Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:43
Tabular Output Report in Format: HTML
Building: OfficeLarge
Environment: RUNPERIOD 1 ** Tampa-MacDill AFB FL USA TMY3 WMO#=747880
Simulation Timestamp: 2023-10-16 08:44:04
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 08:44:04
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 32866.87 | 709.56 | 709.56 |
Net Site Energy | 32866.87 | 709.56 | 709.56 |
Total Source Energy | 102351.52 | 2209.64 | 2209.64 |
Net Source Energy | 102351.52 | 2209.64 | 2209.64 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 46320.38 |
Net Conditioned Building Area | 46320.38 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 162.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 5755.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 3924.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 695.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 14676.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 1934.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 2185.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 815.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 1977.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13682.59 |
Humidification | 1.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.58 |
Heat Recovery | 65.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 672.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2280.17 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 32032.57 | 834.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15963.34 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler | 0.00 | 162.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 5755.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 3924.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 695.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 5334.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DataCenterPlugLoads | 9341.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 80.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 1848.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 5.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | General | 2185.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 815.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 1977.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13682.59 |
Humidification | General | 1.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.58 |
Heat Recovery | General | 65.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2280.17 | |
Water Heater | 0.00 | 672.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 162.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 5755.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 3924.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 695.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 14676.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 1934.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 2185.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 815.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 1977.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13682.59 |
Humidification | Unassigned | 1.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.58 |
Heat Recovery | Unassigned | 65.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 0.00 | 672.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2280.17 |
Refrigeration | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 99.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 231.79 | 18.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.34 |
Other | 360.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 691.54 | 18.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.34 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 99.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 231.79 | 18.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.34 |
Other | 360.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 691.54 | 18.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.34 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 32032.565 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 32032.565 | 100.00 |
Total On-Site and Utility Electric Sources | 32032.565 | 100.00 |
Total Electricity End Uses | 32032.565 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | 0.00 |
Air to Air Heat Recovery for Cooling | 4000.43 | 97.49 |
Air to Air Heat Recovery for Heating | 103.07 | 2.51 |
High-Temperature Geothermal* | 0.00 | 0.00 |
Solar Water Thermal | 0.00 | 0.00 |
Solar Air Thermal | 0.00 | 0.00 |
Total On-Site Thermal Sources | 4103.50 | 100.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 15963.34 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 15963.34 | 100.00 |
Total Water End Uses | 15963.34 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 1.50 |
Time Setpoint Not Met During Occupied Cooling | 736.00 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 5943.00 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2013
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICELARGE
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 2A
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_FL_TAMPA
| Environment |ZoneCoolingSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |ZoneHeatingSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |ZoneElectricSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |SpaceGainsMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |PeakSpaceGainsMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |SpaceGainComponentsAtCoolingPeakMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |ComfortReportSimple55Monthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |OccupantComfortDataSummaryMonthly
| DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 | BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 |ChillerReportMonthly
| COOLSYS1 CHILLER1 | COOLSYS1 CHILLER2 |TowerReportMonthly
| CENTRAL TOWER | TOWERWATERSYS COOLTOWER 1 | TOWERWATERSYS COOLTOWER 2 |BoilerReportMonthly
| HEATSYS1 BOILER | CENTRAL BOILER |DXReportMonthly
| VAV_BOT WITH REHEAT COOLING COIL | VAV_MID WITH REHEAT COOLING COIL | VAV_TOP WITH REHEAT COOLING COIL | CAV_BAS COOLING COIL | AIRLOOP DATACENTER BASEMENT COOLING COIL | AIRLOOP DATACENTER BOT COOLING COIL | AIRLOOP DATACENTER MID COOLING COIL | AIRLOOP DATACENTER TOP COOLING COIL |WindowReportMonthly
| PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW |WindowEnergyReportMonthly
| PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW |WindowZoneSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |WindowEnergyZoneSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWHSYS1 WATER HEATER |DaylightingReportMonthly
| PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_4_DAYLCTRL |CoilReportMonthly
| VAV_BOT WITH REHEAT HEATING COIL | CORE_BOTTOM VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | VAV_MID WITH REHEAT HEATING COIL | CORE_MID VAV BOX REHEAT COIL | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | VAV_TOP WITH REHEAT HEATING COIL | CORE_TOP VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | CAV_BAS HEATING COIL | AIRLOOP DATACENTER BASEMENT HEATING COIL | AIRLOOP DATACENTER BOT HEATING COIL | AIRLOOP DATACENTER MID HEATING COIL | AIRLOOP DATACENTER TOP HEATING COIL | AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | AIRLOOP DATACENTER BOT_SUPPHEATCOIL | AIRLOOP DATACENTER MID_SUPPHEATCOIL | AIRLOOP DATACENTER TOP_SUPPHEATCOIL | VAV_BOT WITH REHEAT COOLING COIL | VAV_MID WITH REHEAT COOLING COIL | VAV_TOP WITH REHEAT COOLING COIL | CAV_BAS COOLING COIL | AIRLOOP DATACENTER BASEMENT COOLING COIL | AIRLOOP DATACENTER BOT COOLING COIL | AIRLOOP DATACENTER MID COOLING COIL | AIRLOOP DATACENTER TOP COOLING COIL |PlantLoopDemandReportMonthly
| HEATSYS1 | COOLSYS1_SUPPLY | COOLSYS1_DEMAND | SINGLE WATER PLANT LOOP | SWHSYS1 | TOWERWATERSYS |FanReportMonthly
| CAV_BAS FAN | VAV_BOT WITH REHEAT FAN | VAV_MID WITH REHEAT FAN | VAV_TOP WITH REHEAT FAN | AIRLOOP DATACENTER BASEMENT SUPPLY FAN | AIRLOOP DATACENTER BOT SUPPLY FAN | AIRLOOP DATACENTER MID SUPPLY FAN | AIRLOOP DATACENTER TOP SUPPLY FAN |PumpReportMonthly
| HEATSYS1 PUMP | COOLSYS1 PUMP SECONDARY | COOLSYS1 CHILLER1 PUMP | COOLSYS1 CHILLER2 PUMP | PLANT CIRC PUMP | SWHSYS1 PUMP | TOWERWATERSYS PUMP |CondLoopDemandReportMonthly
| HEATSYS1 | COOLSYS1_SUPPLY | COOLSYS1_DEMAND | SINGLE WATER PLANT LOOP | SWHSYS1 | TOWERWATERSYS |ZoneTemperatureOscillationReportMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |AirLoopSystemEnergyAndWaterUseMonthly
| VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | CAV_BAS | AIRLOOP DATACENTER BASEMENT | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |AirLoopSystemComponentLoadsMonthly
| VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | CAV_BAS | AIRLOOP DATACENTER BASEMENT | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |AirLoopSystemComponentEnergyUseMonthly
| VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | CAV_BAS | AIRLOOP DATACENTER BASEMENT | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |MechanicalVentilationLoadsMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 08:44:04
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:43 |
RunPeriod | RUNPERIOD 1 |
Weather File | Tampa-MacDill AFB FL USA TMY3 WMO#=747880 |
Latitude [deg] | 27.85 |
Longitude [deg] | -82.5 |
Elevation [m] | 8.00 |
Time Zone | -5.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 12183.89 | 3655.17 | 2436.78 | 3655.17 | 2436.78 |
Above Ground Wall Area [m2] | 11589.54 | 3476.86 | 2317.91 | 3476.86 | 2317.91 |
Window Opening Area [m2] | 4635.80 | 1390.74 | 927.16 | 1390.74 | 927.16 |
Gross Window-Wall Ratio [%] | 38.05 | 38.05 | 38.05 | 38.05 | 38.05 |
Above Ground Window-Wall Ratio [%] | 40.00 | 40.00 | 40.00 | 40.00 | 40.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 12183.89 | 3655.17 | 2436.78 | 3655.17 | 2436.78 |
Above Ground Wall Area [m2] | 11589.54 | 3476.86 | 2317.91 | 3476.86 | 2317.91 |
Window Opening Area [m2] | 4635.80 | 1390.74 | 927.16 | 1390.74 | 927.16 |
Gross Window-Wall Ratio [%] | 38.05 | 38.05 | 38.05 | 38.05 | 38.05 |
Above Ground Window-Wall Ratio [%] | 40.00 | 40.00 | 40.00 | 40.00 | 40.00 |
Total | |
Gross Roof Area [m2] | 3563.11 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
BASEMENT | 2779.43 | Yes | Yes | 6779.02 | 1.00 | 0.00 | 397.05 | 0.00 | 0.00 | 10.2732 | 18.58 | 4.8418 |
CORE_BOTTOM | 2496.12 | Yes | Yes | 6849.35 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.2732 | 18.58 | 8.0697 |
CORE_MID | 2496.12 | Yes | Yes | 6849.35 | 10.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.2732 | 18.58 | 8.0696 |
CORE_TOP | 2496.12 | Yes | Yes | 6849.35 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.2732 | 18.58 | 8.0696 |
PERIMETER_BOT_ZN_3 | 313.41 | Yes | Yes | 860.00 | 1.00 | 200.61 | 0.00 | 115.90 | 115.90 | 10.2732 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_2 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 77.26 | 77.26 | 10.2732 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_1 | 313.42 | Yes | Yes | 860.02 | 1.00 | 200.61 | 0.00 | 115.90 | 115.90 | 10.2732 | 18.58 | 8.0699 |
PERIMETER_BOT_ZN_4 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 77.26 | 77.26 | 10.2732 | 18.58 | 8.0699 |
PERIMETER_MID_ZN_3 | 313.41 | Yes | Yes | 860.00 | 10.00 | 200.61 | 0.00 | 115.90 | 115.90 | 10.2732 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_2 | 201.98 | Yes | Yes | 554.22 | 10.00 | 133.74 | 0.00 | 77.26 | 77.26 | 10.2732 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_1 | 313.42 | Yes | Yes | 860.02 | 10.00 | 200.61 | 0.00 | 115.90 | 115.90 | 10.2732 | 18.58 | 8.0699 |
PERIMETER_MID_ZN_4 | 201.98 | Yes | Yes | 554.22 | 10.00 | 133.74 | 0.00 | 77.26 | 77.26 | 10.2732 | 18.58 | 8.0699 |
PERIMETER_TOP_ZN_3 | 313.41 | Yes | Yes | 860.00 | 1.00 | 200.61 | 0.00 | 115.90 | 115.90 | 10.2732 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_2 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 77.26 | 77.26 | 10.2732 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_1 | 313.42 | Yes | Yes | 860.02 | 1.00 | 200.61 | 0.00 | 115.90 | 115.90 | 10.2732 | 18.58 | 8.0699 |
PERIMETER_TOP_ZN_4 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 77.26 | 77.26 | 10.2732 | 18.58 | 8.0699 |
GROUNDFLOOR_PLENUM | 3563.11 | Yes | No | 4344.14 | 1.00 | 297.11 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
MIDFLOOR_PLENUM | 3563.11 | Yes | No | 4344.14 | 10.00 | 297.11 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
TOPFLOOR_PLENUM | 3563.11 | Yes | No | 4344.14 | 1.00 | 297.11 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
DATACENTER_BOT_ZN_6 | 36.20 | Yes | Yes | 99.34 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.8735 | 18.58 | 215.2992 |
DATACENTER_MID_ZN_6 | 36.20 | Yes | Yes | 99.34 | 10.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.8735 | 18.58 | 215.2992 |
DATACENTER_TOP_ZN_6 | 36.20 | Yes | Yes | 99.34 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.8735 | 18.58 | 215.2992 |
DATACENTER_BASEMENT_ZN_6 | 783.68 | Yes | Yes | 1911.37 | 1.00 | 0.00 | 197.31 | 0.00 | 0.00 | 10.2732 | 18.58 | 484.4232 |
Total | 46320.38 | 126016.35 | 8024.24 | 594.36 | 4635.80 | 4635.80 | 10.3445 | 18.58 | 17.8789 | |||
Conditioned Total | 46320.38 | 126016.35 | 8024.24 | 594.36 | 4635.80 | 4635.80 | 10.3445 | 18.58 | 17.8789 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 42757.27 | 52129.67 | 3565.29 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
BASEMENT | 2779.43 | Yes | Yes | 1.00 | BASEMENT | GENERAL | BASEMENT | 10.2732 | 18.58 | 4.8418 | |
CORE_BOTTOM | 2496.12 | Yes | Yes | 1.00 | CORE_BOTTOM | GENERAL | CORE_BOTTOM | 10.2732 | 18.58 | 8.0697 | |
CORE_MID | 2496.12 | Yes | Yes | 10.00 | CORE_MID | GENERAL | CORE_MID | 10.2732 | 18.58 | 8.0696 | |
CORE_TOP | 2496.12 | Yes | Yes | 1.00 | CORE_TOP | GENERAL | CORE_TOP | 10.2732 | 18.58 | 8.0696 | |
PERIMETER_BOT_ZN_3 | 313.41 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_3 | GENERAL | PERIMETER_BOT_ZN_3 | 10.2732 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_2 | 201.98 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_2 | GENERAL | PERIMETER_BOT_ZN_2 | 10.2732 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_1 | 313.42 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_1 | GENERAL | PERIMETER_BOT_ZN_1 | 10.2732 | 18.58 | 8.0699 | |
PERIMETER_BOT_ZN_4 | 201.98 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_4 | GENERAL | PERIMETER_BOT_ZN_4 | 10.2732 | 18.58 | 8.0699 | |
PERIMETER_MID_ZN_3 | 313.41 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_3 | GENERAL | PERIMETER_MID_ZN_3 | 10.2732 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_2 | 201.98 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_2 | GENERAL | PERIMETER_MID_ZN_2 | 10.2732 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_1 | 313.42 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_1 | GENERAL | PERIMETER_MID_ZN_1 | 10.2732 | 18.58 | 8.0699 | |
PERIMETER_MID_ZN_4 | 201.98 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_4 | GENERAL | PERIMETER_MID_ZN_4 | 10.2732 | 18.58 | 8.0699 | |
PERIMETER_TOP_ZN_3 | 313.41 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_3 | GENERAL | PERIMETER_TOP_ZN_3 | 10.2732 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_2 | 201.98 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_2 | GENERAL | PERIMETER_TOP_ZN_2 | 10.2732 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_1 | 313.42 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_1 | GENERAL | PERIMETER_TOP_ZN_1 | 10.2732 | 18.58 | 8.0699 | |
PERIMETER_TOP_ZN_4 | 201.98 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_4 | GENERAL | PERIMETER_TOP_ZN_4 | 10.2732 | 18.58 | 8.0699 | |
GROUNDFLOOR_PLENUM | 3563.11 | Yes | No | 1.00 | GROUNDFLOOR_PLENUM | GENERAL | GROUNDFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
MIDFLOOR_PLENUM | 3563.11 | Yes | No | 10.00 | MIDFLOOR_PLENUM | GENERAL | MIDFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
TOPFLOOR_PLENUM | 3563.11 | Yes | No | 1.00 | TOPFLOOR_PLENUM | GENERAL | TOPFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
DATACENTER_BOT_ZN_6 | 36.20 | Yes | Yes | 1.00 | DATACENTER_BOT_ZN_6 | GENERAL | DATACENTER_BOT_ZN_6 | 17.8735 | 18.58 | 215.2992 | |
DATACENTER_MID_ZN_6 | 36.20 | Yes | Yes | 10.00 | DATACENTER_MID_ZN_6 | GENERAL | DATACENTER_MID_ZN_6 | 17.8735 | 18.58 | 215.2992 | |
DATACENTER_TOP_ZN_6 | 36.20 | Yes | Yes | 1.00 | DATACENTER_TOP_ZN_6 | GENERAL | DATACENTER_TOP_ZN_6 | 17.8735 | 18.58 | 215.2992 | |
DATACENTER_BASEMENT_ZN_6 | 783.68 | Yes | Yes | 1.00 | DATACENTER_BASEMENT_ZN_6 | GENERAL | DATACENTER_BASEMENT_ZN_6 | 10.2732 | 18.58 | 484.4232 | |
Total | 46320.38 | 10.3445 | 9.29 | 17.8789 | |||||||
Conditioned Total | 46320.38 | 10.3445 | 9.29 | 17.8789 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 42757.27 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 46320.38 | 46320.38 | 0.00 | 42757.27 | 3.1788 | 60.38 | 10.8345 |
Total | 46320.38 | 46320.38 | 0.00 | 42757.27 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:44:04
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 03-AUG-15:30 | 21-DEC-07:10 | - | - | - | - | - | - | - | - | - | - | 30-AUG-15:00 |
Heating | 0.00 | 763980.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 472240.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 332294.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 778371.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 84450.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 147115.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 62781.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 95997.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 5613.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 30848.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 1978865.65 | 794828.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler | 0.00 | 763980.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 472240.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 332294.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 305206.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DataCenterPlugLoads | 473165.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 5015.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 79171.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 263.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | General | 147115.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 62781.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 95997.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 5613.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Water Heater | 0.00 | 30848.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:44:04
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 175.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 18226.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 12427.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 2202.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 46480.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 6127.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 6922.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 2584.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 6263.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 4.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 207.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 728.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 101447.13 | 904.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 3.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 393.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 268.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 47.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1003.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 132.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 149.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 55.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 135.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 4.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 15.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 2190.12 | 19.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 3.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 393.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 268.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 47.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1003.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 132.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 149.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 55.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 135.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 4.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 15.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 2190.12 | 19.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:44:04
AirTerminal:SingleDuct:ConstantVolume:NoReheatDesign Size Maximum Air Flow Rate [m3/s] | |
BASEMENT DIRECT AIR | 6.13 |
DATACENTER_BOT_ZN_6 DIRECT AIR | 0.480202 |
DATACENTER_MID_ZN_6 DIRECT AIR | 4.57 |
DATACENTER_TOP_ZN_6 DIRECT AIR | 0.466051 |
DATACENTER_BASEMENT_ZN_6 DIRECT AIR | 21.44 |
Design Size Maximum Air Flow Rate [m3/s] | Design Size Constant Minimum Air Flow Fraction | User-Specified Constant Minimum Air Flow Fraction | Design Size Minimum Air Flow Rate [m3/s] | Design Size Maximum Flow Fraction during Reheat [] | User-Specified Maximum Flow Fraction during Reheat [] | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | Design Size Maximum Reheat Water Flow Rate [m3/s] | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | |
CORE_BOTTOM VAV BOX COMPONENT | 6.18 | 0.307874 | 0.314000 | 1.94 | 0.820997 | 0.500000 | 0.001238 | 0.000171 | 1.94 | 12.80 | 0.008000 |
CORE_MID VAV BOX COMPONENT | 58.05 | 0.327641 | 0.327000 | 18.98 | 0.873710 | 0.500000 | 0.001163 | 0.003281 | 18.98 | 12.80 | 0.008000 |
CORE_TOP VAV BOX COMPONENT | 5.73 | 0.331819 | 0.340000 | 1.95 | 0.884851 | 0.500000 | 0.001148 | 0.000542 | 1.95 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | 1.02 | 0.233011 | 0.238000 | 0.243934 | 0.621363 | 0.500000 | 0.001635 | 0.000055 | 0.243934 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | 1.12 | 0.137979 | 0.200000 | 0.223085 | 0.367944 | 0.500000 | 0.002761 | 0.000045 | 0.223085 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | 1.27 | 0.188550 | 0.200000 | 0.253329 | 0.502800 | 0.500000 | 0.002021 | 0.000071 | 0.253329 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | 1.40 | 0.110212 | 0.200000 | 0.279290 | 0.300000 | 0.500000 | 0.003457 | 0.000038 | 0.279290 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_3 VAV BOX COMPONENT | 9.62 | 0.248357 | 0.248000 | 2.38 | 0.662285 | 0.500000 | 0.001534 | 0.001390 | 4.74 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_2 VAV BOX COMPONENT | 11.47 | 0.134180 | 0.200000 | 2.29 | 0.357813 | 0.500000 | 0.002839 | 0.000926 | 3.16 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_1 VAV BOX COMPONENT | 12.08 | 0.197667 | 0.200000 | 2.42 | 0.527113 | 0.500000 | 0.001927 | 0.001376 | 4.69 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_4 VAV BOX COMPONENT | 12.18 | 0.126400 | 0.200000 | 2.44 | 0.337066 | 0.500000 | 0.003014 | 0.000830 | 2.83 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | 1.08 | 0.220842 | 0.226000 | 0.244398 | 0.588913 | 0.500000 | 0.001725 | 0.000178 | 0.606672 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | 1.16 | 0.132544 | 0.200000 | 0.232233 | 0.353450 | 0.500000 | 0.002875 | 0.000117 | 0.400713 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | 1.32 | 0.180968 | 0.200000 | 0.263943 | 0.482581 | 0.500000 | 0.002105 | 0.000177 | 0.602221 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | 1.30 | 0.118769 | 0.200000 | 0.259167 | 0.316717 | 0.500000 | 0.003208 | 0.000110 | 0.375823 | 12.80 | 0.008000 |
Design Size Rated Capacity [W] | Design Size Maximum Water Flow Rate [m3/s] | Design Size U-Factor Times Area Value [W/K] | |
CORE_BOTTOM VAV BOX REHEAT COIL | 19516.16 | 0.000171 | 393.43 |
CORE_MID VAV BOX REHEAT COIL | 375050.02 | 0.003281 | 8359.98 |
CORE_TOP VAV BOX REHEAT COIL | 61918.87 | 0.000542 | 1595.60 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | 6305.35 | 0.000055 | 150.77 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | 5143.55 | 0.000045 | 119.00 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | 8121.37 | 0.000071 | 210.08 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | 4330.32 | 0.000038 | 92.22 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | 158838.50 | 0.001390 | 4190.72 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | 105821.15 | 0.000926 | 2791.82 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | 157279.25 | 0.001376 | 4149.63 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | 94912.24 | 0.000830 | 2504.29 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | 20328.69 | 0.000178 | 536.20 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | 13426.57 | 0.000117 | 354.13 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | 20179.88 | 0.000177 | 532.28 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | 12594.20 | 0.000110 | 332.20 |
VAV_BOT WITH REHEAT HEATING COIL | 27700.35 | 0.000242 | 480.06 |
VAV_MID WITH REHEAT HEATING COIL | 233004.13 | 0.002038 | 4058.74 |
VAV_TOP WITH REHEAT HEATING COIL | 20857.58 | 0.000182 | 366.58 |
CAV_BAS HEATING COIL | 289789.72 | 0.002535 | 6568.00 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT | 5.49 | 2.94 | 10.98 | 2.94 | 9.79 | 9.79 | 0.300000 | 0.300277 | 9.79 |
VAV_MID WITH REHEAT | 51.70 | 28.51 | 103.40 | 28.51 | 90.94 | 90.94 | 0.300000 | 0.313560 | 90.94 |
VAV_TOP WITH REHEAT | 5.30 | 2.95 | 10.59 | 3.78 | 9.91 | 9.91 | 0.300000 | 0.381401 | 9.91 |
CAV_BAS | 6.13 | 6.13 | 6.13 | 6.13 | 6.13 | 6.13 | 1.00 | 1.00 | 6.13 |
AIRLOOP DATACENTER BASEMENT | 21.44 | 21.44 | 21.44 | 21.44 | 21.44 | 21.44 | 1.00 | 0.999993 | 21.44 |
AIRLOOP DATACENTER BOT | 0.480202 | 0.480202 | 0.480202 | 0.480202 | 0.480202 | 0.480202 | 1.00 | 1.00 | 0.480202 |
AIRLOOP DATACENTER MID | 4.57 | 4.57 | 4.57 | 4.57 | 4.57 | 4.57 | 1.00 | 1.00 | 4.57 |
AIRLOOP DATACENTER TOP | 0.466051 | 0.466051 | 0.466051 | 0.466051 | 0.466051 | 0.466051 | 1.00 | 1.00 | 0.466051 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT_OA_CONTROLLER | 9.79 | 2.54 |
VAV_MID WITH REHEAT_OA_CONTROLLER | 90.94 | 25.38 |
VAV_TOP WITH REHEAT_OA_CONTROLLER | 9.91 | 2.54 |
CAV_BAS_OA_CONTROLLER | 6.13 | 1.20 |
AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER | 21.44 | 0.338393 |
AIRLOOP DATACENTER BOT_OA_CONTROLLER | 0.480202 | 0.015632 |
AIRLOOP DATACENTER MID_OA_CONTROLLER | 4.57 | 0.156323 |
AIRLOOP DATACENTER TOP_OA_CONTROLLER | 0.466051 | 0.015632 |
Design Size Nominal Supply Air Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT OA HEAT RECOVERY | 2.54 |
VAV_MID WITH REHEAT OA HEAT RECOVERY | 25.38 |
VAV_TOP WITH REHEAT OA HEAT RECOVERY | 2.54 |
Design Size Design Inlet Air Temperature [C] | Design Size Design Inlet Water Temperature [C] | Design Size Design Outlet Air Temperature [C] | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | Design Size Design Coil Load [W] | Design Size Design Water Flow Rate [m3/s] | Design Size Design Air Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT COOLING COIL | 26.63 | 6.67 | 11.05 | 0.010908 | 0.008500 | 259625.88 | 0.011045 | 9.79 |
VAV_MID WITH REHEAT COOLING COIL | 26.91 | 6.67 | 11.05 | 0.011204 | 0.008500 | 2526201.21 | 0.107470 | 90.94 |
VAV_TOP WITH REHEAT COOLING COIL | 26.52 | 6.67 | 11.05 | 0.010892 | 0.008500 | 260981.37 | 0.011103 | 9.91 |
CAV_BAS COOLING COIL | 24.84 | 6.67 | 11.42 | 0.010400 | 0.008500 | 136722.67 | 0.005816 | 6.13 |
Design Size Maximum Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT FAN | 9.79 |
VAV_MID WITH REHEAT FAN | 90.94 |
VAV_TOP WITH REHEAT FAN | 9.91 |
Maximum Actuated Flow [m3/s] | Controller Convergence Tolerance | |
VAV_BOT WITH REHEAT_COOLC_CONTROLLER | 0.011045 | 0.000043 |
VAV_BOT WITH REHEAT_HEATC_CONTROLLER | 0.000242 | |
VAV_MID WITH REHEAT_COOLC_CONTROLLER | 0.107470 | 0.000004 |
VAV_MID WITH REHEAT_HEATC_CONTROLLER | 0.002038 | |
VAV_TOP WITH REHEAT_COOLC_CONTROLLER | 0.011103 | 0.000043 |
VAV_TOP WITH REHEAT_HEATC_CONTROLLER | 0.000182 | |
CAV_BAS_COOLC_CONTROLLER | 0.005816 | 0.000082 |
CAV_BAS_HEATC_CONTROLLER | 0.002535 |
Design Size Maximum Flow Rate [m3/s] | |
CAV_BAS FAN | 6.13 |
Design Size Rated Air Flow Rate [m3/s] | Design Size Rated Total Cooling Capacity [W] | Design Size Rated Sensible Cooling Capacity [W] | Design Size Rated Water Flow Rate [m3/s] | |
AIRLOOP DATACENTER BASEMENT COOLING COIL | 21.44 | 436425.08 | 313849.50 | 0.010688 |
AIRLOOP DATACENTER BOT COOLING COIL | 0.480202 | 9781.48 | 7027.92 | 0.000240 |
AIRLOOP DATACENTER MID COOLING COIL | 4.57 | 93413.42 | 67025.98 | 0.002288 |
AIRLOOP DATACENTER TOP COOLING COIL | 0.466051 | 9511.33 | 6826.93 | 0.000233 |
Supply Air Flow Rate [m3/s] | Supply Air Flow Rate During Heating Operation [m3/s] | Supply Air Flow Rate During Cooling Operation [m3/s] | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | Nominal Heating Capacity [W] | Nominal Cooling Capacity [W] | Supplemental Heating Coil Nominal Capacity [W] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | 21.44 | 21.44 | 21.44 | 21.44 | 436425.08 | 436425.08 | 14482.89 | 1.00 |
AIRLOOP DATACENTER BOT DXAC HEAT PUMP | 0.480202 | 0.480202 | 0.480202 | 0.480202 | 9781.48 | 9781.48 | 669.05 | 1.00 |
AIRLOOP DATACENTER MID DXAC HEAT PUMP | 4.57 | 4.57 | 4.57 | 4.57 | 93413.42 | 93413.42 | 6690.49 | 1.00 |
AIRLOOP DATACENTER TOP DXAC HEAT PUMP | 0.466051 | 0.466051 | 0.466051 | 0.466051 | 9511.33 | 9511.33 | 669.05 | 1.00 |
Design Size Maximum Flow Rate [m3/s] | |
AIRLOOP DATACENTER BASEMENT SUPPLY FAN | 21.44 |
AIRLOOP DATACENTER BOT SUPPLY FAN | 0.480202 |
AIRLOOP DATACENTER MID SUPPLY FAN | 4.57 |
AIRLOOP DATACENTER TOP SUPPLY FAN | 0.466051 |
Design Size Rated Air Flow Rate [m3/s] | Design Size Rated Heating Capacity [W] | Design Size Rated Water Flow Rate [m3/s] | |
AIRLOOP DATACENTER BASEMENT HEATING COIL | 21.44 | 436425.08 | 0.010688 |
AIRLOOP DATACENTER BOT HEATING COIL | 0.480202 | 9781.48 | 0.000240 |
AIRLOOP DATACENTER MID HEATING COIL | 4.57 | 93413.42 | 0.002288 |
AIRLOOP DATACENTER TOP HEATING COIL | 0.466051 | 9511.33 | 0.000233 |
Design Size Nominal Capacity [W] | |
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | 14482.89 |
AIRLOOP DATACENTER BOT_SUPPHEATCOIL | 669.05 |
AIRLOOP DATACENTER MID_SUPPHEATCOIL | 6690.49 |
AIRLOOP DATACENTER TOP_SUPPHEATCOIL | 669.05 |
Design Size Nominal Capacity Volume [m3/s] | User-Specified Nominal Capacity Volume [m3/s] | Design Size Rated Power [W] | User-Specified Rated Power [W] | |
DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | 0.000081 | 0.000037 | 96450.70 | 100000.00 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | Design Minimum Flow Rate [m3/s] | |
COOLSYS1 PUMP SECONDARY | 0.135435 | 22112.36 | |
HEATSYS1 PUMP | 0.014305 | 4307.95 | 0.000000 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
COOLSYS1_DEMAND | 0.135435 | 16.25 |
HEATSYS1 | 0.014305 | 1.72 |
COOLSYS1_SUPPLY | 0.135435 | 16.25 |
SINGLE WATER PLANT LOOP | 0.013448 | 1.61 |
SWHSYS1 | 0.000440 | 0.052800 |
Loop Supply Side Design Fluid Flow Rate [m3/s] | Loop Demand Side Design Fluid Flow Rate [m3/s] | Heat Exchanger U-Factor Times Area Value [W/C] | Loop-to-loop Temperature Difference Used to Size Heat Exchanger U-Factor Times Area Value [C] | |
BYPASS HEAT EXCHANGER | 0.135435 | 0.135435 | 568487.70 | 5.60 |
Design Size Nominal Capacity [W] | User-Specified Nominal Capacity [W] | Design Size Design Water Flow Rate [m3/s] | |
HEATSYS1 BOILER | 1635117.89 | 1635117.89 | 0.014305 |
CENTRAL BOILER | 553950.16 | 543304.15 | 0.013448 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
COOLSYS1 CHILLER1 PUMP | 0.067717 | 7654.57 |
COOLSYS1 CHILLER2 PUMP | 0.067717 | 7654.57 |
PLANT CIRC PUMP | 0.013448 | 3429.96 |
SWHSYS1 PUMP | 0.000440 | 56.21 |
Design Size Reference Chilled Water Flow Rate [m3/s] | User-Specified Reference Chilled Water Flow Rate [m3/s] | Design Size Reference Capacity [W] | User-Specified Reference Capacity [W] | Design Size Reference Condenser Water Flow Rate [m3/s] | |
COOLSYS1 CHILLER1 | 0.135435 | 0.068295 | 1609286.42 | 1616928.90 | 0.080016 |
COOLSYS1 CHILLER2 | 0.135435 | 0.068295 | 1609286.42 | 1616928.90 | 0.080016 |
Design Water Flow Rate [m3/s] | Air Flow Rate at High Fan Speed [m3/s] | Fluid cooler UA value at high fan speed based on nominal capacity input [W/K] | Air Flow Rate at Low Fan Speed [m3/s] | Fan Power at Low Fan Speed [W] | U-factor Times Area Value at Low Fan Speed [W/C] | |
CENTRAL TOWER | 0.013448 | 139666.47 | 58672.22 | 69833.23 | 7879.72 | 21354.91 |
Use Side Design Flow Rate [m3/s] | |
SWHSYS1 WATER HEATER | 0.000440 |
Maximum Loop Flow Rate [m3/s] | Condenser Loop Volume [m3] | |
TOWERWATERSYS | 0.160032 | 19.20 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
TOWERWATERSYS PUMP | 0.160032 | 39620.29 |
Design Air Flow Rate [m3/s] | Nominal Capacity [W] | Air Flow Rate in free convection regime [m3/s] | Tower capacity in free convection regime at design conditions [W] | |
TOWERWATERSYS COOLTOWER 1 | 61.57 | 1918476.60 | 12.31 | 239809.58 |
TOWERWATERSYS COOLTOWER 2 | 61.57 | 1918476.60 | 12.31 | 239809.58 |
Design Water Flow Rate [m3/s] Equipment # 47 | |
WSHPPLANT OPERATION SCHEME | 0.083113 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:44:04
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
PERIMETER_BOT_ZN_3_WALL_NORTH | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | |
PERIMETER_BOT_ZN_2_WALL_EAST | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | |
PERIMETER_BOT_ZN_1_WALL_SOUTH | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | |
PERIMETER_BOT_ZN_4_WALL_WEST | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | |
PERIMETER_MID_ZN_3_WALL_NORTH | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_MID_ZN_2_WALL_EAST | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_MID_ZN_1_WALL_SOUTH | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_MID_ZN_4_WALL_WEST | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | |
PERIMETER_TOP_ZN_3_WALL_NORTH | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_TOP_ZN_2_WALL_EAST | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_TOP_ZN_1_WALL_SOUTH | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_TOP_ZN_4_WALL_WEST | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 08:44:04
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 08:44:04
VersionVersion ID | |
1 | 22.1.0 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 24.20 | 18.90 | 15.70 | 13.60 | 15.50 | 17.10 | 21.20 | 26.90 | 27.60 | 27.90 | 27.40 | 26.20 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Tampa-MacDill AFB FL USA TMY3 WMO#=747880 | 27.85 | -82.52 | -5.00 | 8.00 | 101229 | 1.2032 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 21.85 | 14.30 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | OfficeLarge | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 23 | 221 | 36 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | BASEMENT | 0.0 | 0.00 | 0.00 | 0.00 | 44.59 | 24.37 | -1.22 | 1 | 1 | 1 | 16.08 | 73.11 | 0.00 | 48.74 | -2.44 | 0.00 | 2.44 | 6779.02 | TARP | TARP | 2779.43 | 0.00 | 0.00 | 0.00 | 9 | 0 | 0 | Yes |
2 | CORE_BOTTOM | 0.0 | 0.00 | 0.00 | 0.00 | 37.01 | 24.37 | 1.37 | 1 | 1 | 1 | 5.49 | 68.53 | 4.57 | 44.17 | 0.00 | 2.74 | 2.74 | 6849.35 | TARP | TARP | 2496.12 | 0.00 | 0.00 | 0.00 | 7 | 0 | 0 | Yes |
3 | CORE_MID | 0.0 | 0.00 | 0.00 | 0.00 | 37.01 | 24.37 | 18.14 | 1 | 10 | 1 | 5.49 | 68.53 | 4.57 | 44.17 | 16.77 | 19.51 | 2.74 | 6849.35 | TARP | TARP | 2496.12 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
4 | CORE_TOP | 0.0 | 0.00 | 0.00 | 0.00 | 37.01 | 24.37 | 34.91 | 1 | 1 | 1 | 5.49 | 68.53 | 4.57 | 44.17 | 33.54 | 36.28 | 2.74 | 6849.35 | TARP | TARP | 2496.12 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
5 | PERIMETER_BOT_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 46.54 | 1.37 | 1 | 1 | 1 | 0.00 | 73.11 | 44.17 | 48.74 | 0.00 | 2.74 | 2.74 | 860.00 | TARP | TARP | 313.41 | 200.61 | 76.91 | 115.90 | 8 | 9 | 0 | Yes |
6 | PERIMETER_BOT_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 70.95 | 24.37 | 1.37 | 1 | 1 | 1 | 68.53 | 73.11 | 0.00 | 48.74 | 0.00 | 2.74 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 52.57 | 77.26 | 6 | 5 | 0 | Yes |
7 | PERIMETER_BOT_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 2.20 | 1.37 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 4.57 | 0.00 | 2.74 | 2.74 | 860.02 | TARP | TARP | 313.42 | 200.61 | 76.91 | 115.90 | 8 | 9 | 0 | Yes |
8 | PERIMETER_BOT_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.16 | 24.37 | 1.37 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 48.74 | 0.00 | 2.74 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 52.57 | 77.26 | 6 | 5 | 0 | Yes |
9 | PERIMETER_MID_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 46.54 | 18.14 | 1 | 10 | 1 | 0.00 | 73.11 | 44.17 | 48.74 | 16.77 | 19.51 | 2.74 | 860.00 | TARP | TARP | 313.41 | 200.61 | 84.71 | 115.90 | 7 | 1 | 0 | Yes |
10 | PERIMETER_MID_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 70.95 | 24.37 | 18.14 | 1 | 10 | 1 | 68.53 | 73.11 | 0.00 | 48.74 | 16.77 | 19.51 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 56.47 | 77.26 | 6 | 1 | 0 | Yes |
11 | PERIMETER_MID_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 2.20 | 18.14 | 1 | 10 | 1 | 0.00 | 73.11 | 0.00 | 4.57 | 16.77 | 19.51 | 2.74 | 860.02 | TARP | TARP | 313.42 | 200.61 | 84.71 | 115.90 | 7 | 1 | 0 | Yes |
12 | PERIMETER_MID_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.16 | 24.37 | 18.14 | 1 | 10 | 1 | 0.00 | 4.57 | 0.00 | 48.74 | 16.77 | 19.51 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 56.47 | 77.26 | 6 | 1 | 0 | Yes |
13 | PERIMETER_TOP_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 46.54 | 34.91 | 1 | 1 | 1 | 0.00 | 73.11 | 44.17 | 48.74 | 33.54 | 36.28 | 2.74 | 860.00 | TARP | TARP | 313.41 | 200.61 | 84.71 | 115.90 | 7 | 1 | 0 | Yes |
14 | PERIMETER_TOP_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 70.95 | 24.37 | 34.91 | 1 | 1 | 1 | 68.53 | 73.11 | 0.00 | 48.74 | 33.54 | 36.28 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 56.47 | 77.26 | 6 | 1 | 0 | Yes |
15 | PERIMETER_TOP_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 2.20 | 34.91 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 4.57 | 33.54 | 36.28 | 2.74 | 860.02 | TARP | TARP | 313.42 | 200.61 | 84.71 | 115.90 | 7 | 1 | 0 | Yes |
16 | PERIMETER_TOP_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.16 | 24.37 | 34.91 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 48.74 | 33.54 | 36.28 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 56.47 | 77.26 | 6 | 1 | 0 | Yes |
17 | GROUNDFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 24.37 | 3.35 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 48.74 | 2.74 | 3.96 | 1.22 | 4344.14 | TARP | TARP | 3563.11 | 297.11 | 297.11 | 0.00 | 11 | 0 | 0 | No |
18 | MIDFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 24.37 | 20.12 | 1 | 10 | 1 | 0.00 | 73.11 | 0.00 | 48.74 | 19.51 | 20.73 | 1.22 | 4344.14 | TARP | TARP | 3563.11 | 297.11 | 297.11 | 0.00 | 11 | 0 | 0 | No |
19 | TOPFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 24.37 | 36.89 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 48.74 | 36.28 | 37.50 | 1.22 | 4344.14 | TARP | TARP | 3563.11 | 297.11 | 297.11 | 0.00 | 11 | 0 | 0 | No |
20 | DATACENTER_BOT_ZN_6 | 0.0 | 5.49 | 44.17 | 0.00 | 5.03 | 24.37 | 1.37 | 1 | 1 | 1 | 4.57 | 5.49 | 4.57 | 44.17 | 0.00 | 2.74 | 2.74 | 99.34 | TARP | TARP | 36.20 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
21 | DATACENTER_MID_ZN_6 | 0.0 | 4.57 | 4.57 | 16.77 | 5.03 | 24.37 | 18.14 | 1 | 10 | 1 | 4.57 | 5.49 | 4.57 | 44.17 | 16.77 | 19.51 | 2.74 | 99.34 | TARP | TARP | 36.20 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
22 | DATACENTER_TOP_ZN_6 | 0.0 | 4.57 | 4.57 | 33.54 | 5.03 | 24.37 | 34.91 | 1 | 1 | 1 | 4.57 | 5.49 | 4.57 | 44.17 | 33.54 | 36.28 | 2.74 | 99.34 | TARP | TARP | 36.20 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
23 | DATACENTER_BASEMENT_ZN_6 | 0.0 | 16.08 | 0.00 | -2.44 | 8.04 | 24.37 | -1.22 | 1 | 1 | 1 | 0.00 | 16.08 | 0.00 | 48.74 | -2.44 | 0.00 | 2.44 | 1911.37 | TARP | TARP | 783.68 | 0.00 | 0.00 | 0.00 | 10 | 0 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | BASEMENT | 2779.43 | 149.6 | 18.579 | 5.382E-002 | 10.273 | 4.842 | 0.000 | 0.000 | 0.000 | 0.000 | 15.115 | No |
2 | CORE_BOTTOM | 2496.12 | 134.4 | 18.579 | 5.382E-002 | 10.273 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 18.343 | No |
3 | CORE_MID | 2496.12 | 134.4 | 18.579 | 5.382E-002 | 10.273 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 18.343 | No |
4 | CORE_TOP | 2496.12 | 134.4 | 18.579 | 5.382E-002 | 10.273 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 18.343 | No |
5 | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 18.579 | 5.382E-002 | 10.273 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 18.343 | No |
6 | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 10.273 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 18.343 | No |
7 | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 18.579 | 5.382E-002 | 10.273 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 18.343 | No |
8 | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 10.273 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 18.343 | No |
9 | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 18.579 | 5.382E-002 | 10.273 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 18.343 | No |
10 | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 10.273 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 18.343 | No |
11 | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 18.579 | 5.382E-002 | 10.273 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 18.343 | No |
12 | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 10.273 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 18.343 | No |
13 | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 18.579 | 5.382E-002 | 10.273 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 18.343 | No |
14 | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 10.273 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 18.343 | No |
15 | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 18.579 | 5.382E-002 | 10.273 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 18.343 | No |
16 | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 10.273 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 18.343 | No |
17 | GROUNDFLOOR_PLENUM | 3563.11 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
18 | MIDFLOOR_PLENUM | 3563.11 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
19 | TOPFLOOR_PLENUM | 3563.11 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
20 | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 18.579 | 5.382E-002 | 17.873 | 215.299 | 0.000 | 0.000 | 0.000 | 0.000 | 233.173 | No |
21 | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 18.579 | 5.382E-002 | 17.873 | 215.299 | 0.000 | 0.000 | 0.000 | 0.000 | 233.173 | No |
22 | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 18.579 | 5.382E-002 | 17.873 | 215.299 | 0.000 | 0.000 | 0.000 | 0.000 | 233.173 | No |
23 | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 18.579 | 5.382E-002 | 10.273 | 484.423 | 0.000 | 0.000 | 0.000 | 0.000 | 494.696 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | DATACENTER_BOT_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 1.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | DATACENTER_MID_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 1.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
3 | DATACENTER_TOP_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 1.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
4 | DATACENTER_BASEMENT_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 42.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 42 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
5 | BASEMENT | BLDG_OCC_SCH_WO_SB | BASEMENT | 2779.43 | 149.6 | 149.6 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 150 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
6 | CORE_BOTTOM | BLDG_OCC_SCH_WO_SB | CORE_BOTTOM | 2496.12 | 134.4 | 134.4 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 134 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
7 | CORE_MID | BLDG_OCC_SCH_WO_SB | CORE_MID | 2496.12 | 134.4 | 134.4 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 134 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
8 | CORE_TOP | BLDG_OCC_SCH_WO_SB | CORE_TOP | 2496.12 | 134.4 | 134.4 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 134 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
9 | PERIMETER_BOT_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
10 | PERIMETER_BOT_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
11 | PERIMETER_BOT_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
12 | PERIMETER_BOT_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
13 | PERIMETER_MID_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
14 | PERIMETER_MID_ZN_2 | BLDG_OCC_SCH_W_SB | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
15 | PERIMETER_MID_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
16 | PERIMETER_MID_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
17 | PERIMETER_TOP_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
18 | PERIMETER_TOP_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
19 | PERIMETER_TOP_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
20 | PERIMETER_TOP_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | BASEMENT_LIGHTS | LTG_SCH_OFFICE | BASEMENT | 2779.43 | 149.6 | 28553.717 | 10.273 | 190.864 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 28553.717 |
2 | CORE_BOTTOM_LIGHTS | LTG_SCH_OFFICE | CORE_BOTTOM | 2496.12 | 134.4 | 25643.245 | 10.273 | 190.864 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 25643.245 |
3 | CORE_MID_LIGHTS | LTG_SCH_OFFICE | CORE_MID | 2496.12 | 134.4 | 25643.245 | 10.273 | 190.864 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 25643.245 |
4 | CORE_TOP_LIGHTS | LTG_SCH_OFFICE | CORE_TOP | 2496.12 | 134.4 | 25643.245 | 10.273 | 190.864 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 25643.245 |
5 | PERIMETER_BOT_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 3219.765 | 10.273 | 190.864 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3219.765 |
6 | PERIMETER_BOT_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 2074.939 | 10.273 | 190.864 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2074.939 |
7 | PERIMETER_BOT_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 3219.836 | 10.273 | 190.864 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3219.836 |
8 | PERIMETER_BOT_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 2074.939 | 10.273 | 190.864 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2074.939 |
9 | PERIMETER_MID_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 3219.765 | 10.273 | 190.864 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3219.765 |
10 | PERIMETER_MID_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 2074.939 | 10.273 | 190.864 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2074.939 |
11 | PERIMETER_MID_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 3219.836 | 10.273 | 190.864 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3219.836 |
12 | PERIMETER_MID_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 2074.939 | 10.273 | 190.864 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2074.939 |
13 | PERIMETER_TOP_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 3219.765 | 10.273 | 190.864 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3219.765 |
14 | PERIMETER_TOP_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 2074.939 | 10.273 | 190.864 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2074.939 |
15 | PERIMETER_TOP_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 3219.836 | 10.273 | 190.864 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3219.836 |
16 | PERIMETER_TOP_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 2074.939 | 10.273 | 190.864 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2074.939 |
17 | DATACENTER_BASEMENT_LIGHTS | LTG_SCH_OFFICE | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 8050.927 | 10.273 | 190.864 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 8050.927 |
18 | DATACENTER_BOT_LIGHTS | LTG_SCH_DATACENTER | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 647.068 | 17.873 | 332.067 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 647.068 |
19 | DATACENTER_MID_LIGHTS | LTG_SCH_DATACENTER | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 647.068 | 17.873 | 332.067 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 647.068 |
20 | DATACENTER_TOP_LIGHTS | LTG_SCH_DATACENTER | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 647.068 | 17.873 | 332.067 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 647.068 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | BASEMENT_MISCPLUG_EQUIP | ALWAYS_ON | BASEMENT | 2779.43 | 149.6 | 13457.544 | 4.842 | 89.956 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 13457.544 | 13457.544 |
2 | CORE_BOTTOM_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_BOTTOM | 2496.12 | 134.4 | 20142.877 | 8.070 | 149.925 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 20142.877 |
3 | CORE_MID_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_MID | 2496.12 | 134.4 | 20142.800 | 8.070 | 149.924 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 20142.800 |
4 | CORE_TOP_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_TOP | 2496.12 | 134.4 | 20142.800 | 8.070 | 149.924 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 20142.800 |
5 | PERIMETER_BOT_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 2529.242 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.242 |
6 | PERIMETER_BOT_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 1629.940 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.940 |
7 | PERIMETER_BOT_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 2529.281 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.281 |
8 | PERIMETER_BOT_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 1629.929 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.929 |
9 | PERIMETER_MID_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 2529.242 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.242 |
10 | PERIMETER_MID_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 1629.940 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.940 |
11 | PERIMETER_MID_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 2529.281 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.281 |
12 | PERIMETER_MID_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 1629.929 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.929 |
13 | PERIMETER_TOP_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 2529.242 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.242 |
14 | PERIMETER_TOP_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 1629.940 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.940 |
15 | PERIMETER_TOP_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 2529.281 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.281 |
16 | PERIMETER_TOP_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 1629.929 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.929 |
17 | DATACENTER_BASEMENT_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 379632.522 | 484.423 | 9000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 94908.130 | 379632.522 |
18 | DATACENTER_BOT_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 7794.422 | 215.299 | 4000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 1948.606 | 7794.422 |
19 | DATACENTER_MID_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 7794.422 | 215.299 | 4000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 1948.606 | 7794.422 |
20 | DATACENTER_TOP_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 7794.422 | 215.299 | 4000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 1948.606 | 7794.422 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 3.975 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | INTERIORFURNISHINGS | 2 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
3 | DROPCEILING | 4 | 1 | 3 | 0.167 | 4.488 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
4 | INT_WALL | 7 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | EXT_SLAB_8IN_WITH_CARPET | 8 | 2 | 7 | 0.167 | 3.285 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
6 | INT_SLAB_FLOOR | 12 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
7 | INT_SLAB_CEILING | 13 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | VeryRough |
8 | NONRES_ROOF | 17 | 3 | 3 | 0.167 | 0.2284 | 0.750 | 0.900 | 0.450 | 0.700 | Rough |
9 | NONRES_EXT_WALL_GRD | 20 | 3 | 9 | 0.167 | 1.452 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
10 | NONRES_EXT_WALL_MID | 21 | 3 | 9 | 0.167 | 1.400 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
11 | NONRES_EXT_WALL_TOP | 22 | 3 | 9 | 0.167 | 1.662 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
12 | BASEMENT_WALL_EAST_CFACTOR | 39 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | BASEMENT_WALL_SOUTH_CFACTOR | 40 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | BASEMENT_WALL_NORTH_CFACTOR | 41 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR | 42 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
16 | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR | 43 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
17 | DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR | 44 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2516 |
2 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
3 | AC02 ACOUSTIC CEILING | 0.0127 | 0.057 | 288.000 | 1339.000 | 0.2228 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | 200MM NORMALWEIGHT CONCRETE FLOOR | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
7 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
8 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
9 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
10 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
11 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
12 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
13 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 4.319 |
14 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
15 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
16 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.5215 |
17 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
18 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
19 | NONRES_EXTERIOR_WALL_INSULATION_MID | 0.0000 | 0.000 | 0.000 | 0.000 | 0.5467 |
20 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
21 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
22 | NONRES_EXTERIOR_WALL_INSULATION_TOP | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4343 |
23 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
24 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
25 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
26 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
27 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
28 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
29 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
30 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
31 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
32 | ~FC_Insulation_5 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
33 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
34 | ~FC_Insulation_6 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
35 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 3.9747841 | 3.9747841 | 3.9747841 | |
3 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
4 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
5 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
6 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
7 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
8 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
9 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
10 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
11 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
12 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
13 | 3 | -0.21589802E-09 | 0.15643069E-09 | -0.21589802E-09 | 0.12999471E-21 |
14 | 2 | 0.50772448E-02 | 0.30006816E-02 | 0.50772448E-02 | -0.13693132E-08 |
15 | 1 | -2.5944910 | 1.4597758 | -2.5944910 | 0.76344767E-02 |
16 | 0 | 7.0433378 | 2.9911476 | 7.0433378 | |
17 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
18 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
19 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
20 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
21 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
22 | 7 | -0.18651654E-16 | -0.16428647E-15 | -0.26578847E-08 | -0.25364002E-17 |
23 | 6 | 0.67402962E-01 | 0.99142722E-07 | 0.38101547E-02 | -0.76639482E-03 |
24 | 5 | -1.8580732 | 0.49502125E-04 | -0.10651409 | 0.21891119E-01 |
25 | 4 | 18.220105 | 0.12801333E-02 | 1.0775450 | -0.22586539 |
26 | 3 | -79.928293 | 0.66708484E-02 | -4.9803755 | 1.0625663 |
27 | 2 | 166.43177 | 0.75131194E-02 | 11.128837 | -2.4125483 |
28 | 1 | -159.97298 | 0.18548900E-02 | -11.587784 | 2.5494418 |
29 | 0 | 57.057412 | 0.52755123E-04 | 4.4818272 | |
30 | 7 | 0.43260499E-16 | 0.34524919E-16 | 0.52793240E-17 | 0.0000000 |
31 | 6 | 0.69434179E-09 | 0.98085174E-11 | 0.18162501E-10 | -0.40870994E-12 |
32 | 5 | -0.12888762E-04 | 0.28373718E-06 | -0.16918523E-06 | 0.92361873E-08 |
33 | 4 | 0.25174112E-01 | 0.33697681E-03 | 0.22646198E-03 | -0.31467795E-04 |
34 | 3 | -3.7600775 | 0.27170599E-01 | -0.48495626E-01 | 0.94171705E-02 |
35 | 2 | 51.553741 | 0.22121684 | 1.2284947 | -0.25833933 |
36 | 1 | -128.86110 | 0.21944682 | -5.1479470 | 1.1228340 |
37 | 0 | 81.526494 | 0.16043334E-01 | 4.4519351 | |
38 | 7 | 0.52793240E-17 | 0.34524919E-16 | 0.43260499E-16 | 0.0000000 |
39 | 6 | 0.18162501E-10 | 0.98085174E-11 | 0.69434179E-09 | -0.40870994E-12 |
40 | 5 | -0.16918523E-06 | 0.28373718E-06 | -0.12888762E-04 | 0.92361873E-08 |
41 | 4 | 0.22646198E-03 | 0.33697681E-03 | 0.25174112E-01 | -0.31467795E-04 |
42 | 3 | -0.48495626E-01 | 0.27170599E-01 | -3.7600775 | 0.94171705E-02 |
43 | 2 | 1.2284947 | 0.22121684 | 51.553741 | -0.25833933 |
44 | 1 | -5.1479470 | 0.21944682 | -128.86110 | 1.1228340 |
45 | 0 | 4.4519351 | 0.16043334E-01 | 81.526494 | |
46 | 3 | -0.62451068E-06 | 0.10350887E-08 | -0.38276125E-05 | 0.11995084E-16 |
47 | 2 | 0.77976586 | 0.13989883E-02 | 1.0579789 | -0.73382352E-06 |
48 | 1 | -21.958702 | 0.93426804E-01 | -6.3215779 | 0.20283230 |
49 | 0 | 21.361010 | 0.87247630E-01 | 5.4456762 | |
50 | 9 | 0.81534556E-15 | 0.47534309E-16 | -0.12491808E-09 | -0.15651055E-17 |
51 | 8 | 0.18376575E-07 | 0.18892299E-12 | 0.33997552E-03 | -0.20894799E-09 |
52 | 7 | -0.11109444E-01 | 0.10222184E-07 | -0.21454547E-01 | 0.12631841E-03 |
53 | 6 | 0.37458360 | 0.36213810E-05 | 0.44579641 | -0.43850983E-02 |
54 | 5 | -4.8902522 | 0.13734403E-03 | -4.2389002 | 0.59460182E-01 |
55 | 4 | 31.674104 | 0.11393769E-02 | 20.648451 | -0.40448134 |
56 | 3 | -108.39803 | 0.25142476E-02 | -54.058051 | 1.4743366 |
57 | 2 | 194.32686 | 0.14299560E-02 | 76.440274 | -2.8561868 |
58 | 1 | -170.12819 | 0.15421596E-03 | -54.840647 | 2.7274244 |
59 | 0 | 57.057407 | 0.88766417E-06 | 15.629571 | |
60 | 9 | 0.15527634E-14 | 0.48972640E-16 | -0.12737755E-09 | -0.48559044E-17 |
61 | 8 | 0.18724477E-07 | 0.18300980E-12 | 0.34384059E-03 | -0.21290374E-09 |
62 | 7 | -0.11225506E-01 | 0.98577958E-08 | -0.21621905E-01 | 0.12763808E-03 |
63 | 6 | 0.37773826 | 0.34860306E-05 | 0.44850155 | -0.44222837E-02 |
64 | 5 | -4.9210508 | 0.13200769E-03 | -4.2597582 | 0.59842059E-01 |
65 | 4 | 31.810414 | 0.10936068E-02 | 20.730162 | -0.40629104 |
66 | 3 | -108.68827 | 0.24103335E-02 | -54.219675 | 1.4785295 |
67 | 2 | 194.61479 | 0.13693941E-02 | 76.588171 | -2.8607587 |
68 | 1 | -170.23464 | 0.14753937E-03 | -54.883028 | 2.7292902 |
69 | 0 | 57.057407 | 0.84836289E-06 | 15.622061 | |
70 | 9 | 0.10580992E-14 | 0.52916478E-16 | -0.11479962E-09 | -0.26242945E-17 |
71 | 8 | 0.16943687E-07 | 0.21219816E-12 | 0.32378363E-03 | -0.19265555E-09 |
72 | 7 | -0.10622292E-01 | 0.11706466E-07 | -0.20751735E-01 | 0.12077931E-03 |
73 | 6 | 0.36134106 | 0.41796623E-05 | 0.43441658 | -0.42290030E-02 |
74 | 5 | -4.7609497 | 0.15957712E-03 | -4.1510514 | 0.57856955E-01 |
75 | 4 | 31.101728 | 0.13316855E-02 | 20.304070 | -0.39688243 |
76 | 3 | -107.17897 | 0.29539374E-02 | -53.376774 | 1.4567269 |
77 | 2 | 193.11717 | 0.16877407E-02 | 75.817308 | -2.8369794 |
78 | 1 | -169.68078 | 0.18278585E-03 | -54.662957 | 2.7195831 |
79 | 0 | 57.057407 | 0.10570564E-05 | 15.661738 | |
80 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
81 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
82 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
83 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
84 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
85 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
86 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
87 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
88 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
89 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
90 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
91 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
92 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
93 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
94 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
95 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
96 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
97 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
98 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
99 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
100 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
101 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
102 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
103 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
104 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
105 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
106 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
107 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
108 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
109 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
110 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
111 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
112 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
113 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
114 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
115 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
116 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
117 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
118 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
119 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
120 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
121 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
122 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
123 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
124 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
125 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
126 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
127 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | WINDOW_U_0.567_SHGC_EAST_0.25 | 35 | 1 | VerySmooth | 3.224 | 3.224 | 1.000 | 0.251 | ||
2 | WINDOW_U_0.567_SHGC_SOUTH_0.25 | 36 | 1 | VerySmooth | 3.224 | 3.224 | 1.000 | 0.251 | ||
3 | WINDOW_U_0.567_SHGC_WEST_0.25 | 37 | 1 | VerySmooth | 3.224 | 3.224 | 1.000 | 0.251 | ||
4 | WINDOW_U_0.567_SHGC_NORTH_0.25 | 38 | 1 | VerySmooth | 3.224 | 3.224 | 1.000 | 0.251 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | GLAZING LAYER EAST | SpectralAverage | 2.00000E-003 | 0.16139 | 0.60245 | 0.60245 | 0.27500 | 0.15630 | 0.22588 | 0.00000 | 0.84000 | 0.84000 | 1.42129E-002 | 1.00000 | No | |
2 | GLAZING LAYER SOUTH | SpectralAverage | 2.00000E-003 | 0.16139 | 0.60245 | 0.60245 | 0.27500 | 0.15630 | 0.22588 | 0.00000 | 0.84000 | 0.84000 | 1.42129E-002 | 1.00000 | No | |
3 | GLAZING LAYER WEST | SpectralAverage | 2.00000E-003 | 0.16139 | 0.60245 | 0.60245 | 0.27500 | 0.15630 | 0.22588 | 0.00000 | 0.84000 | 0.84000 | 1.42129E-002 | 1.00000 | No | |
4 | GLAZING LAYER NORTH | SpectralAverage | 2.00000E-003 | 0.16139 | 0.60245 | 0.60245 | 0.27500 | 0.15630 | 0.22588 | 0.00000 | 0.84000 | 0.84000 | 1.42129E-002 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 30 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Enclosure Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Enclosures | |
1 | PERIMETER_BOT_ZN_3 | 5 | 0 |
2 | PERIMETER_BOT_ZN_2 | 3 | 0 |
3 | PERIMETER_BOT_ZN_1 | 5 | 0 |
4 | PERIMETER_BOT_ZN_4 | 3 | 0 |
5 | PERIMETER_MID_ZN_3 | 1 | 0 |
6 | PERIMETER_MID_ZN_2 | 1 | 0 |
7 | PERIMETER_MID_ZN_1 | 1 | 0 |
8 | PERIMETER_MID_ZN_4 | 1 | 0 |
9 | PERIMETER_TOP_ZN_3 | 1 | 0 |
10 | PERIMETER_TOP_ZN_2 | 1 | 0 |
11 | PERIMETER_TOP_ZN_1 | 1 | 0 |
12 | PERIMETER_TOP_ZN_4 | 1 | 0 |
Enclosure Name | Number of Adjacent Enclosures with Windows | Adjacent Enclosure Names - 1st 100 (max) | |
1 | PERIMETER_BOT_ZN_3 | 0 | |
2 | PERIMETER_BOT_ZN_2 | 0 | |
3 | PERIMETER_BOT_ZN_1 | 0 | |
4 | PERIMETER_BOT_ZN_4 | 0 | |
5 | PERIMETER_MID_ZN_3 | 0 | |
6 | PERIMETER_MID_ZN_2 | 0 | |
7 | PERIMETER_MID_ZN_1 | 0 | |
8 | PERIMETER_MID_ZN_4 | 0 | |
9 | PERIMETER_TOP_ZN_3 | 0 | |
10 | PERIMETER_TOP_ZN_2 | 0 | |
11 | PERIMETER_TOP_ZN_1 | 0 | |
12 | PERIMETER_TOP_ZN_4 | 0 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 1.1356 | 87921.3 | 0.481 | 5.5005E-002 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | BASEMENT_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
2 | BASEMENT_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
3 | BASEMENT_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
4 | BASEMENT_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
5 | BASEMENT_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
6 | PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
7 | PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
8 | CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
9 | PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
10 | BASEMENT_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
11 | CORE_BOT_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
12 | CORE_BOT_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
13 | CORE_BOT_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
14 | CORE_BOT_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
15 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
16 | CORE_BOT_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
17 | CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
18 | CORE_BOTTOM_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
19 | CORE_MID_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
20 | CORE_MID_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
21 | CORE_MID_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
22 | CORE_MID_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
23 | CORE_MID_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
24 | CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
25 | CORE_MID_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
26 | CORE_TOP_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
27 | CORE_TOP_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
28 | CORE_TOP_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
29 | CORE_TOP_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
30 | CORE_TOP_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
31 | CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
32 | CORE_TOP_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
33 | PERIMETER_BOT_ZN_3_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
34 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
35 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
36 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
37 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
38 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
39 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
40 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
41 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
42 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
43 | PERIMETER_BOT_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
44 | CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
45 | PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
46 | DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
47 | PERIMETER_BOT_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
48 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
49 | PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
50 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
51 | PERIMETER_BOT_ZN_2_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
52 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
53 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
54 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
55 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
56 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
57 | PERIMETER_BOT_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
58 | CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
59 | PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
60 | PERIMETER_BOT_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
61 | PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
62 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
63 | PERIMETER_BOT_ZN_1_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
64 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
65 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
66 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
67 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
68 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
69 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
70 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
71 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
72 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
73 | PERIMETER_BOT_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
74 | DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
75 | PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
76 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
77 | DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
78 | PERIMETER_BOT_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
79 | PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
80 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
81 | PERIMETER_BOT_ZN_4_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
82 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
83 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
84 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
85 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
86 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
87 | PERIMETER_BOT_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
88 | DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
89 | PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
90 | PERIMETER_BOT_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
91 | PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
92 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
93 | PERIMETER_MID_ZN_3_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
94 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
95 | PERIMETER_MID_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
96 | CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
97 | PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
98 | DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
99 | PERIMETER_MID_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
100 | PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
101 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
102 | PERIMETER_MID_ZN_2_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
103 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
104 | PERIMETER_MID_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
105 | CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
106 | PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
107 | PERIMETER_MID_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
108 | PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
109 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
110 | PERIMETER_MID_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
111 | PERIMETER_MID_ZN_1_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
112 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
113 | DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
114 | PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
115 | CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
116 | PERIMETER_MID_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
117 | PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
118 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
119 | PERIMETER_MID_ZN_4_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
120 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
121 | PERIMETER_MID_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
122 | DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
123 | PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
124 | PERIMETER_MID_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
125 | PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
126 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
127 | PERIMETER_TOP_ZN_3_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
128 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
129 | PERIMETER_TOP_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
130 | CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
131 | PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
132 | DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
133 | PERIMETER_TOP_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
134 | PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
135 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
136 | PERIMETER_TOP_ZN_2_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
137 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
138 | PERIMETER_TOP_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
139 | CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
140 | INT-PER3S-NE-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
141 | PERIMETER_TOP_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
142 | PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
143 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
144 | PERIMETER_TOP_ZN_1_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
145 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
146 | INT-PER3S-NE | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
147 | DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
148 | PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
149 | CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
150 | PERIMETER_TOP_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
151 | PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
152 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
153 | PERIMETER_TOP_ZN_4_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
154 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
155 | PERIMETER_TOP_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
156 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
157 | PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
158 | PERIMETER_TOP_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
159 | PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
160 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
161 | GROUNDFLOOR_PLENUM_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
162 | GROUNDFLOOR_PLENUM_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
163 | GROUNDFLOOR_PLENUM_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
164 | GROUNDFLOOR_PLENUM_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
165 | iz-CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
166 | iz-PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
167 | iz-PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
168 | iz-PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
169 | iz-PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
170 | iz-DATACENTER_BOT_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
171 | GROUNDFLOOR_PLENUM_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
172 | MIDFLOOR_PLENUM_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
173 | MIDFLOOR_PLENUM_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
174 | MIDFLOOR_PLENUM_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
175 | MIDFLOOR_PLENUM_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
176 | iz-CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
177 | iz-PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
178 | iz-PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
179 | iz-PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
180 | iz-PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
181 | iz-DATACENTER_MID_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
182 | MIDFLOOR_PLENUM_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
183 | TOPFLOOR_PLENUM_WALL_NORTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
184 | TOPFLOOR_PLENUM_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
185 | TOPFLOOR_PLENUM_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
186 | TOPFLOOR_PLENUM_WALL_SOUTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
187 | iz-CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
188 | iz-PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
189 | iz-PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
190 | iz-PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
191 | iz-PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
192 | iz-DATACENTER_TOP_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
193 | BUILDING_ROOF | 0 | 3563.11 | 268.06 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
194 | DATACENTER_BOT_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
195 | DATACENTER_BOT_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
196 | DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
197 | DATACENTER_BOT_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
198 | DATACENTER_BOT_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
199 | DATACENTER_BOT_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
200 | DATACENTER_MID_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
201 | DATACENTER_MID_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
202 | DATACENTER_MID_ZN_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
203 | DATACENTER_MID_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
204 | DATACENTER_MID_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
205 | DATACENTER_MID_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
206 | DATACENTER_TOP_ZN_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
207 | DATACENTER_TOP_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
208 | DATACENTER_TOP_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
209 | DATACENTER_TOP_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
210 | DATACENTER_TOP_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
211 | DATACENTER_TOP_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
212 | DATACENTER_BASEMENT_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
213 | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
214 | DATACENTER_BASEMENT_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
215 | DATACENTER_BASEMENT_ZN_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
216 | DATACENTER_BASEMENT_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
217 | DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
218 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
219 | PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
220 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
221 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | PERIMETER_BOT_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 0.114 | 3.646E-004 | 5.482E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | PERIMETER_BOT_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 7.617E-002 | 3.771E-004 | 5.534E-004 | 0.495 | 0.000 | 0.000 | 0.224 | 0.000 |
3 | PERIMETER_BOT_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 0.114 | 3.646E-004 | 5.482E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | PERIMETER_BOT_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 7.617E-002 | 3.771E-004 | 5.534E-004 | 0.495 | 0.000 | 0.000 | 0.224 | 0.000 |
5 | PERIMETER_MID_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 0.114 | 3.646E-004 | 5.696E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
6 | PERIMETER_MID_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 7.617E-002 | 3.771E-004 | 5.696E-004 | 0.495 | 0.000 | 0.000 | 0.224 | 0.000 |
7 | PERIMETER_MID_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 0.114 | 3.646E-004 | 5.696E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
8 | PERIMETER_MID_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 7.617E-002 | 3.771E-004 | 5.696E-004 | 0.495 | 0.000 | 0.000 | 0.224 | 0.000 |
9 | PERIMETER_TOP_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 0.114 | 3.646E-004 | 5.696E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
10 | PERIMETER_TOP_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 7.617E-002 | 3.771E-004 | 5.696E-004 | 0.495 | 0.000 | 0.000 | 0.224 | 0.000 |
11 | PERIMETER_TOP_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 0.114 | 3.646E-004 | 5.696E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
12 | PERIMETER_TOP_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 7.617E-002 | 3.771E-004 | 5.696E-004 | 0.495 | 0.000 | 0.000 | 0.224 | 0.000 |
13 | GROUNDFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | GROUNDFLOOR_PLENUM | 3563.11 | 0.0 | 0.169 | 4.749E-005 | 5.696E-004 | 0.140 | 0.000 | 0.000 | 0.224 | 0.000 |
14 | MIDFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | MIDFLOOR_PLENUM | 3563.11 | 0.0 | 0.169 | 4.749E-005 | 5.696E-004 | 0.140 | 0.000 | 0.000 | 0.224 | 0.000 |
15 | TOPFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | TOPFLOOR_PLENUM | 3563.11 | 0.0 | 0.169 | 4.749E-005 | 4.384E-005 | 0.140 | 0.000 | 0.000 | 0.224 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | BASEMENT | Mixing/Well-Stirred |
2 | CORE_BOTTOM | Mixing/Well-Stirred |
3 | CORE_MID | Mixing/Well-Stirred |
4 | CORE_TOP | Mixing/Well-Stirred |
5 | PERIMETER_BOT_ZN_3 | Mixing/Well-Stirred |
6 | PERIMETER_BOT_ZN_2 | Mixing/Well-Stirred |
7 | PERIMETER_BOT_ZN_1 | Mixing/Well-Stirred |
8 | PERIMETER_BOT_ZN_4 | Mixing/Well-Stirred |
9 | PERIMETER_MID_ZN_3 | Mixing/Well-Stirred |
10 | PERIMETER_MID_ZN_2 | Mixing/Well-Stirred |
11 | PERIMETER_MID_ZN_1 | Mixing/Well-Stirred |
12 | PERIMETER_MID_ZN_4 | Mixing/Well-Stirred |
13 | PERIMETER_TOP_ZN_3 | Mixing/Well-Stirred |
14 | PERIMETER_TOP_ZN_2 | Mixing/Well-Stirred |
15 | PERIMETER_TOP_ZN_1 | Mixing/Well-Stirred |
16 | PERIMETER_TOP_ZN_4 | Mixing/Well-Stirred |
17 | GROUNDFLOOR_PLENUM | Mixing/Well-Stirred |
18 | MIDFLOOR_PLENUM | Mixing/Well-Stirred |
19 | TOPFLOOR_PLENUM | Mixing/Well-Stirred |
20 | DATACENTER_BOT_ZN_6 | Mixing/Well-Stirred |
21 | DATACENTER_MID_ZN_6 | Mixing/Well-Stirred |
22 | DATACENTER_TOP_ZN_6 | Mixing/Well-Stirred |
23 | DATACENTER_BASEMENT_ZN_6 | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sky Type | MonthAndDay | Daylighting Control Name | Enclosure Name | Window Name | Reference Point | Daylight Factor | |
1 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 3.6993E-003 |
2 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 3.7007E-003 |
3 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 3.8972E-003 |
4 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 3.8983E-003 |
5 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 3.0043E-003 |
6 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 3.0050E-003 |
7 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.7585E-003 |
8 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.7591E-003 |
9 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 3.7301E-003 |
10 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 3.8152E-003 |
11 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 3.9222E-003 |
12 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 3.9930E-003 |
13 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 3.0236E-003 |
14 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 3.0803E-003 |
15 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.7734E-003 |
16 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.8107E-003 |
17 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 9.2289E-002 |
18 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 3.7001E-002 |
19 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 0.1010 |
20 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 3.8916E-002 |
21 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 7.3226E-002 |
22 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.6523E-002 |
23 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 3.1622E-002 |
24 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.0968E-002 |
25 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 3.7381E-003 |
26 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 3.8536E-003 |
27 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 3.9308E-003 |
28 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.0345E-003 |
29 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 3.0314E-003 |
30 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 3.1100E-003 |
31 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.7738E-003 |
32 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.8117E-003 |
33 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 3.6993E-003 |
34 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 3.7009E-003 |
35 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 3.8971E-003 |
36 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 3.8985E-003 |
37 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 3.0042E-003 |
38 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 3.0053E-003 |
39 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.7585E-003 |
40 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.7590E-003 |
41 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.9917E-003 |
42 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 4.1450E-003 |
43 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.8348E-003 |
44 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.9931E-003 |
45 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.6044E-003 |
46 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.6843E-003 |
47 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.0071E-003 |
48 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.0329E-003 |
49 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 4.5366E-002 |
50 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 2.1139E-002 |
51 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 4.3023E-002 |
52 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 1.9342E-002 |
53 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 4.3180E-002 |
54 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 1.7344E-002 |
55 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.2931E-002 |
56 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 1.2292E-002 |
57 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.9572E-003 |
58 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 4.0188E-003 |
59 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.7919E-003 |
60 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.8373E-003 |
61 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.5808E-003 |
62 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.6003E-003 |
63 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.0072E-003 |
64 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.0333E-003 |
65 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.7200E-003 |
66 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.7214E-003 |
67 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.4812E-003 |
68 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.4823E-003 |
69 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.3178E-003 |
70 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.3186E-003 |
71 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.7586E-003 |
72 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.7591E-003 |
73 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.7525E-003 |
74 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.8318E-003 |
75 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.5079E-003 |
76 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.5714E-003 |
77 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.3392E-003 |
78 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.3857E-003 |
79 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.7738E-003 |
80 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.8118E-003 |
81 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.6395E-002 |
82 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.3651E-002 |
83 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.0471E-002 |
84 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.0446E-002 |
85 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.8278E-002 |
86 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 7.1207E-003 |
87 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.1622E-002 |
88 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.0965E-002 |
89 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.7498E-003 |
90 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.8285E-003 |
91 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.5044E-003 |
92 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.5644E-003 |
93 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.3331E-003 |
94 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.3672E-003 |
95 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.7735E-003 |
96 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.8107E-003 |
97 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.7199E-003 |
98 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.7212E-003 |
99 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.4810E-003 |
100 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.4821E-003 |
101 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.3176E-003 |
102 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.3183E-003 |
103 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.7585E-003 |
104 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.7591E-003 |
105 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.2904E-003 |
106 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.3553E-003 |
107 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 2.9854E-003 |
108 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.0323E-003 |
109 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 2.9565E-003 |
110 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.9736E-003 |
111 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.0073E-003 |
112 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.0334E-003 |
113 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.3839E-002 |
114 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 1.6870E-002 |
115 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 2.9213E-002 |
116 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 1.4239E-002 |
117 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.1824E-002 |
118 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 1.3079E-002 |
119 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.2931E-002 |
120 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 1.2292E-002 |
121 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.3163E-003 |
122 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.4303E-003 |
123 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.0182E-003 |
124 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.1289E-003 |
125 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 2.9782E-003 |
126 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.0463E-003 |
127 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.0071E-003 |
128 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.0328E-003 |
129 | Clear Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 9.8661E-002 |
130 | Clear Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 5.4630E-002 |
131 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 0.1059 |
132 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 5.7394E-002 |
133 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 8.1919E-002 |
134 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 4.0642E-002 |
135 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 3.8788E-002 |
136 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 1.9168E-002 |
137 | Clear Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 5.3994E-002 |
138 | Clear Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 3.0640E-002 |
139 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 5.1393E-002 |
140 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 2.8479E-002 |
141 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 5.1264E-002 |
142 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 2.5872E-002 |
143 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 3.9762E-002 |
144 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 1.9389E-002 |
145 | Clear Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 3.3241E-002 |
146 | Clear Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 2.1922E-002 |
147 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 2.6497E-002 |
148 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 1.7516E-002 |
149 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 2.4021E-002 |
150 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 1.3301E-002 |
151 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 3.8788E-002 |
152 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 1.9165E-002 |
153 | Clear Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 4.0936E-002 |
154 | Clear Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 2.4718E-002 |
155 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 3.5732E-002 |
156 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 2.1378E-002 |
157 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 3.8502E-002 |
158 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 2.0108E-002 |
159 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 3.9762E-002 |
160 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 1.9389E-002 |
161 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 9.8788E-002 |
162 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 5.4748E-002 |
163 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 0.1061 |
164 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 5.7525E-002 |
165 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 8.2071E-002 |
166 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 4.0743E-002 |
167 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 3.8871E-002 |
168 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 1.9210E-002 |
169 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 5.4048E-002 |
170 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 3.0690E-002 |
171 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 5.1455E-002 |
172 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 2.8528E-002 |
173 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 5.1352E-002 |
174 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 2.5927E-002 |
175 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 3.9845E-002 |
176 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 1.9432E-002 |
177 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 3.3248E-002 |
178 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 2.1947E-002 |
179 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 2.6505E-002 |
180 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 1.7536E-002 |
181 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 2.4059E-002 |
182 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 1.3325E-002 |
183 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 3.8871E-002 |
184 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 1.9207E-002 |
185 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 4.0962E-002 |
186 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 2.4753E-002 |
187 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 3.5761E-002 |
188 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 2.1408E-002 |
189 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 3.8565E-002 |
190 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 2.0148E-002 |
191 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 3.9845E-002 |
192 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 1.9432E-002 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | BASEMENT | Cooling | 85050.19329 | 85050.19329 | 6.13030 | 6.13030 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 28.05400 | 1.65254E-002 | 2779.42662 | 149.60210 | 1.20016 | 0.00000 |
2 | BASEMENT | Heating | 0.00000 | 0.00000 | 0.00000 | 1.20016 | 00:10:00 | 4.60000 | 5.25715E-003 | 2779.42662 | 149.60210 | 1.20016 | 0.00000 | |
3 | CORE_BOTTOM | Cooling | 85727.98676 | 85727.98676 | 6.17800 | 6.17800 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 28.05400 | 1.65254E-002 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 |
4 | CORE_BOTTOM | Heating | 0.00000 | 0.00000 | 0.00000 | 1.07782 | 00:10:00 | 4.60000 | 5.25715E-003 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 | |
5 | CORE_MID | Cooling | 805760.52520 | 805760.52520 | 58.05263 | 58.05263 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 28.05400 | 1.65254E-002 | 2496.12046 | 134.35320 | 10.77825 | 0.00000 |
6 | CORE_MID | Heating | 184070.52639 | 184070.52639 | 7.71434 | 10.77825 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 4.60000 | 5.25715E-003 | 2496.12046 | 134.35320 | 10.77825 | 0.00000 |
7 | CORE_TOP | Cooling | 79564.59064 | 79564.59064 | 5.73217 | 5.73217 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 28.05400 | 1.65254E-002 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 |
8 | CORE_TOP | Heating | 42311.69329 | 42311.69329 | 1.79366 | 1.79366 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 4.60000 | 5.25715E-003 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 |
9 | PERIMETER_BOT_ZN_3 | Cooling | 14094.46823 | 14094.46823 | 1.02493 | 1.02493 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:40:00 | 33.90000 | 1.65364E-002 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
10 | PERIMETER_BOT_ZN_3 | Heating | 3855.06333 | 3855.06333 | 0.16287 | 0.16287 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 4.60000 | 5.25715E-003 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
11 | PERIMETER_BOT_ZN_2 | Cooling | 15338.97541 | 15338.97541 | 1.11542 | 1.11542 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 09:40:00 | 30.45033 | 1.65299E-002 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
12 | PERIMETER_BOT_ZN_2 | Heating | 2902.37297 | 2902.37297 | 0.12287 | 0.12287 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 4.60000 | 5.25715E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
13 | PERIMETER_BOT_ZN_1 | Cooling | 17418.45212 | 17418.45212 | 1.26664 | 1.26664 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:40:00 | 33.76833 | 1.65361E-002 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
14 | PERIMETER_BOT_ZN_1 | Heating | 5575.64623 | 5575.64623 | 0.23647 | 0.23647 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 4.60000 | 5.25715E-003 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
15 | PERIMETER_BOT_ZN_4 | Cooling | 19203.66234 | 19203.66234 | 1.39645 | 1.39645 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 17:00:00 | 32.79400 | 1.65343E-002 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
16 | PERIMETER_BOT_ZN_4 | Heating | 1526.72314 | 1526.72314 | 6.44457E-002 | 8.72129E-002 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 4.60000 | 5.25715E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
17 | PERIMETER_MID_ZN_3 | Cooling | 132227.67279 | 132227.67279 | 9.61602 | 9.61602 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | 33.90000 | 1.65364E-002 | 313.41284 | 16.86939 | 1.35332 | 0.00000 |
18 | PERIMETER_MID_ZN_3 | Heating | 111212.04667 | 111212.04667 | 4.73743 | 4.73743 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 4.60000 | 5.25715E-003 | 313.41284 | 16.86939 | 1.35332 | 0.00000 |
19 | PERIMETER_MID_ZN_2 | Cooling | 157723.31705 | 157723.31705 | 11.47005 | 11.47005 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 09:50:00 | 30.67417 | 1.65303E-002 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
20 | PERIMETER_MID_ZN_2 | Heating | 74087.91732 | 74087.91732 | 3.15645 | 3.15645 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 4.60000 | 5.25715E-003 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
21 | PERIMETER_MID_ZN_1 | Cooling | 166140.18625 | 166140.18625 | 12.08220 | 12.08220 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | 33.83417 | 1.65363E-002 | 313.41969 | 16.86975 | 1.35335 | 0.00000 |
22 | PERIMETER_MID_ZN_1 | Heating | 110122.14638 | 110122.14638 | 4.69080 | 4.69080 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 4.60000 | 5.25715E-003 | 313.41969 | 16.86975 | 1.35335 | 0.00000 |
23 | PERIMETER_MID_ZN_4 | Cooling | 167431.65398 | 167431.65398 | 12.17606 | 12.17606 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 17:00:00 | 32.79400 | 1.65343E-002 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
24 | PERIMETER_MID_ZN_4 | Heating | 66461.15094 | 66461.15094 | 2.83038 | 2.83038 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 4.60000 | 5.25715E-003 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
25 | PERIMETER_TOP_ZN_3 | Cooling | 14869.85458 | 14869.85458 | 1.08141 | 1.08141 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:10:00 | 33.82100 | 1.65362E-002 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
26 | PERIMETER_TOP_ZN_3 | Heating | 14228.57506 | 14228.57506 | 0.60667 | 0.60667 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 4.60000 | 5.25715E-003 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
27 | PERIMETER_TOP_ZN_2 | Cooling | 15966.66126 | 15966.66126 | 1.16117 | 1.16117 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 10:00:00 | 30.89800 | 1.65307E-002 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
28 | PERIMETER_TOP_ZN_2 | Heating | 9397.36038 | 9397.36038 | 0.40071 | 0.40071 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 4.60000 | 5.25715E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
29 | PERIMETER_TOP_ZN_1 | Cooling | 18146.72424 | 18146.72424 | 1.31971 | 1.31971 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | 33.90000 | 1.65364E-002 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
30 | PERIMETER_TOP_ZN_1 | Heating | 14124.54967 | 14124.54967 | 0.60222 | 0.60222 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 4.60000 | 5.25715E-003 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
31 | PERIMETER_TOP_ZN_4 | Cooling | 17818.52769 | 17818.52769 | 1.29584 | 1.29584 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 17:00:00 | 32.79400 | 1.65343E-002 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
32 | PERIMETER_TOP_ZN_4 | Heating | 8815.50959 | 8815.50959 | 0.37582 | 0.37582 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 4.60000 | 5.25715E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
33 | DATACENTER_BOT_ZN_6 | Cooling | 8372.67095 | 8372.67095 | 0.48020 | 0.48020 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 18:40:00 | 31.21400 | 1.65313E-002 | 36.20274 | 1.94861 | 1.56323E-002 | 0.00000 |
34 | DATACENTER_BOT_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 1.56323E-002 | 00:10:00 | 4.60000 | 5.25715E-003 | 36.20274 | 1.94861 | 1.56323E-002 | 0.00000 | |
35 | DATACENTER_MID_ZN_6 | Cooling | 79753.75944 | 79753.75944 | 4.57419 | 4.57419 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 18:40:00 | 31.21400 | 1.65313E-002 | 36.20274 | 1.94861 | 0.15632 | 0.00000 |
36 | DATACENTER_MID_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 0.15632 | 00:10:00 | 4.60000 | 5.25715E-003 | 36.20274 | 1.94861 | 0.15632 | 0.00000 | |
37 | DATACENTER_TOP_ZN_6 | Cooling | 8125.91316 | 8125.91316 | 0.46605 | 0.46605 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 18:40:00 | 31.21400 | 1.65313E-002 | 36.20274 | 1.94861 | 1.56323E-002 | 0.00000 |
38 | DATACENTER_TOP_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 1.56323E-002 | 00:10:00 | 4.60000 | 5.25715E-003 | 36.20274 | 1.94861 | 1.56323E-002 | 0.00000 | |
39 | DATACENTER_BASEMENT_ZN_6 | Cooling | 373799.24476 | 373799.24476 | 21.43837 | 21.43837 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 07:00:00 | 26.71100 | 1.65229E-002 | 783.67941 | 42.18139 | 0.33839 | 0.00000 |
40 | DATACENTER_BASEMENT_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 0.33839 | 00:10:00 | 4.60000 | 5.25715E-003 | 783.67941 | 42.18139 | 0.33839 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | VAV_BOT WITH REHEAT | Cooling | Sensible | 159791.46 | 9.78940 | 9.78940 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 00:00:00 |
2 | VAV_BOT WITH REHEAT | Heating | Sensible | 16727.20 | 1.68725 | 1.68725 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 |
3 | VAV_MID WITH REHEAT | Cooling | Sensible | 1471129.37 | 90.93533 | 90.93533 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 00:00:00 |
4 | VAV_MID WITH REHEAT | Heating | Sensible | 251222.23 | 26.19331 | 26.19331 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:10:00 |
5 | VAV_TOP WITH REHEAT | Cooling | Sensible | 163993.04 | 9.90844 | 9.90844 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 00:00:00 |
6 | VAV_TOP WITH REHEAT | Heating | Sensible | 25150.53 | 3.77908 | 3.77908 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:20:00 |
7 | CAV_BAS | Cooling | Sensible | 89257.68 | 6.13030 | 6.13030 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
8 | CAV_BAS | Heating | Sensible | 51365.55 | 1.20016 | 1.20016 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
9 | AIRLOOP DATACENTER BASEMENT | Cooling | Sensible | 370349.08 | 21.43852 | 21.43852 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
10 | AIRLOOP DATACENTER BASEMENT | Heating | Sensible | 14482.89 | 0.33839 | 0.33839 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
11 | AIRLOOP DATACENTER BOT | Cooling | Sensible | 8322.87 | 0.48020 | 0.48020 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
12 | AIRLOOP DATACENTER BOT | Heating | Sensible | 669.05 | 1.56323E-002 | 1.56323E-002 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
13 | AIRLOOP DATACENTER MID | Cooling | Sensible | 79317.25 | 4.57419 | 4.57419 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
14 | AIRLOOP DATACENTER MID | Heating | Sensible | 6690.49 | 0.15632 | 0.15632 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
15 | AIRLOOP DATACENTER TOP | Cooling | Sensible | 8081.34 | 0.46605 | 0.46605 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
16 | AIRLOOP DATACENTER TOP | Heating | Sensible | 669.05 | 1.56323E-002 | 1.56323E-002 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | BASEMENT DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 6.13030 |
2 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 6.17800 |
3 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.30787 |
4 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.31400 |
5 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.93989 |
6 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.82100 |
7 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
8 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.23752E-003 |
9 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.70736E-004 |
10 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.93989 |
11 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
12 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
13 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 19516.15961 |
14 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.70736E-004 |
15 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 393.43046 |
16 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 58.05263 |
17 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.32764 |
18 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.32700 |
19 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 18.98321 |
20 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.87371 |
21 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
22 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.16286E-003 |
23 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 3.28110E-003 |
24 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 18.98321 |
25 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
26 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
27 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 375050.02036 |
28 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.28110E-003 |
29 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 8359.97987 |
30 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 5.73217 |
31 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.33182 |
32 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.34000 |
33 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.94894 |
34 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.88485 |
35 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
36 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.14822E-003 |
37 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 5.41693E-004 |
38 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.94894 |
39 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
40 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
41 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 61918.86875 |
42 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 5.41693E-004 |
43 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 1595.59526 |
44 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.02493 |
45 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.23301 |
46 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.23800 |
47 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.24393 |
48 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.62136 |
49 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
50 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.63512E-003 |
51 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 5.51619E-005 |
52 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.24393 |
53 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
54 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
55 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 6305.34668 |
56 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 5.51619E-005 |
57 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 150.77374 |
58 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.11542 |
59 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.13798 |
60 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
61 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.22308 |
62 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.36794 |
63 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
64 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.76129E-003 |
65 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 4.49980E-005 |
66 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.22308 |
67 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
68 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
69 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 5143.55331 |
70 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 4.49980E-005 |
71 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 119.00018 |
72 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.26664 |
73 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.18855 |
74 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
75 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.25333 |
76 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.50280 |
77 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
78 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.02068E-003 |
79 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 7.10493E-005 |
80 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.25333 |
81 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
82 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
83 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 8121.36769 |
84 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 7.10493E-005 |
85 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 210.08382 |
86 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.39645 |
87 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.11021 |
88 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
89 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.27929 |
90 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
91 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
92 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.45698E-003 |
93 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 3.78835E-005 |
94 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.27929 |
95 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
96 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
97 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 4330.32237 |
98 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.78835E-005 |
99 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 92.21603 |
100 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 9.61602 |
101 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.24836 |
102 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.24800 |
103 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.38477 |
104 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.66229 |
105 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
106 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.53408E-003 |
107 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.38959E-003 |
108 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 4.73743 |
109 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
110 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
111 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 158838.50119 |
112 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.38959E-003 |
113 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 4190.71715 |
114 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 11.47005 |
115 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.13418 |
116 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
117 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.29401 |
118 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.35781 |
119 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
120 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.83947E-003 |
121 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 9.25770E-004 |
122 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 3.15645 |
123 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
124 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
125 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 105821.15348 |
126 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 9.25770E-004 |
127 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 2791.81671 |
128 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 12.08220 |
129 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.19767 |
130 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
131 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.41644 |
132 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.52711 |
133 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
134 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.92748E-003 |
135 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.37595E-003 |
136 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 4.69080 |
137 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
138 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
139 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 157279.24549 |
140 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.37595E-003 |
141 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 4149.63129 |
142 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 12.17606 |
143 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.12640 |
144 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
145 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.43521 |
146 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.33707 |
147 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
148 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.01425E-003 |
149 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 8.30334E-004 |
150 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 2.83038 |
151 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
152 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
153 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 94912.24029 |
154 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 8.30334E-004 |
155 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 2504.28752 |
156 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.08141 |
157 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.22084 |
158 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.22600 |
159 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.24440 |
160 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.58891 |
161 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
162 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.72521E-003 |
163 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.77844E-004 |
164 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.60667 |
165 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
166 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
167 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 20328.69381 |
168 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.77844E-004 |
169 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 536.19686 |
170 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.16117 |
171 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.13254 |
172 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
173 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.23223 |
174 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.35345 |
175 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
176 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.87453E-003 |
177 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.17461E-004 |
178 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.40071 |
179 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
180 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
181 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 13426.56739 |
182 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.17461E-004 |
183 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 354.13484 |
184 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.31971 |
185 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.18097 |
186 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
187 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.26394 |
188 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.48258 |
189 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
190 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.10534E-003 |
191 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.76542E-004 |
192 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.60222 |
193 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
194 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
195 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 20179.87503 |
196 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.76542E-004 |
197 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 532.27565 |
198 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.29584 |
199 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.11877 |
200 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
201 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.25917 |
202 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.31672 |
203 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
204 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.20791E-003 |
205 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.10180E-004 |
206 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.37582 |
207 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
208 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
209 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 12594.19942 |
210 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.10180E-004 |
211 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 332.20002 |
212 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DATACENTER_BOT_ZN_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.48020 |
213 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DATACENTER_MID_ZN_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 4.57419 |
214 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DATACENTER_TOP_ZN_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.46605 |
215 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DATACENTER_BASEMENT_ZN_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 21.43837 |
216 | AirLoopHVAC | VAV_BOT WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 5.49072 |
217 | AirLoopHVAC | VAV_BOT WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.93953 |
218 | AirLoopHVAC | VAV_BOT WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 10.98145 |
219 | AirLoopHVAC | VAV_BOT WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 2.93953 |
220 | AirLoopHVAC | VAV_BOT WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 9.78940 |
221 | AirLoopHVAC | VAV_BOT WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 9.78940 |
222 | AirLoopHVAC | VAV_BOT WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
223 | AirLoopHVAC | VAV_BOT WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.30028 |
224 | AirLoopHVAC | VAV_MID WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 51.69848 |
225 | AirLoopHVAC | VAV_MID WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 28.51365 |
226 | AirLoopHVAC | VAV_MID WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 103.39697 |
227 | AirLoopHVAC | VAV_MID WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 28.51365 |
228 | AirLoopHVAC | VAV_MID WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 90.93533 |
229 | AirLoopHVAC | VAV_MID WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 90.93533 |
230 | AirLoopHVAC | VAV_MID WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
231 | AirLoopHVAC | VAV_MID WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.31356 |
232 | AirLoopHVAC | VAV_TOP WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 5.29515 |
233 | AirLoopHVAC | VAV_TOP WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.94868 |
234 | AirLoopHVAC | VAV_TOP WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 10.59029 |
235 | AirLoopHVAC | VAV_TOP WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 3.77908 |
236 | AirLoopHVAC | VAV_TOP WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 9.90844 |
237 | AirLoopHVAC | VAV_TOP WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 9.90844 |
238 | AirLoopHVAC | VAV_TOP WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
239 | AirLoopHVAC | VAV_TOP WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.38140 |
240 | AirLoopHVAC | CAV_BAS | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 6.13030 |
241 | AirLoopHVAC | CAV_BAS | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 6.13030 |
242 | AirLoopHVAC | CAV_BAS | Sum of Air Terminal Maximum Flow Rates [m3/s] | 6.13030 |
243 | AirLoopHVAC | CAV_BAS | Adjusted Heating Design Air Flow Rate [m3/s] | 6.13030 |
244 | AirLoopHVAC | CAV_BAS | Adjusted Cooling Design Air Flow Rate [m3/s] | 6.13030 |
245 | AirLoopHVAC | CAV_BAS | Adjusted Main Design Air Flow Rate [m3/s] | 6.13030 |
246 | AirLoopHVAC | CAV_BAS | User Heating Air Flow Ratio [] | 1.00000 |
247 | AirLoopHVAC | CAV_BAS | Calculated Heating Air Flow Ratio [] | 1.00000 |
248 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 21.43837 |
249 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 21.43837 |
250 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 21.43837 |
251 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Adjusted Heating Design Air Flow Rate [m3/s] | 21.43837 |
252 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Adjusted Cooling Design Air Flow Rate [m3/s] | 21.43852 |
253 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Adjusted Main Design Air Flow Rate [m3/s] | 21.43852 |
254 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | User Heating Air Flow Ratio [] | 1.00000 |
255 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Calculated Heating Air Flow Ratio [] | 0.99999 |
256 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.48020 |
257 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.48020 |
258 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.48020 |
259 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Adjusted Heating Design Air Flow Rate [m3/s] | 0.48020 |
260 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.48020 |
261 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Adjusted Main Design Air Flow Rate [m3/s] | 0.48020 |
262 | AirLoopHVAC | AIRLOOP DATACENTER BOT | User Heating Air Flow Ratio [] | 1.00000 |
263 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Calculated Heating Air Flow Ratio [] | 1.00000 |
264 | AirLoopHVAC | AIRLOOP DATACENTER MID | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 4.57419 |
265 | AirLoopHVAC | AIRLOOP DATACENTER MID | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 4.57419 |
266 | AirLoopHVAC | AIRLOOP DATACENTER MID | Sum of Air Terminal Maximum Flow Rates [m3/s] | 4.57419 |
267 | AirLoopHVAC | AIRLOOP DATACENTER MID | Adjusted Heating Design Air Flow Rate [m3/s] | 4.57419 |
268 | AirLoopHVAC | AIRLOOP DATACENTER MID | Adjusted Cooling Design Air Flow Rate [m3/s] | 4.57419 |
269 | AirLoopHVAC | AIRLOOP DATACENTER MID | Adjusted Main Design Air Flow Rate [m3/s] | 4.57419 |
270 | AirLoopHVAC | AIRLOOP DATACENTER MID | User Heating Air Flow Ratio [] | 1.00000 |
271 | AirLoopHVAC | AIRLOOP DATACENTER MID | Calculated Heating Air Flow Ratio [] | 1.00000 |
272 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.46605 |
273 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.46605 |
274 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.46605 |
275 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Adjusted Heating Design Air Flow Rate [m3/s] | 0.46605 |
276 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.46605 |
277 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Adjusted Main Design Air Flow Rate [m3/s] | 0.46605 |
278 | AirLoopHVAC | AIRLOOP DATACENTER TOP | User Heating Air Flow Ratio [] | 1.00000 |
279 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Calculated Heating Air Flow Ratio [] | 1.00000 |
280 | AirLoopHVAC | VAV_BOT WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 9.78940 |
281 | AirLoopHVAC | VAV_MID WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 90.93533 |
282 | AirLoopHVAC | VAV_TOP WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 9.90844 |
283 | AirLoopHVAC | CAV_BAS | Design Supply Air Flow Rate [m3/s] | 6.13030 |
284 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Design Supply Air Flow Rate [m3/s] | 21.43852 |
285 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Design Supply Air Flow Rate [m3/s] | 0.48020 |
286 | AirLoopHVAC | AIRLOOP DATACENTER MID | Design Supply Air Flow Rate [m3/s] | 4.57419 |
287 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Design Supply Air Flow Rate [m3/s] | 0.46605 |
288 | Controller:OutdoorAir | VAV_BOT WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 9.78940 |
289 | Controller:OutdoorAir | VAV_BOT WITH REHEAT_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 2.53819 |
290 | HeatExchanger:AirToAir:SensibleAndLatent | VAV_BOT WITH REHEAT OA HEAT RECOVERY | Design Size Nominal Supply Air Flow Rate [m3/s] | 2.53819 |
291 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Inlet Air Temperature [C] | 26.62800 |
292 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
293 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Outlet Air Temperature [C] | 11.04796 |
294 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 1.09079E-002 |
295 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
296 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Coil Load [W] | 259625.88340 |
297 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 1.10451E-002 |
298 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 9.78940 |
299 | Coil:Heating:Water | VAV_BOT WITH REHEAT HEATING COIL | Design Size Rated Capacity [W] | 27700.35430 |
300 | Coil:Heating:Water | VAV_BOT WITH REHEAT HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.42335E-004 |
301 | Coil:Heating:Water | VAV_BOT WITH REHEAT HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 480.06007 |
302 | Fan:VariableVolume | VAV_BOT WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 9.78940 |
303 | Controller:WaterCoil | VAV_BOT WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 1.10451E-002 |
304 | Controller:WaterCoil | VAV_BOT WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 4.31133E-005 |
305 | Controller:WaterCoil | VAV_BOT WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 2.42335E-004 |
306 | Controller:OutdoorAir | VAV_MID WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 90.93533 |
307 | Controller:OutdoorAir | VAV_MID WITH REHEAT_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 25.38195 |
308 | HeatExchanger:AirToAir:SensibleAndLatent | VAV_MID WITH REHEAT OA HEAT RECOVERY | Design Size Nominal Supply Air Flow Rate [m3/s] | 25.38195 |
309 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Inlet Air Temperature [C] | 26.91330 |
310 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
311 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Outlet Air Temperature [C] | 11.04890 |
312 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 1.12038E-002 |
313 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
314 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Coil Load [W] | 2526201.21331 |
315 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 0.10747 |
316 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 90.93533 |
317 | Coil:Heating:Water | VAV_MID WITH REHEAT HEATING COIL | Design Size Rated Capacity [W] | 233004.13073 |
318 | Coil:Heating:Water | VAV_MID WITH REHEAT HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.03842E-003 |
319 | Coil:Heating:Water | VAV_MID WITH REHEAT HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 4058.74174 |
320 | Fan:VariableVolume | VAV_MID WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 90.93533 |
321 | Controller:WaterCoil | VAV_MID WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 0.10747 |
322 | Controller:WaterCoil | VAV_MID WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 4.43090E-006 |
323 | Controller:WaterCoil | VAV_MID WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 2.03842E-003 |
324 | Controller:OutdoorAir | VAV_TOP WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 9.90844 |
325 | Controller:OutdoorAir | VAV_TOP WITH REHEAT_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 2.53819 |
326 | HeatExchanger:AirToAir:SensibleAndLatent | VAV_TOP WITH REHEAT OA HEAT RECOVERY | Design Size Nominal Supply Air Flow Rate [m3/s] | 2.53819 |
327 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Inlet Air Temperature [C] | 26.52004 |
328 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
329 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Outlet Air Temperature [C] | 11.04791 |
330 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 1.08920E-002 |
331 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
332 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Coil Load [W] | 260981.37478 |
333 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 1.11028E-002 |
334 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 9.90844 |
335 | Coil:Heating:Water | VAV_TOP WITH REHEAT HEATING COIL | Design Size Rated Capacity [W] | 20857.57617 |
336 | Coil:Heating:Water | VAV_TOP WITH REHEAT HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.82471E-004 |
337 | Coil:Heating:Water | VAV_TOP WITH REHEAT HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 366.57951 |
338 | Fan:VariableVolume | VAV_TOP WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 9.90844 |
339 | Controller:WaterCoil | VAV_TOP WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 1.11028E-002 |
340 | Controller:WaterCoil | VAV_TOP WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 4.28894E-005 |
341 | Controller:WaterCoil | VAV_TOP WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 1.82471E-004 |
342 | Controller:OutdoorAir | CAV_BAS_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 6.13030 |
343 | Controller:OutdoorAir | CAV_BAS_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.20016 |
344 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Inlet Air Temperature [C] | 24.84296 |
345 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
346 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Outlet Air Temperature [C] | 11.42394 |
347 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 1.04005E-002 |
348 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
349 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Coil Load [W] | 136722.67034 |
350 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 5.81650E-003 |
351 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 6.13030 |
352 | Coil:Heating:Water | CAV_BAS HEATING COIL | Design Size Rated Capacity [W] | 289789.71787 |
353 | Coil:Heating:Water | CAV_BAS HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.53521E-003 |
354 | Coil:Heating:Water | CAV_BAS HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 6568.00037 |
355 | Fan:ConstantVolume | CAV_BAS FAN | Design Size Maximum Flow Rate [m3/s] | 6.13030 |
356 | Controller:WaterCoil | CAV_BAS_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 5.81650E-003 |
357 | Controller:WaterCoil | CAV_BAS_COOLC_CONTROLLER | Controller Convergence Tolerance | 8.18689E-005 |
358 | Controller:WaterCoil | CAV_BAS_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 2.53521E-003 |
359 | Controller:OutdoorAir | AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 21.43852 |
360 | Controller:OutdoorAir | AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.33839 |
361 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 21.43852 |
362 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Rated Total Cooling Capacity [W] | 436425.08036 |
363 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Rated Sensible Cooling Capacity [W] | 313849.49892 |
364 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Rated Water Flow Rate [m3/s] | 1.06880E-002 |
365 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 21.43852 |
366 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 21.43852 |
367 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 21.43852 |
368 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 21.43852 |
369 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Nominal Heating Capacity [W] | 436425.08036 |
370 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 436425.08036 |
371 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 14482.88751 |
372 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
373 | Fan:OnOff | AIRLOOP DATACENTER BASEMENT SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 21.43852 |
374 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 21.43852 |
375 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT HEATING COIL | Design Size Rated Heating Capacity [W] | 436425.08036 |
376 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT HEATING COIL | Design Size Rated Water Flow Rate [m3/s] | 1.06880E-002 |
377 | Coil:Heating:Electric | AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 14482.88751 |
378 | Humidifier:Steam:Electric | DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | Design Size Nominal Capacity Volume [m3/s] | 8.05456E-005 |
379 | Humidifier:Steam:Electric | DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | User-Specified Nominal Capacity Volume [m3/s] | 3.72000E-005 |
380 | Humidifier:Steam:Electric | DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | Design Size Rated Power [W] | 96450.69782 |
381 | Humidifier:Steam:Electric | DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | User-Specified Rated Power [W] | 100000.00000 |
382 | Controller:OutdoorAir | AIRLOOP DATACENTER BOT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.48020 |
383 | Controller:OutdoorAir | AIRLOOP DATACENTER BOT_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.56323E-002 |
384 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.48020 |
385 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT COOLING COIL | Design Size Rated Total Cooling Capacity [W] | 9781.48279 |
386 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT COOLING COIL | Design Size Rated Sensible Cooling Capacity [W] | 7027.92308 |
387 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT COOLING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.39548E-004 |
388 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 0.48020 |
389 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 0.48020 |
390 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 0.48020 |
391 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 0.48020 |
392 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Nominal Heating Capacity [W] | 9781.48279 |
393 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 9781.48279 |
394 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 669.04940 |
395 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
396 | Fan:OnOff | AIRLOOP DATACENTER BOT SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.48020 |
397 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.48020 |
398 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT HEATING COIL | Design Size Rated Heating Capacity [W] | 9781.48279 |
399 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT HEATING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.39548E-004 |
400 | Coil:Heating:Electric | AIRLOOP DATACENTER BOT_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 669.04940 |
401 | Controller:OutdoorAir | AIRLOOP DATACENTER MID_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 4.57419 |
402 | Controller:OutdoorAir | AIRLOOP DATACENTER MID_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.15632 |
403 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 4.57419 |
404 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID COOLING COIL | Design Size Rated Total Cooling Capacity [W] | 93413.42152 |
405 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID COOLING COIL | Design Size Rated Sensible Cooling Capacity [W] | 67025.97789 |
406 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID COOLING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.28769E-003 |
407 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 4.57419 |
408 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 4.57419 |
409 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 4.57419 |
410 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 4.57419 |
411 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Nominal Heating Capacity [W] | 93413.42152 |
412 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 93413.42152 |
413 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 6690.49404 |
414 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
415 | Fan:OnOff | AIRLOOP DATACENTER MID SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 4.57419 |
416 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 4.57419 |
417 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID HEATING COIL | Design Size Rated Heating Capacity [W] | 93413.42152 |
418 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID HEATING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.28769E-003 |
419 | Coil:Heating:Electric | AIRLOOP DATACENTER MID_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 6690.49404 |
420 | Controller:OutdoorAir | AIRLOOP DATACENTER TOP_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.46605 |
421 | Controller:OutdoorAir | AIRLOOP DATACENTER TOP_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.56323E-002 |
422 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.46605 |
423 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP COOLING COIL | Design Size Rated Total Cooling Capacity [W] | 9511.32942 |
424 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP COOLING COIL | Design Size Rated Sensible Cooling Capacity [W] | 6826.92776 |
425 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP COOLING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.32932E-004 |
426 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 0.46605 |
427 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 0.46605 |
428 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 0.46605 |
429 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 0.46605 |
430 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Nominal Heating Capacity [W] | 9511.32942 |
431 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 9511.32942 |
432 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 669.04940 |
433 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
434 | Fan:OnOff | AIRLOOP DATACENTER TOP SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.46605 |
435 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.46605 |
436 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP HEATING COIL | Design Size Rated Heating Capacity [W] | 9511.32942 |
437 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP HEATING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.32932E-004 |
438 | Coil:Heating:Electric | AIRLOOP DATACENTER TOP_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 669.04940 |
439 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Flow Rate [m3/s] | 0.13543 |
440 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Power Consumption [W] | 22112.36018 |
441 | PlantLoop | COOLSYS1_DEMAND | Maximum Loop Flow Rate [m3/s] | 0.13543 |
442 | PlantLoop | COOLSYS1_DEMAND | Plant Loop Volume [m3] | 16.25217 |
443 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Loop Supply Side Design Fluid Flow Rate [m3/s] | 0.13543 |
444 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Loop Demand Side Design Fluid Flow Rate [m3/s] | 0.13543 |
445 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Heat Exchanger U-Factor Times Area Value [W/C] | 568487.70390 |
446 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Loop-to-loop Temperature Difference Used to Size Heat Exchanger U-Factor Times Area Value [C] | 5.60000 |
447 | PlantLoop | HEATSYS1 | Maximum Loop Flow Rate [m3/s] | 1.43047E-002 |
448 | PlantLoop | HEATSYS1 | Plant Loop Volume [m3] | 1.71657 |
449 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Flow Rate [m3/s] | 1.43047E-002 |
450 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Power Consumption [W] | 4307.95487 |
451 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Minimum Flow Rate [m3/s] | 0.00000 |
452 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Nominal Capacity [W] | 1635117.89393 |
453 | Boiler:HotWater | HEATSYS1 BOILER | User-Specified Nominal Capacity [W] | 1635117.89000 |
454 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Design Water Flow Rate [m3/s] | 1.43047E-002 |
455 | PlantLoop | COOLSYS1_SUPPLY | Maximum Loop Flow Rate [m3/s] | 0.13543 |
456 | PlantLoop | COOLSYS1_SUPPLY | Plant Loop Volume [m3] | 16.25217 |
457 | Pump:ConstantSpeed | COOLSYS1 CHILLER1 PUMP | Design Flow Rate [m3/s] | 6.77174E-002 |
458 | Pump:ConstantSpeed | COOLSYS1 CHILLER1 PUMP | Design Power Consumption [W] | 7654.56633 |
459 | Pump:ConstantSpeed | COOLSYS1 CHILLER2 PUMP | Design Flow Rate [m3/s] | 6.77174E-002 |
460 | Pump:ConstantSpeed | COOLSYS1 CHILLER2 PUMP | Design Power Consumption [W] | 7654.56633 |
461 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | Design Size Reference Chilled Water Flow Rate [m3/s] | 0.13543 |
462 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | User-Specified Reference Chilled Water Flow Rate [m3/s] | 6.82950E-002 |
463 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | Design Size Reference Capacity [W] | 1609286.42098 |
464 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | User-Specified Reference Capacity [W] | 1616928.89500 |
465 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | Design Size Reference Condenser Water Flow Rate [m3/s] | 8.00158E-002 |
466 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | Design Size Reference Chilled Water Flow Rate [m3/s] | 0.13543 |
467 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | User-Specified Reference Chilled Water Flow Rate [m3/s] | 6.82950E-002 |
468 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | Design Size Reference Capacity [W] | 1609286.42098 |
469 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | User-Specified Reference Capacity [W] | 1616928.89500 |
470 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | Design Size Reference Condenser Water Flow Rate [m3/s] | 8.00158E-002 |
471 | PlantLoop | SINGLE WATER PLANT LOOP | Maximum Loop Flow Rate [m3/s] | 1.34482E-002 |
472 | PlantLoop | SINGLE WATER PLANT LOOP | Plant Loop Volume [m3] | 1.61378 |
473 | Pump:ConstantSpeed | PLANT CIRC PUMP | Design Flow Rate [m3/s] | 1.34482E-002 |
474 | Pump:ConstantSpeed | PLANT CIRC PUMP | Design Power Consumption [W] | 3429.96110 |
475 | FluidCooler:TwoSpeed | CENTRAL TOWER | Design Water Flow Rate [m3/s] | 1.34482E-002 |
476 | FluidCooler:TwoSpeed | CENTRAL TOWER | Air Flow Rate at High Fan Speed [m3/s] | 139666.46671 |
477 | FluidCooler:TwoSpeed | CENTRAL TOWER | Fluid cooler UA value at high fan speed based on nominal capacity input [W/K] | 58672.21993 |
478 | FluidCooler:TwoSpeed | CENTRAL TOWER | Air Flow Rate at Low Fan Speed [m3/s] | 69833.23335 |
479 | FluidCooler:TwoSpeed | CENTRAL TOWER | Fan Power at Low Fan Speed [W] | 7879.72339 |
480 | FluidCooler:TwoSpeed | CENTRAL TOWER | U-factor Times Area Value at Low Fan Speed [W/C] | 21354.91127 |
481 | Boiler:HotWater | CENTRAL BOILER | Design Size Nominal Capacity [W] | 553950.15822 |
482 | Boiler:HotWater | CENTRAL BOILER | User-Specified Nominal Capacity [W] | 543304.15000 |
483 | Boiler:HotWater | CENTRAL BOILER | Design Size Design Water Flow Rate [m3/s] | 1.34482E-002 |
484 | PlantLoop | SWHSYS1 | Maximum Loop Flow Rate [m3/s] | 4.40000E-004 |
485 | PlantLoop | SWHSYS1 | Plant Loop Volume [m3] | 5.28000E-002 |
486 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Flow Rate [m3/s] | 4.40000E-004 |
487 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Power Consumption [W] | 56.20530 |
488 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | Use Side Design Flow Rate [m3/s] | 4.40000E-004 |
489 | CondenserLoop | TOWERWATERSYS | Maximum Loop Flow Rate [m3/s] | 0.16003 |
490 | CondenserLoop | TOWERWATERSYS | Condenser Loop Volume [m3] | 19.20380 |
491 | HeaderedPumps:VariableSpeed | TOWERWATERSYS PUMP | Design Flow Rate [m3/s] | 0.16003 |
492 | HeaderedPumps:VariableSpeed | TOWERWATERSYS PUMP | Design Power Consumption [W] | 39620.29252 |
493 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Design Air Flow Rate [m3/s] | 61.57008 |
494 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Nominal Capacity [W] | 1918476.60278 |
495 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Air Flow Rate in free convection regime [m3/s] | 12.31402 |
496 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Tower capacity in free convection regime at design conditions [W] | 239809.57535 |
497 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Design Air Flow Rate [m3/s] | 61.57008 |
498 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Nominal Capacity [W] | 1918476.60278 |
499 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Air Flow Rate in free convection regime [m3/s] | 12.31402 |
500 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Tower capacity in free convection regime at design conditions [W] | 239809.57535 |
501 | PlantEquipmentOperation:ComponentSetPoint | WSHPPLANT OPERATION SCHEME | Design Water Flow Rate [m3/s] Equipment # 47 | 8.31125E-002 |
502 | PlantEquipmentOperation:ComponentSetPoint | WSHPPLANT OPERATION SCHEME | Design Water Flow Rate [m3/s] Equipment # 47 | 8.31125E-002 |
Component Type | Name | Nominal Total Capacity {W} | |
1 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | 18505.12 |
2 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | 355427.53 |
3 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | 58635.02 |
4 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | 5973.20 |
5 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | 4873.33 |
6 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | 7690.54 |
7 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | 4104.65 |
8 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | 150499.81 |
9 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | 100264.98 |
10 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | 149022.76 |
11 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | 89930.68 |
12 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | 19260.50 |
13 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | 12721.00 |
14 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | 19119.53 |
15 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | 11932.50 |
16 | Coil:Heating:Water | VAV_BOT WITH REHEAT HEATING COIL | 23609.83 |
17 | Coil:Heating:Water | VAV_MID WITH REHEAT HEATING COIL | 200518.93 |
18 | Coil:Heating:Water | VAV_TOP WITH REHEAT HEATING COIL | 18251.88 |
19 | Coil:Heating:Water | CAV_BAS HEATING COIL | 234647.64 |
Component Type | Name | Nominal Total Capacity {W} | Nominal Sensible Capacity {W} | Nominal Latent Capacity {W} | Nominal Sensible Heat Ratio | Nominal Coil UA Value {W/C} | Nominal Coil Surface Area {m2} | |
1 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | 265210.15 | 179647.95 | 85562.20 | 0.68 | 27551.68 | 279.44 |
2 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | 2507859.18 | 1689787.34 | 818071.85 | 0.67 | 261478.59 | 2652.06 |
3 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | 267787.48 | 181529.86 | 86257.62 | 0.68 | 27818.70 | 282.15 |
4 | Coil:Cooling:Water | CAV_BAS COOLING COIL | 153520.17 | 106461.25 | 47058.92 | 0.69 | 15635.42 | 158.58 |
Component Type | Component Name | IPLV in SI Units {W/W} | IPLV in IP Units {Btu/W-h} | |
1 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | 6.84 | 23.33 |
2 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | 6.84 | 23.33 |
Zone Name | # Surfaces | |
1 | BASEMENT | 10 |
2 | CORE_BOTTOM | 8 |
3 | CORE_MID | 7 |
4 | CORE_TOP | 7 |
5 | PERIMETER_BOT_ZN_3 | 18 |
6 | PERIMETER_BOT_ZN_2 | 12 |
7 | PERIMETER_BOT_ZN_1 | 18 |
8 | PERIMETER_BOT_ZN_4 | 12 |
9 | PERIMETER_MID_ZN_3 | 9 |
10 | PERIMETER_MID_ZN_2 | 8 |
11 | PERIMETER_MID_ZN_1 | 9 |
12 | PERIMETER_MID_ZN_4 | 8 |
13 | PERIMETER_TOP_ZN_3 | 9 |
14 | PERIMETER_TOP_ZN_2 | 8 |
15 | PERIMETER_TOP_ZN_1 | 9 |
16 | PERIMETER_TOP_ZN_4 | 8 |
17 | GROUNDFLOOR_PLENUM | 11 |
18 | MIDFLOOR_PLENUM | 11 |
19 | TOPFLOOR_PLENUM | 11 |
20 | DATACENTER_BOT_ZN_6 | 6 |
21 | DATACENTER_MID_ZN_6 | 6 |
22 | DATACENTER_TOP_ZN_6 | 6 |
23 | DATACENTER_BASEMENT_ZN_6 | 10 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | BASEMENT_WALL_EAST | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_EAST_CFACTOR | 0.940 | 0.824 | 118.87 | 118.87 | 118.87 | 90.00 | 90.00 | 48.74 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | BASEMENT_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_SOUTH_CFACTOR | 0.940 | 0.824 | 139.09 | 139.09 | 139.09 | 180.00 | 90.00 | 57.03 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
3 | BASEMENT_WALL_NORTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_NORTH_CFACTOR | 0.940 | 0.824 | 139.09 | 139.09 | 139.09 | 0.00 | 90.00 | 57.03 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | BASEMENT_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.87 | 118.87 | 118.87 | 270.00 | 90.00 | 48.74 | 2.44 | 0.00 | DATACENTER_BASEMENT_ZN_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
5 | BASEMENT_FLOOR | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 2779.43 | 2779.43 | 2779.43 | 0.00 | 180.00 | 57.03 | 48.74 | 0.00 | BASEMENT_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
6 | PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | PERIMETER_BOT_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
7 | PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 250.34 | 250.34 | 250.34 | 180.00 | 0.00 | 57.03 | 4.57 | 0.00 | PERIMETER_BOT_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
8 | CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 2076.77 | 2076.77 | 2076.77 | 180.00 | 0.00 | 52.45 | 39.59 | 0.00 | CORE_BOT_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
9 | PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 250.34 | 250.34 | 250.34 | 180.00 | 0.00 | 52.45 | 4.57 | 0.00 | PERIMETER_BOT_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
10 | BASEMENT_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 7126.21 | 7126.21 | 7126.21 | 0.00 | 90.00 | 7126.21 | 1.00 | 0.00 | BASEMENT_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
11 | CORE_BOT_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
12 | CORE_BOT_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
13 | CORE_BOT_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
14 | CORE_BOT_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
15 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 419.30 | 419.30 | 419.30 | 0.00 | 180.00 | 10.59 | 39.59 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
16 | CORE_BOT_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 2076.82 | 2076.82 | 2076.82 | 0.00 | 180.00 | 52.46 | 39.59 | 0.00 | CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
17 | CORE_BOT_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 2496.12 | 2496.12 | 2496.12 | 180.00 | 0.00 | 63.05 | 39.59 | 0.00 | iz-CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
18 | CORE_BOTTOM_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 5064.65 | 5064.65 | 5064.65 | 0.00 | 90.00 | 5064.65 | 1.00 | 0.00 | CORE_BOTTOM_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
19 | CORE_MID_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
20 | CORE_MID_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
21 | CORE_MID_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
22 | CORE_MID_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
23 | CORE_MID_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_MID_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
24 | CORE_MID_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 2496.12 | 2496.12 | 2496.12 | 180.00 | 0.00 | 63.05 | 39.59 | 0.00 | iz-CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
25 | CORE_MID_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 5064.65 | 5064.65 | 5064.65 | 0.00 | 90.00 | 5064.65 | 1.00 | 0.00 | CORE_MID_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
26 | CORE_TOP_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
27 | CORE_TOP_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
28 | CORE_TOP_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
29 | CORE_TOP_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
30 | CORE_TOP_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_TOP_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
31 | CORE_TOP_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 2496.12 | 2496.12 | 2496.12 | 180.00 | 0.00 | 63.05 | 39.59 | 0.00 | iz-CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
32 | CORE_TOP_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 5064.65 | 5064.65 | 5064.65 | 0.00 | 90.00 | 5064.65 | 1.00 | 0.00 | CORE_TOP_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
33 | PERIMETER_BOT_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.452 | 1.193 | 76.91 | 200.61 | 76.91 | 0.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
34 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.567_SHGC_NORTH_0.25 | N/A | 3.224 | No | 23.18 | 23.18 | 23.18 | 0.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
35 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.567_SHGC_NORTH_0.25 | N/A | 3.224 | No | 23.18 | 23.18 | 23.18 | 0.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
36 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.567_SHGC_NORTH_0.25 | N/A | 3.224 | No | 23.18 | 23.18 | 23.18 | 0.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
37 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.567_SHGC_NORTH_0.25 | N/A | 3.224 | No | 23.18 | 23.18 | 23.18 | 0.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
38 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.567_SHGC_NORTH_0.25 | N/A | 3.224 | No | 23.18 | 23.18 | 23.18 | 0.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
39 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.975 | 3.975 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
40 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.975 | 3.975 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
41 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.975 | 3.975 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
42 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.975 | 3.975 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
43 | PERIMETER_BOT_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
44 | CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
45 | PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
46 | DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
47 | PERIMETER_BOT_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 250.34 | 250.34 | 250.34 | 0.00 | 180.00 | 52.46 | 6.47 | 0.00 | PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
48 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 63.07 | 63.07 | 63.07 | 0.00 | 180.00 | 11.51 | 4.57 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
49 | PERIMETER_BOT_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.41 | 313.41 | 313.41 | 180.00 | 0.00 | 63.96 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
50 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.83 | 626.83 | 626.83 | 0.00 | 90.00 | 626.83 | 1.00 | 0.00 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
51 | PERIMETER_BOT_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.452 | 1.193 | 52.57 | 133.74 | 52.57 | 90.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
52 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.567_SHGC_EAST_0.25 | N/A | 3.224 | No | 25.75 | 25.75 | 25.75 | 90.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
53 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.567_SHGC_EAST_0.25 | N/A | 3.224 | No | 25.75 | 25.75 | 25.75 | 90.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
54 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.567_SHGC_EAST_0.25 | N/A | 3.224 | No | 25.75 | 25.75 | 25.75 | 90.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
55 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | Door | PERIMETER_BOT_ZN_2_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.975 | 3.975 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
56 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | Door | PERIMETER_BOT_ZN_2_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.975 | 3.975 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
57 | PERIMETER_BOT_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
58 | CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
59 | PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
60 | PERIMETER_BOT_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
61 | PERIMETER_BOT_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | iz-PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
62 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
63 | PERIMETER_BOT_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.452 | 1.193 | 76.91 | 200.61 | 76.91 | 180.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
64 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.567_SHGC_SOUTH_0.25 | N/A | 3.224 | No | 23.18 | 23.18 | 23.18 | 180.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
65 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.567_SHGC_SOUTH_0.25 | N/A | 3.224 | No | 23.18 | 23.18 | 23.18 | 180.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
66 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.567_SHGC_SOUTH_0.25 | N/A | 3.224 | No | 23.18 | 23.18 | 23.18 | 180.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
67 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.567_SHGC_SOUTH_0.25 | N/A | 3.224 | No | 23.18 | 23.18 | 23.18 | 180.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
68 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.567_SHGC_SOUTH_0.25 | N/A | 3.224 | No | 23.18 | 23.18 | 23.18 | 180.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
69 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.975 | 3.975 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
70 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.975 | 3.975 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
71 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.975 | 3.975 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
72 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.975 | 3.975 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
73 | PERIMETER_BOT_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
74 | DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
75 | PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
76 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
77 | DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 63.07 | 63.07 | 63.07 | 0.00 | 180.00 | 16.08 | 4.57 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
78 | PERIMETER_BOT_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 250.35 | 250.35 | 250.35 | 0.00 | 180.00 | 57.03 | 6.47 | 0.00 | PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
79 | PERIMETER_BOT_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.42 | 313.42 | 313.42 | 180.00 | 0.00 | 73.11 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
80 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.84 | 626.84 | 626.84 | 0.00 | 90.00 | 626.84 | 1.00 | 0.00 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
81 | PERIMETER_BOT_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.452 | 1.193 | 52.57 | 133.74 | 52.57 | 270.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
82 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.567_SHGC_WEST_0.25 | N/A | 3.224 | No | 25.75 | 25.75 | 25.75 | 270.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
83 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.567_SHGC_WEST_0.25 | N/A | 3.224 | No | 25.75 | 25.75 | 25.75 | 270.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
84 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.567_SHGC_WEST_0.25 | N/A | 3.224 | No | 25.75 | 25.75 | 25.75 | 270.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
85 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | Door | PERIMETER_BOT_ZN_4_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.975 | 3.975 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
86 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | Door | PERIMETER_BOT_ZN_4_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.975 | 3.975 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
87 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
88 | DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
89 | PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
90 | PERIMETER_BOT_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
91 | PERIMETER_BOT_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | iz-PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
92 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
93 | PERIMETER_MID_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.400 | 1.158 | 84.71 | 200.61 | 84.71 | 0.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
94 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_MID_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.567_SHGC_NORTH_0.25 | N/A | 3.224 | No | 115.90 | 115.90 | 115.90 | 0.00 | 90.00 | 73.11 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
95 | PERIMETER_MID_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
96 | CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
97 | PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
98 | DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
99 | PERIMETER_MID_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
100 | PERIMETER_MID_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.41 | 313.41 | 313.41 | 180.00 | 0.00 | 63.96 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
101 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.83 | 626.83 | 626.83 | 0.00 | 90.00 | 626.83 | 1.00 | 0.00 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
102 | PERIMETER_MID_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.400 | 1.158 | 56.47 | 133.74 | 56.47 | 90.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
103 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_MID_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.567_SHGC_EAST_0.25 | N/A | 3.224 | No | 77.26 | 77.26 | 77.26 | 90.00 | 90.00 | 48.74 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
104 | PERIMETER_MID_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
105 | CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
106 | PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
107 | PERIMETER_MID_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_MID_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
108 | PERIMETER_MID_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | iz-PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
109 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
110 | PERIMETER_MID_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
111 | PERIMETER_MID_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.400 | 1.158 | 84.71 | 200.61 | 84.71 | 180.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
112 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_MID_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.567_SHGC_SOUTH_0.25 | N/A | 3.224 | No | 115.90 | 115.90 | 115.90 | 180.00 | 90.00 | 73.11 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
113 | DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
114 | PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
115 | CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
116 | PERIMETER_MID_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
117 | PERIMETER_MID_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.42 | 313.42 | 313.42 | 180.00 | 0.00 | 73.11 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
118 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.84 | 626.84 | 626.84 | 0.00 | 90.00 | 626.84 | 1.00 | 0.00 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
119 | PERIMETER_MID_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.400 | 1.158 | 56.47 | 133.74 | 56.47 | 270.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
120 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_MID_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.567_SHGC_WEST_0.25 | N/A | 3.224 | No | 77.26 | 77.26 | 77.26 | 270.00 | 90.00 | 48.74 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
121 | PERIMETER_MID_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
122 | DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
123 | PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
124 | PERIMETER_MID_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_MID_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
125 | PERIMETER_MID_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | iz-PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
126 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
127 | PERIMETER_TOP_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.662 | 1.331 | 84.71 | 200.61 | 84.71 | 0.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
128 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_TOP_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.567_SHGC_NORTH_0.25 | N/A | 3.224 | No | 115.90 | 115.90 | 115.90 | 0.00 | 90.00 | 73.11 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
129 | PERIMETER_TOP_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
130 | CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
131 | PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
132 | DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
133 | PERIMETER_TOP_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_TOP_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
134 | PERIMETER_TOP_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.41 | 313.41 | 313.41 | 180.00 | 0.00 | 63.96 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
135 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.83 | 626.83 | 626.83 | 0.00 | 90.00 | 626.83 | 1.00 | 0.00 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
136 | PERIMETER_TOP_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.662 | 1.331 | 56.47 | 133.74 | 56.47 | 90.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
137 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_TOP_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.567_SHGC_EAST_0.25 | N/A | 3.224 | No | 77.26 | 77.26 | 77.26 | 90.00 | 90.00 | 48.74 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
138 | PERIMETER_TOP_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
139 | CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
140 | INT-PER3S-NE-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | INT-PER3S-NE | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
141 | PERIMETER_TOP_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_TOP_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
142 | PERIMETER_TOP_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | iz-PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
143 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
144 | PERIMETER_TOP_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.662 | 1.331 | 84.71 | 200.61 | 84.71 | 180.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
145 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_TOP_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.567_SHGC_SOUTH_0.25 | N/A | 3.224 | No | 115.90 | 115.90 | 115.90 | 180.00 | 90.00 | 73.11 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
146 | INT-PER3S-NE | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | INT-PER3S-NE-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
147 | DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
148 | PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
149 | CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
150 | PERIMETER_TOP_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_TOP_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
151 | PERIMETER_TOP_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.42 | 313.42 | 313.42 | 180.00 | 0.00 | 73.11 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
152 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.84 | 626.84 | 626.84 | 0.00 | 90.00 | 626.84 | 1.00 | 0.00 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
153 | PERIMETER_TOP_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.662 | 1.331 | 56.47 | 133.74 | 56.47 | 270.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
154 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_TOP_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.567_SHGC_WEST_0.25 | N/A | 3.224 | No | 77.26 | 77.26 | 77.26 | 270.00 | 90.00 | 48.74 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
155 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
156 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
157 | PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
158 | PERIMETER_TOP_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_TOP_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
159 | PERIMETER_TOP_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | iz-PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
160 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
161 | GROUNDFLOOR_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.452 | 1.193 | 89.13 | 89.13 | 89.13 | 0.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
162 | GROUNDFLOOR_PLENUM_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.452 | 1.193 | 59.42 | 59.42 | 59.42 | 270.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
163 | GROUNDFLOOR_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.452 | 1.193 | 89.13 | 89.13 | 89.13 | 180.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
164 | GROUNDFLOOR_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.452 | 1.193 | 59.42 | 59.42 | 59.42 | 90.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
165 | iz-CORE_BOT_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
166 | iz-PERIMETER_BOT_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
167 | iz-PERIMETER_BOT_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
168 | iz-PERIMETER_BOT_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
169 | iz-PERIMETER_BOT_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
170 | iz-DATACENTER_BOT_ZN_6_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_BOT_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
171 | GROUNDFLOOR_PLENUM_CEILING | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 3563.11 | 3563.11 | 3563.11 | 180.00 | 0.00 | 73.11 | 48.74 | 0.00 | GROUNDFLOOR_PLENUM_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
172 | MIDFLOOR_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.400 | 1.158 | 89.13 | 89.13 | 89.13 | 0.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
173 | MIDFLOOR_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.400 | 1.158 | 59.42 | 59.42 | 59.42 | 270.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
174 | MIDFLOOR_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.400 | 1.158 | 89.13 | 89.13 | 89.13 | 180.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
175 | MIDFLOOR_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.400 | 1.158 | 59.42 | 59.42 | 59.42 | 90.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
176 | iz-CORE_MID_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
177 | iz-PERIMETER_MID_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
178 | iz-PERIMETER_MID_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
179 | iz-PERIMETER_MID_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
180 | iz-PERIMETER_MID_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
181 | iz-DATACENTER_MID_ZN_6_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_MID_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
182 | MIDFLOOR_PLENUM_CEILING | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 3563.11 | 3563.11 | 3563.11 | 180.00 | 0.00 | 73.11 | 48.74 | 0.00 | MIDFLOOR_PLENUM_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
183 | TOPFLOOR_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.662 | 1.331 | 89.13 | 89.13 | 89.13 | 180.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
184 | TOPFLOOR_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.662 | 1.331 | 59.42 | 59.42 | 59.42 | 90.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
185 | TOPFLOOR_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.662 | 1.331 | 59.42 | 59.42 | 59.42 | 270.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
186 | TOPFLOOR_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.662 | 1.331 | 89.13 | 89.13 | 89.13 | 0.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
187 | iz-CORE_TOP_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
188 | iz-PERIMETER_TOP_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
189 | iz-PERIMETER_TOP_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
190 | iz-PERIMETER_TOP_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
191 | iz-PERIMETER_TOP_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
192 | iz-DATACENTER_TOP_ZN_6_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_TOP_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
193 | BUILDING_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 3563.11 | 3563.11 | 3563.11 | 180.00 | 0.00 | 73.11 | 48.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
194 | DATACENTER_BOT_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
195 | DATACENTER_BOT_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
196 | DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
197 | DATACENTER_BOT_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
198 | DATACENTER_BOT_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
199 | DATACENTER_BOT_ZN_6_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | iz-DATACENTER_BOT_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
200 | DATACENTER_MID_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
201 | DATACENTER_MID_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
202 | DATACENTER_MID_ZN_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
203 | DATACENTER_MID_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
204 | DATACENTER_MID_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_MID_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
205 | DATACENTER_MID_ZN_6_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | iz-DATACENTER_MID_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
206 | DATACENTER_TOP_ZN_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
207 | DATACENTER_TOP_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
208 | DATACENTER_TOP_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
209 | DATACENTER_TOP_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
210 | DATACENTER_TOP_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_TOP_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
211 | DATACENTER_TOP_ZN_6_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | iz-DATACENTER_TOP_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
212 | DATACENTER_BASEMENT_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR | 0.940 | 0.824 | 39.22 | 39.22 | 39.22 | 0.00 | 90.00 | 16.08 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
213 | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR | 0.940 | 0.824 | 39.22 | 39.22 | 39.22 | 180.00 | 90.00 | 16.08 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
214 | DATACENTER_BASEMENT_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR | 0.940 | 0.824 | 118.87 | 118.87 | 118.87 | 270.00 | 90.00 | 48.74 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
215 | DATACENTER_BASEMENT_ZN_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.87 | 118.87 | 118.87 | 90.00 | 90.00 | 48.74 | 2.44 | 0.00 | BASEMENT_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
216 | DATACENTER_BASEMENT_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 783.68 | 783.68 | 783.68 | 0.00 | 180.00 | 16.08 | 48.74 | 0.00 | DATACENTER_BASEMENT_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
217 | DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | DATACENTER_BOT_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
218 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 419.35 | 419.35 | 419.35 | 180.00 | 0.00 | 10.59 | 39.59 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
219 | PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | PERIMETER_BOT_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
220 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 63.08 | 63.08 | 63.08 | 180.00 | 0.00 | 16.08 | 6.47 | 0.00 | DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
221 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 63.07 | 63.07 | 63.07 | 180.00 | 0.00 | 11.51 | 6.47 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | BASEMENT | RunPeriod: RUNPERIOD 1 | 0.1887535897 | 0.1842427941 | Pass | Pass | 0.6641978197 | 0.5923391003 | Pass | Pass |
2 | CORE_BOTTOM | RunPeriod: RUNPERIOD 1 | 0.2195046336 | 0.2386445599 | Pass | Pass | 0.2381499001 | 0.4244647694 | Pass | Pass |
3 | CORE_MID | RunPeriod: RUNPERIOD 1 | 0.1368556292 | 0.2013052105 | Pass | Pass | 0.1885345006 | 0.3900654389 | Pass | Pass |
4 | CORE_TOP | RunPeriod: RUNPERIOD 1 | 0.1411479389 | 0.2211058522 | Pass | Pass | 0.1836529555 | 0.3861030742 | Pass | Pass |
5 | PERIMETER_BOT_ZN_3 | RunPeriod: RUNPERIOD 1 | 0.1900770795 | 0.2158283921 | Pass | Pass | 0.2370065186 | 0.4230510723 | Pass | Pass |
6 | PERIMETER_BOT_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.2919153354 | 0.3452253131 | Pass | Pass | 0.2398282526 | 0.4238281099 | Pass | Pass |
7 | PERIMETER_BOT_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.4105719158 | 0.6117767968 | Pass | Pass | 0.2640599133 | 0.4461095079 | Pass | Pass |
8 | PERIMETER_BOT_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.3629657445 | 0.4823633969 | Pass | Pass | 0.2420278735 | 0.4219508190 | Pass | Pass |
9 | PERIMETER_MID_ZN_3 | RunPeriod: RUNPERIOD 1 | 0.1264422455 | 0.1921305457 | Pass | Pass | 0.1885953011 | 0.3888132471 | Pass | Pass |
10 | PERIMETER_MID_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.2251851830 | 0.3033954634 | Pass | Pass | 0.1896849926 | 0.3908115156 | Pass | Pass |
11 | PERIMETER_MID_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.3582582033 | 0.6418846323 | Pass | Pass | 0.2063556925 | 0.4133811284 | Pass | Pass |
12 | PERIMETER_MID_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.2102086379 | 0.3373911210 | Pass | Pass | 0.1884731353 | 0.3867751133 | Pass | Pass |
13 | PERIMETER_TOP_ZN_3 | RunPeriod: RUNPERIOD 1 | 0.1375886704 | 0.1953195362 | Pass | Pass | 0.1826229719 | 0.3846467110 | Pass | Pass |
14 | PERIMETER_TOP_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.2365969486 | 0.3050929154 | Pass | Pass | 0.1842712464 | 0.3874931440 | Pass | Pass |
15 | PERIMETER_TOP_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.3705304390 | 0.6176086858 | Pass | Pass | 0.1960856582 | 0.3958734221 | Pass | Pass |
16 | PERIMETER_TOP_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.2325815265 | 0.3500884369 | Pass | Pass | 0.1832603432 | 0.3833780550 | Pass | Pass |
17 | GROUNDFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 5.0919610625E-002 | 5.0505295255E-002 | Pass | Pass | 0.2632558860 | 0.4387943125 | Pass | Pass |
18 | MIDFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 3.2535220271E-002 | 3.7864460920E-002 | Pass | Pass | 0.2086594681 | 0.4001915515 | Pass | Pass |
19 | TOPFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 7.0757100243E-002 | 8.4660647314E-002 | Pass | Pass | 0.1838838298 | 0.3704668258 | Pass | Pass |
20 | DATACENTER_BOT_ZN_6 | RunPeriod: RUNPERIOD 1 | 8.1265816680E-006 | 8.7811847572E-006 | Pass | Pass | 3.5865833810E-003 | 4.8205113529E-003 | Pass | Pass |
21 | DATACENTER_MID_ZN_6 | RunPeriod: RUNPERIOD 1 | 6.8210858272E-006 | 7.5739913431E-006 | Pass | Pass | 5.5419992466E-003 | 6.5857858394E-003 | Pass | Pass |
22 | DATACENTER_TOP_ZN_6 | RunPeriod: RUNPERIOD 1 | 6.5387874192E-006 | 7.5257976150E-006 | Pass | Pass | 8.2882774477E-003 | 6.7994071709E-003 | Pass | Pass |
23 | DATACENTER_BASEMENT_ZN_6 | RunPeriod: RUNPERIOD 1 | 1.1663008641E-005 | 1.5380338973E-005 | Pass | Pass | 4.8629110036E-005 | 1.1255335449E-004 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 08:44:04
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 5735.58 | -59.6 | 0.00 | 655.37 | 37063.60 | 43394.97 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 08:44:04
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 4.60 | 0.00 | 4.60 | Wetbulb [C] | 2.50 | 10.00 |
TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 33.90 | 7.90 | 25.10 | Wetbulb [C] | 3.10 | 270.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 66.00 | 12 | |||
Feb | 66.00 | 22 | |||
Mar | 126.00 | 32 | |||
Apr | 206.00 | 19 | |||
May | 144.00 | 46 | |||
Jun | 99.00 | 30 | |||
Jul | 192.00 | 52 | |||
Aug | 240.00 | 34 | |||
Sep | 310.00 | 44 | |||
Oct | 34.00 | 10 | |||
Nov | 63.00 | 12 | |||
Dec | 35.00 | 24 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 08:44:04
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BASEMENT_WALL_EAST | BASEMENT_WALL_EAST_CFACTOR | 1.00 | 0.845 | 0.940 | 118.87 | 118.87 | 90.00 | 90.00 | E |
BASEMENT_WALL_SOUTH | BASEMENT_WALL_SOUTH_CFACTOR | 1.00 | 0.845 | 0.940 | 139.09 | 139.09 | 180.00 | 90.00 | S |
BASEMENT_WALL_NORTH | BASEMENT_WALL_NORTH_CFACTOR | 1.00 | 0.845 | 0.940 | 139.09 | 139.09 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_3_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 1.193 | 1.452 | 200.61 | 76.91 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_2_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 1.193 | 1.452 | 133.74 | 52.57 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 1.193 | 1.452 | 200.61 | 76.91 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_4_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 1.193 | 1.452 | 133.74 | 52.57 | 270.00 | 90.00 | W |
PERIMETER_MID_ZN_3_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 1.158 | 1.400 | 2006.06 | 847.11 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_2_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 1.158 | 1.400 | 1337.37 | 564.74 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 1.158 | 1.400 | 2006.06 | 847.11 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_4_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 1.158 | 1.400 | 1337.37 | 564.74 | 270.00 | 90.00 | W |
PERIMETER_TOP_ZN_3_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 1.331 | 1.662 | 200.61 | 84.71 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_2_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 1.331 | 1.662 | 133.74 | 56.47 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 1.331 | 1.662 | 200.61 | 84.71 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_4_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 1.331 | 1.662 | 133.74 | 56.47 | 270.00 | 90.00 | W |
GROUNDFLOOR_PLENUM_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 1.193 | 1.452 | 89.13 | 89.13 | 0.00 | 90.00 | N |
GROUNDFLOOR_PLENUM_WEST | NONRES_EXT_WALL_GRD | 0.30 | 1.193 | 1.452 | 59.42 | 59.42 | 270.00 | 90.00 | W |
GROUNDFLOOR_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 1.193 | 1.452 | 89.13 | 89.13 | 180.00 | 90.00 | S |
GROUNDFLOOR_PLENUM_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 1.193 | 1.452 | 59.42 | 59.42 | 90.00 | 90.00 | E |
MIDFLOOR_PLENUM_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 1.158 | 1.400 | 891.32 | 891.32 | 0.00 | 90.00 | N |
MIDFLOOR_PLENUM_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 1.158 | 1.400 | 594.21 | 594.21 | 270.00 | 90.00 | W |
MIDFLOOR_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 1.158 | 1.400 | 891.32 | 891.32 | 180.00 | 90.00 | S |
MIDFLOOR_PLENUM_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 1.158 | 1.400 | 594.21 | 594.21 | 90.00 | 90.00 | E |
TOPFLOOR_PLENUM_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 1.331 | 1.662 | 89.13 | 89.13 | 180.00 | 90.00 | S |
TOPFLOOR_PLENUM_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 1.331 | 1.662 | 59.42 | 59.42 | 90.00 | 90.00 | E |
TOPFLOOR_PLENUM_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 1.331 | 1.662 | 59.42 | 59.42 | 270.00 | 90.00 | W |
TOPFLOOR_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 1.331 | 1.662 | 89.13 | 89.13 | 0.00 | 90.00 | N |
BUILDING_ROOF | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 3563.11 | 3563.11 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_WALL_NORTH | DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR | 1.00 | 0.845 | 0.940 | 39.22 | 39.22 | 0.00 | 90.00 | N |
DATACENTER_BASEMENT_ZN_6_WALL_SOUTH | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR | 1.00 | 0.845 | 0.940 | 39.22 | 39.22 | 180.00 | 90.00 | S |
DATACENTER_BASEMENT_ZN_6_WALL_WEST | DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR | 1.00 | 0.845 | 0.940 | 118.87 | 118.87 | 270.00 | 90.00 | W |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BASEMENT_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 118.87 | 118.87 | 270.00 | 90.00 | W |
BASEMENT_FLOOR | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 2779.43 | 2779.43 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 225.00 | 0.00 | |
PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 250.34 | 250.34 | 180.00 | 0.00 | |
CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 2076.77 | 2076.77 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 250.34 | 250.34 | 180.00 | 0.00 | |
CORE_BOT_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
CORE_BOT_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
CORE_BOT_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 419.30 | 419.30 | 0.00 | 180.00 | |
CORE_BOT_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 2076.82 | 2076.82 | 0.00 | 180.00 | |
CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 180.00 | 0.00 | |
CORE_MID_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 180.00 | 90.00 | S |
CORE_MID_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 270.00 | 90.00 | W |
CORE_MID_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 0.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 90.00 | 90.00 | E |
CORE_MID_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 24961.20 | 24961.20 | 0.00 | 180.00 | |
CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 24961.20 | 24961.20 | 180.00 | 0.00 | |
CORE_TOP_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
CORE_TOP_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
CORE_TOP_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
CORE_TOP_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 2496.12 | 2496.12 | 0.00 | 180.00 | |
CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 250.34 | 250.34 | 0.00 | 180.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 63.07 | 63.07 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
PERIMETER_BOT_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 45.00 | 180.00 | |
PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 225.00 | 0.00 | |
PERIMETER_BOT_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 63.07 | 63.07 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 250.35 | 250.35 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
PERIMETER_BOT_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 315.00 | 180.00 | |
PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 135.00 | 0.00 | |
PERIMETER_MID_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 225.00 | 90.00 | W |
CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 135.00 | 90.00 | S |
DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 3134.13 | 3134.13 | 0.00 | 180.00 | |
PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.13 | 3134.13 | 180.00 | 0.00 | |
PERIMETER_MID_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 315.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 270.00 | 90.00 | W |
PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 225.00 | 90.00 | W |
PERIMETER_MID_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 2019.75 | 2019.75 | 45.00 | 180.00 | |
PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 225.00 | 0.00 | |
PERIMETER_MID_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 45.00 | 90.00 | E |
DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 315.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 3134.20 | 3134.20 | 0.00 | 180.00 | |
PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.20 | 3134.20 | 180.00 | 0.00 | |
PERIMETER_MID_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 135.00 | 90.00 | S |
DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 45.00 | 90.00 | E |
PERIMETER_MID_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 2019.75 | 2019.75 | 315.00 | 180.00 | |
PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 135.00 | 0.00 | |
PERIMETER_TOP_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 313.41 | 313.41 | 0.00 | 180.00 | |
PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 180.00 | 0.00 | |
PERIMETER_TOP_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
INT-PER3S-NE-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
PERIMETER_TOP_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 201.98 | 201.98 | 45.00 | 180.00 | |
PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 225.00 | 0.00 | |
INT-PER3S-NE | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 313.42 | 313.42 | 0.00 | 180.00 | |
PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 180.00 | 0.00 | |
PERIMETER_TOP_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
PERIMETER_TOP_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 201.98 | 201.98 | 315.00 | 180.00 | |
PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 135.00 | 0.00 | |
iz-CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 45.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 315.00 | 180.00 | |
iz-DATACENTER_BOT_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 0.00 | 180.00 | |
GROUNDFLOOR_PLENUM_CEILING | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 3563.11 | 3563.11 | 180.00 | 0.00 | |
iz-CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 24961.20 | 24961.20 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.13 | 3134.13 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 45.00 | 180.00 | |
iz-PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.20 | 3134.20 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 315.00 | 180.00 | |
iz-DATACENTER_MID_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 362.03 | 362.03 | 0.00 | 180.00 | |
MIDFLOOR_PLENUM_CEILING | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 35631.06 | 35631.06 | 180.00 | 0.00 | |
iz-CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 45.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 315.00 | 180.00 | |
iz-DATACENTER_TOP_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 0.00 | 180.00 | |
DATACENTER_BOT_ZN_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
DATACENTER_BOT_ZN_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
DATACENTER_BOT_ZN_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
DATACENTER_BOT_ZN_6_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 36.20 | 36.20 | 0.00 | 180.00 | |
DATACENTER_BOT_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 180.00 | 0.00 | |
DATACENTER_MID_ZN_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 270.00 | 90.00 | W |
DATACENTER_MID_ZN_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 180.00 | 90.00 | S |
DATACENTER_MID_ZN_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 90.00 | 90.00 | E |
DATACENTER_MID_ZN_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 0.00 | 90.00 | N |
DATACENTER_MID_ZN_6_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 362.03 | 362.03 | 0.00 | 180.00 | |
DATACENTER_MID_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 362.03 | 362.03 | 180.00 | 0.00 | |
DATACENTER_TOP_ZN_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
DATACENTER_TOP_ZN_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
DATACENTER_TOP_ZN_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
DATACENTER_TOP_ZN_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
DATACENTER_TOP_ZN_6_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 36.20 | 36.20 | 0.00 | 180.00 | |
DATACENTER_TOP_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 118.87 | 118.87 | 90.00 | 90.00 | E |
DATACENTER_BASEMENT_ZN_6_FLOOR | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 783.68 | 783.68 | 0.00 | 180.00 | |
DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 36.20 | 36.20 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 419.35 | 419.35 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 135.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 63.08 | 63.08 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 63.07 | 63.07 | 180.00 | 0.00 | |
BASEMENT_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 7126.21 | 0.00 | 90.00 | N | ||
CORE_BOTTOM_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 5064.65 | 0.00 | 90.00 | N | ||
CORE_MID_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 50646.53 | 0.00 | 90.00 | N | ||
CORE_TOP_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 5064.65 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.83 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.84 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 6268.26 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 4039.50 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 6268.35 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 4039.48 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.83 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.84 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | WINDOW_U_0.567_SHGC_NORTH_0.25 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 3.224 | 0.251 | 0.276 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | WINDOW_U_0.567_SHGC_NORTH_0.25 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 3.224 | 0.251 | 0.276 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | WINDOW_U_0.567_SHGC_NORTH_0.25 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 3.224 | 0.251 | 0.276 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | WINDOW_U_0.567_SHGC_NORTH_0.25 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 3.224 | 0.251 | 0.276 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | WINDOW_U_0.567_SHGC_NORTH_0.25 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 3.224 | 0.251 | 0.276 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | WINDOW_U_0.567_SHGC_EAST_0.25 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 3.224 | 0.251 | 0.276 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | WINDOW_U_0.567_SHGC_EAST_0.25 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 3.224 | 0.251 | 0.276 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | WINDOW_U_0.567_SHGC_EAST_0.25 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 3.224 | 0.251 | 0.276 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | WINDOW_U_0.567_SHGC_SOUTH_0.25 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 3.224 | 0.251 | 0.276 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | WINDOW_U_0.567_SHGC_SOUTH_0.25 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 3.224 | 0.251 | 0.276 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | WINDOW_U_0.567_SHGC_SOUTH_0.25 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 3.224 | 0.251 | 0.276 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | WINDOW_U_0.567_SHGC_SOUTH_0.25 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 3.224 | 0.251 | 0.276 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | WINDOW_U_0.567_SHGC_SOUTH_0.25 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 3.224 | 0.251 | 0.276 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | WINDOW_U_0.567_SHGC_WEST_0.25 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 3.224 | 0.251 | 0.276 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | WINDOW_U_0.567_SHGC_WEST_0.25 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 3.224 | 0.251 | 0.276 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | WINDOW_U_0.567_SHGC_WEST_0.25 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 3.224 | 0.251 | 0.276 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.567_SHGC_NORTH_0.25 | 115.90 | 0.00 | 0.00 | 115.90 | 1158.95 | 3.224 | 0.251 | 0.276 | No | PERIMETER_MID_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.567_SHGC_EAST_0.25 | 77.26 | 0.00 | 0.00 | 77.26 | 772.63 | 3.224 | 0.251 | 0.276 | No | PERIMETER_MID_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.567_SHGC_SOUTH_0.25 | 115.90 | 0.00 | 0.00 | 115.90 | 1158.95 | 3.224 | 0.251 | 0.276 | No | PERIMETER_MID_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.567_SHGC_WEST_0.25 | 77.26 | 0.00 | 0.00 | 77.26 | 772.63 | 3.224 | 0.251 | 0.276 | No | PERIMETER_MID_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.567_SHGC_NORTH_0.25 | 115.90 | 0.00 | 0.00 | 115.90 | 115.90 | 3.224 | 0.251 | 0.276 | No | PERIMETER_TOP_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.567_SHGC_EAST_0.25 | 77.26 | 0.00 | 0.00 | 77.26 | 77.26 | 3.224 | 0.251 | 0.276 | No | PERIMETER_TOP_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.567_SHGC_SOUTH_0.25 | 115.90 | 0.00 | 0.00 | 115.90 | 115.90 | 3.224 | 0.251 | 0.276 | No | PERIMETER_TOP_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.567_SHGC_WEST_0.25 | 77.26 | 0.00 | 0.00 | 77.26 | 77.26 | 3.224 | 0.251 | 0.276 | No | PERIMETER_TOP_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
Total or Average | 4635.80 | 3.224 | 0.251 | 0.276 | |||||||||||||||||
North Total or Average | 1390.74 | 3.224 | 0.251 | 0.276 | |||||||||||||||||
Non-North Total or Average | 3245.06 | 3.224 | 0.251 | 0.276 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | PERIMETER_BOT_ZN_2_WALL_EAST |
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | PERIMETER_BOT_ZN_2_WALL_EAST |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | PERIMETER_BOT_ZN_4_WALL_WEST |
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | PERIMETER_BOT_ZN_4_WALL_WEST |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 08:44:04
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 08:44:04
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
BASEMENT_LIGHTS | BASEMENT | BASEMENT | GENERAL | 10.2732 | 2779.43 | 28553.72 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 49.04 | 0.0000 | Y | 262.84 |
CORE_BOTTOM_LIGHTS | CORE_BOTTOM | CORE_BOTTOM | GENERAL | 10.2732 | 2496.12 | 25643.24 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 49.04 | 0.0000 | Y | 236.05 |
CORE_MID_LIGHTS | CORE_MID | CORE_MID | GENERAL | 10.2732 | 24961.20 | 256432.45 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 49.04 | 0.0000 | Y | 2360.52 |
CORE_TOP_LIGHTS | CORE_TOP | CORE_TOP | GENERAL | 10.2732 | 2496.12 | 25643.24 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 49.04 | 0.0000 | Y | 236.05 |
PERIMETER_BOT_ZN_3_LIGHTS | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3 | GENERAL | 10.2732 | 313.41 | 3219.77 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 28.61 | 0.0000 | Y | 17.29 |
PERIMETER_BOT_ZN_2_LIGHTS | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2 | GENERAL | 10.2732 | 201.98 | 2074.94 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 28.35 | 0.0000 | Y | 11.04 |
PERIMETER_BOT_ZN_1_LIGHTS | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1 | GENERAL | 10.2732 | 313.42 | 3219.84 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 28.07 | 0.0000 | Y | 16.97 |
PERIMETER_BOT_ZN_4_LIGHTS | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4 | GENERAL | 10.2732 | 201.98 | 2074.94 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 28.39 | 0.0000 | Y | 11.06 |
PERIMETER_MID_ZN_3_LIGHTS | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3 | GENERAL | 10.2732 | 3134.13 | 32197.65 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 28.53 | 0.0000 | Y | 172.43 |
PERIMETER_MID_ZN_2_LIGHTS | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2 | GENERAL | 10.2732 | 2019.75 | 20749.39 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 28.29 | 0.0000 | Y | 110.20 |
PERIMETER_MID_ZN_1_LIGHTS | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1 | GENERAL | 10.2732 | 3134.20 | 32198.36 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 28.03 | 0.0000 | Y | 169.41 |
PERIMETER_MID_ZN_4_LIGHTS | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4 | GENERAL | 10.2732 | 2019.75 | 20749.39 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 28.32 | 0.0000 | Y | 110.30 |
PERIMETER_TOP_ZN_3_LIGHTS | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3 | GENERAL | 10.2732 | 313.41 | 3219.77 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 28.52 | 0.0000 | Y | 17.24 |
PERIMETER_TOP_ZN_2_LIGHTS | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2 | GENERAL | 10.2732 | 201.98 | 2074.94 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 28.29 | 0.0000 | Y | 11.02 |
PERIMETER_TOP_ZN_1_LIGHTS | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1 | GENERAL | 10.2732 | 313.42 | 3219.84 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 28.03 | 0.0000 | Y | 16.94 |
PERIMETER_TOP_ZN_4_LIGHTS | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4 | GENERAL | 10.2732 | 201.98 | 2074.94 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 28.32 | 0.0000 | Y | 11.03 |
DATACENTER_BASEMENT_LIGHTS | DATACENTER_BASEMENT_ZN_6 | DATACENTER_BASEMENT_ZN_6 | GENERAL | 10.2732 | 783.68 | 8050.93 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 49.04 | 0.0000 | Y | 74.11 |
DATACENTER_BOT_LIGHTS | DATACENTER_BOT_ZN_6 | DATACENTER_BOT_ZN_6 | GENERAL | 17.8735 | 36.20 | 647.07 | LightsWired | LTG_SCH_DATACENTER | 56.02 | 168.00 | 54.57 | 0.0000 | Y | 6.63 |
DATACENTER_MID_LIGHTS | DATACENTER_MID_ZN_6 | DATACENTER_MID_ZN_6 | GENERAL | 17.8735 | 362.03 | 6470.68 | LightsWired | LTG_SCH_DATACENTER | 56.02 | 168.00 | 54.57 | 0.0000 | Y | 66.28 |
DATACENTER_TOP_LIGHTS | DATACENTER_TOP_ZN_6 | DATACENTER_TOP_ZN_6 | GENERAL | 17.8735 | 36.20 | 647.07 | LightsWired | LTG_SCH_DATACENTER | 56.02 | 168.00 | 54.57 | 0.0000 | Y | 6.63 |
Interior Lighting Total | 10.3445 | 46320.38 | 479162.15 | 1233.82 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
PERIMETER_BOT_ZN_1_DAYLREFPT1 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_DAYLCTRL | SplitFlux | Stepped | 0.39 | 3219.84 | 1241.89 |
PERIMETER_BOT_ZN_1_DAYLREFPT2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_DAYLCTRL | SplitFlux | Stepped | 0.14 | 3219.84 | 445.95 |
PERIMETER_BOT_ZN_2_DAYLREFPT1 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_DAYLCTRL | SplitFlux | Stepped | 0.39 | 2074.94 | 800.30 |
PERIMETER_BOT_ZN_2_DAYLREFPT2 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_DAYLCTRL | SplitFlux | Stepped | 0.14 | 2074.94 | 287.38 |
PERIMETER_BOT_ZN_3_DAYLREFPT1 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_DAYLCTRL | SplitFlux | Stepped | 0.39 | 3219.77 | 1241.86 |
PERIMETER_BOT_ZN_3_DAYLREFPT2 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_DAYLCTRL | SplitFlux | Stepped | 0.14 | 3219.77 | 445.94 |
PERIMETER_BOT_ZN_4_DAYLREFPT1 | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_DAYLCTRL | SplitFlux | Stepped | 0.39 | 2074.94 | 800.30 |
PERIMETER_BOT_ZN_4_DAYLREFPT2 | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_DAYLCTRL | SplitFlux | Stepped | 0.14 | 2074.94 | 287.38 |
PERIMETER_MID_ZN_1_DAYLREFPT1 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_DAYLCTRL | SplitFlux | Stepped | 0.39 | 3219.84 | 1241.89 |
PERIMETER_MID_ZN_1_DAYLREFPT2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_DAYLCTRL | SplitFlux | Stepped | 0.14 | 3219.84 | 445.95 |
PERIMETER_MID_ZN_2_DAYLREFPT1 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_DAYLCTRL | SplitFlux | Stepped | 0.39 | 2074.94 | 800.30 |
PERIMETER_MID_ZN_2_DAYLREFPT2 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_DAYLCTRL | SplitFlux | Stepped | 0.14 | 2074.94 | 287.38 |
PERIMETER_MID_ZN_3_DAYLREFPT1 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_DAYLCTRL | SplitFlux | Stepped | 0.39 | 3219.77 | 1241.86 |
PERIMETER_MID_ZN_3_DAYLREFPT2 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_DAYLCTRL | SplitFlux | Stepped | 0.14 | 3219.77 | 445.94 |
PERIMETER_MID_ZN_4_DAYLREFPT1 | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_DAYLCTRL | SplitFlux | Stepped | 0.39 | 2074.94 | 800.30 |
PERIMETER_MID_ZN_4_DAYLREFPT2 | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_DAYLCTRL | SplitFlux | Stepped | 0.14 | 2074.94 | 287.38 |
PERIMETER_TOP_ZN_1_DAYLREFPT1 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_DAYLCTRL | SplitFlux | Stepped | 0.39 | 3219.84 | 1241.89 |
PERIMETER_TOP_ZN_1_DAYLREFPT2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_DAYLCTRL | SplitFlux | Stepped | 0.14 | 3219.84 | 445.95 |
PERIMETER_TOP_ZN_2_DAYLREFPT1 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_DAYLCTRL | SplitFlux | Stepped | 0.39 | 2074.94 | 800.30 |
PERIMETER_TOP_ZN_2_DAYLREFPT2 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_DAYLCTRL | SplitFlux | Stepped | 0.14 | 2074.94 | 287.38 |
PERIMETER_TOP_ZN_3_DAYLREFPT1 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_DAYLCTRL | SplitFlux | Stepped | 0.39 | 3219.77 | 1241.86 |
PERIMETER_TOP_ZN_3_DAYLREFPT2 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_DAYLCTRL | SplitFlux | Stepped | 0.14 | 3219.77 | 445.94 |
PERIMETER_TOP_ZN_4_DAYLREFPT1 | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_DAYLCTRL | SplitFlux | Stepped | 0.39 | 2074.94 | 800.30 |
PERIMETER_TOP_ZN_4_DAYLREFPT2 | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_DAYLCTRL | SplitFlux | Stepped | 0.14 | 2074.94 | 287.38 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS_A | 13279.00 | AstronomicalClock | - | 41.73 | 41.73 | 104.01 | |
EXTERIOR_LIGHTS_B | 44301.60 | AstronomicalClock | - | 83.73 | 71.13 | 591.48 | |
Exterior Lighting Total | 57580.60 | 695.49 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 08:44:04
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
BYPASS HEAT EXCHANGER | HeatExchanger:FluidToFluid | 3176209.96 | |||||
HEATSYS1 BOILER | Boiler:HotWater | 1635117.89 | 0.81 | ||||
COOLSYS1 CHILLER1 | Chiller:Electric:ReformulatedEIR | 1616928.90 | 6.28 | 1547611.23 | 5.98 | 6.84 | 23.33 |
COOLSYS1 CHILLER2 | Chiller:Electric:ReformulatedEIR | 1616928.90 | 6.28 | 1547611.23 | 5.98 | 6.84 | 23.33 |
CENTRAL TOWER | FluidCooler:TwoSpeed | 582060.00 | |||||
CENTRAL BOILER | Boiler:HotWater | 543304.15 | 0.80 | ||||
TOWERWATERSYS COOLTOWER 1 | CoolingTower:VariableSpeed | 1918476.60 | |||||
TOWERWATERSYS COOLTOWER 2 | CoolingTower:VariableSpeed | 1918476.60 |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
VAV_BOT WITH REHEAT COOLING COIL | Coil:Cooling:Water | 259625.88 | 265210.15 | 179647.95 | 85562.20 | 0.68 | - | 27551.68 | 279.44 |
VAV_MID WITH REHEAT COOLING COIL | Coil:Cooling:Water | 2526201.21 | 2507859.18 | 1689787.34 | 818071.85 | 0.67 | - | 261478.59 | 2652.06 |
VAV_TOP WITH REHEAT COOLING COIL | Coil:Cooling:Water | 260981.37 | 267787.48 | 181529.86 | 86257.62 | 0.68 | - | 27818.70 | 282.15 |
CAV_BAS COOLING COIL | Coil:Cooling:Water | 136722.67 | 153520.17 | 106461.25 | 47058.92 | 0.69 | - | 15635.42 | 158.58 |
AIRLOOP DATACENTER BASEMENT COOLING COIL | Coil:Cooling:WaterToAirHeatPump:EquationFit | 436425.08 | 313849.50 | 122575.58 | 0.72 | 0.00 | |||
AIRLOOP DATACENTER BOT COOLING COIL | Coil:Cooling:WaterToAirHeatPump:EquationFit | 9781.48 | 7027.92 | 2753.56 | 0.72 | 0.00 | |||
AIRLOOP DATACENTER MID COOLING COIL | Coil:Cooling:WaterToAirHeatPump:EquationFit | 93413.42 | 67025.98 | 26387.44 | 0.72 | 0.00 | |||
AIRLOOP DATACENTER TOP COOLING COIL | Coil:Cooling:WaterToAirHeatPump:EquationFit | 9511.33 | 6826.93 | 2684.40 | 0.72 | 0.00 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
None |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
None |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Water | 19516.16 | 18505.12 | - |
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Water | 375050.02 | 355427.53 | - |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Water | 61918.87 | 58635.02 | - |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 6305.35 | 5973.20 | - |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 5143.55 | 4873.33 | - |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 8121.37 | 7690.54 | - |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 4330.32 | 4104.65 | - |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 158838.50 | 150499.81 | - |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 105821.15 | 100264.98 | - |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 157279.25 | 149022.76 | - |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 94912.24 | 89930.68 | - |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 20328.69 | 19260.50 | - |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 13426.57 | 12721.00 | - |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 20179.88 | 19119.53 | - |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 12594.20 | 11932.50 | - |
VAV_BOT WITH REHEAT HEATING COIL | Coil:Heating:Water | 27700.35 | 23609.83 | - |
VAV_MID WITH REHEAT HEATING COIL | Coil:Heating:Water | 233004.13 | 200518.93 | - |
VAV_TOP WITH REHEAT HEATING COIL | Coil:Heating:Water | 20857.58 | 18251.88 | - |
CAV_BAS HEATING COIL | Coil:Heating:Water | 289789.72 | 234647.64 | - |
AIRLOOP DATACENTER BASEMENT HEATING COIL | Coil:Heating:WaterToAirHeatPump:EquationFit | 436425.08 | 0.00 | |
AIRLOOP DATACENTER BOT HEATING COIL | Coil:Heating:WaterToAirHeatPump:EquationFit | 9781.48 | 0.00 | |
AIRLOOP DATACENTER MID HEATING COIL | Coil:Heating:WaterToAirHeatPump:EquationFit | 93413.42 | 0.00 | |
AIRLOOP DATACENTER TOP HEATING COIL | Coil:Heating:WaterToAirHeatPump:EquationFit | 9511.33 | 0.00 | |
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | Coil:Heating:Electric | 14482.89 | 1.00 | |
AIRLOOP DATACENTER BOT_SUPPHEATCOIL | Coil:Heating:Electric | 669.05 | 1.00 | |
AIRLOOP DATACENTER MID_SUPPHEATCOIL | Coil:Heating:Electric | 6690.49 | 1.00 | |
AIRLOOP DATACENTER TOP_SUPPHEATCOIL | Coil:Heating:Electric | 669.05 | 1.00 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
VAV_BOT WITH REHEAT FAN | Fan:VariableVolume | 0.61 | 1314.72 | 9.79 | 21154.37 | 2160.95 | 1.00 | 1.12 | General | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 |
VAV_MID WITH REHEAT FAN | Fan:VariableVolume | 0.61 | 1314.72 | 90.94 | 196506.41 | 2160.95 | 1.00 | 1.08 | General | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 |
VAV_TOP WITH REHEAT FAN | Fan:VariableVolume | 0.61 | 1314.72 | 9.91 | 21411.61 | 2160.95 | 1.00 | 1.12 | General | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:40:00 |
CAV_BAS FAN | Fan:ConstantVolume | 0.60 | 1018.41 | 6.13 | 10394.87 | 1695.65 | 1.00 | 1.15 | General | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
AIRLOOP DATACENTER BASEMENT SUPPLY FAN | Fan:OnOff | 0.61 | 1018.41 | 21.44 | 35544.49 | 1657.97 | 1.00 | 1.13 | General | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 07:10:00 |
AIRLOOP DATACENTER BOT SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.48 | 537.88 | 1120.11 | 1.00 | 1.62 | General | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
AIRLOOP DATACENTER MID SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 4.57 | 5123.59 | 1120.11 | 1.00 | 1.16 | General | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
AIRLOOP DATACENTER TOP SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.47 | 522.03 | 1120.11 | 1.00 | 1.64 | General | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
COOLSYS1 PUMP SECONDARY | Pump:VariableSpeed | Intermittent | 105797.75 | 0.135435 | 22112.36 | 163269.45 | 0.90 | General |
HEATSYS1 PUMP | Pump:VariableSpeed | Intermittent | 180705.70 | 0.014305 | 4307.95 | 301156.09 | 0.90 | General |
COOLSYS1 CHILLER1 PUMP | Pump:ConstantSpeed | Intermittent | 73247.35 | 0.067717 | 7654.57 | 113036.94 | 0.90 | General |
COOLSYS1 CHILLER2 PUMP | Pump:ConstantSpeed | Intermittent | 73247.35 | 0.067717 | 7654.57 | 113036.94 | 0.90 | General |
PLANT CIRC PUMP | Pump:ConstantSpeed | Intermittent | 179045.11 | 0.013448 | 3429.96 | 255050.01 | 0.90 | General |
SWHSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 29891.00 | 0.000440 | 56.21 | 127739.32 | 0.30 | General |
TOWERWATERSYS PUMP | HeaderedPumps:VariableSpeed | Intermittent | 148556.62 | 0.160032 | 39620.29 | 247577.87 | 0.90 | General |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 1.14 | 87921.32 | 0.80 | 0.48 | 0.06 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:44:04
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 85050.19 | 85050.19 | 30.60 | 6.130 | 6.130 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 24.00 | 24.00 | 0.00891 | 28.05 | 0.01653 | 1.200 | 0.00 |
CORE_BOTTOM | 85727.99 | 85727.99 | 34.34 | 6.178 | 6.178 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 24.00 | 24.00 | 0.00886 | 28.05 | 0.01653 | 1.078 | 0.00 |
CORE_MID | 805760.53 | 805760.53 | 322.81 | 58.053 | 58.053 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 24.00 | 24.00 | 0.00889 | 28.05 | 0.01653 | 10.778 | 0.00 |
CORE_TOP | 79564.59 | 79564.59 | 31.88 | 5.732 | 5.732 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 24.00 | 24.00 | 0.00889 | 28.05 | 0.01653 | 1.078 | 0.00 |
PERIMETER_BOT_ZN_3 | 14094.47 | 14094.47 | 44.97 | 1.025 | 1.025 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:40:00 | 24.00 | 24.00 | 0.00890 | 33.90 | 0.01654 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_2 | 15338.98 | 15338.98 | 75.94 | 1.115 | 1.115 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 09:40:00 | 24.00 | 24.00 | 0.00874 | 30.45 | 0.01653 | 0.087 | 0.00 |
PERIMETER_BOT_ZN_1 | 17418.45 | 17418.45 | 55.58 | 1.267 | 1.267 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:40:00 | 24.00 | 24.00 | 0.00882 | 33.77 | 0.01654 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_4 | 19203.66 | 19203.66 | 95.08 | 1.396 | 1.396 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 17:00:00 | 24.00 | 24.00 | 0.00869 | 32.79 | 0.01653 | 0.087 | 0.00 |
PERIMETER_MID_ZN_3 | 132227.67 | 132227.67 | 421.90 | 9.616 | 9.616 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | 24.00 | 24.00 | 0.00910 | 33.90 | 0.01654 | 1.353 | 0.00 |
PERIMETER_MID_ZN_2 | 157723.32 | 157723.32 | 780.90 | 11.470 | 11.470 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 09:50:00 | 24.00 | 24.00 | 0.00884 | 30.67 | 0.01653 | 0.872 | 0.00 |
PERIMETER_MID_ZN_1 | 166140.19 | 166140.19 | 530.09 | 12.082 | 12.082 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | 24.00 | 24.00 | 0.00898 | 33.83 | 0.01654 | 1.353 | 0.00 |
PERIMETER_MID_ZN_4 | 167431.65 | 167431.65 | 828.97 | 12.176 | 12.176 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 17:00:00 | 24.00 | 24.00 | 0.00882 | 32.79 | 0.01653 | 0.872 | 0.00 |
PERIMETER_TOP_ZN_3 | 14869.85 | 14869.85 | 47.44 | 1.081 | 1.081 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:10:00 | 24.00 | 24.00 | 0.00910 | 33.82 | 0.01654 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_2 | 15966.66 | 15966.66 | 79.05 | 1.161 | 1.161 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 10:00:00 | 24.00 | 24.00 | 0.00888 | 30.90 | 0.01653 | 0.087 | 0.00 |
PERIMETER_TOP_ZN_1 | 18146.72 | 18146.72 | 57.90 | 1.320 | 1.320 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | 24.00 | 24.00 | 0.00900 | 33.90 | 0.01654 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_4 | 17818.53 | 17818.53 | 88.22 | 1.296 | 1.296 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 17:00:00 | 24.00 | 24.00 | 0.00884 | 32.79 | 0.01653 | 0.087 | 0.00 |
DATACENTER_BOT_ZN_6 | 8372.67 | 8372.67 | 231.27 | 0.480 | 0.480 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 18:40:00 | 27.00 | 27.00 | 0.00859 | 31.21 | 0.01653 | 0.016 | 0.00 |
DATACENTER_MID_ZN_6 | 79753.76 | 79753.76 | 2202.98 | 4.574 | 4.574 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 18:40:00 | 27.00 | 27.00 | 0.00859 | 31.21 | 0.01653 | 0.156 | 0.00 |
DATACENTER_TOP_ZN_6 | 8125.91 | 8125.91 | 224.46 | 0.466 | 0.466 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 18:40:00 | 27.00 | 27.00 | 0.00859 | 31.21 | 0.01653 | 0.016 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 373799.24 | 373799.24 | 476.98 | 21.438 | 21.438 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 07:00:00 | 27.00 | 27.00 | 0.00854 | 26.71 | 0.01652 | 0.338 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.000 | 1.200 | 00:10:00 | 15.60 | 25.23 | 0.00526 | 4.60 | 0.00526 | 1.200 | 0.00 | |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.000 | 1.078 | 00:10:00 | 15.60 | 22.86 | 0.00526 | 4.60 | 0.00526 | 1.078 | 0.00 | |
CORE_MID | 184070.53 | 184070.53 | 73.74 | 7.714 | 10.778 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00800 | 4.60 | 0.00526 | 10.778 | 0.00 |
CORE_TOP | 42311.69 | 42311.69 | 16.95 | 1.794 | 1.794 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00800 | 4.60 | 0.00526 | 1.078 | 0.00 |
PERIMETER_BOT_ZN_3 | 3855.06 | 3855.06 | 12.30 | 0.163 | 0.163 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00722 | 4.60 | 0.00526 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_2 | 2902.37 | 2902.37 | 14.37 | 0.123 | 0.123 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00730 | 4.60 | 0.00526 | 0.087 | 0.00 |
PERIMETER_BOT_ZN_1 | 5575.65 | 5575.65 | 17.79 | 0.236 | 0.236 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00745 | 4.60 | 0.00526 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_4 | 1526.72 | 1526.72 | 7.56 | 0.064 | 0.087 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00685 | 4.60 | 0.00526 | 0.087 | 0.00 |
PERIMETER_MID_ZN_3 | 111212.05 | 111212.05 | 354.84 | 4.737 | 4.737 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00768 | 4.60 | 0.00526 | 1.353 | 0.00 |
PERIMETER_MID_ZN_2 | 74087.92 | 74087.92 | 366.82 | 3.156 | 3.156 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00769 | 4.60 | 0.00526 | 0.872 | 0.00 |
PERIMETER_MID_ZN_1 | 110122.15 | 110122.15 | 351.36 | 4.691 | 4.691 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00768 | 4.60 | 0.00526 | 1.353 | 0.00 |
PERIMETER_MID_ZN_4 | 66461.15 | 66461.15 | 329.06 | 2.830 | 2.830 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00762 | 4.60 | 0.00526 | 0.872 | 0.00 |
PERIMETER_TOP_ZN_3 | 14228.58 | 14228.58 | 45.40 | 0.607 | 0.607 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00777 | 4.60 | 0.00526 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_2 | 9397.36 | 9397.36 | 46.53 | 0.401 | 0.401 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00777 | 4.60 | 0.00526 | 0.087 | 0.00 |
PERIMETER_TOP_ZN_1 | 14124.55 | 14124.55 | 45.07 | 0.602 | 0.602 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00777 | 4.60 | 0.00526 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_4 | 8815.51 | 8815.51 | 43.65 | 0.376 | 0.376 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00774 | 4.60 | 0.00526 | 0.087 | 0.00 |
DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.016 | 00:10:00 | 18.00 | 27.00 | 0.00850 | 4.60 | 0.00526 | 0.016 | 0.00 | |
DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.156 | 00:10:00 | 18.00 | 24.85 | 0.00734 | 4.60 | 0.00526 | 0.156 | 0.00 | |
DATACENTER_TOP_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.016 | 00:10:00 | 18.00 | 23.98 | 0.00544 | 4.60 | 0.00526 | 0.016 | 0.00 | |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.338 | 00:10:00 | 18.00 | 27.00 | 0.00850 | 4.60 | 0.00526 | 0.338 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
VAV_BOT WITH REHEAT | 9.79 | 9.79 | 1.69 | 1.69 | 9.7894 | 2.9395 | 9.7894 | 0.3003 | 0.3000 |
VAV_MID WITH REHEAT | 90.94 | 90.94 | 26.19 | 26.19 | 90.9353 | 28.5136 | 90.9353 | 0.3136 | 0.3000 |
VAV_TOP WITH REHEAT | 9.91 | 9.91 | 3.78 | 3.78 | 9.9084 | 3.7791 | 9.9084 | 0.3814 | 0.3000 |
CAV_BAS | 6.13 | 6.13 | 1.20 | 1.20 | 6.1303 | 6.1303 | 6.1303 | 1.0000 | 1.0000 |
AIRLOOP DATACENTER BASEMENT | 21.44 | 21.44 | 0.34 | 0.34 | 21.4385 | 21.4384 | 21.4385 | 1.0000 | 1.0000 |
AIRLOOP DATACENTER BOT | 0.48 | 0.48 | 0.02 | 0.02 | 0.4802 | 0.4802 | 0.4802 | 1.0000 | 1.0000 |
AIRLOOP DATACENTER MID | 4.57 | 4.57 | 0.16 | 0.16 | 4.5742 | 4.5742 | 4.5742 | 1.0000 | 1.0000 |
AIRLOOP DATACENTER TOP | 0.47 | 0.47 | 0.02 | 0.02 | 0.4661 | 0.4661 | 0.4661 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | 19516.160 | 19516.160 | 1.939891 | 0.00017074 | 393.430 | 1/21 00:10:00 | 1/21 00:10:00 | 19516.16 | 19516.16 | 1.939891 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.17 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 0.0000 | 21.00 | 0.00800000 | 51.6744 | 0.00 | 0.00 | 19588.12 | 19588.12 | ||
CORE_MID VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | 375050.020 | 375050.020 | 18.983210 | 0.00328110 | 8359.980 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 375050.02 | 375050.02 | 18.983210 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.17 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 0.0000 | 21.00 | 0.00800000 | 51.6744 | 184070.53 | 0.00 | 376337.40 | 376337.40 |
CORE_TOP VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | 61918.869 | 61918.869 | 1.948938 | 0.00054169 | 1595.595 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 61918.87 | 61918.87 | 1.948938 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.17 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 0.0000 | 21.00 | 0.00800000 | 51.6744 | 42311.69 | 0.00 | 62109.05 | 62109.05 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | 6305.347 | 6305.347 | 0.243934 | 0.00005516 | 150.774 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 6305.35 | 6305.35 | 0.243934 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.17 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 0.0000 | 21.00 | 0.00722183 | 46.7087 | 3855.06 | 0.00 | 6325.83 | 6325.83 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | 5143.553 | 5143.553 | 0.223085 | 0.00004500 | 119.000 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 5143.55 | 5143.55 | 0.223085 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.17 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 0.0000 | 21.00 | 0.00730394 | 47.2337 | 2902.37 | 0.00 | 5160.56 | 5160.56 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | 8121.368 | 8121.368 | 0.253329 | 0.00007105 | 210.084 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 8121.37 | 8121.37 | 0.253329 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.17 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 0.0000 | 21.00 | 0.00745099 | 48.1733 | 5575.65 | 0.00 | 8146.27 | 8146.27 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | 4330.322 | 4330.322 | 0.279290 | 0.00003788 | 92.216 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 4330.32 | 4330.32 | 0.279290 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.17 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 0.0000 | 21.00 | 0.00684965 | 44.3272 | 1526.72 | 0.00 | 4345.57 | 4345.57 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | 158838.501 | 158838.501 | 4.737431 | 0.00138959 | 4190.717 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 158838.50 | 158838.50 | 4.737431 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.17 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 0.0000 | 21.00 | 0.00768069 | 49.6405 | 111212.05 | 0.00 | 159372.06 | 159372.06 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | 105821.153 | 105821.153 | 3.156453 | 0.00092577 | 2791.817 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 105821.15 | 105821.15 | 3.156453 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.17 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 0.0000 | 21.00 | 0.00769188 | 49.7118 | 74087.92 | 0.00 | 106175.78 | 106175.78 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | 157279.245 | 157279.245 | 4.690795 | 0.00137595 | 4149.631 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 157279.25 | 157279.25 | 4.690795 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.17 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 0.0000 | 21.00 | 0.00767530 | 49.6061 | 110122.15 | 0.00 | 157807.95 | 157807.95 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | 94912.240 | 94912.240 | 2.830383 | 0.00083033 | 2504.288 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 94912.24 | 94912.24 | 2.830383 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.17 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 0.0000 | 21.00 | 0.00762372 | 49.2771 | 66461.15 | 0.00 | 95232.28 | 95232.28 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | 20328.694 | 20328.694 | 0.606672 | 0.00017784 | 536.197 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 20328.69 | 20328.69 | 0.606672 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.17 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 0.0000 | 21.00 | 0.00776874 | 50.2020 | 14228.58 | 0.00 | 20395.93 | 20395.93 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | 13426.567 | 13426.567 | 0.400713 | 0.00011746 | 354.135 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 13426.57 | 13426.57 | 0.400713 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.17 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 0.0000 | 21.00 | 0.00777074 | 50.2148 | 9397.36 | 0.00 | 13470.91 | 13470.91 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | 20179.875 | 20179.875 | 0.602221 | 0.00017654 | 532.276 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 20179.88 | 20179.88 | 0.602221 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.17 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 0.0000 | 21.00 | 0.00776598 | 50.1843 | 14124.55 | 0.00 | 20246.65 | 20246.65 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | 12594.199 | 12594.199 | 0.375823 | 0.00011018 | 332.200 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 12594.20 | 12594.20 | 0.375823 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.17 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 0.0000 | 21.00 | 0.00774089 | 50.0245 | 8815.51 | 0.00 | 12635.94 | 12635.94 |
VAV_BOT WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | VAV_BOT WITH REHEAT | 259625.883 | -999.000 | 9.789399 | 0.01104509 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 259625.88 | 185446.15 | 9.789399 | 26.63 | 19.22 | 0.01090787 | 11.05 | 11.05 | 0.00850000 | 33.90 | 0.01653638 | 25.13 | 25.9279 | 24.00 | 0.00887272 | 47.6988 | 131439.45 | 0.00 | 260005.31 | 180512.91 |
VAV_BOT WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoopHVAC | VAV_BOT WITH REHEAT | 27700.354 | 27700.354 | 2.936820 | 0.00024233 | 480.060 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 27700.35 | 27700.35 | 2.936820 | 5.00 | 4.93 | 0.00535603 | 12.80 | 11.59 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 86.4265 | 21.90 | 0.00627275 | 38.4508 | 13859.81 | 0.00 | 28582.13 | 28582.13 |
VAV_MID WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | VAV_MID WITH REHEAT | 2526201.213 | -999.000 | 90.935332 | 0.10747044 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 2526201.21 | 1753209.07 | 90.935332 | 26.91 | 19.54 | 0.01120382 | 11.05 | 11.05 | 0.00850000 | 33.90 | 0.01653638 | 25.13 | 27.9121 | 24.00 | 0.00897892 | 48.2626 | 1185607.13 | 0.00 | 2530081.77 | 1712767.83 |
VAV_MID WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoopHVAC | VAV_MID WITH REHEAT | 233004.131 | 233004.131 | 27.280600 | 0.00203842 | 4058.742 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:10:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 233004.13 | 233004.13 | 27.280600 | 5.74 | 5.41 | 0.00543623 | 12.80 | 11.59 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 93.0403 | 21.00 | 0.00779405 | 50.3628 | 486659.98 | 0.00 | 242752.06 | 242752.06 |
VAV_TOP WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | VAV_TOP WITH REHEAT | 260981.375 | -999.000 | 9.908440 | 0.01110275 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:10:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:40:00 | 260981.37 | 186387.42 | 9.908440 | 26.52 | 19.18 | 0.01089199 | 11.05 | 11.05 | 0.00850000 | 33.82 | 0.01653623 | 25.11 | 25.6164 | 24.00 | 0.00894238 | 48.0692 | 135951.98 | 0.00 | 261360.73 | 181382.77 |
VAV_TOP WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoopHVAC | VAV_TOP WITH REHEAT | 20857.576 | 20857.576 | 2.972532 | 0.00018247 | 366.580 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:20:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 20857.58 | 20857.58 | 2.972532 | 7.00 | 6.30 | 0.00563643 | 12.80 | 11.59 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 85.3881 | 21.00 | 0.00785284 | 50.7371 | 59138.36 | 0.00 | 22096.61 | 22096.61 |
CAV_BAS COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | CAV_BAS | 136722.670 | -999.000 | 6.130299 | 0.00581650 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 136722.67 | 100697.33 | 6.130299 | 24.84 | 18.24 | 0.01040047 | 11.42 | 11.42 | 0.00850000 | 28.05 | 0.01652538 | 23.59 | 19.5775 | 24.00 | 0.00890947 | 47.8933 | 85050.19 | 0.00 | 136940.30 | 97736.29 |
CAV_BAS HEATING COIL | Coil:Heating:Water | AirLoopHVAC | CAV_BAS | 289789.718 | 289789.718 | 6.130299 | 0.00253521 | 6568.000 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 289789.72 | 289789.72 | 6.130299 | 0.90 | 0.90 | 0.00525715 | 40.00 | 21.17 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 19.5775 | 25.23 | 0.00525715 | 26.4073 | 0.00 | 0.00 | 248244.56 | 248244.56 |
AIRLOOP DATACENTER BASEMENT COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | 436425.080 | 313849.499 | 21.438522 | 0.01068802 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 07:10:00 | 408893.31 | 398959.36 | -999.0 | 28.51 | 18.07 | 0.00866839 | 12.80 | 12.09 | 0.00850000 | 33.90 | 0.01653638 | 25.13 | -999.0000 | 27.00 | 0.00854205 | 38.4495 | 373297.50 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BOT COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER BOT | 9781.483 | 7027.923 | 0.480202 | 0.00023955 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 18:40:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 18:40:00 | 9164.65 | 8708.94 | -999.0 | 28.08 | 18.07 | 0.00884508 | 12.80 | 12.09 | 0.00850000 | 31.21 | 0.01653132 | 24.43 | -999.0000 | 27.00 | 0.00858645 | 38.6443 | 8372.67 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER MID COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER MID | 93413.422 | 67025.978 | 4.574191 | 0.00228769 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 18:40:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 18:40:00 | 87560.57 | 83004.98 | -999.0 | 28.09 | 18.09 | 0.00886209 | 12.80 | 12.09 | 0.00850000 | 31.21 | 0.01653132 | 24.43 | -999.0000 | 27.00 | 0.00859072 | 38.6635 | 79753.76 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER TOP COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER TOP | 9511.329 | 6826.928 | 0.466051 | 0.00023293 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 18:30:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 18:40:00 | 8914.44 | 8458.74 | -999.0 | 28.09 | 18.08 | 0.00885551 | 12.80 | 12.09 | 0.00850000 | 31.41 | 0.01653169 | 24.48 | -999.0000 | 27.00 | 0.00858901 | 38.6558 | 8123.55 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BASEMENT HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | 436425.080 | 436425.080 | 21.438522 | 0.01068802 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 436425.08 | 436425.08 | 21.438522 | 4.60 | 4.60 | 0.00525715 | 40.00 | 21.17 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 1.5784 | 27.00 | 0.00850000 | 38.2570 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BOT HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER BOT | 9781.483 | 9781.483 | 0.480202 | 0.00023955 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 9781.48 | 9781.48 | 0.480202 | 4.60 | 4.60 | 0.00525715 | 40.00 | 21.17 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 3.2554 | 27.00 | 0.00850000 | 38.2570 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER MID HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER MID | 93413.422 | 93413.422 | 4.574191 | 0.00228769 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 93413.42 | 93413.42 | 4.574191 | 4.60 | 4.60 | 0.00525715 | 40.00 | 21.17 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 3.4175 | 24.85 | 0.00733798 | 37.5784 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER TOP HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER TOP | 9511.329 | 9511.329 | 0.466051 | 0.00023293 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 9511.33 | 9511.33 | 0.466051 | 4.60 | 4.60 | 0.00525715 | 40.00 | 21.17 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 3.3542 | 23.98 | 0.00543800 | 29.4351 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | 14482.888 | 14482.888 | -999.0 | -999.0 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 14482.89 | 14482.89 | 21.438522 | 0.07 | 0.07 | 0.00844881 | 40.00 | 21.17 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 1.5784 | 27.00 | 0.00850000 | 38.2570 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BOT_SUPPHEATCOIL | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER BOT | 669.049 | 669.049 | -999.0 | -999.0 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 669.05 | 669.05 | 0.480202 | 0.15 | 0.15 | 0.00839443 | 40.00 | 21.17 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 3.2554 | 27.00 | 0.00850000 | 38.2570 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER MID_SUPPHEATCOIL | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER MID | 6690.494 | 6690.494 | -999.0 | -999.0 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 6690.49 | 6690.49 | 4.574191 | 0.16 | 0.16 | 0.00726686 | 40.00 | 21.17 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 3.4175 | 24.85 | 0.00733798 | 37.5784 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER TOP_SUPPHEATCOIL | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER TOP | 669.049 | 669.049 | -999.0 | -999.0 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 669.05 | 669.05 | 0.466051 | 0.15 | 0.15 | 0.00543194 | 40.00 | 21.17 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 3.3542 | 23.98 | 0.00543800 | 29.4351 | 0.00 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 08:44:04
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
CORE_BOTTOM VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | CORE_BOTTOM | N/A | N/A | N/A | Yes | Yes | Yes | No | 19516.160 | 19516.160 | 1.939891 | 0.00017074 | 393.430 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2032 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 14.30326541 | 54.44 | 82.22 | 27.78 | 1668025.29 | 1.1700 | 1.193563 | 1/21 00:10:00 | unknown | unknown | 1/21 00:10:00 | Sensible | 19516.16 | 19516.16 | 1.0000 | 2.33401235 | 1.939891 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.17 | 0.00800000 | 60796.0 | 0.17071846 | 60.00 | 32.22 | 27.78 | 0.000 | 19516.16 | 4.60 | 0.00525715 | 4.60 | 0.00000000 | 0.0000 | 21.00 | 0.00800000 | 21.00 | 0.00800000 | 51.6744 | 0.00 | 0.00 | 19588.12 | 19588.12 | 2.33401235 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 21.03 | 14.86 | 0.00800000 | 41452.3 | |||
CORE_MID VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | CORE_MID | N/A | N/A | N/A | Yes | Yes | Yes | No | 375050.020 | 375050.020 | 18.983210 | 0.00328110 | 8359.980 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2032 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 14.30326541 | 54.44 | 82.22 | 27.78 | 1668025.29 | 22.4847 | 22.937185 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 375050.02 | 375050.02 | 1.0000 | 22.83996978 | 18.983210 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.17 | 0.00800000 | 60796.0 | 3.28076648 | 60.00 | 32.22 | 27.78 | 0.000 | 375050.02 | 4.60 | 0.00525715 | 4.60 | 0.00000000 | 0.0000 | 20.57 | 0.00800000 | 21.00 | 0.00800000 | 51.6744 | 184070.53 | 0.00 | 376337.40 | 376337.40 | 22.83996978 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 28.96 | 17.69 | 0.00800000 | 49537.0 | |
CORE_TOP VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | CORE_TOP | N/A | N/A | N/A | Yes | Yes | Yes | No | 61918.869 | 61918.869 | 1.948938 | 0.00054169 | 1595.595 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2032 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 14.30326541 | 54.44 | 82.22 | 27.78 | 1668025.29 | 3.7121 | 3.786814 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 61918.87 | 61918.87 | 1.0000 | 2.34489728 | 1.948938 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.17 | 0.00800000 | 60796.0 | 0.54163802 | 60.00 | 32.22 | 27.78 | 0.000 | 61918.87 | 4.60 | 0.00525715 | 4.60 | 0.00000000 | 0.0000 | 20.86 | 0.00800000 | 21.00 | 0.00800000 | 51.6744 | 42311.69 | 0.00 | 62109.05 | 62109.05 | 2.34489728 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 38.77 | 20.82 | 0.00800000 | 59546.7 | |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | PERIMETER_BOT_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 6305.347 | 6305.347 | 0.243934 | 0.00005516 | 150.774 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2032 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 14.30326541 | 54.44 | 82.22 | 27.78 | 1668025.29 | 0.3780 | 0.385620 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 6305.35 | 6305.35 | 1.0000 | 0.29349312 | 0.243934 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.17 | 0.00800000 | 60796.0 | 0.05515630 | 60.00 | 32.22 | 27.78 | 0.000 | 6305.35 | 4.60 | 0.00525715 | 4.60 | 0.00000000 | 0.0000 | 20.87 | 0.00722183 | 21.00 | 0.00722183 | 46.7087 | 3855.06 | 0.00 | 6325.83 | 6325.83 | 0.29349312 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 33.94 | 19.32 | 0.00800000 | 54613.4 | |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | PERIMETER_BOT_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 5143.553 | 5143.553 | 0.223085 | 0.00004500 | 119.000 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2032 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 14.30326541 | 54.44 | 82.22 | 27.78 | 1668025.29 | 0.3084 | 0.314568 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 5143.55 | 5143.55 | 1.0000 | 0.26840815 | 0.223085 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.17 | 0.00800000 | 60796.0 | 0.04499346 | 60.00 | 32.22 | 27.78 | 0.000 | 5143.55 | 4.60 | 0.00525715 | 4.60 | 0.00000000 | 0.0000 | 20.87 | 0.00730394 | 21.00 | 0.00730394 | 47.2337 | 2902.37 | 0.00 | 5160.56 | 5160.56 | 0.26840815 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 31.65 | 18.58 | 0.00800000 | 52286.4 | |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | PERIMETER_BOT_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 8121.368 | 8121.368 | 0.253329 | 0.00007105 | 210.084 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2032 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 14.30326541 | 54.44 | 82.22 | 27.78 | 1668025.29 | 0.4869 | 0.496684 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 8121.37 | 8121.37 | 1.0000 | 0.30479684 | 0.253329 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.17 | 0.00800000 | 60796.0 | 0.07104202 | 60.00 | 32.22 | 27.78 | 0.000 | 8121.37 | 4.60 | 0.00525715 | 4.60 | 0.00000000 | 0.0000 | 20.86 | 0.00745099 | 21.00 | 0.00745099 | 48.1733 | 5575.65 | 0.00 | 8146.27 | 8146.27 | 0.30479684 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 39.01 | 20.89 | 0.00800000 | 59786.7 | |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | PERIMETER_BOT_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 4330.322 | 4330.322 | 0.279290 | 0.00003788 | 92.216 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2032 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 14.30326541 | 54.44 | 82.22 | 27.78 | 1668025.29 | 0.2596 | 0.264832 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 4330.32 | 4330.32 | 1.0000 | 0.33603247 | 0.279290 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.17 | 0.00800000 | 60796.0 | 0.03787968 | 60.00 | 32.22 | 27.78 | 0.000 | 4330.32 | 4.60 | 0.00525715 | 4.60 | 0.00000000 | 0.0000 | 20.86 | 0.00684965 | 21.00 | 0.00684965 | 44.3272 | 1526.72 | 0.00 | 4345.57 | 4345.57 | 0.33603247 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 25.48 | 16.48 | 0.00800000 | 45991.8 | |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | PERIMETER_MID_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 158838.501 | 158838.501 | 4.737431 | 0.00138959 | 4190.717 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2032 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 14.30326541 | 54.44 | 82.22 | 27.78 | 1668025.29 | 9.5225 | 9.714193 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 158838.50 | 158838.50 | 1.0000 | 5.69992006 | 4.737431 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.17 | 0.00800000 | 60796.0 | 1.38944675 | 60.00 | 32.22 | 27.78 | 0.000 | 158838.50 | 4.60 | 0.00525715 | 4.60 | 0.00000000 | 0.0000 | 20.95 | 0.00768069 | 21.00 | 0.00768069 | 49.6405 | 111212.05 | 0.00 | 159372.06 | 159372.06 | 5.69992006 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.22 | 21.25 | 0.00800000 | 61020.2 | |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | PERIMETER_MID_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 105821.153 | 105821.153 | 3.156453 | 0.00092577 | 2791.817 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2032 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 14.30326541 | 54.44 | 82.22 | 27.78 | 1668025.29 | 6.3441 | 6.471775 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 105821.15 | 105821.15 | 1.0000 | 3.79773916 | 3.156453 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.17 | 0.00800000 | 60796.0 | 0.92567518 | 60.00 | 32.22 | 27.78 | 0.000 | 105821.15 | 4.60 | 0.00525715 | 4.60 | 0.00000000 | 0.0000 | 20.95 | 0.00769188 | 21.00 | 0.00769188 | 49.7118 | 74087.92 | 0.00 | 106175.78 | 106175.78 | 3.79773916 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.22 | 21.25 | 0.00800000 | 61017.5 | |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | PERIMETER_MID_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 157279.245 | 157279.245 | 4.690795 | 0.00137595 | 4149.631 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2032 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 14.30326541 | 54.44 | 82.22 | 27.78 | 1668025.29 | 9.4291 | 9.618832 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 157279.25 | 157279.25 | 1.0000 | 5.64380939 | 4.690795 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.17 | 0.00800000 | 60796.0 | 1.37580709 | 60.00 | 32.22 | 27.78 | 0.000 | 157279.25 | 4.60 | 0.00525715 | 4.60 | 0.00000000 | 0.0000 | 20.95 | 0.00767530 | 21.00 | 0.00767530 | 49.6061 | 110122.15 | 0.00 | 157807.95 | 157807.95 | 5.64380939 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.22 | 21.25 | 0.00800000 | 61021.1 | |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | PERIMETER_MID_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 94912.240 | 94912.240 | 2.830383 | 0.00083033 | 2504.288 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2032 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 14.30326541 | 54.44 | 82.22 | 27.78 | 1668025.29 | 5.6901 | 5.804611 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 94912.24 | 94912.24 | 1.0000 | 3.40542263 | 2.830383 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.17 | 0.00800000 | 60796.0 | 0.83024898 | 60.00 | 32.22 | 27.78 | 0.000 | 94912.24 | 4.60 | 0.00525715 | 4.60 | 0.00000000 | 0.0000 | 20.91 | 0.00762372 | 21.00 | 0.00762372 | 49.2771 | 66461.15 | 0.00 | 95232.28 | 95232.28 | 3.40542263 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.22 | 21.25 | 0.00800000 | 61024.7 | |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | PERIMETER_TOP_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 20328.694 | 20328.694 | 0.606672 | 0.00017784 | 536.197 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2032 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 14.30326541 | 54.44 | 82.22 | 27.78 | 1668025.29 | 1.2187 | 1.243256 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 20328.69 | 20328.69 | 1.0000 | 0.72992762 | 0.606672 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.17 | 0.00800000 | 60796.0 | 0.17782614 | 60.00 | 32.22 | 27.78 | 0.000 | 20328.69 | 4.60 | 0.00525715 | 4.60 | 0.00000000 | 0.0000 | 20.95 | 0.00776874 | 21.00 | 0.00776874 | 50.2020 | 14228.58 | 0.00 | 20395.93 | 20395.93 | 0.72992762 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.20 | 21.24 | 0.00800000 | 61002.2 | |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | PERIMETER_TOP_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 13426.567 | 13426.567 | 0.400713 | 0.00011746 | 354.135 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2032 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 14.30326541 | 54.44 | 82.22 | 27.78 | 1668025.29 | 0.8049 | 0.821138 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 13426.57 | 13426.57 | 1.0000 | 0.48212499 | 0.400713 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.17 | 0.00800000 | 60796.0 | 0.11744949 | 60.00 | 32.22 | 27.78 | 0.000 | 13426.57 | 4.60 | 0.00525715 | 4.60 | 0.00000000 | 0.0000 | 20.95 | 0.00777074 | 21.00 | 0.00777074 | 50.2148 | 9397.36 | 0.00 | 13470.91 | 13470.91 | 0.48212499 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.20 | 21.24 | 0.00800000 | 61000.5 | |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | PERIMETER_TOP_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 20179.875 | 20179.875 | 0.602221 | 0.00017654 | 532.276 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2032 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 14.30326541 | 54.44 | 82.22 | 27.78 | 1668025.29 | 1.2098 | 1.234154 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 20179.88 | 20179.88 | 1.0000 | 0.72457191 | 0.602221 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.17 | 0.00800000 | 60796.0 | 0.17652434 | 60.00 | 32.22 | 27.78 | 0.000 | 20179.88 | 4.60 | 0.00525715 | 4.60 | 0.00000000 | 0.0000 | 20.95 | 0.00776598 | 21.00 | 0.00776598 | 50.1843 | 14124.55 | 0.00 | 20246.65 | 20246.65 | 0.72457191 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.20 | 21.24 | 0.00800000 | 61002.7 | |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | PERIMETER_TOP_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 12594.199 | 12594.199 | 0.375823 | 0.00011018 | 332.200 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2032 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 14.30326541 | 54.44 | 82.22 | 27.78 | 1668025.29 | 0.7550 | 0.770232 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 12594.20 | 12594.20 | 1.0000 | 0.45217820 | 0.375823 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.17 | 0.00800000 | 60796.0 | 0.11016831 | 60.00 | 32.22 | 27.78 | 0.000 | 12594.20 | 4.60 | 0.00525715 | 4.60 | 0.00000000 | 0.0000 | 20.95 | 0.00774089 | 21.00 | 0.00774089 | 50.0245 | 8815.51 | 0.00 | 12635.94 | 12635.94 | 0.45217820 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.20 | 21.24 | 0.00800000 | 61004.4 | |
VAV_BOT WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV_BOT WITH REHEAT | CORE_BOTTOM; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 259625.883 | -999.000 | 9.789399 | 0.01104509 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1025.1172 | 1004.8586 | 1.2032 | VAV_BOT WITH REHEAT FAN | Fan:VariableVolume | 9.789399 | 11.77828094 | 4197.9300 | 999.8980 | 135.42095840 | 12.27 | 6.67 | 5.60 | 3183531.14 | 8.1553 | 8.155280 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | Sensible | 259625.88 | 185446.15 | 1.0000 | 11.77828094 | 9.789399 | 26.63 | 19.22 | 0.01090787 | 54576.8 | 11.05 | 11.05 | 0.00850000 | 32534.0 | 11.04395854 | 6.67 | 12.27 | 5.60 | 21154.370 | 238471.51 | 33.90 | 0.01653638 | 25.13 | 2.53819000 | 25.9279 | 24.00 | 0.00887272 | 24.00 | 0.00887272 | 47.6988 | 131439.45 | 0.00 | 260005.31 | 180512.91 | 11.77828094 | 26.63 | 19.23 | 0.01090787 | 54576.8 | 11.68 | 11.36 | 0.00823248 | 32501.8 | |
VAV_BOT WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV_BOT WITH REHEAT | CORE_BOTTOM; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 27700.354 | 27700.354 | 2.936820 | 0.00024233 | 480.060 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2032 | VAV_BOT WITH REHEAT FAN | Fan:VariableVolume | 9.789399 | 11.77828094 | 4197.9300 | 999.8980 | 14.30326541 | 54.44 | 82.22 | 27.78 | 1668025.29 | 1.6607 | 1.694089 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 27700.35 | 27700.35 | 1.0000 | 3.53348428 | 2.936820 | 5.00 | 4.93 | 0.00535603 | 18467.6 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 0.24231006 | 60.00 | 32.22 | 27.78 | 0.000 | 27700.35 | 4.60 | 0.00525715 | 4.60 | 2.53819000 | 86.4265 | 7.54 | 0.00598564 | 21.90 | 0.00627275 | 38.4508 | 13859.81 | 0.00 | 28582.13 | 28582.13 | 3.53348428 | 2.80 | 2.80 | 0.00535603 | 16236.5 | 10.77 | 7.81 | 0.00535603 | 24325.5 | |
VAV_MID WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV_MID WITH REHEAT | CORE_MID; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 2526201.213 | -999.000 | 90.935332 | 0.10747044 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1025.6673 | 1004.8586 | 1.2032 | VAV_MID WITH REHEAT FAN | Fan:VariableVolume | 90.935332 | 109.41038170 | 4197.9300 | 999.8980 | 135.42095840 | 12.27 | 6.67 | 5.60 | 3183531.14 | 79.3522 | 79.352175 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | Sensible | 2526201.21 | 1753209.07 | 1.0000 | 109.41038170 | 90.935332 | 26.91 | 19.54 | 0.01120382 | 55624.2 | 11.05 | 11.05 | 0.00850000 | 32534.9 | 107.45947634 | 6.67 | 12.27 | 5.60 | 196506.411 | 2329694.80 | 33.90 | 0.01653638 | 25.13 | 25.38195000 | 27.9121 | 24.00 | 0.00897892 | 24.00 | 0.00897892 | 48.2626 | 1185607.13 | 0.00 | 2530081.77 | 1712767.83 | 109.41038170 | 26.91 | 19.55 | 0.01120382 | 55624.2 | 11.65 | 11.36 | 0.00824252 | 32499.5 | |
VAV_MID WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV_MID WITH REHEAT | CORE_MID; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 233004.131 | 233004.131 | 27.280600 | 0.00203842 | 4058.742 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2032 | VAV_MID WITH REHEAT FAN | Fan:VariableVolume | 90.935332 | 109.41038170 | 4197.9300 | 999.8980 | 14.30326541 | 54.44 | 82.22 | 27.78 | 1668025.29 | 13.9689 | 14.249990 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:10:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 233004.13 | 233004.13 | 1.0000 | 32.82311451 | 27.280600 | 5.74 | 5.41 | 0.00543623 | 19417.0 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 2.03821384 | 60.00 | 32.22 | 27.78 | 0.000 | 233004.13 | 4.60 | 0.00525715 | 4.60 | 25.38195000 | 93.0403 | 20.92 | 0.00783030 | 21.00 | 0.00779405 | 50.3628 | 486659.98 | 0.00 | 242752.06 | 242752.06 | 32.82311451 | 2.80 | 2.80 | 0.00543623 | 16437.5 | 10.09 | 7.58 | 0.00543623 | 23833.3 | |
VAV_TOP WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV_TOP WITH REHEAT | CORE_TOP; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 260981.375 | -999.000 | 9.908440 | 0.01110275 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1025.0877 | 1004.8586 | 1.2032 | VAV_TOP WITH REHEAT FAN | Fan:VariableVolume | 9.908440 | 11.92150699 | 4197.9300 | 999.8980 | 135.42095840 | 12.27 | 6.67 | 5.60 | 3183531.14 | 8.1979 | 8.197858 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:10:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:10:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:40:00 | Sensible | 260981.37 | 186387.42 | 1.0000 | 11.92150699 | 9.908440 | 26.52 | 19.18 | 0.01089199 | 54425.6 | 11.05 | 11.05 | 0.00850000 | 32533.9 | 11.10161840 | 6.67 | 12.27 | 5.60 | 21411.611 | 239569.76 | 33.82 | 0.01653623 | 25.11 | 2.53819000 | 25.6164 | 24.00 | 0.00894238 | 24.00 | 0.00894238 | 48.0692 | 135951.98 | 0.00 | 261360.73 | 181382.77 | 11.92150699 | 26.52 | 19.19 | 0.01089199 | 54425.6 | 11.68 | 11.36 | 0.00823260 | 32502.1 | |
VAV_TOP WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV_TOP WITH REHEAT | CORE_TOP; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 20857.576 | 20857.576 | 2.972532 | 0.00018247 | 366.580 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2032 | VAV_TOP WITH REHEAT FAN | Fan:VariableVolume | 9.908440 | 11.92150699 | 4197.9300 | 999.8980 | 14.30326541 | 54.44 | 82.22 | 27.78 | 1668025.29 | 1.2504 | 1.275601 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:20:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 20857.58 | 20857.58 | 1.0000 | 3.57645210 | 2.972532 | 7.00 | 6.30 | 0.00563643 | 21199.8 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 0.18245256 | 60.00 | 32.22 | 27.78 | 0.000 | 20857.58 | 4.60 | 0.00525715 | 4.60 | 2.53819000 | 85.3881 | 21.00 | 0.00785284 | 21.00 | 0.00785284 | 50.7371 | 59138.36 | 0.00 | 22096.61 | 22096.61 | 3.57645210 | 2.80 | 2.80 | 0.00563643 | 16939.3 | 8.89 | 7.23 | 0.00563643 | 23117.6 | |
CAV_BAS COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | CAV_BAS | BASEMENT | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 136722.670 | -999.000 | 6.130299 | 0.00581650 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1024.1740 | 1004.8586 | 1.2032 | CAV_BAS FAN | Fan:ConstantVolume | 6.130299 | 7.37577258 | 4197.9300 | 999.8980 | 135.42095840 | 12.27 | 6.67 | 5.60 | 3183531.14 | 4.2947 | 4.294686 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | Sensible | 136722.67 | 100697.33 | 1.0000 | 7.37577258 | 6.130299 | 24.84 | 18.24 | 0.01040047 | 51454.5 | 11.42 | 11.42 | 0.00850000 | 32917.7 | 5.81590512 | 6.67 | 12.27 | 5.60 | 10394.868 | 126327.80 | 28.05 | 0.01652538 | 23.59 | 1.20015641 | 19.5775 | 24.06 | 0.00890947 | 24.00 | 0.00890947 | 47.8933 | 85050.19 | 0.00 | 136940.30 | 97736.29 | 7.37577258 | 24.84 | 18.25 | 0.01040047 | 51454.5 | 11.90 | 11.52 | 0.00829381 | 32888.2 | |
CAV_BAS HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | CAV_BAS | BASEMENT | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 289789.718 | 289789.718 | 6.130299 | 0.00253521 | 6568.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2032 | CAV_BAS FAN | Fan:ConstantVolume | 6.130299 | 7.37577258 | 4197.9300 | 999.8980 | 14.30326541 | 54.44 | 82.22 | 27.78 | 1668025.29 | 17.3732 | 17.722864 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 289789.72 | 289789.72 | 1.0000 | 7.37577258 | 6.130299 | 0.90 | 0.90 | 0.00525715 | 14061.5 | 40.00 | 21.17 | 0.00800000 | 60796.0 | 2.53494825 | 60.00 | 32.22 | 27.78 | 0.000 | 289789.72 | 4.60 | 0.00525715 | 4.60 | 1.20015641 | 19.5775 | 0.00 | 0.00525715 | 25.23 | 0.00525715 | 26.4073 | 0.00 | 0.00 | 248244.56 | 248244.56 | 7.37577258 | 12.80 | 8.65 | 0.00525715 | 26134.9 | 45.97 | 20.96 | 0.00525715 | 59791.6 | |
AIRLOOP DATACENTER BASEMENT COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | DATACENTER_BASEMENT_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 436425.080 | 313849.499 | 21.438522 | 0.01068802 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1020.9541 | 1004.8586 | 1.2032 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 07:10:00 | Sensible | 408893.31 | 398959.36 | 0.9369 | -999.0 | -999.0 | 28.51 | 18.07 | 0.00866839 | 50784.7 | 12.80 | 12.09 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 408893.31 | 33.90 | 0.01653638 | 25.13 | 0.33839277 | -999.0000 | 27.00 | 0.00854205 | 27.00 | 0.00854205 | 38.4495 | 373297.50 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BOT COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BOT | DATACENTER_BOT_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 9781.483 | 7027.923 | 0.480202 | 0.00023955 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1021.2826 | 1004.8586 | 1.2032 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 18:40:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 18:40:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 18:40:00 | Sensible | 9164.65 | 8708.94 | 0.9369 | -999.0 | -999.0 | 28.08 | 18.07 | 0.00884508 | 50801.4 | 12.80 | 12.09 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9164.65 | 31.21 | 0.01653132 | 24.43 | 0.01563234 | -999.0000 | 27.00 | 0.00858645 | 27.00 | 0.00858645 | 38.6443 | 8372.67 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER MID COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER MID | DATACENTER_MID_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 93413.422 | 67025.978 | 4.574191 | 0.00228769 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1021.3142 | 1004.8586 | 1.2032 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 18:40:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 18:40:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 18:40:00 | Sensible | 87560.57 | 83004.98 | 0.9373 | -999.0 | -999.0 | 28.09 | 18.09 | 0.00886209 | 50851.7 | 12.80 | 12.09 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 87560.57 | 31.21 | 0.01653132 | 24.43 | 0.15632344 | -999.0000 | 27.00 | 0.00859072 | 27.00 | 0.00859072 | 38.6635 | 79753.76 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER TOP COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER TOP | DATACENTER_TOP_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 9511.329 | 6826.928 | 0.466051 | 0.00023293 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1021.3019 | 1004.8586 | 1.2032 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 18:30:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 18:30:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 18:40:00 | Sensible | 8914.44 | 8458.74 | 0.9372 | -999.0 | -999.0 | 28.09 | 18.08 | 0.00885551 | 50839.0 | 12.80 | 12.09 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 8914.44 | 31.41 | 0.01653169 | 24.48 | 0.01563234 | -999.0000 | 27.00 | 0.00858901 | 27.00 | 0.00858901 | 38.6558 | 8123.55 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BASEMENT HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | DATACENTER_BASEMENT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 436425.080 | 436425.080 | 21.438522 | 0.01068802 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 1.2032 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 436425.08 | 436425.08 | 1.0000 | 25.79411948 | 21.438522 | 4.60 | 4.60 | 0.00525715 | 17815.0 | 40.00 | 21.17 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 436425.08 | 4.60 | 0.00525715 | 4.60 | 0.33839277 | 1.5784 | 0.00 | 0.00850000 | 27.00 | 0.00850000 | 38.2570 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BOT HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BOT | DATACENTER_BOT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 9781.483 | 9781.483 | 0.480202 | 0.00023955 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 1.2032 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 9781.48 | 9781.48 | 1.0000 | 0.57776373 | 0.480202 | 4.60 | 4.60 | 0.00525715 | 17815.0 | 40.00 | 21.17 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9781.48 | 4.60 | 0.00525715 | 4.60 | 0.01563234 | 3.2554 | 0.00 | 0.00850000 | 27.00 | 0.00850000 | 38.2570 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER MID HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER MID | DATACENTER_MID_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 93413.422 | 93413.422 | 4.574191 | 0.00228769 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 1.2032 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 93413.42 | 93413.42 | 1.0000 | 5.50351541 | 4.574191 | 4.60 | 4.60 | 0.00525715 | 17815.0 | 40.00 | 21.17 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 93413.42 | 4.60 | 0.00525715 | 4.60 | 0.15632344 | 3.4175 | 0.00 | 0.00733798 | 24.85 | 0.00733798 | 37.5784 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER TOP HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER TOP | DATACENTER_TOP_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 9511.329 | 9511.329 | 0.466051 | 0.00023293 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 1.2032 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 9511.33 | 9511.33 | 1.0000 | 0.56073771 | 0.466051 | 4.60 | 4.60 | 0.00525715 | 17815.0 | 40.00 | 21.17 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9511.33 | 4.60 | 0.00525715 | 4.60 | 0.01563234 | 3.3542 | 0.00 | 0.00543800 | 23.98 | 0.00543800 | 29.4351 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | DATACENTER_BASEMENT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 14482.888 | 14482.888 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2032 | AIRLOOP DATACENTER BASEMENT SUPPLY FAN | Fan:OnOff | 21.438522 | 25.79411948 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 14482.89 | 14482.89 | 1.0000 | 25.79411948 | 21.438522 | 0.07 | 0.07 | 0.00844881 | 21204.1 | 40.00 | 21.17 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 14482.89 | 4.60 | 0.00525715 | 4.60 | 0.33839277 | 1.5784 | 0.00 | 0.00850000 | 27.00 | 0.00850000 | 38.2570 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BOT_SUPPHEATCOIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BOT | DATACENTER_BOT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 669.049 | 669.049 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2032 | AIRLOOP DATACENTER BOT SUPPLY FAN | Fan:OnOff | 0.480202 | 0.57776373 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 669.05 | 669.05 | 1.0000 | 0.57776373 | 0.480202 | 0.15 | 0.15 | 0.00839443 | 21146.8 | 40.00 | 21.17 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 669.05 | 4.60 | 0.00525715 | 4.60 | 0.01563234 | 3.2554 | 0.00 | 0.00850000 | 27.00 | 0.00850000 | 38.2570 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER MID_SUPPHEATCOIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER MID | DATACENTER_MID_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 6690.494 | 6690.494 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2032 | AIRLOOP DATACENTER MID SUPPLY FAN | Fan:OnOff | 4.574191 | 5.50351541 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 6690.49 | 6690.49 | 1.0000 | 5.50351541 | 4.574191 | 0.16 | 0.16 | 0.00726686 | 18334.1 | 40.00 | 21.17 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 6690.49 | 4.60 | 0.00525715 | 4.60 | 0.15632344 | 3.4175 | 0.00 | 0.00733798 | 24.85 | 0.00733798 | 37.5784 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER TOP_SUPPHEATCOIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER TOP | DATACENTER_TOP_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 669.049 | 669.049 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2032 | AIRLOOP DATACENTER TOP SUPPLY FAN | Fan:OnOff | 0.466051 | 0.56073771 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 669.05 | 669.05 | 1.0000 | 0.56073771 | 0.466051 | 0.15 | 0.15 | 0.00543194 | 13741.5 | 40.00 | 21.17 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 669.05 | 4.60 | 0.00525715 | 4.60 | 0.01563234 | 3.3542 | 0.00 | 0.00543800 | 23.98 | 0.00543800 | 29.4351 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 08:44:04
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
VAV_BOT WITH REHEAT_OA_CONTROLLER | DifferentialEnthalpy | 2.54 | 9.79 | - | |||
VAV_MID WITH REHEAT_OA_CONTROLLER | DifferentialEnthalpy | 25.38 | 90.94 | - | |||
VAV_TOP WITH REHEAT_OA_CONTROLLER | DifferentialEnthalpy | 2.54 | 9.91 | - | |||
CAV_BAS_OA_CONTROLLER | DifferentialEnthalpy | 1.20 | 6.13 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
CORE_BOTTOM | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_MID | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_TOP | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
BASEMENT | 4990.50 | 1868.17 | 1835.67 |
CORE_BOTTOM | 4784.17 | 200.83 | 0.00 |
CORE_MID | 2975.83 | 1321.50 | 0.00 |
CORE_TOP | 3110.00 | 1773.67 | 46.33 |
PERIMETER_BOT_ZN_3 | 4092.17 | 1318.00 | 53.67 |
PERIMETER_BOT_ZN_2 | 3775.00 | 1542.33 | 168.00 |
PERIMETER_BOT_ZN_1 | 4671.00 | 976.83 | 258.67 |
PERIMETER_BOT_ZN_4 | 4953.00 | 865.33 | 310.83 |
PERIMETER_MID_ZN_3 | 3550.17 | 2335.33 | 359.00 |
PERIMETER_MID_ZN_2 | 2897.50 | 2026.33 | 395.00 |
PERIMETER_MID_ZN_1 | 4346.50 | 1423.67 | 402.00 |
PERIMETER_MID_ZN_4 | 3706.67 | 2003.67 | 331.17 |
PERIMETER_TOP_ZN_3 | 3764.00 | 2548.17 | 737.17 |
PERIMETER_TOP_ZN_2 | 3684.67 | 2408.83 | 625.00 |
PERIMETER_TOP_ZN_1 | 4230.33 | 1724.67 | 556.00 |
PERIMETER_TOP_ZN_4 | 3681.67 | 2256.50 | 533.67 |
DATACENTER_BOT_ZN_6 | 5943.00 | 2210.50 | 2210.50 |
DATACENTER_MID_ZN_6 | 5935.83 | 335.17 | 335.17 |
DATACENTER_TOP_ZN_6 | 5878.50 | 815.00 | 796.67 |
DATACENTER_BASEMENT_ZN_6 | 5943.00 | 5938.17 | 5938.17 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
Facility | 5943.00 | 5943.00 | 5943.00 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
BASEMENT | 0.00 | 63.83 | 0.00 | 5.33 |
CORE_BOTTOM | 0.00 | 0.17 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.67 | 0.00 | 0.17 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 1.83 | 0.00 | 1.83 |
PERIMETER_BOT_ZN_2 | 0.00 | 27.33 | 0.00 | 27.33 |
PERIMETER_BOT_ZN_1 | 0.00 | 58.00 | 0.00 | 56.83 |
PERIMETER_BOT_ZN_4 | 0.00 | 134.00 | 0.00 | 58.17 |
PERIMETER_MID_ZN_3 | 0.67 | 0.33 | 0.00 | 0.33 |
PERIMETER_MID_ZN_2 | 0.50 | 35.00 | 0.00 | 35.00 |
PERIMETER_MID_ZN_1 | 0.00 | 59.17 | 0.00 | 57.67 |
PERIMETER_MID_ZN_4 | 0.00 | 37.83 | 0.00 | 26.50 |
PERIMETER_TOP_ZN_3 | 9.17 | 15.50 | 1.50 | 12.67 |
PERIMETER_TOP_ZN_2 | 7.17 | 50.17 | 0.50 | 48.67 |
PERIMETER_TOP_ZN_1 | 3.83 | 56.50 | 0.67 | 53.67 |
PERIMETER_TOP_ZN_4 | 4.00 | 43.00 | 0.83 | 29.00 |
DATACENTER_BOT_ZN_6 | 0.00 | 19.50 | 0.00 | 19.50 |
DATACENTER_MID_ZN_6 | 0.00 | 13.33 | 0.00 | 13.33 |
DATACENTER_TOP_ZN_6 | 0.00 | 6.33 | 0.00 | 6.33 |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 602.00 | 0.00 | 545.17 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 9.50 | 924.67 | 1.50 | 736.00 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 08:44:04
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 62.54 | 149.60 | 6779.02 | 1.061 | 0.000 | 0.000 | 0.000 |
CORE_BOTTOM | 56.16 | 134.35 | 6849.35 | 0.763 | 0.000 | 0.000 | 0.000 |
CORE_MID | 56.16 | 134.35 | 6849.35 | 0.687 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 56.16 | 134.35 | 6849.35 | 0.675 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 7.05 | 16.87 | 860.00 | 0.828 | 0.034 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 4.54 | 10.87 | 554.22 | 1.087 | 0.035 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 7.05 | 16.87 | 860.02 | 1.141 | 0.034 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 4.54 | 10.87 | 554.22 | 1.550 | 0.035 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 7.05 | 16.87 | 860.00 | 0.791 | 0.079 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 3.97 | 10.87 | 554.22 | 1.063 | 0.087 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 7.05 | 16.87 | 860.02 | 1.121 | 0.079 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 4.54 | 10.87 | 554.22 | 1.223 | 0.082 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 7.05 | 16.87 | 860.00 | 0.791 | 0.098 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 4.54 | 10.87 | 554.22 | 1.141 | 0.101 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 7.05 | 16.87 | 860.02 | 1.093 | 0.098 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 4.54 | 10.87 | 554.22 | 1.227 | 0.101 | 0.000 | 0.000 |
DATACENTER_BOT_ZN_6 | 0.81 | 1.95 | 99.34 | 0.427 | 0.000 | 0.000 | 0.000 |
DATACENTER_MID_ZN_6 | 0.81 | 1.95 | 99.34 | 0.427 | 0.000 | 0.000 | 0.000 |
DATACENTER_TOP_ZN_6 | 0.81 | 1.95 | 99.34 | 0.427 | 0.000 | 0.000 | 0.000 |
DATACENTER_BASEMENT_ZN_6 | 17.63 | 42.18 | 1911.37 | 0.481 | 0.000 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 62.54 | 149.60 | 6779.02 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_BOTTOM | 56.16 | 134.35 | 6849.35 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_MID | 56.16 | 134.35 | 6849.35 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 56.16 | 134.35 | 6849.35 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 7.05 | 16.87 | 860.00 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 4.54 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 7.05 | 16.87 | 860.02 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 4.54 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 7.05 | 16.87 | 860.00 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 3.97 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 7.05 | 16.87 | 860.02 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 4.54 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 7.05 | 16.87 | 860.00 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 4.54 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 7.05 | 16.87 | 860.02 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 4.54 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
DATACENTER_BOT_ZN_6 | 0.81 | 1.95 | 99.34 | 0.000 | 0.000 | 0.000 | 0.000 |
DATACENTER_MID_ZN_6 | 0.81 | 1.95 | 99.34 | 0.000 | 0.000 | 0.000 | 0.000 |
DATACENTER_TOP_ZN_6 | 0.81 | 1.95 | 99.34 | 0.000 | 0.000 | 0.000 | 0.000 |
DATACENTER_BASEMENT_ZN_6 | 17.63 | 42.18 | 1911.37 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 08:44:04
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
BASEMENT | CAV_BAS | 62.54 | 149.60 | 6779.02 | 2779.43 | 1.2002 | 1.200 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | 56.16 | 134.35 | 6849.35 | 2496.12 | 0.0000 | 1.078 |
CORE_MID | VAV_MID WITH REHEAT | 56.16 | 134.35 | 6849.35 | 2496.12 | 0.0000 | 10.778 |
CORE_TOP | VAV_TOP WITH REHEAT | 56.16 | 134.35 | 6849.35 | 2496.12 | 0.0000 | 1.078 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | 7.05 | 16.87 | 860.00 | 313.41 | 0.0000 | 0.135 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | 4.54 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | 7.05 | 16.87 | 860.02 | 313.42 | 0.0000 | 0.135 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | 4.54 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | 7.05 | 16.87 | 860.00 | 313.41 | 0.0000 | 1.353 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | 3.97 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.872 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | 7.05 | 16.87 | 860.02 | 313.42 | 0.0000 | 1.353 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | 4.54 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.872 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | 7.05 | 16.87 | 860.00 | 313.41 | 0.0000 | 0.135 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | 4.54 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | 7.05 | 16.87 | 860.02 | 313.42 | 0.0000 | 0.135 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | 4.54 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | 0.81 | 1.95 | 99.34 | 36.20 | 0.0156 | 0.016 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | 0.81 | 1.95 | 99.34 | 36.20 | 0.1563 | 0.156 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | 0.81 | 1.95 | 99.34 | 36.20 | 0.0156 | 0.016 |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | 17.63 | 42.18 | 1911.37 | 783.68 | 0.3384 | 0.338 |
Total Facility | 1036.48 | 2493.19 | 126016.35 | 46320.38 | 1.7261 | 158.471 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
BASEMENT | 43645228.65 | 0.00 | 43645228.65 | 0.00 | 43645228.65 | 37848132.68 | 4117.51 | 2810.58 | 1831.91 | 198.74 |
CORE_BOTTOM | 31115452.49 | 0.00 | 31115452.49 | 0.00 | 31115452.49 | 33990283.35 | 4112.94 | 3.24 | 4643.82 | 91.18 |
CORE_MID | 0.28E+09 | 0.00 | 0.28E+09 | 0.00 | 0.28E+09 | 0.34E+09 | 4229.85 | 1.13 | 4529.02 | 28.21 |
CORE_TOP | 27112612.70 | 0.00 | 27112612.70 | 0.00 | 27112612.70 | 33990283.35 | 4261.63 | 4.71 | 4493.66 | 44.95 |
PERIMETER_BOT_ZN_3 | 4221078.96 | 0.00 | 4221078.96 | 328931.10 | 4550010.06 | 4267819.30 | 4115.44 | 2.29 | 4642.27 | 91.18 |
PERIMETER_BOT_ZN_2 | 3579984.03 | 0.00 | 3579984.03 | 219287.25 | 3799271.27 | 2750345.05 | 4103.43 | 0.00 | 4656.57 | 91.18 |
PERIMETER_BOT_ZN_1 | 5793961.97 | 0.00 | 5793961.97 | 328931.10 | 6122893.07 | 4267912.63 | 4110.16 | 2.09 | 4647.75 | 91.18 |
PERIMETER_BOT_ZN_4 | 5094951.76 | 0.00 | 5094951.76 | 219287.25 | 5314239.01 | 2750345.05 | 4102.37 | 0.00 | 4657.63 | 91.18 |
PERIMETER_MID_ZN_3 | 39854928.83 | 0.00 | 39854928.83 | 771421.61 | 40626350.45 | 42678193.03 | 4233.29 | 6.25 | 4520.46 | 28.21 |
PERIMETER_MID_ZN_2 | 37285445.07 | 0.00 | 37285445.07 | 514280.72 | 37799725.79 | 27503450.52 | 4212.34 | 0.00 | 4547.66 | 937.21 |
PERIMETER_MID_ZN_1 | 56394578.68 | 0.00 | 56394578.68 | 771421.61 | 57166000.30 | 42679126.28 | 4228.51 | 1.25 | 4530.24 | 28.21 |
PERIMETER_MID_ZN_4 | 39732986.40 | 0.00 | 39732986.40 | 514280.72 | 40247267.13 | 27503450.52 | 4212.26 | 0.00 | 4547.74 | 28.21 |
PERIMETER_TOP_ZN_3 | 3994752.48 | 0.00 | 3994752.48 | 957784.80 | 4952537.28 | 4267819.30 | 4246.42 | 3.66 | 4509.92 | 44.95 |
PERIMETER_TOP_ZN_2 | 3713008.26 | 0.00 | 3713008.26 | 638522.76 | 4351531.02 | 2750345.05 | 4225.63 | 0.80 | 4533.57 | 44.95 |
PERIMETER_TOP_ZN_1 | 5502730.53 | 0.00 | 5502730.53 | 957784.80 | 6460515.33 | 4267912.63 | 4244.32 | 1.39 | 4514.29 | 44.95 |
PERIMETER_TOP_ZN_4 | 3994068.04 | 0.00 | 3994068.04 | 638522.76 | 4632590.80 | 2750345.05 | 4221.83 | 2.54 | 4535.63 | 44.95 |
DATACENTER_BOT_ZN_6 | 244296.02 | 0.00 | 244296.02 | 0.00 | 244296.02 | 492981.60 | 4419.00 | 4341.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 2442960.18 | 0.00 | 2442960.18 | 0.00 | 2442960.18 | 4929815.99 | 4419.00 | 4341.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 244296.02 | 0.00 | 244296.02 | 0.00 | 244296.02 | 492981.60 | 4419.00 | 4341.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 5288266.81 | 0.00 | 5288266.81 | 0.00 | 5288266.81 | 10671554.30 | 4419.00 | 4341.00 | 0.00 | 0.00 |
Total Facility | 0.47E+10 | 0.00 | 0.47E+10 | 30003098.57 | 0.47E+10 | 0.50E+10 | 4429.89 | 4355.71 | 4807.66 | 1152.03 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
BASEMENT | 1.9551 | 0.0000 | 1.9551 | 0.0000 | 1.9551 | 1.2002 | 1435.13 | 2809.84 | 1698.04 |
CORE_BOTTOM | 1.4227 | 0.0000 | 1.4227 | 0.0000 | 1.4227 | 1.0778 | 1383.95 | 2.88 | 4556.17 |
CORE_MID | 12.8213 | 0.0000 | 12.8213 | 0.0000 | 12.8213 | 10.7782 | 1434.34 | 0.87 | 4507.79 |
CORE_TOP | 1.2591 | 0.0000 | 1.2591 | 0.0000 | 1.2591 | 1.0778 | 1465.28 | 3.23 | 4474.49 |
PERIMETER_BOT_ZN_3 | 0.1939 | 0.0000 | 0.1939 | 0.0079 | 0.2017 | 0.1353 | 1386.17 | 1.92 | 4554.91 |
PERIMETER_BOT_ZN_2 | 0.1642 | 0.0000 | 0.1642 | 0.0053 | 0.1694 | 0.0872 | 1377.61 | 0.00 | 4565.39 |
PERIMETER_BOT_ZN_1 | 0.2672 | 0.0000 | 0.2672 | 0.0079 | 0.2751 | 0.1353 | 1383.04 | 1.08 | 4558.88 |
PERIMETER_BOT_ZN_4 | 0.2339 | 0.0000 | 0.2339 | 0.0053 | 0.2391 | 0.0872 | 1376.55 | 0.00 | 4566.45 |
PERIMETER_MID_ZN_3 | 1.8535 | 0.0000 | 1.8535 | 0.0185 | 1.8720 | 1.3533 | 1438.52 | 6.01 | 4498.47 |
PERIMETER_MID_ZN_2 | 1.6072 | 0.0000 | 1.6072 | 0.0131 | 1.6202 | 0.8721 | 1423.56 | 0.00 | 3610.44 |
PERIMETER_MID_ZN_1 | 2.6266 | 0.0000 | 2.6266 | 0.0185 | 2.6451 | 1.3533 | 1433.38 | 0.83 | 4508.79 |
PERIMETER_MID_ZN_4 | 1.8475 | 0.0000 | 1.8475 | 0.0123 | 1.8598 | 0.8721 | 1423.48 | 0.00 | 4519.52 |
PERIMETER_TOP_ZN_3 | 0.1855 | 0.0000 | 0.1855 | 0.0229 | 0.2085 | 0.1353 | 1455.79 | 2.41 | 4484.79 |
PERIMETER_TOP_ZN_2 | 0.1725 | 0.0000 | 0.1725 | 0.0153 | 0.1878 | 0.0872 | 1442.02 | 0.28 | 4500.69 |
PERIMETER_TOP_ZN_1 | 0.2560 | 0.0000 | 0.2560 | 0.0229 | 0.2790 | 0.1353 | 1453.29 | 1.22 | 4488.49 |
PERIMETER_TOP_ZN_4 | 0.1856 | 0.0000 | 0.1856 | 0.0153 | 0.2009 | 0.0872 | 1440.99 | 0.98 | 4501.04 |
DATACENTER_BOT_ZN_6 | 0.0114 | 0.0000 | 0.0114 | 0.0000 | 0.0114 | 0.0156 | 1602.00 | 4341.00 | 0.00 |
DATACENTER_MID_ZN_6 | 0.1142 | 0.0000 | 0.1142 | 0.0000 | 0.1142 | 0.1563 | 1602.00 | 4341.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 0.0114 | 0.0000 | 0.0114 | 0.0000 | 0.0114 | 0.0156 | 1602.00 | 4341.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.2472 | 0.0000 | 0.2472 | 0.0000 | 0.2472 | 0.3384 | 1602.00 | 4341.00 | 0.00 |
Total Facility | 215.2677 | 0.0000 | 215.2677 | 0.7263 | 215.9940 | 158.4706 | 1612.89 | 4349.24 | 4622.15 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
VAV_BOT WITH REHEAT | 72099515.17 | 0.00 | 72099515.17 | 48026705.38 | 4102.37 | 0.00 | 4657.63 | 91.18 |
VAV_MID WITH REHEAT | 0.65E+09 | 0.00 | 0.65E+09 | 0.48E+09 | 4212.26 | 0.00 | 4547.74 | 28.21 |
VAV_TOP WITH REHEAT | 64153345.35 | 0.00 | 64153345.35 | 48026705.38 | 4224.32 | 0.43 | 4535.24 | 44.95 |
CAV_BAS | 63181294.82 | 0.00 | 63181294.82 | 37848132.68 | 4085.85 | 0.88 | 4673.27 | 198.74 |
AIRLOOP DATACENTER BASEMENT | 7655350.99 | 0.00 | 7655350.99 | 10671554.30 | 4419.00 | 0.00 | 4341.00 | 0.00 |
AIRLOOP DATACENTER BOT | 353645.50 | 0.00 | 353645.50 | 492981.60 | 4419.00 | 0.00 | 4341.00 | 0.00 |
AIRLOOP DATACENTER MID | 3536455.01 | 0.00 | 3536455.01 | 4929815.99 | 4419.00 | 0.00 | 4341.00 | 0.00 |
AIRLOOP DATACENTER TOP | 353645.50 | 0.00 | 353645.50 | 492981.60 | 4419.00 | 0.00 | 4341.00 | 0.00 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
VAV_BOT WITH REHEAT | 3.3032 | 0.0000 | 3.3032 | 1.5229 | 1376.55 | 0.00 | 4566.45 |
VAV_MID WITH REHEAT | 30.2310 | 0.0000 | 30.2310 | 15.2292 | 1423.48 | 0.00 | 4519.52 |
VAV_TOP WITH REHEAT | 2.9803 | 0.0000 | 2.9803 | 1.5229 | 1441.37 | 0.02 | 4501.61 |
CAV_BAS | 2.8302 | 0.0000 | 2.8302 | 1.2002 | 1431.41 | 0.04 | 4511.55 |
AIRLOOP DATACENTER BASEMENT | 0.3578 | 0.0000 | 0.3578 | 0.3384 | 1602.00 | 0.00 | 4341.00 |
AIRLOOP DATACENTER BOT | 0.0165 | 0.0000 | 0.0165 | 0.0156 | 1602.00 | 0.00 | 4341.00 |
AIRLOOP DATACENTER MID | 0.1653 | 0.0000 | 0.1653 | 0.1563 | 1602.00 | 0.00 | 4341.00 |
AIRLOOP DATACENTER TOP | 0.0165 | 0.0000 | 0.0165 | 0.0156 | 1602.00 | 0.00 | 4341.00 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
VAV_BOT WITH REHEAT | 0.00 | 3168.10 | 1489.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
VAV_MID WITH REHEAT | 0.00 | 3255.39 | 1292.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
VAV_TOP WITH REHEAT | 0.00 | 3285.00 | 1265.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CAV_BAS | 0.00 | 2809.44 | 1903.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER BASEMENT | 0.00 | 4341.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER BOT | 0.00 | 4341.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER MID | 0.00 | 4341.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER TOP | 0.00 | 4341.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
VAV_BOT WITH REHEAT | 0.0000 | 3.6744 | 5.7155 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
VAV_MID WITH REHEAT | 0.0000 | 36.7476 | 47.5076 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
VAV_TOP WITH REHEAT | 0.0000 | 3.6754 | 4.6244 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
CAV_BAS | 0.0000 | 1.7376 | 7.0065 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
AIRLOOP DATACENTER BASEMENT | 0.0000 | 0.4900 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
AIRLOOP DATACENTER BOT | 0.0000 | 0.0226 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
AIRLOOP DATACENTER MID | 0.0000 | 0.2263 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
AIRLOOP DATACENTER TOP | 0.0000 | 0.0226 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 08:44:04
Surfaces by ClassTotal | Outdoors | |
Wall | 98 | 30 |
Floor | 41 | 0 |
Roof | 30 | 1 |
Internal Mass | 16 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 24 | 24 |
Door | 12 | 12 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 8 |
Conditioned Zones | 23 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 3 |
Count | |
IDF Objects | 1404 |
Defaulted Fields | 1182 |
Fields with Defaults | 3915 |
Autosized Fields | 338 |
Autosizable Fields | 414 |
Autocalculated Fields | 226 |
Autocalculatable Fields | 473 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 08:44:04
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 32032.57 | 370622.15 | 22-JAN-10:10 | 1978865.65 | 03-AUG-15:30 |
Electricity:Building | 18600.45 | 225715.65 | 28-MAY-17:10 | 1164206.62 | 12-DEC-08:10 |
Electricity:Zone:BASEMENT | 687.24 | 14732.47 | 01-JAN-00:10 | 36407.88 | 02-JAN-08:10 |
Electricity:SpaceType:GENERAL | 18600.45 | 225715.65 | 28-MAY-17:10 | 1164206.62 | 12-DEC-08:10 |
InteriorLights:Electricity | 3924.05 | 18459.50 | 01-JAN-09:30 | 385834.94 | 25-OCT-07:10 |
InteriorLights:Electricity:Zone:BASEMENT | 262.84 | 1274.92 | 01-JAN-00:10 | 22950.34 | 02-JAN-08:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 3924.05 | 18459.50 | 01-JAN-09:30 | 385834.94 | 25-OCT-07:10 |
LightsWired:InteriorLights:Electricity | 3924.05 | 18459.50 | 01-JAN-09:30 | 385834.94 | 25-OCT-07:10 |
LightsWired:InteriorLights:Electricity:Zone:BASEMENT | 262.84 | 1274.92 | 01-JAN-00:10 | 22950.34 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 3924.05 | 18459.50 | 01-JAN-09:30 | 385834.94 | 25-OCT-07:10 |
Electricity:Zone:CORE_BOTTOM | 525.67 | 5598.20 | 01-JAN-00:10 | 37817.64 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_BOTTOM | 236.05 | 1144.97 | 01-JAN-00:10 | 20611.01 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_BOTTOM | 236.05 | 1144.97 | 01-JAN-00:10 | 20611.01 | 02-JAN-08:10 |
Electricity:Zone:CORE_MID | 5256.66 | 55981.88 | 01-JAN-00:10 | 378175.77 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_MID | 2360.53 | 11449.71 | 01-JAN-00:10 | 206110.14 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_MID | 2360.53 | 11449.71 | 01-JAN-00:10 | 206110.14 | 02-JAN-08:10 |
Electricity:Zone:CORE_TOP | 525.67 | 5598.19 | 01-JAN-00:10 | 37817.58 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_TOP | 236.05 | 1144.97 | 01-JAN-00:10 | 20611.01 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_TOP | 236.05 | 1144.97 | 01-JAN-00:10 | 20611.01 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_3 | 53.66 | 627.57 | 26-MAR-17:10 | 4748.47 | 25-OCT-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 17.29 | 68.40 | 01-JAN-09:30 | 2587.92 | 25-OCT-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 17.29 | 68.40 | 01-JAN-09:30 | 2587.92 | 25-OCT-07:10 |
Electricity:Zone:PERIMETER_BOT_ZN_2 | 34.48 | 404.43 | 28-MAY-17:10 | 3060.10 | 25-OCT-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 11.04 | 44.08 | 01-JAN-07:50 | 1667.75 | 25-OCT-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 11.04 | 44.08 | 01-JAN-07:50 | 1667.75 | 25-OCT-07:10 |
Electricity:Zone:PERIMETER_BOT_ZN_1 | 53.33 | 627.58 | 12-MAR-17:10 | 4748.56 | 25-OCT-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 16.97 | 68.40 | 01-JAN-07:50 | 2587.98 | 25-OCT-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 16.97 | 68.40 | 01-JAN-07:50 | 2587.98 | 25-OCT-07:10 |
Electricity:Zone:PERIMETER_BOT_ZN_4 | 34.49 | 404.43 | 26-FEB-18:10 | 3060.09 | 01-FEB-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 11.06 | 44.08 | 01-JAN-09:30 | 1667.75 | 01-FEB-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 11.06 | 44.08 | 01-JAN-09:30 | 1667.75 | 01-FEB-08:10 |
Electricity:Zone:PERIMETER_MID_ZN_3 | 536.08 | 6275.73 | 26-MAR-17:10 | 47484.70 | 25-OCT-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 172.43 | 684.02 | 01-JAN-09:20 | 25879.19 | 25-OCT-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 172.43 | 684.02 | 01-JAN-09:20 | 25879.19 | 25-OCT-07:10 |
Electricity:Zone:PERIMETER_MID_ZN_2 | 344.56 | 4044.32 | 23-APR-17:10 | 30600.95 | 25-OCT-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 110.20 | 440.81 | 01-JAN-07:50 | 16677.53 | 25-OCT-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 110.20 | 440.81 | 01-JAN-07:50 | 16677.53 | 25-OCT-07:10 |
Electricity:Zone:PERIMETER_MID_ZN_1 | 533.07 | 6275.83 | 12-MAR-17:10 | 47485.60 | 25-OCT-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 169.41 | 684.04 | 01-JAN-07:50 | 25879.75 | 25-OCT-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 169.41 | 684.04 | 01-JAN-07:50 | 25879.75 | 25-OCT-07:10 |
Electricity:Zone:PERIMETER_MID_ZN_4 | 344.65 | 4044.30 | 26-FEB-18:10 | 30600.86 | 25-OCT-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 110.30 | 440.81 | 01-JAN-09:20 | 16677.53 | 25-OCT-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 110.30 | 440.81 | 01-JAN-09:20 | 16677.53 | 25-OCT-07:10 |
Electricity:Zone:PERIMETER_TOP_ZN_3 | 53.61 | 627.57 | 26-MAR-17:10 | 4748.47 | 25-OCT-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 17.24 | 68.40 | 01-JAN-09:20 | 2587.92 | 25-OCT-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 17.24 | 68.40 | 01-JAN-09:20 | 2587.92 | 25-OCT-07:10 |
Electricity:Zone:PERIMETER_TOP_ZN_2 | 34.45 | 404.43 | 23-APR-17:10 | 3060.10 | 25-OCT-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 11.02 | 44.08 | 01-JAN-07:50 | 1667.75 | 25-OCT-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 11.02 | 44.08 | 01-JAN-07:50 | 1667.75 | 25-OCT-07:10 |
Electricity:Zone:PERIMETER_TOP_ZN_1 | 53.31 | 627.58 | 12-MAR-17:10 | 4748.56 | 25-OCT-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 16.94 | 68.40 | 01-JAN-07:50 | 2587.98 | 25-OCT-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 16.94 | 68.40 | 01-JAN-07:50 | 2587.98 | 25-OCT-07:10 |
Electricity:Zone:PERIMETER_TOP_ZN_4 | 34.46 | 404.43 | 26-FEB-18:10 | 3060.09 | 25-OCT-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 11.03 | 44.08 | 01-JAN-09:20 | 1667.75 | 25-OCT-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 11.03 | 44.08 | 01-JAN-09:20 | 1667.75 | 25-OCT-07:10 |
Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 7568.97 | 95267.60 | 01-JAN-00:10 | 386103.53 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 74.11 | 359.47 | 01-JAN-00:10 | 6471.01 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 74.11 | 359.47 | 01-JAN-00:10 | 6471.01 | 02-JAN-08:10 |
Electricity:Zone:DATACENTER_BOT_ZN_6 | 160.51 | 1980.76 | 01-JAN-00:10 | 8373.14 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_BOT_ZN_6 | 6.63 | 32.15 | 01-JAN-00:10 | 578.72 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_BOT_ZN_6 | 6.63 | 32.15 | 01-JAN-00:10 | 578.72 | 02-JAN-08:10 |
Electricity:Zone:DATACENTER_MID_ZN_6 | 1605.09 | 19807.58 | 01-JAN-00:10 | 83731.41 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_MID_ZN_6 | 66.28 | 321.53 | 01-JAN-00:10 | 5787.18 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_MID_ZN_6 | 66.28 | 321.53 | 01-JAN-00:10 | 5787.18 | 02-JAN-08:10 |
Electricity:Zone:DATACENTER_TOP_ZN_6 | 160.51 | 1980.76 | 01-JAN-00:10 | 8373.14 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_TOP_ZN_6 | 6.63 | 32.15 | 01-JAN-00:10 | 578.72 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_TOP_ZN_6 | 6.63 | 32.15 | 01-JAN-00:10 | 578.72 | 02-JAN-08:10 |
InteriorEquipment:Electricity | 14676.40 | 207256.16 | 01-JAN-00:10 | 778371.69 | 03-APR-07:10 |
InteriorEquipment:Electricity:Zone:BASEMENT | 424.40 | 13457.54 | 01-JAN-00:10 | 13457.54 | 01-JAN-00:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 14676.40 | 207256.16 | 01-JAN-00:10 | 778371.69 | 03-APR-07:10 |
MiscPlug:InteriorEquipment:Electricity | 5334.97 | 88964.76 | 01-JAN-00:10 | 305206.10 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:BASEMENT | 424.40 | 13457.54 | 01-JAN-00:10 | 13457.54 | 01-JAN-00:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 5334.97 | 88964.76 | 01-JAN-00:10 | 305206.10 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 289.61 | 4453.23 | 01-JAN-00:10 | 17206.63 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 289.61 | 4453.23 | 01-JAN-00:10 | 17206.63 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_MID | 2896.13 | 44532.17 | 01-JAN-00:10 | 172065.63 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_MID | 2896.13 | 44532.17 | 01-JAN-00:10 | 172065.63 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_TOP | 289.61 | 4453.22 | 01-JAN-00:10 | 17206.56 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_TOP | 289.61 | 4453.22 | 01-JAN-00:10 | 17206.56 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 36.37 | 559.17 | 01-JAN-00:10 | 2160.55 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 36.37 | 559.17 | 01-JAN-00:10 | 2160.55 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.34 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.34 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 36.37 | 559.18 | 01-JAN-00:10 | 2160.58 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 36.37 | 559.18 | 01-JAN-00:10 | 2160.58 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.33 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.33 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 363.65 | 5591.71 | 01-JAN-00:10 | 21605.52 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 363.65 | 5591.71 | 01-JAN-00:10 | 21605.52 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 234.35 | 3603.51 | 01-JAN-00:10 | 13923.42 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 234.35 | 3603.51 | 01-JAN-00:10 | 13923.42 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 363.66 | 5591.79 | 01-JAN-00:10 | 21605.85 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 363.66 | 5591.79 | 01-JAN-00:10 | 21605.85 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 234.35 | 3603.49 | 01-JAN-00:10 | 13923.33 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 234.35 | 3603.49 | 01-JAN-00:10 | 13923.33 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 36.37 | 559.17 | 01-JAN-00:10 | 2160.55 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 36.37 | 559.17 | 01-JAN-00:10 | 2160.55 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.34 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.34 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 36.37 | 559.18 | 01-JAN-00:10 | 2160.58 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 36.37 | 559.18 | 01-JAN-00:10 | 2160.58 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.33 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.33 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 7494.86 | 94908.13 | 01-JAN-00:10 | 379632.52 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity | 9341.42 | 118291.40 | 01-JAN-00:10 | 473165.59 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 7494.86 | 94908.13 | 01-JAN-00:10 | 379632.52 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:SpaceType:GENERAL | 9341.42 | 118291.40 | 01-JAN-00:10 | 473165.59 | 31-MAR-23:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_BOT_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_BOT_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_MID_ZN_6 | 1538.81 | 19486.06 | 01-JAN-00:10 | 77944.22 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_MID_ZN_6 | 1538.81 | 19486.06 | 01-JAN-00:10 | 77944.22 | 31-MAR-23:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_TOP_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_TOP_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
Electricity:Plant | 5559.49 | 7141.41 | 10-JAN-05:00 | 473084.08 | 06-OCT-14:00 |
HeatRejection:Electricity | 1977.79 | 3230.32 | 05-JAN-08:00 | 95997.17 | 18-JAN-12:00 |
General:HeatRejection:Electricity | 1977.79 | 3230.32 | 05-JAN-08:00 | 95997.17 | 18-JAN-12:00 |
Electricity:HVAC | 5322.53 | 76467.53 | 22-JAN-06:00 | 357267.37 | 30-AUG-16:00 |
ExteriorEquipment:Electricity | 1934.79 | 28603.11 | 01-JAN-00:10 | 118535.44 | 25-OCT-07:20 |
Transformer:ExteriorEquipment:Electricity | 80.17 | 1421.04 | 01-JAN-00:10 | 5057.48 | 12-DEC-08:20 |
ElectricityPurchased:Facility | 32032.57 | 370622.15 | 22-JAN-10:10 | 1978865.65 | 03-AUG-15:30 |
ElectricityPurchased:Plant | 32032.57 | 370622.15 | 22-JAN-10:10 | 1978865.65 | 03-AUG-15:30 |
Cogeneration:ElectricityPurchased | 32032.57 | 370622.15 | 22-JAN-10:10 | 1978865.65 | 03-AUG-15:30 |
General:Cogeneration:ElectricityPurchased | 32032.57 | 370622.15 | 22-JAN-10:10 | 1978865.65 | 03-AUG-15:30 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 32032.57 | 370622.15 | 22-JAN-10:10 | 1978865.65 | 03-AUG-15:30 |
ElectricityNet:Plant | 32032.57 | 370622.15 | 22-JAN-10:10 | 1978865.65 | 03-AUG-15:30 |
Cogeneration:ElectricityNet | 32032.57 | 370622.15 | 22-JAN-10:10 | 1978865.65 | 03-AUG-15:30 |
General:Cogeneration:ElectricityNet | 32032.57 | 370622.15 | 22-JAN-10:10 | 1978865.65 | 03-AUG-15:30 |
Fans:Electricity | 2185.95 | 41727.99 | 01-JAN-01:30 | 151679.46 | 30-AUG-16:00 |
General:Fans:Electricity | 2185.95 | 41727.99 | 01-JAN-01:30 | 151679.46 | 30-AUG-16:00 |
ExteriorLights:Electricity | 695.49 | 0.00 | 01-JAN-07:30 | 57580.60 | 01-JAN-06:10 |
General:ExteriorLights:Electricity | 695.49 | 0.00 | 01-JAN-07:30 | 57580.60 | 01-JAN-06:10 |
ElevatorLift:ExteriorEquipment:Electricity | 1848.78 | 27144.47 | 01-JAN-00:10 | 113101.96 | 01-JAN-07:10 |
ElevatorLightsFan:ExteriorEquipment:Electricity | 5.83 | 37.60 | 01-JAN-00:10 | 376.00 | 01-JAN-07:10 |
HeatRecovery:Electricity | 65.40 | 0.00 | 01-JAN-00:10 | 5613.48 | 02-JAN-10:10 |
General:HeatRecovery:Electricity | 65.40 | 0.00 | 01-JAN-00:10 | 5613.48 | 02-JAN-10:10 |
Cooling:Electricity | 5755.20 | 30105.06 | 09-JAN-07:10 | 487572.39 | 07-AUG-12:10 |
General:Cooling:Electricity | 5755.20 | 30105.06 | 09-JAN-07:10 | 487572.39 | 07-AUG-12:10 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Humidifier:Electricity | 1.55 | 0.00 | 01-JAN-00:10 | 4288.72 | 08-MAR-22:00 |
General:Humidifier:Electricity | 1.55 | 0.00 | 01-JAN-00:10 | 4288.72 | 08-MAR-22:00 |
Boiler Parasitic:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Pumps:Electricity | 815.95 | 3429.96 | 01-JAN-00:10 | 66193.26 | 14-JUL-14:30 |
General:Pumps:Electricity | 815.95 | 3429.96 | 01-JAN-00:10 | 66193.26 | 14-JUL-14:30 |
WIRED_LTG_ELECTRICITY | 110.27 | 0.00 | 01-JAN-00:10 | 10841.96 | 25-OCT-07:20 |
WIRED_INT_EQUIP | 5334.97 | 88964.76 | 31-MAR-23:10 | 305206.10 | 03-APR-07:10 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 834.30 | 8146.58 | 29-MAY-16:10 | 794828.69 | 21-DEC-07:10 |
NaturalGas:Plant | 834.30 | 8146.58 | 29-MAY-16:10 | 794828.69 | 21-DEC-07:10 |
Heating:NaturalGas | 162.14 | 0.00 | 01-JAN-00:10 | 763980.07 | 21-DEC-07:10 |
Boiler:Heating:NaturalGas | 162.14 | 0.00 | 01-JAN-00:10 | 763980.07 | 21-DEC-07:10 |
WaterSystems:NaturalGas | 672.16 | 8146.58 | 10-JAN-05:10 | 75833.66 | 20-JAN-12:50 |
Water Heater:WaterSystems:NaturalGas | 672.16 | 8146.58 | 10-JAN-05:10 | 75833.66 | 20-JAN-12:50 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
PlantLoopCoolingDemand:Facility | 30579.00 | 148607.38 | 10-JAN-07:10 | 2781781.46 | 07-AUG-14:50 |
PlantLoopCoolingDemand:HVAC | 30579.00 | 148607.38 | 10-JAN-07:10 | 2781781.46 | 07-AUG-14:50 |
CoolingCoils:PlantLoopCoolingDemand | 30579.00 | 148607.38 | 10-JAN-07:10 | 2781781.46 | 07-AUG-14:50 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 15963.34 | 0.00 | 01-JAN-00:10 | 0.00 | 30-AUG-16:00 |
Water:HVAC | 0.58 | 0.00 | 01-JAN-00:10 | 0.00 | 08-MAR-22:00 |
Humidifier:Water | 0.58 | 0.00 | 01-JAN-00:10 | 0.00 | 08-MAR-22:00 |
General:Humidifier:Water | 0.58 | 0.00 | 01-JAN-00:10 | 0.00 | 08-MAR-22:00 |
MainsWater:Facility | 15963.34 | 0.00 | 01-JAN-00:10 | 0.00 | 30-AUG-16:00 |
MainsWater:HVAC | 0.58 | 0.00 | 01-JAN-00:10 | 0.00 | 08-MAR-22:00 |
Humidifier:MainsWater | 0.58 | 0.00 | 01-JAN-00:10 | 0.00 | 08-MAR-22:00 |
General:Humidifier:MainsWater | 0.58 | 0.00 | 01-JAN-00:10 | 0.00 | 08-MAR-22:00 |
Water:Plant | 15962.76 | 0.00 | 01-JAN-00:10 | 0.00 | 30-AUG-16:00 |
WaterSystems:Water | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterUse:WaterSystems:Water | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
MainsWater:Plant | 15962.76 | 0.00 | 01-JAN-00:10 | 0.00 | 30-AUG-16:00 |
WaterSystems:MainsWater | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterUse:WaterSystems:MainsWater | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water Heater:WaterSystems:Water | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:MainsWater | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
HeatRejection:Water | 13682.59 | 0.00 | 01-JAN-00:10 | 0.00 | 30-AUG-16:20 |
General:HeatRejection:Water | 13682.59 | 0.00 | 01-JAN-00:10 | 0.00 | 30-AUG-16:20 |
HeatRejection:MainsWater | 13682.59 | 0.00 | 01-JAN-00:10 | 0.00 | 30-AUG-16:20 |
General:HeatRejection:MainsWater | 13682.59 | 0.00 | 01-JAN-00:10 | 0.00 | 30-AUG-16:20 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 112722.56 | 222795.17 | 22-JAN-06:00 | 11002478.15 | 06-OCT-14:00 |
EnergyTransfer:Building | 22203.05 | 90898.28 | 22-JAN-07:50 | 1690445.12 | 30-AUG-16:00 |
EnergyTransfer:Zone:BASEMENT | 774.63 | 0.00 | 01-JAN-00:10 | 75701.56 | 13-NOV-06:10 |
Heating:EnergyTransfer | 43.26 | 0.00 | 01-JAN-00:10 | 307968.63 | 06-FEB-06:10 |
Heating:EnergyTransfer:Zone:BASEMENT | 4.38 | 0.00 | 01-JAN-00:10 | 24402.60 | 22-JUL-16:10 |
General:Heating:EnergyTransfer | 43.26 | 0.00 | 01-JAN-00:10 | 307968.63 | 06-FEB-06:10 |
General:Heating:EnergyTransfer:Zone:BASEMENT | 4.38 | 0.00 | 01-JAN-00:10 | 24402.60 | 22-JUL-16:10 |
Cooling:EnergyTransfer | 22159.79 | 90368.27 | 22-JAN-07:50 | 1690445.12 | 30-AUG-16:00 |
Cooling:EnergyTransfer:Zone:BASEMENT | 770.25 | 0.00 | 01-JAN-00:10 | 75701.56 | 13-NOV-06:10 |
General:Cooling:EnergyTransfer | 22159.79 | 90368.27 | 22-JAN-07:50 | 1690445.12 | 30-AUG-16:00 |
General:Cooling:EnergyTransfer:Zone:BASEMENT | 770.25 | 0.00 | 01-JAN-00:10 | 75701.56 | 13-NOV-06:10 |
EnergyTransfer:Zone:CORE_BOTTOM | 778.30 | 0.00 | 01-JAN-00:10 | 54974.66 | 13-NOV-10:20 |
Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 778.30 | 0.00 | 01-JAN-00:10 | 54974.66 | 13-NOV-10:20 |
General:Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 778.30 | 0.00 | 01-JAN-00:10 | 54974.66 | 13-NOV-10:20 |
EnergyTransfer:Zone:CORE_MID | 5861.03 | 0.00 | 01-JAN-00:10 | 470316.20 | 11-OCT-05:10 |
Heating:EnergyTransfer:Zone:CORE_MID | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:CORE_MID | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:CORE_MID | 5861.03 | 0.00 | 01-JAN-00:10 | 470316.20 | 11-OCT-05:10 |
General:Cooling:EnergyTransfer:Zone:CORE_MID | 5861.03 | 0.00 | 01-JAN-00:10 | 470316.20 | 11-OCT-05:10 |
EnergyTransfer:Zone:CORE_TOP | 595.08 | 0.00 | 01-JAN-00:10 | 53967.32 | 18-JUL-15:30 |
Heating:EnergyTransfer:Zone:CORE_TOP | 0.45 | 0.00 | 01-JAN-00:10 | 52617.65 | 06-FEB-05:30 |
General:Heating:EnergyTransfer:Zone:CORE_TOP | 0.45 | 0.00 | 01-JAN-00:10 | 52617.65 | 06-FEB-05:30 |
Cooling:EnergyTransfer:Zone:CORE_TOP | 594.64 | 0.00 | 01-JAN-00:10 | 53967.32 | 18-JUL-15:30 |
General:Cooling:EnergyTransfer:Zone:CORE_TOP | 594.64 | 0.00 | 01-JAN-00:10 | 53967.32 | 18-JUL-15:30 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 110.03 | 0.00 | 01-JAN-00:10 | 12193.84 | 21-AUG-14:30 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 01-JAN-00:10 | 1195.98 | 05-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 01-JAN-00:10 | 1195.98 | 05-JAN-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 110.02 | 0.00 | 01-JAN-00:10 | 12193.84 | 21-AUG-14:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 110.02 | 0.00 | 01-JAN-00:10 | 12193.84 | 21-AUG-14:30 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 91.35 | 0.00 | 01-JAN-00:10 | 12133.36 | 03-MAY-08:40 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 0.01 | 0.00 | 01-JAN-00:10 | 1364.84 | 10-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 0.01 | 0.00 | 01-JAN-00:10 | 1364.84 | 10-JAN-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 91.34 | 0.00 | 01-JAN-00:10 | 12133.36 | 03-MAY-08:40 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 91.34 | 0.00 | 01-JAN-00:10 | 12133.36 | 03-MAY-08:40 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 143.47 | 0.00 | 01-JAN-00:10 | 18520.83 | 06-NOV-13:30 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 0.01 | 0.00 | 01-JAN-00:10 | 1886.64 | 06-FEB-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 0.01 | 0.00 | 01-JAN-00:10 | 1886.64 | 06-FEB-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 143.47 | 0.00 | 01-JAN-00:10 | 18520.83 | 06-NOV-13:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 143.47 | 0.00 | 01-JAN-00:10 | 18520.83 | 06-NOV-13:30 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 131.41 | 0.00 | 01-JAN-00:10 | 17604.91 | 30-AUG-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 131.41 | 0.00 | 01-JAN-00:10 | 17604.91 | 30-AUG-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 131.41 | 0.00 | 01-JAN-00:10 | 17604.91 | 30-AUG-16:00 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 850.04 | 0.00 | 01-JAN-00:10 | 109051.10 | 21-AUG-14:30 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 8.26 | 0.00 | 01-JAN-00:10 | 84557.86 | 06-FEB-05:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 8.26 | 0.00 | 01-JAN-00:10 | 84557.86 | 06-FEB-05:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 841.79 | 0.00 | 01-JAN-00:10 | 109051.10 | 21-AUG-14:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 841.79 | 0.00 | 01-JAN-00:10 | 109051.10 | 21-AUG-14:30 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 792.66 | 0.00 | 01-JAN-00:10 | 125207.11 | 03-MAY-09:00 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 3.99 | 0.00 | 01-JAN-00:10 | 49626.29 | 06-FEB-05:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 3.99 | 0.00 | 01-JAN-00:10 | 49626.29 | 06-FEB-05:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 788.67 | 0.00 | 01-JAN-00:10 | 125207.11 | 03-MAY-09:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 788.67 | 0.00 | 01-JAN-00:10 | 125207.11 | 03-MAY-09:00 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 1211.22 | 0.00 | 01-JAN-00:10 | 181238.85 | 06-NOV-13:50 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 2.52 | 0.00 | 01-JAN-00:10 | 45252.91 | 21-DEC-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 2.52 | 0.00 | 01-JAN-00:10 | 45252.91 | 21-DEC-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 1208.71 | 0.00 | 01-JAN-00:10 | 181238.85 | 06-NOV-13:50 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 1208.71 | 0.00 | 01-JAN-00:10 | 181238.85 | 06-NOV-13:50 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 839.34 | 0.00 | 01-JAN-00:10 | 145624.93 | 30-AUG-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 2.30 | 0.00 | 01-JAN-00:10 | 32735.26 | 06-FEB-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 2.30 | 0.00 | 01-JAN-00:10 | 32735.26 | 06-FEB-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 837.04 | 0.00 | 01-JAN-00:10 | 145624.93 | 30-AUG-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 837.04 | 0.00 | 01-JAN-00:10 | 145624.93 | 30-AUG-16:00 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 89.72 | 0.00 | 01-JAN-00:10 | 14485.49 | 06-FEB-05:30 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 3.60 | 0.00 | 01-JAN-00:10 | 14485.49 | 06-FEB-05:30 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 3.60 | 0.00 | 01-JAN-00:10 | 14485.49 | 06-FEB-05:30 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 86.12 | 0.00 | 01-JAN-00:10 | 11935.05 | 21-AUG-14:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 86.12 | 0.00 | 01-JAN-00:10 | 11935.05 | 21-AUG-14:30 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 82.46 | 0.00 | 01-JAN-00:10 | 12776.32 | 03-MAY-09:30 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 1.64 | 0.00 | 01-JAN-00:10 | 10953.11 | 06-FEB-05:40 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 1.64 | 0.00 | 01-JAN-00:10 | 10953.11 | 06-FEB-05:40 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 80.82 | 0.00 | 01-JAN-00:10 | 12776.32 | 03-MAY-09:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 80.82 | 0.00 | 01-JAN-00:10 | 12776.32 | 03-MAY-09:30 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 123.83 | 0.00 | 01-JAN-00:10 | 19295.51 | 06-NOV-13:50 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 1.59 | 0.00 | 01-JAN-00:10 | 14251.72 | 06-FEB-05:30 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 1.59 | 0.00 | 01-JAN-00:10 | 14251.72 | 06-FEB-05:30 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 122.24 | 0.00 | 01-JAN-00:10 | 19295.51 | 06-NOV-13:50 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 122.24 | 0.00 | 01-JAN-00:10 | 19295.51 | 06-NOV-13:50 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 86.92 | 0.00 | 01-JAN-00:10 | 15296.20 | 30-AUG-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 1.20 | 0.00 | 01-JAN-00:10 | 8875.13 | 06-FEB-05:30 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 1.20 | 0.00 | 01-JAN-00:10 | 8875.13 | 06-FEB-05:30 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 85.72 | 0.00 | 01-JAN-00:10 | 15296.20 | 30-AUG-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 85.72 | 0.00 | 01-JAN-00:10 | 15296.20 | 30-AUG-16:00 |
EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 92.79 | 0.00 | 01-JAN-00:10 | 9075.08 | 10-OCT-13:50 |
Heating:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 0.71 | 0.00 | 01-JAN-00:10 | 3069.70 | 12-MAR-14:20 |
General:Heating:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 0.71 | 0.00 | 01-JAN-00:10 | 3069.70 | 12-MAR-14:20 |
Cooling:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 92.08 | 0.00 | 01-JAN-00:10 | 9075.08 | 10-OCT-13:50 |
General:Cooling:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 92.08 | 0.00 | 01-JAN-00:10 | 9075.08 | 10-OCT-13:50 |
EnergyTransfer:Zone:MIDFLOOR_PLENUM | 675.85 | 0.00 | 01-JAN-00:10 | 73331.38 | 10-OCT-15:30 |
Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 6.86 | 0.00 | 01-JAN-00:10 | 21968.00 | 19-FEB-11:50 |
General:Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 6.86 | 0.00 | 01-JAN-00:10 | 21968.00 | 19-FEB-11:50 |
Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 668.98 | 0.00 | 01-JAN-00:10 | 73331.38 | 10-OCT-15:30 |
General:Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 668.98 | 0.00 | 01-JAN-00:10 | 73331.38 | 10-OCT-15:30 |
EnergyTransfer:Zone:TOPFLOOR_PLENUM | 110.94 | 0.00 | 01-JAN-00:10 | 19736.76 | 07-JUL-14:40 |
Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 5.58 | 0.00 | 01-JAN-00:10 | 18952.72 | 06-FEB-06:20 |
General:Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 5.58 | 0.00 | 01-JAN-00:10 | 18952.72 | 06-FEB-06:20 |
Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 105.35 | 0.00 | 01-JAN-00:10 | 19736.76 | 07-JUL-14:40 |
General:Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 105.35 | 0.00 | 01-JAN-00:10 | 19736.76 | 07-JUL-14:40 |
EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 142.87 | 907.63 | 10-JAN-07:00 | 7998.24 | 16-APR-18:10 |
Heating:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 142.87 | 907.63 | 10-JAN-07:00 | 7998.24 | 16-APR-18:10 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 142.87 | 907.63 | 10-JAN-07:00 | 7998.24 | 16-APR-18:10 |
EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 1300.86 | 1358.36 | 10-JAN-06:20 | 75484.79 | 15-DEC-17:00 |
Heating:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 1300.86 | 1358.36 | 10-JAN-06:20 | 75484.79 | 15-DEC-17:00 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 1300.86 | 1358.36 | 10-JAN-06:20 | 75484.79 | 15-DEC-17:00 |
EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 126.93 | 5.17 | 24-JAN-00:10 | 7620.38 | 15-DEC-17:00 |
Heating:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 0.17 | 0.00 | 01-JAN-00:10 | 545.13 | 10-JAN-04:20 |
General:Heating:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 0.17 | 0.00 | 01-JAN-00:10 | 545.13 | 10-JAN-04:20 |
Cooling:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 126.77 | 0.00 | 04-JAN-03:00 | 7620.38 | 15-DEC-17:00 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 126.77 | 0.00 | 04-JAN-03:00 | 7620.38 | 15-DEC-17:00 |
EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 7191.30 | 87932.14 | 22-JAN-06:00 | 370704.29 | 03-AUG-21:10 |
Heating:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 7191.30 | 87932.14 | 22-JAN-06:00 | 370704.29 | 03-AUG-21:10 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 7191.30 | 87932.14 | 22-JAN-06:00 | 370704.29 | 03-AUG-21:10 |
PlantLoopHeatingDemand:Facility | 437.95 | 0.00 | 01-JAN-00:10 | 607667.97 | 21-DEC-07:10 |
PlantLoopHeatingDemand:Plant | 321.87 | 0.00 | 01-JAN-00:10 | 40639.52 | 23-JAN-12:30 |
WaterSystems:PlantLoopHeatingDemand | 321.87 | 0.00 | 01-JAN-00:10 | 40639.52 | 23-JAN-12:30 |
General:WaterSystems:PlantLoopHeatingDemand | 321.87 | 0.00 | 01-JAN-00:10 | 40639.52 | 23-JAN-12:30 |
EnergyTransfer:HVAC | 31809.13 | 131574.10 | 22-JAN-07:50 | 3206494.46 | 07-AUG-13:00 |
HeatingCoils:EnergyTransfer | 116.08 | 0.00 | 01-JAN-00:10 | 594434.81 | 21-DEC-07:10 |
PlantLoopHeatingDemand:HVAC | 116.08 | 0.00 | 01-JAN-00:10 | 594434.81 | 21-DEC-07:10 |
HeatingCoils:PlantLoopHeatingDemand | 116.08 | 0.00 | 01-JAN-00:10 | 594434.81 | 21-DEC-07:10 |
CoolingCoils:EnergyTransfer | 27589.55 | 118404.63 | 05-JAN-08:00 | 2624854.57 | 07-AUG-14:50 |
HeatRecoveryForHeating:EnergyTransfer | 103.07 | 0.00 | 01-JAN-00:10 | 443828.80 | 20-DEC-08:00 |
HeatRecoveryForCooling:EnergyTransfer | 4000.43 | 0.00 | 01-JAN-00:10 | 923470.75 | 07-OCT-08:00 |
EnergyTransfer:Plant | 58710.38 | 0.00 | 01-JAN-00:10 | 6663247.79 | 07-AUG-14:50 |
LoopToLoop:EnergyTransfer | 18576.33 | 0.00 | 01-JAN-00:10 | 2107851.29 | 07-AUG-14:50 |
WaterSystems:EnergyTransfer | 321.87 | 0.00 | 01-JAN-00:10 | 40639.52 | 23-JAN-12:30 |
WaterUse:WaterSystems:EnergyTransfer | 321.87 | 0.00 | 01-JAN-00:10 | 40639.52 | 23-JAN-12:30 |
Boilers:EnergyTransfer | 114.85 | 0.00 | 01-JAN-00:10 | 638466.46 | 21-DEC-07:10 |
Chillers:EnergyTransfer | 18465.80 | 0.00 | 01-JAN-00:10 | 2183630.23 | 31-JUL-10:50 |
HeatRejection:EnergyTransfer | 21231.54 | 0.00 | 01-JAN-00:10 | 2496410.47 | 31-JUL-10:50 |
General:HeatRejection:EnergyTransfer | 21231.54 | 0.00 | 01-JAN-00:10 | 2496410.47 | 31-JUL-10:50 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 08:44:04
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
BASEMENT | 0.000 | 0.000 | 4.381 | -770.253 | 0.000 | 0.000 | 92.670 | 262.844 | 424.397 | 0.000 | 0.000 | 0.000 | 0.003 | 0.000 | 0.000 | 0.000 | 0.000 | -14.039 |
CORE_BOTTOM | 0.000 | 0.000 | 0.000 | -778.296 | 0.000 | 0.000 | 83.513 | 236.053 | 289.614 | 0.000 | 0.000 | 0.000 | 169.116 | 0.000 | 0.000 | 0.000 | 0.000 | -0.002 |
CORE_MID | 0.000 | 0.000 | 0.000 | -5861.014 | 0.000 | 0.000 | 841.206 | 2360.527 | 2896.128 | 0.000 | 0.000 | 0.000 | 0.014 | 0.000 | 0.000 | 0.000 | 0.000 | -236.848 |
CORE_TOP | 0.000 | 0.000 | 0.447 | -594.634 | 0.000 | 0.000 | 85.385 | 236.053 | 289.613 | 0.000 | 0.000 | 0.000 | 0.001 | 0.000 | 0.000 | 0.000 | 0.000 | -16.864 |
PERIMETER_BOT_ZN_3 | 0.000 | 0.000 | 0.002 | -110.022 | 0.000 | 0.000 | 10.608 | 17.294 | 36.365 | 41.802 | 0.000 | 0.403 | 41.494 | 0.000 | -36.183 | 0.000 | -1.763 | 0.000 |
PERIMETER_BOT_ZN_2 | 0.000 | 0.000 | 0.008 | -91.340 | 0.000 | 0.000 | 6.842 | 11.042 | 23.435 | 60.796 | 0.000 | 0.290 | 11.451 | 0.000 | -21.376 | 0.000 | -1.148 | -0.000 |
PERIMETER_BOT_ZN_1 | 0.000 | 0.000 | 0.009 | -143.464 | 0.000 | 0.000 | 10.529 | 16.966 | 36.366 | 104.469 | 0.000 | 0.385 | 10.465 | 0.000 | -33.846 | 0.000 | -1.879 | -0.002 |
PERIMETER_BOT_ZN_4 | 0.000 | 0.000 | 0.000 | -131.412 | 0.000 | 0.000 | 6.789 | 11.058 | 23.435 | 57.883 | 0.000 | 0.241 | 60.981 | 0.000 | -27.574 | 0.000 | -1.401 | 0.000 |
PERIMETER_MID_ZN_3 | 0.000 | 0.000 | 8.258 | -841.762 | 0.000 | 0.000 | 108.715 | 172.427 | 363.654 | 432.435 | 0.000 | 9.045 | 100.832 | 0.000 | -318.198 | 0.000 | -35.405 | 0.000 |
PERIMETER_MID_ZN_2 | 0.000 | 0.000 | 3.990 | -788.651 | 0.000 | 0.000 | 51.183 | 110.205 | 234.352 | 606.845 | 0.000 | 5.810 | 1.953 | 0.000 | -200.745 | 0.000 | -24.942 | -0.004 |
PERIMETER_MID_ZN_1 | 0.000 | 0.000 | 2.516 | -1208.680 | 0.000 | 0.000 | 105.934 | 169.408 | 363.660 | 1041.877 | 0.000 | 8.240 | 0.048 | 0.000 | -324.778 | 0.000 | -42.280 | -115.897 |
PERIMETER_MID_ZN_4 | 0.000 | 0.000 | 2.303 | -837.018 | 0.000 | 0.000 | 69.926 | 110.301 | 234.351 | 596.838 | 0.000 | 5.668 | 71.198 | 0.000 | -226.787 | 0.000 | -26.779 | -0.003 |
PERIMETER_TOP_ZN_3 | 0.000 | 0.000 | 3.598 | -86.117 | 0.000 | 0.000 | 10.968 | 17.240 | 36.365 | 43.006 | 0.000 | 1.060 | 8.155 | 0.000 | -30.177 | 0.000 | -4.099 | 0.000 |
PERIMETER_TOP_ZN_2 | 0.000 | 0.000 | 1.642 | -80.816 | 0.000 | 0.000 | 6.999 | 11.020 | 23.435 | 60.518 | 0.000 | 0.683 | 0.002 | 0.000 | -19.237 | 0.000 | -2.912 | -1.332 |
PERIMETER_TOP_ZN_1 | 0.000 | 0.000 | 1.589 | -122.233 | 0.000 | 0.000 | 10.682 | 16.940 | 36.366 | 103.925 | 0.000 | 0.979 | 0.000 | 0.000 | -31.032 | 0.000 | -4.945 | -12.271 |
PERIMETER_TOP_ZN_4 | 0.000 | 0.000 | 1.197 | -85.719 | 0.000 | 0.000 | 7.057 | 11.029 | 23.435 | 59.451 | 0.000 | 0.687 | 7.745 | 0.000 | -21.731 | 0.000 | -3.152 | -0.000 |
DATACENTER_BOT_ZN_6 | 0.000 | 0.000 | 0.000 | -142.873 | 0.000 | 0.000 | 0.949 | 6.628 | 153.881 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -18.585 |
DATACENTER_MID_ZN_6 | 0.000 | 0.000 | 0.000 | -1300.860 | 0.000 | 0.000 | 9.493 | 66.280 | 1538.806 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -313.719 |
DATACENTER_TOP_ZN_6 | 0.000 | 0.000 | 0.165 | -126.769 | 0.000 | 0.000 | 0.950 | 6.628 | 153.881 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -34.855 |
DATACENTER_BASEMENT_ZN_6 | 0.000 | 0.000 | 0.000 | -7191.315 | 0.000 | 0.000 | 20.116 | 74.111 | 7494.857 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -397.769 |
GROUNDFLOOR_PLENUM | 0.710 | -92.084 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.689 | 94.708 | 0.000 | 0.000 | 0.000 | -4.022 | 0.000 |
MIDFLOOR_PLENUM | 6.863 | -668.972 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 12.824 | 715.688 | 0.000 | 0.000 | 0.000 | -66.404 | 0.000 |
TOPFLOOR_PLENUM | 5.582 | -105.352 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.143 | 105.457 | 0.000 | 0.000 | 0.000 | -6.831 | 0.000 |
Total Facility | 13.155 | -866.408 | 30.104 | -21293.248 | 0.000 | 0.000 | 1540.514 | 3924.054 | 14676.396 | 3209.845 | 0.000 | 48.148 | 1399.310 | 0.000 | -1291.665 | 0.000 | -227.962 | -1162.188 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | 20-MAR-04:11 | 0.00 | 0.00 | 0.00 | -127724.92 | 0.00 | 0.00 | 0.00 | 2550.13 | 13457.54 | 0.00 | 0.00 | 0.00 | 111717.24 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 02-OCT-04:13 | 0.00 | 0.00 | 0.00 | -101060.30 | 0.00 | 0.00 | 0.00 | 2290.20 | 5937.65 | 0.00 | 0.00 | 0.00 | 92832.46 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 18-MAY-04:13 | 0.00 | 0.00 | 0.00 | -875685.53 | 0.00 | 0.00 | 0.00 | 22901.98 | 59376.23 | 0.00 | 0.00 | 0.00 | 793407.32 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 31-MAY-04:13 | 0.00 | 0.00 | 0.00 | -89513.58 | 0.00 | 0.00 | 0.00 | 2290.20 | 5937.62 | 0.00 | 0.00 | 0.00 | 81285.76 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 25-JUN-16:41 | 0.00 | 0.00 | 0.00 | -17669.83 | 0.00 | 0.00 | 42.43 | 68.40 | 720.18 | 5402.85 | 0.00 | 50.47 | 11385.50 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 10-SEP-09:31 | 0.00 | 0.00 | 0.00 | -21272.18 | 0.00 | 0.00 | 21.35 | 44.08 | 464.11 | 13628.76 | 0.00 | 88.96 | 7024.92 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 01-JAN-13:51 | 0.00 | 0.00 | 0.00 | -25848.95 | 0.00 | 0.00 | 30.66 | 68.40 | 720.19 | 21613.69 | 0.00 | 0.00 | 3452.82 | 0.00 | -0.00 | 0.00 | -36.82 | 0.00 |
PERIMETER_BOT_ZN_4 | 25-JUN-16:01 | 0.00 | 0.00 | 0.00 | -27037.59 | 0.00 | 0.00 | 19.45 | 44.08 | 464.11 | 12601.92 | 0.00 | 18.87 | 13889.16 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 11-JUN-17:21 | 0.00 | 0.00 | 0.00 | -163733.68 | 0.00 | 0.00 | 0.00 | 684.02 | 5591.71 | 58143.79 | 0.00 | 2448.55 | 96865.62 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 07-MAY-10:02 | 0.00 | 0.00 | 0.00 | -217122.47 | 0.00 | 0.00 | 216.96 | 440.81 | 4641.14 | 110761.63 | 0.00 | 822.20 | 100239.73 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 15-OCT-13:31 | 0.00 | 0.00 | 0.00 | -237632.35 | 0.00 | 0.00 | 333.48 | 684.04 | 7201.95 | 165944.21 | 0.00 | 585.65 | 62883.03 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 11-JUN-17:21 | 0.00 | 0.00 | 0.00 | -238106.95 | 0.00 | 0.00 | 0.00 | 440.81 | 3603.49 | 114558.63 | 0.00 | 1049.04 | 118454.98 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 11-JUN-17:21 | 0.00 | 0.00 | 0.00 | -18913.95 | 0.00 | 0.00 | 0.00 | 68.40 | 559.17 | 5558.21 | 0.00 | 267.15 | 12461.01 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 23-JUL-10:11 | 0.00 | 0.00 | 0.00 | -22631.37 | 0.00 | 0.00 | 20.50 | 44.08 | 464.11 | 10801.01 | 0.00 | 9.09 | 11292.58 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 10-DEC-14:11 | 0.00 | 0.00 | 0.00 | -27116.88 | 0.00 | 0.00 | 30.06 | 68.40 | 720.19 | 20556.56 | 0.00 | 0.00 | 5874.23 | 0.00 | -0.00 | 0.00 | -132.57 | 0.00 |
PERIMETER_TOP_ZN_4 | 11-JUN-17:21 | 0.00 | 0.00 | 0.00 | -25461.27 | 0.00 | 0.00 | 0.00 | 44.08 | 360.35 | 11329.83 | 0.00 | 116.23 | 13610.78 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 16-APR-18:05 | 0.00 | 0.00 | 0.00 | -7998.19 | 0.00 | 0.00 | 0.00 | 32.15 | 7794.42 | 0.00 | 0.00 | 0.00 | 171.61 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 15-DEC-17:00 | 0.00 | 0.00 | 0.00 | -75484.54 | 0.00 | 0.00 | 1008.50 | 5787.18 | 77944.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -9255.37 |
DATACENTER_TOP_ZN_6 | 15-DEC-17:00 | 0.00 | 0.00 | 0.00 | -7620.36 | 0.00 | 0.00 | 100.85 | 578.72 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -853.63 |
DATACENTER_BASEMENT_ZN_6 | 09-AUG-21:02 | 0.00 | 0.00 | 0.00 | -371849.83 | 0.00 | 0.00 | 110.24 | 719.03 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -8611.96 |
GROUNDFLOOR_PLENUM | 31-MAY-05:02 | 0.00 | -11684.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11691.03 | 0.00 | -0.00 | 0.00 | -6.20 | 0.00 |
MIDFLOOR_PLENUM | 21-JUL-05:02 | 0.00 | -97499.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.17 | 97485.26 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 07-JUL-14:40 | 0.00 | -19736.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 117.05 | 19619.09 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 16-AUG-05:02 | 0.00 | -15054.41 | 0.00 | -2008652.62 | 0.00 | 0.00 | 16004.34 | 42872.09 | 616289.16 | 0.00 | 0.00 | 16.27 | 1370422.50 | 0.00 | -20832.93 | 0.00 | -1064.39 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | 22-JUL-16:01 | 0.00 | 0.00 | 26078.77 | 0.00 | 0.00 | 0.00 | 520.12 | 1274.92 | 13457.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -41331.36 |
CORE_BOTTOM | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 06-FEB-05:21 | 0.00 | 0.00 | 58954.33 | 0.00 | 0.00 | 0.00 | 0.00 | 2290.20 | 5937.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -67182.15 |
PERIMETER_BOT_ZN_3 | 05-JAN-06:01 | 0.00 | 0.00 | 4119.36 | 0.00 | 0.00 | 0.00 | 141.99 | 287.56 | 960.25 | 0.00 | 0.00 | 0.00 | 1118.37 | 0.00 | -6547.17 | 0.00 | -80.36 | 0.00 |
PERIMETER_BOT_ZN_2 | 05-JAN-06:01 | 0.00 | 0.00 | 2562.04 | 0.00 | 0.00 | 0.00 | 91.93 | 185.31 | 618.82 | 0.00 | 0.00 | 0.00 | 946.41 | 0.00 | -4351.23 | 0.00 | -53.28 | 0.00 |
PERIMETER_BOT_ZN_1 | 06-FEB-06:01 | 0.00 | 0.00 | 6449.15 | 0.00 | 0.00 | 0.00 | 143.39 | 287.56 | 960.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -5295.93 | 0.00 | -52.16 | -2492.27 |
PERIMETER_BOT_ZN_4 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 06-FEB-05:11 | 0.00 | 0.00 | 129206.65 | 0.00 | 0.00 | 0.00 | 0.00 | 2875.57 | 7455.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -46341.74 | 0.00 | -4322.86 | -88873.24 |
PERIMETER_MID_ZN_2 | 06-FEB-05:11 | 0.00 | 0.00 | 101714.50 | 0.00 | 0.00 | 0.00 | 0.00 | 1853.13 | 4804.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -31905.69 | 0.00 | -2990.00 | -73476.61 |
PERIMETER_MID_ZN_1 | 10-JAN-05:01 | 0.00 | 0.00 | 128524.59 | 0.00 | 0.00 | 0.00 | 0.00 | 2875.64 | 7455.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -59044.95 | 0.00 | -8824.26 | -70986.74 |
PERIMETER_MID_ZN_4 | 10-JAN-05:01 | 0.00 | 0.00 | 87337.87 | 0.00 | 0.00 | 0.00 | 0.00 | 1853.13 | 4804.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -38364.36 | 0.00 | -5730.29 | -49900.99 |
PERIMETER_TOP_ZN_3 | 05-FEB-08:33 | 0.00 | 0.00 | 16216.93 | 0.00 | 0.00 | 0.00 | 88.77 | 75.04 | 720.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3997.55 | 0.00 | -2010.78 | -11092.59 |
PERIMETER_TOP_ZN_2 | 06-FEB-05:21 | 0.00 | 0.00 | 14115.35 | 0.00 | 0.00 | 0.00 | 0.00 | 185.31 | 480.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2545.51 | 0.00 | -307.29 | -11928.34 |
PERIMETER_TOP_ZN_1 | 06-FEB-05:21 | 0.00 | 0.00 | 18575.13 | 0.00 | 0.00 | 0.00 | 0.00 | 287.56 | 745.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3934.50 | 0.00 | -470.32 | -15203.45 |
PERIMETER_TOP_ZN_4 | 06-FEB-05:21 | 0.00 | 0.00 | 13690.54 | 0.00 | 0.00 | 0.00 | 0.00 | 185.31 | 480.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2751.73 | 0.00 | -319.05 | -11285.53 |
DATACENTER_BOT_ZN_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 10-JAN-04:20 | 0.00 | 0.00 | 545.13 | 0.00 | 0.00 | 0.00 | 0.00 | 32.15 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -2525.88 |
DATACENTER_BASEMENT_ZN_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 28-DEC-05:11 | 11354.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -403.97 | -10950.85 |
MIDFLOOR_PLENUM | 26-FEB-16:21 | 68670.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 71.11 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -68742.07 |
TOPFLOOR_PLENUM | 06-FEB-06:12 | 20295.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -179.75 | -20116.23 |
Total Facility | 06-FEB-06:01 | -615308.21 | 594407.39 | 526041.36 | -594407.39 | 0.00 | 0.00 | 20002.92 | 42872.09 | 379706.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -203011.52 | 0.00 | -6916.66 | -143386.34 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 08:44:04
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
VAV_BOT WITH REHEAT | 10.9814 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 9.7894 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_MID WITH REHEAT | 103.3970 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 90.9353 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_TOP WITH REHEAT | 10.5903 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 9.9084 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
CAV_BAS | 6.1303 | 0.0000 | 149.6021 | 1.0000 | Calculated from schedules | 1.2002 | 6.1303 | 0.1958 | 1.0000 | Not calculated | 1.2002 | 0.1958 | ||
AIRLOOP DATACENTER BASEMENT | 21.4384 | 0.0000 | 42.1814 | 1.0000 | Calculated from schedules | 0.3384 | 21.4385 | 0.0158 | 1.0000 | Not calculated | 0.3384 | 0.0158 | ||
AIRLOOP DATACENTER BOT | 0.4802 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.4802 | 0.0326 | 1.0000 | Not calculated | 0.0156 | 0.0326 | ||
AIRLOOP DATACENTER MID | 4.5742 | 0.0000 | 19.4861 | 1.0000 | Calculated from schedules | 0.1563 | 4.5742 | 0.0342 | 1.0000 | Not calculated | 0.1563 | 0.0342 | ||
AIRLOOP DATACENTER TOP | 0.4661 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.4661 | 0.0335 | 1.0000 | Not calculated | 0.0156 | 0.0335 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
VAV_BOT WITH REHEAT | 5.4907 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 2.9395 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_MID WITH REHEAT | 51.6985 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 28.5136 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_TOP WITH REHEAT | 5.2951 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 2.9487 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
CAV_BAS | 6.1303 | 0.0000 | 149.6021 | 1.0000 | Calculated from schedules | 1.2002 | 6.1303 | 1.0000 | 1.0000 | Not calculated | 1.2002 | 0.1958 | ||
AIRLOOP DATACENTER BASEMENT | 21.4384 | 0.0000 | 42.1814 | 1.0000 | Calculated from schedules | 0.3384 | 21.4384 | 1.0000 | 1.0000 | Not calculated | 0.3384 | 0.0158 | ||
AIRLOOP DATACENTER BOT | 0.4802 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.4802 | 1.0000 | 1.0000 | Not calculated | 0.0156 | 0.0326 | ||
AIRLOOP DATACENTER MID | 4.5742 | 0.0000 | 19.4861 | 1.0000 | Calculated from schedules | 0.1563 | 4.5742 | 1.0000 | 1.0000 | Not calculated | 0.1563 | 0.0342 | ||
AIRLOOP DATACENTER TOP | 0.4661 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.4661 | 1.0000 | 1.0000 | Not calculated | 0.0156 | 0.0335 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
BASEMENT | CAV_BAS | 0.000000 | 149.6021 | 0.000432 | 2779.43 | 1.2002 | 1.0000 | 1.2002 | 1.000 | 1.2002 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | 0.000000 | 134.3532 | 0.000432 | 2496.12 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_MID | VAV_MID WITH REHEAT | 0.000000 | 1343.5320 | 0.000432 | 24961.20 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_TOP | VAV_TOP WITH REHEAT | 0.000000 | 134.3532 | 0.000432 | 2496.12 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | 0.000000 | 16.8694 | 0.000432 | 313.41 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | 0.000000 | 16.8698 | 0.000432 | 313.42 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | 0.000000 | 168.6939 | 0.000432 | 3134.13 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | 0.000000 | 108.7127 | 0.000432 | 2019.75 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | 0.000000 | 168.6975 | 0.000432 | 3134.20 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | 0.000000 | 108.7127 | 0.000432 | 2019.75 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | 0.000000 | 16.8694 | 0.000432 | 313.41 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | 0.000000 | 16.8698 | 0.000432 | 313.42 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | 0.000000 | 1.9486 | 0.000432 | 36.20 | 0.0156 | 1.0000 | 0.0156 | 1.000 | 0.0156 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | 0.000000 | 19.4861 | 0.000432 | 362.03 | 0.1563 | 1.0000 | 0.1563 | 1.000 | 0.1563 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | 0.000000 | 1.9486 | 0.000432 | 36.20 | 0.0156 | 1.0000 | 0.0156 | 1.000 | 0.0156 |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | 0.000000 | 42.1814 | 0.000432 | 783.68 | 0.3384 | 1.0000 | 0.3384 | 1.000 | 0.3384 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
VAV_BOT WITH REHEAT | 0.00 | 0.000432 | 3526.9033 | 0.0000 | 0.0000 | 0.0000 | |
VAV_MID WITH REHEAT | 0.00 | 0.000432 | 35269.0328 | 0.0000 | 0.0000 | 0.0000 | |
VAV_TOP WITH REHEAT | 0.00 | 0.000432 | 3526.9033 | 0.0000 | 0.0000 | 0.0000 | |
CAV_BAS | 0.000000 | 149.60 | 0.000432 | 2779.4266 | 1.2002 | 1.2002 | 1.2002 |
AIRLOOP DATACENTER BASEMENT | 0.000000 | 42.18 | 0.000432 | 783.6794 | 0.3384 | 0.3384 | 0.3384 |
AIRLOOP DATACENTER BOT | 0.000000 | 1.95 | 0.000432 | 36.2027 | 0.0156 | 0.0156 | 0.0156 |
AIRLOOP DATACENTER MID | 0.000000 | 19.49 | 0.000432 | 362.0274 | 0.1563 | 0.1563 | 0.1563 |
AIRLOOP DATACENTER TOP | 0.000000 | 1.95 | 0.000432 | 36.2027 | 0.0156 | 0.0156 | 0.0156 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | CAV_BAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 6.1303 | 6.1303 | 6.1303 | No | 1.2002 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 6.1780 | 6.1780 | 1.9399 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 58.0526 | 58.0526 | 18.9832 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 5.7322 | 5.7322 | 1.9489 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.0249 | 1.0249 | 0.2439 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.1154 | 1.1154 | 0.2231 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.2666 | 1.2666 | 0.2533 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.3964 | 1.3964 | 0.2793 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 9.6160 | 9.6160 | 2.3848 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 11.4701 | 11.4701 | 2.2940 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 12.0822 | 12.0822 | 2.4164 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 12.1761 | 12.1761 | 2.4352 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.0814 | 1.0814 | 0.2444 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.1612 | 1.1612 | 0.2322 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.3197 | 1.3197 | 0.2639 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.2958 | 1.2958 | 0.2592 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.4802 | 0.4802 | 0.4802 | No | 0.0156 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 4.5742 | 4.5742 | 4.5742 | No | 0.1563 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.4661 | 0.4661 | 0.4661 | No | 0.0156 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 21.4384 | 21.4384 | 21.4384 | No | 0.3384 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
VAV_BOT WITH REHEAT | 10.9814 | 9.7894 | 10.9814 | 2.9395 | 0.0000 | 1.0000 |
VAV_MID WITH REHEAT | 103.3970 | 90.9353 | 103.3970 | 28.5136 | 0.0000 | 1.0000 |
VAV_TOP WITH REHEAT | 10.5903 | 9.9084 | 10.5903 | 2.9487 | 0.0000 | 1.0000 |
CAV_BAS | 6.1303 | 6.1303 | 6.1303 | 6.1303 | 1.2002 | 1.0000 |
AIRLOOP DATACENTER BASEMENT | 21.4384 | 21.4385 | 21.4384 | 21.4384 | 0.3384 | 1.0000 |
AIRLOOP DATACENTER BOT | 0.4802 | 0.4802 | 0.4802 | 0.4802 | 0.0156 | 1.0000 |
AIRLOOP DATACENTER MID | 4.5742 | 4.5742 | 4.5742 | 4.5742 | 0.1563 | 1.0000 |
AIRLOOP DATACENTER TOP | 0.4661 | 0.4661 | 0.4661 | 0.4661 | 0.0156 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | CAV_BAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 6.1303 | 6.1303 | 6.1303 | No | 1.2002 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 3.0890 | 3.0890 | 1.9399 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 29.0263 | 29.0263 | 18.9832 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.8661 | 2.8661 | 1.9489 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5125 | 0.5125 | 0.2439 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5577 | 0.5577 | 0.2231 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6333 | 0.6333 | 0.2533 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6982 | 0.6982 | 0.2793 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 4.8080 | 4.8080 | 2.3848 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 5.7350 | 5.7350 | 2.2940 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 6.0411 | 6.0411 | 2.4164 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 6.0880 | 6.0880 | 2.4352 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5407 | 0.5407 | 0.2444 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5806 | 0.5806 | 0.2322 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6599 | 0.6599 | 0.2639 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6479 | 0.6479 | 0.2592 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.4802 | 0.4802 | 0.4802 | No | 0.0156 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 4.5742 | 4.5742 | 4.5742 | No | 0.1563 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.4661 | 0.4661 | 0.4661 | No | 0.0156 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 21.4384 | 21.4384 | 21.4384 | No | 0.3384 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
VAV_BOT WITH REHEAT | 5.4907 | 2.9395 | 2.9395 | 2.9395 | 0.0000 | 1.0000 |
VAV_MID WITH REHEAT | 51.6985 | 28.5136 | 28.5136 | 28.5136 | 0.0000 | 1.0000 |
VAV_TOP WITH REHEAT | 5.2951 | 2.9487 | 2.9487 | 2.9487 | 0.0000 | 1.0000 |
CAV_BAS | 6.1303 | 6.1303 | 6.1303 | 6.1303 | 1.2002 | 1.0000 |
AIRLOOP DATACENTER BASEMENT | 21.4384 | 21.4384 | 21.4384 | 21.4384 | 0.3384 | 1.0000 |
AIRLOOP DATACENTER BOT | 0.4802 | 0.4802 | 0.4802 | 0.4802 | 0.0156 | 1.0000 |
AIRLOOP DATACENTER MID | 4.5742 | 4.5742 | 4.5742 | 4.5742 | 0.1563 | 1.0000 |
AIRLOOP DATACENTER TOP | 0.4661 | 0.4661 | 0.4661 | 0.4661 | 0.0156 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 08:44:04
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Tampa-MacDill AFB FL USA TMY3 WMO#=747880 |
Total gross floor area [m2] | 46320.38 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
BASEMENT | 2779.43 | 2779.43 | 0.00 | 113.98 |
CORE_BOTTOM | 2496.12 | 2496.12 | 0.00 | 113.98 |
CORE_MID | 2496.12 | 2496.12 | 0.00 | 113.98 |
CORE_TOP | 2496.12 | 2496.12 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_3 | 313.41 | 313.41 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_2 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_1 | 313.42 | 313.42 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_4 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_MID_ZN_3 | 313.41 | 313.41 | 0.00 | 113.98 |
PERIMETER_MID_ZN_2 | 201.98 | 201.98 | 0.00 | 96.54 |
PERIMETER_MID_ZN_1 | 313.42 | 313.42 | 0.00 | 113.98 |
PERIMETER_MID_ZN_4 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_3 | 313.41 | 313.41 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_2 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_1 | 313.42 | 313.42 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_4 | 201.98 | 201.98 | 0.00 | 113.98 |
DATACENTER_BOT_ZN_6 | 36.20 | 36.20 | 0.00 | 113.98 |
DATACENTER_MID_ZN_6 | 36.20 | 36.20 | 0.00 | 113.98 |
DATACENTER_TOP_ZN_6 | 36.20 | 36.20 | 0.00 | 113.98 |
DATACENTER_BASEMENT_ZN_6 | 783.68 | 783.68 | 0.00 | 113.98 |
GROUNDFLOOR_PLENUM | 3563.11 | 3563.11 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 3563.11 | 3563.11 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 3563.11 | 3563.11 | 0.00 | 0.00 |
Totals | 46320.38 | 46320.38 | 0.00 |
Data | |
Number of hours heating loads not met | 1.50 |
Number of hours cooling loads not met | 736.00 |
Number of hours not met | 737.50 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler | 0.00 | 0.00 | 162.14 | 763980.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 5755.20 | 487572.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 3924.05 | 385834.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 695.49 | 57580.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 5334.97 | 305206.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- DataCenterPlugLoads | 9341.42 | 473165.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Transformer | 80.17 | 5057.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLift | 1848.78 | 113101.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLightsFan | 5.83 | 376.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 2185.95 | 151679.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 815.95 | 66193.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- General | 1977.79 | 95997.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- General | 1.55 | 4288.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- General | 65.40 | 5613.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 0.00 | 0.00 | 672.16 | 75833.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 14676.40 | 32032.57 |
Natural Gas | 0.00 | 834.30 |
Additional | 0.00 | 0.00 |
Total | 14676.40 | 32866.87 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 84.72 |
Space Heating | 0.00 |
Space Cooling | 124.25 |
Fans (All) | 47.19 |
Service Water Heating | 0.00 |
Receptacle Equipment | 316.85 |
Miscellaneous (All) | 691.54 |
Subtotal | 691.54 |
Natural Gas [MJ/m2] | |
Space Heating | 3.50 |
Service Water Heating | 14.51 |
Miscellaneous (All) | 18.01 |
Subtotal | 18.01 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 11.94 |
Space Heating | 0.49 |
Space Cooling | 17.51 |
Fans (All) | 6.65 |
Service Water Heating | 2.05 |
Receptacle Equipment | 44.65 |
Miscellaneous | 16.71 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 4472. | 4472. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 6752. | 8760. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 6828. | 8760. |
ALWAYS_OFF | 0. | 0. |
LTG_SCH_OFFICE | 2625. | 8760. |
LTG_SCH_DATACENTER | 2921. | 8760. |
EXTERIOR_LIGHT_SCH | 4380. | 4380. |
BLDG_EQUIP_SCH | 4049. | 8760. |
DATACENTER_EQUIP_SCH | 5478. | 8760. |
BLDG_OCC_SCH | 2528. | 5992. |
BLDG_OCC_SCH_W_SB | 1878. | 5056. |
BLDG_OCC_SCH_WO_SB | 2557. | 5992. |
BLDG_ELEVATORS | 2270. | 8760. |
ELEV_LIGHT_FAN_SCH_24_7 | 8760. | 8760. |
ELEV_LIGHT_FAN_SCH_ADD_DF | 2154. | 8760. |
BLDG_SWH_SCH | 1474. | 6570. |
WORK_EFF_SCH | 0. | 0. |
INFIL_SCH | 3976. | 3976. |
INFIL_SCH_PNNL | 5172. | 8760. |
INFIL_HALF_ON_SCH | 6368. | 8760. |
FAN_SCH | 8760. | 8760. |
REHEATCOILAVAILSCHED | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
MINOA_MOTORIZEDDAMPER_SCHED | 4472. | 4472. |
MINOA_SCHED | 8760. | 8760. |
CORE_BOTTOM SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_BOTTOM SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_MID SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_MID SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_TOP SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_TOP SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
SUPPLYFANSCH | 8760. | 8760. |
PERIMETER_MID_ZN_2_MDP_SCH | 1565. | 7824. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
HTGSETP_DC_SCH | DATACENTER COOLING SETPOINTS DUAL SP CONTROL | January | 18.00 | 365 | 18.00 | 365 |
CLGSETP_DC_SCH | DATACENTER COOLING SETPOINTS DUAL SP CONTROL | July | 27.00 | 365 | 27.00 | 365 |
HTGSETP_SCH_YES_OPTIMUM | CORE_BOTTOM DUAL SP CONTROL | January | 21.00 | 365 | 15.60 | 365 |
CLGSETP_SCH_YES_OPTIMUM | CORE_BOTTOM DUAL SP CONTROL | July | 24.00 | 365 | 26.70 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:44:04
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
BASEMENT | 7102.67 | 1657.33 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 8701.17 | 58.83 | 0.00 | 0.00 | 0.00 |
CORE_MID | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 8759.17 | 0.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 8724.33 | 35.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 8660.67 | 99.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 8604.00 | 156.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 7659.17 | 1100.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 8678.17 | 81.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 8527.67 | 232.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 8444.67 | 315.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 8072.00 | 688.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 8586.00 | 174.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 8447.83 | 312.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 8390.33 | 369.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 8060.83 | 699.17 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 3380.00 | 5380.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 3445.67 | 5314.33 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 3401.33 | 5358.67 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 2789.83 | 5970.17 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 8565.33 | 194.67 | 0.00 | 0.00 | 0.00 |
Min | 2789.83 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 5970.17 | 0.00 | 0.00 | 0.00 |
Average | 7533.95 | 1226.05 | 0.00 | 0.00 | 0.00 |
Sum | 173280.83 | 28199.17 | 0.00 | 0.00 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
BASEMENT | 364682.00 | 3934.00 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 330739.00 | 74.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 330813.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 330813.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 18354.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 518.50 | 1749.50 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 514.17 | 1753.83 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 506.83 | 1761.17 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 24277.17 | 79117.83 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 364682.00 | 79117.83 | 0.00 | 0.00 | 0.00 |
Average | 76491.86 | 3843.06 | 0.00 | 0.00 | 0.00 |
Sum | 1759312.67 | 88390.33 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
BASEMENT | 4324.50 | 4435.50 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 8329.33 | 430.67 | 0.00 | 0.00 | 0.00 |
CORE_MID | 8754.17 | 5.83 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 8735.17 | 24.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 8028.50 | 731.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 8192.67 | 567.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 7862.00 | 898.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 7182.17 | 1577.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 7032.17 | 1727.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 7084.00 | 1676.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 6790.50 | 1969.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 6886.83 | 1873.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 6935.83 | 1824.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 6996.33 | 1763.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 6766.67 | 1993.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 6862.67 | 1897.33 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 5695.67 | 3064.33 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 5679.33 | 3080.67 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 5652.17 | 3107.83 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 5217.83 | 3542.17 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 8512.83 | 247.17 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 7927.33 | 832.67 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 7610.17 | 1149.83 | 0.00 | 0.00 | 0.00 |
Min | 4324.50 | 5.83 | 0.00 | 0.00 | 0.00 |
Max | 8754.17 | 4435.50 | 0.00 | 0.00 | 0.00 |
Average | 7089.51 | 1670.49 | 0.00 | 0.00 | 0.00 |
Sum | 163058.83 | 38421.17 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
BASEMENT | 313275.83 | 55340.17 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 330277.00 | 536.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 330778.00 | 35.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 330775.00 | 38.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 38924.83 | 0.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 38910.83 | 14.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 18351.17 | 2.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 38914.00 | 11.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 24907.67 | 1.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 38906.67 | 18.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 24905.00 | 4.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 38911.00 | 14.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 24906.83 | 2.17 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 714.83 | 1553.17 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 704.50 | 1563.50 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 693.50 | 1574.50 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 36731.50 | 66663.50 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 330778.00 | 66663.50 | 0.00 | 0.00 | 0.00 |
Average | 74797.01 | 5537.91 | 0.00 | 0.00 | 0.00 |
Sum | 1720331.17 | 127371.83 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:44:04
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:44:04
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 0.00 | 8760.00 | 0.00 |
Average | 0.00 | 0.00 | 4570.43 | 0.00 |
Sum | 0.00 | 0.00 | 105120.00 | 0.00 |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 18354.00 | 0.00 |
PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 24909.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 0.00 | 38925.00 | 0.00 |
Average | 0.00 | 0.00 | 16367.35 | 0.00 |
Sum | 0.00 | 0.00 | 376449.00 | 0.00 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.572 |
February | 15.490 |
March | 17.074 |
April | 21.231 |
May | 26.899 |
June | 27.606 |
July | 27.937 |
August | 27.434 |
September | 26.232 |
October | 24.234 |
November | 18.911 |
December | 15.677 |
Annual Sum or Average | 21.892 |
Minimum of Months | 13.572 |
Maximum of Months | 27.937 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Environment
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.572 |
February | 15.490 |
March | 17.074 |
April | 21.231 |
May | 26.899 |
June | 27.606 |
July | 27.937 |
August | 27.434 |
September | 26.232 |
October | 24.234 |
November | 18.911 |
December | 15.677 |
Annual Sum or Average | 21.892 |
Minimum of Months | 13.572 |
Maximum of Months | 27.937 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2013
For: Environment
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.572 |
February | 15.490 |
March | 17.074 |
April | 21.231 |
May | 26.899 |
June | 27.606 |
July | 27.937 |
August | 27.434 |
September | 26.232 |
October | 24.234 |
November | 18.911 |
December | 15.677 |
Annual Sum or Average | 21.892 |
Minimum of Months | 13.572 |
Maximum of Months | 27.937 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.572 |
February | 15.490 |
March | 17.074 |
April | 21.231 |
May | 26.899 |
June | 27.606 |
July | 27.937 |
August | 27.434 |
September | 26.232 |
October | 24.234 |
November | 18.911 |
December | 15.677 |
Annual Sum or Average | 21.892 |
Minimum of Months | 13.572 |
Maximum of Months | 27.937 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICELARGE
For: Environment
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.572 |
February | 15.490 |
March | 17.074 |
April | 21.231 |
May | 26.899 |
June | 27.606 |
July | 27.937 |
August | 27.434 |
September | 26.232 |
October | 24.234 |
November | 18.911 |
December | 15.677 |
Annual Sum or Average | 21.892 |
Minimum of Months | 13.572 |
Maximum of Months | 27.937 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.572 |
February | 15.490 |
March | 17.074 |
April | 21.231 |
May | 26.899 |
June | 27.606 |
July | 27.937 |
August | 27.434 |
September | 26.232 |
October | 24.234 |
November | 18.911 |
December | 15.677 |
Annual Sum or Average | 21.892 |
Minimum of Months | 13.572 |
Maximum of Months | 27.937 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.572 |
February | 15.490 |
March | 17.074 |
April | 21.231 |
May | 26.899 |
June | 27.606 |
July | 27.937 |
August | 27.434 |
September | 26.232 |
October | 24.234 |
November | 18.911 |
December | 15.677 |
Annual Sum or Average | 21.892 |
Minimum of Months | 13.572 |
Maximum of Months | 27.937 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 2A
For: Environment
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.572 |
February | 15.490 |
March | 17.074 |
April | 21.231 |
May | 26.899 |
June | 27.606 |
July | 27.937 |
August | 27.434 |
September | 26.232 |
October | 24.234 |
November | 18.911 |
December | 15.677 |
Annual Sum or Average | 21.892 |
Minimum of Months | 13.572 |
Maximum of Months | 27.937 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_FL_TAMPA
For: Environment
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.572 |
February | 15.490 |
March | 17.074 |
April | 21.231 |
May | 26.899 |
June | 27.606 |
July | 27.937 |
August | 27.434 |
September | 26.232 |
October | 24.234 |
November | 18.911 |
December | 15.677 |
Annual Sum or Average | 21.892 |
Minimum of Months | 13.572 |
Maximum of Months | 27.937 |
Report: ZoneCoolingSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.607822E+11 | 123544.46 | 09-JAN-05:11 | 7.67 | 5.62 | 0.566817E+10 | 7499.40 | 12-JAN-10:09 | 18.17 | 17.41 |
February | 0.538849E+11 | 125214.76 | 13-FEB-05:11 | 5.53 | 1.73 | 0.514064E+10 | 7499.12 | 07-FEB-10:30 | 5.53 | 1.73 |
March | 0.627909E+11 | 127774.04 | 20-MAR-04:11 | 12.27 | 8.01 | 0.613397E+10 | 7499.70 | 23-MAR-09:20 | 16.97 | 14.65 |
April | 0.580745E+11 | 124446.44 | 17-APR-04:12 | 12.83 | 10.47 | 0.545068E+10 | 7499.33 | 12-APR-09:20 | 12.83 | 10.47 |
May | 0.627853E+11 | 91563.84 | 30-MAY-03:02 | 25.60 | 23.91 | 0.590363E+10 | 7498.83 | 26-MAY-09:20 | 25.60 | 23.91 |
June | 0.627807E+11 | 93706.46 | 07-JUN-04:12 | 21.10 | 18.59 | 0.588305E+10 | 7498.83 | 29-JUN-09:20 | 29.63 | 25.44 |
July | 0.640612E+11 | 88445.63 | 05-JUL-04:33 | 25.93 | 24.63 | 0.547553E+10 | 7498.82 | 14-JUL-09:20 | 24.27 | 23.35 |
August | 0.742355E+11 | 92868.86 | 21-AUG-03:02 | 26.27 | 23.88 | 0.614016E+10 | 7498.79 | 25-AUG-13:20 | 27.90 | 24.42 |
September | 0.668200E+11 | 92712.69 | 04-SEP-10:42 | 27.02 | 24.83 | 0.545510E+10 | 7498.81 | 14-SEP-13:20 | 28.13 | 24.89 |
October | 0.701473E+11 | 118216.68 | 27-OCT-04:12 | 15.00 | 8.02 | 0.567424E+10 | 7499.08 | 17-OCT-13:20 | 15.00 | 8.02 |
November | 0.679768E+11 | 121343.91 | 13-NOV-05:11 | 9.93 | 8.14 | 0.561801E+10 | 7499.14 | 13-NOV-14:09 | 23.30 | 17.20 |
December | 0.659076E+11 | 121508.20 | 04-DEC-05:12 | 6.00 | 5.06 | 0.547454E+10 | 7499.58 | 08-DEC-10:00 | 24.00 | 18.77 |
Annual Sum or Average | 0.770247E+12 | 0.680177E+11 | ||||||||
Minimum of Months | 0.538849E+11 | 88445.63 | 5.53 | 1.73 | 0.514064E+10 | 7498.79 | 5.53 | 1.73 | ||
Maximum of Months | 0.742355E+11 | 127774.04 | 27.02 | 24.83 | 0.614016E+10 | 7499.70 | 29.63 | 25.44 |
Report: ZoneCoolingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.515864E+11 | 94672.30 | 17-JAN-05:12 | 16.00 | 16.00 | 0.505042E+10 | 6734.78 | 05-JAN-14:09 | 16.00 | 16.00 |
February | 0.494017E+11 | 98525.88 | 27-FEB-05:13 | 17.77 | 17.77 | 0.459237E+10 | 6734.71 | 07-FEB-10:30 | 17.77 | 17.77 |
March | 0.618775E+11 | 99561.72 | 20-MAR-04:11 | 12.27 | 8.01 | 0.549173E+10 | 6734.92 | 23-MAR-09:09 | 16.78 | 14.63 |
April | 0.669044E+11 | 96956.82 | 10-APR-04:12 | 12.60 | 8.12 | 0.487626E+10 | 6734.90 | 10-APR-13:00 | 20.50 | 10.92 |
May | 0.650610E+11 | 99728.71 | 16-MAY-04:13 | 23.30 | 22.20 | 0.528034E+10 | 6734.43 | 31-MAY-13:09 | 23.27 | 21.49 |
June | 0.701662E+11 | 98433.77 | 01-JUN-04:13 | 21.50 | 20.44 | 0.526218E+10 | 6734.45 | 01-JUN-13:09 | 23.90 | 20.94 |
July | 0.752193E+11 | 79077.33 | 15-JUL-05:03 | 24.32 | 23.57 | 0.488583E+10 | 6734.46 | 13-JUL-09:20 | 24.32 | 23.57 |
August | 0.838726E+11 | 88343.00 | 17-AUG-04:12 | 21.93 | 21.62 | 0.548914E+10 | 6734.43 | 25-AUG-13:09 | 27.80 | 24.45 |
September | 0.632439E+11 | 98967.34 | 29-SEP-04:13 | 23.80 | 22.30 | 0.487527E+10 | 6734.43 | 25-SEP-09:09 | 23.80 | 22.30 |
October | 0.676355E+11 | 101068.50 | 02-OCT-04:13 | 18.03 | 15.02 | 0.507207E+10 | 6734.76 | 17-OCT-13:09 | 22.17 | 15.50 |
November | 0.619492E+11 | 99860.51 | 13-NOV-05:11 | 9.93 | 8.14 | 0.502531E+10 | 6734.72 | 21-NOV-14:00 | 22.20 | 15.14 |
December | 0.613790E+11 | 100422.03 | 18-DEC-05:12 | 4.00 | 0.58 | 0.489458E+10 | 6734.78 | 26-DEC-14:00 | 13.30 | 6.27 |
Annual Sum or Average | 0.778297E+12 | 0.607955E+11 | ||||||||
Minimum of Months | 0.494017E+11 | 79077.33 | 4.00 | 0.58 | 0.459237E+10 | 6734.43 | 13.30 | 6.27 | ||
Maximum of Months | 0.838726E+11 | 101068.50 | 24.32 | 23.57 | 0.549173E+10 | 6734.92 | 27.80 | 24.45 |
Report: ZoneCoolingSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.394854E+11 | 82326.92 | 19-JAN-06:02 | 18.83 | 18.83 | 0.492180E+10 | 6748.57 | 04-JAN-10:39 | 18.83 | 18.83 |
February | 0.370779E+11 | 84423.22 | 28-FEB-05:12 | 18.50 | 18.07 | 0.449445E+10 | 6734.63 | 09-FEB-14:00 | 18.50 | 18.07 |
March | 0.453868E+11 | 84069.34 | 31-MAR-04:12 | 16.90 | 16.90 | 0.540697E+10 | 6734.98 | 23-MAR-09:09 | 16.90 | 16.90 |
April | 0.464519E+11 | 85731.39 | 26-APR-04:12 | 21.10 | 20.64 | 0.484336E+10 | 6734.80 | 10-APR-13:00 | 21.10 | 20.64 |
May | 0.558969E+11 | 87577.08 | 18-MAY-04:13 | 23.30 | 22.03 | 0.526277E+10 | 6734.47 | 31-MAY-13:09 | 23.27 | 21.49 |
June | 0.561695E+11 | 86908.12 | 07-JUN-04:12 | 21.10 | 18.59 | 0.524505E+10 | 6734.50 | 01-JUN-13:09 | 21.10 | 18.59 |
July | 0.559449E+11 | 84235.61 | 12-JUL-04:12 | 23.50 | 23.01 | 0.486799E+10 | 6734.47 | 12-JUL-13:39 | 24.47 | 22.46 |
August | 0.582629E+11 | 86688.18 | 17-AUG-04:12 | 21.93 | 21.62 | 0.547494E+10 | 6734.47 | 25-AUG-13:09 | 27.80 | 24.45 |
September | 0.528276E+11 | 85533.49 | 08-SEP-04:02 | 24.17 | 23.46 | 0.485097E+10 | 6734.46 | 27-SEP-13:09 | 23.30 | 22.57 |
October | 0.525273E+11 | 86908.60 | 17-OCT-04:12 | 17.33 | 12.72 | 0.504735E+10 | 6734.79 | 17-OCT-13:09 | 22.17 | 15.50 |
November | 0.449045E+11 | 87075.71 | 08-NOV-05:11 | 19.80 | 19.09 | 0.497461E+10 | 6734.73 | 13-NOV-10:09 | 16.47 | 13.02 |
December | 0.411678E+11 | 85574.85 | 15-DEC-05:11 | 21.00 | 21.00 | 0.479756E+10 | 6734.61 | 18-DEC-14:09 | 16.17 | 10.34 |
Annual Sum or Average | 0.586103E+12 | 0.601878E+11 | ||||||||
Minimum of Months | 0.370779E+11 | 82326.92 | 16.90 | 12.72 | 0.449445E+10 | 6734.46 | 16.17 | 10.34 | ||
Maximum of Months | 0.582629E+11 | 87577.08 | 24.17 | 23.46 | 0.547494E+10 | 6748.57 | 27.80 | 24.45 |
Report: ZoneCoolingSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.347422E+11 | 81033.88 | 20-JAN-06:02 | 17.00 | 17.00 | 0.456331E+10 | 6734.45 | 03-JAN-14:09 | 17.00 | 17.00 |
February | 0.346509E+11 | 79371.03 | 28-FEB-06:03 | 18.38 | 17.90 | 0.427475E+10 | 6734.57 | 09-FEB-14:00 | 18.38 | 17.90 |
March | 0.424903E+11 | 80034.59 | 30-MAR-05:02 | 20.83 | 19.77 | 0.520895E+10 | 6734.53 | 02-MAR-14:39 | 20.83 | 19.77 |
April | 0.466596E+11 | 84296.42 | 22-APR-04:12 | 20.47 | 19.01 | 0.480086E+10 | 6734.79 | 10-APR-13:00 | 20.47 | 19.01 |
May | 0.606544E+11 | 89522.47 | 31-MAY-04:13 | 23.17 | 21.09 | 0.526509E+10 | 6734.43 | 31-MAY-13:09 | 23.27 | 21.49 |
June | 0.620021E+11 | 86104.51 | 30-JUN-03:42 | 24.22 | 22.90 | 0.525045E+10 | 6734.46 | 01-JUN-13:09 | 24.22 | 22.90 |
July | 0.615541E+11 | 85233.47 | 18-JUL-03:02 | 24.40 | 22.88 | 0.487563E+10 | 6734.45 | 12-JUL-13:09 | 24.40 | 22.88 |
August | 0.635660E+11 | 85624.24 | 11-AUG-03:02 | 24.85 | 22.85 | 0.547826E+10 | 6734.43 | 07-AUG-13:00 | 24.85 | 22.85 |
September | 0.559033E+11 | 84794.10 | 22-SEP-04:12 | 21.70 | 20.03 | 0.484919E+10 | 6734.46 | 07-SEP-13:00 | 21.70 | 20.03 |
October | 0.540102E+11 | 84768.17 | 20-OCT-04:11 | 22.00 | 22.00 | 0.502280E+10 | 6734.74 | 17-OCT-13:09 | 22.00 | 22.00 |
November | 0.416740E+11 | 84534.70 | 08-NOV-05:11 | 19.80 | 19.09 | 0.483111E+10 | 6734.60 | 21-NOV-14:00 | 22.20 | 15.14 |
December | 0.367302E+11 | 81011.33 | 15-DEC-06:02 | 21.00 | 21.00 | 0.450292E+10 | 6734.51 | 07-DEC-14:00 | 21.00 | 21.00 |
Annual Sum or Average | 0.594637E+12 | 0.589233E+11 | ||||||||
Minimum of Months | 0.346509E+11 | 79371.03 | 17.00 | 17.00 | 0.427475E+10 | 6734.43 | 17.00 | 15.14 | ||
Maximum of Months | 0.635660E+11 | 89522.47 | 24.85 | 22.90 | 0.547826E+10 | 6734.79 | 24.85 | 22.90 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.497450E+10 | 7465.06 | 02-JAN-13:30 | 26.00 | 18.64 | 0.586570E+09 | 845.60 | 27-JAN-14:00 | 18.00 | 12.42 |
February | 0.513896E+10 | 7615.72 | 22-FEB-14:30 | 25.55 | 20.41 | 0.552783E+09 | 845.62 | 09-FEB-14:00 | 25.55 | 20.41 |
March | 0.678515E+10 | 9026.06 | 28-MAR-12:30 | 27.45 | 22.17 | 0.669895E+09 | 845.61 | 24-MAR-09:09 | 27.45 | 22.17 |
April | 0.892300E+10 | 9846.92 | 26-APR-14:30 | 28.00 | 22.41 | 0.609404E+09 | 845.65 | 18-APR-13:39 | 28.00 | 22.41 |
May | 0.112099E+11 | 14292.10 | 07-MAY-14:42 | 32.98 | 23.21 | 0.664516E+09 | 845.60 | 31-MAY-13:09 | 23.27 | 21.49 |
June | 0.127000E+11 | 17670.63 | 25-JUN-16:41 | 32.30 | 25.17 | 0.662261E+09 | 845.60 | 01-JUN-13:09 | 32.30 | 25.17 |
July | 0.132379E+11 | 17379.89 | 23-JUL-14:02 | 33.03 | 26.02 | 0.615676E+09 | 845.60 | 12-JUL-13:39 | 33.03 | 26.02 |
August | 0.141272E+11 | 17533.46 | 20-AUG-14:02 | 33.83 | 25.15 | 0.690502E+09 | 845.60 | 25-AUG-13:09 | 27.80 | 24.45 |
September | 0.999108E+10 | 17214.18 | 10-SEP-16:51 | 33.10 | 26.71 | 0.613367E+09 | 845.60 | 27-SEP-13:09 | 23.30 | 22.57 |
October | 0.986815E+10 | 17226.69 | 08-OCT-15:01 | 31.00 | 25.66 | 0.635590E+09 | 845.64 | 17-OCT-13:09 | 22.17 | 15.50 |
November | 0.693401E+10 | 9414.37 | 08-NOV-05:11 | 19.80 | 19.09 | 0.622164E+09 | 845.63 | 21-NOV-14:00 | 22.20 | 15.14 |
December | 0.613375E+10 | 10546.23 | 11-DEC-06:02 | 20.83 | 20.26 | 0.589067E+09 | 845.61 | 18-DEC-14:20 | 16.33 | 10.42 |
Annual Sum or Average | 0.110024E+12 | 0.751180E+10 | ||||||||
Minimum of Months | 0.497450E+10 | 7465.06 | 19.80 | 18.64 | 0.552783E+09 | 845.60 | 16.33 | 10.42 | ||
Maximum of Months | 0.141272E+11 | 17670.63 | 33.83 | 26.71 | 0.690502E+09 | 845.65 | 33.03 | 26.02 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.448794E+10 | 13246.32 | 01-JAN-09:53 | 20.00 | 16.19 | 0.386831E+09 | 544.95 | 11-JAN-10:20 | 15.33 | 12.35 |
February | 0.467142E+10 | 10202.32 | 26-FEB-11:13 | 25.37 | 20.01 | 0.358417E+09 | 544.97 | 09-FEB-10:00 | 25.37 | 20.01 |
March | 0.625950E+10 | 19078.27 | 26-MAR-09:43 | 25.13 | 20.13 | 0.428921E+09 | 544.96 | 23-MAR-09:09 | 25.13 | 20.13 |
April | 0.779384E+10 | 18457.71 | 23-APR-09:12 | 24.97 | 20.75 | 0.390427E+09 | 544.97 | 03-APR-09:09 | 24.97 | 20.75 |
May | 0.951766E+10 | 20878.21 | 14-MAY-09:22 | 28.60 | 23.59 | 0.427915E+09 | 544.94 | 31-MAY-13:09 | 23.27 | 21.49 |
June | 0.102064E+11 | 19240.89 | 04-JUN-09:32 | 29.27 | 24.89 | 0.426189E+09 | 544.94 | 01-JUN-13:09 | 29.27 | 24.89 |
July | 0.104867E+11 | 20364.32 | 16-JUL-08:42 | 28.72 | 24.00 | 0.395946E+09 | 544.94 | 12-JUL-13:39 | 28.72 | 24.00 |
August | 0.106950E+11 | 19113.50 | 06-AUG-11:02 | 31.00 | 26.42 | 0.443544E+09 | 544.94 | 25-AUG-13:09 | 27.80 | 24.45 |
September | 0.813164E+10 | 21271.87 | 10-SEP-09:31 | 33.77 | 27.16 | 0.394331E+09 | 544.93 | 27-SEP-13:09 | 23.30 | 22.57 |
October | 0.820082E+10 | 19314.66 | 15-OCT-08:53 | 23.00 | 19.57 | 0.408130E+09 | 544.96 | 17-OCT-13:09 | 22.17 | 15.50 |
November | 0.589128E+10 | 18473.12 | 11-NOV-09:23 | 24.40 | 21.68 | 0.400391E+09 | 544.96 | 09-NOV-10:09 | 24.40 | 21.68 |
December | 0.499914E+10 | 11019.74 | 10-DEC-10:02 | 24.33 | 20.03 | 0.373738E+09 | 544.95 | 04-DEC-10:00 | 24.33 | 20.03 |
Annual Sum or Average | 0.913413E+11 | 0.483478E+10 | ||||||||
Minimum of Months | 0.448794E+10 | 10202.32 | 20.00 | 16.19 | 0.358417E+09 | 544.93 | 15.33 | 12.35 | ||
Maximum of Months | 0.106950E+11 | 21271.87 | 33.77 | 27.16 | 0.443544E+09 | 544.97 | 29.27 | 24.89 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.978855E+10 | 25851.42 | 01-JAN-13:51 | 26.00 | 17.88 | 0.622069E+09 | 871.29 | 19-JAN-14:09 | 25.00 | 21.54 |
February | 0.939942E+10 | 22602.64 | 26-FEB-11:13 | 25.37 | 20.01 | 0.568052E+09 | 864.99 | 27-FEB-14:20 | 25.70 | 20.08 |
March | 0.960387E+10 | 22349.97 | 05-MAR-12:43 | 27.52 | 18.33 | 0.672586E+09 | 845.65 | 13-MAR-13:09 | 19.68 | 10.43 |
April | 0.105152E+11 | 13024.44 | 28-APR-13:50 | 32.62 | 22.98 | 0.608767E+09 | 845.69 | 18-APR-13:39 | 32.62 | 22.98 |
May | 0.114489E+11 | 19252.50 | 07-MAY-14:02 | 33.72 | 23.65 | 0.664420E+09 | 845.62 | 31-MAY-13:09 | 23.27 | 21.49 |
June | 0.123386E+11 | 21276.88 | 25-JUN-16:01 | 32.70 | 24.34 | 0.661983E+09 | 845.62 | 01-JUN-13:09 | 32.70 | 24.34 |
July | 0.132140E+11 | 21288.30 | 23-JUL-14:02 | 33.03 | 26.02 | 0.615527E+09 | 845.61 | 12-JUL-13:39 | 33.03 | 26.02 |
August | 0.153921E+11 | 21800.62 | 20-AUG-14:02 | 33.83 | 25.15 | 0.690682E+09 | 845.62 | 25-AUG-13:09 | 27.80 | 24.45 |
September | 0.122412E+11 | 22917.57 | 03-SEP-13:32 | 31.83 | 24.36 | 0.614023E+09 | 845.62 | 20-SEP-13:39 | 26.60 | 22.72 |
October | 0.149631E+11 | 24453.73 | 15-OCT-13:31 | 29.67 | 22.65 | 0.638160E+09 | 865.77 | 13-OCT-13:39 | 29.67 | 22.65 |
November | 0.127555E+11 | 24206.26 | 05-NOV-13:12 | 27.20 | 20.74 | 0.630439E+09 | 899.65 | 06-NOV-14:09 | 28.30 | 21.03 |
December | 0.118054E+11 | 25449.82 | 10-DEC-12:41 | 27.00 | 20.34 | 0.604291E+09 | 884.89 | 15-DEC-14:20 | 29.00 | 21.92 |
Annual Sum or Average | 0.143466E+12 | 0.759100E+10 | ||||||||
Minimum of Months | 0.939942E+10 | 13024.44 | 25.37 | 17.88 | 0.568052E+09 | 845.61 | 19.68 | 10.43 | ||
Maximum of Months | 0.153921E+11 | 25851.42 | 33.83 | 26.02 | 0.690682E+09 | 899.65 | 33.03 | 26.02 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.629305E+10 | 24709.32 | 01-JAN-15:52 | 25.00 | 18.55 | 0.383626E+09 | 544.96 | 05-JAN-14:00 | 15.00 | 10.71 |
February | 0.693148E+10 | 22397.66 | 26-FEB-16:32 | 24.77 | 19.88 | 0.362704E+09 | 544.96 | 09-FEB-14:00 | 24.77 | 19.88 |
March | 0.933091E+10 | 24567.39 | 05-MAR-17:22 | 24.95 | 18.50 | 0.440105E+09 | 544.95 | 23-MAR-09:20 | 16.97 | 14.65 |
April | 0.126067E+11 | 25243.20 | 23-APR-16:32 | 27.37 | 21.80 | 0.395952E+09 | 544.99 | 18-APR-13:39 | 27.37 | 21.80 |
May | 0.111560E+11 | 25021.59 | 29-MAY-16:32 | 31.33 | 23.68 | 0.428523E+09 | 544.94 | 31-MAY-13:09 | 23.27 | 21.49 |
June | 0.132788E+11 | 27042.07 | 25-JUN-16:01 | 32.70 | 24.34 | 0.427399E+09 | 544.94 | 01-JUN-13:09 | 32.70 | 24.34 |
July | 0.144997E+11 | 24687.18 | 16-JUL-16:02 | 31.32 | 25.35 | 0.397581E+09 | 544.94 | 12-JUL-13:39 | 31.32 | 25.35 |
August | 0.171508E+11 | 24547.32 | 06-AUG-15:42 | 25.33 | 21.90 | 0.445985E+09 | 544.94 | 25-AUG-13:09 | 27.80 | 24.45 |
September | 0.103697E+11 | 26746.36 | 10-SEP-16:51 | 33.10 | 26.71 | 0.395589E+09 | 544.93 | 07-SEP-13:39 | 33.10 | 26.71 |
October | 0.114730E+11 | 26562.08 | 08-OCT-15:41 | 31.00 | 25.31 | 0.411182E+09 | 544.96 | 17-OCT-13:09 | 22.17 | 15.50 |
November | 0.922648E+10 | 24280.67 | 11-NOV-16:42 | 24.68 | 22.89 | 0.405881E+09 | 544.97 | 21-NOV-14:00 | 22.20 | 15.14 |
December | 0.909724E+10 | 26602.78 | 10-DEC-15:21 | 27.50 | 20.13 | 0.392829E+09 | 544.97 | 26-DEC-14:00 | 13.30 | 6.27 |
Annual Sum or Average | 0.131414E+12 | 0.488736E+10 | ||||||||
Minimum of Months | 0.629305E+10 | 22397.66 | 24.68 | 18.50 | 0.362704E+09 | 544.93 | 13.30 | 6.27 | ||
Maximum of Months | 0.171508E+11 | 27042.07 | 33.10 | 26.71 | 0.445985E+09 | 544.99 | 33.10 | 26.71 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.319025E+10 | 5392.67 | 31-JAN-14:40 | 25.00 | 21.54 | 0.531782E+09 | 845.59 | 02-JAN-14:39 | 25.00 | 21.54 |
February | 0.355008E+10 | 5665.30 | 28-FEB-15:00 | 25.00 | 20.38 | 0.509286E+09 | 845.58 | 27-FEB-14:09 | 25.00 | 20.38 |
March | 0.468457E+10 | 7458.18 | 30-MAR-13:20 | 28.83 | 22.63 | 0.621255E+09 | 845.59 | 24-MAR-13:09 | 28.83 | 22.63 |
April | 0.608373E+10 | 11508.31 | 28-APR-05:02 | 22.80 | 21.69 | 0.594797E+09 | 845.64 | 18-APR-13:00 | 22.80 | 21.69 |
May | 0.990462E+10 | 12741.38 | 30-MAY-05:03 | 25.50 | 24.21 | 0.664144E+09 | 845.59 | 31-MAY-13:09 | 23.27 | 21.49 |
June | 0.107562E+11 | 16374.06 | 11-JUN-17:21 | 32.75 | 21.65 | 0.662256E+09 | 845.59 | 13-JUN-13:09 | 32.98 | 21.38 |
July | 0.106028E+11 | 16124.18 | 23-JUL-15:02 | 31.78 | 24.88 | 0.615952E+09 | 845.59 | 14-JUL-13:09 | 31.78 | 24.88 |
August | 0.105423E+11 | 14996.37 | 14-AUG-03:02 | 26.52 | 24.51 | 0.690647E+09 | 845.59 | 25-AUG-13:09 | 27.80 | 24.45 |
September | 0.847566E+10 | 13222.12 | 11-SEP-05:03 | 25.42 | 23.91 | 0.611934E+09 | 845.59 | 27-SEP-13:09 | 23.30 | 22.57 |
October | 0.774608E+10 | 12401.80 | 13-OCT-04:02 | 23.83 | 21.68 | 0.628691E+09 | 845.63 | 17-OCT-13:09 | 22.17 | 15.50 |
November | 0.487928E+10 | 10268.85 | 02-NOV-05:03 | 23.38 | 22.55 | 0.588098E+09 | 845.61 | 21-NOV-14:00 | 22.20 | 15.14 |
December | 0.376302E+10 | 6294.97 | 15-DEC-14:10 | 29.00 | 22.01 | 0.529049E+09 | 845.59 | 08-DEC-14:09 | 29.00 | 22.01 |
Annual Sum or Average | 0.841786E+11 | 0.724789E+10 | ||||||||
Minimum of Months | 0.319025E+10 | 5392.67 | 22.80 | 20.38 | 0.509286E+09 | 845.58 | 22.17 | 15.14 | ||
Maximum of Months | 0.107562E+11 | 16374.06 | 32.75 | 24.88 | 0.690647E+09 | 845.64 | 32.98 | 24.88 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.341081E+10 | 7433.82 | 19-JAN-10:00 | 23.00 | 20.89 | 0.260393E+09 | 521.19 | 18-JAN-11:20 | 23.00 | 20.89 |
February | 0.374120E+10 | 9191.23 | 26-FEB-10:23 | 22.75 | 19.68 | 0.247521E+09 | 521.22 | 09-FEB-11:09 | 22.75 | 19.68 |
March | 0.504326E+10 | 17045.39 | 26-MAR-10:23 | 26.35 | 20.17 | 0.301310E+09 | 521.24 | 23-MAR-08:50 | 26.35 | 20.17 |
April | 0.644196E+10 | 21515.87 | 23-APR-09:02 | 24.68 | 20.67 | 0.283622E+09 | 521.23 | 10-APR-14:09 | 24.68 | 20.67 |
May | 0.911799E+10 | 21710.42 | 07-MAY-10:02 | 30.18 | 23.66 | 0.314588E+09 | 521.20 | 09-MAY-14:20 | 31.33 | 21.93 |
June | 0.946815E+10 | 20430.13 | 04-JUN-11:02 | 29.53 | 23.08 | 0.313294E+09 | 521.20 | 12-JUN-12:09 | 31.70 | 20.35 |
July | 0.938834E+10 | 21688.93 | 16-JUL-09:12 | 29.63 | 24.63 | 0.292362E+09 | 521.20 | 05-JUL-12:09 | 29.63 | 24.63 |
August | 0.915874E+10 | 18771.10 | 20-AUG-10:23 | 29.00 | 25.39 | 0.326185E+09 | 521.19 | 30-AUG-12:09 | 31.18 | 24.70 |
September | 0.750245E+10 | 20952.38 | 24-SEP-09:02 | 28.48 | 25.03 | 0.288995E+09 | 521.20 | 07-SEP-14:20 | 28.48 | 25.03 |
October | 0.721893E+10 | 19301.44 | 09-OCT-09:52 | 29.00 | 22.62 | 0.297287E+09 | 521.21 | 17-OCT-12:39 | 21.67 | 15.12 |
November | 0.479451E+10 | 15005.55 | 11-NOV-09:23 | 24.40 | 21.68 | 0.283885E+09 | 521.20 | 17-NOV-11:09 | 21.47 | 14.43 |
December | 0.358094E+10 | 6285.62 | 10-DEC-10:23 | 25.00 | 20.24 | 0.253942E+09 | 521.21 | 01-DEC-11:09 | 25.00 | 20.24 |
Annual Sum or Average | 0.788673E+11 | 0.346338E+10 | ||||||||
Minimum of Months | 0.341081E+10 | 6285.62 | 22.75 | 19.68 | 0.247521E+09 | 521.19 | 21.47 | 14.43 | ||
Maximum of Months | 0.946815E+10 | 21710.42 | 30.18 | 25.39 | 0.326185E+09 | 521.24 | 31.70 | 25.03 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.875064E+10 | 23273.20 | 16-JAN-14:42 | 26.83 | 18.71 | 0.612219E+09 | 899.55 | 19-JAN-14:39 | 25.00 | 21.54 |
February | 0.825216E+10 | 23268.44 | 26-FEB-13:42 | 26.52 | 19.51 | 0.558619E+09 | 882.09 | 27-FEB-14:30 | 25.80 | 20.17 |
March | 0.767090E+10 | 21375.76 | 05-MAR-13:43 | 27.70 | 18.31 | 0.654467E+09 | 845.64 | 13-MAR-13:09 | 19.68 | 10.43 |
April | 0.786782E+10 | 14478.83 | 28-APR-05:02 | 22.80 | 21.69 | 0.600759E+09 | 845.69 | 18-APR-13:00 | 22.80 | 21.69 |
May | 0.102000E+11 | 19060.83 | 07-MAY-14:02 | 33.72 | 23.65 | 0.664026E+09 | 845.61 | 31-MAY-13:09 | 23.27 | 21.49 |
June | 0.103546E+11 | 14410.27 | 24-JUN-05:03 | 25.50 | 22.83 | 0.661888E+09 | 845.61 | 13-JUN-13:09 | 25.50 | 22.83 |
July | 0.105463E+11 | 17259.05 | 23-JUL-15:02 | 31.78 | 24.88 | 0.615757E+09 | 845.61 | 12-JUL-13:39 | 31.78 | 24.88 |
August | 0.118683E+11 | 18725.60 | 21-AUG-03:02 | 26.27 | 23.88 | 0.690982E+09 | 845.61 | 25-AUG-13:09 | 27.80 | 24.45 |
September | 0.109933E+11 | 22117.92 | 03-SEP-13:32 | 31.83 | 24.36 | 0.613446E+09 | 845.62 | 20-SEP-13:39 | 26.60 | 22.72 |
October | 0.133688E+11 | 23760.54 | 15-OCT-13:31 | 29.67 | 22.65 | 0.637180E+09 | 888.98 | 13-OCT-13:50 | 29.67 | 22.65 |
November | 0.112125E+11 | 23349.21 | 05-NOV-13:52 | 27.20 | 20.73 | 0.626541E+09 | 926.45 | 06-NOV-14:09 | 28.30 | 21.03 |
December | 0.978545E+10 | 22679.21 | 10-DEC-14:22 | 27.50 | 20.13 | 0.590506E+09 | 898.39 | 15-DEC-14:39 | 29.00 | 21.74 |
Annual Sum or Average | 0.120871E+12 | 0.752639E+10 | ||||||||
Minimum of Months | 0.767090E+10 | 14410.27 | 22.80 | 18.31 | 0.558619E+09 | 845.61 | 19.68 | 10.43 | ||
Maximum of Months | 0.133688E+11 | 23760.54 | 33.72 | 24.88 | 0.690982E+09 | 926.45 | 31.78 | 24.88 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.391410E+10 | 9618.35 | 16-JAN-16:02 | 24.67 | 18.13 | 0.352344E+09 | 544.93 | 02-JAN-14:39 | 24.67 | 18.13 |
February | 0.433305E+10 | 20912.75 | 26-FEB-17:01 | 24.22 | 19.76 | 0.332435E+09 | 544.95 | 09-FEB-14:00 | 24.22 | 19.76 |
March | 0.536724E+10 | 13415.56 | 27-MAR-05:02 | 19.82 | 18.59 | 0.399740E+09 | 544.94 | 03-MAR-14:00 | 19.82 | 18.59 |
April | 0.697951E+10 | 21900.49 | 23-APR-17:01 | 26.92 | 21.65 | 0.382044E+09 | 544.98 | 18-APR-13:00 | 26.92 | 21.65 |
May | 0.887765E+10 | 22012.15 | 29-MAY-16:12 | 32.07 | 23.52 | 0.427082E+09 | 544.93 | 31-MAY-13:09 | 23.27 | 21.49 |
June | 0.951807E+10 | 23813.42 | 11-JUN-17:21 | 32.75 | 21.65 | 0.426271E+09 | 544.93 | 13-JUN-13:09 | 32.98 | 21.38 |
July | 0.926788E+10 | 22729.95 | 16-JUL-16:31 | 30.17 | 24.94 | 0.396594E+09 | 544.93 | 14-JUL-13:09 | 30.17 | 24.94 |
August | 0.973099E+10 | 18474.54 | 20-AUG-17:03 | 30.17 | 24.23 | 0.444806E+09 | 544.93 | 25-AUG-13:09 | 27.80 | 24.45 |
September | 0.794956E+10 | 21853.71 | 10-SEP-16:22 | 33.70 | 26.85 | 0.392951E+09 | 544.93 | 07-SEP-13:39 | 33.70 | 26.85 |
October | 0.782887E+10 | 21416.01 | 08-OCT-15:52 | 31.00 | 25.22 | 0.403831E+09 | 544.96 | 17-OCT-13:09 | 22.17 | 15.50 |
November | 0.544013E+10 | 14727.34 | 11-NOV-16:42 | 24.68 | 22.89 | 0.378697E+09 | 544.96 | 21-NOV-14:00 | 22.20 | 15.14 |
December | 0.449702E+10 | 12042.84 | 10-DEC-16:22 | 26.00 | 19.95 | 0.347366E+09 | 544.94 | 07-DEC-14:00 | 26.00 | 19.95 |
Annual Sum or Average | 0.837041E+11 | 0.468416E+10 | ||||||||
Minimum of Months | 0.391410E+10 | 9618.35 | 19.82 | 18.13 | 0.332435E+09 | 544.93 | 19.82 | 15.14 | ||
Maximum of Months | 0.973099E+10 | 23813.42 | 33.70 | 26.85 | 0.444806E+09 | 544.98 | 33.70 | 26.85 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.257205E+10 | 5740.05 | 31-JAN-15:00 | 25.00 | 21.54 | 0.516568E+09 | 845.59 | 02-JAN-14:39 | 25.00 | 21.54 |
February | 0.321623E+10 | 6115.36 | 22-FEB-14:30 | 25.55 | 20.41 | 0.495291E+09 | 845.58 | 22-FEB-14:00 | 25.00 | 20.08 |
March | 0.440164E+10 | 7928.14 | 30-MAR-13:30 | 28.55 | 22.55 | 0.603409E+09 | 845.59 | 24-MAR-13:09 | 28.55 | 22.55 |
April | 0.618822E+10 | 11678.37 | 28-APR-05:02 | 22.80 | 21.69 | 0.586120E+09 | 845.61 | 12-APR-13:20 | 22.80 | 21.69 |
May | 0.105909E+11 | 16405.32 | 28-MAY-16:32 | 32.03 | 24.85 | 0.664105E+09 | 845.59 | 31-MAY-13:09 | 23.27 | 21.49 |
June | 0.116459E+11 | 18914.71 | 11-JUN-17:21 | 32.75 | 21.65 | 0.662253E+09 | 845.59 | 12-JUN-13:09 | 31.78 | 20.56 |
July | 0.114830E+11 | 18858.67 | 23-JUL-14:12 | 32.77 | 25.73 | 0.616165E+09 | 845.59 | 14-JUL-13:09 | 32.77 | 25.73 |
August | 0.113371E+11 | 18392.00 | 20-AUG-14:53 | 33.00 | 24.29 | 0.690550E+09 | 845.59 | 25-AUG-13:09 | 27.80 | 24.45 |
September | 0.892144E+10 | 18247.79 | 10-SEP-15:02 | 35.38 | 27.24 | 0.611240E+09 | 845.60 | 07-SEP-13:00 | 35.38 | 27.24 |
October | 0.799236E+10 | 16397.36 | 08-OCT-14:32 | 31.67 | 25.93 | 0.623524E+09 | 845.63 | 17-OCT-13:09 | 22.17 | 15.50 |
November | 0.458025E+10 | 9635.08 | 02-NOV-05:03 | 23.38 | 22.55 | 0.569489E+09 | 845.61 | 21-NOV-14:00 | 22.20 | 15.14 |
December | 0.319076E+10 | 6827.84 | 15-DEC-15:00 | 29.00 | 21.56 | 0.512281E+09 | 845.58 | 11-DEC-14:39 | 29.00 | 21.56 |
Annual Sum or Average | 0.861198E+11 | 0.715099E+10 | ||||||||
Minimum of Months | 0.257205E+10 | 5740.05 | 22.80 | 20.41 | 0.495291E+09 | 845.58 | 22.17 | 15.14 | ||
Maximum of Months | 0.116459E+11 | 18914.71 | 35.38 | 27.24 | 0.690550E+09 | 845.63 | 35.38 | 27.24 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.299289E+10 | 7153.03 | 19-JAN-10:20 | 23.57 | 21.08 | 0.343435E+09 | 544.93 | 02-JAN-14:39 | 23.57 | 21.08 |
February | 0.346063E+10 | 7324.68 | 27-FEB-10:30 | 21.90 | 19.28 | 0.331998E+09 | 544.95 | 09-FEB-10:00 | 21.90 | 19.28 |
March | 0.479852E+10 | 15345.52 | 26-MAR-10:23 | 26.35 | 20.17 | 0.406970E+09 | 544.96 | 23-MAR-09:20 | 26.35 | 20.17 |
April | 0.654257E+10 | 21606.28 | 23-APR-09:02 | 24.68 | 20.67 | 0.385447E+09 | 544.97 | 10-APR-13:00 | 24.68 | 20.67 |
May | 0.972283E+10 | 21157.56 | 29-MAY-07:32 | 26.33 | 22.53 | 0.427701E+09 | 544.93 | 03-MAY-13:09 | 26.33 | 22.53 |
June | 0.102200E+11 | 20922.61 | 04-JUN-11:02 | 29.53 | 23.08 | 0.426464E+09 | 544.93 | 12-JUN-13:09 | 31.78 | 20.56 |
July | 0.101404E+11 | 22633.70 | 23-JUL-10:11 | 30.93 | 26.25 | 0.396704E+09 | 544.93 | 14-JUL-13:09 | 30.93 | 26.25 |
August | 0.984899E+10 | 18467.99 | 06-AUG-11:53 | 31.00 | 26.42 | 0.444201E+09 | 544.93 | 25-AUG-13:09 | 27.80 | 24.45 |
September | 0.793401E+10 | 21155.37 | 24-SEP-09:02 | 28.48 | 25.03 | 0.392868E+09 | 544.94 | 07-SEP-13:00 | 28.48 | 25.03 |
October | 0.746818E+10 | 19573.45 | 09-OCT-09:52 | 29.00 | 22.62 | 0.403041E+09 | 544.96 | 17-OCT-13:09 | 22.17 | 15.50 |
November | 0.453776E+10 | 11890.66 | 11-NOV-09:53 | 24.40 | 21.68 | 0.381277E+09 | 544.95 | 21-NOV-14:00 | 22.20 | 15.14 |
December | 0.315134E+10 | 5719.97 | 16-DEC-10:00 | 24.00 | 21.18 | 0.337499E+09 | 544.94 | 01-DEC-10:00 | 24.00 | 21.18 |
Annual Sum or Average | 0.808182E+11 | 0.467760E+10 | ||||||||
Minimum of Months | 0.299289E+10 | 5719.97 | 21.90 | 19.28 | 0.331998E+09 | 544.93 | 21.90 | 15.14 | ||
Maximum of Months | 0.102200E+11 | 22633.70 | 31.00 | 26.42 | 0.444201E+09 | 544.97 | 31.78 | 26.25 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.770330E+10 | 27110.69 | 01-JAN-13:41 | 25.83 | 18.00 | 0.596826E+09 | 876.02 | 19-JAN-14:39 | 25.00 | 21.54 |
February | 0.773854E+10 | 25095.92 | 26-FEB-13:42 | 26.52 | 19.51 | 0.546039E+09 | 860.18 | 27-FEB-14:30 | 25.80 | 20.17 |
March | 0.738602E+10 | 23117.80 | 05-MAR-13:43 | 27.70 | 18.31 | 0.636439E+09 | 845.64 | 13-MAR-13:09 | 19.68 | 10.43 |
April | 0.807275E+10 | 17814.18 | 23-APR-15:01 | 28.62 | 21.65 | 0.591483E+09 | 845.67 | 10-APR-13:00 | 28.62 | 21.65 |
May | 0.109654E+11 | 17223.28 | 31-MAY-04:11 | 23.17 | 21.09 | 0.663418E+09 | 845.61 | 31-MAY-13:09 | 23.27 | 21.49 |
June | 0.113102E+11 | 21946.61 | 11-JUN-17:21 | 32.75 | 21.65 | 0.661393E+09 | 845.61 | 12-JUN-13:09 | 31.78 | 20.56 |
July | 0.115068E+11 | 22720.07 | 23-JUL-14:12 | 32.77 | 25.73 | 0.615587E+09 | 845.61 | 14-JUL-13:09 | 32.77 | 25.73 |
August | 0.127621E+11 | 22318.77 | 20-AUG-14:53 | 33.00 | 24.29 | 0.690499E+09 | 845.61 | 25-AUG-13:09 | 27.80 | 24.45 |
September | 0.115927E+11 | 24319.63 | 03-SEP-13:32 | 31.83 | 24.36 | 0.612288E+09 | 845.62 | 07-SEP-13:00 | 24.40 | 22.88 |
October | 0.136880E+11 | 24560.00 | 09-OCT-13:12 | 31.00 | 23.42 | 0.632882E+09 | 874.34 | 13-OCT-13:50 | 32.87 | 23.24 |
November | 0.106119E+11 | 26421.57 | 11-NOV-13:51 | 26.10 | 22.85 | 0.616742E+09 | 901.69 | 06-NOV-14:09 | 26.10 | 22.85 |
December | 0.889916E+10 | 27118.18 | 10-DEC-14:11 | 27.33 | 20.16 | 0.574333E+09 | 877.10 | 15-DEC-14:39 | 29.00 | 21.74 |
Annual Sum or Average | 0.122237E+12 | 0.743793E+10 | ||||||||
Minimum of Months | 0.738602E+10 | 17223.28 | 23.17 | 18.00 | 0.546039E+09 | 845.61 | 19.68 | 10.43 | ||
Maximum of Months | 0.136880E+11 | 27118.18 | 33.00 | 25.73 | 0.690499E+09 | 901.69 | 32.87 | 25.73 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.348233E+10 | 9728.10 | 01-JAN-17:03 | 23.33 | 19.19 | 0.343493E+09 | 544.93 | 02-JAN-14:39 | 26.67 | 18.58 |
February | 0.413814E+10 | 21985.01 | 26-FEB-17:01 | 24.22 | 19.76 | 0.323874E+09 | 544.95 | 09-FEB-14:00 | 24.22 | 19.76 |
March | 0.520974E+10 | 13593.18 | 26-MAR-16:22 | 25.80 | 20.02 | 0.389079E+09 | 544.94 | 03-MAR-14:00 | 25.80 | 20.02 |
April | 0.715047E+10 | 23430.69 | 23-APR-17:01 | 26.92 | 21.65 | 0.375040E+09 | 544.95 | 12-APR-13:30 | 26.92 | 21.65 |
May | 0.943128E+10 | 23485.25 | 29-MAY-16:12 | 32.07 | 23.52 | 0.426168E+09 | 544.93 | 31-MAY-13:09 | 23.27 | 21.49 |
June | 0.102118E+11 | 25464.66 | 11-JUN-17:21 | 32.75 | 21.65 | 0.425507E+09 | 544.93 | 12-JUN-13:09 | 31.78 | 20.56 |
July | 0.995297E+10 | 24363.49 | 16-JUL-15:51 | 31.70 | 25.48 | 0.396044E+09 | 544.93 | 14-JUL-13:09 | 31.70 | 25.48 |
August | 0.103450E+11 | 18386.58 | 06-AUG-15:12 | 29.33 | 23.81 | 0.444034E+09 | 544.93 | 25-AUG-13:09 | 27.80 | 24.45 |
September | 0.838227E+10 | 23344.08 | 10-SEP-16:22 | 33.70 | 26.85 | 0.391007E+09 | 544.94 | 07-SEP-13:00 | 33.70 | 26.85 |
October | 0.808673E+10 | 22804.27 | 08-OCT-15:52 | 31.00 | 25.22 | 0.399481E+09 | 544.94 | 26-OCT-13:00 | 24.00 | 14.44 |
November | 0.525691E+10 | 22466.04 | 11-NOV-15:52 | 26.10 | 22.85 | 0.368529E+09 | 544.95 | 21-NOV-14:50 | 22.47 | 15.07 |
December | 0.407413E+10 | 22494.87 | 10-DEC-15:31 | 27.33 | 20.16 | 0.338037E+09 | 544.94 | 01-DEC-14:00 | 27.33 | 20.16 |
Annual Sum or Average | 0.857217E+11 | 0.462029E+10 | ||||||||
Minimum of Months | 0.348233E+10 | 9728.10 | 23.33 | 19.19 | 0.323874E+09 | 544.93 | 22.47 | 14.44 | ||
Maximum of Months | 0.103450E+11 | 25464.66 | 33.70 | 26.85 | 0.444034E+09 | 544.95 | 33.70 | 26.85 |
Report: ZoneCoolingSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.435917E+10 | 11652.47 | 02-JAN-06:13 | 16.00 | 15.39 | 0.00 | 0.00 | 01-JAN-00:10 | 16.00 | 15.39 |
February | 0.458765E+10 | 8628.63 | 28-FEB-06:03 | 18.38 | 17.90 | 0.00 | 0.00 | 01-FEB-00:10 | 18.38 | 17.90 |
March | 0.596059E+10 | 8475.96 | 27-MAR-05:02 | 19.82 | 18.59 | 0.00 | 0.00 | 01-MAR-00:10 | 19.82 | 18.59 |
April | 0.744991E+10 | 7343.86 | 20-APR-05:02 | 18.20 | 16.51 | 0.00 | 0.00 | 01-APR-00:10 | 18.20 | 16.51 |
May | 0.896575E+10 | 11685.14 | 31-MAY-05:02 | 23.80 | 21.58 | 0.00 | 0.00 | 01-MAY-00:10 | 23.80 | 21.58 |
June | 0.960570E+10 | 9948.20 | 06-JUN-05:02 | 23.30 | 22.26 | 0.00 | 0.00 | 01-JUN-00:10 | 23.30 | 22.26 |
July | 0.100284E+11 | 8891.69 | 21-JUL-05:02 | 25.60 | 24.31 | 0.00 | 0.00 | 01-JUL-00:10 | 25.60 | 24.31 |
August | 0.110306E+11 | 9256.29 | 21-AUG-05:03 | 26.00 | 23.88 | 0.00 | 0.00 | 01-AUG-00:10 | 26.00 | 23.88 |
September | 0.854343E+10 | 11399.85 | 05-SEP-05:03 | 22.80 | 22.80 | 0.00 | 0.00 | 01-SEP-00:10 | 22.80 | 22.80 |
October | 0.894543E+10 | 11233.07 | 02-OCT-05:02 | 18.08 | 15.07 | 0.00 | 0.00 | 01-OCT-00:10 | 18.08 | 15.07 |
November | 0.681762E+10 | 9060.45 | 03-NOV-05:03 | 22.28 | 21.91 | 0.00 | 0.00 | 01-NOV-00:10 | 22.28 | 21.91 |
December | 0.579013E+10 | 10755.49 | 11-DEC-06:02 | 20.83 | 20.26 | 0.00 | 0.00 | 01-DEC-00:10 | 20.83 | 20.26 |
Annual Sum or Average | 0.920844E+11 | 0.00 | ||||||||
Minimum of Months | 0.435917E+10 | 7343.86 | 16.00 | 15.07 | 0.00 | 0.00 | 16.00 | 15.07 | ||
Maximum of Months | 0.110306E+11 | 11685.14 | 26.00 | 24.31 | 0.00 | 0.00 | 26.00 | 24.31 |
Report: ZoneCoolingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.244102E+10 | 8342.42 | 04-JAN-06:02 | 1.83 | -1.2 | 0.00 | 0.00 | 01-JAN-00:10 | 1.83 | -1.2 |
February | 0.270568E+10 | 7590.34 | 13-FEB-06:03 | 4.80 | 1.11 | 0.00 | 0.00 | 01-FEB-00:10 | 4.80 | 1.11 |
March | 0.362134E+10 | 7843.55 | 09-MAR-06:03 | 1.10 | -2.1 | 0.00 | 0.00 | 01-MAR-00:10 | 1.10 | -2.1 |
April | 0.491354E+10 | 6248.91 | 28-APR-15:50 | 32.38 | 25.18 | 0.00 | 0.00 | 01-APR-00:10 | 32.38 | 25.18 |
May | 0.765112E+10 | 6924.83 | 06-MAY-05:03 | 24.40 | 21.68 | 0.00 | 0.00 | 01-MAY-00:10 | 24.40 | 21.68 |
June | 0.792877E+10 | 8499.09 | 17-JUN-05:03 | 25.50 | 23.83 | 0.00 | 0.00 | 01-JUN-00:10 | 25.50 | 23.83 |
July | 0.799520E+10 | 9750.45 | 21-JUL-05:02 | 25.60 | 24.31 | 0.00 | 0.00 | 01-JUL-00:10 | 25.60 | 24.31 |
August | 0.826719E+10 | 7587.90 | 15-AUG-05:03 | 25.00 | 22.66 | 0.00 | 0.00 | 01-AUG-00:10 | 25.00 | 22.66 |
September | 0.699357E+10 | 9363.90 | 01-SEP-05:03 | 24.42 | 23.29 | 0.00 | 0.00 | 01-SEP-00:10 | 24.42 | 23.29 |
October | 0.689349E+10 | 7333.14 | 10-OCT-15:30 | 30.00 | 22.39 | 0.00 | 0.00 | 01-OCT-00:10 | 30.00 | 22.39 |
November | 0.422876E+10 | 5670.87 | 07-NOV-15:40 | 27.37 | 23.92 | 0.00 | 0.00 | 01-NOV-00:10 | 27.37 | 23.92 |
December | 0.325859E+10 | 7034.10 | 21-DEC-05:01 | 0.17 | -0.7 | 0.00 | 0.00 | 01-DEC-00:10 | 0.17 | -0.7 |
Annual Sum or Average | 0.668983E+11 | 0.00 | ||||||||
Minimum of Months | 0.244102E+10 | 5670.87 | 0.17 | -2.1 | 0.00 | 0.00 | 0.17 | -2.1 | ||
Maximum of Months | 0.826719E+10 | 9750.45 | 32.38 | 25.18 | 0.00 | 0.00 | 32.38 | 25.18 |
Report: ZoneCoolingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.264316E+10 | 10464.89 | 19-JAN-15:00 | 25.00 | 21.54 | 0.00 | 0.00 | 01-JAN-00:10 | 25.00 | 21.54 |
February | 0.372072E+10 | 12172.48 | 24-FEB-14:40 | 26.07 | 21.03 | 0.00 | 0.00 | 01-FEB-00:10 | 26.07 | 21.03 |
March | 0.505399E+10 | 12182.02 | 06-MAR-14:50 | 26.18 | 21.15 | 0.00 | 0.00 | 01-MAR-00:10 | 26.18 | 21.15 |
April | 0.823251E+10 | 17608.60 | 28-APR-15:00 | 33.30 | 23.06 | 0.00 | 0.00 | 01-APR-00:10 | 33.30 | 23.06 |
May | 0.132205E+11 | 18545.62 | 10-MAY-14:40 | 32.80 | 23.17 | 0.00 | 0.00 | 01-MAY-00:10 | 32.80 | 23.17 |
June | 0.145447E+11 | 19409.04 | 28-JUN-14:30 | 33.60 | 26.19 | 0.00 | 0.00 | 01-JUN-00:10 | 33.60 | 26.19 |
July | 0.139808E+11 | 19736.76 | 07-JUL-14:40 | 34.63 | 24.19 | 0.00 | 0.00 | 01-JUL-00:10 | 34.63 | 24.19 |
August | 0.141216E+11 | 19043.20 | 03-AUG-15:00 | 35.00 | 24.85 | 0.00 | 0.00 | 01-AUG-00:10 | 35.00 | 24.85 |
September | 0.109099E+11 | 17617.37 | 01-SEP-14:00 | 32.20 | 22.62 | 0.00 | 0.00 | 01-SEP-00:10 | 32.20 | 22.62 |
October | 0.103879E+11 | 17560.42 | 05-OCT-15:00 | 34.00 | 24.05 | 0.00 | 0.00 | 01-OCT-00:10 | 34.00 | 24.05 |
November | 0.517321E+10 | 14033.18 | 02-NOV-14:00 | 29.40 | 24.47 | 0.00 | 0.00 | 01-NOV-00:10 | 29.40 | 24.47 |
December | 0.336527E+10 | 12068.37 | 15-DEC-15:00 | 29.00 | 21.56 | 0.00 | 0.00 | 01-DEC-00:10 | 29.00 | 21.56 |
Annual Sum or Average | 0.105354E+12 | 0.00 | ||||||||
Minimum of Months | 0.264316E+10 | 10464.89 | 25.00 | 21.03 | 0.00 | 0.00 | 25.00 | 21.03 | ||
Maximum of Months | 0.145447E+11 | 19736.76 | 35.00 | 26.19 | 0.00 | 0.00 | 35.00 | 26.19 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.391066E+10 | 2156.25 | 18-JAN-17:00 | 22.00 | 19.94 | 95232791.63 | 126.85 | 17-JAN-14:20 | 22.00 | 19.94 |
February | 0.836486E+10 | 4183.06 | 26-FEB-17:56 | 23.30 | 19.29 | 86405936.38 | 126.86 | 24-FEB-10:00 | 23.30 | 19.29 |
March | 0.144952E+11 | 7216.12 | 31-MAR-24:00 | 20.70 | 19.78 | 0.103242E+09 | 126.84 | 27-MAR-09:09 | 20.70 | 19.78 |
April | 0.191050E+11 | 7998.24 | 16-APR-18:10 | 18.43 | 13.27 | 91635523.23 | 127.70 | 28-APR-13:00 | 32.70 | 23.02 |
May | 0.473509E+10 | 3507.76 | 31-MAY-24:00 | 23.00 | 21.40 | 99236933.94 | 126.85 | 05-MAY-13:39 | 23.00 | 21.40 |
June | 0.944338E+10 | 5366.65 | 30-JUN-23:35 | 25.17 | 23.22 | 98981379.17 | 126.87 | 19-JUN-09:09 | 25.17 | 23.22 |
July | 0.147744E+11 | 7230.88 | 31-JUL-23:35 | 25.30 | 23.84 | 91894184.14 | 126.85 | 14-JUL-09:09 | 25.30 | 23.84 |
August | 0.199080E+11 | 7827.33 | 14-AUG-16:00 | 26.60 | 24.17 | 0.104264E+09 | 133.38 | 28-AUG-13:00 | 33.00 | 25.67 |
September | 0.459753E+10 | 3501.56 | 30-SEP-24:00 | 22.30 | 21.22 | 91606124.81 | 126.86 | 22-SEP-13:00 | 22.30 | 21.22 |
October | 0.976879E+10 | 5373.35 | 31-OCT-24:00 | 21.60 | 20.90 | 95248534.76 | 126.88 | 24-OCT-09:09 | 21.60 | 20.90 |
November | 0.142032E+11 | 6154.90 | 06-NOV-17:00 | 26.60 | 19.72 | 94306741.71 | 126.85 | 01-NOV-09:09 | 26.60 | 19.72 |
December | 0.195666E+11 | 7984.00 | 14-DEC-17:00 | 26.00 | 22.47 | 91882369.42 | 126.83 | 28-DEC-10:09 | 18.33 | 18.33 |
Annual Sum or Average | 0.142873E+12 | 0.114394E+10 | ||||||||
Minimum of Months | 0.391066E+10 | 2156.25 | 18.43 | 13.27 | 86405936.38 | 126.83 | 18.33 | 18.33 | ||
Maximum of Months | 0.199080E+11 | 7998.24 | 26.60 | 24.17 | 0.104264E+09 | 133.38 | 33.00 | 25.67 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.251597E+10 | 1970.65 | 18-JAN-17:00 | 22.00 | 19.94 | 95231147.29 | 126.84 | 02-JAN-14:20 | 22.00 | 19.94 |
February | 0.699261E+10 | 3821.35 | 27-FEB-17:50 | 22.98 | 19.46 | 86405438.26 | 126.85 | 24-FEB-14:00 | 22.98 | 19.46 |
March | 0.129786E+11 | 6702.70 | 31-MAR-24:00 | 20.70 | 19.78 | 0.103242E+09 | 126.85 | 07-MAR-14:00 | 20.70 | 19.78 |
April | 0.179131E+11 | 7458.27 | 16-APR-18:12 | 18.07 | 13.19 | 91632800.48 | 127.40 | 28-APR-13:00 | 32.70 | 23.02 |
May | 0.432180E+10 | 3272.17 | 31-MAY-24:00 | 23.00 | 21.40 | 99235163.26 | 126.85 | 11-MAY-13:00 | 23.00 | 21.40 |
June | 0.892738E+10 | 5196.43 | 30-JUN-23:57 | 25.10 | 23.16 | 98982528.83 | 126.87 | 01-JUN-13:09 | 25.10 | 23.16 |
July | 0.140548E+11 | 6935.14 | 31-JUL-23:53 | 25.20 | 23.65 | 91895919.63 | 126.85 | 14-JUL-13:00 | 25.20 | 23.65 |
August | 0.188911E+11 | 7413.01 | 14-AUG-16:00 | 26.60 | 24.17 | 0.104052E+09 | 132.82 | 28-AUG-13:00 | 33.00 | 25.67 |
September | 0.409317E+10 | 3222.18 | 30-SEP-24:00 | 22.30 | 21.22 | 91605412.34 | 126.82 | 05-SEP-13:30 | 22.30 | 21.22 |
October | 0.901151E+10 | 4939.78 | 31-OCT-24:00 | 21.60 | 20.90 | 95249182.06 | 126.87 | 25-OCT-13:39 | 21.60 | 20.90 |
November | 0.128005E+11 | 5822.16 | 06-NOV-17:00 | 26.60 | 19.72 | 94307272.33 | 126.85 | 01-NOV-09:00 | 26.60 | 19.72 |
December | 0.175854E+11 | 7548.48 | 15-DEC-17:00 | 28.00 | 21.24 | 91882676.67 | 126.83 | 28-DEC-14:20 | 19.33 | 19.33 |
Annual Sum or Average | 0.130086E+12 | 0.114372E+10 | ||||||||
Minimum of Months | 0.251597E+10 | 1970.65 | 18.07 | 13.19 | 86405438.26 | 126.82 | 19.33 | 19.33 | ||
Maximum of Months | 0.188911E+11 | 7548.48 | 28.00 | 24.17 | 0.104052E+09 | 132.82 | 33.00 | 25.67 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.168304E+10 | 2025.82 | 18-JAN-17:00 | 22.00 | 19.94 | 95092299.58 | 126.84 | 02-JAN-14:30 | 22.00 | 19.94 |
February | 0.621265E+10 | 3882.33 | 27-FEB-17:00 | 24.40 | 20.28 | 86405595.65 | 126.86 | 24-FEB-14:00 | 24.40 | 20.28 |
March | 0.124254E+11 | 6589.28 | 31-MAR-24:00 | 20.70 | 19.78 | 0.103243E+09 | 126.85 | 07-MAR-14:00 | 20.70 | 19.78 |
April | 0.177408E+11 | 7604.34 | 23-APR-18:10 | 25.13 | 21.19 | 91627963.37 | 126.94 | 28-APR-13:00 | 32.70 | 23.02 |
May | 0.441395E+10 | 3234.40 | 31-MAY-24:00 | 23.00 | 21.40 | 99235906.06 | 126.85 | 05-MAY-13:30 | 23.00 | 21.40 |
June | 0.904276E+10 | 5220.43 | 30-JUN-23:57 | 25.10 | 23.16 | 98982173.28 | 126.87 | 19-JUN-09:00 | 25.10 | 23.16 |
July | 0.141838E+11 | 6921.59 | 31-JUL-23:53 | 25.20 | 23.65 | 91895736.03 | 126.85 | 14-JUL-13:00 | 25.20 | 23.65 |
August | 0.190000E+11 | 7533.61 | 14-AUG-16:00 | 26.60 | 24.17 | 0.103784E+09 | 131.30 | 28-AUG-13:00 | 33.00 | 25.67 |
September | 0.413852E+10 | 3215.31 | 30-SEP-24:00 | 22.30 | 21.22 | 91605564.96 | 126.82 | 05-SEP-13:30 | 22.30 | 21.22 |
October | 0.891153E+10 | 4863.12 | 31-OCT-24:00 | 21.60 | 20.90 | 95249129.29 | 126.88 | 25-OCT-13:30 | 21.60 | 20.90 |
November | 0.122555E+11 | 5886.10 | 06-NOV-17:00 | 26.60 | 19.72 | 94307441.44 | 126.85 | 01-NOV-09:00 | 26.60 | 19.72 |
December | 0.167608E+11 | 7620.38 | 15-DEC-17:00 | 28.00 | 21.24 | 91882959.85 | 126.83 | 12-DEC-10:09 | 28.00 | 21.24 |
Annual Sum or Average | 0.126769E+12 | 0.114331E+10 | ||||||||
Minimum of Months | 0.168304E+10 | 2025.82 | 20.70 | 19.72 | 86405595.65 | 126.82 | 20.70 | 19.72 | ||
Maximum of Months | 0.190000E+11 | 7620.38 | 28.00 | 24.17 | 0.103784E+09 | 131.30 | 33.00 | 25.67 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.241592E+12 | 94043.85 | 02-JAN-17:00 | 26.00 | 18.38 | 0.206179E+10 | 2746.97 | 10-JAN-10:09 | 7.33 | 2.79 |
February | 0.437982E+12 | 184956.36 | 27-FEB-17:00 | 24.40 | 20.28 | 0.187058E+10 | 2747.77 | 13-FEB-14:09 | 24.40 | 20.28 |
March | 0.730303E+12 | 359161.65 | 31-MAR-24:00 | 20.70 | 19.78 | 0.223495E+10 | 2747.57 | 09-MAR-10:09 | 20.70 | 19.78 |
April | 0.942263E+12 | 368507.92 | 28-APR-21:02 | 23.82 | 23.08 | 0.204253E+10 | 3333.72 | 28-APR-13:00 | 23.82 | 23.08 |
May | 0.242319E+12 | 176251.81 | 31-MAY-24:00 | 23.00 | 21.40 | 0.214902E+10 | 2747.20 | 22-MAY-13:00 | 23.00 | 21.40 |
June | 0.470861E+12 | 267957.59 | 30-JUN-23:57 | 25.10 | 23.16 | 0.214279E+10 | 2746.57 | 01-JUN-13:09 | 25.10 | 23.16 |
July | 0.732771E+12 | 360068.02 | 31-JUL-23:57 | 25.20 | 23.65 | 0.198925E+10 | 2745.93 | 12-JUL-13:30 | 25.20 | 23.65 |
August | 0.974495E+12 | 371878.22 | 09-AUG-21:02 | 22.58 | 22.41 | 0.259722E+10 | 3566.43 | 28-AUG-13:00 | 33.00 | 25.67 |
September | 0.238334E+12 | 176802.36 | 30-SEP-24:00 | 22.30 | 21.22 | 0.198396E+10 | 2747.19 | 18-SEP-13:00 | 22.30 | 21.22 |
October | 0.490198E+12 | 269266.26 | 31-OCT-24:00 | 21.60 | 20.90 | 0.206195E+10 | 2746.76 | 24-OCT-09:30 | 21.60 | 20.90 |
November | 0.711175E+12 | 277930.25 | 07-NOV-17:00 | 26.10 | 23.27 | 0.204148E+10 | 2746.51 | 22-NOV-14:39 | 19.23 | 9.06 |
December | 0.979012E+12 | 369250.25 | 18-DEC-17:00 | 15.00 | 9.80 | 0.201520E+10 | 3142.11 | 13-DEC-14:00 | 15.00 | 9.80 |
Annual Sum or Average | 0.719130E+13 | 0.251907E+11 | ||||||||
Minimum of Months | 0.238334E+12 | 94043.85 | 15.00 | 9.80 | 0.187058E+10 | 2745.93 | 7.33 | 2.79 | ||
Maximum of Months | 0.979012E+12 | 371878.22 | 26.10 | 23.65 | 0.259722E+10 | 3566.43 | 33.00 | 25.67 |
Report: ZoneHeatingSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.149928E+09 | 14659.47 | 16-JAN-12:02 | 24.17 |
February | 0.216874E+09 | 12919.60 | 04-FEB-05:15 | 8.50 |
March | 0.197665E+09 | 12910.05 | 15-MAR-04:15 | 9.87 |
April | 0.177200E+09 | 17409.61 | 22-APR-16:02 | 30.08 |
May | 0.403415E+09 | 19325.72 | 27-MAY-16:02 | 31.60 |
June | 0.366360E+09 | 22556.14 | 10-JUN-16:02 | 33.72 |
July | 0.545112E+09 | 26076.62 | 22-JUL-16:01 | 35.92 |
August | 0.440088E+09 | 19928.55 | 19-AUG-16:03 | 32.63 |
September | 0.582131E+09 | 25427.44 | 09-SEP-16:02 | 35.73 |
October | 0.518337E+09 | 19457.01 | 07-OCT-16:02 | 31.58 |
November | 0.399253E+09 | 14678.29 | 26-NOV-14:22 | 21.35 |
December | 0.384183E+09 | 14714.23 | 17-DEC-15:42 | 17.17 |
Annual Sum or Average | 0.438054E+10 | |||
Minimum of Months | 0.149928E+09 | 12910.05 | 8.50 | |
Maximum of Months | 0.582131E+09 | 26076.62 | 35.92 |
Report: ZoneHeatingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 17.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 18.20 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 17.62 |
April | 0.00 | 0.00 | 01-APR-00:10 | 20.72 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 22.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 22.93 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 25.07 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 24.85 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 22.17 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 21.63 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 14.12 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 14.12 | |
Maximum of Months | 0.00 | 0.00 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 17.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 18.20 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 17.62 |
April | 0.00 | 0.00 | 01-APR-00:10 | 20.72 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 22.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 22.93 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 25.07 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 24.85 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 22.17 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 21.63 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 14.12 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 14.12 | |
Maximum of Months | 0.00 | 0.00 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 84042469.24 | 49030.33 | 23-JAN-06:02 | 6.83 |
February | 0.319460E+09 | 58954.28 | 06-FEB-05:21 | 2.90 |
March | 20963439.08 | 48972.00 | 13-MAR-05:02 | 6.68 |
April | 0.00 | 0.00 | 01-APR-00:10 | 20.72 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 22.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 22.93 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 25.07 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 24.85 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 22.17 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 21.63 |
December | 22849852.46 | 48503.74 | 21-DEC-06:01 | 0.83 |
Annual Sum or Average | 0.447316E+09 | |||
Minimum of Months | 0.00 | 0.00 | 0.83 | |
Maximum of Months | 0.319460E+09 | 58954.28 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 2188708.45 | 4119.34 | 05-JAN-06:01 | 0.17 |
February | 75398.52 | 879.65 | 06-FEB-06:01 | 2.88 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 17.62 |
April | 0.00 | 0.00 | 01-APR-00:10 | 20.72 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 22.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 22.93 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 25.07 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 24.85 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 22.17 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 21.63 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 14.12 |
Annual Sum or Average | 2264106.97 | |||
Minimum of Months | 0.00 | 0.00 | 0.17 | |
Maximum of Months | 2188708.45 | 4119.34 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 3535912.44 | 2562.03 | 05-JAN-06:01 | 0.17 |
February | 466005.68 | 2334.19 | 06-FEB-06:01 | 2.88 |
March | 185314.63 | 1235.43 | 09-MAR-06:03 | 1.10 |
April | 0.00 | 0.00 | 01-APR-00:10 | 20.72 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 22.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 22.93 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 25.07 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 24.85 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 22.17 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 21.63 |
December | 3921799.00 | 2451.75 | 21-DEC-06:01 | 0.83 |
Annual Sum or Average | 8109031.75 | |||
Minimum of Months | 0.00 | 0.00 | 0.17 | |
Maximum of Months | 3921799.00 | 2562.03 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 3612010.82 | 6280.20 | 05-JAN-06:01 | 0.17 |
February | 2803917.57 | 6449.38 | 06-FEB-06:01 | 2.88 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 17.62 |
April | 0.00 | 0.00 | 01-APR-00:10 | 20.72 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 22.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 22.93 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 25.07 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 24.85 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 22.17 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 21.63 |
December | 2708814.97 | 3255.26 | 21-DEC-06:01 | 0.83 |
Annual Sum or Average | 9124743.36 | |||
Minimum of Months | 0.00 | 0.00 | 0.17 | |
Maximum of Months | 3612010.82 | 6449.38 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 17.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 18.20 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 17.62 |
April | 0.00 | 0.00 | 01-APR-00:10 | 20.72 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 22.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 22.93 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 25.07 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 24.85 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 22.17 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 21.63 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 14.12 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 14.12 | |
Maximum of Months | 0.00 | 0.00 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.355518E+09 | 12555.82 | 10-JAN-05:01 | 1.33 |
February | 0.167067E+09 | 12920.74 | 06-FEB-05:11 | 2.97 |
March | 0.108728E+09 | 11907.52 | 13-MAR-04:11 | 7.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 20.72 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 22.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 22.93 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 25.07 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 24.85 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 22.17 |
November | 2161145.48 | 6723.76 | 16-NOV-06:02 | 9.40 |
December | 0.192312E+09 | 12445.79 | 21-DEC-05:01 | 0.17 |
Annual Sum or Average | 0.825786E+09 | |||
Minimum of Months | 0.00 | 0.00 | 0.17 | |
Maximum of Months | 0.355518E+09 | 12920.74 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.161694E+09 | 9956.19 | 10-JAN-05:01 | 1.33 |
February | 68689711.36 | 10171.58 | 06-FEB-05:11 | 2.97 |
March | 58007695.54 | 8812.43 | 10-MAR-06:02 | 5.68 |
April | 0.00 | 0.00 | 01-APR-00:10 | 20.72 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 22.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 22.93 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 25.07 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 24.85 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 22.17 |
November | 644606.62 | 2573.41 | 16-NOV-06:02 | 9.40 |
December | 0.109932E+09 | 9895.37 | 21-DEC-05:01 | 0.17 |
Annual Sum or Average | 0.398968E+09 | |||
Minimum of Months | 0.00 | 0.00 | 0.17 | |
Maximum of Months | 0.161694E+09 | 10171.58 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 93173729.84 | 12852.39 | 10-JAN-05:01 | 1.33 |
February | 42524832.76 | 12783.53 | 06-FEB-05:11 | 2.97 |
March | 47364771.01 | 12176.44 | 10-MAR-06:02 | 5.68 |
April | 0.00 | 0.00 | 01-APR-00:10 | 20.72 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 22.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 22.93 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 25.07 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 24.85 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 22.17 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 21.63 |
December | 68523069.27 | 12832.31 | 20-DEC-05:11 | 4.33 |
Annual Sum or Average | 0.251586E+09 | |||
Minimum of Months | 0.00 | 0.00 | 1.33 | |
Maximum of Months | 93173729.84 | 12852.39 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.107662E+09 | 8733.69 | 10-JAN-05:01 | 1.33 |
February | 47096866.15 | 8669.24 | 06-FEB-05:11 | 2.97 |
March | 24720351.75 | 7701.37 | 10-MAR-06:02 | 5.68 |
April | 0.00 | 0.00 | 01-APR-00:10 | 20.72 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 22.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 22.93 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 25.07 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 24.85 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 22.17 |
November | 48885.89 | 325.91 | 15-NOV-06:08 | 7.70 |
December | 50736931.91 | 8514.20 | 21-DEC-05:01 | 0.17 |
Annual Sum or Average | 0.230265E+09 | |||
Minimum of Months | 0.00 | 0.00 | 0.17 | |
Maximum of Months | 0.107662E+09 | 8733.69 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.131773E+10 | 15519.20 | 23-JAN-05:11 | 7.67 |
February | 0.820756E+09 | 16216.99 | 05-FEB-08:33 | -1.5 |
March | 0.484248E+09 | 14682.44 | 13-MAR-04:11 | 7.00 |
April | 3339837.33 | 6639.64 | 03-APR-05:03 | 12.28 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 22.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 22.93 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 25.07 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 24.85 |
October | 6890957.57 | 11583.26 | 28-OCT-05:02 | 10.00 |
November | 0.120415E+09 | 13469.72 | 24-NOV-05:12 | 11.23 |
December | 0.844685E+09 | 15011.80 | 21-DEC-04:02 | 1.67 |
Annual Sum or Average | 0.359807E+10 | |||
Minimum of Months | 0.00 | 0.00 | -1.5 | |
Maximum of Months | 0.131773E+10 | 16216.99 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.577218E+09 | 13226.95 | 23-JAN-05:11 | 7.67 |
February | 0.328986E+09 | 14115.36 | 06-FEB-05:21 | 2.90 |
March | 0.257567E+09 | 12417.13 | 10-MAR-05:11 | 5.77 |
April | 77682.64 | 392.07 | 03-APR-05:03 | 12.28 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 22.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 22.93 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 25.07 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 24.85 |
October | 3677427.11 | 7122.69 | 28-OCT-05:02 | 10.00 |
November | 43215309.94 | 10582.23 | 13-NOV-06:02 | 9.80 |
December | 0.431083E+09 | 12866.32 | 21-DEC-04:02 | 1.67 |
Annual Sum or Average | 0.164182E+10 | |||
Minimum of Months | 0.00 | 0.00 | 1.67 | |
Maximum of Months | 0.577218E+09 | 14115.36 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.544535E+09 | 16937.32 | 10-JAN-05:01 | 1.33 |
February | 0.341540E+09 | 18575.13 | 06-FEB-05:21 | 2.90 |
March | 0.318181E+09 | 16477.30 | 10-MAR-05:11 | 5.77 |
April | 73612.02 | 249.90 | 03-APR-05:05 | 12.28 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 22.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 22.93 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 25.07 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 24.85 |
October | 227212.42 | 1811.72 | 28-OCT-05:02 | 10.00 |
November | 16830812.70 | 14742.75 | 16-NOV-06:02 | 9.40 |
December | 0.367412E+09 | 17173.61 | 20-DEC-05:11 | 4.33 |
Annual Sum or Average | 0.158880E+10 | |||
Minimum of Months | 0.00 | 0.00 | 1.33 | |
Maximum of Months | 0.544535E+09 | 18575.13 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.475468E+09 | 12282.30 | 10-JAN-05:01 | 1.33 |
February | 0.272814E+09 | 13690.54 | 06-FEB-05:21 | 2.90 |
March | 0.161678E+09 | 11566.83 | 10-MAR-05:11 | 5.77 |
April | 0.00 | 0.00 | 01-APR-00:10 | 20.72 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 22.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 22.93 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 25.07 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 24.85 |
October | 30523.61 | 254.36 | 28-OCT-05:02 | 10.00 |
November | 20473125.98 | 10088.23 | 16-NOV-06:02 | 9.40 |
December | 0.266476E+09 | 12204.61 | 20-DEC-05:11 | 4.33 |
Annual Sum or Average | 0.119694E+10 | |||
Minimum of Months | 0.00 | 0.00 | 1.33 | |
Maximum of Months | 0.475468E+09 | 13690.54 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 58786124.91 | 10325.82 | 09-JAN-05:11 | 7.67 |
February | 62249865.28 | 9974.48 | 06-FEB-05:14 | 2.97 |
March | 64256732.52 | 10455.25 | 13-MAR-04:11 | 7.00 |
April | 70436406.78 | 10378.28 | 03-APR-04:12 | 12.43 |
May | 42447242.57 | 6756.39 | 24-MAY-03:02 | 25.00 |
June | 41709989.38 | 7090.54 | 07-JUN-04:12 | 21.10 |
July | 41182548.38 | 6232.78 | 23-JUL-14:02 | 33.03 |
August | 34425063.03 | 6649.49 | 20-AUG-14:02 | 33.83 |
September | 45885273.59 | 8115.18 | 29-SEP-04:11 | 23.80 |
October | 67485249.12 | 9500.66 | 30-OCT-04:12 | 16.67 |
November | 75161247.50 | 10051.20 | 20-NOV-05:12 | 16.17 |
December | 0.105945E+09 | 11354.59 | 28-DEC-05:11 | 17.33 |
Annual Sum or Average | 0.709971E+09 | |||
Minimum of Months | 34425063.03 | 6232.78 | 2.97 | |
Maximum of Months | 0.105945E+09 | 11354.59 | 33.83 |
Report: ZoneHeatingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.169305E+09 | 6047.67 | 16-JAN-16:02 | 24.67 |
February | 0.119022E+09 | 6867.12 | 26-FEB-16:21 | 24.95 |
March | 85537199.93 | 6168.73 | 20-MAR-04:11 | 12.27 |
April | 24040964.65 | 5452.45 | 04-APR-05:02 | 16.60 |
May | 26969472.19 | 6769.13 | 22-MAY-03:02 | 26.10 |
June | 19652224.79 | 4899.46 | 28-JUN-03:02 | 27.20 |
July | 24066105.19 | 5528.19 | 20-JUL-03:02 | 26.70 |
August | 21122772.13 | 6020.60 | 23-AUG-03:02 | 26.48 |
September | 34534285.94 | 6626.02 | 10-SEP-15:02 | 35.38 |
October | 39638419.65 | 5770.15 | 06-OCT-03:02 | 26.67 |
November | 41880383.15 | 5545.44 | 14-NOV-06:02 | 15.42 |
December | 80558747.33 | 6138.59 | 28-DEC-06:03 | 17.83 |
Annual Sum or Average | 0.686327E+09 | |||
Minimum of Months | 19652224.79 | 4899.46 | 12.27 | |
Maximum of Months | 0.169305E+09 | 6867.12 | 35.38 |
Report: ZoneHeatingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.167764E+10 | 12437.98 | 10-JAN-06:03 | 3.00 |
February | 0.109956E+10 | 20295.96 | 06-FEB-06:12 | 3.07 |
March | 0.865103E+09 | 14765.83 | 08-MAR-06:03 | 11.00 |
April | 0.148604E+09 | 12194.59 | 04-APR-05:02 | 16.60 |
May | 32945083.74 | 8837.06 | 16-MAY-04:11 | 23.30 |
June | 28978771.83 | 9146.29 | 07-JUN-04:12 | 21.10 |
July | 22345574.51 | 6620.77 | 12-JUL-04:12 | 23.50 |
August | 23881571.91 | 7820.93 | 17-AUG-04:12 | 21.93 |
September | 27493197.66 | 7888.79 | 01-SEP-04:12 | 23.93 |
October | 81872266.35 | 13398.08 | 18-OCT-05:03 | 15.17 |
November | 0.355705E+09 | 11733.07 | 30-NOV-06:03 | 15.08 |
December | 0.121803E+10 | 13565.72 | 21-DEC-06:03 | 0.83 |
Annual Sum or Average | 0.558216E+10 | |||
Minimum of Months | 22345574.51 | 6620.77 | 0.83 | |
Maximum of Months | 0.167764E+10 | 20295.96 | 23.93 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 17.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 18.20 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 17.62 |
April | 0.00 | 0.00 | 01-APR-00:10 | 20.72 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 22.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 22.93 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 25.07 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 24.85 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 22.17 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 21.63 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 14.12 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 14.12 | |
Maximum of Months | 0.00 | 0.00 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 17.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 18.20 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 17.62 |
April | 0.00 | 0.00 | 01-APR-00:10 | 20.72 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 22.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 22.93 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 25.07 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 24.85 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 22.17 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 21.63 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 14.12 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 14.12 | |
Maximum of Months | 0.00 | 0.00 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.163483E+09 | 545.13 | 10-JAN-04:20 | 1.67 |
February | 1692008.90 | 371.60 | 05-FEB-06:45 | -3.3 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 17.62 |
April | 0.00 | 0.00 | 01-APR-00:10 | 20.72 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 22.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 22.93 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 25.07 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 24.85 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 22.17 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 21.63 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 14.12 |
Annual Sum or Average | 0.165175E+09 | |||
Minimum of Months | 0.00 | 0.00 | -3.3 | |
Maximum of Months | 0.163483E+09 | 545.13 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 17.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 18.20 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 17.62 |
April | 0.00 | 0.00 | 01-APR-00:10 | 20.72 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 22.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 22.93 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 25.07 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 24.85 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 22.17 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 21.63 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 14.12 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 14.12 | |
Maximum of Months | 0.00 | 0.00 | 25.13 |
Report: ZoneElectricSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.219312E+11 | 22950.34 | 02-JAN-08:09 | 0.360447E+11 | 13457.54 | 01-JAN-00:10 |
February | 0.198933E+11 | 22950.34 | 01-FEB-08:09 | 0.325565E+11 | 13457.54 | 01-FEB-00:10 |
March | 0.236388E+11 | 22950.34 | 01-MAR-08:09 | 0.360447E+11 | 13457.54 | 01-MAR-00:10 |
April | 0.211142E+11 | 22950.34 | 03-APR-07:10 | 0.348820E+11 | 13457.54 | 01-APR-00:10 |
May | 0.227850E+11 | 22950.34 | 01-MAY-07:10 | 0.360447E+11 | 13457.54 | 01-MAY-00:10 |
June | 0.226748E+11 | 22950.34 | 01-JUN-07:10 | 0.348820E+11 | 13457.54 | 01-JUN-00:10 |
July | 0.212244E+11 | 22950.34 | 03-JUL-07:10 | 0.360447E+11 | 13457.54 | 01-JUL-00:10 |
August | 0.236388E+11 | 22950.34 | 01-AUG-07:10 | 0.360447E+11 | 13457.54 | 01-AUG-00:10 |
September | 0.211142E+11 | 22950.34 | 01-SEP-07:10 | 0.348820E+11 | 13457.54 | 01-SEP-00:10 |
October | 0.219312E+11 | 22950.34 | 02-OCT-07:10 | 0.360447E+11 | 13457.54 | 01-OCT-00:10 |
November | 0.216742E+11 | 22950.34 | 01-NOV-07:10 | 0.348820E+11 | 13457.54 | 01-NOV-00:10 |
December | 0.212244E+11 | 22950.34 | 01-DEC-08:09 | 0.360447E+11 | 13457.54 | 01-DEC-00:10 |
Annual Sum or Average | 0.262844E+12 | 0.424397E+12 | ||||
Minimum of Months | 0.198933E+11 | 22950.34 | 0.325565E+11 | 13457.54 | ||
Maximum of Months | 0.236388E+11 | 22950.34 | 0.360447E+11 | 13457.54 |
Report: ZoneElectricSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.196958E+11 | 20611.01 | 02-JAN-08:09 | 0.243681E+11 | 17206.63 | 02-JAN-08:09 |
February | 0.178655E+11 | 20611.01 | 01-FEB-08:09 | 0.220609E+11 | 17206.63 | 01-FEB-08:09 |
March | 0.212293E+11 | 20611.01 | 01-MAR-08:09 | 0.253549E+11 | 17206.63 | 01-MAR-08:09 |
April | 0.189620E+11 | 20611.01 | 03-APR-07:10 | 0.235306E+11 | 17206.63 | 03-APR-07:10 |
May | 0.204625E+11 | 20611.01 | 01-MAY-07:10 | 0.248615E+11 | 17206.63 | 01-MAY-07:10 |
June | 0.203636E+11 | 20611.01 | 01-JUN-07:10 | 0.244160E+11 | 17206.63 | 01-JUN-07:10 |
July | 0.190610E+11 | 20611.01 | 03-JUL-07:10 | 0.239708E+11 | 17206.63 | 03-JUL-07:10 |
August | 0.212293E+11 | 20611.01 | 01-AUG-07:10 | 0.253549E+11 | 17206.63 | 01-AUG-07:10 |
September | 0.189620E+11 | 20611.01 | 01-SEP-07:10 | 0.235199E+11 | 17206.63 | 01-SEP-07:10 |
October | 0.196958E+11 | 20611.01 | 02-OCT-07:10 | 0.243735E+11 | 17206.63 | 02-OCT-07:10 |
November | 0.194649E+11 | 20611.01 | 01-NOV-07:10 | 0.238373E+11 | 17206.63 | 01-NOV-07:10 |
December | 0.190610E+11 | 20611.01 | 01-DEC-08:09 | 0.239654E+11 | 17206.63 | 01-DEC-08:09 |
Annual Sum or Average | 0.236053E+12 | 0.289614E+12 | ||||
Minimum of Months | 0.178655E+11 | 20611.01 | 0.220609E+11 | 17206.63 | ||
Maximum of Months | 0.212293E+11 | 20611.01 | 0.253549E+11 | 17206.63 |
Report: ZoneElectricSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.196958E+11 | 20611.01 | 02-JAN-08:09 | 0.243680E+11 | 17206.56 | 02-JAN-08:09 |
February | 0.178655E+11 | 20611.01 | 01-FEB-08:09 | 0.220609E+11 | 17206.56 | 01-FEB-08:09 |
March | 0.212293E+11 | 20611.01 | 01-MAR-08:09 | 0.253548E+11 | 17206.56 | 01-MAR-08:09 |
April | 0.189620E+11 | 20611.01 | 03-APR-07:10 | 0.235305E+11 | 17206.56 | 03-APR-07:10 |
May | 0.204625E+11 | 20611.01 | 01-MAY-07:10 | 0.248614E+11 | 17206.56 | 01-MAY-07:10 |
June | 0.203636E+11 | 20611.01 | 01-JUN-07:10 | 0.244159E+11 | 17206.56 | 01-JUN-07:10 |
July | 0.190610E+11 | 20611.01 | 03-JUL-07:10 | 0.239707E+11 | 17206.56 | 03-JUL-07:10 |
August | 0.212293E+11 | 20611.01 | 01-AUG-07:10 | 0.253548E+11 | 17206.56 | 01-AUG-07:10 |
September | 0.189620E+11 | 20611.01 | 01-SEP-07:10 | 0.235198E+11 | 17206.56 | 01-SEP-07:10 |
October | 0.196958E+11 | 20611.01 | 02-OCT-07:10 | 0.243734E+11 | 17206.56 | 02-OCT-07:10 |
November | 0.194649E+11 | 20611.01 | 01-NOV-07:10 | 0.238372E+11 | 17206.56 | 01-NOV-07:10 |
December | 0.190610E+11 | 20611.01 | 01-DEC-08:09 | 0.239653E+11 | 17206.56 | 01-DEC-08:09 |
Annual Sum or Average | 0.236053E+12 | 0.289613E+12 | ||||
Minimum of Months | 0.178655E+11 | 20611.01 | 0.220609E+11 | 17206.56 | ||
Maximum of Months | 0.212293E+11 | 20611.01 | 0.253548E+11 | 17206.56 |
Report: ZoneElectricSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.196958E+11 | 20611.01 | 02-JAN-08:09 | 0.243680E+11 | 17206.56 | 02-JAN-08:09 |
February | 0.178655E+11 | 20611.01 | 01-FEB-08:09 | 0.220609E+11 | 17206.56 | 01-FEB-08:09 |
March | 0.212293E+11 | 20611.01 | 01-MAR-08:09 | 0.253548E+11 | 17206.56 | 01-MAR-08:09 |
April | 0.189620E+11 | 20611.01 | 03-APR-07:10 | 0.235305E+11 | 17206.56 | 03-APR-07:10 |
May | 0.204625E+11 | 20611.01 | 01-MAY-07:10 | 0.248614E+11 | 17206.56 | 01-MAY-07:10 |
June | 0.203636E+11 | 20611.01 | 01-JUN-07:10 | 0.244159E+11 | 17206.56 | 01-JUN-07:10 |
July | 0.190610E+11 | 20611.01 | 03-JUL-07:10 | 0.239707E+11 | 17206.56 | 03-JUL-07:10 |
August | 0.212293E+11 | 20611.01 | 01-AUG-07:10 | 0.253548E+11 | 17206.56 | 01-AUG-07:10 |
September | 0.189620E+11 | 20611.01 | 01-SEP-07:10 | 0.235198E+11 | 17206.56 | 01-SEP-07:10 |
October | 0.196958E+11 | 20611.01 | 02-OCT-07:10 | 0.243734E+11 | 17206.56 | 02-OCT-07:10 |
November | 0.194649E+11 | 20611.01 | 01-NOV-07:10 | 0.238372E+11 | 17206.56 | 01-NOV-07:10 |
December | 0.190610E+11 | 20611.01 | 01-DEC-08:09 | 0.239653E+11 | 17206.56 | 01-DEC-08:09 |
Annual Sum or Average | 0.236053E+12 | 0.289613E+12 | ||||
Minimum of Months | 0.178655E+11 | 20611.01 | 0.220609E+11 | 17206.56 | ||
Maximum of Months | 0.212293E+11 | 20611.01 | 0.253548E+11 | 17206.56 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.156013E+10 | 2255.20 | 02-JAN-08:09 | 0.305979E+10 | 2160.55 | 02-JAN-08:09 |
February | 0.135710E+10 | 2255.20 | 01-FEB-08:09 | 0.277008E+10 | 2160.55 | 01-FEB-08:09 |
March | 0.155628E+10 | 2255.20 | 27-MAR-07:10 | 0.318369E+10 | 2160.55 | 01-MAR-08:09 |
April | 0.134836E+10 | 2255.20 | 06-APR-07:10 | 0.295462E+10 | 2160.55 | 03-APR-07:10 |
May | 0.140368E+10 | 1803.00 | 23-MAY-07:19 | 0.312174E+10 | 2160.55 | 01-MAY-07:10 |
June | 0.137640E+10 | 1350.81 | 16-JUN-07:10 | 0.306580E+10 | 2160.55 | 01-JUN-07:10 |
July | 0.130523E+10 | 1470.28 | 14-JUL-07:10 | 0.300989E+10 | 2160.55 | 03-JUL-07:10 |
August | 0.147739E+10 | 1803.00 | 08-AUG-07:30 | 0.318369E+10 | 2160.55 | 01-AUG-07:10 |
September | 0.136701E+10 | 2255.20 | 26-SEP-07:10 | 0.295328E+10 | 2160.55 | 01-SEP-07:10 |
October | 0.146019E+10 | 2587.92 | 25-OCT-07:10 | 0.306046E+10 | 2160.55 | 02-OCT-07:10 |
November | 0.153489E+10 | 2255.20 | 01-NOV-07:10 | 0.299314E+10 | 2160.55 | 01-NOV-07:10 |
December | 0.154783E+10 | 2587.92 | 12-DEC-08:09 | 0.300922E+10 | 2160.55 | 01-DEC-08:09 |
Annual Sum or Average | 0.172945E+11 | 0.363654E+11 | ||||
Minimum of Months | 0.130523E+10 | 1350.81 | 0.277008E+10 | 2160.55 | ||
Maximum of Months | 0.156013E+10 | 2587.92 | 0.318369E+10 | 2160.55 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.977749E+09 | 1453.34 | 03-JAN-16:00 | 0.197184E+10 | 1392.34 | 02-JAN-08:09 |
February | 0.857915E+09 | 1453.34 | 01-FEB-08:09 | 0.178515E+10 | 1392.34 | 01-FEB-08:09 |
March | 0.986044E+09 | 1453.34 | 27-MAR-07:10 | 0.205169E+10 | 1392.34 | 01-MAR-08:09 |
April | 0.864844E+09 | 1453.34 | 14-APR-07:10 | 0.190407E+10 | 1392.34 | 03-APR-07:10 |
May | 0.911283E+09 | 1161.92 | 30-MAY-15:30 | 0.201177E+10 | 1392.34 | 01-MAY-07:10 |
June | 0.896486E+09 | 870.51 | 16-JUN-14:30 | 0.197572E+10 | 1392.34 | 01-JUN-07:10 |
July | 0.847972E+09 | 870.51 | 11-JUL-15:39 | 0.193969E+10 | 1392.34 | 03-JUL-07:10 |
August | 0.953840E+09 | 947.51 | 21-AUG-07:10 | 0.205169E+10 | 1392.34 | 01-AUG-07:10 |
September | 0.875628E+09 | 1453.34 | 26-SEP-07:10 | 0.190321E+10 | 1392.34 | 01-SEP-07:10 |
October | 0.929622E+09 | 1667.75 | 25-OCT-07:10 | 0.197228E+10 | 1392.34 | 02-OCT-07:10 |
November | 0.966340E+09 | 1667.75 | 21-NOV-16:00 | 0.192889E+10 | 1392.34 | 01-NOV-07:10 |
December | 0.974471E+09 | 1667.75 | 12-DEC-08:09 | 0.193926E+10 | 1392.34 | 01-DEC-08:09 |
Annual Sum or Average | 0.110422E+11 | 0.234352E+11 | ||||
Minimum of Months | 0.847972E+09 | 870.51 | 0.178515E+10 | 1392.34 | ||
Maximum of Months | 0.986044E+09 | 1667.75 | 0.205169E+10 | 1392.34 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.146283E+10 | 2255.25 | 13-JAN-08:09 | 0.305983E+10 | 2160.58 | 02-JAN-08:09 |
February | 0.130224E+10 | 2255.25 | 01-FEB-08:09 | 0.277013E+10 | 2160.58 | 01-FEB-08:09 |
March | 0.152767E+10 | 2255.25 | 27-MAR-07:10 | 0.318374E+10 | 2160.58 | 01-MAR-08:09 |
April | 0.135197E+10 | 2255.25 | 06-APR-07:10 | 0.295467E+10 | 2160.58 | 03-APR-07:10 |
May | 0.142338E+10 | 1803.04 | 23-MAY-07:10 | 0.312179E+10 | 2160.58 | 01-MAY-07:10 |
June | 0.139955E+10 | 1350.84 | 02-JUN-07:10 | 0.306585E+10 | 2160.58 | 01-JUN-07:10 |
July | 0.132215E+10 | 1803.04 | 14-JUL-07:10 | 0.300994E+10 | 2160.58 | 03-JUL-07:10 |
August | 0.148673E+10 | 1803.04 | 08-AUG-07:10 | 0.318374E+10 | 2160.58 | 01-AUG-07:10 |
September | 0.135916E+10 | 2255.25 | 26-SEP-07:10 | 0.295333E+10 | 2160.58 | 01-SEP-07:10 |
October | 0.143339E+10 | 2587.98 | 25-OCT-07:10 | 0.306051E+10 | 2160.58 | 02-OCT-07:10 |
November | 0.144957E+10 | 2255.25 | 01-NOV-07:10 | 0.299318E+10 | 2160.58 | 01-NOV-07:10 |
December | 0.144726E+10 | 2587.98 | 12-DEC-08:09 | 0.300927E+10 | 2160.58 | 01-DEC-08:09 |
Annual Sum or Average | 0.169659E+11 | 0.363660E+11 | ||||
Minimum of Months | 0.130224E+10 | 1350.84 | 0.277013E+10 | 2160.58 | ||
Maximum of Months | 0.152767E+10 | 2587.98 | 0.318374E+10 | 2160.58 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.968103E+09 | 1453.34 | 02-JAN-08:09 | 0.197183E+10 | 1392.33 | 02-JAN-08:09 |
February | 0.856326E+09 | 1667.75 | 01-FEB-08:09 | 0.178514E+10 | 1392.33 | 01-FEB-08:09 |
March | 0.999440E+09 | 1453.34 | 01-MAR-08:09 | 0.205168E+10 | 1392.33 | 01-MAR-08:09 |
April | 0.874276E+09 | 1453.34 | 06-APR-07:10 | 0.190406E+10 | 1392.33 | 03-APR-07:10 |
May | 0.915029E+09 | 1161.92 | 01-MAY-07:10 | 0.201175E+10 | 1392.33 | 01-MAY-07:10 |
June | 0.898337E+09 | 1161.92 | 16-JUN-07:10 | 0.197570E+10 | 1392.33 | 01-JUN-07:10 |
July | 0.851795E+09 | 1161.92 | 11-JUL-07:10 | 0.193968E+10 | 1392.33 | 03-JUL-07:10 |
August | 0.962444E+09 | 1453.34 | 08-AUG-07:10 | 0.205168E+10 | 1392.33 | 01-AUG-07:10 |
September | 0.887175E+09 | 1453.34 | 13-SEP-07:10 | 0.190319E+10 | 1392.33 | 01-SEP-07:10 |
October | 0.936444E+09 | 1667.75 | 25-OCT-07:10 | 0.197226E+10 | 1392.33 | 02-OCT-07:10 |
November | 0.953804E+09 | 1667.75 | 01-NOV-07:10 | 0.192888E+10 | 1392.33 | 01-NOV-07:10 |
December | 0.954691E+09 | 1667.75 | 12-DEC-08:09 | 0.193924E+10 | 1392.33 | 01-DEC-08:09 |
Annual Sum or Average | 0.110579E+11 | 0.234351E+11 | ||||
Minimum of Months | 0.851795E+09 | 1161.92 | 0.178514E+10 | 1392.33 | ||
Maximum of Months | 0.999440E+09 | 1667.75 | 0.205168E+10 | 1392.33 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.155122E+10 | 2255.20 | 13-JAN-08:09 | 0.305979E+10 | 2160.55 | 02-JAN-08:09 |
February | 0.135149E+10 | 2255.20 | 01-FEB-08:09 | 0.277008E+10 | 2160.55 | 01-FEB-08:09 |
March | 0.155010E+10 | 2255.20 | 27-MAR-07:10 | 0.318369E+10 | 2160.55 | 01-MAR-08:09 |
April | 0.134540E+10 | 2255.20 | 14-APR-07:10 | 0.295462E+10 | 2160.55 | 03-APR-07:10 |
May | 0.140175E+10 | 1803.00 | 23-MAY-07:19 | 0.312174E+10 | 2160.55 | 01-MAY-07:10 |
June | 0.137370E+10 | 1350.81 | 16-JUN-07:10 | 0.306580E+10 | 2160.55 | 01-JUN-07:10 |
July | 0.130426E+10 | 1470.28 | 14-JUL-07:10 | 0.300989E+10 | 2160.55 | 03-JUL-07:10 |
August | 0.147601E+10 | 1803.00 | 08-AUG-07:30 | 0.318369E+10 | 2160.55 | 01-AUG-07:10 |
September | 0.136401E+10 | 2255.20 | 26-SEP-07:10 | 0.295328E+10 | 2160.55 | 01-SEP-07:10 |
October | 0.145704E+10 | 2587.92 | 25-OCT-07:10 | 0.306046E+10 | 2160.55 | 02-OCT-07:10 |
November | 0.152708E+10 | 2255.20 | 01-NOV-07:10 | 0.299314E+10 | 2160.55 | 01-NOV-07:10 |
December | 0.154059E+10 | 2587.92 | 12-DEC-08:09 | 0.300922E+10 | 2160.55 | 01-DEC-08:09 |
Annual Sum or Average | 0.172427E+11 | 0.363654E+11 | ||||
Minimum of Months | 0.130426E+10 | 1350.81 | 0.277008E+10 | 2160.55 | ||
Maximum of Months | 0.155122E+10 | 2587.92 | 0.318369E+10 | 2160.55 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.974146E+09 | 1453.34 | 31-JAN-08:09 | 0.197184E+10 | 1392.34 | 02-JAN-08:09 |
February | 0.856255E+09 | 1453.34 | 01-FEB-08:09 | 0.178515E+10 | 1392.34 | 01-FEB-08:09 |
March | 0.984111E+09 | 1376.34 | 27-MAR-07:10 | 0.205169E+10 | 1392.34 | 01-MAR-08:09 |
April | 0.864033E+09 | 1453.34 | 14-APR-07:10 | 0.190407E+10 | 1392.34 | 03-APR-07:10 |
May | 0.909279E+09 | 947.51 | 23-MAY-07:19 | 0.201177E+10 | 1392.34 | 01-MAY-07:10 |
June | 0.895366E+09 | 870.51 | 27-JUN-13:30 | 0.197572E+10 | 1392.34 | 01-JUN-07:10 |
July | 0.846613E+09 | 870.51 | 11-JUL-15:39 | 0.193969E+10 | 1392.34 | 03-JUL-07:10 |
August | 0.952688E+09 | 947.51 | 21-AUG-07:10 | 0.205169E+10 | 1392.34 | 01-AUG-07:10 |
September | 0.874560E+09 | 1161.92 | 26-SEP-07:10 | 0.190321E+10 | 1392.34 | 01-SEP-07:10 |
October | 0.928134E+09 | 1667.75 | 25-OCT-07:10 | 0.197228E+10 | 1392.34 | 02-OCT-07:10 |
November | 0.963898E+09 | 1667.75 | 21-NOV-16:00 | 0.192889E+10 | 1392.34 | 01-NOV-07:10 |
December | 0.971400E+09 | 1667.75 | 12-DEC-08:09 | 0.193926E+10 | 1392.34 | 01-DEC-08:09 |
Annual Sum or Average | 0.110205E+11 | 0.234352E+11 | ||||
Minimum of Months | 0.846613E+09 | 870.51 | 0.178515E+10 | 1392.34 | ||
Maximum of Months | 0.984111E+09 | 1667.75 | 0.205169E+10 | 1392.34 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.146190E+10 | 2255.25 | 13-JAN-08:09 | 0.305983E+10 | 2160.58 | 02-JAN-08:09 |
February | 0.130122E+10 | 2255.25 | 01-FEB-08:09 | 0.277013E+10 | 2160.58 | 01-FEB-08:09 |
March | 0.152475E+10 | 2255.25 | 27-MAR-07:10 | 0.318374E+10 | 2160.58 | 01-MAR-08:09 |
April | 0.134958E+10 | 2255.25 | 06-APR-07:10 | 0.295467E+10 | 2160.58 | 03-APR-07:10 |
May | 0.142053E+10 | 1803.04 | 23-MAY-07:10 | 0.312179E+10 | 2160.58 | 01-MAY-07:10 |
June | 0.139732E+10 | 1350.84 | 02-JUN-07:10 | 0.306585E+10 | 2160.58 | 01-JUN-07:10 |
July | 0.132006E+10 | 1470.31 | 11-JUL-07:10 | 0.300994E+10 | 2160.58 | 03-JUL-07:10 |
August | 0.148429E+10 | 1803.04 | 08-AUG-07:10 | 0.318374E+10 | 2160.58 | 01-AUG-07:10 |
September | 0.135721E+10 | 2255.25 | 26-SEP-07:10 | 0.295333E+10 | 2160.58 | 01-SEP-07:10 |
October | 0.143126E+10 | 2587.98 | 25-OCT-07:10 | 0.306051E+10 | 2160.58 | 02-OCT-07:10 |
November | 0.144678E+10 | 2255.25 | 01-NOV-07:10 | 0.299318E+10 | 2160.58 | 01-NOV-07:10 |
December | 0.144595E+10 | 2587.98 | 12-DEC-08:09 | 0.300927E+10 | 2160.58 | 01-DEC-08:09 |
Annual Sum or Average | 0.169408E+11 | 0.363660E+11 | ||||
Minimum of Months | 0.130122E+10 | 1350.84 | 0.277013E+10 | 2160.58 | ||
Maximum of Months | 0.152475E+10 | 2587.98 | 0.318374E+10 | 2160.58 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.965115E+09 | 1453.34 | 02-JAN-08:09 | 0.197183E+10 | 1392.33 | 02-JAN-08:09 |
February | 0.854421E+09 | 1453.34 | 01-FEB-08:09 | 0.178514E+10 | 1392.33 | 01-FEB-08:09 |
March | 0.996484E+09 | 1453.34 | 01-MAR-08:09 | 0.205168E+10 | 1392.33 | 01-MAR-08:09 |
April | 0.872462E+09 | 1453.34 | 06-APR-07:10 | 0.190406E+10 | 1392.33 | 03-APR-07:10 |
May | 0.913778E+09 | 1161.92 | 01-MAY-07:10 | 0.201175E+10 | 1392.33 | 01-MAY-07:10 |
June | 0.896663E+09 | 1161.92 | 16-JUN-07:10 | 0.197570E+10 | 1392.33 | 01-JUN-07:10 |
July | 0.849870E+09 | 1161.92 | 11-JUL-07:10 | 0.193968E+10 | 1392.33 | 03-JUL-07:10 |
August | 0.958899E+09 | 1376.34 | 08-AUG-07:10 | 0.205168E+10 | 1392.33 | 01-AUG-07:10 |
September | 0.885079E+09 | 1453.34 | 13-SEP-07:10 | 0.190319E+10 | 1392.33 | 01-SEP-07:10 |
October | 0.934526E+09 | 1667.75 | 25-OCT-07:10 | 0.197226E+10 | 1392.33 | 02-OCT-07:10 |
November | 0.951276E+09 | 1667.75 | 01-NOV-07:10 | 0.192888E+10 | 1392.33 | 01-NOV-07:10 |
December | 0.951540E+09 | 1667.75 | 12-DEC-08:09 | 0.193924E+10 | 1392.33 | 01-DEC-08:09 |
Annual Sum or Average | 0.110301E+11 | 0.234351E+11 | ||||
Minimum of Months | 0.849870E+09 | 1161.92 | 0.178514E+10 | 1392.33 | ||
Maximum of Months | 0.996484E+09 | 1667.75 | 0.205168E+10 | 1392.33 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.155087E+10 | 2255.20 | 13-JAN-08:09 | 0.305979E+10 | 2160.55 | 02-JAN-08:09 |
February | 0.135111E+10 | 2255.20 | 01-FEB-08:09 | 0.277008E+10 | 2160.55 | 01-FEB-08:09 |
March | 0.154992E+10 | 2255.20 | 27-MAR-07:10 | 0.318369E+10 | 2160.55 | 01-MAR-08:09 |
April | 0.134533E+10 | 2255.20 | 14-APR-07:10 | 0.295462E+10 | 2160.55 | 03-APR-07:10 |
May | 0.140152E+10 | 1803.00 | 23-MAY-07:19 | 0.312174E+10 | 2160.55 | 01-MAY-07:10 |
June | 0.137360E+10 | 1350.81 | 27-JUN-11:30 | 0.306580E+10 | 2160.55 | 01-JUN-07:10 |
July | 0.130414E+10 | 1470.28 | 14-JUL-07:10 | 0.300989E+10 | 2160.55 | 03-JUL-07:10 |
August | 0.147594E+10 | 1803.00 | 08-AUG-07:30 | 0.318369E+10 | 2160.55 | 01-AUG-07:10 |
September | 0.136351E+10 | 2255.20 | 26-SEP-07:10 | 0.295328E+10 | 2160.55 | 01-SEP-07:10 |
October | 0.145697E+10 | 2587.92 | 25-OCT-07:10 | 0.306046E+10 | 2160.55 | 02-OCT-07:10 |
November | 0.152681E+10 | 2255.20 | 01-NOV-07:10 | 0.299314E+10 | 2160.55 | 01-NOV-07:10 |
December | 0.154025E+10 | 2587.92 | 12-DEC-08:09 | 0.300922E+10 | 2160.55 | 01-DEC-08:09 |
Annual Sum or Average | 0.172400E+11 | 0.363654E+11 | ||||
Minimum of Months | 0.130414E+10 | 1350.81 | 0.277008E+10 | 2160.55 | ||
Maximum of Months | 0.155087E+10 | 2587.92 | 0.318369E+10 | 2160.55 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.974088E+09 | 1453.34 | 31-JAN-08:09 | 0.197184E+10 | 1392.34 | 02-JAN-08:09 |
February | 0.856176E+09 | 1453.34 | 01-FEB-08:09 | 0.178515E+10 | 1392.34 | 01-FEB-08:09 |
March | 0.984065E+09 | 1376.34 | 27-MAR-07:10 | 0.205169E+10 | 1392.34 | 01-MAR-08:09 |
April | 0.864033E+09 | 1453.34 | 14-APR-07:10 | 0.190407E+10 | 1392.34 | 03-APR-07:10 |
May | 0.909233E+09 | 947.51 | 23-MAY-07:19 | 0.201177E+10 | 1392.34 | 01-MAY-07:10 |
June | 0.895320E+09 | 870.51 | 27-JUN-13:30 | 0.197572E+10 | 1392.34 | 01-JUN-07:10 |
July | 0.846508E+09 | 870.51 | 11-JUL-15:39 | 0.193969E+10 | 1392.34 | 03-JUL-07:10 |
August | 0.952599E+09 | 947.51 | 21-AUG-07:10 | 0.205169E+10 | 1392.34 | 01-AUG-07:10 |
September | 0.874501E+09 | 1161.92 | 26-SEP-07:10 | 0.190321E+10 | 1392.34 | 01-SEP-07:10 |
October | 0.928108E+09 | 1667.75 | 25-OCT-07:10 | 0.197228E+10 | 1392.34 | 02-OCT-07:10 |
November | 0.963849E+09 | 1667.75 | 21-NOV-16:00 | 0.192889E+10 | 1392.34 | 01-NOV-07:10 |
December | 0.971207E+09 | 1667.75 | 12-DEC-08:09 | 0.193926E+10 | 1392.34 | 01-DEC-08:09 |
Annual Sum or Average | 0.110197E+11 | 0.234352E+11 | ||||
Minimum of Months | 0.846508E+09 | 870.51 | 0.178515E+10 | 1392.34 | ||
Maximum of Months | 0.984065E+09 | 1667.75 | 0.205169E+10 | 1392.34 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.146190E+10 | 2255.25 | 13-JAN-08:09 | 0.305983E+10 | 2160.58 | 02-JAN-08:09 |
February | 0.130099E+10 | 2255.25 | 01-FEB-08:09 | 0.277013E+10 | 2160.58 | 01-FEB-08:09 |
March | 0.152464E+10 | 2255.25 | 27-MAR-07:10 | 0.318374E+10 | 2160.58 | 01-MAR-08:09 |
April | 0.134956E+10 | 2255.25 | 06-APR-07:10 | 0.295467E+10 | 2160.58 | 03-APR-07:10 |
May | 0.142051E+10 | 1803.04 | 23-MAY-07:10 | 0.312179E+10 | 2160.58 | 01-MAY-07:10 |
June | 0.139729E+10 | 1350.84 | 02-JUN-07:10 | 0.306585E+10 | 2160.58 | 01-JUN-07:10 |
July | 0.132003E+10 | 1470.31 | 11-JUL-07:10 | 0.300994E+10 | 2160.58 | 03-JUL-07:10 |
August | 0.148429E+10 | 1803.04 | 08-AUG-07:10 | 0.318374E+10 | 2160.58 | 01-AUG-07:10 |
September | 0.135710E+10 | 2255.25 | 26-SEP-07:10 | 0.295333E+10 | 2160.58 | 01-SEP-07:10 |
October | 0.143126E+10 | 2587.98 | 25-OCT-07:10 | 0.306051E+10 | 2160.58 | 02-OCT-07:10 |
November | 0.144678E+10 | 2255.25 | 01-NOV-07:10 | 0.299318E+10 | 2160.58 | 01-NOV-07:10 |
December | 0.144595E+10 | 2587.98 | 12-DEC-08:09 | 0.300927E+10 | 2160.58 | 01-DEC-08:09 |
Annual Sum or Average | 0.169403E+11 | 0.363660E+11 | ||||
Minimum of Months | 0.130099E+10 | 1350.84 | 0.277013E+10 | 2160.58 | ||
Maximum of Months | 0.152464E+10 | 2587.98 | 0.318374E+10 | 2160.58 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.964986E+09 | 1453.34 | 02-JAN-08:09 | 0.197183E+10 | 1392.33 | 02-JAN-08:09 |
February | 0.854359E+09 | 1453.34 | 01-FEB-08:09 | 0.178514E+10 | 1392.33 | 01-FEB-08:09 |
March | 0.996370E+09 | 1453.34 | 01-MAR-08:09 | 0.205168E+10 | 1392.33 | 01-MAR-08:09 |
April | 0.872460E+09 | 1453.34 | 06-APR-07:10 | 0.190406E+10 | 1392.33 | 03-APR-07:10 |
May | 0.913720E+09 | 1161.92 | 01-MAY-07:10 | 0.201175E+10 | 1392.33 | 01-MAY-07:10 |
June | 0.896663E+09 | 1161.92 | 16-JUN-07:10 | 0.197570E+10 | 1392.33 | 01-JUN-07:10 |
July | 0.849856E+09 | 1161.92 | 11-JUL-07:10 | 0.193968E+10 | 1392.33 | 03-JUL-07:10 |
August | 0.958896E+09 | 1376.34 | 08-AUG-07:10 | 0.205168E+10 | 1392.33 | 01-AUG-07:10 |
September | 0.884889E+09 | 1453.34 | 13-SEP-07:10 | 0.190319E+10 | 1392.33 | 01-SEP-07:10 |
October | 0.934526E+09 | 1667.75 | 25-OCT-07:10 | 0.197226E+10 | 1392.33 | 02-OCT-07:10 |
November | 0.951101E+09 | 1667.75 | 01-NOV-07:10 | 0.192888E+10 | 1392.33 | 01-NOV-07:10 |
December | 0.951226E+09 | 1667.75 | 12-DEC-08:09 | 0.193924E+10 | 1392.33 | 01-DEC-08:09 |
Annual Sum or Average | 0.110291E+11 | 0.234351E+11 | ||||
Minimum of Months | 0.849856E+09 | 1161.92 | 0.178514E+10 | 1392.33 | ||
Maximum of Months | 0.996370E+09 | 1667.75 | 0.205168E+10 | 1392.33 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.553024E+09 | 578.72 | 02-JAN-08:09 | 0.521915E+10 | 1948.61 | 01-JAN-00:10 |
February | 0.501634E+09 | 578.72 | 01-FEB-08:09 | 0.942813E+10 | 3897.21 | 01-FEB-00:10 |
March | 0.596080E+09 | 578.72 | 01-MAR-08:09 | 0.156645E+11 | 7794.42 | 31-MAR-23:10 |
April | 0.532421E+09 | 578.72 | 03-APR-07:10 | 0.201821E+11 | 7794.42 | 01-APR-00:10 |
May | 0.574552E+09 | 578.72 | 01-MAY-07:10 | 0.522616E+10 | 3897.21 | 31-MAY-23:10 |
June | 0.571774E+09 | 578.72 | 01-JUN-07:10 | 0.101086E+11 | 5845.82 | 30-JUN-23:10 |
July | 0.535199E+09 | 578.72 | 03-JUL-07:10 | 0.156645E+11 | 7794.42 | 31-JUL-23:10 |
August | 0.596080E+09 | 578.72 | 01-AUG-07:10 | 0.208555E+11 | 7794.42 | 01-AUG-00:10 |
September | 0.532421E+09 | 578.72 | 01-SEP-07:10 | 0.505780E+10 | 3897.21 | 30-SEP-23:10 |
October | 0.553024E+09 | 578.72 | 02-OCT-07:10 | 0.104453E+11 | 5845.82 | 31-OCT-23:10 |
November | 0.546542E+09 | 578.72 | 01-NOV-07:10 | 0.151524E+11 | 5845.82 | 01-NOV-00:10 |
December | 0.535199E+09 | 578.72 | 01-DEC-08:09 | 0.208766E+11 | 7794.42 | 01-DEC-00:10 |
Annual Sum or Average | 0.662795E+10 | 0.153881E+12 | ||||
Minimum of Months | 0.501634E+09 | 578.72 | 0.505780E+10 | 1948.61 | ||
Maximum of Months | 0.596080E+09 | 578.72 | 0.208766E+11 | 7794.42 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.553024E+09 | 578.72 | 02-JAN-08:09 | 0.521915E+10 | 1948.61 | 01-JAN-00:10 |
February | 0.501634E+09 | 578.72 | 01-FEB-08:09 | 0.942813E+10 | 3897.21 | 01-FEB-00:10 |
March | 0.596080E+09 | 578.72 | 01-MAR-08:09 | 0.156645E+11 | 7794.42 | 31-MAR-23:10 |
April | 0.532421E+09 | 578.72 | 03-APR-07:10 | 0.201821E+11 | 7794.42 | 01-APR-00:10 |
May | 0.574552E+09 | 578.72 | 01-MAY-07:10 | 0.522616E+10 | 3897.21 | 31-MAY-23:10 |
June | 0.571774E+09 | 578.72 | 01-JUN-07:10 | 0.101086E+11 | 5845.82 | 30-JUN-23:10 |
July | 0.535199E+09 | 578.72 | 03-JUL-07:10 | 0.156645E+11 | 7794.42 | 31-JUL-23:10 |
August | 0.596080E+09 | 578.72 | 01-AUG-07:10 | 0.208555E+11 | 7794.42 | 01-AUG-00:10 |
September | 0.532421E+09 | 578.72 | 01-SEP-07:10 | 0.505780E+10 | 3897.21 | 30-SEP-23:10 |
October | 0.553024E+09 | 578.72 | 02-OCT-07:10 | 0.104453E+11 | 5845.82 | 31-OCT-23:10 |
November | 0.546542E+09 | 578.72 | 01-NOV-07:10 | 0.151524E+11 | 5845.82 | 01-NOV-00:10 |
December | 0.535199E+09 | 578.72 | 01-DEC-08:09 | 0.208766E+11 | 7794.42 | 01-DEC-00:10 |
Annual Sum or Average | 0.662795E+10 | 0.153881E+12 | ||||
Minimum of Months | 0.501634E+09 | 578.72 | 0.505780E+10 | 1948.61 | ||
Maximum of Months | 0.596080E+09 | 578.72 | 0.208766E+11 | 7794.42 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.553024E+09 | 578.72 | 02-JAN-08:09 | 0.521915E+10 | 1948.61 | 01-JAN-00:10 |
February | 0.501634E+09 | 578.72 | 01-FEB-08:09 | 0.942813E+10 | 3897.21 | 01-FEB-00:10 |
March | 0.596080E+09 | 578.72 | 01-MAR-08:09 | 0.156645E+11 | 7794.42 | 31-MAR-23:10 |
April | 0.532421E+09 | 578.72 | 03-APR-07:10 | 0.201821E+11 | 7794.42 | 01-APR-00:10 |
May | 0.574552E+09 | 578.72 | 01-MAY-07:10 | 0.522616E+10 | 3897.21 | 31-MAY-23:10 |
June | 0.571774E+09 | 578.72 | 01-JUN-07:10 | 0.101086E+11 | 5845.82 | 30-JUN-23:10 |
July | 0.535199E+09 | 578.72 | 03-JUL-07:10 | 0.156645E+11 | 7794.42 | 31-JUL-23:10 |
August | 0.596080E+09 | 578.72 | 01-AUG-07:10 | 0.208555E+11 | 7794.42 | 01-AUG-00:10 |
September | 0.532421E+09 | 578.72 | 01-SEP-07:10 | 0.505780E+10 | 3897.21 | 30-SEP-23:10 |
October | 0.553024E+09 | 578.72 | 02-OCT-07:10 | 0.104453E+11 | 5845.82 | 31-OCT-23:10 |
November | 0.546542E+09 | 578.72 | 01-NOV-07:10 | 0.151524E+11 | 5845.82 | 01-NOV-00:10 |
December | 0.535199E+09 | 578.72 | 01-DEC-08:09 | 0.208766E+11 | 7794.42 | 01-DEC-00:10 |
Annual Sum or Average | 0.662795E+10 | 0.153881E+12 | ||||
Minimum of Months | 0.501634E+09 | 578.72 | 0.505780E+10 | 1948.61 | ||
Maximum of Months | 0.596080E+09 | 578.72 | 0.208766E+11 | 7794.42 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.618367E+10 | 6471.01 | 02-JAN-08:09 | 0.254202E+12 | 94908.13 | 01-JAN-00:10 |
February | 0.560905E+10 | 6471.01 | 01-FEB-08:09 | 0.459203E+12 | 189816.26 | 01-FEB-00:10 |
March | 0.666512E+10 | 6471.01 | 01-MAR-08:09 | 0.762947E+12 | 379632.52 | 31-MAR-23:10 |
April | 0.595330E+10 | 6471.01 | 03-APR-07:10 | 0.982982E+12 | 379632.52 | 01-APR-00:10 |
May | 0.642439E+10 | 6471.01 | 01-MAY-07:10 | 0.254544E+12 | 189816.26 | 31-MAY-23:10 |
June | 0.639333E+10 | 6471.01 | 01-JUN-07:10 | 0.492345E+12 | 284724.39 | 30-JUN-23:10 |
July | 0.598436E+10 | 6471.01 | 03-JUL-07:10 | 0.762947E+12 | 379632.52 | 31-JUL-23:10 |
August | 0.666512E+10 | 6471.01 | 01-AUG-07:10 | 0.101578E+13 | 379632.52 | 01-AUG-00:10 |
September | 0.595330E+10 | 6471.01 | 01-SEP-07:10 | 0.246344E+12 | 189816.26 | 30-SEP-23:10 |
October | 0.618367E+10 | 6471.01 | 02-OCT-07:10 | 0.508746E+12 | 284724.39 | 31-OCT-23:10 |
November | 0.611120E+10 | 6471.01 | 01-NOV-07:10 | 0.738006E+12 | 284724.39 | 01-NOV-00:10 |
December | 0.598436E+10 | 6471.01 | 01-DEC-08:09 | 0.101681E+13 | 379632.52 | 01-DEC-00:10 |
Annual Sum or Average | 0.741109E+11 | 0.749486E+13 | ||||
Minimum of Months | 0.560905E+10 | 6471.01 | 0.246344E+12 | 94908.13 | ||
Maximum of Months | 0.666512E+10 | 6471.01 | 0.101681E+13 | 379632.52 |
Report: SpaceGainsMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.133902E+11 | 0.219312E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.121482E+11 | 0.198933E+11 | 0.325565E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.145160E+11 | 0.236388E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.128805E+11 | 0.211142E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.139531E+11 | 0.227850E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.139143E+11 | 0.226748E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.129193E+11 | 0.212244E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.145160E+11 | 0.236388E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.128805E+11 | 0.211142E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.133902E+11 | 0.219312E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.132595E+11 | 0.216742E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.129193E+11 | 0.212244E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.160687E+12 | 0.262844E+12 | 0.424397E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.121482E+11 | 0.198933E+11 | 0.325565E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.145160E+11 | 0.236388E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.120254E+11 | 0.196958E+11 | 0.243681E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.109099E+11 | 0.178655E+11 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.130364E+11 | 0.212293E+11 | 0.253549E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.115676E+11 | 0.189620E+11 | 0.235306E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.125309E+11 | 0.204625E+11 | 0.248615E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.124961E+11 | 0.203636E+11 | 0.244160E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.116025E+11 | 0.190610E+11 | 0.239708E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.130364E+11 | 0.212293E+11 | 0.253549E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.115676E+11 | 0.189620E+11 | 0.235199E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.120254E+11 | 0.196958E+11 | 0.243735E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.119080E+11 | 0.194649E+11 | 0.238373E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.116025E+11 | 0.190610E+11 | 0.239654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.144308E+12 | 0.236053E+12 | 0.289614E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.109099E+11 | 0.178655E+11 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.130364E+11 | 0.212293E+11 | 0.253549E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.120254E+11 | 0.196958E+11 | 0.243680E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.109099E+11 | 0.178655E+11 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.130364E+11 | 0.212293E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.115676E+11 | 0.189620E+11 | 0.235305E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.125309E+11 | 0.204625E+11 | 0.248614E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.124961E+11 | 0.203636E+11 | 0.244159E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.116025E+11 | 0.190610E+11 | 0.239707E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.130364E+11 | 0.212293E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.115676E+11 | 0.189620E+11 | 0.235198E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.120254E+11 | 0.196958E+11 | 0.243734E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.119080E+11 | 0.194649E+11 | 0.238372E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.116025E+11 | 0.190610E+11 | 0.239653E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.144308E+12 | 0.236053E+12 | 0.289613E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.109099E+11 | 0.178655E+11 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.130364E+11 | 0.212293E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.120254E+11 | 0.196958E+11 | 0.243680E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.109099E+11 | 0.178655E+11 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.130364E+11 | 0.212293E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.115676E+11 | 0.189620E+11 | 0.235305E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.125309E+11 | 0.204625E+11 | 0.248614E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.124961E+11 | 0.203636E+11 | 0.244159E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.116025E+11 | 0.190610E+11 | 0.239707E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.130364E+11 | 0.212293E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.115676E+11 | 0.189620E+11 | 0.235198E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.120254E+11 | 0.196958E+11 | 0.243734E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.119080E+11 | 0.194649E+11 | 0.238372E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.116025E+11 | 0.190610E+11 | 0.239653E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.144308E+12 | 0.236053E+12 | 0.289613E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.109099E+11 | 0.178655E+11 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.130364E+11 | 0.212293E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150991E+10 | 0.156013E+10 | 0.305979E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1115542.15 | 0.358786E+09 |
February | 0.136985E+10 | 0.135710E+10 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2083093.52 | 0.279162E+09 |
March | 0.163685E+10 | 0.155628E+10 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6267099.20 | 0.296120E+09 |
April | 0.145243E+10 | 0.134836E+10 | 0.295462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13386798.29 | 0.125581E+09 |
May | 0.157338E+10 | 0.140368E+10 | 0.312174E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 54856424.66 | 19433823.57 |
June | 0.156900E+10 | 0.137640E+10 | 0.306580E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 51579228.82 | 11977429.59 |
July | 0.145680E+10 | 0.130523E+10 | 0.300989E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 76592198.61 | 2273609.99 |
August | 0.163685E+10 | 0.147739E+10 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 74655625.35 | 10855959.89 |
September | 0.145243E+10 | 0.136701E+10 | 0.295328E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 62173631.03 | 33369016.83 |
October | 0.150991E+10 | 0.146019E+10 | 0.306046E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 51379022.61 | 0.106778E+09 |
November | 0.149516E+10 | 0.153489E+10 | 0.299314E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5437026.05 | 0.188091E+09 |
December | 0.145680E+10 | 0.154783E+10 | 0.300922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3463557.48 | 0.330931E+09 |
Annual Sum or Average | 0.181194E+11 | 0.172945E+11 | 0.363654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.402989E+09 | 0.176336E+10 |
Minimum of Months | 0.136985E+10 | 0.130523E+10 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1115542.15 | 2273609.99 |
Maximum of Months | 0.163685E+10 | 0.156013E+10 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 76592198.61 | 0.358786E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.977749E+09 | 0.197184E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 670923.31 | 0.242856E+09 |
February | 0.882782E+09 | 0.857915E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1381481.56 | 0.187424E+09 |
March | 0.105485E+10 | 0.986044E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3929227.09 | 0.193820E+09 |
April | 0.936002E+09 | 0.864844E+09 | 0.190407E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9608970.61 | 78960273.94 |
May | 0.101394E+10 | 0.911283E+09 | 0.201177E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 37628207.38 | 11945630.71 |
June | 0.101113E+10 | 0.896486E+09 | 0.197572E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 37206105.73 | 6157371.49 |
July | 0.938820E+09 | 0.847972E+09 | 0.193969E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 57938822.53 | 807978.27 |
August | 0.105485E+10 | 0.953840E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 58318015.45 | 3798921.80 |
September | 0.936002E+09 | 0.875628E+09 | 0.190321E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 42138880.09 | 20353031.63 |
October | 0.973041E+09 | 0.929622E+09 | 0.197228E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 35501498.94 | 67229485.05 |
November | 0.963541E+09 | 0.966340E+09 | 0.192889E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3663547.63 | 0.123457E+09 |
December | 0.938820E+09 | 0.974471E+09 | 0.193926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2308643.81 | 0.211450E+09 |
Annual Sum or Average | 0.116768E+11 | 0.110422E+11 | 0.234352E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.290294E+09 | 0.114826E+10 |
Minimum of Months | 0.882782E+09 | 0.847972E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 670923.31 | 807978.27 |
Maximum of Months | 0.105485E+10 | 0.986044E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 58318015.45 | 0.242856E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150994E+10 | 0.146283E+10 | 0.305983E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 621750.85 | 0.390026E+09 |
February | 0.136988E+10 | 0.130224E+10 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1505739.08 | 0.298623E+09 |
March | 0.163688E+10 | 0.152767E+10 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4607797.95 | 0.301211E+09 |
April | 0.145246E+10 | 0.135197E+10 | 0.295467E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12219599.38 | 0.128150E+09 |
May | 0.157341E+10 | 0.142338E+10 | 0.312179E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 55460253.12 | 18900805.06 |
June | 0.156904E+10 | 0.139955E+10 | 0.306585E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 53058841.78 | 11289068.63 |
July | 0.145684E+10 | 0.132215E+10 | 0.300994E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 77704177.57 | 2183858.14 |
August | 0.163688E+10 | 0.148673E+10 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 73396119.31 | 11118185.73 |
September | 0.145246E+10 | 0.135916E+10 | 0.295333E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 57406673.34 | 35874289.78 |
October | 0.150994E+10 | 0.143339E+10 | 0.306051E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 42254422.77 | 0.121621E+09 |
November | 0.149520E+10 | 0.144957E+10 | 0.299318E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4036040.77 | 0.206085E+09 |
December | 0.145684E+10 | 0.144726E+10 | 0.300927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2608509.53 | 0.353457E+09 |
Annual Sum or Average | 0.181198E+11 | 0.169659E+11 | 0.363660E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.384880E+09 | 0.187854E+10 |
Minimum of Months | 0.136988E+10 | 0.130224E+10 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 621750.85 | 2183858.14 |
Maximum of Months | 0.163688E+10 | 0.152767E+10 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 77704177.57 | 0.390026E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.968103E+09 | 0.197183E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 585862.68 | 0.261744E+09 |
February | 0.882782E+09 | 0.856326E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1145865.41 | 0.210377E+09 |
March | 0.105485E+10 | 0.999440E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3408788.18 | 0.230346E+09 |
April | 0.936002E+09 | 0.874276E+09 | 0.190406E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7023783.64 | 0.108437E+09 |
May | 0.101394E+10 | 0.915029E+09 | 0.201175E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 35990116.06 | 20140152.76 |
June | 0.101113E+10 | 0.898337E+09 | 0.197570E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 31755106.83 | 13430885.52 |
July | 0.938820E+09 | 0.851795E+09 | 0.193968E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 44409290.83 | 5144610.07 |
August | 0.105485E+10 | 0.962444E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 42617578.28 | 16212617.85 |
September | 0.936002E+09 | 0.887175E+09 | 0.190319E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 39177656.92 | 31461477.98 |
October | 0.973041E+09 | 0.936444E+09 | 0.197226E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 30415462.43 | 91836255.85 |
November | 0.963541E+09 | 0.953804E+09 | 0.192888E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2956757.09 | 0.149400E+09 |
December | 0.938820E+09 | 0.954691E+09 | 0.193924E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1885387.95 | 0.262704E+09 |
Annual Sum or Average | 0.116768E+11 | 0.110579E+11 | 0.234351E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.241372E+09 | 0.140123E+10 |
Minimum of Months | 0.882782E+09 | 0.851795E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 585862.68 | 5144610.07 |
Maximum of Months | 0.105485E+10 | 0.999440E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 44409290.83 | 0.262704E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150991E+10 | 0.155122E+10 | 0.305979E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6286030.97 | 0.707357E+09 |
February | 0.136985E+10 | 0.135149E+10 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7266780.75 | 0.543050E+09 |
March | 0.163685E+10 | 0.155010E+10 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19640324.87 | 0.586908E+09 |
April | 0.145243E+10 | 0.134540E+10 | 0.295462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 30528404.23 | 0.263371E+09 |
May | 0.157338E+10 | 0.140175E+10 | 0.312174E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.123944E+09 | 46768129.58 |
June | 0.156900E+10 | 0.137370E+10 | 0.306580E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.113143E+09 | 35677730.79 |
July | 0.145680E+10 | 0.130426E+10 | 0.300989E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.157709E+09 | 14372346.16 |
August | 0.163685E+10 | 0.147601E+10 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.152732E+09 | 45939622.81 |
September | 0.145243E+10 | 0.136401E+10 | 0.295328E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.144174E+09 | 70211276.24 |
October | 0.150991E+10 | 0.145704E+10 | 0.306046E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.120315E+09 | 0.225046E+09 |
November | 0.149516E+10 | 0.152708E+10 | 0.299314E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17099639.37 | 0.366151E+09 |
December | 0.145680E+10 | 0.154059E+10 | 0.300922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11711518.24 | 0.635687E+09 |
Annual Sum or Average | 0.181194E+11 | 0.172427E+11 | 0.363654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.904549E+09 | 0.354054E+10 |
Minimum of Months | 0.136985E+10 | 0.130426E+10 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6286030.97 | 14372346.16 |
Maximum of Months | 0.163685E+10 | 0.155122E+10 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.157709E+09 | 0.707357E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.715730E+09 | 0.974146E+09 | 0.197184E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2533224.52 | 0.497013E+09 |
February | 0.649041E+09 | 0.856255E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3840918.00 | 0.385176E+09 |
March | 0.773965E+09 | 0.984111E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9566692.00 | 0.413744E+09 |
April | 0.688021E+09 | 0.864033E+09 | 0.190407E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19226810.09 | 0.190086E+09 |
May | 0.744847E+09 | 0.909279E+09 | 0.201177E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 80469356.10 | 33729300.76 |
June | 0.742030E+09 | 0.895366E+09 | 0.197572E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 75982934.53 | 24370128.03 |
July | 0.690839E+09 | 0.846613E+09 | 0.193969E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.104866E+09 | 11132018.36 |
August | 0.773965E+09 | 0.952688E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.101785E+09 | 31570232.85 |
September | 0.688021E+09 | 0.874560E+09 | 0.190321E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 92549775.73 | 48360560.16 |
October | 0.715730E+09 | 0.928134E+09 | 0.197228E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 75138881.46 | 0.158883E+09 |
November | 0.708685E+09 | 0.963898E+09 | 0.192889E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8918601.54 | 0.261448E+09 |
December | 0.690839E+09 | 0.971400E+09 | 0.193926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6142211.54 | 0.438637E+09 |
Annual Sum or Average | 0.858171E+10 | 0.110205E+11 | 0.234352E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.581020E+09 | 0.249415E+10 |
Minimum of Months | 0.649041E+09 | 0.846613E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2533224.52 | 11132018.36 |
Maximum of Months | 0.773965E+09 | 0.984111E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.104866E+09 | 0.497013E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150994E+10 | 0.146190E+10 | 0.305983E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1153077.58 | 0.869882E+09 |
February | 0.136988E+10 | 0.130122E+10 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3237973.74 | 0.658221E+09 |
March | 0.163688E+10 | 0.152475E+10 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10246179.74 | 0.650936E+09 |
April | 0.145246E+10 | 0.134958E+10 | 0.295467E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 26772233.44 | 0.290698E+09 |
May | 0.157341E+10 | 0.142053E+10 | 0.312179E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.124059E+09 | 47270769.08 |
June | 0.156904E+10 | 0.139732E+10 | 0.306585E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.116117E+09 | 33911186.54 |
July | 0.145684E+10 | 0.132006E+10 | 0.300994E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.159572E+09 | 14122060.47 |
August | 0.163688E+10 | 0.148429E+10 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.148212E+09 | 49019060.12 |
September | 0.145246E+10 | 0.135721E+10 | 0.295333E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.127549E+09 | 83521590.91 |
October | 0.150994E+10 | 0.143126E+10 | 0.306051E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 92485250.93 | 0.292658E+09 |
November | 0.149520E+10 | 0.144678E+10 | 0.299318E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8853185.66 | 0.459912E+09 |
December | 0.145684E+10 | 0.144595E+10 | 0.300927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5745725.82 | 0.777865E+09 |
Annual Sum or Average | 0.181198E+11 | 0.169408E+11 | 0.363660E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.824003E+09 | 0.422802E+10 |
Minimum of Months | 0.136988E+10 | 0.130122E+10 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1153077.58 | 14122060.47 |
Maximum of Months | 0.163688E+10 | 0.152475E+10 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.159572E+09 | 0.869882E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.965115E+09 | 0.197183E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2417844.84 | 0.519571E+09 |
February | 0.882782E+09 | 0.854421E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3389429.36 | 0.399283E+09 |
March | 0.105485E+10 | 0.996484E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10902772.90 | 0.428511E+09 |
April | 0.936002E+09 | 0.872462E+09 | 0.190406E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16930327.94 | 0.211107E+09 |
May | 0.101394E+10 | 0.913778E+09 | 0.201175E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 82283993.85 | 40814494.22 |
June | 0.101113E+10 | 0.896663E+09 | 0.197570E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 72421458.26 | 32260369.51 |
July | 0.938820E+09 | 0.849870E+09 | 0.193968E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.100893E+09 | 17248354.27 |
August | 0.105485E+10 | 0.958899E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 98636870.39 | 44081096.68 |
September | 0.936002E+09 | 0.885079E+09 | 0.190319E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 89943988.48 | 60501058.84 |
October | 0.973041E+09 | 0.934526E+09 | 0.197226E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 73168970.62 | 0.182898E+09 |
November | 0.963541E+09 | 0.951276E+09 | 0.192888E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9717830.39 | 0.271174E+09 |
December | 0.938820E+09 | 0.951540E+09 | 0.193924E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6050660.92 | 0.470466E+09 |
Annual Sum or Average | 0.116768E+11 | 0.110301E+11 | 0.234351E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.566757E+09 | 0.267792E+10 |
Minimum of Months | 0.882782E+09 | 0.849870E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2417844.84 | 17248354.27 |
Maximum of Months | 0.105485E+10 | 0.996484E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.100893E+09 | 0.519571E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150991E+10 | 0.155087E+10 | 0.305979E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9946214.38 | 0.799495E+09 |
February | 0.136985E+10 | 0.135111E+10 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10013773.14 | 0.613079E+09 |
March | 0.163685E+10 | 0.154992E+10 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23342249.92 | 0.678800E+09 |
April | 0.145243E+10 | 0.134533E+10 | 0.295462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 35217070.60 | 0.313262E+09 |
May | 0.157338E+10 | 0.140152E+10 | 0.312174E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.144710E+09 | 64626012.65 |
June | 0.156900E+10 | 0.137360E+10 | 0.306580E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.132218E+09 | 48634431.18 |
July | 0.145680E+10 | 0.130414E+10 | 0.300989E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.181809E+09 | 22811244.80 |
August | 0.163685E+10 | 0.147594E+10 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.179102E+09 | 62798580.38 |
September | 0.145243E+10 | 0.136351E+10 | 0.295328E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.166701E+09 | 91130823.02 |
October | 0.150991E+10 | 0.145697E+10 | 0.306046E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.139515E+09 | 0.266214E+09 |
November | 0.149516E+10 | 0.152681E+10 | 0.299314E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21873690.67 | 0.413855E+09 |
December | 0.145680E+10 | 0.154025E+10 | 0.300922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15518720.54 | 0.723814E+09 |
Annual Sum or Average | 0.181194E+11 | 0.172400E+11 | 0.363654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.105997E+10 | 0.409852E+10 |
Minimum of Months | 0.136985E+10 | 0.130414E+10 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9946214.38 | 22811244.80 |
Maximum of Months | 0.163685E+10 | 0.155087E+10 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.181809E+09 | 0.799495E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.974088E+09 | 0.197184E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3845858.89 | 0.564545E+09 |
February | 0.882782E+09 | 0.856176E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4711506.80 | 0.434921E+09 |
March | 0.105485E+10 | 0.984065E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10943269.73 | 0.485127E+09 |
April | 0.936002E+09 | 0.864033E+09 | 0.190407E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22074953.81 | 0.229483E+09 |
May | 0.101394E+10 | 0.909233E+09 | 0.201177E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 94687395.65 | 46169108.65 |
June | 0.101113E+10 | 0.895320E+09 | 0.197572E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 89316249.92 | 33181211.58 |
July | 0.938820E+09 | 0.846508E+09 | 0.193969E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.122771E+09 | 17116603.97 |
August | 0.105485E+10 | 0.952599E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.120393E+09 | 43140167.85 |
September | 0.936002E+09 | 0.874501E+09 | 0.190321E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.108360E+09 | 62883873.13 |
October | 0.973041E+09 | 0.928108E+09 | 0.197228E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 87836480.04 | 0.190192E+09 |
November | 0.963541E+09 | 0.963849E+09 | 0.192889E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10517546.32 | 0.301300E+09 |
December | 0.938820E+09 | 0.971207E+09 | 0.193926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7393556.94 | 0.503605E+09 |
Annual Sum or Average | 0.116768E+11 | 0.110197E+11 | 0.234352E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.682852E+09 | 0.291166E+10 |
Minimum of Months | 0.882782E+09 | 0.846508E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3845858.89 | 17116603.97 |
Maximum of Months | 0.105485E+10 | 0.984065E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.122771E+09 | 0.564545E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150994E+10 | 0.146190E+10 | 0.305983E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1388795.74 | 0.100276E+10 |
February | 0.136988E+10 | 0.130099E+10 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3770770.63 | 0.745267E+09 |
March | 0.163688E+10 | 0.152464E+10 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12150682.67 | 0.756903E+09 |
April | 0.145246E+10 | 0.134956E+10 | 0.295467E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 31534347.70 | 0.345921E+09 |
May | 0.157341E+10 | 0.142051E+10 | 0.312179E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.147251E+09 | 64402544.59 |
June | 0.156904E+10 | 0.139729E+10 | 0.306585E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.137189E+09 | 45659327.13 |
July | 0.145684E+10 | 0.132003E+10 | 0.300994E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.187602E+09 | 21905841.87 |
August | 0.163688E+10 | 0.148429E+10 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.177146E+09 | 65995060.51 |
September | 0.145246E+10 | 0.135710E+10 | 0.295333E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.152776E+09 | 0.106899E+09 |
October | 0.150994E+10 | 0.143126E+10 | 0.306051E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.110524E+09 | 0.351527E+09 |
November | 0.149520E+10 | 0.144678E+10 | 0.299318E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10733167.34 | 0.537790E+09 |
December | 0.145684E+10 | 0.144595E+10 | 0.300927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6858881.05 | 0.900149E+09 |
Annual Sum or Average | 0.181198E+11 | 0.169403E+11 | 0.363660E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.978924E+09 | 0.494517E+10 |
Minimum of Months | 0.136988E+10 | 0.130099E+10 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1388795.74 | 21905841.87 |
Maximum of Months | 0.163688E+10 | 0.152464E+10 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.187602E+09 | 0.100276E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.964986E+09 | 0.197183E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3505152.89 | 0.602613E+09 |
February | 0.882782E+09 | 0.854359E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4397954.47 | 0.458850E+09 |
March | 0.105485E+10 | 0.996370E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13408643.97 | 0.503342E+09 |
April | 0.936002E+09 | 0.872460E+09 | 0.190406E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20326907.37 | 0.252937E+09 |
May | 0.101394E+10 | 0.913720E+09 | 0.201175E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 99496882.49 | 53677984.10 |
June | 0.101113E+10 | 0.896663E+09 | 0.197570E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 87579477.93 | 41862346.32 |
July | 0.938820E+09 | 0.849856E+09 | 0.193968E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.121920E+09 | 23603890.45 |
August | 0.105485E+10 | 0.958896E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.119407E+09 | 57592515.72 |
September | 0.936002E+09 | 0.884889E+09 | 0.190319E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.109039E+09 | 75892191.63 |
October | 0.973041E+09 | 0.934526E+09 | 0.197226E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 88047795.33 | 0.218645E+09 |
November | 0.963541E+09 | 0.951101E+09 | 0.192888E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12619282.74 | 0.314620E+09 |
December | 0.938820E+09 | 0.951226E+09 | 0.193924E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7709913.22 | 0.547975E+09 |
Annual Sum or Average | 0.116768E+11 | 0.110291E+11 | 0.234351E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.687458E+09 | 0.315161E+10 |
Minimum of Months | 0.882782E+09 | 0.849856E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3505152.89 | 23603890.45 |
Maximum of Months | 0.105485E+10 | 0.996370E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.121920E+09 | 0.602613E+09 |
Report: SpaceGainsMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.174411E+09 | 0.553024E+09 | 0.521915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.158233E+09 | 0.501634E+09 | 0.942813E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.189074E+09 | 0.596080E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.167772E+09 | 0.532421E+09 | 0.201821E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.181743E+09 | 0.574552E+09 | 0.522616E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.181238E+09 | 0.571774E+09 | 0.101086E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.168277E+09 | 0.535199E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.189074E+09 | 0.596080E+09 | 0.208555E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.167772E+09 | 0.532421E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.174411E+09 | 0.553024E+09 | 0.104453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.172708E+09 | 0.546542E+09 | 0.151524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.168277E+09 | 0.535199E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.209299E+10 | 0.662795E+10 | 0.153881E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.158233E+09 | 0.501634E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.189074E+09 | 0.596080E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.174411E+09 | 0.553024E+09 | 0.521915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.158233E+09 | 0.501634E+09 | 0.942813E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.189074E+09 | 0.596080E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.167772E+09 | 0.532421E+09 | 0.201821E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.181743E+09 | 0.574552E+09 | 0.522616E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.181238E+09 | 0.571774E+09 | 0.101086E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.168277E+09 | 0.535199E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.189074E+09 | 0.596080E+09 | 0.208555E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.167772E+09 | 0.532421E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.174411E+09 | 0.553024E+09 | 0.104453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.172708E+09 | 0.546542E+09 | 0.151524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.168277E+09 | 0.535199E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.209299E+10 | 0.662795E+10 | 0.153881E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.158233E+09 | 0.501634E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.189074E+09 | 0.596080E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.174411E+09 | 0.553024E+09 | 0.521915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.158233E+09 | 0.501634E+09 | 0.942813E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.189074E+09 | 0.596080E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.167772E+09 | 0.532421E+09 | 0.201821E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.181743E+09 | 0.574552E+09 | 0.522616E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.181238E+09 | 0.571774E+09 | 0.101086E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.168277E+09 | 0.535199E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.189074E+09 | 0.596080E+09 | 0.208555E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.167772E+09 | 0.532421E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.174411E+09 | 0.553024E+09 | 0.104453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.172708E+09 | 0.546542E+09 | 0.151524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.168277E+09 | 0.535199E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.209299E+10 | 0.662795E+10 | 0.153881E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.158233E+09 | 0.501634E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.189074E+09 | 0.596080E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.377547E+10 | 0.618367E+10 | 0.254202E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.342526E+10 | 0.560905E+10 | 0.459203E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.409289E+10 | 0.666512E+10 | 0.762947E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.363176E+10 | 0.595330E+10 | 0.982982E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.393418E+10 | 0.642439E+10 | 0.254544E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.392325E+10 | 0.639333E+10 | 0.492345E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.364269E+10 | 0.598436E+10 | 0.762947E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.409289E+10 | 0.666512E+10 | 0.101578E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.363176E+10 | 0.595330E+10 | 0.246344E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.377547E+10 | 0.618367E+10 | 0.508746E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.373861E+10 | 0.611120E+10 | 0.738006E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.364269E+10 | 0.598436E+10 | 0.101681E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.453069E+11 | 0.741109E+11 | 0.749486E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.342526E+10 | 0.560905E+10 | 0.246344E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.409289E+10 | 0.666512E+10 | 0.101681E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 828043.59 | 0.820925E+09 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2148303.04 | 0.636930E+09 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8473256.75 | 0.662958E+09 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20114970.18 | 0.288082E+09 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 96470798.72 | 37692328.28 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 90016502.02 | 28326358.23 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.139164E+09 | 7389569.24 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.126142E+09 | 35177509.25 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.109552E+09 | 71057973.04 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 84145184.42 | 0.250235E+09 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7055801.49 | 0.432004E+09 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4544639.73 | 0.751609E+09 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.688655E+09 | 0.402239E+10 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 828043.59 | 7389569.24 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.139164E+09 | 0.820925E+09 |
Report: SpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3550950.26 | 0.135445E+10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6191411.88 | 0.105144E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21798670.02 | 0.109358E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38201536.05 | 0.481535E+09 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.179664E+09 | 62967886.70 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.164620E+09 | 50583907.48 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.250017E+09 | 15064994.71 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.223329E+09 | 70027092.92 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.209960E+09 | 0.113234E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.158610E+09 | 0.416597E+09 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15754890.07 | 0.711314E+09 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10731604.79 | 0.121962E+10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.128243E+10 | 0.664041E+10 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3550950.26 | 15064994.71 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.250017E+09 | 0.135445E+10 |
Report: SpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1998240.31 | 0.135092E+10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2653649.90 | 0.104159E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12509985.29 | 0.114474E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25703564.74 | 0.535444E+09 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.160192E+09 | 79718260.62 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.150885E+09 | 61009056.21 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.226169E+09 | 24206348.28 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.211454E+09 | 86944086.33 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.200040E+09 | 0.128366E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.131887E+09 | 0.438033E+09 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11417179.46 | 0.716514E+09 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8380837.26 | 0.122316E+10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.114329E+10 | 0.683065E+10 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1998240.31 | 24206348.28 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.226169E+09 | 0.135092E+10 |
Report: PeakSpaceGainsMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 17832.21 | 02-JAN-10:09 | 22950.34 | 02-JAN-08:09 | 13457.54 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 17832.21 | 01-FEB-10:09 | 22950.34 | 01-FEB-08:09 | 13457.54 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 17832.21 | 01-MAR-10:09 | 22950.34 | 01-MAR-08:09 | 13457.54 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 17832.21 | 03-APR-09:09 | 22950.34 | 03-APR-07:10 | 13457.54 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 17832.21 | 01-MAY-09:09 | 22950.34 | 01-MAY-07:10 | 13457.54 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 17832.21 | 01-JUN-09:09 | 22950.34 | 01-JUN-07:10 | 13457.54 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 17832.21 | 03-JUL-09:09 | 22950.34 | 03-JUL-07:10 | 13457.54 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 17832.21 | 01-AUG-09:09 | 22950.34 | 01-AUG-07:10 | 13457.54 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 17832.21 | 01-SEP-09:09 | 22950.34 | 01-SEP-07:10 | 13457.54 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 17832.21 | 02-OCT-09:09 | 22950.34 | 02-OCT-07:10 | 13457.54 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 17832.21 | 01-NOV-09:09 | 22950.34 | 01-NOV-07:10 | 13457.54 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 17832.21 | 01-DEC-10:09 | 22950.34 | 01-DEC-08:09 | 13457.54 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 17832.21 | 22950.34 | 13457.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 17832.21 | 22950.34 | 13457.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 16014.58 | 02-JAN-10:09 | 20611.01 | 02-JAN-08:09 | 17206.63 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 16014.58 | 01-FEB-10:09 | 20611.01 | 01-FEB-08:09 | 17206.63 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 16014.58 | 01-MAR-10:09 | 20611.01 | 01-MAR-08:09 | 17206.63 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 16014.58 | 03-APR-09:09 | 20611.01 | 03-APR-07:10 | 17206.63 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 16014.58 | 01-MAY-09:09 | 20611.01 | 01-MAY-07:10 | 17206.63 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 16014.58 | 01-JUN-09:09 | 20611.01 | 01-JUN-07:10 | 17206.63 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 16014.58 | 03-JUL-09:09 | 20611.01 | 03-JUL-07:10 | 17206.63 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 16014.58 | 01-AUG-09:09 | 20611.01 | 01-AUG-07:10 | 17206.63 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 16014.58 | 01-SEP-09:09 | 20611.01 | 01-SEP-07:10 | 17206.63 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 16014.58 | 02-OCT-09:09 | 20611.01 | 02-OCT-07:10 | 17206.63 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 16014.58 | 01-NOV-09:09 | 20611.01 | 01-NOV-07:10 | 17206.63 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 16014.58 | 01-DEC-10:09 | 20611.01 | 01-DEC-08:09 | 17206.63 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 16014.58 | 20611.01 | 17206.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 16014.58 | 20611.01 | 17206.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 16014.58 | 02-JAN-10:09 | 20611.01 | 02-JAN-08:09 | 17206.56 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 16014.58 | 01-FEB-10:09 | 20611.01 | 01-FEB-08:09 | 17206.56 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 16014.58 | 01-MAR-10:09 | 20611.01 | 01-MAR-08:09 | 17206.56 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 16014.58 | 03-APR-09:09 | 20611.01 | 03-APR-07:10 | 17206.56 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 16014.58 | 01-MAY-09:09 | 20611.01 | 01-MAY-07:10 | 17206.56 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 16014.58 | 01-JUN-09:09 | 20611.01 | 01-JUN-07:10 | 17206.56 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 16014.58 | 03-JUL-09:09 | 20611.01 | 03-JUL-07:10 | 17206.56 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 16014.58 | 01-AUG-09:09 | 20611.01 | 01-AUG-07:10 | 17206.56 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 16014.58 | 01-SEP-09:09 | 20611.01 | 01-SEP-07:10 | 17206.56 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 16014.58 | 02-OCT-09:09 | 20611.01 | 02-OCT-07:10 | 17206.56 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 16014.58 | 01-NOV-09:09 | 20611.01 | 01-NOV-07:10 | 17206.56 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 16014.58 | 01-DEC-10:09 | 20611.01 | 01-DEC-08:09 | 17206.56 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 16014.58 | 20611.01 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 16014.58 | 20611.01 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 16014.58 | 02-JAN-10:09 | 20611.01 | 02-JAN-08:09 | 17206.56 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 16014.58 | 01-FEB-10:09 | 20611.01 | 01-FEB-08:09 | 17206.56 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 16014.58 | 01-MAR-10:09 | 20611.01 | 01-MAR-08:09 | 17206.56 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 16014.58 | 03-APR-09:09 | 20611.01 | 03-APR-07:10 | 17206.56 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 16014.58 | 01-MAY-09:09 | 20611.01 | 01-MAY-07:10 | 17206.56 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 16014.58 | 01-JUN-09:09 | 20611.01 | 01-JUN-07:10 | 17206.56 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 16014.58 | 03-JUL-09:09 | 20611.01 | 03-JUL-07:10 | 17206.56 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 16014.58 | 01-AUG-09:09 | 20611.01 | 01-AUG-07:10 | 17206.56 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 16014.58 | 01-SEP-09:09 | 20611.01 | 01-SEP-07:10 | 17206.56 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 16014.58 | 02-OCT-09:09 | 20611.01 | 02-OCT-07:10 | 17206.56 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 16014.58 | 01-NOV-09:09 | 20611.01 | 01-NOV-07:10 | 17206.56 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 16014.58 | 01-DEC-10:09 | 20611.01 | 01-DEC-08:09 | 17206.56 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 16014.58 | 20611.01 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 16014.58 | 20611.01 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.79 | 02-JAN-10:09 | 2255.20 | 02-JAN-08:09 | 2160.55 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 57.50 | 16-JAN-15:00 | 679.61 | 09-JAN-05:00 |
February | 2010.79 | 01-FEB-10:09 | 2255.20 | 01-FEB-08:09 | 2160.55 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 49.90 | 02-FEB-13:00 | 945.27 | 05-FEB-08:00 |
March | 2010.79 | 01-MAR-10:09 | 2255.20 | 27-MAR-07:10 | 2160.55 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 109.69 | 05-MAR-12:53 | 813.23 | 20-MAR-22:00 |
April | 2010.79 | 03-APR-09:09 | 2255.20 | 06-APR-07:10 | 2160.55 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 163.24 | 29-APR-17:10 | 498.13 | 01-APR-21:00 |
May | 2010.79 | 01-MAY-09:09 | 1803.00 | 23-MAY-07:19 | 2160.55 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 229.08 | 21-MAY-14:00 | 110.90 | 14-MAY-12:00 |
June | 2010.79 | 01-JUN-09:09 | 1350.81 | 16-JUN-07:10 | 2160.55 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 270.72 | 10-JUN-17:02 | 153.88 | 06-JUN-22:00 |
July | 2010.79 | 03-JUL-09:09 | 1470.28 | 14-JUL-07:10 | 2160.55 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 256.01 | 22-JUL-18:50 | 89.69 | 30-JUL-11:00 |
August | 2010.79 | 01-AUG-09:09 | 1803.00 | 08-AUG-07:30 | 2160.55 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 309.19 | 20-AUG-13:52 | 194.71 | 25-AUG-23:55 |
September | 2010.79 | 01-SEP-09:09 | 2255.20 | 26-SEP-07:10 | 2160.55 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 324.97 | 09-SEP-22:53 | 210.57 | 05-SEP-03:00 |
October | 2010.79 | 02-OCT-09:09 | 2587.92 | 25-OCT-07:10 | 2160.55 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 397.35 | 09-OCT-14:00 | 402.97 | 29-OCT-02:00 |
November | 2010.79 | 01-NOV-09:09 | 2255.20 | 01-NOV-07:10 | 2160.55 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 65.43 | 05-NOV-13:00 | 583.96 | 12-NOV-08:00 |
December | 2010.79 | 01-DEC-10:09 | 2587.92 | 12-DEC-08:09 | 2160.55 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 63.53 | 10-DEC-14:50 | 875.34 | 20-DEC-01:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.79 | 1350.81 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 49.90 | 89.69 | |||||
Maximum of Months | 2010.79 | 2587.92 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 397.35 | 945.27 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 1453.34 | 03-JAN-16:00 | 1392.34 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 36.87 | 16-JAN-15:00 | 461.25 | 22-JAN-08:00 |
February | 1295.83 | 01-FEB-10:09 | 1453.34 | 01-FEB-08:09 | 1392.34 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 39.95 | 20-FEB-15:00 | 694.80 | 05-FEB-10:00 |
March | 1295.83 | 01-MAR-10:09 | 1453.34 | 27-MAR-07:10 | 1392.34 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 71.61 | 05-MAR-12:53 | 530.37 | 20-MAR-22:00 |
April | 1295.83 | 03-APR-09:09 | 1453.34 | 14-APR-07:10 | 1392.34 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 133.42 | 29-APR-17:50 | 318.44 | 01-APR-21:00 |
May | 1295.83 | 01-MAY-09:09 | 1161.92 | 30-MAY-15:30 | 1392.34 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 181.73 | 21-MAY-14:00 | 95.65 | 14-MAY-12:00 |
June | 1295.83 | 01-JUN-09:09 | 870.51 | 16-JUN-14:30 | 1392.34 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 201.30 | 10-JUN-17:02 | 93.28 | 06-JUN-22:10 |
July | 1295.83 | 03-JUL-09:09 | 870.51 | 11-JUL-15:39 | 1392.34 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 198.05 | 22-JUL-18:50 | 92.26 | 30-JUL-11:00 |
August | 1295.83 | 01-AUG-09:09 | 947.51 | 21-AUG-07:10 | 1392.34 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 226.75 | 20-AUG-14:10 | 116.53 | 25-AUG-23:55 |
September | 1295.83 | 01-SEP-09:09 | 1453.34 | 26-SEP-07:10 | 1392.34 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 231.18 | 09-SEP-22:53 | 138.13 | 05-SEP-03:00 |
October | 1295.83 | 02-OCT-09:09 | 1667.75 | 25-OCT-07:10 | 1392.34 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 278.47 | 09-OCT-14:00 | 263.86 | 29-OCT-02:00 |
November | 1295.83 | 01-NOV-09:09 | 1667.75 | 21-NOV-16:00 | 1392.34 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 46.76 | 05-NOV-13:00 | 458.35 | 12-NOV-08:20 |
December | 1295.83 | 01-DEC-10:09 | 1667.75 | 12-DEC-08:09 | 1392.34 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 47.53 | 10-DEC-14:50 | 559.68 | 20-DEC-01:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 870.51 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 36.87 | 92.26 | |||||
Maximum of Months | 1295.83 | 1667.75 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 278.47 | 694.80 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.83 | 02-JAN-10:09 | 2255.25 | 13-JAN-08:09 | 2160.58 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 17.37 | 19-JAN-12:10 | 680.57 | 26-JAN-03:00 |
February | 2010.83 | 01-FEB-10:09 | 2255.25 | 01-FEB-08:09 | 2160.58 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 49.90 | 02-FEB-13:00 | 952.04 | 05-FEB-10:00 |
March | 2010.83 | 01-MAR-10:09 | 2255.25 | 27-MAR-07:10 | 2160.58 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 70.24 | 26-MAR-13:45 | 816.87 | 20-MAR-22:00 |
April | 2010.83 | 03-APR-09:09 | 2255.25 | 06-APR-07:10 | 2160.58 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 150.86 | 29-APR-17:10 | 499.03 | 01-APR-21:00 |
May | 2010.83 | 01-MAY-09:09 | 1803.04 | 23-MAY-07:10 | 2160.58 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 231.04 | 21-MAY-14:00 | 116.66 | 14-MAY-12:00 |
June | 2010.83 | 01-JUN-09:09 | 1350.84 | 02-JUN-07:10 | 2160.58 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 284.35 | 10-JUN-17:02 | 151.41 | 06-JUN-22:00 |
July | 2010.83 | 03-JUL-09:09 | 1803.04 | 14-JUL-07:10 | 2160.58 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 265.99 | 22-JUL-18:50 | 95.67 | 30-JUL-11:00 |
August | 2010.83 | 01-AUG-09:09 | 1803.04 | 08-AUG-07:10 | 2160.58 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 308.21 | 20-AUG-14:06 | 196.50 | 25-AUG-23:55 |
September | 2010.83 | 01-SEP-09:09 | 2255.25 | 26-SEP-07:10 | 2160.58 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 316.42 | 09-SEP-22:53 | 216.66 | 05-SEP-03:00 |
October | 2010.83 | 02-OCT-09:09 | 2587.98 | 25-OCT-07:10 | 2160.58 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 354.13 | 09-OCT-13:55 | 415.92 | 29-OCT-02:00 |
November | 2010.83 | 01-NOV-09:09 | 2255.25 | 01-NOV-07:10 | 2160.58 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 36.96 | 07-NOV-13:00 | 660.00 | 12-NOV-11:00 |
December | 2010.83 | 01-DEC-10:09 | 2587.98 | 12-DEC-08:09 | 2160.58 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 36.29 | 13-DEC-14:00 | 854.45 | 20-DEC-01:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.83 | 1350.84 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 17.37 | 95.67 | |||||
Maximum of Months | 2010.83 | 2587.98 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 354.13 | 952.04 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 1453.34 | 02-JAN-08:09 | 1392.33 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 22.17 | 16-JAN-13:00 | 477.46 | 26-JAN-03:00 |
February | 1295.83 | 01-FEB-10:09 | 1667.75 | 01-FEB-08:09 | 1392.33 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 33.27 | 02-FEB-13:00 | 668.07 | 05-FEB-08:00 |
March | 1295.83 | 01-MAR-10:09 | 1453.34 | 01-MAR-08:09 | 1392.33 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 59.56 | 05-MAR-12:53 | 605.00 | 20-MAR-22:00 |
April | 1295.83 | 03-APR-09:09 | 1453.34 | 06-APR-07:10 | 1392.33 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 58.14 | 29-APR-17:04 | 413.34 | 01-APR-21:00 |
May | 1295.83 | 01-MAY-09:09 | 1161.92 | 01-MAY-07:10 | 1392.33 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 171.80 | 21-MAY-14:00 | 90.37 | 09-MAY-02:00 |
June | 1295.83 | 01-JUN-09:09 | 1161.92 | 16-JUN-07:10 | 1392.33 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 166.04 | 10-JUN-17:07 | 143.95 | 06-JUN-22:00 |
July | 1295.83 | 03-JUL-09:09 | 1161.92 | 11-JUL-07:10 | 1392.33 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 152.33 | 02-JUL-11:10 | 87.58 | 30-JUL-11:00 |
August | 1295.83 | 01-AUG-09:09 | 1453.34 | 08-AUG-07:10 | 1392.33 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 214.48 | 20-AUG-14:06 | 180.83 | 25-AUG-23:55 |
September | 1295.83 | 01-SEP-09:09 | 1453.34 | 13-SEP-07:10 | 1392.33 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 211.27 | 09-SEP-22:50 | 160.01 | 05-SEP-03:00 |
October | 1295.83 | 02-OCT-09:09 | 1667.75 | 25-OCT-07:10 | 1392.33 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 259.78 | 09-OCT-13:55 | 314.17 | 29-OCT-02:00 |
November | 1295.83 | 01-NOV-09:09 | 1667.75 | 01-NOV-07:10 | 1392.33 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 33.00 | 11-NOV-12:10 | 428.79 | 12-NOV-08:00 |
December | 1295.83 | 01-DEC-10:09 | 1667.75 | 12-DEC-08:09 | 1392.33 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 24.20 | 13-DEC-14:00 | 666.67 | 20-DEC-01:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 1161.92 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 22.17 | 87.58 | |||||
Maximum of Months | 1295.83 | 1667.75 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 259.78 | 668.07 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.79 | 02-JAN-10:09 | 2255.20 | 13-JAN-08:09 | 2160.55 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 192.15 | 16-JAN-15:00 | 1439.38 | 21-JAN-05:55 |
February | 2010.79 | 01-FEB-10:09 | 2255.20 | 01-FEB-08:09 | 2160.55 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 247.75 | 20-FEB-14:53 | 1871.10 | 05-FEB-07:53 |
March | 2010.79 | 01-MAR-10:09 | 2255.20 | 27-MAR-07:10 | 2160.55 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 356.20 | 05-MAR-12:30 | 1659.51 | 20-MAR-22:00 |
April | 2010.79 | 03-APR-09:09 | 2255.20 | 14-APR-07:10 | 2160.55 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 408.15 | 29-APR-17:01 | 963.79 | 01-APR-17:53 |
May | 2010.79 | 01-MAY-09:09 | 1803.00 | 23-MAY-07:19 | 2160.55 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 515.39 | 07-MAY-13:52 | 204.54 | 09-MAY-02:00 |
June | 2010.79 | 01-JUN-09:09 | 1350.81 | 16-JUN-07:10 | 2160.55 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 640.14 | 10-JUN-17:02 | 305.71 | 06-JUN-22:00 |
July | 2010.79 | 03-JUL-09:09 | 1470.28 | 14-JUL-07:10 | 2160.55 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 595.68 | 22-JUL-18:50 | 192.23 | 30-JUL-11:00 |
August | 2010.79 | 01-AUG-09:09 | 1803.00 | 08-AUG-07:30 | 2160.55 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 740.71 | 20-AUG-14:00 | 435.56 | 25-AUG-23:55 |
September | 2010.79 | 01-SEP-09:09 | 2255.20 | 26-SEP-07:10 | 2160.55 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 761.31 | 09-SEP-17:02 | 413.19 | 05-SEP-03:00 |
October | 2010.79 | 02-OCT-09:09 | 2587.92 | 25-OCT-07:10 | 2160.55 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 914.82 | 09-OCT-14:00 | 775.60 | 29-OCT-02:00 |
November | 2010.79 | 01-NOV-09:09 | 2255.20 | 01-NOV-07:10 | 2160.55 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 226.49 | 11-NOV-12:50 | 1184.55 | 12-NOV-06:55 |
December | 2010.79 | 01-DEC-10:09 | 2587.92 | 12-DEC-08:09 | 2160.55 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 211.32 | 10-DEC-15:10 | 1691.67 | 20-DEC-01:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.79 | 1350.81 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 192.15 | 192.23 | |||||
Maximum of Months | 2010.79 | 2587.92 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 914.82 | 1871.10 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1239.33 | 02-JAN-08:09 | 1453.34 | 31-JAN-08:09 | 1392.34 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 104.14 | 16-JAN-15:00 | 957.89 | 21-JAN-05:55 |
February | 1239.33 | 01-FEB-08:09 | 1453.34 | 01-FEB-08:09 | 1392.34 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 157.66 | 20-FEB-15:10 | 1400.03 | 05-FEB-10:00 |
March | 1239.33 | 01-MAR-08:09 | 1376.34 | 27-MAR-07:10 | 1392.34 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 173.21 | 05-MAR-13:10 | 1115.94 | 20-MAR-22:00 |
April | 1239.33 | 03-APR-07:10 | 1453.34 | 14-APR-07:10 | 1392.34 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 296.17 | 29-APR-17:50 | 655.48 | 01-APR-21:00 |
May | 1239.33 | 01-MAY-07:10 | 947.51 | 23-MAY-07:19 | 1392.34 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 389.68 | 21-MAY-13:50 | 188.73 | 14-MAY-12:10 |
June | 1239.33 | 01-JUN-07:10 | 870.51 | 27-JUN-13:30 | 1392.34 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 464.26 | 10-JUN-17:02 | 208.17 | 11-JUN-08:00 |
July | 1239.33 | 03-JUL-07:10 | 870.51 | 11-JUL-15:39 | 1392.34 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 442.79 | 22-JUL-18:50 | 259.02 | 30-JUL-11:00 |
August | 1239.33 | 01-AUG-07:10 | 947.51 | 21-AUG-07:10 | 1392.34 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 495.97 | 20-AUG-13:52 | 293.84 | 25-AUG-23:55 |
September | 1239.33 | 01-SEP-07:10 | 1161.92 | 26-SEP-07:10 | 1392.34 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 532.38 | 09-SEP-22:53 | 288.89 | 05-SEP-03:00 |
October | 1239.33 | 02-OCT-07:10 | 1667.75 | 25-OCT-07:10 | 1392.34 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 630.15 | 09-OCT-14:00 | 530.90 | 29-OCT-02:00 |
November | 1239.33 | 01-NOV-07:10 | 1667.75 | 21-NOV-16:00 | 1392.34 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 119.56 | 05-NOV-13:00 | 970.57 | 12-NOV-09:00 |
December | 1239.33 | 01-DEC-08:09 | 1667.75 | 12-DEC-08:09 | 1392.34 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 122.82 | 10-DEC-15:10 | 1128.63 | 20-DEC-01:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1239.33 | 870.51 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 104.14 | 188.73 | |||||
Maximum of Months | 1239.33 | 1667.75 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 630.15 | 1400.03 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.83 | 02-JAN-10:09 | 2255.25 | 13-JAN-08:09 | 2160.58 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 34.48 | 19-JAN-12:00 | 1591.96 | 22-JAN-16:53 |
February | 2010.83 | 01-FEB-10:09 | 2255.25 | 01-FEB-08:09 | 2160.58 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 114.06 | 02-FEB-13:00 | 2002.82 | 05-FEB-10:00 |
March | 2010.83 | 01-MAR-10:09 | 2255.25 | 27-MAR-07:10 | 2160.58 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 158.17 | 26-MAR-13:55 | 1746.39 | 20-MAR-22:00 |
April | 2010.83 | 03-APR-09:09 | 2255.25 | 06-APR-07:10 | 2160.58 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 357.22 | 29-APR-17:01 | 1053.51 | 01-APR-17:53 |
May | 2010.83 | 01-MAY-09:09 | 1803.04 | 23-MAY-07:10 | 2160.58 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 499.83 | 21-MAY-13:50 | 210.38 | 09-MAY-02:00 |
June | 2010.83 | 01-JUN-09:09 | 1350.84 | 02-JUN-07:10 | 2160.58 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 668.13 | 10-JUN-17:02 | 304.89 | 06-JUN-22:00 |
July | 2010.83 | 03-JUL-09:09 | 1470.31 | 11-JUL-07:10 | 2160.58 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 616.90 | 22-JUL-18:50 | 204.03 | 30-JUL-11:00 |
August | 2010.83 | 01-AUG-09:09 | 1803.04 | 08-AUG-07:10 | 2160.58 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 726.74 | 20-AUG-13:52 | 447.11 | 25-AUG-23:55 |
September | 2010.83 | 01-SEP-09:09 | 2255.25 | 26-SEP-07:10 | 2160.58 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 716.84 | 09-SEP-17:02 | 452.74 | 05-SEP-03:00 |
October | 2010.83 | 02-OCT-09:09 | 2587.98 | 25-OCT-07:10 | 2160.58 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 780.92 | 09-OCT-13:58 | 901.44 | 29-OCT-02:00 |
November | 2010.83 | 01-NOV-09:09 | 2255.25 | 01-NOV-07:10 | 2160.58 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 79.95 | 07-NOV-13:00 | 1400.74 | 12-NOV-10:53 |
December | 2010.83 | 01-DEC-10:09 | 2587.98 | 12-DEC-08:09 | 2160.58 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 83.26 | 13-DEC-14:00 | 1759.36 | 20-DEC-01:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.83 | 1350.84 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 34.48 | 204.03 | |||||
Maximum of Months | 2010.83 | 2587.98 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 780.92 | 2002.82 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 1453.34 | 02-JAN-08:09 | 1392.33 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 93.80 | 16-JAN-13:32 | 956.17 | 21-JAN-06:00 |
February | 1295.83 | 01-FEB-10:09 | 1453.34 | 01-FEB-08:09 | 1392.33 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 89.74 | 26-FEB-13:10 | 1279.81 | 05-FEB-07:53 |
March | 1295.83 | 01-MAR-10:09 | 1453.34 | 01-MAR-08:09 | 1392.33 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 247.65 | 05-MAR-12:30 | 1173.11 | 20-MAR-22:00 |
April | 1295.83 | 03-APR-09:09 | 1453.34 | 06-APR-07:10 | 1392.33 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 155.33 | 23-APR-13:50 | 765.73 | 01-APR-17:53 |
May | 1295.83 | 01-MAY-09:09 | 1161.92 | 01-MAY-07:10 | 1392.33 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 382.87 | 21-MAY-13:50 | 191.36 | 06-MAY-19:53 |
June | 1295.83 | 01-JUN-09:09 | 1161.92 | 16-JUN-07:10 | 1392.33 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 379.52 | 10-JUN-17:07 | 239.09 | 06-JUN-22:00 |
July | 1295.83 | 03-JUL-09:09 | 1161.92 | 11-JUL-07:10 | 1392.33 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 375.89 | 16-JUL-12:40 | 165.14 | 31-JUL-01:55 |
August | 1295.83 | 01-AUG-09:09 | 1376.34 | 08-AUG-07:10 | 1392.33 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 511.31 | 20-AUG-14:00 | 331.30 | 25-AUG-23:55 |
September | 1295.83 | 01-SEP-09:09 | 1453.34 | 13-SEP-07:10 | 1392.33 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 485.56 | 09-SEP-22:50 | 308.90 | 05-SEP-03:00 |
October | 1295.83 | 02-OCT-09:09 | 1667.75 | 25-OCT-07:10 | 1392.33 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 635.58 | 09-OCT-12:00 | 584.39 | 29-OCT-02:00 |
November | 1295.83 | 01-NOV-09:09 | 1667.75 | 01-NOV-07:10 | 1392.33 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 161.64 | 11-NOV-12:50 | 832.21 | 12-NOV-06:55 |
December | 1295.83 | 01-DEC-10:09 | 1667.75 | 12-DEC-08:09 | 1392.33 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 137.14 | 10-DEC-11:10 | 1164.11 | 20-DEC-01:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 1161.92 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 89.74 | 165.14 | |||||
Maximum of Months | 1295.83 | 1667.75 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 635.58 | 1279.81 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.79 | 02-JAN-10:09 | 2255.20 | 13-JAN-08:09 | 2160.55 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 283.60 | 15-JAN-14:00 | 1790.97 | 21-JAN-06:00 |
February | 2010.79 | 01-FEB-10:09 | 2255.20 | 01-FEB-08:09 | 2160.55 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 344.46 | 20-FEB-14:53 | 2289.83 | 05-FEB-08:00 |
March | 2010.79 | 01-MAR-10:09 | 2255.20 | 27-MAR-07:10 | 2160.55 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 440.85 | 05-MAR-12:50 | 1972.25 | 20-MAR-21:03 |
April | 2010.79 | 03-APR-09:09 | 2255.20 | 14-APR-07:10 | 2160.55 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 449.54 | 29-APR-17:01 | 1169.89 | 01-APR-17:53 |
May | 2010.79 | 01-MAY-09:09 | 1803.00 | 23-MAY-07:19 | 2160.55 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 617.03 | 07-MAY-13:52 | 259.91 | 09-MAY-02:00 |
June | 2010.79 | 01-JUN-09:09 | 1350.81 | 27-JUN-11:30 | 2160.55 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 735.94 | 10-JUN-17:02 | 389.80 | 06-JUN-21:20 |
July | 2010.79 | 03-JUL-09:09 | 1470.28 | 14-JUL-07:10 | 2160.55 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 639.63 | 22-JUL-18:50 | 294.73 | 30-JUL-11:00 |
August | 2010.79 | 01-AUG-09:09 | 1803.00 | 08-AUG-07:30 | 2160.55 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 886.80 | 20-AUG-13:54 | 529.80 | 25-AUG-23:55 |
September | 2010.79 | 01-SEP-09:09 | 2255.20 | 26-SEP-07:10 | 2160.55 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 902.12 | 09-SEP-17:02 | 548.30 | 05-SEP-03:00 |
October | 2010.79 | 02-OCT-09:09 | 2587.92 | 25-OCT-07:10 | 2160.55 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1059.38 | 09-OCT-14:00 | 835.12 | 28-OCT-04:53 |
November | 2010.79 | 01-NOV-09:09 | 2255.20 | 01-NOV-07:10 | 2160.55 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 290.60 | 05-NOV-13:00 | 1385.84 | 12-NOV-06:55 |
December | 2010.79 | 01-DEC-10:09 | 2587.92 | 12-DEC-08:09 | 2160.55 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 251.68 | 10-DEC-11:00 | 1844.44 | 20-DEC-01:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.79 | 1350.81 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 251.68 | 259.91 | |||||
Maximum of Months | 2010.79 | 2587.92 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 1059.38 | 2289.83 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 1453.34 | 31-JAN-08:09 | 1392.34 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 163.16 | 15-JAN-14:00 | 1193.97 | 21-JAN-05:57 |
February | 1295.83 | 01-FEB-10:09 | 1453.34 | 01-FEB-08:09 | 1392.34 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 221.78 | 20-FEB-15:10 | 1526.60 | 05-FEB-08:00 |
March | 1295.83 | 01-MAR-10:09 | 1376.34 | 27-MAR-07:10 | 1392.34 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 221.60 | 05-MAR-13:10 | 1329.68 | 20-MAR-21:25 |
April | 1295.83 | 03-APR-09:09 | 1453.34 | 14-APR-07:10 | 1392.34 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 327.68 | 29-APR-17:50 | 801.19 | 01-APR-17:53 |
May | 1295.83 | 01-MAY-09:09 | 947.51 | 23-MAY-07:19 | 1392.34 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 463.24 | 21-MAY-14:00 | 254.88 | 14-MAY-12:10 |
June | 1295.83 | 01-JUN-09:09 | 870.51 | 27-JUN-13:30 | 1392.34 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 536.26 | 10-JUN-17:02 | 262.76 | 11-JUN-08:00 |
July | 1295.83 | 03-JUL-09:09 | 870.51 | 11-JUL-15:39 | 1392.34 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 480.36 | 22-JUL-18:50 | 346.33 | 30-JUL-11:00 |
August | 1295.83 | 01-AUG-09:09 | 947.51 | 21-AUG-07:10 | 1392.34 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 591.91 | 20-AUG-13:52 | 358.51 | 25-AUG-23:55 |
September | 1295.83 | 01-SEP-09:09 | 1161.92 | 26-SEP-07:10 | 1392.34 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 632.09 | 09-SEP-22:50 | 378.66 | 05-SEP-03:00 |
October | 1295.83 | 02-OCT-09:09 | 1667.75 | 25-OCT-07:10 | 1392.34 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 789.68 | 09-OCT-14:00 | 567.51 | 29-OCT-02:00 |
November | 1295.83 | 01-NOV-09:09 | 1667.75 | 21-NOV-16:00 | 1392.34 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 157.21 | 05-NOV-13:00 | 1132.72 | 12-NOV-08:40 |
December | 1295.83 | 01-DEC-10:09 | 1667.75 | 12-DEC-08:09 | 1392.34 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 149.98 | 10-DEC-15:00 | 1235.44 | 20-DEC-01:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 870.51 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 149.98 | 254.88 | |||||
Maximum of Months | 1295.83 | 1667.75 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 789.68 | 1526.60 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.83 | 02-JAN-10:09 | 2255.25 | 13-JAN-08:09 | 2160.58 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 47.08 | 19-JAN-12:00 | 1883.88 | 22-JAN-16:53 |
February | 2010.83 | 01-FEB-10:09 | 2255.25 | 01-FEB-08:09 | 2160.58 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 137.94 | 02-FEB-13:00 | 2289.86 | 05-FEB-08:00 |
March | 2010.83 | 01-MAR-10:09 | 2255.25 | 27-MAR-07:10 | 2160.58 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 190.81 | 26-MAR-13:45 | 2061.15 | 20-MAR-21:13 |
April | 2010.83 | 03-APR-09:09 | 2255.25 | 06-APR-07:10 | 2160.58 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 399.04 | 29-APR-17:01 | 1281.98 | 01-APR-17:53 |
May | 2010.83 | 01-MAY-09:09 | 1803.04 | 23-MAY-07:10 | 2160.58 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 630.26 | 21-MAY-13:40 | 266.70 | 09-MAY-02:00 |
June | 2010.83 | 01-JUN-09:09 | 1350.84 | 02-JUN-07:10 | 2160.58 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 780.99 | 10-JUN-17:02 | 384.29 | 06-JUN-21:20 |
July | 2010.83 | 03-JUL-09:09 | 1470.31 | 11-JUL-07:10 | 2160.58 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 681.62 | 22-JUL-18:50 | 299.50 | 30-JUL-11:00 |
August | 2010.83 | 01-AUG-09:09 | 1803.04 | 08-AUG-07:10 | 2160.58 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 886.81 | 20-AUG-13:54 | 543.36 | 25-AUG-23:55 |
September | 2010.83 | 01-SEP-09:09 | 2255.25 | 26-SEP-07:10 | 2160.58 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 858.37 | 09-SEP-22:53 | 588.85 | 05-SEP-03:00 |
October | 2010.83 | 02-OCT-09:09 | 2587.98 | 25-OCT-07:10 | 2160.58 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 958.16 | 09-OCT-13:55 | 992.12 | 29-OCT-02:00 |
November | 2010.83 | 01-NOV-09:09 | 2255.25 | 01-NOV-07:10 | 2160.58 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 103.95 | 07-NOV-13:00 | 1819.53 | 12-NOV-10:58 |
December | 2010.83 | 01-DEC-10:09 | 2587.98 | 12-DEC-08:09 | 2160.58 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 101.07 | 13-DEC-14:00 | 1914.23 | 20-DEC-01:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.83 | 1350.84 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 47.08 | 266.70 | |||||
Maximum of Months | 2010.83 | 2587.98 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 958.16 | 2289.86 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 1453.34 | 02-JAN-08:09 | 1392.33 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 126.28 | 16-JAN-12:50 | 1194.01 | 21-JAN-06:00 |
February | 1295.83 | 01-FEB-10:09 | 1453.34 | 01-FEB-08:09 | 1392.33 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 120.17 | 26-FEB-13:10 | 1526.59 | 05-FEB-08:00 |
March | 1295.83 | 01-MAR-10:09 | 1453.34 | 01-MAR-08:09 | 1392.33 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 308.29 | 05-MAR-12:30 | 1382.45 | 20-MAR-22:00 |
April | 1295.83 | 03-APR-09:09 | 1453.34 | 06-APR-07:10 | 1392.33 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 176.91 | 23-APR-13:50 | 927.03 | 01-APR-17:53 |
May | 1295.83 | 01-MAY-09:09 | 1161.92 | 01-MAY-07:10 | 1392.33 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 486.90 | 21-MAY-13:40 | 261.57 | 06-MAY-19:53 |
June | 1295.83 | 01-JUN-09:09 | 1161.92 | 16-JUN-07:10 | 1392.33 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 457.09 | 10-JUN-17:07 | 298.71 | 06-JUN-22:00 |
July | 1295.83 | 03-JUL-09:09 | 1161.92 | 11-JUL-07:10 | 1392.33 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 454.30 | 02-JUL-12:00 | 221.36 | 31-JUL-01:55 |
August | 1295.83 | 01-AUG-09:09 | 1376.34 | 08-AUG-07:10 | 1392.33 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 610.77 | 20-AUG-14:00 | 403.96 | 25-AUG-23:55 |
September | 1295.83 | 01-SEP-09:09 | 1453.34 | 13-SEP-07:10 | 1392.33 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 589.99 | 09-SEP-22:50 | 395.83 | 05-SEP-03:00 |
October | 1295.83 | 02-OCT-09:09 | 1667.75 | 25-OCT-07:10 | 1392.33 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 756.68 | 09-OCT-12:00 | 651.01 | 29-OCT-02:00 |
November | 1295.83 | 01-NOV-09:09 | 1667.75 | 01-NOV-07:10 | 1392.33 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 202.38 | 05-NOV-12:50 | 979.79 | 12-NOV-06:55 |
December | 1295.83 | 01-DEC-10:09 | 1667.75 | 12-DEC-08:09 | 1392.33 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 173.34 | 10-DEC-11:00 | 1304.12 | 20-DEC-01:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 1161.92 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 120.17 | 221.36 | |||||
Maximum of Months | 1295.83 | 1667.75 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 756.68 | 1526.59 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 232.27 | 02-JAN-10:09 | 578.72 | 02-JAN-08:09 | 1948.61 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 232.27 | 01-FEB-10:09 | 578.72 | 01-FEB-08:09 | 3897.21 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 232.27 | 01-MAR-10:09 | 578.72 | 01-MAR-08:09 | 7794.42 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 232.27 | 03-APR-09:09 | 578.72 | 03-APR-07:10 | 7794.42 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 232.27 | 01-MAY-09:09 | 578.72 | 01-MAY-07:10 | 3897.21 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 232.27 | 01-JUN-09:09 | 578.72 | 01-JUN-07:10 | 5845.82 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 232.27 | 03-JUL-09:09 | 578.72 | 03-JUL-07:10 | 7794.42 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 232.27 | 01-AUG-09:09 | 578.72 | 01-AUG-07:10 | 7794.42 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 232.27 | 01-SEP-09:09 | 578.72 | 01-SEP-07:10 | 3897.21 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 232.27 | 02-OCT-09:09 | 578.72 | 02-OCT-07:10 | 5845.82 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 232.27 | 01-NOV-09:09 | 578.72 | 01-NOV-07:10 | 5845.82 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 232.27 | 01-DEC-10:09 | 578.72 | 01-DEC-08:09 | 7794.42 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 232.27 | 578.72 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 232.27 | 578.72 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 232.27 | 02-JAN-10:09 | 578.72 | 02-JAN-08:09 | 1948.61 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 232.27 | 01-FEB-10:09 | 578.72 | 01-FEB-08:09 | 3897.21 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 232.27 | 01-MAR-10:09 | 578.72 | 01-MAR-08:09 | 7794.42 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 232.27 | 03-APR-09:09 | 578.72 | 03-APR-07:10 | 7794.42 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 232.27 | 01-MAY-09:09 | 578.72 | 01-MAY-07:10 | 3897.21 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 232.27 | 01-JUN-09:09 | 578.72 | 01-JUN-07:10 | 5845.82 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 232.27 | 03-JUL-09:09 | 578.72 | 03-JUL-07:10 | 7794.42 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 232.27 | 01-AUG-09:09 | 578.72 | 01-AUG-07:10 | 7794.42 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 232.27 | 01-SEP-09:09 | 578.72 | 01-SEP-07:10 | 3897.21 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 232.27 | 02-OCT-09:09 | 578.72 | 02-OCT-07:10 | 5845.82 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 232.27 | 01-NOV-09:09 | 578.72 | 01-NOV-07:10 | 5845.82 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 232.27 | 01-DEC-10:09 | 578.72 | 01-DEC-08:09 | 7794.42 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 232.27 | 578.72 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 232.27 | 578.72 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 232.27 | 02-JAN-10:09 | 578.72 | 02-JAN-08:09 | 1948.61 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 232.27 | 01-FEB-10:09 | 578.72 | 01-FEB-08:09 | 3897.21 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 232.27 | 01-MAR-10:09 | 578.72 | 01-MAR-08:09 | 7794.42 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 232.27 | 03-APR-09:09 | 578.72 | 03-APR-07:10 | 7794.42 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 232.27 | 01-MAY-09:09 | 578.72 | 01-MAY-07:10 | 3897.21 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 232.27 | 01-JUN-09:09 | 578.72 | 01-JUN-07:10 | 5845.82 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 232.27 | 03-JUL-09:09 | 578.72 | 03-JUL-07:10 | 7794.42 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 232.27 | 01-AUG-09:09 | 578.72 | 01-AUG-07:10 | 7794.42 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 232.27 | 01-SEP-09:09 | 578.72 | 01-SEP-07:10 | 3897.21 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 232.27 | 02-OCT-09:09 | 578.72 | 02-OCT-07:10 | 5845.82 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 232.27 | 01-NOV-09:09 | 578.72 | 01-NOV-07:10 | 5845.82 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 232.27 | 01-DEC-10:09 | 578.72 | 01-DEC-08:09 | 7794.42 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 232.27 | 578.72 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 232.27 | 578.72 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 5027.92 | 02-JAN-10:09 | 6471.01 | 02-JAN-08:09 | 94908.13 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 5027.92 | 01-FEB-10:09 | 6471.01 | 01-FEB-08:09 | 189816.26 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 5027.92 | 01-MAR-10:09 | 6471.01 | 01-MAR-08:09 | 379632.52 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 5027.92 | 03-APR-09:09 | 6471.01 | 03-APR-07:10 | 379632.52 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 5027.92 | 01-MAY-09:09 | 6471.01 | 01-MAY-07:10 | 189816.26 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5027.92 | 01-JUN-09:09 | 6471.01 | 01-JUN-07:10 | 284724.39 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 5027.92 | 03-JUL-09:09 | 6471.01 | 03-JUL-07:10 | 379632.52 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 5027.92 | 01-AUG-09:09 | 6471.01 | 01-AUG-07:10 | 379632.52 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 5027.92 | 01-SEP-09:09 | 6471.01 | 01-SEP-07:10 | 189816.26 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 5027.92 | 02-OCT-09:09 | 6471.01 | 02-OCT-07:10 | 284724.39 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5027.92 | 01-NOV-09:09 | 6471.01 | 01-NOV-07:10 | 284724.39 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 5027.92 | 01-DEC-10:09 | 6471.01 | 01-DEC-08:09 | 379632.52 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 5027.92 | 6471.01 | 94908.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 5027.92 | 6471.01 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 72.64 | 16-JAN-14:52 | 1516.92 | 26-JAN-03:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 82.90 | 02-FEB-13:00 | 2178.70 | 05-FEB-07:53 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 190.05 | 26-MAR-14:00 | 1853.59 | 20-MAR-22:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 301.65 | 29-APR-17:01 | 1082.49 | 01-APR-21:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 486.10 | 21-MAY-14:00 | 175.71 | 09-MAY-02:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 584.25 | 10-JUN-17:02 | 295.01 | 06-JUN-21:20 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 507.48 | 22-JUL-18:53 | 118.74 | 31-JUL-02:50 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 693.72 | 20-AUG-13:52 | 410.75 | 25-AUG-24:00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 659.38 | 09-SEP-17:02 | 379.53 | 05-SEP-03:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 756.74 | 09-OCT-14:00 | 907.47 | 29-OCT-02:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 91.67 | 05-NOV-13:00 | 1287.00 | 12-NOV-08:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 90.95 | 10-DEC-15:00 | 2027.21 | 20-DEC-01:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 72.64 | 118.74 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 756.74 | 2178.70 |
Report: PeakSpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 216.09 | 16-JAN-15:00 | 2585.80 | 21-JAN-05:53 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 246.16 | 20-FEB-14:53 | 3725.13 | 05-FEB-07:53 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 455.70 | 05-MAR-12:53 | 3147.55 | 20-MAR-22:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 589.05 | 29-APR-17:01 | 1779.59 | 01-APR-21:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 876.10 | 21-MAY-13:53 | 284.98 | 09-MAY-02:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1078.30 | 10-JUN-17:02 | 497.78 | 06-JUN-21:20 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 955.29 | 22-JUL-18:53 | 210.00 | 31-JUL-02:53 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1288.24 | 20-AUG-14:00 | 742.85 | 25-AUG-23:55 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1216.05 | 09-SEP-17:02 | 588.41 | 05-SEP-03:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1423.11 | 09-OCT-14:00 | 1518.26 | 29-OCT-02:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 228.60 | 05-NOV-13:00 | 2184.86 | 12-NOV-08:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 229.21 | 10-DEC-14:51 | 3405.50 | 20-DEC-01:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 216.09 | 210.00 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1423.11 | 3725.13 |
Report: PeakSpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 195.33 | 16-JAN-15:00 | 2583.81 | 21-JAN-06:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 135.24 | 20-FEB-14:53 | 3370.04 | 05-FEB-08:00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 351.49 | 26-MAR-14:00 | 3284.38 | 20-MAR-22:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 447.12 | 29-APR-17:01 | 1930.24 | 01-APR-17:53 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 759.20 | 07-MAY-13:56 | 532.43 | 14-MAY-11:53 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1023.16 | 10-JUN-17:02 | 506.27 | 06-JUN-21:20 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 800.33 | 22-JUL-18:50 | 511.38 | 30-JUL-11:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1204.32 | 20-AUG-14:00 | 807.68 | 25-AUG-23:55 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1350.22 | 09-SEP-22:53 | 773.98 | 05-SEP-03:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1097.72 | 09-OCT-14:00 | 1392.46 | 29-OCT-02:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 199.36 | 05-NOV-13:00 | 2247.12 | 12-NOV-06:55 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 159.95 | 10-DEC-15:00 | 3211.53 | 20-DEC-01:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 135.24 | 506.27 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1350.22 | 3370.04 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 123544.46 | 09-JAN-05:11 | 0.00 | 20401.06 | 107660.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 125214.76 | 13-FEB-05:11 | 0.00 | 20401.06 | 107660.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 127774.04 | 20-MAR-04:11 | 0.00 | 20401.06 | 107660.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 124446.44 | 17-APR-04:12 | 0.00 | 15300.79 | 80745.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 91563.84 | 30-MAY-03:02 | 0.00 | 7649.54 | 80745.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 93706.46 | 07-JUN-04:12 | 0.00 | 15300.79 | 80745.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 88445.63 | 05-JUL-04:33 | 0.00 | 10200.53 | 53830.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 92868.86 | 21-AUG-03:02 | 0.00 | 7649.54 | 80745.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 92712.69 | 04-SEP-10:42 | 4488.06 | 6374.62 | 67287.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 118216.68 | 27-OCT-04:12 | 0.00 | 12750.66 | 67287.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 121343.91 | 13-NOV-05:11 | 0.00 | 17850.93 | 94202.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 121508.20 | 04-DEC-05:12 | 0.00 | 15300.79 | 80745.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 88445.63 | 0.00 | 6374.62 | 53830.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 127774.04 | 4488.06 | 20401.06 | 107660.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 94672.30 | 17-JAN-05:12 | 0.00 | 11450.99 | 29688.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 98525.88 | 27-FEB-05:13 | 0.00 | 13741.19 | 35625.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 99561.72 | 20-MAR-04:11 | 0.00 | 18321.59 | 47501.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 96956.82 | 10-APR-04:12 | 0.00 | 13741.19 | 35625.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 99728.71 | 16-MAY-04:13 | 0.00 | 16031.39 | 41563.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 98433.77 | 01-JUN-04:13 | 0.00 | 13741.19 | 35625.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 79077.33 | 15-JUL-05:03 | 6448.95 | 9160.79 | 30589.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 88343.00 | 17-AUG-04:12 | 0.00 | 13741.19 | 35625.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 98967.34 | 29-SEP-04:13 | 0.00 | 16031.39 | 41563.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 101068.50 | 02-OCT-04:13 | 0.00 | 13741.19 | 35625.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 99860.51 | 13-NOV-05:11 | 0.00 | 16031.39 | 41563.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 100422.03 | 18-DEC-05:12 | 0.00 | 13741.19 | 35625.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 79077.33 | 0.00 | 9160.79 | 29688.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 101068.50 | 6448.95 | 18321.59 | 47501.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 82326.92 | 19-JAN-06:02 | 8061.19 | 11450.99 | 38236.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 84423.22 | 28-FEB-05:12 | 0.00 | 13741.19 | 35625.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 84069.34 | 31-MAR-04:12 | 0.00 | 11450.99 | 29688.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 85731.39 | 26-APR-04:12 | 0.00 | 13741.19 | 35625.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 87577.08 | 18-MAY-04:13 | 0.00 | 16031.39 | 41563.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 86908.12 | 07-JUN-04:12 | 0.00 | 13741.19 | 35625.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 84235.61 | 12-JUL-04:12 | 0.00 | 11450.99 | 29688.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 86688.18 | 17-AUG-04:12 | 0.00 | 13741.19 | 35625.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 85533.49 | 08-SEP-04:02 | 0.00 | 11450.99 | 29688.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 86908.60 | 17-OCT-04:12 | 0.00 | 13741.19 | 35625.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 87075.71 | 08-NOV-05:11 | 0.00 | 16031.39 | 41563.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 85574.85 | 15-DEC-05:11 | 0.00 | 16031.39 | 41563.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 82326.92 | 0.00 | 11450.99 | 29688.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 87577.08 | 8061.19 | 16031.39 | 41563.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 81033.88 | 20-JAN-06:02 | 8061.19 | 11450.99 | 38236.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 79371.03 | 28-FEB-06:03 | 6448.95 | 9160.79 | 30589.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 80034.59 | 30-MAR-05:02 | 8061.19 | 11450.99 | 38236.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 84296.42 | 22-APR-04:12 | 0.00 | 6869.83 | 26719.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 89522.47 | 31-MAY-04:13 | 0.00 | 16031.39 | 41563.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 86104.51 | 30-JUN-03:42 | 0.00 | 5724.85 | 29688.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 85233.47 | 18-JUL-03:02 | 0.00 | 5724.85 | 29688.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 85624.24 | 11-AUG-03:02 | 0.00 | 5724.85 | 29688.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 84794.10 | 22-SEP-04:12 | 0.00 | 13741.19 | 35625.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 84768.17 | 20-OCT-04:11 | 0.00 | 16031.39 | 41563.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 84534.70 | 08-NOV-05:11 | 0.00 | 16031.39 | 41563.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 81011.33 | 15-DEC-06:02 | 8061.19 | 11450.99 | 38236.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 79371.03 | 0.00 | 5724.85 | 26719.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 89522.47 | 8061.19 | 16031.39 | 41563.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 7465.06 | 02-JAN-13:30 | 1923.11 | 1231.33 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 7.30 | 0.00 |
February | 7615.72 | 22-FEB-14:30 | 2010.79 | 1231.33 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 5.52 | 0.00 |
March | 9026.06 | 28-MAR-12:30 | 1923.11 | 1231.33 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 20.20 | 0.00 |
April | 9846.92 | 26-APR-14:30 | 1923.11 | 1231.33 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 30.69 | 0.00 |
May | 14292.10 | 07-MAY-14:42 | 506.08 | 342.01 | 3600.92 | 0.00 | 0.00 | 0.00 | 0.00 | 124.61 | 0.00 |
June | 17670.63 | 25-JUN-16:41 | 809.73 | 547.22 | 5761.47 | 0.00 | 0.00 | 0.00 | 0.00 | 50.47 | 0.00 |
July | 17379.89 | 23-JUL-14:02 | 506.08 | 342.01 | 3600.92 | 0.00 | 0.00 | 0.00 | 0.00 | 133.94 | 0.00 |
August | 17533.46 | 20-AUG-14:02 | 506.08 | 342.01 | 3600.92 | 0.00 | 0.00 | 0.00 | 0.00 | 274.86 | 0.00 |
September | 17214.18 | 10-SEP-16:51 | 809.73 | 547.22 | 5761.47 | 0.00 | 0.00 | 0.00 | 0.00 | 78.10 | 0.00 |
October | 17226.69 | 08-OCT-15:01 | 708.51 | 478.82 | 5041.29 | 0.00 | 0.00 | 0.00 | 0.00 | 219.34 | 0.00 |
November | 9414.37 | 08-NOV-05:11 | 0.00 | 2012.90 | 5218.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 227.64 |
December | 10546.23 | 11-DEC-06:02 | 1012.16 | 1437.79 | 4801.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.50 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 7465.06 | 0.00 | 342.01 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 17670.63 | 2010.79 | 2012.90 | 5761.47 | 0.00 | 0.00 | 0.00 | 0.00 | 274.86 | 227.64 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 13246.32 | 01-JAN-09:53 | 260.91 | 176.32 | 1856.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 134.61 |
February | 10202.32 | 26-FEB-11:13 | 260.91 | 176.32 | 1856.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.73 |
March | 19078.27 | 26-MAR-09:43 | 260.91 | 176.32 | 1856.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.67 |
April | 18457.71 | 23-APR-09:12 | 326.14 | 220.40 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.32 |
May | 20878.21 | 14-MAY-09:22 | 391.37 | 264.49 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 8.05 | 0.00 |
June | 19240.89 | 04-JUN-09:32 | 391.37 | 264.49 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 31.24 | 0.00 |
July | 20364.32 | 16-JUL-08:42 | 326.14 | 220.40 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 20.57 | 0.00 |
August | 19113.50 | 06-AUG-11:02 | 326.14 | 220.40 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 59.73 | 0.00 |
September | 21271.87 | 10-SEP-09:31 | 456.59 | 308.57 | 3248.80 | 0.00 | 0.00 | 0.00 | 0.00 | 88.96 | 0.00 |
October | 19314.66 | 15-OCT-08:53 | 260.91 | 176.32 | 1856.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 106.86 |
November | 18473.12 | 11-NOV-09:23 | 260.91 | 176.32 | 1856.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.18 |
December | 11019.74 | 10-DEC-10:02 | 260.91 | 176.32 | 1856.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42.22 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 10202.32 | 260.91 | 176.32 | 1856.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 21271.87 | 456.59 | 308.57 | 3248.80 | 0.00 | 0.00 | 0.00 | 0.00 | 88.96 | 134.61 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 25851.42 | 01-JAN-13:51 | 809.75 | 547.23 | 5761.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36.82 |
February | 22602.64 | 26-FEB-11:13 | 404.87 | 273.61 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.65 |
March | 22349.97 | 05-MAR-12:43 | 404.87 | 273.61 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 10.87 | 0.00 |
April | 13024.44 | 28-APR-13:50 | 2010.83 | 1231.36 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 46.50 | 0.00 |
May | 19252.50 | 07-MAY-14:02 | 506.09 | 342.02 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 186.92 | 0.00 |
June | 21276.88 | 25-JUN-16:01 | 809.75 | 547.23 | 5761.56 | 0.00 | 0.00 | 0.00 | 0.00 | 44.07 | 0.00 |
July | 21288.30 | 23-JUL-14:02 | 506.09 | 342.02 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 136.63 | 0.00 |
August | 21800.62 | 20-AUG-14:02 | 506.09 | 342.02 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 271.30 | 0.00 |
September | 22917.57 | 03-SEP-13:32 | 506.09 | 342.02 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 72.76 | 0.00 |
October | 24453.73 | 15-OCT-13:31 | 708.53 | 478.83 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 35.79 | 0.00 |
November | 24206.26 | 05-NOV-13:12 | 607.31 | 410.42 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.43 |
December | 25449.82 | 10-DEC-12:41 | 708.53 | 478.83 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40.69 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 13024.44 | 404.87 | 273.61 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 25851.42 | 2010.83 | 1231.36 | 5761.56 | 0.00 | 0.00 | 0.00 | 0.00 | 271.30 | 40.69 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 24709.32 | 01-JAN-15:52 | 391.37 | 264.49 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.75 |
February | 22397.66 | 26-FEB-16:32 | 326.14 | 220.40 | 2320.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.02 |
March | 24567.39 | 05-MAR-17:22 | 326.14 | 220.40 | 2320.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.89 |
April | 25243.20 | 23-APR-16:32 | 391.37 | 264.49 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.94 |
May | 25021.59 | 29-MAY-16:32 | 391.37 | 264.49 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 56.12 | 0.00 |
June | 27042.07 | 25-JUN-16:01 | 521.82 | 352.65 | 3712.89 | 0.00 | 0.00 | 0.00 | 0.00 | 18.87 | 0.00 |
July | 24687.18 | 16-JUL-16:02 | 391.37 | 264.49 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 95.85 | 0.00 |
August | 24547.32 | 06-AUG-15:42 | 391.37 | 264.49 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.26 |
September | 26746.36 | 10-SEP-16:51 | 521.82 | 352.65 | 3712.89 | 0.00 | 0.00 | 0.00 | 0.00 | 35.94 | 0.00 |
October | 26562.08 | 08-OCT-15:41 | 456.59 | 308.57 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 91.25 | 0.00 |
November | 24280.67 | 11-NOV-16:42 | 326.14 | 220.40 | 2320.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.51 |
December | 26602.78 | 10-DEC-15:21 | 456.59 | 308.57 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.31 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 22397.66 | 326.14 | 220.40 | 2320.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 27042.07 | 521.82 | 352.65 | 3712.89 | 0.00 | 0.00 | 0.00 | 0.00 | 95.85 | 34.51 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 5392.67 | 31-JAN-14:40 | 2010.79 | 1231.33 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 23.13 | 0.00 |
February | 5665.30 | 28-FEB-15:00 | 2010.79 | 1231.33 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 24.58 | 0.00 |
March | 7458.18 | 30-MAR-13:20 | 2010.79 | 1231.33 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 51.87 | 0.00 |
April | 11508.31 | 28-APR-05:02 | 1012.16 | 1437.79 | 4801.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.39 |
May | 12741.38 | 30-MAY-05:03 | 809.73 | 1150.23 | 3840.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 16374.06 | 11-JUN-17:21 | 0.00 | 547.22 | 4473.37 | 0.00 | 0.00 | 0.00 | 0.00 | 244.85 | 0.00 |
July | 16124.18 | 23-JUL-15:02 | 404.87 | 273.61 | 2880.74 | 0.00 | 0.00 | 0.00 | 0.00 | 301.76 | 0.00 |
August | 14996.37 | 14-AUG-03:02 | 0.00 | 718.81 | 3727.80 | 0.00 | 0.00 | 0.00 | 0.00 | 19.89 | 0.00 |
September | 13222.12 | 11-SEP-05:03 | 809.73 | 1150.23 | 3840.98 | 0.00 | 0.00 | 0.00 | 0.00 | 7.84 | 0.00 |
October | 12401.80 | 13-OCT-04:02 | 0.00 | 1725.34 | 4473.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 71.42 |
November | 10268.85 | 02-NOV-05:03 | 809.73 | 1150.23 | 3840.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.93 |
December | 6294.97 | 15-DEC-14:10 | 2010.79 | 1231.33 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 44.33 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 5392.67 | 0.00 | 273.61 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 16374.06 | 2010.79 | 1725.34 | 4801.23 | 0.00 | 0.00 | 0.00 | 0.00 | 301.76 | 71.42 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 7433.82 | 19-JAN-10:00 | 1239.33 | 793.52 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.85 |
February | 9191.23 | 26-FEB-10:23 | 260.91 | 176.32 | 1856.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.94 |
March | 17045.39 | 26-MAR-10:23 | 260.91 | 176.32 | 1856.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.13 |
April | 21515.87 | 23-APR-09:02 | 391.37 | 264.49 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 118.48 |
May | 21710.42 | 07-MAY-10:02 | 391.37 | 264.49 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 82.22 | 0.00 |
June | 20430.13 | 04-JUN-11:02 | 326.14 | 220.40 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 54.05 | 0.00 |
July | 21688.93 | 16-JUL-09:12 | 391.37 | 264.49 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 55.41 | 0.00 |
August | 18771.10 | 20-AUG-10:23 | 260.91 | 176.32 | 1856.46 | 0.00 | 0.00 | 0.00 | 0.00 | 79.99 | 0.00 |
September | 20952.38 | 24-SEP-09:02 | 326.14 | 220.40 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 13.63 | 0.00 |
October | 19301.44 | 09-OCT-09:52 | 326.14 | 220.40 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 218.09 | 0.00 |
November | 15005.55 | 11-NOV-09:23 | 260.91 | 176.32 | 1856.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 69.53 |
December | 6285.62 | 10-DEC-10:23 | 260.91 | 176.32 | 1856.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 77.60 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 6285.62 | 260.91 | 176.32 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 21710.42 | 1239.33 | 793.52 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 218.09 | 118.48 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 23273.20 | 16-JAN-14:42 | 607.31 | 410.42 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 76.64 |
February | 23268.44 | 26-FEB-13:42 | 607.31 | 410.42 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 101.30 |
March | 21375.76 | 05-MAR-13:43 | 404.87 | 273.61 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 21.33 | 0.00 |
April | 14478.83 | 28-APR-05:02 | 1012.19 | 1437.82 | 4801.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.46 |
May | 19060.83 | 07-MAY-14:02 | 506.09 | 342.02 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 431.66 | 0.00 |
June | 14410.27 | 24-JUN-05:03 | 809.75 | 1150.25 | 3841.04 | 0.00 | 0.00 | 0.00 | 0.00 | 4.08 | 0.00 |
July | 17259.05 | 23-JUL-15:02 | 404.87 | 273.61 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 303.70 | 0.00 |
August | 18725.60 | 21-AUG-03:02 | 0.00 | 862.59 | 4473.43 | 0.00 | 0.00 | 0.00 | 0.00 | 18.01 | 0.00 |
September | 22117.92 | 03-SEP-13:32 | 506.09 | 342.02 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 159.44 | 0.00 |
October | 23760.54 | 15-OCT-13:31 | 708.53 | 478.83 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 58.56 | 0.00 |
November | 23349.21 | 05-NOV-13:52 | 607.31 | 410.42 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 60.50 |
December | 22679.21 | 10-DEC-14:22 | 607.31 | 410.42 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.79 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 14410.27 | 0.00 | 273.61 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 23760.54 | 1012.19 | 1437.82 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 431.66 | 101.30 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 9618.35 | 16-JAN-16:02 | 326.14 | 220.40 | 2320.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 56.25 |
February | 20912.75 | 26-FEB-17:01 | 456.59 | 308.57 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 76.12 |
March | 13415.56 | 27-MAR-05:02 | 652.28 | 926.56 | 3094.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36.84 |
April | 21900.49 | 23-APR-17:01 | 0.00 | 352.65 | 2882.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.30 |
May | 22012.15 | 29-MAY-16:12 | 391.37 | 264.49 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 124.60 | 0.00 |
June | 23813.42 | 11-JUN-17:21 | 0.00 | 352.65 | 2882.79 | 0.00 | 0.00 | 0.00 | 0.00 | 104.90 | 0.00 |
July | 22729.95 | 16-JUL-16:31 | 456.59 | 308.57 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 100.52 | 0.00 |
August | 18474.54 | 20-AUG-17:03 | 0.00 | 176.32 | 1441.39 | 0.00 | 0.00 | 0.00 | 0.00 | 144.18 | 0.00 |
September | 21853.71 | 10-SEP-16:22 | 391.37 | 264.49 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 133.88 | 0.00 |
October | 21416.01 | 08-OCT-15:52 | 391.37 | 264.49 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 332.33 | 0.00 |
November | 14727.34 | 11-NOV-16:42 | 326.14 | 220.40 | 2320.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 72.98 |
December | 12042.84 | 10-DEC-16:22 | 326.14 | 220.40 | 2320.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.48 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 9618.35 | 0.00 | 176.32 | 1441.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 23813.42 | 652.28 | 926.56 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 332.33 | 76.12 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 5740.05 | 31-JAN-15:00 | 2010.79 | 1231.33 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 25.21 | 0.00 |
February | 6115.36 | 22-FEB-14:30 | 2010.79 | 1231.33 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 13.81 | 0.00 |
March | 7928.14 | 30-MAR-13:30 | 2010.79 | 1231.33 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 60.95 | 0.00 |
April | 11678.37 | 28-APR-05:02 | 1012.16 | 1437.79 | 4801.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.95 |
May | 16405.32 | 28-MAY-16:32 | 607.30 | 410.41 | 4321.10 | 0.00 | 0.00 | 0.00 | 0.00 | 371.02 | 0.00 |
June | 18914.71 | 11-JUN-17:21 | 0.00 | 547.22 | 4473.37 | 0.00 | 0.00 | 0.00 | 0.00 | 267.15 | 0.00 |
July | 18858.67 | 23-JUL-14:12 | 506.08 | 342.01 | 3600.92 | 0.00 | 0.00 | 0.00 | 0.00 | 342.85 | 0.00 |
August | 18392.00 | 20-AUG-14:53 | 404.87 | 273.61 | 2880.74 | 0.00 | 0.00 | 0.00 | 0.00 | 486.76 | 0.00 |
September | 18247.79 | 10-SEP-15:02 | 607.30 | 410.41 | 4321.10 | 0.00 | 0.00 | 0.00 | 0.00 | 329.85 | 0.00 |
October | 16397.36 | 08-OCT-14:32 | 607.30 | 410.41 | 4321.10 | 0.00 | 0.00 | 0.00 | 0.00 | 675.11 | 0.00 |
November | 9635.08 | 02-NOV-05:03 | 809.73 | 1150.23 | 3840.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.91 |
December | 6827.84 | 15-DEC-15:00 | 2010.79 | 1231.33 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 64.02 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 5740.05 | 0.00 | 273.61 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 18914.71 | 2010.79 | 1437.79 | 4801.23 | 0.00 | 0.00 | 0.00 | 0.00 | 675.11 | 8.95 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 7153.03 | 19-JAN-10:20 | 1295.83 | 793.52 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.52 |
February | 7324.68 | 27-FEB-10:30 | 1295.83 | 793.52 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.66 |
March | 15345.52 | 26-MAR-10:23 | 260.91 | 176.32 | 1856.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.58 |
April | 21606.28 | 23-APR-09:02 | 391.37 | 264.49 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 145.97 |
May | 21157.56 | 29-MAY-07:32 | 326.14 | 220.40 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 53.57 |
June | 20922.61 | 04-JUN-11:02 | 326.14 | 220.40 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 57.38 | 0.00 |
July | 22633.70 | 23-JUL-10:11 | 456.59 | 308.57 | 3248.80 | 0.00 | 0.00 | 0.00 | 0.00 | 9.09 | 0.00 |
August | 18467.99 | 06-AUG-11:53 | 260.91 | 176.32 | 1856.46 | 0.00 | 0.00 | 0.00 | 0.00 | 192.35 | 0.00 |
September | 21155.37 | 24-SEP-09:02 | 326.14 | 220.40 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 15.64 | 0.00 |
October | 19573.45 | 09-OCT-09:52 | 326.14 | 220.40 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 255.43 | 0.00 |
November | 11890.66 | 11-NOV-09:53 | 260.91 | 176.32 | 1856.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 88.79 |
December | 5719.97 | 16-DEC-10:00 | 391.37 | 264.51 | 773.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.97 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 5719.97 | 260.91 | 176.32 | 773.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 22633.70 | 1295.83 | 793.52 | 3248.80 | 0.00 | 0.00 | 0.00 | 0.00 | 255.43 | 145.97 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 27110.69 | 01-JAN-13:41 | 809.75 | 547.23 | 5761.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 136.74 |
February | 25095.92 | 26-FEB-13:42 | 607.31 | 410.42 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 120.55 |
March | 23117.80 | 05-MAR-13:43 | 404.87 | 273.61 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 29.67 | 0.00 |
April | 17814.18 | 23-APR-15:01 | 708.53 | 478.83 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 171.33 | 0.00 |
May | 17223.28 | 31-MAY-04:11 | 0.00 | 2012.94 | 5219.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.30 |
June | 21946.61 | 11-JUN-17:21 | 0.00 | 547.23 | 4473.43 | 0.00 | 0.00 | 0.00 | 0.00 | 303.97 | 0.00 |
July | 22720.07 | 23-JUL-14:12 | 506.09 | 342.02 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 354.79 | 0.00 |
August | 22318.77 | 20-AUG-14:53 | 404.87 | 273.61 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 492.67 | 0.00 |
September | 24319.63 | 03-SEP-13:32 | 506.09 | 342.02 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 182.72 | 0.00 |
October | 24560.00 | 09-OCT-13:12 | 607.31 | 410.42 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 543.98 | 0.00 |
November | 26421.57 | 11-NOV-13:51 | 708.53 | 478.83 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.90 |
December | 27118.18 | 10-DEC-14:11 | 809.75 | 547.23 | 5761.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 132.57 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 17223.28 | 0.00 | 273.61 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 27118.18 | 809.75 | 2012.94 | 5761.56 | 0.00 | 0.00 | 0.00 | 0.00 | 543.98 | 271.90 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 9728.10 | 01-JAN-17:03 | 260.91 | 176.32 | 1856.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59.64 |
February | 21985.01 | 26-FEB-17:01 | 456.59 | 308.57 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 95.30 |
March | 13593.18 | 26-MAR-16:22 | 326.14 | 220.40 | 2320.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 85.92 |
April | 23430.69 | 23-APR-17:01 | 0.00 | 352.65 | 2882.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 54.03 |
May | 23485.25 | 29-MAY-16:12 | 391.37 | 264.49 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 144.35 | 0.00 |
June | 25464.66 | 11-JUN-17:21 | 0.00 | 352.65 | 2882.79 | 0.00 | 0.00 | 0.00 | 0.00 | 116.23 | 0.00 |
July | 24363.49 | 16-JUL-15:51 | 456.59 | 308.57 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 207.29 | 0.00 |
August | 18386.58 | 06-AUG-15:12 | 326.14 | 220.40 | 2320.55 | 0.00 | 0.00 | 0.00 | 0.00 | 94.60 | 0.00 |
September | 23344.08 | 10-SEP-16:22 | 391.37 | 264.49 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 157.90 | 0.00 |
October | 22804.27 | 08-OCT-15:52 | 391.37 | 264.49 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 386.25 | 0.00 |
November | 22466.04 | 11-NOV-15:52 | 391.37 | 264.49 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46.76 |
December | 22494.87 | 10-DEC-15:31 | 456.59 | 308.57 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 3.14 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 9728.10 | 0.00 | 176.32 | 1856.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 25464.66 | 456.59 | 352.65 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 386.25 | 95.30 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 11652.47 | 02-JAN-06:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 54.06 |
February | 8628.63 | 28-FEB-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.32 |
March | 8475.96 | 27-MAR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57.30 |
April | 7343.86 | 20-APR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 71.50 |
May | 11685.14 | 31-MAY-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.20 |
June | 9948.20 | 06-JUN-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.97 |
July | 8891.69 | 21-JUL-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.77 | 0.00 |
August | 9256.29 | 21-AUG-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.86 | 0.00 |
September | 11399.85 | 05-SEP-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 58.67 |
October | 11233.07 | 02-OCT-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 50.27 |
November | 9060.45 | 03-NOV-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 10755.49 | 11-DEC-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44.01 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 7343.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 11685.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.86 | 71.50 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 8342.42 | 04-JAN-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 406.24 |
February | 7590.34 | 13-FEB-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 251.15 |
March | 7843.55 | 09-MAR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 576.14 |
April | 6248.91 | 28-APR-15:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 171.05 | 0.00 |
May | 6924.83 | 06-MAY-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.11 |
June | 8499.09 | 17-JUN-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.46 | 0.00 |
July | 9750.45 | 21-JUL-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.42 | 0.00 |
August | 7587.90 | 15-AUG-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.43 |
September | 9363.90 | 01-SEP-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 7333.14 | 10-OCT-15:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 270.43 | 0.00 |
November | 5670.87 | 07-NOV-15:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57.65 | 0.00 |
December | 7034.10 | 21-DEC-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1387.45 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 5670.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 9750.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 270.43 | 1387.45 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 10464.89 | 19-JAN-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37.76 |
February | 12172.48 | 24-FEB-14:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.22 | 0.00 |
March | 12182.02 | 06-MAR-14:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.06 | 0.00 |
April | 17608.60 | 28-APR-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 218.08 | 0.00 |
May | 18545.62 | 10-MAY-14:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.32 | 0.00 |
June | 19409.04 | 28-JUN-14:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 151.48 | 0.00 |
July | 19736.76 | 07-JUL-14:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 117.05 | 0.00 |
August | 19043.20 | 03-AUG-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 300.68 | 0.00 |
September | 17617.37 | 01-SEP-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 112.88 | 0.00 |
October | 17560.42 | 05-OCT-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 154.23 | 0.00 |
November | 14033.18 | 02-NOV-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 76.93 | 0.00 |
December | 12068.37 | 15-DEC-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 63.14 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 10464.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 19736.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 300.68 | 37.76 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 2156.25 | 18-JAN-17:00 | 222.14 | 578.72 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 4183.06 | 26-FEB-17:56 | 58.46 | 160.76 | 19486.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 7216.12 | 31-MAR-24:00 | 0.00 | 32.15 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 7998.24 | 16-APR-18:10 | 0.00 | 64.31 | 15588.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 3507.76 | 31-MAY-24:00 | 0.00 | 32.15 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5366.65 | 30-JUN-23:35 | 0.00 | 64.31 | 11691.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 7230.88 | 31-JUL-23:35 | 0.00 | 64.31 | 15588.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 7827.33 | 14-AUG-16:00 | 222.14 | 578.72 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 3501.56 | 30-SEP-24:00 | 0.00 | 32.15 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 5373.35 | 31-OCT-24:00 | 0.00 | 32.15 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6154.90 | 06-NOV-17:00 | 222.14 | 578.72 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 7984.00 | 14-DEC-17:00 | 222.14 | 578.72 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 2156.25 | 0.00 | 32.15 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 7998.24 | 222.14 | 578.72 | 19486.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 1970.65 | 18-JAN-17:00 | 222.14 | 578.72 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 3821.35 | 27-FEB-17:50 | 70.15 | 321.51 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6702.70 | 31-MAR-24:00 | 0.00 | 32.15 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 7458.27 | 16-APR-18:12 | 0.00 | 192.92 | 46766.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 3272.17 | 31-MAY-24:00 | 0.00 | 32.15 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5196.43 | 30-JUN-23:57 | 0.00 | 96.46 | 17537.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6935.14 | 31-JUL-23:53 | 0.00 | 96.46 | 23383.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 7413.01 | 14-AUG-16:00 | 222.14 | 578.72 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 3222.18 | 30-SEP-24:00 | 0.00 | 32.15 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 4939.78 | 31-OCT-24:00 | 0.00 | 32.15 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5822.16 | 06-NOV-17:00 | 222.14 | 578.72 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 7548.48 | 15-DEC-17:00 | 222.14 | 578.72 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 1970.65 | 0.00 | 32.15 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 7548.48 | 222.14 | 578.72 | 46766.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 2025.82 | 18-JAN-17:00 | 222.14 | 578.72 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 3882.33 | 27-FEB-17:00 | 222.14 | 578.72 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6589.28 | 31-MAR-24:00 | 0.00 | 32.15 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 7604.34 | 23-APR-18:10 | 0.00 | 64.31 | 15588.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 3234.40 | 31-MAY-24:00 | 0.00 | 32.15 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5220.43 | 30-JUN-23:57 | 0.00 | 96.46 | 17537.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6921.59 | 31-JUL-23:53 | 0.00 | 96.46 | 23383.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 7533.61 | 14-AUG-16:00 | 222.14 | 578.72 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 3215.31 | 30-SEP-24:00 | 0.00 | 32.15 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 4863.12 | 31-OCT-24:00 | 0.00 | 32.15 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5886.10 | 06-NOV-17:00 | 222.14 | 578.72 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 7620.38 | 15-DEC-17:00 | 222.14 | 578.72 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 2025.82 | 0.00 | 32.15 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 7620.38 | 222.14 | 578.72 | 23383.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 94043.85 | 02-JAN-17:00 | 4808.68 | 6471.01 | 94908.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 184956.36 | 27-FEB-17:00 | 4808.68 | 6471.01 | 189816.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 359161.65 | 31-MAR-24:00 | 0.00 | 359.47 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 368507.92 | 28-APR-21:02 | 1518.53 | 4314.17 | 2277795.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 176251.81 | 31-MAY-24:00 | 0.00 | 359.47 | 189816.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 267957.59 | 30-JUN-23:57 | 0.00 | 1078.42 | 854173.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 360068.02 | 31-JUL-23:57 | 0.00 | 1078.42 | 1138897.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 371878.22 | 09-AUG-21:02 | 1518.53 | 4314.17 | 2277795.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 176802.36 | 30-SEP-24:00 | 0.00 | 359.47 | 189816.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 269266.26 | 31-OCT-24:00 | 0.00 | 359.47 | 284724.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 277930.25 | 07-NOV-17:00 | 4808.68 | 6471.01 | 284724.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 369250.25 | 18-DEC-17:00 | 4808.68 | 6471.01 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 94043.85 | 0.00 | 359.47 | 94908.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 371878.22 | 4808.68 | 6471.01 | 2277795.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.179378E+13 | 1431185.45 | 19-JAN-16:49 | 0.120100E+12 | 770879.81 | 21-JAN-07:10 |
February | 0.205895E+13 | 1591656.64 | 27-FEB-16:49 | 0.849351E+11 | 733960.34 | 06-FEB-07:10 |
March | 0.274976E+13 | 1745447.56 | 07-MAR-08:00 | 0.884784E+11 | 707841.80 | 09-MAR-07:10 |
April | 0.314841E+13 | 1953721.35 | 28-APR-15:00 | 0.562056E+11 | 182194.66 | 18-APR-14:50 |
May | 0.227140E+13 | 1477005.05 | 04-MAY-15:39 | 0.559236E+11 | 69010.79 | 02-MAY-11:39 |
June | 0.266270E+13 | 1653978.24 | 28-JUN-15:09 | 0.528680E+11 | 65219.41 | 02-JUN-11:00 |
July | 0.313779E+13 | 1828755.22 | 21-JUL-15:50 | 0.511629E+11 | 62731.85 | 03-JUL-11:50 |
August | 0.363132E+13 | 1978865.65 | 03-AUG-15:30 | 0.541721E+11 | 63470.56 | 25-AUG-11:20 |
September | 0.220245E+13 | 1483846.38 | 01-SEP-15:09 | 0.519987E+11 | 66591.80 | 25-SEP-11:39 |
October | 0.260106E+13 | 1675352.47 | 25-OCT-07:10 | 0.563589E+11 | 105778.65 | 28-OCT-06:10 |
November | 0.271154E+13 | 1775171.78 | 02-NOV-15:09 | 0.615620E+11 | 269992.46 | 15-NOV-07:10 |
December | 0.306341E+13 | 1916722.58 | 15-DEC-16:40 | 0.100537E+12 | 794828.69 | 21-DEC-07:10 |
Annual Sum or Average | 0.320326E+14 | 0.834302E+12 | ||||
Minimum of Months | 0.179378E+13 | 1431185.45 | 0.511629E+11 | 62731.85 | ||
Maximum of Months | 0.363132E+13 | 1978865.65 | 0.120100E+12 | 794828.69 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [J] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [J] | HUMIDIFIER:ELECTRICITY [J] | HEATRECOVERY:ELECTRICITY [J] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 0.330545E+12 | 0.691327E+11 | 0.766053E+12 | 0.164269E+12 | 0.167143E+12 | 0.384940E+11 | 0.00 | 0.179295E+12 | 0.749153E+11 | 0.503346E+09 | 0.343245E+10 | 0.00 | 0.00 |
February | 0.298278E+12 | 0.590044E+11 | 0.978954E+12 | 0.148382E+12 | 0.153276E+12 | 0.431180E+11 | 0.00 | 0.270969E+12 | 0.103195E+12 | 0.352408E+09 | 0.342048E+10 | 0.00 | 0.00 |
March | 0.352887E+12 | 0.601502E+11 | 0.141687E+13 | 0.164522E+12 | 0.173188E+12 | 0.515924E+11 | 0.00 | 0.394327E+12 | 0.132415E+12 | 0.230409E+09 | 0.357270E+10 | 0.00 | 0.00 |
April | 0.314187E+12 | 0.531925E+11 | 0.165903E+13 | 0.158946E+12 | 0.173512E+12 | 0.648231E+11 | 0.00 | 0.562896E+12 | 0.156730E+12 | 63996188.86 | 0.503866E+10 | 0.00 | 0.00 |
May | 0.337406E+12 | 0.504421E+11 | 0.774844E+12 | 0.164394E+12 | 0.196161E+12 | 0.788389E+11 | 0.00 | 0.458159E+12 | 0.203593E+12 | 0.00 | 0.755798E+10 | 0.00 | 0.00 |
June | 0.335057E+12 | 0.463520E+11 | 0.106252E+13 | 0.159182E+12 | 0.194754E+12 | 0.856758E+11 | 0.00 | 0.567522E+12 | 0.204079E+12 | 0.00 | 0.755798E+10 | 0.00 | 0.00 |
July | 0.314218E+12 | 0.491983E+11 | 0.139340E+13 | 0.164156E+12 | 0.197208E+12 | 0.931515E+11 | 0.00 | 0.699358E+12 | 0.219919E+12 | 0.00 | 0.717402E+10 | 0.00 | 0.00 |
August | 0.350679E+12 | 0.528605E+11 | 0.173200E+13 | 0.164521E+12 | 0.204759E+12 | 0.987378E+11 | 0.00 | 0.799094E+12 | 0.220801E+12 | 0.00 | 0.786111E+10 | 0.00 | 0.00 |
September | 0.314779E+12 | 0.560946E+11 | 0.740713E+12 | 0.158945E+12 | 0.186668E+12 | 0.793195E+11 | 0.00 | 0.455773E+12 | 0.202988E+12 | 0.00 | 0.717402E+10 | 0.00 | 0.00 |
October | 0.328121E+12 | 0.632250E+11 | 0.108340E+13 | 0.164269E+12 | 0.194457E+12 | 0.769760E+11 | 0.00 | 0.499961E+12 | 0.184684E+12 | 53829314.17 | 0.591155E+10 | 0.00 | 0.00 |
November | 0.326607E+12 | 0.655608E+11 | 0.135889E+13 | 0.159043E+12 | 0.173304E+12 | 0.576621E+11 | 0.00 | 0.425446E+12 | 0.141722E+12 | 85622515.41 | 0.322213E+10 | 0.00 | 0.00 |
December | 0.321290E+12 | 0.702728E+11 | 0.170972E+13 | 0.164158E+12 | 0.171523E+12 | 0.475611E+11 | 0.00 | 0.442400E+12 | 0.132747E+12 | 0.263875E+09 | 0.347493E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.392405E+13 | 0.695486E+12 | 0.146764E+14 | 0.193479E+13 | 0.218595E+13 | 0.815950E+12 | 0.00 | 0.575520E+13 | 0.197779E+13 | 0.155349E+10 | 0.653980E+11 | 0.00 | 0.00 |
Minimum of Months | 0.298278E+12 | 0.463520E+11 | 0.740713E+12 | 0.148382E+12 | 0.153276E+12 | 0.384940E+11 | 0.00 | 0.179295E+12 | 0.749153E+11 | 0.00 | 0.322213E+10 | 0.00 | 0.00 |
Maximum of Months | 0.352887E+12 | 0.702728E+11 | 0.173200E+13 | 0.164522E+12 | 0.204759E+12 | 0.987378E+11 | 0.00 | 0.799094E+12 | 0.220801E+12 | 0.503346E+09 | 0.786111E+10 | 0.00 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [J] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.00 | 0.00 | 0.588965E+11 | 0.00 | 0.612033E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.297265E+11 | 0.00 | 0.552086E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.265258E+11 | 0.00 | 0.619526E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.782776E+09 | 0.00 | 0.554228E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.559236E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.528680E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.511629E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.541721E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.519987E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.418300E+09 | 0.00 | 0.559406E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.463567E+10 | 0.00 | 0.569263E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.411589E+11 | 0.00 | 0.593785E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.162144E+12 | 0.00 | 0.672158E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.511629E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.588965E+11 | 0.00 | 0.619526E+11 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | EXTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum} [W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 372703.55 | 31-JAN-08:09 | 57580.60 | 01-JAN-06:10 | 423497.50 | 02-JAN-08:09 | 118525.16 | 31-JAN-08:20 | 116458.25 | 19-JAN-15:50 | 62957.99 | 19-JAN-10:20 | 0.00 | 01-JAN-00:10 |
February | 372917.97 | 01-FEB-08:09 | 57580.60 | 01-FEB-06:10 | 541788.89 | 01-FEB-08:09 | 118525.33 | 01-FEB-08:20 | 122102.92 | 27-FEB-15:50 | 63316.06 | 24-FEB-11:09 | 0.00 | 01-FEB-00:10 |
March | 371856.61 | 27-MAR-07:10 | 57580.60 | 01-MAR-06:10 | 660080.29 | 01-MAR-08:09 | 118524.50 | 27-MAR-07:19 | 123986.99 | 27-MAR-05:10 | 62933.82 | 29-MAR-10:50 | 0.00 | 01-MAR-00:10 |
April | 372703.55 | 14-APR-07:10 | 57580.60 | 01-APR-05:10 | 778371.69 | 03-APR-07:10 | 118525.16 | 14-APR-07:19 | 143802.86 | 18-APR-14:00 | 63356.21 | 14-APR-10:30 | 0.00 | 01-APR-00:10 |
May | 352283.84 | 23-MAY-07:19 | 57580.60 | 01-MAY-05:10 | 423497.50 | 01-MAY-07:10 | 118509.21 | 23-MAY-07:30 | 136903.44 | 04-MAY-15:00 | 63648.64 | 18-MAY-08:50 | 0.00 | 01-MAY-00:10 |
June | 339463.68 | 16-JUN-07:10 | 57580.60 | 01-JUN-05:10 | 541788.89 | 01-JUN-07:10 | 118499.22 | 16-JUN-07:19 | 136828.23 | 28-JUN-15:00 | 63631.37 | 30-JUN-08:09 | 0.00 | 01-JUN-00:10 |
July | 343707.26 | 14-JUL-07:10 | 57580.60 | 01-JUL-05:10 | 660080.29 | 03-JUL-07:10 | 118502.52 | 14-JUL-07:19 | 141149.81 | 07-JUL-15:00 | 66193.26 | 14-JUL-14:30 | 0.00 | 01-JUL-00:10 |
August | 353085.97 | 08-AUG-07:30 | 57580.60 | 01-AUG-05:10 | 778371.69 | 01-AUG-07:10 | 118509.84 | 08-AUG-07:40 | 151679.46 | 30-AUG-15:00 | 63966.29 | 28-AUG-12:09 | 0.00 | 01-AUG-00:10 |
September | 369498.02 | 26-SEP-07:10 | 57580.60 | 01-SEP-05:10 | 423497.50 | 01-SEP-07:10 | 118522.65 | 26-SEP-07:19 | 141139.36 | 01-SEP-14:00 | 63769.96 | 22-SEP-08:30 | 0.00 | 01-SEP-00:10 |
October | 385834.94 | 25-OCT-07:10 | 57580.60 | 01-OCT-05:10 | 541788.89 | 02-OCT-07:10 | 118535.44 | 25-OCT-07:19 | 151314.95 | 05-OCT-15:20 | 63879.32 | 10-OCT-12:09 | 0.00 | 01-OCT-00:10 |
November | 375276.56 | 01-NOV-07:10 | 57580.60 | 01-NOV-05:10 | 660080.29 | 01-NOV-07:10 | 118527.17 | 01-NOV-07:19 | 134314.95 | 02-NOV-15:30 | 65238.79 | 06-NOV-16:40 | 0.00 | 01-NOV-00:10 |
December | 385834.94 | 12-DEC-08:09 | 57580.60 | 01-DEC-06:10 | 778371.69 | 01-DEC-08:09 | 118535.44 | 12-DEC-08:20 | 127578.32 | 15-DEC-15:30 | 62970.06 | 15-DEC-09:39 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 339463.68 | 57580.60 | 423497.50 | 118499.22 | 116458.25 | 62933.82 | 0.00 | |||||||
Maximum of Months | 385834.94 | 57580.60 | 778371.69 | 118535.44 | 151679.46 | 66193.26 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY {Maximum} [W] | HEATREJECTION:ELECTRICITY {TIMESTAMP} | HUMIDIFIER:ELECTRICITY {Maximum} [W] | HUMIDIFIER:ELECTRICITY {TIMESTAMP} | HEATRECOVERY:ELECTRICITY {Maximum} [W] | HEATRECOVERY:ELECTRICITY {TIMESTAMP} | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 320610.38 | 19-JAN-11:00 | 95997.17 | 18-JAN-11:00 | 4028.21 | 21-JAN-12:00 | 5613.48 | 02-JAN-10:09 | 0.00 | 0.00 |
February | 361093.67 | 24-FEB-13:30 | 95997.17 | 01-FEB-13:39 | 4049.48 | 16-FEB-21:00 | 5613.48 | 01-FEB-11:30 | 0.00 | 0.00 |
March | 397927.61 | 28-MAR-13:50 | 95997.17 | 06-MAR-09:39 | 4288.72 | 08-MAR-21:00 | 5613.48 | 04-MAR-14:09 | 0.00 | 0.00 |
April | 459873.45 | 28-APR-15:00 | 95997.17 | 04-APR-15:20 | 3671.99 | 11-APR-16:10 | 5613.48 | 01-APR-06:10 | 0.00 | 0.00 |
May | 353167.52 | 30-MAY-10:39 | 95997.17 | 01-MAY-06:10 | 0.00 | 01-MAY-00:10 | 5613.48 | 01-MAY-06:10 | 0.00 | 0.00 |
June | 411748.93 | 29-JUN-12:09 | 95997.17 | 01-JUN-06:30 | 0.00 | 01-JUN-00:10 | 5613.48 | 01-JUN-06:10 | 0.00 | 0.00 |
July | 461845.27 | 18-JUL-12:09 | 95997.17 | 01-JUL-06:19 | 0.00 | 01-JUL-00:10 | 5613.48 | 01-JUL-06:10 | 0.00 | 0.00 |
August | 487572.39 | 07-AUG-12:09 | 95997.17 | 01-AUG-06:10 | 0.00 | 01-AUG-00:10 | 5613.48 | 01-AUG-06:10 | 0.00 | 0.00 |
September | 364071.99 | 07-SEP-13:00 | 95997.17 | 01-SEP-06:10 | 0.00 | 01-SEP-00:10 | 5613.48 | 01-SEP-06:10 | 0.00 | 0.00 |
October | 421052.23 | 06-OCT-13:00 | 95997.17 | 02-OCT-10:30 | 2511.23 | 27-OCT-16:10 | 5613.48 | 02-OCT-08:39 | 0.00 | 0.00 |
November | 435874.85 | 07-NOV-13:20 | 95997.17 | 01-NOV-06:10 | 2664.79 | 22-NOV-18:10 | 5613.48 | 01-NOV-06:10 | 0.00 | 0.00 |
December | 440559.75 | 12-DEC-14:20 | 95997.17 | 08-DEC-15:50 | 3467.06 | 20-DEC-20:49 | 5613.48 | 02-DEC-13:20 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | ||||||||
Minimum of Months | 320610.38 | 95997.17 | 0.00 | 5613.48 | 0.00 | 0.00 | ||||
Maximum of Months | 487572.39 | 95997.17 | 4288.72 | 5613.48 | 0.00 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY {AT MAX/MIN} [W] | |
January | 1431185.45 | 19-JAN-16:49 | 334729.47 | 423497.50 | 0.00 | 84452.08 | 107814.47 | 61276.03 | 0.00 | 317805.26 | 95997.17 |
February | 1591656.64 | 27-FEB-16:49 | 334652.47 | 541788.89 | 0.00 | 84451.06 | 116260.41 | 61503.57 | 0.00 | 351389.59 | 95997.17 |
March | 1745447.56 | 07-MAR-08:00 | 332294.83 | 660080.29 | 0.00 | 118493.64 | 87121.19 | 62347.38 | 0.00 | 383499.60 | 95997.17 |
April | 1953721.35 | 28-APR-15:00 | 332294.83 | 778371.69 | 0.00 | 84450.25 | 134717.17 | 62403.31 | 0.00 | 459873.45 | 95997.17 |
May | 1477005.05 | 04-MAY-15:39 | 332294.83 | 423497.50 | 0.00 | 84450.25 | 136472.49 | 61674.22 | 0.00 | 337005.12 | 95997.17 |
June | 1653978.24 | 28-JUN-15:09 | 332294.83 | 541788.89 | 0.00 | 84450.25 | 134521.62 | 62493.34 | 0.00 | 396818.67 | 95997.17 |
July | 1828755.22 | 21-JUL-15:50 | 332294.83 | 660080.29 | 0.00 | 84450.25 | 138499.70 | 62529.03 | 0.00 | 449290.48 | 95997.17 |
August | 1978865.65 | 03-AUG-15:30 | 332294.83 | 778371.69 | 0.00 | 84450.25 | 147115.99 | 62781.37 | 0.00 | 472240.89 | 95997.17 |
September | 1483846.38 | 01-SEP-15:09 | 332294.83 | 423497.50 | 0.00 | 84450.25 | 139585.91 | 62398.52 | 0.00 | 340008.74 | 95997.17 |
October | 1675352.47 | 25-OCT-07:10 | 385834.94 | 541788.89 | 0.00 | 118337.19 | 82299.02 | 61468.89 | 0.00 | 384012.90 | 95997.17 |
November | 1775171.78 | 02-NOV-15:09 | 332294.83 | 660080.29 | 0.00 | 84450.25 | 133501.42 | 61980.88 | 0.00 | 401253.46 | 95997.17 |
December | 1916722.58 | 15-DEC-16:40 | 343575.76 | 778371.69 | 0.00 | 84459.03 | 120096.61 | 62615.80 | 0.00 | 425993.04 | 95997.17 |
Annual Sum or Average | |||||||||||
Minimum of Months | 1431185.45 | 332294.83 | 423497.50 | 0.00 | 84450.25 | 82299.02 | 61276.03 | 0.00 | 317805.26 | 95997.17 | |
Maximum of Months | 1978865.65 | 385834.94 | 778371.69 | 0.00 | 118493.64 | 147115.99 | 62781.37 | 0.00 | 472240.89 | 95997.17 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS {Maximum} [W] | WATERSYSTEMS:NATURALGAS {TIMESTAMP} | COGENERATION:NATURALGAS [] | |
January | 0.00 | 0.00 | 752322.10 | 21-JAN-07:10 | 0.00 | 75833.66 | 20-JAN-12:50 | 0.00 |
February | 0.00 | 0.00 | 709380.30 | 17-FEB-07:10 | 0.00 | 75723.36 | 03-FEB-12:30 | 0.00 |
March | 0.00 | 0.00 | 677041.28 | 09-MAR-07:10 | 0.00 | 74725.57 | 02-MAR-12:39 | 0.00 |
April | 0.00 | 0.00 | 148482.37 | 18-APR-14:50 | 0.00 | 71398.14 | 11-APR-11:50 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 69010.79 | 02-MAY-11:39 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 65219.41 | 02-JUN-11:00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 62731.85 | 03-JUL-11:50 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 63470.56 | 25-AUG-11:20 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 66591.80 | 25-SEP-11:39 | 0.00 |
October | 0.00 | 0.00 | 76443.72 | 28-OCT-06:10 | 0.00 | 70130.54 | 25-OCT-11:30 | 0.00 |
November | 0.00 | 0.00 | 239330.43 | 15-NOV-07:10 | 0.00 | 73577.98 | 29-NOV-12:20 | 0.00 |
December | 0.00 | 0.00 | 763980.07 | 21-DEC-07:10 | 0.00 | 75294.13 | 27-DEC-12:00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 62731.85 | 0.00 | ||
Maximum of Months | 0.00 | 0.00 | 763980.07 | 0.00 | 75833.66 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 26.15 | 0.00 | 26.15 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 26.92 | 0.00 | 26.92 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 26.99 | 0.00 | 26.99 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 25.79 | 0.00 | 25.79 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 3.67 | 26.17 | 0.33 | 26.16 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 25.63 | 0.33 | 25.52 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 6.17 | 25.81 | 0.50 | 25.72 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 9.17 | 26.03 | 0.00 | 26.03 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 9.33 | 26.44 | 1.67 | 26.55 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 9.67 | 26.52 | 1.17 | 26.63 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 8.17 | 26.64 | 0.67 | 26.65 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 7.33 | 26.68 | 0.67 | 26.74 |
Annual Sum or Average | 0.00 | 0.00 | 63.83 | 26.37 | 5.33 | 26.40 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 25.63 | 0.00 | 25.52 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 9.67 | 26.99 | 1.67 | 26.99 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 25.92 | 0.00 | 25.92 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.17 | 25.92 | 0.00 | 25.92 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 25.92 | 0.00 | 25.92 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.67 | 18.86 | 0.17 | 19.11 | 0.00 | 19.11 | 0.00 | 19.11 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.67 | 18.86 | 0.17 | 19.11 | 0.00 | 19.11 | 0.00 | 19.11 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.67 | 18.86 | 0.17 | 19.11 | 0.00 | 19.11 | 0.00 | 19.11 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.30 | 0.17 | 27.30 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.39 | 0.67 | 27.39 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.34 | 0.67 | 27.34 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.28 | 0.33 | 27.28 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 1.83 | 27.34 | 1.83 | 27.34 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.39 | 0.67 | 27.39 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.36 | 0.33 | 27.36 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.43 | 0.17 | 27.43 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.71 | 0.83 | 27.71 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 27.98 | 1.17 | 27.98 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 5.67 | 28.02 | 5.67 | 28.02 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 27.87 | 2.50 | 27.87 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 27.84 | 5.00 | 27.84 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 27.78 | 1.83 | 27.78 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 5.50 | 27.95 | 5.50 | 27.95 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 27.80 | 3.50 | 27.80 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.53 | 0.83 | 27.53 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 27.33 | 27.88 | 27.33 | 27.88 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 5.67 | 28.02 | 5.67 | 28.02 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 7.17 | 27.94 | 7.17 | 27.94 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 4.17 | 27.77 | 4.17 | 27.77 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 27.65 | 2.50 | 27.65 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.35 | 0.67 | 27.35 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.40 | 0.83 | 27.40 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 4.50 | 27.42 | 4.33 | 27.46 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 7.67 | 27.79 | 7.33 | 27.81 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 11.33 | 27.97 | 10.83 | 27.99 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 11.50 | 27.51 | 11.33 | 27.51 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 7.67 | 28.14 | 7.67 | 28.14 |
Annual Sum or Average | 0.00 | 0.00 | 58.00 | 27.79 | 56.83 | 27.80 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 11.50 | 28.14 | 11.33 | 28.14 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 27.77 | 1.33 | 27.77 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 27.90 | 2.00 | 27.90 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 27.60 | 3.00 | 27.76 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 14.67 | 27.42 | 5.17 | 27.62 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 7.50 | 27.79 | 4.17 | 27.87 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 17.00 | 27.33 | 4.83 | 27.50 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 25.67 | 27.29 | 10.00 | 27.48 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 25.33 | 27.17 | 7.67 | 27.39 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 7.00 | 28.00 | 4.33 | 28.14 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 13.67 | 27.52 | 6.50 | 27.71 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 6.83 | 27.60 | 4.50 | 27.77 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 7.83 | 27.48 | 4.67 | 27.67 |
Annual Sum or Average | 0.00 | 0.00 | 134.00 | 27.43 | 58.17 | 27.62 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 27.17 | 1.33 | 27.39 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 25.67 | 28.00 | 10.00 | 28.14 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.33 | 19.36 | 0.00 | 19.36 | 0.00 | 19.36 | 0.00 | 19.36 |
February | 0.17 | 19.12 | 0.00 | 19.12 | 0.00 | 19.12 | 0.00 | 19.12 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.32 | 0.33 | 27.32 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.17 | 19.30 | 0.00 | 19.30 | 0.00 | 19.30 | 0.00 | 19.30 |
Annual Sum or Average | 0.67 | 19.29 | 0.00 | 19.29 | 0.33 | 21.96 | 0.33 | 23.30 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.33 | 19.36 | 0.00 | 19.36 | 0.33 | 27.32 | 0.33 | 27.32 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.17 | 19.35 | 0.00 | 19.35 | 0.00 | 19.35 | 0.00 | 19.35 |
February | 0.17 | 19.27 | 0.00 | 19.27 | 0.00 | 19.27 | 0.00 | 19.27 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.66 | 0.50 | 27.66 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 28.15 | 1.17 | 28.15 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 7.33 | 27.98 | 7.33 | 27.98 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 27.89 | 3.50 | 27.89 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 7.33 | 27.91 | 7.33 | 27.91 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 4.83 | 27.69 | 4.83 | 27.69 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 6.17 | 28.00 | 6.17 | 28.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 3.83 | 27.82 | 3.83 | 27.82 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.45 | 0.33 | 27.45 |
December | 0.17 | 19.30 | 0.00 | 19.30 | 0.00 | 19.30 | 0.00 | 19.30 |
Annual Sum or Average | 0.50 | 19.31 | 0.00 | 19.31 | 35.00 | 27.78 | 35.00 | 27.84 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.27 | 0.00 | 19.27 |
Maximum of Months | 0.17 | 19.35 | 0.00 | 19.35 | 7.33 | 28.15 | 7.33 | 28.15 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 8.17 | 27.20 | 8.17 | 27.20 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 27.84 | 3.17 | 27.84 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 27.62 | 1.83 | 27.62 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.38 | 0.33 | 27.38 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 27.43 | 3.00 | 27.43 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 7.50 | 27.85 | 7.17 | 27.86 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 11.17 | 28.02 | 10.17 | 28.05 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 15.33 | 26.64 | 15.17 | 26.63 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 8.67 | 27.31 | 8.67 | 27.31 |
Annual Sum or Average | 0.00 | 0.00 | 59.17 | 27.37 | 57.67 | 27.37 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 15.33 | 28.02 | 15.17 | 28.05 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 28.12 | 0.50 | 28.12 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 27.57 | 1.00 | 27.57 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 27.98 | 2.17 | 27.99 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 4.50 | 28.15 | 2.83 | 28.14 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 28.10 | 3.00 | 28.14 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 8.17 | 27.73 | 5.67 | 27.74 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.83 | 27.76 | 2.83 | 27.77 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 5.67 | 28.17 | 3.83 | 28.23 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 4.67 | 28.06 | 3.33 | 28.09 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.62 | 0.83 | 27.62 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.56 | 0.50 | 27.56 |
Annual Sum or Average | 0.00 | 0.00 | 37.83 | 27.96 | 26.50 | 27.97 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 8.17 | 28.17 | 5.67 | 28.23 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 2.83 | 18.86 | 0.00 | 18.86 | 0.00 | 18.86 | 0.00 | 18.86 |
February | 4.00 | 17.09 | 1.50 | 16.88 | 0.00 | 16.88 | 0.00 | 16.88 |
March | 0.67 | 19.05 | 0.00 | 19.05 | 0.00 | 19.05 | 0.00 | 19.05 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 27.24 | 1.50 | 27.31 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 27.51 | 1.33 | 27.51 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 5.67 | 27.45 | 4.67 | 27.46 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 27.46 | 2.67 | 27.46 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 27.57 | 1.50 | 27.59 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 27.43 | 1.00 | 27.43 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 1.67 | 18.80 | 0.00 | 18.80 | 0.00 | 18.80 | 0.00 | 18.80 |
Annual Sum or Average | 9.17 | 18.09 | 1.50 | 17.84 | 15.50 | 23.53 | 12.67 | 24.82 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 4.00 | 19.05 | 1.50 | 19.05 | 5.67 | 27.57 | 4.67 | 27.59 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 2.33 | 18.84 | 0.00 | 18.84 | 0.00 | 18.84 | 0.00 | 18.84 |
February | 2.67 | 17.24 | 0.50 | 17.11 | 0.00 | 17.11 | 0.00 | 17.11 |
March | 0.67 | 19.12 | 0.00 | 19.12 | 0.50 | 22.69 | 0.50 | 24.11 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 28.12 | 1.17 | 28.12 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 9.00 | 28.07 | 8.50 | 28.09 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 7.50 | 27.78 | 7.33 | 27.79 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 11.83 | 27.86 | 11.33 | 27.87 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 6.67 | 27.81 | 6.50 | 27.81 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 8.50 | 28.00 | 8.33 | 28.01 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 27.81 | 5.00 | 27.81 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 1.50 | 18.78 | 0.00 | 18.78 | 0.00 | 18.78 | 0.00 | 18.78 |
Annual Sum or Average | 7.17 | 18.26 | 0.50 | 18.14 | 50.17 | 26.61 | 48.67 | 27.20 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2.67 | 19.12 | 0.50 | 19.12 | 11.83 | 28.12 | 11.33 | 28.12 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 1.33 | 19.12 | 0.00 | 19.12 | 5.00 | 26.13 | 5.00 | 26.96 |
February | 1.50 | 16.83 | 0.67 | 16.63 | 1.67 | 21.59 | 1.67 | 23.55 |
March | 0.50 | 19.25 | 0.00 | 19.25 | 1.67 | 25.74 | 1.67 | 26.58 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.39 | 0.67 | 27.39 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 27.44 | 2.67 | 27.44 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 27.49 | 1.00 | 27.49 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 4.17 | 27.43 | 3.83 | 27.44 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 27.60 | 4.83 | 27.61 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 8.67 | 27.98 | 7.83 | 28.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 10.33 | 28.16 | 9.17 | 28.20 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 9.50 | 27.31 | 9.50 | 27.31 |
December | 0.50 | 18.79 | 0.00 | 18.79 | 5.83 | 27.34 | 5.83 | 27.69 |
Annual Sum or Average | 3.83 | 18.20 | 0.67 | 17.90 | 56.50 | 27.06 | 53.67 | 27.41 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 21.59 | 0.67 | 23.55 |
Maximum of Months | 1.50 | 19.25 | 0.67 | 19.25 | 10.33 | 28.16 | 9.50 | 28.20 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 1.50 | 19.09 | 0.00 | 19.09 | 0.17 | 19.91 | 0.17 | 20.58 |
February | 1.50 | 16.90 | 0.83 | 16.58 | 0.50 | 18.61 | 0.50 | 20.03 |
March | 0.50 | 19.34 | 0.00 | 19.34 | 0.83 | 24.59 | 0.83 | 25.80 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 27.98 | 2.00 | 28.01 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 28.30 | 3.00 | 28.34 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 5.50 | 28.28 | 3.17 | 28.33 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 9.33 | 27.90 | 6.00 | 27.93 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 5.33 | 27.89 | 3.83 | 27.91 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 6.17 | 28.34 | 4.17 | 28.41 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 5.33 | 28.13 | 4.00 | 28.16 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.58 | 0.83 | 27.58 |
December | 0.50 | 18.80 | 0.00 | 18.80 | 0.50 | 23.22 | 0.50 | 24.69 |
Annual Sum or Average | 4.00 | 18.27 | 0.83 | 17.87 | 43.00 | 27.05 | 29.00 | 27.46 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 18.61 | 0.17 | 20.03 |
Maximum of Months | 1.50 | 19.34 | 0.83 | 19.34 | 9.33 | 28.34 | 6.00 | 28.41 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.56 | 0.17 | 27.56 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 19.33 | 27.68 | 19.33 | 27.68 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 19.50 | 27.68 | 19.50 | 27.68 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 19.33 | 27.68 | 19.33 | 27.68 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 13.33 | 27.68 | 13.33 | 27.68 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 13.33 | 27.68 | 13.33 | 27.68 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 13.33 | 27.68 | 13.33 | 27.68 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 6.33 | 27.68 | 6.33 | 27.68 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 6.33 | 27.68 | 6.33 | 27.68 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 6.33 | 27.68 | 6.33 | 27.68 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 101.17 | 28.15 | 100.67 | 28.15 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 462.83 | 28.89 | 406.50 | 28.94 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 38.00 | 28.04 | 38.00 | 28.04 |
Annual Sum or Average | 0.00 | 0.00 | 602.00 | 28.71 | 545.17 | 28.74 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 462.83 | 28.89 | 406.50 | 28.94 |
Report: ComfortReportSimple55Monthly
For: BASEMENT
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 53.67 | 24.61 | 245.83 | 25.02 | 43.17 | 24.98 |
February | 76.83 | 24.57 | 320.83 | 24.70 | 65.33 | 24.70 |
March | 87.33 | 24.72 | 320.67 | 24.68 | 77.83 | 24.71 |
April | 157.67 | 24.82 | 434.17 | 24.64 | 157.67 | 24.68 |
May | 267.17 | 24.99 | 508.00 | 24.68 | 267.17 | 24.76 |
June | 248.17 | 24.89 | 496.00 | 24.61 | 248.17 | 24.68 |
July | 252.17 | 25.23 | 497.00 | 24.83 | 252.17 | 24.93 |
August | 203.00 | 25.25 | 514.00 | 24.72 | 203.00 | 24.83 |
September | 224.17 | 25.25 | 485.00 | 24.79 | 224.17 | 24.90 |
October | 167.17 | 25.50 | 453.33 | 24.92 | 167.17 | 25.04 |
November | 75.33 | 25.41 | 395.67 | 24.88 | 75.33 | 24.95 |
December | 55.50 | 24.99 | 320.00 | 24.96 | 54.50 | 24.97 |
Annual Sum or Average | 1868.17 | 25.08 | 4990.50 | 24.77 | 1835.67 | 24.84 |
Minimum of Months | 53.67 | 24.57 | 245.83 | 24.61 | 43.17 | 24.68 |
Maximum of Months | 267.17 | 25.50 | 514.00 | 25.02 | 267.17 | 25.04 |
Report: ComfortReportSimple55Monthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 108.83 | 23.49 | 199.67 | 24.16 | 0.00 | 24.16 |
February | 47.83 | 23.58 | 281.33 | 24.25 | 0.00 | 24.25 |
March | 29.17 | 23.57 | 316.50 | 24.33 | 0.00 | 24.33 |
April | 0.00 | 0.00 | 428.00 | 24.26 | 0.00 | 24.26 |
May | 0.00 | 0.00 | 485.50 | 24.23 | 0.00 | 24.23 |
June | 0.00 | 0.00 | 475.00 | 24.16 | 0.00 | 24.16 |
July | 0.00 | 0.00 | 482.50 | 24.14 | 0.00 | 24.14 |
August | 0.00 | 0.00 | 512.67 | 24.12 | 0.00 | 24.12 |
September | 0.00 | 0.00 | 460.83 | 24.24 | 0.00 | 24.24 |
October | 1.50 | 23.56 | 446.00 | 24.31 | 0.00 | 24.31 |
November | 0.33 | 23.85 | 379.17 | 24.40 | 0.00 | 24.40 |
December | 13.17 | 23.64 | 317.00 | 24.44 | 0.00 | 24.44 |
Annual Sum or Average | 200.83 | 23.53 | 4784.17 | 24.24 | 0.00 | 24.24 |
Minimum of Months | 0.00 | 0.00 | 199.67 | 24.12 | 0.00 | 24.12 |
Maximum of Months | 108.83 | 23.85 | 512.67 | 24.44 | 0.00 | 24.44 |
Report: ComfortReportSimple55Monthly
For: CORE_MID
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 311.83 | 23.09 | 79.17 | 23.31 | 0.00 | 23.31 |
February | 218.67 | 23.12 | 136.67 | 23.53 | 0.00 | 23.53 |
March | 199.50 | 23.13 | 161.00 | 23.63 | 0.00 | 23.63 |
April | 67.50 | 23.20 | 253.67 | 24.12 | 0.00 | 24.12 |
May | 21.83 | 23.18 | 361.67 | 24.17 | 0.00 | 24.17 |
June | 23.17 | 23.19 | 338.67 | 24.15 | 0.00 | 24.15 |
July | 28.17 | 23.20 | 323.67 | 24.15 | 0.00 | 24.15 |
August | 15.50 | 23.19 | 369.67 | 24.18 | 0.00 | 24.18 |
September | 37.00 | 23.16 | 306.67 | 24.11 | 0.00 | 24.11 |
October | 38.33 | 23.21 | 314.33 | 24.16 | 0.00 | 24.16 |
November | 129.67 | 23.21 | 203.17 | 23.86 | 0.00 | 23.86 |
December | 230.33 | 23.08 | 127.50 | 23.51 | 0.00 | 23.51 |
Annual Sum or Average | 1321.50 | 23.13 | 2975.83 | 23.90 | 0.00 | 23.90 |
Minimum of Months | 15.50 | 23.08 | 79.17 | 23.31 | 0.00 | 23.31 |
Maximum of Months | 311.83 | 23.21 | 369.67 | 24.18 | 0.00 | 24.18 |
Report: ComfortReportSimple55Monthly
For: CORE_TOP
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 402.33 | 22.15 | 72.33 | 22.36 | 12.83 | 22.31 |
February | 300.83 | 22.26 | 115.33 | 22.57 | 17.83 | 22.43 |
March | 285.50 | 22.61 | 147.00 | 23.08 | 6.67 | 23.04 |
April | 106.17 | 23.07 | 247.00 | 23.92 | 0.00 | 23.92 |
May | 8.83 | 23.15 | 401.33 | 24.22 | 0.00 | 24.22 |
June | 0.17 | 23.30 | 402.00 | 24.21 | 0.00 | 24.21 |
July | 1.50 | 23.24 | 407.67 | 24.23 | 0.00 | 24.23 |
August | 0.17 | 23.28 | 414.67 | 24.25 | 0.00 | 24.25 |
September | 12.50 | 23.22 | 342.33 | 24.18 | 0.00 | 24.18 |
October | 60.67 | 22.83 | 323.50 | 24.05 | 0.00 | 24.05 |
November | 239.67 | 22.78 | 143.67 | 23.29 | 0.00 | 23.29 |
December | 355.33 | 22.40 | 93.17 | 22.69 | 9.00 | 22.65 |
Annual Sum or Average | 1773.67 | 22.47 | 3110.00 | 23.55 | 46.33 | 23.51 |
Minimum of Months | 0.17 | 22.15 | 72.33 | 22.36 | 0.00 | 22.31 |
Maximum of Months | 402.33 | 23.30 | 414.67 | 24.25 | 17.83 | 24.25 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 350.67 | 22.37 | 96.00 | 22.75 | 1.83 | 22.74 |
February | 233.83 | 22.60 | 142.50 | 23.12 | 6.50 | 23.08 |
March | 214.00 | 22.88 | 196.67 | 23.53 | 0.00 | 23.53 |
April | 40.00 | 23.38 | 351.17 | 24.12 | 0.00 | 24.12 |
May | 9.33 | 26.09 | 507.83 | 24.42 | 9.33 | 24.45 |
June | 2.00 | 26.84 | 494.83 | 24.35 | 2.00 | 24.36 |
July | 10.00 | 26.77 | 496.00 | 24.46 | 10.00 | 24.50 |
August | 7.33 | 26.79 | 514.00 | 24.31 | 7.33 | 24.35 |
September | 10.33 | 26.12 | 479.00 | 24.41 | 10.33 | 24.45 |
October | 41.67 | 23.69 | 420.67 | 24.31 | 6.33 | 24.33 |
November | 151.00 | 23.26 | 231.17 | 23.84 | 0.00 | 23.84 |
December | 247.83 | 22.83 | 162.33 | 23.37 | 0.00 | 23.37 |
Annual Sum or Average | 1318.00 | 22.87 | 4092.17 | 23.96 | 53.67 | 23.97 |
Minimum of Months | 2.00 | 22.37 | 96.00 | 22.75 | 0.00 | 22.74 |
Maximum of Months | 350.67 | 26.84 | 514.00 | 24.46 | 10.33 | 24.50 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 321.67 | 22.37 | 111.33 | 22.89 | 4.50 | 22.89 |
February | 235.83 | 22.54 | 141.33 | 23.15 | 6.33 | 23.13 |
March | 226.50 | 22.56 | 203.50 | 23.41 | 5.17 | 23.45 |
April | 97.67 | 23.14 | 301.17 | 23.96 | 5.83 | 24.01 |
May | 35.17 | 26.60 | 477.67 | 24.58 | 34.00 | 24.72 |
June | 14.33 | 26.48 | 465.67 | 24.39 | 12.83 | 24.45 |
July | 27.17 | 26.47 | 458.50 | 24.50 | 24.67 | 24.62 |
August | 21.67 | 25.25 | 457.50 | 24.27 | 12.50 | 24.33 |
September | 38.50 | 26.25 | 417.50 | 24.61 | 33.17 | 24.75 |
October | 73.17 | 24.09 | 378.83 | 24.36 | 22.83 | 24.47 |
November | 168.00 | 22.95 | 228.00 | 23.76 | 3.67 | 23.78 |
December | 282.67 | 22.47 | 134.00 | 23.04 | 2.50 | 23.04 |
Annual Sum or Average | 1542.33 | 22.98 | 3775.00 | 23.95 | 168.00 | 24.03 |
Minimum of Months | 14.33 | 22.37 | 111.33 | 22.89 | 2.50 | 22.89 |
Maximum of Months | 321.67 | 26.60 | 477.67 | 24.61 | 34.00 | 24.75 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 211.33 | 23.11 | 220.17 | 23.86 | 26.67 | 24.03 |
February | 143.00 | 23.07 | 252.17 | 23.90 | 18.67 | 23.95 |
March | 170.83 | 22.89 | 256.33 | 23.76 | 12.67 | 23.82 |
April | 47.83 | 23.51 | 353.33 | 24.20 | 3.67 | 24.22 |
May | 12.17 | 26.21 | 506.83 | 24.42 | 12.17 | 24.46 |
June | 1.17 | 27.03 | 492.00 | 24.32 | 1.17 | 24.32 |
July | 11.33 | 26.77 | 494.33 | 24.45 | 11.33 | 24.50 |
August | 20.17 | 26.78 | 513.83 | 24.39 | 20.17 | 24.48 |
September | 40.00 | 26.73 | 478.33 | 24.64 | 40.00 | 24.79 |
October | 69.00 | 25.79 | 452.00 | 24.71 | 47.83 | 24.90 |
November | 86.83 | 24.65 | 365.83 | 24.59 | 33.83 | 24.76 |
December | 163.17 | 23.53 | 285.83 | 24.22 | 30.50 | 24.40 |
Annual Sum or Average | 976.83 | 23.79 | 4671.00 | 24.31 | 258.67 | 24.41 |
Minimum of Months | 1.17 | 22.89 | 220.17 | 23.76 | 1.17 | 23.82 |
Maximum of Months | 211.33 | 27.03 | 513.83 | 24.71 | 47.83 | 24.90 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 257.00 | 22.51 | 173.67 | 23.29 | 6.00 | 23.33 |
February | 120.83 | 22.91 | 265.50 | 23.97 | 8.17 | 24.02 |
March | 90.33 | 23.42 | 351.67 | 24.28 | 11.17 | 24.35 |
April | 28.17 | 26.91 | 466.17 | 24.67 | 27.67 | 24.79 |
May | 26.17 | 26.80 | 508.00 | 24.58 | 26.17 | 24.68 |
June | 28.50 | 26.94 | 496.00 | 24.59 | 28.50 | 24.71 |
July | 54.00 | 26.80 | 497.00 | 24.78 | 54.00 | 24.96 |
August | 45.17 | 26.82 | 514.00 | 24.65 | 45.17 | 24.81 |
September | 29.50 | 26.88 | 483.33 | 24.61 | 29.50 | 24.73 |
October | 46.17 | 26.04 | 468.33 | 24.69 | 35.67 | 24.83 |
November | 42.33 | 24.87 | 399.83 | 24.56 | 18.83 | 24.66 |
December | 97.17 | 23.88 | 329.50 | 24.49 | 20.00 | 24.61 |
Annual Sum or Average | 865.33 | 24.18 | 4953.00 | 24.46 | 310.83 | 24.58 |
Minimum of Months | 26.17 | 22.51 | 173.67 | 23.29 | 6.00 | 23.33 |
Maximum of Months | 257.00 | 26.94 | 514.00 | 24.78 | 54.00 | 24.96 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 450.50 | 21.54 | 111.17 | 21.56 | 78.50 | 21.44 |
February | 370.83 | 21.83 | 100.17 | 21.87 | 49.17 | 21.69 |
March | 369.33 | 22.17 | 107.67 | 22.41 | 24.33 | 22.31 |
April | 183.50 | 23.06 | 233.33 | 23.70 | 11.17 | 23.75 |
May | 26.33 | 25.64 | 504.67 | 24.42 | 26.33 | 24.48 |
June | 8.83 | 25.82 | 492.17 | 24.38 | 7.83 | 24.41 |
July | 37.50 | 26.19 | 488.67 | 24.59 | 37.50 | 24.69 |
August | 25.67 | 25.81 | 504.83 | 24.41 | 25.67 | 24.48 |
September | 33.50 | 25.15 | 443.50 | 24.39 | 31.83 | 24.44 |
October | 114.50 | 23.44 | 365.83 | 24.12 | 29.00 | 24.19 |
November | 308.17 | 22.36 | 107.83 | 22.81 | 1.83 | 22.81 |
December | 406.67 | 21.82 | 90.33 | 22.01 | 35.83 | 21.94 |
Annual Sum or Average | 2335.33 | 22.29 | 3550.17 | 23.39 | 359.00 | 23.37 |
Minimum of Months | 8.83 | 21.54 | 90.33 | 21.56 | 1.83 | 21.44 |
Maximum of Months | 450.50 | 26.19 | 504.83 | 24.59 | 78.50 | 24.69 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 369.00 | 21.74 | 76.50 | 21.89 | 40.00 | 21.80 |
February | 292.83 | 21.94 | 91.67 | 22.19 | 28.00 | 22.07 |
March | 266.83 | 22.11 | 130.83 | 22.72 | 18.33 | 22.68 |
April | 142.17 | 23.01 | 219.83 | 23.91 | 15.83 | 24.00 |
May | 51.83 | 26.41 | 393.17 | 24.76 | 49.50 | 24.94 |
June | 29.33 | 26.36 | 390.50 | 24.61 | 26.67 | 24.74 |
July | 61.00 | 26.45 | 396.00 | 24.87 | 57.50 | 25.07 |
August | 44.67 | 26.02 | 390.83 | 24.64 | 39.17 | 24.79 |
September | 74.67 | 25.24 | 322.50 | 24.70 | 49.83 | 24.89 |
October | 118.50 | 23.81 | 288.00 | 24.35 | 39.00 | 24.53 |
November | 239.67 | 22.44 | 117.67 | 23.10 | 4.50 | 23.14 |
December | 335.83 | 21.90 | 80.00 | 22.17 | 26.67 | 22.12 |
Annual Sum or Average | 2026.33 | 22.69 | 2897.50 | 23.68 | 395.00 | 23.77 |
Minimum of Months | 29.33 | 21.74 | 76.50 | 21.89 | 4.50 | 21.80 |
Maximum of Months | 369.00 | 26.45 | 396.00 | 24.87 | 57.50 | 25.07 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 248.67 | 22.72 | 205.50 | 23.48 | 41.17 | 23.59 |
February | 188.50 | 22.61 | 213.17 | 23.48 | 22.67 | 23.49 |
March | 237.50 | 22.46 | 205.33 | 23.22 | 19.50 | 23.21 |
April | 125.00 | 23.21 | 288.50 | 24.00 | 13.33 | 24.06 |
May | 28.33 | 25.69 | 500.00 | 24.43 | 28.33 | 24.49 |
June | 8.83 | 25.61 | 488.17 | 24.36 | 7.67 | 24.38 |
July | 37.50 | 26.13 | 485.83 | 24.57 | 37.50 | 24.68 |
August | 38.83 | 26.18 | 507.00 | 24.51 | 38.83 | 24.62 |
September | 60.67 | 26.24 | 463.00 | 24.66 | 60.67 | 24.83 |
October | 90.50 | 25.37 | 436.33 | 24.70 | 60.00 | 24.90 |
November | 140.83 | 23.86 | 312.33 | 24.37 | 35.00 | 24.56 |
December | 218.50 | 22.90 | 241.33 | 23.77 | 37.33 | 23.92 |
Annual Sum or Average | 1423.67 | 23.43 | 4346.50 | 24.17 | 402.00 | 24.27 |
Minimum of Months | 8.83 | 22.46 | 205.33 | 23.22 | 7.67 | 23.21 |
Maximum of Months | 248.67 | 26.24 | 507.00 | 24.70 | 60.67 | 24.90 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 391.17 | 21.77 | 97.83 | 22.02 | 38.33 | 21.95 |
February | 300.67 | 21.93 | 123.50 | 22.36 | 25.83 | 22.25 |
March | 297.83 | 22.12 | 157.50 | 22.76 | 18.67 | 22.73 |
April | 138.17 | 23.29 | 298.50 | 24.07 | 21.33 | 24.19 |
May | 31.67 | 26.37 | 475.33 | 24.52 | 31.67 | 24.63 |
June | 24.83 | 26.34 | 475.33 | 24.51 | 22.17 | 24.60 |
July | 45.33 | 26.48 | 482.17 | 24.67 | 44.17 | 24.82 |
August | 31.67 | 26.39 | 498.33 | 24.53 | 30.50 | 24.63 |
September | 50.67 | 25.30 | 421.83 | 24.51 | 35.83 | 24.64 |
October | 97.33 | 23.96 | 380.50 | 24.33 | 36.17 | 24.47 |
November | 260.33 | 22.43 | 165.67 | 23.16 | 5.67 | 23.20 |
December | 334.00 | 21.91 | 130.17 | 22.47 | 20.83 | 22.45 |
Annual Sum or Average | 2003.67 | 22.56 | 3706.67 | 23.70 | 331.17 | 23.76 |
Minimum of Months | 24.83 | 21.77 | 97.83 | 22.02 | 5.67 | 21.95 |
Maximum of Months | 391.17 | 26.48 | 498.33 | 24.67 | 44.17 | 24.82 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 457.33 | 21.17 | 192.00 | 21.08 | 162.50 | 20.93 |
February | 384.83 | 21.48 | 145.33 | 21.43 | 95.00 | 21.20 |
March | 384.17 | 21.85 | 144.83 | 22.00 | 64.17 | 21.81 |
April | 203.17 | 22.77 | 224.50 | 23.52 | 11.83 | 23.57 |
May | 41.67 | 25.89 | 498.50 | 24.49 | 41.67 | 24.59 |
June | 26.17 | 26.04 | 489.83 | 24.47 | 24.17 | 24.55 |
July | 56.00 | 26.32 | 486.00 | 24.70 | 56.00 | 24.85 |
August | 46.33 | 25.95 | 498.17 | 24.51 | 45.00 | 24.62 |
September | 58.00 | 24.94 | 431.67 | 24.44 | 45.50 | 24.52 |
October | 131.67 | 23.22 | 361.67 | 24.00 | 41.67 | 24.06 |
November | 341.17 | 21.96 | 124.67 | 22.31 | 32.83 | 22.21 |
December | 417.67 | 21.45 | 166.83 | 21.49 | 116.83 | 21.34 |
Annual Sum or Average | 2548.17 | 22.12 | 3764.00 | 23.14 | 737.17 | 23.05 |
Minimum of Months | 26.17 | 21.17 | 124.67 | 21.08 | 11.83 | 20.93 |
Maximum of Months | 457.33 | 26.32 | 498.50 | 24.70 | 162.50 | 24.85 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 442.50 | 21.42 | 139.50 | 21.45 | 96.67 | 21.29 |
February | 342.67 | 21.63 | 137.67 | 21.83 | 54.67 | 21.61 |
March | 309.17 | 21.91 | 195.67 | 22.50 | 46.50 | 22.37 |
April | 153.00 | 22.82 | 282.83 | 23.81 | 18.00 | 23.90 |
May | 60.00 | 26.34 | 472.33 | 24.68 | 56.50 | 24.86 |
June | 45.67 | 26.26 | 470.33 | 24.59 | 41.33 | 24.74 |
July | 74.33 | 26.33 | 472.17 | 24.79 | 68.00 | 25.00 |
August | 60.83 | 25.87 | 475.83 | 24.58 | 51.17 | 24.74 |
September | 94.50 | 25.14 | 400.83 | 24.61 | 62.50 | 24.80 |
October | 141.00 | 23.59 | 359.00 | 24.19 | 49.33 | 24.34 |
November | 288.33 | 22.20 | 144.83 | 22.80 | 15.17 | 22.78 |
December | 396.83 | 21.61 | 133.67 | 21.83 | 65.17 | 21.71 |
Annual Sum or Average | 2408.83 | 22.48 | 3684.67 | 23.47 | 625.00 | 23.50 |
Minimum of Months | 45.67 | 21.42 | 133.67 | 21.45 | 15.17 | 21.29 |
Maximum of Months | 442.50 | 26.34 | 475.83 | 24.79 | 96.67 | 25.00 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 285.50 | 22.18 | 203.50 | 22.80 | 68.83 | 22.75 |
February | 223.33 | 22.05 | 214.17 | 22.83 | 44.83 | 22.69 |
March | 275.00 | 22.11 | 213.50 | 22.73 | 48.50 | 22.61 |
April | 157.00 | 22.86 | 271.33 | 23.79 | 15.00 | 23.86 |
May | 43.50 | 25.85 | 479.00 | 24.50 | 43.33 | 24.61 |
June | 25.00 | 25.66 | 476.00 | 24.42 | 21.17 | 24.49 |
July | 56.00 | 26.10 | 481.67 | 24.64 | 53.83 | 24.79 |
August | 49.83 | 26.05 | 495.83 | 24.54 | 48.00 | 24.67 |
September | 73.50 | 25.77 | 443.33 | 24.65 | 64.17 | 24.82 |
October | 101.50 | 24.80 | 424.33 | 24.59 | 58.33 | 24.79 |
November | 181.17 | 23.17 | 285.83 | 24.01 | 32.00 | 24.16 |
December | 253.33 | 22.34 | 241.83 | 23.19 | 58.00 | 23.19 |
Annual Sum or Average | 1724.67 | 23.03 | 4230.33 | 23.93 | 556.00 | 23.98 |
Minimum of Months | 25.00 | 22.05 | 203.50 | 22.73 | 15.00 | 22.61 |
Maximum of Months | 285.50 | 26.10 | 495.83 | 24.65 | 68.83 | 24.82 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 411.00 | 21.48 | 146.67 | 21.60 | 94.00 | 21.46 |
February | 326.67 | 21.63 | 147.67 | 21.91 | 61.83 | 21.72 |
March | 325.33 | 21.85 | 171.50 | 22.36 | 45.67 | 22.25 |
April | 171.33 | 22.94 | 273.17 | 23.85 | 22.00 | 23.98 |
May | 42.17 | 25.91 | 457.17 | 24.54 | 36.83 | 24.67 |
June | 32.00 | 26.10 | 466.00 | 24.53 | 27.00 | 24.64 |
July | 55.50 | 26.20 | 471.00 | 24.69 | 50.33 | 24.86 |
August | 43.17 | 26.13 | 485.33 | 24.56 | 39.17 | 24.69 |
September | 74.67 | 24.72 | 401.33 | 24.48 | 42.50 | 24.62 |
October | 121.33 | 23.58 | 361.33 | 24.22 | 40.00 | 24.37 |
November | 295.00 | 22.10 | 150.17 | 22.78 | 15.00 | 22.79 |
December | 358.33 | 21.63 | 150.33 | 22.03 | 59.33 | 21.93 |
Annual Sum or Average | 2256.50 | 22.34 | 3681.67 | 23.46 | 533.67 | 23.46 |
Minimum of Months | 32.00 | 21.48 | 146.67 | 21.60 | 15.00 | 21.46 |
Maximum of Months | 411.00 | 26.20 | 485.33 | 24.69 | 94.00 | 24.86 |
Report: ComfortReportSimple55Monthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 12.17 | 27.00 | 502.00 | 27.00 | 12.17 | 27.00 |
February | 45.83 | 27.00 | 454.00 | 27.00 | 45.83 | 27.00 |
March | 109.17 | 27.00 | 514.00 | 27.00 | 109.17 | 27.00 |
April | 300.67 | 27.00 | 485.00 | 27.00 | 300.67 | 27.00 |
May | 121.50 | 27.00 | 508.00 | 27.00 | 121.50 | 27.00 |
June | 220.33 | 27.00 | 496.00 | 27.00 | 220.33 | 27.00 |
July | 279.83 | 27.00 | 497.00 | 27.00 | 279.83 | 27.00 |
August | 483.50 | 27.08 | 514.00 | 27.08 | 483.50 | 27.08 |
September | 129.83 | 27.00 | 485.00 | 27.00 | 129.83 | 27.00 |
October | 170.67 | 27.00 | 502.00 | 27.00 | 170.67 | 27.00 |
November | 155.83 | 27.00 | 489.00 | 27.00 | 155.83 | 27.00 |
December | 181.17 | 27.00 | 497.00 | 27.00 | 181.17 | 27.00 |
Annual Sum or Average | 2210.50 | 27.02 | 5943.00 | 27.01 | 2210.50 | 27.01 |
Minimum of Months | 12.17 | 27.00 | 454.00 | 27.00 | 12.17 | 27.00 |
Maximum of Months | 483.50 | 27.08 | 514.00 | 27.08 | 483.50 | 27.08 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 1.50 | 27.00 | 502.00 | 27.00 | 1.50 | 27.00 |
February | 3.33 | 27.00 | 446.83 | 27.00 | 3.33 | 27.00 |
March | 1.67 | 27.00 | 514.00 | 27.00 | 1.67 | 27.00 |
April | 36.67 | 27.03 | 485.00 | 27.00 | 36.67 | 27.01 |
May | 13.50 | 27.00 | 508.00 | 27.00 | 13.50 | 27.00 |
June | 28.50 | 27.00 | 496.00 | 27.00 | 28.50 | 27.00 |
July | 50.00 | 27.00 | 497.00 | 27.00 | 50.00 | 27.00 |
August | 129.83 | 27.23 | 514.00 | 27.09 | 129.83 | 27.12 |
September | 16.67 | 27.00 | 485.00 | 27.00 | 16.67 | 27.00 |
October | 28.17 | 27.00 | 502.00 | 27.00 | 28.17 | 27.00 |
November | 12.67 | 27.00 | 489.00 | 27.00 | 12.67 | 27.00 |
December | 12.67 | 27.00 | 497.00 | 27.00 | 12.67 | 27.00 |
Annual Sum or Average | 335.17 | 27.09 | 5935.83 | 27.01 | 335.17 | 27.01 |
Minimum of Months | 1.50 | 27.00 | 446.83 | 27.00 | 1.50 | 27.00 |
Maximum of Months | 129.83 | 27.23 | 514.00 | 27.09 | 129.83 | 27.12 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 14.33 | 26.21 | 473.00 | 26.97 | 4.00 | 26.97 |
February | 16.00 | 27.00 | 433.17 | 27.00 | 8.00 | 27.00 |
March | 6.50 | 27.00 | 506.50 | 27.00 | 6.50 | 27.00 |
April | 73.00 | 27.01 | 485.00 | 27.00 | 73.00 | 27.00 |
May | 83.33 | 27.00 | 508.00 | 27.00 | 83.33 | 27.00 |
June | 122.83 | 27.00 | 496.00 | 27.00 | 122.83 | 27.00 |
July | 136.17 | 27.00 | 497.00 | 27.00 | 136.17 | 27.00 |
August | 192.67 | 27.11 | 514.00 | 27.06 | 192.67 | 27.07 |
September | 58.00 | 27.00 | 485.00 | 27.00 | 58.00 | 27.00 |
October | 74.67 | 27.00 | 502.00 | 27.00 | 74.67 | 27.00 |
November | 20.00 | 27.00 | 489.00 | 27.00 | 20.00 | 27.00 |
December | 17.50 | 27.00 | 489.83 | 27.00 | 17.50 | 27.00 |
Annual Sum or Average | 815.00 | 27.01 | 5878.50 | 27.01 | 796.67 | 27.01 |
Minimum of Months | 6.50 | 26.21 | 433.17 | 26.97 | 4.00 | 26.97 |
Maximum of Months | 192.67 | 27.11 | 514.00 | 27.06 | 192.67 | 27.07 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 497.17 | 27.00 | 502.00 | 27.00 | 497.17 | 27.00 |
February | 454.00 | 27.00 | 454.00 | 27.00 | 454.00 | 27.00 |
March | 514.00 | 27.00 | 514.00 | 27.00 | 514.00 | 27.00 |
April | 485.00 | 27.27 | 485.00 | 27.27 | 485.00 | 27.27 |
May | 508.00 | 27.00 | 508.00 | 27.00 | 508.00 | 27.00 |
June | 496.00 | 27.00 | 496.00 | 27.00 | 496.00 | 27.00 |
July | 497.00 | 27.00 | 497.00 | 27.00 | 497.00 | 27.00 |
August | 514.00 | 28.61 | 514.00 | 28.61 | 514.00 | 28.61 |
September | 485.00 | 27.00 | 485.00 | 27.00 | 485.00 | 27.00 |
October | 502.00 | 27.00 | 502.00 | 27.00 | 502.00 | 27.00 |
November | 489.00 | 27.00 | 489.00 | 27.00 | 489.00 | 27.00 |
December | 497.00 | 27.10 | 497.00 | 27.10 | 497.00 | 27.10 |
Annual Sum or Average | 5938.17 | 27.17 | 5943.00 | 27.17 | 5938.17 | 27.17 |
Minimum of Months | 454.00 | 27.00 | 454.00 | 27.00 | 454.00 | 27.00 |
Maximum of Months | 514.00 | 28.61 | 514.00 | 28.61 | 514.00 | 28.61 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 27.00022 | 32.43501 | 0.88253 | 21.61912 |
February | 454.00000 | 27.00093 | 33.71250 | 0.94326 | 23.95487 |
March | 514.00000 | 27.00053 | 34.00386 | 0.98743 | 25.69374 |
April | 485.00000 | 27.00263 | 36.71031 | 1.06263 | 28.86761 |
May | 508.00000 | 27.00042 | 42.13675 | 0.36364 | 7.82597 |
June | 496.00000 | 27.00226 | 40.66201 | 0.40010 | 8.40168 |
July | 497.00000 | 27.00135 | 39.96828 | 0.43617 | 9.02453 |
August | 514.00000 | 27.07371 | 39.33930 | 0.50711 | 10.52048 |
September | 485.00000 | 27.00021 | 42.50852 | 0.36747 | 7.88788 |
October | 502.00000 | 27.00176 | 38.53519 | 1.02537 | 27.26460 |
November | 489.00000 | 27.00062 | 35.59502 | 1.01666 | 26.89236 |
December | 497.00000 | 27.00016 | 33.60503 | 1.01562 | 26.87828 |
Annual Sum or Average | 5943.00000 | 27.00729 | 37.45545 | 0.74872 | 18.67618 |
Minimum of Months | 454.00000 | 27.00016 | 32.43501 | 0.36364 | 7.82597 |
Maximum of Months | 514.00000 | 27.07371 | 42.50852 | 1.06263 | 28.86761 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 27.00011 | 32.57139 | 0.79565 | 18.58298 |
February | 454.00000 | 27.00089 | 33.76176 | 0.83979 | 20.14437 |
March | 514.00000 | 27.00054 | 33.99162 | 0.87259 | 21.24629 |
April | 485.00000 | 27.00243 | 36.67902 | 0.95773 | 24.45697 |
May | 508.00000 | 27.00025 | 42.35895 | 0.30949 | 7.08448 |
June | 496.00000 | 27.00233 | 40.73822 | 0.32605 | 7.29276 |
July | 497.00000 | 27.00145 | 39.99702 | 0.34047 | 7.48285 |
August | 514.00000 | 27.05865 | 39.35498 | 0.37823 | 8.13068 |
September | 485.00000 | 27.00012 | 42.83663 | 0.30245 | 7.00190 |
October | 502.00000 | 27.00179 | 38.60478 | 0.95869 | 24.51914 |
November | 489.00000 | 27.00065 | 35.58377 | 0.90303 | 22.34688 |
December | 497.00000 | 27.00018 | 33.56495 | 0.86693 | 21.05644 |
Annual Sum or Average | 5943.00000 | 27.00596 | 37.52461 | 0.65231 | 15.72739 |
Minimum of Months | 454.00000 | 27.00011 | 32.57139 | 0.30245 | 7.00190 |
Maximum of Months | 514.00000 | 27.05865 | 42.83663 | 0.95869 | 24.51914 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 26.96552 | 32.69912 | 0.74345 | 17.13048 |
February | 454.00000 | 27.00098 | 33.81641 | 0.80357 | 19.08073 |
March | 514.00000 | 27.00056 | 34.02071 | 0.84773 | 20.47899 |
April | 485.00000 | 27.00204 | 36.70627 | 0.95292 | 24.33024 |
May | 508.00000 | 27.00032 | 42.29614 | 0.32680 | 7.36306 |
June | 496.00000 | 27.00233 | 40.72172 | 0.34882 | 7.66244 |
July | 497.00000 | 27.00146 | 40.00404 | 0.36360 | 7.86435 |
August | 514.00000 | 27.04020 | 39.38616 | 0.39265 | 8.39426 |
September | 485.00000 | 27.00013 | 42.80130 | 0.31313 | 7.19032 |
October | 502.00000 | 27.00180 | 38.61593 | 0.95852 | 24.58656 |
November | 489.00000 | 27.00066 | 35.61977 | 0.87566 | 21.41508 |
December | 497.00000 | 27.00020 | 33.59806 | 0.82566 | 19.71495 |
Annual Sum or Average | 5943.00000 | 27.00143 | 37.54465 | 0.64430 | 15.38833 |
Minimum of Months | 454.00000 | 26.96552 | 32.69912 | 0.31313 | 7.19032 |
Maximum of Months | 514.00000 | 27.04020 | 42.80130 | 0.95852 | 24.58656 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 27.00143 | 33.88602 | 1.12170 | 31.55234 |
February | 454.00000 | 27.00193 | 35.13565 | 1.27567 | 39.05115 |
March | 514.00000 | 27.00108 | 34.94851 | 1.41173 | 46.15011 |
April | 485.00000 | 27.27175 | 37.00523 | 1.61490 | 57.08782 |
May | 508.00000 | 27.00410 | 40.26449 | 0.59737 | 12.53679 |
June | 496.00000 | 27.00288 | 39.78297 | 0.80508 | 18.69466 |
July | 497.00000 | 27.00138 | 39.54929 | 1.01179 | 26.64264 |
August | 514.00000 | 28.61447 | 38.00431 | 1.67045 | 59.73895 |
September | 485.00000 | 27.00461 | 40.30681 | 0.65469 | 14.06467 |
October | 502.00000 | 27.00234 | 38.17454 | 1.34460 | 42.59816 |
November | 489.00000 | 27.00083 | 36.22015 | 1.46091 | 48.78674 |
December | 497.00000 | 27.09955 | 34.75432 | 1.58755 | 55.64170 |
Annual Sum or Average | 5943.00000 | 27.17185 | 37.34601 | 1.21340 | 37.73885 |
Minimum of Months | 454.00000 | 27.00083 | 33.88602 | 0.59737 | 12.53679 |
Maximum of Months | 514.00000 | 28.61447 | 40.30681 | 1.67045 | 59.73895 |
Report: OccupantComfortDataSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.55024 | 37.92842 | 0.50091 | 11.11678 |
February | 454.00000 | 24.52497 | 46.17256 | 0.55109 | 12.15709 |
March | 514.00000 | 24.42798 | 45.06631 | 0.52518 | 11.55258 |
April | 485.00000 | 24.52153 | 56.60052 | 0.62765 | 14.00629 |
May | 508.00000 | 24.51994 | 64.45626 | -0.1587 | 6.79212 |
June | 496.00000 | 24.46700 | 63.95125 | -0.1761 | 6.68905 |
July | 497.00000 | 24.62574 | 63.51905 | -0.1253 | 6.92968 |
August | 514.00000 | 24.50439 | 61.76705 | -0.1554 | 6.81579 |
September | 485.00000 | 24.58126 | 62.30742 | -0.1343 | 6.91850 |
October | 502.00000 | 24.63250 | 56.72048 | 0.67419 | 15.64594 |
November | 489.00000 | 24.63462 | 47.49223 | 0.60627 | 13.60242 |
December | 497.00000 | 24.61998 | 42.51687 | 0.56146 | 12.60499 |
Annual Sum or Average | 5943.00000 | 24.55046 | 54.08816 | 0.27170 | 10.37734 |
Minimum of Months | 454.00000 | 24.42798 | 37.92842 | -0.1761 | 6.68905 |
Maximum of Months | 514.00000 | 24.63462 | 64.45626 | 0.67419 | 15.64594 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.11152 | 37.51993 | 0.40022 | 8.84375 |
February | 454.00000 | 24.19831 | 41.13166 | 0.45325 | 9.73726 |
March | 514.00000 | 24.21597 | 40.39515 | 0.46264 | 9.83803 |
April | 485.00000 | 24.21904 | 45.72832 | 0.51342 | 10.71197 |
May | 508.00000 | 24.20688 | 48.61461 | -0.3367 | 7.69224 |
June | 496.00000 | 24.14159 | 48.54337 | -0.3504 | 7.73978 |
July | 497.00000 | 24.12623 | 48.47333 | -0.3497 | 7.67573 |
August | 514.00000 | 24.11471 | 48.38058 | -0.3388 | 7.46954 |
September | 485.00000 | 24.20921 | 48.60776 | -0.3330 | 7.64595 |
October | 502.00000 | 24.26876 | 46.13107 | 0.52774 | 11.07117 |
November | 489.00000 | 24.31750 | 42.85846 | 0.51380 | 10.85521 |
December | 497.00000 | 24.29366 | 39.54152 | 0.47916 | 10.20634 |
Annual Sum or Average | 5943.00000 | 24.20156 | 44.67865 | 0.13353 | 9.11322 |
Minimum of Months | 454.00000 | 24.11152 | 37.51993 | -0.3504 | 7.46954 |
Maximum of Months | 514.00000 | 24.31750 | 48.61461 | 0.52774 | 11.07117 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.44683 | 39.74742 | 0.22048 | 6.75495 |
February | 454.00000 | 23.58741 | 43.35201 | 0.28439 | 7.48465 |
March | 514.00000 | 23.70970 | 42.62983 | 0.31781 | 7.73118 |
April | 485.00000 | 23.98611 | 47.41502 | 0.42900 | 9.16322 |
May | 508.00000 | 24.04871 | 49.41247 | -0.4084 | 8.87946 |
June | 496.00000 | 24.01933 | 49.37366 | -0.4164 | 8.99351 |
July | 497.00000 | 24.00585 | 49.47654 | -0.4228 | 9.15689 |
August | 514.00000 | 24.05230 | 49.43438 | -0.4039 | 8.77717 |
September | 485.00000 | 23.97562 | 49.72772 | -0.4327 | 9.34089 |
October | 502.00000 | 24.04616 | 47.33601 | 0.45510 | 9.62712 |
November | 489.00000 | 23.86881 | 44.93282 | 0.37963 | 8.40402 |
December | 497.00000 | 23.62109 | 42.19806 | 0.28815 | 7.48591 |
Annual Sum or Average | 5943.00000 | 23.86573 | 46.26590 | 0.02136 | 8.48632 |
Minimum of Months | 454.00000 | 23.44683 | 39.74742 | -0.4327 | 6.75495 |
Maximum of Months | 514.00000 | 24.05230 | 49.72772 | 0.45510 | 9.62712 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.51527 | 41.85697 | -0.0088 | 7.01831 |
February | 454.00000 | 22.84110 | 44.93934 | 0.10359 | 8.03180 |
March | 514.00000 | 23.25009 | 43.80984 | 0.20537 | 7.56255 |
April | 485.00000 | 23.86681 | 47.83841 | 0.40457 | 8.90724 |
May | 508.00000 | 24.10981 | 49.00429 | -0.3711 | 8.25300 |
June | 496.00000 | 24.10964 | 48.80594 | -0.3665 | 8.11853 |
July | 497.00000 | 24.12319 | 48.87476 | -0.3656 | 8.13638 |
August | 514.00000 | 24.12564 | 48.99511 | -0.3624 | 8.10922 |
September | 485.00000 | 24.01973 | 49.49895 | -0.4067 | 8.82694 |
October | 502.00000 | 23.96857 | 47.48850 | 0.44209 | 9.69249 |
November | 489.00000 | 23.40857 | 46.40189 | 0.26666 | 7.47146 |
December | 497.00000 | 22.85996 | 44.12601 | 0.09975 | 7.14116 |
Annual Sum or Average | 5943.00000 | 23.60498 | 46.80769 | -0.0318 | 8.10322 |
Minimum of Months | 454.00000 | 22.51527 | 41.85697 | -0.4067 | 7.01831 |
Maximum of Months | 514.00000 | 24.12564 | 49.49895 | 0.44209 | 9.69249 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.87679 | 39.82600 | 0.07852 | 7.13690 |
February | 454.00000 | 23.29250 | 42.19719 | 0.20775 | 7.80954 |
March | 514.00000 | 23.60513 | 41.22987 | 0.28773 | 8.11663 |
April | 485.00000 | 24.07340 | 45.66402 | 0.46655 | 9.85701 |
May | 508.00000 | 24.38643 | 48.60153 | -0.2351 | 6.92240 |
June | 496.00000 | 24.33499 | 47.63228 | -0.2324 | 6.71865 |
July | 497.00000 | 24.41045 | 47.78639 | -0.2045 | 6.72620 |
August | 514.00000 | 24.27792 | 47.88885 | -0.2432 | 6.82283 |
September | 485.00000 | 24.37083 | 49.12920 | -0.2544 | 7.18968 |
October | 502.00000 | 24.25181 | 46.77290 | 0.53055 | 11.55193 |
November | 489.00000 | 23.84288 | 43.64199 | 0.36996 | 8.56103 |
December | 497.00000 | 23.46369 | 41.26742 | 0.24517 | 7.66960 |
Annual Sum or Average | 5943.00000 | 23.93602 | 45.15022 | 0.08284 | 7.91922 |
Minimum of Months | 454.00000 | 22.87679 | 39.82600 | -0.2544 | 6.71865 |
Maximum of Months | 514.00000 | 24.41045 | 49.12920 | 0.53055 | 11.55193 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.02156 | 38.97370 | 0.14210 | 7.72781 |
February | 454.00000 | 23.27932 | 41.81215 | 0.23967 | 8.19469 |
March | 514.00000 | 23.45831 | 40.95786 | 0.29533 | 8.95934 |
April | 485.00000 | 23.88298 | 45.72367 | 0.46609 | 10.35964 |
May | 508.00000 | 24.37921 | 48.03925 | -0.1771 | 7.21039 |
June | 496.00000 | 24.26962 | 47.44251 | -0.2032 | 6.85155 |
July | 497.00000 | 24.31751 | 47.64810 | -0.1890 | 7.12370 |
August | 514.00000 | 24.13065 | 48.00999 | -0.2563 | 7.36553 |
September | 485.00000 | 24.31522 | 48.65234 | -0.2260 | 7.84595 |
October | 502.00000 | 24.16194 | 46.41683 | 0.54426 | 12.31282 |
November | 489.00000 | 23.74155 | 43.46967 | 0.38016 | 9.19523 |
December | 497.00000 | 23.16692 | 41.48279 | 0.20218 | 7.80661 |
Annual Sum or Average | 5943.00000 | 23.84714 | 44.90001 | 0.09954 | 8.40982 |
Minimum of Months | 454.00000 | 23.02156 | 38.97370 | -0.2563 | 6.85155 |
Maximum of Months | 514.00000 | 24.37921 | 48.65234 | 0.54426 | 12.31282 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.73083 | 37.18878 | 0.34294 | 10.33054 |
February | 454.00000 | 23.86271 | 40.24400 | 0.40337 | 10.75714 |
March | 514.00000 | 23.74797 | 40.35087 | 0.35857 | 9.72707 |
April | 485.00000 | 24.11740 | 45.34381 | 0.49873 | 10.75165 |
May | 508.00000 | 24.37527 | 48.59932 | -0.2354 | 6.95162 |
June | 496.00000 | 24.30413 | 47.75967 | -0.2512 | 6.87208 |
July | 497.00000 | 24.39066 | 47.83142 | -0.2131 | 6.80873 |
August | 514.00000 | 24.29675 | 47.70395 | -0.2152 | 6.74043 |
September | 485.00000 | 24.45433 | 48.52378 | -0.1824 | 7.23642 |
October | 502.00000 | 24.46469 | 45.53945 | 0.64725 | 15.04484 |
November | 489.00000 | 24.32491 | 41.75713 | 0.56337 | 13.11262 |
December | 497.00000 | 24.00690 | 39.29925 | 0.44914 | 11.81301 |
Annual Sum or Average | 5943.00000 | 24.17399 | 44.20103 | 0.17767 | 9.66141 |
Minimum of Months | 454.00000 | 23.73083 | 37.18878 | -0.2512 | 6.74043 |
Maximum of Months | 514.00000 | 24.46469 | 48.59932 | 0.64725 | 15.04484 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.32081 | 37.82132 | 0.24651 | 8.63057 |
February | 454.00000 | 23.89010 | 39.90348 | 0.42745 | 10.81759 |
March | 514.00000 | 24.16422 | 38.94036 | 0.51159 | 11.94969 |
April | 485.00000 | 24.51288 | 43.69059 | 0.69675 | 16.01953 |
May | 508.00000 | 24.46021 | 47.59768 | -0.1114 | 6.58241 |
June | 496.00000 | 24.44971 | 46.69849 | -0.0695 | 6.41482 |
July | 497.00000 | 24.56189 | 46.56905 | -0.0161 | 6.60218 |
August | 514.00000 | 24.45751 | 46.53051 | -0.0002 | 6.28017 |
September | 485.00000 | 24.46720 | 47.83706 | -0.1183 | 6.89619 |
October | 502.00000 | 24.49426 | 45.07929 | 0.67795 | 15.67670 |
November | 489.00000 | 24.38260 | 41.39236 | 0.59038 | 13.28638 |
December | 497.00000 | 24.29786 | 38.27548 | 0.53752 | 12.60691 |
Annual Sum or Average | 5943.00000 | 24.28999 | 43.37976 | 0.27903 | 10.12406 |
Minimum of Months | 454.00000 | 23.32081 | 37.82132 | -0.1183 | 6.28017 |
Maximum of Months | 514.00000 | 24.56189 | 47.83706 | 0.69675 | 16.01953 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.78260 | 43.12095 | -0.2025 | 8.33264 |
February | 454.00000 | 22.21160 | 45.37339 | -0.0653 | 8.50545 |
March | 514.00000 | 22.66991 | 44.24319 | 0.04955 | 7.59366 |
April | 485.00000 | 23.68026 | 48.55275 | 0.35506 | 8.63906 |
May | 508.00000 | 24.34938 | 50.72156 | -0.2561 | 7.13165 |
June | 496.00000 | 24.34993 | 49.33461 | -0.2441 | 6.95634 |
July | 497.00000 | 24.45393 | 50.46927 | -0.2066 | 7.07861 |
August | 514.00000 | 24.33120 | 50.80626 | -0.2535 | 7.16418 |
September | 485.00000 | 24.27205 | 52.12031 | -0.2960 | 7.66775 |
October | 502.00000 | 24.00970 | 49.98064 | 0.46860 | 10.85965 |
November | 489.00000 | 22.94964 | 46.95338 | 0.14428 | 7.20194 |
December | 497.00000 | 22.20128 | 45.48259 | -0.0716 | 7.76417 |
Annual Sum or Average | 5943.00000 | 23.44680 | 48.10755 | -0.0490 | 7.90210 |
Minimum of Months | 454.00000 | 21.78260 | 43.12095 | -0.2960 | 6.95634 |
Maximum of Months | 514.00000 | 24.45393 | 52.12031 | 0.46860 | 10.85965 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 427.00000 | 22.07031 | 41.76585 | -0.1048 | 7.82687 |
February | 385.00000 | 22.44649 | 43.76789 | 0.01990 | 8.00718 |
March | 433.00000 | 22.89679 | 42.53357 | 0.13750 | 8.58504 |
April | 410.00000 | 23.79211 | 47.42837 | 0.42319 | 10.32048 |
May | 430.00000 | 24.45066 | 49.67343 | -0.1682 | 7.75273 |
June | 418.00000 | 24.41200 | 48.58812 | -0.1776 | 7.22954 |
July | 422.00000 | 24.55118 | 49.50771 | -0.1293 | 7.70918 |
August | 433.00000 | 24.37095 | 50.05119 | -0.1990 | 7.57142 |
September | 410.00000 | 24.30419 | 51.06965 | -0.2432 | 8.83728 |
October | 427.00000 | 24.06077 | 49.01328 | 0.51335 | 12.57534 |
November | 417.00000 | 23.16520 | 45.37045 | 0.22569 | 8.02788 |
December | 422.00000 | 22.33686 | 44.32418 | -0.0171 | 7.84429 |
Annual Sum or Average | 5034.00000 | 23.57786 | 46.93537 | 0.02285 | 8.52438 |
Minimum of Months | 385.00000 | 22.07031 | 41.76585 | -0.2432 | 7.22954 |
Maximum of Months | 433.00000 | 24.55118 | 51.06965 | 0.51335 | 12.57534 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.45429 | 38.47578 | 0.27014 | 10.19010 |
February | 454.00000 | 23.54885 | 41.42235 | 0.31890 | 10.46315 |
March | 514.00000 | 23.35498 | 41.98140 | 0.25049 | 9.19021 |
April | 485.00000 | 23.92604 | 47.47514 | 0.43721 | 10.07766 |
May | 508.00000 | 24.34849 | 50.67420 | -0.2514 | 7.16539 |
June | 496.00000 | 24.32005 | 49.51498 | -0.2626 | 7.11411 |
July | 497.00000 | 24.43599 | 50.53887 | -0.2142 | 7.13889 |
August | 514.00000 | 24.36784 | 50.44781 | -0.2171 | 7.03254 |
September | 485.00000 | 24.42090 | 50.97264 | -0.1974 | 7.55200 |
October | 502.00000 | 24.41708 | 47.62392 | 0.63619 | 15.12638 |
November | 489.00000 | 24.12068 | 42.94536 | 0.50414 | 12.43694 |
December | 497.00000 | 23.64838 | 41.14373 | 0.35126 | 11.38943 |
Annual Sum or Average | 5943.00000 | 24.03249 | 46.13024 | 0.13292 | 9.55862 |
Minimum of Months | 454.00000 | 23.35498 | 38.47578 | -0.2626 | 7.03254 |
Maximum of Months | 514.00000 | 24.43599 | 50.97264 | 0.63619 | 15.12638 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.27178 | 41.01995 | -0.0425 | 8.03411 |
February | 454.00000 | 22.64646 | 43.39321 | 0.08778 | 8.85272 |
March | 514.00000 | 22.92881 | 42.66740 | 0.16123 | 8.51064 |
April | 485.00000 | 23.90320 | 47.02848 | 0.47139 | 11.22347 |
May | 508.00000 | 24.33664 | 49.86303 | -0.1955 | 7.19048 |
June | 496.00000 | 24.37195 | 48.59450 | -0.1691 | 7.00562 |
July | 497.00000 | 24.47230 | 49.45083 | -0.1392 | 7.12862 |
August | 514.00000 | 24.37742 | 49.63633 | -0.1623 | 6.86765 |
September | 485.00000 | 24.27370 | 50.77634 | -0.2273 | 7.91157 |
October | 502.00000 | 24.11264 | 48.44487 | 0.54668 | 12.86144 |
November | 489.00000 | 23.19770 | 45.31576 | 0.25332 | 8.39051 |
December | 497.00000 | 22.61889 | 43.44407 | 0.07430 | 8.27999 |
Annual Sum or Average | 5943.00000 | 23.63237 | 46.65199 | 0.05370 | 8.51123 |
Minimum of Months | 454.00000 | 22.27178 | 41.01995 | -0.2273 | 6.86765 |
Maximum of Months | 514.00000 | 24.47230 | 50.77634 | 0.54668 | 12.86144 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.41189 | 44.27075 | -0.3174 | 10.48391 |
February | 454.00000 | 21.84852 | 46.43568 | -0.1670 | 10.17423 |
March | 514.00000 | 22.37951 | 44.98866 | -0.0288 | 8.64830 |
April | 485.00000 | 23.52212 | 49.10093 | 0.32246 | 8.71006 |
May | 508.00000 | 24.36409 | 50.89896 | -0.2328 | 7.12707 |
June | 496.00000 | 24.37071 | 49.35239 | -0.2157 | 6.92294 |
July | 497.00000 | 24.48926 | 50.50332 | -0.1738 | 7.16630 |
August | 514.00000 | 24.34785 | 51.02510 | -0.2284 | 7.18535 |
September | 485.00000 | 24.27405 | 52.52450 | -0.2812 | 7.87051 |
October | 502.00000 | 23.91106 | 50.54691 | 0.45267 | 11.22443 |
November | 489.00000 | 22.56626 | 48.05634 | 0.04811 | 7.72301 |
December | 497.00000 | 21.84304 | 46.75606 | -0.1772 | 9.20455 |
Annual Sum or Average | 5943.00000 | 23.28744 | 48.71152 | -0.0835 | 8.52498 |
Minimum of Months | 454.00000 | 21.41189 | 44.27075 | -0.3174 | 6.92294 |
Maximum of Months | 514.00000 | 24.48926 | 52.52450 | 0.45267 | 11.22443 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.73288 | 42.72589 | -0.1993 | 9.00056 |
February | 454.00000 | 22.20493 | 44.80062 | -0.0408 | 9.28551 |
March | 514.00000 | 22.78197 | 43.16580 | 0.10959 | 9.28969 |
April | 485.00000 | 23.72305 | 47.61192 | 0.42427 | 10.53961 |
May | 508.00000 | 24.39377 | 49.67046 | -0.1463 | 7.49844 |
June | 496.00000 | 24.37018 | 48.53769 | -0.1442 | 6.98613 |
July | 497.00000 | 24.49073 | 49.39524 | -0.1036 | 7.51016 |
August | 514.00000 | 24.32808 | 50.03910 | -0.1703 | 7.31580 |
September | 485.00000 | 24.26119 | 51.16276 | -0.2251 | 8.62996 |
October | 502.00000 | 23.96920 | 49.14435 | 0.51052 | 12.86168 |
November | 489.00000 | 22.96307 | 46.26970 | 0.17810 | 8.06041 |
December | 497.00000 | 22.09108 | 45.33691 | -0.0886 | 8.67112 |
Annual Sum or Average | 5943.00000 | 23.45114 | 47.33071 | 0.00820 | 8.79705 |
Minimum of Months | 454.00000 | 21.73288 | 42.72589 | -0.2251 | 6.98613 |
Maximum of Months | 514.00000 | 24.49073 | 51.16276 | 0.51052 | 12.86168 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.04576 | 39.70591 | 0.15155 | 10.40877 |
February | 454.00000 | 23.13889 | 42.49179 | 0.21049 | 10.81035 |
March | 514.00000 | 23.03158 | 42.81064 | 0.16703 | 9.68947 |
April | 485.00000 | 23.73478 | 48.08856 | 0.39875 | 9.98049 |
May | 508.00000 | 24.33677 | 50.84825 | -0.2359 | 7.23066 |
June | 496.00000 | 24.32086 | 49.52722 | -0.2402 | 7.10395 |
July | 497.00000 | 24.44705 | 50.55812 | -0.1889 | 7.22153 |
August | 514.00000 | 24.36165 | 50.65818 | -0.1989 | 7.10387 |
September | 485.00000 | 24.38302 | 51.37697 | -0.1939 | 7.85957 |
October | 502.00000 | 24.31610 | 48.13477 | 0.61997 | 15.18022 |
November | 489.00000 | 23.84705 | 43.77600 | 0.43132 | 11.83608 |
December | 497.00000 | 23.28117 | 42.35518 | 0.24723 | 11.34946 |
Annual Sum or Average | 5943.00000 | 23.85770 | 46.71914 | 0.09537 | 9.63354 |
Minimum of Months | 454.00000 | 23.03158 | 39.70591 | -0.2402 | 7.10387 |
Maximum of Months | 514.00000 | 24.44705 | 51.37697 | 0.61997 | 15.18022 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.93803 | 41.99923 | -0.1420 | 9.12690 |
February | 454.00000 | 22.30337 | 44.35542 | -0.0035 | 9.74219 |
March | 514.00000 | 22.64555 | 43.39673 | 0.08875 | 9.11080 |
April | 485.00000 | 23.70665 | 47.62799 | 0.43259 | 11.07734 |
May | 508.00000 | 24.30710 | 50.08946 | -0.1859 | 7.39847 |
June | 496.00000 | 24.34935 | 48.68964 | -0.1545 | 7.16425 |
July | 497.00000 | 24.45553 | 49.55312 | -0.1235 | 7.32330 |
August | 514.00000 | 24.35786 | 49.88711 | -0.1492 | 7.06033 |
September | 485.00000 | 24.21357 | 51.22946 | -0.2309 | 8.38204 |
October | 502.00000 | 23.98628 | 49.00267 | 0.52567 | 12.94372 |
November | 489.00000 | 22.86607 | 46.23963 | 0.17165 | 8.40996 |
December | 497.00000 | 22.30386 | 44.51994 | -0.0157 | 8.92377 |
Annual Sum or Average | 5943.00000 | 23.46071 | 47.22784 | 0.01707 | 8.87621 |
Minimum of Months | 454.00000 | 21.93803 | 41.99923 | -0.2309 | 7.06033 |
Maximum of Months | 514.00000 | 24.45553 | 51.22946 | 0.52567 | 12.94372 |
Report: ChillerReportMonthly
For: COOLSYS1 CHILLER1
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportCHILLER ELECTRICITY ENERGY [J] | CHILLER ELECTRICITY RATE {Maximum} [W] | CHILLER ELECTRICITY RATE {TIMESTAMP} | CHILLER ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | CHILLER EVAPORATOR COOLING ENERGY [J] | CHILLER EVAPORATOR COOLING RATE [] | CHILLER CONDENSER HEAT TRANSFER ENERGY [J] | CHILLER COP [W/W] | CHILLER COP {Maximum} [W/W] | CHILLER COP {TIMESTAMP} | CHILLER PART LOAD RATIO [] | CHILLER PART LOAD RATIO [] | |
January | 0.785093E+11 | 230179.90 | 31-JAN-16:00 | 283.34 | 0.501465E+12 | 0.00 | 0.579974E+12 | 2.11 | 7.57 | 19-JAN-06:04 | 0.00 | 0.00 |
February | 0.106438E+12 | 225130.17 | 24-FEB-13:10 | 329.65 | 0.701134E+12 | 0.00 | 0.807572E+12 | 2.89 | 7.56 | 27-FEB-06:04 | 0.00 | 0.00 |
March | 0.126305E+12 | 228843.55 | 06-MAR-13:30 | 397.64 | 0.829713E+12 | 0.00 | 0.956017E+12 | 3.12 | 7.57 | 27-MAR-05:04 | 0.00 | 0.00 |
April | 0.191362E+12 | 237872.93 | 28-APR-16:10 | 515.82 | 0.131298E+13 | 0.00 | 0.150434E+13 | 4.44 | 7.57 | 18-APR-14:20 | 0.00 | 0.00 |
May | 0.256782E+12 | 238381.64 | 01-MAY-16:30 | 525.24 | 0.175140E+13 | 0.00 | 0.200818E+13 | 4.64 | 7.54 | 11-MAY-04:13 | 0.00 | 0.00 |
June | 0.260241E+12 | 242600.32 | 23-JUN-08:40 | 581.91 | 0.174426E+13 | 0.00 | 0.200451E+13 | 5.09 | 7.54 | 08-JUN-04:13 | 0.00 | 0.00 |
July | 0.270976E+12 | 250826.26 | 22-JUL-15:40 | 640.86 | 0.177348E+13 | 0.00 | 0.204446E+13 | 5.21 | 7.35 | 14-JUL-05:04 | 0.00 | 0.00 |
August | 0.274010E+12 | 246065.86 | 17-AUG-17:10 | 671.96 | 0.181484E+13 | 0.00 | 0.208885E+13 | 5.45 | 7.44 | 17-AUG-04:13 | 0.00 | 0.00 |
September | 0.253951E+12 | 250833.73 | 09-SEP-16:00 | 528.14 | 0.171512E+13 | 0.00 | 0.196907E+13 | 4.73 | 7.53 | 22-SEP-05:05 | 0.00 | 0.00 |
October | 0.222078E+12 | 241344.72 | 23-OCT-16:50 | 534.58 | 0.148921E+13 | 0.00 | 0.171129E+13 | 4.48 | 7.56 | 26-OCT-15:00 | 0.00 | 0.00 |
November | 0.146478E+12 | 239307.22 | 01-NOV-14:10 | 439.70 | 0.958418E+12 | 0.00 | 0.110490E+13 | 3.61 | 7.55 | 08-NOV-05:13 | 0.00 | 0.00 |
December | 0.106806E+12 | 235284.75 | 12-DEC-13:10 | 355.08 | 0.698724E+12 | 0.00 | 0.805529E+12 | 2.72 | 7.53 | 16-DEC-06:04 | 0.00 | 0.00 |
Annual Sum or Average | 0.229394E+13 | 5803.92 | 0.152907E+14 | 0.00 | 0.175847E+14 | 4.05 | 0.00 | 0.00 | ||||
Minimum of Months | 0.785093E+11 | 225130.17 | 283.34 | 0.501465E+12 | 0.00 | 0.579974E+12 | 2.11 | 7.35 | 0.00 | 0.00 | ||
Maximum of Months | 0.274010E+12 | 250833.73 | 671.96 | 0.181484E+13 | 0.00 | 0.208885E+13 | 5.45 | 7.57 | 0.00 | 0.00 |
Report: ChillerReportMonthly
For: COOLSYS1 CHILLER2
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportCHILLER ELECTRICITY ENERGY [J] | CHILLER ELECTRICITY RATE {Maximum} [W] | CHILLER ELECTRICITY RATE {TIMESTAMP} | CHILLER ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | CHILLER EVAPORATOR COOLING ENERGY [J] | CHILLER EVAPORATOR COOLING RATE [] | CHILLER CONDENSER HEAT TRANSFER ENERGY [J] | CHILLER COP [W/W] | CHILLER COP {Maximum} [W/W] | CHILLER COP {TIMESTAMP} | CHILLER PART LOAD RATIO [] | CHILLER PART LOAD RATIO [] | |
January | 0.261881E+10 | 133599.56 | 19-JAN-12:00 | 5.83 | 0.184382E+11 | 0.00 | 0.210570E+11 | 0.06 | 7.17 | 18-JAN-15:40 | 0.00 | 0.00 |
February | 0.562013E+10 | 133997.46 | 24-FEB-13:30 | 13.33 | 0.396183E+11 | 0.00 | 0.452385E+11 | 0.14 | 7.22 | 28-FEB-11:20 | 0.00 | 0.00 |
March | 0.926285E+10 | 134374.07 | 07-MAR-09:00 | 21.17 | 0.645002E+11 | 0.00 | 0.737630E+11 | 0.20 | 7.20 | 31-MAR-15:30 | 0.00 | 0.00 |
April | 0.134991E+11 | 150694.58 | 28-APR-07:15 | 30.58 | 0.934438E+11 | 0.00 | 0.106943E+12 | 0.29 | 7.17 | 21-APR-15:30 | 0.00 | 0.00 |
May | 0.592415E+11 | 166571.48 | 18-MAY-04:14 | 129.80 | 0.402197E+12 | 0.00 | 0.461439E+12 | 1.18 | 7.33 | 12-MAY-05:06 | 0.00 | 0.00 |
June | 0.690899E+11 | 150625.53 | 29-JUN-12:10 | 148.82 | 0.462687E+12 | 0.00 | 0.531777E+12 | 1.38 | 7.16 | 12-JUN-10:50 | 0.00 | 0.00 |
July | 0.782451E+11 | 156390.12 | 31-JUL-10:50 | 164.25 | 0.518335E+12 | 0.00 | 0.596581E+12 | 1.46 | 7.07 | 14-JUL-08:00 | 0.00 | 0.00 |
August | 0.869110E+11 | 199432.20 | 16-AUG-05:03 | 184.73 | 0.579172E+12 | 0.00 | 0.666083E+12 | 1.65 | 7.35 | 16-AUG-05:02 | 0.00 | 0.00 |
September | 0.659969E+11 | 226719.88 | 05-SEP-04:14 | 143.25 | 0.445403E+12 | 0.00 | 0.511400E+12 | 1.34 | 7.16 | 13-SEP-04:15 | 0.00 | 0.00 |
October | 0.539681E+11 | 163408.88 | 12-OCT-05:03 | 115.67 | 0.363969E+12 | 0.00 | 0.417937E+12 | 1.05 | 7.37 | 12-OCT-05:03 | 0.00 | 0.00 |
November | 0.175098E+11 | 151696.57 | 02-NOV-07:25 | 38.25 | 0.119281E+12 | 0.00 | 0.136791E+12 | 0.36 | 7.15 | 06-NOV-10:20 | 0.00 | 0.00 |
December | 0.984794E+10 | 139481.14 | 11-DEC-15:00 | 21.67 | 0.680023E+11 | 0.00 | 0.778503E+11 | 0.20 | 7.16 | 11-DEC-17:00 | 0.00 | 0.00 |
Annual Sum or Average | 0.471811E+12 | 1017.35 | 0.317505E+13 | 0.00 | 0.364686E+13 | 0.78 | 0.00 | 0.00 | ||||
Minimum of Months | 0.261881E+10 | 133599.56 | 5.83 | 0.184382E+11 | 0.00 | 0.210570E+11 | 0.06 | 7.07 | 0.00 | 0.00 | ||
Maximum of Months | 0.869110E+11 | 226719.88 | 184.73 | 0.579172E+12 | 0.00 | 0.666083E+12 | 1.65 | 7.37 | 0.00 | 0.00 |
Report: TowerReportMonthly
For: CENTRAL TOWER
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportCOOLING TOWER FAN ELECTRICITY ENERGY [J] | COOLING TOWER FAN ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | COOLING TOWER FAN ELECTRICITY RATE {Maximum} [W] | COOLING TOWER FAN ELECTRICITY RATE {TIMESTAMP} | COOLING TOWER HEAT TRANSFER RATE {Maximum} [W] | COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} | COOLING TOWER INLET TEMPERATURE [C] | COOLING TOWER OUTLET TEMPERATURE [C] | COOLING TOWER MASS FLOW RATE [kg/s] | |
January | 0.673544E+11 | 744.00 | 49248.27 | 01-JAN-00:05 | 271713.48 | 04-JAN-10:15 | 23.25 | 19.59 | 14.30 |
February | 0.921875E+11 | 672.00 | 49248.27 | 01-FEB-00:10 | 384367.83 | 24-FEB-14:20 | 27.38 | 20.80 | 14.32 |
March | 0.117117E+12 | 744.00 | 49248.27 | 01-MAR-00:10 | 625373.59 | 31-MAR-24:00 | 32.11 | 22.61 | 14.32 |
April | 0.127380E+12 | 720.00 | 49248.27 | 01-APR-00:10 | 711321.90 | 28-APR-17:20 | 39.68 | 27.04 | 14.32 |
May | 0.131907E+12 | 744.00 | 49248.27 | 01-MAY-00:03 | 344300.54 | 31-MAY-23:40 | 33.17 | 28.86 | 14.32 |
June | 0.127652E+12 | 720.00 | 49248.27 | 01-JUN-00:10 | 497695.50 | 30-JUN-23:43 | 38.34 | 30.97 | 14.32 |
July | 0.131907E+12 | 744.00 | 49248.27 | 01-JUL-00:05 | 649673.43 | 31-JUL-23:43 | 43.10 | 32.71 | 14.32 |
August | 0.131907E+12 | 744.00 | 49248.27 | 01-AUG-00:05 | 714272.58 | 07-AUG-13:30 | 46.77 | 33.55 | 14.32 |
September | 0.127652E+12 | 720.00 | 49248.27 | 01-SEP-00:03 | 342521.26 | 30-SEP-23:40 | 32.53 | 28.19 | 14.32 |
October | 0.129961E+12 | 744.00 | 49248.27 | 01-OCT-00:10 | 484263.52 | 31-OCT-24:00 | 34.77 | 27.60 | 14.32 |
November | 0.120862E+12 | 720.00 | 49248.27 | 01-NOV-00:10 | 557193.20 | 01-NOV-14:20 | 33.51 | 23.84 | 14.32 |
December | 0.117534E+12 | 744.00 | 49248.27 | 01-DEC-00:10 | 693493.62 | 13-DEC-17:10 | 34.96 | 22.70 | 14.32 |
Annual Sum or Average | 0.142342E+13 | 8760.00 | 35.02 | 26.57 | 14.32 | ||||
Minimum of Months | 0.673544E+11 | 672.00 | 49248.27 | 271713.48 | 23.25 | 19.59 | 14.30 | ||
Maximum of Months | 0.131907E+12 | 744.00 | 49248.27 | 714272.58 | 46.77 | 33.55 | 14.32 |
Report: TowerReportMonthly
For: TOWERWATERSYS COOLTOWER 1
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportCOOLING TOWER FAN ELECTRICITY ENERGY [J] | COOLING TOWER FAN ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | COOLING TOWER FAN ELECTRICITY RATE {Maximum} [W] | COOLING TOWER FAN ELECTRICITY RATE {TIMESTAMP} | COOLING TOWER HEAT TRANSFER RATE {Maximum} [W] | COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} | COOLING TOWER INLET TEMPERATURE [C] | COOLING TOWER OUTLET TEMPERATURE [C] | COOLING TOWER MASS FLOW RATE [kg/s] | |
January | 0.611637E+10 | 201.65 | 23374.45 | 02-JAN-10:20 | 1950462.59 | 20-JAN-05:12 | 22.07 | 21.40 | 25.85 |
February | 0.804840E+10 | 268.16 | 23374.45 | 01-FEB-12:30 | 1724015.34 | 01-FEB-16:40 | 22.62 | 21.60 | 34.75 |
March | 0.111049E+11 | 325.60 | 23374.45 | 06-MAR-08:30 | 1690581.83 | 31-MAR-10:40 | 22.69 | 21.60 | 37.25 |
April | 0.220857E+11 | 463.86 | 23374.45 | 01-APR-04:12 | 1745976.14 | 19-APR-16:00 | 23.72 | 21.96 | 52.23 |
May | 0.439887E+11 | 525.24 | 23374.45 | 01-MAY-01:05 | 1477834.12 | 12-MAY-04:15 | 27.11 | 24.88 | 46.25 |
June | 0.479875E+11 | 581.91 | 23374.45 | 01-JUN-04:12 | 1524799.27 | 01-JUN-04:15 | 27.16 | 24.85 | 54.51 |
July | 0.539272E+11 | 640.86 | 23374.45 | 01-JUL-00:32 | 1248269.01 | 14-JUL-14:40 | 28.07 | 25.77 | 56.25 |
August | 0.557774E+11 | 671.11 | 23374.45 | 01-AUG-00:32 | 1460980.28 | 16-AUG-17:30 | 27.47 | 25.12 | 61.31 |
September | 0.444249E+11 | 528.14 | 23374.45 | 01-SEP-00:03 | 1540848.05 | 29-SEP-04:11 | 27.87 | 25.59 | 46.38 |
October | 0.347117E+11 | 515.48 | 23374.45 | 02-OCT-08:50 | 1766832.62 | 02-OCT-09:50 | 25.70 | 23.77 | 50.55 |
November | 0.145491E+11 | 382.76 | 23374.45 | 01-NOV-03:02 | 1694607.18 | 06-NOV-09:10 | 23.28 | 21.99 | 44.55 |
December | 0.110025E+11 | 275.89 | 23374.45 | 08-DEC-10:50 | 1696547.61 | 08-DEC-15:40 | 22.50 | 21.59 | 32.71 |
Annual Sum or Average | 0.353724E+12 | 5380.65 | 25.04 | 23.35 | 45.26 | ||||
Minimum of Months | 0.611637E+10 | 201.65 | 23374.45 | 1248269.01 | 22.07 | 21.40 | 25.85 | ||
Maximum of Months | 0.557774E+11 | 671.11 | 23374.45 | 1950462.59 | 28.07 | 25.77 | 61.31 |
Report: TowerReportMonthly
For: TOWERWATERSYS COOLTOWER 2
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportCOOLING TOWER FAN ELECTRICITY ENERGY [J] | COOLING TOWER FAN ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | COOLING TOWER FAN ELECTRICITY RATE {Maximum} [W] | COOLING TOWER FAN ELECTRICITY RATE {TIMESTAMP} | COOLING TOWER HEAT TRANSFER RATE {Maximum} [W] | COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} | COOLING TOWER INLET TEMPERATURE [C] | COOLING TOWER OUTLET TEMPERATURE [C] | COOLING TOWER MASS FLOW RATE [kg/s] | |
January | 0.144454E+10 | 17.17 | 23374.45 | 18-JAN-12:00 | 1136154.87 | 18-JAN-16:20 | 22.07 | 21.97 | 1.27 |
February | 0.295921E+10 | 35.17 | 23374.45 | 01-FEB-13:40 | 1216411.34 | 27-FEB-11:30 | 22.62 | 22.38 | 2.87 |
March | 0.419338E+10 | 49.83 | 23374.45 | 06-MAR-09:40 | 1179301.80 | 17-MAR-15:40 | 22.69 | 22.42 | 3.81 |
April | 0.726478E+10 | 86.33 | 23374.45 | 04-APR-15:20 | 1221774.65 | 28-APR-07:15 | 23.72 | 23.23 | 6.62 |
May | 0.276974E+11 | 329.15 | 23374.45 | 01-MAY-06:10 | 1401550.63 | 18-MAY-04:13 | 27.11 | 25.47 | 25.25 |
June | 0.284402E+11 | 337.98 | 23374.45 | 01-JUN-04:13 | 1161800.71 | 01-JUN-12:40 | 27.16 | 25.43 | 27.51 |
July | 0.340851E+11 | 405.06 | 23374.45 | 01-JUL-05:08 | 1248269.01 | 14-JUL-14:40 | 28.07 | 26.14 | 30.99 |
August | 0.331172E+11 | 393.56 | 23374.45 | 01-AUG-06:10 | 1208774.26 | 07-AUG-14:50 | 27.47 | 25.57 | 31.49 |
September | 0.309111E+11 | 367.34 | 23374.45 | 01-SEP-05:05 | 1540848.05 | 29-SEP-04:11 | 27.87 | 26.01 | 28.59 |
October | 0.200113E+11 | 237.81 | 23374.45 | 02-OCT-10:30 | 1225953.43 | 02-OCT-13:30 | 25.70 | 24.54 | 19.27 |
November | 0.631110E+10 | 75.00 | 23374.45 | 01-NOV-06:10 | 1240437.78 | 02-NOV-07:25 | 23.28 | 22.90 | 6.39 |
December | 0.421091E+10 | 50.04 | 23374.45 | 08-DEC-15:50 | 1152017.33 | 11-DEC-14:50 | 22.50 | 22.24 | 3.91 |
Annual Sum or Average | 0.200646E+12 | 2384.44 | 25.04 | 24.03 | 15.75 | ||||
Minimum of Months | 0.144454E+10 | 17.17 | 23374.45 | 1136154.87 | 22.07 | 21.97 | 1.27 | ||
Maximum of Months | 0.340851E+11 | 405.06 | 23374.45 | 1540848.05 | 28.07 | 26.14 | 31.49 |
Report: BoilerReportMonthly
For: HEATSYS1 BOILER
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportBOILER HEATING ENERGY [J] | BOILER GAS CONSUMPTION [] | BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] | BOILER HEATING RATE {Maximum} [W] | BOILER HEATING RATE {TIMESTAMP} | BOILER GAS CONSUMPTION RATE [] | BOILER INLET TEMPERATURE [C] | BOILER OUTLET TEMPERATURE [C] | BOILER MASS FLOW RATE [kg/s] | BOILER ANCILLARY ELECTRICITY RATE [W] | BOILER PART LOAD RATIO [] | BOILER PART LOAD RATIO {Maximum} [] | BOILER PART LOAD RATIO {TIMESTAMP} | |
January | 0.419717E+11 | 0.00 | 225.06 | 1076967.26 | 10-JAN-05:01 | 0.00 | 25.68 | 43.09 | 0.07 | 0.00 | 0.01 | 0.66 | 10-JAN-05:01 |
February | 0.211737E+11 | 0.00 | 133.56 | 1017961.89 | 13-FEB-06:03 | 0.00 | 20.50 | 31.87 | 0.04 | 0.00 | 0.01 | 0.62 | 13-FEB-06:03 |
March | 0.189409E+11 | 0.00 | 117.71 | 1074791.65 | 13-MAR-05:02 | 0.00 | 27.60 | 36.63 | 0.03 | 0.00 | 0.00 | 0.66 | 13-MAR-05:02 |
April | 0.506276E+09 | 0.00 | 15.28 | 100483.60 | 18-APR-14:50 | 0.00 | 40.81 | 41.79 | 0.00 | 0.00 | 0.00 | 0.06 | 18-APR-14:50 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 45.04 | 45.04 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:03 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 45.04 | 45.04 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 45.04 | 45.04 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUL-00:05 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 45.04 | 45.04 | 0.00 | 0.00 | 0.00 | 0.00 | 01-AUG-00:05 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 45.04 | 45.04 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:03 |
October | 0.268006E+09 | 0.00 | 12.28 | 48977.67 | 28-OCT-06:10 | 0.00 | 42.35 | 43.17 | 0.00 | 0.00 | 0.00 | 0.03 | 28-OCT-06:10 |
November | 0.301937E+10 | 0.00 | 59.71 | 352037.12 | 16-NOV-06:02 | 0.00 | 22.14 | 27.10 | 0.00 | 0.00 | 0.00 | 0.22 | 16-NOV-06:02 |
December | 0.289698E+11 | 0.00 | 178.85 | 1181074.68 | 20-DEC-05:11 | 0.00 | 21.58 | 35.23 | 0.05 | 0.00 | 0.01 | 0.72 | 20-DEC-05:11 |
Annual Sum or Average | 0.114850E+12 | 0.00 | 742.44 | 0.00 | 35.58 | 40.42 | 0.02 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.50 | 27.10 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.419717E+11 | 0.00 | 225.06 | 1181074.68 | 0.00 | 45.04 | 45.04 | 0.07 | 0.00 | 0.01 | 0.72 |
Report: BoilerReportMonthly
For: CENTRAL BOILER
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportBOILER HEATING ENERGY [J] | BOILER GAS CONSUMPTION [] | BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] | BOILER HEATING RATE {Maximum} [W] | BOILER HEATING RATE {TIMESTAMP} | BOILER GAS CONSUMPTION RATE [] | BOILER INLET TEMPERATURE [C] | BOILER OUTLET TEMPERATURE [C] | BOILER MASS FLOW RATE [kg/s] | BOILER ANCILLARY ELECTRICITY RATE [W] | BOILER PART LOAD RATIO [] | BOILER PART LOAD RATIO [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 23.25 | 23.25 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 27.38 | 27.38 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 32.11 | 32.11 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 39.68 | 39.68 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 33.17 | 33.17 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 38.34 | 38.34 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 43.10 | 43.10 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 46.77 | 46.77 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 32.53 | 32.53 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 34.77 | 34.77 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 33.51 | 33.51 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 34.96 | 34.96 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 35.02 | 35.02 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.25 | 23.25 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46.77 | 46.77 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: VAV_BOT WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.467295E+11 | 0.00 | 268.28 | 0.338612E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 161479.62 | 19-JAN-06:02 | 131617.94 | 19-JAN-06:02 | 0.00 | 0.00 | 0.00 |
February | 0.661489E+11 | 0.00 | 316.67 | 0.462730E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 176448.21 | 28-FEB-05:12 | 153433.64 | 28-FEB-05:12 | 0.00 | 0.00 | 0.00 |
March | 0.825852E+11 | 0.00 | 393.68 | 0.625065E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 185866.15 | 28-MAR-04:12 | 145481.63 | 06-MAR-05:11 | 0.00 | 0.00 | 0.00 |
April | 0.132836E+12 | 0.00 | 506.35 | 0.101896E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 183472.58 | 01-APR-04:12 | 152649.21 | 24-APR-05:02 | 0.00 | 0.00 | 0.00 |
May | 0.173246E+12 | 0.00 | 506.19 | 0.127712E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 210821.11 | 22-MAY-03:02 | 166699.60 | 31-MAY-04:11 | 0.00 | 0.00 | 0.00 |
June | 0.185700E+12 | 0.00 | 553.60 | 0.140613E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 211507.10 | 08-JUN-04:11 | 163992.89 | 01-JUN-04:12 | 0.00 | 0.00 | 0.00 |
July | 0.200820E+12 | 0.00 | 604.67 | 0.149231E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 189797.96 | 03-JUL-05:02 | 161663.63 | 03-JUL-05:02 | 0.00 | 0.00 | 0.00 |
August | 0.220719E+12 | 0.00 | 642.85 | 0.166009E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 197392.39 | 16-AUG-05:02 | 164605.80 | 28-AUG-05:02 | 0.00 | 0.00 | 0.00 |
September | 0.175495E+12 | 0.00 | 491.81 | 0.120044E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 235391.90 | 13-SEP-04:12 | 165327.27 | 25-SEP-05:03 | 0.00 | 0.00 | 0.00 |
October | 0.160196E+12 | 0.00 | 507.61 | 0.120488E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 216371.89 | 21-OCT-04:12 | 168532.82 | 10-OCT-04:12 | 0.00 | 0.00 | 0.00 |
November | 0.100490E+12 | 0.00 | 424.65 | 0.777419E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 210013.98 | 08-NOV-05:11 | 161443.97 | 08-NOV-05:11 | 0.00 | 0.00 | 0.00 |
December | 0.739762E+11 | 0.00 | 340.12 | 0.556987E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 173772.90 | 11-DEC-05:12 | 154776.13 | 11-DEC-05:12 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.161894E+13 | 0.00 | 5556.48 | 0.120207E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.467295E+11 | 0.00 | 268.28 | 0.338612E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 161479.62 | 131617.94 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.220719E+12 | 0.00 | 642.85 | 0.166009E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 235391.90 | 168532.82 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: VAV_MID WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.374288E+12 | 0.00 | 262.35 | 0.260326E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1364913.68 | 19-JAN-06:02 | 1017855.49 | 19-JAN-06:02 | 0.00 | 0.00 | 0.00 |
February | 0.534092E+12 | 0.00 | 301.75 | 0.356461E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1489725.75 | 03-FEB-06:03 | 1276856.27 | 27-FEB-06:02 | 0.00 | 0.00 | 0.00 |
March | 0.638157E+12 | 0.00 | 362.74 | 0.456894E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1850624.85 | 27-MAR-05:02 | 1413957.22 | 27-MAR-05:02 | 0.00 | 0.00 | 0.00 |
April | 0.998860E+12 | 0.00 | 411.34 | 0.711329E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1975020.46 | 29-APR-05:03 | 1486514.40 | 28-APR-05:02 | 0.00 | 0.00 | 0.00 |
May | 0.157199E+13 | 0.00 | 471.81 | 0.111262E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 2412233.21 | 22-MAY-03:02 | 1514603.51 | 04-MAY-04:11 | 0.00 | 0.00 | 0.00 |
June | 0.160344E+13 | 0.00 | 479.34 | 0.115124E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 2073604.79 | 06-JUN-04:11 | 1494294.27 | 09-JUN-04:12 | 0.00 | 0.00 | 0.00 |
July | 0.167063E+13 | 0.00 | 491.02 | 0.114252E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 2042018.77 | 27-JUL-03:02 | 1522267.65 | 20-JUL-03:02 | 0.00 | 0.00 | 0.00 |
August | 0.173400E+13 | 0.00 | 492.18 | 0.118541E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 2371118.24 | 16-AUG-05:02 | 1517821.36 | 03-AUG-03:02 | 0.00 | 0.00 | 0.00 |
September | 0.157134E+13 | 0.00 | 458.83 | 0.101440E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 2535500.55 | 05-SEP-04:11 | 1520574.42 | 01-SEP-04:12 | 0.00 | 0.00 | 0.00 |
October | 0.135109E+13 | 0.00 | 446.33 | 0.957629E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 2126135.77 | 11-OCT-04:12 | 1520318.95 | 06-OCT-03:02 | 0.00 | 0.00 | 0.00 |
November | 0.783585E+12 | 0.00 | 392.32 | 0.579140E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1747744.60 | 02-NOV-05:03 | 1393993.10 | 03-NOV-04:12 | 0.00 | 0.00 | 0.00 |
December | 0.549538E+12 | 0.00 | 298.81 | 0.382302E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1631610.44 | 11-DEC-06:02 | 1235979.31 | 11-DEC-06:02 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.133810E+14 | 0.00 | 4868.82 | 0.931027E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.374288E+12 | 0.00 | 262.35 | 0.260326E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1364913.68 | 1017855.49 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.173400E+13 | 0.00 | 492.18 | 0.118541E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 2535500.55 | 1522267.65 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: VAV_TOP WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.381698E+11 | 0.00 | 253.39 | 0.258367E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 150912.20 | 19-JAN-15:00 | 96736.88 | 19-JAN-15:50 | 0.00 | 0.00 | 0.00 |
February | 0.546978E+11 | 0.00 | 295.26 | 0.361059E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 145721.95 | 24-FEB-16:00 | 103081.63 | 28-FEB-06:03 | 0.00 | 0.00 | 0.00 |
March | 0.662221E+11 | 0.00 | 358.33 | 0.469344E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 174943.56 | 27-MAR-05:02 | 130043.74 | 27-MAR-05:02 | 0.00 | 0.00 | 0.00 |
April | 0.105315E+12 | 0.00 | 405.67 | 0.759149E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 190405.88 | 28-APR-05:02 | 145680.61 | 28-APR-05:02 | 0.00 | 0.00 | 0.00 |
May | 0.171405E+12 | 0.00 | 475.18 | 0.124180E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 270875.56 | 22-MAY-03:02 | 164187.58 | 26-MAY-03:02 | 0.00 | 0.00 | 0.00 |
June | 0.177286E+12 | 0.00 | 485.18 | 0.130834E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 228923.94 | 06-JUN-04:11 | 159068.73 | 06-JUN-04:11 | 0.00 | 0.00 | 0.00 |
July | 0.184171E+12 | 0.00 | 498.56 | 0.129055E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 235121.27 | 27-JUL-03:02 | 166715.16 | 11-JUL-03:02 | 0.00 | 0.00 | 0.00 |
August | 0.189363E+12 | 0.00 | 497.94 | 0.132637E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 262201.23 | 16-AUG-05:02 | 169899.07 | 03-AUG-03:02 | 0.00 | 0.00 | 0.00 |
September | 0.167509E+12 | 0.00 | 462.47 | 0.110253E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 280468.40 | 05-SEP-04:11 | 162508.69 | 29-SEP-04:11 | 0.00 | 0.00 | 0.00 |
October | 0.142904E+12 | 0.00 | 444.68 | 0.102821E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 225382.07 | 06-OCT-03:02 | 160628.71 | 06-OCT-03:02 | 0.00 | 0.00 | 0.00 |
November | 0.778834E+11 | 0.00 | 386.63 | 0.574615E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 168063.79 | 02-NOV-05:03 | 127364.45 | 02-NOV-05:03 | 0.00 | 0.00 | 0.00 |
December | 0.544034E+11 | 0.00 | 295.51 | 0.374678E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 176718.14 | 11-DEC-06:02 | 124159.51 | 11-DEC-06:02 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.142933E+13 | 0.00 | 4858.80 | 0.100950E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.381698E+11 | 0.00 | 253.39 | 0.258367E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 145721.95 | 96736.88 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.189363E+12 | 0.00 | 498.56 | 0.132637E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 280468.40 | 169899.07 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: CAV_BAS COOLING COIL
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.229355E+11 | 0.00 | 144.71 | 0.183527E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 142337.87 | 19-JAN-05:12 | 119421.51 | 30-JAN-05:12 | 0.00 | 0.00 | 0.00 |
February | 0.284262E+11 | 0.00 | 196.28 | 0.235339E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 140150.66 | 03-FEB-05:12 | 118814.63 | 21-FEB-05:12 | 0.00 | 0.00 | 0.00 |
March | 0.391337E+11 | 0.00 | 240.50 | 0.335794E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 168028.79 | 07-MAR-05:12 | 112142.59 | 06-MAR-05:11 | 0.00 | 0.00 | 0.00 |
April | 0.619439E+11 | 0.00 | 346.42 | 0.544226E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 168339.93 | 26-APR-04:13 | 103325.90 | 24-APR-04:14 | 0.00 | 0.00 | 0.00 |
May | 0.111483E+12 | 0.00 | 431.42 | 0.876833E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 191233.99 | 29-MAY-09:21 | 106482.29 | 30-MAY-03:02 | 0.00 | 0.00 | 0.00 |
June | 0.116580E+12 | 0.00 | 427.90 | 0.892590E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 195095.57 | 19-JUN-03:02 | 105979.95 | 12-JUN-03:02 | 0.00 | 0.00 | 0.00 |
July | 0.124090E+12 | 0.00 | 428.74 | 0.899967E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 186766.06 | 03-JUL-03:13 | 104503.06 | 05-JUL-03:13 | 0.00 | 0.00 | 0.00 |
August | 0.137320E+12 | 0.00 | 474.66 | 0.102164E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 185843.86 | 06-AUG-23:22 | 107924.35 | 21-AUG-03:02 | 0.00 | 0.00 | 0.00 |
September | 0.118261E+12 | 0.00 | 441.20 | 0.884613E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 192778.19 | 10-SEP-15:08 | 108599.07 | 04-SEP-10:42 | 0.00 | 0.00 | 0.00 |
October | 0.101665E+12 | 0.00 | 414.91 | 0.798273E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 192465.53 | 08-OCT-13:50 | 115010.39 | 01-OCT-14:35 | 0.00 | 0.00 | 0.00 |
November | 0.566141E+11 | 0.00 | 304.25 | 0.475519E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 176169.51 | 11-NOV-14:00 | 106069.57 | 05-NOV-13:20 | 0.00 | 0.00 | 0.00 |
December | 0.373098E+11 | 0.00 | 206.73 | 0.308461E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 168780.13 | 15-DEC-05:11 | 110448.79 | 10-DEC-16:18 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.955762E+12 | 0.00 | 4057.74 | 0.745678E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.229355E+11 | 0.00 | 144.71 | 0.183527E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 140150.66 | 103325.90 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.137320E+12 | 0.00 | 474.66 | 0.102164E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 195095.57 | 119421.51 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: AIRLOOP DATACENTER BASEMENT COOLING COIL
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.333017E+12 | 0.862031E+11 | 744.00 | 0.330262E+12 | 0.275450E+10 | 0.00 | 0.37 | 19-JAN-12:00 | 0.30 | 09-JAN-07:10 | 137709.70 | 31-JAN-16:40 | 129486.68 | 02-JAN-15:00 | 10026.76 | 31-JAN-17:00 | 44747.11 | 02-JAN-15:00 | 0.00 |
February | 0.524231E+12 | 0.133468E+12 | 672.00 | 0.519301E+12 | 0.492987E+10 | 0.00 | 0.60 | 24-FEB-13:50 | 0.52 | 13-FEB-07:20 | 229029.45 | 24-FEB-17:00 | 220024.09 | 24-FEB-13:20 | 9736.10 | 24-FEB-17:10 | 77022.80 | 02-FEB-13:10 | 0.00 |
March | 0.825493E+12 | 0.213950E+12 | 744.00 | 0.820562E+12 | 0.493097E+10 | 0.00 | 0.95 | 31-MAR-24:00 | 0.72 | 15-MAR-07:00 | 394706.20 | 31-MAR-24:00 | 394706.20 | 31-MAR-24:00 | 11327.70 | 07-MAR-15:00 | 112193.53 | 30-MAR-13:00 | 0.00 |
April | 0.103845E+13 | 0.292533E+12 | 720.00 | 0.103224E+13 | 0.621055E+10 | 0.00 | 1.00 | 03-APR-13:30 | 0.37 | 30-APR-23:53 | 423667.70 | 28-APR-18:00 | 405503.91 | 18-APR-16:50 | 18570.48 | 28-APR-18:00 | 148735.01 | 28-APR-15:00 | 0.00 |
May | 0.351114E+12 | 0.117454E+12 | 744.00 | 0.338369E+12 | 0.127445E+11 | 0.00 | 0.55 | 31-MAY-23:20 | 0.34 | 07-MAY-01:00 | 213560.08 | 31-MAY-23:10 | 211800.61 | 31-MAY-24:00 | 14691.56 | 23-MAY-16:00 | 63525.17 | 31-MAY-23:20 | 0.00 |
June | 0.578272E+12 | 0.194873E+12 | 720.00 | 0.564382E+12 | 0.138901E+11 | 0.00 | 0.78 | 30-JUN-23:35 | 0.55 | 01-JUN-05:00 | 303567.87 | 30-JUN-24:00 | 303502.08 | 30-JUN-23:57 | 17782.37 | 29-JUN-15:00 | 95389.64 | 30-JUN-23:20 | 0.00 |
July | 0.844125E+12 | 0.285677E+12 | 744.00 | 0.829239E+12 | 0.148862E+11 | 0.00 | 0.98 | 31-JUL-23:23 | 0.77 | 01-JUL-04:10 | 395612.51 | 31-JUL-23:57 | 395612.51 | 31-JUL-23:57 | 16653.93 | 12-JUL-12:50 | 135161.47 | 21-JUL-16:00 | 0.00 |
August | 0.108298E+13 | 0.355464E+12 | 744.00 | 0.106952E+13 | 0.134609E+11 | 0.00 | 1.00 | 01-AUG-06:40 | 0.39 | 31-AUG-24:00 | 425484.91 | 07-AUG-14:00 | 410717.41 | 06-AUG-15:54 | 20725.65 | 07-AUG-14:00 | 156259.46 | 30-AUG-16:00 | 0.00 |
September | 0.344072E+12 | 0.112720E+12 | 720.00 | 0.330460E+12 | 0.136123E+11 | 0.00 | 0.55 | 30-SEP-23:20 | 0.34 | 22-SEP-06:10 | 213643.76 | 30-SEP-24:00 | 212348.25 | 30-SEP-24:00 | 14102.19 | 18-SEP-10:40 | 62702.76 | 30-SEP-23:20 | 0.00 |
October | 0.595694E+12 | 0.184155E+12 | 744.00 | 0.584785E+12 | 0.109093E+11 | 0.00 | 0.76 | 31-OCT-24:00 | 0.53 | 17-OCT-07:00 | 304810.91 | 31-OCT-24:00 | 304810.91 | 31-OCT-24:00 | 16004.57 | 24-OCT-09:00 | 92199.71 | 05-OCT-15:00 | 0.00 |
November | 0.806303E+12 | 0.215691E+12 | 720.00 | 0.800204E+12 | 0.609862E+10 | 0.00 | 0.84 | 02-NOV-13:20 | 0.72 | 15-NOV-07:10 | 326140.70 | 03-NOV-16:00 | 314131.25 | 03-NOV-14:00 | 12838.60 | 03-NOV-16:10 | 115344.07 | 02-NOV-13:00 | 0.00 |
December | 0.107270E+13 | 0.268510E+12 | 744.00 | 0.106892E+13 | 0.377611E+10 | 0.00 | 1.00 | 08-DEC-11:30 | 0.90 | 18-DEC-07:20 | 417636.03 | 13-DEC-18:00 | 405157.70 | 13-DEC-18:00 | 13015.04 | 11-DEC-15:10 | 139867.99 | 13-DEC-15:00 | 0.00 |
Annual Sum or Average | 0.839646E+13 | 0.246070E+13 | 8760.00 | 0.828825E+13 | 0.108204E+12 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.333017E+12 | 0.862031E+11 | 672.00 | 0.330262E+12 | 0.275450E+10 | 0.00 | 0.37 | 0.30 | 137709.70 | 129486.68 | 9736.10 | 44747.11 | 0.00 | ||||||
Maximum of Months | 0.108298E+13 | 0.355464E+12 | 744.00 | 0.106952E+13 | 0.148862E+11 | 0.00 | 1.00 | 0.90 | 425484.91 | 410717.41 | 20725.65 | 156259.46 | 0.00 |
Report: DXReportMonthly
For: AIRLOOP DATACENTER BOT COOLING COIL
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.515835E+10 | 0.134414E+10 | 744.00 | 0.504859E+10 | 0.109757E+09 | 0.00 | 0.35 | 19-JAN-17:00 | 0.13 | 21-JAN-08:00 | 2974.67 | 19-JAN-17:00 | 2623.66 | 01-JAN-17:27 | 407.90 | 31-JAN-17:00 | 871.38 | 19-JAN-16:50 | 0.00 |
February | 0.964382E+10 | 0.244288E+10 | 672.00 | 0.944967E+10 | 0.194154E+09 | 0.00 | 0.57 | 27-FEB-17:00 | 0.37 | 17-FEB-07:10 | 4932.54 | 27-FEB-17:00 | 4720.93 | 26-FEB-17:56 | 401.28 | 24-FEB-17:00 | 1514.22 | 02-FEB-13:10 | 0.00 |
March | 0.159130E+11 | 0.408394E+10 | 744.00 | 0.157072E+11 | 0.205774E+09 | 0.00 | 0.86 | 31-MAR-24:00 | 0.57 | 11-MAR-18:00 | 7754.00 | 31-MAR-24:00 | 7754.00 | 31-MAR-24:00 | 482.07 | 07-MAR-15:00 | 2262.12 | 30-MAR-13:00 | 0.00 |
April | 0.206983E+11 | 0.576304E+10 | 720.00 | 0.204099E+11 | 0.288486E+09 | 0.00 | 1.00 | 28-APR-13:10 | 0.30 | 30-APR-23:53 | 8806.68 | 28-APR-17:10 | 8536.13 | 16-APR-18:10 | 543.63 | 28-APR-17:30 | 3197.30 | 28-APR-15:00 | 0.00 |
May | 0.672551E+10 | 0.219479E+10 | 744.00 | 0.621495E+10 | 0.510563E+09 | 0.00 | 0.49 | 31-MAY-23:20 | 0.26 | 02-MAY-06:10 | 4136.40 | 31-MAY-23:10 | 4046.00 | 31-MAY-24:00 | 562.01 | 23-MAY-16:00 | 1203.21 | 31-MAY-23:20 | 0.00 |
June | 0.114836E+11 | 0.378044E+10 | 720.00 | 0.109016E+11 | 0.581977E+09 | 0.00 | 0.69 | 30-JUN-23:23 | 0.47 | 01-JUN-06:00 | 5921.47 | 30-JUN-23:23 | 5904.54 | 30-JUN-23:35 | 691.55 | 29-JUN-15:00 | 1927.34 | 29-JUN-14:00 | 0.00 |
July | 0.169237E+11 | 0.560633E+10 | 744.00 | 0.162734E+11 | 0.650323E+09 | 0.00 | 0.89 | 31-JUL-23:23 | 0.68 | 15-JUL-06:00 | 7768.75 | 31-JUL-23:35 | 7768.75 | 31-JUL-23:35 | 667.12 | 12-JUL-10:00 | 2820.47 | 21-JUL-16:00 | 0.00 |
August | 0.220562E+11 | 0.720836E+10 | 744.00 | 0.213999E+11 | 0.656287E+09 | 0.00 | 1.00 | 01-AUG-10:50 | 0.32 | 31-AUG-24:00 | 9055.78 | 14-AUG-16:00 | 8395.93 | 14-AUG-16:00 | 739.77 | 07-AUG-13:40 | 3358.88 | 30-AUG-16:00 | 0.00 |
September | 0.653858E+10 | 0.208685E+10 | 720.00 | 0.599133E+10 | 0.547241E+09 | 0.00 | 0.48 | 30-SEP-23:50 | 0.26 | 30-SEP-06:10 | 4071.22 | 30-SEP-24:00 | 4039.51 | 30-SEP-24:00 | 591.66 | 18-SEP-14:30 | 1189.63 | 09-SEP-17:00 | 0.00 |
October | 0.116343E+11 | 0.353031E+10 | 744.00 | 0.111808E+11 | 0.453447E+09 | 0.00 | 0.68 | 31-OCT-24:00 | 0.41 | 28-OCT-07:00 | 5920.13 | 31-OCT-24:00 | 5911.23 | 31-OCT-24:00 | 688.94 | 24-OCT-14:10 | 1910.27 | 05-OCT-15:00 | 0.00 |
November | 0.157062E+11 | 0.414782E+10 | 720.00 | 0.154540E+11 | 0.252150E+09 | 0.00 | 0.80 | 02-NOV-16:00 | 0.60 | 15-NOV-07:10 | 6991.54 | 07-NOV-16:40 | 6686.75 | 06-NOV-17:00 | 561.17 | 01-NOV-11:00 | 2346.80 | 01-NOV-14:00 | 0.00 |
December | 0.209424E+11 | 0.520409E+10 | 744.00 | 0.207657E+11 | 0.176631E+09 | 0.00 | 1.00 | 15-DEC-17:00 | 0.75 | 20-DEC-07:40 | 8973.78 | 14-DEC-17:00 | 8528.56 | 15-DEC-17:00 | 565.33 | 12-DEC-15:00 | 2972.51 | 13-DEC-15:00 | 0.00 |
Annual Sum or Average | 0.163424E+12 | 0.473930E+11 | 8760.00 | 0.158797E+12 | 0.462679E+10 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.515835E+10 | 0.134414E+10 | 672.00 | 0.504859E+10 | 0.109757E+09 | 0.00 | 0.35 | 0.13 | 2974.67 | 2623.66 | 401.28 | 871.38 | 0.00 | ||||||
Maximum of Months | 0.220562E+11 | 0.720836E+10 | 744.00 | 0.213999E+11 | 0.656287E+09 | 0.00 | 1.00 | 0.75 | 9055.78 | 8536.13 | 739.77 | 3358.88 | 0.00 |
Report: DXReportMonthly
For: AIRLOOP DATACENTER MID COOLING COIL
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.369112E+11 | 0.987261E+10 | 744.00 | 0.358553E+11 | 0.105590E+10 | 0.00 | 0.35 | 19-JAN-17:00 | 0.04 | 10-JAN-07:10 | 27910.99 | 19-JAN-17:00 | 24257.01 | 19-JAN-17:00 | 4037.73 | 31-JAN-17:00 | 8170.85 | 19-JAN-17:00 | 0.00 |
February | 0.820651E+11 | 0.210646E+11 | 672.00 | 0.801570E+11 | 0.190803E+10 | 0.00 | 0.56 | 27-FEB-17:00 | 0.26 | 06-FEB-07:10 | 46450.26 | 27-FEB-17:00 | 43115.65 | 26-FEB-17:58 | 3983.25 | 24-FEB-17:00 | 14211.92 | 24-FEB-14:00 | 0.00 |
March | 0.143265E+12 | 0.371181E+11 | 744.00 | 0.141222E+12 | 0.204292E+10 | 0.00 | 0.84 | 31-MAR-24:00 | 0.49 | 13-MAR-06:10 | 72150.61 | 31-MAR-24:00 | 72150.61 | 31-MAR-24:00 | 4802.57 | 07-MAR-15:00 | 21529.18 | 30-MAR-13:00 | 0.00 |
April | 0.194402E+12 | 0.543222E+11 | 720.00 | 0.191518E+12 | 0.288411E+10 | 0.00 | 1.00 | 28-APR-13:20 | 0.28 | 30-APR-23:53 | 84105.77 | 28-APR-17:10 | 80025.53 | 21-APR-16:00 | 5355.39 | 28-APR-17:20 | 30533.55 | 28-APR-15:00 | 0.00 |
May | 0.623773E+11 | 0.204035E+11 | 744.00 | 0.573315E+11 | 0.504580E+10 | 0.00 | 0.48 | 31-MAY-23:20 | 0.24 | 02-MAY-06:10 | 38844.89 | 31-MAY-23:10 | 37849.41 | 31-MAY-24:00 | 5576.77 | 23-MAY-16:00 | 11308.47 | 31-MAY-23:20 | 0.00 |
June | 0.108984E+12 | 0.358975E+11 | 720.00 | 0.103194E+12 | 0.579009E+10 | 0.00 | 0.70 | 30-JUN-23:53 | 0.45 | 07-JUN-06:10 | 57245.95 | 30-JUN-23:53 | 57088.16 | 30-JUN-23:57 | 6850.54 | 29-JUN-15:00 | 18438.07 | 29-JUN-14:00 | 0.00 |
July | 0.161340E+12 | 0.534488E+11 | 744.00 | 0.154854E+12 | 0.648653E+10 | 0.00 | 0.89 | 31-JUL-23:53 | 0.67 | 15-JUL-06:00 | 74476.14 | 31-JUL-24:00 | 74475.01 | 31-JUL-24:00 | 6658.25 | 12-JUL-10:00 | 26952.67 | 21-JUL-16:00 | 0.00 |
August | 0.209714E+12 | 0.685831E+11 | 744.00 | 0.203152E+12 | 0.656283E+10 | 0.00 | 1.00 | 01-AUG-10:50 | 0.29 | 31-AUG-24:00 | 86113.09 | 14-AUG-16:00 | 79517.47 | 14-AUG-16:00 | 7324.16 | 09-AUG-17:00 | 32074.82 | 30-AUG-16:00 | 0.00 |
September | 0.595997E+11 | 0.190827E+11 | 720.00 | 0.542072E+11 | 0.539249E+10 | 0.00 | 0.47 | 30-SEP-23:50 | 0.23 | 28-SEP-06:10 | 37681.43 | 30-SEP-24:00 | 37346.48 | 30-SEP-24:00 | 5863.46 | 18-SEP-14:30 | 11039.99 | 06-SEP-16:00 | 0.00 |
October | 0.108054E+12 | 0.329420E+11 | 744.00 | 0.103552E+12 | 0.450258E+10 | 0.00 | 0.66 | 31-OCT-24:00 | 0.36 | 28-OCT-07:00 | 54645.94 | 31-OCT-24:00 | 54521.48 | 31-OCT-24:00 | 6849.77 | 24-OCT-14:10 | 18169.82 | 05-OCT-15:00 | 0.00 |
November | 0.142352E+12 | 0.379310E+11 | 720.00 | 0.139851E+12 | 0.250083E+10 | 0.00 | 0.80 | 02-NOV-16:00 | 0.54 | 15-NOV-07:10 | 66494.84 | 07-NOV-16:50 | 63285.02 | 06-NOV-17:00 | 5609.73 | 01-NOV-11:00 | 22350.54 | 01-NOV-14:00 | 0.00 |
December | 0.188929E+12 | 0.474392E+11 | 744.00 | 0.187162E+12 | 0.176734E+10 | 0.00 | 1.00 | 15-DEC-17:00 | 0.68 | 20-DEC-07:10 | 85078.37 | 14-DEC-17:00 | 80822.18 | 15-DEC-17:00 | 5638.52 | 12-DEC-15:00 | 28146.62 | 13-DEC-15:00 | 0.00 |
Annual Sum or Average | 0.149800E+13 | 0.438105E+12 | 8760.00 | 0.145206E+13 | 0.459395E+11 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.369112E+11 | 0.987261E+10 | 672.00 | 0.358553E+11 | 0.105590E+10 | 0.00 | 0.35 | 0.04 | 27910.99 | 24257.01 | 3983.25 | 8170.85 | 0.00 | ||||||
Maximum of Months | 0.209714E+12 | 0.685831E+11 | 744.00 | 0.203152E+12 | 0.656283E+10 | 0.00 | 1.00 | 0.68 | 86113.09 | 80822.18 | 7324.16 | 32074.82 | 0.00 |
Report: DXReportMonthly
For: AIRLOOP DATACENTER TOP COOLING COIL
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.272029E+10 | 0.747360E+09 | 687.99 | 0.261647E+10 | 0.103819E+09 | 0.00 | 0.35 | 19-JAN-17:00 | 0.00 | 04-JAN-02:35 | 2856.11 | 19-JAN-17:00 | 2489.81 | 19-JAN-17:00 | 407.32 | 31-JAN-17:00 | 836.35 | 19-JAN-16:50 | 0.00 |
February | 0.744680E+10 | 0.193506E+10 | 671.83 | 0.725747E+10 | 0.189322E+09 | 0.00 | 0.56 | 27-FEB-17:00 | 0.00 | 05-FEB-06:45 | 4718.48 | 27-FEB-17:00 | 4356.76 | 27-FEB-17:00 | 399.42 | 24-FEB-17:00 | 1440.07 | 24-FEB-14:00 | 0.00 |
March | 0.137986E+11 | 0.360769E+10 | 744.00 | 0.135950E+11 | 0.203587E+09 | 0.00 | 0.81 | 31-MAR-24:00 | 0.36 | 12-MAR-07:50 | 7111.30 | 31-MAR-24:00 | 7111.30 | 31-MAR-24:00 | 480.38 | 07-MAR-15:00 | 2172.38 | 30-MAR-13:00 | 0.00 |
April | 0.192925E+11 | 0.541708E+10 | 720.00 | 0.190046E+11 | 0.287903E+09 | 0.00 | 1.00 | 28-APR-13:50 | 0.27 | 30-APR-23:53 | 8516.62 | 28-APR-17:10 | 8137.76 | 21-APR-16:00 | 529.60 | 28-APR-17:20 | 3108.69 | 28-APR-15:00 | 0.00 |
May | 0.635745E+10 | 0.208200E+10 | 744.00 | 0.585127E+10 | 0.506187E+09 | 0.00 | 0.47 | 31-MAY-23:20 | 0.23 | 15-MAY-06:10 | 3862.36 | 31-MAY-23:10 | 3756.85 | 31-MAY-24:00 | 560.79 | 23-MAY-16:00 | 1151.21 | 18-MAY-16:00 | 0.00 |
June | 0.110395E+11 | 0.364042E+10 | 720.00 | 0.104599E+11 | 0.579640E+09 | 0.00 | 0.69 | 30-JUN-23:53 | 0.43 | 07-JUN-06:10 | 5758.24 | 30-JUN-23:53 | 5742.48 | 30-JUN-23:57 | 689.80 | 29-JUN-15:00 | 1887.96 | 29-JUN-14:00 | 0.00 |
July | 0.162890E+11 | 0.540393E+10 | 744.00 | 0.156403E+11 | 0.648655E+09 | 0.00 | 0.87 | 31-JUL-23:53 | 0.65 | 15-JUL-06:00 | 7443.96 | 31-JUL-24:00 | 7443.62 | 31-JUL-24:00 | 666.89 | 12-JUL-10:00 | 2751.03 | 21-JUL-16:00 | 0.00 |
August | 0.211069E+11 | 0.691773E+10 | 744.00 | 0.204506E+11 | 0.656246E+09 | 0.00 | 1.00 | 01-AUG-12:10 | 0.28 | 31-AUG-24:00 | 8747.40 | 14-AUG-15:50 | 8091.01 | 14-AUG-15:50 | 729.63 | 09-AUG-17:00 | 3265.59 | 30-AUG-16:00 | 0.00 |
September | 0.603131E+10 | 0.193527E+10 | 720.00 | 0.549115E+10 | 0.540157E+09 | 0.00 | 0.46 | 30-SEP-23:30 | 0.21 | 28-SEP-06:10 | 3770.58 | 30-SEP-24:00 | 3737.44 | 30-SEP-24:00 | 588.92 | 18-SEP-10:30 | 1162.50 | 09-SEP-17:00 | 0.00 |
October | 0.107311E+11 | 0.328789E+10 | 744.00 | 0.102811E+11 | 0.450044E+09 | 0.00 | 0.64 | 31-OCT-24:00 | 0.30 | 28-OCT-07:00 | 5398.30 | 31-OCT-24:00 | 5385.15 | 31-OCT-24:00 | 687.59 | 24-OCT-14:10 | 1859.41 | 05-OCT-15:00 | 0.00 |
November | 0.137142E+11 | 0.368809E+10 | 720.00 | 0.134652E+11 | 0.248968E+09 | 0.00 | 0.80 | 02-NOV-16:00 | 0.47 | 16-NOV-07:05 | 6718.25 | 07-NOV-16:40 | 6402.12 | 06-NOV-17:00 | 561.58 | 01-NOV-11:00 | 2256.77 | 02-NOV-15:00 | 0.00 |
December | 0.180937E+11 | 0.459244E+10 | 744.00 | 0.179175E+11 | 0.176181E+09 | 0.00 | 0.99 | 15-DEC-17:00 | 0.59 | 20-DEC-07:10 | 8579.12 | 14-DEC-17:00 | 8163.80 | 15-DEC-17:00 | 564.05 | 12-DEC-15:00 | 2837.72 | 13-DEC-15:00 | 0.00 |
Annual Sum or Average | 0.146621E+12 | 0.432549E+11 | 8703.82 | 0.142031E+12 | 0.459071E+10 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.272029E+10 | 0.747360E+09 | 671.83 | 0.261647E+10 | 0.103819E+09 | 0.00 | 0.35 | 0.00 | 2856.11 | 2489.81 | 399.42 | 836.35 | 0.00 | ||||||
Maximum of Months | 0.211069E+11 | 0.691773E+10 | 744.00 | 0.204506E+11 | 0.656246E+09 | 0.00 | 1.00 | 0.65 | 8747.40 | 8163.80 | 729.63 | 3265.59 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 111.15 | 0.00 | 111.15 | 64.62 | 517.73 | 0.00 | 0.00 | 0.00 |
February | 131.13 | 0.00 | 131.13 | 91.15 | 441.10 | 0.00 | 0.00 | 0.00 |
March | 152.12 | 0.00 | 152.12 | 138.91 | 377.02 | 0.00 | 0.00 | 0.00 |
April | 179.53 | 0.74 | 178.80 | 235.19 | 226.02 | 0.00 | 0.00 | 0.00 |
May | 203.36 | 7.44 | 195.92 | 422.73 | 62.38 | 0.00 | 0.00 | 0.00 |
June | 231.26 | 16.01 | 215.25 | 502.71 | 50.31 | 0.00 | 0.00 | 0.00 |
July | 224.42 | 8.55 | 215.87 | 483.04 | 31.76 | 0.00 | 0.00 | 0.00 |
August | 200.97 | 1.58 | 199.39 | 434.93 | 45.74 | 0.00 | 0.00 | 0.00 |
September | 173.60 | 0.01 | 173.58 | 343.63 | 75.04 | 0.00 | 0.00 | 0.00 |
October | 150.85 | 0.00 | 150.85 | 272.39 | 141.63 | 0.00 | 0.00 | 0.00 |
November | 114.52 | 0.00 | 114.52 | 109.21 | 337.45 | 0.00 | 0.00 | 0.00 |
December | 103.32 | 0.00 | 103.32 | 70.18 | 460.62 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 164.85 | 2.87 | 161.98 | 265.11 | 229.47 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 103.32 | 0.00 | 103.32 | 64.62 | 31.76 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 231.26 | 16.01 | 215.87 | 502.71 | 517.73 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 111.15 | 0.00 | 111.15 | 64.62 | 517.73 | 0.00 | 0.00 | 0.00 |
February | 131.13 | 0.00 | 131.13 | 91.15 | 441.10 | 0.00 | 0.00 | 0.00 |
March | 152.12 | 0.00 | 152.12 | 138.91 | 377.02 | 0.00 | 0.00 | 0.00 |
April | 179.53 | 0.74 | 178.80 | 235.19 | 226.02 | 0.00 | 0.00 | 0.00 |
May | 203.36 | 7.44 | 195.92 | 422.73 | 62.38 | 0.00 | 0.00 | 0.00 |
June | 231.26 | 16.01 | 215.25 | 502.71 | 50.31 | 0.00 | 0.00 | 0.00 |
July | 224.42 | 8.55 | 215.87 | 483.04 | 31.76 | 0.00 | 0.00 | 0.00 |
August | 200.97 | 1.58 | 199.39 | 434.93 | 45.74 | 0.00 | 0.00 | 0.00 |
September | 173.60 | 0.01 | 173.58 | 343.63 | 75.04 | 0.00 | 0.00 | 0.00 |
October | 150.85 | 0.00 | 150.85 | 272.39 | 141.63 | 0.00 | 0.00 | 0.00 |
November | 114.52 | 0.00 | 114.52 | 109.21 | 337.45 | 0.00 | 0.00 | 0.00 |
December | 103.32 | 0.00 | 103.32 | 70.18 | 460.62 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 164.85 | 2.87 | 161.98 | 265.11 | 229.47 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 103.32 | 0.00 | 103.32 | 64.62 | 31.76 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 231.26 | 16.01 | 215.87 | 502.71 | 517.73 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 111.15 | 0.00 | 111.15 | 64.62 | 517.73 | 0.00 | 0.00 | 0.00 |
February | 131.13 | 0.00 | 131.13 | 91.15 | 441.10 | 0.00 | 0.00 | 0.00 |
March | 152.12 | 0.00 | 152.12 | 138.91 | 377.02 | 0.00 | 0.00 | 0.00 |
April | 179.53 | 0.74 | 178.80 | 235.19 | 226.02 | 0.00 | 0.00 | 0.00 |
May | 203.36 | 7.44 | 195.92 | 422.73 | 62.38 | 0.00 | 0.00 | 0.00 |
June | 231.26 | 16.01 | 215.25 | 502.71 | 50.31 | 0.00 | 0.00 | 0.00 |
July | 224.42 | 8.55 | 215.87 | 483.04 | 31.76 | 0.00 | 0.00 | 0.00 |
August | 200.97 | 1.58 | 199.39 | 434.93 | 45.74 | 0.00 | 0.00 | 0.00 |
September | 173.60 | 0.01 | 173.58 | 343.63 | 75.04 | 0.00 | 0.00 | 0.00 |
October | 150.85 | 0.00 | 150.85 | 272.39 | 141.63 | 0.00 | 0.00 | 0.00 |
November | 114.52 | 0.00 | 114.52 | 109.21 | 337.45 | 0.00 | 0.00 | 0.00 |
December | 103.32 | 0.00 | 103.32 | 70.18 | 460.62 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 164.85 | 2.87 | 161.98 | 265.11 | 229.47 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 103.32 | 0.00 | 103.32 | 64.62 | 31.76 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 231.26 | 16.01 | 215.87 | 502.71 | 517.73 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 111.15 | 0.00 | 111.15 | 64.62 | 517.73 | 0.00 | 0.00 | 0.00 |
February | 131.13 | 0.00 | 131.13 | 91.15 | 441.10 | 0.00 | 0.00 | 0.00 |
March | 152.12 | 0.00 | 152.12 | 138.91 | 377.02 | 0.00 | 0.00 | 0.00 |
April | 179.53 | 0.74 | 178.80 | 235.19 | 226.02 | 0.00 | 0.00 | 0.00 |
May | 203.36 | 7.44 | 195.92 | 422.73 | 62.38 | 0.00 | 0.00 | 0.00 |
June | 231.26 | 16.01 | 215.25 | 502.71 | 50.31 | 0.00 | 0.00 | 0.00 |
July | 224.42 | 8.55 | 215.87 | 483.04 | 31.76 | 0.00 | 0.00 | 0.00 |
August | 200.97 | 1.58 | 199.39 | 434.93 | 45.74 | 0.00 | 0.00 | 0.00 |
September | 173.60 | 0.01 | 173.58 | 343.63 | 75.04 | 0.00 | 0.00 | 0.00 |
October | 150.85 | 0.00 | 150.85 | 272.39 | 141.63 | 0.00 | 0.00 | 0.00 |
November | 114.52 | 0.00 | 114.52 | 109.21 | 337.45 | 0.00 | 0.00 | 0.00 |
December | 103.32 | 0.00 | 103.32 | 70.18 | 460.62 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 164.85 | 2.87 | 161.98 | 265.11 | 229.47 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 103.32 | 0.00 | 103.32 | 64.62 | 31.76 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 231.26 | 16.01 | 215.87 | 502.71 | 517.73 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 111.14 | 0.00 | 111.14 | 64.62 | 517.71 | 0.00 | 0.00 | 0.00 |
February | 131.12 | 0.00 | 131.12 | 91.14 | 441.08 | 0.00 | 0.00 | 0.00 |
March | 152.11 | 0.00 | 152.11 | 138.90 | 377.00 | 0.00 | 0.00 | 0.00 |
April | 179.53 | 0.74 | 178.79 | 235.18 | 226.01 | 0.00 | 0.00 | 0.00 |
May | 203.35 | 7.44 | 195.91 | 422.71 | 62.37 | 0.00 | 0.00 | 0.00 |
June | 231.25 | 16.01 | 215.24 | 502.69 | 50.31 | 0.00 | 0.00 | 0.00 |
July | 224.41 | 8.55 | 215.86 | 483.02 | 31.76 | 0.00 | 0.00 | 0.00 |
August | 200.97 | 1.58 | 199.39 | 434.91 | 45.74 | 0.00 | 0.00 | 0.00 |
September | 173.59 | 0.01 | 173.58 | 343.61 | 75.03 | 0.00 | 0.00 | 0.00 |
October | 150.85 | 0.00 | 150.85 | 272.38 | 141.62 | 0.00 | 0.00 | 0.00 |
November | 114.52 | 0.00 | 114.52 | 109.21 | 337.43 | 0.00 | 0.00 | 0.00 |
December | 103.32 | 0.00 | 103.32 | 70.18 | 460.60 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 164.85 | 2.87 | 161.98 | 265.10 | 229.47 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 103.32 | 0.00 | 103.32 | 64.62 | 31.76 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 231.25 | 16.01 | 215.86 | 502.69 | 517.71 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 317.83 | 161.84 | 155.99 | 350.15 | 515.91 | 0.00 | 0.00 | 0.00 |
February | 353.92 | 170.86 | 183.06 | 418.02 | 435.19 | 0.00 | 0.00 | 0.00 |
March | 416.32 | 200.78 | 215.54 | 546.03 | 371.84 | 0.00 | 0.00 | 0.00 |
April | 456.87 | 206.63 | 250.24 | 700.35 | 225.32 | 0.00 | 0.00 | 0.00 |
May | 470.91 | 204.19 | 266.71 | 890.39 | 65.67 | 0.00 | 0.00 | 0.00 |
June | 477.58 | 189.39 | 288.18 | 941.57 | 48.25 | 0.00 | 0.00 | 0.00 |
July | 460.45 | 168.50 | 291.95 | 912.47 | 25.69 | 0.00 | 0.00 | 0.00 |
August | 424.29 | 145.88 | 278.42 | 841.27 | 37.17 | 0.00 | 0.00 | 0.00 |
September | 375.85 | 129.21 | 246.63 | 701.56 | 76.78 | 0.00 | 0.00 | 0.00 |
October | 371.41 | 156.73 | 214.68 | 653.38 | 141.50 | 0.00 | 0.00 | 0.00 |
November | 328.83 | 167.75 | 161.08 | 441.17 | 329.49 | 0.00 | 0.00 | 0.00 |
December | 258.90 | 117.28 | 141.63 | 300.17 | 451.58 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 392.90 | 168.18 | 224.72 | 642.61 | 225.95 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 258.90 | 117.28 | 141.63 | 300.17 | 25.69 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 477.58 | 206.63 | 291.95 | 941.57 | 515.91 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 317.83 | 161.84 | 155.99 | 350.15 | 515.91 | 0.00 | 0.00 | 0.00 |
February | 353.92 | 170.86 | 183.06 | 418.02 | 435.19 | 0.00 | 0.00 | 0.00 |
March | 416.32 | 200.78 | 215.54 | 546.03 | 371.84 | 0.00 | 0.00 | 0.00 |
April | 456.87 | 206.63 | 250.24 | 700.35 | 225.32 | 0.00 | 0.00 | 0.00 |
May | 470.91 | 204.19 | 266.71 | 890.39 | 65.67 | 0.00 | 0.00 | 0.00 |
June | 477.58 | 189.39 | 288.18 | 941.57 | 48.25 | 0.00 | 0.00 | 0.00 |
July | 460.45 | 168.50 | 291.95 | 912.47 | 25.69 | 0.00 | 0.00 | 0.00 |
August | 424.29 | 145.88 | 278.42 | 841.27 | 37.17 | 0.00 | 0.00 | 0.00 |
September | 375.85 | 129.21 | 246.63 | 701.56 | 76.78 | 0.00 | 0.00 | 0.00 |
October | 371.41 | 156.73 | 214.68 | 653.38 | 141.50 | 0.00 | 0.00 | 0.00 |
November | 328.83 | 167.75 | 161.08 | 441.17 | 329.49 | 0.00 | 0.00 | 0.00 |
December | 258.90 | 117.28 | 141.63 | 300.17 | 451.58 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 392.90 | 168.18 | 224.72 | 642.61 | 225.95 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 258.90 | 117.28 | 141.63 | 300.17 | 25.69 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 477.58 | 206.63 | 291.95 | 941.57 | 515.91 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 317.83 | 161.84 | 155.99 | 350.15 | 515.90 | 0.00 | 0.00 | 0.00 |
February | 353.91 | 170.86 | 183.05 | 418.01 | 435.18 | 0.00 | 0.00 | 0.00 |
March | 416.31 | 200.78 | 215.54 | 546.02 | 371.83 | 0.00 | 0.00 | 0.00 |
April | 456.86 | 206.62 | 250.23 | 700.34 | 225.31 | 0.00 | 0.00 | 0.00 |
May | 470.90 | 204.19 | 266.71 | 890.38 | 65.67 | 0.00 | 0.00 | 0.00 |
June | 477.57 | 189.39 | 288.18 | 941.55 | 48.25 | 0.00 | 0.00 | 0.00 |
July | 460.44 | 168.50 | 291.95 | 912.46 | 25.69 | 0.00 | 0.00 | 0.00 |
August | 424.28 | 145.87 | 278.41 | 841.25 | 37.17 | 0.00 | 0.00 | 0.00 |
September | 375.84 | 129.21 | 246.63 | 701.54 | 76.78 | 0.00 | 0.00 | 0.00 |
October | 371.41 | 156.73 | 214.67 | 653.36 | 141.50 | 0.00 | 0.00 | 0.00 |
November | 328.83 | 167.75 | 161.08 | 441.16 | 329.48 | 0.00 | 0.00 | 0.00 |
December | 258.90 | 117.28 | 141.62 | 300.17 | 451.57 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 392.89 | 168.18 | 224.71 | 642.60 | 225.94 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 258.90 | 117.28 | 141.62 | 300.17 | 25.69 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 477.57 | 206.62 | 291.95 | 941.55 | 515.90 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 642.46 | 458.18 | 184.27 | 894.68 | 458.17 | 0.00 | 0.00 | 0.00 |
February | 582.67 | 377.15 | 205.52 | 827.73 | 397.15 | 0.00 | 0.00 | 0.00 |
March | 371.99 | 167.88 | 204.11 | 542.84 | 355.95 | 0.00 | 0.00 | 0.00 |
April | 275.71 | 64.61 | 211.11 | 449.72 | 228.09 | 0.00 | 0.00 | 0.00 |
May | 210.67 | 8.95 | 201.71 | 443.93 | 63.87 | 0.00 | 0.00 | 0.00 |
June | 208.10 | 1.94 | 206.16 | 455.59 | 51.42 | 0.00 | 0.00 | 0.00 |
July | 217.85 | 4.00 | 213.84 | 472.14 | 31.25 | 0.00 | 0.00 | 0.00 |
August | 256.29 | 30.76 | 225.53 | 555.15 | 48.57 | 0.00 | 0.00 | 0.00 |
September | 307.50 | 81.04 | 226.46 | 610.66 | 78.98 | 0.00 | 0.00 | 0.00 |
October | 477.09 | 248.52 | 228.57 | 864.90 | 145.71 | 0.00 | 0.00 | 0.00 |
November | 607.13 | 418.02 | 189.11 | 928.89 | 312.37 | 0.00 | 0.00 | 0.00 |
December | 627.76 | 450.82 | 176.94 | 913.66 | 415.90 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 397.80 | 191.70 | 206.09 | 662.54 | 214.65 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 208.10 | 1.94 | 176.94 | 443.93 | 31.25 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 642.46 | 458.18 | 228.57 | 928.89 | 458.17 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 642.46 | 458.18 | 184.27 | 894.68 | 458.17 | 0.00 | 0.00 | 0.00 |
February | 582.67 | 377.15 | 205.52 | 827.73 | 397.15 | 0.00 | 0.00 | 0.00 |
March | 371.99 | 167.88 | 204.11 | 542.84 | 355.95 | 0.00 | 0.00 | 0.00 |
April | 275.71 | 64.61 | 211.11 | 449.72 | 228.09 | 0.00 | 0.00 | 0.00 |
May | 210.67 | 8.95 | 201.71 | 443.93 | 63.87 | 0.00 | 0.00 | 0.00 |
June | 208.10 | 1.94 | 206.16 | 455.59 | 51.42 | 0.00 | 0.00 | 0.00 |
July | 217.85 | 4.00 | 213.84 | 472.14 | 31.25 | 0.00 | 0.00 | 0.00 |
August | 256.29 | 30.76 | 225.53 | 555.15 | 48.57 | 0.00 | 0.00 | 0.00 |
September | 307.50 | 81.04 | 226.46 | 610.66 | 78.98 | 0.00 | 0.00 | 0.00 |
October | 477.09 | 248.52 | 228.57 | 864.90 | 145.71 | 0.00 | 0.00 | 0.00 |
November | 607.13 | 418.02 | 189.11 | 928.89 | 312.37 | 0.00 | 0.00 | 0.00 |
December | 627.76 | 450.82 | 176.94 | 913.65 | 415.90 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 397.80 | 191.70 | 206.09 | 662.54 | 214.65 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 208.10 | 1.94 | 176.94 | 443.93 | 31.25 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 642.46 | 458.18 | 228.57 | 928.89 | 458.17 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 642.46 | 458.18 | 184.27 | 894.68 | 458.17 | 0.00 | 0.00 | 0.00 |
February | 582.67 | 377.15 | 205.52 | 827.73 | 397.15 | 0.00 | 0.00 | 0.00 |
March | 371.99 | 167.88 | 204.11 | 542.84 | 355.95 | 0.00 | 0.00 | 0.00 |
April | 275.71 | 64.61 | 211.11 | 449.72 | 228.09 | 0.00 | 0.00 | 0.00 |
May | 210.67 | 8.95 | 201.71 | 443.93 | 63.87 | 0.00 | 0.00 | 0.00 |
June | 208.10 | 1.94 | 206.16 | 455.59 | 51.42 | 0.00 | 0.00 | 0.00 |
July | 217.85 | 4.00 | 213.84 | 472.14 | 31.25 | 0.00 | 0.00 | 0.00 |
August | 256.29 | 30.76 | 225.53 | 555.15 | 48.57 | 0.00 | 0.00 | 0.00 |
September | 307.50 | 81.04 | 226.46 | 610.66 | 78.98 | 0.00 | 0.00 | 0.00 |
October | 477.09 | 248.52 | 228.57 | 864.90 | 145.71 | 0.00 | 0.00 | 0.00 |
November | 607.13 | 418.02 | 189.11 | 928.89 | 312.37 | 0.00 | 0.00 | 0.00 |
December | 627.76 | 450.82 | 176.94 | 913.66 | 415.90 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 397.80 | 191.70 | 206.09 | 662.54 | 214.65 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 208.10 | 1.94 | 176.94 | 443.93 | 31.25 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 642.46 | 458.18 | 228.57 | 928.89 | 458.17 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 642.46 | 458.18 | 184.27 | 894.68 | 458.17 | 0.00 | 0.00 | 0.00 |
February | 582.67 | 377.15 | 205.52 | 827.73 | 397.15 | 0.00 | 0.00 | 0.00 |
March | 371.99 | 167.88 | 204.11 | 542.84 | 355.95 | 0.00 | 0.00 | 0.00 |
April | 275.71 | 64.61 | 211.11 | 449.72 | 228.09 | 0.00 | 0.00 | 0.00 |
May | 210.67 | 8.95 | 201.71 | 443.93 | 63.87 | 0.00 | 0.00 | 0.00 |
June | 208.10 | 1.94 | 206.16 | 455.59 | 51.42 | 0.00 | 0.00 | 0.00 |
July | 217.85 | 4.00 | 213.84 | 472.14 | 31.25 | 0.00 | 0.00 | 0.00 |
August | 256.29 | 30.76 | 225.53 | 555.15 | 48.57 | 0.00 | 0.00 | 0.00 |
September | 307.50 | 81.04 | 226.46 | 610.66 | 78.98 | 0.00 | 0.00 | 0.00 |
October | 477.09 | 248.52 | 228.57 | 864.90 | 145.71 | 0.00 | 0.00 | 0.00 |
November | 607.13 | 418.02 | 189.11 | 928.89 | 312.37 | 0.00 | 0.00 | 0.00 |
December | 627.76 | 450.82 | 176.94 | 913.65 | 415.90 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 397.80 | 191.70 | 206.09 | 662.54 | 214.65 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 208.10 | 1.94 | 176.94 | 443.93 | 31.25 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 642.46 | 458.18 | 228.57 | 928.89 | 458.17 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 642.43 | 458.16 | 184.27 | 894.64 | 458.16 | 0.00 | 0.00 | 0.00 |
February | 582.65 | 377.14 | 205.51 | 827.70 | 397.14 | 0.00 | 0.00 | 0.00 |
March | 371.98 | 167.87 | 204.10 | 542.82 | 355.94 | 0.00 | 0.00 | 0.00 |
April | 275.70 | 64.60 | 211.10 | 449.70 | 228.09 | 0.00 | 0.00 | 0.00 |
May | 210.66 | 8.95 | 201.70 | 443.91 | 63.86 | 0.00 | 0.00 | 0.00 |
June | 208.09 | 1.94 | 206.15 | 455.57 | 51.42 | 0.00 | 0.00 | 0.00 |
July | 217.84 | 4.00 | 213.84 | 472.12 | 31.25 | 0.00 | 0.00 | 0.00 |
August | 256.28 | 30.76 | 225.52 | 555.13 | 48.56 | 0.00 | 0.00 | 0.00 |
September | 307.49 | 81.04 | 226.45 | 610.64 | 78.97 | 0.00 | 0.00 | 0.00 |
October | 477.07 | 248.51 | 228.56 | 864.86 | 145.70 | 0.00 | 0.00 | 0.00 |
November | 607.11 | 418.00 | 189.11 | 928.85 | 312.35 | 0.00 | 0.00 | 0.00 |
December | 627.73 | 450.80 | 176.93 | 913.62 | 415.89 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 397.78 | 191.69 | 206.09 | 662.52 | 214.64 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 208.09 | 1.94 | 176.93 | 443.91 | 31.25 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 642.43 | 458.16 | 228.56 | 928.85 | 458.16 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 338.06 | 182.81 | 155.26 | 402.46 | 583.36 | 0.00 | 0.00 | 0.00 |
February | 382.76 | 193.73 | 189.03 | 470.17 | 521.91 | 0.00 | 0.00 | 0.00 |
March | 377.25 | 167.00 | 210.25 | 482.60 | 468.14 | 0.00 | 0.00 | 0.00 |
April | 468.56 | 215.55 | 253.01 | 699.84 | 310.28 | 0.00 | 0.00 | 0.00 |
May | 389.66 | 126.93 | 262.73 | 746.48 | 93.86 | 0.00 | 0.00 | 0.00 |
June | 432.87 | 151.78 | 281.08 | 843.74 | 84.15 | 0.00 | 0.00 | 0.00 |
July | 395.13 | 109.60 | 285.53 | 762.91 | 63.09 | 0.00 | 0.00 | 0.00 |
August | 399.53 | 122.30 | 277.23 | 766.67 | 92.06 | 0.00 | 0.00 | 0.00 |
September | 367.90 | 126.21 | 241.69 | 680.55 | 108.08 | 0.00 | 0.00 | 0.00 |
October | 376.65 | 162.75 | 213.90 | 658.34 | 193.20 | 0.00 | 0.00 | 0.00 |
November | 322.83 | 162.24 | 160.59 | 441.10 | 424.77 | 0.00 | 0.00 | 0.00 |
December | 310.54 | 165.14 | 145.40 | 380.36 | 569.25 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 379.93 | 156.80 | 223.13 | 611.83 | 291.46 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 310.54 | 109.60 | 145.40 | 380.36 | 63.09 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 468.56 | 215.55 | 285.53 | 843.74 | 583.36 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 338.06 | 182.81 | 155.26 | 402.46 | 583.36 | 0.00 | 0.00 | 0.00 |
February | 382.76 | 193.73 | 189.03 | 470.17 | 521.91 | 0.00 | 0.00 | 0.00 |
March | 377.25 | 167.00 | 210.25 | 482.60 | 468.14 | 0.00 | 0.00 | 0.00 |
April | 468.56 | 215.55 | 253.01 | 699.84 | 310.28 | 0.00 | 0.00 | 0.00 |
May | 389.66 | 126.93 | 262.73 | 746.48 | 93.86 | 0.00 | 0.00 | 0.00 |
June | 432.87 | 151.78 | 281.08 | 843.74 | 84.15 | 0.00 | 0.00 | 0.00 |
July | 395.13 | 109.60 | 285.53 | 762.91 | 63.09 | 0.00 | 0.00 | 0.00 |
August | 399.53 | 122.30 | 277.23 | 766.67 | 92.06 | 0.00 | 0.00 | 0.00 |
September | 367.90 | 126.21 | 241.69 | 680.55 | 108.08 | 0.00 | 0.00 | 0.00 |
October | 376.65 | 162.75 | 213.90 | 658.34 | 193.20 | 0.00 | 0.00 | 0.00 |
November | 322.83 | 162.24 | 160.59 | 441.10 | 424.77 | 0.00 | 0.00 | 0.00 |
December | 310.54 | 165.14 | 145.40 | 380.36 | 569.25 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 379.93 | 156.80 | 223.13 | 611.83 | 291.46 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 310.54 | 109.60 | 145.40 | 380.36 | 63.09 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 468.56 | 215.55 | 285.53 | 843.74 | 583.36 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 338.06 | 182.80 | 155.26 | 402.45 | 583.35 | 0.00 | 0.00 | 0.00 |
February | 382.76 | 193.73 | 189.03 | 470.16 | 521.90 | 0.00 | 0.00 | 0.00 |
March | 377.25 | 167.00 | 210.25 | 482.59 | 468.13 | 0.00 | 0.00 | 0.00 |
April | 468.55 | 215.54 | 253.01 | 699.82 | 310.27 | 0.00 | 0.00 | 0.00 |
May | 389.65 | 126.93 | 262.72 | 746.47 | 93.86 | 0.00 | 0.00 | 0.00 |
June | 432.86 | 151.78 | 281.08 | 843.73 | 84.15 | 0.00 | 0.00 | 0.00 |
July | 395.12 | 109.60 | 285.52 | 762.89 | 63.09 | 0.00 | 0.00 | 0.00 |
August | 399.52 | 122.30 | 277.22 | 766.65 | 92.06 | 0.00 | 0.00 | 0.00 |
September | 367.89 | 126.20 | 241.69 | 680.54 | 108.08 | 0.00 | 0.00 | 0.00 |
October | 376.64 | 162.74 | 213.90 | 658.33 | 193.20 | 0.00 | 0.00 | 0.00 |
November | 322.83 | 162.24 | 160.59 | 441.09 | 424.76 | 0.00 | 0.00 | 0.00 |
December | 310.53 | 165.14 | 145.40 | 380.36 | 569.24 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 379.92 | 156.79 | 223.13 | 611.81 | 291.46 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 310.53 | 109.60 | 145.40 | 380.36 | 63.09 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 468.55 | 215.54 | 285.52 | 843.73 | 583.35 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 555.73 | 0.00 | 555.73 | 395.04 | 2277.29 | 0.00 | 0.00 | 0.00 |
February | 655.63 | 0.00 | 655.63 | 532.11 | 1906.07 | 0.00 | 0.00 | 0.00 |
March | 760.59 | 0.00 | 760.59 | 770.89 | 1644.86 | 0.00 | 0.00 | 0.00 |
April | 897.66 | 3.68 | 893.98 | 1226.09 | 1019.35 | 0.00 | 0.00 | 0.00 |
May | 1016.77 | 37.19 | 979.58 | 2127.01 | 296.31 | 0.00 | 0.00 | 0.00 |
June | 1156.29 | 80.06 | 1076.22 | 2525.94 | 254.14 | 0.00 | 0.00 | 0.00 |
July | 1122.10 | 42.75 | 1079.35 | 2429.56 | 168.06 | 0.00 | 0.00 | 0.00 |
August | 1004.86 | 7.90 | 996.96 | 2201.97 | 236.61 | 0.00 | 0.00 | 0.00 |
September | 867.98 | 0.07 | 867.91 | 1740.47 | 336.41 | 0.00 | 0.00 | 0.00 |
October | 754.25 | 0.00 | 754.25 | 1397.53 | 636.92 | 0.00 | 0.00 | 0.00 |
November | 572.60 | 0.00 | 572.60 | 618.29 | 1441.11 | 0.00 | 0.00 | 0.00 |
December | 516.62 | 0.00 | 516.62 | 428.99 | 1945.91 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 824.25 | 14.35 | 809.90 | 1371.24 | 1009.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 516.62 | 0.00 | 516.62 | 395.04 | 168.06 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1156.29 | 80.06 | 1079.35 | 2525.94 | 2277.29 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 953.49 | 485.52 | 467.97 | 1086.89 | 1399.71 | 0.00 | 0.00 | 0.00 |
February | 1061.74 | 512.58 | 549.16 | 1286.68 | 1179.14 | 0.00 | 0.00 | 0.00 |
March | 1248.95 | 602.34 | 646.62 | 1647.76 | 1031.21 | 0.00 | 0.00 | 0.00 |
April | 1370.58 | 619.88 | 750.70 | 2084.99 | 666.84 | 0.00 | 0.00 | 0.00 |
May | 1412.70 | 612.57 | 800.13 | 2644.46 | 201.16 | 0.00 | 0.00 | 0.00 |
June | 1432.72 | 568.18 | 864.54 | 2797.36 | 169.88 | 0.00 | 0.00 | 0.00 |
July | 1381.34 | 505.50 | 875.85 | 2700.35 | 110.69 | 0.00 | 0.00 | 0.00 |
August | 1272.87 | 437.62 | 835.24 | 2490.02 | 157.75 | 0.00 | 0.00 | 0.00 |
September | 1127.52 | 387.64 | 739.89 | 2091.24 | 221.17 | 0.00 | 0.00 | 0.00 |
October | 1114.23 | 470.20 | 644.03 | 1946.71 | 412.12 | 0.00 | 0.00 | 0.00 |
November | 986.49 | 503.25 | 483.24 | 1340.46 | 901.84 | 0.00 | 0.00 | 0.00 |
December | 776.70 | 351.83 | 424.87 | 932.77 | 1220.78 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1178.68 | 504.53 | 674.15 | 1924.29 | 636.56 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 776.70 | 351.83 | 424.87 | 932.77 | 110.69 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1432.72 | 619.88 | 875.85 | 2797.36 | 1399.71 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 3212.24 | 2290.89 | 921.36 | 4431.61 | 2216.76 | 0.00 | 0.00 | 0.00 |
February | 2913.32 | 1885.75 | 1027.58 | 4111.77 | 1900.50 | 0.00 | 0.00 | 0.00 |
March | 1859.93 | 839.39 | 1020.54 | 2711.83 | 1670.95 | 0.00 | 0.00 | 0.00 |
April | 1378.56 | 323.03 | 1055.53 | 2255.94 | 1081.83 | 0.00 | 0.00 | 0.00 |
May | 1053.32 | 44.76 | 1008.55 | 2226.66 | 307.61 | 0.00 | 0.00 | 0.00 |
June | 1040.50 | 9.70 | 1030.80 | 2292.57 | 259.48 | 0.00 | 0.00 | 0.00 |
July | 1089.23 | 20.02 | 1069.21 | 2376.01 | 164.39 | 0.00 | 0.00 | 0.00 |
August | 1281.42 | 153.81 | 1127.61 | 2786.42 | 255.11 | 0.00 | 0.00 | 0.00 |
September | 1537.49 | 405.19 | 1132.30 | 3041.00 | 377.11 | 0.00 | 0.00 | 0.00 |
October | 2385.43 | 1242.58 | 1142.85 | 4292.21 | 715.41 | 0.00 | 0.00 | 0.00 |
November | 3035.62 | 2090.05 | 945.56 | 4617.48 | 1495.23 | 0.00 | 0.00 | 0.00 |
December | 3138.75 | 2254.09 | 884.67 | 4547.44 | 1969.06 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1988.95 | 958.50 | 1030.46 | 3303.77 | 1029.87 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 1040.50 | 9.70 | 884.67 | 2226.66 | 164.39 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 3212.24 | 2290.89 | 1142.85 | 4617.48 | 2216.76 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1014.18 | 548.41 | 465.77 | 1257.70 | 1535.44 | 0.00 | 0.00 | 0.00 |
February | 1148.28 | 581.19 | 567.09 | 1479.57 | 1313.02 | 0.00 | 0.00 | 0.00 |
March | 1131.75 | 501.00 | 630.75 | 1522.62 | 1142.48 | 0.00 | 0.00 | 0.00 |
April | 1405.66 | 646.63 | 759.03 | 2168.07 | 763.83 | 0.00 | 0.00 | 0.00 |
May | 1168.97 | 380.80 | 788.18 | 2262.61 | 243.46 | 0.00 | 0.00 | 0.00 |
June | 1298.59 | 455.35 | 843.25 | 2566.22 | 216.14 | 0.00 | 0.00 | 0.00 |
July | 1185.37 | 328.80 | 856.57 | 2346.41 | 148.02 | 0.00 | 0.00 | 0.00 |
August | 1198.56 | 366.90 | 831.67 | 2374.25 | 205.11 | 0.00 | 0.00 | 0.00 |
September | 1103.67 | 378.61 | 725.06 | 2065.91 | 267.15 | 0.00 | 0.00 | 0.00 |
October | 1129.93 | 488.23 | 641.70 | 2017.32 | 484.17 | 0.00 | 0.00 | 0.00 |
November | 968.49 | 486.72 | 481.77 | 1401.88 | 1016.26 | 0.00 | 0.00 | 0.00 |
December | 931.60 | 495.41 | 436.19 | 1228.59 | 1332.25 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1139.77 | 470.38 | 669.39 | 1892.56 | 719.14 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 931.60 | 328.80 | 436.19 | 1228.59 | 148.02 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1405.66 | 646.63 | 856.57 | 2566.22 | 1535.44 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 555.73 | 0.00 | 555.73 | 426.84 | 2111.56 | 0.00 | 0.00 | 0.00 |
February | 655.63 | 0.00 | 655.63 | 557.89 | 1764.63 | 0.00 | 0.00 | 0.00 |
March | 760.59 | 0.00 | 760.59 | 787.03 | 1551.81 | 0.00 | 0.00 | 0.00 |
April | 897.66 | 3.68 | 893.98 | 1222.85 | 987.37 | 0.00 | 0.00 | 0.00 |
May | 1016.77 | 37.19 | 979.58 | 2090.78 | 311.91 | 0.00 | 0.00 | 0.00 |
June | 1156.29 | 80.06 | 1076.22 | 2483.49 | 271.17 | 0.00 | 0.00 | 0.00 |
July | 1122.10 | 42.75 | 1079.35 | 2381.96 | 184.30 | 0.00 | 0.00 | 0.00 |
August | 1004.86 | 7.90 | 996.96 | 2163.79 | 251.73 | 0.00 | 0.00 | 0.00 |
September | 867.98 | 0.07 | 867.91 | 1707.42 | 343.89 | 0.00 | 0.00 | 0.00 |
October | 754.25 | 0.00 | 754.25 | 1383.85 | 620.14 | 0.00 | 0.00 | 0.00 |
November | 572.60 | 0.00 | 572.60 | 644.89 | 1332.45 | 0.00 | 0.00 | 0.00 |
December | 516.62 | 0.00 | 516.62 | 455.16 | 1801.20 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 824.25 | 14.35 | 809.90 | 1363.70 | 956.90 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 516.62 | 0.00 | 516.62 | 426.84 | 184.30 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1156.29 | 80.06 | 1079.35 | 2483.49 | 2111.56 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 953.49 | 485.52 | 467.97 | 1121.98 | 1305.21 | 0.00 | 0.00 | 0.00 |
February | 1061.74 | 512.58 | 549.16 | 1312.20 | 1100.18 | 0.00 | 0.00 | 0.00 |
March | 1248.95 | 602.34 | 646.62 | 1655.38 | 984.93 | 0.00 | 0.00 | 0.00 |
April | 1370.58 | 619.88 | 750.70 | 2076.20 | 653.90 | 0.00 | 0.00 | 0.00 |
May | 1412.70 | 612.57 | 800.13 | 2615.39 | 212.07 | 0.00 | 0.00 | 0.00 |
June | 1432.72 | 568.18 | 864.54 | 2766.13 | 182.25 | 0.00 | 0.00 | 0.00 |
July | 1381.34 | 505.50 | 875.85 | 2666.37 | 121.18 | 0.00 | 0.00 | 0.00 |
August | 1272.87 | 437.62 | 835.24 | 2461.33 | 168.30 | 0.00 | 0.00 | 0.00 |
September | 1127.52 | 387.64 | 739.89 | 2066.65 | 227.39 | 0.00 | 0.00 | 0.00 |
October | 1114.23 | 470.20 | 644.03 | 1932.82 | 405.12 | 0.00 | 0.00 | 0.00 |
November | 986.49 | 503.25 | 483.24 | 1358.10 | 848.24 | 0.00 | 0.00 | 0.00 |
December | 776.70 | 351.83 | 424.87 | 955.87 | 1141.72 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1178.68 | 504.53 | 674.15 | 1919.01 | 610.01 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 776.70 | 351.83 | 424.87 | 955.87 | 121.18 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1432.72 | 619.88 | 875.85 | 2766.13 | 1305.21 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 3212.24 | 2290.89 | 921.36 | 4466.52 | 2071.85 | 0.00 | 0.00 | 0.00 |
February | 2913.32 | 1885.75 | 1027.58 | 4144.43 | 1772.34 | 0.00 | 0.00 | 0.00 |
March | 1859.93 | 839.39 | 1020.54 | 2723.94 | 1581.26 | 0.00 | 0.00 | 0.00 |
April | 1378.56 | 323.03 | 1055.53 | 2248.63 | 1047.50 | 0.00 | 0.00 | 0.00 |
May | 1053.32 | 44.76 | 1008.55 | 2192.99 | 321.22 | 0.00 | 0.00 | 0.00 |
June | 1040.50 | 9.70 | 1030.80 | 2255.05 | 275.23 | 0.00 | 0.00 | 0.00 |
July | 1089.23 | 20.02 | 1069.21 | 2330.87 | 177.56 | 0.00 | 0.00 | 0.00 |
August | 1281.42 | 153.81 | 1127.61 | 2748.90 | 268.72 | 0.00 | 0.00 | 0.00 |
September | 1537.49 | 405.19 | 1132.30 | 3009.77 | 382.81 | 0.00 | 0.00 | 0.00 |
October | 2385.43 | 1242.58 | 1142.85 | 4269.73 | 701.62 | 0.00 | 0.00 | 0.00 |
November | 3035.62 | 2090.05 | 945.56 | 4631.70 | 1414.59 | 0.00 | 0.00 | 0.00 |
December | 3138.75 | 2254.09 | 884.67 | 4571.51 | 1843.38 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1988.95 | 958.50 | 1030.46 | 3295.44 | 984.01 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 1040.50 | 9.70 | 884.67 | 2192.99 | 177.56 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 3212.24 | 2290.89 | 1142.85 | 4631.70 | 2071.85 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1014.18 | 548.41 | 465.77 | 1270.63 | 1446.23 | 0.00 | 0.00 | 0.00 |
February | 1148.28 | 581.19 | 567.09 | 1489.81 | 1233.47 | 0.00 | 0.00 | 0.00 |
March | 1131.75 | 501.00 | 630.75 | 1525.50 | 1088.93 | 0.00 | 0.00 | 0.00 |
April | 1405.66 | 646.63 | 759.03 | 2160.14 | 741.67 | 0.00 | 0.00 | 0.00 |
May | 1168.97 | 380.80 | 788.18 | 2241.06 | 250.05 | 0.00 | 0.00 | 0.00 |
June | 1298.59 | 455.35 | 843.25 | 2541.07 | 223.28 | 0.00 | 0.00 | 0.00 |
July | 1185.37 | 328.80 | 856.57 | 2319.11 | 153.90 | 0.00 | 0.00 | 0.00 |
August | 1198.56 | 366.90 | 831.67 | 2350.76 | 211.97 | 0.00 | 0.00 | 0.00 |
September | 1103.67 | 378.61 | 725.06 | 2048.35 | 268.42 | 0.00 | 0.00 | 0.00 |
October | 1129.93 | 488.23 | 641.70 | 2006.78 | 473.39 | 0.00 | 0.00 | 0.00 |
November | 968.49 | 486.72 | 481.77 | 1411.77 | 957.56 | 0.00 | 0.00 | 0.00 |
December | 931.60 | 495.41 | 436.19 | 1238.95 | 1254.48 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1139.77 | 470.38 | 669.39 | 1885.18 | 689.08 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 931.60 | 328.80 | 436.19 | 1238.95 | 153.90 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1405.66 | 646.63 | 856.57 | 2541.07 | 1446.23 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.297698E+09 | 0.00 | 0.297698E+09 | 0.173081E+09 | 0.138669E+10 |
February | 0.317224E+09 | 0.00 | 0.317224E+09 | 0.220502E+09 | 0.106711E+10 |
March | 0.407437E+09 | 0.00 | 0.407437E+09 | 0.372056E+09 | 0.100980E+10 |
April | 0.465353E+09 | 1909971.49 | 0.463443E+09 | 0.609604E+09 | 0.585844E+09 |
May | 0.544671E+09 | 19922820.22 | 0.524748E+09 | 0.113224E+10 | 0.167067E+09 |
June | 0.599426E+09 | 41505614.60 | 0.557921E+09 | 0.130303E+10 | 0.130408E+09 |
July | 0.601095E+09 | 22900612.59 | 0.578194E+09 | 0.129376E+10 | 85059959.82 |
August | 0.538291E+09 | 4233730.22 | 0.534058E+09 | 0.116492E+10 | 0.122513E+09 |
September | 0.449964E+09 | 34656.08 | 0.449929E+09 | 0.890677E+09 | 0.194493E+09 |
October | 0.404043E+09 | 0.00 | 0.404043E+09 | 0.729578E+09 | 0.379343E+09 |
November | 0.296839E+09 | 0.00 | 0.296839E+09 | 0.283077E+09 | 0.874664E+09 |
December | 0.276744E+09 | 0.00 | 0.276744E+09 | 0.187982E+09 | 0.123372E+10 |
Annual Sum or Average | 0.519878E+10 | 90507405.21 | 0.510828E+10 | 0.836052E+10 | 0.723672E+10 |
Minimum of Months | 0.276744E+09 | 0.00 | 0.276744E+09 | 0.173081E+09 | 85059959.82 |
Maximum of Months | 0.601095E+09 | 41505614.60 | 0.578194E+09 | 0.130303E+10 | 0.138669E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.297698E+09 | 0.00 | 0.297698E+09 | 0.173081E+09 | 0.138669E+10 |
February | 0.317223E+09 | 0.00 | 0.317223E+09 | 0.220502E+09 | 0.106711E+10 |
March | 0.407436E+09 | 0.00 | 0.407436E+09 | 0.372056E+09 | 0.100980E+10 |
April | 0.465353E+09 | 1909969.20 | 0.463443E+09 | 0.609604E+09 | 0.585844E+09 |
May | 0.544671E+09 | 19922796.32 | 0.524748E+09 | 0.113224E+10 | 0.167066E+09 |
June | 0.599426E+09 | 41505564.80 | 0.557920E+09 | 0.130303E+10 | 0.130408E+09 |
July | 0.601095E+09 | 22900585.11 | 0.578194E+09 | 0.129376E+10 | 85059859.46 |
August | 0.538291E+09 | 4233725.14 | 0.534057E+09 | 0.116492E+10 | 0.122513E+09 |
September | 0.449963E+09 | 34656.03 | 0.449929E+09 | 0.890676E+09 | 0.194493E+09 |
October | 0.404043E+09 | 0.00 | 0.404043E+09 | 0.729577E+09 | 0.379343E+09 |
November | 0.296838E+09 | 0.00 | 0.296838E+09 | 0.283077E+09 | 0.874664E+09 |
December | 0.276744E+09 | 0.00 | 0.276744E+09 | 0.187982E+09 | 0.123372E+10 |
Annual Sum or Average | 0.519878E+10 | 90507296.61 | 0.510827E+10 | 0.836051E+10 | 0.723671E+10 |
Minimum of Months | 0.276744E+09 | 0.00 | 0.276744E+09 | 0.173081E+09 | 85059859.46 |
Maximum of Months | 0.601095E+09 | 41505564.80 | 0.578194E+09 | 0.130303E+10 | 0.138669E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.297698E+09 | 0.00 | 0.297698E+09 | 0.173081E+09 | 0.138669E+10 |
February | 0.317224E+09 | 0.00 | 0.317224E+09 | 0.220502E+09 | 0.106711E+10 |
March | 0.407437E+09 | 0.00 | 0.407437E+09 | 0.372056E+09 | 0.100980E+10 |
April | 0.465353E+09 | 1909971.49 | 0.463443E+09 | 0.609604E+09 | 0.585844E+09 |
May | 0.544671E+09 | 19922820.22 | 0.524748E+09 | 0.113224E+10 | 0.167067E+09 |
June | 0.599426E+09 | 41505614.60 | 0.557921E+09 | 0.130303E+10 | 0.130408E+09 |
July | 0.601095E+09 | 22900612.59 | 0.578194E+09 | 0.129376E+10 | 85059959.82 |
August | 0.538291E+09 | 4233730.22 | 0.534058E+09 | 0.116492E+10 | 0.122513E+09 |
September | 0.449964E+09 | 34656.08 | 0.449929E+09 | 0.890677E+09 | 0.194493E+09 |
October | 0.404043E+09 | 0.00 | 0.404043E+09 | 0.729578E+09 | 0.379343E+09 |
November | 0.296839E+09 | 0.00 | 0.296839E+09 | 0.283077E+09 | 0.874664E+09 |
December | 0.276744E+09 | 0.00 | 0.276744E+09 | 0.187982E+09 | 0.123372E+10 |
Annual Sum or Average | 0.519878E+10 | 90507405.21 | 0.510828E+10 | 0.836052E+10 | 0.723672E+10 |
Minimum of Months | 0.276744E+09 | 0.00 | 0.276744E+09 | 0.173081E+09 | 85059959.82 |
Maximum of Months | 0.601095E+09 | 41505614.60 | 0.578194E+09 | 0.130303E+10 | 0.138669E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.297698E+09 | 0.00 | 0.297698E+09 | 0.173081E+09 | 0.138669E+10 |
February | 0.317223E+09 | 0.00 | 0.317223E+09 | 0.220502E+09 | 0.106711E+10 |
March | 0.407436E+09 | 0.00 | 0.407436E+09 | 0.372056E+09 | 0.100980E+10 |
April | 0.465353E+09 | 1909969.20 | 0.463443E+09 | 0.609604E+09 | 0.585844E+09 |
May | 0.544671E+09 | 19922796.32 | 0.524748E+09 | 0.113224E+10 | 0.167066E+09 |
June | 0.599426E+09 | 41505564.80 | 0.557920E+09 | 0.130303E+10 | 0.130408E+09 |
July | 0.601095E+09 | 22900585.11 | 0.578194E+09 | 0.129376E+10 | 85059859.46 |
August | 0.538291E+09 | 4233725.14 | 0.534057E+09 | 0.116492E+10 | 0.122513E+09 |
September | 0.449963E+09 | 34656.03 | 0.449929E+09 | 0.890676E+09 | 0.194493E+09 |
October | 0.404043E+09 | 0.00 | 0.404043E+09 | 0.729577E+09 | 0.379343E+09 |
November | 0.296838E+09 | 0.00 | 0.296838E+09 | 0.283077E+09 | 0.874664E+09 |
December | 0.276744E+09 | 0.00 | 0.276744E+09 | 0.187982E+09 | 0.123372E+10 |
Annual Sum or Average | 0.519878E+10 | 90507296.61 | 0.510827E+10 | 0.836051E+10 | 0.723671E+10 |
Minimum of Months | 0.276744E+09 | 0.00 | 0.276744E+09 | 0.173081E+09 | 85059859.46 |
Maximum of Months | 0.601095E+09 | 41505564.80 | 0.578194E+09 | 0.130303E+10 | 0.138669E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.297686E+09 | 0.00 | 0.297686E+09 | 0.173074E+09 | 0.138663E+10 |
February | 0.317211E+09 | 0.00 | 0.317211E+09 | 0.220493E+09 | 0.106707E+10 |
March | 0.407420E+09 | 0.00 | 0.407420E+09 | 0.372041E+09 | 0.100976E+10 |
April | 0.465334E+09 | 1909894.51 | 0.463424E+09 | 0.609580E+09 | 0.585820E+09 |
May | 0.544649E+09 | 19922017.25 | 0.524727E+09 | 0.113220E+10 | 0.167060E+09 |
June | 0.599402E+09 | 41503941.74 | 0.557898E+09 | 0.130298E+10 | 0.130403E+09 |
July | 0.601071E+09 | 22899689.60 | 0.578171E+09 | 0.129371E+10 | 85056531.53 |
August | 0.538270E+09 | 4233559.59 | 0.534036E+09 | 0.116488E+10 | 0.122508E+09 |
September | 0.449946E+09 | 34654.68 | 0.449911E+09 | 0.890641E+09 | 0.194485E+09 |
October | 0.404027E+09 | 0.00 | 0.404027E+09 | 0.729548E+09 | 0.379328E+09 |
November | 0.296827E+09 | 0.00 | 0.296827E+09 | 0.283066E+09 | 0.874629E+09 |
December | 0.276733E+09 | 0.00 | 0.276733E+09 | 0.187975E+09 | 0.123367E+10 |
Annual Sum or Average | 0.519858E+10 | 90503757.36 | 0.510807E+10 | 0.836018E+10 | 0.723642E+10 |
Minimum of Months | 0.276733E+09 | 0.00 | 0.276733E+09 | 0.173074E+09 | 85056531.53 |
Maximum of Months | 0.601071E+09 | 41503941.74 | 0.578171E+09 | 0.130298E+10 | 0.138663E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.851282E+09 | 0.433476E+09 | 0.417806E+09 | 0.937849E+09 | 0.138182E+10 |
February | 0.856195E+09 | 0.413348E+09 | 0.442847E+09 | 0.101128E+10 | 0.105280E+10 |
March | 0.111508E+10 | 0.537772E+09 | 0.577306E+09 | 0.146250E+10 | 0.995927E+09 |
April | 0.118419E+10 | 0.535579E+09 | 0.648616E+09 | 0.181531E+10 | 0.584026E+09 |
May | 0.126127E+10 | 0.546912E+09 | 0.714361E+09 | 0.238483E+10 | 0.175883E+09 |
June | 0.123788E+10 | 0.490909E+09 | 0.746971E+09 | 0.244055E+10 | 0.125075E+09 |
July | 0.123328E+10 | 0.451313E+09 | 0.781963E+09 | 0.244397E+10 | 68805867.48 |
August | 0.113643E+10 | 0.390712E+09 | 0.745714E+09 | 0.225325E+10 | 99561894.67 |
September | 0.974191E+09 | 0.334924E+09 | 0.639268E+09 | 0.181844E+10 | 0.199009E+09 |
October | 0.994791E+09 | 0.419799E+09 | 0.574993E+09 | 0.175000E+10 | 0.379002E+09 |
November | 0.852333E+09 | 0.434809E+09 | 0.417524E+09 | 0.114352E+10 | 0.854035E+09 |
December | 0.693447E+09 | 0.314116E+09 | 0.379331E+09 | 0.803986E+09 | 0.120951E+10 |
Annual Sum or Average | 0.123904E+11 | 0.530367E+10 | 0.708670E+10 | 0.202655E+11 | 0.712546E+10 |
Minimum of Months | 0.693447E+09 | 0.314116E+09 | 0.379331E+09 | 0.803986E+09 | 68805867.48 |
Maximum of Months | 0.126127E+10 | 0.546912E+09 | 0.781963E+09 | 0.244397E+10 | 0.138182E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.851282E+09 | 0.433476E+09 | 0.417806E+09 | 0.937849E+09 | 0.138182E+10 |
February | 0.856195E+09 | 0.413348E+09 | 0.442847E+09 | 0.101128E+10 | 0.105280E+10 |
March | 0.111508E+10 | 0.537772E+09 | 0.577306E+09 | 0.146250E+10 | 0.995927E+09 |
April | 0.118419E+10 | 0.535579E+09 | 0.648616E+09 | 0.181531E+10 | 0.584026E+09 |
May | 0.126127E+10 | 0.546912E+09 | 0.714361E+09 | 0.238483E+10 | 0.175883E+09 |
June | 0.123788E+10 | 0.490909E+09 | 0.746971E+09 | 0.244055E+10 | 0.125075E+09 |
July | 0.123328E+10 | 0.451313E+09 | 0.781963E+09 | 0.244397E+10 | 68805867.48 |
August | 0.113643E+10 | 0.390712E+09 | 0.745714E+09 | 0.225325E+10 | 99561894.67 |
September | 0.974191E+09 | 0.334924E+09 | 0.639268E+09 | 0.181844E+10 | 0.199009E+09 |
October | 0.994791E+09 | 0.419799E+09 | 0.574993E+09 | 0.175000E+10 | 0.379002E+09 |
November | 0.852333E+09 | 0.434809E+09 | 0.417524E+09 | 0.114352E+10 | 0.854035E+09 |
December | 0.693447E+09 | 0.314116E+09 | 0.379331E+09 | 0.803986E+09 | 0.120951E+10 |
Annual Sum or Average | 0.123904E+11 | 0.530367E+10 | 0.708670E+10 | 0.202655E+11 | 0.712546E+10 |
Minimum of Months | 0.693447E+09 | 0.314116E+09 | 0.379331E+09 | 0.803986E+09 | 68805867.48 |
Maximum of Months | 0.126127E+10 | 0.546912E+09 | 0.781963E+09 | 0.244397E+10 | 0.138182E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.851266E+09 | 0.433468E+09 | 0.417798E+09 | 0.937832E+09 | 0.138180E+10 |
February | 0.856179E+09 | 0.413341E+09 | 0.442839E+09 | 0.101126E+10 | 0.105278E+10 |
March | 0.111506E+10 | 0.537762E+09 | 0.577296E+09 | 0.146247E+10 | 0.995908E+09 |
April | 0.118417E+10 | 0.535569E+09 | 0.648604E+09 | 0.181528E+10 | 0.584016E+09 |
May | 0.126125E+10 | 0.546902E+09 | 0.714348E+09 | 0.238479E+10 | 0.175880E+09 |
June | 0.123786E+10 | 0.490900E+09 | 0.746957E+09 | 0.244050E+10 | 0.125073E+09 |
July | 0.123325E+10 | 0.451304E+09 | 0.781949E+09 | 0.244393E+10 | 68804610.24 |
August | 0.113640E+10 | 0.390705E+09 | 0.745700E+09 | 0.225321E+10 | 99560075.46 |
September | 0.974174E+09 | 0.334918E+09 | 0.639256E+09 | 0.181840E+10 | 0.199005E+09 |
October | 0.994773E+09 | 0.419791E+09 | 0.574982E+09 | 0.174997E+10 | 0.378995E+09 |
November | 0.852317E+09 | 0.434801E+09 | 0.417517E+09 | 0.114350E+10 | 0.854020E+09 |
December | 0.693435E+09 | 0.314111E+09 | 0.379324E+09 | 0.803972E+09 | 0.120949E+10 |
Annual Sum or Average | 0.123901E+11 | 0.530357E+10 | 0.708657E+10 | 0.202651E+11 | 0.712533E+10 |
Minimum of Months | 0.693435E+09 | 0.314111E+09 | 0.379324E+09 | 0.803972E+09 | 68804610.24 |
Maximum of Months | 0.126125E+10 | 0.546902E+09 | 0.781949E+09 | 0.244393E+10 | 0.138180E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.172076E+10 | 0.122720E+10 | 0.493558E+09 | 0.239631E+10 | 0.122718E+10 |
February | 0.140960E+10 | 0.912410E+09 | 0.497190E+09 | 0.200245E+10 | 0.960792E+09 |
March | 0.996339E+09 | 0.449649E+09 | 0.546690E+09 | 0.145394E+10 | 0.953381E+09 |
April | 0.714652E+09 | 0.167461E+09 | 0.547192E+09 | 0.116567E+10 | 0.591221E+09 |
May | 0.564247E+09 | 23979722.50 | 0.540268E+09 | 0.118901E+10 | 0.171062E+09 |
June | 0.539400E+09 | 5027726.94 | 0.534372E+09 | 0.118090E+10 | 0.133293E+09 |
July | 0.583486E+09 | 10724417.16 | 0.572762E+09 | 0.126457E+10 | 83705659.32 |
August | 0.686441E+09 | 82393578.25 | 0.604047E+09 | 0.148691E+10 | 0.130078E+09 |
September | 0.797046E+09 | 0.210055E+09 | 0.586990E+09 | 0.158284E+10 | 0.204705E+09 |
October | 0.127784E+10 | 0.665636E+09 | 0.612208E+09 | 0.231654E+10 | 0.390257E+09 |
November | 0.157368E+10 | 0.108350E+10 | 0.490186E+09 | 0.240769E+10 | 0.809652E+09 |
December | 0.168139E+10 | 0.120748E+10 | 0.473905E+09 | 0.244714E+10 | 0.111396E+10 |
Annual Sum or Average | 0.125449E+11 | 0.604551E+10 | 0.649937E+10 | 0.208940E+11 | 0.676928E+10 |
Minimum of Months | 0.539400E+09 | 5027726.94 | 0.473905E+09 | 0.116567E+10 | 83705659.32 |
Maximum of Months | 0.172076E+10 | 0.122720E+10 | 0.612208E+09 | 0.244714E+10 | 0.122718E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.172075E+10 | 0.122720E+10 | 0.493558E+09 | 0.239631E+10 | 0.122718E+10 |
February | 0.140960E+10 | 0.912409E+09 | 0.497189E+09 | 0.200244E+10 | 0.960792E+09 |
March | 0.996338E+09 | 0.449648E+09 | 0.546689E+09 | 0.145394E+10 | 0.953381E+09 |
April | 0.714652E+09 | 0.167460E+09 | 0.547191E+09 | 0.116566E+10 | 0.591220E+09 |
May | 0.564247E+09 | 23979693.73 | 0.540267E+09 | 0.118901E+10 | 0.171062E+09 |
June | 0.539399E+09 | 5027720.91 | 0.534372E+09 | 0.118089E+10 | 0.133293E+09 |
July | 0.583486E+09 | 10724404.29 | 0.572762E+09 | 0.126457E+10 | 83705563.11 |
August | 0.686440E+09 | 82393479.38 | 0.604047E+09 | 0.148691E+10 | 0.130077E+09 |
September | 0.797045E+09 | 0.210055E+09 | 0.586990E+09 | 0.158284E+10 | 0.204704E+09 |
October | 0.127784E+10 | 0.665635E+09 | 0.612208E+09 | 0.231654E+10 | 0.390257E+09 |
November | 0.157368E+10 | 0.108350E+10 | 0.490185E+09 | 0.240768E+10 | 0.809652E+09 |
December | 0.168139E+10 | 0.120748E+10 | 0.473904E+09 | 0.244713E+10 | 0.111396E+10 |
Annual Sum or Average | 0.125449E+11 | 0.604551E+10 | 0.649936E+10 | 0.208939E+11 | 0.676928E+10 |
Minimum of Months | 0.539399E+09 | 5027720.91 | 0.473904E+09 | 0.116566E+10 | 83705563.11 |
Maximum of Months | 0.172075E+10 | 0.122720E+10 | 0.612208E+09 | 0.244713E+10 | 0.122718E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.172076E+10 | 0.122720E+10 | 0.493558E+09 | 0.239631E+10 | 0.122718E+10 |
February | 0.140960E+10 | 0.912410E+09 | 0.497190E+09 | 0.200245E+10 | 0.960792E+09 |
March | 0.996339E+09 | 0.449649E+09 | 0.546690E+09 | 0.145394E+10 | 0.953381E+09 |
April | 0.714652E+09 | 0.167461E+09 | 0.547192E+09 | 0.116567E+10 | 0.591221E+09 |
May | 0.564247E+09 | 23979722.50 | 0.540268E+09 | 0.118901E+10 | 0.171062E+09 |
June | 0.539400E+09 | 5027726.94 | 0.534372E+09 | 0.118090E+10 | 0.133293E+09 |
July | 0.583486E+09 | 10724417.16 | 0.572762E+09 | 0.126457E+10 | 83705659.32 |
August | 0.686441E+09 | 82393578.25 | 0.604047E+09 | 0.148691E+10 | 0.130078E+09 |
September | 0.797046E+09 | 0.210055E+09 | 0.586990E+09 | 0.158284E+10 | 0.204705E+09 |
October | 0.127784E+10 | 0.665636E+09 | 0.612208E+09 | 0.231654E+10 | 0.390257E+09 |
November | 0.157368E+10 | 0.108350E+10 | 0.490186E+09 | 0.240769E+10 | 0.809652E+09 |
December | 0.168139E+10 | 0.120748E+10 | 0.473905E+09 | 0.244714E+10 | 0.111396E+10 |
Annual Sum or Average | 0.125449E+11 | 0.604551E+10 | 0.649937E+10 | 0.208940E+11 | 0.676928E+10 |
Minimum of Months | 0.539400E+09 | 5027726.94 | 0.473905E+09 | 0.116567E+10 | 83705659.32 |
Maximum of Months | 0.172076E+10 | 0.122720E+10 | 0.612208E+09 | 0.244714E+10 | 0.122718E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.172075E+10 | 0.122720E+10 | 0.493558E+09 | 0.239631E+10 | 0.122718E+10 |
February | 0.140960E+10 | 0.912409E+09 | 0.497189E+09 | 0.200244E+10 | 0.960792E+09 |
March | 0.996338E+09 | 0.449648E+09 | 0.546689E+09 | 0.145394E+10 | 0.953381E+09 |
April | 0.714652E+09 | 0.167460E+09 | 0.547191E+09 | 0.116566E+10 | 0.591220E+09 |
May | 0.564247E+09 | 23979693.73 | 0.540267E+09 | 0.118901E+10 | 0.171062E+09 |
June | 0.539399E+09 | 5027720.91 | 0.534372E+09 | 0.118089E+10 | 0.133293E+09 |
July | 0.583486E+09 | 10724404.29 | 0.572762E+09 | 0.126457E+10 | 83705563.11 |
August | 0.686440E+09 | 82393479.38 | 0.604047E+09 | 0.148691E+10 | 0.130077E+09 |
September | 0.797045E+09 | 0.210055E+09 | 0.586990E+09 | 0.158284E+10 | 0.204704E+09 |
October | 0.127784E+10 | 0.665635E+09 | 0.612208E+09 | 0.231654E+10 | 0.390257E+09 |
November | 0.157368E+10 | 0.108350E+10 | 0.490185E+09 | 0.240768E+10 | 0.809652E+09 |
December | 0.168139E+10 | 0.120748E+10 | 0.473904E+09 | 0.244713E+10 | 0.111396E+10 |
Annual Sum or Average | 0.125449E+11 | 0.604551E+10 | 0.649936E+10 | 0.208939E+11 | 0.676928E+10 |
Minimum of Months | 0.539399E+09 | 5027720.91 | 0.473904E+09 | 0.116566E+10 | 83705563.11 |
Maximum of Months | 0.172075E+10 | 0.122720E+10 | 0.612208E+09 | 0.244713E+10 | 0.122718E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.172069E+10 | 0.122715E+10 | 0.493538E+09 | 0.239621E+10 | 0.122713E+10 |
February | 0.140954E+10 | 0.912373E+09 | 0.497170E+09 | 0.200237E+10 | 0.960754E+09 |
March | 0.996299E+09 | 0.449631E+09 | 0.546668E+09 | 0.145388E+10 | 0.953343E+09 |
April | 0.714623E+09 | 0.167454E+09 | 0.547169E+09 | 0.116562E+10 | 0.591197E+09 |
May | 0.564225E+09 | 23978756.02 | 0.540246E+09 | 0.118896E+10 | 0.171055E+09 |
June | 0.539378E+09 | 5027524.30 | 0.534351E+09 | 0.118085E+10 | 0.133288E+09 |
July | 0.583463E+09 | 10723984.92 | 0.572739E+09 | 0.126452E+10 | 83702285.62 |
August | 0.686413E+09 | 82390257.42 | 0.604023E+09 | 0.148685E+10 | 0.130073E+09 |
September | 0.797014E+09 | 0.210047E+09 | 0.586967E+09 | 0.158277E+10 | 0.204696E+09 |
October | 0.127779E+10 | 0.665609E+09 | 0.612184E+09 | 0.231645E+10 | 0.390242E+09 |
November | 0.157362E+10 | 0.108345E+10 | 0.490166E+09 | 0.240759E+10 | 0.809620E+09 |
December | 0.168132E+10 | 0.120743E+10 | 0.473886E+09 | 0.244704E+10 | 0.111391E+10 |
Annual Sum or Average | 0.125444E+11 | 0.604527E+10 | 0.649911E+10 | 0.208931E+11 | 0.676901E+10 |
Minimum of Months | 0.539378E+09 | 5027524.30 | 0.473886E+09 | 0.116562E+10 | 83702285.62 |
Maximum of Months | 0.172069E+10 | 0.122715E+10 | 0.612184E+09 | 0.244704E+10 | 0.122713E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.905472E+09 | 0.489629E+09 | 0.415843E+09 | 0.107795E+10 | 0.156248E+10 |
February | 0.925983E+09 | 0.468675E+09 | 0.457308E+09 | 0.113744E+10 | 0.126261E+10 |
March | 0.101043E+10 | 0.447294E+09 | 0.563141E+09 | 0.129261E+10 | 0.125385E+10 |
April | 0.121450E+10 | 0.558694E+09 | 0.655809E+09 | 0.181397E+10 | 0.804247E+09 |
May | 0.104367E+10 | 0.339977E+09 | 0.703692E+09 | 0.199938E+10 | 0.251387E+09 |
June | 0.112200E+10 | 0.393425E+09 | 0.728572E+09 | 0.218699E+10 | 0.218111E+09 |
July | 0.105831E+10 | 0.293559E+09 | 0.764753E+09 | 0.204337E+10 | 0.168976E+09 |
August | 0.107009E+10 | 0.327569E+09 | 0.742520E+09 | 0.205344E+10 | 0.246567E+09 |
September | 0.953584E+09 | 0.327125E+09 | 0.626459E+09 | 0.176400E+10 | 0.280146E+09 |
October | 0.100882E+10 | 0.435898E+09 | 0.572918E+09 | 0.176330E+10 | 0.517470E+09 |
November | 0.836783E+09 | 0.420533E+09 | 0.416249E+09 | 0.114332E+10 | 0.110099E+10 |
December | 0.831744E+09 | 0.442310E+09 | 0.389434E+09 | 0.101876E+10 | 0.152469E+10 |
Annual Sum or Average | 0.119814E+11 | 0.494469E+10 | 0.703670E+10 | 0.192945E+11 | 0.919153E+10 |
Minimum of Months | 0.831744E+09 | 0.293559E+09 | 0.389434E+09 | 0.101876E+10 | 0.168976E+09 |
Maximum of Months | 0.121450E+10 | 0.558694E+09 | 0.764753E+09 | 0.218699E+10 | 0.156248E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.905472E+09 | 0.489629E+09 | 0.415843E+09 | 0.107795E+10 | 0.156248E+10 |
February | 0.925983E+09 | 0.468675E+09 | 0.457308E+09 | 0.113744E+10 | 0.126261E+10 |
March | 0.101043E+10 | 0.447294E+09 | 0.563141E+09 | 0.129261E+10 | 0.125385E+10 |
April | 0.121450E+10 | 0.558694E+09 | 0.655809E+09 | 0.181397E+10 | 0.804247E+09 |
May | 0.104367E+10 | 0.339977E+09 | 0.703692E+09 | 0.199938E+10 | 0.251387E+09 |
June | 0.112200E+10 | 0.393425E+09 | 0.728572E+09 | 0.218699E+10 | 0.218111E+09 |
July | 0.105831E+10 | 0.293559E+09 | 0.764753E+09 | 0.204337E+10 | 0.168976E+09 |
August | 0.107009E+10 | 0.327569E+09 | 0.742520E+09 | 0.205344E+10 | 0.246567E+09 |
September | 0.953584E+09 | 0.327125E+09 | 0.626459E+09 | 0.176400E+10 | 0.280146E+09 |
October | 0.100882E+10 | 0.435898E+09 | 0.572918E+09 | 0.176330E+10 | 0.517470E+09 |
November | 0.836783E+09 | 0.420533E+09 | 0.416249E+09 | 0.114332E+10 | 0.110099E+10 |
December | 0.831744E+09 | 0.442310E+09 | 0.389434E+09 | 0.101876E+10 | 0.152469E+10 |
Annual Sum or Average | 0.119814E+11 | 0.494469E+10 | 0.703670E+10 | 0.192945E+11 | 0.919153E+10 |
Minimum of Months | 0.831744E+09 | 0.293559E+09 | 0.389434E+09 | 0.101876E+10 | 0.168976E+09 |
Maximum of Months | 0.121450E+10 | 0.558694E+09 | 0.764753E+09 | 0.218699E+10 | 0.156248E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.905455E+09 | 0.489620E+09 | 0.415835E+09 | 0.107793E+10 | 0.156245E+10 |
February | 0.925966E+09 | 0.468667E+09 | 0.457300E+09 | 0.113742E+10 | 0.126259E+10 |
March | 0.101042E+10 | 0.447286E+09 | 0.563130E+09 | 0.129258E+10 | 0.125383E+10 |
April | 0.121448E+10 | 0.558684E+09 | 0.655797E+09 | 0.181394E+10 | 0.804233E+09 |
May | 0.104365E+10 | 0.339971E+09 | 0.703679E+09 | 0.199935E+10 | 0.251383E+09 |
June | 0.112198E+10 | 0.393418E+09 | 0.728559E+09 | 0.218695E+10 | 0.218107E+09 |
July | 0.105829E+10 | 0.293554E+09 | 0.764739E+09 | 0.204333E+10 | 0.168973E+09 |
August | 0.107007E+10 | 0.327563E+09 | 0.742506E+09 | 0.205341E+10 | 0.246562E+09 |
September | 0.953567E+09 | 0.327119E+09 | 0.626448E+09 | 0.176397E+10 | 0.280141E+09 |
October | 0.100880E+10 | 0.435890E+09 | 0.572907E+09 | 0.176327E+10 | 0.517460E+09 |
November | 0.836768E+09 | 0.420526E+09 | 0.416242E+09 | 0.114330E+10 | 0.110097E+10 |
December | 0.831728E+09 | 0.442302E+09 | 0.389426E+09 | 0.101874E+10 | 0.152466E+10 |
Annual Sum or Average | 0.119812E+11 | 0.494460E+10 | 0.703657E+10 | 0.192942E+11 | 0.919136E+10 |
Minimum of Months | 0.831728E+09 | 0.293554E+09 | 0.389426E+09 | 0.101874E+10 | 0.168973E+09 |
Maximum of Months | 0.121448E+10 | 0.558684E+09 | 0.764739E+09 | 0.218695E+10 | 0.156245E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.148847E+10 | 0.00 | 0.148847E+10 | 0.105807E+10 | 0.609950E+10 |
February | 0.158610E+10 | 0.00 | 0.158610E+10 | 0.128729E+10 | 0.461116E+10 |
March | 0.203716E+10 | 0.00 | 0.203716E+10 | 0.206475E+10 | 0.440559E+10 |
April | 0.232674E+10 | 9549742.00 | 0.231719E+10 | 0.317803E+10 | 0.264214E+10 |
May | 0.272332E+10 | 99612896.60 | 0.262371E+10 | 0.569699E+10 | 0.793624E+09 |
June | 0.299710E+10 | 0.207526E+09 | 0.278957E+10 | 0.654725E+10 | 0.658742E+09 |
July | 0.300544E+10 | 0.114502E+09 | 0.289094E+10 | 0.650733E+10 | 0.450136E+09 |
August | 0.269142E+10 | 21168395.15 | 0.267026E+10 | 0.589774E+10 | 0.633727E+09 |
September | 0.224979E+10 | 173278.28 | 0.224962E+10 | 0.451130E+10 | 0.871976E+09 |
October | 0.202019E+10 | 0.00 | 0.202019E+10 | 0.374315E+10 | 0.170592E+10 |
November | 0.148418E+10 | 0.00 | 0.148418E+10 | 0.160261E+10 | 0.373536E+10 |
December | 0.138370E+10 | 0.00 | 0.138370E+10 | 0.114899E+10 | 0.521194E+10 |
Annual Sum or Average | 0.259936E+11 | 0.452532E+09 | 0.255411E+11 | 0.432435E+11 | 0.318198E+11 |
Minimum of Months | 0.138370E+10 | 0.00 | 0.138370E+10 | 0.105807E+10 | 0.450136E+09 |
Maximum of Months | 0.300544E+10 | 0.207526E+09 | 0.289094E+10 | 0.654725E+10 | 0.609950E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.255382E+10 | 0.130041E+10 | 0.125340E+10 | 0.291113E+10 | 0.374899E+10 |
February | 0.256856E+10 | 0.124003E+10 | 0.132853E+10 | 0.311274E+10 | 0.285256E+10 |
March | 0.334520E+10 | 0.161330E+10 | 0.173190E+10 | 0.441336E+10 | 0.276198E+10 |
April | 0.355255E+10 | 0.160672E+10 | 0.194583E+10 | 0.540429E+10 | 0.172844E+10 |
May | 0.378378E+10 | 0.164072E+10 | 0.214306E+10 | 0.708291E+10 | 0.538782E+09 |
June | 0.371360E+10 | 0.147271E+10 | 0.224089E+10 | 0.725076E+10 | 0.440335E+09 |
July | 0.369979E+10 | 0.135392E+10 | 0.234587E+10 | 0.723262E+10 | 0.296481E+09 |
August | 0.340924E+10 | 0.117212E+10 | 0.223712E+10 | 0.666927E+10 | 0.422526E+09 |
September | 0.292254E+10 | 0.100476E+10 | 0.191778E+10 | 0.542051E+10 | 0.573275E+09 |
October | 0.298434E+10 | 0.125938E+10 | 0.172496E+10 | 0.521407E+10 | 0.110383E+10 |
November | 0.255697E+10 | 0.130441E+10 | 0.125256E+10 | 0.347447E+10 | 0.233758E+10 |
December | 0.208032E+10 | 0.942340E+09 | 0.113798E+10 | 0.249834E+10 | 0.326973E+10 |
Annual Sum or Average | 0.371707E+11 | 0.159108E+11 | 0.212599E+11 | 0.606845E+11 | 0.200745E+11 |
Minimum of Months | 0.208032E+10 | 0.942340E+09 | 0.113798E+10 | 0.249834E+10 | 0.296481E+09 |
Maximum of Months | 0.378378E+10 | 0.164072E+10 | 0.234587E+10 | 0.725076E+10 | 0.374899E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.860368E+10 | 0.613591E+10 | 0.246776E+10 | 0.118696E+11 | 0.593738E+10 |
February | 0.704791E+10 | 0.456200E+10 | 0.248592E+10 | 0.994719E+10 | 0.459768E+10 |
March | 0.498163E+10 | 0.224822E+10 | 0.273342E+10 | 0.726336E+10 | 0.447547E+10 |
April | 0.357322E+10 | 0.837293E+09 | 0.273592E+10 | 0.584739E+10 | 0.280411E+10 |
May | 0.282120E+10 | 0.119897E+09 | 0.270131E+10 | 0.596389E+10 | 0.823892E+09 |
June | 0.269697E+10 | 25138330.74 | 0.267183E+10 | 0.594235E+10 | 0.672560E+09 |
July | 0.291740E+10 | 53621437.41 | 0.286378E+10 | 0.636390E+10 | 0.440293E+09 |
August | 0.343216E+10 | 0.411963E+09 | 0.302020E+10 | 0.746314E+10 | 0.683274E+09 |
September | 0.398518E+10 | 0.105026E+10 | 0.293492E+10 | 0.788228E+10 | 0.977473E+09 |
October | 0.638914E+10 | 0.332814E+10 | 0.306100E+10 | 0.114962E+11 | 0.191615E+10 |
November | 0.786832E+10 | 0.541742E+10 | 0.245090E+10 | 0.119685E+11 | 0.387563E+10 |
December | 0.840684E+10 | 0.603734E+10 | 0.236950E+10 | 0.121799E+11 | 0.527392E+10 |
Annual Sum or Average | 0.627237E+11 | 0.302272E+11 | 0.324964E+11 | 0.104188E+12 | 0.324778E+11 |
Minimum of Months | 0.269697E+10 | 25138330.74 | 0.236950E+10 | 0.584739E+10 | 0.440293E+09 |
Maximum of Months | 0.860368E+10 | 0.613591E+10 | 0.306100E+10 | 0.121799E+11 | 0.593738E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.271639E+10 | 0.146887E+10 | 0.124752E+10 | 0.336862E+10 | 0.411253E+10 |
February | 0.277792E+10 | 0.140601E+10 | 0.137191E+10 | 0.357937E+10 | 0.317646E+10 |
March | 0.303127E+10 | 0.134187E+10 | 0.168940E+10 | 0.407817E+10 | 0.306002E+10 |
April | 0.364347E+10 | 0.167607E+10 | 0.196741E+10 | 0.561964E+10 | 0.197985E+10 |
May | 0.313098E+10 | 0.101992E+10 | 0.211105E+10 | 0.606018E+10 | 0.652071E+09 |
June | 0.336596E+10 | 0.118026E+10 | 0.218569E+10 | 0.665165E+10 | 0.560238E+09 |
July | 0.317491E+10 | 0.880669E+09 | 0.229424E+10 | 0.628463E+10 | 0.396453E+09 |
August | 0.321023E+10 | 0.982696E+09 | 0.222754E+10 | 0.635918E+10 | 0.549377E+09 |
September | 0.286072E+10 | 0.981365E+09 | 0.187936E+10 | 0.535484E+10 | 0.692447E+09 |
October | 0.302642E+10 | 0.130768E+10 | 0.171874E+10 | 0.540320E+10 | 0.129681E+10 |
November | 0.251032E+10 | 0.126159E+10 | 0.124874E+10 | 0.363366E+10 | 0.263416E+10 |
December | 0.249521E+10 | 0.132692E+10 | 0.116829E+10 | 0.329066E+10 | 0.356831E+10 |
Annual Sum or Average | 0.359438E+11 | 0.148339E+11 | 0.211099E+11 | 0.596838E+11 | 0.226787E+11 |
Minimum of Months | 0.249521E+10 | 0.880669E+09 | 0.116829E+10 | 0.329066E+10 | 0.396453E+09 |
Maximum of Months | 0.364347E+10 | 0.167607E+10 | 0.229424E+10 | 0.665165E+10 | 0.411253E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.148847E+10 | 0.00 | 0.148847E+10 | 0.114325E+10 | 0.565561E+10 |
February | 0.158610E+10 | 0.00 | 0.158610E+10 | 0.134964E+10 | 0.426899E+10 |
March | 0.203716E+10 | 0.00 | 0.203716E+10 | 0.210799E+10 | 0.415636E+10 |
April | 0.232674E+10 | 9549742.00 | 0.231719E+10 | 0.316963E+10 | 0.255927E+10 |
May | 0.272332E+10 | 99612896.60 | 0.262371E+10 | 0.559995E+10 | 0.835417E+09 |
June | 0.299710E+10 | 0.207526E+09 | 0.278957E+10 | 0.643722E+10 | 0.702874E+09 |
July | 0.300544E+10 | 0.114502E+09 | 0.289094E+10 | 0.637985E+10 | 0.493640E+09 |
August | 0.269142E+10 | 21168395.15 | 0.267026E+10 | 0.579551E+10 | 0.674238E+09 |
September | 0.224979E+10 | 173278.28 | 0.224962E+10 | 0.442563E+10 | 0.891365E+09 |
October | 0.202019E+10 | 0.00 | 0.202019E+10 | 0.370649E+10 | 0.166098E+10 |
November | 0.148418E+10 | 0.00 | 0.148418E+10 | 0.167155E+10 | 0.345371E+10 |
December | 0.138370E+10 | 0.00 | 0.138370E+10 | 0.121909E+10 | 0.482433E+10 |
Annual Sum or Average | 0.259936E+11 | 0.452532E+09 | 0.255411E+11 | 0.430058E+11 | 0.301768E+11 |
Minimum of Months | 0.138370E+10 | 0.00 | 0.138370E+10 | 0.114325E+10 | 0.493640E+09 |
Maximum of Months | 0.300544E+10 | 0.207526E+09 | 0.289094E+10 | 0.643722E+10 | 0.565561E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.255382E+10 | 0.130041E+10 | 0.125340E+10 | 0.300512E+10 | 0.349587E+10 |
February | 0.256856E+10 | 0.124003E+10 | 0.132853E+10 | 0.317447E+10 | 0.266156E+10 |
March | 0.334520E+10 | 0.161330E+10 | 0.173190E+10 | 0.443377E+10 | 0.263803E+10 |
April | 0.355255E+10 | 0.160672E+10 | 0.194583E+10 | 0.538152E+10 | 0.169492E+10 |
May | 0.378378E+10 | 0.164072E+10 | 0.214306E+10 | 0.700505E+10 | 0.568011E+09 |
June | 0.371360E+10 | 0.147271E+10 | 0.224089E+10 | 0.716982E+10 | 0.472390E+09 |
July | 0.369979E+10 | 0.135392E+10 | 0.234587E+10 | 0.714159E+10 | 0.324566E+09 |
August | 0.340924E+10 | 0.117212E+10 | 0.223712E+10 | 0.659242E+10 | 0.450778E+09 |
September | 0.292254E+10 | 0.100476E+10 | 0.191778E+10 | 0.535677E+10 | 0.589382E+09 |
October | 0.298434E+10 | 0.125938E+10 | 0.172496E+10 | 0.517687E+10 | 0.108506E+10 |
November | 0.255697E+10 | 0.130441E+10 | 0.125256E+10 | 0.352020E+10 | 0.219863E+10 |
December | 0.208032E+10 | 0.942340E+09 | 0.113798E+10 | 0.256019E+10 | 0.305798E+10 |
Annual Sum or Average | 0.371707E+11 | 0.159108E+11 | 0.212599E+11 | 0.605178E+11 | 0.192372E+11 |
Minimum of Months | 0.208032E+10 | 0.942340E+09 | 0.113798E+10 | 0.256019E+10 | 0.324566E+09 |
Maximum of Months | 0.378378E+10 | 0.164072E+10 | 0.234587E+10 | 0.716982E+10 | 0.349587E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.860368E+10 | 0.613591E+10 | 0.246776E+10 | 0.119631E+11 | 0.554923E+10 |
February | 0.704791E+10 | 0.456200E+10 | 0.248592E+10 | 0.100262E+11 | 0.428763E+10 |
March | 0.498163E+10 | 0.224822E+10 | 0.273342E+10 | 0.729581E+10 | 0.423525E+10 |
April | 0.357322E+10 | 0.837293E+09 | 0.273592E+10 | 0.582845E+10 | 0.271513E+10 |
May | 0.282120E+10 | 0.119897E+09 | 0.270131E+10 | 0.587370E+10 | 0.860355E+09 |
June | 0.269697E+10 | 25138330.74 | 0.267183E+10 | 0.584509E+10 | 0.713385E+09 |
July | 0.291740E+10 | 53621437.41 | 0.286378E+10 | 0.624300E+10 | 0.475581E+09 |
August | 0.343216E+10 | 0.411963E+09 | 0.302020E+10 | 0.736266E+10 | 0.719733E+09 |
September | 0.398518E+10 | 0.105026E+10 | 0.293492E+10 | 0.780132E+10 | 0.992234E+09 |
October | 0.638914E+10 | 0.332814E+10 | 0.306100E+10 | 0.114360E+11 | 0.187923E+10 |
November | 0.786832E+10 | 0.541742E+10 | 0.245090E+10 | 0.120054E+11 | 0.366661E+10 |
December | 0.840684E+10 | 0.603734E+10 | 0.236950E+10 | 0.122443E+11 | 0.493730E+10 |
Annual Sum or Average | 0.627237E+11 | 0.302272E+11 | 0.324964E+11 | 0.103925E+12 | 0.310317E+11 |
Minimum of Months | 0.269697E+10 | 25138330.74 | 0.236950E+10 | 0.582845E+10 | 0.475581E+09 |
Maximum of Months | 0.860368E+10 | 0.613591E+10 | 0.306100E+10 | 0.122443E+11 | 0.554923E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.271639E+10 | 0.146887E+10 | 0.124752E+10 | 0.340325E+10 | 0.387360E+10 |
February | 0.277792E+10 | 0.140601E+10 | 0.137191E+10 | 0.360415E+10 | 0.298400E+10 |
March | 0.303127E+10 | 0.134187E+10 | 0.168940E+10 | 0.408591E+10 | 0.291659E+10 |
April | 0.364347E+10 | 0.167607E+10 | 0.196741E+10 | 0.559909E+10 | 0.192240E+10 |
May | 0.313098E+10 | 0.101992E+10 | 0.211105E+10 | 0.600247E+10 | 0.669724E+09 |
June | 0.336596E+10 | 0.118026E+10 | 0.218569E+10 | 0.658646E+10 | 0.578740E+09 |
July | 0.317491E+10 | 0.880669E+09 | 0.229424E+10 | 0.621149E+10 | 0.412207E+09 |
August | 0.321023E+10 | 0.982696E+09 | 0.222754E+10 | 0.629628E+10 | 0.567751E+09 |
September | 0.286072E+10 | 0.981365E+09 | 0.187936E+10 | 0.530933E+10 | 0.695739E+09 |
October | 0.302642E+10 | 0.130768E+10 | 0.171874E+10 | 0.537496E+10 | 0.126793E+10 |
November | 0.251032E+10 | 0.126159E+10 | 0.124874E+10 | 0.365931E+10 | 0.248199E+10 |
December | 0.249521E+10 | 0.132692E+10 | 0.116829E+10 | 0.331839E+10 | 0.336000E+10 |
Annual Sum or Average | 0.359438E+11 | 0.148339E+11 | 0.211099E+11 | 0.594511E+11 | 0.217307E+11 |
Minimum of Months | 0.249521E+10 | 0.880669E+09 | 0.116829E+10 | 0.331839E+10 | 0.412207E+09 |
Maximum of Months | 0.364347E+10 | 0.167607E+10 | 0.229424E+10 | 0.658646E+10 | 0.387360E+10 |
Report: WindowZoneSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 323.10 | 2588.63 | 555.73 | 0.00 | 555.73 | 0.00 | 0.00 |
February | 455.73 | 2205.49 | 655.63 | 0.00 | 655.63 | 0.00 | 0.00 |
March | 694.54 | 1885.06 | 760.59 | 0.00 | 760.59 | 0.00 | 0.00 |
April | 1175.92 | 1130.09 | 897.66 | 3.68 | 893.98 | 0.00 | 0.00 |
May | 2113.64 | 311.87 | 1016.78 | 37.19 | 979.58 | 0.00 | 0.00 |
June | 2513.54 | 251.56 | 1156.29 | 80.06 | 1076.23 | 0.00 | 0.00 |
July | 2415.16 | 158.79 | 1122.11 | 42.75 | 1079.36 | 0.00 | 0.00 |
August | 2174.64 | 228.70 | 1004.87 | 7.90 | 996.96 | 0.00 | 0.00 |
September | 1718.11 | 375.18 | 867.98 | 0.07 | 867.91 | 0.00 | 0.00 |
October | 1361.95 | 708.15 | 754.26 | 0.00 | 754.26 | 0.00 | 0.00 |
November | 546.06 | 1687.22 | 572.60 | 0.00 | 572.60 | 0.00 | 0.00 |
December | 350.92 | 2303.08 | 516.62 | 0.00 | 516.62 | 0.00 | 0.00 |
Annual Sum or Average | 1325.54 | 1147.36 | 824.26 | 14.35 | 809.91 | 0.00 | 0.00 |
Minimum of Months | 323.10 | 158.79 | 516.62 | 0.00 | 516.62 | 0.00 | 0.00 |
Maximum of Months | 2513.54 | 2588.63 | 1156.29 | 80.06 | 1079.36 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1050.45 | 1547.73 | 953.49 | 485.52 | 467.97 | 0.00 | 0.00 |
February | 1254.06 | 1305.55 | 1061.74 | 512.58 | 549.16 | 0.00 | 0.00 |
March | 1638.09 | 1115.50 | 1248.96 | 602.34 | 646.62 | 0.00 | 0.00 |
April | 2101.04 | 675.95 | 1370.59 | 619.88 | 750.71 | 0.00 | 0.00 |
May | 2671.16 | 197.00 | 1412.71 | 612.58 | 800.13 | 0.00 | 0.00 |
June | 2824.69 | 144.76 | 1432.72 | 568.18 | 864.54 | 0.00 | 0.00 |
July | 2737.41 | 77.07 | 1381.35 | 505.50 | 875.85 | 0.00 | 0.00 |
August | 2523.79 | 111.52 | 1272.87 | 437.62 | 835.25 | 0.00 | 0.00 |
September | 2104.66 | 230.33 | 1127.53 | 387.64 | 739.89 | 0.00 | 0.00 |
October | 1960.12 | 424.51 | 1114.23 | 470.20 | 644.03 | 0.00 | 0.00 |
November | 1323.51 | 988.46 | 986.49 | 503.25 | 483.24 | 0.00 | 0.00 |
December | 900.52 | 1354.73 | 776.71 | 351.83 | 424.88 | 0.00 | 0.00 |
Annual Sum or Average | 1927.83 | 677.84 | 1178.68 | 504.53 | 674.15 | 0.00 | 0.00 |
Minimum of Months | 900.52 | 77.07 | 776.71 | 351.83 | 424.88 | 0.00 | 0.00 |
Maximum of Months | 2824.69 | 1547.73 | 1432.72 | 619.88 | 875.85 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 4473.36 | 2290.86 | 3212.26 | 2290.90 | 921.36 | 0.00 | 0.00 |
February | 4138.62 | 1985.75 | 2913.33 | 1885.75 | 1027.58 | 0.00 | 0.00 |
March | 2714.17 | 1779.74 | 1859.94 | 839.39 | 1020.54 | 0.00 | 0.00 |
April | 2248.56 | 1140.46 | 1378.56 | 323.03 | 1055.53 | 0.00 | 0.00 |
May | 2219.61 | 319.33 | 1053.32 | 44.76 | 1008.56 | 0.00 | 0.00 |
June | 2277.94 | 257.12 | 1040.50 | 9.70 | 1030.80 | 0.00 | 0.00 |
July | 2360.67 | 156.26 | 1089.24 | 20.02 | 1069.22 | 0.00 | 0.00 |
August | 2775.72 | 242.83 | 1281.43 | 153.81 | 1127.62 | 0.00 | 0.00 |
September | 3053.29 | 394.87 | 1537.50 | 405.20 | 1132.30 | 0.00 | 0.00 |
October | 4324.46 | 728.52 | 2385.44 | 1242.59 | 1142.85 | 0.00 | 0.00 |
November | 4644.42 | 1561.82 | 3035.63 | 2090.06 | 945.57 | 0.00 | 0.00 |
December | 4568.24 | 2079.50 | 3138.76 | 2254.09 | 884.67 | 0.00 | 0.00 |
Annual Sum or Average | 3312.69 | 1073.25 | 1988.96 | 958.50 | 1030.46 | 0.00 | 0.00 |
Minimum of Months | 2219.61 | 156.26 | 1040.50 | 9.70 | 884.67 | 0.00 | 0.00 |
Maximum of Months | 4644.42 | 2290.86 | 3212.26 | 2290.90 | 1142.85 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1207.38 | 1750.07 | 1014.19 | 548.42 | 465.77 | 0.00 | 0.00 |
February | 1410.51 | 1565.73 | 1148.29 | 581.19 | 567.09 | 0.00 | 0.00 |
March | 1447.80 | 1404.40 | 1131.75 | 501.00 | 630.75 | 0.00 | 0.00 |
April | 2099.50 | 930.84 | 1405.67 | 646.63 | 759.03 | 0.00 | 0.00 |
May | 2239.44 | 281.57 | 1168.98 | 380.80 | 788.18 | 0.00 | 0.00 |
June | 2531.22 | 252.44 | 1298.60 | 455.35 | 843.25 | 0.00 | 0.00 |
July | 2288.71 | 189.26 | 1185.38 | 328.81 | 856.57 | 0.00 | 0.00 |
August | 2299.99 | 276.17 | 1198.57 | 366.90 | 831.67 | 0.00 | 0.00 |
September | 2041.65 | 324.24 | 1103.68 | 378.61 | 725.06 | 0.00 | 0.00 |
October | 1975.02 | 579.60 | 1129.94 | 488.23 | 641.71 | 0.00 | 0.00 |
November | 1323.28 | 1274.29 | 968.49 | 486.73 | 481.77 | 0.00 | 0.00 |
December | 1141.08 | 1707.75 | 931.61 | 495.42 | 436.19 | 0.00 | 0.00 |
Annual Sum or Average | 1835.47 | 874.38 | 1139.77 | 470.38 | 669.39 | 0.00 | 0.00 |
Minimum of Months | 1141.08 | 189.26 | 931.61 | 328.81 | 436.19 | 0.00 | 0.00 |
Maximum of Months | 2531.22 | 1750.07 | 1405.67 | 646.63 | 856.57 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 395.04 | 2277.29 | 555.73 | 0.00 | 555.73 | 0.00 | 0.00 |
February | 532.11 | 1906.07 | 655.63 | 0.00 | 655.63 | 0.00 | 0.00 |
March | 770.89 | 1644.86 | 760.59 | 0.00 | 760.59 | 0.00 | 0.00 |
April | 1226.09 | 1019.35 | 897.66 | 3.68 | 893.98 | 0.00 | 0.00 |
May | 2127.01 | 296.31 | 1016.77 | 37.19 | 979.58 | 0.00 | 0.00 |
June | 2525.94 | 254.14 | 1156.29 | 80.06 | 1076.22 | 0.00 | 0.00 |
July | 2429.56 | 168.06 | 1122.10 | 42.75 | 1079.35 | 0.00 | 0.00 |
August | 2201.97 | 236.61 | 1004.86 | 7.90 | 996.96 | 0.00 | 0.00 |
September | 1740.47 | 336.41 | 867.98 | 0.07 | 867.91 | 0.00 | 0.00 |
October | 1397.53 | 636.92 | 754.25 | 0.00 | 754.25 | 0.00 | 0.00 |
November | 618.29 | 1441.11 | 572.60 | 0.00 | 572.60 | 0.00 | 0.00 |
December | 428.99 | 1945.91 | 516.62 | 0.00 | 516.62 | 0.00 | 0.00 |
Annual Sum or Average | 1371.24 | 1009.00 | 824.25 | 14.35 | 809.90 | 0.00 | 0.00 |
Minimum of Months | 395.04 | 168.06 | 516.62 | 0.00 | 516.62 | 0.00 | 0.00 |
Maximum of Months | 2525.94 | 2277.29 | 1156.29 | 80.06 | 1079.35 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1086.89 | 1399.71 | 953.49 | 485.52 | 467.97 | 0.00 | 0.00 |
February | 1286.68 | 1179.14 | 1061.74 | 512.58 | 549.16 | 0.00 | 0.00 |
March | 1647.76 | 1031.21 | 1248.95 | 602.34 | 646.62 | 0.00 | 0.00 |
April | 2084.99 | 666.84 | 1370.58 | 619.88 | 750.70 | 0.00 | 0.00 |
May | 2644.46 | 201.16 | 1412.70 | 612.57 | 800.13 | 0.00 | 0.00 |
June | 2797.36 | 169.88 | 1432.72 | 568.18 | 864.54 | 0.00 | 0.00 |
July | 2700.35 | 110.69 | 1381.34 | 505.50 | 875.85 | 0.00 | 0.00 |
August | 2490.02 | 157.75 | 1272.87 | 437.62 | 835.24 | 0.00 | 0.00 |
September | 2091.24 | 221.17 | 1127.52 | 387.64 | 739.89 | 0.00 | 0.00 |
October | 1946.71 | 412.12 | 1114.23 | 470.20 | 644.03 | 0.00 | 0.00 |
November | 1340.46 | 901.84 | 986.49 | 503.25 | 483.24 | 0.00 | 0.00 |
December | 932.77 | 1220.78 | 776.70 | 351.83 | 424.87 | 0.00 | 0.00 |
Annual Sum or Average | 1924.29 | 636.56 | 1178.68 | 504.53 | 674.15 | 0.00 | 0.00 |
Minimum of Months | 932.77 | 110.69 | 776.70 | 351.83 | 424.87 | 0.00 | 0.00 |
Maximum of Months | 2797.36 | 1399.71 | 1432.72 | 619.88 | 875.85 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 4431.61 | 2216.76 | 3212.24 | 2290.89 | 921.36 | 0.00 | 0.00 |
February | 4111.77 | 1900.50 | 2913.32 | 1885.75 | 1027.58 | 0.00 | 0.00 |
March | 2711.83 | 1670.95 | 1859.93 | 839.39 | 1020.54 | 0.00 | 0.00 |
April | 2255.94 | 1081.83 | 1378.56 | 323.03 | 1055.53 | 0.00 | 0.00 |
May | 2226.66 | 307.61 | 1053.32 | 44.76 | 1008.55 | 0.00 | 0.00 |
June | 2292.57 | 259.48 | 1040.50 | 9.70 | 1030.80 | 0.00 | 0.00 |
July | 2376.01 | 164.39 | 1089.23 | 20.02 | 1069.21 | 0.00 | 0.00 |
August | 2786.42 | 255.11 | 1281.42 | 153.81 | 1127.61 | 0.00 | 0.00 |
September | 3041.00 | 377.11 | 1537.49 | 405.19 | 1132.30 | 0.00 | 0.00 |
October | 4292.21 | 715.41 | 2385.43 | 1242.58 | 1142.85 | 0.00 | 0.00 |
November | 4617.48 | 1495.23 | 3035.62 | 2090.05 | 945.56 | 0.00 | 0.00 |
December | 4547.44 | 1969.06 | 3138.75 | 2254.09 | 884.67 | 0.00 | 0.00 |
Annual Sum or Average | 3303.77 | 1029.87 | 1988.95 | 958.50 | 1030.46 | 0.00 | 0.00 |
Minimum of Months | 2226.66 | 164.39 | 1040.50 | 9.70 | 884.67 | 0.00 | 0.00 |
Maximum of Months | 4617.48 | 2216.76 | 3212.24 | 2290.89 | 1142.85 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1257.70 | 1535.44 | 1014.18 | 548.41 | 465.77 | 0.00 | 0.00 |
February | 1479.57 | 1313.02 | 1148.28 | 581.19 | 567.09 | 0.00 | 0.00 |
March | 1522.62 | 1142.48 | 1131.75 | 501.00 | 630.75 | 0.00 | 0.00 |
April | 2168.07 | 763.83 | 1405.66 | 646.63 | 759.03 | 0.00 | 0.00 |
May | 2262.61 | 243.46 | 1168.97 | 380.80 | 788.18 | 0.00 | 0.00 |
June | 2566.22 | 216.14 | 1298.59 | 455.35 | 843.25 | 0.00 | 0.00 |
July | 2346.41 | 148.02 | 1185.37 | 328.80 | 856.57 | 0.00 | 0.00 |
August | 2374.25 | 205.11 | 1198.56 | 366.90 | 831.67 | 0.00 | 0.00 |
September | 2065.91 | 267.15 | 1103.67 | 378.61 | 725.06 | 0.00 | 0.00 |
October | 2017.32 | 484.17 | 1129.93 | 488.23 | 641.70 | 0.00 | 0.00 |
November | 1401.88 | 1016.26 | 968.49 | 486.72 | 481.77 | 0.00 | 0.00 |
December | 1228.59 | 1332.25 | 931.60 | 495.41 | 436.19 | 0.00 | 0.00 |
Annual Sum or Average | 1892.56 | 719.14 | 1139.77 | 470.38 | 669.39 | 0.00 | 0.00 |
Minimum of Months | 1228.59 | 148.02 | 931.60 | 328.80 | 436.19 | 0.00 | 0.00 |
Maximum of Months | 2566.22 | 1535.44 | 1405.66 | 646.63 | 856.57 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 426.84 | 2111.56 | 555.73 | 0.00 | 555.73 | 0.00 | 0.00 |
February | 557.89 | 1764.63 | 655.63 | 0.00 | 655.63 | 0.00 | 0.00 |
March | 787.03 | 1551.81 | 760.59 | 0.00 | 760.59 | 0.00 | 0.00 |
April | 1222.85 | 987.37 | 897.66 | 3.68 | 893.98 | 0.00 | 0.00 |
May | 2090.78 | 311.91 | 1016.77 | 37.19 | 979.58 | 0.00 | 0.00 |
June | 2483.49 | 271.17 | 1156.29 | 80.06 | 1076.22 | 0.00 | 0.00 |
July | 2381.96 | 184.30 | 1122.10 | 42.75 | 1079.35 | 0.00 | 0.00 |
August | 2163.79 | 251.73 | 1004.86 | 7.90 | 996.96 | 0.00 | 0.00 |
September | 1707.42 | 343.89 | 867.98 | 0.07 | 867.91 | 0.00 | 0.00 |
October | 1383.85 | 620.14 | 754.25 | 0.00 | 754.25 | 0.00 | 0.00 |
November | 644.89 | 1332.45 | 572.60 | 0.00 | 572.60 | 0.00 | 0.00 |
December | 455.16 | 1801.20 | 516.62 | 0.00 | 516.62 | 0.00 | 0.00 |
Annual Sum or Average | 1363.70 | 956.90 | 824.25 | 14.35 | 809.90 | 0.00 | 0.00 |
Minimum of Months | 426.84 | 184.30 | 516.62 | 0.00 | 516.62 | 0.00 | 0.00 |
Maximum of Months | 2483.49 | 2111.56 | 1156.29 | 80.06 | 1079.35 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1121.98 | 1305.21 | 953.49 | 485.52 | 467.97 | 0.00 | 0.00 |
February | 1312.20 | 1100.18 | 1061.74 | 512.58 | 549.16 | 0.00 | 0.00 |
March | 1655.38 | 984.93 | 1248.95 | 602.34 | 646.62 | 0.00 | 0.00 |
April | 2076.20 | 653.90 | 1370.58 | 619.88 | 750.70 | 0.00 | 0.00 |
May | 2615.39 | 212.07 | 1412.70 | 612.57 | 800.13 | 0.00 | 0.00 |
June | 2766.13 | 182.25 | 1432.72 | 568.18 | 864.54 | 0.00 | 0.00 |
July | 2666.37 | 121.18 | 1381.34 | 505.50 | 875.85 | 0.00 | 0.00 |
August | 2461.33 | 168.30 | 1272.87 | 437.62 | 835.24 | 0.00 | 0.00 |
September | 2066.65 | 227.39 | 1127.52 | 387.64 | 739.89 | 0.00 | 0.00 |
October | 1932.82 | 405.12 | 1114.23 | 470.20 | 644.03 | 0.00 | 0.00 |
November | 1358.10 | 848.24 | 986.49 | 503.25 | 483.24 | 0.00 | 0.00 |
December | 955.87 | 1141.72 | 776.70 | 351.83 | 424.87 | 0.00 | 0.00 |
Annual Sum or Average | 1919.01 | 610.01 | 1178.68 | 504.53 | 674.15 | 0.00 | 0.00 |
Minimum of Months | 955.87 | 121.18 | 776.70 | 351.83 | 424.87 | 0.00 | 0.00 |
Maximum of Months | 2766.13 | 1305.21 | 1432.72 | 619.88 | 875.85 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 4466.52 | 2071.85 | 3212.24 | 2290.89 | 921.36 | 0.00 | 0.00 |
February | 4144.43 | 1772.34 | 2913.32 | 1885.75 | 1027.58 | 0.00 | 0.00 |
March | 2723.94 | 1581.26 | 1859.93 | 839.39 | 1020.54 | 0.00 | 0.00 |
April | 2248.63 | 1047.50 | 1378.56 | 323.03 | 1055.53 | 0.00 | 0.00 |
May | 2192.99 | 321.22 | 1053.32 | 44.76 | 1008.55 | 0.00 | 0.00 |
June | 2255.05 | 275.23 | 1040.50 | 9.70 | 1030.80 | 0.00 | 0.00 |
July | 2330.87 | 177.56 | 1089.23 | 20.02 | 1069.21 | 0.00 | 0.00 |
August | 2748.90 | 268.72 | 1281.42 | 153.81 | 1127.61 | 0.00 | 0.00 |
September | 3009.77 | 382.81 | 1537.49 | 405.19 | 1132.30 | 0.00 | 0.00 |
October | 4269.73 | 701.62 | 2385.43 | 1242.58 | 1142.85 | 0.00 | 0.00 |
November | 4631.70 | 1414.59 | 3035.62 | 2090.05 | 945.56 | 0.00 | 0.00 |
December | 4571.51 | 1843.38 | 3138.75 | 2254.09 | 884.67 | 0.00 | 0.00 |
Annual Sum or Average | 3295.44 | 984.01 | 1988.95 | 958.50 | 1030.46 | 0.00 | 0.00 |
Minimum of Months | 2192.99 | 177.56 | 1040.50 | 9.70 | 884.67 | 0.00 | 0.00 |
Maximum of Months | 4631.70 | 2071.85 | 3212.24 | 2290.89 | 1142.85 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1270.63 | 1446.23 | 1014.18 | 548.41 | 465.77 | 0.00 | 0.00 |
February | 1489.81 | 1233.47 | 1148.28 | 581.19 | 567.09 | 0.00 | 0.00 |
March | 1525.50 | 1088.93 | 1131.75 | 501.00 | 630.75 | 0.00 | 0.00 |
April | 2160.14 | 741.67 | 1405.66 | 646.63 | 759.03 | 0.00 | 0.00 |
May | 2241.06 | 250.05 | 1168.97 | 380.80 | 788.18 | 0.00 | 0.00 |
June | 2541.07 | 223.28 | 1298.59 | 455.35 | 843.25 | 0.00 | 0.00 |
July | 2319.11 | 153.90 | 1185.37 | 328.80 | 856.57 | 0.00 | 0.00 |
August | 2350.76 | 211.97 | 1198.56 | 366.90 | 831.67 | 0.00 | 0.00 |
September | 2048.35 | 268.42 | 1103.67 | 378.61 | 725.06 | 0.00 | 0.00 |
October | 2006.78 | 473.39 | 1129.93 | 488.23 | 641.70 | 0.00 | 0.00 |
November | 1411.77 | 957.56 | 968.49 | 486.72 | 481.77 | 0.00 | 0.00 |
December | 1238.95 | 1254.48 | 931.60 | 495.41 | 436.19 | 0.00 | 0.00 |
Annual Sum or Average | 1885.18 | 689.08 | 1139.77 | 470.38 | 669.39 | 0.00 | 0.00 |
Minimum of Months | 1238.95 | 153.90 | 931.60 | 328.80 | 436.19 | 0.00 | 0.00 |
Maximum of Months | 2541.07 | 1446.23 | 1405.66 | 646.63 | 856.57 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.865396E+09 | 0.693340E+10 | 0.148848E+10 | 0.00 | 0.148848E+10 | 0.00 | 0.00 |
February | 0.110250E+10 | 0.533552E+10 | 0.158610E+10 | 0.00 | 0.158610E+10 | 0.00 | 0.00 |
March | 0.186027E+10 | 0.504895E+10 | 0.203717E+10 | 0.00 | 0.203717E+10 | 0.00 | 0.00 |
April | 0.304800E+10 | 0.292919E+10 | 0.232675E+10 | 9549775.91 | 0.231720E+10 | 0.00 | 0.00 |
May | 0.566117E+10 | 0.835326E+09 | 0.272333E+10 | 99613250.33 | 0.262372E+10 | 0.00 | 0.00 |
June | 0.651509E+10 | 0.652034E+09 | 0.299711E+10 | 0.207526E+09 | 0.278958E+10 | 0.00 | 0.00 |
July | 0.646877E+10 | 0.425296E+09 | 0.300545E+10 | 0.114502E+09 | 0.289095E+10 | 0.00 | 0.00 |
August | 0.582457E+10 | 0.612559E+09 | 0.269143E+10 | 21168470.32 | 0.267027E+10 | 0.00 | 0.00 |
September | 0.445335E+10 | 0.972457E+09 | 0.224980E+10 | 173278.90 | 0.224963E+10 | 0.00 | 0.00 |
October | 0.364786E+10 | 0.189670E+10 | 0.202020E+10 | 0.00 | 0.202020E+10 | 0.00 | 0.00 |
November | 0.141537E+10 | 0.437328E+10 | 0.148418E+10 | 0.00 | 0.148418E+10 | 0.00 | 0.00 |
December | 0.939903E+09 | 0.616857E+10 | 0.138371E+10 | 0.00 | 0.138371E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.418022E+11 | 0.361833E+11 | 0.259937E+11 | 0.452533E+09 | 0.255412E+11 | 0.00 | 0.00 |
Minimum of Months | 0.865396E+09 | 0.425296E+09 | 0.138371E+10 | 0.00 | 0.138371E+10 | 0.00 | 0.00 |
Maximum of Months | 0.651509E+10 | 0.693340E+10 | 0.300545E+10 | 0.207526E+09 | 0.289095E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.281353E+10 | 0.414545E+10 | 0.255383E+10 | 0.130042E+10 | 0.125341E+10 | 0.00 | 0.00 |
February | 0.303381E+10 | 0.315839E+10 | 0.256857E+10 | 0.124004E+10 | 0.132853E+10 | 0.00 | 0.00 |
March | 0.438746E+10 | 0.298776E+10 | 0.334521E+10 | 0.161330E+10 | 0.173191E+10 | 0.00 | 0.00 |
April | 0.544589E+10 | 0.175207E+10 | 0.355256E+10 | 0.160673E+10 | 0.194584E+10 | 0.00 | 0.00 |
May | 0.715444E+10 | 0.527646E+09 | 0.378379E+10 | 0.164072E+10 | 0.214307E+10 | 0.00 | 0.00 |
June | 0.732159E+10 | 0.375224E+09 | 0.371362E+10 | 0.147272E+10 | 0.224090E+10 | 0.00 | 0.00 |
July | 0.733187E+10 | 0.206416E+09 | 0.369981E+10 | 0.135393E+10 | 0.234588E+10 | 0.00 | 0.00 |
August | 0.675972E+10 | 0.298684E+09 | 0.340926E+10 | 0.117213E+10 | 0.223713E+10 | 0.00 | 0.00 |
September | 0.545528E+10 | 0.597023E+09 | 0.292256E+10 | 0.100477E+10 | 0.191779E+10 | 0.00 | 0.00 |
October | 0.524997E+10 | 0.113700E+10 | 0.298436E+10 | 0.125939E+10 | 0.172497E+10 | 0.00 | 0.00 |
November | 0.343053E+10 | 0.256209E+10 | 0.255698E+10 | 0.130442E+10 | 0.125257E+10 | 0.00 | 0.00 |
December | 0.241194E+10 | 0.362850E+10 | 0.208033E+10 | 0.942343E+09 | 0.113799E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.607961E+11 | 0.213762E+11 | 0.371709E+11 | 0.159109E+11 | 0.212600E+11 | 0.00 | 0.00 |
Minimum of Months | 0.241194E+10 | 0.206416E+09 | 0.208033E+10 | 0.942343E+09 | 0.113799E+10 | 0.00 | 0.00 |
Maximum of Months | 0.733187E+10 | 0.414545E+10 | 0.378379E+10 | 0.164072E+10 | 0.234588E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.119814E+11 | 0.613583E+10 | 0.860371E+10 | 0.613594E+10 | 0.246777E+10 | 0.00 | 0.00 |
February | 0.100121E+11 | 0.480392E+10 | 0.704794E+10 | 0.456201E+10 | 0.248593E+10 | 0.00 | 0.00 |
March | 0.726962E+10 | 0.476687E+10 | 0.498165E+10 | 0.224823E+10 | 0.273343E+10 | 0.00 | 0.00 |
April | 0.582828E+10 | 0.295608E+10 | 0.357323E+10 | 0.837296E+09 | 0.273593E+10 | 0.00 | 0.00 |
May | 0.594500E+10 | 0.855305E+09 | 0.282121E+10 | 0.119898E+09 | 0.270132E+10 | 0.00 | 0.00 |
June | 0.590443E+10 | 0.666462E+09 | 0.269698E+10 | 25138420.01 | 0.267184E+10 | 0.00 | 0.00 |
July | 0.632282E+10 | 0.418525E+09 | 0.291741E+10 | 53621627.83 | 0.286379E+10 | 0.00 | 0.00 |
August | 0.743449E+10 | 0.650383E+09 | 0.343218E+10 | 0.411964E+09 | 0.302021E+10 | 0.00 | 0.00 |
September | 0.791413E+10 | 0.102351E+10 | 0.398520E+10 | 0.105027E+10 | 0.293493E+10 | 0.00 | 0.00 |
October | 0.115826E+11 | 0.195127E+10 | 0.638917E+10 | 0.332815E+10 | 0.306102E+10 | 0.00 | 0.00 |
November | 0.120383E+11 | 0.404823E+10 | 0.786835E+10 | 0.541744E+10 | 0.245091E+10 | 0.00 | 0.00 |
December | 0.122356E+11 | 0.556975E+10 | 0.840687E+10 | 0.603736E+10 | 0.236950E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.104469E+12 | 0.338461E+11 | 0.627239E+11 | 0.302273E+11 | 0.324966E+11 | 0.00 | 0.00 |
Minimum of Months | 0.582828E+10 | 0.418525E+09 | 0.269698E+10 | 25138420.01 | 0.236950E+10 | 0.00 | 0.00 |
Maximum of Months | 0.122356E+11 | 0.613583E+10 | 0.860371E+10 | 0.613594E+10 | 0.306102E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.323384E+10 | 0.468740E+10 | 0.271640E+10 | 0.146888E+10 | 0.124752E+10 | 0.00 | 0.00 |
February | 0.341230E+10 | 0.378782E+10 | 0.277793E+10 | 0.140602E+10 | 0.137192E+10 | 0.00 | 0.00 |
March | 0.387779E+10 | 0.376154E+10 | 0.303129E+10 | 0.134187E+10 | 0.168941E+10 | 0.00 | 0.00 |
April | 0.544189E+10 | 0.241273E+10 | 0.364349E+10 | 0.167607E+10 | 0.196741E+10 | 0.00 | 0.00 |
May | 0.599812E+10 | 0.754157E+09 | 0.313099E+10 | 0.101993E+10 | 0.211106E+10 | 0.00 | 0.00 |
June | 0.656092E+10 | 0.654329E+09 | 0.336597E+10 | 0.118027E+10 | 0.218570E+10 | 0.00 | 0.00 |
July | 0.613008E+10 | 0.506926E+09 | 0.317492E+10 | 0.880673E+09 | 0.229425E+10 | 0.00 | 0.00 |
August | 0.616029E+10 | 0.739696E+09 | 0.321025E+10 | 0.982700E+09 | 0.222755E+10 | 0.00 | 0.00 |
September | 0.529196E+10 | 0.840432E+09 | 0.286073E+10 | 0.981369E+09 | 0.187937E+10 | 0.00 | 0.00 |
October | 0.528988E+10 | 0.155240E+10 | 0.302643E+10 | 0.130769E+10 | 0.171874E+10 | 0.00 | 0.00 |
November | 0.342995E+10 | 0.330296E+10 | 0.251033E+10 | 0.126159E+10 | 0.124874E+10 | 0.00 | 0.00 |
December | 0.305627E+10 | 0.457404E+10 | 0.249522E+10 | 0.132692E+10 | 0.116829E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.578833E+11 | 0.275744E+11 | 0.359439E+11 | 0.148340E+11 | 0.211100E+11 | 0.00 | 0.00 |
Minimum of Months | 0.305627E+10 | 0.506926E+09 | 0.249522E+10 | 0.880673E+09 | 0.116829E+10 | 0.00 | 0.00 |
Maximum of Months | 0.656092E+10 | 0.468740E+10 | 0.364349E+10 | 0.167607E+10 | 0.229425E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.105807E+10 | 0.609950E+10 | 0.148847E+10 | 0.00 | 0.148847E+10 | 0.00 | 0.00 |
February | 0.128729E+10 | 0.461116E+10 | 0.158610E+10 | 0.00 | 0.158610E+10 | 0.00 | 0.00 |
March | 0.206475E+10 | 0.440559E+10 | 0.203716E+10 | 0.00 | 0.203716E+10 | 0.00 | 0.00 |
April | 0.317803E+10 | 0.264214E+10 | 0.232674E+10 | 9549742.00 | 0.231719E+10 | 0.00 | 0.00 |
May | 0.569699E+10 | 0.793624E+09 | 0.272332E+10 | 99612896.60 | 0.262371E+10 | 0.00 | 0.00 |
June | 0.654725E+10 | 0.658742E+09 | 0.299710E+10 | 0.207526E+09 | 0.278957E+10 | 0.00 | 0.00 |
July | 0.650733E+10 | 0.450136E+09 | 0.300544E+10 | 0.114502E+09 | 0.289094E+10 | 0.00 | 0.00 |
August | 0.589774E+10 | 0.633727E+09 | 0.269142E+10 | 21168395.15 | 0.267026E+10 | 0.00 | 0.00 |
September | 0.451130E+10 | 0.871976E+09 | 0.224979E+10 | 173278.28 | 0.224962E+10 | 0.00 | 0.00 |
October | 0.374315E+10 | 0.170592E+10 | 0.202019E+10 | 0.00 | 0.202019E+10 | 0.00 | 0.00 |
November | 0.160261E+10 | 0.373536E+10 | 0.148418E+10 | 0.00 | 0.148418E+10 | 0.00 | 0.00 |
December | 0.114899E+10 | 0.521194E+10 | 0.138370E+10 | 0.00 | 0.138370E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.432435E+11 | 0.318198E+11 | 0.259936E+11 | 0.452532E+09 | 0.255411E+11 | 0.00 | 0.00 |
Minimum of Months | 0.105807E+10 | 0.450136E+09 | 0.138370E+10 | 0.00 | 0.138370E+10 | 0.00 | 0.00 |
Maximum of Months | 0.654725E+10 | 0.609950E+10 | 0.300544E+10 | 0.207526E+09 | 0.289094E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.291113E+10 | 0.374899E+10 | 0.255382E+10 | 0.130041E+10 | 0.125340E+10 | 0.00 | 0.00 |
February | 0.311274E+10 | 0.285256E+10 | 0.256856E+10 | 0.124003E+10 | 0.132853E+10 | 0.00 | 0.00 |
March | 0.441336E+10 | 0.276198E+10 | 0.334520E+10 | 0.161330E+10 | 0.173190E+10 | 0.00 | 0.00 |
April | 0.540429E+10 | 0.172844E+10 | 0.355255E+10 | 0.160672E+10 | 0.194583E+10 | 0.00 | 0.00 |
May | 0.708291E+10 | 0.538782E+09 | 0.378378E+10 | 0.164072E+10 | 0.214306E+10 | 0.00 | 0.00 |
June | 0.725076E+10 | 0.440335E+09 | 0.371360E+10 | 0.147271E+10 | 0.224089E+10 | 0.00 | 0.00 |
July | 0.723262E+10 | 0.296481E+09 | 0.369979E+10 | 0.135392E+10 | 0.234587E+10 | 0.00 | 0.00 |
August | 0.666927E+10 | 0.422526E+09 | 0.340924E+10 | 0.117212E+10 | 0.223712E+10 | 0.00 | 0.00 |
September | 0.542051E+10 | 0.573275E+09 | 0.292254E+10 | 0.100476E+10 | 0.191778E+10 | 0.00 | 0.00 |
October | 0.521407E+10 | 0.110383E+10 | 0.298434E+10 | 0.125938E+10 | 0.172496E+10 | 0.00 | 0.00 |
November | 0.347447E+10 | 0.233758E+10 | 0.255697E+10 | 0.130441E+10 | 0.125256E+10 | 0.00 | 0.00 |
December | 0.249834E+10 | 0.326973E+10 | 0.208032E+10 | 0.942340E+09 | 0.113798E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.606845E+11 | 0.200745E+11 | 0.371707E+11 | 0.159108E+11 | 0.212599E+11 | 0.00 | 0.00 |
Minimum of Months | 0.249834E+10 | 0.296481E+09 | 0.208032E+10 | 0.942340E+09 | 0.113798E+10 | 0.00 | 0.00 |
Maximum of Months | 0.725076E+10 | 0.374899E+10 | 0.378378E+10 | 0.164072E+10 | 0.234587E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.118696E+11 | 0.593738E+10 | 0.860368E+10 | 0.613591E+10 | 0.246776E+10 | 0.00 | 0.00 |
February | 0.994719E+10 | 0.459768E+10 | 0.704791E+10 | 0.456200E+10 | 0.248592E+10 | 0.00 | 0.00 |
March | 0.726336E+10 | 0.447547E+10 | 0.498163E+10 | 0.224822E+10 | 0.273342E+10 | 0.00 | 0.00 |
April | 0.584739E+10 | 0.280411E+10 | 0.357322E+10 | 0.837293E+09 | 0.273592E+10 | 0.00 | 0.00 |
May | 0.596389E+10 | 0.823892E+09 | 0.282120E+10 | 0.119897E+09 | 0.270131E+10 | 0.00 | 0.00 |
June | 0.594235E+10 | 0.672560E+09 | 0.269697E+10 | 25138330.74 | 0.267183E+10 | 0.00 | 0.00 |
July | 0.636390E+10 | 0.440293E+09 | 0.291740E+10 | 53621437.41 | 0.286378E+10 | 0.00 | 0.00 |
August | 0.746314E+10 | 0.683274E+09 | 0.343216E+10 | 0.411963E+09 | 0.302020E+10 | 0.00 | 0.00 |
September | 0.788228E+10 | 0.977473E+09 | 0.398518E+10 | 0.105026E+10 | 0.293492E+10 | 0.00 | 0.00 |
October | 0.114962E+11 | 0.191615E+10 | 0.638914E+10 | 0.332814E+10 | 0.306100E+10 | 0.00 | 0.00 |
November | 0.119685E+11 | 0.387563E+10 | 0.786832E+10 | 0.541742E+10 | 0.245090E+10 | 0.00 | 0.00 |
December | 0.121799E+11 | 0.527392E+10 | 0.840684E+10 | 0.603734E+10 | 0.236950E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.104188E+12 | 0.324778E+11 | 0.627237E+11 | 0.302272E+11 | 0.324964E+11 | 0.00 | 0.00 |
Minimum of Months | 0.584739E+10 | 0.440293E+09 | 0.269697E+10 | 25138330.74 | 0.236950E+10 | 0.00 | 0.00 |
Maximum of Months | 0.121799E+11 | 0.593738E+10 | 0.860368E+10 | 0.613591E+10 | 0.306100E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.336862E+10 | 0.411253E+10 | 0.271639E+10 | 0.146887E+10 | 0.124752E+10 | 0.00 | 0.00 |
February | 0.357937E+10 | 0.317646E+10 | 0.277792E+10 | 0.140601E+10 | 0.137191E+10 | 0.00 | 0.00 |
March | 0.407817E+10 | 0.306002E+10 | 0.303127E+10 | 0.134187E+10 | 0.168940E+10 | 0.00 | 0.00 |
April | 0.561964E+10 | 0.197985E+10 | 0.364347E+10 | 0.167607E+10 | 0.196741E+10 | 0.00 | 0.00 |
May | 0.606018E+10 | 0.652071E+09 | 0.313098E+10 | 0.101992E+10 | 0.211105E+10 | 0.00 | 0.00 |
June | 0.665165E+10 | 0.560238E+09 | 0.336596E+10 | 0.118026E+10 | 0.218569E+10 | 0.00 | 0.00 |
July | 0.628463E+10 | 0.396453E+09 | 0.317491E+10 | 0.880669E+09 | 0.229424E+10 | 0.00 | 0.00 |
August | 0.635918E+10 | 0.549377E+09 | 0.321023E+10 | 0.982696E+09 | 0.222754E+10 | 0.00 | 0.00 |
September | 0.535484E+10 | 0.692447E+09 | 0.286072E+10 | 0.981365E+09 | 0.187936E+10 | 0.00 | 0.00 |
October | 0.540320E+10 | 0.129681E+10 | 0.302642E+10 | 0.130768E+10 | 0.171874E+10 | 0.00 | 0.00 |
November | 0.363366E+10 | 0.263416E+10 | 0.251032E+10 | 0.126159E+10 | 0.124874E+10 | 0.00 | 0.00 |
December | 0.329066E+10 | 0.356831E+10 | 0.249521E+10 | 0.132692E+10 | 0.116829E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.596838E+11 | 0.226787E+11 | 0.359438E+11 | 0.148339E+11 | 0.211099E+11 | 0.00 | 0.00 |
Minimum of Months | 0.329066E+10 | 0.396453E+09 | 0.249521E+10 | 0.880669E+09 | 0.116829E+10 | 0.00 | 0.00 |
Maximum of Months | 0.665165E+10 | 0.411253E+10 | 0.364347E+10 | 0.167607E+10 | 0.229424E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.114325E+10 | 0.565561E+10 | 0.148847E+10 | 0.00 | 0.148847E+10 | 0.00 | 0.00 |
February | 0.134964E+10 | 0.426899E+10 | 0.158610E+10 | 0.00 | 0.158610E+10 | 0.00 | 0.00 |
March | 0.210799E+10 | 0.415636E+10 | 0.203716E+10 | 0.00 | 0.203716E+10 | 0.00 | 0.00 |
April | 0.316963E+10 | 0.255927E+10 | 0.232674E+10 | 9549742.00 | 0.231719E+10 | 0.00 | 0.00 |
May | 0.559995E+10 | 0.835417E+09 | 0.272332E+10 | 99612896.60 | 0.262371E+10 | 0.00 | 0.00 |
June | 0.643722E+10 | 0.702874E+09 | 0.299710E+10 | 0.207526E+09 | 0.278957E+10 | 0.00 | 0.00 |
July | 0.637985E+10 | 0.493640E+09 | 0.300544E+10 | 0.114502E+09 | 0.289094E+10 | 0.00 | 0.00 |
August | 0.579551E+10 | 0.674238E+09 | 0.269142E+10 | 21168395.15 | 0.267026E+10 | 0.00 | 0.00 |
September | 0.442563E+10 | 0.891365E+09 | 0.224979E+10 | 173278.28 | 0.224962E+10 | 0.00 | 0.00 |
October | 0.370649E+10 | 0.166098E+10 | 0.202019E+10 | 0.00 | 0.202019E+10 | 0.00 | 0.00 |
November | 0.167155E+10 | 0.345371E+10 | 0.148418E+10 | 0.00 | 0.148418E+10 | 0.00 | 0.00 |
December | 0.121909E+10 | 0.482433E+10 | 0.138370E+10 | 0.00 | 0.138370E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.430058E+11 | 0.301768E+11 | 0.259936E+11 | 0.452532E+09 | 0.255411E+11 | 0.00 | 0.00 |
Minimum of Months | 0.114325E+10 | 0.493640E+09 | 0.138370E+10 | 0.00 | 0.138370E+10 | 0.00 | 0.00 |
Maximum of Months | 0.643722E+10 | 0.565561E+10 | 0.300544E+10 | 0.207526E+09 | 0.289094E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.300512E+10 | 0.349587E+10 | 0.255382E+10 | 0.130041E+10 | 0.125340E+10 | 0.00 | 0.00 |
February | 0.317447E+10 | 0.266156E+10 | 0.256856E+10 | 0.124003E+10 | 0.132853E+10 | 0.00 | 0.00 |
March | 0.443377E+10 | 0.263803E+10 | 0.334520E+10 | 0.161330E+10 | 0.173190E+10 | 0.00 | 0.00 |
April | 0.538152E+10 | 0.169492E+10 | 0.355255E+10 | 0.160672E+10 | 0.194583E+10 | 0.00 | 0.00 |
May | 0.700505E+10 | 0.568011E+09 | 0.378378E+10 | 0.164072E+10 | 0.214306E+10 | 0.00 | 0.00 |
June | 0.716982E+10 | 0.472390E+09 | 0.371360E+10 | 0.147271E+10 | 0.224089E+10 | 0.00 | 0.00 |
July | 0.714159E+10 | 0.324566E+09 | 0.369979E+10 | 0.135392E+10 | 0.234587E+10 | 0.00 | 0.00 |
August | 0.659242E+10 | 0.450778E+09 | 0.340924E+10 | 0.117212E+10 | 0.223712E+10 | 0.00 | 0.00 |
September | 0.535677E+10 | 0.589382E+09 | 0.292254E+10 | 0.100476E+10 | 0.191778E+10 | 0.00 | 0.00 |
October | 0.517687E+10 | 0.108506E+10 | 0.298434E+10 | 0.125938E+10 | 0.172496E+10 | 0.00 | 0.00 |
November | 0.352020E+10 | 0.219863E+10 | 0.255697E+10 | 0.130441E+10 | 0.125256E+10 | 0.00 | 0.00 |
December | 0.256019E+10 | 0.305798E+10 | 0.208032E+10 | 0.942340E+09 | 0.113798E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.605178E+11 | 0.192372E+11 | 0.371707E+11 | 0.159108E+11 | 0.212599E+11 | 0.00 | 0.00 |
Minimum of Months | 0.256019E+10 | 0.324566E+09 | 0.208032E+10 | 0.942340E+09 | 0.113798E+10 | 0.00 | 0.00 |
Maximum of Months | 0.716982E+10 | 0.349587E+10 | 0.378378E+10 | 0.164072E+10 | 0.234587E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.119631E+11 | 0.554923E+10 | 0.860368E+10 | 0.613591E+10 | 0.246776E+10 | 0.00 | 0.00 |
February | 0.100262E+11 | 0.428763E+10 | 0.704791E+10 | 0.456200E+10 | 0.248592E+10 | 0.00 | 0.00 |
March | 0.729581E+10 | 0.423525E+10 | 0.498163E+10 | 0.224822E+10 | 0.273342E+10 | 0.00 | 0.00 |
April | 0.582845E+10 | 0.271513E+10 | 0.357322E+10 | 0.837293E+09 | 0.273592E+10 | 0.00 | 0.00 |
May | 0.587370E+10 | 0.860355E+09 | 0.282120E+10 | 0.119897E+09 | 0.270131E+10 | 0.00 | 0.00 |
June | 0.584509E+10 | 0.713385E+09 | 0.269697E+10 | 25138330.74 | 0.267183E+10 | 0.00 | 0.00 |
July | 0.624300E+10 | 0.475581E+09 | 0.291740E+10 | 53621437.41 | 0.286378E+10 | 0.00 | 0.00 |
August | 0.736266E+10 | 0.719733E+09 | 0.343216E+10 | 0.411963E+09 | 0.302020E+10 | 0.00 | 0.00 |
September | 0.780132E+10 | 0.992234E+09 | 0.398518E+10 | 0.105026E+10 | 0.293492E+10 | 0.00 | 0.00 |
October | 0.114360E+11 | 0.187923E+10 | 0.638914E+10 | 0.332814E+10 | 0.306100E+10 | 0.00 | 0.00 |
November | 0.120054E+11 | 0.366661E+10 | 0.786832E+10 | 0.541742E+10 | 0.245090E+10 | 0.00 | 0.00 |
December | 0.122443E+11 | 0.493730E+10 | 0.840684E+10 | 0.603734E+10 | 0.236950E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.103925E+12 | 0.310317E+11 | 0.627237E+11 | 0.302272E+11 | 0.324964E+11 | 0.00 | 0.00 |
Minimum of Months | 0.582845E+10 | 0.475581E+09 | 0.269697E+10 | 25138330.74 | 0.236950E+10 | 0.00 | 0.00 |
Maximum of Months | 0.122443E+11 | 0.554923E+10 | 0.860368E+10 | 0.613591E+10 | 0.306100E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.340325E+10 | 0.387360E+10 | 0.271639E+10 | 0.146887E+10 | 0.124752E+10 | 0.00 | 0.00 |
February | 0.360415E+10 | 0.298400E+10 | 0.277792E+10 | 0.140601E+10 | 0.137191E+10 | 0.00 | 0.00 |
March | 0.408591E+10 | 0.291659E+10 | 0.303127E+10 | 0.134187E+10 | 0.168940E+10 | 0.00 | 0.00 |
April | 0.559909E+10 | 0.192240E+10 | 0.364347E+10 | 0.167607E+10 | 0.196741E+10 | 0.00 | 0.00 |
May | 0.600247E+10 | 0.669724E+09 | 0.313098E+10 | 0.101992E+10 | 0.211105E+10 | 0.00 | 0.00 |
June | 0.658646E+10 | 0.578740E+09 | 0.336596E+10 | 0.118026E+10 | 0.218569E+10 | 0.00 | 0.00 |
July | 0.621149E+10 | 0.412207E+09 | 0.317491E+10 | 0.880669E+09 | 0.229424E+10 | 0.00 | 0.00 |
August | 0.629628E+10 | 0.567751E+09 | 0.321023E+10 | 0.982696E+09 | 0.222754E+10 | 0.00 | 0.00 |
September | 0.530933E+10 | 0.695739E+09 | 0.286072E+10 | 0.981365E+09 | 0.187936E+10 | 0.00 | 0.00 |
October | 0.537496E+10 | 0.126793E+10 | 0.302642E+10 | 0.130768E+10 | 0.171874E+10 | 0.00 | 0.00 |
November | 0.365931E+10 | 0.248199E+10 | 0.251032E+10 | 0.126159E+10 | 0.124874E+10 | 0.00 | 0.00 |
December | 0.331839E+10 | 0.336000E+10 | 0.249521E+10 | 0.132692E+10 | 0.116829E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.594511E+11 | 0.217307E+11 | 0.359438E+11 | 0.148339E+11 | 0.211099E+11 | 0.00 | 0.00 |
Minimum of Months | 0.331839E+10 | 0.412207E+09 | 0.249521E+10 | 0.880669E+09 | 0.116829E+10 | 0.00 | 0.00 |
Maximum of Months | 0.658646E+10 | 0.387360E+10 | 0.364347E+10 | 0.167607E+10 | 0.229424E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 13.57 | 11.02 | 8.64 | 3.24 | 3.13 | 48.31 | 209.17 | 0.01 |
February | 15.49 | 12.82 | 10.40 | 2.82 | 4.36 | 58.07 | 218.23 | 0.02 |
March | 17.07 | 13.58 | 10.72 | 3.68 | 7.24 | 76.61 | 186.08 | 0.03 |
April | 21.23 | 17.54 | 15.23 | 2.65 | 11.47 | 90.28 | 216.86 | 0.02 |
May | 26.90 | 22.82 | 21.10 | 3.11 | 19.64 | 106.10 | 173.47 | 0.04 |
June | 27.61 | 23.37 | 21.62 | 2.44 | 19.77 | 115.40 | 187.69 | 0.03 |
July | 27.94 | 24.58 | 23.34 | 2.53 | 20.70 | 123.49 | 154.05 | 0.05 |
August | 27.43 | 23.90 | 22.52 | 3.20 | 20.40 | 118.51 | 145.78 | 0.03 |
September | 26.23 | 23.37 | 22.24 | 3.39 | 19.02 | 101.73 | 135.58 | 0.05 |
October | 24.23 | 20.47 | 18.40 | 4.11 | 16.60 | 78.24 | 178.15 | 0.01 |
November | 18.91 | 15.31 | 12.62 | 2.63 | 7.99 | 49.56 | 205.43 | 0.01 |
December | 15.68 | 12.88 | 10.53 | 3.17 | 6.01 | 45.08 | 191.18 | 0.02 |
Annual Sum or Average | 21.89 | 18.50 | 16.48 | 3.09 | 13.08 | 84.44 | 183.16 | 0.03 |
Minimum of Months | 13.57 | 11.02 | 8.64 | 2.44 | 3.13 | 45.08 | 135.58 | 0.01 |
Maximum of Months | 27.94 | 24.58 | 23.34 | 4.11 | 20.70 | 123.49 | 218.23 | 0.05 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 27.00 | 02-JAN-14:00 | 18.67 | 14.00 | 1.50 | 17.75 | 146.50 | 0.00 |
February | 28.30 | 02-FEB-12:00 | 20.78 | 17.20 | 6.60 | 17.93 | 127.50 | 748.50 |
March | 30.00 | 26-MAR-13:00 | 19.88 | 14.40 | 3.00 | 19.52 | 288.50 | 548.00 |
April | 33.30 | 28-APR-14:00 | 23.06 | 18.80 | 4.10 | 23.15 | 150.50 | 762.50 |
May | 33.90 | 07-MAY-13:00 | 23.76 | 19.40 | 4.10 | 23.15 | 287.50 | 507.50 |
June | 35.00 | 14-JUN-13:00 | 23.95 | 19.40 | 2.10 | 24.16 | 194.50 | 712.50 |
July | 36.10 | 21-JUL-15:00 | 25.96 | 22.20 | 1.50 | 26.65 | 216.00 | 245.00 |
August | 36.30 | 30-AUG-15:00 | 23.74 | 18.50 | 2.40 | 25.33 | 116.00 | 698.50 |
September | 36.40 | 09-SEP-16:00 | 26.65 | 23.40 | 4.40 | 26.48 | 114.00 | 401.50 |
October | 34.00 | 05-OCT-14:00 | 24.05 | 20.00 | 2.60 | 29.55 | 169.50 | 606.00 |
November | 30.00 | 01-NOV-13:00 | 25.01 | 23.30 | 2.00 | 26.48 | 216.50 | 118.00 |
December | 30.00 | 13-DEC-14:00 | 21.84 | 18.00 | 3.10 | 20.92 | 101.50 | 682.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 27.00 | 18.67 | 14.00 | 1.50 | 17.75 | 101.50 | 0.00 | |
Maximum of Months | 36.40 | 26.65 | 23.40 | 6.60 | 29.55 | 288.50 | 762.50 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 0.00 | 05-JAN-05:00 | -0.0 | -0.0 | 2.10 | -16.0 | 0.00 | 0.00 |
February | -3.4 | 05-FEB-07:10 | -5.4 | -9.4 | 4.68 | -21.3 | 0.00 | 0.00 |
March | 1.10 | 09-MAR-05:00 | -2.1 | -7.3 | 3.60 | -14.4 | 0.00 | 0.00 |
April | 8.30 | 11-APR-05:00 | 6.95 | 5.50 | 0.00 | -6.9 | 0.00 | 0.00 |
May | 21.10 | 07-MAY-00:00 | 19.58 | 18.90 | 0.00 | 11.46 | 0.00 | 0.00 |
June | 20.60 | 07-JUN-01:00 | 18.00 | 16.70 | 3.60 | 10.50 | 0.00 | 0.00 |
July | 22.20 | 11-JUL-19:00 | 21.37 | 21.10 | 2.10 | 20.22 | 0.00 | 0.00 |
August | 20.20 | 25-AUG-23:00 | 20.20 | 20.20 | 5.30 | 11.84 | 0.00 | 0.00 |
September | 19.20 | 07-SEP-17:00 | 19.20 | 19.20 | 2.50 | 16.85 | 35.00 | 7.00 |
October | 10.00 | 28-OCT-04:00 | 5.56 | 0.00 | 3.60 | -0.1 | 0.00 | 0.00 |
November | 7.20 | 12-NOV-07:49 | 4.12 | 0.18 | 4.60 | -9.0 | 36.00 | 517.00 |
December | 0.00 | 21-DEC-04:00 | -0.9 | -2.0 | 2.10 | -16.2 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -3.4 | -5.4 | -9.4 | 0.00 | -21.3 | 0.00 | 0.00 | |
Maximum of Months | 22.20 | 21.37 | 21.10 | 5.30 | 20.22 | 36.00 | 517.00 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 22.11 | 31-JAN-12:00 | 25.00 | 21.00 | 5.70 | 20.92 | 336.50 | 96.00 |
February | 21.49 | 24-FEB-12:00 | 27.70 | 18.80 | 4.10 | 17.75 | 165.00 | 746.50 |
March | 22.77 | 30-MAR-12:00 | 29.40 | 20.00 | 2.50 | 27.14 | 340.00 | 0.00 |
April | 25.55 | 28-APR-15:00 | 32.20 | 23.30 | 3.60 | 22.47 | 156.00 | 575.50 |
May | 25.84 | 27-MAY-13:00 | 31.70 | 23.90 | 3.10 | 22.13 | 168.50 | 735.50 |
June | 26.52 | 29-JUN-16:00 | 29.40 | 25.60 | 1.50 | 26.32 | 164.00 | 36.00 |
July | 27.17 | 22-JUL-10:00 | 32.20 | 25.60 | 2.10 | 21.96 | 191.00 | 719.50 |
August | 27.24 | 07-AUG-12:00 | 31.00 | 26.00 | 3.10 | 27.95 | 473.00 | 200.00 |
September | 27.79 | 10-SEP-12:00 | 35.00 | 25.50 | 2.90 | 24.66 | 239.50 | 662.00 |
October | 28.18 | 07-OCT-07:00 | 29.00 | 28.00 | 2.60 | 21.09 | 95.00 | 500.50 |
November | 25.01 | 01-NOV-13:00 | 30.00 | 23.30 | 2.00 | 26.48 | 216.50 | 118.00 |
December | 24.12 | 12-DEC-13:00 | 27.00 | 23.00 | 2.10 | 19.17 | 160.50 | 599.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 21.49 | 25.00 | 18.80 | 1.50 | 17.75 | 95.00 | 0.00 | |
Maximum of Months | 28.18 | 35.00 | 28.00 | 5.70 | 27.95 | 473.00 | 746.50 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 21.00 | 31-JAN-12:00 | 25.00 | 22.11 | 5.70 | 20.92 | 336.50 | 96.00 |
February | 20.20 | 02-FEB-22:00 | 21.50 | 20.56 | 4.80 | 14.65 | 0.00 | 0.00 |
March | 21.10 | 07-MAR-08:00 | 23.30 | 21.69 | 2.00 | 13.91 | 126.00 | 566.50 |
April | 23.30 | 28-APR-15:00 | 32.20 | 25.55 | 3.60 | 22.47 | 156.00 | 575.50 |
May | 24.40 | 26-MAY-08:20 | 27.07 | 25.09 | 3.10 | 23.71 | 252.67 | 47.33 |
June | 25.60 | 29-JUN-14:00 | 27.20 | 26.00 | 5.10 | 24.16 | 335.00 | 238.00 |
July | 25.60 | 02-JUL-05:00 | 26.10 | 25.71 | 2.60 | 19.52 | 30.50 | 8.50 |
August | 26.60 | 09-AUG-18:00 | 26.60 | 26.60 | 1.90 | 19.52 | 26.00 | 23.00 |
September | 25.50 | 10-SEP-12:00 | 35.00 | 27.79 | 2.90 | 24.66 | 239.50 | 662.00 |
October | 28.00 | 07-OCT-07:00 | 29.00 | 28.18 | 2.60 | 21.09 | 95.00 | 500.50 |
November | 23.80 | 01-NOV-10:00 | 26.10 | 24.39 | 2.00 | 22.64 | 228.50 | 113.00 |
December | 23.00 | 12-DEC-13:00 | 27.00 | 24.12 | 2.10 | 19.17 | 160.50 | 599.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 20.20 | 21.50 | 20.56 | 1.90 | 13.91 | 0.00 | 0.00 | |
Maximum of Months | 28.00 | 35.00 | 28.18 | 5.70 | 24.66 | 336.50 | 662.00 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 20.46 | 29.60 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 20.78 | 36.65 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 22.23 | 38.94 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 24.49 | 49.11 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 26.95 | 46.95 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 28.93 | 51.71 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 29.89 | 48.43 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 29.58 | 45.50 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 28.08 | 39.22 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 25.80 | 37.51 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 23.35 | 31.26 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 21.40 | 27.18 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 25.18 | 40.17 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 20.46 | 27.18 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 29.89 | 51.71 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.316629E+11 | -0.306421E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.102089E+10 | 58.98 | 0.00 | 0.00 |
February | 0.285423E+11 | -0.276197E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -922612928.2 | 58.97 | 0.00 | 0.00 |
March | 0.322667E+11 | -0.312422E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.102452E+10 | 58.97 | 0.00 | 0.00 |
April | 0.275746E+11 | -0.265867E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -987929281.1 | 58.97 | 0.00 | 0.00 |
May | 0.274178E+11 | -0.263962E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.102157E+10 | 58.97 | 0.00 | 0.00 |
June | 0.255234E+11 | -0.245329E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -990430300.4 | 58.97 | 0.00 | 0.00 |
July | 0.235913E+11 | -0.225732E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.101810E+10 | 58.98 | 0.00 | 0.00 |
August | 0.260136E+11 | -0.249922E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.102137E+10 | 58.97 | 0.00 | 0.00 |
September | 0.248295E+11 | -0.238439E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -985589927.8 | 58.97 | 0.00 | 0.00 |
October | 0.274226E+11 | -0.264056E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.101702E+10 | 58.97 | 0.00 | 0.00 |
November | 0.287879E+11 | -0.278039E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -983986707.8 | 58.97 | 0.00 | 0.00 |
December | 0.301973E+11 | -0.291798E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.101746E+10 | 58.98 | 0.00 | 0.00 |
Annual Sum or Average | 0.333830E+12 | -0.321818E+12 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.120115E+11 | 58.97 | 0.00 | 0.00 |
Minimum of Months | 0.235913E+11 | -0.312422E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -0.102452E+10 | 58.97 | 0.00 | 0.00 |
Maximum of Months | 0.322667E+11 | -0.225732E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -922612928.2 | 58.98 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_1_DAYLCTRL
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 307.33 | 0.51 | 0.48 | 01-JAN-07:49 | 7786.26 | 36.98 | 300.33 | 296.17 | 1440.04 | 25.99 | 217.50 | 278.83 |
February | 295.50 | 0.51 | 0.48 | 01-FEB-11:39 | 3382.90 | 28.27 | 173.83 | 280.00 | 1249.28 | 23.24 | 187.00 | 266.50 |
March | 296.00 | 0.52 | 0.48 | 02-MAR-12:39 | 1588.85 | 20.03 | 57.33 | 319.67 | 927.46 | 21.36 | 175.00 | 281.33 |
April | 347.33 | 0.53 | 0.48 | 01-APR-07:00 | 1263.77 | 19.23 | 30.83 | 323.83 | 728.41 | 20.54 | 172.83 | 284.50 |
May | 353.67 | 0.52 | 0.48 | 01-MAY-07:40 | 1129.55 | 19.48 | 9.17 | 349.67 | 635.44 | 20.83 | 167.33 | 300.00 |
June | 394.00 | 0.53 | 0.48 | 01-JUN-07:10 | 1073.17 | 19.12 | 2.67 | 350.50 | 607.48 | 20.48 | 167.67 | 303.83 |
July | 390.00 | 0.52 | 0.48 | 01-JUL-07:10 | 1183.45 | 19.48 | 15.50 | 360.00 | 649.86 | 20.82 | 195.50 | 313.33 |
August | 380.83 | 0.52 | 0.48 | 01-AUG-07:30 | 1373.81 | 19.77 | 43.83 | 346.67 | 739.31 | 21.09 | 241.67 | 307.67 |
September | 342.17 | 0.52 | 0.48 | 01-SEP-07:30 | 1616.16 | 20.06 | 89.67 | 317.83 | 854.96 | 21.30 | 227.00 | 282.00 |
October | 330.00 | 0.50 | 0.48 | 01-OCT-07:19 | 2786.45 | 23.95 | 168.67 | 314.50 | 1159.34 | 22.39 | 238.00 | 283.33 |
November | 308.00 | 0.51 | 0.48 | 01-NOV-08:09 | 7858.82 | 36.41 | 297.33 | 288.67 | 1372.11 | 24.19 | 202.17 | 271.17 |
December | 282.83 | 0.50 | 0.48 | 01-DEC-07:49 | 7936.92 | 37.75 | 279.33 | 284.33 | 1828.58 | 27.88 | 207.17 | 267.17 |
Annual Sum or Average | 4027.67 | 0.52 | 3040.67 | 24.46 | 1468.50 | 3831.83 | 981.52 | 22.32 | 2398.83 | 3439.67 | ||
Minimum of Months | 282.83 | 0.50 | 0.48 | 1073.17 | 19.12 | 2.67 | 280.00 | 607.48 | 20.48 | 167.33 | 266.50 | |
Maximum of Months | 394.00 | 0.53 | 0.48 | 7936.92 | 37.75 | 300.33 | 360.00 | 1828.58 | 27.88 | 241.67 | 313.33 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_2_DAYLCTRL
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 307.33 | 0.54 | 0.48 | 01-JAN-07:49 | 2000.21 | 23.67 | 104.83 | 271.17 | 1078.28 | 23.74 | 125.83 | 223.67 |
February | 295.50 | 0.53 | 0.48 | 01-FEB-11:39 | 2214.40 | 23.75 | 91.00 | 261.50 | 1174.55 | 23.90 | 114.17 | 228.17 |
March | 296.00 | 0.52 | 0.48 | 02-MAR-12:39 | 2306.25 | 23.72 | 86.33 | 315.83 | 1218.46 | 23.85 | 123.33 | 276.67 |
April | 347.33 | 0.53 | 0.48 | 01-APR-07:19 | 2360.31 | 22.80 | 96.00 | 326.50 | 1252.79 | 23.17 | 122.33 | 293.50 |
May | 353.67 | 0.51 | 0.48 | 01-MAY-06:40 | 2670.74 | 24.09 | 112.00 | 360.50 | 1070.54 | 23.07 | 128.33 | 315.17 |
June | 394.00 | 0.52 | 0.48 | 01-JUN-06:10 | 2402.01 | 23.71 | 123.17 | 359.17 | 1013.23 | 22.97 | 146.83 | 321.50 |
July | 390.00 | 0.51 | 0.48 | 01-JUL-06:30 | 2312.68 | 23.18 | 113.00 | 365.50 | 994.88 | 22.43 | 159.00 | 318.67 |
August | 380.83 | 0.52 | 0.48 | 01-AUG-06:49 | 2130.59 | 23.09 | 106.33 | 347.33 | 1109.20 | 23.49 | 172.00 | 308.33 |
September | 342.17 | 0.53 | 0.48 | 01-SEP-06:49 | 2035.16 | 23.21 | 101.33 | 314.50 | 1039.86 | 23.50 | 171.33 | 278.83 |
October | 330.00 | 0.52 | 0.48 | 01-OCT-06:49 | 2117.80 | 23.43 | 93.67 | 303.17 | 1082.90 | 23.57 | 160.83 | 269.83 |
November | 308.00 | 0.53 | 0.48 | 01-NOV-07:00 | 1759.14 | 22.81 | 86.17 | 267.33 | 901.40 | 22.85 | 124.50 | 230.83 |
December | 282.83 | 0.54 | 0.48 | 01-DEC-07:49 | 1893.03 | 23.41 | 91.83 | 257.83 | 1008.71 | 23.43 | 111.67 | 208.17 |
Annual Sum or Average | 4027.67 | 0.52 | 2196.88 | 23.40 | 1205.67 | 3750.33 | 1077.20 | 23.30 | 1660.17 | 3273.33 | ||
Minimum of Months | 282.83 | 0.51 | 0.48 | 1759.14 | 22.80 | 86.17 | 257.83 | 901.40 | 22.43 | 111.67 | 208.17 | |
Maximum of Months | 394.00 | 0.54 | 0.48 | 2670.74 | 24.09 | 123.17 | 365.50 | 1252.79 | 23.90 | 172.00 | 321.50 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_3_DAYLCTRL
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 307.33 | 0.57 | 0.48 | 01-JAN-09:30 | 546.90 | 16.27 | 0.00 | 252.17 | 353.84 | 17.94 | 0.00 | 165.33 |
February | 295.50 | 0.55 | 0.48 | 01-FEB-11:00 | 631.61 | 17.44 | 0.00 | 248.50 | 410.11 | 19.03 | 2.83 | 184.67 |
March | 296.00 | 0.53 | 0.48 | 02-MAR-12:50 | 738.24 | 18.44 | 0.00 | 306.67 | 463.86 | 19.83 | 11.50 | 237.17 |
April | 347.33 | 0.53 | 0.48 | 01-APR-08:09 | 878.76 | 18.84 | 0.00 | 327.00 | 534.99 | 20.14 | 82.17 | 285.17 |
May | 353.67 | 0.50 | 0.48 | 01-MAY-07:19 | 1078.31 | 21.06 | 58.50 | 370.33 | 620.51 | 22.23 | 189.50 | 330.67 |
June | 394.00 | 0.51 | 0.48 | 01-JUN-06:40 | 1247.26 | 22.17 | 110.17 | 374.17 | 657.49 | 21.36 | 219.00 | 338.33 |
July | 390.00 | 0.50 | 0.48 | 01-JUL-06:49 | 1219.85 | 20.87 | 81.50 | 376.67 | 662.14 | 22.15 | 243.17 | 340.50 |
August | 380.83 | 0.51 | 0.48 | 01-AUG-07:19 | 1070.66 | 19.61 | 12.50 | 353.33 | 601.34 | 20.91 | 178.00 | 318.17 |
September | 342.17 | 0.53 | 0.48 | 01-SEP-07:40 | 896.84 | 18.83 | 0.33 | 316.00 | 515.72 | 20.12 | 76.67 | 265.33 |
October | 330.00 | 0.52 | 0.48 | 01-OCT-08:09 | 774.15 | 18.59 | 0.00 | 297.17 | 473.64 | 20.05 | 14.83 | 244.50 |
November | 308.00 | 0.57 | 0.48 | 01-NOV-10:20 | 562.03 | 16.88 | 0.00 | 243.33 | 365.55 | 18.53 | 0.00 | 170.00 |
December | 282.83 | 0.56 | 0.48 | 01-DEC-09:20 | 547.39 | 16.53 | 0.00 | 242.83 | 355.86 | 18.26 | 0.00 | 149.33 |
Annual Sum or Average | 4027.67 | 0.53 | 875.19 | 18.97 | 263.00 | 3708.17 | 512.66 | 20.17 | 1017.67 | 3029.17 | ||
Minimum of Months | 282.83 | 0.50 | 0.48 | 546.90 | 16.27 | 0.00 | 242.83 | 353.84 | 17.94 | 0.00 | 149.33 | |
Maximum of Months | 394.00 | 0.57 | 0.48 | 1247.26 | 22.17 | 110.17 | 376.67 | 662.14 | 22.23 | 243.17 | 340.50 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_4_DAYLCTRL
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 307.33 | 0.54 | 0.48 | 01-JAN-09:30 | 2289.76 | 24.59 | 112.83 | 275.83 | 1268.49 | 24.49 | 129.00 | 230.33 |
February | 295.50 | 0.52 | 0.48 | 01-FEB-11:50 | 2045.06 | 23.85 | 89.33 | 266.17 | 1077.68 | 23.85 | 129.17 | 234.17 |
March | 296.00 | 0.52 | 0.48 | 02-MAR-12:39 | 2193.49 | 23.23 | 81.00 | 311.83 | 1151.04 | 23.54 | 115.50 | 269.67 |
April | 347.33 | 0.53 | 0.48 | 01-APR-08:39 | 2478.55 | 21.71 | 82.83 | 327.00 | 1300.55 | 22.13 | 110.00 | 293.67 |
May | 353.67 | 0.51 | 0.48 | 01-MAY-08:09 | 2053.81 | 18.25 | 1.17 | 356.83 | 908.14 | 20.36 | 102.67 | 318.00 |
June | 394.00 | 0.52 | 0.48 | 01-JUN-07:30 | 2174.13 | 18.12 | 0.67 | 359.00 | 926.65 | 20.16 | 105.17 | 318.50 |
July | 390.00 | 0.51 | 0.48 | 01-JUL-07:30 | 2011.73 | 18.60 | 6.50 | 366.00 | 894.05 | 20.41 | 122.83 | 322.33 |
August | 380.83 | 0.52 | 0.48 | 01-AUG-07:00 | 2077.42 | 20.54 | 59.17 | 349.50 | 951.12 | 20.64 | 138.67 | 309.67 |
September | 342.17 | 0.52 | 0.48 | 01-SEP-07:00 | 1927.49 | 21.95 | 82.33 | 314.83 | 987.33 | 22.34 | 154.17 | 279.17 |
October | 330.00 | 0.51 | 0.48 | 01-OCT-08:20 | 2465.57 | 24.59 | 110.67 | 309.50 | 1018.50 | 23.47 | 167.33 | 273.00 |
November | 308.00 | 0.53 | 0.48 | 01-NOV-10:09 | 1986.50 | 23.75 | 96.67 | 267.33 | 1067.36 | 23.80 | 125.33 | 231.67 |
December | 282.83 | 0.52 | 0.48 | 01-DEC-09:20 | 2132.83 | 25.21 | 107.17 | 271.00 | 1151.82 | 24.96 | 125.00 | 219.83 |
Annual Sum or Average | 4027.67 | 0.52 | 2151.40 | 21.79 | 830.33 | 3774.83 | 1049.34 | 22.34 | 1524.83 | 3300.00 | ||
Minimum of Months | 282.83 | 0.51 | 0.48 | 1927.49 | 18.12 | 0.67 | 266.17 | 894.05 | 20.16 | 102.67 | 219.83 | |
Maximum of Months | 394.00 | 0.54 | 0.48 | 2478.55 | 25.21 | 112.83 | 366.00 | 1300.55 | 24.96 | 167.33 | 322.33 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_1_DAYLCTRL
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 307.33 | 0.51 | 0.48 | 01-JAN-07:49 | 7850.13 | 36.48 | 297.33 | 296.17 | 1541.59 | 21.76 | 92.17 | 281.67 |
February | 295.50 | 0.51 | 0.48 | 01-FEB-11:39 | 3438.86 | 24.69 | 165.33 | 280.00 | 1342.31 | 18.95 | 36.50 | 268.17 |
March | 296.00 | 0.51 | 0.48 | 02-MAR-12:39 | 1627.98 | 13.82 | 0.00 | 320.50 | 995.70 | 17.39 | 0.00 | 286.33 |
April | 347.33 | 0.53 | 0.48 | 01-APR-07:00 | 1289.25 | 13.40 | 0.00 | 324.17 | 778.39 | 16.82 | 0.00 | 290.00 |
May | 353.67 | 0.52 | 0.48 | 01-MAY-07:40 | 1147.48 | 13.62 | 0.00 | 350.83 | 676.56 | 17.07 | 0.00 | 305.67 |
June | 394.00 | 0.53 | 0.48 | 01-JUN-07:10 | 1089.95 | 13.27 | 0.00 | 351.17 | 646.66 | 16.70 | 0.00 | 308.33 |
July | 390.00 | 0.52 | 0.48 | 01-JUL-06:00 | 1200.05 | 13.49 | 0.00 | 360.50 | 691.15 | 16.90 | 0.00 | 319.00 |
August | 380.83 | 0.52 | 0.48 | 01-AUG-07:30 | 1392.37 | 13.76 | 0.00 | 347.00 | 786.61 | 17.14 | 0.00 | 313.00 |
September | 342.17 | 0.52 | 0.48 | 01-SEP-07:30 | 1636.22 | 13.92 | 3.67 | 318.17 | 910.28 | 17.14 | 0.00 | 286.83 |
October | 330.00 | 0.50 | 0.48 | 01-OCT-07:19 | 2826.10 | 18.78 | 80.67 | 314.83 | 1246.46 | 18.29 | 10.50 | 288.33 |
November | 308.00 | 0.51 | 0.48 | 01-NOV-08:09 | 7915.39 | 35.90 | 296.17 | 289.17 | 1502.83 | 21.57 | 90.83 | 276.50 |
December | 282.83 | 0.50 | 0.48 | 01-DEC-07:49 | 7999.34 | 37.35 | 279.33 | 284.33 | 1935.63 | 23.99 | 110.83 | 268.67 |
Annual Sum or Average | 4027.67 | 0.52 | 3074.96 | 19.96 | 1122.50 | 3836.83 | 1050.69 | 18.46 | 340.83 | 3492.50 | ||
Minimum of Months | 282.83 | 0.50 | 0.48 | 1089.95 | 13.27 | 0.00 | 280.00 | 646.66 | 16.70 | 0.00 | 268.17 | |
Maximum of Months | 394.00 | 0.53 | 0.48 | 7999.34 | 37.35 | 297.33 | 360.50 | 1935.63 | 23.99 | 110.83 | 319.00 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_2_DAYLCTRL
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 307.33 | 0.54 | 0.48 | 01-JAN-07:49 | 2033.75 | 21.18 | 100.17 | 273.00 | 1122.73 | 21.84 | 72.33 | 229.83 |
February | 295.50 | 0.53 | 0.48 | 01-FEB-11:39 | 2256.37 | 21.01 | 89.67 | 262.67 | 1223.72 | 21.82 | 64.33 | 231.83 |
March | 296.00 | 0.52 | 0.48 | 02-MAR-12:39 | 2331.38 | 19.47 | 74.33 | 316.33 | 1279.71 | 21.40 | 56.50 | 282.33 |
April | 347.33 | 0.53 | 0.48 | 01-APR-07:19 | 2390.38 | 19.76 | 95.83 | 327.17 | 1309.17 | 20.74 | 68.00 | 297.00 |
May | 353.67 | 0.51 | 0.48 | 01-MAY-06:40 | 2689.83 | 20.42 | 106.00 | 361.33 | 1129.78 | 20.41 | 55.00 | 321.17 |
June | 394.00 | 0.52 | 0.48 | 01-JUN-06:10 | 2429.98 | 19.87 | 114.00 | 359.50 | 1068.25 | 20.36 | 62.67 | 326.83 |
July | 390.00 | 0.51 | 0.48 | 01-JUL-06:30 | 2342.91 | 20.11 | 112.33 | 366.67 | 1049.40 | 19.76 | 53.67 | 323.83 |
August | 380.83 | 0.52 | 0.48 | 01-AUG-06:49 | 2153.48 | 20.02 | 105.17 | 347.83 | 1161.35 | 21.12 | 75.50 | 313.00 |
September | 342.17 | 0.53 | 0.48 | 01-SEP-06:49 | 2071.56 | 20.22 | 96.00 | 314.67 | 1089.88 | 21.15 | 67.50 | 282.17 |
October | 330.00 | 0.52 | 0.48 | 01-OCT-06:49 | 2164.81 | 20.46 | 87.67 | 303.33 | 1135.19 | 21.25 | 57.00 | 273.67 |
November | 308.00 | 0.53 | 0.48 | 01-NOV-07:00 | 1793.86 | 19.98 | 84.00 | 267.83 | 946.46 | 20.66 | 55.50 | 235.00 |
December | 282.83 | 0.54 | 0.48 | 01-DEC-07:49 | 1922.70 | 20.92 | 89.17 | 258.67 | 1050.13 | 21.58 | 61.67 | 214.33 |
Annual Sum or Average | 4027.67 | 0.52 | 2228.15 | 20.26 | 1154.33 | 3759.00 | 1129.25 | 20.95 | 749.67 | 3331.00 | ||
Minimum of Months | 282.83 | 0.51 | 0.48 | 1793.86 | 19.47 | 74.33 | 258.67 | 946.46 | 19.76 | 53.67 | 214.33 | |
Maximum of Months | 394.00 | 0.54 | 0.48 | 2689.83 | 21.18 | 114.00 | 366.67 | 1309.17 | 21.84 | 75.50 | 326.83 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_3_DAYLCTRL
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 307.33 | 0.57 | 0.48 | 01-JAN-09:20 | 556.74 | 10.78 | 0.00 | 253.00 | 377.15 | 14.41 | 0.00 | 180.67 |
February | 295.50 | 0.55 | 0.48 | 01-FEB-11:00 | 643.97 | 12.00 | 0.00 | 249.67 | 437.40 | 15.63 | 0.00 | 194.00 |
March | 296.00 | 0.53 | 0.48 | 02-MAR-12:39 | 753.69 | 13.19 | 0.00 | 307.83 | 494.96 | 16.69 | 0.00 | 249.67 |
April | 347.33 | 0.53 | 0.48 | 01-APR-07:00 | 897.04 | 13.45 | 0.00 | 327.33 | 570.73 | 16.88 | 0.00 | 292.00 |
May | 353.67 | 0.50 | 0.48 | 01-MAY-07:10 | 1097.99 | 15.69 | 27.17 | 370.83 | 661.02 | 19.01 | 27.50 | 336.17 |
June | 394.00 | 0.50 | 0.48 | 01-JUN-06:30 | 1268.08 | 17.20 | 58.00 | 374.67 | 709.89 | 20.33 | 59.33 | 348.67 |
July | 390.00 | 0.50 | 0.48 | 01-JUL-06:49 | 1239.18 | 15.32 | 23.50 | 376.67 | 704.31 | 18.63 | 24.50 | 343.50 |
August | 380.83 | 0.51 | 0.48 | 01-AUG-07:19 | 1088.05 | 13.88 | 0.00 | 353.67 | 639.75 | 17.28 | 0.00 | 322.00 |
September | 342.17 | 0.53 | 0.48 | 01-SEP-07:30 | 912.18 | 13.27 | 0.00 | 316.00 | 548.87 | 16.61 | 0.00 | 271.33 |
October | 330.00 | 0.52 | 0.48 | 01-OCT-07:00 | 788.02 | 13.20 | 0.00 | 297.50 | 504.55 | 16.70 | 0.00 | 252.67 |
November | 308.00 | 0.56 | 0.48 | 01-NOV-10:09 | 572.42 | 11.30 | 0.00 | 245.17 | 389.72 | 14.99 | 0.00 | 181.67 |
December | 282.83 | 0.56 | 0.48 | 01-DEC-09:09 | 556.74 | 10.93 | 0.00 | 244.17 | 379.17 | 14.64 | 0.00 | 162.83 |
Annual Sum or Average | 4027.67 | 0.53 | 890.74 | 13.53 | 108.67 | 3716.50 | 547.04 | 16.98 | 111.33 | 3135.17 | ||
Minimum of Months | 282.83 | 0.50 | 0.48 | 556.74 | 10.78 | 0.00 | 244.17 | 377.15 | 14.41 | 0.00 | 162.83 | |
Maximum of Months | 394.00 | 0.57 | 0.48 | 1268.08 | 17.20 | 58.00 | 376.67 | 709.89 | 20.33 | 59.33 | 348.67 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_4_DAYLCTRL
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 307.33 | 0.53 | 0.48 | 01-JAN-09:20 | 2323.79 | 22.17 | 109.33 | 277.17 | 1314.89 | 22.70 | 81.83 | 237.67 |
February | 295.50 | 0.52 | 0.48 | 01-FEB-11:50 | 2064.52 | 19.86 | 79.17 | 267.33 | 1130.99 | 21.65 | 60.17 | 237.67 |
March | 296.00 | 0.52 | 0.48 | 02-MAR-12:39 | 2244.42 | 20.19 | 81.00 | 313.33 | 1205.07 | 21.14 | 56.67 | 277.00 |
April | 347.33 | 0.52 | 0.48 | 01-APR-08:39 | 2507.62 | 18.41 | 82.00 | 327.67 | 1358.06 | 19.43 | 53.00 | 297.83 |
May | 353.67 | 0.51 | 0.48 | 01-MAY-07:00 | 2078.19 | 13.74 | 0.00 | 357.33 | 958.84 | 17.14 | 0.00 | 321.17 |
June | 394.00 | 0.52 | 0.48 | 01-JUN-07:30 | 2202.07 | 13.63 | 0.00 | 359.17 | 977.86 | 16.97 | 0.00 | 324.50 |
July | 390.00 | 0.51 | 0.48 | 01-JUL-07:19 | 2035.10 | 14.19 | 3.67 | 366.83 | 943.12 | 17.27 | 0.00 | 328.17 |
August | 380.83 | 0.52 | 0.48 | 01-AUG-07:49 | 2101.22 | 16.87 | 59.00 | 350.83 | 1001.70 | 17.55 | 5.50 | 316.67 |
September | 342.17 | 0.52 | 0.48 | 01-SEP-07:00 | 1962.37 | 18.75 | 80.50 | 315.67 | 1036.15 | 19.81 | 51.67 | 283.17 |
October | 330.00 | 0.51 | 0.48 | 01-OCT-08:09 | 2512.40 | 21.92 | 108.83 | 310.17 | 1070.85 | 21.09 | 53.50 | 277.17 |
November | 308.00 | 0.53 | 0.48 | 01-NOV-09:00 | 2021.85 | 21.07 | 95.17 | 268.33 | 1112.77 | 21.77 | 66.67 | 236.33 |
December | 282.83 | 0.52 | 0.48 | 01-DEC-09:09 | 2168.60 | 22.86 | 103.00 | 271.50 | 1199.20 | 23.19 | 74.00 | 226.17 |
Annual Sum or Average | 4027.67 | 0.52 | 2183.08 | 18.34 | 801.67 | 3785.33 | 1099.95 | 19.75 | 503.00 | 3363.50 | ||
Minimum of Months | 282.83 | 0.51 | 0.48 | 1962.37 | 13.63 | 0.00 | 267.33 | 943.12 | 16.97 | 0.00 | 226.17 | |
Maximum of Months | 394.00 | 0.53 | 0.48 | 2512.40 | 22.86 | 109.33 | 366.83 | 1358.06 | 23.19 | 81.83 | 328.17 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_1_DAYLCTRL
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 307.33 | 0.51 | 0.48 | 01-JAN-07:49 | 7851.76 | 36.47 | 297.33 | 296.17 | 1543.26 | 21.75 | 92.17 | 281.67 |
February | 295.50 | 0.51 | 0.48 | 01-FEB-11:39 | 3441.09 | 24.67 | 165.33 | 280.00 | 1343.91 | 18.93 | 36.50 | 268.17 |
March | 296.00 | 0.51 | 0.48 | 02-MAR-12:39 | 1630.08 | 13.79 | 0.00 | 320.67 | 997.05 | 17.38 | 0.00 | 286.50 |
April | 347.33 | 0.53 | 0.48 | 01-APR-07:00 | 1290.93 | 13.37 | 0.00 | 324.17 | 779.48 | 16.80 | 0.00 | 290.00 |
May | 353.67 | 0.52 | 0.48 | 01-MAY-07:40 | 1149.02 | 13.59 | 0.00 | 350.83 | 677.56 | 17.06 | 0.00 | 305.83 |
June | 394.00 | 0.53 | 0.48 | 01-JUN-07:10 | 1091.39 | 13.24 | 0.00 | 351.17 | 647.59 | 16.68 | 0.00 | 308.33 |
July | 390.00 | 0.52 | 0.48 | 01-JUL-06:00 | 1201.80 | 13.47 | 0.00 | 360.50 | 692.22 | 16.89 | 0.00 | 319.00 |
August | 380.83 | 0.52 | 0.48 | 01-AUG-07:30 | 1394.53 | 13.73 | 0.00 | 347.00 | 787.88 | 17.12 | 0.00 | 313.00 |
September | 342.17 | 0.52 | 0.48 | 01-SEP-07:30 | 1638.83 | 13.89 | 3.67 | 318.17 | 911.83 | 17.13 | 0.00 | 287.17 |
October | 330.00 | 0.50 | 0.48 | 01-OCT-07:19 | 2828.95 | 18.76 | 80.67 | 314.83 | 1248.32 | 18.27 | 10.50 | 288.33 |
November | 308.00 | 0.51 | 0.48 | 01-NOV-08:09 | 7917.31 | 35.89 | 296.17 | 289.17 | 1504.49 | 21.56 | 90.83 | 276.50 |
December | 282.83 | 0.50 | 0.48 | 01-DEC-07:49 | 8000.93 | 37.34 | 279.33 | 284.33 | 1937.42 | 23.98 | 110.83 | 268.67 |
Annual Sum or Average | 4027.67 | 0.52 | 3076.91 | 19.93 | 1122.50 | 3837.00 | 1052.07 | 18.44 | 340.83 | 3493.17 | ||
Minimum of Months | 282.83 | 0.50 | 0.48 | 1091.39 | 13.24 | 0.00 | 280.00 | 647.59 | 16.68 | 0.00 | 268.17 | |
Maximum of Months | 394.00 | 0.53 | 0.48 | 8000.93 | 37.34 | 297.33 | 360.50 | 1937.42 | 23.98 | 110.83 | 319.00 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_2_DAYLCTRL
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 307.33 | 0.54 | 0.48 | 01-JAN-07:49 | 2034.48 | 21.15 | 100.17 | 273.17 | 1123.59 | 21.82 | 72.33 | 230.00 |
February | 295.50 | 0.53 | 0.48 | 01-FEB-11:39 | 2257.18 | 20.98 | 89.67 | 262.67 | 1224.70 | 21.80 | 64.33 | 232.17 |
March | 296.00 | 0.52 | 0.48 | 02-MAR-12:39 | 2332.51 | 19.44 | 74.33 | 316.33 | 1280.88 | 21.39 | 56.50 | 282.50 |
April | 347.33 | 0.53 | 0.48 | 01-APR-07:19 | 2391.79 | 19.73 | 95.67 | 327.17 | 1310.36 | 20.73 | 68.00 | 297.00 |
May | 353.67 | 0.51 | 0.48 | 01-MAY-06:40 | 2691.47 | 20.39 | 106.00 | 361.33 | 1131.13 | 20.39 | 55.00 | 321.17 |
June | 394.00 | 0.52 | 0.48 | 01-JUN-06:10 | 2431.78 | 19.84 | 114.00 | 359.50 | 1069.61 | 20.35 | 62.67 | 326.83 |
July | 390.00 | 0.51 | 0.48 | 01-JUL-06:30 | 2344.95 | 20.08 | 112.33 | 366.83 | 1050.88 | 19.74 | 53.67 | 323.83 |
August | 380.83 | 0.52 | 0.48 | 01-AUG-06:49 | 2155.50 | 20.00 | 105.17 | 348.00 | 1162.81 | 21.11 | 75.50 | 313.17 |
September | 342.17 | 0.53 | 0.48 | 01-SEP-06:49 | 2073.51 | 20.19 | 96.00 | 314.83 | 1091.31 | 21.14 | 67.50 | 282.17 |
October | 330.00 | 0.52 | 0.48 | 01-OCT-06:49 | 2166.17 | 20.43 | 87.67 | 303.33 | 1136.46 | 21.24 | 57.00 | 273.67 |
November | 308.00 | 0.53 | 0.48 | 01-NOV-07:00 | 1794.64 | 19.95 | 84.00 | 267.83 | 947.36 | 20.65 | 55.50 | 235.33 |
December | 282.83 | 0.54 | 0.48 | 01-DEC-07:49 | 1923.41 | 20.89 | 89.17 | 258.67 | 1050.98 | 21.56 | 61.67 | 214.83 |
Annual Sum or Average | 4027.67 | 0.52 | 2229.56 | 20.23 | 1154.17 | 3759.67 | 1130.46 | 20.94 | 749.67 | 3332.67 | ||
Minimum of Months | 282.83 | 0.51 | 0.48 | 1794.64 | 19.44 | 74.33 | 258.67 | 947.36 | 19.74 | 53.67 | 214.83 | |
Maximum of Months | 394.00 | 0.54 | 0.48 | 2691.47 | 21.15 | 114.00 | 366.83 | 1310.36 | 21.82 | 75.50 | 326.83 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_3_DAYLCTRL
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 307.33 | 0.57 | 0.48 | 01-JAN-09:20 | 557.07 | 10.74 | 0.00 | 253.00 | 377.55 | 14.39 | 0.00 | 181.00 |
February | 295.50 | 0.55 | 0.48 | 01-FEB-11:00 | 644.35 | 11.96 | 0.00 | 250.00 | 437.85 | 15.61 | 0.00 | 194.33 |
March | 296.00 | 0.53 | 0.48 | 02-MAR-12:39 | 754.28 | 13.16 | 0.00 | 307.83 | 495.52 | 16.68 | 0.00 | 250.00 |
April | 347.33 | 0.53 | 0.48 | 01-APR-07:00 | 897.89 | 13.42 | 0.00 | 327.50 | 571.44 | 16.87 | 0.00 | 292.00 |
May | 353.67 | 0.50 | 0.48 | 01-MAY-07:10 | 1099.28 | 15.66 | 27.17 | 370.83 | 661.96 | 19.00 | 27.50 | 336.17 |
June | 394.00 | 0.50 | 0.48 | 01-JUN-06:30 | 1269.58 | 17.18 | 58.00 | 374.67 | 710.92 | 20.31 | 59.33 | 349.00 |
July | 390.00 | 0.50 | 0.48 | 01-JUL-06:49 | 1240.82 | 15.29 | 23.50 | 376.83 | 705.40 | 18.62 | 24.50 | 343.83 |
August | 380.83 | 0.51 | 0.48 | 01-AUG-07:19 | 1089.45 | 13.85 | 0.00 | 353.67 | 640.72 | 17.27 | 0.00 | 322.00 |
September | 342.17 | 0.53 | 0.48 | 01-SEP-07:30 | 913.25 | 13.24 | 0.00 | 316.33 | 549.66 | 16.60 | 0.00 | 271.83 |
October | 330.00 | 0.52 | 0.48 | 01-OCT-07:00 | 788.70 | 13.17 | 0.00 | 297.67 | 505.18 | 16.68 | 0.00 | 252.67 |
November | 308.00 | 0.56 | 0.48 | 01-NOV-10:09 | 572.74 | 11.26 | 0.00 | 245.33 | 390.12 | 14.97 | 0.00 | 181.83 |
December | 282.83 | 0.56 | 0.48 | 01-DEC-09:09 | 557.04 | 10.90 | 0.00 | 244.17 | 379.56 | 14.62 | 0.00 | 162.83 |
Annual Sum or Average | 4027.67 | 0.53 | 891.65 | 13.50 | 108.67 | 3717.83 | 547.76 | 16.96 | 111.33 | 3137.50 | ||
Minimum of Months | 282.83 | 0.50 | 0.48 | 557.04 | 10.74 | 0.00 | 244.17 | 377.55 | 14.39 | 0.00 | 162.83 | |
Maximum of Months | 394.00 | 0.57 | 0.48 | 1269.58 | 17.18 | 58.00 | 376.83 | 710.92 | 20.31 | 59.33 | 349.00 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_4_DAYLCTRL
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 307.33 | 0.53 | 0.48 | 01-JAN-09:20 | 2324.51 | 22.15 | 109.33 | 277.33 | 1315.75 | 22.69 | 81.83 | 237.67 |
February | 295.50 | 0.52 | 0.48 | 01-FEB-11:50 | 2065.41 | 19.84 | 79.17 | 267.33 | 1132.00 | 21.64 | 60.17 | 237.67 |
March | 296.00 | 0.52 | 0.48 | 02-MAR-12:39 | 2245.58 | 20.16 | 81.00 | 313.33 | 1206.17 | 21.13 | 56.67 | 277.17 |
April | 347.33 | 0.52 | 0.48 | 01-APR-08:39 | 2509.06 | 18.38 | 82.00 | 327.67 | 1359.30 | 19.42 | 53.00 | 298.00 |
May | 353.67 | 0.51 | 0.48 | 01-MAY-07:00 | 2079.91 | 13.70 | 0.00 | 357.50 | 1142.38 | 17.13 | 0.00 | 321.33 |
June | 394.00 | 0.52 | 0.48 | 01-JUN-07:30 | 2203.82 | 13.60 | 0.00 | 359.17 | 979.15 | 16.95 | 0.00 | 324.50 |
July | 390.00 | 0.51 | 0.48 | 01-JUL-07:19 | 2037.14 | 14.16 | 3.67 | 366.83 | 952.17 | 17.25 | 0.00 | 328.17 |
August | 380.83 | 0.52 | 0.48 | 01-AUG-07:49 | 2103.29 | 16.84 | 59.00 | 350.83 | 1129.98 | 17.53 | 5.50 | 316.67 |
September | 342.17 | 0.52 | 0.48 | 01-SEP-07:00 | 1964.21 | 18.72 | 80.50 | 315.83 | 1037.50 | 19.80 | 51.67 | 283.50 |
October | 330.00 | 0.51 | 0.48 | 01-OCT-08:09 | 2513.81 | 21.90 | 108.83 | 310.17 | 1072.14 | 21.07 | 53.50 | 277.17 |
November | 308.00 | 0.53 | 0.48 | 01-NOV-09:00 | 2022.58 | 21.05 | 95.17 | 268.50 | 1113.64 | 21.76 | 66.67 | 236.50 |
December | 282.83 | 0.52 | 0.48 | 01-DEC-09:09 | 2169.30 | 22.84 | 103.00 | 271.67 | 1200.05 | 23.18 | 74.00 | 226.33 |
Annual Sum or Average | 4027.67 | 0.52 | 2184.50 | 18.31 | 801.67 | 3786.17 | 1129.87 | 19.74 | 503.00 | 3364.67 | ||
Minimum of Months | 282.83 | 0.51 | 0.48 | 1964.21 | 13.60 | 0.00 | 267.33 | 952.17 | 16.95 | 0.00 | 226.33 | |
Maximum of Months | 394.00 | 0.53 | 0.48 | 2513.81 | 22.84 | 109.33 | 366.83 | 1359.30 | 23.18 | 81.83 | 328.17 |
Report: CoilReportMonthly
For: VAV_BOT WITH REHEAT HEATING COIL
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.213789E+09 | 28124.54 | 05-JAN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 83762690.78 | 28039.64 | 17-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 85182035.77 | 28050.18 | 09-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 7314064.13 | 2063.83 | 03-APR-15:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 2480054.62 | 1174.80 | 28-OCT-07:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5171655.82 | 5866.42 | 15-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.118614E+09 | 28246.44 | 21-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.516314E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.213789E+09 | 28246.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_BOTTOM VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 80099991.54 | 8684.04 | 10-JAN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 23669092.55 | 3102.47 | 06-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 4176759.94 | 947.09 | 09-MAR-06:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 22416240.64 | 2262.05 | 21-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.130362E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 80099991.54 | 8684.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.117007E+09 | 7525.79 | 05-JAN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 38544338.68 | 7382.80 | 06-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 52330388.44 | 3354.11 | 09-MAR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 118014.25 | 196.69 | 16-NOV-06:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 71936084.43 | 7452.28 | 21-DEC-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.279935E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.117007E+09 | 7525.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 79018488.09 | 12088.54 | 10-JAN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 32019017.20 | 11996.39 | 06-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 31106938.55 | 2057.89 | 09-MAR-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 37574748.31 | 5611.10 | 21-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.179719E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 79018488.09 | 12088.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 32626616.90 | 2530.78 | 05-JAN-06:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 93876.07 | 83.34 | 06-FEB-06:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 32720492.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 32626616.90 | 2530.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV_MID WITH REHEAT HEATING COIL
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.227241E+10 | 245340.81 | 05-JAN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.160940E+10 | 244642.90 | 17-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.115552E+10 | 244733.88 | 09-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.203809E+09 | 62254.97 | 11-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 15995651.99 | 26268.29 | 28-OCT-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.264040E+09 | 95685.06 | 15-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.229216E+10 | 246564.55 | 21-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.781334E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.229216E+10 | 246564.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_MID VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.125023E+11 | 159546.91 | 23-JAN-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.593779E+10 | 159463.85 | 06-FEB-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.439683E+10 | 159456.98 | 13-MAR-04:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 36607532.12 | 7503.34 | 03-APR-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 46016240.04 | 8505.34 | 28-OCT-06:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.794872E+09 | 94381.46 | 16-NOV-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.762028E+10 | 159995.51 | 20-DEC-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.313347E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.125023E+11 | 159995.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.758447E+10 | 141059.03 | 10-JAN-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.339115E+10 | 141105.64 | 06-FEB-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.368119E+10 | 140980.67 | 13-MAR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 42829351.95 | 8118.92 | 11-APR-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 72090289.59 | 17205.73 | 28-OCT-05:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.519992E+09 | 47143.64 | 16-NOV-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.601356E+10 | 141128.56 | 21-DEC-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.213053E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.758447E+10 | 141128.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.359484E+10 | 179369.90 | 09-JAN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.164001E+10 | 179179.64 | 13-FEB-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.262622E+10 | 179419.00 | 13-MAR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 18185907.76 | 8605.38 | 16-NOV-06:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.241933E+10 | 179271.37 | 20-DEC-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.102986E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.359484E+10 | 179419.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.744562E+10 | 135040.80 | 10-JAN-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.333997E+10 | 134907.48 | 18-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.292329E+10 | 134881.63 | 11-MAR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 55949630.69 | 8058.69 | 28-OCT-06:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.422046E+09 | 27630.75 | 15-NOV-06:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.443291E+10 | 134891.64 | 26-DEC-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.186198E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.744562E+10 | 135040.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV_TOP WITH REHEAT HEATING COIL
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.162450E+09 | 21989.95 | 05-JAN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 66871118.52 | 21763.27 | 17-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 63768894.33 | 21736.93 | 09-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 5802936.59 | 6081.29 | 11-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 1594865.29 | 2554.56 | 28-OCT-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6561738.69 | 9745.39 | 15-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 93576770.92 | 22208.71 | 21-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.400626E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.162450E+09 | 22208.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_TOP VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.132869E+10 | 75205.45 | 23-JAN-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.112753E+10 | 75126.62 | 06-FEB-06:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.624350E+09 | 74923.22 | 13-MAR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 23489955.91 | 3771.29 | 27-NOV-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.777901E+09 | 75048.93 | 21-DEC-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.388196E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.132869E+10 | 75205.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.288213E+10 | 18047.08 | 23-JAN-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.164192E+10 | 18033.59 | 08-FEB-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.113310E+10 | 18068.24 | 13-MAR-05:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 60156728.57 | 9491.74 | 03-APR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 54640695.40 | 16552.29 | 28-OCT-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.411490E+09 | 18049.92 | 27-NOV-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.198654E+10 | 18041.48 | 30-DEC-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.816998E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.288213E+10 | 18068.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.152624E+10 | 16233.16 | 05-JAN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.867747E+09 | 16226.59 | 18-FEB-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.768001E+09 | 16227.01 | 11-MAR-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 38554449.12 | 2722.80 | 03-APR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 38345132.69 | 10182.47 | 28-OCT-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.231180E+09 | 16216.71 | 13-NOV-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.130314E+10 | 16221.55 | 05-DEC-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.477320E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.152624E+10 | 16233.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.110443E+10 | 21201.31 | 05-JAN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.691464E+09 | 21179.99 | 06-FEB-05:35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.807312E+09 | 21196.56 | 11-MAR-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 37594517.46 | 2899.71 | 03-APR-05:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 21355424.80 | 4444.12 | 28-OCT-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.115077E+09 | 21162.62 | 16-NOV-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.883250E+09 | 21180.50 | 04-DEC-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.366049E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.110443E+10 | 21201.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.164254E+10 | 16445.57 | 05-JAN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.876436E+09 | 16418.94 | 06-FEB-05:33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.713407E+09 | 16419.73 | 10-MAR-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 21173400.23 | 1908.75 | 11-APR-05:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 36858094.46 | 2839.70 | 28-OCT-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.247947E+09 | 16411.75 | 16-NOV-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.114629E+10 | 16426.50 | 20-DEC-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.468465E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.164254E+10 | 16445.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CAV_BAS HEATING COIL
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BASEMENT HEATING COIL
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BOT HEATING COIL
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER MID HEATING COIL
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER TOP HEATING COIL
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BOT_SUPPHEATCOIL
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER MID_SUPPHEATCOIL
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER TOP_SUPPHEATCOIL
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV_BOT WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.467295E+11 | 0.338612E+11 | 161479.62 | 19-JAN-06:02 | 131617.94 | 0.27 |
February | 0.00 | 0.00 | 0.661489E+11 | 0.462730E+11 | 176448.21 | 28-FEB-05:12 | 153433.64 | 0.42 |
March | 0.00 | 0.00 | 0.825852E+11 | 0.625065E+11 | 185866.15 | 28-MAR-04:12 | 141086.34 | 0.41 |
April | 0.00 | 0.00 | 0.132836E+12 | 0.101896E+12 | 183472.58 | 01-APR-04:12 | 139199.20 | 0.65 |
May | 0.00 | 0.00 | 0.173246E+12 | 0.127712E+12 | 210821.11 | 22-MAY-03:02 | 157594.43 | 0.68 |
June | 0.00 | 0.00 | 0.185700E+12 | 0.140613E+12 | 211507.10 | 08-JUN-04:11 | 162664.77 | 0.77 |
July | 0.00 | 0.00 | 0.200820E+12 | 0.149231E+12 | 189797.96 | 03-JUL-05:02 | 161663.63 | 0.81 |
August | 0.00 | 0.00 | 0.220719E+12 | 0.166009E+12 | 197392.39 | 16-AUG-05:02 | 159441.46 | 0.86 |
September | 0.00 | 0.00 | 0.175495E+12 | 0.120044E+12 | 235391.90 | 13-SEP-04:12 | 155750.17 | 0.68 |
October | 0.00 | 0.00 | 0.160196E+12 | 0.120488E+12 | 216371.89 | 21-OCT-04:12 | 162554.56 | 0.63 |
November | 0.00 | 0.00 | 0.100490E+12 | 0.777419E+11 | 210013.98 | 08-NOV-05:11 | 161443.97 | 0.51 |
December | 0.00 | 0.00 | 0.739762E+11 | 0.556987E+11 | 173772.90 | 11-DEC-05:12 | 154776.13 | 0.37 |
Annual Sum or Average | 0.00 | 0.00 | 0.161894E+13 | 0.120207E+13 | 0.59 | |||
Minimum of Months | 0.00 | 0.00 | 0.467295E+11 | 0.338612E+11 | 161479.62 | 131617.94 | 0.27 | |
Maximum of Months | 0.00 | 0.00 | 0.220719E+12 | 0.166009E+12 | 235391.90 | 162664.77 | 0.86 |
Report: CoilReportMonthly
For: VAV_MID WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.374288E+12 | 0.260326E+12 | 1364913.68 | 19-JAN-06:02 | 1017855.49 | 0.26 |
February | 0.00 | 0.00 | 0.534092E+12 | 0.356461E+12 | 1489725.75 | 03-FEB-06:03 | 1026924.75 | 0.40 |
March | 0.00 | 0.00 | 0.638157E+12 | 0.456894E+12 | 1850624.85 | 27-MAR-05:02 | 1413957.22 | 0.38 |
April | 0.00 | 0.00 | 0.998860E+12 | 0.711329E+12 | 1975020.46 | 29-APR-05:03 | 1481962.41 | 0.52 |
May | 0.00 | 0.00 | 0.157199E+13 | 0.111262E+13 | 2412233.21 | 22-MAY-03:02 | 1366271.57 | 0.63 |
June | 0.00 | 0.00 | 0.160344E+13 | 0.115124E+13 | 2073604.79 | 06-JUN-04:11 | 1490845.85 | 0.67 |
July | 0.00 | 0.00 | 0.167063E+13 | 0.114252E+13 | 2042018.77 | 27-JUL-03:02 | 1481995.24 | 0.66 |
August | 0.00 | 0.00 | 0.173400E+13 | 0.118541E+13 | 2371118.24 | 16-AUG-05:02 | 1498113.45 | 0.66 |
September | 0.00 | 0.00 | 0.157134E+13 | 0.101440E+13 | 2535500.55 | 05-SEP-04:11 | 1320982.51 | 0.64 |
October | 0.00 | 0.00 | 0.135109E+13 | 0.957629E+12 | 2126135.77 | 11-OCT-04:12 | 1494231.68 | 0.55 |
November | 0.00 | 0.00 | 0.783585E+12 | 0.579140E+12 | 1747744.60 | 02-NOV-05:03 | 1360080.34 | 0.46 |
December | 0.00 | 0.00 | 0.549538E+12 | 0.382302E+12 | 1631610.44 | 11-DEC-06:02 | 1235979.31 | 0.32 |
Annual Sum or Average | 0.00 | 0.00 | 0.133810E+14 | 0.931027E+13 | 0.51 | |||
Minimum of Months | 0.00 | 0.00 | 0.374288E+12 | 0.260326E+12 | 1364913.68 | 1017855.49 | 0.26 | |
Maximum of Months | 0.00 | 0.00 | 0.173400E+13 | 0.118541E+13 | 2535500.55 | 1498113.45 | 0.67 |
Report: CoilReportMonthly
For: VAV_TOP WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.381698E+11 | 0.258367E+11 | 150912.20 | 19-JAN-15:00 | 95037.95 | 0.26 |
February | 0.00 | 0.00 | 0.546978E+11 | 0.361059E+11 | 145721.95 | 24-FEB-16:00 | 96696.19 | 0.40 |
March | 0.00 | 0.00 | 0.662221E+11 | 0.469344E+11 | 174943.56 | 27-MAR-05:02 | 130043.74 | 0.37 |
April | 0.00 | 0.00 | 0.105315E+12 | 0.759149E+11 | 190405.88 | 28-APR-05:02 | 145680.61 | 0.51 |
May | 0.00 | 0.00 | 0.171405E+12 | 0.124180E+12 | 270875.56 | 22-MAY-03:02 | 151322.34 | 0.64 |
June | 0.00 | 0.00 | 0.177286E+12 | 0.130834E+12 | 228923.94 | 06-JUN-04:11 | 159068.73 | 0.67 |
July | 0.00 | 0.00 | 0.184171E+12 | 0.129055E+12 | 235121.27 | 27-JUL-03:02 | 166093.38 | 0.67 |
August | 0.00 | 0.00 | 0.189363E+12 | 0.132637E+12 | 262201.23 | 16-AUG-05:02 | 159406.97 | 0.67 |
September | 0.00 | 0.00 | 0.167509E+12 | 0.110253E+12 | 280468.40 | 05-SEP-04:11 | 140118.98 | 0.64 |
October | 0.00 | 0.00 | 0.142904E+12 | 0.102821E+12 | 225382.07 | 06-OCT-03:02 | 160628.71 | 0.55 |
November | 0.00 | 0.00 | 0.778834E+11 | 0.574615E+11 | 168063.79 | 02-NOV-05:03 | 127364.45 | 0.45 |
December | 0.00 | 0.00 | 0.544034E+11 | 0.374678E+11 | 176718.14 | 11-DEC-06:02 | 124159.51 | 0.31 |
Annual Sum or Average | 0.00 | 0.00 | 0.142933E+13 | 0.100950E+13 | 0.51 | |||
Minimum of Months | 0.00 | 0.00 | 0.381698E+11 | 0.258367E+11 | 145721.95 | 95037.95 | 0.26 | |
Maximum of Months | 0.00 | 0.00 | 0.189363E+12 | 0.132637E+12 | 280468.40 | 166093.38 | 0.67 |
Report: CoilReportMonthly
For: CAV_BAS COOLING COIL
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.229355E+11 | 0.183527E+11 | 142337.87 | 19-JAN-05:12 | 51826.57 | 0.17 |
February | 0.00 | 0.00 | 0.284262E+11 | 0.235339E+11 | 140150.66 | 03-FEB-05:12 | 52699.54 | 0.28 |
March | 0.00 | 0.00 | 0.391337E+11 | 0.335794E+11 | 168028.79 | 07-MAR-05:12 | 101378.61 | 0.26 |
April | 0.00 | 0.00 | 0.619439E+11 | 0.544226E+11 | 168339.93 | 26-APR-04:13 | 95899.04 | 0.44 |
May | 0.00 | 0.00 | 0.111483E+12 | 0.876833E+11 | 191233.99 | 29-MAY-09:21 | 99216.57 | 0.58 |
June | 0.00 | 0.00 | 0.116580E+12 | 0.892590E+11 | 195095.57 | 19-JUN-03:02 | 97674.03 | 0.59 |
July | 0.00 | 0.00 | 0.124090E+12 | 0.899967E+11 | 186766.06 | 03-JUL-03:13 | 98273.40 | 0.58 |
August | 0.00 | 0.00 | 0.137320E+12 | 0.102164E+12 | 185843.86 | 06-AUG-23:22 | 102958.02 | 0.64 |
September | 0.00 | 0.00 | 0.118261E+12 | 0.884613E+11 | 192778.19 | 10-SEP-15:08 | 99142.27 | 0.61 |
October | 0.00 | 0.00 | 0.101665E+12 | 0.798273E+11 | 192465.53 | 08-OCT-13:50 | 99344.57 | 0.53 |
November | 0.00 | 0.00 | 0.566141E+11 | 0.475519E+11 | 176169.51 | 11-NOV-14:00 | 104335.65 | 0.38 |
December | 0.00 | 0.00 | 0.373098E+11 | 0.308461E+11 | 168780.13 | 15-DEC-05:11 | 101826.16 | 0.25 |
Annual Sum or Average | 0.00 | 0.00 | 0.955762E+12 | 0.745678E+12 | 0.44 | |||
Minimum of Months | 0.00 | 0.00 | 0.229355E+11 | 0.183527E+11 | 140150.66 | 51826.57 | 0.17 | |
Maximum of Months | 0.00 | 0.00 | 0.137320E+12 | 0.102164E+12 | 195095.57 | 104335.65 | 0.64 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BASEMENT COOLING COIL
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.333017E+12 | 0.330262E+12 | 137709.70 | 31-JAN-16:40 | 127861.89 | 0.00 |
February | 0.00 | 0.00 | 0.524231E+12 | 0.519301E+12 | 229029.45 | 24-FEB-17:00 | 219373.62 | 0.00 |
March | 0.00 | 0.00 | 0.825493E+12 | 0.820562E+12 | 394706.20 | 31-MAR-24:00 | 394706.20 | 0.00 |
April | 0.00 | 0.00 | 0.103845E+13 | 0.103224E+13 | 423667.70 | 28-APR-18:00 | 405097.22 | 0.00 |
May | 0.00 | 0.00 | 0.351114E+12 | 0.338369E+12 | 213560.08 | 31-MAY-23:10 | 211214.04 | 0.00 |
June | 0.00 | 0.00 | 0.578272E+12 | 0.564382E+12 | 303567.87 | 30-JUN-24:00 | 303502.08 | 0.00 |
July | 0.00 | 0.00 | 0.844125E+12 | 0.829239E+12 | 395612.51 | 31-JUL-23:57 | 395612.51 | 0.00 |
August | 0.00 | 0.00 | 0.108298E+13 | 0.106952E+13 | 425484.91 | 07-AUG-14:00 | 404759.27 | 0.00 |
September | 0.00 | 0.00 | 0.344072E+12 | 0.330460E+12 | 213643.76 | 30-SEP-24:00 | 212348.25 | 0.00 |
October | 0.00 | 0.00 | 0.595694E+12 | 0.584785E+12 | 304810.91 | 31-OCT-24:00 | 304810.91 | 0.00 |
November | 0.00 | 0.00 | 0.806303E+12 | 0.800204E+12 | 326140.70 | 03-NOV-16:00 | 313485.75 | 0.00 |
December | 0.00 | 0.00 | 0.107270E+13 | 0.106892E+13 | 417636.03 | 13-DEC-18:00 | 405157.70 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.839646E+13 | 0.828825E+13 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.333017E+12 | 0.330262E+12 | 137709.70 | 127861.89 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.108298E+13 | 0.106952E+13 | 425484.91 | 405157.70 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BOT COOLING COIL
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.515835E+10 | 0.504859E+10 | 2974.67 | 19-JAN-17:00 | 2607.47 | 0.00 |
February | 0.00 | 0.00 | 0.964382E+10 | 0.944967E+10 | 4932.54 | 27-FEB-17:00 | 4568.83 | 0.00 |
March | 0.00 | 0.00 | 0.159130E+11 | 0.157072E+11 | 7754.00 | 31-MAR-24:00 | 7754.00 | 0.00 |
April | 0.00 | 0.00 | 0.206983E+11 | 0.204099E+11 | 8806.68 | 28-APR-17:10 | 8298.36 | 0.00 |
May | 0.00 | 0.00 | 0.672551E+10 | 0.621495E+10 | 4136.40 | 31-MAY-23:10 | 3995.40 | 0.00 |
June | 0.00 | 0.00 | 0.114836E+11 | 0.109016E+11 | 5921.47 | 30-JUN-23:23 | 5904.28 | 0.00 |
July | 0.00 | 0.00 | 0.169237E+11 | 0.162734E+11 | 7768.75 | 31-JUL-23:35 | 7768.75 | 0.00 |
August | 0.00 | 0.00 | 0.220562E+11 | 0.213999E+11 | 9055.78 | 14-AUG-16:00 | 8395.93 | 0.00 |
September | 0.00 | 0.00 | 0.653858E+10 | 0.599133E+10 | 4071.22 | 30-SEP-24:00 | 4039.51 | 0.00 |
October | 0.00 | 0.00 | 0.116343E+11 | 0.111808E+11 | 5920.13 | 31-OCT-24:00 | 5911.23 | 0.00 |
November | 0.00 | 0.00 | 0.157062E+11 | 0.154540E+11 | 6991.54 | 07-NOV-16:40 | 6455.42 | 0.00 |
December | 0.00 | 0.00 | 0.209424E+11 | 0.207657E+11 | 8973.78 | 14-DEC-17:00 | 8505.72 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.163424E+12 | 0.158797E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.515835E+10 | 0.504859E+10 | 2974.67 | 2607.47 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.220562E+11 | 0.213999E+11 | 9055.78 | 8505.72 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER MID COOLING COIL
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.369112E+11 | 0.358553E+11 | 27910.99 | 19-JAN-17:00 | 24257.01 | 0.00 |
February | 0.00 | 0.00 | 0.820651E+11 | 0.801570E+11 | 46450.26 | 27-FEB-17:00 | 42845.16 | 0.00 |
March | 0.00 | 0.00 | 0.143265E+12 | 0.141222E+12 | 72150.61 | 31-MAR-24:00 | 72150.61 | 0.00 |
April | 0.00 | 0.00 | 0.194402E+12 | 0.191518E+12 | 84105.77 | 28-APR-17:10 | 79040.74 | 0.00 |
May | 0.00 | 0.00 | 0.623773E+11 | 0.573315E+11 | 38844.89 | 31-MAY-23:10 | 37292.49 | 0.00 |
June | 0.00 | 0.00 | 0.108984E+12 | 0.103194E+12 | 57245.95 | 30-JUN-23:53 | 57087.92 | 0.00 |
July | 0.00 | 0.00 | 0.161340E+12 | 0.154854E+12 | 74476.14 | 31-JUL-24:00 | 74475.01 | 0.00 |
August | 0.00 | 0.00 | 0.209714E+12 | 0.203152E+12 | 86113.09 | 14-AUG-16:00 | 79517.47 | 0.00 |
September | 0.00 | 0.00 | 0.595997E+11 | 0.542072E+11 | 37681.43 | 30-SEP-24:00 | 37346.48 | 0.00 |
October | 0.00 | 0.00 | 0.108054E+12 | 0.103552E+12 | 54645.94 | 31-OCT-24:00 | 54521.48 | 0.00 |
November | 0.00 | 0.00 | 0.142352E+12 | 0.139851E+12 | 66494.84 | 07-NOV-16:50 | 61171.00 | 0.00 |
December | 0.00 | 0.00 | 0.188929E+12 | 0.187162E+12 | 85078.37 | 14-DEC-17:00 | 80402.87 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.149800E+13 | 0.145206E+13 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.369112E+11 | 0.358553E+11 | 27910.99 | 24257.01 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.209714E+12 | 0.203152E+12 | 86113.09 | 80402.87 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER TOP COOLING COIL
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.272029E+10 | 0.261647E+10 | 2856.11 | 19-JAN-17:00 | 2489.81 | 0.00 |
February | 0.00 | 0.00 | 0.744680E+10 | 0.725747E+10 | 4718.48 | 27-FEB-17:00 | 4356.76 | 0.00 |
March | 0.00 | 0.00 | 0.137986E+11 | 0.135950E+11 | 7111.30 | 31-MAR-24:00 | 7111.30 | 0.00 |
April | 0.00 | 0.00 | 0.192925E+11 | 0.190046E+11 | 8516.62 | 28-APR-17:10 | 8010.01 | 0.00 |
May | 0.00 | 0.00 | 0.635745E+10 | 0.585127E+10 | 3862.36 | 31-MAY-23:10 | 3707.04 | 0.00 |
June | 0.00 | 0.00 | 0.110395E+11 | 0.104599E+11 | 5758.24 | 30-JUN-23:53 | 5742.46 | 0.00 |
July | 0.00 | 0.00 | 0.162890E+11 | 0.156403E+11 | 7443.96 | 31-JUL-24:00 | 7443.62 | 0.00 |
August | 0.00 | 0.00 | 0.211069E+11 | 0.204506E+11 | 8747.40 | 14-AUG-15:50 | 8091.01 | 0.00 |
September | 0.00 | 0.00 | 0.603131E+10 | 0.549115E+10 | 3770.58 | 30-SEP-24:00 | 3737.44 | 0.00 |
October | 0.00 | 0.00 | 0.107311E+11 | 0.102811E+11 | 5398.30 | 31-OCT-24:00 | 5385.15 | 0.00 |
November | 0.00 | 0.00 | 0.137142E+11 | 0.134652E+11 | 6718.25 | 07-NOV-16:40 | 6183.60 | 0.00 |
December | 0.00 | 0.00 | 0.180937E+11 | 0.179175E+11 | 8579.12 | 14-DEC-17:00 | 8111.63 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.146621E+12 | 0.142031E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.272029E+10 | 0.261647E+10 | 2856.11 | 2489.81 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.211069E+11 | 0.204506E+11 | 8747.40 | 8111.63 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 15670.44 | 1076967.26 | 10-JAN-05:01 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 8752.35 | 1017961.89 | 13-FEB-06:03 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 7071.73 | 1074791.65 | 13-MAR-05:02 |
April | 0.00 | 0.00 | 01-APR-00:10 | 195.32 | 100483.60 | 18-APR-14:50 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 01-MAY-00:03 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 01-JUL-00:05 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 01-AUG-00:05 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 01-SEP-00:03 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 100.06 | 48977.67 | 28-OCT-06:10 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 1164.88 | 352037.12 | 16-NOV-06:02 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 10816.08 | 1181074.68 | 20-DEC-05:11 |
Annual Sum or Average | 0.00 | 3641.86 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.00 | 0.00 | 15670.44 | 1181074.68 |
Report: PlantLoopDemandReportMonthly
For: COOLSYS1_SUPPLY
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 194991.09 | 1904265.29 | 19-JAN-16:50 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 308338.86 | 2041352.44 | 23-FEB-15:20 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 335435.35 | 1902285.10 | 07-MAR-09:00 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 548944.73 | 2122941.39 | 28-APR-07:15 | 0.00 | 0.00 | 01-APR-00:10 |
May | 829984.20 | 2362987.39 | 18-MAY-04:14 | 0.00 | 0.00 | 01-MAY-00:03 |
June | 872079.34 | 2117332.83 | 06-JUN-05:06 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 869799.12 | 2183630.23 | 31-JUL-10:50 | 0.00 | 0.00 | 01-JUL-00:05 |
August | 913945.22 | 2879464.57 | 16-AUG-05:03 | 0.00 | 0.00 | 01-AUG-00:05 |
September | 849504.50 | 3239971.13 | 05-SEP-04:14 | 0.00 | 0.00 | 01-SEP-00:03 |
October | 705099.05 | 2408697.01 | 12-OCT-05:03 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 422154.22 | 2118028.06 | 02-NOV-07:25 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 289879.11 | 1942811.71 | 11-DEC-15:00 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 596512.60 | 0.00 | ||||
Minimum of Months | 194991.09 | 1902285.10 | 0.00 | 0.00 | ||
Maximum of Months | 913945.22 | 3239971.13 | 0.00 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: COOLSYS1_DEMAND
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 192554.05 | 2039251.96 | 19-JAN-10:20 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 304918.63 | 2226587.41 | 03-FEB-06:03 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 331937.22 | 3132746.70 | 27-MAR-05:04 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 544184.59 | 3516798.16 | 29-APR-05:03 | 0.00 | 0.00 | 01-APR-00:10 |
May | 828065.71 | 4362754.49 | 22-MAY-03:02 | 0.00 | 0.00 | 01-MAY-00:03 |
June | 867169.31 | 3868680.65 | 09-JUN-05:03 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 864604.94 | 3768410.36 | 25-JUL-05:03 | 0.00 | 0.00 | 01-JUL-00:05 |
August | 908278.46 | 3995443.00 | 26-AUG-05:03 | 0.00 | 0.00 | 01-AUG-00:05 |
September | 847451.31 | 5258531.41 | 05-SEP-04:11 | 0.00 | 0.00 | 01-SEP-00:03 |
October | 701823.36 | 4043422.49 | 16-OCT-04:12 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 418187.26 | 2761043.76 | 02-NOV-05:03 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 286647.49 | 2623645.75 | 11-DEC-06:02 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 592818.47 | 0.00 | ||||
Minimum of Months | 192554.05 | 2039251.96 | 0.00 | 0.00 | ||
Maximum of Months | 908278.46 | 5258531.41 | 0.00 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SINGLE WATER PLANT LOOP
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 244694.07 | 757808.25 | 02-JAN-15:00 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 453531.44 | 1051181.21 | 02-FEB-13:10 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 693565.65 | 1355782.43 | 30-MAR-13:00 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 1082205.04 | 1785833.50 | 28-APR-15:00 | 0.00 | 0.00 | 01-APR-00:10 |
May | 747346.89 | 1121222.28 | 18-MAY-16:00 | 0.00 | 0.00 | 01-MAY-00:03 |
June | 1012099.31 | 1446365.16 | 14-JUN-14:00 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 1258577.43 | 1766253.46 | 21-JUL-16:00 | 0.00 | 0.00 | 01-JUL-00:05 |
August | 1450252.59 | 1940154.46 | 30-AUG-16:10 | 0.00 | 0.00 | 01-AUG-00:05 |
September | 714376.78 | 1280277.87 | 09-SEP-17:00 | 0.00 | 0.00 | 01-SEP-00:03 |
October | 829313.69 | 1398137.11 | 05-OCT-15:00 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 765033.61 | 1403194.82 | 02-NOV-13:00 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 839259.71 | 1598071.29 | 13-DEC-15:00 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 843462.01 | 0.00 | ||||
Minimum of Months | 244694.07 | 757808.25 | 0.00 | 0.00 | ||
Maximum of Months | 1450252.59 | 1940154.46 | 0.00 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 12861.44 | 42408.96 | 24-JAN-13:00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 12836.67 | 42335.53 | 01-FEB-13:00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 13081.24 | 41396.33 | 01-MAR-12:30 |
April | 0.00 | 0.00 | 01-APR-00:10 | 11678.08 | 39140.91 | 03-APR-11:50 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 11278.95 | 36737.49 | 01-MAY-11:40 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 10890.08 | 34307.17 | 01-JUN-11:20 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 9856.92 | 32656.74 | 03-JUL-11:40 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 10754.41 | 33348.11 | 31-AUG-11:40 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 10625.05 | 35312.44 | 29-SEP-11:40 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 11282.63 | 38022.01 | 31-OCT-11:20 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 12146.67 | 40397.64 | 30-NOV-12:20 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 12316.14 | 41954.38 | 29-DEC-12:20 |
Annual Sum or Average | 0.00 | 11627.42 | ||||
Minimum of Months | 0.00 | 0.00 | 9856.92 | 32656.74 | ||
Maximum of Months | 0.00 | 0.00 | 13081.24 | 42408.96 |
Report: PlantLoopDemandReportMonthly
For: TOWERWATERSYS
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 279361.05 | 3997220.18 | 19-JAN-12:00 | 2009.84 | 177899.66 | 03-JAN-09:50 |
February | 434761.35 | 3868919.93 | 24-FEB-13:20 | 1496.07 | 171078.48 | 04-FEB-09:00 |
March | 518349.70 | 4562343.40 | 30-MAR-13:10 | 1872.90 | 204923.97 | 09-MAR-07:40 |
April | 919467.27 | 6110870.91 | 28-APR-16:00 | 487.18 | 113711.65 | 17-APR-06:00 |
May | 2053599.29 | 6272777.52 | 26-MAY-11:00 | 0.00 | 0.00 | 01-MAY-00:03 |
June | 2400503.29 | 6749978.90 | 28-JUN-14:00 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 2802263.26 | 6984286.73 | 03-JUL-16:00 | 0.00 | 0.00 | 01-JUL-00:05 |
August | 2744810.34 | 6923548.85 | 07-AUG-13:00 | 0.00 | 0.00 | 01-AUG-00:05 |
September | 2286893.00 | 6876295.10 | 18-SEP-14:00 | 0.00 | 0.00 | 01-SEP-00:03 |
October | 1723641.34 | 7211654.05 | 06-OCT-14:00 | 179.21 | 69482.81 | 27-OCT-19:30 |
November | 752317.07 | 5839330.35 | 01-NOV-14:00 | 929.79 | 158571.49 | 15-NOV-08:00 |
December | 488392.17 | 5204478.31 | 12-DEC-14:20 | 2078.39 | 206335.78 | 18-DEC-09:00 |
Annual Sum or Average | 1457182.65 | 752.74 | ||||
Minimum of Months | 279361.05 | 3868919.93 | 0.00 | 0.00 | ||
Maximum of Months | 2802263.26 | 7211654.05 | 2078.39 | 206335.78 |
Report: FanReportMonthly
For: CAV_BAS FAN
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.162293E+11 | 0.81 | 10394.87 | 01-JAN-00:13 | 1.37 |
February | 0.141360E+11 | 0.78 | 10394.87 | 01-FEB-05:12 | 1.38 |
March | 0.163594E+11 | 0.81 | 10394.87 | 01-MAR-05:12 | 1.38 |
April | 0.148439E+11 | 0.76 | 10394.87 | 01-APR-04:12 | 1.38 |
May | 0.164777E+11 | 0.81 | 10394.87 | 01-MAY-03:02 | 1.38 |
June | 0.162524E+11 | 0.83 | 10394.87 | 01-JUN-04:12 | 1.38 |
July | 0.163878E+11 | 0.81 | 10394.87 | 01-JUL-03:02 | 1.38 |
August | 0.180627E+11 | 0.89 | 10394.87 | 01-AUG-03:02 | 1.38 |
September | 0.169814E+11 | 0.87 | 10394.87 | 01-SEP-04:12 | 1.38 |
October | 0.174398E+11 | 0.86 | 10394.87 | 01-OCT-12:32 | 1.38 |
November | 0.167225E+11 | 0.86 | 10394.87 | 01-NOV-04:12 | 1.38 |
December | 0.167531E+11 | 0.83 | 10394.87 | 01-DEC-05:12 | 1.39 |
Annual Sum or Average | 0.196646E+12 | 0.83 | |||
Minimum of Months | 0.141360E+11 | 0.76 | 10394.87 | 1.37 | |
Maximum of Months | 0.180627E+11 | 0.89 | 10394.87 | 1.39 |
Report: FanReportMonthly
For: VAV_BOT WITH REHEAT FAN
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.416201E+10 | 0.32 | 15087.69 | 20-JAN-06:02 | 1.42 |
February | 0.425823E+10 | 0.34 | 17774.67 | 28-FEB-05:12 | 1.57 |
March | 0.528209E+10 | 0.38 | 15933.07 | 06-MAR-05:11 | 1.47 |
April | 0.619952E+10 | 0.44 | 18854.95 | 24-APR-05:02 | 1.64 |
May | 0.638286E+10 | 0.42 | 21145.91 | 03-MAY-04:11 | 1.76 |
June | 0.703128E+10 | 0.48 | 21145.91 | 01-JUN-04:12 | 1.76 |
July | 0.742022E+10 | 0.50 | 21145.91 | 01-JUL-05:03 | 1.76 |
August | 0.874932E+10 | 0.56 | 21145.91 | 07-AUG-05:02 | 1.76 |
September | 0.606918E+10 | 0.42 | 21145.91 | 02-SEP-05:03 | 1.76 |
October | 0.687080E+10 | 0.44 | 21145.91 | 02-OCT-04:12 | 1.76 |
November | 0.578473E+10 | 0.39 | 20676.94 | 08-NOV-05:11 | 1.73 |
December | 0.537610E+10 | 0.37 | 18657.49 | 11-DEC-05:12 | 1.62 |
Annual Sum or Average | 0.735863E+11 | 0.42 | |||
Minimum of Months | 0.416201E+10 | 0.32 | 15087.69 | 1.42 | |
Maximum of Months | 0.874932E+10 | 0.56 | 21145.91 | 1.76 |
Report: FanReportMonthly
For: VAV_MID WITH REHEAT FAN
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.319138E+11 | 0.30 | 89081.60 | 03-JAN-06:02 | 1.08 |
February | 0.308545E+11 | 0.30 | 150568.67 | 27-FEB-06:02 | 1.49 |
March | 0.362469E+11 | 0.32 | 196427.81 | 27-MAR-05:02 | 1.76 |
April | 0.402611E+11 | 0.33 | 196427.81 | 28-APR-05:02 | 1.76 |
May | 0.555179E+11 | 0.40 | 196427.81 | 03-MAY-04:11 | 1.76 |
June | 0.569916E+11 | 0.42 | 196427.81 | 02-JUN-05:03 | 1.76 |
July | 0.555300E+11 | 0.40 | 196427.81 | 01-JUL-05:03 | 1.76 |
August | 0.596953E+11 | 0.42 | 196427.81 | 01-AUG-05:02 | 1.76 |
September | 0.502343E+11 | 0.39 | 196427.81 | 05-SEP-04:11 | 1.76 |
October | 0.529935E+11 | 0.38 | 196427.81 | 05-OCT-05:02 | 1.76 |
November | 0.390281E+11 | 0.33 | 168775.82 | 03-NOV-04:12 | 1.60 |
December | 0.343836E+11 | 0.30 | 142655.38 | 11-DEC-06:02 | 1.44 |
Annual Sum or Average | 0.543651E+12 | 0.36 | |||
Minimum of Months | 0.308545E+11 | 0.30 | 89081.60 | 1.08 | |
Maximum of Months | 0.596953E+11 | 0.42 | 196427.81 | 1.76 |
Report: FanReportMonthly
For: VAV_TOP WITH REHEAT FAN
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.307333E+10 | 0.29 | 9077.36 | 02-JAN-06:03 | 1.03 |
February | 0.307884E+10 | 0.30 | 8835.93 | 28-FEB-06:03 | 1.01 |
March | 0.353563E+10 | 0.31 | 15301.35 | 27-MAR-05:02 | 1.42 |
April | 0.404818E+10 | 0.32 | 18275.91 | 28-APR-05:02 | 1.59 |
May | 0.601855E+10 | 0.40 | 21403.05 | 03-MAY-04:11 | 1.76 |
June | 0.631989E+10 | 0.42 | 21403.05 | 06-JUN-04:11 | 1.76 |
July | 0.610612E+10 | 0.41 | 21403.05 | 10-JUL-05:03 | 1.76 |
August | 0.648754E+10 | 0.42 | 21403.05 | 01-AUG-05:02 | 1.76 |
September | 0.522375E+10 | 0.38 | 21403.05 | 05-SEP-04:11 | 1.75 |
October | 0.538821E+10 | 0.37 | 21403.05 | 05-OCT-05:02 | 1.76 |
November | 0.360992E+10 | 0.31 | 13058.42 | 02-NOV-05:03 | 1.29 |
December | 0.324573E+10 | 0.29 | 13675.10 | 11-DEC-06:02 | 1.32 |
Annual Sum or Average | 0.561357E+11 | 0.35 | |||
Minimum of Months | 0.307333E+10 | 0.29 | 8835.93 | 1.01 | |
Maximum of Months | 0.648754E+10 | 0.42 | 21403.05 | 1.76 |
Report: FanReportMonthly
For: AIRLOOP DATACENTER BASEMENT SUPPLY FAN
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.952024E+11 | 1.35 | 35544.49 | 01-JAN-00:05 | 1.35 |
February | 0.859892E+11 | 1.35 | 35544.49 | 01-FEB-00:10 | 1.35 |
March | 0.952024E+11 | 1.35 | 35544.49 | 01-MAR-00:10 | 1.35 |
April | 0.921313E+11 | 1.35 | 35544.49 | 01-APR-00:10 | 1.35 |
May | 0.952024E+11 | 1.35 | 35544.49 | 01-MAY-00:03 | 1.35 |
June | 0.921313E+11 | 1.35 | 35544.49 | 01-JUN-00:10 | 1.35 |
July | 0.952024E+11 | 1.35 | 35544.49 | 01-JUL-00:10 | 1.35 |
August | 0.952024E+11 | 1.35 | 35544.49 | 01-AUG-00:05 | 1.35 |
September | 0.921313E+11 | 1.35 | 35544.49 | 01-SEP-00:03 | 1.35 |
October | 0.952024E+11 | 1.35 | 35544.49 | 01-OCT-00:10 | 1.35 |
November | 0.921313E+11 | 1.35 | 35544.49 | 01-NOV-00:10 | 1.35 |
December | 0.952024E+11 | 1.35 | 35544.49 | 01-DEC-00:10 | 1.35 |
Annual Sum or Average | 0.112093E+13 | 1.35 | |||
Minimum of Months | 0.859892E+11 | 1.35 | 35544.49 | 1.35 | |
Maximum of Months | 0.952024E+11 | 1.35 | 35544.49 | 1.35 |
Report: FanReportMonthly
For: AIRLOOP DATACENTER BOT SUPPLY FAN
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.144065E+10 | 0.91 | 537.88 | 01-JAN-00:05 | 0.91 |
February | 0.130124E+10 | 0.91 | 537.88 | 01-FEB-00:10 | 0.91 |
March | 0.144065E+10 | 0.91 | 537.88 | 01-MAR-00:10 | 0.91 |
April | 0.139418E+10 | 0.91 | 537.88 | 01-APR-00:10 | 0.91 |
May | 0.144065E+10 | 0.91 | 537.88 | 01-MAY-00:03 | 0.91 |
June | 0.139418E+10 | 0.91 | 537.88 | 01-JUN-00:10 | 0.91 |
July | 0.144065E+10 | 0.91 | 537.88 | 01-JUL-00:05 | 0.91 |
August | 0.144065E+10 | 0.91 | 537.88 | 01-AUG-00:05 | 0.91 |
September | 0.139418E+10 | 0.91 | 537.88 | 01-SEP-00:03 | 0.91 |
October | 0.144065E+10 | 0.91 | 537.88 | 01-OCT-00:10 | 0.91 |
November | 0.139418E+10 | 0.91 | 537.88 | 01-NOV-00:10 | 0.91 |
December | 0.144065E+10 | 0.91 | 537.88 | 01-DEC-00:10 | 0.91 |
Annual Sum or Average | 0.169625E+11 | 0.91 | |||
Minimum of Months | 0.130124E+10 | 0.91 | 537.88 | 0.91 | |
Maximum of Months | 0.144065E+10 | 0.91 | 537.88 | 0.91 |
Report: FanReportMonthly
For: AIRLOOP DATACENTER MID SUPPLY FAN
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.137230E+11 | 0.91 | 5123.59 | 01-JAN-00:05 | 0.91 |
February | 0.123950E+11 | 0.91 | 5123.59 | 01-FEB-00:10 | 0.91 |
March | 0.137230E+11 | 0.91 | 5123.59 | 01-MAR-00:10 | 0.91 |
April | 0.132803E+11 | 0.91 | 5123.59 | 01-APR-00:10 | 0.91 |
May | 0.137230E+11 | 0.91 | 5123.59 | 01-MAY-00:03 | 0.91 |
June | 0.132803E+11 | 0.91 | 5123.59 | 01-JUN-00:10 | 0.91 |
July | 0.137230E+11 | 0.91 | 5123.59 | 01-JUL-00:05 | 0.91 |
August | 0.137230E+11 | 0.91 | 5123.59 | 01-AUG-00:05 | 0.91 |
September | 0.132803E+11 | 0.91 | 5123.59 | 01-SEP-00:03 | 0.91 |
October | 0.137230E+11 | 0.91 | 5123.59 | 01-OCT-00:10 | 0.91 |
November | 0.132803E+11 | 0.91 | 5123.59 | 01-NOV-00:10 | 0.91 |
December | 0.137230E+11 | 0.91 | 5123.59 | 01-DEC-00:10 | 0.91 |
Annual Sum or Average | 0.161577E+12 | 0.91 | |||
Minimum of Months | 0.123950E+11 | 0.91 | 5123.59 | 0.91 | |
Maximum of Months | 0.137230E+11 | 0.91 | 5123.59 | 0.91 |
Report: FanReportMonthly
For: AIRLOOP DATACENTER TOP SUPPLY FAN
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.139820E+10 | 0.91 | 522.03 | 01-JAN-00:05 | 0.91 |
February | 0.126289E+10 | 0.91 | 522.03 | 01-FEB-00:20 | 0.91 |
March | 0.139820E+10 | 0.91 | 522.03 | 01-MAR-00:10 | 0.91 |
April | 0.135310E+10 | 0.91 | 522.03 | 01-APR-00:10 | 0.91 |
May | 0.139820E+10 | 0.91 | 522.03 | 01-MAY-00:03 | 0.91 |
June | 0.135310E+10 | 0.91 | 522.03 | 01-JUN-00:10 | 0.91 |
July | 0.139820E+10 | 0.91 | 522.03 | 01-JUL-00:05 | 0.91 |
August | 0.139820E+10 | 0.91 | 522.03 | 01-AUG-00:05 | 0.91 |
September | 0.135310E+10 | 0.91 | 522.03 | 01-SEP-00:03 | 0.91 |
October | 0.139820E+10 | 0.91 | 522.03 | 01-OCT-00:10 | 0.91 |
November | 0.135310E+10 | 0.91 | 522.03 | 01-NOV-00:10 | 0.91 |
December | 0.139820E+10 | 0.91 | 522.03 | 01-DEC-00:10 | 0.91 |
Annual Sum or Average | 0.164627E+11 | 0.91 | |||
Minimum of Months | 0.126289E+10 | 0.91 | 522.03 | 0.91 | |
Maximum of Months | 0.139820E+10 | 0.91 | 522.03 | 0.91 |
Report: PumpReportMonthly
For: HEATSYS1 PUMP
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.176414E+09 | 0.158772E+09 | 3042.92 | 10-JAN-06:03 | 2738.63 | 2738.63 | 41.84 | 5.76 |
February | 89450102.62 | 80505092.36 | 3036.69 | 06-FEB-06:01 | 2733.02 | 2733.02 | 44.43 | 5.73 |
March | 77923632.96 | 70131269.66 | 3008.38 | 13-MAR-05:02 | 2707.54 | 2707.54 | 36.12 | 5.60 |
April | 2670609.99 | 2403548.99 | 623.08 | 18-APR-14:50 | 560.77 | 560.77 | 46.45 | 0.68 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 45.04 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 45.04 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 45.04 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 45.04 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 45.04 | 0.00 |
October | 1268888.10 | 1141999.29 | 240.84 | 28-OCT-06:10 | 216.76 | 216.76 | 35.33 | 0.25 |
November | 11821619.85 | 10639457.87 | 1252.69 | 16-NOV-06:02 | 1127.42 | 1127.42 | 25.53 | 1.49 |
December | 0.120267E+09 | 0.108240E+09 | 3026.15 | 21-DEC-06:01 | 2723.54 | 2723.54 | 41.34 | 5.68 |
Annual Sum or Average | 0.479815E+09 | 0.431834E+09 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.53 | 0.00 | |
Maximum of Months | 0.176414E+09 | 0.158772E+09 | 3042.92 | 2738.63 | 2738.63 | 46.45 | 5.76 |
Report: PumpReportMonthly
For: COOLSYS1 PUMP SECONDARY
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.467128E+09 | 0.420415E+09 | 4675.41 | 19-JAN-10:20 | 4207.87 | 4207.87 | 7.55 | 71.73 |
February | 0.762679E+09 | 0.686411E+09 | 5438.04 | 03-FEB-06:03 | 4894.24 | 4894.24 | 7.07 | 76.46 |
March | 0.900782E+09 | 0.810704E+09 | 18595.78 | 27-MAR-05:04 | 16736.20 | 16736.20 | 9.14 | 126.19 |
April | 0.155949E+10 | 0.140354E+10 | 17957.83 | 29-APR-05:03 | 16162.05 | 16162.05 | 8.59 | 124.46 |
May | 0.313164E+10 | 0.281848E+10 | 22242.82 | 03-MAY-04:13 | 20018.54 | 20018.54 | 9.22 | 135.42 |
June | 0.316904E+10 | 0.285213E+10 | 22242.82 | 06-JUN-04:13 | 20018.54 | 20018.54 | 9.55 | 135.42 |
July | 0.323272E+10 | 0.290945E+10 | 21081.11 | 01-JUL-05:03 | 18973.00 | 18973.00 | 8.79 | 132.58 |
August | 0.355450E+10 | 0.319905E+10 | 21986.74 | 08-AUG-05:02 | 19788.07 | 19788.07 | 8.67 | 134.79 |
September | 0.309875E+10 | 0.278887E+10 | 22242.82 | 05-SEP-04:11 | 20018.54 | 20018.54 | 8.88 | 135.42 |
October | 0.263820E+10 | 0.237438E+10 | 22242.82 | 10-OCT-04:13 | 20018.54 | 20018.54 | 9.73 | 135.42 |
November | 0.119386E+10 | 0.107448E+10 | 9366.95 | 02-NOV-05:03 | 8430.25 | 8430.25 | 7.78 | 95.81 |
December | 0.808724E+09 | 0.727851E+09 | 7687.72 | 11-DEC-06:02 | 6918.95 | 6918.95 | 7.44 | 88.34 |
Annual Sum or Average | 0.245175E+11 | 0.220658E+11 | ||||||
Minimum of Months | 0.467128E+09 | 0.420415E+09 | 4675.41 | 4207.87 | 4207.87 | 7.07 | 71.73 | |
Maximum of Months | 0.355450E+10 | 0.319905E+10 | 22242.82 | 20018.54 | 20018.54 | 9.73 | 135.42 |
Report: PumpReportMonthly
For: COOLSYS1 CHILLER1 PUMP
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.780777E+10 | 0.702700E+10 | 7654.57 | 01-JAN-06:10 | 6889.11 | 6889.11 | 6.78 | 67.71 |
February | 0.908410E+10 | 0.817569E+10 | 7654.57 | 01-FEB-05:12 | 6889.11 | 6889.11 | 9.07 | 67.71 |
March | 0.109575E+11 | 0.986179E+10 | 7654.57 | 01-MAR-05:12 | 6889.11 | 6889.11 | 9.18 | 67.71 |
April | 0.142143E+11 | 0.127928E+11 | 7654.57 | 01-APR-04:12 | 6889.11 | 6889.11 | 10.74 | 67.71 |
May | 0.144736E+11 | 0.130263E+11 | 7654.57 | 01-MAY-00:42 | 6889.11 | 6889.11 | 6.90 | 67.71 |
June | 0.160352E+11 | 0.144317E+11 | 7654.57 | 01-JUN-04:12 | 6889.11 | 6889.11 | 11.77 | 67.71 |
July | 0.176598E+11 | 0.158939E+11 | 7654.57 | 01-JUL-00:32 | 6889.11 | 6889.11 | 6.91 | 67.71 |
August | 0.185168E+11 | 0.166651E+11 | 7654.57 | 01-AUG-00:32 | 6889.11 | 6889.11 | 6.92 | 67.71 |
September | 0.145536E+11 | 0.130982E+11 | 7654.57 | 01-SEP-00:03 | 6889.11 | 6889.11 | 6.90 | 67.71 |
October | 0.147313E+11 | 0.132581E+11 | 7654.57 | 01-OCT-07:30 | 6889.11 | 6889.11 | 7.95 | 67.71 |
November | 0.121166E+11 | 0.109049E+11 | 7654.57 | 01-NOV-03:02 | 6889.11 | 6889.11 | 8.74 | 67.71 |
December | 0.978483E+10 | 0.880635E+10 | 7654.57 | 01-DEC-05:12 | 6889.11 | 6889.11 | 7.09 | 67.71 |
Annual Sum or Average | 0.159935E+12 | 0.143942E+12 | ||||||
Minimum of Months | 0.780777E+10 | 0.702700E+10 | 7654.57 | 6889.11 | 6889.11 | 6.78 | 67.71 | |
Maximum of Months | 0.185168E+11 | 0.166651E+11 | 7654.57 | 6889.11 | 6889.11 | 11.77 | 67.71 |
Report: PumpReportMonthly
For: COOLSYS1 CHILLER2 PUMP
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.192895E+09 | 0.173606E+09 | 7654.57 | 18-JAN-14:50 | 6889.11 | 6889.11 | 12.74 | 33.86 |
February | 0.408754E+09 | 0.367878E+09 | 7654.57 | 02-FEB-16:50 | 6889.11 | 6889.11 | 12.69 | 33.86 |
March | 0.624613E+09 | 0.562151E+09 | 7654.57 | 06-MAR-13:40 | 6889.11 | 6889.11 | 12.63 | 33.86 |
April | 0.102648E+10 | 0.923830E+09 | 7654.57 | 06-APR-12:30 | 6889.11 | 6889.11 | 12.39 | 33.86 |
May | 0.444035E+10 | 0.399631E+10 | 7654.57 | 01-MAY-08:00 | 6889.11 | 6889.11 | 12.43 | 33.86 |
June | 0.475303E+10 | 0.427772E+10 | 7654.57 | 01-JUN-08:70 | 6889.11 | 6889.11 | 12.47 | 33.86 |
July | 0.500379E+10 | 0.450341E+10 | 7654.57 | 03-JUL-07:00 | 6889.11 | 6889.11 | 12.29 | 33.86 |
August | 0.573358E+10 | 0.516022E+10 | 7654.57 | 01-AUG-06:20 | 6889.11 | 6889.11 | 12.25 | 33.86 |
September | 0.446408E+10 | 0.401767E+10 | 7654.57 | 01-SEP-06:20 | 6889.11 | 6889.11 | 12.43 | 33.86 |
October | 0.362252E+10 | 0.326027E+10 | 7654.57 | 02-OCT-12:50 | 6889.11 | 6889.11 | 12.61 | 33.86 |
November | 0.126760E+10 | 0.114084E+10 | 7654.57 | 01-NOV-07:15 | 6889.11 | 6889.11 | 9.81 | 67.71 |
December | 0.725653E+09 | 0.653088E+09 | 7654.57 | 11-DEC-09:50 | 6889.11 | 6889.11 | 12.39 | 33.86 |
Annual Sum or Average | 0.322633E+11 | 0.290370E+11 | ||||||
Minimum of Months | 0.192895E+09 | 0.173606E+09 | 7654.57 | 6889.11 | 6889.11 | 9.81 | 33.86 | |
Maximum of Months | 0.573358E+10 | 0.516022E+10 | 7654.57 | 6889.11 | 6889.11 | 12.74 | 67.71 |
Report: PumpReportMonthly
For: PLANT CIRC PUMP
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.918681E+10 | 0.826813E+10 | 3429.96 | 01-JAN-00:05 | 3086.96 | 3086.96 | 22.57 | 14.32 |
February | 0.829776E+10 | 0.746799E+10 | 3429.96 | 01-FEB-00:10 | 3086.96 | 3086.96 | 27.11 | 14.32 |
March | 0.918681E+10 | 0.826813E+10 | 3429.96 | 01-MAR-00:10 | 3086.96 | 3086.96 | 30.56 | 14.32 |
April | 0.889046E+10 | 0.800141E+10 | 3429.96 | 01-APR-00:10 | 3086.96 | 3086.96 | 38.74 | 14.32 |
May | 0.918681E+10 | 0.826813E+10 | 3429.96 | 01-MAY-00:03 | 3086.96 | 3086.96 | 28.57 | 14.32 |
June | 0.889046E+10 | 0.800141E+10 | 3429.96 | 01-JUN-00:10 | 3086.96 | 3086.96 | 32.87 | 14.32 |
July | 0.918681E+10 | 0.826813E+10 | 3429.96 | 01-JUL-00:05 | 3086.96 | 3086.96 | 39.40 | 14.32 |
August | 0.918681E+10 | 0.826813E+10 | 3429.96 | 01-AUG-00:05 | 3086.96 | 3086.96 | 43.80 | 14.32 |
September | 0.889046E+10 | 0.800141E+10 | 3429.96 | 01-SEP-00:03 | 3086.96 | 3086.96 | 31.50 | 14.32 |
October | 0.918681E+10 | 0.826813E+10 | 3429.96 | 01-OCT-00:10 | 3086.96 | 3086.96 | 32.06 | 14.32 |
November | 0.889046E+10 | 0.800141E+10 | 3429.96 | 01-NOV-00:10 | 3086.96 | 3086.96 | 35.61 | 14.32 |
December | 0.918681E+10 | 0.826813E+10 | 3429.96 | 01-DEC-00:10 | 3086.96 | 3086.96 | 30.81 | 14.32 |
Annual Sum or Average | 0.108167E+12 | 0.973505E+11 | ||||||
Minimum of Months | 0.829776E+10 | 0.746799E+10 | 3429.96 | 3086.96 | 3086.96 | 22.57 | 14.32 | |
Maximum of Months | 0.918681E+10 | 0.826813E+10 | 3429.96 | 3086.96 | 3086.96 | 43.80 | 14.32 |
Report: PumpReportMonthly
For: SWHSYS1 PUMP
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.112905E+09 | 33871561.48 | 56.21 | 01-JAN-06:05 | 16.86 | 16.86 | 55.87 | 0.44 |
February | 0.101979E+09 | 30593668.43 | 56.21 | 01-FEB-06:02 | 16.86 | 16.86 | 55.96 | 0.44 |
March | 0.112905E+09 | 33871561.48 | 56.21 | 01-MAR-06:03 | 16.86 | 16.86 | 56.87 | 0.44 |
April | 0.109263E+09 | 32778930.46 | 56.21 | 01-APR-05:03 | 16.86 | 16.86 | 56.63 | 0.44 |
May | 0.112905E+09 | 33871561.48 | 56.21 | 01-MAY-05:03 | 16.86 | 16.86 | 57.08 | 0.44 |
June | 0.109263E+09 | 32778930.46 | 56.21 | 01-JUN-05:03 | 16.86 | 16.86 | 57.68 | 0.44 |
July | 0.112905E+09 | 33871561.48 | 56.21 | 01-JUL-05:03 | 16.86 | 16.86 | 56.60 | 0.44 |
August | 0.112905E+09 | 33871561.48 | 56.21 | 01-AUG-05:02 | 16.86 | 16.86 | 56.77 | 0.44 |
September | 0.109263E+09 | 32778930.46 | 56.21 | 01-SEP-05:03 | 16.86 | 16.86 | 57.14 | 0.44 |
October | 0.112905E+09 | 33871561.48 | 56.21 | 01-OCT-05:10 | 16.86 | 16.86 | 56.22 | 0.44 |
November | 0.109263E+09 | 32778930.46 | 56.21 | 01-NOV-05:03 | 16.86 | 16.86 | 56.13 | 0.44 |
December | 0.112905E+09 | 33871561.48 | 56.21 | 01-DEC-06:02 | 16.86 | 16.86 | 56.09 | 0.44 |
Annual Sum or Average | 0.132937E+10 | 0.398810E+09 | ||||||
Minimum of Months | 0.101979E+09 | 30593668.43 | 56.21 | 16.86 | 16.86 | 55.87 | 0.44 | |
Maximum of Months | 0.112905E+09 | 33871561.48 | 56.21 | 16.86 | 16.86 | 57.68 | 0.44 |
Report: PumpReportMonthly
For: TOWERWATERSYS PUMP
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.205501E+11 | 0.184951E+11 | 39508.16 | 19-JAN-12:00 | 35557.34 | 35557.34 | 27.10 | 159.38 |
February | 0.243733E+11 | 0.219360E+11 | 39501.77 | 24-FEB-13:20 | 35551.60 | 35551.60 | 26.91 | 159.38 |
March | 0.297318E+11 | 0.267586E+11 | 39536.30 | 30-MAR-13:10 | 35582.67 | 35582.67 | 27.95 | 159.38 |
April | 0.390205E+11 | 0.351185E+11 | 39564.82 | 28-APR-15:30 | 35608.34 | 35608.34 | 29.02 | 159.38 |
May | 0.474936E+11 | 0.427442E+11 | 39564.82 | 01-MAY-08:00 | 35608.34 | 35608.34 | 29.08 | 159.38 |
June | 0.527188E+11 | 0.474469E+11 | 39564.82 | 01-JUN-11:30 | 35608.34 | 35608.34 | 28.98 | 159.38 |
July | 0.579554E+11 | 0.521599E+11 | 39564.82 | 03-JUL-08:00 | 35608.34 | 35608.34 | 29.78 | 159.38 |
August | 0.616333E+11 | 0.554699E+11 | 39564.82 | 01-AUG-08:00 | 35608.34 | 35608.34 | 29.18 | 159.38 |
September | 0.482034E+11 | 0.433831E+11 | 39564.82 | 01-SEP-07:30 | 35608.34 | 35608.34 | 29.29 | 159.38 |
October | 0.466830E+11 | 0.420147E+11 | 39564.82 | 04-OCT-16:00 | 35608.34 | 35608.34 | 28.84 | 159.38 |
November | 0.340725E+11 | 0.306653E+11 | 39564.82 | 01-NOV-10:30 | 35608.34 | 35608.34 | 28.87 | 159.38 |
December | 0.268219E+11 | 0.241397E+11 | 39564.82 | 12-DEC-14:00 | 35608.34 | 35608.34 | 28.90 | 159.38 |
Annual Sum or Average | 0.489258E+12 | 0.440332E+12 | ||||||
Minimum of Months | 0.205501E+11 | 0.184951E+11 | 39501.77 | 35551.60 | 35551.60 | 26.91 | 159.38 | |
Maximum of Months | 0.616333E+11 | 0.554699E+11 | 39564.82 | 35608.34 | 35608.34 | 29.78 | 159.38 |
Report: CondLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 82.00 | 82.00 | 15670.44 | 1076967.26 | 10-JAN-05:01 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 19.44 | 19.44 | 8752.35 | 1017961.89 | 13-FEB-06:03 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 17.48 | 17.48 | 7071.73 | 1074791.65 | 13-MAR-05:02 |
April | 0.00 | 0.00 | 01-APR-00:10 | 29.12 | 29.12 | 195.32 | 100483.60 | 18-APR-14:50 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 45.04 | 45.04 | 0.00 | 0.00 | 01-MAY-00:03 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 45.04 | 45.04 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 45.04 | 45.04 | 0.00 | 0.00 | 01-JUL-00:05 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 45.04 | 45.04 | 0.00 | 0.00 | 01-AUG-00:05 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 45.04 | 45.04 | 0.00 | 0.00 | 01-SEP-00:03 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 45.04 | 45.04 | 100.06 | 48977.67 | 28-OCT-06:10 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 24.30 | 24.30 | 1164.88 | 352037.12 | 16-NOV-06:02 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 20.25 | 20.25 | 10816.08 | 1181074.68 | 20-DEC-05:11 |
Annual Sum or Average | 0.00 | 3641.86 | ||||||
Minimum of Months | 0.00 | 0.00 | 17.48 | 17.48 | 0.00 | 0.00 | ||
Maximum of Months | 0.00 | 0.00 | 82.00 | 82.00 | 15670.44 | 1181074.68 |
Report: CondLoopDemandReportMonthly
For: COOLSYS1_SUPPLY
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 194991.09 | 1904265.29 | 19-JAN-16:50 | 10.06 | 6.70 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 308338.86 | 2041352.44 | 23-FEB-15:20 | 10.30 | 8.12 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 335435.35 | 1902285.10 | 07-MAR-09:00 | 13.41 | 6.70 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 548944.73 | 2122941.39 | 28-APR-07:15 | 10.44 | 6.70 | 0.00 | 0.00 | 01-APR-00:10 |
May | 829984.20 | 2362987.39 | 18-MAY-04:14 | 10.86 | 6.70 | 0.00 | 0.00 | 01-MAY-00:03 |
June | 872079.34 | 2117332.83 | 06-JUN-05:06 | 10.43 | 6.70 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 869799.12 | 2183630.23 | 31-JUL-10:50 | 10.55 | 6.70 | 0.00 | 0.00 | 01-JUL-00:05 |
August | 913945.22 | 2879464.57 | 16-AUG-05:03 | 11.78 | 6.70 | 0.00 | 0.00 | 01-AUG-00:05 |
September | 849504.50 | 3239971.13 | 05-SEP-04:14 | 12.41 | 6.71 | 0.00 | 0.00 | 01-SEP-00:03 |
October | 705099.05 | 2408697.01 | 12-OCT-05:03 | 10.95 | 6.70 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 422154.22 | 2118028.06 | 02-NOV-07:25 | 10.43 | 6.70 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 289879.11 | 1942811.71 | 11-DEC-15:00 | 10.12 | 6.70 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 596512.60 | 0.00 | ||||||
Minimum of Months | 194991.09 | 1902285.10 | 10.06 | 6.70 | 0.00 | 0.00 | ||
Maximum of Months | 913945.22 | 3239971.13 | 13.41 | 8.12 | 0.00 | 0.00 |
Report: CondLoopDemandReportMonthly
For: COOLSYS1_DEMAND
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 192554.05 | 2039251.96 | 19-JAN-10:20 | 13.49 | 7.42 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 304918.63 | 2226587.41 | 03-FEB-06:03 | 13.66 | 7.48 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 331937.22 | 3132746.70 | 27-MAR-05:04 | 12.63 | 9.44 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 544184.59 | 3516798.16 | 29-APR-05:03 | 13.45 | 9.77 | 0.00 | 0.00 | 01-APR-00:10 |
May | 828065.71 | 4362754.49 | 22-MAY-03:02 | 14.40 | 10.54 | 0.00 | 0.00 | 01-MAY-00:03 |
June | 867169.31 | 3868680.65 | 09-JUN-05:03 | 13.53 | 10.10 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 864604.94 | 3768410.36 | 25-JUL-05:03 | 13.73 | 10.00 | 0.00 | 0.00 | 01-JUL-00:05 |
August | 908278.46 | 3995443.00 | 26-AUG-05:03 | 13.98 | 10.21 | 0.00 | 0.00 | 01-AUG-00:05 |
September | 847451.31 | 5258531.41 | 05-SEP-04:11 | 15.98 | 11.33 | 0.00 | 0.00 | 01-SEP-00:03 |
October | 701823.36 | 4043422.49 | 16-OCT-04:12 | 13.91 | 10.26 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 418187.26 | 2761043.76 | 02-NOV-05:03 | 13.58 | 8.71 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 286647.49 | 2623645.75 | 11-DEC-06:02 | 13.79 | 8.34 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 592818.47 | 0.00 | ||||||
Minimum of Months | 192554.05 | 2039251.96 | 12.63 | 7.42 | 0.00 | 0.00 | ||
Maximum of Months | 908278.46 | 5258531.41 | 15.98 | 11.33 | 0.00 | 0.00 |
Report: CondLoopDemandReportMonthly
For: SINGLE WATER PLANT LOOP
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 244694.07 | 757808.25 | 02-JAN-15:00 | 33.39 | 28.99 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 453531.44 | 1051181.21 | 02-FEB-13:10 | 39.11 | 31.62 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 693565.65 | 1355782.43 | 30-MAR-13:00 | 44.98 | 34.32 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 1082205.04 | 1785833.50 | 28-APR-15:00 | 53.16 | 39.63 | 0.00 | 0.00 | 01-APR-00:10 |
May | 747346.89 | 1121222.28 | 18-MAY-16:00 | 40.46 | 35.55 | 0.00 | 0.00 | 01-MAY-00:03 |
June | 1012099.31 | 1446365.16 | 14-JUN-14:00 | 46.71 | 38.70 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 1258577.43 | 1766253.46 | 21-JUL-16:00 | 52.79 | 41.41 | 0.00 | 0.00 | 01-JUL-00:05 |
August | 1450252.59 | 1940154.46 | 30-AUG-16:10 | 56.07 | 42.46 | 0.00 | 0.00 | 01-AUG-00:05 |
September | 714376.78 | 1280277.87 | 09-SEP-17:00 | 43.53 | 38.65 | 0.00 | 0.00 | 01-SEP-00:03 |
October | 829313.69 | 1398137.11 | 05-OCT-15:00 | 45.79 | 37.72 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 765033.61 | 1403194.82 | 02-NOV-13:00 | 45.88 | 35.02 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 839259.71 | 1598071.29 | 13-DEC-15:00 | 49.60 | 36.22 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 843462.01 | 0.00 | ||||||
Minimum of Months | 244694.07 | 757808.25 | 33.39 | 28.99 | 0.00 | 0.00 | ||
Maximum of Months | 1450252.59 | 1940154.46 | 56.07 | 42.46 | 0.00 | 0.00 |
Report: CondLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 56.94 | 56.94 | 12861.44 | 42408.96 | 24-JAN-13:00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 56.43 | 56.43 | 12836.67 | 42335.53 | 01-FEB-13:00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 57.38 | 57.38 | 13081.24 | 41396.33 | 01-MAR-12:30 |
April | 0.00 | 0.00 | 01-APR-00:10 | 57.10 | 57.10 | 11678.08 | 39140.91 | 03-APR-11:50 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 58.22 | 58.22 | 11278.95 | 36737.49 | 01-MAY-11:40 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 57.92 | 57.92 | 10890.08 | 34307.17 | 01-JUN-11:20 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 56.97 | 56.97 | 9856.92 | 32656.74 | 03-JUL-11:40 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 57.29 | 57.29 | 10754.41 | 33348.11 | 31-AUG-11:40 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 57.52 | 57.52 | 10625.05 | 35312.44 | 29-SEP-11:40 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 56.94 | 56.94 | 11282.63 | 38022.01 | 31-OCT-11:20 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 56.57 | 56.57 | 12146.67 | 40397.64 | 30-NOV-12:20 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 56.53 | 56.53 | 12316.14 | 41954.38 | 29-DEC-12:20 |
Annual Sum or Average | 0.00 | 11627.42 | ||||||
Minimum of Months | 0.00 | 0.00 | 56.43 | 56.43 | 9856.92 | 32656.74 | ||
Maximum of Months | 0.00 | 0.00 | 58.22 | 58.22 | 13081.24 | 42408.96 |
Report: CondLoopDemandReportMonthly
For: TOWERWATERSYS
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 279361.05 | 3997220.18 | 19-JAN-12:00 | 27.10 | 23.91 | 2009.84 | 177899.66 | 03-JAN-09:50 |
February | 434761.35 | 3868919.93 | 24-FEB-13:20 | 26.91 | 23.62 | 1496.07 | 171078.48 | 04-FEB-09:00 |
March | 518349.70 | 4562343.40 | 30-MAR-13:10 | 27.95 | 24.68 | 1872.90 | 204923.97 | 09-MAR-07:40 |
April | 919467.27 | 6110870.91 | 28-APR-16:00 | 30.27 | 27.12 | 487.18 | 113711.65 | 17-APR-06:00 |
May | 2053599.29 | 6272777.52 | 26-MAY-11:00 | 30.52 | 27.37 | 0.00 | 0.00 | 01-MAY-00:03 |
June | 2400503.29 | 6749978.90 | 28-JUN-14:00 | 31.23 | 27.98 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 2802263.26 | 6984286.73 | 03-JUL-16:00 | 31.58 | 28.23 | 0.00 | 0.00 | 01-JUL-00:05 |
August | 2744810.34 | 6923548.85 | 07-AUG-13:00 | 31.49 | 28.20 | 0.00 | 0.00 | 01-AUG-00:05 |
September | 2286893.00 | 6876295.10 | 18-SEP-14:00 | 31.42 | 28.15 | 0.00 | 0.00 | 01-SEP-00:03 |
October | 1723641.34 | 7211654.05 | 06-OCT-14:00 | 31.92 | 28.35 | 179.21 | 69482.81 | 27-OCT-19:30 |
November | 752317.07 | 5839330.35 | 01-NOV-14:00 | 29.87 | 26.67 | 929.79 | 158571.49 | 15-NOV-08:00 |
December | 488392.17 | 5204478.31 | 12-DEC-14:20 | 28.91 | 25.78 | 2078.39 | 206335.78 | 18-DEC-09:00 |
Annual Sum or Average | 1457182.65 | 752.74 | ||||||
Minimum of Months | 279361.05 | 3868919.93 | 26.91 | 23.62 | 0.00 | 0.00 | ||
Maximum of Months | 2802263.26 | 7211654.05 | 31.92 | 28.35 | 2078.39 | 206335.78 |
Report: ZoneTemperatureOscillationReportMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV_BOT WITH REHEAT
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.522541E+09 | 0.00 | 0.467295E+11 | 0.416201E+10 | 0.00 | 0.00 |
February | 0.178089E+09 | 0.00 | 0.661489E+11 | 0.425823E+10 | 0.00 | 0.00 |
March | 0.172796E+09 | 0.00 | 0.825852E+11 | 0.528209E+10 | 0.00 | 0.00 |
April | 7314064.13 | 0.00 | 0.132836E+12 | 0.619952E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.173246E+12 | 0.638286E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.185700E+12 | 0.703128E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.200820E+12 | 0.742022E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.220719E+12 | 0.874932E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.175495E+12 | 0.606918E+10 | 0.00 | 0.00 |
October | 2480054.62 | 0.00 | 0.160196E+12 | 0.687080E+10 | 0.00 | 0.00 |
November | 5289670.07 | 0.00 | 0.100490E+12 | 0.578473E+10 | 0.00 | 0.00 |
December | 0.250541E+09 | 0.00 | 0.739762E+11 | 0.537610E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.113905E+10 | 0.00 | 0.161894E+13 | 0.735863E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.467295E+11 | 0.416201E+10 | 0.00 | 0.00 |
Maximum of Months | 0.522541E+09 | 0.00 | 0.220719E+12 | 0.874932E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV_MID WITH REHEAT
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.333997E+11 | 0.00 | 0.374288E+12 | 0.319138E+11 | 0.00 | 0.00 |
February | 0.159183E+11 | 0.00 | 0.534092E+12 | 0.308545E+11 | 0.00 | 0.00 |
March | 0.147831E+11 | 0.00 | 0.638157E+12 | 0.362469E+11 | 0.00 | 0.00 |
April | 0.283246E+09 | 0.00 | 0.998860E+12 | 0.402611E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.157199E+13 | 0.555179E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.160344E+13 | 0.569916E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.167063E+13 | 0.555300E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.173400E+13 | 0.596953E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.157134E+13 | 0.502343E+11 | 0.00 | 0.00 |
October | 0.190052E+09 | 0.00 | 0.135109E+13 | 0.529935E+11 | 0.00 | 0.00 |
November | 0.201914E+10 | 0.00 | 0.783585E+12 | 0.390281E+11 | 0.00 | 0.00 |
December | 0.227782E+11 | 0.00 | 0.549538E+12 | 0.343836E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.893717E+11 | 0.00 | 0.133810E+14 | 0.543651E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.374288E+12 | 0.308545E+11 | 0.00 | 0.00 |
Maximum of Months | 0.333997E+11 | 0.00 | 0.173400E+13 | 0.596953E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV_TOP WITH REHEAT
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.864647E+10 | 0.00 | 0.381698E+11 | 0.307333E+10 | 0.00 | 0.00 |
February | 0.527197E+10 | 0.00 | 0.546978E+11 | 0.307884E+10 | 0.00 | 0.00 |
March | 0.410994E+10 | 0.00 | 0.662221E+11 | 0.353563E+10 | 0.00 | 0.00 |
April | 0.163282E+09 | 0.00 | 0.105315E+12 | 0.404818E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.171405E+12 | 0.601855E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.177286E+12 | 0.631989E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.184171E+12 | 0.610612E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.189363E+12 | 0.648754E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.167509E+12 | 0.522375E+10 | 0.00 | 0.00 |
October | 0.152794E+09 | 0.00 | 0.142904E+12 | 0.538821E+10 | 0.00 | 0.00 |
November | 0.103575E+10 | 0.00 | 0.778834E+11 | 0.360992E+10 | 0.00 | 0.00 |
December | 0.619070E+10 | 0.00 | 0.544034E+11 | 0.324573E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.255709E+11 | 0.00 | 0.142933E+13 | 0.561357E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.381698E+11 | 0.307333E+10 | 0.00 | 0.00 |
Maximum of Months | 0.864647E+10 | 0.00 | 0.189363E+12 | 0.648754E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: CAV_BAS
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.229355E+11 | 0.162293E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.284262E+11 | 0.141360E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.391337E+11 | 0.163594E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.619439E+11 | 0.148439E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.111483E+12 | 0.164777E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.116580E+12 | 0.162524E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.124090E+12 | 0.163878E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.137320E+12 | 0.180627E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.118261E+12 | 0.169814E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.101665E+12 | 0.174398E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.566141E+11 | 0.167225E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.373098E+11 | 0.167531E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.955762E+12 | 0.196646E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.229355E+11 | 0.141360E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.137320E+12 | 0.180627E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER BASEMENT
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.419220E+12 | 0.181909E+12 | 0.00 | 0.19 |
February | 0.00 | 0.00 | 0.657699E+12 | 0.219810E+12 | 0.00 | 0.13 |
March | 0.00 | 0.00 | 0.103944E+13 | 0.309382E+12 | 0.00 | 0.09 |
April | 0.00 | 0.00 | 0.133099E+13 | 0.384728E+12 | 0.00 | 0.02 |
May | 0.00 | 0.00 | 0.468568E+12 | 0.212657E+12 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.773145E+12 | 0.287004E+12 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.112980E+13 | 0.380879E+12 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.143845E+13 | 0.450667E+12 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.456792E+12 | 0.204852E+12 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.779849E+12 | 0.279411E+12 | 0.00 | 0.02 |
November | 0.00 | 0.00 | 0.102199E+13 | 0.307908E+12 | 0.00 | 0.03 |
December | 0.00 | 0.00 | 0.134121E+13 | 0.363977E+12 | 0.00 | 0.10 |
Annual Sum or Average | 0.00 | 0.00 | 0.108572E+14 | 0.358318E+13 | 0.00 | 0.58 |
Minimum of Months | 0.00 | 0.00 | 0.419220E+12 | 0.181909E+12 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.143845E+13 | 0.450667E+12 | 0.00 | 0.19 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER BOT
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.650249E+10 | 0.278479E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.120867E+11 | 0.374412E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.199969E+11 | 0.552460E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.264614E+11 | 0.715722E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.892030E+10 | 0.363544E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.152640E+11 | 0.517462E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.225300E+11 | 0.704698E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.292645E+11 | 0.864901E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.862543E+10 | 0.348103E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.151646E+11 | 0.497096E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.198540E+11 | 0.554200E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.261465E+11 | 0.664474E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.210817E+12 | 0.643555E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.650249E+10 | 0.278479E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.292645E+11 | 0.864901E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER MID
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.467838E+11 | 0.235956E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.103130E+12 | 0.334596E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.180383E+12 | 0.508411E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.248724E+12 | 0.676026E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.827808E+11 | 0.341265E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.144882E+12 | 0.491778E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.214789E+12 | 0.671718E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.278298E+12 | 0.823061E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.786824E+11 | 0.323631E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.140996E+12 | 0.466650E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.180283E+12 | 0.512114E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.236369E+12 | 0.611623E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.193610E+13 | 0.599683E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.467838E+11 | 0.235956E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.278298E+12 | 0.823061E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER TOP
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.346765E+10 | 0.214556E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.938185E+10 | 0.319795E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.174063E+11 | 0.500589E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.247096E+11 | 0.677017E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.843945E+10 | 0.348020E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.146799E+11 | 0.499351E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.216929E+11 | 0.680213E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.280246E+11 | 0.831593E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.796658E+10 | 0.328836E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.140190E+11 | 0.468609E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.174023E+11 | 0.504118E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.226862E+11 | 0.599064E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.189876E+12 | 0.597176E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.346765E+10 | 0.214556E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.280246E+11 | 0.831593E+10 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV_BOT WITH REHEAT
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.416201E+10 | 0.467295E+11 | 0.522541E+09 | 0.236583E+10 | 0.128597E+10 | 0.00 | 0.00 | 0.00 |
February | 0.425823E+10 | 0.661489E+11 | 0.178089E+09 | 0.121504E+10 | 0.210451E+10 | 0.00 | 0.00 | 0.00 |
March | 0.528209E+10 | 0.825852E+11 | 0.172796E+09 | 0.749118E+09 | 0.404297E+10 | 0.00 | 0.00 | 0.00 |
April | 0.619952E+10 | 0.132836E+12 | 7314064.13 | 0.00 | 0.109640E+11 | 0.00 | 0.00 | 0.00 |
May | 0.638286E+10 | 0.173246E+12 | 0.00 | 0.00 | 0.469436E+11 | 0.00 | 0.00 | 0.00 |
June | 0.703128E+10 | 0.185700E+12 | 0.00 | 0.00 | 0.567521E+11 | 0.00 | 0.00 | 0.00 |
July | 0.742022E+10 | 0.200820E+12 | 0.00 | 0.00 | 0.619540E+11 | 0.00 | 0.00 | 0.00 |
August | 0.874932E+10 | 0.220719E+12 | 0.00 | 0.00 | 0.611864E+11 | 0.00 | 0.00 | 0.00 |
September | 0.606918E+10 | 0.175495E+12 | 0.00 | 0.00 | 0.405832E+11 | 0.00 | 0.00 | 0.00 |
October | 0.687080E+10 | 0.160196E+12 | 2480054.62 | 4393221.41 | 0.343978E+11 | 0.00 | 0.00 | 0.00 |
November | 0.578473E+10 | 0.100490E+12 | 5289670.07 | 60710576.57 | 0.819496E+10 | 0.00 | 0.00 | 0.00 |
December | 0.537610E+10 | 0.739762E+11 | 0.250541E+09 | 0.971903E+09 | 0.457543E+10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.735863E+11 | 0.161894E+13 | 0.113905E+10 | 0.536699E+10 | 0.332985E+12 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.416201E+10 | 0.467295E+11 | 0.00 | 0.00 | 0.128597E+10 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.874932E+10 | 0.220719E+12 | 0.522541E+09 | 0.236583E+10 | 0.619540E+11 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV_MID WITH REHEAT
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.319138E+11 | 0.374288E+12 | 0.333997E+11 | 0.350315E+11 | 0.147994E+11 | 0.00 | 0.00 | 0.00 |
February | 0.308545E+11 | 0.534092E+12 | 0.159183E+11 | 0.180990E+11 | 0.239951E+11 | 0.00 | 0.00 | 0.00 |
March | 0.362469E+11 | 0.638157E+12 | 0.147831E+11 | 0.118841E+11 | 0.461752E+11 | 0.00 | 0.00 | 0.00 |
April | 0.402611E+11 | 0.998860E+12 | 0.283246E+09 | 44467303.29 | 0.109197E+12 | 0.00 | 0.00 | 0.00 |
May | 0.555179E+11 | 0.157199E+13 | 0.00 | 0.00 | 0.471541E+12 | 0.00 | 0.00 | 0.00 |
June | 0.569916E+11 | 0.160344E+13 | 0.00 | 0.00 | 0.566406E+12 | 0.00 | 0.00 | 0.00 |
July | 0.555300E+11 | 0.167063E+13 | 0.00 | 0.00 | 0.615834E+12 | 0.00 | 0.00 | 0.00 |
August | 0.596953E+11 | 0.173400E+13 | 0.00 | 0.00 | 0.607822E+12 | 0.00 | 0.00 | 0.00 |
September | 0.502343E+11 | 0.157134E+13 | 0.00 | 0.00 | 0.411327E+12 | 0.00 | 0.00 | 0.00 |
October | 0.529935E+11 | 0.135109E+13 | 0.190052E+09 | 0.193279E+09 | 0.344060E+12 | 0.00 | 0.00 | 0.00 |
November | 0.390281E+11 | 0.783585E+12 | 0.201914E+10 | 0.138626E+10 | 0.890699E+11 | 0.00 | 0.00 | 0.00 |
December | 0.343836E+11 | 0.549538E+12 | 0.227782E+11 | 0.216063E+11 | 0.471139E+11 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.543651E+12 | 0.133810E+14 | 0.893717E+11 | 0.882448E+11 | 0.334734E+13 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.308545E+11 | 0.374288E+12 | 0.00 | 0.00 | 0.147994E+11 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.596953E+11 | 0.173400E+13 | 0.333997E+11 | 0.350315E+11 | 0.615834E+12 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV_TOP WITH REHEAT
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.307333E+10 | 0.381698E+11 | 0.864647E+10 | 0.372933E+10 | 0.365652E+09 | 0.00 | 0.00 | 0.00 |
February | 0.307884E+10 | 0.546978E+11 | 0.527197E+10 | 0.184734E+10 | 0.116505E+10 | 0.00 | 0.00 | 0.00 |
March | 0.353563E+10 | 0.662221E+11 | 0.410994E+10 | 0.125133E+10 | 0.313384E+10 | 0.00 | 0.00 | 0.00 |
April | 0.404818E+10 | 0.105315E+12 | 0.163282E+09 | 4162036.91 | 0.939524E+10 | 0.00 | 0.00 | 0.00 |
May | 0.601855E+10 | 0.171405E+12 | 0.00 | 0.00 | 0.458387E+11 | 0.00 | 0.00 | 0.00 |
June | 0.631989E+10 | 0.177286E+12 | 0.00 | 0.00 | 0.550610E+11 | 0.00 | 0.00 | 0.00 |
July | 0.610612E+10 | 0.184171E+12 | 0.00 | 0.00 | 0.596236E+11 | 0.00 | 0.00 | 0.00 |
August | 0.648754E+10 | 0.189363E+12 | 0.00 | 0.00 | 0.592008E+11 | 0.00 | 0.00 | 0.00 |
September | 0.522375E+10 | 0.167509E+12 | 0.00 | 0.00 | 0.399677E+11 | 0.00 | 0.00 | 0.00 |
October | 0.538821E+10 | 0.142904E+12 | 0.152794E+09 | 19285630.65 | 0.336586E+11 | 0.00 | 0.00 | 0.00 |
November | 0.360992E+10 | 0.778834E+11 | 0.103575E+10 | 0.154674E+09 | 0.849102E+10 | 0.00 | 0.00 | 0.00 |
December | 0.324573E+10 | 0.544034E+11 | 0.619070E+10 | 0.245060E+10 | 0.420847E+10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.561357E+11 | 0.142933E+13 | 0.255709E+11 | 0.945672E+10 | 0.320110E+12 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.307333E+10 | 0.381698E+11 | 0.00 | 0.00 | 0.365652E+09 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.648754E+10 | 0.189363E+12 | 0.864647E+10 | 0.372933E+10 | 0.596236E+11 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: CAV_BAS
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.162293E+11 | 0.229355E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.141360E+11 | 0.284262E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.163594E+11 | 0.391337E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.148439E+11 | 0.619439E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.164777E+11 | 0.111483E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.162524E+11 | 0.116580E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.163878E+11 | 0.124090E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.180627E+11 | 0.137320E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.169814E+11 | 0.118261E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.174398E+11 | 0.101665E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.167225E+11 | 0.566141E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.167531E+11 | 0.373098E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.196646E+12 | 0.955762E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.141360E+11 | 0.229355E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.180627E+11 | 0.137320E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER BASEMENT
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.952024E+11 | 0.333017E+12 | 0.00 | 0.00 | 0.00 | 0.501091E+09 | 0.00 | 0.00 |
February | 0.859892E+11 | 0.524231E+12 | 0.00 | 0.00 | 0.00 | 0.350829E+09 | 0.00 | 0.00 |
March | 0.952024E+11 | 0.825493E+12 | 0.00 | 0.00 | 0.00 | 0.229377E+09 | 0.00 | 0.00 |
April | 0.921313E+11 | 0.103845E+13 | 0.00 | 0.00 | 0.00 | 63709407.00 | 0.00 | 0.00 |
May | 0.952024E+11 | 0.351114E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.921313E+11 | 0.578272E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.952024E+11 | 0.844125E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.952024E+11 | 0.108298E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.921313E+11 | 0.344072E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.952024E+11 | 0.595694E+12 | 0.00 | 0.00 | 0.00 | 53588092.45 | 0.00 | 0.00 |
November | 0.921313E+11 | 0.806303E+12 | 0.00 | 0.00 | 0.00 | 85238820.92 | 0.00 | 0.00 |
December | 0.952024E+11 | 0.107270E+13 | 0.00 | 0.00 | 0.00 | 0.262692E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.112093E+13 | 0.839646E+13 | 0.00 | 0.00 | 0.00 | 0.154652E+10 | 0.00 | 0.00 |
Minimum of Months | 0.859892E+11 | 0.333017E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.952024E+11 | 0.108298E+13 | 0.00 | 0.00 | 0.00 | 0.501091E+09 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER BOT
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.144065E+10 | 0.515835E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.130124E+10 | 0.964382E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.144065E+10 | 0.159130E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.139418E+10 | 0.206983E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.144065E+10 | 0.672551E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.139418E+10 | 0.114836E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.144065E+10 | 0.169237E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.144065E+10 | 0.220562E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.139418E+10 | 0.653858E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.144065E+10 | 0.116343E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.139418E+10 | 0.157062E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.144065E+10 | 0.209424E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.169625E+11 | 0.163424E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.130124E+10 | 0.515835E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.144065E+10 | 0.220562E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER MID
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.137230E+11 | 0.369112E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.123950E+11 | 0.820651E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.137230E+11 | 0.143265E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.132803E+11 | 0.194402E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.137230E+11 | 0.623773E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.132803E+11 | 0.108984E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.137230E+11 | 0.161340E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.137230E+11 | 0.209714E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.132803E+11 | 0.595997E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.137230E+11 | 0.108054E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.132803E+11 | 0.142352E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.137230E+11 | 0.188929E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.161577E+12 | 0.149800E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.123950E+11 | 0.369112E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.137230E+11 | 0.209714E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER TOP
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.139820E+10 | 0.272029E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.126289E+10 | 0.744680E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.139820E+10 | 0.137986E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.135310E+10 | 0.192925E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.139820E+10 | 0.635745E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.135310E+10 | 0.110395E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.139820E+10 | 0.162890E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.139820E+10 | 0.211069E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.135310E+10 | 0.603131E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.139820E+10 | 0.107311E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.135310E+10 | 0.137142E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.139820E+10 | 0.180937E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.164627E+11 | 0.146621E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.126289E+10 | 0.272029E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.139820E+10 | 0.211069E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV_BOT WITH REHEAT
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.416201E+10 | 0.522541E+09 | 0.467295E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.425823E+10 | 0.178089E+09 | 0.661489E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.528209E+10 | 0.172796E+09 | 0.825852E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.619952E+10 | 7314064.13 | 0.132836E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.638286E+10 | 0.00 | 0.173246E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.703128E+10 | 0.00 | 0.185700E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.742022E+10 | 0.00 | 0.200820E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.874932E+10 | 0.00 | 0.220719E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.606918E+10 | 0.00 | 0.175495E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.687080E+10 | 2480054.62 | 0.160196E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.578473E+10 | 5289670.07 | 0.100490E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.537610E+10 | 0.250541E+09 | 0.739762E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.735863E+11 | 0.113905E+10 | 0.161894E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.416201E+10 | 0.00 | 0.467295E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.874932E+10 | 0.522541E+09 | 0.220719E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV_MID WITH REHEAT
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.319138E+11 | 0.333997E+11 | 0.374288E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.308545E+11 | 0.159183E+11 | 0.534092E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.362469E+11 | 0.147831E+11 | 0.638157E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.402611E+11 | 0.283246E+09 | 0.998860E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.555179E+11 | 0.00 | 0.157199E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.569916E+11 | 0.00 | 0.160344E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.555300E+11 | 0.00 | 0.167063E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.596953E+11 | 0.00 | 0.173400E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.502343E+11 | 0.00 | 0.157134E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.529935E+11 | 0.190052E+09 | 0.135109E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.390281E+11 | 0.201914E+10 | 0.783585E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.343836E+11 | 0.227782E+11 | 0.549538E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.543651E+12 | 0.893717E+11 | 0.133810E+14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.308545E+11 | 0.00 | 0.374288E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.596953E+11 | 0.333997E+11 | 0.173400E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV_TOP WITH REHEAT
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.307333E+10 | 0.864647E+10 | 0.381698E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.307884E+10 | 0.527197E+10 | 0.546978E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.353563E+10 | 0.410994E+10 | 0.662221E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.404818E+10 | 0.163282E+09 | 0.105315E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.601855E+10 | 0.00 | 0.171405E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.631989E+10 | 0.00 | 0.177286E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.610612E+10 | 0.00 | 0.184171E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.648754E+10 | 0.00 | 0.189363E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.522375E+10 | 0.00 | 0.167509E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.538821E+10 | 0.152794E+09 | 0.142904E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.360992E+10 | 0.103575E+10 | 0.778834E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.324573E+10 | 0.619070E+10 | 0.544034E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.561357E+11 | 0.255709E+11 | 0.142933E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.307333E+10 | 0.00 | 0.381698E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.648754E+10 | 0.864647E+10 | 0.189363E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: CAV_BAS
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.162293E+11 | 0.00 | 0.229355E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.141360E+11 | 0.00 | 0.284262E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.163594E+11 | 0.00 | 0.391337E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.148439E+11 | 0.00 | 0.619439E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.164777E+11 | 0.00 | 0.111483E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.162524E+11 | 0.00 | 0.116580E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.163878E+11 | 0.00 | 0.124090E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.180627E+11 | 0.00 | 0.137320E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.169814E+11 | 0.00 | 0.118261E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.174398E+11 | 0.00 | 0.101665E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.167225E+11 | 0.00 | 0.566141E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.167531E+11 | 0.00 | 0.373098E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.196646E+12 | 0.00 | 0.955762E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.141360E+11 | 0.00 | 0.229355E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.180627E+11 | 0.00 | 0.137320E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER BASEMENT
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.952024E+11 | 0.00 | 0.419220E+12 | 0.00 | 0.862031E+11 | 0.00 | 0.00 | 0.00 | 0.503346E+09 | 0.00 | 0.00 | 0.00 |
February | 0.859892E+11 | 0.00 | 0.657699E+12 | 0.00 | 0.133468E+12 | 0.00 | 0.00 | 0.00 | 0.352408E+09 | 0.00 | 0.00 | 0.00 |
March | 0.952024E+11 | 0.00 | 0.103944E+13 | 0.00 | 0.213950E+12 | 0.00 | 0.00 | 0.00 | 0.230409E+09 | 0.00 | 0.00 | 0.00 |
April | 0.921313E+11 | 0.00 | 0.133099E+13 | 0.00 | 0.292533E+12 | 0.00 | 0.00 | 0.00 | 63996188.86 | 0.00 | 0.00 | 0.00 |
May | 0.952024E+11 | 0.00 | 0.468568E+12 | 0.00 | 0.117454E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.921313E+11 | 0.00 | 0.773145E+12 | 0.00 | 0.194873E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.952024E+11 | 0.00 | 0.112980E+13 | 0.00 | 0.285677E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.952024E+11 | 0.00 | 0.143845E+13 | 0.00 | 0.355464E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.921313E+11 | 0.00 | 0.456792E+12 | 0.00 | 0.112720E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.952024E+11 | 0.00 | 0.779849E+12 | 0.00 | 0.184155E+12 | 0.00 | 0.00 | 0.00 | 53829314.17 | 0.00 | 0.00 | 0.00 |
November | 0.921313E+11 | 0.00 | 0.102199E+13 | 0.00 | 0.215691E+12 | 0.00 | 0.00 | 0.00 | 85622515.41 | 0.00 | 0.00 | 0.00 |
December | 0.952024E+11 | 0.00 | 0.134121E+13 | 0.00 | 0.268510E+12 | 0.00 | 0.00 | 0.00 | 0.263875E+09 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.112093E+13 | 0.00 | 0.108572E+14 | 0.00 | 0.246070E+13 | 0.00 | 0.00 | 0.00 | 0.155349E+10 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.859892E+11 | 0.00 | 0.419220E+12 | 0.00 | 0.862031E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.952024E+11 | 0.00 | 0.143845E+13 | 0.00 | 0.355464E+12 | 0.00 | 0.00 | 0.00 | 0.503346E+09 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER BOT
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.144065E+10 | 0.00 | 0.650249E+10 | 0.00 | 0.134414E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.130124E+10 | 0.00 | 0.120867E+11 | 0.00 | 0.244288E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.144065E+10 | 0.00 | 0.199969E+11 | 0.00 | 0.408394E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.139418E+10 | 0.00 | 0.264614E+11 | 0.00 | 0.576304E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.144065E+10 | 0.00 | 0.892030E+10 | 0.00 | 0.219479E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.139418E+10 | 0.00 | 0.152640E+11 | 0.00 | 0.378044E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.144065E+10 | 0.00 | 0.225300E+11 | 0.00 | 0.560633E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.144065E+10 | 0.00 | 0.292645E+11 | 0.00 | 0.720836E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.139418E+10 | 0.00 | 0.862543E+10 | 0.00 | 0.208685E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.144065E+10 | 0.00 | 0.151646E+11 | 0.00 | 0.353031E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.139418E+10 | 0.00 | 0.198540E+11 | 0.00 | 0.414782E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.144065E+10 | 0.00 | 0.261465E+11 | 0.00 | 0.520409E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.169625E+11 | 0.00 | 0.210817E+12 | 0.00 | 0.473930E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.130124E+10 | 0.00 | 0.650249E+10 | 0.00 | 0.134414E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.144065E+10 | 0.00 | 0.292645E+11 | 0.00 | 0.720836E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER MID
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.137230E+11 | 0.00 | 0.467838E+11 | 0.00 | 0.987261E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.123950E+11 | 0.00 | 0.103130E+12 | 0.00 | 0.210646E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.137230E+11 | 0.00 | 0.180383E+12 | 0.00 | 0.371181E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.132803E+11 | 0.00 | 0.248724E+12 | 0.00 | 0.543222E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.137230E+11 | 0.00 | 0.827808E+11 | 0.00 | 0.204035E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.132803E+11 | 0.00 | 0.144882E+12 | 0.00 | 0.358975E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.137230E+11 | 0.00 | 0.214789E+12 | 0.00 | 0.534488E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.137230E+11 | 0.00 | 0.278298E+12 | 0.00 | 0.685831E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.132803E+11 | 0.00 | 0.786824E+11 | 0.00 | 0.190827E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.137230E+11 | 0.00 | 0.140996E+12 | 0.00 | 0.329420E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.132803E+11 | 0.00 | 0.180283E+12 | 0.00 | 0.379310E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.137230E+11 | 0.00 | 0.236369E+12 | 0.00 | 0.474392E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.161577E+12 | 0.00 | 0.193610E+13 | 0.00 | 0.438105E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.123950E+11 | 0.00 | 0.467838E+11 | 0.00 | 0.987261E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.137230E+11 | 0.00 | 0.278298E+12 | 0.00 | 0.685831E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER TOP
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.139820E+10 | 0.00 | 0.346765E+10 | 0.00 | 0.747360E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.126289E+10 | 0.00 | 0.938185E+10 | 0.00 | 0.193506E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.139820E+10 | 0.00 | 0.174063E+11 | 0.00 | 0.360769E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.135310E+10 | 0.00 | 0.247096E+11 | 0.00 | 0.541708E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.139820E+10 | 0.00 | 0.843945E+10 | 0.00 | 0.208200E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.135310E+10 | 0.00 | 0.146799E+11 | 0.00 | 0.364042E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.139820E+10 | 0.00 | 0.216929E+11 | 0.00 | 0.540393E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.139820E+10 | 0.00 | 0.280246E+11 | 0.00 | 0.691773E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.135310E+10 | 0.00 | 0.796658E+10 | 0.00 | 0.193527E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.139820E+10 | 0.00 | 0.140190E+11 | 0.00 | 0.328789E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.135310E+10 | 0.00 | 0.174023E+11 | 0.00 | 0.368809E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.139820E+10 | 0.00 | 0.226862E+11 | 0.00 | 0.459244E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.164627E+11 | 0.00 | 0.189876E+12 | 0.00 | 0.432549E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.126289E+10 | 0.00 | 0.346765E+10 | 0.00 | 0.747360E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.139820E+10 | 0.00 | 0.280246E+11 | 0.00 | 0.691773E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.243392E+09 | 0.151532E+10 | 0.00 | 0.115086E+09 | 0.00 | 0.00 | 0.608662E+11 | 0.00 | 1.06 |
February | 0.198622E+09 | 0.161628E+10 | 0.00 | 92051924.46 | 3557102.15 | 0.00 | 0.459597E+11 | 0.00 | 1.16 |
March | 0.130722E+09 | 0.331589E+10 | 0.00 | 99791728.34 | 5574606.93 | 0.00 | 0.492071E+11 | 0.00 | 1.16 |
April | 0.119404E+09 | 0.584394E+10 | 0.00 | 66029511.31 | 71835478.61 | 0.00 | 0.219647E+11 | 0.00 | 0.99 |
May | 337575.76 | 0.265713E+11 | 0.00 | 1457651.17 | 0.147091E+09 | 0.00 | 13805520.41 | 0.00 | 0.33 |
June | 0.00 | 0.319651E+11 | 0.00 | 2247198.16 | 0.204663E+09 | 0.00 | 81534263.97 | 0.00 | 0.35 |
July | 0.00 | 0.383474E+11 | 0.00 | 0.00 | 0.401541E+09 | 0.00 | 0.00 | 0.00 | 0.31 |
August | 0.00 | 0.391665E+11 | 0.00 | 195417.91 | 0.224867E+09 | 0.00 | 10354922.10 | 0.00 | 0.34 |
September | 0.00 | 0.294466E+11 | 0.00 | 1470794.02 | 0.285732E+09 | 0.00 | 0.113475E+09 | 0.00 | 0.34 |
October | 0.122731E+09 | 0.222525E+11 | 0.00 | 44955518.59 | 0.225553E+09 | 0.00 | 0.136138E+11 | 0.00 | 0.73 |
November | 0.294444E+09 | 0.669784E+10 | 0.00 | 0.105000E+09 | 6698695.24 | 0.00 | 0.400171E+11 | 0.00 | 1.24 |
December | 0.346179E+09 | 0.424889E+10 | 0.00 | 0.112103E+09 | 9353834.13 | 0.00 | 0.544675E+11 | 0.00 | 1.03 |
Annual Sum or Average | 0.145583E+10 | 0.210988E+12 | 0.00 | 0.640389E+09 | 0.158647E+10 | 0.00 | 0.286315E+12 | 0.00 | 0.75 |
Minimum of Months | 0.00 | 0.151532E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.31 |
Maximum of Months | 0.346179E+09 | 0.391665E+11 | 0.00 | 0.115086E+09 | 0.401541E+09 | 0.00 | 0.608662E+11 | 0.00 | 1.24 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.355776E+10 | 0.365483E+10 | 0.00 | 56873877.30 | 0.00 | 0.00 | 0.326969E+11 | 0.00 | 0.61 |
February | 0.260298E+10 | 0.426920E+10 | 0.00 | 50511085.46 | 61139657.02 | 0.00 | 0.202056E+11 | 0.00 | 0.62 |
March | 0.207820E+10 | 0.651818E+10 | 0.00 | 71440906.72 | 0.136262E+09 | 0.00 | 0.281313E+11 | 0.00 | 0.69 |
April | 0.221295E+10 | 0.102106E+11 | 0.00 | 38676838.20 | 0.132040E+09 | 0.00 | 0.778881E+10 | 0.00 | 0.61 |
May | 0.00 | 0.215109E+11 | 0.00 | 0.00 | 0.227013E+09 | 0.00 | 0.00 | 0.00 | 0.41 |
June | 0.00 | 0.218577E+11 | 0.00 | 0.00 | 0.233924E+09 | 0.00 | 0.00 | 0.00 | 0.41 |
July | 0.00 | 0.249103E+11 | 0.00 | 0.00 | 0.399275E+09 | 0.00 | 0.00 | 0.00 | 0.38 |
August | 4917862.93 | 0.262944E+11 | 0.00 | 0.00 | 0.254596E+09 | 0.00 | 0.00 | 0.00 | 0.41 |
September | 0.00 | 0.262400E+11 | 0.00 | 0.00 | 0.449793E+09 | 0.00 | 0.00 | 0.00 | 0.41 |
October | 0.443876E+09 | 0.169612E+11 | 0.00 | 23070074.63 | 0.276791E+09 | 0.00 | 0.621965E+10 | 0.00 | 0.48 |
November | 0.255905E+10 | 0.836247E+10 | 0.00 | 63796564.73 | 75837553.19 | 0.00 | 0.190388E+11 | 0.00 | 0.68 |
December | 0.260864E+10 | 0.675494E+10 | 0.00 | 74513945.94 | 0.127826E+09 | 0.00 | 0.325347E+11 | 0.00 | 0.66 |
Annual Sum or Average | 0.160684E+11 | 0.177545E+12 | 0.00 | 0.378883E+09 | 0.237450E+10 | 0.00 | 0.146616E+12 | 0.00 | 0.53 |
Minimum of Months | 0.00 | 0.365483E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.38 |
Maximum of Months | 0.355776E+10 | 0.262944E+11 | 0.00 | 74513945.94 | 0.449793E+09 | 0.00 | 0.326969E+11 | 0.00 | 0.69 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.139262E+12 | 0.266202E+11 | 0.00 | 0.218446E+09 | 0.780257E+10 | 0.00 | 0.141881E+12 | 0.00 | 0.51 |
February | 0.839744E+11 | 0.338329E+11 | 0.00 | 0.188616E+09 | 0.727752E+10 | 0.00 | 0.818241E+11 | 0.00 | 0.51 |
March | 0.832502E+11 | 0.494855E+11 | 0.00 | 0.298558E+09 | 0.123474E+11 | 0.00 | 0.135747E+12 | 0.00 | 0.57 |
April | 0.224046E+11 | 0.905107E+11 | 0.00 | 0.190598E+09 | 0.114616E+11 | 0.00 | 0.401044E+11 | 0.00 | 0.52 |
May | 0.00 | 0.199688E+12 | 0.00 | 0.00 | 0.112429E+11 | 0.00 | 0.00 | 0.00 | 0.41 |
June | 0.00 | 0.205352E+12 | 0.00 | 0.00 | 0.113455E+11 | 0.00 | 0.00 | 0.00 | 0.41 |
July | 0.00 | 0.231129E+12 | 0.00 | 0.00 | 0.165881E+11 | 0.00 | 0.00 | 0.00 | 0.38 |
August | 0.00 | 0.246011E+12 | 0.00 | 0.00 | 0.105030E+11 | 0.00 | 0.00 | 0.00 | 0.42 |
September | 0.00 | 0.239443E+12 | 0.00 | 0.00 | 0.174078E+11 | 0.00 | 0.00 | 0.00 | 0.41 |
October | 0.114657E+11 | 0.155059E+12 | 0.00 | 0.133990E+09 | 0.108531E+11 | 0.00 | 0.422816E+11 | 0.00 | 0.45 |
November | 0.530750E+11 | 0.712201E+11 | 0.00 | 0.288182E+09 | 0.610842E+10 | 0.00 | 0.979859E+11 | 0.00 | 0.56 |
December | 0.104349E+12 | 0.590795E+11 | 0.00 | 0.245161E+09 | 0.742813E+10 | 0.00 | 0.128464E+12 | 0.00 | 0.51 |
Annual Sum or Average | 0.497781E+12 | 0.160743E+13 | 0.00 | 0.156355E+10 | 0.130366E+12 | 0.00 | 0.668288E+12 | 0.00 | 0.47 |
Minimum of Months | 0.00 | 0.266202E+11 | 0.00 | 0.00 | 0.610842E+10 | 0.00 | 0.00 | 0.00 | 0.38 |
Maximum of Months | 0.139262E+12 | 0.246011E+12 | 0.00 | 0.298558E+09 | 0.174078E+11 | 0.00 | 0.141881E+12 | 0.00 | 0.57 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.191433E+11 | 0.279817E+10 | 0.00 | 6136112.37 | 0.115466E+10 | 0.179822E+09 | 0.491074E+10 | 0.00 | 0.49 |
February | 0.103464E+11 | 0.344451E+10 | 0.00 | 8576727.75 | 0.123354E+10 | 0.167907E+09 | 0.445994E+10 | 0.00 | 0.50 |
March | 0.116787E+11 | 0.518442E+10 | 0.00 | 14867662.65 | 0.152817E+10 | 61455381.88 | 0.750294E+10 | 0.00 | 0.55 |
April | 0.251615E+10 | 0.875555E+10 | 0.00 | 13782828.41 | 0.167253E+10 | 0.00 | 0.326836E+10 | 0.00 | 0.50 |
May | 0.00 | 0.200419E+11 | 0.00 | 0.00 | 0.835068E+09 | 0.00 | 0.00 | 0.00 | 0.41 |
June | 0.00 | 0.211635E+11 | 0.00 | 0.00 | 0.299950E+09 | 0.00 | 0.00 | 0.00 | 0.41 |
July | 0.00 | 0.243550E+11 | 0.00 | 0.00 | 0.594978E+09 | 0.00 | 0.00 | 0.00 | 0.38 |
August | 0.00 | 0.250617E+11 | 0.00 | 0.00 | 0.492118E+09 | 0.00 | 0.00 | 0.00 | 0.42 |
September | 0.00 | 0.236377E+11 | 0.00 | 0.00 | 0.189109E+10 | 0.00 | 0.00 | 0.00 | 0.41 |
October | 0.171346E+10 | 0.153420E+11 | 0.00 | 9207618.52 | 0.940349E+09 | 0.00 | 0.284982E+10 | 0.00 | 0.44 |
November | 0.722242E+10 | 0.625618E+10 | 0.00 | 15138164.41 | 0.154328E+10 | 0.00 | 0.571783E+10 | 0.00 | 0.53 |
December | 0.165784E+11 | 0.499602E+10 | 0.00 | 5376553.69 | 0.178505E+10 | 35019783.03 | 0.314658E+10 | 0.00 | 0.49 |
Annual Sum or Average | 0.691988E+11 | 0.161037E+12 | 0.00 | 73085667.79 | 0.139708E+11 | 0.444205E+09 | 0.318562E+11 | 0.00 | 0.46 |
Minimum of Months | 0.00 | 0.279817E+10 | 0.00 | 0.00 | 0.299950E+09 | 0.00 | 0.00 | 0.00 | 0.38 |
Maximum of Months | 0.191433E+11 | 0.250617E+11 | 0.00 | 15138164.41 | 0.189109E+10 | 0.179822E+09 | 0.750294E+10 | 0.00 | 0.55 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.313446E+10 | 0.423259E+09 | 0.00 | 719856.26 | 25751789.64 | 20153322.01 | 0.533239E+09 | 0.00 | 0.51 |
February | 0.171655E+10 | 0.524434E+09 | 0.00 | 1363717.56 | 16231518.96 | 290467.73 | 0.590727E+09 | 0.00 | 0.52 |
March | 0.175292E+10 | 0.887780E+09 | 0.00 | 2786098.42 | 19358819.03 | 0.00 | 0.120252E+10 | 0.00 | 0.60 |
April | 0.559291E+09 | 0.149431E+10 | 0.00 | 2465464.39 | 17474482.01 | 0.00 | 0.506707E+09 | 0.00 | 0.63 |
May | 0.00 | 0.380578E+10 | 0.00 | 0.00 | 28546075.04 | 0.00 | 0.00 | 0.00 | 0.58 |
June | 0.00 | 0.427608E+10 | 0.00 | 0.00 | 29415084.53 | 0.00 | 0.00 | 0.00 | 0.64 |
July | 0.00 | 0.480809E+10 | 0.00 | 0.00 | 50207294.98 | 0.00 | 0.00 | 0.00 | 0.58 |
August | 618402.44 | 0.472825E+10 | 0.00 | 0.00 | 32014455.40 | 0.00 | 0.00 | 0.00 | 0.60 |
September | 0.00 | 0.416932E+10 | 0.00 | 0.00 | 56559724.06 | 0.00 | 0.00 | 0.00 | 0.53 |
October | 0.287652E+09 | 0.272413E+10 | 0.00 | 1483967.41 | 34805457.31 | 0.00 | 0.432318E+09 | 0.00 | 0.55 |
November | 0.118061E+10 | 0.110103E+10 | 0.00 | 2948315.08 | 9536282.03 | 0.00 | 0.978265E+09 | 0.00 | 0.59 |
December | 0.236252E+10 | 0.835159E+09 | 0.00 | 1688078.82 | 20275257.23 | 0.00 | 0.885044E+09 | 0.00 | 0.53 |
Annual Sum or Average | 0.109946E+11 | 0.297776E+11 | 0.00 | 13455497.94 | 0.340176E+09 | 20443789.74 | 0.512882E+10 | 0.00 | 0.57 |
Minimum of Months | 0.00 | 0.423259E+09 | 0.00 | 0.00 | 9536282.03 | 0.00 | 0.00 | 0.00 | 0.51 |
Maximum of Months | 0.313446E+10 | 0.480809E+10 | 0.00 | 2948315.08 | 56559724.06 | 20153322.01 | 0.120252E+10 | 0.00 | 0.64 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.222034E+10 | 0.272746E+09 | 0.00 | 1702073.58 | 98046262.02 | 35501967.87 | 0.124076E+10 | 0.00 | 0.72 |
February | 0.132605E+10 | 0.399077E+09 | 0.00 | 1854897.27 | 67068144.93 | 1662155.72 | 0.898585E+09 | 0.00 | 0.76 |
March | 0.164022E+10 | 0.683205E+09 | 0.00 | 3209352.76 | 90895156.05 | 584798.97 | 0.130136E+10 | 0.00 | 0.89 |
April | 0.537850E+09 | 0.117015E+10 | 0.00 | 2447961.42 | 0.129717E+09 | 0.00 | 0.614490E+09 | 0.00 | 0.89 |
May | 0.00 | 0.314487E+10 | 0.00 | 0.00 | 27362069.66 | 0.00 | 0.00 | 0.00 | 0.75 |
June | 0.00 | 0.332188E+10 | 0.00 | 0.00 | 33177415.90 | 0.00 | 0.00 | 0.00 | 0.77 |
July | 0.00 | 0.367784E+10 | 0.00 | 0.00 | 46882231.66 | 0.00 | 0.00 | 0.00 | 0.68 |
August | 565547.34 | 0.337540E+10 | 0.00 | 0.00 | 84750228.20 | 0.00 | 0.00 | 0.00 | 0.68 |
September | 0.00 | 0.325851E+10 | 0.00 | 0.00 | 0.112408E+09 | 0.00 | 0.00 | 0.00 | 0.65 |
October | 0.294664E+09 | 0.216133E+10 | 0.00 | 1303070.56 | 69520942.67 | 0.00 | 0.350813E+09 | 0.00 | 0.70 |
November | 0.107458E+10 | 0.775839E+09 | 0.00 | 2984450.83 | 0.112500E+09 | 0.00 | 0.998395E+09 | 0.00 | 0.81 |
December | 0.211878E+10 | 0.447813E+09 | 0.00 | 1849868.44 | 0.176288E+09 | 36574138.38 | 0.892236E+09 | 0.00 | 0.71 |
Annual Sum or Average | 0.921305E+10 | 0.226887E+11 | 0.00 | 15351674.86 | 0.104862E+10 | 74323060.95 | 0.629664E+10 | 0.00 | 0.75 |
Minimum of Months | 0.00 | 0.272746E+09 | 0.00 | 0.00 | 27362069.66 | 0.00 | 0.00 | 0.00 | 0.65 |
Maximum of Months | 0.222034E+10 | 0.367784E+10 | 0.00 | 3209352.76 | 0.176288E+09 | 36574138.38 | 0.130136E+10 | 0.00 | 0.89 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.172682E+10 | 0.684166E+09 | 0.00 | 10054595.69 | 9908607.29 | 24047782.09 | 0.478566E+10 | 0.00 | 0.93 |
February | 0.108727E+10 | 0.100807E+10 | 0.00 | 6429411.22 | 10395969.38 | 15912132.32 | 0.262804E+10 | 0.00 | 0.90 |
March | 0.159324E+10 | 0.118866E+10 | 0.00 | 6032906.07 | 20734340.69 | 0.00 | 0.230548E+10 | 0.00 | 0.85 |
April | 0.587881E+09 | 0.173457E+10 | 0.00 | 2959549.81 | 25840851.83 | 0.00 | 0.609637E+09 | 0.00 | 0.74 |
May | 0.00 | 0.381870E+10 | 0.00 | 0.00 | 29645510.90 | 0.00 | 0.00 | 0.00 | 0.59 |
June | 0.00 | 0.407336E+10 | 0.00 | 0.00 | 30547989.79 | 0.00 | 0.00 | 0.00 | 0.61 |
July | 0.00 | 0.472789E+10 | 0.00 | 0.00 | 52141000.41 | 0.00 | 0.00 | 0.00 | 0.57 |
August | 642219.86 | 0.511604E+10 | 0.00 | 0.00 | 33247473.96 | 0.00 | 0.00 | 0.00 | 0.65 |
September | 0.00 | 0.502022E+10 | 0.00 | 0.00 | 58738089.68 | 0.00 | 0.00 | 0.00 | 0.64 |
October | 0.232035E+09 | 0.394671E+10 | 0.00 | 3138518.68 | 32479647.71 | 0.00 | 0.751034E+09 | 0.00 | 0.83 |
November | 0.668782E+09 | 0.175616E+10 | 0.00 | 11927178.45 | 9903566.51 | 0.00 | 0.314933E+10 | 0.00 | 1.09 |
December | 0.147097E+10 | 0.133828E+10 | 0.00 | 11845274.37 | 17282238.25 | 21327982.50 | 0.415811E+10 | 0.00 | 1.01 |
Annual Sum or Average | 0.736764E+10 | 0.344128E+11 | 0.00 | 52387434.29 | 0.330865E+09 | 61287896.92 | 0.183873E+11 | 0.00 | 0.78 |
Minimum of Months | 0.00 | 0.684166E+09 | 0.00 | 0.00 | 9903566.51 | 0.00 | 0.00 | 0.00 | 0.57 |
Maximum of Months | 0.172682E+10 | 0.511604E+10 | 0.00 | 11927178.45 | 58738089.68 | 24047782.09 | 0.478566E+10 | 0.00 | 1.09 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.288024E+10 | 0.513210E+09 | 0.00 | 2895995.74 | 3370923.76 | 0.00 | 0.168576E+10 | 0.00 | 0.97 |
February | 0.133823E+10 | 0.703962E+09 | 0.00 | 3848583.22 | 4307854.15 | 0.00 | 0.162143E+10 | 0.00 | 1.06 |
March | 0.971011E+09 | 0.110742E+10 | 0.00 | 7488466.84 | 9746023.33 | 0.00 | 0.301489E+10 | 0.00 | 1.28 |
April | 0.241962E+09 | 0.213529E+10 | 0.00 | 7131106.61 | 5140629.61 | 0.00 | 0.122587E+10 | 0.00 | 1.38 |
May | 0.00 | 0.367427E+10 | 0.00 | 0.00 | 23671915.41 | 0.00 | 0.00 | 0.00 | 0.88 |
June | 0.00 | 0.429826E+10 | 0.00 | 0.00 | 9242815.01 | 0.00 | 0.00 | 0.00 | 1.01 |
July | 0.00 | 0.511628E+10 | 0.00 | 0.00 | 14311711.65 | 0.00 | 0.00 | 0.00 | 0.95 |
August | 566057.45 | 0.570944E+10 | 0.00 | 13549.95 | 10670654.41 | 0.00 | 128695.78 | 0.00 | 1.12 |
September | 0.00 | 0.424105E+10 | 0.00 | 0.00 | 39634478.34 | 0.00 | 0.00 | 0.00 | 0.83 |
October | 0.157741E+09 | 0.301809E+10 | 0.00 | 2504754.15 | 29323370.18 | 0.00 | 0.708877E+09 | 0.00 | 0.99 |
November | 0.585737E+09 | 0.138325E+10 | 0.00 | 7263582.30 | 1784617.59 | 0.00 | 0.223684E+10 | 0.00 | 1.22 |
December | 0.102202E+10 | 0.115196E+10 | 0.00 | 7336991.82 | 18403362.91 | 0.00 | 0.336136E+10 | 0.00 | 1.17 |
Annual Sum or Average | 0.719751E+10 | 0.330525E+11 | 0.00 | 38483030.63 | 0.169608E+09 | 0.00 | 0.138552E+11 | 0.00 | 1.07 |
Minimum of Months | 0.00 | 0.513210E+09 | 0.00 | 0.00 | 1784617.59 | 0.00 | 0.00 | 0.00 | 0.83 |
Maximum of Months | 0.288024E+10 | 0.570944E+10 | 0.00 | 7488466.84 | 39634478.34 | 0.00 | 0.336136E+10 | 0.00 | 1.38 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.264145E+11 | 0.219706E+10 | 0.00 | 137039.73 | 0.195159E+10 | 0.710211E+10 | 38179864.82 | 0.00 | 0.48 |
February | 0.158311E+11 | 0.309689E+10 | 0.00 | 762919.11 | 0.185209E+10 | 0.297542E+10 | 0.829616E+09 | 0.00 | 0.48 |
March | 0.204006E+11 | 0.604993E+10 | 0.00 | 4068480.49 | 0.191971E+10 | 0.278775E+10 | 0.165937E+10 | 0.00 | 0.53 |
April | 0.546891E+10 | 0.121032E+11 | 0.00 | 9745412.87 | 0.200709E+10 | 0.00 | 0.156888E+10 | 0.00 | 0.53 |
May | 0.00 | 0.366430E+11 | 0.00 | 0.00 | 0.286571E+09 | 0.00 | 0.00 | 0.00 | 0.58 |
June | 0.00 | 0.421364E+11 | 0.00 | 0.00 | 0.368473E+09 | 0.00 | 0.00 | 0.00 | 0.65 |
July | 0.00 | 0.478725E+11 | 0.00 | 0.00 | 0.510313E+09 | 0.00 | 0.00 | 0.00 | 0.59 |
August | 0.00 | 0.462514E+11 | 0.00 | 0.00 | 0.324922E+09 | 0.00 | 0.00 | 0.00 | 0.61 |
September | 0.00 | 0.390098E+11 | 0.00 | 0.00 | 0.108268E+10 | 0.00 | 0.00 | 0.00 | 0.52 |
October | 0.369650E+10 | 0.251465E+11 | 0.00 | 7617534.97 | 0.913637E+09 | 0.00 | 0.226617E+10 | 0.00 | 0.51 |
November | 0.146151E+11 | 0.790069E+10 | 0.00 | 6653640.14 | 0.197638E+10 | 98939227.66 | 0.220261E+10 | 0.00 | 0.51 |
December | 0.228210E+11 | 0.528694E+10 | 0.00 | 643455.83 | 0.274661E+10 | 0.428812E+10 | 0.267237E+09 | 0.00 | 0.47 |
Annual Sum or Average | 0.109248E+12 | 0.273694E+12 | 0.00 | 29628483.14 | 0.159401E+11 | 0.172523E+11 | 0.883207E+10 | 0.00 | 0.54 |
Minimum of Months | 0.00 | 0.219706E+10 | 0.00 | 0.00 | 0.286571E+09 | 0.00 | 0.00 | 0.00 | 0.47 |
Maximum of Months | 0.264145E+11 | 0.478725E+11 | 0.00 | 9745412.87 | 0.274661E+10 | 0.710211E+10 | 0.226617E+10 | 0.00 | 0.65 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.258280E+11 | 0.181473E+10 | 0.00 | 2001138.67 | 0.217893E+10 | 0.443603E+10 | 0.201203E+10 | 0.00 | 0.72 |
February | 0.148307E+11 | 0.336648E+10 | 0.00 | 6425160.79 | 0.164131E+10 | 0.145030E+10 | 0.288886E+10 | 0.00 | 0.74 |
March | 0.156835E+11 | 0.657534E+10 | 0.00 | 18396900.80 | 0.172332E+10 | 0.234452E+10 | 0.721792E+10 | 0.00 | 0.86 |
April | 0.376113E+10 | 0.122878E+11 | 0.00 | 19225933.09 | 0.237570E+10 | 0.00 | 0.487370E+10 | 0.00 | 0.88 |
May | 0.00 | 0.328229E+11 | 0.00 | 0.00 | 0.618516E+09 | 0.00 | 0.00 | 0.00 | 0.82 |
June | 0.00 | 0.363796E+11 | 0.00 | 0.00 | 0.359117E+09 | 0.00 | 0.00 | 0.00 | 0.87 |
July | 0.00 | 0.414594E+11 | 0.00 | 0.00 | 0.748839E+09 | 0.00 | 0.00 | 0.00 | 0.79 |
August | 0.00 | 0.389807E+11 | 0.00 | 0.00 | 0.110571E+10 | 0.00 | 0.00 | 0.00 | 0.81 |
September | 0.00 | 0.313944E+11 | 0.00 | 0.00 | 0.375811E+10 | 0.00 | 0.00 | 0.00 | 0.70 |
October | 0.344106E+10 | 0.222690E+11 | 0.00 | 8924881.40 | 0.170044E+10 | 0.00 | 0.229974E+10 | 0.00 | 0.74 |
November | 0.110671E+11 | 0.689951E+10 | 0.00 | 14255369.70 | 0.243685E+10 | 83594452.60 | 0.557188E+10 | 0.00 | 0.77 |
December | 0.210362E+11 | 0.375650E+10 | 0.00 | 4332866.13 | 0.337111E+10 | 0.321937E+10 | 0.218719E+10 | 0.00 | 0.70 |
Annual Sum or Average | 0.956476E+11 | 0.238006E+12 | 0.00 | 73562250.57 | 0.220180E+11 | 0.115338E+11 | 0.270513E+11 | 0.00 | 0.78 |
Minimum of Months | 0.00 | 0.181473E+10 | 0.00 | 0.00 | 0.359117E+09 | 0.00 | 0.00 | 0.00 | 0.70 |
Maximum of Months | 0.258280E+11 | 0.414594E+11 | 0.00 | 19225933.09 | 0.375811E+10 | 0.443603E+10 | 0.721792E+10 | 0.00 | 0.88 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.143893E+11 | 0.650659E+10 | 0.00 | 87789986.88 | 0.623240E+09 | 0.257507E+10 | 0.406495E+11 | 0.00 | 0.90 |
February | 0.941285E+10 | 0.105463E+11 | 0.00 | 51992712.80 | 0.290865E+09 | 0.107481E+10 | 0.201363E+11 | 0.00 | 0.86 |
March | 0.149429E+11 | 0.106159E+11 | 0.00 | 42006027.15 | 0.980344E+09 | 0.202538E+10 | 0.146794E+11 | 0.00 | 0.77 |
April | 0.459800E+10 | 0.159126E+11 | 0.00 | 20105786.25 | 0.132786E+10 | 0.00 | 0.363218E+10 | 0.00 | 0.67 |
May | 0.00 | 0.373220E+11 | 0.00 | 0.00 | 0.290377E+09 | 0.00 | 0.00 | 0.00 | 0.60 |
June | 0.00 | 0.401223E+11 | 0.00 | 0.00 | 0.378283E+09 | 0.00 | 0.00 | 0.00 | 0.62 |
July | 0.00 | 0.473108E+11 | 0.00 | 0.00 | 0.517089E+09 | 0.00 | 0.00 | 0.00 | 0.58 |
August | 0.00 | 0.515561E+11 | 0.00 | 0.00 | 0.329236E+09 | 0.00 | 0.00 | 0.00 | 0.68 |
September | 0.00 | 0.498109E+11 | 0.00 | 0.00 | 0.838072E+09 | 0.00 | 0.00 | 0.00 | 0.67 |
October | 0.259185E+10 | 0.404817E+11 | 0.00 | 24755983.27 | 0.381352E+09 | 0.00 | 0.579723E+10 | 0.00 | 0.85 |
November | 0.658519E+10 | 0.171152E+11 | 0.00 | 0.105962E+09 | 0.627246E+09 | 0.00 | 0.249317E+11 | 0.00 | 1.04 |
December | 0.141991E+11 | 0.134564E+11 | 0.00 | 94861757.81 | 0.730443E+09 | 0.133833E+10 | 0.299640E+11 | 0.00 | 0.94 |
Annual Sum or Average | 0.667191E+11 | 0.340757E+12 | 0.00 | 0.427474E+09 | 0.731441E+10 | 0.701359E+10 | 0.139790E+12 | 0.00 | 0.76 |
Minimum of Months | 0.00 | 0.650659E+10 | 0.00 | 0.00 | 0.290377E+09 | 0.00 | 0.00 | 0.00 | 0.58 |
Maximum of Months | 0.149429E+11 | 0.515561E+11 | 0.00 | 0.105962E+09 | 0.132786E+10 | 0.257507E+10 | 0.406495E+11 | 0.00 | 1.04 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.252302E+11 | 0.306757E+10 | 0.00 | 9197743.98 | 0.163128E+10 | 0.423376E+10 | 0.550134E+10 | 0.00 | 0.80 |
February | 0.150348E+11 | 0.459075E+10 | 0.00 | 8856691.92 | 0.136975E+10 | 0.169862E+10 | 0.403741E+10 | 0.00 | 0.83 |
March | 0.192162E+11 | 0.649601E+10 | 0.00 | 19445947.16 | 0.158727E+10 | 0.144212E+10 | 0.669651E+10 | 0.00 | 0.92 |
April | 0.466683E+10 | 0.141420E+11 | 0.00 | 18987832.04 | 0.154949E+10 | 0.00 | 0.323297E+10 | 0.00 | 0.94 |
May | 0.00 | 0.320883E+11 | 0.00 | 0.00 | 0.425114E+09 | 0.00 | 0.00 | 0.00 | 0.80 |
June | 0.00 | 0.358571E+11 | 0.00 | 0.00 | 0.381991E+09 | 0.00 | 0.00 | 0.00 | 0.87 |
July | 0.00 | 0.408087E+11 | 0.00 | 0.00 | 0.354325E+09 | 0.00 | 0.00 | 0.00 | 0.78 |
August | 0.00 | 0.422618E+11 | 0.00 | 0.00 | 0.393210E+09 | 0.00 | 0.00 | 0.00 | 0.87 |
September | 0.00 | 0.344911E+11 | 0.00 | 0.00 | 0.247414E+10 | 0.00 | 0.00 | 0.00 | 0.74 |
October | 0.373032E+10 | 0.239673E+11 | 0.00 | 9039518.38 | 0.883807E+09 | 0.00 | 0.254046E+10 | 0.00 | 0.80 |
November | 0.136352E+11 | 0.818766E+10 | 0.00 | 15769754.79 | 0.193143E+10 | 6743035.66 | 0.473456E+10 | 0.00 | 0.86 |
December | 0.231180E+11 | 0.624121E+10 | 0.00 | 9639573.41 | 0.224888E+10 | 0.174486E+10 | 0.378591E+10 | 0.00 | 0.80 |
Annual Sum or Average | 0.104632E+12 | 0.252199E+12 | 0.00 | 90937061.69 | 0.152307E+11 | 0.912611E+10 | 0.305292E+11 | 0.00 | 0.83 |
Minimum of Months | 0.00 | 0.306757E+10 | 0.00 | 0.00 | 0.354325E+09 | 0.00 | 0.00 | 0.00 | 0.74 |
Maximum of Months | 0.252302E+11 | 0.422618E+11 | 0.00 | 19445947.16 | 0.247414E+10 | 0.423376E+10 | 0.669651E+10 | 0.00 | 0.94 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.183111E+10 | 0.245386E+09 | 0.00 | 11864.77 | 0.241619E+09 | 0.123660E+10 | 3041989.90 | 0.00 | 0.49 |
February | 0.117360E+10 | 0.327626E+09 | 0.00 | 66502.06 | 0.244964E+09 | 0.641439E+09 | 50311817.84 | 0.00 | 0.49 |
March | 0.176209E+10 | 0.635096E+09 | 0.00 | 386673.32 | 0.234798E+09 | 0.465609E+09 | 0.112095E+09 | 0.00 | 0.54 |
April | 0.471135E+09 | 0.117891E+10 | 0.00 | 1041533.46 | 0.269517E+09 | 25143941.66 | 0.194891E+09 | 0.00 | 0.53 |
May | 0.00 | 0.359194E+10 | 0.00 | 0.00 | 30511904.59 | 0.00 | 0.00 | 0.00 | 0.58 |
June | 0.00 | 0.410861E+10 | 0.00 | 0.00 | 42461284.70 | 0.00 | 0.00 | 0.00 | 0.64 |
July | 0.00 | 0.474599E+10 | 0.00 | 0.00 | 59230540.63 | 0.00 | 0.00 | 0.00 | 0.59 |
August | 0.00 | 0.452930E+10 | 0.00 | 0.00 | 70455495.43 | 0.00 | 0.00 | 0.00 | 0.60 |
September | 0.00 | 0.375852E+10 | 0.00 | 0.00 | 0.223847E+09 | 0.00 | 0.00 | 0.00 | 0.52 |
October | 0.319562E+09 | 0.239170E+10 | 0.00 | 661064.99 | 0.153271E+09 | 31116768.44 | 0.185453E+09 | 0.00 | 0.51 |
November | 0.123250E+10 | 0.727026E+09 | 1818333.09 | 457657.20 | 0.272673E+09 | 0.159551E+09 | 0.160382E+09 | 10931.29 | 0.51 |
December | 0.158086E+10 | 0.482982E+09 | 690280.00 | 32422.92 | 0.350252E+09 | 0.906473E+09 | 15907241.94 | 6769.50 | 0.48 |
Annual Sum or Average | 0.837086E+10 | 0.267231E+11 | 2508613.10 | 2657718.71 | 0.219360E+10 | 0.346593E+10 | 0.722083E+09 | 17700.79 | 0.54 |
Minimum of Months | 0.00 | 0.245386E+09 | 0.00 | 0.00 | 30511904.59 | 0.00 | 0.00 | 0.00 | 0.48 |
Maximum of Months | 0.183111E+10 | 0.474599E+10 | 1818333.09 | 1041533.46 | 0.350252E+09 | 0.123660E+10 | 0.194891E+09 | 10931.29 | 0.64 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.220070E+10 | 0.229999E+09 | 0.00 | 20301.30 | 0.229793E+09 | 0.644377E+09 | 27997054.12 | 0.00 | 0.72 |
February | 0.126130E+10 | 0.381792E+09 | 0.00 | 473851.63 | 0.186056E+09 | 0.347837E+09 | 0.150575E+09 | 0.00 | 0.74 |
March | 0.126629E+10 | 0.718730E+09 | 0.00 | 1506151.28 | 0.185187E+09 | 0.349029E+09 | 0.666463E+09 | 0.00 | 0.85 |
April | 0.320513E+09 | 0.124957E+10 | 0.00 | 1929030.60 | 0.254511E+09 | 754956.04 | 0.496557E+09 | 0.00 | 0.87 |
May | 0.00 | 0.318345E+10 | 0.00 | 0.00 | 74508679.95 | 0.00 | 0.00 | 0.00 | 0.81 |
June | 0.00 | 0.353843E+10 | 0.00 | 0.00 | 47856396.39 | 0.00 | 0.00 | 0.00 | 0.86 |
July | 0.00 | 0.410253E+10 | 0.00 | 0.00 | 92982426.84 | 0.00 | 0.00 | 0.00 | 0.79 |
August | 0.00 | 0.382656E+10 | 0.00 | 0.00 | 0.133146E+09 | 0.00 | 0.00 | 0.00 | 0.81 |
September | 0.00 | 0.313083E+10 | 0.00 | 0.00 | 0.371540E+09 | 0.00 | 0.00 | 0.00 | 0.71 |
October | 0.275215E+09 | 0.213553E+10 | 0.00 | 785251.21 | 0.219503E+09 | 18815957.39 | 0.210782E+09 | 0.00 | 0.74 |
November | 0.986448E+09 | 0.681488E+09 | 726853.91 | 973697.00 | 0.271696E+09 | 77038480.67 | 0.418024E+09 | 1072.61 | 0.75 |
December | 0.167700E+10 | 0.367456E+09 | 0.00 | 189254.92 | 0.377295E+09 | 0.575275E+09 | 0.105289E+09 | 0.00 | 0.70 |
Annual Sum or Average | 0.798747E+10 | 0.235464E+11 | 726853.91 | 5877537.95 | 0.244407E+10 | 0.201313E+10 | 0.207569E+10 | 1072.61 | 0.78 |
Minimum of Months | 0.00 | 0.229999E+09 | 0.00 | 0.00 | 47856396.39 | 0.00 | 0.00 | 0.00 | 0.70 |
Maximum of Months | 0.220070E+10 | 0.410253E+10 | 726853.91 | 1929030.60 | 0.377295E+09 | 0.644377E+09 | 0.666463E+09 | 1072.61 | 0.87 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.135076E+10 | 0.763226E+09 | 0.00 | 6505966.31 | 0.107559E+09 | 0.469198E+09 | 0.303598E+10 | 0.00 | 0.83 |
February | 0.902912E+09 | 0.113448E+10 | 0.00 | 4063175.49 | 82687640.29 | 0.239432E+09 | 0.165122E+10 | 0.00 | 0.83 |
March | 0.136577E+10 | 0.113193E+10 | 0.00 | 3858580.48 | 0.141492E+09 | 0.365112E+09 | 0.137896E+10 | 0.00 | 0.78 |
April | 0.434147E+09 | 0.152888E+10 | 0.00 | 2094572.18 | 0.243592E+09 | 1082906.27 | 0.425181E+09 | 0.00 | 0.67 |
May | 0.00 | 0.365821E+10 | 0.00 | 0.00 | 48096829.87 | 0.00 | 0.00 | 0.00 | 0.59 |
June | 0.00 | 0.390928E+10 | 0.00 | 0.00 | 63725494.73 | 0.00 | 0.00 | 0.00 | 0.61 |
July | 0.00 | 0.467070E+10 | 0.00 | 0.00 | 85219101.67 | 0.00 | 0.00 | 0.00 | 0.58 |
August | 0.00 | 0.501377E+10 | 0.00 | 0.00 | 84018541.34 | 0.00 | 0.00 | 0.00 | 0.67 |
September | 0.00 | 0.480881E+10 | 0.00 | 0.00 | 0.207659E+09 | 0.00 | 0.00 | 0.00 | 0.66 |
October | 0.268616E+09 | 0.389011E+10 | 0.00 | 2108303.02 | 50248671.60 | 2278804.64 | 0.504483E+09 | 0.00 | 0.83 |
November | 0.666568E+09 | 0.162102E+10 | 0.00 | 8565090.14 | 0.140976E+09 | 41357283.24 | 0.218695E+10 | 0.00 | 1.00 |
December | 0.121881E+10 | 0.127934E+10 | 0.00 | 7694039.50 | 0.156738E+09 | 0.408501E+09 | 0.230938E+10 | 0.00 | 0.89 |
Annual Sum or Average | 0.620759E+10 | 0.334098E+11 | 0.00 | 34889727.12 | 0.141201E+10 | 0.152696E+10 | 0.114922E+11 | 0.00 | 0.74 |
Minimum of Months | 0.00 | 0.763226E+09 | 0.00 | 0.00 | 48096829.87 | 0.00 | 0.00 | 0.00 | 0.58 |
Maximum of Months | 0.136577E+10 | 0.501377E+10 | 0.00 | 8565090.14 | 0.243592E+09 | 0.469198E+09 | 0.303598E+10 | 0.00 | 1.00 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.210959E+10 | 0.325277E+09 | 0.00 | 657022.93 | 0.236070E+09 | 0.690715E+09 | 0.439571E+09 | 0.00 | 0.82 |
February | 0.132196E+10 | 0.475022E+09 | 0.00 | 793539.86 | 0.220520E+09 | 0.339739E+09 | 0.343402E+09 | 0.00 | 0.86 |
March | 0.165154E+10 | 0.651738E+09 | 0.00 | 1955691.27 | 0.238774E+09 | 0.313553E+09 | 0.711390E+09 | 0.00 | 0.95 |
April | 0.445196E+09 | 0.136215E+10 | 0.00 | 1961813.40 | 0.255100E+09 | 0.00 | 0.372412E+09 | 0.00 | 0.94 |
May | 0.00 | 0.305549E+10 | 0.00 | 0.00 | 0.104547E+09 | 0.00 | 0.00 | 0.00 | 0.78 |
June | 0.00 | 0.343584E+10 | 0.00 | 0.00 | 50306318.87 | 0.00 | 0.00 | 0.00 | 0.85 |
July | 0.00 | 0.396974E+10 | 0.00 | 0.00 | 65470972.24 | 0.00 | 0.00 | 0.00 | 0.76 |
August | 0.00 | 0.408883E+10 | 0.00 | 0.00 | 74096054.40 | 0.00 | 0.00 | 0.00 | 0.85 |
September | 0.00 | 0.331572E+10 | 0.00 | 0.00 | 0.360533E+09 | 0.00 | 0.00 | 0.00 | 0.74 |
October | 0.376807E+09 | 0.225518E+10 | 0.00 | 799964.19 | 0.174197E+09 | 404287.07 | 0.208909E+09 | 0.00 | 0.80 |
November | 0.120170E+10 | 0.763951E+09 | 182171.58 | 1447707.70 | 0.288189E+09 | 73724356.00 | 0.464963E+09 | 29.17 | 0.88 |
December | 0.184365E+10 | 0.584264E+09 | 456263.45 | 749032.02 | 0.323868E+09 | 0.505036E+09 | 0.322557E+09 | 1080.66 | 0.82 |
Annual Sum or Average | 0.895044E+10 | 0.242832E+11 | 638435.04 | 8364771.37 | 0.239167E+10 | 0.192317E+10 | 0.286320E+10 | 1109.83 | 0.84 |
Minimum of Months | 0.00 | 0.325277E+09 | 0.00 | 0.00 | 50306318.87 | 0.00 | 0.00 | 0.00 | 0.74 |
Maximum of Months | 0.210959E+10 | 0.408883E+10 | 456263.45 | 1961813.40 | 0.360533E+09 | 0.690715E+09 | 0.711390E+09 | 1080.66 | 0.95 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 31429476.79 | 0.00 | 2803402.52 | 0.00 | 0.00 | 0.326287E+09 | 0.00 | 0.28 |
February | 0.00 | 48082917.25 | 0.00 | 4695206.26 | 0.00 | 0.00 | 0.176015E+09 | 0.00 | 0.29 |
March | 0.00 | 82820989.23 | 0.00 | 9105272.41 | 0.00 | 0.00 | 0.220120E+09 | 0.00 | 0.31 |
April | 0.00 | 0.158350E+09 | 0.00 | 5123326.77 | 0.00 | 0.00 | 50743652.47 | 0.00 | 0.29 |
May | 0.00 | 0.424098E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.29 |
June | 0.00 | 0.519202E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.30 |
July | 0.00 | 0.600567E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.28 |
August | 0.00 | 0.607476E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.31 |
September | 0.00 | 0.429767E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.29 |
October | 0.00 | 0.348158E+09 | 0.00 | 1609158.86 | 0.00 | 0.00 | 45221469.78 | 0.00 | 0.28 |
November | 0.00 | 0.123351E+09 | 0.00 | 7092807.00 | 0.00 | 0.00 | 0.125786E+09 | 0.00 | 0.28 |
December | 0.00 | 89983045.51 | 0.00 | 11681453.31 | 0.00 | 0.00 | 0.240930E+09 | 0.00 | 0.28 |
Annual Sum or Average | 0.00 | 0.346328E+10 | 0.00 | 42110627.12 | 0.00 | 0.00 | 0.118510E+10 | 0.00 | 0.29 |
Minimum of Months | 0.00 | 31429476.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.28 |
Maximum of Months | 0.00 | 0.607476E+09 | 0.00 | 11681453.31 | 0.00 | 0.00 | 0.326287E+09 | 0.00 | 0.31 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.295520E+09 | 0.00 | 19683092.21 | 0.00 | 0.00 | 0.327708E+10 | 0.00 | 0.28 |
February | 0.00 | 0.472766E+09 | 0.00 | 40125145.13 | 0.00 | 0.00 | 0.176852E+10 | 0.00 | 0.29 |
March | 0.00 | 0.825177E+09 | 0.00 | 81701453.37 | 0.00 | 0.00 | 0.220741E+10 | 0.00 | 0.31 |
April | 0.00 | 0.158432E+10 | 0.00 | 47760506.06 | 0.00 | 0.00 | 0.508938E+09 | 0.00 | 0.29 |
May | 0.00 | 0.420203E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.29 |
June | 0.00 | 0.517663E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.30 |
July | 0.00 | 0.599747E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.28 |
August | 0.00 | 0.608155E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.31 |
September | 0.00 | 0.424322E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.29 |
October | 0.00 | 0.346673E+10 | 0.00 | 14501401.61 | 0.00 | 0.00 | 0.452907E+09 | 0.00 | 0.28 |
November | 0.00 | 0.123008E+10 | 0.00 | 64145873.08 | 0.00 | 0.00 | 0.126222E+10 | 0.00 | 0.28 |
December | 0.00 | 0.898916E+09 | 0.00 | 0.105288E+09 | 0.00 | 0.00 | 0.241567E+10 | 0.00 | 0.28 |
Annual Sum or Average | 0.00 | 0.344744E+11 | 0.00 | 0.373205E+09 | 0.00 | 0.00 | 0.118927E+11 | 0.00 | 0.29 |
Minimum of Months | 0.00 | 0.295520E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.28 |
Maximum of Months | 0.00 | 0.608155E+10 | 0.00 | 0.105288E+09 | 0.00 | 0.00 | 0.327708E+10 | 0.00 | 0.31 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 49058172.88 | 29159867.51 | 0.00 | 1363965.35 | 0.00 | 0.00 | 0.279571E+09 | 0.00 | 0.28 |
February | 0.00 | 46978213.26 | 0.00 | 3638864.36 | 0.00 | 0.00 | 0.177714E+09 | 0.00 | 0.29 |
March | 0.00 | 82343906.09 | 0.00 | 7789818.20 | 0.00 | 0.00 | 0.221420E+09 | 0.00 | 0.31 |
April | 0.00 | 0.158180E+09 | 0.00 | 4703649.59 | 0.00 | 0.00 | 51087545.67 | 0.00 | 0.29 |
May | 0.00 | 0.421360E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.29 |
June | 0.00 | 0.518014E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.30 |
July | 0.00 | 0.599694E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.28 |
August | 0.00 | 0.609163E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.31 |
September | 0.00 | 0.425011E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.29 |
October | 0.00 | 0.346628E+09 | 0.00 | 1380014.05 | 0.00 | 0.00 | 45451045.70 | 0.00 | 0.28 |
November | 0.00 | 0.122766E+09 | 0.00 | 6140633.42 | 0.00 | 0.00 | 0.126783E+09 | 0.00 | 0.28 |
December | 0.00 | 89687893.28 | 0.00 | 9996689.22 | 0.00 | 0.00 | 0.242400E+09 | 0.00 | 0.28 |
Annual Sum or Average | 49058172.88 | 0.344899E+10 | 0.00 | 35013634.19 | 0.00 | 0.00 | 0.114443E+10 | 0.00 | 0.29 |
Minimum of Months | 0.00 | 29159867.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.28 |
Maximum of Months | 49058172.88 | 0.609163E+09 | 0.00 | 9996689.22 | 0.00 | 0.00 | 0.279571E+09 | 0.00 | 0.31 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.821623E+09 | 0.00 | 0.170014E+09 | 0.00 | 0.00 | 0.745243E+10 | 0.00 | 0.32 |
February | 0.00 | 0.111417E+10 | 0.00 | 0.237498E+09 | 0.00 | 0.00 | 0.403433E+10 | 0.00 | 0.32 |
March | 0.00 | 0.182482E+10 | 0.00 | 0.456690E+09 | 0.00 | 0.00 | 0.480747E+10 | 0.00 | 0.34 |
April | 0.00 | 0.308016E+10 | 0.00 | 0.245940E+09 | 0.00 | 0.00 | 0.108363E+10 | 0.00 | 0.32 |
May | 0.00 | 0.993571E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 |
June | 0.00 | 0.116293E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.34 |
July | 0.00 | 0.132330E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.31 |
August | 0.00 | 0.112743E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.35 |
September | 0.00 | 0.101519E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 |
October | 0.00 | 0.782763E+10 | 0.00 | 80971766.82 | 0.00 | 0.00 | 0.101269E+10 | 0.00 | 0.32 |
November | 0.00 | 0.271797E+10 | 0.00 | 0.351962E+09 | 0.00 | 0.00 | 0.268008E+10 | 0.00 | 0.32 |
December | 0.00 | 0.182194E+10 | 0.00 | 0.583357E+09 | 0.00 | 0.00 | 0.521963E+10 | 0.00 | 0.31 |
Annual Sum or Average | 0.00 | 0.754326E+11 | 0.00 | 0.212643E+10 | 0.00 | 0.00 | 0.262903E+11 | 0.00 | 0.33 |
Minimum of Months | 0.00 | 0.821623E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.31 |
Maximum of Months | 0.00 | 0.132330E+11 | 0.00 | 0.583357E+09 | 0.00 | 0.00 | 0.745243E+10 | 0.00 | 0.35 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 08:44:04
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.406922E+12 | 0.894391E+10 | 0.00 | 0.169506E+13 | 0.119733E+13 |
February | 0.435889E+12 | 0.683136E+10 | 0.00 | 0.116003E+13 | 0.177938E+13 |
March | 0.500396E+12 | 0.601800E+10 | 0.00 | 0.122340E+13 | 0.246821E+13 |
April | 0.557956E+12 | -671297890.0 | 0.00 | 0.339251E+12 | 0.345824E+13 |
May | 0.555487E+12 | -0.139623E+11 | 0.00 | -0.102835E+13 | 0.328673E+13 |
June | 0.552901E+12 | -0.112851E+11 | 0.00 | -0.117405E+13 | 0.374429E+13 |
July | 0.571189E+12 | -0.187200E+11 | 0.00 | -0.131044E+13 | 0.432373E+13 |
August | 0.526404E+12 | -0.180197E+11 | 0.00 | -0.130964E+13 | 0.483207E+13 |
September | 0.454243E+12 | -0.173948E+11 | 0.00 | -0.104181E+13 | 0.328018E+13 |
October | 0.456980E+12 | -0.113036E+11 | 0.00 | -0.370644E+12 | 0.331959E+13 |
November | 0.352364E+12 | 0.287348E+10 | 0.00 | 0.988839E+12 | 0.267164E+13 |
December | 0.364846E+12 | 0.710701E+10 | 0.00 | 0.148363E+13 | 0.270211E+13 |
Annual Sum or Average | 0.573558E+13 | -0.595830E+11 | 0.00 | 0.655282E+12 | 0.370635E+14 |
Minimum of Months | 0.352364E+12 | -0.187200E+11 | 0.00 | -0.131044E+13 | 0.119733E+13 |
Maximum of Months | 0.571189E+12 | 0.894391E+10 | 0.00 | 0.169506E+13 | 0.483207E+13 |