |
VAV_MID WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoopHVAC | VAV_MID WITH REHEAT | 483782.727 | 483782.727 | 28.540109 | 0.00423234 | 8049.847 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 19:20:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 483782.73 | 483782.73 | 28.540109 | -1.41 | -1.68 | 0.00323414 | 12.80 | 11.47 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 88.9343 | 21.00 | 0.00750496 | 47.8672 | 465989.32 | 0.00 | 460711.85 | 460711.85 |
VAV_TOP WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | VAV_TOP WITH REHEAT | 193036.606 | -999.000 | 10.601598 | 0.00821222 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:10:00 | 193036.61 | 182982.36 | 10.601598 | 25.29 | 16.95 | 0.00880617 | 11.03 | 11.03 | 0.00850000 | 29.40 | 0.00882150 | 18.34 | 23.9416 | 24.00 | 0.00880135 | 46.6836 | 143824.15 | 0.00 | 195295.89 | 172545.93 |
VAV_TOP WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoopHVAC | VAV_TOP WITH REHEAT | 45185.734 | 45185.734 | 3.180479 | 0.00039530 | 762.450 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 22:10:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 45185.73 | 45185.73 | 3.180479 | 0.89 | 0.29 | 0.00366953 | 12.80 | 11.47 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 79.8053 | 19.76 | 0.00750409 | 51.6648 | 54625.49 | 0.00 | 44254.78 | 44254.78 |
CAV_BAS COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | CAV_BAS | 106856.934 | -999.000 | 6.066679 | 0.00454594 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 12:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 106856.93 | 99088.13 | 6.066679 | 24.88 | 16.91 | 0.00892412 | 11.40 | 11.39 | 0.00850000 | 28.05 | 0.00881933 | 17.90 | 19.7828 | 24.00 | 0.00895335 | 47.4788 | 74655.79 | 0.00 | 108098.83 | 94270.48 |
CAV_BAS HEATING COIL | Coil:Heating:Water | AirLoopHVAC | CAV_BAS | 295455.449 | 295455.449 | 6.066679 | 0.00258477 | 6586.602 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 295455.45 | 295455.45 | 6.066679 | -0.83 | -2.21 | 0.00269032 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 19.7828 | 24.37 | 0.00269032 | 14.0954 | 0.00 | 0.00 | 247795.02 | 247795.02 |
AIRLOOP DATACENTER BASEMENT COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | 429490.733 | 307640.142 | 21.716147 | 0.01051820 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 07:10:00 | 399531.74 | 396831.53 | -999.0 | 28.45 | 17.81 | 0.00854641 | 12.80 | 11.97 | 0.00850000 | 29.40 | 0.00882150 | 18.34 | -999.0000 | 27.00 | 0.00854205 | 37.9327 | 373207.35 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BOT COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER BOT | 10215.997 | 7404.553 | 0.528855 | 0.00025019 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 18:50:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 18:50:00 | 9465.76 | 9343.44 | -999.0 | 27.92 | 17.66 | 0.00858655 | 12.80 | 11.97 | 0.00850000 | 25.60 | 0.00881543 | 17.07 | -999.0000 | 27.00 | 0.00857957 | 38.0944 | 9097.05 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER MID COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER MID | 98317.412 | 71245.338 | 5.087728 | 0.00240779 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 18:50:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 18:50:00 | 91102.59 | 89880.56 | -999.0 | 27.92 | 17.67 | 0.00858987 | 12.80 | 11.97 | 0.00850000 | 25.60 | 0.00881543 | 17.07 | -999.0000 | 27.00 | 0.00858272 | 38.1083 | 87515.71 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER TOP COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER TOP | 9970.906 | 7224.479 | 0.515849 | 0.00024419 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 18:40:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 18:40:00 | 9239.63 | 9117.75 | -999.0 | 27.92 | 17.67 | 0.00858840 | 12.80 | 11.97 | 0.00850000 | 25.86 | 0.00881585 | 17.16 | -999.0000 | 27.00 | 0.00858129 | 38.1020 | 8873.29 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BASEMENT HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | 429490.733 | 429490.733 | 21.716147 | 0.01051820 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 429490.73 | 429490.73 | 21.716147 | -4.20 | -4.20 | 0.00269032 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 1.5583 | 27.00 | 0.00850000 | 37.7427 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BOT HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER BOT | 10215.997 | 10215.997 | 0.528855 | 0.00025019 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 10216.00 | 10216.00 | 0.528855 | -4.20 | -4.20 | 0.00269032 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 2.9559 | 26.71 | 0.00849987 | 38.3857 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER MID HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER MID | 98317.412 | 98317.412 | 5.087728 | 0.00240779 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 98317.41 | 98317.41 | 5.087728 | -4.20 | -4.20 | 0.00269032 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 3.0726 | 24.37 | 0.00418209 | 21.8569 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER TOP HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER TOP | 9970.906 | 9970.906 | 0.515849 | 0.00024419 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 9970.91 | 9970.91 | 0.515849 | -4.20 | -4.20 | 0.00269032 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 3.0304 | 23.37 | 0.00310466 | 17.2626 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | 17840.032 | 17840.032 | -999.0 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 17840.03 | 17840.03 | 21.716147 | -0.07 | -0.07 | 0.00840947 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 1.5583 | 27.00 | 0.00850000 | 37.7427 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BOT_SUPPHEATCOIL | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER BOT | 824.136 | 824.136 | -999.0 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 824.14 | 824.14 | 0.528855 | -0.12 | -0.12 | 0.00832815 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 2.9559 | 26.71 | 0.00849987 | 38.3857 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER MID_SUPPHEATCOIL | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER MID | 8241.356 | 8241.356 | -999.0 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 8241.36 | 8241.36 | 5.087728 | -0.13 | -0.13 | 0.00413625 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 3.0726 | 24.37 | 0.00418209 | 21.8569 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER TOP_SUPPHEATCOIL | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER TOP | 824.136 | 824.136 | -999.0 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 824.14 | 824.14 | 0.515849 | -0.13 | -1.18 | 0.00309210 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 3.0304 | 23.37 | 0.00310466 | 17.2626 | 0.00 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 08:44:06
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
CORE_BOTTOM VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | CORE_BOTTOM | N/A | N/A | N/A | Yes | Yes | Yes | No | 19540.371 | 19540.371 | 1.968767 | 0.00017095 | 393.919 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 19.16957636 | 54.44 | 82.22 | 27.78 | 2235527.15 | 0.8741 | 0.891675 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 06:20:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 06:20:00 | Sensible | 19540.37 | 19540.37 | 1.0000 | 2.33690784 | 1.968767 | 12.80 | 11.47 | 0.00800000 | 33059.8 | 40.00 | 21.01 | 0.00800000 | 60796.0 | 0.17093025 | 60.00 | 32.22 | 27.78 | 0.000 | 19540.37 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 21.00 | 0.00800000 | 21.00 | 0.00800000 | 50.9797 | 0.00 | 0.00 | 19612.42 | 19612.42 | 2.33690784 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 21.03 | 14.86 | 0.00800000 | 41452.3 | |
CORE_MID VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | CORE_MID | N/A | N/A | N/A | Yes | Yes | Yes | No | 421720.924 | 421720.924 | 19.216616 | 0.00368940 | 9666.133 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 19.16957636 | 54.44 | 82.22 | 27.78 | 2235527.15 | 18.8645 | 19.244151 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 421720.92 | 421720.92 | 1.0000 | 22.80994650 | 19.216616 | 12.80 | 11.47 | 0.00800000 | 33059.8 | 40.00 | 21.01 | 0.00800000 | 60796.0 | 3.68902226 | 60.00 | 32.22 | 27.78 | 0.000 | 421720.92 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 20.87 | 0.00800000 | 21.00 | 0.00800000 | 50.9797 | 230992.38 | 0.00 | 423123.28 | 423123.28 | 22.80994650 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 30.99 | 18.37 | 0.00800000 | 51609.8 | |
CORE_TOP VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | CORE_TOP | N/A | N/A | N/A | Yes | Yes | Yes | No | 74373.796 | 74373.796 | 2.243465 | 0.00065065 | 1964.246 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 19.16957636 | 54.44 | 82.22 | 27.78 | 2235527.15 | 3.3269 | 3.393857 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 74373.80 | 74373.80 | 1.0000 | 2.66297175 | 2.243465 | 12.80 | 11.47 | 0.00800000 | 33059.8 | 40.00 | 21.01 | 0.00800000 | 60796.0 | 0.65058804 | 60.00 | 32.22 | 27.78 | 0.000 | 74373.80 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 20.92 | 0.00800000 | 21.00 | 0.00800000 | 50.9797 | 52107.00 | 0.00 | 74638.01 | 74638.01 | 2.66297175 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.29 | 21.27 | 0.00800000 | 61087.9 | |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | PERIMETER_BOT_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 10177.092 | 10177.092 | 0.307305 | 0.00008903 | 268.655 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 19.16957636 | 54.44 | 82.22 | 27.78 | 2235527.15 | 0.4552 | 0.464405 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 10177.09 | 10177.09 | 1.0000 | 0.36476872 | 0.307305 | 12.80 | 11.47 | 0.00800000 | 33059.8 | 40.00 | 21.01 | 0.00800000 | 60796.0 | 0.08902455 | 60.00 | 32.22 | 27.78 | 0.000 | 10177.09 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 20.91 | 0.00705722 | 21.00 | 0.00705722 | 45.0458 | 7133.15 | 0.00 | 10212.33 | 10212.33 | 0.36476872 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.26 | 21.26 | 0.00800000 | 61056.6 | |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | PERIMETER_BOT_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 7893.080 | 7893.080 | 0.286949 | 0.00006905 | 193.486 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 19.16957636 | 54.44 | 82.22 | 27.78 | 2235527.15 | 0.3531 | 0.360180 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 7893.08 | 7893.08 | 1.0000 | 0.34060524 | 0.286949 | 12.80 | 11.47 | 0.00800000 | 33059.8 | 40.00 | 21.01 | 0.00800000 | 60796.0 | 0.06904506 | 60.00 | 32.22 | 27.78 | 0.000 | 7893.08 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 20.91 | 0.00719852 | 21.00 | 0.00719852 | 45.9369 | 5049.99 | 0.00 | 7917.97 | 7917.97 | 0.34060524 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 35.60 | 19.84 | 0.00800000 | 56306.6 | |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | PERIMETER_BOT_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 12555.116 | 12555.116 | 0.398753 | 0.00010984 | 324.156 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 19.16957636 | 54.44 | 82.22 | 27.78 | 2235527.15 | 0.5616 | 0.572920 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 12555.12 | 12555.12 | 1.0000 | 0.47331657 | 0.398753 | 12.80 | 11.47 | 0.00800000 | 33059.8 | 40.00 | 21.01 | 0.00800000 | 60796.0 | 0.10982643 | 60.00 | 32.22 | 27.78 | 0.000 | 12555.12 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 20.91 | 0.00734592 | 21.00 | 0.00734592 | 46.8657 | 8603.05 | 0.00 | 12593.65 | 12593.65 | 0.47331657 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 38.89 | 20.85 | 0.00800000 | 59667.1 | |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | PERIMETER_BOT_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 6740.401 | 6740.401 | 0.340644 | 0.00005897 | 150.746 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 19.16957636 | 54.44 | 82.22 | 27.78 | 2235527.15 | 0.3015 | 0.307581 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 6740.40 | 6740.40 | 1.0000 | 0.40434075 | 0.340644 | 12.80 | 11.47 | 0.00800000 | 33059.8 | 40.00 | 21.01 | 0.00800000 | 60796.0 | 0.05896195 | 60.00 | 32.22 | 27.78 | 0.000 | 6740.40 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 20.86 | 0.00651991 | 21.00 | 0.00651991 | 41.6525 | 3369.66 | 0.00 | 6763.50 | 6763.50 | 0.40434075 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 29.20 | 17.77 | 0.00800000 | 49787.1 | |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | PERIMETER_MID_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 206186.696 | 206186.696 | 6.238718 | 0.00180381 | 5437.814 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 19.16957636 | 54.44 | 82.22 | 27.78 | 2235527.15 | 9.2232 | 9.408800 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 206186.70 | 206186.70 | 1.0000 | 7.40530040 | 6.238718 | 12.80 | 11.47 | 0.00800000 | 33059.8 | 40.00 | 21.01 | 0.00800000 | 60796.0 | 1.80362715 | 60.00 | 32.22 | 27.78 | 0.000 | 206186.70 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 20.95 | 0.00746600 | 21.00 | 0.00746600 | 47.6235 | 144343.03 | 0.00 | 206864.08 | 206864.08 | 7.40530040 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.19 | 21.24 | 0.00800000 | 60994.4 | |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | PERIMETER_MID_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 136866.046 | 136866.046 | 4.141510 | 0.00119736 | 3609.495 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 19.16957636 | 54.44 | 82.22 | 27.78 | 2235527.15 | 6.1223 | 6.245530 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 136866.05 | 136866.05 | 1.0000 | 4.91593418 | 4.141510 | 12.80 | 11.47 | 0.00800000 | 33059.8 | 40.00 | 21.01 | 0.00800000 | 60796.0 | 1.19724174 | 60.00 | 32.22 | 27.78 | 0.000 | 136866.05 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 20.95 | 0.00746804 | 21.00 | 0.00746804 | 47.6365 | 95811.74 | 0.00 | 137314.92 | 137314.92 | 4.91593418 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.19 | 21.24 | 0.00800000 | 60992.4 | |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | PERIMETER_MID_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 204190.011 | 204190.011 | 6.178180 | 0.00178634 | 5385.204 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 19.16957636 | 54.44 | 82.22 | 27.78 | 2235527.15 | 9.1339 | 9.317687 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 204190.01 | 204190.01 | 1.0000 | 7.33344272 | 6.178180 | 12.80 | 11.47 | 0.00800000 | 33059.8 | 40.00 | 21.01 | 0.00800000 | 60796.0 | 1.78616106 | 60.00 | 32.22 | 27.78 | 0.000 | 204190.01 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 20.95 | 0.00746002 | 21.00 | 0.00746002 | 47.5859 | 142947.17 | 0.00 | 204861.19 | 204861.19 | 7.33344272 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.20 | 21.24 | 0.00800000 | 60995.0 | |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | PERIMETER_MID_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 128100.020 | 128100.020 | 3.875777 | 0.00112067 | 3378.503 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 19.16957636 | 54.44 | 82.22 | 27.78 | 2235527.15 | 5.7302 | 5.845515 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 128100.02 | 128100.02 | 1.0000 | 4.60051183 | 3.875777 | 12.80 | 11.47 | 0.00800000 | 33059.8 | 40.00 | 21.01 | 0.00800000 | 60796.0 | 1.12056054 | 60.00 | 32.22 | 27.78 | 0.000 | 128100.02 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 20.95 | 0.00742507 | 21.00 | 0.00742507 | 47.3659 | 89683.27 | 0.00 | 128521.51 | 128521.51 | 4.60051183 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.20 | 21.24 | 0.00800000 | 60996.2 | |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | PERIMETER_TOP_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 26054.262 | 26054.262 | 0.788691 | 0.00022793 | 686.996 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 19.16957636 | 54.44 | 82.22 | 27.78 | 2235527.15 | 1.1655 | 1.188919 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 26054.26 | 26054.26 | 1.0000 | 0.93616879 | 0.788691 | 12.80 | 11.47 | 0.00800000 | 33059.8 | 40.00 | 21.01 | 0.00800000 | 60796.0 | 0.22791080 | 60.00 | 32.22 | 27.78 | 0.000 | 26054.26 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 20.95 | 0.00749508 | 21.00 | 0.00749508 | 47.8076 | 18235.89 | 0.00 | 26138.85 | 26138.85 | 0.93616879 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.18 | 21.24 | 0.00800000 | 60980.9 | |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | PERIMETER_TOP_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 17205.686 | 17205.686 | 0.520858 | 0.00015052 | 453.668 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 19.16957636 | 54.44 | 82.22 | 27.78 | 2235527.15 | 0.7696 | 0.785137 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 17205.69 | 17205.69 | 1.0000 | 0.61825419 | 0.520858 | 12.80 | 11.47 | 0.00800000 | 33059.8 | 40.00 | 21.01 | 0.00800000 | 60796.0 | 0.15050749 | 60.00 | 32.22 | 27.78 | 0.000 | 17205.69 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 20.95 | 0.00749155 | 21.00 | 0.00749155 | 47.7855 | 12042.43 | 0.00 | 17261.48 | 17261.48 | 0.61825419 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.18 | 21.24 | 0.00800000 | 60979.5 | |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | PERIMETER_TOP_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 25834.865 | 25834.865 | 0.782039 | 0.00022601 | 681.215 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 19.16957636 | 54.44 | 82.22 | 27.78 | 2235527.15 | 1.1556 | 1.178908 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 25834.86 | 25834.86 | 1.0000 | 0.92827283 | 0.782039 | 12.80 | 11.47 | 0.00800000 | 33059.8 | 40.00 | 21.01 | 0.00800000 | 60796.0 | 0.22599161 | 60.00 | 32.22 | 27.78 | 0.000 | 25834.86 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 20.95 | 0.00749092 | 21.00 | 0.00749092 | 47.7813 | 18082.50 | 0.00 | 25918.77 | 25918.77 | 0.92827283 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.18 | 21.24 | 0.00800000 | 60981.3 | |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | PERIMETER_TOP_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 16438.089 | 16438.089 | 0.497590 | 0.00014381 | 433.441 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 19.16957636 | 54.44 | 82.22 | 27.78 | 2235527.15 | 0.7353 | 0.750110 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 16438.09 | 16438.09 | 1.0000 | 0.59063490 | 0.497590 | 12.80 | 11.47 | 0.00800000 | 33059.8 | 40.00 | 21.01 | 0.00800000 | 60796.0 | 0.14379290 | 60.00 | 32.22 | 27.78 | 0.000 | 16438.09 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 20.95 | 0.00746827 | 21.00 | 0.00746827 | 47.6389 | 11505.72 | 0.00 | 16491.48 | 16491.48 | 0.59063490 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.18 | 21.24 | 0.00800000 | 60981.4 | |
VAV_BOT WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV_BOT WITH REHEAT | CORE_BOTTOM; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 188034.131 | -999.000 | 10.290635 | 0.00799941 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.2206 | 1004.8586 | 1.1870 | VAV_BOT WITH REHEAT FAN | Fan:VariableVolume | 10.290635 | 12.21488907 | 4197.9300 | 999.8980 | 95.51691425 | 12.27 | 6.67 | 5.60 | 2245450.59 | 8.3740 | 8.374004 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | Sensible | 188034.13 | 178097.63 | 1.0000 | 12.21488907 | 10.290635 | 25.33 | 16.97 | 0.00881175 | 47906.2 | 11.03 | 11.03 | 0.00850000 | 32512.4 | 7.99859061 | 6.67 | 12.27 | 5.60 | 22119.356 | 165914.78 | 29.40 | 0.00882150 | 18.34 | 2.53819000 | 24.6650 | 24.00 | 0.00880856 | 24.00 | 0.00880856 | 46.7213 | 139615.92 | 0.00 | 190231.12 | 167981.06 | 12.21488907 | 25.33 | 17.12 | 0.00881175 | 47906.2 | 11.86 | 11.29 | 0.00808977 | 32332.5 | |
VAV_BOT WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV_BOT WITH REHEAT | CORE_BOTTOM; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 53123.511 | 53123.511 | 3.087191 | 0.00046475 | 882.847 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | VAV_BOT WITH REHEAT FAN | Fan:VariableVolume | 10.290635 | 12.21488907 | 4197.9300 | 999.8980 | 19.16957636 | 54.44 | 82.22 | 27.78 | 2235527.15 | 2.3763 | 2.424155 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 53123.51 | 53123.51 | 1.0000 | 3.66446672 | 3.087191 | -1.63 | -2.05 | 0.00307688 | 6051.1 | 12.80 | 11.47 | 0.00800000 | 33059.8 | 0.46470024 | 60.00 | 32.22 | 27.78 | 0.000 | 53123.51 | -4.20 | 0.00269032 | -4.20 | 2.53819000 | 82.2168 | 10.27 | 0.00486407 | 21.36 | 0.00541660 | 33.8949 | 24155.85 | 0.00 | 50459.55 | 50459.55 | 3.66446672 | 2.80 | 0.63 | 0.00307688 | 10524.7 | 16.43 | 7.83 | 0.00307688 | 24294.6 | |
VAV_MID WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV_MID WITH REHEAT | CORE_MID; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 1757522.920 | -999.000 | 95.133698 | 0.07476909 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.2566 | 1004.8586 | 1.1870 | VAV_MID WITH REHEAT FAN | Fan:VariableVolume | 95.133698 | 112.92282303 | 4197.9300 | 999.8980 | 95.51691425 | 12.27 | 6.67 | 5.60 | 2245450.59 | 78.2704 | 78.270389 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | Sensible | 1757522.92 | 1659914.78 | 1.0000 | 112.92282303 | 95.133698 | 25.44 | 17.02 | 0.00883111 | 48066.7 | 11.02 | 11.02 | 0.00850000 | 32502.8 | 74.76146066 | 6.67 | 12.27 | 5.60 | 205578.856 | 1551944.06 | 29.40 | 0.00882150 | 18.34 | 25.38195000 | 26.6803 | 24.00 | 0.00883460 | 24.00 | 0.00883460 | 46.8576 | 1290703.72 | 0.00 | 1777964.54 | 1566511.33 | 112.92282303 | 25.44 | 17.17 | 0.00883111 | 48066.7 | 11.86 | 11.29 | 0.00808891 | 32321.7 | |
VAV_MID WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV_MID WITH REHEAT | CORE_MID; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 483782.727 | 483782.727 | 28.540109 | 0.00423234 | 8049.847 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | VAV_MID WITH REHEAT FAN | Fan:VariableVolume | 95.133698 | 112.92282303 | 4197.9300 | 999.8980 | 19.16957636 | 54.44 | 82.22 | 27.78 | 2235527.15 | 21.6407 | 22.076182 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 19:20:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 483782.73 | 483782.73 | 1.0000 | 33.87684691 | 28.540109 | -1.41 | -1.68 | 0.00323414 | 6661.5 | 12.80 | 11.47 | 0.00800000 | 33059.8 | 4.23191060 | 60.00 | 32.22 | 27.78 | 0.000 | 483782.73 | -4.20 | 0.00269032 | -4.20 | 25.38195000 | 88.9343 | 21.00 | 0.00760479 | 21.00 | 0.00750496 | 47.8672 | 465989.32 | 0.00 | 460711.85 | 460711.85 | 33.87684691 | 2.80 | 0.86 | 0.00323414 | 10918.8 | 16.25 | 7.93 | 0.00323414 | 24518.4 | |
VAV_TOP WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV_TOP WITH REHEAT | CORE_TOP; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 193036.606 | -999.000 | 10.601598 | 0.00821222 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.2102 | 1004.8586 | 1.1870 | VAV_TOP WITH REHEAT FAN | Fan:VariableVolume | 10.601598 | 12.58399929 | 4197.9300 | 999.8980 | 95.51691425 | 12.27 | 6.67 | 5.60 | 2245450.59 | 8.5968 | 8.596787 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:10:00 | Sensible | 193036.61 | 182982.36 | 1.0000 | 12.58399929 | 10.601598 | 25.29 | 16.95 | 0.00880617 | 47852.2 | 11.03 | 11.03 | 0.00850000 | 32512.4 | 8.21138573 | 6.67 | 12.27 | 5.60 | 22787.760 | 170248.85 | 29.40 | 0.00882150 | 18.34 | 2.53819000 | 23.9416 | 24.00 | 0.00880135 | 24.00 | 0.00880135 | 46.6836 | 143824.15 | 0.00 | 195295.89 | 172545.93 | 12.58399929 | 25.29 | 17.10 | 0.00880617 | 47852.2 | 11.87 | 11.29 | 0.00808962 | 32332.8 | |
VAV_TOP WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV_TOP WITH REHEAT | CORE_TOP; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 45185.734 | 45185.734 | 3.180479 | 0.00039530 | 762.450 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | VAV_TOP WITH REHEAT FAN | Fan:VariableVolume | 10.601598 | 12.58399929 | 4197.9300 | 999.8980 | 19.16957636 | 54.44 | 82.22 | 27.78 | 2235527.15 | 2.0213 | 2.061935 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 22:10:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 45185.73 | 45185.73 | 1.0000 | 3.77519979 | 3.180479 | 0.89 | 0.29 | 0.00366953 | 10076.4 | 12.80 | 11.47 | 0.00800000 | 33059.8 | 0.39526419 | 60.00 | 32.22 | 27.78 | 0.000 | 45185.73 | -4.20 | 0.00269032 | -4.20 | 2.53819000 | 79.8053 | 21.00 | 0.00753915 | 19.76 | 0.00750409 | 51.6648 | 54625.49 | 0.00 | 44254.78 | 44254.78 | 3.77519979 | 2.80 | 1.48 | 0.00366953 | 12009.9 | 14.39 | 7.56 | 0.00366953 | 23732.4 | |
CAV_BAS COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | CAV_BAS | BASEMENT | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 106856.934 | -999.000 | 6.066679 | 0.00454594 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.4295 | 1004.8586 | 1.1870 | CAV_BAS FAN | Fan:ConstantVolume | 6.066679 | 7.20109200 | 4197.9300 | 999.8980 | 95.51691425 | 12.27 | 6.67 | 5.60 | 2245450.59 | 4.7588 | 4.758819 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 12:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 12:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | Sensible | 106856.93 | 99088.13 | 1.0000 | 7.20109200 | 6.066679 | 24.88 | 16.91 | 0.00892412 | 47733.8 | 11.40 | 11.39 | 0.00850000 | 32894.8 | 4.54547725 | 6.67 | 12.27 | 5.60 | 10286.991 | 96569.94 | 28.05 | 0.00881933 | 17.90 | 1.20015641 | 19.7828 | 24.00 | 0.00895335 | 24.00 | 0.00895335 | 47.4788 | 74655.79 | 0.00 | 108098.83 | 94270.48 | 7.20109200 | 24.88 | 17.06 | 0.00892412 | 47733.8 | 12.07 | 11.45 | 0.00816311 | 32722.3 | |
CAV_BAS HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | CAV_BAS | BASEMENT | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 295455.449 | 295455.449 | 6.066679 | 0.00258477 | 6586.602 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | CAV_BAS FAN | Fan:ConstantVolume | 6.066679 | 7.20109200 | 4197.9300 | 999.8980 | 19.16957636 | 54.44 | 82.22 | 27.78 | 2235527.15 | 13.2164 | 13.482351 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 295455.45 | 295455.45 | 1.0000 | 7.20109200 | 6.066679 | -0.83 | -2.21 | 0.00269032 | 5889.3 | 40.00 | 21.01 | 0.00800000 | 60796.0 | 2.58450949 | 60.00 | 32.22 | 27.78 | 0.000 | 295455.45 | -4.20 | 0.00269032 | -4.20 | 1.20015641 | 19.7828 | 0.00 | 0.00269032 | 24.37 | 0.00269032 | 14.0954 | 0.00 | 0.00 | 247795.02 | 247795.02 | 7.20109200 | 12.80 | 5.58 | 0.00269032 | 19654.3 | 46.88 | 19.29 | 0.00269032 | 54065.0 | |
AIRLOOP DATACENTER BASEMENT COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | DATACENTER_BASEMENT_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 429490.733 | 307640.142 | 21.716147 | 0.01051820 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1020.7273 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 07:10:00 | Sensible | 399531.74 | 396831.53 | 0.9302 | -999.0 | -999.0 | 28.45 | 17.81 | 0.00854641 | 50411.6 | 12.80 | 11.97 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 399531.74 | 29.40 | 0.00882150 | 18.34 | 0.33839277 | -999.0000 | 27.00 | 0.00854205 | 27.00 | 0.00854205 | 37.9327 | 373207.35 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BOT COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BOT | DATACENTER_BOT_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 10215.997 | 7404.553 | 0.528855 | 0.00025019 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1020.8020 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 18:50:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 18:50:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 18:50:00 | Sensible | 9465.76 | 9343.44 | 0.9266 | -999.0 | -999.0 | 27.92 | 17.66 | 0.00858655 | 49971.9 | 12.80 | 11.97 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9465.76 | 25.60 | 0.00881543 | 17.07 | 0.01563234 | -999.0000 | 27.00 | 0.00857957 | 27.00 | 0.00857957 | 38.0944 | 9097.05 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER MID COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER MID | DATACENTER_MID_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 98317.412 | 71245.338 | 5.087728 | 0.00240779 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1020.8081 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 18:50:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 18:50:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 18:50:00 | Sensible | 91102.59 | 89880.56 | 0.9266 | -999.0 | -999.0 | 27.92 | 17.67 | 0.00858987 | 49978.7 | 12.80 | 11.97 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 91102.59 | 25.60 | 0.00881543 | 17.07 | 0.15632344 | -999.0000 | 27.00 | 0.00858272 | 27.00 | 0.00858272 | 38.1083 | 87515.71 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER TOP COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER TOP | DATACENTER_TOP_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 9970.906 | 7224.479 | 0.515849 | 0.00024419 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1020.8054 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 18:40:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 18:40:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 18:40:00 | Sensible | 9239.63 | 9117.75 | 0.9267 | -999.0 | -999.0 | 27.92 | 17.67 | 0.00858840 | 49983.6 | 12.80 | 11.97 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9239.63 | 25.86 | 0.00881585 | 17.16 | 0.01563234 | -999.0000 | 27.00 | 0.00858129 | 27.00 | 0.00858129 | 38.1020 | 8873.29 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BASEMENT HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | DATACENTER_BASEMENT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 429490.733 | 429490.733 | 21.716147 | 0.01051820 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 429490.73 | 429490.73 | 1.0000 | 25.77686686 | 21.716147 | -4.20 | -4.20 | 0.00269032 | 2487.0 | 40.00 | 21.01 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 429490.73 | -4.20 | 0.00269032 | -4.20 | 0.33839277 | 1.5583 | 0.00 | 0.00850000 | 27.00 | 0.00850000 | 37.7427 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BOT HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BOT | DATACENTER_BOT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 10215.997 | 10215.997 | 0.528855 | 0.00025019 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 10216.00 | 10216.00 | 1.0000 | 0.62774639 | 0.528855 | -4.20 | -4.20 | 0.00269032 | 2487.0 | 40.00 | 21.01 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 10216.00 | -4.20 | 0.00269032 | -4.20 | 0.01563234 | 2.9559 | 0.00 | 0.00849987 | 26.71 | 0.00849987 | 38.3857 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER MID HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER MID | DATACENTER_MID_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 98317.412 | 98317.412 | 5.087728 | 0.00240779 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 98317.41 | 98317.41 | 1.0000 | 6.03908596 | 5.087728 | -4.20 | -4.20 | 0.00269032 | 2487.0 | 40.00 | 21.01 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 98317.41 | -4.20 | 0.00269032 | -4.20 | 0.15632344 | 3.0726 | 0.00 | 0.00418209 | 24.37 | 0.00418209 | 21.8569 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER TOP HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER TOP | DATACENTER_TOP_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 9970.906 | 9970.906 | 0.515849 | 0.00024419 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 9970.91 | 9970.91 | 1.0000 | 0.61230759 | 0.515849 | -4.20 | -4.20 | 0.00269032 | 2487.0 | 40.00 | 21.01 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9970.91 | -4.20 | 0.00269032 | -4.20 | 0.01563234 | 3.0304 | 0.00 | 0.00310466 | 23.37 | 0.00310466 | 17.2626 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | DATACENTER_BASEMENT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 17840.032 | 17840.032 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | AIRLOOP DATACENTER BASEMENT SUPPLY FAN | Fan:OnOff | 21.716147 | 25.77686686 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 17840.03 | 17840.03 | 1.0000 | 25.77686686 | 21.716147 | -0.07 | -0.07 | 0.00840947 | 20964.8 | 40.00 | 21.01 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 17840.03 | -4.20 | 0.00269032 | -4.20 | 0.33839277 | 1.5583 | 0.00 | 0.00850000 | 27.00 | 0.00850000 | 37.7427 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BOT_SUPPHEATCOIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BOT | DATACENTER_BOT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 824.136 | 824.136 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | AIRLOOP DATACENTER BOT SUPPLY FAN | Fan:OnOff | 0.528855 | 0.62774639 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 824.14 | 824.14 | 1.0000 | 0.62774639 | 0.528855 | -0.12 | -0.12 | 0.00832815 | 20701.5 | 40.00 | 21.01 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 824.14 | -4.20 | 0.00269032 | -4.20 | 0.01563234 | 2.9559 | 0.00 | 0.00849987 | 26.71 | 0.00849987 | 38.3857 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER MID_SUPPHEATCOIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER MID | DATACENTER_MID_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 8241.356 | 8241.356 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | AIRLOOP DATACENTER MID SUPPLY FAN | Fan:OnOff | 5.087728 | 6.03908596 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 8241.36 | 8241.36 | 1.0000 | 6.03908596 | 5.087728 | -0.13 | -0.13 | 0.00413625 | 10213.9 | 40.00 | 21.01 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 8241.36 | -4.20 | 0.00269032 | -4.20 | 0.15632344 | 3.0726 | 0.00 | 0.00418209 | 24.37 | 0.00418209 | 21.8569 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER TOP_SUPPHEATCOIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER TOP | DATACENTER_TOP_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 824.136 | 824.136 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | AIRLOOP DATACENTER TOP SUPPLY FAN | Fan:OnOff | 0.515849 | 0.61230759 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 824.14 | 824.14 | 1.0000 | 0.61230759 | 0.515849 | -0.13 | -1.18 | 0.00309210 | 7604.5 | 40.00 | 21.01 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 824.14 | -4.20 | 0.00269032 | -4.20 | 0.01563234 | 3.0304 | 0.00 | 0.00310466 | 23.37 | 0.00310466 | 17.2626 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 08:44:06
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
VAV_BOT WITH REHEAT_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 10.29 | - | |||
VAV_MID WITH REHEAT_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 95.13 | - | |||
VAV_TOP WITH REHEAT_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 10.60 | - | |||
CAV_BAS_OA_CONTROLLER | DifferentialDryBulb | 1.20 | 6.07 | - | |||
AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER | DifferentialDryBulb | 0.34 | 21.72 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
CORE_BOTTOM | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_MID | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_TOP | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
BASEMENT | 2807.17 | 171.17 | 1.83 |
CORE_BOTTOM | 2722.50 | 415.33 | 12.83 |
CORE_MID | 1409.00 | 2503.33 | 18.83 |
CORE_TOP | 1432.50 | 3604.83 | 352.67 |
PERIMETER_BOT_ZN_3 | 1529.17 | 3056.50 | 53.50 |
PERIMETER_BOT_ZN_2 | 1708.50 | 3469.00 | 101.67 |
PERIMETER_BOT_ZN_1 | 2167.67 | 3080.50 | 173.00 |
PERIMETER_BOT_ZN_4 | 2869.17 | 2047.17 | 183.50 |
PERIMETER_MID_ZN_3 | 1771.33 | 4237.50 | 921.67 |
PERIMETER_MID_ZN_2 | 1831.17 | 3597.33 | 869.00 |
PERIMETER_MID_ZN_1 | 2302.67 | 3669.83 | 668.67 |
PERIMETER_MID_ZN_4 | 2081.33 | 4095.00 | 772.00 |
PERIMETER_TOP_ZN_3 | 2329.33 | 4516.00 | 1569.67 |
PERIMETER_TOP_ZN_2 | 2657.33 | 4214.83 | 1463.50 |
PERIMETER_TOP_ZN_1 | 2621.50 | 3955.83 | 1157.67 |
PERIMETER_TOP_ZN_4 | 2462.67 | 4358.50 | 1287.33 |
DATACENTER_BOT_ZN_6 | 5943.00 | 1025.50 | 1025.50 |
DATACENTER_MID_ZN_6 | 5840.33 | 263.67 | 243.33 |
DATACENTER_TOP_ZN_6 | 5540.83 | 457.17 | 337.33 |
DATACENTER_BASEMENT_ZN_6 | 5943.00 | 5785.67 | 5785.67 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
Facility | 5943.00 | 5943.00 | 5943.00 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
BASEMENT | 0.00 | 40.83 | 0.00 | 3.33 |
CORE_BOTTOM | 0.00 | 0.17 | 0.00 | 0.00 |
CORE_MID | 1.50 | 0.00 | 0.83 | 0.00 |
CORE_TOP | 4.00 | 0.00 | 0.67 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 12.17 | 0.00 | 12.17 |
PERIMETER_BOT_ZN_1 | 0.00 | 24.33 | 0.00 | 24.00 |
PERIMETER_BOT_ZN_4 | 0.00 | 53.00 | 0.00 | 26.33 |
PERIMETER_MID_ZN_3 | 8.00 | 0.00 | 1.00 | 0.00 |
PERIMETER_MID_ZN_2 | 7.50 | 12.33 | 0.33 | 12.33 |
PERIMETER_MID_ZN_1 | 4.67 | 20.50 | 0.00 | 20.33 |
PERIMETER_MID_ZN_4 | 4.00 | 22.50 | 0.00 | 12.50 |
PERIMETER_TOP_ZN_3 | 73.33 | 0.00 | 14.83 | 0.00 |
PERIMETER_TOP_ZN_2 | 49.00 | 12.67 | 4.17 | 12.67 |
PERIMETER_TOP_ZN_1 | 35.50 | 16.17 | 2.67 | 15.67 |
PERIMETER_TOP_ZN_4 | 24.67 | 22.67 | 1.83 | 13.00 |
DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 73.50 | 0.00 | 72.17 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 78.17 | 258.17 | 15.67 | 182.00 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 08:44:06
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 60.99 | 149.60 | 6779.02 | 1.552 | 0.000 | 0.000 | 0.000 |
CORE_BOTTOM | 54.77 | 134.35 | 6849.35 | 1.121 | 0.000 | 0.000 | 0.000 |
CORE_MID | 54.77 | 134.35 | 6849.35 | 0.828 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 54.77 | 134.35 | 6849.35 | 0.776 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 6.88 | 16.87 | 860.00 | 0.994 | 0.041 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 4.43 | 10.87 | 554.22 | 1.625 | 0.042 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 6.88 | 16.87 | 860.02 | 1.742 | 0.041 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 4.43 | 10.87 | 554.22 | 2.221 | 0.042 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 6.88 | 16.87 | 860.00 | 0.775 | 0.095 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 3.86 | 10.87 | 554.22 | 1.429 | 0.105 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 6.88 | 16.87 | 860.02 | 1.642 | 0.095 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 4.43 | 10.87 | 554.22 | 1.649 | 0.099 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 6.88 | 16.87 | 860.00 | 0.769 | 0.118 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 4.43 | 10.87 | 554.22 | 1.522 | 0.122 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 6.88 | 16.87 | 860.02 | 1.623 | 0.118 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 4.43 | 10.87 | 554.22 | 1.667 | 0.122 | 0.000 | 0.000 |
DATACENTER_BOT_ZN_6 | 0.79 | 1.95 | 99.34 | 0.428 | 0.000 | 0.000 | 0.000 |
DATACENTER_MID_ZN_6 | 0.79 | 1.95 | 99.34 | 0.428 | 0.000 | 0.000 | 0.000 |
DATACENTER_TOP_ZN_6 | 0.79 | 1.95 | 99.34 | 0.428 | 0.000 | 0.000 | 0.000 |
DATACENTER_BASEMENT_ZN_6 | 17.20 | 42.18 | 1911.37 | 27.559 | 0.000 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 60.99 | 149.60 | 6779.02 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_BOTTOM | 54.77 | 134.35 | 6849.35 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_MID | 54.77 | 134.35 | 6849.35 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 54.77 | 134.35 | 6849.35 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 6.88 | 16.87 | 860.00 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 4.43 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 6.88 | 16.87 | 860.02 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 4.43 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 6.88 | 16.87 | 860.00 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 3.86 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 6.88 | 16.87 | 860.02 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 4.43 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 6.88 | 16.87 | 860.00 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 4.43 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 6.88 | 16.87 | 860.02 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 4.43 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
DATACENTER_BOT_ZN_6 | 0.79 | 1.95 | 99.34 | 0.000 | 0.000 | 0.000 | 0.000 |
DATACENTER_MID_ZN_6 | 0.79 | 1.95 | 99.34 | 0.000 | 0.000 | 0.000 | 0.000 |
DATACENTER_TOP_ZN_6 | 0.79 | 1.95 | 99.34 | 0.000 | 0.000 | 0.000 | 0.000 |
DATACENTER_BASEMENT_ZN_6 | 17.20 | 42.18 | 1911.37 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 08:44:06
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
BASEMENT | CAV_BAS | 60.99 | 149.60 | 6779.02 | 2779.43 | 1.2002 | 1.200 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | 54.77 | 134.35 | 6849.35 | 2496.12 | 0.0000 | 1.078 |
CORE_MID | VAV_MID WITH REHEAT | 54.77 | 134.35 | 6849.35 | 2496.12 | 0.0000 | 10.778 |
CORE_TOP | VAV_TOP WITH REHEAT | 54.77 | 134.35 | 6849.35 | 2496.12 | 0.0000 | 1.078 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | 6.88 | 16.87 | 860.00 | 313.41 | 0.0000 | 0.135 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | 4.43 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | 6.88 | 16.87 | 860.02 | 313.42 | 0.0000 | 0.135 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | 4.43 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | 6.88 | 16.87 | 860.00 | 313.41 | 0.0000 | 1.353 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | 3.86 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.872 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | 6.88 | 16.87 | 860.02 | 313.42 | 0.0000 | 1.353 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | 4.43 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.872 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | 6.88 | 16.87 | 860.00 | 313.41 | 0.0000 | 0.135 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | 4.43 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | 6.88 | 16.87 | 860.02 | 313.42 | 0.0000 | 0.135 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | 4.43 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | 0.79 | 1.95 | 99.34 | 36.20 | 0.0156 | 0.016 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | 0.79 | 1.95 | 99.34 | 36.20 | 0.1563 | 0.156 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | 0.79 | 1.95 | 99.34 | 36.20 | 0.0156 | 0.016 |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | 17.20 | 42.18 | 1911.37 | 783.68 | 0.3384 | 0.338 |
Total Facility | 1010.73 | 2493.19 | 126016.35 | 46320.38 | 1.7261 | 158.471 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
BASEMENT | 63175124.88 | 0.00 | 63175124.88 | 0.00 | 63175124.88 | 37848132.68 | 3933.31 | 244.92 | 4581.77 | 291.95 |
CORE_BOTTOM | 46693038.81 | 0.00 | 46693038.81 | 0.00 | 46693038.81 | 33990283.35 | 4119.12 | 39.45 | 4601.43 | 310.66 |
CORE_MID | 0.34E+09 | 0.00 | 0.34E+09 | 0.00 | 0.34E+09 | 0.34E+09 | 5180.15 | 57.74 | 3522.10 | 169.84 |
CORE_TOP | 31551026.67 | 0.00 | 31551026.67 | 0.00 | 31551026.67 | 33990283.35 | 5617.93 | 48.52 | 3093.56 | 232.51 |
PERIMETER_BOT_ZN_3 | 5200305.72 | 0.00 | 5200305.72 | 420131.66 | 5620437.38 | 4267819.30 | 4755.61 | 78.15 | 3926.24 | 310.66 |
PERIMETER_BOT_ZN_2 | 5512853.93 | 0.00 | 5512853.93 | 280087.58 | 5792941.51 | 2750345.05 | 3556.84 | 1.00 | 5202.16 | 310.66 |
PERIMETER_BOT_ZN_1 | 9093454.53 | 0.00 | 9093454.53 | 420131.66 | 9513586.19 | 4267912.63 | 3558.24 | 1.02 | 5200.73 | 310.66 |
PERIMETER_BOT_ZN_4 | 7517685.19 | 0.00 | 7517685.19 | 280087.58 | 7797772.77 | 2750345.05 | 3554.34 | 0.00 | 5205.66 | 310.66 |
PERIMETER_MID_ZN_3 | 39853196.24 | 0.00 | 39853196.24 | 985321.86 | 40838518.09 | 42678193.03 | 5314.06 | 70.02 | 3375.93 | 169.84 |
PERIMETER_MID_ZN_2 | 51627553.83 | 0.00 | 51627553.83 | 656880.79 | 52284434.62 | 27503450.52 | 3825.23 | 1.83 | 4932.95 | 1078.84 |
PERIMETER_MID_ZN_1 | 84002733.77 | 0.00 | 84002733.77 | 985321.86 | 84988055.62 | 42679126.28 | 3838.94 | 7.84 | 4913.22 | 169.84 |
PERIMETER_MID_ZN_4 | 54795330.30 | 0.00 | 54795330.30 | 656880.79 | 55452211.08 | 27503450.52 | 3820.08 | 3.39 | 4936.53 | 169.84 |
PERIMETER_TOP_ZN_3 | 3940956.89 | 0.00 | 3940956.89 | 1223376.39 | 5164333.28 | 4267819.30 | 5486.04 | 67.37 | 3206.59 | 232.51 |
PERIMETER_TOP_ZN_2 | 5017218.92 | 0.00 | 5017218.92 | 815583.70 | 5832802.63 | 2750345.05 | 3944.68 | 5.90 | 4809.42 | 232.51 |
PERIMETER_TOP_ZN_1 | 8279809.54 | 0.00 | 8279809.54 | 1223376.39 | 9503185.93 | 4267912.63 | 3964.23 | 6.46 | 4789.31 | 232.51 |
PERIMETER_TOP_ZN_4 | 5524876.49 | 0.00 | 5524876.49 | 815583.70 | 6340460.19 | 2750345.05 | 3926.57 | 4.47 | 4828.96 | 232.51 |
DATACENTER_BOT_ZN_6 | 244296.02 | 0.00 | 244296.02 | 0.00 | 244296.02 | 492981.60 | 4419.00 | 4341.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 2442960.18 | 0.00 | 2442960.18 | 0.00 | 2442960.18 | 4929815.99 | 4419.00 | 4341.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 244296.02 | 0.00 | 244296.02 | 0.00 | 244296.02 | 492981.60 | 4419.00 | 4341.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.43E+09 | 0.00 | 0.43E+09 | 0.00 | 0.43E+09 | 10671554.30 | 5.33 | 32.83 | 8721.83 | 2817.00 |
Total Facility | 0.63E+10 | 0.00 | 0.63E+10 | 38322411.53 | 0.64E+10 | 0.50E+10 | 5980.03 | 4394.30 | 8755.01 | 3726.00 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
BASEMENT | 2.8579 | 0.0000 | 2.8579 | 0.0000 | 2.8579 | 1.2002 | 1292.36 | 243.36 | 4407.28 |
CORE_BOTTOM | 2.0866 | 0.0000 | 2.0866 | 0.0000 | 2.0866 | 1.0778 | 1571.90 | 36.68 | 4334.42 |
CORE_MID | 15.4103 | 0.0000 | 15.4103 | 0.0000 | 15.4103 | 10.7782 | 2461.33 | 57.72 | 3423.96 |
CORE_TOP | 1.4454 | 0.0000 | 1.4454 | 0.0000 | 1.4454 | 1.0778 | 2858.68 | 47.72 | 3036.59 |
PERIMETER_BOT_ZN_3 | 0.2323 | 0.0000 | 0.2323 | 0.0095 | 0.2419 | 0.1353 | 2205.14 | 75.52 | 3662.34 |
PERIMETER_BOT_ZN_2 | 0.2452 | 0.0000 | 0.2452 | 0.0064 | 0.2516 | 0.0872 | 1050.50 | 1.00 | 4891.50 |
PERIMETER_BOT_ZN_1 | 0.4077 | 0.0000 | 0.4077 | 0.0095 | 0.4173 | 0.1353 | 1051.91 | 1.02 | 4890.07 |
PERIMETER_BOT_ZN_4 | 0.3347 | 0.0000 | 0.3347 | 0.0064 | 0.3410 | 0.0872 | 1048.00 | 0.00 | 4895.00 |
PERIMETER_MID_ZN_3 | 1.8168 | 0.0000 | 1.8168 | 0.0224 | 1.8392 | 1.3533 | 2599.52 | 69.80 | 3273.68 |
PERIMETER_MID_ZN_2 | 2.1597 | 0.0000 | 2.1597 | 0.0159 | 2.1755 | 0.8721 | 1157.50 | 0.81 | 3875.69 |
PERIMETER_MID_ZN_1 | 3.8482 | 0.0000 | 3.8482 | 0.0224 | 3.8705 | 1.3533 | 1164.94 | 4.59 | 4773.48 |
PERIMETER_MID_ZN_4 | 2.4909 | 0.0000 | 2.4909 | 0.0149 | 2.5058 | 0.8721 | 1155.12 | 1.42 | 4786.46 |
PERIMETER_TOP_ZN_3 | 0.1803 | 0.0000 | 0.1803 | 0.0278 | 0.2081 | 0.1353 | 2733.82 | 65.99 | 3143.19 |
PERIMETER_TOP_ZN_2 | 0.2300 | 0.0000 | 0.2300 | 0.0185 | 0.2486 | 0.0872 | 1230.17 | 3.99 | 4708.84 |
PERIMETER_TOP_ZN_1 | 0.3805 | 0.0000 | 0.3805 | 0.0278 | 0.4083 | 0.1353 | 1241.40 | 3.45 | 4698.15 |
PERIMETER_TOP_ZN_4 | 0.2520 | 0.0000 | 0.2520 | 0.0185 | 0.2706 | 0.0872 | 1218.58 | 2.99 | 4721.43 |
DATACENTER_BOT_ZN_6 | 0.0114 | 0.0000 | 0.0114 | 0.0000 | 0.0114 | 0.0156 | 1602.00 | 4341.00 | 0.00 |
DATACENTER_MID_ZN_6 | 0.1142 | 0.0000 | 0.1142 | 0.0000 | 0.1142 | 0.1563 | 1602.00 | 4341.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 0.0114 | 0.0000 | 0.0114 | 0.0000 | 0.0114 | 0.0156 | 1602.00 | 4341.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 14.1727 | 0.0000 | 14.1727 | 0.0000 | 14.1727 | 0.3384 | 5.33 | 32.83 | 5904.83 |
Total Facility | 281.2483 | 0.0000 | 281.2483 | 0.8803 | 282.1285 | 158.4706 | 3163.03 | 4376.02 | 5938.01 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
VAV_BOT WITH REHEAT | 0.10E+09 | 0.00 | 0.10E+09 | 48026705.38 | 3557.58 | 0.72 | 5201.70 | 310.66 |
VAV_MID WITH REHEAT | 0.80E+09 | 0.00 | 0.80E+09 | 0.48E+09 | 3848.95 | 6.53 | 4904.52 | 169.84 |
VAV_TOP WITH REHEAT | 76525397.58 | 0.00 | 76525397.58 | 48026705.38 | 3985.87 | 6.77 | 4767.36 | 232.51 |
CAV_BAS | 89010410.24 | 0.00 | 89010410.24 | 37848132.68 | 3888.08 | 1.79 | 4870.13 | 291.95 |
AIRLOOP DATACENTER BASEMENT | 0.61E+09 | 0.00 | 0.61E+09 | 10671554.30 | 5.33 | 0.00 | 8754.67 | 2817.00 |
AIRLOOP DATACENTER BOT | 344200.17 | 0.00 | 344200.17 | 492981.60 | 4419.00 | 0.00 | 4341.00 | 0.00 |
AIRLOOP DATACENTER MID | 3442001.72 | 0.00 | 3442001.72 | 4929815.99 | 4419.00 | 0.00 | 4341.00 | 0.00 |
AIRLOOP DATACENTER TOP | 344200.17 | 0.00 | 344200.17 | 492981.60 | 4419.00 | 0.00 | 4341.00 | 0.00 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
VAV_BOT WITH REHEAT | 4.6588 | 0.0000 | 4.6588 | 1.5229 | 1051.24 | 0.72 | 4891.04 |
VAV_MID WITH REHEAT | 36.5237 | 0.0000 | 36.5237 | 15.2292 | 1170.69 | 3.56 | 4768.76 |
VAV_TOP WITH REHEAT | 3.5057 | 0.0000 | 3.5057 | 1.5229 | 1253.39 | 5.08 | 4684.53 |
CAV_BAS | 4.0267 | 0.0000 | 4.0267 | 1.2002 | 1285.52 | 0.06 | 4657.42 |
AIRLOOP DATACENTER BASEMENT | 19.9686 | 0.0000 | 19.9686 | 0.3384 | 5.33 | 0.00 | 5937.67 |
AIRLOOP DATACENTER BOT | 0.0161 | 0.0000 | 0.0161 | 0.0156 | 1602.00 | 0.00 | 4341.00 |
AIRLOOP DATACENTER MID | 0.1609 | 0.0000 | 0.1609 | 0.1563 | 1602.00 | 0.00 | 4341.00 |
AIRLOOP DATACENTER TOP | 0.0161 | 0.0000 | 0.0161 | 0.0156 | 1602.00 | 0.00 | 4341.00 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
VAV_BOT WITH REHEAT | 0.00 | 0.00 | 4718.08 | 0.00 | 0.00 | 0.00 | 487.58 | 0.00 | 0.00 | 0.00 |
VAV_MID WITH REHEAT | 0.00 | 0.00 | 4222.49 | 0.00 | 0.00 | 0.00 | 745.61 | 0.00 | 0.00 | 0.00 |
VAV_TOP WITH REHEAT | 0.00 | 0.00 | 3700.75 | 0.00 | 0.00 | 0.00 | 1346.25 | 0.00 | 0.00 | 0.00 |
CAV_BAS | 0.00 | 241.50 | 4719.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER BASEMENT | 0.00 | 32.83 | 8721.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER BOT | 0.00 | 4341.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER MID | 0.00 | 4341.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER TOP | 0.00 | 4341.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
VAV_BOT WITH REHEAT | 0.0000 | 0.0000 | 6.0186 | 0.0000 | 0.0000 | 0.0000 | 2.3888 | 0.0000 | 0.0000 | 0.0000 |
VAV_MID WITH REHEAT | 0.0000 | 0.0000 | 49.1926 | 0.0000 | 0.0000 | 0.0000 | 23.8007 | 0.0000 | 0.0000 | 0.0000 |
VAV_TOP WITH REHEAT | 0.0000 | 0.0000 | 5.0950 | 0.0000 | 0.0000 | 0.0000 | 2.3513 | 0.0000 | 0.0000 | 0.0000 |
CAV_BAS | 0.0000 | 1.6945 | 5.3134 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
AIRLOOP DATACENTER BASEMENT | 0.0000 | 0.4892 | 20.0979 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
AIRLOOP DATACENTER BOT | 0.0000 | 0.0220 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
AIRLOOP DATACENTER MID | 0.0000 | 0.2203 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
AIRLOOP DATACENTER TOP | 0.0000 | 0.0220 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 08:44:06
Surfaces by ClassTotal | Outdoors | |
Wall | 98 | 30 |
Floor | 41 | 0 |
Roof | 30 | 1 |
Internal Mass | 16 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 24 | 24 |
Door | 12 | 12 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 8 |
Conditioned Zones | 23 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 3 |
Count | |
IDF Objects | 1395 |
Defaulted Fields | 1182 |
Fields with Defaults | 3867 |
Autosized Fields | 332 |
Autosizable Fields | 411 |
Autocalculated Fields | 226 |
Autocalculatable Fields | 473 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 08:44:06
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 26435.25 | 327789.53 | 29-MAY-05:00 | 2030054.14 | 29-AUG-15:10 |
Electricity:Building | 18620.46 | 225715.65 | 07-MAY-17:10 | 1164206.62 | 01-DEC-16:20 |
Electricity:Zone:BASEMENT | 687.24 | 14732.47 | 01-JAN-00:10 | 36407.88 | 02-JAN-08:10 |
Electricity:SpaceType:GENERAL | 18620.46 | 225715.65 | 07-MAY-17:10 | 1164206.62 | 01-DEC-16:20 |
InteriorLights:Electricity | 3944.06 | 18459.50 | 08-JAN-10:30 | 385834.94 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:BASEMENT | 262.84 | 1274.92 | 01-JAN-00:10 | 22950.34 | 02-JAN-08:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 3944.06 | 18459.50 | 08-JAN-10:30 | 385834.94 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity | 3944.06 | 18459.50 | 08-JAN-10:30 | 385834.94 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:BASEMENT | 262.84 | 1274.92 | 01-JAN-00:10 | 22950.34 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 3944.06 | 18459.50 | 08-JAN-10:30 | 385834.94 | 02-JAN-08:10 |
Electricity:Zone:CORE_BOTTOM | 525.67 | 5598.20 | 01-JAN-00:10 | 37817.64 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_BOTTOM | 236.05 | 1144.97 | 01-JAN-00:10 | 20611.01 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_BOTTOM | 236.05 | 1144.97 | 01-JAN-00:10 | 20611.01 | 02-JAN-08:10 |
Electricity:Zone:CORE_MID | 5256.66 | 55981.88 | 01-JAN-00:10 | 378175.77 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_MID | 2360.53 | 11449.71 | 01-JAN-00:10 | 206110.14 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_MID | 2360.53 | 11449.71 | 01-JAN-00:10 | 206110.14 | 02-JAN-08:10 |
Electricity:Zone:CORE_TOP | 525.67 | 5598.19 | 01-JAN-00:10 | 37817.58 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_TOP | 236.05 | 1144.97 | 01-JAN-00:10 | 20611.01 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_TOP | 236.05 | 1144.97 | 01-JAN-00:10 | 20611.01 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_3 | 54.23 | 627.57 | 02-APR-17:10 | 4748.47 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 17.87 | 68.40 | 08-JAN-10:30 | 2587.92 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 17.87 | 68.40 | 08-JAN-10:30 | 2587.92 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_2 | 34.80 | 404.43 | 23-APR-17:10 | 3060.10 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 11.37 | 44.08 | 01-JAN-10:00 | 1667.75 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 11.37 | 44.08 | 01-JAN-10:00 | 1667.75 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_1 | 53.81 | 627.58 | 19-MAR-17:10 | 4748.56 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 17.44 | 68.40 | 01-JAN-09:50 | 2587.98 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 17.44 | 68.40 | 01-JAN-09:50 | 2587.98 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_4 | 34.78 | 404.43 | 19-MAR-17:10 | 3060.09 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 11.35 | 44.08 | 01-JAN-13:10 | 1667.75 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 11.35 | 44.08 | 01-JAN-13:10 | 1667.75 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_MID_ZN_3 | 541.79 | 6275.73 | 19-MAR-17:10 | 47484.70 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 178.14 | 684.02 | 08-JAN-10:20 | 25879.19 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 178.14 | 684.02 | 08-JAN-10:20 | 25879.19 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_MID_ZN_2 | 347.79 | 4044.32 | 09-APR-17:10 | 30600.95 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 113.43 | 440.81 | 01-JAN-10:00 | 16677.53 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 113.43 | 440.81 | 01-JAN-10:00 | 16677.53 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_MID_ZN_1 | 537.85 | 6275.83 | 19-MAR-17:10 | 47485.60 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 174.19 | 684.04 | 01-JAN-09:50 | 25879.75 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 174.19 | 684.04 | 01-JAN-09:50 | 25879.75 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_MID_ZN_4 | 347.61 | 4044.30 | 19-MAR-17:10 | 30600.86 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 113.26 | 440.81 | 01-JAN-13:00 | 16677.53 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 113.26 | 440.81 | 01-JAN-13:00 | 16677.53 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_3 | 54.18 | 627.57 | 19-MAR-17:10 | 4748.47 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 17.81 | 68.40 | 08-JAN-10:20 | 2587.92 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 17.81 | 68.40 | 08-JAN-10:20 | 2587.92 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_2 | 34.78 | 404.43 | 09-APR-17:10 | 3060.10 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 11.34 | 44.08 | 01-JAN-10:00 | 1667.75 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 11.34 | 44.08 | 01-JAN-10:00 | 1667.75 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_1 | 53.78 | 627.58 | 19-MAR-17:10 | 4748.56 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 17.42 | 68.40 | 01-JAN-09:50 | 2587.98 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 17.42 | 68.40 | 01-JAN-09:50 | 2587.98 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_4 | 34.76 | 404.43 | 19-MAR-17:10 | 3060.09 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 11.32 | 44.08 | 01-JAN-13:00 | 1667.75 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 11.32 | 44.08 | 01-JAN-13:00 | 1667.75 | 02-JAN-08:10 |
Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 7568.97 | 95267.60 | 01-JAN-00:10 | 386103.53 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 74.11 | 359.47 | 01-JAN-00:10 | 6471.01 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 74.11 | 359.47 | 01-JAN-00:10 | 6471.01 | 02-JAN-08:10 |
Electricity:Zone:DATACENTER_BOT_ZN_6 | 160.51 | 1980.76 | 01-JAN-00:10 | 8373.14 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_BOT_ZN_6 | 6.63 | 32.15 | 01-JAN-00:10 | 578.72 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_BOT_ZN_6 | 6.63 | 32.15 | 01-JAN-00:10 | 578.72 | 02-JAN-08:10 |
Electricity:Zone:DATACENTER_MID_ZN_6 | 1605.09 | 19807.58 | 01-JAN-00:10 | 83731.41 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_MID_ZN_6 | 66.28 | 321.53 | 01-JAN-00:10 | 5787.18 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_MID_ZN_6 | 66.28 | 321.53 | 01-JAN-00:10 | 5787.18 | 02-JAN-08:10 |
Electricity:Zone:DATACENTER_TOP_ZN_6 | 160.51 | 1980.76 | 01-JAN-00:10 | 8373.14 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_TOP_ZN_6 | 6.63 | 32.15 | 01-JAN-00:10 | 578.72 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_TOP_ZN_6 | 6.63 | 32.15 | 01-JAN-00:10 | 578.72 | 02-JAN-08:10 |
InteriorEquipment:Electricity | 14676.40 | 207256.16 | 01-JAN-00:10 | 778371.69 | 03-APR-07:10 |
InteriorEquipment:Electricity:Zone:BASEMENT | 424.40 | 13457.54 | 01-JAN-00:10 | 13457.54 | 01-JAN-00:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 14676.40 | 207256.16 | 01-JAN-00:10 | 778371.69 | 03-APR-07:10 |
MiscPlug:InteriorEquipment:Electricity | 5334.97 | 88964.76 | 01-JAN-00:10 | 305206.10 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:BASEMENT | 424.40 | 13457.54 | 01-JAN-00:10 | 13457.54 | 01-JAN-00:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 5334.97 | 88964.76 | 01-JAN-00:10 | 305206.10 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 289.61 | 4453.23 | 01-JAN-00:10 | 17206.63 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 289.61 | 4453.23 | 01-JAN-00:10 | 17206.63 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_MID | 2896.13 | 44532.17 | 01-JAN-00:10 | 172065.63 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_MID | 2896.13 | 44532.17 | 01-JAN-00:10 | 172065.63 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_TOP | 289.61 | 4453.22 | 01-JAN-00:10 | 17206.56 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_TOP | 289.61 | 4453.22 | 01-JAN-00:10 | 17206.56 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 36.37 | 559.17 | 01-JAN-00:10 | 2160.55 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 36.37 | 559.17 | 01-JAN-00:10 | 2160.55 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.34 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.34 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 36.37 | 559.18 | 01-JAN-00:10 | 2160.58 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 36.37 | 559.18 | 01-JAN-00:10 | 2160.58 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.33 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.33 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 363.65 | 5591.71 | 01-JAN-00:10 | 21605.52 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 363.65 | 5591.71 | 01-JAN-00:10 | 21605.52 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 234.35 | 3603.51 | 01-JAN-00:10 | 13923.42 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 234.35 | 3603.51 | 01-JAN-00:10 | 13923.42 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 363.66 | 5591.79 | 01-JAN-00:10 | 21605.85 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 363.66 | 5591.79 | 01-JAN-00:10 | 21605.85 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 234.35 | 3603.49 | 01-JAN-00:10 | 13923.33 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 234.35 | 3603.49 | 01-JAN-00:10 | 13923.33 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 36.37 | 559.17 | 01-JAN-00:10 | 2160.55 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 36.37 | 559.17 | 01-JAN-00:10 | 2160.55 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.34 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.34 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 36.37 | 559.18 | 01-JAN-00:10 | 2160.58 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 36.37 | 559.18 | 01-JAN-00:10 | 2160.58 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.33 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.33 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 7494.86 | 94908.13 | 01-JAN-00:10 | 379632.52 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity | 9341.42 | 118291.40 | 01-JAN-00:10 | 473165.59 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 7494.86 | 94908.13 | 01-JAN-00:10 | 379632.52 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:SpaceType:GENERAL | 9341.42 | 118291.40 | 01-JAN-00:10 | 473165.59 | 31-MAR-23:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_BOT_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_BOT_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_MID_ZN_6 | 1538.81 | 19486.06 | 01-JAN-00:10 | 77944.22 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_MID_ZN_6 | 1538.81 | 19486.06 | 01-JAN-00:10 | 77944.22 | 31-MAR-23:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_TOP_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_TOP_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
Electricity:Plant | 1091.75 | 3606.72 | 16-JAN-05:50 | 388890.74 | 29-AUG-14:30 |
HeatRejection:Electricity | 413.76 | 160.60 | 07-JAN-08:00 | 82535.37 | 27-APR-12:20 |
General:HeatRejection:Electricity | 413.76 | 160.60 | 07-JAN-08:00 | 82535.37 | 27-APR-12:20 |
Electricity:HVAC | 4169.66 | 48507.72 | 12-JAN-02:20 | 462329.12 | 29-AUG-15:10 |
ExteriorEquipment:Electricity | 1934.80 | 28603.11 | 01-JAN-00:10 | 118535.44 | 02-JAN-08:20 |
Transformer:ExteriorEquipment:Electricity | 80.19 | 1421.04 | 01-JAN-00:10 | 5057.48 | 01-DEC-16:30 |
ElectricityPurchased:Facility | 26435.25 | 327789.53 | 29-MAY-05:00 | 2030054.14 | 29-AUG-15:10 |
ElectricityPurchased:Plant | 26435.25 | 327789.53 | 29-MAY-05:00 | 2030054.14 | 29-AUG-15:10 |
Cogeneration:ElectricityPurchased | 26435.25 | 327789.53 | 29-MAY-05:00 | 2030054.14 | 29-AUG-15:10 |
General:Cogeneration:ElectricityPurchased | 26435.25 | 327789.53 | 29-MAY-05:00 | 2030054.14 | 29-AUG-15:10 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 26435.25 | 327789.53 | 29-MAY-05:00 | 2030054.14 | 29-AUG-15:10 |
ElectricityNet:Plant | 26435.25 | 327789.53 | 29-MAY-05:00 | 2030054.14 | 29-AUG-15:10 |
Cogeneration:ElectricityNet | 26435.25 | 327789.53 | 29-MAY-05:00 | 2030054.14 | 29-AUG-15:10 |
General:Cogeneration:ElectricityNet | 26435.25 | 327789.53 | 29-MAY-05:00 | 2030054.14 | 29-AUG-15:10 |
Fans:Electricity | 2326.84 | 42684.28 | 02-JAN-23:20 | 284421.05 | 10-AUG-14:50 |
General:Fans:Electricity | 2326.84 | 42684.28 | 02-JAN-23:20 | 284421.05 | 10-AUG-14:50 |
ExteriorLights:Electricity | 698.76 | 0.00 | 01-JAN-08:10 | 57580.60 | 01-JAN-06:10 |
General:ExteriorLights:Electricity | 698.76 | 0.00 | 01-JAN-08:10 | 57580.60 | 01-JAN-06:10 |
ElevatorLift:ExteriorEquipment:Electricity | 1848.78 | 27144.47 | 01-JAN-00:10 | 113101.96 | 01-JAN-07:10 |
ElevatorLightsFan:ExteriorEquipment:Electricity | 5.83 | 37.60 | 01-JAN-00:10 | 376.00 | 01-JAN-07:10 |
Cooling:Electricity | 1136.32 | 1472.93 | 03-JAN-08:00 | 433009.80 | 29-AUG-14:30 |
General:Cooling:Electricity | 1136.32 | 1472.93 | 03-JAN-08:00 | 433009.80 | 29-AUG-14:30 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Humidifier:Electricity | 1029.99 | 0.00 | 11-JAN-20:10 | 100000.00 | 12-FEB-09:40 |
General:Humidifier:Electricity | 1029.99 | 0.00 | 11-JAN-20:10 | 100000.00 | 12-FEB-09:40 |
Boiler Parasitic:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Pumps:Electricity | 274.32 | 3422.86 | 14-JAN-05:50 | 47863.96 | 27-APR-11:50 |
General:Pumps:Electricity | 274.32 | 3422.86 | 14-JAN-05:50 | 47863.96 | 27-APR-11:50 |
WIRED_LTG_ELECTRICITY | 110.83 | 0.00 | 01-JAN-00:10 | 10841.96 | 02-JAN-08:20 |
WIRED_INT_EQUIP | 5334.97 | 88964.76 | 31-MAR-23:10 | 305206.10 | 03-APR-07:10 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 1909.12 | 8146.58 | 07-MAY-16:00 | 1643369.88 | 02-JAN-05:20 |
NaturalGas:Plant | 1909.12 | 8146.58 | 07-MAY-16:00 | 1643369.88 | 02-JAN-05:20 |
Heating:NaturalGas | 1110.48 | 0.00 | 01-JAN-10:00 | 1635223.30 | 02-JAN-05:20 |
Boiler:Heating:NaturalGas | 1110.48 | 0.00 | 01-JAN-10:00 | 1635223.30 | 02-JAN-05:20 |
WaterSystems:NaturalGas | 798.65 | 8146.58 | 03-JAN-05:20 | 83859.11 | 14-FEB-12:20 |
Water Heater:WaterSystems:NaturalGas | 798.65 | 8146.58 | 03-JAN-05:20 | 83859.11 | 14-FEB-12:20 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
PlantLoopCoolingDemand:Facility | 6003.01 | 3550.94 | 03-JAN-08:00 | 2527242.32 | 29-AUG-14:30 |
PlantLoopCoolingDemand:HVAC | 6003.01 | 3550.94 | 03-JAN-08:00 | 2527242.32 | 29-AUG-14:30 |
CoolingCoils:PlantLoopCoolingDemand | 6003.01 | 3550.94 | 03-JAN-08:00 | 2527242.32 | 29-AUG-14:30 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 4667.06 | 0.00 | 12-JAN-01:20 | 0.00 | 10-AUG-16:00 |
Water:HVAC | 383.16 | 0.00 | 11-JAN-20:10 | 0.00 | 13-FEB-05:10 |
Humidifier:Water | 383.16 | 0.00 | 11-JAN-20:10 | 0.00 | 13-FEB-05:10 |
General:Humidifier:Water | 383.16 | 0.00 | 11-JAN-20:10 | 0.00 | 13-FEB-05:10 |
MainsWater:Facility | 4667.06 | 0.00 | 12-JAN-01:20 | 0.00 | 10-AUG-16:00 |
MainsWater:HVAC | 383.16 | 0.00 | 11-JAN-20:10 | 0.00 | 13-FEB-05:10 |
Humidifier:MainsWater | 383.16 | 0.00 | 11-JAN-20:10 | 0.00 | 13-FEB-05:10 |
General:Humidifier:MainsWater | 383.16 | 0.00 | 11-JAN-20:10 | 0.00 | 13-FEB-05:10 |
Water:Plant | 4283.90 | 0.00 | 01-JAN-00:10 | 0.00 | 10-AUG-16:00 |
WaterSystems:Water | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterUse:WaterSystems:Water | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
MainsWater:Plant | 4283.90 | 0.00 | 01-JAN-00:10 | 0.00 | 10-AUG-16:00 |
WaterSystems:MainsWater | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterUse:WaterSystems:MainsWater | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water Heater:WaterSystems:Water | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:MainsWater | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
HeatRejection:Water | 2003.73 | 0.00 | 01-JAN-00:10 | 0.00 | 10-AUG-16:00 |
General:HeatRejection:Water | 2003.73 | 0.00 | 01-JAN-00:10 | 0.00 | 10-AUG-16:00 |
HeatRejection:MainsWater | 2003.73 | 0.00 | 01-JAN-00:10 | 0.00 | 10-AUG-16:00 |
General:HeatRejection:MainsWater | 2003.73 | 0.00 | 01-JAN-00:10 | 0.00 | 10-AUG-16:00 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 34065.32 | 96775.10 | 16-JAN-05:50 | 9935700.55 | 29-AUG-14:30 |
EnergyTransfer:Building | 18472.10 | 88491.21 | 21-JAN-18:20 | 1758776.93 | 10-AUG-15:20 |
EnergyTransfer:Zone:BASEMENT | 711.30 | 0.00 | 01-JAN-00:10 | 69607.37 | 28-AUG-05:10 |
Heating:EnergyTransfer | 273.33 | 0.00 | 05-JAN-22:10 | 1141795.06 | 02-JAN-05:30 |
Heating:EnergyTransfer:Zone:BASEMENT | 2.48 | 0.00 | 01-JAN-00:10 | 12228.46 | 01-APR-16:10 |
General:Heating:EnergyTransfer | 273.33 | 0.00 | 05-JAN-22:10 | 1141795.06 | 02-JAN-05:30 |
General:Heating:EnergyTransfer:Zone:BASEMENT | 2.48 | 0.00 | 01-JAN-00:10 | 12228.46 | 01-APR-16:10 |
Cooling:EnergyTransfer | 18198.78 | 87023.17 | 16-JAN-05:50 | 1758776.93 | 10-AUG-15:20 |
Cooling:EnergyTransfer:Zone:BASEMENT | 708.82 | 0.00 | 01-JAN-00:10 | 69607.37 | 28-AUG-05:10 |
General:Cooling:EnergyTransfer | 18198.78 | 87023.17 | 16-JAN-05:50 | 1758776.93 | 10-AUG-15:20 |
General:Cooling:EnergyTransfer:Zone:BASEMENT | 708.82 | 0.00 | 01-JAN-00:10 | 69607.37 | 28-AUG-05:10 |
EnergyTransfer:Zone:CORE_BOTTOM | 630.94 | 0.00 | 01-JAN-00:10 | 54347.93 | 14-AUG-13:10 |
Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 630.94 | 0.00 | 01-JAN-00:10 | 54347.93 | 14-AUG-13:10 |
General:Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 630.94 | 0.00 | 01-JAN-00:10 | 54347.93 | 14-AUG-13:10 |
EnergyTransfer:Zone:CORE_MID | 4404.54 | 0.00 | 01-JAN-00:10 | 451493.01 | 10-AUG-16:00 |
Heating:EnergyTransfer:Zone:CORE_MID | 3.90 | 0.00 | 01-JAN-00:10 | 395304.53 | 02-JAN-05:20 |
General:Heating:EnergyTransfer:Zone:CORE_MID | 3.90 | 0.00 | 01-JAN-00:10 | 395304.53 | 02-JAN-05:20 |
Cooling:EnergyTransfer:Zone:CORE_MID | 4400.63 | 0.00 | 01-JAN-00:10 | 451493.01 | 10-AUG-16:00 |
General:Cooling:EnergyTransfer:Zone:CORE_MID | 4400.63 | 0.00 | 01-JAN-00:10 | 451493.01 | 10-AUG-16:00 |
EnergyTransfer:Zone:CORE_TOP | 391.59 | 0.00 | 01-JAN-00:40 | 72394.94 | 02-JAN-05:20 |
Heating:EnergyTransfer:Zone:CORE_TOP | 5.32 | 0.00 | 01-JAN-00:10 | 72394.94 | 02-JAN-05:20 |
General:Heating:EnergyTransfer:Zone:CORE_TOP | 5.32 | 0.00 | 01-JAN-00:10 | 72394.94 | 02-JAN-05:20 |
Cooling:EnergyTransfer:Zone:CORE_TOP | 386.26 | 0.00 | 01-JAN-00:40 | 51505.50 | 10-AUG-15:50 |
General:Cooling:EnergyTransfer:Zone:CORE_TOP | 386.26 | 0.00 | 01-JAN-00:40 | 51505.50 | 10-AUG-15:50 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 64.49 | 0.00 | 01-JAN-00:10 | 10363.51 | 24-JUL-15:00 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 0.01 | 0.00 | 01-JAN-00:10 | 2519.21 | 17-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 0.01 | 0.00 | 01-JAN-00:10 | 2519.21 | 17-JAN-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 64.48 | 0.00 | 01-JAN-00:10 | 10363.51 | 24-JUL-15:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 64.48 | 0.00 | 01-JAN-00:10 | 10363.51 | 24-JUL-15:00 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 64.70 | 0.00 | 01-JAN-00:10 | 16307.84 | 31-JUL-08:00 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 0.02 | 0.00 | 01-JAN-00:10 | 2093.11 | 17-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 0.02 | 0.00 | 01-JAN-00:10 | 2093.11 | 17-JAN-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 64.68 | 0.00 | 01-JAN-00:10 | 16307.84 | 31-JUL-08:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 64.68 | 0.00 | 01-JAN-00:10 | 16307.84 | 31-JUL-08:00 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 111.47 | 0.00 | 01-JAN-00:10 | 25950.40 | 04-OCT-12:40 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 0.13 | 0.00 | 01-JAN-00:10 | 4850.71 | 17-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 0.13 | 0.00 | 01-JAN-00:10 | 4850.71 | 17-JAN-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 111.34 | 0.00 | 01-JAN-00:10 | 25950.40 | 04-OCT-12:40 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 111.34 | 0.00 | 01-JAN-00:10 | 25950.40 | 04-OCT-12:40 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 96.79 | 0.00 | 01-JAN-00:10 | 20850.19 | 10-AUG-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 01-JAN-00:10 | 1006.48 | 17-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 01-JAN-00:10 | 1006.48 | 17-JAN-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 96.79 | 0.00 | 01-JAN-00:10 | 20850.19 | 10-AUG-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 96.79 | 0.00 | 01-JAN-00:10 | 20850.19 | 10-AUG-16:00 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 456.94 | 0.00 | 01-JAN-00:10 | 118417.43 | 02-JAN-05:20 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 44.76 | 0.00 | 01-JAN-00:10 | 118417.43 | 02-JAN-05:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 44.76 | 0.00 | 01-JAN-00:10 | 118417.43 | 02-JAN-05:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 412.19 | 0.00 | 01-JAN-00:10 | 92103.34 | 24-JUL-15:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 412.19 | 0.00 | 01-JAN-00:10 | 92103.34 | 24-JUL-15:00 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 542.48 | 0.00 | 01-JAN-00:10 | 170991.86 | 10-AUG-08:40 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 30.27 | 0.00 | 01-JAN-00:10 | 107348.64 | 02-JAN-05:30 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 30.27 | 0.00 | 01-JAN-00:10 | 107348.64 | 02-JAN-05:30 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 512.21 | 0.00 | 01-JAN-00:10 | 170991.86 | 10-AUG-08:40 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 512.21 | 0.00 | 01-JAN-00:10 | 170991.86 | 10-AUG-08:40 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 978.93 | 0.00 | 01-JAN-00:10 | 280974.83 | 04-OCT-13:00 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 30.87 | 0.00 | 01-JAN-00:10 | 162430.89 | 02-JAN-05:30 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 30.87 | 0.00 | 01-JAN-00:10 | 162430.89 | 02-JAN-05:30 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 948.07 | 0.00 | 01-JAN-00:10 | 280974.83 | 04-OCT-13:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 948.07 | 0.00 | 01-JAN-00:10 | 280974.83 | 04-OCT-13:00 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 594.90 | 0.00 | 01-JAN-00:10 | 188207.92 | 10-AUG-16:30 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 17.84 | 0.00 | 01-JAN-00:10 | 94768.35 | 02-JAN-05:30 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 17.84 | 0.00 | 01-JAN-00:10 | 94768.35 | 02-JAN-05:30 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 577.06 | 0.00 | 01-JAN-00:10 | 188207.92 | 10-AUG-16:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 577.06 | 0.00 | 01-JAN-00:10 | 188207.92 | 10-AUG-16:30 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 51.23 | 0.00 | 01-JAN-00:40 | 13161.90 | 02-JAN-05:20 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 15.30 | 0.00 | 01-JAN-00:40 | 13161.90 | 02-JAN-05:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 15.30 | 0.00 | 01-JAN-00:40 | 13161.90 | 02-JAN-05:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 35.93 | 0.00 | 01-JAN-00:20 | 10164.75 | 24-JUL-15:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 35.93 | 0.00 | 01-JAN-00:20 | 10164.75 | 24-JUL-15:00 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 55.67 | 0.00 | 01-JAN-00:40 | 16969.26 | 10-AUG-08:50 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 9.30 | 0.00 | 01-JAN-00:40 | 13011.39 | 21-FEB-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 9.30 | 0.00 | 01-JAN-00:40 | 13011.39 | 21-FEB-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 46.36 | 0.00 | 01-JAN-00:20 | 16969.26 | 10-AUG-08:50 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 46.36 | 0.00 | 01-JAN-00:20 | 16969.26 | 10-AUG-08:50 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 96.70 | 0.00 | 01-JAN-00:40 | 28132.02 | 04-OCT-13:10 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 10.87 | 0.00 | 01-JAN-00:40 | 19194.94 | 17-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 10.87 | 0.00 | 01-JAN-00:40 | 19194.94 | 17-JAN-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 85.84 | 0.00 | 01-JAN-00:20 | 28132.02 | 04-OCT-13:10 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 85.84 | 0.00 | 01-JAN-00:20 | 28132.02 | 04-OCT-13:10 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 59.20 | 0.00 | 01-JAN-00:40 | 19385.31 | 10-AUG-16:30 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 6.24 | 0.00 | 01-JAN-00:40 | 11789.13 | 17-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 6.24 | 0.00 | 01-JAN-00:40 | 11789.13 | 17-JAN-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 52.95 | 0.00 | 01-JAN-00:20 | 19385.31 | 10-AUG-16:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 52.95 | 0.00 | 01-JAN-00:20 | 19385.31 | 10-AUG-16:30 |
EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 61.22 | 0.00 | 01-JAN-00:10 | 9348.99 | 14-AUG-15:00 |
Heating:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 1.15 | 0.00 | 01-JAN-00:10 | 4164.79 | 12-FEB-10:50 |
General:Heating:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 1.15 | 0.00 | 01-JAN-00:10 | 4164.79 | 12-FEB-10:50 |
Cooling:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 60.07 | 0.00 | 01-JAN-00:10 | 9348.99 | 14-AUG-15:00 |
General:Cooling:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 60.07 | 0.00 | 01-JAN-00:10 | 9348.99 | 14-AUG-15:00 |
EnergyTransfer:Zone:MIDFLOOR_PLENUM | 400.57 | 0.00 | 01-JAN-00:10 | 144582.70 | 02-JAN-06:10 |
Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 62.55 | 0.00 | 01-JAN-00:10 | 144582.70 | 02-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 62.55 | 0.00 | 01-JAN-00:10 | 144582.70 | 02-JAN-06:10 |
Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 338.02 | 0.00 | 01-JAN-00:10 | 76831.13 | 10-AUG-15:10 |
General:Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 338.02 | 0.00 | 01-JAN-00:10 | 76831.13 | 10-AUG-15:10 |
EnergyTransfer:Zone:TOPFLOOR_PLENUM | 73.92 | 0.00 | 01-JAN-00:40 | 22745.88 | 17-JAN-05:30 |
Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 28.56 | 0.00 | 01-JAN-00:40 | 22745.88 | 17-JAN-05:30 |
General:Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 28.56 | 0.00 | 01-JAN-00:40 | 22745.88 | 17-JAN-05:30 |
Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 45.37 | 0.00 | 01-JAN-00:10 | 20091.87 | 10-AUG-14:20 |
General:Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 45.37 | 0.00 | 01-JAN-00:10 | 20091.87 | 10-AUG-14:20 |
EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 139.11 | 624.72 | 17-JAN-07:00 | 8852.88 | 06-AUG-18:50 |
Heating:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 139.11 | 624.72 | 17-JAN-07:00 | 8852.88 | 06-AUG-18:50 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 139.11 | 624.72 | 17-JAN-07:00 | 8852.88 | 06-AUG-18:50 |
EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 1192.61 | 10.03 | 21-JAN-18:20 | 82950.23 | 06-AUG-18:40 |
Heating:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 3.00 | 0.00 | 02-JAN-14:50 | 5809.87 | 03-JAN-01:00 |
General:Heating:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 3.00 | 0.00 | 02-JAN-14:50 | 5809.87 | 03-JAN-01:00 |
Cooling:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 1189.62 | 0.00 | 01-JAN-00:10 | 82950.23 | 06-AUG-18:40 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 1189.62 | 0.00 | 01-JAN-00:10 | 82950.23 | 06-AUG-18:40 |
EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 109.84 | 2.72 | 26-JAN-08:30 | 8401.66 | 06-AUG-18:30 |
Heating:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 0.77 | 0.00 | 02-JAN-13:20 | 632.63 | 08-JAN-17:30 |
General:Heating:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 0.77 | 0.00 | 02-JAN-13:20 | 632.63 | 08-JAN-17:30 |
Cooling:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 109.07 | 0.00 | 01-JAN-00:10 | 8401.66 | 06-AUG-18:30 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 109.07 | 0.00 | 01-JAN-00:10 | 8401.66 | 06-AUG-18:30 |
EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 7182.97 | 86317.95 | 17-JAN-05:00 | 370176.85 | 30-AUG-16:00 |
Heating:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 7182.97 | 86317.95 | 17-JAN-05:00 | 370176.85 | 30-AUG-16:00 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 7182.97 | 86317.95 | 17-JAN-05:00 | 370176.85 | 30-AUG-16:00 |
PlantLoopHeatingDemand:Facility | 1236.16 | 0.00 | 03-JAN-00:10 | 1222336.96 | 02-JAN-05:30 |
PlantLoopHeatingDemand:Plant | 423.42 | 0.00 | 01-JAN-00:10 | 50361.36 | 13-FEB-12:20 |
WaterSystems:PlantLoopHeatingDemand | 423.42 | 0.00 | 01-JAN-00:10 | 50361.36 | 13-FEB-12:20 |
General:WaterSystems:PlantLoopHeatingDemand | 423.42 | 0.00 | 01-JAN-00:10 | 50361.36 | 13-FEB-12:20 |
EnergyTransfer:HVAC | 6083.11 | 2145.33 | 03-JAN-05:00 | 2353999.18 | 29-AUG-14:30 |
HeatingCoils:EnergyTransfer | 812.74 | 0.00 | 01-JAN-10:00 | 1222336.96 | 02-JAN-05:30 |
PlantLoopHeatingDemand:HVAC | 812.74 | 0.00 | 01-JAN-10:00 | 1222336.96 | 02-JAN-05:30 |
HeatingCoils:PlantLoopHeatingDemand | 812.74 | 0.00 | 01-JAN-10:00 | 1222336.96 | 02-JAN-05:30 |
CoolingCoils:EnergyTransfer | 5270.36 | 2078.00 | 03-JAN-08:00 | 2353999.18 | 29-AUG-14:30 |
EnergyTransfer:Plant | 9510.11 | 0.00 | 03-JAN-00:10 | 5856882.04 | 29-AUG-14:30 |
LoopToLoop:EnergyTransfer | 2616.20 | 0.00 | 01-JAN-00:10 | 1854293.90 | 29-AUG-14:30 |
WaterSystems:EnergyTransfer | 423.42 | 0.00 | 01-JAN-00:10 | 50361.36 | 13-FEB-12:20 |
WaterUse:WaterSystems:EnergyTransfer | 423.42 | 0.00 | 01-JAN-00:10 | 50361.36 | 13-FEB-12:20 |
Boilers:EnergyTransfer | 805.64 | 0.00 | 01-JAN-10:00 | 1350998.38 | 02-JAN-05:20 |
Chillers:EnergyTransfer | 2630.59 | 0.00 | 01-JAN-00:10 | 1858956.08 | 29-AUG-14:30 |
HeatRejection:EnergyTransfer | 3034.26 | 0.00 | 01-JAN-00:10 | 2118722.74 | 29-AUG-14:30 |
General:HeatRejection:EnergyTransfer | 3034.26 | 0.00 | 01-JAN-00:10 | 2118722.74 | 29-AUG-14:30 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 08:44:06
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
BASEMENT | 0.000 | 0.000 | 2.482 | -708.815 | 0.000 | 0.000 | 92.711 | 262.844 | 424.397 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -73.620 |
CORE_BOTTOM | 0.000 | 0.000 | 0.000 | -630.937 | 0.000 | 0.000 | 83.431 | 236.053 | 289.614 | 0.000 | 0.000 | 0.000 | 21.839 | 0.000 | 0.000 | 0.000 | 0.000 | -0.002 |
CORE_MID | 0.000 | 0.000 | 3.903 | -4400.610 | 0.000 | 0.000 | 845.669 | 2360.527 | 2896.128 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -1705.618 |
CORE_TOP | 0.000 | 0.000 | 5.323 | -386.260 | 0.000 | 0.000 | 87.278 | 236.053 | 289.613 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -232.006 |
PERIMETER_BOT_ZN_3 | 0.000 | 0.000 | 0.006 | -64.482 | 0.000 | 0.000 | 10.771 | 17.866 | 36.365 | 25.026 | 0.000 | 0.014 | 49.109 | 0.000 | -68.182 | 0.000 | -6.493 | 0.000 |
PERIMETER_BOT_ZN_2 | 0.000 | 0.000 | 0.019 | -64.681 | 0.000 | 0.000 | 7.097 | 11.367 | 23.435 | 50.425 | 0.000 | 0.010 | 18.549 | 0.000 | -42.034 | 0.000 | -4.186 | 0.000 |
PERIMETER_BOT_ZN_1 | 0.000 | 0.000 | 0.127 | -111.340 | 0.000 | 0.000 | 10.914 | 17.441 | 36.366 | 109.691 | 0.000 | 0.013 | 6.633 | 0.000 | -63.456 | 0.000 | -6.388 | 0.000 |
PERIMETER_BOT_ZN_4 | 0.000 | 0.000 | 0.001 | -96.791 | 0.000 | 0.000 | 6.888 | 11.348 | 23.435 | 53.247 | 0.000 | 0.008 | 55.585 | 0.000 | -48.984 | 0.000 | -4.735 | 0.000 |
PERIMETER_MID_ZN_3 | 0.000 | 0.000 | 44.757 | -412.184 | 0.000 | 0.000 | 113.683 | 178.139 | 363.654 | 263.622 | 0.000 | 0.377 | 177.608 | 0.000 | -597.593 | 0.000 | -132.063 | -0.019 |
PERIMETER_MID_ZN_2 | 0.000 | 0.000 | 30.269 | -512.215 | 0.000 | 0.000 | 54.258 | 113.434 | 234.352 | 508.358 | 0.000 | 0.220 | 42.673 | 0.000 | -382.959 | 0.000 | -88.390 | -0.008 |
PERIMETER_MID_ZN_1 | 0.000 | 0.000 | 30.867 | -948.059 | 0.000 | 0.000 | 112.193 | 174.194 | 363.660 | 1097.153 | 0.000 | 0.286 | 0.041 | 0.000 | -598.510 | 0.000 | -138.946 | -92.837 |
PERIMETER_MID_ZN_4 | 0.000 | 0.000 | 17.839 | -577.058 | 0.000 | 0.000 | 73.993 | 113.256 | 234.351 | 547.915 | 0.000 | 0.196 | 92.278 | 0.000 | -410.299 | 0.000 | -92.470 | -0.013 |
PERIMETER_TOP_ZN_3 | 0.000 | 0.000 | 15.299 | -35.931 | 0.000 | 0.000 | 11.584 | 17.811 | 36.365 | 27.079 | 0.000 | 0.042 | 0.000 | 0.000 | -55.593 | 0.000 | -15.281 | -1.376 |
PERIMETER_TOP_ZN_2 | 0.000 | 0.000 | 9.304 | -46.362 | 0.000 | 0.000 | 7.433 | 11.343 | 23.435 | 51.276 | 0.000 | 0.025 | 0.000 | 0.000 | -35.950 | 0.000 | -10.310 | -10.195 |
PERIMETER_TOP_ZN_1 | 0.000 | 0.000 | 10.866 | -85.835 | 0.000 | 0.000 | 11.407 | 17.418 | 36.366 | 110.491 | 0.000 | 0.033 | 0.000 | 0.000 | -56.073 | 0.000 | -16.138 | -28.536 |
PERIMETER_TOP_ZN_4 | 0.000 | 0.000 | 6.245 | -52.952 | 0.000 | 0.000 | 7.504 | 11.324 | 23.435 | 55.064 | 0.000 | 0.023 | 0.001 | 0.000 | -38.764 | 0.000 | -10.852 | -1.027 |
DATACENTER_BOT_ZN_6 | 0.000 | 0.000 | 0.000 | -139.106 | 0.000 | 0.000 | 0.950 | 6.628 | 153.881 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -22.353 |
DATACENTER_MID_ZN_6 | 0.000 | 0.000 | 2.998 | -1189.616 | 0.000 | 0.000 | 9.505 | 66.280 | 1538.806 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -427.972 |
DATACENTER_TOP_ZN_6 | 0.000 | 0.000 | 0.769 | -109.067 | 0.000 | 0.000 | 0.952 | 6.628 | 153.881 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -53.162 |
DATACENTER_BASEMENT_ZN_6 | 0.000 | 0.000 | 0.000 | -7182.967 | 0.000 | 0.000 | 20.504 | 74.111 | 7494.857 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -406.505 |
GROUNDFLOOR_PLENUM | 1.149 | -60.071 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.023 | 72.824 | 0.000 | 0.000 | 0.000 | -13.925 | 0.000 |
MIDFLOOR_PLENUM | 62.552 | -338.021 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.462 | 507.471 | 0.000 | 0.000 | 0.000 | -232.465 | -0.003 |
TOPFLOOR_PLENUM | 28.556 | -45.366 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.026 | 41.230 | 0.000 | 0.000 | 0.000 | -24.446 | -0.007 |
Total Facility | 92.257 | -443.458 | 181.073 | -17755.268 | 0.000 | 0.000 | 1568.724 | 3944.063 | 14676.396 | 2899.346 | 0.000 | 1.758 | 1085.841 | 0.000 | -2398.398 | 0.000 | -797.086 | -3055.257 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | 02-OCT-04:11 | 0.00 | 0.00 | 0.00 | -124206.40 | 0.00 | 0.00 | 0.00 | 2550.13 | 13457.54 | 0.00 | 0.00 | 0.00 | 108198.72 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 10-OCT-04:12 | 0.00 | 0.00 | 0.00 | -101603.64 | 0.00 | 0.00 | 0.00 | 2290.20 | 5937.65 | 0.00 | 0.00 | 0.00 | 93375.79 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 25-AUG-04:11 | 0.00 | 0.00 | 0.00 | -877380.83 | 0.00 | 0.00 | 0.00 | 22901.98 | 59376.23 | 0.00 | 0.00 | 0.00 | 795102.62 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 25-AUG-04:11 | 0.00 | 0.00 | 0.00 | -83869.68 | 0.00 | 0.00 | 0.00 | 2290.20 | 5937.62 | 0.00 | 0.00 | 0.00 | 75641.85 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 24-JUL-05:03 | 0.00 | 0.00 | 0.00 | -11524.84 | 0.00 | 0.00 | 113.47 | 136.82 | 960.25 | 2371.49 | 0.00 | 0.00 | 7949.22 | 0.00 | -0.00 | 0.00 | -6.40 | 0.00 |
PERIMETER_BOT_ZN_2 | 10-SEP-08:31 | 0.00 | 0.00 | 0.00 | -27182.34 | 0.00 | 0.00 | 20.29 | 44.08 | 464.11 | 19941.22 | 0.00 | 0.00 | 6800.18 | 0.00 | -0.00 | 0.00 | -87.55 | 0.00 |
PERIMETER_BOT_ZN_1 | 10-SEP-15:11 | 0.00 | 0.00 | 0.00 | -37075.23 | 0.00 | 0.00 | 33.32 | 68.40 | 720.19 | 16123.63 | 0.00 | 0.00 | 20263.79 | 0.00 | -0.00 | 0.00 | -134.11 | 0.00 |
PERIMETER_BOT_ZN_4 | 06-AUG-16:31 | 0.00 | 0.00 | 0.00 | -36526.98 | 0.00 | 0.00 | 12.88 | 44.08 | 464.11 | 23465.18 | 0.00 | 0.00 | 12704.45 | 0.00 | -0.00 | 0.00 | -163.72 | 0.00 |
PERIMETER_MID_ZN_3 | 24-JUL-15:00 | 0.00 | 0.00 | 0.00 | -92101.50 | 0.00 | 0.00 | 11143.81 | 12313.32 | 21605.52 | 70669.14 | 0.00 | 810.55 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -24440.84 |
PERIMETER_MID_ZN_2 | 30-JUL-08:41 | 0.00 | 0.00 | 0.00 | -302430.50 | 0.00 | 0.00 | 177.24 | 440.81 | 4641.14 | 207480.36 | 0.00 | 0.00 | 92336.98 | 0.00 | -0.00 | 0.00 | -2646.02 | 0.00 |
PERIMETER_MID_ZN_1 | 13-AUG-12:51 | 0.00 | 0.00 | 0.00 | -401577.25 | 0.00 | 0.00 | 301.55 | 684.04 | 7201.95 | 243432.18 | 0.00 | 0.00 | 151929.50 | 0.00 | -0.00 | 0.00 | -1971.96 | 0.00 |
PERIMETER_MID_ZN_4 | 23-JUL-17:11 | 0.00 | 0.00 | 0.00 | -338262.56 | 0.00 | 0.00 | 0.00 | 440.81 | 3603.49 | 226129.05 | 0.00 | 0.00 | 110798.23 | 0.00 | -0.00 | 0.00 | -2709.02 | 0.00 |
PERIMETER_TOP_ZN_3 | 24-JUL-15:00 | 0.00 | 0.00 | 0.00 | -10164.62 | 0.00 | 0.00 | 1114.38 | 1231.33 | 2160.55 | 7003.25 | 0.00 | 98.95 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -1443.84 |
PERIMETER_TOP_ZN_2 | 23-JUL-08:41 | 0.00 | 0.00 | 0.00 | -29231.67 | 0.00 | 0.00 | 18.67 | 44.08 | 464.11 | 20044.06 | 0.00 | 0.00 | 9328.12 | 0.00 | -0.00 | 0.00 | -667.38 | 0.00 |
PERIMETER_TOP_ZN_1 | 10-SEP-15:01 | 0.00 | 0.00 | 0.00 | -42131.40 | 0.00 | 0.00 | 29.34 | 68.40 | 720.19 | 17306.54 | 0.00 | 0.00 | 24471.17 | 0.00 | -0.00 | 0.00 | -464.26 | 0.00 |
PERIMETER_TOP_ZN_4 | 23-JUL-17:21 | 0.00 | 0.00 | 0.00 | -35116.39 | 0.00 | 0.00 | 0.00 | 44.08 | 360.35 | 22035.63 | 0.00 | 0.00 | 13016.51 | 0.00 | -0.00 | 0.00 | -340.17 | 0.00 |
DATACENTER_BOT_ZN_6 | 06-AUG-18:43 | 0.00 | 0.00 | 0.00 | -8852.88 | 0.00 | 0.00 | 0.00 | 32.15 | 7794.42 | 0.00 | 0.00 | 0.00 | 1026.30 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 06-AUG-18:32 | 0.00 | 0.00 | 0.00 | -82950.23 | 0.00 | 0.00 | 0.00 | 321.53 | 77944.22 | 0.00 | 0.00 | 0.00 | 4684.48 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 06-AUG-18:23 | 0.00 | 0.00 | 0.00 | -8401.66 | 0.00 | 0.00 | 0.00 | 32.15 | 7794.42 | 0.00 | 0.00 | 0.00 | 575.08 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 10-AUG-21:02 | 0.00 | 0.00 | 0.00 | -371121.10 | 0.00 | 0.00 | 114.06 | 719.03 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -9344.52 |
GROUNDFLOOR_PLENUM | 14-AUG-15:00 | 0.00 | -9348.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.88 | 9321.06 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 14-JAN-05:11 | 0.00 | -93490.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 121376.97 | 0.00 | -0.00 | 0.00 | -27886.08 | 0.00 |
TOPFLOOR_PLENUM | 10-AUG-14:20 | 0.00 | -20091.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 58.20 | 20033.55 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 25-AUG-04:11 | 0.00 | 67595.13 | 0.00 | -1881977.87 | 0.00 | 0.00 | 0.00 | 42872.09 | 587299.42 | 0.00 | 0.00 | 0.00 | 1295481.94 | 0.00 | -87064.52 | 0.00 | -24206.19 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | 09-OCT-16:23 | 0.00 | 0.00 | 14691.02 | 0.00 | 0.00 | 0.00 | 416.69 | 1274.92 | 13457.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -29840.18 |
CORE_BOTTOM | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 02-JAN-05:11 | 0.00 | 0.00 | 442033.42 | 0.00 | 0.00 | 0.00 | 0.00 | 22901.98 | 59376.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -524311.63 |
CORE_TOP | 17-JAN-04:51 | 0.00 | 0.00 | 79331.63 | 0.00 | 0.00 | 0.00 | 0.00 | 1144.97 | 5937.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -86414.23 |
PERIMETER_BOT_ZN_3 | 17-JAN-06:03 | 0.00 | 0.00 | 9210.37 | 0.00 | 0.00 | 0.00 | 145.06 | 287.56 | 960.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -4477.03 | 0.00 | -92.08 | -6034.12 |
PERIMETER_BOT_ZN_2 | 17-JAN-06:03 | 0.00 | 0.00 | 6793.05 | 0.00 | 0.00 | 0.00 | 94.15 | 185.31 | 618.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3015.86 | 0.00 | -60.96 | -4614.51 |
PERIMETER_BOT_ZN_1 | 17-JAN-05:01 | 0.00 | 0.00 | 13315.79 | 0.00 | 0.00 | 0.00 | 0.00 | 287.56 | 745.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -4043.40 | 0.00 | -302.29 | -10003.23 |
PERIMETER_BOT_ZN_4 | 17-JAN-06:03 | 0.00 | 0.00 | 4026.15 | 0.00 | 0.00 | 0.00 | 93.27 | 185.31 | 618.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3039.90 | 0.00 | -61.26 | -1822.39 |
PERIMETER_MID_ZN_3 | 02-JAN-05:11 | 0.00 | 0.00 | 128559.95 | 0.00 | 0.00 | 0.00 | 0.00 | 2875.57 | 7455.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -22028.24 | 0.00 | -9906.99 | -106955.90 |
PERIMETER_MID_ZN_2 | 02-JAN-05:11 | 0.00 | 0.00 | 170150.78 | 0.00 | 0.00 | 0.00 | 0.00 | 1853.13 | 4804.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -14646.56 | 0.00 | -6866.47 | -155295.56 |
PERIMETER_MID_ZN_1 | 02-JAN-05:11 | 0.00 | 0.00 | 246963.73 | 0.00 | 0.00 | 0.00 | 0.00 | 2875.64 | 7455.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -22710.38 | 0.00 | -10256.25 | -224328.46 |
PERIMETER_MID_ZN_4 | 02-JAN-05:11 | 0.00 | 0.00 | 166296.68 | 0.00 | 0.00 | 0.00 | 0.00 | 1853.13 | 4804.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -15683.14 | 0.00 | -6891.00 | -150380.32 |
PERIMETER_TOP_ZN_3 | 19-FEB-07:23 | 0.00 | 0.00 | 14890.94 | 0.00 | 0.00 | 0.00 | 89.32 | 143.76 | 720.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -4439.56 | 0.00 | -2333.43 | -9071.22 |
PERIMETER_TOP_ZN_2 | 21-FEB-04:51 | 0.00 | 0.00 | 19770.98 | 0.00 | 0.00 | 0.00 | 0.00 | 92.65 | 480.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2166.19 | 0.00 | -660.27 | -17517.63 |
PERIMETER_TOP_ZN_1 | 02-JAN-05:11 | 0.00 | 0.00 | 29276.74 | 0.00 | 0.00 | 0.00 | 0.00 | 287.56 | 745.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2146.30 | 0.00 | -1234.00 | -26929.57 |
PERIMETER_TOP_ZN_4 | 02-JAN-05:11 | 0.00 | 0.00 | 19937.56 | 0.00 | 0.00 | 0.00 | 0.00 | 185.31 | 480.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1494.24 | 0.00 | -841.24 | -18267.86 |
DATACENTER_BOT_ZN_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 03-JAN-01:00 | 0.00 | 0.00 | 5809.87 | 0.00 | 0.00 | 0.00 | 0.00 | 321.53 | 19486.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -25617.45 |
DATACENTER_TOP_ZN_6 | 08-JAN-17:25 | 0.00 | 0.00 | 648.74 | 0.00 | 0.00 | 0.00 | 5.64 | 32.15 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -2635.13 |
DATACENTER_BASEMENT_ZN_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 28-DEC-05:11 | 13203.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -1694.16 | -11509.57 |
MIDFLOOR_PLENUM | 02-JAN-06:03 | 168635.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -4919.84 | -163715.20 |
TOPFLOOR_PLENUM | 17-JAN-05:22 | 27097.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -1119.73 | -25977.87 |
Total Facility | 02-JAN-05:11 | -278730.68 | 311461.49 | 1330346.93 | -311461.49 | 0.00 | 0.00 | 0.00 | 42872.09 | 232425.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -94437.38 | 0.00 | -58737.86 | -1173738.32 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 08:44:06
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
VAV_BOT WITH REHEAT | 12.3355 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 10.2906 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_MID WITH REHEAT | 119.2228 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 95.1337 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_TOP WITH REHEAT | 11.9701 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 10.6016 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
CAV_BAS | 6.0667 | 0.0000 | 149.6021 | 1.0000 | Calculated from schedules | 1.2002 | 6.0667 | 0.1978 | 1.0000 | Not calculated | 1.2002 | 0.1978 | ||
AIRLOOP DATACENTER BASEMENT | 21.7161 | 0.0000 | 42.1814 | 1.0000 | Calculated from schedules | 0.3384 | 21.7161 | 0.0156 | 1.0000 | Not calculated | 0.3384 | 0.0156 | ||
AIRLOOP DATACENTER BOT | 0.5289 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.5289 | 0.0296 | 1.0000 | Not calculated | 0.0156 | 0.0296 | ||
AIRLOOP DATACENTER MID | 5.0877 | 0.0000 | 19.4861 | 1.0000 | Calculated from schedules | 0.1563 | 5.0877 | 0.0307 | 1.0000 | Not calculated | 0.1563 | 0.0307 | ||
AIRLOOP DATACENTER TOP | 0.5158 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.5158 | 0.0303 | 1.0000 | Not calculated | 0.0156 | 0.0303 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
VAV_BOT WITH REHEAT | 6.1678 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 3.2421 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_MID WITH REHEAT | 59.6114 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 31.9538 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_TOP WITH REHEAT | 5.9851 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 3.2921 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
CAV_BAS | 6.0667 | 0.0000 | 149.6021 | 1.0000 | Calculated from schedules | 1.2002 | 6.0667 | 1.0000 | 1.0000 | Not calculated | 1.2002 | 0.1978 | ||
AIRLOOP DATACENTER BASEMENT | 21.7161 | 0.0000 | 42.1814 | 1.0000 | Calculated from schedules | 0.3384 | 21.7161 | 1.0000 | 1.0000 | Not calculated | 0.3384 | 0.0156 | ||
AIRLOOP DATACENTER BOT | 0.5289 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.5289 | 1.0000 | 1.0000 | Not calculated | 0.0156 | 0.0296 | ||
AIRLOOP DATACENTER MID | 5.0877 | 0.0000 | 19.4861 | 1.0000 | Calculated from schedules | 0.1563 | 5.0877 | 1.0000 | 1.0000 | Not calculated | 0.1563 | 0.0307 | ||
AIRLOOP DATACENTER TOP | 0.5158 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.5158 | 1.0000 | 1.0000 | Not calculated | 0.0156 | 0.0303 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
BASEMENT | CAV_BAS | 0.000000 | 149.6021 | 0.000432 | 2779.43 | 1.2002 | 1.0000 | 1.2002 | 1.000 | 1.2002 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | 0.000000 | 134.3532 | 0.000432 | 2496.12 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_MID | VAV_MID WITH REHEAT | 0.000000 | 1343.5320 | 0.000432 | 24961.20 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_TOP | VAV_TOP WITH REHEAT | 0.000000 | 134.3532 | 0.000432 | 2496.12 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | 0.000000 | 16.8694 | 0.000432 | 313.41 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | 0.000000 | 16.8698 | 0.000432 | 313.42 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | 0.000000 | 168.6939 | 0.000432 | 3134.13 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | 0.000000 | 108.7127 | 0.000432 | 2019.75 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | 0.000000 | 168.6975 | 0.000432 | 3134.20 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | 0.000000 | 108.7127 | 0.000432 | 2019.75 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | 0.000000 | 16.8694 | 0.000432 | 313.41 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | 0.000000 | 16.8698 | 0.000432 | 313.42 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | 0.000000 | 1.9486 | 0.000432 | 36.20 | 0.0156 | 1.0000 | 0.0156 | 1.000 | 0.0156 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | 0.000000 | 19.4861 | 0.000432 | 362.03 | 0.1563 | 1.0000 | 0.1563 | 1.000 | 0.1563 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | 0.000000 | 1.9486 | 0.000432 | 36.20 | 0.0156 | 1.0000 | 0.0156 | 1.000 | 0.0156 |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | 0.000000 | 42.1814 | 0.000432 | 783.68 | 0.3384 | 1.0000 | 0.3384 | 1.000 | 0.3384 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
VAV_BOT WITH REHEAT | 0.00 | 0.000432 | 3526.9033 | 0.0000 | 0.0000 | 0.0000 | |
VAV_MID WITH REHEAT | 0.00 | 0.000432 | 35269.0328 | 0.0000 | 0.0000 | 0.0000 | |
VAV_TOP WITH REHEAT | 0.00 | 0.000432 | 3526.9033 | 0.0000 | 0.0000 | 0.0000 | |
CAV_BAS | 0.000000 | 149.60 | 0.000432 | 2779.4266 | 1.2002 | 1.2002 | 1.2002 |
AIRLOOP DATACENTER BASEMENT | 0.000000 | 42.18 | 0.000432 | 783.6794 | 0.3384 | 0.3384 | 0.3384 |
AIRLOOP DATACENTER BOT | 0.000000 | 1.95 | 0.000432 | 36.2027 | 0.0156 | 0.0156 | 0.0156 |
AIRLOOP DATACENTER MID | 0.000000 | 19.49 | 0.000432 | 362.0274 | 0.1563 | 0.1563 | 0.1563 |
AIRLOOP DATACENTER TOP | 0.000000 | 1.95 | 0.000432 | 36.2027 | 0.0156 | 0.0156 | 0.0156 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | CAV_BAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 6.0667 | 6.0667 | 6.0667 | No | 1.2002 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 6.2501 | 6.2501 | 1.9688 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 58.7664 | 58.7664 | 19.2166 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 5.6776 | 5.6776 | 1.9815 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.9537 | 0.9537 | 0.2470 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.4347 | 1.4347 | 0.2869 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.9938 | 1.9938 | 0.3988 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.7032 | 1.7032 | 0.3406 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 8.8485 | 8.8485 | 2.4156 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 14.9939 | 14.9939 | 2.9988 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 20.7592 | 20.7592 | 4.1518 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 15.8548 | 15.8548 | 3.1710 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.9825 | 0.9825 | 0.2486 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.4871 | 1.4871 | 0.2974 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.1730 | 2.1730 | 0.4346 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.6498 | 1.6498 | 0.3300 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.5289 | 0.5289 | 0.5289 | No | 0.0156 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 5.0877 | 5.0877 | 5.0877 | No | 0.1563 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.5158 | 0.5158 | 0.5158 | No | 0.0156 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 21.7161 | 21.7161 | 21.7161 | No | 0.3384 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
VAV_BOT WITH REHEAT | 12.3355 | 10.2906 | 12.3355 | 3.2421 | 0.0000 | 1.0000 |
VAV_MID WITH REHEAT | 119.2228 | 95.1337 | 119.2228 | 31.9538 | 0.0000 | 1.0000 |
VAV_TOP WITH REHEAT | 11.9701 | 10.6016 | 11.9701 | 3.2921 | 0.0000 | 1.0000 |
CAV_BAS | 6.0667 | 6.0667 | 6.0667 | 6.0667 | 1.2002 | 1.0000 |
AIRLOOP DATACENTER BASEMENT | 21.7161 | 21.7161 | 21.7161 | 21.7161 | 0.3384 | 1.0000 |
AIRLOOP DATACENTER BOT | 0.5289 | 0.5289 | 0.5289 | 0.5289 | 0.0156 | 1.0000 |
AIRLOOP DATACENTER MID | 5.0877 | 5.0877 | 5.0877 | 5.0877 | 0.1563 | 1.0000 |
AIRLOOP DATACENTER TOP | 0.5158 | 0.5158 | 0.5158 | 0.5158 | 0.0156 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | CAV_BAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 6.0667 | 6.0667 | 6.0667 | No | 1.2002 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 3.1250 | 3.1250 | 1.9688 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 29.3832 | 29.3832 | 19.2166 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.8388 | 2.8388 | 1.9815 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4769 | 0.4769 | 0.2470 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7174 | 0.7174 | 0.2869 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.9969 | 0.9969 | 0.3988 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8516 | 0.8516 | 0.3406 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 4.4243 | 4.4243 | 2.4156 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 7.4969 | 7.4969 | 2.9988 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 10.3796 | 10.3796 | 4.1518 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 7.9274 | 7.9274 | 3.1710 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4913 | 0.4913 | 0.2486 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7435 | 0.7435 | 0.2974 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.0865 | 1.0865 | 0.4346 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8249 | 0.8249 | 0.3300 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.5289 | 0.5289 | 0.5289 | No | 0.0156 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 5.0877 | 5.0877 | 5.0877 | No | 0.1563 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.5158 | 0.5158 | 0.5158 | No | 0.0156 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 21.7161 | 21.7161 | 21.7161 | No | 0.3384 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
VAV_BOT WITH REHEAT | 6.1678 | 3.2421 | 3.2421 | 3.2421 | 0.0000 | 1.0000 |
VAV_MID WITH REHEAT | 59.6114 | 31.9538 | 31.9538 | 31.9538 | 0.0000 | 1.0000 |
VAV_TOP WITH REHEAT | 5.9851 | 3.2921 | 3.2921 | 3.2921 | 0.0000 | 1.0000 |
CAV_BAS | 6.0667 | 6.0667 | 6.0667 | 6.0667 | 1.2002 | 1.0000 |
AIRLOOP DATACENTER BASEMENT | 21.7161 | 21.7161 | 21.7161 | 21.7161 | 0.3384 | 1.0000 |
AIRLOOP DATACENTER BOT | 0.5289 | 0.5289 | 0.5289 | 0.5289 | 0.0156 | 1.0000 |
AIRLOOP DATACENTER MID | 5.0877 | 5.0877 | 5.0877 | 5.0877 | 0.1563 | 1.0000 |
AIRLOOP DATACENTER TOP | 0.5158 | 0.5158 | 0.5158 | 0.5158 | 0.0156 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 08:44:06
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Seattle Seattle Tacoma Intl A WA USA TMY3 WMO#=727930 |
Total gross floor area [m2] | 46320.38 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
BASEMENT | 2779.43 | 2779.43 | 0.00 | 113.98 |
CORE_BOTTOM | 2496.12 | 2496.12 | 0.00 | 113.98 |
CORE_MID | 2496.12 | 2496.12 | 0.00 | 113.98 |
CORE_TOP | 2496.12 | 2496.12 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_3 | 313.41 | 313.41 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_2 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_1 | 313.42 | 313.42 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_4 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_MID_ZN_3 | 313.41 | 313.41 | 0.00 | 113.98 |
PERIMETER_MID_ZN_2 | 201.98 | 201.98 | 0.00 | 96.54 |
PERIMETER_MID_ZN_1 | 313.42 | 313.42 | 0.00 | 113.98 |
PERIMETER_MID_ZN_4 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_3 | 313.41 | 313.41 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_2 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_1 | 313.42 | 313.42 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_4 | 201.98 | 201.98 | 0.00 | 113.98 |
DATACENTER_BOT_ZN_6 | 36.20 | 36.20 | 0.00 | 113.98 |
DATACENTER_MID_ZN_6 | 36.20 | 36.20 | 0.00 | 113.98 |
DATACENTER_TOP_ZN_6 | 36.20 | 36.20 | 0.00 | 113.98 |
DATACENTER_BASEMENT_ZN_6 | 783.68 | 783.68 | 0.00 | 113.98 |
GROUNDFLOOR_PLENUM | 3563.11 | 3563.11 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 3563.11 | 3563.11 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 3563.11 | 3563.11 | 0.00 | 0.00 |
Totals | 46320.38 | 46320.38 | 0.00 |
Data | |
Number of hours heating loads not met | 15.67 |
Number of hours cooling loads not met | 182.00 |
Number of hours not met | 197.50 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler | 0.00 | 0.00 | 1110.48 | 1635223.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 1136.32 | 433009.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 3944.06 | 385834.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 698.76 | 57580.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 5334.97 | 305206.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- DataCenterPlugLoads | 9341.42 | 473165.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Transformer | 80.19 | 5057.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLift | 1848.78 | 113101.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLightsFan | 5.83 | 376.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 2326.84 | 284421.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 274.32 | 47863.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- General | 413.76 | 82535.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- General | 1029.99 | 100000.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 0.00 | 0.00 | 798.65 | 83859.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 14676.40 | 26435.25 |
Natural Gas | 0.00 | 1909.12 |
Additional | 0.00 | 0.00 |
Total | 14676.40 | 28344.37 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 85.15 |
Space Heating | 0.00 |
Space Cooling | 24.53 |
Fans (All) | 50.23 |
Service Water Heating | 0.00 |
Receptacle Equipment | 316.85 |
Miscellaneous (All) | 570.70 |
Subtotal | 570.70 |
Natural Gas [MJ/m2] | |
Space Heating | 23.97 |
Service Water Heating | 17.24 |
Miscellaneous (All) | 41.22 |
Subtotal | 41.22 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 13.91 |
Space Heating | 3.92 |
Space Cooling | 4.01 |
Fans (All) | 8.21 |
Service Water Heating | 2.82 |
Receptacle Equipment | 51.78 |
Miscellaneous | 15.35 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 4472. | 4472. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 6752. | 8760. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 6828. | 8760. |
ALWAYS_OFF | 0. | 0. |
LTG_SCH_OFFICE | 2625. | 8760. |
LTG_SCH_DATACENTER | 2921. | 8760. |
EXTERIOR_LIGHT_SCH | 4380. | 4380. |
BLDG_EQUIP_SCH | 4049. | 8760. |
DATACENTER_EQUIP_SCH | 5478. | 8760. |
BLDG_OCC_SCH | 2528. | 5992. |
BLDG_OCC_SCH_W_SB | 1878. | 5056. |
BLDG_OCC_SCH_WO_SB | 2557. | 5992. |
BLDG_ELEVATORS | 2270. | 8760. |
ELEV_LIGHT_FAN_SCH_24_7 | 8760. | 8760. |
ELEV_LIGHT_FAN_SCH_ADD_DF | 2154. | 8760. |
BLDG_SWH_SCH | 1474. | 6570. |
WORK_EFF_SCH | 0. | 0. |
INFIL_SCH | 3976. | 3976. |
INFIL_SCH_PNNL | 5172. | 8760. |
INFIL_HALF_ON_SCH | 6368. | 8760. |
FAN_SCH | 8760. | 8760. |
REHEATCOILAVAILSCHED | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
MINOA_MOTORIZEDDAMPER_SCHED | 4472. | 4472. |
MINOA_SCHED | 8760. | 8760. |
CORE_BOTTOM SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_BOTTOM SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_MID SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_MID SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_TOP SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_TOP SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
SUPPLYFANSCH | 8760. | 8760. |
PERIMETER_MID_ZN_2_MDP_SCH | 1565. | 7824. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
HTGSETP_DC_SCH | DATACENTER COOLING SETPOINTS DUAL SP CONTROL | January | 18.00 | 365 | 18.00 | 365 |
CLGSETP_DC_SCH | DATACENTER COOLING SETPOINTS DUAL SP CONTROL | July | 27.00 | 365 | 27.00 | 365 |
HTGSETP_SCH_YES_OPTIMUM | CORE_BOTTOM DUAL SP CONTROL | January | 21.00 | 365 | 15.60 | 365 |
CLGSETP_SCH_YES_OPTIMUM | CORE_BOTTOM DUAL SP CONTROL | July | 24.00 | 365 | 26.70 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:44:06
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
BASEMENT | 8487.50 | 272.50 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 8721.33 | 38.67 | 0.00 | 0.00 | 0.00 |
CORE_MID | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 8759.50 | 0.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 8741.17 | 18.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 8732.33 | 27.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 8526.33 | 233.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 8738.67 | 21.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 8729.33 | 30.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 8711.33 | 48.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 8740.33 | 19.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 8732.83 | 27.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 8714.67 | 45.33 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 7805.17 | 954.83 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 7759.17 | 1000.83 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 7741.33 | 1018.67 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 7488.50 | 1271.50 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 8744.67 | 15.33 | 0.00 | 0.00 | 0.00 |
Min | 7488.50 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 1271.50 | 0.00 | 0.00 | 0.00 |
Average | 8540.62 | 219.38 | 0.00 | 0.00 | 0.00 |
Sum | 196434.17 | 5045.83 | 0.00 | 0.00 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
BASEMENT | 367813.33 | 802.67 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 330749.00 | 64.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 330813.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 330813.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 18354.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 1710.83 | 557.17 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 1673.67 | 594.33 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 1662.83 | 605.17 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 87639.67 | 15755.33 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 367813.33 | 15755.33 | 0.00 | 0.00 | 0.00 |
Average | 79535.84 | 799.07 | 0.00 | 0.00 | 0.00 |
Sum | 1829324.33 | 18378.67 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
BASEMENT | 8297.67 | 462.33 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 8498.33 | 261.67 | 0.00 | 0.00 | 0.00 |
CORE_MID | 8604.33 | 155.67 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 8672.33 | 87.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 8744.83 | 15.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 8736.33 | 23.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 8720.33 | 39.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 8499.33 | 260.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 8757.83 | 2.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 8738.17 | 21.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 8712.50 | 47.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 8670.67 | 89.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 8755.33 | 4.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 8738.00 | 22.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 8722.83 | 37.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 8686.33 | 73.67 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 8456.00 | 304.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 8432.17 | 327.83 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 8425.00 | 335.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 7913.17 | 846.83 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 8726.83 | 33.17 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 8759.50 | 0.50 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 8696.50 | 63.50 | 0.00 | 0.00 | 0.00 |
Min | 7913.17 | 0.50 | 0.00 | 0.00 | 0.00 |
Max | 8759.50 | 846.83 | 0.00 | 0.00 | 0.00 |
Average | 8607.14 | 152.86 | 0.00 | 0.00 | 0.00 |
Sum | 197964.33 | 3515.67 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
BASEMENT | 367540.33 | 1075.67 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 330411.33 | 401.67 | 0.00 | 0.00 | 0.00 |
CORE_MID | 330533.00 | 280.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 330648.00 | 165.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 18354.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 2061.50 | 206.50 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 2042.17 | 225.83 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 2037.67 | 230.33 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 92240.67 | 11154.33 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 367540.33 | 11154.33 | 0.00 | 0.00 | 0.00 |
Average | 79737.55 | 597.36 | 0.00 | 0.00 | 0.00 |
Sum | 1833963.67 | 13739.33 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:44:06
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:44:06
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 0.00 | 8760.00 | 0.00 |
Average | 0.00 | 0.00 | 4570.43 | 0.00 |
Sum | 0.00 | 0.00 | 105120.00 | 0.00 |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 18354.00 | 0.00 |
PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 24909.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 0.00 | 38925.00 | 0.00 |
Average | 0.00 | 0.00 | 16367.35 | 0.00 |
Sum | 0.00 | 0.00 | 376449.00 | 0.00 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.496 |
February | 5.822 |
March | 8.326 |
April | 10.851 |
May | 12.973 |
June | 15.587 |
July | 17.665 |
August | 18.800 |
September | 15.086 |
October | 11.426 |
November | 8.070 |
December | 5.416 |
Annual Sum or Average | 11.241 |
Minimum of Months | 4.496 |
Maximum of Months | 18.800 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Environment
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.496 |
February | 5.822 |
March | 8.326 |
April | 10.851 |
May | 12.973 |
June | 15.587 |
July | 17.665 |
August | 18.800 |
September | 15.086 |
October | 11.426 |
November | 8.070 |
December | 5.416 |
Annual Sum or Average | 11.241 |
Minimum of Months | 4.496 |
Maximum of Months | 18.800 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2013
For: Environment
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.496 |
February | 5.822 |
March | 8.326 |
April | 10.851 |
May | 12.973 |
June | 15.587 |
July | 17.665 |
August | 18.800 |
September | 15.086 |
October | 11.426 |
November | 8.070 |
December | 5.416 |
Annual Sum or Average | 11.241 |
Minimum of Months | 4.496 |
Maximum of Months | 18.800 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.496 |
February | 5.822 |
March | 8.326 |
April | 10.851 |
May | 12.973 |
June | 15.587 |
July | 17.665 |
August | 18.800 |
September | 15.086 |
October | 11.426 |
November | 8.070 |
December | 5.416 |
Annual Sum or Average | 11.241 |
Minimum of Months | 4.496 |
Maximum of Months | 18.800 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICELARGE
For: Environment
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.496 |
February | 5.822 |
March | 8.326 |
April | 10.851 |
May | 12.973 |
June | 15.587 |
July | 17.665 |
August | 18.800 |
September | 15.086 |
October | 11.426 |
November | 8.070 |
December | 5.416 |
Annual Sum or Average | 11.241 |
Minimum of Months | 4.496 |
Maximum of Months | 18.800 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.496 |
February | 5.822 |
March | 8.326 |
April | 10.851 |
May | 12.973 |
June | 15.587 |
July | 17.665 |
August | 18.800 |
September | 15.086 |
October | 11.426 |
November | 8.070 |
December | 5.416 |
Annual Sum or Average | 11.241 |
Minimum of Months | 4.496 |
Maximum of Months | 18.800 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.496 |
February | 5.822 |
March | 8.326 |
April | 10.851 |
May | 12.973 |
June | 15.587 |
July | 17.665 |
August | 18.800 |
September | 15.086 |
October | 11.426 |
November | 8.070 |
December | 5.416 |
Annual Sum or Average | 11.241 |
Minimum of Months | 4.496 |
Maximum of Months | 18.800 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 4C
For: Environment
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.496 |
February | 5.822 |
March | 8.326 |
April | 10.851 |
May | 12.973 |
June | 15.587 |
July | 17.665 |
August | 18.800 |
September | 15.086 |
October | 11.426 |
November | 8.070 |
December | 5.416 |
Annual Sum or Average | 11.241 |
Minimum of Months | 4.496 |
Maximum of Months | 18.800 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_WA_SEATTLE
For: Environment
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.496 |
February | 5.822 |
March | 8.326 |
April | 10.851 |
May | 12.973 |
June | 15.587 |
July | 17.665 |
August | 18.800 |
September | 15.086 |
October | 11.426 |
November | 8.070 |
December | 5.416 |
Annual Sum or Average | 11.241 |
Minimum of Months | 4.496 |
Maximum of Months | 18.800 |
Report: ZoneCoolingSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.493910E+11 | 122538.05 | 02-JAN-05:11 | 6.10 | 5.29 | 0.566047E+10 | 7499.16 | 05-JAN-10:20 | 2.60 | 2.43 |
February | 0.476925E+11 | 119151.00 | 27-FEB-05:11 | 6.50 | 5.53 | 0.513546E+10 | 7499.16 | 08-FEB-10:09 | 6.50 | 5.53 |
March | 0.606704E+11 | 120381.56 | 27-MAR-04:11 | 4.80 | 3.63 | 0.613237E+10 | 7499.09 | 09-MAR-14:20 | 4.80 | 3.63 |
April | 0.583022E+11 | 120501.88 | 17-APR-04:12 | 6.10 | 5.14 | 0.545038E+10 | 7499.10 | 20-APR-09:39 | 9.80 | 7.10 |
May | 0.605417E+11 | 120432.90 | 01-MAY-04:12 | 12.20 | 10.35 | 0.590139E+10 | 7499.15 | 05-MAY-09:20 | 16.33 | 13.64 |
June | 0.631440E+11 | 123929.65 | 26-JUN-04:11 | 12.80 | 10.62 | 0.588258E+10 | 7499.17 | 09-JUN-13:20 | 12.80 | 10.62 |
July | 0.637910E+11 | 117666.48 | 03-JUL-04:12 | 11.30 | 8.24 | 0.547434E+10 | 7499.13 | 11-JUL-09:20 | 16.13 | 15.49 |
August | 0.702980E+11 | 118273.60 | 07-AUG-04:11 | 12.53 | 11.52 | 0.613789E+10 | 7499.57 | 09-AUG-09:00 | 23.80 | 15.92 |
September | 0.607010E+11 | 116192.47 | 06-SEP-04:12 | 9.80 | 8.99 | 0.545197E+10 | 7499.21 | 22-SEP-09:09 | 14.37 | 14.11 |
October | 0.612495E+11 | 124229.65 | 02-OCT-04:11 | 9.40 | 8.23 | 0.566896E+10 | 7499.08 | 25-OCT-09:09 | 11.88 | 9.92 |
November | 0.578813E+11 | 121225.27 | 20-NOV-05:11 | 8.13 | 6.37 | 0.561304E+10 | 7499.07 | 10-NOV-10:09 | 8.13 | 6.37 |
December | 0.551534E+11 | 121267.87 | 26-DEC-04:01 | -1.0 | -1.0 | 0.546761E+10 | 7499.27 | 13-DEC-14:20 | -1.0 | -1.0 |
Annual Sum or Average | 0.708816E+12 | 0.679764E+11 | ||||||||
Minimum of Months | 0.476925E+11 | 116192.47 | -1.0 | -1.0 | 0.513546E+10 | 7499.07 | -1.0 | -1.0 | ||
Maximum of Months | 0.702980E+11 | 124229.65 | 12.80 | 11.52 | 0.613789E+10 | 7499.57 | 23.80 | 15.92 |
Report: ZoneCoolingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.374934E+11 | 91435.77 | 02-JAN-05:11 | 6.10 | 5.29 | 0.504903E+10 | 6734.78 | 20-JAN-10:09 | 4.18 | 2.79 |
February | 0.390448E+11 | 93135.42 | 27-FEB-05:11 | 6.50 | 5.53 | 0.459542E+10 | 6734.78 | 08-FEB-10:09 | 6.50 | 5.53 |
March | 0.534188E+11 | 96210.58 | 27-MAR-04:11 | 4.80 | 3.63 | 0.550119E+10 | 6734.75 | 09-MAR-14:09 | 4.80 | 3.63 |
April | 0.562954E+11 | 97730.00 | 17-APR-04:12 | 6.10 | 5.14 | 0.488427E+10 | 6734.77 | 20-APR-09:39 | 9.80 | 7.10 |
May | 0.542263E+11 | 99403.06 | 01-MAY-04:12 | 12.20 | 10.35 | 0.528706E+10 | 6734.85 | 05-MAY-09:09 | 15.97 | 13.48 |
June | 0.589187E+11 | 98657.69 | 12-JUN-04:12 | 14.80 | 13.61 | 0.527121E+10 | 6734.87 | 05-JUN-13:00 | 14.80 | 13.61 |
July | 0.635752E+11 | 100155.52 | 17-JUL-04:12 | 14.23 | 12.63 | 0.489823E+10 | 6734.80 | 28-JUL-13:00 | 20.00 | 15.26 |
August | 0.722170E+11 | 97940.90 | 21-AUG-04:12 | 11.47 | 11.08 | 0.549726E+10 | 6735.37 | 09-AUG-09:00 | 11.47 | 11.08 |
September | 0.518125E+11 | 100576.52 | 05-SEP-04:12 | 11.33 | 9.63 | 0.488495E+10 | 6734.83 | 14-SEP-09:09 | 17.38 | 15.51 |
October | 0.508043E+11 | 101604.98 | 10-OCT-04:12 | 12.20 | 11.04 | 0.507896E+10 | 6734.77 | 12-OCT-09:09 | 9.18 | 7.86 |
November | 0.472328E+11 | 99489.75 | 06-NOV-05:12 | 10.77 | 8.10 | 0.503008E+10 | 6734.74 | 13-NOV-10:00 | 2.80 | 2.80 |
December | 0.458996E+11 | 95448.88 | 04-DEC-05:11 | 3.70 | 1.47 | 0.489974E+10 | 6734.87 | 13-DEC-14:09 | 7.10 | 5.11 |
Annual Sum or Average | 0.630939E+12 | 0.608774E+11 | ||||||||
Minimum of Months | 0.374934E+11 | 91435.77 | 3.70 | 1.47 | 0.459542E+10 | 6734.74 | 2.80 | 2.79 | ||
Maximum of Months | 0.722170E+11 | 101604.98 | 14.80 | 13.61 | 0.550119E+10 | 6735.37 | 20.00 | 15.51 |
Report: ZoneCoolingSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.243667E+11 | 27912.33 | 12-JAN-17:00 | 7.20 | 5.41 | 0.467201E+10 | 6734.61 | 27-JAN-14:09 | 9.72 | 8.09 |
February | 0.257504E+11 | 61505.88 | 28-FEB-06:03 | 10.60 | 9.74 | 0.442617E+10 | 6734.78 | 08-FEB-10:09 | 10.60 | 9.74 |
March | 0.351457E+11 | 78575.06 | 03-MAR-06:02 | 6.60 | 6.18 | 0.542393E+10 | 6734.74 | 09-MAR-14:09 | 14.90 | 12.35 |
April | 0.359394E+11 | 84449.47 | 28-APR-04:12 | 11.50 | 10.06 | 0.484098E+10 | 6734.76 | 20-APR-09:39 | 11.50 | 10.06 |
May | 0.431771E+11 | 83805.78 | 01-MAY-04:12 | 12.20 | 10.35 | 0.526421E+10 | 6734.82 | 05-MAY-09:09 | 15.97 | 13.48 |
June | 0.457602E+11 | 85792.85 | 12-JUN-04:12 | 14.80 | 13.61 | 0.525841E+10 | 6734.84 | 09-JUN-13:09 | 14.80 | 13.61 |
July | 0.462992E+11 | 87030.51 | 25-JUL-04:12 | 13.90 | 13.04 | 0.488995E+10 | 6734.79 | 28-JUL-13:00 | 20.00 | 15.26 |
August | 0.506074E+11 | 87748.64 | 25-AUG-04:11 | 17.93 | 15.42 | 0.549159E+10 | 6735.26 | 09-AUG-09:00 | 17.93 | 15.42 |
September | 0.418019E+11 | 85693.67 | 14-SEP-04:12 | 13.53 | 12.71 | 0.486776E+10 | 6734.83 | 14-SEP-09:09 | 17.38 | 15.51 |
October | 0.355995E+11 | 83953.66 | 06-OCT-05:02 | 11.10 | 10.49 | 0.502432E+10 | 6734.78 | 12-OCT-09:09 | 9.18 | 7.86 |
November | 0.289483E+11 | 77390.43 | 07-NOV-06:02 | 12.12 | 9.85 | 0.490853E+10 | 6734.74 | 15-NOV-10:09 | 7.30 | 5.72 |
December | 0.266675E+11 | 30889.41 | 06-DEC-16:20 | 2.57 | 2.27 | 0.467367E+10 | 6734.73 | 05-DEC-10:20 | 2.57 | 2.27 |
Annual Sum or Average | 0.440063E+12 | 0.597415E+11 | ||||||||
Minimum of Months | 0.243667E+11 | 27912.33 | 2.57 | 2.27 | 0.442617E+10 | 6734.61 | 2.57 | 2.27 | ||
Maximum of Months | 0.506074E+11 | 87748.64 | 17.93 | 15.42 | 0.549159E+10 | 6735.26 | 20.00 | 15.51 |
Report: ZoneCoolingSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.197333E+11 | 19925.41 | 11-JAN-17:00 | 12.20 | 9.27 | 0.424590E+10 | 6537.69 | 12-JAN-14:00 | 7.20 | 5.88 |
February | 0.206907E+11 | 31655.08 | 28-FEB-17:00 | 14.40 | 10.82 | 0.401978E+10 | 6734.43 | 24-FEB-14:20 | 14.40 | 10.82 |
March | 0.281985E+11 | 34830.40 | 15-MAR-16:00 | 11.10 | 7.72 | 0.509826E+10 | 6734.66 | 09-MAR-14:09 | 11.10 | 7.72 |
April | 0.312776E+11 | 77883.00 | 28-APR-05:03 | 11.10 | 9.92 | 0.467805E+10 | 6734.72 | 27-APR-13:00 | 11.10 | 9.92 |
May | 0.393988E+11 | 78200.12 | 05-MAY-05:03 | 12.98 | 10.75 | 0.519428E+10 | 6734.80 | 05-MAY-09:09 | 15.97 | 13.48 |
June | 0.440289E+11 | 82546.48 | 12-JUN-04:12 | 14.80 | 13.61 | 0.523032E+10 | 6734.83 | 09-JUN-13:09 | 14.80 | 13.61 |
July | 0.459854E+11 | 82294.48 | 25-JUL-04:12 | 13.90 | 13.04 | 0.487184E+10 | 6734.81 | 11-JUL-09:09 | 13.90 | 13.04 |
August | 0.494721E+11 | 83879.00 | 25-AUG-04:11 | 17.93 | 15.42 | 0.547089E+10 | 6735.24 | 09-AUG-09:00 | 17.93 | 15.42 |
September | 0.369859E+11 | 78764.49 | 14-SEP-05:03 | 12.62 | 12.25 | 0.480326E+10 | 6734.80 | 22-SEP-09:09 | 14.37 | 14.11 |
October | 0.284290E+11 | 41735.69 | 04-OCT-15:50 | 21.20 | 11.42 | 0.479497E+10 | 6734.67 | 06-OCT-09:20 | 12.57 | 10.89 |
November | 0.221451E+11 | 28694.18 | 02-NOV-16:00 | 13.30 | 10.88 | 0.446661E+10 | 6734.58 | 06-NOV-14:00 | 11.10 | 10.22 |
December | 0.199182E+11 | 20024.96 | 06-DEC-17:00 | 1.10 | 0.98 | 0.415648E+10 | 6612.16 | 06-DEC-14:00 | 1.10 | 0.98 |
Annual Sum or Average | 0.386264E+12 | 0.570306E+11 | ||||||||
Minimum of Months | 0.197333E+11 | 19925.41 | 1.10 | 0.98 | 0.401978E+10 | 6537.69 | 1.10 | 0.98 | ||
Maximum of Months | 0.494721E+11 | 83879.00 | 21.20 | 15.42 | 0.547089E+10 | 6735.24 | 17.93 | 15.42 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.260185E+10 | 2754.66 | 11-JAN-06:02 | 9.90 | 7.47 | 0.550050E+09 | 831.04 | 11-JAN-14:39 | 14.40 | 10.49 |
February | 0.285853E+10 | 4871.74 | 27-FEB-15:30 | 19.70 | 12.30 | 0.524038E+09 | 845.61 | 27-FEB-14:09 | 19.70 | 12.30 |
March | 0.421075E+10 | 5454.27 | 10-MAR-14:30 | 16.40 | 11.76 | 0.665742E+09 | 845.63 | 09-MAR-14:09 | 16.40 | 11.76 |
April | 0.550709E+10 | 8130.28 | 27-APR-15:20 | 27.20 | 17.16 | 0.604168E+09 | 845.63 | 27-APR-13:20 | 27.20 | 17.16 |
May | 0.651652E+10 | 8118.96 | 15-MAY-13:50 | 23.22 | 13.56 | 0.657871E+09 | 845.64 | 15-MAY-13:09 | 23.22 | 13.56 |
June | 0.782570E+10 | 8869.51 | 21-JUN-13:40 | 22.77 | 15.04 | 0.660310E+09 | 845.64 | 09-JUN-13:09 | 22.77 | 15.04 |
July | 0.904977E+10 | 11524.60 | 24-JUL-05:03 | 15.87 | 13.15 | 0.614552E+09 | 845.64 | 28-JUL-13:50 | 20.55 | 15.38 |
August | 0.974544E+10 | 9840.14 | 25-AUG-14:00 | 27.40 | 18.74 | 0.689527E+09 | 845.78 | 25-AUG-13:50 | 27.40 | 18.74 |
September | 0.561489E+10 | 7408.96 | 12-SEP-14:30 | 24.40 | 16.63 | 0.607248E+09 | 845.63 | 14-SEP-09:09 | 17.38 | 15.51 |
October | 0.423049E+10 | 5539.08 | 04-OCT-14:40 | 21.50 | 11.47 | 0.620343E+09 | 845.62 | 12-OCT-09:39 | 10.03 | 8.14 |
November | 0.332736E+10 | 4588.76 | 06-NOV-11:40 | 13.70 | 9.94 | 0.596462E+09 | 845.62 | 06-NOV-14:09 | 11.60 | 10.16 |
December | 0.299360E+10 | 2962.60 | 04-DEC-05:12 | 3.70 | 1.47 | 0.558451E+09 | 845.61 | 04-DEC-14:30 | 8.90 | 5.55 |
Annual Sum or Average | 0.644820E+11 | 0.734876E+10 | ||||||||
Minimum of Months | 0.260185E+10 | 2754.66 | 3.70 | 1.47 | 0.524038E+09 | 831.04 | 8.90 | 5.55 | ||
Maximum of Months | 0.974544E+10 | 11524.60 | 27.40 | 18.74 | 0.689527E+09 | 845.78 | 27.40 | 18.74 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.242722E+10 | 3053.46 | 11-JAN-06:02 | 9.90 | 7.47 | 0.332297E+09 | 530.91 | 20-JAN-10:39 | 5.03 | 3.09 |
February | 0.282269E+10 | 5115.42 | 08-FEB-09:45 | 1.93 | 0.91 | 0.322190E+09 | 544.95 | 08-FEB-10:09 | 2.48 | 1.47 |
March | 0.434195E+10 | 10049.29 | 14-MAR-08:55 | 7.80 | 5.89 | 0.413405E+09 | 544.96 | 02-MAR-10:09 | 7.80 | 5.89 |
April | 0.585197E+10 | 13651.07 | 27-APR-08:30 | 16.95 | 12.18 | 0.383693E+09 | 544.96 | 20-APR-09:00 | 16.95 | 12.18 |
May | 0.664130E+10 | 26634.20 | 14-MAY-08:31 | 15.93 | 11.13 | 0.419002E+09 | 544.98 | 15-MAY-09:00 | 18.90 | 13.25 |
June | 0.801079E+10 | 27098.80 | 25-JUN-08:31 | 16.33 | 11.87 | 0.423178E+09 | 544.97 | 09-JUN-13:09 | 16.33 | 11.87 |
July | 0.860334E+10 | 25525.69 | 30-JUL-08:22 | 19.45 | 15.24 | 0.393797E+09 | 546.21 | 31-JUL-09:30 | 22.75 | 17.29 |
August | 0.944287E+10 | 26664.52 | 06-AUG-09:51 | 17.10 | 13.58 | 0.441524E+09 | 546.22 | 10-AUG-09:39 | 22.97 | 17.14 |
September | 0.613609E+10 | 27183.40 | 10-SEP-08:31 | 15.53 | 13.26 | 0.385712E+09 | 544.97 | 14-SEP-09:09 | 17.38 | 15.51 |
October | 0.447016E+10 | 11134.05 | 04-OCT-08:50 | 15.32 | 10.37 | 0.384554E+09 | 544.97 | 05-OCT-09:00 | 13.90 | 9.28 |
November | 0.318875E+10 | 4459.95 | 15-NOV-09:10 | 6.78 | 5.27 | 0.353206E+09 | 544.95 | 15-NOV-10:09 | 7.30 | 5.72 |
December | 0.274359E+10 | 3792.93 | 05-DEC-09:55 | 6.70 | 5.10 | 0.327110E+09 | 544.95 | 05-DEC-10:09 | 6.97 | 5.16 |
Annual Sum or Average | 0.646807E+11 | 0.457967E+10 | ||||||||
Minimum of Months | 0.242722E+10 | 3053.46 | 1.93 | 0.91 | 0.322190E+09 | 530.91 | 2.48 | 1.47 | ||
Maximum of Months | 0.944287E+10 | 27183.40 | 19.45 | 15.24 | 0.441524E+09 | 546.22 | 22.97 | 17.29 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.422563E+10 | 20288.24 | 08-JAN-13:43 | 4.90 | 2.68 | 0.537050E+09 | 845.65 | 11-JAN-14:09 | 14.40 | 10.49 |
February | 0.591219E+10 | 23551.13 | 12-FEB-13:23 | 6.40 | 1.13 | 0.518917E+09 | 846.63 | 27-FEB-14:50 | 19.72 | 12.05 |
March | 0.902167E+10 | 22223.77 | 01-MAR-13:30 | 11.15 | 5.98 | 0.647387E+09 | 846.78 | 01-MAR-14:50 | 13.03 | 7.20 |
April | 0.101456E+11 | 35511.32 | 02-APR-13:12 | 18.90 | 11.02 | 0.593564E+09 | 846.77 | 26-APR-13:00 | 23.90 | 13.95 |
May | 0.101041E+11 | 35512.12 | 14-MAY-12:32 | 21.83 | 12.33 | 0.647161E+09 | 845.67 | 15-MAY-13:09 | 22.88 | 13.76 |
June | 0.105874E+11 | 34000.57 | 11-JUN-12:52 | 21.70 | 15.29 | 0.654011E+09 | 845.68 | 28-JUN-13:39 | 24.80 | 15.68 |
July | 0.130571E+11 | 34189.84 | 30-JUL-13:02 | 26.20 | 17.74 | 0.611511E+09 | 846.87 | 31-JUL-13:00 | 28.30 | 18.92 |
August | 0.154467E+11 | 36979.93 | 06-AUG-13:11 | 22.00 | 15.46 | 0.686454E+09 | 848.12 | 29-AUG-13:30 | 29.30 | 20.07 |
September | 0.119764E+11 | 37073.12 | 10-SEP-15:11 | 22.60 | 14.37 | 0.600342E+09 | 847.46 | 15-SEP-13:50 | 21.70 | 16.50 |
October | 0.960950E+10 | 34839.20 | 29-OCT-12:52 | 11.10 | 7.72 | 0.604269E+09 | 846.85 | 02-OCT-13:39 | 11.10 | 7.72 |
November | 0.576662E+10 | 30464.68 | 11-NOV-11:32 | 4.43 | 3.68 | 0.568959E+09 | 845.64 | 13-NOV-14:30 | 6.70 | 4.24 |
December | 0.548833E+10 | 27487.24 | 03-DEC-12:13 | 11.87 | 6.24 | 0.536401E+09 | 845.66 | 05-DEC-14:00 | 10.00 | 7.01 |
Annual Sum or Average | 0.111341E+12 | 0.720603E+10 | ||||||||
Minimum of Months | 0.422563E+10 | 20288.24 | 4.43 | 1.13 | 0.518917E+09 | 845.64 | 6.70 | 4.24 | ||
Maximum of Months | 0.154467E+11 | 37073.12 | 26.20 | 17.74 | 0.686454E+09 | 848.12 | 29.30 | 20.07 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.363715E+10 | 5693.47 | 05-JAN-15:30 | 6.40 | 4.89 | 0.349617E+09 | 544.94 | 20-JAN-14:50 | 7.12 | 4.90 |
February | 0.438535E+10 | 12938.65 | 26-FEB-15:13 | 14.40 | 10.43 | 0.345039E+09 | 544.95 | 22-FEB-14:09 | 14.40 | 10.43 |
March | 0.688109E+10 | 16274.70 | 18-MAR-17:06 | 19.22 | 9.55 | 0.437248E+09 | 544.96 | 09-MAR-14:09 | 19.22 | 9.55 |
April | 0.943060E+10 | 28987.15 | 02-APR-13:52 | 18.90 | 11.31 | 0.394726E+09 | 544.96 | 27-APR-13:00 | 26.10 | 16.83 |
May | 0.886930E+10 | 34808.49 | 14-MAY-16:31 | 22.97 | 11.85 | 0.422987E+09 | 544.96 | 15-MAY-13:09 | 22.88 | 13.76 |
June | 0.103512E+11 | 31119.73 | 18-JUN-16:51 | 17.20 | 12.22 | 0.426436E+09 | 544.98 | 28-JUN-13:39 | 24.80 | 15.68 |
July | 0.138057E+11 | 32860.66 | 23-JUL-16:51 | 26.70 | 15.58 | 0.397638E+09 | 544.97 | 28-JUL-13:39 | 21.10 | 15.48 |
August | 0.150611E+11 | 36522.15 | 06-AUG-16:31 | 23.53 | 15.27 | 0.445916E+09 | 545.03 | 09-AUG-09:00 | 23.80 | 15.92 |
September | 0.813779E+10 | 33373.19 | 10-SEP-15:51 | 22.20 | 14.48 | 0.390828E+09 | 544.96 | 14-SEP-09:09 | 17.38 | 15.51 |
October | 0.627520E+10 | 18002.59 | 01-OCT-15:53 | 16.70 | 13.67 | 0.401483E+09 | 544.96 | 05-OCT-09:00 | 13.90 | 9.28 |
November | 0.499564E+10 | 10127.86 | 04-NOV-15:30 | 20.55 | 15.94 | 0.394352E+09 | 544.95 | 03-NOV-13:00 | 20.55 | 15.94 |
December | 0.496114E+10 | 8705.03 | 05-DEC-15:30 | 8.05 | 5.82 | 0.382928E+09 | 544.97 | 13-DEC-14:09 | 7.10 | 5.11 |
Annual Sum or Average | 0.967913E+11 | 0.478920E+10 | ||||||||
Minimum of Months | 0.363715E+10 | 5693.47 | 6.40 | 4.89 | 0.345039E+09 | 544.94 | 7.10 | 4.90 | ||
Maximum of Months | 0.150611E+11 | 36522.15 | 26.70 | 15.94 | 0.445916E+09 | 545.03 | 26.10 | 16.83 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.752984E+09 | 1980.28 | 11-JAN-16:20 | 13.67 | 10.10 | 0.472020E+09 | 714.02 | 11-JAN-14:00 | 13.67 | 10.10 |
February | 0.126347E+10 | 2399.54 | 28-FEB-15:00 | 13.90 | 10.81 | 0.447824E+09 | 828.74 | 28-FEB-14:00 | 13.90 | 10.81 |
March | 0.247634E+10 | 2945.49 | 10-MAR-14:30 | 16.40 | 11.76 | 0.582478E+09 | 845.59 | 10-MAR-14:09 | 16.40 | 11.76 |
April | 0.315462E+10 | 6667.33 | 27-APR-15:20 | 27.20 | 17.16 | 0.557571E+09 | 845.62 | 27-APR-13:30 | 27.20 | 17.16 |
May | 0.485282E+10 | 7345.70 | 05-MAY-13:30 | 23.85 | 16.52 | 0.639703E+09 | 845.63 | 15-MAY-13:09 | 22.88 | 13.76 |
June | 0.583394E+10 | 7954.49 | 21-JUN-15:30 | 24.70 | 15.68 | 0.652101E+09 | 845.64 | 09-JUN-13:09 | 24.70 | 15.68 |
July | 0.658694E+10 | 9210.33 | 24-JUL-15:00 | 30.60 | 18.78 | 0.609796E+09 | 845.64 | 28-JUL-13:50 | 20.55 | 15.38 |
August | 0.674160E+10 | 8796.88 | 25-AUG-14:00 | 27.40 | 18.74 | 0.683399E+09 | 845.70 | 09-AUG-09:00 | 27.40 | 18.74 |
September | 0.425589E+10 | 6470.11 | 12-SEP-14:40 | 24.40 | 16.65 | 0.589583E+09 | 845.63 | 14-SEP-09:09 | 17.38 | 15.51 |
October | 0.270562E+10 | 3927.45 | 06-OCT-14:40 | 17.20 | 12.13 | 0.558816E+09 | 845.60 | 05-OCT-13:00 | 17.20 | 12.13 |
November | 0.166596E+10 | 2278.02 | 02-NOV-14:10 | 14.22 | 11.35 | 0.498769E+09 | 795.29 | 02-NOV-13:00 | 14.22 | 11.35 |
December | 0.928400E+09 | 1878.68 | 29-DEC-16:10 | 10.40 | 8.63 | 0.458958E+09 | 692.00 | 29-DEC-14:00 | 10.40 | 8.63 |
Annual Sum or Average | 0.412186E+11 | 0.675102E+10 | ||||||||
Minimum of Months | 0.752984E+09 | 1878.68 | 10.40 | 8.63 | 0.447824E+09 | 692.00 | 10.40 | 8.63 | ||
Maximum of Months | 0.674160E+10 | 9210.33 | 30.60 | 18.78 | 0.683399E+09 | 845.70 | 27.40 | 18.74 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.670389E+09 | 2318.54 | 05-JAN-09:40 | 1.67 | 1.50 | 0.221019E+09 | 429.71 | 05-JAN-09:50 | 2.23 | 2.03 |
February | 0.141748E+10 | 3198.37 | 12-FEB-11:52 | 5.60 | 0.67 | 0.211259E+09 | 511.63 | 08-FEB-09:00 | 5.60 | 0.67 |
March | 0.310613E+10 | 8127.63 | 14-MAR-10:10 | 10.28 | 7.92 | 0.273300E+09 | 521.21 | 14-MAR-10:09 | 10.28 | 7.92 |
April | 0.465231E+10 | 13863.99 | 27-APR-09:00 | 17.80 | 12.21 | 0.267514E+09 | 521.22 | 20-APR-10:09 | 17.80 | 12.21 |
May | 0.598465E+10 | 22731.29 | 14-MAY-09:22 | 17.80 | 11.88 | 0.296530E+09 | 521.23 | 15-MAY-10:09 | 19.18 | 13.24 |
June | 0.750120E+10 | 28339.56 | 25-JUN-08:21 | 16.15 | 11.79 | 0.304913E+09 | 521.22 | 07-JUN-10:09 | 16.15 | 11.79 |
July | 0.786901E+10 | 30249.09 | 30-JUL-08:41 | 20.22 | 15.61 | 0.286287E+09 | 521.64 | 31-JUL-08:00 | 22.20 | 16.89 |
August | 0.844248E+10 | 30193.51 | 13-AUG-08:51 | 20.90 | 15.90 | 0.320829E+09 | 521.60 | 10-AUG-10:09 | 20.90 | 15.90 |
September | 0.567388E+10 | 23234.17 | 10-SEP-08:42 | 15.82 | 13.36 | 0.272404E+09 | 521.21 | 14-SEP-07:10 | 14.18 | 13.39 |
October | 0.337814E+10 | 10193.78 | 04-OCT-09:00 | 15.60 | 10.49 | 0.259198E+09 | 521.22 | 05-OCT-10:09 | 14.08 | 9.36 |
November | 0.160636E+10 | 2927.69 | 04-NOV-10:30 | 16.95 | 14.30 | 0.227638E+09 | 501.68 | 02-NOV-10:50 | 16.95 | 14.30 |
December | 0.919352E+09 | 2568.67 | 05-DEC-10:00 | 6.70 | 5.10 | 0.215018E+09 | 456.45 | 05-DEC-09:00 | 6.70 | 5.10 |
Annual Sum or Average | 0.512214E+11 | 0.315591E+10 | ||||||||
Minimum of Months | 0.670389E+09 | 2318.54 | 1.67 | 0.67 | 0.211259E+09 | 429.71 | 2.23 | 0.67 | ||
Maximum of Months | 0.844248E+10 | 30249.09 | 20.90 | 15.90 | 0.320829E+09 | 521.64 | 22.20 | 16.89 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.258924E+10 | 18884.24 | 20-JAN-13:20 | 6.70 | 4.72 | 0.502753E+09 | 845.64 | 11-JAN-14:09 | 6.70 | 4.72 |
February | 0.474217E+10 | 37094.89 | 12-FEB-13:12 | 6.30 | 1.05 | 0.487989E+09 | 846.27 | 27-FEB-14:50 | 19.72 | 12.05 |
March | 0.766748E+10 | 23922.67 | 01-MAR-13:40 | 11.33 | 6.09 | 0.611047E+09 | 846.62 | 01-MAR-14:00 | 13.30 | 7.37 |
April | 0.836034E+10 | 23885.58 | 23-APR-14:32 | 18.13 | 9.41 | 0.567881E+09 | 846.56 | 27-APR-13:00 | 26.10 | 16.83 |
May | 0.926586E+10 | 28638.94 | 14-MAY-13:22 | 22.50 | 12.24 | 0.629415E+09 | 845.67 | 15-MAY-13:09 | 22.88 | 13.76 |
June | 0.941462E+10 | 35126.21 | 11-JUN-13:02 | 21.78 | 15.29 | 0.639378E+09 | 845.68 | 28-JUN-13:30 | 24.70 | 15.69 |
July | 0.114050E+11 | 40029.12 | 30-JUL-13:21 | 26.40 | 17.72 | 0.601371E+09 | 846.63 | 31-JUL-13:00 | 28.30 | 18.92 |
August | 0.132596E+11 | 40163.35 | 13-AUG-12:51 | 26.50 | 18.40 | 0.677267E+09 | 847.92 | 29-AUG-13:39 | 29.43 | 20.04 |
September | 0.118831E+11 | 37874.73 | 10-SEP-12:42 | 20.40 | 13.99 | 0.586565E+09 | 847.43 | 15-SEP-13:00 | 21.70 | 16.45 |
October | 0.871439E+10 | 36677.31 | 08-OCT-13:22 | 18.90 | 13.91 | 0.576673E+09 | 849.78 | 04-OCT-13:20 | 18.90 | 13.91 |
November | 0.410286E+10 | 36979.67 | 11-NOV-12:42 | 6.42 | 5.03 | 0.523142E+09 | 845.64 | 15-NOV-10:09 | 7.30 | 5.72 |
December | 0.340213E+10 | 18827.96 | 05-DEC-12:30 | 10.30 | 6.13 | 0.496962E+09 | 845.65 | 05-DEC-14:00 | 10.00 | 7.01 |
Annual Sum or Average | 0.948068E+11 | 0.690044E+10 | ||||||||
Minimum of Months | 0.258924E+10 | 18827.96 | 6.30 | 1.05 | 0.487989E+09 | 845.64 | 6.70 | 4.72 | ||
Maximum of Months | 0.132596E+11 | 40163.35 | 26.50 | 18.40 | 0.677267E+09 | 849.78 | 29.43 | 20.04 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.102111E+10 | 3011.48 | 05-JAN-15:50 | 6.20 | 4.71 | 0.305086E+09 | 495.81 | 05-JAN-15:00 | 6.10 | 4.61 |
February | 0.185392E+10 | 8856.86 | 27-FEB-15:30 | 19.70 | 12.30 | 0.291679E+09 | 544.93 | 27-FEB-14:00 | 19.70 | 12.30 |
March | 0.352408E+10 | 11873.93 | 14-MAR-16:00 | 17.20 | 10.94 | 0.367582E+09 | 544.95 | 02-MAR-14:00 | 17.20 | 10.94 |
April | 0.493032E+10 | 18064.92 | 01-APR-17:04 | 26.52 | 12.40 | 0.350617E+09 | 544.96 | 27-APR-13:00 | 26.10 | 16.83 |
May | 0.684902E+10 | 29069.52 | 14-MAY-16:41 | 22.88 | 11.80 | 0.399822E+09 | 544.96 | 15-MAY-13:09 | 22.88 | 13.76 |
June | 0.736387E+10 | 27929.05 | 25-JUN-16:21 | 21.70 | 13.23 | 0.410043E+09 | 544.97 | 28-JUN-13:30 | 24.70 | 15.69 |
July | 0.951991E+10 | 33828.04 | 23-JUL-17:11 | 26.50 | 15.70 | 0.388865E+09 | 544.96 | 28-JUL-13:50 | 20.55 | 15.38 |
August | 0.913747E+10 | 32804.26 | 06-AUG-17:41 | 23.73 | 15.23 | 0.435249E+09 | 545.01 | 09-AUG-09:00 | 23.80 | 15.92 |
September | 0.638717E+10 | 27951.00 | 10-SEP-16:42 | 22.20 | 14.22 | 0.368528E+09 | 544.96 | 15-SEP-13:00 | 21.70 | 16.45 |
October | 0.376751E+10 | 13169.93 | 04-OCT-16:00 | 21.10 | 11.40 | 0.347546E+09 | 544.93 | 24-OCT-13:00 | 16.70 | 11.78 |
November | 0.202560E+10 | 6301.45 | 04-NOV-15:30 | 20.55 | 15.94 | 0.314089E+09 | 544.93 | 15-NOV-14:00 | 8.90 | 6.49 |
December | 0.132634E+10 | 3214.48 | 05-DEC-15:40 | 7.40 | 5.40 | 0.298434E+09 | 524.58 | 05-DEC-14:00 | 7.40 | 5.40 |
Annual Sum or Average | 0.577063E+11 | 0.427754E+10 | ||||||||
Minimum of Months | 0.102111E+10 | 3011.48 | 6.20 | 4.71 | 0.291679E+09 | 495.81 | 6.10 | 4.61 | ||
Maximum of Months | 0.951991E+10 | 33828.04 | 26.52 | 15.94 | 0.435249E+09 | 545.01 | 26.10 | 16.83 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.328570E+09 | 1888.82 | 11-JAN-16:20 | 13.67 | 10.10 | 0.465386E+09 | 674.88 | 11-JAN-14:00 | 13.67 | 10.10 |
February | 0.753687E+09 | 2369.71 | 28-FEB-15:10 | 13.90 | 10.77 | 0.434133E+09 | 802.28 | 28-FEB-14:00 | 13.90 | 10.77 |
March | 0.177408E+10 | 2521.36 | 10-MAR-14:50 | 16.20 | 11.59 | 0.549137E+09 | 844.02 | 10-MAR-14:00 | 16.10 | 11.51 |
April | 0.270567E+10 | 7280.27 | 27-APR-15:20 | 27.20 | 17.16 | 0.531803E+09 | 845.63 | 27-APR-13:30 | 27.20 | 17.16 |
May | 0.444510E+10 | 7656.04 | 05-MAY-13:30 | 23.85 | 16.52 | 0.619390E+09 | 845.63 | 15-MAY-13:09 | 22.88 | 13.76 |
June | 0.561231E+10 | 8579.05 | 21-JUN-15:30 | 24.70 | 15.68 | 0.641562E+09 | 845.64 | 09-JUN-13:09 | 24.70 | 15.68 |
July | 0.652786E+10 | 10164.75 | 24-JUL-15:00 | 30.60 | 18.78 | 0.604077E+09 | 845.64 | 28-JUL-13:50 | 20.55 | 15.38 |
August | 0.661521E+10 | 9335.42 | 09-AUG-14:40 | 28.17 | 18.42 | 0.675949E+09 | 845.69 | 09-AUG-09:00 | 28.17 | 18.42 |
September | 0.385469E+10 | 6765.52 | 12-SEP-14:40 | 24.40 | 16.65 | 0.567782E+09 | 845.62 | 07-SEP-13:09 | 24.40 | 16.65 |
October | 0.204341E+10 | 3758.68 | 04-OCT-15:30 | 21.40 | 11.45 | 0.523194E+09 | 845.60 | 05-OCT-13:00 | 16.10 | 10.65 |
November | 0.938143E+09 | 2209.84 | 02-NOV-14:40 | 13.67 | 11.26 | 0.474107E+09 | 758.64 | 02-NOV-13:00 | 13.67 | 11.26 |
December | 0.332891E+09 | 1783.85 | 29-DEC-16:10 | 10.40 | 8.63 | 0.448883E+09 | 655.72 | 29-DEC-14:00 | 10.40 | 8.63 |
Annual Sum or Average | 0.359316E+11 | 0.653540E+10 | ||||||||
Minimum of Months | 0.328570E+09 | 1783.85 | 10.40 | 8.63 | 0.434133E+09 | 655.72 | 10.40 | 8.63 | ||
Maximum of Months | 0.661521E+10 | 10164.75 | 30.60 | 18.78 | 0.675949E+09 | 845.69 | 28.17 | 18.42 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.357960E+09 | 2106.76 | 20-JAN-10:40 | 5.03 | 3.09 | 0.299620E+09 | 424.87 | 20-JAN-10:50 | 5.32 | 3.17 |
February | 0.100350E+10 | 2633.53 | 03-FEB-10:40 | 9.43 | 7.01 | 0.281399E+09 | 492.50 | 03-FEB-10:50 | 9.72 | 7.15 |
March | 0.240753E+10 | 6902.81 | 14-MAR-09:50 | 9.63 | 7.44 | 0.364061E+09 | 544.96 | 02-MAR-10:09 | 9.63 | 7.44 |
April | 0.413717E+10 | 13428.29 | 27-APR-09:10 | 17.98 | 12.34 | 0.359675E+09 | 544.96 | 20-APR-09:00 | 17.98 | 12.34 |
May | 0.559054E+10 | 26653.06 | 14-MAY-09:42 | 18.53 | 12.07 | 0.400226E+09 | 544.98 | 15-MAY-09:00 | 18.90 | 13.25 |
June | 0.731346E+10 | 22612.40 | 25-JUN-08:42 | 16.52 | 11.95 | 0.413688E+09 | 544.97 | 09-JUN-13:09 | 16.52 | 11.95 |
July | 0.783194E+10 | 29229.87 | 23-JUL-08:41 | 18.72 | 13.76 | 0.387689E+09 | 545.97 | 31-JUL-09:00 | 23.30 | 17.69 |
August | 0.837415E+10 | 29036.21 | 13-AUG-08:21 | 20.20 | 15.50 | 0.435580E+09 | 546.01 | 10-AUG-09:00 | 20.20 | 15.50 |
September | 0.525024E+10 | 26848.17 | 10-SEP-09:42 | 17.02 | 13.53 | 0.365277E+09 | 544.97 | 14-SEP-09:09 | 17.38 | 15.51 |
October | 0.267107E+10 | 9080.02 | 04-OCT-09:20 | 16.13 | 10.66 | 0.344598E+09 | 544.96 | 05-OCT-09:00 | 13.90 | 9.28 |
November | 0.986416E+09 | 2684.65 | 04-NOV-10:30 | 16.95 | 14.30 | 0.302647E+09 | 479.45 | 02-NOV-13:00 | 16.95 | 14.30 |
December | 0.437642E+09 | 2207.68 | 05-DEC-10:30 | 7.50 | 5.28 | 0.289460E+09 | 437.34 | 05-DEC-10:39 | 7.77 | 5.32 |
Annual Sum or Average | 0.463616E+11 | 0.424392E+10 | ||||||||
Minimum of Months | 0.357960E+09 | 2106.76 | 5.03 | 3.09 | 0.281399E+09 | 424.87 | 5.32 | 3.17 | ||
Maximum of Months | 0.837415E+10 | 29229.87 | 20.20 | 15.50 | 0.435580E+09 | 546.01 | 23.30 | 17.69 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.181446E+10 | 17327.38 | 20-JAN-13:30 | 6.70 | 4.72 | 0.489657E+09 | 845.64 | 20-JAN-14:20 | 6.87 | 4.79 |
February | 0.372842E+10 | 20544.28 | 27-FEB-14:20 | 18.87 | 11.68 | 0.474547E+09 | 845.64 | 10-FEB-14:09 | 18.87 | 11.68 |
March | 0.641962E+10 | 23132.54 | 14-MAR-13:30 | 15.00 | 10.00 | 0.589615E+09 | 846.15 | 01-MAR-14:39 | 15.00 | 10.00 |
April | 0.755561E+10 | 38317.37 | 02-APR-13:42 | 18.90 | 11.23 | 0.551294E+09 | 846.62 | 27-APR-13:00 | 26.10 | 16.83 |
May | 0.868012E+10 | 38507.72 | 14-MAY-13:42 | 22.70 | 12.26 | 0.612841E+09 | 845.67 | 15-MAY-13:09 | 22.88 | 13.76 |
June | 0.917655E+10 | 28873.58 | 11-JUN-12:32 | 21.70 | 15.39 | 0.627550E+09 | 845.68 | 09-JUN-13:09 | 21.70 | 15.39 |
July | 0.113788E+11 | 40560.73 | 30-JUL-12:11 | 26.10 | 17.39 | 0.593258E+09 | 846.67 | 31-JUL-13:00 | 28.30 | 18.92 |
August | 0.131723E+11 | 41129.97 | 13-AUG-14:21 | 27.65 | 18.96 | 0.668208E+09 | 847.49 | 29-AUG-13:30 | 29.30 | 20.07 |
September | 0.112975E+11 | 42128.01 | 10-SEP-15:01 | 22.70 | 14.34 | 0.569475E+09 | 847.43 | 15-SEP-13:00 | 21.70 | 16.45 |
October | 0.743361E+10 | 38750.68 | 08-OCT-13:52 | 20.00 | 14.17 | 0.555328E+09 | 846.23 | 04-OCT-13:00 | 20.00 | 14.17 |
November | 0.287127E+10 | 19870.21 | 04-NOV-13:30 | 20.85 | 16.00 | 0.499443E+09 | 845.64 | 15-NOV-14:00 | 8.90 | 6.49 |
December | 0.230762E+10 | 16552.57 | 05-DEC-12:30 | 10.30 | 6.13 | 0.481984E+09 | 845.65 | 05-DEC-14:00 | 10.00 | 7.01 |
Annual Sum or Average | 0.858358E+11 | 0.671320E+10 | ||||||||
Minimum of Months | 0.181446E+10 | 16552.57 | 6.70 | 4.72 | 0.474547E+09 | 845.64 | 6.87 | 4.79 | ||
Maximum of Months | 0.131723E+11 | 42128.01 | 27.65 | 18.96 | 0.668208E+09 | 847.49 | 29.30 | 20.07 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.623929E+09 | 3014.33 | 05-JAN-15:50 | 6.20 | 4.71 | 0.302178E+09 | 481.83 | 05-JAN-15:00 | 6.10 | 4.61 |
February | 0.132491E+10 | 8408.43 | 27-FEB-15:30 | 19.70 | 12.30 | 0.286351E+09 | 544.93 | 27-FEB-14:00 | 19.70 | 12.30 |
March | 0.285849E+10 | 11857.87 | 14-MAR-16:00 | 17.20 | 10.94 | 0.355349E+09 | 544.94 | 02-MAR-14:00 | 17.20 | 10.94 |
April | 0.449645E+10 | 22383.02 | 02-APR-15:41 | 20.60 | 11.97 | 0.338828E+09 | 544.96 | 27-APR-13:00 | 26.10 | 16.83 |
May | 0.654634E+10 | 33739.29 | 14-MAY-17:01 | 22.70 | 11.79 | 0.388070E+09 | 544.96 | 15-MAY-13:09 | 22.88 | 13.76 |
June | 0.724535E+10 | 31940.20 | 18-JUN-17:01 | 17.12 | 12.23 | 0.401480E+09 | 544.97 | 09-JUN-13:09 | 17.12 | 12.23 |
July | 0.951905E+10 | 35118.88 | 23-JUL-17:21 | 26.40 | 15.75 | 0.383514E+09 | 544.97 | 28-JUL-13:50 | 20.55 | 15.38 |
August | 0.909779E+10 | 30483.60 | 06-AUG-17:21 | 23.60 | 15.18 | 0.428541E+09 | 545.01 | 09-AUG-09:00 | 23.80 | 15.92 |
September | 0.607133E+10 | 30240.37 | 10-SEP-16:21 | 22.20 | 14.33 | 0.356191E+09 | 544.95 | 15-SEP-13:00 | 21.70 | 16.45 |
October | 0.311914E+10 | 13125.23 | 04-OCT-16:00 | 21.10 | 11.40 | 0.333349E+09 | 544.93 | 03-OCT-13:00 | 21.10 | 11.40 |
November | 0.131309E+10 | 5952.10 | 04-NOV-15:30 | 20.55 | 15.94 | 0.305239E+09 | 533.28 | 15-NOV-14:00 | 8.90 | 6.49 |
December | 0.736677E+09 | 3148.77 | 05-DEC-15:40 | 7.40 | 5.40 | 0.293786E+09 | 500.86 | 05-DEC-14:00 | 7.40 | 5.40 |
Annual Sum or Average | 0.529525E+11 | 0.417288E+10 | ||||||||
Minimum of Months | 0.623929E+09 | 3014.33 | 6.20 | 4.71 | 0.286351E+09 | 481.83 | 6.10 | 4.61 | ||
Maximum of Months | 0.951905E+10 | 35118.88 | 26.40 | 15.94 | 0.428541E+09 | 545.01 | 26.10 | 16.83 |
Report: ZoneCoolingSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.138725E+10 | 5911.60 | 17-JAN-06:03 | 1.20 | -0.4 | 0.00 | 0.00 | 01-JAN-00:10 | 1.20 | -0.4 |
February | 0.195395E+10 | 4681.92 | 28-FEB-06:15 | 10.60 | 9.74 | 0.00 | 0.00 | 01-FEB-00:10 | 10.60 | 9.74 |
March | 0.396696E+10 | 5765.37 | 01-MAR-06:10 | -0.1 | -1.5 | 0.00 | 0.00 | 01-MAR-00:10 | -0.1 | -1.5 |
April | 0.533000E+10 | 7352.95 | 27-APR-14:50 | 27.02 | 17.21 | 0.00 | 0.00 | 01-APR-00:10 | 27.02 | 17.21 |
May | 0.581463E+10 | 7176.60 | 15-MAY-15:10 | 23.40 | 12.66 | 0.00 | 0.00 | 01-MAY-00:10 | 23.40 | 12.66 |
June | 0.721553E+10 | 8976.14 | 12-JUN-05:15 | 14.40 | 13.42 | 0.00 | 0.00 | 01-JUN-00:10 | 14.40 | 13.42 |
July | 0.863194E+10 | 9177.43 | 31-JUL-15:00 | 28.30 | 18.91 | 0.00 | 0.00 | 01-JUL-00:10 | 28.30 | 18.91 |
August | 0.963891E+10 | 9348.99 | 14-AUG-15:00 | 27.00 | 17.53 | 0.00 | 0.00 | 01-AUG-00:10 | 27.00 | 17.53 |
September | 0.626420E+10 | 8755.92 | 05-SEP-05:15 | 10.77 | 9.27 | 0.00 | 0.00 | 01-SEP-00:10 | 10.77 | 9.27 |
October | 0.453685E+10 | 8427.11 | 10-OCT-05:15 | 12.20 | 11.16 | 0.00 | 0.00 | 01-OCT-00:10 | 12.20 | 11.16 |
November | 0.304866E+10 | 6730.18 | 06-NOV-06:15 | 11.47 | 8.44 | 0.00 | 0.00 | 01-NOV-00:10 | 11.47 | 8.44 |
December | 0.228260E+10 | 4633.97 | 07-DEC-06:10 | 4.27 | 2.78 | 0.00 | 0.00 | 01-DEC-00:10 | 4.27 | 2.78 |
Annual Sum or Average | 0.600715E+11 | 0.00 | ||||||||
Minimum of Months | 0.138725E+10 | 4633.97 | -0.1 | -1.5 | 0.00 | 0.00 | -0.1 | -1.5 | ||
Maximum of Months | 0.963891E+10 | 9348.99 | 28.30 | 18.91 | 0.00 | 0.00 | 28.30 | 18.91 |
Report: ZoneCoolingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.261170E+09 | 9349.07 | 14-JAN-05:11 | 2.20 | 1.37 | 0.00 | 0.00 | 01-JAN-00:10 | 2.20 | 1.37 |
February | 0.698721E+09 | 8605.92 | 13-FEB-05:01 | 1.28 | -1.7 | 0.00 | 0.00 | 01-FEB-00:10 | 1.28 | -1.7 |
March | 0.152692E+10 | 7027.24 | 06-MAR-05:11 | 6.70 | 6.18 | 0.00 | 0.00 | 01-MAR-00:10 | 6.70 | 6.18 |
April | 0.222709E+10 | 5674.28 | 29-APR-05:10 | 8.40 | 8.40 | 0.00 | 0.00 | 01-APR-00:10 | 8.40 | 8.40 |
May | 0.368750E+10 | 5481.14 | 17-MAY-05:10 | 8.90 | 8.37 | 0.00 | 0.00 | 01-MAY-00:10 | 8.90 | 8.37 |
June | 0.469637E+10 | 5754.62 | 28-JUN-15:40 | 26.10 | 16.04 | 0.00 | 0.00 | 01-JUN-00:10 | 26.10 | 16.04 |
July | 0.570997E+10 | 6622.86 | 31-JUL-15:20 | 28.50 | 19.00 | 0.00 | 0.00 | 01-JUL-00:10 | 28.50 | 19.00 |
August | 0.654341E+10 | 7683.11 | 10-AUG-15:10 | 30.37 | 18.88 | 0.00 | 0.00 | 01-AUG-00:10 | 30.37 | 18.88 |
September | 0.449427E+10 | 7344.19 | 15-SEP-05:13 | 11.50 | 11.26 | 0.00 | 0.00 | 01-SEP-00:10 | 11.50 | 11.26 |
October | 0.235830E+10 | 5536.85 | 06-OCT-05:10 | 11.10 | 10.49 | 0.00 | 0.00 | 01-OCT-00:10 | 11.10 | 10.49 |
November | 0.102205E+10 | 8185.11 | 24-NOV-05:11 | 2.60 | 1.97 | 0.00 | 0.00 | 01-NOV-00:10 | 2.60 | 1.97 |
December | 0.576445E+09 | 8806.51 | 09-DEC-05:11 | 1.67 | 1.26 | 0.00 | 0.00 | 01-DEC-00:10 | 1.67 | 1.26 |
Annual Sum or Average | 0.338022E+11 | 0.00 | ||||||||
Minimum of Months | 0.261170E+09 | 5481.14 | 1.28 | -1.7 | 0.00 | 0.00 | 1.28 | -1.7 | ||
Maximum of Months | 0.654341E+10 | 9349.07 | 30.37 | 19.00 | 0.00 | 0.00 | 30.37 | 19.00 |
Report: ZoneCoolingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 673373.51 | 349.49 | 11-JAN-17:30 | 12.50 | 9.44 | 0.00 | 0.00 | 01-JAN-00:10 | 12.50 | 9.44 |
February | 0.185772E+09 | 3679.31 | 27-FEB-15:30 | 19.70 | 12.30 | 0.00 | 0.00 | 01-FEB-00:10 | 19.70 | 12.30 |
March | 0.110791E+10 | 6869.54 | 14-MAR-15:00 | 16.10 | 10.31 | 0.00 | 0.00 | 01-MAR-00:10 | 16.10 | 10.31 |
April | 0.340862E+10 | 16862.39 | 27-APR-14:30 | 26.65 | 17.06 | 0.00 | 0.00 | 01-APR-00:10 | 26.65 | 17.06 |
May | 0.602640E+10 | 17068.23 | 04-MAY-14:00 | 23.90 | 15.33 | 0.00 | 0.00 | 01-MAY-00:10 | 23.90 | 15.33 |
June | 0.784387E+10 | 17552.73 | 28-JUN-14:30 | 25.55 | 15.61 | 0.00 | 0.00 | 01-JUN-00:10 | 25.55 | 15.61 |
July | 0.100593E+11 | 19197.22 | 24-JUL-14:00 | 29.40 | 18.12 | 0.00 | 0.00 | 01-JUL-00:10 | 29.40 | 18.12 |
August | 0.984034E+10 | 20091.87 | 10-AUG-14:20 | 29.67 | 19.07 | 0.00 | 0.00 | 01-AUG-00:10 | 29.67 | 19.07 |
September | 0.524989E+10 | 15438.22 | 14-SEP-14:50 | 23.90 | 16.99 | 0.00 | 0.00 | 01-SEP-00:10 | 23.90 | 16.99 |
October | 0.150463E+10 | 10024.81 | 04-OCT-14:50 | 21.60 | 11.48 | 0.00 | 0.00 | 01-OCT-00:10 | 21.60 | 11.48 |
November | 0.139600E+09 | 3786.40 | 04-NOV-13:50 | 21.02 | 15.96 | 0.00 | 0.00 | 01-NOV-00:10 | 21.02 | 15.96 |
December | 141110.56 | 144.58 | 30-DEC-12:40 | 8.70 | 7.56 | 0.00 | 0.00 | 01-DEC-00:10 | 8.70 | 7.56 |
Annual Sum or Average | 0.453671E+11 | 0.00 | ||||||||
Minimum of Months | 141110.56 | 144.58 | 8.70 | 7.56 | 0.00 | 0.00 | 8.70 | 7.56 | ||
Maximum of Months | 0.100593E+11 | 20091.87 | 29.67 | 19.07 | 0.00 | 0.00 | 29.67 | 19.07 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.293532E+10 | 2108.67 | 05-JAN-16:10 | 5.73 | 4.38 | 95230012.09 | 126.82 | 19-JAN-14:09 | 5.40 | 2.91 |
February | 0.777375E+10 | 4255.90 | 07-FEB-16:50 | 7.30 | 3.84 | 86397269.50 | 126.83 | 24-FEB-10:00 | 13.30 | 12.07 |
March | 0.142718E+11 | 6984.10 | 31-MAR-24:00 | 8.00 | 7.45 | 0.103237E+09 | 126.83 | 09-MAR-14:00 | 8.00 | 7.45 |
April | 0.189824E+11 | 8393.34 | 26-APR-18:00 | 22.80 | 13.49 | 91605332.99 | 126.83 | 28-APR-09:00 | 11.70 | 11.07 |
May | 0.448144E+10 | 3476.74 | 31-MAY-24:00 | 13.00 | 10.11 | 99236441.06 | 126.84 | 31-MAY-13:00 | 13.00 | 10.11 |
June | 0.941527E+10 | 5349.92 | 30-JUN-24:00 | 15.50 | 12.58 | 98961140.12 | 126.84 | 12-JUN-13:00 | 15.50 | 12.58 |
July | 0.149770E+11 | 7258.35 | 31-JUL-23:27 | 18.10 | 14.47 | 91884362.07 | 126.84 | 11-JUL-09:30 | 18.10 | 14.47 |
August | 0.199675E+11 | 8852.88 | 06-AUG-18:43 | 22.13 | 15.01 | 0.103239E+09 | 126.83 | 02-AUG-09:09 | 22.13 | 15.01 |
September | 0.441076E+10 | 3313.14 | 30-SEP-24:00 | 14.30 | 12.32 | 91612659.82 | 126.84 | 13-SEP-13:39 | 14.30 | 12.32 |
October | 0.927741E+10 | 4983.46 | 31-OCT-24:00 | 9.10 | 7.85 | 95231910.17 | 126.84 | 26-OCT-13:00 | 9.10 | 7.85 |
November | 0.136360E+11 | 5913.31 | 10-NOV-16:00 | 8.90 | 6.48 | 94301513.92 | 126.83 | 01-NOV-13:00 | 8.90 | 6.48 |
December | 0.189773E+11 | 7978.84 | 05-DEC-15:50 | 6.75 | 4.97 | 91880892.89 | 126.82 | 28-DEC-14:00 | 11.10 | 9.78 |
Annual Sum or Average | 0.139106E+12 | 0.114282E+10 | ||||||||
Minimum of Months | 0.293532E+10 | 2108.67 | 5.73 | 3.84 | 86397269.50 | 126.82 | 5.40 | 2.91 | ||
Maximum of Months | 0.199675E+11 | 8852.88 | 22.80 | 15.01 | 0.103239E+09 | 126.84 | 22.13 | 15.01 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.847672E+09 | 1680.87 | 05-JAN-16:20 | 5.37 | 4.14 | 94921358.06 | 126.82 | 19-JAN-14:09 | 5.40 | 2.91 |
February | 0.566972E+10 | 3887.75 | 08-FEB-17:00 | 6.70 | 3.26 | 86397186.20 | 126.83 | 24-FEB-10:00 | 13.30 | 12.07 |
March | 0.121867E+11 | 6104.15 | 31-MAR-23:40 | 8.10 | 7.54 | 0.103237E+09 | 126.83 | 09-MAR-14:00 | 8.10 | 7.54 |
April | 0.171522E+11 | 8014.17 | 26-APR-18:00 | 22.80 | 13.49 | 91605421.41 | 126.83 | 28-APR-13:09 | 16.97 | 14.14 |
May | 0.361241E+10 | 3224.57 | 31-MAY-23:50 | 13.17 | 10.29 | 99236174.57 | 126.84 | 31-MAY-13:00 | 13.17 | 10.29 |
June | 0.849830E+10 | 5002.81 | 30-JUN-24:00 | 15.50 | 12.58 | 98961025.72 | 126.84 | 12-JUN-13:00 | 15.50 | 12.58 |
July | 0.139668E+11 | 7003.15 | 31-JUL-24:00 | 17.40 | 14.08 | 91884819.50 | 126.84 | 11-JUL-13:30 | 17.40 | 14.08 |
August | 0.187813E+11 | 8295.02 | 06-AUG-18:32 | 22.47 | 15.07 | 0.103240E+09 | 126.83 | 30-AUG-09:00 | 20.00 | 17.05 |
September | 0.361104E+10 | 2897.89 | 30-SEP-23:40 | 14.20 | 12.22 | 91612066.01 | 126.84 | 13-SEP-13:39 | 14.20 | 12.22 |
October | 0.761377E+10 | 4393.12 | 04-OCT-16:50 | 20.68 | 11.37 | 95231721.61 | 126.83 | 26-OCT-13:00 | 13.30 | 12.35 |
November | 0.112021E+11 | 5460.81 | 10-NOV-16:10 | 8.53 | 6.27 | 94301382.03 | 126.83 | 01-NOV-13:00 | 8.53 | 6.27 |
December | 0.158198E+11 | 7303.23 | 05-DEC-16:00 | 6.10 | 4.53 | 91880922.49 | 126.82 | 28-DEC-14:00 | 11.10 | 9.78 |
Annual Sum or Average | 0.118962E+12 | 0.114251E+10 | ||||||||
Minimum of Months | 0.847672E+09 | 1680.87 | 5.37 | 3.26 | 86397186.20 | 126.82 | 5.40 | 2.91 | ||
Maximum of Months | 0.187813E+11 | 8295.02 | 22.80 | 15.07 | 0.103240E+09 | 126.84 | 20.00 | 17.05 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.414754E+09 | 1612.48 | 05-JAN-16:20 | 5.37 | 4.14 | 93628526.73 | 127.20 | 30-JAN-10:00 | 7.80 | 6.21 |
February | 0.424883E+10 | 3812.91 | 08-FEB-17:00 | 6.70 | 3.26 | 86397218.36 | 126.83 | 24-FEB-10:00 | 13.30 | 12.07 |
March | 0.109743E+11 | 5892.46 | 01-MAR-17:00 | 12.20 | 6.61 | 0.103237E+09 | 126.83 | 09-MAR-14:00 | 14.40 | 11.89 |
April | 0.163748E+11 | 8088.27 | 26-APR-18:00 | 22.80 | 13.49 | 91605440.09 | 126.83 | 28-APR-09:00 | 11.70 | 11.07 |
May | 0.307356E+10 | 3142.31 | 31-MAY-23:20 | 13.67 | 10.85 | 99236444.73 | 126.84 | 31-MAY-13:00 | 13.67 | 10.85 |
June | 0.824286E+10 | 4899.13 | 30-JUN-23:40 | 15.63 | 12.81 | 98961024.20 | 126.84 | 12-JUN-13:00 | 15.63 | 12.81 |
July | 0.137982E+11 | 6969.80 | 31-JUL-23:45 | 17.63 | 14.21 | 91884763.84 | 126.84 | 11-JUL-13:20 | 17.63 | 14.21 |
August | 0.185851E+11 | 8401.66 | 06-AUG-18:23 | 22.80 | 15.13 | 0.103240E+09 | 126.83 | 31-AUG-09:50 | 15.78 | 14.63 |
September | 0.307631E+10 | 2610.69 | 10-SEP-17:22 | 21.40 | 14.01 | 91611723.35 | 126.85 | 13-SEP-13:39 | 22.23 | 17.24 |
October | 0.650505E+10 | 4421.28 | 04-OCT-16:50 | 20.68 | 11.37 | 95231678.84 | 126.83 | 26-OCT-13:00 | 13.30 | 12.35 |
November | 0.971963E+10 | 5329.22 | 10-NOV-16:10 | 8.53 | 6.27 | 94301385.16 | 126.83 | 01-NOV-13:00 | 8.53 | 6.27 |
December | 0.140539E+11 | 7149.51 | 05-DEC-16:00 | 6.10 | 4.53 | 91880934.78 | 126.82 | 28-DEC-14:00 | 11.10 | 9.78 |
Annual Sum or Average | 0.109067E+12 | 0.114122E+10 | ||||||||
Minimum of Months | 0.414754E+09 | 1612.48 | 5.37 | 3.26 | 86397218.36 | 126.82 | 7.80 | 6.21 | ||
Maximum of Months | 0.185851E+11 | 8401.66 | 22.80 | 15.13 | 0.103240E+09 | 127.20 | 22.23 | 17.24 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.237434E+12 | 92054.50 | 12-JAN-17:00 | 7.20 | 5.41 | 0.206144E+10 | 2745.29 | 09-JAN-14:00 | 7.20 | 5.41 |
February | 0.436042E+12 | 184430.60 | 27-FEB-17:00 | 18.90 | 12.17 | 0.187023E+10 | 2745.80 | 22-FEB-14:39 | 18.90 | 12.17 |
March | 0.730638E+12 | 358856.31 | 31-MAR-24:00 | 8.00 | 7.45 | 0.223484E+10 | 2749.50 | 10-MAR-14:50 | 8.00 | 7.45 |
April | 0.944769E+12 | 368990.77 | 01-APR-18:12 | 24.67 | 11.75 | 0.198440E+10 | 2799.43 | 27-APR-15:00 | 27.20 | 16.90 |
May | 0.242315E+12 | 176730.48 | 31-MAY-24:00 | 13.00 | 10.11 | 0.214808E+10 | 2746.48 | 05-MAY-13:00 | 13.00 | 10.11 |
June | 0.471900E+12 | 268312.73 | 30-JUN-24:00 | 15.50 | 12.58 | 0.214223E+10 | 2747.25 | 19-JUN-13:39 | 15.50 | 12.58 |
July | 0.734001E+12 | 360825.13 | 31-JUL-24:00 | 17.40 | 14.08 | 0.199025E+10 | 2750.32 | 14-JUL-13:09 | 17.40 | 14.08 |
August | 0.978772E+12 | 371155.07 | 10-AUG-21:02 | 22.92 | 16.74 | 0.229656E+10 | 3506.80 | 29-AUG-13:20 | 29.17 | 20.09 |
September | 0.236145E+12 | 175823.14 | 30-SEP-24:00 | 14.30 | 12.32 | 0.198297E+10 | 2746.90 | 14-SEP-13:00 | 14.30 | 12.32 |
October | 0.487096E+12 | 267537.25 | 31-OCT-24:00 | 9.10 | 7.85 | 0.206144E+10 | 2746.44 | 06-OCT-13:00 | 9.10 | 7.85 |
November | 0.707990E+12 | 276947.41 | 06-NOV-17:00 | 11.70 | 10.80 | 0.204134E+10 | 2747.96 | 17-NOV-14:30 | 10.30 | 8.83 |
December | 0.975865E+12 | 368425.69 | 05-DEC-17:00 | 6.10 | 4.53 | 0.198901E+10 | 2747.04 | 28-DEC-10:09 | 10.10 | 8.95 |
Annual Sum or Average | 0.718297E+13 | 0.248028E+11 | ||||||||
Minimum of Months | 0.236145E+12 | 92054.50 | 6.10 | 4.53 | 0.187023E+10 | 2745.29 | 7.20 | 5.41 | ||
Maximum of Months | 0.978772E+12 | 371155.07 | 24.67 | 16.74 | 0.229656E+10 | 3506.80 | 29.17 | 20.09 |
Report: ZoneHeatingSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.147471E+09 | 12451.02 | 11-JAN-05:14 | 10.00 |
February | 89221604.37 | 12687.46 | 25-FEB-05:15 | 10.77 |
March | 0.103507E+09 | 12710.09 | 11-MAR-05:15 | 10.60 |
April | 0.174562E+09 | 13448.24 | 01-APR-16:01 | 27.12 |
May | 0.195766E+09 | 13162.88 | 29-MAY-18:32 | 15.77 |
June | 0.296763E+09 | 12732.73 | 03-JUN-04:15 | 12.20 |
July | 0.356612E+09 | 12475.81 | 10-JUL-04:15 | 13.30 |
August | 0.290498E+09 | 13704.32 | 13-AUG-20:13 | 23.00 |
September | 0.342214E+09 | 14389.70 | 04-SEP-15:33 | 17.60 |
October | 0.231606E+09 | 14690.81 | 09-OCT-16:23 | 18.05 |
November | 0.177201E+09 | 12688.44 | 09-NOV-05:15 | 6.87 |
December | 76802591.04 | 12136.92 | 26-DEC-04:04 | -1.0 |
Annual Sum or Average | 0.248222E+10 | |||
Minimum of Months | 76802591.04 | 12136.92 | -1.0 | |
Maximum of Months | 0.356612E+09 | 14690.81 | 27.12 |
Report: ZoneHeatingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 5.92 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 7.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 5.92 |
April | 0.00 | 0.00 | 01-APR-00:10 | 7.93 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 10.38 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 17.17 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 16.38 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 14.35 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 9.22 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 4.40 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 4.40 | |
Maximum of Months | 0.00 | 0.00 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.385667E+09 | 44203.37 | 02-JAN-05:11 | 6.10 |
February | 4643844.13 | 30958.96 | 21-FEB-06:03 | 1.70 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 5.92 |
April | 0.00 | 0.00 | 01-APR-00:10 | 7.93 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 10.38 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 17.17 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 16.38 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 14.35 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 9.22 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 4.40 |
Annual Sum or Average | 0.390311E+09 | |||
Minimum of Months | 0.00 | 0.00 | 1.70 | |
Maximum of Months | 0.385667E+09 | 44203.37 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.224471E+10 | 79331.63 | 17-JAN-04:51 | 1.70 |
February | 0.963481E+09 | 76951.50 | 21-FEB-04:51 | 1.70 |
March | 0.242797E+09 | 71680.74 | 06-MAR-05:11 | 6.70 |
April | 4613797.85 | 30758.65 | 17-APR-05:03 | 6.10 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 10.38 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 17.17 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 16.38 |
October | 43480310.75 | 64119.81 | 16-OCT-05:03 | 7.12 |
November | 0.599587E+09 | 71611.69 | 13-NOV-05:01 | 1.20 |
December | 0.122417E+10 | 77387.46 | 26-DEC-04:01 | -1.0 |
Annual Sum or Average | 0.532284E+10 | |||
Minimum of Months | 0.00 | 0.00 | -1.0 | |
Maximum of Months | 0.224471E+10 | 79331.63 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 6059299.16 | 9210.09 | 17-JAN-06:03 | 1.20 |
February | 56462.91 | 330.05 | 18-FEB-06:03 | -1.8 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 5.92 |
April | 0.00 | 0.00 | 01-APR-00:10 | 7.93 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 10.38 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 17.17 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 16.38 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 14.35 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 9.22 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 4.40 |
Annual Sum or Average | 6115762.06 | |||
Minimum of Months | 0.00 | 0.00 | -1.8 | |
Maximum of Months | 6059299.16 | 9210.09 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 14759181.00 | 6792.66 | 17-JAN-06:03 | 1.20 |
February | 3115236.39 | 5125.65 | 18-FEB-06:01 | -1.8 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 5.92 |
April | 0.00 | 0.00 | 01-APR-00:10 | 7.93 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 10.38 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 17.17 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 16.38 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 14.35 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 9.22 |
December | 861373.98 | 2142.27 | 22-DEC-06:01 | 0.60 |
Annual Sum or Average | 18735791.38 | |||
Minimum of Months | 0.00 | 0.00 | -1.8 | |
Maximum of Months | 14759181.00 | 6792.66 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 87365730.41 | 13315.61 | 17-JAN-05:01 | 1.60 |
February | 20007028.25 | 9923.15 | 18-FEB-06:01 | -1.8 |
March | 558554.22 | 4394.58 | 06-MAR-06:02 | 6.70 |
April | 0.00 | 0.00 | 01-APR-00:10 | 7.93 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 10.38 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 17.17 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 16.38 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 14.35 |
November | 2148093.59 | 9626.15 | 13-NOV-06:01 | 1.70 |
December | 17315076.92 | 9867.35 | 26-DEC-06:02 | -0.8 |
Annual Sum or Average | 0.127394E+09 | |||
Minimum of Months | 0.00 | 0.00 | -1.8 | |
Maximum of Months | 87365730.41 | 13315.61 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 603885.56 | 4025.90 | 17-JAN-06:03 | 1.20 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 7.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 5.92 |
April | 0.00 | 0.00 | 01-APR-00:10 | 7.93 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 10.38 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 17.17 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 16.38 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 14.35 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 9.22 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 4.40 |
Annual Sum or Average | 603885.56 | |||
Minimum of Months | 0.00 | 0.00 | 1.20 | |
Maximum of Months | 603885.56 | 4025.90 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.189895E+10 | 12855.99 | 02-JAN-05:11 | 6.10 |
February | 0.802243E+09 | 12361.03 | 21-FEB-04:51 | 1.70 |
March | 0.207594E+09 | 11314.10 | 06-MAR-05:11 | 6.70 |
April | 40696620.57 | 10665.87 | 11-APR-04:11 | 5.20 |
May | 1021282.27 | 6330.35 | 18-MAY-05:03 | 5.60 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 17.17 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 16.38 |
October | 50445720.28 | 10859.87 | 30-OCT-04:11 | 7.20 |
November | 0.381590E+09 | 11280.40 | 24-NOV-05:11 | 2.60 |
December | 0.109310E+10 | 12402.52 | 26-DEC-04:01 | -1.0 |
Annual Sum or Average | 0.447564E+10 | |||
Minimum of Months | 0.00 | 0.00 | -1.0 | |
Maximum of Months | 0.189895E+10 | 12855.99 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.125834E+10 | 17015.07 | 02-JAN-05:11 | 6.10 |
February | 0.492886E+09 | 16084.07 | 21-FEB-04:51 | 1.70 |
March | 0.129503E+09 | 14645.51 | 06-MAR-05:11 | 6.70 |
April | 29276270.82 | 13008.48 | 18-APR-05:02 | 3.30 |
May | 1908327.67 | 7121.78 | 18-MAY-05:03 | 5.60 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 17.17 |
September | 111381.96 | 742.55 | 27-SEP-05:05 | 7.38 |
October | 41229100.59 | 13256.55 | 28-OCT-05:02 | 8.22 |
November | 0.282455E+09 | 14615.54 | 24-NOV-05:11 | 2.60 |
December | 0.791146E+09 | 16296.56 | 26-DEC-04:01 | -1.0 |
Annual Sum or Average | 0.302685E+10 | |||
Minimum of Months | 0.00 | 0.00 | -1.0 | |
Maximum of Months | 0.125834E+10 | 17015.07 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.135288E+10 | 24696.36 | 02-JAN-05:11 | 6.10 |
February | 0.457938E+09 | 21813.44 | 21-FEB-05:01 | 1.70 |
March | 0.113381E+09 | 21130.88 | 06-MAR-05:11 | 6.70 |
April | 34062634.99 | 19010.79 | 18-APR-05:02 | 3.30 |
May | 2651261.33 | 10213.27 | 18-MAY-05:03 | 5.60 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 17.17 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 16.38 |
October | 25589458.73 | 19188.91 | 28-OCT-05:02 | 8.22 |
November | 0.281696E+09 | 20937.74 | 24-NOV-05:11 | 2.60 |
December | 0.818469E+09 | 23025.03 | 26-DEC-04:01 | -1.0 |
Annual Sum or Average | 0.308667E+10 | |||
Minimum of Months | 0.00 | 0.00 | -1.0 | |
Maximum of Months | 0.135288E+10 | 24696.36 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.812215E+09 | 16629.66 | 02-JAN-05:11 | 6.10 |
February | 0.305856E+09 | 14553.53 | 13-FEB-05:01 | 1.28 |
March | 66398933.50 | 13630.66 | 06-MAR-05:11 | 6.70 |
April | 12322983.45 | 10921.00 | 18-APR-05:02 | 3.30 |
May | 1276557.12 | 5633.28 | 18-MAY-05:03 | 5.60 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 17.17 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 16.38 |
October | 13617485.16 | 11019.33 | 28-OCT-05:02 | 8.22 |
November | 0.152079E+09 | 13569.91 | 30-NOV-05:11 | 5.60 |
December | 0.420097E+09 | 14339.47 | 26-DEC-05:01 | -0.6 |
Annual Sum or Average | 0.178386E+10 | |||
Minimum of Months | 0.00 | 0.00 | -0.6 | |
Maximum of Months | 0.812215E+09 | 16629.66 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.469596E+10 | 14607.16 | 16-JAN-02:33 | -1.5 |
February | 0.295982E+10 | 14891.14 | 19-FEB-07:23 | -5.0 |
March | 0.115972E+10 | 14343.73 | 06-MAR-05:11 | 6.70 |
April | 0.437609E+09 | 12965.86 | 11-APR-04:11 | 5.20 |
May | 50945584.48 | 12116.93 | 18-MAY-04:12 | 6.33 |
June | 2792431.26 | 8988.41 | 14-JUN-05:03 | 10.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 17.17 |
September | 14536840.09 | 11342.59 | 27-SEP-05:03 | 7.38 |
October | 0.534465E+09 | 13460.83 | 30-OCT-04:11 | 7.20 |
November | 0.179888E+10 | 14239.72 | 13-NOV-04:01 | 1.60 |
December | 0.364392E+10 | 14599.05 | 26-DEC-03:53 | -1.1 |
Annual Sum or Average | 0.152986E+11 | |||
Minimum of Months | 0.00 | 0.00 | -5.0 | |
Maximum of Months | 0.469596E+10 | 14891.14 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.292035E+10 | 19769.01 | 09-JAN-04:11 | 0.60 |
February | 0.165727E+10 | 19770.94 | 21-FEB-04:51 | 1.70 |
March | 0.659040E+09 | 19467.51 | 06-MAR-05:11 | 6.70 |
April | 0.237033E+09 | 17479.21 | 11-APR-04:11 | 5.20 |
May | 41245640.26 | 15218.89 | 18-MAY-04:12 | 6.33 |
June | 4304440.14 | 8409.04 | 14-JUN-05:03 | 10.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 17.17 |
September | 10150441.79 | 10024.92 | 27-SEP-05:03 | 7.38 |
October | 0.339682E+09 | 17805.31 | 30-OCT-04:11 | 7.20 |
November | 0.114190E+10 | 19284.86 | 27-NOV-05:11 | 12.03 |
December | 0.229333E+10 | 19513.35 | 18-DEC-05:11 | 3.50 |
Annual Sum or Average | 0.930431E+10 | |||
Minimum of Months | 0.00 | 0.00 | 0.60 | |
Maximum of Months | 0.292035E+10 | 19770.94 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.334330E+10 | 29276.64 | 02-JAN-05:11 | 6.10 |
February | 0.178462E+10 | 29164.27 | 21-FEB-04:51 | 1.70 |
March | 0.831439E+09 | 28832.80 | 06-MAR-05:11 | 6.70 |
April | 0.364397E+09 | 25672.72 | 11-APR-04:11 | 5.20 |
May | 62651607.98 | 23033.48 | 18-MAY-04:12 | 6.33 |
June | 5063907.19 | 10399.03 | 14-JUN-05:03 | 10.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 17.17 |
September | 11595989.84 | 11860.78 | 27-SEP-05:03 | 7.38 |
October | 0.362772E+09 | 25728.37 | 16-OCT-04:11 | 7.20 |
November | 0.135103E+10 | 28606.43 | 24-NOV-05:11 | 2.60 |
December | 0.274950E+10 | 28930.11 | 18-DEC-05:11 | 3.50 |
Annual Sum or Average | 0.108664E+11 | |||
Minimum of Months | 0.00 | 0.00 | 1.70 | |
Maximum of Months | 0.334330E+10 | 29276.64 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.214323E+10 | 19937.49 | 02-JAN-05:11 | 6.10 |
February | 0.108333E+10 | 19747.47 | 21-FEB-04:51 | 1.70 |
March | 0.455972E+09 | 19176.10 | 06-MAR-05:11 | 6.70 |
April | 0.161094E+09 | 16829.15 | 11-APR-04:11 | 5.20 |
May | 26141147.86 | 12035.29 | 18-MAY-04:12 | 6.33 |
June | 422314.54 | 2648.18 | 14-JUN-05:03 | 10.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 17.17 |
September | 1316092.69 | 1987.93 | 27-SEP-05:03 | 7.38 |
October | 0.191858E+09 | 16818.20 | 30-OCT-04:11 | 7.20 |
November | 0.721900E+09 | 18982.09 | 24-NOV-05:11 | 2.60 |
December | 0.145963E+10 | 19408.49 | 18-DEC-05:11 | 3.50 |
Annual Sum or Average | 0.624489E+10 | |||
Minimum of Months | 0.00 | 0.00 | 1.70 | |
Maximum of Months | 0.214323E+10 | 19937.49 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.173837E+09 | 11781.67 | 02-JAN-05:11 | 6.10 |
February | 89273338.17 | 10809.55 | 22-FEB-06:03 | 7.62 |
March | 69610684.00 | 11826.35 | 06-MAR-05:11 | 6.70 |
April | 0.122541E+09 | 12605.78 | 02-APR-13:52 | 18.90 |
May | 90832934.77 | 12133.62 | 14-MAY-15:11 | 23.30 |
June | 77537770.73 | 9649.28 | 26-JUN-04:11 | 12.80 |
July | 0.115024E+09 | 11291.98 | 30-JUL-15:41 | 27.70 |
August | 0.114641E+09 | 12561.85 | 06-AUG-15:11 | 23.73 |
September | 59769417.05 | 12376.72 | 10-SEP-14:31 | 22.60 |
October | 86419486.03 | 10773.98 | 23-OCT-04:11 | 10.60 |
November | 74243770.46 | 13026.35 | 27-NOV-05:11 | 12.03 |
December | 75487513.86 | 13203.41 | 28-DEC-05:11 | 9.07 |
Annual Sum or Average | 0.114922E+10 | |||
Minimum of Months | 59769417.05 | 9649.28 | 6.10 | |
Maximum of Months | 0.173837E+09 | 13203.41 | 27.70 |
Report: ZoneHeatingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.260595E+10 | 16863.53 | 02-JAN-06:03 | 6.10 |
February | 0.107217E+10 | 14158.69 | 12-FEB-13:12 | 6.30 |
March | 0.321768E+09 | 7270.98 | 15-MAR-05:02 | 8.03 |
April | 97590517.41 | 8046.79 | 02-APR-15:23 | 20.60 |
May | 79170679.59 | 11097.33 | 14-MAY-15:22 | 23.30 |
June | 56573690.58 | 7376.93 | 18-JUN-17:12 | 17.03 |
July | 79230088.84 | 12946.41 | 30-JUL-16:01 | 27.62 |
August | 60256963.22 | 13505.46 | 06-AUG-15:41 | 23.78 |
September | 50290646.15 | 13549.67 | 10-SEP-15:22 | 22.50 |
October | 0.148699E+09 | 11426.63 | 29-OCT-12:22 | 10.85 |
November | 0.526557E+09 | 11002.91 | 11-NOV-12:42 | 6.42 |
December | 0.115676E+10 | 4722.94 | 03-DEC-13:43 | 12.20 |
Annual Sum or Average | 0.625501E+10 | |||
Minimum of Months | 50290646.15 | 4722.94 | 6.10 | |
Maximum of Months | 0.260595E+10 | 16863.53 | 27.62 |
Report: ZoneHeatingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.758558E+10 | 27097.60 | 17-JAN-05:22 | 1.40 |
February | 0.472037E+10 | 21762.39 | 21-FEB-05:13 | 1.70 |
March | 0.247778E+10 | 18124.86 | 06-MAR-05:22 | 6.70 |
April | 0.119456E+10 | 13962.09 | 27-APR-05:03 | 9.37 |
May | 0.489450E+09 | 15056.20 | 04-MAY-05:03 | 10.78 |
June | 0.192895E+09 | 15765.76 | 02-JUN-05:03 | 10.18 |
July | 0.102428E+09 | 14117.32 | 07-JUL-05:03 | 11.47 |
August | 0.135284E+09 | 13989.51 | 22-AUG-05:03 | 13.02 |
September | 0.385961E+09 | 14767.41 | 08-SEP-05:02 | 10.18 |
October | 0.155946E+10 | 11181.83 | 05-OCT-05:03 | 8.30 |
November | 0.353314E+10 | 18940.01 | 13-NOV-06:12 | 1.70 |
December | 0.617846E+10 | 23754.27 | 26-DEC-05:22 | -0.6 |
Annual Sum or Average | 0.285554E+11 | |||
Minimum of Months | 0.102428E+09 | 11181.83 | -0.6 | |
Maximum of Months | 0.758558E+10 | 27097.60 | 13.02 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 5.92 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 7.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 5.92 |
April | 0.00 | 0.00 | 01-APR-00:10 | 7.93 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 10.38 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 17.17 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 16.38 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 14.35 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 9.22 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 4.40 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 4.40 | |
Maximum of Months | 0.00 | 0.00 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.299769E+09 | 580.99 | 03-JAN-01:00 | 7.20 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 7.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 5.92 |
April | 0.00 | 0.00 | 01-APR-00:10 | 7.93 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 10.38 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 17.17 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 16.38 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 14.35 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 9.22 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 4.40 |
Annual Sum or Average | 0.299769E+09 | |||
Minimum of Months | 0.00 | 0.00 | 4.40 | |
Maximum of Months | 0.299769E+09 | 580.99 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.741230E+09 | 648.74 | 08-JAN-17:25 | 2.75 |
February | 26177862.04 | 439.19 | 20-FEB-07:40 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 5.92 |
April | 0.00 | 0.00 | 01-APR-00:10 | 7.93 |
May | 1898028.06 | 387.45 | 29-MAY-07:35 | 10.40 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 17.17 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 16.38 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 14.35 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 9.22 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 4.40 |
Annual Sum or Average | 0.769306E+09 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.741230E+09 | 648.74 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 5.92 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 7.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 5.92 |
April | 0.00 | 0.00 | 01-APR-00:10 | 7.93 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 10.38 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 17.17 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 16.38 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 14.35 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 9.22 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 4.40 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 4.40 | |
Maximum of Months | 0.00 | 0.00 | 17.17 |
Report: ZoneElectricSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.219312E+11 | 22950.34 | 02-JAN-08:09 | 0.360447E+11 | 13457.54 | 01-JAN-00:10 |
February | 0.198933E+11 | 22950.34 | 01-FEB-08:09 | 0.325565E+11 | 13457.54 | 01-FEB-00:10 |
March | 0.236388E+11 | 22950.34 | 01-MAR-08:09 | 0.360447E+11 | 13457.54 | 01-MAR-00:10 |
April | 0.211142E+11 | 22950.34 | 03-APR-07:10 | 0.348820E+11 | 13457.54 | 01-APR-00:10 |
May | 0.227850E+11 | 22950.34 | 01-MAY-07:10 | 0.360447E+11 | 13457.54 | 01-MAY-00:10 |
June | 0.226748E+11 | 22950.34 | 01-JUN-07:10 | 0.348820E+11 | 13457.54 | 01-JUN-00:10 |
July | 0.212244E+11 | 22950.34 | 03-JUL-07:10 | 0.360447E+11 | 13457.54 | 01-JUL-00:10 |
August | 0.236388E+11 | 22950.34 | 01-AUG-07:10 | 0.360447E+11 | 13457.54 | 01-AUG-00:10 |
September | 0.211142E+11 | 22950.34 | 01-SEP-07:10 | 0.348820E+11 | 13457.54 | 01-SEP-00:10 |
October | 0.219312E+11 | 22950.34 | 02-OCT-07:10 | 0.360447E+11 | 13457.54 | 01-OCT-00:10 |
November | 0.216742E+11 | 22950.34 | 01-NOV-07:10 | 0.348820E+11 | 13457.54 | 01-NOV-00:10 |
December | 0.212244E+11 | 22950.34 | 01-DEC-08:09 | 0.360447E+11 | 13457.54 | 01-DEC-00:10 |
Annual Sum or Average | 0.262844E+12 | 0.424397E+12 | ||||
Minimum of Months | 0.198933E+11 | 22950.34 | 0.325565E+11 | 13457.54 | ||
Maximum of Months | 0.236388E+11 | 22950.34 | 0.360447E+11 | 13457.54 |
Report: ZoneElectricSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.196958E+11 | 20611.01 | 02-JAN-08:09 | 0.243681E+11 | 17206.63 | 02-JAN-08:09 |
February | 0.178655E+11 | 20611.01 | 01-FEB-08:09 | 0.220609E+11 | 17206.63 | 01-FEB-08:09 |
March | 0.212293E+11 | 20611.01 | 01-MAR-08:09 | 0.253549E+11 | 17206.63 | 01-MAR-08:09 |
April | 0.189620E+11 | 20611.01 | 03-APR-07:10 | 0.235306E+11 | 17206.63 | 03-APR-07:10 |
May | 0.204625E+11 | 20611.01 | 01-MAY-07:10 | 0.248615E+11 | 17206.63 | 01-MAY-07:10 |
June | 0.203636E+11 | 20611.01 | 01-JUN-07:10 | 0.244160E+11 | 17206.63 | 01-JUN-07:10 |
July | 0.190610E+11 | 20611.01 | 03-JUL-07:10 | 0.239708E+11 | 17206.63 | 03-JUL-07:10 |
August | 0.212293E+11 | 20611.01 | 01-AUG-07:10 | 0.253549E+11 | 17206.63 | 01-AUG-07:10 |
September | 0.189620E+11 | 20611.01 | 01-SEP-07:10 | 0.235199E+11 | 17206.63 | 01-SEP-07:10 |
October | 0.196958E+11 | 20611.01 | 02-OCT-07:10 | 0.243735E+11 | 17206.63 | 02-OCT-07:10 |
November | 0.194649E+11 | 20611.01 | 01-NOV-07:10 | 0.238373E+11 | 17206.63 | 01-NOV-07:10 |
December | 0.190610E+11 | 20611.01 | 01-DEC-08:09 | 0.239654E+11 | 17206.63 | 01-DEC-08:09 |
Annual Sum or Average | 0.236053E+12 | 0.289614E+12 | ||||
Minimum of Months | 0.178655E+11 | 20611.01 | 0.220609E+11 | 17206.63 | ||
Maximum of Months | 0.212293E+11 | 20611.01 | 0.253549E+11 | 17206.63 |
Report: ZoneElectricSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.196958E+11 | 20611.01 | 02-JAN-08:09 | 0.243680E+11 | 17206.56 | 02-JAN-08:09 |
February | 0.178655E+11 | 20611.01 | 01-FEB-08:09 | 0.220609E+11 | 17206.56 | 01-FEB-08:09 |
March | 0.212293E+11 | 20611.01 | 01-MAR-08:09 | 0.253548E+11 | 17206.56 | 01-MAR-08:09 |
April | 0.189620E+11 | 20611.01 | 03-APR-07:10 | 0.235305E+11 | 17206.56 | 03-APR-07:10 |
May | 0.204625E+11 | 20611.01 | 01-MAY-07:10 | 0.248614E+11 | 17206.56 | 01-MAY-07:10 |
June | 0.203636E+11 | 20611.01 | 01-JUN-07:10 | 0.244159E+11 | 17206.56 | 01-JUN-07:10 |
July | 0.190610E+11 | 20611.01 | 03-JUL-07:10 | 0.239707E+11 | 17206.56 | 03-JUL-07:10 |
August | 0.212293E+11 | 20611.01 | 01-AUG-07:10 | 0.253548E+11 | 17206.56 | 01-AUG-07:10 |
September | 0.189620E+11 | 20611.01 | 01-SEP-07:10 | 0.235198E+11 | 17206.56 | 01-SEP-07:10 |
October | 0.196958E+11 | 20611.01 | 02-OCT-07:10 | 0.243734E+11 | 17206.56 | 02-OCT-07:10 |
November | 0.194649E+11 | 20611.01 | 01-NOV-07:10 | 0.238372E+11 | 17206.56 | 01-NOV-07:10 |
December | 0.190610E+11 | 20611.01 | 01-DEC-08:09 | 0.239653E+11 | 17206.56 | 01-DEC-08:09 |
Annual Sum or Average | 0.236053E+12 | 0.289613E+12 | ||||
Minimum of Months | 0.178655E+11 | 20611.01 | 0.220609E+11 | 17206.56 | ||
Maximum of Months | 0.212293E+11 | 20611.01 | 0.253548E+11 | 17206.56 |
Report: ZoneElectricSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.196958E+11 | 20611.01 | 02-JAN-08:09 | 0.243680E+11 | 17206.56 | 02-JAN-08:09 |
February | 0.178655E+11 | 20611.01 | 01-FEB-08:09 | 0.220609E+11 | 17206.56 | 01-FEB-08:09 |
March | 0.212293E+11 | 20611.01 | 01-MAR-08:09 | 0.253548E+11 | 17206.56 | 01-MAR-08:09 |
April | 0.189620E+11 | 20611.01 | 03-APR-07:10 | 0.235305E+11 | 17206.56 | 03-APR-07:10 |
May | 0.204625E+11 | 20611.01 | 01-MAY-07:10 | 0.248614E+11 | 17206.56 | 01-MAY-07:10 |
June | 0.203636E+11 | 20611.01 | 01-JUN-07:10 | 0.244159E+11 | 17206.56 | 01-JUN-07:10 |
July | 0.190610E+11 | 20611.01 | 03-JUL-07:10 | 0.239707E+11 | 17206.56 | 03-JUL-07:10 |
August | 0.212293E+11 | 20611.01 | 01-AUG-07:10 | 0.253548E+11 | 17206.56 | 01-AUG-07:10 |
September | 0.189620E+11 | 20611.01 | 01-SEP-07:10 | 0.235198E+11 | 17206.56 | 01-SEP-07:10 |
October | 0.196958E+11 | 20611.01 | 02-OCT-07:10 | 0.243734E+11 | 17206.56 | 02-OCT-07:10 |
November | 0.194649E+11 | 20611.01 | 01-NOV-07:10 | 0.238372E+11 | 17206.56 | 01-NOV-07:10 |
December | 0.190610E+11 | 20611.01 | 01-DEC-08:09 | 0.239653E+11 | 17206.56 | 01-DEC-08:09 |
Annual Sum or Average | 0.236053E+12 | 0.289613E+12 | ||||
Minimum of Months | 0.178655E+11 | 20611.01 | 0.220609E+11 | 17206.56 | ||
Maximum of Months | 0.212293E+11 | 20611.01 | 0.253548E+11 | 17206.56 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.176859E+10 | 2587.92 | 02-JAN-08:09 | 0.305979E+10 | 2160.55 | 02-JAN-08:09 |
February | 0.143470E+10 | 2587.92 | 02-FEB-08:09 | 0.277008E+10 | 2160.55 | 01-FEB-08:09 |
March | 0.155823E+10 | 2255.20 | 13-MAR-07:10 | 0.318369E+10 | 2160.55 | 01-MAR-08:09 |
April | 0.131668E+10 | 1803.00 | 03-APR-07:10 | 0.295462E+10 | 2160.55 | 03-APR-07:10 |
May | 0.137806E+10 | 1350.81 | 01-MAY-07:10 | 0.312174E+10 | 2160.55 | 01-MAY-07:10 |
June | 0.134298E+10 | 1350.81 | 16-JUN-07:10 | 0.306580E+10 | 2160.55 | 01-JUN-07:10 |
July | 0.126733E+10 | 1470.28 | 12-JUL-07:19 | 0.300989E+10 | 2160.55 | 03-JUL-07:10 |
August | 0.143211E+10 | 1470.28 | 02-AUG-07:19 | 0.318369E+10 | 2160.55 | 01-AUG-07:10 |
September | 0.136165E+10 | 2255.20 | 21-SEP-07:10 | 0.295328E+10 | 2160.55 | 01-SEP-07:10 |
October | 0.153460E+10 | 2587.92 | 26-OCT-07:10 | 0.306046E+10 | 2160.55 | 02-OCT-07:10 |
November | 0.170078E+10 | 2587.92 | 01-NOV-07:10 | 0.299314E+10 | 2160.55 | 01-NOV-07:10 |
December | 0.177034E+10 | 2587.92 | 01-DEC-08:09 | 0.300922E+10 | 2160.55 | 01-DEC-08:09 |
Annual Sum or Average | 0.178660E+11 | 0.363654E+11 | ||||
Minimum of Months | 0.126733E+10 | 1350.81 | 0.277008E+10 | 2160.55 | ||
Maximum of Months | 0.177034E+10 | 2587.92 | 0.318369E+10 | 2160.55 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.109822E+10 | 1667.75 | 02-JAN-08:09 | 0.197184E+10 | 1392.34 | 02-JAN-08:09 |
February | 0.908478E+09 | 1667.75 | 01-FEB-16:00 | 0.178515E+10 | 1392.34 | 01-FEB-08:09 |
March | 0.996882E+09 | 1453.34 | 07-MAR-16:00 | 0.205169E+10 | 1392.34 | 01-MAR-08:09 |
April | 0.848371E+09 | 947.51 | 03-APR-07:10 | 0.190407E+10 | 1392.34 | 03-APR-07:10 |
May | 0.892399E+09 | 793.52 | 01-MAY-07:10 | 0.201177E+10 | 1392.34 | 01-MAY-07:10 |
June | 0.870760E+09 | 793.52 | 01-JUN-07:10 | 0.197572E+10 | 1392.34 | 01-JUN-07:10 |
July | 0.821084E+09 | 870.51 | 12-JUL-07:00 | 0.193969E+10 | 1392.34 | 03-JUL-07:10 |
August | 0.927712E+09 | 870.51 | 02-AUG-07:19 | 0.205169E+10 | 1392.34 | 01-AUG-07:10 |
September | 0.870073E+09 | 1453.34 | 21-SEP-07:10 | 0.190321E+10 | 1392.34 | 01-SEP-07:10 |
October | 0.970389E+09 | 1667.75 | 30-OCT-07:10 | 0.197228E+10 | 1392.34 | 02-OCT-07:10 |
November | 0.106696E+10 | 1667.75 | 01-NOV-07:10 | 0.192889E+10 | 1392.34 | 01-NOV-07:10 |
December | 0.109535E+10 | 1667.75 | 01-DEC-16:10 | 0.193926E+10 | 1392.34 | 01-DEC-08:09 |
Annual Sum or Average | 0.113667E+11 | 0.234352E+11 | ||||
Minimum of Months | 0.821084E+09 | 793.52 | 0.178515E+10 | 1392.34 | ||
Maximum of Months | 0.109822E+10 | 1667.75 | 0.205169E+10 | 1392.34 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.165491E+10 | 2587.98 | 02-JAN-08:09 | 0.305983E+10 | 2160.58 | 02-JAN-08:09 |
February | 0.137488E+10 | 2587.98 | 02-FEB-16:00 | 0.277013E+10 | 2160.58 | 01-FEB-08:09 |
March | 0.153538E+10 | 2255.25 | 16-MAR-07:10 | 0.318374E+10 | 2160.58 | 01-MAR-08:09 |
April | 0.131716E+10 | 1803.04 | 03-APR-07:10 | 0.295467E+10 | 2160.58 | 03-APR-07:10 |
May | 0.138625E+10 | 1350.84 | 01-MAY-07:10 | 0.312179E+10 | 2160.58 | 01-MAY-07:10 |
June | 0.135373E+10 | 1350.84 | 16-JUN-07:10 | 0.306585E+10 | 2160.58 | 01-JUN-07:10 |
July | 0.128198E+10 | 1470.31 | 12-JUL-07:19 | 0.300994E+10 | 2160.58 | 03-JUL-07:10 |
August | 0.144165E+10 | 1470.31 | 02-AUG-07:30 | 0.318374E+10 | 2160.58 | 01-AUG-07:10 |
September | 0.135156E+10 | 2255.25 | 21-SEP-07:10 | 0.295333E+10 | 2160.58 | 01-SEP-07:10 |
October | 0.148588E+10 | 2587.98 | 26-OCT-07:10 | 0.306051E+10 | 2160.58 | 02-OCT-07:10 |
November | 0.161328E+10 | 2587.98 | 01-NOV-07:10 | 0.299318E+10 | 2160.58 | 01-NOV-07:10 |
December | 0.164453E+10 | 2587.98 | 01-DEC-16:19 | 0.300927E+10 | 2160.58 | 01-DEC-08:09 |
Annual Sum or Average | 0.174412E+11 | 0.363660E+11 | ||||
Minimum of Months | 0.128198E+10 | 1350.84 | 0.277013E+10 | 2160.58 | ||
Maximum of Months | 0.165491E+10 | 2587.98 | 0.318374E+10 | 2160.58 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.109741E+10 | 1667.75 | 02-JAN-08:09 | 0.197183E+10 | 1392.33 | 02-JAN-08:09 |
February | 0.899363E+09 | 1667.75 | 02-FEB-08:09 | 0.178514E+10 | 1392.33 | 01-FEB-08:09 |
March | 0.996082E+09 | 1453.34 | 13-MAR-07:10 | 0.205168E+10 | 1392.33 | 01-MAR-08:09 |
April | 0.847990E+09 | 1161.92 | 03-APR-07:10 | 0.190406E+10 | 1392.33 | 03-APR-07:10 |
May | 0.889837E+09 | 870.51 | 01-MAY-07:10 | 0.201175E+10 | 1392.33 | 01-MAY-07:10 |
June | 0.867743E+09 | 870.51 | 06-JUN-07:10 | 0.197570E+10 | 1392.33 | 01-JUN-07:10 |
July | 0.822342E+09 | 1161.92 | 12-JUL-07:19 | 0.193968E+10 | 1392.33 | 03-JUL-07:10 |
August | 0.924337E+09 | 1161.92 | 28-AUG-07:10 | 0.205168E+10 | 1392.33 | 01-AUG-07:10 |
September | 0.876231E+09 | 1453.34 | 21-SEP-07:10 | 0.190319E+10 | 1392.33 | 01-SEP-07:10 |
October | 0.971296E+09 | 1667.75 | 20-OCT-07:10 | 0.197226E+10 | 1392.33 | 02-OCT-07:10 |
November | 0.106109E+10 | 1667.75 | 01-NOV-07:10 | 0.192888E+10 | 1392.33 | 01-NOV-07:10 |
December | 0.109414E+10 | 1667.75 | 01-DEC-08:09 | 0.193924E+10 | 1392.33 | 01-DEC-08:09 |
Annual Sum or Average | 0.113479E+11 | 0.234351E+11 | ||||
Minimum of Months | 0.822342E+09 | 870.51 | 0.178514E+10 | 1392.33 | ||
Maximum of Months | 0.109741E+10 | 1667.75 | 0.205168E+10 | 1392.33 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.175908E+10 | 2587.92 | 02-JAN-08:09 | 0.305979E+10 | 2160.55 | 02-JAN-08:09 |
February | 0.142918E+10 | 2587.92 | 02-FEB-08:09 | 0.277008E+10 | 2160.55 | 01-FEB-08:09 |
March | 0.155349E+10 | 2255.20 | 16-MAR-07:10 | 0.318369E+10 | 2160.55 | 01-MAR-08:09 |
April | 0.131492E+10 | 1803.00 | 03-APR-07:10 | 0.295462E+10 | 2160.55 | 03-APR-07:10 |
May | 0.137689E+10 | 1350.81 | 02-MAY-07:10 | 0.312174E+10 | 2160.55 | 01-MAY-07:10 |
June | 0.134168E+10 | 1350.81 | 16-JUN-07:10 | 0.306580E+10 | 2160.55 | 01-JUN-07:10 |
July | 0.126560E+10 | 1470.28 | 12-JUL-07:30 | 0.300989E+10 | 2160.55 | 03-JUL-07:10 |
August | 0.143058E+10 | 1470.28 | 02-AUG-07:30 | 0.318369E+10 | 2160.55 | 01-AUG-07:10 |
September | 0.135868E+10 | 2255.20 | 21-SEP-07:10 | 0.295328E+10 | 2160.55 | 01-SEP-07:10 |
October | 0.152804E+10 | 2587.92 | 26-OCT-07:10 | 0.306046E+10 | 2160.55 | 02-OCT-07:10 |
November | 0.169238E+10 | 2587.92 | 01-NOV-07:10 | 0.299314E+10 | 2160.55 | 01-NOV-07:10 |
December | 0.176333E+10 | 2587.92 | 01-DEC-08:09 | 0.300922E+10 | 2160.55 | 01-DEC-08:09 |
Annual Sum or Average | 0.178139E+11 | 0.363654E+11 | ||||
Minimum of Months | 0.126560E+10 | 1350.81 | 0.277008E+10 | 2160.55 | ||
Maximum of Months | 0.176333E+10 | 2587.92 | 0.318369E+10 | 2160.55 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.109398E+10 | 1667.75 | 02-JAN-08:09 | 0.197184E+10 | 1392.34 | 02-JAN-08:09 |
February | 0.906266E+09 | 1667.75 | 01-FEB-16:00 | 0.178515E+10 | 1392.34 | 01-FEB-08:09 |
March | 0.994516E+09 | 1453.34 | 07-MAR-16:00 | 0.205169E+10 | 1392.34 | 01-MAR-08:09 |
April | 0.847563E+09 | 870.51 | 03-APR-07:10 | 0.190407E+10 | 1392.34 | 03-APR-07:10 |
May | 0.891603E+09 | 793.52 | 01-MAY-07:10 | 0.201177E+10 | 1392.34 | 01-MAY-07:10 |
June | 0.870023E+09 | 793.52 | 01-JUN-07:10 | 0.197572E+10 | 1392.34 | 01-JUN-07:10 |
July | 0.820649E+09 | 870.51 | 12-JUL-07:00 | 0.193969E+10 | 1392.34 | 03-JUL-07:10 |
August | 0.926931E+09 | 870.51 | 02-AUG-07:30 | 0.205169E+10 | 1392.34 | 01-AUG-07:10 |
September | 0.868446E+09 | 1453.34 | 21-SEP-07:10 | 0.190321E+10 | 1392.34 | 01-SEP-07:10 |
October | 0.968176E+09 | 1667.75 | 30-OCT-07:10 | 0.197228E+10 | 1392.34 | 02-OCT-07:10 |
November | 0.106332E+10 | 1667.75 | 01-NOV-07:10 | 0.192889E+10 | 1392.34 | 01-NOV-07:10 |
December | 0.109189E+10 | 1667.75 | 01-DEC-16:10 | 0.193926E+10 | 1392.34 | 01-DEC-08:09 |
Annual Sum or Average | 0.113434E+11 | 0.234352E+11 | ||||
Minimum of Months | 0.820649E+09 | 793.52 | 0.178515E+10 | 1392.34 | ||
Maximum of Months | 0.109398E+10 | 1667.75 | 0.205169E+10 | 1392.34 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.165261E+10 | 2587.98 | 02-JAN-08:09 | 0.305983E+10 | 2160.58 | 02-JAN-08:09 |
February | 0.137260E+10 | 2587.98 | 02-FEB-16:00 | 0.277013E+10 | 2160.58 | 01-FEB-08:09 |
March | 0.153313E+10 | 2255.25 | 16-MAR-07:10 | 0.318374E+10 | 2160.58 | 01-MAR-08:09 |
April | 0.131589E+10 | 1803.04 | 03-APR-07:10 | 0.295467E+10 | 2160.58 | 03-APR-07:10 |
May | 0.138495E+10 | 1350.84 | 02-MAY-07:10 | 0.312179E+10 | 2160.58 | 01-MAY-07:10 |
June | 0.135274E+10 | 1350.84 | 16-JUN-07:10 | 0.306585E+10 | 2160.58 | 01-JUN-07:10 |
July | 0.128050E+10 | 1470.31 | 12-JUL-07:19 | 0.300994E+10 | 2160.58 | 03-JUL-07:10 |
August | 0.144022E+10 | 1470.31 | 02-AUG-07:30 | 0.318374E+10 | 2160.58 | 01-AUG-07:10 |
September | 0.135013E+10 | 2255.25 | 21-SEP-07:10 | 0.295333E+10 | 2160.58 | 01-SEP-07:10 |
October | 0.148397E+10 | 2587.98 | 26-OCT-07:10 | 0.306051E+10 | 2160.58 | 02-OCT-07:10 |
November | 0.161098E+10 | 2587.98 | 01-NOV-07:10 | 0.299318E+10 | 2160.58 | 01-NOV-07:10 |
December | 0.164164E+10 | 2587.98 | 01-DEC-16:19 | 0.300927E+10 | 2160.58 | 01-DEC-08:09 |
Annual Sum or Average | 0.174194E+11 | 0.363660E+11 | ||||
Minimum of Months | 0.128050E+10 | 1350.84 | 0.277013E+10 | 2160.58 | ||
Maximum of Months | 0.165261E+10 | 2587.98 | 0.318374E+10 | 2160.58 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.109391E+10 | 1667.75 | 02-JAN-08:09 | 0.197183E+10 | 1392.33 | 02-JAN-08:09 |
February | 0.897229E+09 | 1667.75 | 02-FEB-08:09 | 0.178514E+10 | 1392.33 | 01-FEB-08:09 |
March | 0.994312E+09 | 1453.34 | 13-MAR-07:10 | 0.205168E+10 | 1392.33 | 01-MAR-08:09 |
April | 0.847040E+09 | 1161.92 | 03-APR-07:10 | 0.190406E+10 | 1392.33 | 03-APR-07:10 |
May | 0.888904E+09 | 870.51 | 01-MAY-07:10 | 0.201175E+10 | 1392.33 | 01-MAY-07:10 |
June | 0.867055E+09 | 870.51 | 06-JUN-07:10 | 0.197570E+10 | 1392.33 | 01-JUN-07:10 |
July | 0.821230E+09 | 1161.92 | 12-JUL-07:19 | 0.193968E+10 | 1392.33 | 03-JUL-07:10 |
August | 0.923489E+09 | 1161.92 | 28-AUG-07:10 | 0.205168E+10 | 1392.33 | 01-AUG-07:10 |
September | 0.874568E+09 | 1453.34 | 21-SEP-07:10 | 0.190319E+10 | 1392.33 | 01-SEP-07:10 |
October | 0.969317E+09 | 1667.75 | 26-OCT-07:10 | 0.197226E+10 | 1392.33 | 02-OCT-07:10 |
November | 0.105797E+10 | 1667.75 | 01-NOV-07:10 | 0.192888E+10 | 1392.33 | 01-NOV-07:10 |
December | 0.109054E+10 | 1667.75 | 01-DEC-08:09 | 0.193924E+10 | 1392.33 | 01-DEC-08:09 |
Annual Sum or Average | 0.113256E+11 | 0.234351E+11 | ||||
Minimum of Months | 0.821230E+09 | 870.51 | 0.178514E+10 | 1392.33 | ||
Maximum of Months | 0.109391E+10 | 1667.75 | 0.205168E+10 | 1392.33 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.175818E+10 | 2587.92 | 02-JAN-08:09 | 0.305979E+10 | 2160.55 | 02-JAN-08:09 |
February | 0.142903E+10 | 2587.92 | 02-FEB-08:09 | 0.277008E+10 | 2160.55 | 01-FEB-08:09 |
March | 0.155323E+10 | 2255.20 | 16-MAR-07:10 | 0.318369E+10 | 2160.55 | 01-MAR-08:09 |
April | 0.131489E+10 | 1803.00 | 03-APR-07:10 | 0.295462E+10 | 2160.55 | 03-APR-07:10 |
May | 0.137680E+10 | 1350.81 | 02-MAY-07:10 | 0.312174E+10 | 2160.55 | 01-MAY-07:10 |
June | 0.134164E+10 | 1350.81 | 16-JUN-07:10 | 0.306580E+10 | 2160.55 | 01-JUN-07:10 |
July | 0.126552E+10 | 1470.28 | 12-JUL-07:30 | 0.300989E+10 | 2160.55 | 03-JUL-07:10 |
August | 0.143049E+10 | 1470.28 | 02-AUG-07:30 | 0.318369E+10 | 2160.55 | 01-AUG-07:10 |
September | 0.135863E+10 | 2255.20 | 21-SEP-07:10 | 0.295328E+10 | 2160.55 | 01-SEP-07:10 |
October | 0.152774E+10 | 2587.92 | 26-OCT-07:10 | 0.306046E+10 | 2160.55 | 02-OCT-07:10 |
November | 0.169216E+10 | 2587.92 | 01-NOV-07:10 | 0.299314E+10 | 2160.55 | 01-NOV-07:10 |
December | 0.176290E+10 | 2587.92 | 01-DEC-08:09 | 0.300922E+10 | 2160.55 | 01-DEC-08:09 |
Annual Sum or Average | 0.178112E+11 | 0.363654E+11 | ||||
Minimum of Months | 0.126552E+10 | 1350.81 | 0.277008E+10 | 2160.55 | ||
Maximum of Months | 0.176290E+10 | 2587.92 | 0.318369E+10 | 2160.55 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.109388E+10 | 1667.75 | 02-JAN-08:09 | 0.197184E+10 | 1392.34 | 02-JAN-08:09 |
February | 0.906199E+09 | 1667.75 | 01-FEB-16:00 | 0.178515E+10 | 1392.34 | 01-FEB-08:09 |
March | 0.994398E+09 | 1453.34 | 07-MAR-16:00 | 0.205169E+10 | 1392.34 | 01-MAR-08:09 |
April | 0.847538E+09 | 870.51 | 03-APR-07:10 | 0.190407E+10 | 1392.34 | 03-APR-07:10 |
May | 0.891569E+09 | 793.52 | 01-MAY-07:10 | 0.201177E+10 | 1392.34 | 01-MAY-07:10 |
June | 0.869983E+09 | 793.52 | 01-JUN-07:10 | 0.197572E+10 | 1392.34 | 01-JUN-07:10 |
July | 0.820649E+09 | 870.51 | 12-JUL-07:00 | 0.193969E+10 | 1392.34 | 03-JUL-07:10 |
August | 0.926902E+09 | 870.51 | 02-AUG-07:30 | 0.205169E+10 | 1392.34 | 01-AUG-07:10 |
September | 0.868468E+09 | 1453.34 | 25-SEP-07:10 | 0.190321E+10 | 1392.34 | 01-SEP-07:10 |
October | 0.968199E+09 | 1667.75 | 30-OCT-07:10 | 0.197228E+10 | 1392.34 | 02-OCT-07:10 |
November | 0.106318E+10 | 1667.75 | 01-NOV-07:10 | 0.192889E+10 | 1392.34 | 01-NOV-07:10 |
December | 0.109165E+10 | 1667.75 | 01-DEC-16:10 | 0.193926E+10 | 1392.34 | 01-DEC-08:09 |
Annual Sum or Average | 0.113426E+11 | 0.234352E+11 | ||||
Minimum of Months | 0.820649E+09 | 793.52 | 0.178515E+10 | 1392.34 | ||
Maximum of Months | 0.109388E+10 | 1667.75 | 0.205169E+10 | 1392.34 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.165227E+10 | 2587.98 | 02-JAN-08:09 | 0.305983E+10 | 2160.58 | 02-JAN-08:09 |
February | 0.137260E+10 | 2587.98 | 02-FEB-16:00 | 0.277013E+10 | 2160.58 | 01-FEB-08:09 |
March | 0.153301E+10 | 2255.25 | 16-MAR-07:10 | 0.318374E+10 | 2160.58 | 01-MAR-08:09 |
April | 0.131580E+10 | 1803.04 | 03-APR-07:10 | 0.295467E+10 | 2160.58 | 03-APR-07:10 |
May | 0.138488E+10 | 1350.84 | 02-MAY-07:10 | 0.312179E+10 | 2160.58 | 01-MAY-07:10 |
June | 0.135268E+10 | 1350.84 | 16-JUN-07:10 | 0.306585E+10 | 2160.58 | 01-JUN-07:10 |
July | 0.128048E+10 | 1470.31 | 12-JUL-07:19 | 0.300994E+10 | 2160.58 | 03-JUL-07:10 |
August | 0.144020E+10 | 1470.31 | 02-AUG-07:30 | 0.318374E+10 | 2160.58 | 01-AUG-07:10 |
September | 0.135013E+10 | 2255.25 | 21-SEP-07:10 | 0.295333E+10 | 2160.58 | 01-SEP-07:10 |
October | 0.148397E+10 | 2587.98 | 26-OCT-07:10 | 0.306051E+10 | 2160.58 | 02-OCT-07:10 |
November | 0.161070E+10 | 2587.98 | 01-NOV-07:10 | 0.299318E+10 | 2160.58 | 01-NOV-07:10 |
December | 0.164164E+10 | 2587.98 | 01-DEC-16:19 | 0.300927E+10 | 2160.58 | 01-DEC-08:09 |
Annual Sum or Average | 0.174184E+11 | 0.363660E+11 | ||||
Minimum of Months | 0.128048E+10 | 1350.84 | 0.277013E+10 | 2160.58 | ||
Maximum of Months | 0.165227E+10 | 2587.98 | 0.318374E+10 | 2160.58 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.109373E+10 | 1667.75 | 02-JAN-08:09 | 0.197183E+10 | 1392.33 | 02-JAN-08:09 |
February | 0.896946E+09 | 1667.75 | 02-FEB-08:09 | 0.178514E+10 | 1392.33 | 01-FEB-08:09 |
March | 0.994092E+09 | 1453.34 | 13-MAR-07:10 | 0.205168E+10 | 1392.33 | 01-MAR-08:09 |
April | 0.846952E+09 | 1161.92 | 03-APR-07:10 | 0.190406E+10 | 1392.33 | 03-APR-07:10 |
May | 0.888885E+09 | 870.51 | 01-MAY-07:10 | 0.201175E+10 | 1392.33 | 01-MAY-07:10 |
June | 0.867052E+09 | 870.51 | 06-JUN-07:10 | 0.197570E+10 | 1392.33 | 01-JUN-07:10 |
July | 0.821225E+09 | 1161.92 | 12-JUL-07:19 | 0.193968E+10 | 1392.33 | 03-JUL-07:10 |
August | 0.923489E+09 | 1161.92 | 28-AUG-07:10 | 0.205168E+10 | 1392.33 | 01-AUG-07:10 |
September | 0.874565E+09 | 1453.34 | 21-SEP-07:10 | 0.190319E+10 | 1392.33 | 01-SEP-07:10 |
October | 0.968885E+09 | 1667.75 | 26-OCT-07:10 | 0.197226E+10 | 1392.33 | 02-OCT-07:10 |
November | 0.105792E+10 | 1667.75 | 01-NOV-07:10 | 0.192888E+10 | 1392.33 | 01-NOV-07:10 |
December | 0.109036E+10 | 1667.75 | 01-DEC-08:09 | 0.193924E+10 | 1392.33 | 01-DEC-08:09 |
Annual Sum or Average | 0.113241E+11 | 0.234351E+11 | ||||
Minimum of Months | 0.821225E+09 | 870.51 | 0.178514E+10 | 1392.33 | ||
Maximum of Months | 0.109373E+10 | 1667.75 | 0.205168E+10 | 1392.33 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.553024E+09 | 578.72 | 02-JAN-08:09 | 0.521915E+10 | 1948.61 | 01-JAN-00:10 |
February | 0.501634E+09 | 578.72 | 01-FEB-08:09 | 0.942813E+10 | 3897.21 | 01-FEB-00:10 |
March | 0.596080E+09 | 578.72 | 01-MAR-08:09 | 0.156645E+11 | 7794.42 | 31-MAR-23:10 |
April | 0.532421E+09 | 578.72 | 03-APR-07:10 | 0.201821E+11 | 7794.42 | 01-APR-00:10 |
May | 0.574552E+09 | 578.72 | 01-MAY-07:10 | 0.522616E+10 | 3897.21 | 31-MAY-23:10 |
June | 0.571774E+09 | 578.72 | 01-JUN-07:10 | 0.101086E+11 | 5845.82 | 30-JUN-23:10 |
July | 0.535199E+09 | 578.72 | 03-JUL-07:10 | 0.156645E+11 | 7794.42 | 31-JUL-23:10 |
August | 0.596080E+09 | 578.72 | 01-AUG-07:10 | 0.208555E+11 | 7794.42 | 01-AUG-00:10 |
September | 0.532421E+09 | 578.72 | 01-SEP-07:10 | 0.505780E+10 | 3897.21 | 30-SEP-23:10 |
October | 0.553024E+09 | 578.72 | 02-OCT-07:10 | 0.104453E+11 | 5845.82 | 31-OCT-23:10 |
November | 0.546542E+09 | 578.72 | 01-NOV-07:10 | 0.151524E+11 | 5845.82 | 01-NOV-00:10 |
December | 0.535199E+09 | 578.72 | 01-DEC-08:09 | 0.208766E+11 | 7794.42 | 01-DEC-00:10 |
Annual Sum or Average | 0.662795E+10 | 0.153881E+12 | ||||
Minimum of Months | 0.501634E+09 | 578.72 | 0.505780E+10 | 1948.61 | ||
Maximum of Months | 0.596080E+09 | 578.72 | 0.208766E+11 | 7794.42 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.553024E+09 | 578.72 | 02-JAN-08:09 | 0.521915E+10 | 1948.61 | 01-JAN-00:10 |
February | 0.501634E+09 | 578.72 | 01-FEB-08:09 | 0.942813E+10 | 3897.21 | 01-FEB-00:10 |
March | 0.596080E+09 | 578.72 | 01-MAR-08:09 | 0.156645E+11 | 7794.42 | 31-MAR-23:10 |
April | 0.532421E+09 | 578.72 | 03-APR-07:10 | 0.201821E+11 | 7794.42 | 01-APR-00:10 |
May | 0.574552E+09 | 578.72 | 01-MAY-07:10 | 0.522616E+10 | 3897.21 | 31-MAY-23:10 |
June | 0.571774E+09 | 578.72 | 01-JUN-07:10 | 0.101086E+11 | 5845.82 | 30-JUN-23:10 |
July | 0.535199E+09 | 578.72 | 03-JUL-07:10 | 0.156645E+11 | 7794.42 | 31-JUL-23:10 |
August | 0.596080E+09 | 578.72 | 01-AUG-07:10 | 0.208555E+11 | 7794.42 | 01-AUG-00:10 |
September | 0.532421E+09 | 578.72 | 01-SEP-07:10 | 0.505780E+10 | 3897.21 | 30-SEP-23:10 |
October | 0.553024E+09 | 578.72 | 02-OCT-07:10 | 0.104453E+11 | 5845.82 | 31-OCT-23:10 |
November | 0.546542E+09 | 578.72 | 01-NOV-07:10 | 0.151524E+11 | 5845.82 | 01-NOV-00:10 |
December | 0.535199E+09 | 578.72 | 01-DEC-08:09 | 0.208766E+11 | 7794.42 | 01-DEC-00:10 |
Annual Sum or Average | 0.662795E+10 | 0.153881E+12 | ||||
Minimum of Months | 0.501634E+09 | 578.72 | 0.505780E+10 | 1948.61 | ||
Maximum of Months | 0.596080E+09 | 578.72 | 0.208766E+11 | 7794.42 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.553024E+09 | 578.72 | 02-JAN-08:09 | 0.521915E+10 | 1948.61 | 01-JAN-00:10 |
February | 0.501634E+09 | 578.72 | 01-FEB-08:09 | 0.942813E+10 | 3897.21 | 01-FEB-00:10 |
March | 0.596080E+09 | 578.72 | 01-MAR-08:09 | 0.156645E+11 | 7794.42 | 31-MAR-23:10 |
April | 0.532421E+09 | 578.72 | 03-APR-07:10 | 0.201821E+11 | 7794.42 | 01-APR-00:10 |
May | 0.574552E+09 | 578.72 | 01-MAY-07:10 | 0.522616E+10 | 3897.21 | 31-MAY-23:10 |
June | 0.571774E+09 | 578.72 | 01-JUN-07:10 | 0.101086E+11 | 5845.82 | 30-JUN-23:10 |
July | 0.535199E+09 | 578.72 | 03-JUL-07:10 | 0.156645E+11 | 7794.42 | 31-JUL-23:10 |
August | 0.596080E+09 | 578.72 | 01-AUG-07:10 | 0.208555E+11 | 7794.42 | 01-AUG-00:10 |
September | 0.532421E+09 | 578.72 | 01-SEP-07:10 | 0.505780E+10 | 3897.21 | 30-SEP-23:10 |
October | 0.553024E+09 | 578.72 | 02-OCT-07:10 | 0.104453E+11 | 5845.82 | 31-OCT-23:10 |
November | 0.546542E+09 | 578.72 | 01-NOV-07:10 | 0.151524E+11 | 5845.82 | 01-NOV-00:10 |
December | 0.535199E+09 | 578.72 | 01-DEC-08:09 | 0.208766E+11 | 7794.42 | 01-DEC-00:10 |
Annual Sum or Average | 0.662795E+10 | 0.153881E+12 | ||||
Minimum of Months | 0.501634E+09 | 578.72 | 0.505780E+10 | 1948.61 | ||
Maximum of Months | 0.596080E+09 | 578.72 | 0.208766E+11 | 7794.42 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.618367E+10 | 6471.01 | 02-JAN-08:09 | 0.254202E+12 | 94908.13 | 01-JAN-00:10 |
February | 0.560905E+10 | 6471.01 | 01-FEB-08:09 | 0.459203E+12 | 189816.26 | 01-FEB-00:10 |
March | 0.666512E+10 | 6471.01 | 01-MAR-08:09 | 0.762947E+12 | 379632.52 | 31-MAR-23:10 |
April | 0.595330E+10 | 6471.01 | 03-APR-07:10 | 0.982982E+12 | 379632.52 | 01-APR-00:10 |
May | 0.642439E+10 | 6471.01 | 01-MAY-07:10 | 0.254544E+12 | 189816.26 | 31-MAY-23:10 |
June | 0.639333E+10 | 6471.01 | 01-JUN-07:10 | 0.492345E+12 | 284724.39 | 30-JUN-23:10 |
July | 0.598436E+10 | 6471.01 | 03-JUL-07:10 | 0.762947E+12 | 379632.52 | 31-JUL-23:10 |
August | 0.666512E+10 | 6471.01 | 01-AUG-07:10 | 0.101578E+13 | 379632.52 | 01-AUG-00:10 |
September | 0.595330E+10 | 6471.01 | 01-SEP-07:10 | 0.246344E+12 | 189816.26 | 30-SEP-23:10 |
October | 0.618367E+10 | 6471.01 | 02-OCT-07:10 | 0.508746E+12 | 284724.39 | 31-OCT-23:10 |
November | 0.611120E+10 | 6471.01 | 01-NOV-07:10 | 0.738006E+12 | 284724.39 | 01-NOV-00:10 |
December | 0.598436E+10 | 6471.01 | 01-DEC-08:09 | 0.101681E+13 | 379632.52 | 01-DEC-00:10 |
Annual Sum or Average | 0.741109E+11 | 0.749486E+13 | ||||
Minimum of Months | 0.560905E+10 | 6471.01 | 0.246344E+12 | 94908.13 | ||
Maximum of Months | 0.666512E+10 | 6471.01 | 0.101681E+13 | 379632.52 |
Report: SpaceGainsMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.133902E+11 | 0.219312E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.121482E+11 | 0.198933E+11 | 0.325565E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.145160E+11 | 0.236388E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.128805E+11 | 0.211142E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.139531E+11 | 0.227850E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.139143E+11 | 0.226748E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.129193E+11 | 0.212244E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.145160E+11 | 0.236388E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.128805E+11 | 0.211142E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.133902E+11 | 0.219312E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.132595E+11 | 0.216742E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.129193E+11 | 0.212244E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.160687E+12 | 0.262844E+12 | 0.424397E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.121482E+11 | 0.198933E+11 | 0.325565E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.145160E+11 | 0.236388E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.120254E+11 | 0.196958E+11 | 0.243681E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.109099E+11 | 0.178655E+11 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.130364E+11 | 0.212293E+11 | 0.253549E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.115676E+11 | 0.189620E+11 | 0.235306E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.125309E+11 | 0.204625E+11 | 0.248615E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.124961E+11 | 0.203636E+11 | 0.244160E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.116025E+11 | 0.190610E+11 | 0.239708E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.130364E+11 | 0.212293E+11 | 0.253549E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.115676E+11 | 0.189620E+11 | 0.235199E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.120254E+11 | 0.196958E+11 | 0.243735E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.119080E+11 | 0.194649E+11 | 0.238373E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.116025E+11 | 0.190610E+11 | 0.239654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.144308E+12 | 0.236053E+12 | 0.289614E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.109099E+11 | 0.178655E+11 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.130364E+11 | 0.212293E+11 | 0.253549E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.120254E+11 | 0.196958E+11 | 0.243680E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.109099E+11 | 0.178655E+11 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.130364E+11 | 0.212293E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.115676E+11 | 0.189620E+11 | 0.235305E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.125309E+11 | 0.204625E+11 | 0.248614E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.124961E+11 | 0.203636E+11 | 0.244159E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.116025E+11 | 0.190610E+11 | 0.239707E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.130364E+11 | 0.212293E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.115676E+11 | 0.189620E+11 | 0.235198E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.120254E+11 | 0.196958E+11 | 0.243734E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.119080E+11 | 0.194649E+11 | 0.238372E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.116025E+11 | 0.190610E+11 | 0.239653E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.144308E+12 | 0.236053E+12 | 0.289613E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.109099E+11 | 0.178655E+11 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.130364E+11 | 0.212293E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.120254E+11 | 0.196958E+11 | 0.243680E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.109099E+11 | 0.178655E+11 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.130364E+11 | 0.212293E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.115676E+11 | 0.189620E+11 | 0.235305E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.125309E+11 | 0.204625E+11 | 0.248614E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.124961E+11 | 0.203636E+11 | 0.244159E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.116025E+11 | 0.190610E+11 | 0.239707E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.130364E+11 | 0.212293E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.115676E+11 | 0.189620E+11 | 0.235198E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.120254E+11 | 0.196958E+11 | 0.243734E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.119080E+11 | 0.194649E+11 | 0.238372E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.116025E+11 | 0.190610E+11 | 0.239653E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.144308E+12 | 0.236053E+12 | 0.289613E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.109099E+11 | 0.178655E+11 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.130364E+11 | 0.212293E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150991E+10 | 0.176859E+10 | 0.305979E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.795925E+09 |
February | 0.136985E+10 | 0.143470E+10 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.709926E+09 |
March | 0.163685E+10 | 0.155823E+10 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.685672E+09 |
April | 0.145243E+10 | 0.131668E+10 | 0.295462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 928164.11 | 0.651247E+09 |
May | 0.157338E+10 | 0.137806E+10 | 0.312174E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 38450.03 | 0.497602E+09 |
June | 0.156900E+10 | 0.134298E+10 | 0.306580E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 386370.49 | 0.413613E+09 |
July | 0.145680E+10 | 0.126733E+10 | 0.300989E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4771791.18 | 0.345637E+09 |
August | 0.163685E+10 | 0.143211E+10 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8224856.68 | 0.278548E+09 |
September | 0.145243E+10 | 0.136165E+10 | 0.295328E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 38315.59 | 0.232486E+09 |
October | 0.150991E+10 | 0.153460E+10 | 0.306046E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.549554E+09 |
November | 0.149516E+10 | 0.170078E+10 | 0.299314E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.638008E+09 |
December | 0.145680E+10 | 0.177034E+10 | 0.300922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.694815E+09 |
Annual Sum or Average | 0.181194E+11 | 0.178660E+11 | 0.363654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 14387948.08 | 0.649303E+10 |
Minimum of Months | 0.136985E+10 | 0.126733E+10 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.232486E+09 |
Maximum of Months | 0.163685E+10 | 0.177034E+10 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8224856.68 | 0.795925E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.109822E+10 | 0.197184E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.518729E+09 |
February | 0.882782E+09 | 0.908478E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.464837E+09 |
March | 0.105485E+10 | 0.996882E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.442750E+09 |
April | 0.936002E+09 | 0.848371E+09 | 0.190407E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 774347.00 | 0.419052E+09 |
May | 0.101394E+10 | 0.892399E+09 | 0.201177E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 25632.55 | 0.326198E+09 |
June | 0.101113E+10 | 0.870760E+09 | 0.197572E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 257575.08 | 0.270244E+09 |
July | 0.938820E+09 | 0.821084E+09 | 0.193969E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3206128.07 | 0.218804E+09 |
August | 0.105485E+10 | 0.927712E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5538066.82 | 0.172929E+09 |
September | 0.936002E+09 | 0.870073E+09 | 0.190321E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 25542.39 | 0.151795E+09 |
October | 0.973041E+09 | 0.970389E+09 | 0.197228E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.353901E+09 |
November | 0.963541E+09 | 0.106696E+10 | 0.192889E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.404865E+09 |
December | 0.938820E+09 | 0.109535E+10 | 0.193926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.441883E+09 |
Annual Sum or Average | 0.116768E+11 | 0.113667E+11 | 0.234352E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 9827291.92 | 0.418599E+10 |
Minimum of Months | 0.882782E+09 | 0.821084E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.151795E+09 |
Maximum of Months | 0.105485E+10 | 0.109822E+10 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5538066.82 | 0.518729E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150994E+10 | 0.165491E+10 | 0.305983E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.769314E+09 |
February | 0.136988E+10 | 0.137488E+10 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.713125E+09 |
March | 0.163688E+10 | 0.153538E+10 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.676785E+09 |
April | 0.145246E+10 | 0.131716E+10 | 0.295467E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 829004.52 | 0.641528E+09 |
May | 0.157341E+10 | 0.138625E+10 | 0.312179E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 38445.68 | 0.493073E+09 |
June | 0.156904E+10 | 0.135373E+10 | 0.306585E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 386352.35 | 0.409043E+09 |
July | 0.145684E+10 | 0.128198E+10 | 0.300994E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3687023.94 | 0.340818E+09 |
August | 0.163688E+10 | 0.144165E+10 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7906996.61 | 0.275017E+09 |
September | 0.145246E+10 | 0.135156E+10 | 0.295333E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 38153.21 | 0.236631E+09 |
October | 0.150994E+10 | 0.148588E+10 | 0.306051E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.547593E+09 |
November | 0.149520E+10 | 0.161328E+10 | 0.299318E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.614291E+09 |
December | 0.145684E+10 | 0.164453E+10 | 0.300927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.670899E+09 |
Annual Sum or Average | 0.181198E+11 | 0.174412E+11 | 0.363660E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 12885976.30 | 0.638812E+10 |
Minimum of Months | 0.136988E+10 | 0.128198E+10 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.236631E+09 |
Maximum of Months | 0.163688E+10 | 0.165491E+10 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7906996.61 | 0.769314E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.109741E+10 | 0.197183E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.548619E+09 |
February | 0.882782E+09 | 0.899363E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.508966E+09 |
March | 0.105485E+10 | 0.996082E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.500895E+09 |
April | 0.936002E+09 | 0.847990E+09 | 0.190406E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 347247.53 | 0.485682E+09 |
May | 0.101394E+10 | 0.889837E+09 | 0.201175E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 25632.54 | 0.356823E+09 |
June | 0.101113E+10 | 0.867743E+09 | 0.197570E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 257564.12 | 0.303506E+09 |
July | 0.938820E+09 | 0.822342E+09 | 0.193968E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2198609.95 | 0.265959E+09 |
August | 0.105485E+10 | 0.924337E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5221686.60 | 0.217627E+09 |
September | 0.936002E+09 | 0.876231E+09 | 0.190319E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 25539.78 | 0.170420E+09 |
October | 0.973041E+09 | 0.971296E+09 | 0.197226E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.398272E+09 |
November | 0.963541E+09 | 0.106109E+10 | 0.192888E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.464188E+09 |
December | 0.938820E+09 | 0.109414E+10 | 0.193924E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.514408E+09 |
Annual Sum or Average | 0.116768E+11 | 0.113479E+11 | 0.234351E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 8076280.53 | 0.473537E+10 |
Minimum of Months | 0.882782E+09 | 0.822342E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.170420E+09 |
Maximum of Months | 0.105485E+10 | 0.109741E+10 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5221686.60 | 0.548619E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150991E+10 | 0.175908E+10 | 0.305979E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.156273E+10 |
February | 0.136985E+10 | 0.142918E+10 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.140940E+10 |
March | 0.163685E+10 | 0.155349E+10 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.138346E+10 |
April | 0.145243E+10 | 0.131492E+10 | 0.295462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3190377.51 | 0.133186E+10 |
May | 0.157338E+10 | 0.137689E+10 | 0.312174E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 64017.88 | 0.107297E+10 |
June | 0.156900E+10 | 0.134168E+10 | 0.306580E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 795789.47 | 0.893211E+09 |
July | 0.145680E+10 | 0.126560E+10 | 0.300989E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13861552.06 | 0.750518E+09 |
August | 0.163685E+10 | 0.143058E+10 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19723077.33 | 0.611374E+09 |
September | 0.145243E+10 | 0.135868E+10 | 0.295328E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 67131.71 | 0.494862E+09 |
October | 0.150991E+10 | 0.152804E+10 | 0.306046E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.110478E+10 |
November | 0.149516E+10 | 0.169238E+10 | 0.299314E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.124570E+10 |
December | 0.145680E+10 | 0.176333E+10 | 0.300922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.134548E+10 |
Annual Sum or Average | 0.181194E+11 | 0.178139E+11 | 0.363654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 37701945.96 | 0.132063E+11 |
Minimum of Months | 0.136985E+10 | 0.126560E+10 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.494862E+09 |
Maximum of Months | 0.163685E+10 | 0.176333E+10 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19723077.33 | 0.156273E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.715730E+09 | 0.109398E+10 | 0.197184E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.104022E+10 |
February | 0.649041E+09 | 0.906266E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.955582E+09 |
March | 0.773965E+09 | 0.994516E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.927120E+09 |
April | 0.688021E+09 | 0.847563E+09 | 0.190407E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2072378.27 | 0.900189E+09 |
May | 0.744847E+09 | 0.891603E+09 | 0.201177E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 42662.68 | 0.715854E+09 |
June | 0.742030E+09 | 0.870023E+09 | 0.197572E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 530486.58 | 0.601891E+09 |
July | 0.690839E+09 | 0.820649E+09 | 0.193969E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6938979.10 | 0.500089E+09 |
August | 0.773965E+09 | 0.926931E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12394058.51 | 0.412402E+09 |
September | 0.688021E+09 | 0.868446E+09 | 0.190321E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 44857.33 | 0.329821E+09 |
October | 0.715730E+09 | 0.968176E+09 | 0.197228E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.736971E+09 |
November | 0.708685E+09 | 0.106332E+10 | 0.192889E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.823232E+09 |
December | 0.690839E+09 | 0.109189E+10 | 0.193926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.895586E+09 |
Annual Sum or Average | 0.858171E+10 | 0.113434E+11 | 0.234352E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 22023422.47 | 0.883895E+10 |
Minimum of Months | 0.649041E+09 | 0.820649E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.329821E+09 |
Maximum of Months | 0.773965E+09 | 0.109398E+10 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12394058.51 | 0.104022E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150994E+10 | 0.165261E+10 | 0.305983E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.163208E+10 |
February | 0.136988E+10 | 0.137260E+10 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.154946E+10 |
March | 0.163688E+10 | 0.153313E+10 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.146867E+10 |
April | 0.145246E+10 | 0.131589E+10 | 0.295467E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1872990.93 | 0.139569E+10 |
May | 0.157341E+10 | 0.138495E+10 | 0.312179E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 64006.47 | 0.109858E+10 |
June | 0.156904E+10 | 0.135274E+10 | 0.306585E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 795734.74 | 0.903595E+09 |
July | 0.145684E+10 | 0.128050E+10 | 0.300994E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8020687.45 | 0.767667E+09 |
August | 0.163688E+10 | 0.144022E+10 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17759966.67 | 0.638334E+09 |
September | 0.145246E+10 | 0.135013E+10 | 0.295333E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 66318.31 | 0.530852E+09 |
October | 0.150994E+10 | 0.148397E+10 | 0.306051E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.119831E+10 |
November | 0.149520E+10 | 0.161098E+10 | 0.299318E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.129795E+10 |
December | 0.145684E+10 | 0.164164E+10 | 0.300927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.141339E+10 |
Annual Sum or Average | 0.181198E+11 | 0.174194E+11 | 0.363660E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 28579704.57 | 0.138946E+11 |
Minimum of Months | 0.136988E+10 | 0.128050E+10 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.530852E+09 |
Maximum of Months | 0.163688E+10 | 0.165261E+10 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17759966.67 | 0.163208E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.109391E+10 | 0.197183E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.106869E+10 |
February | 0.882782E+09 | 0.897229E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.986036E+09 |
March | 0.105485E+10 | 0.994312E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.961957E+09 |
April | 0.936002E+09 | 0.847040E+09 | 0.190406E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 784445.42 | 0.935077E+09 |
May | 0.101394E+10 | 0.888904E+09 | 0.201175E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 42617.76 | 0.759081E+09 |
June | 0.101113E+10 | 0.867055E+09 | 0.197570E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 530418.16 | 0.626239E+09 |
July | 0.938820E+09 | 0.821230E+09 | 0.193968E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5899211.90 | 0.554339E+09 |
August | 0.105485E+10 | 0.923489E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12314987.26 | 0.450290E+09 |
September | 0.936002E+09 | 0.874568E+09 | 0.190319E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 44745.88 | 0.357110E+09 |
October | 0.973041E+09 | 0.969317E+09 | 0.197226E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.769021E+09 |
November | 0.963541E+09 | 0.105797E+10 | 0.192888E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.851175E+09 |
December | 0.938820E+09 | 0.109054E+10 | 0.193924E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.928034E+09 |
Annual Sum or Average | 0.116768E+11 | 0.113256E+11 | 0.234351E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 19616426.38 | 0.924705E+10 |
Minimum of Months | 0.882782E+09 | 0.821230E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.357110E+09 |
Maximum of Months | 0.105485E+10 | 0.109391E+10 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12314987.26 | 0.106869E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150991E+10 | 0.175818E+10 | 0.305979E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.182654E+10 |
February | 0.136985E+10 | 0.142903E+10 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.162468E+10 |
March | 0.163685E+10 | 0.155323E+10 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.157494E+10 |
April | 0.145243E+10 | 0.131489E+10 | 0.295462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3876118.05 | 0.153671E+10 |
May | 0.157338E+10 | 0.137680E+10 | 0.312174E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 51954.70 | 0.126466E+10 |
June | 0.156900E+10 | 0.134164E+10 | 0.306580E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 861555.54 | 0.107547E+10 |
July | 0.145680E+10 | 0.126552E+10 | 0.300989E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14272009.63 | 0.907870E+09 |
August | 0.163685E+10 | 0.143049E+10 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23004414.30 | 0.734651E+09 |
September | 0.145243E+10 | 0.135863E+10 | 0.295328E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 57893.70 | 0.577086E+09 |
October | 0.150991E+10 | 0.152774E+10 | 0.306046E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.123886E+10 |
November | 0.149516E+10 | 0.169216E+10 | 0.299314E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.139857E+10 |
December | 0.145680E+10 | 0.176290E+10 | 0.300922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.152049E+10 |
Annual Sum or Average | 0.181194E+11 | 0.178112E+11 | 0.363654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 42123945.91 | 0.152805E+11 |
Minimum of Months | 0.136985E+10 | 0.126552E+10 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.577086E+09 |
Maximum of Months | 0.163685E+10 | 0.176290E+10 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23004414.30 | 0.182654E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.109388E+10 | 0.197184E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.121711E+10 |
February | 0.882782E+09 | 0.906199E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.109656E+10 |
March | 0.105485E+10 | 0.994398E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.106561E+10 |
April | 0.936002E+09 | 0.847538E+09 | 0.190407E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2358696.60 | 0.105068E+10 |
May | 0.101394E+10 | 0.891569E+09 | 0.201177E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 34633.75 | 0.854074E+09 |
June | 0.101113E+10 | 0.869983E+09 | 0.197572E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 574349.19 | 0.733046E+09 |
July | 0.938820E+09 | 0.820649E+09 | 0.193969E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7078630.26 | 0.611141E+09 |
August | 0.105485E+10 | 0.926902E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14416365.96 | 0.501521E+09 |
September | 0.936002E+09 | 0.868468E+09 | 0.190321E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 38591.39 | 0.391244E+09 |
October | 0.973041E+09 | 0.968199E+09 | 0.197228E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.840398E+09 |
November | 0.963541E+09 | 0.106318E+10 | 0.192889E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.932135E+09 |
December | 0.938820E+09 | 0.109165E+10 | 0.193926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.101600E+10 |
Annual Sum or Average | 0.116768E+11 | 0.113426E+11 | 0.234352E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 24501267.16 | 0.103095E+11 |
Minimum of Months | 0.882782E+09 | 0.820649E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.391244E+09 |
Maximum of Months | 0.105485E+10 | 0.109388E+10 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14416365.96 | 0.121711E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150994E+10 | 0.165227E+10 | 0.305983E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.188443E+10 |
February | 0.136988E+10 | 0.137260E+10 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.176557E+10 |
March | 0.163688E+10 | 0.153301E+10 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.169014E+10 |
April | 0.145246E+10 | 0.131580E+10 | 0.295467E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2204139.01 | 0.162706E+10 |
May | 0.157341E+10 | 0.138488E+10 | 0.312179E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 51943.38 | 0.130421E+10 |
June | 0.156904E+10 | 0.135268E+10 | 0.306585E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 861503.15 | 0.109093E+10 |
July | 0.145684E+10 | 0.128048E+10 | 0.300994E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8947778.68 | 0.931445E+09 |
August | 0.163688E+10 | 0.144020E+10 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21104381.56 | 0.769799E+09 |
September | 0.145246E+10 | 0.135013E+10 | 0.295333E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 57252.33 | 0.628182E+09 |
October | 0.150994E+10 | 0.148397E+10 | 0.306051E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.137319E+10 |
November | 0.149520E+10 | 0.161070E+10 | 0.299318E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.147029E+10 |
December | 0.145684E+10 | 0.164164E+10 | 0.300927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.160271E+10 |
Annual Sum or Average | 0.181198E+11 | 0.174184E+11 | 0.363660E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 33226998.12 | 0.161380E+11 |
Minimum of Months | 0.136988E+10 | 0.128048E+10 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.628182E+09 |
Maximum of Months | 0.163688E+10 | 0.165227E+10 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21104381.56 | 0.188443E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.109373E+10 | 0.197183E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.124902E+10 |
February | 0.882782E+09 | 0.896946E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.114205E+10 |
March | 0.105485E+10 | 0.994092E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.111882E+10 |
April | 0.936002E+09 | 0.846952E+09 | 0.190406E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 921939.10 | 0.109827E+10 |
May | 0.101394E+10 | 0.888885E+09 | 0.201175E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 34634.53 | 0.906414E+09 |
June | 0.101113E+10 | 0.867052E+09 | 0.197570E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 574239.12 | 0.757909E+09 |
July | 0.938820E+09 | 0.821225E+09 | 0.193968E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6677379.65 | 0.674396E+09 |
August | 0.105485E+10 | 0.923489E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14633133.58 | 0.544305E+09 |
September | 0.936002E+09 | 0.874565E+09 | 0.190319E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 38590.34 | 0.424977E+09 |
October | 0.973041E+09 | 0.968885E+09 | 0.197226E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.888582E+09 |
November | 0.963541E+09 | 0.105792E+10 | 0.192888E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.980307E+09 |
December | 0.938820E+09 | 0.109036E+10 | 0.193924E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.106655E+10 |
Annual Sum or Average | 0.116768E+11 | 0.113241E+11 | 0.234351E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 22879916.31 | 0.108516E+11 |
Minimum of Months | 0.882782E+09 | 0.821225E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.424977E+09 |
Maximum of Months | 0.105485E+10 | 0.109373E+10 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14633133.58 | 0.124902E+10 |
Report: SpaceGainsMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.174411E+09 | 0.553024E+09 | 0.521915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.158233E+09 | 0.501634E+09 | 0.942813E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.189074E+09 | 0.596080E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.167772E+09 | 0.532421E+09 | 0.201821E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.181743E+09 | 0.574552E+09 | 0.522616E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.181238E+09 | 0.571774E+09 | 0.101086E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.168277E+09 | 0.535199E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.189074E+09 | 0.596080E+09 | 0.208555E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.167772E+09 | 0.532421E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.174411E+09 | 0.553024E+09 | 0.104453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.172708E+09 | 0.546542E+09 | 0.151524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.168277E+09 | 0.535199E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.209299E+10 | 0.662795E+10 | 0.153881E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.158233E+09 | 0.501634E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.189074E+09 | 0.596080E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.174411E+09 | 0.553024E+09 | 0.521915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.158233E+09 | 0.501634E+09 | 0.942813E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.189074E+09 | 0.596080E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.167772E+09 | 0.532421E+09 | 0.201821E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.181743E+09 | 0.574552E+09 | 0.522616E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.181238E+09 | 0.571774E+09 | 0.101086E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.168277E+09 | 0.535199E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.189074E+09 | 0.596080E+09 | 0.208555E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.167772E+09 | 0.532421E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.174411E+09 | 0.553024E+09 | 0.104453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.172708E+09 | 0.546542E+09 | 0.151524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.168277E+09 | 0.535199E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.209299E+10 | 0.662795E+10 | 0.153881E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.158233E+09 | 0.501634E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.189074E+09 | 0.596080E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.174411E+09 | 0.553024E+09 | 0.521915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.158233E+09 | 0.501634E+09 | 0.942813E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.189074E+09 | 0.596080E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.167772E+09 | 0.532421E+09 | 0.201821E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.181743E+09 | 0.574552E+09 | 0.522616E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.181238E+09 | 0.571774E+09 | 0.101086E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.168277E+09 | 0.535199E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.189074E+09 | 0.596080E+09 | 0.208555E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.167772E+09 | 0.532421E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.174411E+09 | 0.553024E+09 | 0.104453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.172708E+09 | 0.546542E+09 | 0.151524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.168277E+09 | 0.535199E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.209299E+10 | 0.662795E+10 | 0.153881E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.158233E+09 | 0.501634E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.189074E+09 | 0.596080E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.377547E+10 | 0.618367E+10 | 0.254202E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.342526E+10 | 0.560905E+10 | 0.459203E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.409289E+10 | 0.666512E+10 | 0.762947E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.363176E+10 | 0.595330E+10 | 0.982982E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.393418E+10 | 0.642439E+10 | 0.254544E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.392325E+10 | 0.639333E+10 | 0.492345E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.364269E+10 | 0.598436E+10 | 0.762947E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.409289E+10 | 0.666512E+10 | 0.101578E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.363176E+10 | 0.595330E+10 | 0.246344E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.377547E+10 | 0.618367E+10 | 0.508746E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.373861E+10 | 0.611120E+10 | 0.738006E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.364269E+10 | 0.598436E+10 | 0.101681E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.453069E+11 | 0.741109E+11 | 0.749486E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.342526E+10 | 0.560905E+10 | 0.246344E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.409289E+10 | 0.666512E+10 | 0.101681E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.173085E+10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.153864E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.146967E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1384575.61 | 0.137948E+10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4637.46 | 0.105476E+10 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 297899.56 | 0.871089E+09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7822009.38 | 0.729189E+09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13137060.12 | 0.602089E+09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2547.24 | 0.498834E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.118125E+10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.136823E+10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.150065E+10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22648729.39 | 0.139247E+11 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.498834E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13137060.12 | 0.173085E+10 |
Report: SpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.275186E+10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.253820E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.246977E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3640039.34 | 0.232248E+10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7828.63 | 0.182887E+10 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 554004.76 | 0.150479E+10 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17375790.46 | 0.125893E+10 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24639156.97 | 0.104843E+10 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3691.76 | 0.863295E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.198484E+10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.224300E+10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.243198E+10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46220511.91 | 0.232465E+11 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.863295E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24639156.97 | 0.275186E+10 |
Report: SpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.281178E+10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.257740E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.255539E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2759688.13 | 0.248885E+10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.203283E+10 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 164313.78 | 0.171680E+10 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5830959.67 | 0.144981E+10 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17738732.73 | 0.117917E+10 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.936884E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.203602E+10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.224913E+10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.241159E+10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26493694.31 | 0.244456E+11 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.936884E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17738732.73 | 0.281178E+10 |
Report: PeakSpaceGainsMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 17832.21 | 02-JAN-10:09 | 22950.34 | 02-JAN-08:09 | 13457.54 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 17832.21 | 01-FEB-10:09 | 22950.34 | 01-FEB-08:09 | 13457.54 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 17832.21 | 01-MAR-10:09 | 22950.34 | 01-MAR-08:09 | 13457.54 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 17832.21 | 03-APR-09:09 | 22950.34 | 03-APR-07:10 | 13457.54 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 17832.21 | 01-MAY-09:09 | 22950.34 | 01-MAY-07:10 | 13457.54 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 17832.21 | 01-JUN-09:09 | 22950.34 | 01-JUN-07:10 | 13457.54 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 17832.21 | 03-JUL-09:09 | 22950.34 | 03-JUL-07:10 | 13457.54 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 17832.21 | 01-AUG-09:09 | 22950.34 | 01-AUG-07:10 | 13457.54 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 17832.21 | 01-SEP-09:09 | 22950.34 | 01-SEP-07:10 | 13457.54 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 17832.21 | 02-OCT-09:09 | 22950.34 | 02-OCT-07:10 | 13457.54 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 17832.21 | 01-NOV-09:09 | 22950.34 | 01-NOV-07:10 | 13457.54 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 17832.21 | 01-DEC-10:09 | 22950.34 | 01-DEC-08:09 | 13457.54 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 17832.21 | 22950.34 | 13457.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 17832.21 | 22950.34 | 13457.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 16014.58 | 02-JAN-10:09 | 20611.01 | 02-JAN-08:09 | 17206.63 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 16014.58 | 01-FEB-10:09 | 20611.01 | 01-FEB-08:09 | 17206.63 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 16014.58 | 01-MAR-10:09 | 20611.01 | 01-MAR-08:09 | 17206.63 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 16014.58 | 03-APR-09:09 | 20611.01 | 03-APR-07:10 | 17206.63 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 16014.58 | 01-MAY-09:09 | 20611.01 | 01-MAY-07:10 | 17206.63 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 16014.58 | 01-JUN-09:09 | 20611.01 | 01-JUN-07:10 | 17206.63 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 16014.58 | 03-JUL-09:09 | 20611.01 | 03-JUL-07:10 | 17206.63 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 16014.58 | 01-AUG-09:09 | 20611.01 | 01-AUG-07:10 | 17206.63 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 16014.58 | 01-SEP-09:09 | 20611.01 | 01-SEP-07:10 | 17206.63 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 16014.58 | 02-OCT-09:09 | 20611.01 | 02-OCT-07:10 | 17206.63 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 16014.58 | 01-NOV-09:09 | 20611.01 | 01-NOV-07:10 | 17206.63 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 16014.58 | 01-DEC-10:09 | 20611.01 | 01-DEC-08:09 | 17206.63 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 16014.58 | 20611.01 | 17206.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 16014.58 | 20611.01 | 17206.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 16014.58 | 02-JAN-10:09 | 20611.01 | 02-JAN-08:09 | 17206.56 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 16014.58 | 01-FEB-10:09 | 20611.01 | 01-FEB-08:09 | 17206.56 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 16014.58 | 01-MAR-10:09 | 20611.01 | 01-MAR-08:09 | 17206.56 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 16014.58 | 03-APR-09:09 | 20611.01 | 03-APR-07:10 | 17206.56 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 16014.58 | 01-MAY-09:09 | 20611.01 | 01-MAY-07:10 | 17206.56 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 16014.58 | 01-JUN-09:09 | 20611.01 | 01-JUN-07:10 | 17206.56 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 16014.58 | 03-JUL-09:09 | 20611.01 | 03-JUL-07:10 | 17206.56 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 16014.58 | 01-AUG-09:09 | 20611.01 | 01-AUG-07:10 | 17206.56 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 16014.58 | 01-SEP-09:09 | 20611.01 | 01-SEP-07:10 | 17206.56 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 16014.58 | 02-OCT-09:09 | 20611.01 | 02-OCT-07:10 | 17206.56 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 16014.58 | 01-NOV-09:09 | 20611.01 | 01-NOV-07:10 | 17206.56 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 16014.58 | 01-DEC-10:09 | 20611.01 | 01-DEC-08:09 | 17206.56 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 16014.58 | 20611.01 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 16014.58 | 20611.01 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 16014.58 | 02-JAN-10:09 | 20611.01 | 02-JAN-08:09 | 17206.56 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 16014.58 | 01-FEB-10:09 | 20611.01 | 01-FEB-08:09 | 17206.56 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 16014.58 | 01-MAR-10:09 | 20611.01 | 01-MAR-08:09 | 17206.56 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 16014.58 | 03-APR-09:09 | 20611.01 | 03-APR-07:10 | 17206.56 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 16014.58 | 01-MAY-09:09 | 20611.01 | 01-MAY-07:10 | 17206.56 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 16014.58 | 01-JUN-09:09 | 20611.01 | 01-JUN-07:10 | 17206.56 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 16014.58 | 03-JUL-09:09 | 20611.01 | 03-JUL-07:10 | 17206.56 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 16014.58 | 01-AUG-09:09 | 20611.01 | 01-AUG-07:10 | 17206.56 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 16014.58 | 01-SEP-09:09 | 20611.01 | 01-SEP-07:10 | 17206.56 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 16014.58 | 02-OCT-09:09 | 20611.01 | 02-OCT-07:10 | 17206.56 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 16014.58 | 01-NOV-09:09 | 20611.01 | 01-NOV-07:10 | 17206.56 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 16014.58 | 01-DEC-10:09 | 20611.01 | 01-DEC-08:09 | 17206.56 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 16014.58 | 20611.01 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 16014.58 | 20611.01 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.79 | 02-JAN-10:09 | 2587.92 | 02-JAN-08:09 | 2160.55 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 1289.94 | 28-JAN-04:00 |
February | 2010.79 | 01-FEB-10:09 | 2587.92 | 02-FEB-08:09 | 2160.55 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1212.44 | 16-FEB-04:00 |
March | 2010.79 | 01-MAR-10:09 | 2255.20 | 13-MAR-07:10 | 2160.55 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1139.79 | 28-MAR-24:00 |
April | 2010.79 | 03-APR-09:09 | 1803.00 | 03-APR-07:10 | 2160.55 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 104.00 | 01-APR-17:01 | 1174.13 | 07-APR-24:00 |
May | 2010.79 | 01-MAY-09:09 | 1350.81 | 01-MAY-07:10 | 2160.55 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4.56 | 05-MAY-16:00 | 844.56 | 18-MAY-05:00 |
June | 2010.79 | 01-JUN-09:09 | 1350.81 | 16-JUN-07:10 | 2160.55 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 16.91 | 28-JUN-16:00 | 1143.58 | 13-JUN-03:00 |
July | 2010.79 | 03-JUL-09:09 | 1470.28 | 12-JUL-07:19 | 2160.55 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 115.03 | 23-JUL-16:00 | 588.50 | 02-JUL-04:00 |
August | 2010.79 | 01-AUG-09:09 | 1470.28 | 02-AUG-07:19 | 2160.55 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 67.24 | 08-AUG-17:00 | 767.86 | 11-AUG-04:00 |
September | 2010.79 | 01-SEP-09:09 | 2255.20 | 21-SEP-07:10 | 2160.55 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.45 | 14-SEP-17:00 | 559.03 | 18-SEP-23:00 |
October | 2010.79 | 02-OCT-09:09 | 2587.92 | 26-OCT-07:10 | 2160.55 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 1025.99 | 31-OCT-21:10 |
November | 2010.79 | 01-NOV-09:09 | 2587.92 | 01-NOV-07:10 | 2160.55 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1239.29 | 29-NOV-23:00 |
December | 2010.79 | 01-DEC-10:09 | 2587.92 | 01-DEC-08:09 | 2160.55 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1016.59 | 17-DEC-20:55 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.79 | 1350.81 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 559.03 | |||||
Maximum of Months | 2010.79 | 2587.92 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 115.03 | 1289.94 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 1667.75 | 02-JAN-08:09 | 1392.34 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 835.41 | 28-JAN-04:00 |
February | 1295.83 | 01-FEB-10:09 | 1667.75 | 01-FEB-16:00 | 1392.34 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 798.89 | 19-FEB-10:00 |
March | 1295.83 | 01-MAR-10:09 | 1453.34 | 07-MAR-16:00 | 1392.34 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 745.40 | 28-MAR-24:00 |
April | 1295.83 | 03-APR-09:09 | 947.51 | 03-APR-07:10 | 1392.34 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 93.69 | 01-APR-17:10 | 766.42 | 07-APR-24:00 |
May | 1295.83 | 01-MAY-09:09 | 793.52 | 01-MAY-07:10 | 1392.34 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3.04 | 05-MAY-16:00 | 547.40 | 18-MAY-05:00 |
June | 1295.83 | 01-JUN-09:09 | 793.52 | 01-JUN-07:10 | 1392.34 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11.27 | 28-JUN-16:00 | 742.22 | 13-JUN-03:00 |
July | 1295.83 | 03-JUL-09:09 | 870.51 | 12-JUL-07:00 | 1392.34 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 85.01 | 23-JUL-16:00 | 376.13 | 02-JUL-04:00 |
August | 1295.83 | 01-AUG-09:09 | 870.51 | 02-AUG-07:19 | 1392.34 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 49.96 | 13-AUG-15:20 | 489.72 | 11-AUG-04:00 |
September | 1295.83 | 01-SEP-09:09 | 1453.34 | 21-SEP-07:10 | 1392.34 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3.63 | 14-SEP-17:00 | 360.95 | 18-SEP-23:00 |
October | 1295.83 | 02-OCT-09:09 | 1667.75 | 30-OCT-07:10 | 1392.34 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 644.68 | 31-OCT-21:10 |
November | 1295.83 | 01-NOV-09:09 | 1667.75 | 01-NOV-07:10 | 1392.34 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 790.05 | 29-NOV-23:00 |
December | 1295.83 | 01-DEC-10:09 | 1667.75 | 01-DEC-16:10 | 1392.34 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 650.23 | 17-DEC-20:55 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 793.52 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 360.95 | |||||
Maximum of Months | 1295.83 | 1667.75 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 93.69 | 835.41 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.83 | 02-JAN-10:09 | 2587.98 | 02-JAN-08:09 | 2160.58 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 1235.15 | 12-JAN-24:00 |
February | 2010.83 | 01-FEB-10:09 | 2587.98 | 02-FEB-16:00 | 2160.58 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1280.21 | 19-FEB-11:57 |
March | 2010.83 | 01-MAR-10:09 | 2255.25 | 16-MAR-07:10 | 2160.58 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1147.04 | 28-MAR-24:00 |
April | 2010.83 | 03-APR-09:09 | 1803.04 | 03-APR-07:10 | 2160.58 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 83.13 | 01-APR-17:10 | 1166.29 | 07-APR-24:00 |
May | 2010.83 | 01-MAY-09:09 | 1350.84 | 01-MAY-07:10 | 2160.58 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4.56 | 05-MAY-16:00 | 822.95 | 22-MAY-24:00 |
June | 2010.83 | 01-JUN-09:09 | 1350.84 | 16-JUN-07:10 | 2160.58 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 16.91 | 28-JUN-16:00 | 1109.05 | 13-JUN-03:00 |
July | 2010.83 | 03-JUL-09:09 | 1470.31 | 12-JUL-07:19 | 2160.58 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 94.04 | 23-JUL-15:36 | 574.89 | 02-JUL-04:00 |
August | 2010.83 | 01-AUG-09:09 | 1470.31 | 02-AUG-07:30 | 2160.58 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 67.24 | 08-AUG-17:00 | 775.36 | 11-AUG-04:00 |
September | 2010.83 | 01-SEP-09:09 | 2255.25 | 21-SEP-07:10 | 2160.58 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.45 | 14-SEP-17:00 | 539.97 | 18-SEP-23:00 |
October | 2010.83 | 02-OCT-09:09 | 2587.98 | 26-OCT-07:10 | 2160.58 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 968.49 | 31-OCT-21:10 |
November | 2010.83 | 01-NOV-09:09 | 2587.98 | 01-NOV-07:10 | 2160.58 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1185.65 | 29-NOV-23:00 |
December | 2010.83 | 01-DEC-10:09 | 2587.98 | 01-DEC-16:19 | 2160.58 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 943.39 | 02-DEC-21:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.83 | 1350.84 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 539.97 | |||||
Maximum of Months | 2010.83 | 2587.98 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 94.04 | 1280.21 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 1667.75 | 02-JAN-08:09 | 1392.33 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 896.64 | 28-JAN-04:00 |
February | 1295.83 | 01-FEB-10:09 | 1667.75 | 02-FEB-08:09 | 1392.33 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 860.14 | 16-FEB-04:00 |
March | 1295.83 | 01-MAR-10:09 | 1453.34 | 13-MAR-07:10 | 1392.33 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 843.41 | 28-MAR-24:00 |
April | 1295.83 | 03-APR-09:09 | 1161.92 | 03-APR-07:10 | 1392.33 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 26.63 | 01-APR-16:00 | 877.53 | 07-APR-24:00 |
May | 1295.83 | 01-MAY-09:09 | 870.51 | 01-MAY-07:10 | 1392.33 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3.04 | 05-MAY-16:00 | 590.39 | 22-MAY-24:00 |
June | 1295.83 | 01-JUN-09:09 | 870.51 | 06-JUN-07:10 | 1392.33 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11.27 | 28-JUN-16:00 | 829.35 | 13-JUN-03:00 |
July | 1295.83 | 03-JUL-09:09 | 1161.92 | 12-JUL-07:19 | 1392.33 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 42.39 | 23-JUL-14:14 | 455.42 | 02-JUL-04:00 |
August | 1295.83 | 01-AUG-09:09 | 1161.92 | 28-AUG-07:10 | 1392.33 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 44.83 | 08-AUG-17:00 | 608.55 | 04-AUG-24:00 |
September | 1295.83 | 01-SEP-09:09 | 1453.34 | 21-SEP-07:10 | 1392.33 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3.63 | 14-SEP-17:00 | 395.16 | 18-SEP-23:00 |
October | 1295.83 | 02-OCT-09:09 | 1667.75 | 20-OCT-07:10 | 1392.33 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 711.24 | 31-OCT-21:10 |
November | 1295.83 | 01-NOV-09:09 | 1667.75 | 01-NOV-07:10 | 1392.33 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 893.30 | 29-NOV-23:00 |
December | 1295.83 | 01-DEC-10:09 | 1667.75 | 01-DEC-08:09 | 1392.33 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 757.83 | 17-DEC-20:55 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 870.51 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 395.16 | |||||
Maximum of Months | 1295.83 | 1667.75 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 44.83 | 896.64 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.79 | 02-JAN-10:09 | 2587.92 | 02-JAN-08:09 | 2160.55 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 2577.36 | 12-JAN-24:00 |
February | 2010.79 | 01-FEB-10:09 | 2587.92 | 02-FEB-08:09 | 2160.55 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 2349.05 | 16-FEB-04:00 |
March | 2010.79 | 01-MAR-10:09 | 2255.20 | 16-MAR-07:10 | 2160.55 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 2258.55 | 28-MAR-24:00 |
April | 2010.79 | 03-APR-09:09 | 1803.00 | 03-APR-07:10 | 2160.55 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 382.84 | 01-APR-17:01 | 2391.71 | 07-APR-24:00 |
May | 2010.79 | 01-MAY-09:09 | 1350.81 | 02-MAY-07:10 | 2160.55 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9.54 | 05-MAY-16:00 | 1769.43 | 22-MAY-24:00 |
June | 2010.79 | 01-JUN-09:09 | 1350.81 | 16-JUN-07:10 | 2160.55 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 37.60 | 28-JUN-16:00 | 2312.64 | 13-JUN-03:00 |
July | 2010.79 | 03-JUL-09:09 | 1470.28 | 12-JUL-07:30 | 2160.55 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 366.91 | 23-JUL-16:00 | 1191.57 | 02-JUL-04:00 |
August | 2010.79 | 01-AUG-09:09 | 1470.28 | 02-AUG-07:30 | 2160.55 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 183.60 | 13-AUG-15:00 | 1685.35 | 11-AUG-03:55 |
September | 2010.79 | 01-SEP-09:09 | 2255.20 | 21-SEP-07:10 | 2160.55 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11.39 | 14-SEP-17:00 | 1167.52 | 18-SEP-23:00 |
October | 2010.79 | 02-OCT-09:09 | 2587.92 | 26-OCT-07:10 | 2160.55 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 2163.60 | 31-OCT-21:03 |
November | 2010.79 | 01-NOV-09:09 | 2587.92 | 01-NOV-07:10 | 2160.55 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 2452.48 | 29-NOV-23:00 |
December | 2010.79 | 01-DEC-10:09 | 2587.92 | 01-DEC-08:09 | 2160.55 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1983.60 | 22-DEC-23:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.79 | 1350.81 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1167.52 | |||||
Maximum of Months | 2010.79 | 2587.92 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 382.84 | 2577.36 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1239.33 | 02-JAN-08:09 | 1667.75 | 02-JAN-08:09 | 1392.34 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 1696.59 | 12-JAN-24:00 |
February | 1239.33 | 01-FEB-08:09 | 1667.75 | 01-FEB-16:00 | 1392.34 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1613.16 | 19-FEB-10:00 |
March | 1239.33 | 01-MAR-08:09 | 1453.34 | 07-MAR-16:00 | 1392.34 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1530.08 | 28-MAR-24:00 |
April | 1239.33 | 03-APR-07:10 | 870.51 | 03-APR-07:10 | 1392.34 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 252.52 | 01-APR-17:01 | 1620.34 | 07-APR-24:00 |
May | 1239.33 | 01-MAY-07:10 | 793.52 | 01-MAY-07:10 | 1392.34 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6.36 | 05-MAY-16:00 | 1166.58 | 22-MAY-24:00 |
June | 1239.33 | 01-JUN-07:10 | 793.52 | 01-JUN-07:10 | 1392.34 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 25.07 | 28-JUN-16:00 | 1525.61 | 13-JUN-03:00 |
July | 1239.33 | 03-JUL-07:10 | 870.51 | 12-JUL-07:00 | 1392.34 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 199.77 | 23-JUL-16:00 | 801.61 | 02-JUL-10:20 |
August | 1239.33 | 01-AUG-07:10 | 870.51 | 02-AUG-07:30 | 1392.34 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 116.90 | 13-AUG-14:56 | 1144.66 | 11-AUG-03:55 |
September | 1239.33 | 01-SEP-07:10 | 1453.34 | 21-SEP-07:10 | 1392.34 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7.59 | 14-SEP-17:00 | 748.80 | 18-SEP-23:00 |
October | 1239.33 | 02-OCT-07:10 | 1667.75 | 30-OCT-07:10 | 1392.34 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 1438.03 | 31-OCT-21:03 |
November | 1239.33 | 01-NOV-07:10 | 1667.75 | 01-NOV-07:10 | 1392.34 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1621.16 | 29-NOV-23:00 |
December | 1239.33 | 01-DEC-08:09 | 1667.75 | 01-DEC-16:10 | 1392.34 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1315.03 | 22-DEC-23:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1239.33 | 793.52 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 748.80 | |||||
Maximum of Months | 1239.33 | 1667.75 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 252.52 | 1696.59 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.83 | 02-JAN-10:09 | 2587.98 | 02-JAN-08:09 | 2160.58 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 2577.95 | 12-JAN-24:00 |
February | 2010.83 | 01-FEB-10:09 | 2587.98 | 02-FEB-16:00 | 2160.58 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 2873.24 | 19-FEB-12:10 |
March | 2010.83 | 01-MAR-10:09 | 2255.25 | 16-MAR-07:10 | 2160.58 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 2404.40 | 28-MAR-24:00 |
April | 2010.83 | 03-APR-09:09 | 1803.04 | 03-APR-07:10 | 2160.58 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 189.17 | 01-APR-17:10 | 2451.23 | 07-APR-24:00 |
May | 2010.83 | 01-MAY-09:09 | 1350.84 | 02-MAY-07:10 | 2160.58 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9.54 | 05-MAY-16:00 | 1771.53 | 22-MAY-24:00 |
June | 2010.83 | 01-JUN-09:09 | 1350.84 | 16-JUN-07:10 | 2160.58 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 37.60 | 28-JUN-16:00 | 2282.32 | 13-JUN-03:00 |
July | 2010.83 | 03-JUL-09:09 | 1470.31 | 12-JUL-07:19 | 2160.58 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 237.18 | 23-JUL-15:54 | 1209.89 | 02-JUL-04:00 |
August | 2010.83 | 01-AUG-09:09 | 1470.31 | 02-AUG-07:30 | 2160.58 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 154.74 | 08-AUG-17:00 | 1752.84 | 11-AUG-03:55 |
September | 2010.83 | 01-SEP-09:09 | 2255.25 | 21-SEP-07:10 | 2160.58 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11.39 | 14-SEP-17:00 | 1154.60 | 18-SEP-23:00 |
October | 2010.83 | 02-OCT-09:09 | 2587.98 | 26-OCT-07:10 | 2160.58 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 2161.42 | 31-OCT-21:03 |
November | 2010.83 | 01-NOV-09:09 | 2587.98 | 01-NOV-07:10 | 2160.58 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 2451.35 | 29-NOV-23:00 |
December | 2010.83 | 01-DEC-10:09 | 2587.98 | 01-DEC-16:19 | 2160.58 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 2008.34 | 22-DEC-23:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.83 | 1350.84 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1154.60 | |||||
Maximum of Months | 2010.83 | 2587.98 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 237.18 | 2873.24 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 1667.75 | 02-JAN-08:09 | 1392.33 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 1724.40 | 12-JAN-24:00 |
February | 1295.83 | 01-FEB-10:09 | 1667.75 | 02-FEB-08:09 | 1392.33 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1579.28 | 16-FEB-04:00 |
March | 1295.83 | 01-MAR-10:09 | 1453.34 | 13-MAR-07:10 | 1392.33 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1559.18 | 28-MAR-24:00 |
April | 1295.83 | 03-APR-09:09 | 1161.92 | 03-APR-07:10 | 1392.33 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 60.33 | 01-APR-16:00 | 1614.28 | 07-APR-24:00 |
May | 1295.83 | 01-MAY-09:09 | 870.51 | 01-MAY-07:10 | 1392.33 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6.36 | 05-MAY-16:00 | 1224.98 | 27-MAY-17:40 |
June | 1295.83 | 01-JUN-09:09 | 870.51 | 06-JUN-07:10 | 1392.33 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 25.06 | 28-JUN-16:00 | 1536.82 | 13-JUN-03:00 |
July | 1295.83 | 03-JUL-09:09 | 1161.92 | 12-JUL-07:19 | 1392.33 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 157.41 | 23-JUL-13:20 | 846.74 | 02-JUL-04:00 |
August | 1295.83 | 01-AUG-09:09 | 1161.92 | 28-AUG-07:10 | 1392.33 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 104.75 | 13-AUG-12:20 | 1231.76 | 11-AUG-03:55 |
September | 1295.83 | 01-SEP-09:09 | 1453.34 | 21-SEP-07:10 | 1392.33 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7.59 | 14-SEP-17:00 | 768.11 | 18-SEP-23:00 |
October | 1295.83 | 02-OCT-09:09 | 1667.75 | 26-OCT-07:10 | 1392.33 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 1442.90 | 31-OCT-21:03 |
November | 1295.83 | 01-NOV-09:09 | 1667.75 | 01-NOV-07:10 | 1392.33 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1652.18 | 29-NOV-23:00 |
December | 1295.83 | 01-DEC-10:09 | 1667.75 | 01-DEC-08:09 | 1392.33 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1344.27 | 22-DEC-23:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 870.51 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 768.11 | |||||
Maximum of Months | 1295.83 | 1667.75 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 157.41 | 1724.40 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.79 | 02-JAN-10:09 | 2587.92 | 02-JAN-08:09 | 2160.55 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 3106.88 | 12-JAN-22:03 |
February | 2010.79 | 01-FEB-10:09 | 2587.92 | 02-FEB-08:09 | 2160.55 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 2904.14 | 16-FEB-22:03 |
March | 2010.79 | 01-MAR-10:09 | 2255.20 | 16-MAR-07:10 | 2160.55 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 2822.28 | 29-MAR-05:00 |
April | 2010.79 | 03-APR-09:09 | 1803.00 | 03-APR-07:10 | 2160.55 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 482.98 | 01-APR-17:01 | 2905.48 | 10-APR-21:03 |
May | 2010.79 | 01-MAY-09:09 | 1350.81 | 02-MAY-07:10 | 2160.55 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 10.40 | 05-MAY-16:00 | 2132.86 | 18-MAY-05:00 |
June | 2010.79 | 01-JUN-09:09 | 1350.81 | 16-JUN-07:10 | 2160.55 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 44.13 | 28-JUN-16:00 | 2634.14 | 13-JUN-03:00 |
July | 2010.79 | 03-JUL-09:09 | 1470.28 | 12-JUL-07:30 | 2160.55 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 365.33 | 23-JUL-14:10 | 1353.88 | 02-JUL-04:00 |
August | 2010.79 | 01-AUG-09:09 | 1470.28 | 02-AUG-07:30 | 2160.55 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 200.32 | 13-AUG-15:10 | 2020.35 | 11-AUG-03:55 |
September | 2010.79 | 01-SEP-09:09 | 2255.20 | 21-SEP-07:10 | 2160.55 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12.42 | 14-SEP-17:00 | 1314.38 | 18-SEP-23:00 |
October | 2010.79 | 02-OCT-09:09 | 2587.92 | 26-OCT-07:10 | 2160.55 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 2674.08 | 31-OCT-21:03 |
November | 2010.79 | 01-NOV-09:09 | 2587.92 | 01-NOV-07:10 | 2160.55 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 2903.83 | 29-NOV-22:03 |
December | 2010.79 | 01-DEC-10:09 | 2587.92 | 01-DEC-08:09 | 2160.55 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 2399.33 | 22-DEC-22:03 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.79 | 1350.81 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1314.38 | |||||
Maximum of Months | 2010.79 | 2587.92 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 482.98 | 3106.88 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 1667.75 | 02-JAN-08:09 | 1392.34 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 2068.70 | 12-JAN-22:03 |
February | 1295.83 | 01-FEB-10:09 | 1667.75 | 01-FEB-16:00 | 1392.34 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1934.63 | 16-FEB-22:03 |
March | 1295.83 | 01-MAR-10:09 | 1453.34 | 07-MAR-16:00 | 1392.34 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1886.17 | 29-MAR-04:57 |
April | 1295.83 | 03-APR-09:09 | 870.51 | 03-APR-07:10 | 1392.34 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 304.95 | 01-APR-17:01 | 1932.64 | 10-APR-21:03 |
May | 1295.83 | 01-MAY-09:09 | 793.52 | 01-MAY-07:10 | 1392.34 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6.93 | 05-MAY-16:00 | 1423.00 | 18-MAY-04:57 |
June | 1295.83 | 01-JUN-09:09 | 793.52 | 01-JUN-07:10 | 1392.34 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 29.42 | 28-JUN-16:00 | 1739.64 | 13-JUN-03:00 |
July | 1295.83 | 03-JUL-09:09 | 870.51 | 12-JUL-07:00 | 1392.34 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 210.16 | 23-JUL-16:10 | 986.85 | 02-JUL-10:00 |
August | 1295.83 | 01-AUG-09:09 | 870.51 | 02-AUG-07:30 | 1392.34 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 125.63 | 08-AUG-17:00 | 1376.07 | 11-AUG-03:55 |
September | 1295.83 | 01-SEP-09:09 | 1453.34 | 25-SEP-07:10 | 1392.34 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8.28 | 14-SEP-17:00 | 845.12 | 18-SEP-23:00 |
October | 1295.83 | 02-OCT-09:09 | 1667.75 | 30-OCT-07:10 | 1392.34 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 1779.73 | 31-OCT-21:03 |
November | 1295.83 | 01-NOV-09:09 | 1667.75 | 01-NOV-07:10 | 1392.34 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1933.75 | 29-NOV-22:03 |
December | 1295.83 | 01-DEC-10:09 | 1667.75 | 01-DEC-16:10 | 1392.34 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1598.21 | 22-DEC-22:03 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 793.52 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 845.12 | |||||
Maximum of Months | 1295.83 | 1667.75 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 304.95 | 2068.70 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.83 | 02-JAN-10:09 | 2587.98 | 02-JAN-08:09 | 2160.58 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 3107.70 | 12-JAN-22:03 |
February | 2010.83 | 01-FEB-10:09 | 2587.98 | 02-FEB-16:00 | 2160.58 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 3089.56 | 19-FEB-12:00 |
March | 2010.83 | 01-MAR-10:09 | 2255.25 | 16-MAR-07:10 | 2160.58 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 2830.23 | 29-MAR-04:57 |
April | 2010.83 | 03-APR-09:09 | 1803.04 | 03-APR-07:10 | 2160.58 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 229.89 | 01-APR-17:10 | 2913.36 | 10-APR-21:03 |
May | 2010.83 | 01-MAY-09:09 | 1350.84 | 02-MAY-07:10 | 2160.58 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 10.39 | 05-MAY-16:00 | 2136.31 | 18-MAY-04:57 |
June | 2010.83 | 01-JUN-09:09 | 1350.84 | 16-JUN-07:10 | 2160.58 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 44.12 | 28-JUN-16:00 | 2594.24 | 13-JUN-03:00 |
July | 2010.83 | 03-JUL-09:09 | 1470.31 | 12-JUL-07:19 | 2160.58 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 242.52 | 23-JUL-16:10 | 1378.69 | 02-JUL-04:00 |
August | 2010.83 | 01-AUG-09:09 | 1470.31 | 02-AUG-07:30 | 2160.58 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 188.44 | 08-AUG-17:00 | 2107.08 | 11-AUG-03:55 |
September | 2010.83 | 01-SEP-09:09 | 2255.25 | 21-SEP-07:10 | 2160.58 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12.42 | 14-SEP-17:00 | 1299.49 | 30-SEP-04:53 |
October | 2010.83 | 02-OCT-09:09 | 2587.98 | 26-OCT-07:10 | 2160.58 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 2672.92 | 31-OCT-21:03 |
November | 2010.83 | 01-NOV-09:09 | 2587.98 | 01-NOV-07:10 | 2160.58 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 2903.88 | 29-NOV-22:03 |
December | 2010.83 | 01-DEC-10:09 | 2587.98 | 01-DEC-16:19 | 2160.58 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 2403.17 | 22-DEC-22:03 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.83 | 1350.84 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1299.49 | |||||
Maximum of Months | 2010.83 | 2587.98 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 242.52 | 3107.70 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 1667.75 | 02-JAN-08:09 | 1392.33 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 2073.99 | 12-JAN-22:03 |
February | 1295.83 | 01-FEB-10:09 | 1667.75 | 02-FEB-08:09 | 1392.33 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1938.79 | 16-FEB-22:03 |
March | 1295.83 | 01-MAR-10:09 | 1453.34 | 13-MAR-07:10 | 1392.33 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1883.53 | 29-MAR-04:57 |
April | 1295.83 | 03-APR-09:09 | 1161.92 | 03-APR-07:10 | 1392.33 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 72.26 | 01-APR-16:00 | 1956.93 | 10-APR-21:03 |
May | 1295.83 | 01-MAY-09:09 | 870.51 | 01-MAY-07:10 | 1392.33 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6.93 | 05-MAY-16:00 | 1496.34 | 27-MAY-17:40 |
June | 1295.83 | 01-JUN-09:09 | 870.51 | 06-JUN-07:10 | 1392.33 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 29.41 | 28-JUN-16:00 | 1756.28 | 13-JUN-03:00 |
July | 1295.83 | 03-JUL-09:09 | 1161.92 | 12-JUL-07:19 | 1392.33 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 161.53 | 23-JUL-13:30 | 1014.56 | 22-JUL-22:55 |
August | 1295.83 | 01-AUG-09:09 | 1161.92 | 28-AUG-07:10 | 1392.33 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 125.63 | 08-AUG-17:00 | 1482.67 | 11-AUG-03:55 |
September | 1295.83 | 01-SEP-09:09 | 1453.34 | 21-SEP-07:10 | 1392.33 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8.28 | 14-SEP-17:00 | 877.44 | 30-SEP-04:53 |
October | 1295.83 | 02-OCT-09:09 | 1667.75 | 26-OCT-07:10 | 1392.33 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 1785.30 | 31-OCT-21:03 |
November | 1295.83 | 01-NOV-09:09 | 1667.75 | 01-NOV-07:10 | 1392.33 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1940.02 | 29-NOV-22:03 |
December | 1295.83 | 01-DEC-10:09 | 1667.75 | 01-DEC-08:09 | 1392.33 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1603.94 | 22-DEC-22:03 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 870.51 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 877.44 | |||||
Maximum of Months | 1295.83 | 1667.75 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 161.53 | 2073.99 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 232.27 | 02-JAN-10:09 | 578.72 | 02-JAN-08:09 | 1948.61 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 232.27 | 01-FEB-10:09 | 578.72 | 01-FEB-08:09 | 3897.21 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 232.27 | 01-MAR-10:09 | 578.72 | 01-MAR-08:09 | 7794.42 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 232.27 | 03-APR-09:09 | 578.72 | 03-APR-07:10 | 7794.42 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 232.27 | 01-MAY-09:09 | 578.72 | 01-MAY-07:10 | 3897.21 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 232.27 | 01-JUN-09:09 | 578.72 | 01-JUN-07:10 | 5845.82 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 232.27 | 03-JUL-09:09 | 578.72 | 03-JUL-07:10 | 7794.42 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 232.27 | 01-AUG-09:09 | 578.72 | 01-AUG-07:10 | 7794.42 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 232.27 | 01-SEP-09:09 | 578.72 | 01-SEP-07:10 | 3897.21 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 232.27 | 02-OCT-09:09 | 578.72 | 02-OCT-07:10 | 5845.82 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 232.27 | 01-NOV-09:09 | 578.72 | 01-NOV-07:10 | 5845.82 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 232.27 | 01-DEC-10:09 | 578.72 | 01-DEC-08:09 | 7794.42 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 232.27 | 578.72 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 232.27 | 578.72 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 232.27 | 02-JAN-10:09 | 578.72 | 02-JAN-08:09 | 1948.61 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 232.27 | 01-FEB-10:09 | 578.72 | 01-FEB-08:09 | 3897.21 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 232.27 | 01-MAR-10:09 | 578.72 | 01-MAR-08:09 | 7794.42 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 232.27 | 03-APR-09:09 | 578.72 | 03-APR-07:10 | 7794.42 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 232.27 | 01-MAY-09:09 | 578.72 | 01-MAY-07:10 | 3897.21 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 232.27 | 01-JUN-09:09 | 578.72 | 01-JUN-07:10 | 5845.82 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 232.27 | 03-JUL-09:09 | 578.72 | 03-JUL-07:10 | 7794.42 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 232.27 | 01-AUG-09:09 | 578.72 | 01-AUG-07:10 | 7794.42 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 232.27 | 01-SEP-09:09 | 578.72 | 01-SEP-07:10 | 3897.21 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 232.27 | 02-OCT-09:09 | 578.72 | 02-OCT-07:10 | 5845.82 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 232.27 | 01-NOV-09:09 | 578.72 | 01-NOV-07:10 | 5845.82 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 232.27 | 01-DEC-10:09 | 578.72 | 01-DEC-08:09 | 7794.42 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 232.27 | 578.72 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 232.27 | 578.72 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 232.27 | 02-JAN-10:09 | 578.72 | 02-JAN-08:09 | 1948.61 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 232.27 | 01-FEB-10:09 | 578.72 | 01-FEB-08:09 | 3897.21 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 232.27 | 01-MAR-10:09 | 578.72 | 01-MAR-08:09 | 7794.42 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 232.27 | 03-APR-09:09 | 578.72 | 03-APR-07:10 | 7794.42 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 232.27 | 01-MAY-09:09 | 578.72 | 01-MAY-07:10 | 3897.21 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 232.27 | 01-JUN-09:09 | 578.72 | 01-JUN-07:10 | 5845.82 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 232.27 | 03-JUL-09:09 | 578.72 | 03-JUL-07:10 | 7794.42 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 232.27 | 01-AUG-09:09 | 578.72 | 01-AUG-07:10 | 7794.42 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 232.27 | 01-SEP-09:09 | 578.72 | 01-SEP-07:10 | 3897.21 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 232.27 | 02-OCT-09:09 | 578.72 | 02-OCT-07:10 | 5845.82 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 232.27 | 01-NOV-09:09 | 578.72 | 01-NOV-07:10 | 5845.82 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 232.27 | 01-DEC-10:09 | 578.72 | 01-DEC-08:09 | 7794.42 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 232.27 | 578.72 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 232.27 | 578.72 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 5027.92 | 02-JAN-10:09 | 6471.01 | 02-JAN-08:09 | 94908.13 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 5027.92 | 01-FEB-10:09 | 6471.01 | 01-FEB-08:09 | 189816.26 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 5027.92 | 01-MAR-10:09 | 6471.01 | 01-MAR-08:09 | 379632.52 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 5027.92 | 03-APR-09:09 | 6471.01 | 03-APR-07:10 | 379632.52 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 5027.92 | 01-MAY-09:09 | 6471.01 | 01-MAY-07:10 | 189816.26 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5027.92 | 01-JUN-09:09 | 6471.01 | 01-JUN-07:10 | 284724.39 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 5027.92 | 03-JUL-09:09 | 6471.01 | 03-JUL-07:10 | 379632.52 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 5027.92 | 01-AUG-09:09 | 6471.01 | 01-AUG-07:10 | 379632.52 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 5027.92 | 01-SEP-09:09 | 6471.01 | 01-SEP-07:10 | 189816.26 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 5027.92 | 02-OCT-09:09 | 6471.01 | 02-OCT-07:10 | 284724.39 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5027.92 | 01-NOV-09:09 | 6471.01 | 01-NOV-07:10 | 284724.39 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 5027.92 | 01-DEC-10:09 | 6471.01 | 01-DEC-08:09 | 379632.52 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 5027.92 | 6471.01 | 94908.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 5027.92 | 6471.01 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 2836.33 | 28-JAN-04:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 2641.85 | 16-FEB-04:00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 2475.89 | 28-MAR-24:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 179.50 | 01-APR-17:01 | 2518.65 | 07-APR-24:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.19 | 05-MAY-16:00 | 1852.68 | 18-MAY-05:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.51 | 28-JUN-15:00 | 2482.33 | 13-JUN-03:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 223.79 | 23-JUL-16:00 | 1255.22 | 02-JUL-04:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 139.14 | 13-AUG-15:00 | 1641.43 | 11-AUG-04:00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.31 | 14-SEP-17:00 | 1175.78 | 18-SEP-23:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 2213.33 | 31-OCT-21:10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 2689.44 | 29-NOV-23:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 2204.91 | 17-DEC-20:55 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1175.78 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 223.79 | 2836.33 |
Report: PeakSpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 4739.45 | 28-JAN-04:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 4382.48 | 16-FEB-04:00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 4161.55 | 28-MAR-24:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 485.64 | 01-APR-17:01 | 4302.04 | 07-APR-24:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.54 | 05-MAY-16:00 | 3239.15 | 18-MAY-04:53 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40.92 | 28-JUN-15:00 | 4245.16 | 13-JUN-03:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 492.07 | 23-JUL-16:00 | 2143.85 | 02-JUL-04:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 280.43 | 13-AUG-15:20 | 2930.29 | 11-AUG-03:55 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.61 | 14-SEP-17:00 | 2011.52 | 18-SEP-23:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 3738.29 | 31-OCT-21:03 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 4438.38 | 29-NOV-23:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 3568.67 | 22-DEC-23:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2011.52 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 492.07 | 4739.45 |
Report: PeakSpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 4838.05 | 12-JAN-24:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 4358.01 | 16-FEB-04:00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 4233.72 | 28-MAR-24:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 434.47 | 01-APR-17:01 | 4573.80 | 07-APR-24:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:05 | 3293.77 | 22-MAY-24:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.05 | 28-JUN-17:00 | 4280.29 | 13-JUN-03:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 137.81 | 23-JUL-13:52 | 2170.31 | 02-JUL-04:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 203.47 | 08-AUG-17:00 | 3243.49 | 11-AUG-03:55 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:03 | 2073.96 | 18-SEP-23:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 4089.09 | 31-OCT-21:03 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 4606.13 | 29-NOV-23:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 3792.14 | 22-DEC-23:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2073.96 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 434.47 | 4838.05 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 122538.05 | 02-JAN-05:11 | 0.00 | 25501.32 | 134575.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 119151.00 | 27-FEB-05:11 | 0.00 | 17850.93 | 94202.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 120381.56 | 27-MAR-04:11 | 0.00 | 22951.19 | 121117.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 120501.88 | 17-APR-04:12 | 0.00 | 15300.79 | 80745.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 120432.90 | 01-MAY-04:12 | 0.00 | 15300.79 | 80745.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 123929.65 | 26-JUN-04:11 | 0.00 | 20401.06 | 107660.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 117666.48 | 03-JUL-04:12 | 0.00 | 15300.79 | 80745.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 118273.60 | 07-AUG-04:11 | 0.00 | 17850.93 | 94202.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 116192.47 | 06-SEP-04:12 | 0.00 | 12750.66 | 67287.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 124229.65 | 02-OCT-04:11 | 0.00 | 20401.06 | 107660.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 121225.27 | 20-NOV-05:11 | 0.00 | 20401.06 | 107660.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 121267.87 | 26-DEC-04:01 | 0.00 | 8924.46 | 94202.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 116192.47 | 0.00 | 8924.46 | 67287.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 124229.65 | 0.00 | 25501.32 | 134575.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 91435.77 | 02-JAN-05:11 | 0.00 | 22901.98 | 59376.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 93135.42 | 27-FEB-05:11 | 0.00 | 16031.39 | 41563.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 96210.58 | 27-MAR-04:11 | 0.00 | 20611.78 | 53438.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 97730.00 | 17-APR-04:12 | 0.00 | 13741.19 | 35625.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 99403.06 | 01-MAY-04:12 | 0.00 | 13741.19 | 35625.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 98657.69 | 12-JUN-04:12 | 0.00 | 13741.19 | 35625.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 100155.52 | 17-JUL-04:12 | 0.00 | 13741.19 | 35625.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 97940.90 | 21-AUG-04:12 | 0.00 | 13741.19 | 35625.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 100576.52 | 05-SEP-04:12 | 0.00 | 13741.19 | 35625.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 101604.98 | 10-OCT-04:12 | 0.00 | 13741.19 | 35625.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 99489.75 | 06-NOV-05:12 | 0.00 | 13741.19 | 35625.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 95448.88 | 04-DEC-05:11 | 0.00 | 22901.98 | 59376.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 91435.77 | 0.00 | 13741.19 | 35625.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 101604.98 | 0.00 | 22901.98 | 59376.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 27912.33 | 12-JAN-17:00 | 15316.26 | 20611.01 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 61505.88 | 28-FEB-06:03 | 6448.95 | 9160.79 | 30589.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 78575.06 | 03-MAR-06:02 | 8061.19 | 11450.99 | 38236.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 84449.47 | 28-APR-04:12 | 0.00 | 13741.19 | 35625.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 83805.78 | 01-MAY-04:12 | 0.00 | 13741.19 | 35625.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 85792.85 | 12-JUN-04:12 | 0.00 | 13741.19 | 35625.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 87030.51 | 25-JUL-04:12 | 0.00 | 13741.19 | 35625.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 87748.64 | 25-AUG-04:11 | 0.00 | 16031.39 | 41563.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 85693.67 | 14-SEP-04:12 | 0.00 | 11450.99 | 29688.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 83953.66 | 06-OCT-05:02 | 8061.19 | 11450.99 | 38236.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 77390.43 | 07-NOV-06:02 | 8061.19 | 11450.99 | 38236.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 30889.41 | 06-DEC-16:20 | 15316.26 | 20611.01 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 27912.33 | 0.00 | 9160.79 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 87748.64 | 15316.26 | 20611.01 | 41563.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 19925.41 | 11-JAN-17:00 | 15316.26 | 20611.01 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 31655.08 | 28-FEB-17:00 | 15316.26 | 20611.01 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 34830.40 | 15-MAR-16:00 | 15316.26 | 20611.01 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 77883.00 | 28-APR-05:03 | 6448.95 | 9160.79 | 30589.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 78200.12 | 05-MAY-05:03 | 6448.95 | 9160.79 | 30589.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 82546.48 | 12-JUN-04:12 | 0.00 | 13741.19 | 35625.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 82294.48 | 25-JUL-04:12 | 0.00 | 13741.19 | 35625.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 83879.00 | 25-AUG-04:11 | 0.00 | 16031.39 | 41563.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 78764.49 | 14-SEP-05:03 | 6448.95 | 9160.79 | 30589.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 41735.69 | 04-OCT-15:50 | 15316.26 | 20611.01 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 28694.18 | 02-NOV-16:00 | 15316.26 | 20611.01 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 20024.96 | 06-DEC-17:00 | 15316.26 | 20611.01 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 19925.41 | 0.00 | 9160.79 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 83879.00 | 15316.26 | 20611.01 | 41563.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2754.66 | 11-JAN-06:02 | 1214.60 | 1725.34 | 5761.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 69.92 |
February | 4871.74 | 27-FEB-15:30 | 1923.11 | 1231.33 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.95 |
March | 5454.27 | 10-MAR-14:30 | 2010.79 | 1231.33 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 63.62 |
April | 8130.28 | 27-APR-15:20 | 1923.11 | 1231.33 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 22.77 | 0.00 |
May | 8118.96 | 15-MAY-13:50 | 2010.79 | 1231.33 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.64 |
June | 8869.51 | 21-JUN-13:40 | 2010.79 | 1231.33 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.67 |
July | 11524.60 | 24-JUL-05:03 | 809.73 | 547.28 | 3840.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.40 |
August | 9840.14 | 25-AUG-14:00 | 2010.79 | 1231.33 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 15.29 | 0.00 |
September | 7408.96 | 12-SEP-14:30 | 1923.11 | 1231.33 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 2.18 | 0.00 |
October | 5539.08 | 04-OCT-14:40 | 1923.11 | 1231.33 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.29 |
November | 4588.76 | 06-NOV-11:40 | 1923.11 | 1231.33 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 90.04 |
December | 2962.60 | 04-DEC-05:12 | 0.00 | 2875.57 | 7455.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2754.66 | 0.00 | 547.28 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 11524.60 | 2010.79 | 2875.57 | 7455.61 | 0.00 | 0.00 | 0.00 | 0.00 | 22.77 | 90.04 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3053.46 | 11-JAN-06:02 | 782.73 | 1111.88 | 3712.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45.04 |
February | 5115.42 | 08-FEB-09:45 | 2478.65 | 1587.03 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 56.21 |
March | 10049.29 | 14-MAR-08:55 | 2478.65 | 1587.03 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 52.60 |
April | 13651.07 | 27-APR-08:30 | 1239.33 | 793.52 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.91 |
May | 26634.20 | 14-MAY-08:31 | 456.59 | 308.57 | 3248.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 233.08 |
June | 27098.80 | 25-JUN-08:31 | 456.59 | 308.57 | 3248.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 132.65 |
July | 25525.69 | 30-JUL-08:22 | 391.37 | 264.49 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 90.81 |
August | 26664.52 | 06-AUG-09:51 | 456.59 | 308.57 | 3248.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 166.89 |
September | 27183.40 | 10-SEP-08:31 | 456.59 | 308.57 | 3248.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.55 |
October | 11134.05 | 04-OCT-08:50 | 1239.33 | 793.52 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36.85 |
November | 4459.95 | 15-NOV-09:10 | 1239.33 | 793.52 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.18 |
December | 3792.93 | 05-DEC-09:55 | 2478.65 | 1587.03 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 98.59 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3053.46 | 391.37 | 264.49 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.91 | |
Maximum of Months | 27183.40 | 2478.65 | 1587.03 | 3712.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 233.08 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 20288.24 | 08-JAN-13:43 | 404.87 | 273.61 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 430.64 |
February | 23551.13 | 12-FEB-13:23 | 404.87 | 273.61 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 902.38 |
March | 22223.77 | 01-MAR-13:30 | 1923.15 | 1231.36 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 56.12 |
April | 35511.32 | 02-APR-13:12 | 607.31 | 410.42 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 305.85 |
May | 35512.12 | 14-MAY-12:32 | 607.31 | 410.42 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 304.52 |
June | 34000.57 | 11-JUN-12:52 | 506.09 | 342.02 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 135.31 |
July | 34189.84 | 30-JUL-13:02 | 506.09 | 342.02 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.47 |
August | 36979.93 | 06-AUG-13:11 | 708.53 | 478.83 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 163.16 |
September | 37073.12 | 10-SEP-15:11 | 809.75 | 547.23 | 5761.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 134.11 |
October | 34839.20 | 29-OCT-12:52 | 506.09 | 342.02 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 313.37 |
November | 30464.68 | 11-NOV-11:32 | 404.87 | 273.61 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 356.25 |
December | 27487.24 | 03-DEC-12:13 | 404.87 | 273.61 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 358.62 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 20288.24 | 404.87 | 273.61 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.47 | |
Maximum of Months | 37073.12 | 1923.15 | 1231.36 | 5761.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 902.38 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 5693.47 | 05-JAN-15:30 | 1239.33 | 793.52 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 62.39 |
February | 12938.65 | 26-FEB-15:13 | 260.91 | 176.32 | 1856.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 312.90 |
March | 16274.70 | 18-MAR-17:06 | 326.14 | 220.40 | 2320.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 221.25 |
April | 28987.15 | 02-APR-13:52 | 391.37 | 264.49 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 161.11 |
May | 34808.49 | 14-MAY-16:31 | 652.28 | 440.81 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 223.92 |
June | 31119.73 | 18-JUN-16:51 | 521.82 | 352.65 | 3712.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 270.42 |
July | 32860.66 | 23-JUL-16:51 | 521.82 | 352.65 | 3712.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 64.53 |
August | 36522.15 | 06-AUG-16:31 | 652.28 | 440.81 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 163.72 |
September | 33373.19 | 10-SEP-15:51 | 587.05 | 396.73 | 4177.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 86.26 |
October | 18002.59 | 01-OCT-15:53 | 260.91 | 176.32 | 1856.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 303.77 |
November | 10127.86 | 04-NOV-15:30 | 130.46 | 132.25 | 541.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.31 |
December | 8705.03 | 05-DEC-15:30 | 1239.33 | 793.52 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 55.93 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 5693.47 | 130.46 | 132.25 | 541.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.31 | |
Maximum of Months | 36522.15 | 1239.33 | 793.52 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 312.90 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1980.28 | 11-JAN-16:20 | 1923.11 | 2587.92 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 220.70 |
February | 2399.54 | 28-FEB-15:00 | 2010.79 | 1231.33 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 2945.49 | 10-MAR-14:30 | 2010.79 | 1231.33 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 151.35 |
April | 6667.33 | 27-APR-15:20 | 1923.11 | 1231.33 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 51.58 | 0.00 |
May | 7345.70 | 05-MAY-13:30 | 2010.79 | 1231.33 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.30 |
June | 7954.49 | 21-JUN-15:30 | 1923.11 | 1231.33 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 8.17 | 0.00 |
July | 9210.33 | 24-JUL-15:00 | 1923.11 | 1231.33 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 81.05 | 0.00 |
August | 8796.88 | 25-AUG-14:00 | 2010.79 | 1231.33 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 34.71 | 0.00 |
September | 6470.11 | 12-SEP-14:40 | 1923.11 | 1231.33 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 3.73 | 0.00 |
October | 3927.45 | 06-OCT-14:40 | 1923.11 | 1231.33 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 100.48 |
November | 2278.02 | 02-NOV-14:10 | 1923.11 | 1231.33 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 119.89 |
December | 1878.68 | 29-DEC-16:10 | 1923.11 | 2587.92 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 184.28 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1878.68 | 1923.11 | 1231.33 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 9210.33 | 2010.79 | 2587.92 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 81.05 | 220.70 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2318.54 | 05-JAN-09:40 | 2478.65 | 1587.03 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 147.73 |
February | 3198.37 | 12-FEB-11:52 | 326.14 | 220.40 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 778.03 |
March | 8127.63 | 14-MAR-10:10 | 1239.33 | 793.52 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 70.19 |
April | 13863.99 | 27-APR-09:00 | 1239.33 | 793.52 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46.08 |
May | 22731.29 | 14-MAY-09:22 | 326.14 | 220.40 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 454.38 |
June | 28339.56 | 25-JUN-08:21 | 456.59 | 308.57 | 3248.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 331.27 |
July | 30249.09 | 30-JUL-08:41 | 587.05 | 396.73 | 4177.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 264.60 |
August | 30193.51 | 13-AUG-08:51 | 587.05 | 396.73 | 4177.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 501.35 |
September | 23234.17 | 10-SEP-08:42 | 326.14 | 220.40 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 223.78 |
October | 10193.78 | 04-OCT-09:00 | 1239.33 | 793.52 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 86.62 |
November | 2927.69 | 04-NOV-10:30 | 391.37 | 264.51 | 773.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.08 |
December | 2568.67 | 05-DEC-10:00 | 2478.65 | 1587.03 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 215.46 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2318.54 | 326.14 | 220.40 | 773.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.08 | |
Maximum of Months | 30249.09 | 2478.65 | 1587.03 | 4177.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 778.03 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 18884.24 | 20-JAN-13:20 | 1923.15 | 1231.36 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.53 |
February | 37094.89 | 12-FEB-13:12 | 607.31 | 410.42 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2264.00 |
March | 23922.67 | 01-MAR-13:40 | 1923.15 | 1231.36 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 126.11 |
April | 23885.58 | 23-APR-14:32 | 506.09 | 342.02 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 960.61 |
May | 28638.94 | 14-MAY-13:22 | 506.09 | 342.02 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 596.77 |
June | 35126.21 | 11-JUN-13:02 | 506.09 | 342.02 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 312.24 |
July | 40029.12 | 30-JUL-13:21 | 809.75 | 547.23 | 5761.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 177.14 |
August | 40163.35 | 13-AUG-12:51 | 809.75 | 547.23 | 5761.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 197.20 |
September | 37874.73 | 10-SEP-12:42 | 607.31 | 410.42 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 374.90 |
October | 36677.31 | 08-OCT-13:22 | 607.31 | 410.42 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 488.77 |
November | 36979.67 | 11-NOV-12:42 | 607.31 | 410.42 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 947.45 |
December | 18827.96 | 05-DEC-12:30 | 1058.33 | 1231.36 | 1920.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 154.23 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 18827.96 | 506.09 | 342.02 | 1920.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.53 | |
Maximum of Months | 40163.35 | 1923.15 | 1231.36 | 5761.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2264.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3011.48 | 05-JAN-15:50 | 1239.33 | 793.52 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 153.06 |
February | 8856.86 | 27-FEB-15:30 | 1239.33 | 793.52 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.99 |
March | 11873.93 | 14-MAR-16:00 | 1239.33 | 793.52 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40.92 |
April | 18064.92 | 01-APR-17:04 | 456.59 | 308.57 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.30 |
May | 29069.52 | 14-MAY-16:41 | 456.59 | 308.57 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 411.98 |
June | 27929.05 | 25-JUN-16:21 | 587.05 | 396.73 | 4177.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 250.62 |
July | 33828.04 | 23-JUL-17:11 | 0.00 | 440.81 | 3603.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 270.90 |
August | 32804.26 | 06-AUG-17:41 | 0.00 | 440.81 | 3603.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 323.79 |
September | 27951.00 | 10-SEP-16:42 | 391.37 | 264.49 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 157.90 |
October | 13169.93 | 04-OCT-16:00 | 1239.33 | 793.52 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43.13 |
November | 6301.45 | 04-NOV-15:30 | 130.46 | 132.25 | 541.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.42 |
December | 3214.48 | 05-DEC-15:40 | 1239.33 | 793.52 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 133.70 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3011.48 | 0.00 | 132.25 | 541.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.42 | |
Maximum of Months | 33828.04 | 1239.33 | 793.52 | 4177.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 411.98 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1888.82 | 11-JAN-16:20 | 1923.11 | 2587.92 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 261.97 |
February | 2369.71 | 28-FEB-15:10 | 1923.11 | 1231.33 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.49 |
March | 2521.36 | 10-MAR-14:50 | 2010.79 | 1231.33 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 179.71 |
April | 7280.27 | 27-APR-15:20 | 1923.11 | 1231.33 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 61.78 | 0.00 |
May | 7656.04 | 05-MAY-13:30 | 2010.79 | 1231.33 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.83 |
June | 8579.05 | 21-JUN-15:30 | 1923.11 | 1231.33 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 8.28 | 0.00 |
July | 10164.75 | 24-JUL-15:00 | 1923.11 | 1231.33 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 98.95 | 0.00 |
August | 9335.42 | 09-AUG-14:40 | 1923.11 | 1231.33 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 99.89 | 0.00 |
September | 6765.52 | 12-SEP-14:40 | 1923.11 | 1231.33 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 2.90 | 0.00 |
October | 3758.68 | 04-OCT-15:30 | 1923.11 | 1231.33 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 75.18 |
November | 2209.84 | 02-NOV-14:40 | 1923.11 | 1231.33 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 140.20 |
December | 1783.85 | 29-DEC-16:10 | 1923.11 | 2587.92 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 221.23 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1783.85 | 1923.11 | 1231.33 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 10164.75 | 2010.79 | 2587.92 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 99.89 | 261.97 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2106.76 | 20-JAN-10:40 | 2591.66 | 1587.03 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 92.29 |
February | 2633.53 | 03-FEB-10:40 | 1295.83 | 793.52 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 99.81 |
March | 6902.81 | 14-MAR-09:50 | 1295.83 | 793.52 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 114.97 |
April | 13428.29 | 27-APR-09:10 | 1295.83 | 793.52 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 56.50 |
May | 26653.06 | 14-MAY-09:42 | 391.37 | 264.49 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 588.88 |
June | 22612.40 | 25-JUN-08:42 | 326.14 | 220.40 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 327.21 |
July | 29229.87 | 23-JUL-08:41 | 521.82 | 352.65 | 3712.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 667.38 |
August | 29036.21 | 13-AUG-08:21 | 521.82 | 352.65 | 3712.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 577.16 |
September | 26848.17 | 10-SEP-09:42 | 391.37 | 264.49 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 245.72 |
October | 9080.02 | 04-OCT-09:20 | 1295.83 | 793.52 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 101.99 |
November | 2684.65 | 04-NOV-10:30 | 391.37 | 264.51 | 773.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.84 |
December | 2207.68 | 05-DEC-10:30 | 1295.83 | 793.52 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 174.42 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2106.76 | 326.14 | 220.40 | 773.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.84 | |
Maximum of Months | 29229.87 | 2591.66 | 1587.03 | 3712.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 667.38 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 17327.38 | 20-JAN-13:30 | 1923.15 | 1231.36 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 72.20 |
February | 20544.28 | 27-FEB-14:20 | 2010.83 | 1231.36 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 72.51 |
March | 23132.54 | 14-MAR-13:30 | 2010.83 | 1231.36 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 75.83 |
April | 38317.37 | 02-APR-13:42 | 607.31 | 410.42 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 786.03 |
May | 38507.72 | 14-MAY-13:42 | 607.31 | 410.42 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 822.08 |
June | 28873.58 | 11-JUN-12:32 | 404.87 | 273.61 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 383.75 |
July | 40560.73 | 30-JUL-12:11 | 708.53 | 478.83 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 204.47 |
August | 41129.97 | 13-AUG-14:21 | 809.75 | 547.23 | 5761.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 114.62 |
September | 42128.01 | 10-SEP-15:01 | 809.75 | 547.23 | 5761.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 464.26 |
October | 38750.68 | 08-OCT-13:52 | 607.31 | 410.42 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 586.87 |
November | 19870.21 | 04-NOV-13:30 | 211.67 | 205.23 | 840.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 16552.57 | 05-DEC-12:30 | 1058.33 | 1231.36 | 1920.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 193.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 16552.57 | 211.67 | 205.23 | 840.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 42128.01 | 2010.83 | 1231.36 | 5761.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 822.08 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3014.33 | 05-JAN-15:50 | 1239.33 | 793.52 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 187.98 |
February | 8408.43 | 27-FEB-15:30 | 1239.33 | 793.52 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40.70 |
March | 11857.87 | 14-MAR-16:00 | 1239.33 | 793.52 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
April | 22383.02 | 02-APR-15:41 | 521.82 | 352.65 | 3712.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 418.97 |
May | 33739.29 | 14-MAY-17:01 | 0.00 | 440.81 | 3603.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 677.16 |
June | 31940.20 | 18-JUN-17:01 | 0.00 | 352.65 | 2882.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 844.15 |
July | 35118.88 | 23-JUL-17:21 | 0.00 | 440.81 | 3603.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 340.17 |
August | 30483.60 | 06-AUG-17:21 | 0.00 | 308.57 | 2522.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 299.09 |
September | 30240.37 | 10-SEP-16:21 | 652.28 | 440.81 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 221.62 |
October | 13125.23 | 04-OCT-16:00 | 1239.33 | 793.52 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 55.49 |
November | 5952.10 | 04-NOV-15:30 | 130.46 | 132.25 | 541.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.33 |
December | 3148.77 | 05-DEC-15:40 | 1239.33 | 793.52 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 162.25 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3014.33 | 0.00 | 132.25 | 541.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.33 | |
Maximum of Months | 35118.88 | 1239.33 | 793.52 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 844.15 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 5911.60 | 17-JAN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 196.55 |
February | 4681.92 | 28-FEB-06:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.00 |
March | 5765.37 | 01-MAR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 140.35 |
April | 7352.95 | 27-APR-14:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.70 | 0.00 |
May | 7176.60 | 15-MAY-15:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.46 |
June | 8976.14 | 12-JUN-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 132.24 |
July | 9177.43 | 31-JUL-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 69.70 | 0.00 |
August | 9348.99 | 14-AUG-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.88 | 0.00 |
September | 8755.92 | 05-SEP-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 78.54 |
October | 8427.11 | 10-OCT-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 143.43 |
November | 6730.18 | 06-NOV-06:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 222.92 |
December | 4633.97 | 07-DEC-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 140.33 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 4633.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 9348.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 69.70 | 222.92 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 9349.07 | 14-JAN-05:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2788.61 |
February | 8605.92 | 13-FEB-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2514.43 |
March | 7027.24 | 06-MAR-05:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1945.45 |
April | 5674.28 | 29-APR-05:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 256.96 |
May | 5481.14 | 17-MAY-05:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 348.86 |
June | 5754.62 | 28-JUN-15:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40.71 | 0.00 |
July | 6622.86 | 31-JUL-15:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 121.44 | 0.00 |
August | 7683.11 | 10-AUG-15:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 96.98 | 0.00 |
September | 7344.19 | 15-SEP-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44.43 |
October | 5536.85 | 06-OCT-05:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 183.69 |
November | 8185.11 | 24-NOV-05:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1397.57 |
December | 8806.51 | 09-DEC-05:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1577.20 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 5481.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 9349.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 121.44 | 2788.61 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 349.49 | 11-JAN-17:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 451.37 |
February | 3679.31 | 27-FEB-15:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 101.91 |
March | 6869.54 | 14-MAR-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 186.04 |
April | 16862.39 | 27-APR-14:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.98 | 0.00 |
May | 17068.23 | 04-MAY-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 68.07 |
June | 17552.73 | 28-JUN-14:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.54 |
July | 19197.22 | 24-JUL-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 122.52 | 0.00 |
August | 20091.87 | 10-AUG-14:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 58.20 | 0.00 |
September | 15438.22 | 14-SEP-14:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.42 |
October | 10024.81 | 04-OCT-14:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 144.91 |
November | 3786.40 | 04-NOV-13:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 144.58 | 30-DEC-12:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 52.55 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 144.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 20091.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 122.52 | 451.37 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 2108.67 | 05-JAN-16:10 | 222.14 | 578.72 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 4255.90 | 07-FEB-16:50 | 222.14 | 578.72 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6984.10 | 31-MAR-24:00 | 0.00 | 32.15 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 8393.34 | 26-APR-18:00 | 23.38 | 192.90 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 3476.74 | 31-MAY-24:00 | 0.00 | 32.15 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5349.92 | 30-JUN-24:00 | 0.00 | 32.15 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 7258.35 | 31-JUL-23:27 | 0.00 | 96.46 | 23383.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 8852.88 | 06-AUG-18:43 | 0.00 | 192.92 | 46766.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 3313.14 | 30-SEP-24:00 | 0.00 | 32.15 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 4983.46 | 31-OCT-24:00 | 0.00 | 32.15 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5913.31 | 10-NOV-16:00 | 222.14 | 578.72 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 7978.84 | 05-DEC-15:50 | 222.14 | 578.72 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 2108.67 | 0.00 | 32.15 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 8852.88 | 222.14 | 578.72 | 46766.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 1680.87 | 05-JAN-16:20 | 222.14 | 578.72 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 3887.75 | 08-FEB-17:00 | 222.14 | 578.72 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6104.15 | 31-MAR-23:40 | 0.00 | 32.15 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 8014.17 | 26-APR-18:00 | 23.38 | 192.90 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 3224.57 | 31-MAY-23:50 | 0.00 | 32.15 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5002.81 | 30-JUN-24:00 | 0.00 | 32.15 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 7003.15 | 31-JUL-24:00 | 0.00 | 64.31 | 15588.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 8295.02 | 06-AUG-18:32 | 0.00 | 257.22 | 62355.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 2897.89 | 30-SEP-23:40 | 0.00 | 32.15 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 4393.12 | 04-OCT-16:50 | 70.15 | 321.51 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5460.81 | 10-NOV-16:10 | 222.14 | 578.72 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 7303.23 | 05-DEC-16:00 | 222.14 | 578.72 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 1680.87 | 0.00 | 32.15 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 8295.02 | 222.14 | 578.72 | 62355.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 1612.48 | 05-JAN-16:20 | 222.14 | 578.72 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 3812.91 | 08-FEB-17:00 | 222.14 | 578.72 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 5892.46 | 01-MAR-17:00 | 222.14 | 578.72 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 8088.27 | 26-APR-18:00 | 23.38 | 192.90 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 3142.31 | 31-MAY-23:20 | 0.00 | 32.15 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 4899.13 | 30-JUN-23:40 | 0.00 | 32.15 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6969.80 | 31-JUL-23:45 | 0.00 | 128.61 | 31177.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 8401.66 | 06-AUG-18:23 | 0.00 | 321.53 | 77944.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 2610.69 | 10-SEP-17:22 | 0.00 | 192.92 | 11691.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 4421.28 | 04-OCT-16:50 | 70.15 | 321.51 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5329.22 | 10-NOV-16:10 | 222.14 | 578.72 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 7149.51 | 05-DEC-16:00 | 222.14 | 578.72 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 1612.48 | 0.00 | 32.15 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 8401.66 | 222.14 | 578.72 | 77944.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 92054.50 | 12-JAN-17:00 | 4808.68 | 6471.01 | 94908.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 184430.60 | 27-FEB-17:00 | 4808.68 | 6471.01 | 189816.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 358856.31 | 31-MAR-24:00 | 0.00 | 359.47 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 368990.77 | 01-APR-18:12 | 0.00 | 1437.90 | 1518530.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 176730.48 | 31-MAY-24:00 | 0.00 | 359.47 | 189816.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 268312.73 | 30-JUN-24:00 | 0.00 | 359.47 | 284724.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 360825.13 | 31-JUL-24:00 | 0.00 | 718.95 | 759265.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 371155.07 | 10-AUG-21:02 | 1518.53 | 4314.17 | 2277795.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 175823.14 | 30-SEP-24:00 | 0.00 | 359.47 | 189816.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 267537.25 | 31-OCT-24:00 | 0.00 | 359.47 | 284724.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 276947.41 | 06-NOV-17:00 | 4808.68 | 6471.01 | 284724.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 368425.69 | 05-DEC-17:00 | 4808.68 | 6471.01 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 92054.50 | 0.00 | 359.47 | 94908.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 371155.07 | 4808.68 | 6471.01 | 2277795.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.162952E+13 | 1097472.13 | 12-JAN-16:00 | 0.445363E+12 | 1643369.88 | 02-JAN-05:19 |
February | 0.182249E+13 | 1289109.75 | 27-FEB-14:00 | 0.266207E+12 | 823936.25 | 21-FEB-06:10 |
March | 0.243145E+13 | 1456591.62 | 14-MAR-15:50 | 0.140796E+12 | 590932.85 | 06-MAR-05:19 |
April | 0.267638E+13 | 1911858.21 | 27-APR-15:09 | 0.905540E+11 | 451224.63 | 19-APR-05:10 |
May | 0.165839E+13 | 1444906.74 | 15-MAY-15:20 | 0.723672E+11 | 325223.28 | 18-MAY-05:10 |
June | 0.201329E+13 | 1558498.21 | 28-JUN-15:30 | 0.659457E+11 | 80287.41 | 02-JUN-11:20 |
July | 0.251763E+13 | 1829349.09 | 31-JUL-15:09 | 0.630746E+11 | 78964.79 | 03-JUL-11:00 |
August | 0.309324E+13 | 2030054.14 | 29-AUG-15:09 | 0.665197E+11 | 78344.71 | 28-AUG-11:00 |
September | 0.161171E+13 | 1435438.88 | 14-SEP-15:09 | 0.634314E+11 | 110764.60 | 27-SEP-05:10 |
October | 0.195556E+13 | 1506485.69 | 04-OCT-15:30 | 0.939088E+11 | 400452.31 | 31-OCT-05:10 |
November | 0.227531E+13 | 1401249.79 | 15-NOV-16:00 | 0.202763E+12 | 561444.31 | 24-NOV-07:10 |
December | 0.275028E+13 | 1549844.04 | 05-DEC-16:19 | 0.338192E+12 | 867245.71 | 26-DEC-07:19 |
Annual Sum or Average | 0.264353E+14 | 0.190912E+13 | ||||
Minimum of Months | 0.161171E+13 | 1097472.13 | 0.630746E+11 | 78344.71 | ||
Maximum of Months | 0.309324E+13 | 2030054.14 | 0.445363E+12 | 1643369.88 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [J] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [J] | HUMIDIFIER:ELECTRICITY [J] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 0.338314E+12 | 0.803955E+11 | 0.766053E+12 | 0.164274E+12 | 0.168736E+12 | 0.113757E+11 | 0.00 | 0.930404E+10 | 0.147301E+10 | 0.895986E+11 | 0.00 | 0.00 | 0.00 |
February | 0.301183E+12 | 0.648776E+11 | 0.978954E+12 | 0.148383E+12 | 0.156026E+12 | 0.117764E+11 | 0.00 | 0.253803E+11 | 0.547633E+10 | 0.130437E+12 | 0.00 | 0.00 | 0.00 |
March | 0.353124E+12 | 0.612212E+11 | 0.141687E+13 | 0.164522E+12 | 0.184007E+12 | 0.138714E+11 | 0.00 | 0.464563E+11 | 0.117461E+11 | 0.179626E+12 | 0.00 | 0.00 | 0.00 |
April | 0.312911E+12 | 0.485976E+11 | 0.165903E+13 | 0.158945E+12 | 0.187912E+12 | 0.179714E+11 | 0.00 | 0.101291E+12 | 0.334009E+11 | 0.156327E+12 | 0.00 | 0.00 | 0.00 |
May | 0.336166E+12 | 0.419721E+11 | 0.774844E+12 | 0.164394E+12 | 0.206023E+12 | 0.238205E+11 | 0.00 | 0.513425E+11 | 0.248288E+11 | 0.350002E+11 | 0.00 | 0.00 | 0.00 |
June | 0.333474E+12 | 0.365051E+11 | 0.106252E+13 | 0.159182E+12 | 0.213852E+12 | 0.320469E+11 | 0.00 | 0.103387E+12 | 0.503428E+11 | 0.219837E+11 | 0.00 | 0.00 | 0.00 |
July | 0.312623E+12 | 0.392428E+11 | 0.139340E+13 | 0.164155E+12 | 0.232521E+12 | 0.429515E+11 | 0.00 | 0.221999E+12 | 0.892953E+11 | 0.214363E+11 | 0.00 | 0.00 | 0.00 |
August | 0.348867E+12 | 0.460624E+11 | 0.173200E+13 | 0.164521E+12 | 0.248766E+12 | 0.500665E+11 | 0.00 | 0.374438E+12 | 0.127447E+12 | 0.107358E+10 | 0.00 | 0.00 | 0.00 |
September | 0.314431E+12 | 0.546090E+11 | 0.740713E+12 | 0.158944E+12 | 0.207162E+12 | 0.287920E+11 | 0.00 | 0.694233E+11 | 0.360136E+11 | 0.161959E+10 | 0.00 | 0.00 | 0.00 |
October | 0.330507E+12 | 0.674399E+11 | 0.108340E+13 | 0.164270E+12 | 0.186452E+12 | 0.157732E+11 | 0.00 | 0.384363E+11 | 0.147985E+11 | 0.544802E+11 | 0.00 | 0.00 | 0.00 |
November | 0.333036E+12 | 0.749235E+11 | 0.135889E+13 | 0.159047E+12 | 0.166398E+12 | 0.131378E+11 | 0.00 | 0.416003E+11 | 0.101484E+11 | 0.118125E+12 | 0.00 | 0.00 | 0.00 |
December | 0.329428E+12 | 0.829175E+11 | 0.170972E+13 | 0.164164E+12 | 0.168989E+12 | 0.127335E+11 | 0.00 | 0.532589E+11 | 0.879202E+10 | 0.220281E+12 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.394406E+13 | 0.698764E+12 | 0.146764E+14 | 0.193480E+13 | 0.232684E+13 | 0.274317E+12 | 0.00 | 0.113632E+13 | 0.413762E+12 | 0.102999E+13 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.301183E+12 | 0.365051E+11 | 0.740713E+12 | 0.148383E+12 | 0.156026E+12 | 0.113757E+11 | 0.00 | 0.930404E+10 | 0.147301E+10 | 0.107358E+10 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.353124E+12 | 0.829175E+11 | 0.173200E+13 | 0.164522E+12 | 0.248766E+12 | 0.500665E+11 | 0.00 | 0.374438E+12 | 0.127447E+12 | 0.220281E+12 | 0.00 | 0.00 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [J] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.00 | 0.00 | 0.375252E+12 | 0.00 | 0.701111E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.202318E+12 | 0.00 | 0.638888E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.676647E+11 | 0.00 | 0.731314E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.240823E+11 | 0.00 | 0.664717E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.391874E+10 | 0.00 | 0.684485E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.332493E+09 | 0.00 | 0.656132E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.630746E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 12847428.10 | 0.00 | 0.665068E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.117611E+10 | 0.00 | 0.622553E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.283237E+11 | 0.00 | 0.655852E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.137052E+12 | 0.00 | 0.657111E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.270342E+12 | 0.00 | 0.678498E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.111048E+13 | 0.00 | 0.798648E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.622553E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.375252E+12 | 0.00 | 0.731314E+11 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | EXTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum} [W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 385834.94 | 02-JAN-08:09 | 57580.60 | 01-JAN-06:10 | 423497.50 | 02-JAN-08:09 | 118535.44 | 02-JAN-08:20 | 105456.21 | 02-JAN-05:19 | 25447.66 | 17-JAN-06:40 | 0.00 | 01-JAN-00:10 |
February | 385620.52 | 15-FEB-16:00 | 57580.60 | 01-FEB-06:10 | 541788.89 | 01-FEB-08:09 | 118530.30 | 02-FEB-08:20 | 137678.33 | 27-FEB-14:00 | 24275.33 | 16-FEB-06:10 | 0.00 | 01-FEB-00:10 |
March | 372703.55 | 22-MAR-07:10 | 57580.60 | 01-MAR-06:10 | 660080.29 | 01-MAR-08:09 | 118525.16 | 22-MAR-07:19 | 156032.86 | 14-MAR-15:30 | 24220.35 | 13-MAR-05:10 | 0.00 | 01-MAR-00:10 |
April | 351436.90 | 03-APR-07:10 | 57580.60 | 01-APR-05:10 | 778371.69 | 03-APR-07:10 | 118508.55 | 03-APR-07:19 | 243640.68 | 27-APR-14:30 | 47863.96 | 27-APR-11:50 | 0.00 | 01-APR-00:10 |
May | 336086.21 | 02-MAY-07:10 | 57580.60 | 01-MAY-19:19 | 423497.50 | 01-MAY-07:10 | 118496.59 | 02-MAY-07:19 | 221654.21 | 15-MAY-14:50 | 46520.25 | 04-MAY-14:00 | 0.00 | 01-MAY-00:10 |
June | 336086.21 | 16-JUN-07:10 | 57580.60 | 01-JUN-19:00 | 541788.89 | 01-JUN-07:10 | 118496.59 | 16-JUN-07:19 | 226748.28 | 28-JUN-15:20 | 47191.58 | 27-JUN-14:00 | 0.00 | 01-JUN-00:10 |
July | 343374.53 | 12-JUL-07:00 | 57580.60 | 01-JUL-20:10 | 660080.29 | 03-JUL-07:10 | 118501.55 | 12-JUL-07:40 | 259608.54 | 31-JUL-14:50 | 46232.68 | 31-JUL-15:00 | 0.00 | 01-JUL-00:10 |
August | 340801.53 | 02-AUG-07:30 | 57580.60 | 01-AUG-19:40 | 778371.69 | 01-AUG-07:10 | 118500.26 | 02-AUG-07:40 | 284421.05 | 10-AUG-14:50 | 47151.03 | 10-AUG-15:00 | 0.00 | 01-AUG-00:10 |
September | 372703.55 | 25-SEP-07:10 | 57580.60 | 01-SEP-05:10 | 423497.50 | 01-SEP-07:10 | 118525.16 | 25-SEP-07:19 | 254251.23 | 14-SEP-14:00 | 46545.56 | 08-SEP-15:20 | 0.00 | 01-SEP-00:10 |
October | 385834.94 | 30-OCT-07:10 | 57580.60 | 01-OCT-05:10 | 541788.89 | 02-OCT-07:10 | 118535.44 | 30-OCT-07:19 | 215560.24 | 04-OCT-15:30 | 23926.73 | 04-OCT-13:39 | 0.00 | 01-OCT-00:10 |
November | 385834.94 | 01-NOV-07:10 | 57580.60 | 01-NOV-05:10 | 660080.29 | 01-NOV-07:10 | 118535.44 | 01-NOV-07:19 | 115434.78 | 15-NOV-13:30 | 24579.14 | 24-NOV-06:10 | 0.00 | 01-NOV-00:10 |
December | 385834.94 | 01-DEC-16:19 | 57580.60 | 01-DEC-06:10 | 778371.69 | 01-DEC-08:09 | 118535.44 | 08-DEC-08:20 | 109858.01 | 05-DEC-11:00 | 25682.94 | 26-DEC-06:19 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 336086.21 | 57580.60 | 423497.50 | 118496.59 | 105456.21 | 23926.73 | 0.00 | |||||||
Maximum of Months | 385834.94 | 57580.60 | 778371.69 | 118535.44 | 284421.05 | 47863.96 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY {Maximum} [W] | HEATREJECTION:ELECTRICITY {TIMESTAMP} | HUMIDIFIER:ELECTRICITY {Maximum} [W] | HUMIDIFIER:ELECTRICITY {TIMESTAMP} | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 7976.15 | 20-JAN-15:50 | 2863.05 | 11-JAN-15:20 | 61997.36 | 09-JAN-11:00 | 0.00 | 0.00 | 0.00 |
February | 100992.64 | 27-FEB-15:00 | 50121.99 | 27-FEB-15:00 | 100000.00 | 12-FEB-09:39 | 0.00 | 0.00 | 0.00 |
March | 123367.55 | 18-MAR-15:00 | 49528.87 | 18-MAR-15:00 | 100000.00 | 01-MAR-04:19 | 0.00 | 0.00 | 0.00 |
April | 356724.95 | 27-APR-14:00 | 82535.37 | 27-APR-12:20 | 100000.00 | 01-APR-17:40 | 0.00 | 0.00 | 0.00 |
May | 215340.62 | 04-MAY-13:50 | 82535.37 | 05-MAY-12:00 | 100000.00 | 14-MAY-12:39 | 0.00 | 0.00 | 0.00 |
June | 276400.31 | 28-JUN-15:30 | 82535.37 | 21-JUN-15:30 | 100000.00 | 01-JUN-14:09 | 0.00 | 0.00 | 0.00 |
July | 379438.38 | 31-JUL-15:00 | 82535.37 | 07-JUL-12:20 | 100000.00 | 18-JUL-14:39 | 0.00 | 0.00 | 0.00 |
August | 433009.80 | 29-AUG-14:30 | 82535.37 | 07-AUG-10:39 | 97483.15 | 09-AUG-08:00 | 0.00 | 0.00 | 0.00 |
September | 224193.43 | 08-SEP-15:20 | 82535.37 | 11-SEP-14:09 | 29951.93 | 20-SEP-15:00 | 0.00 | 0.00 | 0.00 |
October | 179888.40 | 04-OCT-14:00 | 51113.18 | 04-OCT-14:00 | 100000.00 | 03-OCT-11:20 | 0.00 | 0.00 | 0.00 |
November | 143569.29 | 04-NOV-14:09 | 50919.96 | 04-NOV-14:09 | 100000.00 | 13-NOV-22:10 | 0.00 | 0.00 | 0.00 |
December | 34983.46 | 14-DEC-11:00 | 14768.57 | 14-DEC-11:00 | 100000.00 | 02-DEC-05:19 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 7976.15 | 2863.05 | 29951.93 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 433009.80 | 82535.37 | 100000.00 | 0.00 | 0.00 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY {AT MAX/MIN} [W] | |
January | 1097472.13 | 12-JAN-16:00 | 385834.94 | 423497.50 | 57580.60 | 84492.05 | 87019.28 | 22826.63 | 0.00 | 6657.67 | 1034.68 |
February | 1289109.75 | 27-FEB-14:00 | 332294.83 | 541788.89 | 0.00 | 39059.06 | 137678.33 | 22987.83 | 0.00 | 98850.96 | 49922.07 |
March | 1456591.62 | 14-MAR-15:50 | 332294.83 | 660080.29 | 0.00 | 84450.25 | 153834.96 | 22870.03 | 0.00 | 79759.62 | 49423.73 |
April | 1911858.21 | 27-APR-15:09 | 332294.83 | 778371.69 | 0.00 | 84450.25 | 233792.52 | 44585.14 | 0.00 | 355828.42 | 82535.37 |
May | 1444906.74 | 15-MAY-15:20 | 332294.83 | 423497.50 | 0.00 | 84450.25 | 220714.91 | 43125.16 | 0.00 | 189719.03 | 51105.07 |
June | 1558498.21 | 28-JUN-15:30 | 332294.83 | 541788.89 | 0.00 | 84450.25 | 226438.53 | 44776.84 | 0.00 | 276400.31 | 52348.56 |
July | 1829349.09 | 31-JUL-15:09 | 332294.83 | 660080.29 | 0.00 | 84450.25 | 258911.76 | 45117.89 | 0.00 | 365958.70 | 82535.37 |
August | 2030054.14 | 29-AUG-15:09 | 332294.83 | 778371.69 | 0.00 | 84450.25 | 281451.10 | 45738.57 | 0.00 | 425212.34 | 82535.37 |
September | 1435438.88 | 14-SEP-15:09 | 332294.83 | 423497.50 | 0.00 | 84450.25 | 251539.36 | 44030.07 | 0.00 | 217091.51 | 82535.37 |
October | 1506485.69 | 04-OCT-15:30 | 332294.83 | 541788.89 | 0.00 | 84450.25 | 215560.24 | 23343.09 | 0.00 | 158199.99 | 50848.40 |
November | 1401249.79 | 15-NOV-16:00 | 385834.94 | 660080.29 | 57580.60 | 84492.05 | 90988.91 | 22809.52 | 0.00 | 18291.18 | 2926.33 |
December | 1549844.04 | 05-DEC-16:19 | 385834.94 | 778371.69 | 57580.60 | 84486.19 | 93155.51 | 22815.01 | 0.00 | 23828.35 | 3771.76 |
Annual Sum or Average | |||||||||||
Minimum of Months | 1097472.13 | 332294.83 | 423497.50 | 0.00 | 39059.06 | 87019.28 | 22809.52 | 0.00 | 6657.67 | 1034.68 | |
Maximum of Months | 2030054.14 | 385834.94 | 778371.69 | 57580.60 | 84492.05 | 281451.10 | 45738.57 | 0.00 | 425212.34 | 82535.37 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS {Maximum} [W] | WATERSYSTEMS:NATURALGAS {TIMESTAMP} | COGENERATION:NATURALGAS [] | |
January | 0.00 | 0.00 | 1635223.30 | 02-JAN-05:19 | 0.00 | 83799.35 | 30-JAN-12:00 | 0.00 |
February | 0.00 | 0.00 | 815789.67 | 21-FEB-06:10 | 0.00 | 83859.11 | 14-FEB-12:20 | 0.00 |
March | 0.00 | 0.00 | 582786.27 | 06-MAR-05:19 | 0.00 | 83710.17 | 02-MAR-12:50 | 0.00 |
April | 0.00 | 0.00 | 421947.47 | 19-APR-05:10 | 0.00 | 82943.73 | 03-APR-11:30 | 0.00 |
May | 0.00 | 0.00 | 296053.92 | 18-MAY-05:10 | 0.00 | 81834.66 | 01-MAY-11:39 | 0.00 |
June | 0.00 | 0.00 | 48038.62 | 14-JUN-05:10 | 0.00 | 80287.41 | 02-JUN-11:20 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 78964.79 | 03-JUL-11:00 | 0.00 |
August | 0.00 | 0.00 | 1957.14 | 03-AUG-05:00 | 0.00 | 78344.71 | 28-AUG-11:00 | 0.00 |
September | 0.00 | 0.00 | 81675.56 | 27-SEP-05:10 | 0.00 | 79212.73 | 28-SEP-11:30 | 0.00 |
October | 0.00 | 0.00 | 392305.73 | 31-OCT-05:10 | 0.00 | 80644.05 | 30-OCT-11:30 | 0.00 |
November | 0.00 | 0.00 | 535042.89 | 24-NOV-05:19 | 0.00 | 82101.53 | 30-NOV-12:39 | 0.00 |
December | 0.00 | 0.00 | 850137.76 | 26-DEC-07:10 | 0.00 | 83157.65 | 29-DEC-12:39 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 78344.71 | 0.00 | ||
Maximum of Months | 0.00 | 0.00 | 1635223.30 | 0.00 | 83859.11 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 26.94 | 1.00 | 27.12 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 25.83 | 0.00 | 25.83 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 25.96 | 0.00 | 25.96 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 26.82 | 0.00 | 26.82 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 26.96 | 0.17 | 26.98 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 4.83 | 27.04 | 0.00 | 27.04 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 5.67 | 26.87 | 0.00 | 26.87 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 26.65 | 0.00 | 26.65 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 5.67 | 27.14 | 0.00 | 27.14 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 5.33 | 27.07 | 0.67 | 27.11 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 3.67 | 26.87 | 1.50 | 27.02 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 25.97 | 0.00 | 25.97 |
Annual Sum or Average | 0.00 | 0.00 | 40.83 | 26.84 | 3.33 | 26.89 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 25.83 | 0.00 | 25.83 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 5.67 | 27.14 | 1.50 | 27.14 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 25.59 | 0.00 | 25.59 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.17 | 25.59 | 0.00 | 25.59 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 25.59 | 0.00 | 25.59 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 1.50 | 19.50 | 0.83 | 19.73 | 0.00 | 19.73 | 0.00 | 19.73 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1.50 | 19.50 | 0.83 | 19.73 | 0.00 | 19.73 | 0.00 | 19.73 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1.50 | 19.50 | 0.83 | 19.73 | 0.00 | 19.73 | 0.00 | 19.73 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 2.67 | 19.06 | 0.67 | 19.30 | 0.00 | 19.30 | 0.00 | 19.30 |
February | 0.33 | 18.97 | 0.00 | 18.97 | 0.00 | 18.97 | 0.00 | 18.97 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.17 | 19.17 | 0.00 | 19.17 | 0.00 | 19.17 | 0.00 | 19.17 |
December | 0.83 | 18.85 | 0.00 | 18.85 | 0.00 | 18.85 | 0.00 | 18.85 |
Annual Sum or Average | 4.00 | 19.01 | 0.67 | 19.19 | 0.00 | 19.19 | 0.00 | 19.19 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2.67 | 19.17 | 0.67 | 19.30 | 0.00 | 19.30 | 0.00 | 19.30 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 28.24 | 1.33 | 28.24 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 28.04 | 3.00 | 28.04 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 28.47 | 3.33 | 28.47 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 28.51 | 2.83 | 28.51 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 28.24 | 1.67 | 28.24 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 12.17 | 28.32 | 12.17 | 28.32 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 28.51 | 3.33 | 28.51 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.39 | 0.33 | 27.39 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 28.05 | 1.17 | 28.05 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.34 | 0.17 | 27.34 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 27.93 | 1.83 | 27.93 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 27.81 | 3.33 | 27.81 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 27.64 | 3.00 | 27.64 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 4.00 | 28.09 | 4.00 | 28.09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.67 | 28.25 | 3.50 | 28.27 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 28.44 | 2.17 | 28.48 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 27.99 | 2.33 | 27.99 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 28.03 | 1.17 | 28.03 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 27.73 | 1.00 | 27.73 |
Annual Sum or Average | 0.00 | 0.00 | 24.33 | 28.00 | 24.00 | 28.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.34 | 0.17 | 27.34 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 4.00 | 28.44 | 4.00 | 28.48 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.31 | 0.17 | 27.31 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.36 | 0.50 | 27.36 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 6.00 | 27.93 | 3.67 | 28.01 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 6.67 | 28.65 | 3.50 | 28.71 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 5.67 | 28.25 | 3.33 | 28.28 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 13.50 | 28.16 | 6.33 | 28.30 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 15.33 | 27.62 | 4.83 | 27.81 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 4.17 | 28.22 | 3.00 | 28.26 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.52 | 0.67 | 27.52 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.41 | 0.17 | 27.41 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.28 | 0.17 | 27.28 |
Annual Sum or Average | 0.00 | 0.00 | 53.00 | 28.03 | 26.33 | 28.15 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 15.33 | 28.65 | 6.33 | 28.71 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 5.00 | 19.16 | 0.83 | 19.30 | 0.00 | 19.30 | 0.00 | 19.30 |
February | 1.50 | 19.10 | 0.00 | 19.10 | 0.00 | 19.10 | 0.00 | 19.10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.33 | 19.38 | 0.00 | 19.38 | 0.00 | 19.38 | 0.00 | 19.38 |
December | 1.17 | 19.22 | 0.17 | 19.34 | 0.00 | 19.34 | 0.00 | 19.34 |
Annual Sum or Average | 8.00 | 19.17 | 1.00 | 19.27 | 0.00 | 19.27 | 0.00 | 19.27 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 5.00 | 19.38 | 0.83 | 19.38 | 0.00 | 19.38 | 0.00 | 19.38 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 3.67 | 18.68 | 0.33 | 18.38 | 0.00 | 18.38 | 0.00 | 18.38 |
February | 1.33 | 19.10 | 0.00 | 19.10 | 0.00 | 19.10 | 0.00 | 19.10 |
March | 0.17 | 19.41 | 0.00 | 19.41 | 0.00 | 19.41 | 0.00 | 19.41 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 28.28 | 1.33 | 28.28 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 28.13 | 2.50 | 28.13 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 28.62 | 3.33 | 28.62 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.67 | 28.41 | 3.67 | 28.41 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 28.22 | 1.50 | 28.22 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.50 | 19.35 | 0.00 | 19.35 | 0.00 | 19.35 | 0.00 | 19.35 |
December | 1.83 | 19.21 | 0.00 | 19.21 | 0.00 | 19.21 | 0.00 | 19.21 |
Annual Sum or Average | 7.50 | 18.95 | 0.33 | 18.78 | 12.33 | 24.65 | 12.33 | 26.06 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 3.67 | 19.41 | 0.33 | 19.41 | 3.67 | 28.62 | 3.67 | 28.62 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 2.67 | 19.13 | 0.00 | 19.13 | 0.17 | 19.61 | 0.17 | 20.05 |
February | 1.00 | 19.30 | 0.00 | 19.30 | 1.33 | 24.28 | 1.33 | 25.64 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.32 | 0.17 | 27.32 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 27.92 | 1.50 | 27.92 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 27.85 | 3.00 | 27.85 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 27.68 | 1.50 | 27.68 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 28.15 | 3.50 | 28.15 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 28.43 | 3.17 | 28.43 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 28.58 | 2.33 | 28.61 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 28.07 | 2.17 | 28.07 |
November | 0.17 | 19.44 | 0.00 | 19.44 | 1.00 | 26.87 | 1.00 | 27.44 |
December | 0.83 | 19.10 | 0.00 | 19.10 | 0.50 | 22.29 | 0.50 | 23.74 |
Annual Sum or Average | 4.67 | 19.17 | 0.00 | 19.17 | 20.50 | 26.45 | 20.33 | 27.19 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 19.61 | 0.17 | 20.05 |
Maximum of Months | 2.67 | 19.44 | 0.00 | 19.44 | 3.50 | 28.58 | 3.50 | 28.61 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 2.33 | 19.13 | 0.00 | 19.13 | 0.00 | 19.13 | 0.00 | 19.13 |
February | 1.00 | 19.26 | 0.00 | 19.26 | 0.00 | 19.26 | 0.00 | 19.26 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.71 | 0.67 | 27.75 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 5.67 | 28.65 | 2.83 | 28.69 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 28.31 | 1.50 | 28.29 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 6.33 | 28.70 | 3.00 | 28.68 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 4.00 | 28.68 | 2.17 | 28.69 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 28.25 | 2.33 | 28.22 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.67 | 19.20 | 0.00 | 19.20 | 0.00 | 19.20 | 0.00 | 19.20 |
Annual Sum or Average | 4.00 | 19.17 | 0.00 | 19.17 | 22.50 | 27.13 | 12.50 | 27.57 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2.33 | 19.26 | 0.00 | 19.26 | 6.33 | 28.70 | 3.00 | 28.69 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 30.00 | 16.68 | 7.17 | 16.78 | 0.00 | 16.78 | 0.00 | 16.78 |
February | 17.83 | 16.96 | 4.50 | 16.92 | 0.00 | 16.92 | 0.00 | 16.92 |
March | 3.83 | 19.15 | 0.33 | 19.23 | 0.00 | 19.23 | 0.00 | 19.23 |
April | 0.83 | 19.24 | 0.00 | 19.24 | 0.00 | 19.24 | 0.00 | 19.24 |
May | 0.17 | 19.39 | 0.00 | 19.39 | 0.00 | 19.39 | 0.00 | 19.39 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 1.17 | 19.20 | 0.00 | 19.20 | 0.00 | 19.20 | 0.00 | 19.20 |
November | 6.17 | 18.85 | 0.83 | 19.02 | 0.00 | 19.02 | 0.00 | 19.02 |
December | 13.33 | 18.02 | 2.00 | 18.23 | 0.00 | 18.23 | 0.00 | 18.23 |
Annual Sum or Average | 73.33 | 17.38 | 14.83 | 17.42 | 0.00 | 17.42 | 0.00 | 17.42 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 30.00 | 19.39 | 7.17 | 19.39 | 0.00 | 19.39 | 0.00 | 19.39 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 21.67 | 15.89 | 3.17 | 15.76 | 0.00 | 15.76 | 0.00 | 15.76 |
February | 10.17 | 16.51 | 0.83 | 16.37 | 0.00 | 16.37 | 0.00 | 16.37 |
March | 3.00 | 18.89 | 0.00 | 18.89 | 0.00 | 18.89 | 0.00 | 18.89 |
April | 0.83 | 19.19 | 0.00 | 19.19 | 0.00 | 19.19 | 0.00 | 19.19 |
May | 0.17 | 19.34 | 0.00 | 19.34 | 1.17 | 27.04 | 1.17 | 27.55 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 27.89 | 2.33 | 27.89 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 4.33 | 28.26 | 4.33 | 28.26 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.83 | 28.33 | 3.83 | 28.33 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 28.25 | 1.00 | 28.25 |
October | 0.83 | 19.14 | 0.00 | 19.14 | 0.00 | 19.14 | 0.00 | 19.14 |
November | 3.50 | 18.37 | 0.00 | 18.37 | 0.00 | 18.37 | 0.00 | 18.37 |
December | 8.83 | 17.07 | 0.17 | 17.04 | 0.00 | 17.04 | 0.00 | 17.04 |
Annual Sum or Average | 49.00 | 16.72 | 4.17 | 16.57 | 12.67 | 18.81 | 12.67 | 20.32 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.76 | 0.00 | 15.76 |
Maximum of Months | 21.67 | 19.34 | 3.17 | 19.34 | 4.33 | 28.33 | 4.33 | 28.33 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 16.33 | 16.24 | 1.83 | 16.10 | 0.00 | 16.10 | 0.00 | 16.10 |
February | 6.17 | 17.18 | 0.83 | 16.90 | 0.33 | 17.38 | 0.33 | 17.82 |
March | 1.67 | 19.11 | 0.00 | 19.11 | 0.00 | 19.11 | 0.00 | 19.11 |
April | 0.83 | 19.29 | 0.00 | 19.29 | 1.17 | 24.39 | 1.17 | 25.73 |
May | 0.17 | 19.35 | 0.00 | 19.35 | 2.33 | 27.37 | 2.33 | 27.64 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 27.73 | 1.50 | 27.73 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 3.67 | 28.16 | 3.50 | 28.18 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 28.36 | 3.33 | 28.39 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 28.76 | 1.83 | 28.83 |
October | 0.67 | 19.31 | 0.00 | 19.31 | 1.17 | 24.77 | 1.17 | 25.98 |
November | 3.00 | 18.85 | 0.00 | 18.85 | 0.50 | 20.09 | 0.50 | 21.02 |
December | 6.67 | 17.58 | 0.00 | 17.58 | 0.00 | 17.58 | 0.00 | 17.58 |
Annual Sum or Average | 35.50 | 17.16 | 2.67 | 17.00 | 16.17 | 20.31 | 15.67 | 22.07 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.10 | 0.00 | 16.10 |
Maximum of Months | 16.33 | 19.35 | 1.83 | 19.35 | 3.67 | 28.76 | 3.50 | 28.83 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 10.33 | 16.92 | 1.00 | 16.74 | 0.00 | 16.74 | 0.00 | 16.74 |
February | 4.83 | 17.48 | 0.83 | 17.10 | 0.00 | 17.10 | 0.00 | 17.10 |
March | 1.33 | 19.17 | 0.00 | 19.17 | 0.00 | 19.17 | 0.00 | 19.17 |
April | 0.50 | 19.36 | 0.00 | 19.36 | 0.83 | 24.54 | 0.83 | 25.74 |
May | 0.17 | 19.40 | 0.00 | 19.40 | 5.83 | 28.31 | 3.00 | 28.42 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 28.22 | 1.83 | 28.19 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 6.50 | 28.73 | 3.33 | 28.70 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.67 | 28.88 | 1.83 | 28.93 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 28.18 | 2.17 | 28.19 |
October | 0.50 | 19.41 | 0.00 | 19.41 | 0.00 | 19.41 | 0.00 | 19.41 |
November | 2.33 | 19.06 | 0.00 | 19.06 | 0.00 | 19.06 | 0.00 | 19.06 |
December | 4.67 | 18.86 | 0.00 | 18.86 | 0.00 | 18.86 | 0.00 | 18.86 |
Annual Sum or Average | 24.67 | 17.84 | 1.83 | 17.63 | 22.67 | 22.66 | 13.00 | 23.88 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.74 | 0.00 | 16.74 |
Maximum of Months | 10.33 | 19.41 | 1.00 | 19.41 | 6.50 | 28.88 | 3.33 | 28.93 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 4.50 | 28.24 | 4.33 | 28.25 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 69.00 | 28.68 | 67.83 | 28.69 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 73.50 | 28.65 | 72.17 | 28.66 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 69.00 | 28.68 | 67.83 | 28.69 |
Report: ComfortReportSimple55Monthly
For: BASEMENT
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 71.17 | 24.00 | 88.33 | 25.11 | 0.00 | 25.11 |
February | 48.00 | 24.00 | 107.50 | 25.09 | 0.00 | 25.09 |
March | 26.83 | 24.00 | 110.83 | 25.43 | 0.00 | 25.43 |
April | 2.67 | 24.00 | 165.50 | 25.47 | 0.00 | 25.47 |
May | 0.00 | 0.00 | 244.83 | 25.01 | 0.00 | 25.01 |
June | 0.00 | 0.00 | 293.00 | 24.79 | 0.00 | 24.79 |
July | 0.00 | 0.00 | 422.50 | 24.72 | 0.00 | 24.72 |
August | 1.83 | 27.16 | 479.83 | 24.53 | 1.83 | 24.54 |
September | 0.00 | 0.00 | 385.67 | 24.68 | 0.00 | 24.68 |
October | 0.00 | 0.00 | 201.00 | 25.39 | 0.00 | 25.39 |
November | 1.33 | 24.00 | 199.50 | 25.35 | 0.00 | 25.35 |
December | 19.33 | 24.00 | 108.67 | 25.92 | 0.00 | 25.92 |
Annual Sum or Average | 171.17 | 24.03 | 2807.17 | 24.97 | 1.83 | 24.97 |
Minimum of Months | 0.00 | 0.00 | 88.33 | 24.53 | 0.00 | 24.54 |
Maximum of Months | 71.17 | 27.16 | 479.83 | 25.92 | 1.83 | 25.92 |
Report: ComfortReportSimple55Monthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 203.17 | 23.86 | 22.33 | 24.00 | 12.83 | 24.08 |
February | 103.50 | 23.85 | 68.83 | 24.28 | 0.00 | 24.28 |
March | 31.67 | 23.96 | 112.00 | 24.97 | 0.00 | 24.97 |
April | 1.50 | 24.00 | 176.50 | 24.90 | 0.00 | 24.90 |
May | 6.50 | 23.80 | 233.83 | 24.58 | 0.00 | 24.58 |
June | 0.00 | 0.00 | 313.83 | 24.44 | 0.00 | 24.44 |
July | 0.00 | 0.00 | 435.67 | 24.37 | 0.00 | 24.37 |
August | 0.00 | 0.00 | 490.00 | 24.26 | 0.00 | 24.26 |
September | 0.00 | 0.00 | 376.17 | 24.46 | 0.00 | 24.46 |
October | 7.17 | 23.72 | 204.00 | 24.87 | 0.00 | 24.87 |
November | 14.83 | 23.86 | 192.00 | 24.88 | 0.00 | 24.88 |
December | 47.00 | 23.89 | 97.33 | 25.09 | 0.00 | 25.09 |
Annual Sum or Average | 415.33 | 23.86 | 2722.50 | 24.51 | 12.83 | 24.52 |
Minimum of Months | 0.00 | 0.00 | 22.33 | 24.00 | 0.00 | 24.08 |
Maximum of Months | 203.17 | 24.00 | 490.00 | 25.09 | 12.83 | 25.09 |
Report: ComfortReportSimple55Monthly
For: CORE_MID
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 474.67 | 22.59 | 18.83 | 22.43 | 18.83 | 22.29 |
February | 380.83 | 23.11 | 0.00 | 23.11 | 0.00 | 23.11 |
March | 319.17 | 23.56 | 4.33 | 23.57 | 0.00 | 23.57 |
April | 190.83 | 23.55 | 44.33 | 23.77 | 0.00 | 23.77 |
May | 92.50 | 23.57 | 128.83 | 24.07 | 0.00 | 24.07 |
June | 37.67 | 23.60 | 166.00 | 24.30 | 0.00 | 24.30 |
July | 8.83 | 23.61 | 304.50 | 24.34 | 0.00 | 24.34 |
August | 12.33 | 23.48 | 406.67 | 24.24 | 0.00 | 24.24 |
September | 23.67 | 23.46 | 260.33 | 24.32 | 0.00 | 24.32 |
October | 184.67 | 23.43 | 51.17 | 23.74 | 0.00 | 23.74 |
November | 330.67 | 23.34 | 24.00 | 23.41 | 0.00 | 23.41 |
December | 447.50 | 23.05 | 0.00 | 23.05 | 0.00 | 23.05 |
Annual Sum or Average | 2503.33 | 23.18 | 1409.00 | 23.58 | 18.83 | 23.56 |
Minimum of Months | 8.83 | 22.59 | 0.00 | 22.43 | 0.00 | 22.29 |
Maximum of Months | 474.67 | 23.61 | 406.67 | 24.34 | 18.83 | 24.34 |
Report: ComfortReportSimple55Monthly
For: CORE_TOP
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 21.34 | 124.67 | 20.91 | 124.67 | 20.62 |
February | 438.33 | 21.85 | 75.67 | 21.50 | 75.67 | 21.25 |
March | 450.33 | 22.64 | 18.67 | 22.56 | 18.00 | 22.48 |
April | 320.17 | 22.93 | 33.50 | 23.07 | 0.00 | 23.07 |
May | 205.50 | 23.18 | 81.67 | 23.48 | 0.00 | 23.48 |
June | 104.50 | 23.40 | 147.17 | 23.93 | 0.00 | 23.93 |
July | 46.83 | 23.47 | 288.67 | 24.16 | 0.00 | 24.16 |
August | 51.67 | 23.32 | 354.33 | 24.09 | 0.00 | 24.09 |
September | 151.83 | 23.17 | 168.33 | 23.71 | 0.00 | 23.71 |
October | 376.33 | 22.73 | 3.17 | 22.74 | 0.17 | 22.74 |
November | 460.33 | 22.17 | 36.17 | 22.04 | 33.67 | 21.91 |
December | 497.00 | 21.63 | 100.50 | 21.34 | 100.50 | 21.13 |
Annual Sum or Average | 3604.83 | 22.30 | 1432.50 | 22.52 | 352.67 | 22.33 |
Minimum of Months | 46.83 | 21.34 | 3.17 | 20.91 | 0.00 | 20.62 |
Maximum of Months | 502.00 | 23.47 | 354.33 | 24.16 | 124.67 | 24.16 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 21.98 | 36.00 | 21.89 | 36.00 | 21.81 |
February | 420.83 | 22.41 | 17.00 | 22.34 | 17.00 | 22.27 |
March | 415.50 | 23.17 | 0.33 | 23.17 | 0.00 | 23.17 |
April | 215.83 | 23.41 | 59.83 | 23.64 | 0.00 | 23.64 |
May | 146.50 | 23.42 | 136.17 | 23.88 | 0.00 | 23.88 |
June | 34.00 | 23.59 | 224.83 | 24.26 | 0.00 | 24.26 |
July | 0.00 | 0.00 | 386.50 | 24.34 | 0.00 | 24.34 |
August | 6.17 | 23.85 | 426.33 | 24.23 | 0.50 | 24.23 |
September | 109.67 | 23.33 | 212.67 | 23.98 | 0.00 | 23.98 |
October | 310.67 | 23.19 | 19.00 | 23.30 | 0.00 | 23.30 |
November | 402.50 | 22.89 | 10.50 | 22.93 | 0.00 | 22.93 |
December | 492.83 | 22.58 | 0.00 | 22.58 | 0.00 | 22.58 |
Annual Sum or Average | 3056.50 | 22.78 | 1529.17 | 23.25 | 53.50 | 23.22 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 21.89 | 0.00 | 21.81 |
Maximum of Months | 502.00 | 23.85 | 426.33 | 24.34 | 36.00 | 24.34 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 21.51 | 36.17 | 21.44 | 36.17 | 21.39 |
February | 420.67 | 21.92 | 16.17 | 21.91 | 13.00 | 21.87 |
March | 409.33 | 22.49 | 11.33 | 22.53 | 0.83 | 22.53 |
April | 238.33 | 22.81 | 117.00 | 23.29 | 0.00 | 23.29 |
May | 187.83 | 23.03 | 197.83 | 23.72 | 5.67 | 23.77 |
June | 99.83 | 23.52 | 287.33 | 24.13 | 11.50 | 24.21 |
July | 68.83 | 23.92 | 359.33 | 24.25 | 12.83 | 24.33 |
August | 73.83 | 23.73 | 378.50 | 24.12 | 13.67 | 24.20 |
September | 171.67 | 22.98 | 234.50 | 23.76 | 6.67 | 23.81 |
October | 346.33 | 22.58 | 59.83 | 22.86 | 0.00 | 22.86 |
November | 457.00 | 22.13 | 9.17 | 22.18 | 0.00 | 22.18 |
December | 493.33 | 21.73 | 1.33 | 21.72 | 1.33 | 21.72 |
Annual Sum or Average | 3469.00 | 22.29 | 1708.50 | 22.92 | 101.67 | 22.94 |
Minimum of Months | 68.83 | 21.51 | 1.33 | 21.44 | 0.00 | 21.39 |
Maximum of Months | 502.00 | 23.92 | 378.50 | 24.25 | 36.17 | 24.33 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 457.83 | 21.53 | 77.00 | 21.49 | 61.67 | 21.38 |
February | 351.50 | 22.03 | 88.17 | 22.38 | 23.50 | 22.32 |
March | 340.17 | 22.52 | 88.33 | 22.88 | 0.17 | 22.88 |
April | 226.50 | 22.99 | 156.00 | 23.55 | 5.17 | 23.59 |
May | 204.00 | 23.14 | 202.00 | 23.76 | 10.33 | 23.84 |
June | 120.33 | 23.43 | 270.83 | 24.07 | 10.50 | 24.15 |
July | 71.67 | 24.12 | 361.50 | 24.34 | 16.83 | 24.44 |
August | 55.50 | 24.13 | 400.67 | 24.25 | 14.33 | 24.33 |
September | 144.17 | 23.22 | 279.50 | 24.00 | 11.00 | 24.08 |
October | 285.00 | 22.79 | 143.00 | 23.37 | 8.17 | 23.44 |
November | 395.67 | 22.27 | 53.83 | 22.57 | 4.33 | 22.61 |
December | 428.17 | 21.87 | 46.83 | 22.09 | 7.00 | 22.09 |
Annual Sum or Average | 3080.50 | 22.43 | 2167.67 | 23.17 | 173.00 | 23.19 |
Minimum of Months | 55.50 | 21.53 | 46.83 | 21.49 | 0.17 | 21.38 |
Maximum of Months | 457.83 | 24.13 | 400.67 | 24.34 | 61.67 | 24.44 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 490.17 | 22.06 | 6.17 | 22.04 | 6.00 | 22.03 |
February | 335.17 | 22.66 | 51.67 | 22.94 | 0.33 | 22.95 |
March | 176.00 | 23.26 | 116.83 | 23.85 | 1.33 | 23.86 |
April | 46.83 | 24.50 | 305.83 | 24.69 | 14.50 | 24.79 |
May | 104.50 | 23.71 | 294.50 | 24.31 | 17.83 | 24.43 |
June | 21.00 | 25.76 | 431.00 | 24.51 | 14.00 | 24.58 |
July | 49.33 | 26.13 | 488.50 | 24.74 | 49.33 | 24.86 |
August | 57.33 | 25.59 | 514.00 | 24.58 | 57.33 | 24.67 |
September | 75.33 | 23.95 | 345.67 | 24.44 | 18.50 | 24.54 |
October | 163.00 | 23.12 | 171.67 | 23.97 | 3.33 | 24.00 |
November | 240.83 | 23.16 | 102.33 | 23.66 | 0.67 | 23.66 |
December | 287.67 | 23.17 | 41.00 | 23.41 | 0.33 | 23.41 |
Annual Sum or Average | 2047.17 | 23.07 | 2869.17 | 23.95 | 183.50 | 24.03 |
Minimum of Months | 21.00 | 22.06 | 6.17 | 22.04 | 0.33 | 22.03 |
Maximum of Months | 490.17 | 26.13 | 514.00 | 24.74 | 57.33 | 24.86 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.37 | 300.17 | 20.18 | 300.17 | 20.10 |
February | 454.00 | 20.85 | 181.33 | 20.58 | 181.33 | 20.44 |
March | 510.83 | 21.75 | 58.67 | 21.60 | 58.67 | 21.49 |
April | 415.17 | 22.41 | 24.33 | 22.46 | 6.67 | 22.43 |
May | 286.17 | 22.87 | 64.17 | 23.10 | 0.00 | 23.10 |
June | 152.50 | 23.22 | 107.17 | 23.61 | 0.00 | 23.61 |
July | 87.67 | 23.35 | 262.33 | 23.97 | 0.00 | 23.97 |
August | 107.83 | 23.24 | 304.00 | 23.91 | 0.00 | 23.91 |
September | 254.00 | 22.88 | 94.33 | 23.22 | 0.00 | 23.22 |
October | 481.33 | 22.12 | 12.67 | 22.07 | 12.67 | 22.03 |
November | 489.00 | 21.20 | 115.50 | 20.99 | 115.50 | 20.84 |
December | 497.00 | 20.62 | 246.67 | 20.44 | 246.67 | 20.35 |
Annual Sum or Average | 4237.50 | 21.67 | 1771.33 | 21.77 | 921.67 | 21.53 |
Minimum of Months | 87.67 | 20.37 | 12.67 | 20.18 | 0.00 | 20.10 |
Maximum of Months | 510.83 | 23.35 | 304.00 | 23.97 | 300.17 | 23.97 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 427.00 | 20.25 | 268.17 | 20.07 | 268.17 | 19.99 |
February | 385.00 | 20.88 | 151.67 | 20.66 | 151.67 | 20.54 |
March | 414.67 | 21.54 | 45.67 | 21.43 | 43.17 | 21.33 |
April | 285.17 | 22.09 | 66.17 | 22.45 | 6.50 | 22.42 |
May | 245.00 | 22.49 | 107.17 | 23.11 | 5.83 | 23.17 |
June | 155.67 | 23.05 | 175.50 | 23.80 | 11.00 | 23.90 |
July | 123.67 | 23.44 | 241.67 | 24.10 | 14.50 | 24.22 |
August | 117.33 | 23.35 | 272.67 | 24.05 | 15.17 | 24.16 |
September | 231.83 | 22.50 | 131.67 | 23.19 | 5.67 | 23.25 |
October | 374.33 | 21.74 | 34.50 | 21.85 | 11.00 | 21.81 |
November | 415.67 | 20.99 | 110.67 | 20.80 | 110.67 | 20.68 |
December | 422.00 | 20.52 | 225.67 | 20.36 | 225.67 | 20.28 |
Annual Sum or Average | 3597.33 | 21.51 | 1831.17 | 21.83 | 869.00 | 21.64 |
Minimum of Months | 117.33 | 20.25 | 34.50 | 20.07 | 5.67 | 19.99 |
Maximum of Months | 427.00 | 23.44 | 272.67 | 24.10 | 268.17 | 24.22 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 468.33 | 20.76 | 220.00 | 20.58 | 209.67 | 20.43 |
February | 373.17 | 21.31 | 153.50 | 21.49 | 99.17 | 21.33 |
March | 379.50 | 21.71 | 110.00 | 22.03 | 32.33 | 21.93 |
April | 294.17 | 22.23 | 132.33 | 22.87 | 9.33 | 22.90 |
May | 265.50 | 22.63 | 167.17 | 23.31 | 10.33 | 23.39 |
June | 197.67 | 22.88 | 201.83 | 23.61 | 7.00 | 23.67 |
July | 141.83 | 23.32 | 296.67 | 24.03 | 13.83 | 24.13 |
August | 135.83 | 23.30 | 341.17 | 24.03 | 13.83 | 24.11 |
September | 202.83 | 22.83 | 235.83 | 23.67 | 10.67 | 23.75 |
October | 334.83 | 22.14 | 130.67 | 22.78 | 13.67 | 22.83 |
November | 432.00 | 21.42 | 111.33 | 21.51 | 77.33 | 21.41 |
December | 444.17 | 20.97 | 202.17 | 20.94 | 171.50 | 20.79 |
Annual Sum or Average | 3669.83 | 21.82 | 2302.67 | 22.39 | 668.67 | 22.25 |
Minimum of Months | 135.83 | 20.76 | 110.00 | 20.58 | 7.00 | 20.43 |
Maximum of Months | 468.33 | 23.32 | 341.17 | 24.03 | 209.67 | 24.13 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.53 | 248.83 | 20.33 | 248.83 | 20.23 |
February | 435.33 | 21.00 | 128.83 | 20.81 | 125.33 | 20.68 |
March | 461.50 | 21.60 | 55.00 | 21.62 | 35.17 | 21.54 |
April | 352.83 | 22.18 | 87.83 | 22.62 | 7.33 | 22.64 |
May | 279.33 | 22.75 | 161.00 | 23.37 | 15.00 | 23.49 |
June | 187.00 | 22.93 | 209.17 | 23.67 | 7.67 | 23.73 |
July | 114.00 | 23.56 | 335.50 | 24.23 | 20.33 | 24.32 |
August | 119.50 | 23.27 | 347.00 | 24.06 | 21.33 | 24.13 |
September | 242.83 | 22.77 | 182.33 | 23.49 | 14.00 | 23.59 |
October | 429.33 | 21.87 | 48.50 | 22.09 | 4.83 | 22.07 |
November | 476.00 | 21.16 | 88.00 | 21.07 | 82.83 | 20.97 |
December | 495.33 | 20.82 | 189.33 | 20.65 | 189.33 | 20.56 |
Annual Sum or Average | 4095.00 | 21.65 | 2081.33 | 22.10 | 772.00 | 21.95 |
Minimum of Months | 114.00 | 20.53 | 48.50 | 20.33 | 4.83 | 20.23 |
Maximum of Months | 502.00 | 23.56 | 347.00 | 24.23 | 248.83 | 24.32 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.02 | 378.17 | 19.88 | 378.17 | 19.83 |
February | 454.00 | 20.38 | 265.17 | 20.14 | 265.17 | 20.03 |
March | 512.67 | 21.11 | 175.67 | 20.85 | 175.67 | 20.70 |
April | 435.33 | 21.89 | 73.83 | 21.74 | 62.50 | 21.59 |
May | 331.67 | 22.40 | 65.33 | 22.57 | 11.00 | 22.51 |
June | 199.00 | 22.86 | 104.17 | 23.31 | 0.00 | 23.31 |
July | 133.17 | 23.03 | 246.50 | 23.77 | 0.00 | 23.77 |
August | 150.17 | 22.87 | 275.83 | 23.69 | 0.00 | 23.69 |
September | 317.83 | 22.42 | 67.50 | 22.70 | 0.00 | 22.70 |
October | 494.17 | 21.44 | 79.50 | 21.22 | 79.50 | 21.05 |
November | 489.00 | 20.54 | 227.33 | 20.28 | 227.33 | 20.14 |
December | 497.00 | 20.11 | 370.33 | 19.97 | 370.33 | 19.92 |
Annual Sum or Average | 4516.00 | 21.23 | 2329.33 | 21.23 | 1569.67 | 20.96 |
Minimum of Months | 133.17 | 20.02 | 65.33 | 19.88 | 0.00 | 19.83 |
Maximum of Months | 512.67 | 23.03 | 378.17 | 23.77 | 378.17 | 23.77 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.04 | 364.00 | 19.89 | 364.00 | 19.82 |
February | 454.00 | 20.50 | 236.33 | 20.26 | 236.33 | 20.15 |
March | 491.50 | 21.20 | 127.00 | 20.95 | 125.00 | 20.77 |
April | 325.17 | 21.71 | 97.50 | 21.90 | 39.33 | 21.76 |
May | 282.83 | 22.17 | 152.67 | 22.84 | 14.83 | 22.82 |
June | 175.83 | 22.81 | 237.67 | 23.69 | 10.33 | 23.77 |
July | 148.67 | 23.25 | 307.33 | 23.98 | 17.67 | 24.09 |
August | 137.83 | 23.09 | 328.00 | 23.92 | 15.83 | 24.02 |
September | 268.83 | 22.08 | 156.17 | 22.89 | 4.50 | 22.93 |
October | 442.17 | 21.36 | 85.33 | 21.25 | 70.33 | 21.10 |
November | 489.00 | 20.55 | 215.00 | 20.31 | 215.00 | 20.17 |
December | 497.00 | 20.14 | 350.33 | 19.99 | 350.33 | 19.93 |
Annual Sum or Average | 4214.83 | 21.17 | 2657.33 | 21.45 | 1463.50 | 21.20 |
Minimum of Months | 137.83 | 20.04 | 85.33 | 19.89 | 4.50 | 19.82 |
Maximum of Months | 502.00 | 23.25 | 364.00 | 23.98 | 364.00 | 24.09 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 483.33 | 20.35 | 292.50 | 20.11 | 287.17 | 19.98 |
February | 390.17 | 20.83 | 211.67 | 20.82 | 172.17 | 20.64 |
March | 400.00 | 21.21 | 172.00 | 21.29 | 110.33 | 21.08 |
April | 317.33 | 21.77 | 158.00 | 22.23 | 50.50 | 22.10 |
May | 290.50 | 22.18 | 164.33 | 22.87 | 21.00 | 22.89 |
June | 224.50 | 22.57 | 192.33 | 23.38 | 8.50 | 23.45 |
July | 173.00 | 22.98 | 280.83 | 23.83 | 14.67 | 23.93 |
August | 167.00 | 22.90 | 316.67 | 23.82 | 13.50 | 23.91 |
September | 245.33 | 22.32 | 211.33 | 23.26 | 8.33 | 23.33 |
October | 358.67 | 21.55 | 145.83 | 22.05 | 43.17 | 21.94 |
November | 447.67 | 20.85 | 189.83 | 20.79 | 160.00 | 20.61 |
December | 458.33 | 20.43 | 286.17 | 20.28 | 268.33 | 20.14 |
Annual Sum or Average | 3955.83 | 21.38 | 2621.50 | 21.81 | 1157.67 | 21.58 |
Minimum of Months | 167.00 | 20.35 | 145.83 | 20.11 | 8.33 | 19.98 |
Maximum of Months | 483.33 | 22.98 | 316.67 | 23.83 | 287.17 | 23.93 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.17 | 322.50 | 19.97 | 322.50 | 19.89 |
February | 442.67 | 20.65 | 216.17 | 20.42 | 213.67 | 20.30 |
March | 471.83 | 21.19 | 132.67 | 21.08 | 117.17 | 20.94 |
April | 368.17 | 21.76 | 114.83 | 22.08 | 42.00 | 21.99 |
May | 309.83 | 22.35 | 148.83 | 22.99 | 19.33 | 23.09 |
June | 222.17 | 22.64 | 196.17 | 23.43 | 7.83 | 23.49 |
July | 151.17 | 23.20 | 312.83 | 24.03 | 21.17 | 24.13 |
August | 172.00 | 22.98 | 310.67 | 23.84 | 24.33 | 23.91 |
September | 291.83 | 22.37 | 164.33 | 23.10 | 12.17 | 23.20 |
October | 447.50 | 21.43 | 73.50 | 21.51 | 40.00 | 21.40 |
November | 482.33 | 20.75 | 171.17 | 20.55 | 168.17 | 20.42 |
December | 497.00 | 20.40 | 299.00 | 20.21 | 299.00 | 20.13 |
Annual Sum or Average | 4358.50 | 21.33 | 2462.67 | 21.64 | 1287.33 | 21.43 |
Minimum of Months | 151.17 | 20.17 | 73.50 | 19.97 | 7.83 | 19.89 |
Maximum of Months | 502.00 | 23.20 | 322.50 | 24.03 | 322.50 | 24.13 |
Report: ComfortReportSimple55Monthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 502.00 | 27.00 | 0.00 | 27.00 |
February | 5.17 | 27.00 | 454.00 | 27.00 | 5.17 | 27.00 |
March | 20.50 | 27.00 | 514.00 | 27.00 | 20.50 | 27.00 |
April | 160.67 | 27.00 | 485.00 | 27.00 | 160.67 | 27.00 |
May | 25.50 | 27.00 | 508.00 | 27.00 | 25.50 | 27.00 |
June | 76.00 | 27.00 | 496.00 | 27.00 | 76.00 | 27.00 |
July | 262.00 | 27.00 | 497.00 | 27.00 | 262.00 | 27.00 |
August | 380.83 | 27.00 | 514.00 | 27.00 | 380.83 | 27.00 |
September | 51.17 | 27.00 | 485.00 | 27.00 | 51.17 | 27.00 |
October | 22.17 | 27.00 | 502.00 | 27.00 | 22.17 | 27.00 |
November | 10.00 | 27.00 | 489.00 | 27.00 | 10.00 | 27.00 |
December | 11.50 | 27.00 | 497.00 | 27.00 | 11.50 | 27.00 |
Annual Sum or Average | 1025.50 | 27.00 | 5943.00 | 27.00 | 1025.50 | 27.00 |
Minimum of Months | 0.00 | 0.00 | 454.00 | 27.00 | 0.00 | 27.00 |
Maximum of Months | 380.83 | 27.00 | 514.00 | 27.00 | 380.83 | 27.00 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 20.33 | 24.46 | 432.00 | 26.88 | 0.00 | 26.88 |
February | 0.00 | 0.00 | 421.33 | 27.00 | 0.00 | 27.00 |
March | 4.17 | 27.00 | 514.00 | 27.00 | 4.17 | 27.00 |
April | 13.17 | 27.00 | 485.00 | 27.00 | 13.17 | 27.00 |
May | 5.50 | 27.00 | 508.00 | 27.00 | 5.50 | 27.00 |
June | 22.17 | 27.00 | 496.00 | 27.00 | 22.17 | 27.00 |
July | 72.67 | 27.00 | 497.00 | 27.00 | 72.67 | 27.00 |
August | 96.50 | 27.00 | 514.00 | 27.00 | 96.50 | 27.00 |
September | 23.33 | 27.00 | 485.00 | 27.00 | 23.33 | 27.00 |
October | 5.83 | 27.00 | 502.00 | 27.00 | 5.83 | 27.00 |
November | 0.00 | 0.00 | 489.00 | 27.00 | 0.00 | 27.00 |
December | 0.00 | 0.00 | 497.00 | 27.00 | 0.00 | 27.00 |
Annual Sum or Average | 263.67 | 26.80 | 5840.33 | 26.99 | 243.33 | 26.99 |
Minimum of Months | 0.00 | 0.00 | 421.33 | 26.88 | 0.00 | 26.88 |
Maximum of Months | 96.50 | 27.00 | 514.00 | 27.00 | 96.50 | 27.00 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 101.17 | 24.38 | 336.00 | 26.27 | 12.17 | 26.17 |
February | 23.83 | 27.00 | 358.50 | 27.00 | 0.00 | 27.00 |
March | 4.00 | 27.00 | 483.00 | 27.00 | 4.00 | 27.00 |
April | 16.50 | 27.00 | 485.00 | 27.00 | 16.50 | 27.00 |
May | 17.50 | 27.00 | 508.00 | 27.00 | 17.50 | 27.00 |
June | 32.67 | 27.00 | 496.00 | 27.00 | 32.67 | 27.00 |
July | 101.33 | 27.00 | 497.00 | 27.00 | 101.33 | 27.00 |
August | 118.33 | 27.00 | 514.00 | 27.00 | 118.33 | 27.00 |
September | 28.83 | 27.00 | 485.00 | 27.00 | 28.83 | 27.00 |
October | 6.00 | 27.00 | 500.50 | 27.00 | 6.00 | 27.00 |
November | 0.00 | 0.00 | 463.67 | 27.00 | 0.00 | 27.00 |
December | 7.00 | 27.00 | 414.17 | 27.00 | 0.00 | 27.00 |
Annual Sum or Average | 457.17 | 26.42 | 5540.83 | 26.95 | 337.33 | 26.94 |
Minimum of Months | 0.00 | 0.00 | 336.00 | 26.27 | 0.00 | 26.17 |
Maximum of Months | 118.33 | 27.00 | 514.00 | 27.00 | 118.33 | 27.00 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 344.67 | 27.00 | 502.00 | 27.00 | 344.67 | 27.00 |
February | 454.00 | 27.00 | 454.00 | 27.00 | 454.00 | 27.00 |
March | 514.00 | 27.00 | 514.00 | 27.00 | 514.00 | 27.00 |
April | 485.00 | 27.01 | 485.00 | 27.01 | 485.00 | 27.01 |
May | 508.00 | 27.00 | 508.00 | 27.00 | 508.00 | 27.00 |
June | 496.00 | 27.00 | 496.00 | 27.00 | 496.00 | 27.00 |
July | 497.00 | 27.01 | 497.00 | 27.01 | 497.00 | 27.01 |
August | 514.00 | 27.25 | 514.00 | 27.25 | 514.00 | 27.25 |
September | 485.00 | 27.00 | 485.00 | 27.00 | 485.00 | 27.00 |
October | 502.00 | 27.00 | 502.00 | 27.00 | 502.00 | 27.00 |
November | 489.00 | 27.00 | 489.00 | 27.00 | 489.00 | 27.00 |
December | 497.00 | 27.00 | 497.00 | 27.00 | 497.00 | 27.00 |
Annual Sum or Average | 5785.67 | 27.02 | 5943.00 | 27.02 | 5785.67 | 27.02 |
Minimum of Months | 344.67 | 27.00 | 454.00 | 27.00 | 344.67 | 27.00 |
Maximum of Months | 514.00 | 27.25 | 514.00 | 27.25 | 514.00 | 27.25 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 27.00000 | 26.88349 | 0.77433 | 17.74351 |
February | 454.00000 | 27.00006 | 27.15986 | 0.84303 | 20.15168 |
March | 514.00000 | 27.00003 | 28.08109 | 0.91850 | 22.91050 |
April | 485.00000 | 27.00002 | 30.83162 | 0.99986 | 26.18273 |
May | 508.00000 | 27.00026 | 33.79623 | 0.26730 | 6.62484 |
June | 496.00000 | 27.00028 | 35.11253 | 0.34611 | 7.59092 |
July | 497.00000 | 27.00029 | 36.40627 | 0.42689 | 8.90079 |
August | 514.00000 | 27.00069 | 37.09707 | 0.46772 | 9.68165 |
September | 485.00000 | 27.00064 | 36.58955 | 0.29964 | 7.00651 |
October | 502.00000 | 27.00013 | 33.35302 | 0.93851 | 23.66667 |
November | 489.00000 | 27.00010 | 31.39347 | 0.92848 | 23.28200 |
December | 497.00000 | 27.00000 | 27.27075 | 0.90949 | 22.53158 |
Annual Sum or Average | 5943.00000 | 27.00021 | 32.02984 | 0.67491 | 16.30880 |
Minimum of Months | 454.00000 | 27.00000 | 26.88349 | 0.26730 | 6.62484 |
Maximum of Months | 514.00000 | 27.00069 | 37.09707 | 0.99986 | 26.18273 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 26.88421 | 27.62730 | 0.62494 | 13.67631 |
February | 454.00000 | 27.00006 | 27.16071 | 0.70595 | 15.72383 |
March | 514.00000 | 27.00003 | 28.06175 | 0.77885 | 17.93861 |
April | 485.00000 | 27.00003 | 30.81263 | 0.85841 | 20.70498 |
May | 508.00000 | 27.00024 | 33.81900 | 0.17540 | 5.86221 |
June | 496.00000 | 27.00027 | 35.11339 | 0.23690 | 6.34046 |
July | 497.00000 | 27.00032 | 36.40922 | 0.30490 | 7.12450 |
August | 514.00000 | 27.00061 | 37.10236 | 0.32926 | 7.47220 |
September | 485.00000 | 27.00060 | 36.70536 | 0.21064 | 6.13560 |
October | 502.00000 | 27.00012 | 33.35219 | 0.82615 | 19.50973 |
November | 489.00000 | 27.00009 | 31.38247 | 0.76740 | 17.52305 |
December | 497.00000 | 27.00000 | 27.25887 | 0.71420 | 15.84827 |
Annual Sum or Average | 5943.00000 | 26.99042 | 32.09971 | 0.54272 | 12.78579 |
Minimum of Months | 454.00000 | 26.88421 | 27.16071 | 0.17540 | 5.86221 |
Maximum of Months | 514.00000 | 27.00061 | 37.10236 | 0.85841 | 20.70498 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 26.41949 | 27.99973 | 0.47657 | 11.84842 |
February | 454.00000 | 27.00015 | 27.17048 | 0.64131 | 14.03911 |
March | 514.00000 | 27.00003 | 28.07068 | 0.72345 | 16.28948 |
April | 485.00000 | 27.00003 | 30.81932 | 0.81982 | 19.45383 |
May | 508.00000 | 27.00039 | 33.83980 | 0.14205 | 5.83693 |
June | 496.00000 | 27.00027 | 35.12060 | 0.22271 | 6.33099 |
July | 497.00000 | 27.00032 | 36.40901 | 0.29740 | 7.16218 |
August | 514.00000 | 27.00054 | 37.10228 | 0.31562 | 7.42466 |
September | 485.00000 | 27.00057 | 36.78140 | 0.17261 | 5.99784 |
October | 502.00000 | 27.00011 | 33.37423 | 0.77338 | 17.80651 |
November | 489.00000 | 27.00009 | 31.39650 | 0.69898 | 15.48060 |
December | 497.00000 | 27.00000 | 27.26368 | 0.63917 | 13.79238 |
Annual Sum or Average | 5943.00000 | 26.95117 | 32.14522 | 0.49200 | 11.75895 |
Minimum of Months | 454.00000 | 26.41949 | 27.17048 | 0.14205 | 5.83693 |
Maximum of Months | 514.00000 | 27.00057 | 37.10228 | 0.81982 | 19.45383 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 26.99998 | 30.01439 | 1.03877 | 27.79686 |
February | 454.00000 | 27.00030 | 30.51517 | 1.21552 | 36.02630 |
March | 514.00000 | 27.00041 | 28.89559 | 1.36304 | 43.56539 |
April | 485.00000 | 27.01449 | 29.81407 | 1.51510 | 51.72259 |
May | 508.00000 | 27.00010 | 32.19062 | 0.52683 | 10.87928 |
June | 496.00000 | 27.00080 | 32.82744 | 0.75953 | 17.19013 |
July | 497.00000 | 27.00672 | 35.50646 | 0.99430 | 25.92236 |
August | 514.00000 | 27.24683 | 35.55937 | 1.25596 | 38.23702 |
September | 485.00000 | 27.00011 | 36.86707 | 0.59236 | 12.44156 |
October | 502.00000 | 27.00029 | 31.24174 | 1.25848 | 38.16221 |
November | 489.00000 | 27.00057 | 31.22055 | 1.39114 | 45.04836 |
December | 497.00000 | 27.00048 | 28.57640 | 1.48910 | 50.31153 |
Annual Sum or Average | 5943.00000 | 27.02335 | 31.94110 | 1.11597 | 33.08149 |
Minimum of Months | 454.00000 | 26.99998 | 28.57640 | 0.52683 | 10.87928 |
Maximum of Months | 514.00000 | 27.24683 | 36.86707 | 1.51510 | 51.72259 |
Report: OccupantComfortDataSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.43753 | 26.76160 | 0.36902 | 8.18159 |
February | 454.00000 | 24.43948 | 28.02137 | 0.38643 | 8.48731 |
March | 514.00000 | 24.40596 | 27.89189 | 0.39250 | 8.55635 |
April | 485.00000 | 24.51754 | 31.51948 | 0.44742 | 9.73622 |
May | 508.00000 | 24.49305 | 36.21099 | -0.3760 | 8.89736 |
June | 496.00000 | 24.46811 | 38.34294 | -0.3565 | 8.51737 |
July | 497.00000 | 24.61560 | 43.68643 | -0.2703 | 7.75579 |
August | 514.00000 | 24.48319 | 47.63235 | -0.2732 | 7.49166 |
September | 485.00000 | 24.54115 | 43.81459 | -0.2965 | 7.96360 |
October | 502.00000 | 24.56318 | 34.76822 | 0.48261 | 10.47347 |
November | 489.00000 | 24.56429 | 32.87592 | 0.46421 | 10.12897 |
December | 497.00000 | 24.51863 | 27.47563 | 0.40768 | 8.95712 |
Annual Sum or Average | 5943.00000 | 24.50390 | 34.96943 | 0.11188 | 8.75905 |
Minimum of Months | 454.00000 | 24.40596 | 26.76160 | -0.3760 | 7.49166 |
Maximum of Months | 514.00000 | 24.61560 | 47.63235 | 0.48261 | 10.47347 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.08078 | 31.40544 | 0.31000 | 7.49218 |
February | 454.00000 | 24.20237 | 29.80556 | 0.34259 | 7.71070 |
March | 514.00000 | 24.30971 | 29.33037 | 0.38722 | 8.38636 |
April | 485.00000 | 24.34776 | 32.42851 | 0.43384 | 9.23858 |
May | 508.00000 | 24.29000 | 37.56013 | -0.4171 | 9.10132 |
June | 496.00000 | 24.27849 | 39.65679 | -0.3834 | 8.47233 |
July | 497.00000 | 24.32801 | 44.49581 | -0.3225 | 7.59013 |
August | 514.00000 | 24.24963 | 48.10293 | -0.3099 | 7.30806 |
September | 485.00000 | 24.35379 | 45.19520 | -0.3388 | 8.01276 |
October | 502.00000 | 24.37160 | 36.33199 | 0.45046 | 9.57846 |
November | 489.00000 | 24.38968 | 34.70232 | 0.43416 | 9.28939 |
December | 497.00000 | 24.35543 | 29.67822 | 0.38438 | 8.37131 |
Annual Sum or Average | 5943.00000 | 24.29655 | 36.60918 | 0.07810 | 8.38046 |
Minimum of Months | 454.00000 | 24.08078 | 29.33037 | -0.4171 | 7.30806 |
Maximum of Months | 514.00000 | 24.38968 | 48.10293 | 0.45046 | 9.57846 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.66469 | 32.91067 | -0.0721 | 6.99775 |
February | 454.00000 | 23.25824 | 32.58533 | 0.08794 | 6.04346 |
March | 514.00000 | 23.76134 | 31.53233 | 0.22259 | 6.34904 |
April | 485.00000 | 23.94751 | 34.38086 | 0.29917 | 7.18398 |
May | 508.00000 | 24.06298 | 38.50673 | -0.5266 | 11.19494 |
June | 496.00000 | 24.11486 | 40.44112 | -0.4791 | 10.08810 |
July | 497.00000 | 24.20082 | 45.54277 | -0.4138 | 8.95406 |
August | 514.00000 | 24.17578 | 48.91208 | -0.3889 | 8.49747 |
September | 485.00000 | 24.15216 | 46.10735 | -0.4389 | 9.42213 |
October | 502.00000 | 23.90229 | 38.22868 | 0.30913 | 7.31495 |
November | 489.00000 | 23.57452 | 37.98283 | 0.20516 | 6.39271 |
December | 497.00000 | 23.14784 | 33.37860 | 0.06009 | 5.70814 |
Annual Sum or Average | 5943.00000 | 23.75047 | 38.41640 | -0.0968 | 7.86095 |
Minimum of Months | 454.00000 | 22.66469 | 31.53233 | -0.5266 | 5.70814 |
Maximum of Months | 514.00000 | 24.20082 | 48.91208 | 0.30913 | 11.19494 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.34110 | 34.46941 | -0.4040 | 12.09828 |
February | 454.00000 | 21.91907 | 34.72110 | -0.2464 | 9.51902 |
March | 514.00000 | 22.81096 | 33.85047 | -0.0181 | 6.48703 |
April | 485.00000 | 23.33287 | 36.07065 | 0.14472 | 6.50050 |
May | 508.00000 | 23.72375 | 39.53106 | -0.6488 | 14.95279 |
June | 496.00000 | 23.97986 | 40.83506 | -0.5257 | 11.25300 |
July | 497.00000 | 24.09577 | 45.88108 | -0.4442 | 9.54839 |
August | 514.00000 | 24.05135 | 49.38276 | -0.4301 | 9.33753 |
September | 485.00000 | 23.79851 | 47.50842 | -0.5696 | 12.62603 |
October | 502.00000 | 23.05605 | 40.87905 | 0.09364 | 6.35961 |
November | 489.00000 | 22.27510 | 41.32766 | -0.1197 | 7.11982 |
December | 497.00000 | 21.63164 | 36.03567 | -0.3209 | 9.19652 |
Annual Sum or Average | 5943.00000 | 23.01014 | 40.07469 | -0.2916 | 9.58657 |
Minimum of Months | 454.00000 | 21.34110 | 33.85047 | -0.6488 | 6.35961 |
Maximum of Months | 514.00000 | 24.09577 | 49.38276 | 0.14472 | 14.95279 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.98445 | 31.67878 | -0.2298 | 7.11237 |
February | 454.00000 | 22.52663 | 31.50887 | -0.0898 | 6.60040 |
March | 514.00000 | 23.33413 | 30.65817 | 0.11036 | 5.92805 |
April | 485.00000 | 23.82429 | 32.83906 | 0.27119 | 7.06922 |
May | 508.00000 | 23.95224 | 37.44376 | -0.5537 | 12.33202 |
June | 496.00000 | 24.15133 | 39.21563 | -0.4391 | 9.47169 |
July | 497.00000 | 24.27494 | 43.81968 | -0.3422 | 7.86036 |
August | 514.00000 | 24.18559 | 47.58456 | -0.3467 | 7.87963 |
September | 485.00000 | 23.98139 | 45.49150 | -0.5065 | 11.14349 |
October | 502.00000 | 23.54958 | 37.69736 | 0.21185 | 6.49545 |
November | 489.00000 | 23.09941 | 36.64663 | 0.08095 | 6.00827 |
December | 497.00000 | 22.59673 | 31.83758 | -0.0782 | 5.69465 |
Annual Sum or Average | 5943.00000 | 23.46184 | 37.24267 | -0.1605 | 7.80675 |
Minimum of Months | 454.00000 | 21.98445 | 30.65817 | -0.5537 | 5.69465 |
Maximum of Months | 514.00000 | 24.27494 | 47.58456 | 0.27119 | 12.33202 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.50743 | 31.64290 | -0.3239 | 7.85229 |
February | 454.00000 | 22.09249 | 31.55496 | -0.1645 | 7.03177 |
March | 514.00000 | 22.80850 | 30.92469 | 0.02827 | 6.20510 |
April | 485.00000 | 23.47721 | 33.11140 | 0.24819 | 7.56495 |
May | 508.00000 | 23.75470 | 37.52493 | -0.5398 | 13.68400 |
June | 496.00000 | 24.02075 | 39.24276 | -0.3878 | 10.13704 |
July | 497.00000 | 24.11347 | 44.02889 | -0.3126 | 8.92052 |
August | 514.00000 | 23.98906 | 47.96386 | -0.3201 | 9.09193 |
September | 485.00000 | 23.73670 | 45.72234 | -0.5003 | 12.83607 |
October | 502.00000 | 23.06735 | 38.10173 | 0.14308 | 6.72326 |
November | 489.00000 | 22.26195 | 37.48541 | -0.0863 | 6.27208 |
December | 497.00000 | 21.74475 | 32.41480 | -0.2547 | 6.95311 |
Annual Sum or Average | 5943.00000 | 23.05545 | 37.51822 | -0.2067 | 8.61555 |
Minimum of Months | 454.00000 | 21.50743 | 30.92469 | -0.5398 | 6.20510 |
Maximum of Months | 514.00000 | 24.11347 | 47.96386 | 0.24819 | 13.68400 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.77447 | 31.33728 | -0.2583 | 8.49365 |
February | 454.00000 | 22.57689 | 30.72171 | -0.0325 | 8.11977 |
March | 514.00000 | 23.06978 | 30.28941 | 0.11603 | 7.21115 |
April | 485.00000 | 23.61150 | 32.73856 | 0.29067 | 8.45376 |
May | 508.00000 | 23.74762 | 37.49374 | -0.5468 | 14.19478 |
June | 496.00000 | 23.99575 | 39.36751 | -0.4332 | 10.71201 |
July | 497.00000 | 24.18648 | 43.81616 | -0.2956 | 8.59061 |
August | 514.00000 | 24.09935 | 47.56345 | -0.2727 | 8.36208 |
September | 485.00000 | 23.92815 | 45.07411 | -0.3916 | 11.36395 |
October | 502.00000 | 23.42607 | 37.17797 | 0.25979 | 8.58185 |
November | 489.00000 | 22.65816 | 36.72655 | 0.01442 | 7.30078 |
December | 497.00000 | 22.20609 | 31.65280 | -0.1338 | 7.56982 |
Annual Sum or Average | 5943.00000 | 23.27863 | 37.04161 | -0.1418 | 9.08639 |
Minimum of Months | 454.00000 | 21.77447 | 30.28941 | -0.5468 | 7.21115 |
Maximum of Months | 514.00000 | 24.18648 | 47.56345 | 0.29067 | 14.19478 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.10428 | 30.40333 | -0.1606 | 6.32782 |
February | 454.00000 | 23.09792 | 29.50407 | 0.10003 | 6.71930 |
March | 514.00000 | 23.94073 | 28.55858 | 0.33394 | 8.07418 |
April | 485.00000 | 24.41195 | 31.03414 | 0.52833 | 11.82286 |
May | 508.00000 | 24.12708 | 36.56195 | -0.3617 | 10.34407 |
June | 496.00000 | 24.35350 | 38.34721 | -0.2193 | 7.50144 |
July | 497.00000 | 24.59073 | 42.62331 | -0.0266 | 7.11861 |
August | 514.00000 | 24.46541 | 46.40750 | -0.0324 | 6.77846 |
September | 485.00000 | 24.21121 | 44.27742 | -0.2891 | 9.09810 |
October | 502.00000 | 23.95369 | 35.91166 | 0.38024 | 8.98706 |
November | 489.00000 | 23.77184 | 34.16150 | 0.29380 | 7.80919 |
December | 497.00000 | 23.67507 | 28.80021 | 0.22834 | 6.73399 |
Annual Sum or Average | 5943.00000 | 23.89685 | 35.59478 | 0.06362 | 8.11013 |
Minimum of Months | 454.00000 | 22.10428 | 28.55858 | -0.3617 | 6.32782 |
Maximum of Months | 514.00000 | 24.59073 | 46.40750 | 0.52833 | 11.82286 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.37406 | 34.30955 | -0.6676 | 16.55730 |
February | 454.00000 | 20.84989 | 34.47132 | -0.5171 | 12.99534 |
March | 514.00000 | 21.76084 | 34.07727 | -0.2730 | 7.88369 |
April | 485.00000 | 22.64786 | 35.90227 | -0.0253 | 6.56695 |
May | 508.00000 | 23.38444 | 39.05367 | -0.7654 | 19.23711 |
June | 496.00000 | 23.80367 | 40.40805 | -0.5880 | 13.12854 |
July | 497.00000 | 23.98883 | 44.75598 | -0.4788 | 10.46424 |
August | 514.00000 | 23.91989 | 48.74495 | -0.4801 | 10.63887 |
September | 485.00000 | 23.42381 | 47.33832 | -0.7144 | 17.21979 |
October | 502.00000 | 22.20029 | 41.24327 | -0.1157 | 6.50421 |
November | 489.00000 | 21.20075 | 40.86587 | -0.3857 | 9.51682 |
December | 497.00000 | 20.62070 | 35.58004 | -0.5857 | 13.22518 |
Annual Sum or Average | 5943.00000 | 22.36023 | 39.76306 | -0.4664 | 11.98814 |
Minimum of Months | 454.00000 | 20.37406 | 34.07727 | -0.7654 | 6.50421 |
Maximum of Months | 514.00000 | 23.98883 | 48.74495 | -0.0253 | 19.23711 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 427.00000 | 20.24651 | 33.07060 | -0.6978 | 17.31492 |
February | 385.00000 | 20.88086 | 33.01056 | -0.5001 | 12.00574 |
March | 433.00000 | 21.64295 | 32.94835 | -0.2723 | 8.10261 |
April | 410.00000 | 22.71653 | 34.45479 | 0.04283 | 7.39908 |
May | 430.00000 | 23.20899 | 38.46295 | -0.7454 | 21.00599 |
June | 418.00000 | 23.73812 | 39.86644 | -0.5067 | 13.76157 |
July | 422.00000 | 23.95358 | 44.14671 | -0.3983 | 11.47864 |
August | 433.00000 | 23.89832 | 48.03080 | -0.3836 | 11.20701 |
September | 410.00000 | 23.21678 | 46.87093 | -0.6967 | 19.42176 |
October | 427.00000 | 22.04176 | 40.33998 | -0.1207 | 7.14749 |
November | 417.00000 | 20.99446 | 39.89244 | -0.4282 | 10.01870 |
December | 422.00000 | 20.52286 | 34.37243 | -0.6079 | 13.75362 |
Annual Sum or Average | 5034.00000 | 22.26349 | 38.82327 | -0.4429 | 12.72070 |
Minimum of Months | 385.00000 | 20.24651 | 32.94835 | -0.7454 | 7.14749 |
Maximum of Months | 433.00000 | 23.95358 | 48.03080 | 0.04283 | 21.00599 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.99708 | 32.57952 | -0.4824 | 13.34210 |
February | 454.00000 | 21.86505 | 32.04382 | -0.2183 | 10.27048 |
March | 514.00000 | 22.35906 | 31.99621 | -0.0589 | 8.28079 |
April | 485.00000 | 23.00686 | 34.21816 | 0.13686 | 8.38167 |
May | 508.00000 | 23.34303 | 38.49456 | -0.6859 | 19.30746 |
June | 496.00000 | 23.63319 | 40.36252 | -0.5661 | 14.58360 |
July | 497.00000 | 23.92707 | 44.54272 | -0.4013 | 11.24324 |
August | 514.00000 | 23.91169 | 48.29017 | -0.3570 | 10.71838 |
September | 485.00000 | 23.61121 | 45.95311 | -0.4938 | 14.87743 |
October | 502.00000 | 22.84984 | 38.67595 | 0.12116 | 8.79132 |
November | 489.00000 | 21.76987 | 38.88712 | -0.2135 | 9.10661 |
December | 497.00000 | 21.32687 | 33.48739 | -0.3775 | 11.23886 |
Annual Sum or Average | 5943.00000 | 22.72385 | 38.33758 | -0.3009 | 11.69248 |
Minimum of Months | 454.00000 | 20.99708 | 31.99621 | -0.6859 | 8.28079 |
Maximum of Months | 514.00000 | 23.92707 | 48.29017 | 0.13686 | 19.30746 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.52997 | 33.11451 | -0.6077 | 14.56003 |
February | 454.00000 | 21.12363 | 33.14284 | -0.4195 | 10.97536 |
March | 514.00000 | 21.85882 | 32.86977 | -0.2036 | 7.73077 |
April | 485.00000 | 22.73585 | 34.81724 | 0.06392 | 7.70394 |
May | 508.00000 | 23.34450 | 38.52676 | -0.6658 | 19.11313 |
June | 496.00000 | 23.66261 | 40.29992 | -0.5215 | 13.62089 |
July | 497.00000 | 24.08010 | 44.11345 | -0.2977 | 10.03595 |
August | 514.00000 | 23.94157 | 48.27913 | -0.3355 | 10.33210 |
September | 485.00000 | 23.43344 | 46.52995 | -0.5898 | 16.46456 |
October | 502.00000 | 22.20649 | 40.17444 | -0.0655 | 6.90488 |
November | 489.00000 | 21.24329 | 39.84921 | -0.3500 | 8.82835 |
December | 497.00000 | 20.82963 | 34.22151 | -0.5118 | 11.47698 |
Annual Sum or Average | 5943.00000 | 22.42657 | 38.86605 | -0.3754 | 11.48219 |
Minimum of Months | 454.00000 | 20.52997 | 32.86977 | -0.6658 | 6.90488 |
Maximum of Months | 514.00000 | 24.08010 | 48.27913 | 0.06392 | 19.11313 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.02391 | 35.03222 | -0.7976 | 21.45948 |
February | 454.00000 | 20.38136 | 35.45736 | -0.6720 | 17.78928 |
March | 514.00000 | 21.12087 | 35.38311 | -0.4499 | 11.33185 |
April | 485.00000 | 22.10461 | 37.08947 | -0.1656 | 7.95366 |
May | 508.00000 | 22.96450 | 40.09155 | -0.9104 | 25.60991 |
June | 496.00000 | 23.58231 | 40.97512 | -0.6615 | 15.95728 |
July | 497.00000 | 23.82287 | 45.16035 | -0.5301 | 12.26951 |
August | 514.00000 | 23.73493 | 49.33819 | -0.5404 | 12.71285 |
September | 485.00000 | 22.95541 | 48.75966 | -0.8764 | 23.82295 |
October | 502.00000 | 21.47902 | 43.08426 | -0.3048 | 8.74188 |
November | 489.00000 | 20.53896 | 42.47365 | -0.5813 | 14.62018 |
December | 497.00000 | 20.10641 | 36.80918 | -0.7595 | 19.57487 |
Annual Sum or Average | 5943.00000 | 21.91432 | 40.83701 | -0.6038 | 15.96982 |
Minimum of Months | 454.00000 | 20.02391 | 35.03222 | -0.9104 | 7.95366 |
Maximum of Months | 514.00000 | 23.82287 | 49.33819 | -0.1656 | 25.60991 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.04018 | 34.23357 | -0.7867 | 21.00519 |
February | 454.00000 | 20.50348 | 34.52267 | -0.6210 | 15.89786 |
March | 514.00000 | 21.32559 | 34.25275 | -0.3679 | 10.41744 |
April | 485.00000 | 22.47529 | 35.52739 | -0.0181 | 8.15837 |
May | 508.00000 | 23.03555 | 39.31459 | -0.7977 | 23.57973 |
June | 496.00000 | 23.65740 | 40.16560 | -0.5172 | 14.41203 |
July | 497.00000 | 23.85340 | 44.68210 | -0.4064 | 11.98137 |
August | 514.00000 | 23.79932 | 48.66133 | -0.3938 | 11.77522 |
September | 485.00000 | 22.98001 | 47.94836 | -0.7712 | 22.77587 |
October | 502.00000 | 21.67705 | 41.74517 | -0.2248 | 8.57714 |
November | 489.00000 | 20.55077 | 41.64563 | -0.5684 | 14.10370 |
December | 497.00000 | 20.14007 | 35.96069 | -0.7433 | 18.99668 |
Annual Sum or Average | 5943.00000 | 22.01596 | 39.92198 | -0.5174 | 15.12666 |
Minimum of Months | 454.00000 | 20.04018 | 34.23357 | -0.7977 | 8.15837 |
Maximum of Months | 514.00000 | 23.85340 | 48.66133 | -0.0181 | 23.57973 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.49555 | 33.51204 | -0.6404 | 17.90457 |
February | 454.00000 | 21.31186 | 33.08134 | -0.3879 | 13.23265 |
March | 514.00000 | 21.85135 | 33.14866 | -0.2077 | 10.42613 |
April | 485.00000 | 22.59320 | 35.19805 | 0.02311 | 9.09027 |
May | 508.00000 | 23.00273 | 39.34683 | -0.8082 | 24.62236 |
June | 496.00000 | 23.41330 | 40.89099 | -0.6383 | 17.62391 |
July | 497.00000 | 23.74443 | 44.98875 | -0.4559 | 13.36683 |
August | 514.00000 | 23.71657 | 48.90371 | -0.4187 | 12.91231 |
September | 485.00000 | 23.23584 | 47.09009 | -0.6272 | 19.99150 |
October | 502.00000 | 22.32940 | 40.09396 | -0.0266 | 9.46842 |
November | 489.00000 | 21.16343 | 40.32107 | -0.3968 | 12.31682 |
December | 497.00000 | 20.72817 | 34.87821 | -0.5646 | 16.24089 |
Annual Sum or Average | 5943.00000 | 22.30740 | 39.32943 | -0.4298 | 14.77992 |
Minimum of Months | 454.00000 | 20.49555 | 33.08134 | -0.8082 | 9.09027 |
Maximum of Months | 514.00000 | 23.74443 | 48.90371 | 0.02311 | 24.62236 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.17196 | 33.86431 | -0.7315 | 19.19717 |
February | 454.00000 | 20.73344 | 33.95093 | -0.5478 | 14.51632 |
March | 514.00000 | 21.42864 | 33.84545 | -0.3311 | 9.91367 |
April | 485.00000 | 22.33770 | 35.74429 | -0.0426 | 8.48463 |
May | 508.00000 | 23.00828 | 39.33702 | -0.7834 | 24.11793 |
June | 496.00000 | 23.43591 | 40.81654 | -0.5943 | 16.48853 |
July | 497.00000 | 23.90426 | 44.53123 | -0.3498 | 11.79790 |
August | 514.00000 | 23.74277 | 48.89177 | -0.3978 | 12.38373 |
September | 485.00000 | 23.05925 | 47.64263 | -0.7199 | 21.52162 |
October | 502.00000 | 21.72563 | 41.47493 | -0.2000 | 8.10999 |
November | 489.00000 | 20.79458 | 40.95509 | -0.4929 | 12.05893 |
December | 497.00000 | 20.40130 | 35.26082 | -0.6561 | 16.11155 |
Annual Sum or Average | 5943.00000 | 22.07337 | 39.73002 | -0.4870 | 14.55671 |
Minimum of Months | 454.00000 | 20.17196 | 33.84545 | -0.7834 | 8.10999 |
Maximum of Months | 514.00000 | 23.90426 | 48.89177 | -0.0426 | 24.11793 |
Report: ChillerReportMonthly
For: COOLSYS1 CHILLER1
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportCHILLER ELECTRICITY ENERGY [J] | CHILLER ELECTRICITY RATE {Maximum} [W] | CHILLER ELECTRICITY RATE {TIMESTAMP} | CHILLER ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | CHILLER EVAPORATOR COOLING ENERGY [J] | CHILLER EVAPORATOR COOLING RATE [] | CHILLER CONDENSER HEAT TRANSFER ENERGY [J] | CHILLER COP [W/W] | CHILLER COP {Maximum} [W/W] | CHILLER COP {TIMESTAMP} | CHILLER PART LOAD RATIO [] | CHILLER PART LOAD RATIO [] | |
January | 55744741.99 | 1136.46 | 13-JAN-06:40 | 13.67 | 0.238678E+09 | 0.00 | 0.294423E+09 | 0.08 | 4.29 | 20-JAN-06:50 | 0.00 | 0.00 |
February | 0.138103E+10 | 80876.28 | 27-FEB-16:00 | 40.02 | 0.785295E+10 | 0.00 | 0.923398E+10 | 0.27 | 7.11 | 27-FEB-16:00 | 0.00 | 0.00 |
March | 0.236412E+10 | 57665.27 | 18-MAR-16:00 | 63.26 | 0.111871E+11 | 0.00 | 0.135512E+11 | 0.37 | 6.19 | 18-MAR-16:00 | 0.00 | 0.00 |
April | 0.150905E+11 | 150306.13 | 27-APR-11:40 | 119.00 | 0.926694E+11 | 0.00 | 0.107760E+12 | 0.84 | 7.57 | 26-APR-16:10 | 0.00 | 0.00 |
May | 0.302261E+11 | 149182.42 | 04-MAY-13:10 | 198.87 | 0.183359E+12 | 0.00 | 0.213585E+12 | 1.40 | 7.57 | 15-MAY-16:30 | 0.00 | 0.00 |
June | 0.547629E+11 | 150963.72 | 27-JUN-13:00 | 309.42 | 0.339432E+12 | 0.00 | 0.394194E+12 | 2.34 | 7.57 | 28-JUN-12:00 | 0.00 | 0.00 |
July | 0.876925E+11 | 153254.99 | 20-JUL-11:50 | 436.87 | 0.578750E+12 | 0.00 | 0.666442E+12 | 3.38 | 7.57 | 06-JUL-15:40 | 0.00 | 0.00 |
August | 0.100820E+12 | 153672.14 | 29-AUG-16:40 | 486.95 | 0.676605E+12 | 0.00 | 0.777425E+12 | 3.81 | 7.57 | 21-AUG-12:40 | 0.00 | 0.00 |
September | 0.445776E+11 | 151307.85 | 15-SEP-12:20 | 261.51 | 0.277309E+12 | 0.00 | 0.321886E+12 | 1.96 | 7.57 | 08-SEP-14:30 | 0.00 | 0.00 |
October | 0.938351E+10 | 136475.66 | 04-OCT-15:00 | 91.86 | 0.528815E+11 | 0.00 | 0.622650E+11 | 0.59 | 7.57 | 04-OCT-14:20 | 0.00 | 0.00 |
November | 0.161180E+10 | 67658.97 | 04-NOV-14:10 | 54.23 | 0.895329E+10 | 0.00 | 0.105651E+11 | 0.34 | 6.69 | 04-NOV-14:10 | 0.00 | 0.00 |
December | 0.160300E+09 | 6861.32 | 16-DEC-06:03 | 38.21 | 0.686142E+09 | 0.00 | 0.846442E+09 | 0.22 | 4.29 | 26-DEC-06:50 | 0.00 | 0.00 |
Annual Sum or Average | 0.348126E+12 | 2113.87 | 0.222992E+13 | 0.00 | 0.257805E+13 | 1.31 | 0.00 | 0.00 | ||||
Minimum of Months | 55744741.99 | 1136.46 | 13.67 | 0.238678E+09 | 0.00 | 0.294423E+09 | 0.08 | 4.29 | 0.00 | 0.00 | ||
Maximum of Months | 0.100820E+12 | 153672.14 | 486.95 | 0.676605E+12 | 0.00 | 0.777425E+12 | 3.81 | 7.57 | 0.00 | 0.00 |
Report: ChillerReportMonthly
For: COOLSYS1 CHILLER2
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportCHILLER ELECTRICITY ENERGY [J] | CHILLER ELECTRICITY RATE {Maximum} [W] | CHILLER ELECTRICITY RATE {TIMESTAMP} | CHILLER ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | CHILLER EVAPORATOR COOLING ENERGY [J] | CHILLER EVAPORATOR COOLING RATE [] | CHILLER CONDENSER HEAT TRANSFER ENERGY [J] | CHILLER COP [W/W] | CHILLER COP {Maximum} [W/W] | CHILLER COP {TIMESTAMP} | CHILLER PART LOAD RATIO [] | CHILLER PART LOAD RATIO [] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 |
April | 0.234262E+10 | 98113.26 | 27-APR-14:40 | 7.33 | 0.169611E+11 | 0.00 | 0.193037E+11 | 0.07 | 7.39 | 27-APR-14:30 | 0.00 | 0.00 |
May | 0.215639E+10 | 96406.87 | 04-MAY-13:50 | 7.17 | 0.153998E+11 | 0.00 | 0.175562E+11 | 0.07 | 7.28 | 04-MAY-15:00 | 0.00 | 0.00 |
June | 0.458723E+10 | 99462.86 | 27-JUN-13:50 | 15.67 | 0.328191E+11 | 0.00 | 0.374063E+11 | 0.15 | 7.40 | 27-JUN-13:50 | 0.00 | 0.00 |
July | 0.118607E+11 | 121353.89 | 31-JUL-16:00 | 35.67 | 0.855185E+11 | 0.00 | 0.973792E+11 | 0.34 | 7.50 | 19-JUL-14:40 | 0.00 | 0.00 |
August | 0.288575E+11 | 129883.33 | 29-AUG-14:30 | 82.00 | 0.208740E+12 | 0.00 | 0.237598E+12 | 0.79 | 7.44 | 14-AUG-16:00 | 0.00 | 0.00 |
September | 0.574213E+10 | 104062.61 | 08-SEP-15:20 | 18.00 | 0.412250E+11 | 0.00 | 0.469671E+11 | 0.18 | 7.47 | 08-SEP-15:20 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.555466E+11 | 165.83 | 0.400664E+12 | 0.00 | 0.456210E+12 | 0.14 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.288575E+11 | 129883.33 | 82.00 | 0.208740E+12 | 0.00 | 0.237598E+12 | 0.79 | 7.50 | 0.00 | 0.00 |
Report: TowerReportMonthly
For: CENTRAL TOWER
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportCOOLING TOWER FAN ELECTRICITY ENERGY [J] | COOLING TOWER FAN ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | COOLING TOWER FAN ELECTRICITY RATE {Maximum} [W] | COOLING TOWER FAN ELECTRICITY RATE {TIMESTAMP} | COOLING TOWER HEAT TRANSFER RATE {Maximum} [W] | COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} | COOLING TOWER INLET TEMPERATURE [C] | COOLING TOWER OUTLET TEMPERATURE [C] | COOLING TOWER MASS FLOW RATE [kg/s] | |
January | 0.147301E+10 | 744.00 | 2863.05 | 11-JAN-15:20 | 34041.12 | 05-JAN-16:20 | 18.65 | 18.33 | 14.30 |
February | 0.546929E+10 | 672.00 | 49248.27 | 27-FEB-13:00 | 113151.91 | 27-FEB-15:10 | 19.33 | 18.34 | 14.30 |
March | 0.117409E+11 | 744.00 | 49248.27 | 09-MAR-12:00 | 283972.96 | 18-MAR-16:02 | 20.06 | 18.35 | 14.30 |
April | 0.327493E+11 | 720.00 | 49248.27 | 01-APR-09:55 | 657829.29 | 27-APR-15:10 | 22.17 | 18.93 | 14.30 |
May | 0.239902E+11 | 744.00 | 49248.27 | 02-MAY-15:30 | 159412.85 | 05-MAY-16:00 | 19.41 | 18.73 | 14.30 |
June | 0.489702E+11 | 720.00 | 49248.27 | 01-JUN-14:00 | 357876.15 | 28-JUN-17:00 | 20.93 | 19.30 | 14.30 |
July | 0.827644E+11 | 744.00 | 49248.27 | 01-JUL-12:20 | 574862.86 | 27-JUL-16:00 | 25.38 | 21.12 | 14.30 |
August | 0.114996E+12 | 744.00 | 49248.27 | 01-AUG-00:10 | 693565.47 | 10-AUG-19:15 | 31.75 | 23.32 | 14.30 |
September | 0.331396E+11 | 720.00 | 49248.27 | 01-SEP-14:20 | 161558.48 | 22-SEP-16:00 | 19.54 | 18.85 | 14.30 |
October | 0.147465E+11 | 744.00 | 49248.27 | 03-OCT-12:30 | 184357.41 | 04-OCT-15:00 | 19.49 | 18.38 | 14.30 |
November | 0.101221E+11 | 720.00 | 49248.27 | 04-NOV-10:30 | 353634.87 | 04-NOV-15:00 | 19.98 | 18.37 | 14.30 |
December | 0.879202E+10 | 744.00 | 14768.57 | 14-DEC-12:00 | 171379.46 | 14-DEC-12:00 | 20.43 | 18.33 | 14.30 |
Annual Sum or Average | 0.388954E+12 | 8760.00 | 21.45 | 19.21 | 14.30 | ||||
Minimum of Months | 0.147301E+10 | 672.00 | 2863.05 | 34041.12 | 18.65 | 18.33 | 14.30 | ||
Maximum of Months | 0.114996E+12 | 744.00 | 49248.27 | 693565.47 | 31.75 | 23.32 | 14.30 |
Report: TowerReportMonthly
For: TOWERWATERSYS COOLTOWER 1
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportCOOLING TOWER FAN ELECTRICITY ENERGY [J] | COOLING TOWER FAN ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | COOLING TOWER FAN ELECTRICITY RATE {Maximum} [W] | COOLING TOWER FAN ELECTRICITY RATE {TIMESTAMP} | COOLING TOWER HEAT TRANSFER RATE {Maximum} [W] | COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} | COOLING TOWER INLET TEMPERATURE [C] | COOLING TOWER OUTLET TEMPERATURE [C] | COOLING TOWER MASS FLOW RATE [kg/s] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 154123.09 | 25-JAN-15:40 | 21.00 | 21.00 | 0.01 |
February | 7033662.85 | 5.50 | 873.72 | 27-FEB-16:00 | 640622.71 | 27-FEB-16:00 | 21.03 | 21.01 | 0.84 |
March | 5134355.66 | 12.11 | 280.60 | 18-MAR-16:00 | 425917.38 | 18-MAR-16:00 | 20.95 | 20.92 | 1.67 |
April | 0.446344E+09 | 60.61 | 16643.55 | 27-APR-11:40 | 1224510.01 | 27-APR-11:40 | 21.21 | 21.02 | 6.34 |
May | 0.721155E+09 | 132.68 | 16643.55 | 04-MAY-13:10 | 1217348.20 | 05-MAY-12:50 | 21.46 | 21.10 | 12.73 |
June | 0.116422E+10 | 236.87 | 16643.55 | 20-JUN-12:20 | 1243024.48 | 27-JUN-13:00 | 21.88 | 21.20 | 21.99 |
July | 0.489240E+10 | 332.03 | 16643.55 | 06-JUL-15:50 | 1289169.45 | 19-JUL-13:40 | 22.31 | 21.21 | 29.49 |
August | 0.832226E+10 | 364.00 | 16643.55 | 07-AUG-09:50 | 1259277.59 | 28-AUG-12:40 | 22.55 | 21.26 | 32.98 |
September | 0.213139E+10 | 193.06 | 16643.55 | 11-SEP-13:00 | 1289357.20 | 08-SEP-15:00 | 21.81 | 21.26 | 18.73 |
October | 52023675.54 | 42.92 | 1864.90 | 04-OCT-15:00 | 1179472.44 | 04-OCT-15:00 | 21.14 | 21.04 | 4.80 |
November | 26292304.08 | 6.96 | 1671.69 | 04-NOV-14:10 | 532732.23 | 04-NOV-14:10 | 20.98 | 20.96 | 0.92 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 223170.25 | 26-DEC-04:04 | 21.03 | 21.03 | 0.17 |
Annual Sum or Average | 0.177683E+11 | 1386.72 | 21.45 | 21.08 | 10.96 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 154123.09 | 20.95 | 20.92 | 0.01 | ||
Maximum of Months | 0.832226E+10 | 364.00 | 16643.55 | 1289357.20 | 22.55 | 21.26 | 32.98 |
Report: TowerReportMonthly
For: TOWERWATERSYS COOLTOWER 2
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportCOOLING TOWER FAN ELECTRICITY ENERGY [J] | COOLING TOWER FAN ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | COOLING TOWER FAN ELECTRICITY RATE {Maximum} [W] | COOLING TOWER FAN ELECTRICITY RATE {TIMESTAMP} | COOLING TOWER HEAT TRANSFER RATE {Maximum} [W] | COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} | COOLING TOWER INLET TEMPERATURE [C] | COOLING TOWER OUTLET TEMPERATURE [C] | COOLING TOWER MASS FLOW RATE [kg/s] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 21.00 | 21.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 21.03 | 21.03 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 20.95 | 20.95 | 0.00 |
April | 0.205286E+09 | 6.00 | 16643.55 | 27-APR-12:20 | 1143072.14 | 26-APR-14:30 | 21.21 | 21.18 | 0.47 |
May | 0.117371E+09 | 5.67 | 16643.55 | 05-MAY-13:00 | 1090246.75 | 04-MAY-15:00 | 21.46 | 21.43 | 0.43 |
June | 0.208384E+09 | 9.83 | 16643.55 | 21-JUN-15:30 | 1098944.76 | 28-JUN-14:20 | 21.88 | 21.82 | 0.77 |
July | 0.163842E+10 | 31.50 | 16643.55 | 07-JUL-12:20 | 1082898.57 | 07-JUL-14:30 | 22.31 | 22.15 | 2.39 |
August | 0.412807E+10 | 72.75 | 16643.55 | 07-AUG-10:40 | 1070050.97 | 29-AUG-14:30 | 22.55 | 22.18 | 5.52 |
September | 0.742577E+09 | 13.50 | 16643.55 | 11-SEP-14:10 | 1074585.98 | 11-SEP-14:10 | 21.81 | 21.74 | 1.06 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 21.14 | 21.14 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 20.98 | 20.98 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 21.03 | 21.03 | 0.00 |
Annual Sum or Average | 0.704011E+10 | 139.25 | 21.45 | 21.39 | 0.90 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 20.95 | 20.95 | 0.00 | ||
Maximum of Months | 0.412807E+10 | 72.75 | 16643.55 | 1143072.14 | 22.55 | 22.18 | 5.52 |
Report: BoilerReportMonthly
For: HEATSYS1 BOILER
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportBOILER HEATING ENERGY [J] | BOILER GAS CONSUMPTION [] | BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] | BOILER HEATING RATE {Maximum} [W] | BOILER HEATING RATE {TIMESTAMP} | BOILER GAS CONSUMPTION RATE [] | BOILER INLET TEMPERATURE [C] | BOILER OUTLET TEMPERATURE [C] | BOILER MASS FLOW RATE [kg/s] | BOILER ANCILLARY ELECTRICITY RATE [W] | BOILER PART LOAD RATIO [] | BOILER PART LOAD RATIO {Maximum} [] | BOILER PART LOAD RATIO {TIMESTAMP} | |
January | 0.280865E+12 | 0.00 | 493.52 | 2187605.85 | 02-JAN-05:11 | 0.00 | 27.84 | 63.60 | 0.50 | 0.00 | 0.05 | 1.00 | 02-JAN-05:11 |
February | 0.147898E+12 | 0.00 | 367.05 | 1532401.55 | 21-FEB-06:03 | 0.00 | 25.71 | 55.81 | 0.28 | 0.00 | 0.03 | 0.70 | 21-FEB-06:03 |
March | 0.465371E+11 | 0.00 | 267.07 | 1478114.30 | 06-MAR-05:11 | 0.00 | 22.91 | 43.81 | 0.08 | 0.00 | 0.01 | 0.67 | 06-MAR-05:11 |
April | 0.161039E+11 | 0.00 | 120.53 | 1171044.54 | 19-APR-05:02 | 0.00 | 22.69 | 32.49 | 0.03 | 0.00 | 0.00 | 0.53 | 19-APR-05:02 |
May | 0.254453E+10 | 0.00 | 55.61 | 768105.06 | 18-MAY-05:03 | 0.00 | 21.59 | 26.07 | 0.00 | 0.00 | 0.00 | 0.35 | 18-MAY-05:03 |
June | 0.213029E+09 | 0.00 | 13.86 | 70083.82 | 14-JUN-05:03 | 0.00 | 20.48 | 21.67 | 0.00 | 0.00 | 0.00 | 0.03 | 14-JUN-05:03 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 20.70 | 20.70 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 8231376.94 | 0.00 | 4.66 | 1375.67 | 03-AUG-05:10 | 0.00 | 20.62 | 21.00 | 0.00 | 0.00 | 0.00 | 0.00 | 03-AUG-05:10 |
September | 0.753539E+09 | 0.00 | 45.00 | 84679.58 | 27-SEP-05:03 | 0.00 | 20.41 | 24.26 | 0.00 | 0.00 | 0.00 | 0.04 | 27-SEP-05:03 |
October | 0.186456E+11 | 0.00 | 194.77 | 1183483.38 | 28-OCT-05:02 | 0.00 | 20.90 | 36.67 | 0.03 | 0.00 | 0.00 | 0.54 | 28-OCT-05:02 |
November | 0.955895E+11 | 0.00 | 336.54 | 1452715.99 | 27-NOV-05:11 | 0.00 | 22.89 | 50.14 | 0.16 | 0.00 | 0.02 | 0.66 | 27-NOV-05:11 |
December | 0.196480E+12 | 0.00 | 427.50 | 1391701.66 | 18-DEC-05:11 | 0.00 | 25.68 | 57.88 | 0.33 | 0.00 | 0.03 | 0.64 | 18-DEC-05:11 |
Annual Sum or Average | 0.805638E+12 | 0.00 | 2326.11 | 0.00 | 22.69 | 37.76 | 0.12 | 0.00 | 0.01 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.41 | 20.70 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.280865E+12 | 0.00 | 493.52 | 2187605.85 | 0.00 | 27.84 | 63.60 | 0.50 | 0.00 | 0.05 | 1.00 |
Report: BoilerReportMonthly
For: CENTRAL BOILER
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportBOILER HEATING ENERGY [J] | BOILER GAS CONSUMPTION [] | BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] | BOILER HEATING RATE {Maximum} [W] | BOILER HEATING RATE {TIMESTAMP} | BOILER GAS CONSUMPTION RATE [] | BOILER INLET TEMPERATURE [C] | BOILER OUTLET TEMPERATURE [C] | BOILER MASS FLOW RATE [kg/s] | BOILER ANCILLARY ELECTRICITY RATE [W] | BOILER PART LOAD RATIO [] | BOILER PART LOAD RATIO [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 18.65 | 18.65 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 19.33 | 19.33 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 20.06 | 20.06 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 22.17 | 22.17 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 19.41 | 19.41 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 20.93 | 20.93 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 25.38 | 25.38 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 31.75 | 31.75 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 19.54 | 19.54 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 19.49 | 19.49 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 19.98 | 19.98 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 20.43 | 20.43 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 21.45 | 21.45 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.65 | 18.65 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.75 | 31.75 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: VAV_BOT WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 736.07 | 0.00 | 0.46 | 736.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.98 | 02-JAN-06:03 | 0.98 | 02-JAN-06:03 | 0.00 | 0.00 | 0.00 |
February | 0.840364E+09 | 0.00 | 9.53 | 0.840364E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 57804.65 | 27-FEB-15:00 | 57804.65 | 27-FEB-15:00 | 0.00 | 0.00 | 0.00 |
March | 0.110992E+10 | 0.00 | 28.80 | 0.110992E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 30441.76 | 18-MAR-16:00 | 30441.76 | 18-MAR-16:00 | 0.00 | 0.00 | 0.00 |
April | 0.107974E+11 | 0.00 | 93.97 | 0.107974E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 131845.78 | 27-APR-14:30 | 131845.78 | 27-APR-14:30 | 0.00 | 0.00 | 0.00 |
May | 0.175815E+11 | 0.00 | 180.59 | 0.175780E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 107416.23 | 04-MAY-15:00 | 107416.23 | 04-MAY-15:00 | 0.00 | 0.00 | 0.00 |
June | 0.342120E+11 | 0.00 | 293.09 | 0.342064E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 119130.45 | 28-JUN-15:20 | 119130.45 | 28-JUN-15:20 | 0.00 | 0.00 | 0.00 |
July | 0.625953E+11 | 0.00 | 412.55 | 0.615638E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 151932.38 | 31-JUL-14:40 | 139248.92 | 31-JUL-14:40 | 0.00 | 0.00 | 0.00 |
August | 0.856034E+11 | 0.00 | 471.54 | 0.826075E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 163941.76 | 29-AUG-14:30 | 147934.89 | 29-AUG-15:10 | 0.00 | 0.00 | 0.00 |
September | 0.274451E+11 | 0.00 | 248.81 | 0.268987E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 122116.13 | 14-SEP-13:00 | 115080.87 | 12-SEP-14:20 | 0.00 | 0.00 | 0.00 |
October | 0.494085E+10 | 0.00 | 74.69 | 0.494085E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 83106.86 | 04-OCT-15:00 | 83106.86 | 04-OCT-15:00 | 0.00 | 0.00 | 0.00 |
November | 0.722474E+09 | 0.00 | 9.91 | 0.722474E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 40066.02 | 04-NOV-14:00 | 40066.02 | 04-NOV-14:00 | 0.00 | 0.00 | 0.00 |
December | 1456.30 | 0.00 | 1.14 | 1456.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.89 | 26-DEC-06:13 | 0.89 | 26-DEC-06:13 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.245848E+12 | 0.00 | 1825.09 | 0.241265E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 736.07 | 0.00 | 0.46 | 736.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.89 | 0.89 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.856034E+11 | 0.00 | 471.54 | 0.826075E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 163941.76 | 147934.89 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: VAV_MID WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 46032.53 | 0.00 | 24.75 | 46032.53 | 0.00 | 0.00 | 0.00 | 0.00 | 3.21 | 18-JAN-06:30 | 3.21 | 18-JAN-06:30 | 0.00 | 0.00 | 0.00 |
February | 0.552779E+10 | 0.00 | 39.39 | 0.552779E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 396423.28 | 27-FEB-15:00 | 396423.28 | 27-FEB-15:00 | 0.00 | 0.00 | 0.00 |
March | 0.826430E+10 | 0.00 | 59.78 | 0.826430E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 285453.90 | 18-MAR-16:00 | 285453.90 | 18-MAR-16:00 | 0.00 | 0.00 | 0.00 |
April | 0.828809E+11 | 0.00 | 104.47 | 0.828809E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 1121146.08 | 27-APR-14:40 | 1121146.08 | 27-APR-14:40 | 0.00 | 0.00 | 0.00 |
May | 0.153180E+12 | 0.00 | 184.28 | 0.153144E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1010200.20 | 04-MAY-15:00 | 1010200.20 | 04-MAY-15:00 | 0.00 | 0.00 | 0.00 |
June | 0.283078E+12 | 0.00 | 285.83 | 0.283052E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1075038.06 | 28-JUN-15:30 | 1075038.06 | 28-JUN-15:30 | 0.00 | 0.00 | 0.00 |
July | 0.503780E+12 | 0.00 | 376.11 | 0.496657E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1358525.19 | 31-JUL-16:00 | 1212826.52 | 31-JUL-15:20 | 0.00 | 0.00 | 0.00 |
August | 0.670024E+12 | 0.00 | 394.24 | 0.647696E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1449146.03 | 29-AUG-14:30 | 1325210.59 | 29-AUG-15:30 | 0.00 | 0.00 | 0.00 |
September | 0.247875E+12 | 0.00 | 246.91 | 0.241423E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1191956.53 | 14-SEP-13:00 | 1085090.13 | 12-SEP-14:50 | 0.00 | 0.00 | 0.00 |
October | 0.401280E+11 | 0.00 | 81.34 | 0.401280E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 735473.18 | 04-OCT-15:00 | 735473.18 | 04-OCT-15:00 | 0.00 | 0.00 | 0.00 |
November | 0.640785E+10 | 0.00 | 52.05 | 0.640785E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 355900.74 | 04-NOV-14:10 | 355900.74 | 04-NOV-14:10 | 0.00 | 0.00 | 0.00 |
December | 83990.50 | 0.00 | 37.94 | 83990.50 | 0.00 | 0.00 | 0.00 | 0.00 | 3.11 | 30-DEC-12:50 | 3.11 | 30-DEC-12:50 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.200115E+13 | 0.00 | 1887.11 | 0.196518E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 46032.53 | 0.00 | 24.75 | 46032.53 | 0.00 | 0.00 | 0.00 | 0.00 | 3.11 | 3.11 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.670024E+12 | 0.00 | 394.24 | 0.647696E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1449146.03 | 1325210.59 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: VAV_TOP WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 56866.44 | 0.00 | 1.14 | 56866.44 | 0.00 | 0.00 | 0.00 | 0.00 | 338.84 | 09-JAN-04:52 | 338.84 | 09-JAN-04:52 | 0.00 | 0.00 | 0.00 |
February | 0.463910E+09 | 0.00 | 9.50 | 0.463910E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 31501.52 | 27-FEB-15:00 | 31501.52 | 27-FEB-15:00 | 0.00 | 0.00 | 0.00 |
March | 0.742032E+09 | 0.00 | 27.23 | 0.742032E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 28007.08 | 18-MAR-16:00 | 28007.08 | 18-MAR-16:00 | 0.00 | 0.00 | 0.00 |
April | 0.856015E+10 | 0.00 | 79.45 | 0.856015E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 131094.23 | 27-APR-14:30 | 131094.23 | 27-APR-14:30 | 0.00 | 0.00 | 0.00 |
May | 0.157180E+11 | 0.00 | 170.70 | 0.157151E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 110752.76 | 04-MAY-15:00 | 110752.76 | 04-MAY-15:00 | 0.00 | 0.00 | 0.00 |
June | 0.296458E+11 | 0.00 | 275.95 | 0.296436E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 127721.15 | 28-JUN-15:20 | 127721.15 | 28-JUN-15:20 | 0.00 | 0.00 | 0.00 |
July | 0.535315E+11 | 0.00 | 364.76 | 0.528186E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 155320.98 | 31-JUL-16:00 | 142250.46 | 31-JUL-14:50 | 0.00 | 0.00 | 0.00 |
August | 0.702697E+11 | 0.00 | 386.53 | 0.681700E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 170605.04 | 13-AUG-14:21 | 153342.92 | 10-AUG-15:10 | 0.00 | 0.00 | 0.00 |
September | 0.242451E+11 | 0.00 | 236.06 | 0.238040E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 119880.09 | 14-SEP-13:10 | 113053.77 | 12-SEP-15:20 | 0.00 | 0.00 | 0.00 |
October | 0.348473E+10 | 0.00 | 63.04 | 0.348473E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 72985.60 | 04-OCT-15:00 | 72985.60 | 04-OCT-15:00 | 0.00 | 0.00 | 0.00 |
November | 0.628742E+09 | 0.00 | 8.87 | 0.628742E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 34984.32 | 04-NOV-14:00 | 34984.32 | 04-NOV-14:00 | 0.00 | 0.00 | 0.00 |
December | 85.53 | 0.00 | 0.08 | 85.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.29 | 12-DEC-04:50 | 0.29 | 12-DEC-04:50 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.207290E+12 | 0.00 | 1623.30 | 0.204031E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 85.53 | 0.00 | 0.08 | 85.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.29 | 0.29 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.702697E+11 | 0.00 | 386.53 | 0.681700E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 170605.04 | 153342.92 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: CAV_BAS COOLING COIL
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 3148880.28 | 0.00 | 0.09 | 3148880.28 | 0.00 | 0.00 | 0.00 | 0.00 | 10309.93 | 11-JAN-05:12 | 10309.93 | 11-JAN-05:12 | 0.00 | 0.00 | 0.00 |
February | 0.460191E+09 | 0.00 | 6.80 | 0.449769E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 51108.07 | 24-FEB-06:02 | 34391.54 | 24-FEB-05:12 | 0.00 | 0.00 | 0.00 |
March | 0.129088E+09 | 0.00 | 5.54 | 0.117366E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 41243.35 | 10-MAR-06:03 | 20065.88 | 09-MAR-05:12 | 0.00 | 0.00 | 0.00 |
April | 0.423654E+10 | 0.00 | 44.75 | 0.423051E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 63625.30 | 27-APR-16:00 | 63625.30 | 27-APR-16:00 | 0.00 | 0.00 | 0.00 |
May | 0.800834E+10 | 0.00 | 96.54 | 0.798632E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 62338.51 | 15-MAY-16:00 | 62338.51 | 15-MAY-16:00 | 0.00 | 0.00 | 0.00 |
June | 0.167524E+11 | 0.00 | 190.82 | 0.166860E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 67060.83 | 12-JUN-04:12 | 61964.21 | 28-JUN-15:10 | 0.00 | 0.00 | 0.00 |
July | 0.314443E+11 | 0.00 | 272.99 | 0.311055E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 119093.84 | 30-JUL-16:50 | 104399.28 | 30-JUL-16:50 | 0.00 | 0.00 | 0.00 |
August | 0.440211E+11 | 0.00 | 310.69 | 0.433886E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 121185.98 | 13-AUG-16:54 | 106961.08 | 13-AUG-16:54 | 0.00 | 0.00 | 0.00 |
September | 0.129255E+11 | 0.00 | 154.22 | 0.128028E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 68446.80 | 01-SEP-04:12 | 62066.48 | 12-SEP-14:00 | 0.00 | 0.00 | 0.00 |
October | 0.170447E+10 | 0.00 | 35.75 | 0.168239E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 43546.39 | 26-OCT-04:12 | 43242.07 | 04-OCT-15:00 | 0.00 | 0.00 | 0.00 |
November | 0.282626E+09 | 0.00 | 5.27 | 0.267546E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 49153.86 | 04-NOV-04:12 | 29268.49 | 04-NOV-04:12 | 0.00 | 0.00 | 0.00 |
December | 7063244.24 | 0.00 | 0.18 | 6377953.92 | 0.00 | 0.00 | 0.00 | 0.00 | 19265.78 | 16-DEC-06:03 | 14697.18 | 16-DEC-06:03 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.119975E+12 | 0.00 | 1123.64 | 0.118726E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 3148880.28 | 0.00 | 0.09 | 3148880.28 | 0.00 | 0.00 | 0.00 | 0.00 | 10309.93 | 10309.93 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.440211E+11 | 0.00 | 310.69 | 0.433886E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 121185.98 | 106961.08 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: AIRLOOP DATACENTER BASEMENT COOLING COIL
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.437180E+10 | 0.365518E+10 | 740.50 | 0.437169E+10 | 113413.11 | 0.00 | 0.02 | 09-JAN-12:00 | 0.01 | 11-JAN-22:40 | 3024.82 | 09-JAN-12:00 | 3024.82 | 09-JAN-12:00 | 10.93 | 11-JAN-23:00 | 1751.01 | 09-JAN-12:00 | 0.00 |
February | 0.695535E+10 | 0.422890E+10 | 594.94 | 0.688840E+10 | 66950337.92 | 0.00 | 0.13 | 27-FEB-15:00 | 0.01 | 28-FEB-05:27 | 39713.26 | 27-FEB-15:00 | 39713.26 | 27-FEB-15:00 | 673.79 | 27-FEB-16:00 | 13051.78 | 27-FEB-15:00 | 0.00 |
March | 0.142125E+11 | 0.676950E+10 | 693.82 | 0.134955E+11 | 0.716983E+09 | 0.00 | 0.46 | 18-MAR-16:00 | 0.01 | 11-MAR-06:03 | 145247.12 | 18-MAR-16:00 | 145247.12 | 18-MAR-16:00 | 11811.38 | 09-MAR-12:00 | 47839.24 | 18-MAR-16:00 | 0.00 |
April | 0.104986E+12 | 0.341274E+11 | 665.62 | 0.964204E+11 | 0.856575E+10 | 0.00 | 1.00 | 01-APR-14:50 | 0.01 | 30-APR-23:43 | 389000.90 | 27-APR-15:00 | 389000.90 | 27-APR-15:00 | 83184.89 | 28-APR-13:00 | 129621.37 | 27-APR-15:10 | 0.00 |
May | 0.514281E+10 | 0.414418E+10 | 482.56 | 0.484263E+10 | 0.300179E+09 | 0.00 | 0.25 | 05-MAY-16:00 | 0.01 | 15-MAY-21:30 | 88315.05 | 05-MAY-16:00 | 76341.97 | 05-MAY-16:00 | 12539.13 | 06-MAY-13:00 | 28550.85 | 05-MAY-16:00 | 0.00 |
June | 0.416097E+11 | 0.156399E+11 | 373.43 | 0.394260E+11 | 0.218374E+10 | 0.00 | 0.58 | 28-JUN-17:00 | 0.01 | 25-JUN-20:37 | 211667.88 | 28-JUN-17:00 | 211667.88 | 28-JUN-17:00 | 18088.30 | 21-JUN-17:00 | 70813.01 | 28-JUN-17:00 | 0.00 |
July | 0.251124E+12 | 0.770923E+11 | 619.85 | 0.209726E+12 | 0.413975E+11 | 0.00 | 0.88 | 27-JUL-16:00 | 0.01 | 19-JUL-07:05 | 355718.64 | 27-JUL-16:00 | 314414.06 | 24-JUL-15:00 | 89262.62 | 27-JUL-19:00 | 114642.79 | 24-JUL-15:00 | 0.00 |
August | 0.626898E+12 | 0.183030E+12 | 733.46 | 0.485673E+12 | 0.141225E+12 | 0.00 | 1.00 | 07-AUG-11:40 | 0.01 | 18-AUG-04:27 | 413266.82 | 29-AUG-13:00 | 398387.95 | 08-AUG-17:20 | 186038.45 | 30-AUG-08:30 | 142221.92 | 10-AUG-17:00 | 0.00 |
September | 0.469211E+10 | 0.427434E+10 | 242.86 | 0.393888E+10 | 0.753230E+09 | 0.00 | 0.26 | 22-SEP-16:00 | 0.01 | 27-SEP-07:15 | 90510.36 | 22-SEP-16:00 | 76937.83 | 22-SEP-16:00 | 13863.35 | 15-SEP-16:00 | 29094.84 | 22-SEP-16:00 | 0.00 |
October | 0.453200E+10 | 0.386850E+10 | 502.59 | 0.439617E+10 | 0.135829E+09 | 0.00 | 0.29 | 04-OCT-15:00 | 0.01 | 08-OCT-19:10 | 87624.13 | 04-OCT-15:00 | 87624.13 | 04-OCT-15:00 | 6304.52 | 08-OCT-13:52 | 29610.66 | 04-OCT-15:00 | 0.00 |
November | 0.116969E+11 | 0.583078E+10 | 556.01 | 0.976269E+10 | 0.193422E+10 | 0.00 | 0.55 | 04-NOV-15:00 | 0.01 | 20-NOV-22:17 | 203494.38 | 04-NOV-15:00 | 152901.48 | 04-NOV-15:00 | 57191.61 | 04-NOV-16:00 | 58963.15 | 04-NOV-15:00 | 0.00 |
December | 0.139065E+11 | 0.686768E+10 | 723.53 | 0.127554E+11 | 0.115112E+10 | 0.00 | 0.18 | 14-DEC-12:00 | 0.01 | 29-DEC-05:15 | 50881.23 | 14-DEC-12:00 | 49466.51 | 14-DEC-12:00 | 2022.59 | 14-DEC-12:20 | 16346.40 | 14-DEC-12:00 | 0.00 |
Annual Sum or Average | 0.109013E+13 | 0.349529E+12 | 6929.17 | 0.891697E+12 | 0.198431E+12 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.437180E+10 | 0.365518E+10 | 242.86 | 0.393888E+10 | 113413.11 | 0.00 | 0.02 | 0.01 | 3024.82 | 3024.82 | 10.93 | 1751.01 | 0.00 | ||||||
Maximum of Months | 0.626898E+12 | 0.183030E+12 | 740.50 | 0.485673E+12 | 0.141225E+12 | 0.00 | 1.00 | 0.01 | 413266.82 | 398387.95 | 186038.45 | 142221.92 | 0.00 |
Report: DXReportMonthly
For: AIRLOOP DATACENTER BOT COOLING COIL
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.399559E+10 | 0.104308E+10 | 744.00 | 0.399526E+10 | 332430.87 | 0.00 | 0.27 | 05-JAN-16:10 | 0.11 | 17-JAN-07:10 | 2300.84 | 05-JAN-16:10 | 2300.84 | 05-JAN-16:10 | 14.27 | 02-JAN-07:10 | 571.80 | 05-JAN-16:10 | 0.00 |
February | 0.877191E+10 | 0.212579E+10 | 672.00 | 0.876152E+10 | 10392743.23 | 0.00 | 0.52 | 12-FEB-16:43 | 0.34 | 18-FEB-08:00 | 4593.96 | 27-FEB-16:20 | 4579.89 | 27-FEB-16:20 | 128.68 | 24-FEB-11:10 | 1111.16 | 27-FEB-16:10 | 0.00 |
March | 0.154069E+11 | 0.354913E+10 | 744.00 | 0.153986E+11 | 8343429.24 | 0.00 | 0.78 | 31-MAR-24:00 | 0.55 | 01-MAR-07:10 | 7576.47 | 31-MAR-24:00 | 7576.47 | 31-MAR-24:00 | 136.58 | 09-MAR-17:00 | 1657.53 | 18-MAR-17:02 | 0.00 |
April | 0.201714E+11 | 0.451157E+10 | 720.00 | 0.201582E+11 | 13203484.71 | 0.00 | 0.97 | 01-APR-17:42 | 0.29 | 30-APR-24:00 | 8905.82 | 26-APR-18:00 | 8905.82 | 26-APR-18:00 | 162.88 | 28-APR-11:10 | 2779.46 | 01-APR-17:01 | 0.00 |
May | 0.578728E+10 | 0.144433E+10 | 744.00 | 0.575028E+10 | 37003568.80 | 0.00 | 0.44 | 31-MAY-24:00 | 0.17 | 18-MAY-06:10 | 4077.32 | 31-MAY-24:00 | 4069.18 | 31-MAY-24:00 | 135.99 | 05-MAY-17:00 | 937.27 | 31-MAY-24:00 | 0.00 |
June | 0.107530E+11 | 0.257065E+10 | 720.00 | 0.106993E+11 | 53726932.60 | 0.00 | 0.62 | 30-JUN-24:00 | 0.40 | 14-JUN-06:10 | 5948.48 | 30-JUN-24:00 | 5942.30 | 30-JUN-24:00 | 194.38 | 12-JUN-15:00 | 1489.70 | 28-JUN-16:00 | 0.00 |
July | 0.165028E+11 | 0.400532E+10 | 744.00 | 0.163862E+11 | 0.116658E+09 | 0.00 | 0.84 | 30-JUL-18:31 | 0.59 | 01-JUL-07:00 | 7880.91 | 31-JUL-23:55 | 7850.78 | 31-JUL-23:27 | 255.83 | 11-JUL-09:40 | 2389.24 | 30-JUL-18:01 | 0.00 |
August | 0.215475E+11 | 0.541621E+10 | 744.00 | 0.213904E+11 | 0.157009E+09 | 0.00 | 1.00 | 10-AUG-17:50 | 0.29 | 31-AUG-24:00 | 9445.25 | 06-AUG-18:43 | 9445.25 | 06-AUG-18:43 | 261.97 | 30-AUG-08:00 | 3197.46 | 10-AUG-17:50 | 0.00 |
September | 0.578331E+10 | 0.142809E+10 | 720.00 | 0.569098E+10 | 92335870.30 | 0.00 | 0.43 | 30-SEP-24:00 | 0.18 | 28-SEP-06:35 | 3906.72 | 30-SEP-24:00 | 3905.53 | 30-SEP-24:00 | 175.98 | 13-SEP-14:40 | 902.02 | 30-SEP-24:00 | 0.00 |
October | 0.105283E+11 | 0.246426E+10 | 744.00 | 0.105056E+11 | 22763633.43 | 0.00 | 0.60 | 31-OCT-24:00 | 0.36 | 28-OCT-07:00 | 5575.83 | 31-OCT-24:00 | 5575.83 | 31-OCT-24:00 | 136.30 | 26-OCT-14:10 | 1330.50 | 04-OCT-16:50 | 0.00 |
November | 0.147607E+11 | 0.335005E+10 | 720.00 | 0.147371E+11 | 23613915.65 | 0.00 | 0.68 | 04-NOV-16:00 | 0.56 | 13-NOV-07:10 | 6433.73 | 04-NOV-16:00 | 6422.43 | 12-NOV-16:00 | 165.17 | 03-NOV-16:00 | 1637.00 | 04-NOV-15:50 | 0.00 |
December | 0.200623E+11 | 0.448020E+10 | 744.00 | 0.200599E+11 | 2370922.76 | 0.00 | 0.87 | 03-DEC-15:23 | 0.73 | 16-DEC-18:00 | 8213.93 | 10-DEC-15:50 | 8213.93 | 10-DEC-15:50 | 85.28 | 28-DEC-15:00 | 1825.49 | 03-DEC-15:23 | 0.00 |
Annual Sum or Average | 0.154071E+12 | 0.363887E+11 | 8760.00 | 0.153533E+12 | 0.537754E+09 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.399559E+10 | 0.104308E+10 | 672.00 | 0.399526E+10 | 332430.87 | 0.00 | 0.27 | 0.11 | 2300.84 | 2300.84 | 14.27 | 571.80 | 0.00 | ||||||
Maximum of Months | 0.215475E+11 | 0.541621E+10 | 744.00 | 0.213904E+11 | 0.157009E+09 | 0.00 | 1.00 | 0.73 | 9445.25 | 9445.25 | 261.97 | 3197.46 | 0.00 |
Report: DXReportMonthly
For: AIRLOOP DATACENTER MID COOLING COIL
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.154744E+11 | 0.434780E+10 | 656.53 | 0.154737E+11 | 704977.39 | 0.00 | 0.23 | 20-JAN-16:20 | 0.00 | 01-JAN-00:03 | 18437.12 | 05-JAN-16:20 | 18437.12 | 05-JAN-16:20 | 60.43 | 02-JAN-14:20 | 4651.64 | 05-JAN-16:20 | 0.00 |
February | 0.661330E+11 | 0.163450E+11 | 672.00 | 0.660312E+11 | 0.101792E+09 | 0.00 | 0.48 | 08-FEB-16:50 | 0.21 | 21-FEB-07:10 | 42081.65 | 27-FEB-16:20 | 41929.57 | 27-FEB-16:20 | 1245.59 | 24-FEB-11:10 | 10218.23 | 27-FEB-16:20 | 0.00 |
March | 0.132616E+12 | 0.309296E+11 | 744.00 | 0.132533E+12 | 83291634.88 | 0.00 | 0.72 | 31-MAR-23:40 | 0.46 | 06-MAR-07:10 | 66740.27 | 31-MAR-23:40 | 66740.27 | 31-MAR-23:40 | 1352.08 | 09-MAR-17:00 | 15293.36 | 18-MAR-17:02 | 0.00 |
April | 0.182830E+12 | 0.412358E+11 | 720.00 | 0.182696E+12 | 0.133235E+09 | 0.00 | 0.95 | 26-APR-18:00 | 0.21 | 30-APR-24:00 | 85041.56 | 26-APR-18:00 | 85041.56 | 26-APR-18:00 | 1622.67 | 28-APR-11:10 | 26366.93 | 27-APR-16:00 | 0.00 |
May | 0.485722E+11 | 0.122648E+11 | 744.00 | 0.482100E+11 | 0.362136E+09 | 0.00 | 0.43 | 31-MAY-23:40 | 0.11 | 18-MAY-06:10 | 38069.38 | 31-MAY-23:30 | 37945.41 | 31-MAY-23:50 | 1333.83 | 05-MAY-16:10 | 8773.35 | 31-MAY-23:40 | 0.00 |
June | 0.977718E+11 | 0.235205E+11 | 720.00 | 0.972400E+11 | 0.531856E+09 | 0.00 | 0.61 | 30-JUN-24:00 | 0.35 | 14-JUN-06:40 | 55792.96 | 30-JUN-24:00 | 55726.90 | 30-JUN-24:00 | 1933.94 | 12-JUN-15:00 | 14138.27 | 28-JUN-16:00 | 0.00 |
July | 0.154309E+12 | 0.376075E+11 | 744.00 | 0.153157E+12 | 0.115236E+10 | 0.00 | 0.83 | 30-JUL-18:21 | 0.56 | 03-JUL-06:30 | 76054.54 | 31-JUL-23:55 | 75730.93 | 31-JUL-24:00 | 2531.75 | 11-JUL-09:40 | 22551.16 | 30-JUL-18:11 | 0.00 |
August | 0.202997E+12 | 0.512136E+11 | 744.00 | 0.201440E+12 | 0.155720E+10 | 0.00 | 1.00 | 10-AUG-18:00 | 0.24 | 31-AUG-24:00 | 88649.03 | 06-AUG-18:32 | 88649.03 | 06-AUG-18:32 | 2609.10 | 30-AUG-08:00 | 30737.56 | 10-AUG-17:50 | 0.00 |
September | 0.492305E+11 | 0.122887E+11 | 720.00 | 0.483295E+11 | 0.901065E+09 | 0.00 | 0.40 | 30-SEP-23:40 | 0.13 | 28-SEP-06:45 | 34700.28 | 30-SEP-23:40 | 34677.86 | 30-SEP-23:40 | 1746.91 | 13-SEP-14:40 | 8467.48 | 14-SEP-17:00 | 0.00 |
October | 0.880421E+11 | 0.208697E+11 | 744.00 | 0.878172E+11 | 0.224856E+09 | 0.00 | 0.56 | 04-OCT-16:50 | 0.29 | 30-OCT-06:10 | 48436.32 | 04-OCT-16:50 | 48436.32 | 04-OCT-16:50 | 1324.72 | 26-OCT-14:10 | 12648.52 | 04-OCT-16:50 | 0.00 |
November | 0.122684E+12 | 0.282838E+11 | 720.00 | 0.122449E+12 | 0.234535E+09 | 0.00 | 0.65 | 04-NOV-16:00 | 0.45 | 24-NOV-07:10 | 58920.62 | 04-NOV-16:00 | 57748.11 | 04-NOV-16:00 | 1637.55 | 03-NOV-16:00 | 15061.38 | 04-NOV-15:50 | 0.00 |
December | 0.168447E+12 | 0.382727E+11 | 744.00 | 0.168423E+12 | 24003721.02 | 0.00 | 0.81 | 05-DEC-15:50 | 0.59 | 26-DEC-07:10 | 74818.78 | 05-DEC-15:50 | 74818.78 | 05-DEC-15:50 | 841.74 | 28-DEC-15:00 | 16532.27 | 05-DEC-15:50 | 0.00 |
Annual Sum or Average | 0.132911E+13 | 0.317179E+12 | 8672.53 | 0.132380E+13 | 0.530704E+10 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.154744E+11 | 0.434780E+10 | 656.53 | 0.154737E+11 | 704977.39 | 0.00 | 0.23 | 0.00 | 18437.12 | 18437.12 | 60.43 | 4651.64 | 0.00 | ||||||
Maximum of Months | 0.202997E+12 | 0.512136E+11 | 744.00 | 0.201440E+12 | 0.155720E+10 | 0.00 | 1.00 | 0.59 | 88649.03 | 88649.03 | 2609.10 | 30737.56 | 0.00 |
Report: DXReportMonthly
For: AIRLOOP DATACENTER TOP COOLING COIL
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.698593E+09 | 0.202235E+09 | 386.13 | 0.698556E+09 | 36796.36 | 0.00 | 0.22 | 05-JAN-16:20 | 0.00 | 01-JAN-00:03 | 1783.26 | 05-JAN-16:20 | 1783.26 | 05-JAN-16:20 | 4.07 | 02-JAN-13:10 | 451.71 | 05-JAN-16:20 | 0.00 |
February | 0.518537E+10 | 0.129951E+10 | 671.69 | 0.517528E+10 | 10082012.68 | 0.00 | 0.47 | 27-FEB-16:20 | 0.00 | 19-FEB-04:55 | 4187.39 | 27-FEB-16:30 | 4171.73 | 27-FEB-16:20 | 123.65 | 24-FEB-11:20 | 1018.62 | 27-FEB-16:20 | 0.00 |
March | 0.120704E+11 | 0.284396E+10 | 744.00 | 0.120621E+11 | 8266557.11 | 0.00 | 0.68 | 01-MAR-17:00 | 0.32 | 06-MAR-05:11 | 6248.31 | 31-MAR-23:20 | 6248.31 | 31-MAR-23:20 | 134.84 | 09-MAR-17:00 | 1507.04 | 18-MAR-17:02 | 0.00 |
April | 0.175261E+11 | 0.398260E+10 | 720.00 | 0.175129E+11 | 13261893.00 | 0.00 | 0.94 | 26-APR-17:50 | 0.16 | 30-APR-24:00 | 8586.18 | 26-APR-18:00 | 8586.18 | 26-APR-18:00 | 161.97 | 28-APR-11:10 | 2672.27 | 27-APR-16:00 | 0.00 |
May | 0.433752E+10 | 0.110672E+10 | 743.58 | 0.430154E+10 | 35978771.85 | 0.00 | 0.42 | 31-MAY-23:20 | 0.00 | 18-MAY-03:15 | 3736.97 | 31-MAY-23:20 | 3720.24 | 31-MAY-23:20 | 134.50 | 05-MAY-16:10 | 867.73 | 14-MAY-18:02 | 0.00 |
June | 0.954232E+10 | 0.230594E+10 | 720.00 | 0.948911E+10 | 53210078.28 | 0.00 | 0.59 | 30-JUN-23:40 | 0.30 | 14-JUN-06:10 | 5483.66 | 30-JUN-23:40 | 5476.93 | 30-JUN-23:40 | 193.46 | 12-JUN-15:00 | 1448.08 | 28-JUN-16:00 | 0.00 |
July | 0.152836E+11 | 0.374053E+10 | 744.00 | 0.151683E+11 | 0.115264E+09 | 0.00 | 0.84 | 30-JUL-18:21 | 0.53 | 18-JUL-06:05 | 7582.44 | 31-JUL-23:03 | 7547.69 | 31-JUL-23:45 | 252.56 | 11-JUL-09:40 | 2318.64 | 30-JUL-18:01 | 0.00 |
August | 0.201246E+11 | 0.510038E+10 | 744.00 | 0.199691E+11 | 0.155540E+09 | 0.00 | 1.00 | 10-AUG-18:00 | 0.22 | 31-AUG-24:00 | 8979.46 | 06-AUG-18:23 | 8979.46 | 06-AUG-18:23 | 260.01 | 30-AUG-08:00 | 3113.97 | 10-AUG-17:50 | 0.00 |
September | 0.440774E+10 | 0.111254E+10 | 720.00 | 0.431876E+10 | 88977227.94 | 0.00 | 0.37 | 10-SEP-17:22 | 0.06 | 27-SEP-06:10 | 3200.18 | 10-SEP-17:25 | 3188.56 | 10-SEP-17:25 | 177.59 | 14-SEP-11:00 | 865.92 | 14-SEP-17:00 | 0.00 |
October | 0.771641E+10 | 0.185035E+10 | 744.00 | 0.769426E+10 | 22150529.81 | 0.00 | 0.56 | 04-OCT-16:50 | 0.19 | 16-OCT-06:10 | 4879.72 | 04-OCT-16:50 | 4879.72 | 04-OCT-16:50 | 130.66 | 26-OCT-14:10 | 1275.12 | 04-OCT-16:50 | 0.00 |
November | 0.108063E+11 | 0.252385E+10 | 720.00 | 0.107831E+11 | 23274821.56 | 0.00 | 0.64 | 04-NOV-16:00 | 0.31 | 13-NOV-04:20 | 5825.12 | 04-NOV-16:00 | 5708.43 | 04-NOV-16:00 | 163.39 | 03-NOV-16:00 | 1493.02 | 04-NOV-15:50 | 0.00 |
December | 0.151001E+11 | 0.347802E+10 | 744.00 | 0.150977E+11 | 2378784.17 | 0.00 | 0.79 | 05-DEC-16:00 | 0.44 | 26-DEC-04:04 | 7333.51 | 05-DEC-16:00 | 7333.51 | 05-DEC-16:00 | 83.82 | 28-DEC-15:10 | 1627.56 | 05-DEC-16:00 | 0.00 |
Annual Sum or Average | 0.122799E+12 | 0.295466E+11 | 8401.40 | 0.122271E+12 | 0.528421E+09 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.698593E+09 | 0.202235E+09 | 386.13 | 0.698556E+09 | 36796.36 | 0.00 | 0.22 | 0.00 | 1783.26 | 1783.26 | 4.07 | 451.71 | 0.00 | ||||||
Maximum of Months | 0.201246E+11 | 0.510038E+10 | 744.00 | 0.199691E+11 | 0.155540E+09 | 0.00 | 1.00 | 0.53 | 8979.46 | 8979.46 | 260.01 | 3113.97 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 98.55 | 0.00 | 98.55 | 0.89 | 694.53 | 0.00 | 0.00 | 0.00 |
February | 153.34 | 0.00 | 153.34 | 17.33 | 613.75 | 0.00 | 0.00 | 0.00 |
March | 225.93 | 0.00 | 225.93 | 70.61 | 501.62 | 0.00 | 0.00 | 0.00 |
April | 319.71 | 1.13 | 318.57 | 177.77 | 393.69 | 0.00 | 0.00 | 0.00 |
May | 411.38 | 12.22 | 399.16 | 306.77 | 301.92 | 0.00 | 0.00 | 0.00 |
June | 432.56 | 28.56 | 403.99 | 360.61 | 232.97 | 0.00 | 0.00 | 0.00 |
July | 411.12 | 32.23 | 378.89 | 390.10 | 209.25 | 0.00 | 0.00 | 0.00 |
August | 332.81 | 9.00 | 323.81 | 319.84 | 205.84 | 0.00 | 0.00 | 0.00 |
September | 258.51 | 0.08 | 258.44 | 180.43 | 309.32 | 0.00 | 0.00 | 0.00 |
October | 177.12 | 0.00 | 177.12 | 61.54 | 439.71 | 0.00 | 0.00 | 0.00 |
November | 111.57 | 0.00 | 111.57 | 7.75 | 579.56 | 0.00 | 0.00 | 0.00 |
December | 83.74 | 0.00 | 83.74 | 0.18 | 717.42 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 251.85 | 6.99 | 244.86 | 158.71 | 432.41 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 83.74 | 0.00 | 83.74 | 0.18 | 205.84 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 432.56 | 32.23 | 403.99 | 390.10 | 717.42 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 98.55 | 0.00 | 98.55 | 0.89 | 694.53 | 0.00 | 0.00 | 0.00 |
February | 153.34 | 0.00 | 153.34 | 17.33 | 613.75 | 0.00 | 0.00 | 0.00 |
March | 225.93 | 0.00 | 225.93 | 70.61 | 501.62 | 0.00 | 0.00 | 0.00 |
April | 319.71 | 1.13 | 318.57 | 177.77 | 393.69 | 0.00 | 0.00 | 0.00 |
May | 411.38 | 12.22 | 399.16 | 306.77 | 301.92 | 0.00 | 0.00 | 0.00 |
June | 432.56 | 28.56 | 403.99 | 360.61 | 232.97 | 0.00 | 0.00 | 0.00 |
July | 411.12 | 32.23 | 378.89 | 390.10 | 209.25 | 0.00 | 0.00 | 0.00 |
August | 332.81 | 9.00 | 323.81 | 319.84 | 205.84 | 0.00 | 0.00 | 0.00 |
September | 258.51 | 0.08 | 258.44 | 180.43 | 309.32 | 0.00 | 0.00 | 0.00 |
October | 177.12 | 0.00 | 177.12 | 61.54 | 439.71 | 0.00 | 0.00 | 0.00 |
November | 111.57 | 0.00 | 111.57 | 7.75 | 579.56 | 0.00 | 0.00 | 0.00 |
December | 83.74 | 0.00 | 83.74 | 0.18 | 717.42 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 251.85 | 6.99 | 244.86 | 158.71 | 432.41 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 83.74 | 0.00 | 83.74 | 0.18 | 205.84 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 432.56 | 32.23 | 403.99 | 390.10 | 717.42 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 98.55 | 0.00 | 98.55 | 0.89 | 694.53 | 0.00 | 0.00 | 0.00 |
February | 153.34 | 0.00 | 153.34 | 17.33 | 613.75 | 0.00 | 0.00 | 0.00 |
March | 225.93 | 0.00 | 225.93 | 70.61 | 501.62 | 0.00 | 0.00 | 0.00 |
April | 319.71 | 1.13 | 318.57 | 177.77 | 393.69 | 0.00 | 0.00 | 0.00 |
May | 411.38 | 12.22 | 399.16 | 306.77 | 301.92 | 0.00 | 0.00 | 0.00 |
June | 432.56 | 28.56 | 403.99 | 360.61 | 232.97 | 0.00 | 0.00 | 0.00 |
July | 411.12 | 32.23 | 378.89 | 390.10 | 209.25 | 0.00 | 0.00 | 0.00 |
August | 332.81 | 9.00 | 323.81 | 319.84 | 205.84 | 0.00 | 0.00 | 0.00 |
September | 258.51 | 0.08 | 258.44 | 180.43 | 309.32 | 0.00 | 0.00 | 0.00 |
October | 177.12 | 0.00 | 177.12 | 61.54 | 439.71 | 0.00 | 0.00 | 0.00 |
November | 111.57 | 0.00 | 111.57 | 7.75 | 579.56 | 0.00 | 0.00 | 0.00 |
December | 83.74 | 0.00 | 83.74 | 0.18 | 717.42 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 251.85 | 6.99 | 244.86 | 158.71 | 432.41 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 83.74 | 0.00 | 83.74 | 0.18 | 205.84 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 432.56 | 32.23 | 403.99 | 390.10 | 717.42 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 98.55 | 0.00 | 98.55 | 0.89 | 694.53 | 0.00 | 0.00 | 0.00 |
February | 153.34 | 0.00 | 153.34 | 17.33 | 613.75 | 0.00 | 0.00 | 0.00 |
March | 225.93 | 0.00 | 225.93 | 70.61 | 501.62 | 0.00 | 0.00 | 0.00 |
April | 319.71 | 1.13 | 318.57 | 177.77 | 393.69 | 0.00 | 0.00 | 0.00 |
May | 411.38 | 12.22 | 399.16 | 306.77 | 301.92 | 0.00 | 0.00 | 0.00 |
June | 432.56 | 28.56 | 403.99 | 360.61 | 232.97 | 0.00 | 0.00 | 0.00 |
July | 411.12 | 32.23 | 378.89 | 390.10 | 209.25 | 0.00 | 0.00 | 0.00 |
August | 332.81 | 9.00 | 323.81 | 319.84 | 205.84 | 0.00 | 0.00 | 0.00 |
September | 258.51 | 0.08 | 258.44 | 180.43 | 309.32 | 0.00 | 0.00 | 0.00 |
October | 177.12 | 0.00 | 177.12 | 61.54 | 439.71 | 0.00 | 0.00 | 0.00 |
November | 111.57 | 0.00 | 111.57 | 7.75 | 579.56 | 0.00 | 0.00 | 0.00 |
December | 83.74 | 0.00 | 83.74 | 0.18 | 717.42 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 251.85 | 6.99 | 244.86 | 158.71 | 432.41 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 83.74 | 0.00 | 83.74 | 0.18 | 205.84 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 432.56 | 32.23 | 403.99 | 390.10 | 717.42 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 98.54 | 0.00 | 98.54 | 0.89 | 694.50 | 0.00 | 0.00 | 0.00 |
February | 153.34 | 0.00 | 153.34 | 17.33 | 613.73 | 0.00 | 0.00 | 0.00 |
March | 225.92 | 0.00 | 225.92 | 70.61 | 501.60 | 0.00 | 0.00 | 0.00 |
April | 319.69 | 1.13 | 318.56 | 177.76 | 393.68 | 0.00 | 0.00 | 0.00 |
May | 411.37 | 12.22 | 399.15 | 306.76 | 301.91 | 0.00 | 0.00 | 0.00 |
June | 432.54 | 28.56 | 403.98 | 360.59 | 232.96 | 0.00 | 0.00 | 0.00 |
July | 411.11 | 32.23 | 378.87 | 390.08 | 209.24 | 0.00 | 0.00 | 0.00 |
August | 332.79 | 9.00 | 323.80 | 319.83 | 205.83 | 0.00 | 0.00 | 0.00 |
September | 258.50 | 0.08 | 258.43 | 180.42 | 309.31 | 0.00 | 0.00 | 0.00 |
October | 177.12 | 0.00 | 177.12 | 61.53 | 439.69 | 0.00 | 0.00 | 0.00 |
November | 111.57 | 0.00 | 111.57 | 7.75 | 579.54 | 0.00 | 0.00 | 0.00 |
December | 83.74 | 0.00 | 83.74 | 0.18 | 717.39 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 251.84 | 6.99 | 244.85 | 158.71 | 432.39 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 83.74 | 0.00 | 83.74 | 0.18 | 205.83 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 432.54 | 32.23 | 403.98 | 390.08 | 717.39 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 175.95 | 44.61 | 131.34 | 51.29 | 714.56 | 0.00 | 0.00 | 0.00 |
February | 322.84 | 114.58 | 208.26 | 181.85 | 617.31 | 0.00 | 0.00 | 0.00 |
March | 482.03 | 174.50 | 307.53 | 365.13 | 508.22 | 0.00 | 0.00 | 0.00 |
April | 747.22 | 310.48 | 436.74 | 709.43 | 399.25 | 0.00 | 0.00 | 0.00 |
May | 795.11 | 276.44 | 518.67 | 800.97 | 329.03 | 0.00 | 0.00 | 0.00 |
June | 952.24 | 414.33 | 537.91 | 1038.45 | 256.65 | 0.00 | 0.00 | 0.00 |
July | 886.75 | 398.03 | 488.73 | 1012.85 | 222.16 | 0.00 | 0.00 | 0.00 |
August | 871.56 | 436.00 | 435.55 | 1030.96 | 213.67 | 0.00 | 0.00 | 0.00 |
September | 644.39 | 297.20 | 347.19 | 672.04 | 321.32 | 0.00 | 0.00 | 0.00 |
October | 420.01 | 178.47 | 241.55 | 351.98 | 449.38 | 0.00 | 0.00 | 0.00 |
November | 205.87 | 58.12 | 147.75 | 92.73 | 585.74 | 0.00 | 0.00 | 0.00 |
December | 168.86 | 54.36 | 114.50 | 66.44 | 724.11 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 557.09 | 230.26 | 326.83 | 532.99 | 444.30 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 168.86 | 44.61 | 114.50 | 51.29 | 213.67 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 952.24 | 436.00 | 537.91 | 1038.45 | 724.11 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 175.95 | 44.61 | 131.34 | 51.29 | 714.56 | 0.00 | 0.00 | 0.00 |
February | 322.84 | 114.58 | 208.26 | 181.85 | 617.31 | 0.00 | 0.00 | 0.00 |
March | 482.03 | 174.50 | 307.53 | 365.13 | 508.22 | 0.00 | 0.00 | 0.00 |
April | 747.22 | 310.48 | 436.74 | 709.43 | 399.25 | 0.00 | 0.00 | 0.00 |
May | 795.11 | 276.44 | 518.67 | 800.97 | 329.03 | 0.00 | 0.00 | 0.00 |
June | 952.24 | 414.33 | 537.91 | 1038.45 | 256.65 | 0.00 | 0.00 | 0.00 |
July | 886.75 | 398.03 | 488.73 | 1012.85 | 222.16 | 0.00 | 0.00 | 0.00 |
August | 871.56 | 436.00 | 435.55 | 1030.96 | 213.67 | 0.00 | 0.00 | 0.00 |
September | 644.39 | 297.20 | 347.19 | 672.04 | 321.32 | 0.00 | 0.00 | 0.00 |
October | 420.01 | 178.47 | 241.55 | 351.98 | 449.38 | 0.00 | 0.00 | 0.00 |
November | 205.87 | 58.12 | 147.75 | 92.73 | 585.74 | 0.00 | 0.00 | 0.00 |
December | 168.86 | 54.36 | 114.50 | 66.44 | 724.11 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 557.09 | 230.26 | 326.83 | 532.99 | 444.30 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 168.86 | 44.61 | 114.50 | 51.29 | 213.67 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 952.24 | 436.00 | 537.91 | 1038.45 | 724.11 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 175.94 | 44.61 | 131.34 | 51.29 | 714.55 | 0.00 | 0.00 | 0.00 |
February | 322.84 | 114.58 | 208.26 | 181.85 | 617.30 | 0.00 | 0.00 | 0.00 |
March | 482.02 | 174.49 | 307.52 | 365.13 | 508.22 | 0.00 | 0.00 | 0.00 |
April | 747.21 | 310.48 | 436.73 | 709.42 | 399.24 | 0.00 | 0.00 | 0.00 |
May | 795.10 | 276.44 | 518.66 | 800.96 | 329.03 | 0.00 | 0.00 | 0.00 |
June | 952.22 | 414.32 | 537.90 | 1038.43 | 256.65 | 0.00 | 0.00 | 0.00 |
July | 886.74 | 398.02 | 488.72 | 1012.83 | 222.16 | 0.00 | 0.00 | 0.00 |
August | 871.54 | 435.99 | 435.55 | 1030.94 | 213.67 | 0.00 | 0.00 | 0.00 |
September | 644.38 | 297.19 | 347.18 | 672.03 | 321.32 | 0.00 | 0.00 | 0.00 |
October | 420.00 | 178.46 | 241.54 | 351.98 | 449.37 | 0.00 | 0.00 | 0.00 |
November | 205.86 | 58.12 | 147.75 | 92.73 | 585.73 | 0.00 | 0.00 | 0.00 |
December | 168.85 | 54.36 | 114.49 | 66.44 | 724.10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 557.08 | 230.26 | 326.82 | 532.98 | 444.29 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 168.85 | 44.61 | 114.49 | 51.29 | 213.67 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 952.22 | 435.99 | 537.90 | 1038.43 | 724.10 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 435.41 | 258.55 | 176.86 | 356.78 | 589.50 | 0.00 | 0.00 | 0.00 |
February | 669.60 | 414.49 | 255.11 | 633.44 | 532.22 | 0.00 | 0.00 | 0.00 |
March | 720.29 | 384.12 | 336.17 | 719.41 | 467.44 | 0.00 | 0.00 | 0.00 |
April | 760.49 | 330.20 | 430.29 | 806.69 | 392.38 | 0.00 | 0.00 | 0.00 |
May | 695.37 | 207.16 | 488.21 | 749.36 | 316.91 | 0.00 | 0.00 | 0.00 |
June | 636.20 | 170.81 | 465.39 | 700.17 | 252.66 | 0.00 | 0.00 | 0.00 |
July | 693.80 | 254.11 | 439.69 | 845.97 | 227.65 | 0.00 | 0.00 | 0.00 |
August | 745.40 | 347.59 | 397.81 | 940.91 | 219.59 | 0.00 | 0.00 | 0.00 |
September | 825.88 | 456.08 | 369.80 | 978.08 | 306.78 | 0.00 | 0.00 | 0.00 |
October | 748.10 | 461.90 | 286.20 | 803.77 | 410.42 | 0.00 | 0.00 | 0.00 |
November | 442.30 | 253.48 | 188.83 | 389.89 | 504.53 | 0.00 | 0.00 | 0.00 |
December | 462.78 | 299.48 | 163.30 | 420.40 | 616.81 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 652.69 | 319.24 | 333.45 | 695.66 | 402.44 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 435.41 | 170.81 | 163.30 | 356.78 | 219.59 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 825.88 | 461.90 | 488.21 | 978.08 | 616.81 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 435.41 | 258.55 | 176.86 | 356.78 | 589.50 | 0.00 | 0.00 | 0.00 |
February | 669.60 | 414.49 | 255.11 | 633.44 | 532.22 | 0.00 | 0.00 | 0.00 |
March | 720.29 | 384.12 | 336.17 | 719.41 | 467.44 | 0.00 | 0.00 | 0.00 |
April | 760.49 | 330.20 | 430.29 | 806.69 | 392.38 | 0.00 | 0.00 | 0.00 |
May | 695.37 | 207.16 | 488.21 | 749.36 | 316.91 | 0.00 | 0.00 | 0.00 |
June | 636.20 | 170.81 | 465.39 | 700.17 | 252.66 | 0.00 | 0.00 | 0.00 |
July | 693.80 | 254.11 | 439.69 | 845.97 | 227.65 | 0.00 | 0.00 | 0.00 |
August | 745.40 | 347.59 | 397.81 | 940.91 | 219.59 | 0.00 | 0.00 | 0.00 |
September | 825.88 | 456.08 | 369.80 | 978.08 | 306.78 | 0.00 | 0.00 | 0.00 |
October | 748.10 | 461.90 | 286.20 | 803.77 | 410.42 | 0.00 | 0.00 | 0.00 |
November | 442.30 | 253.48 | 188.83 | 389.89 | 504.53 | 0.00 | 0.00 | 0.00 |
December | 462.78 | 299.48 | 163.30 | 420.40 | 616.81 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 652.69 | 319.24 | 333.45 | 695.66 | 402.44 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 435.41 | 170.81 | 163.30 | 356.78 | 219.59 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 825.88 | 461.90 | 488.21 | 978.08 | 616.81 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 435.41 | 258.55 | 176.86 | 356.78 | 589.50 | 0.00 | 0.00 | 0.00 |
February | 669.60 | 414.49 | 255.11 | 633.44 | 532.22 | 0.00 | 0.00 | 0.00 |
March | 720.29 | 384.12 | 336.17 | 719.41 | 467.44 | 0.00 | 0.00 | 0.00 |
April | 760.49 | 330.20 | 430.29 | 806.69 | 392.38 | 0.00 | 0.00 | 0.00 |
May | 695.37 | 207.16 | 488.21 | 749.36 | 316.91 | 0.00 | 0.00 | 0.00 |
June | 636.20 | 170.81 | 465.39 | 700.17 | 252.66 | 0.00 | 0.00 | 0.00 |
July | 693.80 | 254.11 | 439.69 | 845.97 | 227.65 | 0.00 | 0.00 | 0.00 |
August | 745.40 | 347.59 | 397.81 | 940.91 | 219.59 | 0.00 | 0.00 | 0.00 |
September | 825.88 | 456.08 | 369.80 | 978.08 | 306.78 | 0.00 | 0.00 | 0.00 |
October | 748.10 | 461.90 | 286.20 | 803.77 | 410.42 | 0.00 | 0.00 | 0.00 |
November | 442.30 | 253.48 | 188.83 | 389.89 | 504.53 | 0.00 | 0.00 | 0.00 |
December | 462.78 | 299.48 | 163.30 | 420.40 | 616.81 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 652.69 | 319.24 | 333.45 | 695.66 | 402.44 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 435.41 | 170.81 | 163.30 | 356.78 | 219.59 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 825.88 | 461.90 | 488.21 | 978.08 | 616.81 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 435.41 | 258.55 | 176.86 | 356.78 | 589.50 | 0.00 | 0.00 | 0.00 |
February | 669.60 | 414.49 | 255.11 | 633.44 | 532.22 | 0.00 | 0.00 | 0.00 |
March | 720.29 | 384.12 | 336.17 | 719.41 | 467.44 | 0.00 | 0.00 | 0.00 |
April | 760.49 | 330.20 | 430.29 | 806.69 | 392.38 | 0.00 | 0.00 | 0.00 |
May | 695.37 | 207.16 | 488.21 | 749.36 | 316.91 | 0.00 | 0.00 | 0.00 |
June | 636.20 | 170.81 | 465.39 | 700.17 | 252.66 | 0.00 | 0.00 | 0.00 |
July | 693.80 | 254.11 | 439.69 | 845.97 | 227.65 | 0.00 | 0.00 | 0.00 |
August | 745.40 | 347.59 | 397.81 | 940.91 | 219.59 | 0.00 | 0.00 | 0.00 |
September | 825.88 | 456.08 | 369.80 | 978.08 | 306.78 | 0.00 | 0.00 | 0.00 |
October | 748.10 | 461.90 | 286.20 | 803.77 | 410.42 | 0.00 | 0.00 | 0.00 |
November | 442.30 | 253.48 | 188.83 | 389.89 | 504.53 | 0.00 | 0.00 | 0.00 |
December | 462.78 | 299.48 | 163.30 | 420.40 | 616.81 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 652.69 | 319.24 | 333.45 | 695.66 | 402.44 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 435.41 | 170.81 | 163.30 | 356.78 | 219.59 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 825.88 | 461.90 | 488.21 | 978.08 | 616.81 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 435.39 | 258.54 | 176.86 | 356.77 | 589.47 | 0.00 | 0.00 | 0.00 |
February | 669.57 | 414.47 | 255.10 | 633.42 | 532.20 | 0.00 | 0.00 | 0.00 |
March | 720.26 | 384.11 | 336.16 | 719.38 | 467.42 | 0.00 | 0.00 | 0.00 |
April | 760.46 | 330.19 | 430.27 | 806.66 | 392.36 | 0.00 | 0.00 | 0.00 |
May | 695.35 | 207.15 | 488.19 | 749.33 | 316.90 | 0.00 | 0.00 | 0.00 |
June | 636.17 | 170.80 | 465.37 | 700.14 | 252.65 | 0.00 | 0.00 | 0.00 |
July | 693.77 | 254.10 | 439.68 | 845.93 | 227.65 | 0.00 | 0.00 | 0.00 |
August | 745.37 | 347.58 | 397.79 | 940.87 | 219.58 | 0.00 | 0.00 | 0.00 |
September | 825.84 | 456.06 | 369.79 | 978.04 | 306.77 | 0.00 | 0.00 | 0.00 |
October | 748.07 | 461.88 | 286.19 | 803.74 | 410.41 | 0.00 | 0.00 | 0.00 |
November | 442.29 | 253.47 | 188.82 | 389.88 | 504.51 | 0.00 | 0.00 | 0.00 |
December | 462.76 | 299.47 | 163.29 | 420.38 | 616.78 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 652.66 | 319.23 | 333.43 | 695.63 | 402.42 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 435.39 | 170.80 | 163.29 | 356.77 | 219.58 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 825.84 | 461.88 | 488.19 | 978.04 | 616.78 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 185.58 | 54.72 | 130.86 | 64.68 | 763.02 | 0.00 | 0.00 | 0.00 |
February | 332.73 | 125.05 | 207.68 | 196.81 | 691.54 | 0.00 | 0.00 | 0.00 |
March | 466.24 | 157.37 | 308.87 | 338.73 | 594.82 | 0.00 | 0.00 | 0.00 |
April | 709.33 | 271.21 | 438.13 | 642.37 | 493.63 | 0.00 | 0.00 | 0.00 |
May | 912.75 | 370.80 | 541.95 | 944.16 | 374.68 | 0.00 | 0.00 | 0.00 |
June | 877.81 | 340.83 | 536.99 | 925.11 | 307.22 | 0.00 | 0.00 | 0.00 |
July | 1084.42 | 570.03 | 514.39 | 1261.56 | 288.24 | 0.00 | 0.00 | 0.00 |
August | 897.07 | 458.07 | 439.00 | 1052.48 | 286.88 | 0.00 | 0.00 | 0.00 |
September | 730.53 | 350.52 | 380.01 | 791.93 | 370.90 | 0.00 | 0.00 | 0.00 |
October | 415.89 | 169.46 | 246.44 | 342.02 | 520.95 | 0.00 | 0.00 | 0.00 |
November | 207.11 | 58.41 | 148.70 | 89.18 | 679.26 | 0.00 | 0.00 | 0.00 |
December | 174.12 | 59.67 | 114.45 | 75.69 | 851.77 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 584.32 | 249.79 | 334.53 | 562.82 | 517.76 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 174.12 | 54.72 | 114.45 | 64.68 | 286.88 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1084.42 | 570.03 | 541.95 | 1261.56 | 851.77 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 185.58 | 54.72 | 130.86 | 64.68 | 763.02 | 0.00 | 0.00 | 0.00 |
February | 332.73 | 125.05 | 207.68 | 196.81 | 691.54 | 0.00 | 0.00 | 0.00 |
March | 466.24 | 157.37 | 308.87 | 338.73 | 594.82 | 0.00 | 0.00 | 0.00 |
April | 709.33 | 271.21 | 438.13 | 642.37 | 493.63 | 0.00 | 0.00 | 0.00 |
May | 912.75 | 370.80 | 541.95 | 944.16 | 374.68 | 0.00 | 0.00 | 0.00 |
June | 877.81 | 340.83 | 536.99 | 925.11 | 307.22 | 0.00 | 0.00 | 0.00 |
July | 1084.42 | 570.03 | 514.39 | 1261.56 | 288.24 | 0.00 | 0.00 | 0.00 |
August | 897.07 | 458.07 | 439.00 | 1052.48 | 286.88 | 0.00 | 0.00 | 0.00 |
September | 730.53 | 350.52 | 380.01 | 791.93 | 370.90 | 0.00 | 0.00 | 0.00 |
October | 415.89 | 169.46 | 246.44 | 342.02 | 520.95 | 0.00 | 0.00 | 0.00 |
November | 207.11 | 58.41 | 148.70 | 89.18 | 679.26 | 0.00 | 0.00 | 0.00 |
December | 174.12 | 59.67 | 114.45 | 75.69 | 851.77 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 584.32 | 249.79 | 334.53 | 562.82 | 517.76 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 174.12 | 54.72 | 114.45 | 64.68 | 286.88 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1084.42 | 570.03 | 541.95 | 1261.56 | 851.77 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 185.58 | 54.72 | 130.85 | 64.68 | 763.01 | 0.00 | 0.00 | 0.00 |
February | 332.72 | 125.05 | 207.68 | 196.80 | 691.53 | 0.00 | 0.00 | 0.00 |
March | 466.23 | 157.37 | 308.87 | 338.72 | 594.81 | 0.00 | 0.00 | 0.00 |
April | 709.32 | 271.20 | 438.12 | 642.36 | 493.62 | 0.00 | 0.00 | 0.00 |
May | 912.73 | 370.79 | 541.94 | 944.15 | 374.67 | 0.00 | 0.00 | 0.00 |
June | 877.80 | 340.82 | 536.98 | 925.10 | 307.21 | 0.00 | 0.00 | 0.00 |
July | 1084.40 | 570.01 | 514.38 | 1261.54 | 288.23 | 0.00 | 0.00 | 0.00 |
August | 897.06 | 458.06 | 438.99 | 1052.46 | 286.87 | 0.00 | 0.00 | 0.00 |
September | 730.52 | 350.52 | 380.00 | 791.92 | 370.89 | 0.00 | 0.00 | 0.00 |
October | 415.88 | 169.45 | 246.43 | 342.01 | 520.94 | 0.00 | 0.00 | 0.00 |
November | 207.11 | 58.41 | 148.69 | 89.18 | 679.25 | 0.00 | 0.00 | 0.00 |
December | 174.11 | 59.66 | 114.45 | 75.69 | 851.75 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 584.31 | 249.79 | 334.53 | 562.81 | 517.76 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 174.11 | 54.72 | 114.45 | 64.68 | 286.87 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1084.40 | 570.01 | 541.94 | 1261.54 | 851.75 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 492.73 | 0.00 | 492.73 | 13.82 | 2972.38 | 0.00 | 0.00 | 0.00 |
February | 766.70 | 0.00 | 766.70 | 133.44 | 2651.43 | 0.00 | 0.00 | 0.00 |
March | 1129.61 | 0.00 | 1129.61 | 431.62 | 2186.77 | 0.00 | 0.00 | 0.00 |
April | 1598.52 | 5.67 | 1592.85 | 973.87 | 1738.29 | 0.00 | 0.00 | 0.00 |
May | 2056.89 | 61.11 | 1995.78 | 1577.68 | 1408.46 | 0.00 | 0.00 | 0.00 |
June | 2162.77 | 142.82 | 2019.95 | 1837.42 | 1088.56 | 0.00 | 0.00 | 0.00 |
July | 2055.59 | 161.17 | 1894.43 | 1988.34 | 976.52 | 0.00 | 0.00 | 0.00 |
August | 1664.02 | 44.98 | 1619.03 | 1638.82 | 959.72 | 0.00 | 0.00 | 0.00 |
September | 1292.55 | 0.38 | 1292.17 | 937.33 | 1429.03 | 0.00 | 0.00 | 0.00 |
October | 885.61 | 0.00 | 885.61 | 372.17 | 1919.05 | 0.00 | 0.00 | 0.00 |
November | 557.85 | 0.00 | 557.85 | 67.58 | 2436.33 | 0.00 | 0.00 | 0.00 |
December | 418.69 | 0.00 | 418.69 | 6.44 | 3017.50 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1259.22 | 34.93 | 1224.29 | 835.94 | 1894.95 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 418.69 | 0.00 | 418.69 | 6.44 | 959.72 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2162.77 | 161.17 | 2019.95 | 1988.34 | 3017.50 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 527.83 | 133.82 | 394.01 | 172.98 | 1881.67 | 0.00 | 0.00 | 0.00 |
February | 968.52 | 343.75 | 624.77 | 586.33 | 1668.39 | 0.00 | 0.00 | 0.00 |
March | 1446.07 | 523.49 | 922.58 | 1128.76 | 1384.82 | 0.00 | 0.00 | 0.00 |
April | 2241.65 | 931.44 | 1310.21 | 2145.25 | 1110.14 | 0.00 | 0.00 | 0.00 |
May | 2385.32 | 829.32 | 1556.00 | 2408.61 | 932.17 | 0.00 | 0.00 | 0.00 |
June | 2856.69 | 1242.96 | 1613.72 | 3103.04 | 736.48 | 0.00 | 0.00 | 0.00 |
July | 2660.24 | 1194.07 | 1466.17 | 3028.09 | 645.20 | 0.00 | 0.00 | 0.00 |
August | 2614.64 | 1307.99 | 1306.65 | 3076.32 | 635.04 | 0.00 | 0.00 | 0.00 |
September | 1933.14 | 891.58 | 1041.56 | 2023.53 | 905.57 | 0.00 | 0.00 | 0.00 |
October | 1260.02 | 535.39 | 724.63 | 1084.18 | 1219.66 | 0.00 | 0.00 | 0.00 |
November | 617.59 | 174.35 | 443.24 | 304.97 | 1552.36 | 0.00 | 0.00 | 0.00 |
December | 506.56 | 163.08 | 343.49 | 219.01 | 1926.86 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1671.26 | 690.79 | 980.48 | 1611.99 | 1214.36 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 506.56 | 133.82 | 343.49 | 172.98 | 635.04 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2856.69 | 1307.99 | 1613.72 | 3103.04 | 1926.86 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 2177.04 | 1292.73 | 884.30 | 1805.06 | 2740.04 | 0.00 | 0.00 | 0.00 |
February | 3347.95 | 2072.42 | 1275.52 | 3182.46 | 2517.13 | 0.00 | 0.00 | 0.00 |
March | 3601.42 | 1920.60 | 1680.82 | 3598.85 | 2198.96 | 0.00 | 0.00 | 0.00 |
April | 3802.42 | 1650.99 | 2151.43 | 4032.32 | 1849.61 | 0.00 | 0.00 | 0.00 |
May | 3476.82 | 1035.78 | 2441.04 | 3730.86 | 1525.67 | 0.00 | 0.00 | 0.00 |
June | 3180.95 | 854.05 | 2326.91 | 3493.40 | 1204.59 | 0.00 | 0.00 | 0.00 |
July | 3468.97 | 1270.52 | 2198.45 | 4218.50 | 1090.86 | 0.00 | 0.00 | 0.00 |
August | 3726.97 | 1737.95 | 1989.02 | 4689.75 | 1065.71 | 0.00 | 0.00 | 0.00 |
September | 4129.33 | 2280.35 | 1848.98 | 4874.09 | 1486.23 | 0.00 | 0.00 | 0.00 |
October | 3740.47 | 2309.47 | 1431.01 | 4008.22 | 1946.25 | 0.00 | 0.00 | 0.00 |
November | 2211.49 | 1267.37 | 944.12 | 1974.67 | 2336.81 | 0.00 | 0.00 | 0.00 |
December | 2313.86 | 1497.39 | 816.47 | 2126.48 | 2849.38 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 3263.40 | 1596.19 | 1667.21 | 3479.05 | 1897.86 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 2177.04 | 854.05 | 816.47 | 1805.06 | 1065.71 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 4129.33 | 2309.47 | 2441.04 | 4874.09 | 2849.38 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 556.73 | 164.17 | 392.56 | 216.14 | 1947.68 | 0.00 | 0.00 | 0.00 |
February | 998.18 | 375.14 | 623.04 | 648.86 | 1739.54 | 0.00 | 0.00 | 0.00 |
March | 1398.70 | 472.10 | 926.60 | 1096.23 | 1463.42 | 0.00 | 0.00 | 0.00 |
April | 2127.98 | 813.61 | 1314.37 | 2021.47 | 1221.97 | 0.00 | 0.00 | 0.00 |
May | 2738.21 | 1112.39 | 1625.82 | 2859.97 | 1027.76 | 0.00 | 0.00 | 0.00 |
June | 2633.41 | 1022.47 | 1610.94 | 2817.12 | 813.37 | 0.00 | 0.00 | 0.00 |
July | 3253.22 | 1710.06 | 1543.16 | 3821.92 | 761.98 | 0.00 | 0.00 | 0.00 |
August | 2691.19 | 1374.20 | 1316.99 | 3209.57 | 740.74 | 0.00 | 0.00 | 0.00 |
September | 2191.56 | 1051.56 | 1140.00 | 2406.66 | 1004.80 | 0.00 | 0.00 | 0.00 |
October | 1247.66 | 508.36 | 739.30 | 1088.13 | 1302.76 | 0.00 | 0.00 | 0.00 |
November | 621.33 | 175.24 | 446.09 | 316.71 | 1608.09 | 0.00 | 0.00 | 0.00 |
December | 522.35 | 179.00 | 343.35 | 260.74 | 2004.99 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1752.95 | 749.37 | 1003.59 | 1737.43 | 1301.05 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 522.35 | 164.17 | 343.35 | 216.14 | 740.74 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 3253.22 | 1710.06 | 1625.82 | 3821.92 | 2004.99 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 492.73 | 0.00 | 492.73 | 21.90 | 2785.73 | 0.00 | 0.00 | 0.00 |
February | 766.70 | 0.00 | 766.70 | 159.27 | 2455.38 | 0.00 | 0.00 | 0.00 |
March | 1129.61 | 0.00 | 1129.61 | 477.31 | 2010.48 | 0.00 | 0.00 | 0.00 |
April | 1598.52 | 5.67 | 1592.85 | 1018.41 | 1623.70 | 0.00 | 0.00 | 0.00 |
May | 2056.89 | 61.11 | 1995.78 | 1610.18 | 1335.62 | 0.00 | 0.00 | 0.00 |
June | 2162.77 | 142.82 | 2019.95 | 1845.12 | 1054.02 | 0.00 | 0.00 | 0.00 |
July | 2055.59 | 161.17 | 1894.43 | 1986.58 | 951.17 | 0.00 | 0.00 | 0.00 |
August | 1664.02 | 44.98 | 1619.03 | 1643.57 | 928.83 | 0.00 | 0.00 | 0.00 |
September | 1292.55 | 0.38 | 1292.17 | 966.05 | 1340.70 | 0.00 | 0.00 | 0.00 |
October | 885.61 | 0.00 | 885.61 | 420.00 | 1742.36 | 0.00 | 0.00 | 0.00 |
November | 557.85 | 0.00 | 557.85 | 89.25 | 2198.37 | 0.00 | 0.00 | 0.00 |
December | 418.69 | 0.00 | 418.69 | 14.33 | 2767.81 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1259.22 | 34.93 | 1224.29 | 858.67 | 1762.84 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 418.69 | 0.00 | 418.69 | 14.33 | 928.83 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2162.77 | 161.17 | 2019.95 | 1986.58 | 2785.73 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 527.83 | 133.82 | 394.01 | 185.59 | 1767.20 | 0.00 | 0.00 | 0.00 |
February | 968.52 | 343.75 | 624.77 | 615.69 | 1549.82 | 0.00 | 0.00 | 0.00 |
March | 1446.07 | 523.49 | 922.58 | 1158.62 | 1287.73 | 0.00 | 0.00 | 0.00 |
April | 2241.65 | 931.44 | 1310.21 | 2167.54 | 1049.28 | 0.00 | 0.00 | 0.00 |
May | 2385.32 | 829.32 | 1556.00 | 2419.85 | 893.08 | 0.00 | 0.00 | 0.00 |
June | 2856.69 | 1242.96 | 1613.72 | 3097.98 | 719.51 | 0.00 | 0.00 | 0.00 |
July | 2660.24 | 1194.07 | 1466.17 | 3021.44 | 634.31 | 0.00 | 0.00 | 0.00 |
August | 2614.64 | 1307.99 | 1306.65 | 3072.70 | 620.85 | 0.00 | 0.00 | 0.00 |
September | 1933.14 | 891.58 | 1041.56 | 2035.58 | 862.14 | 0.00 | 0.00 | 0.00 |
October | 1260.02 | 535.39 | 724.63 | 1113.00 | 1125.69 | 0.00 | 0.00 | 0.00 |
November | 617.59 | 174.35 | 443.24 | 326.65 | 1416.20 | 0.00 | 0.00 | 0.00 |
December | 506.56 | 163.08 | 343.49 | 235.45 | 1776.93 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1671.26 | 690.79 | 980.48 | 1625.97 | 1139.97 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 506.56 | 133.82 | 343.49 | 185.59 | 620.85 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2856.69 | 1307.99 | 1613.72 | 3097.98 | 1776.93 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 2177.04 | 1292.73 | 884.30 | 1843.68 | 2555.18 | 0.00 | 0.00 | 0.00 |
February | 3347.95 | 2072.42 | 1275.52 | 3237.09 | 2332.48 | 0.00 | 0.00 | 0.00 |
March | 3601.42 | 1920.60 | 1680.82 | 3634.70 | 2041.23 | 0.00 | 0.00 | 0.00 |
April | 3802.42 | 1650.99 | 2151.43 | 4059.47 | 1745.31 | 0.00 | 0.00 | 0.00 |
May | 3476.82 | 1035.78 | 2441.04 | 3745.59 | 1454.45 | 0.00 | 0.00 | 0.00 |
June | 3180.95 | 854.05 | 2326.91 | 3490.71 | 1168.12 | 0.00 | 0.00 | 0.00 |
July | 3468.97 | 1270.52 | 2198.45 | 4209.92 | 1065.33 | 0.00 | 0.00 | 0.00 |
August | 3726.97 | 1737.95 | 1989.02 | 4685.31 | 1034.64 | 0.00 | 0.00 | 0.00 |
September | 4129.33 | 2280.35 | 1848.98 | 4891.83 | 1411.68 | 0.00 | 0.00 | 0.00 |
October | 3740.47 | 2309.47 | 1431.01 | 4046.38 | 1799.11 | 0.00 | 0.00 | 0.00 |
November | 2211.49 | 1267.37 | 944.12 | 2020.99 | 2135.93 | 0.00 | 0.00 | 0.00 |
December | 2313.86 | 1497.39 | 816.47 | 2166.86 | 2626.09 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 3263.40 | 1596.19 | 1667.21 | 3503.65 | 1778.08 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 2177.04 | 854.05 | 816.47 | 1843.68 | 1034.64 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 4129.33 | 2309.47 | 2441.04 | 4891.83 | 2626.09 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 556.73 | 164.17 | 392.56 | 224.89 | 1833.46 | 0.00 | 0.00 | 0.00 |
February | 998.18 | 375.14 | 623.04 | 666.30 | 1631.72 | 0.00 | 0.00 | 0.00 |
March | 1398.70 | 472.10 | 926.60 | 1114.71 | 1371.86 | 0.00 | 0.00 | 0.00 |
April | 2127.98 | 813.61 | 1314.37 | 2037.28 | 1159.84 | 0.00 | 0.00 | 0.00 |
May | 2738.21 | 1112.39 | 1625.82 | 2866.81 | 984.97 | 0.00 | 0.00 | 0.00 |
June | 2633.41 | 1022.47 | 1610.94 | 2813.56 | 790.29 | 0.00 | 0.00 | 0.00 |
July | 3253.22 | 1710.06 | 1543.16 | 3812.67 | 745.21 | 0.00 | 0.00 | 0.00 |
August | 2691.19 | 1374.20 | 1316.99 | 3205.90 | 720.88 | 0.00 | 0.00 | 0.00 |
September | 2191.56 | 1051.56 | 1140.00 | 2416.94 | 959.30 | 0.00 | 0.00 | 0.00 |
October | 1247.66 | 508.36 | 739.30 | 1108.65 | 1213.87 | 0.00 | 0.00 | 0.00 |
November | 621.33 | 175.24 | 446.09 | 330.84 | 1490.37 | 0.00 | 0.00 | 0.00 |
December | 522.35 | 179.00 | 343.35 | 269.39 | 1870.77 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1752.95 | 749.37 | 1003.59 | 1746.05 | 1229.19 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 522.35 | 164.17 | 343.35 | 224.89 | 720.88 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 3253.22 | 1710.06 | 1625.82 | 3812.67 | 1870.77 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.263949E+09 | 0.00 | 0.263949E+09 | 2380475.08 | 0.186023E+10 |
February | 0.370965E+09 | 0.00 | 0.370965E+09 | 41922147.95 | 0.148479E+10 |
March | 0.605119E+09 | 0.00 | 0.605119E+09 | 0.189128E+09 | 0.134355E+10 |
April | 0.828682E+09 | 2939586.61 | 0.825742E+09 | 0.460782E+09 | 0.102046E+10 |
May | 0.110185E+10 | 32734317.53 | 0.106911E+10 | 0.821663E+09 | 0.808668E+09 |
June | 0.112119E+10 | 74038924.27 | 0.104715E+10 | 0.934699E+09 | 0.603853E+09 |
July | 0.110115E+10 | 86335685.02 | 0.101482E+10 | 0.104484E+10 | 0.560451E+09 |
August | 0.891392E+09 | 24097003.63 | 0.867295E+09 | 0.856670E+09 | 0.551312E+09 |
September | 0.670066E+09 | 197592.30 | 0.669868E+09 | 0.467679E+09 | 0.801754E+09 |
October | 0.474410E+09 | 0.00 | 0.474410E+09 | 0.164821E+09 | 0.117772E+10 |
November | 0.289192E+09 | 0.00 | 0.289192E+09 | 20095635.49 | 0.150222E+10 |
December | 0.224288E+09 | 0.00 | 0.224288E+09 | 488133.33 | 0.192154E+10 |
Annual Sum or Average | 0.794226E+10 | 0.220343E+09 | 0.772192E+10 | 0.500516E+10 | 0.136366E+11 |
Minimum of Months | 0.224288E+09 | 0.00 | 0.224288E+09 | 488133.33 | 0.551312E+09 |
Maximum of Months | 0.112119E+10 | 86335685.02 | 0.106911E+10 | 0.104484E+10 | 0.192154E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.263949E+09 | 0.00 | 0.263949E+09 | 2380453.54 | 0.186023E+10 |
February | 0.370965E+09 | 0.00 | 0.370965E+09 | 41922010.82 | 0.148479E+10 |
March | 0.605118E+09 | 0.00 | 0.605118E+09 | 0.189127E+09 | 0.134355E+10 |
April | 0.828681E+09 | 2939583.08 | 0.825741E+09 | 0.460781E+09 | 0.102046E+10 |
May | 0.110185E+10 | 32734278.25 | 0.106911E+10 | 0.821662E+09 | 0.808668E+09 |
June | 0.112119E+10 | 74038835.43 | 0.104715E+10 | 0.934698E+09 | 0.603853E+09 |
July | 0.110115E+10 | 86335581.43 | 0.101482E+10 | 0.104484E+10 | 0.560451E+09 |
August | 0.891391E+09 | 24096974.72 | 0.867294E+09 | 0.856669E+09 | 0.551312E+09 |
September | 0.670065E+09 | 197592.06 | 0.669868E+09 | 0.467678E+09 | 0.801754E+09 |
October | 0.474410E+09 | 0.00 | 0.474410E+09 | 0.164821E+09 | 0.117772E+10 |
November | 0.289192E+09 | 0.00 | 0.289192E+09 | 20095562.96 | 0.150222E+10 |
December | 0.224288E+09 | 0.00 | 0.224288E+09 | 488128.04 | 0.192154E+10 |
Annual Sum or Average | 0.794225E+10 | 0.220343E+09 | 0.772191E+10 | 0.500516E+10 | 0.136366E+11 |
Minimum of Months | 0.224288E+09 | 0.00 | 0.224288E+09 | 488128.04 | 0.551312E+09 |
Maximum of Months | 0.112119E+10 | 86335581.43 | 0.106911E+10 | 0.104484E+10 | 0.192154E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.263949E+09 | 0.00 | 0.263949E+09 | 2380475.08 | 0.186023E+10 |
February | 0.370965E+09 | 0.00 | 0.370965E+09 | 41922147.95 | 0.148479E+10 |
March | 0.605119E+09 | 0.00 | 0.605119E+09 | 0.189128E+09 | 0.134355E+10 |
April | 0.828682E+09 | 2939586.61 | 0.825742E+09 | 0.460782E+09 | 0.102046E+10 |
May | 0.110185E+10 | 32734317.53 | 0.106911E+10 | 0.821663E+09 | 0.808668E+09 |
June | 0.112119E+10 | 74038924.27 | 0.104715E+10 | 0.934699E+09 | 0.603853E+09 |
July | 0.110115E+10 | 86335685.02 | 0.101482E+10 | 0.104484E+10 | 0.560451E+09 |
August | 0.891392E+09 | 24097003.63 | 0.867295E+09 | 0.856670E+09 | 0.551312E+09 |
September | 0.670066E+09 | 197592.30 | 0.669868E+09 | 0.467679E+09 | 0.801754E+09 |
October | 0.474410E+09 | 0.00 | 0.474410E+09 | 0.164821E+09 | 0.117772E+10 |
November | 0.289192E+09 | 0.00 | 0.289192E+09 | 20095635.49 | 0.150222E+10 |
December | 0.224288E+09 | 0.00 | 0.224288E+09 | 488133.33 | 0.192154E+10 |
Annual Sum or Average | 0.794226E+10 | 0.220343E+09 | 0.772192E+10 | 0.500516E+10 | 0.136366E+11 |
Minimum of Months | 0.224288E+09 | 0.00 | 0.224288E+09 | 488133.33 | 0.551312E+09 |
Maximum of Months | 0.112119E+10 | 86335685.02 | 0.106911E+10 | 0.104484E+10 | 0.192154E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.263949E+09 | 0.00 | 0.263949E+09 | 2380453.54 | 0.186023E+10 |
February | 0.370965E+09 | 0.00 | 0.370965E+09 | 41922010.82 | 0.148479E+10 |
March | 0.605118E+09 | 0.00 | 0.605118E+09 | 0.189127E+09 | 0.134355E+10 |
April | 0.828681E+09 | 2939583.08 | 0.825741E+09 | 0.460781E+09 | 0.102046E+10 |
May | 0.110185E+10 | 32734278.25 | 0.106911E+10 | 0.821662E+09 | 0.808668E+09 |
June | 0.112119E+10 | 74038835.43 | 0.104715E+10 | 0.934698E+09 | 0.603853E+09 |
July | 0.110115E+10 | 86335581.43 | 0.101482E+10 | 0.104484E+10 | 0.560451E+09 |
August | 0.891391E+09 | 24096974.72 | 0.867294E+09 | 0.856669E+09 | 0.551312E+09 |
September | 0.670065E+09 | 197592.06 | 0.669868E+09 | 0.467678E+09 | 0.801754E+09 |
October | 0.474410E+09 | 0.00 | 0.474410E+09 | 0.164821E+09 | 0.117772E+10 |
November | 0.289192E+09 | 0.00 | 0.289192E+09 | 20095562.96 | 0.150222E+10 |
December | 0.224288E+09 | 0.00 | 0.224288E+09 | 488128.04 | 0.192154E+10 |
Annual Sum or Average | 0.794225E+10 | 0.220343E+09 | 0.772191E+10 | 0.500516E+10 | 0.136366E+11 |
Minimum of Months | 0.224288E+09 | 0.00 | 0.224288E+09 | 488128.04 | 0.551312E+09 |
Maximum of Months | 0.112119E+10 | 86335581.43 | 0.106911E+10 | 0.104484E+10 | 0.192154E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.263938E+09 | 0.00 | 0.263938E+09 | 2380379.13 | 0.186016E+10 |
February | 0.370950E+09 | 0.00 | 0.370950E+09 | 41920458.31 | 0.148473E+10 |
March | 0.605095E+09 | 0.00 | 0.605095E+09 | 0.189120E+09 | 0.134350E+10 |
April | 0.828648E+09 | 2939468.13 | 0.825709E+09 | 0.460763E+09 | 0.102041E+10 |
May | 0.110180E+10 | 32732998.19 | 0.106907E+10 | 0.821629E+09 | 0.808636E+09 |
June | 0.112115E+10 | 74035940.18 | 0.104711E+10 | 0.934661E+09 | 0.603828E+09 |
July | 0.110111E+10 | 86332205.32 | 0.101478E+10 | 0.104479E+10 | 0.560428E+09 |
August | 0.891356E+09 | 24096032.41 | 0.867260E+09 | 0.856636E+09 | 0.551290E+09 |
September | 0.670039E+09 | 197584.34 | 0.669841E+09 | 0.467660E+09 | 0.801722E+09 |
October | 0.474391E+09 | 0.00 | 0.474391E+09 | 0.164814E+09 | 0.117767E+10 |
November | 0.289180E+09 | 0.00 | 0.289180E+09 | 20094825.55 | 0.150216E+10 |
December | 0.224279E+09 | 0.00 | 0.224279E+09 | 488113.65 | 0.192146E+10 |
Annual Sum or Average | 0.794194E+10 | 0.220334E+09 | 0.772161E+10 | 0.500496E+10 | 0.136360E+11 |
Minimum of Months | 0.224279E+09 | 0.00 | 0.224279E+09 | 488113.65 | 0.551290E+09 |
Maximum of Months | 0.112115E+10 | 86332205.32 | 0.106907E+10 | 0.104479E+10 | 0.192146E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.471253E+09 | 0.119478E+09 | 0.351774E+09 | 0.137384E+09 | 0.191389E+10 |
February | 0.781022E+09 | 0.277201E+09 | 0.503821E+09 | 0.439942E+09 | 0.149339E+10 |
March | 0.129106E+10 | 0.467375E+09 | 0.823686E+09 | 0.977972E+09 | 0.136123E+10 |
April | 0.193681E+10 | 0.804771E+09 | 0.113203E+10 | 0.183885E+10 | 0.103485E+10 |
May | 0.212963E+10 | 0.740424E+09 | 0.138921E+10 | 0.214532E+10 | 0.881282E+09 |
June | 0.246820E+10 | 0.107393E+10 | 0.139427E+10 | 0.269167E+10 | 0.665242E+09 |
July | 0.237508E+10 | 0.106607E+10 | 0.130901E+10 | 0.271282E+10 | 0.595035E+09 |
August | 0.233438E+10 | 0.116779E+10 | 0.116659E+10 | 0.276133E+10 | 0.572295E+09 |
September | 0.167025E+10 | 0.770336E+09 | 0.899918E+09 | 0.174193E+10 | 0.832871E+09 |
October | 0.112496E+10 | 0.478001E+09 | 0.646957E+09 | 0.942749E+09 | 0.120363E+10 |
November | 0.533605E+09 | 0.150642E+09 | 0.382963E+09 | 0.240353E+09 | 0.151823E+10 |
December | 0.452265E+09 | 0.145598E+09 | 0.306668E+09 | 0.177960E+09 | 0.193946E+10 |
Annual Sum or Average | 0.175685E+11 | 0.726162E+10 | 0.103069E+11 | 0.168083E+11 | 0.140114E+11 |
Minimum of Months | 0.452265E+09 | 0.119478E+09 | 0.306668E+09 | 0.137384E+09 | 0.572295E+09 |
Maximum of Months | 0.246820E+10 | 0.116779E+10 | 0.139427E+10 | 0.276133E+10 | 0.193946E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.471253E+09 | 0.119478E+09 | 0.351774E+09 | 0.137384E+09 | 0.191389E+10 |
February | 0.781022E+09 | 0.277201E+09 | 0.503821E+09 | 0.439942E+09 | 0.149339E+10 |
March | 0.129106E+10 | 0.467375E+09 | 0.823686E+09 | 0.977972E+09 | 0.136123E+10 |
April | 0.193681E+10 | 0.804771E+09 | 0.113203E+10 | 0.183885E+10 | 0.103485E+10 |
May | 0.212963E+10 | 0.740424E+09 | 0.138921E+10 | 0.214532E+10 | 0.881282E+09 |
June | 0.246820E+10 | 0.107393E+10 | 0.139427E+10 | 0.269167E+10 | 0.665242E+09 |
July | 0.237508E+10 | 0.106607E+10 | 0.130901E+10 | 0.271282E+10 | 0.595035E+09 |
August | 0.233438E+10 | 0.116779E+10 | 0.116659E+10 | 0.276133E+10 | 0.572295E+09 |
September | 0.167025E+10 | 0.770336E+09 | 0.899918E+09 | 0.174193E+10 | 0.832871E+09 |
October | 0.112496E+10 | 0.478001E+09 | 0.646957E+09 | 0.942749E+09 | 0.120363E+10 |
November | 0.533605E+09 | 0.150642E+09 | 0.382963E+09 | 0.240353E+09 | 0.151823E+10 |
December | 0.452265E+09 | 0.145598E+09 | 0.306668E+09 | 0.177960E+09 | 0.193946E+10 |
Annual Sum or Average | 0.175685E+11 | 0.726162E+10 | 0.103069E+11 | 0.168083E+11 | 0.140114E+11 |
Minimum of Months | 0.452265E+09 | 0.119478E+09 | 0.306668E+09 | 0.137384E+09 | 0.572295E+09 |
Maximum of Months | 0.246820E+10 | 0.116779E+10 | 0.139427E+10 | 0.276133E+10 | 0.193946E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.471244E+09 | 0.119476E+09 | 0.351768E+09 | 0.137381E+09 | 0.191385E+10 |
February | 0.781007E+09 | 0.277196E+09 | 0.503811E+09 | 0.439934E+09 | 0.149336E+10 |
March | 0.129104E+10 | 0.467367E+09 | 0.823671E+09 | 0.977954E+09 | 0.136120E+10 |
April | 0.193677E+10 | 0.804757E+09 | 0.113201E+10 | 0.183882E+10 | 0.103483E+10 |
May | 0.212959E+10 | 0.740411E+09 | 0.138918E+10 | 0.214529E+10 | 0.881266E+09 |
June | 0.246816E+10 | 0.107391E+10 | 0.139424E+10 | 0.269162E+10 | 0.665230E+09 |
July | 0.237504E+10 | 0.106606E+10 | 0.130899E+10 | 0.271277E+10 | 0.595024E+09 |
August | 0.233433E+10 | 0.116777E+10 | 0.116657E+10 | 0.276128E+10 | 0.572285E+09 |
September | 0.167022E+10 | 0.770321E+09 | 0.899902E+09 | 0.174190E+10 | 0.832856E+09 |
October | 0.112494E+10 | 0.477993E+09 | 0.646945E+09 | 0.942732E+09 | 0.120361E+10 |
November | 0.533596E+09 | 0.150639E+09 | 0.382956E+09 | 0.240349E+09 | 0.151820E+10 |
December | 0.452257E+09 | 0.145595E+09 | 0.306662E+09 | 0.177957E+09 | 0.193943E+10 |
Annual Sum or Average | 0.175682E+11 | 0.726149E+10 | 0.103067E+11 | 0.168080E+11 | 0.140111E+11 |
Minimum of Months | 0.452257E+09 | 0.119476E+09 | 0.306662E+09 | 0.137381E+09 | 0.572285E+09 |
Maximum of Months | 0.246816E+10 | 0.116777E+10 | 0.139424E+10 | 0.276128E+10 | 0.193943E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.116621E+10 | 0.692500E+09 | 0.473709E+09 | 0.955598E+09 | 0.157891E+10 |
February | 0.161989E+10 | 0.100273E+10 | 0.617156E+09 | 0.153243E+10 | 0.128755E+10 |
March | 0.192923E+10 | 0.102884E+10 | 0.900394E+09 | 0.192687E+10 | 0.125199E+10 |
April | 0.197120E+10 | 0.855883E+09 | 0.111531E+10 | 0.209094E+10 | 0.101704E+10 |
May | 0.186249E+10 | 0.554854E+09 | 0.130763E+10 | 0.200709E+10 | 0.848822E+09 |
June | 0.164903E+10 | 0.442743E+09 | 0.120628E+10 | 0.181483E+10 | 0.654883E+09 |
July | 0.185828E+10 | 0.680601E+09 | 0.117768E+10 | 0.226584E+10 | 0.609750E+09 |
August | 0.199649E+10 | 0.930996E+09 | 0.106549E+10 | 0.252014E+10 | 0.588145E+09 |
September | 0.214067E+10 | 0.118215E+10 | 0.958522E+09 | 0.253519E+10 | 0.795185E+09 |
October | 0.200372E+10 | 0.123715E+10 | 0.766571E+09 | 0.215283E+10 | 0.109927E+10 |
November | 0.114645E+10 | 0.657013E+09 | 0.489438E+09 | 0.101060E+10 | 0.130775E+10 |
December | 0.123950E+10 | 0.802130E+09 | 0.437371E+09 | 0.112599E+10 | 0.165206E+10 |
Annual Sum or Average | 0.205832E+11 | 0.100676E+11 | 0.105156E+11 | 0.219383E+11 | 0.126914E+11 |
Minimum of Months | 0.114645E+10 | 0.442743E+09 | 0.437371E+09 | 0.955598E+09 | 0.588145E+09 |
Maximum of Months | 0.214067E+10 | 0.123715E+10 | 0.130763E+10 | 0.253519E+10 | 0.165206E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.116621E+10 | 0.692499E+09 | 0.473708E+09 | 0.955597E+09 | 0.157891E+10 |
February | 0.161989E+10 | 0.100273E+10 | 0.617155E+09 | 0.153242E+10 | 0.128755E+10 |
March | 0.192923E+10 | 0.102884E+10 | 0.900393E+09 | 0.192687E+10 | 0.125199E+10 |
April | 0.197120E+10 | 0.855882E+09 | 0.111531E+10 | 0.209094E+10 | 0.101704E+10 |
May | 0.186249E+10 | 0.554853E+09 | 0.130763E+10 | 0.200708E+10 | 0.848822E+09 |
June | 0.164903E+10 | 0.442742E+09 | 0.120628E+10 | 0.181483E+10 | 0.654883E+09 |
July | 0.185828E+10 | 0.680600E+09 | 0.117768E+10 | 0.226584E+10 | 0.609750E+09 |
August | 0.199649E+10 | 0.930994E+09 | 0.106549E+10 | 0.252013E+10 | 0.588144E+09 |
September | 0.214067E+10 | 0.118215E+10 | 0.958521E+09 | 0.253518E+10 | 0.795185E+09 |
October | 0.200372E+10 | 0.123715E+10 | 0.766571E+09 | 0.215283E+10 | 0.109927E+10 |
November | 0.114645E+10 | 0.657013E+09 | 0.489438E+09 | 0.101060E+10 | 0.130775E+10 |
December | 0.123950E+10 | 0.802129E+09 | 0.437370E+09 | 0.112599E+10 | 0.165206E+10 |
Annual Sum or Average | 0.205831E+11 | 0.100676E+11 | 0.105156E+11 | 0.219383E+11 | 0.126914E+11 |
Minimum of Months | 0.114645E+10 | 0.442742E+09 | 0.437370E+09 | 0.955597E+09 | 0.588144E+09 |
Maximum of Months | 0.214067E+10 | 0.123715E+10 | 0.130763E+10 | 0.253518E+10 | 0.165206E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.116621E+10 | 0.692500E+09 | 0.473709E+09 | 0.955598E+09 | 0.157891E+10 |
February | 0.161989E+10 | 0.100273E+10 | 0.617156E+09 | 0.153243E+10 | 0.128755E+10 |
March | 0.192923E+10 | 0.102884E+10 | 0.900394E+09 | 0.192687E+10 | 0.125199E+10 |
April | 0.197120E+10 | 0.855883E+09 | 0.111531E+10 | 0.209094E+10 | 0.101704E+10 |
May | 0.186249E+10 | 0.554854E+09 | 0.130763E+10 | 0.200709E+10 | 0.848822E+09 |
June | 0.164903E+10 | 0.442743E+09 | 0.120628E+10 | 0.181483E+10 | 0.654883E+09 |
July | 0.185828E+10 | 0.680601E+09 | 0.117768E+10 | 0.226584E+10 | 0.609750E+09 |
August | 0.199649E+10 | 0.930996E+09 | 0.106549E+10 | 0.252014E+10 | 0.588145E+09 |
September | 0.214067E+10 | 0.118215E+10 | 0.958522E+09 | 0.253519E+10 | 0.795185E+09 |
October | 0.200372E+10 | 0.123715E+10 | 0.766571E+09 | 0.215283E+10 | 0.109927E+10 |
November | 0.114645E+10 | 0.657013E+09 | 0.489438E+09 | 0.101060E+10 | 0.130775E+10 |
December | 0.123950E+10 | 0.802130E+09 | 0.437371E+09 | 0.112599E+10 | 0.165206E+10 |
Annual Sum or Average | 0.205832E+11 | 0.100676E+11 | 0.105156E+11 | 0.219383E+11 | 0.126914E+11 |
Minimum of Months | 0.114645E+10 | 0.442743E+09 | 0.437371E+09 | 0.955598E+09 | 0.588145E+09 |
Maximum of Months | 0.214067E+10 | 0.123715E+10 | 0.130763E+10 | 0.253519E+10 | 0.165206E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.116621E+10 | 0.692499E+09 | 0.473708E+09 | 0.955597E+09 | 0.157891E+10 |
February | 0.161989E+10 | 0.100273E+10 | 0.617155E+09 | 0.153242E+10 | 0.128755E+10 |
March | 0.192923E+10 | 0.102884E+10 | 0.900393E+09 | 0.192687E+10 | 0.125199E+10 |
April | 0.197120E+10 | 0.855882E+09 | 0.111531E+10 | 0.209094E+10 | 0.101704E+10 |
May | 0.186249E+10 | 0.554853E+09 | 0.130763E+10 | 0.200708E+10 | 0.848822E+09 |
June | 0.164903E+10 | 0.442742E+09 | 0.120628E+10 | 0.181483E+10 | 0.654883E+09 |
July | 0.185828E+10 | 0.680600E+09 | 0.117768E+10 | 0.226584E+10 | 0.609750E+09 |
August | 0.199649E+10 | 0.930994E+09 | 0.106549E+10 | 0.252013E+10 | 0.588144E+09 |
September | 0.214067E+10 | 0.118215E+10 | 0.958521E+09 | 0.253518E+10 | 0.795185E+09 |
October | 0.200372E+10 | 0.123715E+10 | 0.766571E+09 | 0.215283E+10 | 0.109927E+10 |
November | 0.114645E+10 | 0.657013E+09 | 0.489438E+09 | 0.101060E+10 | 0.130775E+10 |
December | 0.123950E+10 | 0.802129E+09 | 0.437370E+09 | 0.112599E+10 | 0.165206E+10 |
Annual Sum or Average | 0.205831E+11 | 0.100676E+11 | 0.105156E+11 | 0.219383E+11 | 0.126914E+11 |
Minimum of Months | 0.114645E+10 | 0.442742E+09 | 0.437370E+09 | 0.955597E+09 | 0.588144E+09 |
Maximum of Months | 0.214067E+10 | 0.123715E+10 | 0.130763E+10 | 0.253518E+10 | 0.165206E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.116616E+10 | 0.692472E+09 | 0.473690E+09 | 0.955560E+09 | 0.157885E+10 |
February | 0.161982E+10 | 0.100269E+10 | 0.617131E+09 | 0.153236E+10 | 0.128750E+10 |
March | 0.192916E+10 | 0.102880E+10 | 0.900358E+09 | 0.192679E+10 | 0.125194E+10 |
April | 0.197112E+10 | 0.855849E+09 | 0.111527E+10 | 0.209086E+10 | 0.101700E+10 |
May | 0.186241E+10 | 0.554832E+09 | 0.130758E+10 | 0.200701E+10 | 0.848787E+09 |
June | 0.164896E+10 | 0.442725E+09 | 0.120624E+10 | 0.181476E+10 | 0.654857E+09 |
July | 0.185821E+10 | 0.680574E+09 | 0.117763E+10 | 0.226575E+10 | 0.609726E+09 |
August | 0.199641E+10 | 0.930958E+09 | 0.106545E+10 | 0.252003E+10 | 0.588121E+09 |
September | 0.214058E+10 | 0.118210E+10 | 0.958483E+09 | 0.253508E+10 | 0.795153E+09 |
October | 0.200364E+10 | 0.123710E+10 | 0.766540E+09 | 0.215274E+10 | 0.109923E+10 |
November | 0.114641E+10 | 0.656987E+09 | 0.489419E+09 | 0.101056E+10 | 0.130770E+10 |
December | 0.123945E+10 | 0.802098E+09 | 0.437353E+09 | 0.112594E+10 | 0.165199E+10 |
Annual Sum or Average | 0.205823E+11 | 0.100672E+11 | 0.105151E+11 | 0.219375E+11 | 0.126909E+11 |
Minimum of Months | 0.114641E+10 | 0.442725E+09 | 0.437353E+09 | 0.955560E+09 | 0.588121E+09 |
Maximum of Months | 0.214058E+10 | 0.123710E+10 | 0.130758E+10 | 0.253508E+10 | 0.165199E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.497057E+09 | 0.146573E+09 | 0.350484E+09 | 0.173250E+09 | 0.204368E+10 |
February | 0.804940E+09 | 0.302519E+09 | 0.502421E+09 | 0.476117E+09 | 0.167297E+10 |
March | 0.124878E+10 | 0.421495E+09 | 0.827280E+09 | 0.907253E+09 | 0.159316E+10 |
April | 0.183859E+10 | 0.702964E+09 | 0.113563E+10 | 0.166503E+10 | 0.127949E+10 |
May | 0.244470E+10 | 0.993150E+09 | 0.145155E+10 | 0.252885E+10 | 0.100353E+10 |
June | 0.227529E+10 | 0.883419E+09 | 0.139187E+10 | 0.239789E+10 | 0.796315E+09 |
July | 0.290450E+10 | 0.152676E+10 | 0.137775E+10 | 0.337897E+10 | 0.772018E+09 |
August | 0.240272E+10 | 0.122690E+10 | 0.117582E+10 | 0.281895E+10 | 0.768367E+09 |
September | 0.189353E+10 | 0.908557E+09 | 0.984973E+09 | 0.205269E+10 | 0.961362E+09 |
October | 0.111393E+10 | 0.453872E+09 | 0.660054E+09 | 0.916063E+09 | 0.139531E+10 |
November | 0.536834E+09 | 0.151409E+09 | 0.385424E+09 | 0.231161E+09 | 0.176065E+10 |
December | 0.466356E+09 | 0.159808E+09 | 0.306548E+09 | 0.202736E+09 | 0.228137E+10 |
Annual Sum or Average | 0.184272E+11 | 0.787742E+10 | 0.105498E+11 | 0.177490E+11 | 0.163282E+11 |
Minimum of Months | 0.466356E+09 | 0.146573E+09 | 0.306548E+09 | 0.173250E+09 | 0.768367E+09 |
Maximum of Months | 0.290450E+10 | 0.152676E+10 | 0.145155E+10 | 0.337897E+10 | 0.228137E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.497057E+09 | 0.146573E+09 | 0.350484E+09 | 0.173250E+09 | 0.204368E+10 |
February | 0.804940E+09 | 0.302519E+09 | 0.502421E+09 | 0.476117E+09 | 0.167297E+10 |
March | 0.124878E+10 | 0.421495E+09 | 0.827280E+09 | 0.907253E+09 | 0.159316E+10 |
April | 0.183859E+10 | 0.702964E+09 | 0.113563E+10 | 0.166503E+10 | 0.127949E+10 |
May | 0.244470E+10 | 0.993150E+09 | 0.145155E+10 | 0.252885E+10 | 0.100353E+10 |
June | 0.227529E+10 | 0.883419E+09 | 0.139187E+10 | 0.239789E+10 | 0.796315E+09 |
July | 0.290450E+10 | 0.152676E+10 | 0.137775E+10 | 0.337897E+10 | 0.772018E+09 |
August | 0.240272E+10 | 0.122690E+10 | 0.117582E+10 | 0.281895E+10 | 0.768367E+09 |
September | 0.189353E+10 | 0.908557E+09 | 0.984973E+09 | 0.205269E+10 | 0.961362E+09 |
October | 0.111393E+10 | 0.453872E+09 | 0.660054E+09 | 0.916063E+09 | 0.139531E+10 |
November | 0.536834E+09 | 0.151409E+09 | 0.385424E+09 | 0.231161E+09 | 0.176065E+10 |
December | 0.466356E+09 | 0.159808E+09 | 0.306548E+09 | 0.202736E+09 | 0.228137E+10 |
Annual Sum or Average | 0.184272E+11 | 0.787742E+10 | 0.105498E+11 | 0.177490E+11 | 0.163282E+11 |
Minimum of Months | 0.466356E+09 | 0.146573E+09 | 0.306548E+09 | 0.173250E+09 | 0.768367E+09 |
Maximum of Months | 0.290450E+10 | 0.152676E+10 | 0.145155E+10 | 0.337897E+10 | 0.228137E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.497047E+09 | 0.146570E+09 | 0.350477E+09 | 0.173247E+09 | 0.204364E+10 |
February | 0.804925E+09 | 0.302514E+09 | 0.502412E+09 | 0.476108E+09 | 0.167294E+10 |
March | 0.124875E+10 | 0.421487E+09 | 0.827265E+09 | 0.907236E+09 | 0.159313E+10 |
April | 0.183856E+10 | 0.702951E+09 | 0.113561E+10 | 0.166500E+10 | 0.127947E+10 |
May | 0.244466E+10 | 0.993131E+09 | 0.145152E+10 | 0.252880E+10 | 0.100351E+10 |
June | 0.227525E+10 | 0.883403E+09 | 0.139184E+10 | 0.239785E+10 | 0.796301E+09 |
July | 0.290445E+10 | 0.152673E+10 | 0.137772E+10 | 0.337891E+10 | 0.772004E+09 |
August | 0.240268E+10 | 0.122688E+10 | 0.117580E+10 | 0.281890E+10 | 0.768353E+09 |
September | 0.189350E+10 | 0.908541E+09 | 0.984955E+09 | 0.205265E+10 | 0.961344E+09 |
October | 0.111391E+10 | 0.453863E+09 | 0.660042E+09 | 0.916046E+09 | 0.139528E+10 |
November | 0.536824E+09 | 0.151407E+09 | 0.385417E+09 | 0.231157E+09 | 0.176062E+10 |
December | 0.466348E+09 | 0.159806E+09 | 0.306542E+09 | 0.202732E+09 | 0.228133E+10 |
Annual Sum or Average | 0.184269E+11 | 0.787728E+10 | 0.105496E+11 | 0.177486E+11 | 0.163279E+11 |
Minimum of Months | 0.466348E+09 | 0.146570E+09 | 0.306542E+09 | 0.173247E+09 | 0.768353E+09 |
Maximum of Months | 0.290445E+10 | 0.152673E+10 | 0.145152E+10 | 0.337891E+10 | 0.228133E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.131973E+10 | 0.00 | 0.131973E+10 | 37012953.48 | 0.796121E+10 |
February | 0.185480E+10 | 0.00 | 0.185480E+10 | 0.322823E+09 | 0.641434E+10 |
March | 0.302556E+10 | 0.00 | 0.302556E+10 | 0.115605E+10 | 0.585705E+10 |
April | 0.414336E+10 | 14697755.32 | 0.412866E+10 | 0.252428E+10 | 0.450564E+10 |
May | 0.550918E+10 | 0.163670E+09 | 0.534551E+10 | 0.422566E+10 | 0.377241E+10 |
June | 0.560590E+10 | 0.370190E+09 | 0.523571E+10 | 0.476260E+10 | 0.282154E+10 |
July | 0.550570E+10 | 0.431673E+09 | 0.507403E+10 | 0.532558E+10 | 0.261552E+10 |
August | 0.445691E+10 | 0.120484E+09 | 0.433642E+10 | 0.438942E+10 | 0.257052E+10 |
September | 0.335029E+10 | 987949.56 | 0.334930E+10 | 0.242956E+10 | 0.370404E+10 |
October | 0.237202E+10 | 0.00 | 0.237202E+10 | 0.996833E+09 | 0.513999E+10 |
November | 0.144594E+10 | 0.00 | 0.144594E+10 | 0.175178E+09 | 0.631497E+10 |
December | 0.112143E+10 | 0.00 | 0.112143E+10 | 17248377.72 | 0.808206E+10 |
Annual Sum or Average | 0.397108E+11 | 0.110170E+10 | 0.386091E+11 | 0.263622E+11 | 0.597593E+11 |
Minimum of Months | 0.112143E+10 | 0.00 | 0.112143E+10 | 17248377.72 | 0.257052E+10 |
Maximum of Months | 0.560590E+10 | 0.431673E+09 | 0.534551E+10 | 0.532558E+10 | 0.808206E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.141374E+10 | 0.358431E+09 | 0.105531E+10 | 0.463319E+09 | 0.503985E+10 |
February | 0.234304E+10 | 0.831595E+09 | 0.151145E+10 | 0.141844E+10 | 0.403616E+10 |
March | 0.387314E+10 | 0.140211E+10 | 0.247103E+10 | 0.302328E+10 | 0.370911E+10 |
April | 0.581036E+10 | 0.241429E+10 | 0.339607E+10 | 0.556050E+10 | 0.287749E+10 |
May | 0.638883E+10 | 0.222125E+10 | 0.416758E+10 | 0.645121E+10 | 0.249672E+10 |
June | 0.740453E+10 | 0.322176E+10 | 0.418277E+10 | 0.804309E+10 | 0.190896E+10 |
July | 0.712518E+10 | 0.319819E+10 | 0.392699E+10 | 0.811043E+10 | 0.172811E+10 |
August | 0.700306E+10 | 0.350333E+10 | 0.349973E+10 | 0.823962E+10 | 0.170090E+10 |
September | 0.501071E+10 | 0.231098E+10 | 0.269973E+10 | 0.524498E+10 | 0.234725E+10 |
October | 0.337484E+10 | 0.143399E+10 | 0.194085E+10 | 0.290387E+10 | 0.326673E+10 |
November | 0.160080E+10 | 0.451922E+09 | 0.114888E+10 | 0.790470E+09 | 0.402372E+10 |
December | 0.135678E+10 | 0.436788E+09 | 0.919994E+09 | 0.586587E+09 | 0.516091E+10 |
Annual Sum or Average | 0.527050E+11 | 0.217846E+11 | 0.309204E+11 | 0.508358E+11 | 0.382959E+11 |
Minimum of Months | 0.135678E+10 | 0.358431E+09 | 0.919994E+09 | 0.463319E+09 | 0.170090E+10 |
Maximum of Months | 0.740453E+10 | 0.350333E+10 | 0.418277E+10 | 0.823962E+10 | 0.516091E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.583097E+10 | 0.346246E+10 | 0.236851E+10 | 0.483466E+10 | 0.733893E+10 |
February | 0.809935E+10 | 0.501361E+10 | 0.308574E+10 | 0.769900E+10 | 0.608944E+10 |
March | 0.964605E+10 | 0.514413E+10 | 0.450192E+10 | 0.963916E+10 | 0.588970E+10 |
April | 0.985587E+10 | 0.427936E+10 | 0.557651E+10 | 0.104518E+11 | 0.479418E+10 |
May | 0.931233E+10 | 0.277424E+10 | 0.653809E+10 | 0.999274E+10 | 0.408636E+10 |
June | 0.824504E+10 | 0.221369E+10 | 0.603135E+10 | 0.905489E+10 | 0.312228E+10 |
July | 0.929129E+10 | 0.340296E+10 | 0.588832E+10 | 0.112988E+11 | 0.292175E+10 |
August | 0.998232E+10 | 0.465492E+10 | 0.532740E+10 | 0.125610E+11 | 0.285441E+10 |
September | 0.107032E+11 | 0.591068E+10 | 0.479255E+10 | 0.126336E+11 | 0.385231E+10 |
October | 0.100185E+11 | 0.618568E+10 | 0.383281E+10 | 0.107356E+11 | 0.521285E+10 |
November | 0.573219E+10 | 0.328503E+10 | 0.244716E+10 | 0.511834E+10 | 0.605701E+10 |
December | 0.619743E+10 | 0.401060E+10 | 0.218683E+10 | 0.569556E+10 | 0.763177E+10 |
Annual Sum or Average | 0.102915E+12 | 0.503374E+11 | 0.525772E+11 | 0.109715E+12 | 0.598510E+11 |
Minimum of Months | 0.573219E+10 | 0.221369E+10 | 0.218683E+10 | 0.483466E+10 | 0.285441E+10 |
Maximum of Months | 0.107032E+11 | 0.618568E+10 | 0.653809E+10 | 0.126336E+11 | 0.763177E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.149115E+10 | 0.439714E+09 | 0.105144E+10 | 0.578916E+09 | 0.521666E+10 |
February | 0.241479E+10 | 0.907548E+09 | 0.150725E+10 | 0.156973E+10 | 0.420830E+10 |
March | 0.374629E+10 | 0.126447E+10 | 0.248182E+10 | 0.293614E+10 | 0.391962E+10 |
April | 0.551572E+10 | 0.210887E+10 | 0.340685E+10 | 0.523966E+10 | 0.316734E+10 |
May | 0.733403E+10 | 0.297942E+10 | 0.435461E+10 | 0.766014E+10 | 0.275276E+10 |
June | 0.682580E+10 | 0.265023E+10 | 0.417557E+10 | 0.730199E+10 | 0.210826E+10 |
July | 0.871342E+10 | 0.458022E+10 | 0.413320E+10 | 0.102366E+11 | 0.204089E+10 |
August | 0.720808E+10 | 0.368066E+10 | 0.352743E+10 | 0.859652E+10 | 0.198400E+10 |
September | 0.568053E+10 | 0.272564E+10 | 0.295489E+10 | 0.623805E+10 | 0.260443E+10 |
October | 0.334174E+10 | 0.136160E+10 | 0.198014E+10 | 0.291446E+10 | 0.348932E+10 |
November | 0.161048E+10 | 0.454224E+09 | 0.115626E+10 | 0.820906E+09 | 0.416816E+10 |
December | 0.139905E+10 | 0.479421E+09 | 0.919634E+09 | 0.698356E+09 | 0.537016E+10 |
Annual Sum or Average | 0.552811E+11 | 0.236320E+11 | 0.316491E+11 | 0.547915E+11 | 0.410299E+11 |
Minimum of Months | 0.139905E+10 | 0.439714E+09 | 0.919634E+09 | 0.578916E+09 | 0.198400E+10 |
Maximum of Months | 0.871342E+10 | 0.458022E+10 | 0.435461E+10 | 0.102366E+11 | 0.537016E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.131973E+10 | 0.00 | 0.131973E+10 | 58651596.34 | 0.746130E+10 |
February | 0.185480E+10 | 0.00 | 0.185480E+10 | 0.385299E+09 | 0.594005E+10 |
March | 0.302556E+10 | 0.00 | 0.302556E+10 | 0.127842E+10 | 0.538488E+10 |
April | 0.414336E+10 | 14697755.32 | 0.412866E+10 | 0.263972E+10 | 0.420864E+10 |
May | 0.550918E+10 | 0.163670E+09 | 0.534551E+10 | 0.431271E+10 | 0.357732E+10 |
June | 0.560590E+10 | 0.370190E+09 | 0.523571E+10 | 0.478256E+10 | 0.273203E+10 |
July | 0.550570E+10 | 0.431673E+09 | 0.507403E+10 | 0.532086E+10 | 0.254761E+10 |
August | 0.445691E+10 | 0.120484E+09 | 0.433642E+10 | 0.440215E+10 | 0.248779E+10 |
September | 0.335029E+10 | 987949.56 | 0.334930E+10 | 0.250399E+10 | 0.347510E+10 |
October | 0.237202E+10 | 0.00 | 0.237202E+10 | 0.112494E+10 | 0.466673E+10 |
November | 0.144594E+10 | 0.00 | 0.144594E+10 | 0.231338E+09 | 0.569818E+10 |
December | 0.112143E+10 | 0.00 | 0.112143E+10 | 38393613.46 | 0.741330E+10 |
Annual Sum or Average | 0.397108E+11 | 0.110170E+10 | 0.386091E+11 | 0.270790E+11 | 0.555929E+11 |
Minimum of Months | 0.112143E+10 | 0.00 | 0.112143E+10 | 38393613.46 | 0.248779E+10 |
Maximum of Months | 0.560590E+10 | 0.431673E+09 | 0.534551E+10 | 0.532086E+10 | 0.746130E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.141374E+10 | 0.358431E+09 | 0.105531E+10 | 0.497095E+09 | 0.473326E+10 |
February | 0.234304E+10 | 0.831595E+09 | 0.151145E+10 | 0.148948E+10 | 0.374933E+10 |
March | 0.387314E+10 | 0.140211E+10 | 0.247103E+10 | 0.310324E+10 | 0.344907E+10 |
April | 0.581036E+10 | 0.241429E+10 | 0.339607E+10 | 0.561825E+10 | 0.271974E+10 |
May | 0.638883E+10 | 0.222125E+10 | 0.416758E+10 | 0.648132E+10 | 0.239202E+10 |
June | 0.740453E+10 | 0.322176E+10 | 0.418277E+10 | 0.802996E+10 | 0.186498E+10 |
July | 0.712518E+10 | 0.319819E+10 | 0.392699E+10 | 0.809263E+10 | 0.169895E+10 |
August | 0.700306E+10 | 0.350333E+10 | 0.349973E+10 | 0.822992E+10 | 0.166289E+10 |
September | 0.501071E+10 | 0.231098E+10 | 0.269973E+10 | 0.527622E+10 | 0.223467E+10 |
October | 0.337484E+10 | 0.143399E+10 | 0.194085E+10 | 0.298106E+10 | 0.301506E+10 |
November | 0.160080E+10 | 0.451922E+09 | 0.114888E+10 | 0.846666E+09 | 0.367079E+10 |
December | 0.135678E+10 | 0.436788E+09 | 0.919994E+09 | 0.630639E+09 | 0.475932E+10 |
Annual Sum or Average | 0.527050E+11 | 0.217846E+11 | 0.309204E+11 | 0.512765E+11 | 0.359501E+11 |
Minimum of Months | 0.135678E+10 | 0.358431E+09 | 0.919994E+09 | 0.497095E+09 | 0.166289E+10 |
Maximum of Months | 0.740453E+10 | 0.350333E+10 | 0.418277E+10 | 0.822992E+10 | 0.475932E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.583097E+10 | 0.346246E+10 | 0.236851E+10 | 0.493810E+10 | 0.684378E+10 |
February | 0.809935E+10 | 0.501361E+10 | 0.308574E+10 | 0.783116E+10 | 0.564275E+10 |
March | 0.964605E+10 | 0.514413E+10 | 0.450192E+10 | 0.973517E+10 | 0.546723E+10 |
April | 0.985587E+10 | 0.427936E+10 | 0.557651E+10 | 0.105222E+11 | 0.452384E+10 |
May | 0.931233E+10 | 0.277424E+10 | 0.653809E+10 | 0.100322E+11 | 0.389560E+10 |
June | 0.824504E+10 | 0.221369E+10 | 0.603135E+10 | 0.904793E+10 | 0.302776E+10 |
July | 0.929129E+10 | 0.340296E+10 | 0.588832E+10 | 0.112759E+11 | 0.285338E+10 |
August | 0.998232E+10 | 0.465492E+10 | 0.532740E+10 | 0.125491E+11 | 0.277117E+10 |
September | 0.107032E+11 | 0.591068E+10 | 0.479255E+10 | 0.126796E+11 | 0.365908E+10 |
October | 0.100185E+11 | 0.618568E+10 | 0.383281E+10 | 0.108378E+11 | 0.481875E+10 |
November | 0.573219E+10 | 0.328503E+10 | 0.244716E+10 | 0.523842E+10 | 0.553634E+10 |
December | 0.619743E+10 | 0.401060E+10 | 0.218683E+10 | 0.580371E+10 | 0.703372E+10 |
Annual Sum or Average | 0.102915E+12 | 0.503374E+11 | 0.525772E+11 | 0.110491E+12 | 0.560734E+11 |
Minimum of Months | 0.573219E+10 | 0.221369E+10 | 0.218683E+10 | 0.493810E+10 | 0.277117E+10 |
Maximum of Months | 0.107032E+11 | 0.618568E+10 | 0.653809E+10 | 0.126796E+11 | 0.703372E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.149115E+10 | 0.439714E+09 | 0.105144E+10 | 0.602356E+09 | 0.491075E+10 |
February | 0.241479E+10 | 0.907548E+09 | 0.150725E+10 | 0.161192E+10 | 0.394746E+10 |
March | 0.374629E+10 | 0.126447E+10 | 0.248182E+10 | 0.298564E+10 | 0.367438E+10 |
April | 0.551572E+10 | 0.210887E+10 | 0.340685E+10 | 0.528063E+10 | 0.300631E+10 |
May | 0.733403E+10 | 0.297942E+10 | 0.435461E+10 | 0.767847E+10 | 0.263815E+10 |
June | 0.682580E+10 | 0.265023E+10 | 0.417557E+10 | 0.729275E+10 | 0.204843E+10 |
July | 0.871342E+10 | 0.458022E+10 | 0.413320E+10 | 0.102118E+11 | 0.199597E+10 |
August | 0.720808E+10 | 0.368066E+10 | 0.352743E+10 | 0.858669E+10 | 0.193080E+10 |
September | 0.568053E+10 | 0.272564E+10 | 0.295489E+10 | 0.626472E+10 | 0.248652E+10 |
October | 0.334174E+10 | 0.136160E+10 | 0.198014E+10 | 0.296941E+10 | 0.325124E+10 |
November | 0.161048E+10 | 0.454224E+09 | 0.115626E+10 | 0.857544E+09 | 0.386303E+10 |
December | 0.139905E+10 | 0.479421E+09 | 0.919634E+09 | 0.721540E+09 | 0.501068E+10 |
Annual Sum or Average | 0.552811E+11 | 0.236320E+11 | 0.316491E+11 | 0.550635E+11 | 0.387637E+11 |
Minimum of Months | 0.139905E+10 | 0.439714E+09 | 0.919634E+09 | 0.602356E+09 | 0.193080E+10 |
Maximum of Months | 0.871342E+10 | 0.458022E+10 | 0.435461E+10 | 0.102118E+11 | 0.501068E+10 |
Report: WindowZoneSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 4.44 | 3472.63 | 492.73 | 0.00 | 492.73 | 0.00 | 0.00 |
February | 86.64 | 3068.73 | 766.70 | 0.00 | 766.70 | 0.00 | 0.00 |
March | 353.06 | 2508.10 | 1129.62 | 0.00 | 1129.62 | 0.00 | 0.00 |
April | 888.85 | 1968.46 | 1598.52 | 5.67 | 1592.85 | 0.00 | 0.00 |
May | 1533.86 | 1509.60 | 2056.90 | 61.11 | 1995.79 | 0.00 | 0.00 |
June | 1803.03 | 1164.83 | 2162.78 | 142.82 | 2019.96 | 0.00 | 0.00 |
July | 1950.47 | 1046.23 | 2055.60 | 161.17 | 1894.43 | 0.00 | 0.00 |
August | 1599.21 | 1029.17 | 1664.02 | 44.98 | 1619.04 | 0.00 | 0.00 |
September | 902.15 | 1546.58 | 1292.55 | 0.38 | 1292.17 | 0.00 | 0.00 |
October | 307.68 | 2198.54 | 885.61 | 0.00 | 885.61 | 0.00 | 0.00 |
November | 38.76 | 2897.79 | 557.85 | 0.00 | 557.85 | 0.00 | 0.00 |
December | 0.91 | 3587.08 | 418.70 | 0.00 | 418.70 | 0.00 | 0.00 |
Annual Sum or Average | 793.56 | 2162.04 | 1259.23 | 34.93 | 1224.29 | 0.00 | 0.00 |
Minimum of Months | 0.91 | 1029.17 | 418.70 | 0.00 | 418.70 | 0.00 | 0.00 |
Maximum of Months | 1950.47 | 3587.08 | 2162.78 | 161.17 | 2019.96 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 153.88 | 2143.68 | 527.83 | 133.82 | 394.01 | 0.00 | 0.00 |
February | 545.56 | 1851.91 | 968.52 | 343.75 | 624.77 | 0.00 | 0.00 |
March | 1095.39 | 1524.66 | 1446.07 | 523.49 | 922.58 | 0.00 | 0.00 |
April | 2128.29 | 1197.74 | 2241.66 | 931.44 | 1310.22 | 0.00 | 0.00 |
May | 2402.90 | 987.09 | 2385.33 | 829.32 | 1556.00 | 0.00 | 0.00 |
June | 3115.33 | 769.95 | 2856.70 | 1242.97 | 1613.73 | 0.00 | 0.00 |
July | 3038.54 | 666.48 | 2660.25 | 1194.07 | 1466.18 | 0.00 | 0.00 |
August | 3092.86 | 641.01 | 2614.65 | 1308.00 | 1306.65 | 0.00 | 0.00 |
September | 2016.12 | 963.96 | 1933.15 | 891.59 | 1041.57 | 0.00 | 0.00 |
October | 1055.94 | 1348.14 | 1260.03 | 535.39 | 724.63 | 0.00 | 0.00 |
November | 278.18 | 1757.20 | 617.59 | 174.35 | 443.24 | 0.00 | 0.00 |
December | 199.33 | 2172.32 | 506.57 | 163.08 | 343.49 | 0.00 | 0.00 |
Annual Sum or Average | 1598.95 | 1332.89 | 1671.27 | 690.79 | 980.48 | 0.00 | 0.00 |
Minimum of Months | 153.88 | 641.01 | 506.57 | 133.82 | 343.49 | 0.00 | 0.00 |
Maximum of Months | 3115.33 | 2172.32 | 2856.70 | 1308.00 | 1613.73 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1783.88 | 2947.47 | 2177.04 | 1292.74 | 884.31 | 0.00 | 0.00 |
February | 3167.19 | 2661.08 | 3347.96 | 2072.43 | 1275.53 | 0.00 | 0.00 |
March | 3597.03 | 2337.18 | 3601.44 | 1920.61 | 1680.83 | 0.00 | 0.00 |
April | 4033.42 | 1961.87 | 3802.43 | 1651.00 | 2151.44 | 0.00 | 0.00 |
May | 3746.77 | 1584.56 | 3476.84 | 1035.78 | 2441.05 | 0.00 | 0.00 |
June | 3500.81 | 1263.27 | 3180.97 | 854.05 | 2326.92 | 0.00 | 0.00 |
July | 4229.81 | 1138.26 | 3468.98 | 1270.53 | 2198.46 | 0.00 | 0.00 |
August | 4704.52 | 1097.93 | 3726.98 | 1737.95 | 1989.03 | 0.00 | 0.00 |
September | 4890.36 | 1533.91 | 4129.35 | 2280.36 | 1848.98 | 0.00 | 0.00 |
October | 4018.84 | 2052.09 | 3740.49 | 2309.48 | 1431.01 | 0.00 | 0.00 |
November | 1949.44 | 2522.65 | 2211.50 | 1267.38 | 944.12 | 0.00 | 0.00 |
December | 2101.96 | 3084.02 | 2313.86 | 1497.39 | 816.47 | 0.00 | 0.00 |
Annual Sum or Average | 3478.27 | 2012.19 | 3263.41 | 1596.19 | 1667.22 | 0.00 | 0.00 |
Minimum of Months | 1783.88 | 1097.93 | 2177.04 | 854.05 | 816.47 | 0.00 | 0.00 |
Maximum of Months | 4890.36 | 3084.02 | 4129.35 | 2309.48 | 2441.05 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 194.05 | 2289.06 | 556.74 | 164.17 | 392.56 | 0.00 | 0.00 |
February | 590.42 | 2074.60 | 998.18 | 375.15 | 623.04 | 0.00 | 0.00 |
March | 1016.18 | 1784.44 | 1398.71 | 472.10 | 926.61 | 0.00 | 0.00 |
April | 1927.10 | 1480.88 | 2127.99 | 813.61 | 1314.38 | 0.00 | 0.00 |
May | 2832.48 | 1124.02 | 2738.22 | 1112.39 | 1625.83 | 0.00 | 0.00 |
June | 2775.32 | 921.66 | 2633.42 | 1022.47 | 1610.95 | 0.00 | 0.00 |
July | 3784.66 | 864.71 | 3253.23 | 1710.06 | 1543.17 | 0.00 | 0.00 |
August | 3157.41 | 860.62 | 2691.20 | 1374.21 | 1317.00 | 0.00 | 0.00 |
September | 2375.79 | 1112.68 | 2191.57 | 1051.56 | 1140.01 | 0.00 | 0.00 |
October | 1026.05 | 1562.83 | 1247.67 | 508.37 | 739.30 | 0.00 | 0.00 |
November | 267.55 | 2037.78 | 621.33 | 175.24 | 446.09 | 0.00 | 0.00 |
December | 227.08 | 2555.28 | 522.35 | 179.00 | 343.35 | 0.00 | 0.00 |
Annual Sum or Average | 1688.44 | 1553.28 | 1752.96 | 749.37 | 1003.59 | 0.00 | 0.00 |
Minimum of Months | 194.05 | 860.62 | 522.35 | 164.17 | 343.35 | 0.00 | 0.00 |
Maximum of Months | 3784.66 | 2555.28 | 3253.23 | 1710.06 | 1625.83 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 13.82 | 2972.38 | 492.73 | 0.00 | 492.73 | 0.00 | 0.00 |
February | 133.44 | 2651.43 | 766.70 | 0.00 | 766.70 | 0.00 | 0.00 |
March | 431.62 | 2186.77 | 1129.61 | 0.00 | 1129.61 | 0.00 | 0.00 |
April | 973.87 | 1738.29 | 1598.52 | 5.67 | 1592.85 | 0.00 | 0.00 |
May | 1577.68 | 1408.46 | 2056.89 | 61.11 | 1995.78 | 0.00 | 0.00 |
June | 1837.42 | 1088.56 | 2162.77 | 142.82 | 2019.95 | 0.00 | 0.00 |
July | 1988.34 | 976.52 | 2055.59 | 161.17 | 1894.43 | 0.00 | 0.00 |
August | 1638.82 | 959.72 | 1664.02 | 44.98 | 1619.03 | 0.00 | 0.00 |
September | 937.33 | 1429.03 | 1292.55 | 0.38 | 1292.17 | 0.00 | 0.00 |
October | 372.17 | 1919.05 | 885.61 | 0.00 | 885.61 | 0.00 | 0.00 |
November | 67.58 | 2436.33 | 557.85 | 0.00 | 557.85 | 0.00 | 0.00 |
December | 6.44 | 3017.50 | 418.69 | 0.00 | 418.69 | 0.00 | 0.00 |
Annual Sum or Average | 835.94 | 1894.95 | 1259.22 | 34.93 | 1224.29 | 0.00 | 0.00 |
Minimum of Months | 6.44 | 959.72 | 418.69 | 0.00 | 418.69 | 0.00 | 0.00 |
Maximum of Months | 1988.34 | 3017.50 | 2162.77 | 161.17 | 2019.95 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 172.98 | 1881.67 | 527.83 | 133.82 | 394.01 | 0.00 | 0.00 |
February | 586.33 | 1668.39 | 968.52 | 343.75 | 624.77 | 0.00 | 0.00 |
March | 1128.76 | 1384.82 | 1446.07 | 523.49 | 922.58 | 0.00 | 0.00 |
April | 2145.25 | 1110.14 | 2241.65 | 931.44 | 1310.21 | 0.00 | 0.00 |
May | 2408.61 | 932.17 | 2385.32 | 829.32 | 1556.00 | 0.00 | 0.00 |
June | 3103.04 | 736.48 | 2856.69 | 1242.96 | 1613.72 | 0.00 | 0.00 |
July | 3028.09 | 645.20 | 2660.24 | 1194.07 | 1466.17 | 0.00 | 0.00 |
August | 3076.32 | 635.04 | 2614.64 | 1307.99 | 1306.65 | 0.00 | 0.00 |
September | 2023.53 | 905.57 | 1933.14 | 891.58 | 1041.56 | 0.00 | 0.00 |
October | 1084.18 | 1219.66 | 1260.02 | 535.39 | 724.63 | 0.00 | 0.00 |
November | 304.97 | 1552.36 | 617.59 | 174.35 | 443.24 | 0.00 | 0.00 |
December | 219.01 | 1926.86 | 506.56 | 163.08 | 343.49 | 0.00 | 0.00 |
Annual Sum or Average | 1611.99 | 1214.36 | 1671.26 | 690.79 | 980.48 | 0.00 | 0.00 |
Minimum of Months | 172.98 | 635.04 | 506.56 | 133.82 | 343.49 | 0.00 | 0.00 |
Maximum of Months | 3103.04 | 1926.86 | 2856.69 | 1307.99 | 1613.72 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1805.06 | 2740.04 | 2177.04 | 1292.73 | 884.30 | 0.00 | 0.00 |
February | 3182.46 | 2517.13 | 3347.95 | 2072.42 | 1275.52 | 0.00 | 0.00 |
March | 3598.85 | 2198.96 | 3601.42 | 1920.60 | 1680.82 | 0.00 | 0.00 |
April | 4032.32 | 1849.61 | 3802.42 | 1650.99 | 2151.43 | 0.00 | 0.00 |
May | 3730.86 | 1525.67 | 3476.82 | 1035.78 | 2441.04 | 0.00 | 0.00 |
June | 3493.40 | 1204.59 | 3180.95 | 854.05 | 2326.91 | 0.00 | 0.00 |
July | 4218.50 | 1090.86 | 3468.97 | 1270.52 | 2198.45 | 0.00 | 0.00 |
August | 4689.75 | 1065.71 | 3726.97 | 1737.95 | 1989.02 | 0.00 | 0.00 |
September | 4874.09 | 1486.23 | 4129.33 | 2280.35 | 1848.98 | 0.00 | 0.00 |
October | 4008.22 | 1946.25 | 3740.47 | 2309.47 | 1431.01 | 0.00 | 0.00 |
November | 1974.67 | 2336.81 | 2211.49 | 1267.37 | 944.12 | 0.00 | 0.00 |
December | 2126.48 | 2849.38 | 2313.86 | 1497.39 | 816.47 | 0.00 | 0.00 |
Annual Sum or Average | 3479.05 | 1897.86 | 3263.40 | 1596.19 | 1667.21 | 0.00 | 0.00 |
Minimum of Months | 1805.06 | 1065.71 | 2177.04 | 854.05 | 816.47 | 0.00 | 0.00 |
Maximum of Months | 4874.09 | 2849.38 | 4129.33 | 2309.47 | 2441.04 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 216.14 | 1947.68 | 556.73 | 164.17 | 392.56 | 0.00 | 0.00 |
February | 648.86 | 1739.54 | 998.18 | 375.14 | 623.04 | 0.00 | 0.00 |
March | 1096.23 | 1463.42 | 1398.70 | 472.10 | 926.60 | 0.00 | 0.00 |
April | 2021.47 | 1221.97 | 2127.98 | 813.61 | 1314.37 | 0.00 | 0.00 |
May | 2859.97 | 1027.76 | 2738.21 | 1112.39 | 1625.82 | 0.00 | 0.00 |
June | 2817.12 | 813.37 | 2633.41 | 1022.47 | 1610.94 | 0.00 | 0.00 |
July | 3821.92 | 761.98 | 3253.22 | 1710.06 | 1543.16 | 0.00 | 0.00 |
August | 3209.57 | 740.74 | 2691.19 | 1374.20 | 1316.99 | 0.00 | 0.00 |
September | 2406.66 | 1004.80 | 2191.56 | 1051.56 | 1140.00 | 0.00 | 0.00 |
October | 1088.13 | 1302.76 | 1247.66 | 508.36 | 739.30 | 0.00 | 0.00 |
November | 316.71 | 1608.09 | 621.33 | 175.24 | 446.09 | 0.00 | 0.00 |
December | 260.74 | 2004.99 | 522.35 | 179.00 | 343.35 | 0.00 | 0.00 |
Annual Sum or Average | 1737.43 | 1301.05 | 1752.95 | 749.37 | 1003.59 | 0.00 | 0.00 |
Minimum of Months | 216.14 | 740.74 | 522.35 | 164.17 | 343.35 | 0.00 | 0.00 |
Maximum of Months | 3821.92 | 2004.99 | 3253.22 | 1710.06 | 1625.82 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 21.90 | 2785.73 | 492.73 | 0.00 | 492.73 | 0.00 | 0.00 |
February | 159.27 | 2455.38 | 766.70 | 0.00 | 766.70 | 0.00 | 0.00 |
March | 477.31 | 2010.48 | 1129.61 | 0.00 | 1129.61 | 0.00 | 0.00 |
April | 1018.41 | 1623.70 | 1598.52 | 5.67 | 1592.85 | 0.00 | 0.00 |
May | 1610.18 | 1335.62 | 2056.89 | 61.11 | 1995.78 | 0.00 | 0.00 |
June | 1845.12 | 1054.02 | 2162.77 | 142.82 | 2019.95 | 0.00 | 0.00 |
July | 1986.58 | 951.17 | 2055.59 | 161.17 | 1894.43 | 0.00 | 0.00 |
August | 1643.57 | 928.83 | 1664.02 | 44.98 | 1619.03 | 0.00 | 0.00 |
September | 966.05 | 1340.70 | 1292.55 | 0.38 | 1292.17 | 0.00 | 0.00 |
October | 420.00 | 1742.36 | 885.61 | 0.00 | 885.61 | 0.00 | 0.00 |
November | 89.25 | 2198.37 | 557.85 | 0.00 | 557.85 | 0.00 | 0.00 |
December | 14.33 | 2767.81 | 418.69 | 0.00 | 418.69 | 0.00 | 0.00 |
Annual Sum or Average | 858.67 | 1762.84 | 1259.22 | 34.93 | 1224.29 | 0.00 | 0.00 |
Minimum of Months | 14.33 | 928.83 | 418.69 | 0.00 | 418.69 | 0.00 | 0.00 |
Maximum of Months | 1986.58 | 2785.73 | 2162.77 | 161.17 | 2019.95 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 185.59 | 1767.20 | 527.83 | 133.82 | 394.01 | 0.00 | 0.00 |
February | 615.69 | 1549.82 | 968.52 | 343.75 | 624.77 | 0.00 | 0.00 |
March | 1158.62 | 1287.73 | 1446.07 | 523.49 | 922.58 | 0.00 | 0.00 |
April | 2167.54 | 1049.28 | 2241.65 | 931.44 | 1310.21 | 0.00 | 0.00 |
May | 2419.85 | 893.08 | 2385.32 | 829.32 | 1556.00 | 0.00 | 0.00 |
June | 3097.98 | 719.51 | 2856.69 | 1242.96 | 1613.72 | 0.00 | 0.00 |
July | 3021.44 | 634.31 | 2660.24 | 1194.07 | 1466.17 | 0.00 | 0.00 |
August | 3072.70 | 620.85 | 2614.64 | 1307.99 | 1306.65 | 0.00 | 0.00 |
September | 2035.58 | 862.14 | 1933.14 | 891.58 | 1041.56 | 0.00 | 0.00 |
October | 1113.00 | 1125.69 | 1260.02 | 535.39 | 724.63 | 0.00 | 0.00 |
November | 326.65 | 1416.20 | 617.59 | 174.35 | 443.24 | 0.00 | 0.00 |
December | 235.45 | 1776.93 | 506.56 | 163.08 | 343.49 | 0.00 | 0.00 |
Annual Sum or Average | 1625.97 | 1139.97 | 1671.26 | 690.79 | 980.48 | 0.00 | 0.00 |
Minimum of Months | 185.59 | 620.85 | 506.56 | 133.82 | 343.49 | 0.00 | 0.00 |
Maximum of Months | 3097.98 | 1776.93 | 2856.69 | 1307.99 | 1613.72 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1843.68 | 2555.18 | 2177.04 | 1292.73 | 884.30 | 0.00 | 0.00 |
February | 3237.09 | 2332.48 | 3347.95 | 2072.42 | 1275.52 | 0.00 | 0.00 |
March | 3634.70 | 2041.23 | 3601.42 | 1920.60 | 1680.82 | 0.00 | 0.00 |
April | 4059.47 | 1745.31 | 3802.42 | 1650.99 | 2151.43 | 0.00 | 0.00 |
May | 3745.59 | 1454.45 | 3476.82 | 1035.78 | 2441.04 | 0.00 | 0.00 |
June | 3490.71 | 1168.12 | 3180.95 | 854.05 | 2326.91 | 0.00 | 0.00 |
July | 4209.92 | 1065.33 | 3468.97 | 1270.52 | 2198.45 | 0.00 | 0.00 |
August | 4685.31 | 1034.64 | 3726.97 | 1737.95 | 1989.02 | 0.00 | 0.00 |
September | 4891.83 | 1411.68 | 4129.33 | 2280.35 | 1848.98 | 0.00 | 0.00 |
October | 4046.38 | 1799.11 | 3740.47 | 2309.47 | 1431.01 | 0.00 | 0.00 |
November | 2020.99 | 2135.93 | 2211.49 | 1267.37 | 944.12 | 0.00 | 0.00 |
December | 2166.86 | 2626.09 | 2313.86 | 1497.39 | 816.47 | 0.00 | 0.00 |
Annual Sum or Average | 3503.65 | 1778.08 | 3263.40 | 1596.19 | 1667.21 | 0.00 | 0.00 |
Minimum of Months | 1843.68 | 1034.64 | 2177.04 | 854.05 | 816.47 | 0.00 | 0.00 |
Maximum of Months | 4891.83 | 2626.09 | 4129.33 | 2309.47 | 2441.04 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 224.89 | 1833.46 | 556.73 | 164.17 | 392.56 | 0.00 | 0.00 |
February | 666.30 | 1631.72 | 998.18 | 375.14 | 623.04 | 0.00 | 0.00 |
March | 1114.71 | 1371.86 | 1398.70 | 472.10 | 926.60 | 0.00 | 0.00 |
April | 2037.28 | 1159.84 | 2127.98 | 813.61 | 1314.37 | 0.00 | 0.00 |
May | 2866.81 | 984.97 | 2738.21 | 1112.39 | 1625.82 | 0.00 | 0.00 |
June | 2813.56 | 790.29 | 2633.41 | 1022.47 | 1610.94 | 0.00 | 0.00 |
July | 3812.67 | 745.21 | 3253.22 | 1710.06 | 1543.16 | 0.00 | 0.00 |
August | 3205.90 | 720.88 | 2691.19 | 1374.20 | 1316.99 | 0.00 | 0.00 |
September | 2416.94 | 959.30 | 2191.56 | 1051.56 | 1140.00 | 0.00 | 0.00 |
October | 1108.65 | 1213.87 | 1247.66 | 508.36 | 739.30 | 0.00 | 0.00 |
November | 330.84 | 1490.37 | 621.33 | 175.24 | 446.09 | 0.00 | 0.00 |
December | 269.39 | 1870.77 | 522.35 | 179.00 | 343.35 | 0.00 | 0.00 |
Annual Sum or Average | 1746.05 | 1229.19 | 1752.95 | 749.37 | 1003.59 | 0.00 | 0.00 |
Minimum of Months | 224.89 | 720.88 | 522.35 | 164.17 | 343.35 | 0.00 | 0.00 |
Maximum of Months | 3812.67 | 1870.77 | 3253.22 | 1710.06 | 1625.82 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 11902236.38 | 0.930110E+10 | 0.131973E+10 | 0.00 | 0.131973E+10 | 0.00 | 0.00 |
February | 0.209609E+09 | 0.742388E+10 | 0.185481E+10 | 0.00 | 0.185481E+10 | 0.00 | 0.00 |
March | 0.945630E+09 | 0.671770E+10 | 0.302557E+10 | 0.00 | 0.302557E+10 | 0.00 | 0.00 |
April | 0.230389E+10 | 0.510224E+10 | 0.414337E+10 | 14697807.51 | 0.412868E+10 | 0.00 | 0.00 |
May | 0.410828E+10 | 0.404331E+10 | 0.550920E+10 | 0.163670E+09 | 0.534553E+10 | 0.00 | 0.00 |
June | 0.467345E+10 | 0.301924E+10 | 0.560592E+10 | 0.370191E+09 | 0.523573E+10 | 0.00 | 0.00 |
July | 0.522414E+10 | 0.280223E+10 | 0.550572E+10 | 0.431675E+09 | 0.507405E+10 | 0.00 | 0.00 |
August | 0.428331E+10 | 0.275654E+10 | 0.445692E+10 | 0.120484E+09 | 0.433644E+10 | 0.00 | 0.00 |
September | 0.233837E+10 | 0.400874E+10 | 0.335030E+10 | 987953.07 | 0.334931E+10 | 0.00 | 0.00 |
October | 0.824097E+09 | 0.588856E+10 | 0.237203E+10 | 0.00 | 0.237203E+10 | 0.00 | 0.00 |
November | 0.100477E+09 | 0.751106E+10 | 0.144595E+10 | 0.00 | 0.144595E+10 | 0.00 | 0.00 |
December | 2440636.39 | 0.960763E+10 | 0.112143E+10 | 0.00 | 0.112143E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.250256E+11 | 0.681822E+11 | 0.397110E+11 | 0.110171E+10 | 0.386093E+11 | 0.00 | 0.00 |
Minimum of Months | 2440636.39 | 0.275654E+10 | 0.112143E+10 | 0.00 | 0.112143E+10 | 0.00 | 0.00 |
Maximum of Months | 0.522414E+10 | 0.960763E+10 | 0.560592E+10 | 0.431675E+09 | 0.534553E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.412148E+09 | 0.574162E+10 | 0.141375E+10 | 0.358432E+09 | 0.105532E+10 | 0.00 | 0.00 |
February | 0.131982E+10 | 0.448014E+10 | 0.234305E+10 | 0.831598E+09 | 0.151145E+10 | 0.00 | 0.00 |
March | 0.293390E+10 | 0.408366E+10 | 0.387316E+10 | 0.140212E+10 | 0.247104E+10 | 0.00 | 0.00 |
April | 0.551652E+10 | 0.310454E+10 | 0.581038E+10 | 0.241430E+10 | 0.339608E+10 | 0.00 | 0.00 |
May | 0.643593E+10 | 0.264383E+10 | 0.638886E+10 | 0.222126E+10 | 0.416760E+10 | 0.00 | 0.00 |
June | 0.807495E+10 | 0.199571E+10 | 0.740456E+10 | 0.322178E+10 | 0.418278E+10 | 0.00 | 0.00 |
July | 0.813842E+10 | 0.178509E+10 | 0.712521E+10 | 0.319820E+10 | 0.392700E+10 | 0.00 | 0.00 |
August | 0.828393E+10 | 0.171688E+10 | 0.700309E+10 | 0.350334E+10 | 0.349974E+10 | 0.00 | 0.00 |
September | 0.522577E+10 | 0.249860E+10 | 0.501073E+10 | 0.231099E+10 | 0.269974E+10 | 0.00 | 0.00 |
October | 0.282823E+10 | 0.361086E+10 | 0.337485E+10 | 0.143400E+10 | 0.194086E+10 | 0.00 | 0.00 |
November | 0.721055E+09 | 0.455467E+10 | 0.160081E+10 | 0.451924E+09 | 0.114888E+10 | 0.00 | 0.00 |
December | 0.533878E+09 | 0.581836E+10 | 0.135679E+10 | 0.436790E+09 | 0.919998E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.504245E+11 | 0.420340E+11 | 0.527052E+11 | 0.217847E+11 | 0.309205E+11 | 0.00 | 0.00 |
Minimum of Months | 0.412148E+09 | 0.171688E+10 | 0.135679E+10 | 0.358432E+09 | 0.919998E+09 | 0.00 | 0.00 |
Maximum of Months | 0.828393E+10 | 0.581836E+10 | 0.740456E+10 | 0.350334E+10 | 0.418278E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.477795E+10 | 0.789450E+10 | 0.583099E+10 | 0.346247E+10 | 0.236852E+10 | 0.00 | 0.00 |
February | 0.766206E+10 | 0.643769E+10 | 0.809938E+10 | 0.501363E+10 | 0.308575E+10 | 0.00 | 0.00 |
March | 0.963428E+10 | 0.625991E+10 | 0.964608E+10 | 0.514415E+10 | 0.450193E+10 | 0.00 | 0.00 |
April | 0.104546E+11 | 0.508517E+10 | 0.985591E+10 | 0.427938E+10 | 0.557653E+10 | 0.00 | 0.00 |
May | 0.100353E+11 | 0.424407E+10 | 0.931236E+10 | 0.277425E+10 | 0.653811E+10 | 0.00 | 0.00 |
June | 0.907410E+10 | 0.327439E+10 | 0.824507E+10 | 0.221370E+10 | 0.603137E+10 | 0.00 | 0.00 |
July | 0.113291E+11 | 0.304873E+10 | 0.929132E+10 | 0.340298E+10 | 0.588835E+10 | 0.00 | 0.00 |
August | 0.126006E+11 | 0.294070E+10 | 0.998236E+10 | 0.465494E+10 | 0.532742E+10 | 0.00 | 0.00 |
September | 0.126758E+11 | 0.397589E+10 | 0.107033E+11 | 0.591070E+10 | 0.479257E+10 | 0.00 | 0.00 |
October | 0.107641E+11 | 0.549633E+10 | 0.100185E+11 | 0.618570E+10 | 0.383282E+10 | 0.00 | 0.00 |
November | 0.505296E+10 | 0.653871E+10 | 0.573221E+10 | 0.328504E+10 | 0.244717E+10 | 0.00 | 0.00 |
December | 0.562990E+10 | 0.826023E+10 | 0.619745E+10 | 0.401062E+10 | 0.218684E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.109691E+12 | 0.634563E+11 | 0.102915E+12 | 0.503375E+11 | 0.525774E+11 | 0.00 | 0.00 |
Minimum of Months | 0.477795E+10 | 0.294070E+10 | 0.573221E+10 | 0.221370E+10 | 0.218684E+10 | 0.00 | 0.00 |
Maximum of Months | 0.126758E+11 | 0.826023E+10 | 0.107033E+11 | 0.618570E+10 | 0.653811E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.519748E+09 | 0.613101E+10 | 0.149116E+10 | 0.439716E+09 | 0.105144E+10 | 0.00 | 0.00 |
February | 0.142834E+10 | 0.501888E+10 | 0.241480E+10 | 0.907552E+09 | 0.150725E+10 | 0.00 | 0.00 |
March | 0.272174E+10 | 0.477945E+10 | 0.374630E+10 | 0.126448E+10 | 0.248183E+10 | 0.00 | 0.00 |
April | 0.499506E+10 | 0.383845E+10 | 0.551574E+10 | 0.210888E+10 | 0.340686E+10 | 0.00 | 0.00 |
May | 0.758651E+10 | 0.301058E+10 | 0.733406E+10 | 0.297943E+10 | 0.435463E+10 | 0.00 | 0.00 |
June | 0.719363E+10 | 0.238893E+10 | 0.682582E+10 | 0.265024E+10 | 0.417558E+10 | 0.00 | 0.00 |
July | 0.101368E+11 | 0.231604E+10 | 0.871346E+10 | 0.458024E+10 | 0.413322E+10 | 0.00 | 0.00 |
August | 0.845681E+10 | 0.230509E+10 | 0.720811E+10 | 0.368067E+10 | 0.352744E+10 | 0.00 | 0.00 |
September | 0.615804E+10 | 0.288407E+10 | 0.568056E+10 | 0.272566E+10 | 0.295490E+10 | 0.00 | 0.00 |
October | 0.274817E+10 | 0.418589E+10 | 0.334176E+10 | 0.136161E+10 | 0.198015E+10 | 0.00 | 0.00 |
November | 0.693479E+09 | 0.528192E+10 | 0.161049E+10 | 0.454226E+09 | 0.115627E+10 | 0.00 | 0.00 |
December | 0.608204E+09 | 0.684407E+10 | 0.139906E+10 | 0.479423E+09 | 0.919638E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.532466E+11 | 0.489844E+11 | 0.552813E+11 | 0.236321E+11 | 0.316492E+11 | 0.00 | 0.00 |
Minimum of Months | 0.519748E+09 | 0.230509E+10 | 0.139906E+10 | 0.439716E+09 | 0.919638E+09 | 0.00 | 0.00 |
Maximum of Months | 0.101368E+11 | 0.684407E+10 | 0.871346E+10 | 0.458024E+10 | 0.435463E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 37012953.48 | 0.796121E+10 | 0.131973E+10 | 0.00 | 0.131973E+10 | 0.00 | 0.00 |
February | 0.322823E+09 | 0.641434E+10 | 0.185480E+10 | 0.00 | 0.185480E+10 | 0.00 | 0.00 |
March | 0.115605E+10 | 0.585705E+10 | 0.302556E+10 | 0.00 | 0.302556E+10 | 0.00 | 0.00 |
April | 0.252428E+10 | 0.450564E+10 | 0.414336E+10 | 14697755.32 | 0.412866E+10 | 0.00 | 0.00 |
May | 0.422566E+10 | 0.377241E+10 | 0.550918E+10 | 0.163670E+09 | 0.534551E+10 | 0.00 | 0.00 |
June | 0.476260E+10 | 0.282154E+10 | 0.560590E+10 | 0.370190E+09 | 0.523571E+10 | 0.00 | 0.00 |
July | 0.532558E+10 | 0.261552E+10 | 0.550570E+10 | 0.431673E+09 | 0.507403E+10 | 0.00 | 0.00 |
August | 0.438942E+10 | 0.257052E+10 | 0.445691E+10 | 0.120484E+09 | 0.433642E+10 | 0.00 | 0.00 |
September | 0.242956E+10 | 0.370404E+10 | 0.335029E+10 | 987949.56 | 0.334930E+10 | 0.00 | 0.00 |
October | 0.996833E+09 | 0.513999E+10 | 0.237202E+10 | 0.00 | 0.237202E+10 | 0.00 | 0.00 |
November | 0.175178E+09 | 0.631497E+10 | 0.144594E+10 | 0.00 | 0.144594E+10 | 0.00 | 0.00 |
December | 17248377.72 | 0.808206E+10 | 0.112143E+10 | 0.00 | 0.112143E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.263622E+11 | 0.597593E+11 | 0.397108E+11 | 0.110170E+10 | 0.386091E+11 | 0.00 | 0.00 |
Minimum of Months | 17248377.72 | 0.257052E+10 | 0.112143E+10 | 0.00 | 0.112143E+10 | 0.00 | 0.00 |
Maximum of Months | 0.532558E+10 | 0.808206E+10 | 0.560590E+10 | 0.431673E+09 | 0.534551E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.463319E+09 | 0.503985E+10 | 0.141374E+10 | 0.358431E+09 | 0.105531E+10 | 0.00 | 0.00 |
February | 0.141844E+10 | 0.403616E+10 | 0.234304E+10 | 0.831595E+09 | 0.151145E+10 | 0.00 | 0.00 |
March | 0.302328E+10 | 0.370911E+10 | 0.387314E+10 | 0.140211E+10 | 0.247103E+10 | 0.00 | 0.00 |
April | 0.556050E+10 | 0.287749E+10 | 0.581036E+10 | 0.241429E+10 | 0.339607E+10 | 0.00 | 0.00 |
May | 0.645121E+10 | 0.249672E+10 | 0.638883E+10 | 0.222125E+10 | 0.416758E+10 | 0.00 | 0.00 |
June | 0.804309E+10 | 0.190896E+10 | 0.740453E+10 | 0.322176E+10 | 0.418277E+10 | 0.00 | 0.00 |
July | 0.811043E+10 | 0.172811E+10 | 0.712518E+10 | 0.319819E+10 | 0.392699E+10 | 0.00 | 0.00 |
August | 0.823962E+10 | 0.170090E+10 | 0.700306E+10 | 0.350333E+10 | 0.349973E+10 | 0.00 | 0.00 |
September | 0.524498E+10 | 0.234725E+10 | 0.501071E+10 | 0.231098E+10 | 0.269973E+10 | 0.00 | 0.00 |
October | 0.290387E+10 | 0.326673E+10 | 0.337484E+10 | 0.143399E+10 | 0.194085E+10 | 0.00 | 0.00 |
November | 0.790470E+09 | 0.402372E+10 | 0.160080E+10 | 0.451922E+09 | 0.114888E+10 | 0.00 | 0.00 |
December | 0.586587E+09 | 0.516091E+10 | 0.135678E+10 | 0.436788E+09 | 0.919994E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.508358E+11 | 0.382959E+11 | 0.527050E+11 | 0.217846E+11 | 0.309204E+11 | 0.00 | 0.00 |
Minimum of Months | 0.463319E+09 | 0.170090E+10 | 0.135678E+10 | 0.358431E+09 | 0.919994E+09 | 0.00 | 0.00 |
Maximum of Months | 0.823962E+10 | 0.516091E+10 | 0.740453E+10 | 0.350333E+10 | 0.418277E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.483466E+10 | 0.733893E+10 | 0.583097E+10 | 0.346246E+10 | 0.236851E+10 | 0.00 | 0.00 |
February | 0.769900E+10 | 0.608944E+10 | 0.809935E+10 | 0.501361E+10 | 0.308574E+10 | 0.00 | 0.00 |
March | 0.963916E+10 | 0.588970E+10 | 0.964605E+10 | 0.514413E+10 | 0.450192E+10 | 0.00 | 0.00 |
April | 0.104518E+11 | 0.479418E+10 | 0.985587E+10 | 0.427936E+10 | 0.557651E+10 | 0.00 | 0.00 |
May | 0.999274E+10 | 0.408636E+10 | 0.931233E+10 | 0.277424E+10 | 0.653809E+10 | 0.00 | 0.00 |
June | 0.905489E+10 | 0.312228E+10 | 0.824504E+10 | 0.221369E+10 | 0.603135E+10 | 0.00 | 0.00 |
July | 0.112988E+11 | 0.292175E+10 | 0.929129E+10 | 0.340296E+10 | 0.588832E+10 | 0.00 | 0.00 |
August | 0.125610E+11 | 0.285441E+10 | 0.998232E+10 | 0.465492E+10 | 0.532740E+10 | 0.00 | 0.00 |
September | 0.126336E+11 | 0.385231E+10 | 0.107032E+11 | 0.591068E+10 | 0.479255E+10 | 0.00 | 0.00 |
October | 0.107356E+11 | 0.521285E+10 | 0.100185E+11 | 0.618568E+10 | 0.383281E+10 | 0.00 | 0.00 |
November | 0.511834E+10 | 0.605701E+10 | 0.573219E+10 | 0.328503E+10 | 0.244716E+10 | 0.00 | 0.00 |
December | 0.569556E+10 | 0.763177E+10 | 0.619743E+10 | 0.401060E+10 | 0.218683E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.109715E+12 | 0.598510E+11 | 0.102915E+12 | 0.503374E+11 | 0.525772E+11 | 0.00 | 0.00 |
Minimum of Months | 0.483466E+10 | 0.285441E+10 | 0.573219E+10 | 0.221369E+10 | 0.218683E+10 | 0.00 | 0.00 |
Maximum of Months | 0.126336E+11 | 0.763177E+10 | 0.107032E+11 | 0.618568E+10 | 0.653809E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.578916E+09 | 0.521666E+10 | 0.149115E+10 | 0.439714E+09 | 0.105144E+10 | 0.00 | 0.00 |
February | 0.156973E+10 | 0.420830E+10 | 0.241479E+10 | 0.907548E+09 | 0.150725E+10 | 0.00 | 0.00 |
March | 0.293614E+10 | 0.391962E+10 | 0.374629E+10 | 0.126447E+10 | 0.248182E+10 | 0.00 | 0.00 |
April | 0.523966E+10 | 0.316734E+10 | 0.551572E+10 | 0.210887E+10 | 0.340685E+10 | 0.00 | 0.00 |
May | 0.766014E+10 | 0.275276E+10 | 0.733403E+10 | 0.297942E+10 | 0.435461E+10 | 0.00 | 0.00 |
June | 0.730199E+10 | 0.210826E+10 | 0.682580E+10 | 0.265023E+10 | 0.417557E+10 | 0.00 | 0.00 |
July | 0.102366E+11 | 0.204089E+10 | 0.871342E+10 | 0.458022E+10 | 0.413320E+10 | 0.00 | 0.00 |
August | 0.859652E+10 | 0.198400E+10 | 0.720808E+10 | 0.368066E+10 | 0.352743E+10 | 0.00 | 0.00 |
September | 0.623805E+10 | 0.260443E+10 | 0.568053E+10 | 0.272564E+10 | 0.295489E+10 | 0.00 | 0.00 |
October | 0.291446E+10 | 0.348932E+10 | 0.334174E+10 | 0.136160E+10 | 0.198014E+10 | 0.00 | 0.00 |
November | 0.820906E+09 | 0.416816E+10 | 0.161048E+10 | 0.454224E+09 | 0.115626E+10 | 0.00 | 0.00 |
December | 0.698356E+09 | 0.537016E+10 | 0.139905E+10 | 0.479421E+09 | 0.919634E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.547915E+11 | 0.410299E+11 | 0.552811E+11 | 0.236320E+11 | 0.316491E+11 | 0.00 | 0.00 |
Minimum of Months | 0.578916E+09 | 0.198400E+10 | 0.139905E+10 | 0.439714E+09 | 0.919634E+09 | 0.00 | 0.00 |
Maximum of Months | 0.102366E+11 | 0.537016E+10 | 0.871342E+10 | 0.458022E+10 | 0.435461E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 58651596.34 | 0.746130E+10 | 0.131973E+10 | 0.00 | 0.131973E+10 | 0.00 | 0.00 |
February | 0.385299E+09 | 0.594005E+10 | 0.185480E+10 | 0.00 | 0.185480E+10 | 0.00 | 0.00 |
March | 0.127842E+10 | 0.538488E+10 | 0.302556E+10 | 0.00 | 0.302556E+10 | 0.00 | 0.00 |
April | 0.263972E+10 | 0.420864E+10 | 0.414336E+10 | 14697755.32 | 0.412866E+10 | 0.00 | 0.00 |
May | 0.431271E+10 | 0.357732E+10 | 0.550918E+10 | 0.163670E+09 | 0.534551E+10 | 0.00 | 0.00 |
June | 0.478256E+10 | 0.273203E+10 | 0.560590E+10 | 0.370190E+09 | 0.523571E+10 | 0.00 | 0.00 |
July | 0.532086E+10 | 0.254761E+10 | 0.550570E+10 | 0.431673E+09 | 0.507403E+10 | 0.00 | 0.00 |
August | 0.440215E+10 | 0.248779E+10 | 0.445691E+10 | 0.120484E+09 | 0.433642E+10 | 0.00 | 0.00 |
September | 0.250399E+10 | 0.347510E+10 | 0.335029E+10 | 987949.56 | 0.334930E+10 | 0.00 | 0.00 |
October | 0.112494E+10 | 0.466673E+10 | 0.237202E+10 | 0.00 | 0.237202E+10 | 0.00 | 0.00 |
November | 0.231338E+09 | 0.569818E+10 | 0.144594E+10 | 0.00 | 0.144594E+10 | 0.00 | 0.00 |
December | 38393613.46 | 0.741330E+10 | 0.112143E+10 | 0.00 | 0.112143E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.270790E+11 | 0.555929E+11 | 0.397108E+11 | 0.110170E+10 | 0.386091E+11 | 0.00 | 0.00 |
Minimum of Months | 38393613.46 | 0.248779E+10 | 0.112143E+10 | 0.00 | 0.112143E+10 | 0.00 | 0.00 |
Maximum of Months | 0.532086E+10 | 0.746130E+10 | 0.560590E+10 | 0.431673E+09 | 0.534551E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.497095E+09 | 0.473326E+10 | 0.141374E+10 | 0.358431E+09 | 0.105531E+10 | 0.00 | 0.00 |
February | 0.148948E+10 | 0.374933E+10 | 0.234304E+10 | 0.831595E+09 | 0.151145E+10 | 0.00 | 0.00 |
March | 0.310324E+10 | 0.344907E+10 | 0.387314E+10 | 0.140211E+10 | 0.247103E+10 | 0.00 | 0.00 |
April | 0.561825E+10 | 0.271974E+10 | 0.581036E+10 | 0.241429E+10 | 0.339607E+10 | 0.00 | 0.00 |
May | 0.648132E+10 | 0.239202E+10 | 0.638883E+10 | 0.222125E+10 | 0.416758E+10 | 0.00 | 0.00 |
June | 0.802996E+10 | 0.186498E+10 | 0.740453E+10 | 0.322176E+10 | 0.418277E+10 | 0.00 | 0.00 |
July | 0.809263E+10 | 0.169895E+10 | 0.712518E+10 | 0.319819E+10 | 0.392699E+10 | 0.00 | 0.00 |
August | 0.822992E+10 | 0.166289E+10 | 0.700306E+10 | 0.350333E+10 | 0.349973E+10 | 0.00 | 0.00 |
September | 0.527622E+10 | 0.223467E+10 | 0.501071E+10 | 0.231098E+10 | 0.269973E+10 | 0.00 | 0.00 |
October | 0.298106E+10 | 0.301506E+10 | 0.337484E+10 | 0.143399E+10 | 0.194085E+10 | 0.00 | 0.00 |
November | 0.846666E+09 | 0.367079E+10 | 0.160080E+10 | 0.451922E+09 | 0.114888E+10 | 0.00 | 0.00 |
December | 0.630639E+09 | 0.475932E+10 | 0.135678E+10 | 0.436788E+09 | 0.919994E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.512765E+11 | 0.359501E+11 | 0.527050E+11 | 0.217846E+11 | 0.309204E+11 | 0.00 | 0.00 |
Minimum of Months | 0.497095E+09 | 0.166289E+10 | 0.135678E+10 | 0.358431E+09 | 0.919994E+09 | 0.00 | 0.00 |
Maximum of Months | 0.822992E+10 | 0.475932E+10 | 0.740453E+10 | 0.350333E+10 | 0.418277E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.493810E+10 | 0.684378E+10 | 0.583097E+10 | 0.346246E+10 | 0.236851E+10 | 0.00 | 0.00 |
February | 0.783116E+10 | 0.564275E+10 | 0.809935E+10 | 0.501361E+10 | 0.308574E+10 | 0.00 | 0.00 |
March | 0.973517E+10 | 0.546723E+10 | 0.964605E+10 | 0.514413E+10 | 0.450192E+10 | 0.00 | 0.00 |
April | 0.105222E+11 | 0.452384E+10 | 0.985587E+10 | 0.427936E+10 | 0.557651E+10 | 0.00 | 0.00 |
May | 0.100322E+11 | 0.389560E+10 | 0.931233E+10 | 0.277424E+10 | 0.653809E+10 | 0.00 | 0.00 |
June | 0.904793E+10 | 0.302776E+10 | 0.824504E+10 | 0.221369E+10 | 0.603135E+10 | 0.00 | 0.00 |
July | 0.112759E+11 | 0.285338E+10 | 0.929129E+10 | 0.340296E+10 | 0.588832E+10 | 0.00 | 0.00 |
August | 0.125491E+11 | 0.277117E+10 | 0.998232E+10 | 0.465492E+10 | 0.532740E+10 | 0.00 | 0.00 |
September | 0.126796E+11 | 0.365908E+10 | 0.107032E+11 | 0.591068E+10 | 0.479255E+10 | 0.00 | 0.00 |
October | 0.108378E+11 | 0.481875E+10 | 0.100185E+11 | 0.618568E+10 | 0.383281E+10 | 0.00 | 0.00 |
November | 0.523842E+10 | 0.553634E+10 | 0.573219E+10 | 0.328503E+10 | 0.244716E+10 | 0.00 | 0.00 |
December | 0.580371E+10 | 0.703372E+10 | 0.619743E+10 | 0.401060E+10 | 0.218683E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.110491E+12 | 0.560734E+11 | 0.102915E+12 | 0.503374E+11 | 0.525772E+11 | 0.00 | 0.00 |
Minimum of Months | 0.493810E+10 | 0.277117E+10 | 0.573219E+10 | 0.221369E+10 | 0.218683E+10 | 0.00 | 0.00 |
Maximum of Months | 0.126796E+11 | 0.703372E+10 | 0.107032E+11 | 0.618568E+10 | 0.653809E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.602356E+09 | 0.491075E+10 | 0.149115E+10 | 0.439714E+09 | 0.105144E+10 | 0.00 | 0.00 |
February | 0.161192E+10 | 0.394746E+10 | 0.241479E+10 | 0.907548E+09 | 0.150725E+10 | 0.00 | 0.00 |
March | 0.298564E+10 | 0.367438E+10 | 0.374629E+10 | 0.126447E+10 | 0.248182E+10 | 0.00 | 0.00 |
April | 0.528063E+10 | 0.300631E+10 | 0.551572E+10 | 0.210887E+10 | 0.340685E+10 | 0.00 | 0.00 |
May | 0.767847E+10 | 0.263815E+10 | 0.733403E+10 | 0.297942E+10 | 0.435461E+10 | 0.00 | 0.00 |
June | 0.729275E+10 | 0.204843E+10 | 0.682580E+10 | 0.265023E+10 | 0.417557E+10 | 0.00 | 0.00 |
July | 0.102118E+11 | 0.199597E+10 | 0.871342E+10 | 0.458022E+10 | 0.413320E+10 | 0.00 | 0.00 |
August | 0.858669E+10 | 0.193080E+10 | 0.720808E+10 | 0.368066E+10 | 0.352743E+10 | 0.00 | 0.00 |
September | 0.626472E+10 | 0.248652E+10 | 0.568053E+10 | 0.272564E+10 | 0.295489E+10 | 0.00 | 0.00 |
October | 0.296941E+10 | 0.325124E+10 | 0.334174E+10 | 0.136160E+10 | 0.198014E+10 | 0.00 | 0.00 |
November | 0.857544E+09 | 0.386303E+10 | 0.161048E+10 | 0.454224E+09 | 0.115626E+10 | 0.00 | 0.00 |
December | 0.721540E+09 | 0.501068E+10 | 0.139905E+10 | 0.479421E+09 | 0.919634E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.550635E+11 | 0.387637E+11 | 0.552811E+11 | 0.236320E+11 | 0.316491E+11 | 0.00 | 0.00 |
Minimum of Months | 0.602356E+09 | 0.193080E+10 | 0.139905E+10 | 0.439714E+09 | 0.919634E+09 | 0.00 | 0.00 |
Maximum of Months | 0.102118E+11 | 0.501068E+10 | 0.871342E+10 | 0.458022E+10 | 0.435461E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 4.50 | 3.10 | 1.22 | 3.91 | -4.2 | 29.50 | 44.23 | 0.00 |
February | 5.82 | 4.07 | 1.77 | 3.94 | -3.8 | 43.80 | 82.64 | 0.00 |
March | 8.33 | 5.86 | 2.94 | 3.85 | -1.4 | 65.55 | 100.60 | 0.02 |
April | 10.85 | 8.04 | 5.25 | 4.23 | 1.22 | 89.73 | 150.02 | 0.00 |
May | 12.97 | 10.02 | 7.49 | 3.85 | 3.75 | 114.98 | 168.60 | 0.00 |
June | 15.59 | 11.80 | 8.88 | 4.02 | 5.93 | 107.53 | 199.74 | 0.01 |
July | 17.66 | 13.41 | 10.38 | 3.76 | 8.02 | 92.25 | 247.81 | 0.00 |
August | 18.80 | 14.57 | 11.86 | 3.84 | 8.90 | 79.20 | 215.47 | 0.01 |
September | 15.09 | 12.55 | 10.74 | 2.23 | 5.47 | 68.06 | 162.11 | 0.01 |
October | 11.43 | 9.19 | 7.19 | 4.02 | 2.10 | 48.18 | 106.36 | 0.04 |
November | 8.07 | 6.72 | 5.29 | 3.86 | 0.13 | 33.26 | 46.10 | 0.00 |
December | 5.42 | 4.09 | 2.46 | 3.51 | -3.8 | 24.03 | 50.49 | 0.04 |
Annual Sum or Average | 11.24 | 8.64 | 6.31 | 3.75 | 1.89 | 66.43 | 131.49 | 0.01 |
Minimum of Months | 4.50 | 3.10 | 1.22 | 2.23 | -4.2 | 24.03 | 44.23 | 0.00 |
Maximum of Months | 18.80 | 14.57 | 11.86 | 4.23 | 8.90 | 114.98 | 247.81 | 0.04 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 14.40 | 11-JAN-14:20 | 10.49 | 7.20 | 8.40 | 3.89 | 99.17 | 130.33 |
February | 20.00 | 27-FEB-14:00 | 12.17 | 5.60 | 2.60 | 5.54 | 87.00 | 691.00 |
March | 20.60 | 18-MAR-15:00 | 10.43 | 0.00 | 6.20 | 6.55 | 111.50 | 465.50 |
April | 27.20 | 27-APR-15:09 | 17.22 | 11.02 | 4.10 | 12.63 | 151.33 | 598.33 |
May | 25.00 | 05-MAY-15:00 | 17.36 | 12.80 | 2.60 | 18.99 | 208.50 | 29.50 |
June | 26.70 | 28-JUN-16:00 | 16.74 | 10.60 | 3.10 | 11.84 | 131.50 | 527.00 |
July | 30.60 | 24-JUL-14:00 | 18.78 | 12.20 | 3.10 | 20.75 | 267.00 | 383.50 |
August | 31.80 | 10-AUG-16:00 | 18.70 | 11.10 | 2.60 | 16.85 | 50.50 | 750.50 |
September | 25.00 | 14-SEP-16:00 | 16.69 | 11.70 | 3.10 | 13.54 | 100.50 | 235.00 |
October | 21.70 | 04-OCT-14:00 | 11.49 | 1.70 | 5.20 | 4.92 | 56.50 | 783.50 |
November | 21.10 | 04-NOV-13:00 | 15.94 | 12.80 | 0.00 | 6.95 | 52.50 | 729.00 |
December | 13.30 | 14-DEC-11:00 | 8.44 | 3.60 | 13.90 | 5.33 | 127.50 | 85.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 13.30 | 8.44 | 0.00 | 0.00 | 3.89 | 50.50 | 29.50 | |
Maximum of Months | 31.80 | 18.78 | 12.80 | 13.90 | 20.75 | 267.00 | 783.50 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -3.9 | 07-JAN-07:00 | -3.9 | -3.9 | 2.10 | -14.4 | 0.00 | 0.00 |
February | -5.6 | 19-FEB-05:10 | -6.1 | -7.3 | 3.77 | -22.8 | 0.00 | 0.00 |
March | -0.6 | 01-MAR-06:00 | -2.0 | -3.9 | 1.50 | -17.3 | 16.50 | 102.00 |
April | 1.70 | 19-APR-04:00 | 1.21 | 0.60 | 3.10 | -11.9 | 0.00 | 0.00 |
May | 4.40 | 11-MAY-02:00 | 3.92 | 3.30 | 3.10 | -10.9 | 0.00 | 0.00 |
June | 8.30 | 15-JUN-02:00 | 7.50 | 6.70 | 3.10 | -3.2 | 0.00 | 0.00 |
July | 11.10 | 03-JUL-03:00 | 8.19 | 5.00 | 2.60 | 5.54 | 0.00 | 0.00 |
August | 11.00 | 06-AUG-04:00 | 10.57 | 10.20 | 2.60 | -3.2 | 11.00 | 135.50 |
September | 7.20 | 27-SEP-04:49 | 6.72 | 6.20 | 0.25 | -4.0 | 0.00 | 0.00 |
October | 5.60 | 13-OCT-04:00 | 4.51 | 3.30 | 2.10 | -8.5 | 0.00 | 0.00 |
November | 0.00 | 11-NOV-06:00 | -0.2 | -0.6 | 2.10 | -16.0 | 0.00 | 0.00 |
December | -1.7 | 26-DEC-06:00 | -1.7 | -1.7 | 2.10 | -15.7 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -5.6 | -6.1 | -7.3 | 0.25 | -22.8 | 0.00 | 0.00 | |
Maximum of Months | 11.10 | 10.57 | 10.20 | 3.77 | 5.54 | 16.50 | 135.50 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 10.49 | 11-JAN-13:00 | 14.40 | 7.20 | 8.20 | 2.85 | 105.50 | 249.00 |
February | 12.42 | 27-FEB-15:00 | 19.40 | 6.70 | 2.60 | 6.35 | 88.00 | 342.50 |
March | 12.45 | 09-MAR-11:00 | 17.20 | 8.90 | 2.10 | 12.41 | 178.00 | 40.00 |
April | 17.29 | 27-APR-14:00 | 27.20 | 11.10 | 4.10 | 12.41 | 147.50 | 646.00 |
May | 17.58 | 06-MAY-12:00 | 23.90 | 13.90 | 5.20 | 15.57 | 365.50 | 282.50 |
June | 16.74 | 28-JUN-16:00 | 26.70 | 10.60 | 3.10 | 11.84 | 131.50 | 527.00 |
July | 19.18 | 31-JUL-15:00 | 28.90 | 13.90 | 4.10 | 14.65 | 45.00 | 848.50 |
August | 20.13 | 29-AUG-12:00 | 28.90 | 15.70 | 2.60 | 17.39 | 136.50 | 655.00 |
September | 17.97 | 23-SEP-13:00 | 23.30 | 15.00 | 2.10 | 9.72 | 148.00 | 670.50 |
October | 15.15 | 01-OCT-11:00 | 17.20 | 13.90 | 4.60 | 13.73 | 236.50 | 63.50 |
November | 16.05 | 04-NOV-12:00 | 20.60 | 13.30 | 0.00 | 7.95 | 62.00 | 746.50 |
December | 10.71 | 16-DEC-11:00 | 11.70 | 10.00 | 6.70 | 7.35 | 89.50 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 10.49 | 11.70 | 6.70 | 0.00 | 2.85 | 45.00 | 0.00 | |
Maximum of Months | 20.13 | 28.90 | 15.70 | 8.20 | 17.39 | 365.50 | 848.50 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 10.00 | 11-JAN-21:00 | 11.10 | 10.49 | 4.60 | 6.75 | 0.00 | 0.00 |
February | 11.70 | 24-FEB-00:00 | 12.80 | 12.15 | 4.10 | 8.74 | 0.00 | 0.00 |
March | 11.70 | 09-MAR-16:00 | 12.80 | 12.15 | 2.10 | 8.74 | 37.50 | 0.00 |
April | 12.80 | 28-APR-12:00 | 16.70 | 14.35 | 4.10 | 8.35 | 265.50 | 596.00 |
May | 13.90 | 05-MAY-16:00 | 22.80 | 17.10 | 2.60 | 19.17 | 111.50 | 27.50 |
June | 13.90 | 12-JUN-12:00 | 16.70 | 15.00 | 3.60 | 13.16 | 263.50 | 0.00 |
July | 15.00 | 11-JUL-09:20 | 16.13 | 15.49 | 4.60 | 12.91 | 204.17 | 28.17 |
August | 16.40 | 30-AUG-07:00 | 17.40 | 16.77 | 5.20 | 12.41 | 168.50 | 34.50 |
September | 15.00 | 14-SEP-11:20 | 20.37 | 16.93 | 2.10 | 6.89 | 152.83 | 748.17 |
October | 13.90 | 01-OCT-10:00 | 16.70 | 15.01 | 4.10 | 13.16 | 184.50 | 0.00 |
November | 13.90 | 03-NOV-19:00 | 15.00 | 14.31 | 4.60 | 11.46 | 0.00 | 0.00 |
December | 10.00 | 16-DEC-10:00 | 11.10 | 10.48 | 7.70 | 6.75 | 81.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 10.00 | 11.10 | 10.48 | 2.10 | 6.75 | 0.00 | 0.00 | |
Maximum of Months | 16.40 | 22.80 | 17.10 | 7.70 | 19.17 | 265.50 | 748.17 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 11.48 | 8.35 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 11.14 | 14.81 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 11.69 | 23.26 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 12.99 | 36.00 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 14.72 | 45.46 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 16.40 | 49.26 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 17.58 | 51.50 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 17.95 | 42.11 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 17.39 | 30.76 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 16.06 | 18.91 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 14.32 | 9.65 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 12.65 | 7.39 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 14.55 | 28.19 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 11.14 | 7.39 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 17.95 | 51.50 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.388271E+11 | -0.378000E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.102714E+10 | 58.98 | 0.00 | 0.00 |
February | 0.355151E+11 | -0.345882E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -926908821.3 | 58.98 | 0.00 | 0.00 |
March | 0.412550E+11 | -0.402291E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.102589E+10 | 58.97 | 0.00 | 0.00 |
April | 0.364579E+11 | -0.354697E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -988259025.3 | 58.98 | 0.00 | 0.00 |
May | 0.374880E+11 | -0.364651E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.102287E+10 | 58.98 | 0.00 | 0.00 |
June | 0.357733E+11 | -0.347836E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -989657951.5 | 58.97 | 0.00 | 0.00 |
July | 0.331678E+11 | -0.321503E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.101744E+10 | 58.97 | 0.00 | 0.00 |
August | 0.359247E+11 | -0.349028E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.102192E+10 | 58.98 | 0.00 | 0.00 |
September | 0.330755E+11 | -0.320884E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -987142564.1 | 58.97 | 0.00 | 0.00 |
October | 0.351804E+11 | -0.341605E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.101981E+10 | 58.98 | 0.00 | 0.00 |
November | 0.358503E+11 | -0.348626E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -987627478.6 | 58.98 | 0.00 | 0.00 |
December | 0.370065E+11 | -0.359842E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.102226E+10 | 58.97 | 0.00 | 0.00 |
Annual Sum or Average | 0.435522E+12 | -0.423485E+12 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.120369E+11 | 58.98 | 0.00 | 0.00 |
Minimum of Months | 0.330755E+11 | -0.402291E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -0.102714E+10 | 58.97 | 0.00 | 0.00 |
Maximum of Months | 0.412550E+11 | -0.320884E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -926908821.3 | 58.98 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_1_DAYLCTRL
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 237.83 | 0.51 | 0.48 | 01-JAN-09:50 | 3071.03 | 32.88 | 225.17 | 223.83 | 2421.56 | 33.99 | 227.83 | 196.33 |
February | 259.50 | 0.51 | 0.48 | 01-FEB-08:39 | 5222.97 | 33.84 | 248.00 | 247.17 | 2265.91 | 29.58 | 228.50 | 223.67 |
March | 247.00 | 0.51 | 0.48 | 01-MAR-07:40 | 8649.78 | 33.83 | 211.17 | 317.17 | 1849.35 | 23.07 | 219.17 | 276.50 |
April | 379.50 | 0.51 | 0.48 | 01-APR-07:10 | 2470.90 | 20.70 | 196.17 | 349.67 | 1350.53 | 22.13 | 264.83 | 315.83 |
May | 427.83 | 0.51 | 0.48 | 01-MAY-07:19 | 2271.28 | 20.56 | 188.33 | 391.33 | 1225.72 | 21.95 | 298.50 | 352.67 |
June | 375.17 | 0.52 | 0.48 | 01-JUN-06:10 | 1993.48 | 20.10 | 156.67 | 401.83 | 1132.65 | 21.52 | 291.50 | 356.33 |
July | 471.00 | 0.54 | 0.48 | 01-JUL-05:30 | 1772.20 | 18.96 | 137.33 | 403.17 | 1028.31 | 20.36 | 214.33 | 353.17 |
August | 366.67 | 0.52 | 0.48 | 01-AUG-06:10 | 2093.82 | 19.99 | 140.67 | 380.33 | 1237.68 | 21.40 | 228.67 | 338.00 |
September | 301.17 | 0.50 | 0.48 | 01-SEP-07:40 | 3353.96 | 22.70 | 163.50 | 323.50 | 1628.08 | 22.88 | 239.83 | 294.83 |
October | 245.33 | 0.51 | 0.48 | 01-OCT-07:49 | 8029.11 | 35.27 | 227.17 | 288.33 | 2158.55 | 24.24 | 205.00 | 262.00 |
November | 242.67 | 0.51 | 0.48 | 01-NOV-08:09 | 3422.71 | 32.43 | 228.50 | 228.17 | 2718.82 | 33.61 | 232.17 | 200.50 |
December | 160.33 | 0.51 | 0.48 | 01-DEC-09:39 | 4122.38 | 36.09 | 149.67 | 211.67 | 3465.17 | 37.36 | 151.83 | 176.00 |
Annual Sum or Average | 3714.00 | 0.52 | 3487.74 | 25.46 | 2272.33 | 3766.17 | 1684.43 | 24.70 | 2802.17 | 3345.83 | ||
Minimum of Months | 160.33 | 0.50 | 0.48 | 1772.20 | 18.96 | 137.33 | 211.67 | 1028.31 | 20.36 | 151.83 | 176.00 | |
Maximum of Months | 471.00 | 0.54 | 0.48 | 8649.78 | 36.09 | 248.00 | 403.17 | 3465.17 | 37.36 | 298.50 | 356.33 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_2_DAYLCTRL
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 237.83 | 0.54 | 0.48 | 01-JAN-09:00 | 1039.85 | 21.63 | 77.67 | 208.50 | 637.88 | 22.97 | 103.50 | 144.33 |
February | 259.50 | 0.52 | 0.48 | 01-FEB-08:30 | 1697.96 | 23.59 | 105.17 | 234.00 | 883.89 | 23.73 | 148.67 | 193.33 |
March | 247.00 | 0.51 | 0.48 | 01-MAR-07:30 | 3056.22 | 25.97 | 124.83 | 310.67 | 1334.94 | 24.86 | 176.33 | 265.83 |
April | 379.50 | 0.51 | 0.48 | 01-APR-06:19 | 3189.91 | 24.68 | 165.17 | 352.33 | 1774.02 | 25.06 | 247.17 | 318.00 |
May | 427.83 | 0.51 | 0.48 | 01-MAY-06:00 | 3279.36 | 23.98 | 176.67 | 397.00 | 1429.64 | 23.76 | 274.17 | 361.17 |
June | 375.17 | 0.51 | 0.48 | 01-JUN-05:10 | 3448.16 | 23.87 | 114.33 | 410.33 | 1887.14 | 24.33 | 245.17 | 369.33 |
July | 471.00 | 0.52 | 0.48 | 01-JUL-04:00 | 3240.66 | 24.10 | 175.83 | 417.33 | 1464.88 | 23.68 | 245.17 | 384.00 |
August | 366.67 | 0.51 | 0.48 | 01-AUG-05:30 | 3771.54 | 24.77 | 135.33 | 385.50 | 1640.30 | 24.07 | 201.83 | 350.83 |
September | 301.17 | 0.50 | 0.48 | 01-SEP-07:40 | 3095.40 | 24.53 | 111.17 | 327.00 | 1716.51 | 24.88 | 185.67 | 294.33 |
October | 245.33 | 0.53 | 0.48 | 01-OCT-07:40 | 2803.37 | 25.60 | 116.50 | 278.50 | 1225.86 | 24.42 | 152.33 | 237.50 |
November | 242.67 | 0.53 | 0.48 | 01-NOV-08:09 | 1290.80 | 22.86 | 92.17 | 214.00 | 669.44 | 23.02 | 107.50 | 160.67 |
December | 160.33 | 0.54 | 0.48 | 01-DEC-09:39 | 1218.69 | 23.82 | 67.33 | 193.50 | 653.29 | 23.76 | 78.67 | 123.50 |
Annual Sum or Average | 3714.00 | 0.52 | 2796.96 | 24.16 | 1462.17 | 3728.67 | 1367.79 | 24.08 | 2166.17 | 3202.83 | ||
Minimum of Months | 160.33 | 0.50 | 0.48 | 1039.85 | 21.63 | 67.33 | 193.50 | 637.88 | 22.97 | 78.67 | 123.50 | |
Maximum of Months | 471.00 | 0.54 | 0.48 | 3771.54 | 25.97 | 176.67 | 417.33 | 1887.14 | 25.06 | 274.17 | 384.00 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_3_DAYLCTRL
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 237.83 | 0.58 | 0.48 | 02-JAN-11:20 | 564.27 | 16.55 | 0.00 | 189.50 | 306.64 | 17.89 | 0.00 | 77.33 |
February | 259.50 | 0.54 | 0.48 | 01-FEB-09:30 | 717.77 | 17.70 | 0.00 | 225.00 | 404.86 | 19.13 | 10.17 | 151.33 |
March | 247.00 | 0.52 | 0.48 | 01-MAR-08:20 | 970.19 | 19.04 | 0.83 | 306.17 | 573.31 | 20.51 | 97.50 | 237.67 |
April | 379.50 | 0.51 | 0.48 | 01-APR-07:10 | 1137.23 | 19.70 | 11.17 | 353.00 | 657.25 | 21.04 | 214.17 | 313.83 |
May | 427.83 | 0.50 | 0.48 | 01-MAY-07:19 | 1396.07 | 21.75 | 121.33 | 403.67 | 799.10 | 22.48 | 304.67 | 373.17 |
June | 375.17 | 0.51 | 0.48 | 01-JUN-05:30 | 1483.98 | 22.78 | 155.00 | 418.67 | 842.02 | 22.79 | 310.67 | 386.50 |
July | 471.00 | 0.52 | 0.48 | 01-JUL-04:00 | 1252.31 | 21.96 | 153.33 | 428.67 | 719.07 | 21.91 | 260.00 | 386.83 |
August | 366.67 | 0.51 | 0.48 | 01-AUG-05:00 | 1087.21 | 19.72 | 35.67 | 392.67 | 677.29 | 21.08 | 186.33 | 359.00 |
September | 301.17 | 0.51 | 0.48 | 01-SEP-07:40 | 1056.93 | 19.80 | 6.17 | 319.50 | 639.57 | 21.23 | 149.33 | 273.33 |
October | 245.33 | 0.54 | 0.48 | 01-OCT-08:20 | 787.56 | 18.15 | 0.17 | 269.50 | 475.54 | 19.68 | 43.00 | 197.00 |
November | 242.67 | 0.56 | 0.48 | 01-NOV-10:30 | 608.03 | 16.85 | 0.00 | 202.00 | 330.48 | 18.15 | 1.17 | 94.50 |
December | 160.33 | 0.59 | 0.48 | 01-DEC-10:09 | 529.18 | 16.56 | 0.00 | 167.67 | 307.80 | 18.16 | 0.00 | 57.17 |
Annual Sum or Average | 3714.00 | 0.53 | 1044.19 | 19.73 | 483.67 | 3676.00 | 606.53 | 20.74 | 1577.00 | 2907.67 | ||
Minimum of Months | 160.33 | 0.50 | 0.48 | 529.18 | 16.55 | 0.00 | 167.67 | 306.64 | 17.89 | 0.00 | 57.17 | |
Maximum of Months | 471.00 | 0.59 | 0.48 | 1483.98 | 22.78 | 155.00 | 428.67 | 842.02 | 22.79 | 310.67 | 386.83 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_4_DAYLCTRL
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 237.83 | 0.54 | 0.48 | 01-JAN-13:09 | 1183.88 | 22.97 | 93.67 | 208.33 | 629.09 | 23.10 | 104.83 | 152.67 |
February | 259.50 | 0.52 | 0.48 | 01-FEB-09:30 | 1681.07 | 23.55 | 103.83 | 236.50 | 861.69 | 23.63 | 139.67 | 195.17 |
March | 247.00 | 0.51 | 0.48 | 01-MAR-08:20 | 2672.39 | 24.76 | 118.50 | 313.00 | 1425.33 | 24.96 | 175.50 | 264.33 |
April | 379.50 | 0.51 | 0.48 | 01-APR-07:40 | 3194.23 | 23.56 | 149.83 | 351.00 | 1392.34 | 23.01 | 225.33 | 318.33 |
May | 427.83 | 0.51 | 0.48 | 01-MAY-07:30 | 3312.53 | 21.12 | 102.17 | 396.50 | 1770.74 | 21.33 | 250.00 | 365.50 |
June | 375.17 | 0.51 | 0.48 | 01-JUN-06:10 | 3379.75 | 20.69 | 62.33 | 409.17 | 1523.41 | 21.07 | 221.00 | 371.50 |
July | 471.00 | 0.53 | 0.48 | 01-JUL-09:50 | 3706.23 | 19.96 | 86.67 | 410.83 | 1623.61 | 20.03 | 178.00 | 372.17 |
August | 366.67 | 0.51 | 0.48 | 01-AUG-06:30 | 3536.58 | 22.36 | 102.83 | 388.83 | 2030.60 | 23.05 | 180.67 | 354.33 |
September | 301.17 | 0.50 | 0.48 | 01-SEP-07:00 | 3910.78 | 25.80 | 133.00 | 321.00 | 2171.39 | 25.86 | 197.33 | 286.67 |
October | 245.33 | 0.52 | 0.48 | 01-OCT-08:39 | 2696.94 | 26.27 | 123.17 | 280.50 | 1197.67 | 25.06 | 164.83 | 239.17 |
November | 242.67 | 0.53 | 0.48 | 01-NOV-09:00 | 1257.68 | 22.45 | 87.17 | 217.17 | 655.35 | 22.55 | 106.33 | 157.17 |
December | 160.33 | 0.54 | 0.48 | 01-DEC-09:00 | 1242.46 | 22.98 | 59.33 | 192.50 | 657.18 | 22.98 | 74.00 | 120.00 |
Annual Sum or Average | 3714.00 | 0.52 | 2870.63 | 22.72 | 1222.50 | 3725.33 | 1428.18 | 22.76 | 2017.50 | 3197.00 | ||
Minimum of Months | 160.33 | 0.50 | 0.48 | 1183.88 | 19.96 | 59.33 | 192.50 | 629.09 | 20.03 | 74.00 | 120.00 | |
Maximum of Months | 471.00 | 0.54 | 0.48 | 3910.78 | 26.27 | 149.83 | 410.83 | 2171.39 | 25.86 | 250.00 | 372.17 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_1_DAYLCTRL
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 237.83 | 0.51 | 0.48 | 01-JAN-09:50 | 3075.69 | 32.30 | 222.33 | 223.83 | 2490.01 | 33.43 | 222.67 | 199.00 |
February | 259.50 | 0.50 | 0.48 | 01-FEB-08:39 | 5248.55 | 33.26 | 241.33 | 247.17 | 2369.05 | 27.78 | 158.33 | 227.33 |
March | 247.00 | 0.51 | 0.48 | 01-MAR-07:30 | 8693.93 | 32.63 | 208.67 | 317.33 | 1973.04 | 18.35 | 10.00 | 280.33 |
April | 379.50 | 0.51 | 0.48 | 01-APR-07:10 | 2504.34 | 14.21 | 0.00 | 349.67 | 1442.80 | 17.67 | 5.50 | 319.67 |
May | 427.83 | 0.51 | 0.48 | 01-MAY-07:10 | 2298.86 | 14.22 | 0.00 | 391.33 | 1306.86 | 17.62 | 1.00 | 357.33 |
June | 375.17 | 0.52 | 0.48 | 01-JUN-05:00 | 2028.36 | 14.06 | 0.00 | 402.17 | 1210.17 | 17.48 | 0.00 | 361.00 |
July | 471.00 | 0.54 | 0.48 | 01-JUL-05:30 | 1808.29 | 12.71 | 0.00 | 404.17 | 1101.31 | 16.17 | 0.00 | 359.33 |
August | 366.67 | 0.52 | 0.48 | 01-AUG-05:00 | 2141.70 | 13.79 | 0.00 | 381.00 | 1329.11 | 17.32 | 4.00 | 342.67 |
September | 301.17 | 0.50 | 0.48 | 01-SEP-07:40 | 3405.90 | 16.79 | 27.00 | 323.50 | 1745.66 | 18.50 | 19.17 | 297.83 |
October | 245.33 | 0.51 | 0.48 | 01-OCT-07:49 | 8075.73 | 34.36 | 220.50 | 288.50 | 2281.64 | 19.73 | 27.00 | 263.83 |
November | 242.67 | 0.51 | 0.48 | 01-NOV-08:09 | 3436.49 | 31.80 | 223.67 | 228.50 | 2789.47 | 33.08 | 227.50 | 203.83 |
December | 160.33 | 0.50 | 0.48 | 01-DEC-09:39 | 4141.12 | 35.26 | 149.50 | 211.83 | 3562.65 | 36.73 | 149.67 | 180.67 |
Annual Sum or Average | 3714.00 | 0.51 | 3521.18 | 21.28 | 1293.00 | 3769.00 | 1775.63 | 21.21 | 824.83 | 3392.83 | ||
Minimum of Months | 160.33 | 0.50 | 0.48 | 1808.29 | 12.71 | 0.00 | 211.83 | 1101.31 | 16.17 | 0.00 | 180.67 | |
Maximum of Months | 471.00 | 0.54 | 0.48 | 8693.93 | 35.26 | 241.33 | 404.17 | 3562.65 | 36.73 | 227.50 | 361.00 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_2_DAYLCTRL
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 237.83 | 0.54 | 0.48 | 01-JAN-09:00 | 1057.81 | 18.82 | 62.33 | 209.67 | 664.40 | 21.11 | 74.17 | 153.17 |
February | 259.50 | 0.52 | 0.48 | 01-FEB-08:30 | 1727.12 | 20.91 | 82.00 | 234.83 | 924.25 | 21.69 | 67.17 | 196.67 |
March | 247.00 | 0.51 | 0.48 | 01-MAR-07:30 | 3110.03 | 23.50 | 91.67 | 311.50 | 1400.10 | 22.70 | 59.67 | 271.33 |
April | 379.50 | 0.51 | 0.48 | 01-APR-06:19 | 3245.41 | 21.87 | 118.67 | 353.33 | 1845.75 | 22.88 | 91.67 | 321.00 |
May | 427.83 | 0.51 | 0.48 | 01-MAY-06:00 | 3326.62 | 20.76 | 133.33 | 397.83 | 1501.47 | 21.29 | 79.67 | 365.17 |
June | 375.17 | 0.51 | 0.48 | 01-JUN-05:10 | 3504.16 | 20.74 | 99.17 | 410.50 | 1973.97 | 21.90 | 73.83 | 373.17 |
July | 471.00 | 0.52 | 0.48 | 01-JUL-04:00 | 3286.45 | 20.40 | 148.50 | 416.67 | 1537.04 | 21.25 | 99.67 | 387.67 |
August | 366.67 | 0.51 | 0.48 | 01-AUG-05:30 | 3832.58 | 21.89 | 116.33 | 385.83 | 1721.16 | 21.54 | 66.83 | 354.67 |
September | 301.17 | 0.50 | 0.48 | 01-SEP-07:40 | 3155.11 | 21.70 | 84.67 | 328.17 | 1787.66 | 22.67 | 62.50 | 298.33 |
October | 245.33 | 0.53 | 0.48 | 01-OCT-07:40 | 2847.72 | 23.26 | 93.67 | 279.33 | 1283.15 | 22.38 | 65.00 | 241.50 |
November | 242.67 | 0.53 | 0.48 | 01-NOV-08:09 | 1312.14 | 20.23 | 80.17 | 216.00 | 699.20 | 21.00 | 66.83 | 167.00 |
December | 160.33 | 0.54 | 0.48 | 01-DEC-09:39 | 1239.23 | 21.45 | 56.50 | 194.33 | 683.31 | 22.04 | 56.33 | 130.17 |
Annual Sum or Average | 3714.00 | 0.52 | 2842.38 | 21.24 | 1167.00 | 3738.00 | 1430.95 | 21.84 | 863.33 | 3259.83 | ||
Minimum of Months | 160.33 | 0.50 | 0.48 | 1057.81 | 18.82 | 56.50 | 194.33 | 664.40 | 21.00 | 56.33 | 130.17 | |
Maximum of Months | 471.00 | 0.54 | 0.48 | 3832.58 | 23.50 | 148.50 | 416.67 | 1973.97 | 22.88 | 99.67 | 387.67 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_3_DAYLCTRL
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 237.83 | 0.57 | 0.48 | 02-JAN-11:09 | 569.77 | 10.11 | 0.00 | 189.83 | 325.22 | 13.58 | 0.00 | 92.33 |
February | 259.50 | 0.54 | 0.48 | 01-FEB-09:20 | 726.39 | 11.64 | 0.00 | 225.17 | 429.95 | 15.12 | 0.00 | 160.33 |
March | 247.00 | 0.52 | 0.48 | 01-MAR-08:20 | 985.33 | 13.40 | 0.00 | 306.67 | 609.81 | 16.87 | 0.00 | 247.17 |
April | 379.50 | 0.51 | 0.48 | 01-APR-07:10 | 1155.47 | 14.08 | 0.00 | 353.33 | 699.47 | 17.47 | 0.50 | 319.00 |
May | 427.83 | 0.50 | 0.48 | 01-MAY-07:10 | 1436.64 | 16.54 | 39.33 | 404.00 | 855.26 | 19.68 | 50.33 | 378.33 |
June | 375.17 | 0.50 | 0.48 | 01-JUN-05:30 | 1511.86 | 18.11 | 60.67 | 419.00 | 924.96 | 21.19 | 68.17 | 392.50 |
July | 471.00 | 0.52 | 0.48 | 01-JUL-04:00 | 1282.23 | 17.10 | 78.17 | 429.50 | 799.22 | 20.22 | 84.00 | 396.83 |
August | 366.67 | 0.51 | 0.48 | 01-AUG-05:49 | 1133.63 | 14.27 | 0.00 | 394.67 | 722.34 | 17.82 | 3.33 | 362.33 |
September | 301.17 | 0.51 | 0.48 | 01-SEP-07:40 | 1074.56 | 14.56 | 0.00 | 320.33 | 681.05 | 18.00 | 0.17 | 278.67 |
October | 245.33 | 0.54 | 0.48 | 01-OCT-08:20 | 799.23 | 12.57 | 0.00 | 269.67 | 505.81 | 16.09 | 0.00 | 208.67 |
November | 242.67 | 0.56 | 0.48 | 01-NOV-10:09 | 614.29 | 10.47 | 0.00 | 202.83 | 350.62 | 13.88 | 0.00 | 107.17 |
December | 160.33 | 0.58 | 0.48 | 01-DEC-10:09 | 534.19 | 10.39 | 0.00 | 168.67 | 326.54 | 14.08 | 0.00 | 64.33 |
Annual Sum or Average | 3714.00 | 0.52 | 1066.70 | 14.25 | 178.17 | 3683.67 | 653.16 | 17.60 | 206.50 | 3007.67 | ||
Minimum of Months | 160.33 | 0.50 | 0.48 | 534.19 | 10.11 | 0.00 | 168.67 | 325.22 | 13.58 | 0.00 | 64.33 | |
Maximum of Months | 471.00 | 0.58 | 0.48 | 1511.86 | 18.11 | 78.17 | 429.50 | 924.96 | 21.19 | 84.00 | 396.83 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_4_DAYLCTRL
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 237.83 | 0.54 | 0.48 | 01-JAN-12:00 | 1203.20 | 20.44 | 81.17 | 209.83 | 656.86 | 21.17 | 70.83 | 158.67 |
February | 259.50 | 0.52 | 0.48 | 01-FEB-09:20 | 1697.85 | 19.76 | 67.00 | 236.83 | 903.24 | 21.56 | 64.83 | 200.67 |
March | 247.00 | 0.51 | 0.48 | 01-MAR-08:20 | 2714.28 | 21.98 | 78.33 | 313.33 | 1487.36 | 22.91 | 68.33 | 269.17 |
April | 379.50 | 0.51 | 0.48 | 01-APR-07:30 | 3247.50 | 20.56 | 106.00 | 351.17 | 1461.26 | 20.38 | 51.00 | 322.17 |
May | 427.83 | 0.51 | 0.48 | 01-MAY-07:30 | 3352.70 | 17.21 | 52.50 | 397.33 | 1849.98 | 18.05 | 0.00 | 368.67 |
June | 375.17 | 0.51 | 0.48 | 01-JUN-06:10 | 3432.05 | 16.81 | 42.83 | 409.83 | 1603.57 | 17.81 | 0.00 | 375.00 |
July | 471.00 | 0.53 | 0.48 | 01-JUL-06:19 | 3760.67 | 15.95 | 58.83 | 413.00 | 1707.69 | 16.63 | 3.67 | 375.33 |
August | 366.67 | 0.51 | 0.48 | 01-AUG-06:19 | 3573.93 | 18.88 | 75.83 | 389.33 | 2116.29 | 20.29 | 50.33 | 357.83 |
September | 301.17 | 0.50 | 0.48 | 01-SEP-07:49 | 3950.28 | 22.77 | 100.50 | 320.83 | 2255.27 | 23.66 | 79.17 | 291.00 |
October | 245.33 | 0.52 | 0.48 | 01-OCT-08:30 | 2708.85 | 22.59 | 89.83 | 281.17 | 1255.34 | 23.07 | 70.17 | 243.67 |
November | 242.67 | 0.53 | 0.48 | 01-NOV-09:50 | 1278.96 | 19.75 | 71.67 | 218.17 | 685.43 | 20.46 | 57.00 | 164.00 |
December | 160.33 | 0.54 | 0.48 | 01-DEC-09:00 | 1262.80 | 20.35 | 48.67 | 193.33 | 687.04 | 21.11 | 50.67 | 128.33 |
Annual Sum or Average | 3714.00 | 0.52 | 2908.03 | 19.33 | 873.17 | 3734.17 | 1494.24 | 20.15 | 566.00 | 3254.50 | ||
Minimum of Months | 160.33 | 0.50 | 0.48 | 1203.20 | 15.95 | 42.83 | 193.33 | 656.86 | 16.63 | 0.00 | 128.33 | |
Maximum of Months | 471.00 | 0.54 | 0.48 | 3950.28 | 22.77 | 106.00 | 413.00 | 2255.27 | 23.66 | 79.17 | 375.33 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_1_DAYLCTRL
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 237.83 | 0.51 | 0.48 | 01-JAN-09:50 | 3076.98 | 32.29 | 222.33 | 224.00 | 2491.64 | 33.43 | 222.67 | 199.17 |
February | 259.50 | 0.50 | 0.48 | 01-FEB-08:39 | 5250.53 | 33.25 | 241.33 | 247.17 | 2371.34 | 27.78 | 158.33 | 227.33 |
March | 247.00 | 0.51 | 0.48 | 01-MAR-07:30 | 8697.31 | 32.62 | 208.67 | 317.33 | 1975.89 | 18.34 | 10.00 | 280.83 |
April | 379.50 | 0.51 | 0.48 | 01-APR-07:10 | 2508.10 | 14.18 | 0.00 | 349.83 | 1445.14 | 17.66 | 4.67 | 319.83 |
May | 427.83 | 0.51 | 0.48 | 01-MAY-07:10 | 2302.49 | 14.19 | 0.00 | 391.33 | 1309.00 | 17.61 | 1.00 | 357.33 |
June | 375.17 | 0.52 | 0.48 | 01-JUN-05:00 | 2031.17 | 14.03 | 0.00 | 402.17 | 1211.91 | 17.47 | 0.00 | 361.50 |
July | 471.00 | 0.54 | 0.48 | 01-JUL-05:30 | 1810.75 | 12.68 | 0.00 | 404.33 | 1102.82 | 16.15 | 0.00 | 359.33 |
August | 366.67 | 0.52 | 0.48 | 01-AUG-05:00 | 2144.43 | 13.76 | 0.00 | 381.17 | 1330.88 | 17.30 | 3.33 | 342.67 |
September | 301.17 | 0.50 | 0.48 | 01-SEP-07:40 | 3409.35 | 16.77 | 27.00 | 323.50 | 1748.21 | 18.48 | 19.00 | 297.83 |
October | 245.33 | 0.51 | 0.48 | 01-OCT-07:49 | 8077.91 | 34.35 | 220.50 | 288.50 | 2284.25 | 19.71 | 27.00 | 263.83 |
November | 242.67 | 0.51 | 0.48 | 01-NOV-08:09 | 3437.92 | 31.79 | 223.50 | 228.50 | 2791.31 | 33.07 | 227.50 | 203.83 |
December | 160.33 | 0.50 | 0.48 | 01-DEC-09:39 | 4141.95 | 35.25 | 149.50 | 211.83 | 3564.28 | 36.73 | 149.67 | 180.67 |
Annual Sum or Average | 3714.00 | 0.51 | 3523.85 | 21.26 | 1292.83 | 3769.67 | 1777.68 | 21.20 | 823.17 | 3394.17 | ||
Minimum of Months | 160.33 | 0.50 | 0.48 | 1810.75 | 12.68 | 0.00 | 211.83 | 1102.82 | 16.15 | 0.00 | 180.67 | |
Maximum of Months | 471.00 | 0.54 | 0.48 | 8697.31 | 35.25 | 241.33 | 404.33 | 3564.28 | 36.73 | 227.50 | 361.50 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_2_DAYLCTRL
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 237.83 | 0.54 | 0.48 | 01-JAN-09:00 | 1058.89 | 18.79 | 62.33 | 209.67 | 665.30 | 21.10 | 74.17 | 153.33 |
February | 259.50 | 0.52 | 0.48 | 01-FEB-08:30 | 1728.46 | 20.89 | 81.83 | 235.00 | 925.42 | 21.68 | 66.33 | 196.67 |
March | 247.00 | 0.51 | 0.48 | 01-MAR-07:30 | 3111.88 | 23.47 | 91.67 | 311.50 | 1401.72 | 22.68 | 58.83 | 271.50 |
April | 379.50 | 0.51 | 0.48 | 01-APR-06:19 | 3219.77 | 20.77 | 105.50 | 352.83 | 1847.53 | 22.86 | 91.67 | 321.17 |
May | 427.83 | 0.51 | 0.48 | 01-MAY-06:00 | 3329.28 | 20.73 | 133.33 | 397.83 | 1503.37 | 21.27 | 79.67 | 365.33 |
June | 375.17 | 0.51 | 0.48 | 01-JUN-05:10 | 3506.43 | 20.72 | 99.17 | 410.67 | 1975.85 | 21.89 | 73.83 | 373.33 |
July | 471.00 | 0.52 | 0.48 | 01-JUL-04:00 | 3288.31 | 20.38 | 148.50 | 416.67 | 1538.51 | 21.24 | 99.67 | 387.67 |
August | 366.67 | 0.51 | 0.48 | 01-AUG-05:30 | 3834.16 | 21.87 | 116.33 | 385.83 | 1722.71 | 21.53 | 66.83 | 355.00 |
September | 301.17 | 0.50 | 0.48 | 01-SEP-07:40 | 3151.72 | 21.47 | 82.83 | 328.00 | 1789.23 | 22.65 | 62.50 | 298.50 |
October | 245.33 | 0.53 | 0.48 | 01-OCT-07:40 | 2805.07 | 21.81 | 83.00 | 279.17 | 1284.44 | 22.37 | 64.50 | 241.67 |
November | 242.67 | 0.53 | 0.48 | 01-NOV-08:09 | 1313.33 | 20.21 | 80.17 | 216.00 | 700.18 | 20.99 | 66.67 | 167.17 |
December | 160.33 | 0.54 | 0.48 | 01-DEC-09:39 | 1240.04 | 21.43 | 56.50 | 194.33 | 684.18 | 22.03 | 56.17 | 130.50 |
Annual Sum or Average | 3714.00 | 0.52 | 2838.00 | 21.00 | 1141.17 | 3737.50 | 1432.44 | 21.83 | 860.83 | 3261.83 | ||
Minimum of Months | 160.33 | 0.50 | 0.48 | 1058.89 | 18.79 | 56.50 | 194.33 | 665.30 | 20.99 | 56.17 | 130.50 | |
Maximum of Months | 471.00 | 0.54 | 0.48 | 3834.16 | 23.47 | 148.50 | 416.67 | 1975.85 | 22.86 | 99.67 | 387.67 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_3_DAYLCTRL
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 237.83 | 0.57 | 0.48 | 02-JAN-10:00 | 570.54 | 10.08 | 0.00 | 190.17 | 325.77 | 13.57 | 0.00 | 93.67 |
February | 259.50 | 0.54 | 0.48 | 01-FEB-09:20 | 727.27 | 11.61 | 0.00 | 225.17 | 430.61 | 15.10 | 0.00 | 160.83 |
March | 247.00 | 0.52 | 0.48 | 01-MAR-08:20 | 986.32 | 13.37 | 0.00 | 306.83 | 610.65 | 16.86 | 0.00 | 247.67 |
April | 379.50 | 0.51 | 0.48 | 01-APR-07:10 | 1156.75 | 14.05 | 0.00 | 353.67 | 700.47 | 17.46 | 0.50 | 319.00 |
May | 427.83 | 0.50 | 0.48 | 01-MAY-07:10 | 1438.34 | 16.51 | 39.33 | 404.00 | 856.51 | 19.67 | 50.33 | 378.50 |
June | 375.17 | 0.50 | 0.48 | 01-JUN-05:30 | 1513.25 | 18.09 | 60.67 | 419.00 | 926.13 | 21.18 | 68.00 | 392.67 |
July | 471.00 | 0.51 | 0.48 | 01-JUL-04:00 | 1283.45 | 17.08 | 78.17 | 429.50 | 800.20 | 20.21 | 83.83 | 397.17 |
August | 366.67 | 0.51 | 0.48 | 01-AUG-05:49 | 1134.58 | 14.24 | 0.00 | 394.67 | 723.20 | 17.81 | 3.33 | 362.67 |
September | 301.17 | 0.51 | 0.48 | 01-SEP-07:40 | 1075.51 | 14.53 | 0.00 | 320.33 | 681.93 | 17.99 | 0.00 | 279.00 |
October | 245.33 | 0.54 | 0.48 | 01-OCT-08:20 | 799.93 | 12.54 | 0.00 | 269.83 | 506.47 | 16.08 | 0.00 | 208.83 |
November | 242.67 | 0.56 | 0.48 | 01-NOV-10:09 | 615.14 | 10.44 | 0.00 | 202.83 | 351.20 | 13.87 | 0.00 | 107.67 |
December | 160.33 | 0.58 | 0.48 | 01-DEC-10:09 | 534.70 | 10.36 | 0.00 | 168.67 | 327.01 | 14.07 | 0.00 | 64.67 |
Annual Sum or Average | 3714.00 | 0.52 | 1067.80 | 14.22 | 178.17 | 3684.67 | 654.05 | 17.59 | 206.00 | 3012.33 | ||
Minimum of Months | 160.33 | 0.50 | 0.48 | 534.70 | 10.08 | 0.00 | 168.67 | 325.77 | 13.57 | 0.00 | 64.67 | |
Maximum of Months | 471.00 | 0.58 | 0.48 | 1513.25 | 18.09 | 78.17 | 429.50 | 926.13 | 21.18 | 83.83 | 397.17 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_4_DAYLCTRL
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 237.83 | 0.54 | 0.48 | 01-JAN-12:00 | 1204.28 | 20.42 | 81.00 | 210.00 | 657.75 | 21.16 | 70.83 | 158.67 |
February | 259.50 | 0.52 | 0.48 | 01-FEB-09:20 | 1699.18 | 19.73 | 67.00 | 236.83 | 904.41 | 21.55 | 64.67 | 200.83 |
March | 247.00 | 0.51 | 0.48 | 01-MAR-08:20 | 2716.08 | 21.95 | 78.33 | 313.50 | 1489.01 | 22.90 | 67.17 | 269.33 |
April | 379.50 | 0.51 | 0.48 | 01-APR-07:30 | 3249.67 | 20.54 | 105.83 | 351.17 | 1463.06 | 20.37 | 51.00 | 322.17 |
May | 427.83 | 0.51 | 0.48 | 01-MAY-07:30 | 3355.40 | 17.18 | 52.50 | 397.33 | 1852.02 | 18.03 | 0.00 | 368.67 |
June | 375.17 | 0.51 | 0.48 | 01-JUN-06:10 | 3434.32 | 16.78 | 42.83 | 409.83 | 1605.43 | 17.80 | 0.00 | 375.00 |
July | 471.00 | 0.53 | 0.48 | 01-JUL-06:19 | 3762.63 | 15.92 | 58.83 | 413.00 | 1709.30 | 16.61 | 3.67 | 375.50 |
August | 366.67 | 0.51 | 0.48 | 01-AUG-06:19 | 3575.53 | 18.85 | 75.83 | 389.33 | 2117.87 | 20.28 | 50.33 | 357.83 |
September | 301.17 | 0.50 | 0.48 | 01-SEP-07:49 | 3952.21 | 22.74 | 100.50 | 320.83 | 2257.19 | 23.64 | 79.00 | 291.17 |
October | 245.33 | 0.52 | 0.48 | 01-OCT-08:30 | 2710.09 | 22.56 | 89.83 | 281.50 | 1256.68 | 23.06 | 69.83 | 243.67 |
November | 242.67 | 0.53 | 0.48 | 01-NOV-09:50 | 1280.15 | 19.72 | 71.67 | 218.17 | 686.40 | 20.45 | 56.83 | 164.17 |
December | 160.33 | 0.54 | 0.48 | 01-DEC-09:00 | 1263.57 | 20.33 | 48.67 | 193.33 | 687.88 | 21.09 | 50.67 | 128.50 |
Annual Sum or Average | 3714.00 | 0.52 | 2909.82 | 19.30 | 872.83 | 3734.83 | 1495.80 | 20.14 | 564.00 | 3255.50 | ||
Minimum of Months | 160.33 | 0.50 | 0.48 | 1204.28 | 15.92 | 42.83 | 193.33 | 657.75 | 16.61 | 0.00 | 128.50 | |
Maximum of Months | 471.00 | 0.54 | 0.48 | 3952.21 | 22.74 | 105.83 | 413.00 | 2257.19 | 23.64 | 79.00 | 375.50 |
Report: CoilReportMonthly
For: VAV_BOT WITH REHEAT HEATING COIL
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.431673E+10 | 23135.83 | 07-JAN-08:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.236831E+10 | 18604.48 | 18-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.257391E+09 | 12994.44 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 26295068.59 | 5890.78 | 19-APR-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 4335583.48 | 1985.10 | 18-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.487782E+09 | 9926.46 | 24-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.163238E+10 | 16188.75 | 26-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.909322E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.431673E+10 | 23135.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_BOTTOM VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.107010E+09 | 12545.09 | 09-JAN-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 15053241.78 | 2309.68 | 18-FEB-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.122063E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.107010E+09 | 12545.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.453990E+09 | 11504.35 | 07-JAN-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.188701E+09 | 11507.43 | 18-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 18235187.81 | 1655.30 | 24-MAR-05:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 284203.15 | 450.80 | 19-APR-05:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 2122372.54 | 689.06 | 31-OCT-05:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 62624620.76 | 1799.82 | 30-NOV-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.276570E+09 | 4845.06 | 22-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.100253E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.453990E+09 | 11507.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.679859E+09 | 18585.38 | 05-JAN-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.267377E+09 | 18598.42 | 21-FEB-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 28760249.33 | 8216.96 | 06-MAR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 266588.35 | 162.69 | 18-APR-05:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 4958729.65 | 1131.59 | 28-OCT-05:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.104447E+09 | 18564.13 | 13-NOV-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.331846E+09 | 18619.44 | 26-DEC-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.141751E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.679859E+09 | 18619.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 57643402.51 | 9305.40 | 17-JAN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 57643402.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 57643402.51 | 9305.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV_MID WITH REHEAT HEATING COIL
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.969324E+11 | 264179.09 | 07-JAN-08:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.561791E+11 | 217138.59 | 18-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.111515E+11 | 164372.99 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.391667E+10 | 114449.56 | 19-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.203383E+09 | 37342.76 | 18-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.872804E+09 | 43415.69 | 16-OCT-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.269099E+11 | 167498.68 | 13-NOV-08:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.652491E+11 | 236954.74 | 26-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.261415E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.969324E+11 | 264179.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_MID VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.103338E+11 | 495021.23 | 02-JAN-05:44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.374197E+09 | 491962.00 | 21-FEB-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.316043E+09 | 91726.54 | 26-DEC-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.110241E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.103338E+11 | 495021.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.345473E+11 | 131389.39 | 17-JAN-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.174151E+11 | 130805.38 | 22-FEB-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.547858E+10 | 141067.60 | 02-MAR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.158937E+10 | 140689.13 | 12-APR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 74186977.68 | 89051.63 | 18-MAY-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.213029E+10 | 130086.05 | 30-OCT-04:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.107757E+11 | 131293.11 | 27-NOV-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.244712E+11 | 130816.91 | 28-DEC-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.964818E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.345473E+11 | 141067.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.340023E+11 | 175675.36 | 23-JAN-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.179323E+11 | 175530.52 | 13-FEB-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.699861E+10 | 180431.00 | 02-MAR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.205009E+10 | 180373.28 | 12-APR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.407685E+09 | 100052.52 | 18-MAY-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 40741500.87 | 12374.09 | 14-JUN-05:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.148976E+09 | 29113.55 | 27-SEP-05:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.416275E+10 | 175396.93 | 31-OCT-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.148653E+11 | 175734.68 | 24-NOV-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.267223E+11 | 175706.22 | 23-DEC-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.107331E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.340023E+11 | 180431.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.338878E+11 | 254331.17 | 02-JAN-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.157871E+11 | 253745.78 | 21-FEB-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.656199E+10 | 256011.35 | 23-MAR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.266267E+10 | 253243.07 | 18-APR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.449567E+09 | 143471.03 | 18-MAY-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 14925140.15 | 9180.70 | 14-JUN-05:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 99262323.64 | 21865.77 | 27-SEP-05:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.322985E+10 | 247333.16 | 28-OCT-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.135270E+11 | 253467.59 | 28-NOV-05:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.258312E+11 | 253985.97 | 26-DEC-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.102051E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.338878E+11 | 256011.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.279841E+11 | 172322.29 | 03-JAN-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.144767E+11 | 172326.79 | 13-FEB-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.561637E+10 | 171906.16 | 06-MAR-05:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.177058E+10 | 150730.28 | 19-APR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.312085E+09 | 85766.94 | 18-MAY-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 1182263.63 | 1060.56 | 14-JUN-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 57894874.67 | 10564.88 | 28-SEP-05:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.313972E+10 | 137011.26 | 28-OCT-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.115887E+11 | 171889.11 | 13-NOV-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.210075E+11 | 172273.57 | 18-DEC-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.859548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.279841E+11 | 172326.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV_TOP WITH REHEAT HEATING COIL
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.116894E+11 | 30262.61 | 07-JAN-08:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.746811E+10 | 26689.80 | 18-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.264401E+10 | 21415.33 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.972143E+09 | 16180.07 | 19-APR-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.134112E+09 | 8133.18 | 18-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 10724739.21 | 1985.73 | 27-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.420047E+09 | 9003.78 | 16-OCT-06:55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.442692E+10 | 20916.65 | 13-NOV-08:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.935457E+10 | 26996.58 | 26-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.371200E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.116894E+11 | 30262.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_TOP VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.541600E+10 | 81341.68 | 30-JAN-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.254669E+10 | 81270.53 | 21-FEB-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.599612E+09 | 81326.64 | 06-MAR-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 37739503.55 | 43513.86 | 17-APR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.264581E+09 | 81070.02 | 23-OCT-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.163016E+10 | 81311.05 | 13-NOV-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.356468E+10 | 81315.56 | 18-DEC-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.140595E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.541600E+10 | 81341.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.680494E+10 | 14580.58 | 30-JAN-05:23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.446556E+10 | 14545.81 | 06-FEB-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.214641E+10 | 14580.21 | 06-MAR-05:23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.857269E+09 | 14497.21 | 18-APR-04:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.171917E+09 | 14424.40 | 24-MAY-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 16397520.58 | 11529.89 | 14-JUN-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 75892055.48 | 14484.24 | 27-SEP-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.117118E+10 | 14532.60 | 23-OCT-04:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.321905E+10 | 14580.95 | 27-NOV-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.569389E+10 | 14574.82 | 18-DEC-05:43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.246225E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.680494E+10 | 14580.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.537248E+10 | 19914.25 | 30-JAN-05:14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.330961E+10 | 19926.12 | 06-FEB-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.172207E+10 | 19914.02 | 06-MAR-05:14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.636933E+09 | 19904.00 | 11-APR-04:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.225061E+09 | 18511.81 | 18-MAY-04:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 35539077.68 | 10770.08 | 14-JUN-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 4948472.80 | 810.19 | 03-AUG-05:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.144808E+09 | 12819.07 | 27-SEP-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.113739E+10 | 19920.91 | 30-OCT-04:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.290743E+10 | 19921.33 | 27-NOV-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.462147E+10 | 19934.66 | 11-DEC-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.201177E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.537248E+10 | 19934.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.613118E+10 | 29522.77 | 30-JAN-05:14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.361164E+10 | 29540.10 | 06-FEB-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.212593E+10 | 29522.41 | 06-MAR-05:14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.104160E+10 | 29507.40 | 11-APR-04:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.377560E+09 | 28085.00 | 18-MAY-04:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 69933904.40 | 13328.95 | 14-JUN-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 3829780.04 | 810.28 | 03-AUG-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.138822E+09 | 15191.08 | 27-SEP-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.125519E+10 | 29518.44 | 16-OCT-04:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.339893E+10 | 29533.51 | 27-NOV-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.532083E+10 | 29552.83 | 11-DEC-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.234755E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.613118E+10 | 29552.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.464772E+10 | 20338.51 | 18-JAN-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.281634E+10 | 20322.66 | 22-FEB-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.160005E+10 | 20323.61 | 06-MAR-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.668179E+09 | 20286.58 | 11-APR-04:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.219820E+09 | 14610.00 | 18-MAY-04:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 34302936.12 | 4791.89 | 14-JUN-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 86750239.88 | 4130.09 | 27-SEP-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.100558E+10 | 20295.86 | 23-OCT-04:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.249971E+10 | 20347.11 | 24-NOV-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.382004E+10 | 20336.47 | 04-DEC-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.173985E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.464772E+10 | 20347.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CAV_BAS HEATING COIL
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BASEMENT HEATING COIL
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BOT HEATING COIL
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER MID HEATING COIL
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER TOP HEATING COIL
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BOT_SUPPHEATCOIL
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER MID_SUPPHEATCOIL
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER TOP_SUPPHEATCOIL
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV_BOT WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 736.07 | 736.07 | 0.98 | 02-JAN-06:03 | 0.98 | 0.00 |
February | 0.00 | 0.00 | 0.840364E+09 | 0.840364E+09 | 57804.65 | 27-FEB-15:00 | 57804.65 | 0.01 |
March | 0.00 | 0.00 | 0.110992E+10 | 0.110992E+10 | 30441.76 | 18-MAR-16:00 | 30441.76 | 0.02 |
April | 0.00 | 0.00 | 0.107974E+11 | 0.107974E+11 | 131845.78 | 27-APR-14:30 | 131845.78 | 0.05 |
May | 0.00 | 0.00 | 0.175815E+11 | 0.175780E+11 | 107416.23 | 04-MAY-15:00 | 107416.23 | 0.16 |
June | 0.00 | 0.00 | 0.342120E+11 | 0.342064E+11 | 119130.45 | 28-JUN-15:20 | 119130.45 | 0.33 |
July | 0.00 | 0.00 | 0.625953E+11 | 0.615638E+11 | 151932.38 | 31-JUL-14:40 | 139248.92 | 0.53 |
August | 0.00 | 0.00 | 0.856034E+11 | 0.826075E+11 | 163941.76 | 29-AUG-14:30 | 143317.70 | 0.63 |
September | 0.00 | 0.00 | 0.274451E+11 | 0.268987E+11 | 122116.13 | 14-SEP-13:00 | 90348.62 | 0.34 |
October | 0.00 | 0.00 | 0.494085E+10 | 0.494085E+10 | 83106.86 | 04-OCT-15:00 | 83106.86 | 0.05 |
November | 0.00 | 0.00 | 0.722474E+09 | 0.722474E+09 | 40066.02 | 04-NOV-14:00 | 40066.02 | 0.01 |
December | 0.00 | 0.00 | 1456.30 | 1456.30 | 0.89 | 26-DEC-06:13 | 0.89 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.245848E+12 | 0.241265E+12 | 0.18 | |||
Minimum of Months | 0.00 | 0.00 | 736.07 | 736.07 | 0.89 | 0.89 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.856034E+11 | 0.826075E+11 | 163941.76 | 143317.70 | 0.63 |
Report: CoilReportMonthly
For: VAV_MID WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 46032.53 | 46032.53 | 3.21 | 18-JAN-06:30 | 3.21 | 0.00 |
February | 0.00 | 0.00 | 0.552779E+10 | 0.552779E+10 | 396423.28 | 27-FEB-15:00 | 396423.28 | 0.01 |
March | 0.00 | 0.00 | 0.826430E+10 | 0.826430E+10 | 285453.90 | 18-MAR-16:00 | 285453.90 | 0.02 |
April | 0.00 | 0.00 | 0.828809E+11 | 0.828809E+11 | 1121146.08 | 27-APR-14:40 | 1121146.08 | 0.05 |
May | 0.00 | 0.00 | 0.153180E+12 | 0.153144E+12 | 1010200.20 | 04-MAY-15:00 | 1010200.20 | 0.17 |
June | 0.00 | 0.00 | 0.283078E+12 | 0.283052E+12 | 1075038.06 | 28-JUN-15:30 | 1075038.06 | 0.33 |
July | 0.00 | 0.00 | 0.503780E+12 | 0.496657E+12 | 1358525.19 | 31-JUL-16:00 | 1162844.61 | 0.48 |
August | 0.00 | 0.00 | 0.670024E+12 | 0.647696E+12 | 1449146.03 | 29-AUG-14:30 | 1259882.80 | 0.53 |
September | 0.00 | 0.00 | 0.247875E+12 | 0.241423E+12 | 1191956.53 | 14-SEP-13:00 | 854189.68 | 0.34 |
October | 0.00 | 0.00 | 0.401280E+11 | 0.401280E+11 | 735473.18 | 04-OCT-15:00 | 735473.18 | 0.05 |
November | 0.00 | 0.00 | 0.640785E+10 | 0.640785E+10 | 355900.74 | 04-NOV-14:10 | 355900.74 | 0.04 |
December | 0.00 | 0.00 | 83990.50 | 83990.50 | 3.11 | 30-DEC-12:50 | 3.11 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.200115E+13 | 0.196518E+13 | 0.17 | |||
Minimum of Months | 0.00 | 0.00 | 46032.53 | 46032.53 | 3.11 | 3.11 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.670024E+12 | 0.647696E+12 | 1449146.03 | 1259882.80 | 0.53 |
Report: CoilReportMonthly
For: VAV_TOP WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 56866.44 | 56866.44 | 338.84 | 09-JAN-04:52 | 338.84 | 0.00 |
February | 0.00 | 0.00 | 0.463910E+09 | 0.463910E+09 | 31501.52 | 27-FEB-15:00 | 31501.52 | 0.01 |
March | 0.00 | 0.00 | 0.742032E+09 | 0.742032E+09 | 28007.08 | 18-MAR-16:00 | 28007.08 | 0.02 |
April | 0.00 | 0.00 | 0.856015E+10 | 0.856015E+10 | 131094.23 | 27-APR-14:30 | 131094.23 | 0.05 |
May | 0.00 | 0.00 | 0.157180E+11 | 0.157151E+11 | 110752.76 | 04-MAY-15:00 | 110752.76 | 0.15 |
June | 0.00 | 0.00 | 0.296458E+11 | 0.296436E+11 | 127721.15 | 28-JUN-15:20 | 127721.15 | 0.31 |
July | 0.00 | 0.00 | 0.535315E+11 | 0.528186E+11 | 155320.98 | 31-JUL-16:00 | 135111.70 | 0.46 |
August | 0.00 | 0.00 | 0.702697E+11 | 0.681700E+11 | 170605.04 | 13-AUG-14:21 | 139657.52 | 0.52 |
September | 0.00 | 0.00 | 0.242451E+11 | 0.238040E+11 | 119880.09 | 14-SEP-13:10 | 91383.82 | 0.32 |
October | 0.00 | 0.00 | 0.348473E+10 | 0.348473E+10 | 72985.60 | 04-OCT-15:00 | 72985.60 | 0.04 |
November | 0.00 | 0.00 | 0.628742E+09 | 0.628742E+09 | 34984.32 | 04-NOV-14:00 | 34984.32 | 0.01 |
December | 0.00 | 0.00 | 85.53 | 85.53 | 0.29 | 12-DEC-04:50 | 0.29 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.207290E+12 | 0.204031E+12 | 0.16 | |||
Minimum of Months | 0.00 | 0.00 | 85.53 | 85.53 | 0.29 | 0.29 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.702697E+11 | 0.681700E+11 | 170605.04 | 139657.52 | 0.52 |
Report: CoilReportMonthly
For: CAV_BAS COOLING COIL
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 3148880.28 | 3148880.28 | 10309.93 | 11-JAN-05:12 | 10309.93 | 0.00 |
February | 0.00 | 0.00 | 0.460191E+09 | 0.449769E+09 | 51108.07 | 24-FEB-06:02 | 34390.31 | 0.00 |
March | 0.00 | 0.00 | 0.129088E+09 | 0.117366E+09 | 41243.35 | 10-MAR-06:03 | 18805.70 | 0.00 |
April | 0.00 | 0.00 | 0.423654E+10 | 0.423051E+10 | 63625.30 | 27-APR-16:00 | 63625.30 | 0.04 |
May | 0.00 | 0.00 | 0.800834E+10 | 0.798632E+10 | 62338.51 | 15-MAY-16:00 | 62338.51 | 0.11 |
June | 0.00 | 0.00 | 0.167524E+11 | 0.166860E+11 | 67060.83 | 12-JUN-04:12 | 35653.62 | 0.21 |
July | 0.00 | 0.00 | 0.314443E+11 | 0.311055E+11 | 119093.84 | 30-JUL-16:50 | 104399.28 | 0.35 |
August | 0.00 | 0.00 | 0.440211E+11 | 0.433886E+11 | 121185.98 | 13-AUG-16:54 | 106961.08 | 0.42 |
September | 0.00 | 0.00 | 0.129255E+11 | 0.128028E+11 | 68446.80 | 01-SEP-04:12 | 43142.70 | 0.21 |
October | 0.00 | 0.00 | 0.170447E+10 | 0.168239E+10 | 43546.39 | 26-OCT-04:12 | 27688.68 | 0.02 |
November | 0.00 | 0.00 | 0.282626E+09 | 0.267546E+09 | 49153.86 | 04-NOV-04:12 | 29268.49 | 0.01 |
December | 0.00 | 0.00 | 7063244.24 | 6377953.92 | 19265.78 | 16-DEC-06:03 | 14697.18 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.119975E+12 | 0.118726E+12 | 0.11 | |||
Minimum of Months | 0.00 | 0.00 | 3148880.28 | 3148880.28 | 10309.93 | 10309.93 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.440211E+11 | 0.433886E+11 | 121185.98 | 106961.08 | 0.42 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BASEMENT COOLING COIL
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.437180E+10 | 0.437169E+10 | 3024.82 | 09-JAN-12:00 | 3024.82 | 0.00 |
February | 0.00 | 0.00 | 0.695535E+10 | 0.688840E+10 | 39713.26 | 27-FEB-15:00 | 39713.26 | 0.00 |
March | 0.00 | 0.00 | 0.142125E+11 | 0.134955E+11 | 145247.12 | 18-MAR-16:00 | 145247.12 | 0.00 |
April | 0.00 | 0.00 | 0.104986E+12 | 0.964204E+11 | 389000.90 | 27-APR-15:00 | 389000.90 | 0.00 |
May | 0.00 | 0.00 | 0.514281E+10 | 0.484263E+10 | 88315.05 | 05-MAY-16:00 | 76341.97 | 0.00 |
June | 0.00 | 0.00 | 0.416097E+11 | 0.394260E+11 | 211667.88 | 28-JUN-17:00 | 211667.88 | 0.00 |
July | 0.00 | 0.00 | 0.251124E+12 | 0.209726E+12 | 355718.64 | 27-JUL-16:00 | 289768.93 | 0.00 |
August | 0.00 | 0.00 | 0.626898E+12 | 0.485673E+12 | 413266.82 | 29-AUG-13:00 | 358925.27 | 0.00 |
September | 0.00 | 0.00 | 0.469211E+10 | 0.393888E+10 | 90510.36 | 22-SEP-16:00 | 76937.83 | 0.00 |
October | 0.00 | 0.00 | 0.453200E+10 | 0.439617E+10 | 87624.13 | 04-OCT-15:00 | 87624.13 | 0.00 |
November | 0.00 | 0.00 | 0.116969E+11 | 0.976269E+10 | 203494.38 | 04-NOV-15:00 | 152901.48 | 0.00 |
December | 0.00 | 0.00 | 0.139065E+11 | 0.127554E+11 | 50881.23 | 14-DEC-12:00 | 49466.51 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.109013E+13 | 0.891697E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.437180E+10 | 0.393888E+10 | 3024.82 | 3024.82 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.626898E+12 | 0.485673E+12 | 413266.82 | 389000.90 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BOT COOLING COIL
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.399559E+10 | 0.399526E+10 | 2300.84 | 05-JAN-16:10 | 2300.84 | 0.00 |
February | 0.00 | 0.00 | 0.877191E+10 | 0.876152E+10 | 4593.96 | 27-FEB-16:20 | 4579.89 | 0.00 |
March | 0.00 | 0.00 | 0.154069E+11 | 0.153986E+11 | 7576.47 | 31-MAR-24:00 | 7576.47 | 0.00 |
April | 0.00 | 0.00 | 0.201714E+11 | 0.201582E+11 | 8905.82 | 26-APR-18:00 | 8905.82 | 0.00 |
May | 0.00 | 0.00 | 0.578728E+10 | 0.575028E+10 | 4077.32 | 31-MAY-24:00 | 4069.18 | 0.00 |
June | 0.00 | 0.00 | 0.107530E+11 | 0.106993E+11 | 5948.48 | 30-JUN-24:00 | 5942.30 | 0.00 |
July | 0.00 | 0.00 | 0.165028E+11 | 0.163862E+11 | 7880.91 | 31-JUL-23:55 | 7847.66 | 0.00 |
August | 0.00 | 0.00 | 0.215475E+11 | 0.213904E+11 | 9445.25 | 06-AUG-18:43 | 9445.25 | 0.00 |
September | 0.00 | 0.00 | 0.578331E+10 | 0.569098E+10 | 3906.72 | 30-SEP-24:00 | 3905.53 | 0.00 |
October | 0.00 | 0.00 | 0.105283E+11 | 0.105056E+11 | 5575.83 | 31-OCT-24:00 | 5575.83 | 0.00 |
November | 0.00 | 0.00 | 0.147607E+11 | 0.147371E+11 | 6433.73 | 04-NOV-16:00 | 6312.73 | 0.00 |
December | 0.00 | 0.00 | 0.200623E+11 | 0.200599E+11 | 8213.93 | 10-DEC-15:50 | 8213.93 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.154071E+12 | 0.153533E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.399559E+10 | 0.399526E+10 | 2300.84 | 2300.84 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.215475E+11 | 0.213904E+11 | 9445.25 | 9445.25 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER MID COOLING COIL
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.154744E+11 | 0.154737E+11 | 18437.12 | 05-JAN-16:20 | 18437.12 | 0.00 |
February | 0.00 | 0.00 | 0.661330E+11 | 0.660312E+11 | 42081.65 | 27-FEB-16:20 | 41929.57 | 0.00 |
March | 0.00 | 0.00 | 0.132616E+12 | 0.132533E+12 | 66740.27 | 31-MAR-23:40 | 66740.27 | 0.00 |
April | 0.00 | 0.00 | 0.182830E+12 | 0.182696E+12 | 85041.56 | 26-APR-18:00 | 85041.56 | 0.00 |
May | 0.00 | 0.00 | 0.485722E+11 | 0.482100E+11 | 38069.38 | 31-MAY-23:30 | 37926.84 | 0.00 |
June | 0.00 | 0.00 | 0.977718E+11 | 0.972400E+11 | 55792.96 | 30-JUN-24:00 | 55726.90 | 0.00 |
July | 0.00 | 0.00 | 0.154309E+12 | 0.153157E+12 | 76054.54 | 31-JUL-23:55 | 75730.68 | 0.00 |
August | 0.00 | 0.00 | 0.202997E+12 | 0.201440E+12 | 88649.03 | 06-AUG-18:32 | 88649.03 | 0.00 |
September | 0.00 | 0.00 | 0.492305E+11 | 0.483295E+11 | 34700.28 | 30-SEP-23:40 | 34677.86 | 0.00 |
October | 0.00 | 0.00 | 0.880421E+11 | 0.878172E+11 | 48436.32 | 04-OCT-16:50 | 48436.32 | 0.00 |
November | 0.00 | 0.00 | 0.122684E+12 | 0.122449E+12 | 58920.62 | 04-NOV-16:00 | 57748.11 | 0.00 |
December | 0.00 | 0.00 | 0.168447E+12 | 0.168423E+12 | 74818.78 | 05-DEC-15:50 | 74818.78 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.132911E+13 | 0.132380E+13 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.154744E+11 | 0.154737E+11 | 18437.12 | 18437.12 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.202997E+12 | 0.201440E+12 | 88649.03 | 88649.03 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER TOP COOLING COIL
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.698593E+09 | 0.698556E+09 | 1783.26 | 05-JAN-16:20 | 1783.26 | 0.00 |
February | 0.00 | 0.00 | 0.518537E+10 | 0.517528E+10 | 4187.39 | 27-FEB-16:30 | 4165.13 | 0.00 |
March | 0.00 | 0.00 | 0.120704E+11 | 0.120621E+11 | 6248.31 | 31-MAR-23:20 | 6248.31 | 0.00 |
April | 0.00 | 0.00 | 0.175261E+11 | 0.175129E+11 | 8586.18 | 26-APR-18:00 | 8586.18 | 0.00 |
May | 0.00 | 0.00 | 0.433752E+10 | 0.430154E+10 | 3736.97 | 31-MAY-23:20 | 3720.24 | 0.00 |
June | 0.00 | 0.00 | 0.954232E+10 | 0.948911E+10 | 5483.66 | 30-JUN-23:40 | 5476.93 | 0.00 |
July | 0.00 | 0.00 | 0.152836E+11 | 0.151683E+11 | 7582.44 | 31-JUL-23:03 | 7534.49 | 0.00 |
August | 0.00 | 0.00 | 0.201246E+11 | 0.199691E+11 | 8979.46 | 06-AUG-18:23 | 8979.46 | 0.00 |
September | 0.00 | 0.00 | 0.440774E+10 | 0.431876E+10 | 3200.18 | 10-SEP-17:25 | 3188.56 | 0.00 |
October | 0.00 | 0.00 | 0.771641E+10 | 0.769426E+10 | 4879.72 | 04-OCT-16:50 | 4879.72 | 0.00 |
November | 0.00 | 0.00 | 0.108063E+11 | 0.107831E+11 | 5825.12 | 04-NOV-16:00 | 5708.43 | 0.00 |
December | 0.00 | 0.00 | 0.151001E+11 | 0.150977E+11 | 7333.51 | 05-DEC-16:00 | 7333.51 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.122799E+12 | 0.122271E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.698593E+09 | 0.698556E+09 | 1783.26 | 1783.26 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.201246E+11 | 0.199691E+11 | 8979.46 | 8979.46 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 104863.16 | 2187605.85 | 02-JAN-05:11 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 61134.96 | 1532401.55 | 21-FEB-06:03 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 17374.98 | 1478114.30 | 06-MAR-05:11 |
April | 0.00 | 0.00 | 01-APR-00:10 | 6212.92 | 1171044.54 | 19-APR-05:02 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 950.02 | 768105.06 | 18-MAY-05:03 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 82.19 | 70083.82 | 14-JUN-05:03 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 3.07 | 1375.67 | 03-AUG-05:10 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 290.72 | 84679.58 | 27-SEP-05:03 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 6961.45 | 1183483.38 | 28-OCT-05:02 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 36878.67 | 1452715.99 | 27-NOV-05:11 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 73357.14 | 1391701.66 | 18-DEC-05:11 |
Annual Sum or Average | 0.00 | 25546.63 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.00 | 0.00 | 104863.16 | 2187605.85 |
Report: PlantLoopDemandReportMonthly
For: COOLSYS1_SUPPLY
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 89.11 | 4863.57 | 11-JAN-20:00 | 0.00 | 0.00 | 01-JAN-00:03 |
February | 3246.09 | 575114.40 | 27-FEB-16:00 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 4176.79 | 356990.40 | 18-MAR-16:00 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 42688.10 | 1449612.78 | 27-APR-14:40 | 0.00 | 0.00 | 01-APR-00:10 |
May | 74982.74 | 1390150.39 | 04-MAY-13:50 | 0.00 | 0.00 | 01-MAY-00:05 |
June | 145340.75 | 1472689.14 | 27-JUN-13:50 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 251905.63 | 1758741.44 | 31-JUL-16:00 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 335779.54 | 1858956.08 | 29-AUG-14:30 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 124736.39 | 1553867.30 | 08-SEP-15:20 | 0.00 | 0.00 | 01-SEP-00:03 |
October | 19743.70 | 1032648.88 | 04-OCT-15:00 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 3454.20 | 452853.02 | 04-NOV-14:10 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 256.18 | 29359.45 | 16-DEC-06:03 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 84581.97 | 0.00 | ||||
Minimum of Months | 89.11 | 4863.57 | 0.00 | 0.00 | ||
Maximum of Months | 335779.54 | 1858956.08 | 0.00 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: COOLSYS1_DEMAND
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.04 | 470.58 | 11-JAN-06:03 | 0.00 | 0.00 | 01-JAN-00:03 |
February | 2958.48 | 603275.25 | 27-FEB-16:00 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 3764.88 | 353435.05 | 18-MAR-16:00 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 41948.53 | 1526463.15 | 27-APR-11:50 | 0.00 | 0.00 | 01-APR-00:10 |
May | 73626.40 | 1329364.12 | 04-MAY-13:40 | 0.00 | 0.00 | 01-MAY-00:05 |
June | 143255.77 | 1395509.63 | 22-JUN-14:40 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 248955.84 | 1752621.00 | 31-JUL-16:00 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 331711.49 | 1913577.54 | 13-AUG-15:31 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 122884.05 | 1485688.72 | 14-SEP-13:00 | 0.00 | 0.00 | 01-SEP-00:03 |
October | 19158.14 | 1031025.35 | 04-OCT-15:00 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 3089.93 | 448397.31 | 04-NOV-14:00 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 6.62 | 41173.66 | 16-DEC-06:03 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 83320.85 | 0.00 | ||||
Minimum of Months | 0.04 | 470.58 | 0.00 | 0.00 | ||
Maximum of Months | 331711.49 | 1913577.54 | 0.00 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SINGLE WATER PLANT LOOP
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 15694.31 | 34041.12 | 05-JAN-16:20 | 0.00 | 0.00 | 01-JAN-00:03 |
February | 49345.74 | 243088.36 | 27-FEB-15:00 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 85887.28 | 519279.26 | 18-MAR-16:00 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 191747.42 | 1410745.33 | 27-APR-15:10 | 0.00 | 0.00 | 01-APR-00:10 |
May | 53393.18 | 564490.89 | 05-MAY-16:00 | 0.00 | 0.00 | 01-MAY-00:05 |
June | 129732.65 | 941555.29 | 28-JUN-17:00 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 353658.17 | 1414495.07 | 24-JUL-15:00 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 676326.47 | 1687100.07 | 10-AUG-17:00 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 60240.44 | 567623.60 | 22-SEP-16:00 | 0.00 | 0.00 | 01-SEP-00:03 |
October | 57379.09 | 434677.19 | 04-OCT-15:00 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 82006.59 | 651047.26 | 04-NOV-15:00 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 104277.09 | 171379.46 | 14-DEC-12:00 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 156270.07 | 0.00 | ||||
Minimum of Months | 15694.31 | 34041.12 | 0.00 | 0.00 | ||
Maximum of Months | 676326.47 | 1687100.07 | 0.00 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 15524.86 | 52057.49 | 31-JAN-12:40 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 15707.65 | 52120.04 | 10-FEB-12:40 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 16426.34 | 51947.12 | 01-MAR-12:30 |
April | 0.00 | 0.00 | 01-APR-00:10 | 15095.95 | 50807.63 | 03-APR-11:50 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 15027.11 | 49253.29 | 01-MAY-12:00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 14828.71 | 47339.58 | 01-JUN-11:20 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 13417.13 | 45735.84 | 03-JUL-11:30 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 14439.89 | 45070.72 | 31-AUG-12:00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 13796.63 | 46042.71 | 29-SEP-11:30 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 14171.17 | 47778.44 | 31-OCT-11:30 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 14865.40 | 49631.27 | 30-NOV-13:00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 14850.68 | 51134.55 | 29-DEC-13:00 |
Annual Sum or Average | 0.00 | 14841.06 | ||||
Minimum of Months | 0.00 | 0.00 | 13417.13 | 45070.72 | ||
Maximum of Months | 0.00 | 0.00 | 16426.34 | 52120.04 |
Report: PlantLoopDemandReportMonthly
For: TOWERWATERSYS
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.01 | 33.27 | 25-JAN-15:40 | 641.87 | 123964.55 | 15-JAN-19:30 |
February | 3526.79 | 640622.71 | 27-FEB-16:00 | 1719.24 | 132455.19 | 08-FEB-06:30 |
March | 4320.69 | 425917.38 | 18-MAR-16:00 | 2057.89 | 130813.12 | 01-MAR-07:00 |
April | 52426.42 | 2288366.62 | 27-APR-14:00 | 1557.79 | 111427.56 | 12-APR-06:00 |
May | 91908.03 | 2208737.76 | 05-MAY-13:00 | 969.76 | 95540.22 | 17-MAY-19:10 |
June | 178322.67 | 2282512.85 | 28-JUN-14:20 | 737.21 | 68187.21 | 24-JUN-08:70 |
July | 321157.23 | 3209054.92 | 31-JUL-16:00 | 1085.86 | 75282.22 | 03-JUL-10:10 |
August | 459470.15 | 3671794.69 | 29-AUG-14:30 | 956.74 | 63504.12 | 03-AUG-19:50 |
September | 155042.90 | 2357741.26 | 14-SEP-16:00 | 644.84 | 70883.36 | 29-SEP-10:00 |
October | 22447.53 | 1179472.44 | 04-OCT-15:00 | 962.66 | 98240.57 | 11-OCT-06:00 |
November | 3684.84 | 532732.23 | 04-NOV-14:10 | 1988.46 | 118190.80 | 14-NOV-05:53 |
December | 10.40 | 10109.72 | 16-DEC-06:03 | 1836.36 | 118266.29 | 02-DEC-05:53 |
Annual Sum or Average | 108662.44 | 1259.82 | ||||
Minimum of Months | 0.01 | 33.27 | 641.87 | 63504.12 | ||
Maximum of Months | 459470.15 | 3671794.69 | 2057.89 | 132455.19 |
Report: FanReportMonthly
For: CAV_BAS FAN
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.151257E+11 | 0.77 | 10286.99 | 01-JAN-06:10 | 1.41 |
February | 0.136858E+11 | 0.77 | 10286.99 | 01-FEB-05:11 | 1.40 |
March | 0.161156E+11 | 0.82 | 10286.99 | 01-MAR-04:10 | 1.41 |
April | 0.147701E+11 | 0.78 | 10286.99 | 01-APR-04:12 | 1.41 |
May | 0.158234E+11 | 0.81 | 10286.99 | 01-MAY-00:40 | 1.40 |
June | 0.158934E+11 | 0.84 | 10286.99 | 01-JUN-04:12 | 1.41 |
July | 0.158280E+11 | 0.80 | 10286.99 | 01-JUL-04:12 | 1.40 |
August | 0.169692E+11 | 0.86 | 10286.99 | 01-AUG-04:12 | 1.40 |
September | 0.157607E+11 | 0.83 | 10286.99 | 01-SEP-04:12 | 1.40 |
October | 0.156079E+11 | 0.80 | 10286.99 | 02-OCT-02:70 | 1.40 |
November | 0.150257E+11 | 0.79 | 10286.99 | 01-NOV-04:12 | 1.40 |
December | 0.148102E+11 | 0.76 | 10286.99 | 01-DEC-05:11 | 1.41 |
Annual Sum or Average | 0.185416E+12 | 0.80 | |||
Minimum of Months | 0.136858E+11 | 0.76 | 10286.99 | 1.40 | |
Maximum of Months | 0.169692E+11 | 0.86 | 10286.99 | 1.41 |
Report: FanReportMonthly
For: VAV_BOT WITH REHEAT FAN
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.388470E+10 | 0.29 | 14362.02 | 09-JAN-06:01 | 1.36 |
February | 0.449590E+10 | 0.33 | 13387.03 | 18-FEB-06:01 | 1.30 |
March | 0.693704E+10 | 0.40 | 13311.27 | 14-MAR-15:00 | 1.29 |
April | 0.878303E+10 | 0.46 | 19922.67 | 27-APR-14:30 | 1.66 |
May | 0.815132E+10 | 0.44 | 16471.66 | 15-MAY-14:30 | 1.48 |
June | 0.985548E+10 | 0.50 | 15948.93 | 28-JUN-15:20 | 1.44 |
July | 0.119989E+11 | 0.56 | 20677.38 | 31-JUL-14:40 | 1.70 |
August | 0.139542E+11 | 0.63 | 22110.51 | 29-AUG-15:00 | 1.77 |
September | 0.830971E+10 | 0.44 | 18550.06 | 11-SEP-14:50 | 1.59 |
October | 0.680998E+10 | 0.39 | 16134.91 | 04-OCT-15:10 | 1.46 |
November | 0.527109E+10 | 0.35 | 11695.45 | 13-NOV-06:01 | 1.20 |
December | 0.513387E+10 | 0.33 | 11695.45 | 18-DEC-06:03 | 1.20 |
Annual Sum or Average | 0.935852E+11 | 0.43 | |||
Minimum of Months | 0.388470E+10 | 0.29 | 11695.45 | 1.20 | |
Maximum of Months | 0.139542E+11 | 0.63 | 22110.51 | 1.77 |
Report: FanReportMonthly
For: VAV_MID WITH REHEAT FAN
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.317013E+11 | 0.30 | 61569.79 | 02-JAN-05:11 | 0.86 |
February | 0.313418E+11 | 0.30 | 95893.30 | 28-FEB-06:03 | 1.11 |
March | 0.430148E+11 | 0.33 | 157201.14 | 23-MAR-05:02 | 1.51 |
April | 0.495154E+11 | 0.35 | 155920.84 | 18-APR-05:02 | 1.51 |
May | 0.623504E+11 | 0.40 | 137946.97 | 04-MAY-14:50 | 1.39 |
June | 0.710497E+11 | 0.44 | 142216.20 | 28-JUN-15:20 | 1.41 |
July | 0.826392E+11 | 0.45 | 167732.39 | 31-JUL-14:50 | 1.56 |
August | 0.948609E+11 | 0.49 | 190528.25 | 10-AUG-15:10 | 1.70 |
September | 0.668688E+11 | 0.41 | 168478.61 | 14-SEP-15:00 | 1.57 |
October | 0.460331E+11 | 0.33 | 135705.32 | 04-OCT-15:30 | 1.38 |
November | 0.324906E+11 | 0.29 | 96415.36 | 08-NOV-06:02 | 1.11 |
December | 0.314710E+11 | 0.29 | 44664.70 | 06-DEC-14:10 | 0.72 |
Annual Sum or Average | 0.643337E+12 | 0.37 | |||
Minimum of Months | 0.313418E+11 | 0.29 | 44664.70 | 0.72 | |
Maximum of Months | 0.948609E+11 | 0.49 | 190528.25 | 1.70 |
Report: FanReportMonthly
For: VAV_TOP WITH REHEAT FAN
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.369878E+10 | 0.34 | 5401.64 | 21-JAN-06:01 | 0.75 |
February | 0.324071E+10 | 0.32 | 5401.64 | 06-FEB-05:11 | 0.75 |
March | 0.361401E+10 | 0.31 | 6492.76 | 14-MAR-15:40 | 0.83 |
April | 0.420592E+10 | 0.32 | 16447.78 | 27-APR-14:30 | 1.44 |
May | 0.537230E+10 | 0.35 | 14895.74 | 15-MAY-15:10 | 1.36 |
June | 0.641593E+10 | 0.39 | 15611.88 | 28-JUN-15:20 | 1.40 |
July | 0.772924E+10 | 0.41 | 18309.38 | 31-JUL-15:00 | 1.54 |
August | 0.865589E+10 | 0.44 | 20337.55 | 10-AUG-15:10 | 1.65 |
September | 0.558523E+10 | 0.35 | 16495.43 | 14-SEP-15:00 | 1.44 |
October | 0.367582E+10 | 0.29 | 11805.67 | 04-OCT-15:20 | 1.18 |
November | 0.297306E+10 | 0.28 | 5401.64 | 13-NOV-05:01 | 0.75 |
December | 0.324804E+10 | 0.30 | 5401.64 | 12-DEC-06:01 | 0.75 |
Annual Sum or Average | 0.584149E+11 | 0.34 | |||
Minimum of Months | 0.297306E+10 | 0.28 | 5401.64 | 0.75 | |
Maximum of Months | 0.865589E+10 | 0.44 | 20337.55 | 1.65 |
Report: FanReportMonthly
For: AIRLOOP DATACENTER BASEMENT SUPPLY FAN
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.959277E+11 | 1.37 | 35815.29 | 01-JAN-00:03 | 1.37 |
February | 0.866444E+11 | 1.37 | 35815.29 | 01-FEB-00:10 | 1.37 |
March | 0.959277E+11 | 1.37 | 35815.29 | 01-MAR-00:10 | 1.37 |
April | 0.928332E+11 | 1.37 | 35815.29 | 01-APR-00:10 | 1.37 |
May | 0.959277E+11 | 1.37 | 35815.29 | 01-MAY-00:05 | 1.37 |
June | 0.928332E+11 | 1.36 | 35815.29 | 01-JUN-00:10 | 1.37 |
July | 0.959277E+11 | 1.36 | 35815.29 | 01-JUL-00:10 | 1.36 |
August | 0.959277E+11 | 1.36 | 35815.29 | 01-AUG-00:10 | 1.36 |
September | 0.928332E+11 | 1.36 | 35815.29 | 01-SEP-00:03 | 1.36 |
October | 0.959277E+11 | 1.37 | 35815.29 | 01-OCT-00:10 | 1.36 |
November | 0.928332E+11 | 1.37 | 35815.29 | 01-NOV-00:10 | 1.37 |
December | 0.959277E+11 | 1.37 | 35815.29 | 01-DEC-00:20 | 1.37 |
Annual Sum or Average | 0.112947E+13 | 1.37 | |||
Minimum of Months | 0.866444E+11 | 1.36 | 35815.29 | 1.36 | |
Maximum of Months | 0.959277E+11 | 1.37 | 35815.29 | 1.37 |
Report: FanReportMonthly
For: AIRLOOP DATACENTER BOT SUPPLY FAN
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.158662E+10 | 0.93 | 592.38 | 01-JAN-00:03 | 0.93 |
February | 0.143307E+10 | 0.93 | 592.38 | 01-FEB-00:10 | 0.93 |
March | 0.158662E+10 | 0.93 | 592.38 | 01-MAR-00:10 | 0.93 |
April | 0.153544E+10 | 0.93 | 592.38 | 01-APR-00:10 | 0.93 |
May | 0.158662E+10 | 0.93 | 592.38 | 01-MAY-00:05 | 0.93 |
June | 0.153544E+10 | 0.93 | 592.38 | 01-JUN-00:20 | 0.93 |
July | 0.158662E+10 | 0.93 | 592.38 | 01-JUL-00:10 | 0.93 |
August | 0.158662E+10 | 0.92 | 592.38 | 01-AUG-00:10 | 0.93 |
September | 0.153544E+10 | 0.93 | 592.38 | 01-SEP-00:07 | 0.93 |
October | 0.158662E+10 | 0.93 | 592.38 | 01-OCT-00:10 | 0.93 |
November | 0.153544E+10 | 0.93 | 592.38 | 01-NOV-00:10 | 0.93 |
December | 0.158662E+10 | 0.93 | 592.38 | 01-DEC-00:10 | 0.93 |
Annual Sum or Average | 0.186811E+11 | 0.93 | |||
Minimum of Months | 0.143307E+10 | 0.92 | 592.38 | 0.93 | |
Maximum of Months | 0.158662E+10 | 0.93 | 592.38 | 0.93 |
Report: FanReportMonthly
For: AIRLOOP DATACENTER MID SUPPLY FAN
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.152637E+11 | 0.93 | 5698.80 | 01-JAN-00:03 | 0.92 |
February | 0.137865E+11 | 0.93 | 5698.80 | 01-FEB-00:10 | 0.93 |
March | 0.152637E+11 | 0.93 | 5698.80 | 01-MAR-00:10 | 0.93 |
April | 0.147713E+11 | 0.93 | 5698.80 | 01-APR-00:10 | 0.93 |
May | 0.152637E+11 | 0.93 | 5698.80 | 01-MAY-00:05 | 0.93 |
June | 0.147713E+11 | 0.93 | 5698.80 | 01-JUN-00:20 | 0.93 |
July | 0.152637E+11 | 0.93 | 5698.80 | 01-JUL-00:10 | 0.93 |
August | 0.152637E+11 | 0.92 | 5698.80 | 01-AUG-00:10 | 0.93 |
September | 0.147713E+11 | 0.93 | 5698.80 | 01-SEP-00:03 | 0.93 |
October | 0.152637E+11 | 0.93 | 5698.80 | 01-OCT-00:30 | 0.93 |
November | 0.147713E+11 | 0.93 | 5698.80 | 01-NOV-00:10 | 0.93 |
December | 0.152637E+11 | 0.93 | 5698.80 | 01-DEC-00:10 | 0.93 |
Annual Sum or Average | 0.179717E+12 | 0.93 | |||
Minimum of Months | 0.137865E+11 | 0.92 | 5698.80 | 0.92 | |
Maximum of Months | 0.152637E+11 | 0.93 | 5698.80 | 0.93 |
Report: FanReportMonthly
For: AIRLOOP DATACENTER TOP SUPPLY FAN
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.154760E+10 | 0.93 | 577.81 | 01-JAN-00:03 | 0.92 |
February | 0.139783E+10 | 0.93 | 577.81 | 01-FEB-00:10 | 0.93 |
March | 0.154760E+10 | 0.93 | 577.81 | 01-MAR-00:10 | 0.93 |
April | 0.149767E+10 | 0.93 | 577.81 | 01-APR-00:10 | 0.93 |
May | 0.154760E+10 | 0.93 | 577.81 | 01-MAY-00:05 | 0.93 |
June | 0.149767E+10 | 0.93 | 577.81 | 01-JUN-00:10 | 0.93 |
July | 0.154760E+10 | 0.93 | 577.81 | 01-JUL-00:10 | 0.93 |
August | 0.154760E+10 | 0.92 | 577.81 | 01-AUG-00:10 | 0.93 |
September | 0.149767E+10 | 0.93 | 577.81 | 01-SEP-00:03 | 0.93 |
October | 0.154760E+10 | 0.93 | 577.81 | 01-OCT-00:10 | 0.93 |
November | 0.149767E+10 | 0.93 | 577.81 | 01-NOV-00:10 | 0.93 |
December | 0.154760E+10 | 0.93 | 577.81 | 01-DEC-00:10 | 0.93 |
Annual Sum or Average | 0.182217E+11 | 0.93 | |||
Minimum of Months | 0.139783E+10 | 0.92 | 577.81 | 0.92 | |
Maximum of Months | 0.154760E+10 | 0.93 | 577.81 | 0.93 |
Report: PumpReportMonthly
For: HEATSYS1 PUMP
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.114383E+10 | 0.102945E+10 | 4447.21 | 17-JAN-06:03 | 4002.49 | 4002.49 | 46.14 | 10.31 |
February | 0.606124E+09 | 0.545512E+09 | 4426.18 | 21-FEB-06:03 | 3983.56 | 3983.56 | 45.75 | 10.11 |
March | 0.187065E+09 | 0.168359E+09 | 3757.90 | 06-MAR-06:02 | 3382.11 | 3382.11 | 42.35 | 6.37 |
April | 64126961.15 | 57714265.03 | 3534.87 | 19-APR-05:02 | 3181.38 | 3181.38 | 32.49 | 5.66 |
May | 9995125.61 | 8995613.05 | 2621.12 | 18-MAY-05:03 | 2359.01 | 2359.01 | 29.86 | 3.52 |
June | 810414.41 | 729372.97 | 261.69 | 14-JUN-05:03 | 235.52 | 235.52 | 20.51 | 0.27 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 20.70 | 0.00 |
August | 31449.16 | 28304.25 | 5.26 | 03-AUG-05:10 | 4.73 | 4.73 | 20.69 | 0.01 |
September | 2860744.44 | 2574669.99 | 313.93 | 27-SEP-05:03 | 282.54 | 282.54 | 20.33 | 0.33 |
October | 72952963.76 | 65657667.39 | 3507.64 | 28-OCT-05:02 | 3156.88 | 3156.88 | 31.26 | 5.58 |
November | 0.380468E+09 | 0.342421E+09 | 3771.31 | 13-NOV-06:01 | 3394.18 | 3394.18 | 37.12 | 6.43 |
December | 0.794398E+09 | 0.714959E+09 | 3842.31 | 26-DEC-06:03 | 3458.07 | 3458.07 | 45.44 | 6.67 |
Annual Sum or Average | 0.326267E+10 | 0.293640E+10 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.33 | 0.00 | |
Maximum of Months | 0.114383E+10 | 0.102945E+10 | 4447.21 | 4002.49 | 4002.49 | 46.14 | 10.31 |
Report: PumpReportMonthly
For: COOLSYS1 PUMP SECONDARY
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 1329.96 | 1196.97 | 4.36 | 11-JAN-05:12 | 3.92 | 3.92 | 6.70 | 1.06 |
February | 2843809.46 | 2559428.52 | 428.29 | 27-FEB-16:00 | 385.46 | 385.46 | 6.70 | 19.97 |
March | 2101654.05 | 1891488.65 | 70.48 | 18-MAR-16:00 | 63.43 | 63.43 | 6.70 | 7.60 |
April | 0.121076E+09 | 0.108969E+09 | 5668.24 | 27-APR-11:50 | 5101.42 | 5101.42 | 8.96 | 63.46 |
May | 0.150192E+09 | 0.135173E+09 | 4292.89 | 04-MAY-15:00 | 3863.60 | 3863.60 | 6.72 | 56.54 |
June | 0.374547E+09 | 0.337093E+09 | 4967.27 | 27-JUN-15:00 | 4470.54 | 4470.54 | 6.72 | 60.09 |
July | 0.597147E+09 | 0.537433E+09 | 6754.76 | 19-JUL-14:20 | 6079.28 | 6079.28 | 8.29 | 68.19 |
August | 0.916087E+09 | 0.824479E+09 | 4873.52 | 10-AUG-16:00 | 4386.17 | 4386.17 | 6.72 | 59.62 |
September | 0.277302E+09 | 0.249571E+09 | 6995.58 | 08-SEP-15:40 | 6296.02 | 6296.02 | 6.72 | 69.17 |
October | 26129712.20 | 23516740.98 | 1074.08 | 04-OCT-13:40 | 966.67 | 966.67 | 6.71 | 30.86 |
November | 2512978.92 | 2261681.03 | 171.87 | 04-NOV-14:10 | 154.68 | 154.68 | 6.70 | 12.51 |
December | 4275.52 | 3847.97 | 10.61 | 16-DEC-06:03 | 9.55 | 9.55 | 6.70 | 2.16 |
Annual Sum or Average | 0.246995E+10 | 0.222295E+10 | ||||||
Minimum of Months | 1329.96 | 1196.97 | 4.36 | 3.92 | 3.92 | 6.70 | 1.06 | |
Maximum of Months | 0.916087E+09 | 0.824479E+09 | 6995.58 | 6296.02 | 6296.02 | 8.96 | 69.17 |
Report: PumpReportMonthly
For: COOLSYS1 CHILLER1 PUMP
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.265740E+09 | 0.239166E+09 | 5399.02 | 11-JAN-05:12 | 4859.12 | 4859.12 | 6.71 | 47.76 |
February | 0.777922E+09 | 0.700130E+09 | 5399.02 | 01-FEB-05:11 | 4859.12 | 4859.12 | 6.72 | 47.76 |
March | 0.122952E+10 | 0.110657E+10 | 5399.02 | 01-MAR-05:02 | 4859.12 | 4859.12 | 6.72 | 47.76 |
April | 0.231288E+10 | 0.208159E+10 | 5399.02 | 01-APR-05:03 | 4859.12 | 4859.12 | 6.72 | 47.76 |
May | 0.386527E+10 | 0.347874E+10 | 5399.02 | 01-MAY-04:12 | 4859.12 | 4859.12 | 6.91 | 47.76 |
June | 0.601405E+10 | 0.541265E+10 | 5399.02 | 01-JUN-04:12 | 4859.12 | 4859.12 | 6.89 | 47.76 |
July | 0.849119E+10 | 0.764207E+10 | 5399.02 | 01-JUL-04:12 | 4859.12 | 4859.12 | 7.27 | 47.76 |
August | 0.946463E+10 | 0.851817E+10 | 5399.02 | 01-AUG-00:23 | 4859.12 | 4859.12 | 6.78 | 47.76 |
September | 0.508275E+10 | 0.457447E+10 | 5399.02 | 01-SEP-04:12 | 4859.12 | 4859.12 | 7.59 | 47.76 |
October | 0.178538E+10 | 0.160684E+10 | 5399.02 | 01-OCT-12:32 | 4859.12 | 4859.12 | 6.74 | 47.76 |
November | 0.105412E+10 | 0.948705E+09 | 5399.02 | 01-NOV-04:12 | 4859.12 | 4859.12 | 6.87 | 47.76 |
December | 0.742691E+09 | 0.668422E+09 | 5399.02 | 01-DEC-11:40 | 4859.12 | 4859.12 | 6.72 | 47.76 |
Annual Sum or Average | 0.410861E+11 | 0.369775E+11 | ||||||
Minimum of Months | 0.265740E+09 | 0.239166E+09 | 5399.02 | 4859.12 | 4859.12 | 6.71 | 47.76 | |
Maximum of Months | 0.946463E+10 | 0.851817E+10 | 5399.02 | 4859.12 | 4859.12 | 7.59 | 47.76 |
Report: PumpReportMonthly
For: COOLSYS1 CHILLER2 PUMP
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 | 6.70 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 6.72 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 6.72 | 0.00 |
April | 0.152252E+09 | 0.137027E+09 | 5399.02 | 26-APR-13:40 | 4859.12 | 4859.12 | 11.98 | 23.88 |
May | 0.165210E+09 | 0.148689E+09 | 5399.02 | 04-MAY-13:20 | 4859.12 | 4859.12 | 12.89 | 23.88 |
June | 0.340138E+09 | 0.306124E+09 | 5399.02 | 09-JUN-14:50 | 4859.12 | 4859.12 | 12.16 | 23.88 |
July | 0.819571E+09 | 0.737614E+09 | 5399.02 | 06-JUL-16:00 | 4859.12 | 4859.12 | 12.39 | 23.88 |
August | 0.176224E+10 | 0.158602E+10 | 5399.02 | 07-AUG-10:30 | 4859.12 | 4859.12 | 12.40 | 23.88 |
September | 0.408166E+09 | 0.367349E+09 | 5399.02 | 08-SEP-15:10 | 4859.12 | 4859.12 | 13.45 | 23.88 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 6.74 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 6.72 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 6.72 | 0.00 |
Annual Sum or Average | 0.364758E+10 | 0.328282E+10 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.70 | 0.00 | |
Maximum of Months | 0.176224E+10 | 0.158602E+10 | 5399.02 | 4859.12 | 4859.12 | 13.45 | 23.88 |
Report: PumpReportMonthly
For: PLANT CIRC PUMP
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.916780E+10 | 0.825102E+10 | 3422.86 | 01-JAN-00:03 | 3080.58 | 3080.58 | 18.48 | 14.30 |
February | 0.828059E+10 | 0.745253E+10 | 3422.86 | 01-FEB-00:10 | 3080.58 | 3080.58 | 19.18 | 14.30 |
March | 0.916780E+10 | 0.825102E+10 | 3422.86 | 01-MAR-00:10 | 3080.58 | 3080.58 | 19.93 | 14.30 |
April | 0.887206E+10 | 0.798486E+10 | 3422.86 | 01-APR-00:10 | 3080.58 | 3080.58 | 20.47 | 14.30 |
May | 0.916780E+10 | 0.825102E+10 | 3422.86 | 01-MAY-00:05 | 3080.58 | 3080.58 | 18.93 | 14.30 |
June | 0.887206E+10 | 0.798486E+10 | 3422.86 | 01-JUN-00:10 | 3080.58 | 3080.58 | 19.53 | 14.30 |
July | 0.916780E+10 | 0.825102E+10 | 3422.86 | 01-JUL-00:10 | 3080.58 | 3080.58 | 20.08 | 14.30 |
August | 0.916780E+10 | 0.825102E+10 | 3422.86 | 01-AUG-00:10 | 3080.58 | 3080.58 | 28.07 | 14.30 |
September | 0.887206E+10 | 0.798486E+10 | 3422.86 | 01-SEP-00:03 | 3080.58 | 3080.58 | 19.03 | 14.30 |
October | 0.916780E+10 | 0.825102E+10 | 3422.86 | 01-OCT-00:10 | 3080.58 | 3080.58 | 19.43 | 14.30 |
November | 0.887206E+10 | 0.798486E+10 | 3422.86 | 01-NOV-00:10 | 3080.58 | 3080.58 | 19.85 | 14.30 |
December | 0.916780E+10 | 0.825102E+10 | 3422.86 | 01-DEC-00:10 | 3080.58 | 3080.58 | 20.41 | 14.30 |
Annual Sum or Average | 0.107943E+12 | 0.971491E+11 | ||||||
Minimum of Months | 0.828059E+10 | 0.745253E+10 | 3422.86 | 3080.58 | 3080.58 | 18.48 | 14.30 | |
Maximum of Months | 0.916780E+10 | 0.825102E+10 | 3422.86 | 3080.58 | 3080.58 | 28.07 | 14.30 |
Report: PumpReportMonthly
For: SWHSYS1 PUMP
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.112905E+09 | 33871561.48 | 56.21 | 01-JAN-06:05 | 16.86 | 16.86 | 55.75 | 0.44 |
February | 0.101979E+09 | 30593668.43 | 56.21 | 01-FEB-06:02 | 16.86 | 16.86 | 56.38 | 0.44 |
March | 0.112905E+09 | 33871561.48 | 56.21 | 01-MAR-06:02 | 16.86 | 16.86 | 56.25 | 0.44 |
April | 0.109263E+09 | 32778930.46 | 56.21 | 01-APR-05:03 | 16.86 | 16.86 | 56.44 | 0.44 |
May | 0.112905E+09 | 33871561.48 | 56.21 | 01-MAY-05:03 | 16.86 | 16.86 | 55.63 | 0.44 |
June | 0.109263E+09 | 32778930.46 | 56.21 | 01-JUN-05:03 | 16.86 | 16.86 | 55.92 | 0.44 |
July | 0.112905E+09 | 33871561.48 | 56.21 | 01-JUL-05:03 | 16.86 | 16.86 | 56.70 | 0.44 |
August | 0.112905E+09 | 33871561.48 | 56.21 | 01-AUG-05:03 | 16.86 | 16.86 | 56.81 | 0.44 |
September | 0.109263E+09 | 32778930.46 | 56.21 | 01-SEP-05:03 | 16.86 | 16.86 | 56.92 | 0.44 |
October | 0.112905E+09 | 33871561.48 | 56.21 | 01-OCT-05:10 | 16.86 | 16.86 | 55.94 | 0.44 |
November | 0.109263E+09 | 32778930.46 | 56.21 | 01-NOV-05:03 | 16.86 | 16.86 | 56.66 | 0.44 |
December | 0.112905E+09 | 33871561.48 | 56.21 | 01-DEC-06:03 | 16.86 | 16.86 | 56.61 | 0.44 |
Annual Sum or Average | 0.132937E+10 | 0.398810E+09 | ||||||
Minimum of Months | 0.101979E+09 | 30593668.43 | 56.21 | 16.86 | 16.86 | 55.63 | 0.44 | |
Maximum of Months | 0.112905E+09 | 33871561.48 | 56.21 | 16.86 | 16.86 | 56.92 | 0.44 |
Report: PumpReportMonthly
For: TOWERWATERSYS PUMP
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.685439E+09 | 0.616895E+09 | 13927.50 | 25-JAN-15:40 | 12534.75 | 12534.75 | 21.10 | 56.44 |
February | 0.200694E+10 | 0.180625E+10 | 13954.73 | 27-FEB-16:00 | 12559.26 | 12559.26 | 23.82 | 56.44 |
March | 0.317197E+10 | 0.285477E+10 | 13945.59 | 18-MAR-16:00 | 12551.04 | 12551.04 | 22.91 | 56.44 |
April | 0.633972E+10 | 0.570575E+10 | 27955.61 | 27-APR-14:00 | 25160.05 | 25160.05 | 25.95 | 112.89 |
May | 0.103491E+11 | 0.931418E+10 | 27951.65 | 05-MAY-13:00 | 25156.49 | 25156.49 | 25.78 | 112.89 |
June | 0.163360E+11 | 0.147024E+11 | 27955.32 | 28-JUN-14:20 | 25159.79 | 25159.79 | 25.94 | 112.89 |
July | 0.237629E+11 | 0.213866E+11 | 28001.41 | 31-JUL-16:00 | 25201.27 | 25201.27 | 27.90 | 112.89 |
August | 0.286428E+11 | 0.257786E+11 | 28022.73 | 29-AUG-14:30 | 25220.45 | 25220.45 | 28.88 | 112.89 |
September | 0.140396E+11 | 0.126357E+11 | 27959.05 | 14-SEP-16:00 | 25163.15 | 25163.15 | 26.10 | 112.89 |
October | 0.460808E+10 | 0.414727E+10 | 13979.53 | 04-OCT-15:00 | 12581.58 | 12581.58 | 26.10 | 56.44 |
November | 0.271942E+10 | 0.244748E+10 | 13950.14 | 04-NOV-14:10 | 12555.12 | 12555.12 | 23.36 | 56.44 |
December | 0.191566E+10 | 0.172410E+10 | 13927.93 | 16-DEC-06:03 | 12535.14 | 12535.14 | 21.14 | 56.44 |
Annual Sum or Average | 0.114578E+12 | 0.103120E+12 | ||||||
Minimum of Months | 0.685439E+09 | 0.616895E+09 | 13927.50 | 12534.75 | 12534.75 | 21.10 | 56.44 | |
Maximum of Months | 0.286428E+11 | 0.257786E+11 | 28022.73 | 25220.45 | 25220.45 | 28.88 | 112.89 |
Report: CondLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 30.60 | 82.00 | 104863.16 | 2187605.85 | 02-JAN-05:11 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 24.68 | 24.68 | 61134.96 | 1532401.55 | 21-FEB-06:03 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 20.91 | 20.91 | 17374.98 | 1478114.30 | 06-MAR-05:11 |
April | 0.00 | 0.00 | 01-APR-00:10 | 19.99 | 19.99 | 6212.92 | 1171044.54 | 19-APR-05:02 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 23.07 | 23.07 | 950.02 | 768105.06 | 18-MAY-05:03 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 20.33 | 20.33 | 82.19 | 70083.82 | 14-JUN-05:03 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 20.70 | 20.70 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 20.70 | 20.70 | 3.07 | 1375.67 | 03-AUG-05:10 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 20.60 | 20.60 | 290.72 | 84679.58 | 27-SEP-05:03 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 19.91 | 19.91 | 6961.45 | 1183483.38 | 28-OCT-05:02 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 21.86 | 21.86 | 36878.67 | 1452715.99 | 27-NOV-05:11 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 26.03 | 26.03 | 73357.14 | 1391701.66 | 18-DEC-05:11 |
Annual Sum or Average | 0.00 | 25546.63 | ||||||
Minimum of Months | 0.00 | 0.00 | 19.91 | 19.91 | 0.00 | 0.00 | ||
Maximum of Months | 0.00 | 0.00 | 30.60 | 82.00 | 104863.16 | 2187605.85 |
Report: CondLoopDemandReportMonthly
For: COOLSYS1_SUPPLY
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 89.11 | 4863.57 | 11-JAN-20:00 | 6.72 | 6.70 | 0.00 | 0.00 | 01-JAN-00:03 |
February | 3246.09 | 575114.40 | 27-FEB-16:00 | 9.57 | 6.70 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 4176.79 | 356990.40 | 18-MAR-16:00 | 8.48 | 6.70 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 42688.10 | 1449612.78 | 27-APR-14:40 | 10.32 | 6.70 | 0.00 | 0.00 | 01-APR-00:10 |
May | 74982.74 | 1390150.39 | 04-MAY-13:50 | 10.17 | 6.70 | 0.00 | 0.00 | 01-MAY-00:05 |
June | 145340.75 | 1472689.14 | 27-JUN-13:50 | 10.38 | 6.70 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 251905.63 | 1758741.44 | 31-JUL-16:00 | 11.09 | 6.70 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 335779.54 | 1858956.08 | 29-AUG-14:30 | 11.35 | 6.70 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 124736.39 | 1553867.30 | 08-SEP-15:20 | 10.58 | 6.70 | 0.00 | 0.00 | 01-SEP-00:03 |
October | 19743.70 | 1032648.88 | 04-OCT-15:00 | 11.86 | 6.70 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 3454.20 | 452853.02 | 04-NOV-14:10 | 8.96 | 6.70 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 256.18 | 29359.45 | 16-DEC-06:03 | 6.85 | 6.70 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 84581.97 | 0.00 | ||||||
Minimum of Months | 89.11 | 4863.57 | 6.72 | 6.70 | 0.00 | 0.00 | ||
Maximum of Months | 335779.54 | 1858956.08 | 11.86 | 6.70 | 0.00 | 0.00 |
Report: CondLoopDemandReportMonthly
For: COOLSYS1_DEMAND
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.04 | 470.58 | 11-JAN-06:03 | 6.81 | 6.70 | 0.00 | 0.00 | 01-JAN-00:03 |
February | 2958.48 | 603275.25 | 27-FEB-16:00 | 13.92 | 6.70 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 3764.88 | 353435.05 | 18-MAR-16:00 | 17.82 | 6.70 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 41948.53 | 1526463.15 | 27-APR-11:50 | 12.44 | 9.26 | 0.00 | 0.00 | 01-APR-00:10 |
May | 73626.40 | 1329364.12 | 04-MAY-13:40 | 13.14 | 7.97 | 0.00 | 0.00 | 01-MAY-00:05 |
June | 143255.77 | 1395509.63 | 22-JUN-14:40 | 12.80 | 9.12 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 248955.84 | 1752621.00 | 31-JUL-16:00 | 14.36 | 6.70 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 331711.49 | 1913577.54 | 13-AUG-15:31 | 15.23 | 7.61 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 122884.05 | 1485688.72 | 14-SEP-13:00 | 14.18 | 6.70 | 0.00 | 0.00 | 01-SEP-00:03 |
October | 19158.14 | 1031025.35 | 04-OCT-15:00 | 15.50 | 6.70 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 3089.93 | 448397.31 | 04-NOV-14:00 | 15.28 | 6.70 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 6.62 | 41173.66 | 16-DEC-06:03 | 11.25 | 6.70 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 83320.85 | 0.00 | ||||||
Minimum of Months | 0.04 | 470.58 | 6.81 | 6.70 | 0.00 | 0.00 | ||
Maximum of Months | 331711.49 | 1913577.54 | 17.82 | 9.26 | 0.00 | 0.00 |
Report: CondLoopDemandReportMonthly
For: SINGLE WATER PLANT LOOP
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 15694.31 | 34041.12 | 05-JAN-16:20 | 19.02 | 18.33 | 0.00 | 0.00 | 01-JAN-00:03 |
February | 49345.74 | 243088.36 | 27-FEB-15:00 | 23.22 | 20.99 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 85887.28 | 519279.26 | 18-MAR-16:00 | 28.72 | 23.11 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 191747.42 | 1410745.33 | 27-APR-15:10 | 46.08 | 33.14 | 0.00 | 0.00 | 01-APR-00:10 |
May | 53393.18 | 564490.89 | 05-MAY-16:00 | 29.61 | 26.42 | 0.00 | 0.00 | 01-MAY-00:05 |
June | 129732.65 | 941555.29 | 28-JUN-17:00 | 37.02 | 29.91 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 353658.17 | 1414495.07 | 24-JUL-15:00 | 46.16 | 35.50 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 676326.47 | 1687100.07 | 10-AUG-17:00 | 51.36 | 37.99 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 60240.44 | 567623.60 | 22-SEP-16:00 | 29.67 | 26.44 | 0.00 | 0.00 | 01-SEP-00:03 |
October | 57379.09 | 434677.19 | 04-OCT-15:00 | 27.04 | 23.34 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 82006.59 | 651047.26 | 04-NOV-15:00 | 31.32 | 24.26 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 104277.09 | 171379.46 | 14-DEC-12:00 | 21.78 | 18.33 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 156270.07 | 0.00 | ||||||
Minimum of Months | 15694.31 | 34041.12 | 19.02 | 18.33 | 0.00 | 0.00 | ||
Maximum of Months | 676326.47 | 1687100.07 | 51.36 | 37.99 | 0.00 | 0.00 |
Report: CondLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 57.83 | 57.83 | 15524.86 | 52057.49 | 31-JAN-12:40 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 56.93 | 56.93 | 15707.65 | 52120.04 | 10-FEB-12:40 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 56.46 | 56.46 | 16426.34 | 51947.12 | 01-MAR-12:30 |
April | 0.00 | 0.00 | 01-APR-00:10 | 57.03 | 57.03 | 15095.95 | 50807.63 | 03-APR-11:50 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 56.61 | 56.61 | 15027.11 | 49253.29 | 01-MAY-12:00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 56.59 | 56.59 | 14828.71 | 47339.58 | 01-JUN-11:20 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 56.88 | 56.88 | 13417.13 | 45735.84 | 03-JUL-11:30 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 57.31 | 57.31 | 14439.89 | 45070.72 | 31-AUG-12:00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 57.45 | 57.45 | 13796.63 | 46042.71 | 29-SEP-11:30 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 56.98 | 56.98 | 14171.17 | 47778.44 | 31-OCT-11:30 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 56.98 | 56.98 | 14865.40 | 49631.27 | 30-NOV-13:00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 57.03 | 57.03 | 14850.68 | 51134.55 | 29-DEC-13:00 |
Annual Sum or Average | 0.00 | 14841.06 | ||||||
Minimum of Months | 0.00 | 0.00 | 56.46 | 56.46 | 13417.13 | 45070.72 | ||
Maximum of Months | 0.00 | 0.00 | 57.83 | 57.83 | 16426.34 | 52120.04 |
Report: CondLoopDemandReportMonthly
For: TOWERWATERSYS
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.01 | 33.27 | 25-JAN-15:40 | 21.10 | 20.45 | 641.87 | 123964.55 | 15-JAN-19:30 |
February | 3526.79 | 640622.71 | 27-FEB-16:00 | 23.82 | 21.10 | 1719.24 | 132455.19 | 08-FEB-06:30 |
March | 4320.69 | 425917.38 | 18-MAR-16:00 | 22.91 | 21.10 | 2057.89 | 130813.12 | 01-MAR-07:00 |
April | 52426.42 | 2288366.62 | 27-APR-14:00 | 25.95 | 21.74 | 1557.79 | 111427.56 | 12-APR-06:00 |
May | 91908.03 | 2208737.76 | 05-MAY-13:00 | 25.78 | 21.51 | 969.76 | 95540.22 | 17-MAY-19:10 |
June | 178322.67 | 2282512.85 | 28-JUN-14:20 | 25.94 | 21.28 | 737.21 | 68187.21 | 24-JUN-08:70 |
July | 321157.23 | 3209054.92 | 31-JUL-16:00 | 27.90 | 23.62 | 1085.86 | 75282.22 | 03-JUL-10:10 |
August | 459470.15 | 3671794.69 | 29-AUG-14:30 | 28.88 | 24.35 | 956.74 | 63504.12 | 03-AUG-19:50 |
September | 155042.90 | 2357741.26 | 14-SEP-16:00 | 26.10 | 21.89 | 644.84 | 70883.36 | 29-SEP-10:00 |
October | 22447.53 | 1179472.44 | 04-OCT-15:00 | 26.10 | 21.10 | 962.66 | 98240.57 | 11-OCT-06:00 |
November | 3684.84 | 532732.23 | 04-NOV-14:10 | 23.36 | 21.10 | 1988.46 | 118190.80 | 14-NOV-05:53 |
December | 10.40 | 10109.72 | 16-DEC-06:03 | 21.14 | 20.58 | 1836.36 | 118266.29 | 02-DEC-05:53 |
Annual Sum or Average | 108662.44 | 1259.82 | ||||||
Minimum of Months | 0.01 | 33.27 | 21.10 | 20.45 | 641.87 | 63504.12 | ||
Maximum of Months | 459470.15 | 3671794.69 | 28.88 | 24.35 | 2057.89 | 132455.19 |
Report: ZoneTemperatureOscillationReportMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV_BOT WITH REHEAT
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.561523E+10 | 0.00 | 736.07 | 0.388470E+10 | 0.00 | 0.00 |
February | 0.283944E+10 | 0.00 | 0.840364E+09 | 0.449590E+10 | 0.00 | 0.00 |
March | 0.304387E+09 | 0.00 | 0.110992E+10 | 0.693704E+10 | 0.00 | 0.00 |
April | 26845860.09 | 0.00 | 0.107974E+11 | 0.878303E+10 | 0.00 | 0.00 |
May | 4335583.48 | 0.00 | 0.175815E+11 | 0.815132E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.342120E+11 | 0.985548E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.625953E+11 | 0.119989E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.856034E+11 | 0.139542E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.274451E+11 | 0.830971E+10 | 0.00 | 0.00 |
October | 7081102.19 | 0.00 | 0.494085E+10 | 0.680998E+10 | 0.00 | 0.00 |
November | 0.654854E+09 | 0.00 | 0.722474E+09 | 0.527109E+10 | 0.00 | 0.00 |
December | 0.224080E+10 | 0.00 | 1456.30 | 0.513387E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.116930E+11 | 0.00 | 0.245848E+12 | 0.935852E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 736.07 | 0.388470E+10 | 0.00 | 0.00 |
Maximum of Months | 0.561523E+10 | 0.00 | 0.856034E+11 | 0.139542E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV_MID WITH REHEAT
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.237688E+12 | 0.00 | 46032.53 | 0.317013E+11 | 0.00 | 0.00 |
February | 0.122165E+12 | 0.00 | 0.552779E+10 | 0.313418E+11 | 0.00 | 0.00 |
March | 0.358070E+11 | 0.00 | 0.826430E+10 | 0.430148E+11 | 0.00 | 0.00 |
April | 0.119894E+11 | 0.00 | 0.828809E+11 | 0.495154E+11 | 0.00 | 0.00 |
May | 0.144691E+10 | 0.00 | 0.153180E+12 | 0.623504E+11 | 0.00 | 0.00 |
June | 56848904.65 | 0.00 | 0.283078E+12 | 0.710497E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.503780E+12 | 0.826392E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.670024E+12 | 0.948609E+11 | 0.00 | 0.00 |
September | 0.306133E+09 | 0.00 | 0.247875E+12 | 0.668688E+11 | 0.00 | 0.00 |
October | 0.135354E+11 | 0.00 | 0.401280E+11 | 0.460331E+11 | 0.00 | 0.00 |
November | 0.776665E+11 | 0.00 | 0.640785E+10 | 0.324906E+11 | 0.00 | 0.00 |
December | 0.163597E+12 | 0.00 | 83990.50 | 0.314710E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.664258E+12 | 0.00 | 0.200115E+13 | 0.643337E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 46032.53 | 0.313418E+11 | 0.00 | 0.00 |
Maximum of Months | 0.237688E+12 | 0.00 | 0.670024E+12 | 0.948609E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV_TOP WITH REHEAT
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.400617E+11 | 0.00 | 56866.44 | 0.369878E+10 | 0.00 | 0.00 |
February | 0.242180E+11 | 0.00 | 0.463910E+09 | 0.324071E+10 | 0.00 | 0.00 |
March | 0.108381E+11 | 0.00 | 0.742032E+09 | 0.361401E+10 | 0.00 | 0.00 |
April | 0.421387E+10 | 0.00 | 0.856015E+10 | 0.420592E+10 | 0.00 | 0.00 |
May | 0.112847E+10 | 0.00 | 0.157180E+11 | 0.537230E+10 | 0.00 | 0.00 |
June | 0.156173E+09 | 0.00 | 0.296458E+11 | 0.641593E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.535315E+11 | 0.772924E+10 | 0.00 | 0.00 |
August | 8778252.83 | 0.00 | 0.702697E+11 | 0.865589E+10 | 0.00 | 0.00 |
September | 0.456998E+09 | 0.00 | 0.242451E+11 | 0.558523E+10 | 0.00 | 0.00 |
October | 0.525398E+10 | 0.00 | 0.348473E+10 | 0.367582E+10 | 0.00 | 0.00 |
November | 0.180822E+11 | 0.00 | 0.628742E+09 | 0.297306E+10 | 0.00 | 0.00 |
December | 0.323755E+11 | 0.00 | 85.53 | 0.324804E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.136794E+12 | 0.00 | 0.207290E+12 | 0.584149E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 85.53 | 0.297306E+10 | 0.00 | 0.00 |
Maximum of Months | 0.400617E+11 | 0.00 | 0.702697E+11 | 0.865589E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: CAV_BAS
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 3148880.28 | 0.151257E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.460191E+09 | 0.136858E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.129088E+09 | 0.161156E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.423654E+10 | 0.147701E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.800834E+10 | 0.158234E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.167524E+11 | 0.158934E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.314443E+11 | 0.158280E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.440211E+11 | 0.169692E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.129255E+11 | 0.157607E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.170447E+10 | 0.156079E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.282626E+09 | 0.150257E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 7063244.24 | 0.148102E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.119975E+12 | 0.185416E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 3148880.28 | 0.136858E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.440211E+11 | 0.169692E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER BASEMENT
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.802698E+10 | 0.189181E+12 | 0.00 | 33.33 |
February | 0.00 | 0.00 | 0.111842E+11 | 0.221310E+12 | 0.00 | 48.52 |
March | 0.00 | 0.00 | 0.209820E+11 | 0.282324E+12 | 0.00 | 66.82 |
April | 0.00 | 0.00 | 0.139114E+12 | 0.283288E+12 | 0.00 | 58.15 |
May | 0.00 | 0.00 | 0.928699E+10 | 0.135072E+12 | 0.00 | 13.02 |
June | 0.00 | 0.00 | 0.572497E+11 | 0.130457E+12 | 0.00 | 8.18 |
July | 0.00 | 0.00 | 0.328216E+12 | 0.194456E+12 | 0.00 | 7.97 |
August | 0.00 | 0.00 | 0.809928E+12 | 0.280031E+12 | 0.00 | 0.40 |
September | 0.00 | 0.00 | 0.896645E+10 | 0.987272E+11 | 0.00 | 0.60 |
October | 0.00 | 0.00 | 0.840050E+10 | 0.154276E+12 | 0.00 | 20.27 |
November | 0.00 | 0.00 | 0.175277E+11 | 0.216789E+12 | 0.00 | 43.94 |
December | 0.00 | 0.00 | 0.207742E+11 | 0.323076E+12 | 0.00 | 81.94 |
Annual Sum or Average | 0.00 | 0.00 | 0.143966E+13 | 0.250899E+13 | 0.00 | 383.16 |
Minimum of Months | 0.00 | 0.00 | 0.802698E+10 | 0.987272E+11 | 0.00 | 0.40 |
Maximum of Months | 0.00 | 0.00 | 0.809928E+12 | 0.323076E+12 | 0.00 | 81.94 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER BOT
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.503867E+10 | 0.262970E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.108977E+11 | 0.355886E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.189560E+11 | 0.513575E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.246829E+11 | 0.604700E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.723161E+10 | 0.303094E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.133236E+11 | 0.410608E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.205081E+11 | 0.559194E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.269637E+11 | 0.700283E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.721141E+10 | 0.296353E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.129926E+11 | 0.405087E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.181108E+11 | 0.488549E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.245425E+11 | 0.606682E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.190460E+12 | 0.550698E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.503867E+10 | 0.262970E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.269637E+11 | 0.700283E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER MID
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.198222E+11 | 0.196115E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.824780E+11 | 0.301316E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.163545E+12 | 0.461932E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.224065E+12 | 0.560071E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.608370E+11 | 0.275285E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.121292E+12 | 0.382918E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.191917E+12 | 0.528712E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.254211E+12 | 0.664773E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.615192E+11 | 0.270600E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.108912E+12 | 0.361334E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.150968E+12 | 0.430551E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.206720E+12 | 0.535364E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.164629E+13 | 0.496897E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.198222E+11 | 0.196115E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.254211E+12 | 0.664773E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER TOP
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.900828E+09 | 0.174983E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.648488E+10 | 0.269734E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.149144E+11 | 0.439156E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.215087E+11 | 0.548027E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.544424E+10 | 0.265432E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.118483E+11 | 0.380361E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.190241E+11 | 0.528813E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.252250E+11 | 0.664798E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.552028E+10 | 0.261021E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.956676E+10 | 0.339794E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.133302E+11 | 0.402153E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.185781E+11 | 0.502561E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.152346E+12 | 0.477683E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.900828E+09 | 0.174983E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.252250E+11 | 0.664798E+10 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV_BOT WITH REHEAT
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.388470E+10 | 736.07 | 0.561523E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.449590E+10 | 0.840364E+09 | 0.283944E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.693704E+10 | 0.110992E+10 | 0.304387E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.878303E+10 | 0.107974E+11 | 26845860.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.815132E+10 | 0.175815E+11 | 4335583.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.985548E+10 | 0.342120E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.119989E+11 | 0.625953E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.139542E+11 | 0.856034E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.830971E+10 | 0.274451E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.680998E+10 | 0.494085E+10 | 7081102.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.527109E+10 | 0.722474E+09 | 0.654854E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.513387E+10 | 1456.30 | 0.224080E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.935852E+11 | 0.245848E+12 | 0.116930E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.388470E+10 | 736.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.139542E+11 | 0.856034E+11 | 0.561523E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV_MID WITH REHEAT
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.317013E+11 | 46032.53 | 0.237688E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.313418E+11 | 0.552779E+10 | 0.122165E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.430148E+11 | 0.826430E+10 | 0.358070E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.495154E+11 | 0.828809E+11 | 0.119894E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.623504E+11 | 0.153180E+12 | 0.144691E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.710497E+11 | 0.283078E+12 | 56848904.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.826392E+11 | 0.503780E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.948609E+11 | 0.670024E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.668688E+11 | 0.247875E+12 | 0.306133E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.460331E+11 | 0.401280E+11 | 0.135354E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.324906E+11 | 0.640785E+10 | 0.776665E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.314710E+11 | 83990.50 | 0.163597E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.643337E+12 | 0.200115E+13 | 0.664258E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.313418E+11 | 46032.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.948609E+11 | 0.670024E+12 | 0.237688E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV_TOP WITH REHEAT
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.369878E+10 | 56866.44 | 0.400617E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.324071E+10 | 0.463910E+09 | 0.242180E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.361401E+10 | 0.742032E+09 | 0.108381E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.420592E+10 | 0.856015E+10 | 0.421387E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.537230E+10 | 0.157180E+11 | 0.112847E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.641593E+10 | 0.296458E+11 | 0.156173E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.772924E+10 | 0.535315E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.865589E+10 | 0.702697E+11 | 8778252.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.558523E+10 | 0.242451E+11 | 0.456998E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.367582E+10 | 0.348473E+10 | 0.525398E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.297306E+10 | 0.628742E+09 | 0.180822E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.324804E+10 | 85.53 | 0.323755E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.584149E+11 | 0.207290E+12 | 0.136794E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.297306E+10 | 85.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.865589E+10 | 0.702697E+11 | 0.400617E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: CAV_BAS
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.151257E+11 | 3148880.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.136858E+11 | 0.460191E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.161156E+11 | 0.129088E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.147701E+11 | 0.423654E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.158234E+11 | 0.800834E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.158934E+11 | 0.167524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.158280E+11 | 0.314443E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.169692E+11 | 0.440211E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.157607E+11 | 0.129255E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.156079E+11 | 0.170447E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.150257E+11 | 0.282626E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.148102E+11 | 7063244.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.185416E+12 | 0.119975E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.136858E+11 | 3148880.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.169692E+11 | 0.440211E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER BASEMENT
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.959277E+11 | 0.437180E+10 | 0.00 | 0.00 | 0.00 | 0.891971E+11 | 0.00 | 0.00 |
February | 0.866444E+11 | 0.695535E+10 | 0.00 | 0.00 | 0.00 | 0.129852E+12 | 0.00 | 0.00 |
March | 0.959277E+11 | 0.142125E+11 | 0.00 | 0.00 | 0.00 | 0.178821E+12 | 0.00 | 0.00 |
April | 0.928332E+11 | 0.104986E+12 | 0.00 | 0.00 | 0.00 | 0.155626E+12 | 0.00 | 0.00 |
May | 0.959277E+11 | 0.514281E+10 | 0.00 | 0.00 | 0.00 | 0.348434E+11 | 0.00 | 0.00 |
June | 0.928332E+11 | 0.416097E+11 | 0.00 | 0.00 | 0.00 | 0.218851E+11 | 0.00 | 0.00 |
July | 0.959277E+11 | 0.251124E+12 | 0.00 | 0.00 | 0.00 | 0.213402E+11 | 0.00 | 0.00 |
August | 0.959277E+11 | 0.626898E+12 | 0.00 | 0.00 | 0.00 | 0.106877E+10 | 0.00 | 0.00 |
September | 0.928332E+11 | 0.469211E+10 | 0.00 | 0.00 | 0.00 | 0.161233E+10 | 0.00 | 0.00 |
October | 0.959277E+11 | 0.453200E+10 | 0.00 | 0.00 | 0.00 | 0.542361E+11 | 0.00 | 0.00 |
November | 0.928332E+11 | 0.116969E+11 | 0.00 | 0.00 | 0.00 | 0.117595E+12 | 0.00 | 0.00 |
December | 0.959277E+11 | 0.139065E+11 | 0.00 | 0.00 | 0.00 | 0.219294E+12 | 0.00 | 0.00 |
Annual Sum or Average | 0.112947E+13 | 0.109013E+13 | 0.00 | 0.00 | 0.00 | 0.102537E+13 | 0.00 | 0.00 |
Minimum of Months | 0.866444E+11 | 0.437180E+10 | 0.00 | 0.00 | 0.00 | 0.106877E+10 | 0.00 | 0.00 |
Maximum of Months | 0.959277E+11 | 0.626898E+12 | 0.00 | 0.00 | 0.00 | 0.219294E+12 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER BOT
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.158662E+10 | 0.399559E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.143307E+10 | 0.877191E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.158662E+10 | 0.154069E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.153544E+10 | 0.201714E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.158662E+10 | 0.578728E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.153544E+10 | 0.107530E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.158662E+10 | 0.165028E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.158662E+10 | 0.215475E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.153544E+10 | 0.578331E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.158662E+10 | 0.105283E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.153544E+10 | 0.147607E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.158662E+10 | 0.200623E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.186811E+11 | 0.154071E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.143307E+10 | 0.399559E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.158662E+10 | 0.215475E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER MID
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.152637E+11 | 0.154744E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.137865E+11 | 0.661330E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.152637E+11 | 0.132616E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.147713E+11 | 0.182830E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.152637E+11 | 0.485722E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.147713E+11 | 0.977718E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.152637E+11 | 0.154309E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.152637E+11 | 0.202997E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.147713E+11 | 0.492305E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.152637E+11 | 0.880421E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.147713E+11 | 0.122684E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.152637E+11 | 0.168447E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.179717E+12 | 0.132911E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.137865E+11 | 0.154744E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.152637E+11 | 0.202997E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER TOP
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.154760E+10 | 0.698593E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.139783E+10 | 0.518537E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.154760E+10 | 0.120704E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.149767E+10 | 0.175261E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.154760E+10 | 0.433752E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.149767E+10 | 0.954232E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.154760E+10 | 0.152836E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.154760E+10 | 0.201246E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.149767E+10 | 0.440774E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.154760E+10 | 0.771641E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.149767E+10 | 0.108063E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.154760E+10 | 0.151001E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.182217E+11 | 0.122799E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.139783E+10 | 0.698593E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.154760E+10 | 0.201246E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV_BOT WITH REHEAT
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.388470E+10 | 0.561523E+10 | 736.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.449590E+10 | 0.283944E+10 | 0.840364E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.693704E+10 | 0.304387E+09 | 0.110992E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.878303E+10 | 26845860.09 | 0.107974E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.815132E+10 | 4335583.48 | 0.175815E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.985548E+10 | 0.00 | 0.342120E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.119989E+11 | 0.00 | 0.625953E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.139542E+11 | 0.00 | 0.856034E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.830971E+10 | 0.00 | 0.274451E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.680998E+10 | 7081102.19 | 0.494085E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.527109E+10 | 0.654854E+09 | 0.722474E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.513387E+10 | 0.224080E+10 | 1456.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.935852E+11 | 0.116930E+11 | 0.245848E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.388470E+10 | 0.00 | 736.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.139542E+11 | 0.561523E+10 | 0.856034E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV_MID WITH REHEAT
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.317013E+11 | 0.237688E+12 | 46032.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.313418E+11 | 0.122165E+12 | 0.552779E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.430148E+11 | 0.358070E+11 | 0.826430E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.495154E+11 | 0.119894E+11 | 0.828809E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.623504E+11 | 0.144691E+10 | 0.153180E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.710497E+11 | 56848904.65 | 0.283078E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.826392E+11 | 0.00 | 0.503780E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.948609E+11 | 0.00 | 0.670024E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.668688E+11 | 0.306133E+09 | 0.247875E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.460331E+11 | 0.135354E+11 | 0.401280E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.324906E+11 | 0.776665E+11 | 0.640785E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.314710E+11 | 0.163597E+12 | 83990.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.643337E+12 | 0.664258E+12 | 0.200115E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.313418E+11 | 0.00 | 46032.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.948609E+11 | 0.237688E+12 | 0.670024E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV_TOP WITH REHEAT
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.369878E+10 | 0.400617E+11 | 56866.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.324071E+10 | 0.242180E+11 | 0.463910E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.361401E+10 | 0.108381E+11 | 0.742032E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.420592E+10 | 0.421387E+10 | 0.856015E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.537230E+10 | 0.112847E+10 | 0.157180E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.641593E+10 | 0.156173E+09 | 0.296458E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.772924E+10 | 0.00 | 0.535315E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.865589E+10 | 8778252.83 | 0.702697E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.558523E+10 | 0.456998E+09 | 0.242451E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.367582E+10 | 0.525398E+10 | 0.348473E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.297306E+10 | 0.180822E+11 | 0.628742E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.324804E+10 | 0.323755E+11 | 85.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.584149E+11 | 0.136794E+12 | 0.207290E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.297306E+10 | 0.00 | 85.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.865589E+10 | 0.400617E+11 | 0.702697E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: CAV_BAS
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.151257E+11 | 0.00 | 3148880.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.136858E+11 | 0.00 | 0.460191E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.161156E+11 | 0.00 | 0.129088E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.147701E+11 | 0.00 | 0.423654E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.158234E+11 | 0.00 | 0.800834E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.158934E+11 | 0.00 | 0.167524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.158280E+11 | 0.00 | 0.314443E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.169692E+11 | 0.00 | 0.440211E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.157607E+11 | 0.00 | 0.129255E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.156079E+11 | 0.00 | 0.170447E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.150257E+11 | 0.00 | 0.282626E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.148102E+11 | 0.00 | 7063244.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.185416E+12 | 0.00 | 0.119975E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.136858E+11 | 0.00 | 3148880.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.169692E+11 | 0.00 | 0.440211E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER BASEMENT
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.959277E+11 | 0.00 | 0.802698E+10 | 0.00 | 0.365518E+10 | 0.00 | 0.00 | 0.00 | 0.895986E+11 | 0.00 | 0.00 | 0.00 |
February | 0.866444E+11 | 0.00 | 0.111842E+11 | 0.00 | 0.422890E+10 | 0.00 | 0.00 | 0.00 | 0.130437E+12 | 0.00 | 0.00 | 0.00 |
March | 0.959277E+11 | 0.00 | 0.209820E+11 | 0.00 | 0.676950E+10 | 0.00 | 0.00 | 0.00 | 0.179626E+12 | 0.00 | 0.00 | 0.00 |
April | 0.928332E+11 | 0.00 | 0.139114E+12 | 0.00 | 0.341274E+11 | 0.00 | 0.00 | 0.00 | 0.156327E+12 | 0.00 | 0.00 | 0.00 |
May | 0.959277E+11 | 0.00 | 0.928699E+10 | 0.00 | 0.414418E+10 | 0.00 | 0.00 | 0.00 | 0.350002E+11 | 0.00 | 0.00 | 0.00 |
June | 0.928332E+11 | 0.00 | 0.572497E+11 | 0.00 | 0.156399E+11 | 0.00 | 0.00 | 0.00 | 0.219837E+11 | 0.00 | 0.00 | 0.00 |
July | 0.959277E+11 | 0.00 | 0.328216E+12 | 0.00 | 0.770923E+11 | 0.00 | 0.00 | 0.00 | 0.214363E+11 | 0.00 | 0.00 | 0.00 |
August | 0.959277E+11 | 0.00 | 0.809928E+12 | 0.00 | 0.183030E+12 | 0.00 | 0.00 | 0.00 | 0.107358E+10 | 0.00 | 0.00 | 0.00 |
September | 0.928332E+11 | 0.00 | 0.896645E+10 | 0.00 | 0.427434E+10 | 0.00 | 0.00 | 0.00 | 0.161959E+10 | 0.00 | 0.00 | 0.00 |
October | 0.959277E+11 | 0.00 | 0.840050E+10 | 0.00 | 0.386850E+10 | 0.00 | 0.00 | 0.00 | 0.544802E+11 | 0.00 | 0.00 | 0.00 |
November | 0.928332E+11 | 0.00 | 0.175277E+11 | 0.00 | 0.583078E+10 | 0.00 | 0.00 | 0.00 | 0.118125E+12 | 0.00 | 0.00 | 0.00 |
December | 0.959277E+11 | 0.00 | 0.207742E+11 | 0.00 | 0.686768E+10 | 0.00 | 0.00 | 0.00 | 0.220281E+12 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.112947E+13 | 0.00 | 0.143966E+13 | 0.00 | 0.349529E+12 | 0.00 | 0.00 | 0.00 | 0.102999E+13 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.866444E+11 | 0.00 | 0.802698E+10 | 0.00 | 0.365518E+10 | 0.00 | 0.00 | 0.00 | 0.107358E+10 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.959277E+11 | 0.00 | 0.809928E+12 | 0.00 | 0.183030E+12 | 0.00 | 0.00 | 0.00 | 0.220281E+12 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER BOT
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.158662E+10 | 0.00 | 0.503867E+10 | 0.00 | 0.104308E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.143307E+10 | 0.00 | 0.108977E+11 | 0.00 | 0.212579E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.158662E+10 | 0.00 | 0.189560E+11 | 0.00 | 0.354913E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.153544E+10 | 0.00 | 0.246829E+11 | 0.00 | 0.451157E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.158662E+10 | 0.00 | 0.723161E+10 | 0.00 | 0.144433E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.153544E+10 | 0.00 | 0.133236E+11 | 0.00 | 0.257065E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.158662E+10 | 0.00 | 0.205081E+11 | 0.00 | 0.400532E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.158662E+10 | 0.00 | 0.269637E+11 | 0.00 | 0.541621E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.153544E+10 | 0.00 | 0.721141E+10 | 0.00 | 0.142809E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.158662E+10 | 0.00 | 0.129926E+11 | 0.00 | 0.246426E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.153544E+10 | 0.00 | 0.181108E+11 | 0.00 | 0.335005E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.158662E+10 | 0.00 | 0.245425E+11 | 0.00 | 0.448020E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.186811E+11 | 0.00 | 0.190460E+12 | 0.00 | 0.363887E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.143307E+10 | 0.00 | 0.503867E+10 | 0.00 | 0.104308E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.158662E+10 | 0.00 | 0.269637E+11 | 0.00 | 0.541621E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER MID
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.152637E+11 | 0.00 | 0.198222E+11 | 0.00 | 0.434780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.137865E+11 | 0.00 | 0.824780E+11 | 0.00 | 0.163450E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.152637E+11 | 0.00 | 0.163545E+12 | 0.00 | 0.309296E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.147713E+11 | 0.00 | 0.224065E+12 | 0.00 | 0.412358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.152637E+11 | 0.00 | 0.608370E+11 | 0.00 | 0.122648E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.147713E+11 | 0.00 | 0.121292E+12 | 0.00 | 0.235205E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.152637E+11 | 0.00 | 0.191917E+12 | 0.00 | 0.376075E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.152637E+11 | 0.00 | 0.254211E+12 | 0.00 | 0.512136E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.147713E+11 | 0.00 | 0.615192E+11 | 0.00 | 0.122887E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.152637E+11 | 0.00 | 0.108912E+12 | 0.00 | 0.208697E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.147713E+11 | 0.00 | 0.150968E+12 | 0.00 | 0.282838E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.152637E+11 | 0.00 | 0.206720E+12 | 0.00 | 0.382727E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.179717E+12 | 0.00 | 0.164629E+13 | 0.00 | 0.317179E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.137865E+11 | 0.00 | 0.198222E+11 | 0.00 | 0.434780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.152637E+11 | 0.00 | 0.254211E+12 | 0.00 | 0.512136E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER TOP
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.154760E+10 | 0.00 | 0.900828E+09 | 0.00 | 0.202235E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.139783E+10 | 0.00 | 0.648488E+10 | 0.00 | 0.129951E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.154760E+10 | 0.00 | 0.149144E+11 | 0.00 | 0.284396E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.149767E+10 | 0.00 | 0.215087E+11 | 0.00 | 0.398260E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.154760E+10 | 0.00 | 0.544424E+10 | 0.00 | 0.110672E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.149767E+10 | 0.00 | 0.118483E+11 | 0.00 | 0.230594E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.154760E+10 | 0.00 | 0.190241E+11 | 0.00 | 0.374053E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.154760E+10 | 0.00 | 0.252250E+11 | 0.00 | 0.510038E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.149767E+10 | 0.00 | 0.552028E+10 | 0.00 | 0.111254E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.154760E+10 | 0.00 | 0.956676E+10 | 0.00 | 0.185035E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.149767E+10 | 0.00 | 0.133302E+11 | 0.00 | 0.252385E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.154760E+10 | 0.00 | 0.185781E+11 | 0.00 | 0.347802E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.182217E+11 | 0.00 | 0.152346E+12 | 0.00 | 0.295466E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.139783E+10 | 0.00 | 0.900828E+09 | 0.00 | 0.202235E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.154760E+10 | 0.00 | 0.252250E+11 | 0.00 | 0.510038E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.482815E+09 | 0.00 | 0.00 | 0.107377E+09 | 0.00 | 0.00 | 0.696260E+11 | 0.00 | 0.59 |
February | 0.405433E+09 | 0.00 | 0.00 | 0.102077E+09 | 0.00 | 0.00 | 0.656009E+11 | 0.00 | 0.72 |
March | 0.287855E+09 | 0.00 | 0.00 | 0.129639E+09 | 0.00 | 0.00 | 0.824207E+11 | 0.00 | 0.92 |
April | 0.274003E+09 | 23316773.82 | 0.00 | 0.120555E+09 | 0.00 | 0.00 | 0.738393E+11 | 0.00 | 1.02 |
May | 0.225430E+09 | 14745465.78 | 0.00 | 0.121364E+09 | 0.00 | 0.00 | 0.738860E+11 | 0.00 | 1.26 |
June | 0.173768E+09 | 17477223.61 | 0.00 | 0.126208E+09 | 1266942.15 | 0.00 | 0.677138E+11 | 0.00 | 1.52 |
July | 0.267170E+09 | 0.228862E+09 | 0.00 | 0.125044E+09 | 5221211.03 | 0.00 | 0.532099E+11 | 0.00 | 1.48 |
August | 0.170226E+09 | 0.520884E+09 | 0.00 | 0.130748E+09 | 161826.53 | 0.00 | 0.495000E+11 | 0.00 | 1.44 |
September | 0.372949E+09 | 0.00 | 0.00 | 0.125570E+09 | 0.00 | 0.00 | 0.683363E+11 | 0.00 | 1.45 |
October | 0.372483E+09 | 0.00 | 0.00 | 0.129717E+09 | 0.00 | 0.00 | 0.803929E+11 | 0.00 | 1.11 |
November | 0.344046E+09 | 0.00 | 0.00 | 0.123878E+09 | 0.00 | 0.00 | 0.778400E+11 | 0.00 | 0.85 |
December | 0.496618E+09 | 0.00 | 0.00 | 0.122343E+09 | 0.00 | 0.00 | 0.748886E+11 | 0.00 | 0.66 |
Annual Sum or Average | 0.387280E+10 | 0.805286E+09 | 0.00 | 0.146452E+10 | 6649979.70 | 0.00 | 0.837254E+12 | 0.00 | 1.09 |
Minimum of Months | 0.170226E+09 | 0.00 | 0.00 | 0.102077E+09 | 0.00 | 0.00 | 0.495000E+11 | 0.00 | 0.59 |
Maximum of Months | 0.496618E+09 | 0.520884E+09 | 0.00 | 0.130748E+09 | 5221211.03 | 0.00 | 0.824207E+11 | 0.00 | 1.52 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.412246E+10 | 0.00 | 0.00 | 57979317.62 | 0.00 | 0.00 | 0.425857E+11 | 0.00 | 0.38 |
February | 0.221514E+10 | 0.00 | 0.00 | 69725336.48 | 0.00 | 0.00 | 0.453762E+11 | 0.00 | 0.50 |
March | 0.176069E+10 | 0.00 | 0.00 | 0.105293E+09 | 0.00 | 0.00 | 0.634536E+11 | 0.00 | 0.69 |
April | 0.410459E+10 | 16880386.34 | 0.00 | 0.104738E+09 | 0.00 | 0.00 | 0.601936E+11 | 0.00 | 0.84 |
May | 0.368963E+10 | 639952.13 | 0.00 | 95653778.67 | 0.00 | 0.00 | 0.548554E+11 | 0.00 | 0.92 |
June | 0.325431E+10 | 20289581.70 | 0.00 | 0.105676E+09 | 6035038.30 | 0.00 | 0.523887E+11 | 0.00 | 1.10 |
July | 0.628675E+10 | 0.198281E+09 | 0.00 | 0.102036E+09 | 3134266.41 | 0.00 | 0.402326E+11 | 0.00 | 1.11 |
August | 0.738546E+10 | 0.713226E+09 | 0.00 | 0.102047E+09 | 3772222.66 | 0.00 | 0.374883E+11 | 0.00 | 1.16 |
September | 0.281426E+10 | 0.00 | 0.00 | 94927481.30 | 0.00 | 0.00 | 0.479521E+11 | 0.00 | 0.97 |
October | 0.254202E+10 | 0.00 | 0.00 | 95735066.70 | 0.00 | 0.00 | 0.578602E+11 | 0.00 | 0.78 |
November | 0.196638E+10 | 0.00 | 0.00 | 88849637.30 | 0.00 | 0.00 | 0.554117E+11 | 0.00 | 0.59 |
December | 0.180657E+10 | 0.00 | 0.00 | 88959779.71 | 0.00 | 0.00 | 0.537135E+11 | 0.00 | 0.47 |
Annual Sum or Average | 0.419483E+11 | 0.949317E+09 | 0.00 | 0.111162E+10 | 12941527.37 | 0.00 | 0.611512E+12 | 0.00 | 0.80 |
Minimum of Months | 0.176069E+10 | 0.00 | 0.00 | 57979317.62 | 0.00 | 0.00 | 0.374883E+11 | 0.00 | 0.38 |
Maximum of Months | 0.738546E+10 | 0.713226E+09 | 0.00 | 0.105676E+09 | 6035038.30 | 0.00 | 0.634536E+11 | 0.00 | 1.16 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.228819E+12 | 0.00 | 0.00 | 0.107509E+09 | 0.00 | 0.236783E+10 | 0.103966E+12 | 0.00 | 0.29 |
February | 0.160197E+12 | 0.00 | 0.00 | 0.209117E+09 | 0.00 | 28828264.31 | 0.165878E+12 | 0.00 | 0.35 |
March | 0.109242E+12 | 0.00 | 0.00 | 0.438275E+09 | 0.00 | 0.00 | 0.310531E+12 | 0.00 | 0.46 |
April | 0.665943E+11 | 0.165084E+09 | 0.00 | 0.484145E+09 | 56478676.91 | 0.00 | 0.331633E+12 | 0.00 | 0.54 |
May | 0.417225E+11 | 11176884.59 | 0.00 | 0.657804E+09 | 0.00 | 0.00 | 0.414310E+12 | 0.00 | 0.74 |
June | 0.272059E+11 | 0.175802E+09 | 0.00 | 0.737645E+09 | 49836010.38 | 0.00 | 0.395321E+12 | 0.00 | 0.86 |
July | 0.309768E+11 | 0.163293E+10 | 0.00 | 0.701847E+09 | 42024192.33 | 0.00 | 0.291213E+12 | 0.00 | 0.82 |
August | 0.202377E+11 | 0.616726E+10 | 0.00 | 0.726786E+09 | 44451441.96 | 0.00 | 0.276108E+12 | 0.00 | 0.80 |
September | 0.323209E+11 | 1502465.73 | 0.00 | 0.664977E+09 | 0.00 | 0.00 | 0.363346E+12 | 0.00 | 0.79 |
October | 0.784864E+11 | 0.00 | 0.00 | 0.485574E+09 | 0.00 | 0.00 | 0.332333E+12 | 0.00 | 0.56 |
November | 0.128317E+12 | 0.00 | 0.00 | 0.285817E+09 | 0.00 | 0.00 | 0.220367E+12 | 0.00 | 0.38 |
December | 0.189300E+12 | 0.00 | 0.00 | 0.183493E+09 | 0.00 | 0.00 | 0.152071E+12 | 0.00 | 0.30 |
Annual Sum or Average | 0.111342E+13 | 0.815375E+10 | 0.00 | 0.568299E+10 | 0.192790E+09 | 0.239666E+10 | 0.335708E+13 | 0.00 | 0.58 |
Minimum of Months | 0.202377E+11 | 0.00 | 0.00 | 0.107509E+09 | 0.00 | 0.00 | 0.103966E+12 | 0.00 | 0.29 |
Maximum of Months | 0.228819E+12 | 0.616726E+10 | 0.00 | 0.737645E+09 | 56478676.91 | 0.236783E+10 | 0.414310E+12 | 0.00 | 0.86 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.276139E+11 | 0.00 | 0.00 | 715294.77 | 0.00 | 0.110400E+10 | 0.144797E+10 | 0.00 | 0.28 |
February | 0.226060E+11 | 0.00 | 0.00 | 4708663.46 | 0.00 | 0.611445E+09 | 0.494868E+10 | 0.00 | 0.32 |
March | 0.188586E+11 | 0.00 | 0.00 | 16075675.67 | 0.00 | 0.181487E+09 | 0.152977E+11 | 0.00 | 0.39 |
April | 0.122136E+11 | 4713901.73 | 0.00 | 28804550.23 | 1584124.33 | 1892944.67 | 0.224255E+11 | 0.00 | 0.49 |
May | 0.917544E+10 | 0.00 | 0.00 | 47777037.31 | 0.00 | 0.00 | 0.326770E+11 | 0.00 | 0.69 |
June | 0.580953E+10 | 7940301.96 | 0.00 | 61248857.87 | 3153303.45 | 0.00 | 0.348796E+11 | 0.00 | 0.85 |
July | 0.458634E+10 | 0.104391E+09 | 0.00 | 62163758.99 | 3175214.75 | 0.00 | 0.271408E+11 | 0.00 | 0.83 |
August | 0.391098E+10 | 0.430571E+09 | 0.00 | 61775796.80 | 8939939.05 | 0.00 | 0.234952E+11 | 0.00 | 0.79 |
September | 0.861486E+10 | 0.00 | 0.00 | 45297296.63 | 0.00 | 0.00 | 0.254787E+11 | 0.00 | 0.72 |
October | 0.146187E+11 | 0.00 | 0.00 | 21589047.69 | 0.00 | 46271285.69 | 0.177715E+11 | 0.00 | 0.46 |
November | 0.214273E+11 | 0.00 | 0.00 | 5767115.43 | 0.00 | 0.405357E+09 | 0.623961E+10 | 0.00 | 0.33 |
December | 0.258683E+11 | 0.00 | 0.00 | 1051036.09 | 0.00 | 0.828477E+09 | 0.214335E+10 | 0.00 | 0.28 |
Annual Sum or Average | 0.175304E+12 | 0.547616E+09 | 0.00 | 0.356974E+09 | 16852581.57 | 0.317893E+10 | 0.213946E+12 | 0.00 | 0.54 |
Minimum of Months | 0.391098E+10 | 0.00 | 0.00 | 715294.77 | 0.00 | 0.00 | 0.144797E+10 | 0.00 | 0.28 |
Maximum of Months | 0.276139E+11 | 0.430571E+09 | 0.00 | 62163758.99 | 8939939.05 | 0.110400E+10 | 0.348796E+11 | 0.00 | 0.85 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.422284E+10 | 0.00 | 0.00 | 31276.30 | 0.00 | 44901007.34 | 48080385.06 | 0.00 | 0.28 |
February | 0.338819E+10 | 0.00 | 0.00 | 809889.27 | 0.00 | 515839.63 | 0.765750E+09 | 0.00 | 0.35 |
March | 0.258772E+10 | 0.00 | 0.00 | 3672152.30 | 0.00 | 0.00 | 0.294076E+10 | 0.00 | 0.47 |
April | 0.171344E+10 | 2679829.54 | 0.00 | 6496399.88 | 0.00 | 0.00 | 0.458743E+10 | 0.00 | 0.69 |
May | 0.133818E+10 | 171191.57 | 0.00 | 8795596.86 | 0.00 | 0.00 | 0.553727E+10 | 0.00 | 0.92 |
June | 0.711534E+09 | 3579927.98 | 0.00 | 11952685.96 | 757194.90 | 0.00 | 0.623432E+10 | 0.00 | 1.18 |
July | 0.920262E+09 | 36008155.17 | 0.00 | 12436909.68 | 393245.31 | 0.00 | 0.512446E+10 | 0.00 | 1.25 |
August | 0.108934E+10 | 0.124331E+09 | 0.00 | 11370510.90 | 473287.43 | 0.00 | 0.430741E+10 | 0.00 | 1.20 |
September | 0.130690E+10 | 0.00 | 0.00 | 7246423.42 | 0.00 | 0.00 | 0.400570E+10 | 0.00 | 0.86 |
October | 0.222598E+10 | 0.00 | 0.00 | 3852795.53 | 0.00 | 0.00 | 0.305132E+10 | 0.00 | 0.56 |
November | 0.286128E+10 | 0.00 | 0.00 | 1595368.77 | 0.00 | 0.00 | 0.162506E+10 | 0.00 | 0.38 |
December | 0.390446E+10 | 0.00 | 0.00 | 258037.59 | 0.00 | 0.00 | 0.427158E+09 | 0.00 | 0.29 |
Annual Sum or Average | 0.262701E+11 | 0.166770E+09 | 0.00 | 68518046.48 | 1623727.64 | 45416846.98 | 0.386547E+11 | 0.00 | 0.71 |
Minimum of Months | 0.711534E+09 | 0.00 | 0.00 | 31276.30 | 0.00 | 0.00 | 48080385.06 | 0.00 | 0.28 |
Maximum of Months | 0.422284E+10 | 0.124331E+09 | 0.00 | 12436909.68 | 757194.90 | 44901007.34 | 0.623432E+10 | 0.00 | 1.25 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.481846E+10 | 0.00 | 0.00 | 28390.11 | 0.00 | 0.158163E+09 | 37923265.97 | 0.00 | 0.50 |
February | 0.413555E+10 | 0.00 | 0.00 | 787588.27 | 0.00 | 27278796.84 | 0.589129E+09 | 0.00 | 0.61 |
March | 0.348967E+10 | 0.00 | 0.00 | 3592132.98 | 0.00 | 0.00 | 0.264008E+10 | 0.00 | 0.79 |
April | 0.239043E+10 | 2076533.05 | 0.00 | 6947727.40 | 0.00 | 0.00 | 0.462688E+10 | 0.00 | 1.16 |
May | 0.192177E+10 | 136371.21 | 0.00 | 9202442.60 | 0.00 | 0.00 | 0.534090E+10 | 0.00 | 1.45 |
June | 0.123337E+10 | 2296723.82 | 0.00 | 12489087.83 | 879609.22 | 0.00 | 0.640371E+10 | 0.00 | 1.90 |
July | 0.143886E+10 | 27886563.43 | 0.00 | 12980249.64 | 456820.57 | 0.00 | 0.476880E+10 | 0.00 | 1.90 |
August | 0.173119E+10 | 95694144.02 | 0.00 | 12228738.94 | 90412.21 | 0.00 | 0.406356E+10 | 0.00 | 1.93 |
September | 0.201332E+10 | 0.00 | 0.00 | 8355172.19 | 0.00 | 0.00 | 0.413054E+10 | 0.00 | 1.49 |
October | 0.330272E+10 | 0.00 | 0.00 | 3822591.61 | 0.00 | 0.00 | 0.266898E+10 | 0.00 | 0.96 |
November | 0.456014E+10 | 0.00 | 0.00 | 452675.71 | 0.00 | 0.00 | 0.458148E+09 | 0.00 | 0.64 |
December | 0.490423E+10 | 0.00 | 0.00 | 153766.82 | 0.00 | 4740397.72 | 0.127758E+09 | 0.00 | 0.53 |
Annual Sum or Average | 0.359397E+11 | 0.128090E+09 | 0.00 | 71040564.11 | 1426841.99 | 0.190182E+09 | 0.358564E+11 | 0.00 | 1.16 |
Minimum of Months | 0.123337E+10 | 0.00 | 0.00 | 28390.11 | 0.00 | 0.00 | 37923265.97 | 0.00 | 0.50 |
Maximum of Months | 0.490423E+10 | 95694144.02 | 0.00 | 12980249.64 | 879609.22 | 0.158163E+09 | 0.640371E+10 | 0.00 | 1.93 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.550487E+10 | 0.00 | 0.00 | 2435258.75 | 0.00 | 0.474077E+09 | 0.169229E+10 | 0.00 | 0.50 |
February | 0.462959E+10 | 0.00 | 0.00 | 6125674.76 | 0.00 | 0.109670E+09 | 0.388641E+10 | 0.00 | 0.73 |
March | 0.425948E+10 | 0.00 | 0.00 | 10879789.06 | 0.00 | 2025389.78 | 0.775193E+10 | 0.00 | 1.06 |
April | 0.309153E+10 | 7063582.50 | 0.00 | 13052836.82 | 0.00 | 0.00 | 0.832502E+10 | 0.00 | 1.32 |
May | 0.278702E+10 | 319820.24 | 0.00 | 13904464.09 | 0.00 | 0.00 | 0.784564E+10 | 0.00 | 1.46 |
June | 0.206129E+10 | 4225563.93 | 0.00 | 14554913.92 | 1222334.73 | 0.00 | 0.719954E+10 | 0.00 | 1.63 |
July | 0.221440E+10 | 61476529.01 | 0.00 | 16157203.08 | 634813.31 | 0.00 | 0.600448E+10 | 0.00 | 1.78 |
August | 0.229664E+10 | 0.233899E+09 | 0.00 | 16597334.02 | 0.00 | 0.00 | 0.533474E+10 | 0.00 | 1.81 |
September | 0.242207E+10 | 0.00 | 0.00 | 19428330.16 | 0.00 | 0.00 | 0.786221E+10 | 0.00 | 1.87 |
October | 0.367465E+10 | 0.00 | 0.00 | 12857142.49 | 0.00 | 0.00 | 0.805153E+10 | 0.00 | 1.31 |
November | 0.506340E+10 | 0.00 | 0.00 | 4600486.24 | 0.00 | 10166396.39 | 0.306759E+10 | 0.00 | 0.70 |
December | 0.547155E+10 | 0.00 | 0.00 | 4388847.44 | 0.00 | 88685216.69 | 0.298313E+10 | 0.00 | 0.59 |
Annual Sum or Average | 0.434765E+11 | 0.306984E+09 | 0.00 | 0.134982E+09 | 1857148.04 | 0.684625E+09 | 0.700045E+11 | 0.00 | 1.23 |
Minimum of Months | 0.206129E+10 | 0.00 | 0.00 | 2435258.75 | 0.00 | 0.00 | 0.169229E+10 | 0.00 | 0.50 |
Maximum of Months | 0.550487E+10 | 0.233899E+09 | 0.00 | 19428330.16 | 1222334.73 | 0.474077E+09 | 0.832502E+10 | 0.00 | 1.87 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.556987E+10 | 0.00 | 0.00 | 323361.44 | 0.00 | 1214060.20 | 0.408770E+09 | 0.00 | 0.60 |
February | 0.354529E+10 | 0.00 | 0.00 | 2573914.35 | 0.00 | 0.00 | 0.249529E+10 | 0.00 | 0.79 |
March | 0.151699E+10 | 0.00 | 0.00 | 8957675.27 | 0.00 | 0.00 | 0.710822E+10 | 0.00 | 1.18 |
April | 0.778682E+09 | 4943797.91 | 0.00 | 16191548.54 | 0.00 | 0.00 | 0.931512E+10 | 0.00 | 1.79 |
May | 0.127319E+10 | 177979.01 | 0.00 | 17449831.98 | 0.00 | 0.00 | 0.751736E+10 | 0.00 | 1.93 |
June | 0.584449E+09 | 10170114.88 | 0.00 | 18591439.59 | 970566.21 | 0.00 | 0.790296E+10 | 0.00 | 2.39 |
July | 0.844771E+09 | 73013102.90 | 0.00 | 23350742.05 | 81085.51 | 0.00 | 0.742381E+10 | 0.00 | 2.83 |
August | 0.101457E+10 | 0.220461E+09 | 0.00 | 23789295.88 | 583061.75 | 0.00 | 0.664599E+10 | 0.00 | 2.69 |
September | 0.119631E+10 | 0.00 | 0.00 | 13497892.98 | 0.00 | 0.00 | 0.589905E+10 | 0.00 | 1.93 |
October | 0.189871E+10 | 0.00 | 0.00 | 7213195.47 | 0.00 | 0.00 | 0.564809E+10 | 0.00 | 1.28 |
November | 0.220929E+10 | 0.00 | 0.00 | 4430246.92 | 0.00 | 0.00 | 0.416820E+10 | 0.00 | 0.84 |
December | 0.256849E+10 | 0.00 | 0.00 | 4137702.26 | 0.00 | 0.00 | 0.387703E+10 | 0.00 | 0.68 |
Annual Sum or Average | 0.230006E+11 | 0.308766E+09 | 0.00 | 0.140507E+09 | 1634713.48 | 1214060.20 | 0.684099E+11 | 0.00 | 1.58 |
Minimum of Months | 0.584449E+09 | 0.00 | 0.00 | 323361.44 | 0.00 | 0.00 | 0.408770E+09 | 0.00 | 0.60 |
Maximum of Months | 0.556987E+10 | 0.220461E+09 | 0.00 | 23789295.88 | 970566.21 | 1214060.20 | 0.931512E+10 | 0.00 | 2.83 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.186302E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.229204E+11 | 0.00 | 0.00 | 0.29 |
February | 0.247631E+11 | 0.00 | 0.00 | 247313.39 | 0.00 | 0.125870E+11 | 0.570363E+09 | 0.00 | 0.32 |
March | 0.363528E+11 | 0.00 | 0.00 | 1169451.28 | 0.00 | 0.413653E+10 | 0.201005E+10 | 0.00 | 0.37 |
April | 0.263475E+11 | 25374492.34 | 0.00 | 16546549.40 | 7099708.14 | 0.118020E+10 | 0.122732E+11 | 0.00 | 0.44 |
May | 0.193279E+11 | 2678476.70 | 0.00 | 51142516.43 | 0.00 | 29345222.37 | 0.316497E+11 | 0.00 | 0.71 |
June | 0.116405E+11 | 32260939.64 | 0.00 | 75673288.07 | 6264685.15 | 0.00 | 0.386509E+11 | 0.00 | 0.89 |
July | 0.933744E+10 | 0.314570E+09 | 0.00 | 81537976.10 | 5282692.81 | 0.00 | 0.318990E+11 | 0.00 | 0.91 |
August | 0.946680E+10 | 0.111604E+10 | 0.00 | 69270599.17 | 5587812.63 | 0.00 | 0.248240E+11 | 0.00 | 0.81 |
September | 0.200733E+11 | 202266.36 | 0.00 | 40198484.23 | 0.00 | 0.00 | 0.203503E+11 | 0.00 | 0.68 |
October | 0.328891E+11 | 0.00 | 0.00 | 6315325.50 | 0.00 | 0.108340E+10 | 0.577371E+10 | 0.00 | 0.42 |
November | 0.307535E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.764616E+10 | 0.00 | 0.00 | 0.33 |
December | 0.216442E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.190797E+11 | 0.00 | 0.00 | 0.29 |
Annual Sum or Average | 0.261226E+12 | 0.149113E+10 | 0.00 | 0.342102E+09 | 24234898.73 | 0.686628E+11 | 0.168001E+12 | 0.00 | 0.54 |
Minimum of Months | 0.933744E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.29 |
Maximum of Months | 0.363528E+11 | 0.111604E+10 | 0.00 | 81537976.10 | 7099708.14 | 0.229204E+11 | 0.386509E+11 | 0.00 | 0.91 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.238586E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.273634E+11 | 0.00 | 0.00 | 0.55 |
February | 0.332045E+11 | 0.00 | 0.00 | 290776.20 | 0.00 | 0.130171E+11 | 0.730378E+09 | 0.00 | 0.62 |
March | 0.410897E+11 | 0.00 | 0.00 | 14152896.93 | 0.00 | 0.382556E+10 | 0.102483E+11 | 0.00 | 0.73 |
April | 0.258913E+11 | 31990686.95 | 0.00 | 47833261.16 | 1440328.58 | 0.101278E+10 | 0.309970E+11 | 0.00 | 0.98 |
May | 0.246886E+11 | 2603112.79 | 0.00 | 72712166.30 | 0.00 | 79121539.04 | 0.408208E+11 | 0.00 | 1.36 |
June | 0.154967E+11 | 23399750.46 | 0.00 | 0.108944E+09 | 7776961.97 | 0.00 | 0.548313E+11 | 0.00 | 1.80 |
July | 0.136474E+11 | 0.283307E+09 | 0.00 | 0.123933E+09 | 6557919.53 | 0.00 | 0.399807E+11 | 0.00 | 1.74 |
August | 0.116574E+11 | 0.104159E+10 | 0.00 | 0.118244E+09 | 290230.08 | 0.00 | 0.355513E+11 | 0.00 | 1.70 |
September | 0.261904E+11 | 212873.36 | 0.00 | 67733549.02 | 0.00 | 6299890.35 | 0.308271E+11 | 0.00 | 1.44 |
October | 0.355300E+11 | 0.00 | 0.00 | 21371689.76 | 0.00 | 0.166512E+10 | 0.155915E+11 | 0.00 | 0.87 |
November | 0.369921E+11 | 0.00 | 0.00 | 184438.36 | 0.00 | 0.103062E+11 | 0.339782E+09 | 0.00 | 0.63 |
December | 0.274252E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.229679E+11 | 0.00 | 0.00 | 0.55 |
Annual Sum or Average | 0.315672E+12 | 0.138311E+10 | 0.00 | 0.575399E+09 | 16065440.16 | 0.802435E+11 | 0.259918E+12 | 0.00 | 1.08 |
Minimum of Months | 0.116574E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.55 |
Maximum of Months | 0.410897E+11 | 0.104159E+10 | 0.00 | 0.123933E+09 | 7776961.97 | 0.273634E+11 | 0.548313E+11 | 0.00 | 1.80 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.401359E+11 | 0.00 | 0.00 | 16043232.09 | 0.00 | 0.237867E+11 | 0.112691E+11 | 0.00 | 0.52 |
February | 0.402157E+11 | 0.00 | 0.00 | 55066605.78 | 0.00 | 0.117496E+11 | 0.315452E+11 | 0.00 | 0.73 |
March | 0.431290E+11 | 0.00 | 0.00 | 89475680.45 | 0.00 | 0.425467E+10 | 0.614488E+11 | 0.00 | 0.98 |
April | 0.331246E+11 | 0.123599E+09 | 0.00 | 98818027.64 | 0.00 | 0.155431E+10 | 0.604122E+11 | 0.00 | 1.13 |
May | 0.336119E+11 | 5628876.88 | 0.00 | 0.118682E+09 | 0.00 | 0.109862E+09 | 0.629971E+11 | 0.00 | 1.37 |
June | 0.270170E+11 | 42397276.32 | 0.00 | 0.115316E+09 | 10767302.96 | 0.00 | 0.545751E+11 | 0.00 | 1.47 |
July | 0.213940E+11 | 0.640821E+09 | 0.00 | 0.130759E+09 | 9079523.16 | 0.00 | 0.465164E+11 | 0.00 | 1.56 |
August | 0.193369E+11 | 0.253972E+10 | 0.00 | 0.140551E+09 | 7853.85 | 0.00 | 0.393144E+11 | 0.00 | 1.50 |
September | 0.292635E+11 | 866285.96 | 0.00 | 0.188798E+09 | 0.00 | 0.00 | 0.685214E+11 | 0.00 | 1.87 |
October | 0.381855E+11 | 0.00 | 0.00 | 0.116925E+09 | 0.00 | 0.129774E+10 | 0.684463E+11 | 0.00 | 1.26 |
November | 0.485899E+11 | 0.00 | 0.00 | 33230029.59 | 0.00 | 0.824111E+10 | 0.173898E+11 | 0.00 | 0.66 |
December | 0.391209E+11 | 0.00 | 0.00 | 29394466.71 | 0.00 | 0.213778E+11 | 0.190340E+11 | 0.00 | 0.57 |
Annual Sum or Average | 0.413125E+12 | 0.335304E+10 | 0.00 | 0.113306E+10 | 19854679.97 | 0.723717E+11 | 0.541470E+12 | 0.00 | 1.14 |
Minimum of Months | 0.193369E+11 | 0.00 | 0.00 | 16043232.09 | 0.00 | 0.00 | 0.112691E+11 | 0.00 | 0.52 |
Maximum of Months | 0.485899E+11 | 0.253972E+10 | 0.00 | 0.188798E+09 | 10767302.96 | 0.237867E+11 | 0.685214E+11 | 0.00 | 1.87 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.316314E+11 | 0.00 | 0.00 | 62948.27 | 0.00 | 0.222388E+11 | 0.227626E+09 | 0.00 | 0.58 |
February | 0.363764E+11 | 0.00 | 0.00 | 4690325.57 | 0.00 | 0.101445E+11 | 0.383597E+10 | 0.00 | 0.67 |
March | 0.431738E+11 | 0.00 | 0.00 | 16520267.79 | 0.00 | 0.322910E+10 | 0.134982E+11 | 0.00 | 0.82 |
April | 0.330734E+11 | 59880133.86 | 0.00 | 40453826.33 | 729921.88 | 0.701617E+09 | 0.250889E+11 | 0.00 | 1.05 |
May | 0.257843E+11 | 2460130.34 | 0.00 | 0.121817E+09 | 0.00 | 42703673.27 | 0.422282E+11 | 0.00 | 1.56 |
June | 0.193413E+11 | 0.102695E+09 | 0.00 | 0.102020E+09 | 8223489.84 | 0.00 | 0.398475E+11 | 0.00 | 1.74 |
July | 0.135929E+11 | 0.703567E+09 | 0.00 | 0.130126E+09 | 865840.96 | 0.00 | 0.383828E+11 | 0.00 | 1.96 |
August | 0.136118E+11 | 0.190378E+10 | 0.00 | 0.114052E+09 | 7328978.47 | 0.00 | 0.274646E+11 | 0.00 | 1.59 |
September | 0.257310E+11 | 205565.61 | 0.00 | 81616368.17 | 0.00 | 0.00 | 0.305107E+11 | 0.00 | 1.59 |
October | 0.420377E+11 | 0.00 | 0.00 | 18752637.25 | 0.00 | 0.787683E+09 | 0.131360E+11 | 0.00 | 0.96 |
November | 0.428090E+11 | 0.00 | 0.00 | 1672875.68 | 0.00 | 0.631393E+10 | 0.128973E+10 | 0.00 | 0.67 |
December | 0.365403E+11 | 0.00 | 0.00 | 396846.63 | 0.00 | 0.159630E+11 | 0.704429E+09 | 0.00 | 0.58 |
Annual Sum or Average | 0.363703E+12 | 0.277259E+10 | 0.00 | 0.632181E+09 | 17148231.15 | 0.594213E+11 | 0.236215E+12 | 0.00 | 1.15 |
Minimum of Months | 0.135929E+11 | 0.00 | 0.00 | 62948.27 | 0.00 | 0.00 | 0.227626E+09 | 0.00 | 0.58 |
Maximum of Months | 0.431738E+11 | 0.190378E+10 | 0.00 | 0.130126E+09 | 8223489.84 | 0.222388E+11 | 0.422282E+11 | 0.00 | 1.96 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.102137E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.288742E+10 | 0.00 | 0.00 | 0.29 |
February | 0.156138E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.200715E+10 | 0.00 | 0.00 | 0.32 |
March | 0.310154E+10 | 0.00 | 0.00 | 35037.43 | 0.00 | 0.920067E+09 | 55221766.80 | 0.00 | 0.37 |
April | 0.248063E+10 | 703730.72 | 0.00 | 1261760.81 | 198725.06 | 0.405584E+09 | 0.944093E+09 | 0.00 | 0.43 |
May | 0.212603E+10 | 0.00 | 0.00 | 4278088.03 | 0.00 | 74945050.48 | 0.273095E+10 | 0.00 | 0.68 |
June | 0.136151E+10 | 1357392.54 | 0.00 | 6888590.77 | 395575.27 | 6477309.96 | 0.358336E+10 | 0.00 | 0.89 |
July | 0.100103E+10 | 19179655.56 | 0.00 | 7928064.98 | 398324.00 | 0.00 | 0.316482E+10 | 0.00 | 0.92 |
August | 0.106047E+10 | 75597263.32 | 0.00 | 6655556.41 | 1121496.52 | 0.00 | 0.221931E+10 | 0.00 | 0.81 |
September | 0.213772E+10 | 0.00 | 0.00 | 3148149.20 | 0.00 | 33892171.83 | 0.160649E+10 | 0.00 | 0.65 |
October | 0.293220E+10 | 0.00 | 0.00 | 274990.54 | 0.00 | 0.525472E+09 | 0.220461E+09 | 0.00 | 0.41 |
November | 0.188884E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.163562E+10 | 0.00 | 0.00 | 0.33 |
December | 0.108585E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.262902E+10 | 0.00 | 0.00 | 0.28 |
Annual Sum or Average | 0.217586E+11 | 96838042.15 | 0.00 | 30470238.16 | 2114120.85 | 0.111257E+11 | 0.145247E+11 | 0.00 | 0.53 |
Minimum of Months | 0.100103E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.28 |
Maximum of Months | 0.310154E+10 | 75597263.32 | 0.00 | 7928064.98 | 1121496.52 | 0.288742E+10 | 0.358336E+10 | 0.00 | 0.92 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.151266E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.303378E+10 | 0.00 | 0.00 | 0.52 |
February | 0.226522E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.192365E+10 | 0.00 | 0.00 | 0.59 |
March | 0.344226E+10 | 0.00 | 0.00 | 884322.89 | 0.00 | 0.804548E+09 | 0.708242E+09 | 0.00 | 0.69 |
April | 0.220948E+10 | 691342.66 | 0.00 | 4167419.60 | 237773.71 | 0.305619E+09 | 0.279009E+10 | 0.00 | 0.93 |
May | 0.225150E+10 | 0.00 | 0.00 | 6754290.05 | 0.00 | 93139354.80 | 0.396473E+10 | 0.00 | 1.31 |
June | 0.143710E+10 | 1017512.25 | 0.00 | 10400874.63 | 473304.18 | 14171362.37 | 0.547415E+10 | 0.00 | 1.79 |
July | 0.122785E+10 | 16756350.69 | 0.00 | 12506582.70 | 423239.28 | 0.00 | 0.412930E+10 | 0.00 | 1.75 |
August | 0.107154E+10 | 69874013.82 | 0.00 | 11601811.92 | 445680.00 | 0.00 | 0.345146E+10 | 0.00 | 1.71 |
September | 0.238116E+10 | 0.00 | 0.00 | 6313970.70 | 0.00 | 28486752.84 | 0.286652E+10 | 0.00 | 1.38 |
October | 0.290711E+10 | 0.00 | 0.00 | 1537494.56 | 0.00 | 0.519199E+09 | 0.119755E+10 | 0.00 | 0.81 |
November | 0.242936E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.174157E+10 | 0.00 | 0.00 | 0.60 |
December | 0.161379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.273377E+10 | 0.00 | 0.00 | 0.52 |
Annual Sum or Average | 0.247490E+11 | 88339219.42 | 0.00 | 54166767.05 | 1579997.18 | 0.111979E+11 | 0.245820E+11 | 0.00 | 1.05 |
Minimum of Months | 0.107154E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.52 |
Maximum of Months | 0.344226E+10 | 69874013.82 | 0.00 | 12506582.70 | 473304.18 | 0.303378E+10 | 0.547415E+10 | 0.00 | 1.79 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.289946E+10 | 0.00 | 0.00 | 909962.13 | 0.00 | 0.326502E+10 | 0.698860E+09 | 0.00 | 0.51 |
February | 0.305431E+10 | 0.00 | 0.00 | 3815633.00 | 0.00 | 0.192372E+10 | 0.248622E+10 | 0.00 | 0.69 |
March | 0.376283E+10 | 0.00 | 0.00 | 7367919.38 | 0.00 | 0.103794E+10 | 0.529447E+10 | 0.00 | 0.93 |
April | 0.299820E+10 | 3242683.36 | 0.00 | 8999816.25 | 0.00 | 0.570235E+09 | 0.570042E+10 | 0.00 | 1.11 |
May | 0.330194E+10 | 0.00 | 0.00 | 10907589.26 | 0.00 | 0.158047E+09 | 0.627152E+10 | 0.00 | 1.34 |
June | 0.277874E+10 | 1799019.37 | 0.00 | 11042525.88 | 691625.08 | 17348465.21 | 0.557760E+10 | 0.00 | 1.49 |
July | 0.220296E+10 | 37400076.27 | 0.00 | 14344100.14 | 109429.42 | 0.00 | 0.494716E+10 | 0.00 | 1.61 |
August | 0.199206E+10 | 0.167992E+09 | 0.00 | 14281464.18 | 81697.91 | 0.00 | 0.395840E+10 | 0.00 | 1.56 |
September | 0.300199E+10 | 0.00 | 0.00 | 17908643.85 | 0.00 | 46215941.67 | 0.673227E+10 | 0.00 | 1.84 |
October | 0.333492E+10 | 0.00 | 0.00 | 9523577.51 | 0.00 | 0.579010E+09 | 0.598031E+10 | 0.00 | 1.17 |
November | 0.355432E+10 | 0.00 | 0.00 | 1977600.36 | 0.00 | 0.193008E+10 | 0.112438E+10 | 0.00 | 0.64 |
December | 0.273728E+10 | 0.00 | 0.00 | 1862087.66 | 0.00 | 0.290960E+10 | 0.125857E+10 | 0.00 | 0.53 |
Annual Sum or Average | 0.356190E+11 | 0.210434E+09 | 0.00 | 0.102941E+09 | 882752.40 | 0.124372E+11 | 0.500302E+11 | 0.00 | 1.12 |
Minimum of Months | 0.199206E+10 | 0.00 | 0.00 | 909962.13 | 0.00 | 0.00 | 0.698860E+09 | 0.00 | 0.51 |
Maximum of Months | 0.376283E+10 | 0.167992E+09 | 0.00 | 17908643.85 | 691625.08 | 0.326502E+10 | 0.673227E+10 | 0.00 | 1.84 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.212458E+10 | 0.00 | 0.00 | 412.11 | 0.00 | 0.289978E+10 | 7304160.66 | 0.00 | 0.58 |
February | 0.271983E+10 | 0.00 | 0.00 | 334376.19 | 0.00 | 0.165768E+10 | 0.310418E+09 | 0.00 | 0.67 |
March | 0.381158E+10 | 0.00 | 0.00 | 1343908.83 | 0.00 | 0.731166E+09 | 0.119435E+10 | 0.00 | 0.81 |
April | 0.310200E+10 | 1706663.41 | 0.00 | 3845120.54 | 0.00 | 0.325919E+09 | 0.238679E+10 | 0.00 | 1.07 |
May | 0.268406E+10 | 0.00 | 0.00 | 11713310.61 | 0.00 | 63203323.29 | 0.418731E+10 | 0.00 | 1.55 |
June | 0.208294E+10 | 4051992.23 | 0.00 | 9920131.94 | 525104.28 | 1472011.51 | 0.401985E+10 | 0.00 | 1.79 |
July | 0.142349E+10 | 42731036.16 | 0.00 | 15728596.91 | 291291.92 | 0.00 | 0.404604E+10 | 0.00 | 2.03 |
August | 0.147347E+10 | 0.126281E+09 | 0.00 | 11171853.35 | 1241677.49 | 0.00 | 0.264360E+10 | 0.00 | 1.62 |
September | 0.279341E+10 | 0.00 | 0.00 | 7613834.05 | 0.00 | 16267216.71 | 0.274009E+10 | 0.00 | 1.58 |
October | 0.367013E+10 | 0.00 | 0.00 | 1569480.12 | 0.00 | 0.437497E+09 | 0.113252E+10 | 0.00 | 0.94 |
November | 0.306135E+10 | 0.00 | 0.00 | 105901.89 | 0.00 | 0.147111E+10 | 91445083.46 | 0.00 | 0.67 |
December | 0.226885E+10 | 0.00 | 0.00 | 7195.46 | 0.00 | 0.252331E+10 | 17997319.22 | 0.00 | 0.57 |
Annual Sum or Average | 0.312157E+11 | 0.174770E+09 | 0.00 | 63354122.01 | 2058073.70 | 0.101274E+11 | 0.227777E+11 | 0.00 | 1.16 |
Minimum of Months | 0.142349E+10 | 0.00 | 0.00 | 412.11 | 0.00 | 0.00 | 7304160.66 | 0.00 | 0.57 |
Maximum of Months | 0.381158E+10 | 0.126281E+09 | 0.00 | 15728596.91 | 1241677.49 | 0.289978E+10 | 0.418731E+10 | 0.00 | 2.03 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 2984235.88 | 0.00 | 0.00 | 0.621563E+09 | 0.00 | 0.28 |
February | 0.00 | 0.00 | 0.00 | 7230960.69 | 0.00 | 0.00 | 0.514627E+09 | 0.00 | 0.29 |
March | 0.00 | 0.00 | 0.00 | 14088411.47 | 0.00 | 0.00 | 0.542073E+09 | 0.00 | 0.31 |
April | 0.00 | 0.00 | 0.00 | 17467919.00 | 0.00 | 0.00 | 0.421294E+09 | 0.00 | 0.29 |
May | 0.00 | 15139.89 | 0.00 | 4187243.29 | 0.00 | 0.00 | 0.379783E+09 | 0.00 | 0.29 |
June | 0.00 | 0.00 | 0.00 | 8691850.95 | 0.00 | 0.00 | 0.296390E+09 | 0.00 | 0.30 |
July | 0.00 | 3859760.95 | 0.00 | 11350174.77 | 0.00 | 0.00 | 0.170164E+09 | 0.00 | 0.28 |
August | 0.00 | 12590219.52 | 0.00 | 14794124.08 | 0.00 | 0.00 | 0.129203E+09 | 0.00 | 0.31 |
September | 0.00 | 89778.03 | 0.00 | 4051267.49 | 0.00 | 0.00 | 0.255426E+09 | 0.00 | 0.29 |
October | 0.00 | 0.00 | 0.00 | 8310361.21 | 0.00 | 0.00 | 0.426088E+09 | 0.00 | 0.28 |
November | 0.00 | 0.00 | 0.00 | 11888103.79 | 0.00 | 0.00 | 0.496232E+09 | 0.00 | 0.28 |
December | 0.00 | 0.00 | 0.00 | 16783614.85 | 0.00 | 0.00 | 0.576770E+09 | 0.00 | 0.28 |
Annual Sum or Average | 0.00 | 16554898.38 | 0.00 | 0.121828E+09 | 0.00 | 0.00 | 0.482961E+10 | 0.00 | 0.29 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 2984235.88 | 0.00 | 0.00 | 0.129203E+09 | 0.00 | 0.28 |
Maximum of Months | 0.00 | 12590219.52 | 0.00 | 17467919.00 | 0.00 | 0.00 | 0.621563E+09 | 0.00 | 0.31 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.458675E+09 | 0.00 | 0.00 | 13573469.94 | 0.00 | 0.00 | 0.579568E+10 | 0.00 | 0.28 |
February | 0.00 | 0.00 | 0.00 | 57530244.57 | 0.00 | 0.00 | 0.516323E+10 | 0.00 | 0.29 |
March | 0.00 | 0.00 | 0.00 | 0.124004E+09 | 0.00 | 0.00 | 0.543680E+10 | 0.00 | 0.31 |
April | 0.00 | 0.00 | 0.00 | 0.160114E+09 | 0.00 | 0.00 | 0.422624E+10 | 0.00 | 0.29 |
May | 0.00 | 125007.69 | 0.00 | 35460025.82 | 0.00 | 0.00 | 0.381038E+10 | 0.00 | 0.29 |
June | 0.00 | 0.00 | 0.00 | 79902770.96 | 0.00 | 0.00 | 0.297245E+10 | 0.00 | 0.30 |
July | 0.00 | 38218511.43 | 0.00 | 0.106709E+09 | 0.00 | 0.00 | 0.170951E+10 | 0.00 | 0.28 |
August | 0.00 | 0.125256E+09 | 0.00 | 0.139833E+09 | 0.00 | 0.00 | 0.130106E+10 | 0.00 | 0.31 |
September | 0.00 | 717714.21 | 0.00 | 34472491.91 | 0.00 | 0.00 | 0.258031E+10 | 0.00 | 0.29 |
October | 0.00 | 0.00 | 0.00 | 70829459.72 | 0.00 | 0.00 | 0.427487E+10 | 0.00 | 0.28 |
November | 0.00 | 0.00 | 0.00 | 0.101375E+09 | 0.00 | 0.00 | 0.497991E+10 | 0.00 | 0.28 |
December | 0.00 | 0.00 | 0.00 | 0.145469E+09 | 0.00 | 0.00 | 0.578981E+10 | 0.00 | 0.28 |
Annual Sum or Average | 0.458675E+09 | 0.164317E+09 | 0.00 | 0.106927E+10 | 0.00 | 0.00 | 0.480403E+11 | 0.00 | 0.29 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 13573469.94 | 0.00 | 0.00 | 0.130106E+10 | 0.00 | 0.28 |
Maximum of Months | 0.458675E+09 | 0.125256E+09 | 0.00 | 0.160114E+09 | 0.00 | 0.00 | 0.579568E+10 | 0.00 | 0.31 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.205012E+09 | 0.00 | 0.00 | 730395.13 | 0.00 | 0.00 | 0.415231E+09 | 0.00 | 0.28 |
February | 0.00 | 0.00 | 0.00 | 4983331.06 | 0.00 | 0.00 | 0.517178E+09 | 0.00 | 0.29 |
March | 0.00 | 0.00 | 0.00 | 11606526.41 | 0.00 | 0.00 | 0.544539E+09 | 0.00 | 0.31 |
April | 0.00 | 0.00 | 0.00 | 15534379.13 | 0.00 | 0.00 | 0.423151E+09 | 0.00 | 0.29 |
May | 0.00 | 12193.59 | 0.00 | 3258029.57 | 0.00 | 0.00 | 0.381628E+09 | 0.00 | 0.29 |
June | 0.00 | 0.00 | 0.00 | 7861337.41 | 0.00 | 0.00 | 0.297464E+09 | 0.00 | 0.30 |
July | 0.00 | 3840645.01 | 0.00 | 10605661.41 | 0.00 | 0.00 | 0.171034E+09 | 0.00 | 0.28 |
August | 0.00 | 12559621.60 | 0.00 | 13867521.36 | 0.00 | 0.00 | 0.130262E+09 | 0.00 | 0.31 |
September | 0.00 | 68480.16 | 0.00 | 3118256.26 | 0.00 | 0.00 | 0.259609E+09 | 0.00 | 0.29 |
October | 0.00 | 0.00 | 0.00 | 6414813.21 | 0.00 | 0.00 | 0.428488E+09 | 0.00 | 0.28 |
November | 0.00 | 0.00 | 0.00 | 9287090.48 | 0.00 | 0.00 | 0.499023E+09 | 0.00 | 0.28 |
December | 0.00 | 0.00 | 0.00 | 13576108.22 | 0.00 | 0.00 | 0.579971E+09 | 0.00 | 0.28 |
Annual Sum or Average | 0.205012E+09 | 16480940.36 | 0.00 | 0.100843E+09 | 0.00 | 0.00 | 0.464758E+10 | 0.00 | 0.29 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 730395.13 | 0.00 | 0.00 | 0.130262E+09 | 0.00 | 0.28 |
Maximum of Months | 0.205012E+09 | 12559621.60 | 0.00 | 15534379.13 | 0.00 | 0.00 | 0.579971E+09 | 0.00 | 0.31 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.541995E+09 | 0.00 | 0.00 | 0.419689E+12 | 0.00 | 9.14 |
February | 0.00 | 0.00 | 0.00 | 0.977388E+09 | 0.00 | 0.00 | 0.646489E+12 | 0.00 | 17.40 |
March | 0.00 | 0.00 | 0.00 | 0.148788E+10 | 0.00 | 0.00 | 0.991823E+12 | 0.00 | 27.38 |
April | 0.00 | 0.00 | 0.00 | 0.220285E+10 | 0.00 | 0.00 | 0.108804E+13 | 0.00 | 37.54 |
May | 0.00 | 0.00 | 0.00 | 0.574789E+09 | 0.00 | 0.00 | 0.369521E+12 | 0.00 | 16.44 |
June | 0.00 | 0.00 | 0.00 | 0.111269E+10 | 0.00 | 0.00 | 0.546093E+12 | 0.00 | 31.02 |
July | 0.00 | 0.922454E+09 | 0.00 | 0.198802E+10 | 0.00 | 0.00 | 0.601552E+12 | 0.00 | 39.43 |
August | 0.00 | 0.115027E+10 | 0.00 | 0.275315E+10 | 0.00 | 0.00 | 0.449851E+12 | 0.00 | 41.22 |
September | 0.00 | 0.00 | 0.00 | 0.538955E+09 | 0.00 | 0.00 | 0.327388E+12 | 0.00 | 19.00 |
October | 0.00 | 0.00 | 0.00 | 0.103482E+10 | 0.00 | 0.00 | 0.633766E+12 | 0.00 | 23.44 |
November | 0.00 | 0.00 | 0.00 | 0.145977E+10 | 0.00 | 0.00 | 0.907266E+12 | 0.00 | 27.18 |
December | 0.00 | 0.00 | 0.00 | 0.207550E+10 | 0.00 | 0.00 | 0.127710E+13 | 0.00 | 30.32 |
Annual Sum or Average | 0.00 | 0.207272E+10 | 0.00 | 0.167478E+11 | 0.00 | 0.00 | 0.825858E+13 | 0.00 | 26.68 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.538955E+09 | 0.00 | 0.00 | 0.327388E+12 | 0.00 | 9.14 |
Maximum of Months | 0.00 | 0.115027E+10 | 0.00 | 0.275315E+10 | 0.00 | 0.00 | 0.127710E+13 | 0.00 | 41.22 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 08:44:06
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.119767E+12 | 0.229380E+11 | 0.00 | 0.209841E+13 | 0.137978E+12 |
February | 0.230458E+12 | 0.208195E+11 | 0.00 | 0.238002E+13 | 0.188727E+12 |
March | 0.419445E+12 | 0.198332E+11 | 0.00 | 0.311531E+13 | 0.274743E+12 |
April | 0.646861E+12 | 0.190682E+11 | 0.00 | 0.326925E+13 | 0.597861E+12 |
May | 0.850499E+12 | 0.151933E+11 | 0.00 | 0.264655E+13 | 0.365414E+12 |
June | 0.863771E+12 | 0.125551E+11 | 0.00 | 0.263808E+13 | 0.716388E+12 |
July | 0.907589E+12 | 0.109019E+11 | 0.00 | 0.268438E+13 | 0.145896E+13 |
August | 0.712110E+12 | 0.860775E+10 | 0.00 | 0.219680E+13 | 0.230912E+13 |
September | 0.494773E+12 | 0.725356E+10 | 0.00 | 0.259136E+13 | 0.511311E+12 |
October | 0.316029E+12 | 0.159927E+11 | 0.00 | 0.290894E+13 | 0.238205E+12 |
November | 0.136357E+12 | 0.183863E+11 | 0.00 | 0.292554E+13 | 0.270772E+12 |
December | 0.899266E+11 | 0.197283E+11 | 0.00 | 0.314746E+13 | 0.363400E+12 |
Annual Sum or Average | 0.578758E+13 | 0.191278E+12 | 0.00 | 0.326021E+14 | 0.743287E+13 |
Minimum of Months | 0.899266E+11 | 0.725356E+10 | 0.00 | 0.209841E+13 | 0.137978E+12 |
Maximum of Months | 0.907589E+12 | 0.229380E+11 | 0.00 | 0.326925E+13 | 0.230912E+13 |