Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:43
Tabular Output Report in Format: HTML
Building: OfficeLarge
Environment: RUNPERIOD 1 ** Denver-Aurora-Buckley AFB CO USA TMY3 WMO#=724695
Simulation Timestamp: 2023-10-16 08:43:27
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 08:43:27
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 32313.20 | 697.60 | 697.60 |
Net Site Energy | 32313.20 | 697.60 | 697.60 |
Total Source Energy | 96753.49 | 2088.79 | 2088.79 |
Net Source Energy | 96753.49 | 2088.79 | 2088.79 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 46320.38 |
Net Conditioned Building Area | 46320.38 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 1866.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 2072.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 3926.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 697.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 14676.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 1934.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 2955.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 405.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 590.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5652.77 |
Humidification | 2374.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 883.27 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 813.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2280.17 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 29633.21 | 2680.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8816.21 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler | 0.00 | 1866.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 2072.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 3926.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 697.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 5334.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DataCenterPlugLoads | 9341.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 80.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 1848.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 5.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | General | 2955.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 405.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 590.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5652.77 |
Humidification | General | 2374.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 883.27 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2280.17 | |
Water Heater | 0.00 | 813.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 1866.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 2072.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 3926.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 697.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 14676.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 1934.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 2955.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 405.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 590.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5652.77 |
Humidification | Unassigned | 2374.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 883.27 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 0.00 | 813.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2280.17 |
Refrigeration | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 99.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 181.30 | 57.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.19 |
Other | 358.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 639.74 | 57.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.19 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 99.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 181.30 | 57.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.19 |
Other | 358.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 639.74 | 57.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.19 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 29633.209 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 29633.209 | 100.00 |
Total On-Site and Utility Electric Sources | 29633.209 | 100.00 |
Total Electricity End Uses | 29633.209 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 8816.21 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 8816.21 | 100.00 |
Total Water End Uses | 8816.21 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 60.50 |
Time Setpoint Not Met During Occupied Cooling | 577.17 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 5921.17 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2013
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICELARGE
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 5B
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_CO_DENVER
| Environment |ZoneCoolingSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |ZoneHeatingSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |ZoneElectricSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |SpaceGainsMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |PeakSpaceGainsMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |SpaceGainComponentsAtCoolingPeakMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |ComfortReportSimple55Monthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |OccupantComfortDataSummaryMonthly
| DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 | BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 |ChillerReportMonthly
| COOLSYS1 CHILLER1 | COOLSYS1 CHILLER2 |TowerReportMonthly
| CENTRAL TOWER | TOWERWATERSYS COOLTOWER 1 | TOWERWATERSYS COOLTOWER 2 |BoilerReportMonthly
| HEATSYS1 BOILER | CENTRAL BOILER |DXReportMonthly
| VAV_BOT WITH REHEAT COOLING COIL | VAV_MID WITH REHEAT COOLING COIL | VAV_TOP WITH REHEAT COOLING COIL | CAV_BAS COOLING COIL | AIRLOOP DATACENTER BASEMENT COOLING COIL | AIRLOOP DATACENTER BOT COOLING COIL | AIRLOOP DATACENTER MID COOLING COIL | AIRLOOP DATACENTER TOP COOLING COIL |WindowReportMonthly
| PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW |WindowEnergyReportMonthly
| PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW |WindowZoneSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |WindowEnergyZoneSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWHSYS1 WATER HEATER |DaylightingReportMonthly
| PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_4_DAYLCTRL |CoilReportMonthly
| VAV_BOT WITH REHEAT HEATING COIL | CORE_BOTTOM VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | VAV_MID WITH REHEAT HEATING COIL | CORE_MID VAV BOX REHEAT COIL | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | VAV_TOP WITH REHEAT HEATING COIL | CORE_TOP VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | CAV_BAS HEATING COIL | AIRLOOP DATACENTER BASEMENT HEATING COIL | AIRLOOP DATACENTER BOT HEATING COIL | AIRLOOP DATACENTER MID HEATING COIL | AIRLOOP DATACENTER TOP HEATING COIL | AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | AIRLOOP DATACENTER BOT_SUPPHEATCOIL | AIRLOOP DATACENTER MID_SUPPHEATCOIL | AIRLOOP DATACENTER TOP_SUPPHEATCOIL | VAV_BOT WITH REHEAT COOLING COIL | VAV_MID WITH REHEAT COOLING COIL | VAV_TOP WITH REHEAT COOLING COIL | CAV_BAS COOLING COIL | AIRLOOP DATACENTER BASEMENT COOLING COIL | AIRLOOP DATACENTER BOT COOLING COIL | AIRLOOP DATACENTER MID COOLING COIL | AIRLOOP DATACENTER TOP COOLING COIL |PlantLoopDemandReportMonthly
| HEATSYS1 | COOLSYS1_SUPPLY | COOLSYS1_DEMAND | SINGLE WATER PLANT LOOP | SWHSYS1 | TOWERWATERSYS |FanReportMonthly
| CAV_BAS FAN | VAV_BOT WITH REHEAT FAN | VAV_MID WITH REHEAT FAN | VAV_TOP WITH REHEAT FAN | AIRLOOP DATACENTER BASEMENT SUPPLY FAN | AIRLOOP DATACENTER BOT SUPPLY FAN | AIRLOOP DATACENTER MID SUPPLY FAN | AIRLOOP DATACENTER TOP SUPPLY FAN |PumpReportMonthly
| HEATSYS1 PUMP | COOLSYS1 PUMP SECONDARY | COOLSYS1 CHILLER1 PUMP | COOLSYS1 CHILLER2 PUMP | PLANT CIRC PUMP | SWHSYS1 PUMP | TOWERWATERSYS PUMP |CondLoopDemandReportMonthly
| HEATSYS1 | COOLSYS1_SUPPLY | COOLSYS1_DEMAND | SINGLE WATER PLANT LOOP | SWHSYS1 | TOWERWATERSYS |ZoneTemperatureOscillationReportMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |AirLoopSystemEnergyAndWaterUseMonthly
| VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | CAV_BAS | AIRLOOP DATACENTER BASEMENT | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |AirLoopSystemComponentLoadsMonthly
| VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | CAV_BAS | AIRLOOP DATACENTER BASEMENT | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |AirLoopSystemComponentEnergyUseMonthly
| VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | CAV_BAS | AIRLOOP DATACENTER BASEMENT | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |MechanicalVentilationLoadsMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 08:43:27
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:43 |
RunPeriod | RUNPERIOD 1 |
Weather File | Denver-Aurora-Buckley AFB CO USA TMY3 WMO#=724695 |
Latitude [deg] | 39.72 |
Longitude [deg] | -104.8 |
Elevation [m] | 1726.00 |
Time Zone | -7.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 12183.89 | 3655.17 | 2436.78 | 3655.17 | 2436.78 |
Above Ground Wall Area [m2] | 11589.54 | 3476.86 | 2317.91 | 3476.86 | 2317.91 |
Window Opening Area [m2] | 4635.80 | 1390.74 | 927.16 | 1390.74 | 927.16 |
Gross Window-Wall Ratio [%] | 38.05 | 38.05 | 38.05 | 38.05 | 38.05 |
Above Ground Window-Wall Ratio [%] | 40.00 | 40.00 | 40.00 | 40.00 | 40.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 12183.89 | 3655.17 | 2436.78 | 3655.17 | 2436.78 |
Above Ground Wall Area [m2] | 11589.54 | 3476.86 | 2317.91 | 3476.86 | 2317.91 |
Window Opening Area [m2] | 4635.80 | 1390.74 | 927.16 | 1390.74 | 927.16 |
Gross Window-Wall Ratio [%] | 38.05 | 38.05 | 38.05 | 38.05 | 38.05 |
Above Ground Window-Wall Ratio [%] | 40.00 | 40.00 | 40.00 | 40.00 | 40.00 |
Total | |
Gross Roof Area [m2] | 3563.11 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
BASEMENT | 2779.43 | Yes | Yes | 6779.02 | 1.00 | 0.00 | 397.05 | 0.00 | 0.00 | 10.2732 | 18.58 | 4.8418 |
CORE_BOTTOM | 2496.12 | Yes | Yes | 6849.35 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.2732 | 18.58 | 8.0697 |
CORE_MID | 2496.12 | Yes | Yes | 6849.35 | 10.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.2732 | 18.58 | 8.0696 |
CORE_TOP | 2496.12 | Yes | Yes | 6849.35 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.2732 | 18.58 | 8.0696 |
PERIMETER_BOT_ZN_3 | 313.41 | Yes | Yes | 860.00 | 1.00 | 200.61 | 0.00 | 115.90 | 115.90 | 10.2732 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_2 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 77.26 | 77.26 | 10.2732 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_1 | 313.42 | Yes | Yes | 860.02 | 1.00 | 200.61 | 0.00 | 115.90 | 115.90 | 10.2732 | 18.58 | 8.0699 |
PERIMETER_BOT_ZN_4 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 77.26 | 77.26 | 10.2732 | 18.58 | 8.0699 |
PERIMETER_MID_ZN_3 | 313.41 | Yes | Yes | 860.00 | 10.00 | 200.61 | 0.00 | 115.90 | 115.90 | 10.2732 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_2 | 201.98 | Yes | Yes | 554.22 | 10.00 | 133.74 | 0.00 | 77.26 | 77.26 | 10.2732 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_1 | 313.42 | Yes | Yes | 860.02 | 10.00 | 200.61 | 0.00 | 115.90 | 115.90 | 10.2732 | 18.58 | 8.0699 |
PERIMETER_MID_ZN_4 | 201.98 | Yes | Yes | 554.22 | 10.00 | 133.74 | 0.00 | 77.26 | 77.26 | 10.2732 | 18.58 | 8.0699 |
PERIMETER_TOP_ZN_3 | 313.41 | Yes | Yes | 860.00 | 1.00 | 200.61 | 0.00 | 115.90 | 115.90 | 10.2732 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_2 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 77.26 | 77.26 | 10.2732 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_1 | 313.42 | Yes | Yes | 860.02 | 1.00 | 200.61 | 0.00 | 115.90 | 115.90 | 10.2732 | 18.58 | 8.0699 |
PERIMETER_TOP_ZN_4 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 77.26 | 77.26 | 10.2732 | 18.58 | 8.0699 |
GROUNDFLOOR_PLENUM | 3563.11 | Yes | No | 4344.14 | 1.00 | 297.11 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
MIDFLOOR_PLENUM | 3563.11 | Yes | No | 4344.14 | 10.00 | 297.11 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
TOPFLOOR_PLENUM | 3563.11 | Yes | No | 4344.14 | 1.00 | 297.11 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
DATACENTER_BOT_ZN_6 | 36.20 | Yes | Yes | 99.34 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.8735 | 18.58 | 215.2992 |
DATACENTER_MID_ZN_6 | 36.20 | Yes | Yes | 99.34 | 10.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.8735 | 18.58 | 215.2992 |
DATACENTER_TOP_ZN_6 | 36.20 | Yes | Yes | 99.34 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.8735 | 18.58 | 215.2992 |
DATACENTER_BASEMENT_ZN_6 | 783.68 | Yes | Yes | 1911.37 | 1.00 | 0.00 | 197.31 | 0.00 | 0.00 | 10.2732 | 18.58 | 484.4232 |
Total | 46320.38 | 126016.35 | 8024.24 | 594.36 | 4635.80 | 4635.80 | 10.3445 | 18.58 | 17.8789 | |||
Conditioned Total | 46320.38 | 126016.35 | 8024.24 | 594.36 | 4635.80 | 4635.80 | 10.3445 | 18.58 | 17.8789 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 42757.27 | 52129.67 | 3565.29 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
BASEMENT | 2779.43 | Yes | Yes | 1.00 | BASEMENT | GENERAL | BASEMENT | 10.2732 | 18.58 | 4.8418 | |
CORE_BOTTOM | 2496.12 | Yes | Yes | 1.00 | CORE_BOTTOM | GENERAL | CORE_BOTTOM | 10.2732 | 18.58 | 8.0697 | |
CORE_MID | 2496.12 | Yes | Yes | 10.00 | CORE_MID | GENERAL | CORE_MID | 10.2732 | 18.58 | 8.0696 | |
CORE_TOP | 2496.12 | Yes | Yes | 1.00 | CORE_TOP | GENERAL | CORE_TOP | 10.2732 | 18.58 | 8.0696 | |
PERIMETER_BOT_ZN_3 | 313.41 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_3 | GENERAL | PERIMETER_BOT_ZN_3 | 10.2732 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_2 | 201.98 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_2 | GENERAL | PERIMETER_BOT_ZN_2 | 10.2732 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_1 | 313.42 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_1 | GENERAL | PERIMETER_BOT_ZN_1 | 10.2732 | 18.58 | 8.0699 | |
PERIMETER_BOT_ZN_4 | 201.98 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_4 | GENERAL | PERIMETER_BOT_ZN_4 | 10.2732 | 18.58 | 8.0699 | |
PERIMETER_MID_ZN_3 | 313.41 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_3 | GENERAL | PERIMETER_MID_ZN_3 | 10.2732 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_2 | 201.98 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_2 | GENERAL | PERIMETER_MID_ZN_2 | 10.2732 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_1 | 313.42 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_1 | GENERAL | PERIMETER_MID_ZN_1 | 10.2732 | 18.58 | 8.0699 | |
PERIMETER_MID_ZN_4 | 201.98 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_4 | GENERAL | PERIMETER_MID_ZN_4 | 10.2732 | 18.58 | 8.0699 | |
PERIMETER_TOP_ZN_3 | 313.41 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_3 | GENERAL | PERIMETER_TOP_ZN_3 | 10.2732 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_2 | 201.98 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_2 | GENERAL | PERIMETER_TOP_ZN_2 | 10.2732 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_1 | 313.42 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_1 | GENERAL | PERIMETER_TOP_ZN_1 | 10.2732 | 18.58 | 8.0699 | |
PERIMETER_TOP_ZN_4 | 201.98 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_4 | GENERAL | PERIMETER_TOP_ZN_4 | 10.2732 | 18.58 | 8.0699 | |
GROUNDFLOOR_PLENUM | 3563.11 | Yes | No | 1.00 | GROUNDFLOOR_PLENUM | GENERAL | GROUNDFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
MIDFLOOR_PLENUM | 3563.11 | Yes | No | 10.00 | MIDFLOOR_PLENUM | GENERAL | MIDFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
TOPFLOOR_PLENUM | 3563.11 | Yes | No | 1.00 | TOPFLOOR_PLENUM | GENERAL | TOPFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
DATACENTER_BOT_ZN_6 | 36.20 | Yes | Yes | 1.00 | DATACENTER_BOT_ZN_6 | GENERAL | DATACENTER_BOT_ZN_6 | 17.8735 | 18.58 | 215.2992 | |
DATACENTER_MID_ZN_6 | 36.20 | Yes | Yes | 10.00 | DATACENTER_MID_ZN_6 | GENERAL | DATACENTER_MID_ZN_6 | 17.8735 | 18.58 | 215.2992 | |
DATACENTER_TOP_ZN_6 | 36.20 | Yes | Yes | 1.00 | DATACENTER_TOP_ZN_6 | GENERAL | DATACENTER_TOP_ZN_6 | 17.8735 | 18.58 | 215.2992 | |
DATACENTER_BASEMENT_ZN_6 | 783.68 | Yes | Yes | 1.00 | DATACENTER_BASEMENT_ZN_6 | GENERAL | DATACENTER_BASEMENT_ZN_6 | 10.2732 | 18.58 | 484.4232 | |
Total | 46320.38 | 10.3445 | 9.29 | 17.8789 | |||||||
Conditioned Total | 46320.38 | 10.3445 | 9.29 | 17.8789 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 42757.27 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 46320.38 | 46320.38 | 0.00 | 42757.27 | 3.1788 | 60.38 | 10.8345 |
Total | 46320.38 | 46320.38 | 0.00 | 42757.27 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:43:27
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 16-AUG-15:09 | 23-DEC-07:10 | - | - | - | - | - | - | - | - | - | - | 26-JUN-15:20 |
Heating | 0.00 | 1508880.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 462978.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 332294.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 778371.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 84450.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 307376.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 46542.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 83748.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 100000.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 30301.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 2195763.20 | 1539182.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler | 0.00 | 1508880.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 462978.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 332294.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 305206.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DataCenterPlugLoads | 473165.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 5015.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 79171.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 263.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | General | 307376.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 46542.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 83748.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 100000.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Water Heater | 0.00 | 30301.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:43:27
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 2023.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 6562.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 12434.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 2210.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 46480.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 6127.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 9359.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 1283.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 1870.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 7519.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 882.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 93848.37 | 2905.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 43.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 141.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 268.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 47.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1003.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 132.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 202.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 27.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 40.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 162.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 19.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 2026.07 | 62.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 43.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 141.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 268.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 47.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1003.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 132.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 202.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 27.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 40.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 162.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 19.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 2026.07 | 62.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:43:27
AirTerminal:SingleDuct:ConstantVolume:NoReheatDesign Size Maximum Air Flow Rate [m3/s] | |
BASEMENT DIRECT AIR | 7.28 |
DATACENTER_BOT_ZN_6 DIRECT AIR | 0.622682 |
DATACENTER_MID_ZN_6 DIRECT AIR | 5.98 |
DATACENTER_TOP_ZN_6 DIRECT AIR | 0.609545 |
DATACENTER_BASEMENT_ZN_6 DIRECT AIR | 26.41 |
Design Size Maximum Air Flow Rate [m3/s] | Design Size Constant Minimum Air Flow Fraction | User-Specified Constant Minimum Air Flow Fraction | Design Size Minimum Air Flow Rate [m3/s] | Design Size Maximum Flow Fraction during Reheat [] | User-Specified Maximum Flow Fraction during Reheat [] | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | Design Size Maximum Reheat Water Flow Rate [m3/s] | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | |
CORE_BOTTOM VAV BOX COMPONENT | 7.60 | 0.250360 | 0.272000 | 2.07 | 0.667626 | 0.500000 | 0.001522 | 0.000148 | 2.07 | 12.80 | 0.008000 |
CORE_MID VAV BOX COMPONENT | 71.73 | 0.265169 | 0.284000 | 20.37 | 0.707118 | 0.500000 | 0.001437 | 0.003965 | 20.37 | 12.80 | 0.008000 |
CORE_TOP VAV BOX COMPONENT | 7.04 | 0.270321 | 0.297000 | 2.09 | 0.720856 | 0.500000 | 0.001409 | 0.000843 | 3.53 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | 1.31 | 0.182383 | 0.200000 | 0.261888 | 0.486356 | 0.500000 | 0.002089 | 0.000143 | 0.599388 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | 1.71 | 0.090132 | 0.200000 | 0.341510 | 0.300000 | 0.500000 | 0.004227 | 0.000100 | 0.420646 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | 1.87 | 0.127637 | 0.200000 | 0.374227 | 0.340365 | 0.500000 | 0.002985 | 0.000162 | 0.680112 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | 2.13 | 0.072101 | 0.200000 | 0.426916 | 0.300000 | 0.500000 | 0.005284 | 0.000086 | 0.426916 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_3 VAV BOX COMPONENT | 12.45 | 0.191826 | 0.205000 | 2.55 | 0.511536 | 0.500000 | 0.001986 | 0.002208 | 9.28 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_2 VAV BOX COMPONENT | 18.19 | 0.084591 | 0.200000 | 3.64 | 0.300000 | 0.500000 | 0.004504 | 0.001485 | 6.24 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_1 VAV BOX COMPONENT | 18.56 | 0.128687 | 0.200000 | 3.71 | 0.343166 | 0.500000 | 0.002961 | 0.002237 | 9.40 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_4 VAV BOX COMPONENT | 20.01 | 0.076920 | 0.200000 | 4.00 | 0.300000 | 0.500000 | 0.004953 | 0.001429 | 6.01 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | 1.41 | 0.169837 | 0.200000 | 0.281235 | 0.452898 | 0.500000 | 0.002243 | 0.000280 | 1.18 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | 1.82 | 0.084434 | 0.200000 | 0.364557 | 0.300000 | 0.500000 | 0.004512 | 0.000187 | 0.786800 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | 2.00 | 0.119151 | 0.200000 | 0.400879 | 0.317736 | 0.500000 | 0.003198 | 0.000284 | 1.19 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | 2.11 | 0.072970 | 0.200000 | 0.421829 | 0.300000 | 0.500000 | 0.005221 | 0.000183 | 0.770418 | 12.80 | 0.008000 |
Design Size Rated Capacity [W] | Design Size Maximum Water Flow Rate [m3/s] | Design Size U-Factor Times Area Value [W/K] | |
CORE_BOTTOM VAV BOX REHEAT COIL | 16889.04 | 0.000148 | 340.47 |
CORE_MID VAV BOX REHEAT COIL | 453273.89 | 0.003965 | 11044.68 |
CORE_TOP VAV BOX REHEAT COIL | 96322.26 | 0.000843 | 2541.78 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | 16316.18 | 0.000143 | 430.36 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | 11448.46 | 0.000100 | 301.94 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | 18509.23 | 0.000162 | 488.15 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | 9843.95 | 0.000086 | 242.83 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | 252351.22 | 0.002208 | 6653.47 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | 169747.39 | 0.001485 | 4475.42 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | 255715.28 | 0.002237 | 6742.11 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | 163334.33 | 0.001429 | 4306.43 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | 32045.87 | 0.000280 | 844.80 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | 21392.44 | 0.000187 | 563.94 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | 32413.93 | 0.000284 | 854.50 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | 20947.33 | 0.000183 | 552.21 |
VAV_BOT WITH REHEAT HEATING COIL | 77297.82 | 0.000676 | 1239.36 |
VAV_MID WITH REHEAT HEATING COIL | 685347.74 | 0.005996 | 11052.28 |
VAV_TOP WITH REHEAT HEATING COIL | 66608.52 | 0.000583 | 1088.97 |
CAV_BAS HEATING COIL | 307268.00 | 0.002688 | 6711.49 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT | 7.31 | 3.47 | 14.62 | 3.47 | 12.55 | 12.55 | 0.300000 | 0.276466 | 12.55 |
VAV_MID WITH REHEAT | 70.47 | 34.28 | 140.94 | 45.87 | 117.72 | 117.72 | 0.300000 | 0.389655 | 117.72 |
VAV_TOP WITH REHEAT | 7.19 | 3.56 | 14.38 | 7.46 | 13.11 | 13.11 | 0.300000 | 0.569399 | 13.11 |
CAV_BAS | 7.28 | 7.28 | 7.28 | 7.28 | 7.28 | 7.28 | 1.00 | 1.00 | 7.28 |
AIRLOOP DATACENTER BASEMENT | 26.41 | 26.41 | 26.41 | 26.41 | 26.41 | 26.41 | 1.00 | 0.999992 | 26.41 |
AIRLOOP DATACENTER BOT | 0.622682 | 0.622682 | 0.622682 | 0.622682 | 0.622682 | 0.622682 | 1.00 | 1.00 | 0.622682 |
AIRLOOP DATACENTER MID | 5.98 | 5.98 | 5.98 | 5.98 | 5.98 | 5.98 | 1.00 | 1.00 | 5.98 |
AIRLOOP DATACENTER TOP | 0.609545 | 0.609545 | 0.609545 | 0.609545 | 0.609545 | 0.609545 | 1.00 | 1.00 | 0.609545 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT_OA_CONTROLLER | 12.55 | |
VAV_MID WITH REHEAT_OA_CONTROLLER | 117.72 | |
VAV_TOP WITH REHEAT_OA_CONTROLLER | 13.11 | |
CAV_BAS_OA_CONTROLLER | 7.28 | 1.20 |
AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER | 26.41 | 0.338393 |
AIRLOOP DATACENTER BOT_OA_CONTROLLER | 0.622682 | 0.015632 |
AIRLOOP DATACENTER MID_OA_CONTROLLER | 5.98 | 0.156323 |
AIRLOOP DATACENTER TOP_OA_CONTROLLER | 0.609545 | 0.015632 |
Design Size Design Inlet Air Temperature [C] | Design Size Design Inlet Water Temperature [C] | Design Size Design Outlet Air Temperature [C] | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | Design Size Design Coil Load [W] | Design Size Design Water Flow Rate [m3/s] | Design Size Design Air Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT COOLING COIL | 26.03 | 6.67 | 10.64 | 0.006927 | 0.006927 | 192210.79 | 0.008177 | 12.55 |
VAV_MID WITH REHEAT COOLING COIL | 26.21 | 6.67 | 10.64 | 0.006904 | 0.006904 | 1823099.00 | 0.077559 | 117.72 |
VAV_TOP WITH REHEAT COOLING COIL | 25.92 | 6.67 | 10.64 | 0.006921 | 0.006921 | 199215.66 | 0.008475 | 13.11 |
CAV_BAS COOLING COIL | 25.70 | 6.67 | 11.11 | 0.007099 | 0.007099 | 105752.34 | 0.004499 | 7.28 |
Design Size Maximum Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT FAN | 12.55 |
VAV_MID WITH REHEAT FAN | 117.72 |
VAV_TOP WITH REHEAT FAN | 13.11 |
Maximum Actuated Flow [m3/s] | Controller Convergence Tolerance | |
VAV_BOT WITH REHEAT_COOLC_CONTROLLER | 0.008177 | 0.000058 |
VAV_BOT WITH REHEAT_HEATC_CONTROLLER | 0.000676 | |
VAV_MID WITH REHEAT_COOLC_CONTROLLER | 0.077559 | 0.000006 |
VAV_MID WITH REHEAT_HEATC_CONTROLLER | 0.005996 | |
VAV_TOP WITH REHEAT_COOLC_CONTROLLER | 0.008475 | 0.000056 |
VAV_TOP WITH REHEAT_HEATC_CONTROLLER | 0.000583 | |
CAV_BAS_COOLC_CONTROLLER | 0.004499 | 0.000106 |
CAV_BAS_HEATC_CONTROLLER | 0.002688 |
Design Size Maximum Flow Rate [m3/s] | |
CAV_BAS FAN | 7.28 |
Design Size Rated Air Flow Rate [m3/s] | Design Size Rated Total Cooling Capacity [W] | Design Size Rated Sensible Cooling Capacity [W] | Design Size Rated Water Flow Rate [m3/s] | |
AIRLOOP DATACENTER BASEMENT COOLING COIL | 26.41 | 479130.06 | 251095.38 | 0.011734 |
AIRLOOP DATACENTER BOT COOLING COIL | 0.622682 | 10972.23 | 5809.80 | 0.000269 |
AIRLOOP DATACENTER MID COOLING COIL | 5.98 | 105453.92 | 55828.60 | 0.002583 |
AIRLOOP DATACENTER TOP COOLING COIL | 0.609545 | 10747.41 | 5689.23 | 0.000263 |
Supply Air Flow Rate [m3/s] | Supply Air Flow Rate During Heating Operation [m3/s] | Supply Air Flow Rate During Cooling Operation [m3/s] | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | Nominal Heating Capacity [W] | Nominal Cooling Capacity [W] | Supplemental Heating Coil Nominal Capacity [W] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | 26.41 | 26.41 | 26.41 | 26.41 | 479130.06 | 479130.06 | 19243.92 | 1.00 |
AIRLOOP DATACENTER BOT DXAC HEAT PUMP | 0.622682 | 0.622682 | 0.622682 | 0.622682 | 10972.23 | 10972.23 | 888.99 | 1.00 |
AIRLOOP DATACENTER MID DXAC HEAT PUMP | 5.98 | 5.98 | 5.98 | 5.98 | 105453.92 | 105453.92 | 8889.90 | 1.00 |
AIRLOOP DATACENTER TOP DXAC HEAT PUMP | 0.609545 | 0.609545 | 0.609545 | 0.609545 | 10747.41 | 10747.41 | 888.99 | 1.00 |
Design Size Maximum Flow Rate [m3/s] | |
AIRLOOP DATACENTER BASEMENT SUPPLY FAN | 26.41 |
AIRLOOP DATACENTER BOT SUPPLY FAN | 0.622682 |
AIRLOOP DATACENTER MID SUPPLY FAN | 5.98 |
AIRLOOP DATACENTER TOP SUPPLY FAN | 0.609545 |
Design Size Rated Air Flow Rate [m3/s] | Design Size Rated Heating Capacity [W] | Design Size Rated Water Flow Rate [m3/s] | |
AIRLOOP DATACENTER BASEMENT HEATING COIL | 26.41 | 479130.06 | 0.011734 |
AIRLOOP DATACENTER BOT HEATING COIL | 0.622682 | 10972.23 | 0.000269 |
AIRLOOP DATACENTER MID HEATING COIL | 5.98 | 105453.92 | 0.002583 |
AIRLOOP DATACENTER TOP HEATING COIL | 0.609545 | 10747.41 | 0.000263 |
Design Size Nominal Capacity [W] | |
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | 19243.92 |
AIRLOOP DATACENTER BOT_SUPPHEATCOIL | 888.99 |
AIRLOOP DATACENTER MID_SUPPHEATCOIL | 8889.90 |
AIRLOOP DATACENTER TOP_SUPPHEATCOIL | 888.99 |
Design Size Nominal Capacity Volume [m3/s] | User-Specified Nominal Capacity Volume [m3/s] | Design Size Rated Power [W] | User-Specified Rated Power [W] | |
DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | 0.000176 | 0.000037 | 96450.70 | 100000.00 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | Design Minimum Flow Rate [m3/s] | |
COOLSYS1 PUMP SECONDARY | 0.098710 | 16116.32 | |
HEATSYS1 PUMP | 0.023683 | 7132.18 | 0.000000 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
COOLSYS1_DEMAND | 0.098710 | 11.85 |
HEATSYS1 | 0.023683 | 2.84 |
COOLSYS1_SUPPLY | 0.098710 | 11.85 |
SINGLE WATER PLANT LOOP | 0.014848 | 1.78 |
SWHSYS1 | 0.000440 | 0.052800 |
Loop Supply Side Design Fluid Flow Rate [m3/s] | Loop Demand Side Design Fluid Flow Rate [m3/s] | Heat Exchanger U-Factor Times Area Value [W/C] | Loop-to-loop Temperature Difference Used to Size Heat Exchanger U-Factor Times Area Value [C] | |
BYPASS HEAT EXCHANGER | 0.098710 | 0.098710 | 414335.32 | 5.60 |
Design Size Nominal Capacity [W] | User-Specified Nominal Capacity [W] | Design Size Design Water Flow Rate [m3/s] | |
HEATSYS1 BOILER | 2707072.89 | 2707072.89 | 0.023683 |
CENTRAL BOILER | 611624.18 | 597767.97 | 0.014848 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
COOLSYS1 CHILLER1 PUMP | 0.049355 | 5578.94 |
COOLSYS1 CHILLER2 PUMP | 0.049355 | 5578.94 |
PLANT CIRC PUMP | 0.014848 | 3787.07 |
SWHSYS1 PUMP | 0.000440 | 56.21 |
Design Size Reference Chilled Water Flow Rate [m3/s] | User-Specified Reference Chilled Water Flow Rate [m3/s] | Design Size Reference Capacity [W] | User-Specified Reference Capacity [W] | Design Size Reference Condenser Water Flow Rate [m3/s] | |
COOLSYS1 CHILLER1 | 0.098710 | 0.050135 | 1181368.69 | 1186966.84 | 0.058739 |
COOLSYS1 CHILLER2 | 0.098710 | 0.050135 | 1181368.69 | 1186966.84 | 0.058739 |
Design Water Flow Rate [m3/s] | Air Flow Rate at High Fan Speed [m3/s] | Fluid cooler UA value at high fan speed based on nominal capacity input [W/K] | Air Flow Rate at Low Fan Speed [m3/s] | Fan Power at Low Fan Speed [W] | U-factor Times Area Value at Low Fan Speed [W/C] | |
CENTRAL TOWER | 0.014848 | 139666.47 | 54366.00 | 69833.23 | 7879.72 | 20886.87 |
Use Side Design Flow Rate [m3/s] | |
SWHSYS1 WATER HEATER | 0.000440 |
Maximum Loop Flow Rate [m3/s] | Condenser Loop Volume [m3] | |
TOWERWATERSYS | 0.117477 | 14.10 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
TOWERWATERSYS PUMP | 0.117477 | 29084.75 |
Design Air Flow Rate [m3/s] | Nominal Capacity [W] | Air Flow Rate in free convection regime [m3/s] | Tower capacity in free convection regime at design conditions [W] | |
TOWERWATERSYS COOLTOWER 1 | 55.93 | 1410050.16 | 11.19 | 176256.27 |
TOWERWATERSYS COOLTOWER 2 | 55.93 | 1410050.16 | 11.19 | 176256.27 |
Design Water Flow Rate [m3/s] Equipment # 47 | |
WSHPPLANT OPERATION SCHEME | 0.061010 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:43:27
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
PERIMETER_BOT_ZN_3_WALL_NORTH | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | |
PERIMETER_BOT_ZN_2_WALL_EAST | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | |
PERIMETER_BOT_ZN_1_WALL_SOUTH | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | |
PERIMETER_BOT_ZN_4_WALL_WEST | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | |
PERIMETER_MID_ZN_3_WALL_NORTH | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_MID_ZN_2_WALL_EAST | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_MID_ZN_1_WALL_SOUTH | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_MID_ZN_4_WALL_WEST | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | |
PERIMETER_TOP_ZN_3_WALL_NORTH | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_TOP_ZN_2_WALL_EAST | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_TOP_ZN_1_WALL_SOUTH | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_TOP_ZN_4_WALL_WEST | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 08:43:27
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 08:43:27
VersionVersion ID | |
1 | 22.1.0 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 7.10 | 3.00 | -1.00 | 0.80 | -0.20 | 4.80 | 6.10 | 13.70 | 22.20 | 22.70 | 21.70 | 18.50 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Denver-Aurora-Buckley AFB CO USA TMY3 WMO#=724695 | 39.72 | -104.75 | -7.00 | 1726.00 | 82237 | 0.9774 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 9.95 | 23.70 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | OfficeLarge | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 23 | 221 | 36 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | BASEMENT | 0.0 | 0.00 | 0.00 | 0.00 | 44.59 | 24.37 | -1.22 | 1 | 1 | 1 | 16.08 | 73.11 | 0.00 | 48.74 | -2.44 | 0.00 | 2.44 | 6779.02 | TARP | TARP | 2779.43 | 0.00 | 0.00 | 0.00 | 9 | 0 | 0 | Yes |
2 | CORE_BOTTOM | 0.0 | 0.00 | 0.00 | 0.00 | 37.01 | 24.37 | 1.37 | 1 | 1 | 1 | 5.49 | 68.53 | 4.57 | 44.17 | 0.00 | 2.74 | 2.74 | 6849.35 | TARP | TARP | 2496.12 | 0.00 | 0.00 | 0.00 | 7 | 0 | 0 | Yes |
3 | CORE_MID | 0.0 | 0.00 | 0.00 | 0.00 | 37.01 | 24.37 | 18.14 | 1 | 10 | 1 | 5.49 | 68.53 | 4.57 | 44.17 | 16.77 | 19.51 | 2.74 | 6849.35 | TARP | TARP | 2496.12 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
4 | CORE_TOP | 0.0 | 0.00 | 0.00 | 0.00 | 37.01 | 24.37 | 34.91 | 1 | 1 | 1 | 5.49 | 68.53 | 4.57 | 44.17 | 33.54 | 36.28 | 2.74 | 6849.35 | TARP | TARP | 2496.12 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
5 | PERIMETER_BOT_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 46.54 | 1.37 | 1 | 1 | 1 | 0.00 | 73.11 | 44.17 | 48.74 | 0.00 | 2.74 | 2.74 | 860.00 | TARP | TARP | 313.41 | 200.61 | 76.91 | 115.90 | 8 | 9 | 0 | Yes |
6 | PERIMETER_BOT_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 70.95 | 24.37 | 1.37 | 1 | 1 | 1 | 68.53 | 73.11 | 0.00 | 48.74 | 0.00 | 2.74 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 52.57 | 77.26 | 6 | 5 | 0 | Yes |
7 | PERIMETER_BOT_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 2.20 | 1.37 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 4.57 | 0.00 | 2.74 | 2.74 | 860.02 | TARP | TARP | 313.42 | 200.61 | 76.91 | 115.90 | 8 | 9 | 0 | Yes |
8 | PERIMETER_BOT_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.16 | 24.37 | 1.37 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 48.74 | 0.00 | 2.74 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 52.57 | 77.26 | 6 | 5 | 0 | Yes |
9 | PERIMETER_MID_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 46.54 | 18.14 | 1 | 10 | 1 | 0.00 | 73.11 | 44.17 | 48.74 | 16.77 | 19.51 | 2.74 | 860.00 | TARP | TARP | 313.41 | 200.61 | 84.71 | 115.90 | 7 | 1 | 0 | Yes |
10 | PERIMETER_MID_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 70.95 | 24.37 | 18.14 | 1 | 10 | 1 | 68.53 | 73.11 | 0.00 | 48.74 | 16.77 | 19.51 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 56.47 | 77.26 | 6 | 1 | 0 | Yes |
11 | PERIMETER_MID_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 2.20 | 18.14 | 1 | 10 | 1 | 0.00 | 73.11 | 0.00 | 4.57 | 16.77 | 19.51 | 2.74 | 860.02 | TARP | TARP | 313.42 | 200.61 | 84.71 | 115.90 | 7 | 1 | 0 | Yes |
12 | PERIMETER_MID_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.16 | 24.37 | 18.14 | 1 | 10 | 1 | 0.00 | 4.57 | 0.00 | 48.74 | 16.77 | 19.51 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 56.47 | 77.26 | 6 | 1 | 0 | Yes |
13 | PERIMETER_TOP_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 46.54 | 34.91 | 1 | 1 | 1 | 0.00 | 73.11 | 44.17 | 48.74 | 33.54 | 36.28 | 2.74 | 860.00 | TARP | TARP | 313.41 | 200.61 | 84.71 | 115.90 | 7 | 1 | 0 | Yes |
14 | PERIMETER_TOP_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 70.95 | 24.37 | 34.91 | 1 | 1 | 1 | 68.53 | 73.11 | 0.00 | 48.74 | 33.54 | 36.28 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 56.47 | 77.26 | 6 | 1 | 0 | Yes |
15 | PERIMETER_TOP_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 2.20 | 34.91 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 4.57 | 33.54 | 36.28 | 2.74 | 860.02 | TARP | TARP | 313.42 | 200.61 | 84.71 | 115.90 | 7 | 1 | 0 | Yes |
16 | PERIMETER_TOP_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.16 | 24.37 | 34.91 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 48.74 | 33.54 | 36.28 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 56.47 | 77.26 | 6 | 1 | 0 | Yes |
17 | GROUNDFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 24.37 | 3.35 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 48.74 | 2.74 | 3.96 | 1.22 | 4344.14 | TARP | TARP | 3563.11 | 297.11 | 297.11 | 0.00 | 11 | 0 | 0 | No |
18 | MIDFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 24.37 | 20.12 | 1 | 10 | 1 | 0.00 | 73.11 | 0.00 | 48.74 | 19.51 | 20.73 | 1.22 | 4344.14 | TARP | TARP | 3563.11 | 297.11 | 297.11 | 0.00 | 11 | 0 | 0 | No |
19 | TOPFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 24.37 | 36.89 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 48.74 | 36.28 | 37.50 | 1.22 | 4344.14 | TARP | TARP | 3563.11 | 297.11 | 297.11 | 0.00 | 11 | 0 | 0 | No |
20 | DATACENTER_BOT_ZN_6 | 0.0 | 5.49 | 44.17 | 0.00 | 5.03 | 24.37 | 1.37 | 1 | 1 | 1 | 4.57 | 5.49 | 4.57 | 44.17 | 0.00 | 2.74 | 2.74 | 99.34 | TARP | TARP | 36.20 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
21 | DATACENTER_MID_ZN_6 | 0.0 | 4.57 | 4.57 | 16.77 | 5.03 | 24.37 | 18.14 | 1 | 10 | 1 | 4.57 | 5.49 | 4.57 | 44.17 | 16.77 | 19.51 | 2.74 | 99.34 | TARP | TARP | 36.20 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
22 | DATACENTER_TOP_ZN_6 | 0.0 | 4.57 | 4.57 | 33.54 | 5.03 | 24.37 | 34.91 | 1 | 1 | 1 | 4.57 | 5.49 | 4.57 | 44.17 | 33.54 | 36.28 | 2.74 | 99.34 | TARP | TARP | 36.20 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
23 | DATACENTER_BASEMENT_ZN_6 | 0.0 | 16.08 | 0.00 | -2.44 | 8.04 | 24.37 | -1.22 | 1 | 1 | 1 | 0.00 | 16.08 | 0.00 | 48.74 | -2.44 | 0.00 | 2.44 | 1911.37 | TARP | TARP | 783.68 | 0.00 | 0.00 | 0.00 | 10 | 0 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | BASEMENT | 2779.43 | 149.6 | 18.579 | 5.382E-002 | 10.273 | 4.842 | 0.000 | 0.000 | 0.000 | 0.000 | 15.115 | No |
2 | CORE_BOTTOM | 2496.12 | 134.4 | 18.579 | 5.382E-002 | 10.273 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 18.343 | No |
3 | CORE_MID | 2496.12 | 134.4 | 18.579 | 5.382E-002 | 10.273 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 18.343 | No |
4 | CORE_TOP | 2496.12 | 134.4 | 18.579 | 5.382E-002 | 10.273 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 18.343 | No |
5 | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 18.579 | 5.382E-002 | 10.273 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 18.343 | No |
6 | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 10.273 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 18.343 | No |
7 | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 18.579 | 5.382E-002 | 10.273 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 18.343 | No |
8 | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 10.273 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 18.343 | No |
9 | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 18.579 | 5.382E-002 | 10.273 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 18.343 | No |
10 | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 10.273 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 18.343 | No |
11 | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 18.579 | 5.382E-002 | 10.273 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 18.343 | No |
12 | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 10.273 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 18.343 | No |
13 | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 18.579 | 5.382E-002 | 10.273 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 18.343 | No |
14 | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 10.273 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 18.343 | No |
15 | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 18.579 | 5.382E-002 | 10.273 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 18.343 | No |
16 | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 10.273 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 18.343 | No |
17 | GROUNDFLOOR_PLENUM | 3563.11 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
18 | MIDFLOOR_PLENUM | 3563.11 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
19 | TOPFLOOR_PLENUM | 3563.11 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
20 | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 18.579 | 5.382E-002 | 17.873 | 215.299 | 0.000 | 0.000 | 0.000 | 0.000 | 233.173 | No |
21 | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 18.579 | 5.382E-002 | 17.873 | 215.299 | 0.000 | 0.000 | 0.000 | 0.000 | 233.173 | No |
22 | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 18.579 | 5.382E-002 | 17.873 | 215.299 | 0.000 | 0.000 | 0.000 | 0.000 | 233.173 | No |
23 | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 18.579 | 5.382E-002 | 10.273 | 484.423 | 0.000 | 0.000 | 0.000 | 0.000 | 494.696 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | DATACENTER_BOT_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 1.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | DATACENTER_MID_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 1.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
3 | DATACENTER_TOP_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 1.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
4 | DATACENTER_BASEMENT_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 42.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 42 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
5 | BASEMENT | BLDG_OCC_SCH_WO_SB | BASEMENT | 2779.43 | 149.6 | 149.6 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 150 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
6 | CORE_BOTTOM | BLDG_OCC_SCH_WO_SB | CORE_BOTTOM | 2496.12 | 134.4 | 134.4 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 134 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
7 | CORE_MID | BLDG_OCC_SCH_WO_SB | CORE_MID | 2496.12 | 134.4 | 134.4 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 134 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
8 | CORE_TOP | BLDG_OCC_SCH_WO_SB | CORE_TOP | 2496.12 | 134.4 | 134.4 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 134 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
9 | PERIMETER_BOT_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
10 | PERIMETER_BOT_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
11 | PERIMETER_BOT_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
12 | PERIMETER_BOT_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
13 | PERIMETER_MID_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
14 | PERIMETER_MID_ZN_2 | BLDG_OCC_SCH_W_SB | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
15 | PERIMETER_MID_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
16 | PERIMETER_MID_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
17 | PERIMETER_TOP_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
18 | PERIMETER_TOP_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
19 | PERIMETER_TOP_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
20 | PERIMETER_TOP_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | BASEMENT_LIGHTS | LTG_SCH_OFFICE | BASEMENT | 2779.43 | 149.6 | 28553.717 | 10.273 | 190.864 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 28553.717 |
2 | CORE_BOTTOM_LIGHTS | LTG_SCH_OFFICE | CORE_BOTTOM | 2496.12 | 134.4 | 25643.245 | 10.273 | 190.864 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 25643.245 |
3 | CORE_MID_LIGHTS | LTG_SCH_OFFICE | CORE_MID | 2496.12 | 134.4 | 25643.245 | 10.273 | 190.864 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 25643.245 |
4 | CORE_TOP_LIGHTS | LTG_SCH_OFFICE | CORE_TOP | 2496.12 | 134.4 | 25643.245 | 10.273 | 190.864 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 25643.245 |
5 | PERIMETER_BOT_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 3219.765 | 10.273 | 190.864 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3219.765 |
6 | PERIMETER_BOT_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 2074.939 | 10.273 | 190.864 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2074.939 |
7 | PERIMETER_BOT_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 3219.836 | 10.273 | 190.864 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3219.836 |
8 | PERIMETER_BOT_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 2074.939 | 10.273 | 190.864 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2074.939 |
9 | PERIMETER_MID_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 3219.765 | 10.273 | 190.864 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3219.765 |
10 | PERIMETER_MID_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 2074.939 | 10.273 | 190.864 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2074.939 |
11 | PERIMETER_MID_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 3219.836 | 10.273 | 190.864 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3219.836 |
12 | PERIMETER_MID_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 2074.939 | 10.273 | 190.864 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2074.939 |
13 | PERIMETER_TOP_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 3219.765 | 10.273 | 190.864 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3219.765 |
14 | PERIMETER_TOP_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 2074.939 | 10.273 | 190.864 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2074.939 |
15 | PERIMETER_TOP_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 3219.836 | 10.273 | 190.864 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3219.836 |
16 | PERIMETER_TOP_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 2074.939 | 10.273 | 190.864 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2074.939 |
17 | DATACENTER_BASEMENT_LIGHTS | LTG_SCH_OFFICE | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 8050.927 | 10.273 | 190.864 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 8050.927 |
18 | DATACENTER_BOT_LIGHTS | LTG_SCH_DATACENTER | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 647.068 | 17.873 | 332.067 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 647.068 |
19 | DATACENTER_MID_LIGHTS | LTG_SCH_DATACENTER | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 647.068 | 17.873 | 332.067 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 647.068 |
20 | DATACENTER_TOP_LIGHTS | LTG_SCH_DATACENTER | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 647.068 | 17.873 | 332.067 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 647.068 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | BASEMENT_MISCPLUG_EQUIP | ALWAYS_ON | BASEMENT | 2779.43 | 149.6 | 13457.544 | 4.842 | 89.956 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 13457.544 | 13457.544 |
2 | CORE_BOTTOM_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_BOTTOM | 2496.12 | 134.4 | 20142.877 | 8.070 | 149.925 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 20142.877 |
3 | CORE_MID_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_MID | 2496.12 | 134.4 | 20142.800 | 8.070 | 149.924 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 20142.800 |
4 | CORE_TOP_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_TOP | 2496.12 | 134.4 | 20142.800 | 8.070 | 149.924 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 20142.800 |
5 | PERIMETER_BOT_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 2529.242 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.242 |
6 | PERIMETER_BOT_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 1629.940 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.940 |
7 | PERIMETER_BOT_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 2529.281 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.281 |
8 | PERIMETER_BOT_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 1629.929 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.929 |
9 | PERIMETER_MID_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 2529.242 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.242 |
10 | PERIMETER_MID_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 1629.940 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.940 |
11 | PERIMETER_MID_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 2529.281 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.281 |
12 | PERIMETER_MID_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 1629.929 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.929 |
13 | PERIMETER_TOP_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 2529.242 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.242 |
14 | PERIMETER_TOP_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 1629.940 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.940 |
15 | PERIMETER_TOP_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 2529.281 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.281 |
16 | PERIMETER_TOP_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 1629.929 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.929 |
17 | DATACENTER_BASEMENT_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 379632.522 | 484.423 | 9000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 94908.130 | 379632.522 |
18 | DATACENTER_BOT_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 7794.422 | 215.299 | 4000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 1948.606 | 7794.422 |
19 | DATACENTER_MID_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 7794.422 | 215.299 | 4000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 1948.606 | 7794.422 |
20 | DATACENTER_TOP_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 7794.422 | 215.299 | 4000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 1948.606 | 7794.422 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 2.839 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | INTERIORFURNISHINGS | 2 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
3 | DROPCEILING | 4 | 1 | 3 | 0.167 | 4.488 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
4 | INT_WALL | 7 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | EXT_SLAB_8IN_WITH_CARPET | 8 | 2 | 7 | 0.167 | 3.285 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
6 | INT_SLAB_FLOOR | 12 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
7 | INT_SLAB_CEILING | 13 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | VeryRough |
8 | NONRES_ROOF | 17 | 3 | 3 | 0.167 | 0.1864 | 0.900 | 0.900 | 0.700 | 0.700 | Rough |
9 | NONRES_EXT_WALL_GRD | 20 | 3 | 9 | 0.167 | 0.9689 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
10 | NONRES_EXT_WALL_MID | 21 | 3 | 9 | 0.167 | 0.9235 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
11 | NONRES_EXT_WALL_TOP | 22 | 3 | 9 | 0.167 | 1.155 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
12 | BASEMENT_WALL_EAST_CFACTOR | 39 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | BASEMENT_WALL_SOUTH_CFACTOR | 40 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | BASEMENT_WALL_NORTH_CFACTOR | 41 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR | 42 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
16 | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR | 43 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
17 | DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR | 44 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.3522 |
2 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
3 | AC02 ACOUSTIC CEILING | 0.0127 | 0.057 | 288.000 | 1339.000 | 0.2228 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | 200MM NORMALWEIGHT CONCRETE FLOOR | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
7 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
8 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
9 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
10 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
11 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
12 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
13 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 5.307 |
14 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
15 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
16 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.8647 |
17 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
18 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
19 | NONRES_EXTERIOR_WALL_INSULATION_MID | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9155 |
20 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
21 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
22 | NONRES_EXTERIOR_WALL_INSULATION_TOP | 0.0000 | 0.000 | 0.000 | 0.000 | 0.6987 |
23 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
24 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
25 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
26 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
27 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
28 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
29 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
30 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
31 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
32 | ~FC_Insulation_5 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
33 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
34 | ~FC_Insulation_6 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
35 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 2.8391315 | 2.8391315 | 2.8391315 | |
3 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
4 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
5 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
6 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
7 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
8 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
9 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
10 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
11 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
12 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
13 | 3 | -0.21589802E-09 | 0.15643069E-09 | -0.21589802E-09 | 0.12999471E-21 |
14 | 2 | 0.50772448E-02 | 0.30006816E-02 | 0.50772448E-02 | -0.13693132E-08 |
15 | 1 | -2.5944910 | 1.4597758 | -2.5944910 | 0.76344767E-02 |
16 | 0 | 7.0433378 | 2.9911476 | 7.0433378 | |
17 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
18 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
19 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
20 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
21 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
22 | 7 | -0.18651654E-16 | -0.16428647E-15 | -0.26578847E-08 | -0.25364002E-17 |
23 | 6 | 0.67402962E-01 | 0.99142722E-07 | 0.38101547E-02 | -0.76639482E-03 |
24 | 5 | -1.8580732 | 0.49502125E-04 | -0.10651409 | 0.21891119E-01 |
25 | 4 | 18.220105 | 0.12801333E-02 | 1.0775450 | -0.22586539 |
26 | 3 | -79.928293 | 0.66708484E-02 | -4.9803755 | 1.0625663 |
27 | 2 | 166.43177 | 0.75131194E-02 | 11.128837 | -2.4125483 |
28 | 1 | -159.97298 | 0.18548900E-02 | -11.587784 | 2.5494418 |
29 | 0 | 57.057412 | 0.52755123E-04 | 4.4818272 | |
30 | 7 | 0.43260499E-16 | 0.34524919E-16 | 0.52793240E-17 | 0.0000000 |
31 | 6 | 0.69434179E-09 | 0.98085174E-11 | 0.18162501E-10 | -0.40870994E-12 |
32 | 5 | -0.12888762E-04 | 0.28373718E-06 | -0.16918523E-06 | 0.92361873E-08 |
33 | 4 | 0.25174112E-01 | 0.33697681E-03 | 0.22646198E-03 | -0.31467795E-04 |
34 | 3 | -3.7600775 | 0.27170599E-01 | -0.48495626E-01 | 0.94171705E-02 |
35 | 2 | 51.553741 | 0.22121684 | 1.2284947 | -0.25833933 |
36 | 1 | -128.86110 | 0.21944682 | -5.1479470 | 1.1228340 |
37 | 0 | 81.526494 | 0.16043334E-01 | 4.4519351 | |
38 | 7 | 0.52793240E-17 | 0.34524919E-16 | 0.43260499E-16 | 0.0000000 |
39 | 6 | 0.18162501E-10 | 0.98085174E-11 | 0.69434179E-09 | -0.40870994E-12 |
40 | 5 | -0.16918523E-06 | 0.28373718E-06 | -0.12888762E-04 | 0.92361873E-08 |
41 | 4 | 0.22646198E-03 | 0.33697681E-03 | 0.25174112E-01 | -0.31467795E-04 |
42 | 3 | -0.48495626E-01 | 0.27170599E-01 | -3.7600775 | 0.94171705E-02 |
43 | 2 | 1.2284947 | 0.22121684 | 51.553741 | -0.25833933 |
44 | 1 | -5.1479470 | 0.21944682 | -128.86110 | 1.1228340 |
45 | 0 | 4.4519351 | 0.16043334E-01 | 81.526494 | |
46 | 3 | -0.62854340E-06 | 0.84784826E-09 | -0.38512804E-05 | 0.91756347E-17 |
47 | 2 | 0.78257096 | 0.11428808E-02 | 1.0614277 | -0.73836085E-06 |
48 | 1 | -21.991499 | 0.76199851E-01 | -6.3161914 | 0.20349372 |
49 | 0 | 21.357363 | 0.71091016E-01 | 5.4032014 | |
50 | 9 | -0.61082983E-15 | 0.35276446E-16 | -0.14787207E-09 | 0.18036823E-17 |
51 | 8 | 0.21615122E-07 | 0.13022774E-12 | 0.37506347E-03 | -0.24577139E-09 |
52 | 7 | -0.12160115E-01 | 0.67804000E-08 | -0.22968555E-01 | 0.13826493E-03 |
53 | 6 | 0.40313748 | 0.23652218E-05 | 0.47020644 | -0.47216777E-02 |
54 | 5 | -5.1689687 | 0.88520675E-04 | -4.4267872 | 0.62916081E-01 |
55 | 4 | 32.907337 | 0.72566064E-03 | 21.383769 | -0.42085466 |
56 | 3 | -111.02301 | 0.15845227E-02 | -55.512186 | 1.5122587 |
57 | 2 | 196.92983 | 0.89280554E-03 | 77.772262 | -2.8975199 |
58 | 1 | -171.09018 | 0.95459611E-04 | -55.224854 | 2.7442846 |
59 | 0 | 57.057407 | 0.54436501E-06 | 15.563573 | |
60 | 9 | -0.28033836E-14 | 0.31423843E-16 | -0.15000593E-09 | 0.49342508E-16 |
61 | 8 | 0.21915022E-07 | 0.12441777E-12 | 0.37821899E-03 | -0.24918134E-09 |
62 | 7 | -0.12254290E-01 | 0.64567074E-08 | -0.23104155E-01 | 0.13933574E-03 |
63 | 6 | 0.40569641 | 0.22493722E-05 | 0.47238617 | -0.47518414E-02 |
64 | 5 | -5.1939411 | 0.84090406E-04 | -4.4435303 | 0.63225727E-01 |
65 | 4 | 33.017798 | 0.68864468E-03 | 21.449218 | -0.42232128 |
66 | 3 | -111.25804 | 0.15023393E-02 | -55.641580 | 1.5156542 |
67 | 2 | 197.16277 | 0.84581883E-03 | 77.890928 | -2.9012190 |
68 | 1 | -171.17623 | 0.90368420E-04 | -55.259345 | 2.7457926 |
69 | 0 | 57.057407 | 0.51494858E-06 | 15.557864 | |
70 | 9 | 0.16475985E-14 | 0.40698495E-16 | -0.13909959E-09 | -0.62647149E-17 |
71 | 8 | 0.20378875E-07 | 0.15355384E-12 | 0.36189576E-03 | -0.23171482E-09 |
72 | 7 | -0.11766586E-01 | 0.81065314E-08 | -0.22401745E-01 | 0.13379037E-03 |
73 | 6 | 0.39244372 | 0.28436739E-05 | 0.46108386 | -0.45956244E-02 |
74 | 5 | -5.0645996 | 0.10693990E-03 | -4.3566540 | 0.61621961E-01 |
75 | 4 | 32.445620 | 0.88045565E-03 | 21.109484 | -0.41472443 |
76 | 3 | -110.04047 | 0.19299305E-02 | -54.969854 | 1.4980638 |
77 | 2 | 195.95581 | 0.10911488E-02 | 77.275137 | -2.8820526 |
78 | 1 | -170.73031 | 0.11703553E-03 | -55.080813 | 2.7379774 |
79 | 0 | 57.057407 | 0.66971377E-06 | 15.587784 | |
80 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
81 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
82 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
83 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
84 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
85 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
86 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
87 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 | |
88 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
89 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
90 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
91 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
92 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
93 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
94 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
95 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 | |
96 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
97 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
98 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
99 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
100 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
101 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
102 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
103 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 | |
104 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
105 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
106 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
107 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
108 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
109 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
110 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
111 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 | |
112 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
113 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
114 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
115 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
116 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
117 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
118 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
119 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 | |
120 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
121 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
122 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
123 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
124 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
125 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
126 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
127 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | WINDOW_U_0.419_SHGC_EAST_0.4 | 35 | 1 | VerySmooth | 2.381 | 2.381 | 1.000 | 0.401 | ||
2 | WINDOW_U_0.419_SHGC_SOUTH_0.4 | 36 | 1 | VerySmooth | 2.381 | 2.381 | 1.000 | 0.401 | ||
3 | WINDOW_U_0.419_SHGC_WEST_0.4 | 37 | 1 | VerySmooth | 2.381 | 2.381 | 1.000 | 0.401 | ||
4 | WINDOW_U_0.419_SHGC_NORTH_0.4 | 38 | 1 | VerySmooth | 2.381 | 2.381 | 1.000 | 0.401 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | GLAZING LAYER EAST | SpectralAverage | 3.03930E-002 | 0.31435 | 0.47506 | 0.47506 | 0.44000 | 0.13397 | 0.17027 | 0.00000 | 0.84000 | 0.84000 | 0.12237 | 1.00000 | No | |
2 | GLAZING LAYER SOUTH | SpectralAverage | 3.03930E-002 | 0.31435 | 0.47506 | 0.47506 | 0.44000 | 0.13397 | 0.17027 | 0.00000 | 0.84000 | 0.84000 | 0.12237 | 1.00000 | No | |
3 | GLAZING LAYER WEST | SpectralAverage | 3.03930E-002 | 0.31435 | 0.47506 | 0.47506 | 0.44000 | 0.13397 | 0.17027 | 0.00000 | 0.84000 | 0.84000 | 0.12237 | 1.00000 | No | |
4 | GLAZING LAYER NORTH | SpectralAverage | 3.03930E-002 | 0.31435 | 0.47506 | 0.47506 | 0.44000 | 0.13397 | 0.17027 | 0.00000 | 0.84000 | 0.84000 | 0.12237 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 30 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Enclosure Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Enclosures | |
1 | PERIMETER_BOT_ZN_3 | 5 | 0 |
2 | PERIMETER_BOT_ZN_2 | 3 | 0 |
3 | PERIMETER_BOT_ZN_1 | 5 | 0 |
4 | PERIMETER_BOT_ZN_4 | 3 | 0 |
5 | PERIMETER_MID_ZN_3 | 1 | 0 |
6 | PERIMETER_MID_ZN_2 | 1 | 0 |
7 | PERIMETER_MID_ZN_1 | 1 | 0 |
8 | PERIMETER_MID_ZN_4 | 1 | 0 |
9 | PERIMETER_TOP_ZN_3 | 1 | 0 |
10 | PERIMETER_TOP_ZN_2 | 1 | 0 |
11 | PERIMETER_TOP_ZN_1 | 1 | 0 |
12 | PERIMETER_TOP_ZN_4 | 1 | 0 |
Enclosure Name | Number of Adjacent Enclosures with Windows | Adjacent Enclosure Names - 1st 100 (max) | |
1 | PERIMETER_BOT_ZN_3 | 0 | |
2 | PERIMETER_BOT_ZN_2 | 0 | |
3 | PERIMETER_BOT_ZN_1 | 0 | |
4 | PERIMETER_BOT_ZN_4 | 0 | |
5 | PERIMETER_MID_ZN_3 | 0 | |
6 | PERIMETER_MID_ZN_2 | 0 | |
7 | PERIMETER_MID_ZN_1 | 0 | |
8 | PERIMETER_MID_ZN_4 | 0 | |
9 | PERIMETER_TOP_ZN_3 | 0 | |
10 | PERIMETER_TOP_ZN_2 | 0 | |
11 | PERIMETER_TOP_ZN_1 | 0 | |
12 | PERIMETER_TOP_ZN_4 | 0 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 1.1356 | 87921.3 | 0.481 | 5.5005E-002 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | BASEMENT_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
2 | BASEMENT_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
3 | BASEMENT_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
4 | BASEMENT_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
5 | BASEMENT_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
6 | PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
7 | PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
8 | CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
9 | PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
10 | BASEMENT_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
11 | CORE_BOT_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
12 | CORE_BOT_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
13 | CORE_BOT_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
14 | CORE_BOT_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
15 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
16 | CORE_BOT_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
17 | CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
18 | CORE_BOTTOM_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
19 | CORE_MID_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
20 | CORE_MID_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
21 | CORE_MID_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
22 | CORE_MID_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
23 | CORE_MID_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
24 | CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
25 | CORE_MID_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
26 | CORE_TOP_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
27 | CORE_TOP_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
28 | CORE_TOP_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
29 | CORE_TOP_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
30 | CORE_TOP_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
31 | CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
32 | CORE_TOP_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
33 | PERIMETER_BOT_ZN_3_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
34 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
35 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
36 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
37 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
38 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
39 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
40 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
41 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
42 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
43 | PERIMETER_BOT_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
44 | CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
45 | PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
46 | DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
47 | PERIMETER_BOT_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
48 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
49 | PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
50 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
51 | PERIMETER_BOT_ZN_2_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
52 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
53 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
54 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
55 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
56 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
57 | PERIMETER_BOT_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
58 | CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
59 | PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
60 | PERIMETER_BOT_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
61 | PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
62 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
63 | PERIMETER_BOT_ZN_1_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
64 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
65 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
66 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
67 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
68 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
69 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
70 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
71 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
72 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
73 | PERIMETER_BOT_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
74 | DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
75 | PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
76 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
77 | DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
78 | PERIMETER_BOT_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
79 | PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
80 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
81 | PERIMETER_BOT_ZN_4_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
82 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
83 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
84 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
85 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
86 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
87 | PERIMETER_BOT_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
88 | DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
89 | PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
90 | PERIMETER_BOT_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
91 | PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
92 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
93 | PERIMETER_MID_ZN_3_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
94 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
95 | PERIMETER_MID_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
96 | CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
97 | PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
98 | DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
99 | PERIMETER_MID_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
100 | PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
101 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
102 | PERIMETER_MID_ZN_2_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
103 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
104 | PERIMETER_MID_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
105 | CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
106 | PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
107 | PERIMETER_MID_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
108 | PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
109 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
110 | PERIMETER_MID_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
111 | PERIMETER_MID_ZN_1_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
112 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
113 | DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
114 | PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
115 | CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
116 | PERIMETER_MID_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
117 | PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
118 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
119 | PERIMETER_MID_ZN_4_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
120 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
121 | PERIMETER_MID_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
122 | DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
123 | PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
124 | PERIMETER_MID_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
125 | PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
126 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
127 | PERIMETER_TOP_ZN_3_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
128 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
129 | PERIMETER_TOP_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
130 | CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
131 | PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
132 | DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
133 | PERIMETER_TOP_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
134 | PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
135 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
136 | PERIMETER_TOP_ZN_2_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
137 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
138 | PERIMETER_TOP_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
139 | CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
140 | INT-PER3S-NE-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
141 | PERIMETER_TOP_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
142 | PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
143 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
144 | PERIMETER_TOP_ZN_1_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
145 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
146 | INT-PER3S-NE | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
147 | DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
148 | PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
149 | CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
150 | PERIMETER_TOP_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
151 | PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
152 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
153 | PERIMETER_TOP_ZN_4_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
154 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
155 | PERIMETER_TOP_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
156 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
157 | PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
158 | PERIMETER_TOP_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
159 | PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
160 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
161 | GROUNDFLOOR_PLENUM_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
162 | GROUNDFLOOR_PLENUM_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
163 | GROUNDFLOOR_PLENUM_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
164 | GROUNDFLOOR_PLENUM_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
165 | iz-CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
166 | iz-PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
167 | iz-PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
168 | iz-PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
169 | iz-PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
170 | iz-DATACENTER_BOT_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
171 | GROUNDFLOOR_PLENUM_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
172 | MIDFLOOR_PLENUM_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
173 | MIDFLOOR_PLENUM_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
174 | MIDFLOOR_PLENUM_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
175 | MIDFLOOR_PLENUM_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
176 | iz-CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
177 | iz-PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
178 | iz-PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
179 | iz-PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
180 | iz-PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
181 | iz-DATACENTER_MID_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
182 | MIDFLOOR_PLENUM_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
183 | TOPFLOOR_PLENUM_WALL_NORTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
184 | TOPFLOOR_PLENUM_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
185 | TOPFLOOR_PLENUM_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
186 | TOPFLOOR_PLENUM_WALL_SOUTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
187 | iz-CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
188 | iz-PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
189 | iz-PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
190 | iz-PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
191 | iz-PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
192 | iz-DATACENTER_TOP_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
193 | BUILDING_ROOF | 0 | 3563.11 | 268.06 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
194 | DATACENTER_BOT_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
195 | DATACENTER_BOT_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
196 | DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
197 | DATACENTER_BOT_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
198 | DATACENTER_BOT_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
199 | DATACENTER_BOT_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
200 | DATACENTER_MID_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
201 | DATACENTER_MID_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
202 | DATACENTER_MID_ZN_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
203 | DATACENTER_MID_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
204 | DATACENTER_MID_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
205 | DATACENTER_MID_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
206 | DATACENTER_TOP_ZN_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
207 | DATACENTER_TOP_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
208 | DATACENTER_TOP_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
209 | DATACENTER_TOP_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
210 | DATACENTER_TOP_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
211 | DATACENTER_TOP_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
212 | DATACENTER_BASEMENT_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
213 | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
214 | DATACENTER_BASEMENT_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
215 | DATACENTER_BASEMENT_ZN_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
216 | DATACENTER_BASEMENT_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
217 | DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
218 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
219 | PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
220 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
221 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | PERIMETER_BOT_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 0.114 | 3.646E-004 | 5.482E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | PERIMETER_BOT_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 7.617E-002 | 3.771E-004 | 5.534E-004 | 0.495 | 0.000 | 0.000 | 0.224 | 0.000 |
3 | PERIMETER_BOT_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 0.114 | 3.646E-004 | 5.482E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | PERIMETER_BOT_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 7.617E-002 | 3.771E-004 | 5.534E-004 | 0.495 | 0.000 | 0.000 | 0.224 | 0.000 |
5 | PERIMETER_MID_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 0.114 | 3.646E-004 | 5.696E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
6 | PERIMETER_MID_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 7.617E-002 | 3.771E-004 | 5.696E-004 | 0.495 | 0.000 | 0.000 | 0.224 | 0.000 |
7 | PERIMETER_MID_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 0.114 | 3.646E-004 | 5.696E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
8 | PERIMETER_MID_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 7.617E-002 | 3.771E-004 | 5.696E-004 | 0.495 | 0.000 | 0.000 | 0.224 | 0.000 |
9 | PERIMETER_TOP_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 0.114 | 3.646E-004 | 5.696E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
10 | PERIMETER_TOP_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 7.617E-002 | 3.771E-004 | 5.696E-004 | 0.495 | 0.000 | 0.000 | 0.224 | 0.000 |
11 | PERIMETER_TOP_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 0.114 | 3.646E-004 | 5.696E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
12 | PERIMETER_TOP_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 7.617E-002 | 3.771E-004 | 5.696E-004 | 0.495 | 0.000 | 0.000 | 0.224 | 0.000 |
13 | GROUNDFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | GROUNDFLOOR_PLENUM | 3563.11 | 0.0 | 0.169 | 4.749E-005 | 5.696E-004 | 0.140 | 0.000 | 0.000 | 0.224 | 0.000 |
14 | MIDFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | MIDFLOOR_PLENUM | 3563.11 | 0.0 | 0.169 | 4.749E-005 | 5.696E-004 | 0.140 | 0.000 | 0.000 | 0.224 | 0.000 |
15 | TOPFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | TOPFLOOR_PLENUM | 3563.11 | 0.0 | 0.169 | 4.749E-005 | 4.384E-005 | 0.140 | 0.000 | 0.000 | 0.224 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | BASEMENT | Mixing/Well-Stirred |
2 | CORE_BOTTOM | Mixing/Well-Stirred |
3 | CORE_MID | Mixing/Well-Stirred |
4 | CORE_TOP | Mixing/Well-Stirred |
5 | PERIMETER_BOT_ZN_3 | Mixing/Well-Stirred |
6 | PERIMETER_BOT_ZN_2 | Mixing/Well-Stirred |
7 | PERIMETER_BOT_ZN_1 | Mixing/Well-Stirred |
8 | PERIMETER_BOT_ZN_4 | Mixing/Well-Stirred |
9 | PERIMETER_MID_ZN_3 | Mixing/Well-Stirred |
10 | PERIMETER_MID_ZN_2 | Mixing/Well-Stirred |
11 | PERIMETER_MID_ZN_1 | Mixing/Well-Stirred |
12 | PERIMETER_MID_ZN_4 | Mixing/Well-Stirred |
13 | PERIMETER_TOP_ZN_3 | Mixing/Well-Stirred |
14 | PERIMETER_TOP_ZN_2 | Mixing/Well-Stirred |
15 | PERIMETER_TOP_ZN_1 | Mixing/Well-Stirred |
16 | PERIMETER_TOP_ZN_4 | Mixing/Well-Stirred |
17 | GROUNDFLOOR_PLENUM | Mixing/Well-Stirred |
18 | MIDFLOOR_PLENUM | Mixing/Well-Stirred |
19 | TOPFLOOR_PLENUM | Mixing/Well-Stirred |
20 | DATACENTER_BOT_ZN_6 | Mixing/Well-Stirred |
21 | DATACENTER_MID_ZN_6 | Mixing/Well-Stirred |
22 | DATACENTER_TOP_ZN_6 | Mixing/Well-Stirred |
23 | DATACENTER_BASEMENT_ZN_6 | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sky Type | MonthAndDay | Daylighting Control Name | Enclosure Name | Window Name | Reference Point | Daylight Factor | |
1 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 7.3145E-003 |
2 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 7.3170E-003 |
3 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 8.0578E-003 |
4 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 8.0598E-003 |
5 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 5.0422E-003 |
6 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 5.0438E-003 |
7 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.7740E-003 |
8 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.7748E-003 |
9 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 7.3704E-003 |
10 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 7.5390E-003 |
11 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 8.1055E-003 |
12 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 8.2551E-003 |
13 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 5.0832E-003 |
14 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 5.2045E-003 |
15 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.7969E-003 |
16 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.8551E-003 |
17 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 0.1798 |
18 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 9.0667E-002 |
19 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 0.2040 |
20 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 0.1030 |
21 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 0.1236 |
22 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.9835E-002 |
23 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 5.0165E-002 |
24 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.7447E-002 |
25 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 7.3707E-003 |
26 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 7.5384E-003 |
27 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 8.1055E-003 |
28 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 8.2534E-003 |
29 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 5.0832E-003 |
30 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 5.2045E-003 |
31 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.7974E-003 |
32 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.8568E-003 |
33 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 7.3143E-003 |
34 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 7.3167E-003 |
35 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 8.0574E-003 |
36 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 8.0595E-003 |
37 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 5.0420E-003 |
38 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 5.0436E-003 |
39 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.7739E-003 |
40 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.7747E-003 |
41 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 6.0132E-003 |
42 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 6.3402E-003 |
43 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 5.6665E-003 |
44 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 6.0249E-003 |
45 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 5.4614E-003 |
46 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 5.6021E-003 |
47 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 4.7428E-003 |
48 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 4.7830E-003 |
49 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 6.5610E-002 |
50 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.2390E-002 |
51 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 6.0072E-002 |
52 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 2.8915E-002 |
53 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 6.4482E-002 |
54 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 2.6854E-002 |
55 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 5.2230E-002 |
56 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 1.9536E-002 |
57 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 5.9074E-003 |
58 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 6.0240E-003 |
59 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 5.5285E-003 |
60 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 5.6127E-003 |
61 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 5.4159E-003 |
62 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 5.4474E-003 |
63 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 4.7430E-003 |
64 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 4.7836E-003 |
65 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.9265E-003 |
66 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.9287E-003 |
67 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.4810E-003 |
68 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.4828E-003 |
69 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.1935E-003 |
70 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.1948E-003 |
71 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.7740E-003 |
72 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.7749E-003 |
73 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.9773E-003 |
74 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 3.1109E-003 |
75 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.5221E-003 |
76 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.6271E-003 |
77 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.2262E-003 |
78 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.2990E-003 |
79 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.7975E-003 |
80 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.8569E-003 |
81 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 4.7226E-002 |
82 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.4954E-002 |
83 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.6127E-002 |
84 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.8857E-002 |
85 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.2630E-002 |
86 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.2694E-002 |
87 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 5.0165E-002 |
88 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.7442E-002 |
89 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.9763E-003 |
90 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 3.1070E-003 |
91 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.5215E-003 |
92 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.6246E-003 |
93 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.2261E-003 |
94 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.2991E-003 |
95 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.7969E-003 |
96 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.8551E-003 |
97 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.9264E-003 |
98 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.9286E-003 |
99 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.4809E-003 |
100 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.4827E-003 |
101 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.1934E-003 |
102 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.1947E-003 |
103 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.7739E-003 |
104 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.7748E-003 |
105 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 5.9986E-003 |
106 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 6.1146E-003 |
107 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 5.6433E-003 |
108 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 5.7273E-003 |
109 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 5.4866E-003 |
110 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 5.5185E-003 |
111 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 4.7431E-003 |
112 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 4.7837E-003 |
113 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 6.7197E-002 |
114 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.3025E-002 |
115 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 6.2055E-002 |
116 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.9711E-002 |
117 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 6.5787E-002 |
118 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.7377E-002 |
119 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 5.2230E-002 |
120 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 1.9536E-002 |
121 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 6.1079E-003 |
122 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 6.4486E-003 |
123 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 5.7857E-003 |
124 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 6.1617E-003 |
125 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 5.5323E-003 |
126 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 5.6752E-003 |
127 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 4.7428E-003 |
128 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 4.7829E-003 |
129 | Clear Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 0.1736 |
130 | Clear Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 0.1218 |
131 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 0.1901 |
132 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 0.1363 |
133 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 0.1360 |
134 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 7.3175E-002 |
135 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 6.1425E-002 |
136 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 3.0380E-002 |
137 | Clear Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 7.8420E-002 |
138 | Clear Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 4.6778E-002 |
139 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 7.2224E-002 |
140 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 4.2503E-002 |
141 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 7.6656E-002 |
142 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 3.9781E-002 |
143 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 6.2997E-002 |
144 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 3.0728E-002 |
145 | Clear Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 5.8573E-002 |
146 | Clear Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 3.9047E-002 |
147 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 4.6009E-002 |
148 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 3.0726E-002 |
149 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 4.2194E-002 |
150 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 2.3025E-002 |
151 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 6.1425E-002 |
152 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 3.0375E-002 |
153 | Clear Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 8.0215E-002 |
154 | Clear Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 4.7655E-002 |
155 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 7.4469E-002 |
156 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 4.3605E-002 |
157 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 7.8118E-002 |
158 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 4.0475E-002 |
159 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 6.2997E-002 |
160 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 3.0728E-002 |
161 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 0.1737 |
162 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 0.1220 |
163 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 0.1902 |
164 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 0.1366 |
165 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 0.1362 |
166 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 7.3354E-002 |
167 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 6.1557E-002 |
168 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 3.0447E-002 |
169 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 7.8469E-002 |
170 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 4.6847E-002 |
171 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 7.2279E-002 |
172 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 4.2568E-002 |
173 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 7.6774E-002 |
174 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 3.9864E-002 |
175 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 6.3129E-002 |
176 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 3.0795E-002 |
177 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 5.8577E-002 |
178 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 3.9092E-002 |
179 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 4.6016E-002 |
180 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 3.0761E-002 |
181 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 4.2261E-002 |
182 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 2.3068E-002 |
183 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 6.1557E-002 |
184 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 3.0442E-002 |
185 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 8.0267E-002 |
186 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 4.7727E-002 |
187 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 7.4529E-002 |
188 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 4.3672E-002 |
189 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 7.8238E-002 |
190 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 4.0560E-002 |
191 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 6.3129E-002 |
192 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 3.0795E-002 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | BASEMENT | Cooling | 81824.74093 | 81824.74093 | 7.28395 | 7.28395 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 22.94800 | 5.45871E-003 | 2779.42662 | 149.60210 | 1.20016 | 0.00000 |
2 | BASEMENT | Heating | 0.00000 | 0.00000 | 0.00000 | 1.20016 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:20:00 | -17.90000 | 9.55238E-004 | 2779.42662 | 149.60210 | 1.20016 | 0.00000 |
3 | CORE_BOTTOM | Cooling | 85355.15165 | 85355.15165 | 7.59724 | 7.59724 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 22.94800 | 5.45871E-003 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 |
4 | CORE_BOTTOM | Heating | 0.00000 | 0.00000 | 0.00000 | 1.07782 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 05:50:00 | -17.90000 | 9.55238E-004 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 |
5 | CORE_MID | Cooling | 806036.02819 | 806036.02819 | 71.72946 | 71.72946 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 22.94800 | 5.45871E-003 | 2496.12046 | 134.35320 | 10.77825 | 0.00000 |
6 | CORE_MID | Heating | 286780.81635 | 286780.81635 | 14.94285 | 14.94285 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -17.90000 | 9.55238E-004 | 2496.12046 | 134.35320 | 10.77825 | 0.00000 |
7 | CORE_TOP | Cooling | 79067.01580 | 79067.01580 | 7.03624 | 7.03624 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 22.94800 | 5.45871E-003 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 |
8 | CORE_TOP | Heating | 67431.53289 | 67431.53289 | 3.53491 | 3.53491 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -17.90000 | 9.55238E-004 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 |
9 | PERIMETER_BOT_ZN_3 | Cooling | 14589.34915 | 14589.34915 | 1.30944 | 1.30944 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | 33.90000 | 5.47527E-003 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
10 | PERIMETER_BOT_ZN_3 | Heating | 11420.00284 | 11420.00284 | 0.59939 | 0.59939 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -17.90000 | 9.55238E-004 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
11 | PERIMETER_BOT_ZN_2 | Cooling | 19025.19445 | 19025.19445 | 1.70755 | 1.70755 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:40:00 | 24.82267 | 5.46148E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
12 | PERIMETER_BOT_ZN_2 | Heating | 8012.16653 | 8012.16653 | 0.42065 | 0.42065 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -17.90000 | 9.55238E-004 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
13 | PERIMETER_BOT_ZN_1 | Cooling | 20847.65796 | 20847.65796 | 1.87114 | 1.87114 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:10:00 | 33.28333 | 5.47432E-003 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
14 | PERIMETER_BOT_ZN_1 | Heating | 12953.08653 | 12953.08653 | 0.68011 | 0.68011 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -17.90000 | 9.55238E-004 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
15 | PERIMETER_BOT_ZN_4 | Cooling | 23783.02653 | 23783.02653 | 2.13458 | 2.13458 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 | 32.02533 | 5.47238E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
16 | PERIMETER_BOT_ZN_4 | Heating | 6357.31743 | 6357.31743 | 0.33347 | 0.33347 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -17.90000 | 9.55238E-004 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
17 | PERIMETER_MID_ZN_3 | Cooling | 138714.10035 | 138714.10035 | 12.44987 | 12.44987 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | 33.90000 | 5.47527E-003 | 313.41284 | 16.86939 | 1.35332 | 0.00000 |
18 | PERIMETER_MID_ZN_3 | Heating | 176575.82915 | 176575.82915 | 9.27819 | 9.27819 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -17.90000 | 9.55238E-004 | 313.41284 | 16.86939 | 1.35332 | 0.00000 |
19 | PERIMETER_MID_ZN_2 | Cooling | 202716.91863 | 202716.91863 | 18.19405 | 18.19405 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | 25.76000 | 5.46288E-003 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
20 | PERIMETER_MID_ZN_2 | Heating | 118772.87729 | 118772.87729 | 6.24148 | 6.24148 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -17.90000 | 9.55238E-004 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
21 | PERIMETER_MID_ZN_1 | Cooling | 206777.42335 | 206777.42335 | 18.55861 | 18.55861 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:20:00 | 33.40667 | 5.47451E-003 | 313.41969 | 16.86975 | 1.35335 | 0.00000 |
22 | PERIMETER_MID_ZN_1 | Heating | 178927.78682 | 178927.78682 | 9.40204 | 9.40204 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -17.90000 | 9.55238E-004 | 313.41969 | 16.86975 | 1.35335 | 0.00000 |
23 | PERIMETER_MID_ZN_4 | Cooling | 222932.90534 | 222932.90534 | 20.00847 | 20.00847 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 31.82800 | 5.47208E-003 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
24 | PERIMETER_MID_ZN_4 | Heating | 114288.95358 | 114288.95358 | 6.00540 | 6.00540 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -17.90000 | 9.55238E-004 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
25 | PERIMETER_TOP_ZN_3 | Cooling | 15667.47768 | 15667.47768 | 1.40618 | 1.40618 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 33.90000 | 5.47527E-003 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
26 | PERIMETER_TOP_ZN_3 | Heating | 22420.56170 | 22420.56170 | 1.17858 | 1.17858 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -17.90000 | 9.55238E-004 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
27 | PERIMETER_TOP_ZN_2 | Cooling | 20309.43185 | 20309.43185 | 1.82278 | 1.82278 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:10:00 | 26.17933 | 5.46350E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
28 | PERIMETER_TOP_ZN_2 | Heating | 14966.77112 | 14966.77112 | 0.78680 | 0.78680 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -17.90000 | 9.55238E-004 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
29 | PERIMETER_TOP_ZN_1 | Cooling | 22332.83249 | 22332.83249 | 2.00440 | 2.00440 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 33.53000 | 5.47470E-003 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
30 | PERIMETER_TOP_ZN_1 | Heating | 22677.90236 | 22677.90236 | 1.19213 | 1.19213 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -17.90000 | 9.55238E-004 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
31 | PERIMETER_TOP_ZN_4 | Cooling | 23500.10284 | 23500.10284 | 2.10915 | 2.10915 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 31.82800 | 5.47208E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
32 | PERIMETER_TOP_ZN_4 | Heating | 14655.52782 | 14655.52782 | 0.77042 | 0.77042 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -17.90000 | 9.55238E-004 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
33 | DATACENTER_BOT_ZN_6 | Cooling | 8795.87440 | 8795.87440 | 0.62268 | 0.62268 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:50:00 | 28.49800 | 5.46700E-003 | 36.20274 | 1.94861 | 1.56323E-002 | 0.00000 |
34 | DATACENTER_BOT_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 1.56323E-002 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 05:30:00 | -17.90000 | 9.55238E-004 | 36.20274 | 1.94861 | 1.56323E-002 | 0.00000 |
35 | DATACENTER_MID_ZN_6 | Cooling | 84512.22694 | 84512.22694 | 5.98286 | 5.98286 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:50:00 | 28.49800 | 5.46700E-003 | 36.20274 | 1.94861 | 0.15632 | 0.00000 |
36 | DATACENTER_MID_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 0.15632 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 05:40:00 | -17.90000 | 9.55238E-004 | 36.20274 | 1.94861 | 0.15632 | 0.00000 |
37 | DATACENTER_TOP_ZN_6 | Cooling | 8610.28315 | 8610.28315 | 0.60954 | 0.60954 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:50:00 | 28.49800 | 5.46700E-003 | 36.20274 | 1.94861 | 1.56323E-002 | 0.00000 |
38 | DATACENTER_TOP_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 1.56323E-002 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 05:40:00 | -17.90000 | 9.55238E-004 | 36.20274 | 1.94861 | 1.56323E-002 | 0.00000 |
39 | DATACENTER_BASEMENT_ZN_6 | Cooling | 373125.53880 | 373125.53880 | 26.41420 | 26.41420 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 07:00:00 | 20.43200 | 5.45503E-003 | 783.67941 | 42.18139 | 0.33839 | 0.00000 |
40 | DATACENTER_BASEMENT_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 0.33839 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 07:50:00 | -17.90000 | 9.55238E-004 | 783.67941 | 42.18139 | 0.33839 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | VAV_BOT WITH REHEAT | Cooling | Sensible | 160797.39 | 12.55486 | 12.55486 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
2 | VAV_BOT WITH REHEAT | Heating | Sensible | 76665.40 | 3.11144 | 3.11144 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 07:20:00 |
3 | VAV_MID WITH REHEAT | Cooling | Sensible | 1497963.64 | 117.71948 | 117.71948 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
4 | VAV_MID WITH REHEAT | Heating | Sensible | 761750.83 | 45.86996 | 45.86996 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 22:20:00 |
5 | VAV_TOP WITH REHEAT | Cooling | Sensible | 168626.40 | 13.10651 | 13.10651 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
6 | VAV_TOP WITH REHEAT | Heating | Sensible | 76321.64 | 7.46283 | 7.46283 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 22:30:00 |
7 | CAV_BAS | Cooling | Sensible | 81984.28 | 7.28395 | 7.28395 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
8 | CAV_BAS | Heating | Sensible | 68251.22 | 1.20016 | 1.20016 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
9 | AIRLOOP DATACENTER BASEMENT | Cooling | Sensible | 370256.97 | 26.41442 | 26.41442 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
10 | AIRLOOP DATACENTER BASEMENT | Heating | Sensible | 19243.92 | 0.33839 | 0.33839 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
11 | AIRLOOP DATACENTER BOT | Cooling | Sensible | 8706.61 | 0.62268 | 0.62268 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
12 | AIRLOOP DATACENTER BOT | Heating | Sensible | 888.99 | 1.56323E-002 | 1.56323E-002 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
13 | AIRLOOP DATACENTER MID | Cooling | Sensible | 83663.59 | 5.98286 | 5.98286 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
14 | AIRLOOP DATACENTER MID | Heating | Sensible | 8889.90 | 0.15632 | 0.15632 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
15 | AIRLOOP DATACENTER TOP | Cooling | Sensible | 8526.54 | 0.60954 | 0.60954 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
16 | AIRLOOP DATACENTER TOP | Heating | Sensible | 888.99 | 1.56323E-002 | 1.56323E-002 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | BASEMENT DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 7.28395 |
2 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 7.59724 |
3 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.25036 |
4 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.27200 |
5 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.06645 |
6 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.66763 |
7 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
8 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.52181E-003 |
9 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.47753E-004 |
10 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 2.06645 |
11 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
12 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
13 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 16889.03660 |
14 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.47753E-004 |
15 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 340.46972 |
16 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 71.72946 |
17 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.26517 |
18 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.28400 |
19 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 20.37117 |
20 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.70712 |
21 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
22 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.43682E-003 |
23 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 3.96544E-003 |
24 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 20.37117 |
25 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
26 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
27 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 453273.89122 |
28 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.96544E-003 |
29 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 11044.67607 |
30 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 7.03624 |
31 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.27032 |
32 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.29700 |
33 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.08976 |
34 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.72086 |
35 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
36 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.40943E-003 |
37 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 8.42669E-004 |
38 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 3.53491 |
39 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
40 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
41 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 96322.26044 |
42 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 8.42669E-004 |
43 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 2541.78138 |
44 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.30944 |
45 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.18238 |
46 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
47 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.26189 |
48 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.48636 |
49 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
50 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.08900E-003 |
51 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.42741E-004 |
52 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.59939 |
53 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
54 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
55 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 16316.17697 |
56 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.42741E-004 |
57 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 430.35734 |
58 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.70755 |
59 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 9.01320E-002 |
60 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
61 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.34151 |
62 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
63 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
64 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 4.22713E-003 |
65 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.00156E-004 |
66 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.42065 |
67 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
68 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
69 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 11448.46080 |
70 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.00156E-004 |
71 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 301.94057 |
72 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.87114 |
73 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.12764 |
74 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
75 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.37423 |
76 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.34036 |
77 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
78 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.98503E-003 |
79 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.61927E-004 |
80 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.68011 |
81 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
82 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
83 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 18509.23210 |
84 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.61927E-004 |
85 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 488.14920 |
86 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.13458 |
87 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 7.21009E-002 |
88 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
89 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.42692 |
90 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
91 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
92 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 5.28426E-003 |
93 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 8.61192E-005 |
94 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.42692 |
95 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
96 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
97 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 9843.95001 |
98 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 8.61192E-005 |
99 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 242.82541 |
100 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 12.44987 |
101 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.19183 |
102 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20500 |
103 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.55222 |
104 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.51154 |
105 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
106 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.98618E-003 |
107 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.20768E-003 |
108 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 9.27819 |
109 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
110 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
111 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 252351.22498 |
112 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.20768E-003 |
113 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 6653.46889 |
114 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 18.19405 |
115 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 8.45909E-002 |
116 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
117 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 3.63881 |
118 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
119 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
120 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 4.50403E-003 |
121 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.48502E-003 |
122 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 6.24148 |
123 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
124 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
125 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 169747.39133 |
126 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.48502E-003 |
127 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 4475.41887 |
128 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 18.55861 |
129 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.12869 |
130 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
131 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 3.71172 |
132 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.34317 |
133 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
134 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.96067E-003 |
135 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.23711E-003 |
136 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 9.40204 |
137 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
138 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
139 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 255715.27737 |
140 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.23711E-003 |
141 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 6742.10977 |
142 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 20.00847 |
143 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 7.69199E-002 |
144 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
145 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 4.00169 |
146 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
147 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
148 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 4.95320E-003 |
149 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.42892E-003 |
150 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 6.00540 |
151 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
152 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
153 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 163334.33330 |
154 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.42892E-003 |
155 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 4306.42556 |
156 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.40618 |
157 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.16984 |
158 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
159 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.28124 |
160 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.45290 |
161 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
162 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.24333E-003 |
163 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.80351E-004 |
164 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.17858 |
165 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
166 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
167 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 32045.86763 |
168 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.80351E-004 |
169 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 844.80402 |
170 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.82278 |
171 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 8.44341E-002 |
172 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
173 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.36456 |
174 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
175 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
176 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 4.51239E-003 |
177 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.87150E-004 |
178 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.78680 |
179 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
180 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
181 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 21392.43899 |
182 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.87150E-004 |
183 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 563.94433 |
184 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.00440 |
185 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.11915 |
186 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
187 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.40088 |
188 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.31774 |
189 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
190 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.19762E-003 |
191 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.83571E-004 |
192 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.19213 |
193 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
194 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
195 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 32413.93422 |
196 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.83571E-004 |
197 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 854.50246 |
198 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.10915 |
199 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 7.29703E-002 |
200 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
201 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.42183 |
202 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
203 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
204 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 5.22130E-003 |
205 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.83256E-004 |
206 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.77042 |
207 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
208 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
209 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 20947.33138 |
210 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.83256E-004 |
211 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 552.21421 |
212 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DATACENTER_BOT_ZN_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.62268 |
213 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DATACENTER_MID_ZN_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 5.98286 |
214 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DATACENTER_TOP_ZN_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.60954 |
215 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DATACENTER_BASEMENT_ZN_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 26.41420 |
216 | AirLoopHVAC | VAV_BOT WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 7.30997 |
217 | AirLoopHVAC | VAV_BOT WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 3.47099 |
218 | AirLoopHVAC | VAV_BOT WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 14.61995 |
219 | AirLoopHVAC | VAV_BOT WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 3.47099 |
220 | AirLoopHVAC | VAV_BOT WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 12.55486 |
221 | AirLoopHVAC | VAV_BOT WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 12.55486 |
222 | AirLoopHVAC | VAV_BOT WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
223 | AirLoopHVAC | VAV_BOT WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.27647 |
224 | AirLoopHVAC | VAV_MID WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 70.47024 |
225 | AirLoopHVAC | VAV_MID WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 34.27562 |
226 | AirLoopHVAC | VAV_MID WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 140.94047 |
227 | AirLoopHVAC | VAV_MID WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 45.86996 |
228 | AirLoopHVAC | VAV_MID WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 117.71948 |
229 | AirLoopHVAC | VAV_MID WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 117.71948 |
230 | AirLoopHVAC | VAV_MID WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
231 | AirLoopHVAC | VAV_MID WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.38965 |
232 | AirLoopHVAC | VAV_TOP WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 7.18937 |
233 | AirLoopHVAC | VAV_TOP WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 3.55826 |
234 | AirLoopHVAC | VAV_TOP WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 14.37874 |
235 | AirLoopHVAC | VAV_TOP WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 7.46283 |
236 | AirLoopHVAC | VAV_TOP WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 13.10651 |
237 | AirLoopHVAC | VAV_TOP WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 13.10651 |
238 | AirLoopHVAC | VAV_TOP WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
239 | AirLoopHVAC | VAV_TOP WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.56940 |
240 | AirLoopHVAC | CAV_BAS | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 7.28395 |
241 | AirLoopHVAC | CAV_BAS | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 7.28395 |
242 | AirLoopHVAC | CAV_BAS | Sum of Air Terminal Maximum Flow Rates [m3/s] | 7.28395 |
243 | AirLoopHVAC | CAV_BAS | Adjusted Heating Design Air Flow Rate [m3/s] | 7.28395 |
244 | AirLoopHVAC | CAV_BAS | Adjusted Cooling Design Air Flow Rate [m3/s] | 7.28395 |
245 | AirLoopHVAC | CAV_BAS | Adjusted Main Design Air Flow Rate [m3/s] | 7.28395 |
246 | AirLoopHVAC | CAV_BAS | User Heating Air Flow Ratio [] | 1.00000 |
247 | AirLoopHVAC | CAV_BAS | Calculated Heating Air Flow Ratio [] | 1.00000 |
248 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 26.41420 |
249 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 26.41420 |
250 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 26.41420 |
251 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Adjusted Heating Design Air Flow Rate [m3/s] | 26.41420 |
252 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Adjusted Cooling Design Air Flow Rate [m3/s] | 26.41442 |
253 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Adjusted Main Design Air Flow Rate [m3/s] | 26.41442 |
254 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | User Heating Air Flow Ratio [] | 1.00000 |
255 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Calculated Heating Air Flow Ratio [] | 0.99999 |
256 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.62268 |
257 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.62268 |
258 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.62268 |
259 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Adjusted Heating Design Air Flow Rate [m3/s] | 0.62268 |
260 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.62268 |
261 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Adjusted Main Design Air Flow Rate [m3/s] | 0.62268 |
262 | AirLoopHVAC | AIRLOOP DATACENTER BOT | User Heating Air Flow Ratio [] | 1.00000 |
263 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Calculated Heating Air Flow Ratio [] | 1.00000 |
264 | AirLoopHVAC | AIRLOOP DATACENTER MID | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 5.98286 |
265 | AirLoopHVAC | AIRLOOP DATACENTER MID | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 5.98286 |
266 | AirLoopHVAC | AIRLOOP DATACENTER MID | Sum of Air Terminal Maximum Flow Rates [m3/s] | 5.98286 |
267 | AirLoopHVAC | AIRLOOP DATACENTER MID | Adjusted Heating Design Air Flow Rate [m3/s] | 5.98286 |
268 | AirLoopHVAC | AIRLOOP DATACENTER MID | Adjusted Cooling Design Air Flow Rate [m3/s] | 5.98286 |
269 | AirLoopHVAC | AIRLOOP DATACENTER MID | Adjusted Main Design Air Flow Rate [m3/s] | 5.98286 |
270 | AirLoopHVAC | AIRLOOP DATACENTER MID | User Heating Air Flow Ratio [] | 1.00000 |
271 | AirLoopHVAC | AIRLOOP DATACENTER MID | Calculated Heating Air Flow Ratio [] | 1.00000 |
272 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.60954 |
273 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.60954 |
274 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.60954 |
275 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Adjusted Heating Design Air Flow Rate [m3/s] | 0.60954 |
276 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.60954 |
277 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Adjusted Main Design Air Flow Rate [m3/s] | 0.60954 |
278 | AirLoopHVAC | AIRLOOP DATACENTER TOP | User Heating Air Flow Ratio [] | 1.00000 |
279 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Calculated Heating Air Flow Ratio [] | 1.00000 |
280 | AirLoopHVAC | VAV_BOT WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 12.55486 |
281 | AirLoopHVAC | VAV_MID WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 117.71948 |
282 | AirLoopHVAC | VAV_TOP WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 13.10651 |
283 | AirLoopHVAC | CAV_BAS | Design Supply Air Flow Rate [m3/s] | 7.28395 |
284 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Design Supply Air Flow Rate [m3/s] | 26.41442 |
285 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Design Supply Air Flow Rate [m3/s] | 0.62268 |
286 | AirLoopHVAC | AIRLOOP DATACENTER MID | Design Supply Air Flow Rate [m3/s] | 5.98286 |
287 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Design Supply Air Flow Rate [m3/s] | 0.60954 |
288 | Controller:OutdoorAir | VAV_BOT WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 12.55486 |
289 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Inlet Air Temperature [C] | 26.02959 |
290 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
291 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Outlet Air Temperature [C] | 10.63920 |
292 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 6.92696E-003 |
293 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 6.92696E-003 |
294 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Coil Load [W] | 192210.78715 |
295 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 8.17709E-003 |
296 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 12.55486 |
297 | Coil:Heating:Water | VAV_BOT WITH REHEAT HEATING COIL | Design Size Rated Capacity [W] | 77297.81559 |
298 | Coil:Heating:Water | VAV_BOT WITH REHEAT HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 6.76235E-004 |
299 | Coil:Heating:Water | VAV_BOT WITH REHEAT HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 1239.36479 |
300 | Fan:VariableVolume | VAV_BOT WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 12.55486 |
301 | Controller:WaterCoil | VAV_BOT WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 8.17709E-003 |
302 | Controller:WaterCoil | VAV_BOT WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 5.82347E-005 |
303 | Controller:WaterCoil | VAV_BOT WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 6.76235E-004 |
304 | Controller:OutdoorAir | VAV_MID WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 117.71948 |
305 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Inlet Air Temperature [C] | 26.20823 |
306 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
307 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Outlet Air Temperature [C] | 10.63911 |
308 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 6.90412E-003 |
309 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 6.90412E-003 |
310 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Coil Load [W] | 1823098.99631 |
311 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 7.75588E-002 |
312 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 117.71948 |
313 | Coil:Heating:Water | VAV_MID WITH REHEAT HEATING COIL | Design Size Rated Capacity [W] | 685347.73933 |
314 | Coil:Heating:Water | VAV_MID WITH REHEAT HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 5.99572E-003 |
315 | Coil:Heating:Water | VAV_MID WITH REHEAT HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 11052.28105 |
316 | Fan:VariableVolume | VAV_MID WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 117.71948 |
317 | Controller:WaterCoil | VAV_MID WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 7.75588E-002 |
318 | Controller:WaterCoil | VAV_MID WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 6.13973E-006 |
319 | Controller:WaterCoil | VAV_MID WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 5.99572E-003 |
320 | Controller:OutdoorAir | VAV_TOP WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 13.10651 |
321 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Inlet Air Temperature [C] | 25.91924 |
322 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
323 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Outlet Air Temperature [C] | 10.63918 |
324 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 6.92107E-003 |
325 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 6.92107E-003 |
326 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Coil Load [W] | 199215.66068 |
327 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 8.47509E-003 |
328 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 13.10651 |
329 | Coil:Heating:Water | VAV_TOP WITH REHEAT HEATING COIL | Design Size Rated Capacity [W] | 66608.52427 |
330 | Coil:Heating:Water | VAV_TOP WITH REHEAT HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 5.82720E-004 |
331 | Coil:Heating:Water | VAV_TOP WITH REHEAT HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 1088.96939 |
332 | Fan:VariableVolume | VAV_TOP WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 13.10651 |
333 | Controller:WaterCoil | VAV_TOP WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 8.47509E-003 |
334 | Controller:WaterCoil | VAV_TOP WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 5.61870E-005 |
335 | Controller:WaterCoil | VAV_TOP WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 5.82720E-004 |
336 | Controller:OutdoorAir | CAV_BAS_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 7.28395 |
337 | Controller:OutdoorAir | CAV_BAS_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.20016 |
338 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Inlet Air Temperature [C] | 25.69746 |
339 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
340 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Outlet Air Temperature [C] | 11.10693 |
341 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 7.09867E-003 |
342 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 7.09867E-003 |
343 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Coil Load [W] | 105752.34229 |
344 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 4.49895E-003 |
345 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 7.28395 |
346 | Coil:Heating:Water | CAV_BAS HEATING COIL | Design Size Rated Capacity [W] | 307268.00048 |
347 | Coil:Heating:Water | CAV_BAS HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.68811E-003 |
348 | Coil:Heating:Water | CAV_BAS HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 6711.49193 |
349 | Fan:ConstantVolume | CAV_BAS FAN | Design Size Maximum Flow Rate [m3/s] | 7.28395 |
350 | Controller:WaterCoil | CAV_BAS_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 4.49895E-003 |
351 | Controller:WaterCoil | CAV_BAS_COOLC_CONTROLLER | Controller Convergence Tolerance | 1.05845E-004 |
352 | Controller:WaterCoil | CAV_BAS_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 2.68811E-003 |
353 | Controller:OutdoorAir | AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 26.41442 |
354 | Controller:OutdoorAir | AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.33839 |
355 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 26.41442 |
356 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Rated Total Cooling Capacity [W] | 479130.06052 |
357 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Rated Sensible Cooling Capacity [W] | 251095.38088 |
358 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Rated Water Flow Rate [m3/s] | 1.17339E-002 |
359 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 26.41442 |
360 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 26.41442 |
361 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 26.41442 |
362 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 26.41442 |
363 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Nominal Heating Capacity [W] | 479130.06052 |
364 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 479130.06052 |
365 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 19243.92393 |
366 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
367 | Fan:OnOff | AIRLOOP DATACENTER BASEMENT SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 26.41442 |
368 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 26.41442 |
369 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT HEATING COIL | Design Size Rated Heating Capacity [W] | 479130.06052 |
370 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT HEATING COIL | Design Size Rated Water Flow Rate [m3/s] | 1.17339E-002 |
371 | Coil:Heating:Electric | AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 19243.92393 |
372 | Humidifier:Steam:Electric | DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | Design Size Nominal Capacity Volume [m3/s] | 1.75612E-004 |
373 | Humidifier:Steam:Electric | DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | User-Specified Nominal Capacity Volume [m3/s] | 3.72000E-005 |
374 | Humidifier:Steam:Electric | DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | Design Size Rated Power [W] | 96450.69782 |
375 | Humidifier:Steam:Electric | DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | User-Specified Rated Power [W] | 100000.00000 |
376 | Controller:OutdoorAir | AIRLOOP DATACENTER BOT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.62268 |
377 | Controller:OutdoorAir | AIRLOOP DATACENTER BOT_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.56323E-002 |
378 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.62268 |
379 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT COOLING COIL | Design Size Rated Total Cooling Capacity [W] | 10972.22807 |
380 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT COOLING COIL | Design Size Rated Sensible Cooling Capacity [W] | 5809.80128 |
381 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT COOLING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.68709E-004 |
382 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 0.62268 |
383 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 0.62268 |
384 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 0.62268 |
385 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 0.62268 |
386 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Nominal Heating Capacity [W] | 10972.22807 |
387 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 10972.22807 |
388 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 888.98956 |
389 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
390 | Fan:OnOff | AIRLOOP DATACENTER BOT SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.62268 |
391 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.62268 |
392 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT HEATING COIL | Design Size Rated Heating Capacity [W] | 10972.22807 |
393 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT HEATING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.68709E-004 |
394 | Coil:Heating:Electric | AIRLOOP DATACENTER BOT_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 888.98956 |
395 | Controller:OutdoorAir | AIRLOOP DATACENTER MID_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 5.98286 |
396 | Controller:OutdoorAir | AIRLOOP DATACENTER MID_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.15632 |
397 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 5.98286 |
398 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID COOLING COIL | Design Size Rated Total Cooling Capacity [W] | 105453.92286 |
399 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID COOLING COIL | Design Size Rated Sensible Cooling Capacity [W] | 55828.60300 |
400 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID COOLING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.58256E-003 |
401 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 5.98286 |
402 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 5.98286 |
403 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 5.98286 |
404 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 5.98286 |
405 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Nominal Heating Capacity [W] | 105453.92286 |
406 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 105453.92286 |
407 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 8889.89563 |
408 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
409 | Fan:OnOff | AIRLOOP DATACENTER MID SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 5.98286 |
410 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 5.98286 |
411 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID HEATING COIL | Design Size Rated Heating Capacity [W] | 105453.92286 |
412 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID HEATING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.58256E-003 |
413 | Coil:Heating:Electric | AIRLOOP DATACENTER MID_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 8889.89563 |
414 | Controller:OutdoorAir | AIRLOOP DATACENTER TOP_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.60954 |
415 | Controller:OutdoorAir | AIRLOOP DATACENTER TOP_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.56323E-002 |
416 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.60954 |
417 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP COOLING COIL | Design Size Rated Total Cooling Capacity [W] | 10747.41487 |
418 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP COOLING COIL | Design Size Rated Sensible Cooling Capacity [W] | 5689.23301 |
419 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP COOLING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.63203E-004 |
420 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 0.60954 |
421 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 0.60954 |
422 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 0.60954 |
423 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 0.60954 |
424 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Nominal Heating Capacity [W] | 10747.41487 |
425 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 10747.41487 |
426 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 888.98956 |
427 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
428 | Fan:OnOff | AIRLOOP DATACENTER TOP SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.60954 |
429 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.60954 |
430 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP HEATING COIL | Design Size Rated Heating Capacity [W] | 10747.41487 |
431 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP HEATING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.63203E-004 |
432 | Coil:Heating:Electric | AIRLOOP DATACENTER TOP_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 888.98956 |
433 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Flow Rate [m3/s] | 9.87100E-002 |
434 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Power Consumption [W] | 16116.32362 |
435 | PlantLoop | COOLSYS1_DEMAND | Maximum Loop Flow Rate [m3/s] | 9.87100E-002 |
436 | PlantLoop | COOLSYS1_DEMAND | Plant Loop Volume [m3] | 11.84520 |
437 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Loop Supply Side Design Fluid Flow Rate [m3/s] | 9.87100E-002 |
438 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Loop Demand Side Design Fluid Flow Rate [m3/s] | 9.87100E-002 |
439 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Heat Exchanger U-Factor Times Area Value [W/C] | 414335.31900 |
440 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Loop-to-loop Temperature Difference Used to Size Heat Exchanger U-Factor Times Area Value [C] | 5.60000 |
441 | PlantLoop | HEATSYS1 | Maximum Loop Flow Rate [m3/s] | 2.36827E-002 |
442 | PlantLoop | HEATSYS1 | Plant Loop Volume [m3] | 2.84192 |
443 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Flow Rate [m3/s] | 2.36827E-002 |
444 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Power Consumption [W] | 7132.17553 |
445 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Minimum Flow Rate [m3/s] | 0.00000 |
446 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Nominal Capacity [W] | 2707072.88702 |
447 | Boiler:HotWater | HEATSYS1 BOILER | User-Specified Nominal Capacity [W] | 2707072.89000 |
448 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Design Water Flow Rate [m3/s] | 2.36827E-002 |
449 | PlantLoop | COOLSYS1_SUPPLY | Maximum Loop Flow Rate [m3/s] | 9.87100E-002 |
450 | PlantLoop | COOLSYS1_SUPPLY | Plant Loop Volume [m3] | 11.84520 |
451 | Pump:ConstantSpeed | COOLSYS1 CHILLER1 PUMP | Design Flow Rate [m3/s] | 4.93550E-002 |
452 | Pump:ConstantSpeed | COOLSYS1 CHILLER1 PUMP | Design Power Consumption [W] | 5578.93717 |
453 | Pump:ConstantSpeed | COOLSYS1 CHILLER2 PUMP | Design Flow Rate [m3/s] | 4.93550E-002 |
454 | Pump:ConstantSpeed | COOLSYS1 CHILLER2 PUMP | Design Power Consumption [W] | 5578.93717 |
455 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | Design Size Reference Chilled Water Flow Rate [m3/s] | 9.87100E-002 |
456 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | User-Specified Reference Chilled Water Flow Rate [m3/s] | 5.01350E-002 |
457 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | Design Size Reference Capacity [W] | 1181368.69047 |
458 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | User-Specified Reference Capacity [W] | 1186966.84500 |
459 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | Design Size Reference Condenser Water Flow Rate [m3/s] | 5.87386E-002 |
460 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | Design Size Reference Chilled Water Flow Rate [m3/s] | 9.87100E-002 |
461 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | User-Specified Reference Chilled Water Flow Rate [m3/s] | 5.01350E-002 |
462 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | Design Size Reference Capacity [W] | 1181368.69047 |
463 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | User-Specified Reference Capacity [W] | 1186966.84500 |
464 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | Design Size Reference Condenser Water Flow Rate [m3/s] | 5.87386E-002 |
465 | PlantLoop | SINGLE WATER PLANT LOOP | Maximum Loop Flow Rate [m3/s] | 1.48483E-002 |
466 | PlantLoop | SINGLE WATER PLANT LOOP | Plant Loop Volume [m3] | 1.78180 |
467 | Pump:ConstantSpeed | PLANT CIRC PUMP | Design Flow Rate [m3/s] | 1.48483E-002 |
468 | Pump:ConstantSpeed | PLANT CIRC PUMP | Design Power Consumption [W] | 3787.06841 |
469 | FluidCooler:TwoSpeed | CENTRAL TOWER | Design Water Flow Rate [m3/s] | 1.48483E-002 |
470 | FluidCooler:TwoSpeed | CENTRAL TOWER | Air Flow Rate at High Fan Speed [m3/s] | 139666.46671 |
471 | FluidCooler:TwoSpeed | CENTRAL TOWER | Fluid cooler UA value at high fan speed based on nominal capacity input [W/K] | 54366.00439 |
472 | FluidCooler:TwoSpeed | CENTRAL TOWER | Air Flow Rate at Low Fan Speed [m3/s] | 69833.23335 |
473 | FluidCooler:TwoSpeed | CENTRAL TOWER | Fan Power at Low Fan Speed [W] | 7879.72339 |
474 | FluidCooler:TwoSpeed | CENTRAL TOWER | U-factor Times Area Value at Low Fan Speed [W/C] | 20886.86724 |
475 | Boiler:HotWater | CENTRAL BOILER | Design Size Nominal Capacity [W] | 611624.18005 |
476 | Boiler:HotWater | CENTRAL BOILER | User-Specified Nominal Capacity [W] | 597767.97000 |
477 | Boiler:HotWater | CENTRAL BOILER | Design Size Design Water Flow Rate [m3/s] | 1.48483E-002 |
478 | PlantLoop | SWHSYS1 | Maximum Loop Flow Rate [m3/s] | 4.40000E-004 |
479 | PlantLoop | SWHSYS1 | Plant Loop Volume [m3] | 5.28000E-002 |
480 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Flow Rate [m3/s] | 4.40000E-004 |
481 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Power Consumption [W] | 56.20530 |
482 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | Use Side Design Flow Rate [m3/s] | 4.40000E-004 |
483 | CondenserLoop | TOWERWATERSYS | Maximum Loop Flow Rate [m3/s] | 0.11748 |
484 | CondenserLoop | TOWERWATERSYS | Condenser Loop Volume [m3] | 14.09726 |
485 | HeaderedPumps:VariableSpeed | TOWERWATERSYS PUMP | Design Flow Rate [m3/s] | 0.11748 |
486 | HeaderedPumps:VariableSpeed | TOWERWATERSYS PUMP | Design Power Consumption [W] | 29084.75058 |
487 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Design Air Flow Rate [m3/s] | 55.93132 |
488 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Nominal Capacity [W] | 1410050.16479 |
489 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Air Flow Rate in free convection regime [m3/s] | 11.18626 |
490 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Tower capacity in free convection regime at design conditions [W] | 176256.27060 |
491 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Design Air Flow Rate [m3/s] | 55.93132 |
492 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Nominal Capacity [W] | 1410050.16479 |
493 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Air Flow Rate in free convection regime [m3/s] | 11.18626 |
494 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Tower capacity in free convection regime at design conditions [W] | 176256.27060 |
495 | PlantEquipmentOperation:ComponentSetPoint | WSHPPLANT OPERATION SCHEME | Design Water Flow Rate [m3/s] Equipment # 47 | 6.10100E-002 |
496 | PlantEquipmentOperation:ComponentSetPoint | WSHPPLANT OPERATION SCHEME | Design Water Flow Rate [m3/s] Equipment # 47 | 6.10100E-002 |
Component Type | Name | Nominal Total Capacity {W} | |
1 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | 16016.92 |
2 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | 429586.49 |
3 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | 91308.40 |
4 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | 15465.53 |
5 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | 10851.42 |
6 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | 17543.89 |
7 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | 9328.65 |
8 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | 239177.32 |
9 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | 160884.94 |
10 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | 242365.38 |
11 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | 154807.30 |
12 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | 30372.15 |
13 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | 20275.07 |
14 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | 30720.96 |
15 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | 19853.23 |
16 | Coil:Heating:Water | VAV_BOT WITH REHEAT HEATING COIL | 56354.90 |
17 | Coil:Heating:Water | VAV_MID WITH REHEAT HEATING COIL | 505951.93 |
18 | Coil:Heating:Water | VAV_TOP WITH REHEAT HEATING COIL | 50596.28 |
19 | Coil:Heating:Water | CAV_BAS HEATING COIL | 238169.85 |
Component Type | Name | Nominal Total Capacity {W} | Nominal Sensible Capacity {W} | Nominal Latent Capacity {W} | Nominal Sensible Heat Ratio | Nominal Coil UA Value {W/C} | Nominal Coil Surface Area {m2} | |
1 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | 264812.85 | 167743.30 | 97069.55 | 0.63 | 27197.13 | 275.85 |
2 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | 2493022.83 | 1576637.02 | 916385.81 | 0.63 | 255533.55 | 2591.76 |
3 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | 275671.10 | 174810.56 | 100860.54 | 0.63 | 28335.12 | 287.39 |
4 | Coil:Cooling:Water | CAV_BAS COOLING COIL | 146253.68 | 93953.72 | 52299.96 | 0.64 | 14416.08 | 146.22 |
Component Type | Component Name | IPLV in SI Units {W/W} | IPLV in IP Units {Btu/W-h} | |
1 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | 6.84 | 23.33 |
2 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | 6.84 | 23.33 |
Zone Name | # Surfaces | |
1 | BASEMENT | 10 |
2 | CORE_BOTTOM | 8 |
3 | CORE_MID | 7 |
4 | CORE_TOP | 7 |
5 | PERIMETER_BOT_ZN_3 | 18 |
6 | PERIMETER_BOT_ZN_2 | 12 |
7 | PERIMETER_BOT_ZN_1 | 18 |
8 | PERIMETER_BOT_ZN_4 | 12 |
9 | PERIMETER_MID_ZN_3 | 9 |
10 | PERIMETER_MID_ZN_2 | 8 |
11 | PERIMETER_MID_ZN_1 | 9 |
12 | PERIMETER_MID_ZN_4 | 8 |
13 | PERIMETER_TOP_ZN_3 | 9 |
14 | PERIMETER_TOP_ZN_2 | 8 |
15 | PERIMETER_TOP_ZN_1 | 9 |
16 | PERIMETER_TOP_ZN_4 | 8 |
17 | GROUNDFLOOR_PLENUM | 11 |
18 | MIDFLOOR_PLENUM | 11 |
19 | TOPFLOOR_PLENUM | 11 |
20 | DATACENTER_BOT_ZN_6 | 6 |
21 | DATACENTER_MID_ZN_6 | 6 |
22 | DATACENTER_TOP_ZN_6 | 6 |
23 | DATACENTER_BASEMENT_ZN_6 | 10 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | BASEMENT_WALL_EAST | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_EAST_CFACTOR | 0.419 | 0.394 | 118.87 | 118.87 | 118.87 | 90.00 | 90.00 | 48.74 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | BASEMENT_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_SOUTH_CFACTOR | 0.419 | 0.394 | 139.09 | 139.09 | 139.09 | 180.00 | 90.00 | 57.03 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
3 | BASEMENT_WALL_NORTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_NORTH_CFACTOR | 0.419 | 0.394 | 139.09 | 139.09 | 139.09 | 0.00 | 90.00 | 57.03 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | BASEMENT_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.87 | 118.87 | 118.87 | 270.00 | 90.00 | 48.74 | 2.44 | 0.00 | DATACENTER_BASEMENT_ZN_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
5 | BASEMENT_FLOOR | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 2779.43 | 2779.43 | 2779.43 | 0.00 | 180.00 | 57.03 | 48.74 | 0.00 | BASEMENT_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
6 | PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | PERIMETER_BOT_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
7 | PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 250.34 | 250.34 | 250.34 | 180.00 | 0.00 | 57.03 | 4.57 | 0.00 | PERIMETER_BOT_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
8 | CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 2076.77 | 2076.77 | 2076.77 | 180.00 | 0.00 | 52.45 | 39.59 | 0.00 | CORE_BOT_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
9 | PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 250.34 | 250.34 | 250.34 | 180.00 | 0.00 | 52.45 | 4.57 | 0.00 | PERIMETER_BOT_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
10 | BASEMENT_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 7126.21 | 7126.21 | 7126.21 | 0.00 | 90.00 | 7126.21 | 1.00 | 0.00 | BASEMENT_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
11 | CORE_BOT_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
12 | CORE_BOT_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
13 | CORE_BOT_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
14 | CORE_BOT_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
15 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 419.30 | 419.30 | 419.30 | 0.00 | 180.00 | 10.59 | 39.59 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
16 | CORE_BOT_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 2076.82 | 2076.82 | 2076.82 | 0.00 | 180.00 | 52.46 | 39.59 | 0.00 | CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
17 | CORE_BOT_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 2496.12 | 2496.12 | 2496.12 | 180.00 | 0.00 | 63.05 | 39.59 | 0.00 | iz-CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
18 | CORE_BOTTOM_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 5064.65 | 5064.65 | 5064.65 | 0.00 | 90.00 | 5064.65 | 1.00 | 0.00 | CORE_BOTTOM_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
19 | CORE_MID_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
20 | CORE_MID_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
21 | CORE_MID_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
22 | CORE_MID_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
23 | CORE_MID_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_MID_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
24 | CORE_MID_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 2496.12 | 2496.12 | 2496.12 | 180.00 | 0.00 | 63.05 | 39.59 | 0.00 | iz-CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
25 | CORE_MID_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 5064.65 | 5064.65 | 5064.65 | 0.00 | 90.00 | 5064.65 | 1.00 | 0.00 | CORE_MID_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
26 | CORE_TOP_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
27 | CORE_TOP_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
28 | CORE_TOP_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
29 | CORE_TOP_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
30 | CORE_TOP_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_TOP_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
31 | CORE_TOP_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 2496.12 | 2496.12 | 2496.12 | 180.00 | 0.00 | 63.05 | 39.59 | 0.00 | iz-CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
32 | CORE_TOP_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 5064.65 | 5064.65 | 5064.65 | 0.00 | 90.00 | 5064.65 | 1.00 | 0.00 | CORE_TOP_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
33 | PERIMETER_BOT_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.969 | 0.846 | 76.91 | 200.61 | 76.91 | 0.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
34 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.419_SHGC_NORTH_0.4 | N/A | 2.381 | No | 23.18 | 23.18 | 23.18 | 0.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
35 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.419_SHGC_NORTH_0.4 | N/A | 2.381 | No | 23.18 | 23.18 | 23.18 | 0.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
36 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.419_SHGC_NORTH_0.4 | N/A | 2.381 | No | 23.18 | 23.18 | 23.18 | 0.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
37 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.419_SHGC_NORTH_0.4 | N/A | 2.381 | No | 23.18 | 23.18 | 23.18 | 0.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
38 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.419_SHGC_NORTH_0.4 | N/A | 2.381 | No | 23.18 | 23.18 | 23.18 | 0.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
39 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.839 | 2.839 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
40 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.839 | 2.839 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
41 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.839 | 2.839 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
42 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.839 | 2.839 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
43 | PERIMETER_BOT_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
44 | CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
45 | PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
46 | DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
47 | PERIMETER_BOT_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 250.34 | 250.34 | 250.34 | 0.00 | 180.00 | 52.46 | 6.47 | 0.00 | PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
48 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 63.07 | 63.07 | 63.07 | 0.00 | 180.00 | 11.51 | 4.57 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
49 | PERIMETER_BOT_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.41 | 313.41 | 313.41 | 180.00 | 0.00 | 63.96 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
50 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.83 | 626.83 | 626.83 | 0.00 | 90.00 | 626.83 | 1.00 | 0.00 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
51 | PERIMETER_BOT_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.969 | 0.846 | 52.57 | 133.74 | 52.57 | 90.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
52 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.419_SHGC_EAST_0.4 | N/A | 2.381 | No | 25.75 | 25.75 | 25.75 | 90.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
53 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.419_SHGC_EAST_0.4 | N/A | 2.381 | No | 25.75 | 25.75 | 25.75 | 90.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
54 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.419_SHGC_EAST_0.4 | N/A | 2.381 | No | 25.75 | 25.75 | 25.75 | 90.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
55 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | Door | PERIMETER_BOT_ZN_2_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.839 | 2.839 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
56 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | Door | PERIMETER_BOT_ZN_2_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.839 | 2.839 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
57 | PERIMETER_BOT_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
58 | CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
59 | PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
60 | PERIMETER_BOT_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
61 | PERIMETER_BOT_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | iz-PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
62 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
63 | PERIMETER_BOT_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.969 | 0.846 | 76.91 | 200.61 | 76.91 | 180.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
64 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.419_SHGC_SOUTH_0.4 | N/A | 2.381 | No | 23.18 | 23.18 | 23.18 | 180.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
65 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.419_SHGC_SOUTH_0.4 | N/A | 2.381 | No | 23.18 | 23.18 | 23.18 | 180.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
66 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.419_SHGC_SOUTH_0.4 | N/A | 2.381 | No | 23.18 | 23.18 | 23.18 | 180.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
67 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.419_SHGC_SOUTH_0.4 | N/A | 2.381 | No | 23.18 | 23.18 | 23.18 | 180.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
68 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.419_SHGC_SOUTH_0.4 | N/A | 2.381 | No | 23.18 | 23.18 | 23.18 | 180.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
69 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.839 | 2.839 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
70 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.839 | 2.839 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
71 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.839 | 2.839 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
72 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.839 | 2.839 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
73 | PERIMETER_BOT_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
74 | DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
75 | PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
76 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
77 | DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 63.07 | 63.07 | 63.07 | 0.00 | 180.00 | 16.08 | 4.57 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
78 | PERIMETER_BOT_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 250.35 | 250.35 | 250.35 | 0.00 | 180.00 | 57.03 | 6.47 | 0.00 | PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
79 | PERIMETER_BOT_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.42 | 313.42 | 313.42 | 180.00 | 0.00 | 73.11 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
80 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.84 | 626.84 | 626.84 | 0.00 | 90.00 | 626.84 | 1.00 | 0.00 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
81 | PERIMETER_BOT_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.969 | 0.846 | 52.57 | 133.74 | 52.57 | 270.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
82 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.419_SHGC_WEST_0.4 | N/A | 2.381 | No | 25.75 | 25.75 | 25.75 | 270.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
83 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.419_SHGC_WEST_0.4 | N/A | 2.381 | No | 25.75 | 25.75 | 25.75 | 270.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
84 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.419_SHGC_WEST_0.4 | N/A | 2.381 | No | 25.75 | 25.75 | 25.75 | 270.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
85 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | Door | PERIMETER_BOT_ZN_4_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.839 | 2.839 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
86 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | Door | PERIMETER_BOT_ZN_4_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.839 | 2.839 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
87 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
88 | DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
89 | PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
90 | PERIMETER_BOT_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
91 | PERIMETER_BOT_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | iz-PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
92 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
93 | PERIMETER_MID_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.924 | 0.811 | 84.71 | 200.61 | 84.71 | 0.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
94 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_MID_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.419_SHGC_NORTH_0.4 | N/A | 2.381 | No | 115.90 | 115.90 | 115.90 | 0.00 | 90.00 | 73.11 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
95 | PERIMETER_MID_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
96 | CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
97 | PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
98 | DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
99 | PERIMETER_MID_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
100 | PERIMETER_MID_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.41 | 313.41 | 313.41 | 180.00 | 0.00 | 63.96 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
101 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.83 | 626.83 | 626.83 | 0.00 | 90.00 | 626.83 | 1.00 | 0.00 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
102 | PERIMETER_MID_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.924 | 0.811 | 56.47 | 133.74 | 56.47 | 90.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
103 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_MID_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.419_SHGC_EAST_0.4 | N/A | 2.381 | No | 77.26 | 77.26 | 77.26 | 90.00 | 90.00 | 48.74 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
104 | PERIMETER_MID_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
105 | CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
106 | PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
107 | PERIMETER_MID_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_MID_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
108 | PERIMETER_MID_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | iz-PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
109 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
110 | PERIMETER_MID_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
111 | PERIMETER_MID_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.924 | 0.811 | 84.71 | 200.61 | 84.71 | 180.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
112 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_MID_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.419_SHGC_SOUTH_0.4 | N/A | 2.381 | No | 115.90 | 115.90 | 115.90 | 180.00 | 90.00 | 73.11 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
113 | DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
114 | PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
115 | CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
116 | PERIMETER_MID_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
117 | PERIMETER_MID_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.42 | 313.42 | 313.42 | 180.00 | 0.00 | 73.11 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
118 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.84 | 626.84 | 626.84 | 0.00 | 90.00 | 626.84 | 1.00 | 0.00 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
119 | PERIMETER_MID_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.924 | 0.811 | 56.47 | 133.74 | 56.47 | 270.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
120 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_MID_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.419_SHGC_WEST_0.4 | N/A | 2.381 | No | 77.26 | 77.26 | 77.26 | 270.00 | 90.00 | 48.74 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
121 | PERIMETER_MID_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
122 | DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
123 | PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
124 | PERIMETER_MID_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_MID_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
125 | PERIMETER_MID_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | iz-PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
126 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
127 | PERIMETER_TOP_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.155 | 0.985 | 84.71 | 200.61 | 84.71 | 0.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
128 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_TOP_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.419_SHGC_NORTH_0.4 | N/A | 2.381 | No | 115.90 | 115.90 | 115.90 | 0.00 | 90.00 | 73.11 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
129 | PERIMETER_TOP_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
130 | CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
131 | PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
132 | DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
133 | PERIMETER_TOP_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_TOP_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
134 | PERIMETER_TOP_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.41 | 313.41 | 313.41 | 180.00 | 0.00 | 63.96 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
135 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.83 | 626.83 | 626.83 | 0.00 | 90.00 | 626.83 | 1.00 | 0.00 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
136 | PERIMETER_TOP_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.155 | 0.985 | 56.47 | 133.74 | 56.47 | 90.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
137 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_TOP_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.419_SHGC_EAST_0.4 | N/A | 2.381 | No | 77.26 | 77.26 | 77.26 | 90.00 | 90.00 | 48.74 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
138 | PERIMETER_TOP_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
139 | CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
140 | INT-PER3S-NE-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | INT-PER3S-NE | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
141 | PERIMETER_TOP_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_TOP_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
142 | PERIMETER_TOP_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | iz-PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
143 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
144 | PERIMETER_TOP_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.155 | 0.985 | 84.71 | 200.61 | 84.71 | 180.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
145 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_TOP_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.419_SHGC_SOUTH_0.4 | N/A | 2.381 | No | 115.90 | 115.90 | 115.90 | 180.00 | 90.00 | 73.11 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
146 | INT-PER3S-NE | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | INT-PER3S-NE-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
147 | DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
148 | PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
149 | CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
150 | PERIMETER_TOP_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_TOP_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
151 | PERIMETER_TOP_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.42 | 313.42 | 313.42 | 180.00 | 0.00 | 73.11 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
152 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.84 | 626.84 | 626.84 | 0.00 | 90.00 | 626.84 | 1.00 | 0.00 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
153 | PERIMETER_TOP_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.155 | 0.985 | 56.47 | 133.74 | 56.47 | 270.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
154 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_TOP_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.419_SHGC_WEST_0.4 | N/A | 2.381 | No | 77.26 | 77.26 | 77.26 | 270.00 | 90.00 | 48.74 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
155 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
156 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
157 | PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
158 | PERIMETER_TOP_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_TOP_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
159 | PERIMETER_TOP_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | iz-PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
160 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
161 | GROUNDFLOOR_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.969 | 0.846 | 89.13 | 89.13 | 89.13 | 0.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
162 | GROUNDFLOOR_PLENUM_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.969 | 0.846 | 59.42 | 59.42 | 59.42 | 270.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
163 | GROUNDFLOOR_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.969 | 0.846 | 89.13 | 89.13 | 89.13 | 180.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
164 | GROUNDFLOOR_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.969 | 0.846 | 59.42 | 59.42 | 59.42 | 90.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
165 | iz-CORE_BOT_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
166 | iz-PERIMETER_BOT_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
167 | iz-PERIMETER_BOT_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
168 | iz-PERIMETER_BOT_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
169 | iz-PERIMETER_BOT_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
170 | iz-DATACENTER_BOT_ZN_6_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_BOT_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
171 | GROUNDFLOOR_PLENUM_CEILING | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 3563.11 | 3563.11 | 3563.11 | 180.00 | 0.00 | 73.11 | 48.74 | 0.00 | GROUNDFLOOR_PLENUM_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
172 | MIDFLOOR_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.924 | 0.811 | 89.13 | 89.13 | 89.13 | 0.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
173 | MIDFLOOR_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.924 | 0.811 | 59.42 | 59.42 | 59.42 | 270.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
174 | MIDFLOOR_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.924 | 0.811 | 89.13 | 89.13 | 89.13 | 180.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
175 | MIDFLOOR_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.924 | 0.811 | 59.42 | 59.42 | 59.42 | 90.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
176 | iz-CORE_MID_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
177 | iz-PERIMETER_MID_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
178 | iz-PERIMETER_MID_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
179 | iz-PERIMETER_MID_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
180 | iz-PERIMETER_MID_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
181 | iz-DATACENTER_MID_ZN_6_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_MID_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
182 | MIDFLOOR_PLENUM_CEILING | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 3563.11 | 3563.11 | 3563.11 | 180.00 | 0.00 | 73.11 | 48.74 | 0.00 | MIDFLOOR_PLENUM_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
183 | TOPFLOOR_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.155 | 0.985 | 89.13 | 89.13 | 89.13 | 180.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
184 | TOPFLOOR_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.155 | 0.985 | 59.42 | 59.42 | 59.42 | 90.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
185 | TOPFLOOR_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.155 | 0.985 | 59.42 | 59.42 | 59.42 | 270.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
186 | TOPFLOOR_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.155 | 0.985 | 89.13 | 89.13 | 89.13 | 0.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
187 | iz-CORE_TOP_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
188 | iz-PERIMETER_TOP_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
189 | iz-PERIMETER_TOP_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
190 | iz-PERIMETER_TOP_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
191 | iz-PERIMETER_TOP_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
192 | iz-DATACENTER_TOP_ZN_6_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_TOP_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
193 | BUILDING_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 3563.11 | 3563.11 | 3563.11 | 180.00 | 0.00 | 73.11 | 48.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
194 | DATACENTER_BOT_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
195 | DATACENTER_BOT_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
196 | DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
197 | DATACENTER_BOT_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
198 | DATACENTER_BOT_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
199 | DATACENTER_BOT_ZN_6_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | iz-DATACENTER_BOT_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
200 | DATACENTER_MID_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
201 | DATACENTER_MID_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
202 | DATACENTER_MID_ZN_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
203 | DATACENTER_MID_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
204 | DATACENTER_MID_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_MID_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
205 | DATACENTER_MID_ZN_6_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | iz-DATACENTER_MID_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
206 | DATACENTER_TOP_ZN_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
207 | DATACENTER_TOP_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
208 | DATACENTER_TOP_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
209 | DATACENTER_TOP_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
210 | DATACENTER_TOP_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_TOP_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
211 | DATACENTER_TOP_ZN_6_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | iz-DATACENTER_TOP_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
212 | DATACENTER_BASEMENT_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR | 0.419 | 0.394 | 39.22 | 39.22 | 39.22 | 0.00 | 90.00 | 16.08 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
213 | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR | 0.419 | 0.394 | 39.22 | 39.22 | 39.22 | 180.00 | 90.00 | 16.08 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
214 | DATACENTER_BASEMENT_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR | 0.419 | 0.394 | 118.87 | 118.87 | 118.87 | 270.00 | 90.00 | 48.74 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
215 | DATACENTER_BASEMENT_ZN_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.87 | 118.87 | 118.87 | 90.00 | 90.00 | 48.74 | 2.44 | 0.00 | BASEMENT_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
216 | DATACENTER_BASEMENT_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 783.68 | 783.68 | 783.68 | 0.00 | 180.00 | 16.08 | 48.74 | 0.00 | DATACENTER_BASEMENT_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
217 | DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | DATACENTER_BOT_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
218 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 419.35 | 419.35 | 419.35 | 180.00 | 0.00 | 10.59 | 39.59 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
219 | PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | PERIMETER_BOT_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
220 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 63.08 | 63.08 | 63.08 | 180.00 | 0.00 | 16.08 | 6.47 | 0.00 | DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
221 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 63.07 | 63.07 | 63.07 | 180.00 | 0.00 | 11.51 | 6.47 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | BASEMENT | RunPeriod: RUNPERIOD 1 | 0.2398321069 | 0.1892100535 | Pass | Pass | 11.1120308240 | 82.8226862454 | Pass | Pass |
2 | CORE_BOTTOM | RunPeriod: RUNPERIOD 1 | 0.1045589970 | 0.1871780720 | Pass | Pass | 0.1615416545 | 0.3665060252 | Pass | Pass |
3 | CORE_MID | RunPeriod: RUNPERIOD 1 | 5.8106353868E-002 | 0.1020932456 | Pass | Pass | 0.1325739979 | 0.3376874094 | Pass | Pass |
4 | CORE_TOP | RunPeriod: RUNPERIOD 1 | 6.3452465085E-002 | 5.2517850327E-002 | Pass | Pass | 0.4490367064 | 0.4881791501 | Pass | Pass |
5 | PERIMETER_BOT_ZN_3 | RunPeriod: RUNPERIOD 1 | 7.4526179479E-002 | 0.1132514436 | Pass | Pass | 0.1607445651 | 0.3651739522 | Pass | Pass |
6 | PERIMETER_BOT_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.2095933023 | 0.3116469998 | Pass | Pass | 0.1639703996 | 0.3707638985 | Pass | Pass |
7 | PERIMETER_BOT_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.3490158677 | 0.6210251966 | Pass | Pass | 0.1640162325 | 0.3660321171 | Pass | Pass |
8 | PERIMETER_BOT_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.2083823595 | 0.3424838792 | Pass | Pass | 0.1618588945 | 0.3600208005 | Pass | Pass |
9 | PERIMETER_MID_ZN_3 | RunPeriod: RUNPERIOD 1 | 4.1474914906E-002 | 4.1553135000E-002 | Pass | Pass | 0.1329820628 | 0.3331875488 | Pass | Pass |
10 | PERIMETER_MID_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.1610704122 | 0.2209159628 | Pass | Pass | 0.1381152888 | 0.3492601306 | Pass | Pass |
11 | PERIMETER_MID_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.3700854842 | 0.6138329508 | Pass | Pass | 0.1492473187 | 0.3785024860 | Pass | Pass |
12 | PERIMETER_MID_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.1305287827 | 0.1850926623 | Pass | Pass | 0.1302404713 | 0.3244659234 | Pass | Pass |
13 | PERIMETER_TOP_ZN_3 | RunPeriod: RUNPERIOD 1 | 0.3072121236 | 0.3517621043 | Pass | Pass | 8.7702887134 | 34.0563929984 | Pass | Pass |
14 | PERIMETER_TOP_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.2522059520 | 0.2805949854 | Pass | Pass | 4.6187217010 | 29.8485735541 | Pass | Pass |
15 | PERIMETER_TOP_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.3102184597 | 0.3364919909 | Pass | Pass | 2.3101209200 | 21.1388091215 | Pass | Pass |
16 | PERIMETER_TOP_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.1899431951 | 0.2146263715 | Pass | Pass | 1.4649550508 | 8.1533573950 | Pass | Pass |
17 | GROUNDFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 2.6293223494E-002 | 3.6516579463E-002 | Pass | Pass | 0.5551429127 | 2.1394683375 | Pass | Pass |
18 | MIDFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 3.8652112360E-002 | 6.1454973586E-002 | Pass | Pass | 0.2036363404 | 0.5835303238 | Pass | Pass |
19 | TOPFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 0.1096609282 | 9.3626831805E-002 | Pass | Pass | 0.5151316435 | 0.6116208961 | Pass | Pass |
20 | DATACENTER_BOT_ZN_6 | RunPeriod: RUNPERIOD 1 | 4.4862008206E-006 | 5.8591940337E-006 | Pass | Pass | 9.2635610018E-003 | 1.2114102428E-002 | Pass | Pass |
21 | DATACENTER_MID_ZN_6 | RunPeriod: RUNPERIOD 1 | 4.9544335376E-006 | 8.5157454939E-006 | Pass | Pass | 0.2756297229 | 1.6962413802 | Pass | Pass |
22 | DATACENTER_TOP_ZN_6 | RunPeriod: RUNPERIOD 1 | 5.4943309360E-002 | 5.0067201046E-002 | Pass | Pass | 3.4691664101E-002 | 0.1248172258 | Pass | Pass |
23 | DATACENTER_BASEMENT_ZN_6 | RunPeriod: RUNPERIOD 1 | 5.8664710698E-005 | 4.9113834535E-005 | Pass | Pass | 8.2411372173E-005 | 1.0835743808E-004 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 08:43:27
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 7910.68 | 195.16 | 0.00 | 29791.65 | 13797.70 | 51695.19 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 08:43:27
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | -17.90 | 0.00 | -17.90 | Wetbulb [C] | 2.50 | 180.00 |
DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 33.90 | 14.80 | 15.00 | Wetbulb [C] | 3.60 | 30.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 11.00 | 10 | |||
Feb | 15.00 | 16 | |||
Mar | 88.00 | 32 | |||
Apr | 159.00 | 54 | |||
May | 30.00 | 24 | |||
Jun | 11.00 | 4 | |||
Jul | 167.00 | 26 | |||
Aug | 33.00 | 24 | |||
Sep | 8.00 | 8 | |||
Oct | 13.00 | 10 | |||
Nov | 12.00 | 22 | |||
Dec | 11.00 | 18 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 08:43:27
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BASEMENT_WALL_EAST | BASEMENT_WALL_EAST_CFACTOR | 1.00 | 0.399 | 0.419 | 118.87 | 118.87 | 90.00 | 90.00 | E |
BASEMENT_WALL_SOUTH | BASEMENT_WALL_SOUTH_CFACTOR | 1.00 | 0.399 | 0.419 | 139.09 | 139.09 | 180.00 | 90.00 | S |
BASEMENT_WALL_NORTH | BASEMENT_WALL_NORTH_CFACTOR | 1.00 | 0.399 | 0.419 | 139.09 | 139.09 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_3_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.846 | 0.969 | 200.61 | 76.91 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_2_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.846 | 0.969 | 133.74 | 52.57 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.846 | 0.969 | 200.61 | 76.91 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_4_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.846 | 0.969 | 133.74 | 52.57 | 270.00 | 90.00 | W |
PERIMETER_MID_ZN_3_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.811 | 0.924 | 2006.06 | 847.11 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_2_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 0.811 | 0.924 | 1337.37 | 564.74 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.811 | 0.924 | 2006.06 | 847.11 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_4_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 0.811 | 0.924 | 1337.37 | 564.74 | 270.00 | 90.00 | W |
PERIMETER_TOP_ZN_3_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 0.985 | 1.155 | 200.61 | 84.71 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_2_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 0.985 | 1.155 | 133.74 | 56.47 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 0.985 | 1.155 | 200.61 | 84.71 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_4_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 0.985 | 1.155 | 133.74 | 56.47 | 270.00 | 90.00 | W |
GROUNDFLOOR_PLENUM_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.846 | 0.969 | 89.13 | 89.13 | 0.00 | 90.00 | N |
GROUNDFLOOR_PLENUM_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.846 | 0.969 | 59.42 | 59.42 | 270.00 | 90.00 | W |
GROUNDFLOOR_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.846 | 0.969 | 89.13 | 89.13 | 180.00 | 90.00 | S |
GROUNDFLOOR_PLENUM_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.846 | 0.969 | 59.42 | 59.42 | 90.00 | 90.00 | E |
MIDFLOOR_PLENUM_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.811 | 0.924 | 891.32 | 891.32 | 0.00 | 90.00 | N |
MIDFLOOR_PLENUM_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 0.811 | 0.924 | 594.21 | 594.21 | 270.00 | 90.00 | W |
MIDFLOOR_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.811 | 0.924 | 891.32 | 891.32 | 180.00 | 90.00 | S |
MIDFLOOR_PLENUM_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 0.811 | 0.924 | 594.21 | 594.21 | 90.00 | 90.00 | E |
TOPFLOOR_PLENUM_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 0.985 | 1.155 | 89.13 | 89.13 | 180.00 | 90.00 | S |
TOPFLOOR_PLENUM_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 0.985 | 1.155 | 59.42 | 59.42 | 90.00 | 90.00 | E |
TOPFLOOR_PLENUM_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 0.985 | 1.155 | 59.42 | 59.42 | 270.00 | 90.00 | W |
TOPFLOOR_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 0.985 | 1.155 | 89.13 | 89.13 | 0.00 | 90.00 | N |
BUILDING_ROOF | NONRES_ROOF | 0.30 | 0.182 | 0.186 | 3563.11 | 3563.11 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_WALL_NORTH | DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR | 1.00 | 0.399 | 0.419 | 39.22 | 39.22 | 0.00 | 90.00 | N |
DATACENTER_BASEMENT_ZN_6_WALL_SOUTH | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR | 1.00 | 0.399 | 0.419 | 39.22 | 39.22 | 180.00 | 90.00 | S |
DATACENTER_BASEMENT_ZN_6_WALL_WEST | DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR | 1.00 | 0.399 | 0.419 | 118.87 | 118.87 | 270.00 | 90.00 | W |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BASEMENT_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 118.87 | 118.87 | 270.00 | 90.00 | W |
BASEMENT_FLOOR | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 2779.43 | 2779.43 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 225.00 | 0.00 | |
PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 250.34 | 250.34 | 180.00 | 0.00 | |
CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 2076.77 | 2076.77 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 250.34 | 250.34 | 180.00 | 0.00 | |
CORE_BOT_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
CORE_BOT_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
CORE_BOT_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 419.30 | 419.30 | 0.00 | 180.00 | |
CORE_BOT_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 2076.82 | 2076.82 | 0.00 | 180.00 | |
CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 180.00 | 0.00 | |
CORE_MID_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 180.00 | 90.00 | S |
CORE_MID_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 270.00 | 90.00 | W |
CORE_MID_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 0.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 90.00 | 90.00 | E |
CORE_MID_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 24961.20 | 24961.20 | 0.00 | 180.00 | |
CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 24961.20 | 24961.20 | 180.00 | 0.00 | |
CORE_TOP_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
CORE_TOP_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
CORE_TOP_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
CORE_TOP_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 2496.12 | 2496.12 | 0.00 | 180.00 | |
CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 250.34 | 250.34 | 0.00 | 180.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 63.07 | 63.07 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
PERIMETER_BOT_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 45.00 | 180.00 | |
PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 225.00 | 0.00 | |
PERIMETER_BOT_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 63.07 | 63.07 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 250.35 | 250.35 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
PERIMETER_BOT_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 315.00 | 180.00 | |
PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 135.00 | 0.00 | |
PERIMETER_MID_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 225.00 | 90.00 | W |
CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 135.00 | 90.00 | S |
DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 3134.13 | 3134.13 | 0.00 | 180.00 | |
PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.13 | 3134.13 | 180.00 | 0.00 | |
PERIMETER_MID_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 315.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 270.00 | 90.00 | W |
PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 225.00 | 90.00 | W |
PERIMETER_MID_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 2019.75 | 2019.75 | 45.00 | 180.00 | |
PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 225.00 | 0.00 | |
PERIMETER_MID_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 45.00 | 90.00 | E |
DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 315.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 3134.20 | 3134.20 | 0.00 | 180.00 | |
PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.20 | 3134.20 | 180.00 | 0.00 | |
PERIMETER_MID_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 135.00 | 90.00 | S |
DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 45.00 | 90.00 | E |
PERIMETER_MID_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 2019.75 | 2019.75 | 315.00 | 180.00 | |
PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 135.00 | 0.00 | |
PERIMETER_TOP_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 313.41 | 313.41 | 0.00 | 180.00 | |
PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 180.00 | 0.00 | |
PERIMETER_TOP_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
INT-PER3S-NE-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
PERIMETER_TOP_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 201.98 | 201.98 | 45.00 | 180.00 | |
PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 225.00 | 0.00 | |
INT-PER3S-NE | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 313.42 | 313.42 | 0.00 | 180.00 | |
PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 180.00 | 0.00 | |
PERIMETER_TOP_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
PERIMETER_TOP_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 201.98 | 201.98 | 315.00 | 180.00 | |
PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 135.00 | 0.00 | |
iz-CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 45.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 315.00 | 180.00 | |
iz-DATACENTER_BOT_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 0.00 | 180.00 | |
GROUNDFLOOR_PLENUM_CEILING | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 3563.11 | 3563.11 | 180.00 | 0.00 | |
iz-CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 24961.20 | 24961.20 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.13 | 3134.13 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 45.00 | 180.00 | |
iz-PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.20 | 3134.20 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 315.00 | 180.00 | |
iz-DATACENTER_MID_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 362.03 | 362.03 | 0.00 | 180.00 | |
MIDFLOOR_PLENUM_CEILING | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 35631.06 | 35631.06 | 180.00 | 0.00 | |
iz-CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 45.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 315.00 | 180.00 | |
iz-DATACENTER_TOP_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 0.00 | 180.00 | |
DATACENTER_BOT_ZN_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
DATACENTER_BOT_ZN_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
DATACENTER_BOT_ZN_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
DATACENTER_BOT_ZN_6_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 36.20 | 36.20 | 0.00 | 180.00 | |
DATACENTER_BOT_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 180.00 | 0.00 | |
DATACENTER_MID_ZN_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 270.00 | 90.00 | W |
DATACENTER_MID_ZN_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 180.00 | 90.00 | S |
DATACENTER_MID_ZN_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 90.00 | 90.00 | E |
DATACENTER_MID_ZN_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 0.00 | 90.00 | N |
DATACENTER_MID_ZN_6_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 362.03 | 362.03 | 0.00 | 180.00 | |
DATACENTER_MID_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 362.03 | 362.03 | 180.00 | 0.00 | |
DATACENTER_TOP_ZN_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
DATACENTER_TOP_ZN_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
DATACENTER_TOP_ZN_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
DATACENTER_TOP_ZN_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
DATACENTER_TOP_ZN_6_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 36.20 | 36.20 | 0.00 | 180.00 | |
DATACENTER_TOP_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 118.87 | 118.87 | 90.00 | 90.00 | E |
DATACENTER_BASEMENT_ZN_6_FLOOR | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 783.68 | 783.68 | 0.00 | 180.00 | |
DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 36.20 | 36.20 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 419.35 | 419.35 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 135.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 63.08 | 63.08 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 63.07 | 63.07 | 180.00 | 0.00 | |
BASEMENT_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 7126.21 | 0.00 | 90.00 | N | ||
CORE_BOTTOM_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 5064.65 | 0.00 | 90.00 | N | ||
CORE_MID_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 50646.53 | 0.00 | 90.00 | N | ||
CORE_TOP_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 5064.65 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.83 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.84 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 6268.26 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 4039.50 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 6268.35 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 4039.48 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.83 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.84 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | WINDOW_U_0.419_SHGC_NORTH_0.4 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.381 | 0.401 | 0.442 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | WINDOW_U_0.419_SHGC_NORTH_0.4 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.381 | 0.401 | 0.442 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | WINDOW_U_0.419_SHGC_NORTH_0.4 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.381 | 0.401 | 0.442 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | WINDOW_U_0.419_SHGC_NORTH_0.4 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.381 | 0.401 | 0.442 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | WINDOW_U_0.419_SHGC_NORTH_0.4 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.381 | 0.401 | 0.442 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | WINDOW_U_0.419_SHGC_EAST_0.4 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 2.381 | 0.401 | 0.442 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | WINDOW_U_0.419_SHGC_EAST_0.4 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 2.381 | 0.401 | 0.442 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | WINDOW_U_0.419_SHGC_EAST_0.4 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 2.381 | 0.401 | 0.442 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | WINDOW_U_0.419_SHGC_SOUTH_0.4 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.381 | 0.401 | 0.442 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | WINDOW_U_0.419_SHGC_SOUTH_0.4 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.381 | 0.401 | 0.442 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | WINDOW_U_0.419_SHGC_SOUTH_0.4 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.381 | 0.401 | 0.442 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | WINDOW_U_0.419_SHGC_SOUTH_0.4 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.381 | 0.401 | 0.442 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | WINDOW_U_0.419_SHGC_SOUTH_0.4 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.381 | 0.401 | 0.442 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | WINDOW_U_0.419_SHGC_WEST_0.4 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 2.381 | 0.401 | 0.442 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | WINDOW_U_0.419_SHGC_WEST_0.4 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 2.381 | 0.401 | 0.442 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | WINDOW_U_0.419_SHGC_WEST_0.4 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 2.381 | 0.401 | 0.442 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.419_SHGC_NORTH_0.4 | 115.90 | 0.00 | 0.00 | 115.90 | 1158.95 | 2.381 | 0.401 | 0.442 | No | PERIMETER_MID_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.419_SHGC_EAST_0.4 | 77.26 | 0.00 | 0.00 | 77.26 | 772.63 | 2.381 | 0.401 | 0.442 | No | PERIMETER_MID_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.419_SHGC_SOUTH_0.4 | 115.90 | 0.00 | 0.00 | 115.90 | 1158.95 | 2.381 | 0.401 | 0.442 | No | PERIMETER_MID_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.419_SHGC_WEST_0.4 | 77.26 | 0.00 | 0.00 | 77.26 | 772.63 | 2.381 | 0.401 | 0.442 | No | PERIMETER_MID_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.419_SHGC_NORTH_0.4 | 115.90 | 0.00 | 0.00 | 115.90 | 115.90 | 2.381 | 0.401 | 0.442 | No | PERIMETER_TOP_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.419_SHGC_EAST_0.4 | 77.26 | 0.00 | 0.00 | 77.26 | 77.26 | 2.381 | 0.401 | 0.442 | No | PERIMETER_TOP_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.419_SHGC_SOUTH_0.4 | 115.90 | 0.00 | 0.00 | 115.90 | 115.90 | 2.381 | 0.401 | 0.442 | No | PERIMETER_TOP_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.419_SHGC_WEST_0.4 | 77.26 | 0.00 | 0.00 | 77.26 | 77.26 | 2.381 | 0.401 | 0.442 | No | PERIMETER_TOP_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
Total or Average | 4635.80 | 2.381 | 0.401 | 0.442 | |||||||||||||||||
North Total or Average | 1390.74 | 2.381 | 0.401 | 0.442 | |||||||||||||||||
Non-North Total or Average | 3245.06 | 2.381 | 0.401 | 0.442 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | SWINGING DOOR_CON | 1.992 | 2.839 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | SWINGING DOOR_CON | 1.992 | 2.839 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | SWINGING DOOR_CON | 1.992 | 2.839 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | SWINGING DOOR_CON | 1.992 | 2.839 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | SWINGING DOOR_CON | 1.992 | 2.839 | 1.95 | PERIMETER_BOT_ZN_2_WALL_EAST |
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | SWINGING DOOR_CON | 1.992 | 2.839 | 1.95 | PERIMETER_BOT_ZN_2_WALL_EAST |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | SWINGING DOOR_CON | 1.992 | 2.839 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | SWINGING DOOR_CON | 1.992 | 2.839 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | SWINGING DOOR_CON | 1.992 | 2.839 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | SWINGING DOOR_CON | 1.992 | 2.839 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | SWINGING DOOR_CON | 1.992 | 2.839 | 1.95 | PERIMETER_BOT_ZN_4_WALL_WEST |
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | SWINGING DOOR_CON | 1.992 | 2.839 | 1.95 | PERIMETER_BOT_ZN_4_WALL_WEST |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 08:43:27
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 08:43:27
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
BASEMENT_LIGHTS | BASEMENT | BASEMENT | GENERAL | 10.2732 | 2779.43 | 28553.72 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 49.04 | 0.0000 | Y | 262.84 |
CORE_BOTTOM_LIGHTS | CORE_BOTTOM | CORE_BOTTOM | GENERAL | 10.2732 | 2496.12 | 25643.24 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 49.04 | 0.0000 | Y | 236.05 |
CORE_MID_LIGHTS | CORE_MID | CORE_MID | GENERAL | 10.2732 | 24961.20 | 256432.45 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 49.04 | 0.0000 | Y | 2360.52 |
CORE_TOP_LIGHTS | CORE_TOP | CORE_TOP | GENERAL | 10.2732 | 2496.12 | 25643.24 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 49.04 | 0.0000 | Y | 236.05 |
PERIMETER_BOT_ZN_3_LIGHTS | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3 | GENERAL | 10.2732 | 313.41 | 3219.77 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 28.68 | 0.0000 | Y | 17.33 |
PERIMETER_BOT_ZN_2_LIGHTS | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2 | GENERAL | 10.2732 | 201.98 | 2074.94 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 28.59 | 0.0000 | Y | 11.13 |
PERIMETER_BOT_ZN_1_LIGHTS | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1 | GENERAL | 10.2732 | 313.42 | 3219.84 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 28.20 | 0.0000 | Y | 17.05 |
PERIMETER_BOT_ZN_4_LIGHTS | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4 | GENERAL | 10.2732 | 201.98 | 2074.94 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 28.21 | 0.0000 | Y | 10.99 |
PERIMETER_MID_ZN_3_LIGHTS | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3 | GENERAL | 10.2732 | 3134.13 | 32197.65 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 28.62 | 0.0000 | Y | 172.99 |
PERIMETER_MID_ZN_2_LIGHTS | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2 | GENERAL | 10.2732 | 2019.75 | 20749.39 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 28.55 | 0.0000 | Y | 111.19 |
PERIMETER_MID_ZN_1_LIGHTS | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1 | GENERAL | 10.2732 | 3134.20 | 32198.36 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 28.17 | 0.0000 | Y | 170.27 |
PERIMETER_MID_ZN_4_LIGHTS | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4 | GENERAL | 10.2732 | 2019.75 | 20749.39 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 28.18 | 0.0000 | Y | 109.75 |
PERIMETER_TOP_ZN_3_LIGHTS | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3 | GENERAL | 10.2732 | 313.41 | 3219.77 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 28.62 | 0.0000 | Y | 17.30 |
PERIMETER_TOP_ZN_2_LIGHTS | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2 | GENERAL | 10.2732 | 201.98 | 2074.94 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 28.55 | 0.0000 | Y | 11.12 |
PERIMETER_TOP_ZN_1_LIGHTS | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1 | GENERAL | 10.2732 | 313.42 | 3219.84 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 28.17 | 0.0000 | Y | 17.03 |
PERIMETER_TOP_ZN_4_LIGHTS | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4 | GENERAL | 10.2732 | 201.98 | 2074.94 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 28.17 | 0.0000 | Y | 10.97 |
DATACENTER_BASEMENT_LIGHTS | DATACENTER_BASEMENT_ZN_6 | DATACENTER_BASEMENT_ZN_6 | GENERAL | 10.2732 | 783.68 | 8050.93 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 49.04 | 0.0000 | Y | 74.11 |
DATACENTER_BOT_LIGHTS | DATACENTER_BOT_ZN_6 | DATACENTER_BOT_ZN_6 | GENERAL | 17.8735 | 36.20 | 647.07 | LightsWired | LTG_SCH_DATACENTER | 56.02 | 168.00 | 54.57 | 0.0000 | Y | 6.63 |
DATACENTER_MID_LIGHTS | DATACENTER_MID_ZN_6 | DATACENTER_MID_ZN_6 | GENERAL | 17.8735 | 362.03 | 6470.68 | LightsWired | LTG_SCH_DATACENTER | 56.02 | 168.00 | 54.57 | 0.0000 | Y | 66.28 |
DATACENTER_TOP_LIGHTS | DATACENTER_TOP_ZN_6 | DATACENTER_TOP_ZN_6 | GENERAL | 17.8735 | 36.20 | 647.07 | LightsWired | LTG_SCH_DATACENTER | 56.02 | 168.00 | 54.57 | 0.0000 | Y | 6.63 |
Interior Lighting Total | 10.3445 | 46320.38 | 479162.15 | 1234.33 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
PERIMETER_BOT_ZN_1_DAYLREFPT1 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_DAYLCTRL | SplitFlux | Stepped | 0.39 | 3219.84 | 1241.89 |
PERIMETER_BOT_ZN_1_DAYLREFPT2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_DAYLCTRL | SplitFlux | Stepped | 0.14 | 3219.84 | 445.95 |
PERIMETER_BOT_ZN_2_DAYLREFPT1 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_DAYLCTRL | SplitFlux | Stepped | 0.39 | 2074.94 | 800.30 |
PERIMETER_BOT_ZN_2_DAYLREFPT2 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_DAYLCTRL | SplitFlux | Stepped | 0.14 | 2074.94 | 287.38 |
PERIMETER_BOT_ZN_3_DAYLREFPT1 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_DAYLCTRL | SplitFlux | Stepped | 0.39 | 3219.77 | 1241.86 |
PERIMETER_BOT_ZN_3_DAYLREFPT2 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_DAYLCTRL | SplitFlux | Stepped | 0.14 | 3219.77 | 445.94 |
PERIMETER_BOT_ZN_4_DAYLREFPT1 | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_DAYLCTRL | SplitFlux | Stepped | 0.39 | 2074.94 | 800.30 |
PERIMETER_BOT_ZN_4_DAYLREFPT2 | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_DAYLCTRL | SplitFlux | Stepped | 0.14 | 2074.94 | 287.38 |
PERIMETER_MID_ZN_1_DAYLREFPT1 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_DAYLCTRL | SplitFlux | Stepped | 0.39 | 3219.84 | 1241.89 |
PERIMETER_MID_ZN_1_DAYLREFPT2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_DAYLCTRL | SplitFlux | Stepped | 0.14 | 3219.84 | 445.95 |
PERIMETER_MID_ZN_2_DAYLREFPT1 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_DAYLCTRL | SplitFlux | Stepped | 0.39 | 2074.94 | 800.30 |
PERIMETER_MID_ZN_2_DAYLREFPT2 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_DAYLCTRL | SplitFlux | Stepped | 0.14 | 2074.94 | 287.38 |
PERIMETER_MID_ZN_3_DAYLREFPT1 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_DAYLCTRL | SplitFlux | Stepped | 0.39 | 3219.77 | 1241.86 |
PERIMETER_MID_ZN_3_DAYLREFPT2 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_DAYLCTRL | SplitFlux | Stepped | 0.14 | 3219.77 | 445.94 |
PERIMETER_MID_ZN_4_DAYLREFPT1 | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_DAYLCTRL | SplitFlux | Stepped | 0.39 | 2074.94 | 800.30 |
PERIMETER_MID_ZN_4_DAYLREFPT2 | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_DAYLCTRL | SplitFlux | Stepped | 0.14 | 2074.94 | 287.38 |
PERIMETER_TOP_ZN_1_DAYLREFPT1 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_DAYLCTRL | SplitFlux | Stepped | 0.39 | 3219.84 | 1241.89 |
PERIMETER_TOP_ZN_1_DAYLREFPT2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_DAYLCTRL | SplitFlux | Stepped | 0.14 | 3219.84 | 445.95 |
PERIMETER_TOP_ZN_2_DAYLREFPT1 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_DAYLCTRL | SplitFlux | Stepped | 0.39 | 2074.94 | 800.30 |
PERIMETER_TOP_ZN_2_DAYLREFPT2 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_DAYLCTRL | SplitFlux | Stepped | 0.14 | 2074.94 | 287.38 |
PERIMETER_TOP_ZN_3_DAYLREFPT1 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_DAYLCTRL | SplitFlux | Stepped | 0.39 | 3219.77 | 1241.86 |
PERIMETER_TOP_ZN_3_DAYLREFPT2 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_DAYLCTRL | SplitFlux | Stepped | 0.14 | 3219.77 | 445.94 |
PERIMETER_TOP_ZN_4_DAYLREFPT1 | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_DAYLCTRL | SplitFlux | Stepped | 0.39 | 2074.94 | 800.30 |
PERIMETER_TOP_ZN_4_DAYLREFPT2 | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_DAYLCTRL | SplitFlux | Stepped | 0.14 | 2074.94 | 287.38 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS_A | 13279.00 | AstronomicalClock | - | 42.26 | 42.26 | 105.34 | |
EXTERIOR_LIGHTS_B | 44301.60 | AstronomicalClock | - | 83.67 | 71.25 | 592.50 | |
Exterior Lighting Total | 57580.60 | 697.85 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 08:43:27
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
BYPASS HEAT EXCHANGER | HeatExchanger:FluidToFluid | 2314941.83 | |||||
HEATSYS1 BOILER | Boiler:HotWater | 2707072.89 | 0.81 | ||||
COOLSYS1 CHILLER1 | Chiller:Electric:ReformulatedEIR | 1186966.84 | 6.28 | 1136083.69 | 5.98 | 6.84 | 23.33 |
COOLSYS1 CHILLER2 | Chiller:Electric:ReformulatedEIR | 1186966.84 | 6.28 | 1136083.69 | 5.98 | 6.84 | 23.33 |
CENTRAL TOWER | FluidCooler:TwoSpeed | 582060.00 | |||||
CENTRAL BOILER | Boiler:HotWater | 597767.97 | 0.80 | ||||
TOWERWATERSYS COOLTOWER 1 | CoolingTower:VariableSpeed | 1410050.16 | |||||
TOWERWATERSYS COOLTOWER 2 | CoolingTower:VariableSpeed | 1410050.16 |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
VAV_BOT WITH REHEAT COOLING COIL | Coil:Cooling:Water | 192210.79 | 264812.85 | 167743.30 | 97069.55 | 0.63 | - | 27197.13 | 275.85 |
VAV_MID WITH REHEAT COOLING COIL | Coil:Cooling:Water | 1823099.00 | 2493022.83 | 1576637.02 | 916385.81 | 0.63 | - | 255533.55 | 2591.76 |
VAV_TOP WITH REHEAT COOLING COIL | Coil:Cooling:Water | 199215.66 | 275671.10 | 174810.56 | 100860.54 | 0.63 | - | 28335.12 | 287.39 |
CAV_BAS COOLING COIL | Coil:Cooling:Water | 105752.34 | 146253.68 | 93953.72 | 52299.96 | 0.64 | - | 14416.08 | 146.22 |
AIRLOOP DATACENTER BASEMENT COOLING COIL | Coil:Cooling:WaterToAirHeatPump:EquationFit | 479130.06 | 251095.38 | 228034.68 | 0.52 | 0.00 | |||
AIRLOOP DATACENTER BOT COOLING COIL | Coil:Cooling:WaterToAirHeatPump:EquationFit | 10972.23 | 5809.80 | 5162.43 | 0.53 | 0.00 | |||
AIRLOOP DATACENTER MID COOLING COIL | Coil:Cooling:WaterToAirHeatPump:EquationFit | 105453.92 | 55828.60 | 49625.32 | 0.53 | 0.00 | |||
AIRLOOP DATACENTER TOP COOLING COIL | Coil:Cooling:WaterToAirHeatPump:EquationFit | 10747.41 | 5689.23 | 5058.18 | 0.53 | 0.00 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
None |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
None |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Water | 16889.04 | 16016.92 | - |
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Water | 453273.89 | 429586.49 | - |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Water | 96322.26 | 91308.40 | - |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 16316.18 | 15465.53 | - |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 11448.46 | 10851.42 | - |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 18509.23 | 17543.89 | - |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 9843.95 | 9328.65 | - |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 252351.22 | 239177.32 | - |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 169747.39 | 160884.94 | - |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 255715.28 | 242365.38 | - |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 163334.33 | 154807.30 | - |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 32045.87 | 30372.15 | - |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 21392.44 | 20275.07 | - |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 32413.93 | 30720.96 | - |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 20947.33 | 19853.23 | - |
VAV_BOT WITH REHEAT HEATING COIL | Coil:Heating:Water | 77297.82 | 56354.90 | - |
VAV_MID WITH REHEAT HEATING COIL | Coil:Heating:Water | 685347.74 | 505951.93 | - |
VAV_TOP WITH REHEAT HEATING COIL | Coil:Heating:Water | 66608.52 | 50596.28 | - |
CAV_BAS HEATING COIL | Coil:Heating:Water | 307268.00 | 238169.85 | - |
AIRLOOP DATACENTER BASEMENT HEATING COIL | Coil:Heating:WaterToAirHeatPump:EquationFit | 479130.06 | 0.00 | |
AIRLOOP DATACENTER BOT HEATING COIL | Coil:Heating:WaterToAirHeatPump:EquationFit | 10972.23 | 0.00 | |
AIRLOOP DATACENTER MID HEATING COIL | Coil:Heating:WaterToAirHeatPump:EquationFit | 105453.92 | 0.00 | |
AIRLOOP DATACENTER TOP HEATING COIL | Coil:Heating:WaterToAirHeatPump:EquationFit | 10747.41 | 0.00 | |
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | Coil:Heating:Electric | 19243.92 | 1.00 | |
AIRLOOP DATACENTER BOT_SUPPHEATCOIL | Coil:Heating:Electric | 888.99 | 1.00 | |
AIRLOOP DATACENTER MID_SUPPHEATCOIL | Coil:Heating:Electric | 8889.90 | 1.00 | |
AIRLOOP DATACENTER TOP_SUPPHEATCOIL | Coil:Heating:Electric | 888.99 | 1.00 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
VAV_BOT WITH REHEAT FAN | Fan:VariableVolume | 0.61 | 1314.72 | 12.55 | 26986.24 | 2149.46 | 1.00 | 1.12 | General | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 |
VAV_MID WITH REHEAT FAN | Fan:VariableVolume | 0.61 | 1314.72 | 117.72 | 253033.85 | 2149.46 | 1.00 | 1.08 | General | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 |
VAV_TOP WITH REHEAT FAN | Fan:VariableVolume | 0.61 | 1314.72 | 13.11 | 28171.98 | 2149.46 | 1.00 | 1.12 | General | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 |
CAV_BAS FAN | Fan:ConstantVolume | 0.60 | 1018.41 | 7.28 | 12271.38 | 1684.71 | 1.00 | 1.15 | General | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
AIRLOOP DATACENTER BASEMENT SUPPLY FAN | Fan:OnOff | 0.62 | 1018.41 | 26.41 | 43381.25 | 1642.33 | 1.00 | 1.14 | General | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 07:10:00 |
AIRLOOP DATACENTER BOT SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.62 | 697.47 | 1120.11 | 1.00 | 1.52 | General | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
AIRLOOP DATACENTER MID SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 5.98 | 6701.45 | 1120.11 | 1.00 | 1.14 | General | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
AIRLOOP DATACENTER TOP SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.61 | 682.76 | 1120.11 | 1.00 | 1.52 | General | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
COOLSYS1 PUMP SECONDARY | Pump:VariableSpeed | Intermittent | 105797.75 | 0.098710 | 16116.32 | 163269.45 | 0.90 | General |
HEATSYS1 PUMP | Pump:VariableSpeed | Intermittent | 180705.70 | 0.023683 | 7132.18 | 301156.09 | 0.90 | General |
COOLSYS1 CHILLER1 PUMP | Pump:ConstantSpeed | Intermittent | 73247.35 | 0.049355 | 5578.94 | 113036.94 | 0.90 | General |
COOLSYS1 CHILLER2 PUMP | Pump:ConstantSpeed | Intermittent | 73247.35 | 0.049355 | 5578.94 | 113036.94 | 0.90 | General |
PLANT CIRC PUMP | Pump:ConstantSpeed | Intermittent | 179045.11 | 0.014848 | 3787.07 | 255050.01 | 0.90 | General |
SWHSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 29891.00 | 0.000440 | 56.21 | 127739.32 | 0.30 | General |
TOWERWATERSYS PUMP | HeaderedPumps:VariableSpeed | Intermittent | 148556.62 | 0.117477 | 29084.75 | 247577.87 | 0.90 | General |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 1.14 | 87921.32 | 0.80 | 0.48 | 0.06 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:43:27
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 81824.74 | 81824.74 | 29.44 | 7.284 | 7.284 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 24.00 | 24.00 | 0.00742 | 22.95 | 0.00546 | 1.200 | 0.00 |
CORE_BOTTOM | 85355.15 | 85355.15 | 34.20 | 7.597 | 7.597 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 24.00 | 24.00 | 0.00736 | 22.95 | 0.00546 | 1.078 | 0.00 |
CORE_MID | 806036.03 | 806036.03 | 322.92 | 71.729 | 71.729 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 24.00 | 24.00 | 0.00739 | 22.95 | 0.00546 | 10.778 | 0.00 |
CORE_TOP | 79067.02 | 79067.02 | 31.68 | 7.036 | 7.036 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 24.00 | 24.00 | 0.00739 | 22.95 | 0.00546 | 1.078 | 0.00 |
PERIMETER_BOT_ZN_3 | 14589.35 | 14589.35 | 46.55 | 1.309 | 1.309 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | 24.00 | 24.00 | 0.00723 | 33.90 | 0.00548 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_2 | 19025.19 | 19025.19 | 94.20 | 1.708 | 1.708 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:40:00 | 24.00 | 24.00 | 0.00712 | 24.82 | 0.00546 | 0.087 | 0.00 |
PERIMETER_BOT_ZN_1 | 20847.66 | 20847.66 | 66.52 | 1.871 | 1.871 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:10:00 | 24.00 | 24.00 | 0.00716 | 33.28 | 0.00547 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_4 | 23783.03 | 23783.03 | 117.75 | 2.135 | 2.135 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 | 24.00 | 24.00 | 0.00709 | 32.03 | 0.00547 | 0.087 | 0.00 |
PERIMETER_MID_ZN_3 | 138714.10 | 138714.10 | 442.59 | 12.450 | 12.450 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | 24.00 | 24.00 | 0.00721 | 33.90 | 0.00548 | 1.353 | 0.00 |
PERIMETER_MID_ZN_2 | 202716.92 | 202716.92 | 1003.67 | 18.194 | 18.194 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | 24.00 | 24.00 | 0.00709 | 25.76 | 0.00546 | 0.872 | 0.00 |
PERIMETER_MID_ZN_1 | 206777.42 | 206777.42 | 659.75 | 18.559 | 18.559 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:20:00 | 24.00 | 24.00 | 0.00714 | 33.41 | 0.00547 | 1.353 | 0.00 |
PERIMETER_MID_ZN_4 | 222932.91 | 222932.91 | 1103.76 | 20.008 | 20.008 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 24.00 | 24.00 | 0.00708 | 31.83 | 0.00547 | 0.872 | 0.00 |
PERIMETER_TOP_ZN_3 | 15667.48 | 15667.48 | 49.99 | 1.406 | 1.406 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 24.00 | 24.00 | 0.00717 | 33.90 | 0.00548 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_2 | 20309.43 | 20309.43 | 100.55 | 1.823 | 1.823 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:10:00 | 24.00 | 24.00 | 0.00708 | 26.18 | 0.00546 | 0.087 | 0.00 |
PERIMETER_TOP_ZN_1 | 22332.83 | 22332.83 | 71.26 | 2.004 | 2.004 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 24.00 | 24.00 | 0.00712 | 33.53 | 0.00547 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_4 | 23500.10 | 23500.10 | 116.35 | 2.109 | 2.109 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 24.00 | 24.00 | 0.00707 | 31.83 | 0.00547 | 0.087 | 0.00 |
DATACENTER_BOT_ZN_6 | 8795.87 | 8795.87 | 242.96 | 0.623 | 0.623 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:50:00 | 27.00 | 27.00 | 0.00708 | 28.50 | 0.00547 | 0.016 | 0.00 |
DATACENTER_MID_ZN_6 | 84512.23 | 84512.23 | 2334.42 | 5.983 | 5.983 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:50:00 | 27.00 | 27.00 | 0.00709 | 28.50 | 0.00547 | 0.156 | 0.00 |
DATACENTER_TOP_ZN_6 | 8610.28 | 8610.28 | 237.84 | 0.610 | 0.610 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:50:00 | 27.00 | 27.00 | 0.00708 | 28.50 | 0.00547 | 0.016 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 373125.54 | 373125.54 | 476.12 | 26.414 | 26.414 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 07:00:00 | 27.00 | 27.00 | 0.00704 | 20.43 | 0.00546 | 0.338 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.000 | 1.200 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:20:00 | 21.00 | 23.63 | 0.00096 | -17.90 | 0.00096 | 1.200 | 0.00 |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.000 | 1.078 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 05:50:00 | 17.60 | 21.01 | 0.00096 | -17.90 | 0.00096 | 1.078 | 0.00 |
CORE_MID | 286780.82 | 286780.82 | 114.89 | 14.943 | 14.943 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00800 | -17.90 | 0.00096 | 10.778 | 0.00 |
CORE_TOP | 67431.53 | 67431.53 | 27.01 | 3.535 | 3.535 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00800 | -17.90 | 0.00096 | 1.078 | 0.00 |
PERIMETER_BOT_ZN_3 | 11420.00 | 11420.00 | 36.44 | 0.599 | 0.599 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00777 | -17.90 | 0.00096 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_2 | 8012.17 | 8012.17 | 39.67 | 0.421 | 0.421 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00780 | -17.90 | 0.00096 | 0.087 | 0.00 |
PERIMETER_BOT_ZN_1 | 12953.09 | 12953.09 | 41.33 | 0.680 | 0.680 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00782 | -17.90 | 0.00096 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_4 | 6357.32 | 6357.32 | 31.48 | 0.333 | 0.333 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00768 | -17.90 | 0.00096 | 0.087 | 0.00 |
PERIMETER_MID_ZN_3 | 176575.83 | 176575.83 | 563.40 | 9.278 | 9.278 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00770 | -17.90 | 0.00096 | 1.353 | 0.00 |
PERIMETER_MID_ZN_2 | 118772.88 | 118772.88 | 588.06 | 6.241 | 6.241 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00771 | -17.90 | 0.00096 | 0.872 | 0.00 |
PERIMETER_MID_ZN_1 | 178927.79 | 178927.79 | 570.89 | 9.402 | 9.402 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00771 | -17.90 | 0.00096 | 1.353 | 0.00 |
PERIMETER_MID_ZN_4 | 114288.95 | 114288.95 | 565.86 | 6.005 | 6.005 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00770 | -17.90 | 0.00096 | 0.872 | 0.00 |
PERIMETER_TOP_ZN_3 | 22420.56 | 22420.56 | 71.54 | 1.179 | 1.179 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00771 | -17.90 | 0.00096 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_2 | 14966.77 | 14966.77 | 74.10 | 0.787 | 0.787 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00771 | -17.90 | 0.00096 | 0.087 | 0.00 |
PERIMETER_TOP_ZN_1 | 22677.90 | 22677.90 | 72.36 | 1.192 | 1.192 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00771 | -17.90 | 0.00096 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_4 | 14655.53 | 14655.53 | 72.56 | 0.770 | 0.770 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00771 | -17.90 | 0.00096 | 0.087 | 0.00 |
DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.016 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 05:30:00 | 18.00 | 25.04 | 0.00163 | -17.90 | 0.00096 | 0.016 | 0.00 |
DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.156 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 05:40:00 | 18.00 | 22.61 | 0.00163 | -17.90 | 0.00096 | 0.156 | 0.00 |
DATACENTER_TOP_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.016 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 05:40:00 | 18.00 | 20.44 | 0.00163 | -17.90 | 0.00096 | 0.016 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.338 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 07:50:00 | 18.00 | 27.00 | 0.00700 | -17.90 | 0.00096 | 0.338 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
VAV_BOT WITH REHEAT | 12.55 | 12.55 | 3.11 | 3.11 | 12.5549 | 3.4710 | 12.5549 | 0.2765 | 0.3000 |
VAV_MID WITH REHEAT | 117.72 | 117.72 | 45.87 | 45.87 | 117.7195 | 45.8700 | 117.7195 | 0.3897 | 0.3000 |
VAV_TOP WITH REHEAT | 13.11 | 13.11 | 7.46 | 7.46 | 13.1065 | 7.4628 | 13.1065 | 0.5694 | 0.3000 |
CAV_BAS | 7.28 | 7.28 | 1.20 | 1.20 | 7.2839 | 7.2839 | 7.2839 | 1.0000 | 1.0000 |
AIRLOOP DATACENTER BASEMENT | 26.41 | 26.41 | 0.34 | 0.34 | 26.4144 | 26.4142 | 26.4144 | 1.0000 | 1.0000 |
AIRLOOP DATACENTER BOT | 0.62 | 0.62 | 0.02 | 0.02 | 0.6227 | 0.6227 | 0.6227 | 1.0000 | 1.0000 |
AIRLOOP DATACENTER MID | 5.98 | 5.98 | 0.16 | 0.16 | 5.9829 | 5.9829 | 5.9829 | 1.0000 | 1.0000 |
AIRLOOP DATACENTER TOP | 0.61 | 0.61 | 0.02 | 0.02 | 0.6095 | 0.6095 | 0.6095 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | 16889.037 | 16889.037 | 2.066449 | 0.00014775 | 340.470 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 05:50:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 05:50:00 | 16889.04 | 16889.04 | 2.066449 | 12.80 | 9.74 | 0.00800000 | 40.00 | 18.76 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 0.0000 | 21.00 | 0.00800000 | 41.9796 | 0.00 | 0.00 | 16951.31 | 16951.31 |
CORE_MID VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | 453273.891 | 453273.891 | 20.371167 | 0.00396544 | 11044.676 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 453273.89 | 453273.89 | 20.371167 | 12.80 | 9.74 | 0.00800000 | 40.00 | 18.76 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 0.0000 | 21.00 | 0.00800000 | 41.9796 | 286780.82 | 0.00 | 454734.88 | 454734.88 |
CORE_TOP VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | 96322.260 | 96322.260 | 3.534909 | 0.00084267 | 2541.781 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 96322.26 | 96322.26 | 3.534909 | 12.80 | 9.74 | 0.00800000 | 40.00 | 18.76 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 0.0000 | 21.00 | 0.00800000 | 41.9796 | 67431.53 | 0.00 | 96649.14 | 96649.14 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | 16316.177 | 16316.177 | 0.599388 | 0.00014274 | 430.357 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 16316.18 | 16316.18 | 0.599388 | 12.80 | 9.74 | 0.00800000 | 40.00 | 18.76 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 0.0000 | 21.00 | 0.00776907 | 40.7851 | 11420.00 | 0.00 | 16370.12 | 16370.12 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | 11448.461 | 11448.461 | 0.420646 | 0.00010016 | 301.941 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 11448.46 | 11448.46 | 0.420646 | 12.80 | 9.74 | 0.00800000 | 40.00 | 18.76 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 0.0000 | 21.00 | 0.00779548 | 40.9218 | 8012.17 | 0.00 | 11486.13 | 11486.13 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | 18509.232 | 18509.232 | 0.680112 | 0.00016193 | 488.149 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 18509.23 | 18509.23 | 0.680112 | 12.80 | 9.74 | 0.00800000 | 40.00 | 18.76 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 0.0000 | 21.00 | 0.00781542 | 41.0250 | 12953.09 | 0.00 | 18570.04 | 18570.04 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | 9843.950 | 9843.950 | 0.426916 | 0.00008612 | 242.825 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 9843.95 | 9843.95 | 0.426916 | 12.80 | 9.74 | 0.00800000 | 40.00 | 18.76 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 0.0000 | 21.00 | 0.00768147 | 40.3315 | 6357.32 | 0.00 | 9874.87 | 9874.87 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | 252351.225 | 252351.225 | 9.278186 | 0.00220768 | 6653.469 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 252351.22 | 252351.22 | 9.278186 | 12.80 | 9.74 | 0.00800000 | 40.00 | 18.76 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 0.0000 | 21.00 | 0.00770430 | 40.4508 | 176575.83 | 0.00 | 253166.91 | 253166.91 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | 169747.391 | 169747.391 | 6.241477 | 0.00148502 | 4475.419 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 169747.39 | 169747.39 | 6.241477 | 12.80 | 9.74 | 0.00800000 | 40.00 | 18.76 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 0.0000 | 21.00 | 0.00770716 | 40.4657 | 118772.88 | 0.00 | 170295.17 | 170295.17 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | 255715.277 | 255715.277 | 9.402042 | 0.00223711 | 6742.110 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 255715.28 | 255715.28 | 9.402042 | 12.80 | 9.74 | 0.00800000 | 40.00 | 18.76 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 0.0000 | 21.00 | 0.00770815 | 40.4707 | 178927.79 | 0.00 | 256541.43 | 256541.43 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | 163334.333 | 163334.333 | 6.005405 | 0.00142892 | 4306.426 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 163334.33 | 163334.33 | 6.005405 | 12.80 | 9.74 | 0.00800000 | 40.00 | 18.76 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 0.0000 | 21.00 | 0.00769588 | 40.4072 | 114288.95 | 0.00 | 163862.05 | 163862.05 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | 32045.868 | 32045.868 | 1.178578 | 0.00028035 | 844.804 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 32045.87 | 32045.87 | 1.178578 | 12.80 | 9.74 | 0.00800000 | 40.00 | 18.76 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 0.0000 | 21.00 | 0.00771091 | 40.4857 | 22420.56 | 0.00 | 32148.63 | 32148.63 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | 21392.439 | 21392.439 | 0.786800 | 0.00018715 | 563.944 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21392.44 | 21392.44 | 0.786800 | 12.80 | 9.74 | 0.00800000 | 40.00 | 18.76 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 0.0000 | 21.00 | 0.00771119 | 40.4873 | 14966.77 | 0.00 | 21460.96 | 21460.96 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | 32413.934 | 32413.934 | 1.192129 | 0.00028357 | 854.502 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 32413.93 | 32413.93 | 1.192129 | 12.80 | 9.74 | 0.00800000 | 40.00 | 18.76 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 0.0000 | 21.00 | 0.00771405 | 40.5020 | 22677.90 | 0.00 | 32517.84 | 32517.84 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | 20947.331 | 20947.331 | 0.770418 | 0.00018326 | 552.214 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 20947.33 | 20947.33 | 0.770418 | 12.80 | 9.74 | 0.00800000 | 40.00 | 18.76 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 0.0000 | 21.00 | 0.00770553 | 40.4579 | 14655.53 | 0.00 | 21014.45 | 21014.45 |
VAV_BOT WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | VAV_BOT WITH REHEAT | 192210.787 | -999.000 | 12.554864 | 0.00817709 | -999.000 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 192210.79 | 192210.79 | 12.554864 | 26.03 | 13.64 | 0.00692696 | 10.64 | 7.78 | 0.00692696 | 33.90 | 0.00547527 | 15.07 | 20.2168 | 24.00 | 0.00730155 | 31.9674 | 137873.94 | 0.00 | 171779.27 | 171779.27 |
VAV_BOT WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoopHVAC | VAV_BOT WITH REHEAT | 77297.816 | 77297.816 | 3.766459 | 0.00067624 | 1239.365 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 07:20:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 77297.82 | 77297.82 | 3.766459 | -8.09 | -8.18 | 0.00228754 | 12.80 | 9.74 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 67.3893 | 21.02 | 0.00570330 | 30.0066 | 33236.11 | 0.00 | 68131.75 | 68131.75 |
VAV_MID WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | VAV_MID WITH REHEAT | 1823098.996 | -999.000 | 117.719482 | 0.07755884 | -999.000 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 1823099.00 | 1823099.00 | 117.719482 | 26.21 | 13.68 | 0.00690412 | 10.64 | 7.76 | 0.00690412 | 33.90 | 0.00547527 | 15.07 | 21.5614 | 24.00 | 0.00731454 | 32.0235 | 1267307.78 | 0.00 | 1626612.04 | 1626612.04 |
VAV_MID WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoopHVAC | VAV_MID WITH REHEAT | 685347.739 | 685347.739 | 35.315844 | 0.00599572 | 11052.281 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 22:20:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 685347.74 | 685347.74 | 35.315844 | -6.96 | -6.96 | 0.00284621 | 12.80 | 9.74 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 71.8713 | 18.18 | 0.00759338 | 47.5166 | 387581.74 | 0.00 | 611819.28 | 611819.28 |
VAV_TOP WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | VAV_TOP WITH REHEAT | 199215.661 | -999.000 | 13.106511 | 0.00847509 | -999.000 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | 199215.66 | 199215.66 | 13.106511 | 25.92 | 13.60 | 0.00692107 | 10.64 | 7.78 | 0.00692107 | 33.90 | 0.00547527 | 15.07 | 19.3659 | 24.00 | 0.00726896 | 31.8262 | 145804.46 | 0.00 | 177815.56 | 177815.56 |
VAV_TOP WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoopHVAC | VAV_TOP WITH REHEAT | 66608.524 | 66608.524 | 3.931953 | 0.00058272 | 1088.969 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 22:30:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 66608.52 | 66608.52 | 3.931953 | -4.45 | -4.45 | 0.00331737 | 12.80 | 9.74 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 64.5529 | 17.26 | 0.00758799 | 50.2978 | 44579.70 | 0.00 | 61198.58 | 61198.58 |
CAV_BAS COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | CAV_BAS | 105752.342 | -999.000 | 7.283949 | 0.00449895 | -999.000 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 105752.34 | 105752.34 | 7.283949 | 25.70 | 13.67 | 0.00709867 | 11.11 | 8.16 | 0.00709867 | 33.16 | 0.00547412 | 14.83 | 16.4767 | 24.00 | 0.00746851 | 32.6901 | 72105.48 | 0.00 | 95147.56 | 95147.56 |
CAV_BAS HEATING COIL | Coil:Heating:Water | AirLoopHVAC | CAV_BAS | 307268.000 | 307268.000 | 7.283949 | 0.00268811 | 6711.492 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 307268.00 | 307268.00 | 7.283949 | -2.95 | -7.30 | 0.00095524 | 40.00 | 18.76 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 16.4767 | 23.74 | 0.00095524 | 4.2906 | 0.00 | 0.00 | 251262.81 | 251262.81 |
AIRLOOP DATACENTER BASEMENT COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | 479130.061 | 251095.381 | 26.414423 | 0.01173386 | -999.000 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 07:10:00 | 407244.56 | 406278.26 | -999.0 | 28.80 | 14.64 | 0.00702190 | 12.80 | 8.76 | 0.00700000 | 33.90 | 0.00547527 | 15.07 | -999.0000 | 27.00 | 0.00704199 | 25.8125 | 372720.89 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BOT COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER BOT | 10972.228 | 5809.801 | 0.622682 | 0.00026871 | -999.000 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:50:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:50:00 | 9275.89 | 9233.21 | -999.0 | 28.20 | 14.46 | 0.00704149 | 12.80 | 8.76 | 0.00700000 | 28.50 | 0.00546700 | 13.26 | -999.0000 | 27.00 | 0.00708204 | 25.9557 | 8795.87 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER MID COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER MID | 105453.923 | 55828.603 | 5.982861 | 0.00258256 | -999.000 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:50:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:50:00 | 89155.16 | 88729.50 | -999.0 | 28.20 | 14.47 | 0.00704306 | 12.80 | 8.76 | 0.00700000 | 28.50 | 0.00546700 | 13.26 | -999.0000 | 27.00 | 0.00708534 | 25.9677 | 84512.23 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER TOP COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER TOP | 10747.415 | 5689.233 | 0.609545 | 0.00026320 | -999.000 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:50:00 | 9086.92 | 9044.43 | -999.0 | 28.21 | 14.47 | 0.00704218 | 12.80 | 8.76 | 0.00700000 | 28.87 | 0.00546756 | 13.38 | -999.0000 | 27.00 | 0.00708363 | 25.9615 | 8607.72 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BASEMENT HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | 479130.061 | 479130.061 | 26.414423 | 0.01173386 | -999.000 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 479130.06 | 479130.06 | 26.414423 | -17.90 | -17.90 | 0.00095524 | 40.00 | 18.76 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 1.2811 | 27.00 | 0.00700000 | 25.6559 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BOT HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER BOT | 10972.228 | 10972.228 | 0.622682 | 0.00026871 | -999.000 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 10972.23 | 10972.23 | 0.622682 | -17.90 | -17.90 | 0.00095524 | 40.00 | 18.76 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 2.5105 | 25.70 | 0.00162734 | 6.4937 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER MID HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER MID | 105453.923 | 105453.923 | 5.982861 | 0.00258256 | -999.000 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 105453.92 | 105453.92 | 5.982861 | -17.90 | -17.90 | 0.00095524 | 40.00 | 18.76 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 2.6129 | 23.78 | 0.00162735 | 7.2860 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER TOP HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER TOP | 10747.415 | 10747.415 | 0.609545 | 0.00026320 | -999.000 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 10747.41 | 10747.41 | 0.609545 | -17.90 | -17.90 | 0.00095524 | 40.00 | 18.76 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 2.5646 | 22.50 | 0.00162693 | 7.8690 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | 19243.924 | 19243.924 | -999.0 | -999.0 | -999.000 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 19243.92 | 19243.92 | 26.414423 | -0.23 | -0.23 | 0.00692256 | 40.00 | 18.76 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 1.2811 | 27.00 | 0.00700000 | 25.6559 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BOT_SUPPHEATCOIL | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER BOT | 888.990 | 888.990 | -999.0 | -999.0 | -999.000 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 888.99 | 888.99 | 0.622682 | -0.45 | -4.71 | 0.00161046 | 40.00 | 18.76 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 2.5105 | 25.70 | 0.00162734 | 6.4937 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER MID_SUPPHEATCOIL | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER MID | 8889.896 | 8889.896 | -999.0 | -999.0 | -999.000 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 8889.90 | 8889.90 | 5.982861 | -0.47 | -4.72 | 0.00160979 | 40.00 | 18.76 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 2.6129 | 23.78 | 0.00162735 | 7.2860 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER TOP_SUPPHEATCOIL | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER TOP | 888.990 | 888.990 | -999.0 | -999.0 | -999.000 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 888.99 | 888.99 | 0.609545 | -0.46 | -4.72 | 0.00160970 | 40.00 | 18.76 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 2.5646 | 22.50 | 0.00162693 | 7.8690 | 0.00 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 08:43:27
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
CORE_BOTTOM VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | CORE_BOTTOM | N/A | N/A | N/A | Yes | Yes | Yes | No | 16889.037 | 16889.037 | 2.066449 | 0.00014775 | 340.470 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 23.68023867 | 54.44 | 82.22 | 27.78 | 2761553.80 | 0.6116 | 0.623886 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 05:50:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 05:50:00 | Sensible | 16889.04 | 16889.04 | 1.0000 | 2.01982463 | 2.066449 | 12.80 | 9.74 | 0.00800000 | 33059.8 | 40.00 | 18.76 | 0.00800000 | 60796.0 | 0.14773759 | 60.00 | 32.22 | 27.78 | 0.000 | 16889.04 | -17.90 | 0.00095524 | -17.90 | 0.00000000 | 0.0000 | 21.00 | 0.00800000 | 21.00 | 0.00800000 | 41.9796 | 0.00 | 0.00 | 16951.31 | 16951.31 | 2.01982463 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 21.03 | 14.86 | 0.00800000 | 41452.3 | |
CORE_MID VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | CORE_MID | N/A | N/A | N/A | Yes | Yes | Yes | No | 453273.891 | 453273.891 | 20.371167 | 0.00396544 | 11044.676 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 23.68023867 | 54.44 | 82.22 | 27.78 | 2761553.80 | 16.4137 | 16.744059 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 453273.89 | 453273.89 | 1.0000 | 19.91154511 | 20.371167 | 12.80 | 9.74 | 0.00800000 | 33059.8 | 40.00 | 18.76 | 0.00800000 | 60796.0 | 3.96503322 | 60.00 | 32.22 | 27.78 | 0.000 | 453273.89 | -17.90 | 0.00095524 | -17.90 | 0.00000000 | 0.0000 | 20.87 | 0.00800000 | 21.00 | 0.00800000 | 41.9796 | 286780.82 | 0.00 | 454734.88 | 454734.88 | 19.91154511 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 35.20 | 19.72 | 0.00800000 | 55897.6 | |
CORE_TOP VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | CORE_TOP | N/A | N/A | N/A | Yes | Yes | Yes | No | 96322.260 | 96322.260 | 3.534909 | 0.00084267 | 2541.781 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 23.68023867 | 54.44 | 82.22 | 27.78 | 2761553.80 | 3.4880 | 3.558170 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 96322.26 | 96322.26 | 1.0000 | 3.45515287 | 3.534909 | 12.80 | 9.74 | 0.00800000 | 33059.8 | 40.00 | 18.76 | 0.00800000 | 60796.0 | 0.84258319 | 60.00 | 32.22 | 27.78 | 0.000 | 96322.26 | -17.90 | 0.00095524 | -17.90 | 0.00000000 | 0.0000 | 20.91 | 0.00800000 | 21.00 | 0.00800000 | 41.9796 | 67431.53 | 0.00 | 96649.14 | 96649.14 | 3.45515287 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.23 | 21.25 | 0.00800000 | 61032.3 | |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | PERIMETER_BOT_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 16316.177 | 16316.177 | 0.599388 | 0.00014274 | 430.357 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 23.68023867 | 54.44 | 82.22 | 27.78 | 2761553.80 | 0.5908 | 0.602724 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 16316.18 | 16316.18 | 1.0000 | 0.58586484 | 0.599388 | 12.80 | 9.74 | 0.00800000 | 33059.8 | 40.00 | 18.76 | 0.00800000 | 60796.0 | 0.14272647 | 60.00 | 32.22 | 27.78 | 0.000 | 16316.18 | -17.90 | 0.00095524 | -17.90 | 0.00000000 | 0.0000 | 20.95 | 0.00776907 | 21.00 | 0.00776907 | 40.7851 | 11420.00 | 0.00 | 16370.12 | 16370.12 | 0.58586484 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.20 | 21.24 | 0.00800000 | 61001.6 | |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | PERIMETER_BOT_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 11448.461 | 11448.461 | 0.420646 | 0.00010016 | 301.941 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 23.68023867 | 54.44 | 82.22 | 27.78 | 2761553.80 | 0.4146 | 0.422909 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 11448.46 | 11448.46 | 1.0000 | 0.41115521 | 0.420646 | 12.80 | 9.74 | 0.00800000 | 33059.8 | 40.00 | 18.76 | 0.00800000 | 60796.0 | 0.10014591 | 60.00 | 32.22 | 27.78 | 0.000 | 11448.46 | -17.90 | 0.00095524 | -17.90 | 0.00000000 | 0.0000 | 20.95 | 0.00779548 | 21.00 | 0.00779548 | 40.9218 | 8012.17 | 0.00 | 11486.13 | 11486.13 | 0.41115521 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.20 | 21.24 | 0.00800000 | 60996.1 | |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | PERIMETER_BOT_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 18509.232 | 18509.232 | 0.680112 | 0.00016193 | 488.149 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 23.68023867 | 54.44 | 82.22 | 27.78 | 2761553.80 | 0.6702 | 0.683736 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 18509.23 | 18509.23 | 1.0000 | 0.66476687 | 0.680112 | 12.80 | 9.74 | 0.00800000 | 33059.8 | 40.00 | 18.76 | 0.00800000 | 60796.0 | 0.16191032 | 60.00 | 32.22 | 27.78 | 0.000 | 18509.23 | -17.90 | 0.00095524 | -17.90 | 0.00000000 | 0.0000 | 20.95 | 0.00781542 | 21.00 | 0.00781542 | 41.0250 | 12953.09 | 0.00 | 18570.04 | 18570.04 | 0.66476687 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.19 | 21.24 | 0.00800000 | 60994.5 | |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | PERIMETER_BOT_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 9843.950 | 9843.950 | 0.426916 | 0.00008612 | 242.825 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 23.68023867 | 54.44 | 82.22 | 27.78 | 2761553.80 | 0.3565 | 0.363638 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 9843.95 | 9843.95 | 1.0000 | 0.41728337 | 0.426916 | 12.80 | 9.74 | 0.00800000 | 33059.8 | 40.00 | 18.76 | 0.00800000 | 60796.0 | 0.08611038 | 60.00 | 32.22 | 27.78 | 0.000 | 9843.95 | -17.90 | 0.00095524 | -17.90 | 0.00000000 | 0.0000 | 20.95 | 0.00768147 | 21.00 | 0.00768147 | 40.3315 | 6357.32 | 0.00 | 9874.87 | 9874.87 | 0.41728337 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 36.01 | 19.97 | 0.00800000 | 56724.5 | |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | PERIMETER_MID_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 252351.225 | 252351.225 | 9.278186 | 0.00220768 | 6653.469 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 23.68023867 | 54.44 | 82.22 | 27.78 | 2761553.80 | 9.1380 | 9.321922 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 252351.22 | 252351.22 | 1.0000 | 9.06884844 | 9.278186 | 12.80 | 9.74 | 0.00800000 | 33059.8 | 40.00 | 18.76 | 0.00800000 | 60796.0 | 2.20745340 | 60.00 | 32.22 | 27.78 | 0.000 | 252351.22 | -17.90 | 0.00095524 | -17.90 | 0.00000000 | 0.0000 | 20.95 | 0.00770430 | 21.00 | 0.00770430 | 40.4508 | 176575.83 | 0.00 | 253166.91 | 253166.91 | 9.06884844 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.18 | 21.23 | 0.00800000 | 60975.9 | |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | PERIMETER_MID_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 169747.391 | 169747.391 | 6.241477 | 0.00148502 | 4475.419 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 23.68023867 | 54.44 | 82.22 | 27.78 | 2761553.80 | 6.1468 | 6.270514 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 169747.39 | 169747.39 | 1.0000 | 6.10065403 | 6.241477 | 12.80 | 9.74 | 0.00800000 | 33059.8 | 40.00 | 18.76 | 0.00800000 | 60796.0 | 1.48487274 | 60.00 | 32.22 | 27.78 | 0.000 | 169747.39 | -17.90 | 0.00095524 | -17.90 | 0.00000000 | 0.0000 | 20.95 | 0.00770716 | 21.00 | 0.00770716 | 40.4657 | 118772.88 | 0.00 | 170295.17 | 170295.17 | 6.10065403 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.17 | 21.23 | 0.00800000 | 60974.1 | |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | PERIMETER_MID_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 255715.277 | 255715.277 | 9.402042 | 0.00223711 | 6742.110 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 23.68023867 | 54.44 | 82.22 | 27.78 | 2761553.80 | 9.2598 | 9.446191 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 255715.28 | 255715.28 | 1.0000 | 9.18990911 | 9.402042 | 12.80 | 9.74 | 0.00800000 | 33059.8 | 40.00 | 18.76 | 0.00800000 | 60796.0 | 2.23688059 | 60.00 | 32.22 | 27.78 | 0.000 | 255715.28 | -17.90 | 0.00095524 | -17.90 | 0.00000000 | 0.0000 | 20.95 | 0.00770815 | 21.00 | 0.00770815 | 40.4707 | 178927.79 | 0.00 | 256541.43 | 256541.43 | 9.18990911 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.18 | 21.23 | 0.00800000 | 60975.4 | |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | PERIMETER_MID_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 163334.333 | 163334.333 | 6.005405 | 0.00142892 | 4306.426 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 23.68023867 | 54.44 | 82.22 | 27.78 | 2761553.80 | 5.9146 | 6.033614 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 163334.33 | 163334.33 | 1.0000 | 5.86990850 | 6.005405 | 12.80 | 9.74 | 0.00800000 | 33059.8 | 40.00 | 18.76 | 0.00800000 | 60796.0 | 1.42877424 | 60.00 | 32.22 | 27.78 | 0.000 | 163334.33 | -17.90 | 0.00095524 | -17.90 | 0.00000000 | 0.0000 | 20.95 | 0.00769588 | 21.00 | 0.00769588 | 40.4072 | 114288.95 | 0.00 | 163862.05 | 163862.05 | 5.86990850 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.18 | 21.23 | 0.00800000 | 60975.4 | |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | PERIMETER_TOP_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 32045.868 | 32045.868 | 1.178578 | 0.00028035 | 844.804 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 23.68023867 | 54.44 | 82.22 | 27.78 | 2761553.80 | 1.1604 | 1.183783 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 32045.87 | 32045.87 | 1.0000 | 1.15198666 | 1.178578 | 12.80 | 9.74 | 0.00800000 | 33059.8 | 40.00 | 18.76 | 0.00800000 | 60796.0 | 0.28032263 | 60.00 | 32.22 | 27.78 | 0.000 | 32045.87 | -17.90 | 0.00095524 | -17.90 | 0.00000000 | 0.0000 | 20.95 | 0.00771091 | 21.00 | 0.00771091 | 40.4857 | 22420.56 | 0.00 | 32148.63 | 32148.63 | 1.15198666 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.17 | 21.23 | 0.00800000 | 60966.9 | |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | PERIMETER_TOP_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 21392.439 | 21392.439 | 0.786800 | 0.00018715 | 563.944 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 23.68023867 | 54.44 | 82.22 | 27.78 | 2761553.80 | 0.7747 | 0.790242 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 21392.44 | 21392.44 | 1.0000 | 0.76904766 | 0.786800 | 12.80 | 9.74 | 0.00800000 | 33059.8 | 40.00 | 18.76 | 0.00800000 | 60796.0 | 0.18713130 | 60.00 | 32.22 | 27.78 | 0.000 | 21392.44 | -17.90 | 0.00095524 | -17.90 | 0.00000000 | 0.0000 | 20.95 | 0.00771119 | 21.00 | 0.00771119 | 40.4873 | 14966.77 | 0.00 | 21460.96 | 21460.96 | 0.76904766 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.17 | 21.23 | 0.00800000 | 60965.7 | |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | PERIMETER_TOP_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 32413.934 | 32413.934 | 1.192129 | 0.00028357 | 854.502 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 23.68023867 | 54.44 | 82.22 | 27.78 | 2761553.80 | 1.1738 | 1.197379 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 32413.93 | 32413.93 | 1.0000 | 1.16523184 | 1.192129 | 12.80 | 9.74 | 0.00800000 | 33059.8 | 40.00 | 18.76 | 0.00800000 | 60796.0 | 0.28354231 | 60.00 | 32.22 | 27.78 | 0.000 | 32413.93 | -17.90 | 0.00095524 | -17.90 | 0.00000000 | 0.0000 | 20.95 | 0.00771405 | 21.00 | 0.00771405 | 40.5020 | 22677.90 | 0.00 | 32517.84 | 32517.84 | 1.16523184 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.17 | 21.23 | 0.00800000 | 60966.6 | |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | PERIMETER_TOP_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 20947.331 | 20947.331 | 0.770418 | 0.00018326 | 552.214 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 23.68023867 | 54.44 | 82.22 | 27.78 | 2761553.80 | 0.7585 | 0.773800 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 20947.33 | 20947.33 | 1.0000 | 0.75303508 | 0.770418 | 12.80 | 9.74 | 0.00800000 | 33059.8 | 40.00 | 18.76 | 0.00800000 | 60796.0 | 0.18323770 | 60.00 | 32.22 | 27.78 | 0.000 | 20947.33 | -17.90 | 0.00095524 | -17.90 | 0.00000000 | 0.0000 | 20.95 | 0.00770553 | 21.00 | 0.00770553 | 40.4579 | 14655.53 | 0.00 | 21014.45 | 21014.45 | 0.75303508 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.17 | 21.23 | 0.00800000 | 60966.2 | |
VAV_BOT WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV_BOT WITH REHEAT | CORE_BOTTOM; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 192210.787 | -999.000 | 12.554864 | 0.00817709 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1017.7169 | 1004.8586 | 0.9774 | VAV_BOT WITH REHEAT FAN | Fan:VariableVolume | 12.554864 | 12.27159648 | 4197.9300 | 999.8980 | 98.69991139 | 12.27 | 6.67 | 5.60 | 2320277.79 | 8.2840 | 8.283956 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | Sensible | 192210.79 | 192210.79 | 1.0000 | 12.27159648 | 12.554864 | 26.03 | 13.64 | 0.00692696 | 43814.7 | 10.64 | 7.78 | 0.00692696 | 28151.6 | 8.17625707 | 6.67 | 12.27 | 5.60 | 26986.236 | 165224.55 | 33.90 | 0.00547527 | 15.07 | 2.53819000 | 20.2168 | 24.00 | 0.00730155 | 24.00 | 0.00730155 | 31.9674 | 137873.94 | 0.00 | 171779.27 | 171779.27 | 12.27159648 | 26.03 | 15.74 | 0.00692696 | 43814.7 | 12.28 | 10.25 | 0.00692696 | 29816.6 | |
VAV_BOT WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV_BOT WITH REHEAT | CORE_BOTTOM; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 77297.816 | 77297.816 | 3.766459 | 0.00067624 | 1239.365 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | VAV_BOT WITH REHEAT FAN | Fan:VariableVolume | 12.554864 | 12.27159648 | 4197.9300 | 999.8980 | 23.68023867 | 54.44 | 82.22 | 27.78 | 2761553.80 | 2.7991 | 2.855402 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 07:20:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 77297.82 | 77297.82 | 1.0000 | 3.68147894 | 3.766459 | -8.09 | -8.18 | 0.00228754 | -2447.5 | 12.80 | 9.74 | 0.00800000 | 33059.8 | 0.67616603 | 60.00 | 32.22 | 27.78 | 0.000 | 77297.82 | -17.90 | 0.00095524 | -17.90 | 2.53819000 | 67.3893 | 12.17 | 0.00504070 | 21.02 | 0.00570330 | 30.0066 | 33236.11 | 0.00 | 68131.75 | 68131.75 | 3.68147894 | 2.80 | -0.74 | 0.00228754 | 8546.4 | 21.14 | 9.12 | 0.00228754 | 27053.1 | |
VAV_MID WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV_MID WITH REHEAT | CORE_MID; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 1823098.996 | -999.000 | 117.719482 | 0.07755884 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1017.6744 | 1004.8586 | 0.9774 | VAV_MID WITH REHEAT FAN | Fan:VariableVolume | 117.719482 | 115.06344908 | 4197.9300 | 999.8980 | 98.69991139 | 12.27 | 6.67 | 5.60 | 2320277.79 | 78.5724 | 78.572445 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | Sensible | 1823099.00 | 1823099.00 | 1.0000 | 115.06344908 | 117.719482 | 26.21 | 13.68 | 0.00690412 | 43938.2 | 10.64 | 7.76 | 0.00690412 | 28093.9 | 77.55093396 | 6.67 | 12.27 | 5.60 | 253033.854 | 1570065.14 | 33.90 | 0.00547527 | 15.07 | 25.38195000 | 21.5614 | 24.00 | 0.00731454 | 24.00 | 0.00731454 | 32.0235 | 1267307.78 | 0.00 | 1626612.04 | 1626612.04 | 115.06344908 | 26.21 | 15.79 | 0.00690412 | 43938.2 | 12.32 | 10.24 | 0.00690412 | 29801.6 | |
VAV_MID WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV_MID WITH REHEAT | CORE_MID; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 685347.739 | 685347.739 | 35.315844 | 0.00599572 | 11052.281 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | VAV_MID WITH REHEAT FAN | Fan:VariableVolume | 117.719482 | 115.06344908 | 4197.9300 | 999.8980 | 23.68023867 | 54.44 | 82.22 | 27.78 | 2761553.80 | 24.8175 | 25.316930 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 22:20:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 685347.74 | 685347.74 | 1.0000 | 34.51903472 | 35.315844 | -6.96 | -6.96 | 0.00284621 | 89.5 | 12.80 | 9.74 | 0.00800000 | 33059.8 | 5.99510937 | 60.00 | 32.22 | 27.78 | 0.000 | 685347.74 | -17.90 | 0.00095524 | -17.90 | 25.38195000 | 71.8713 | 21.00 | 0.00767781 | 18.18 | 0.00759338 | 47.5166 | 387581.74 | 0.00 | 611819.28 | 611819.28 | 34.51903472 | 2.80 | 0.30 | 0.00284621 | 9946.6 | 20.35 | 9.38 | 0.00284621 | 27670.7 | |
VAV_TOP WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV_TOP WITH REHEAT | CORE_TOP; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 199215.661 | -999.000 | 13.106511 | 0.00847509 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1017.7059 | 1004.8586 | 0.9774 | VAV_TOP WITH REHEAT FAN | Fan:VariableVolume | 13.106511 | 12.81079675 | 4197.9300 | 999.8980 | 98.69991139 | 12.27 | 6.67 | 5.60 | 2320277.79 | 8.5859 | 8.585854 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | Sensible | 199215.66 | 199215.66 | 1.0000 | 12.81079675 | 13.106511 | 25.92 | 13.60 | 0.00692107 | 43687.3 | 10.64 | 7.78 | 0.00692107 | 28136.7 | 8.47423019 | 6.67 | 12.27 | 5.60 | 28171.981 | 171043.68 | 33.90 | 0.00547527 | 15.07 | 2.53819000 | 19.3659 | 24.00 | 0.00726896 | 24.00 | 0.00726896 | 31.8262 | 145804.46 | 0.00 | 177815.56 | 177815.56 | 12.81079675 | 25.92 | 15.70 | 0.00692107 | 43687.3 | 12.28 | 10.25 | 0.00692107 | 29807.2 | |
VAV_TOP WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV_TOP WITH REHEAT | CORE_TOP; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 66608.524 | 66608.524 | 3.931953 | 0.00058272 | 1088.969 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | VAV_TOP WITH REHEAT FAN | Fan:VariableVolume | 13.106511 | 12.81079675 | 4197.9300 | 999.8980 | 23.68023867 | 54.44 | 82.22 | 27.78 | 2761553.80 | 2.4120 | 2.460537 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 22:30:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 66608.52 | 66608.52 | 1.0000 | 3.84323902 | 3.931953 | -4.45 | -4.45 | 0.00331737 | 3800.0 | 12.80 | 9.74 | 0.00800000 | 33059.8 | 0.58266098 | 60.00 | 32.22 | 27.78 | 0.000 | 66608.52 | -17.90 | 0.00095524 | -17.90 | 2.53819000 | 64.5529 | 20.05 | 0.00761906 | 17.26 | 0.00758799 | 50.2978 | 44579.70 | 0.00 | 61198.58 | 61198.58 | 3.84323902 | 2.80 | 0.98 | 0.00331737 | 11127.4 | 18.55 | 9.10 | 0.00331737 | 27051.1 | |
CAV_BAS COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | CAV_BAS | BASEMENT | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 105752.342 | -999.000 | 7.283949 | 0.00449895 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1018.0361 | 1004.8586 | 0.9774 | CAV_BAS FAN | Fan:ConstantVolume | 7.283949 | 7.11960583 | 4197.9300 | 999.8980 | 98.69991139 | 12.27 | 6.67 | 5.60 | 2320277.79 | 4.5577 | 4.557745 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | Sensible | 105752.34 | 105752.34 | 1.0000 | 7.11960583 | 7.283949 | 25.70 | 13.67 | 0.00709867 | 43914.3 | 11.11 | 8.16 | 0.00709867 | 29060.6 | 4.49849017 | 6.67 | 12.27 | 5.60 | 12271.376 | 93480.97 | 33.16 | 0.00547412 | 14.83 | 1.20015641 | 16.4767 | 24.00 | 0.00746851 | 24.00 | 0.00746851 | 32.6901 | 72105.48 | 0.00 | 95147.56 | 95147.56 | 7.11960583 | 25.70 | 15.78 | 0.00709867 | 43914.3 | 12.57 | 10.56 | 0.00709867 | 30550.1 | |
CAV_BAS HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | CAV_BAS | BASEMENT | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 307268.000 | 307268.000 | 7.283949 | 0.00268811 | 6711.492 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | CAV_BAS FAN | Fan:ConstantVolume | 7.283949 | 7.11960583 | 4197.9300 | 999.8980 | 23.68023867 | 54.44 | 82.22 | 27.78 | 2761553.80 | 11.1266 | 11.350563 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 307268.00 | 307268.00 | 1.0000 | 7.11960583 | 7.283949 | -2.95 | -7.30 | 0.00095524 | -579.9 | 40.00 | 18.76 | 0.00800000 | 60796.0 | 2.68784029 | 60.00 | 32.22 | 27.78 | 0.000 | 307268.00 | -17.90 | 0.00095524 | -17.90 | 1.20015641 | 16.4767 | 0.00 | 0.00095524 | 23.74 | 0.00095524 | 4.2906 | 0.00 | 0.00 | 251262.81 | 251262.81 | 7.11960583 | 12.80 | 3.31 | 0.00095524 | 15273.7 | 47.86 | 18.21 | 0.00095524 | 50565.3 | |
AIRLOOP DATACENTER BASEMENT COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | DATACENTER_BASEMENT_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 479130.061 | 251095.381 | 26.414423 | 0.01173386 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1017.8934 | 1004.8586 | 0.9774 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 07:10:00 | Sensible | 407244.56 | 406278.26 | 0.8500 | -999.0 | -999.0 | 28.80 | 14.64 | 0.00702190 | 46871.9 | 12.80 | 8.76 | 0.00700000 | 30535.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 407244.56 | 33.90 | 0.00547527 | 15.07 | 0.33839277 | -999.0000 | 27.00 | 0.00704199 | 27.00 | 0.00704199 | 25.8125 | 372720.89 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BOT COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BOT | DATACENTER_BOT_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 10972.228 | 5809.801 | 0.622682 | 0.00026871 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1017.9298 | 1004.8586 | 0.9774 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:50:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:50:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:50:00 | Sensible | 9275.89 | 9233.21 | 0.8454 | -999.0 | -999.0 | 28.20 | 14.46 | 0.00704149 | 46317.9 | 12.80 | 8.76 | 0.00700000 | 30535.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9275.89 | 28.50 | 0.00546700 | 13.26 | 0.01563234 | -999.0000 | 27.00 | 0.00708204 | 27.00 | 0.00708204 | 25.9557 | 8795.87 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER MID COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER MID | DATACENTER_MID_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 105453.923 | 55828.603 | 5.982861 | 0.00258256 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1017.9327 | 1004.8586 | 0.9774 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:50:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:50:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:50:00 | Sensible | 89155.16 | 88729.50 | 0.8454 | -999.0 | -999.0 | 28.20 | 14.47 | 0.00704306 | 46323.4 | 12.80 | 8.76 | 0.00700000 | 30535.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 89155.16 | 28.50 | 0.00546700 | 13.26 | 0.15632344 | -999.0000 | 27.00 | 0.00708534 | 27.00 | 0.00708534 | 25.9677 | 84512.23 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER TOP COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER TOP | DATACENTER_TOP_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 10747.415 | 5689.233 | 0.609545 | 0.00026320 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1017.9311 | 1004.8586 | 0.9774 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:50:00 | Sensible | 9086.92 | 9044.43 | 0.8455 | -999.0 | -999.0 | 28.21 | 14.47 | 0.00704218 | 46330.1 | 12.80 | 8.76 | 0.00700000 | 30535.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9086.92 | 28.87 | 0.00546756 | 13.38 | 0.01563234 | -999.0000 | 27.00 | 0.00708363 | 27.00 | 0.00708363 | 25.9615 | 8607.72 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BASEMENT HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | DATACENTER_BASEMENT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 479130.061 | 479130.061 | 26.414423 | 0.01173386 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 0.9774 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 479130.06 | 479130.06 | 1.0000 | 25.81845020 | 26.414423 | -17.90 | -17.90 | 0.00095524 | -15629.4 | 40.00 | 18.76 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 479130.06 | -17.90 | 0.00095524 | -17.90 | 0.33839277 | 1.2811 | 0.00 | 0.00700000 | 27.00 | 0.00700000 | 25.6559 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BOT HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BOT | DATACENTER_BOT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 10972.228 | 10972.228 | 0.622682 | 0.00026871 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 0.9774 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 10972.23 | 10972.23 | 1.0000 | 0.60863271 | 0.622682 | -17.90 | -17.90 | 0.00095524 | -15629.4 | 40.00 | 18.76 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 10972.23 | -17.90 | 0.00095524 | -17.90 | 0.01563234 | 2.5105 | 0.00 | 0.00162734 | 25.70 | 0.00162734 | 6.4937 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER MID HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER MID | DATACENTER_MID_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 105453.923 | 105453.923 | 5.982861 | 0.00258256 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 0.9774 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 105453.92 | 105453.92 | 1.0000 | 5.84787304 | 5.982861 | -17.90 | -17.90 | 0.00095524 | -15629.4 | 40.00 | 18.76 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 105453.92 | -17.90 | 0.00095524 | -17.90 | 0.15632344 | 2.6129 | 0.00 | 0.00162735 | 23.78 | 0.00162735 | 7.2860 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER TOP HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER TOP | DATACENTER_TOP_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 10747.415 | 10747.415 | 0.609545 | 0.00026320 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 0.9774 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 10747.41 | 10747.41 | 1.0000 | 0.59579185 | 0.609545 | -17.90 | -17.90 | 0.00095524 | -15629.4 | 40.00 | 18.76 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 10747.41 | -17.90 | 0.00095524 | -17.90 | 0.01563234 | 2.5646 | 0.00 | 0.00162693 | 22.50 | 0.00162693 | 7.8690 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | DATACENTER_BASEMENT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 19243.924 | 19243.924 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | AIRLOOP DATACENTER BASEMENT SUPPLY FAN | Fan:OnOff | 26.414423 | 25.81845020 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 19243.92 | 19243.92 | 1.0000 | 25.81845020 | 26.414423 | -0.23 | -0.23 | 0.00692256 | 17079.5 | 40.00 | 18.76 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 19243.92 | -17.90 | 0.00095524 | -17.90 | 0.33839277 | 1.2811 | 0.00 | 0.00700000 | 27.00 | 0.00700000 | 25.6559 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BOT_SUPPHEATCOIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BOT | DATACENTER_BOT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 888.990 | 888.990 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | AIRLOOP DATACENTER BOT SUPPLY FAN | Fan:OnOff | 0.622682 | 0.60863271 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 888.99 | 888.99 | 1.0000 | 0.60863271 | 0.622682 | -0.45 | -4.71 | 0.00161046 | 3574.8 | 40.00 | 18.76 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 888.99 | -17.90 | 0.00095524 | -17.90 | 0.01563234 | 2.5105 | 0.00 | 0.00162734 | 25.70 | 0.00162734 | 6.4937 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER MID_SUPPHEATCOIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER MID | DATACENTER_MID_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 8889.896 | 8889.896 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | AIRLOOP DATACENTER MID SUPPLY FAN | Fan:OnOff | 5.982861 | 5.84787304 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 8889.90 | 8889.90 | 1.0000 | 5.84787304 | 5.982861 | -0.47 | -4.72 | 0.00160979 | 3554.6 | 40.00 | 18.76 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 8889.90 | -17.90 | 0.00095524 | -17.90 | 0.15632344 | 2.6129 | 0.00 | 0.00162735 | 23.78 | 0.00162735 | 7.2860 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER TOP_SUPPHEATCOIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER TOP | DATACENTER_TOP_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 888.990 | 888.990 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | AIRLOOP DATACENTER TOP SUPPLY FAN | Fan:OnOff | 0.609545 | 0.59579185 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 888.99 | 888.99 | 1.0000 | 0.59579185 | 0.609545 | -0.46 | -4.72 | 0.00160970 | 3563.1 | 40.00 | 18.76 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 888.99 | -17.90 | 0.00095524 | -17.90 | 0.01563234 | 2.5646 | 0.00 | 0.00162693 | 22.50 | 0.00162693 | 7.8690 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 08:43:27
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
VAV_BOT WITH REHEAT_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 12.55 | - | |||
VAV_MID WITH REHEAT_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 117.72 | - | |||
VAV_TOP WITH REHEAT_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 13.11 | - | |||
CAV_BAS_OA_CONTROLLER | DifferentialDryBulb | 1.20 | 7.28 | - | |||
AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER | DifferentialDryBulb | 0.34 | 26.41 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
CORE_BOTTOM | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_MID | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_TOP | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
BASEMENT | 2014.00 | 1098.00 | 154.50 |
CORE_BOTTOM | 1835.83 | 1265.17 | 149.33 |
CORE_MID | 1169.33 | 3246.83 | 212.00 |
CORE_TOP | 1741.17 | 3779.33 | 779.83 |
PERIMETER_BOT_ZN_3 | 1874.33 | 3655.17 | 533.67 |
PERIMETER_BOT_ZN_2 | 2353.67 | 3248.83 | 641.00 |
PERIMETER_BOT_ZN_1 | 2912.00 | 2597.33 | 676.50 |
PERIMETER_BOT_ZN_4 | 2736.00 | 2520.67 | 455.17 |
PERIMETER_MID_ZN_3 | 2799.00 | 4090.67 | 1731.50 |
PERIMETER_MID_ZN_2 | 2504.17 | 3198.50 | 1295.33 |
PERIMETER_MID_ZN_1 | 3104.50 | 2949.50 | 1092.67 |
PERIMETER_MID_ZN_4 | 2802.50 | 3782.67 | 1315.33 |
PERIMETER_TOP_ZN_3 | 3340.33 | 4242.00 | 2314.33 |
PERIMETER_TOP_ZN_2 | 3316.83 | 3751.67 | 1827.67 |
PERIMETER_TOP_ZN_1 | 3318.50 | 3181.83 | 1435.50 |
PERIMETER_TOP_ZN_4 | 3224.50 | 3969.50 | 1822.33 |
DATACENTER_BOT_ZN_6 | 5943.00 | 709.67 | 709.67 |
DATACENTER_MID_ZN_6 | 5696.00 | 156.17 | 144.50 |
DATACENTER_TOP_ZN_6 | 5140.67 | 422.67 | 247.50 |
DATACENTER_BASEMENT_ZN_6 | 5943.00 | 5889.17 | 5889.17 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
Facility | 5943.00 | 5942.67 | 5921.17 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
BASEMENT | 0.00 | 54.50 | 0.00 | 1.17 |
CORE_BOTTOM | 0.00 | 4.17 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 7.50 | 0.00 | 0.33 | 0.00 |
PERIMETER_BOT_ZN_3 | 1.50 | 13.00 | 0.00 | 10.50 |
PERIMETER_BOT_ZN_2 | 2.17 | 40.83 | 0.00 | 40.67 |
PERIMETER_BOT_ZN_1 | 3.00 | 127.00 | 0.00 | 125.83 |
PERIMETER_BOT_ZN_4 | 0.00 | 83.67 | 0.00 | 48.00 |
PERIMETER_MID_ZN_3 | 52.50 | 7.00 | 9.50 | 5.50 |
PERIMETER_MID_ZN_2 | 40.33 | 39.67 | 3.17 | 39.33 |
PERIMETER_MID_ZN_1 | 26.17 | 208.50 | 2.50 | 206.50 |
PERIMETER_MID_ZN_4 | 27.17 | 37.00 | 2.50 | 24.67 |
PERIMETER_TOP_ZN_3 | 196.33 | 12.67 | 56.67 | 9.33 |
PERIMETER_TOP_ZN_2 | 130.67 | 41.33 | 18.33 | 39.67 |
PERIMETER_TOP_ZN_1 | 105.50 | 102.67 | 16.17 | 99.50 |
PERIMETER_TOP_ZN_4 | 96.50 | 38.17 | 15.17 | 25.00 |
DATACENTER_BOT_ZN_6 | 0.00 | 33.00 | 0.00 | 31.83 |
DATACENTER_MID_ZN_6 | 0.00 | 24.50 | 0.00 | 23.67 |
DATACENTER_TOP_ZN_6 | 0.00 | 22.17 | 0.00 | 21.33 |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 246.33 | 0.00 | 234.67 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 224.67 | 682.50 | 60.50 | 577.17 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 08:43:27
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 62.01 | 149.60 | 6779.02 | 1.556 | 0.000 | 0.000 | 0.000 |
CORE_BOTTOM | 55.69 | 134.35 | 6849.35 | 1.100 | 0.000 | 0.000 | 0.000 |
CORE_MID | 55.69 | 134.35 | 6849.35 | 0.820 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 55.69 | 134.35 | 6849.35 | 0.774 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 6.99 | 16.87 | 860.00 | 0.987 | 0.043 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 4.51 | 10.87 | 554.22 | 1.907 | 0.045 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 6.99 | 16.87 | 860.02 | 1.973 | 0.043 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 4.51 | 10.87 | 554.22 | 2.366 | 0.045 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 6.99 | 16.87 | 860.00 | 0.807 | 0.101 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 3.94 | 10.87 | 554.22 | 1.764 | 0.112 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 6.99 | 16.87 | 860.02 | 1.872 | 0.101 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 4.51 | 10.87 | 554.22 | 1.806 | 0.104 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 6.99 | 16.87 | 860.00 | 0.846 | 0.125 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 4.51 | 10.87 | 554.22 | 1.848 | 0.129 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 6.99 | 16.87 | 860.02 | 1.860 | 0.125 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 4.51 | 10.87 | 554.22 | 1.853 | 0.129 | 0.000 | 0.000 |
DATACENTER_BOT_ZN_6 | 0.81 | 1.95 | 99.34 | 0.424 | 0.000 | 0.000 | 0.000 |
DATACENTER_MID_ZN_6 | 0.81 | 1.95 | 99.34 | 0.424 | 0.000 | 0.000 | 0.000 |
DATACENTER_TOP_ZN_6 | 0.81 | 1.95 | 99.34 | 0.424 | 0.000 | 0.000 | 0.000 |
DATACENTER_BASEMENT_ZN_6 | 17.48 | 42.18 | 1911.37 | 30.461 | 0.000 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 62.01 | 149.60 | 6779.02 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_BOTTOM | 55.69 | 134.35 | 6849.35 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_MID | 55.69 | 134.35 | 6849.35 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 55.69 | 134.35 | 6849.35 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 6.99 | 16.87 | 860.00 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 4.51 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 6.99 | 16.87 | 860.02 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 4.51 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 6.99 | 16.87 | 860.00 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 3.94 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 6.99 | 16.87 | 860.02 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 4.51 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 6.99 | 16.87 | 860.00 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 4.51 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 6.99 | 16.87 | 860.02 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 4.51 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
DATACENTER_BOT_ZN_6 | 0.81 | 1.95 | 99.34 | 0.000 | 0.000 | 0.000 | 0.000 |
DATACENTER_MID_ZN_6 | 0.81 | 1.95 | 99.34 | 0.000 | 0.000 | 0.000 | 0.000 |
DATACENTER_TOP_ZN_6 | 0.81 | 1.95 | 99.34 | 0.000 | 0.000 | 0.000 | 0.000 |
DATACENTER_BASEMENT_ZN_6 | 17.48 | 42.18 | 1911.37 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 08:43:27
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
BASEMENT | CAV_BAS | 62.01 | 149.60 | 6779.02 | 2779.43 | 1.2002 | 1.200 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | 55.69 | 134.35 | 6849.35 | 2496.12 | 0.0000 | 1.078 |
CORE_MID | VAV_MID WITH REHEAT | 55.69 | 134.35 | 6849.35 | 2496.12 | 0.0000 | 10.778 |
CORE_TOP | VAV_TOP WITH REHEAT | 55.69 | 134.35 | 6849.35 | 2496.12 | 0.0000 | 1.078 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | 6.99 | 16.87 | 860.00 | 313.41 | 0.0000 | 0.135 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | 4.51 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | 6.99 | 16.87 | 860.02 | 313.42 | 0.0000 | 0.135 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | 4.51 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | 6.99 | 16.87 | 860.00 | 313.41 | 0.0000 | 1.353 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | 3.94 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.872 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | 6.99 | 16.87 | 860.02 | 313.42 | 0.0000 | 1.353 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | 4.51 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.872 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | 6.99 | 16.87 | 860.00 | 313.41 | 0.0000 | 0.135 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | 4.51 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | 6.99 | 16.87 | 860.02 | 313.42 | 0.0000 | 0.135 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | 4.51 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | 0.81 | 1.95 | 99.34 | 36.20 | 0.0156 | 0.016 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | 0.81 | 1.95 | 99.34 | 36.20 | 0.1563 | 0.156 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | 0.81 | 1.95 | 99.34 | 36.20 | 0.0156 | 0.016 |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | 17.48 | 42.18 | 1911.37 | 783.68 | 0.3384 | 0.338 |
Total Facility | 1027.73 | 2493.19 | 126016.35 | 46320.38 | 1.7261 | 158.471 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
BASEMENT | 65096109.30 | 0.00 | 65096109.30 | 0.00 | 65096109.30 | 37848132.68 | 3865.44 | 963.84 | 3930.72 | 399.63 |
CORE_BOTTOM | 46930391.78 | 0.00 | 46930391.78 | 0.00 | 46930391.78 | 33990283.35 | 4655.43 | 38.87 | 4065.70 | 412.54 |
CORE_MID | 0.34E+09 | 0.00 | 0.34E+09 | 0.00 | 0.34E+09 | 0.34E+09 | 5868.48 | 36.99 | 2854.53 | 291.73 |
CORE_TOP | 32067182.61 | 0.00 | 32067182.61 | 0.00 | 32067182.61 | 33990283.35 | 6235.77 | 26.94 | 2497.29 | 400.27 |
PERIMETER_BOT_ZN_3 | 5308848.35 | 0.00 | 5308848.35 | 451114.65 | 5759963.00 | 4267819.30 | 5018.73 | 50.47 | 3690.80 | 412.54 |
PERIMETER_BOT_ZN_2 | 6627157.06 | 0.00 | 6627157.06 | 300742.89 | 6927899.96 | 2750345.05 | 3429.18 | 7.28 | 5323.55 | 412.54 |
PERIMETER_BOT_ZN_1 | 10421961.49 | 0.00 | 10421961.49 | 451114.65 | 10873076.14 | 4267912.63 | 3591.23 | 30.47 | 5138.30 | 412.54 |
PERIMETER_BOT_ZN_4 | 8249479.42 | 0.00 | 8249479.42 | 300742.89 | 8550222.31 | 2750345.05 | 3404.91 | 0.02 | 5355.07 | 412.54 |
PERIMETER_MID_ZN_3 | 42219812.20 | 0.00 | 42219812.20 | 1057988.21 | 43277800.41 | 42678193.03 | 5425.82 | 49.49 | 3284.69 | 291.73 |
PERIMETER_MID_ZN_2 | 63138477.20 | 0.00 | 63138477.20 | 705324.99 | 63843802.19 | 27503450.52 | 3737.29 | 4.81 | 5017.90 | 1200.73 |
PERIMETER_MID_ZN_1 | 96474079.19 | 0.00 | 96474079.19 | 1057988.21 | 97532067.40 | 42679126.28 | 3877.19 | 5.07 | 4877.74 | 291.73 |
PERIMETER_MID_ZN_4 | 61097948.16 | 0.00 | 61097948.16 | 705324.99 | 61803273.15 | 27503450.52 | 3729.04 | 7.47 | 5023.49 | 291.73 |
PERIMETER_TOP_ZN_3 | 4411041.58 | 0.00 | 4411041.58 | 1313602.61 | 5724644.19 | 4267819.30 | 5254.02 | 53.87 | 3452.11 | 400.27 |
PERIMETER_TOP_ZN_2 | 6181150.58 | 0.00 | 6181150.58 | 875734.47 | 7056885.05 | 2750345.05 | 3903.42 | 2.72 | 4853.86 | 400.27 |
PERIMETER_TOP_ZN_1 | 9576536.15 | 0.00 | 9576536.15 | 1313602.61 | 10890138.76 | 4267912.63 | 3968.82 | 5.78 | 4785.40 | 400.27 |
PERIMETER_TOP_ZN_4 | 6242165.59 | 0.00 | 6242165.59 | 875734.47 | 7117900.07 | 2750345.05 | 3882.05 | 8.03 | 4869.92 | 400.27 |
DATACENTER_BOT_ZN_6 | 244296.02 | 0.00 | 244296.02 | 0.00 | 244296.02 | 492981.60 | 4419.00 | 4341.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 2442960.18 | 0.00 | 2442960.18 | 0.00 | 2442960.18 | 4929815.99 | 4419.00 | 4341.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 244296.02 | 0.00 | 244296.02 | 0.00 | 244296.02 | 492981.60 | 4419.00 | 4341.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.48E+09 | 0.00 | 0.48E+09 | 0.00 | 0.48E+09 | 10671554.30 | 91.76 | 375.44 | 8292.80 | 2800.17 |
Total Facility | 0.67E+10 | 0.00 | 0.67E+10 | 41148653.23 | 0.68E+10 | 0.50E+10 | 6712.31 | 4407.72 | 8669.96 | 3709.59 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
BASEMENT | 2.8908 | 0.0000 | 2.8908 | 0.0000 | 2.8908 | 1.2002 | 1295.88 | 959.62 | 3687.50 |
CORE_BOTTOM | 2.0643 | 0.0000 | 2.0643 | 0.0000 | 2.0643 | 1.0778 | 2170.75 | 36.37 | 3735.88 |
CORE_MID | 15.4036 | 0.0000 | 15.4036 | 0.0000 | 15.4036 | 10.7782 | 3161.73 | 36.38 | 2744.89 |
CORE_TOP | 1.4558 | 0.0000 | 1.4558 | 0.0000 | 1.4558 | 1.0778 | 3503.03 | 26.94 | 2413.04 |
PERIMETER_BOT_ZN_3 | 0.2330 | 0.0000 | 0.2330 | 0.0102 | 0.2432 | 0.1353 | 2530.22 | 48.08 | 3364.70 |
PERIMETER_BOT_ZN_2 | 0.2902 | 0.0000 | 0.2902 | 0.0068 | 0.2970 | 0.0872 | 1011.06 | 5.91 | 4926.03 |
PERIMETER_BOT_ZN_1 | 0.4657 | 0.0000 | 0.4657 | 0.0102 | 0.4758 | 0.1353 | 1149.69 | 28.27 | 4765.04 |
PERIMETER_BOT_ZN_4 | 0.3598 | 0.0000 | 0.3598 | 0.0068 | 0.3666 | 0.0872 | 994.48 | 0.00 | 4948.52 |
PERIMETER_MID_ZN_3 | 1.9076 | 0.0000 | 1.9076 | 0.0239 | 1.9315 | 1.3533 | 2728.35 | 48.39 | 3166.25 |
PERIMETER_MID_ZN_2 | 2.6872 | 0.0000 | 2.6872 | 0.0171 | 2.7043 | 0.8721 | 1105.68 | 3.56 | 3924.76 |
PERIMETER_MID_ZN_1 | 4.4173 | 0.0000 | 4.4173 | 0.0239 | 4.4412 | 1.3533 | 1187.48 | 3.11 | 4752.41 |
PERIMETER_MID_ZN_4 | 2.7525 | 0.0000 | 2.7525 | 0.0159 | 2.7684 | 0.8721 | 1107.73 | 5.22 | 4830.05 |
PERIMETER_TOP_ZN_3 | 0.2001 | 0.0000 | 0.2001 | 0.0297 | 0.2298 | 0.1353 | 2527.49 | 53.56 | 3361.95 |
PERIMETER_TOP_ZN_2 | 0.2816 | 0.0000 | 0.2816 | 0.0198 | 0.3013 | 0.0872 | 1205.86 | 1.57 | 4735.58 |
PERIMETER_TOP_ZN_1 | 0.4394 | 0.0000 | 0.4394 | 0.0297 | 0.4691 | 0.1353 | 1251.75 | 4.64 | 4686.61 |
PERIMETER_TOP_ZN_4 | 0.2826 | 0.0000 | 0.2826 | 0.0198 | 0.3023 | 0.0872 | 1197.41 | 5.77 | 4739.82 |
DATACENTER_BOT_ZN_6 | 0.0114 | 0.0000 | 0.0114 | 0.0000 | 0.0114 | 0.0156 | 1602.00 | 4341.00 | 0.00 |
DATACENTER_MID_ZN_6 | 0.1142 | 0.0000 | 0.1142 | 0.0000 | 0.1142 | 0.1563 | 1602.00 | 4341.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 0.0114 | 0.0000 | 0.0114 | 0.0000 | 0.0114 | 0.0156 | 1602.00 | 4341.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 15.7583 | 0.0000 | 15.7583 | 0.0000 | 15.7583 | 0.3384 | 74.92 | 375.44 | 5492.63 |
Total Facility | 297.5683 | 0.0000 | 297.5683 | 0.9407 | 298.5089 | 158.4706 | 3895.31 | 4386.00 | 5869.37 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
VAV_BOT WITH REHEAT | 74078451.90 | 0.00 | 74078451.90 | 48026705.38 | 3621.71 | 384.07 | 4754.22 | 412.54 |
VAV_MID WITH REHEAT | 0.58E+09 | 0.00 | 0.58E+09 | 0.48E+09 | 3962.09 | 154.74 | 4643.17 | 291.73 |
VAV_TOP WITH REHEAT | 55869039.92 | 0.00 | 55869039.92 | 48026705.38 | 4043.38 | 291.67 | 4424.95 | 399.93 |
CAV_BAS | 62191799.90 | 0.00 | 62191799.90 | 37848132.68 | 4848.89 | 17.86 | 3893.25 | 399.63 |
AIRLOOP DATACENTER BASEMENT | 0.46E+09 | 0.00 | 0.46E+09 | 10671554.30 | 467.20 | 0.00 | 8292.80 | 2800.17 |
AIRLOOP DATACENTER BOT | 233396.58 | 0.00 | 233396.58 | 492981.60 | 8760.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER MID | 2333965.77 | 0.00 | 2333965.77 | 4929815.99 | 8760.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER TOP | 233396.58 | 0.00 | 233396.58 | 492981.60 | 8760.00 | 0.00 | 0.00 | 0.00 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
VAV_BOT WITH REHEAT | 3.2607 | 0.0000 | 3.2607 | 1.5229 | 1149.71 | 382.09 | 4411.20 |
VAV_MID WITH REHEAT | 26.1227 | 0.0000 | 26.1227 | 15.2292 | 1257.58 | 154.63 | 4530.79 |
VAV_TOP WITH REHEAT | 2.5408 | 0.0000 | 2.5408 | 1.5229 | 1311.02 | 291.42 | 4340.56 |
CAV_BAS | 2.7619 | 0.0000 | 2.7619 | 1.2002 | 2270.78 | 14.68 | 3657.54 |
AIRLOOP DATACENTER BASEMENT | 15.0553 | 0.0000 | 15.0553 | 0.3384 | 450.37 | 0.00 | 5492.63 |
AIRLOOP DATACENTER BOT | 0.0109 | 0.0000 | 0.0109 | 0.0156 | 5943.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER MID | 0.1091 | 0.0000 | 0.1091 | 0.1563 | 5943.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER TOP | 0.0109 | 0.0000 | 0.0109 | 0.0156 | 5943.00 | 0.00 | 0.00 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
VAV_BOT WITH REHEAT | 0.00 | 0.00 | 4024.97 | 0.00 | 0.00 | 0.00 | 1341.00 | 0.00 | 0.00 | 0.00 |
VAV_MID WITH REHEAT | 0.00 | 0.00 | 3840.45 | 0.00 | 0.00 | 0.00 | 1341.26 | 0.00 | 0.00 | 0.00 |
VAV_TOP WITH REHEAT | 0.00 | 0.00 | 3310.80 | 0.00 | 0.00 | 0.00 | 2005.03 | 0.00 | 0.00 | 0.00 |
CAV_BAS | 0.00 | 954.89 | 4123.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER BASEMENT | 0.00 | 375.44 | 8292.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER BOT | 0.00 | 4341.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER MID | 0.00 | 4341.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER TOP | 0.00 | 4341.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
VAV_BOT WITH REHEAT | 0.0000 | 0.0000 | 4.7606 | 0.0000 | 0.0000 | 0.0000 | 1.6280 | 0.0000 | 0.0000 | 0.0000 |
VAV_MID WITH REHEAT | 0.0000 | 0.0000 | 37.6549 | 0.0000 | 0.0000 | 0.0000 | 16.1430 | 0.0000 | 0.0000 | 0.0000 |
VAV_TOP WITH REHEAT | 0.0000 | 0.0000 | 4.0818 | 0.0000 | 0.0000 | 0.0000 | 1.6070 | 0.0000 | 0.0000 | 0.0000 |
CAV_BAS | 0.0000 | 1.1477 | 4.1146 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
AIRLOOP DATACENTER BASEMENT | 0.0000 | 0.3237 | 16.2695 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
AIRLOOP DATACENTER BOT | 0.0000 | 0.0149 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
AIRLOOP DATACENTER MID | 0.0000 | 0.1494 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
AIRLOOP DATACENTER TOP | 0.0000 | 0.0149 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 08:43:27
Surfaces by ClassTotal | Outdoors | |
Wall | 98 | 30 |
Floor | 41 | 0 |
Roof | 30 | 1 |
Internal Mass | 16 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 24 | 24 |
Door | 12 | 12 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 8 |
Conditioned Zones | 23 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 3 |
Count | |
IDF Objects | 1395 |
Defaulted Fields | 1182 |
Fields with Defaults | 3867 |
Autosized Fields | 332 |
Autosizable Fields | 411 |
Autocalculated Fields | 226 |
Autocalculatable Fields | 473 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 08:43:27
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 29633.21 | 336233.11 | 29-MAY-05:00 | 2195763.20 | 16-AUG-15:10 |
Electricity:Building | 18602.64 | 225715.65 | 14-MAY-17:10 | 1164206.62 | 01-DEC-16:30 |
Electricity:Zone:BASEMENT | 687.24 | 14732.47 | 01-JAN-00:10 | 36407.88 | 02-JAN-08:10 |
Electricity:SpaceType:GENERAL | 18602.64 | 225715.65 | 14-MAY-17:10 | 1164206.62 | 01-DEC-16:30 |
InteriorLights:Electricity | 3926.24 | 18459.50 | 01-JAN-09:10 | 385834.94 | 02-JAN-16:40 |
InteriorLights:Electricity:Zone:BASEMENT | 262.84 | 1274.92 | 01-JAN-00:10 | 22950.34 | 02-JAN-08:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 3926.24 | 18459.50 | 01-JAN-09:10 | 385834.94 | 02-JAN-16:40 |
LightsWired:InteriorLights:Electricity | 3926.24 | 18459.50 | 01-JAN-09:10 | 385834.94 | 02-JAN-16:40 |
LightsWired:InteriorLights:Electricity:Zone:BASEMENT | 262.84 | 1274.92 | 01-JAN-00:10 | 22950.34 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 3926.24 | 18459.50 | 01-JAN-09:10 | 385834.94 | 02-JAN-16:40 |
Electricity:Zone:CORE_BOTTOM | 525.67 | 5598.20 | 01-JAN-00:10 | 37817.64 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_BOTTOM | 236.05 | 1144.97 | 01-JAN-00:10 | 20611.01 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_BOTTOM | 236.05 | 1144.97 | 01-JAN-00:10 | 20611.01 | 02-JAN-08:10 |
Electricity:Zone:CORE_MID | 5256.66 | 55981.88 | 01-JAN-00:10 | 378175.77 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_MID | 2360.53 | 11449.71 | 01-JAN-00:10 | 206110.14 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_MID | 2360.53 | 11449.71 | 01-JAN-00:10 | 206110.14 | 02-JAN-08:10 |
Electricity:Zone:CORE_TOP | 525.67 | 5598.19 | 01-JAN-00:10 | 37817.58 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_TOP | 236.05 | 1144.97 | 01-JAN-00:10 | 20611.01 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_TOP | 236.05 | 1144.97 | 01-JAN-00:10 | 20611.01 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_3 | 53.70 | 627.57 | 09-APR-17:10 | 4748.47 | 02-JAN-16:20 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 17.33 | 68.40 | 01-JAN-09:10 | 2587.92 | 02-JAN-16:20 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 17.33 | 68.40 | 01-JAN-09:10 | 2587.92 | 02-JAN-16:20 |
Electricity:Zone:PERIMETER_BOT_ZN_2 | 34.57 | 404.43 | 14-MAY-17:10 | 3060.10 | 02-JAN-16:20 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 11.14 | 44.08 | 01-JAN-07:50 | 1667.75 | 02-JAN-16:20 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 11.14 | 44.08 | 01-JAN-07:50 | 1667.75 | 02-JAN-16:20 |
Electricity:Zone:PERIMETER_BOT_ZN_1 | 53.41 | 627.58 | 26-MAR-17:10 | 4748.56 | 02-JAN-16:40 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 17.05 | 68.40 | 01-JAN-07:50 | 2587.98 | 02-JAN-16:40 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 17.05 | 68.40 | 01-JAN-07:50 | 2587.98 | 02-JAN-16:40 |
Electricity:Zone:PERIMETER_BOT_ZN_4 | 34.42 | 404.43 | 12-MAR-17:10 | 3060.09 | 02-JAN-16:40 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 10.99 | 44.08 | 01-JAN-09:10 | 1667.75 | 02-JAN-16:40 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 10.99 | 44.08 | 01-JAN-09:10 | 1667.75 | 02-JAN-16:40 |
Electricity:Zone:PERIMETER_MID_ZN_3 | 536.65 | 6275.73 | 09-APR-17:10 | 47484.70 | 02-JAN-16:20 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 172.99 | 684.02 | 01-JAN-09:00 | 25879.19 | 02-JAN-16:20 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 172.99 | 684.02 | 01-JAN-09:00 | 25879.19 | 02-JAN-16:20 |
Electricity:Zone:PERIMETER_MID_ZN_2 | 345.55 | 4044.32 | 14-MAY-17:10 | 30600.95 | 02-JAN-16:20 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 111.19 | 440.81 | 01-JAN-07:40 | 16677.53 | 02-JAN-16:20 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 111.19 | 440.81 | 01-JAN-07:40 | 16677.53 | 02-JAN-16:20 |
Electricity:Zone:PERIMETER_MID_ZN_1 | 533.93 | 6275.83 | 12-MAR-17:10 | 47485.60 | 02-JAN-16:40 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 170.27 | 684.04 | 01-JAN-07:50 | 25879.75 | 02-JAN-16:40 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 170.27 | 684.04 | 01-JAN-07:50 | 25879.75 | 02-JAN-16:40 |
Electricity:Zone:PERIMETER_MID_ZN_4 | 344.10 | 4044.30 | 12-MAR-17:10 | 30600.86 | 02-JAN-16:40 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 109.75 | 440.81 | 01-JAN-09:00 | 16677.53 | 02-JAN-16:40 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 109.75 | 440.81 | 01-JAN-09:00 | 16677.53 | 02-JAN-16:40 |
Electricity:Zone:PERIMETER_TOP_ZN_3 | 53.66 | 627.57 | 09-APR-17:10 | 4748.47 | 02-JAN-16:20 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 17.30 | 68.40 | 01-JAN-09:00 | 2587.92 | 02-JAN-16:20 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 17.30 | 68.40 | 01-JAN-09:00 | 2587.92 | 02-JAN-16:20 |
Electricity:Zone:PERIMETER_TOP_ZN_2 | 34.55 | 404.43 | 14-MAY-17:10 | 3060.10 | 02-JAN-16:20 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 11.12 | 44.08 | 01-JAN-07:40 | 1667.75 | 02-JAN-16:20 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 11.12 | 44.08 | 01-JAN-07:40 | 1667.75 | 02-JAN-16:20 |
Electricity:Zone:PERIMETER_TOP_ZN_1 | 53.39 | 627.58 | 12-MAR-17:10 | 4748.56 | 02-JAN-16:40 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 17.03 | 68.40 | 01-JAN-07:50 | 2587.98 | 02-JAN-16:40 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 17.03 | 68.40 | 01-JAN-07:50 | 2587.98 | 02-JAN-16:40 |
Electricity:Zone:PERIMETER_TOP_ZN_4 | 34.41 | 404.43 | 12-MAR-17:10 | 3060.09 | 02-JAN-16:40 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 10.97 | 44.08 | 01-JAN-09:00 | 1667.75 | 02-JAN-16:40 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 10.97 | 44.08 | 01-JAN-09:00 | 1667.75 | 02-JAN-16:40 |
Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 7568.97 | 95267.60 | 01-JAN-00:10 | 386103.53 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 74.11 | 359.47 | 01-JAN-00:10 | 6471.01 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 74.11 | 359.47 | 01-JAN-00:10 | 6471.01 | 02-JAN-08:10 |
Electricity:Zone:DATACENTER_BOT_ZN_6 | 160.51 | 1980.76 | 01-JAN-00:10 | 8373.14 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_BOT_ZN_6 | 6.63 | 32.15 | 01-JAN-00:10 | 578.72 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_BOT_ZN_6 | 6.63 | 32.15 | 01-JAN-00:10 | 578.72 | 02-JAN-08:10 |
Electricity:Zone:DATACENTER_MID_ZN_6 | 1605.09 | 19807.58 | 01-JAN-00:10 | 83731.41 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_MID_ZN_6 | 66.28 | 321.53 | 01-JAN-00:10 | 5787.18 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_MID_ZN_6 | 66.28 | 321.53 | 01-JAN-00:10 | 5787.18 | 02-JAN-08:10 |
Electricity:Zone:DATACENTER_TOP_ZN_6 | 160.51 | 1980.76 | 01-JAN-00:10 | 8373.14 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_TOP_ZN_6 | 6.63 | 32.15 | 01-JAN-00:10 | 578.72 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_TOP_ZN_6 | 6.63 | 32.15 | 01-JAN-00:10 | 578.72 | 02-JAN-08:10 |
InteriorEquipment:Electricity | 14676.40 | 207256.16 | 01-JAN-00:10 | 778371.69 | 03-APR-07:10 |
InteriorEquipment:Electricity:Zone:BASEMENT | 424.40 | 13457.54 | 01-JAN-00:10 | 13457.54 | 01-JAN-00:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 14676.40 | 207256.16 | 01-JAN-00:10 | 778371.69 | 03-APR-07:10 |
MiscPlug:InteriorEquipment:Electricity | 5334.97 | 88964.76 | 01-JAN-00:10 | 305206.10 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:BASEMENT | 424.40 | 13457.54 | 01-JAN-00:10 | 13457.54 | 01-JAN-00:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 5334.97 | 88964.76 | 01-JAN-00:10 | 305206.10 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 289.61 | 4453.23 | 01-JAN-00:10 | 17206.63 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 289.61 | 4453.23 | 01-JAN-00:10 | 17206.63 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_MID | 2896.13 | 44532.17 | 01-JAN-00:10 | 172065.63 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_MID | 2896.13 | 44532.17 | 01-JAN-00:10 | 172065.63 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_TOP | 289.61 | 4453.22 | 01-JAN-00:10 | 17206.56 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_TOP | 289.61 | 4453.22 | 01-JAN-00:10 | 17206.56 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 36.37 | 559.17 | 01-JAN-00:10 | 2160.55 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 36.37 | 559.17 | 01-JAN-00:10 | 2160.55 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.34 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.34 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 36.37 | 559.18 | 01-JAN-00:10 | 2160.58 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 36.37 | 559.18 | 01-JAN-00:10 | 2160.58 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.33 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.33 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 363.65 | 5591.71 | 01-JAN-00:10 | 21605.52 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 363.65 | 5591.71 | 01-JAN-00:10 | 21605.52 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 234.35 | 3603.51 | 01-JAN-00:10 | 13923.42 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 234.35 | 3603.51 | 01-JAN-00:10 | 13923.42 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 363.66 | 5591.79 | 01-JAN-00:10 | 21605.85 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 363.66 | 5591.79 | 01-JAN-00:10 | 21605.85 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 234.35 | 3603.49 | 01-JAN-00:10 | 13923.33 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 234.35 | 3603.49 | 01-JAN-00:10 | 13923.33 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 36.37 | 559.17 | 01-JAN-00:10 | 2160.55 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 36.37 | 559.17 | 01-JAN-00:10 | 2160.55 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.34 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.34 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 36.37 | 559.18 | 01-JAN-00:10 | 2160.58 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 36.37 | 559.18 | 01-JAN-00:10 | 2160.58 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.33 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.33 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 7494.86 | 94908.13 | 01-JAN-00:10 | 379632.52 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity | 9341.42 | 118291.40 | 01-JAN-00:10 | 473165.59 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 7494.86 | 94908.13 | 01-JAN-00:10 | 379632.52 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:SpaceType:GENERAL | 9341.42 | 118291.40 | 01-JAN-00:10 | 473165.59 | 31-MAR-23:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_BOT_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_BOT_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_MID_ZN_6 | 1538.81 | 19486.06 | 01-JAN-00:10 | 77944.22 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_MID_ZN_6 | 1538.81 | 19486.06 | 01-JAN-00:10 | 77944.22 | 31-MAR-23:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_TOP_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_TOP_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
Electricity:Plant | 1841.45 | 3969.27 | 05-JAN-03:50 | 374016.03 | 16-AUG-15:10 |
HeatRejection:Electricity | 590.73 | 122.41 | 05-JAN-07:20 | 83748.33 | 15-JUN-13:20 |
General:HeatRejection:Electricity | 590.73 | 122.41 | 05-JAN-07:20 | 83748.33 | 15-JUN-13:20 |
Electricity:HVAC | 6636.66 | 58490.87 | 21-MAY-02:30 | 634823.43 | 16-AUG-15:00 |
ExteriorEquipment:Electricity | 1934.79 | 28603.11 | 01-JAN-00:10 | 118525.16 | 31-JAN-08:20 |
Transformer:ExteriorEquipment:Electricity | 80.18 | 1421.04 | 01-JAN-00:10 | 5057.48 | 01-DEC-16:40 |
ElectricityPurchased:Facility | 29633.21 | 336233.11 | 29-MAY-05:00 | 2195763.20 | 16-AUG-15:10 |
ElectricityPurchased:Plant | 29633.21 | 336233.11 | 29-MAY-05:00 | 2195763.20 | 16-AUG-15:10 |
Cogeneration:ElectricityPurchased | 29633.21 | 336233.11 | 29-MAY-05:00 | 2195763.20 | 16-AUG-15:10 |
General:Cogeneration:ElectricityPurchased | 29633.21 | 336233.11 | 29-MAY-05:00 | 2195763.20 | 16-AUG-15:10 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 29633.21 | 336233.11 | 29-MAY-05:00 | 2195763.20 | 16-AUG-15:10 |
ElectricityNet:Plant | 29633.21 | 336233.11 | 29-MAY-05:00 | 2195763.20 | 16-AUG-15:10 |
Cogeneration:ElectricityNet | 29633.21 | 336233.11 | 29-MAY-05:00 | 2195763.20 | 16-AUG-15:10 |
General:Cogeneration:ElectricityNet | 29633.21 | 336233.11 | 29-MAY-05:00 | 2195763.20 | 16-AUG-15:10 |
Fans:Electricity | 2955.25 | 51462.93 | 01-JAN-17:00 | 371803.09 | 26-JUN-14:10 |
General:Fans:Electricity | 2955.25 | 51462.93 | 01-JAN-17:00 | 371803.09 | 26-JUN-14:10 |
ExteriorLights:Electricity | 697.85 | 0.00 | 01-JAN-07:30 | 57580.60 | 01-JAN-06:10 |
General:ExteriorLights:Electricity | 697.85 | 0.00 | 01-JAN-07:30 | 57580.60 | 01-JAN-06:10 |
ElevatorLift:ExteriorEquipment:Electricity | 1848.78 | 27144.47 | 01-JAN-00:10 | 113101.96 | 01-JAN-07:10 |
ElevatorLightsFan:ExteriorEquipment:Electricity | 5.83 | 37.60 | 01-JAN-00:10 | 376.00 | 01-JAN-07:10 |
Cooling:Electricity | 2072.18 | 2159.98 | 05-JAN-07:10 | 462978.65 | 16-AUG-15:10 |
General:Cooling:Electricity | 2072.18 | 2159.98 | 05-JAN-07:10 | 462978.65 | 16-AUG-15:10 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Humidifier:Electricity | 2374.39 | 0.00 | 13-APR-19:00 | 100000.00 | 01-JAN-10:00 |
General:Humidifier:Electricity | 2374.39 | 0.00 | 13-APR-19:00 | 100000.00 | 01-JAN-10:00 |
Boiler Parasitic:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Pumps:Electricity | 405.38 | 3787.07 | 01-JAN-00:10 | 59450.27 | 12-SEP-15:20 |
General:Pumps:Electricity | 405.38 | 3787.07 | 01-JAN-00:10 | 59450.27 | 12-SEP-15:20 |
WIRED_LTG_ELECTRICITY | 110.33 | 0.00 | 01-JAN-00:10 | 10841.96 | 02-JAN-16:50 |
WIRED_INT_EQUIP | 5334.97 | 88964.76 | 31-MAR-23:10 | 305206.10 | 03-APR-07:10 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 2680.00 | 8146.58 | 15-JAN-14:20 | 1539182.19 | 23-DEC-07:10 |
NaturalGas:Plant | 2680.00 | 8146.58 | 15-JAN-14:20 | 1539182.19 | 23-DEC-07:10 |
Heating:NaturalGas | 1866.34 | 0.00 | 01-JAN-00:10 | 1508880.84 | 23-DEC-07:10 |
Boiler:Heating:NaturalGas | 1866.34 | 0.00 | 01-JAN-00:10 | 1508880.84 | 23-DEC-07:10 |
WaterSystems:NaturalGas | 813.65 | 8146.58 | 05-JAN-05:50 | 85997.10 | 14-FEB-12:30 |
Water Heater:WaterSystems:NaturalGas | 813.65 | 8146.58 | 05-JAN-05:50 | 85997.10 | 14-FEB-12:30 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
PlantLoopCoolingDemand:Facility | 10728.31 | 6148.68 | 05-JAN-07:10 | 2523456.58 | 16-AUG-15:10 |
PlantLoopCoolingDemand:HVAC | 10728.31 | 6148.68 | 05-JAN-07:10 | 2523456.58 | 16-AUG-15:10 |
CoolingCoils:PlantLoopCoolingDemand | 10728.31 | 6148.68 | 05-JAN-07:10 | 2523456.58 | 16-AUG-15:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 8816.21 | 0.00 | 20-MAY-24:00 | 0.00 | 26-JUN-15:20 |
Water:HVAC | 883.27 | 0.00 | 13-APR-19:00 | 0.00 | 02-FEB-04:10 |
Humidifier:Water | 883.27 | 0.00 | 13-APR-19:00 | 0.00 | 02-FEB-04:10 |
General:Humidifier:Water | 883.27 | 0.00 | 13-APR-19:00 | 0.00 | 02-FEB-04:10 |
MainsWater:Facility | 8816.21 | 0.00 | 20-MAY-24:00 | 0.00 | 26-JUN-15:20 |
MainsWater:HVAC | 883.27 | 0.00 | 13-APR-19:00 | 0.00 | 02-FEB-04:10 |
Humidifier:MainsWater | 883.27 | 0.00 | 13-APR-19:00 | 0.00 | 02-FEB-04:10 |
General:Humidifier:MainsWater | 883.27 | 0.00 | 13-APR-19:00 | 0.00 | 02-FEB-04:10 |
Water:Plant | 7932.94 | 0.00 | 01-JAN-00:10 | 0.00 | 26-JUN-15:20 |
WaterSystems:Water | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterUse:WaterSystems:Water | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
MainsWater:Plant | 7932.94 | 0.00 | 01-JAN-00:10 | 0.00 | 26-JUN-15:20 |
WaterSystems:MainsWater | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterUse:WaterSystems:MainsWater | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water Heater:WaterSystems:Water | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:MainsWater | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
HeatRejection:Water | 5652.77 | 0.00 | 01-JAN-00:10 | 0.00 | 26-JUN-16:30 |
General:HeatRejection:Water | 5652.77 | 0.00 | 01-JAN-00:10 | 0.00 | 26-JUN-16:30 |
HeatRejection:MainsWater | 5652.77 | 0.00 | 01-JAN-00:10 | 0.00 | 26-JUN-16:30 |
General:HeatRejection:MainsWater | 5652.77 | 0.00 | 01-JAN-00:10 | 0.00 | 26-JUN-16:30 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 51200.33 | 99522.23 | 08-JAN-03:30 | 9833991.81 | 16-AUG-15:10 |
EnergyTransfer:Building | 20102.16 | 88401.89 | 08-JAN-13:30 | 1781874.85 | 31-AUG-15:20 |
EnergyTransfer:Zone:BASEMENT | 718.91 | 0.00 | 01-JAN-00:40 | 75548.41 | 10-OCT-05:10 |
Heating:EnergyTransfer | 558.86 | 0.00 | 03-JAN-22:10 | 849929.70 | 26-DEC-06:10 |
Heating:EnergyTransfer:Zone:BASEMENT | 2.85 | 0.00 | 01-JAN-00:20 | 21011.65 | 15-JUL-16:10 |
General:Heating:EnergyTransfer | 558.86 | 0.00 | 03-JAN-22:10 | 849929.70 | 26-DEC-06:10 |
General:Heating:EnergyTransfer:Zone:BASEMENT | 2.85 | 0.00 | 01-JAN-00:20 | 21011.65 | 15-JUL-16:10 |
Cooling:EnergyTransfer | 19543.29 | 87102.25 | 08-JAN-05:30 | 1781874.85 | 31-AUG-15:20 |
Cooling:EnergyTransfer:Zone:BASEMENT | 716.07 | 0.00 | 01-JAN-00:40 | 75548.41 | 10-OCT-05:10 |
General:Cooling:EnergyTransfer | 19543.29 | 87102.25 | 08-JAN-05:30 | 1781874.85 | 31-AUG-15:20 |
General:Cooling:EnergyTransfer:Zone:BASEMENT | 716.07 | 0.00 | 01-JAN-00:40 | 75548.41 | 10-OCT-05:10 |
EnergyTransfer:Zone:CORE_BOTTOM | 645.82 | 0.00 | 01-JAN-00:10 | 56207.74 | 07-AUG-13:10 |
Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 645.82 | 0.00 | 01-JAN-00:10 | 56207.74 | 07-AUG-13:10 |
General:Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 645.82 | 0.00 | 01-JAN-00:10 | 56207.74 | 07-AUG-13:10 |
EnergyTransfer:Zone:CORE_MID | 4625.78 | 0.00 | 01-JAN-00:10 | 464965.01 | 18-JUL-13:10 |
Heating:EnergyTransfer:Zone:CORE_MID | 1.59 | 0.00 | 01-JAN-00:10 | 242586.29 | 26-DEC-06:10 |
General:Heating:EnergyTransfer:Zone:CORE_MID | 1.59 | 0.00 | 01-JAN-00:10 | 242586.29 | 26-DEC-06:10 |
Cooling:EnergyTransfer:Zone:CORE_MID | 4624.19 | 0.00 | 01-JAN-00:10 | 464965.01 | 18-JUL-13:10 |
General:Cooling:EnergyTransfer:Zone:CORE_MID | 4624.19 | 0.00 | 01-JAN-00:10 | 464965.01 | 18-JUL-13:10 |
EnergyTransfer:Zone:CORE_TOP | 424.01 | 0.00 | 01-JAN-00:10 | 71953.26 | 06-FEB-05:10 |
Heating:EnergyTransfer:Zone:CORE_TOP | 10.27 | 0.00 | 01-JAN-00:10 | 71953.26 | 06-FEB-05:10 |
General:Heating:EnergyTransfer:Zone:CORE_TOP | 10.27 | 0.00 | 01-JAN-00:10 | 71953.26 | 06-FEB-05:10 |
Cooling:EnergyTransfer:Zone:CORE_TOP | 413.73 | 0.00 | 01-JAN-00:10 | 56596.17 | 26-JUN-15:00 |
General:Cooling:EnergyTransfer:Zone:CORE_TOP | 413.73 | 0.00 | 01-JAN-00:10 | 56596.17 | 26-JUN-15:00 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 72.26 | 0.00 | 01-JAN-00:10 | 12721.13 | 17-JUL-13:30 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 0.97 | 0.00 | 01-JAN-00:10 | 9013.32 | 23-DEC-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 0.97 | 0.00 | 01-JAN-00:10 | 9013.32 | 23-DEC-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 71.29 | 0.00 | 01-JAN-00:10 | 12721.13 | 17-JUL-13:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 71.29 | 0.00 | 01-JAN-00:10 | 12721.13 | 17-JUL-13:30 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 82.66 | 0.00 | 01-JAN-00:10 | 16846.12 | 07-AUG-08:00 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 0.90 | 0.00 | 01-JAN-00:10 | 7037.77 | 23-DEC-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 0.90 | 0.00 | 01-JAN-00:10 | 7037.77 | 23-DEC-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 81.76 | 0.00 | 01-JAN-00:10 | 16846.12 | 07-AUG-08:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 81.76 | 0.00 | 01-JAN-00:10 | 16846.12 | 07-AUG-08:00 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 142.92 | 0.00 | 01-JAN-00:10 | 23414.93 | 07-NOV-13:20 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 1.43 | 0.00 | 01-JAN-00:10 | 9904.61 | 23-DEC-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 1.43 | 0.00 | 01-JAN-00:10 | 9904.61 | 23-DEC-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 141.50 | 0.00 | 01-JAN-00:10 | 23414.93 | 07-NOV-13:20 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 141.50 | 0.00 | 01-JAN-00:10 | 23414.93 | 07-NOV-13:20 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 112.74 | 0.00 | 01-JAN-00:10 | 22972.09 | 16-AUG-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 0.06 | 0.00 | 01-JAN-00:10 | 2422.62 | 05-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 0.06 | 0.00 | 01-JAN-00:10 | 2422.62 | 05-JAN-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 112.68 | 0.00 | 01-JAN-00:10 | 22972.09 | 16-AUG-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 112.68 | 0.00 | 01-JAN-00:10 | 22972.09 | 16-AUG-16:00 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 624.96 | 0.00 | 01-JAN-00:10 | 134160.17 | 23-DEC-05:30 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 122.68 | 0.00 | 01-JAN-00:10 | 134160.17 | 23-DEC-05:30 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 122.68 | 0.00 | 01-JAN-00:10 | 134160.17 | 23-DEC-05:30 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 502.28 | 0.00 | 01-JAN-00:10 | 119455.24 | 17-JUL-13:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 502.28 | 0.00 | 01-JAN-00:10 | 119455.24 | 17-JUL-13:30 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 786.83 | 0.00 | 01-JAN-00:10 | 179928.21 | 17-JUL-08:30 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 68.12 | 0.00 | 01-JAN-00:10 | 118750.67 | 23-DEC-05:30 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 68.12 | 0.00 | 01-JAN-00:10 | 118750.67 | 23-DEC-05:30 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 718.71 | 0.00 | 01-JAN-00:10 | 179928.21 | 17-JUL-08:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 718.71 | 0.00 | 01-JAN-00:10 | 179928.21 | 17-JUL-08:30 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 1368.44 | 0.00 | 01-JAN-00:10 | 266859.42 | 05-NOV-12:50 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 66.54 | 0.00 | 01-JAN-00:10 | 162077.52 | 21-DEC-05:30 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 66.54 | 0.00 | 01-JAN-00:10 | 162077.52 | 21-DEC-05:30 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 1301.89 | 0.00 | 01-JAN-00:10 | 266859.42 | 05-NOV-12:50 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 1301.89 | 0.00 | 01-JAN-00:10 | 266859.42 | 05-NOV-12:50 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 770.26 | 0.00 | 01-JAN-00:10 | 201945.56 | 16-AUG-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 50.64 | 0.00 | 01-JAN-00:10 | 109450.04 | 23-DEC-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 50.64 | 0.00 | 01-JAN-00:10 | 109450.04 | 23-DEC-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 719.62 | 0.00 | 01-JAN-00:10 | 201945.56 | 16-AUG-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 719.62 | 0.00 | 01-JAN-00:10 | 201945.56 | 16-AUG-16:00 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 79.72 | 0.00 | 01-JAN-00:10 | 16868.63 | 23-DEC-04:20 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 31.65 | 0.00 | 01-JAN-00:10 | 16868.63 | 23-DEC-04:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 31.65 | 0.00 | 01-JAN-00:10 | 16868.63 | 23-DEC-04:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 48.06 | 0.00 | 01-JAN-00:10 | 12928.91 | 17-JUL-13:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 48.06 | 0.00 | 01-JAN-00:10 | 12928.91 | 17-JUL-13:30 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 85.14 | 0.00 | 01-JAN-00:10 | 18198.12 | 17-JUL-08:30 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 17.01 | 0.00 | 01-JAN-00:10 | 16860.58 | 23-DEC-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 17.01 | 0.00 | 01-JAN-00:10 | 16860.58 | 23-DEC-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 68.13 | 0.00 | 01-JAN-00:10 | 18198.12 | 17-JUL-08:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 68.13 | 0.00 | 01-JAN-00:10 | 18198.12 | 17-JUL-08:30 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 141.77 | 0.00 | 01-JAN-00:10 | 25849.69 | 28-SEP-13:20 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 19.34 | 0.00 | 01-JAN-00:10 | 21026.60 | 21-DEC-05:30 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 19.34 | 0.00 | 01-JAN-00:10 | 21026.60 | 21-DEC-05:30 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 122.43 | 0.00 | 01-JAN-00:10 | 25849.69 | 28-SEP-13:20 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 122.43 | 0.00 | 01-JAN-00:10 | 25849.69 | 28-SEP-13:20 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 82.37 | 0.00 | 01-JAN-00:10 | 20994.46 | 16-AUG-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 13.42 | 0.00 | 01-JAN-00:10 | 15184.15 | 23-DEC-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 13.42 | 0.00 | 01-JAN-00:10 | 15184.15 | 23-DEC-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 68.95 | 0.00 | 01-JAN-00:10 | 20994.46 | 16-AUG-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 68.95 | 0.00 | 01-JAN-00:10 | 20994.46 | 16-AUG-16:00 |
EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 68.09 | 0.00 | 01-JAN-00:10 | 10478.97 | 17-JUL-10:20 |
Heating:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 2.44 | 0.00 | 01-JAN-00:10 | 5105.45 | 25-DEC-10:50 |
General:Heating:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 2.44 | 0.00 | 01-JAN-00:10 | 5105.45 | 25-DEC-10:50 |
Cooling:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 65.65 | 0.00 | 01-JAN-00:10 | 10478.97 | 17-JUL-10:20 |
General:Cooling:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 65.65 | 0.00 | 01-JAN-00:10 | 10478.97 | 17-JUL-10:20 |
EnergyTransfer:Zone:MIDFLOOR_PLENUM | 521.55 | 0.00 | 01-JAN-00:10 | 89344.96 | 17-JUL-16:00 |
Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 103.36 | 0.00 | 01-JAN-00:10 | 81358.63 | 26-DEC-06:10 |
General:Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 103.36 | 0.00 | 01-JAN-00:10 | 81358.63 | 26-DEC-06:10 |
Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 418.18 | 0.00 | 01-JAN-00:10 | 89344.96 | 17-JUL-16:00 |
General:Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 418.18 | 0.00 | 01-JAN-00:10 | 89344.96 | 17-JUL-16:00 |
EnergyTransfer:Zone:TOPFLOOR_PLENUM | 113.38 | 0.00 | 01-JAN-00:10 | 26968.94 | 13-FEB-05:10 |
Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 43.45 | 0.00 | 01-JAN-00:10 | 26968.94 | 13-FEB-05:10 |
General:Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 43.45 | 0.00 | 01-JAN-00:10 | 26968.94 | 13-FEB-05:10 |
Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 69.93 | 0.00 | 01-JAN-00:10 | 24198.52 | 26-JUN-13:40 |
General:Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 69.93 | 0.00 | 01-JAN-00:10 | 24198.52 | 26-JUN-13:40 |
EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 139.33 | 481.38 | 06-JAN-06:00 | 8763.50 | 05-AUG-18:30 |
Heating:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 139.33 | 481.38 | 06-JAN-06:00 | 8763.50 | 05-AUG-18:30 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 139.33 | 481.38 | 06-JAN-06:00 | 8763.50 | 05-AUG-18:30 |
EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 1205.48 | 5.91 | 14-JAN-04:50 | 83195.26 | 13-AUG-18:40 |
Heating:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 1.34 | 0.00 | 01-JAN-14:40 | 6484.74 | 01-JAN-08:00 |
General:Heating:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 1.34 | 0.00 | 01-JAN-14:40 | 6484.74 | 01-JAN-08:00 |
Cooling:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 1204.14 | 0.00 | 01-JAN-00:10 | 83195.26 | 13-AUG-18:40 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 1204.14 | 0.00 | 01-JAN-00:10 | 83195.26 | 13-AUG-18:40 |
EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 111.09 | 0.82 | 28-JAN-10:20 | 8460.13 | 13-AUG-18:30 |
Heating:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 0.82 | 0.00 | 02-JAN-11:30 | 757.31 | 30-APR-23:20 |
General:Heating:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 0.82 | 0.00 | 02-JAN-11:30 | 757.31 | 30-APR-23:20 |
Cooling:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 110.27 | 0.00 | 01-JAN-00:10 | 8460.13 | 13-AUG-18:30 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 110.27 | 0.00 | 01-JAN-00:10 | 8460.13 | 13-AUG-18:30 |
EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 7178.66 | 86442.28 | 08-JAN-08:40 | 379429.13 | 16-AUG-21:40 |
Heating:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 7178.66 | 86442.28 | 08-JAN-08:40 | 379429.13 | 16-AUG-21:40 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 7178.66 | 86442.28 | 08-JAN-08:40 | 379429.13 | 16-AUG-21:40 |
PlantLoopHeatingDemand:Facility | 1856.04 | 0.00 | 01-JAN-00:10 | 1286033.37 | 23-DEC-07:10 |
PlantLoopHeatingDemand:Plant | 435.47 | 0.00 | 01-JAN-00:10 | 53786.41 | 15-FEB-12:40 |
WaterSystems:PlantLoopHeatingDemand | 435.47 | 0.00 | 01-JAN-00:10 | 53786.41 | 15-FEB-12:40 |
General:WaterSystems:PlantLoopHeatingDemand | 435.47 | 0.00 | 01-JAN-00:10 | 53786.41 | 15-FEB-12:40 |
EnergyTransfer:HVAC | 10922.05 | 5337.34 | 01-JAN-08:10 | 2304203.02 | 16-AUG-15:10 |
HeatingCoils:EnergyTransfer | 1420.58 | 0.00 | 01-JAN-00:10 | 1276165.38 | 23-DEC-07:10 |
PlantLoopHeatingDemand:HVAC | 1420.58 | 0.00 | 01-JAN-00:10 | 1276165.38 | 23-DEC-07:10 |
HeatingCoils:PlantLoopHeatingDemand | 1420.58 | 0.00 | 01-JAN-00:10 | 1276165.38 | 23-DEC-07:10 |
CoolingCoils:EnergyTransfer | 9501.47 | 3988.69 | 05-JAN-07:10 | 2304203.02 | 16-AUG-15:10 |
EnergyTransfer:Plant | 20176.12 | 0.00 | 01-JAN-00:10 | 5893455.93 | 26-JUN-15:20 |
LoopToLoop:EnergyTransfer | 5831.88 | 0.00 | 01-JAN-00:10 | 1869907.48 | 26-JUN-14:10 |
WaterSystems:EnergyTransfer | 435.47 | 0.00 | 01-JAN-00:10 | 53786.41 | 15-FEB-12:40 |
WaterUse:WaterSystems:EnergyTransfer | 435.47 | 0.00 | 01-JAN-00:10 | 53786.41 | 15-FEB-12:40 |
Boilers:EnergyTransfer | 1407.85 | 0.00 | 01-JAN-00:10 | 1260167.13 | 23-DEC-07:10 |
Chillers:EnergyTransfer | 5827.79 | 0.00 | 01-JAN-00:10 | 1873500.72 | 26-JUN-15:20 |
HeatRejection:EnergyTransfer | 6673.14 | 0.00 | 01-JAN-00:10 | 2121564.05 | 26-JUN-15:20 |
General:HeatRejection:EnergyTransfer | 6673.14 | 0.00 | 01-JAN-00:10 | 2121564.05 | 26-JUN-15:20 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 08:43:27
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
BASEMENT | 0.000 | 0.000 | 2.848 | -716.063 | 0.000 | 0.000 | 92.717 | 262.844 | 424.397 | 0.000 | 0.000 | 0.000 | 0.001 | 0.000 | 0.000 | 0.000 | 0.000 | -66.743 |
CORE_BOTTOM | 0.000 | 0.000 | 0.000 | -645.817 | 0.000 | 0.000 | 83.437 | 236.053 | 289.614 | 0.000 | 0.000 | 0.000 | 36.714 | 0.000 | 0.000 | 0.000 | 0.000 | -0.001 |
CORE_MID | 0.000 | 0.000 | 1.586 | -4624.170 | 0.000 | 0.000 | 843.639 | 2360.527 | 2896.128 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -1477.711 |
CORE_TOP | 0.000 | 0.000 | 10.271 | -413.731 | 0.000 | 0.000 | 87.037 | 236.053 | 289.613 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -209.242 |
PERIMETER_BOT_ZN_3 | 0.000 | 0.000 | 0.965 | -71.292 | 0.000 | 0.000 | 10.860 | 17.333 | 36.365 | 35.958 | 0.000 | 0.123 | 57.994 | 0.000 | -81.816 | 0.000 | -6.491 | 0.000 |
PERIMETER_BOT_ZN_2 | 0.000 | 0.000 | 0.896 | -81.762 | 0.000 | 0.000 | 7.020 | 11.135 | 23.435 | 84.874 | 0.000 | 0.086 | 9.430 | 0.000 | -50.845 | 0.000 | -4.268 | -0.001 |
PERIMETER_BOT_ZN_1 | 0.000 | 0.000 | 1.425 | -141.495 | 0.000 | 0.000 | 10.705 | 17.045 | 36.366 | 176.486 | 0.000 | 0.122 | 0.004 | 0.000 | -76.530 | 0.000 | -6.573 | -17.551 |
PERIMETER_BOT_ZN_4 | 0.000 | 0.000 | 0.062 | -112.681 | 0.000 | 0.000 | 6.934 | 10.987 | 23.435 | 76.565 | 0.000 | 0.079 | 56.703 | 0.000 | -57.392 | 0.000 | -4.692 | 0.000 |
PERIMETER_MID_ZN_3 | 0.000 | 0.000 | 122.677 | -502.280 | 0.000 | 0.000 | 113.462 | 172.994 | 363.654 | 373.541 | 0.000 | 2.870 | 235.138 | 0.000 | -745.465 | 0.000 | -136.591 | 0.000 |
PERIMETER_MID_ZN_2 | 0.000 | 0.000 | 68.118 | -718.708 | 0.000 | 0.000 | 52.946 | 111.193 | 234.352 | 849.177 | 0.000 | 1.927 | 0.007 | 0.000 | -479.402 | 0.000 | -93.290 | -26.313 |
PERIMETER_MID_ZN_1 | 0.000 | 0.000 | 66.542 | -1301.881 | 0.000 | 0.000 | 108.064 | 170.267 | 363.660 | 1757.271 | 0.000 | 2.787 | 0.057 | 0.000 | -742.864 | 0.000 | -147.027 | -276.817 |
PERIMETER_MID_ZN_4 | 0.000 | 0.000 | 50.638 | -719.617 | 0.000 | 0.000 | 72.973 | 109.749 | 234.351 | 782.070 | 0.000 | 1.917 | 71.396 | 0.000 | -507.724 | 0.000 | -95.753 | 0.000 |
PERIMETER_TOP_ZN_3 | 0.000 | 0.000 | 31.654 | -48.064 | 0.000 | 0.000 | 11.498 | 17.298 | 36.365 | 37.858 | 0.000 | 0.343 | 0.000 | 0.000 | -70.677 | 0.000 | -16.130 | -0.146 |
PERIMETER_TOP_ZN_2 | 0.000 | 0.000 | 17.009 | -68.126 | 0.000 | 0.000 | 7.244 | 11.119 | 23.435 | 85.239 | 0.000 | 0.228 | 0.001 | 0.000 | -45.748 | 0.000 | -11.084 | -19.315 |
PERIMETER_TOP_ZN_1 | 0.000 | 0.000 | 19.340 | -122.428 | 0.000 | 0.000 | 10.958 | 17.026 | 36.366 | 176.299 | 0.000 | 0.335 | 0.005 | 0.000 | -70.647 | 0.000 | -17.386 | -49.863 |
PERIMETER_TOP_ZN_4 | 0.000 | 0.000 | 13.418 | -68.949 | 0.000 | 0.000 | 7.367 | 10.974 | 23.435 | 78.358 | 0.000 | 0.232 | 0.000 | 0.000 | -48.572 | 0.000 | -11.398 | -4.864 |
DATACENTER_BOT_ZN_6 | 0.000 | 0.000 | 0.000 | -139.332 | 0.000 | 0.000 | 0.949 | 6.628 | 153.881 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -22.126 |
DATACENTER_MID_ZN_6 | 0.000 | 0.000 | 1.339 | -1204.140 | 0.000 | 0.000 | 9.496 | 66.280 | 1538.806 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -411.781 |
DATACENTER_TOP_ZN_6 | 0.000 | 0.000 | 0.821 | -110.268 | 0.000 | 0.000 | 0.951 | 6.628 | 153.881 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -52.012 |
DATACENTER_BASEMENT_ZN_6 | 0.000 | 0.000 | 0.000 | -7178.667 | 0.000 | 0.000 | 20.149 | 74.111 | 7494.857 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -410.450 |
GROUNDFLOOR_PLENUM | 2.441 | -65.654 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.228 | 77.050 | 0.000 | 0.000 | 0.000 | -14.065 | 0.000 |
MIDFLOOR_PLENUM | 103.367 | -418.180 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 4.225 | 550.504 | 0.000 | 0.000 | 0.000 | -239.915 | -0.001 |
TOPFLOOR_PLENUM | 43.446 | -69.931 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.365 | 51.471 | 0.000 | 0.000 | 0.000 | -25.352 | -0.004 |
Total Facility | 149.254 | -553.764 | 409.611 | -18989.471 | 0.000 | 0.000 | 1558.406 | 3926.244 | 14676.396 | 4513.695 | 0.000 | 15.866 | 1146.475 | 0.000 | -2977.684 | 0.000 | -830.018 | -3044.941 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | 12-NOV-11:30 | 0.00 | 0.00 | 0.00 | -120836.56 | 0.00 | 0.00 | 399.95 | 1274.92 | 13457.54 | 0.00 | 0.00 | 0.00 | 105704.15 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 14-JUN-04:13 | 0.00 | 0.00 | 0.00 | -99350.64 | 0.00 | 0.00 | 0.00 | 2290.20 | 5937.65 | 0.00 | 0.00 | 0.00 | 91122.79 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 28-AUG-04:12 | 0.00 | 0.00 | 0.00 | -888466.54 | 0.00 | 0.00 | 0.00 | 22901.98 | 59376.23 | 0.00 | 0.00 | 0.00 | 806188.33 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 24-JUL-04:12 | 0.00 | 0.00 | 0.00 | -88001.56 | 0.00 | 0.00 | 0.00 | 2290.20 | 5937.62 | 0.00 | 0.00 | 0.00 | 79773.74 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 16-JUL-13:22 | 0.00 | 0.00 | 0.00 | -18372.85 | 0.00 | 0.00 | 39.21 | 68.40 | 720.18 | 9716.32 | 0.00 | 235.61 | 7593.13 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 06-AUG-08:11 | 0.00 | 0.00 | 0.00 | -28452.93 | 0.00 | 0.00 | 17.37 | 44.08 | 464.11 | 23534.73 | 0.00 | 0.00 | 4463.67 | 0.00 | -0.00 | 0.00 | -71.03 | 0.00 |
PERIMETER_BOT_ZN_1 | 09-OCT-12:31 | 0.00 | 0.00 | 0.00 | -32348.86 | 0.00 | 0.00 | 25.09 | 68.40 | 720.19 | 33356.50 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -79.33 | -1742.00 |
PERIMETER_BOT_ZN_4 | 13-AUG-16:41 | 0.00 | 0.00 | 0.00 | -37174.01 | 0.00 | 0.00 | 12.11 | 44.08 | 464.11 | 22489.79 | 0.00 | 0.00 | 14252.96 | 0.00 | -0.00 | 0.00 | -89.04 | 0.00 |
PERIMETER_MID_ZN_3 | 16-JUL-14:51 | 0.00 | 0.00 | 0.00 | -179743.19 | 0.00 | 0.00 | 375.03 | 684.02 | 7201.84 | 83306.95 | 0.00 | 6491.77 | 81683.58 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 06-AUG-08:51 | 0.00 | 0.00 | 0.00 | -311562.59 | 0.00 | 0.00 | 154.84 | 440.81 | 4641.14 | 212035.96 | 0.00 | 0.00 | 95266.17 | 0.00 | -0.00 | 0.00 | -976.33 | 0.00 |
PERIMETER_MID_ZN_1 | 05-NOV-13:21 | 0.00 | 0.00 | 0.00 | -340105.74 | 0.00 | 0.00 | 190.91 | 684.04 | 7201.95 | 358279.20 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -1093.90 | -25156.44 |
PERIMETER_MID_ZN_4 | 11-JUN-16:51 | 0.00 | 0.00 | 0.00 | -348117.66 | 0.00 | 0.00 | 127.40 | 440.81 | 4641.11 | 216308.71 | 0.00 | 0.00 | 127273.99 | 0.00 | -0.00 | 0.00 | -674.36 | 0.00 |
PERIMETER_TOP_ZN_3 | 16-JUL-15:02 | 0.00 | 0.00 | 0.00 | -19541.46 | 0.00 | 0.00 | 35.65 | 68.40 | 720.18 | 7005.50 | 0.00 | 858.94 | 10852.78 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 11-JUN-08:21 | 0.00 | 0.00 | 0.00 | -28600.52 | 0.00 | 0.00 | 19.30 | 44.08 | 464.11 | 19417.06 | 0.00 | 0.00 | 9046.10 | 0.00 | -0.00 | 0.00 | -390.13 | 0.00 |
PERIMETER_TOP_ZN_1 | 05-NOV-13:31 | 0.00 | 0.00 | 0.00 | -35787.53 | 0.00 | 0.00 | 21.27 | 68.40 | 720.19 | 34718.13 | 0.00 | 0.00 | 405.10 | 0.00 | -0.00 | 0.00 | -145.58 | 0.00 |
PERIMETER_TOP_ZN_4 | 11-JUN-17:01 | 0.00 | 0.00 | 0.00 | -36351.14 | 0.00 | 0.00 | 0.00 | 44.08 | 360.35 | 21188.18 | 0.00 | 0.00 | 14852.62 | 0.00 | -0.00 | 0.00 | -94.09 | 0.00 |
DATACENTER_BOT_ZN_6 | 05-AUG-18:21 | 0.00 | 0.00 | 0.00 | -8767.14 | 0.00 | 0.00 | 0.00 | 32.15 | 7794.42 | 0.00 | 0.00 | 0.00 | 940.56 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 13-AUG-18:34 | 0.00 | 0.00 | 0.00 | -83339.94 | 0.00 | 0.00 | 0.00 | 321.53 | 77944.22 | 0.00 | 0.00 | 0.00 | 5074.19 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 13-AUG-18:30 | 0.00 | 0.00 | 0.00 | -8469.31 | 0.00 | 0.00 | 0.00 | 32.15 | 7794.42 | 0.00 | 0.00 | 0.00 | 642.74 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 16-AUG-21:12 | 0.00 | 0.00 | 0.00 | -384667.40 | 0.00 | 0.00 | 103.43 | 719.03 | 379632.52 | 0.00 | 0.00 | 0.00 | 4212.41 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 21-AUG-05:15 | 0.00 | -12261.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12315.76 | 0.00 | -0.00 | 0.00 | -53.98 | 0.00 |
MIDFLOOR_PLENUM | 19-MAR-06:32 | 0.00 | -155648.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 239302.27 | 0.00 | -0.00 | 0.00 | -83654.02 | 0.00 |
TOPFLOOR_PLENUM | 26-JUN-13:40 | 0.00 | -24196.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 161.52 | 24034.84 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 17-JUL-04:12 | 0.00 | 49711.01 | 0.00 | -1996026.20 | 0.00 | 0.00 | 0.00 | 42872.09 | 469008.02 | 0.00 | 0.00 | 0.00 | 1542050.10 | 0.00 | -86758.15 | 0.00 | -20856.87 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | 15-JUL-16:01 | 0.00 | 0.00 | 22334.48 | 0.00 | 0.00 | 0.00 | 520.13 | 1274.92 | 13457.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -37587.08 |
CORE_BOTTOM | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 26-DEC-05:11 | 0.00 | 0.00 | 445393.87 | 0.00 | 0.00 | 0.00 | 0.00 | 22901.98 | 59376.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -527672.08 |
CORE_TOP | 06-FEB-04:01 | 0.00 | 0.00 | 83329.77 | 0.00 | 0.00 | 0.00 | 0.00 | 1144.97 | 5937.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -90412.36 |
PERIMETER_BOT_ZN_3 | 22-DEC-05:01 | 0.00 | 0.00 | 13976.65 | 0.00 | 0.00 | 0.00 | 0.00 | 287.56 | 745.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -8886.22 | 0.00 | -360.85 | -5762.70 |
PERIMETER_BOT_ZN_2 | 20-DEC-05:01 | 0.00 | 0.00 | 13190.35 | 0.00 | 0.00 | 0.00 | 0.00 | 185.31 | 480.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -5659.47 | 0.00 | -633.79 | -7562.88 |
PERIMETER_BOT_ZN_1 | 06-FEB-04:01 | 0.00 | 0.00 | 19110.05 | 0.00 | 0.00 | 0.00 | 0.00 | 143.77 | 745.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -6461.98 | 0.00 | -635.62 | -12901.79 |
PERIMETER_BOT_ZN_4 | 21-DEC-05:01 | 0.00 | 0.00 | 9611.16 | 0.00 | 0.00 | 0.00 | 0.00 | 185.31 | 480.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -7467.08 | 0.00 | -610.13 | -2199.73 |
PERIMETER_MID_ZN_3 | 19-MAR-06:32 | 0.00 | 0.00 | 158440.93 | 0.00 | 0.00 | 0.00 | 906.78 | 1437.63 | 7201.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -70437.30 | 0.00 | -45685.91 | -51863.98 |
PERIMETER_MID_ZN_2 | 19-MAR-06:32 | 0.00 | 0.00 | 204101.74 | 0.00 | 0.00 | 0.00 | 586.57 | 926.46 | 4641.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -44742.14 | 0.00 | -31302.87 | -134210.89 |
PERIMETER_MID_ZN_1 | 19-MAR-06:32 | 0.00 | 0.00 | 230929.99 | 0.00 | 0.00 | 0.00 | 903.53 | 1437.66 | 7201.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -67574.03 | 0.00 | -46647.73 | -126251.38 |
PERIMETER_MID_ZN_4 | 24-DEC-06:51 | 0.00 | 0.00 | 204911.75 | 0.00 | 0.00 | 0.00 | 582.53 | 926.46 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -53827.98 | 0.00 | -23319.75 | -133914.11 |
PERIMETER_TOP_ZN_3 | 19-MAR-05:31 | 0.00 | 0.00 | 18747.30 | 0.00 | 0.00 | 0.00 | 92.63 | 143.76 | 720.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -7304.12 | 0.00 | -4193.69 | -8206.07 |
PERIMETER_TOP_ZN_2 | 23-DEC-04:11 | 0.00 | 0.00 | 23653.78 | 0.00 | 0.00 | 0.00 | 0.00 | 92.65 | 360.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -5568.80 | 0.00 | -1967.29 | -16570.69 |
PERIMETER_TOP_ZN_1 | 19-MAR-05:31 | 0.00 | 0.00 | 26352.23 | 0.00 | 0.00 | 0.00 | 92.62 | 143.77 | 720.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -7308.57 | 0.00 | -4255.48 | -15744.76 |
PERIMETER_TOP_ZN_4 | 19-MAR-02:11 | 0.00 | 0.00 | 25104.44 | 0.00 | 0.00 | 0.00 | 0.00 | 92.65 | 360.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -4417.19 | 0.00 | -3473.06 | -17667.19 |
DATACENTER_BOT_ZN_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 01-JAN-08:00 | 0.00 | 0.00 | 6484.77 | 0.00 | 0.00 | 0.00 | 53.08 | 321.53 | 19486.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -26345.43 |
DATACENTER_TOP_ZN_6 | 30-APR-23:20 | 0.00 | 0.00 | 757.31 | 0.00 | 0.00 | 0.00 | 0.00 | 32.15 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -2738.07 |
DATACENTER_BASEMENT_ZN_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 05-NOV-14:21 | 15310.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -76.87 | -15233.49 |
MIDFLOOR_PLENUM | 26-MAR-16:01 | 175274.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -7481.45 | -167792.67 |
TOPFLOOR_PLENUM | 22-DEC-05:12 | 32856.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -1822.09 | -31034.20 |
Total Facility | 26-DEC-05:11 | -546443.48 | 526962.23 | 1355961.94 | -526962.23 | 0.00 | 0.00 | 0.00 | 42872.09 | 587299.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -119541.46 | 0.00 | -70415.26 | -1249733.24 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 08:43:27
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
VAV_BOT WITH REHEAT | 14.6199 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 12.5549 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_MID WITH REHEAT | 140.9405 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 117.7195 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_TOP WITH REHEAT | 14.3787 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 13.1065 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
CAV_BAS | 7.2839 | 0.0000 | 149.6021 | 1.0000 | Calculated from schedules | 1.2002 | 7.2839 | 0.1648 | 1.0000 | Not calculated | 1.2002 | 0.1648 | ||
AIRLOOP DATACENTER BASEMENT | 26.4142 | 0.0000 | 42.1814 | 1.0000 | Calculated from schedules | 0.3384 | 26.4144 | 0.0128 | 1.0000 | Not calculated | 0.3384 | 0.0128 | ||
AIRLOOP DATACENTER BOT | 0.6227 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.6227 | 0.0251 | 1.0000 | Not calculated | 0.0156 | 0.0251 | ||
AIRLOOP DATACENTER MID | 5.9829 | 0.0000 | 19.4861 | 1.0000 | Calculated from schedules | 0.1563 | 5.9829 | 0.0261 | 1.0000 | Not calculated | 0.1563 | 0.0261 | ||
AIRLOOP DATACENTER TOP | 0.6095 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.6095 | 0.0256 | 1.0000 | Not calculated | 0.0156 | 0.0256 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
VAV_BOT WITH REHEAT | 7.3100 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 3.4710 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_MID WITH REHEAT | 70.4702 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 34.2756 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_TOP WITH REHEAT | 7.1894 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 3.5583 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
CAV_BAS | 7.2839 | 0.0000 | 149.6021 | 1.0000 | Calculated from schedules | 1.2002 | 7.2839 | 1.0000 | 1.0000 | Not calculated | 1.2002 | 0.1648 | ||
AIRLOOP DATACENTER BASEMENT | 26.4142 | 0.0000 | 42.1814 | 1.0000 | Calculated from schedules | 0.3384 | 26.4142 | 1.0000 | 1.0000 | Not calculated | 0.3384 | 0.0128 | ||
AIRLOOP DATACENTER BOT | 0.6227 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.6227 | 1.0000 | 1.0000 | Not calculated | 0.0156 | 0.0251 | ||
AIRLOOP DATACENTER MID | 5.9829 | 0.0000 | 19.4861 | 1.0000 | Calculated from schedules | 0.1563 | 5.9829 | 1.0000 | 1.0000 | Not calculated | 0.1563 | 0.0261 | ||
AIRLOOP DATACENTER TOP | 0.6095 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.6095 | 1.0000 | 1.0000 | Not calculated | 0.0156 | 0.0256 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
BASEMENT | CAV_BAS | 0.000000 | 149.6021 | 0.000432 | 2779.43 | 1.2002 | 1.0000 | 1.2002 | 1.000 | 1.2002 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | 0.000000 | 134.3532 | 0.000432 | 2496.12 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_MID | VAV_MID WITH REHEAT | 0.000000 | 1343.5320 | 0.000432 | 24961.20 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_TOP | VAV_TOP WITH REHEAT | 0.000000 | 134.3532 | 0.000432 | 2496.12 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | 0.000000 | 16.8694 | 0.000432 | 313.41 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | 0.000000 | 16.8698 | 0.000432 | 313.42 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | 0.000000 | 168.6939 | 0.000432 | 3134.13 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | 0.000000 | 108.7127 | 0.000432 | 2019.75 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | 0.000000 | 168.6975 | 0.000432 | 3134.20 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | 0.000000 | 108.7127 | 0.000432 | 2019.75 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | 0.000000 | 16.8694 | 0.000432 | 313.41 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | 0.000000 | 16.8698 | 0.000432 | 313.42 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | 0.000000 | 1.9486 | 0.000432 | 36.20 | 0.0156 | 1.0000 | 0.0156 | 1.000 | 0.0156 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | 0.000000 | 19.4861 | 0.000432 | 362.03 | 0.1563 | 1.0000 | 0.1563 | 1.000 | 0.1563 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | 0.000000 | 1.9486 | 0.000432 | 36.20 | 0.0156 | 1.0000 | 0.0156 | 1.000 | 0.0156 |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | 0.000000 | 42.1814 | 0.000432 | 783.68 | 0.3384 | 1.0000 | 0.3384 | 1.000 | 0.3384 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
VAV_BOT WITH REHEAT | 0.00 | 0.000432 | 3526.9033 | 0.0000 | 0.0000 | 0.0000 | |
VAV_MID WITH REHEAT | 0.00 | 0.000432 | 35269.0328 | 0.0000 | 0.0000 | 0.0000 | |
VAV_TOP WITH REHEAT | 0.00 | 0.000432 | 3526.9033 | 0.0000 | 0.0000 | 0.0000 | |
CAV_BAS | 0.000000 | 149.60 | 0.000432 | 2779.4266 | 1.2002 | 1.2002 | 1.2002 |
AIRLOOP DATACENTER BASEMENT | 0.000000 | 42.18 | 0.000432 | 783.6794 | 0.3384 | 0.3384 | 0.3384 |
AIRLOOP DATACENTER BOT | 0.000000 | 1.95 | 0.000432 | 36.2027 | 0.0156 | 0.0156 | 0.0156 |
AIRLOOP DATACENTER MID | 0.000000 | 19.49 | 0.000432 | 362.0274 | 0.1563 | 0.1563 | 0.1563 |
AIRLOOP DATACENTER TOP | 0.000000 | 1.95 | 0.000432 | 36.2027 | 0.0156 | 0.0156 | 0.0156 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | CAV_BAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 7.2839 | 7.2839 | 7.2839 | No | 1.2002 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 7.5972 | 7.5972 | 2.0664 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 71.7295 | 71.7295 | 20.3712 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 7.0362 | 7.0362 | 2.0898 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.3094 | 1.3094 | 0.2619 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.7076 | 1.7076 | 0.3415 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.8711 | 1.8711 | 0.3742 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.1346 | 2.1346 | 0.4269 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 12.4499 | 12.4499 | 2.5522 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 18.1941 | 18.1941 | 3.6388 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 18.5586 | 18.5586 | 3.7117 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 20.0085 | 20.0085 | 4.0017 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.4062 | 1.4062 | 0.2812 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.8228 | 1.8228 | 0.3646 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.0044 | 2.0044 | 0.4009 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.1091 | 2.1091 | 0.4218 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.6227 | 0.6227 | 0.6227 | No | 0.0156 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 5.9829 | 5.9829 | 5.9829 | No | 0.1563 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.6095 | 0.6095 | 0.6095 | No | 0.0156 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 26.4142 | 26.4142 | 26.4142 | No | 0.3384 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
VAV_BOT WITH REHEAT | 14.6199 | 12.5549 | 14.6199 | 3.4710 | 0.0000 | 1.0000 |
VAV_MID WITH REHEAT | 140.9405 | 117.7195 | 140.9405 | 34.2756 | 0.0000 | 1.0000 |
VAV_TOP WITH REHEAT | 14.3787 | 13.1065 | 14.3787 | 3.5583 | 0.0000 | 1.0000 |
CAV_BAS | 7.2839 | 7.2839 | 7.2839 | 7.2839 | 1.2002 | 1.0000 |
AIRLOOP DATACENTER BASEMENT | 26.4142 | 26.4144 | 26.4142 | 26.4142 | 0.3384 | 1.0000 |
AIRLOOP DATACENTER BOT | 0.6227 | 0.6227 | 0.6227 | 0.6227 | 0.0156 | 1.0000 |
AIRLOOP DATACENTER MID | 5.9829 | 5.9829 | 5.9829 | 5.9829 | 0.1563 | 1.0000 |
AIRLOOP DATACENTER TOP | 0.6095 | 0.6095 | 0.6095 | 0.6095 | 0.0156 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | CAV_BAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 7.2839 | 7.2839 | 7.2839 | No | 1.2002 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 3.7986 | 3.7986 | 2.0664 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 35.8647 | 35.8647 | 20.3712 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 3.5181 | 3.5181 | 2.0898 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6547 | 0.6547 | 0.2619 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8538 | 0.8538 | 0.3415 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.9356 | 0.9356 | 0.3742 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.0673 | 1.0673 | 0.4269 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 6.2249 | 6.2249 | 2.5522 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 9.0970 | 9.0970 | 3.6388 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 9.2793 | 9.2793 | 3.7117 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 10.0042 | 10.0042 | 4.0017 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7031 | 0.7031 | 0.2812 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.9114 | 0.9114 | 0.3646 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.0022 | 1.0022 | 0.4009 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.0546 | 1.0546 | 0.4218 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.6227 | 0.6227 | 0.6227 | No | 0.0156 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 5.9829 | 5.9829 | 5.9829 | No | 0.1563 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.6095 | 0.6095 | 0.6095 | No | 0.0156 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 26.4142 | 26.4142 | 26.4142 | No | 0.3384 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
VAV_BOT WITH REHEAT | 7.3100 | 3.4710 | 3.4710 | 3.4710 | 0.0000 | 1.0000 |
VAV_MID WITH REHEAT | 70.4702 | 34.2756 | 34.2756 | 34.2756 | 0.0000 | 1.0000 |
VAV_TOP WITH REHEAT | 7.1894 | 3.5583 | 3.5583 | 3.5583 | 0.0000 | 1.0000 |
CAV_BAS | 7.2839 | 7.2839 | 7.2839 | 7.2839 | 1.2002 | 1.0000 |
AIRLOOP DATACENTER BASEMENT | 26.4142 | 26.4142 | 26.4142 | 26.4142 | 0.3384 | 1.0000 |
AIRLOOP DATACENTER BOT | 0.6227 | 0.6227 | 0.6227 | 0.6227 | 0.0156 | 1.0000 |
AIRLOOP DATACENTER MID | 5.9829 | 5.9829 | 5.9829 | 5.9829 | 0.1563 | 1.0000 |
AIRLOOP DATACENTER TOP | 0.6095 | 0.6095 | 0.6095 | 0.6095 | 0.0156 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 08:43:27
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Denver-Aurora-Buckley AFB CO USA TMY3 WMO#=724695 |
Total gross floor area [m2] | 46320.38 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
BASEMENT | 2779.43 | 2779.43 | 0.00 | 113.98 |
CORE_BOTTOM | 2496.12 | 2496.12 | 0.00 | 113.98 |
CORE_MID | 2496.12 | 2496.12 | 0.00 | 113.98 |
CORE_TOP | 2496.12 | 2496.12 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_3 | 313.41 | 313.41 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_2 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_1 | 313.42 | 313.42 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_4 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_MID_ZN_3 | 313.41 | 313.41 | 0.00 | 113.98 |
PERIMETER_MID_ZN_2 | 201.98 | 201.98 | 0.00 | 96.54 |
PERIMETER_MID_ZN_1 | 313.42 | 313.42 | 0.00 | 113.98 |
PERIMETER_MID_ZN_4 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_3 | 313.41 | 313.41 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_2 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_1 | 313.42 | 313.42 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_4 | 201.98 | 201.98 | 0.00 | 113.98 |
DATACENTER_BOT_ZN_6 | 36.20 | 36.20 | 0.00 | 113.98 |
DATACENTER_MID_ZN_6 | 36.20 | 36.20 | 0.00 | 113.98 |
DATACENTER_TOP_ZN_6 | 36.20 | 36.20 | 0.00 | 113.98 |
DATACENTER_BASEMENT_ZN_6 | 783.68 | 783.68 | 0.00 | 113.98 |
GROUNDFLOOR_PLENUM | 3563.11 | 3563.11 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 3563.11 | 3563.11 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 3563.11 | 3563.11 | 0.00 | 0.00 |
Totals | 46320.38 | 46320.38 | 0.00 |
Data | |
Number of hours heating loads not met | 60.50 |
Number of hours cooling loads not met | 577.17 |
Number of hours not met | 637.67 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler | 0.00 | 0.00 | 1866.34 | 1508880.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 2072.18 | 462978.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 3926.24 | 385834.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 697.85 | 57580.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 5334.97 | 305206.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- DataCenterPlugLoads | 9341.42 | 473165.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Transformer | 80.18 | 5057.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLift | 1848.78 | 113101.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLightsFan | 5.83 | 376.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 2955.25 | 371803.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 405.38 | 59450.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- General | 590.73 | 83748.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- General | 2374.39 | 100000.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 0.00 | 0.00 | 813.65 | 85997.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 14676.40 | 29633.21 |
Natural Gas | 0.00 | 2680.00 |
Additional | 0.00 | 0.00 |
Total | 14676.40 | 32313.20 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 84.76 |
Space Heating | 0.00 |
Space Cooling | 44.74 |
Fans (All) | 63.80 |
Service Water Heating | 0.00 |
Receptacle Equipment | 316.85 |
Miscellaneous (All) | 639.74 |
Subtotal | 639.74 |
Natural Gas [MJ/m2] | |
Space Heating | 40.29 |
Service Water Heating | 17.57 |
Miscellaneous (All) | 57.86 |
Subtotal | 57.86 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 12.15 |
Space Heating | 5.78 |
Space Cooling | 6.41 |
Fans (All) | 9.15 |
Service Water Heating | 2.52 |
Receptacle Equipment | 45.42 |
Miscellaneous | 18.58 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 4472. | 4472. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 6752. | 8760. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 6828. | 8760. |
ALWAYS_OFF | 0. | 0. |
LTG_SCH_OFFICE | 2625. | 8760. |
LTG_SCH_DATACENTER | 2921. | 8760. |
EXTERIOR_LIGHT_SCH | 4380. | 4380. |
BLDG_EQUIP_SCH | 4049. | 8760. |
DATACENTER_EQUIP_SCH | 5478. | 8760. |
BLDG_OCC_SCH | 2528. | 5992. |
BLDG_OCC_SCH_W_SB | 1878. | 5056. |
BLDG_OCC_SCH_WO_SB | 2557. | 5992. |
BLDG_ELEVATORS | 2270. | 8760. |
ELEV_LIGHT_FAN_SCH_24_7 | 8760. | 8760. |
ELEV_LIGHT_FAN_SCH_ADD_DF | 2154. | 8760. |
BLDG_SWH_SCH | 1474. | 6570. |
WORK_EFF_SCH | 0. | 0. |
INFIL_SCH | 3976. | 3976. |
INFIL_SCH_PNNL | 5172. | 8760. |
INFIL_HALF_ON_SCH | 6368. | 8760. |
FAN_SCH | 8760. | 8760. |
REHEATCOILAVAILSCHED | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
MINOA_MOTORIZEDDAMPER_SCHED | 4472. | 4472. |
MINOA_SCHED | 8760. | 8760. |
CORE_BOTTOM SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_BOTTOM SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_MID SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_MID SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_TOP SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_TOP SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
SUPPLYFANSCH | 8760. | 8760. |
PERIMETER_MID_ZN_2_MDP_SCH | 1565. | 7824. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
HTGSETP_DC_SCH | DATACENTER COOLING SETPOINTS DUAL SP CONTROL | January | 18.00 | 365 | 18.00 | 365 |
CLGSETP_DC_SCH | DATACENTER COOLING SETPOINTS DUAL SP CONTROL | July | 27.00 | 365 | 27.00 | 365 |
HTGSETP_SCH_YES_OPTIMUM | CORE_BOTTOM DUAL SP CONTROL | January | 21.00 | 365 | 15.60 | 365 |
CLGSETP_SCH_YES_OPTIMUM | CORE_BOTTOM DUAL SP CONTROL | July | 24.00 | 365 | 26.70 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:43:27
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
BASEMENT | 8663.33 | 96.67 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 8753.33 | 6.67 | 0.00 | 0.00 | 0.00 |
CORE_MID | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 8758.33 | 1.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 8753.83 | 6.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 8725.33 | 34.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 8709.17 | 50.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 8597.67 | 162.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 8758.17 | 1.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 8720.33 | 39.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 8707.83 | 52.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 8721.00 | 39.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 8754.50 | 5.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 8722.00 | 38.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 8716.50 | 43.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 8723.83 | 36.17 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 8736.33 | 23.67 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 8741.17 | 18.83 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 8744.83 | 15.17 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 8212.83 | 536.67 | 10.50 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 8715.83 | 44.17 | 0.00 | 0.00 | 0.00 |
Min | 8212.83 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 536.67 | 10.50 | 0.00 | 0.00 |
Average | 8705.05 | 54.49 | 0.46 | 0.00 | 0.00 |
Sum | 200216.17 | 1253.33 | 10.50 | 0.00 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
BASEMENT | 368311.50 | 304.50 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 330813.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 330813.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 330813.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 18354.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 2257.83 | 10.17 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 2260.50 | 7.50 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 2262.67 | 5.33 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 95812.50 | 7248.67 | 333.83 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 368311.50 | 7248.67 | 333.83 | 0.00 | 0.00 |
Average | 79991.00 | 329.40 | 14.51 | 0.00 | 0.00 |
Sum | 1839793.00 | 7576.17 | 333.83 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
BASEMENT | 8542.67 | 217.33 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 8636.83 | 123.17 | 0.00 | 0.00 | 0.00 |
CORE_MID | 8675.17 | 84.83 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 8688.33 | 71.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 8699.33 | 60.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 8724.67 | 35.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 8706.17 | 53.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 8569.00 | 191.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 8737.67 | 22.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 8716.83 | 43.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 8721.17 | 38.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 8704.17 | 55.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 8728.67 | 31.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 8714.17 | 45.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 8720.83 | 39.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 8710.67 | 49.33 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 8364.83 | 395.17 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 8671.17 | 88.83 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 8725.67 | 34.33 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 8714.83 | 45.17 | 0.00 | 0.00 | 0.00 |
Min | 8364.83 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 395.17 | 0.00 | 0.00 | 0.00 |
Average | 8684.91 | 75.09 | 0.00 | 0.00 | 0.00 |
Sum | 199752.83 | 1727.17 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
BASEMENT | 368056.17 | 559.83 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 330658.00 | 155.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 330722.00 | 91.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 330734.00 | 79.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 18354.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 2268.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 2268.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 2268.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 98080.67 | 5314.33 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 368056.17 | 5314.33 | 0.00 | 0.00 | 0.00 |
Average | 80065.38 | 269.53 | 0.00 | 0.00 | 0.00 |
Sum | 1841503.83 | 6199.17 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:43:27
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:43:27
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 0.00 | 8760.00 | 0.00 |
Average | 0.00 | 0.00 | 4570.43 | 0.00 |
Sum | 0.00 | 0.00 | 105120.00 | 0.00 |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 18354.00 | 0.00 |
PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 24909.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 0.00 | 38925.00 | 0.00 |
Average | 0.00 | 0.00 | 16367.35 | 0.00 |
Sum | 0.00 | 0.00 | 376449.00 | 0.00 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 0.846 |
February | -0.25 |
March | 4.824 |
April | 6.083 |
May | 13.735 |
June | 22.164 |
July | 22.707 |
August | 21.737 |
September | 18.538 |
October | 7.117 |
November | 3.031 |
December | -1.01 |
Annual Sum or Average | 10.017 |
Minimum of Months | -1.01 |
Maximum of Months | 22.707 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Environment
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 0.846 |
February | -0.25 |
March | 4.824 |
April | 6.083 |
May | 13.735 |
June | 22.164 |
July | 22.707 |
August | 21.737 |
September | 18.538 |
October | 7.117 |
November | 3.031 |
December | -1.01 |
Annual Sum or Average | 10.017 |
Minimum of Months | -1.01 |
Maximum of Months | 22.707 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2013
For: Environment
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 0.846 |
February | -0.25 |
March | 4.824 |
April | 6.083 |
May | 13.735 |
June | 22.164 |
July | 22.707 |
August | 21.737 |
September | 18.538 |
October | 7.117 |
November | 3.031 |
December | -1.01 |
Annual Sum or Average | 10.017 |
Minimum of Months | -1.01 |
Maximum of Months | 22.707 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 0.846 |
February | -0.25 |
March | 4.824 |
April | 6.083 |
May | 13.735 |
June | 22.164 |
July | 22.707 |
August | 21.737 |
September | 18.538 |
October | 7.117 |
November | 3.031 |
December | -1.01 |
Annual Sum or Average | 10.017 |
Minimum of Months | -1.01 |
Maximum of Months | 22.707 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICELARGE
For: Environment
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 0.846 |
February | -0.25 |
March | 4.824 |
April | 6.083 |
May | 13.735 |
June | 22.164 |
July | 22.707 |
August | 21.737 |
September | 18.538 |
October | 7.117 |
November | 3.031 |
December | -1.01 |
Annual Sum or Average | 10.017 |
Minimum of Months | -1.01 |
Maximum of Months | 22.707 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 0.846 |
February | -0.25 |
March | 4.824 |
April | 6.083 |
May | 13.735 |
June | 22.164 |
July | 22.707 |
August | 21.737 |
September | 18.538 |
October | 7.117 |
November | 3.031 |
December | -1.01 |
Annual Sum or Average | 10.017 |
Minimum of Months | -1.01 |
Maximum of Months | 22.707 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 0.846 |
February | -0.25 |
March | 4.824 |
April | 6.083 |
May | 13.735 |
June | 22.164 |
July | 22.707 |
August | 21.737 |
September | 18.538 |
October | 7.117 |
November | 3.031 |
December | -1.01 |
Annual Sum or Average | 10.017 |
Minimum of Months | -1.01 |
Maximum of Months | 22.707 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 5B
For: Environment
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 0.846 |
February | -0.25 |
March | 4.824 |
April | 6.083 |
May | 13.735 |
June | 22.164 |
July | 22.707 |
August | 21.737 |
September | 18.538 |
October | 7.117 |
November | 3.031 |
December | -1.01 |
Annual Sum or Average | 10.017 |
Minimum of Months | -1.01 |
Maximum of Months | 22.707 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_CO_DENVER
For: Environment
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 0.846 |
February | -0.25 |
March | 4.824 |
April | 6.083 |
May | 13.735 |
June | 22.164 |
July | 22.707 |
August | 21.737 |
September | 18.538 |
October | 7.117 |
November | 3.031 |
December | -1.01 |
Annual Sum or Average | 10.017 |
Minimum of Months | -1.01 |
Maximum of Months | 22.707 |
Report: ZoneCoolingSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.528857E+11 | 118053.37 | 02-JAN-04:01 | -2.8 | -3.4 | 0.566083E+10 | 7499.15 | 27-JAN-10:30 | 2.50 | 2.25 |
February | 0.467556E+11 | 117226.81 | 27-FEB-05:11 | 4.67 | -0.4 | 0.513639E+10 | 7499.16 | 08-FEB-14:20 | 4.67 | -0.4 |
March | 0.578564E+11 | 116994.15 | 27-MAR-04:11 | 1.67 | -2.3 | 0.612965E+10 | 7499.18 | 27-MAR-09:09 | 1.67 | -0.8 |
April | 0.547895E+11 | 116729.88 | 10-APR-04:11 | 2.67 | -3.2 | 0.544690E+10 | 7499.28 | 13-APR-13:00 | 15.00 | 9.82 |
May | 0.589122E+11 | 118772.62 | 01-MAY-04:11 | 6.00 | 2.17 | 0.590116E+10 | 7499.23 | 26-MAY-13:20 | 12.67 | 7.73 |
June | 0.640141E+11 | 116641.22 | 05-JUN-04:12 | 12.37 | 8.77 | 0.588358E+10 | 7503.41 | 26-JUN-13:09 | 36.78 | 15.39 |
July | 0.638425E+11 | 117752.36 | 03-JUL-04:12 | 11.00 | 7.64 | 0.547511E+10 | 7499.03 | 21-JUL-09:20 | 25.00 | 15.23 |
August | 0.721340E+11 | 114283.03 | 19-AUG-04:11 | 12.33 | 5.72 | 0.613883E+10 | 7530.33 | 21-AUG-09:20 | 25.67 | 14.10 |
September | 0.646971E+11 | 120319.74 | 18-SEP-04:11 | 12.53 | 6.74 | 0.545398E+10 | 7499.80 | 05-SEP-09:20 | 12.53 | 6.74 |
October | 0.631091E+11 | 120724.79 | 02-OCT-04:11 | 3.67 | 3.67 | 0.567164E+10 | 7499.39 | 03-OCT-13:20 | 12.33 | 8.58 |
November | 0.601412E+11 | 120836.92 | 12-NOV-11:30 | 5.00 | 3.27 | 0.561488E+10 | 7499.16 | 29-NOV-10:30 | -9.0 | -9.0 |
December | 0.569288E+11 | 117753.42 | 04-DEC-04:22 | 1.50 | -0.9 | 0.545749E+10 | 7499.11 | 21-DEC-14:30 | -16.0 | -16.7 |
Annual Sum or Average | 0.716066E+12 | 0.679704E+11 | ||||||||
Minimum of Months | 0.467556E+11 | 114283.03 | -2.8 | -3.4 | 0.513639E+10 | 7499.03 | -16.0 | -16.7 | ||
Maximum of Months | 0.721340E+11 | 120836.92 | 12.53 | 8.77 | 0.613883E+10 | 7530.33 | 36.78 | 15.39 |
Report: ZoneCoolingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.417083E+11 | 89487.60 | 23-JAN-05:11 | 4.33 | 0.07 | 0.506475E+10 | 6734.77 | 06-JAN-10:09 | 4.33 | 0.07 |
February | 0.387623E+11 | 92034.42 | 27-FEB-05:11 | 4.67 | -0.4 | 0.459461E+10 | 6734.74 | 08-FEB-14:09 | 4.67 | -0.4 |
March | 0.524905E+11 | 94563.63 | 13-MAR-04:12 | 6.67 | 1.13 | 0.549478E+10 | 6734.80 | 27-MAR-09:30 | 1.00 | -0.6 |
April | 0.501740E+11 | 97384.90 | 10-APR-04:11 | 2.67 | -3.2 | 0.488560E+10 | 6735.10 | 13-APR-13:00 | 15.00 | 9.82 |
May | 0.535522E+11 | 94992.19 | 30-MAY-04:12 | 8.67 | 7.88 | 0.528764E+10 | 6734.91 | 26-MAY-13:09 | 8.67 | 7.88 |
June | 0.637952E+11 | 99364.41 | 14-JUN-04:13 | 21.47 | 8.56 | 0.526993E+10 | 6735.00 | 20-JUN-13:00 | 23.30 | 16.53 |
July | 0.668677E+11 | 98679.11 | 11-JUL-04:13 | 18.00 | 10.47 | 0.489753E+10 | 6734.80 | 26-JUL-09:09 | 25.17 | 15.80 |
August | 0.756507E+11 | 96925.33 | 28-AUG-04:13 | 14.33 | 14.13 | 0.549743E+10 | 6734.84 | 10-AUG-09:50 | 14.33 | 14.13 |
September | 0.557800E+11 | 98540.66 | 11-SEP-04:13 | 16.97 | 8.44 | 0.488298E+10 | 6735.44 | 05-SEP-09:09 | 16.97 | 8.44 |
October | 0.511917E+11 | 99278.85 | 10-OCT-04:12 | 9.00 | 5.09 | 0.507763E+10 | 6735.02 | 03-OCT-13:09 | 9.00 | 5.09 |
November | 0.493659E+11 | 94879.70 | 06-NOV-05:11 | 6.00 | -0.7 | 0.502579E+10 | 6734.79 | 29-NOV-10:30 | -9.0 | -9.0 |
December | 0.464804E+11 | 95596.53 | 18-DEC-05:11 | 2.00 | -2.3 | 0.489324E+10 | 6734.75 | 21-DEC-10:30 | -19.0 | -19.3 |
Annual Sum or Average | 0.645819E+12 | 0.608719E+11 | ||||||||
Minimum of Months | 0.387623E+11 | 89487.60 | 2.00 | -3.2 | 0.459461E+10 | 6734.74 | -19.0 | -19.3 | ||
Maximum of Months | 0.756507E+11 | 99364.41 | 21.47 | 14.13 | 0.549743E+10 | 6735.44 | 25.17 | 16.53 |
Report: ZoneCoolingSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.295523E+11 | 76351.16 | 27-JAN-06:02 | -1.2 | -1.2 | 0.493731E+10 | 6734.75 | 27-JAN-10:30 | 2.50 | 2.25 |
February | 0.267650E+11 | 72479.28 | 28-FEB-06:02 | -3.0 | -3.4 | 0.440580E+10 | 6734.74 | 21-FEB-10:20 | -3.0 | -3.4 |
March | 0.354444E+11 | 81743.41 | 14-MAR-05:02 | 8.67 | 1.59 | 0.537688E+10 | 6734.75 | 17-MAR-09:20 | 6.67 | 6.28 |
April | 0.312433E+11 | 79096.16 | 14-APR-05:03 | 4.67 | 4.13 | 0.480235E+10 | 6735.02 | 13-APR-13:00 | 4.67 | 4.13 |
May | 0.425042E+11 | 83180.16 | 18-MAY-04:12 | 11.67 | 7.63 | 0.527392E+10 | 6734.87 | 26-MAY-13:09 | 12.83 | 7.87 |
June | 0.517535E+11 | 87037.95 | 28-JUN-04:12 | 15.40 | 6.83 | 0.526563E+10 | 6734.99 | 20-JUN-13:00 | 15.40 | 6.83 |
July | 0.507398E+11 | 87738.52 | 25-JUL-04:12 | 17.00 | 13.73 | 0.489191E+10 | 6734.77 | 26-JUL-09:09 | 25.17 | 15.80 |
August | 0.532537E+11 | 88835.39 | 28-AUG-04:12 | 14.33 | 14.13 | 0.549558E+10 | 6734.77 | 29-AUG-09:00 | 22.00 | 14.30 |
September | 0.456960E+11 | 87112.19 | 05-SEP-04:12 | 14.40 | 9.51 | 0.487379E+10 | 6735.37 | 05-SEP-09:09 | 16.47 | 11.53 |
October | 0.363198E+11 | 81748.57 | 02-OCT-05:02 | 3.00 | 3.00 | 0.502146E+10 | 6734.93 | 03-OCT-13:09 | 12.17 | 8.60 |
November | 0.311957E+11 | 79803.73 | 09-NOV-06:03 | 9.17 | 4.69 | 0.493935E+10 | 6734.75 | 29-NOV-10:00 | -9.0 | -9.0 |
December | 0.279518E+11 | 34074.85 | 15-DEC-16:20 | 4.67 | 1.42 | 0.466060E+10 | 6734.70 | 06-DEC-10:09 | 4.67 | 1.42 |
Annual Sum or Average | 0.462419E+12 | 0.599446E+11 | ||||||||
Minimum of Months | 0.267650E+11 | 34074.85 | -3.0 | -3.4 | 0.440580E+10 | 6734.70 | -9.0 | -9.0 | ||
Maximum of Months | 0.532537E+11 | 88835.39 | 17.00 | 14.13 | 0.549558E+10 | 6735.37 | 25.17 | 15.80 |
Report: ZoneCoolingSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.217962E+11 | 36463.37 | 20-JAN-16:20 | 16.00 | 6.84 | 0.445026E+10 | 6734.61 | 26-JAN-14:00 | 9.00 | 2.97 |
February | 0.197671E+11 | 30326.50 | 23-FEB-17:00 | 5.00 | 2.11 | 0.405194E+10 | 6734.53 | 17-FEB-14:20 | 5.00 | 2.11 |
March | 0.291526E+11 | 46424.65 | 15-MAR-15:20 | 19.67 | 5.62 | 0.509802E+10 | 6734.77 | 17-MAR-09:20 | 6.67 | 6.28 |
April | 0.277622E+11 | 57619.38 | 21-APR-05:03 | 5.83 | 3.87 | 0.454790E+10 | 6735.03 | 13-APR-13:00 | 5.83 | 3.87 |
May | 0.389123E+11 | 77589.99 | 18-MAY-05:03 | 11.67 | 7.89 | 0.518903E+10 | 6734.84 | 26-MAY-13:09 | 12.83 | 7.87 |
June | 0.543944E+11 | 85252.86 | 26-JUN-04:12 | 14.40 | 9.85 | 0.526430E+10 | 6744.35 | 26-JUN-13:00 | 37.70 | 15.22 |
July | 0.527862E+11 | 88012.71 | 24-JUL-04:12 | 18.00 | 14.77 | 0.489120E+10 | 6734.76 | 14-JUL-09:39 | 18.00 | 14.77 |
August | 0.546539E+11 | 85959.63 | 21-AUG-04:12 | 19.33 | 11.98 | 0.549213E+10 | 6734.78 | 10-AUG-09:50 | 19.33 | 11.98 |
September | 0.433238E+11 | 85350.99 | 11-SEP-04:12 | 16.97 | 8.44 | 0.484257E+10 | 6735.35 | 05-SEP-09:09 | 16.97 | 8.44 |
October | 0.286303E+11 | 46572.65 | 11-OCT-15:20 | 25.33 | 9.18 | 0.472570E+10 | 6734.78 | 03-OCT-13:09 | 25.33 | 9.18 |
November | 0.230491E+11 | 37791.59 | 08-NOV-16:20 | 16.33 | 7.18 | 0.451597E+10 | 6734.54 | 10-NOV-10:00 | 5.00 | 5.00 |
December | 0.195067E+11 | 27027.49 | 14-DEC-16:20 | 11.33 | 3.88 | 0.420269E+10 | 6734.45 | 15-DEC-14:00 | 9.00 | 3.00 |
Annual Sum or Average | 0.413735E+12 | 0.572717E+11 | ||||||||
Minimum of Months | 0.195067E+11 | 27027.49 | 5.00 | 2.11 | 0.405194E+10 | 6734.45 | 5.00 | 2.11 | ||
Maximum of Months | 0.546539E+11 | 88012.71 | 25.33 | 14.77 | 0.549213E+10 | 6744.35 | 37.70 | 15.22 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.249158E+10 | 3824.77 | 20-JAN-14:50 | 20.17 | 6.81 | 0.559098E+09 | 845.61 | 18-JAN-14:30 | 20.17 | 6.81 |
February | 0.227651E+10 | 4427.79 | 27-FEB-15:30 | 13.50 | 4.54 | 0.502998E+09 | 845.61 | 28-FEB-14:39 | 4.33 | 2.90 |
March | 0.397777E+10 | 7284.14 | 14-MAR-13:40 | 23.33 | 7.70 | 0.651538E+09 | 845.62 | 17-MAR-09:20 | 6.67 | 6.28 |
April | 0.443700E+10 | 8119.56 | 20-APR-13:30 | 21.50 | 8.83 | 0.592053E+09 | 845.67 | 13-APR-13:50 | 21.50 | 8.83 |
May | 0.678528E+10 | 9772.43 | 17-MAY-13:30 | 29.00 | 11.78 | 0.659581E+09 | 845.65 | 26-MAY-13:09 | 12.83 | 7.87 |
June | 0.112783E+11 | 17975.55 | 25-JUN-17:41 | 31.78 | 13.99 | 0.662461E+09 | 848.83 | 26-JUN-14:00 | 39.40 | 15.63 |
July | 0.115801E+11 | 18373.21 | 16-JUL-13:22 | 36.00 | 14.59 | 0.616112E+09 | 846.78 | 06-JUL-13:20 | 36.00 | 14.59 |
August | 0.115328E+11 | 17872.64 | 06-AUG-12:51 | 31.00 | 15.61 | 0.690399E+09 | 846.17 | 18-AUG-13:20 | 33.67 | 12.84 |
September | 0.730616E+10 | 13130.14 | 11-SEP-05:02 | 17.88 | 8.62 | 0.609721E+09 | 845.71 | 05-SEP-09:09 | 17.88 | 8.62 |
October | 0.401492E+10 | 7639.09 | 10-OCT-14:30 | 25.00 | 8.59 | 0.600273E+09 | 845.65 | 03-OCT-13:09 | 25.00 | 8.59 |
November | 0.319851E+10 | 6039.88 | 09-NOV-13:20 | 20.00 | 8.84 | 0.575686E+09 | 845.61 | 09-NOV-14:00 | 18.00 | 8.10 |
December | 0.241370E+10 | 4918.72 | 04-DEC-14:10 | 19.83 | 6.62 | 0.539066E+09 | 845.60 | 04-DEC-10:50 | 19.83 | 6.62 |
Annual Sum or Average | 0.712926E+11 | 0.725898E+10 | ||||||||
Minimum of Months | 0.227651E+10 | 3824.77 | 13.50 | 4.54 | 0.502998E+09 | 845.60 | 4.33 | 2.90 | ||
Maximum of Months | 0.115801E+11 | 18373.21 | 36.00 | 15.61 | 0.690399E+09 | 848.83 | 39.40 | 15.63 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.346319E+10 | 9027.52 | 20-JAN-09:30 | 12.00 | 3.86 | 0.363916E+09 | 544.96 | 10-JAN-10:09 | 12.00 | 3.86 |
February | 0.357032E+10 | 19614.27 | 26-FEB-09:42 | 12.50 | 2.99 | 0.331623E+09 | 544.96 | 23-FEB-10:09 | 12.50 | 2.99 |
March | 0.566730E+10 | 23979.08 | 12-MAR-09:02 | 14.17 | 5.14 | 0.415486E+09 | 544.97 | 13-MAR-09:09 | 14.50 | 4.95 |
April | 0.564331E+10 | 17256.98 | 09-APR-08:62 | 10.17 | 4.69 | 0.376340E+09 | 545.89 | 21-APR-09:09 | 12.00 | 5.90 |
May | 0.769809E+10 | 22054.84 | 28-MAY-09:52 | 14.00 | 9.00 | 0.424301E+09 | 546.08 | 16-MAY-09:09 | 14.00 | 9.00 |
June | 0.116702E+11 | 24383.59 | 11-JUN-07:52 | 17.20 | 10.73 | 0.426516E+09 | 546.66 | 26-JUN-09:39 | 29.40 | 15.89 |
July | 0.113342E+11 | 27281.63 | 09-JUL-09:01 | 24.67 | 12.86 | 0.396639E+09 | 547.27 | 18-JUL-09:50 | 30.50 | 14.42 |
August | 0.121064E+11 | 28449.96 | 06-AUG-08:11 | 23.00 | 15.16 | 0.443862E+09 | 548.32 | 07-AUG-09:09 | 26.33 | 14.81 |
September | 0.855545E+10 | 26012.72 | 17-SEP-09:11 | 18.50 | 10.61 | 0.392217E+09 | 546.76 | 18-SEP-09:30 | 23.85 | 10.92 |
October | 0.518987E+10 | 19170.88 | 01-OCT-08:52 | 13.00 | 7.66 | 0.379146E+09 | 544.98 | 03-OCT-13:09 | 12.17 | 8.60 |
November | 0.394440E+10 | 12420.39 | 19-NOV-09:32 | 9.00 | 5.11 | 0.365133E+09 | 544.95 | 24-NOV-10:09 | 1.50 | -0.2 |
December | 0.291925E+10 | 7183.78 | 18-DEC-09:20 | 1.00 | -1.7 | 0.341599E+09 | 544.95 | 27-DEC-10:20 | 3.00 | -2.0 |
Annual Sum or Average | 0.817619E+11 | 0.465678E+10 | ||||||||
Minimum of Months | 0.291925E+10 | 7183.78 | 1.00 | -1.7 | 0.331623E+09 | 544.95 | 1.50 | -2.0 | ||
Maximum of Months | 0.121064E+11 | 28449.96 | 24.67 | 15.16 | 0.443862E+09 | 548.32 | 30.50 | 15.89 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.112617E+11 | 28495.45 | 22-JAN-12:11 | 6.33 | 3.28 | 0.608420E+09 | 942.90 | 20-JAN-14:09 | 6.33 | 3.28 |
February | 0.102412E+11 | 31910.07 | 26-FEB-13:01 | 17.83 | 4.74 | 0.546873E+09 | 891.21 | 17-FEB-14:09 | 17.83 | 4.74 |
March | 0.109181E+11 | 27978.82 | 12-MAR-12:22 | 18.50 | 6.07 | 0.655042E+09 | 906.18 | 13-MAR-13:20 | 22.33 | 6.86 |
April | 0.787479E+10 | 22864.63 | 09-APR-12:02 | 15.83 | 5.03 | 0.582222E+09 | 849.46 | 19-APR-13:00 | 22.00 | 9.00 |
May | 0.888007E+10 | 13971.01 | 16-MAY-13:10 | 27.17 | 12.14 | 0.652714E+09 | 845.68 | 26-MAY-13:09 | 12.83 | 7.87 |
June | 0.127684E+11 | 23513.37 | 25-JUN-16:21 | 32.70 | 13.84 | 0.661523E+09 | 846.43 | 30-JUN-13:20 | 34.97 | 13.87 |
July | 0.136544E+11 | 26180.86 | 09-JUL-13:02 | 33.33 | 13.33 | 0.615551E+09 | 847.12 | 31-JUL-13:20 | 26.67 | 17.30 |
August | 0.168939E+11 | 28194.18 | 06-AUG-12:11 | 31.67 | 16.04 | 0.690809E+09 | 886.92 | 31-AUG-13:09 | 30.00 | 11.91 |
September | 0.144172E+11 | 29835.79 | 17-SEP-11:51 | 24.40 | 10.51 | 0.611683E+09 | 961.64 | 28-SEP-13:09 | 30.50 | 11.31 |
October | 0.124496E+11 | 32343.47 | 09-OCT-12:31 | 21.33 | 9.03 | 0.602745E+09 | 953.39 | 10-OCT-13:09 | 24.17 | 8.07 |
November | 0.120993E+11 | 30251.05 | 19-NOV-10:51 | 10.00 | 4.18 | 0.607443E+09 | 949.61 | 07-NOV-14:09 | 10.00 | 4.18 |
December | 0.100380E+11 | 28958.72 | 17-DEC-13:01 | 18.00 | 5.78 | 0.579546E+09 | 910.10 | 14-DEC-14:09 | 18.00 | 5.78 |
Annual Sum or Average | 0.141497E+12 | 0.741457E+10 | ||||||||
Minimum of Months | 0.787479E+10 | 13971.01 | 6.33 | 3.28 | 0.546873E+09 | 845.68 | 6.33 | 3.28 | ||
Maximum of Months | 0.168939E+11 | 32343.47 | 33.33 | 16.04 | 0.690809E+09 | 961.64 | 34.97 | 17.30 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.510793E+10 | 16072.89 | 22-JAN-16:12 | 8.00 | 4.43 | 0.363371E+09 | 544.95 | 17-JAN-14:00 | 8.00 | 4.43 |
February | 0.544240E+10 | 30614.37 | 26-FEB-15:41 | 17.83 | 5.06 | 0.335797E+09 | 544.96 | 17-FEB-14:00 | 17.83 | 5.06 |
March | 0.846122E+10 | 31165.41 | 12-MAR-15:41 | 18.00 | 5.76 | 0.428094E+09 | 544.96 | 27-MAR-09:00 | 0.00 | -0.5 |
April | 0.860067E+10 | 30155.55 | 08-APR-17:41 | 14.33 | 4.60 | 0.388797E+09 | 545.00 | 13-APR-13:39 | 16.00 | 9.74 |
May | 0.898438E+10 | 30012.74 | 28-MAY-15:52 | 20.00 | 9.73 | 0.422821E+09 | 544.98 | 26-MAY-13:09 | 20.00 | 9.73 |
June | 0.142259E+11 | 33240.95 | 11-JUN-15:51 | 28.90 | 12.69 | 0.427466E+09 | 545.00 | 20-JUN-13:00 | 23.30 | 16.53 |
July | 0.144826E+11 | 33249.79 | 02-JUL-16:51 | 28.00 | 12.40 | 0.397686E+09 | 544.98 | 26-JUL-09:09 | 25.17 | 15.80 |
August | 0.171171E+11 | 37172.90 | 13-AUG-16:41 | 22.17 | 9.87 | 0.446018E+09 | 544.99 | 15-AUG-13:39 | 25.33 | 13.66 |
September | 0.981934E+10 | 35084.85 | 17-SEP-15:51 | 26.60 | 10.64 | 0.392243E+09 | 545.01 | 05-SEP-09:09 | 26.60 | 10.64 |
October | 0.777558E+10 | 32226.78 | 09-OCT-13:51 | 22.00 | 8.58 | 0.387830E+09 | 544.99 | 03-OCT-13:09 | 22.00 | 8.58 |
November | 0.676847E+10 | 28307.02 | 05-NOV-14:21 | 21.00 | 6.57 | 0.383693E+09 | 544.95 | 16-NOV-14:09 | 16.00 | 6.65 |
December | 0.589578E+10 | 23066.97 | 03-DEC-15:32 | 16.67 | 6.40 | 0.369208E+09 | 544.97 | 15-DEC-14:39 | 10.00 | 3.25 |
Annual Sum or Average | 0.112681E+12 | 0.474302E+10 | ||||||||
Minimum of Months | 0.510793E+10 | 16072.89 | 8.00 | 4.43 | 0.335797E+09 | 544.95 | 0.00 | -0.5 | ||
Maximum of Months | 0.171171E+11 | 37172.90 | 28.90 | 12.69 | 0.446018E+09 | 545.01 | 26.60 | 16.53 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.125522E+10 | 2676.48 | 20-JAN-16:00 | 18.00 | 7.49 | 0.492708E+09 | 795.33 | 20-JAN-14:00 | 18.00 | 7.49 |
February | 0.102879E+10 | 2603.28 | 27-FEB-15:20 | 13.67 | 4.61 | 0.440092E+09 | 772.41 | 27-FEB-14:00 | 13.67 | 4.61 |
March | 0.214738E+10 | 5459.43 | 14-MAR-14:40 | 23.00 | 7.59 | 0.578718E+09 | 845.60 | 16-MAR-13:00 | 16.00 | 5.44 |
April | 0.235609E+10 | 6022.84 | 20-APR-13:30 | 21.50 | 8.83 | 0.536754E+09 | 845.65 | 13-APR-13:00 | 21.50 | 8.83 |
May | 0.517191E+10 | 9190.11 | 17-MAY-13:30 | 29.00 | 11.78 | 0.643935E+09 | 845.64 | 26-MAY-13:09 | 12.83 | 7.87 |
June | 0.966839E+10 | 17092.75 | 25-JUN-17:41 | 31.78 | 13.99 | 0.661591E+09 | 846.40 | 12-JUN-13:39 | 31.78 | 13.99 |
July | 0.943945E+10 | 17974.95 | 16-JUL-14:51 | 36.00 | 14.77 | 0.615078E+09 | 846.06 | 18-JUL-13:39 | 32.33 | 15.11 |
August | 0.841855E+10 | 11582.31 | 21-AUG-05:02 | 19.92 | 12.21 | 0.688521E+09 | 846.13 | 18-AUG-13:50 | 19.92 | 12.21 |
September | 0.587083E+10 | 16773.79 | 10-SEP-14:31 | 31.97 | 12.55 | 0.601208E+09 | 845.69 | 05-SEP-09:09 | 31.97 | 12.55 |
October | 0.246250E+10 | 5929.88 | 11-OCT-14:00 | 27.00 | 9.73 | 0.550411E+09 | 845.61 | 10-OCT-13:00 | 27.00 | 9.73 |
November | 0.153177E+10 | 3859.60 | 09-NOV-13:30 | 20.00 | 8.78 | 0.502544E+09 | 845.60 | 09-NOV-14:00 | 18.00 | 8.10 |
December | 0.877409E+09 | 2534.19 | 04-DEC-14:10 | 19.83 | 6.62 | 0.461650E+09 | 773.56 | 04-DEC-14:00 | 19.00 | 6.13 |
Annual Sum or Average | 0.502283E+11 | 0.677321E+10 | ||||||||
Minimum of Months | 0.877409E+09 | 2534.19 | 13.67 | 4.61 | 0.440092E+09 | 772.41 | 12.83 | 4.61 | ||
Maximum of Months | 0.966839E+10 | 17974.95 | 36.00 | 14.77 | 0.688521E+09 | 846.40 | 32.33 | 15.11 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.236553E+10 | 7318.31 | 20-JAN-09:40 | 12.67 | 4.18 | 0.244787E+09 | 521.20 | 20-JAN-11:20 | 18.67 | 6.97 |
February | 0.254561E+10 | 9473.25 | 27-FEB-09:10 | 9.17 | 2.67 | 0.227306E+09 | 521.20 | 17-FEB-11:09 | 9.17 | 2.67 |
March | 0.449075E+10 | 26684.68 | 12-MAR-09:31 | 14.67 | 5.41 | 0.289906E+09 | 521.22 | 27-MAR-10:09 | 0.33 | -0.4 |
April | 0.447550E+10 | 14898.11 | 21-APR-08:40 | 11.67 | 5.95 | 0.263975E+09 | 521.23 | 13-APR-10:09 | 11.67 | 5.95 |
May | 0.715038E+10 | 26440.72 | 28-MAY-09:02 | 12.33 | 8.71 | 0.306476E+09 | 521.76 | 16-MAY-08:00 | 12.33 | 8.71 |
June | 0.116999E+11 | 29431.29 | 11-JUN-08:51 | 20.00 | 10.75 | 0.313018E+09 | 523.43 | 29-JUN-08:00 | 28.30 | 13.38 |
July | 0.109785E+11 | 30220.41 | 16-JUL-08:51 | 33.00 | 14.82 | 0.291960E+09 | 529.05 | 17-JUL-07:19 | 26.00 | 12.45 |
August | 0.113112E+11 | 31148.77 | 06-AUG-08:51 | 25.00 | 15.42 | 0.325596E+09 | 522.38 | 07-AUG-10:09 | 28.33 | 14.90 |
September | 0.826414E+10 | 28514.14 | 04-SEP-09:51 | 26.10 | 13.35 | 0.285181E+09 | 521.27 | 05-SEP-08:00 | 16.10 | 11.43 |
October | 0.422417E+10 | 25953.24 | 01-OCT-09:22 | 13.50 | 7.83 | 0.264971E+09 | 521.22 | 03-OCT-12:50 | 12.83 | 8.70 |
November | 0.270706E+10 | 8910.86 | 07-NOV-09:10 | 14.00 | 4.09 | 0.247640E+09 | 521.21 | 07-NOV-11:09 | 16.67 | 5.90 |
December | 0.165846E+10 | 4113.00 | 14-DEC-09:40 | 9.33 | 1.23 | 0.226303E+09 | 521.19 | 01-DEC-09:30 | 9.33 | 1.23 |
Annual Sum or Average | 0.718712E+11 | 0.328712E+10 | ||||||||
Minimum of Months | 0.165846E+10 | 4113.00 | 9.17 | 1.23 | 0.226303E+09 | 521.19 | 0.33 | -0.4 | ||
Maximum of Months | 0.116999E+11 | 31148.77 | 33.00 | 15.42 | 0.325596E+09 | 529.05 | 28.33 | 14.90 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.113435E+11 | 30286.37 | 01-JAN-13:21 | 5.00 | 1.37 | 0.604971E+09 | 1018.90 | 20-JAN-14:09 | 20.83 | 6.93 |
February | 0.100594E+11 | 29456.82 | 26-FEB-13:11 | 17.67 | 4.65 | 0.543038E+09 | 949.74 | 17-FEB-14:09 | 17.67 | 4.65 |
March | 0.998879E+10 | 31310.76 | 12-MAR-12:11 | 18.33 | 6.09 | 0.636344E+09 | 944.00 | 15-MAR-13:39 | 20.67 | 6.10 |
April | 0.631189E+10 | 17587.29 | 12-APR-13:10 | 21.00 | 7.79 | 0.558793E+09 | 847.48 | 21-APR-13:50 | 15.17 | 5.71 |
May | 0.786394E+10 | 13955.38 | 16-MAY-13:20 | 27.33 | 12.20 | 0.640774E+09 | 845.68 | 26-MAY-13:09 | 12.83 | 7.87 |
June | 0.115168E+11 | 25661.90 | 11-JUN-13:32 | 27.93 | 13.13 | 0.659498E+09 | 846.76 | 30-JUN-13:39 | 35.53 | 14.15 |
July | 0.117786E+11 | 26443.42 | 16-JUL-14:51 | 36.00 | 14.77 | 0.614052E+09 | 845.66 | 20-JUL-13:09 | 25.00 | 16.72 |
August | 0.144028E+11 | 28723.01 | 27-AUG-13:01 | 26.00 | 15.11 | 0.689376E+09 | 913.07 | 31-AUG-13:20 | 30.00 | 11.86 |
September | 0.142581E+11 | 31407.55 | 04-SEP-13:11 | 29.40 | 13.45 | 0.609949E+09 | 1027.31 | 28-SEP-13:20 | 30.50 | 11.31 |
October | 0.122093E+11 | 33181.90 | 08-OCT-13:01 | 20.83 | 8.58 | 0.593430E+09 | 998.58 | 10-OCT-13:30 | 24.50 | 8.32 |
November | 0.116076E+11 | 34009.38 | 05-NOV-13:21 | 21.00 | 6.47 | 0.599028E+09 | 1013.96 | 07-NOV-14:09 | 22.00 | 7.34 |
December | 0.884874E+10 | 29307.58 | 17-DEC-13:01 | 18.00 | 5.78 | 0.564130E+09 | 951.74 | 14-DEC-14:09 | 18.00 | 5.78 |
Annual Sum or Average | 0.130189E+12 | 0.731338E+10 | ||||||||
Minimum of Months | 0.631189E+10 | 13955.38 | 5.00 | 1.37 | 0.543038E+09 | 845.66 | 12.83 | 4.65 | ||
Maximum of Months | 0.144028E+11 | 34009.38 | 36.00 | 15.11 | 0.689376E+09 | 1027.31 | 35.53 | 16.72 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.285999E+10 | 10016.15 | 20-JAN-15:40 | 18.67 | 7.30 | 0.333067E+09 | 544.94 | 23-JAN-14:30 | 19.00 | 5.63 |
February | 0.282409E+10 | 11141.89 | 17-FEB-16:30 | 13.50 | 6.66 | 0.301198E+09 | 544.95 | 17-FEB-14:00 | 13.50 | 6.66 |
March | 0.479134E+10 | 29123.38 | 12-MAR-16:11 | 18.00 | 5.71 | 0.372018E+09 | 544.94 | 16-MAR-13:50 | 16.00 | 5.38 |
April | 0.451685E+10 | 26669.18 | 08-APR-17:03 | 15.67 | 5.07 | 0.339806E+09 | 544.97 | 13-APR-13:30 | 16.50 | 9.66 |
May | 0.694982E+10 | 27509.11 | 28-MAY-15:42 | 20.00 | 9.79 | 0.401865E+09 | 544.97 | 10-MAY-13:39 | 20.00 | 9.79 |
June | 0.112897E+11 | 34812.47 | 11-JUN-16:51 | 27.80 | 12.54 | 0.423631E+09 | 545.00 | 20-JUN-13:00 | 23.30 | 16.53 |
July | 0.998490E+10 | 33818.44 | 02-JUL-16:41 | 28.00 | 12.40 | 0.393971E+09 | 544.96 | 19-JUL-09:00 | 25.00 | 15.80 |
August | 0.104307E+11 | 30563.98 | 13-AUG-17:31 | 22.67 | 10.36 | 0.440325E+09 | 544.98 | 15-AUG-13:39 | 25.33 | 13.66 |
September | 0.789879E+10 | 34297.44 | 10-SEP-16:31 | 31.07 | 12.39 | 0.379363E+09 | 545.00 | 01-SEP-13:00 | 31.07 | 12.39 |
October | 0.502055E+10 | 29359.54 | 08-OCT-16:21 | 17.50 | 8.44 | 0.347528E+09 | 544.98 | 10-OCT-13:00 | 25.00 | 8.71 |
November | 0.330995E+10 | 27155.14 | 05-NOV-14:41 | 21.00 | 6.70 | 0.333946E+09 | 544.94 | 06-NOV-14:00 | 20.00 | 6.59 |
December | 0.208534E+10 | 8440.02 | 01-DEC-15:30 | 19.50 | 7.14 | 0.312746E+09 | 544.95 | 15-DEC-14:00 | 9.00 | 3.00 |
Annual Sum or Average | 0.719620E+11 | 0.437946E+10 | ||||||||
Minimum of Months | 0.208534E+10 | 8440.02 | 13.50 | 5.07 | 0.301198E+09 | 544.94 | 9.00 | 3.00 | ||
Maximum of Months | 0.112897E+11 | 34812.47 | 31.07 | 12.54 | 0.440325E+09 | 545.00 | 31.07 | 16.53 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.764155E+09 | 2887.06 | 20-JAN-15:50 | 18.33 | 7.40 | 0.476692E+09 | 776.65 | 20-JAN-14:00 | 18.33 | 7.40 |
February | 0.660051E+09 | 2637.84 | 27-FEB-14:30 | 14.00 | 4.75 | 0.429444E+09 | 725.31 | 27-FEB-14:00 | 14.00 | 4.75 |
March | 0.177871E+10 | 5545.90 | 14-MAR-14:40 | 23.00 | 7.59 | 0.558654E+09 | 845.60 | 16-MAR-13:00 | 16.00 | 5.44 |
April | 0.208585E+10 | 6546.20 | 20-APR-13:30 | 21.50 | 8.83 | 0.516871E+09 | 845.65 | 13-APR-13:00 | 21.50 | 8.83 |
May | 0.487029E+10 | 9648.05 | 17-MAY-13:30 | 29.00 | 11.78 | 0.625604E+09 | 845.63 | 26-MAY-13:09 | 12.83 | 7.87 |
June | 0.100723E+11 | 19497.63 | 04-JUN-18:11 | 26.10 | 12.42 | 0.660721E+09 | 857.23 | 26-JUN-13:00 | 37.70 | 15.22 |
July | 0.978552E+10 | 19541.19 | 16-JUL-15:02 | 35.83 | 14.63 | 0.614128E+09 | 846.26 | 18-JUL-13:39 | 32.33 | 15.11 |
August | 0.868638E+10 | 16576.50 | 20-AUG-15:31 | 28.00 | 14.04 | 0.685697E+09 | 845.64 | 09-AUG-13:09 | 28.00 | 14.04 |
September | 0.576615E+10 | 19402.17 | 10-SEP-14:31 | 31.97 | 12.55 | 0.591137E+09 | 845.69 | 05-SEP-09:09 | 31.97 | 12.55 |
October | 0.205344E+10 | 6164.19 | 11-OCT-14:30 | 26.50 | 9.60 | 0.523891E+09 | 845.62 | 11-OCT-13:09 | 26.50 | 9.60 |
November | 0.101827E+10 | 3190.77 | 09-NOV-13:50 | 20.00 | 8.66 | 0.485868E+09 | 845.60 | 09-NOV-14:00 | 18.00 | 8.10 |
December | 0.523069E+09 | 2639.50 | 01-DEC-14:50 | 21.17 | 7.46 | 0.452481E+09 | 733.48 | 04-DEC-14:00 | 19.00 | 6.13 |
Annual Sum or Average | 0.480641E+11 | 0.662119E+10 | ||||||||
Minimum of Months | 0.523069E+09 | 2637.84 | 14.00 | 4.75 | 0.429444E+09 | 725.31 | 12.83 | 4.75 | ||
Maximum of Months | 0.100723E+11 | 19541.19 | 35.83 | 14.63 | 0.685697E+09 | 857.23 | 37.70 | 15.22 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.174002E+10 | 5846.49 | 20-JAN-09:50 | 13.33 | 4.49 | 0.324384E+09 | 544.94 | 24-JAN-10:09 | 11.50 | 3.54 |
February | 0.197742E+10 | 6901.65 | 27-FEB-09:30 | 9.50 | 2.73 | 0.304174E+09 | 544.96 | 23-FEB-10:09 | 9.50 | 2.73 |
March | 0.387906E+10 | 18210.41 | 12-MAR-09:21 | 14.50 | 5.32 | 0.392717E+09 | 544.96 | 27-MAR-09:00 | 0.00 | -0.5 |
April | 0.406079E+10 | 14306.79 | 21-APR-09:00 | 12.00 | 5.98 | 0.355501E+09 | 544.98 | 13-APR-13:50 | 12.00 | 5.98 |
May | 0.674549E+10 | 15200.53 | 16-MAY-08:40 | 22.00 | 11.45 | 0.413977E+09 | 545.07 | 16-MAY-09:09 | 23.17 | 11.60 |
June | 0.120454E+11 | 28591.60 | 11-JUN-08:21 | 18.60 | 10.81 | 0.426039E+09 | 546.37 | 06-JUN-09:00 | 18.60 | 10.81 |
July | 0.112552E+11 | 28548.27 | 04-JUL-09:01 | 18.33 | 11.09 | 0.395737E+09 | 546.84 | 18-JUL-09:00 | 31.00 | 14.50 |
August | 0.115360E+11 | 27660.10 | 06-AUG-09:01 | 25.33 | 15.45 | 0.443115E+09 | 546.44 | 04-AUG-09:00 | 25.33 | 15.45 |
September | 0.807222E+10 | 28526.25 | 04-SEP-09:21 | 25.25 | 13.40 | 0.386974E+09 | 545.05 | 06-SEP-09:30 | 25.75 | 13.14 |
October | 0.355797E+10 | 19016.70 | 08-OCT-10:21 | 19.50 | 8.51 | 0.357927E+09 | 544.96 | 11-OCT-13:09 | 26.17 | 9.50 |
November | 0.202656E+10 | 7131.05 | 07-NOV-09:20 | 14.00 | 4.09 | 0.330813E+09 | 544.95 | 07-NOV-10:50 | 15.67 | 5.30 |
December | 0.123075E+10 | 3387.84 | 01-DEC-14:20 | 21.67 | 7.75 | 0.301002E+09 | 525.13 | 14-DEC-10:09 | 10.50 | 1.74 |
Annual Sum or Average | 0.681268E+11 | 0.443236E+10 | ||||||||
Minimum of Months | 0.123075E+10 | 3387.84 | 9.50 | 2.73 | 0.301002E+09 | 525.13 | 0.00 | -0.5 | ||
Maximum of Months | 0.120454E+11 | 28591.60 | 25.33 | 15.45 | 0.443115E+09 | 546.84 | 31.00 | 15.45 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.969216E+10 | 31344.32 | 22-JAN-14:01 | 8.00 | 4.11 | 0.583719E+09 | 975.12 | 20-JAN-14:09 | 8.00 | 4.11 |
February | 0.890394E+10 | 33940.88 | 26-FEB-13:01 | 17.83 | 4.74 | 0.527481E+09 | 899.59 | 17-FEB-14:09 | 17.83 | 4.74 |
March | 0.908508E+10 | 32659.45 | 12-MAR-13:21 | 18.00 | 5.75 | 0.620876E+09 | 915.22 | 15-MAR-13:39 | 20.67 | 6.10 |
April | 0.571643E+10 | 17915.40 | 21-APR-13:20 | 15.67 | 6.21 | 0.544313E+09 | 847.79 | 21-APR-13:50 | 15.17 | 5.71 |
May | 0.743646E+10 | 14520.64 | 16-MAY-13:20 | 27.33 | 12.20 | 0.625047E+09 | 845.68 | 26-MAY-13:09 | 12.83 | 7.87 |
June | 0.120081E+11 | 27812.57 | 11-JUN-15:01 | 28.82 | 13.08 | 0.656809E+09 | 850.74 | 26-JUN-13:00 | 37.70 | 15.22 |
July | 0.121818E+11 | 27938.82 | 23-JUL-13:22 | 34.50 | 16.47 | 0.611705E+09 | 845.66 | 27-JUL-13:09 | 28.50 | 17.50 |
August | 0.147200E+11 | 28898.96 | 20-AUG-13:32 | 27.67 | 14.76 | 0.685496E+09 | 896.84 | 31-AUG-13:20 | 30.00 | 11.86 |
September | 0.140281E+11 | 33558.46 | 04-SEP-12:01 | 28.48 | 13.40 | 0.602703E+09 | 996.70 | 28-SEP-13:30 | 30.50 | 11.31 |
October | 0.111654E+11 | 35339.97 | 09-OCT-13:21 | 22.00 | 8.88 | 0.574753E+09 | 957.99 | 10-OCT-13:39 | 24.67 | 8.45 |
November | 0.995761E+10 | 35785.75 | 05-NOV-13:31 | 21.00 | 6.43 | 0.581634E+09 | 968.39 | 07-NOV-14:09 | 22.00 | 7.34 |
December | 0.753414E+10 | 30401.85 | 03-DEC-13:31 | 17.73 | 6.51 | 0.547235E+09 | 898.52 | 14-DEC-14:09 | 16.25 | 4.44 |
Annual Sum or Average | 0.122429E+12 | 0.716177E+10 | ||||||||
Minimum of Months | 0.571643E+10 | 14520.64 | 8.00 | 4.11 | 0.527481E+09 | 845.66 | 8.00 | 4.11 | ||
Maximum of Months | 0.147200E+11 | 35785.75 | 34.50 | 16.47 | 0.685496E+09 | 996.70 | 37.70 | 17.50 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.227100E+10 | 10012.91 | 20-JAN-15:40 | 18.67 | 7.30 | 0.326957E+09 | 544.93 | 20-JAN-14:00 | 18.67 | 7.30 |
February | 0.236187E+10 | 10998.05 | 17-FEB-16:30 | 13.50 | 6.66 | 0.297240E+09 | 544.94 | 17-FEB-14:00 | 13.50 | 6.66 |
March | 0.434139E+10 | 31808.27 | 12-MAR-16:01 | 18.00 | 5.74 | 0.364619E+09 | 544.94 | 16-MAR-13:50 | 16.00 | 5.38 |
April | 0.414569E+10 | 27966.43 | 08-APR-17:03 | 15.67 | 5.07 | 0.332194E+09 | 544.96 | 19-APR-13:00 | 22.00 | 9.00 |
May | 0.668871E+10 | 20742.66 | 07-MAY-15:32 | 22.33 | 8.84 | 0.391782E+09 | 544.96 | 04-MAY-13:00 | 22.33 | 8.84 |
June | 0.116468E+11 | 36332.58 | 11-JUN-16:21 | 28.35 | 12.62 | 0.421327E+09 | 546.47 | 26-JUN-13:00 | 37.70 | 15.22 |
July | 0.102621E+11 | 32707.06 | 01-JUL-17:41 | 28.17 | 10.55 | 0.391529E+09 | 544.96 | 14-JUL-09:39 | 25.33 | 12.19 |
August | 0.106550E+11 | 35770.92 | 13-AUG-17:11 | 22.33 | 10.08 | 0.436405E+09 | 544.97 | 15-AUG-13:00 | 26.00 | 13.91 |
September | 0.780252E+10 | 36271.41 | 10-SEP-16:31 | 31.07 | 12.39 | 0.372551E+09 | 545.00 | 01-SEP-13:00 | 31.07 | 12.39 |
October | 0.447331E+10 | 32962.39 | 09-OCT-16:01 | 21.83 | 8.61 | 0.338791E+09 | 544.95 | 11-OCT-13:20 | 26.33 | 9.54 |
November | 0.266258E+10 | 27828.23 | 05-NOV-15:31 | 19.67 | 6.02 | 0.328091E+09 | 544.94 | 06-NOV-14:00 | 20.00 | 6.59 |
December | 0.163835E+10 | 8225.79 | 01-DEC-15:30 | 19.50 | 7.14 | 0.308437E+09 | 544.93 | 15-DEC-14:00 | 9.00 | 3.00 |
Annual Sum or Average | 0.689493E+11 | 0.430992E+10 | ||||||||
Minimum of Months | 0.163835E+10 | 8225.79 | 13.50 | 5.07 | 0.297240E+09 | 544.93 | 9.00 | 3.00 | ||
Maximum of Months | 0.116468E+11 | 36332.58 | 31.07 | 12.62 | 0.436405E+09 | 546.47 | 37.70 | 15.22 |
Report: ZoneCoolingSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.213073E+10 | 7713.97 | 05-JAN-05:01 | -17.0 | -17.0 | 0.00 | 0.00 | 01-JAN-00:10 | -17.0 | -17.0 |
February | 0.173336E+10 | 8176.25 | 06-FEB-05:01 | -10.0 | -10.0 | 0.00 | 0.00 | 01-FEB-00:10 | -10.0 | -10.0 |
March | 0.369454E+10 | 7309.13 | 13-MAR-16:00 | 23.00 | 6.97 | 0.00 | 0.00 | 01-MAR-00:10 | 23.00 | 6.97 |
April | 0.380654E+10 | 6359.43 | 21-APR-13:40 | 15.33 | 5.87 | 0.00 | 0.00 | 01-APR-00:10 | 15.33 | 5.87 |
May | 0.573487E+10 | 6733.39 | 18-MAY-14:30 | 23.50 | 11.45 | 0.00 | 0.00 | 01-MAY-00:10 | 23.50 | 11.45 |
June | 0.100542E+11 | 11163.12 | 26-JUN-15:00 | 39.40 | 15.63 | 0.00 | 0.00 | 01-JUN-00:10 | 39.40 | 15.63 |
July | 0.102778E+11 | 10767.52 | 05-JUL-05:02 | 15.17 | 9.13 | 0.00 | 0.00 | 01-JUL-00:10 | 15.17 | 9.13 |
August | 0.108893E+11 | 12261.44 | 21-AUG-05:15 | 19.83 | 12.23 | 0.00 | 0.00 | 01-AUG-00:10 | 19.83 | 12.23 |
September | 0.771602E+10 | 11081.75 | 05-SEP-05:15 | 14.20 | 8.43 | 0.00 | 0.00 | 01-SEP-00:10 | 14.20 | 8.43 |
October | 0.444803E+10 | 8919.51 | 10-OCT-15:50 | 25.00 | 8.26 | 0.00 | 0.00 | 01-OCT-00:10 | 25.00 | 8.26 |
November | 0.319080E+10 | 6196.45 | 30-NOV-06:01 | -12.0 | -12.8 | 0.00 | 0.00 | 01-NOV-00:10 | -12.0 | -12.8 |
December | 0.197770E+10 | 9860.85 | 21-DEC-05:01 | -18.2 | -18.4 | 0.00 | 0.00 | 01-DEC-00:10 | -18.2 | -18.4 |
Annual Sum or Average | 0.656539E+11 | 0.00 | ||||||||
Minimum of Months | 0.173336E+10 | 6196.45 | -18.2 | -18.4 | 0.00 | 0.00 | -18.2 | -18.4 | ||
Maximum of Months | 0.108893E+11 | 12261.44 | 39.40 | 15.63 | 0.00 | 0.00 | 39.40 | 15.63 |
Report: ZoneCoolingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.815809E+09 | 13450.67 | 05-JAN-04:01 | -16.2 | -16.2 | 0.00 | 0.00 | 01-JAN-00:10 | -16.2 | -16.2 |
February | 0.826836E+09 | 11519.55 | 02-FEB-05:01 | -9.0 | -9.0 | 0.00 | 0.00 | 01-FEB-00:10 | -9.0 | -9.0 |
March | 0.171986E+10 | 15564.73 | 19-MAR-06:32 | -14.8 | -14.8 | 0.00 | 0.00 | 01-MAR-00:10 | -14.8 | -14.8 |
April | 0.140515E+10 | 13302.56 | 03-APR-03:01 | -8.0 | -8.0 | 0.00 | 0.00 | 01-APR-00:10 | -8.0 | -8.0 |
May | 0.364477E+10 | 6856.10 | 01-MAY-04:11 | 6.00 | 2.17 | 0.00 | 0.00 | 01-MAY-00:10 | 6.00 | 2.17 |
June | 0.781982E+10 | 8662.17 | 26-JUN-14:30 | 38.55 | 15.43 | 0.00 | 0.00 | 01-JUN-00:10 | 38.55 | 15.43 |
July | 0.784925E+10 | 8934.50 | 17-JUL-16:00 | 32.00 | 14.52 | 0.00 | 0.00 | 01-JUL-00:10 | 32.00 | 14.52 |
August | 0.780748E+10 | 8107.78 | 21-AUG-14:30 | 27.50 | 14.51 | 0.00 | 0.00 | 01-AUG-00:10 | 27.50 | 14.51 |
September | 0.572970E+10 | 7859.94 | 11-SEP-14:30 | 28.85 | 13.58 | 0.00 | 0.00 | 01-SEP-00:10 | 28.85 | 13.58 |
October | 0.228801E+10 | 15000.06 | 30-OCT-03:01 | -9.2 | -9.2 | 0.00 | 0.00 | 01-OCT-00:10 | -9.2 | -9.2 |
November | 0.110688E+10 | 13329.30 | 30-NOV-04:01 | -13.8 | -14.3 | 0.00 | 0.00 | 01-NOV-00:10 | -13.8 | -14.3 |
December | 0.804566E+09 | 13837.62 | 21-DEC-04:01 | -18.8 | -18.9 | 0.00 | 0.00 | 01-DEC-00:10 | -18.8 | -18.9 |
Annual Sum or Average | 0.418181E+11 | 0.00 | ||||||||
Minimum of Months | 0.804566E+09 | 6856.10 | -18.8 | -18.9 | 0.00 | 0.00 | -18.8 | -18.9 | ||
Maximum of Months | 0.784925E+10 | 15564.73 | 38.55 | 15.43 | 0.00 | 0.00 | 38.55 | 15.43 |
Report: ZoneCoolingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.511355E+09 | 6049.99 | 20-JAN-16:00 | 18.00 | 7.49 | 0.00 | 0.00 | 01-JAN-00:10 | 18.00 | 7.49 |
February | 0.713796E+09 | 5560.38 | 18-FEB-14:40 | 19.33 | 7.91 | 0.00 | 0.00 | 01-FEB-00:10 | 19.33 | 7.91 |
March | 0.268248E+10 | 13296.69 | 14-MAR-14:10 | 23.00 | 7.59 | 0.00 | 0.00 | 01-MAR-00:10 | 23.00 | 7.59 |
April | 0.313721E+10 | 13857.69 | 21-APR-13:40 | 15.33 | 5.87 | 0.00 | 0.00 | 01-APR-00:10 | 15.33 | 5.87 |
May | 0.679163E+10 | 17858.28 | 31-MAY-14:30 | 28.00 | 14.75 | 0.00 | 0.00 | 01-MAY-00:10 | 28.00 | 14.75 |
June | 0.150538E+11 | 24198.52 | 26-JUN-13:40 | 37.33 | 15.29 | 0.00 | 0.00 | 01-JUN-00:10 | 37.33 | 15.29 |
July | 0.138226E+11 | 21110.51 | 18-JUL-14:30 | 31.00 | 15.18 | 0.00 | 0.00 | 01-JUL-00:10 | 31.00 | 15.18 |
August | 0.139678E+11 | 23285.50 | 16-AUG-15:00 | 36.00 | 16.15 | 0.00 | 0.00 | 01-AUG-00:10 | 36.00 | 16.15 |
September | 0.888231E+10 | 17794.91 | 12-SEP-14:00 | 29.40 | 13.78 | 0.00 | 0.00 | 01-SEP-00:10 | 29.40 | 13.78 |
October | 0.302679E+10 | 12658.24 | 11-OCT-14:40 | 26.33 | 9.55 | 0.00 | 0.00 | 01-OCT-00:10 | 26.33 | 9.55 |
November | 0.103919E+10 | 7905.82 | 09-NOV-13:10 | 20.00 | 8.90 | 0.00 | 0.00 | 01-NOV-00:10 | 20.00 | 8.90 |
December | 0.302746E+09 | 4005.26 | 03-DEC-13:34 | 17.73 | 6.51 | 0.00 | 0.00 | 01-DEC-00:10 | 17.73 | 6.51 |
Annual Sum or Average | 0.699317E+11 | 0.00 | ||||||||
Minimum of Months | 0.302746E+09 | 4005.26 | 15.33 | 5.87 | 0.00 | 0.00 | 15.33 | 5.87 | ||
Maximum of Months | 0.150538E+11 | 24198.52 | 37.33 | 16.15 | 0.00 | 0.00 | 37.33 | 16.15 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.335695E+10 | 2721.98 | 23-JAN-16:40 | 15.67 | 5.76 | 95230851.45 | 126.83 | 27-JAN-14:00 | 10.00 | 5.47 |
February | 0.771127E+10 | 4719.88 | 23-FEB-17:00 | 5.00 | 2.11 | 86396806.33 | 126.83 | 23-FEB-10:00 | 5.00 | 2.11 |
March | 0.141443E+11 | 7157.34 | 31-MAR-24:00 | 6.10 | 2.00 | 0.103237E+09 | 126.83 | 17-MAR-13:00 | 6.10 | 2.00 |
April | 0.187147E+11 | 8493.92 | 08-APR-18:00 | 14.00 | 4.47 | 91605673.43 | 126.83 | 28-APR-09:39 | 10.67 | 8.02 |
May | 0.445093E+10 | 3504.20 | 31-MAY-24:00 | 16.00 | 10.67 | 99238086.01 | 126.86 | 22-MAY-13:00 | 16.00 | 10.67 |
June | 0.965033E+10 | 5375.78 | 30-JUN-24:00 | 22.50 | 11.08 | 98962625.65 | 126.86 | 22-JUN-13:09 | 22.50 | 11.08 |
July | 0.149614E+11 | 7289.27 | 31-JUL-24:00 | 18.90 | 16.75 | 91884420.47 | 126.84 | 28-JUL-09:09 | 18.90 | 16.75 |
August | 0.200559E+11 | 8767.19 | 05-AUG-18:21 | 19.50 | 15.20 | 0.104059E+09 | 142.98 | 16-AUG-13:00 | 37.00 | 16.36 |
September | 0.455735E+10 | 3328.73 | 30-SEP-24:00 | 10.40 | 8.79 | 91608444.99 | 126.85 | 01-SEP-13:00 | 10.40 | 8.79 |
October | 0.923607E+10 | 5024.37 | 09-OCT-16:41 | 21.17 | 8.73 | 95231552.80 | 126.84 | 27-OCT-13:00 | 7.00 | 5.91 |
November | 0.136736E+11 | 6643.43 | 07-NOV-16:20 | 19.00 | 6.82 | 94301124.63 | 126.83 | 10-NOV-10:00 | 5.00 | 5.00 |
December | 0.188195E+11 | 8284.19 | 29-DEC-16:20 | 11.00 | 4.49 | 91880746.10 | 126.82 | 13-DEC-14:09 | 11.00 | 4.49 |
Annual Sum or Average | 0.139332E+12 | 0.114364E+10 | ||||||||
Minimum of Months | 0.335695E+10 | 2721.98 | 5.00 | 2.00 | 86396806.33 | 126.82 | 5.00 | 2.00 | ||
Maximum of Months | 0.200559E+11 | 8767.19 | 22.50 | 16.75 | 0.104059E+09 | 142.98 | 37.00 | 16.75 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.172714E+10 | 2496.45 | 23-JAN-16:50 | 14.83 | 5.56 | 95224899.57 | 126.83 | 27-JAN-14:00 | 10.00 | 5.47 |
February | 0.575637E+10 | 4407.22 | 23-FEB-17:00 | 5.00 | 2.11 | 86396800.60 | 126.83 | 23-FEB-14:00 | 5.00 | 2.11 |
March | 0.120357E+11 | 6621.87 | 31-MAR-23:30 | 6.75 | 2.17 | 0.103237E+09 | 126.83 | 17-MAR-13:00 | 6.75 | 2.17 |
April | 0.164580E+11 | 8028.66 | 07-APR-17:50 | 17.33 | 7.10 | 91605798.34 | 126.83 | 28-APR-13:09 | 15.50 | 11.11 |
May | 0.364419E+10 | 3286.18 | 31-MAY-24:00 | 16.00 | 10.67 | 99237468.36 | 126.85 | 22-MAY-09:00 | 16.00 | 10.67 |
June | 0.900373E+10 | 5248.58 | 30-JUN-24:00 | 22.50 | 11.08 | 98962929.52 | 126.86 | 22-JUN-13:09 | 22.50 | 11.08 |
July | 0.141184E+11 | 6849.51 | 31-JUL-24:00 | 18.90 | 16.75 | 91885015.57 | 126.84 | 28-JUL-09:20 | 18.90 | 16.75 |
August | 0.189270E+11 | 8333.99 | 13-AUG-18:34 | 21.67 | 9.90 | 0.103820E+09 | 140.42 | 16-AUG-13:00 | 37.00 | 16.36 |
September | 0.389036E+10 | 2959.18 | 30-SEP-23:50 | 10.50 | 8.84 | 91608243.26 | 126.86 | 01-SEP-13:00 | 10.50 | 8.84 |
October | 0.765573E+10 | 4530.35 | 08-OCT-16:45 | 17.17 | 8.30 | 95231462.08 | 126.84 | 03-OCT-13:00 | 17.17 | 8.30 |
November | 0.115168E+11 | 6232.88 | 07-NOV-16:20 | 19.00 | 6.82 | 94301103.25 | 126.83 | 10-NOV-10:00 | 5.00 | 5.00 |
December | 0.156807E+11 | 7669.43 | 14-DEC-16:00 | 13.00 | 4.65 | 91880783.13 | 126.82 | 13-DEC-14:09 | 13.00 | 4.65 |
Annual Sum or Average | 0.120414E+12 | 0.114339E+10 | ||||||||
Minimum of Months | 0.172714E+10 | 2496.45 | 5.00 | 2.11 | 86396800.60 | 126.82 | 5.00 | 2.11 | ||
Maximum of Months | 0.189270E+11 | 8333.99 | 22.50 | 16.75 | 0.103820E+09 | 140.42 | 37.00 | 16.75 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.905568E+09 | 2500.79 | 20-JAN-16:40 | 14.00 | 6.06 | 94069824.54 | 126.83 | 27-JAN-14:00 | 10.00 | 5.47 |
February | 0.438754E+10 | 4394.94 | 17-FEB-17:00 | 13.00 | 6.46 | 86396800.40 | 126.83 | 23-FEB-14:00 | 9.00 | 4.54 |
March | 0.108064E+11 | 6429.94 | 31-MAR-17:40 | 16.33 | 7.73 | 0.103237E+09 | 126.83 | 17-MAR-13:00 | 16.33 | 7.73 |
April | 0.151712E+11 | 8117.85 | 07-APR-17:50 | 17.33 | 7.10 | 91605863.77 | 126.83 | 28-APR-13:09 | 15.50 | 11.11 |
May | 0.316069E+10 | 3229.20 | 31-MAY-23:40 | 16.23 | 10.60 | 99215033.53 | 127.04 | 01-MAY-09:09 | 16.23 | 10.60 |
June | 0.897292E+10 | 5243.37 | 30-JUN-24:00 | 22.50 | 11.08 | 98962889.80 | 126.87 | 22-JUN-13:09 | 22.50 | 11.08 |
July | 0.140954E+11 | 6836.78 | 01-JUL-18:50 | 26.33 | 10.09 | 91884978.93 | 126.84 | 28-JUL-09:30 | 18.50 | 16.18 |
August | 0.188717E+11 | 8469.31 | 13-AUG-18:30 | 22.00 | 10.09 | 0.103717E+09 | 139.35 | 16-AUG-13:00 | 37.00 | 16.36 |
September | 0.359422E+10 | 3170.35 | 10-SEP-17:35 | 29.77 | 11.98 | 91608268.27 | 126.86 | 01-SEP-13:00 | 29.77 | 11.98 |
October | 0.641530E+10 | 4532.59 | 05-OCT-16:50 | 19.12 | 7.42 | 95231443.03 | 126.83 | 03-OCT-13:00 | 19.12 | 7.42 |
November | 0.996467E+10 | 6255.14 | 07-NOV-16:20 | 19.00 | 6.82 | 94301126.96 | 126.83 | 10-NOV-10:00 | 5.00 | 5.00 |
December | 0.139225E+11 | 7634.20 | 14-DEC-16:00 | 13.00 | 4.65 | 91880795.79 | 126.82 | 13-DEC-14:09 | 13.00 | 4.65 |
Annual Sum or Average | 0.110268E+12 | 0.114211E+10 | ||||||||
Minimum of Months | 0.905568E+09 | 2500.79 | 13.00 | 4.65 | 86396800.40 | 126.82 | 5.00 | 4.54 | ||
Maximum of Months | 0.188717E+11 | 8469.31 | 29.77 | 11.98 | 0.103717E+09 | 139.35 | 37.00 | 16.36 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.238303E+12 | 92885.93 | 20-JAN-17:00 | 12.00 | 5.16 | 0.206153E+10 | 2745.53 | 09-JAN-10:09 | 12.00 | 5.16 |
February | 0.435402E+12 | 184399.67 | 27-FEB-17:00 | 13.00 | 4.60 | 0.187031E+10 | 2745.92 | 02-FEB-10:09 | 13.00 | 4.60 |
March | 0.729048E+12 | 359469.22 | 31-MAR-24:00 | 6.10 | 2.00 | 0.223484E+10 | 2746.17 | 30-MAR-09:09 | 6.10 | 2.00 |
April | 0.942875E+12 | 368460.23 | 07-APR-16:00 | 21.00 | 8.12 | 0.198325E+10 | 2751.49 | 28-APR-13:50 | 17.50 | 12.23 |
May | 0.241364E+12 | 176420.07 | 31-MAY-24:00 | 16.00 | 10.67 | 0.214821E+10 | 2746.83 | 31-MAY-09:00 | 16.00 | 10.67 |
June | 0.472218E+12 | 268615.02 | 30-JUN-23:55 | 22.50 | 11.08 | 0.214296E+10 | 2749.81 | 02-JUN-09:00 | 22.50 | 11.08 |
July | 0.733259E+12 | 359772.24 | 31-JUL-24:00 | 18.90 | 16.75 | 0.199018E+10 | 2751.15 | 17-JUL-13:39 | 18.90 | 16.75 |
August | 0.975265E+12 | 384368.46 | 16-AUG-21:12 | 25.33 | 11.70 | 0.265161E+10 | 5027.92 | 16-AUG-13:09 | 25.33 | 11.70 |
September | 0.237885E+12 | 176428.75 | 30-SEP-24:00 | 10.40 | 8.79 | 0.198337E+10 | 2747.81 | 13-SEP-13:50 | 10.40 | 8.79 |
October | 0.488028E+12 | 266451.26 | 31-OCT-24:00 | -5.8 | -5.8 | 0.206154E+10 | 2745.80 | 26-OCT-09:09 | -5.8 | -5.8 |
November | 0.708848E+12 | 277967.86 | 07-NOV-17:00 | 15.00 | 5.62 | 0.204142E+10 | 2745.77 | 09-NOV-10:09 | 18.33 | 8.73 |
December | 0.976164E+12 | 369201.23 | 04-DEC-17:00 | 12.00 | 4.76 | 0.198896E+10 | 2745.58 | 08-DEC-10:09 | 3.83 | -2.7 |
Annual Sum or Average | 0.717866E+13 | 0.251582E+11 | ||||||||
Minimum of Months | 0.237885E+12 | 92885.93 | -5.8 | -5.8 | 0.187031E+10 | 2745.53 | -5.8 | -5.8 | ||
Maximum of Months | 0.976164E+12 | 384368.46 | 25.33 | 16.75 | 0.265161E+10 | 5027.92 | 25.33 | 16.75 |
Report: ZoneHeatingSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.207056E+09 | 16785.32 | 06-JAN-05:21 | -7.5 |
February | 0.115501E+09 | 15000.88 | 27-FEB-05:55 | 4.00 |
March | 0.102797E+09 | 14548.40 | 11-MAR-05:15 | 4.00 |
April | 0.108256E+09 | 14579.56 | 29-APR-04:15 | 7.00 |
May | 0.204520E+09 | 14641.36 | 31-MAY-04:15 | 11.33 |
June | 0.247270E+09 | 19411.23 | 24-JUN-16:01 | 31.60 |
July | 0.476516E+09 | 22334.54 | 15-JUL-16:01 | 34.00 |
August | 0.404638E+09 | 20512.71 | 26-AUG-16:01 | 32.67 |
September | 0.366519E+09 | 17273.52 | 02-SEP-16:01 | 29.62 |
October | 0.243911E+09 | 14583.18 | 07-OCT-04:15 | 6.00 |
November | 0.224042E+09 | 14579.67 | 10-NOV-05:15 | 6.67 |
December | 0.147315E+09 | 14809.03 | 18-DEC-06:06 | -0.2 |
Annual Sum or Average | 0.284834E+10 | |||
Minimum of Months | 0.102797E+09 | 14548.40 | -7.5 | |
Maximum of Months | 0.476516E+09 | 22334.54 | 34.00 |
Report: ZoneHeatingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.50 |
February | 0.00 | 0.00 | 01-FEB-00:10 | -5.3 |
March | 0.00 | 0.00 | 01-MAR-00:10 | -1.1 |
April | 0.00 | 0.00 | 01-APR-00:10 | 5.90 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 5.43 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 15.88 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 22.27 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.93 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 18.18 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 10.30 |
November | 0.00 | 0.00 | 01-NOV-00:05 | -5.7 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 2.77 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | -5.7 | |
Maximum of Months | 0.00 | 0.00 | 22.27 |
Report: ZoneHeatingSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.50 |
February | 28450717.82 | 41947.06 | 06-FEB-05:01 | -10.0 |
March | 5904874.47 | 39547.74 | 20-MAR-05:01 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 5.90 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 5.43 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 15.88 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 22.27 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.93 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 18.18 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 10.30 |
November | 0.00 | 0.00 | 01-NOV-00:05 | -5.7 |
December | 0.124283E+09 | 44539.31 | 26-DEC-05:11 | 4.33 |
Annual Sum or Average | 0.158639E+09 | |||
Minimum of Months | 0.00 | 0.00 | -10.0 | |
Maximum of Months | 0.124283E+09 | 44539.31 | 22.27 |
Report: ZoneHeatingSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.189464E+10 | 79620.35 | 17-JAN-04:01 | -1.8 |
February | 0.191584E+10 | 83329.98 | 06-FEB-04:01 | -10.0 |
March | 0.944880E+09 | 81250.08 | 20-MAR-03:01 | -1.5 |
April | 0.129637E+10 | 79660.93 | 17-APR-03:01 | -8.0 |
May | 97364507.74 | 71741.92 | 01-MAY-04:11 | 6.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 15.88 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 22.27 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.93 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 18.18 |
October | 0.750151E+09 | 78721.55 | 30-OCT-03:01 | -9.2 |
November | 0.924070E+09 | 74209.94 | 27-NOV-05:11 | -7.0 |
December | 0.244800E+10 | 82109.77 | 26-DEC-04:01 | 0.50 |
Annual Sum or Average | 0.102713E+11 | |||
Minimum of Months | 0.00 | 0.00 | -10.0 | |
Maximum of Months | 0.244800E+10 | 83329.98 | 22.27 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.172753E+09 | 13326.89 | 06-JAN-05:01 | -7.8 |
February | 0.166625E+09 | 13402.59 | 06-FEB-05:01 | -10.0 |
March | 9361950.67 | 12555.54 | 20-MAR-05:01 | 0.00 |
April | 6098102.88 | 12527.48 | 17-APR-05:01 | -8.0 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 5.43 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 15.88 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 22.27 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.93 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 18.18 |
October | 32712933.68 | 12587.43 | 31-OCT-05:01 | -8.2 |
November | 70944836.68 | 13059.04 | 30-NOV-05:01 | -12.8 |
December | 0.506731E+09 | 13976.60 | 22-DEC-05:01 | -21.0 |
Annual Sum or Average | 0.965227E+09 | |||
Minimum of Months | 0.00 | 0.00 | -21.0 | |
Maximum of Months | 0.506731E+09 | 13976.60 | 22.27 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.127486E+09 | 12282.29 | 06-JAN-05:01 | -7.8 |
February | 0.164845E+09 | 12629.72 | 06-FEB-05:01 | -10.0 |
March | 21229743.12 | 11012.44 | 20-MAR-05:01 | 0.00 |
April | 17999837.49 | 11214.43 | 17-APR-05:01 | -8.0 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 5.43 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 15.88 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 22.27 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.93 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 18.18 |
October | 51731822.47 | 11272.56 | 30-OCT-05:01 | -10.0 |
November | 92916732.71 | 12399.68 | 29-NOV-05:01 | -10.0 |
December | 0.419706E+09 | 13190.20 | 20-DEC-05:01 | -19.0 |
Annual Sum or Average | 0.895915E+09 | |||
Minimum of Months | 0.00 | 0.00 | -19.0 | |
Maximum of Months | 0.419706E+09 | 13190.20 | 22.27 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.196177E+09 | 17922.84 | 05-JAN-05:01 | -17.0 |
February | 0.313225E+09 | 19109.98 | 06-FEB-04:01 | -10.0 |
March | 62683403.35 | 17399.02 | 20-MAR-04:01 | 0.83 |
April | 85272382.12 | 16980.04 | 17-APR-04:41 | -8.0 |
May | 460367.24 | 3069.11 | 01-MAY-05:03 | 6.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 15.88 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 22.27 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.93 |
September | 48994.35 | 408.29 | 22-SEP-05:04 | -1.7 |
October | 0.137327E+09 | 17268.51 | 31-OCT-04:01 | -8.0 |
November | 0.135781E+09 | 18167.34 | 29-NOV-05:01 | -10.0 |
December | 0.494232E+09 | 18961.80 | 20-DEC-05:01 | -19.0 |
Annual Sum or Average | 0.142521E+10 | |||
Minimum of Months | 0.00 | 0.00 | -19.0 | |
Maximum of Months | 0.494232E+09 | 19109.98 | 22.27 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 21204246.40 | 8866.06 | 06-JAN-06:01 | -7.0 |
February | 11412631.66 | 9339.56 | 06-FEB-05:01 | -10.0 |
March | 235851.96 | 3144.69 | 20-MAR-05:01 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 5.90 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 5.43 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 15.88 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 22.27 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.93 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 18.18 |
October | 1616297.05 | 8883.53 | 30-OCT-05:01 | -10.0 |
November | 2252405.93 | 8737.41 | 30-NOV-06:01 | -12.0 |
December | 25447378.26 | 9611.07 | 21-DEC-05:01 | -18.2 |
Annual Sum or Average | 62168811.25 | |||
Minimum of Months | 0.00 | 0.00 | -18.2 | |
Maximum of Months | 25447378.26 | 9611.07 | 22.27 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.177176E+10 | 14370.39 | 17-JAN-04:01 | -1.8 |
February | 0.246662E+10 | 15326.44 | 12-FEB-05:21 | -19.5 |
March | 0.125411E+10 | 15844.54 | 19-MAR-06:32 | -14.8 |
April | 0.624418E+09 | 14706.02 | 17-APR-03:01 | -8.0 |
May | 36482796.52 | 12717.92 | 01-MAY-04:11 | 6.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 15.88 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 22.27 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.93 |
September | 10130495.90 | 11970.93 | 22-SEP-05:02 | -1.7 |
October | 0.757535E+09 | 14886.12 | 30-OCT-03:01 | -9.2 |
November | 0.130222E+10 | 14582.95 | 30-NOV-04:01 | -13.8 |
December | 0.404452E+10 | 15623.31 | 24-DEC-06:51 | -20.0 |
Annual Sum or Average | 0.122678E+11 | |||
Minimum of Months | 0.00 | 0.00 | -20.0 | |
Maximum of Months | 0.404452E+10 | 15844.54 | 22.27 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.882761E+09 | 18463.90 | 06-JAN-04:01 | -11.3 |
February | 0.131559E+10 | 19696.89 | 06-FEB-04:01 | -10.0 |
March | 0.723865E+09 | 20410.08 | 19-MAR-06:32 | -14.8 |
April | 0.367606E+09 | 18737.16 | 17-APR-03:01 | -8.0 |
May | 18518728.07 | 16233.67 | 01-MAY-04:11 | 6.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 15.88 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 22.27 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.93 |
September | 5562412.94 | 12551.73 | 22-SEP-05:02 | -1.7 |
October | 0.527906E+09 | 19282.21 | 30-OCT-03:01 | -9.2 |
November | 0.746443E+09 | 18921.47 | 30-NOV-04:01 | -13.8 |
December | 0.222359E+10 | 20397.59 | 24-DEC-06:51 | -20.0 |
Annual Sum or Average | 0.681184E+10 | |||
Minimum of Months | 0.00 | 0.00 | -20.0 | |
Maximum of Months | 0.222359E+10 | 20410.08 | 22.27 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.650816E+09 | 20686.25 | 05-JAN-04:01 | -16.2 |
February | 0.131036E+10 | 22398.96 | 06-FEB-04:01 | -10.0 |
March | 0.894566E+09 | 23093.10 | 19-MAR-06:32 | -14.8 |
April | 0.547830E+09 | 21647.44 | 17-APR-03:01 | -8.0 |
May | 40057118.08 | 18833.68 | 01-MAY-04:11 | 6.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 15.88 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 22.27 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.93 |
September | 9677616.51 | 16266.15 | 22-SEP-05:02 | -1.7 |
October | 0.629819E+09 | 21633.01 | 30-OCT-03:01 | -9.2 |
November | 0.656506E+09 | 21134.31 | 01-NOV-03:01 | -3.5 |
December | 0.191454E+10 | 22835.07 | 24-DEC-06:51 | -20.0 |
Annual Sum or Average | 0.665417E+10 | |||
Minimum of Months | 0.00 | 0.00 | -20.0 | |
Maximum of Months | 0.191454E+10 | 23093.10 | 22.27 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.669484E+09 | 18162.58 | 05-JAN-04:01 | -16.2 |
February | 0.950199E+09 | 19851.82 | 06-FEB-04:01 | -10.0 |
March | 0.531040E+09 | 20013.78 | 19-MAR-06:32 | -14.8 |
April | 0.290494E+09 | 18779.00 | 17-APR-03:01 | -8.0 |
May | 15091101.13 | 13602.94 | 01-MAY-04:11 | 6.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 15.88 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 22.27 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.93 |
September | 8217514.91 | 12975.62 | 22-SEP-05:02 | -1.7 |
October | 0.382021E+09 | 19165.60 | 30-OCT-03:01 | -9.2 |
November | 0.533483E+09 | 18592.00 | 30-NOV-04:01 | -13.8 |
December | 0.168374E+10 | 20491.15 | 24-DEC-06:51 | -20.0 |
Annual Sum or Average | 0.506377E+10 | |||
Minimum of Months | 0.00 | 0.00 | -20.0 | |
Maximum of Months | 0.168374E+10 | 20491.15 | 22.27 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.524048E+10 | 17473.42 | 16-JAN-02:32 | -10.3 |
February | 0.560205E+10 | 18316.15 | 13-FEB-02:52 | -12.0 |
March | 0.360457E+10 | 18748.33 | 19-MAR-05:31 | -12.1 |
April | 0.242766E+10 | 17447.42 | 16-APR-20:53 | -3.0 |
May | 0.212512E+09 | 16754.94 | 01-MAY-04:11 | 6.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 15.88 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 22.27 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.93 |
September | 91469515.07 | 14881.23 | 22-SEP-04:01 | -0.3 |
October | 0.248284E+10 | 17463.78 | 29-OCT-18:03 | -6.0 |
November | 0.368335E+10 | 17412.47 | 30-NOV-03:02 | -14.0 |
December | 0.830909E+10 | 18747.29 | 24-DEC-01:01 | -21.0 |
Annual Sum or Average | 0.316540E+11 | |||
Minimum of Months | 0.00 | 0.00 | -21.0 | |
Maximum of Months | 0.830909E+10 | 18748.33 | 22.27 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.253815E+10 | 21669.03 | 17-JAN-04:01 | -1.8 |
February | 0.290083E+10 | 22824.05 | 13-FEB-03:32 | -12.0 |
March | 0.194866E+10 | 23613.98 | 19-MAR-05:31 | -12.1 |
April | 0.138795E+10 | 21754.50 | 24-APR-03:01 | -2.0 |
May | 0.101287E+09 | 21307.40 | 01-MAY-04:11 | 6.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 15.88 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 22.27 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.93 |
September | 45613847.17 | 18730.42 | 22-SEP-04:01 | -0.3 |
October | 0.153703E+10 | 21557.76 | 31-OCT-03:01 | -8.0 |
November | 0.195676E+10 | 21221.07 | 21-NOV-04:11 | -4.0 |
December | 0.459280E+10 | 23654.57 | 23-DEC-04:11 | -21.1 |
Annual Sum or Average | 0.170091E+11 | |||
Minimum of Months | 0.00 | 0.00 | -21.1 | |
Maximum of Months | 0.459280E+10 | 23654.57 | 22.27 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.225290E+10 | 23879.03 | 06-JAN-04:01 | -11.3 |
February | 0.335774E+10 | 25101.58 | 06-FEB-04:01 | -10.0 |
March | 0.270138E+10 | 26353.68 | 19-MAR-05:31 | -12.1 |
April | 0.214279E+10 | 24353.24 | 17-APR-01:32 | -6.7 |
May | 0.226183E+09 | 23657.75 | 01-MAY-04:11 | 6.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 15.88 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 22.27 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.93 |
September | 68159927.89 | 20746.91 | 22-SEP-04:01 | -0.3 |
October | 0.198348E+10 | 23989.44 | 31-OCT-03:01 | -8.0 |
November | 0.201204E+10 | 23533.48 | 21-NOV-04:11 | -4.0 |
December | 0.459568E+10 | 25981.89 | 23-DEC-04:11 | -21.1 |
Annual Sum or Average | 0.193403E+11 | |||
Minimum of Months | 0.00 | 0.00 | -21.1 | |
Maximum of Months | 0.459568E+10 | 26353.68 | 22.27 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.206057E+10 | 23097.79 | 17-JAN-04:01 | -1.8 |
February | 0.232919E+10 | 24064.27 | 06-FEB-04:01 | -10.0 |
March | 0.156188E+10 | 25105.04 | 19-MAR-02:11 | -8.9 |
April | 0.102029E+10 | 22909.49 | 24-APR-03:01 | -2.0 |
May | 0.105310E+09 | 21933.45 | 01-MAY-04:11 | 6.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 15.88 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 22.27 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.93 |
September | 42583691.71 | 19784.45 | 22-SEP-04:01 | -0.3 |
October | 0.114291E+10 | 22847.87 | 31-OCT-03:01 | -8.0 |
November | 0.151422E+10 | 22356.23 | 30-NOV-04:01 | -13.8 |
December | 0.364119E+10 | 25054.94 | 23-DEC-04:11 | -21.1 |
Annual Sum or Average | 0.134181E+11 | |||
Minimum of Months | 0.00 | 0.00 | -21.1 | |
Maximum of Months | 0.364119E+10 | 25105.04 | 22.27 |
Report: ZoneHeatingSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.243088E+09 | 10351.53 | 09-JAN-06:01 | 4.00 |
February | 0.460590E+09 | 14103.77 | 26-FEB-15:41 | 17.83 |
March | 0.214801E+09 | 14491.07 | 26-MAR-15:22 | 11.00 |
April | 85006957.17 | 12844.64 | 05-APR-04:01 | 0.00 |
May | 70451499.71 | 11577.91 | 01-MAY-04:11 | 6.00 |
June | 87697452.18 | 12844.03 | 25-JUN-16:21 | 32.70 |
July | 0.131400E+09 | 12009.91 | 16-JUL-14:41 | 35.83 |
August | 0.126366E+09 | 13586.80 | 20-AUG-15:31 | 28.00 |
September | 86748501.37 | 11771.58 | 24-SEP-14:52 | 22.20 |
October | 0.119542E+09 | 13320.18 | 15-OCT-14:21 | 14.50 |
November | 0.272227E+09 | 15310.47 | 05-NOV-14:21 | 21.00 |
December | 0.542956E+09 | 14014.08 | 26-DEC-06:03 | 7.00 |
Annual Sum or Average | 0.244087E+10 | |||
Minimum of Months | 70451499.71 | 10351.53 | 0.00 | |
Maximum of Months | 0.542956E+09 | 15310.47 | 35.83 |
Report: ZoneHeatingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.163224E+10 | 13727.55 | 01-JAN-13:21 | 5.00 |
February | 0.202497E+10 | 11639.96 | 12-FEB-15:02 | -5.2 |
March | 0.117122E+10 | 17527.37 | 26-MAR-16:01 | 11.33 |
April | 0.901230E+09 | 7880.02 | 08-APR-17:41 | 14.33 |
May | 0.154829E+09 | 7225.37 | 28-MAY-15:42 | 20.00 |
June | 72276206.94 | 14070.89 | 25-JUN-16:21 | 32.70 |
July | 86915115.35 | 13120.25 | 02-JUL-15:21 | 28.50 |
August | 63935426.12 | 12452.52 | 20-AUG-15:31 | 28.00 |
September | 84500808.80 | 13981.01 | 10-SEP-14:31 | 31.97 |
October | 0.438108E+09 | 14459.85 | 08-OCT-15:01 | 19.67 |
November | 0.118649E+10 | 17166.21 | 05-NOV-14:41 | 21.00 |
December | 0.251979E+10 | 10784.16 | 17-DEC-13:41 | 18.00 |
Annual Sum or Average | 0.103365E+11 | |||
Minimum of Months | 63935426.12 | 7225.37 | -5.2 | |
Maximum of Months | 0.251979E+10 | 17527.37 | 32.70 |
Report: ZoneHeatingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.715833E+10 | 25849.20 | 05-JAN-06:01 | -17.0 |
February | 0.704541E+10 | 30790.19 | 13-FEB-05:12 | -11.0 |
March | 0.492859E+10 | 25972.12 | 20-MAR-04:22 | 0.50 |
April | 0.360769E+10 | 28816.65 | 17-APR-04:22 | -8.0 |
May | 0.687105E+09 | 16787.32 | 05-MAY-05:02 | 6.00 |
June | 99705334.39 | 16363.93 | 09-JUN-05:03 | 6.97 |
July | 86587083.11 | 13679.93 | 06-JUL-05:03 | 14.50 |
August | 86713827.34 | 13416.68 | 23-AUG-05:03 | 11.17 |
September | 0.440390E+09 | 15883.61 | 15-SEP-05:03 | 9.00 |
October | 0.393284E+10 | 27481.17 | 30-OCT-04:12 | -10.0 |
November | 0.522859E+10 | 25862.56 | 30-NOV-06:01 | -12.0 |
December | 0.101443E+11 | 32856.27 | 22-DEC-05:12 | -21.0 |
Annual Sum or Average | 0.434462E+11 | |||
Minimum of Months | 86587083.11 | 13416.68 | -21.0 | |
Maximum of Months | 0.101443E+11 | 32856.27 | 14.50 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.50 |
February | 0.00 | 0.00 | 01-FEB-00:10 | -5.3 |
March | 0.00 | 0.00 | 01-MAR-00:10 | -1.1 |
April | 0.00 | 0.00 | 01-APR-00:10 | 5.90 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 5.43 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 15.88 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 22.27 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.93 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 18.18 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 10.30 |
November | 0.00 | 0.00 | 01-NOV-00:05 | -5.7 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 2.77 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | -5.7 | |
Maximum of Months | 0.00 | 0.00 | 22.27 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.133945E+09 | 648.48 | 01-JAN-07:53 | -4.0 |
February | 0.00 | 0.00 | 01-FEB-00:10 | -5.3 |
March | 0.00 | 0.00 | 01-MAR-00:10 | -1.1 |
April | 0.00 | 0.00 | 01-APR-00:10 | 5.90 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 5.43 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 15.88 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 22.27 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.93 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 18.18 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 10.30 |
November | 0.00 | 0.00 | 01-NOV-00:05 | -5.7 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 2.77 |
Annual Sum or Average | 0.133945E+09 | |||
Minimum of Months | 0.00 | 0.00 | -5.7 | |
Maximum of Months | 0.133945E+09 | 648.48 | 22.27 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.695062E+09 | 753.05 | 16-JAN-17:55 | -3.0 |
February | 77439349.87 | 691.07 | 06-FEB-03:00 | -11.0 |
March | 0.00 | 0.00 | 01-MAR-00:10 | -1.1 |
April | 2655410.15 | 757.31 | 30-APR-23:20 | 5.33 |
May | 27539042.04 | 717.01 | 01-MAY-00:10 | 5.43 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 15.88 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 22.27 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.93 |
September | 6021969.56 | 446.24 | 22-SEP-00:35 | -1.0 |
October | 11935482.24 | 511.68 | 29-OCT-17:53 | -6.0 |
November | 0.00 | 0.00 | 01-NOV-00:05 | -5.7 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 2.77 |
Annual Sum or Average | 0.820654E+09 | |||
Minimum of Months | 0.00 | 0.00 | -11.0 | |
Maximum of Months | 0.695062E+09 | 757.31 | 22.27 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.50 |
February | 0.00 | 0.00 | 01-FEB-00:10 | -5.3 |
March | 0.00 | 0.00 | 01-MAR-00:10 | -1.1 |
April | 0.00 | 0.00 | 01-APR-00:10 | 5.90 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 5.43 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 15.88 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 22.27 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.93 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 18.18 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 10.30 |
November | 0.00 | 0.00 | 01-NOV-00:05 | -5.7 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 2.77 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | -5.7 | |
Maximum of Months | 0.00 | 0.00 | 22.27 |
Report: ZoneElectricSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.219312E+11 | 22950.34 | 02-JAN-08:09 | 0.360447E+11 | 13457.54 | 01-JAN-00:10 |
February | 0.198933E+11 | 22950.34 | 01-FEB-08:09 | 0.325565E+11 | 13457.54 | 01-FEB-00:10 |
March | 0.236388E+11 | 22950.34 | 01-MAR-08:09 | 0.360447E+11 | 13457.54 | 01-MAR-00:10 |
April | 0.211142E+11 | 22950.34 | 03-APR-07:10 | 0.348820E+11 | 13457.54 | 01-APR-00:10 |
May | 0.227850E+11 | 22950.34 | 01-MAY-07:10 | 0.360447E+11 | 13457.54 | 01-MAY-00:10 |
June | 0.226748E+11 | 22950.34 | 01-JUN-07:10 | 0.348820E+11 | 13457.54 | 01-JUN-00:10 |
July | 0.212244E+11 | 22950.34 | 03-JUL-07:10 | 0.360447E+11 | 13457.54 | 01-JUL-00:10 |
August | 0.236388E+11 | 22950.34 | 01-AUG-07:10 | 0.360447E+11 | 13457.54 | 01-AUG-00:10 |
September | 0.211142E+11 | 22950.34 | 01-SEP-07:10 | 0.348820E+11 | 13457.54 | 01-SEP-00:10 |
October | 0.219312E+11 | 22950.34 | 02-OCT-07:10 | 0.360447E+11 | 13457.54 | 01-OCT-00:10 |
November | 0.216742E+11 | 22950.34 | 01-NOV-07:10 | 0.348820E+11 | 13457.54 | 01-NOV-00:10 |
December | 0.212244E+11 | 22950.34 | 01-DEC-08:09 | 0.360447E+11 | 13457.54 | 01-DEC-00:10 |
Annual Sum or Average | 0.262844E+12 | 0.424397E+12 | ||||
Minimum of Months | 0.198933E+11 | 22950.34 | 0.325565E+11 | 13457.54 | ||
Maximum of Months | 0.236388E+11 | 22950.34 | 0.360447E+11 | 13457.54 |
Report: ZoneElectricSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.196958E+11 | 20611.01 | 02-JAN-08:09 | 0.243681E+11 | 17206.63 | 02-JAN-08:09 |
February | 0.178655E+11 | 20611.01 | 01-FEB-08:09 | 0.220609E+11 | 17206.63 | 01-FEB-08:09 |
March | 0.212293E+11 | 20611.01 | 01-MAR-08:09 | 0.253549E+11 | 17206.63 | 01-MAR-08:09 |
April | 0.189620E+11 | 20611.01 | 03-APR-07:10 | 0.235306E+11 | 17206.63 | 03-APR-07:10 |
May | 0.204625E+11 | 20611.01 | 01-MAY-07:10 | 0.248615E+11 | 17206.63 | 01-MAY-07:10 |
June | 0.203636E+11 | 20611.01 | 01-JUN-07:10 | 0.244160E+11 | 17206.63 | 01-JUN-07:10 |
July | 0.190610E+11 | 20611.01 | 03-JUL-07:10 | 0.239708E+11 | 17206.63 | 03-JUL-07:10 |
August | 0.212293E+11 | 20611.01 | 01-AUG-07:10 | 0.253549E+11 | 17206.63 | 01-AUG-07:10 |
September | 0.189620E+11 | 20611.01 | 01-SEP-07:10 | 0.235199E+11 | 17206.63 | 01-SEP-07:10 |
October | 0.196958E+11 | 20611.01 | 02-OCT-07:10 | 0.243735E+11 | 17206.63 | 02-OCT-07:10 |
November | 0.194649E+11 | 20611.01 | 01-NOV-07:10 | 0.238373E+11 | 17206.63 | 01-NOV-07:10 |
December | 0.190610E+11 | 20611.01 | 01-DEC-08:09 | 0.239654E+11 | 17206.63 | 01-DEC-08:09 |
Annual Sum or Average | 0.236053E+12 | 0.289614E+12 | ||||
Minimum of Months | 0.178655E+11 | 20611.01 | 0.220609E+11 | 17206.63 | ||
Maximum of Months | 0.212293E+11 | 20611.01 | 0.253549E+11 | 17206.63 |
Report: ZoneElectricSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.196958E+11 | 20611.01 | 02-JAN-08:09 | 0.243680E+11 | 17206.56 | 02-JAN-08:09 |
February | 0.178655E+11 | 20611.01 | 01-FEB-08:09 | 0.220609E+11 | 17206.56 | 01-FEB-08:09 |
March | 0.212293E+11 | 20611.01 | 01-MAR-08:09 | 0.253548E+11 | 17206.56 | 01-MAR-08:09 |
April | 0.189620E+11 | 20611.01 | 03-APR-07:10 | 0.235305E+11 | 17206.56 | 03-APR-07:10 |
May | 0.204625E+11 | 20611.01 | 01-MAY-07:10 | 0.248614E+11 | 17206.56 | 01-MAY-07:10 |
June | 0.203636E+11 | 20611.01 | 01-JUN-07:10 | 0.244159E+11 | 17206.56 | 01-JUN-07:10 |
July | 0.190610E+11 | 20611.01 | 03-JUL-07:10 | 0.239707E+11 | 17206.56 | 03-JUL-07:10 |
August | 0.212293E+11 | 20611.01 | 01-AUG-07:10 | 0.253548E+11 | 17206.56 | 01-AUG-07:10 |
September | 0.189620E+11 | 20611.01 | 01-SEP-07:10 | 0.235198E+11 | 17206.56 | 01-SEP-07:10 |
October | 0.196958E+11 | 20611.01 | 02-OCT-07:10 | 0.243734E+11 | 17206.56 | 02-OCT-07:10 |
November | 0.194649E+11 | 20611.01 | 01-NOV-07:10 | 0.238372E+11 | 17206.56 | 01-NOV-07:10 |
December | 0.190610E+11 | 20611.01 | 01-DEC-08:09 | 0.239653E+11 | 17206.56 | 01-DEC-08:09 |
Annual Sum or Average | 0.236053E+12 | 0.289613E+12 | ||||
Minimum of Months | 0.178655E+11 | 20611.01 | 0.220609E+11 | 17206.56 | ||
Maximum of Months | 0.212293E+11 | 20611.01 | 0.253548E+11 | 17206.56 |
Report: ZoneElectricSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.196958E+11 | 20611.01 | 02-JAN-08:09 | 0.243680E+11 | 17206.56 | 02-JAN-08:09 |
February | 0.178655E+11 | 20611.01 | 01-FEB-08:09 | 0.220609E+11 | 17206.56 | 01-FEB-08:09 |
March | 0.212293E+11 | 20611.01 | 01-MAR-08:09 | 0.253548E+11 | 17206.56 | 01-MAR-08:09 |
April | 0.189620E+11 | 20611.01 | 03-APR-07:10 | 0.235305E+11 | 17206.56 | 03-APR-07:10 |
May | 0.204625E+11 | 20611.01 | 01-MAY-07:10 | 0.248614E+11 | 17206.56 | 01-MAY-07:10 |
June | 0.203636E+11 | 20611.01 | 01-JUN-07:10 | 0.244159E+11 | 17206.56 | 01-JUN-07:10 |
July | 0.190610E+11 | 20611.01 | 03-JUL-07:10 | 0.239707E+11 | 17206.56 | 03-JUL-07:10 |
August | 0.212293E+11 | 20611.01 | 01-AUG-07:10 | 0.253548E+11 | 17206.56 | 01-AUG-07:10 |
September | 0.189620E+11 | 20611.01 | 01-SEP-07:10 | 0.235198E+11 | 17206.56 | 01-SEP-07:10 |
October | 0.196958E+11 | 20611.01 | 02-OCT-07:10 | 0.243734E+11 | 17206.56 | 02-OCT-07:10 |
November | 0.194649E+11 | 20611.01 | 01-NOV-07:10 | 0.238372E+11 | 17206.56 | 01-NOV-07:10 |
December | 0.190610E+11 | 20611.01 | 01-DEC-08:09 | 0.239653E+11 | 17206.56 | 01-DEC-08:09 |
Annual Sum or Average | 0.236053E+12 | 0.289613E+12 | ||||
Minimum of Months | 0.178655E+11 | 20611.01 | 0.220609E+11 | 17206.56 | ||
Maximum of Months | 0.212293E+11 | 20611.01 | 0.253548E+11 | 17206.56 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.163916E+10 | 2587.92 | 02-JAN-16:19 | 0.305979E+10 | 2160.55 | 02-JAN-08:09 |
February | 0.138798E+10 | 2587.92 | 06-FEB-16:30 | 0.277008E+10 | 2160.55 | 01-FEB-08:09 |
March | 0.152816E+10 | 2255.20 | 21-MAR-07:10 | 0.318369E+10 | 2160.55 | 01-MAR-08:09 |
April | 0.131658E+10 | 1803.00 | 03-APR-07:10 | 0.295462E+10 | 2160.55 | 03-APR-07:10 |
May | 0.137297E+10 | 1231.33 | 01-MAY-07:10 | 0.312174E+10 | 2160.55 | 01-MAY-07:10 |
June | 0.134413E+10 | 1231.33 | 01-JUN-07:10 | 0.306580E+10 | 2160.55 | 01-JUN-07:10 |
July | 0.127336E+10 | 1231.33 | 03-JUL-07:10 | 0.300989E+10 | 2160.55 | 03-JUL-07:10 |
August | 0.144799E+10 | 1350.81 | 07-AUG-15:30 | 0.318369E+10 | 2160.55 | 01-AUG-07:10 |
September | 0.133353E+10 | 1350.81 | 08-SEP-15:00 | 0.295328E+10 | 2160.55 | 01-SEP-07:10 |
October | 0.148254E+10 | 2255.20 | 12-OCT-07:10 | 0.306046E+10 | 2160.55 | 02-OCT-07:10 |
November | 0.160104E+10 | 2587.92 | 06-NOV-16:30 | 0.299314E+10 | 2160.55 | 01-NOV-07:10 |
December | 0.160604E+10 | 2587.92 | 01-DEC-16:10 | 0.300922E+10 | 2160.55 | 01-DEC-08:09 |
Annual Sum or Average | 0.173335E+11 | 0.363654E+11 | ||||
Minimum of Months | 0.127336E+10 | 1231.33 | 0.277008E+10 | 2160.55 | ||
Maximum of Months | 0.163916E+10 | 2587.92 | 0.318369E+10 | 2160.55 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.103714E+10 | 1667.75 | 02-JAN-16:19 | 0.197184E+10 | 1392.34 | 02-JAN-08:09 |
February | 0.887287E+09 | 1667.75 | 06-FEB-16:30 | 0.178515E+10 | 1392.34 | 01-FEB-08:09 |
March | 0.981957E+09 | 1161.92 | 01-MAR-16:00 | 0.205169E+10 | 1392.34 | 01-MAR-08:09 |
April | 0.850862E+09 | 947.51 | 03-APR-07:10 | 0.190407E+10 | 1392.34 | 03-APR-07:10 |
May | 0.891535E+09 | 793.52 | 01-MAY-07:10 | 0.201177E+10 | 1392.34 | 01-MAY-07:10 |
June | 0.874167E+09 | 793.52 | 01-JUN-07:10 | 0.197572E+10 | 1392.34 | 01-JUN-07:10 |
July | 0.827255E+09 | 793.52 | 03-JUL-07:10 | 0.193969E+10 | 1392.34 | 03-JUL-07:10 |
August | 0.938539E+09 | 870.51 | 07-AUG-15:20 | 0.205169E+10 | 1392.34 | 01-AUG-07:10 |
September | 0.859040E+09 | 947.51 | 21-SEP-15:00 | 0.190321E+10 | 1392.34 | 01-SEP-07:10 |
October | 0.945784E+09 | 1453.34 | 23-OCT-07:10 | 0.197228E+10 | 1392.34 | 02-OCT-07:10 |
November | 0.102156E+10 | 1667.75 | 06-NOV-16:30 | 0.192889E+10 | 1392.34 | 01-NOV-07:10 |
December | 0.101992E+10 | 1667.75 | 01-DEC-16:10 | 0.193926E+10 | 1392.34 | 01-DEC-08:09 |
Annual Sum or Average | 0.111350E+11 | 0.234352E+11 | ||||
Minimum of Months | 0.827255E+09 | 793.52 | 0.178515E+10 | 1392.34 | ||
Maximum of Months | 0.103714E+10 | 1667.75 | 0.205169E+10 | 1392.34 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.154348E+10 | 2587.98 | 02-JAN-16:40 | 0.305983E+10 | 2160.58 | 02-JAN-08:09 |
February | 0.134478E+10 | 2587.98 | 06-FEB-16:30 | 0.277013E+10 | 2160.58 | 01-FEB-08:09 |
March | 0.151566E+10 | 2255.25 | 21-MAR-07:10 | 0.318374E+10 | 2160.58 | 01-MAR-08:09 |
April | 0.131945E+10 | 1803.04 | 03-APR-07:10 | 0.295467E+10 | 2160.58 | 03-APR-07:10 |
May | 0.138266E+10 | 1231.36 | 01-MAY-07:10 | 0.312179E+10 | 2160.58 | 01-MAY-07:10 |
June | 0.135978E+10 | 1350.84 | 16-JUN-07:10 | 0.306585E+10 | 2160.58 | 01-JUN-07:10 |
July | 0.128475E+10 | 1231.36 | 03-JUL-07:10 | 0.300994E+10 | 2160.58 | 03-JUL-07:10 |
August | 0.145497E+10 | 1350.84 | 07-AUG-15:39 | 0.318374E+10 | 2160.58 | 01-AUG-07:10 |
September | 0.133018E+10 | 1350.84 | 21-SEP-15:30 | 0.295333E+10 | 2160.58 | 01-SEP-07:10 |
October | 0.145392E+10 | 2255.25 | 23-OCT-07:10 | 0.306051E+10 | 2160.58 | 02-OCT-07:10 |
November | 0.152956E+10 | 2587.98 | 06-NOV-16:49 | 0.299318E+10 | 2160.58 | 01-NOV-07:10 |
December | 0.152607E+10 | 2587.98 | 01-DEC-16:30 | 0.300927E+10 | 2160.58 | 01-DEC-08:09 |
Annual Sum or Average | 0.170453E+11 | 0.363660E+11 | ||||
Minimum of Months | 0.128475E+10 | 1231.36 | 0.277013E+10 | 2160.58 | ||
Maximum of Months | 0.154348E+10 | 2587.98 | 0.318374E+10 | 2160.58 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.100862E+10 | 1667.75 | 02-JAN-16:40 | 0.197183E+10 | 1392.33 | 02-JAN-08:09 |
February | 0.870208E+09 | 1667.75 | 06-FEB-16:40 | 0.178514E+10 | 1392.33 | 01-FEB-08:09 |
March | 0.973952E+09 | 1453.34 | 21-MAR-07:10 | 0.205168E+10 | 1392.33 | 01-MAR-08:09 |
April | 0.845210E+09 | 1161.92 | 03-APR-07:10 | 0.190406E+10 | 1392.33 | 03-APR-07:10 |
May | 0.885246E+09 | 870.51 | 19-MAY-07:10 | 0.201175E+10 | 1392.33 | 01-MAY-07:10 |
June | 0.868881E+09 | 870.51 | 16-JUN-07:10 | 0.197570E+10 | 1392.33 | 01-JUN-07:10 |
July | 0.821904E+09 | 870.51 | 28-JUL-07:10 | 0.193968E+10 | 1392.33 | 03-JUL-07:10 |
August | 0.928851E+09 | 870.51 | 21-AUG-07:10 | 0.205168E+10 | 1392.33 | 01-AUG-07:10 |
September | 0.855462E+09 | 947.51 | 22-SEP-07:10 | 0.190319E+10 | 1392.33 | 01-SEP-07:10 |
October | 0.941742E+09 | 1453.34 | 12-OCT-07:10 | 0.197226E+10 | 1392.33 | 02-OCT-07:10 |
November | 0.992260E+09 | 1667.75 | 06-NOV-16:49 | 0.192888E+10 | 1392.33 | 01-NOV-07:10 |
December | 0.994347E+09 | 1667.75 | 01-DEC-16:30 | 0.193924E+10 | 1392.33 | 01-DEC-08:09 |
Annual Sum or Average | 0.109867E+11 | 0.234351E+11 | ||||
Minimum of Months | 0.821904E+09 | 870.51 | 0.178514E+10 | 1392.33 | ||
Maximum of Months | 0.100862E+10 | 1667.75 | 0.205168E+10 | 1392.33 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.163222E+10 | 2587.92 | 02-JAN-16:19 | 0.305979E+10 | 2160.55 | 02-JAN-08:09 |
February | 0.138389E+10 | 2587.92 | 06-FEB-16:30 | 0.277008E+10 | 2160.55 | 01-FEB-08:09 |
March | 0.152554E+10 | 2255.20 | 21-MAR-07:10 | 0.318369E+10 | 2160.55 | 01-MAR-08:09 |
April | 0.131536E+10 | 1803.00 | 03-APR-07:10 | 0.295462E+10 | 2160.55 | 03-APR-07:10 |
May | 0.137242E+10 | 1231.33 | 01-MAY-07:10 | 0.312174E+10 | 2160.55 | 01-MAY-07:10 |
June | 0.134376E+10 | 1231.33 | 01-JUN-07:10 | 0.306580E+10 | 2160.55 | 01-JUN-07:10 |
July | 0.127229E+10 | 1231.33 | 03-JUL-07:10 | 0.300989E+10 | 2160.55 | 03-JUL-07:10 |
August | 0.144682E+10 | 1350.81 | 07-AUG-15:39 | 0.318369E+10 | 2160.55 | 01-AUG-07:10 |
September | 0.133231E+10 | 1350.81 | 08-SEP-15:00 | 0.295328E+10 | 2160.55 | 01-SEP-07:10 |
October | 0.147841E+10 | 2255.20 | 12-OCT-07:10 | 0.306046E+10 | 2160.55 | 02-OCT-07:10 |
November | 0.159592E+10 | 2587.92 | 06-NOV-16:30 | 0.299314E+10 | 2160.55 | 01-NOV-07:10 |
December | 0.160044E+10 | 2587.92 | 01-DEC-16:10 | 0.300922E+10 | 2160.55 | 01-DEC-08:09 |
Annual Sum or Average | 0.172994E+11 | 0.363654E+11 | ||||
Minimum of Months | 0.127229E+10 | 1231.33 | 0.277008E+10 | 2160.55 | ||
Maximum of Months | 0.163222E+10 | 2587.92 | 0.318369E+10 | 2160.55 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.103511E+10 | 1667.75 | 02-JAN-16:19 | 0.197184E+10 | 1392.34 | 02-JAN-08:09 |
February | 0.885131E+09 | 1667.75 | 06-FEB-16:30 | 0.178515E+10 | 1392.34 | 01-FEB-08:09 |
March | 0.980621E+09 | 1161.92 | 01-MAR-16:00 | 0.205169E+10 | 1392.34 | 01-MAR-08:09 |
April | 0.850077E+09 | 947.51 | 03-APR-07:10 | 0.190407E+10 | 1392.34 | 03-APR-07:10 |
May | 0.890834E+09 | 793.52 | 01-MAY-07:10 | 0.201177E+10 | 1392.34 | 01-MAY-07:10 |
June | 0.873584E+09 | 793.52 | 01-JUN-07:10 | 0.197572E+10 | 1392.34 | 01-JUN-07:10 |
July | 0.826554E+09 | 793.52 | 03-JUL-07:10 | 0.193969E+10 | 1392.34 | 03-JUL-07:10 |
August | 0.937754E+09 | 870.51 | 07-AUG-15:30 | 0.205169E+10 | 1392.34 | 01-AUG-07:10 |
September | 0.858560E+09 | 870.51 | 08-SEP-15:50 | 0.190321E+10 | 1392.34 | 01-SEP-07:10 |
October | 0.944294E+09 | 1453.34 | 23-OCT-07:10 | 0.197228E+10 | 1392.34 | 02-OCT-07:10 |
November | 0.101922E+10 | 1667.75 | 06-NOV-16:30 | 0.192889E+10 | 1392.34 | 01-NOV-07:10 |
December | 0.101758E+10 | 1667.75 | 01-DEC-16:10 | 0.193926E+10 | 1392.34 | 01-DEC-08:09 |
Annual Sum or Average | 0.111193E+11 | 0.234352E+11 | ||||
Minimum of Months | 0.826554E+09 | 793.52 | 0.178515E+10 | 1392.34 | ||
Maximum of Months | 0.103511E+10 | 1667.75 | 0.205169E+10 | 1392.34 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.154226E+10 | 2587.98 | 02-JAN-16:40 | 0.305983E+10 | 2160.58 | 02-JAN-08:09 |
February | 0.134324E+10 | 2587.98 | 06-FEB-16:30 | 0.277013E+10 | 2160.58 | 01-FEB-08:09 |
March | 0.151276E+10 | 2255.25 | 21-MAR-07:10 | 0.318374E+10 | 2160.58 | 01-MAR-08:09 |
April | 0.131846E+10 | 1803.04 | 03-APR-07:10 | 0.295467E+10 | 2160.58 | 03-APR-07:10 |
May | 0.138169E+10 | 1231.36 | 01-MAY-07:10 | 0.312179E+10 | 2160.58 | 01-MAY-07:10 |
June | 0.135874E+10 | 1231.36 | 01-JUN-07:10 | 0.306585E+10 | 2160.58 | 01-JUN-07:10 |
July | 0.128384E+10 | 1231.36 | 03-JUL-07:10 | 0.300994E+10 | 2160.58 | 03-JUL-07:10 |
August | 0.145384E+10 | 1350.84 | 07-AUG-15:50 | 0.318374E+10 | 2160.58 | 01-AUG-07:10 |
September | 0.132895E+10 | 1350.84 | 21-SEP-15:39 | 0.295333E+10 | 2160.58 | 01-SEP-07:10 |
October | 0.145182E+10 | 2255.25 | 23-OCT-07:10 | 0.306051E+10 | 2160.58 | 02-OCT-07:10 |
November | 0.152670E+10 | 2587.98 | 06-NOV-16:49 | 0.299318E+10 | 2160.58 | 01-NOV-07:10 |
December | 0.152437E+10 | 2587.98 | 01-DEC-16:30 | 0.300927E+10 | 2160.58 | 01-DEC-08:09 |
Annual Sum or Average | 0.170267E+11 | 0.363660E+11 | ||||
Minimum of Months | 0.128384E+10 | 1231.36 | 0.277013E+10 | 2160.58 | ||
Maximum of Months | 0.154226E+10 | 2587.98 | 0.318374E+10 | 2160.58 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.100705E+10 | 1667.75 | 02-JAN-16:40 | 0.197183E+10 | 1392.33 | 02-JAN-08:09 |
February | 0.868787E+09 | 1667.75 | 06-FEB-16:40 | 0.178514E+10 | 1392.33 | 01-FEB-08:09 |
March | 0.973199E+09 | 1453.34 | 21-MAR-07:10 | 0.205168E+10 | 1392.33 | 01-MAR-08:09 |
April | 0.844396E+09 | 1161.92 | 03-APR-07:10 | 0.190406E+10 | 1392.33 | 03-APR-07:10 |
May | 0.884744E+09 | 870.51 | 19-MAY-07:10 | 0.201175E+10 | 1392.33 | 01-MAY-07:10 |
June | 0.868563E+09 | 870.51 | 16-JUN-07:10 | 0.197570E+10 | 1392.33 | 01-JUN-07:10 |
July | 0.821386E+09 | 870.51 | 28-JUL-07:10 | 0.193968E+10 | 1392.33 | 03-JUL-07:10 |
August | 0.928309E+09 | 870.51 | 21-AUG-07:10 | 0.205168E+10 | 1392.33 | 01-AUG-07:10 |
September | 0.854699E+09 | 947.51 | 22-SEP-07:10 | 0.190319E+10 | 1392.33 | 01-SEP-07:10 |
October | 0.939999E+09 | 1453.34 | 12-OCT-07:10 | 0.197226E+10 | 1392.33 | 02-OCT-07:10 |
November | 0.990915E+09 | 1667.75 | 06-NOV-16:49 | 0.192888E+10 | 1392.33 | 01-NOV-07:10 |
December | 0.992832E+09 | 1667.75 | 01-DEC-16:30 | 0.193924E+10 | 1392.33 | 01-DEC-08:09 |
Annual Sum or Average | 0.109749E+11 | 0.234351E+11 | ||||
Minimum of Months | 0.821386E+09 | 870.51 | 0.178514E+10 | 1392.33 | ||
Maximum of Months | 0.100705E+10 | 1667.75 | 0.205168E+10 | 1392.33 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.163215E+10 | 2587.92 | 02-JAN-16:19 | 0.305979E+10 | 2160.55 | 02-JAN-08:09 |
February | 0.138367E+10 | 2587.92 | 06-FEB-16:30 | 0.277008E+10 | 2160.55 | 01-FEB-08:09 |
March | 0.152551E+10 | 2255.20 | 21-MAR-07:10 | 0.318369E+10 | 2160.55 | 01-MAR-08:09 |
April | 0.131536E+10 | 1803.00 | 03-APR-07:10 | 0.295462E+10 | 2160.55 | 03-APR-07:10 |
May | 0.137241E+10 | 1231.33 | 01-MAY-07:10 | 0.312174E+10 | 2160.55 | 01-MAY-07:10 |
June | 0.134376E+10 | 1231.33 | 01-JUN-07:10 | 0.306580E+10 | 2160.55 | 01-JUN-07:10 |
July | 0.127225E+10 | 1231.33 | 03-JUL-07:10 | 0.300989E+10 | 2160.55 | 03-JUL-07:10 |
August | 0.144669E+10 | 1350.81 | 07-AUG-15:39 | 0.318369E+10 | 2160.55 | 01-AUG-07:10 |
September | 0.133230E+10 | 1350.81 | 08-SEP-15:00 | 0.295328E+10 | 2160.55 | 01-SEP-07:10 |
October | 0.147834E+10 | 2255.20 | 12-OCT-07:10 | 0.306046E+10 | 2160.55 | 02-OCT-07:10 |
November | 0.159550E+10 | 2587.92 | 06-NOV-16:30 | 0.299314E+10 | 2160.55 | 01-NOV-07:10 |
December | 0.160034E+10 | 2587.92 | 01-DEC-16:10 | 0.300922E+10 | 2160.55 | 01-DEC-08:09 |
Annual Sum or Average | 0.172983E+11 | 0.363654E+11 | ||||
Minimum of Months | 0.127225E+10 | 1231.33 | 0.277008E+10 | 2160.55 | ||
Maximum of Months | 0.163215E+10 | 2587.92 | 0.318369E+10 | 2160.55 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.103511E+10 | 1667.75 | 02-JAN-16:19 | 0.197184E+10 | 1392.34 | 02-JAN-08:09 |
February | 0.885085E+09 | 1667.75 | 06-FEB-16:30 | 0.178515E+10 | 1392.34 | 01-FEB-08:09 |
March | 0.980526E+09 | 1161.92 | 01-MAR-16:00 | 0.205169E+10 | 1392.34 | 01-MAR-08:09 |
April | 0.849996E+09 | 947.51 | 03-APR-07:10 | 0.190407E+10 | 1392.34 | 03-APR-07:10 |
May | 0.890818E+09 | 793.52 | 01-MAY-07:10 | 0.201177E+10 | 1392.34 | 01-MAY-07:10 |
June | 0.873568E+09 | 793.52 | 01-JUN-07:10 | 0.197572E+10 | 1392.34 | 01-JUN-07:10 |
July | 0.826503E+09 | 793.52 | 03-JUL-07:10 | 0.193969E+10 | 1392.34 | 03-JUL-07:10 |
August | 0.937726E+09 | 870.51 | 07-AUG-15:30 | 0.205169E+10 | 1392.34 | 01-AUG-07:10 |
September | 0.858492E+09 | 870.51 | 08-SEP-15:50 | 0.190321E+10 | 1392.34 | 01-SEP-07:10 |
October | 0.944247E+09 | 1453.34 | 23-OCT-07:10 | 0.197228E+10 | 1392.34 | 02-OCT-07:10 |
November | 0.101917E+10 | 1667.75 | 06-NOV-16:30 | 0.192889E+10 | 1392.34 | 01-NOV-07:10 |
December | 0.101758E+10 | 1667.75 | 01-DEC-16:10 | 0.193926E+10 | 1392.34 | 01-DEC-08:09 |
Annual Sum or Average | 0.111188E+11 | 0.234352E+11 | ||||
Minimum of Months | 0.826503E+09 | 793.52 | 0.178515E+10 | 1392.34 | ||
Maximum of Months | 0.103511E+10 | 1667.75 | 0.205169E+10 | 1392.34 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.154219E+10 | 2587.98 | 02-JAN-16:40 | 0.305983E+10 | 2160.58 | 02-JAN-08:09 |
February | 0.134322E+10 | 2587.98 | 06-FEB-16:30 | 0.277013E+10 | 2160.58 | 01-FEB-08:09 |
March | 0.151270E+10 | 2255.25 | 21-MAR-07:10 | 0.318374E+10 | 2160.58 | 01-MAR-08:09 |
April | 0.131844E+10 | 1803.04 | 03-APR-07:10 | 0.295467E+10 | 2160.58 | 03-APR-07:10 |
May | 0.138166E+10 | 1231.36 | 01-MAY-07:10 | 0.312179E+10 | 2160.58 | 01-MAY-07:10 |
June | 0.135872E+10 | 1231.36 | 01-JUN-07:10 | 0.306585E+10 | 2160.58 | 01-JUN-07:10 |
July | 0.128372E+10 | 1231.36 | 03-JUL-07:10 | 0.300994E+10 | 2160.58 | 03-JUL-07:10 |
August | 0.145383E+10 | 1350.84 | 07-AUG-15:50 | 0.318374E+10 | 2160.58 | 01-AUG-07:10 |
September | 0.132884E+10 | 1350.84 | 21-SEP-15:39 | 0.295333E+10 | 2160.58 | 01-SEP-07:10 |
October | 0.145171E+10 | 2255.25 | 23-OCT-07:10 | 0.306051E+10 | 2160.58 | 02-OCT-07:10 |
November | 0.152662E+10 | 2587.98 | 06-NOV-16:49 | 0.299318E+10 | 2160.58 | 01-NOV-07:10 |
December | 0.152423E+10 | 2587.98 | 01-DEC-16:30 | 0.300927E+10 | 2160.58 | 01-DEC-08:09 |
Annual Sum or Average | 0.170259E+11 | 0.363660E+11 | ||||
Minimum of Months | 0.128372E+10 | 1231.36 | 0.277013E+10 | 2160.58 | ||
Maximum of Months | 0.154219E+10 | 2587.98 | 0.318374E+10 | 2160.58 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.100692E+10 | 1667.75 | 02-JAN-16:40 | 0.197183E+10 | 1392.33 | 02-JAN-08:09 |
February | 0.868741E+09 | 1667.75 | 06-FEB-16:40 | 0.178514E+10 | 1392.33 | 01-FEB-08:09 |
March | 0.973070E+09 | 1453.34 | 21-MAR-07:10 | 0.205168E+10 | 1392.33 | 01-MAR-08:09 |
April | 0.844318E+09 | 1161.92 | 03-APR-07:10 | 0.190406E+10 | 1392.33 | 03-APR-07:10 |
May | 0.884679E+09 | 870.51 | 19-MAY-07:10 | 0.201175E+10 | 1392.33 | 01-MAY-07:10 |
June | 0.868550E+09 | 870.51 | 16-JUN-07:10 | 0.197570E+10 | 1392.33 | 01-JUN-07:10 |
July | 0.821386E+09 | 870.51 | 28-JUL-07:10 | 0.193968E+10 | 1392.33 | 03-JUL-07:10 |
August | 0.928265E+09 | 870.51 | 21-AUG-07:10 | 0.205168E+10 | 1392.33 | 01-AUG-07:10 |
September | 0.854632E+09 | 947.51 | 22-SEP-07:10 | 0.190319E+10 | 1392.33 | 01-SEP-07:10 |
October | 0.939864E+09 | 1453.34 | 12-OCT-07:10 | 0.197226E+10 | 1392.33 | 02-OCT-07:10 |
November | 0.990858E+09 | 1667.75 | 06-NOV-16:49 | 0.192888E+10 | 1392.33 | 01-NOV-07:10 |
December | 0.992789E+09 | 1667.75 | 01-DEC-16:30 | 0.193924E+10 | 1392.33 | 01-DEC-08:09 |
Annual Sum or Average | 0.109741E+11 | 0.234351E+11 | ||||
Minimum of Months | 0.821386E+09 | 870.51 | 0.178514E+10 | 1392.33 | ||
Maximum of Months | 0.100692E+10 | 1667.75 | 0.205168E+10 | 1392.33 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.553024E+09 | 578.72 | 02-JAN-08:09 | 0.521915E+10 | 1948.61 | 01-JAN-00:10 |
February | 0.501634E+09 | 578.72 | 01-FEB-08:09 | 0.942813E+10 | 3897.21 | 01-FEB-00:10 |
March | 0.596080E+09 | 578.72 | 01-MAR-08:09 | 0.156645E+11 | 7794.42 | 31-MAR-23:10 |
April | 0.532421E+09 | 578.72 | 03-APR-07:10 | 0.201821E+11 | 7794.42 | 01-APR-00:10 |
May | 0.574552E+09 | 578.72 | 01-MAY-07:10 | 0.522616E+10 | 3897.21 | 31-MAY-23:10 |
June | 0.571774E+09 | 578.72 | 01-JUN-07:10 | 0.101086E+11 | 5845.82 | 30-JUN-23:10 |
July | 0.535199E+09 | 578.72 | 03-JUL-07:10 | 0.156645E+11 | 7794.42 | 31-JUL-23:10 |
August | 0.596080E+09 | 578.72 | 01-AUG-07:10 | 0.208555E+11 | 7794.42 | 01-AUG-00:10 |
September | 0.532421E+09 | 578.72 | 01-SEP-07:10 | 0.505780E+10 | 3897.21 | 30-SEP-23:10 |
October | 0.553024E+09 | 578.72 | 02-OCT-07:10 | 0.104453E+11 | 5845.82 | 31-OCT-23:10 |
November | 0.546542E+09 | 578.72 | 01-NOV-07:10 | 0.151524E+11 | 5845.82 | 01-NOV-00:10 |
December | 0.535199E+09 | 578.72 | 01-DEC-08:09 | 0.208766E+11 | 7794.42 | 01-DEC-00:10 |
Annual Sum or Average | 0.662795E+10 | 0.153881E+12 | ||||
Minimum of Months | 0.501634E+09 | 578.72 | 0.505780E+10 | 1948.61 | ||
Maximum of Months | 0.596080E+09 | 578.72 | 0.208766E+11 | 7794.42 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.553024E+09 | 578.72 | 02-JAN-08:09 | 0.521915E+10 | 1948.61 | 01-JAN-00:10 |
February | 0.501634E+09 | 578.72 | 01-FEB-08:09 | 0.942813E+10 | 3897.21 | 01-FEB-00:10 |
March | 0.596080E+09 | 578.72 | 01-MAR-08:09 | 0.156645E+11 | 7794.42 | 31-MAR-23:10 |
April | 0.532421E+09 | 578.72 | 03-APR-07:10 | 0.201821E+11 | 7794.42 | 01-APR-00:10 |
May | 0.574552E+09 | 578.72 | 01-MAY-07:10 | 0.522616E+10 | 3897.21 | 31-MAY-23:10 |
June | 0.571774E+09 | 578.72 | 01-JUN-07:10 | 0.101086E+11 | 5845.82 | 30-JUN-23:10 |
July | 0.535199E+09 | 578.72 | 03-JUL-07:10 | 0.156645E+11 | 7794.42 | 31-JUL-23:10 |
August | 0.596080E+09 | 578.72 | 01-AUG-07:10 | 0.208555E+11 | 7794.42 | 01-AUG-00:10 |
September | 0.532421E+09 | 578.72 | 01-SEP-07:10 | 0.505780E+10 | 3897.21 | 30-SEP-23:10 |
October | 0.553024E+09 | 578.72 | 02-OCT-07:10 | 0.104453E+11 | 5845.82 | 31-OCT-23:10 |
November | 0.546542E+09 | 578.72 | 01-NOV-07:10 | 0.151524E+11 | 5845.82 | 01-NOV-00:10 |
December | 0.535199E+09 | 578.72 | 01-DEC-08:09 | 0.208766E+11 | 7794.42 | 01-DEC-00:10 |
Annual Sum or Average | 0.662795E+10 | 0.153881E+12 | ||||
Minimum of Months | 0.501634E+09 | 578.72 | 0.505780E+10 | 1948.61 | ||
Maximum of Months | 0.596080E+09 | 578.72 | 0.208766E+11 | 7794.42 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.553024E+09 | 578.72 | 02-JAN-08:09 | 0.521915E+10 | 1948.61 | 01-JAN-00:10 |
February | 0.501634E+09 | 578.72 | 01-FEB-08:09 | 0.942813E+10 | 3897.21 | 01-FEB-00:10 |
March | 0.596080E+09 | 578.72 | 01-MAR-08:09 | 0.156645E+11 | 7794.42 | 31-MAR-23:10 |
April | 0.532421E+09 | 578.72 | 03-APR-07:10 | 0.201821E+11 | 7794.42 | 01-APR-00:10 |
May | 0.574552E+09 | 578.72 | 01-MAY-07:10 | 0.522616E+10 | 3897.21 | 31-MAY-23:10 |
June | 0.571774E+09 | 578.72 | 01-JUN-07:10 | 0.101086E+11 | 5845.82 | 30-JUN-23:10 |
July | 0.535199E+09 | 578.72 | 03-JUL-07:10 | 0.156645E+11 | 7794.42 | 31-JUL-23:10 |
August | 0.596080E+09 | 578.72 | 01-AUG-07:10 | 0.208555E+11 | 7794.42 | 01-AUG-00:10 |
September | 0.532421E+09 | 578.72 | 01-SEP-07:10 | 0.505780E+10 | 3897.21 | 30-SEP-23:10 |
October | 0.553024E+09 | 578.72 | 02-OCT-07:10 | 0.104453E+11 | 5845.82 | 31-OCT-23:10 |
November | 0.546542E+09 | 578.72 | 01-NOV-07:10 | 0.151524E+11 | 5845.82 | 01-NOV-00:10 |
December | 0.535199E+09 | 578.72 | 01-DEC-08:09 | 0.208766E+11 | 7794.42 | 01-DEC-00:10 |
Annual Sum or Average | 0.662795E+10 | 0.153881E+12 | ||||
Minimum of Months | 0.501634E+09 | 578.72 | 0.505780E+10 | 1948.61 | ||
Maximum of Months | 0.596080E+09 | 578.72 | 0.208766E+11 | 7794.42 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.618367E+10 | 6471.01 | 02-JAN-08:09 | 0.254202E+12 | 94908.13 | 01-JAN-00:10 |
February | 0.560905E+10 | 6471.01 | 01-FEB-08:09 | 0.459203E+12 | 189816.26 | 01-FEB-00:10 |
March | 0.666512E+10 | 6471.01 | 01-MAR-08:09 | 0.762947E+12 | 379632.52 | 31-MAR-23:10 |
April | 0.595330E+10 | 6471.01 | 03-APR-07:10 | 0.982982E+12 | 379632.52 | 01-APR-00:10 |
May | 0.642439E+10 | 6471.01 | 01-MAY-07:10 | 0.254544E+12 | 189816.26 | 31-MAY-23:10 |
June | 0.639333E+10 | 6471.01 | 01-JUN-07:10 | 0.492345E+12 | 284724.39 | 30-JUN-23:10 |
July | 0.598436E+10 | 6471.01 | 03-JUL-07:10 | 0.762947E+12 | 379632.52 | 31-JUL-23:10 |
August | 0.666512E+10 | 6471.01 | 01-AUG-07:10 | 0.101578E+13 | 379632.52 | 01-AUG-00:10 |
September | 0.595330E+10 | 6471.01 | 01-SEP-07:10 | 0.246344E+12 | 189816.26 | 30-SEP-23:10 |
October | 0.618367E+10 | 6471.01 | 02-OCT-07:10 | 0.508746E+12 | 284724.39 | 31-OCT-23:10 |
November | 0.611120E+10 | 6471.01 | 01-NOV-07:10 | 0.738006E+12 | 284724.39 | 01-NOV-00:10 |
December | 0.598436E+10 | 6471.01 | 01-DEC-08:09 | 0.101681E+13 | 379632.52 | 01-DEC-00:10 |
Annual Sum or Average | 0.741109E+11 | 0.749486E+13 | ||||
Minimum of Months | 0.560905E+10 | 6471.01 | 0.246344E+12 | 94908.13 | ||
Maximum of Months | 0.666512E+10 | 6471.01 | 0.101681E+13 | 379632.52 |
Report: SpaceGainsMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.133902E+11 | 0.219312E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.121482E+11 | 0.198933E+11 | 0.325565E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.145160E+11 | 0.236388E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.128805E+11 | 0.211142E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.139531E+11 | 0.227850E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.139143E+11 | 0.226748E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.129193E+11 | 0.212244E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.145160E+11 | 0.236388E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.128805E+11 | 0.211142E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.133902E+11 | 0.219312E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.132595E+11 | 0.216742E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.129193E+11 | 0.212244E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.160687E+12 | 0.262844E+12 | 0.424397E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.121482E+11 | 0.198933E+11 | 0.325565E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.145160E+11 | 0.236388E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.120254E+11 | 0.196958E+11 | 0.243681E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.109099E+11 | 0.178655E+11 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.130364E+11 | 0.212293E+11 | 0.253549E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.115676E+11 | 0.189620E+11 | 0.235306E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.125309E+11 | 0.204625E+11 | 0.248615E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.124961E+11 | 0.203636E+11 | 0.244160E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.116025E+11 | 0.190610E+11 | 0.239708E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.130364E+11 | 0.212293E+11 | 0.253549E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.115676E+11 | 0.189620E+11 | 0.235199E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.120254E+11 | 0.196958E+11 | 0.243735E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.119080E+11 | 0.194649E+11 | 0.238373E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.116025E+11 | 0.190610E+11 | 0.239654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.144308E+12 | 0.236053E+12 | 0.289614E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.109099E+11 | 0.178655E+11 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.130364E+11 | 0.212293E+11 | 0.253549E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.120254E+11 | 0.196958E+11 | 0.243680E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.109099E+11 | 0.178655E+11 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.130364E+11 | 0.212293E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.115676E+11 | 0.189620E+11 | 0.235305E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.125309E+11 | 0.204625E+11 | 0.248614E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.124961E+11 | 0.203636E+11 | 0.244159E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.116025E+11 | 0.190610E+11 | 0.239707E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.130364E+11 | 0.212293E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.115676E+11 | 0.189620E+11 | 0.235198E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.120254E+11 | 0.196958E+11 | 0.243734E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.119080E+11 | 0.194649E+11 | 0.238372E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.116025E+11 | 0.190610E+11 | 0.239653E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.144308E+12 | 0.236053E+12 | 0.289613E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.109099E+11 | 0.178655E+11 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.130364E+11 | 0.212293E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.120254E+11 | 0.196958E+11 | 0.243680E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.109099E+11 | 0.178655E+11 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.130364E+11 | 0.212293E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.115676E+11 | 0.189620E+11 | 0.235305E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.125309E+11 | 0.204625E+11 | 0.248614E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.124961E+11 | 0.203636E+11 | 0.244159E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.116025E+11 | 0.190610E+11 | 0.239707E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.130364E+11 | 0.212293E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.115676E+11 | 0.189620E+11 | 0.235198E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.120254E+11 | 0.196958E+11 | 0.243734E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.119080E+11 | 0.194649E+11 | 0.238372E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.116025E+11 | 0.190610E+11 | 0.239653E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.144308E+12 | 0.236053E+12 | 0.289613E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.109099E+11 | 0.178655E+11 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.130364E+11 | 0.212293E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150991E+10 | 0.163916E+10 | 0.305979E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.485223E+09 |
February | 0.136985E+10 | 0.138798E+10 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.754814E+09 |
March | 0.163685E+10 | 0.152816E+10 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4.44 | 0.828645E+09 |
April | 0.145243E+10 | 0.131658E+10 | 0.295462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.901026E+09 |
May | 0.157338E+10 | 0.137297E+10 | 0.312174E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1759828.20 | 0.452587E+09 |
June | 0.156900E+10 | 0.134413E+10 | 0.306580E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 36322552.77 | 0.191189E+09 |
July | 0.145680E+10 | 0.127336E+10 | 0.300989E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 46003879.02 | 0.187324E+09 |
August | 0.163685E+10 | 0.144799E+10 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 24672584.55 | 0.181924E+09 |
September | 0.145243E+10 | 0.133353E+10 | 0.295328E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13509525.12 | 0.285351E+09 |
October | 0.150991E+10 | 0.148254E+10 | 0.306046E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 250146.28 | 0.630942E+09 |
November | 0.149516E+10 | 0.160104E+10 | 0.299314E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.551544E+09 |
December | 0.145680E+10 | 0.160604E+10 | 0.300922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.104075E+10 |
Annual Sum or Average | 0.181194E+11 | 0.173335E+11 | 0.363654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.122519E+09 | 0.649132E+10 |
Minimum of Months | 0.136985E+10 | 0.127336E+10 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.181924E+09 |
Maximum of Months | 0.163685E+10 | 0.163916E+10 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 46003879.02 | 0.104075E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.103714E+10 | 0.197184E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.326223E+09 |
February | 0.882782E+09 | 0.887287E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.504470E+09 |
March | 0.105485E+10 | 0.981957E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2.88 | 0.547591E+09 |
April | 0.936002E+09 | 0.850862E+09 | 0.190407E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.589280E+09 |
May | 0.101394E+10 | 0.891535E+09 | 0.201177E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1180649.13 | 0.297412E+09 |
June | 0.101113E+10 | 0.874167E+09 | 0.197572E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 25072108.36 | 0.121983E+09 |
July | 0.938820E+09 | 0.827255E+09 | 0.193969E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 32662656.04 | 0.116583E+09 |
August | 0.105485E+10 | 0.938539E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16989461.43 | 0.107486E+09 |
September | 0.936002E+09 | 0.859040E+09 | 0.190321E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9476863.03 | 0.189398E+09 |
October | 0.973041E+09 | 0.945784E+09 | 0.197228E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 166758.17 | 0.419915E+09 |
November | 0.963541E+09 | 0.102156E+10 | 0.192889E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.363285E+09 |
December | 0.938820E+09 | 0.101992E+10 | 0.193926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.684637E+09 |
Annual Sum or Average | 0.116768E+11 | 0.111350E+11 | 0.234352E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 85548499.04 | 0.426826E+10 |
Minimum of Months | 0.882782E+09 | 0.827255E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.107486E+09 |
Maximum of Months | 0.105485E+10 | 0.103714E+10 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 32662656.04 | 0.684637E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150994E+10 | 0.154348E+10 | 0.305983E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.508131E+09 |
February | 0.136988E+10 | 0.134478E+10 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.776818E+09 |
March | 0.163688E+10 | 0.151566E+10 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.834967E+09 |
April | 0.145246E+10 | 0.131945E+10 | 0.295467E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.881437E+09 |
May | 0.157341E+10 | 0.138266E+10 | 0.312179E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1761243.08 | 0.445118E+09 |
June | 0.156904E+10 | 0.135978E+10 | 0.306585E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 36775281.81 | 0.185956E+09 |
July | 0.145684E+10 | 0.128475E+10 | 0.300994E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 47080287.62 | 0.181266E+09 |
August | 0.163688E+10 | 0.145497E+10 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 24228459.92 | 0.181257E+09 |
September | 0.145246E+10 | 0.133018E+10 | 0.295333E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12100825.24 | 0.296401E+09 |
October | 0.150994E+10 | 0.145392E+10 | 0.306051E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 154492.27 | 0.646045E+09 |
November | 0.149520E+10 | 0.152956E+10 | 0.299318E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.568173E+09 |
December | 0.145684E+10 | 0.152607E+10 | 0.300927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.106736E+10 |
Annual Sum or Average | 0.181198E+11 | 0.170453E+11 | 0.363660E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.122101E+09 | 0.657293E+10 |
Minimum of Months | 0.136988E+10 | 0.128475E+10 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.181257E+09 |
Maximum of Months | 0.163688E+10 | 0.154348E+10 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 47080287.62 | 0.106736E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.100862E+10 | 0.197183E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.339788E+09 |
February | 0.882782E+09 | 0.870208E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.535222E+09 |
March | 0.105485E+10 | 0.973952E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3.04 | 0.597978E+09 |
April | 0.936002E+09 | 0.845210E+09 | 0.190406E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.658893E+09 |
May | 0.101394E+10 | 0.885246E+09 | 0.201175E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1171762.32 | 0.320810E+09 |
June | 0.101113E+10 | 0.868881E+09 | 0.197570E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23830530.36 | 0.145021E+09 |
July | 0.938820E+09 | 0.821904E+09 | 0.193968E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 29639234.73 | 0.142073E+09 |
August | 0.105485E+10 | 0.928851E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16150006.32 | 0.142189E+09 |
September | 0.936002E+09 | 0.855462E+09 | 0.190319E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8527799.99 | 0.209693E+09 |
October | 0.973041E+09 | 0.941742E+09 | 0.197226E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 166764.29 | 0.449897E+09 |
November | 0.963541E+09 | 0.992260E+09 | 0.192888E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.395692E+09 |
December | 0.938820E+09 | 0.994347E+09 | 0.193924E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.754365E+09 |
Annual Sum or Average | 0.116768E+11 | 0.109867E+11 | 0.234351E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 79486101.05 | 0.469162E+10 |
Minimum of Months | 0.882782E+09 | 0.821904E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.142073E+09 |
Maximum of Months | 0.105485E+10 | 0.100862E+10 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 29639234.73 | 0.754365E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150991E+10 | 0.163222E+10 | 0.305979E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.101163E+10 |
February | 0.136985E+10 | 0.138389E+10 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.159085E+10 |
March | 0.163685E+10 | 0.152554E+10 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.172476E+10 |
April | 0.145243E+10 | 0.131536E+10 | 0.295462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.184160E+10 |
May | 0.157338E+10 | 0.137242E+10 | 0.312174E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3927731.98 | 0.986266E+09 |
June | 0.156900E+10 | 0.134376E+10 | 0.306580E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 84546180.68 | 0.428483E+09 |
July | 0.145680E+10 | 0.127229E+10 | 0.300989E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.107328E+09 | 0.427071E+09 |
August | 0.163685E+10 | 0.144682E+10 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 57876379.66 | 0.416694E+09 |
September | 0.145243E+10 | 0.133231E+10 | 0.295328E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 32747318.71 | 0.613058E+09 |
October | 0.150991E+10 | 0.147841E+10 | 0.306046E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 540445.51 | 0.131790E+10 |
November | 0.149516E+10 | 0.159592E+10 | 0.299314E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.115167E+10 |
December | 0.145680E+10 | 0.160044E+10 | 0.300922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8063.51 | 0.214914E+10 |
Annual Sum or Average | 0.181194E+11 | 0.172994E+11 | 0.363654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.286974E+09 | 0.136591E+11 |
Minimum of Months | 0.136985E+10 | 0.127229E+10 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.416694E+09 |
Maximum of Months | 0.163685E+10 | 0.163222E+10 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.107328E+09 | 0.214914E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.715730E+09 | 0.103511E+10 | 0.197184E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.697335E+09 |
February | 0.649041E+09 | 0.885131E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.109159E+10 |
March | 0.773965E+09 | 0.980621E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.118541E+10 |
April | 0.688021E+09 | 0.850077E+09 | 0.190407E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.125729E+10 |
May | 0.744847E+09 | 0.890834E+09 | 0.201177E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2635183.74 | 0.661904E+09 |
June | 0.742030E+09 | 0.873584E+09 | 0.197572E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 57109684.51 | 0.286205E+09 |
July | 0.690839E+09 | 0.826554E+09 | 0.193969E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 73021015.53 | 0.291990E+09 |
August | 0.773965E+09 | 0.937754E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 37947579.31 | 0.284600E+09 |
September | 0.688021E+09 | 0.858560E+09 | 0.190321E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21623037.09 | 0.422082E+09 |
October | 0.715730E+09 | 0.944294E+09 | 0.197228E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 361134.63 | 0.909614E+09 |
November | 0.708685E+09 | 0.101922E+10 | 0.192889E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.783906E+09 |
December | 0.690839E+09 | 0.101758E+10 | 0.193926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7265.22 | 0.145711E+10 |
Annual Sum or Average | 0.858171E+10 | 0.111193E+11 | 0.234352E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.192705E+09 | 0.932904E+10 |
Minimum of Months | 0.649041E+09 | 0.826554E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.284600E+09 |
Maximum of Months | 0.773965E+09 | 0.103511E+10 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 73021015.53 | 0.145711E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150994E+10 | 0.154226E+10 | 0.305983E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.115666E+10 |
February | 0.136988E+10 | 0.134324E+10 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.174413E+10 |
March | 0.163688E+10 | 0.151276E+10 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.185323E+10 |
April | 0.145246E+10 | 0.131846E+10 | 0.295467E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.190206E+10 |
May | 0.157341E+10 | 0.138169E+10 | 0.312179E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3926073.75 | 0.998668E+09 |
June | 0.156904E+10 | 0.135874E+10 | 0.306585E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 84905095.44 | 0.422746E+09 |
July | 0.145684E+10 | 0.128384E+10 | 0.300994E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.107747E+09 | 0.427034E+09 |
August | 0.163688E+10 | 0.145384E+10 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 55135069.47 | 0.443023E+09 |
September | 0.145246E+10 | 0.132895E+10 | 0.295333E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 26761119.14 | 0.672208E+09 |
October | 0.150994E+10 | 0.145182E+10 | 0.306051E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 187367.86 | 0.144903E+10 |
November | 0.149520E+10 | 0.152670E+10 | 0.299318E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.127805E+10 |
December | 0.145684E+10 | 0.152437E+10 | 0.300927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.235586E+10 |
Annual Sum or Average | 0.181198E+11 | 0.170267E+11 | 0.363660E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.278662E+09 | 0.147027E+11 |
Minimum of Months | 0.136988E+10 | 0.128384E+10 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.422746E+09 |
Maximum of Months | 0.163688E+10 | 0.154226E+10 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.107747E+09 | 0.235586E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.100705E+10 | 0.197183E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.713623E+09 |
February | 0.882782E+09 | 0.868787E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.111129E+10 |
March | 0.105485E+10 | 0.973199E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.120723E+10 |
April | 0.936002E+09 | 0.844396E+09 | 0.190406E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.127696E+10 |
May | 0.101394E+10 | 0.884744E+09 | 0.201175E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2679620.61 | 0.686628E+09 |
June | 0.101113E+10 | 0.868563E+09 | 0.197570E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 56662661.50 | 0.309782E+09 |
July | 0.938820E+09 | 0.821386E+09 | 0.193968E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 72043856.51 | 0.304687E+09 |
August | 0.105485E+10 | 0.928309E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 39183877.22 | 0.310451E+09 |
September | 0.936002E+09 | 0.854699E+09 | 0.190319E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20711860.20 | 0.441713E+09 |
October | 0.973041E+09 | 0.939999E+09 | 0.197226E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 432498.62 | 0.922672E+09 |
November | 0.963541E+09 | 0.990915E+09 | 0.192888E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.803287E+09 |
December | 0.938820E+09 | 0.992832E+09 | 0.193924E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.148701E+10 |
Annual Sum or Average | 0.116768E+11 | 0.109749E+11 | 0.234351E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.191714E+09 | 0.957534E+10 |
Minimum of Months | 0.882782E+09 | 0.821386E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.304687E+09 |
Maximum of Months | 0.105485E+10 | 0.100705E+10 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 72043856.51 | 0.148701E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150991E+10 | 0.163215E+10 | 0.305979E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.117512E+10 |
February | 0.136985E+10 | 0.138367E+10 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.189123E+10 |
March | 0.163685E+10 | 0.152551E+10 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.204889E+10 |
April | 0.145243E+10 | 0.131536E+10 | 0.295462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.213978E+10 |
May | 0.157338E+10 | 0.137241E+10 | 0.312174E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4624847.39 | 0.116348E+10 |
June | 0.156900E+10 | 0.134376E+10 | 0.306580E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.101619E+09 | 0.525624E+09 |
July | 0.145680E+10 | 0.127225E+10 | 0.300989E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.128511E+09 | 0.523738E+09 |
August | 0.163685E+10 | 0.144669E+10 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 69390808.75 | 0.507752E+09 |
September | 0.145243E+10 | 0.133230E+10 | 0.295328E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 38495641.77 | 0.726765E+09 |
October | 0.150991E+10 | 0.147834E+10 | 0.306046E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 653208.98 | 0.152479E+10 |
November | 0.149516E+10 | 0.159550E+10 | 0.299314E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 29465.97 | 0.133791E+10 |
December | 0.145680E+10 | 0.160034E+10 | 0.300922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23457.89 | 0.256481E+10 |
Annual Sum or Average | 0.181194E+11 | 0.172983E+11 | 0.363654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.343347E+09 | 0.161299E+11 |
Minimum of Months | 0.136985E+10 | 0.127225E+10 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.507752E+09 |
Maximum of Months | 0.163685E+10 | 0.163215E+10 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.128511E+09 | 0.256481E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.103511E+10 | 0.197184E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.805569E+09 |
February | 0.882782E+09 | 0.885085E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.130149E+10 |
March | 0.105485E+10 | 0.980526E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.141620E+10 |
April | 0.936002E+09 | 0.849996E+09 | 0.190407E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.147264E+10 |
May | 0.101394E+10 | 0.890818E+09 | 0.201177E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3097616.15 | 0.791648E+09 |
June | 0.101113E+10 | 0.873568E+09 | 0.197572E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 67929076.76 | 0.354338E+09 |
July | 0.938820E+09 | 0.826503E+09 | 0.193969E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 86417256.88 | 0.361254E+09 |
August | 0.105485E+10 | 0.937726E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 45410541.15 | 0.350887E+09 |
September | 0.936002E+09 | 0.858492E+09 | 0.190321E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 24821443.42 | 0.510196E+09 |
October | 0.973041E+09 | 0.944247E+09 | 0.197228E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 409655.04 | 0.106654E+10 |
November | 0.963541E+09 | 0.101917E+10 | 0.192889E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.917099E+09 |
December | 0.938820E+09 | 0.101758E+10 | 0.193926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8884.44 | 0.173660E+10 |
Annual Sum or Average | 0.116768E+11 | 0.111188E+11 | 0.234352E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.228094E+09 | 0.110845E+11 |
Minimum of Months | 0.882782E+09 | 0.826503E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.350887E+09 |
Maximum of Months | 0.105485E+10 | 0.103511E+10 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 86417256.88 | 0.173660E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150994E+10 | 0.154219E+10 | 0.305983E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.133112E+10 |
February | 0.136988E+10 | 0.134322E+10 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.207257E+10 |
March | 0.163688E+10 | 0.151270E+10 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.220751E+10 |
April | 0.145246E+10 | 0.131844E+10 | 0.295467E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.221886E+10 |
May | 0.157341E+10 | 0.138166E+10 | 0.312179E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4622365.37 | 0.118392E+10 |
June | 0.156904E+10 | 0.135872E+10 | 0.306585E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.102045E+09 | 0.517484E+09 |
July | 0.145684E+10 | 0.128372E+10 | 0.300994E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.129099E+09 | 0.522170E+09 |
August | 0.163688E+10 | 0.145383E+10 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 66819573.65 | 0.541362E+09 |
September | 0.145246E+10 | 0.132884E+10 | 0.295333E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 32061380.67 | 0.807496E+09 |
October | 0.150994E+10 | 0.145171E+10 | 0.306051E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 297141.32 | 0.169585E+10 |
November | 0.149520E+10 | 0.152662E+10 | 0.299318E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.150264E+10 |
December | 0.145684E+10 | 0.152423E+10 | 0.300927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.278539E+10 |
Annual Sum or Average | 0.181198E+11 | 0.170259E+11 | 0.363660E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.334944E+09 | 0.173864E+11 |
Minimum of Months | 0.136988E+10 | 0.128372E+10 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.517484E+09 |
Maximum of Months | 0.163688E+10 | 0.154219E+10 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.129099E+09 | 0.278539E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.100692E+10 | 0.197183E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.828283E+09 |
February | 0.882782E+09 | 0.868741E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.132933E+10 |
March | 0.105485E+10 | 0.973070E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.144478E+10 |
April | 0.936002E+09 | 0.844318E+09 | 0.190406E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.149867E+10 |
May | 0.101394E+10 | 0.884679E+09 | 0.201175E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3257323.51 | 0.822351E+09 |
June | 0.101113E+10 | 0.868550E+09 | 0.197570E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 68579131.50 | 0.379789E+09 |
July | 0.938820E+09 | 0.821386E+09 | 0.193968E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 87094507.13 | 0.372514E+09 |
August | 0.105485E+10 | 0.928265E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 47569267.60 | 0.379458E+09 |
September | 0.936002E+09 | 0.854632E+09 | 0.190319E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 24890062.05 | 0.531358E+09 |
October | 0.973041E+09 | 0.939864E+09 | 0.197226E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 538990.99 | 0.108486E+10 |
November | 0.963541E+09 | 0.990858E+09 | 0.192888E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.948613E+09 |
December | 0.938820E+09 | 0.992789E+09 | 0.193924E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.177832E+10 |
Annual Sum or Average | 0.116768E+11 | 0.109741E+11 | 0.234351E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.231929E+09 | 0.113983E+11 |
Minimum of Months | 0.882782E+09 | 0.821386E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.372514E+09 |
Maximum of Months | 0.105485E+10 | 0.100692E+10 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 87094507.13 | 0.177832E+10 |
Report: SpaceGainsMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.174411E+09 | 0.553024E+09 | 0.521915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.158233E+09 | 0.501634E+09 | 0.942813E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.189074E+09 | 0.596080E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.167772E+09 | 0.532421E+09 | 0.201821E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.181743E+09 | 0.574552E+09 | 0.522616E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.181238E+09 | 0.571774E+09 | 0.101086E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.168277E+09 | 0.535199E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.189074E+09 | 0.596080E+09 | 0.208555E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.167772E+09 | 0.532421E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.174411E+09 | 0.553024E+09 | 0.104453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.172708E+09 | 0.546542E+09 | 0.151524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.168277E+09 | 0.535199E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.209299E+10 | 0.662795E+10 | 0.153881E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.158233E+09 | 0.501634E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.189074E+09 | 0.596080E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.174411E+09 | 0.553024E+09 | 0.521915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.158233E+09 | 0.501634E+09 | 0.942813E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.189074E+09 | 0.596080E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.167772E+09 | 0.532421E+09 | 0.201821E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.181743E+09 | 0.574552E+09 | 0.522616E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.181238E+09 | 0.571774E+09 | 0.101086E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.168277E+09 | 0.535199E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.189074E+09 | 0.596080E+09 | 0.208555E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.167772E+09 | 0.532421E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.174411E+09 | 0.553024E+09 | 0.104453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.172708E+09 | 0.546542E+09 | 0.151524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.168277E+09 | 0.535199E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.209299E+10 | 0.662795E+10 | 0.153881E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.158233E+09 | 0.501634E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.189074E+09 | 0.596080E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.174411E+09 | 0.553024E+09 | 0.521915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.158233E+09 | 0.501634E+09 | 0.942813E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.189074E+09 | 0.596080E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.167772E+09 | 0.532421E+09 | 0.201821E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.181743E+09 | 0.574552E+09 | 0.522616E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.181238E+09 | 0.571774E+09 | 0.101086E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.168277E+09 | 0.535199E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.189074E+09 | 0.596080E+09 | 0.208555E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.167772E+09 | 0.532421E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.174411E+09 | 0.553024E+09 | 0.104453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.172708E+09 | 0.546542E+09 | 0.151524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.168277E+09 | 0.535199E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.209299E+10 | 0.662795E+10 | 0.153881E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.158233E+09 | 0.501634E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.189074E+09 | 0.596080E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.377547E+10 | 0.618367E+10 | 0.254202E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.342526E+10 | 0.560905E+10 | 0.459203E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.409289E+10 | 0.666512E+10 | 0.762947E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.363176E+10 | 0.595330E+10 | 0.982982E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.393418E+10 | 0.642439E+10 | 0.254544E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.392325E+10 | 0.639333E+10 | 0.492345E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.364269E+10 | 0.598436E+10 | 0.762947E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.409289E+10 | 0.666512E+10 | 0.101578E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.363176E+10 | 0.595330E+10 | 0.246344E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.377547E+10 | 0.618367E+10 | 0.508746E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.373861E+10 | 0.611120E+10 | 0.738006E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.364269E+10 | 0.598436E+10 | 0.101681E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.453069E+11 | 0.741109E+11 | 0.749486E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.342526E+10 | 0.560905E+10 | 0.246344E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.409289E+10 | 0.666512E+10 | 0.101681E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.106571E+10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.165044E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.180571E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.193532E+10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2551068.29 | 0.955846E+09 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67493824.29 | 0.401299E+09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 90958637.11 | 0.396426E+09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43515864.04 | 0.397362E+09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23494070.45 | 0.616148E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 203634.06 | 0.137340E+10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.119951E+10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.226801E+10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.228217E+09 | 0.140652E+11 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.396426E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 90958637.11 | 0.226801E+10 |
Report: SpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.181635E+10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.280767E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.306913E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.327392E+10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4699291.06 | 0.166373E+10 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.124485E+09 | 0.703339E+09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.168315E+09 | 0.697238E+09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 79972798.74 | 0.704232E+09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44573150.75 | 0.107238E+10 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 410533.74 | 0.236684E+10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.204521E+10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.377149E+10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.422456E+09 | 0.239915E+11 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.697238E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.168315E+09 | 0.377149E+10 |
Report: SpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.184969E+10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.295328E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.323367E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.341051E+10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3128220.75 | 0.183640E+10 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.111931E+09 | 0.795994E+09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.145834E+09 | 0.793619E+09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 70192275.67 | 0.799584E+09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33786905.94 | 0.116526E+10 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 102569.58 | 0.245931E+10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.212324E+10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.393172E+10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.364975E+09 | 0.253523E+11 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.793619E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.145834E+09 | 0.393172E+10 |
Report: PeakSpaceGainsMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 17832.21 | 02-JAN-10:09 | 22950.34 | 02-JAN-08:09 | 13457.54 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 17832.21 | 01-FEB-10:09 | 22950.34 | 01-FEB-08:09 | 13457.54 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 17832.21 | 01-MAR-10:09 | 22950.34 | 01-MAR-08:09 | 13457.54 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 17832.21 | 03-APR-09:09 | 22950.34 | 03-APR-07:10 | 13457.54 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 17832.21 | 01-MAY-09:09 | 22950.34 | 01-MAY-07:10 | 13457.54 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 17832.21 | 01-JUN-09:09 | 22950.34 | 01-JUN-07:10 | 13457.54 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 17832.21 | 03-JUL-09:09 | 22950.34 | 03-JUL-07:10 | 13457.54 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 17832.21 | 01-AUG-09:09 | 22950.34 | 01-AUG-07:10 | 13457.54 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 17832.21 | 01-SEP-09:09 | 22950.34 | 01-SEP-07:10 | 13457.54 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 17832.21 | 02-OCT-09:09 | 22950.34 | 02-OCT-07:10 | 13457.54 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 17832.21 | 01-NOV-09:09 | 22950.34 | 01-NOV-07:10 | 13457.54 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 17832.21 | 01-DEC-10:09 | 22950.34 | 01-DEC-08:09 | 13457.54 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 17832.21 | 22950.34 | 13457.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 17832.21 | 22950.34 | 13457.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 16014.58 | 02-JAN-10:09 | 20611.01 | 02-JAN-08:09 | 17206.63 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 16014.58 | 01-FEB-10:09 | 20611.01 | 01-FEB-08:09 | 17206.63 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 16014.58 | 01-MAR-10:09 | 20611.01 | 01-MAR-08:09 | 17206.63 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 16014.58 | 03-APR-09:09 | 20611.01 | 03-APR-07:10 | 17206.63 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 16014.58 | 01-MAY-09:09 | 20611.01 | 01-MAY-07:10 | 17206.63 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 16014.58 | 01-JUN-09:09 | 20611.01 | 01-JUN-07:10 | 17206.63 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 16014.58 | 03-JUL-09:09 | 20611.01 | 03-JUL-07:10 | 17206.63 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 16014.58 | 01-AUG-09:09 | 20611.01 | 01-AUG-07:10 | 17206.63 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 16014.58 | 01-SEP-09:09 | 20611.01 | 01-SEP-07:10 | 17206.63 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 16014.58 | 02-OCT-09:09 | 20611.01 | 02-OCT-07:10 | 17206.63 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 16014.58 | 01-NOV-09:09 | 20611.01 | 01-NOV-07:10 | 17206.63 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 16014.58 | 01-DEC-10:09 | 20611.01 | 01-DEC-08:09 | 17206.63 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 16014.58 | 20611.01 | 17206.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 16014.58 | 20611.01 | 17206.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 16014.58 | 02-JAN-10:09 | 20611.01 | 02-JAN-08:09 | 17206.56 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 16014.58 | 01-FEB-10:09 | 20611.01 | 01-FEB-08:09 | 17206.56 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 16014.58 | 01-MAR-10:09 | 20611.01 | 01-MAR-08:09 | 17206.56 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 16014.58 | 03-APR-09:09 | 20611.01 | 03-APR-07:10 | 17206.56 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 16014.58 | 01-MAY-09:09 | 20611.01 | 01-MAY-07:10 | 17206.56 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 16014.58 | 01-JUN-09:09 | 20611.01 | 01-JUN-07:10 | 17206.56 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 16014.58 | 03-JUL-09:09 | 20611.01 | 03-JUL-07:10 | 17206.56 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 16014.58 | 01-AUG-09:09 | 20611.01 | 01-AUG-07:10 | 17206.56 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 16014.58 | 01-SEP-09:09 | 20611.01 | 01-SEP-07:10 | 17206.56 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 16014.58 | 02-OCT-09:09 | 20611.01 | 02-OCT-07:10 | 17206.56 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 16014.58 | 01-NOV-09:09 | 20611.01 | 01-NOV-07:10 | 17206.56 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 16014.58 | 01-DEC-10:09 | 20611.01 | 01-DEC-08:09 | 17206.56 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 16014.58 | 20611.01 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 16014.58 | 20611.01 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 16014.58 | 02-JAN-10:09 | 20611.01 | 02-JAN-08:09 | 17206.56 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 16014.58 | 01-FEB-10:09 | 20611.01 | 01-FEB-08:09 | 17206.56 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 16014.58 | 01-MAR-10:09 | 20611.01 | 01-MAR-08:09 | 17206.56 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 16014.58 | 03-APR-09:09 | 20611.01 | 03-APR-07:10 | 17206.56 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 16014.58 | 01-MAY-09:09 | 20611.01 | 01-MAY-07:10 | 17206.56 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 16014.58 | 01-JUN-09:09 | 20611.01 | 01-JUN-07:10 | 17206.56 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 16014.58 | 03-JUL-09:09 | 20611.01 | 03-JUL-07:10 | 17206.56 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 16014.58 | 01-AUG-09:09 | 20611.01 | 01-AUG-07:10 | 17206.56 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 16014.58 | 01-SEP-09:09 | 20611.01 | 01-SEP-07:10 | 17206.56 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 16014.58 | 02-OCT-09:09 | 20611.01 | 02-OCT-07:10 | 17206.56 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 16014.58 | 01-NOV-09:09 | 20611.01 | 01-NOV-07:10 | 17206.56 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 16014.58 | 01-DEC-10:09 | 20611.01 | 01-DEC-08:09 | 17206.56 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 16014.58 | 20611.01 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 16014.58 | 20611.01 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.79 | 02-JAN-10:09 | 2587.92 | 02-JAN-16:19 | 2160.55 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 937.56 | 13-JAN-05:00 |
February | 2010.79 | 01-FEB-10:09 | 2587.92 | 06-FEB-16:30 | 2160.55 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1160.76 | 05-FEB-23:00 |
March | 2010.79 | 01-MAR-10:09 | 2255.20 | 21-MAR-07:10 | 2160.55 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 | 14-MAR-13:00 | 2405.48 | 19-MAR-06:51 |
April | 2010.79 | 03-APR-09:09 | 1803.00 | 03-APR-07:10 | 2160.55 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 1713.20 | 16-APR-14:53 |
May | 2010.79 | 01-MAY-09:09 | 1231.33 | 01-MAY-07:10 | 2160.55 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 42.97 | 17-MAY-14:50 | 962.29 | 03-MAY-03:00 |
June | 2010.79 | 01-JUN-09:09 | 1231.33 | 01-JUN-07:10 | 2160.55 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 241.02 | 25-JUN-17:44 | 560.00 | 08-JUN-23:00 |
July | 2010.79 | 03-JUL-09:09 | 1231.33 | 03-JUL-07:10 | 2160.55 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 368.20 | 16-JUL-11:52 | 536.38 | 03-JUL-04:00 |
August | 2010.79 | 01-AUG-09:09 | 1350.81 | 07-AUG-15:30 | 2160.55 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 134.54 | 02-AUG-16:00 | 609.27 | 27-AUG-18:10 |
September | 2010.79 | 01-SEP-09:09 | 1350.81 | 08-SEP-15:00 | 2160.55 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 157.17 | 10-SEP-14:50 | 606.60 | 22-SEP-02:00 |
October | 2010.79 | 02-OCT-09:09 | 2255.20 | 12-OCT-07:10 | 2160.55 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 19.87 | 11-OCT-14:00 | 1448.00 | 29-OCT-09:00 |
November | 2010.79 | 01-NOV-09:09 | 2587.92 | 06-NOV-16:30 | 2160.55 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 1401.20 | 01-NOV-04:00 |
December | 2010.79 | 01-DEC-10:09 | 2587.92 | 01-DEC-16:10 | 2160.55 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 2028.60 | 21-DEC-22:52 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.79 | 1231.33 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 536.38 | |||||
Maximum of Months | 2010.79 | 2587.92 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 368.20 | 2405.48 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 1667.75 | 02-JAN-16:19 | 1392.34 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 648.22 | 08-JAN-09:00 |
February | 1295.83 | 01-FEB-10:09 | 1667.75 | 06-FEB-16:30 | 1392.34 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 760.62 | 05-FEB-23:00 |
March | 1295.83 | 01-MAR-10:09 | 1161.92 | 01-MAR-16:00 | 1392.34 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14-MAR-13:00 | 1577.14 | 19-MAR-06:51 |
April | 1295.83 | 03-APR-09:09 | 947.51 | 03-APR-07:10 | 1392.34 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 1140.02 | 16-APR-14:53 |
May | 1295.83 | 01-MAY-09:09 | 793.52 | 01-MAY-07:10 | 1392.34 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 28.65 | 17-MAY-14:50 | 632.34 | 03-MAY-03:00 |
June | 1295.83 | 01-JUN-09:09 | 793.52 | 01-JUN-07:10 | 1392.34 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 187.76 | 25-JUN-17:50 | 368.20 | 08-JUN-23:00 |
July | 1295.83 | 03-JUL-09:09 | 793.52 | 03-JUL-07:10 | 1392.34 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 265.10 | 16-JUL-12:05 | 394.63 | 02-JUL-08:50 |
August | 1295.83 | 01-AUG-09:09 | 870.51 | 07-AUG-15:20 | 1392.34 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 89.69 | 02-AUG-16:00 | 354.55 | 27-AUG-18:10 |
September | 1295.83 | 01-SEP-09:09 | 947.51 | 21-SEP-15:00 | 1392.34 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 119.75 | 10-SEP-14:50 | 399.84 | 22-SEP-02:00 |
October | 1295.83 | 02-OCT-09:09 | 1453.34 | 23-OCT-07:10 | 1392.34 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 13.25 | 11-OCT-14:00 | 957.44 | 29-OCT-09:00 |
November | 1295.83 | 01-NOV-09:09 | 1667.75 | 06-NOV-16:30 | 1392.34 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 924.48 | 01-NOV-04:03 |
December | 1295.83 | 01-DEC-10:09 | 1667.75 | 01-DEC-16:10 | 1392.34 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1330.99 | 21-DEC-22:52 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 793.52 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 354.55 | |||||
Maximum of Months | 1295.83 | 1667.75 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 265.10 | 1577.14 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.83 | 02-JAN-10:09 | 2587.98 | 02-JAN-16:40 | 2160.58 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 944.56 | 13-JAN-05:00 |
February | 2010.83 | 01-FEB-10:09 | 2587.98 | 06-FEB-16:30 | 2160.58 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1184.87 | 23-FEB-24:00 |
March | 2010.83 | 01-MAR-10:09 | 2255.25 | 21-MAR-07:10 | 2160.58 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 2311.02 | 19-MAR-06:51 |
April | 2010.83 | 03-APR-09:09 | 1803.04 | 03-APR-07:10 | 2160.58 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 1610.40 | 16-APR-14:53 |
May | 2010.83 | 01-MAY-09:09 | 1231.36 | 01-MAY-07:10 | 2160.58 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 42.97 | 17-MAY-14:50 | 941.42 | 03-MAY-03:00 |
June | 2010.83 | 01-JUN-09:09 | 1350.84 | 16-JUN-07:10 | 2160.58 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 255.08 | 25-JUN-17:50 | 556.41 | 08-JUN-23:00 |
July | 2010.83 | 03-JUL-09:09 | 1231.36 | 03-JUL-07:10 | 2160.58 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 365.89 | 16-JUL-11:52 | 527.95 | 03-JUL-04:00 |
August | 2010.83 | 01-AUG-09:09 | 1350.84 | 07-AUG-15:39 | 2160.58 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 134.54 | 02-AUG-16:00 | 644.61 | 27-AUG-18:10 |
September | 2010.83 | 01-SEP-09:09 | 1350.84 | 21-SEP-15:30 | 2160.58 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 143.90 | 10-SEP-14:44 | 597.06 | 22-SEP-02:00 |
October | 2010.83 | 02-OCT-09:09 | 2255.25 | 23-OCT-07:10 | 2160.58 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 14.11 | 11-OCT-15:00 | 1417.52 | 29-OCT-09:00 |
November | 2010.83 | 01-NOV-09:09 | 2587.98 | 06-NOV-16:49 | 2160.58 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 1374.43 | 01-NOV-04:10 |
December | 2010.83 | 01-DEC-10:09 | 2587.98 | 01-DEC-16:30 | 2160.58 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 2037.07 | 21-DEC-22:52 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.83 | 1231.36 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 527.95 | |||||
Maximum of Months | 2010.83 | 2587.98 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 365.89 | 2311.02 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 1667.75 | 02-JAN-16:40 | 1392.33 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 656.30 | 13-JAN-05:00 |
February | 1295.83 | 01-FEB-10:09 | 1667.75 | 06-FEB-16:40 | 1392.33 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 824.10 | 23-FEB-24:00 |
March | 1295.83 | 01-MAR-10:09 | 1453.34 | 21-MAR-07:10 | 1392.33 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 | 14-MAR-13:00 | 1679.45 | 19-MAR-06:51 |
April | 1295.83 | 03-APR-09:09 | 1161.92 | 03-APR-07:10 | 1392.33 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 1244.29 | 16-APR-14:53 |
May | 1295.83 | 01-MAY-09:09 | 870.51 | 19-MAY-07:10 | 1392.33 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 28.64 | 17-MAY-14:50 | 682.28 | 03-MAY-03:00 |
June | 1295.83 | 01-JUN-09:09 | 870.51 | 16-JUN-07:10 | 1392.33 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 153.87 | 25-JUN-17:44 | 442.11 | 08-JUN-23:00 |
July | 1295.83 | 03-JUL-09:09 | 870.51 | 28-JUL-07:10 | 1392.33 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 268.67 | 16-JUL-12:05 | 403.50 | 03-JUL-04:00 |
August | 1295.83 | 01-AUG-09:09 | 870.51 | 21-AUG-07:10 | 1392.33 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 89.68 | 02-AUG-15:10 | 519.27 | 27-AUG-18:10 |
September | 1295.83 | 01-SEP-09:09 | 947.51 | 22-SEP-07:10 | 1392.33 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 95.14 | 10-SEP-15:00 | 416.51 | 22-SEP-02:00 |
October | 1295.83 | 02-OCT-09:09 | 1453.34 | 12-OCT-07:10 | 1392.33 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 13.25 | 11-OCT-14:00 | 1018.88 | 29-OCT-09:00 |
November | 1295.83 | 01-NOV-09:09 | 1667.75 | 06-NOV-16:49 | 1392.33 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 987.56 | 01-NOV-04:00 |
December | 1295.83 | 01-DEC-10:09 | 1667.75 | 01-DEC-16:30 | 1392.33 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1425.63 | 21-DEC-22:52 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 870.51 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 403.50 | |||||
Maximum of Months | 1295.83 | 1667.75 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 268.67 | 1679.45 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.79 | 02-JAN-10:09 | 2587.92 | 02-JAN-16:19 | 2160.55 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 1979.39 | 13-JAN-05:06 |
February | 2010.79 | 01-FEB-10:09 | 2587.92 | 06-FEB-16:30 | 2160.55 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 2369.01 | 05-FEB-23:00 |
March | 2010.79 | 01-MAR-10:09 | 2255.20 | 21-MAR-07:10 | 2160.55 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 5275.45 | 19-MAR-06:54 |
April | 2010.79 | 03-APR-09:09 | 1803.00 | 03-APR-07:10 | 2160.55 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 3729.31 | 15-APR-04:56 |
May | 2010.79 | 01-MAY-09:09 | 1231.33 | 01-MAY-07:10 | 2160.55 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 97.47 | 17-MAY-14:50 | 1986.17 | 03-MAY-03:00 |
June | 2010.79 | 01-JUN-09:09 | 1231.33 | 01-JUN-07:10 | 2160.55 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 536.60 | 25-JUN-17:44 | 1215.11 | 08-JUN-23:00 |
July | 2010.79 | 03-JUL-09:09 | 1231.33 | 03-JUL-07:10 | 2160.55 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 880.55 | 16-JUL-11:53 | 1173.90 | 03-JUL-03:00 |
August | 2010.79 | 01-AUG-09:09 | 1350.81 | 07-AUG-15:39 | 2160.55 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 310.60 | 02-AUG-16:00 | 1431.28 | 27-AUG-17:55 |
September | 2010.79 | 01-SEP-09:09 | 1350.81 | 08-SEP-15:00 | 2160.55 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 350.43 | 10-SEP-14:40 | 1311.84 | 22-SEP-02:00 |
October | 2010.79 | 02-OCT-09:09 | 2255.20 | 12-OCT-07:10 | 2160.55 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 44.92 | 11-OCT-14:00 | 2840.00 | 29-OCT-09:00 |
November | 2010.79 | 01-NOV-09:09 | 2587.92 | 06-NOV-16:30 | 2160.55 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 3238.77 | 01-NOV-04:07 |
December | 2010.79 | 01-DEC-10:09 | 2587.92 | 01-DEC-16:10 | 2160.55 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 6.30 | 02-DEC-15:00 | 4401.93 | 21-DEC-22:52 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.79 | 1231.33 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1173.90 | |||||
Maximum of Months | 2010.79 | 2587.92 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 880.55 | 5275.45 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1239.33 | 02-JAN-08:09 | 1667.75 | 02-JAN-16:19 | 1392.34 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 1328.09 | 13-JAN-05:04 |
February | 1239.33 | 01-FEB-08:09 | 1667.75 | 06-FEB-16:30 | 1392.34 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1607.02 | 23-FEB-24:00 |
March | 1239.33 | 01-MAR-08:09 | 1161.92 | 01-MAR-16:00 | 1392.34 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 3516.99 | 19-MAR-06:57 |
April | 1239.33 | 03-APR-07:10 | 947.51 | 03-APR-07:10 | 1392.34 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 2486.22 | 15-APR-04:56 |
May | 1239.33 | 01-MAY-07:10 | 793.52 | 01-MAY-07:10 | 1392.34 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 64.98 | 17-MAY-14:50 | 1319.80 | 03-MAY-03:00 |
June | 1239.33 | 01-JUN-07:10 | 793.52 | 01-JUN-07:10 | 1392.34 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 431.58 | 25-JUN-17:50 | 812.15 | 08-JUN-23:00 |
July | 1239.33 | 03-JUL-07:10 | 793.52 | 03-JUL-07:10 | 1392.34 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 587.03 | 16-JUL-11:55 | 947.54 | 02-JUL-08:40 |
August | 1239.33 | 01-AUG-07:10 | 870.51 | 07-AUG-15:30 | 1392.34 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 207.07 | 02-AUG-16:00 | 976.53 | 27-AUG-17:55 |
September | 1239.33 | 01-SEP-07:10 | 870.51 | 08-SEP-15:50 | 1392.34 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 277.99 | 10-SEP-14:40 | 870.59 | 22-SEP-02:00 |
October | 1239.33 | 02-OCT-07:10 | 1453.34 | 23-OCT-07:10 | 1392.34 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 29.94 | 11-OCT-14:00 | 1918.25 | 29-OCT-09:00 |
November | 1239.33 | 01-NOV-07:10 | 1667.75 | 06-NOV-16:30 | 1392.34 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 2159.24 | 01-NOV-04:06 |
December | 1239.33 | 01-DEC-08:09 | 1667.75 | 01-DEC-16:10 | 1392.34 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5.29 | 02-DEC-15:00 | 2916.26 | 21-DEC-22:52 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1239.33 | 793.52 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 812.15 | |||||
Maximum of Months | 1239.33 | 1667.75 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 587.03 | 3516.99 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.83 | 02-JAN-10:09 | 2587.98 | 02-JAN-16:40 | 2160.58 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 2052.67 | 13-JAN-05:00 |
February | 2010.83 | 01-FEB-10:09 | 2587.98 | 06-FEB-16:30 | 2160.58 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 2670.08 | 19-FEB-16:55 |
March | 2010.83 | 01-MAR-10:09 | 2255.25 | 21-MAR-07:10 | 2160.58 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 5275.51 | 19-MAR-06:54 |
April | 2010.83 | 03-APR-09:09 | 1803.04 | 03-APR-07:10 | 2160.58 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 3729.32 | 15-APR-04:56 |
May | 2010.83 | 01-MAY-09:09 | 1231.36 | 01-MAY-07:10 | 2160.58 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 97.47 | 17-MAY-14:50 | 2019.24 | 03-MAY-03:00 |
June | 2010.83 | 01-JUN-09:09 | 1231.36 | 01-JUN-07:10 | 2160.58 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 589.26 | 25-JUN-17:50 | 1210.22 | 08-JUN-23:00 |
July | 2010.83 | 03-JUL-09:09 | 1231.36 | 03-JUL-07:10 | 2160.58 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 880.55 | 16-JUL-11:53 | 1174.96 | 03-JUL-03:00 |
August | 2010.83 | 01-AUG-09:09 | 1350.84 | 07-AUG-15:50 | 2160.58 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 310.60 | 02-AUG-16:00 | 1667.16 | 27-AUG-17:55 |
September | 2010.83 | 01-SEP-09:09 | 1350.84 | 21-SEP-15:39 | 2160.58 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 327.44 | 10-SEP-15:00 | 1322.67 | 22-SEP-02:00 |
October | 2010.83 | 02-OCT-09:09 | 2255.25 | 23-OCT-07:10 | 2160.58 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 20.83 | 11-OCT-14:00 | 2985.34 | 29-OCT-09:00 |
November | 2010.83 | 01-NOV-09:09 | 2587.98 | 06-NOV-16:49 | 2160.58 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 3238.77 | 01-NOV-04:06 |
December | 2010.83 | 01-DEC-10:09 | 2587.98 | 01-DEC-16:30 | 2160.58 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 4512.13 | 21-DEC-22:52 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.83 | 1231.36 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1174.96 | |||||
Maximum of Months | 2010.83 | 2587.98 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 880.55 | 5275.51 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 1667.75 | 02-JAN-16:40 | 1392.33 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 1321.68 | 13-JAN-05:00 |
February | 1295.83 | 01-FEB-10:09 | 1667.75 | 06-FEB-16:40 | 1392.33 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1663.83 | 23-FEB-24:00 |
March | 1295.83 | 01-MAR-10:09 | 1453.34 | 21-MAR-07:10 | 1392.33 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 3517.03 | 19-MAR-06:51 |
April | 1295.83 | 03-APR-09:09 | 1161.92 | 03-APR-07:10 | 1392.33 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 2486.21 | 15-APR-04:56 |
May | 1295.83 | 01-MAY-09:09 | 870.51 | 19-MAY-07:10 | 1392.33 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 64.98 | 17-MAY-14:50 | 1386.00 | 03-MAY-03:00 |
June | 1295.83 | 01-JUN-09:09 | 870.51 | 16-JUN-07:10 | 1392.33 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 353.22 | 25-JUN-17:44 | 903.63 | 08-JUN-23:00 |
July | 1295.83 | 03-JUL-09:09 | 870.51 | 28-JUL-07:10 | 1392.33 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 615.73 | 16-JUL-12:00 | 853.85 | 03-JUL-03:00 |
August | 1295.83 | 01-AUG-09:09 | 870.51 | 21-AUG-07:10 | 1392.33 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 226.16 | 06-AUG-12:00 | 1123.38 | 27-AUG-17:55 |
September | 1295.83 | 01-SEP-09:09 | 947.51 | 22-SEP-07:10 | 1392.33 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 235.46 | 10-SEP-14:33 | 866.88 | 22-SEP-02:00 |
October | 1295.83 | 02-OCT-09:09 | 1453.34 | 12-OCT-07:10 | 1392.33 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 29.94 | 11-OCT-14:00 | 1933.91 | 29-OCT-09:00 |
November | 1295.83 | 01-NOV-09:09 | 1667.75 | 06-NOV-16:49 | 1392.33 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 2159.24 | 01-NOV-04:07 |
December | 1295.83 | 01-DEC-10:09 | 1667.75 | 01-DEC-16:30 | 1392.33 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 2977.50 | 21-DEC-22:52 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 870.51 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 853.85 | |||||
Maximum of Months | 1295.83 | 1667.75 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 615.73 | 3517.03 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.79 | 02-JAN-10:09 | 2587.92 | 02-JAN-16:19 | 2160.55 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 2469.53 | 13-JAN-05:10 |
February | 2010.79 | 01-FEB-10:09 | 2587.92 | 06-FEB-16:30 | 2160.55 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 2956.13 | 05-FEB-23:00 |
March | 2010.79 | 01-MAR-10:09 | 2255.20 | 21-MAR-07:10 | 2160.55 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 6573.13 | 19-MAR-07:00 |
April | 2010.79 | 03-APR-09:09 | 1803.00 | 03-APR-07:10 | 2160.55 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 4558.95 | 15-APR-04:51 |
May | 2010.79 | 01-MAY-09:09 | 1231.33 | 01-MAY-07:10 | 2160.55 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 116.93 | 17-MAY-14:50 | 2367.98 | 02-MAY-04:57 |
June | 2010.79 | 01-JUN-09:09 | 1231.33 | 01-JUN-07:10 | 2160.55 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 644.10 | 25-JUN-17:44 | 1471.20 | 08-JUN-23:00 |
July | 2010.79 | 03-JUL-09:09 | 1231.33 | 03-JUL-07:10 | 2160.55 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1080.32 | 16-JUL-11:52 | 1410.27 | 03-JUL-03:00 |
August | 2010.79 | 01-AUG-09:09 | 1350.81 | 07-AUG-15:39 | 2160.55 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 379.53 | 02-AUG-16:00 | 1796.13 | 27-AUG-17:55 |
September | 2010.79 | 01-SEP-09:09 | 1350.81 | 08-SEP-15:00 | 2160.55 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 409.50 | 10-SEP-14:34 | 1526.15 | 21-SEP-23:00 |
October | 2010.79 | 02-OCT-09:09 | 2255.20 | 12-OCT-07:10 | 2160.55 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 53.66 | 11-OCT-14:00 | 3358.46 | 29-OCT-19:00 |
November | 2010.79 | 01-NOV-09:09 | 2587.92 | 06-NOV-16:30 | 2160.55 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.78 | 05-NOV-13:11 | 3792.49 | 01-NOV-04:00 |
December | 2010.79 | 01-DEC-10:09 | 2587.92 | 01-DEC-16:10 | 2160.55 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 11.67 | 02-DEC-15:00 | 5401.28 | 21-DEC-22:52 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.79 | 1231.33 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1410.27 | |||||
Maximum of Months | 2010.79 | 2587.92 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 1080.32 | 6573.13 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 1667.75 | 02-JAN-16:19 | 1392.34 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 1646.36 | 13-JAN-05:08 |
February | 1295.83 | 01-FEB-10:09 | 1667.75 | 06-FEB-16:30 | 1392.34 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1970.66 | 05-FEB-23:00 |
March | 1295.83 | 01-MAR-10:09 | 1161.92 | 01-MAR-16:00 | 1392.34 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 4381.94 | 19-MAR-06:56 |
April | 1295.83 | 03-APR-09:09 | 947.51 | 03-APR-07:10 | 1392.34 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 3039.10 | 15-APR-04:51 |
May | 1295.83 | 01-MAY-09:09 | 793.52 | 01-MAY-07:10 | 1392.34 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 77.95 | 17-MAY-14:50 | 1595.65 | 02-MAY-04:55 |
June | 1295.83 | 01-JUN-09:09 | 793.52 | 01-JUN-07:10 | 1392.34 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 540.91 | 25-JUN-17:50 | 985.61 | 08-JUN-23:00 |
July | 1295.83 | 03-JUL-09:09 | 793.52 | 03-JUL-07:10 | 1392.34 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 721.45 | 16-JUL-11:52 | 1177.55 | 02-JUL-08:50 |
August | 1295.83 | 01-AUG-09:09 | 870.51 | 07-AUG-15:30 | 1392.34 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 253.02 | 02-AUG-16:00 | 1227.05 | 27-AUG-17:55 |
September | 1295.83 | 01-SEP-09:09 | 870.51 | 08-SEP-15:50 | 1392.34 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 349.71 | 10-SEP-14:40 | 1019.61 | 21-SEP-23:00 |
October | 1295.83 | 02-OCT-09:09 | 1453.34 | 23-OCT-07:10 | 1392.34 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 35.78 | 11-OCT-14:00 | 2238.84 | 29-OCT-19:00 |
November | 1295.83 | 01-NOV-09:09 | 1667.75 | 06-NOV-16:30 | 1392.34 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 2594.35 | 01-NOV-04:17 |
December | 1295.83 | 01-DEC-10:09 | 1667.75 | 01-DEC-16:10 | 1392.34 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5.67 | 02-DEC-15:00 | 3596.67 | 21-DEC-22:52 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 793.52 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 985.61 | |||||
Maximum of Months | 1295.83 | 1667.75 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 721.45 | 4381.94 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.83 | 02-JAN-10:09 | 2587.98 | 02-JAN-16:40 | 2160.58 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 2469.55 | 13-JAN-05:09 |
February | 2010.83 | 01-FEB-10:09 | 2587.98 | 06-FEB-16:30 | 2160.58 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 3111.20 | 19-FEB-16:55 |
March | 2010.83 | 01-MAR-10:09 | 2255.25 | 21-MAR-07:10 | 2160.58 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 6573.10 | 19-MAR-07:00 |
April | 2010.83 | 03-APR-09:09 | 1803.04 | 03-APR-07:10 | 2160.58 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 4563.70 | 15-APR-04:51 |
May | 2010.83 | 01-MAY-09:09 | 1231.36 | 01-MAY-07:10 | 2160.58 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 116.93 | 17-MAY-14:50 | 2368.06 | 02-MAY-04:57 |
June | 2010.83 | 01-JUN-09:09 | 1231.36 | 01-JUN-07:10 | 2160.58 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 741.71 | 25-JUN-17:45 | 1463.41 | 08-JUN-23:00 |
July | 2010.83 | 03-JUL-09:09 | 1231.36 | 03-JUL-07:10 | 2160.58 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1081.33 | 16-JUL-11:52 | 1410.60 | 03-JUL-03:00 |
August | 2010.83 | 01-AUG-09:09 | 1350.84 | 07-AUG-15:50 | 2160.58 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 379.53 | 02-AUG-16:00 | 2076.29 | 27-AUG-17:55 |
September | 2010.83 | 01-SEP-09:09 | 1350.84 | 21-SEP-15:39 | 2160.58 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 397.28 | 10-SEP-15:00 | 1547.86 | 21-SEP-23:00 |
October | 2010.83 | 02-OCT-09:09 | 2255.25 | 23-OCT-07:10 | 2160.58 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 30.83 | 11-OCT-14:00 | 3358.28 | 29-OCT-19:00 |
November | 2010.83 | 01-NOV-09:09 | 2587.98 | 06-NOV-16:49 | 2160.58 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 3891.51 | 01-NOV-04:20 |
December | 2010.83 | 01-DEC-10:09 | 2587.98 | 01-DEC-16:30 | 2160.58 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 5423.39 | 21-DEC-22:52 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.83 | 1231.36 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1410.60 | |||||
Maximum of Months | 2010.83 | 2587.98 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 1081.33 | 6573.10 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 1667.75 | 02-JAN-16:40 | 1392.33 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 1646.36 | 13-JAN-05:05 |
February | 1295.83 | 01-FEB-10:09 | 1667.75 | 06-FEB-16:40 | 1392.33 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1970.93 | 05-FEB-23:00 |
March | 1295.83 | 01-MAR-10:09 | 1453.34 | 21-MAR-07:10 | 1392.33 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 4382.05 | 19-MAR-06:59 |
April | 1295.83 | 03-APR-09:09 | 1161.92 | 03-APR-07:10 | 1392.33 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 3043.83 | 15-APR-04:51 |
May | 1295.83 | 01-MAY-09:09 | 870.51 | 19-MAY-07:10 | 1392.33 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 77.95 | 17-MAY-14:50 | 1588.70 | 03-MAY-03:00 |
June | 1295.83 | 01-JUN-09:09 | 870.51 | 16-JUN-07:10 | 1392.33 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 430.89 | 25-JUN-17:44 | 1098.84 | 08-JUN-23:00 |
July | 1295.83 | 03-JUL-09:09 | 870.51 | 28-JUL-07:10 | 1392.33 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 782.88 | 16-JUL-11:52 | 1026.14 | 03-JUL-03:00 |
August | 1295.83 | 01-AUG-09:09 | 870.51 | 21-AUG-07:10 | 1392.33 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 296.51 | 06-AUG-12:00 | 1394.44 | 27-AUG-17:55 |
September | 1295.83 | 01-SEP-09:09 | 947.51 | 22-SEP-07:10 | 1392.33 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 288.51 | 10-SEP-14:33 | 1017.68 | 21-SEP-23:00 |
October | 1295.83 | 02-OCT-09:09 | 1453.34 | 12-OCT-07:10 | 1392.33 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 35.78 | 11-OCT-14:00 | 2238.98 | 29-OCT-19:00 |
November | 1295.83 | 01-NOV-09:09 | 1667.75 | 06-NOV-16:49 | 1392.33 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 2594.33 | 01-NOV-04:18 |
December | 1295.83 | 01-DEC-10:09 | 1667.75 | 01-DEC-16:30 | 1392.33 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 3613.60 | 21-DEC-22:52 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 870.51 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1017.68 | |||||
Maximum of Months | 1295.83 | 1667.75 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 782.88 | 4382.05 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 232.27 | 02-JAN-10:09 | 578.72 | 02-JAN-08:09 | 1948.61 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 232.27 | 01-FEB-10:09 | 578.72 | 01-FEB-08:09 | 3897.21 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 232.27 | 01-MAR-10:09 | 578.72 | 01-MAR-08:09 | 7794.42 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 232.27 | 03-APR-09:09 | 578.72 | 03-APR-07:10 | 7794.42 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 232.27 | 01-MAY-09:09 | 578.72 | 01-MAY-07:10 | 3897.21 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 232.27 | 01-JUN-09:09 | 578.72 | 01-JUN-07:10 | 5845.82 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 232.27 | 03-JUL-09:09 | 578.72 | 03-JUL-07:10 | 7794.42 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 232.27 | 01-AUG-09:09 | 578.72 | 01-AUG-07:10 | 7794.42 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 232.27 | 01-SEP-09:09 | 578.72 | 01-SEP-07:10 | 3897.21 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 232.27 | 02-OCT-09:09 | 578.72 | 02-OCT-07:10 | 5845.82 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 232.27 | 01-NOV-09:09 | 578.72 | 01-NOV-07:10 | 5845.82 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 232.27 | 01-DEC-10:09 | 578.72 | 01-DEC-08:09 | 7794.42 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 232.27 | 578.72 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 232.27 | 578.72 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 232.27 | 02-JAN-10:09 | 578.72 | 02-JAN-08:09 | 1948.61 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 232.27 | 01-FEB-10:09 | 578.72 | 01-FEB-08:09 | 3897.21 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 232.27 | 01-MAR-10:09 | 578.72 | 01-MAR-08:09 | 7794.42 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 232.27 | 03-APR-09:09 | 578.72 | 03-APR-07:10 | 7794.42 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 232.27 | 01-MAY-09:09 | 578.72 | 01-MAY-07:10 | 3897.21 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 232.27 | 01-JUN-09:09 | 578.72 | 01-JUN-07:10 | 5845.82 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 232.27 | 03-JUL-09:09 | 578.72 | 03-JUL-07:10 | 7794.42 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 232.27 | 01-AUG-09:09 | 578.72 | 01-AUG-07:10 | 7794.42 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 232.27 | 01-SEP-09:09 | 578.72 | 01-SEP-07:10 | 3897.21 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 232.27 | 02-OCT-09:09 | 578.72 | 02-OCT-07:10 | 5845.82 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 232.27 | 01-NOV-09:09 | 578.72 | 01-NOV-07:10 | 5845.82 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 232.27 | 01-DEC-10:09 | 578.72 | 01-DEC-08:09 | 7794.42 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 232.27 | 578.72 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 232.27 | 578.72 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 232.27 | 02-JAN-10:09 | 578.72 | 02-JAN-08:09 | 1948.61 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 232.27 | 01-FEB-10:09 | 578.72 | 01-FEB-08:09 | 3897.21 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 232.27 | 01-MAR-10:09 | 578.72 | 01-MAR-08:09 | 7794.42 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 232.27 | 03-APR-09:09 | 578.72 | 03-APR-07:10 | 7794.42 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 232.27 | 01-MAY-09:09 | 578.72 | 01-MAY-07:10 | 3897.21 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 232.27 | 01-JUN-09:09 | 578.72 | 01-JUN-07:10 | 5845.82 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 232.27 | 03-JUL-09:09 | 578.72 | 03-JUL-07:10 | 7794.42 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 232.27 | 01-AUG-09:09 | 578.72 | 01-AUG-07:10 | 7794.42 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 232.27 | 01-SEP-09:09 | 578.72 | 01-SEP-07:10 | 3897.21 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 232.27 | 02-OCT-09:09 | 578.72 | 02-OCT-07:10 | 5845.82 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 232.27 | 01-NOV-09:09 | 578.72 | 01-NOV-07:10 | 5845.82 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 232.27 | 01-DEC-10:09 | 578.72 | 01-DEC-08:09 | 7794.42 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 232.27 | 578.72 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 232.27 | 578.72 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 5027.92 | 02-JAN-10:09 | 6471.01 | 02-JAN-08:09 | 94908.13 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 5027.92 | 01-FEB-10:09 | 6471.01 | 01-FEB-08:09 | 189816.26 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 5027.92 | 01-MAR-10:09 | 6471.01 | 01-MAR-08:09 | 379632.52 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 5027.92 | 03-APR-09:09 | 6471.01 | 03-APR-07:10 | 379632.52 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 5027.92 | 01-MAY-09:09 | 6471.01 | 01-MAY-07:10 | 189816.26 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5027.92 | 01-JUN-09:09 | 6471.01 | 01-JUN-07:10 | 284724.39 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 5027.92 | 03-JUL-09:09 | 6471.01 | 03-JUL-07:10 | 379632.52 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 5027.92 | 01-AUG-09:09 | 6471.01 | 01-AUG-07:10 | 379632.52 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 5027.92 | 01-SEP-09:09 | 6471.01 | 01-SEP-07:10 | 189816.26 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 5027.92 | 02-OCT-09:09 | 6471.01 | 02-OCT-07:10 | 284724.39 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5027.92 | 01-NOV-09:09 | 6471.01 | 01-NOV-07:10 | 284724.39 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 5027.92 | 01-DEC-10:09 | 6471.01 | 01-DEC-08:09 | 379632.52 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 5027.92 | 6471.01 | 94908.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 5027.92 | 6471.01 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 2125.93 | 13-JAN-05:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 2592.30 | 05-FEB-23:00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 5413.72 | 19-MAR-06:51 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 3626.90 | 16-APR-14:53 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 69.25 | 17-MAY-14:40 | 2121.02 | 03-MAY-03:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 504.55 | 25-JUN-18:00 | 1156.47 | 08-JUN-23:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 807.08 | 16-JUL-11:52 | 1119.74 | 03-JUL-04:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 248.36 | 06-AUG-12:00 | 1254.82 | 27-AUG-17:55 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 312.99 | 10-SEP-15:00 | 1336.59 | 22-SEP-02:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.08 | 11-OCT-14:00 | 3163.95 | 29-OCT-09:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 3132.33 | 01-NOV-04:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 4428.55 | 21-DEC-22:52 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1119.74 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 807.08 | 5413.72 |
Report: PeakSpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 3692.52 | 13-JAN-05:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 4329.54 | 23-FEB-24:00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 9147.52 | 19-MAR-06:51 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 6218.72 | 15-APR-04:59 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 124.41 | 17-MAY-14:40 | 3633.28 | 03-MAY-03:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 948.73 | 25-JUN-18:00 | 2029.35 | 08-JUN-23:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1471.53 | 16-JUL-12:00 | 1949.93 | 03-JUL-03:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 475.13 | 06-AUG-12:00 | 2248.33 | 27-AUG-17:55 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 588.29 | 10-SEP-15:00 | 2370.06 | 22-SEP-02:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 49.47 | 11-OCT-14:00 | 5348.52 | 29-OCT-09:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 5211.96 | 01-NOV-04:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 7671.16 | 21-DEC-22:52 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1949.93 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1471.53 | 9147.52 |
Report: PeakSpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 3611.12 | 13-JAN-05:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 4521.03 | 23-FEB-24:00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 9320.46 | 19-MAR-07:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 6436.92 | 15-APR-04:51 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 109.86 | 17-MAY-13:00 | 3610.42 | 03-MAY-03:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 768.83 | 25-JUN-18:00 | 2225.78 | 08-JUN-23:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1454.02 | 16-JUL-11:55 | 2116.17 | 03-JUL-03:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 447.27 | 02-AUG-16:00 | 2870.86 | 27-AUG-17:55 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 454.26 | 10-SEP-15:00 | 2410.13 | 21-SEP-23:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.37 | 11-OCT-14:00 | 5246.74 | 29-OCT-09:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 5253.21 | 01-NOV-04:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 8290.16 | 21-DEC-22:52 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2116.17 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1454.02 | 9320.46 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 118053.37 | 02-JAN-04:01 | 0.00 | 8924.46 | 94202.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 117226.81 | 27-FEB-05:11 | 0.00 | 20401.06 | 107660.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 116994.15 | 27-MAR-04:11 | 0.00 | 25501.32 | 134575.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 116729.88 | 10-APR-04:11 | 0.00 | 25501.32 | 134575.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 118772.62 | 01-MAY-04:11 | 0.00 | 25501.32 | 134575.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 116641.22 | 05-JUN-04:12 | 0.00 | 15300.79 | 80745.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 117752.36 | 03-JUL-04:12 | 0.00 | 15300.79 | 80745.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 114283.03 | 19-AUG-04:11 | 0.00 | 8924.46 | 94202.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 120319.74 | 18-SEP-04:11 | 0.00 | 17850.93 | 94202.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 120724.79 | 02-OCT-04:11 | 0.00 | 17850.93 | 94202.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 120836.92 | 12-NOV-11:30 | 8078.51 | 11474.31 | 121117.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 117753.42 | 04-DEC-04:22 | 0.00 | 7649.54 | 80745.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 114283.03 | 0.00 | 7649.54 | 80745.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 120836.92 | 8078.51 | 25501.32 | 134575.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 89487.60 | 23-JAN-05:11 | 0.00 | 22901.98 | 59376.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 92034.42 | 27-FEB-05:11 | 0.00 | 18321.59 | 47501.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 94563.63 | 13-MAR-04:12 | 0.00 | 11450.99 | 29688.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 97384.90 | 10-APR-04:11 | 0.00 | 22901.98 | 59376.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 94992.19 | 30-MAY-04:12 | 0.00 | 11450.99 | 29688.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 99364.41 | 14-JUN-04:13 | 0.00 | 16031.39 | 41563.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 98679.11 | 11-JUL-04:13 | 0.00 | 16031.39 | 41563.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 96925.33 | 28-AUG-04:13 | 0.00 | 13741.19 | 35625.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 98540.66 | 11-SEP-04:13 | 0.00 | 13741.19 | 35625.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 99278.85 | 10-OCT-04:12 | 0.00 | 13741.19 | 35625.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 94879.70 | 06-NOV-05:11 | 0.00 | 16031.39 | 41563.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 95596.53 | 18-DEC-05:11 | 0.00 | 22901.98 | 59376.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 89487.60 | 0.00 | 11450.99 | 29688.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 99364.41 | 0.00 | 22901.98 | 59376.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 76351.16 | 27-JAN-06:02 | 8061.19 | 11450.99 | 38236.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 72479.28 | 28-FEB-06:02 | 8061.19 | 11450.99 | 38236.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 81743.41 | 14-MAR-05:02 | 8061.19 | 11450.99 | 38236.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 79096.16 | 14-APR-05:03 | 6448.95 | 9160.79 | 30589.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 83180.16 | 18-MAY-04:12 | 0.00 | 11450.99 | 29688.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 87037.95 | 28-JUN-04:12 | 0.00 | 13741.19 | 35625.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 87738.52 | 25-JUL-04:12 | 0.00 | 13741.19 | 35625.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 88835.39 | 28-AUG-04:12 | 0.00 | 13741.19 | 35625.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 87112.19 | 05-SEP-04:12 | 0.00 | 11450.99 | 29688.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 81748.57 | 02-OCT-05:02 | 8061.19 | 11450.99 | 38236.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 79803.73 | 09-NOV-06:03 | 6448.95 | 9160.79 | 30589.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 34074.85 | 15-DEC-16:20 | 15316.26 | 20611.01 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 34074.85 | 0.00 | 9160.79 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 88835.39 | 15316.26 | 20611.01 | 38236.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 36463.37 | 20-JAN-16:20 | 15316.26 | 20611.01 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 30326.50 | 23-FEB-17:00 | 15316.26 | 20611.01 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 46424.65 | 15-MAR-15:20 | 15316.26 | 20611.01 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 57619.38 | 21-APR-05:03 | 6448.95 | 9160.79 | 30589.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 77589.99 | 18-MAY-05:03 | 6448.95 | 9160.79 | 30589.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 85252.86 | 26-JUN-04:12 | 0.00 | 13741.19 | 35625.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 88012.71 | 24-JUL-04:12 | 0.00 | 11450.99 | 29688.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 85959.63 | 21-AUG-04:12 | 0.00 | 11450.99 | 29688.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 85350.99 | 11-SEP-04:12 | 0.00 | 13741.19 | 35625.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 46572.65 | 11-OCT-15:20 | 15316.26 | 20611.01 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 37791.59 | 08-NOV-16:20 | 15316.26 | 20611.01 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 27027.49 | 14-DEC-16:20 | 15316.26 | 20611.01 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 27027.49 | 0.00 | 9160.79 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 88012.71 | 15316.26 | 20611.01 | 35625.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3824.77 | 20-JAN-14:50 | 2010.79 | 1350.81 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.68 |
February | 4427.79 | 27-FEB-15:30 | 1923.11 | 1231.33 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 149.36 |
March | 7284.14 | 14-MAR-13:40 | 2010.79 | 1231.33 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.97 |
April | 8119.56 | 20-APR-13:30 | 2010.79 | 1231.33 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.50 |
May | 9772.43 | 17-MAY-13:30 | 2010.79 | 1231.33 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 34.84 | 0.00 |
June | 17975.55 | 25-JUN-17:41 | 0.00 | 547.22 | 4473.37 | 0.00 | 0.00 | 0.00 | 0.00 | 217.42 | 0.00 |
July | 18373.21 | 16-JUL-13:22 | 607.30 | 410.41 | 4321.10 | 0.00 | 0.00 | 0.00 | 0.00 | 235.61 | 0.00 |
August | 17872.64 | 06-AUG-12:51 | 708.51 | 478.82 | 5041.29 | 0.00 | 0.00 | 0.00 | 0.00 | 59.44 | 0.00 |
September | 13130.14 | 11-SEP-05:02 | 1012.16 | 1437.79 | 4801.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.23 |
October | 7639.09 | 10-OCT-14:30 | 1923.11 | 1231.33 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 4.52 | 0.00 |
November | 6039.88 | 09-NOV-13:20 | 1923.11 | 1231.33 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.90 |
December | 4918.72 | 04-DEC-14:10 | 2010.79 | 1231.33 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45.88 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3824.77 | 0.00 | 410.41 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 18373.21 | 2010.79 | 1437.79 | 5041.29 | 0.00 | 0.00 | 0.00 | 0.00 | 235.61 | 149.36 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 9027.52 | 20-JAN-09:30 | 1239.33 | 793.52 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43.72 |
February | 19614.27 | 26-FEB-09:42 | 326.14 | 220.40 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 381.89 |
March | 23979.08 | 12-MAR-09:02 | 391.37 | 264.49 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 289.24 |
April | 17256.98 | 09-APR-08:62 | 326.14 | 220.40 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 808.00 |
May | 22054.84 | 28-MAY-09:52 | 326.14 | 220.40 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 52.33 |
June | 24383.59 | 11-JUN-07:52 | 391.37 | 264.49 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 119.40 |
July | 27281.63 | 09-JUL-09:01 | 587.05 | 396.73 | 4177.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40.41 |
August | 28449.96 | 06-AUG-08:11 | 652.28 | 440.81 | 4641.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 71.03 |
September | 26012.72 | 17-SEP-09:11 | 456.59 | 308.57 | 3248.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 104.07 |
October | 19170.88 | 01-OCT-08:52 | 326.14 | 220.40 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 322.09 |
November | 12420.39 | 19-NOV-09:32 | 326.14 | 220.40 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 98.53 |
December | 7183.78 | 18-DEC-09:20 | 1239.33 | 793.52 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 110.46 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 7183.78 | 326.14 | 220.40 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40.41 | |
Maximum of Months | 28449.96 | 1239.33 | 793.52 | 4641.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 808.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 28495.45 | 22-JAN-12:11 | 910.97 | 615.63 | 6481.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 557.06 |
February | 31910.07 | 26-FEB-13:01 | 1012.19 | 684.04 | 7201.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 377.50 |
March | 27978.82 | 12-MAR-12:22 | 607.31 | 410.42 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 331.22 |
April | 22864.63 | 09-APR-12:02 | 404.87 | 273.61 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 911.28 |
May | 13971.01 | 16-MAY-13:10 | 2010.83 | 1231.36 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 22.71 | 0.00 |
June | 23513.37 | 25-JUN-16:21 | 910.97 | 615.63 | 6481.75 | 0.00 | 0.00 | 0.00 | 0.00 | 155.65 | 0.00 |
July | 26180.86 | 09-JUL-13:02 | 607.31 | 410.42 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 164.25 | 0.00 |
August | 28194.18 | 06-AUG-12:11 | 708.53 | 478.83 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 60.69 | 0.00 |
September | 29835.79 | 17-SEP-11:51 | 809.75 | 547.23 | 5761.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.45 |
October | 32343.47 | 09-OCT-12:31 | 1012.19 | 684.04 | 7201.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 79.33 |
November | 30251.05 | 19-NOV-10:51 | 809.75 | 547.23 | 5761.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 592.21 |
December | 28958.72 | 17-DEC-13:01 | 708.53 | 478.83 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 375.59 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 13971.01 | 404.87 | 273.61 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 32343.47 | 2010.83 | 1231.36 | 7201.95 | 0.00 | 0.00 | 0.00 | 0.00 | 164.25 | 911.28 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 16072.89 | 22-JAN-16:12 | 326.14 | 220.40 | 2320.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 317.50 |
February | 30614.37 | 26-FEB-15:41 | 456.59 | 308.57 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 242.96 |
March | 31165.41 | 12-MAR-15:41 | 456.59 | 308.57 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 165.78 |
April | 30155.55 | 08-APR-17:41 | 456.59 | 308.57 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 175.97 |
May | 30012.74 | 28-MAY-15:52 | 391.37 | 264.49 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 86.54 |
June | 33240.95 | 11-JUN-15:51 | 521.82 | 352.65 | 3712.89 | 0.00 | 0.00 | 0.00 | 0.00 | 3.30 | 0.00 |
July | 33249.79 | 02-JUL-16:51 | 521.82 | 352.65 | 3712.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.82 |
August | 37172.90 | 13-AUG-16:41 | 652.28 | 440.81 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 89.04 |
September | 35084.85 | 17-SEP-15:51 | 652.28 | 440.81 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.61 |
October | 32226.78 | 09-OCT-13:51 | 652.28 | 440.81 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.21 |
November | 28307.02 | 05-NOV-14:21 | 456.59 | 308.57 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36.67 |
December | 23066.97 | 03-DEC-15:32 | 391.37 | 264.49 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 216.57 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 16072.89 | 326.14 | 220.40 | 2320.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 37172.90 | 652.28 | 440.81 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 3.30 | 317.50 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2676.48 | 20-JAN-16:00 | 1923.11 | 1803.00 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.83 |
February | 2603.28 | 27-FEB-15:20 | 1923.11 | 1231.33 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 327.81 |
March | 5459.43 | 14-MAR-14:40 | 1923.11 | 1231.33 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.35 |
April | 6022.84 | 20-APR-13:30 | 2010.79 | 1231.33 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.25 |
May | 9190.11 | 17-MAY-13:30 | 2010.79 | 1231.33 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 79.94 | 0.00 |
June | 17092.75 | 25-JUN-17:41 | 0.00 | 547.22 | 4473.37 | 0.00 | 0.00 | 0.00 | 0.00 | 490.66 | 0.00 |
July | 17974.95 | 16-JUL-14:51 | 708.51 | 478.82 | 5041.29 | 0.00 | 0.00 | 0.00 | 0.00 | 649.18 | 0.00 |
August | 11582.31 | 21-AUG-05:02 | 1214.60 | 1725.34 | 5761.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47.30 |
September | 16773.79 | 10-SEP-14:31 | 1012.16 | 684.02 | 7201.84 | 0.00 | 0.00 | 0.00 | 0.00 | 307.58 | 0.00 |
October | 5929.88 | 11-OCT-14:00 | 2010.79 | 1231.33 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 44.92 | 0.00 |
November | 3859.60 | 09-NOV-13:30 | 1923.11 | 1231.33 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.56 |
December | 2534.19 | 04-DEC-14:10 | 2010.79 | 1231.33 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 81.07 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2534.19 | 0.00 | 478.82 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 17974.95 | 2010.79 | 1803.00 | 7201.84 | 0.00 | 0.00 | 0.00 | 0.00 | 649.18 | 327.81 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 7318.31 | 20-JAN-09:40 | 1239.33 | 793.52 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 97.56 |
February | 9473.25 | 27-FEB-09:10 | 1239.33 | 793.52 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 136.68 |
March | 26684.68 | 12-MAR-09:31 | 456.59 | 308.57 | 3248.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 884.89 |
April | 14898.11 | 21-APR-08:40 | 1239.33 | 793.52 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 129.27 |
May | 26440.72 | 28-MAY-09:02 | 391.37 | 264.49 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 339.01 |
June | 29431.29 | 11-JUN-08:51 | 587.05 | 396.73 | 4177.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 308.45 |
July | 30220.41 | 16-JUL-08:51 | 652.28 | 440.81 | 4641.14 | 0.00 | 0.00 | 0.00 | 0.00 | 116.62 | 0.00 |
August | 31148.77 | 06-AUG-08:51 | 652.28 | 440.81 | 4641.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 97.63 |
September | 28514.14 | 04-SEP-09:51 | 521.82 | 352.65 | 3712.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 49.82 |
October | 25953.24 | 01-OCT-09:22 | 391.37 | 264.49 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 851.65 |
November | 8910.86 | 07-NOV-09:10 | 1239.33 | 793.52 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 70.19 |
December | 4113.00 | 14-DEC-09:40 | 1239.33 | 793.52 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 214.35 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 4113.00 | 391.37 | 264.49 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 31148.77 | 1239.33 | 793.52 | 4641.14 | 0.00 | 0.00 | 0.00 | 0.00 | 116.62 | 884.89 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 30286.37 | 01-JAN-13:21 | 809.75 | 547.23 | 5761.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1632.98 |
February | 29456.82 | 26-FEB-13:11 | 708.53 | 478.83 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 834.85 |
March | 31310.76 | 12-MAR-12:11 | 910.97 | 615.63 | 6481.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 720.81 |
April | 17587.29 | 12-APR-13:10 | 2010.83 | 1231.36 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 66.90 |
May | 13955.38 | 16-MAY-13:20 | 2010.83 | 1231.36 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 52.38 | 0.00 |
June | 25661.90 | 11-JUN-13:32 | 607.31 | 410.42 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 24.93 | 0.00 |
July | 26443.42 | 16-JUL-14:51 | 708.53 | 478.83 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 664.95 | 0.00 |
August | 28723.01 | 27-AUG-13:01 | 708.53 | 478.83 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 273.39 |
September | 31407.55 | 04-SEP-13:11 | 1012.19 | 684.04 | 7201.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45.38 |
October | 33181.90 | 08-OCT-13:01 | 1012.19 | 684.04 | 7201.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 462.40 |
November | 34009.38 | 05-NOV-13:21 | 1012.19 | 684.04 | 7201.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 109.39 |
December | 29307.58 | 17-DEC-13:01 | 708.53 | 478.83 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 916.89 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 13955.38 | 607.31 | 410.42 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 34009.38 | 2010.83 | 1231.36 | 7201.95 | 0.00 | 0.00 | 0.00 | 0.00 | 664.95 | 1632.98 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 10016.15 | 20-JAN-15:40 | 1239.33 | 793.52 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.56 |
February | 11141.89 | 17-FEB-16:30 | 1239.33 | 793.52 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 78.25 |
March | 29123.38 | 12-MAR-16:11 | 652.28 | 440.81 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 394.43 |
April | 26669.18 | 08-APR-17:03 | 652.28 | 440.81 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 509.19 |
May | 27509.11 | 28-MAY-15:42 | 391.37 | 264.49 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 209.16 |
June | 34812.47 | 11-JUN-16:51 | 652.28 | 440.81 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67.44 |
July | 33818.44 | 02-JUL-16:41 | 652.28 | 440.81 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 340.94 |
August | 30563.98 | 13-AUG-17:31 | 0.00 | 352.65 | 2882.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 98.47 |
September | 34297.44 | 10-SEP-16:31 | 652.28 | 440.81 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 13.18 | 0.00 |
October | 29359.54 | 08-OCT-16:21 | 652.28 | 440.81 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 453.40 |
November | 27155.14 | 05-NOV-14:41 | 652.28 | 440.81 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 104.08 |
December | 8440.02 | 01-DEC-15:30 | 1239.33 | 793.52 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.84 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 8440.02 | 0.00 | 264.49 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 34812.47 | 1239.33 | 793.52 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 13.18 | 509.19 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2887.06 | 20-JAN-15:50 | 1923.11 | 1803.00 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36.91 |
February | 2637.84 | 27-FEB-14:30 | 2010.79 | 1231.33 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 418.85 |
March | 5545.90 | 14-MAR-14:40 | 1923.11 | 1231.33 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.84 |
April | 6546.20 | 20-APR-13:30 | 2010.79 | 1231.33 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.08 |
May | 9648.05 | 17-MAY-13:30 | 2010.79 | 1231.33 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 97.03 | 0.00 |
June | 19497.63 | 04-JUN-18:11 | 0.00 | 547.22 | 4473.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 54.59 |
July | 19541.19 | 16-JUL-15:02 | 607.30 | 410.41 | 4321.10 | 0.00 | 0.00 | 0.00 | 0.00 | 858.94 | 0.00 |
August | 16576.50 | 20-AUG-15:31 | 809.73 | 547.22 | 5761.47 | 0.00 | 0.00 | 0.00 | 0.00 | 59.81 | 0.00 |
September | 19402.17 | 10-SEP-14:31 | 1012.16 | 684.02 | 7201.84 | 0.00 | 0.00 | 0.00 | 0.00 | 345.93 | 0.00 |
October | 6164.19 | 11-OCT-14:30 | 1923.11 | 1231.33 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 49.37 | 0.00 |
November | 3190.77 | 09-NOV-13:50 | 1923.11 | 1231.33 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.45 |
December | 2639.50 | 01-DEC-14:50 | 2010.79 | 1350.81 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.74 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2637.84 | 0.00 | 410.41 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 19541.19 | 2010.79 | 1803.00 | 7201.84 | 0.00 | 0.00 | 0.00 | 0.00 | 858.94 | 418.85 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 5846.49 | 20-JAN-09:50 | 1239.33 | 793.52 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 114.98 |
February | 6901.65 | 27-FEB-09:30 | 1239.33 | 793.52 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 188.63 |
March | 18210.41 | 12-MAR-09:21 | 456.59 | 308.57 | 3248.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 972.89 |
April | 14306.79 | 21-APR-09:00 | 1239.33 | 793.52 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 145.64 |
May | 15200.53 | 16-MAY-08:40 | 1239.33 | 793.52 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.71 |
June | 28591.60 | 11-JUN-08:21 | 521.82 | 352.65 | 3712.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 390.13 |
July | 28548.27 | 04-JUL-09:01 | 521.82 | 352.65 | 3712.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 245.42 |
August | 27660.10 | 06-AUG-09:01 | 456.59 | 308.57 | 3248.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 79.97 |
September | 28526.25 | 04-SEP-09:21 | 521.82 | 352.65 | 3712.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 116.60 |
October | 19016.70 | 08-OCT-10:21 | 521.82 | 352.65 | 3712.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 310.45 |
November | 7131.05 | 07-NOV-09:20 | 1239.33 | 793.52 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 83.10 |
December | 3387.84 | 01-DEC-14:20 | 1295.83 | 793.52 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.88 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3387.84 | 456.59 | 308.57 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.88 | |
Maximum of Months | 28591.60 | 1295.83 | 793.52 | 3712.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 972.89 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 31344.32 | 22-JAN-14:01 | 708.53 | 478.83 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1724.15 |
February | 33940.88 | 26-FEB-13:01 | 1012.19 | 684.04 | 7201.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1107.86 |
March | 32659.45 | 12-MAR-13:21 | 910.97 | 615.63 | 6481.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1845.71 |
April | 17915.40 | 21-APR-13:20 | 2010.83 | 1231.36 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 181.62 |
May | 14520.64 | 16-MAY-13:20 | 2010.83 | 1231.36 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 62.83 | 0.00 |
June | 27812.57 | 11-JUN-15:01 | 1012.19 | 684.04 | 7201.95 | 0.00 | 0.00 | 0.00 | 0.00 | 53.45 | 0.00 |
July | 27938.82 | 23-JUL-13:22 | 506.09 | 342.02 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 403.93 | 0.00 |
August | 28898.96 | 20-AUG-13:32 | 607.31 | 410.42 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.99 | 0.00 |
September | 33558.46 | 04-SEP-12:01 | 910.97 | 615.63 | 6481.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 133.63 |
October | 35339.97 | 09-OCT-13:21 | 1012.19 | 684.04 | 7201.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 273.17 |
November | 35785.75 | 05-NOV-13:31 | 1012.19 | 684.04 | 7201.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 145.58 |
December | 30401.85 | 03-DEC-13:31 | 708.53 | 478.83 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 967.97 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 14520.64 | 506.09 | 342.02 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 35785.75 | 2010.83 | 1231.36 | 7201.95 | 0.00 | 0.00 | 0.00 | 0.00 | 403.93 | 1845.71 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 10012.91 | 20-JAN-15:40 | 1239.33 | 793.52 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.84 |
February | 10998.05 | 17-FEB-16:30 | 1239.33 | 793.52 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 98.15 |
March | 31808.27 | 12-MAR-16:01 | 521.82 | 352.65 | 3712.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 478.08 |
April | 27966.43 | 08-APR-17:03 | 652.28 | 440.81 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 632.82 |
May | 20742.66 | 07-MAY-15:32 | 391.37 | 264.49 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 371.83 |
June | 36332.58 | 11-JUN-16:21 | 652.28 | 440.81 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 76.38 |
July | 32707.06 | 01-JUL-17:41 | 521.82 | 352.65 | 3712.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 56.35 |
August | 35770.92 | 13-AUG-17:11 | 0.00 | 440.81 | 3603.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 203.53 |
September | 36271.41 | 10-SEP-16:31 | 652.28 | 440.81 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 7.65 | 0.00 |
October | 32962.39 | 09-OCT-16:01 | 587.05 | 396.73 | 4177.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 213.21 |
November | 27828.23 | 05-NOV-15:31 | 521.82 | 352.65 | 3712.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 263.50 |
December | 8225.79 | 01-DEC-15:30 | 1239.33 | 793.52 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37.93 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 8225.79 | 0.00 | 264.49 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 36332.58 | 1239.33 | 793.52 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 7.65 | 632.82 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 7713.97 | 05-JAN-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 569.69 |
February | 8176.25 | 06-FEB-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1381.33 |
March | 7309.13 | 13-MAR-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.21 |
April | 6359.43 | 21-APR-13:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 130.19 |
May | 6733.39 | 18-MAY-14:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.37 |
June | 11163.12 | 26-JUN-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 184.56 | 0.00 |
July | 10767.52 | 05-JUL-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 89.05 |
August | 12261.44 | 21-AUG-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 53.98 |
September | 11081.75 | 05-SEP-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 161.06 |
October | 8919.51 | 10-OCT-15:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.73 | 0.00 |
November | 6196.45 | 30-NOV-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 647.34 |
December | 9860.85 | 21-DEC-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1927.69 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 6196.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 12261.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 184.56 | 1927.69 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 13450.67 | 05-JAN-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 894.35 |
February | 11519.55 | 02-FEB-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1878.96 |
March | 15564.73 | 19-MAR-06:32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8365.40 |
April | 13302.56 | 03-APR-03:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2108.57 |
May | 6856.10 | 01-MAY-04:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2135.54 |
June | 8662.17 | 26-JUN-14:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 243.89 | 0.00 |
July | 8934.50 | 17-JUL-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 314.84 | 0.00 |
August | 8107.78 | 21-AUG-14:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 77.08 | 0.00 |
September | 7859.94 | 11-SEP-14:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 159.03 | 0.00 |
October | 15000.06 | 30-OCT-03:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2129.60 |
November | 13329.30 | 30-NOV-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2912.04 |
December | 13837.62 | 21-DEC-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1357.24 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 6856.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 15564.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 314.84 | 8365.40 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 6049.99 | 20-JAN-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 69.12 |
February | 5560.38 | 18-FEB-14:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 128.90 |
March | 13296.69 | 14-MAR-14:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 78.32 |
April | 13857.69 | 21-APR-13:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 320.09 |
May | 17858.28 | 31-MAY-14:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 54.16 | 0.00 |
June | 24198.52 | 26-JUN-13:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 161.52 | 0.00 |
July | 21110.51 | 18-JUL-14:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 275.71 | 0.00 |
August | 23285.50 | 16-AUG-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 91.52 | 0.00 |
September | 17794.91 | 12-SEP-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 62.88 | 0.00 |
October | 12658.24 | 11-OCT-14:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.34 | 0.00 |
November | 7905.82 | 09-NOV-13:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.84 |
December | 4005.26 | 03-DEC-13:34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 754.17 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 4005.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 24198.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 275.71 | 754.17 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 2721.98 | 23-JAN-16:40 | 222.14 | 578.72 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 4719.88 | 23-FEB-17:00 | 222.14 | 578.72 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 7157.34 | 31-MAR-24:00 | 0.00 | 32.15 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 8493.92 | 08-APR-18:00 | 23.38 | 64.31 | 15588.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 3504.20 | 31-MAY-24:00 | 0.00 | 32.15 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5375.78 | 30-JUN-24:00 | 0.00 | 64.31 | 11691.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 7289.27 | 31-JUL-24:00 | 0.00 | 32.15 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 8767.19 | 05-AUG-18:21 | 0.00 | 225.07 | 54560.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 3328.73 | 30-SEP-24:00 | 0.00 | 32.15 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 5024.37 | 09-OCT-16:41 | 93.53 | 257.22 | 31177.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6643.43 | 07-NOV-16:20 | 222.14 | 578.72 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 8284.19 | 29-DEC-16:20 | 222.14 | 578.72 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 2721.98 | 0.00 | 32.15 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 8767.19 | 222.14 | 578.72 | 54560.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 2496.45 | 23-JAN-16:50 | 222.14 | 578.72 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 4407.22 | 23-FEB-17:00 | 222.14 | 578.72 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6621.87 | 31-MAR-23:30 | 0.00 | 32.15 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 8028.66 | 07-APR-17:50 | 23.38 | 192.90 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 3286.18 | 31-MAY-24:00 | 0.00 | 32.15 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5248.58 | 30-JUN-24:00 | 0.00 | 64.31 | 11691.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6849.51 | 31-JUL-24:00 | 0.00 | 32.15 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 8333.99 | 13-AUG-18:34 | 0.00 | 289.38 | 70149.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 2959.18 | 30-SEP-23:50 | 0.00 | 32.15 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 4530.35 | 08-OCT-16:45 | 23.38 | 64.31 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6232.88 | 07-NOV-16:20 | 222.14 | 578.72 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 7669.43 | 14-DEC-16:00 | 222.14 | 578.72 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 2496.45 | 0.00 | 32.15 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 8333.99 | 222.14 | 578.72 | 70149.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 2500.79 | 20-JAN-16:40 | 222.14 | 578.72 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 4394.94 | 17-FEB-17:00 | 222.14 | 578.72 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6429.94 | 31-MAR-17:40 | 23.38 | 192.90 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 8117.85 | 07-APR-17:50 | 23.38 | 192.90 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 3229.20 | 31-MAY-23:40 | 0.00 | 32.15 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5243.37 | 30-JUN-24:00 | 0.00 | 64.31 | 11691.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6836.78 | 01-JUL-18:50 | 0.00 | 32.15 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 8469.31 | 13-AUG-18:30 | 0.00 | 289.38 | 70149.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 3170.35 | 10-SEP-17:35 | 0.00 | 64.31 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 4532.59 | 05-OCT-16:50 | 70.15 | 321.51 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6255.14 | 07-NOV-16:20 | 222.14 | 578.72 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 7634.20 | 14-DEC-16:00 | 222.14 | 578.72 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 2500.79 | 0.00 | 32.15 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 8469.31 | 222.14 | 578.72 | 70149.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 92885.93 | 20-JAN-17:00 | 4808.68 | 6471.01 | 94908.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 184399.67 | 27-FEB-17:00 | 4808.68 | 6471.01 | 189816.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 359469.22 | 31-MAR-24:00 | 0.00 | 359.47 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 368460.23 | 07-APR-16:00 | 4808.68 | 6471.01 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 176420.07 | 31-MAY-24:00 | 0.00 | 359.47 | 189816.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 268615.02 | 30-JUN-23:55 | 0.00 | 718.95 | 569448.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 359772.24 | 31-JUL-24:00 | 0.00 | 359.47 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 384368.46 | 16-AUG-21:12 | 1012.35 | 2876.11 | 1518530.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 176428.75 | 30-SEP-24:00 | 0.00 | 359.47 | 189816.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 266451.26 | 31-OCT-24:00 | 0.00 | 359.47 | 284724.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 277967.86 | 07-NOV-17:00 | 4808.68 | 6471.01 | 284724.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 369201.23 | 04-DEC-17:00 | 4808.68 | 6471.01 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 92885.93 | 0.00 | 359.47 | 94908.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 384368.46 | 4808.68 | 6471.01 | 1518530.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.176944E+13 | 1254928.44 | 23-JAN-16:10 | 0.371070E+12 | 1163579.77 | 05-JAN-07:10 |
February | 0.197197E+13 | 1269638.55 | 17-FEB-16:10 | 0.398309E+12 | 1325168.53 | 06-FEB-07:10 |
March | 0.260396E+13 | 1729090.73 | 13-MAR-15:30 | 0.286188E+12 | 914303.81 | 20-MAR-05:10 |
April | 0.279353E+13 | 1812674.02 | 07-APR-15:30 | 0.193888E+12 | 913077.59 | 03-APR-06:19 |
May | 0.190039E+13 | 1517689.72 | 16-MAY-15:09 | 0.790374E+11 | 478202.25 | 01-MAY-04:19 |
June | 0.251174E+13 | 1789914.99 | 26-JUN-14:09 | 0.659836E+11 | 81042.73 | 01-JUN-11:50 |
July | 0.299268E+13 | 1945874.98 | 24-JUL-15:20 | 0.626787E+11 | 78831.92 | 03-JUL-11:30 |
August | 0.351616E+13 | 2195763.20 | 16-AUG-15:09 | 0.657677E+11 | 77706.10 | 30-AUG-11:30 |
September | 0.200181E+13 | 1553856.70 | 12-SEP-15:50 | 0.677239E+11 | 470394.95 | 22-SEP-05:10 |
October | 0.223010E+13 | 1633911.95 | 10-OCT-15:00 | 0.216913E+12 | 1026473.08 | 30-OCT-06:19 |
November | 0.247886E+13 | 1618999.69 | 06-NOV-16:49 | 0.302696E+12 | 966074.26 | 30-NOV-07:10 |
December | 0.286257E+13 | 1679625.14 | 01-DEC-14:09 | 0.569742E+12 | 1539182.19 | 23-DEC-07:10 |
Annual Sum or Average | 0.296332E+14 | 0.268000E+13 | ||||
Minimum of Months | 0.176944E+13 | 1254928.44 | 0.626787E+11 | 77706.10 | ||
Maximum of Months | 0.351616E+13 | 2195763.20 | 0.569742E+12 | 1539182.19 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [J] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [J] | HUMIDIFIER:ELECTRICITY [J] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 0.333712E+12 | 0.751096E+11 | 0.766053E+12 | 0.164271E+12 | 0.212048E+12 | 0.175629E+11 | 0.00 | 0.223107E+11 | 0.475636E+10 | 0.173619E+12 | 0.00 | 0.00 | 0.00 |
February | 0.299690E+12 | 0.621483E+11 | 0.978954E+12 | 0.148382E+12 | 0.194241E+12 | 0.182700E+11 | 0.00 | 0.321963E+11 | 0.537720E+10 | 0.232707E+12 | 0.00 | 0.00 | 0.00 |
March | 0.352121E+12 | 0.607720E+11 | 0.141687E+13 | 0.164522E+12 | 0.228864E+12 | 0.219317E+11 | 0.00 | 0.756286E+11 | 0.188832E+11 | 0.264367E+12 | 0.00 | 0.00 | 0.00 |
April | 0.312944E+12 | 0.506705E+11 | 0.165903E+13 | 0.158945E+12 | 0.215963E+12 | 0.211305E+11 | 0.00 | 0.999731E+11 | 0.270855E+11 | 0.247797E+12 | 0.00 | 0.00 | 0.00 |
May | 0.336013E+12 | 0.460277E+11 | 0.774844E+12 | 0.164393E+12 | 0.250075E+12 | 0.324484E+11 | 0.00 | 0.924427E+11 | 0.427924E+11 | 0.161353E+12 | 0.00 | 0.00 | 0.00 |
June | 0.333631E+12 | 0.415335E+11 | 0.106252E+13 | 0.159182E+12 | 0.313354E+12 | 0.588616E+11 | 0.00 | 0.340401E+12 | 0.104978E+12 | 0.972840E+11 | 0.00 | 0.00 | 0.00 |
July | 0.312815E+12 | 0.438990E+11 | 0.139340E+13 | 0.164155E+12 | 0.308438E+12 | 0.625660E+11 | 0.00 | 0.468464E+12 | 0.129631E+12 | 0.109309E+12 | 0.00 | 0.00 | 0.00 |
August | 0.349412E+12 | 0.492329E+11 | 0.173200E+13 | 0.164521E+12 | 0.315793E+12 | 0.645398E+11 | 0.00 | 0.546555E+12 | 0.131705E+12 | 0.162401E+12 | 0.00 | 0.00 | 0.00 |
September | 0.313499E+12 | 0.552654E+11 | 0.740713E+12 | 0.158944E+12 | 0.266544E+12 | 0.460043E+11 | 0.00 | 0.184313E+12 | 0.766723E+11 | 0.159857E+12 | 0.00 | 0.00 | 0.00 |
October | 0.328884E+12 | 0.655052E+11 | 0.108340E+13 | 0.164269E+12 | 0.227550E+12 | 0.244174E+11 | 0.00 | 0.717556E+11 | 0.219301E+11 | 0.242387E+12 | 0.00 | 0.00 | 0.00 |
November | 0.329527E+12 | 0.705704E+11 | 0.135889E+13 | 0.159045E+12 | 0.210519E+12 | 0.187012E+11 | 0.00 | 0.630458E+11 | 0.130819E+11 | 0.255474E+12 | 0.00 | 0.00 | 0.00 |
December | 0.323996E+12 | 0.771134E+11 | 0.170972E+13 | 0.164160E+12 | 0.211861E+12 | 0.189455E+11 | 0.00 | 0.750978E+11 | 0.138326E+11 | 0.267840E+12 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.392624E+13 | 0.697848E+12 | 0.146764E+14 | 0.193479E+13 | 0.295525E+13 | 0.405379E+12 | 0.00 | 0.207218E+13 | 0.590725E+12 | 0.237439E+13 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.299690E+12 | 0.415335E+11 | 0.740713E+12 | 0.148382E+12 | 0.194241E+12 | 0.175629E+11 | 0.00 | 0.223107E+11 | 0.475636E+10 | 0.972840E+11 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.352121E+12 | 0.771134E+11 | 0.173200E+13 | 0.164522E+12 | 0.315793E+12 | 0.645398E+11 | 0.00 | 0.546555E+12 | 0.131705E+12 | 0.267840E+12 | 0.00 | 0.00 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [J] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.00 | 0.00 | 0.298031E+12 | 0.00 | 0.730396E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.331498E+12 | 0.00 | 0.668104E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.209842E+12 | 0.00 | 0.763460E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.125156E+12 | 0.00 | 0.687316E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.914047E+10 | 0.00 | 0.698970E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.659836E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.626787E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 3080097.00 | 0.00 | 0.657646E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.592829E+10 | 0.00 | 0.617956E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.151120E+12 | 0.00 | 0.657925E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.235833E+12 | 0.00 | 0.668625E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.499792E+12 | 0.00 | 0.699501E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.186634E+13 | 0.00 | 0.813652E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.617956E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.499792E+12 | 0.00 | 0.763460E+11 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | EXTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum} [W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 385834.94 | 02-JAN-16:40 | 57580.60 | 01-JAN-06:10 | 423497.50 | 02-JAN-08:09 | 118525.16 | 31-JAN-08:20 | 170906.33 | 24-JAN-16:40 | 25967.28 | 14-JAN-06:10 | 0.00 | 01-JAN-00:10 |
February | 385834.94 | 06-FEB-16:40 | 57580.60 | 01-FEB-06:10 | 541788.89 | 01-FEB-08:09 | 118525.16 | 06-FEB-08:20 | 167760.62 | 23-FEB-16:19 | 27605.34 | 06-FEB-06:49 | 0.00 | 01-FEB-00:10 |
March | 369206.61 | 21-MAR-07:10 | 57580.60 | 01-MAR-06:10 | 660080.29 | 01-MAR-08:09 | 118522.43 | 21-MAR-07:19 | 216311.58 | 10-MAR-16:10 | 46606.37 | 14-MAR-13:39 | 0.00 | 01-MAR-00:10 |
April | 352283.84 | 03-APR-07:10 | 57580.60 | 01-APR-05:10 | 778371.69 | 03-APR-07:10 | 118509.21 | 03-APR-07:19 | 213398.40 | 07-APR-15:20 | 27222.60 | 17-APR-05:10 | 0.00 | 01-APR-00:10 |
May | 333218.76 | 19-MAY-07:10 | 57580.60 | 01-MAY-18:49 | 423497.50 | 01-MAY-07:10 | 118494.36 | 19-MAY-07:19 | 248124.99 | 18-MAY-14:30 | 48297.99 | 31-MAY-12:30 | 0.00 | 01-MAY-00:10 |
June | 333338.24 | 16-JUN-07:10 | 57580.60 | 01-JUN-19:19 | 541788.89 | 01-JUN-07:10 | 118494.45 | 16-JUN-07:19 | 371803.09 | 26-JUN-14:09 | 59147.18 | 26-JUN-14:09 | 0.00 | 01-JUN-00:10 |
July | 333218.76 | 28-JUL-07:10 | 57580.60 | 01-JUL-19:30 | 660080.29 | 03-JUL-07:10 | 118494.36 | 28-JUL-07:19 | 321369.05 | 24-JUL-15:20 | 58678.89 | 18-JUL-15:09 | 0.00 | 01-JUL-00:10 |
August | 337010.14 | 28-AUG-15:00 | 57580.60 | 01-AUG-19:10 | 778371.69 | 01-AUG-07:10 | 118494.45 | 21-AUG-07:40 | 324413.22 | 11-AUG-14:00 | 57778.26 | 31-AUG-10:39 | 0.00 | 01-AUG-00:10 |
September | 337087.14 | 21-SEP-15:00 | 57580.60 | 01-SEP-05:10 | 423497.50 | 01-SEP-07:10 | 118497.31 | 22-SEP-07:19 | 301152.81 | 05-SEP-15:39 | 59450.27 | 12-SEP-15:20 | 0.00 | 01-SEP-00:10 |
October | 372703.55 | 23-OCT-07:10 | 57580.60 | 01-OCT-05:10 | 541788.89 | 02-OCT-07:10 | 118525.16 | 23-OCT-07:19 | 214009.37 | 20-OCT-15:39 | 46565.55 | 11-OCT-10:00 | 0.00 | 01-OCT-00:10 |
November | 385834.94 | 06-NOV-16:49 | 57580.60 | 01-NOV-05:10 | 660080.29 | 01-NOV-07:10 | 118525.16 | 01-NOV-07:19 | 187423.42 | 08-NOV-15:39 | 26636.77 | 02-NOV-05:10 | 0.00 | 01-NOV-00:10 |
December | 385834.94 | 01-DEC-16:30 | 57580.60 | 01-DEC-06:10 | 778371.69 | 01-DEC-08:09 | 118525.16 | 21-DEC-08:20 | 154323.55 | 04-DEC-15:30 | 26973.86 | 19-DEC-06:10 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 333218.76 | 57580.60 | 423497.50 | 118494.36 | 154323.55 | 25967.28 | 0.00 | |||||||
Maximum of Months | 385834.94 | 57580.60 | 778371.69 | 118525.16 | 371803.09 | 59450.27 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY {Maximum} [W] | HEATREJECTION:ELECTRICITY {TIMESTAMP} | HUMIDIFIER:ELECTRICITY {Maximum} [W] | HUMIDIFIER:ELECTRICITY {TIMESTAMP} | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 111199.47 | 20-JAN-14:20 | 49524.27 | 20-JAN-13:20 | 100000.00 | 01-JAN-09:00 | 0.00 | 0.00 | 0.00 |
February | 99729.94 | 18-FEB-13:00 | 49467.26 | 18-FEB-13:00 | 100000.00 | 01-FEB-10:50 | 0.00 | 0.00 | 0.00 |
March | 311825.56 | 14-MAR-13:39 | 51136.95 | 14-MAR-13:50 | 100000.00 | 01-MAR-04:10 | 0.00 | 0.00 | 0.00 |
April | 252117.20 | 19-APR-13:30 | 50071.24 | 20-APR-12:00 | 100000.00 | 01-APR-03:39 | 0.00 | 0.00 | 0.00 |
May | 280776.12 | 31-MAY-13:30 | 66498.30 | 31-MAY-16:10 | 100000.00 | 01-MAY-21:10 | 0.00 | 0.00 | 0.00 |
June | 395224.76 | 26-JUN-15:20 | 83748.33 | 15-JUN-13:20 | 100000.00 | 04-JUN-09:39 | 0.00 | 0.00 | 0.00 |
July | 418874.15 | 17-JUL-13:30 | 83748.33 | 19-JUL-09:09 | 100000.00 | 01-JUL-00:20 | 0.00 | 0.00 | 0.00 |
August | 462978.65 | 16-AUG-15:09 | 83748.33 | 03-AUG-10:20 | 100000.00 | 01-AUG-00:49 | 0.00 | 0.00 | 0.00 |
September | 300849.64 | 12-SEP-15:20 | 66498.30 | 01-SEP-11:39 | 100000.00 | 04-SEP-09:39 | 0.00 | 0.00 | 0.00 |
October | 302440.07 | 11-OCT-13:00 | 51893.86 | 11-OCT-11:09 | 100000.00 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 |
November | 235013.00 | 07-NOV-14:00 | 50086.52 | 07-NOV-14:00 | 100000.00 | 01-NOV-00:49 | 0.00 | 0.00 | 0.00 |
December | 238726.26 | 01-DEC-14:09 | 49605.25 | 01-DEC-14:09 | 100000.00 | 01-DEC-05:30 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 99729.94 | 49467.26 | 100000.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 462978.65 | 83748.33 | 100000.00 | 0.00 | 0.00 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY {AT MAX/MIN} [W] | |
January | 1254928.44 | 23-JAN-16:10 | 350141.41 | 423497.50 | 0.00 | 84459.03 | 146099.61 | 24010.46 | 0.00 | 77305.23 | 49415.20 |
February | 1269638.55 | 17-FEB-16:10 | 334652.47 | 541788.89 | 0.00 | 84452.08 | 150098.27 | 23864.42 | 0.00 | 28835.78 | 5946.64 |
March | 1729090.73 | 13-MAR-15:30 | 332294.83 | 660080.29 | 0.00 | 84450.25 | 168655.26 | 45182.72 | 0.00 | 287580.42 | 50846.97 |
April | 1812674.02 | 07-APR-15:30 | 332294.83 | 778371.69 | 0.00 | 84450.25 | 213322.50 | 24233.34 | 0.00 | 230277.12 | 49724.30 |
May | 1517689.72 | 16-MAY-15:09 | 332294.83 | 423497.50 | 0.00 | 84450.25 | 233703.05 | 44906.01 | 0.00 | 248537.16 | 50300.93 |
June | 1789914.99 | 26-JUN-14:09 | 332294.83 | 541788.89 | 0.00 | 39059.06 | 371803.09 | 59147.18 | 0.00 | 389698.90 | 53095.78 |
July | 1945874.98 | 24-JUL-15:20 | 332294.83 | 660080.29 | 0.00 | 84450.25 | 321369.05 | 47645.90 | 0.00 | 404909.60 | 83748.33 |
August | 2195763.20 | 16-AUG-15:09 | 332294.83 | 778371.69 | 0.00 | 84450.25 | 307376.85 | 46542.60 | 0.00 | 462978.65 | 83748.33 |
September | 1553856.70 | 12-SEP-15:50 | 332294.83 | 423497.50 | 0.00 | 84450.25 | 297493.84 | 58117.51 | 0.00 | 296323.41 | 52493.15 |
October | 1633911.95 | 10-OCT-15:00 | 332294.83 | 541788.89 | 0.00 | 84450.25 | 209536.67 | 44984.29 | 0.00 | 269126.52 | 51730.50 |
November | 1618999.69 | 06-NOV-16:49 | 385834.94 | 660080.29 | 57580.60 | 84486.19 | 139235.45 | 23952.14 | 0.00 | 118456.21 | 49373.87 |
December | 1679625.14 | 01-DEC-14:09 | 332294.83 | 778371.69 | 0.00 | 39059.06 | 117175.04 | 24393.01 | 0.00 | 238726.26 | 49605.25 |
Annual Sum or Average | |||||||||||
Minimum of Months | 1254928.44 | 332294.83 | 423497.50 | 0.00 | 39059.06 | 117175.04 | 23864.42 | 0.00 | 28835.78 | 5946.64 | |
Maximum of Months | 2195763.20 | 385834.94 | 778371.69 | 57580.60 | 84486.19 | 371803.09 | 59147.18 | 0.00 | 462978.65 | 83748.33 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS {Maximum} [W] | WATERSYSTEMS:NATURALGAS {TIMESTAMP} | COGENERATION:NATURALGAS [] | |
January | 0.00 | 0.00 | 1133039.41 | 05-JAN-07:10 | 0.00 | 85890.16 | 30-JAN-12:20 | 0.00 |
February | 0.00 | 0.00 | 1292911.72 | 06-FEB-07:10 | 0.00 | 85997.10 | 14-FEB-12:30 | 0.00 |
March | 0.00 | 0.00 | 906157.23 | 20-MAR-05:10 | 0.00 | 85777.50 | 06-MAR-12:30 | 0.00 |
April | 0.00 | 0.00 | 880685.32 | 03-APR-06:19 | 0.00 | 84805.83 | 03-APR-11:39 | 0.00 |
May | 0.00 | 0.00 | 470055.67 | 01-MAY-04:19 | 0.00 | 83218.86 | 01-MAY-11:00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 81042.73 | 01-JUN-11:50 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 78831.92 | 03-JUL-11:30 | 0.00 |
August | 0.00 | 0.00 | 978.86 | 23-AUG-05:40 | 0.00 | 77706.10 | 30-AUG-11:30 | 0.00 |
September | 0.00 | 0.00 | 441255.35 | 22-SEP-05:10 | 0.00 | 78824.99 | 26-SEP-11:00 | 0.00 |
October | 0.00 | 0.00 | 994630.77 | 30-OCT-06:19 | 0.00 | 81146.09 | 30-OCT-11:30 | 0.00 |
November | 0.00 | 0.00 | 945304.03 | 30-NOV-07:10 | 0.00 | 83272.71 | 29-NOV-12:20 | 0.00 |
December | 0.00 | 0.00 | 1508880.84 | 23-DEC-07:10 | 0.00 | 84927.91 | 29-DEC-12:39 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 77706.10 | 0.00 | ||
Maximum of Months | 0.00 | 0.00 | 1508880.84 | 0.00 | 85997.10 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 4.83 | 26.80 | 0.50 | 26.86 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 26.30 | 0.00 | 26.30 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 25.74 | 0.00 | 25.74 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 25.70 | 0.00 | 25.70 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 26.42 | 0.00 | 26.42 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 3.67 | 25.75 | 0.00 | 25.75 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 6.33 | 26.30 | 0.00 | 26.30 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 6.83 | 26.30 | 0.17 | 26.32 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 7.00 | 26.44 | 0.17 | 26.46 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 7.33 | 26.46 | 0.17 | 26.49 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 7.83 | 26.45 | 0.17 | 26.46 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 4.00 | 26.35 | 0.00 | 26.35 |
Annual Sum or Average | 0.00 | 0.00 | 54.50 | 26.35 | 1.17 | 26.37 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 25.70 | 0.00 | 25.70 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 7.83 | 26.80 | 0.50 | 26.86 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 25.57 | 0.00 | 25.57 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 25.64 | 0.00 | 25.64 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 25.73 | 0.00 | 25.73 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 25.65 | 0.00 | 25.65 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 25.68 | 0.00 | 25.68 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 25.90 | 0.00 | 25.90 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 4.17 | 25.68 | 0.00 | 25.68 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 25.90 | 0.00 | 25.90 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 1.33 | 18.69 | 0.00 | 18.69 | 0.00 | 18.69 | 0.00 | 18.69 |
February | 1.83 | 18.71 | 0.33 | 18.93 | 0.00 | 18.93 | 0.00 | 18.93 |
March | 0.83 | 18.36 | 0.00 | 18.36 | 0.00 | 18.36 | 0.00 | 18.36 |
April | 1.50 | 18.83 | 0.00 | 18.83 | 0.00 | 18.83 | 0.00 | 18.83 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.17 | 19.06 | 0.00 | 19.06 | 0.00 | 19.06 | 0.00 | 19.06 |
November | 0.33 | 18.69 | 0.00 | 18.69 | 0.00 | 18.69 | 0.00 | 18.69 |
December | 1.50 | 18.60 | 0.00 | 18.60 | 0.00 | 18.60 | 0.00 | 18.60 |
Annual Sum or Average | 7.50 | 18.68 | 0.33 | 18.74 | 0.00 | 18.74 | 0.00 | 18.74 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1.83 | 19.06 | 0.33 | 19.06 | 0.00 | 19.06 | 0.00 | 19.06 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.50 | 19.35 | 0.00 | 19.35 | 0.00 | 19.35 | 0.00 | 19.35 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 4.17 | 27.43 | 3.00 | 27.42 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 7.00 | 27.49 | 5.67 | 27.52 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 27.35 | 1.50 | 27.35 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.28 | 0.33 | 27.28 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 1.00 | 18.81 | 0.00 | 18.81 | 0.00 | 18.81 | 0.00 | 18.81 |
Annual Sum or Average | 1.50 | 18.99 | 0.00 | 18.99 | 13.00 | 26.58 | 10.50 | 26.96 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1.00 | 19.35 | 0.00 | 19.35 | 7.00 | 27.49 | 5.67 | 27.52 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.33 | 19.34 | 0.00 | 19.34 | 0.00 | 19.34 | 0.00 | 19.34 |
February | 0.67 | 19.21 | 0.00 | 19.21 | 0.67 | 23.47 | 0.67 | 24.90 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 28.42 | 1.83 | 28.42 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 28.24 | 1.00 | 28.24 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 27.89 | 1.67 | 27.89 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 7.83 | 28.00 | 7.83 | 28.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 13.67 | 28.27 | 13.50 | 28.27 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 28.46 | 5.17 | 28.46 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 4.83 | 28.26 | 4.83 | 28.26 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 28.23 | 3.17 | 28.23 |
November | 0.17 | 19.29 | 0.00 | 19.29 | 1.00 | 26.46 | 1.00 | 27.01 |
December | 1.00 | 18.53 | 0.00 | 18.53 | 0.00 | 18.53 | 0.00 | 18.53 |
Annual Sum or Average | 2.17 | 18.92 | 0.00 | 18.92 | 40.83 | 27.74 | 40.67 | 27.97 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.53 | 0.00 | 18.53 |
Maximum of Months | 1.00 | 19.34 | 0.00 | 19.34 | 13.67 | 28.46 | 13.50 | 28.46 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.33 | 19.19 | 0.00 | 19.19 | 16.67 | 26.05 | 16.67 | 26.12 |
February | 0.83 | 18.99 | 0.00 | 18.99 | 6.83 | 26.47 | 6.83 | 26.90 |
March | 0.17 | 19.35 | 0.00 | 19.35 | 9.33 | 26.14 | 9.33 | 26.20 |
April | 0.17 | 19.38 | 0.00 | 19.38 | 0.50 | 25.68 | 0.50 | 26.58 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.43 | 0.33 | 27.43 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 5.33 | 27.73 | 5.17 | 27.73 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 9.83 | 27.88 | 9.67 | 27.88 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 6.50 | 28.14 | 6.33 | 28.15 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 13.00 | 27.35 | 12.50 | 27.35 |
October | 0.17 | 19.36 | 0.00 | 19.36 | 17.00 | 26.79 | 16.83 | 26.83 |
November | 0.17 | 19.26 | 0.00 | 19.26 | 23.83 | 26.09 | 23.83 | 26.11 |
December | 1.17 | 18.38 | 0.00 | 18.38 | 17.83 | 25.44 | 17.83 | 25.66 |
Annual Sum or Average | 3.00 | 18.85 | 0.00 | 18.85 | 127.00 | 26.54 | 125.83 | 26.63 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 25.44 | 0.33 | 25.66 |
Maximum of Months | 1.17 | 19.38 | 0.00 | 19.38 | 23.83 | 28.14 | 23.83 | 28.15 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.50 | 0.33 | 27.50 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 28.30 | 1.33 | 28.30 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 28.82 | 2.67 | 28.82 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 28.58 | 1.00 | 28.61 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 4.33 | 27.99 | 3.67 | 28.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 14.00 | 28.27 | 6.33 | 28.50 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 23.00 | 27.88 | 10.83 | 28.08 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 20.00 | 27.68 | 8.50 | 27.89 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 8.00 | 28.45 | 5.67 | 28.57 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 4.00 | 28.85 | 3.50 | 28.89 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 28.14 | 2.50 | 28.14 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 28.30 | 1.67 | 28.30 |
Annual Sum or Average | 0.00 | 0.00 | 83.67 | 28.07 | 48.00 | 28.25 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.50 | 0.33 | 27.50 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 23.00 | 28.85 | 10.83 | 28.89 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 4.50 | 18.62 | 0.50 | 18.80 | 0.00 | 18.80 | 0.00 | 18.80 |
February | 13.17 | 17.11 | 2.17 | 17.29 | 0.00 | 17.29 | 0.00 | 17.29 |
March | 5.50 | 16.90 | 1.67 | 16.46 | 0.00 | 16.46 | 0.00 | 16.46 |
April | 2.50 | 18.59 | 0.33 | 18.76 | 0.00 | 18.76 | 0.00 | 18.76 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 27.50 | 1.50 | 27.48 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 27.57 | 4.00 | 27.59 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 1.67 | 18.42 | 0.17 | 18.60 | 0.00 | 18.60 | 0.00 | 18.60 |
November | 4.17 | 18.67 | 0.67 | 18.90 | 0.00 | 18.90 | 0.00 | 18.90 |
December | 21.00 | 16.91 | 4.00 | 17.07 | 0.00 | 17.07 | 0.00 | 17.07 |
Annual Sum or Average | 52.50 | 17.37 | 9.50 | 17.46 | 7.00 | 18.48 | 5.50 | 19.15 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 21.00 | 18.67 | 4.00 | 18.90 | 5.00 | 27.57 | 4.00 | 27.59 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 3.67 | 18.59 | 0.00 | 18.59 | 0.00 | 18.59 | 0.00 | 18.59 |
February | 9.67 | 16.71 | 0.50 | 16.70 | 0.00 | 16.70 | 0.00 | 16.70 |
March | 6.17 | 16.65 | 1.50 | 16.19 | 1.67 | 18.30 | 1.67 | 19.77 |
April | 2.17 | 18.35 | 0.00 | 18.35 | 0.67 | 20.59 | 0.67 | 21.98 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 28.20 | 1.17 | 28.20 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 8.33 | 28.14 | 8.17 | 28.15 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 14.50 | 28.48 | 14.33 | 28.49 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 6.33 | 28.55 | 6.33 | 28.55 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 4.50 | 28.32 | 4.50 | 28.32 |
October | 1.50 | 18.17 | 0.00 | 18.17 | 2.50 | 24.33 | 2.50 | 25.75 |
November | 3.50 | 18.24 | 0.00 | 18.24 | 0.00 | 18.24 | 0.00 | 18.24 |
December | 13.67 | 16.17 | 1.17 | 16.16 | 0.00 | 16.16 | 0.00 | 16.16 |
Annual Sum or Average | 40.33 | 16.96 | 3.17 | 16.84 | 39.67 | 22.32 | 39.33 | 24.26 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.16 | 0.00 | 16.16 |
Maximum of Months | 13.67 | 18.59 | 1.50 | 18.59 | 14.50 | 28.55 | 14.33 | 28.55 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 2.33 | 18.64 | 0.00 | 18.64 | 36.00 | 25.32 | 36.00 | 25.53 |
February | 5.17 | 17.38 | 0.17 | 17.46 | 28.00 | 24.17 | 28.00 | 24.75 |
March | 4.50 | 16.61 | 1.33 | 16.10 | 13.50 | 22.96 | 13.33 | 24.16 |
April | 2.00 | 18.40 | 0.17 | 18.54 | 0.00 | 18.54 | 0.00 | 18.54 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.37 | 0.17 | 27.37 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 27.69 | 4.67 | 27.70 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 9.17 | 27.87 | 9.00 | 27.88 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 8.50 | 27.26 | 8.33 | 27.26 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 14.50 | 27.45 | 13.50 | 27.45 |
October | 1.50 | 18.32 | 0.00 | 18.32 | 35.33 | 25.62 | 35.17 | 25.77 |
November | 2.67 | 18.29 | 0.00 | 18.29 | 34.67 | 25.49 | 34.67 | 25.76 |
December | 8.00 | 17.13 | 0.83 | 17.09 | 23.67 | 23.35 | 23.67 | 24.33 |
Annual Sum or Average | 26.17 | 17.51 | 2.50 | 17.37 | 208.50 | 25.06 | 206.50 | 25.54 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.54 | 0.00 | 18.54 |
Maximum of Months | 8.00 | 18.64 | 1.33 | 18.64 | 36.00 | 27.87 | 36.00 | 27.88 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 3.00 | 18.66 | 0.00 | 18.66 | 0.00 | 18.66 | 0.00 | 18.66 |
February | 5.00 | 17.66 | 0.17 | 17.75 | 0.17 | 18.05 | 0.17 | 18.34 |
March | 4.50 | 16.86 | 1.33 | 16.33 | 1.67 | 19.04 | 1.00 | 20.19 |
April | 1.83 | 18.38 | 0.00 | 18.38 | 0.33 | 19.91 | 0.17 | 20.56 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 27.85 | 2.33 | 27.86 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 8.17 | 29.04 | 4.17 | 29.14 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 9.50 | 28.48 | 6.50 | 28.46 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 4.67 | 28.83 | 2.83 | 28.84 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 6.50 | 28.61 | 4.50 | 28.66 |
October | 1.50 | 18.36 | 0.00 | 18.36 | 2.67 | 24.92 | 2.33 | 26.30 |
November | 2.83 | 18.34 | 0.00 | 18.34 | 0.67 | 20.12 | 0.67 | 21.34 |
December | 8.50 | 16.61 | 1.00 | 16.49 | 0.00 | 16.49 | 0.00 | 16.49 |
Annual Sum or Average | 27.17 | 17.47 | 2.50 | 17.28 | 37.00 | 23.58 | 24.67 | 24.95 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.49 | 0.00 | 16.49 |
Maximum of Months | 8.50 | 18.66 | 1.33 | 18.66 | 9.50 | 29.04 | 6.50 | 29.14 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 31.00 | 16.41 | 7.00 | 16.57 | 0.00 | 16.57 | 0.00 | 16.57 |
February | 36.00 | 16.27 | 10.83 | 16.38 | 0.00 | 16.38 | 0.00 | 16.38 |
March | 24.00 | 16.08 | 6.00 | 16.01 | 0.00 | 16.01 | 0.00 | 16.01 |
April | 21.33 | 16.37 | 6.67 | 16.46 | 0.00 | 16.46 | 0.00 | 16.46 |
May | 0.67 | 18.65 | 0.00 | 18.65 | 0.00 | 18.65 | 0.00 | 18.65 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 4.17 | 27.49 | 2.50 | 27.47 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 6.67 | 27.72 | 5.00 | 27.75 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 27.40 | 1.00 | 27.40 |
September | 0.17 | 18.96 | 0.00 | 18.96 | 0.83 | 25.99 | 0.83 | 26.63 |
October | 11.17 | 17.08 | 3.00 | 17.28 | 0.00 | 17.28 | 0.00 | 17.28 |
November | 14.67 | 17.64 | 2.00 | 17.94 | 0.00 | 17.94 | 0.00 | 17.94 |
December | 57.33 | 16.32 | 21.17 | 16.59 | 0.00 | 16.59 | 0.00 | 16.59 |
Annual Sum or Average | 196.33 | 16.45 | 56.67 | 16.60 | 12.67 | 17.12 | 9.33 | 17.48 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.01 | 0.00 | 16.01 |
Maximum of Months | 57.33 | 18.96 | 21.17 | 18.96 | 6.67 | 27.72 | 5.00 | 27.75 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 20.00 | 15.92 | 1.67 | 15.82 | 0.00 | 15.82 | 0.00 | 15.82 |
February | 23.83 | 15.50 | 3.83 | 15.36 | 0.00 | 15.36 | 0.00 | 15.36 |
March | 18.17 | 15.60 | 3.33 | 15.36 | 0.67 | 15.74 | 0.67 | 16.09 |
April | 16.83 | 15.49 | 3.83 | 15.37 | 0.00 | 15.37 | 0.00 | 15.37 |
May | 0.67 | 18.80 | 0.00 | 18.80 | 1.00 | 24.22 | 1.00 | 25.58 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 10.17 | 28.11 | 9.67 | 28.13 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 15.83 | 28.48 | 14.83 | 28.52 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 6.83 | 28.51 | 6.67 | 28.52 |
September | 0.17 | 18.94 | 0.00 | 18.94 | 5.67 | 27.79 | 5.67 | 27.92 |
October | 8.50 | 15.99 | 1.17 | 15.84 | 1.17 | 17.12 | 1.17 | 18.14 |
November | 10.00 | 16.71 | 0.17 | 16.68 | 0.00 | 16.68 | 0.00 | 16.68 |
December | 32.50 | 15.25 | 4.33 | 15.20 | 0.00 | 15.20 | 0.00 | 15.20 |
Annual Sum or Average | 130.67 | 15.66 | 18.33 | 15.53 | 41.33 | 18.30 | 39.67 | 20.03 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.20 | 0.00 | 15.20 |
Maximum of Months | 32.50 | 18.94 | 4.33 | 18.94 | 15.83 | 28.51 | 14.83 | 28.52 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 9.83 | 17.19 | 0.83 | 17.09 | 13.50 | 22.06 | 13.50 | 23.46 |
February | 21.33 | 15.98 | 4.00 | 15.79 | 3.67 | 17.24 | 3.67 | 18.36 |
March | 17.17 | 15.69 | 3.50 | 15.42 | 8.33 | 18.49 | 8.17 | 20.15 |
April | 15.50 | 15.51 | 4.17 | 15.37 | 0.00 | 15.37 | 0.00 | 15.37 |
May | 0.67 | 18.80 | 0.00 | 18.80 | 0.17 | 20.51 | 0.17 | 21.65 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 6.17 | 27.83 | 5.67 | 27.83 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 10.00 | 28.00 | 9.17 | 28.03 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 7.67 | 27.65 | 7.33 | 27.66 |
September | 0.17 | 19.02 | 0.00 | 19.02 | 13.67 | 27.38 | 12.50 | 27.42 |
October | 6.67 | 16.07 | 0.50 | 15.99 | 16.83 | 23.62 | 16.67 | 24.95 |
November | 8.00 | 17.15 | 0.00 | 17.15 | 17.17 | 23.35 | 17.17 | 24.53 |
December | 26.17 | 15.89 | 3.17 | 15.84 | 5.50 | 17.58 | 5.50 | 18.84 |
Annual Sum or Average | 105.50 | 16.07 | 16.17 | 15.91 | 102.67 | 20.94 | 99.50 | 22.77 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.37 | 0.00 | 15.37 |
Maximum of Months | 26.17 | 19.02 | 4.17 | 19.02 | 17.17 | 28.00 | 17.17 | 28.03 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 12.17 | 16.50 | 2.00 | 16.27 | 0.00 | 16.27 | 0.00 | 16.27 |
February | 20.17 | 15.91 | 4.50 | 15.70 | 0.00 | 15.70 | 0.00 | 15.70 |
March | 14.83 | 15.92 | 3.00 | 15.64 | 1.50 | 16.63 | 0.83 | 17.13 |
April | 9.00 | 15.95 | 1.00 | 15.86 | 0.33 | 16.26 | 0.17 | 16.46 |
May | 0.50 | 18.96 | 0.00 | 18.96 | 2.50 | 26.34 | 2.17 | 26.95 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 9.00 | 29.07 | 4.67 | 29.18 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 10.67 | 28.55 | 7.33 | 28.54 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 4.67 | 28.96 | 2.67 | 28.98 |
September | 0.17 | 19.01 | 0.00 | 19.01 | 7.00 | 28.40 | 4.83 | 28.53 |
October | 5.50 | 16.04 | 0.33 | 15.98 | 2.17 | 19.40 | 2.00 | 21.25 |
November | 6.83 | 17.35 | 0.00 | 17.35 | 0.33 | 17.83 | 0.33 | 18.27 |
December | 27.33 | 15.49 | 4.33 | 15.42 | 0.00 | 15.42 | 0.00 | 15.42 |
Annual Sum or Average | 96.50 | 16.00 | 15.17 | 15.83 | 38.17 | 19.10 | 25.00 | 20.48 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.42 | 0.00 | 15.42 |
Maximum of Months | 27.33 | 19.01 | 4.50 | 19.01 | 10.67 | 29.07 | 7.33 | 29.18 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 33.00 | 28.21 | 31.83 | 28.21 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 33.00 | 28.21 | 31.83 | 28.21 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 33.00 | 28.21 | 31.83 | 28.21 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 24.50 | 28.15 | 23.67 | 28.15 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 24.50 | 28.15 | 23.67 | 28.15 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 24.50 | 28.15 | 23.67 | 28.15 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 22.17 | 28.09 | 21.33 | 28.09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 22.17 | 28.09 | 21.33 | 28.09 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 22.17 | 28.09 | 21.33 | 28.09 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 28.39 | 3.17 | 28.39 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 243.17 | 30.29 | 231.50 | 30.34 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 246.33 | 30.26 | 234.67 | 30.32 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 243.17 | 30.29 | 231.50 | 30.34 |
Report: ComfortReportSimple55Monthly
For: BASEMENT
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 125.33 | 23.96 | 83.17 | 24.86 | 0.00 | 24.86 |
February | 199.50 | 23.99 | 54.33 | 24.51 | 0.00 | 24.51 |
March | 196.17 | 23.99 | 71.83 | 24.49 | 0.00 | 24.49 |
April | 60.33 | 24.01 | 101.67 | 25.24 | 0.00 | 25.24 |
May | 48.00 | 24.00 | 172.83 | 25.07 | 0.00 | 25.07 |
June | 35.33 | 24.48 | 306.67 | 24.73 | 34.33 | 24.71 |
July | 85.33 | 24.67 | 366.67 | 24.81 | 79.50 | 24.80 |
August | 41.33 | 25.16 | 352.33 | 24.76 | 40.67 | 24.80 |
September | 14.83 | 24.00 | 197.67 | 25.27 | 0.00 | 25.27 |
October | 58.33 | 24.00 | 125.33 | 25.53 | 0.00 | 25.53 |
November | 41.50 | 23.99 | 106.00 | 25.81 | 0.00 | 25.81 |
December | 192.00 | 23.90 | 75.50 | 24.62 | 0.00 | 24.62 |
Annual Sum or Average | 1098.00 | 24.09 | 2014.00 | 24.89 | 154.50 | 24.89 |
Minimum of Months | 14.83 | 23.90 | 54.33 | 24.49 | 0.00 | 24.49 |
Maximum of Months | 199.50 | 25.16 | 366.67 | 25.81 | 79.50 | 25.81 |
Report: ComfortReportSimple55Monthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 191.33 | 23.95 | 30.67 | 24.17 | 0.00 | 24.17 |
February | 233.00 | 23.97 | 29.00 | 24.18 | 0.00 | 24.18 |
March | 154.33 | 23.98 | 36.67 | 24.26 | 0.00 | 24.26 |
April | 59.67 | 24.00 | 90.17 | 24.95 | 0.00 | 24.95 |
May | 45.67 | 24.00 | 161.00 | 24.64 | 0.00 | 24.64 |
June | 40.17 | 24.34 | 336.17 | 24.37 | 40.17 | 24.36 |
July | 86.33 | 24.41 | 385.33 | 24.39 | 83.33 | 24.40 |
August | 25.83 | 24.17 | 386.17 | 24.31 | 25.83 | 24.30 |
September | 29.83 | 24.00 | 174.33 | 24.69 | 0.00 | 24.69 |
October | 91.83 | 23.99 | 100.00 | 24.73 | 0.00 | 24.73 |
November | 76.83 | 23.98 | 74.00 | 24.79 | 0.00 | 24.79 |
December | 230.33 | 24.01 | 32.33 | 24.25 | 0.00 | 24.25 |
Annual Sum or Average | 1265.17 | 24.03 | 1835.83 | 24.43 | 149.33 | 24.42 |
Minimum of Months | 25.83 | 23.95 | 29.00 | 24.17 | 0.00 | 24.17 |
Maximum of Months | 233.00 | 24.41 | 386.17 | 24.95 | 83.33 | 24.95 |
Report: ComfortReportSimple55Monthly
For: CORE_MID
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 434.83 | 23.33 | 0.00 | 23.33 | 0.00 | 23.33 |
February | 406.00 | 23.18 | 13.33 | 23.11 | 13.33 | 23.04 |
March | 448.50 | 23.47 | 11.17 | 23.46 | 3.67 | 23.44 |
April | 330.50 | 23.58 | 13.33 | 23.63 | 0.00 | 23.63 |
May | 150.33 | 23.86 | 95.33 | 24.17 | 0.00 | 24.17 |
June | 52.50 | 24.15 | 262.00 | 24.28 | 40.67 | 24.27 |
July | 104.33 | 24.20 | 297.50 | 24.27 | 88.33 | 24.27 |
August | 35.33 | 24.07 | 311.83 | 24.30 | 30.33 | 24.29 |
September | 95.83 | 23.84 | 119.67 | 24.29 | 0.00 | 24.29 |
October | 312.17 | 23.70 | 7.67 | 23.74 | 0.00 | 23.74 |
November | 383.33 | 23.54 | 1.83 | 23.55 | 0.00 | 23.55 |
December | 493.17 | 23.04 | 35.67 | 22.85 | 35.67 | 22.69 |
Annual Sum or Average | 3246.83 | 23.46 | 1169.33 | 23.66 | 212.00 | 23.64 |
Minimum of Months | 35.33 | 23.04 | 0.00 | 22.85 | 0.00 | 22.69 |
Maximum of Months | 493.17 | 24.20 | 311.83 | 24.30 | 88.33 | 24.29 |
Report: ComfortReportSimple55Monthly
For: CORE_TOP
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 492.50 | 21.86 | 120.33 | 21.45 | 120.33 | 21.17 |
February | 444.33 | 22.02 | 107.00 | 21.64 | 107.00 | 21.39 |
March | 481.33 | 22.58 | 60.67 | 22.26 | 58.83 | 22.01 |
April | 386.83 | 22.39 | 70.17 | 22.04 | 64.50 | 21.75 |
May | 233.17 | 23.43 | 59.17 | 23.59 | 1.17 | 23.58 |
June | 57.67 | 24.07 | 297.17 | 24.26 | 38.17 | 24.26 |
July | 97.50 | 24.19 | 329.33 | 24.27 | 85.67 | 24.27 |
August | 49.17 | 23.98 | 311.50 | 24.25 | 32.00 | 24.24 |
September | 145.83 | 23.49 | 113.67 | 23.97 | 0.00 | 23.97 |
October | 434.50 | 22.81 | 41.83 | 22.61 | 41.83 | 22.45 |
November | 459.50 | 22.30 | 57.33 | 22.12 | 57.33 | 21.99 |
December | 497.00 | 21.63 | 173.00 | 21.21 | 173.00 | 20.96 |
Annual Sum or Average | 3779.33 | 22.44 | 1741.17 | 22.55 | 779.83 | 22.34 |
Minimum of Months | 49.17 | 21.63 | 41.83 | 21.21 | 0.00 | 20.96 |
Maximum of Months | 497.00 | 24.19 | 329.33 | 24.27 | 173.00 | 24.27 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 22.10 | 87.00 | 21.89 | 87.00 | 21.74 |
February | 454.00 | 22.06 | 89.50 | 21.80 | 89.50 | 21.62 |
March | 483.67 | 22.81 | 26.83 | 22.66 | 26.83 | 22.53 |
April | 368.50 | 23.05 | 14.00 | 23.02 | 7.50 | 22.98 |
May | 167.17 | 23.61 | 122.33 | 24.03 | 0.00 | 24.03 |
June | 39.33 | 24.76 | 396.33 | 24.45 | 39.17 | 24.47 |
July | 86.50 | 24.86 | 430.33 | 24.58 | 86.50 | 24.62 |
August | 35.33 | 24.73 | 391.17 | 24.37 | 30.00 | 24.40 |
September | 125.67 | 23.62 | 143.33 | 24.22 | 1.00 | 24.23 |
October | 420.17 | 22.97 | 25.33 | 22.92 | 18.00 | 22.84 |
November | 475.83 | 22.66 | 22.67 | 22.58 | 22.67 | 22.50 |
December | 497.00 | 22.10 | 125.50 | 21.79 | 125.50 | 21.58 |
Annual Sum or Average | 3655.17 | 22.70 | 1874.33 | 23.03 | 533.67 | 22.93 |
Minimum of Months | 35.33 | 22.06 | 14.00 | 21.79 | 0.00 | 21.58 |
Maximum of Months | 502.00 | 24.86 | 430.33 | 24.58 | 125.50 | 24.62 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 450.17 | 21.96 | 71.00 | 21.89 | 58.83 | 21.77 |
February | 375.67 | 21.80 | 124.17 | 21.71 | 97.00 | 21.53 |
March | 374.67 | 22.21 | 85.83 | 22.36 | 33.83 | 22.27 |
April | 308.67 | 22.34 | 85.33 | 22.59 | 21.67 | 22.54 |
May | 146.00 | 23.23 | 208.83 | 23.96 | 3.83 | 23.99 |
June | 59.33 | 25.27 | 414.50 | 24.49 | 53.33 | 24.59 |
July | 115.50 | 25.25 | 436.50 | 24.65 | 109.33 | 24.77 |
August | 77.33 | 24.49 | 392.33 | 24.29 | 46.67 | 24.39 |
September | 126.83 | 23.67 | 241.00 | 24.25 | 16.17 | 24.37 |
October | 350.83 | 22.46 | 99.00 | 22.77 | 35.17 | 22.76 |
November | 402.50 | 22.10 | 59.50 | 22.17 | 34.00 | 22.09 |
December | 461.33 | 21.72 | 135.67 | 21.51 | 131.17 | 21.35 |
Annual Sum or Average | 3248.83 | 22.41 | 2353.67 | 23.00 | 641.00 | 22.95 |
Minimum of Months | 59.33 | 21.72 | 59.50 | 21.51 | 3.83 | 21.35 |
Maximum of Months | 461.33 | 25.27 | 436.50 | 24.65 | 131.17 | 24.77 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 306.00 | 22.56 | 196.67 | 23.07 | 61.83 | 23.03 |
February | 268.00 | 22.13 | 201.83 | 22.55 | 83.33 | 22.36 |
March | 314.50 | 22.36 | 150.00 | 22.71 | 45.00 | 22.59 |
April | 298.17 | 22.31 | 117.33 | 22.47 | 43.33 | 22.29 |
May | 180.17 | 23.16 | 156.50 | 23.77 | 0.17 | 23.77 |
June | 62.67 | 24.81 | 371.17 | 24.45 | 48.50 | 24.52 |
July | 103.17 | 25.03 | 414.17 | 24.60 | 95.33 | 24.68 |
August | 59.83 | 25.24 | 422.33 | 24.46 | 47.67 | 24.57 |
September | 113.00 | 24.35 | 287.33 | 24.57 | 34.33 | 24.76 |
October | 287.00 | 22.92 | 208.33 | 23.38 | 69.83 | 23.39 |
November | 277.50 | 22.90 | 197.50 | 23.49 | 56.50 | 23.55 |
December | 327.33 | 22.33 | 188.83 | 22.63 | 90.67 | 22.49 |
Annual Sum or Average | 2597.33 | 22.84 | 2912.00 | 23.50 | 676.50 | 23.48 |
Minimum of Months | 59.83 | 22.13 | 117.33 | 22.47 | 0.17 | 22.29 |
Maximum of Months | 327.33 | 25.24 | 422.33 | 24.60 | 95.33 | 24.76 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 405.17 | 22.15 | 78.50 | 22.27 | 34.00 | 22.18 |
February | 339.83 | 22.30 | 84.00 | 22.53 | 30.17 | 22.47 |
March | 267.33 | 22.93 | 103.83 | 23.35 | 15.17 | 23.39 |
April | 144.83 | 23.29 | 187.33 | 24.00 | 4.50 | 24.04 |
May | 119.33 | 23.53 | 251.83 | 24.27 | 12.67 | 24.36 |
June | 71.33 | 25.39 | 459.83 | 24.63 | 70.50 | 24.72 |
July | 111.83 | 25.48 | 486.67 | 24.77 | 111.83 | 24.88 |
August | 81.67 | 25.56 | 500.50 | 24.63 | 81.67 | 24.75 |
September | 95.67 | 24.14 | 285.33 | 24.56 | 24.67 | 24.71 |
October | 257.00 | 22.92 | 113.83 | 23.47 | 15.83 | 23.59 |
November | 284.50 | 22.90 | 94.33 | 23.34 | 8.33 | 23.38 |
December | 342.17 | 22.69 | 90.00 | 22.77 | 45.83 | 22.65 |
Annual Sum or Average | 2520.67 | 23.04 | 2736.00 | 23.77 | 455.17 | 23.84 |
Minimum of Months | 71.33 | 22.15 | 78.50 | 22.27 | 4.50 | 22.18 |
Maximum of Months | 405.17 | 25.56 | 500.50 | 24.77 | 111.83 | 24.88 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.73 | 274.67 | 20.48 | 274.67 | 20.36 |
February | 454.00 | 20.68 | 287.67 | 20.49 | 287.67 | 20.40 |
March | 513.50 | 21.53 | 177.00 | 21.16 | 177.00 | 20.94 |
April | 455.83 | 21.70 | 125.17 | 21.32 | 121.67 | 21.06 |
May | 268.33 | 23.09 | 87.67 | 23.33 | 7.33 | 23.28 |
June | 48.50 | 24.24 | 350.00 | 24.34 | 35.83 | 24.35 |
July | 95.00 | 24.39 | 382.67 | 24.44 | 87.83 | 24.44 |
August | 69.00 | 23.69 | 303.50 | 24.19 | 25.00 | 24.18 |
September | 205.50 | 23.16 | 98.50 | 23.60 | 2.33 | 23.58 |
October | 493.50 | 21.97 | 107.17 | 21.66 | 107.17 | 21.45 |
November | 488.50 | 21.16 | 227.83 | 20.93 | 227.83 | 20.80 |
December | 497.00 | 20.40 | 377.17 | 20.24 | 377.17 | 20.18 |
Annual Sum or Average | 4090.67 | 21.55 | 2799.00 | 21.72 | 1731.50 | 21.48 |
Minimum of Months | 48.50 | 20.40 | 87.67 | 20.24 | 2.33 | 20.18 |
Maximum of Months | 513.50 | 24.39 | 382.67 | 24.44 | 377.17 | 24.44 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 413.33 | 21.03 | 182.83 | 20.79 | 182.00 | 20.67 |
February | 354.00 | 20.96 | 185.17 | 20.74 | 172.17 | 20.55 |
March | 356.17 | 21.43 | 149.17 | 21.31 | 119.17 | 21.08 |
April | 315.33 | 21.37 | 135.67 | 21.27 | 97.83 | 21.01 |
May | 185.50 | 22.74 | 148.67 | 23.50 | 8.00 | 23.51 |
June | 62.00 | 25.12 | 331.17 | 24.57 | 48.83 | 24.69 |
July | 121.17 | 25.16 | 357.00 | 24.76 | 108.17 | 24.88 |
August | 89.00 | 24.37 | 310.83 | 24.42 | 49.33 | 24.54 |
September | 156.50 | 23.23 | 168.33 | 23.97 | 17.00 | 24.11 |
October | 341.00 | 21.74 | 123.00 | 21.80 | 87.50 | 21.64 |
November | 388.00 | 21.28 | 145.17 | 21.13 | 138.17 | 20.99 |
December | 416.50 | 20.61 | 267.17 | 20.37 | 267.17 | 20.27 |
Annual Sum or Average | 3198.50 | 21.69 | 2504.17 | 22.12 | 1295.33 | 21.94 |
Minimum of Months | 62.00 | 20.61 | 123.00 | 20.37 | 8.00 | 20.27 |
Maximum of Months | 416.50 | 25.16 | 357.00 | 24.76 | 267.17 | 24.88 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 323.83 | 22.29 | 238.67 | 22.73 | 116.50 | 22.64 |
February | 282.50 | 21.64 | 246.50 | 22.05 | 130.83 | 21.80 |
March | 342.50 | 21.81 | 210.83 | 22.03 | 112.17 | 21.81 |
April | 341.33 | 21.45 | 154.00 | 21.43 | 94.83 | 21.15 |
May | 230.83 | 22.78 | 139.67 | 23.35 | 7.17 | 23.31 |
June | 94.50 | 24.08 | 335.17 | 24.30 | 45.83 | 24.36 |
July | 126.50 | 24.49 | 382.50 | 24.47 | 95.00 | 24.53 |
August | 91.67 | 24.45 | 382.33 | 24.42 | 48.67 | 24.52 |
September | 147.33 | 24.02 | 270.33 | 24.40 | 37.67 | 24.59 |
October | 312.33 | 22.48 | 235.00 | 22.94 | 105.17 | 22.88 |
November | 304.83 | 22.47 | 240.67 | 22.99 | 113.33 | 22.94 |
December | 351.33 | 21.65 | 268.83 | 21.81 | 185.50 | 21.60 |
Annual Sum or Average | 2949.50 | 22.38 | 3104.50 | 22.99 | 1092.67 | 22.87 |
Minimum of Months | 91.67 | 21.45 | 139.67 | 21.43 | 7.17 | 21.15 |
Maximum of Months | 351.33 | 24.49 | 382.50 | 24.47 | 185.50 | 24.59 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 456.33 | 21.09 | 196.50 | 20.93 | 182.33 | 20.79 |
February | 402.00 | 20.98 | 210.67 | 20.86 | 189.17 | 20.70 |
March | 432.00 | 21.43 | 161.00 | 21.40 | 117.67 | 21.20 |
April | 387.50 | 21.47 | 131.00 | 21.43 | 87.17 | 21.21 |
May | 252.00 | 22.69 | 160.00 | 23.36 | 11.83 | 23.40 |
June | 105.50 | 24.15 | 379.67 | 24.35 | 60.83 | 24.42 |
July | 134.33 | 24.30 | 403.50 | 24.38 | 99.83 | 24.43 |
August | 94.00 | 23.78 | 380.00 | 24.25 | 40.50 | 24.31 |
September | 205.83 | 23.13 | 198.00 | 23.83 | 23.50 | 23.97 |
October | 412.00 | 21.77 | 141.00 | 21.90 | 85.83 | 21.78 |
November | 431.67 | 21.35 | 157.67 | 21.29 | 135.50 | 21.16 |
December | 469.50 | 20.75 | 283.50 | 20.54 | 281.17 | 20.43 |
Annual Sum or Average | 3782.67 | 21.70 | 2802.50 | 22.18 | 1315.33 | 22.00 |
Minimum of Months | 94.00 | 20.75 | 131.00 | 20.54 | 11.83 | 20.43 |
Maximum of Months | 469.50 | 24.30 | 403.50 | 24.38 | 281.17 | 24.43 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.20 | 367.83 | 20.01 | 367.83 | 19.93 |
February | 454.00 | 20.30 | 356.67 | 20.17 | 356.67 | 20.12 |
March | 514.00 | 21.14 | 252.17 | 20.78 | 252.17 | 20.59 |
April | 454.67 | 21.10 | 191.50 | 20.63 | 188.33 | 20.36 |
May | 310.67 | 22.62 | 84.50 | 22.78 | 21.50 | 22.67 |
June | 68.83 | 24.11 | 342.67 | 24.30 | 35.50 | 24.34 |
July | 117.83 | 24.31 | 376.50 | 24.40 | 90.00 | 24.42 |
August | 97.83 | 23.42 | 301.33 | 24.06 | 28.50 | 24.06 |
September | 239.83 | 22.81 | 110.67 | 23.19 | 17.33 | 23.08 |
October | 496.33 | 21.36 | 194.50 | 20.99 | 194.50 | 20.78 |
November | 489.00 | 20.58 | 323.83 | 20.34 | 323.83 | 20.24 |
December | 497.00 | 20.02 | 438.17 | 19.93 | 438.17 | 19.89 |
Annual Sum or Average | 4242.00 | 21.16 | 3340.33 | 21.29 | 2314.33 | 21.04 |
Minimum of Months | 68.83 | 20.02 | 84.50 | 19.93 | 17.33 | 19.89 |
Maximum of Months | 514.00 | 24.31 | 438.17 | 24.40 | 438.17 | 24.42 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 493.17 | 20.60 | 276.17 | 20.30 | 276.17 | 20.16 |
February | 425.17 | 20.78 | 231.17 | 20.45 | 229.83 | 20.29 |
March | 411.83 | 21.23 | 202.50 | 21.01 | 176.33 | 20.78 |
April | 357.33 | 20.90 | 198.50 | 20.73 | 150.50 | 20.40 |
May | 211.17 | 22.44 | 183.17 | 23.22 | 15.33 | 23.16 |
June | 76.33 | 25.02 | 408.00 | 24.48 | 56.33 | 24.61 |
July | 141.67 | 24.97 | 432.50 | 24.63 | 119.83 | 24.75 |
August | 99.83 | 24.15 | 395.67 | 24.30 | 51.00 | 24.40 |
September | 175.17 | 23.05 | 229.67 | 23.79 | 24.67 | 23.84 |
October | 396.00 | 21.44 | 178.83 | 21.31 | 147.33 | 21.09 |
November | 467.00 | 20.96 | 227.17 | 20.68 | 226.83 | 20.53 |
December | 497.00 | 20.33 | 353.50 | 20.11 | 353.50 | 20.02 |
Annual Sum or Average | 3751.67 | 21.38 | 3316.83 | 21.79 | 1827.67 | 21.55 |
Minimum of Months | 76.33 | 20.33 | 178.83 | 20.11 | 15.33 | 20.02 |
Maximum of Months | 497.00 | 25.02 | 432.50 | 24.63 | 353.50 | 24.75 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 337.50 | 21.42 | 275.67 | 21.70 | 169.67 | 21.45 |
February | 299.00 | 21.14 | 265.83 | 21.45 | 162.67 | 21.18 |
March | 356.83 | 21.42 | 253.83 | 21.54 | 166.17 | 21.30 |
April | 354.17 | 20.87 | 205.50 | 20.75 | 149.17 | 20.42 |
May | 260.50 | 22.34 | 143.33 | 22.86 | 23.67 | 22.75 |
June | 114.83 | 23.83 | 331.83 | 24.21 | 45.17 | 24.29 |
July | 149.33 | 24.25 | 375.33 | 24.38 | 98.17 | 24.46 |
August | 115.67 | 23.97 | 369.00 | 24.28 | 49.00 | 24.38 |
September | 169.17 | 23.54 | 259.00 | 24.09 | 43.33 | 24.24 |
October | 329.50 | 21.91 | 271.67 | 22.25 | 152.17 | 22.08 |
November | 317.67 | 21.78 | 270.67 | 22.16 | 151.67 | 21.96 |
December | 377.67 | 21.10 | 296.83 | 21.15 | 224.67 | 20.91 |
Annual Sum or Average | 3181.83 | 21.88 | 3318.50 | 22.43 | 1435.50 | 22.21 |
Minimum of Months | 114.83 | 20.87 | 143.33 | 20.75 | 23.67 | 20.42 |
Maximum of Months | 377.67 | 24.25 | 375.33 | 24.38 | 224.67 | 24.46 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 468.00 | 20.65 | 283.67 | 20.44 | 274.50 | 20.32 |
February | 409.17 | 20.71 | 267.00 | 20.57 | 248.83 | 20.43 |
March | 435.33 | 21.13 | 225.17 | 21.06 | 184.17 | 20.87 |
April | 391.33 | 20.97 | 188.17 | 20.82 | 143.50 | 20.54 |
May | 282.50 | 22.35 | 158.33 | 23.00 | 21.67 | 23.00 |
June | 129.67 | 23.83 | 370.00 | 24.24 | 61.67 | 24.32 |
July | 156.00 | 24.06 | 391.17 | 24.29 | 102.00 | 24.35 |
August | 123.33 | 23.45 | 365.83 | 24.12 | 45.00 | 24.17 |
September | 238.83 | 22.88 | 194.67 | 23.55 | 32.67 | 23.66 |
October | 415.00 | 21.30 | 203.83 | 21.35 | 151.00 | 21.17 |
November | 442.00 | 20.98 | 236.83 | 20.84 | 217.67 | 20.69 |
December | 478.33 | 20.44 | 339.83 | 20.22 | 339.67 | 20.13 |
Annual Sum or Average | 3969.50 | 21.40 | 3224.50 | 21.78 | 1822.33 | 21.56 |
Minimum of Months | 123.33 | 20.44 | 158.33 | 20.22 | 21.67 | 20.13 |
Maximum of Months | 478.33 | 24.06 | 391.17 | 24.29 | 339.67 | 24.35 |
Report: ComfortReportSimple55Monthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 7.00 | 27.00 | 502.00 | 27.00 | 7.00 | 27.00 |
February | 14.67 | 27.00 | 454.00 | 27.00 | 14.67 | 27.00 |
March | 25.00 | 27.00 | 514.00 | 27.00 | 25.00 | 27.00 |
April | 44.67 | 27.00 | 485.00 | 27.00 | 44.67 | 27.00 |
May | 4.17 | 27.00 | 508.00 | 27.00 | 4.17 | 27.00 |
June | 81.17 | 27.00 | 496.00 | 27.00 | 81.17 | 27.00 |
July | 168.00 | 27.00 | 497.00 | 27.00 | 168.00 | 27.00 |
August | 270.17 | 27.17 | 514.00 | 27.11 | 270.17 | 27.13 |
September | 16.83 | 27.00 | 485.00 | 27.00 | 16.83 | 27.00 |
October | 25.00 | 27.00 | 502.00 | 27.00 | 25.00 | 27.00 |
November | 30.67 | 27.00 | 489.00 | 27.00 | 30.67 | 27.00 |
December | 22.33 | 27.00 | 497.00 | 27.00 | 22.33 | 27.00 |
Annual Sum or Average | 709.67 | 27.06 | 5943.00 | 27.01 | 709.67 | 27.02 |
Minimum of Months | 4.17 | 27.00 | 454.00 | 27.00 | 4.17 | 27.00 |
Maximum of Months | 270.17 | 27.17 | 514.00 | 27.11 | 270.17 | 27.13 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.50 | 27.00 | 443.83 | 27.00 | 0.50 | 27.00 |
February | 5.00 | 27.00 | 400.83 | 27.00 | 5.00 | 27.00 |
March | 7.17 | 27.00 | 489.50 | 27.00 | 7.17 | 27.00 |
April | 7.67 | 27.00 | 470.50 | 27.00 | 7.67 | 27.00 |
May | 1.33 | 27.00 | 508.00 | 27.00 | 1.33 | 27.00 |
June | 19.67 | 27.00 | 496.00 | 27.00 | 19.67 | 27.00 |
July | 15.50 | 27.00 | 497.00 | 27.00 | 15.50 | 27.00 |
August | 67.83 | 27.46 | 514.00 | 27.11 | 67.83 | 27.15 |
September | 5.67 | 27.00 | 485.00 | 27.00 | 5.67 | 27.00 |
October | 9.00 | 27.00 | 494.67 | 27.00 | 9.00 | 27.00 |
November | 5.17 | 27.00 | 483.17 | 27.00 | 5.17 | 27.00 |
December | 11.67 | 27.00 | 413.50 | 27.00 | 0.00 | 27.00 |
Annual Sum or Average | 156.17 | 27.20 | 5696.00 | 27.01 | 144.50 | 27.02 |
Minimum of Months | 0.50 | 27.00 | 400.83 | 27.00 | 0.00 | 27.00 |
Maximum of Months | 67.83 | 27.46 | 514.00 | 27.11 | 67.83 | 27.15 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 80.00 | 24.97 | 334.83 | 26.57 | 4.67 | 26.54 |
February | 28.00 | 27.00 | 304.50 | 27.00 | 3.83 | 27.00 |
March | 28.17 | 27.00 | 447.00 | 27.00 | 8.33 | 27.00 |
April | 22.83 | 27.00 | 422.67 | 27.00 | 9.00 | 27.00 |
May | 5.83 | 26.62 | 501.17 | 27.00 | 3.83 | 27.00 |
June | 52.83 | 27.00 | 496.00 | 27.00 | 52.83 | 27.00 |
July | 51.83 | 27.00 | 497.00 | 27.00 | 51.83 | 27.00 |
August | 89.50 | 27.30 | 514.00 | 27.09 | 89.50 | 27.12 |
September | 10.17 | 27.00 | 484.50 | 27.00 | 10.17 | 27.00 |
October | 11.83 | 27.00 | 430.50 | 27.00 | 9.67 | 27.00 |
November | 4.17 | 27.00 | 413.00 | 27.00 | 3.83 | 27.00 |
December | 37.50 | 27.00 | 295.50 | 27.00 | 0.00 | 27.00 |
Annual Sum or Average | 422.67 | 26.67 | 5140.67 | 26.98 | 247.50 | 26.98 |
Minimum of Months | 4.17 | 24.97 | 295.50 | 26.57 | 0.00 | 26.54 |
Maximum of Months | 89.50 | 27.30 | 514.00 | 27.09 | 89.50 | 27.12 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 469.17 | 27.00 | 502.00 | 27.00 | 469.17 | 27.00 |
February | 454.00 | 27.00 | 454.00 | 27.00 | 454.00 | 27.00 |
March | 514.00 | 27.00 | 514.00 | 27.00 | 514.00 | 27.00 |
April | 485.00 | 27.00 | 485.00 | 27.00 | 485.00 | 27.00 |
May | 487.00 | 27.00 | 508.00 | 27.00 | 487.00 | 27.00 |
June | 496.00 | 27.00 | 496.00 | 27.00 | 496.00 | 27.00 |
July | 497.00 | 27.02 | 497.00 | 27.02 | 497.00 | 27.02 |
August | 514.00 | 28.56 | 514.00 | 28.56 | 514.00 | 28.56 |
September | 485.00 | 27.00 | 485.00 | 27.00 | 485.00 | 27.00 |
October | 502.00 | 27.00 | 502.00 | 27.00 | 502.00 | 27.00 |
November | 489.00 | 27.00 | 489.00 | 27.00 | 489.00 | 27.00 |
December | 497.00 | 27.00 | 497.00 | 27.00 | 497.00 | 27.00 |
Annual Sum or Average | 5889.17 | 27.14 | 5943.00 | 27.14 | 5889.17 | 27.14 |
Minimum of Months | 454.00 | 27.00 | 454.00 | 27.00 | 454.00 | 27.00 |
Maximum of Months | 514.00 | 28.56 | 514.00 | 28.56 | 514.00 | 28.56 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 27.00006 | 18.48013 | 0.74028 | 16.71003 |
February | 454.00000 | 27.00002 | 17.24345 | 0.76592 | 17.55096 |
March | 514.00000 | 27.00004 | 17.56434 | 0.82970 | 19.65042 |
April | 485.00000 | 27.00005 | 19.56172 | 0.88624 | 21.68901 |
May | 508.00000 | 27.00041 | 22.05427 | 0.17268 | 5.75580 |
June | 496.00000 | 27.00056 | 24.01843 | 0.28828 | 6.84348 |
July | 497.00000 | 27.00038 | 24.58470 | 0.33057 | 7.36601 |
August | 514.00000 | 27.08755 | 24.35960 | 0.40184 | 8.69280 |
September | 485.00000 | 27.00030 | 22.00757 | 0.19860 | 5.99764 |
October | 502.00000 | 27.00011 | 19.08326 | 0.82159 | 19.37999 |
November | 489.00000 | 27.00006 | 19.80402 | 0.84347 | 20.14324 |
December | 497.00000 | 26.99999 | 14.68977 | 0.80386 | 18.80894 |
Annual Sum or Average | 5943.00000 | 27.00774 | 20.31224 | 0.58858 | 14.00960 |
Minimum of Months | 454.00000 | 26.99999 | 14.68977 | 0.17268 | 5.75580 |
Maximum of Months | 514.00000 | 27.08755 | 24.58470 | 0.88624 | 21.68901 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 26.99911 | 18.49560 | 0.64335 | 13.95066 |
February | 454.00000 | 27.00002 | 17.22972 | 0.64170 | 13.95804 |
March | 514.00000 | 27.00004 | 17.55359 | 0.69643 | 15.44753 |
April | 485.00000 | 27.00006 | 19.55102 | 0.73336 | 16.57490 |
May | 508.00000 | 27.00037 | 22.08857 | 0.08806 | 5.38874 |
June | 496.00000 | 27.00058 | 24.03865 | 0.20545 | 6.05718 |
July | 497.00000 | 27.00042 | 24.59938 | 0.22467 | 6.19527 |
August | 514.00000 | 27.06439 | 24.38372 | 0.26370 | 6.78764 |
September | 485.00000 | 27.00029 | 22.03219 | 0.12018 | 5.55833 |
October | 502.00000 | 27.00010 | 19.07108 | 0.71803 | 16.08149 |
November | 489.00000 | 27.00005 | 19.79260 | 0.70280 | 15.58819 |
December | 497.00000 | 26.99999 | 14.67639 | 0.61922 | 13.35646 |
Annual Sum or Average | 5943.00000 | 27.00566 | 20.31755 | 0.46979 | 11.21626 |
Minimum of Months | 454.00000 | 26.99911 | 14.67639 | 0.08806 | 5.38874 |
Maximum of Months | 514.00000 | 27.06439 | 24.59938 | 0.73336 | 16.57490 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 26.64872 | 18.92848 | 0.50124 | 11.85000 |
February | 454.00000 | 27.00006 | 17.24006 | 0.57944 | 12.51301 |
March | 514.00000 | 27.00004 | 17.56727 | 0.64808 | 14.26627 |
April | 485.00000 | 27.00007 | 19.56012 | 0.68284 | 15.34533 |
May | 508.00000 | 26.99569 | 22.11737 | 0.05675 | 5.53956 |
June | 496.00000 | 27.00058 | 24.03985 | 0.21442 | 6.24753 |
July | 497.00000 | 27.00042 | 24.59908 | 0.23143 | 6.35814 |
August | 514.00000 | 27.05419 | 24.39407 | 0.26374 | 6.89383 |
September | 485.00000 | 27.00028 | 22.04437 | 0.10407 | 5.66975 |
October | 502.00000 | 27.00010 | 19.09656 | 0.66266 | 14.65373 |
November | 489.00000 | 27.00006 | 19.80678 | 0.63398 | 13.78453 |
December | 497.00000 | 26.99999 | 14.68264 | 0.54778 | 11.74889 |
Annual Sum or Average | 5943.00000 | 26.97478 | 20.36510 | 0.42573 | 10.38315 |
Minimum of Months | 454.00000 | 26.64872 | 14.68264 | 0.05675 | 5.53956 |
Maximum of Months | 514.00000 | 27.05419 | 24.59908 | 0.68284 | 15.34533 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 27.00051 | 29.11837 | 1.04341 | 28.00293 |
February | 454.00000 | 27.00060 | 26.45326 | 1.17498 | 34.06154 |
March | 514.00000 | 27.00042 | 20.65524 | 1.28242 | 39.38782 |
April | 485.00000 | 27.00146 | 21.93674 | 1.43263 | 47.27162 |
May | 508.00000 | 27.00051 | 27.73678 | 0.47544 | 9.78292 |
June | 496.00000 | 27.00401 | 30.89050 | 0.75011 | 16.91042 |
July | 497.00000 | 27.01539 | 31.32524 | 0.95443 | 24.31372 |
August | 514.00000 | 28.55995 | 25.77204 | 1.52897 | 50.39663 |
September | 485.00000 | 27.00181 | 27.08726 | 0.53749 | 11.15430 |
October | 502.00000 | 27.00049 | 24.45119 | 1.20885 | 35.70375 |
November | 489.00000 | 27.00060 | 23.93947 | 1.33780 | 42.24445 |
December | 497.00000 | 27.00005 | 17.80188 | 1.40145 | 45.59795 |
Annual Sum or Average | 5943.00000 | 27.13707 | 25.58918 | 1.09427 | 32.08672 |
Minimum of Months | 454.00000 | 27.00005 | 17.80188 | 0.47544 | 9.78292 |
Maximum of Months | 514.00000 | 28.55995 | 31.32524 | 1.52897 | 50.39663 |
Report: OccupantComfortDataSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.46496 | 17.17453 | 0.31520 | 7.50982 |
February | 454.00000 | 24.45502 | 15.89297 | 0.30099 | 7.33482 |
March | 514.00000 | 24.36703 | 15.82253 | 0.29177 | 7.06954 |
April | 485.00000 | 24.46233 | 19.80335 | 0.34273 | 7.87885 |
May | 508.00000 | 24.48930 | 24.28815 | -0.4674 | 10.55225 |
June | 496.00000 | 24.47748 | 33.83230 | -0.3826 | 9.08594 |
July | 497.00000 | 24.62562 | 36.38819 | -0.3215 | 8.37976 |
August | 514.00000 | 24.49266 | 34.44706 | -0.3588 | 8.78565 |
September | 485.00000 | 24.56802 | 24.29191 | -0.4160 | 9.86924 |
October | 502.00000 | 24.59717 | 18.13255 | 0.37401 | 8.64814 |
November | 489.00000 | 24.58480 | 18.70050 | 0.37237 | 8.57019 |
December | 497.00000 | 24.46891 | 12.54915 | 0.29284 | 7.31780 |
Annual Sum or Average | 5943.00000 | 24.50424 | 22.67372 | 0.02579 | 8.42308 |
Minimum of Months | 454.00000 | 24.36703 | 12.54915 | -0.4674 | 7.06954 |
Maximum of Months | 514.00000 | 24.62562 | 36.38819 | 0.37401 | 10.55225 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.18099 | 18.93156 | 0.25924 | 6.60060 |
February | 454.00000 | 24.19383 | 17.35072 | 0.25249 | 6.57509 |
March | 514.00000 | 24.21507 | 17.02220 | 0.27663 | 6.74757 |
April | 485.00000 | 24.36876 | 21.08384 | 0.34256 | 7.78247 |
May | 508.00000 | 24.29853 | 25.36670 | -0.4998 | 10.72169 |
June | 496.00000 | 24.25799 | 35.11234 | -0.4066 | 8.87744 |
July | 497.00000 | 24.31603 | 37.55159 | -0.3667 | 8.26491 |
August | 514.00000 | 24.24750 | 36.12037 | -0.3850 | 8.49598 |
September | 485.00000 | 24.32105 | 25.73045 | -0.4705 | 10.22543 |
October | 502.00000 | 24.34833 | 19.23759 | 0.32569 | 7.51199 |
November | 489.00000 | 24.32444 | 19.87681 | 0.32148 | 7.40285 |
December | 497.00000 | 24.26634 | 13.68858 | 0.25274 | 6.58886 |
Annual Sum or Average | 5943.00000 | 24.27827 | 23.98561 | -0.0109 | 7.99104 |
Minimum of Months | 454.00000 | 24.18099 | 13.68858 | -0.4998 | 6.57509 |
Maximum of Months | 514.00000 | 24.36876 | 37.55159 | 0.34256 | 10.72169 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.44178 | 20.63452 | 0.05567 | 5.91467 |
February | 454.00000 | 23.28229 | 18.92270 | 0.00369 | 6.12442 |
March | 514.00000 | 23.58815 | 18.44691 | 0.08917 | 5.89309 |
April | 485.00000 | 23.76953 | 22.90067 | 0.15941 | 6.01517 |
May | 508.00000 | 24.14970 | 26.01400 | -0.5860 | 12.61196 |
June | 496.00000 | 24.17907 | 35.39111 | -0.4700 | 9.94858 |
July | 497.00000 | 24.21267 | 37.78487 | -0.4428 | 9.44192 |
August | 514.00000 | 24.21454 | 35.90623 | -0.4550 | 9.66028 |
September | 485.00000 | 24.18234 | 26.13431 | -0.5507 | 11.82446 |
October | 502.00000 | 23.93029 | 20.41144 | 0.19467 | 6.17805 |
November | 489.00000 | 23.67509 | 21.77359 | 0.12732 | 5.77916 |
December | 497.00000 | 23.04982 | 15.78782 | -0.0784 | 6.71530 |
Annual Sum or Average | 5943.00000 | 23.81047 | 25.06436 | -0.1646 | 8.02544 |
Minimum of Months | 454.00000 | 23.04982 | 15.78782 | -0.5860 | 5.77916 |
Maximum of Months | 514.00000 | 24.21454 | 37.78487 | 0.19467 | 12.61196 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.89780 | 22.49979 | -0.3352 | 10.87450 |
February | 454.00000 | 22.05997 | 20.40918 | -0.3092 | 10.06450 |
March | 514.00000 | 22.67698 | 19.76006 | -0.1430 | 8.46918 |
April | 485.00000 | 22.73801 | 23.99422 | -0.0959 | 8.59334 |
May | 508.00000 | 23.82538 | 26.59118 | -0.7044 | 16.60596 |
June | 496.00000 | 24.18158 | 35.28290 | -0.4562 | 9.69997 |
July | 497.00000 | 24.22102 | 37.73376 | -0.4290 | 9.22133 |
August | 514.00000 | 24.19186 | 35.96929 | -0.4531 | 9.62923 |
September | 485.00000 | 24.02488 | 26.30244 | -0.6097 | 13.89171 |
October | 502.00000 | 22.97934 | 21.90173 | -0.0514 | 6.94314 |
November | 489.00000 | 22.39989 | 23.81587 | -0.1989 | 7.62422 |
December | 497.00000 | 21.63236 | 17.03775 | -0.4394 | 12.55149 |
Annual Sum or Average | 5943.00000 | 23.07827 | 25.99195 | -0.3527 | 10.35132 |
Minimum of Months | 454.00000 | 21.63236 | 17.03775 | -0.7044 | 6.94314 |
Maximum of Months | 514.00000 | 24.22102 | 37.73376 | -0.0514 | 16.60596 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.10423 | 20.87277 | -0.2755 | 8.09973 |
February | 454.00000 | 22.06395 | 18.92665 | -0.2940 | 8.68065 |
March | 514.00000 | 22.88493 | 17.95236 | -0.0837 | 6.84938 |
April | 485.00000 | 23.29006 | 21.55402 | 0.05102 | 6.28134 |
May | 508.00000 | 24.05010 | 25.20330 | -0.5986 | 13.60501 |
June | 496.00000 | 24.34318 | 34.17174 | -0.3345 | 8.13977 |
July | 497.00000 | 24.45574 | 36.62004 | -0.2795 | 7.68110 |
August | 514.00000 | 24.27030 | 35.43027 | -0.3666 | 8.51284 |
September | 485.00000 | 24.14357 | 25.43041 | -0.5468 | 12.80691 |
October | 502.00000 | 23.17463 | 20.43873 | 0.00393 | 6.41338 |
November | 489.00000 | 22.69590 | 21.72480 | -0.1168 | 6.46546 |
December | 497.00000 | 22.10012 | 14.98206 | -0.3151 | 9.22054 |
Annual Sum or Average | 5943.00000 | 23.30781 | 24.49593 | -0.2632 | 8.56318 |
Minimum of Months | 454.00000 | 22.06395 | 14.98206 | -0.5986 | 6.28134 |
Maximum of Months | 514.00000 | 24.45574 | 36.62004 | 0.05102 | 13.60501 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.20753 | 19.74552 | -0.2085 | 8.06915 |
February | 454.00000 | 22.22385 | 17.72591 | -0.2043 | 9.25593 |
March | 514.00000 | 22.73310 | 17.26108 | -0.0479 | 8.35241 |
April | 485.00000 | 22.96442 | 21.37777 | 0.04444 | 7.72986 |
May | 508.00000 | 23.95568 | 24.91864 | -0.5218 | 12.98786 |
June | 496.00000 | 24.30884 | 33.98628 | -0.2191 | 7.76569 |
July | 497.00000 | 24.42095 | 36.60770 | -0.1813 | 8.11359 |
August | 514.00000 | 24.13103 | 35.44250 | -0.2845 | 8.85940 |
September | 485.00000 | 24.09639 | 25.12787 | -0.4366 | 11.99778 |
October | 502.00000 | 23.00673 | 19.83173 | 0.02657 | 8.18551 |
November | 489.00000 | 22.48819 | 21.01574 | -0.1193 | 7.61525 |
December | 497.00000 | 21.90869 | 14.20572 | -0.3271 | 9.78807 |
Annual Sum or Average | 5943.00000 | 23.21203 | 23.99580 | -0.2070 | 9.06064 |
Minimum of Months | 454.00000 | 21.90869 | 14.20572 | -0.5218 | 7.61525 |
Maximum of Months | 514.00000 | 24.42095 | 36.60770 | 0.04444 | 12.98786 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.23289 | 18.47026 | 0.10782 | 10.11129 |
February | 454.00000 | 23.00735 | 16.80033 | 0.04213 | 10.93052 |
March | 514.00000 | 23.08588 | 16.90909 | 0.05671 | 9.51551 |
April | 485.00000 | 23.00570 | 21.40083 | 0.03584 | 7.97072 |
May | 508.00000 | 23.87242 | 25.25835 | -0.6115 | 15.04530 |
June | 496.00000 | 24.28141 | 34.21543 | -0.3283 | 8.45282 |
July | 497.00000 | 24.40720 | 36.64510 | -0.2585 | 7.98813 |
August | 514.00000 | 24.28324 | 35.21061 | -0.2658 | 8.07370 |
September | 485.00000 | 24.28286 | 24.81971 | -0.3532 | 11.13539 |
October | 502.00000 | 23.48793 | 19.18254 | 0.19168 | 10.62708 |
November | 489.00000 | 23.51881 | 19.57590 | 0.19894 | 10.56645 |
December | 497.00000 | 23.01870 | 13.22537 | 0.00573 | 10.66334 |
Annual Sum or Average | 5943.00000 | 23.62847 | 23.53961 | -0.0999 | 10.08797 |
Minimum of Months | 454.00000 | 23.00570 | 13.22537 | -0.6115 | 7.97072 |
Maximum of Months | 514.00000 | 24.40720 | 36.64510 | 0.19894 | 15.04530 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.54525 | 19.05926 | -0.0939 | 7.44692 |
February | 454.00000 | 22.79887 | 16.91894 | -0.0277 | 7.90837 |
March | 514.00000 | 23.55312 | 16.19230 | 0.18936 | 7.93585 |
April | 485.00000 | 23.99554 | 19.91102 | 0.33431 | 8.59173 |
May | 508.00000 | 24.13315 | 24.67165 | -0.4312 | 11.30064 |
June | 496.00000 | 24.47072 | 33.65528 | -0.1084 | 7.39302 |
July | 497.00000 | 24.59030 | 36.12937 | -0.0565 | 7.08561 |
August | 514.00000 | 24.46695 | 34.67022 | -0.0662 | 6.99625 |
September | 485.00000 | 24.27315 | 24.85264 | -0.3475 | 10.68899 |
October | 502.00000 | 23.57641 | 18.99076 | 0.20679 | 8.41969 |
November | 489.00000 | 23.50049 | 19.50790 | 0.17030 | 7.55736 |
December | 497.00000 | 23.21111 | 12.89434 | 0.03731 | 7.56833 |
Annual Sum or Average | 5943.00000 | 23.76621 | 23.18129 | -0.0165 | 8.23959 |
Minimum of Months | 454.00000 | 22.54525 | 12.89434 | -0.4312 | 6.99625 |
Maximum of Months | 514.00000 | 24.59030 | 36.12937 | 0.33431 | 11.30064 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.73334 | 22.44849 | -0.6395 | 15.89041 |
February | 454.00000 | 20.67858 | 20.24348 | -0.6705 | 16.66552 |
March | 514.00000 | 21.53686 | 19.70818 | -0.4342 | 12.01010 |
April | 485.00000 | 21.83897 | 23.85593 | -0.3152 | 10.62180 |
May | 508.00000 | 23.59233 | 26.27439 | -0.7770 | 19.76683 |
June | 496.00000 | 24.25891 | 34.20496 | -0.3939 | 8.93830 |
July | 497.00000 | 24.35375 | 36.70541 | -0.3488 | 8.50021 |
August | 514.00000 | 24.15406 | 35.53195 | -0.4558 | 10.07022 |
September | 485.00000 | 23.79242 | 26.04891 | -0.6907 | 17.41722 |
October | 502.00000 | 22.00091 | 22.23858 | -0.2965 | 9.29028 |
November | 489.00000 | 21.16522 | 23.76580 | -0.5149 | 12.13816 |
December | 497.00000 | 20.39773 | 16.38379 | -0.7772 | 20.15462 |
Annual Sum or Average | 5943.00000 | 22.39031 | 25.66727 | -0.5252 | 13.42874 |
Minimum of Months | 454.00000 | 20.39773 | 16.38379 | -0.7772 | 8.50021 |
Maximum of Months | 514.00000 | 24.35375 | 36.70541 | -0.2965 | 20.15462 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 427.00000 | 21.12573 | 20.74948 | -0.5102 | 12.90146 |
February | 385.00000 | 21.23081 | 18.56989 | -0.4886 | 14.64044 |
March | 433.00000 | 21.92570 | 18.01195 | -0.2787 | 11.76741 |
April | 410.00000 | 21.99463 | 22.68663 | -0.2126 | 11.16879 |
May | 430.00000 | 23.61441 | 25.64219 | -0.6599 | 17.99668 |
June | 418.00000 | 24.33399 | 33.65830 | -0.2331 | 8.48001 |
July | 422.00000 | 24.49623 | 36.10446 | -0.1802 | 9.09059 |
August | 433.00000 | 24.21804 | 35.04402 | -0.2926 | 9.71267 |
September | 410.00000 | 23.88052 | 25.28928 | -0.5375 | 15.56472 |
October | 427.00000 | 22.27705 | 20.55395 | -0.1799 | 10.37489 |
November | 417.00000 | 21.49799 | 22.08993 | -0.3981 | 10.94428 |
December | 422.00000 | 20.65646 | 15.02982 | -0.6834 | 17.88975 |
Annual Sum or Average | 5034.00000 | 22.61438 | 24.49638 | -0.3872 | 12.52878 |
Minimum of Months | 385.00000 | 20.65646 | 15.02982 | -0.6834 | 8.48001 |
Maximum of Months | 433.00000 | 24.49623 | 36.10446 | -0.1799 | 17.99668 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.01088 | 18.75550 | 0.05099 | 11.90686 |
February | 454.00000 | 22.67139 | 17.17940 | -0.0494 | 13.68721 |
March | 514.00000 | 22.61512 | 17.64327 | -0.0701 | 11.71555 |
April | 485.00000 | 22.23366 | 22.58847 | -0.1597 | 10.69432 |
May | 508.00000 | 23.57681 | 25.88103 | -0.7224 | 19.20643 |
June | 496.00000 | 24.17640 | 34.27696 | -0.3849 | 9.54428 |
July | 497.00000 | 24.31995 | 36.67527 | -0.3128 | 8.92366 |
August | 514.00000 | 24.24127 | 35.05763 | -0.3114 | 9.07039 |
September | 485.00000 | 24.15717 | 24.94832 | -0.3965 | 12.96710 |
October | 502.00000 | 23.16299 | 19.65016 | 0.10979 | 12.30067 |
November | 489.00000 | 23.18664 | 20.05793 | 0.11045 | 12.12002 |
December | 497.00000 | 22.44282 | 13.82839 | -0.1550 | 13.61886 |
Annual Sum or Average | 5943.00000 | 23.32218 | 23.94082 | -0.1925 | 12.13984 |
Minimum of Months | 454.00000 | 22.23366 | 13.82839 | -0.7224 | 8.92366 |
Maximum of Months | 514.00000 | 24.31995 | 36.67527 | 0.11045 | 19.20643 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.35912 | 20.51626 | -0.4322 | 12.15036 |
February | 454.00000 | 21.34576 | 18.51882 | -0.4425 | 13.55985 |
March | 514.00000 | 21.87093 | 18.27099 | -0.2742 | 11.28233 |
April | 485.00000 | 21.99038 | 22.76072 | -0.2047 | 10.39678 |
May | 508.00000 | 23.46275 | 25.87225 | -0.7014 | 19.77457 |
June | 496.00000 | 24.18674 | 34.22126 | -0.2773 | 9.43279 |
July | 497.00000 | 24.25027 | 36.82787 | -0.2708 | 8.81012 |
August | 514.00000 | 24.13787 | 35.35758 | -0.3188 | 9.57749 |
September | 485.00000 | 23.73915 | 25.66528 | -0.5741 | 16.81736 |
October | 502.00000 | 22.20610 | 20.79091 | -0.1677 | 9.92549 |
November | 489.00000 | 21.67593 | 21.93895 | -0.3304 | 10.12444 |
December | 497.00000 | 20.93766 | 14.95367 | -0.5933 | 16.07526 |
Annual Sum or Average | 5943.00000 | 22.60839 | 24.69727 | -0.3819 | 12.31736 |
Minimum of Months | 454.00000 | 20.93766 | 14.95367 | -0.7014 | 8.81012 |
Maximum of Months | 514.00000 | 24.25027 | 36.82787 | -0.1677 | 19.77457 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.19813 | 23.11657 | -0.8173 | 22.16079 |
February | 454.00000 | 20.29600 | 20.72320 | -0.8077 | 21.26725 |
March | 514.00000 | 21.14336 | 20.00962 | -0.5605 | 15.31592 |
April | 485.00000 | 21.28551 | 24.66077 | -0.4698 | 15.20011 |
May | 508.00000 | 23.20044 | 26.86731 | -0.9129 | 25.71713 |
June | 496.00000 | 24.20983 | 34.23952 | -0.3991 | 9.36923 |
July | 497.00000 | 24.29713 | 36.84876 | -0.3568 | 9.03806 |
August | 514.00000 | 24.05496 | 35.83836 | -0.4786 | 11.01948 |
September | 485.00000 | 23.53965 | 26.31218 | -0.7766 | 21.30728 |
October | 502.00000 | 21.39088 | 22.88783 | -0.4702 | 13.08756 |
November | 489.00000 | 20.57872 | 24.50066 | -0.6958 | 17.91966 |
December | 497.00000 | 20.01521 | 16.64221 | -0.9224 | 25.74110 |
Annual Sum or Average | 5943.00000 | 22.03337 | 26.10256 | -0.6376 | 17.22226 |
Minimum of Months | 454.00000 | 20.01521 | 16.64221 | -0.9224 | 9.03806 |
Maximum of Months | 514.00000 | 24.29713 | 36.84876 | -0.3568 | 25.74110 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.65698 | 21.72976 | -0.6556 | 17.57728 |
February | 454.00000 | 20.98846 | 19.22327 | -0.5783 | 16.92095 |
March | 514.00000 | 21.81295 | 18.46791 | -0.3292 | 13.20252 |
April | 485.00000 | 21.73833 | 23.35145 | -0.2895 | 14.39502 |
May | 508.00000 | 23.45746 | 25.75893 | -0.7074 | 19.85780 |
June | 496.00000 | 24.27176 | 33.78868 | -0.2149 | 8.21309 |
July | 497.00000 | 24.39816 | 36.46286 | -0.1745 | 8.91007 |
August | 514.00000 | 24.14306 | 35.12874 | -0.2753 | 9.48659 |
September | 485.00000 | 23.78842 | 25.34561 | -0.5483 | 16.08244 |
October | 502.00000 | 22.04140 | 21.12334 | -0.2627 | 12.05775 |
November | 489.00000 | 21.10318 | 22.94322 | -0.5244 | 14.12909 |
December | 497.00000 | 20.33033 | 15.74451 | -0.7988 | 21.92939 |
Annual Sum or Average | 5943.00000 | 22.40786 | 24.97348 | -0.4454 | 14.36992 |
Minimum of Months | 454.00000 | 20.33033 | 15.74451 | -0.7988 | 8.21309 |
Maximum of Months | 514.00000 | 24.39816 | 36.46286 | -0.1745 | 21.92939 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.35493 | 19.63998 | -0.1494 | 13.80163 |
February | 454.00000 | 22.20154 | 17.87679 | -0.2010 | 15.22870 |
March | 514.00000 | 22.25869 | 18.05849 | -0.1871 | 13.40842 |
April | 485.00000 | 21.73742 | 23.46694 | -0.3012 | 14.80767 |
May | 508.00000 | 23.24555 | 26.38142 | -0.8409 | 24.30357 |
June | 496.00000 | 24.08864 | 34.40761 | -0.4003 | 10.46229 |
July | 497.00000 | 24.23230 | 36.88706 | -0.3293 | 9.82894 |
August | 514.00000 | 24.13332 | 35.37258 | -0.3360 | 10.08231 |
September | 485.00000 | 23.96584 | 25.13276 | -0.4639 | 15.56997 |
October | 502.00000 | 22.70093 | 20.28310 | -0.0321 | 13.96983 |
November | 489.00000 | 22.67471 | 20.79238 | -0.0536 | 13.13780 |
December | 497.00000 | 21.85757 | 14.42250 | -0.3352 | 16.60949 |
Annual Sum or Average | 5943.00000 | 22.96154 | 24.45367 | -0.3037 | 14.26254 |
Minimum of Months | 454.00000 | 21.73742 | 14.42250 | -0.8409 | 9.82894 |
Maximum of Months | 514.00000 | 24.23230 | 36.88706 | -0.0321 | 24.30357 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.87817 | 21.25242 | -0.5897 | 16.75445 |
February | 454.00000 | 21.04141 | 19.04302 | -0.5535 | 16.48744 |
March | 514.00000 | 21.58811 | 18.59287 | -0.3706 | 13.42157 |
April | 485.00000 | 21.55956 | 23.52282 | -0.3261 | 14.03745 |
May | 508.00000 | 23.17152 | 26.27885 | -0.8046 | 24.26314 |
June | 496.00000 | 24.09926 | 34.35260 | -0.2926 | 10.39830 |
July | 497.00000 | 24.15440 | 37.04813 | -0.2898 | 9.78933 |
August | 514.00000 | 24.01306 | 35.67706 | -0.3482 | 10.75077 |
September | 485.00000 | 23.52964 | 25.85094 | -0.6447 | 19.93311 |
October | 502.00000 | 21.81195 | 21.32969 | -0.2898 | 12.40414 |
November | 489.00000 | 21.27651 | 22.53784 | -0.4638 | 13.34162 |
December | 497.00000 | 20.57959 | 15.40111 | -0.7202 | 20.30991 |
Annual Sum or Average | 5943.00000 | 22.32069 | 25.12865 | -0.4738 | 15.14215 |
Minimum of Months | 454.00000 | 20.57959 | 15.40111 | -0.8046 | 9.78933 |
Maximum of Months | 514.00000 | 24.15440 | 37.04813 | -0.2898 | 24.26314 |
Report: ChillerReportMonthly
For: COOLSYS1 CHILLER1
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportCHILLER ELECTRICITY ENERGY [J] | CHILLER ELECTRICITY RATE {Maximum} [W] | CHILLER ELECTRICITY RATE {TIMESTAMP} | CHILLER ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | CHILLER EVAPORATOR COOLING ENERGY [J] | CHILLER EVAPORATOR COOLING RATE [] | CHILLER CONDENSER HEAT TRANSFER ENERGY [J] | CHILLER COP [W/W] | CHILLER COP {Maximum} [W/W] | CHILLER COP {TIMESTAMP} | CHILLER PART LOAD RATIO [] | CHILLER PART LOAD RATIO [] | |
January | 0.667035E+10 | 100481.54 | 20-JAN-14:20 | 87.76 | 0.397577E+11 | 0.00 | 0.464280E+11 | 0.56 | 7.39 | 20-JAN-14:20 | 0.00 | 0.00 |
February | 0.326971E+10 | 71135.53 | 18-FEB-14:00 | 110.04 | 0.160667E+11 | 0.00 | 0.193364E+11 | 0.71 | 6.73 | 18-FEB-14:00 | 0.00 | 0.00 |
March | 0.174853E+11 | 154446.46 | 14-MAR-14:20 | 149.64 | 0.108578E+12 | 0.00 | 0.126063E+12 | 1.00 | 7.57 | 13-MAR-13:30 | 0.00 | 0.00 |
April | 0.160485E+11 | 116090.79 | 19-APR-13:30 | 149.76 | 0.978378E+11 | 0.00 | 0.113886E+12 | 1.04 | 7.52 | 19-APR-13:30 | 0.00 | 0.00 |
May | 0.551613E+11 | 152604.04 | 18-MAY-14:30 | 280.02 | 0.357090E+12 | 0.00 | 0.412251E+12 | 2.12 | 7.57 | 15-MAY-15:30 | 0.00 | 0.00 |
June | 0.133918E+12 | 156280.13 | 19-JUN-08:20 | 494.24 | 0.932527E+12 | 0.00 | 0.106644E+13 | 4.39 | 7.57 | 14-JUN-17:40 | 0.00 | 0.00 |
July | 0.140470E+12 | 161657.02 | 22-JUL-12:40 | 549.80 | 0.972673E+12 | 0.00 | 0.111314E+13 | 4.62 | 7.57 | 03-JUL-13:10 | 0.00 | 0.00 |
August | 0.133764E+12 | 156705.03 | 04-AUG-14:20 | 576.54 | 0.927901E+12 | 0.00 | 0.106167E+13 | 4.70 | 7.57 | 26-AUG-16:00 | 0.00 | 0.00 |
September | 0.101656E+12 | 155974.55 | 27-SEP-12:30 | 400.95 | 0.692891E+12 | 0.00 | 0.794546E+12 | 3.45 | 7.57 | 25-SEP-13:20 | 0.00 | 0.00 |
October | 0.268221E+11 | 149302.03 | 10-OCT-13:00 | 179.51 | 0.171072E+12 | 0.00 | 0.197894E+12 | 1.28 | 7.57 | 11-OCT-11:20 | 0.00 | 0.00 |
November | 0.112291E+11 | 135924.54 | 07-NOV-15:00 | 110.93 | 0.698745E+11 | 0.00 | 0.811036E+11 | 0.76 | 7.57 | 07-NOV-15:00 | 0.00 | 0.00 |
December | 0.673852E+10 | 102838.02 | 01-DEC-14:20 | 96.62 | 0.398105E+11 | 0.00 | 0.465491E+11 | 0.61 | 7.42 | 01-DEC-14:20 | 0.00 | 0.00 |
Annual Sum or Average | 0.653233E+12 | 3185.81 | 0.442608E+13 | 0.00 | 0.507931E+13 | 2.11 | 0.00 | 0.00 | ||||
Minimum of Months | 0.326971E+10 | 71135.53 | 87.76 | 0.160667E+11 | 0.00 | 0.193364E+11 | 0.56 | 6.73 | 0.00 | 0.00 | ||
Maximum of Months | 0.140470E+12 | 161657.02 | 576.54 | 0.972673E+12 | 0.00 | 0.111314E+13 | 4.70 | 7.57 | 0.00 | 0.00 |
Report: ChillerReportMonthly
For: COOLSYS1 CHILLER2
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportCHILLER ELECTRICITY ENERGY [J] | CHILLER ELECTRICITY RATE {Maximum} [W] | CHILLER ELECTRICITY RATE {TIMESTAMP} | CHILLER ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | CHILLER EVAPORATOR COOLING ENERGY [J] | CHILLER EVAPORATOR COOLING RATE [] | CHILLER CONDENSER HEAT TRANSFER ENERGY [J] | CHILLER COP [W/W] | CHILLER COP {Maximum} [W/W] | CHILLER COP {TIMESTAMP} | CHILLER PART LOAD RATIO [] | CHILLER PART LOAD RATIO [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
March | 0.451438E+09 | 97806.82 | 14-MAR-13:40 | 1.50 | 0.316537E+10 | 0.00 | 0.361681E+10 | 0.01 | 7.28 | 13-MAR-14:40 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 |
May | 0.673071E+10 | 108669.02 | 31-MAY-13:30 | 22.00 | 0.482952E+11 | 0.00 | 0.550259E+11 | 0.21 | 7.45 | 31-MAY-13:30 | 0.00 | 0.00 |
June | 0.536357E+11 | 124456.21 | 26-JUN-15:10 | 155.62 | 0.392362E+12 | 0.00 | 0.445998E+12 | 1.57 | 7.55 | 26-JUN-15:10 | 0.00 | 0.00 |
July | 0.505743E+11 | 117893.16 | 18-JUL-15:10 | 147.83 | 0.368750E+12 | 0.00 | 0.419324E+12 | 1.44 | 7.53 | 18-JUL-15:10 | 0.00 | 0.00 |
August | 0.507855E+11 | 121862.55 | 16-AUG-15:10 | 145.89 | 0.372067E+12 | 0.00 | 0.422853E+12 | 1.43 | 7.54 | 21-AUG-09:50 | 0.00 | 0.00 |
September | 0.273926E+11 | 114268.88 | 12-SEP-15:20 | 83.17 | 0.198824E+12 | 0.00 | 0.226217E+12 | 0.83 | 7.51 | 12-SEP-15:20 | 0.00 | 0.00 |
October | 0.253832E+10 | 97904.98 | 11-OCT-11:00 | 8.00 | 0.182527E+11 | 0.00 | 0.207910E+11 | 0.08 | 7.31 | 11-OCT-15:00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.192109E+12 | 564.01 | 0.140172E+13 | 0.00 | 0.159383E+13 | 0.47 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.536357E+11 | 124456.21 | 155.62 | 0.392362E+12 | 0.00 | 0.445998E+12 | 1.57 | 7.55 | 0.00 | 0.00 |
Report: TowerReportMonthly
For: CENTRAL TOWER
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportCOOLING TOWER FAN ELECTRICITY ENERGY [J] | COOLING TOWER FAN ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | COOLING TOWER FAN ELECTRICITY RATE {Maximum} [W] | COOLING TOWER FAN ELECTRICITY RATE {TIMESTAMP} | COOLING TOWER HEAT TRANSFER RATE {Maximum} [W] | COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} | COOLING TOWER INLET TEMPERATURE [C] | COOLING TOWER OUTLET TEMPERATURE [C] | COOLING TOWER MASS FLOW RATE [kg/s] | |
January | 0.474662E+10 | 744.00 | 49248.27 | 19-JAN-13:55 | 62847.60 | 23-JAN-16:10 | 18.83 | 18.35 | 15.82 |
February | 0.537380E+10 | 672.00 | 49248.27 | 18-FEB-11:50 | 118680.53 | 18-FEB-14:00 | 19.36 | 18.34 | 15.82 |
March | 0.188398E+11 | 744.00 | 49248.27 | 08-MAR-12:50 | 446687.60 | 14-MAR-13:10 | 20.42 | 18.59 | 15.82 |
April | 0.270404E+11 | 720.00 | 49248.27 | 06-APR-12:30 | 524242.86 | 19-APR-14:00 | 21.59 | 18.81 | 15.82 |
May | 0.422813E+11 | 744.00 | 49248.27 | 04-MAY-08:20 | 258933.99 | 31-MAY-16:00 | 20.34 | 19.45 | 15.82 |
June | 0.100428E+12 | 720.00 | 49248.27 | 01-JUN-07:50 | 517942.80 | 18-JUN-10:50 | 29.44 | 25.35 | 15.82 |
July | 0.121741E+12 | 744.00 | 49248.27 | 01-JUL-00:03 | 746211.67 | 30-JUL-14:11 | 34.84 | 27.51 | 15.82 |
August | 0.126744E+12 | 744.00 | 49248.27 | 01-AUG-00:10 | 760905.36 | 05-AUG-14:25 | 37.64 | 27.89 | 15.82 |
September | 0.755367E+11 | 720.00 | 49248.27 | 01-SEP-00:05 | 274306.06 | 10-SEP-17:41 | 23.38 | 21.85 | 15.82 |
October | 0.218061E+11 | 744.00 | 49248.27 | 01-OCT-14:31 | 409576.16 | 11-OCT-14:00 | 20.06 | 18.74 | 15.82 |
November | 0.130535E+11 | 720.00 | 49248.27 | 05-NOV-09:42 | 376412.49 | 07-NOV-15:00 | 20.25 | 18.51 | 15.82 |
December | 0.138199E+11 | 744.00 | 49248.27 | 01-DEC-10:20 | 519148.81 | 01-DEC-14:00 | 20.70 | 18.50 | 15.82 |
Annual Sum or Average | 0.571412E+12 | 8760.00 | 23.94 | 21.01 | 15.82 | ||||
Minimum of Months | 0.474662E+10 | 672.00 | 49248.27 | 62847.60 | 18.83 | 18.34 | 15.82 | ||
Maximum of Months | 0.126744E+12 | 744.00 | 49248.27 | 760905.36 | 37.64 | 27.89 | 15.82 |
Report: TowerReportMonthly
For: TOWERWATERSYS COOLTOWER 1
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportCOOLING TOWER FAN ELECTRICITY ENERGY [J] | COOLING TOWER FAN ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | COOLING TOWER FAN ELECTRICITY RATE {Maximum} [W] | COOLING TOWER FAN ELECTRICITY RATE {TIMESTAMP} | COOLING TOWER HEAT TRANSFER RATE {Maximum} [W] | COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} | COOLING TOWER INLET TEMPERATURE [C] | COOLING TOWER OUTLET TEMPERATURE [C] | COOLING TOWER MASS FLOW RATE [kg/s] | |
January | 9738447.57 | 17.33 | 276.00 | 20-JAN-13:10 | 855470.98 | 20-JAN-14:20 | 21.10 | 21.02 | 2.70 |
February | 3396535.45 | 9.65 | 219.03 | 18-FEB-14:00 | 562856.00 | 18-FEB-14:00 | 20.93 | 20.89 | 2.10 |
March | 41477055.99 | 59.81 | 1179.61 | 14-MAR-12:40 | 1309352.67 | 14-MAR-12:40 | 21.14 | 20.94 | 6.40 |
April | 45087340.63 | 61.00 | 822.96 | 20-APR-13:00 | 996834.29 | 19-APR-13:30 | 21.14 | 20.95 | 6.85 |
May | 0.421024E+09 | 194.78 | 17250.03 | 31-MAY-16:10 | 1282023.63 | 18-MAY-13:00 | 21.79 | 21.11 | 18.71 |
June | 0.322357E+10 | 432.38 | 17250.03 | 01-JUN-16:10 | 1310513.48 | 19-JUN-08:20 | 23.11 | 21.22 | 37.93 |
July | 0.548079E+10 | 456.04 | 17250.03 | 10-JUL-16:50 | 1338592.61 | 22-JUL-12:40 | 23.07 | 21.18 | 40.39 |
August | 0.341009E+10 | 427.07 | 17250.03 | 02-AUG-17:00 | 1305425.34 | 22-AUG-15:40 | 22.95 | 21.12 | 39.55 |
September | 0.913804E+09 | 340.43 | 17250.03 | 01-SEP-11:40 | 1318130.80 | 05-SEP-12:30 | 22.63 | 21.21 | 30.26 |
October | 97067988.23 | 92.11 | 1329.95 | 10-OCT-11:00 | 1271779.09 | 10-OCT-11:00 | 21.28 | 20.95 | 9.56 |
November | 28385915.31 | 38.84 | 838.24 | 07-NOV-15:00 | 1175624.79 | 07-NOV-15:00 | 21.05 | 20.92 | 4.47 |
December | 12684515.10 | 25.42 | 356.98 | 01-DEC-14:10 | 878424.69 | 01-DEC-14:20 | 21.00 | 20.92 | 2.95 |
Annual Sum or Average | 0.136871E+11 | 2154.87 | 21.77 | 21.04 | 16.91 | ||||
Minimum of Months | 3396535.45 | 9.65 | 219.03 | 562856.00 | 20.93 | 20.89 | 2.10 | ||
Maximum of Months | 0.548079E+10 | 456.04 | 17250.03 | 1338592.61 | 23.11 | 21.22 | 40.39 |
Report: TowerReportMonthly
For: TOWERWATERSYS COOLTOWER 2
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportCOOLING TOWER FAN ELECTRICITY ENERGY [J] | COOLING TOWER FAN ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | COOLING TOWER FAN ELECTRICITY RATE {Maximum} [W] | COOLING TOWER FAN ELECTRICITY RATE {TIMESTAMP} | COOLING TOWER HEAT TRANSFER RATE {Maximum} [W] | COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} | COOLING TOWER INLET TEMPERATURE [C] | COOLING TOWER OUTLET TEMPERATURE [C] | COOLING TOWER MASS FLOW RATE [kg/s] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 21.10 | 21.10 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 20.93 | 20.93 | 0.00 |
March | 1896547.77 | 0.83 | 944.34 | 14-MAR-13:50 | 1096788.81 | 13-MAR-14:40 | 21.14 | 21.14 | 0.07 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 21.14 | 21.14 | 0.00 |
May | 90002840.11 | 17.67 | 3532.22 | 31-MAY-13:30 | 1154078.15 | 17-MAY-12:10 | 21.79 | 21.68 | 1.39 |
June | 0.132590E+10 | 144.77 | 17250.03 | 15-JUN-13:20 | 1220079.97 | 14-JUN-10:00 | 23.11 | 22.26 | 11.76 |
July | 0.240927E+10 | 135.00 | 17250.03 | 19-JUL-09:10 | 1220265.75 | 14-JUL-14:40 | 23.07 | 22.32 | 10.61 |
August | 0.155019E+10 | 138.28 | 17250.03 | 03-AUG-10:20 | 1220528.18 | 11-AUG-11:20 | 22.95 | 22.16 | 10.87 |
September | 0.221803E+09 | 77.33 | 3723.49 | 01-SEP-12:30 | 1220572.60 | 08-SEP-12:50 | 22.63 | 22.15 | 6.28 |
October | 26928456.60 | 7.83 | 1322.80 | 11-OCT-11:10 | 1156000.52 | 11-OCT-15:00 | 21.28 | 21.23 | 0.62 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 01-NOV-00:05 | 21.05 | 21.05 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 21.00 | 21.00 | 0.00 |
Annual Sum or Average | 0.562599E+10 | 521.71 | 21.77 | 21.52 | 3.48 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 20.93 | 20.93 | 0.00 | ||
Maximum of Months | 0.240927E+10 | 144.77 | 17250.03 | 1220572.60 | 23.11 | 22.32 | 11.76 |
Report: BoilerReportMonthly
For: HEATSYS1 BOILER
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportBOILER HEATING ENERGY [J] | BOILER GAS CONSUMPTION [] | BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] | BOILER HEATING RATE {Maximum} [W] | BOILER HEATING RATE {TIMESTAMP} | BOILER GAS CONSUMPTION RATE [] | BOILER INLET TEMPERATURE [C] | BOILER OUTLET TEMPERATURE [C] | BOILER MASS FLOW RATE [kg/s] | BOILER ANCILLARY ELECTRICITY RATE [W] | BOILER PART LOAD RATIO [] | BOILER PART LOAD RATIO {Maximum} [] | BOILER PART LOAD RATIO {TIMESTAMP} | |
January | 0.224707E+12 | 0.00 | 430.19 | 1396601.25 | 03-JAN-05:01 | 0.00 | 28.29 | 58.58 | 0.42 | 0.00 | 0.03 | 0.52 | 03-JAN-05:01 |
February | 0.249868E+12 | 0.00 | 399.18 | 1843350.51 | 06-FEB-05:01 | 0.00 | 28.19 | 59.22 | 0.52 | 0.00 | 0.04 | 0.68 | 06-FEB-05:01 |
March | 0.153103E+12 | 0.00 | 320.97 | 1696019.32 | 20-MAR-05:01 | 0.00 | 26.06 | 49.15 | 0.27 | 0.00 | 0.02 | 0.63 | 20-MAR-05:01 |
April | 0.898199E+11 | 0.00 | 242.22 | 1380853.91 | 05-APR-04:01 | 0.00 | 25.10 | 43.52 | 0.17 | 0.00 | 0.01 | 0.51 | 05-APR-04:01 |
May | 0.619422E+10 | 0.00 | 57.91 | 1659424.56 | 01-MAY-04:11 | 0.00 | 22.85 | 27.33 | 0.01 | 0.00 | 0.00 | 0.61 | 01-MAY-04:11 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 22.12 | 22.12 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 22.12 | 22.12 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUL-00:03 |
August | 1973425.28 | 0.00 | 1.12 | 2361.84 | 23-AUG-05:10 | 0.00 | 22.12 | 22.21 | 0.00 | 0.00 | 0.00 | 0.00 | 23-AUG-05:10 |
September | 0.397013E+10 | 0.00 | 31.07 | 1291715.35 | 22-SEP-05:02 | 0.00 | 22.36 | 24.86 | 0.01 | 0.00 | 0.00 | 0.48 | 22-SEP-05:02 |
October | 0.114827E+12 | 0.00 | 226.44 | 1535099.78 | 23-OCT-04:01 | 0.00 | 24.10 | 40.87 | 0.21 | 0.00 | 0.02 | 0.57 | 23-OCT-04:01 |
November | 0.175581E+12 | 0.00 | 329.70 | 1421092.06 | 24-NOV-05:01 | 0.00 | 25.53 | 50.51 | 0.33 | 0.00 | 0.03 | 0.52 | 24-NOV-05:01 |
December | 0.389773E+12 | 0.00 | 486.06 | 1876877.49 | 27-DEC-06:01 | 0.00 | 30.01 | 62.86 | 0.81 | 0.00 | 0.05 | 0.69 | 27-DEC-06:01 |
Annual Sum or Average | 0.140785E+13 | 0.00 | 2524.87 | 0.00 | 24.89 | 40.18 | 0.23 | 0.00 | 0.02 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.12 | 22.12 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.389773E+12 | 0.00 | 486.06 | 1876877.49 | 0.00 | 30.01 | 62.86 | 0.81 | 0.00 | 0.05 | 0.69 |
Report: BoilerReportMonthly
For: CENTRAL BOILER
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportBOILER HEATING ENERGY [J] | BOILER GAS CONSUMPTION [] | BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] | BOILER HEATING RATE {Maximum} [W] | BOILER HEATING RATE {TIMESTAMP} | BOILER GAS CONSUMPTION RATE [] | BOILER INLET TEMPERATURE [C] | BOILER OUTLET TEMPERATURE [C] | BOILER MASS FLOW RATE [kg/s] | BOILER ANCILLARY ELECTRICITY RATE [W] | BOILER PART LOAD RATIO [] | BOILER PART LOAD RATIO [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 18.83 | 18.83 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 19.36 | 19.36 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 20.42 | 20.42 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 21.59 | 21.59 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 20.34 | 20.34 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 29.44 | 29.44 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 34.84 | 34.84 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 37.64 | 37.64 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 23.38 | 23.38 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 20.06 | 20.06 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 20.25 | 20.25 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 20.70 | 20.70 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 23.94 | 23.94 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.83 | 18.83 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37.64 | 37.64 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: VAV_BOT WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.360834E+10 | 0.00 | 35.53 | 0.360834E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 64736.05 | 20-JAN-14:00 | 64736.05 | 20-JAN-14:00 | 0.00 | 0.00 | 0.00 |
February | 0.125846E+10 | 0.00 | 22.32 | 0.125846E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 40914.82 | 18-FEB-13:55 | 40914.82 | 18-FEB-13:55 | 0.00 | 0.00 | 0.00 |
March | 0.106820E+11 | 0.00 | 89.14 | 0.106820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 105869.45 | 13-MAR-16:00 | 105869.45 | 13-MAR-16:00 | 0.00 | 0.00 | 0.00 |
April | 0.108314E+11 | 0.00 | 96.44 | 0.108314E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 86248.13 | 19-APR-13:50 | 86248.13 | 19-APR-13:50 | 0.00 | 0.00 | 0.00 |
May | 0.361822E+11 | 0.00 | 253.40 | 0.361822E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 115300.00 | 31-MAY-15:20 | 115300.00 | 31-MAY-15:20 | 0.00 | 0.00 | 0.00 |
June | 0.116996E+12 | 0.00 | 478.29 | 0.116792E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 160122.77 | 26-JUN-15:00 | 160122.77 | 26-JUN-15:00 | 0.00 | 0.00 | 0.00 |
July | 0.123968E+12 | 0.00 | 530.06 | 0.121029E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 151229.84 | 17-JUL-10:20 | 151229.84 | 17-JUL-10:20 | 0.00 | 0.00 | 0.00 |
August | 0.125278E+12 | 0.00 | 563.41 | 0.124508E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 158748.97 | 16-AUG-14:40 | 158748.97 | 16-AUG-14:40 | 0.00 | 0.00 | 0.00 |
September | 0.776261E+11 | 0.00 | 375.33 | 0.776261E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 138098.95 | 12-SEP-15:40 | 138098.95 | 12-SEP-15:40 | 0.00 | 0.00 | 0.00 |
October | 0.169947E+11 | 0.00 | 130.08 | 0.169947E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 125394.35 | 10-OCT-15:50 | 125394.35 | 10-OCT-15:50 | 0.00 | 0.00 | 0.00 |
November | 0.679412E+10 | 0.00 | 57.19 | 0.679412E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 88260.32 | 07-NOV-15:00 | 88260.32 | 07-NOV-15:00 | 0.00 | 0.00 | 0.00 |
December | 0.399240E+10 | 0.00 | 38.01 | 0.399240E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 75149.06 | 01-DEC-13:55 | 75149.06 | 01-DEC-13:55 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.534211E+12 | 0.00 | 2669.20 | 0.530299E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.125846E+10 | 0.00 | 22.32 | 0.125846E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 40914.82 | 40914.82 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.125278E+12 | 0.00 | 563.41 | 0.124508E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 160122.77 | 160122.77 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: VAV_MID WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.310026E+11 | 0.00 | 100.58 | 0.310026E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 538898.64 | 20-JAN-14:10 | 538898.64 | 20-JAN-14:10 | 0.00 | 0.00 | 0.00 |
February | 0.117119E+11 | 0.00 | 108.31 | 0.117119E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 383053.19 | 18-FEB-14:00 | 383053.19 | 18-FEB-14:00 | 0.00 | 0.00 | 0.00 |
March | 0.855252E+11 | 0.00 | 145.36 | 0.855252E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 847605.73 | 13-MAR-15:40 | 847605.73 | 13-MAR-15:40 | 0.00 | 0.00 | 0.00 |
April | 0.724676E+11 | 0.00 | 144.01 | 0.724676E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 641589.51 | 20-APR-13:00 | 641589.51 | 20-APR-13:00 | 0.00 | 0.00 | 0.00 |
May | 0.310742E+12 | 0.00 | 262.64 | 0.310742E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1049601.73 | 31-MAY-15:50 | 1049601.73 | 31-MAY-15:50 | 0.00 | 0.00 | 0.00 |
June | 0.101384E+13 | 0.00 | 452.00 | 0.101209E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 1469172.30 | 26-JUN-14:50 | 1469172.30 | 26-JUN-14:50 | 0.00 | 0.00 | 0.00 |
July | 0.102112E+13 | 0.00 | 457.86 | 0.100124E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 1341152.97 | 24-JUL-15:30 | 1341152.97 | 24-JUL-15:30 | 0.00 | 0.00 | 0.00 |
August | 0.985463E+12 | 0.00 | 448.16 | 0.981803E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1422355.14 | 16-AUG-15:10 | 1422355.14 | 16-AUG-15:10 | 0.00 | 0.00 | 0.00 |
September | 0.684236E+12 | 0.00 | 373.10 | 0.684236E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1294477.73 | 12-SEP-15:50 | 1294477.73 | 12-SEP-15:50 | 0.00 | 0.00 | 0.00 |
October | 0.146134E+12 | 0.00 | 170.18 | 0.146134E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1062231.90 | 11-OCT-15:00 | 1062231.90 | 11-OCT-15:00 | 0.00 | 0.00 | 0.00 |
November | 0.524123E+11 | 0.00 | 106.83 | 0.524123E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 696709.69 | 07-NOV-15:00 | 696709.69 | 07-NOV-15:00 | 0.00 | 0.00 | 0.00 |
December | 0.297373E+11 | 0.00 | 93.74 | 0.297373E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 541067.51 | 01-DEC-14:10 | 541067.51 | 01-DEC-14:10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.444439E+13 | 0.00 | 2862.77 | 0.441911E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.117119E+11 | 0.00 | 93.74 | 0.117119E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 383053.19 | 383053.19 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.102112E+13 | 0.00 | 457.86 | 0.101209E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 1469172.30 | 1469172.30 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: VAV_TOP WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.256010E+10 | 0.00 | 32.67 | 0.256010E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 53588.93 | 20-JAN-14:10 | 53588.93 | 20-JAN-14:10 | 0.00 | 0.00 | 0.00 |
February | 0.105158E+10 | 0.00 | 21.14 | 0.105158E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 40135.44 | 18-FEB-13:55 | 40135.44 | 18-FEB-13:55 | 0.00 | 0.00 | 0.00 |
March | 0.807168E+10 | 0.00 | 82.31 | 0.807168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 86902.07 | 13-MAR-15:40 | 86902.07 | 13-MAR-15:40 | 0.00 | 0.00 | 0.00 |
April | 0.747890E+10 | 0.00 | 88.37 | 0.747890E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 70338.34 | 20-APR-13:00 | 70338.34 | 20-APR-13:00 | 0.00 | 0.00 | 0.00 |
May | 0.320597E+11 | 0.00 | 238.63 | 0.320597E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 127127.86 | 31-MAY-15:20 | 127127.86 | 31-MAY-15:20 | 0.00 | 0.00 | 0.00 |
June | 0.112913E+12 | 0.00 | 445.78 | 0.112789E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 183092.46 | 26-JUN-15:00 | 183092.46 | 26-JUN-15:00 | 0.00 | 0.00 | 0.00 |
July | 0.111448E+12 | 0.00 | 457.14 | 0.109497E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 160093.91 | 17-JUL-14:00 | 160093.91 | 17-JUL-14:00 | 0.00 | 0.00 | 0.00 |
August | 0.108017E+12 | 0.00 | 442.83 | 0.107690E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 171997.97 | 16-AUG-15:00 | 171997.97 | 16-AUG-15:00 | 0.00 | 0.00 | 0.00 |
September | 0.711736E+11 | 0.00 | 360.50 | 0.711736E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 151431.18 | 10-SEP-14:31 | 151431.18 | 10-SEP-14:31 | 0.00 | 0.00 | 0.00 |
October | 0.135552E+11 | 0.00 | 120.88 | 0.135552E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 119202.95 | 11-OCT-15:00 | 119202.95 | 11-OCT-15:00 | 0.00 | 0.00 | 0.00 |
November | 0.451056E+10 | 0.00 | 50.94 | 0.451056E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 69536.78 | 07-NOV-15:00 | 69536.78 | 07-NOV-15:00 | 0.00 | 0.00 | 0.00 |
December | 0.258236E+10 | 0.00 | 35.00 | 0.258236E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 50278.83 | 01-DEC-14:00 | 50278.83 | 01-DEC-14:00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.475421E+12 | 0.00 | 2376.19 | 0.473019E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.105158E+10 | 0.00 | 21.14 | 0.105158E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 40135.44 | 40135.44 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.112913E+12 | 0.00 | 457.14 | 0.112789E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 183092.46 | 183092.46 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: CAV_BAS COOLING COIL
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.119122E+10 | 0.00 | 18.33 | 0.119122E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 34967.27 | 20-JAN-13:55 | 34967.27 | 20-JAN-13:55 | 0.00 | 0.00 | 0.00 |
February | 87731165.80 | 0.00 | 3.50 | 87731165.80 | 0.00 | 0.00 | 0.00 | 0.00 | 11613.53 | 18-FEB-13:00 | 11613.53 | 18-FEB-13:00 | 0.00 | 0.00 | 0.00 |
March | 0.401397E+10 | 0.00 | 47.16 | 0.401397E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 61281.42 | 14-MAR-13:00 | 61281.42 | 14-MAR-13:00 | 0.00 | 0.00 | 0.00 |
April | 0.448175E+10 | 0.00 | 60.20 | 0.448175E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 44718.93 | 20-APR-13:00 | 44718.93 | 20-APR-13:00 | 0.00 | 0.00 | 0.00 |
May | 0.204671E+11 | 0.00 | 170.65 | 0.204575E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 64711.63 | 31-MAY-14:00 | 64711.63 | 31-MAY-14:00 | 0.00 | 0.00 | 0.00 |
June | 0.650860E+11 | 0.00 | 356.91 | 0.650314E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 86188.11 | 26-JUN-15:00 | 86188.11 | 26-JUN-15:00 | 0.00 | 0.00 | 0.00 |
July | 0.660625E+11 | 0.00 | 365.66 | 0.654151E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 114582.14 | 04-JUL-14:27 | 114582.14 | 04-JUL-14:27 | 0.00 | 0.00 | 0.00 |
August | 0.684522E+11 | 0.00 | 382.62 | 0.682785E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 140914.62 | 06-AUG-13:27 | 114789.99 | 20-AUG-16:50 | 0.00 | 0.00 | 0.00 |
September | 0.476710E+11 | 0.00 | 304.62 | 0.476649E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 114604.39 | 10-SEP-16:30 | 114604.39 | 10-SEP-16:30 | 0.00 | 0.00 | 0.00 |
October | 0.814880E+10 | 0.00 | 76.24 | 0.814880E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 75662.14 | 10-OCT-14:00 | 75662.14 | 10-OCT-14:00 | 0.00 | 0.00 | 0.00 |
November | 0.300102E+10 | 0.00 | 32.08 | 0.300102E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 56773.77 | 06-NOV-13:05 | 56773.77 | 06-NOV-13:05 | 0.00 | 0.00 | 0.00 |
December | 0.155603E+10 | 0.00 | 19.89 | 0.155603E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 43367.47 | 01-DEC-14:00 | 43367.47 | 01-DEC-14:00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.290219E+12 | 0.00 | 1837.85 | 0.289328E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 87731165.80 | 0.00 | 3.50 | 87731165.80 | 0.00 | 0.00 | 0.00 | 0.00 | 11613.53 | 11613.53 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.684522E+11 | 0.00 | 382.62 | 0.682785E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 140914.62 | 114789.99 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: AIRLOOP DATACENTER BASEMENT COOLING COIL
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.999590E+10 | 0.556140E+10 | 744.00 | 0.847445E+10 | 0.152145E+10 | 0.00 | 0.03 | 20-JAN-14:00 | 0.01 | 28-JAN-10:55 | 5665.83 | 19-JAN-11:30 | 4962.40 | 23-JAN-17:15 | 784.47 | 19-JAN-11:30 | 2859.66 | 20-JAN-14:00 | 0.00 |
February | 0.142924E+11 | 0.673535E+10 | 672.00 | 0.122221E+11 | 0.207027E+10 | 0.00 | 0.15 | 18-FEB-14:00 | 0.02 | 19-FEB-14:22 | 45253.73 | 18-FEB-13:55 | 45253.73 | 18-FEB-13:55 | 1305.58 | 16-FEB-22:20 | 16816.55 | 18-FEB-13:20 | 0.00 |
March | 0.393196E+11 | 0.164917E+11 | 744.00 | 0.377007E+11 | 0.161893E+10 | 0.00 | 0.76 | 14-MAR-13:00 | 0.02 | 17-MAR-15:00 | 245822.25 | 14-MAR-13:00 | 245822.25 | 14-MAR-13:00 | 2928.16 | 31-MAR-17:50 | 99138.73 | 14-MAR-13:00 | 0.00 |
April | 0.859432E+11 | 0.313467E+11 | 718.83 | 0.803029E+11 | 0.564032E+10 | 0.00 | 0.84 | 19-APR-13:00 | 0.01 | 13-APR-19:10 | 285374.41 | 19-APR-14:00 | 285374.41 | 19-APR-14:00 | 92998.79 | 28-APR-14:00 | 107178.86 | 19-APR-13:10 | 0.00 |
May | 0.281589E+11 | 0.127411E+11 | 673.46 | 0.268488E+11 | 0.131014E+10 | 0.00 | 0.42 | 17-MAY-11:00 | 0.00 | 20-MAY-23:50 | 148756.08 | 31-MAY-16:00 | 140895.16 | 16-MAY-16:00 | 12025.53 | 31-MAY-16:50 | 55932.08 | 17-MAY-14:00 | 0.00 |
June | 0.291414E+12 | 0.111300E+12 | 628.29 | 0.262568E+12 | 0.288460E+11 | 0.00 | 0.77 | 18-JUN-10:50 | 0.00 | 08-JUN-23:10 | 335268.33 | 18-JUN-10:42 | 232708.50 | 26-JUN-14:55 | 118564.50 | 18-JUN-10:31 | 118436.90 | 26-JUN-15:00 | 0.00 |
July | 0.604409E+12 | 0.214863E+12 | 737.40 | 0.495042E+12 | 0.109367E+12 | 0.00 | 1.00 | 29-JUL-12:30 | 0.01 | 12-JUL-00:10 | 462232.64 | 31-JUL-23:05 | 324462.93 | 13-JUL-13:00 | 287833.81 | 31-JUL-23:05 | 155732.94 | 30-JUL-14:00 | 0.00 |
August | 0.821816E+12 | 0.283094E+12 | 744.00 | 0.651974E+12 | 0.169842E+12 | 0.00 | 1.00 | 02-AUG-10:40 | 0.02 | 23-AUG-05:15 | 468917.57 | 04-AUG-01:53 | 411729.33 | 06-AUG-12:06 | 329567.08 | 04-AUG-01:53 | 177276.54 | 16-AUG-16:00 | 0.00 |
September | 0.867252E+11 | 0.348103E+11 | 679.44 | 0.822163E+11 | 0.450887E+10 | 0.00 | 0.43 | 18-SEP-12:40 | 0.00 | 03-SEP-01:10 | 150456.93 | 07-SEP-16:00 | 141866.16 | 18-SEP-12:40 | 20021.33 | 01-SEP-12:00 | 61165.87 | 09-SEP-13:00 | 0.00 |
October | 0.311665E+11 | 0.134567E+11 | 744.00 | 0.293384E+11 | 0.182818E+10 | 0.00 | 0.71 | 11-OCT-14:00 | 0.01 | 03-OCT-13:00 | 234058.92 | 11-OCT-14:00 | 234058.92 | 11-OCT-14:00 | 1563.48 | 31-OCT-23:10 | 97745.87 | 11-OCT-14:00 | 0.00 |
November | 0.312033E+11 | 0.131048E+11 | 720.00 | 0.286959E+11 | 0.250741E+10 | 0.00 | 0.62 | 06-NOV-14:00 | 0.02 | 09-NOV-24:00 | 195531.47 | 07-NOV-15:00 | 195531.47 | 07-NOV-15:00 | 3731.17 | 09-NOV-09:30 | 76020.03 | 06-NOV-14:00 | 0.00 |
December | 0.409576E+11 | 0.170623E+11 | 744.00 | 0.404444E+11 | 0.513218E+09 | 0.00 | 0.85 | 01-DEC-14:00 | 0.03 | 23-DEC-08:35 | 284146.84 | 01-DEC-14:00 | 284146.84 | 01-DEC-14:00 | 1536.71 | 30-DEC-17:10 | 108302.34 | 01-DEC-14:00 | 0.00 |
Annual Sum or Average | 0.208540E+13 | 0.760567E+12 | 8549.42 | 0.175583E+13 | 0.329574E+12 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.999590E+10 | 0.556140E+10 | 628.29 | 0.847445E+10 | 0.513218E+09 | 0.00 | 0.03 | 0.00 | 5665.83 | 4962.40 | 784.47 | 2859.66 | 0.00 | ||||||
Maximum of Months | 0.821816E+12 | 0.283094E+12 | 744.00 | 0.651974E+12 | 0.169842E+12 | 0.00 | 1.00 | 0.03 | 468917.57 | 411729.33 | 329567.08 | 177276.54 | 0.00 |
Report: DXReportMonthly
For: AIRLOOP DATACENTER BOT COOLING COIL
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.475440E+10 | 0.131137E+10 | 744.00 | 0.474523E+10 | 9175038.41 | 0.00 | 0.38 | 23-JAN-16:40 | 0.09 | 05-JAN-07:05 | 3244.27 | 23-JAN-16:40 | 3244.27 | 23-JAN-16:40 | 113.21 | 10-JAN-16:20 | 853.46 | 23-JAN-16:40 | 0.00 |
February | 0.894405E+10 | 0.233403E+10 | 672.00 | 0.894005E+10 | 4001336.26 | 0.00 | 0.56 | 26-FEB-16:52 | 0.30 | 06-FEB-07:10 | 5201.86 | 17-FEB-17:00 | 5184.93 | 17-FEB-17:00 | 88.56 | 28-FEB-16:50 | 1272.32 | 17-FEB-17:00 | 0.00 |
March | 0.155939E+11 | 0.391813E+10 | 744.00 | 0.155824E+11 | 11452433.62 | 0.00 | 0.82 | 13-MAR-17:00 | 0.53 | 20-MAR-06:10 | 7854.81 | 31-MAR-24:00 | 7854.81 | 31-MAR-24:00 | 155.59 | 17-MAR-15:10 | 2254.90 | 13-MAR-17:00 | 0.00 |
April | 0.202017E+11 | 0.487335E+10 | 720.00 | 0.201727E+11 | 28993534.68 | 0.00 | 0.98 | 08-APR-17:55 | 0.29 | 30-APR-24:00 | 9191.39 | 08-APR-18:00 | 9191.39 | 08-APR-18:00 | 263.49 | 28-APR-16:05 | 2599.48 | 19-APR-14:00 | 0.00 |
May | 0.616237E+10 | 0.170225E+10 | 744.00 | 0.610009E+10 | 62280890.73 | 0.00 | 0.46 | 31-MAY-24:00 | 0.18 | 03-MAY-06:10 | 4226.21 | 31-MAY-23:30 | 4201.87 | 31-MAY-24:00 | 223.88 | 22-MAY-14:10 | 1119.91 | 31-MAY-16:00 | 0.00 |
June | 0.115464E+11 | 0.365564E+10 | 720.00 | 0.114262E+11 | 0.120146E+09 | 0.00 | 0.70 | 30-JUN-23:15 | 0.43 | 10-JUN-06:30 | 6073.25 | 30-JUN-24:00 | 6073.25 | 30-JUN-24:00 | 425.61 | 20-JUN-17:00 | 2529.98 | 26-JUN-15:30 | 0.00 |
July | 0.169534E+11 | 0.546977E+10 | 744.00 | 0.168017E+11 | 0.151708E+09 | 0.00 | 0.93 | 01-JUL-18:35 | 0.64 | 13-JUL-06:10 | 7986.74 | 31-JUL-24:00 | 7986.74 | 31-JUL-24:00 | 566.69 | 31-JUL-16:00 | 3241.49 | 16-JUL-13:00 | 0.00 |
August | 0.219906E+11 | 0.690069E+10 | 744.00 | 0.218718E+11 | 0.118761E+09 | 0.00 | 1.00 | 02-AUG-15:10 | 0.31 | 31-AUG-24:00 | 9504.98 | 05-AUG-18:21 | 9466.08 | 05-AUG-18:21 | 505.64 | 29-AUG-14:55 | 3888.18 | 16-AUG-16:00 | 0.00 |
September | 0.629867E+10 | 0.189613E+10 | 720.00 | 0.624982E+10 | 48853397.02 | 0.00 | 0.47 | 10-SEP-17:35 | 0.16 | 22-SEP-06:10 | 4026.20 | 30-SEP-24:00 | 4026.20 | 30-SEP-24:00 | 249.32 | 01-SEP-14:20 | 1486.91 | 10-SEP-17:35 | 0.00 |
October | 0.107705E+11 | 0.280400E+10 | 744.00 | 0.107489E+11 | 21591581.69 | 0.00 | 0.64 | 09-OCT-16:41 | 0.33 | 30-OCT-06:10 | 5721.81 | 09-OCT-16:44 | 5721.81 | 09-OCT-16:44 | 142.69 | 03-OCT-11:00 | 1783.00 | 11-OCT-14:00 | 0.00 |
November | 0.150662E+11 | 0.371906E+10 | 720.00 | 0.150513E+11 | 14812054.73 | 0.00 | 0.81 | 07-NOV-16:00 | 0.54 | 29-NOV-07:10 | 7240.47 | 05-NOV-16:13 | 7240.47 | 05-NOV-16:13 | 141.43 | 09-NOV-16:10 | 2148.69 | 07-NOV-16:00 | 0.00 |
December | 0.201645E+11 | 0.496732E+10 | 744.00 | 0.201645E+11 | 0.00 | 0.00 | 0.96 | 03-DEC-16:00 | 0.72 | 23-DEC-07:05 | 8948.77 | 03-DEC-16:00 | 8948.77 | 03-DEC-16:00 | 0.00 | 16-DEC-09:00 | 2622.06 | 02-DEC-15:00 | 0.00 |
Annual Sum or Average | 0.158447E+12 | 0.435518E+11 | 8760.00 | 0.157855E+12 | 0.591776E+09 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.475440E+10 | 0.131137E+10 | 672.00 | 0.474523E+10 | 0.00 | 0.00 | 0.38 | 0.09 | 3244.27 | 3244.27 | 0.00 | 853.46 | 0.00 | ||||||
Maximum of Months | 0.219906E+11 | 0.690069E+10 | 744.00 | 0.218718E+11 | 0.151708E+09 | 0.00 | 1.00 | 0.72 | 9504.98 | 9466.08 | 566.69 | 3888.18 | 0.00 |
Report: DXReportMonthly
For: AIRLOOP DATACENTER MID COOLING COIL
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.291718E+11 | 0.831318E+10 | 741.11 | 0.290838E+11 | 87938806.92 | 0.00 | 0.36 | 23-JAN-16:40 | 0.00 | 02-JAN-07:10 | 29891.02 | 23-JAN-16:40 | 29891.02 | 23-JAN-16:40 | 1143.74 | 10-JAN-16:20 | 7893.37 | 23-JAN-16:40 | 0.00 |
February | 0.692312E+11 | 0.183749E+11 | 672.00 | 0.691909E+11 | 40227976.78 | 0.00 | 0.55 | 17-FEB-17:00 | 0.15 | 06-FEB-04:17 | 48760.22 | 17-FEB-17:00 | 48506.69 | 17-FEB-17:00 | 883.76 | 28-FEB-16:50 | 11954.49 | 17-FEB-17:00 | 0.00 |
March | 0.134121E+12 | 0.341389E+11 | 744.00 | 0.134007E+12 | 0.114193E+09 | 0.00 | 0.81 | 13-MAR-17:00 | 0.39 | 20-MAR-03:03 | 72920.17 | 31-MAR-23:30 | 72920.17 | 31-MAR-23:30 | 1550.97 | 17-MAR-15:10 | 21429.10 | 13-MAR-17:00 | 0.00 |
April | 0.178743E+12 | 0.436062E+11 | 720.00 | 0.178453E+12 | 0.289526E+09 | 0.00 | 0.96 | 08-APR-17:55 | 0.13 | 30-APR-24:00 | 86526.89 | 08-APR-17:55 | 86526.89 | 08-APR-17:55 | 2611.74 | 28-APR-16:05 | 24419.28 | 19-APR-14:00 | 0.00 |
May | 0.528108E+11 | 0.147509E+11 | 744.00 | 0.522018E+11 | 0.609017E+09 | 0.00 | 0.46 | 31-MAY-23:30 | 0.08 | 01-MAY-06:10 | 39942.56 | 31-MAY-23:20 | 39565.34 | 31-MAY-24:00 | 2236.23 | 22-MAY-14:10 | 10628.20 | 31-MAY-16:00 | 0.00 |
June | 0.108279E+12 | 0.344299E+11 | 720.00 | 0.107088E+12 | 0.119071E+10 | 0.00 | 0.71 | 30-JUN-23:15 | 0.40 | 10-JUN-06:30 | 59187.27 | 30-JUN-24:00 | 59187.27 | 30-JUN-24:00 | 4161.09 | 20-JUN-17:00 | 24283.34 | 26-JUN-18:10 | 0.00 |
July | 0.160362E+12 | 0.518732E+11 | 744.00 | 0.158855E+12 | 0.150691E+10 | 0.00 | 0.94 | 01-JUL-18:35 | 0.60 | 29-JUL-06:10 | 75196.60 | 31-JUL-24:00 | 75196.60 | 31-JUL-24:00 | 5578.85 | 31-JUL-16:00 | 30664.92 | 15-JUL-18:21 | 0.00 |
August | 0.207889E+12 | 0.654431E+11 | 744.00 | 0.206705E+12 | 0.118383E+10 | 0.00 | 1.00 | 10-AUG-14:00 | 0.28 | 31-AUG-24:00 | 90176.10 | 13-AUG-18:34 | 90176.10 | 13-AUG-18:34 | 4980.79 | 29-AUG-14:55 | 37360.37 | 16-AUG-16:00 | 0.00 |
September | 0.555964E+11 | 0.169277E+11 | 720.00 | 0.551200E+11 | 0.476377E+09 | 0.00 | 0.48 | 10-SEP-17:35 | 0.11 | 22-SEP-06:10 | 36293.22 | 30-SEP-23:50 | 36293.22 | 30-SEP-23:50 | 2432.30 | 01-SEP-14:30 | 14378.89 | 10-SEP-17:21 | 0.00 |
October | 0.911660E+11 | 0.240256E+11 | 744.00 | 0.909537E+11 | 0.212248E+09 | 0.00 | 0.61 | 09-OCT-16:41 | 0.20 | 30-OCT-06:10 | 52004.97 | 08-OCT-16:45 | 52004.97 | 08-OCT-16:45 | 1410.64 | 03-OCT-11:00 | 16703.95 | 11-OCT-14:00 | 0.00 |
November | 0.128385E+12 | 0.321206E+11 | 720.00 | 0.128237E+12 | 0.148144E+09 | 0.00 | 0.79 | 07-NOV-16:00 | 0.45 | 02-NOV-06:10 | 67789.66 | 07-NOV-16:20 | 67789.66 | 07-NOV-16:20 | 1363.20 | 09-NOV-16:10 | 20204.25 | 07-NOV-16:00 | 0.00 |
December | 0.169525E+12 | 0.424629E+11 | 744.00 | 0.169525E+12 | -0.0 | 0.00 | 0.92 | 01-DEC-15:50 | 0.58 | 26-DEC-04:01 | 81966.17 | 01-DEC-16:00 | 81966.17 | 01-DEC-16:00 | 0.00 | 09-DEC-05:47 | 24134.62 | 01-DEC-14:10 | 0.00 |
Annual Sum or Average | 0.138528E+13 | 0.386467E+12 | 8757.11 | 0.137942E+13 | 0.585912E+10 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.291718E+11 | 0.831318E+10 | 672.00 | 0.290838E+11 | -0.0 | 0.00 | 0.36 | 0.00 | 29891.02 | 29891.02 | 0.00 | 7893.37 | 0.00 | ||||||
Maximum of Months | 0.207889E+12 | 0.654431E+11 | 744.00 | 0.206705E+12 | 0.150691E+10 | 0.00 | 1.00 | 0.60 | 90176.10 | 90176.10 | 5578.85 | 37360.37 | 0.00 |
Report: DXReportMonthly
For: AIRLOOP DATACENTER TOP COOLING COIL
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.157265E+10 | 0.454407E+09 | 482.37 | 0.156457E+10 | 8074116.03 | 0.00 | 0.35 | 20-JAN-16:40 | 0.00 | 01-JAN-00:05 | 2982.34 | 20-JAN-16:40 | 2982.34 | 20-JAN-16:40 | 114.53 | 10-JAN-16:20 | 779.42 | 20-JAN-16:40 | 0.00 |
February | 0.550741E+10 | 0.148232E+10 | 660.33 | 0.550346E+10 | 3948119.89 | 0.00 | 0.54 | 17-FEB-17:00 | 0.00 | 05-FEB-01:53 | 4882.43 | 17-FEB-17:00 | 4860.71 | 17-FEB-17:00 | 87.32 | 28-FEB-17:00 | 1199.44 | 17-FEB-17:00 | 0.00 |
March | 0.122165E+11 | 0.314323E+10 | 744.00 | 0.122053E+11 | 11279457.08 | 0.00 | 0.81 | 13-MAR-17:00 | 0.23 | 20-MAR-03:01 | 7112.05 | 31-MAR-23:20 | 7112.05 | 31-MAR-23:20 | 154.80 | 17-MAR-15:10 | 2168.35 | 13-MAR-17:00 | 0.00 |
April | 0.166176E+11 | 0.409830E+10 | 719.00 | 0.165887E+11 | 28873101.23 | 0.00 | 0.95 | 08-APR-17:55 | 0.00 | 30-APR-23:10 | 8687.25 | 08-APR-17:55 | 8687.25 | 08-APR-17:55 | 261.76 | 28-APR-16:05 | 2478.46 | 19-APR-14:00 | 0.00 |
May | 0.480355E+10 | 0.135654E+10 | 735.75 | 0.474296E+10 | 60585551.25 | 0.00 | 0.45 | 31-MAY-23:20 | 0.00 | 01-MAY-00:10 | 3959.19 | 31-MAY-23:20 | 3912.25 | 31-MAY-23:40 | 224.94 | 22-MAY-14:00 | 1106.18 | 31-MAY-16:00 | 0.00 |
June | 0.108298E+11 | 0.346160E+10 | 720.00 | 0.107107E+11 | 0.119100E+09 | 0.00 | 0.70 | 30-JUN-23:15 | 0.36 | 10-JUN-06:30 | 5926.13 | 30-JUN-24:00 | 5926.13 | 30-JUN-24:00 | 418.73 | 20-JUN-17:00 | 2489.92 | 26-JUN-18:10 | 0.00 |
July | 0.160469E+11 | 0.521353E+10 | 744.00 | 0.158963E+11 | 0.150590E+09 | 0.00 | 0.95 | 01-JUL-18:35 | 0.57 | 29-JUL-06:10 | 7519.53 | 01-JUL-18:50 | 7519.53 | 01-JUL-18:50 | 560.73 | 31-JUL-16:00 | 3161.12 | 16-JUL-15:00 | 0.00 |
August | 0.207674E+11 | 0.656749E+10 | 744.00 | 0.206492E+11 | 0.118214E+09 | 0.00 | 1.00 | 10-AUG-14:20 | 0.27 | 31-AUG-24:00 | 9156.73 | 13-AUG-18:28 | 9156.73 | 13-AUG-18:28 | 499.29 | 29-AUG-14:55 | 3807.40 | 16-AUG-16:00 | 0.00 |
September | 0.529004E+10 | 0.163062E+10 | 719.75 | 0.524256E+10 | 47478504.27 | 0.00 | 0.50 | 10-SEP-17:21 | 0.00 | 22-SEP-00:35 | 3853.11 | 10-SEP-17:35 | 3853.11 | 10-SEP-17:35 | 245.49 | 01-SEP-14:30 | 1542.00 | 10-SEP-17:21 | 0.00 |
October | 0.789778E+10 | 0.210891E+10 | 743.96 | 0.787682E+10 | 20953986.21 | 0.00 | 0.60 | 11-OCT-16:30 | 0.00 | 29-OCT-17:53 | 5168.71 | 08-OCT-16:45 | 5168.71 | 08-OCT-16:45 | 143.89 | 03-OCT-11:00 | 1692.55 | 11-OCT-14:00 | 0.00 |
November | 0.113190E+11 | 0.287210E+10 | 720.00 | 0.113043E+11 | 14657108.43 | 0.00 | 0.78 | 07-NOV-16:00 | 0.32 | 27-NOV-04:15 | 6813.84 | 07-NOV-16:20 | 6813.84 | 07-NOV-16:20 | 136.05 | 09-NOV-16:10 | 2035.29 | 07-NOV-16:00 | 0.00 |
December | 0.152282E+11 | 0.386675E+10 | 744.00 | 0.152282E+11 | 0.00 | 0.00 | 0.90 | 01-DEC-15:50 | 0.44 | 25-DEC-06:00 | 8170.64 | 01-DEC-16:00 | 8170.64 | 01-DEC-16:00 | 0.00 | 03-DEC-10:05 | 2396.13 | 01-DEC-14:10 | 0.00 |
Annual Sum or Average | 0.128097E+12 | 0.362558E+11 | 8477.16 | 0.127513E+12 | 0.583753E+09 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.157265E+10 | 0.454407E+09 | 482.37 | 0.156457E+10 | 0.00 | 0.00 | 0.35 | 0.00 | 2982.34 | 2982.34 | 0.00 | 779.42 | 0.00 | ||||||
Maximum of Months | 0.207674E+11 | 0.656749E+10 | 744.00 | 0.206492E+11 | 0.150590E+09 | 0.00 | 1.00 | 0.57 | 9156.73 | 9156.73 | 560.73 | 3807.40 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 147.17 | 0.00 | 147.17 | 17.06 | 819.38 | 0.00 | 0.00 | 0.00 |
February | 184.97 | 0.00 | 184.97 | 22.28 | 825.76 | 0.00 | 0.00 | 0.00 |
March | 251.68 | 0.00 | 251.68 | 89.95 | 635.95 | 0.00 | 0.00 | 0.00 |
April | 316.08 | 1.75 | 314.33 | 144.23 | 561.54 | 0.00 | 0.00 | 0.00 |
May | 431.78 | 14.27 | 417.51 | 359.29 | 310.77 | 0.00 | 0.00 | 0.00 |
June | 473.48 | 52.49 | 420.99 | 606.27 | 169.09 | 0.00 | 0.00 | 0.00 |
July | 447.78 | 28.99 | 418.80 | 580.24 | 160.02 | 0.00 | 0.00 | 0.00 |
August | 356.40 | 8.43 | 347.97 | 438.05 | 184.43 | 0.00 | 0.00 | 0.00 |
September | 299.38 | 0.07 | 299.31 | 321.23 | 286.82 | 0.00 | 0.00 | 0.00 |
October | 214.43 | 0.00 | 214.43 | 99.18 | 612.72 | 0.00 | 0.00 | 0.00 |
November | 162.78 | 0.00 | 162.78 | 31.34 | 750.10 | 0.00 | 0.00 | 0.00 |
December | 137.69 | 0.00 | 137.69 | 13.69 | 929.71 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 285.82 | 8.85 | 276.97 | 228.05 | 518.88 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 137.69 | 0.00 | 137.69 | 13.69 | 160.02 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 473.48 | 52.49 | 420.99 | 606.27 | 929.71 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 147.17 | 0.00 | 147.17 | 17.06 | 819.38 | 0.00 | 0.00 | 0.00 |
February | 184.97 | 0.00 | 184.97 | 22.28 | 825.76 | 0.00 | 0.00 | 0.00 |
March | 251.68 | 0.00 | 251.68 | 89.95 | 635.95 | 0.00 | 0.00 | 0.00 |
April | 316.08 | 1.75 | 314.33 | 144.23 | 561.54 | 0.00 | 0.00 | 0.00 |
May | 431.78 | 14.27 | 417.51 | 359.29 | 310.77 | 0.00 | 0.00 | 0.00 |
June | 473.48 | 52.49 | 420.99 | 606.27 | 169.09 | 0.00 | 0.00 | 0.00 |
July | 447.78 | 28.99 | 418.80 | 580.24 | 160.02 | 0.00 | 0.00 | 0.00 |
August | 356.40 | 8.43 | 347.97 | 438.05 | 184.43 | 0.00 | 0.00 | 0.00 |
September | 299.38 | 0.07 | 299.31 | 321.23 | 286.82 | 0.00 | 0.00 | 0.00 |
October | 214.43 | 0.00 | 214.43 | 99.18 | 612.72 | 0.00 | 0.00 | 0.00 |
November | 162.78 | 0.00 | 162.78 | 31.34 | 750.10 | 0.00 | 0.00 | 0.00 |
December | 137.69 | 0.00 | 137.69 | 13.69 | 929.71 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 285.82 | 8.85 | 276.97 | 228.05 | 518.88 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 137.69 | 0.00 | 137.69 | 13.69 | 160.02 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 473.48 | 52.49 | 420.99 | 606.27 | 929.71 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 147.17 | 0.00 | 147.17 | 17.06 | 819.38 | 0.00 | 0.00 | 0.00 |
February | 184.97 | 0.00 | 184.97 | 22.28 | 825.76 | 0.00 | 0.00 | 0.00 |
March | 251.68 | 0.00 | 251.68 | 89.95 | 635.95 | 0.00 | 0.00 | 0.00 |
April | 316.08 | 1.75 | 314.33 | 144.23 | 561.54 | 0.00 | 0.00 | 0.00 |
May | 431.78 | 14.27 | 417.51 | 359.29 | 310.77 | 0.00 | 0.00 | 0.00 |
June | 473.48 | 52.49 | 420.99 | 606.27 | 169.09 | 0.00 | 0.00 | 0.00 |
July | 447.78 | 28.99 | 418.80 | 580.24 | 160.02 | 0.00 | 0.00 | 0.00 |
August | 356.40 | 8.43 | 347.97 | 438.05 | 184.43 | 0.00 | 0.00 | 0.00 |
September | 299.38 | 0.07 | 299.31 | 321.23 | 286.82 | 0.00 | 0.00 | 0.00 |
October | 214.43 | 0.00 | 214.43 | 99.18 | 612.72 | 0.00 | 0.00 | 0.00 |
November | 162.78 | 0.00 | 162.78 | 31.34 | 750.10 | 0.00 | 0.00 | 0.00 |
December | 137.69 | 0.00 | 137.69 | 13.69 | 929.71 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 285.82 | 8.85 | 276.97 | 228.05 | 518.88 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 137.69 | 0.00 | 137.69 | 13.69 | 160.02 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 473.48 | 52.49 | 420.99 | 606.27 | 929.71 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 147.17 | 0.00 | 147.17 | 17.06 | 819.38 | 0.00 | 0.00 | 0.00 |
February | 184.97 | 0.00 | 184.97 | 22.28 | 825.76 | 0.00 | 0.00 | 0.00 |
March | 251.68 | 0.00 | 251.68 | 89.95 | 635.95 | 0.00 | 0.00 | 0.00 |
April | 316.08 | 1.75 | 314.33 | 144.23 | 561.54 | 0.00 | 0.00 | 0.00 |
May | 431.78 | 14.27 | 417.51 | 359.29 | 310.77 | 0.00 | 0.00 | 0.00 |
June | 473.48 | 52.49 | 420.99 | 606.27 | 169.09 | 0.00 | 0.00 | 0.00 |
July | 447.78 | 28.99 | 418.80 | 580.24 | 160.02 | 0.00 | 0.00 | 0.00 |
August | 356.40 | 8.43 | 347.97 | 438.05 | 184.43 | 0.00 | 0.00 | 0.00 |
September | 299.38 | 0.07 | 299.31 | 321.23 | 286.82 | 0.00 | 0.00 | 0.00 |
October | 214.43 | 0.00 | 214.43 | 99.18 | 612.72 | 0.00 | 0.00 | 0.00 |
November | 162.78 | 0.00 | 162.78 | 31.34 | 750.10 | 0.00 | 0.00 | 0.00 |
December | 137.69 | 0.00 | 137.69 | 13.69 | 929.71 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 285.82 | 8.85 | 276.97 | 228.05 | 518.88 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 137.69 | 0.00 | 137.69 | 13.69 | 160.02 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 473.48 | 52.49 | 420.99 | 606.27 | 929.71 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 147.16 | 0.00 | 147.16 | 17.06 | 819.35 | 0.00 | 0.00 | 0.00 |
February | 184.96 | 0.00 | 184.96 | 22.27 | 825.72 | 0.00 | 0.00 | 0.00 |
March | 251.67 | 0.00 | 251.67 | 89.95 | 635.92 | 0.00 | 0.00 | 0.00 |
April | 316.07 | 1.75 | 314.31 | 144.22 | 561.52 | 0.00 | 0.00 | 0.00 |
May | 431.77 | 14.27 | 417.49 | 359.27 | 310.76 | 0.00 | 0.00 | 0.00 |
June | 473.46 | 52.49 | 420.97 | 606.24 | 169.09 | 0.00 | 0.00 | 0.00 |
July | 447.76 | 28.98 | 418.78 | 580.22 | 160.01 | 0.00 | 0.00 | 0.00 |
August | 356.39 | 8.43 | 347.96 | 438.04 | 184.43 | 0.00 | 0.00 | 0.00 |
September | 299.37 | 0.07 | 299.29 | 321.22 | 286.80 | 0.00 | 0.00 | 0.00 |
October | 214.42 | 0.00 | 214.42 | 99.18 | 612.70 | 0.00 | 0.00 | 0.00 |
November | 162.77 | 0.00 | 162.77 | 31.34 | 750.07 | 0.00 | 0.00 | 0.00 |
December | 137.69 | 0.00 | 137.69 | 13.69 | 929.67 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 285.81 | 8.85 | 276.96 | 228.04 | 518.86 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 137.69 | 0.00 | 137.69 | 13.69 | 160.01 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 473.46 | 52.49 | 420.97 | 606.24 | 929.67 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 512.02 | 313.78 | 198.24 | 421.41 | 832.96 | 0.00 | 0.00 | 0.00 |
February | 680.16 | 429.38 | 250.78 | 604.22 | 854.73 | 0.00 | 0.00 | 0.00 |
March | 820.94 | 478.85 | 342.09 | 790.68 | 655.06 | 0.00 | 0.00 | 0.00 |
April | 841.92 | 410.11 | 431.80 | 792.26 | 581.15 | 0.00 | 0.00 | 0.00 |
May | 984.19 | 411.10 | 573.09 | 1070.65 | 339.96 | 0.00 | 0.00 | 0.00 |
June | 1200.81 | 630.39 | 570.42 | 1573.78 | 183.34 | 0.00 | 0.00 | 0.00 |
July | 1091.63 | 519.81 | 571.82 | 1444.60 | 169.04 | 0.00 | 0.00 | 0.00 |
August | 1101.06 | 606.43 | 494.64 | 1447.77 | 190.59 | 0.00 | 0.00 | 0.00 |
September | 916.14 | 497.67 | 418.47 | 1135.29 | 298.80 | 0.00 | 0.00 | 0.00 |
October | 663.47 | 363.54 | 299.93 | 665.78 | 646.37 | 0.00 | 0.00 | 0.00 |
November | 516.42 | 291.58 | 224.85 | 452.67 | 771.90 | 0.00 | 0.00 | 0.00 |
December | 447.09 | 257.55 | 189.53 | 349.72 | 945.89 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 815.17 | 433.97 | 381.20 | 897.12 | 537.44 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 447.09 | 257.55 | 189.53 | 349.72 | 169.04 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1200.81 | 630.39 | 573.09 | 1573.78 | 945.89 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 512.02 | 313.78 | 198.24 | 421.41 | 832.96 | 0.00 | 0.00 | 0.00 |
February | 680.16 | 429.38 | 250.78 | 604.22 | 854.73 | 0.00 | 0.00 | 0.00 |
March | 820.94 | 478.85 | 342.09 | 790.68 | 655.06 | 0.00 | 0.00 | 0.00 |
April | 841.92 | 410.11 | 431.80 | 792.26 | 581.15 | 0.00 | 0.00 | 0.00 |
May | 984.19 | 411.10 | 573.09 | 1070.65 | 339.96 | 0.00 | 0.00 | 0.00 |
June | 1200.81 | 630.39 | 570.42 | 1573.78 | 183.34 | 0.00 | 0.00 | 0.00 |
July | 1091.63 | 519.81 | 571.82 | 1444.60 | 169.04 | 0.00 | 0.00 | 0.00 |
August | 1101.06 | 606.43 | 494.64 | 1447.77 | 190.59 | 0.00 | 0.00 | 0.00 |
September | 916.14 | 497.67 | 418.47 | 1135.29 | 298.80 | 0.00 | 0.00 | 0.00 |
October | 663.47 | 363.54 | 299.93 | 665.78 | 646.37 | 0.00 | 0.00 | 0.00 |
November | 516.42 | 291.58 | 224.85 | 452.67 | 771.90 | 0.00 | 0.00 | 0.00 |
December | 447.09 | 257.55 | 189.53 | 349.72 | 945.89 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 815.17 | 433.97 | 381.20 | 897.12 | 537.44 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 447.09 | 257.55 | 189.53 | 349.72 | 169.04 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1200.81 | 630.39 | 573.09 | 1573.78 | 945.89 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 512.01 | 313.78 | 198.24 | 421.40 | 832.95 | 0.00 | 0.00 | 0.00 |
February | 680.15 | 429.38 | 250.77 | 604.21 | 854.71 | 0.00 | 0.00 | 0.00 |
March | 820.92 | 478.84 | 342.09 | 790.67 | 655.05 | 0.00 | 0.00 | 0.00 |
April | 841.90 | 410.11 | 431.80 | 792.25 | 581.14 | 0.00 | 0.00 | 0.00 |
May | 984.17 | 411.09 | 573.08 | 1070.64 | 339.95 | 0.00 | 0.00 | 0.00 |
June | 1200.79 | 630.38 | 570.41 | 1573.76 | 183.34 | 0.00 | 0.00 | 0.00 |
July | 1091.61 | 519.80 | 571.81 | 1444.57 | 169.03 | 0.00 | 0.00 | 0.00 |
August | 1101.04 | 606.41 | 494.63 | 1447.75 | 190.59 | 0.00 | 0.00 | 0.00 |
September | 916.12 | 497.66 | 418.46 | 1135.27 | 298.80 | 0.00 | 0.00 | 0.00 |
October | 663.46 | 363.54 | 299.92 | 665.76 | 646.36 | 0.00 | 0.00 | 0.00 |
November | 516.41 | 291.57 | 224.84 | 452.66 | 771.88 | 0.00 | 0.00 | 0.00 |
December | 447.08 | 257.55 | 189.53 | 349.71 | 945.87 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 815.15 | 433.96 | 381.19 | 897.10 | 537.43 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 447.08 | 257.55 | 189.53 | 349.71 | 169.03 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1200.79 | 630.38 | 573.08 | 1573.76 | 945.87 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1410.42 | 1160.22 | 250.20 | 1551.53 | 710.30 | 0.00 | 0.00 | 0.00 |
February | 1352.86 | 1078.58 | 274.27 | 1474.83 | 739.12 | 0.00 | 0.00 | 0.00 |
March | 997.43 | 656.25 | 341.18 | 1099.41 | 598.19 | 0.00 | 0.00 | 0.00 |
April | 646.01 | 259.76 | 386.25 | 641.45 | 548.44 | 0.00 | 0.00 | 0.00 |
May | 592.00 | 108.51 | 483.49 | 646.41 | 333.37 | 0.00 | 0.00 | 0.00 |
June | 545.80 | 99.76 | 446.04 | 764.26 | 184.45 | 0.00 | 0.00 | 0.00 |
July | 568.17 | 101.74 | 466.42 | 797.82 | 170.05 | 0.00 | 0.00 | 0.00 |
August | 723.39 | 302.41 | 420.99 | 1021.46 | 192.29 | 0.00 | 0.00 | 0.00 |
September | 930.71 | 519.33 | 411.38 | 1232.77 | 291.73 | 0.00 | 0.00 | 0.00 |
October | 1112.86 | 789.60 | 323.26 | 1304.86 | 587.38 | 0.00 | 0.00 | 0.00 |
November | 1355.87 | 1080.82 | 275.04 | 1527.49 | 681.04 | 0.00 | 0.00 | 0.00 |
December | 1296.56 | 1049.42 | 247.14 | 1393.37 | 804.81 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 958.79 | 597.82 | 360.97 | 1119.27 | 485.35 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 545.80 | 99.76 | 247.14 | 641.45 | 170.05 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1410.42 | 1160.22 | 483.49 | 1551.53 | 804.81 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1410.42 | 1160.22 | 250.20 | 1551.52 | 710.30 | 0.00 | 0.00 | 0.00 |
February | 1352.86 | 1078.58 | 274.27 | 1474.83 | 739.12 | 0.00 | 0.00 | 0.00 |
March | 997.43 | 656.25 | 341.18 | 1099.41 | 598.19 | 0.00 | 0.00 | 0.00 |
April | 646.01 | 259.76 | 386.25 | 641.44 | 548.44 | 0.00 | 0.00 | 0.00 |
May | 592.00 | 108.51 | 483.49 | 646.41 | 333.37 | 0.00 | 0.00 | 0.00 |
June | 545.80 | 99.76 | 446.04 | 764.26 | 184.45 | 0.00 | 0.00 | 0.00 |
July | 568.17 | 101.74 | 466.42 | 797.82 | 170.05 | 0.00 | 0.00 | 0.00 |
August | 723.39 | 302.40 | 420.99 | 1021.46 | 192.29 | 0.00 | 0.00 | 0.00 |
September | 930.71 | 519.33 | 411.38 | 1232.77 | 291.73 | 0.00 | 0.00 | 0.00 |
October | 1112.86 | 789.60 | 323.26 | 1304.86 | 587.38 | 0.00 | 0.00 | 0.00 |
November | 1355.87 | 1080.82 | 275.04 | 1527.48 | 681.04 | 0.00 | 0.00 | 0.00 |
December | 1296.56 | 1049.42 | 247.14 | 1393.37 | 804.81 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 958.79 | 597.82 | 360.97 | 1119.27 | 485.35 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 545.80 | 99.76 | 247.14 | 641.44 | 170.05 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1410.42 | 1160.22 | 483.49 | 1551.52 | 804.81 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1410.42 | 1160.22 | 250.20 | 1551.53 | 710.30 | 0.00 | 0.00 | 0.00 |
February | 1352.86 | 1078.58 | 274.27 | 1474.83 | 739.12 | 0.00 | 0.00 | 0.00 |
March | 997.43 | 656.25 | 341.18 | 1099.41 | 598.19 | 0.00 | 0.00 | 0.00 |
April | 646.01 | 259.76 | 386.25 | 641.45 | 548.44 | 0.00 | 0.00 | 0.00 |
May | 592.00 | 108.51 | 483.49 | 646.41 | 333.37 | 0.00 | 0.00 | 0.00 |
June | 545.80 | 99.76 | 446.04 | 764.26 | 184.45 | 0.00 | 0.00 | 0.00 |
July | 568.17 | 101.74 | 466.42 | 797.82 | 170.05 | 0.00 | 0.00 | 0.00 |
August | 723.39 | 302.41 | 420.99 | 1021.46 | 192.29 | 0.00 | 0.00 | 0.00 |
September | 930.71 | 519.33 | 411.38 | 1232.77 | 291.73 | 0.00 | 0.00 | 0.00 |
October | 1112.86 | 789.60 | 323.26 | 1304.86 | 587.38 | 0.00 | 0.00 | 0.00 |
November | 1355.87 | 1080.82 | 275.04 | 1527.49 | 681.04 | 0.00 | 0.00 | 0.00 |
December | 1296.56 | 1049.42 | 247.14 | 1393.37 | 804.81 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 958.79 | 597.82 | 360.97 | 1119.27 | 485.35 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 545.80 | 99.76 | 247.14 | 641.45 | 170.05 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1410.42 | 1160.22 | 483.49 | 1551.53 | 804.81 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1410.42 | 1160.22 | 250.20 | 1551.52 | 710.30 | 0.00 | 0.00 | 0.00 |
February | 1352.86 | 1078.58 | 274.27 | 1474.83 | 739.12 | 0.00 | 0.00 | 0.00 |
March | 997.43 | 656.25 | 341.18 | 1099.41 | 598.19 | 0.00 | 0.00 | 0.00 |
April | 646.01 | 259.76 | 386.25 | 641.44 | 548.44 | 0.00 | 0.00 | 0.00 |
May | 592.00 | 108.51 | 483.49 | 646.41 | 333.37 | 0.00 | 0.00 | 0.00 |
June | 545.80 | 99.76 | 446.04 | 764.26 | 184.45 | 0.00 | 0.00 | 0.00 |
July | 568.17 | 101.74 | 466.42 | 797.82 | 170.05 | 0.00 | 0.00 | 0.00 |
August | 723.39 | 302.40 | 420.99 | 1021.46 | 192.29 | 0.00 | 0.00 | 0.00 |
September | 930.71 | 519.33 | 411.38 | 1232.77 | 291.73 | 0.00 | 0.00 | 0.00 |
October | 1112.86 | 789.60 | 323.26 | 1304.86 | 587.38 | 0.00 | 0.00 | 0.00 |
November | 1355.87 | 1080.82 | 275.04 | 1527.48 | 681.04 | 0.00 | 0.00 | 0.00 |
December | 1296.56 | 1049.42 | 247.14 | 1393.37 | 804.81 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 958.79 | 597.82 | 360.97 | 1119.27 | 485.35 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 545.80 | 99.76 | 247.14 | 641.44 | 170.05 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1410.42 | 1160.22 | 483.49 | 1551.52 | 804.81 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1410.37 | 1160.18 | 250.19 | 1551.46 | 710.27 | 0.00 | 0.00 | 0.00 |
February | 1352.80 | 1078.54 | 274.26 | 1474.77 | 739.09 | 0.00 | 0.00 | 0.00 |
March | 997.39 | 656.23 | 341.16 | 1099.37 | 598.17 | 0.00 | 0.00 | 0.00 |
April | 645.98 | 259.75 | 386.23 | 641.42 | 548.42 | 0.00 | 0.00 | 0.00 |
May | 591.97 | 108.50 | 483.47 | 646.39 | 333.36 | 0.00 | 0.00 | 0.00 |
June | 545.78 | 99.75 | 446.03 | 764.23 | 184.44 | 0.00 | 0.00 | 0.00 |
July | 568.14 | 101.74 | 466.41 | 797.79 | 170.04 | 0.00 | 0.00 | 0.00 |
August | 723.36 | 302.39 | 420.97 | 1021.42 | 192.28 | 0.00 | 0.00 | 0.00 |
September | 930.68 | 519.31 | 411.36 | 1232.72 | 291.71 | 0.00 | 0.00 | 0.00 |
October | 1112.82 | 789.57 | 323.25 | 1304.81 | 587.36 | 0.00 | 0.00 | 0.00 |
November | 1355.81 | 1080.78 | 275.03 | 1527.42 | 681.01 | 0.00 | 0.00 | 0.00 |
December | 1296.51 | 1049.38 | 247.13 | 1393.32 | 804.78 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 958.75 | 597.79 | 360.96 | 1119.23 | 485.33 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 545.78 | 99.75 | 247.13 | 641.42 | 170.04 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1410.37 | 1160.18 | 483.47 | 1551.46 | 804.78 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 544.68 | 345.14 | 199.54 | 483.11 | 890.91 | 0.00 | 0.00 | 0.00 |
February | 656.80 | 407.02 | 249.78 | 578.20 | 923.87 | 0.00 | 0.00 | 0.00 |
March | 769.07 | 424.32 | 344.76 | 717.76 | 740.69 | 0.00 | 0.00 | 0.00 |
April | 724.12 | 306.58 | 417.54 | 634.84 | 682.65 | 0.00 | 0.00 | 0.00 |
May | 885.06 | 312.02 | 573.04 | 952.42 | 388.81 | 0.00 | 0.00 | 0.00 |
June | 1082.48 | 520.82 | 561.66 | 1421.33 | 235.16 | 0.00 | 0.00 | 0.00 |
July | 881.97 | 323.05 | 558.92 | 1153.25 | 219.99 | 0.00 | 0.00 | 0.00 |
August | 920.52 | 454.75 | 465.77 | 1183.11 | 250.86 | 0.00 | 0.00 | 0.00 |
September | 816.23 | 391.44 | 424.79 | 1009.50 | 346.81 | 0.00 | 0.00 | 0.00 |
October | 686.66 | 392.48 | 294.18 | 702.68 | 711.33 | 0.00 | 0.00 | 0.00 |
November | 563.44 | 342.08 | 221.36 | 508.26 | 858.27 | 0.00 | 0.00 | 0.00 |
December | 455.11 | 268.84 | 186.26 | 355.54 | 1051.20 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 749.08 | 373.60 | 375.48 | 809.29 | 606.64 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 455.11 | 268.84 | 186.26 | 355.54 | 219.99 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1082.48 | 520.82 | 573.04 | 1421.33 | 1051.20 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 544.68 | 345.14 | 199.54 | 483.11 | 890.91 | 0.00 | 0.00 | 0.00 |
February | 656.80 | 407.02 | 249.78 | 578.20 | 923.87 | 0.00 | 0.00 | 0.00 |
March | 769.07 | 424.32 | 344.76 | 717.76 | 740.69 | 0.00 | 0.00 | 0.00 |
April | 724.12 | 306.58 | 417.54 | 634.84 | 682.65 | 0.00 | 0.00 | 0.00 |
May | 885.06 | 312.02 | 573.04 | 952.42 | 388.81 | 0.00 | 0.00 | 0.00 |
June | 1082.48 | 520.82 | 561.66 | 1421.33 | 235.16 | 0.00 | 0.00 | 0.00 |
July | 881.97 | 323.05 | 558.92 | 1153.25 | 219.99 | 0.00 | 0.00 | 0.00 |
August | 920.52 | 454.75 | 465.77 | 1183.11 | 250.86 | 0.00 | 0.00 | 0.00 |
September | 816.23 | 391.44 | 424.79 | 1009.50 | 346.81 | 0.00 | 0.00 | 0.00 |
October | 686.66 | 392.48 | 294.18 | 702.68 | 711.33 | 0.00 | 0.00 | 0.00 |
November | 563.44 | 342.08 | 221.36 | 508.26 | 858.27 | 0.00 | 0.00 | 0.00 |
December | 455.11 | 268.84 | 186.26 | 355.54 | 1051.20 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 749.08 | 373.60 | 375.48 | 809.29 | 606.64 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 455.11 | 268.84 | 186.26 | 355.54 | 219.99 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1082.48 | 520.82 | 573.04 | 1421.33 | 1051.20 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 544.67 | 345.13 | 199.54 | 483.10 | 890.89 | 0.00 | 0.00 | 0.00 |
February | 656.79 | 407.02 | 249.77 | 578.19 | 923.86 | 0.00 | 0.00 | 0.00 |
March | 769.06 | 424.31 | 344.75 | 717.74 | 740.67 | 0.00 | 0.00 | 0.00 |
April | 724.11 | 306.57 | 417.53 | 634.83 | 682.63 | 0.00 | 0.00 | 0.00 |
May | 885.04 | 312.01 | 573.03 | 952.40 | 388.80 | 0.00 | 0.00 | 0.00 |
June | 1082.46 | 520.81 | 561.65 | 1421.31 | 235.16 | 0.00 | 0.00 | 0.00 |
July | 881.95 | 323.04 | 558.91 | 1153.23 | 219.99 | 0.00 | 0.00 | 0.00 |
August | 920.50 | 454.74 | 465.76 | 1183.09 | 250.86 | 0.00 | 0.00 | 0.00 |
September | 816.21 | 391.43 | 424.78 | 1009.49 | 346.80 | 0.00 | 0.00 | 0.00 |
October | 686.65 | 392.47 | 294.18 | 702.66 | 711.32 | 0.00 | 0.00 | 0.00 |
November | 563.43 | 342.07 | 221.36 | 508.25 | 858.26 | 0.00 | 0.00 | 0.00 |
December | 455.10 | 268.84 | 186.26 | 355.53 | 1051.18 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 749.06 | 373.59 | 375.48 | 809.28 | 606.63 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 455.10 | 268.84 | 186.26 | 355.53 | 219.99 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1082.46 | 520.81 | 573.03 | 1421.31 | 1051.18 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 735.82 | 0.00 | 735.82 | 120.61 | 3727.14 | 0.00 | 0.00 | 0.00 |
February | 924.84 | 0.00 | 924.84 | 156.58 | 3759.71 | 0.00 | 0.00 | 0.00 |
March | 1258.40 | 0.00 | 1258.40 | 522.28 | 2864.76 | 0.00 | 0.00 | 0.00 |
April | 1580.38 | 8.77 | 1571.61 | 795.81 | 2473.86 | 0.00 | 0.00 | 0.00 |
May | 2158.89 | 71.36 | 2087.52 | 1835.58 | 1469.78 | 0.00 | 0.00 | 0.00 |
June | 2367.37 | 262.46 | 2104.91 | 3052.55 | 815.40 | 0.00 | 0.00 | 0.00 |
July | 2238.89 | 144.93 | 2093.96 | 2925.14 | 773.84 | 0.00 | 0.00 | 0.00 |
August | 1781.99 | 42.16 | 1739.83 | 2224.11 | 881.26 | 0.00 | 0.00 | 0.00 |
September | 1496.87 | 0.35 | 1496.52 | 1641.28 | 1350.14 | 0.00 | 0.00 | 0.00 |
October | 1072.12 | 0.00 | 1072.12 | 553.75 | 2803.98 | 0.00 | 0.00 | 0.00 |
November | 813.87 | 0.00 | 813.87 | 207.86 | 3366.33 | 0.00 | 0.00 | 0.00 |
December | 688.45 | 0.00 | 688.45 | 109.81 | 4168.38 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1429.10 | 44.27 | 1384.83 | 1184.49 | 2363.85 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 688.45 | 0.00 | 688.45 | 109.81 | 773.84 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2367.37 | 262.46 | 2104.91 | 3052.55 | 4168.38 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1536.05 | 941.34 | 594.71 | 1293.33 | 2334.49 | 0.00 | 0.00 | 0.00 |
February | 2040.47 | 1288.14 | 752.33 | 1824.15 | 2405.07 | 0.00 | 0.00 | 0.00 |
March | 2462.79 | 1436.53 | 1026.27 | 2377.53 | 1837.33 | 0.00 | 0.00 | 0.00 |
April | 2525.73 | 1230.33 | 1295.40 | 2383.98 | 1602.55 | 0.00 | 0.00 | 0.00 |
May | 2952.54 | 1233.29 | 1719.25 | 3203.51 | 980.57 | 0.00 | 0.00 | 0.00 |
June | 3602.40 | 1891.16 | 1711.23 | 4696.94 | 544.27 | 0.00 | 0.00 | 0.00 |
July | 3274.86 | 1559.41 | 1715.45 | 4307.60 | 517.68 | 0.00 | 0.00 | 0.00 |
August | 3303.15 | 1819.26 | 1483.89 | 4317.27 | 588.94 | 0.00 | 0.00 | 0.00 |
September | 2748.39 | 1493.00 | 1255.39 | 3395.04 | 862.01 | 0.00 | 0.00 | 0.00 |
October | 1990.38 | 1090.61 | 899.77 | 2001.84 | 1828.26 | 0.00 | 0.00 | 0.00 |
November | 1549.26 | 874.73 | 674.53 | 1381.35 | 2161.72 | 0.00 | 0.00 | 0.00 |
December | 1341.24 | 772.65 | 568.59 | 1081.13 | 2635.50 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 2445.47 | 1301.89 | 1143.58 | 2692.72 | 1520.17 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 1341.24 | 772.65 | 568.59 | 1081.13 | 517.68 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 3602.40 | 1891.16 | 1719.25 | 4696.94 | 2635.50 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 7052.03 | 5801.05 | 1250.97 | 7706.38 | 3507.45 | 0.00 | 0.00 | 0.00 |
February | 6764.20 | 5392.85 | 1371.35 | 7311.87 | 3607.06 | 0.00 | 0.00 | 0.00 |
March | 4987.09 | 3281.22 | 1705.87 | 5468.29 | 2872.78 | 0.00 | 0.00 | 0.00 |
April | 3230.01 | 1298.80 | 1931.21 | 3212.10 | 2568.46 | 0.00 | 0.00 | 0.00 |
May | 2959.95 | 542.54 | 2417.41 | 3229.45 | 1619.06 | 0.00 | 0.00 | 0.00 |
June | 2728.97 | 498.78 | 2230.19 | 3826.09 | 894.85 | 0.00 | 0.00 | 0.00 |
July | 2840.80 | 508.71 | 2332.09 | 3992.62 | 835.80 | 0.00 | 0.00 | 0.00 |
August | 3616.91 | 1512.01 | 2104.91 | 5097.07 | 949.16 | 0.00 | 0.00 | 0.00 |
September | 4653.51 | 2596.64 | 2056.88 | 6129.01 | 1429.76 | 0.00 | 0.00 | 0.00 |
October | 5564.24 | 3947.96 | 1616.29 | 6483.56 | 2865.47 | 0.00 | 0.00 | 0.00 |
November | 6779.26 | 5404.05 | 1375.21 | 7588.70 | 3323.70 | 0.00 | 0.00 | 0.00 |
December | 6482.74 | 5247.04 | 1235.70 | 6940.98 | 3875.94 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 4793.88 | 2989.05 | 1804.83 | 5572.27 | 2355.61 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 2728.97 | 498.78 | 1235.70 | 3212.10 | 835.80 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 7052.03 | 5801.05 | 2417.41 | 7706.38 | 3875.94 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1634.01 | 1035.40 | 598.61 | 1488.64 | 2450.81 | 0.00 | 0.00 | 0.00 |
February | 1970.39 | 1221.06 | 749.33 | 1781.62 | 2495.29 | 0.00 | 0.00 | 0.00 |
March | 2307.20 | 1272.93 | 1034.26 | 2221.72 | 1932.51 | 0.00 | 0.00 | 0.00 |
April | 2172.33 | 919.73 | 1252.60 | 1987.37 | 1695.76 | 0.00 | 0.00 | 0.00 |
May | 2655.15 | 936.04 | 1719.11 | 2893.90 | 1078.32 | 0.00 | 0.00 | 0.00 |
June | 3247.41 | 1562.45 | 1684.95 | 4295.59 | 644.78 | 0.00 | 0.00 | 0.00 |
July | 2645.87 | 969.13 | 1676.74 | 3508.81 | 590.30 | 0.00 | 0.00 | 0.00 |
August | 2761.54 | 1364.24 | 1397.30 | 3608.72 | 660.46 | 0.00 | 0.00 | 0.00 |
September | 2448.66 | 1174.29 | 1274.36 | 3058.00 | 958.83 | 0.00 | 0.00 | 0.00 |
October | 2059.97 | 1177.43 | 882.54 | 2158.30 | 1910.43 | 0.00 | 0.00 | 0.00 |
November | 1690.31 | 1026.23 | 664.08 | 1588.19 | 2251.26 | 0.00 | 0.00 | 0.00 |
December | 1365.31 | 806.53 | 558.79 | 1133.26 | 2708.03 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 2247.21 | 1120.78 | 1126.44 | 2479.93 | 1609.98 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 1365.31 | 806.53 | 558.79 | 1133.26 | 590.30 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 3247.41 | 1562.45 | 1719.11 | 4295.59 | 2708.03 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 735.82 | 0.00 | 735.82 | 145.85 | 3495.44 | 0.00 | 0.00 | 0.00 |
February | 924.84 | 0.00 | 924.84 | 178.74 | 3579.37 | 0.00 | 0.00 | 0.00 |
March | 1258.40 | 0.00 | 1258.40 | 548.58 | 2717.72 | 0.00 | 0.00 | 0.00 |
April | 1580.38 | 8.77 | 1571.61 | 827.22 | 2294.14 | 0.00 | 0.00 | 0.00 |
May | 2158.89 | 71.36 | 2087.52 | 1870.35 | 1403.16 | 0.00 | 0.00 | 0.00 |
June | 2367.37 | 262.46 | 2104.91 | 3036.04 | 807.19 | 0.00 | 0.00 | 0.00 |
July | 2238.89 | 144.93 | 2093.96 | 2909.37 | 767.71 | 0.00 | 0.00 | 0.00 |
August | 1781.99 | 42.16 | 1739.83 | 2214.74 | 866.83 | 0.00 | 0.00 | 0.00 |
September | 1496.87 | 0.35 | 1496.52 | 1649.92 | 1299.47 | 0.00 | 0.00 | 0.00 |
October | 1072.12 | 0.00 | 1072.12 | 589.85 | 2625.19 | 0.00 | 0.00 | 0.00 |
November | 813.87 | 0.00 | 813.87 | 241.15 | 3146.21 | 0.00 | 0.00 | 0.00 |
December | 688.45 | 0.00 | 688.45 | 125.62 | 3975.35 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1429.10 | 44.27 | 1384.83 | 1200.46 | 2241.17 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 688.45 | 0.00 | 688.45 | 125.62 | 767.71 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2367.37 | 262.46 | 2104.91 | 3036.04 | 3975.35 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1536.05 | 941.34 | 594.71 | 1329.18 | 2192.32 | 0.00 | 0.00 | 0.00 |
February | 2040.47 | 1288.14 | 752.33 | 1848.22 | 2299.70 | 0.00 | 0.00 | 0.00 |
March | 2462.79 | 1436.53 | 1026.27 | 2392.75 | 1755.70 | 0.00 | 0.00 | 0.00 |
April | 2525.73 | 1230.33 | 1295.40 | 2399.82 | 1496.57 | 0.00 | 0.00 | 0.00 |
May | 2952.54 | 1233.29 | 1719.25 | 3213.74 | 946.81 | 0.00 | 0.00 | 0.00 |
June | 3602.40 | 1891.16 | 1711.23 | 4678.89 | 541.73 | 0.00 | 0.00 | 0.00 |
July | 3274.86 | 1559.41 | 1715.45 | 4291.41 | 515.81 | 0.00 | 0.00 | 0.00 |
August | 3303.15 | 1819.26 | 1483.89 | 4303.91 | 584.13 | 0.00 | 0.00 | 0.00 |
September | 2748.39 | 1493.00 | 1255.39 | 3392.18 | 840.52 | 0.00 | 0.00 | 0.00 |
October | 1990.38 | 1090.61 | 899.77 | 2017.10 | 1730.89 | 0.00 | 0.00 | 0.00 |
November | 1549.26 | 874.73 | 674.53 | 1412.47 | 2037.50 | 0.00 | 0.00 | 0.00 |
December | 1341.24 | 772.65 | 568.59 | 1107.05 | 2519.97 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 2445.47 | 1301.89 | 1143.58 | 2702.90 | 1450.67 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 1341.24 | 772.65 | 568.59 | 1107.05 | 515.81 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 3602.40 | 1891.16 | 1719.25 | 4678.89 | 2519.97 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 7052.03 | 5801.05 | 1250.97 | 7771.67 | 3284.04 | 0.00 | 0.00 | 0.00 |
February | 6764.20 | 5392.85 | 1371.35 | 7346.63 | 3435.11 | 0.00 | 0.00 | 0.00 |
March | 4987.09 | 3281.22 | 1705.87 | 5489.19 | 2733.54 | 0.00 | 0.00 | 0.00 |
April | 3230.01 | 1298.80 | 1931.21 | 3234.09 | 2394.10 | 0.00 | 0.00 | 0.00 |
May | 2959.95 | 542.54 | 2417.41 | 3248.80 | 1549.06 | 0.00 | 0.00 | 0.00 |
June | 2728.97 | 498.78 | 2230.19 | 3808.78 | 883.35 | 0.00 | 0.00 | 0.00 |
July | 2840.80 | 508.71 | 2332.09 | 3975.70 | 826.76 | 0.00 | 0.00 | 0.00 |
August | 3616.91 | 1512.01 | 2104.91 | 5081.64 | 934.86 | 0.00 | 0.00 | 0.00 |
September | 4653.51 | 2596.64 | 2056.88 | 6124.77 | 1386.75 | 0.00 | 0.00 | 0.00 |
October | 5564.24 | 3947.96 | 1616.29 | 6506.39 | 2707.96 | 0.00 | 0.00 | 0.00 |
November | 6779.26 | 5404.05 | 1375.21 | 7631.27 | 3138.96 | 0.00 | 0.00 | 0.00 |
December | 6482.74 | 5247.04 | 1235.70 | 6985.49 | 3686.34 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 4793.88 | 2989.05 | 1804.83 | 5590.40 | 2240.21 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 2728.97 | 498.78 | 1235.70 | 3234.09 | 826.76 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 7052.03 | 5801.05 | 2417.41 | 7771.67 | 3686.34 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1634.01 | 1035.40 | 598.61 | 1508.95 | 2311.15 | 0.00 | 0.00 | 0.00 |
February | 1970.39 | 1221.06 | 749.33 | 1791.16 | 2392.85 | 0.00 | 0.00 | 0.00 |
March | 2307.20 | 1272.93 | 1034.26 | 2228.83 | 1848.25 | 0.00 | 0.00 | 0.00 |
April | 2172.33 | 919.73 | 1252.60 | 1996.52 | 1592.53 | 0.00 | 0.00 | 0.00 |
May | 2655.15 | 936.04 | 1719.11 | 2901.74 | 1038.51 | 0.00 | 0.00 | 0.00 |
June | 3247.41 | 1562.45 | 1684.95 | 4282.24 | 636.86 | 0.00 | 0.00 | 0.00 |
July | 2645.87 | 969.13 | 1676.74 | 3496.95 | 583.13 | 0.00 | 0.00 | 0.00 |
August | 2761.54 | 1364.24 | 1397.30 | 3599.83 | 650.74 | 0.00 | 0.00 | 0.00 |
September | 2448.66 | 1174.29 | 1274.36 | 3057.54 | 931.33 | 0.00 | 0.00 | 0.00 |
October | 2059.97 | 1177.43 | 882.54 | 2169.56 | 1815.72 | 0.00 | 0.00 | 0.00 |
November | 1690.31 | 1026.23 | 664.08 | 1603.90 | 2137.27 | 0.00 | 0.00 | 0.00 |
December | 1365.31 | 806.53 | 558.79 | 1144.38 | 2598.88 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 2247.21 | 1120.78 | 1126.44 | 2484.70 | 1540.21 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 1365.31 | 806.53 | 558.79 | 1144.38 | 583.13 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 3247.41 | 1562.45 | 1719.11 | 4282.24 | 2598.88 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.394170E+09 | 0.00 | 0.394170E+09 | 45686187.98 | 0.219464E+10 |
February | 0.447480E+09 | 0.00 | 0.447480E+09 | 53887866.54 | 0.199767E+10 |
March | 0.674110E+09 | 0.00 | 0.674110E+09 | 0.240932E+09 | 0.170332E+10 |
April | 0.819276E+09 | 4544993.20 | 0.814731E+09 | 0.373840E+09 | 0.145552E+10 |
May | 0.115649E+10 | 38228815.27 | 0.111826E+10 | 0.962317E+09 | 0.832363E+09 |
June | 0.122726E+10 | 0.136062E+09 | 0.109120E+10 | 0.157144E+10 | 0.438287E+09 |
July | 0.119934E+10 | 77635533.73 | 0.112171E+10 | 0.155411E+10 | 0.428587E+09 |
August | 0.954585E+09 | 22582275.17 | 0.932003E+09 | 0.117329E+10 | 0.493985E+09 |
September | 0.775985E+09 | 182265.27 | 0.775803E+09 | 0.832627E+09 | 0.743428E+09 |
October | 0.574319E+09 | 0.00 | 0.574319E+09 | 0.265651E+09 | 0.164112E+10 |
November | 0.421917E+09 | 0.00 | 0.421917E+09 | 81226602.28 | 0.194426E+10 |
December | 0.368796E+09 | 0.00 | 0.368796E+09 | 36678129.66 | 0.249014E+10 |
Annual Sum or Average | 0.901373E+10 | 0.279235E+09 | 0.873449E+10 | 0.719169E+10 | 0.163633E+11 |
Minimum of Months | 0.368796E+09 | 0.00 | 0.368796E+09 | 36678129.66 | 0.428587E+09 |
Maximum of Months | 0.122726E+10 | 0.136062E+09 | 0.112171E+10 | 0.157144E+10 | 0.249014E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.394170E+09 | 0.00 | 0.394170E+09 | 45686091.71 | 0.219464E+10 |
February | 0.447480E+09 | 0.00 | 0.447480E+09 | 53887773.20 | 0.199767E+10 |
March | 0.674110E+09 | 0.00 | 0.674110E+09 | 0.240932E+09 | 0.170332E+10 |
April | 0.819276E+09 | 4544987.75 | 0.814731E+09 | 0.373839E+09 | 0.145552E+10 |
May | 0.115649E+10 | 38228769.40 | 0.111826E+10 | 0.962316E+09 | 0.832363E+09 |
June | 0.122726E+10 | 0.136061E+09 | 0.109120E+10 | 0.157144E+10 | 0.438287E+09 |
July | 0.119934E+10 | 77635440.58 | 0.112171E+10 | 0.155411E+10 | 0.428587E+09 |
August | 0.954585E+09 | 22582248.08 | 0.932002E+09 | 0.117328E+10 | 0.493985E+09 |
September | 0.775985E+09 | 182265.05 | 0.775803E+09 | 0.832627E+09 | 0.743428E+09 |
October | 0.574319E+09 | 0.00 | 0.574319E+09 | 0.265651E+09 | 0.164112E+10 |
November | 0.421917E+09 | 0.00 | 0.421917E+09 | 81226487.11 | 0.194426E+10 |
December | 0.368795E+09 | 0.00 | 0.368795E+09 | 36678075.76 | 0.249014E+10 |
Annual Sum or Average | 0.901372E+10 | 0.279235E+09 | 0.873449E+10 | 0.719168E+10 | 0.163633E+11 |
Minimum of Months | 0.368795E+09 | 0.00 | 0.368795E+09 | 36678075.76 | 0.428587E+09 |
Maximum of Months | 0.122726E+10 | 0.136061E+09 | 0.112171E+10 | 0.157144E+10 | 0.249014E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.394170E+09 | 0.00 | 0.394170E+09 | 45686187.98 | 0.219464E+10 |
February | 0.447480E+09 | 0.00 | 0.447480E+09 | 53887866.54 | 0.199767E+10 |
March | 0.674110E+09 | 0.00 | 0.674110E+09 | 0.240932E+09 | 0.170332E+10 |
April | 0.819276E+09 | 4544993.20 | 0.814731E+09 | 0.373840E+09 | 0.145552E+10 |
May | 0.115649E+10 | 38228815.27 | 0.111826E+10 | 0.962317E+09 | 0.832363E+09 |
June | 0.122726E+10 | 0.136062E+09 | 0.109120E+10 | 0.157144E+10 | 0.438287E+09 |
July | 0.119934E+10 | 77635533.73 | 0.112171E+10 | 0.155411E+10 | 0.428587E+09 |
August | 0.954585E+09 | 22582275.17 | 0.932003E+09 | 0.117329E+10 | 0.493985E+09 |
September | 0.775985E+09 | 182265.27 | 0.775803E+09 | 0.832627E+09 | 0.743428E+09 |
October | 0.574319E+09 | 0.00 | 0.574319E+09 | 0.265651E+09 | 0.164112E+10 |
November | 0.421917E+09 | 0.00 | 0.421917E+09 | 81226602.28 | 0.194426E+10 |
December | 0.368796E+09 | 0.00 | 0.368796E+09 | 36678129.66 | 0.249014E+10 |
Annual Sum or Average | 0.901373E+10 | 0.279235E+09 | 0.873449E+10 | 0.719169E+10 | 0.163633E+11 |
Minimum of Months | 0.368796E+09 | 0.00 | 0.368796E+09 | 36678129.66 | 0.428587E+09 |
Maximum of Months | 0.122726E+10 | 0.136062E+09 | 0.112171E+10 | 0.157144E+10 | 0.249014E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.394170E+09 | 0.00 | 0.394170E+09 | 45686091.71 | 0.219464E+10 |
February | 0.447480E+09 | 0.00 | 0.447480E+09 | 53887773.20 | 0.199767E+10 |
March | 0.674110E+09 | 0.00 | 0.674110E+09 | 0.240932E+09 | 0.170332E+10 |
April | 0.819276E+09 | 4544987.75 | 0.814731E+09 | 0.373839E+09 | 0.145552E+10 |
May | 0.115649E+10 | 38228769.40 | 0.111826E+10 | 0.962316E+09 | 0.832363E+09 |
June | 0.122726E+10 | 0.136061E+09 | 0.109120E+10 | 0.157144E+10 | 0.438287E+09 |
July | 0.119934E+10 | 77635440.58 | 0.112171E+10 | 0.155411E+10 | 0.428587E+09 |
August | 0.954585E+09 | 22582248.08 | 0.932002E+09 | 0.117328E+10 | 0.493985E+09 |
September | 0.775985E+09 | 182265.05 | 0.775803E+09 | 0.832627E+09 | 0.743428E+09 |
October | 0.574319E+09 | 0.00 | 0.574319E+09 | 0.265651E+09 | 0.164112E+10 |
November | 0.421917E+09 | 0.00 | 0.421917E+09 | 81226487.11 | 0.194426E+10 |
December | 0.368795E+09 | 0.00 | 0.368795E+09 | 36678075.76 | 0.249014E+10 |
Annual Sum or Average | 0.901372E+10 | 0.279235E+09 | 0.873449E+10 | 0.719168E+10 | 0.163633E+11 |
Minimum of Months | 0.368795E+09 | 0.00 | 0.368795E+09 | 36678075.76 | 0.428587E+09 |
Maximum of Months | 0.122726E+10 | 0.136061E+09 | 0.112171E+10 | 0.157144E+10 | 0.249014E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.394155E+09 | 0.00 | 0.394155E+09 | 45684346.63 | 0.219455E+10 |
February | 0.447462E+09 | 0.00 | 0.447462E+09 | 53885694.62 | 0.199759E+10 |
March | 0.674083E+09 | 0.00 | 0.674083E+09 | 0.240923E+09 | 0.170325E+10 |
April | 0.819243E+09 | 4544810.02 | 0.814699E+09 | 0.373825E+09 | 0.145546E+10 |
May | 0.115644E+10 | 38227274.48 | 0.111821E+10 | 0.962279E+09 | 0.832330E+09 |
June | 0.122721E+10 | 0.136056E+09 | 0.109115E+10 | 0.157138E+10 | 0.438270E+09 |
July | 0.119929E+10 | 77632404.68 | 0.112166E+10 | 0.155405E+10 | 0.428570E+09 |
August | 0.954547E+09 | 22581365.01 | 0.931965E+09 | 0.117324E+10 | 0.493965E+09 |
September | 0.775954E+09 | 182257.92 | 0.775772E+09 | 0.832594E+09 | 0.743398E+09 |
October | 0.574296E+09 | 0.00 | 0.574296E+09 | 0.265640E+09 | 0.164105E+10 |
November | 0.421900E+09 | 0.00 | 0.421900E+09 | 81223328.49 | 0.194418E+10 |
December | 0.368781E+09 | 0.00 | 0.368781E+09 | 36676651.37 | 0.249004E+10 |
Annual Sum or Average | 0.901337E+10 | 0.279224E+09 | 0.873414E+10 | 0.719140E+10 | 0.163627E+11 |
Minimum of Months | 0.368781E+09 | 0.00 | 0.368781E+09 | 36676651.37 | 0.428570E+09 |
Maximum of Months | 0.122721E+10 | 0.136056E+09 | 0.112166E+10 | 0.157138E+10 | 0.249004E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.137140E+10 | 0.840435E+09 | 0.530964E+09 | 0.112871E+10 | 0.223100E+10 |
February | 0.164545E+10 | 0.103877E+10 | 0.606685E+09 | 0.146173E+10 | 0.206776E+10 |
March | 0.219880E+10 | 0.128254E+10 | 0.916261E+09 | 0.211777E+10 | 0.175451E+10 |
April | 0.218225E+10 | 0.106301E+10 | 0.111924E+10 | 0.205355E+10 | 0.150635E+10 |
May | 0.263605E+10 | 0.110109E+10 | 0.153496E+10 | 0.286764E+10 | 0.910542E+09 |
June | 0.311250E+10 | 0.163398E+10 | 0.147852E+10 | 0.407925E+10 | 0.475223E+09 |
July | 0.292383E+10 | 0.139226E+10 | 0.153157E+10 | 0.386921E+10 | 0.452747E+09 |
August | 0.294908E+10 | 0.162425E+10 | 0.132483E+10 | 0.387772E+10 | 0.510484E+09 |
September | 0.237463E+10 | 0.128997E+10 | 0.108467E+10 | 0.294266E+10 | 0.774497E+09 |
October | 0.177703E+10 | 0.973710E+09 | 0.803321E+09 | 0.178322E+10 | 0.173123E+10 |
November | 0.133857E+10 | 0.755771E+09 | 0.582801E+09 | 0.117333E+10 | 0.200076E+10 |
December | 0.119747E+10 | 0.689830E+09 | 0.507644E+09 | 0.936677E+09 | 0.253347E+10 |
Annual Sum or Average | 0.257071E+11 | 0.136856E+11 | 0.120215E+11 | 0.282915E+11 | 0.169486E+11 |
Minimum of Months | 0.119747E+10 | 0.689830E+09 | 0.507644E+09 | 0.936677E+09 | 0.452747E+09 |
Maximum of Months | 0.311250E+10 | 0.163398E+10 | 0.153496E+10 | 0.407925E+10 | 0.253347E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.137140E+10 | 0.840435E+09 | 0.530964E+09 | 0.112871E+10 | 0.223100E+10 |
February | 0.164545E+10 | 0.103877E+10 | 0.606685E+09 | 0.146173E+10 | 0.206776E+10 |
March | 0.219880E+10 | 0.128254E+10 | 0.916261E+09 | 0.211777E+10 | 0.175451E+10 |
April | 0.218225E+10 | 0.106301E+10 | 0.111924E+10 | 0.205355E+10 | 0.150635E+10 |
May | 0.263605E+10 | 0.110109E+10 | 0.153496E+10 | 0.286764E+10 | 0.910542E+09 |
June | 0.311250E+10 | 0.163398E+10 | 0.147852E+10 | 0.407925E+10 | 0.475223E+09 |
July | 0.292383E+10 | 0.139226E+10 | 0.153157E+10 | 0.386921E+10 | 0.452747E+09 |
August | 0.294908E+10 | 0.162425E+10 | 0.132483E+10 | 0.387772E+10 | 0.510484E+09 |
September | 0.237463E+10 | 0.128997E+10 | 0.108467E+10 | 0.294266E+10 | 0.774497E+09 |
October | 0.177703E+10 | 0.973710E+09 | 0.803321E+09 | 0.178322E+10 | 0.173123E+10 |
November | 0.133857E+10 | 0.755771E+09 | 0.582801E+09 | 0.117333E+10 | 0.200076E+10 |
December | 0.119747E+10 | 0.689830E+09 | 0.507644E+09 | 0.936677E+09 | 0.253347E+10 |
Annual Sum or Average | 0.257071E+11 | 0.136856E+11 | 0.120215E+11 | 0.282915E+11 | 0.169486E+11 |
Minimum of Months | 0.119747E+10 | 0.689830E+09 | 0.507644E+09 | 0.936677E+09 | 0.452747E+09 |
Maximum of Months | 0.311250E+10 | 0.163398E+10 | 0.153496E+10 | 0.407925E+10 | 0.253347E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.137137E+10 | 0.840419E+09 | 0.530954E+09 | 0.112869E+10 | 0.223096E+10 |
February | 0.164542E+10 | 0.103875E+10 | 0.606674E+09 | 0.146170E+10 | 0.206773E+10 |
March | 0.219876E+10 | 0.128252E+10 | 0.916244E+09 | 0.211773E+10 | 0.175448E+10 |
April | 0.218221E+10 | 0.106299E+10 | 0.111922E+10 | 0.205351E+10 | 0.150632E+10 |
May | 0.263600E+10 | 0.110107E+10 | 0.153493E+10 | 0.286759E+10 | 0.910525E+09 |
June | 0.311245E+10 | 0.163395E+10 | 0.147849E+10 | 0.407917E+10 | 0.475214E+09 |
July | 0.292378E+10 | 0.139223E+10 | 0.153155E+10 | 0.386914E+10 | 0.452739E+09 |
August | 0.294903E+10 | 0.162422E+10 | 0.132481E+10 | 0.387765E+10 | 0.510474E+09 |
September | 0.237459E+10 | 0.128994E+10 | 0.108465E+10 | 0.294261E+10 | 0.774483E+09 |
October | 0.177700E+10 | 0.973692E+09 | 0.803306E+09 | 0.178318E+10 | 0.173120E+10 |
November | 0.133855E+10 | 0.755757E+09 | 0.582790E+09 | 0.117331E+10 | 0.200073E+10 |
December | 0.119745E+10 | 0.689818E+09 | 0.507634E+09 | 0.936660E+09 | 0.253342E+10 |
Annual Sum or Average | 0.257066E+11 | 0.136854E+11 | 0.120212E+11 | 0.282909E+11 | 0.169483E+11 |
Minimum of Months | 0.119745E+10 | 0.689818E+09 | 0.507634E+09 | 0.936660E+09 | 0.452739E+09 |
Maximum of Months | 0.311245E+10 | 0.163395E+10 | 0.153493E+10 | 0.407917E+10 | 0.253342E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.377768E+10 | 0.310755E+10 | 0.670130E+09 | 0.415561E+10 | 0.190248E+10 |
February | 0.327283E+10 | 0.260931E+10 | 0.663523E+09 | 0.356791E+10 | 0.178807E+10 |
March | 0.267152E+10 | 0.175771E+10 | 0.913810E+09 | 0.294466E+10 | 0.160220E+10 |
April | 0.167446E+10 | 0.673306E+09 | 0.100115E+10 | 0.166263E+10 | 0.142156E+10 |
May | 0.158560E+10 | 0.290630E+09 | 0.129497E+10 | 0.173135E+10 | 0.892902E+09 |
June | 0.141472E+10 | 0.258571E+09 | 0.115615E+10 | 0.198096E+10 | 0.478092E+09 |
July | 0.152178E+10 | 0.272508E+09 | 0.124927E+10 | 0.213689E+10 | 0.455455E+09 |
August | 0.193753E+10 | 0.809962E+09 | 0.112757E+10 | 0.273587E+10 | 0.515020E+09 |
September | 0.241241E+10 | 0.134611E+10 | 0.106630E+10 | 0.319534E+10 | 0.756154E+09 |
October | 0.298069E+10 | 0.211487E+10 | 0.865822E+09 | 0.349493E+10 | 0.157325E+10 |
November | 0.351441E+10 | 0.280149E+10 | 0.712915E+09 | 0.395924E+10 | 0.176525E+10 |
December | 0.347271E+10 | 0.281077E+10 | 0.661947E+09 | 0.373201E+10 | 0.215561E+10 |
Annual Sum or Average | 0.302363E+11 | 0.188528E+11 | 0.113836E+11 | 0.352974E+11 | 0.153060E+11 |
Minimum of Months | 0.141472E+10 | 0.258571E+09 | 0.661947E+09 | 0.166263E+10 | 0.455455E+09 |
Maximum of Months | 0.377768E+10 | 0.310755E+10 | 0.129497E+10 | 0.415561E+10 | 0.215561E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.377767E+10 | 0.310754E+10 | 0.670130E+09 | 0.415560E+10 | 0.190248E+10 |
February | 0.327283E+10 | 0.260930E+10 | 0.663523E+09 | 0.356790E+10 | 0.178807E+10 |
March | 0.267151E+10 | 0.175770E+10 | 0.913809E+09 | 0.294466E+10 | 0.160220E+10 |
April | 0.167446E+10 | 0.673305E+09 | 0.100115E+10 | 0.166262E+10 | 0.142156E+10 |
May | 0.158560E+10 | 0.290630E+09 | 0.129497E+10 | 0.173135E+10 | 0.892902E+09 |
June | 0.141472E+10 | 0.258570E+09 | 0.115615E+10 | 0.198096E+10 | 0.478092E+09 |
July | 0.152178E+10 | 0.272508E+09 | 0.124927E+10 | 0.213689E+10 | 0.455455E+09 |
August | 0.193753E+10 | 0.809961E+09 | 0.112757E+10 | 0.273587E+10 | 0.515019E+09 |
September | 0.241241E+10 | 0.134611E+10 | 0.106630E+10 | 0.319534E+10 | 0.756154E+09 |
October | 0.298069E+10 | 0.211486E+10 | 0.865822E+09 | 0.349493E+10 | 0.157325E+10 |
November | 0.351440E+10 | 0.280149E+10 | 0.712914E+09 | 0.395924E+10 | 0.176525E+10 |
December | 0.347271E+10 | 0.281076E+10 | 0.661946E+09 | 0.373201E+10 | 0.215561E+10 |
Annual Sum or Average | 0.302363E+11 | 0.188528E+11 | 0.113835E+11 | 0.352974E+11 | 0.153060E+11 |
Minimum of Months | 0.141472E+10 | 0.258570E+09 | 0.661946E+09 | 0.166262E+10 | 0.455455E+09 |
Maximum of Months | 0.377767E+10 | 0.310754E+10 | 0.129497E+10 | 0.415560E+10 | 0.215561E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.377768E+10 | 0.310755E+10 | 0.670130E+09 | 0.415561E+10 | 0.190248E+10 |
February | 0.327283E+10 | 0.260931E+10 | 0.663523E+09 | 0.356791E+10 | 0.178807E+10 |
March | 0.267152E+10 | 0.175771E+10 | 0.913810E+09 | 0.294466E+10 | 0.160220E+10 |
April | 0.167446E+10 | 0.673306E+09 | 0.100115E+10 | 0.166263E+10 | 0.142156E+10 |
May | 0.158560E+10 | 0.290630E+09 | 0.129497E+10 | 0.173135E+10 | 0.892902E+09 |
June | 0.141472E+10 | 0.258571E+09 | 0.115615E+10 | 0.198096E+10 | 0.478092E+09 |
July | 0.152178E+10 | 0.272508E+09 | 0.124927E+10 | 0.213689E+10 | 0.455455E+09 |
August | 0.193753E+10 | 0.809962E+09 | 0.112757E+10 | 0.273587E+10 | 0.515020E+09 |
September | 0.241241E+10 | 0.134611E+10 | 0.106630E+10 | 0.319534E+10 | 0.756154E+09 |
October | 0.298069E+10 | 0.211487E+10 | 0.865822E+09 | 0.349493E+10 | 0.157325E+10 |
November | 0.351441E+10 | 0.280149E+10 | 0.712915E+09 | 0.395924E+10 | 0.176525E+10 |
December | 0.347271E+10 | 0.281077E+10 | 0.661947E+09 | 0.373201E+10 | 0.215561E+10 |
Annual Sum or Average | 0.302363E+11 | 0.188528E+11 | 0.113836E+11 | 0.352974E+11 | 0.153060E+11 |
Minimum of Months | 0.141472E+10 | 0.258571E+09 | 0.661947E+09 | 0.166263E+10 | 0.455455E+09 |
Maximum of Months | 0.377768E+10 | 0.310755E+10 | 0.129497E+10 | 0.415561E+10 | 0.215561E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.377767E+10 | 0.310754E+10 | 0.670130E+09 | 0.415560E+10 | 0.190248E+10 |
February | 0.327283E+10 | 0.260930E+10 | 0.663523E+09 | 0.356790E+10 | 0.178807E+10 |
March | 0.267151E+10 | 0.175770E+10 | 0.913809E+09 | 0.294466E+10 | 0.160220E+10 |
April | 0.167446E+10 | 0.673305E+09 | 0.100115E+10 | 0.166262E+10 | 0.142156E+10 |
May | 0.158560E+10 | 0.290630E+09 | 0.129497E+10 | 0.173135E+10 | 0.892902E+09 |
June | 0.141472E+10 | 0.258570E+09 | 0.115615E+10 | 0.198096E+10 | 0.478092E+09 |
July | 0.152178E+10 | 0.272508E+09 | 0.124927E+10 | 0.213689E+10 | 0.455455E+09 |
August | 0.193753E+10 | 0.809961E+09 | 0.112757E+10 | 0.273587E+10 | 0.515019E+09 |
September | 0.241241E+10 | 0.134611E+10 | 0.106630E+10 | 0.319534E+10 | 0.756154E+09 |
October | 0.298069E+10 | 0.211486E+10 | 0.865822E+09 | 0.349493E+10 | 0.157325E+10 |
November | 0.351440E+10 | 0.280149E+10 | 0.712914E+09 | 0.395924E+10 | 0.176525E+10 |
December | 0.347271E+10 | 0.281076E+10 | 0.661946E+09 | 0.373201E+10 | 0.215561E+10 |
Annual Sum or Average | 0.302363E+11 | 0.188528E+11 | 0.113835E+11 | 0.352974E+11 | 0.153060E+11 |
Minimum of Months | 0.141472E+10 | 0.258570E+09 | 0.661946E+09 | 0.166262E+10 | 0.455455E+09 |
Maximum of Months | 0.377767E+10 | 0.310754E+10 | 0.129497E+10 | 0.415560E+10 | 0.215561E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.377752E+10 | 0.310742E+10 | 0.670103E+09 | 0.415544E+10 | 0.190240E+10 |
February | 0.327270E+10 | 0.260920E+10 | 0.663497E+09 | 0.356776E+10 | 0.178800E+10 |
March | 0.267141E+10 | 0.175764E+10 | 0.913773E+09 | 0.294455E+10 | 0.160214E+10 |
April | 0.167439E+10 | 0.673279E+09 | 0.100111E+10 | 0.166256E+10 | 0.142151E+10 |
May | 0.158554E+10 | 0.290618E+09 | 0.129492E+10 | 0.173128E+10 | 0.892866E+09 |
June | 0.141466E+10 | 0.258560E+09 | 0.115610E+10 | 0.198088E+10 | 0.478072E+09 |
July | 0.152172E+10 | 0.272497E+09 | 0.124922E+10 | 0.213680E+10 | 0.455437E+09 |
August | 0.193745E+10 | 0.809929E+09 | 0.112753E+10 | 0.273576E+10 | 0.514999E+09 |
September | 0.241231E+10 | 0.134606E+10 | 0.106626E+10 | 0.319521E+10 | 0.756124E+09 |
October | 0.298057E+10 | 0.211478E+10 | 0.865788E+09 | 0.349479E+10 | 0.157318E+10 |
November | 0.351427E+10 | 0.280138E+10 | 0.712886E+09 | 0.395908E+10 | 0.176518E+10 |
December | 0.347257E+10 | 0.281065E+10 | 0.661920E+09 | 0.373186E+10 | 0.215552E+10 |
Annual Sum or Average | 0.302351E+11 | 0.188520E+11 | 0.113831E+11 | 0.352960E+11 | 0.153054E+11 |
Minimum of Months | 0.141466E+10 | 0.258560E+09 | 0.661920E+09 | 0.166256E+10 | 0.455437E+09 |
Maximum of Months | 0.377752E+10 | 0.310742E+10 | 0.129492E+10 | 0.415544E+10 | 0.215552E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.145886E+10 | 0.924414E+09 | 0.534447E+09 | 0.129395E+10 | 0.238622E+10 |
February | 0.158894E+10 | 0.984671E+09 | 0.604266E+09 | 0.139878E+10 | 0.223504E+10 |
March | 0.205989E+10 | 0.113649E+10 | 0.923401E+09 | 0.192244E+10 | 0.198385E+10 |
April | 0.187691E+10 | 0.794654E+09 | 0.108226E+10 | 0.164550E+10 | 0.176942E+10 |
May | 0.237054E+10 | 0.835704E+09 | 0.153484E+10 | 0.255095E+10 | 0.104139E+10 |
June | 0.280579E+10 | 0.134997E+10 | 0.145581E+10 | 0.368409E+10 | 0.609541E+09 |
July | 0.236226E+10 | 0.865251E+09 | 0.149700E+10 | 0.308886E+10 | 0.589234E+09 |
August | 0.246552E+10 | 0.121800E+10 | 0.124752E+10 | 0.316884E+10 | 0.671903E+09 |
September | 0.211566E+10 | 0.101460E+10 | 0.110106E+10 | 0.261663E+10 | 0.898925E+09 |
October | 0.183916E+10 | 0.105122E+10 | 0.787942E+09 | 0.188204E+10 | 0.190524E+10 |
November | 0.146045E+10 | 0.886671E+09 | 0.573774E+09 | 0.131741E+10 | 0.222465E+10 |
December | 0.121896E+10 | 0.720073E+09 | 0.498888E+09 | 0.952269E+09 | 0.281554E+10 |
Annual Sum or Average | 0.236229E+11 | 0.117817E+11 | 0.118412E+11 | 0.255218E+11 | 0.191309E+11 |
Minimum of Months | 0.121896E+10 | 0.720073E+09 | 0.498888E+09 | 0.952269E+09 | 0.589234E+09 |
Maximum of Months | 0.280579E+10 | 0.134997E+10 | 0.153484E+10 | 0.368409E+10 | 0.281554E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.145886E+10 | 0.924414E+09 | 0.534447E+09 | 0.129395E+10 | 0.238622E+10 |
February | 0.158894E+10 | 0.984671E+09 | 0.604266E+09 | 0.139878E+10 | 0.223504E+10 |
March | 0.205989E+10 | 0.113649E+10 | 0.923401E+09 | 0.192244E+10 | 0.198385E+10 |
April | 0.187691E+10 | 0.794654E+09 | 0.108226E+10 | 0.164550E+10 | 0.176942E+10 |
May | 0.237054E+10 | 0.835704E+09 | 0.153484E+10 | 0.255095E+10 | 0.104139E+10 |
June | 0.280579E+10 | 0.134997E+10 | 0.145581E+10 | 0.368409E+10 | 0.609541E+09 |
July | 0.236226E+10 | 0.865251E+09 | 0.149700E+10 | 0.308886E+10 | 0.589234E+09 |
August | 0.246552E+10 | 0.121800E+10 | 0.124752E+10 | 0.316884E+10 | 0.671903E+09 |
September | 0.211566E+10 | 0.101460E+10 | 0.110106E+10 | 0.261663E+10 | 0.898925E+09 |
October | 0.183916E+10 | 0.105122E+10 | 0.787942E+09 | 0.188204E+10 | 0.190524E+10 |
November | 0.146045E+10 | 0.886671E+09 | 0.573774E+09 | 0.131741E+10 | 0.222465E+10 |
December | 0.121896E+10 | 0.720073E+09 | 0.498888E+09 | 0.952269E+09 | 0.281554E+10 |
Annual Sum or Average | 0.236229E+11 | 0.117817E+11 | 0.118412E+11 | 0.255218E+11 | 0.191309E+11 |
Minimum of Months | 0.121896E+10 | 0.720073E+09 | 0.498888E+09 | 0.952269E+09 | 0.589234E+09 |
Maximum of Months | 0.280579E+10 | 0.134997E+10 | 0.153484E+10 | 0.368409E+10 | 0.281554E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.145884E+10 | 0.924397E+09 | 0.534438E+09 | 0.129393E+10 | 0.238617E+10 |
February | 0.158891E+10 | 0.984653E+09 | 0.604255E+09 | 0.139876E+10 | 0.223500E+10 |
March | 0.205985E+10 | 0.113646E+10 | 0.923384E+09 | 0.192240E+10 | 0.198382E+10 |
April | 0.187688E+10 | 0.794639E+09 | 0.108224E+10 | 0.164547E+10 | 0.176938E+10 |
May | 0.237050E+10 | 0.835688E+09 | 0.153481E+10 | 0.255090E+10 | 0.104137E+10 |
June | 0.280574E+10 | 0.134995E+10 | 0.145579E+10 | 0.368403E+10 | 0.609530E+09 |
July | 0.236221E+10 | 0.865235E+09 | 0.149698E+10 | 0.308881E+10 | 0.589224E+09 |
August | 0.246548E+10 | 0.121798E+10 | 0.124750E+10 | 0.316878E+10 | 0.671890E+09 |
September | 0.211562E+10 | 0.101458E+10 | 0.110104E+10 | 0.261659E+10 | 0.898908E+09 |
October | 0.183913E+10 | 0.105120E+10 | 0.787928E+09 | 0.188201E+10 | 0.190520E+10 |
November | 0.146042E+10 | 0.886655E+09 | 0.573763E+09 | 0.131739E+10 | 0.222461E+10 |
December | 0.121894E+10 | 0.720060E+09 | 0.498879E+09 | 0.952251E+09 | 0.281548E+10 |
Annual Sum or Average | 0.236225E+11 | 0.117815E+11 | 0.118410E+11 | 0.255213E+11 | 0.191306E+11 |
Minimum of Months | 0.121894E+10 | 0.720060E+09 | 0.498879E+09 | 0.952251E+09 | 0.589224E+09 |
Maximum of Months | 0.280574E+10 | 0.134995E+10 | 0.153481E+10 | 0.368403E+10 | 0.281548E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.197083E+10 | 0.00 | 0.197083E+10 | 0.323032E+09 | 0.998277E+10 |
February | 0.223737E+10 | 0.00 | 0.223737E+10 | 0.378794E+09 | 0.909548E+10 |
March | 0.337051E+10 | 0.00 | 0.337051E+10 | 0.139887E+10 | 0.767298E+10 |
April | 0.409633E+10 | 22724691.21 | 0.407361E+10 | 0.206275E+10 | 0.641224E+10 |
May | 0.578237E+10 | 0.191142E+09 | 0.559123E+10 | 0.491643E+10 | 0.393665E+10 |
June | 0.613622E+10 | 0.680300E+09 | 0.545592E+10 | 0.791222E+10 | 0.211351E+10 |
July | 0.599664E+10 | 0.388173E+09 | 0.560846E+10 | 0.783470E+10 | 0.207265E+10 |
August | 0.477287E+10 | 0.112910E+09 | 0.465996E+10 | 0.595706E+10 | 0.236036E+10 |
September | 0.387988E+10 | 911315.33 | 0.387897E+10 | 0.425420E+10 | 0.349957E+10 |
October | 0.287156E+10 | 0.00 | 0.287156E+10 | 0.148317E+10 | 0.751017E+10 |
November | 0.210956E+10 | 0.00 | 0.210956E+10 | 0.538774E+09 | 0.872552E+10 |
December | 0.184396E+10 | 0.00 | 0.184396E+10 | 0.294104E+09 | 0.111646E+11 |
Annual Sum or Average | 0.450681E+11 | 0.139616E+10 | 0.436719E+11 | 0.373541E+11 | 0.745465E+11 |
Minimum of Months | 0.184396E+10 | 0.00 | 0.184396E+10 | 0.294104E+09 | 0.207265E+10 |
Maximum of Months | 0.613622E+10 | 0.680300E+09 | 0.560846E+10 | 0.791222E+10 | 0.111646E+11 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.411415E+10 | 0.252128E+10 | 0.159288E+10 | 0.346405E+10 | 0.625271E+10 |
February | 0.493631E+10 | 0.311627E+10 | 0.182004E+10 | 0.441299E+10 | 0.581834E+10 |
March | 0.659634E+10 | 0.384759E+10 | 0.274875E+10 | 0.636797E+10 | 0.492110E+10 |
April | 0.654669E+10 | 0.318901E+10 | 0.335768E+10 | 0.617928E+10 | 0.415381E+10 |
May | 0.790807E+10 | 0.330323E+10 | 0.460484E+10 | 0.858028E+10 | 0.262635E+10 |
June | 0.933741E+10 | 0.490189E+10 | 0.443552E+10 | 0.121745E+11 | 0.141074E+10 |
July | 0.877140E+10 | 0.417672E+10 | 0.459467E+10 | 0.115375E+11 | 0.138655E+10 |
August | 0.884716E+10 | 0.487270E+10 | 0.397446E+10 | 0.115634E+11 | 0.157741E+10 |
September | 0.712382E+10 | 0.386986E+10 | 0.325396E+10 | 0.879995E+10 | 0.223433E+10 |
October | 0.533104E+10 | 0.292110E+10 | 0.240994E+10 | 0.536172E+10 | 0.489681E+10 |
November | 0.401567E+10 | 0.226729E+10 | 0.174838E+10 | 0.358047E+10 | 0.560317E+10 |
December | 0.359238E+10 | 0.206947E+10 | 0.152292E+10 | 0.289570E+10 | 0.705893E+10 |
Annual Sum or Average | 0.771205E+11 | 0.410564E+11 | 0.360640E+11 | 0.849177E+11 | 0.479402E+11 |
Minimum of Months | 0.359238E+10 | 0.206947E+10 | 0.152292E+10 | 0.289570E+10 | 0.138655E+10 |
Maximum of Months | 0.933741E+10 | 0.490189E+10 | 0.460484E+10 | 0.121745E+11 | 0.705893E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.188881E+11 | 0.155375E+11 | 0.335061E+10 | 0.206408E+11 | 0.939436E+10 |
February | 0.163640E+11 | 0.130464E+11 | 0.331758E+10 | 0.176889E+11 | 0.872620E+10 |
March | 0.133574E+11 | 0.878843E+10 | 0.456900E+10 | 0.146463E+11 | 0.769444E+10 |
April | 0.837219E+10 | 0.336649E+10 | 0.500570E+10 | 0.832576E+10 | 0.665744E+10 |
May | 0.792793E+10 | 0.145313E+10 | 0.647479E+10 | 0.864977E+10 | 0.433650E+10 |
June | 0.707350E+10 | 0.129284E+10 | 0.578066E+10 | 0.991722E+10 | 0.231945E+10 |
July | 0.760880E+10 | 0.136252E+10 | 0.624627E+10 | 0.106938E+11 | 0.223860E+10 |
August | 0.968754E+10 | 0.404976E+10 | 0.563779E+10 | 0.136520E+11 | 0.254224E+10 |
September | 0.120619E+11 | 0.673048E+10 | 0.533143E+10 | 0.158864E+11 | 0.370593E+10 |
October | 0.149033E+11 | 0.105742E+11 | 0.432906E+10 | 0.173656E+11 | 0.767487E+10 |
November | 0.175718E+11 | 0.140073E+11 | 0.356453E+10 | 0.196699E+11 | 0.861504E+10 |
December | 0.173634E+11 | 0.140537E+11 | 0.330969E+10 | 0.185907E+11 | 0.103813E+11 |
Annual Sum or Average | 0.151180E+12 | 0.942627E+11 | 0.569171E+11 | 0.175727E+12 | 0.742864E+11 |
Minimum of Months | 0.707350E+10 | 0.129284E+10 | 0.330969E+10 | 0.832576E+10 | 0.223860E+10 |
Maximum of Months | 0.188881E+11 | 0.155375E+11 | 0.647479E+10 | 0.206408E+11 | 0.103813E+11 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.437654E+10 | 0.277321E+10 | 0.160333E+10 | 0.398718E+10 | 0.656425E+10 |
February | 0.476676E+10 | 0.295398E+10 | 0.181278E+10 | 0.431009E+10 | 0.603660E+10 |
March | 0.617960E+10 | 0.340942E+10 | 0.277017E+10 | 0.595066E+10 | 0.517602E+10 |
April | 0.563069E+10 | 0.238394E+10 | 0.324675E+10 | 0.515125E+10 | 0.439542E+10 |
May | 0.711155E+10 | 0.250709E+10 | 0.460446E+10 | 0.775102E+10 | 0.288817E+10 |
June | 0.841728E+10 | 0.404988E+10 | 0.436740E+10 | 0.111342E+11 | 0.167127E+10 |
July | 0.708669E+10 | 0.259573E+10 | 0.449097E+10 | 0.939800E+10 | 0.158107E+10 |
August | 0.739650E+10 | 0.365398E+10 | 0.374252E+10 | 0.966560E+10 | 0.176898E+10 |
September | 0.634691E+10 | 0.304377E+10 | 0.330314E+10 | 0.792633E+10 | 0.248529E+10 |
October | 0.551742E+10 | 0.315362E+10 | 0.236380E+10 | 0.578079E+10 | 0.511689E+10 |
November | 0.438129E+10 | 0.265999E+10 | 0.172130E+10 | 0.411659E+10 | 0.583526E+10 |
December | 0.365685E+10 | 0.216020E+10 | 0.149665E+10 | 0.303533E+10 | 0.725318E+10 |
Annual Sum or Average | 0.708681E+11 | 0.353448E+11 | 0.355233E+11 | 0.782070E+11 | 0.507724E+11 |
Minimum of Months | 0.365685E+10 | 0.216020E+10 | 0.149665E+10 | 0.303533E+10 | 0.158107E+10 |
Maximum of Months | 0.841728E+10 | 0.404988E+10 | 0.460446E+10 | 0.111342E+11 | 0.725318E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.197083E+10 | 0.00 | 0.197083E+10 | 0.390657E+09 | 0.936219E+10 |
February | 0.223737E+10 | 0.00 | 0.223737E+10 | 0.432401E+09 | 0.865921E+10 |
March | 0.337051E+10 | 0.00 | 0.337051E+10 | 0.146931E+10 | 0.727915E+10 |
April | 0.409633E+10 | 22724691.21 | 0.407361E+10 | 0.214415E+10 | 0.594641E+10 |
May | 0.578237E+10 | 0.191142E+09 | 0.559123E+10 | 0.500955E+10 | 0.375822E+10 |
June | 0.613622E+10 | 0.680300E+09 | 0.545592E+10 | 0.786941E+10 | 0.209224E+10 |
July | 0.599664E+10 | 0.388173E+09 | 0.560846E+10 | 0.779245E+10 | 0.205622E+10 |
August | 0.477287E+10 | 0.112910E+09 | 0.465996E+10 | 0.593195E+10 | 0.232172E+10 |
September | 0.387988E+10 | 911315.33 | 0.387897E+10 | 0.427659E+10 | 0.336822E+10 |
October | 0.287156E+10 | 0.00 | 0.287156E+10 | 0.157986E+10 | 0.703130E+10 |
November | 0.210956E+10 | 0.00 | 0.210956E+10 | 0.625050E+09 | 0.815496E+10 |
December | 0.184396E+10 | 0.00 | 0.184396E+10 | 0.336455E+09 | 0.106476E+11 |
Annual Sum or Average | 0.450681E+11 | 0.139616E+10 | 0.436719E+11 | 0.378578E+11 | 0.706774E+11 |
Minimum of Months | 0.184396E+10 | 0.00 | 0.184396E+10 | 0.336455E+09 | 0.205622E+10 |
Maximum of Months | 0.613622E+10 | 0.680300E+09 | 0.560846E+10 | 0.786941E+10 | 0.106476E+11 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.411415E+10 | 0.252128E+10 | 0.159288E+10 | 0.356007E+10 | 0.587190E+10 |
February | 0.493631E+10 | 0.311627E+10 | 0.182004E+10 | 0.447122E+10 | 0.556343E+10 |
March | 0.659634E+10 | 0.384759E+10 | 0.274875E+10 | 0.640875E+10 | 0.470247E+10 |
April | 0.654669E+10 | 0.318901E+10 | 0.335768E+10 | 0.622033E+10 | 0.387910E+10 |
May | 0.790807E+10 | 0.330323E+10 | 0.460484E+10 | 0.860768E+10 | 0.253594E+10 |
June | 0.933741E+10 | 0.490189E+10 | 0.443552E+10 | 0.121277E+11 | 0.140416E+10 |
July | 0.877140E+10 | 0.417672E+10 | 0.459467E+10 | 0.114941E+11 | 0.138154E+10 |
August | 0.884716E+10 | 0.487270E+10 | 0.397446E+10 | 0.115276E+11 | 0.156453E+10 |
September | 0.712382E+10 | 0.386986E+10 | 0.325396E+10 | 0.879252E+10 | 0.217863E+10 |
October | 0.533104E+10 | 0.292110E+10 | 0.240994E+10 | 0.540261E+10 | 0.463601E+10 |
November | 0.401567E+10 | 0.226729E+10 | 0.174838E+10 | 0.366113E+10 | 0.528120E+10 |
December | 0.359238E+10 | 0.206947E+10 | 0.152292E+10 | 0.296513E+10 | 0.674950E+10 |
Annual Sum or Average | 0.771205E+11 | 0.410564E+11 | 0.360640E+11 | 0.852388E+11 | 0.457484E+11 |
Minimum of Months | 0.359238E+10 | 0.206947E+10 | 0.152292E+10 | 0.296513E+10 | 0.138154E+10 |
Maximum of Months | 0.933741E+10 | 0.490189E+10 | 0.460484E+10 | 0.121277E+11 | 0.674950E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.188881E+11 | 0.155375E+11 | 0.335061E+10 | 0.208156E+11 | 0.879597E+10 |
February | 0.163640E+11 | 0.130464E+11 | 0.331758E+10 | 0.177730E+11 | 0.831022E+10 |
March | 0.133574E+11 | 0.878843E+10 | 0.456900E+10 | 0.147022E+11 | 0.732151E+10 |
April | 0.837219E+10 | 0.336649E+10 | 0.500570E+10 | 0.838275E+10 | 0.620551E+10 |
May | 0.792793E+10 | 0.145313E+10 | 0.647479E+10 | 0.870158E+10 | 0.414900E+10 |
June | 0.707350E+10 | 0.129284E+10 | 0.578066E+10 | 0.987235E+10 | 0.228963E+10 |
July | 0.760880E+10 | 0.136252E+10 | 0.624627E+10 | 0.106485E+11 | 0.221438E+10 |
August | 0.968754E+10 | 0.404976E+10 | 0.563779E+10 | 0.136107E+11 | 0.250393E+10 |
September | 0.120619E+11 | 0.673048E+10 | 0.533143E+10 | 0.158754E+11 | 0.359446E+10 |
October | 0.149033E+11 | 0.105742E+11 | 0.432906E+10 | 0.174267E+11 | 0.725301E+10 |
November | 0.175718E+11 | 0.140073E+11 | 0.356453E+10 | 0.197803E+11 | 0.813619E+10 |
December | 0.173634E+11 | 0.140537E+11 | 0.330969E+10 | 0.187099E+11 | 0.987350E+10 |
Annual Sum or Average | 0.151180E+12 | 0.942627E+11 | 0.569171E+11 | 0.176299E+12 | 0.706473E+11 |
Minimum of Months | 0.707350E+10 | 0.129284E+10 | 0.330969E+10 | 0.838275E+10 | 0.221438E+10 |
Maximum of Months | 0.188881E+11 | 0.155375E+11 | 0.647479E+10 | 0.208156E+11 | 0.987350E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.437654E+10 | 0.277321E+10 | 0.160333E+10 | 0.404156E+10 | 0.619017E+10 |
February | 0.476676E+10 | 0.295398E+10 | 0.181278E+10 | 0.433318E+10 | 0.578878E+10 |
March | 0.617960E+10 | 0.340942E+10 | 0.277017E+10 | 0.596971E+10 | 0.495036E+10 |
April | 0.563069E+10 | 0.238394E+10 | 0.324675E+10 | 0.517497E+10 | 0.412784E+10 |
May | 0.711155E+10 | 0.250709E+10 | 0.460446E+10 | 0.777203E+10 | 0.278154E+10 |
June | 0.841728E+10 | 0.404988E+10 | 0.436740E+10 | 0.110996E+11 | 0.165075E+10 |
July | 0.708669E+10 | 0.259573E+10 | 0.449097E+10 | 0.936623E+10 | 0.156185E+10 |
August | 0.739650E+10 | 0.365398E+10 | 0.374252E+10 | 0.964179E+10 | 0.174293E+10 |
September | 0.634691E+10 | 0.304377E+10 | 0.330314E+10 | 0.792516E+10 | 0.241401E+10 |
October | 0.551742E+10 | 0.315362E+10 | 0.236380E+10 | 0.581094E+10 | 0.486322E+10 |
November | 0.438129E+10 | 0.265999E+10 | 0.172130E+10 | 0.415731E+10 | 0.553980E+10 |
December | 0.365685E+10 | 0.216020E+10 | 0.149665E+10 | 0.306512E+10 | 0.696084E+10 |
Annual Sum or Average | 0.708681E+11 | 0.353448E+11 | 0.355233E+11 | 0.783576E+11 | 0.485721E+11 |
Minimum of Months | 0.365685E+10 | 0.216020E+10 | 0.149665E+10 | 0.306512E+10 | 0.156185E+10 |
Maximum of Months | 0.841728E+10 | 0.404988E+10 | 0.460446E+10 | 0.110996E+11 | 0.696084E+10 |
Report: WindowZoneSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 85.29 | 4096.89 | 735.83 | 0.00 | 735.83 | 0.00 | 0.00 |
February | 111.37 | 4128.75 | 924.84 | 0.00 | 924.84 | 0.00 | 0.00 |
March | 449.77 | 3179.71 | 1258.41 | 0.00 | 1258.41 | 0.00 | 0.00 |
April | 721.14 | 2807.69 | 1580.38 | 8.77 | 1571.61 | 0.00 | 0.00 |
May | 1796.43 | 1553.83 | 2158.90 | 71.36 | 2087.53 | 0.00 | 0.00 |
June | 3031.30 | 845.46 | 2367.38 | 262.46 | 2104.92 | 0.00 | 0.00 |
July | 2901.17 | 800.07 | 2238.90 | 144.93 | 2093.97 | 0.00 | 0.00 |
August | 2190.25 | 922.16 | 1781.99 | 42.16 | 1739.84 | 0.00 | 0.00 |
September | 1606.13 | 1434.07 | 1496.87 | 0.35 | 1496.52 | 0.00 | 0.00 |
October | 495.91 | 3063.59 | 1072.12 | 0.00 | 1072.12 | 0.00 | 0.00 |
November | 156.69 | 3750.46 | 813.88 | 0.00 | 813.88 | 0.00 | 0.00 |
December | 68.47 | 4648.52 | 688.46 | 0.00 | 688.46 | 0.00 | 0.00 |
Annual Sum or Average | 1140.22 | 2594.37 | 1429.11 | 44.27 | 1384.83 | 0.00 | 0.00 |
Minimum of Months | 68.47 | 800.07 | 688.46 | 0.00 | 688.46 | 0.00 | 0.00 |
Maximum of Months | 3031.30 | 4648.52 | 2367.38 | 262.46 | 2104.92 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1264.23 | 2498.87 | 1536.06 | 941.34 | 594.71 | 0.00 | 0.00 |
February | 1812.65 | 2564.18 | 2040.48 | 1288.15 | 752.33 | 0.00 | 0.00 |
March | 2372.04 | 1965.16 | 2462.80 | 1436.53 | 1026.27 | 0.00 | 0.00 |
April | 2376.77 | 1743.45 | 2525.74 | 1230.33 | 1295.41 | 0.00 | 0.00 |
May | 3211.94 | 1019.87 | 2952.55 | 1233.29 | 1719.26 | 0.00 | 0.00 |
June | 4721.32 | 550.02 | 3602.41 | 1891.17 | 1711.24 | 0.00 | 0.00 |
July | 4333.76 | 507.11 | 3274.88 | 1559.42 | 1715.46 | 0.00 | 0.00 |
August | 4343.30 | 571.77 | 3303.16 | 1819.26 | 1483.90 | 0.00 | 0.00 |
September | 3405.84 | 896.40 | 2748.40 | 1493.01 | 1255.39 | 0.00 | 0.00 |
October | 1997.32 | 1939.09 | 1990.39 | 1090.62 | 899.77 | 0.00 | 0.00 |
November | 1358.01 | 2315.68 | 1549.26 | 874.73 | 674.53 | 0.00 | 0.00 |
December | 1049.14 | 2837.65 | 1341.25 | 772.65 | 568.59 | 0.00 | 0.00 |
Annual Sum or Average | 2691.33 | 1612.30 | 2445.48 | 1301.90 | 1143.59 | 0.00 | 0.00 |
Minimum of Months | 1049.14 | 507.11 | 1341.25 | 772.65 | 568.59 | 0.00 | 0.00 |
Maximum of Months | 4721.32 | 2837.65 | 3602.41 | 1891.17 | 1719.26 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 7757.57 | 3551.49 | 7052.05 | 5801.07 | 1250.98 | 0.00 | 0.00 |
February | 7374.09 | 3695.55 | 6764.23 | 5392.87 | 1371.36 | 0.00 | 0.00 |
March | 5497.01 | 2990.95 | 4987.11 | 3281.23 | 1705.87 | 0.00 | 0.00 |
April | 3207.20 | 2742.19 | 3230.02 | 1298.80 | 1931.22 | 0.00 | 0.00 |
May | 3232.04 | 1666.84 | 2959.96 | 542.54 | 2417.42 | 0.00 | 0.00 |
June | 3821.26 | 922.24 | 2728.98 | 498.78 | 2230.20 | 0.00 | 0.00 |
July | 3989.08 | 850.23 | 2840.81 | 508.71 | 2332.10 | 0.00 | 0.00 |
August | 5107.24 | 961.42 | 3616.93 | 1512.01 | 2104.92 | 0.00 | 0.00 |
September | 6163.80 | 1458.62 | 4653.53 | 2596.64 | 2056.89 | 0.00 | 0.00 |
October | 6524.23 | 2936.89 | 5564.26 | 3947.97 | 1616.29 | 0.00 | 0.00 |
November | 7637.36 | 3405.17 | 6779.28 | 5404.07 | 1375.21 | 0.00 | 0.00 |
December | 6966.81 | 4024.03 | 6482.76 | 5247.06 | 1235.70 | 0.00 | 0.00 |
Annual Sum or Average | 5596.32 | 2426.74 | 4793.90 | 2989.06 | 1804.84 | 0.00 | 0.00 |
Minimum of Months | 3207.20 | 850.23 | 2728.98 | 498.78 | 1235.70 | 0.00 | 0.00 |
Maximum of Months | 7757.57 | 4024.03 | 7052.05 | 5801.07 | 2417.42 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1449.31 | 2672.72 | 1634.02 | 1035.40 | 598.62 | 0.00 | 0.00 |
February | 1734.59 | 2771.61 | 1970.40 | 1221.06 | 749.33 | 0.00 | 0.00 |
March | 2153.26 | 2222.04 | 2307.21 | 1272.94 | 1034.27 | 0.00 | 0.00 |
April | 1904.50 | 2047.92 | 2172.34 | 919.73 | 1252.61 | 0.00 | 0.00 |
May | 2857.23 | 1166.42 | 2655.16 | 936.04 | 1719.12 | 0.00 | 0.00 |
June | 4263.97 | 705.48 | 3247.42 | 1562.46 | 1684.96 | 0.00 | 0.00 |
July | 3459.73 | 659.98 | 2645.88 | 969.14 | 1676.74 | 0.00 | 0.00 |
August | 3549.30 | 752.57 | 2761.55 | 1364.24 | 1397.30 | 0.00 | 0.00 |
September | 3028.49 | 1040.42 | 2448.67 | 1174.30 | 1274.37 | 0.00 | 0.00 |
October | 2108.01 | 2133.99 | 2059.98 | 1177.43 | 882.55 | 0.00 | 0.00 |
November | 1524.78 | 2574.81 | 1690.32 | 1026.23 | 664.09 | 0.00 | 0.00 |
December | 1066.60 | 3153.58 | 1365.32 | 806.53 | 558.79 | 0.00 | 0.00 |
Annual Sum or Average | 2427.86 | 1819.90 | 2247.22 | 1120.78 | 1126.44 | 0.00 | 0.00 |
Minimum of Months | 1066.60 | 659.98 | 1365.32 | 806.53 | 558.79 | 0.00 | 0.00 |
Maximum of Months | 4263.97 | 3153.58 | 3247.42 | 1562.46 | 1719.12 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 120.61 | 3727.14 | 735.82 | 0.00 | 735.82 | 0.00 | 0.00 |
February | 156.58 | 3759.71 | 924.84 | 0.00 | 924.84 | 0.00 | 0.00 |
March | 522.28 | 2864.76 | 1258.40 | 0.00 | 1258.40 | 0.00 | 0.00 |
April | 795.81 | 2473.86 | 1580.38 | 8.77 | 1571.61 | 0.00 | 0.00 |
May | 1835.58 | 1469.78 | 2158.89 | 71.36 | 2087.52 | 0.00 | 0.00 |
June | 3052.55 | 815.40 | 2367.37 | 262.46 | 2104.91 | 0.00 | 0.00 |
July | 2925.14 | 773.84 | 2238.89 | 144.93 | 2093.96 | 0.00 | 0.00 |
August | 2224.11 | 881.26 | 1781.99 | 42.16 | 1739.83 | 0.00 | 0.00 |
September | 1641.28 | 1350.14 | 1496.87 | 0.35 | 1496.52 | 0.00 | 0.00 |
October | 553.75 | 2803.98 | 1072.12 | 0.00 | 1072.12 | 0.00 | 0.00 |
November | 207.86 | 3366.33 | 813.87 | 0.00 | 813.87 | 0.00 | 0.00 |
December | 109.81 | 4168.38 | 688.45 | 0.00 | 688.45 | 0.00 | 0.00 |
Annual Sum or Average | 1184.49 | 2363.85 | 1429.10 | 44.27 | 1384.83 | 0.00 | 0.00 |
Minimum of Months | 109.81 | 773.84 | 688.45 | 0.00 | 688.45 | 0.00 | 0.00 |
Maximum of Months | 3052.55 | 4168.38 | 2367.37 | 262.46 | 2104.91 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1293.33 | 2334.49 | 1536.05 | 941.34 | 594.71 | 0.00 | 0.00 |
February | 1824.15 | 2405.07 | 2040.47 | 1288.14 | 752.33 | 0.00 | 0.00 |
March | 2377.53 | 1837.33 | 2462.79 | 1436.53 | 1026.27 | 0.00 | 0.00 |
April | 2383.98 | 1602.55 | 2525.73 | 1230.33 | 1295.40 | 0.00 | 0.00 |
May | 3203.51 | 980.57 | 2952.54 | 1233.29 | 1719.25 | 0.00 | 0.00 |
June | 4696.94 | 544.27 | 3602.40 | 1891.16 | 1711.23 | 0.00 | 0.00 |
July | 4307.60 | 517.68 | 3274.86 | 1559.41 | 1715.45 | 0.00 | 0.00 |
August | 4317.27 | 588.94 | 3303.15 | 1819.26 | 1483.89 | 0.00 | 0.00 |
September | 3395.04 | 862.01 | 2748.39 | 1493.00 | 1255.39 | 0.00 | 0.00 |
October | 2001.84 | 1828.26 | 1990.38 | 1090.61 | 899.77 | 0.00 | 0.00 |
November | 1381.35 | 2161.72 | 1549.26 | 874.73 | 674.53 | 0.00 | 0.00 |
December | 1081.13 | 2635.50 | 1341.24 | 772.65 | 568.59 | 0.00 | 0.00 |
Annual Sum or Average | 2692.72 | 1520.17 | 2445.47 | 1301.89 | 1143.58 | 0.00 | 0.00 |
Minimum of Months | 1081.13 | 517.68 | 1341.24 | 772.65 | 568.59 | 0.00 | 0.00 |
Maximum of Months | 4696.94 | 2635.50 | 3602.40 | 1891.16 | 1719.25 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 7706.38 | 3507.45 | 7052.03 | 5801.05 | 1250.97 | 0.00 | 0.00 |
February | 7311.87 | 3607.06 | 6764.20 | 5392.85 | 1371.35 | 0.00 | 0.00 |
March | 5468.29 | 2872.78 | 4987.09 | 3281.22 | 1705.87 | 0.00 | 0.00 |
April | 3212.10 | 2568.46 | 3230.01 | 1298.80 | 1931.21 | 0.00 | 0.00 |
May | 3229.45 | 1619.06 | 2959.95 | 542.54 | 2417.41 | 0.00 | 0.00 |
June | 3826.09 | 894.85 | 2728.97 | 498.78 | 2230.19 | 0.00 | 0.00 |
July | 3992.62 | 835.80 | 2840.80 | 508.71 | 2332.09 | 0.00 | 0.00 |
August | 5097.07 | 949.16 | 3616.91 | 1512.01 | 2104.91 | 0.00 | 0.00 |
September | 6129.01 | 1429.76 | 4653.51 | 2596.64 | 2056.88 | 0.00 | 0.00 |
October | 6483.56 | 2865.47 | 5564.24 | 3947.96 | 1616.29 | 0.00 | 0.00 |
November | 7588.70 | 3323.70 | 6779.26 | 5404.05 | 1375.21 | 0.00 | 0.00 |
December | 6940.98 | 3875.94 | 6482.74 | 5247.04 | 1235.70 | 0.00 | 0.00 |
Annual Sum or Average | 5572.27 | 2355.61 | 4793.88 | 2989.05 | 1804.83 | 0.00 | 0.00 |
Minimum of Months | 3212.10 | 835.80 | 2728.97 | 498.78 | 1235.70 | 0.00 | 0.00 |
Maximum of Months | 7706.38 | 3875.94 | 7052.03 | 5801.05 | 2417.41 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1488.64 | 2450.81 | 1634.01 | 1035.40 | 598.61 | 0.00 | 0.00 |
February | 1781.62 | 2495.29 | 1970.39 | 1221.06 | 749.33 | 0.00 | 0.00 |
March | 2221.72 | 1932.51 | 2307.20 | 1272.93 | 1034.26 | 0.00 | 0.00 |
April | 1987.37 | 1695.76 | 2172.33 | 919.73 | 1252.60 | 0.00 | 0.00 |
May | 2893.90 | 1078.32 | 2655.15 | 936.04 | 1719.11 | 0.00 | 0.00 |
June | 4295.59 | 644.78 | 3247.41 | 1562.45 | 1684.95 | 0.00 | 0.00 |
July | 3508.81 | 590.30 | 2645.87 | 969.13 | 1676.74 | 0.00 | 0.00 |
August | 3608.72 | 660.46 | 2761.54 | 1364.24 | 1397.30 | 0.00 | 0.00 |
September | 3058.00 | 958.83 | 2448.66 | 1174.29 | 1274.36 | 0.00 | 0.00 |
October | 2158.30 | 1910.43 | 2059.97 | 1177.43 | 882.54 | 0.00 | 0.00 |
November | 1588.19 | 2251.26 | 1690.31 | 1026.23 | 664.08 | 0.00 | 0.00 |
December | 1133.26 | 2708.03 | 1365.31 | 806.53 | 558.79 | 0.00 | 0.00 |
Annual Sum or Average | 2479.93 | 1609.98 | 2247.21 | 1120.78 | 1126.44 | 0.00 | 0.00 |
Minimum of Months | 1133.26 | 590.30 | 1365.31 | 806.53 | 558.79 | 0.00 | 0.00 |
Maximum of Months | 4295.59 | 2708.03 | 3247.41 | 1562.45 | 1719.11 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 145.85 | 3495.44 | 735.82 | 0.00 | 735.82 | 0.00 | 0.00 |
February | 178.74 | 3579.37 | 924.84 | 0.00 | 924.84 | 0.00 | 0.00 |
March | 548.58 | 2717.72 | 1258.40 | 0.00 | 1258.40 | 0.00 | 0.00 |
April | 827.22 | 2294.14 | 1580.38 | 8.77 | 1571.61 | 0.00 | 0.00 |
May | 1870.35 | 1403.16 | 2158.89 | 71.36 | 2087.52 | 0.00 | 0.00 |
June | 3036.04 | 807.19 | 2367.37 | 262.46 | 2104.91 | 0.00 | 0.00 |
July | 2909.37 | 767.71 | 2238.89 | 144.93 | 2093.96 | 0.00 | 0.00 |
August | 2214.74 | 866.83 | 1781.99 | 42.16 | 1739.83 | 0.00 | 0.00 |
September | 1649.92 | 1299.47 | 1496.87 | 0.35 | 1496.52 | 0.00 | 0.00 |
October | 589.85 | 2625.19 | 1072.12 | 0.00 | 1072.12 | 0.00 | 0.00 |
November | 241.15 | 3146.21 | 813.87 | 0.00 | 813.87 | 0.00 | 0.00 |
December | 125.62 | 3975.35 | 688.45 | 0.00 | 688.45 | 0.00 | 0.00 |
Annual Sum or Average | 1200.46 | 2241.17 | 1429.10 | 44.27 | 1384.83 | 0.00 | 0.00 |
Minimum of Months | 125.62 | 767.71 | 688.45 | 0.00 | 688.45 | 0.00 | 0.00 |
Maximum of Months | 3036.04 | 3975.35 | 2367.37 | 262.46 | 2104.91 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1329.18 | 2192.32 | 1536.05 | 941.34 | 594.71 | 0.00 | 0.00 |
February | 1848.22 | 2299.70 | 2040.47 | 1288.14 | 752.33 | 0.00 | 0.00 |
March | 2392.75 | 1755.70 | 2462.79 | 1436.53 | 1026.27 | 0.00 | 0.00 |
April | 2399.82 | 1496.57 | 2525.73 | 1230.33 | 1295.40 | 0.00 | 0.00 |
May | 3213.74 | 946.81 | 2952.54 | 1233.29 | 1719.25 | 0.00 | 0.00 |
June | 4678.89 | 541.73 | 3602.40 | 1891.16 | 1711.23 | 0.00 | 0.00 |
July | 4291.41 | 515.81 | 3274.86 | 1559.41 | 1715.45 | 0.00 | 0.00 |
August | 4303.91 | 584.13 | 3303.15 | 1819.26 | 1483.89 | 0.00 | 0.00 |
September | 3392.18 | 840.52 | 2748.39 | 1493.00 | 1255.39 | 0.00 | 0.00 |
October | 2017.10 | 1730.89 | 1990.38 | 1090.61 | 899.77 | 0.00 | 0.00 |
November | 1412.47 | 2037.50 | 1549.26 | 874.73 | 674.53 | 0.00 | 0.00 |
December | 1107.05 | 2519.97 | 1341.24 | 772.65 | 568.59 | 0.00 | 0.00 |
Annual Sum or Average | 2702.90 | 1450.67 | 2445.47 | 1301.89 | 1143.58 | 0.00 | 0.00 |
Minimum of Months | 1107.05 | 515.81 | 1341.24 | 772.65 | 568.59 | 0.00 | 0.00 |
Maximum of Months | 4678.89 | 2519.97 | 3602.40 | 1891.16 | 1719.25 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 7771.67 | 3284.04 | 7052.03 | 5801.05 | 1250.97 | 0.00 | 0.00 |
February | 7346.63 | 3435.11 | 6764.20 | 5392.85 | 1371.35 | 0.00 | 0.00 |
March | 5489.19 | 2733.54 | 4987.09 | 3281.22 | 1705.87 | 0.00 | 0.00 |
April | 3234.09 | 2394.10 | 3230.01 | 1298.80 | 1931.21 | 0.00 | 0.00 |
May | 3248.80 | 1549.06 | 2959.95 | 542.54 | 2417.41 | 0.00 | 0.00 |
June | 3808.78 | 883.35 | 2728.97 | 498.78 | 2230.19 | 0.00 | 0.00 |
July | 3975.70 | 826.76 | 2840.80 | 508.71 | 2332.09 | 0.00 | 0.00 |
August | 5081.64 | 934.86 | 3616.91 | 1512.01 | 2104.91 | 0.00 | 0.00 |
September | 6124.77 | 1386.75 | 4653.51 | 2596.64 | 2056.88 | 0.00 | 0.00 |
October | 6506.39 | 2707.96 | 5564.24 | 3947.96 | 1616.29 | 0.00 | 0.00 |
November | 7631.27 | 3138.96 | 6779.26 | 5404.05 | 1375.21 | 0.00 | 0.00 |
December | 6985.49 | 3686.34 | 6482.74 | 5247.04 | 1235.70 | 0.00 | 0.00 |
Annual Sum or Average | 5590.40 | 2240.21 | 4793.88 | 2989.05 | 1804.83 | 0.00 | 0.00 |
Minimum of Months | 3234.09 | 826.76 | 2728.97 | 498.78 | 1235.70 | 0.00 | 0.00 |
Maximum of Months | 7771.67 | 3686.34 | 7052.03 | 5801.05 | 2417.41 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1508.95 | 2311.15 | 1634.01 | 1035.40 | 598.61 | 0.00 | 0.00 |
February | 1791.16 | 2392.85 | 1970.39 | 1221.06 | 749.33 | 0.00 | 0.00 |
March | 2228.83 | 1848.25 | 2307.20 | 1272.93 | 1034.26 | 0.00 | 0.00 |
April | 1996.52 | 1592.53 | 2172.33 | 919.73 | 1252.60 | 0.00 | 0.00 |
May | 2901.74 | 1038.51 | 2655.15 | 936.04 | 1719.11 | 0.00 | 0.00 |
June | 4282.24 | 636.86 | 3247.41 | 1562.45 | 1684.95 | 0.00 | 0.00 |
July | 3496.95 | 583.13 | 2645.87 | 969.13 | 1676.74 | 0.00 | 0.00 |
August | 3599.83 | 650.74 | 2761.54 | 1364.24 | 1397.30 | 0.00 | 0.00 |
September | 3057.54 | 931.33 | 2448.66 | 1174.29 | 1274.36 | 0.00 | 0.00 |
October | 2169.56 | 1815.72 | 2059.97 | 1177.43 | 882.54 | 0.00 | 0.00 |
November | 1603.90 | 2137.27 | 1690.31 | 1026.23 | 664.08 | 0.00 | 0.00 |
December | 1144.38 | 2598.88 | 1365.31 | 806.53 | 558.79 | 0.00 | 0.00 |
Annual Sum or Average | 2484.70 | 1540.21 | 2247.21 | 1120.78 | 1126.44 | 0.00 | 0.00 |
Minimum of Months | 1144.38 | 583.13 | 1365.31 | 806.53 | 558.79 | 0.00 | 0.00 |
Maximum of Months | 4282.24 | 2598.88 | 3247.41 | 1562.45 | 1719.11 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.228429E+09 | 0.109731E+11 | 0.197084E+10 | 0.00 | 0.197084E+10 | 0.00 | 0.00 |
February | 0.269437E+09 | 0.998828E+10 | 0.223738E+10 | 0.00 | 0.223738E+10 | 0.00 | 0.00 |
March | 0.120465E+10 | 0.851654E+10 | 0.337052E+10 | 0.00 | 0.337052E+10 | 0.00 | 0.00 |
April | 0.186918E+10 | 0.727752E+10 | 0.409635E+10 | 22724771.91 | 0.407362E+10 | 0.00 | 0.00 |
May | 0.481155E+10 | 0.416178E+10 | 0.578239E+10 | 0.191142E+09 | 0.559125E+10 | 0.00 | 0.00 |
June | 0.785714E+10 | 0.219142E+10 | 0.613625E+10 | 0.680302E+09 | 0.545594E+10 | 0.00 | 0.00 |
July | 0.777050E+10 | 0.214292E+10 | 0.599666E+10 | 0.388174E+09 | 0.560849E+10 | 0.00 | 0.00 |
August | 0.586638E+10 | 0.246991E+10 | 0.477289E+10 | 0.112910E+09 | 0.465998E+10 | 0.00 | 0.00 |
September | 0.416310E+10 | 0.371711E+10 | 0.387990E+10 | 911318.57 | 0.387898E+10 | 0.00 | 0.00 |
October | 0.132824E+10 | 0.820553E+10 | 0.287157E+10 | 0.00 | 0.287157E+10 | 0.00 | 0.00 |
November | 0.406130E+09 | 0.972120E+10 | 0.210957E+10 | 0.00 | 0.210957E+10 | 0.00 | 0.00 |
December | 0.183389E+09 | 0.124506E+11 | 0.184396E+10 | 0.00 | 0.184396E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.359581E+11 | 0.818159E+11 | 0.450683E+11 | 0.139617E+10 | 0.436721E+11 | 0.00 | 0.00 |
Minimum of Months | 0.183389E+09 | 0.214292E+10 | 0.184396E+10 | 0.00 | 0.184396E+10 | 0.00 | 0.00 |
Maximum of Months | 0.785714E+10 | 0.124506E+11 | 0.613625E+10 | 0.680302E+09 | 0.560849E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.338611E+10 | 0.669296E+10 | 0.411417E+10 | 0.252129E+10 | 0.159288E+10 | 0.00 | 0.00 |
February | 0.438516E+10 | 0.620325E+10 | 0.493633E+10 | 0.311629E+10 | 0.182004E+10 | 0.00 | 0.00 |
March | 0.635326E+10 | 0.526350E+10 | 0.659637E+10 | 0.384760E+10 | 0.274877E+10 | 0.00 | 0.00 |
April | 0.616060E+10 | 0.451901E+10 | 0.654671E+10 | 0.318902E+10 | 0.335769E+10 | 0.00 | 0.00 |
May | 0.860287E+10 | 0.273161E+10 | 0.790810E+10 | 0.330325E+10 | 0.460486E+10 | 0.00 | 0.00 |
June | 0.122377E+11 | 0.142566E+10 | 0.933745E+10 | 0.490191E+10 | 0.443554E+10 | 0.00 | 0.00 |
July | 0.116075E+11 | 0.135823E+10 | 0.877143E+10 | 0.417674E+10 | 0.459469E+10 | 0.00 | 0.00 |
August | 0.116331E+11 | 0.153144E+10 | 0.884719E+10 | 0.487272E+10 | 0.397448E+10 | 0.00 | 0.00 |
September | 0.882794E+10 | 0.232348E+10 | 0.712385E+10 | 0.386988E+10 | 0.325398E+10 | 0.00 | 0.00 |
October | 0.534961E+10 | 0.519366E+10 | 0.533106E+10 | 0.292111E+10 | 0.240995E+10 | 0.00 | 0.00 |
November | 0.351997E+10 | 0.600225E+10 | 0.401569E+10 | 0.226730E+10 | 0.174839E+10 | 0.00 | 0.00 |
December | 0.281002E+10 | 0.760036E+10 | 0.359240E+10 | 0.206948E+10 | 0.152292E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.848738E+11 | 0.508454E+11 | 0.771208E+11 | 0.410566E+11 | 0.360642E+11 | 0.00 | 0.00 |
Minimum of Months | 0.281002E+10 | 0.135823E+10 | 0.359240E+10 | 0.206948E+10 | 0.152292E+10 | 0.00 | 0.00 |
Maximum of Months | 0.122377E+11 | 0.760036E+10 | 0.933745E+10 | 0.490191E+10 | 0.460486E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.207779E+11 | 0.951230E+10 | 0.188882E+11 | 0.155376E+11 | 0.335062E+10 | 0.00 | 0.00 |
February | 0.178394E+11 | 0.894029E+10 | 0.163640E+11 | 0.130464E+11 | 0.331759E+10 | 0.00 | 0.00 |
March | 0.147232E+11 | 0.801095E+10 | 0.133575E+11 | 0.878846E+10 | 0.456901E+10 | 0.00 | 0.00 |
April | 0.831306E+10 | 0.710777E+10 | 0.837222E+10 | 0.336650E+10 | 0.500572E+10 | 0.00 | 0.00 |
May | 0.865670E+10 | 0.446447E+10 | 0.792796E+10 | 0.145314E+10 | 0.647482E+10 | 0.00 | 0.00 |
June | 0.990471E+10 | 0.239044E+10 | 0.707353E+10 | 0.129284E+10 | 0.578068E+10 | 0.00 | 0.00 |
July | 0.106844E+11 | 0.227726E+10 | 0.760882E+10 | 0.136253E+10 | 0.624630E+10 | 0.00 | 0.00 |
August | 0.136792E+11 | 0.257508E+10 | 0.968758E+10 | 0.404977E+10 | 0.563781E+10 | 0.00 | 0.00 |
September | 0.159766E+11 | 0.378074E+10 | 0.120620E+11 | 0.673050E+10 | 0.533145E+10 | 0.00 | 0.00 |
October | 0.174745E+11 | 0.786617E+10 | 0.149033E+11 | 0.105742E+11 | 0.432908E+10 | 0.00 | 0.00 |
November | 0.197960E+11 | 0.882620E+10 | 0.175719E+11 | 0.140073E+11 | 0.356454E+10 | 0.00 | 0.00 |
December | 0.186599E+11 | 0.107780E+11 | 0.173634E+11 | 0.140537E+11 | 0.330971E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.176486E+12 | 0.765296E+11 | 0.151180E+12 | 0.942631E+11 | 0.569173E+11 | 0.00 | 0.00 |
Minimum of Months | 0.831306E+10 | 0.227726E+10 | 0.707353E+10 | 0.129284E+10 | 0.330971E+10 | 0.00 | 0.00 |
Maximum of Months | 0.207779E+11 | 0.107780E+11 | 0.188882E+11 | 0.155376E+11 | 0.647482E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.388183E+10 | 0.715861E+10 | 0.437656E+10 | 0.277323E+10 | 0.160333E+10 | 0.00 | 0.00 |
February | 0.419633E+10 | 0.670507E+10 | 0.476678E+10 | 0.295399E+10 | 0.181279E+10 | 0.00 | 0.00 |
March | 0.576728E+10 | 0.595152E+10 | 0.617962E+10 | 0.340944E+10 | 0.277019E+10 | 0.00 | 0.00 |
April | 0.493646E+10 | 0.530822E+10 | 0.563071E+10 | 0.238395E+10 | 0.324676E+10 | 0.00 | 0.00 |
May | 0.765280E+10 | 0.312414E+10 | 0.711158E+10 | 0.250710E+10 | 0.460448E+10 | 0.00 | 0.00 |
June | 0.110522E+11 | 0.182861E+10 | 0.841731E+10 | 0.404990E+10 | 0.436742E+10 | 0.00 | 0.00 |
July | 0.926653E+10 | 0.176769E+10 | 0.708672E+10 | 0.259574E+10 | 0.449099E+10 | 0.00 | 0.00 |
August | 0.950645E+10 | 0.201570E+10 | 0.739653E+10 | 0.365399E+10 | 0.374254E+10 | 0.00 | 0.00 |
September | 0.784986E+10 | 0.269676E+10 | 0.634694E+10 | 0.304378E+10 | 0.330316E+10 | 0.00 | 0.00 |
October | 0.564610E+10 | 0.571568E+10 | 0.551744E+10 | 0.315363E+10 | 0.236381E+10 | 0.00 | 0.00 |
November | 0.395222E+10 | 0.667390E+10 | 0.438131E+10 | 0.266000E+10 | 0.172131E+10 | 0.00 | 0.00 |
December | 0.285679E+10 | 0.844656E+10 | 0.365686E+10 | 0.216021E+10 | 0.149666E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.765649E+11 | 0.573925E+11 | 0.708684E+11 | 0.353449E+11 | 0.355234E+11 | 0.00 | 0.00 |
Minimum of Months | 0.285679E+10 | 0.176769E+10 | 0.365686E+10 | 0.216021E+10 | 0.149666E+10 | 0.00 | 0.00 |
Maximum of Months | 0.110522E+11 | 0.844656E+10 | 0.841731E+10 | 0.404990E+10 | 0.460448E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.323032E+09 | 0.998277E+10 | 0.197083E+10 | 0.00 | 0.197083E+10 | 0.00 | 0.00 |
February | 0.378794E+09 | 0.909548E+10 | 0.223737E+10 | 0.00 | 0.223737E+10 | 0.00 | 0.00 |
March | 0.139887E+10 | 0.767298E+10 | 0.337051E+10 | 0.00 | 0.337051E+10 | 0.00 | 0.00 |
April | 0.206275E+10 | 0.641224E+10 | 0.409633E+10 | 22724691.21 | 0.407361E+10 | 0.00 | 0.00 |
May | 0.491643E+10 | 0.393665E+10 | 0.578237E+10 | 0.191142E+09 | 0.559123E+10 | 0.00 | 0.00 |
June | 0.791222E+10 | 0.211351E+10 | 0.613622E+10 | 0.680300E+09 | 0.545592E+10 | 0.00 | 0.00 |
July | 0.783470E+10 | 0.207265E+10 | 0.599664E+10 | 0.388173E+09 | 0.560846E+10 | 0.00 | 0.00 |
August | 0.595706E+10 | 0.236036E+10 | 0.477287E+10 | 0.112910E+09 | 0.465996E+10 | 0.00 | 0.00 |
September | 0.425420E+10 | 0.349957E+10 | 0.387988E+10 | 911315.33 | 0.387897E+10 | 0.00 | 0.00 |
October | 0.148317E+10 | 0.751017E+10 | 0.287156E+10 | 0.00 | 0.287156E+10 | 0.00 | 0.00 |
November | 0.538774E+09 | 0.872552E+10 | 0.210956E+10 | 0.00 | 0.210956E+10 | 0.00 | 0.00 |
December | 0.294104E+09 | 0.111646E+11 | 0.184396E+10 | 0.00 | 0.184396E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.373541E+11 | 0.745465E+11 | 0.450681E+11 | 0.139616E+10 | 0.436719E+11 | 0.00 | 0.00 |
Minimum of Months | 0.294104E+09 | 0.207265E+10 | 0.184396E+10 | 0.00 | 0.184396E+10 | 0.00 | 0.00 |
Maximum of Months | 0.791222E+10 | 0.111646E+11 | 0.613622E+10 | 0.680300E+09 | 0.560846E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.346405E+10 | 0.625271E+10 | 0.411415E+10 | 0.252128E+10 | 0.159288E+10 | 0.00 | 0.00 |
February | 0.441299E+10 | 0.581834E+10 | 0.493631E+10 | 0.311627E+10 | 0.182004E+10 | 0.00 | 0.00 |
March | 0.636797E+10 | 0.492110E+10 | 0.659634E+10 | 0.384759E+10 | 0.274875E+10 | 0.00 | 0.00 |
April | 0.617928E+10 | 0.415381E+10 | 0.654669E+10 | 0.318901E+10 | 0.335768E+10 | 0.00 | 0.00 |
May | 0.858028E+10 | 0.262635E+10 | 0.790807E+10 | 0.330323E+10 | 0.460484E+10 | 0.00 | 0.00 |
June | 0.121745E+11 | 0.141074E+10 | 0.933741E+10 | 0.490189E+10 | 0.443552E+10 | 0.00 | 0.00 |
July | 0.115375E+11 | 0.138655E+10 | 0.877140E+10 | 0.417672E+10 | 0.459467E+10 | 0.00 | 0.00 |
August | 0.115634E+11 | 0.157741E+10 | 0.884716E+10 | 0.487270E+10 | 0.397446E+10 | 0.00 | 0.00 |
September | 0.879995E+10 | 0.223433E+10 | 0.712382E+10 | 0.386986E+10 | 0.325396E+10 | 0.00 | 0.00 |
October | 0.536172E+10 | 0.489681E+10 | 0.533104E+10 | 0.292110E+10 | 0.240994E+10 | 0.00 | 0.00 |
November | 0.358047E+10 | 0.560317E+10 | 0.401567E+10 | 0.226729E+10 | 0.174838E+10 | 0.00 | 0.00 |
December | 0.289570E+10 | 0.705893E+10 | 0.359238E+10 | 0.206947E+10 | 0.152292E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.849177E+11 | 0.479402E+11 | 0.771205E+11 | 0.410564E+11 | 0.360640E+11 | 0.00 | 0.00 |
Minimum of Months | 0.289570E+10 | 0.138655E+10 | 0.359238E+10 | 0.206947E+10 | 0.152292E+10 | 0.00 | 0.00 |
Maximum of Months | 0.121745E+11 | 0.705893E+10 | 0.933741E+10 | 0.490189E+10 | 0.460484E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.206408E+11 | 0.939436E+10 | 0.188881E+11 | 0.155375E+11 | 0.335061E+10 | 0.00 | 0.00 |
February | 0.176889E+11 | 0.872620E+10 | 0.163640E+11 | 0.130464E+11 | 0.331758E+10 | 0.00 | 0.00 |
March | 0.146463E+11 | 0.769444E+10 | 0.133574E+11 | 0.878843E+10 | 0.456900E+10 | 0.00 | 0.00 |
April | 0.832576E+10 | 0.665744E+10 | 0.837219E+10 | 0.336649E+10 | 0.500570E+10 | 0.00 | 0.00 |
May | 0.864977E+10 | 0.433650E+10 | 0.792793E+10 | 0.145313E+10 | 0.647479E+10 | 0.00 | 0.00 |
June | 0.991722E+10 | 0.231945E+10 | 0.707350E+10 | 0.129284E+10 | 0.578066E+10 | 0.00 | 0.00 |
July | 0.106938E+11 | 0.223860E+10 | 0.760880E+10 | 0.136252E+10 | 0.624627E+10 | 0.00 | 0.00 |
August | 0.136520E+11 | 0.254224E+10 | 0.968754E+10 | 0.404976E+10 | 0.563779E+10 | 0.00 | 0.00 |
September | 0.158864E+11 | 0.370593E+10 | 0.120619E+11 | 0.673048E+10 | 0.533143E+10 | 0.00 | 0.00 |
October | 0.173656E+11 | 0.767487E+10 | 0.149033E+11 | 0.105742E+11 | 0.432906E+10 | 0.00 | 0.00 |
November | 0.196699E+11 | 0.861504E+10 | 0.175718E+11 | 0.140073E+11 | 0.356453E+10 | 0.00 | 0.00 |
December | 0.185907E+11 | 0.103813E+11 | 0.173634E+11 | 0.140537E+11 | 0.330969E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.175727E+12 | 0.742864E+11 | 0.151180E+12 | 0.942627E+11 | 0.569171E+11 | 0.00 | 0.00 |
Minimum of Months | 0.832576E+10 | 0.223860E+10 | 0.707350E+10 | 0.129284E+10 | 0.330969E+10 | 0.00 | 0.00 |
Maximum of Months | 0.206408E+11 | 0.103813E+11 | 0.188881E+11 | 0.155375E+11 | 0.647479E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.398718E+10 | 0.656425E+10 | 0.437654E+10 | 0.277321E+10 | 0.160333E+10 | 0.00 | 0.00 |
February | 0.431009E+10 | 0.603660E+10 | 0.476676E+10 | 0.295398E+10 | 0.181278E+10 | 0.00 | 0.00 |
March | 0.595066E+10 | 0.517602E+10 | 0.617960E+10 | 0.340942E+10 | 0.277017E+10 | 0.00 | 0.00 |
April | 0.515125E+10 | 0.439542E+10 | 0.563069E+10 | 0.238394E+10 | 0.324675E+10 | 0.00 | 0.00 |
May | 0.775102E+10 | 0.288817E+10 | 0.711155E+10 | 0.250709E+10 | 0.460446E+10 | 0.00 | 0.00 |
June | 0.111342E+11 | 0.167127E+10 | 0.841728E+10 | 0.404988E+10 | 0.436740E+10 | 0.00 | 0.00 |
July | 0.939800E+10 | 0.158107E+10 | 0.708669E+10 | 0.259573E+10 | 0.449097E+10 | 0.00 | 0.00 |
August | 0.966560E+10 | 0.176898E+10 | 0.739650E+10 | 0.365398E+10 | 0.374252E+10 | 0.00 | 0.00 |
September | 0.792633E+10 | 0.248529E+10 | 0.634691E+10 | 0.304377E+10 | 0.330314E+10 | 0.00 | 0.00 |
October | 0.578079E+10 | 0.511689E+10 | 0.551742E+10 | 0.315362E+10 | 0.236380E+10 | 0.00 | 0.00 |
November | 0.411659E+10 | 0.583526E+10 | 0.438129E+10 | 0.265999E+10 | 0.172130E+10 | 0.00 | 0.00 |
December | 0.303533E+10 | 0.725318E+10 | 0.365685E+10 | 0.216020E+10 | 0.149665E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.782070E+11 | 0.507724E+11 | 0.708681E+11 | 0.353448E+11 | 0.355233E+11 | 0.00 | 0.00 |
Minimum of Months | 0.303533E+10 | 0.158107E+10 | 0.365685E+10 | 0.216020E+10 | 0.149665E+10 | 0.00 | 0.00 |
Maximum of Months | 0.111342E+11 | 0.725318E+10 | 0.841728E+10 | 0.404988E+10 | 0.460446E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.390657E+09 | 0.936219E+10 | 0.197083E+10 | 0.00 | 0.197083E+10 | 0.00 | 0.00 |
February | 0.432401E+09 | 0.865921E+10 | 0.223737E+10 | 0.00 | 0.223737E+10 | 0.00 | 0.00 |
March | 0.146931E+10 | 0.727915E+10 | 0.337051E+10 | 0.00 | 0.337051E+10 | 0.00 | 0.00 |
April | 0.214415E+10 | 0.594641E+10 | 0.409633E+10 | 22724691.21 | 0.407361E+10 | 0.00 | 0.00 |
May | 0.500955E+10 | 0.375822E+10 | 0.578237E+10 | 0.191142E+09 | 0.559123E+10 | 0.00 | 0.00 |
June | 0.786941E+10 | 0.209224E+10 | 0.613622E+10 | 0.680300E+09 | 0.545592E+10 | 0.00 | 0.00 |
July | 0.779245E+10 | 0.205622E+10 | 0.599664E+10 | 0.388173E+09 | 0.560846E+10 | 0.00 | 0.00 |
August | 0.593195E+10 | 0.232172E+10 | 0.477287E+10 | 0.112910E+09 | 0.465996E+10 | 0.00 | 0.00 |
September | 0.427659E+10 | 0.336822E+10 | 0.387988E+10 | 911315.33 | 0.387897E+10 | 0.00 | 0.00 |
October | 0.157986E+10 | 0.703130E+10 | 0.287156E+10 | 0.00 | 0.287156E+10 | 0.00 | 0.00 |
November | 0.625050E+09 | 0.815496E+10 | 0.210956E+10 | 0.00 | 0.210956E+10 | 0.00 | 0.00 |
December | 0.336455E+09 | 0.106476E+11 | 0.184396E+10 | 0.00 | 0.184396E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.378578E+11 | 0.706774E+11 | 0.450681E+11 | 0.139616E+10 | 0.436719E+11 | 0.00 | 0.00 |
Minimum of Months | 0.336455E+09 | 0.205622E+10 | 0.184396E+10 | 0.00 | 0.184396E+10 | 0.00 | 0.00 |
Maximum of Months | 0.786941E+10 | 0.106476E+11 | 0.613622E+10 | 0.680300E+09 | 0.560846E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.356007E+10 | 0.587190E+10 | 0.411415E+10 | 0.252128E+10 | 0.159288E+10 | 0.00 | 0.00 |
February | 0.447122E+10 | 0.556343E+10 | 0.493631E+10 | 0.311627E+10 | 0.182004E+10 | 0.00 | 0.00 |
March | 0.640875E+10 | 0.470247E+10 | 0.659634E+10 | 0.384759E+10 | 0.274875E+10 | 0.00 | 0.00 |
April | 0.622033E+10 | 0.387910E+10 | 0.654669E+10 | 0.318901E+10 | 0.335768E+10 | 0.00 | 0.00 |
May | 0.860768E+10 | 0.253594E+10 | 0.790807E+10 | 0.330323E+10 | 0.460484E+10 | 0.00 | 0.00 |
June | 0.121277E+11 | 0.140416E+10 | 0.933741E+10 | 0.490189E+10 | 0.443552E+10 | 0.00 | 0.00 |
July | 0.114941E+11 | 0.138154E+10 | 0.877140E+10 | 0.417672E+10 | 0.459467E+10 | 0.00 | 0.00 |
August | 0.115276E+11 | 0.156453E+10 | 0.884716E+10 | 0.487270E+10 | 0.397446E+10 | 0.00 | 0.00 |
September | 0.879252E+10 | 0.217863E+10 | 0.712382E+10 | 0.386986E+10 | 0.325396E+10 | 0.00 | 0.00 |
October | 0.540261E+10 | 0.463601E+10 | 0.533104E+10 | 0.292110E+10 | 0.240994E+10 | 0.00 | 0.00 |
November | 0.366113E+10 | 0.528120E+10 | 0.401567E+10 | 0.226729E+10 | 0.174838E+10 | 0.00 | 0.00 |
December | 0.296513E+10 | 0.674950E+10 | 0.359238E+10 | 0.206947E+10 | 0.152292E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.852388E+11 | 0.457484E+11 | 0.771205E+11 | 0.410564E+11 | 0.360640E+11 | 0.00 | 0.00 |
Minimum of Months | 0.296513E+10 | 0.138154E+10 | 0.359238E+10 | 0.206947E+10 | 0.152292E+10 | 0.00 | 0.00 |
Maximum of Months | 0.121277E+11 | 0.674950E+10 | 0.933741E+10 | 0.490189E+10 | 0.460484E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.208156E+11 | 0.879597E+10 | 0.188881E+11 | 0.155375E+11 | 0.335061E+10 | 0.00 | 0.00 |
February | 0.177730E+11 | 0.831022E+10 | 0.163640E+11 | 0.130464E+11 | 0.331758E+10 | 0.00 | 0.00 |
March | 0.147022E+11 | 0.732151E+10 | 0.133574E+11 | 0.878843E+10 | 0.456900E+10 | 0.00 | 0.00 |
April | 0.838275E+10 | 0.620551E+10 | 0.837219E+10 | 0.336649E+10 | 0.500570E+10 | 0.00 | 0.00 |
May | 0.870158E+10 | 0.414900E+10 | 0.792793E+10 | 0.145313E+10 | 0.647479E+10 | 0.00 | 0.00 |
June | 0.987235E+10 | 0.228963E+10 | 0.707350E+10 | 0.129284E+10 | 0.578066E+10 | 0.00 | 0.00 |
July | 0.106485E+11 | 0.221438E+10 | 0.760880E+10 | 0.136252E+10 | 0.624627E+10 | 0.00 | 0.00 |
August | 0.136107E+11 | 0.250393E+10 | 0.968754E+10 | 0.404976E+10 | 0.563779E+10 | 0.00 | 0.00 |
September | 0.158754E+11 | 0.359446E+10 | 0.120619E+11 | 0.673048E+10 | 0.533143E+10 | 0.00 | 0.00 |
October | 0.174267E+11 | 0.725301E+10 | 0.149033E+11 | 0.105742E+11 | 0.432906E+10 | 0.00 | 0.00 |
November | 0.197803E+11 | 0.813619E+10 | 0.175718E+11 | 0.140073E+11 | 0.356453E+10 | 0.00 | 0.00 |
December | 0.187099E+11 | 0.987350E+10 | 0.173634E+11 | 0.140537E+11 | 0.330969E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.176299E+12 | 0.706473E+11 | 0.151180E+12 | 0.942627E+11 | 0.569171E+11 | 0.00 | 0.00 |
Minimum of Months | 0.838275E+10 | 0.221438E+10 | 0.707350E+10 | 0.129284E+10 | 0.330969E+10 | 0.00 | 0.00 |
Maximum of Months | 0.208156E+11 | 0.987350E+10 | 0.188881E+11 | 0.155375E+11 | 0.647479E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.404156E+10 | 0.619017E+10 | 0.437654E+10 | 0.277321E+10 | 0.160333E+10 | 0.00 | 0.00 |
February | 0.433318E+10 | 0.578878E+10 | 0.476676E+10 | 0.295398E+10 | 0.181278E+10 | 0.00 | 0.00 |
March | 0.596971E+10 | 0.495036E+10 | 0.617960E+10 | 0.340942E+10 | 0.277017E+10 | 0.00 | 0.00 |
April | 0.517497E+10 | 0.412784E+10 | 0.563069E+10 | 0.238394E+10 | 0.324675E+10 | 0.00 | 0.00 |
May | 0.777203E+10 | 0.278154E+10 | 0.711155E+10 | 0.250709E+10 | 0.460446E+10 | 0.00 | 0.00 |
June | 0.110996E+11 | 0.165075E+10 | 0.841728E+10 | 0.404988E+10 | 0.436740E+10 | 0.00 | 0.00 |
July | 0.936623E+10 | 0.156185E+10 | 0.708669E+10 | 0.259573E+10 | 0.449097E+10 | 0.00 | 0.00 |
August | 0.964179E+10 | 0.174293E+10 | 0.739650E+10 | 0.365398E+10 | 0.374252E+10 | 0.00 | 0.00 |
September | 0.792516E+10 | 0.241401E+10 | 0.634691E+10 | 0.304377E+10 | 0.330314E+10 | 0.00 | 0.00 |
October | 0.581094E+10 | 0.486322E+10 | 0.551742E+10 | 0.315362E+10 | 0.236380E+10 | 0.00 | 0.00 |
November | 0.415731E+10 | 0.553980E+10 | 0.438129E+10 | 0.265999E+10 | 0.172130E+10 | 0.00 | 0.00 |
December | 0.306512E+10 | 0.696084E+10 | 0.365685E+10 | 0.216020E+10 | 0.149665E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.783576E+11 | 0.485721E+11 | 0.708681E+11 | 0.353448E+11 | 0.355233E+11 | 0.00 | 0.00 |
Minimum of Months | 0.306512E+10 | 0.156185E+10 | 0.365685E+10 | 0.216020E+10 | 0.149665E+10 | 0.00 | 0.00 |
Maximum of Months | 0.110996E+11 | 0.696084E+10 | 0.841728E+10 | 0.404988E+10 | 0.460446E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 0.85 | -1.5 | -4.5 | 2.30 | -12.1 | 27.63 | 226.20 | 0.01 |
February | -0.2 | -2.7 | -6.1 | 3.74 | -13.6 | 32.55 | 253.27 | 0.01 |
March | 4.82 | 0.36 | -5.5 | 4.48 | -7.8 | 54.65 | 233.06 | 0.03 |
April | 6.08 | 2.29 | -2.0 | 5.23 | -4.9 | 81.86 | 179.11 | 0.05 |
May | 13.74 | 7.52 | 1.82 | 4.10 | 2.75 | 117.64 | 180.87 | 0.01 |
June | 22.16 | 12.46 | 5.10 | 4.19 | 9.76 | 95.26 | 290.95 | 0.00 |
July | 22.71 | 13.25 | 6.43 | 4.25 | 12.01 | 110.54 | 215.12 | 0.03 |
August | 21.74 | 12.79 | 6.20 | 3.81 | 10.76 | 77.72 | 272.61 | 0.02 |
September | 18.54 | 9.35 | 1.35 | 4.13 | 5.52 | 70.51 | 233.03 | 0.01 |
October | 7.12 | 2.51 | -2.7 | 3.54 | -5.8 | 44.60 | 216.74 | 0.01 |
November | 3.03 | 0.31 | -2.9 | 2.79 | -8.8 | 30.71 | 220.86 | 0.01 |
December | -1.0 | -4.5 | -9.5 | 4.43 | -15.4 | 27.45 | 194.75 | 0.01 |
Annual Sum or Average | 10.02 | 4.37 | -1.0 | 3.91 | -2.2 | 64.46 | 226.11 | 0.02 |
Minimum of Months | -1.0 | -4.5 | -9.5 | 2.30 | -15.4 | 27.45 | 179.11 | 0.00 |
Maximum of Months | 22.71 | 13.25 | 6.43 | 5.23 | 12.01 | 117.64 | 290.95 | 0.05 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 21.00 | 20-JAN-12:00 | 6.97 | -11.0 | 0.50 | 6.55 | 41.00 | 961.00 |
February | 20.00 | 18-FEB-12:00 | 7.74 | -5.0 | 3.60 | 6.35 | 56.00 | 998.00 |
March | 24.00 | 14-MAR-12:00 | 7.90 | -12.0 | 3.10 | 11.65 | 160.00 | 837.50 |
April | 22.00 | 19-APR-13:09 | 8.49 | -5.7 | 5.52 | 11.55 | 235.67 | 789.67 |
May | 29.00 | 17-MAY-12:00 | 11.92 | -3.0 | 5.10 | 18.99 | 432.50 | 162.00 |
June | 39.40 | 26-JUN-14:00 | 15.63 | -2.8 | 4.60 | 21.96 | 136.50 | 752.00 |
July | 37.00 | 16-JUL-12:00 | 14.90 | -3.0 | 3.10 | 26.65 | 319.50 | 109.50 |
August | 37.00 | 16-AUG-13:00 | 16.36 | 3.00 | 3.60 | 28.27 | 90.00 | 895.00 |
September | 32.70 | 09-SEP-12:00 | 13.05 | -3.9 | 3.00 | 16.30 | 270.50 | 562.00 |
October | 27.00 | 11-OCT-13:00 | 9.73 | -9.0 | 4.60 | 12.03 | 89.50 | 844.00 |
November | 22.00 | 06-NOV-13:09 | 7.10 | -13.0 | 2.60 | 4.92 | 88.67 | 883.33 |
December | 22.00 | 01-DEC-13:00 | 7.94 | -8.0 | 2.60 | 5.13 | 49.00 | 862.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 20.00 | 6.97 | -13.0 | 0.50 | 4.92 | 41.00 | 109.50 | |
Maximum of Months | 39.40 | 16.36 | 3.00 | 5.52 | 28.27 | 432.50 | 998.00 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -19.0 | 05-JAN-18:00 | -19.0 | -19.0 | 1.50 | -37.1 | 0.00 | 0.00 |
February | -20.0 | 12-FEB-04:00 | -20.0 | -20.0 | 3.60 | -39.1 | 0.00 | 0.00 |
March | -15.6 | 19-MAR-06:00 | -15.6 | -15.6 | 10.80 | -25.3 | 24.00 | 0.00 |
April | -8.0 | 03-APR-02:00 | -8.0 | -8.0 | 3.10 | -22.2 | 0.00 | 0.00 |
May | -1.0 | 03-MAY-01:00 | -2.4 | -4.0 | 4.10 | -15.7 | 0.00 | 0.00 |
June | 6.60 | 09-JUN-03:00 | 3.45 | 0.00 | 3.60 | -6.9 | 0.00 | 0.00 |
July | 9.00 | 02-JUL-04:00 | 3.30 | -3.0 | 3.60 | -5.3 | 20.00 | 184.50 |
August | 11.00 | 12-AUG-22:00 | 7.22 | 4.00 | 4.10 | 5.13 | 0.00 | 0.00 |
September | -1.7 | 22-SEP-05:10 | -2.9 | -4.3 | 3.60 | -15.8 | 0.00 | 0.00 |
October | -10.0 | 30-OCT-03:00 | -10.0 | -10.0 | 2.60 | -18.6 | 0.00 | 0.00 |
November | -15.0 | 29-NOV-20:00 | -15.0 | -15.0 | 3.10 | -33.5 | 0.00 | 0.00 |
December | -23.0 | 22-DEC-02:00 | -23.0 | -23.0 | 3.60 | -42.7 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -23.0 | -23.0 | -23.0 | 1.50 | -42.7 | 0.00 | 0.00 | |
Maximum of Months | 11.00 | 7.22 | 4.00 | 10.80 | 5.13 | 24.00 | 184.50 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 7.55 | 20-JAN-11:00 | 20.00 | -6.0 | 2.60 | 7.95 | 43.00 | 971.50 |
February | 7.98 | 18-FEB-14:00 | 19.00 | -3.0 | 3.60 | 5.94 | 151.00 | 410.00 |
March | 8.00 | 31-MAR-17:00 | 15.00 | 2.00 | 2.60 | 1.58 | 19.50 | 261.00 |
April | 12.50 | 28-APR-13:00 | 18.00 | 9.00 | 9.80 | 9.72 | 335.00 | 196.50 |
May | 14.87 | 31-MAY-13:00 | 28.00 | 7.00 | 4.60 | 14.47 | 157.50 | 830.50 |
June | 19.65 | 18-JUN-11:00 | 29.40 | 15.50 | 6.10 | 16.85 | 272.50 | 596.00 |
July | 19.75 | 30-JUL-13:00 | 29.00 | 16.00 | 3.60 | 18.99 | 217.50 | 412.00 |
August | 18.80 | 05-AUG-14:09 | 25.83 | 15.33 | 6.62 | 20.54 | 196.33 | 4.00 |
September | 14.95 | 01-SEP-11:00 | 24.40 | 9.40 | 3.00 | 10.69 | 193.50 | 684.00 |
October | 9.73 | 11-OCT-13:00 | 27.00 | -9.0 | 4.60 | 12.03 | 89.50 | 844.00 |
November | 9.33 | 09-NOV-10:00 | 20.00 | 0.00 | 1.50 | 11.07 | 112.00 | 860.50 |
December | 7.94 | 01-DEC-13:00 | 22.00 | -8.0 | 2.60 | 5.13 | 49.00 | 862.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 7.55 | 15.00 | -9.0 | 1.50 | 1.58 | 19.50 | 4.00 | |
Maximum of Months | 19.75 | 29.40 | 16.00 | 9.80 | 20.54 | 335.00 | 971.50 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 5.00 | 28-JAN-10:00 | 5.00 | 5.00 | 1.00 | -6.2 | 207.00 | 309.00 |
February | 5.00 | 19-FEB-14:30 | 5.00 | 5.00 | 1.80 | -0.4 | 188.00 | 467.00 |
March | 7.00 | 17-MAR-14:00 | 8.00 | 7.39 | 8.20 | 1.16 | 121.50 | 3.00 |
April | 9.00 | 28-APR-13:00 | 18.00 | 12.50 | 9.80 | 9.72 | 335.00 | 196.50 |
May | 11.00 | 21-MAY-21:10 | 12.83 | 11.73 | 2.68 | 6.78 | 0.00 | 0.00 |
June | 15.50 | 18-JUN-11:00 | 29.40 | 19.65 | 6.10 | 16.85 | 272.50 | 596.00 |
July | 17.00 | 28-JUL-16:00 | 20.00 | 17.92 | 5.70 | 15.02 | 155.00 | 32.00 |
August | 18.00 | 04-AUG-01:00 | 18.00 | 18.00 | 2.60 | 8.74 | 0.00 | 0.00 |
September | 12.20 | 30-SEP-14:00 | 17.20 | 13.90 | 5.10 | 9.72 | 209.00 | 82.50 |
October | 6.00 | 01-OCT-19:00 | 9.00 | 7.28 | 3.10 | 3.69 | 0.00 | 0.00 |
November | 7.00 | 09-NOV-23:00 | 8.00 | 7.40 | 4.10 | 3.06 | 0.00 | 0.00 |
December | 1.00 | 30-DEC-14:00 | 7.00 | 4.06 | 9.80 | -1.2 | 101.00 | 91.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 1.00 | 5.00 | 4.06 | 1.00 | -6.2 | 0.00 | 0.00 | |
Maximum of Months | 18.00 | 29.40 | 19.65 | 9.80 | 16.85 | 335.00 | 596.00 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 8.52 | 21.53 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 7.90 | 29.36 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 8.65 | 35.75 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 10.64 | 38.62 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 13.34 | 48.35 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 16.03 | 59.81 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 17.97 | 52.29 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 18.66 | 51.98 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 17.88 | 41.73 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 15.85 | 30.82 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 13.14 | 23.90 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 10.46 | 18.59 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 13.28 | 37.76 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 7.90 | 18.59 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 18.66 | 59.81 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.411782E+11 | -0.401525E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.102572E+10 | 58.99 | 0.00 | 0.00 |
February | 0.378663E+11 | -0.369395E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -926810559.1 | 58.97 | 0.00 | 0.00 |
March | 0.438402E+11 | -0.428116E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.102860E+10 | 58.98 | 0.00 | 0.00 |
April | 0.382807E+11 | -0.372895E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -991210012.5 | 58.97 | 0.00 | 0.00 |
May | 0.386440E+11 | -0.376208E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.102316E+10 | 58.98 | 0.00 | 0.00 |
June | 0.360712E+11 | -0.350816E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -989676382.5 | 58.98 | 0.00 | 0.00 |
July | 0.328546E+11 | -0.318371E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.101755E+10 | 58.98 | 0.00 | 0.00 |
August | 0.353207E+11 | -0.342993E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.102138E+10 | 58.98 | 0.00 | 0.00 |
September | 0.327045E+11 | -0.317184E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -986156432.0 | 58.98 | 0.00 | 0.00 |
October | 0.353513E+11 | -0.343324E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.101891E+10 | 58.97 | 0.00 | 0.00 |
November | 0.367750E+11 | -0.357879E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -987055399.7 | 58.98 | 0.00 | 0.00 |
December | 0.387005E+11 | -0.376763E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.102420E+10 | 58.98 | 0.00 | 0.00 |
Annual Sum or Average | 0.447587E+12 | -0.435547E+12 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.120404E+11 | 58.98 | 0.00 | 0.00 |
Minimum of Months | 0.327045E+11 | -0.428116E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -0.102860E+10 | 58.97 | 0.00 | 0.00 |
Maximum of Months | 0.438402E+11 | -0.317184E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -926810559.1 | 58.99 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_1_DAYLCTRL
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 276.50 | 0.50 | 0.48 | 01-JAN-07:49 | 11194.49 | 39.94 | 274.33 | 269.00 | 5977.35 | 35.60 | 241.33 | 261.67 |
February | 245.50 | 0.49 | 0.48 | 01-FEB-10:39 | 14966.18 | 39.72 | 241.00 | 266.00 | 2464.11 | 25.81 | 137.50 | 246.50 |
March | 296.17 | 0.50 | 0.48 | 01-MAR-07:10 | 2983.47 | 21.08 | 110.33 | 329.50 | 1691.81 | 22.14 | 178.83 | 296.50 |
April | 296.67 | 0.51 | 0.48 | 03-APR-09:39 | 2299.42 | 20.79 | 129.00 | 343.17 | 1323.06 | 22.19 | 214.17 | 307.00 |
May | 415.33 | 0.51 | 0.48 | 01-MAY-06:19 | 2068.25 | 20.87 | 203.00 | 398.00 | 1131.49 | 22.27 | 313.83 | 363.33 |
June | 421.50 | 0.51 | 0.48 | 01-JUN-05:00 | 1694.33 | 20.34 | 124.50 | 396.83 | 1008.29 | 21.80 | 276.83 | 358.50 |
July | 430.33 | 0.51 | 0.48 | 01-JUL-06:19 | 1890.45 | 20.50 | 180.67 | 401.83 | 1062.48 | 21.92 | 303.17 | 363.33 |
August | 394.50 | 0.52 | 0.48 | 01-AUG-06:10 | 2021.65 | 20.25 | 129.83 | 373.33 | 1221.27 | 21.66 | 245.50 | 342.00 |
September | 354.00 | 0.51 | 0.48 | 01-SEP-06:30 | 3236.59 | 22.02 | 157.33 | 336.00 | 1497.78 | 22.13 | 226.17 | 307.83 |
October | 262.67 | 0.50 | 0.48 | 01-OCT-06:40 | 14575.36 | 37.23 | 242.33 | 300.67 | 2069.71 | 22.72 | 184.33 | 280.67 |
November | 257.67 | 0.50 | 0.48 | 01-NOV-08:39 | 12806.60 | 40.04 | 256.00 | 266.83 | 3797.70 | 30.34 | 185.50 | 246.50 |
December | 251.17 | 0.49 | 0.48 | 01-DEC-07:40 | 10492.66 | 40.36 | 250.67 | 259.17 | 8429.42 | 40.90 | 252.00 | 250.33 |
Annual Sum or Average | 3902.00 | 0.51 | 5748.06 | 26.98 | 2299.00 | 3940.33 | 2346.18 | 25.02 | 2759.17 | 3624.17 | ||
Minimum of Months | 245.50 | 0.49 | 0.48 | 1694.33 | 20.25 | 110.33 | 259.17 | 1008.29 | 21.66 | 137.50 | 246.50 | |
Maximum of Months | 430.33 | 0.52 | 0.48 | 14966.18 | 40.36 | 274.33 | 401.83 | 8429.42 | 40.90 | 313.83 | 363.33 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_2_DAYLCTRL
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 276.50 | 0.53 | 0.48 | 01-JAN-07:49 | 2792.98 | 25.18 | 118.33 | 246.17 | 1583.91 | 24.86 | 130.17 | 216.17 |
February | 245.50 | 0.51 | 0.48 | 01-FEB-10:39 | 4205.33 | 25.52 | 91.00 | 256.33 | 2488.07 | 25.38 | 94.67 | 216.00 |
March | 296.17 | 0.51 | 0.48 | 01-MAR-06:49 | 4033.02 | 24.87 | 102.00 | 323.83 | 2238.29 | 25.00 | 129.50 | 288.33 |
April | 296.67 | 0.51 | 0.48 | 03-APR-09:39 | 4472.35 | 25.52 | 109.50 | 346.17 | 1942.60 | 24.66 | 168.33 | 312.00 |
May | 415.33 | 0.50 | 0.48 | 01-MAY-05:49 | 3541.24 | 24.43 | 134.83 | 404.33 | 1913.74 | 24.90 | 280.17 | 373.00 |
June | 421.50 | 0.50 | 0.48 | 01-JUN-04:00 | 4230.23 | 24.90 | 130.50 | 409.83 | 2402.29 | 25.39 | 210.50 | 381.83 |
July | 430.33 | 0.51 | 0.48 | 01-JUL-05:10 | 3787.00 | 24.28 | 129.50 | 410.83 | 2032.11 | 24.64 | 264.00 | 381.00 |
August | 394.50 | 0.51 | 0.48 | 01-AUG-05:49 | 5194.64 | 25.48 | 139.83 | 376.83 | 2067.65 | 24.26 | 191.00 | 346.67 |
September | 354.00 | 0.51 | 0.48 | 01-SEP-05:49 | 4265.50 | 25.73 | 136.17 | 337.00 | 1684.16 | 24.44 | 188.50 | 315.00 |
October | 262.67 | 0.51 | 0.48 | 01-OCT-06:19 | 3918.44 | 25.34 | 92.17 | 294.00 | 2186.02 | 25.39 | 147.33 | 261.17 |
November | 257.67 | 0.53 | 0.48 | 01-NOV-08:39 | 2703.90 | 24.37 | 100.00 | 248.33 | 1416.54 | 24.05 | 116.17 | 210.00 |
December | 251.17 | 0.53 | 0.48 | 01-DEC-07:40 | 2819.85 | 25.80 | 110.33 | 238.83 | 1640.20 | 25.49 | 119.50 | 204.17 |
Annual Sum or Average | 3902.00 | 0.51 | 3896.18 | 25.07 | 1394.17 | 3892.50 | 1981.78 | 24.85 | 2039.83 | 3505.33 | ||
Minimum of Months | 245.50 | 0.50 | 0.48 | 2703.90 | 24.28 | 91.00 | 238.83 | 1416.54 | 24.05 | 94.67 | 204.17 | |
Maximum of Months | 430.33 | 0.53 | 0.48 | 5194.64 | 25.80 | 139.83 | 410.83 | 2488.07 | 25.49 | 280.17 | 381.83 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_3_DAYLCTRL
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 276.50 | 0.56 | 0.48 | 01-JAN-09:09 | 630.03 | 16.50 | 0.00 | 228.00 | 416.64 | 18.43 | 21.83 | 177.50 |
February | 245.50 | 0.52 | 0.48 | 01-FEB-10:39 | 755.22 | 17.91 | 0.00 | 246.33 | 517.11 | 19.77 | 29.50 | 189.67 |
March | 296.17 | 0.51 | 0.48 | 01-MAR-07:30 | 972.06 | 19.09 | 1.50 | 320.00 | 627.32 | 20.67 | 81.83 | 271.33 |
April | 296.67 | 0.50 | 0.48 | 03-APR-09:39 | 1284.35 | 20.25 | 40.33 | 348.17 | 759.09 | 21.61 | 179.67 | 307.83 |
May | 415.33 | 0.50 | 0.48 | 01-MAY-05:00 | 1505.66 | 20.98 | 139.00 | 411.33 | 857.26 | 22.36 | 326.67 | 384.17 |
June | 421.50 | 0.49 | 0.48 | 01-JUN-05:10 | 1695.27 | 23.35 | 199.67 | 420.00 | 943.09 | 24.72 | 343.17 | 407.17 |
July | 430.33 | 0.50 | 0.48 | 01-JUL-05:30 | 1594.84 | 21.88 | 166.67 | 422.17 | 870.57 | 22.27 | 324.17 | 393.67 |
August | 394.50 | 0.51 | 0.48 | 01-AUG-05:00 | 1257.67 | 20.10 | 67.67 | 382.17 | 774.82 | 21.48 | 221.33 | 352.00 |
September | 354.00 | 0.51 | 0.48 | 01-SEP-06:40 | 1060.64 | 19.56 | 9.50 | 334.50 | 666.65 | 21.05 | 150.33 | 297.67 |
October | 262.67 | 0.52 | 0.48 | 01-OCT-06:00 | 912.05 | 18.89 | 0.00 | 287.50 | 609.34 | 20.62 | 65.67 | 230.83 |
November | 257.67 | 0.54 | 0.48 | 01-NOV-08:50 | 708.98 | 17.45 | 0.00 | 236.50 | 477.59 | 19.36 | 34.17 | 181.33 |
December | 251.17 | 0.55 | 0.48 | 01-DEC-08:39 | 649.58 | 17.13 | 0.00 | 224.33 | 426.01 | 19.08 | 18.33 | 169.17 |
Annual Sum or Average | 3902.00 | 0.51 | 1156.27 | 19.79 | 624.33 | 3861.00 | 695.31 | 21.24 | 1796.67 | 3362.33 | ||
Minimum of Months | 245.50 | 0.49 | 0.48 | 630.03 | 16.50 | 0.00 | 224.33 | 416.64 | 18.43 | 18.33 | 169.17 | |
Maximum of Months | 430.33 | 0.56 | 0.48 | 1695.27 | 23.35 | 199.67 | 422.17 | 943.09 | 24.72 | 343.17 | 407.17 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_4_DAYLCTRL
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 276.50 | 0.52 | 0.48 | 01-JAN-09:09 | 3157.95 | 26.22 | 127.67 | 255.67 | 1873.75 | 25.85 | 136.33 | 228.50 |
February | 245.50 | 0.50 | 0.48 | 01-FEB-10:39 | 3356.51 | 25.84 | 94.67 | 260.17 | 1835.59 | 25.57 | 98.33 | 225.33 |
March | 296.17 | 0.50 | 0.48 | 01-MAR-07:30 | 3818.53 | 25.35 | 120.83 | 332.33 | 2152.81 | 25.50 | 146.00 | 302.00 |
April | 296.67 | 0.50 | 0.48 | 03-APR-09:39 | 3631.03 | 24.08 | 101.00 | 351.00 | 1616.85 | 23.57 | 163.00 | 318.00 |
May | 415.33 | 0.50 | 0.48 | 01-MAY-07:10 | 3110.83 | 21.51 | 84.33 | 403.00 | 1624.51 | 21.61 | 249.00 | 372.67 |
June | 421.50 | 0.50 | 0.48 | 01-JUN-05:00 | 3699.90 | 19.01 | 18.17 | 407.00 | 2065.24 | 21.33 | 185.67 | 384.33 |
July | 430.33 | 0.51 | 0.48 | 01-JUL-06:19 | 3176.12 | 21.19 | 79.67 | 409.17 | 1703.50 | 21.41 | 237.67 | 383.50 |
August | 394.50 | 0.50 | 0.48 | 01-AUG-06:19 | 4097.14 | 22.12 | 88.83 | 382.83 | 1823.34 | 21.36 | 153.17 | 362.00 |
September | 354.00 | 0.50 | 0.48 | 01-SEP-06:49 | 3587.10 | 24.98 | 137.83 | 339.17 | 1929.70 | 25.17 | 194.17 | 315.50 |
October | 262.67 | 0.50 | 0.48 | 01-OCT-06:00 | 4647.56 | 27.20 | 110.83 | 299.17 | 1798.40 | 25.38 | 153.00 | 269.17 |
November | 257.67 | 0.51 | 0.48 | 01-NOV-08:50 | 3209.62 | 26.74 | 117.67 | 257.50 | 1817.90 | 26.41 | 135.50 | 221.67 |
December | 251.17 | 0.51 | 0.48 | 01-DEC-08:30 | 2645.25 | 26.55 | 114.17 | 246.67 | 1506.32 | 26.12 | 130.17 | 223.33 |
Annual Sum or Average | 3902.00 | 0.50 | 3516.65 | 23.73 | 1195.67 | 3943.67 | 1815.95 | 23.71 | 1982.00 | 3606.00 | ||
Minimum of Months | 245.50 | 0.50 | 0.48 | 2645.25 | 19.01 | 18.17 | 246.67 | 1506.32 | 21.33 | 98.33 | 221.67 | |
Maximum of Months | 430.33 | 0.52 | 0.48 | 4647.56 | 27.20 | 137.83 | 409.17 | 2152.81 | 26.41 | 249.00 | 384.33 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_1_DAYLCTRL
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 276.50 | 0.50 | 0.48 | 01-JAN-07:49 | 11306.24 | 39.54 | 274.17 | 269.33 | 6158.59 | 33.59 | 205.33 | 262.50 |
February | 245.50 | 0.49 | 0.48 | 01-FEB-10:39 | 15108.06 | 39.25 | 241.00 | 266.17 | 2652.81 | 21.33 | 69.50 | 249.50 |
March | 296.17 | 0.50 | 0.48 | 01-MAR-07:10 | 3146.88 | 14.59 | 10.33 | 331.17 | 1828.66 | 17.70 | 12.83 | 299.67 |
April | 296.67 | 0.51 | 0.48 | 03-APR-09:39 | 2345.29 | 14.64 | 0.00 | 344.00 | 1417.73 | 18.13 | 9.83 | 311.67 |
May | 415.33 | 0.51 | 0.48 | 01-MAY-06:10 | 2097.42 | 14.79 | 0.00 | 398.33 | 1205.44 | 18.24 | 0.00 | 367.00 |
June | 421.50 | 0.51 | 0.48 | 01-JUN-05:49 | 1728.74 | 14.56 | 0.00 | 397.00 | 1077.59 | 18.10 | 0.00 | 362.50 |
July | 430.33 | 0.51 | 0.48 | 01-JUL-06:19 | 1920.69 | 14.51 | 0.00 | 401.83 | 1133.08 | 17.99 | 0.50 | 368.00 |
August | 394.50 | 0.51 | 0.48 | 01-AUG-06:10 | 2071.39 | 14.24 | 0.00 | 373.33 | 1311.30 | 17.76 | 9.83 | 346.00 |
September | 354.00 | 0.51 | 0.48 | 01-SEP-06:30 | 3303.31 | 16.10 | 29.50 | 337.00 | 1611.28 | 17.82 | 5.50 | 311.67 |
October | 262.67 | 0.50 | 0.48 | 01-OCT-06:40 | 14711.34 | 36.44 | 240.33 | 302.17 | 2243.04 | 17.90 | 9.33 | 282.67 |
November | 257.67 | 0.50 | 0.48 | 01-NOV-08:39 | 12930.15 | 39.65 | 256.00 | 267.17 | 4013.21 | 27.30 | 131.83 | 251.33 |
December | 251.17 | 0.49 | 0.48 | 01-DEC-07:40 | 10609.96 | 39.96 | 250.67 | 259.50 | 8614.96 | 40.49 | 247.17 | 251.83 |
Annual Sum or Average | 3902.00 | 0.50 | 5826.90 | 22.78 | 1302.00 | 3947.00 | 2468.86 | 21.35 | 701.67 | 3664.33 | ||
Minimum of Months | 245.50 | 0.49 | 0.48 | 1728.74 | 14.24 | 0.00 | 259.50 | 1077.59 | 17.70 | 0.00 | 249.50 | |
Maximum of Months | 430.33 | 0.51 | 0.48 | 15108.06 | 39.96 | 274.17 | 401.83 | 8614.96 | 40.49 | 247.17 | 368.00 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_2_DAYLCTRL
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 276.50 | 0.53 | 0.48 | 01-JAN-07:40 | 2841.97 | 22.89 | 99.83 | 247.00 | 1645.04 | 23.13 | 87.17 | 222.00 |
February | 245.50 | 0.51 | 0.48 | 01-FEB-10:39 | 4273.36 | 22.95 | 84.33 | 256.83 | 2569.35 | 23.40 | 66.00 | 222.33 |
March | 296.17 | 0.51 | 0.48 | 01-MAR-06:49 | 4118.24 | 21.87 | 83.50 | 324.00 | 2332.27 | 22.66 | 61.83 | 292.33 |
April | 296.67 | 0.51 | 0.48 | 03-APR-09:39 | 4537.77 | 22.66 | 96.17 | 346.83 | 2035.89 | 22.11 | 52.50 | 316.00 |
May | 415.33 | 0.50 | 0.48 | 01-MAY-05:49 | 3588.04 | 21.23 | 111.83 | 405.33 | 1999.01 | 22.44 | 83.83 | 376.50 |
June | 421.50 | 0.50 | 0.48 | 01-JUN-04:00 | 4269.65 | 20.84 | 109.00 | 409.83 | 2504.11 | 22.92 | 91.67 | 385.17 |
July | 430.33 | 0.50 | 0.48 | 01-JUL-05:10 | 3841.21 | 21.08 | 116.50 | 411.83 | 2124.66 | 22.12 | 84.67 | 384.17 |
August | 394.50 | 0.51 | 0.48 | 01-AUG-05:49 | 5256.08 | 22.50 | 131.00 | 377.17 | 2169.16 | 21.65 | 70.83 | 350.17 |
September | 354.00 | 0.51 | 0.48 | 01-SEP-05:49 | 4311.58 | 22.05 | 108.33 | 336.50 | 1774.15 | 21.93 | 63.00 | 316.17 |
October | 262.67 | 0.51 | 0.48 | 01-OCT-06:19 | 3986.28 | 22.49 | 79.83 | 294.00 | 2275.31 | 23.26 | 56.67 | 266.50 |
November | 257.67 | 0.52 | 0.48 | 01-NOV-08:39 | 2720.85 | 20.95 | 70.50 | 249.67 | 1485.29 | 22.08 | 70.00 | 212.83 |
December | 251.17 | 0.52 | 0.48 | 01-DEC-07:40 | 2865.98 | 23.58 | 93.17 | 240.17 | 1698.58 | 23.85 | 87.17 | 209.33 |
Annual Sum or Average | 3902.00 | 0.51 | 3949.64 | 21.98 | 1184.00 | 3899.17 | 2068.47 | 22.56 | 875.33 | 3553.50 | ||
Minimum of Months | 245.50 | 0.50 | 0.48 | 2720.85 | 20.84 | 70.50 | 240.17 | 1485.29 | 21.65 | 52.50 | 209.33 | |
Maximum of Months | 430.33 | 0.53 | 0.48 | 5256.08 | 23.58 | 131.00 | 411.83 | 2569.35 | 23.85 | 91.67 | 385.17 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_3_DAYLCTRL
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 276.50 | 0.56 | 0.48 | 01-JAN-08:00 | 641.05 | 10.75 | 0.00 | 229.83 | 444.11 | 14.57 | 0.00 | 187.17 |
February | 245.50 | 0.52 | 0.48 | 01-FEB-10:39 | 771.89 | 12.27 | 0.00 | 247.00 | 552.30 | 16.12 | 0.00 | 197.33 |
March | 296.17 | 0.51 | 0.48 | 01-MAR-07:30 | 992.60 | 13.74 | 0.00 | 320.17 | 669.62 | 17.33 | 0.00 | 278.67 |
April | 296.67 | 0.50 | 0.48 | 03-APR-09:39 | 1308.19 | 14.88 | 0.00 | 348.33 | 809.28 | 18.35 | 8.33 | 312.83 |
May | 415.33 | 0.50 | 0.48 | 01-MAY-05:00 | 1576.23 | 15.26 | 2.33 | 411.67 | 912.97 | 18.77 | 12.33 | 387.17 |
June | 421.50 | 0.49 | 0.48 | 01-JUN-05:10 | 1730.18 | 18.54 | 65.17 | 420.33 | 1006.91 | 21.75 | 81.83 | 408.83 |
July | 430.33 | 0.50 | 0.48 | 01-JUL-05:30 | 1625.76 | 16.53 | 29.50 | 422.33 | 937.22 | 19.91 | 45.67 | 399.50 |
August | 394.50 | 0.50 | 0.48 | 01-AUG-05:00 | 1311.61 | 14.71 | 0.00 | 384.50 | 827.47 | 18.26 | 18.17 | 355.50 |
September | 354.00 | 0.51 | 0.48 | 01-SEP-06:30 | 1082.43 | 14.25 | 0.00 | 334.83 | 711.13 | 17.78 | 0.00 | 302.17 |
October | 262.67 | 0.52 | 0.48 | 01-OCT-06:00 | 930.30 | 13.53 | 0.00 | 288.00 | 650.22 | 17.22 | 0.00 | 239.33 |
November | 257.67 | 0.54 | 0.48 | 01-NOV-08:50 | 721.62 | 11.76 | 0.00 | 237.83 | 509.19 | 15.59 | 0.00 | 188.50 |
December | 251.17 | 0.55 | 0.48 | 01-DEC-08:30 | 659.02 | 11.37 | 0.00 | 224.50 | 453.53 | 15.21 | 0.00 | 179.67 |
Annual Sum or Average | 3902.00 | 0.51 | 1186.26 | 14.36 | 97.00 | 3869.33 | 742.64 | 17.93 | 166.33 | 3436.67 | ||
Minimum of Months | 245.50 | 0.49 | 0.48 | 641.05 | 10.75 | 0.00 | 224.50 | 444.11 | 14.57 | 0.00 | 179.67 | |
Maximum of Months | 430.33 | 0.56 | 0.48 | 1730.18 | 18.54 | 65.17 | 422.33 | 1006.91 | 21.75 | 81.83 | 408.83 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_4_DAYLCTRL
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 276.50 | 0.52 | 0.48 | 01-JAN-08:00 | 3209.58 | 24.05 | 109.00 | 256.17 | 1935.95 | 24.24 | 97.83 | 233.17 |
February | 245.50 | 0.50 | 0.48 | 01-FEB-10:39 | 3427.50 | 23.21 | 81.50 | 260.33 | 1918.96 | 23.53 | 64.50 | 230.50 |
March | 296.17 | 0.50 | 0.48 | 01-MAR-07:30 | 3891.87 | 22.61 | 99.83 | 332.67 | 2237.28 | 23.32 | 74.67 | 304.50 |
April | 296.67 | 0.50 | 0.48 | 03-APR-09:39 | 3692.43 | 21.02 | 85.33 | 352.00 | 1698.53 | 20.84 | 38.33 | 321.67 |
May | 415.33 | 0.50 | 0.48 | 01-MAY-06:49 | 3866.28 | 19.04 | 82.17 | 403.50 | 1705.03 | 18.36 | 0.00 | 376.00 |
June | 421.50 | 0.50 | 0.48 | 01-JUN-05:00 | 3738.98 | 14.38 | 1.83 | 407.50 | 2159.11 | 17.94 | 0.00 | 386.83 |
July | 430.33 | 0.51 | 0.48 | 01-JUL-06:19 | 3211.06 | 17.31 | 56.83 | 410.17 | 1783.25 | 18.13 | 0.17 | 386.83 |
August | 394.50 | 0.50 | 0.48 | 01-AUG-06:19 | 4155.71 | 18.62 | 79.33 | 383.50 | 1908.53 | 18.10 | 7.83 | 364.00 |
September | 354.00 | 0.50 | 0.48 | 01-SEP-06:49 | 3647.62 | 21.88 | 109.83 | 339.17 | 2009.62 | 22.87 | 80.17 | 318.50 |
October | 262.67 | 0.50 | 0.48 | 01-OCT-06:00 | 4659.60 | 23.62 | 93.83 | 299.83 | 1887.82 | 23.19 | 55.17 | 273.00 |
November | 257.67 | 0.51 | 0.48 | 01-NOV-08:50 | 3264.24 | 24.49 | 98.50 | 258.33 | 1888.29 | 24.72 | 90.00 | 224.33 |
December | 251.17 | 0.51 | 0.48 | 01-DEC-08:30 | 2692.76 | 24.42 | 96.50 | 247.33 | 1566.35 | 24.55 | 87.50 | 227.33 |
Annual Sum or Average | 3902.00 | 0.50 | 3642.39 | 20.61 | 994.50 | 3950.50 | 1896.12 | 21.12 | 596.17 | 3646.67 | ||
Minimum of Months | 245.50 | 0.50 | 0.48 | 2692.76 | 14.38 | 1.83 | 247.33 | 1566.35 | 17.94 | 0.00 | 224.33 | |
Maximum of Months | 430.33 | 0.52 | 0.48 | 4659.60 | 24.49 | 109.83 | 410.17 | 2237.28 | 24.72 | 97.83 | 386.83 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_1_DAYLCTRL
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 276.50 | 0.50 | 0.48 | 01-JAN-07:49 | 11307.37 | 39.54 | 274.17 | 269.33 | 6160.61 | 33.58 | 205.33 | 262.67 |
February | 245.50 | 0.49 | 0.48 | 01-FEB-10:39 | 15109.62 | 39.24 | 241.00 | 266.17 | 2654.80 | 21.32 | 69.50 | 249.50 |
March | 296.17 | 0.50 | 0.48 | 01-MAR-07:10 | 3149.63 | 14.56 | 10.33 | 331.17 | 1830.67 | 17.68 | 12.33 | 299.67 |
April | 296.67 | 0.51 | 0.48 | 03-APR-09:39 | 2348.50 | 14.61 | 0.00 | 344.00 | 1419.74 | 18.12 | 9.50 | 311.67 |
May | 415.33 | 0.51 | 0.48 | 01-MAY-06:10 | 2100.55 | 14.76 | 0.00 | 398.33 | 1207.35 | 18.23 | 0.00 | 367.17 |
June | 421.50 | 0.51 | 0.48 | 01-JUN-05:49 | 1730.77 | 14.53 | 0.00 | 397.00 | 1078.97 | 18.09 | 0.00 | 362.83 |
July | 430.33 | 0.51 | 0.48 | 01-JUL-06:19 | 1923.38 | 14.48 | 0.00 | 401.83 | 1134.75 | 17.97 | 0.50 | 368.33 |
August | 394.50 | 0.51 | 0.48 | 01-AUG-06:10 | 2073.86 | 14.21 | 0.00 | 373.50 | 1312.93 | 17.75 | 9.17 | 346.00 |
September | 354.00 | 0.51 | 0.48 | 01-SEP-06:30 | 3306.42 | 16.07 | 29.50 | 337.00 | 1613.37 | 17.80 | 5.00 | 311.83 |
October | 262.67 | 0.50 | 0.48 | 01-OCT-06:40 | 14713.83 | 36.43 | 240.33 | 302.33 | 2245.37 | 17.88 | 9.00 | 282.67 |
November | 257.67 | 0.50 | 0.48 | 01-NOV-08:39 | 12931.32 | 39.64 | 256.00 | 267.17 | 4015.55 | 27.29 | 131.83 | 251.50 |
December | 251.17 | 0.49 | 0.48 | 01-DEC-07:40 | 10610.91 | 39.95 | 250.67 | 259.50 | 8617.20 | 40.49 | 247.17 | 252.17 |
Annual Sum or Average | 3902.00 | 0.50 | 5829.21 | 22.76 | 1302.00 | 3947.33 | 2470.78 | 21.34 | 699.33 | 3666.00 | ||
Minimum of Months | 245.50 | 0.49 | 0.48 | 1730.77 | 14.21 | 0.00 | 259.50 | 1078.97 | 17.68 | 0.00 | 249.50 | |
Maximum of Months | 430.33 | 0.51 | 0.48 | 15109.62 | 39.95 | 274.17 | 401.83 | 8617.20 | 40.49 | 247.17 | 368.33 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_2_DAYLCTRL
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 276.50 | 0.53 | 0.48 | 01-JAN-07:40 | 2842.59 | 22.86 | 99.83 | 247.00 | 1645.90 | 23.11 | 87.00 | 222.00 |
February | 245.50 | 0.51 | 0.48 | 01-FEB-10:39 | 4273.91 | 22.92 | 84.33 | 256.83 | 2570.37 | 23.39 | 65.67 | 222.33 |
March | 296.17 | 0.51 | 0.48 | 01-MAR-06:49 | 4119.24 | 21.85 | 83.50 | 324.00 | 2333.63 | 22.65 | 61.83 | 292.50 |
April | 296.67 | 0.51 | 0.48 | 03-APR-09:39 | 4539.75 | 22.63 | 96.17 | 346.83 | 2037.74 | 22.10 | 52.50 | 316.33 |
May | 415.33 | 0.50 | 0.48 | 01-MAY-05:49 | 3590.60 | 21.21 | 111.67 | 405.33 | 2001.07 | 22.43 | 83.83 | 376.50 |
June | 421.50 | 0.50 | 0.48 | 01-JUN-04:00 | 4271.54 | 20.81 | 109.00 | 409.83 | 2505.94 | 22.90 | 91.67 | 385.33 |
July | 430.33 | 0.50 | 0.48 | 01-JUL-05:10 | 3843.55 | 21.06 | 116.50 | 411.83 | 2126.63 | 22.11 | 84.67 | 384.33 |
August | 394.50 | 0.51 | 0.48 | 01-AUG-05:49 | 5257.92 | 22.47 | 131.00 | 377.17 | 2275.87 | 21.83 | 73.83 | 350.33 |
September | 354.00 | 0.51 | 0.48 | 01-SEP-05:49 | 4313.15 | 22.03 | 108.33 | 336.50 | 2465.66 | 23.60 | 88.17 | 316.17 |
October | 262.67 | 0.51 | 0.48 | 01-OCT-06:19 | 3987.17 | 22.46 | 79.83 | 294.00 | 2276.76 | 23.24 | 56.67 | 266.50 |
November | 257.67 | 0.52 | 0.48 | 01-NOV-08:39 | 2721.50 | 20.92 | 70.50 | 249.67 | 1486.31 | 22.07 | 69.83 | 212.83 |
December | 251.17 | 0.52 | 0.48 | 01-DEC-07:40 | 2866.57 | 23.56 | 93.17 | 240.17 | 1699.52 | 23.84 | 87.17 | 209.33 |
Annual Sum or Average | 3902.00 | 0.51 | 3951.15 | 21.95 | 1183.83 | 3899.17 | 2143.22 | 22.71 | 902.83 | 3554.50 | ||
Minimum of Months | 245.50 | 0.50 | 0.48 | 2721.50 | 20.81 | 70.50 | 240.17 | 1486.31 | 21.83 | 52.50 | 209.33 | |
Maximum of Months | 430.33 | 0.53 | 0.48 | 5257.92 | 23.56 | 131.00 | 411.83 | 2570.37 | 23.84 | 91.67 | 385.33 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_3_DAYLCTRL
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 276.50 | 0.56 | 0.48 | 01-JAN-08:00 | 641.36 | 10.71 | 0.00 | 229.83 | 444.56 | 14.55 | 0.00 | 187.33 |
February | 245.50 | 0.52 | 0.48 | 01-FEB-10:39 | 772.19 | 12.24 | 0.00 | 247.00 | 552.79 | 16.10 | 0.00 | 197.83 |
March | 296.17 | 0.51 | 0.48 | 01-MAR-07:30 | 993.28 | 13.71 | 0.00 | 320.17 | 670.34 | 17.32 | 0.00 | 278.83 |
April | 296.67 | 0.50 | 0.48 | 03-APR-09:39 | 1309.46 | 14.85 | 0.00 | 348.33 | 810.33 | 18.33 | 8.00 | 312.83 |
May | 415.33 | 0.50 | 0.48 | 01-MAY-05:00 | 1577.94 | 15.23 | 2.33 | 411.83 | 914.28 | 18.75 | 12.00 | 387.17 |
June | 421.50 | 0.49 | 0.48 | 01-JUN-05:10 | 1731.47 | 18.51 | 65.17 | 420.33 | 1008.07 | 21.74 | 81.17 | 408.83 |
July | 430.33 | 0.50 | 0.48 | 01-JUL-05:30 | 1627.37 | 16.50 | 29.50 | 422.33 | 938.48 | 19.90 | 45.33 | 399.50 |
August | 394.50 | 0.50 | 0.48 | 01-AUG-05:00 | 1312.61 | 14.68 | 0.00 | 384.83 | 828.42 | 18.25 | 17.83 | 355.50 |
September | 354.00 | 0.51 | 0.48 | 01-SEP-06:30 | 1083.28 | 14.21 | 0.00 | 334.83 | 711.96 | 17.76 | 0.00 | 302.50 |
October | 262.67 | 0.52 | 0.48 | 01-OCT-06:00 | 930.72 | 13.50 | 0.00 | 288.00 | 650.84 | 17.20 | 0.00 | 239.50 |
November | 257.67 | 0.54 | 0.48 | 01-NOV-08:50 | 721.89 | 11.73 | 0.00 | 238.00 | 509.67 | 15.57 | 0.00 | 188.67 |
December | 251.17 | 0.55 | 0.48 | 01-DEC-08:30 | 659.32 | 11.34 | 0.00 | 224.50 | 454.00 | 15.20 | 0.00 | 180.17 |
Annual Sum or Average | 3902.00 | 0.51 | 1187.20 | 14.33 | 97.00 | 3870.00 | 743.52 | 17.91 | 164.33 | 3438.67 | ||
Minimum of Months | 245.50 | 0.49 | 0.48 | 641.36 | 10.71 | 0.00 | 224.50 | 444.56 | 14.55 | 0.00 | 180.17 | |
Maximum of Months | 430.33 | 0.56 | 0.48 | 1731.47 | 18.51 | 65.17 | 422.33 | 1008.07 | 21.74 | 81.17 | 408.83 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_4_DAYLCTRL
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 276.50 | 0.52 | 0.48 | 01-JAN-08:00 | 3210.26 | 24.02 | 109.00 | 256.33 | 1936.82 | 24.22 | 97.50 | 233.17 |
February | 245.50 | 0.50 | 0.48 | 01-FEB-10:39 | 3428.12 | 23.18 | 81.50 | 260.33 | 1919.97 | 23.52 | 64.33 | 230.67 |
March | 296.17 | 0.50 | 0.48 | 01-MAR-07:30 | 3893.13 | 22.59 | 99.83 | 332.83 | 2238.72 | 23.30 | 74.67 | 304.50 |
April | 296.67 | 0.50 | 0.48 | 03-APR-09:39 | 3694.51 | 20.99 | 85.33 | 351.83 | 1700.29 | 20.83 | 38.33 | 321.67 |
May | 415.33 | 0.50 | 0.48 | 01-MAY-06:40 | 3869.07 | 19.01 | 82.17 | 403.50 | 1707.13 | 18.34 | 0.00 | 376.50 |
June | 421.50 | 0.50 | 0.48 | 01-JUN-05:00 | 3740.91 | 14.35 | 1.83 | 407.50 | 2160.88 | 17.92 | 0.00 | 386.83 |
July | 430.33 | 0.51 | 0.48 | 01-JUL-06:19 | 3213.56 | 17.28 | 56.83 | 410.17 | 1785.19 | 18.11 | 0.17 | 386.83 |
August | 394.50 | 0.50 | 0.48 | 01-AUG-06:19 | 4157.34 | 18.59 | 79.33 | 383.50 | 1910.09 | 18.09 | 7.83 | 364.33 |
September | 354.00 | 0.50 | 0.48 | 01-SEP-06:49 | 3649.34 | 21.86 | 109.83 | 339.17 | 2011.28 | 22.86 | 80.17 | 318.67 |
October | 262.67 | 0.50 | 0.48 | 01-OCT-06:00 | 4660.61 | 23.59 | 93.83 | 299.83 | 1889.12 | 23.18 | 55.00 | 273.33 |
November | 257.67 | 0.51 | 0.48 | 01-NOV-08:50 | 3264.86 | 24.47 | 98.50 | 258.33 | 1889.26 | 24.71 | 89.50 | 224.50 |
December | 251.17 | 0.51 | 0.48 | 01-DEC-08:30 | 2693.36 | 24.39 | 96.50 | 247.50 | 1567.25 | 24.54 | 87.33 | 227.33 |
Annual Sum or Average | 3902.00 | 0.50 | 3643.98 | 20.59 | 994.50 | 3950.83 | 1897.64 | 21.11 | 594.83 | 3648.33 | ||
Minimum of Months | 245.50 | 0.50 | 0.48 | 2693.36 | 14.35 | 1.83 | 247.50 | 1567.25 | 17.92 | 0.00 | 224.50 | |
Maximum of Months | 430.33 | 0.52 | 0.48 | 4660.61 | 24.47 | 109.83 | 410.17 | 2238.72 | 24.71 | 97.50 | 386.83 |
Report: CoilReportMonthly
For: VAV_BOT WITH REHEAT HEATING COIL
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.683402E+10 | 41334.40 | 05-JAN-19:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.642014E+10 | 29953.54 | 11-FEB-18:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.287688E+10 | 26185.25 | 04-MAR-18:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.106628E+10 | 21800.31 | 17-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 29106792.09 | 6482.15 | 02-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 88093720.90 | 9574.37 | 22-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.261998E+10 | 26567.40 | 30-OCT-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.369253E+10 | 34600.73 | 29-NOV-21:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.116647E+11 | 48399.32 | 23-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.352917E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.116647E+11 | 48399.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_BOTTOM VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.422131E+09 | 16911.67 | 13-JAN-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.431828E+09 | 16892.79 | 02-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 53977227.99 | 15774.11 | 20-MAR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 26370143.89 | 15609.12 | 03-APR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.113025E+09 | 15694.91 | 31-OCT-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.178009E+09 | 16096.67 | 02-NOV-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.886431E+09 | 16892.36 | 11-DEC-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.211177E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.886431E+09 | 16911.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.539902E+09 | 15766.43 | 13-JAN-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.651438E+09 | 15778.28 | 03-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.269129E+09 | 15341.56 | 20-MAR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.114008E+09 | 15789.07 | 15-APR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 2920616.91 | 1381.63 | 22-SEP-05:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.289260E+09 | 15321.71 | 31-OCT-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.410102E+09 | 15546.06 | 27-NOV-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.110619E+10 | 15797.12 | 09-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.338295E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.110619E+10 | 15797.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.463807E+09 | 21640.67 | 03-JAN-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.693916E+09 | 21574.49 | 01-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.308991E+09 | 21018.93 | 20-MAR-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.212891E+09 | 21611.49 | 04-APR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6922554.77 | 5893.64 | 01-MAY-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 6406900.65 | 2551.97 | 22-SEP-05:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.403605E+09 | 21646.04 | 25-OCT-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.354386E+09 | 21613.32 | 21-NOV-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.923357E+09 | 21603.40 | 27-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.337428E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.923357E+09 | 21646.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.244315E+09 | 13941.70 | 06-JAN-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.162431E+09 | 13945.67 | 06-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 4280951.75 | 5406.86 | 20-MAR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 60850913.89 | 13943.97 | 31-OCT-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 41914438.68 | 13945.38 | 01-NOV-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.203260E+09 | 13942.60 | 23-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.717052E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.244315E+09 | 13945.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV_MID WITH REHEAT HEATING COIL
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.101137E+12 | 433993.13 | 05-JAN-19:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.101274E+12 | 327255.85 | 11-FEB-18:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.586668E+11 | 287061.81 | 04-MAR-18:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.324029E+11 | 275339.92 | 17-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.116923E+10 | 112230.91 | 02-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.172630E+10 | 125985.43 | 22-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.460914E+11 | 310022.78 | 30-OCT-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.764770E+11 | 369816.11 | 29-NOV-21:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.164553E+12 | 542466.09 | 23-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.583497E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.164553E+12 | 542466.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_MID VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.168970E+09 | 85750.37 | 02-JAN-06:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.184911E+10 | 566353.53 | 06-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.545270E+09 | 564071.59 | 20-MAR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.291761E+10 | 567545.77 | 26-DEC-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.548096E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.291761E+10 | 567545.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.285823E+11 | 163526.53 | 27-JAN-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.362291E+11 | 160856.63 | 28-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.197703E+11 | 162243.59 | 31-MAR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.106208E+11 | 151241.93 | 24-APR-04:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.718616E+09 | 150520.22 | 01-MAY-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.247706E+09 | 161691.88 | 22-SEP-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.121949E+11 | 162427.04 | 17-OCT-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.221027E+11 | 160183.89 | 16-NOV-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.553163E+11 | 152082.72 | 27-DEC-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.185783E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.553163E+11 | 163526.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.207167E+11 | 197971.30 | 30-JAN-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.244940E+11 | 198647.65 | 06-FEB-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.161437E+11 | 198777.69 | 20-MAR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.961918E+10 | 198053.98 | 03-APR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.600896E+09 | 197876.36 | 01-MAY-04:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.304564E+09 | 172847.63 | 22-SEP-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.123418E+11 | 198023.96 | 31-OCT-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.180779E+11 | 198110.28 | 02-NOV-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.384454E+11 | 198183.31 | 11-DEC-04:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.140744E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.384454E+11 | 198777.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.122739E+11 | 224080.15 | 06-JAN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.203477E+11 | 225509.43 | 13-FEB-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.161362E+11 | 226526.24 | 20-MAR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.102979E+11 | 225218.42 | 24-APR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.995768E+09 | 223762.95 | 01-MAY-04:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.276510E+09 | 224202.84 | 22-SEP-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.113496E+11 | 224151.12 | 31-OCT-04:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.119324E+11 | 225120.87 | 21-NOV-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.286582E+11 | 226577.59 | 27-DEC-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.112268E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.286582E+11 | 226577.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.198531E+11 | 202108.23 | 06-JAN-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.225478E+11 | 202761.80 | 06-FEB-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.150073E+11 | 201978.59 | 21-MAR-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.874966E+10 | 202232.83 | 03-APR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.876680E+09 | 165151.76 | 01-MAY-04:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.434807E+09 | 185477.89 | 22-SEP-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.108456E+11 | 202202.45 | 30-OCT-04:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.164968E+11 | 202200.25 | 01-NOV-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.340113E+11 | 202144.87 | 26-DEC-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.128823E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.340113E+11 | 202761.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV_TOP WITH REHEAT HEATING COIL
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.133066E+11 | 50322.20 | 05-JAN-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.129333E+11 | 36478.87 | 11-FEB-18:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.788307E+10 | 34509.76 | 04-MAR-18:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.470283E+10 | 32847.80 | 17-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.285501E+09 | 16223.29 | 02-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.328777E+09 | 18936.94 | 22-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.667417E+10 | 36986.70 | 30-OCT-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.103923E+11 | 43047.92 | 29-NOV-21:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.204195E+11 | 62372.48 | 23-DEC-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.769261E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.204195E+11 | 62372.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_TOP VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.379097E+10 | 85760.87 | 30-JAN-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.397390E+10 | 85559.01 | 21-FEB-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.203579E+10 | 85365.04 | 20-MAR-03:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.214338E+10 | 85531.93 | 24-APR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.209359E+09 | 84896.41 | 01-MAY-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.158979E+10 | 85159.43 | 30-OCT-04:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.220676E+10 | 85535.89 | 27-NOV-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.533714E+10 | 85153.77 | 26-DEC-04:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.212871E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.533714E+10 | 85760.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.708866E+10 | 17180.03 | 30-JAN-05:23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.737118E+10 | 17168.60 | 21-FEB-05:23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.486711E+10 | 17175.02 | 21-MAR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.329764E+10 | 17090.16 | 03-APR-03:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.349535E+09 | 17165.98 | 01-MAY-05:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.165397E+09 | 17062.85 | 22-SEP-04:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.343647E+10 | 17165.92 | 24-OCT-04:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.527697E+10 | 17166.00 | 27-NOV-05:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.105153E+11 | 17088.24 | 27-DEC-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.423683E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.105153E+11 | 17180.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.413594E+10 | 22131.14 | 05-JAN-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.427748E+10 | 22132.88 | 07-FEB-05:32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.308112E+10 | 22047.15 | 27-MAR-04:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.219642E+10 | 22133.97 | 04-APR-04:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.215304E+09 | 22153.31 | 01-MAY-04:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 327193.14 | 1109.09 | 23-AUG-05:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.120114E+09 | 21929.11 | 22-SEP-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.252368E+10 | 22135.04 | 31-OCT-04:23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.337317E+10 | 22146.17 | 24-NOV-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.652474E+10 | 22137.76 | 13-DEC-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.264483E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.652474E+10 | 22153.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.328412E+10 | 24407.13 | 03-JAN-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.441428E+10 | 24399.73 | 01-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.384198E+10 | 24482.44 | 21-MAR-04:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.314139E+10 | 24400.80 | 03-APR-03:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.460036E+09 | 24397.49 | 01-MAY-04:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.140204E+09 | 24135.10 | 22-SEP-04:42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.293559E+10 | 24411.49 | 24-OCT-04:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.301092E+10 | 24406.87 | 22-NOV-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.600554E+10 | 24397.90 | 27-DEC-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.272341E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.600554E+10 | 24482.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.392773E+10 | 23762.68 | 06-JAN-05:22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.407478E+10 | 23736.94 | 08-FEB-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.298642E+10 | 23721.22 | 18-MAR-04:22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.205011E+10 | 23776.90 | 04-APR-04:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.327886E+09 | 23795.47 | 01-MAY-04:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 1815962.37 | 1396.81 | 23-AUG-05:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.160642E+09 | 23701.79 | 22-SEP-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.230643E+10 | 23734.33 | 23-OCT-04:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.316483E+10 | 23788.61 | 24-NOV-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.583693E+10 | 23770.47 | 12-DEC-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.248376E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.583693E+10 | 23795.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CAV_BAS HEATING COIL
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 108.04 | 0.72 | 17-AUG-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 108.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 108.04 | 0.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BASEMENT HEATING COIL
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BOT HEATING COIL
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER MID HEATING COIL
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER TOP HEATING COIL
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BOT_SUPPHEATCOIL
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER MID_SUPPHEATCOIL
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER TOP_SUPPHEATCOIL
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV_BOT WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.360834E+10 | 0.360834E+10 | 64736.05 | 20-JAN-14:00 | 64736.05 | 0.00 |
February | 0.00 | 0.00 | 0.125846E+10 | 0.125846E+10 | 40914.82 | 18-FEB-13:55 | 40914.82 | 0.00 |
March | 0.00 | 0.00 | 0.106820E+11 | 0.106820E+11 | 105869.45 | 13-MAR-16:00 | 105869.45 | 0.00 |
April | 0.00 | 0.00 | 0.108314E+11 | 0.108314E+11 | 86248.13 | 19-APR-13:50 | 86248.13 | 0.01 |
May | 0.00 | 0.00 | 0.361822E+11 | 0.361822E+11 | 115300.00 | 31-MAY-15:20 | 115300.00 | 0.06 |
June | 0.00 | 0.00 | 0.116996E+12 | 0.116792E+12 | 160122.77 | 26-JUN-15:00 | 160122.77 | 0.32 |
July | 0.00 | 0.00 | 0.123968E+12 | 0.121029E+12 | 151229.84 | 17-JUL-10:20 | 151229.84 | 0.36 |
August | 0.00 | 0.00 | 0.125278E+12 | 0.124508E+12 | 158748.97 | 16-AUG-14:40 | 158748.97 | 0.43 |
September | 0.00 | 0.00 | 0.776261E+11 | 0.776261E+11 | 138098.95 | 12-SEP-15:40 | 138098.95 | 0.08 |
October | 0.00 | 0.00 | 0.169947E+11 | 0.169947E+11 | 125394.35 | 10-OCT-15:50 | 125394.35 | 0.00 |
November | 0.00 | 0.00 | 0.679412E+10 | 0.679412E+10 | 88260.32 | 07-NOV-15:00 | 88260.32 | 0.00 |
December | 0.00 | 0.00 | 0.399240E+10 | 0.399240E+10 | 75149.06 | 01-DEC-13:55 | 75149.06 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.534211E+12 | 0.530299E+12 | 0.11 | |||
Minimum of Months | 0.00 | 0.00 | 0.125846E+10 | 0.125846E+10 | 40914.82 | 40914.82 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.125278E+12 | 0.124508E+12 | 160122.77 | 160122.77 | 0.43 |
Report: CoilReportMonthly
For: VAV_MID WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.310026E+11 | 0.310026E+11 | 538898.64 | 20-JAN-14:10 | 538898.64 | 0.00 |
February | 0.00 | 0.00 | 0.117119E+11 | 0.117119E+11 | 383053.19 | 18-FEB-14:00 | 383053.19 | 0.00 |
March | 0.00 | 0.00 | 0.855252E+11 | 0.855252E+11 | 847605.73 | 13-MAR-15:40 | 847605.73 | 0.00 |
April | 0.00 | 0.00 | 0.724676E+11 | 0.724676E+11 | 641589.51 | 20-APR-13:00 | 641589.51 | 0.01 |
May | 0.00 | 0.00 | 0.310742E+12 | 0.310742E+12 | 1049601.73 | 31-MAY-15:50 | 1049601.73 | 0.06 |
June | 0.00 | 0.00 | 0.101384E+13 | 0.101209E+13 | 1469172.30 | 26-JUN-14:50 | 1469172.30 | 0.30 |
July | 0.00 | 0.00 | 0.102112E+13 | 0.100124E+13 | 1341152.97 | 24-JUL-15:30 | 1341152.97 | 0.31 |
August | 0.00 | 0.00 | 0.985463E+12 | 0.981803E+12 | 1422355.14 | 16-AUG-15:10 | 1422355.14 | 0.33 |
September | 0.00 | 0.00 | 0.684236E+12 | 0.684236E+12 | 1294477.73 | 12-SEP-15:50 | 1294477.73 | 0.07 |
October | 0.00 | 0.00 | 0.146134E+12 | 0.146134E+12 | 1062231.90 | 11-OCT-15:00 | 1062231.90 | 0.00 |
November | 0.00 | 0.00 | 0.524123E+11 | 0.524123E+11 | 696709.69 | 07-NOV-15:00 | 696709.69 | 0.00 |
December | 0.00 | 0.00 | 0.297373E+11 | 0.297373E+11 | 541067.51 | 01-DEC-14:10 | 541067.51 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.444439E+13 | 0.441911E+13 | 0.09 | |||
Minimum of Months | 0.00 | 0.00 | 0.117119E+11 | 0.117119E+11 | 383053.19 | 383053.19 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.102112E+13 | 0.101209E+13 | 1469172.30 | 1469172.30 | 0.33 |
Report: CoilReportMonthly
For: VAV_TOP WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.256010E+10 | 0.256010E+10 | 53588.93 | 20-JAN-14:10 | 53588.93 | 0.00 |
February | 0.00 | 0.00 | 0.105158E+10 | 0.105158E+10 | 40135.44 | 18-FEB-13:55 | 40135.44 | 0.00 |
March | 0.00 | 0.00 | 0.807168E+10 | 0.807168E+10 | 86902.07 | 13-MAR-15:40 | 86902.07 | 0.00 |
April | 0.00 | 0.00 | 0.747890E+10 | 0.747890E+10 | 70338.34 | 20-APR-13:00 | 70338.34 | 0.01 |
May | 0.00 | 0.00 | 0.320597E+11 | 0.320597E+11 | 127127.86 | 31-MAY-15:20 | 127127.86 | 0.05 |
June | 0.00 | 0.00 | 0.112913E+12 | 0.112789E+12 | 183092.46 | 26-JUN-15:00 | 183092.46 | 0.30 |
July | 0.00 | 0.00 | 0.111448E+12 | 0.109497E+12 | 160093.91 | 17-JUL-14:00 | 160093.91 | 0.31 |
August | 0.00 | 0.00 | 0.108017E+12 | 0.107690E+12 | 171997.97 | 16-AUG-15:00 | 171997.97 | 0.32 |
September | 0.00 | 0.00 | 0.711736E+11 | 0.711736E+11 | 151431.18 | 10-SEP-14:31 | 151431.18 | 0.07 |
October | 0.00 | 0.00 | 0.135552E+11 | 0.135552E+11 | 119202.95 | 11-OCT-15:00 | 119202.95 | 0.00 |
November | 0.00 | 0.00 | 0.451056E+10 | 0.451056E+10 | 69536.78 | 07-NOV-15:00 | 69536.78 | 0.00 |
December | 0.00 | 0.00 | 0.258236E+10 | 0.258236E+10 | 50278.83 | 01-DEC-14:00 | 50278.83 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.475421E+12 | 0.473019E+12 | 0.09 | |||
Minimum of Months | 0.00 | 0.00 | 0.105158E+10 | 0.105158E+10 | 40135.44 | 40135.44 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.112913E+12 | 0.112789E+12 | 183092.46 | 183092.46 | 0.32 |
Report: CoilReportMonthly
For: CAV_BAS COOLING COIL
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.119122E+10 | 0.119122E+10 | 34967.27 | 20-JAN-13:55 | 34967.27 | 0.00 |
February | 0.00 | 0.00 | 87731165.80 | 87731165.80 | 11613.53 | 18-FEB-13:00 | 11613.53 | 0.00 |
March | 0.00 | 0.00 | 0.401397E+10 | 0.401397E+10 | 61281.42 | 14-MAR-13:00 | 61281.42 | 0.00 |
April | 0.00 | 0.00 | 0.448175E+10 | 0.448175E+10 | 44718.93 | 20-APR-13:00 | 44718.93 | 0.00 |
May | 0.00 | 0.00 | 0.204671E+11 | 0.204575E+11 | 64711.63 | 31-MAY-14:00 | 64711.63 | 0.04 |
June | 0.00 | 0.00 | 0.650860E+11 | 0.650314E+11 | 86188.11 | 26-JUN-15:00 | 86188.11 | 0.23 |
July | 0.00 | 0.00 | 0.660625E+11 | 0.654151E+11 | 114582.14 | 04-JUL-14:27 | 114582.14 | 0.27 |
August | 0.00 | 0.00 | 0.684522E+11 | 0.682785E+11 | 140914.62 | 06-AUG-13:27 | 100160.04 | 0.26 |
September | 0.00 | 0.00 | 0.476710E+11 | 0.476649E+11 | 114604.39 | 10-SEP-16:30 | 114604.39 | 0.06 |
October | 0.00 | 0.00 | 0.814880E+10 | 0.814880E+10 | 75662.14 | 10-OCT-14:00 | 75662.14 | 0.00 |
November | 0.00 | 0.00 | 0.300102E+10 | 0.300102E+10 | 56773.77 | 06-NOV-13:05 | 56773.77 | 0.00 |
December | 0.00 | 0.00 | 0.155603E+10 | 0.155603E+10 | 43367.47 | 01-DEC-14:00 | 43367.47 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.290219E+12 | 0.289328E+12 | 0.07 | |||
Minimum of Months | 0.00 | 0.00 | 87731165.80 | 87731165.80 | 11613.53 | 11613.53 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.684522E+11 | 0.682785E+11 | 140914.62 | 114604.39 | 0.27 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BASEMENT COOLING COIL
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.999590E+10 | 0.847445E+10 | 5665.83 | 19-JAN-11:30 | 4881.36 | 0.00 |
February | 0.00 | 0.00 | 0.142924E+11 | 0.122221E+11 | 45253.73 | 18-FEB-13:55 | 45253.73 | 0.00 |
March | 0.00 | 0.00 | 0.393196E+11 | 0.377007E+11 | 245822.25 | 14-MAR-13:00 | 245822.25 | 0.00 |
April | 0.00 | 0.00 | 0.859432E+11 | 0.803029E+11 | 285374.41 | 19-APR-14:00 | 285374.41 | 0.00 |
May | 0.00 | 0.00 | 0.281589E+11 | 0.268488E+11 | 148756.08 | 31-MAY-16:00 | 137211.57 | 0.00 |
June | 0.00 | 0.00 | 0.291414E+12 | 0.262568E+12 | 335268.33 | 18-JUN-10:42 | 217476.57 | 0.00 |
July | 0.00 | 0.00 | 0.604409E+12 | 0.495042E+12 | 462232.64 | 31-JUL-23:05 | 174398.83 | 0.00 |
August | 0.00 | 0.00 | 0.821816E+12 | 0.651974E+12 | 468917.57 | 04-AUG-01:53 | 139350.49 | 0.00 |
September | 0.00 | 0.00 | 0.867252E+11 | 0.822163E+11 | 150456.93 | 07-SEP-16:00 | 138881.03 | 0.00 |
October | 0.00 | 0.00 | 0.311665E+11 | 0.293384E+11 | 234058.92 | 11-OCT-14:00 | 234058.92 | 0.00 |
November | 0.00 | 0.00 | 0.312033E+11 | 0.286959E+11 | 195531.47 | 07-NOV-15:00 | 195531.47 | 0.00 |
December | 0.00 | 0.00 | 0.409576E+11 | 0.404444E+11 | 284146.84 | 01-DEC-14:00 | 284146.84 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.208540E+13 | 0.175583E+13 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.999590E+10 | 0.847445E+10 | 5665.83 | 4881.36 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.821816E+12 | 0.651974E+12 | 468917.57 | 285374.41 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BOT COOLING COIL
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.475440E+10 | 0.474523E+10 | 3244.27 | 23-JAN-16:40 | 3244.27 | 0.00 |
February | 0.00 | 0.00 | 0.894405E+10 | 0.894005E+10 | 5201.86 | 17-FEB-17:00 | 5184.93 | 0.00 |
March | 0.00 | 0.00 | 0.155939E+11 | 0.155824E+11 | 7854.81 | 31-MAR-24:00 | 7854.81 | 0.00 |
April | 0.00 | 0.00 | 0.202017E+11 | 0.201727E+11 | 9191.39 | 08-APR-18:00 | 9191.39 | 0.00 |
May | 0.00 | 0.00 | 0.616237E+10 | 0.610009E+10 | 4226.21 | 31-MAY-23:30 | 4185.91 | 0.00 |
June | 0.00 | 0.00 | 0.115464E+11 | 0.114262E+11 | 6073.25 | 30-JUN-24:00 | 6073.25 | 0.00 |
July | 0.00 | 0.00 | 0.169534E+11 | 0.168017E+11 | 7986.74 | 31-JUL-24:00 | 7986.74 | 0.00 |
August | 0.00 | 0.00 | 0.219906E+11 | 0.218718E+11 | 9504.98 | 05-AUG-18:21 | 9466.08 | 0.00 |
September | 0.00 | 0.00 | 0.629867E+10 | 0.624982E+10 | 4026.20 | 30-SEP-24:00 | 4026.20 | 0.00 |
October | 0.00 | 0.00 | 0.107705E+11 | 0.107489E+11 | 5721.81 | 09-OCT-16:44 | 5721.81 | 0.00 |
November | 0.00 | 0.00 | 0.150662E+11 | 0.150513E+11 | 7240.47 | 05-NOV-16:13 | 7240.47 | 0.00 |
December | 0.00 | 0.00 | 0.201645E+11 | 0.201645E+11 | 8948.77 | 03-DEC-16:00 | 8948.77 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.158447E+12 | 0.157855E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.475440E+10 | 0.474523E+10 | 3244.27 | 3244.27 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.219906E+11 | 0.218718E+11 | 9504.98 | 9466.08 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER MID COOLING COIL
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.291718E+11 | 0.290838E+11 | 29891.02 | 23-JAN-16:40 | 29891.02 | 0.00 |
February | 0.00 | 0.00 | 0.692312E+11 | 0.691909E+11 | 48760.22 | 17-FEB-17:00 | 48506.69 | 0.00 |
March | 0.00 | 0.00 | 0.134121E+12 | 0.134007E+12 | 72920.17 | 31-MAR-23:30 | 72920.17 | 0.00 |
April | 0.00 | 0.00 | 0.178743E+12 | 0.178453E+12 | 86526.89 | 08-APR-17:55 | 86526.89 | 0.00 |
May | 0.00 | 0.00 | 0.528108E+11 | 0.522018E+11 | 39942.56 | 31-MAY-23:20 | 39436.65 | 0.00 |
June | 0.00 | 0.00 | 0.108279E+12 | 0.107088E+12 | 59187.27 | 30-JUN-24:00 | 59187.27 | 0.00 |
July | 0.00 | 0.00 | 0.160362E+12 | 0.158855E+12 | 75196.60 | 31-JUL-24:00 | 75196.60 | 0.00 |
August | 0.00 | 0.00 | 0.207889E+12 | 0.206705E+12 | 90176.10 | 13-AUG-18:34 | 90176.10 | 0.00 |
September | 0.00 | 0.00 | 0.555964E+11 | 0.551200E+11 | 36293.22 | 30-SEP-23:50 | 36293.22 | 0.00 |
October | 0.00 | 0.00 | 0.911660E+11 | 0.909537E+11 | 52004.97 | 08-OCT-16:45 | 52004.97 | 0.00 |
November | 0.00 | 0.00 | 0.128385E+12 | 0.128237E+12 | 67789.66 | 07-NOV-16:20 | 67789.66 | 0.00 |
December | 0.00 | 0.00 | 0.169525E+12 | 0.169525E+12 | 81966.17 | 01-DEC-16:00 | 81966.17 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.138528E+13 | 0.137942E+13 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.291718E+11 | 0.290838E+11 | 29891.02 | 29891.02 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.207889E+12 | 0.206705E+12 | 90176.10 | 90176.10 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER TOP COOLING COIL
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.157265E+10 | 0.156457E+10 | 2982.34 | 20-JAN-16:40 | 2982.34 | 0.00 |
February | 0.00 | 0.00 | 0.550741E+10 | 0.550346E+10 | 4882.43 | 17-FEB-17:00 | 4860.71 | 0.00 |
March | 0.00 | 0.00 | 0.122165E+11 | 0.122053E+11 | 7112.05 | 31-MAR-23:20 | 7112.05 | 0.00 |
April | 0.00 | 0.00 | 0.166176E+11 | 0.165887E+11 | 8687.25 | 08-APR-17:55 | 8687.25 | 0.00 |
May | 0.00 | 0.00 | 0.480355E+10 | 0.474296E+10 | 3959.19 | 31-MAY-23:20 | 3908.43 | 0.00 |
June | 0.00 | 0.00 | 0.108298E+11 | 0.107107E+11 | 5926.13 | 30-JUN-24:00 | 5926.13 | 0.00 |
July | 0.00 | 0.00 | 0.160469E+11 | 0.158963E+11 | 7519.53 | 01-JUL-18:50 | 7519.53 | 0.00 |
August | 0.00 | 0.00 | 0.207674E+11 | 0.206492E+11 | 9156.73 | 13-AUG-18:28 | 9156.73 | 0.00 |
September | 0.00 | 0.00 | 0.529004E+10 | 0.524256E+10 | 3853.11 | 10-SEP-17:35 | 3853.11 | 0.00 |
October | 0.00 | 0.00 | 0.789778E+10 | 0.787682E+10 | 5168.71 | 08-OCT-16:45 | 5168.71 | 0.00 |
November | 0.00 | 0.00 | 0.113190E+11 | 0.113043E+11 | 6813.84 | 07-NOV-16:20 | 6813.84 | 0.00 |
December | 0.00 | 0.00 | 0.152282E+11 | 0.152282E+11 | 8170.64 | 01-DEC-16:00 | 8170.64 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.128097E+12 | 0.127513E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.157265E+10 | 0.156457E+10 | 2982.34 | 2982.34 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.207674E+11 | 0.206492E+11 | 9156.73 | 9156.73 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 83895.95 | 1396601.25 | 03-JAN-05:01 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 103285.19 | 1843350.51 | 06-FEB-05:01 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 57162.07 | 1696019.32 | 20-MAR-05:01 |
April | 0.00 | 0.00 | 01-APR-00:10 | 34652.74 | 1380853.91 | 05-APR-04:01 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 2312.66 | 1659424.56 | 01-MAY-04:11 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 01-JUL-00:03 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.74 | 2361.84 | 23-AUG-05:10 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 1531.68 | 1291715.35 | 22-SEP-05:02 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 42871.63 | 1535099.78 | 23-OCT-04:01 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 67739.65 | 1421092.06 | 24-NOV-05:01 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 145524.71 | 1876877.49 | 27-DEC-06:01 |
Annual Sum or Average | 0.00 | 44642.49 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.00 | 0.00 | 145524.71 | 1876877.49 |
Report: PlantLoopDemandReportMonthly
For: COOLSYS1_SUPPLY
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 14843.81 | 742842.37 | 20-JAN-14:20 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 6641.31 | 478890.43 | 18-FEB-14:00 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 43358.72 | 1410534.32 | 14-MAR-13:40 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 37746.08 | 873116.90 | 19-APR-13:30 | 0.00 | 0.00 | 01-APR-00:10 |
May | 155328.82 | 1620212.00 | 31-MAY-13:30 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 520175.29 | 1880206.19 | 26-JUN-15:10 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 511266.28 | 1775428.77 | 18-JUL-15:10 | 0.00 | 0.00 | 01-JUL-00:03 |
August | 493738.90 | 1835267.01 | 21-AUG-09:50 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 350924.19 | 1716536.51 | 12-SEP-15:20 | 0.00 | 0.00 | 01-SEP-00:05 |
October | 71588.87 | 1411960.39 | 11-OCT-11:00 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 26957.75 | 1028808.43 | 07-NOV-15:00 | 0.00 | 0.00 | 01-NOV-00:05 |
December | 14863.55 | 762956.55 | 01-DEC-14:20 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 188259.49 | 0.00 | ||||
Minimum of Months | 6641.31 | 478890.43 | 0.00 | 0.00 | ||
Maximum of Months | 520175.29 | 1880206.19 | 0.00 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: COOLSYS1_DEMAND
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 14261.76 | 747789.19 | 20-JAN-14:10 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 5821.56 | 474289.25 | 18-FEB-13:55 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 42180.19 | 1454632.40 | 14-MAR-13:40 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 36729.51 | 871454.81 | 19-APR-13:30 | 0.00 | 0.00 | 01-APR-00:10 |
May | 152992.46 | 1470192.89 | 31-MAY-12:30 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 515907.63 | 1936535.52 | 25-JUN-16:21 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 505597.20 | 1793305.20 | 16-JUL-14:51 | 0.00 | 0.00 | 01-JUL-00:03 |
August | 489531.96 | 2044699.57 | 04-AUG-04:12 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 347258.61 | 2012379.28 | 10-SEP-15:11 | 0.00 | 0.00 | 01-SEP-00:05 |
October | 70281.92 | 1472088.48 | 11-OCT-11:00 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 26206.37 | 1026961.75 | 07-NOV-15:00 | 0.00 | 0.00 | 01-NOV-00:05 |
December | 14221.49 | 766245.41 | 01-DEC-14:10 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 186046.97 | 0.00 | ||||
Minimum of Months | 5821.56 | 474289.25 | 0.00 | 0.00 | ||
Maximum of Months | 515907.63 | 2044699.57 | 0.00 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SINGLE WATER PLANT LOOP
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 27496.80 | 218075.91 | 20-JAN-14:00 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 56588.18 | 281029.17 | 18-FEB-14:00 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 114810.78 | 1027602.62 | 14-MAR-13:00 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 179380.04 | 1046412.13 | 19-APR-14:00 | 0.00 | 0.00 | 01-APR-00:10 |
May | 111014.07 | 995901.11 | 17-MAY-14:00 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 619804.77 | 1910276.17 | 26-JUN-15:00 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 923963.51 | 2017720.71 | 16-JUL-13:00 | 0.00 | 0.00 | 01-JUL-00:03 |
August | 1081698.67 | 2211558.70 | 16-AUG-16:00 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 280174.87 | 1205401.10 | 10-SEP-13:40 | 0.00 | 0.00 | 01-SEP-00:05 |
October | 95030.29 | 1142484.82 | 11-OCT-14:00 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 105346.72 | 806808.82 | 07-NOV-15:00 | 0.00 | 0.00 | 01-NOV-00:05 |
December | 130448.45 | 1038134.94 | 01-DEC-14:00 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 312723.29 | 0.00 | ||||
Minimum of Months | 27496.80 | 218075.91 | 0.00 | 0.00 | ||
Maximum of Months | 1081698.67 | 2211558.70 | 0.00 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 16398.21 | 55393.69 | 31-JAN-12:40 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 16671.56 | 55534.35 | 13-FEB-12:30 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 17384.39 | 55339.15 | 02-MAR-12:10 |
April | 0.00 | 0.00 | 01-APR-00:10 | 15795.02 | 53635.51 | 03-APR-12:00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 15454.68 | 51217.87 | 01-MAY-11:50 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 14942.11 | 48226.40 | 01-JUN-11:20 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 13298.74 | 45593.17 | 03-JUL-11:50 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 14213.74 | 44358.69 | 31-AUG-11:30 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 13650.77 | 45771.24 | 29-SEP-12:00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 14230.33 | 48472.54 | 31-OCT-11:40 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 15218.69 | 51379.96 | 30-NOV-12:40 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 15475.33 | 53829.57 | 29-DEC-13:00 |
Annual Sum or Average | 0.00 | 15219.51 | ||||
Minimum of Months | 0.00 | 0.00 | 13298.74 | 44358.69 | ||
Maximum of Months | 0.00 | 0.00 | 17384.39 | 55534.35 |
Report: PlantLoopDemandReportMonthly
For: TOWERWATERSYS
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 16406.03 | 855470.98 | 20-JAN-14:20 | 3383.55 | 141611.78 | 31-JAN-16:00 |
February | 5910.05 | 562856.00 | 18-FEB-14:00 | 5988.98 | 154104.58 | 12-FEB-07:21 |
March | 48065.45 | 2193577.62 | 13-MAR-14:40 | 3979.03 | 156956.84 | 28-MAR-04:01 |
April | 42563.36 | 996834.29 | 19-APR-13:30 | 3604.21 | 142538.78 | 15-APR-04:01 |
May | 191285.69 | 2308156.29 | 17-MAY-12:10 | 1840.19 | 135108.76 | 08-MAY-06:20 |
June | 684223.36 | 2443608.63 | 26-JUN-16:30 | 853.54 | 106768.35 | 09-JUN-05:30 |
July | 669345.19 | 2440531.50 | 14-JUL-14:40 | 705.60 | 87770.95 | 01-JUL-23:08 |
August | 644090.83 | 2441056.36 | 11-AUG-11:20 | 1452.63 | 86891.04 | 18-AUG-23:00 |
September | 465540.69 | 2441145.21 | 08-SEP-12:50 | 1115.66 | 125111.82 | 21-SEP-15:50 |
October | 87100.33 | 2312001.05 | 11-OCT-15:00 | 3035.61 | 136982.05 | 24-OCT-05:50 |
November | 29880.05 | 1175624.79 | 07-NOV-15:00 | 3320.72 | 147541.71 | 30-NOV-04:01 |
December | 16378.85 | 878424.69 | 01-DEC-14:20 | 3687.21 | 152326.84 | 23-DEC-02:42 |
Annual Sum or Average | 242971.37 | 2726.34 | ||||
Minimum of Months | 5910.05 | 562856.00 | 705.60 | 86891.04 | ||
Maximum of Months | 684223.36 | 2443608.63 | 5988.98 | 156956.84 |
Report: FanReportMonthly
For: CAV_BAS FAN
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.186703E+11 | 0.97 | 12271.38 | 01-JAN-00:05 | 1.70 |
February | 0.167674E+11 | 0.96 | 12271.38 | 01-FEB-05:01 | 1.71 |
March | 0.193790E+11 | 1.00 | 12271.38 | 01-MAR-04:03 | 1.70 |
April | 0.178009E+11 | 0.95 | 12271.38 | 01-APR-03:32 | 1.70 |
May | 0.188297E+11 | 0.97 | 12271.38 | 01-MAY-04:11 | 1.70 |
June | 0.190107E+11 | 1.01 | 12271.38 | 01-JUN-04:12 | 1.69 |
July | 0.191592E+11 | 0.98 | 12271.38 | 01-JUL-04:12 | 1.71 |
August | 0.207517E+11 | 1.07 | 12271.38 | 01-AUG-04:12 | 1.69 |
September | 0.195756E+11 | 1.04 | 12271.38 | 01-SEP-04:12 | 1.69 |
October | 0.197491E+11 | 1.02 | 12271.38 | 01-OCT-15:40 | 1.68 |
November | 0.185303E+11 | 0.99 | 12271.38 | 01-NOV-04:01 | 1.70 |
December | 0.182886E+11 | 0.95 | 12271.38 | 01-DEC-05:11 | 1.71 |
Annual Sum or Average | 0.226512E+12 | 0.99 | |||
Minimum of Months | 0.167674E+11 | 0.95 | 12271.38 | 1.68 | |
Maximum of Months | 0.207517E+11 | 1.07 | 12271.38 | 1.71 |
Report: FanReportMonthly
For: VAV_BOT WITH REHEAT FAN
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.603397E+10 | 0.41 | 16475.88 | 07-JAN-06:01 | 1.60 |
February | 0.584346E+10 | 0.43 | 16475.88 | 02-FEB-06:02 | 1.59 |
March | 0.881456E+10 | 0.51 | 20069.17 | 15-MAR-16:00 | 1.81 |
April | 0.922031E+10 | 0.51 | 18723.43 | 07-APR-15:00 | 1.73 |
May | 0.100556E+11 | 0.54 | 16291.90 | 16-MAY-14:00 | 1.57 |
June | 0.163403E+11 | 0.75 | 26975.44 | 14-JUN-04:11 | 2.17 |
July | 0.165309E+11 | 0.75 | 26975.44 | 18-JUL-14:20 | 2.16 |
August | 0.184645E+11 | 0.84 | 26975.44 | 02-AUG-15:20 | 2.16 |
September | 0.117665E+11 | 0.60 | 25985.13 | 13-SEP-04:12 | 2.11 |
October | 0.825951E+10 | 0.48 | 20400.80 | 10-OCT-16:00 | 1.82 |
November | 0.753746E+10 | 0.47 | 17329.15 | 07-NOV-16:10 | 1.65 |
December | 0.674541E+10 | 0.44 | 16777.53 | 04-DEC-15:30 | 1.61 |
Annual Sum or Average | 0.125613E+12 | 0.56 | |||
Minimum of Months | 0.584346E+10 | 0.41 | 16291.90 | 1.57 | |
Maximum of Months | 0.184645E+11 | 0.84 | 26975.44 | 2.17 |
Report: FanReportMonthly
For: VAV_MID WITH REHEAT FAN
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.448800E+11 | 0.38 | 131136.88 | 26-JAN-06:02 | 1.44 |
February | 0.428494E+11 | 0.42 | 129269.30 | 28-FEB-06:02 | 1.43 |
March | 0.574056E+11 | 0.45 | 125435.13 | 10-MAR-16:10 | 1.40 |
April | 0.504300E+11 | 0.40 | 121391.44 | 07-APR-15:30 | 1.37 |
May | 0.765697E+11 | 0.48 | 152448.00 | 18-MAY-14:30 | 1.57 |
June | 0.131195E+12 | 0.67 | 252932.64 | 26-JUN-14:10 | 2.16 |
July | 0.122710E+12 | 0.62 | 232746.75 | 17-JUL-04:12 | 2.06 |
August | 0.126216E+12 | 0.64 | 215517.20 | 10-AUG-15:00 | 1.95 |
September | 0.932392E+11 | 0.54 | 201281.90 | 11-SEP-05:02 | 1.88 |
October | 0.566696E+11 | 0.42 | 129471.53 | 17-OCT-05:02 | 1.43 |
November | 0.467784E+11 | 0.40 | 128564.53 | 16-NOV-06:02 | 1.42 |
December | 0.443212E+11 | 0.41 | 72365.11 | 15-DEC-15:50 | 1.01 |
Annual Sum or Average | 0.893264E+12 | 0.49 | |||
Minimum of Months | 0.428494E+11 | 0.38 | 72365.11 | 1.01 | |
Maximum of Months | 0.131195E+12 | 0.67 | 252932.64 | 2.16 |
Report: FanReportMonthly
For: VAV_TOP WITH REHEAT FAN
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.462581E+10 | 0.43 | 8257.63 | 20-JAN-16:30 | 1.03 |
February | 0.428185E+10 | 0.43 | 6844.24 | 17-FEB-16:20 | 0.92 |
March | 0.542617E+10 | 0.45 | 13682.56 | 15-MAR-16:00 | 1.39 |
April | 0.512033E+10 | 0.43 | 13054.83 | 07-APR-15:30 | 1.35 |
May | 0.678138E+10 | 0.44 | 16276.92 | 31-MAY-15:40 | 1.52 |
June | 0.134165E+11 | 0.64 | 28160.71 | 26-JUN-13:50 | 2.16 |
July | 0.121997E+11 | 0.59 | 28160.71 | 18-JUL-14:30 | 2.16 |
August | 0.125217E+11 | 0.60 | 25040.89 | 11-AUG-15:00 | 2.01 |
September | 0.857023E+10 | 0.50 | 21410.71 | 12-SEP-15:50 | 1.81 |
October | 0.503316E+10 | 0.41 | 12716.76 | 10-OCT-16:00 | 1.33 |
November | 0.428117E+10 | 0.39 | 8726.07 | 07-NOV-16:10 | 1.06 |
December | 0.466770E+10 | 0.44 | 6279.32 | 07-DEC-06:01 | 0.88 |
Annual Sum or Average | 0.869257E+11 | 0.48 | |||
Minimum of Months | 0.428117E+10 | 0.39 | 6279.32 | 0.88 | |
Maximum of Months | 0.134165E+11 | 0.64 | 28160.71 | 2.16 |
Report: FanReportMonthly
For: AIRLOOP DATACENTER BASEMENT SUPPLY FAN
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.116192E+12 | 1.65 | 43381.25 | 01-JAN-00:05 | 1.65 |
February | 0.104948E+12 | 1.65 | 43381.25 | 01-FEB-00:10 | 1.65 |
March | 0.116192E+12 | 1.66 | 43381.25 | 01-MAR-00:10 | 1.65 |
April | 0.112444E+12 | 1.66 | 43381.25 | 01-APR-00:10 | 1.66 |
May | 0.116192E+12 | 1.65 | 43381.25 | 01-MAY-00:10 | 1.65 |
June | 0.112444E+12 | 1.65 | 43381.25 | 01-JUN-00:10 | 1.65 |
July | 0.116192E+12 | 1.65 | 43381.25 | 01-JUL-00:03 | 1.66 |
August | 0.116192E+12 | 1.65 | 43381.25 | 01-AUG-00:10 | 1.64 |
September | 0.112444E+12 | 1.65 | 43381.25 | 01-SEP-00:05 | 1.65 |
October | 0.116192E+12 | 1.66 | 43381.25 | 01-OCT-00:10 | 1.65 |
November | 0.112444E+12 | 1.66 | 43381.25 | 01-NOV-00:05 | 1.66 |
December | 0.116192E+12 | 1.66 | 43381.25 | 01-DEC-00:10 | 1.66 |
Annual Sum or Average | 0.136807E+13 | 1.65 | |||
Minimum of Months | 0.104948E+12 | 1.65 | 43381.25 | 1.64 | |
Maximum of Months | 0.116192E+12 | 1.66 | 43381.25 | 1.66 |
Report: FanReportMonthly
For: AIRLOOP DATACENTER BOT SUPPLY FAN
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.186811E+10 | 1.13 | 697.47 | 01-JAN-00:05 | 1.13 |
February | 0.168732E+10 | 1.13 | 697.47 | 01-FEB-00:10 | 1.13 |
March | 0.186811E+10 | 1.13 | 697.47 | 01-MAR-00:10 | 1.13 |
April | 0.180784E+10 | 1.13 | 697.47 | 01-APR-00:10 | 1.13 |
May | 0.186811E+10 | 1.13 | 697.47 | 01-MAY-00:10 | 1.13 |
June | 0.180784E+10 | 1.13 | 697.47 | 01-JUN-00:10 | 1.13 |
July | 0.186811E+10 | 1.13 | 697.47 | 01-JUL-00:03 | 1.13 |
August | 0.186811E+10 | 1.13 | 697.47 | 01-AUG-00:10 | 1.13 |
September | 0.180784E+10 | 1.13 | 697.47 | 01-SEP-00:05 | 1.13 |
October | 0.186811E+10 | 1.13 | 697.47 | 01-OCT-00:10 | 1.13 |
November | 0.180784E+10 | 1.13 | 697.47 | 01-NOV-00:05 | 1.13 |
December | 0.186811E+10 | 1.13 | 697.47 | 01-DEC-00:10 | 1.13 |
Annual Sum or Average | 0.219954E+11 | 1.13 | |||
Minimum of Months | 0.168732E+10 | 1.13 | 697.47 | 1.13 | |
Maximum of Months | 0.186811E+10 | 1.13 | 697.47 | 1.13 |
Report: FanReportMonthly
For: AIRLOOP DATACENTER MID SUPPLY FAN
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.179492E+11 | 1.13 | 6701.45 | 01-JAN-00:05 | 1.13 |
February | 0.162121E+11 | 1.13 | 6701.45 | 01-FEB-00:10 | 1.13 |
March | 0.179492E+11 | 1.13 | 6701.45 | 01-MAR-00:10 | 1.13 |
April | 0.173702E+11 | 1.13 | 6701.45 | 01-APR-00:20 | 1.13 |
May | 0.179492E+11 | 1.13 | 6701.45 | 01-MAY-00:20 | 1.13 |
June | 0.173702E+11 | 1.13 | 6701.45 | 01-JUN-00:10 | 1.13 |
July | 0.179492E+11 | 1.13 | 6701.45 | 01-JUL-00:03 | 1.13 |
August | 0.179492E+11 | 1.13 | 6701.45 | 01-AUG-00:10 | 1.13 |
September | 0.173702E+11 | 1.13 | 6701.45 | 01-SEP-00:10 | 1.13 |
October | 0.179492E+11 | 1.13 | 6701.45 | 01-OCT-00:10 | 1.13 |
November | 0.173702E+11 | 1.13 | 6701.45 | 01-NOV-00:10 | 1.13 |
December | 0.179492E+11 | 1.13 | 6701.45 | 01-DEC-00:10 | 1.13 |
Annual Sum or Average | 0.211337E+12 | 1.13 | |||
Minimum of Months | 0.162121E+11 | 1.13 | 6701.45 | 1.13 | |
Maximum of Months | 0.179492E+11 | 1.13 | 6701.45 | 1.13 |
Report: FanReportMonthly
For: AIRLOOP DATACENTER TOP SUPPLY FAN
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.182869E+10 | 1.13 | 682.76 | 01-JAN-00:05 | 1.13 |
February | 0.165172E+10 | 1.13 | 682.76 | 01-FEB-00:10 | 1.13 |
March | 0.182869E+10 | 1.13 | 682.76 | 01-MAR-00:10 | 1.13 |
April | 0.176970E+10 | 1.13 | 682.76 | 01-APR-00:10 | 1.13 |
May | 0.182869E+10 | 1.13 | 682.76 | 01-MAY-00:10 | 1.13 |
June | 0.176970E+10 | 1.13 | 682.76 | 01-JUN-00:10 | 1.13 |
July | 0.182869E+10 | 1.13 | 682.76 | 01-JUL-00:03 | 1.13 |
August | 0.182869E+10 | 1.13 | 682.76 | 01-AUG-00:10 | 1.13 |
September | 0.176970E+10 | 1.13 | 682.76 | 01-SEP-00:05 | 1.13 |
October | 0.182869E+10 | 1.13 | 682.76 | 01-OCT-00:10 | 1.13 |
November | 0.176970E+10 | 1.13 | 682.76 | 01-NOV-00:05 | 1.13 |
December | 0.182869E+10 | 1.13 | 682.76 | 01-DEC-00:10 | 1.13 |
Annual Sum or Average | 0.215314E+11 | 1.13 | |||
Minimum of Months | 0.165172E+10 | 1.13 | 682.76 | 1.13 | |
Maximum of Months | 0.182869E+10 | 1.13 | 682.76 | 1.13 |
Report: PumpReportMonthly
For: HEATSYS1 PUMP
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.965984E+09 | 0.869385E+09 | 4543.21 | 06-JAN-06:01 | 4088.89 | 4088.89 | 44.21 | 7.52 |
February | 0.107368E+10 | 0.966311E+09 | 5353.44 | 06-FEB-06:02 | 4818.09 | 4818.09 | 48.76 | 11.49 |
March | 0.650394E+09 | 0.585354E+09 | 5341.50 | 20-MAR-05:01 | 4807.35 | 4807.35 | 46.44 | 11.41 |
April | 0.382811E+09 | 0.344530E+09 | 4521.38 | 03-APR-05:01 | 4069.24 | 4069.24 | 45.09 | 7.44 |
May | 25864812.61 | 23278331.35 | 4368.85 | 01-MAY-04:11 | 3931.97 | 3931.97 | 25.37 | 7.01 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 22.12 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 22.12 | 0.00 |
August | 7728.50 | 6955.65 | 9.25 | 23-AUG-05:10 | 8.32 | 8.32 | 22.12 | 0.01 |
September | 16135307.06 | 14521776.35 | 4182.76 | 22-SEP-05:02 | 3764.48 | 3764.48 | 34.18 | 6.46 |
October | 0.484433E+09 | 0.435990E+09 | 4550.29 | 30-OCT-05:01 | 4095.26 | 4095.26 | 46.52 | 7.53 |
November | 0.746868E+09 | 0.672181E+09 | 4546.91 | 01-NOV-05:01 | 4092.22 | 4092.22 | 45.40 | 7.52 |
December | 0.171227E+10 | 0.154105E+10 | 5336.93 | 11-DEC-06:02 | 4803.24 | 4803.24 | 47.81 | 11.37 |
Annual Sum or Average | 0.605845E+10 | 0.545260E+10 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.12 | 0.00 | |
Maximum of Months | 0.171227E+10 | 0.154105E+10 | 5353.44 | 4818.09 | 4818.09 | 48.76 | 11.49 |
Report: PumpReportMonthly
For: COOLSYS1 PUMP SECONDARY
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 16251184.88 | 14626066.39 | 509.32 | 20-JAN-14:10 | 458.39 | 458.39 | 6.70 | 22.10 |
February | 3923735.48 | 3531361.93 | 193.93 | 18-FEB-13:55 | 174.53 | 174.53 | 6.70 | 13.55 |
March | 69971036.85 | 62973933.17 | 2662.16 | 14-MAR-13:40 | 2395.95 | 2395.95 | 7.35 | 47.03 |
April | 27576707.80 | 24819037.02 | 461.26 | 19-APR-13:30 | 415.14 | 415.14 | 6.70 | 21.05 |
May | 0.259647E+09 | 0.233683E+09 | 6065.74 | 31-MAY-12:50 | 5459.17 | 5459.17 | 6.72 | 66.53 |
June | 0.171731E+10 | 0.154558E+10 | 15183.10 | 26-JUN-14:10 | 13664.79 | 13664.79 | 6.73 | 96.19 |
July | 0.154598E+10 | 0.139138E+10 | 14720.63 | 18-JUL-15:10 | 13248.57 | 13248.57 | 6.73 | 95.02 |
August | 0.183470E+10 | 0.165123E+10 | 13911.70 | 31-AUG-10:40 | 12520.53 | 12520.53 | 6.73 | 92.93 |
September | 0.886742E+09 | 0.798068E+09 | 15495.44 | 12-SEP-15:20 | 13945.89 | 13945.89 | 6.73 | 96.96 |
October | 0.121304E+09 | 0.109173E+09 | 2621.30 | 11-OCT-11:00 | 2359.17 | 2359.17 | 7.29 | 46.72 |
November | 33442896.58 | 30098606.92 | 1109.71 | 07-NOV-15:00 | 998.74 | 998.74 | 6.71 | 31.89 |
December | 14325650.69 | 12893085.62 | 498.66 | 01-DEC-14:10 | 448.79 | 448.79 | 6.70 | 21.87 |
Annual Sum or Average | 0.653117E+10 | 0.587806E+10 | ||||||
Minimum of Months | 3923735.48 | 3531361.93 | 193.93 | 174.53 | 174.53 | 6.70 | 13.55 | |
Maximum of Months | 0.183470E+10 | 0.165123E+10 | 15495.44 | 13945.89 | 13945.89 | 7.35 | 96.96 |
Report: PumpReportMonthly
For: COOLSYS1 CHILLER1 PUMP
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.176254E+10 | 0.158629E+10 | 5578.94 | 09-JAN-11:00 | 5021.04 | 5021.04 | 6.72 | 49.35 |
February | 0.221016E+10 | 0.198914E+10 | 5578.94 | 01-FEB-05:01 | 5021.04 | 5021.04 | 6.72 | 49.35 |
March | 0.300543E+10 | 0.270489E+10 | 5578.94 | 01-MAR-05:01 | 5021.04 | 5021.04 | 6.72 | 49.35 |
April | 0.300786E+10 | 0.270707E+10 | 5578.94 | 03-APR-03:01 | 5021.04 | 5021.04 | 6.75 | 49.35 |
May | 0.562407E+10 | 0.506166E+10 | 5578.94 | 01-MAY-04:11 | 5021.04 | 5021.04 | 6.72 | 49.35 |
June | 0.992632E+10 | 0.893369E+10 | 5578.94 | 01-JUN-04:12 | 5021.04 | 5021.04 | 7.51 | 49.35 |
July | 0.110422E+11 | 0.993800E+10 | 5578.94 | 01-JUL-00:03 | 5021.04 | 5021.04 | 6.84 | 49.35 |
August | 0.115793E+11 | 0.104214E+11 | 5578.94 | 01-AUG-00:42 | 5021.04 | 5021.04 | 7.49 | 49.35 |
September | 0.805266E+10 | 0.724740E+10 | 5578.94 | 01-SEP-00:12 | 5021.04 | 5021.04 | 6.82 | 49.35 |
October | 0.360536E+10 | 0.324483E+10 | 5578.94 | 01-OCT-07:22 | 5021.04 | 5021.04 | 6.76 | 49.35 |
November | 0.222796E+10 | 0.200516E+10 | 5578.94 | 02-NOV-03:01 | 5021.04 | 5021.04 | 6.72 | 49.35 |
December | 0.194046E+10 | 0.174641E+10 | 5578.94 | 01-DEC-05:11 | 5021.04 | 5021.04 | 6.78 | 49.35 |
Annual Sum or Average | 0.639843E+11 | 0.575859E+11 | ||||||
Minimum of Months | 0.176254E+10 | 0.158629E+10 | 5578.94 | 5021.04 | 5021.04 | 6.72 | 49.35 | |
Maximum of Months | 0.115793E+11 | 0.104214E+11 | 5578.94 | 5021.04 | 5021.04 | 7.51 | 49.35 |
Report: PumpReportMonthly
For: COOLSYS1 CHILLER2 PUMP
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 6.70 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 6.72 | 0.00 |
March | 90378782.22 | 81340903.99 | 5578.94 | 13-MAR-14:10 | 5021.04 | 5021.04 | 12.41 | 24.67 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 6.76 | 0.00 |
May | 0.565704E+09 | 0.509134E+09 | 5578.94 | 04-MAY-13:50 | 5021.04 | 5021.04 | 12.03 | 24.67 |
June | 0.338493E+10 | 0.304643E+10 | 5578.94 | 01-JUN-10:40 | 5021.04 | 5021.04 | 12.80 | 24.67 |
July | 0.328711E+10 | 0.295840E+10 | 5578.94 | 01-JUL-14:40 | 5021.04 | 5021.04 | 11.91 | 24.67 |
August | 0.320733E+10 | 0.288660E+10 | 5578.94 | 02-AUG-09:50 | 5021.04 | 5021.04 | 11.89 | 24.67 |
September | 0.188791E+10 | 0.169912E+10 | 5578.94 | 01-SEP-12:20 | 5021.04 | 5021.04 | 13.06 | 24.67 |
October | 0.187452E+09 | 0.168707E+09 | 5578.94 | 10-OCT-12:20 | 5021.04 | 5021.04 | 12.34 | 24.67 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 6.72 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 6.72 | 0.00 |
Annual Sum or Average | 0.126108E+11 | 0.113497E+11 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.70 | 0.00 | |
Maximum of Months | 0.338493E+10 | 0.304643E+10 | 5578.94 | 5021.04 | 5021.04 | 13.06 | 24.67 |
Report: PumpReportMonthly
For: PLANT CIRC PUMP
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.101433E+11 | 0.912896E+10 | 3787.07 | 01-JAN-00:05 | 3408.36 | 3408.36 | 18.62 | 15.82 |
February | 0.916168E+10 | 0.824551E+10 | 3787.07 | 01-FEB-00:10 | 3408.36 | 3408.36 | 19.29 | 15.82 |
March | 0.101433E+11 | 0.912896E+10 | 3787.07 | 01-MAR-00:10 | 3408.36 | 3408.36 | 19.86 | 15.82 |
April | 0.981608E+10 | 0.883447E+10 | 3787.07 | 01-APR-00:10 | 3408.36 | 3408.36 | 20.54 | 15.82 |
May | 0.101433E+11 | 0.912896E+10 | 3787.07 | 01-MAY-00:10 | 3408.36 | 3408.36 | 18.75 | 15.82 |
June | 0.981608E+10 | 0.883447E+10 | 3787.07 | 01-JUN-00:10 | 3408.36 | 3408.36 | 19.49 | 15.82 |
July | 0.101433E+11 | 0.912896E+10 | 3787.07 | 01-JUL-00:03 | 3408.36 | 3408.36 | 33.00 | 15.82 |
August | 0.101433E+11 | 0.912896E+10 | 3787.07 | 01-AUG-00:10 | 3408.36 | 3408.36 | 37.26 | 15.82 |
September | 0.981608E+10 | 0.883447E+10 | 3787.07 | 01-SEP-00:05 | 3408.36 | 3408.36 | 19.66 | 15.82 |
October | 0.101433E+11 | 0.912896E+10 | 3787.07 | 01-OCT-00:10 | 3408.36 | 3408.36 | 19.46 | 15.82 |
November | 0.981608E+10 | 0.883447E+10 | 3787.07 | 01-NOV-00:05 | 3408.36 | 3408.36 | 19.69 | 15.82 |
December | 0.101433E+11 | 0.912896E+10 | 3787.07 | 01-DEC-00:10 | 3408.36 | 3408.36 | 20.27 | 15.82 |
Annual Sum or Average | 0.119429E+12 | 0.107486E+12 | ||||||
Minimum of Months | 0.916168E+10 | 0.824551E+10 | 3787.07 | 3408.36 | 3408.36 | 18.62 | 15.82 | |
Maximum of Months | 0.101433E+11 | 0.912896E+10 | 3787.07 | 3408.36 | 3408.36 | 37.26 | 15.82 |
Report: PumpReportMonthly
For: SWHSYS1 PUMP
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.112905E+09 | 33871561.48 | 56.21 | 01-JAN-06:03 | 16.86 | 16.86 | 55.59 | 0.44 |
February | 0.101979E+09 | 30593668.43 | 56.21 | 01-FEB-06:01 | 16.86 | 16.86 | 56.06 | 0.44 |
March | 0.112905E+09 | 33871561.48 | 56.21 | 01-MAR-06:01 | 16.86 | 16.86 | 55.66 | 0.44 |
April | 0.109263E+09 | 32778930.46 | 56.21 | 01-APR-05:03 | 16.86 | 16.86 | 56.10 | 0.44 |
May | 0.112905E+09 | 33871561.48 | 56.21 | 01-MAY-05:03 | 16.86 | 16.86 | 56.18 | 0.44 |
June | 0.109263E+09 | 32778930.46 | 56.21 | 01-JUN-05:02 | 16.86 | 16.86 | 55.74 | 0.44 |
July | 0.112905E+09 | 33871561.48 | 56.21 | 01-JUL-05:03 | 16.86 | 16.86 | 55.75 | 0.44 |
August | 0.112905E+09 | 33871561.48 | 56.21 | 01-AUG-05:02 | 16.86 | 16.86 | 56.28 | 0.44 |
September | 0.109263E+09 | 32778930.46 | 56.21 | 01-SEP-05:03 | 16.86 | 16.86 | 55.83 | 0.44 |
October | 0.112905E+09 | 33871561.48 | 56.21 | 01-OCT-05:10 | 16.86 | 16.86 | 56.16 | 0.44 |
November | 0.109263E+09 | 32778930.46 | 56.21 | 01-NOV-05:01 | 16.86 | 16.86 | 56.49 | 0.44 |
December | 0.112905E+09 | 33871561.48 | 56.21 | 01-DEC-06:03 | 16.86 | 16.86 | 55.99 | 0.44 |
Annual Sum or Average | 0.132937E+10 | 0.398810E+09 | ||||||
Minimum of Months | 0.101979E+09 | 30593668.43 | 56.21 | 16.86 | 16.86 | 55.59 | 0.44 | |
Maximum of Months | 0.112905E+09 | 33871561.48 | 56.21 | 16.86 | 16.86 | 56.49 | 0.44 |
Report: PumpReportMonthly
For: TOWERWATERSYS PUMP
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.456194E+10 | 0.410575E+10 | 14471.47 | 20-JAN-14:20 | 13024.33 | 13024.33 | 24.60 | 58.50 |
February | 0.571862E+10 | 0.514676E+10 | 14459.02 | 18-FEB-14:00 | 13013.11 | 13013.11 | 23.40 | 58.50 |
March | 0.785933E+10 | 0.707340E+10 | 28965.62 | 13-MAR-14:40 | 26069.06 | 26069.06 | 25.59 | 117.00 |
April | 0.778691E+10 | 0.700822E+10 | 14477.80 | 19-APR-13:30 | 13030.02 | 13030.02 | 25.18 | 58.50 |
May | 0.157169E+11 | 0.141452E+11 | 28971.31 | 17-MAY-12:10 | 26074.18 | 26074.18 | 25.82 | 117.00 |
June | 0.339077E+11 | 0.305169E+11 | 28978.04 | 26-JUN-16:30 | 26080.23 | 26080.23 | 26.10 | 117.00 |
July | 0.364345E+11 | 0.327910E+11 | 28977.88 | 14-JUL-14:40 | 26080.10 | 26080.10 | 26.09 | 117.00 |
August | 0.376623E+11 | 0.338961E+11 | 28977.91 | 11-AUG-11:20 | 26080.12 | 26080.12 | 26.09 | 117.00 |
September | 0.252355E+11 | 0.227120E+11 | 28977.91 | 08-SEP-12:50 | 26080.12 | 26080.12 | 26.09 | 117.00 |
October | 0.976267E+10 | 0.878640E+10 | 28971.50 | 11-OCT-15:00 | 26074.35 | 26074.35 | 25.83 | 117.00 |
November | 0.576762E+10 | 0.519086E+10 | 14486.70 | 07-NOV-15:00 | 13038.03 | 13038.03 | 25.91 | 58.50 |
December | 0.502225E+10 | 0.452002E+10 | 14472.45 | 01-DEC-14:20 | 13025.21 | 13025.21 | 24.69 | 58.50 |
Annual Sum or Average | 0.195436E+12 | 0.175893E+12 | ||||||
Minimum of Months | 0.456194E+10 | 0.410575E+10 | 14459.02 | 13013.11 | 13013.11 | 23.40 | 58.50 | |
Maximum of Months | 0.376623E+11 | 0.338961E+11 | 28978.04 | 26080.23 | 26080.23 | 26.10 | 117.00 |
Report: CondLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 36.98 | 36.98 | 83895.95 | 1396601.25 | 03-JAN-05:01 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 29.90 | 29.90 | 103285.19 | 1843350.51 | 06-FEB-05:01 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 24.09 | 24.09 | 57162.07 | 1696019.32 | 20-MAR-05:01 |
April | 0.00 | 0.00 | 01-APR-00:10 | 23.69 | 23.69 | 34652.74 | 1380853.91 | 05-APR-04:01 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 21.34 | 21.34 | 2312.66 | 1659424.56 | 01-MAY-04:11 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 22.12 | 22.12 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 22.12 | 22.12 | 0.00 | 0.00 | 01-JUL-00:03 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 22.12 | 22.12 | 0.74 | 2361.84 | 23-AUG-05:10 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 22.10 | 22.10 | 1531.68 | 1291715.35 | 22-SEP-05:02 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 22.58 | 22.58 | 42871.63 | 1535099.78 | 23-OCT-04:01 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 35.27 | 35.27 | 67739.65 | 1421092.06 | 24-NOV-05:01 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 29.59 | 29.59 | 145524.71 | 1876877.49 | 27-DEC-06:01 |
Annual Sum or Average | 0.00 | 44642.49 | ||||||
Minimum of Months | 0.00 | 0.00 | 21.34 | 21.34 | 0.00 | 0.00 | ||
Maximum of Months | 0.00 | 0.00 | 36.98 | 36.98 | 145524.71 | 1876877.49 |
Report: CondLoopDemandReportMonthly
For: COOLSYS1_SUPPLY
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 14843.81 | 742842.37 | 20-JAN-14:20 | 10.29 | 6.70 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 6641.31 | 478890.43 | 18-FEB-14:00 | 9.01 | 6.70 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 43358.72 | 1410534.32 | 14-MAR-13:40 | 13.53 | 6.70 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 37746.08 | 873116.90 | 19-APR-13:30 | 10.92 | 6.70 | 0.00 | 0.00 | 01-APR-00:10 |
May | 155328.82 | 1620212.00 | 31-MAY-13:30 | 10.62 | 6.70 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 520175.29 | 1880206.19 | 26-JUN-15:10 | 11.25 | 6.70 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 511266.28 | 1775428.77 | 18-JUL-15:10 | 10.99 | 6.70 | 0.00 | 0.00 | 01-JUL-00:03 |
August | 493738.90 | 1835267.01 | 21-AUG-09:50 | 11.14 | 6.70 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 350924.19 | 1716536.51 | 12-SEP-15:20 | 10.85 | 6.70 | 0.00 | 0.00 | 01-SEP-00:05 |
October | 71588.87 | 1411960.39 | 11-OCT-11:00 | 13.53 | 6.70 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 26957.75 | 1028808.43 | 07-NOV-15:00 | 11.68 | 6.70 | 0.00 | 0.00 | 01-NOV-00:05 |
December | 14863.55 | 762956.55 | 01-DEC-14:20 | 10.39 | 6.70 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 188259.49 | 0.00 | ||||||
Minimum of Months | 6641.31 | 478890.43 | 9.01 | 6.70 | 0.00 | 0.00 | ||
Maximum of Months | 520175.29 | 1880206.19 | 13.53 | 6.70 | 0.00 | 0.00 |
Report: CondLoopDemandReportMonthly
For: COOLSYS1_DEMAND
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 14261.76 | 747789.19 | 20-JAN-14:10 | 14.79 | 6.70 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 5821.56 | 474289.25 | 18-FEB-13:55 | 15.06 | 6.70 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 42180.19 | 1454632.40 | 14-MAR-13:40 | 14.09 | 7.09 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 36729.51 | 871454.81 | 19-APR-13:30 | 16.59 | 6.70 | 0.00 | 0.00 | 01-APR-00:10 |
May | 152992.46 | 1470192.89 | 31-MAY-12:30 | 12.75 | 7.59 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 515907.63 | 1936535.52 | 25-JUN-16:21 | 18.46 | 6.70 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 505597.20 | 1793305.20 | 16-JUL-14:51 | 18.29 | 6.70 | 0.00 | 0.00 | 01-JUL-00:03 |
August | 489531.96 | 2044699.57 | 04-AUG-04:12 | 14.95 | 8.06 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 347258.61 | 2012379.28 | 10-SEP-15:11 | 18.37 | 6.70 | 0.00 | 0.00 | 01-SEP-00:05 |
October | 70281.92 | 1472088.48 | 11-OCT-11:00 | 14.23 | 7.08 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 26206.37 | 1026961.75 | 07-NOV-15:00 | 14.39 | 6.70 | 0.00 | 0.00 | 01-NOV-00:05 |
December | 14221.49 | 766245.41 | 01-DEC-14:10 | 15.07 | 6.70 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 186046.97 | 0.00 | ||||||
Minimum of Months | 5821.56 | 474289.25 | 12.75 | 6.70 | 0.00 | 0.00 | ||
Maximum of Months | 515907.63 | 2044699.57 | 18.46 | 8.06 | 0.00 | 0.00 |
Report: CondLoopDemandReportMonthly
For: SINGLE WATER PLANT LOOP
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 27496.80 | 218075.91 | 20-JAN-14:00 | 22.30 | 21.48 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 56588.18 | 281029.17 | 18-FEB-14:00 | 23.44 | 21.28 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 114810.78 | 1027602.62 | 14-MAR-13:00 | 36.77 | 28.81 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 179380.04 | 1046412.13 | 19-APR-14:00 | 37.10 | 27.70 | 0.00 | 0.00 | 01-APR-00:10 |
May | 111014.07 | 995901.11 | 17-MAY-14:00 | 36.21 | 31.72 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 619804.77 | 1910276.17 | 26-JUN-15:00 | 52.11 | 44.26 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 923963.51 | 2017720.71 | 16-JUL-13:00 | 53.95 | 43.49 | 0.00 | 0.00 | 01-JUL-00:03 |
August | 1081698.67 | 2211558.70 | 16-AUG-16:00 | 57.25 | 44.78 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 280174.87 | 1205401.10 | 10-SEP-13:40 | 39.89 | 35.42 | 0.00 | 0.00 | 01-SEP-00:05 |
October | 95030.29 | 1142484.82 | 11-OCT-14:00 | 38.79 | 31.45 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 105346.72 | 806808.82 | 07-NOV-15:00 | 32.86 | 26.08 | 0.00 | 0.00 | 01-NOV-00:05 |
December | 130448.45 | 1038134.94 | 01-DEC-14:00 | 36.95 | 27.64 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 312723.29 | 0.00 | ||||||
Minimum of Months | 27496.80 | 218075.91 | 22.30 | 21.28 | 0.00 | 0.00 | ||
Maximum of Months | 1081698.67 | 2211558.70 | 57.25 | 44.78 | 0.00 | 0.00 |
Report: CondLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 57.05 | 57.05 | 16398.21 | 55393.69 | 31-JAN-12:40 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 56.30 | 56.30 | 16671.56 | 55534.35 | 13-FEB-12:30 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 56.22 | 56.22 | 17384.39 | 55339.15 | 02-MAR-12:10 |
April | 0.00 | 0.00 | 01-APR-00:10 | 56.76 | 56.76 | 15795.02 | 53635.51 | 03-APR-12:00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 57.09 | 57.09 | 15454.68 | 51217.87 | 01-MAY-11:50 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 56.27 | 56.27 | 14942.11 | 48226.40 | 01-JUN-11:20 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 56.29 | 56.29 | 13298.74 | 45593.17 | 03-JUL-11:50 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 56.76 | 56.76 | 14213.74 | 44358.69 | 31-AUG-11:30 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 56.37 | 56.37 | 13650.77 | 45771.24 | 29-SEP-12:00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 56.54 | 56.54 | 14230.33 | 48472.54 | 31-OCT-11:40 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 56.69 | 56.69 | 15218.69 | 51379.96 | 30-NOV-12:40 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 56.47 | 56.47 | 15475.33 | 53829.57 | 29-DEC-13:00 |
Annual Sum or Average | 0.00 | 15219.51 | ||||||
Minimum of Months | 0.00 | 0.00 | 56.22 | 56.22 | 13298.74 | 44358.69 | ||
Maximum of Months | 0.00 | 0.00 | 57.09 | 57.09 | 17384.39 | 55534.35 |
Report: CondLoopDemandReportMonthly
For: TOWERWATERSYS
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 16406.03 | 855470.98 | 20-JAN-14:20 | 24.60 | 21.10 | 3383.55 | 141611.78 | 31-JAN-16:00 |
February | 5910.05 | 562856.00 | 18-FEB-14:00 | 23.40 | 21.10 | 5988.98 | 154104.58 | 12-FEB-07:21 |
March | 48065.45 | 2193577.62 | 13-MAR-14:40 | 25.59 | 21.10 | 3979.03 | 156956.84 | 28-MAR-04:01 |
April | 42563.36 | 996834.29 | 19-APR-13:30 | 25.18 | 21.10 | 3604.21 | 142538.78 | 15-APR-04:01 |
May | 191285.69 | 2308156.29 | 17-MAY-12:10 | 25.82 | 21.10 | 1840.19 | 135108.76 | 08-MAY-06:20 |
June | 684223.36 | 2443608.63 | 26-JUN-16:30 | 26.10 | 21.31 | 853.54 | 106768.35 | 09-JUN-05:30 |
July | 669345.19 | 2440531.50 | 14-JUL-14:40 | 26.09 | 21.10 | 705.60 | 87770.95 | 01-JUL-23:08 |
August | 644090.83 | 2441056.36 | 11-AUG-11:20 | 26.09 | 21.10 | 1452.63 | 86891.04 | 18-AUG-23:00 |
September | 465540.69 | 2441145.21 | 08-SEP-12:50 | 26.09 | 21.10 | 1115.66 | 125111.82 | 21-SEP-15:50 |
October | 87100.33 | 2312001.05 | 11-OCT-15:00 | 25.83 | 21.10 | 3035.61 | 136982.05 | 24-OCT-05:50 |
November | 29880.05 | 1175624.79 | 07-NOV-15:00 | 25.91 | 21.10 | 3320.72 | 147541.71 | 30-NOV-04:01 |
December | 16378.85 | 878424.69 | 01-DEC-14:20 | 24.69 | 21.10 | 3687.21 | 152326.84 | 23-DEC-02:42 |
Annual Sum or Average | 242971.37 | 2726.34 | ||||||
Minimum of Months | 5910.05 | 562856.00 | 23.40 | 21.10 | 705.60 | 86891.04 | ||
Maximum of Months | 684223.36 | 2443608.63 | 26.10 | 21.31 | 5988.98 | 156956.84 |
Report: ZoneTemperatureOscillationReportMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV_BOT WITH REHEAT
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.850417E+10 | 0.00 | 0.360834E+10 | 0.603397E+10 | 0.00 | 0.00 |
February | 0.835975E+10 | 0.00 | 0.125846E+10 | 0.584346E+10 | 0.00 | 0.00 |
March | 0.351326E+10 | 0.00 | 0.106820E+11 | 0.881456E+10 | 0.00 | 0.00 |
April | 0.141955E+10 | 0.00 | 0.108314E+11 | 0.922031E+10 | 0.00 | 0.00 |
May | 36029346.86 | 0.00 | 0.361822E+11 | 0.100556E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.116996E+12 | 0.163403E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.123968E+12 | 0.165309E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.125278E+12 | 0.184645E+11 | 0.00 | 0.00 |
September | 97421238.46 | 0.00 | 0.776261E+11 | 0.117665E+11 | 0.00 | 0.00 |
October | 0.348672E+10 | 0.00 | 0.169947E+11 | 0.825951E+10 | 0.00 | 0.00 |
November | 0.467695E+10 | 0.00 | 0.679412E+10 | 0.753746E+10 | 0.00 | 0.00 |
December | 0.147840E+11 | 0.00 | 0.399240E+10 | 0.674541E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.448778E+11 | 0.00 | 0.534211E+12 | 0.125613E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.125846E+10 | 0.584346E+10 | 0.00 | 0.00 |
Maximum of Months | 0.147840E+11 | 0.00 | 0.125278E+12 | 0.184645E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV_MID WITH REHEAT
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.182732E+12 | 0.00 | 0.310026E+11 | 0.448800E+11 | 0.00 | 0.00 |
February | 0.206742E+12 | 0.00 | 0.117119E+11 | 0.428494E+11 | 0.00 | 0.00 |
March | 0.126269E+12 | 0.00 | 0.855252E+11 | 0.574056E+11 | 0.00 | 0.00 |
April | 0.716905E+11 | 0.00 | 0.724676E+11 | 0.504300E+11 | 0.00 | 0.00 |
May | 0.436119E+10 | 0.00 | 0.310742E+12 | 0.765697E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.101384E+13 | 0.131195E+12 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.102112E+13 | 0.122710E+12 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.985463E+12 | 0.126216E+12 | 0.00 | 0.00 |
September | 0.298989E+10 | 0.00 | 0.684236E+12 | 0.932392E+11 | 0.00 | 0.00 |
October | 0.928233E+11 | 0.00 | 0.146134E+12 | 0.566696E+11 | 0.00 | 0.00 |
November | 0.145087E+12 | 0.00 | 0.524123E+11 | 0.467784E+11 | 0.00 | 0.00 |
December | 0.323902E+12 | 0.00 | 0.297373E+11 | 0.443212E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.115660E+13 | 0.00 | 0.444439E+13 | 0.893264E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.117119E+11 | 0.428494E+11 | 0.00 | 0.00 |
Maximum of Months | 0.323902E+12 | 0.00 | 0.102112E+13 | 0.131195E+12 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV_TOP WITH REHEAT
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.355340E+11 | 0.00 | 0.256010E+10 | 0.462581E+10 | 0.00 | 0.00 |
February | 0.370450E+11 | 0.00 | 0.105158E+10 | 0.428185E+10 | 0.00 | 0.00 |
March | 0.246955E+11 | 0.00 | 0.807168E+10 | 0.542617E+10 | 0.00 | 0.00 |
April | 0.175318E+11 | 0.00 | 0.747890E+10 | 0.512033E+10 | 0.00 | 0.00 |
May | 0.184762E+10 | 0.00 | 0.320597E+11 | 0.678138E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.112913E+12 | 0.134165E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.111448E+12 | 0.121997E+11 | 0.00 | 0.00 |
August | 2143155.51 | 0.00 | 0.108017E+12 | 0.125217E+11 | 0.00 | 0.00 |
September | 0.915133E+09 | 0.00 | 0.711736E+11 | 0.857023E+10 | 0.00 | 0.00 |
October | 0.194661E+11 | 0.00 | 0.135552E+11 | 0.503316E+10 | 0.00 | 0.00 |
November | 0.274250E+11 | 0.00 | 0.451056E+10 | 0.428117E+10 | 0.00 | 0.00 |
December | 0.546392E+11 | 0.00 | 0.258236E+10 | 0.466770E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.219101E+12 | 0.00 | 0.475421E+12 | 0.869257E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.105158E+10 | 0.428117E+10 | 0.00 | 0.00 |
Maximum of Months | 0.546392E+11 | 0.00 | 0.112913E+12 | 0.134165E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: CAV_BAS
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.119122E+10 | 0.186703E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 87731165.80 | 0.167674E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.401397E+10 | 0.193790E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.448175E+10 | 0.178009E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.204671E+11 | 0.188297E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.650860E+11 | 0.190107E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.660625E+11 | 0.191592E+11 | 0.00 | 0.00 |
August | 108.04 | 0.00 | 0.684522E+11 | 0.207517E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.476710E+11 | 0.195756E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.814880E+10 | 0.197491E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.300102E+10 | 0.185303E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.155603E+10 | 0.182886E+11 | 0.00 | 0.00 |
Annual Sum or Average | 108.04 | 0.00 | 0.290219E+12 | 0.226512E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 87731165.80 | 0.167674E+11 | 0.00 | 0.00 |
Maximum of Months | 108.04 | 0.00 | 0.684522E+11 | 0.207517E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER BASEMENT
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.155573E+11 | 0.295373E+12 | 0.00 | 64.59 |
February | 0.00 | 0.00 | 0.210277E+11 | 0.344390E+12 | 0.00 | 86.57 |
March | 0.00 | 0.00 | 0.558113E+11 | 0.397051E+12 | 0.00 | 98.34 |
April | 0.00 | 0.00 | 0.117290E+12 | 0.391588E+12 | 0.00 | 92.18 |
May | 0.00 | 0.00 | 0.409000E+11 | 0.290287E+12 | 0.00 | 60.02 |
June | 0.00 | 0.00 | 0.402714E+12 | 0.321028E+12 | 0.00 | 36.19 |
July | 0.00 | 0.00 | 0.819272E+12 | 0.440364E+12 | 0.00 | 40.66 |
August | 0.00 | 0.00 | 0.110491E+13 | 0.561687E+12 | 0.00 | 60.41 |
September | 0.00 | 0.00 | 0.121536E+12 | 0.307112E+12 | 0.00 | 59.47 |
October | 0.00 | 0.00 | 0.446232E+11 | 0.372036E+12 | 0.00 | 90.17 |
November | 0.00 | 0.00 | 0.443081E+11 | 0.381023E+12 | 0.00 | 95.04 |
December | 0.00 | 0.00 | 0.580199E+11 | 0.401095E+12 | 0.00 | 99.64 |
Annual Sum or Average | 0.00 | 0.00 | 0.284597E+13 | 0.450303E+13 | 0.00 | 883.27 |
Minimum of Months | 0.00 | 0.00 | 0.155573E+11 | 0.290287E+12 | 0.00 | 36.19 |
Maximum of Months | 0.00 | 0.00 | 0.110491E+13 | 0.561687E+12 | 0.00 | 99.64 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER BOT
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.606577E+10 | 0.317948E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.112781E+11 | 0.402135E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.195120E+11 | 0.578624E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.250751E+11 | 0.668119E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.786462E+10 | 0.357036E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.152020E+11 | 0.546349E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.224232E+11 | 0.733788E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.288913E+11 | 0.876880E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.819480E+10 | 0.370398E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.135745E+11 | 0.467210E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.187852E+11 | 0.552690E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.251318E+11 | 0.683543E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.201998E+12 | 0.655472E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.606577E+10 | 0.317948E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.288913E+11 | 0.876880E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER MID
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.374850E+11 | 0.262623E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.876061E+11 | 0.345871E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.168260E+12 | 0.520881E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.222349E+12 | 0.609764E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.675616E+11 | 0.327000E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.142708E+12 | 0.518000E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.212235E+12 | 0.698224E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.273332E+12 | 0.833922E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.725241E+11 | 0.342978E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.115192E+12 | 0.419748E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.160506E+12 | 0.494908E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.211988E+12 | 0.604121E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.177175E+13 | 0.597804E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.374850E+11 | 0.262623E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.273332E+12 | 0.833922E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER TOP
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.202706E+10 | 0.228310E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.698974E+10 | 0.313405E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.153598E+11 | 0.497192E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.207159E+11 | 0.586800E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.616009E+10 | 0.318523E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.142914E+11 | 0.523130E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.212604E+11 | 0.704222E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.273349E+11 | 0.839618E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.692066E+10 | 0.340033E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.100067E+11 | 0.393761E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.141911E+11 | 0.464180E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.190949E+11 | 0.569544E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.164353E+12 | 0.577872E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.202706E+10 | 0.228310E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.273349E+11 | 0.839618E+10 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV_BOT WITH REHEAT
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.603397E+10 | 0.360834E+10 | 0.850417E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.584346E+10 | 0.125846E+10 | 0.835975E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.881456E+10 | 0.106820E+11 | 0.351326E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.922031E+10 | 0.108314E+11 | 0.141955E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.100556E+11 | 0.361822E+11 | 36029346.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.163403E+11 | 0.116996E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.165309E+11 | 0.123968E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.184645E+11 | 0.125278E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.117665E+11 | 0.776261E+11 | 97421238.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.825951E+10 | 0.169947E+11 | 0.348672E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.753746E+10 | 0.679412E+10 | 0.467695E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.674541E+10 | 0.399240E+10 | 0.147840E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.125613E+12 | 0.534211E+12 | 0.448778E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.584346E+10 | 0.125846E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.184645E+11 | 0.125278E+12 | 0.147840E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV_MID WITH REHEAT
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.448800E+11 | 0.310026E+11 | 0.182732E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.428494E+11 | 0.117119E+11 | 0.206742E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.574056E+11 | 0.855252E+11 | 0.126269E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.504300E+11 | 0.724676E+11 | 0.716905E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.765697E+11 | 0.310742E+12 | 0.436119E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.131195E+12 | 0.101384E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.122710E+12 | 0.102112E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.126216E+12 | 0.985463E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.932392E+11 | 0.684236E+12 | 0.298989E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.566696E+11 | 0.146134E+12 | 0.928233E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.467784E+11 | 0.524123E+11 | 0.145087E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.443212E+11 | 0.297373E+11 | 0.323902E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.893264E+12 | 0.444439E+13 | 0.115660E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.428494E+11 | 0.117119E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.131195E+12 | 0.102112E+13 | 0.323902E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV_TOP WITH REHEAT
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.462581E+10 | 0.256010E+10 | 0.355340E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.428185E+10 | 0.105158E+10 | 0.370450E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.542617E+10 | 0.807168E+10 | 0.246955E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.512033E+10 | 0.747890E+10 | 0.175318E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.678138E+10 | 0.320597E+11 | 0.184762E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.134165E+11 | 0.112913E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.121997E+11 | 0.111448E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.125217E+11 | 0.108017E+12 | 2143155.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.857023E+10 | 0.711736E+11 | 0.915133E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.503316E+10 | 0.135552E+11 | 0.194661E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.428117E+10 | 0.451056E+10 | 0.274250E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.466770E+10 | 0.258236E+10 | 0.546392E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.869257E+11 | 0.475421E+12 | 0.219101E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.428117E+10 | 0.105158E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.134165E+11 | 0.112913E+12 | 0.546392E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: CAV_BAS
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.186703E+11 | 0.119122E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.167674E+11 | 87731165.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.193790E+11 | 0.401397E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.178009E+11 | 0.448175E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.188297E+11 | 0.204671E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.190107E+11 | 0.650860E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.191592E+11 | 0.660625E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.207517E+11 | 0.684522E+11 | 108.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.195756E+11 | 0.476710E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.197491E+11 | 0.814880E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.185303E+11 | 0.300102E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.182886E+11 | 0.155603E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.226512E+12 | 0.290219E+12 | 108.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.167674E+11 | 87731165.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.207517E+11 | 0.684522E+11 | 108.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER BASEMENT
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.116192E+12 | 0.999590E+10 | 0.00 | 0.00 | 0.00 | 0.172841E+12 | 0.00 | 0.00 |
February | 0.104948E+12 | 0.142924E+11 | 0.00 | 0.00 | 0.00 | 0.231664E+12 | 0.00 | 0.00 |
March | 0.116192E+12 | 0.393196E+11 | 0.00 | 0.00 | 0.00 | 0.263182E+12 | 0.00 | 0.00 |
April | 0.112444E+12 | 0.859432E+11 | 0.00 | 0.00 | 0.00 | 0.246687E+12 | 0.00 | 0.00 |
May | 0.116192E+12 | 0.281589E+11 | 0.00 | 0.00 | 0.00 | 0.160630E+12 | 0.00 | 0.00 |
June | 0.112444E+12 | 0.291414E+12 | 0.00 | 0.00 | 0.00 | 0.968480E+11 | 0.00 | 0.00 |
July | 0.116192E+12 | 0.604409E+12 | 0.00 | 0.00 | 0.00 | 0.108819E+12 | 0.00 | 0.00 |
August | 0.116192E+12 | 0.821816E+12 | 0.00 | 0.00 | 0.00 | 0.161673E+12 | 0.00 | 0.00 |
September | 0.112444E+12 | 0.867252E+11 | 0.00 | 0.00 | 0.00 | 0.159141E+12 | 0.00 | 0.00 |
October | 0.116192E+12 | 0.311665E+11 | 0.00 | 0.00 | 0.00 | 0.241301E+12 | 0.00 | 0.00 |
November | 0.112444E+12 | 0.312033E+11 | 0.00 | 0.00 | 0.00 | 0.254329E+12 | 0.00 | 0.00 |
December | 0.116192E+12 | 0.409576E+11 | 0.00 | 0.00 | 0.00 | 0.266640E+12 | 0.00 | 0.00 |
Annual Sum or Average | 0.136807E+13 | 0.208540E+13 | 0.00 | 0.00 | 0.00 | 0.236375E+13 | 0.00 | 0.00 |
Minimum of Months | 0.104948E+12 | 0.999590E+10 | 0.00 | 0.00 | 0.00 | 0.968480E+11 | 0.00 | 0.00 |
Maximum of Months | 0.116192E+12 | 0.821816E+12 | 0.00 | 0.00 | 0.00 | 0.266640E+12 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER BOT
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.186811E+10 | 0.475440E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.168732E+10 | 0.894405E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.186811E+10 | 0.155939E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.180784E+10 | 0.202017E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.186811E+10 | 0.616237E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.180784E+10 | 0.115464E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.186811E+10 | 0.169534E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.186811E+10 | 0.219906E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.180784E+10 | 0.629867E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.186811E+10 | 0.107705E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.180784E+10 | 0.150662E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.186811E+10 | 0.201645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.219954E+11 | 0.158447E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.168732E+10 | 0.475440E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.186811E+10 | 0.219906E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER MID
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.179492E+11 | 0.291718E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.162121E+11 | 0.692312E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.179492E+11 | 0.134121E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.173702E+11 | 0.178743E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.179492E+11 | 0.528108E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.173702E+11 | 0.108279E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.179492E+11 | 0.160362E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.179492E+11 | 0.207889E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.173702E+11 | 0.555964E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.179492E+11 | 0.911660E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.173702E+11 | 0.128385E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.179492E+11 | 0.169525E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.211337E+12 | 0.138528E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.162121E+11 | 0.291718E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.179492E+11 | 0.207889E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER TOP
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.182869E+10 | 0.157265E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.165172E+10 | 0.550741E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.182869E+10 | 0.122165E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.176970E+10 | 0.166176E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.182869E+10 | 0.480355E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.176970E+10 | 0.108298E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.182869E+10 | 0.160469E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.182869E+10 | 0.207674E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.176970E+10 | 0.529004E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.182869E+10 | 0.789778E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.176970E+10 | 0.113190E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.182869E+10 | 0.152282E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.215314E+11 | 0.128097E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.165172E+10 | 0.157265E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.182869E+10 | 0.207674E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV_BOT WITH REHEAT
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.603397E+10 | 0.850417E+10 | 0.360834E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.584346E+10 | 0.835975E+10 | 0.125846E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.881456E+10 | 0.351326E+10 | 0.106820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.922031E+10 | 0.141955E+10 | 0.108314E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.100556E+11 | 36029346.86 | 0.361822E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.163403E+11 | 0.00 | 0.116996E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.165309E+11 | 0.00 | 0.123968E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.184645E+11 | 0.00 | 0.125278E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.117665E+11 | 97421238.46 | 0.776261E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.825951E+10 | 0.348672E+10 | 0.169947E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.753746E+10 | 0.467695E+10 | 0.679412E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.674541E+10 | 0.147840E+11 | 0.399240E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.125613E+12 | 0.448778E+11 | 0.534211E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.584346E+10 | 0.00 | 0.125846E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.184645E+11 | 0.147840E+11 | 0.125278E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV_MID WITH REHEAT
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.448800E+11 | 0.182732E+12 | 0.310026E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.428494E+11 | 0.206742E+12 | 0.117119E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.574056E+11 | 0.126269E+12 | 0.855252E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.504300E+11 | 0.716905E+11 | 0.724676E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.765697E+11 | 0.436119E+10 | 0.310742E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.131195E+12 | 0.00 | 0.101384E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.122710E+12 | 0.00 | 0.102112E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.126216E+12 | 0.00 | 0.985463E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.932392E+11 | 0.298989E+10 | 0.684236E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.566696E+11 | 0.928233E+11 | 0.146134E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.467784E+11 | 0.145087E+12 | 0.524123E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.443212E+11 | 0.323902E+12 | 0.297373E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.893264E+12 | 0.115660E+13 | 0.444439E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.428494E+11 | 0.00 | 0.117119E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.131195E+12 | 0.323902E+12 | 0.102112E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV_TOP WITH REHEAT
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.462581E+10 | 0.355340E+11 | 0.256010E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.428185E+10 | 0.370450E+11 | 0.105158E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.542617E+10 | 0.246955E+11 | 0.807168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.512033E+10 | 0.175318E+11 | 0.747890E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.678138E+10 | 0.184762E+10 | 0.320597E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.134165E+11 | 0.00 | 0.112913E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.121997E+11 | 0.00 | 0.111448E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.125217E+11 | 2143155.51 | 0.108017E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.857023E+10 | 0.915133E+09 | 0.711736E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.503316E+10 | 0.194661E+11 | 0.135552E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.428117E+10 | 0.274250E+11 | 0.451056E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.466770E+10 | 0.546392E+11 | 0.258236E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.869257E+11 | 0.219101E+12 | 0.475421E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.428117E+10 | 0.00 | 0.105158E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.134165E+11 | 0.546392E+11 | 0.112913E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: CAV_BAS
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.186703E+11 | 0.00 | 0.119122E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.167674E+11 | 0.00 | 87731165.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.193790E+11 | 0.00 | 0.401397E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.178009E+11 | 0.00 | 0.448175E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.188297E+11 | 0.00 | 0.204671E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.190107E+11 | 0.00 | 0.650860E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.191592E+11 | 0.00 | 0.660625E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.207517E+11 | 108.04 | 0.684522E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.195756E+11 | 0.00 | 0.476710E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.197491E+11 | 0.00 | 0.814880E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.185303E+11 | 0.00 | 0.300102E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.182886E+11 | 0.00 | 0.155603E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.226512E+12 | 108.04 | 0.290219E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.167674E+11 | 0.00 | 87731165.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.207517E+11 | 108.04 | 0.684522E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER BASEMENT
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.116192E+12 | 0.00 | 0.155573E+11 | 0.00 | 0.556140E+10 | 0.00 | 0.00 | 0.00 | 0.173619E+12 | 0.00 | 0.00 | 0.00 |
February | 0.104948E+12 | 0.00 | 0.210277E+11 | 0.00 | 0.673535E+10 | 0.00 | 0.00 | 0.00 | 0.232707E+12 | 0.00 | 0.00 | 0.00 |
March | 0.116192E+12 | 0.00 | 0.558113E+11 | 0.00 | 0.164917E+11 | 0.00 | 0.00 | 0.00 | 0.264367E+12 | 0.00 | 0.00 | 0.00 |
April | 0.112444E+12 | 0.00 | 0.117290E+12 | 0.00 | 0.313467E+11 | 0.00 | 0.00 | 0.00 | 0.247797E+12 | 0.00 | 0.00 | 0.00 |
May | 0.116192E+12 | 0.00 | 0.409000E+11 | 0.00 | 0.127411E+11 | 0.00 | 0.00 | 0.00 | 0.161353E+12 | 0.00 | 0.00 | 0.00 |
June | 0.112444E+12 | 0.00 | 0.402714E+12 | 0.00 | 0.111300E+12 | 0.00 | 0.00 | 0.00 | 0.972840E+11 | 0.00 | 0.00 | 0.00 |
July | 0.116192E+12 | 0.00 | 0.819272E+12 | 0.00 | 0.214863E+12 | 0.00 | 0.00 | 0.00 | 0.109309E+12 | 0.00 | 0.00 | 0.00 |
August | 0.116192E+12 | 0.00 | 0.110491E+13 | 0.00 | 0.283094E+12 | 0.00 | 0.00 | 0.00 | 0.162401E+12 | 0.00 | 0.00 | 0.00 |
September | 0.112444E+12 | 0.00 | 0.121536E+12 | 0.00 | 0.348103E+11 | 0.00 | 0.00 | 0.00 | 0.159857E+12 | 0.00 | 0.00 | 0.00 |
October | 0.116192E+12 | 0.00 | 0.446232E+11 | 0.00 | 0.134567E+11 | 0.00 | 0.00 | 0.00 | 0.242387E+12 | 0.00 | 0.00 | 0.00 |
November | 0.112444E+12 | 0.00 | 0.443081E+11 | 0.00 | 0.131048E+11 | 0.00 | 0.00 | 0.00 | 0.255474E+12 | 0.00 | 0.00 | 0.00 |
December | 0.116192E+12 | 0.00 | 0.580199E+11 | 0.00 | 0.170623E+11 | 0.00 | 0.00 | 0.00 | 0.267840E+12 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.136807E+13 | 0.00 | 0.284597E+13 | 0.00 | 0.760567E+12 | 0.00 | 0.00 | 0.00 | 0.237439E+13 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.104948E+12 | 0.00 | 0.155573E+11 | 0.00 | 0.556140E+10 | 0.00 | 0.00 | 0.00 | 0.972840E+11 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.116192E+12 | 0.00 | 0.110491E+13 | 0.00 | 0.283094E+12 | 0.00 | 0.00 | 0.00 | 0.267840E+12 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER BOT
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.186811E+10 | 0.00 | 0.606577E+10 | 0.00 | 0.131137E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.168732E+10 | 0.00 | 0.112781E+11 | 0.00 | 0.233403E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.186811E+10 | 0.00 | 0.195120E+11 | 0.00 | 0.391813E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.180784E+10 | 0.00 | 0.250751E+11 | 0.00 | 0.487335E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.186811E+10 | 0.00 | 0.786462E+10 | 0.00 | 0.170225E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.180784E+10 | 0.00 | 0.152020E+11 | 0.00 | 0.365564E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.186811E+10 | 0.00 | 0.224232E+11 | 0.00 | 0.546977E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.186811E+10 | 0.00 | 0.288913E+11 | 0.00 | 0.690069E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.180784E+10 | 0.00 | 0.819480E+10 | 0.00 | 0.189613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.186811E+10 | 0.00 | 0.135745E+11 | 0.00 | 0.280400E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.180784E+10 | 0.00 | 0.187852E+11 | 0.00 | 0.371906E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.186811E+10 | 0.00 | 0.251318E+11 | 0.00 | 0.496732E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.219954E+11 | 0.00 | 0.201998E+12 | 0.00 | 0.435518E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.168732E+10 | 0.00 | 0.606577E+10 | 0.00 | 0.131137E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.186811E+10 | 0.00 | 0.288913E+11 | 0.00 | 0.690069E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER MID
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.179492E+11 | 0.00 | 0.374850E+11 | 0.00 | 0.831318E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.162121E+11 | 0.00 | 0.876061E+11 | 0.00 | 0.183749E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.179492E+11 | 0.00 | 0.168260E+12 | 0.00 | 0.341389E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.173702E+11 | 0.00 | 0.222349E+12 | 0.00 | 0.436062E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.179492E+11 | 0.00 | 0.675616E+11 | 0.00 | 0.147509E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.173702E+11 | 0.00 | 0.142708E+12 | 0.00 | 0.344299E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.179492E+11 | 0.00 | 0.212235E+12 | 0.00 | 0.518732E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.179492E+11 | 0.00 | 0.273332E+12 | 0.00 | 0.654431E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.173702E+11 | 0.00 | 0.725241E+11 | 0.00 | 0.169277E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.179492E+11 | 0.00 | 0.115192E+12 | 0.00 | 0.240256E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.173702E+11 | 0.00 | 0.160506E+12 | 0.00 | 0.321206E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.179492E+11 | 0.00 | 0.211988E+12 | 0.00 | 0.424629E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.211337E+12 | 0.00 | 0.177175E+13 | 0.00 | 0.386467E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.162121E+11 | 0.00 | 0.374850E+11 | 0.00 | 0.831318E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.179492E+11 | 0.00 | 0.273332E+12 | 0.00 | 0.654431E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER TOP
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.182869E+10 | 0.00 | 0.202706E+10 | 0.00 | 0.454407E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.165172E+10 | 0.00 | 0.698974E+10 | 0.00 | 0.148232E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.182869E+10 | 0.00 | 0.153598E+11 | 0.00 | 0.314323E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.176970E+10 | 0.00 | 0.207159E+11 | 0.00 | 0.409830E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.182869E+10 | 0.00 | 0.616009E+10 | 0.00 | 0.135654E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.176970E+10 | 0.00 | 0.142914E+11 | 0.00 | 0.346160E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.182869E+10 | 0.00 | 0.212604E+11 | 0.00 | 0.521353E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.182869E+10 | 0.00 | 0.273349E+11 | 0.00 | 0.656749E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.176970E+10 | 0.00 | 0.692066E+10 | 0.00 | 0.163062E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.182869E+10 | 0.00 | 0.100067E+11 | 0.00 | 0.210891E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.176970E+10 | 0.00 | 0.141911E+11 | 0.00 | 0.287210E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.182869E+10 | 0.00 | 0.190949E+11 | 0.00 | 0.386675E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.215314E+11 | 0.00 | 0.164353E+12 | 0.00 | 0.362558E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.165172E+10 | 0.00 | 0.202706E+10 | 0.00 | 0.454407E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.182869E+10 | 0.00 | 0.273349E+11 | 0.00 | 0.656749E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.522497E+09 | 0.00 | 0.00 | 0.129447E+09 | 0.00 | 0.00 | 0.753329E+11 | 0.00 | 0.81 |
February | 0.456453E+09 | 0.00 | 0.00 | 0.118288E+09 | 0.00 | 0.00 | 0.679813E+11 | 0.00 | 0.72 |
March | 0.398770E+09 | 0.00 | 0.00 | 0.134622E+09 | 0.00 | 0.00 | 0.788681E+11 | 0.00 | 1.08 |
April | 0.439479E+09 | 0.00 | 0.00 | 0.123710E+09 | 0.00 | 0.00 | 0.729231E+11 | 0.00 | 1.16 |
May | 0.127979E+09 | 14008233.28 | 0.00 | 0.117046E+09 | 243631.82 | 0.00 | 0.628861E+11 | 0.00 | 1.48 |
June | 70685966.40 | 0.166494E+10 | 0.00 | 88754830.17 | 20767790.94 | 0.00 | 0.253827E+11 | 0.00 | 1.19 |
July | 85843862.54 | 0.164992E+10 | 0.00 | 96295955.31 | 62809285.58 | 0.00 | 0.232528E+11 | 0.00 | 1.15 |
August | 0.123581E+09 | 0.165278E+10 | 0.00 | 0.128811E+09 | 19168428.43 | 0.00 | 0.318414E+11 | 0.00 | 1.31 |
September | 0.216947E+09 | 0.325151E+09 | 0.00 | 0.126354E+09 | 20544979.00 | 0.00 | 0.417332E+11 | 0.00 | 1.47 |
October | 0.340167E+09 | 0.00 | 0.00 | 0.148115E+09 | 0.00 | 0.00 | 0.799993E+11 | 0.00 | 1.21 |
November | 0.378194E+09 | 0.00 | 0.00 | 0.148976E+09 | 0.00 | 0.00 | 0.806807E+11 | 0.00 | 0.97 |
December | 0.836977E+09 | 0.00 | 0.00 | 0.136201E+09 | 0.00 | 0.00 | 0.780533E+11 | 0.00 | 0.79 |
Annual Sum or Average | 0.399757E+10 | 0.530680E+10 | 0.00 | 0.149662E+10 | 0.123534E+09 | 0.00 | 0.718935E+12 | 0.00 | 1.11 |
Minimum of Months | 70685966.40 | 0.00 | 0.00 | 88754830.17 | 0.00 | 0.00 | 0.232528E+11 | 0.00 | 0.72 |
Maximum of Months | 0.836977E+09 | 0.166494E+10 | 0.00 | 0.148976E+09 | 62809285.58 | 0.00 | 0.806807E+11 | 0.00 | 1.48 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.339941E+10 | 0.00 | 0.00 | 85153926.63 | 0.00 | 0.00 | 0.491212E+11 | 0.00 | 0.53 |
February | 0.348293E+10 | 0.00 | 0.00 | 81329019.25 | 0.00 | 0.00 | 0.459483E+11 | 0.00 | 0.50 |
March | 0.287210E+10 | 0.00 | 0.00 | 0.109306E+09 | 0.00 | 0.00 | 0.579425E+11 | 0.00 | 0.79 |
April | 0.198628E+10 | 0.00 | 0.00 | 0.102233E+09 | 0.00 | 0.00 | 0.551979E+11 | 0.00 | 0.86 |
May | 0.261080E+10 | 7613789.04 | 0.00 | 95264477.90 | 514665.09 | 0.00 | 0.455413E+11 | 0.00 | 1.03 |
June | 0.267496E+10 | 0.724832E+09 | 0.00 | 83438729.01 | 59255262.09 | 0.00 | 0.181067E+11 | 0.00 | 0.87 |
July | 0.394944E+10 | 0.760696E+09 | 0.00 | 81291772.71 | 0.181918E+09 | 0.00 | 0.150963E+11 | 0.00 | 0.89 |
August | 0.688903E+10 | 0.741664E+09 | 0.00 | 0.110793E+09 | 0.270151E+09 | 0.00 | 0.233689E+11 | 0.00 | 1.07 |
September | 0.178802E+10 | 0.144369E+09 | 0.00 | 95609599.78 | 62327171.29 | 0.00 | 0.276734E+11 | 0.00 | 0.92 |
October | 0.340838E+10 | 0.00 | 0.00 | 0.100184E+09 | 0.00 | 0.00 | 0.528023E+11 | 0.00 | 0.79 |
November | 0.359634E+10 | 0.00 | 0.00 | 0.102712E+09 | 0.00 | 0.00 | 0.550747E+11 | 0.00 | 0.68 |
December | 0.373498E+10 | 0.00 | 0.00 | 97694649.81 | 0.00 | 0.00 | 0.570220E+11 | 0.00 | 0.57 |
Annual Sum or Average | 0.403927E+11 | 0.237917E+10 | 0.00 | 0.114501E+10 | 0.574167E+09 | 0.00 | 0.502895E+12 | 0.00 | 0.79 |
Minimum of Months | 0.178802E+10 | 0.00 | 0.00 | 81291772.71 | 0.00 | 0.00 | 0.150963E+11 | 0.00 | 0.50 |
Maximum of Months | 0.688903E+10 | 0.760696E+09 | 0.00 | 0.110793E+09 | 0.270151E+09 | 0.00 | 0.579425E+11 | 0.00 | 1.07 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.145941E+12 | 0.00 | 0.00 | 0.365786E+09 | 0.00 | 0.00 | 0.243870E+12 | 0.00 | 0.39 |
February | 0.177570E+12 | 0.00 | 0.00 | 0.267650E+09 | 0.00 | 0.455469E+09 | 0.183168E+12 | 0.00 | 0.37 |
March | 0.131325E+12 | 0.00 | 0.00 | 0.478793E+09 | 0.00 | 52253683.87 | 0.282924E+12 | 0.00 | 0.55 |
April | 0.857792E+11 | 0.00 | 0.00 | 0.421757E+09 | 0.00 | 0.00 | 0.269655E+12 | 0.00 | 0.56 |
May | 0.269158E+11 | 0.100573E+09 | 0.00 | 0.696875E+09 | 18356954.40 | 0.00 | 0.340509E+12 | 0.00 | 0.82 |
June | 0.150456E+11 | 0.776431E+10 | 0.00 | 0.641437E+09 | 0.752544E+09 | 0.00 | 0.140470E+12 | 0.00 | 0.69 |
July | 0.116575E+11 | 0.752539E+10 | 0.00 | 0.625109E+09 | 0.153834E+10 | 0.00 | 0.114242E+12 | 0.00 | 0.65 |
August | 0.153689E+11 | 0.751858E+10 | 0.00 | 0.842928E+09 | 0.783649E+09 | 0.00 | 0.173901E+12 | 0.00 | 0.72 |
September | 0.164959E+11 | 0.151674E+10 | 0.00 | 0.734574E+09 | 0.440707E+09 | 0.00 | 0.210742E+12 | 0.00 | 0.74 |
October | 0.805483E+11 | 0.00 | 0.00 | 0.559275E+09 | 0.00 | 0.00 | 0.316642E+12 | 0.00 | 0.58 |
November | 0.122016E+12 | 0.00 | 0.00 | 0.407759E+09 | 0.00 | 0.00 | 0.263668E+12 | 0.00 | 0.46 |
December | 0.214964E+12 | 0.00 | 0.00 | 0.246106E+09 | 0.00 | 0.932708E+09 | 0.180864E+12 | 0.00 | 0.37 |
Annual Sum or Average | 0.104363E+13 | 0.244256E+11 | 0.00 | 0.628805E+10 | 0.353359E+10 | 0.144043E+10 | 0.272065E+13 | 0.00 | 0.58 |
Minimum of Months | 0.116575E+11 | 0.00 | 0.00 | 0.246106E+09 | 0.00 | 0.00 | 0.114242E+12 | 0.00 | 0.37 |
Maximum of Months | 0.214964E+12 | 0.776431E+10 | 0.00 | 0.842928E+09 | 0.153834E+10 | 0.932708E+09 | 0.340509E+12 | 0.00 | 0.82 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.233918E+11 | 0.00 | 0.00 | 9349662.63 | 0.00 | 0.137833E+10 | 0.713660E+10 | 0.00 | 0.34 |
February | 0.212207E+11 | 0.00 | 0.00 | 7613913.41 | 0.00 | 0.149514E+10 | 0.710656E+10 | 0.00 | 0.32 |
March | 0.173503E+11 | 0.00 | 0.00 | 26465909.03 | 0.00 | 0.412816E+09 | 0.177457E+11 | 0.00 | 0.49 |
April | 0.130833E+11 | 0.00 | 0.00 | 27415791.31 | 0.00 | 0.610780E+09 | 0.188716E+11 | 0.00 | 0.53 |
May | 0.631574E+10 | 501116.53 | 0.00 | 52304599.27 | 1312733.46 | 0.113610E+09 | 0.269544E+11 | 0.00 | 0.78 |
June | 0.183194E+10 | 0.572379E+09 | 0.00 | 66662129.02 | 52605256.92 | 0.00 | 0.130994E+11 | 0.00 | 0.73 |
July | 0.130501E+10 | 0.495826E+09 | 0.00 | 65729758.84 | 0.112183E+09 | 0.00 | 0.105479E+11 | 0.00 | 0.66 |
August | 0.173580E+10 | 0.582898E+09 | 0.00 | 84283335.02 | 63399748.53 | 0.00 | 0.156985E+11 | 0.00 | 0.71 |
September | 0.327394E+10 | 0.104347E+09 | 0.00 | 62218651.31 | 38552677.24 | 0.00 | 0.163164E+11 | 0.00 | 0.71 |
October | 0.152120E+11 | 0.00 | 0.00 | 26672834.90 | 0.00 | 0.589613E+09 | 0.164111E+11 | 0.00 | 0.51 |
November | 0.205905E+11 | 0.00 | 0.00 | 12979695.93 | 0.00 | 0.107855E+10 | 0.947196E+10 | 0.00 | 0.39 |
December | 0.249704E+11 | 0.00 | 0.00 | 5214561.89 | 0.00 | 0.237486E+10 | 0.481345E+10 | 0.00 | 0.32 |
Annual Sum or Average | 0.150281E+12 | 0.175595E+10 | 0.00 | 0.446911E+09 | 0.268054E+09 | 0.805369E+10 | 0.164174E+12 | 0.00 | 0.54 |
Minimum of Months | 0.130501E+10 | 0.00 | 0.00 | 5214561.89 | 0.00 | 0.00 | 0.481345E+10 | 0.00 | 0.32 |
Maximum of Months | 0.249704E+11 | 0.582898E+09 | 0.00 | 84283335.02 | 0.112183E+09 | 0.237486E+10 | 0.269544E+11 | 0.00 | 0.78 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.338545E+10 | 0.00 | 0.00 | 816055.30 | 0.00 | 0.414250E+09 | 0.565968E+09 | 0.00 | 0.34 |
February | 0.314001E+10 | 0.00 | 0.00 | 607076.73 | 0.00 | 0.396978E+09 | 0.583508E+09 | 0.00 | 0.33 |
March | 0.268325E+10 | 0.00 | 0.00 | 3758573.20 | 0.00 | 42210689.45 | 0.228782E+10 | 0.00 | 0.55 |
April | 0.172813E+10 | 0.00 | 0.00 | 5489090.64 | 0.00 | 19580533.25 | 0.343517E+10 | 0.00 | 0.69 |
May | 0.918565E+09 | 2027045.20 | 0.00 | 9759709.19 | 65225.34 | 0.00 | 0.455924E+10 | 0.00 | 1.05 |
June | 0.436190E+09 | 0.160028E+09 | 0.00 | 12531072.55 | 7362315.09 | 0.00 | 0.252631E+10 | 0.00 | 1.11 |
July | 0.575051E+09 | 0.176383E+09 | 0.00 | 11978706.67 | 21539150.42 | 0.00 | 0.202518E+10 | 0.00 | 1.09 |
August | 0.997728E+09 | 0.150311E+09 | 0.00 | 15108849.39 | 34237245.67 | 0.00 | 0.274560E+10 | 0.00 | 1.16 |
September | 0.694233E+09 | 32695963.02 | 0.00 | 9879365.72 | 7898944.16 | 0.00 | 0.239507E+10 | 0.00 | 0.88 |
October | 0.227662E+10 | 0.00 | 0.00 | 3992726.31 | 0.00 | 0.164915E+09 | 0.220745E+10 | 0.00 | 0.56 |
November | 0.310790E+10 | 0.00 | 0.00 | 1948749.11 | 0.00 | 0.178991E+09 | 0.120795E+10 | 0.00 | 0.43 |
December | 0.303115E+10 | 0.00 | 0.00 | 773448.72 | 0.00 | 0.909803E+09 | 0.664485E+09 | 0.00 | 0.34 |
Annual Sum or Average | 0.229743E+11 | 0.521444E+09 | 0.00 | 76643423.52 | 71102880.67 | 0.212673E+10 | 0.252038E+11 | 0.00 | 0.71 |
Minimum of Months | 0.436190E+09 | 0.00 | 0.00 | 607076.73 | 0.00 | 0.00 | 0.565968E+09 | 0.00 | 0.33 |
Maximum of Months | 0.338545E+10 | 0.176383E+09 | 0.00 | 15108849.39 | 34237245.67 | 0.909803E+09 | 0.455924E+10 | 0.00 | 1.16 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.395018E+10 | 0.00 | 0.00 | 2623775.05 | 0.00 | 0.486654E+09 | 0.165664E+10 | 0.00 | 0.73 |
February | 0.319979E+10 | 0.00 | 0.00 | 4260353.05 | 0.00 | 0.614877E+09 | 0.241462E+10 | 0.00 | 0.78 |
March | 0.309605E+10 | 0.00 | 0.00 | 9167677.06 | 0.00 | 0.111933E+09 | 0.452104E+10 | 0.00 | 1.23 |
April | 0.235749E+10 | 0.00 | 0.00 | 8347121.84 | 0.00 | 76110001.66 | 0.474541E+10 | 0.00 | 1.35 |
May | 0.128329E+10 | 1492905.83 | 0.00 | 11554118.58 | 85055.77 | 0.00 | 0.555083E+10 | 0.00 | 1.89 |
June | 0.602517E+09 | 0.115497E+09 | 0.00 | 15141553.66 | 9739844.23 | 0.00 | 0.332082E+10 | 0.00 | 2.04 |
July | 0.779778E+09 | 0.135278E+09 | 0.00 | 14181160.58 | 25285342.40 | 0.00 | 0.212737E+10 | 0.00 | 1.78 |
August | 0.145441E+10 | 0.111114E+09 | 0.00 | 17657432.07 | 44646382.00 | 0.00 | 0.368612E+10 | 0.00 | 2.21 |
September | 0.932237E+09 | 27728000.81 | 0.00 | 13564879.94 | 10300457.04 | 0.00 | 0.349548E+10 | 0.00 | 1.79 |
October | 0.284415E+10 | 0.00 | 0.00 | 7614710.65 | 0.00 | 0.301819E+09 | 0.348851E+10 | 0.00 | 1.19 |
November | 0.365242E+10 | 0.00 | 0.00 | 3781702.98 | 0.00 | 0.371303E+09 | 0.210153E+10 | 0.00 | 0.86 |
December | 0.379137E+10 | 0.00 | 0.00 | 1741529.39 | 0.00 | 0.128029E+10 | 0.109692E+10 | 0.00 | 0.69 |
Annual Sum or Average | 0.279437E+11 | 0.391110E+09 | 0.00 | 0.109636E+09 | 90057081.44 | 0.324299E+10 | 0.382053E+11 | 0.00 | 1.38 |
Minimum of Months | 0.602517E+09 | 0.00 | 0.00 | 1741529.39 | 0.00 | 0.00 | 0.109692E+10 | 0.00 | 0.69 |
Maximum of Months | 0.395018E+10 | 0.135278E+09 | 0.00 | 17657432.07 | 44646382.00 | 0.128029E+10 | 0.555083E+10 | 0.00 | 2.21 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.240980E+10 | 0.00 | 0.00 | 26679357.71 | 0.00 | 0.530739E+09 | 0.110411E+11 | 0.00 | 1.27 |
February | 0.211968E+10 | 0.00 | 0.00 | 23021123.04 | 0.00 | 0.650195E+09 | 0.108593E+11 | 0.00 | 1.22 |
March | 0.276756E+10 | 0.00 | 0.00 | 20701370.20 | 0.00 | 0.205597E+09 | 0.970220E+10 | 0.00 | 1.51 |
April | 0.246581E+10 | 0.00 | 0.00 | 11146430.14 | 0.00 | 0.160919E+09 | 0.665204E+10 | 0.00 | 1.27 |
May | 0.172765E+10 | 2879590.64 | 0.00 | 11964432.94 | 93204.26 | 974792.50 | 0.549930E+10 | 0.00 | 1.40 |
June | 0.752282E+09 | 0.175005E+09 | 0.00 | 12826565.24 | 10707394.39 | 0.00 | 0.230632E+10 | 0.00 | 1.20 |
July | 0.879185E+09 | 0.229557E+09 | 0.00 | 12732501.97 | 23946877.86 | 0.00 | 0.192866E+10 | 0.00 | 1.23 |
August | 0.146326E+10 | 0.221549E+09 | 0.00 | 22530975.25 | 48923583.52 | 0.00 | 0.347791E+10 | 0.00 | 1.58 |
September | 0.923394E+09 | 64778734.95 | 0.00 | 22552866.50 | 11287258.85 | 505054.82 | 0.452398E+10 | 0.00 | 1.66 |
October | 0.207066E+10 | 0.00 | 0.00 | 31912853.85 | 0.00 | 0.425343E+09 | 0.103341E+11 | 0.00 | 1.77 |
November | 0.231224E+10 | 0.00 | 0.00 | 32278226.79 | 0.00 | 0.346906E+09 | 0.115712E+11 | 0.00 | 1.50 |
December | 0.249152E+10 | 0.00 | 0.00 | 22501762.49 | 0.00 | 0.100182E+10 | 0.972923E+10 | 0.00 | 1.18 |
Annual Sum or Average | 0.223831E+11 | 0.693770E+09 | 0.00 | 0.250848E+09 | 94958318.89 | 0.332300E+10 | 0.876253E+11 | 0.00 | 1.40 |
Minimum of Months | 0.752282E+09 | 0.00 | 0.00 | 11146430.14 | 0.00 | 0.00 | 0.192866E+10 | 0.00 | 1.18 |
Maximum of Months | 0.276756E+10 | 0.229557E+09 | 0.00 | 32278226.79 | 48923583.52 | 0.100182E+10 | 0.115712E+11 | 0.00 | 1.77 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.492737E+10 | 0.00 | 0.00 | 4249627.56 | 0.00 | 0.213464E+09 | 0.277293E+10 | 0.00 | 1.00 |
February | 0.409434E+10 | 0.00 | 0.00 | 6002805.58 | 0.00 | 71409461.95 | 0.394188E+10 | 0.00 | 1.05 |
March | 0.256515E+10 | 0.00 | 0.00 | 13532708.95 | 0.00 | 242532.53 | 0.725300E+10 | 0.00 | 1.76 |
April | 0.132079E+10 | 0.00 | 0.00 | 13898064.57 | 0.00 | 0.00 | 0.831214E+10 | 0.00 | 1.99 |
May | 0.124071E+10 | 3264491.21 | 0.00 | 13193804.43 | 104549.28 | 0.00 | 0.605812E+10 | 0.00 | 2.16 |
June | 0.533069E+09 | 0.241063E+09 | 0.00 | 16294672.64 | 2999271.14 | 0.00 | 0.284417E+10 | 0.00 | 2.02 |
July | 0.738330E+09 | 0.256952E+09 | 0.00 | 14980066.03 | 17040363.13 | 0.00 | 0.252484E+10 | 0.00 | 2.11 |
August | 0.110928E+10 | 0.275939E+09 | 0.00 | 26639431.94 | 23461050.05 | 0.00 | 0.429174E+10 | 0.00 | 2.61 |
September | 0.942959E+09 | 51101642.48 | 0.00 | 13997054.40 | 7339038.80 | 0.00 | 0.329972E+10 | 0.00 | 1.85 |
October | 0.285823E+10 | 0.00 | 0.00 | 12915771.02 | 0.00 | 3654786.64 | 0.562885E+10 | 0.00 | 1.69 |
November | 0.327972E+10 | 0.00 | 0.00 | 8968425.26 | 0.00 | 4187847.79 | 0.524353E+10 | 0.00 | 1.31 |
December | 0.383853E+10 | 0.00 | 0.00 | 7230177.49 | 0.00 | 0.178524E+09 | 0.458656E+10 | 0.00 | 1.06 |
Annual Sum or Average | 0.274485E+11 | 0.828320E+09 | 0.00 | 0.151903E+09 | 50944272.40 | 0.471482E+09 | 0.567575E+11 | 0.00 | 1.72 |
Minimum of Months | 0.533069E+09 | 0.00 | 0.00 | 4249627.56 | 0.00 | 0.00 | 0.252484E+10 | 0.00 | 1.00 |
Maximum of Months | 0.492737E+10 | 0.275939E+09 | 0.00 | 26639431.94 | 23461050.05 | 0.213464E+09 | 0.831214E+10 | 0.00 | 2.61 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.224457E+11 | 0.00 | 0.00 | 12751.00 | 0.00 | 0.211595E+11 | 0.101068E+09 | 0.00 | 0.33 |
February | 0.198039E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.223233E+11 | 0.00 | 0.00 | 0.34 |
March | 0.248788E+11 | 0.00 | 0.00 | 9626739.28 | 0.00 | 0.127952E+11 | 0.520434E+10 | 0.00 | 0.44 |
April | 0.217446E+11 | 0.00 | 0.00 | 15857066.30 | 0.00 | 0.648214E+10 | 0.920291E+10 | 0.00 | 0.46 |
May | 0.130366E+11 | 25080491.50 | 0.00 | 64691122.80 | 2299869.94 | 0.531726E+09 | 0.272938E+11 | 0.00 | 0.81 |
June | 0.300617E+10 | 0.192929E+10 | 0.00 | 97613974.07 | 92192564.27 | 0.00 | 0.187666E+11 | 0.00 | 0.91 |
July | 0.254854E+10 | 0.205598E+10 | 0.00 | 92305885.02 | 0.187263E+09 | 0.00 | 0.146290E+11 | 0.00 | 0.84 |
August | 0.482064E+10 | 0.171658E+10 | 0.00 | 0.106360E+09 | 98271962.38 | 0.00 | 0.175266E+11 | 0.00 | 0.78 |
September | 0.925032E+10 | 0.376787E+09 | 0.00 | 69200464.13 | 55214418.12 | 0.206156E+09 | 0.141359E+11 | 0.00 | 0.69 |
October | 0.240579E+11 | 0.00 | 0.00 | 11319817.27 | 0.00 | 0.908048E+10 | 0.546408E+10 | 0.00 | 0.44 |
November | 0.233205E+11 | 0.00 | 0.00 | 2956543.31 | 0.00 | 0.165654E+11 | 0.159048E+10 | 0.00 | 0.37 |
December | 0.161094E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.349390E+11 | 0.00 | 0.00 | 0.35 |
Annual Sum or Average | 0.185023E+12 | 0.610371E+10 | 0.00 | 0.469944E+09 | 0.435242E+09 | 0.124083E+12 | 0.113915E+12 | 0.00 | 0.57 |
Minimum of Months | 0.254854E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 |
Maximum of Months | 0.248788E+11 | 0.205598E+10 | 0.00 | 0.106360E+09 | 0.187263E+09 | 0.349390E+11 | 0.272938E+11 | 0.00 | 0.91 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.335085E+11 | 0.00 | 0.00 | 9187898.70 | 0.00 | 0.217292E+11 | 0.681406E+10 | 0.00 | 0.75 |
February | 0.278819E+11 | 0.00 | 0.00 | 21161207.83 | 0.00 | 0.211187E+11 | 0.131571E+11 | 0.00 | 0.79 |
March | 0.278092E+11 | 0.00 | 0.00 | 65997570.80 | 0.00 | 0.135625E+11 | 0.321168E+11 | 0.00 | 1.18 |
April | 0.236465E+11 | 0.00 | 0.00 | 59903580.08 | 0.00 | 0.686590E+10 | 0.343951E+11 | 0.00 | 1.24 |
May | 0.158258E+11 | 21784994.77 | 0.00 | 0.100906E+09 | 3279020.92 | 0.388897E+09 | 0.461367E+11 | 0.00 | 1.78 |
June | 0.452848E+10 | 0.153418E+10 | 0.00 | 0.147619E+09 | 0.128675E+09 | 0.00 | 0.318722E+11 | 0.00 | 2.00 |
July | 0.399849E+10 | 0.186364E+10 | 0.00 | 0.141730E+09 | 0.203673E+09 | 0.00 | 0.198408E+11 | 0.00 | 1.62 |
August | 0.609703E+10 | 0.159679E+10 | 0.00 | 0.174979E+09 | 0.139214E+09 | 0.00 | 0.361980E+11 | 0.00 | 1.94 |
September | 0.112399E+11 | 0.381335E+09 | 0.00 | 0.122053E+09 | 78721508.77 | 0.187135E+09 | 0.295186E+11 | 0.00 | 1.72 |
October | 0.252151E+11 | 0.00 | 0.00 | 53679315.61 | 0.00 | 0.122023E+11 | 0.254057E+11 | 0.00 | 1.13 |
November | 0.327852E+11 | 0.00 | 0.00 | 16507567.77 | 0.00 | 0.173577E+11 | 0.101264E+11 | 0.00 | 0.85 |
December | 0.277315E+11 | 0.00 | 0.00 | 3052574.04 | 0.00 | 0.355088E+11 | 0.259497E+10 | 0.00 | 0.74 |
Annual Sum or Average | 0.240267E+12 | 0.539773E+10 | 0.00 | 0.916778E+09 | 0.553563E+09 | 0.128921E+12 | 0.288177E+12 | 0.00 | 1.31 |
Minimum of Months | 0.399849E+10 | 0.00 | 0.00 | 3052574.04 | 0.00 | 0.00 | 0.259497E+10 | 0.00 | 0.74 |
Maximum of Months | 0.335085E+11 | 0.186364E+10 | 0.00 | 0.174979E+09 | 0.203673E+09 | 0.355088E+11 | 0.461367E+11 | 0.00 | 2.00 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.229475E+11 | 0.00 | 0.00 | 0.294254E+09 | 0.00 | 0.972214E+10 | 0.105335E+12 | 0.00 | 1.28 |
February | 0.178054E+11 | 0.00 | 0.00 | 0.239172E+09 | 0.00 | 0.141212E+11 | 0.101544E+12 | 0.00 | 1.23 |
March | 0.216823E+11 | 0.00 | 0.00 | 0.202974E+09 | 0.00 | 0.127058E+11 | 0.847646E+11 | 0.00 | 1.46 |
April | 0.239608E+11 | 0.00 | 0.00 | 84839148.53 | 0.00 | 0.695879E+10 | 0.486471E+11 | 0.00 | 1.12 |
May | 0.185197E+11 | 40819282.00 | 0.00 | 0.101026E+09 | 3344723.86 | 0.814262E+09 | 0.436854E+11 | 0.00 | 1.25 |
June | 0.768615E+10 | 0.217215E+10 | 0.00 | 0.104655E+09 | 0.136080E+09 | 0.00 | 0.171473E+11 | 0.00 | 1.05 |
July | 0.534338E+10 | 0.276047E+10 | 0.00 | 0.103667E+09 | 0.200885E+09 | 0.00 | 0.147351E+11 | 0.00 | 0.99 |
August | 0.754900E+10 | 0.296083E+10 | 0.00 | 0.189300E+09 | 0.128405E+09 | 0.00 | 0.269300E+11 | 0.00 | 1.24 |
September | 0.957801E+10 | 0.907871E+09 | 0.00 | 0.217313E+09 | 78217904.48 | 0.300695E+09 | 0.394460E+11 | 0.00 | 1.59 |
October | 0.168029E+11 | 0.00 | 0.00 | 0.347299E+09 | 0.00 | 0.106161E+11 | 0.951839E+11 | 0.00 | 1.75 |
November | 0.200330E+11 | 0.00 | 0.00 | 0.347680E+09 | 0.00 | 0.927357E+10 | 0.106239E+12 | 0.00 | 1.47 |
December | 0.225023E+11 | 0.00 | 0.00 | 0.208302E+09 | 0.00 | 0.207414E+11 | 0.799755E+11 | 0.00 | 1.12 |
Annual Sum or Average | 0.194410E+12 | 0.884214E+10 | 0.00 | 0.244048E+10 | 0.546932E+09 | 0.852539E+11 | 0.763633E+12 | 0.00 | 1.30 |
Minimum of Months | 0.534338E+10 | 0.00 | 0.00 | 84839148.53 | 0.00 | 0.00 | 0.147351E+11 | 0.00 | 0.99 |
Maximum of Months | 0.239608E+11 | 0.296083E+10 | 0.00 | 0.347680E+09 | 0.200885E+09 | 0.207414E+11 | 0.106239E+12 | 0.00 | 1.75 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.381583E+11 | 0.00 | 0.00 | 18673266.50 | 0.00 | 0.202239E+11 | 0.116243E+11 | 0.00 | 0.87 |
February | 0.342797E+11 | 0.00 | 0.00 | 21970204.74 | 0.00 | 0.202376E+11 | 0.151700E+11 | 0.00 | 0.89 |
March | 0.375756E+11 | 0.00 | 0.00 | 55971672.67 | 0.00 | 0.140490E+11 | 0.258853E+11 | 0.00 | 1.35 |
April | 0.317568E+11 | 0.00 | 0.00 | 45986021.53 | 0.00 | 0.673952E+10 | 0.270512E+11 | 0.00 | 1.31 |
May | 0.218726E+11 | 39731012.11 | 0.00 | 84948295.91 | 3543832.30 | 0.673643E+09 | 0.352990E+11 | 0.00 | 1.75 |
June | 0.786938E+10 | 0.282759E+10 | 0.00 | 0.101019E+09 | 44973698.72 | 0.00 | 0.152268E+11 | 0.00 | 1.53 |
July | 0.596168E+10 | 0.260340E+10 | 0.00 | 76480686.91 | 0.186414E+09 | 0.00 | 0.126624E+11 | 0.00 | 1.37 |
August | 0.872601E+10 | 0.256059E+10 | 0.00 | 0.132423E+09 | 0.120710E+09 | 0.00 | 0.174662E+11 | 0.00 | 1.46 |
September | 0.147881E+11 | 0.542894E+09 | 0.00 | 93727039.61 | 50992684.01 | 0.321956E+09 | 0.189471E+11 | 0.00 | 1.52 |
October | 0.346152E+11 | 0.00 | 0.00 | 65686885.34 | 0.00 | 0.113556E+11 | 0.233194E+11 | 0.00 | 1.34 |
November | 0.383233E+11 | 0.00 | 0.00 | 24529334.12 | 0.00 | 0.160900E+11 | 0.137009E+11 | 0.00 | 0.99 |
December | 0.337018E+11 | 0.00 | 0.00 | 9997725.55 | 0.00 | 0.334521E+11 | 0.606523E+10 | 0.00 | 0.84 |
Annual Sum or Average | 0.307628E+12 | 0.857420E+10 | 0.00 | 0.731413E+09 | 0.406634E+09 | 0.123143E+12 | 0.222418E+12 | 0.00 | 1.27 |
Minimum of Months | 0.596168E+10 | 0.00 | 0.00 | 9997725.55 | 0.00 | 0.00 | 0.606523E+10 | 0.00 | 0.84 |
Maximum of Months | 0.383233E+11 | 0.282759E+10 | 0.00 | 0.132423E+09 | 0.186414E+09 | 0.334521E+11 | 0.352990E+11 | 0.00 | 1.75 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.153382E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.301393E+10 | 0.00 | 0.00 | 0.37 |
February | 0.148425E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.276274E+10 | 0.00 | 0.00 | 0.36 |
March | 0.212090E+10 | 0.00 | 0.00 | 769890.65 | 0.00 | 0.185097E+10 | 0.434885E+09 | 0.00 | 0.46 |
April | 0.187298E+10 | 0.00 | 0.00 | 1449985.05 | 0.00 | 0.119559E+10 | 0.900590E+09 | 0.00 | 0.49 |
May | 0.149667E+10 | 241445.59 | 0.00 | 5740292.88 | 83676.56 | 0.109919E+09 | 0.245648E+10 | 0.00 | 0.82 |
June | 0.369410E+09 | 0.133888E+09 | 0.00 | 11031638.03 | 7010680.86 | 0.00 | 0.183187E+10 | 0.00 | 0.96 |
July | 0.323861E+09 | 0.127239E+09 | 0.00 | 10337732.39 | 12746418.42 | 0.00 | 0.139007E+10 | 0.00 | 0.86 |
August | 0.610273E+09 | 0.121871E+09 | 0.00 | 11467788.92 | 8555118.20 | 0.00 | 0.162525E+10 | 0.00 | 0.80 |
September | 0.991874E+09 | 24408394.22 | 0.00 | 6812072.02 | 5188329.56 | 65980061.84 | 0.126352E+10 | 0.00 | 0.71 |
October | 0.223925E+10 | 0.00 | 0.00 | 731444.28 | 0.00 | 0.145446E+10 | 0.327956E+09 | 0.00 | 0.48 |
November | 0.163869E+10 | 0.00 | 0.00 | 146512.09 | 0.00 | 0.246439E+10 | 0.110887E+09 | 0.00 | 0.39 |
December | 0.105464E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.431316E+10 | 0.00 | 0.00 | 0.39 |
Annual Sum or Average | 0.157366E+11 | 0.407649E+09 | 0.00 | 48487356.32 | 33584223.61 | 0.172311E+11 | 0.103415E+11 | 0.00 | 0.59 |
Minimum of Months | 0.323861E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.36 |
Maximum of Months | 0.223925E+10 | 0.133888E+09 | 0.00 | 11467788.92 | 12746418.42 | 0.431316E+10 | 0.245648E+10 | 0.00 | 0.96 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.276059E+10 | 0.00 | 0.00 | 390352.84 | 0.00 | 0.237945E+10 | 0.329680E+09 | 0.00 | 0.70 |
February | 0.251192E+10 | 0.00 | 0.00 | 1153996.55 | 0.00 | 0.202281E+10 | 0.750244E+09 | 0.00 | 0.70 |
March | 0.221627E+10 | 0.00 | 0.00 | 5164899.56 | 0.00 | 0.152159E+10 | 0.278638E+10 | 0.00 | 1.10 |
April | 0.183733E+10 | 0.00 | 0.00 | 5095592.53 | 0.00 | 0.108626E+10 | 0.317679E+10 | 0.00 | 1.20 |
May | 0.144214E+10 | 250811.40 | 0.00 | 9300911.46 | 108467.26 | 72359531.05 | 0.435700E+10 | 0.00 | 1.74 |
June | 0.386036E+09 | 0.105672E+09 | 0.00 | 16293256.22 | 8775755.81 | 0.00 | 0.323341E+10 | 0.00 | 2.09 |
July | 0.386734E+09 | 0.116022E+09 | 0.00 | 15575540.44 | 11862906.75 | 0.00 | 0.194161E+10 | 0.00 | 1.66 |
August | 0.572596E+09 | 0.111935E+09 | 0.00 | 18546368.67 | 11089727.93 | 0.00 | 0.357566E+10 | 0.00 | 1.96 |
September | 0.104595E+10 | 24790531.91 | 0.00 | 12226219.44 | 6725466.78 | 51861649.15 | 0.266841E+10 | 0.00 | 1.72 |
October | 0.200187E+10 | 0.00 | 0.00 | 3799010.18 | 0.00 | 0.148902E+10 | 0.204813E+10 | 0.00 | 1.06 |
November | 0.254297E+10 | 0.00 | 0.00 | 1004275.20 | 0.00 | 0.201032E+10 | 0.703420E+09 | 0.00 | 0.78 |
December | 0.219096E+10 | 0.00 | 0.00 | 47843.09 | 0.00 | 0.336756E+10 | 74435849.02 | 0.00 | 0.68 |
Annual Sum or Average | 0.198954E+11 | 0.358670E+09 | 0.00 | 88598266.19 | 38562324.54 | 0.140012E+11 | 0.256452E+11 | 0.00 | 1.29 |
Minimum of Months | 0.386036E+09 | 0.00 | 0.00 | 47843.09 | 0.00 | 0.00 | 74435849.02 | 0.00 | 0.68 |
Maximum of Months | 0.276059E+10 | 0.116022E+09 | 0.00 | 18546368.67 | 11862906.75 | 0.336756E+10 | 0.435700E+10 | 0.00 | 2.09 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.180886E+10 | 0.00 | 0.00 | 21106358.19 | 0.00 | 0.160384E+10 | 0.882070E+10 | 0.00 | 1.18 |
February | 0.160083E+10 | 0.00 | 0.00 | 19134897.67 | 0.00 | 0.150231E+10 | 0.917523E+10 | 0.00 | 1.16 |
March | 0.187792E+10 | 0.00 | 0.00 | 17644618.03 | 0.00 | 0.154156E+10 | 0.826993E+10 | 0.00 | 1.43 |
April | 0.190323E+10 | 0.00 | 0.00 | 7728801.85 | 0.00 | 0.127605E+10 | 0.498197E+10 | 0.00 | 1.11 |
May | 0.192776E+10 | 395928.73 | 0.00 | 9416793.42 | 119274.38 | 0.164594E+09 | 0.426003E+10 | 0.00 | 1.26 |
June | 0.833404E+09 | 0.144951E+09 | 0.00 | 12201914.09 | 10145900.44 | 0.00 | 0.185086E+10 | 0.00 | 1.14 |
July | 0.603751E+09 | 0.165037E+09 | 0.00 | 12342911.76 | 12104858.02 | 0.00 | 0.152361E+10 | 0.00 | 1.06 |
August | 0.850676E+09 | 0.194851E+09 | 0.00 | 21970646.72 | 12194651.22 | 0.00 | 0.275051E+10 | 0.00 | 1.29 |
September | 0.932683E+09 | 55656442.59 | 0.00 | 24488128.76 | 7308306.44 | 62560476.25 | 0.400916E+10 | 0.00 | 1.63 |
October | 0.133568E+10 | 0.00 | 0.00 | 31402228.28 | 0.00 | 0.150257E+10 | 0.921798E+10 | 0.00 | 1.75 |
November | 0.152259E+10 | 0.00 | 0.00 | 26970201.91 | 0.00 | 0.151942E+10 | 0.918034E+10 | 0.00 | 1.38 |
December | 0.183326E+10 | 0.00 | 0.00 | 15312414.71 | 0.00 | 0.240930E+10 | 0.647718E+10 | 0.00 | 1.03 |
Annual Sum or Average | 0.170306E+11 | 0.560891E+09 | 0.00 | 0.219720E+09 | 41872990.51 | 0.115822E+11 | 0.705175E+11 | 0.00 | 1.29 |
Minimum of Months | 0.603751E+09 | 0.00 | 0.00 | 7728801.85 | 0.00 | 0.00 | 0.152361E+10 | 0.00 | 1.03 |
Maximum of Months | 0.192776E+10 | 0.194851E+09 | 0.00 | 31402228.28 | 12194651.22 | 0.240930E+10 | 0.921798E+10 | 0.00 | 1.75 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.292280E+10 | 0.00 | 0.00 | 1442705.24 | 0.00 | 0.257323E+10 | 0.102026E+10 | 0.00 | 0.86 |
February | 0.274301E+10 | 0.00 | 0.00 | 1903449.85 | 0.00 | 0.229721E+10 | 0.138708E+10 | 0.00 | 0.86 |
March | 0.330284E+10 | 0.00 | 0.00 | 5264604.84 | 0.00 | 0.168747E+10 | 0.261219E+10 | 0.00 | 1.35 |
April | 0.277076E+10 | 0.00 | 0.00 | 4460247.92 | 0.00 | 0.103633E+10 | 0.286337E+10 | 0.00 | 1.34 |
May | 0.225587E+10 | 346211.26 | 0.00 | 8086717.54 | 125507.79 | 0.115374E+09 | 0.349950E+10 | 0.00 | 1.80 |
June | 0.814401E+09 | 0.186688E+09 | 0.00 | 12764284.58 | 3584647.75 | 0.00 | 0.161178E+10 | 0.00 | 1.64 |
July | 0.663336E+09 | 0.152912E+09 | 0.00 | 9609053.10 | 14601150.01 | 0.00 | 0.125790E+10 | 0.00 | 1.45 |
August | 0.948073E+09 | 0.171934E+09 | 0.00 | 15534362.77 | 9817363.87 | 0.00 | 0.172832E+10 | 0.00 | 1.51 |
September | 0.144029E+10 | 36584736.40 | 0.00 | 10865573.23 | 3820539.55 | 67219501.65 | 0.187369E+10 | 0.00 | 1.59 |
October | 0.284864E+10 | 0.00 | 0.00 | 6055532.14 | 0.00 | 0.160782E+10 | 0.230057E+10 | 0.00 | 1.37 |
November | 0.286241E+10 | 0.00 | 0.00 | 1986648.19 | 0.00 | 0.223412E+10 | 0.125389E+10 | 0.00 | 0.97 |
December | 0.247188E+10 | 0.00 | 0.00 | 808947.40 | 0.00 | 0.351704E+10 | 0.558435E+09 | 0.00 | 0.81 |
Annual Sum or Average | 0.260443E+11 | 0.548466E+09 | 0.00 | 78782126.80 | 31949208.97 | 0.151358E+11 | 0.219670E+11 | 0.00 | 1.30 |
Minimum of Months | 0.663336E+09 | 0.00 | 0.00 | 808947.40 | 0.00 | 0.00 | 0.558435E+09 | 0.00 | 0.81 |
Maximum of Months | 0.330284E+10 | 0.186688E+09 | 0.00 | 15534362.77 | 14601150.01 | 0.351704E+10 | 0.349950E+10 | 0.00 | 1.80 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 3942011.61 | 0.00 | 0.00 | 0.566411E+09 | 0.00 | 0.28 |
February | 0.00 | 0.00 | 0.00 | 8767424.54 | 0.00 | 0.00 | 0.532493E+09 | 0.00 | 0.29 |
March | 0.00 | 0.00 | 0.00 | 15616055.87 | 0.00 | 0.00 | 0.508659E+09 | 0.00 | 0.31 |
April | 0.00 | 0.00 | 0.00 | 18341410.60 | 0.00 | 0.00 | 0.395107E+09 | 0.00 | 0.29 |
May | 0.00 | 166443.97 | 0.00 | 4127908.94 | 0.00 | 0.00 | 0.262827E+09 | 0.00 | 0.29 |
June | 0.00 | 27884605.49 | 0.00 | 5148953.22 | 0.00 | 0.00 | 46048300.21 | 0.00 | 0.30 |
July | 0.00 | 52020258.58 | 0.00 | 5436891.41 | 0.00 | 0.00 | 29489678.27 | 0.00 | 0.28 |
August | 0.00 | 27254366.10 | 0.00 | 13875748.30 | 0.00 | 0.00 | 54225931.38 | 0.00 | 0.30 |
September | 0.00 | 675471.24 | 0.00 | 4060146.13 | 0.00 | 0.00 | 0.165424E+09 | 0.00 | 0.28 |
October | 0.00 | 0.00 | 0.00 | 9011345.77 | 0.00 | 0.00 | 0.427924E+09 | 0.00 | 0.28 |
November | 0.00 | 0.00 | 0.00 | 14047036.97 | 0.00 | 0.00 | 0.498537E+09 | 0.00 | 0.28 |
December | 0.00 | 0.00 | 0.00 | 19517259.54 | 0.00 | 0.00 | 0.596720E+09 | 0.00 | 0.28 |
Annual Sum or Average | 0.00 | 0.108001E+09 | 0.00 | 0.121892E+09 | 0.00 | 0.00 | 0.408387E+10 | 0.00 | 0.29 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 3942011.61 | 0.00 | 0.00 | 29489678.27 | 0.00 | 0.28 |
Maximum of Months | 0.00 | 52020258.58 | 0.00 | 19517259.54 | 0.00 | 0.00 | 0.596720E+09 | 0.00 | 0.31 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.153861E+09 | 0.00 | 0.00 | 26542129.90 | 0.00 | 0.00 | 0.552560E+10 | 0.00 | 0.28 |
February | 0.00 | 0.00 | 0.00 | 71454567.03 | 0.00 | 0.00 | 0.534077E+10 | 0.00 | 0.29 |
March | 0.00 | 0.00 | 0.00 | 0.137538E+09 | 0.00 | 0.00 | 0.510501E+10 | 0.00 | 0.31 |
April | 0.00 | 0.00 | 0.00 | 0.166113E+09 | 0.00 | 0.00 | 0.396827E+10 | 0.00 | 0.29 |
May | 0.00 | 1522967.47 | 0.00 | 35325412.89 | 0.00 | 0.00 | 0.264126E+10 | 0.00 | 0.29 |
June | 0.00 | 0.275076E+09 | 0.00 | 48632584.78 | 0.00 | 0.00 | 0.464243E+09 | 0.00 | 0.30 |
July | 0.00 | 0.516736E+09 | 0.00 | 51775139.74 | 0.00 | 0.00 | 0.297890E+09 | 0.00 | 0.28 |
August | 0.00 | 0.272556E+09 | 0.00 | 0.130805E+09 | 0.00 | 0.00 | 0.543699E+09 | 0.00 | 0.30 |
September | 0.00 | 6594228.09 | 0.00 | 35568762.91 | 0.00 | 0.00 | 0.166417E+10 | 0.00 | 0.28 |
October | 0.00 | 0.00 | 0.00 | 77621743.63 | 0.00 | 0.00 | 0.429216E+10 | 0.00 | 0.28 |
November | 0.00 | 0.00 | 0.00 | 0.122829E+09 | 0.00 | 0.00 | 0.500227E+10 | 0.00 | 0.28 |
December | 0.00 | 0.00 | 0.00 | 0.170761E+09 | 0.00 | 0.00 | 0.599112E+10 | 0.00 | 0.28 |
Annual Sum or Average | 0.153861E+09 | 0.107249E+10 | 0.00 | 0.107497E+10 | 0.00 | 0.00 | 0.408365E+11 | 0.00 | 0.29 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 26542129.90 | 0.00 | 0.00 | 0.297890E+09 | 0.00 | 0.28 |
Maximum of Months | 0.153861E+09 | 0.516736E+09 | 0.00 | 0.170761E+09 | 0.00 | 0.00 | 0.599112E+10 | 0.00 | 0.31 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.155547E+09 | 0.00 | 0.00 | 1707578.20 | 0.00 | 0.00 | 0.410980E+09 | 0.00 | 0.28 |
February | 0.00 | 0.00 | 0.00 | 6214944.27 | 0.00 | 0.00 | 0.535091E+09 | 0.00 | 0.29 |
March | 0.00 | 0.00 | 0.00 | 12914074.42 | 0.00 | 0.00 | 0.511508E+09 | 0.00 | 0.31 |
April | 0.00 | 0.00 | 0.00 | 15990177.09 | 0.00 | 0.00 | 0.397529E+09 | 0.00 | 0.29 |
May | 6328825.71 | 161998.68 | 0.00 | 3257104.50 | 0.00 | 0.00 | 0.258343E+09 | 0.00 | 0.29 |
June | 0.00 | 27561274.17 | 0.00 | 4870783.00 | 0.00 | 0.00 | 46425101.96 | 0.00 | 0.30 |
July | 0.00 | 51701897.85 | 0.00 | 5178001.22 | 0.00 | 0.00 | 29759370.38 | 0.00 | 0.28 |
August | 0.00 | 27323519.90 | 0.00 | 13029906.48 | 0.00 | 0.00 | 54129835.31 | 0.00 | 0.30 |
September | 2125712.49 | 648473.80 | 0.00 | 3362009.98 | 0.00 | 0.00 | 0.164614E+09 | 0.00 | 0.28 |
October | 0.00 | 0.00 | 0.00 | 6924088.59 | 0.00 | 0.00 | 0.430388E+09 | 0.00 | 0.28 |
November | 0.00 | 0.00 | 0.00 | 11267739.13 | 0.00 | 0.00 | 0.501422E+09 | 0.00 | 0.28 |
December | 0.00 | 0.00 | 0.00 | 15985844.68 | 0.00 | 0.00 | 0.600225E+09 | 0.00 | 0.28 |
Annual Sum or Average | 0.164001E+09 | 0.107397E+09 | 0.00 | 0.100702E+09 | 0.00 | 0.00 | 0.394041E+10 | 0.00 | 0.29 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 1707578.20 | 0.00 | 0.00 | 29759370.38 | 0.00 | 0.28 |
Maximum of Months | 0.155547E+09 | 51701897.85 | 0.00 | 15990177.09 | 0.00 | 0.00 | 0.600225E+09 | 0.00 | 0.31 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.667386E+09 | 0.00 | 0.00 | 0.518726E+12 | 0.00 | 11.11 |
February | 0.00 | 0.00 | 0.00 | 0.130234E+10 | 0.00 | 0.00 | 0.758168E+12 | 0.00 | 17.54 |
March | 0.00 | 0.00 | 0.00 | 0.201815E+10 | 0.00 | 0.00 | 0.106916E+13 | 0.00 | 30.51 |
April | 0.00 | 0.00 | 0.00 | 0.227423E+10 | 0.00 | 0.00 | 0.121565E+13 | 0.00 | 38.50 |
May | 0.00 | 0.00 | 0.00 | 0.547124E+09 | 0.00 | 0.00 | 0.491718E+12 | 0.00 | 23.30 |
June | 0.00 | 0.289946E+10 | 0.00 | 0.113430E+10 | 0.00 | 0.00 | 0.394210E+12 | 0.00 | 34.74 |
July | 0.00 | 0.133733E+11 | 0.00 | 0.183782E+10 | 0.00 | 0.00 | 0.367527E+12 | 0.00 | 37.62 |
August | 0.00 | 0.583390E+10 | 0.00 | 0.325803E+10 | 0.00 | 0.00 | 0.436629E+12 | 0.00 | 50.67 |
September | 0.00 | 0.00 | 0.00 | 0.600788E+09 | 0.00 | 0.00 | 0.424166E+12 | 0.00 | 26.97 |
October | 0.00 | 0.00 | 0.00 | 0.134082E+10 | 0.00 | 0.00 | 0.814955E+12 | 0.00 | 25.55 |
November | 0.00 | 0.00 | 0.00 | 0.200228E+10 | 0.00 | 0.00 | 0.104430E+13 | 0.00 | 27.90 |
December | 0.00 | 0.00 | 0.00 | 0.309860E+10 | 0.00 | 0.00 | 0.131689E+13 | 0.00 | 31.15 |
Annual Sum or Average | 0.00 | 0.221067E+11 | 0.00 | 0.200819E+11 | 0.00 | 0.00 | 0.885209E+13 | 0.00 | 29.70 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.547124E+09 | 0.00 | 0.00 | 0.367527E+12 | 0.00 | 11.11 |
Maximum of Months | 0.00 | 0.133733E+11 | 0.00 | 0.325803E+10 | 0.00 | 0.00 | 0.131689E+13 | 0.00 | 50.67 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 08:43:27
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.439362E+12 | 0.148667E+11 | 0.00 | 0.255116E+13 | 0.197339E+12 |
February | 0.559198E+12 | 0.233467E+11 | 0.00 | 0.252415E+13 | 0.244431E+12 |
March | 0.694075E+12 | 0.253070E+11 | 0.00 | 0.305763E+13 | 0.481861E+12 |
April | 0.748338E+12 | 0.265009E+11 | 0.00 | 0.323094E+13 | 0.579878E+12 |
May | 0.859997E+12 | 0.135408E+11 | 0.00 | 0.252919E+13 | 0.693688E+12 |
June | 0.906002E+12 | 0.608215E+10 | 0.00 | 0.168000E+13 | 0.243638E+13 |
July | 0.854905E+12 | 0.485312E+10 | 0.00 | 0.143806E+13 | 0.296183E+13 |
August | 0.837363E+12 | 0.501569E+10 | 0.00 | 0.155261E+13 | 0.330139E+13 |
September | 0.629084E+12 | 0.869414E+10 | 0.00 | 0.196647E+13 | 0.149925E+13 |
October | 0.549434E+12 | 0.188174E+11 | 0.00 | 0.299292E+13 | 0.496527E+12 |
November | 0.466932E+12 | 0.169136E+11 | 0.00 | 0.311697E+13 | 0.406493E+12 |
December | 0.365993E+12 | 0.312236E+11 | 0.00 | 0.315125E+13 | 0.498629E+12 |
Annual Sum or Average | 0.791068E+13 | 0.195162E+12 | 0.00 | 0.297914E+14 | 0.137977E+14 |
Minimum of Months | 0.365993E+12 | 0.485312E+10 | 0.00 | 0.143806E+13 | 0.197339E+12 |
Maximum of Months | 0.906002E+12 | 0.312236E+11 | 0.00 | 0.323094E+13 | 0.330139E+13 |