Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:43
Tabular Output Report in Format: HTML
Building: OfficeLarge
Environment: RUNPERIOD 1 ** Atlanta-Hartsfield Jackson Intl AP GA USA TMY3 WMO#=722190
Simulation Timestamp: 2023-10-16 08:43:24
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 08:43:24
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 31609.06 | 682.40 | 682.40 |
Net Site Energy | 31609.06 | 682.40 | 682.40 |
Total Source Energy | 96578.89 | 2085.02 | 2085.02 |
Net Source Energy | 96578.89 | 2085.02 | 2085.02 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 46320.38 |
Net Conditioned Building Area | 46320.38 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 958.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 4405.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 3936.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 695.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 14676.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 1934.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 2129.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 597.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 1479.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8800.50 |
Humidification | 8.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 |
Heat Recovery | 52.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 734.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2280.17 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 29915.83 | 1693.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11083.99 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler | 0.00 | 958.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 4405.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 3936.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 695.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 5334.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DataCenterPlugLoads | 9341.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 80.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 1848.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 5.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | General | 2129.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 597.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 1479.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8800.50 |
Humidification | General | 8.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 |
Heat Recovery | General | 52.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2280.17 | |
Water Heater | 0.00 | 734.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 958.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 4405.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 3936.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 695.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 14676.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 1934.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 2129.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 597.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 1479.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8800.50 |
Humidification | Unassigned | 8.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 |
Heat Recovery | Unassigned | 52.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 0.00 | 734.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2280.17 |
Refrigeration | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 100.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 186.10 | 36.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.24 |
Other | 359.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 645.85 | 36.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.24 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 100.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 186.10 | 36.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.24 |
Other | 359.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 645.85 | 36.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.24 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 29915.830 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 29915.830 | 100.00 |
Total On-Site and Utility Electric Sources | 29915.830 | 100.00 |
Total Electricity End Uses | 29915.830 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | 0.00 |
Air to Air Heat Recovery for Cooling | 1507.92 | 68.64 |
Air to Air Heat Recovery for Heating | 689.01 | 31.36 |
High-Temperature Geothermal* | 0.00 | 0.00 |
Solar Water Thermal | 0.00 | 0.00 |
Solar Air Thermal | 0.00 | 0.00 |
Total On-Site Thermal Sources | 2196.93 | 100.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 11083.99 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 11083.99 | 100.00 |
Total Water End Uses | 11083.99 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 32.33 |
Time Setpoint Not Met During Occupied Cooling | 532.33 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 5932.33 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2013
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICELARGE
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 3A
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_GA_ATLANTA
| Environment |ZoneCoolingSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |ZoneHeatingSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |ZoneElectricSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |SpaceGainsMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |PeakSpaceGainsMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |SpaceGainComponentsAtCoolingPeakMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |ComfortReportSimple55Monthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |OccupantComfortDataSummaryMonthly
| DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 | BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 |ChillerReportMonthly
| COOLSYS1 CHILLER1 | COOLSYS1 CHILLER2 |TowerReportMonthly
| CENTRAL TOWER | TOWERWATERSYS COOLTOWER 1 | TOWERWATERSYS COOLTOWER 2 |BoilerReportMonthly
| HEATSYS1 BOILER | CENTRAL BOILER |DXReportMonthly
| VAV_BOT WITH REHEAT COOLING COIL | VAV_MID WITH REHEAT COOLING COIL | VAV_TOP WITH REHEAT COOLING COIL | CAV_BAS COOLING COIL | AIRLOOP DATACENTER BASEMENT COOLING COIL | AIRLOOP DATACENTER BOT COOLING COIL | AIRLOOP DATACENTER MID COOLING COIL | AIRLOOP DATACENTER TOP COOLING COIL |WindowReportMonthly
| PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW |WindowEnergyReportMonthly
| PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW |WindowZoneSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |WindowEnergyZoneSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWHSYS1 WATER HEATER |DaylightingReportMonthly
| PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_4_DAYLCTRL |CoilReportMonthly
| VAV_BOT WITH REHEAT HEATING COIL | CORE_BOTTOM VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | VAV_MID WITH REHEAT HEATING COIL | CORE_MID VAV BOX REHEAT COIL | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | VAV_TOP WITH REHEAT HEATING COIL | CORE_TOP VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | CAV_BAS HEATING COIL | AIRLOOP DATACENTER BASEMENT HEATING COIL | AIRLOOP DATACENTER BOT HEATING COIL | AIRLOOP DATACENTER MID HEATING COIL | AIRLOOP DATACENTER TOP HEATING COIL | AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | AIRLOOP DATACENTER BOT_SUPPHEATCOIL | AIRLOOP DATACENTER MID_SUPPHEATCOIL | AIRLOOP DATACENTER TOP_SUPPHEATCOIL | VAV_BOT WITH REHEAT COOLING COIL | VAV_MID WITH REHEAT COOLING COIL | VAV_TOP WITH REHEAT COOLING COIL | CAV_BAS COOLING COIL | AIRLOOP DATACENTER BASEMENT COOLING COIL | AIRLOOP DATACENTER BOT COOLING COIL | AIRLOOP DATACENTER MID COOLING COIL | AIRLOOP DATACENTER TOP COOLING COIL |PlantLoopDemandReportMonthly
| HEATSYS1 | COOLSYS1_SUPPLY | COOLSYS1_DEMAND | SINGLE WATER PLANT LOOP | SWHSYS1 | TOWERWATERSYS |FanReportMonthly
| CAV_BAS FAN | VAV_BOT WITH REHEAT FAN | VAV_MID WITH REHEAT FAN | VAV_TOP WITH REHEAT FAN | AIRLOOP DATACENTER BASEMENT SUPPLY FAN | AIRLOOP DATACENTER BOT SUPPLY FAN | AIRLOOP DATACENTER MID SUPPLY FAN | AIRLOOP DATACENTER TOP SUPPLY FAN |PumpReportMonthly
| HEATSYS1 PUMP | COOLSYS1 PUMP SECONDARY | COOLSYS1 CHILLER1 PUMP | COOLSYS1 CHILLER2 PUMP | PLANT CIRC PUMP | SWHSYS1 PUMP | TOWERWATERSYS PUMP |CondLoopDemandReportMonthly
| HEATSYS1 | COOLSYS1_SUPPLY | COOLSYS1_DEMAND | SINGLE WATER PLANT LOOP | SWHSYS1 | TOWERWATERSYS |ZoneTemperatureOscillationReportMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |AirLoopSystemEnergyAndWaterUseMonthly
| VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | CAV_BAS | AIRLOOP DATACENTER BASEMENT | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |AirLoopSystemComponentLoadsMonthly
| VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | CAV_BAS | AIRLOOP DATACENTER BASEMENT | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |AirLoopSystemComponentEnergyUseMonthly
| VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | CAV_BAS | AIRLOOP DATACENTER BASEMENT | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |MechanicalVentilationLoadsMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 08:43:24
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:43 |
RunPeriod | RUNPERIOD 1 |
Weather File | Atlanta-Hartsfield Jackson Intl AP GA USA TMY3 WMO#=722190 |
Latitude [deg] | 33.63 |
Longitude [deg] | -84.4 |
Elevation [m] | 308.00 |
Time Zone | -5.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 12183.89 | 3655.17 | 2436.78 | 3655.17 | 2436.78 |
Above Ground Wall Area [m2] | 11589.54 | 3476.86 | 2317.91 | 3476.86 | 2317.91 |
Window Opening Area [m2] | 4635.80 | 1390.74 | 927.16 | 1390.74 | 927.16 |
Gross Window-Wall Ratio [%] | 38.05 | 38.05 | 38.05 | 38.05 | 38.05 |
Above Ground Window-Wall Ratio [%] | 40.00 | 40.00 | 40.00 | 40.00 | 40.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 12183.89 | 3655.17 | 2436.78 | 3655.17 | 2436.78 |
Above Ground Wall Area [m2] | 11589.54 | 3476.86 | 2317.91 | 3476.86 | 2317.91 |
Window Opening Area [m2] | 4635.80 | 1390.74 | 927.16 | 1390.74 | 927.16 |
Gross Window-Wall Ratio [%] | 38.05 | 38.05 | 38.05 | 38.05 | 38.05 |
Above Ground Window-Wall Ratio [%] | 40.00 | 40.00 | 40.00 | 40.00 | 40.00 |
Total | |
Gross Roof Area [m2] | 3563.11 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
BASEMENT | 2779.43 | Yes | Yes | 6779.02 | 1.00 | 0.00 | 397.05 | 0.00 | 0.00 | 10.2732 | 18.58 | 4.8418 |
CORE_BOTTOM | 2496.12 | Yes | Yes | 6849.35 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.2732 | 18.58 | 8.0697 |
CORE_MID | 2496.12 | Yes | Yes | 6849.35 | 10.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.2732 | 18.58 | 8.0696 |
CORE_TOP | 2496.12 | Yes | Yes | 6849.35 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.2732 | 18.58 | 8.0696 |
PERIMETER_BOT_ZN_3 | 313.41 | Yes | Yes | 860.00 | 1.00 | 200.61 | 0.00 | 115.90 | 115.90 | 10.2732 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_2 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 77.26 | 77.26 | 10.2732 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_1 | 313.42 | Yes | Yes | 860.02 | 1.00 | 200.61 | 0.00 | 115.90 | 115.90 | 10.2732 | 18.58 | 8.0699 |
PERIMETER_BOT_ZN_4 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 77.26 | 77.26 | 10.2732 | 18.58 | 8.0699 |
PERIMETER_MID_ZN_3 | 313.41 | Yes | Yes | 860.00 | 10.00 | 200.61 | 0.00 | 115.90 | 115.90 | 10.2732 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_2 | 201.98 | Yes | Yes | 554.22 | 10.00 | 133.74 | 0.00 | 77.26 | 77.26 | 10.2732 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_1 | 313.42 | Yes | Yes | 860.02 | 10.00 | 200.61 | 0.00 | 115.90 | 115.90 | 10.2732 | 18.58 | 8.0699 |
PERIMETER_MID_ZN_4 | 201.98 | Yes | Yes | 554.22 | 10.00 | 133.74 | 0.00 | 77.26 | 77.26 | 10.2732 | 18.58 | 8.0699 |
PERIMETER_TOP_ZN_3 | 313.41 | Yes | Yes | 860.00 | 1.00 | 200.61 | 0.00 | 115.90 | 115.90 | 10.2732 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_2 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 77.26 | 77.26 | 10.2732 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_1 | 313.42 | Yes | Yes | 860.02 | 1.00 | 200.61 | 0.00 | 115.90 | 115.90 | 10.2732 | 18.58 | 8.0699 |
PERIMETER_TOP_ZN_4 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 77.26 | 77.26 | 10.2732 | 18.58 | 8.0699 |
GROUNDFLOOR_PLENUM | 3563.11 | Yes | No | 4344.14 | 1.00 | 297.11 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
MIDFLOOR_PLENUM | 3563.11 | Yes | No | 4344.14 | 10.00 | 297.11 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
TOPFLOOR_PLENUM | 3563.11 | Yes | No | 4344.14 | 1.00 | 297.11 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
DATACENTER_BOT_ZN_6 | 36.20 | Yes | Yes | 99.34 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.8735 | 18.58 | 215.2992 |
DATACENTER_MID_ZN_6 | 36.20 | Yes | Yes | 99.34 | 10.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.8735 | 18.58 | 215.2992 |
DATACENTER_TOP_ZN_6 | 36.20 | Yes | Yes | 99.34 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.8735 | 18.58 | 215.2992 |
DATACENTER_BASEMENT_ZN_6 | 783.68 | Yes | Yes | 1911.37 | 1.00 | 0.00 | 197.31 | 0.00 | 0.00 | 10.2732 | 18.58 | 484.4232 |
Total | 46320.38 | 126016.35 | 8024.24 | 594.36 | 4635.80 | 4635.80 | 10.3445 | 18.58 | 17.8789 | |||
Conditioned Total | 46320.38 | 126016.35 | 8024.24 | 594.36 | 4635.80 | 4635.80 | 10.3445 | 18.58 | 17.8789 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 42757.27 | 52129.67 | 3565.29 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
BASEMENT | 2779.43 | Yes | Yes | 1.00 | BASEMENT | GENERAL | BASEMENT | 10.2732 | 18.58 | 4.8418 | |
CORE_BOTTOM | 2496.12 | Yes | Yes | 1.00 | CORE_BOTTOM | GENERAL | CORE_BOTTOM | 10.2732 | 18.58 | 8.0697 | |
CORE_MID | 2496.12 | Yes | Yes | 10.00 | CORE_MID | GENERAL | CORE_MID | 10.2732 | 18.58 | 8.0696 | |
CORE_TOP | 2496.12 | Yes | Yes | 1.00 | CORE_TOP | GENERAL | CORE_TOP | 10.2732 | 18.58 | 8.0696 | |
PERIMETER_BOT_ZN_3 | 313.41 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_3 | GENERAL | PERIMETER_BOT_ZN_3 | 10.2732 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_2 | 201.98 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_2 | GENERAL | PERIMETER_BOT_ZN_2 | 10.2732 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_1 | 313.42 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_1 | GENERAL | PERIMETER_BOT_ZN_1 | 10.2732 | 18.58 | 8.0699 | |
PERIMETER_BOT_ZN_4 | 201.98 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_4 | GENERAL | PERIMETER_BOT_ZN_4 | 10.2732 | 18.58 | 8.0699 | |
PERIMETER_MID_ZN_3 | 313.41 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_3 | GENERAL | PERIMETER_MID_ZN_3 | 10.2732 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_2 | 201.98 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_2 | GENERAL | PERIMETER_MID_ZN_2 | 10.2732 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_1 | 313.42 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_1 | GENERAL | PERIMETER_MID_ZN_1 | 10.2732 | 18.58 | 8.0699 | |
PERIMETER_MID_ZN_4 | 201.98 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_4 | GENERAL | PERIMETER_MID_ZN_4 | 10.2732 | 18.58 | 8.0699 | |
PERIMETER_TOP_ZN_3 | 313.41 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_3 | GENERAL | PERIMETER_TOP_ZN_3 | 10.2732 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_2 | 201.98 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_2 | GENERAL | PERIMETER_TOP_ZN_2 | 10.2732 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_1 | 313.42 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_1 | GENERAL | PERIMETER_TOP_ZN_1 | 10.2732 | 18.58 | 8.0699 | |
PERIMETER_TOP_ZN_4 | 201.98 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_4 | GENERAL | PERIMETER_TOP_ZN_4 | 10.2732 | 18.58 | 8.0699 | |
GROUNDFLOOR_PLENUM | 3563.11 | Yes | No | 1.00 | GROUNDFLOOR_PLENUM | GENERAL | GROUNDFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
MIDFLOOR_PLENUM | 3563.11 | Yes | No | 10.00 | MIDFLOOR_PLENUM | GENERAL | MIDFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
TOPFLOOR_PLENUM | 3563.11 | Yes | No | 1.00 | TOPFLOOR_PLENUM | GENERAL | TOPFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
DATACENTER_BOT_ZN_6 | 36.20 | Yes | Yes | 1.00 | DATACENTER_BOT_ZN_6 | GENERAL | DATACENTER_BOT_ZN_6 | 17.8735 | 18.58 | 215.2992 | |
DATACENTER_MID_ZN_6 | 36.20 | Yes | Yes | 10.00 | DATACENTER_MID_ZN_6 | GENERAL | DATACENTER_MID_ZN_6 | 17.8735 | 18.58 | 215.2992 | |
DATACENTER_TOP_ZN_6 | 36.20 | Yes | Yes | 1.00 | DATACENTER_TOP_ZN_6 | GENERAL | DATACENTER_TOP_ZN_6 | 17.8735 | 18.58 | 215.2992 | |
DATACENTER_BASEMENT_ZN_6 | 783.68 | Yes | Yes | 1.00 | DATACENTER_BASEMENT_ZN_6 | GENERAL | DATACENTER_BASEMENT_ZN_6 | 10.2732 | 18.58 | 484.4232 | |
Total | 46320.38 | 10.3445 | 9.29 | 17.8789 | |||||||
Conditioned Total | 46320.38 | 10.3445 | 9.29 | 17.8789 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 42757.27 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 46320.38 | 46320.38 | 0.00 | 42757.27 | 3.1788 | 60.38 | 10.8345 |
Total | 46320.38 | 46320.38 | 0.00 | 42757.27 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:43:24
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 17-AUG-15:30 | 13-FEB-07:10 | - | - | - | - | - | - | - | - | - | - | 17-APR-14:39 |
Heating | 0.00 | 1771654.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 456876.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 332294.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 778371.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 84450.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 148727.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 58733.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 92827.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 5613.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 31612.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 1957895.51 | 1803266.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler | 0.00 | 1771654.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 456876.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 332294.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 305206.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DataCenterPlugLoads | 473165.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 5015.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 79171.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 263.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | General | 148727.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 58733.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 92827.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 5613.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Water Heater | 0.00 | 31612.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:43:24
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 1039.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 13950.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 12465.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 2204.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 46480.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 6127.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 6744.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 1891.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 4686.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 28.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 165.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 796.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 94743.43 | 1835.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 22.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 301.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 269.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 47.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1003.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 132.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 145.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 40.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 101.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 3.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 17.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 2045.39 | 39.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 22.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 301.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 269.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 47.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1003.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 132.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 145.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 40.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 101.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 3.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 17.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 2045.39 | 39.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:43:24
AirTerminal:SingleDuct:ConstantVolume:NoReheatDesign Size Maximum Air Flow Rate [m3/s] | |
BASEMENT DIRECT AIR | 6.09 |
DATACENTER_BOT_ZN_6 DIRECT AIR | 0.492156 |
DATACENTER_MID_ZN_6 DIRECT AIR | 4.69 |
DATACENTER_TOP_ZN_6 DIRECT AIR | 0.477940 |
DATACENTER_BASEMENT_ZN_6 DIRECT AIR | 22.14 |
Design Size Maximum Air Flow Rate [m3/s] | Design Size Constant Minimum Air Flow Fraction | User-Specified Constant Minimum Air Flow Fraction | Design Size Minimum Air Flow Rate [m3/s] | Design Size Maximum Flow Fraction during Reheat [] | User-Specified Maximum Flow Fraction during Reheat [] | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | Design Size Maximum Reheat Water Flow Rate [m3/s] | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | |
CORE_BOTTOM VAV BOX COMPONENT | 6.35 | 0.299672 | 0.308000 | 1.95 | 0.799126 | 0.500000 | 0.001271 | 0.000166 | 1.95 | 12.80 | 0.008000 |
CORE_MID VAV BOX COMPONENT | 59.97 | 0.317171 | 0.320000 | 19.19 | 0.845790 | 0.500000 | 0.001201 | 0.004042 | 19.19 | 12.80 | 0.008000 |
CORE_TOP VAV BOX COMPONENT | 5.91 | 0.321776 | 0.332000 | 1.96 | 0.858069 | 0.500000 | 0.001184 | 0.000753 | 2.66 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | 1.07 | 0.223413 | 0.230000 | 0.245862 | 0.595769 | 0.500000 | 0.001705 | 0.000131 | 0.461816 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | 1.11 | 0.139113 | 0.200000 | 0.221266 | 0.370968 | 0.500000 | 0.002739 | 0.000089 | 0.315843 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | 1.25 | 0.190528 | 0.200000 | 0.250698 | 0.508076 | 0.500000 | 0.002000 | 0.000145 | 0.512475 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | 1.40 | 0.110304 | 0.200000 | 0.279056 | 0.300000 | 0.500000 | 0.003454 | 0.000072 | 0.279056 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_3 VAV BOX COMPONENT | 10.14 | 0.235588 | 0.238000 | 2.41 | 0.628236 | 0.500000 | 0.001617 | 0.002144 | 7.59 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_2 VAV BOX COMPONENT | 11.46 | 0.134354 | 0.200000 | 2.29 | 0.358278 | 0.500000 | 0.002836 | 0.001403 | 4.96 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_1 VAV BOX COMPONENT | 11.97 | 0.199470 | 0.201000 | 2.41 | 0.531921 | 0.500000 | 0.001910 | 0.002114 | 7.48 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_4 VAV BOX COMPONENT | 12.15 | 0.126714 | 0.200000 | 2.43 | 0.337904 | 0.500000 | 0.003007 | 0.001363 | 4.82 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | 1.14 | 0.209114 | 0.216000 | 0.246685 | 0.557637 | 0.500000 | 0.001822 | 0.000269 | 0.951089 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | 1.16 | 0.132145 | 0.200000 | 0.232934 | 0.352386 | 0.500000 | 0.002883 | 0.000175 | 0.620532 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | 1.32 | 0.181404 | 0.200000 | 0.263308 | 0.483745 | 0.500000 | 0.002100 | 0.000266 | 0.939737 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | 1.30 | 0.118581 | 0.200000 | 0.259578 | 0.316216 | 0.500000 | 0.003213 | 0.000173 | 0.611693 | 12.80 | 0.008000 |
Design Size Rated Capacity [W] | Design Size Maximum Water Flow Rate [m3/s] | Design Size U-Factor Times Area Value [W/K] | |
CORE_BOTTOM VAV BOX REHEAT COIL | 18977.52 | 0.000166 | 382.57 |
CORE_MID VAV BOX REHEAT COIL | 462014.40 | 0.004042 | 10929.41 |
CORE_TOP VAV BOX REHEAT COIL | 86090.02 | 0.000753 | 2272.77 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | 14939.37 | 0.000131 | 394.13 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | 10215.85 | 0.000089 | 269.50 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | 16574.76 | 0.000145 | 437.24 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | 8286.08 | 0.000072 | 210.74 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | 245103.78 | 0.002144 | 6462.91 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | 160408.20 | 0.001403 | 4229.59 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | 241668.01 | 0.002114 | 6372.39 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | 155852.35 | 0.001363 | 4109.54 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | 30720.05 | 0.000269 | 809.90 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | 20042.61 | 0.000175 | 528.39 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | 30353.83 | 0.000266 | 800.25 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | 19757.34 | 0.000173 | 520.88 |
VAV_BOT WITH REHEAT HEATING COIL | 56839.85 | 0.000497 | 935.40 |
VAV_MID WITH REHEAT HEATING COIL | 544940.17 | 0.004767 | 8945.38 |
VAV_TOP WITH REHEAT HEATING COIL | 53637.39 | 0.000469 | 888.20 |
CAV_BAS HEATING COIL | 292827.06 | 0.002562 | 6501.96 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT | 5.59 | 2.95 | 11.17 | 2.95 | 10.08 | 10.08 | 0.300000 | 0.292952 | 10.08 |
VAV_MID WITH REHEAT | 52.84 | 28.73 | 105.68 | 36.91 | 94.04 | 94.04 | 0.300000 | 0.392524 | 94.04 |
VAV_TOP WITH REHEAT | 5.42 | 2.96 | 10.83 | 5.78 | 10.20 | 10.20 | 0.300000 | 0.566825 | 10.20 |
CAV_BAS | 6.09 | 6.09 | 6.09 | 6.09 | 6.09 | 6.09 | 1.00 | 1.00 | 6.09 |
AIRLOOP DATACENTER BASEMENT | 22.14 | 22.14 | 22.14 | 22.14 | 22.14 | 22.14 | 1.00 | 0.999992 | 22.14 |
AIRLOOP DATACENTER BOT | 0.492156 | 0.492156 | 0.492156 | 0.492156 | 0.492156 | 0.492156 | 1.00 | 1.00 | 0.492156 |
AIRLOOP DATACENTER MID | 4.69 | 4.69 | 4.69 | 4.69 | 4.69 | 4.69 | 1.00 | 1.00 | 4.69 |
AIRLOOP DATACENTER TOP | 0.477940 | 0.477940 | 0.477940 | 0.477940 | 0.477940 | 0.477940 | 1.00 | 1.00 | 0.477940 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT_OA_CONTROLLER | 10.08 | 2.54 |
VAV_MID WITH REHEAT_OA_CONTROLLER | 94.04 | 25.38 |
VAV_TOP WITH REHEAT_OA_CONTROLLER | 10.20 | 2.54 |
CAV_BAS_OA_CONTROLLER | 6.09 | 1.20 |
AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER | 22.14 | 0.338393 |
AIRLOOP DATACENTER BOT_OA_CONTROLLER | 0.492156 | 0.015632 |
AIRLOOP DATACENTER MID_OA_CONTROLLER | 4.69 | 0.156323 |
AIRLOOP DATACENTER TOP_OA_CONTROLLER | 0.477940 | 0.015632 |
Design Size Nominal Supply Air Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT OA HEAT RECOVERY | 2.54 |
VAV_MID WITH REHEAT OA HEAT RECOVERY | 25.38 |
VAV_TOP WITH REHEAT OA HEAT RECOVERY | 2.54 |
Design Size Design Inlet Air Temperature [C] | Design Size Design Inlet Water Temperature [C] | Design Size Design Outlet Air Temperature [C] | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | Design Size Design Coil Load [W] | Design Size Design Water Flow Rate [m3/s] | Design Size Design Air Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT COOLING COIL | 26.71 | 6.67 | 10.99 | 0.010332 | 0.008500 | 242286.81 | 0.010307 | 10.08 |
VAV_MID WITH REHEAT COOLING COIL | 26.99 | 6.67 | 10.98 | 0.010553 | 0.008500 | 2354776.15 | 0.100178 | 94.04 |
VAV_TOP WITH REHEAT COOLING COIL | 26.60 | 6.67 | 10.99 | 0.010322 | 0.008500 | 243642.38 | 0.010365 | 10.20 |
CAV_BAS COOLING COIL | 24.79 | 6.67 | 11.37 | 0.010025 | 0.008500 | 124171.22 | 0.005283 | 6.09 |
Design Size Maximum Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT FAN | 10.08 |
VAV_MID WITH REHEAT FAN | 94.04 |
VAV_TOP WITH REHEAT FAN | 10.20 |
Maximum Actuated Flow [m3/s] | Controller Convergence Tolerance | |
VAV_BOT WITH REHEAT_COOLC_CONTROLLER | 0.010307 | 0.000046 |
VAV_BOT WITH REHEAT_HEATC_CONTROLLER | 0.000497 | |
VAV_MID WITH REHEAT_COOLC_CONTROLLER | 0.100178 | 0.000005 |
VAV_MID WITH REHEAT_HEATC_CONTROLLER | 0.004767 | |
VAV_TOP WITH REHEAT_COOLC_CONTROLLER | 0.010365 | 0.000046 |
VAV_TOP WITH REHEAT_HEATC_CONTROLLER | 0.000469 | |
CAV_BAS_COOLC_CONTROLLER | 0.005283 | 0.000090 |
CAV_BAS_HEATC_CONTROLLER | 0.002562 |
Design Size Maximum Flow Rate [m3/s] | |
CAV_BAS FAN | 6.09 |
Design Size Rated Air Flow Rate [m3/s] | Design Size Rated Total Cooling Capacity [W] | Design Size Rated Sensible Cooling Capacity [W] | Design Size Rated Water Flow Rate [m3/s] | |
AIRLOOP DATACENTER BASEMENT COOLING COIL | 22.14 | 438414.06 | 303822.62 | 0.010737 |
AIRLOOP DATACENTER BOT COOLING COIL | 0.492156 | 9691.18 | 6727.91 | 0.000237 |
AIRLOOP DATACENTER MID COOLING COIL | 4.69 | 92549.83 | 64188.78 | 0.002267 |
AIRLOOP DATACENTER TOP COOLING COIL | 0.477940 | 9422.96 | 6537.25 | 0.000231 |
Supply Air Flow Rate [m3/s] | Supply Air Flow Rate During Heating Operation [m3/s] | Supply Air Flow Rate During Cooling Operation [m3/s] | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | Nominal Heating Capacity [W] | Nominal Cooling Capacity [W] | Supplemental Heating Coil Nominal Capacity [W] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | 22.14 | 22.14 | 22.14 | 22.14 | 438414.06 | 438414.06 | 18278.08 | 1.00 |
AIRLOOP DATACENTER BOT DXAC HEAT PUMP | 0.492156 | 0.492156 | 0.492156 | 0.492156 | 9691.18 | 9691.18 | 844.37 | 1.00 |
AIRLOOP DATACENTER MID DXAC HEAT PUMP | 4.69 | 4.69 | 4.69 | 4.69 | 92549.83 | 92549.83 | 8443.71 | 1.00 |
AIRLOOP DATACENTER TOP DXAC HEAT PUMP | 0.477940 | 0.477940 | 0.477940 | 0.477940 | 9422.96 | 9422.96 | 844.37 | 1.00 |
Design Size Maximum Flow Rate [m3/s] | |
AIRLOOP DATACENTER BASEMENT SUPPLY FAN | 22.14 |
AIRLOOP DATACENTER BOT SUPPLY FAN | 0.492156 |
AIRLOOP DATACENTER MID SUPPLY FAN | 4.69 |
AIRLOOP DATACENTER TOP SUPPLY FAN | 0.477940 |
Design Size Rated Air Flow Rate [m3/s] | Design Size Rated Heating Capacity [W] | Design Size Rated Water Flow Rate [m3/s] | |
AIRLOOP DATACENTER BASEMENT HEATING COIL | 22.14 | 438414.06 | 0.010737 |
AIRLOOP DATACENTER BOT HEATING COIL | 0.492156 | 9691.18 | 0.000237 |
AIRLOOP DATACENTER MID HEATING COIL | 4.69 | 92549.83 | 0.002267 |
AIRLOOP DATACENTER TOP HEATING COIL | 0.477940 | 9422.96 | 0.000231 |
Design Size Nominal Capacity [W] | |
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | 18278.08 |
AIRLOOP DATACENTER BOT_SUPPHEATCOIL | 844.37 |
AIRLOOP DATACENTER MID_SUPPHEATCOIL | 8443.71 |
AIRLOOP DATACENTER TOP_SUPPHEATCOIL | 844.37 |
Design Size Nominal Capacity Volume [m3/s] | User-Specified Nominal Capacity Volume [m3/s] | Design Size Rated Power [W] | User-Specified Rated Power [W] | |
DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | 0.000153 | 0.000037 | 96450.70 | 100000.00 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | Design Minimum Flow Rate [m3/s] | |
COOLSYS1 PUMP SECONDARY | 0.126133 | 20593.62 | |
HEATSYS1 PUMP | 0.021602 | 6505.59 | 0.000000 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
COOLSYS1_DEMAND | 0.126133 | 15.14 |
HEATSYS1 | 0.021602 | 2.59 |
COOLSYS1_SUPPLY | 0.126133 | 15.14 |
SINGLE WATER PLANT LOOP | 0.013471 | 1.62 |
SWHSYS1 | 0.000440 | 0.052800 |
Loop Supply Side Design Fluid Flow Rate [m3/s] | Loop Demand Side Design Fluid Flow Rate [m3/s] | Heat Exchanger U-Factor Times Area Value [W/C] | Loop-to-loop Temperature Difference Used to Size Heat Exchanger U-Factor Times Area Value [C] | |
BYPASS HEAT EXCHANGER | 0.126133 | 0.126133 | 529442.24 | 5.60 |
Design Size Nominal Capacity [W] | User-Specified Nominal Capacity [W] | Design Size Design Water Flow Rate [m3/s] | |
HEATSYS1 BOILER | 2469248.63 | 2469248.63 | 0.021602 |
CENTRAL BOILER | 554905.19 | 543970.57 | 0.013471 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
COOLSYS1 CHILLER1 PUMP | 0.063066 | 7128.83 |
COOLSYS1 CHILLER2 PUMP | 0.063066 | 7128.83 |
PLANT CIRC PUMP | 0.013471 | 3435.87 |
SWHSYS1 PUMP | 0.000440 | 56.21 |
Design Size Reference Chilled Water Flow Rate [m3/s] | User-Specified Reference Chilled Water Flow Rate [m3/s] | Design Size Reference Capacity [W] | User-Specified Reference Capacity [W] | Design Size Reference Condenser Water Flow Rate [m3/s] | |
COOLSYS1 CHILLER1 | 0.126133 | 0.063665 | 1500186.25 | 1507316.17 | 0.074591 |
COOLSYS1 CHILLER2 | 0.126133 | 0.063665 | 1500186.25 | 1507316.17 | 0.074591 |
Design Water Flow Rate [m3/s] | Air Flow Rate at High Fan Speed [m3/s] | Fluid cooler UA value at high fan speed based on nominal capacity input [W/K] | Air Flow Rate at Low Fan Speed [m3/s] | Fan Power at Low Fan Speed [W] | U-factor Times Area Value at Low Fan Speed [W/C] | |
CENTRAL TOWER | 0.013471 | 139666.47 | 58584.37 | 69833.23 | 7879.72 | 21346.17 |
Use Side Design Flow Rate [m3/s] | |
SWHSYS1 WATER HEATER | 0.000440 |
Maximum Loop Flow Rate [m3/s] | Condenser Loop Volume [m3] | |
TOWERWATERSYS | 0.149183 | 17.90 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
TOWERWATERSYS PUMP | 0.149183 | 36934.41 |
Design Air Flow Rate [m3/s] | Nominal Capacity [W] | Air Flow Rate in free convection regime [m3/s] | Tower capacity in free convection regime at design conditions [W] | |
TOWERWATERSYS COOLTOWER 1 | 59.48 | 1788404.52 | 11.90 | 223550.57 |
TOWERWATERSYS COOLTOWER 2 | 59.48 | 1788404.52 | 11.90 | 223550.57 |
Design Water Flow Rate [m3/s] Equipment # 47 | |
WSHPPLANT OPERATION SCHEME | 0.077478 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:43:24
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
PERIMETER_BOT_ZN_3_WALL_NORTH | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | |
PERIMETER_BOT_ZN_2_WALL_EAST | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | |
PERIMETER_BOT_ZN_1_WALL_SOUTH | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | |
PERIMETER_BOT_ZN_4_WALL_WEST | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | |
PERIMETER_MID_ZN_3_WALL_NORTH | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_MID_ZN_2_WALL_EAST | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_MID_ZN_1_WALL_SOUTH | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_MID_ZN_4_WALL_WEST | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | |
PERIMETER_TOP_ZN_3_WALL_NORTH | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_TOP_ZN_2_WALL_EAST | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_TOP_ZN_1_WALL_SOUTH | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_TOP_ZN_4_WALL_WEST | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 08:43:24
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 08:43:24
VersionVersion ID | |
1 | 22.1.0 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 11.90 | 7.70 | 4.00 | 7.90 | 13.80 | 17.20 | 20.80 | 24.80 | 26.10 | 26.50 | 22.50 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Atlanta-Hartsfield Jackson Intl AP GA USA TMY3 WMO#=722190 | 33.63 | -84.43 | -5.00 | 308.00 | 97679 | 1.1610 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 16.60 | 22.50 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | OfficeLarge | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 23 | 221 | 36 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | BASEMENT | 0.0 | 0.00 | 0.00 | 0.00 | 44.59 | 24.37 | -1.22 | 1 | 1 | 1 | 16.08 | 73.11 | 0.00 | 48.74 | -2.44 | 0.00 | 2.44 | 6779.02 | TARP | TARP | 2779.43 | 0.00 | 0.00 | 0.00 | 9 | 0 | 0 | Yes |
2 | CORE_BOTTOM | 0.0 | 0.00 | 0.00 | 0.00 | 37.01 | 24.37 | 1.37 | 1 | 1 | 1 | 5.49 | 68.53 | 4.57 | 44.17 | 0.00 | 2.74 | 2.74 | 6849.35 | TARP | TARP | 2496.12 | 0.00 | 0.00 | 0.00 | 7 | 0 | 0 | Yes |
3 | CORE_MID | 0.0 | 0.00 | 0.00 | 0.00 | 37.01 | 24.37 | 18.14 | 1 | 10 | 1 | 5.49 | 68.53 | 4.57 | 44.17 | 16.77 | 19.51 | 2.74 | 6849.35 | TARP | TARP | 2496.12 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
4 | CORE_TOP | 0.0 | 0.00 | 0.00 | 0.00 | 37.01 | 24.37 | 34.91 | 1 | 1 | 1 | 5.49 | 68.53 | 4.57 | 44.17 | 33.54 | 36.28 | 2.74 | 6849.35 | TARP | TARP | 2496.12 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
5 | PERIMETER_BOT_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 46.54 | 1.37 | 1 | 1 | 1 | 0.00 | 73.11 | 44.17 | 48.74 | 0.00 | 2.74 | 2.74 | 860.00 | TARP | TARP | 313.41 | 200.61 | 76.91 | 115.90 | 8 | 9 | 0 | Yes |
6 | PERIMETER_BOT_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 70.95 | 24.37 | 1.37 | 1 | 1 | 1 | 68.53 | 73.11 | 0.00 | 48.74 | 0.00 | 2.74 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 52.57 | 77.26 | 6 | 5 | 0 | Yes |
7 | PERIMETER_BOT_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 2.20 | 1.37 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 4.57 | 0.00 | 2.74 | 2.74 | 860.02 | TARP | TARP | 313.42 | 200.61 | 76.91 | 115.90 | 8 | 9 | 0 | Yes |
8 | PERIMETER_BOT_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.16 | 24.37 | 1.37 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 48.74 | 0.00 | 2.74 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 52.57 | 77.26 | 6 | 5 | 0 | Yes |
9 | PERIMETER_MID_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 46.54 | 18.14 | 1 | 10 | 1 | 0.00 | 73.11 | 44.17 | 48.74 | 16.77 | 19.51 | 2.74 | 860.00 | TARP | TARP | 313.41 | 200.61 | 84.71 | 115.90 | 7 | 1 | 0 | Yes |
10 | PERIMETER_MID_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 70.95 | 24.37 | 18.14 | 1 | 10 | 1 | 68.53 | 73.11 | 0.00 | 48.74 | 16.77 | 19.51 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 56.47 | 77.26 | 6 | 1 | 0 | Yes |
11 | PERIMETER_MID_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 2.20 | 18.14 | 1 | 10 | 1 | 0.00 | 73.11 | 0.00 | 4.57 | 16.77 | 19.51 | 2.74 | 860.02 | TARP | TARP | 313.42 | 200.61 | 84.71 | 115.90 | 7 | 1 | 0 | Yes |
12 | PERIMETER_MID_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.16 | 24.37 | 18.14 | 1 | 10 | 1 | 0.00 | 4.57 | 0.00 | 48.74 | 16.77 | 19.51 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 56.47 | 77.26 | 6 | 1 | 0 | Yes |
13 | PERIMETER_TOP_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 46.54 | 34.91 | 1 | 1 | 1 | 0.00 | 73.11 | 44.17 | 48.74 | 33.54 | 36.28 | 2.74 | 860.00 | TARP | TARP | 313.41 | 200.61 | 84.71 | 115.90 | 7 | 1 | 0 | Yes |
14 | PERIMETER_TOP_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 70.95 | 24.37 | 34.91 | 1 | 1 | 1 | 68.53 | 73.11 | 0.00 | 48.74 | 33.54 | 36.28 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 56.47 | 77.26 | 6 | 1 | 0 | Yes |
15 | PERIMETER_TOP_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 2.20 | 34.91 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 4.57 | 33.54 | 36.28 | 2.74 | 860.02 | TARP | TARP | 313.42 | 200.61 | 84.71 | 115.90 | 7 | 1 | 0 | Yes |
16 | PERIMETER_TOP_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.16 | 24.37 | 34.91 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 48.74 | 33.54 | 36.28 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 56.47 | 77.26 | 6 | 1 | 0 | Yes |
17 | GROUNDFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 24.37 | 3.35 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 48.74 | 2.74 | 3.96 | 1.22 | 4344.14 | TARP | TARP | 3563.11 | 297.11 | 297.11 | 0.00 | 11 | 0 | 0 | No |
18 | MIDFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 24.37 | 20.12 | 1 | 10 | 1 | 0.00 | 73.11 | 0.00 | 48.74 | 19.51 | 20.73 | 1.22 | 4344.14 | TARP | TARP | 3563.11 | 297.11 | 297.11 | 0.00 | 11 | 0 | 0 | No |
19 | TOPFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 24.37 | 36.89 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 48.74 | 36.28 | 37.50 | 1.22 | 4344.14 | TARP | TARP | 3563.11 | 297.11 | 297.11 | 0.00 | 11 | 0 | 0 | No |
20 | DATACENTER_BOT_ZN_6 | 0.0 | 5.49 | 44.17 | 0.00 | 5.03 | 24.37 | 1.37 | 1 | 1 | 1 | 4.57 | 5.49 | 4.57 | 44.17 | 0.00 | 2.74 | 2.74 | 99.34 | TARP | TARP | 36.20 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
21 | DATACENTER_MID_ZN_6 | 0.0 | 4.57 | 4.57 | 16.77 | 5.03 | 24.37 | 18.14 | 1 | 10 | 1 | 4.57 | 5.49 | 4.57 | 44.17 | 16.77 | 19.51 | 2.74 | 99.34 | TARP | TARP | 36.20 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
22 | DATACENTER_TOP_ZN_6 | 0.0 | 4.57 | 4.57 | 33.54 | 5.03 | 24.37 | 34.91 | 1 | 1 | 1 | 4.57 | 5.49 | 4.57 | 44.17 | 33.54 | 36.28 | 2.74 | 99.34 | TARP | TARP | 36.20 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
23 | DATACENTER_BASEMENT_ZN_6 | 0.0 | 16.08 | 0.00 | -2.44 | 8.04 | 24.37 | -1.22 | 1 | 1 | 1 | 0.00 | 16.08 | 0.00 | 48.74 | -2.44 | 0.00 | 2.44 | 1911.37 | TARP | TARP | 783.68 | 0.00 | 0.00 | 0.00 | 10 | 0 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | BASEMENT | 2779.43 | 149.6 | 18.579 | 5.382E-002 | 10.273 | 4.842 | 0.000 | 0.000 | 0.000 | 0.000 | 15.115 | No |
2 | CORE_BOTTOM | 2496.12 | 134.4 | 18.579 | 5.382E-002 | 10.273 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 18.343 | No |
3 | CORE_MID | 2496.12 | 134.4 | 18.579 | 5.382E-002 | 10.273 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 18.343 | No |
4 | CORE_TOP | 2496.12 | 134.4 | 18.579 | 5.382E-002 | 10.273 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 18.343 | No |
5 | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 18.579 | 5.382E-002 | 10.273 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 18.343 | No |
6 | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 10.273 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 18.343 | No |
7 | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 18.579 | 5.382E-002 | 10.273 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 18.343 | No |
8 | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 10.273 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 18.343 | No |
9 | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 18.579 | 5.382E-002 | 10.273 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 18.343 | No |
10 | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 10.273 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 18.343 | No |
11 | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 18.579 | 5.382E-002 | 10.273 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 18.343 | No |
12 | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 10.273 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 18.343 | No |
13 | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 18.579 | 5.382E-002 | 10.273 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 18.343 | No |
14 | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 10.273 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 18.343 | No |
15 | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 18.579 | 5.382E-002 | 10.273 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 18.343 | No |
16 | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 10.273 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 18.343 | No |
17 | GROUNDFLOOR_PLENUM | 3563.11 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
18 | MIDFLOOR_PLENUM | 3563.11 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
19 | TOPFLOOR_PLENUM | 3563.11 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
20 | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 18.579 | 5.382E-002 | 17.873 | 215.299 | 0.000 | 0.000 | 0.000 | 0.000 | 233.173 | No |
21 | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 18.579 | 5.382E-002 | 17.873 | 215.299 | 0.000 | 0.000 | 0.000 | 0.000 | 233.173 | No |
22 | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 18.579 | 5.382E-002 | 17.873 | 215.299 | 0.000 | 0.000 | 0.000 | 0.000 | 233.173 | No |
23 | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 18.579 | 5.382E-002 | 10.273 | 484.423 | 0.000 | 0.000 | 0.000 | 0.000 | 494.696 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | DATACENTER_BOT_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 1.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | DATACENTER_MID_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 1.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
3 | DATACENTER_TOP_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 1.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
4 | DATACENTER_BASEMENT_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 42.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 42 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
5 | BASEMENT | BLDG_OCC_SCH_WO_SB | BASEMENT | 2779.43 | 149.6 | 149.6 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 150 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
6 | CORE_BOTTOM | BLDG_OCC_SCH_WO_SB | CORE_BOTTOM | 2496.12 | 134.4 | 134.4 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 134 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
7 | CORE_MID | BLDG_OCC_SCH_WO_SB | CORE_MID | 2496.12 | 134.4 | 134.4 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 134 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
8 | CORE_TOP | BLDG_OCC_SCH_WO_SB | CORE_TOP | 2496.12 | 134.4 | 134.4 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 134 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
9 | PERIMETER_BOT_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
10 | PERIMETER_BOT_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
11 | PERIMETER_BOT_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
12 | PERIMETER_BOT_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
13 | PERIMETER_MID_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
14 | PERIMETER_MID_ZN_2 | BLDG_OCC_SCH_W_SB | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
15 | PERIMETER_MID_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
16 | PERIMETER_MID_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
17 | PERIMETER_TOP_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
18 | PERIMETER_TOP_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
19 | PERIMETER_TOP_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
20 | PERIMETER_TOP_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | BASEMENT_LIGHTS | LTG_SCH_OFFICE | BASEMENT | 2779.43 | 149.6 | 28553.717 | 10.273 | 190.864 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 28553.717 |
2 | CORE_BOTTOM_LIGHTS | LTG_SCH_OFFICE | CORE_BOTTOM | 2496.12 | 134.4 | 25643.245 | 10.273 | 190.864 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 25643.245 |
3 | CORE_MID_LIGHTS | LTG_SCH_OFFICE | CORE_MID | 2496.12 | 134.4 | 25643.245 | 10.273 | 190.864 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 25643.245 |
4 | CORE_TOP_LIGHTS | LTG_SCH_OFFICE | CORE_TOP | 2496.12 | 134.4 | 25643.245 | 10.273 | 190.864 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 25643.245 |
5 | PERIMETER_BOT_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 3219.765 | 10.273 | 190.864 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3219.765 |
6 | PERIMETER_BOT_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 2074.939 | 10.273 | 190.864 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2074.939 |
7 | PERIMETER_BOT_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 3219.836 | 10.273 | 190.864 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3219.836 |
8 | PERIMETER_BOT_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 2074.939 | 10.273 | 190.864 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2074.939 |
9 | PERIMETER_MID_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 3219.765 | 10.273 | 190.864 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3219.765 |
10 | PERIMETER_MID_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 2074.939 | 10.273 | 190.864 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2074.939 |
11 | PERIMETER_MID_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 3219.836 | 10.273 | 190.864 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3219.836 |
12 | PERIMETER_MID_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 2074.939 | 10.273 | 190.864 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2074.939 |
13 | PERIMETER_TOP_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 3219.765 | 10.273 | 190.864 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3219.765 |
14 | PERIMETER_TOP_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 2074.939 | 10.273 | 190.864 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2074.939 |
15 | PERIMETER_TOP_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 3219.836 | 10.273 | 190.864 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3219.836 |
16 | PERIMETER_TOP_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 2074.939 | 10.273 | 190.864 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2074.939 |
17 | DATACENTER_BASEMENT_LIGHTS | LTG_SCH_OFFICE | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 8050.927 | 10.273 | 190.864 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 8050.927 |
18 | DATACENTER_BOT_LIGHTS | LTG_SCH_DATACENTER | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 647.068 | 17.873 | 332.067 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 647.068 |
19 | DATACENTER_MID_LIGHTS | LTG_SCH_DATACENTER | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 647.068 | 17.873 | 332.067 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 647.068 |
20 | DATACENTER_TOP_LIGHTS | LTG_SCH_DATACENTER | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 647.068 | 17.873 | 332.067 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 647.068 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | BASEMENT_MISCPLUG_EQUIP | ALWAYS_ON | BASEMENT | 2779.43 | 149.6 | 13457.544 | 4.842 | 89.956 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 13457.544 | 13457.544 |
2 | CORE_BOTTOM_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_BOTTOM | 2496.12 | 134.4 | 20142.877 | 8.070 | 149.925 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 20142.877 |
3 | CORE_MID_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_MID | 2496.12 | 134.4 | 20142.800 | 8.070 | 149.924 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 20142.800 |
4 | CORE_TOP_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_TOP | 2496.12 | 134.4 | 20142.800 | 8.070 | 149.924 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 20142.800 |
5 | PERIMETER_BOT_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 2529.242 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.242 |
6 | PERIMETER_BOT_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 1629.940 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.940 |
7 | PERIMETER_BOT_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 2529.281 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.281 |
8 | PERIMETER_BOT_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 1629.929 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.929 |
9 | PERIMETER_MID_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 2529.242 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.242 |
10 | PERIMETER_MID_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 1629.940 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.940 |
11 | PERIMETER_MID_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 2529.281 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.281 |
12 | PERIMETER_MID_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 1629.929 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.929 |
13 | PERIMETER_TOP_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 2529.242 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.242 |
14 | PERIMETER_TOP_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 1629.940 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.940 |
15 | PERIMETER_TOP_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 2529.281 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.281 |
16 | PERIMETER_TOP_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 1629.929 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.929 |
17 | DATACENTER_BASEMENT_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 379632.522 | 484.423 | 9000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 94908.130 | 379632.522 |
18 | DATACENTER_BOT_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 7794.422 | 215.299 | 4000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 1948.606 | 7794.422 |
19 | DATACENTER_MID_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 7794.422 | 215.299 | 4000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 1948.606 | 7794.422 |
20 | DATACENTER_TOP_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 7794.422 | 215.299 | 4000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 1948.606 | 7794.422 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 3.975 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | INTERIORFURNISHINGS | 2 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
3 | DROPCEILING | 4 | 1 | 3 | 0.167 | 4.488 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
4 | INT_WALL | 7 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | EXT_SLAB_8IN_WITH_CARPET | 8 | 2 | 7 | 0.167 | 3.285 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
6 | INT_SLAB_FLOOR | 12 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
7 | INT_SLAB_CEILING | 13 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | VeryRough |
8 | NONRES_ROOF | 17 | 3 | 3 | 0.167 | 0.2284 | 0.750 | 0.900 | 0.450 | 0.700 | Rough |
9 | NONRES_EXT_WALL_GRD | 20 | 3 | 9 | 0.167 | 1.223 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
10 | NONRES_EXT_WALL_MID | 21 | 3 | 9 | 0.167 | 1.174 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
11 | NONRES_EXT_WALL_TOP | 22 | 3 | 9 | 0.167 | 1.421 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
12 | BASEMENT_WALL_EAST_CFACTOR | 39 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | BASEMENT_WALL_SOUTH_CFACTOR | 40 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | BASEMENT_WALL_NORTH_CFACTOR | 41 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR | 42 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
16 | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR | 43 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
17 | DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR | 44 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2516 |
2 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
3 | AC02 ACOUSTIC CEILING | 0.0127 | 0.057 | 288.000 | 1339.000 | 0.2228 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | 200MM NORMALWEIGHT CONCRETE FLOOR | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
7 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
8 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
9 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
10 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
11 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
12 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
13 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 4.319 |
14 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
15 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
16 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.6505 |
17 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
18 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
19 | NONRES_EXTERIOR_WALL_INSULATION_MID | 0.0000 | 0.000 | 0.000 | 0.000 | 0.6842 |
20 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
21 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
22 | NONRES_EXTERIOR_WALL_INSULATION_TOP | 0.0000 | 0.000 | 0.000 | 0.000 | 0.5363 |
23 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
24 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
25 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
26 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
27 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
28 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
29 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
30 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
31 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
32 | ~FC_Insulation_5 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
33 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
34 | ~FC_Insulation_6 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
35 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 3.9747841 | 3.9747841 | 3.9747841 | |
3 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
4 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
5 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
6 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
7 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
8 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
9 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
10 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
11 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
12 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
13 | 3 | -0.21589802E-09 | 0.15643069E-09 | -0.21589802E-09 | 0.12999471E-21 |
14 | 2 | 0.50772448E-02 | 0.30006816E-02 | 0.50772448E-02 | -0.13693132E-08 |
15 | 1 | -2.5944910 | 1.4597758 | -2.5944910 | 0.76344767E-02 |
16 | 0 | 7.0433378 | 2.9911476 | 7.0433378 | |
17 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
18 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
19 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
20 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
21 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
22 | 7 | -0.18651654E-16 | -0.16428647E-15 | -0.26578847E-08 | -0.25364002E-17 |
23 | 6 | 0.67402962E-01 | 0.99142722E-07 | 0.38101547E-02 | -0.76639482E-03 |
24 | 5 | -1.8580732 | 0.49502125E-04 | -0.10651409 | 0.21891119E-01 |
25 | 4 | 18.220105 | 0.12801333E-02 | 1.0775450 | -0.22586539 |
26 | 3 | -79.928293 | 0.66708484E-02 | -4.9803755 | 1.0625663 |
27 | 2 | 166.43177 | 0.75131194E-02 | 11.128837 | -2.4125483 |
28 | 1 | -159.97298 | 0.18548900E-02 | -11.587784 | 2.5494418 |
29 | 0 | 57.057412 | 0.52755123E-04 | 4.4818272 | |
30 | 7 | 0.43260499E-16 | 0.34524919E-16 | 0.52793240E-17 | 0.0000000 |
31 | 6 | 0.69434179E-09 | 0.98085174E-11 | 0.18162501E-10 | -0.40870994E-12 |
32 | 5 | -0.12888762E-04 | 0.28373718E-06 | -0.16918523E-06 | 0.92361873E-08 |
33 | 4 | 0.25174112E-01 | 0.33697681E-03 | 0.22646198E-03 | -0.31467795E-04 |
34 | 3 | -3.7600775 | 0.27170599E-01 | -0.48495626E-01 | 0.94171705E-02 |
35 | 2 | 51.553741 | 0.22121684 | 1.2284947 | -0.25833933 |
36 | 1 | -128.86110 | 0.21944682 | -5.1479470 | 1.1228340 |
37 | 0 | 81.526494 | 0.16043334E-01 | 4.4519351 | |
38 | 7 | 0.52793240E-17 | 0.34524919E-16 | 0.43260499E-16 | 0.0000000 |
39 | 6 | 0.18162501E-10 | 0.98085174E-11 | 0.69434179E-09 | -0.40870994E-12 |
40 | 5 | -0.16918523E-06 | 0.28373718E-06 | -0.12888762E-04 | 0.92361873E-08 |
41 | 4 | 0.22646198E-03 | 0.33697681E-03 | 0.25174112E-01 | -0.31467795E-04 |
42 | 3 | -0.48495626E-01 | 0.27170599E-01 | -3.7600775 | 0.94171705E-02 |
43 | 2 | 1.2284947 | 0.22121684 | 51.553741 | -0.25833933 |
44 | 1 | -5.1479470 | 0.21944682 | -128.86110 | 1.1228340 |
45 | 0 | 4.4519351 | 0.16043334E-01 | 81.526494 | |
46 | 3 | -0.62451068E-06 | 0.10350887E-08 | -0.38276125E-05 | 0.11995084E-16 |
47 | 2 | 0.77976586 | 0.13989883E-02 | 1.0579789 | -0.73382352E-06 |
48 | 1 | -21.958702 | 0.93426804E-01 | -6.3215779 | 0.20283230 |
49 | 0 | 21.361010 | 0.87247630E-01 | 5.4456762 | |
50 | 9 | 0.12806887E-14 | 0.42271709E-16 | -0.13586671E-09 | -0.40936836E-17 |
51 | 8 | 0.19922932E-07 | 0.16187222E-12 | 0.35697139E-03 | -0.22653060E-09 |
52 | 7 | -0.11619186E-01 | 0.85920355E-08 | -0.22189363E-01 | 0.13211437E-03 |
53 | 6 | 0.38843793 | 0.30204786E-05 | 0.45766083 | -0.45484060E-02 |
54 | 5 | -5.0254998 | 0.11379910E-03 | -4.3303126 | 0.61137149E-01 |
55 | 4 | 32.272621 | 0.93848507E-03 | 21.006408 | -0.41242756 |
56 | 3 | -109.67225 | 0.20601564E-02 | -54.766020 | 1.4927443 |
57 | 2 | 195.59070 | 0.11662962E-02 | 77.088399 | -2.8762550 |
58 | 1 | -170.59539 | 0.12524661E-03 | -55.026900 | 2.7356126 |
59 | 0 | 57.057407 | 0.71759292E-06 | 15.597005 | |
60 | 9 | 0.14110139E-14 | 0.39742576E-16 | -0.13817129E-09 | -0.60843190E-17 |
61 | 8 | 0.20247994E-07 | 0.15595569E-12 | 0.36048606E-03 | -0.23022666E-09 |
62 | 7 | -0.11724403E-01 | 0.82461052E-08 | -0.22340970E-01 | 0.13331073E-03 |
63 | 6 | 0.39129736 | 0.28944083E-05 | 0.46010459 | -0.45821116E-02 |
64 | 5 | -5.0534104 | 0.10890513E-03 | -4.3491197 | 0.61483222E-01 |
65 | 4 | 32.396114 | 0.89705981E-03 | 21.080005 | -0.41406715 |
66 | 3 | -109.93510 | 0.19671505E-02 | -54.911560 | 1.4965416 |
67 | 2 | 195.85133 | 0.11126060E-02 | 77.221727 | -2.8803937 |
68 | 1 | -170.69171 | 0.11937799E-03 | -55.065382 | 2.7373008 |
69 | 0 | 57.057407 | 0.68337402E-06 | 15.590414 | |
70 | 9 | 0.11953810E-14 | 0.45347951E-16 | -0.12637851E-09 | -0.31580148E-17 |
71 | 8 | 0.18583176E-07 | 0.18541820E-12 | 0.34227377E-03 | -0.21129711E-09 |
72 | 7 | -0.11178467E-01 | 0.10005971E-07 | -0.21554080E-01 | 0.12710323E-03 |
73 | 6 | 0.37645972 | 0.35409928E-05 | 0.44740546 | -0.44072130E-02 |
74 | 5 | -4.9085688 | 0.13417224E-03 | -4.2513079 | 0.59687292E-01 |
75 | 4 | 31.755172 | 0.11121548E-02 | 20.697061 | -0.40555762 |
76 | 3 | -108.57065 | 0.24524110E-02 | -54.154201 | 1.4768303 |
77 | 2 | 194.49811 | 0.13939007E-02 | 76.528253 | -2.8589059 |
78 | 1 | -170.19150 | 0.15023953E-03 | -54.865849 | 2.7285341 |
79 | 0 | 57.057407 | 0.86422455E-06 | 15.625098 | |
80 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
81 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
82 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
83 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
84 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
85 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
86 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
87 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
88 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
89 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
90 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
91 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
92 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
93 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
94 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
95 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
96 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
97 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
98 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
99 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
100 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
101 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
102 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
103 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
104 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
105 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
106 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
107 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
108 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
109 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
110 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
111 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
112 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
113 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
114 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
115 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
116 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
117 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
118 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
119 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
120 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
121 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
122 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
123 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
124 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
125 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
126 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
127 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | WINDOW_U_0.498_SHGC_EAST_0.25 | 35 | 1 | VerySmooth | 2.831 | 2.831 | 1.000 | 0.251 | ||
2 | WINDOW_U_0.498_SHGC_SOUTH_0.25 | 36 | 1 | VerySmooth | 2.831 | 2.831 | 1.000 | 0.251 | ||
3 | WINDOW_U_0.498_SHGC_WEST_0.25 | 37 | 1 | VerySmooth | 2.831 | 2.831 | 1.000 | 0.251 | ||
4 | WINDOW_U_0.498_SHGC_NORTH_0.25 | 38 | 1 | VerySmooth | 2.831 | 2.831 | 1.000 | 0.251 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | GLAZING LAYER EAST | SpectralAverage | 2.00974E-002 | 0.16139 | 0.61139 | 0.61139 | 0.27500 | 0.15630 | 0.22588 | 0.00000 | 0.84000 | 0.84000 | 0.10990 | 1.00000 | No | |
2 | GLAZING LAYER SOUTH | SpectralAverage | 2.00974E-002 | 0.16139 | 0.61139 | 0.61139 | 0.27500 | 0.15630 | 0.22588 | 0.00000 | 0.84000 | 0.84000 | 0.10990 | 1.00000 | No | |
3 | GLAZING LAYER WEST | SpectralAverage | 2.00974E-002 | 0.16139 | 0.61139 | 0.61139 | 0.27500 | 0.15630 | 0.22588 | 0.00000 | 0.84000 | 0.84000 | 0.10990 | 1.00000 | No | |
4 | GLAZING LAYER NORTH | SpectralAverage | 2.00974E-002 | 0.16139 | 0.61139 | 0.61139 | 0.27500 | 0.15630 | 0.22588 | 0.00000 | 0.84000 | 0.84000 | 0.10990 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 30 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Enclosure Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Enclosures | |
1 | PERIMETER_BOT_ZN_3 | 5 | 0 |
2 | PERIMETER_BOT_ZN_2 | 3 | 0 |
3 | PERIMETER_BOT_ZN_1 | 5 | 0 |
4 | PERIMETER_BOT_ZN_4 | 3 | 0 |
5 | PERIMETER_MID_ZN_3 | 1 | 0 |
6 | PERIMETER_MID_ZN_2 | 1 | 0 |
7 | PERIMETER_MID_ZN_1 | 1 | 0 |
8 | PERIMETER_MID_ZN_4 | 1 | 0 |
9 | PERIMETER_TOP_ZN_3 | 1 | 0 |
10 | PERIMETER_TOP_ZN_2 | 1 | 0 |
11 | PERIMETER_TOP_ZN_1 | 1 | 0 |
12 | PERIMETER_TOP_ZN_4 | 1 | 0 |
Enclosure Name | Number of Adjacent Enclosures with Windows | Adjacent Enclosure Names - 1st 100 (max) | |
1 | PERIMETER_BOT_ZN_3 | 0 | |
2 | PERIMETER_BOT_ZN_2 | 0 | |
3 | PERIMETER_BOT_ZN_1 | 0 | |
4 | PERIMETER_BOT_ZN_4 | 0 | |
5 | PERIMETER_MID_ZN_3 | 0 | |
6 | PERIMETER_MID_ZN_2 | 0 | |
7 | PERIMETER_MID_ZN_1 | 0 | |
8 | PERIMETER_MID_ZN_4 | 0 | |
9 | PERIMETER_TOP_ZN_3 | 0 | |
10 | PERIMETER_TOP_ZN_2 | 0 | |
11 | PERIMETER_TOP_ZN_1 | 0 | |
12 | PERIMETER_TOP_ZN_4 | 0 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 1.1356 | 87921.3 | 0.481 | 5.5005E-002 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | BASEMENT_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
2 | BASEMENT_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
3 | BASEMENT_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
4 | BASEMENT_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
5 | BASEMENT_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
6 | PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
7 | PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
8 | CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
9 | PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
10 | BASEMENT_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
11 | CORE_BOT_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
12 | CORE_BOT_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
13 | CORE_BOT_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
14 | CORE_BOT_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
15 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
16 | CORE_BOT_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
17 | CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
18 | CORE_BOTTOM_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
19 | CORE_MID_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
20 | CORE_MID_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
21 | CORE_MID_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
22 | CORE_MID_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
23 | CORE_MID_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
24 | CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
25 | CORE_MID_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
26 | CORE_TOP_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
27 | CORE_TOP_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
28 | CORE_TOP_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
29 | CORE_TOP_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
30 | CORE_TOP_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
31 | CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
32 | CORE_TOP_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
33 | PERIMETER_BOT_ZN_3_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
34 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
35 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
36 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
37 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
38 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
39 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
40 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
41 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
42 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
43 | PERIMETER_BOT_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
44 | CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
45 | PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
46 | DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
47 | PERIMETER_BOT_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
48 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
49 | PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
50 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
51 | PERIMETER_BOT_ZN_2_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
52 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
53 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
54 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
55 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
56 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
57 | PERIMETER_BOT_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
58 | CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
59 | PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
60 | PERIMETER_BOT_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
61 | PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
62 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
63 | PERIMETER_BOT_ZN_1_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
64 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
65 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
66 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
67 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
68 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
69 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
70 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
71 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
72 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
73 | PERIMETER_BOT_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
74 | DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
75 | PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
76 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
77 | DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
78 | PERIMETER_BOT_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
79 | PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
80 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
81 | PERIMETER_BOT_ZN_4_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
82 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
83 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
84 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
85 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
86 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
87 | PERIMETER_BOT_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
88 | DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
89 | PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
90 | PERIMETER_BOT_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
91 | PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
92 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
93 | PERIMETER_MID_ZN_3_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
94 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
95 | PERIMETER_MID_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
96 | CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
97 | PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
98 | DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
99 | PERIMETER_MID_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
100 | PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
101 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
102 | PERIMETER_MID_ZN_2_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
103 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
104 | PERIMETER_MID_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
105 | CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
106 | PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
107 | PERIMETER_MID_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
108 | PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
109 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
110 | PERIMETER_MID_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
111 | PERIMETER_MID_ZN_1_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
112 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
113 | DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
114 | PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
115 | CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
116 | PERIMETER_MID_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
117 | PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
118 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
119 | PERIMETER_MID_ZN_4_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
120 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
121 | PERIMETER_MID_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
122 | DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
123 | PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
124 | PERIMETER_MID_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
125 | PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
126 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
127 | PERIMETER_TOP_ZN_3_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
128 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
129 | PERIMETER_TOP_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
130 | CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
131 | PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
132 | DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
133 | PERIMETER_TOP_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
134 | PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
135 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
136 | PERIMETER_TOP_ZN_2_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
137 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
138 | PERIMETER_TOP_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
139 | CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
140 | INT-PER3S-NE-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
141 | PERIMETER_TOP_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
142 | PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
143 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
144 | PERIMETER_TOP_ZN_1_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
145 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
146 | INT-PER3S-NE | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
147 | DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
148 | PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
149 | CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
150 | PERIMETER_TOP_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
151 | PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
152 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
153 | PERIMETER_TOP_ZN_4_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
154 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
155 | PERIMETER_TOP_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
156 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
157 | PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
158 | PERIMETER_TOP_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
159 | PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
160 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
161 | GROUNDFLOOR_PLENUM_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
162 | GROUNDFLOOR_PLENUM_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
163 | GROUNDFLOOR_PLENUM_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
164 | GROUNDFLOOR_PLENUM_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
165 | iz-CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
166 | iz-PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
167 | iz-PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
168 | iz-PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
169 | iz-PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
170 | iz-DATACENTER_BOT_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
171 | GROUNDFLOOR_PLENUM_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
172 | MIDFLOOR_PLENUM_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
173 | MIDFLOOR_PLENUM_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
174 | MIDFLOOR_PLENUM_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
175 | MIDFLOOR_PLENUM_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
176 | iz-CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
177 | iz-PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
178 | iz-PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
179 | iz-PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
180 | iz-PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
181 | iz-DATACENTER_MID_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
182 | MIDFLOOR_PLENUM_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
183 | TOPFLOOR_PLENUM_WALL_NORTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
184 | TOPFLOOR_PLENUM_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
185 | TOPFLOOR_PLENUM_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
186 | TOPFLOOR_PLENUM_WALL_SOUTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
187 | iz-CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
188 | iz-PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
189 | iz-PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
190 | iz-PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
191 | iz-PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
192 | iz-DATACENTER_TOP_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
193 | BUILDING_ROOF | 0 | 3563.11 | 268.06 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
194 | DATACENTER_BOT_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
195 | DATACENTER_BOT_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
196 | DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
197 | DATACENTER_BOT_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
198 | DATACENTER_BOT_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
199 | DATACENTER_BOT_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
200 | DATACENTER_MID_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
201 | DATACENTER_MID_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
202 | DATACENTER_MID_ZN_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
203 | DATACENTER_MID_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
204 | DATACENTER_MID_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
205 | DATACENTER_MID_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
206 | DATACENTER_TOP_ZN_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
207 | DATACENTER_TOP_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
208 | DATACENTER_TOP_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
209 | DATACENTER_TOP_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
210 | DATACENTER_TOP_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
211 | DATACENTER_TOP_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
212 | DATACENTER_BASEMENT_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
213 | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
214 | DATACENTER_BASEMENT_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
215 | DATACENTER_BASEMENT_ZN_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
216 | DATACENTER_BASEMENT_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
217 | DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
218 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
219 | PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
220 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
221 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | PERIMETER_BOT_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 0.114 | 3.646E-004 | 5.482E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | PERIMETER_BOT_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 7.617E-002 | 3.771E-004 | 5.534E-004 | 0.495 | 0.000 | 0.000 | 0.224 | 0.000 |
3 | PERIMETER_BOT_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 0.114 | 3.646E-004 | 5.482E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | PERIMETER_BOT_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 7.617E-002 | 3.771E-004 | 5.534E-004 | 0.495 | 0.000 | 0.000 | 0.224 | 0.000 |
5 | PERIMETER_MID_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 0.114 | 3.646E-004 | 5.696E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
6 | PERIMETER_MID_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 7.617E-002 | 3.771E-004 | 5.696E-004 | 0.495 | 0.000 | 0.000 | 0.224 | 0.000 |
7 | PERIMETER_MID_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 0.114 | 3.646E-004 | 5.696E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
8 | PERIMETER_MID_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 7.617E-002 | 3.771E-004 | 5.696E-004 | 0.495 | 0.000 | 0.000 | 0.224 | 0.000 |
9 | PERIMETER_TOP_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 0.114 | 3.646E-004 | 5.696E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
10 | PERIMETER_TOP_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 7.617E-002 | 3.771E-004 | 5.696E-004 | 0.495 | 0.000 | 0.000 | 0.224 | 0.000 |
11 | PERIMETER_TOP_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 0.114 | 3.646E-004 | 5.696E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
12 | PERIMETER_TOP_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 7.617E-002 | 3.771E-004 | 5.696E-004 | 0.495 | 0.000 | 0.000 | 0.224 | 0.000 |
13 | GROUNDFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | GROUNDFLOOR_PLENUM | 3563.11 | 0.0 | 0.169 | 4.749E-005 | 5.696E-004 | 0.140 | 0.000 | 0.000 | 0.224 | 0.000 |
14 | MIDFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | MIDFLOOR_PLENUM | 3563.11 | 0.0 | 0.169 | 4.749E-005 | 5.696E-004 | 0.140 | 0.000 | 0.000 | 0.224 | 0.000 |
15 | TOPFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | TOPFLOOR_PLENUM | 3563.11 | 0.0 | 0.169 | 4.749E-005 | 4.384E-005 | 0.140 | 0.000 | 0.000 | 0.224 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | BASEMENT | Mixing/Well-Stirred |
2 | CORE_BOTTOM | Mixing/Well-Stirred |
3 | CORE_MID | Mixing/Well-Stirred |
4 | CORE_TOP | Mixing/Well-Stirred |
5 | PERIMETER_BOT_ZN_3 | Mixing/Well-Stirred |
6 | PERIMETER_BOT_ZN_2 | Mixing/Well-Stirred |
7 | PERIMETER_BOT_ZN_1 | Mixing/Well-Stirred |
8 | PERIMETER_BOT_ZN_4 | Mixing/Well-Stirred |
9 | PERIMETER_MID_ZN_3 | Mixing/Well-Stirred |
10 | PERIMETER_MID_ZN_2 | Mixing/Well-Stirred |
11 | PERIMETER_MID_ZN_1 | Mixing/Well-Stirred |
12 | PERIMETER_MID_ZN_4 | Mixing/Well-Stirred |
13 | PERIMETER_TOP_ZN_3 | Mixing/Well-Stirred |
14 | PERIMETER_TOP_ZN_2 | Mixing/Well-Stirred |
15 | PERIMETER_TOP_ZN_1 | Mixing/Well-Stirred |
16 | PERIMETER_TOP_ZN_4 | Mixing/Well-Stirred |
17 | GROUNDFLOOR_PLENUM | Mixing/Well-Stirred |
18 | MIDFLOOR_PLENUM | Mixing/Well-Stirred |
19 | TOPFLOOR_PLENUM | Mixing/Well-Stirred |
20 | DATACENTER_BOT_ZN_6 | Mixing/Well-Stirred |
21 | DATACENTER_MID_ZN_6 | Mixing/Well-Stirred |
22 | DATACENTER_TOP_ZN_6 | Mixing/Well-Stirred |
23 | DATACENTER_BASEMENT_ZN_6 | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sky Type | MonthAndDay | Daylighting Control Name | Enclosure Name | Window Name | Reference Point | Daylight Factor | |
1 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.0259E-003 |
2 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.0273E-003 |
3 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.3141E-003 |
4 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.3153E-003 |
5 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 3.0965E-003 |
6 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 3.0973E-003 |
7 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.7585E-003 |
8 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.7591E-003 |
9 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.0574E-003 |
10 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.1444E-003 |
11 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.3398E-003 |
12 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.4126E-003 |
13 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 3.1170E-003 |
14 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 3.1771E-003 |
15 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.7734E-003 |
16 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.8107E-003 |
17 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 0.1021 |
18 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.3682E-002 |
19 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 0.1138 |
20 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.7418E-002 |
21 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 7.6268E-002 |
22 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.8697E-002 |
23 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 3.1622E-002 |
24 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.0968E-002 |
25 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.0671E-003 |
26 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.1932E-003 |
27 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.3504E-003 |
28 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.4660E-003 |
29 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 3.1262E-003 |
30 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 3.2121E-003 |
31 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.7738E-003 |
32 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.8117E-003 |
33 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.0258E-003 |
34 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.0275E-003 |
35 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.3141E-003 |
36 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.3155E-003 |
37 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 3.0965E-003 |
38 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 3.0976E-003 |
39 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.7585E-003 |
40 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.7590E-003 |
41 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 4.2034E-003 |
42 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 4.3976E-003 |
43 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 4.0891E-003 |
44 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 4.2986E-003 |
45 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.7560E-003 |
46 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.8453E-003 |
47 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.0071E-003 |
48 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.0329E-003 |
49 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 4.8886E-002 |
50 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 2.2855E-002 |
51 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 4.7304E-002 |
52 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 2.1359E-002 |
53 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 4.6131E-002 |
54 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 1.8727E-002 |
55 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.2931E-002 |
56 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 1.2292E-002 |
57 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 4.1558E-003 |
58 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 4.2209E-003 |
59 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 4.0290E-003 |
60 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 4.0768E-003 |
61 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.7295E-003 |
62 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.7504E-003 |
63 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.0072E-003 |
64 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.0333E-003 |
65 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.7686E-003 |
66 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.7701E-003 |
67 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.5140E-003 |
68 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.5153E-003 |
69 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.3517E-003 |
70 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.3527E-003 |
71 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.7586E-003 |
72 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.7591E-003 |
73 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.8023E-003 |
74 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.8840E-003 |
75 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.5421E-003 |
76 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.6080E-003 |
77 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.3751E-003 |
78 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.4258E-003 |
79 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.7738E-003 |
80 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.8118E-003 |
81 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.7628E-002 |
82 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.4405E-002 |
83 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.1316E-002 |
84 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.0970E-002 |
85 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.9365E-002 |
86 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 7.5418E-003 |
87 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.1622E-002 |
88 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.0965E-002 |
89 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.7994E-003 |
90 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.8819E-003 |
91 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.5381E-003 |
92 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.6009E-003 |
93 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.3680E-003 |
94 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.4040E-003 |
95 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.7735E-003 |
96 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.8107E-003 |
97 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.7685E-003 |
98 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.7698E-003 |
99 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.5139E-003 |
100 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.5150E-003 |
101 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.3516E-003 |
102 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.3523E-003 |
103 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.7585E-003 |
104 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.7591E-003 |
105 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.3341E-003 |
106 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.4039E-003 |
107 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.0182E-003 |
108 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.0684E-003 |
109 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.0210E-003 |
110 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.0389E-003 |
111 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.0073E-003 |
112 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.0334E-003 |
113 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.4499E-002 |
114 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 1.7374E-002 |
115 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 2.9738E-002 |
116 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 1.4668E-002 |
117 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.3111E-002 |
118 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 1.3713E-002 |
119 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.2931E-002 |
120 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 1.2292E-002 |
121 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.3670E-003 |
122 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.4949E-003 |
123 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.0607E-003 |
124 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.1879E-003 |
125 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.0449E-003 |
126 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.1184E-003 |
127 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.0071E-003 |
128 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.0328E-003 |
129 | Clear Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 0.1095 |
130 | Clear Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 6.3135E-002 |
131 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 0.1199 |
132 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 6.8227E-002 |
133 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 8.5681E-002 |
134 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 4.3320E-002 |
135 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 3.8788E-002 |
136 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 1.9168E-002 |
137 | Clear Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 5.7944E-002 |
138 | Clear Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 3.2907E-002 |
139 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 5.6194E-002 |
140 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 3.1160E-002 |
141 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 5.4533E-002 |
142 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 2.7624E-002 |
143 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 3.9762E-002 |
144 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 1.9389E-002 |
145 | Clear Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 3.4617E-002 |
146 | Clear Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 2.2921E-002 |
147 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 2.7441E-002 |
148 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 1.8209E-002 |
149 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 2.5264E-002 |
150 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 1.3896E-002 |
151 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 3.8788E-002 |
152 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 1.9165E-002 |
153 | Clear Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 4.1681E-002 |
154 | Clear Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 2.5356E-002 |
155 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 3.6323E-002 |
156 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 2.1920E-002 |
157 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 3.9926E-002 |
158 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 2.0905E-002 |
159 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 3.9762E-002 |
160 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 1.9389E-002 |
161 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 0.1096 |
162 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 6.3276E-002 |
163 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 0.1200 |
164 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 6.8389E-002 |
165 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 8.5825E-002 |
166 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 4.3430E-002 |
167 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 3.8871E-002 |
168 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 1.9210E-002 |
169 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 5.7999E-002 |
170 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 3.2961E-002 |
171 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 5.6258E-002 |
172 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 3.1214E-002 |
173 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 5.4623E-002 |
174 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 2.7684E-002 |
175 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 3.9845E-002 |
176 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 1.9432E-002 |
177 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 3.4622E-002 |
178 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 2.2947E-002 |
179 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 2.7448E-002 |
180 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 1.8229E-002 |
181 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 2.5305E-002 |
182 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 1.3921E-002 |
183 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 3.8871E-002 |
184 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 1.9207E-002 |
185 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 4.1705E-002 |
186 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 2.5391E-002 |
187 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 3.6349E-002 |
188 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 2.1951E-002 |
189 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 3.9990E-002 |
190 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 2.0947E-002 |
191 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 3.9845E-002 |
192 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 1.9432E-002 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | BASEMENT | Cooling | 81476.79981 | 81476.79981 | 6.08611 | 6.08611 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 27.37000 | 1.44605E-002 | 2779.42662 | 149.60210 | 1.20016 | 0.00000 |
2 | BASEMENT | Heating | 0.00000 | 0.00000 | 0.00000 | 1.20016 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:10:00 | -6.30000 | 2.29779E-003 | 2779.42662 | 149.60210 | 1.20016 | 0.00000 |
3 | CORE_BOTTOM | Cooling | 84977.64863 | 84977.64863 | 6.34708 | 6.34708 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 27.37000 | 1.44605E-002 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 |
4 | CORE_BOTTOM | Heating | 0.00000 | 0.00000 | 0.00000 | 1.07782 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 05:50:00 | -6.30000 | 2.29779E-003 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 |
5 | CORE_MID | Cooling | 803073.62031 | 803073.62031 | 59.96899 | 59.96899 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 27.37000 | 1.44605E-002 | 2496.12046 | 134.35320 | 10.77825 | 0.00000 |
6 | CORE_MID | Heating | 275723.61336 | 275723.61336 | 12.05844 | 12.05844 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -6.30000 | 2.29779E-003 | 2496.12046 | 134.35320 | 10.77825 | 0.00000 |
7 | CORE_TOP | Cooling | 79160.97142 | 79160.97142 | 5.91108 | 5.91108 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 27.37000 | 1.44605E-002 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 |
8 | CORE_TOP | Heating | 60293.16614 | 60293.16614 | 2.65737 | 2.65737 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -6.30000 | 2.29779E-003 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 |
9 | PERIMETER_BOT_ZN_3 | Cooling | 14184.52619 | 14184.52619 | 1.06896 | 1.06896 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | 34.40000 | 1.44733E-002 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
10 | PERIMETER_BOT_ZN_3 | Heating | 10461.87834 | 10461.87834 | 0.46182 | 0.46182 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -6.30000 | 2.29779E-003 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
11 | PERIMETER_BOT_ZN_2 | Cooling | 14680.43792 | 14680.43792 | 1.10633 | 1.10633 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:50:00 | 30.52083 | 1.44662E-002 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
12 | PERIMETER_BOT_ZN_2 | Heating | 7153.34481 | 7153.34481 | 0.31584 | 0.31584 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -6.30000 | 2.29779E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
13 | PERIMETER_BOT_ZN_1 | Cooling | 16633.14454 | 16633.14454 | 1.25349 | 1.25349 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 34.24167 | 1.44730E-002 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
14 | PERIMETER_BOT_ZN_1 | Heating | 11605.04676 | 11605.04676 | 0.51247 | 0.51247 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -6.30000 | 2.29779E-003 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
15 | PERIMETER_BOT_ZN_4 | Cooling | 18514.73939 | 18514.73939 | 1.39528 | 1.39528 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 | 32.91167 | 1.44705E-002 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
16 | PERIMETER_BOT_ZN_4 | Heating | 5582.07505 | 5582.07505 | 0.24619 | 0.24619 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -6.30000 | 2.29779E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
17 | PERIMETER_MID_ZN_3 | Cooling | 134507.14604 | 134507.14604 | 10.13720 | 10.13720 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 34.40000 | 1.44733E-002 | 313.41284 | 16.86939 | 1.35332 | 0.00000 |
18 | PERIMETER_MID_ZN_3 | Heating | 171564.19834 | 171564.19834 | 7.58569 | 7.58569 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -6.30000 | 2.29779E-003 | 313.41284 | 16.86939 | 1.35332 | 0.00000 |
19 | PERIMETER_MID_ZN_2 | Cooling | 151996.01979 | 151996.01979 | 11.45518 | 11.45518 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:00:00 | 30.79000 | 1.44667E-002 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
20 | PERIMETER_MID_ZN_2 | Heating | 112279.74863 | 112279.74863 | 4.96462 | 4.96462 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -6.30000 | 2.29779E-003 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
21 | PERIMETER_MID_ZN_1 | Cooling | 158866.10754 | 158866.10754 | 11.97300 | 11.97300 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | 34.32083 | 1.44731E-002 | 313.41969 | 16.86975 | 1.35335 | 0.00000 |
22 | PERIMETER_MID_ZN_1 | Heating | 169162.05030 | 169162.05030 | 7.47919 | 7.47919 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -6.30000 | 2.29779E-003 | 313.41969 | 16.86975 | 1.35335 | 0.00000 |
23 | PERIMETER_MID_ZN_4 | Cooling | 161161.06551 | 161161.06551 | 12.14587 | 12.14587 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:20:00 | 32.75333 | 1.44703E-002 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
24 | PERIMETER_MID_ZN_4 | Heating | 109094.22645 | 109094.22645 | 4.82343 | 4.82343 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -6.30000 | 2.29779E-003 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
25 | PERIMETER_TOP_ZN_3 | Cooling | 15153.30497 | 15153.30497 | 1.14206 | 1.14206 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | 34.21000 | 1.44729E-002 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
26 | PERIMETER_TOP_ZN_3 | Heating | 21499.98515 | 21499.98515 | 0.95109 | 0.95109 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -6.30000 | 2.29779E-003 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
27 | PERIMETER_TOP_ZN_2 | Cooling | 15453.40460 | 15453.40460 | 1.16467 | 1.16467 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:10:00 | 31.02750 | 1.44671E-002 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
28 | PERIMETER_TOP_ZN_2 | Heating | 14027.21866 | 14027.21866 | 0.62053 | 0.62053 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -6.30000 | 2.29779E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
29 | PERIMETER_TOP_ZN_1 | Cooling | 17468.40261 | 17468.40261 | 1.31654 | 1.31654 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | 34.40000 | 1.44733E-002 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
30 | PERIMETER_TOP_ZN_1 | Heating | 21243.92356 | 21243.92356 | 0.93974 | 0.93974 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -6.30000 | 2.29779E-003 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
31 | PERIMETER_TOP_ZN_4 | Cooling | 17221.06978 | 17221.06978 | 1.29789 | 1.29789 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:20:00 | 32.75333 | 1.44703E-002 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
32 | PERIMETER_TOP_ZN_4 | Heating | 13827.72071 | 13827.72071 | 0.61169 | 0.61169 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -6.30000 | 2.29779E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
33 | DATACENTER_BOT_ZN_6 | Cooling | 8280.15536 | 8280.15536 | 0.49216 | 0.49216 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:10:00 | 30.52083 | 1.44662E-002 | 36.20274 | 1.94861 | 1.56323E-002 | 0.00000 |
34 | DATACENTER_BOT_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 1.56323E-002 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 05:40:00 | -6.30000 | 2.29779E-003 | 36.20274 | 1.94861 | 1.56323E-002 | 0.00000 |
35 | DATACENTER_MID_ZN_6 | Cooling | 78935.51948 | 78935.51948 | 4.69180 | 4.69180 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:10:00 | 30.52083 | 1.44662E-002 | 36.20274 | 1.94861 | 0.15632 | 0.00000 |
36 | DATACENTER_MID_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 0.15632 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 05:40:00 | -6.30000 | 2.29779E-003 | 36.20274 | 1.94861 | 0.15632 | 0.00000 |
37 | DATACENTER_TOP_ZN_6 | Cooling | 8040.96317 | 8040.96317 | 0.47794 | 0.47794 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 30.69500 | 1.44665E-002 | 36.20274 | 1.94861 | 1.56323E-002 | 0.00000 |
38 | DATACENTER_TOP_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 1.56323E-002 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 05:40:00 | -6.30000 | 2.29779E-003 | 36.20274 | 1.94861 | 1.56323E-002 | 0.00000 |
39 | DATACENTER_BASEMENT_ZN_6 | Cooling | 372434.49124 | 372434.49124 | 22.13638 | 22.13638 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 07:00:00 | 25.75500 | 1.44575E-002 | 783.67941 | 42.18139 | 0.33839 | 0.00000 |
40 | DATACENTER_BASEMENT_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 0.33839 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 00:50:00 | -6.30000 | 2.29779E-003 | 783.67941 | 42.18139 | 0.33839 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | VAV_BOT WITH REHEAT | Cooling | Sensible | 158173.35 | 10.07599 | 10.07599 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
2 | VAV_BOT WITH REHEAT | Heating | Sensible | 56601.28 | 2.61415 | 2.61415 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 |
3 | VAV_MID WITH REHEAT | Cooling | Sensible | 1462716.08 | 94.03603 | 94.03603 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
4 | VAV_MID WITH REHEAT | Heating | Sensible | 561825.29 | 36.91136 | 36.91136 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 06:20:00 |
5 | VAV_TOP WITH REHEAT | Cooling | Sensible | 163249.97 | 10.19790 | 10.19790 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
6 | VAV_TOP WITH REHEAT | Heating | Sensible | 56440.70 | 5.78042 | 5.78042 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 05:40:00 |
7 | CAV_BAS | Cooling | Sensible | 84679.67 | 6.08611 | 6.08611 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
8 | CAV_BAS | Heating | Sensible | 64825.70 | 1.20016 | 1.20016 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
9 | AIRLOOP DATACENTER BASEMENT | Cooling | Sensible | 369106.53 | 22.13657 | 22.13657 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
10 | AIRLOOP DATACENTER BASEMENT | Heating | Sensible | 18278.08 | 0.33839 | 0.33839 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
11 | AIRLOOP DATACENTER BOT | Cooling | Sensible | 8217.92 | 0.49216 | 0.49216 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
12 | AIRLOOP DATACENTER BOT | Heating | Sensible | 844.37 | 1.56323E-002 | 1.56323E-002 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
13 | AIRLOOP DATACENTER MID | Cooling | Sensible | 78357.32 | 4.69180 | 4.69180 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
14 | AIRLOOP DATACENTER MID | Heating | Sensible | 8443.71 | 0.15632 | 0.15632 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
15 | AIRLOOP DATACENTER TOP | Cooling | Sensible | 7984.04 | 0.47794 | 0.47794 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
16 | AIRLOOP DATACENTER TOP | Heating | Sensible | 844.37 | 1.56323E-002 | 1.56323E-002 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | BASEMENT DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 6.08611 |
2 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 6.34708 |
3 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.29967 |
4 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30800 |
5 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.95490 |
6 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.79913 |
7 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
8 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.27139E-003 |
9 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.66024E-004 |
10 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.95490 |
11 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
12 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
13 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 18977.52327 |
14 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.66024E-004 |
15 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 382.57197 |
16 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 59.96899 |
17 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.31717 |
18 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.32000 |
19 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 19.19008 |
20 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.84579 |
21 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
22 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.20124E-003 |
23 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 4.04190E-003 |
24 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 19.19008 |
25 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
26 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
27 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 462014.39680 |
28 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 4.04190E-003 |
29 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 10929.40925 |
30 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 5.91108 |
31 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.32178 |
32 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.33200 |
33 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.96248 |
34 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.85807 |
35 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
36 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.18405E-003 |
37 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 7.53153E-004 |
38 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 2.65737 |
39 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
40 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
41 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 86090.01699 |
42 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 7.53153E-004 |
43 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 2272.77242 |
44 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.06896 |
45 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.22341 |
46 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.23000 |
47 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.24586 |
48 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.59577 |
49 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
50 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.70536E-003 |
51 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.30696E-004 |
52 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.46182 |
53 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
54 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
55 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 14939.36917 |
56 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.30696E-004 |
57 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 394.13330 |
58 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.10633 |
59 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.13911 |
60 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
61 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.22127 |
62 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.37097 |
63 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
64 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.73878E-003 |
65 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 8.93727E-005 |
66 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.31584 |
67 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
68 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
69 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 10215.84741 |
70 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 8.93727E-005 |
71 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 269.49956 |
72 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.25349 |
73 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.19053 |
74 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
75 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.25070 |
76 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.50808 |
77 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
78 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.99970E-003 |
79 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.45003E-004 |
80 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.51247 |
81 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
82 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
83 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 16574.75910 |
84 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.45003E-004 |
85 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 437.23781 |
86 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.39528 |
87 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.11030 |
88 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
89 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.27906 |
90 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
91 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
92 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.45408E-003 |
93 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 7.24903E-005 |
94 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.27906 |
95 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
96 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
97 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 8286.08256 |
98 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 7.24903E-005 |
99 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 210.73941 |
100 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 10.13720 |
101 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.23559 |
102 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.23800 |
103 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.41265 |
104 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.62824 |
105 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
106 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.61723E-003 |
107 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.14427E-003 |
108 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 7.58569 |
109 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
110 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
111 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 245103.78299 |
112 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.14427E-003 |
113 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 6462.91470 |
114 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 11.45518 |
115 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.13435 |
116 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
117 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.29104 |
118 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.35828 |
119 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
120 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.83579E-003 |
121 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.40332E-003 |
122 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 4.96462 |
123 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
124 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
125 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 160408.19580 |
126 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.40332E-003 |
127 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 4229.59316 |
128 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 11.97300 |
129 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.19947 |
130 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20100 |
131 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.40657 |
132 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.53192 |
133 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
134 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.91006E-003 |
135 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.11422E-003 |
136 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 7.47919 |
137 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
138 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
139 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 241668.01381 |
140 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.11422E-003 |
141 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 6372.38706 |
142 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 12.14587 |
143 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.12671 |
144 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
145 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.42917 |
146 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.33790 |
147 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
148 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.00677E-003 |
149 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.36346E-003 |
150 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 4.82343 |
151 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
152 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
153 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 155852.34939 |
154 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.36346E-003 |
155 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 4109.53748 |
156 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.14206 |
157 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.20911 |
158 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.21600 |
159 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.24668 |
160 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.55764 |
161 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
162 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.82197E-003 |
163 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.68752E-004 |
164 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.95109 |
165 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
166 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
167 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 30720.04645 |
168 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.68752E-004 |
169 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 809.89700 |
170 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.16467 |
171 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.13214 |
172 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
173 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.23293 |
174 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.35239 |
175 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
176 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.88321E-003 |
177 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.75341E-004 |
178 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.62053 |
179 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
180 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
181 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 20042.60938 |
182 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.75341E-004 |
183 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 528.39361 |
184 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.31654 |
185 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.18140 |
186 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
187 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.26331 |
188 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.48375 |
189 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
190 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.10028E-003 |
191 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.65549E-004 |
192 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.93974 |
193 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
194 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
195 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 30353.82930 |
196 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.65549E-004 |
197 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 800.24768 |
198 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.29789 |
199 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.11858 |
200 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
201 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.25958 |
202 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.31622 |
203 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
204 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.21299E-003 |
205 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.72846E-004 |
206 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.61169 |
207 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
208 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
209 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 19757.33927 |
210 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.72846E-004 |
211 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 520.87525 |
212 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DATACENTER_BOT_ZN_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.49216 |
213 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DATACENTER_MID_ZN_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 4.69180 |
214 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DATACENTER_TOP_ZN_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.47794 |
215 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DATACENTER_BASEMENT_ZN_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 22.13638 |
216 | AirLoopHVAC | VAV_BOT WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 5.58557 |
217 | AirLoopHVAC | VAV_BOT WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.95178 |
218 | AirLoopHVAC | VAV_BOT WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 11.17115 |
219 | AirLoopHVAC | VAV_BOT WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 2.95178 |
220 | AirLoopHVAC | VAV_BOT WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 10.07599 |
221 | AirLoopHVAC | VAV_BOT WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 10.07599 |
222 | AirLoopHVAC | VAV_BOT WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
223 | AirLoopHVAC | VAV_BOT WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.29295 |
224 | AirLoopHVAC | VAV_MID WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 52.84012 |
225 | AirLoopHVAC | VAV_MID WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 28.72951 |
226 | AirLoopHVAC | VAV_MID WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 105.68024 |
227 | AirLoopHVAC | VAV_MID WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 36.91136 |
228 | AirLoopHVAC | VAV_MID WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 94.03603 |
229 | AirLoopHVAC | VAV_MID WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 94.03603 |
230 | AirLoopHVAC | VAV_MID WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
231 | AirLoopHVAC | VAV_MID WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.39252 |
232 | AirLoopHVAC | VAV_TOP WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 5.41612 |
233 | AirLoopHVAC | VAV_TOP WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.96498 |
234 | AirLoopHVAC | VAV_TOP WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 10.83224 |
235 | AirLoopHVAC | VAV_TOP WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 5.78042 |
236 | AirLoopHVAC | VAV_TOP WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 10.19790 |
237 | AirLoopHVAC | VAV_TOP WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 10.19790 |
238 | AirLoopHVAC | VAV_TOP WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
239 | AirLoopHVAC | VAV_TOP WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.56682 |
240 | AirLoopHVAC | CAV_BAS | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 6.08611 |
241 | AirLoopHVAC | CAV_BAS | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 6.08611 |
242 | AirLoopHVAC | CAV_BAS | Sum of Air Terminal Maximum Flow Rates [m3/s] | 6.08611 |
243 | AirLoopHVAC | CAV_BAS | Adjusted Heating Design Air Flow Rate [m3/s] | 6.08611 |
244 | AirLoopHVAC | CAV_BAS | Adjusted Cooling Design Air Flow Rate [m3/s] | 6.08611 |
245 | AirLoopHVAC | CAV_BAS | Adjusted Main Design Air Flow Rate [m3/s] | 6.08611 |
246 | AirLoopHVAC | CAV_BAS | User Heating Air Flow Ratio [] | 1.00000 |
247 | AirLoopHVAC | CAV_BAS | Calculated Heating Air Flow Ratio [] | 1.00000 |
248 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 22.13638 |
249 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 22.13638 |
250 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 22.13638 |
251 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Adjusted Heating Design Air Flow Rate [m3/s] | 22.13638 |
252 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Adjusted Cooling Design Air Flow Rate [m3/s] | 22.13657 |
253 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Adjusted Main Design Air Flow Rate [m3/s] | 22.13657 |
254 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | User Heating Air Flow Ratio [] | 1.00000 |
255 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Calculated Heating Air Flow Ratio [] | 0.99999 |
256 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.49216 |
257 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.49216 |
258 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.49216 |
259 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Adjusted Heating Design Air Flow Rate [m3/s] | 0.49216 |
260 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.49216 |
261 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Adjusted Main Design Air Flow Rate [m3/s] | 0.49216 |
262 | AirLoopHVAC | AIRLOOP DATACENTER BOT | User Heating Air Flow Ratio [] | 1.00000 |
263 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Calculated Heating Air Flow Ratio [] | 1.00000 |
264 | AirLoopHVAC | AIRLOOP DATACENTER MID | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 4.69180 |
265 | AirLoopHVAC | AIRLOOP DATACENTER MID | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 4.69180 |
266 | AirLoopHVAC | AIRLOOP DATACENTER MID | Sum of Air Terminal Maximum Flow Rates [m3/s] | 4.69180 |
267 | AirLoopHVAC | AIRLOOP DATACENTER MID | Adjusted Heating Design Air Flow Rate [m3/s] | 4.69180 |
268 | AirLoopHVAC | AIRLOOP DATACENTER MID | Adjusted Cooling Design Air Flow Rate [m3/s] | 4.69180 |
269 | AirLoopHVAC | AIRLOOP DATACENTER MID | Adjusted Main Design Air Flow Rate [m3/s] | 4.69180 |
270 | AirLoopHVAC | AIRLOOP DATACENTER MID | User Heating Air Flow Ratio [] | 1.00000 |
271 | AirLoopHVAC | AIRLOOP DATACENTER MID | Calculated Heating Air Flow Ratio [] | 1.00000 |
272 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.47794 |
273 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.47794 |
274 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.47794 |
275 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Adjusted Heating Design Air Flow Rate [m3/s] | 0.47794 |
276 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.47794 |
277 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Adjusted Main Design Air Flow Rate [m3/s] | 0.47794 |
278 | AirLoopHVAC | AIRLOOP DATACENTER TOP | User Heating Air Flow Ratio [] | 1.00000 |
279 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Calculated Heating Air Flow Ratio [] | 1.00000 |
280 | AirLoopHVAC | VAV_BOT WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 10.07599 |
281 | AirLoopHVAC | VAV_MID WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 94.03603 |
282 | AirLoopHVAC | VAV_TOP WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 10.19790 |
283 | AirLoopHVAC | CAV_BAS | Design Supply Air Flow Rate [m3/s] | 6.08611 |
284 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Design Supply Air Flow Rate [m3/s] | 22.13657 |
285 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Design Supply Air Flow Rate [m3/s] | 0.49216 |
286 | AirLoopHVAC | AIRLOOP DATACENTER MID | Design Supply Air Flow Rate [m3/s] | 4.69180 |
287 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Design Supply Air Flow Rate [m3/s] | 0.47794 |
288 | Controller:OutdoorAir | VAV_BOT WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 10.07599 |
289 | Controller:OutdoorAir | VAV_BOT WITH REHEAT_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 2.53819 |
290 | HeatExchanger:AirToAir:SensibleAndLatent | VAV_BOT WITH REHEAT OA HEAT RECOVERY | Design Size Nominal Supply Air Flow Rate [m3/s] | 2.53819 |
291 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Inlet Air Temperature [C] | 26.70645 |
292 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
293 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Outlet Air Temperature [C] | 10.99205 |
294 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 1.03322E-002 |
295 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
296 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Coil Load [W] | 242286.81281 |
297 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 1.03074E-002 |
298 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 10.07599 |
299 | Coil:Heating:Water | VAV_BOT WITH REHEAT HEATING COIL | Design Size Rated Capacity [W] | 56839.84829 |
300 | Coil:Heating:Water | VAV_BOT WITH REHEAT HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 4.97260E-004 |
301 | Coil:Heating:Water | VAV_BOT WITH REHEAT HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 935.40172 |
302 | Fan:VariableVolume | VAV_BOT WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 10.07599 |
303 | Controller:WaterCoil | VAV_BOT WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 1.03074E-002 |
304 | Controller:WaterCoil | VAV_BOT WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 4.61987E-005 |
305 | Controller:WaterCoil | VAV_BOT WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 4.97260E-004 |
306 | Controller:OutdoorAir | VAV_MID WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 94.03603 |
307 | Controller:OutdoorAir | VAV_MID WITH REHEAT_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 25.38195 |
308 | HeatExchanger:AirToAir:SensibleAndLatent | VAV_MID WITH REHEAT OA HEAT RECOVERY | Design Size Nominal Supply Air Flow Rate [m3/s] | 25.38195 |
309 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Inlet Air Temperature [C] | 26.98529 |
310 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
311 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Outlet Air Temperature [C] | 10.98312 |
312 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 1.05527E-002 |
313 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
314 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Coil Load [W] | 2354776.14956 |
315 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 0.10018 |
316 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 94.03603 |
317 | Coil:Heating:Water | VAV_MID WITH REHEAT HEATING COIL | Design Size Rated Capacity [W] | 544940.17353 |
318 | Coil:Heating:Water | VAV_MID WITH REHEAT HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 4.76737E-003 |
319 | Coil:Heating:Water | VAV_MID WITH REHEAT HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 8945.37805 |
320 | Fan:VariableVolume | VAV_MID WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 94.03603 |
321 | Controller:WaterCoil | VAV_MID WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 0.10018 |
322 | Controller:WaterCoil | VAV_MID WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 4.75346E-006 |
323 | Controller:WaterCoil | VAV_MID WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 4.76737E-003 |
324 | Controller:OutdoorAir | VAV_TOP WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 10.19790 |
325 | Controller:OutdoorAir | VAV_TOP WITH REHEAT_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 2.53819 |
326 | HeatExchanger:AirToAir:SensibleAndLatent | VAV_TOP WITH REHEAT OA HEAT RECOVERY | Design Size Nominal Supply Air Flow Rate [m3/s] | 2.53819 |
327 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Inlet Air Temperature [C] | 26.60232 |
328 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
329 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Outlet Air Temperature [C] | 10.99201 |
330 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 1.03218E-002 |
331 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
332 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Coil Load [W] | 243642.38479 |
333 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 1.03651E-002 |
334 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 10.19790 |
335 | Coil:Heating:Water | VAV_TOP WITH REHEAT HEATING COIL | Design Size Rated Capacity [W] | 53637.38768 |
336 | Coil:Heating:Water | VAV_TOP WITH REHEAT HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 4.69243E-004 |
337 | Coil:Heating:Water | VAV_TOP WITH REHEAT HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 888.20229 |
338 | Fan:VariableVolume | VAV_TOP WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 10.19790 |
339 | Controller:WaterCoil | VAV_TOP WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 1.03651E-002 |
340 | Controller:WaterCoil | VAV_TOP WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 4.59417E-005 |
341 | Controller:WaterCoil | VAV_TOP WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 4.69243E-004 |
342 | Controller:OutdoorAir | CAV_BAS_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 6.08611 |
343 | Controller:OutdoorAir | CAV_BAS_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.20016 |
344 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Inlet Air Temperature [C] | 24.78600 |
345 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
346 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Outlet Air Temperature [C] | 11.37296 |
347 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 1.00248E-002 |
348 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
349 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Coil Load [W] | 124171.22380 |
350 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 5.28253E-003 |
351 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 6.08611 |
352 | Coil:Heating:Water | CAV_BAS HEATING COIL | Design Size Rated Capacity [W] | 292827.05549 |
353 | Coil:Heating:Water | CAV_BAS HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.56178E-003 |
354 | Coil:Heating:Water | CAV_BAS HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 6501.96253 |
355 | Fan:ConstantVolume | CAV_BAS FAN | Design Size Maximum Flow Rate [m3/s] | 6.08611 |
356 | Controller:WaterCoil | CAV_BAS_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 5.28253E-003 |
357 | Controller:WaterCoil | CAV_BAS_COOLC_CONTROLLER | Controller Convergence Tolerance | 9.01444E-005 |
358 | Controller:WaterCoil | CAV_BAS_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 2.56178E-003 |
359 | Controller:OutdoorAir | AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 22.13657 |
360 | Controller:OutdoorAir | AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.33839 |
361 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 22.13657 |
362 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Rated Total Cooling Capacity [W] | 438414.06316 |
363 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Rated Sensible Cooling Capacity [W] | 303822.62253 |
364 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Rated Water Flow Rate [m3/s] | 1.07367E-002 |
365 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 22.13657 |
366 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 22.13657 |
367 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 22.13657 |
368 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 22.13657 |
369 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Nominal Heating Capacity [W] | 438414.06316 |
370 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 438414.06316 |
371 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 18278.07505 |
372 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
373 | Fan:OnOff | AIRLOOP DATACENTER BASEMENT SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 22.13657 |
374 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 22.13657 |
375 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT HEATING COIL | Design Size Rated Heating Capacity [W] | 438414.06316 |
376 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT HEATING COIL | Design Size Rated Water Flow Rate [m3/s] | 1.07367E-002 |
377 | Coil:Heating:Electric | AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 18278.07505 |
378 | Humidifier:Steam:Electric | DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | Design Size Nominal Capacity Volume [m3/s] | 1.53403E-004 |
379 | Humidifier:Steam:Electric | DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | User-Specified Nominal Capacity Volume [m3/s] | 3.72000E-005 |
380 | Humidifier:Steam:Electric | DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | Design Size Rated Power [W] | 96450.69782 |
381 | Humidifier:Steam:Electric | DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | User-Specified Rated Power [W] | 100000.00000 |
382 | Controller:OutdoorAir | AIRLOOP DATACENTER BOT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.49216 |
383 | Controller:OutdoorAir | AIRLOOP DATACENTER BOT_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.56323E-002 |
384 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.49216 |
385 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT COOLING COIL | Design Size Rated Total Cooling Capacity [W] | 9691.18057 |
386 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT COOLING COIL | Design Size Rated Sensible Cooling Capacity [W] | 6727.90539 |
387 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT COOLING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.37336E-004 |
388 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 0.49216 |
389 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 0.49216 |
390 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 0.49216 |
391 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 0.49216 |
392 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Nominal Heating Capacity [W] | 9691.18057 |
393 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 9691.18057 |
394 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 844.37135 |
395 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
396 | Fan:OnOff | AIRLOOP DATACENTER BOT SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.49216 |
397 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.49216 |
398 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT HEATING COIL | Design Size Rated Heating Capacity [W] | 9691.18057 |
399 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT HEATING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.37336E-004 |
400 | Coil:Heating:Electric | AIRLOOP DATACENTER BOT_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 844.37135 |
401 | Controller:OutdoorAir | AIRLOOP DATACENTER MID_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 4.69180 |
402 | Controller:OutdoorAir | AIRLOOP DATACENTER MID_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.15632 |
403 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 4.69180 |
404 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID COOLING COIL | Design Size Rated Total Cooling Capacity [W] | 92549.83409 |
405 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID COOLING COIL | Design Size Rated Sensible Cooling Capacity [W] | 64188.78238 |
406 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID COOLING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.26654E-003 |
407 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 4.69180 |
408 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 4.69180 |
409 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 4.69180 |
410 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 4.69180 |
411 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Nominal Heating Capacity [W] | 92549.83409 |
412 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 92549.83409 |
413 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 8443.71345 |
414 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
415 | Fan:OnOff | AIRLOOP DATACENTER MID SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 4.69180 |
416 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 4.69180 |
417 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID HEATING COIL | Design Size Rated Heating Capacity [W] | 92549.83409 |
418 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID HEATING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.26654E-003 |
419 | Coil:Heating:Electric | AIRLOOP DATACENTER MID_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 8443.71345 |
420 | Controller:OutdoorAir | AIRLOOP DATACENTER TOP_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.47794 |
421 | Controller:OutdoorAir | AIRLOOP DATACENTER TOP_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.56323E-002 |
422 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.47794 |
423 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP COOLING COIL | Design Size Rated Total Cooling Capacity [W] | 9422.96064 |
424 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP COOLING COIL | Design Size Rated Sensible Cooling Capacity [W] | 6537.25476 |
425 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP COOLING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.30768E-004 |
426 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 0.47794 |
427 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 0.47794 |
428 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 0.47794 |
429 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 0.47794 |
430 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Nominal Heating Capacity [W] | 9422.96064 |
431 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 9422.96064 |
432 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 844.37135 |
433 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
434 | Fan:OnOff | AIRLOOP DATACENTER TOP SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.47794 |
435 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.47794 |
436 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP HEATING COIL | Design Size Rated Heating Capacity [W] | 9422.96064 |
437 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP HEATING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.30768E-004 |
438 | Coil:Heating:Electric | AIRLOOP DATACENTER TOP_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 844.37135 |
439 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Flow Rate [m3/s] | 0.12613 |
440 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Power Consumption [W] | 20593.61625 |
441 | PlantLoop | COOLSYS1_DEMAND | Maximum Loop Flow Rate [m3/s] | 0.12613 |
442 | PlantLoop | COOLSYS1_DEMAND | Plant Loop Volume [m3] | 15.13592 |
443 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Loop Supply Side Design Fluid Flow Rate [m3/s] | 0.12613 |
444 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Loop Demand Side Design Fluid Flow Rate [m3/s] | 0.12613 |
445 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Heat Exchanger U-Factor Times Area Value [W/C] | 529442.24481 |
446 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Loop-to-loop Temperature Difference Used to Size Heat Exchanger U-Factor Times Area Value [C] | 5.60000 |
447 | PlantLoop | HEATSYS1 | Maximum Loop Flow Rate [m3/s] | 2.16021E-002 |
448 | PlantLoop | HEATSYS1 | Plant Loop Volume [m3] | 2.59225 |
449 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Flow Rate [m3/s] | 2.16021E-002 |
450 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Power Consumption [W] | 6505.59308 |
451 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Minimum Flow Rate [m3/s] | 0.00000 |
452 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Nominal Capacity [W] | 2469248.62669 |
453 | Boiler:HotWater | HEATSYS1 BOILER | User-Specified Nominal Capacity [W] | 2469248.63000 |
454 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Design Water Flow Rate [m3/s] | 2.16021E-002 |
455 | PlantLoop | COOLSYS1_SUPPLY | Maximum Loop Flow Rate [m3/s] | 0.12613 |
456 | PlantLoop | COOLSYS1_SUPPLY | Plant Loop Volume [m3] | 15.13592 |
457 | Pump:ConstantSpeed | COOLSYS1 CHILLER1 PUMP | Design Flow Rate [m3/s] | 6.30664E-002 |
458 | Pump:ConstantSpeed | COOLSYS1 CHILLER1 PUMP | Design Power Consumption [W] | 7128.82751 |
459 | Pump:ConstantSpeed | COOLSYS1 CHILLER2 PUMP | Design Flow Rate [m3/s] | 6.30664E-002 |
460 | Pump:ConstantSpeed | COOLSYS1 CHILLER2 PUMP | Design Power Consumption [W] | 7128.82751 |
461 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | Design Size Reference Chilled Water Flow Rate [m3/s] | 0.12613 |
462 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | User-Specified Reference Chilled Water Flow Rate [m3/s] | 6.36650E-002 |
463 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | Design Size Reference Capacity [W] | 1500186.25070 |
464 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | User-Specified Reference Capacity [W] | 1507316.17000 |
465 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | Design Size Reference Condenser Water Flow Rate [m3/s] | 7.45915E-002 |
466 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | Design Size Reference Chilled Water Flow Rate [m3/s] | 0.12613 |
467 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | User-Specified Reference Chilled Water Flow Rate [m3/s] | 6.36650E-002 |
468 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | Design Size Reference Capacity [W] | 1500186.25070 |
469 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | User-Specified Reference Capacity [W] | 1507316.17000 |
470 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | Design Size Reference Condenser Water Flow Rate [m3/s] | 7.45915E-002 |
471 | PlantLoop | SINGLE WATER PLANT LOOP | Maximum Loop Flow Rate [m3/s] | 1.34714E-002 |
472 | PlantLoop | SINGLE WATER PLANT LOOP | Plant Loop Volume [m3] | 1.61657 |
473 | Pump:ConstantSpeed | PLANT CIRC PUMP | Design Flow Rate [m3/s] | 1.34714E-002 |
474 | Pump:ConstantSpeed | PLANT CIRC PUMP | Design Power Consumption [W] | 3435.87449 |
475 | FluidCooler:TwoSpeed | CENTRAL TOWER | Design Water Flow Rate [m3/s] | 1.34714E-002 |
476 | FluidCooler:TwoSpeed | CENTRAL TOWER | Air Flow Rate at High Fan Speed [m3/s] | 139666.46671 |
477 | FluidCooler:TwoSpeed | CENTRAL TOWER | Fluid cooler UA value at high fan speed based on nominal capacity input [W/K] | 58584.36926 |
478 | FluidCooler:TwoSpeed | CENTRAL TOWER | Air Flow Rate at Low Fan Speed [m3/s] | 69833.23335 |
479 | FluidCooler:TwoSpeed | CENTRAL TOWER | Fan Power at Low Fan Speed [W] | 7879.72339 |
480 | FluidCooler:TwoSpeed | CENTRAL TOWER | U-factor Times Area Value at Low Fan Speed [W/C] | 21346.17500 |
481 | Boiler:HotWater | CENTRAL BOILER | Design Size Nominal Capacity [W] | 554905.19047 |
482 | Boiler:HotWater | CENTRAL BOILER | User-Specified Nominal Capacity [W] | 543970.57000 |
483 | Boiler:HotWater | CENTRAL BOILER | Design Size Design Water Flow Rate [m3/s] | 1.34714E-002 |
484 | PlantLoop | SWHSYS1 | Maximum Loop Flow Rate [m3/s] | 4.40000E-004 |
485 | PlantLoop | SWHSYS1 | Plant Loop Volume [m3] | 5.28000E-002 |
486 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Flow Rate [m3/s] | 4.40000E-004 |
487 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Power Consumption [W] | 56.20530 |
488 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | Use Side Design Flow Rate [m3/s] | 4.40000E-004 |
489 | CondenserLoop | TOWERWATERSYS | Maximum Loop Flow Rate [m3/s] | 0.14918 |
490 | CondenserLoop | TOWERWATERSYS | Condenser Loop Volume [m3] | 17.90196 |
491 | HeaderedPumps:VariableSpeed | TOWERWATERSYS PUMP | Design Flow Rate [m3/s] | 0.14918 |
492 | HeaderedPumps:VariableSpeed | TOWERWATERSYS PUMP | Design Power Consumption [W] | 36934.40557 |
493 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Design Air Flow Rate [m3/s] | 59.48143 |
494 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Nominal Capacity [W] | 1788404.52389 |
495 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Air Flow Rate in free convection regime [m3/s] | 11.89629 |
496 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Tower capacity in free convection regime at design conditions [W] | 223550.56549 |
497 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Design Air Flow Rate [m3/s] | 59.48143 |
498 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Nominal Capacity [W] | 1788404.52389 |
499 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Air Flow Rate in free convection regime [m3/s] | 11.89629 |
500 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Tower capacity in free convection regime at design conditions [W] | 223550.56549 |
501 | PlantEquipmentOperation:ComponentSetPoint | WSHPPLANT OPERATION SCHEME | Design Water Flow Rate [m3/s] Equipment # 47 | 7.74775E-002 |
502 | PlantEquipmentOperation:ComponentSetPoint | WSHPPLANT OPERATION SCHEME | Design Water Flow Rate [m3/s] Equipment # 47 | 7.74775E-002 |
Component Type | Name | Nominal Total Capacity {W} | |
1 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | 17994.89 |
2 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | 437729.20 |
3 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | 81585.54 |
4 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | 14155.92 |
5 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | 9680.00 |
6 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | 15705.28 |
7 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | 7847.78 |
8 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | 232226.85 |
9 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | 151980.47 |
10 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | 228972.03 |
11 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | 147664.46 |
12 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | 29105.23 |
13 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | 18989.02 |
14 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | 28758.30 |
15 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | 18718.76 |
16 | Coil:Heating:Water | VAV_BOT WITH REHEAT HEATING COIL | 43740.55 |
17 | Coil:Heating:Water | VAV_MID WITH REHEAT HEATING COIL | 417202.15 |
18 | Coil:Heating:Water | VAV_TOP WITH REHEAT HEATING COIL | 41806.40 |
19 | Coil:Heating:Water | CAV_BAS HEATING COIL | 231340.80 |
Component Type | Name | Nominal Total Capacity {W} | Nominal Sensible Capacity {W} | Nominal Latent Capacity {W} | Nominal Sensible Heat Ratio | Nominal Coil UA Value {W/C} | Nominal Coil Surface Area {m2} | |
1 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | 266205.00 | 177631.86 | 88573.14 | 0.67 | 28251.46 | 286.54 |
2 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | 2524490.77 | 1676090.29 | 848400.47 | 0.66 | 268406.63 | 2722.33 |
3 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | 268814.03 | 179507.15 | 89306.88 | 0.67 | 28536.96 | 289.44 |
4 | Coil:Cooling:Water | CAV_BAS COOLING COIL | 149077.94 | 101882.01 | 47195.93 | 0.68 | 15614.12 | 158.37 |
Component Type | Component Name | IPLV in SI Units {W/W} | IPLV in IP Units {Btu/W-h} | |
1 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | 6.84 | 23.33 |
2 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | 6.84 | 23.33 |
Zone Name | # Surfaces | |
1 | BASEMENT | 10 |
2 | CORE_BOTTOM | 8 |
3 | CORE_MID | 7 |
4 | CORE_TOP | 7 |
5 | PERIMETER_BOT_ZN_3 | 18 |
6 | PERIMETER_BOT_ZN_2 | 12 |
7 | PERIMETER_BOT_ZN_1 | 18 |
8 | PERIMETER_BOT_ZN_4 | 12 |
9 | PERIMETER_MID_ZN_3 | 9 |
10 | PERIMETER_MID_ZN_2 | 8 |
11 | PERIMETER_MID_ZN_1 | 9 |
12 | PERIMETER_MID_ZN_4 | 8 |
13 | PERIMETER_TOP_ZN_3 | 9 |
14 | PERIMETER_TOP_ZN_2 | 8 |
15 | PERIMETER_TOP_ZN_1 | 9 |
16 | PERIMETER_TOP_ZN_4 | 8 |
17 | GROUNDFLOOR_PLENUM | 11 |
18 | MIDFLOOR_PLENUM | 11 |
19 | TOPFLOOR_PLENUM | 11 |
20 | DATACENTER_BOT_ZN_6 | 6 |
21 | DATACENTER_MID_ZN_6 | 6 |
22 | DATACENTER_TOP_ZN_6 | 6 |
23 | DATACENTER_BASEMENT_ZN_6 | 10 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | BASEMENT_WALL_EAST | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_EAST_CFACTOR | 0.940 | 0.824 | 118.87 | 118.87 | 118.87 | 90.00 | 90.00 | 48.74 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | BASEMENT_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_SOUTH_CFACTOR | 0.940 | 0.824 | 139.09 | 139.09 | 139.09 | 180.00 | 90.00 | 57.03 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
3 | BASEMENT_WALL_NORTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_NORTH_CFACTOR | 0.940 | 0.824 | 139.09 | 139.09 | 139.09 | 0.00 | 90.00 | 57.03 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | BASEMENT_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.87 | 118.87 | 118.87 | 270.00 | 90.00 | 48.74 | 2.44 | 0.00 | DATACENTER_BASEMENT_ZN_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
5 | BASEMENT_FLOOR | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 2779.43 | 2779.43 | 2779.43 | 0.00 | 180.00 | 57.03 | 48.74 | 0.00 | BASEMENT_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
6 | PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | PERIMETER_BOT_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
7 | PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 250.34 | 250.34 | 250.34 | 180.00 | 0.00 | 57.03 | 4.57 | 0.00 | PERIMETER_BOT_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
8 | CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 2076.77 | 2076.77 | 2076.77 | 180.00 | 0.00 | 52.45 | 39.59 | 0.00 | CORE_BOT_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
9 | PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 250.34 | 250.34 | 250.34 | 180.00 | 0.00 | 52.45 | 4.57 | 0.00 | PERIMETER_BOT_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
10 | BASEMENT_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 7126.21 | 7126.21 | 7126.21 | 0.00 | 90.00 | 7126.21 | 1.00 | 0.00 | BASEMENT_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
11 | CORE_BOT_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
12 | CORE_BOT_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
13 | CORE_BOT_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
14 | CORE_BOT_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
15 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 419.30 | 419.30 | 419.30 | 0.00 | 180.00 | 10.59 | 39.59 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
16 | CORE_BOT_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 2076.82 | 2076.82 | 2076.82 | 0.00 | 180.00 | 52.46 | 39.59 | 0.00 | CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
17 | CORE_BOT_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 2496.12 | 2496.12 | 2496.12 | 180.00 | 0.00 | 63.05 | 39.59 | 0.00 | iz-CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
18 | CORE_BOTTOM_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 5064.65 | 5064.65 | 5064.65 | 0.00 | 90.00 | 5064.65 | 1.00 | 0.00 | CORE_BOTTOM_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
19 | CORE_MID_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
20 | CORE_MID_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
21 | CORE_MID_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
22 | CORE_MID_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
23 | CORE_MID_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_MID_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
24 | CORE_MID_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 2496.12 | 2496.12 | 2496.12 | 180.00 | 0.00 | 63.05 | 39.59 | 0.00 | iz-CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
25 | CORE_MID_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 5064.65 | 5064.65 | 5064.65 | 0.00 | 90.00 | 5064.65 | 1.00 | 0.00 | CORE_MID_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
26 | CORE_TOP_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
27 | CORE_TOP_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
28 | CORE_TOP_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
29 | CORE_TOP_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
30 | CORE_TOP_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_TOP_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
31 | CORE_TOP_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 2496.12 | 2496.12 | 2496.12 | 180.00 | 0.00 | 63.05 | 39.59 | 0.00 | iz-CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
32 | CORE_TOP_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 5064.65 | 5064.65 | 5064.65 | 0.00 | 90.00 | 5064.65 | 1.00 | 0.00 | CORE_TOP_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
33 | PERIMETER_BOT_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.223 | 1.034 | 76.91 | 200.61 | 76.91 | 0.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
34 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.498_SHGC_NORTH_0.25 | N/A | 2.831 | No | 23.18 | 23.18 | 23.18 | 0.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
35 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.498_SHGC_NORTH_0.25 | N/A | 2.831 | No | 23.18 | 23.18 | 23.18 | 0.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
36 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.498_SHGC_NORTH_0.25 | N/A | 2.831 | No | 23.18 | 23.18 | 23.18 | 0.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
37 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.498_SHGC_NORTH_0.25 | N/A | 2.831 | No | 23.18 | 23.18 | 23.18 | 0.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
38 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.498_SHGC_NORTH_0.25 | N/A | 2.831 | No | 23.18 | 23.18 | 23.18 | 0.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
39 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.975 | 3.975 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
40 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.975 | 3.975 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
41 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.975 | 3.975 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
42 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.975 | 3.975 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
43 | PERIMETER_BOT_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
44 | CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
45 | PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
46 | DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
47 | PERIMETER_BOT_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 250.34 | 250.34 | 250.34 | 0.00 | 180.00 | 52.46 | 6.47 | 0.00 | PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
48 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 63.07 | 63.07 | 63.07 | 0.00 | 180.00 | 11.51 | 4.57 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
49 | PERIMETER_BOT_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.41 | 313.41 | 313.41 | 180.00 | 0.00 | 63.96 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
50 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.83 | 626.83 | 626.83 | 0.00 | 90.00 | 626.83 | 1.00 | 0.00 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
51 | PERIMETER_BOT_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.223 | 1.034 | 52.57 | 133.74 | 52.57 | 90.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
52 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.498_SHGC_EAST_0.25 | N/A | 2.831 | No | 25.75 | 25.75 | 25.75 | 90.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
53 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.498_SHGC_EAST_0.25 | N/A | 2.831 | No | 25.75 | 25.75 | 25.75 | 90.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
54 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.498_SHGC_EAST_0.25 | N/A | 2.831 | No | 25.75 | 25.75 | 25.75 | 90.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
55 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | Door | PERIMETER_BOT_ZN_2_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.975 | 3.975 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
56 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | Door | PERIMETER_BOT_ZN_2_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.975 | 3.975 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
57 | PERIMETER_BOT_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
58 | CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
59 | PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
60 | PERIMETER_BOT_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
61 | PERIMETER_BOT_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | iz-PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
62 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
63 | PERIMETER_BOT_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.223 | 1.034 | 76.91 | 200.61 | 76.91 | 180.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
64 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.498_SHGC_SOUTH_0.25 | N/A | 2.831 | No | 23.18 | 23.18 | 23.18 | 180.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
65 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.498_SHGC_SOUTH_0.25 | N/A | 2.831 | No | 23.18 | 23.18 | 23.18 | 180.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
66 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.498_SHGC_SOUTH_0.25 | N/A | 2.831 | No | 23.18 | 23.18 | 23.18 | 180.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
67 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.498_SHGC_SOUTH_0.25 | N/A | 2.831 | No | 23.18 | 23.18 | 23.18 | 180.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
68 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.498_SHGC_SOUTH_0.25 | N/A | 2.831 | No | 23.18 | 23.18 | 23.18 | 180.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
69 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.975 | 3.975 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
70 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.975 | 3.975 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
71 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.975 | 3.975 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
72 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.975 | 3.975 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
73 | PERIMETER_BOT_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
74 | DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
75 | PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
76 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
77 | DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 63.07 | 63.07 | 63.07 | 0.00 | 180.00 | 16.08 | 4.57 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
78 | PERIMETER_BOT_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 250.35 | 250.35 | 250.35 | 0.00 | 180.00 | 57.03 | 6.47 | 0.00 | PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
79 | PERIMETER_BOT_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.42 | 313.42 | 313.42 | 180.00 | 0.00 | 73.11 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
80 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.84 | 626.84 | 626.84 | 0.00 | 90.00 | 626.84 | 1.00 | 0.00 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
81 | PERIMETER_BOT_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.223 | 1.034 | 52.57 | 133.74 | 52.57 | 270.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
82 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.498_SHGC_WEST_0.25 | N/A | 2.831 | No | 25.75 | 25.75 | 25.75 | 270.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
83 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.498_SHGC_WEST_0.25 | N/A | 2.831 | No | 25.75 | 25.75 | 25.75 | 270.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
84 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.498_SHGC_WEST_0.25 | N/A | 2.831 | No | 25.75 | 25.75 | 25.75 | 270.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
85 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | Door | PERIMETER_BOT_ZN_4_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.975 | 3.975 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
86 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | Door | PERIMETER_BOT_ZN_4_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.975 | 3.975 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
87 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
88 | DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
89 | PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
90 | PERIMETER_BOT_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
91 | PERIMETER_BOT_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | iz-PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
92 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
93 | PERIMETER_MID_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.174 | 0.999 | 84.71 | 200.61 | 84.71 | 0.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
94 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_MID_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.498_SHGC_NORTH_0.25 | N/A | 2.831 | No | 115.90 | 115.90 | 115.90 | 0.00 | 90.00 | 73.11 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
95 | PERIMETER_MID_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
96 | CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
97 | PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
98 | DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
99 | PERIMETER_MID_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
100 | PERIMETER_MID_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.41 | 313.41 | 313.41 | 180.00 | 0.00 | 63.96 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
101 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.83 | 626.83 | 626.83 | 0.00 | 90.00 | 626.83 | 1.00 | 0.00 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
102 | PERIMETER_MID_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.174 | 0.999 | 56.47 | 133.74 | 56.47 | 90.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
103 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_MID_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.498_SHGC_EAST_0.25 | N/A | 2.831 | No | 77.26 | 77.26 | 77.26 | 90.00 | 90.00 | 48.74 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
104 | PERIMETER_MID_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
105 | CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
106 | PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
107 | PERIMETER_MID_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_MID_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
108 | PERIMETER_MID_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | iz-PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
109 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
110 | PERIMETER_MID_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
111 | PERIMETER_MID_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.174 | 0.999 | 84.71 | 200.61 | 84.71 | 180.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
112 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_MID_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.498_SHGC_SOUTH_0.25 | N/A | 2.831 | No | 115.90 | 115.90 | 115.90 | 180.00 | 90.00 | 73.11 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
113 | DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
114 | PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
115 | CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
116 | PERIMETER_MID_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
117 | PERIMETER_MID_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.42 | 313.42 | 313.42 | 180.00 | 0.00 | 73.11 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
118 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.84 | 626.84 | 626.84 | 0.00 | 90.00 | 626.84 | 1.00 | 0.00 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
119 | PERIMETER_MID_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.174 | 0.999 | 56.47 | 133.74 | 56.47 | 270.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
120 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_MID_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.498_SHGC_WEST_0.25 | N/A | 2.831 | No | 77.26 | 77.26 | 77.26 | 270.00 | 90.00 | 48.74 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
121 | PERIMETER_MID_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
122 | DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
123 | PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
124 | PERIMETER_MID_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_MID_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
125 | PERIMETER_MID_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | iz-PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
126 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
127 | PERIMETER_TOP_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.421 | 1.172 | 84.71 | 200.61 | 84.71 | 0.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
128 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_TOP_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.498_SHGC_NORTH_0.25 | N/A | 2.831 | No | 115.90 | 115.90 | 115.90 | 0.00 | 90.00 | 73.11 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
129 | PERIMETER_TOP_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
130 | CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
131 | PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
132 | DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
133 | PERIMETER_TOP_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_TOP_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
134 | PERIMETER_TOP_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.41 | 313.41 | 313.41 | 180.00 | 0.00 | 63.96 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
135 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.83 | 626.83 | 626.83 | 0.00 | 90.00 | 626.83 | 1.00 | 0.00 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
136 | PERIMETER_TOP_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.421 | 1.172 | 56.47 | 133.74 | 56.47 | 90.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
137 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_TOP_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.498_SHGC_EAST_0.25 | N/A | 2.831 | No | 77.26 | 77.26 | 77.26 | 90.00 | 90.00 | 48.74 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
138 | PERIMETER_TOP_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
139 | CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
140 | INT-PER3S-NE-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | INT-PER3S-NE | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
141 | PERIMETER_TOP_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_TOP_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
142 | PERIMETER_TOP_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | iz-PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
143 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
144 | PERIMETER_TOP_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.421 | 1.172 | 84.71 | 200.61 | 84.71 | 180.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
145 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_TOP_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.498_SHGC_SOUTH_0.25 | N/A | 2.831 | No | 115.90 | 115.90 | 115.90 | 180.00 | 90.00 | 73.11 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
146 | INT-PER3S-NE | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | INT-PER3S-NE-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
147 | DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
148 | PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
149 | CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
150 | PERIMETER_TOP_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_TOP_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
151 | PERIMETER_TOP_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.42 | 313.42 | 313.42 | 180.00 | 0.00 | 73.11 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
152 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.84 | 626.84 | 626.84 | 0.00 | 90.00 | 626.84 | 1.00 | 0.00 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
153 | PERIMETER_TOP_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.421 | 1.172 | 56.47 | 133.74 | 56.47 | 270.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
154 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_TOP_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.498_SHGC_WEST_0.25 | N/A | 2.831 | No | 77.26 | 77.26 | 77.26 | 270.00 | 90.00 | 48.74 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
155 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
156 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
157 | PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
158 | PERIMETER_TOP_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_TOP_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
159 | PERIMETER_TOP_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | iz-PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
160 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
161 | GROUNDFLOOR_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.223 | 1.034 | 89.13 | 89.13 | 89.13 | 0.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
162 | GROUNDFLOOR_PLENUM_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.223 | 1.034 | 59.42 | 59.42 | 59.42 | 270.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
163 | GROUNDFLOOR_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.223 | 1.034 | 89.13 | 89.13 | 89.13 | 180.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
164 | GROUNDFLOOR_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.223 | 1.034 | 59.42 | 59.42 | 59.42 | 90.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
165 | iz-CORE_BOT_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
166 | iz-PERIMETER_BOT_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
167 | iz-PERIMETER_BOT_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
168 | iz-PERIMETER_BOT_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
169 | iz-PERIMETER_BOT_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
170 | iz-DATACENTER_BOT_ZN_6_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_BOT_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
171 | GROUNDFLOOR_PLENUM_CEILING | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 3563.11 | 3563.11 | 3563.11 | 180.00 | 0.00 | 73.11 | 48.74 | 0.00 | GROUNDFLOOR_PLENUM_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
172 | MIDFLOOR_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.174 | 0.999 | 89.13 | 89.13 | 89.13 | 0.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
173 | MIDFLOOR_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.174 | 0.999 | 59.42 | 59.42 | 59.42 | 270.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
174 | MIDFLOOR_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.174 | 0.999 | 89.13 | 89.13 | 89.13 | 180.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
175 | MIDFLOOR_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.174 | 0.999 | 59.42 | 59.42 | 59.42 | 90.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
176 | iz-CORE_MID_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
177 | iz-PERIMETER_MID_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
178 | iz-PERIMETER_MID_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
179 | iz-PERIMETER_MID_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
180 | iz-PERIMETER_MID_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
181 | iz-DATACENTER_MID_ZN_6_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_MID_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
182 | MIDFLOOR_PLENUM_CEILING | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 3563.11 | 3563.11 | 3563.11 | 180.00 | 0.00 | 73.11 | 48.74 | 0.00 | MIDFLOOR_PLENUM_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
183 | TOPFLOOR_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.421 | 1.172 | 89.13 | 89.13 | 89.13 | 180.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
184 | TOPFLOOR_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.421 | 1.172 | 59.42 | 59.42 | 59.42 | 90.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
185 | TOPFLOOR_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.421 | 1.172 | 59.42 | 59.42 | 59.42 | 270.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
186 | TOPFLOOR_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.421 | 1.172 | 89.13 | 89.13 | 89.13 | 0.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
187 | iz-CORE_TOP_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
188 | iz-PERIMETER_TOP_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
189 | iz-PERIMETER_TOP_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
190 | iz-PERIMETER_TOP_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
191 | iz-PERIMETER_TOP_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
192 | iz-DATACENTER_TOP_ZN_6_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_TOP_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
193 | BUILDING_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 3563.11 | 3563.11 | 3563.11 | 180.00 | 0.00 | 73.11 | 48.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
194 | DATACENTER_BOT_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
195 | DATACENTER_BOT_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
196 | DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
197 | DATACENTER_BOT_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
198 | DATACENTER_BOT_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
199 | DATACENTER_BOT_ZN_6_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | iz-DATACENTER_BOT_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
200 | DATACENTER_MID_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
201 | DATACENTER_MID_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
202 | DATACENTER_MID_ZN_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
203 | DATACENTER_MID_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
204 | DATACENTER_MID_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_MID_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
205 | DATACENTER_MID_ZN_6_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | iz-DATACENTER_MID_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
206 | DATACENTER_TOP_ZN_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
207 | DATACENTER_TOP_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
208 | DATACENTER_TOP_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
209 | DATACENTER_TOP_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
210 | DATACENTER_TOP_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_TOP_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
211 | DATACENTER_TOP_ZN_6_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | iz-DATACENTER_TOP_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
212 | DATACENTER_BASEMENT_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR | 0.940 | 0.824 | 39.22 | 39.22 | 39.22 | 0.00 | 90.00 | 16.08 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
213 | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR | 0.940 | 0.824 | 39.22 | 39.22 | 39.22 | 180.00 | 90.00 | 16.08 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
214 | DATACENTER_BASEMENT_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR | 0.940 | 0.824 | 118.87 | 118.87 | 118.87 | 270.00 | 90.00 | 48.74 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
215 | DATACENTER_BASEMENT_ZN_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.87 | 118.87 | 118.87 | 90.00 | 90.00 | 48.74 | 2.44 | 0.00 | BASEMENT_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
216 | DATACENTER_BASEMENT_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 783.68 | 783.68 | 783.68 | 0.00 | 180.00 | 16.08 | 48.74 | 0.00 | DATACENTER_BASEMENT_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
217 | DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | DATACENTER_BOT_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
218 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 419.35 | 419.35 | 419.35 | 180.00 | 0.00 | 10.59 | 39.59 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
219 | PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | PERIMETER_BOT_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
220 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 63.08 | 63.08 | 63.08 | 180.00 | 0.00 | 16.08 | 6.47 | 0.00 | DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
221 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 63.07 | 63.07 | 63.07 | 180.00 | 0.00 | 11.51 | 6.47 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | BASEMENT | RunPeriod: RUNPERIOD 1 | 0.2330065948 | 0.2299243882 | Pass | Pass | 0.7609838585 | 2.1132672043 | Pass | Pass |
2 | CORE_BOTTOM | RunPeriod: RUNPERIOD 1 | 3.7209159212E-003 | 5.9399468738E-003 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
3 | CORE_MID | RunPeriod: RUNPERIOD 1 | 4.6922029274E-003 | 6.7377814783E-003 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
4 | CORE_TOP | RunPeriod: RUNPERIOD 1 | 9.3041196908E-002 | 8.5046056146E-002 | Pass | Pass | 0.2747371822 | 0.4837540746 | Pass | Pass |
5 | PERIMETER_BOT_ZN_3 | RunPeriod: RUNPERIOD 1 | 2.8467251791E-002 | 3.0319372204E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
6 | PERIMETER_BOT_ZN_2 | RunPeriod: RUNPERIOD 1 | 2.8931109597E-002 | 3.1407873671E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
7 | PERIMETER_BOT_ZN_1 | RunPeriod: RUNPERIOD 1 | 2.8683790820E-002 | 3.0356252351E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
8 | PERIMETER_BOT_ZN_4 | RunPeriod: RUNPERIOD 1 | 2.8730527230E-002 | 3.0615894926E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
9 | PERIMETER_MID_ZN_3 | RunPeriod: RUNPERIOD 1 | 3.4096179532E-002 | 3.4680982160E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
10 | PERIMETER_MID_ZN_2 | RunPeriod: RUNPERIOD 1 | 3.5007370549E-002 | 3.5921931300E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
11 | PERIMETER_MID_ZN_1 | RunPeriod: RUNPERIOD 1 | 3.5654799570E-002 | 3.7319502384E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
12 | PERIMETER_MID_ZN_4 | RunPeriod: RUNPERIOD 1 | 3.5788581952E-002 | 3.6171552164E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
13 | PERIMETER_TOP_ZN_3 | RunPeriod: RUNPERIOD 1 | 0.1620909527 | 0.1961762846 | Pass | Pass | 0.8695292671 | 2.8458333016 | Pass | Pass |
14 | PERIMETER_TOP_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.1601019422 | 0.1931929272 | Pass | Pass | 2.4918377009 | 18.5975078102 | Pass | Pass |
15 | PERIMETER_TOP_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.1483366675 | 0.1757080494 | Pass | Pass | 0.8631431271 | 2.8318454656 | Pass | Pass |
16 | PERIMETER_TOP_ZN_4 | RunPeriod: RUNPERIOD 1 | 6.3141849096E-002 | 9.3737622137E-002 | Pass | Pass | 1.1443488727 | 3.6120874667 | Pass | Pass |
17 | GROUNDFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 4.1725199189E-003 | 4.7458942672E-003 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
18 | MIDFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 5.5914111673E-003 | 6.9815217508E-003 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
19 | TOPFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 6.3083515130E-002 | 4.1245456113E-002 | Pass | Pass | 0.2549044147 | 0.4394454640 | Pass | Pass |
20 | DATACENTER_BOT_ZN_6 | RunPeriod: RUNPERIOD 1 | 5.7446490670E-006 | 7.4258721911E-006 | Pass | Pass | 2.8280598937E-003 | 1.9210543970E-003 | Pass | Pass |
21 | DATACENTER_MID_ZN_6 | RunPeriod: RUNPERIOD 1 | 9.4584497169E-003 | 7.7270624815E-003 | Pass | Pass | 4.9872981068E-003 | 6.1568889440E-003 | Pass | Pass |
22 | DATACENTER_TOP_ZN_6 | RunPeriod: RUNPERIOD 1 | 1.7570039025E-002 | 1.3511349641E-002 | Pass | Pass | 3.5181292975E-003 | 3.8762959033E-003 | Pass | Pass |
23 | DATACENTER_BASEMENT_ZN_6 | RunPeriod: RUNPERIOD 1 | 7.3407145655E-006 | 9.8845308530E-006 | Pass | Pass | 4.0367131652E-005 | 1.0956580787E-004 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 08:43:24
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 5374.23 | 88.64 | 0.00 | 12100.87 | 27789.74 | 45353.46 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 08:43:24
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | -6.30 | 0.00 | -6.30 | Wetbulb [C] | 5.30 | 320.00 |
ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 34.40 | 9.50 | 23.50 | Wetbulb [C] | 4.00 | 300.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 0.00 | 0 | |||
Feb | 0.00 | 0 | |||
Mar | 0.00 | 0 | |||
Apr | 0.00 | 0 | |||
May | 0.00 | 0 | |||
Jun | 0.00 | 0 | |||
Jul | 0.00 | 0 | |||
Aug | 0.00 | 0 | |||
Sep | 90.00 | 25 | |||
Oct | 0.00 | 0 | |||
Nov | 0.00 | 0 | |||
Dec | 0.00 | 0 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 08:43:24
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BASEMENT_WALL_EAST | BASEMENT_WALL_EAST_CFACTOR | 1.00 | 0.845 | 0.940 | 118.87 | 118.87 | 90.00 | 90.00 | E |
BASEMENT_WALL_SOUTH | BASEMENT_WALL_SOUTH_CFACTOR | 1.00 | 0.845 | 0.940 | 139.09 | 139.09 | 180.00 | 90.00 | S |
BASEMENT_WALL_NORTH | BASEMENT_WALL_NORTH_CFACTOR | 1.00 | 0.845 | 0.940 | 139.09 | 139.09 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_3_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 1.034 | 1.223 | 200.61 | 76.91 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_2_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 1.034 | 1.223 | 133.74 | 52.57 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 1.034 | 1.223 | 200.61 | 76.91 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_4_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 1.034 | 1.223 | 133.74 | 52.57 | 270.00 | 90.00 | W |
PERIMETER_MID_ZN_3_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.999 | 1.174 | 2006.06 | 847.11 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_2_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 0.999 | 1.174 | 1337.37 | 564.74 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.999 | 1.174 | 2006.06 | 847.11 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_4_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 0.999 | 1.174 | 1337.37 | 564.74 | 270.00 | 90.00 | W |
PERIMETER_TOP_ZN_3_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 1.172 | 1.421 | 200.61 | 84.71 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_2_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 1.172 | 1.421 | 133.74 | 56.47 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 1.172 | 1.421 | 200.61 | 84.71 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_4_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 1.172 | 1.421 | 133.74 | 56.47 | 270.00 | 90.00 | W |
GROUNDFLOOR_PLENUM_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 1.034 | 1.223 | 89.13 | 89.13 | 0.00 | 90.00 | N |
GROUNDFLOOR_PLENUM_WEST | NONRES_EXT_WALL_GRD | 0.30 | 1.034 | 1.223 | 59.42 | 59.42 | 270.00 | 90.00 | W |
GROUNDFLOOR_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 1.034 | 1.223 | 89.13 | 89.13 | 180.00 | 90.00 | S |
GROUNDFLOOR_PLENUM_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 1.034 | 1.223 | 59.42 | 59.42 | 90.00 | 90.00 | E |
MIDFLOOR_PLENUM_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.999 | 1.174 | 891.32 | 891.32 | 0.00 | 90.00 | N |
MIDFLOOR_PLENUM_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 0.999 | 1.174 | 594.21 | 594.21 | 270.00 | 90.00 | W |
MIDFLOOR_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.999 | 1.174 | 891.32 | 891.32 | 180.00 | 90.00 | S |
MIDFLOOR_PLENUM_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 0.999 | 1.174 | 594.21 | 594.21 | 90.00 | 90.00 | E |
TOPFLOOR_PLENUM_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 1.172 | 1.421 | 89.13 | 89.13 | 180.00 | 90.00 | S |
TOPFLOOR_PLENUM_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 1.172 | 1.421 | 59.42 | 59.42 | 90.00 | 90.00 | E |
TOPFLOOR_PLENUM_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 1.172 | 1.421 | 59.42 | 59.42 | 270.00 | 90.00 | W |
TOPFLOOR_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 1.172 | 1.421 | 89.13 | 89.13 | 0.00 | 90.00 | N |
BUILDING_ROOF | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 3563.11 | 3563.11 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_WALL_NORTH | DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR | 1.00 | 0.845 | 0.940 | 39.22 | 39.22 | 0.00 | 90.00 | N |
DATACENTER_BASEMENT_ZN_6_WALL_SOUTH | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR | 1.00 | 0.845 | 0.940 | 39.22 | 39.22 | 180.00 | 90.00 | S |
DATACENTER_BASEMENT_ZN_6_WALL_WEST | DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR | 1.00 | 0.845 | 0.940 | 118.87 | 118.87 | 270.00 | 90.00 | W |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BASEMENT_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 118.87 | 118.87 | 270.00 | 90.00 | W |
BASEMENT_FLOOR | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 2779.43 | 2779.43 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 225.00 | 0.00 | |
PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 250.34 | 250.34 | 180.00 | 0.00 | |
CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 2076.77 | 2076.77 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 250.34 | 250.34 | 180.00 | 0.00 | |
CORE_BOT_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
CORE_BOT_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
CORE_BOT_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 419.30 | 419.30 | 0.00 | 180.00 | |
CORE_BOT_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 2076.82 | 2076.82 | 0.00 | 180.00 | |
CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 180.00 | 0.00 | |
CORE_MID_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 180.00 | 90.00 | S |
CORE_MID_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 270.00 | 90.00 | W |
CORE_MID_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 0.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 90.00 | 90.00 | E |
CORE_MID_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 24961.20 | 24961.20 | 0.00 | 180.00 | |
CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 24961.20 | 24961.20 | 180.00 | 0.00 | |
CORE_TOP_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
CORE_TOP_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
CORE_TOP_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
CORE_TOP_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 2496.12 | 2496.12 | 0.00 | 180.00 | |
CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 250.34 | 250.34 | 0.00 | 180.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 63.07 | 63.07 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
PERIMETER_BOT_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 45.00 | 180.00 | |
PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 225.00 | 0.00 | |
PERIMETER_BOT_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 63.07 | 63.07 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 250.35 | 250.35 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
PERIMETER_BOT_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 315.00 | 180.00 | |
PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 135.00 | 0.00 | |
PERIMETER_MID_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 225.00 | 90.00 | W |
CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 135.00 | 90.00 | S |
DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 3134.13 | 3134.13 | 0.00 | 180.00 | |
PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.13 | 3134.13 | 180.00 | 0.00 | |
PERIMETER_MID_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 315.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 270.00 | 90.00 | W |
PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 225.00 | 90.00 | W |
PERIMETER_MID_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 2019.75 | 2019.75 | 45.00 | 180.00 | |
PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 225.00 | 0.00 | |
PERIMETER_MID_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 45.00 | 90.00 | E |
DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 315.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 3134.20 | 3134.20 | 0.00 | 180.00 | |
PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.20 | 3134.20 | 180.00 | 0.00 | |
PERIMETER_MID_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 135.00 | 90.00 | S |
DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 45.00 | 90.00 | E |
PERIMETER_MID_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 2019.75 | 2019.75 | 315.00 | 180.00 | |
PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 135.00 | 0.00 | |
PERIMETER_TOP_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 313.41 | 313.41 | 0.00 | 180.00 | |
PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 180.00 | 0.00 | |
PERIMETER_TOP_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
INT-PER3S-NE-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
PERIMETER_TOP_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 201.98 | 201.98 | 45.00 | 180.00 | |
PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 225.00 | 0.00 | |
INT-PER3S-NE | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 313.42 | 313.42 | 0.00 | 180.00 | |
PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 180.00 | 0.00 | |
PERIMETER_TOP_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
PERIMETER_TOP_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 201.98 | 201.98 | 315.00 | 180.00 | |
PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 135.00 | 0.00 | |
iz-CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 45.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 315.00 | 180.00 | |
iz-DATACENTER_BOT_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 0.00 | 180.00 | |
GROUNDFLOOR_PLENUM_CEILING | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 3563.11 | 3563.11 | 180.00 | 0.00 | |
iz-CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 24961.20 | 24961.20 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.13 | 3134.13 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 45.00 | 180.00 | |
iz-PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.20 | 3134.20 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 315.00 | 180.00 | |
iz-DATACENTER_MID_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 362.03 | 362.03 | 0.00 | 180.00 | |
MIDFLOOR_PLENUM_CEILING | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 35631.06 | 35631.06 | 180.00 | 0.00 | |
iz-CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 45.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 315.00 | 180.00 | |
iz-DATACENTER_TOP_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 0.00 | 180.00 | |
DATACENTER_BOT_ZN_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
DATACENTER_BOT_ZN_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
DATACENTER_BOT_ZN_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
DATACENTER_BOT_ZN_6_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 36.20 | 36.20 | 0.00 | 180.00 | |
DATACENTER_BOT_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 180.00 | 0.00 | |
DATACENTER_MID_ZN_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 270.00 | 90.00 | W |
DATACENTER_MID_ZN_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 180.00 | 90.00 | S |
DATACENTER_MID_ZN_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 90.00 | 90.00 | E |
DATACENTER_MID_ZN_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 0.00 | 90.00 | N |
DATACENTER_MID_ZN_6_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 362.03 | 362.03 | 0.00 | 180.00 | |
DATACENTER_MID_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 362.03 | 362.03 | 180.00 | 0.00 | |
DATACENTER_TOP_ZN_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
DATACENTER_TOP_ZN_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
DATACENTER_TOP_ZN_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
DATACENTER_TOP_ZN_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
DATACENTER_TOP_ZN_6_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 36.20 | 36.20 | 0.00 | 180.00 | |
DATACENTER_TOP_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 118.87 | 118.87 | 90.00 | 90.00 | E |
DATACENTER_BASEMENT_ZN_6_FLOOR | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 783.68 | 783.68 | 0.00 | 180.00 | |
DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 36.20 | 36.20 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 419.35 | 419.35 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 135.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 63.08 | 63.08 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 63.07 | 63.07 | 180.00 | 0.00 | |
BASEMENT_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 7126.21 | 0.00 | 90.00 | N | ||
CORE_BOTTOM_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 5064.65 | 0.00 | 90.00 | N | ||
CORE_MID_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 50646.53 | 0.00 | 90.00 | N | ||
CORE_TOP_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 5064.65 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.83 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.84 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 6268.26 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 4039.50 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 6268.35 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 4039.48 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.83 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.84 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | WINDOW_U_0.498_SHGC_NORTH_0.25 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.831 | 0.251 | 0.276 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | WINDOW_U_0.498_SHGC_NORTH_0.25 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.831 | 0.251 | 0.276 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | WINDOW_U_0.498_SHGC_NORTH_0.25 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.831 | 0.251 | 0.276 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | WINDOW_U_0.498_SHGC_NORTH_0.25 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.831 | 0.251 | 0.276 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | WINDOW_U_0.498_SHGC_NORTH_0.25 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.831 | 0.251 | 0.276 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | WINDOW_U_0.498_SHGC_EAST_0.25 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 2.831 | 0.251 | 0.276 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | WINDOW_U_0.498_SHGC_EAST_0.25 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 2.831 | 0.251 | 0.276 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | WINDOW_U_0.498_SHGC_EAST_0.25 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 2.831 | 0.251 | 0.276 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | WINDOW_U_0.498_SHGC_SOUTH_0.25 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.831 | 0.251 | 0.276 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | WINDOW_U_0.498_SHGC_SOUTH_0.25 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.831 | 0.251 | 0.276 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | WINDOW_U_0.498_SHGC_SOUTH_0.25 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.831 | 0.251 | 0.276 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | WINDOW_U_0.498_SHGC_SOUTH_0.25 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.831 | 0.251 | 0.276 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | WINDOW_U_0.498_SHGC_SOUTH_0.25 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.831 | 0.251 | 0.276 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | WINDOW_U_0.498_SHGC_WEST_0.25 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 2.831 | 0.251 | 0.276 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | WINDOW_U_0.498_SHGC_WEST_0.25 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 2.831 | 0.251 | 0.276 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | WINDOW_U_0.498_SHGC_WEST_0.25 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 2.831 | 0.251 | 0.276 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.498_SHGC_NORTH_0.25 | 115.90 | 0.00 | 0.00 | 115.90 | 1158.95 | 2.831 | 0.251 | 0.276 | No | PERIMETER_MID_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.498_SHGC_EAST_0.25 | 77.26 | 0.00 | 0.00 | 77.26 | 772.63 | 2.831 | 0.251 | 0.276 | No | PERIMETER_MID_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.498_SHGC_SOUTH_0.25 | 115.90 | 0.00 | 0.00 | 115.90 | 1158.95 | 2.831 | 0.251 | 0.276 | No | PERIMETER_MID_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.498_SHGC_WEST_0.25 | 77.26 | 0.00 | 0.00 | 77.26 | 772.63 | 2.831 | 0.251 | 0.276 | No | PERIMETER_MID_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.498_SHGC_NORTH_0.25 | 115.90 | 0.00 | 0.00 | 115.90 | 115.90 | 2.831 | 0.251 | 0.276 | No | PERIMETER_TOP_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.498_SHGC_EAST_0.25 | 77.26 | 0.00 | 0.00 | 77.26 | 77.26 | 2.831 | 0.251 | 0.276 | No | PERIMETER_TOP_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.498_SHGC_SOUTH_0.25 | 115.90 | 0.00 | 0.00 | 115.90 | 115.90 | 2.831 | 0.251 | 0.276 | No | PERIMETER_TOP_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.498_SHGC_WEST_0.25 | 77.26 | 0.00 | 0.00 | 77.26 | 77.26 | 2.831 | 0.251 | 0.276 | No | PERIMETER_TOP_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
Total or Average | 4635.80 | 2.831 | 0.251 | 0.276 | |||||||||||||||||
North Total or Average | 1390.74 | 2.831 | 0.251 | 0.276 | |||||||||||||||||
Non-North Total or Average | 3245.06 | 2.831 | 0.251 | 0.276 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | PERIMETER_BOT_ZN_2_WALL_EAST |
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | PERIMETER_BOT_ZN_2_WALL_EAST |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | PERIMETER_BOT_ZN_4_WALL_WEST |
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | PERIMETER_BOT_ZN_4_WALL_WEST |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 08:43:24
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 08:43:24
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
BASEMENT_LIGHTS | BASEMENT | BASEMENT | GENERAL | 10.2732 | 2779.43 | 28553.72 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 49.04 | 0.0000 | Y | 262.84 |
CORE_BOTTOM_LIGHTS | CORE_BOTTOM | CORE_BOTTOM | GENERAL | 10.2732 | 2496.12 | 25643.24 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 49.04 | 0.0000 | Y | 236.05 |
CORE_MID_LIGHTS | CORE_MID | CORE_MID | GENERAL | 10.2732 | 24961.20 | 256432.45 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 49.04 | 0.0000 | Y | 2360.52 |
CORE_TOP_LIGHTS | CORE_TOP | CORE_TOP | GENERAL | 10.2732 | 2496.12 | 25643.24 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 49.04 | 0.0000 | Y | 236.05 |
PERIMETER_BOT_ZN_3_LIGHTS | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3 | GENERAL | 10.2732 | 313.41 | 3219.77 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 29.31 | 0.0000 | Y | 17.72 |
PERIMETER_BOT_ZN_2_LIGHTS | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2 | GENERAL | 10.2732 | 201.98 | 2074.94 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 28.73 | 0.0000 | Y | 11.19 |
PERIMETER_BOT_ZN_1_LIGHTS | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1 | GENERAL | 10.2732 | 313.42 | 3219.84 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 28.46 | 0.0000 | Y | 17.20 |
PERIMETER_BOT_ZN_4_LIGHTS | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4 | GENERAL | 10.2732 | 201.98 | 2074.94 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 28.99 | 0.0000 | Y | 11.29 |
PERIMETER_MID_ZN_3_LIGHTS | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3 | GENERAL | 10.2732 | 3134.13 | 32197.65 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 29.19 | 0.0000 | Y | 176.43 |
PERIMETER_MID_ZN_2_LIGHTS | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2 | GENERAL | 10.2732 | 2019.75 | 20749.39 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 28.66 | 0.0000 | Y | 111.63 |
PERIMETER_MID_ZN_1_LIGHTS | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1 | GENERAL | 10.2732 | 3134.20 | 32198.36 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 28.41 | 0.0000 | Y | 171.73 |
PERIMETER_MID_ZN_4_LIGHTS | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4 | GENERAL | 10.2732 | 2019.75 | 20749.39 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 28.91 | 0.0000 | Y | 112.59 |
PERIMETER_TOP_ZN_3_LIGHTS | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3 | GENERAL | 10.2732 | 313.41 | 3219.77 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 29.19 | 0.0000 | Y | 17.64 |
PERIMETER_TOP_ZN_2_LIGHTS | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2 | GENERAL | 10.2732 | 201.98 | 2074.94 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 28.66 | 0.0000 | Y | 11.16 |
PERIMETER_TOP_ZN_1_LIGHTS | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1 | GENERAL | 10.2732 | 313.42 | 3219.84 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 28.41 | 0.0000 | Y | 17.17 |
PERIMETER_TOP_ZN_4_LIGHTS | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4 | GENERAL | 10.2732 | 201.98 | 2074.94 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 28.90 | 0.0000 | Y | 11.26 |
DATACENTER_BASEMENT_LIGHTS | DATACENTER_BASEMENT_ZN_6 | DATACENTER_BASEMENT_ZN_6 | GENERAL | 10.2732 | 783.68 | 8050.93 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 49.04 | 0.0000 | Y | 74.11 |
DATACENTER_BOT_LIGHTS | DATACENTER_BOT_ZN_6 | DATACENTER_BOT_ZN_6 | GENERAL | 17.8735 | 36.20 | 647.07 | LightsWired | LTG_SCH_DATACENTER | 56.02 | 168.00 | 54.57 | 0.0000 | Y | 6.63 |
DATACENTER_MID_LIGHTS | DATACENTER_MID_ZN_6 | DATACENTER_MID_ZN_6 | GENERAL | 17.8735 | 362.03 | 6470.68 | LightsWired | LTG_SCH_DATACENTER | 56.02 | 168.00 | 54.57 | 0.0000 | Y | 66.28 |
DATACENTER_TOP_LIGHTS | DATACENTER_TOP_ZN_6 | DATACENTER_TOP_ZN_6 | GENERAL | 17.8735 | 36.20 | 647.07 | LightsWired | LTG_SCH_DATACENTER | 56.02 | 168.00 | 54.57 | 0.0000 | Y | 6.63 |
Interior Lighting Total | 10.3445 | 46320.38 | 479162.15 | 1236.86 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
PERIMETER_BOT_ZN_1_DAYLREFPT1 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_DAYLCTRL | SplitFlux | Stepped | 0.39 | 3219.84 | 1241.89 |
PERIMETER_BOT_ZN_1_DAYLREFPT2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_DAYLCTRL | SplitFlux | Stepped | 0.14 | 3219.84 | 445.95 |
PERIMETER_BOT_ZN_2_DAYLREFPT1 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_DAYLCTRL | SplitFlux | Stepped | 0.39 | 2074.94 | 800.30 |
PERIMETER_BOT_ZN_2_DAYLREFPT2 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_DAYLCTRL | SplitFlux | Stepped | 0.14 | 2074.94 | 287.38 |
PERIMETER_BOT_ZN_3_DAYLREFPT1 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_DAYLCTRL | SplitFlux | Stepped | 0.39 | 3219.77 | 1241.86 |
PERIMETER_BOT_ZN_3_DAYLREFPT2 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_DAYLCTRL | SplitFlux | Stepped | 0.14 | 3219.77 | 445.94 |
PERIMETER_BOT_ZN_4_DAYLREFPT1 | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_DAYLCTRL | SplitFlux | Stepped | 0.39 | 2074.94 | 800.30 |
PERIMETER_BOT_ZN_4_DAYLREFPT2 | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_DAYLCTRL | SplitFlux | Stepped | 0.14 | 2074.94 | 287.38 |
PERIMETER_MID_ZN_1_DAYLREFPT1 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_DAYLCTRL | SplitFlux | Stepped | 0.39 | 3219.84 | 1241.89 |
PERIMETER_MID_ZN_1_DAYLREFPT2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_DAYLCTRL | SplitFlux | Stepped | 0.14 | 3219.84 | 445.95 |
PERIMETER_MID_ZN_2_DAYLREFPT1 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_DAYLCTRL | SplitFlux | Stepped | 0.39 | 2074.94 | 800.30 |
PERIMETER_MID_ZN_2_DAYLREFPT2 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_DAYLCTRL | SplitFlux | Stepped | 0.14 | 2074.94 | 287.38 |
PERIMETER_MID_ZN_3_DAYLREFPT1 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_DAYLCTRL | SplitFlux | Stepped | 0.39 | 3219.77 | 1241.86 |
PERIMETER_MID_ZN_3_DAYLREFPT2 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_DAYLCTRL | SplitFlux | Stepped | 0.14 | 3219.77 | 445.94 |
PERIMETER_MID_ZN_4_DAYLREFPT1 | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_DAYLCTRL | SplitFlux | Stepped | 0.39 | 2074.94 | 800.30 |
PERIMETER_MID_ZN_4_DAYLREFPT2 | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_DAYLCTRL | SplitFlux | Stepped | 0.14 | 2074.94 | 287.38 |
PERIMETER_TOP_ZN_1_DAYLREFPT1 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_DAYLCTRL | SplitFlux | Stepped | 0.39 | 3219.84 | 1241.89 |
PERIMETER_TOP_ZN_1_DAYLREFPT2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_DAYLCTRL | SplitFlux | Stepped | 0.14 | 3219.84 | 445.95 |
PERIMETER_TOP_ZN_2_DAYLREFPT1 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_DAYLCTRL | SplitFlux | Stepped | 0.39 | 2074.94 | 800.30 |
PERIMETER_TOP_ZN_2_DAYLREFPT2 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_DAYLCTRL | SplitFlux | Stepped | 0.14 | 2074.94 | 287.38 |
PERIMETER_TOP_ZN_3_DAYLREFPT1 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_DAYLCTRL | SplitFlux | Stepped | 0.39 | 3219.77 | 1241.86 |
PERIMETER_TOP_ZN_3_DAYLREFPT2 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_DAYLCTRL | SplitFlux | Stepped | 0.14 | 3219.77 | 445.94 |
PERIMETER_TOP_ZN_4_DAYLREFPT1 | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_DAYLCTRL | SplitFlux | Stepped | 0.39 | 2074.94 | 800.30 |
PERIMETER_TOP_ZN_4_DAYLREFPT2 | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_DAYLCTRL | SplitFlux | Stepped | 0.14 | 2074.94 | 287.38 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS_A | 13279.00 | AstronomicalClock | - | 41.77 | 41.77 | 104.12 | |
EXTERIOR_LIGHTS_B | 44301.60 | AstronomicalClock | - | 83.77 | 71.17 | 591.85 | |
Exterior Lighting Total | 57580.60 | 695.97 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 08:43:24
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
BYPASS HEAT EXCHANGER | HeatExchanger:FluidToFluid | 2958058.23 | |||||
HEATSYS1 BOILER | Boiler:HotWater | 2469248.63 | 0.81 | ||||
COOLSYS1 CHILLER1 | Chiller:Electric:ReformulatedEIR | 1507316.17 | 6.28 | 1442696.66 | 5.98 | 6.84 | 23.33 |
COOLSYS1 CHILLER2 | Chiller:Electric:ReformulatedEIR | 1507316.17 | 6.28 | 1442696.66 | 5.98 | 6.84 | 23.33 |
CENTRAL TOWER | FluidCooler:TwoSpeed | 582060.00 | |||||
CENTRAL BOILER | Boiler:HotWater | 543970.57 | 0.80 | ||||
TOWERWATERSYS COOLTOWER 1 | CoolingTower:VariableSpeed | 1788404.52 | |||||
TOWERWATERSYS COOLTOWER 2 | CoolingTower:VariableSpeed | 1788404.52 |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
VAV_BOT WITH REHEAT COOLING COIL | Coil:Cooling:Water | 242286.81 | 266205.00 | 177631.86 | 88573.14 | 0.67 | - | 28251.46 | 286.54 |
VAV_MID WITH REHEAT COOLING COIL | Coil:Cooling:Water | 2354776.15 | 2524490.77 | 1676090.29 | 848400.47 | 0.66 | - | 268406.63 | 2722.33 |
VAV_TOP WITH REHEAT COOLING COIL | Coil:Cooling:Water | 243642.38 | 268814.03 | 179507.15 | 89306.88 | 0.67 | - | 28536.96 | 289.44 |
CAV_BAS COOLING COIL | Coil:Cooling:Water | 124171.22 | 149077.94 | 101882.01 | 47195.93 | 0.68 | - | 15614.12 | 158.37 |
AIRLOOP DATACENTER BASEMENT COOLING COIL | Coil:Cooling:WaterToAirHeatPump:EquationFit | 438414.06 | 303822.62 | 134591.44 | 0.69 | 0.00 | |||
AIRLOOP DATACENTER BOT COOLING COIL | Coil:Cooling:WaterToAirHeatPump:EquationFit | 9691.18 | 6727.91 | 2963.28 | 0.69 | 0.00 | |||
AIRLOOP DATACENTER MID COOLING COIL | Coil:Cooling:WaterToAirHeatPump:EquationFit | 92549.83 | 64188.78 | 28361.05 | 0.69 | 0.00 | |||
AIRLOOP DATACENTER TOP COOLING COIL | Coil:Cooling:WaterToAirHeatPump:EquationFit | 9422.96 | 6537.25 | 2885.71 | 0.69 | 0.00 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
None |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
None |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Water | 18977.52 | 17994.89 | - |
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Water | 462014.40 | 437729.20 | - |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Water | 86090.02 | 81585.54 | - |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 14939.37 | 14155.92 | - |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 10215.85 | 9680.00 | - |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 16574.76 | 15705.28 | - |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 8286.08 | 7847.78 | - |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 245103.78 | 232226.85 | - |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 160408.20 | 151980.47 | - |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 241668.01 | 228972.03 | - |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 155852.35 | 147664.46 | - |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 30720.05 | 29105.23 | - |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 20042.61 | 18989.02 | - |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 30353.83 | 28758.30 | - |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 19757.34 | 18718.76 | - |
VAV_BOT WITH REHEAT HEATING COIL | Coil:Heating:Water | 56839.85 | 43740.55 | - |
VAV_MID WITH REHEAT HEATING COIL | Coil:Heating:Water | 544940.17 | 417202.15 | - |
VAV_TOP WITH REHEAT HEATING COIL | Coil:Heating:Water | 53637.39 | 41806.40 | - |
CAV_BAS HEATING COIL | Coil:Heating:Water | 292827.06 | 231340.80 | - |
AIRLOOP DATACENTER BASEMENT HEATING COIL | Coil:Heating:WaterToAirHeatPump:EquationFit | 438414.06 | 0.00 | |
AIRLOOP DATACENTER BOT HEATING COIL | Coil:Heating:WaterToAirHeatPump:EquationFit | 9691.18 | 0.00 | |
AIRLOOP DATACENTER MID HEATING COIL | Coil:Heating:WaterToAirHeatPump:EquationFit | 92549.83 | 0.00 | |
AIRLOOP DATACENTER TOP HEATING COIL | Coil:Heating:WaterToAirHeatPump:EquationFit | 9422.96 | 0.00 | |
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | Coil:Heating:Electric | 18278.08 | 1.00 | |
AIRLOOP DATACENTER BOT_SUPPHEATCOIL | Coil:Heating:Electric | 844.37 | 1.00 | |
AIRLOOP DATACENTER MID_SUPPHEATCOIL | Coil:Heating:Electric | 8443.71 | 1.00 | |
AIRLOOP DATACENTER TOP_SUPPHEATCOIL | Coil:Heating:Electric | 844.37 | 1.00 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
VAV_BOT WITH REHEAT FAN | Fan:VariableVolume | 0.61 | 1314.72 | 10.08 | 21657.98 | 2149.46 | 1.00 | 1.12 | General | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 |
VAV_MID WITH REHEAT FAN | Fan:VariableVolume | 0.61 | 1314.72 | 94.04 | 203206.86 | 2160.95 | 1.00 | 1.08 | General | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 |
VAV_TOP WITH REHEAT FAN | Fan:VariableVolume | 0.61 | 1314.72 | 10.20 | 21920.02 | 2149.46 | 1.00 | 1.12 | General | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:50:00 |
CAV_BAS FAN | Fan:ConstantVolume | 0.60 | 1018.41 | 6.09 | 10319.93 | 1695.65 | 1.00 | 1.15 | General | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
AIRLOOP DATACENTER BASEMENT SUPPLY FAN | Fan:OnOff | 0.62 | 1018.41 | 22.14 | 36508.66 | 1649.25 | 1.00 | 1.14 | General | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 07:10:00 |
AIRLOOP DATACENTER BOT SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.49 | 551.27 | 1120.11 | 1.00 | 1.61 | General | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
AIRLOOP DATACENTER MID SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 4.69 | 5255.32 | 1120.11 | 1.00 | 1.16 | General | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
AIRLOOP DATACENTER TOP SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.48 | 535.34 | 1120.11 | 1.00 | 1.63 | General | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
COOLSYS1 PUMP SECONDARY | Pump:VariableSpeed | Intermittent | 105797.75 | 0.126133 | 20593.62 | 163269.45 | 0.90 | General |
HEATSYS1 PUMP | Pump:VariableSpeed | Intermittent | 180705.70 | 0.021602 | 6505.59 | 301156.09 | 0.90 | General |
COOLSYS1 CHILLER1 PUMP | Pump:ConstantSpeed | Intermittent | 73247.35 | 0.063066 | 7128.83 | 113036.94 | 0.90 | General |
COOLSYS1 CHILLER2 PUMP | Pump:ConstantSpeed | Intermittent | 73247.35 | 0.063066 | 7128.83 | 113036.94 | 0.90 | General |
PLANT CIRC PUMP | Pump:ConstantSpeed | Intermittent | 179045.11 | 0.013471 | 3435.87 | 255050.01 | 0.90 | General |
SWHSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 29891.00 | 0.000440 | 56.21 | 127739.32 | 0.30 | General |
TOWERWATERSYS PUMP | HeaderedPumps:VariableSpeed | Intermittent | 148556.62 | 0.149183 | 36934.41 | 247577.87 | 0.90 | General |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 1.14 | 87921.32 | 0.80 | 0.48 | 0.06 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:43:24
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 81476.80 | 81476.80 | 29.31 | 6.086 | 6.086 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 24.00 | 24.00 | 0.00893 | 27.37 | 0.01446 | 1.200 | 0.00 |
CORE_BOTTOM | 84977.65 | 84977.65 | 34.04 | 6.347 | 6.347 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 24.00 | 24.00 | 0.00887 | 27.37 | 0.01446 | 1.078 | 0.00 |
CORE_MID | 803073.62 | 803073.62 | 321.73 | 59.969 | 59.969 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 24.00 | 24.00 | 0.00889 | 27.37 | 0.01446 | 10.778 | 0.00 |
CORE_TOP | 79160.97 | 79160.97 | 31.71 | 5.911 | 5.911 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 24.00 | 24.00 | 0.00889 | 27.37 | 0.01446 | 1.078 | 0.00 |
PERIMETER_BOT_ZN_3 | 14184.53 | 14184.53 | 45.26 | 1.069 | 1.069 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | 24.00 | 24.00 | 0.00889 | 34.40 | 0.01447 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_2 | 14680.44 | 14680.44 | 72.68 | 1.106 | 1.106 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:50:00 | 24.00 | 24.00 | 0.00874 | 30.52 | 0.01447 | 0.087 | 0.00 |
PERIMETER_BOT_ZN_1 | 16633.14 | 16633.14 | 53.07 | 1.253 | 1.253 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 24.00 | 24.00 | 0.00883 | 34.24 | 0.01447 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_4 | 18514.74 | 18514.74 | 91.67 | 1.395 | 1.395 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 | 24.00 | 24.00 | 0.00869 | 32.91 | 0.01447 | 0.087 | 0.00 |
PERIMETER_MID_ZN_3 | 134507.15 | 134507.15 | 429.17 | 10.137 | 10.137 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 24.00 | 24.00 | 0.00906 | 34.40 | 0.01447 | 1.353 | 0.00 |
PERIMETER_MID_ZN_2 | 151996.02 | 151996.02 | 752.55 | 11.455 | 11.455 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:00:00 | 24.00 | 24.00 | 0.00883 | 30.79 | 0.01447 | 0.872 | 0.00 |
PERIMETER_MID_ZN_1 | 158866.11 | 158866.11 | 506.88 | 11.973 | 11.973 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | 24.00 | 24.00 | 0.00898 | 34.32 | 0.01447 | 1.353 | 0.00 |
PERIMETER_MID_ZN_4 | 161161.07 | 161161.07 | 797.93 | 12.146 | 12.146 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:20:00 | 24.00 | 24.00 | 0.00881 | 32.75 | 0.01447 | 0.872 | 0.00 |
PERIMETER_TOP_ZN_3 | 15153.30 | 15153.30 | 48.35 | 1.142 | 1.142 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | 24.00 | 24.00 | 0.00906 | 34.21 | 0.01447 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_2 | 15453.40 | 15453.40 | 76.51 | 1.165 | 1.165 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:10:00 | 24.00 | 24.00 | 0.00887 | 31.03 | 0.01447 | 0.087 | 0.00 |
PERIMETER_TOP_ZN_1 | 17468.40 | 17468.40 | 55.73 | 1.317 | 1.317 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | 24.00 | 24.00 | 0.00899 | 34.40 | 0.01447 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_4 | 17221.07 | 17221.07 | 85.26 | 1.298 | 1.298 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:20:00 | 24.00 | 24.00 | 0.00883 | 32.75 | 0.01447 | 0.087 | 0.00 |
DATACENTER_BOT_ZN_6 | 8280.16 | 8280.16 | 228.72 | 0.492 | 0.492 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:10:00 | 27.00 | 27.00 | 0.00859 | 30.52 | 0.01447 | 0.016 | 0.00 |
DATACENTER_MID_ZN_6 | 78935.52 | 78935.52 | 2180.37 | 4.692 | 4.692 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:10:00 | 27.00 | 27.00 | 0.00859 | 30.52 | 0.01447 | 0.156 | 0.00 |
DATACENTER_TOP_ZN_6 | 8040.96 | 8040.96 | 222.11 | 0.478 | 0.478 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 27.00 | 27.00 | 0.00859 | 30.70 | 0.01447 | 0.016 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 372434.49 | 372434.49 | 475.24 | 22.136 | 22.136 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 07:00:00 | 27.00 | 27.00 | 0.00854 | 25.75 | 0.01446 | 0.338 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.000 | 1.200 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:10:00 | 21.00 | 23.37 | 0.00230 | -6.30 | 0.00230 | 1.200 | 0.00 |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.000 | 1.078 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 05:50:00 | 17.60 | 21.00 | 0.00230 | -6.30 | 0.00230 | 1.078 | 0.00 |
CORE_MID | 275723.61 | 275723.61 | 110.46 | 12.058 | 12.058 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00800 | -6.30 | 0.00230 | 10.778 | 0.00 |
CORE_TOP | 60293.17 | 60293.17 | 24.15 | 2.657 | 2.657 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00800 | -6.30 | 0.00230 | 1.078 | 0.00 |
PERIMETER_BOT_ZN_3 | 10461.88 | 10461.88 | 33.38 | 0.462 | 0.462 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00744 | -6.30 | 0.00230 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_2 | 7153.34 | 7153.34 | 35.42 | 0.316 | 0.316 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00748 | -6.30 | 0.00230 | 0.087 | 0.00 |
PERIMETER_BOT_ZN_1 | 11605.05 | 11605.05 | 37.03 | 0.512 | 0.512 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00754 | -6.30 | 0.00230 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_4 | 5582.08 | 5582.08 | 27.64 | 0.246 | 0.246 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00716 | -6.30 | 0.00230 | 0.087 | 0.00 |
PERIMETER_MID_ZN_3 | 171564.20 | 171564.20 | 547.41 | 7.586 | 7.586 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00744 | -6.30 | 0.00230 | 1.353 | 0.00 |
PERIMETER_MID_ZN_2 | 112279.75 | 112279.75 | 555.91 | 4.965 | 4.965 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00743 | -6.30 | 0.00230 | 0.872 | 0.00 |
PERIMETER_MID_ZN_1 | 169162.05 | 169162.05 | 539.73 | 7.479 | 7.479 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00743 | -6.30 | 0.00230 | 1.353 | 0.00 |
PERIMETER_MID_ZN_4 | 109094.23 | 109094.23 | 540.14 | 4.823 | 4.823 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00741 | -6.30 | 0.00230 | 0.872 | 0.00 |
PERIMETER_TOP_ZN_3 | 21499.99 | 21499.99 | 68.60 | 0.951 | 0.951 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00745 | -6.30 | 0.00230 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_2 | 14027.22 | 14027.22 | 69.45 | 0.621 | 0.621 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00744 | -6.30 | 0.00230 | 0.087 | 0.00 |
PERIMETER_TOP_ZN_1 | 21243.92 | 21243.92 | 67.78 | 0.940 | 0.940 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00744 | -6.30 | 0.00230 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_4 | 13827.72 | 13827.72 | 68.46 | 0.612 | 0.612 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00743 | -6.30 | 0.00230 | 0.087 | 0.00 |
DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.016 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 05:40:00 | 18.00 | 25.30 | 0.00733 | -6.30 | 0.00230 | 0.016 | 0.00 |
DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.156 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 05:40:00 | 18.00 | 22.84 | 0.00276 | -6.30 | 0.00230 | 0.156 | 0.00 |
DATACENTER_TOP_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.016 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 05:40:00 | 18.00 | 21.01 | 0.00276 | -6.30 | 0.00230 | 0.016 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.338 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 00:50:00 | 18.00 | 27.00 | 0.00850 | -6.30 | 0.00230 | 0.338 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
VAV_BOT WITH REHEAT | 10.08 | 10.08 | 2.61 | 2.61 | 10.0760 | 2.9518 | 10.0760 | 0.2930 | 0.3000 |
VAV_MID WITH REHEAT | 94.04 | 94.04 | 36.91 | 36.91 | 94.0360 | 36.9114 | 94.0360 | 0.3925 | 0.3000 |
VAV_TOP WITH REHEAT | 10.20 | 10.20 | 5.78 | 5.78 | 10.1979 | 5.7804 | 10.1979 | 0.5668 | 0.3000 |
CAV_BAS | 6.09 | 6.09 | 1.20 | 1.20 | 6.0861 | 6.0861 | 6.0861 | 1.0000 | 1.0000 |
AIRLOOP DATACENTER BASEMENT | 22.14 | 22.14 | 0.34 | 0.34 | 22.1366 | 22.1364 | 22.1366 | 1.0000 | 1.0000 |
AIRLOOP DATACENTER BOT | 0.49 | 0.49 | 0.02 | 0.02 | 0.4922 | 0.4922 | 0.4922 | 1.0000 | 1.0000 |
AIRLOOP DATACENTER MID | 4.69 | 4.69 | 0.16 | 0.16 | 4.6918 | 4.6918 | 4.6918 | 1.0000 | 1.0000 |
AIRLOOP DATACENTER TOP | 0.48 | 0.48 | 0.02 | 0.02 | 0.4779 | 0.4779 | 0.4779 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | 18977.523 | 18977.523 | 1.954901 | 0.00016602 | 382.572 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 05:50:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 05:50:00 | 18977.52 | 18977.52 | 1.954901 | 12.80 | 11.27 | 0.00800000 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 0.0000 | 21.00 | 0.00800000 | 49.8624 | 0.00 | 0.00 | 19047.50 | 19047.50 |
CORE_MID VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | 462014.397 | 462014.397 | 19.190077 | 0.00404190 | 10929.409 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 462014.40 | 462014.40 | 19.190077 | 12.80 | 11.27 | 0.00800000 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 0.0000 | 21.00 | 0.00800000 | 49.8624 | 275723.61 | 0.00 | 463523.39 | 463523.39 |
CORE_TOP VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | 86090.017 | 86090.017 | 2.657370 | 0.00075315 | 2272.772 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 86090.02 | 86090.02 | 2.657370 | 12.80 | 11.27 | 0.00800000 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 0.0000 | 21.00 | 0.00800000 | 49.8624 | 60293.17 | 0.00 | 86389.37 | 86389.37 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | 14939.369 | 14939.369 | 0.461816 | 0.00013070 | 394.133 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 14939.37 | 14939.37 | 0.461816 | 12.80 | 11.27 | 0.00800000 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 0.0000 | 21.00 | 0.00743951 | 46.4159 | 10461.88 | 0.00 | 14989.41 | 14989.41 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | 10215.847 | 10215.847 | 0.315843 | 0.00008937 | 269.500 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 10215.85 | 10215.85 | 0.315843 | 12.80 | 11.27 | 0.00800000 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 0.0000 | 21.00 | 0.00748356 | 46.6872 | 7153.34 | 0.00 | 10249.95 | 10249.95 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | 16574.759 | 16574.759 | 0.512475 | 0.00014500 | 437.238 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 16574.76 | 16574.76 | 0.512475 | 12.80 | 11.27 | 0.00800000 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 0.0000 | 21.00 | 0.00753960 | 47.0321 | 11605.05 | 0.00 | 16629.99 | 16629.99 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | 8286.083 | 8286.083 | 0.279056 | 0.00007249 | 210.739 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 8286.08 | 8286.08 | 0.279056 | 12.80 | 11.27 | 0.00800000 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 0.0000 | 21.00 | 0.00716250 | 44.7088 | 5582.08 | 0.00 | 8311.68 | 8311.68 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | 245103.783 | 245103.783 | 7.585691 | 0.00214427 | 6462.915 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 245103.78 | 245103.78 | 7.585691 | 12.80 | 11.27 | 0.00800000 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 0.0000 | 21.00 | 0.00743552 | 46.3933 | 171564.20 | 0.00 | 245899.87 | 245899.87 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | 160408.196 | 160408.196 | 4.964616 | 0.00140332 | 4229.593 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 160408.20 | 160408.20 | 4.964616 | 12.80 | 11.27 | 0.00800000 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 0.0000 | 21.00 | 0.00742697 | 46.3408 | 112279.75 | 0.00 | 160928.75 | 160928.75 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | 241668.014 | 241668.014 | 7.479186 | 0.00211422 | 6372.387 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 241668.01 | 241668.01 | 7.479186 | 12.80 | 11.27 | 0.00800000 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 0.0000 | 21.00 | 0.00742756 | 46.3442 | 169162.05 | 0.00 | 242453.43 | 242453.43 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | 155852.349 | 155852.349 | 4.823429 | 0.00136346 | 4109.537 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 155852.35 | 155852.35 | 4.823429 | 12.80 | 11.27 | 0.00800000 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 0.0000 | 21.00 | 0.00741025 | 46.2378 | 109094.23 | 0.00 | 156358.63 | 156358.63 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | 30720.046 | 30720.046 | 0.951089 | 0.00026875 | 809.897 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 30720.05 | 30720.05 | 0.951089 | 12.80 | 11.27 | 0.00800000 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 0.0000 | 21.00 | 0.00744711 | 46.4659 | 21499.99 | 0.00 | 30818.88 | 30818.88 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | 20042.609 | 20042.609 | 0.620532 | 0.00017534 | 528.394 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 20042.61 | 20042.61 | 0.620532 | 12.80 | 11.27 | 0.00800000 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 0.0000 | 21.00 | 0.00743631 | 46.3996 | 14027.22 | 0.00 | 20107.05 | 20107.05 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | 30353.829 | 30353.829 | 0.939737 | 0.00026555 | 800.248 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 30353.83 | 30353.83 | 0.939737 | 12.80 | 11.27 | 0.00800000 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 0.0000 | 21.00 | 0.00744096 | 46.4280 | 21243.92 | 0.00 | 30451.52 | 30451.52 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | 19757.339 | 19757.339 | 0.611693 | 0.00017285 | 520.875 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 19757.34 | 19757.34 | 0.611693 | 12.80 | 11.27 | 0.00800000 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 0.0000 | 21.00 | 0.00742897 | 46.3544 | 13827.72 | 0.00 | 19820.88 | 19820.88 |
VAV_BOT WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | VAV_BOT WITH REHEAT | 242286.813 | -999.000 | 10.075991 | 0.01030744 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 242286.81 | 187471.49 | 10.075991 | 26.71 | 18.41 | 0.01033215 | 10.99 | 10.99 | 0.00850000 | 34.40 | 0.01447326 | 23.54 | 25.1905 | 24.00 | 0.00887462 | 46.0359 | 129374.30 | 0.00 | 248147.72 | 182657.25 |
VAV_BOT WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoopHVAC | VAV_BOT WITH REHEAT | 56839.848 | 56839.848 | 3.022797 | 0.00049726 | 935.402 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 56839.85 | 56839.85 | 3.022797 | -3.32 | -3.62 | 0.00278205 | 12.80 | 11.27 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 83.9683 | 21.02 | 0.00601079 | 37.5427 | 34802.34 | 0.00 | 52916.40 | 52916.40 |
VAV_MID WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | VAV_MID WITH REHEAT | 2354776.150 | -999.000 | 94.036032 | 0.10017762 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 2354776.15 | 1781328.00 | 94.036032 | 26.99 | 18.67 | 0.01055269 | 10.98 | 10.98 | 0.00850000 | 34.40 | 0.01447326 | 23.54 | 26.9917 | 24.00 | 0.00897329 | 46.5413 | 1172846.59 | 0.00 | 2410437.32 | 1739582.96 |
VAV_MID WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoopHVAC | VAV_MID WITH REHEAT | 544940.174 | 544940.174 | 28.210810 | 0.00476737 | 8945.378 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 06:20:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 544940.17 | 544940.17 | 28.210810 | -3.76 | -3.83 | 0.00281427 | 12.80 | 11.27 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 89.9724 | 19.60 | 0.00713138 | 48.5308 | 411160.19 | 0.00 | 504716.89 | 504716.89 |
VAV_TOP WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | VAV_TOP WITH REHEAT | 243642.385 | -999.000 | 10.197899 | 0.01036511 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:50:00 | 243642.38 | 188481.55 | 10.197899 | 26.60 | 18.37 | 0.01032177 | 10.99 | 10.99 | 0.00850000 | 34.40 | 0.01447326 | 23.54 | 24.8893 | 24.00 | 0.00893533 | 46.3474 | 134529.52 | 0.00 | 249559.29 | 183599.75 |
VAV_TOP WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoopHVAC | VAV_TOP WITH REHEAT | 53637.388 | 53637.388 | 3.059370 | 0.00046924 | 888.202 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 05:40:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 53637.39 | 53637.39 | 3.059370 | -2.23 | -2.37 | 0.00316307 | 12.80 | 11.27 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 82.9645 | 17.60 | 0.00716335 | 55.2617 | 51870.08 | 0.00 | 50582.92 | 50582.92 |
CAV_BAS COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | CAV_BAS | 124171.224 | -999.000 | 6.086107 | 0.00528253 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:20:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 124171.22 | 97239.51 | 6.086107 | 24.79 | 17.54 | 0.01002476 | 11.37 | 11.18 | 0.00850000 | 27.97 | 0.01446155 | 21.78 | 19.7196 | 24.00 | 0.00892815 | 46.3094 | 80359.54 | 0.00 | 127479.11 | 94773.08 |
CAV_BAS HEATING COIL | Coil:Heating:Water | AirLoopHVAC | CAV_BAS | 292827.055 | 292827.055 | 6.086107 | 0.00256178 | 6501.963 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 292827.06 | 292827.06 | 6.086107 | -1.24 | -3.20 | 0.00229779 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 19.7196 | 23.47 | 0.00229779 | 12.4368 | 0.00 | 0.00 | 244374.09 | 244374.09 |
AIRLOOP DATACENTER BASEMENT COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | 438414.063 | 303822.623 | 22.136565 | 0.01073673 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 07:10:00 | 406380.19 | 398800.54 | -999.0 | 28.56 | 17.68 | 0.00863298 | 12.80 | 11.77 | 0.00850000 | 34.40 | 0.01447326 | 23.54 | -999.0000 | 27.00 | 0.00854220 | 37.1020 | 371935.50 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BOT COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER BOT | 9691.181 | 6727.905 | 0.492156 | 0.00023734 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:10:00 | 8973.66 | 8626.58 | -999.0 | 28.10 | 17.64 | 0.00877422 | 12.80 | 11.77 | 0.00850000 | 30.70 | 0.01446650 | 22.54 | -999.0000 | 27.00 | 0.00858744 | 37.2936 | 8278.52 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER MID COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER MID | 92549.834 | 64188.782 | 4.691799 | 0.00226654 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:10:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:10:00 | 85722.43 | 82252.88 | -999.0 | 28.10 | 17.65 | 0.00878749 | 12.80 | 11.77 | 0.00850000 | 30.52 | 0.01446618 | 22.49 | -999.0000 | 27.00 | 0.00859177 | 37.3123 | 78935.52 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER TOP COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER TOP | 9422.961 | 6537.255 | 0.477940 | 0.00023077 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 8727.11 | 8380.12 | -999.0 | 28.10 | 17.65 | 0.00878227 | 12.80 | 11.77 | 0.00850000 | 30.70 | 0.01446650 | 22.54 | -999.0000 | 27.00 | 0.00859007 | 37.3049 | 8040.96 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BASEMENT HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | 438414.063 | 438414.063 | 22.136565 | 0.01073673 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 438414.06 | 438414.06 | 22.136565 | -6.30 | -6.30 | 0.00229779 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 1.5287 | 27.00 | 0.00850000 | 36.9155 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BOT HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER BOT | 9691.181 | 9691.181 | 0.492156 | 0.00023734 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 9691.18 | 9691.18 | 0.492156 | -6.30 | -6.30 | 0.00229779 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 3.1763 | 25.87 | 0.00732509 | 34.0766 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER MID HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER MID | 92549.834 | 92549.834 | 4.691799 | 0.00226654 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 92549.83 | 92549.83 | 4.691799 | -6.30 | -6.30 | 0.00229779 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 3.3318 | 23.96 | 0.00276482 | 14.5193 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER TOP HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER TOP | 9422.961 | 9422.961 | 0.477940 | 0.00023077 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 9422.96 | 9422.96 | 0.477940 | -6.30 | -6.30 | 0.00229779 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 3.2708 | 22.88 | 0.00276446 | 15.4880 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | 18278.075 | 18278.075 | -999.0 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 18278.08 | 18278.08 | 22.136565 | -0.10 | -0.10 | 0.00840519 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 1.5287 | 27.00 | 0.00850000 | 36.9155 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BOT_SUPPHEATCOIL | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER BOT | 844.371 | 844.371 | -999.0 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 844.37 | 844.37 | 0.492156 | -0.20 | -0.20 | 0.00716540 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 3.1763 | 25.87 | 0.00732509 | 34.0766 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER MID_SUPPHEATCOIL | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER MID | 8443.713 | 8443.713 | -999.0 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 8443.71 | 8443.71 | 4.691799 | -0.21 | -1.88 | 0.00274926 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 3.3318 | 23.96 | 0.00276482 | 14.5193 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER TOP_SUPPHEATCOIL | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER TOP | 844.371 | 844.371 | -999.0 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 844.37 | 844.37 | 0.477940 | -0.21 | -1.88 | 0.00274920 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 3.2708 | 22.88 | 0.00276446 | 15.4880 | 0.00 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 08:43:24
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
CORE_BOTTOM VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | CORE_BOTTOM | N/A | N/A | N/A | Yes | Yes | Yes | No | 18977.523 | 18977.523 | 1.954901 | 0.00016602 | 382.572 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 21.59986053 | 54.44 | 82.22 | 27.78 | 2518943.24 | 0.7534 | 0.768555 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 05:50:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 05:50:00 | Sensible | 18977.52 | 18977.52 | 1.0000 | 2.26959476 | 1.954901 | 12.80 | 11.27 | 0.00800000 | 33059.8 | 40.00 | 20.76 | 0.00800000 | 60796.0 | 0.16600672 | 60.00 | 32.22 | 27.78 | 0.000 | 18977.52 | -6.30 | 0.00229779 | -6.30 | 0.00000000 | 0.0000 | 21.00 | 0.00800000 | 21.00 | 0.00800000 | 49.8624 | 0.00 | 0.00 | 19047.50 | 19047.50 | 2.26959476 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 21.03 | 14.86 | 0.00800000 | 41452.3 | |
CORE_MID VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | CORE_MID | N/A | N/A | N/A | Yes | Yes | Yes | No | 462014.397 | 462014.397 | 19.190077 | 0.00404190 | 10929.409 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 21.59986053 | 54.44 | 82.22 | 27.78 | 2518943.24 | 18.3416 | 18.710728 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 462014.40 | 462014.40 | 1.0000 | 22.27922897 | 19.190077 | 12.80 | 11.27 | 0.00800000 | 33059.8 | 40.00 | 20.76 | 0.00800000 | 60796.0 | 4.04149118 | 60.00 | 32.22 | 27.78 | 0.000 | 462014.40 | -6.30 | 0.00229779 | -6.30 | 0.00000000 | 0.0000 | 20.87 | 0.00800000 | 21.00 | 0.00800000 | 49.8624 | 275723.61 | 0.00 | 463523.39 | 463523.39 | 22.27922897 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 33.20 | 19.09 | 0.00800000 | 53865.0 | |
CORE_TOP VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | CORE_TOP | N/A | N/A | N/A | Yes | Yes | Yes | No | 86090.017 | 86090.017 | 2.657370 | 0.00075315 | 2272.772 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 21.59986053 | 54.44 | 82.22 | 27.78 | 2518943.24 | 3.4177 | 3.486486 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 86090.02 | 86090.02 | 1.0000 | 3.08514429 | 2.657370 | 12.80 | 11.27 | 0.00800000 | 33059.8 | 40.00 | 20.76 | 0.00800000 | 60796.0 | 0.75307620 | 60.00 | 32.22 | 27.78 | 0.000 | 86090.02 | -6.30 | 0.00229779 | -6.30 | 0.00000000 | 0.0000 | 20.91 | 0.00800000 | 21.00 | 0.00800000 | 49.8624 | 60293.17 | 0.00 | 86389.37 | 86389.37 | 3.08514429 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.26 | 21.26 | 0.00800000 | 61061.6 | |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | PERIMETER_BOT_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 14939.369 | 14939.369 | 0.461816 | 0.00013070 | 394.133 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 21.59986053 | 54.44 | 82.22 | 27.78 | 2518943.24 | 0.5931 | 0.605017 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 14939.37 | 14939.37 | 1.0000 | 0.53615779 | 0.461816 | 12.80 | 11.27 | 0.00800000 | 33059.8 | 40.00 | 20.76 | 0.00800000 | 60796.0 | 0.13068279 | 60.00 | 32.22 | 27.78 | 0.000 | 14939.37 | -6.30 | 0.00229779 | -6.30 | 0.00000000 | 0.0000 | 20.91 | 0.00743951 | 21.00 | 0.00743951 | 46.4159 | 10461.88 | 0.00 | 14989.41 | 14989.41 | 0.53615779 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.22 | 21.25 | 0.00800000 | 61016.9 | |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | PERIMETER_BOT_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 10215.847 | 10215.847 | 0.315843 | 0.00008937 | 269.500 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 21.59986053 | 54.44 | 82.22 | 27.78 | 2518943.24 | 0.4056 | 0.413723 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 10215.85 | 10215.85 | 1.0000 | 0.36668589 | 0.315843 | 12.80 | 11.27 | 0.00800000 | 33059.8 | 40.00 | 20.76 | 0.00800000 | 60796.0 | 0.08936357 | 60.00 | 32.22 | 27.78 | 0.000 | 10215.85 | -6.30 | 0.00229779 | -6.30 | 0.00000000 | 0.0000 | 20.95 | 0.00748356 | 21.00 | 0.00748356 | 46.6872 | 7153.34 | 0.00 | 10249.95 | 10249.95 | 0.36668589 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.21 | 21.25 | 0.00800000 | 61012.8 | |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | PERIMETER_BOT_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 16574.759 | 16574.759 | 0.512475 | 0.00014500 | 437.238 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 21.59986053 | 54.44 | 82.22 | 27.78 | 2518943.24 | 0.6580 | 0.671247 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 16574.76 | 16574.76 | 1.0000 | 0.59497102 | 0.512475 | 12.80 | 11.27 | 0.00800000 | 33059.8 | 40.00 | 20.76 | 0.00800000 | 60796.0 | 0.14498843 | 60.00 | 32.22 | 27.78 | 0.000 | 16574.76 | -6.30 | 0.00229779 | -6.30 | 0.00000000 | 0.0000 | 20.95 | 0.00753960 | 21.00 | 0.00753960 | 47.0321 | 11605.05 | 0.00 | 16629.99 | 16629.99 | 0.59497102 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.21 | 21.24 | 0.00800000 | 61010.7 | |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | PERIMETER_BOT_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 8286.083 | 8286.083 | 0.279056 | 0.00007249 | 210.739 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 21.59986053 | 54.44 | 82.22 | 27.78 | 2518943.24 | 0.3290 | 0.335571 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 8286.08 | 8286.08 | 1.0000 | 0.32397714 | 0.279056 | 12.80 | 11.27 | 0.00800000 | 33059.8 | 40.00 | 20.76 | 0.00800000 | 60796.0 | 0.07248287 | 60.00 | 32.22 | 27.78 | 0.000 | 8286.08 | -6.30 | 0.00229779 | -6.30 | 0.00000000 | 0.0000 | 20.91 | 0.00716250 | 21.00 | 0.00716250 | 44.7088 | 5582.08 | 0.00 | 8311.68 | 8311.68 | 0.32397714 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 37.96 | 20.57 | 0.00800000 | 58715.0 | |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | PERIMETER_MID_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 245103.783 | 245103.783 | 7.585691 | 0.00214427 | 6462.915 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 21.59986053 | 54.44 | 82.22 | 27.78 | 2518943.24 | 9.7304 | 9.926250 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 245103.78 | 245103.78 | 1.0000 | 8.80680978 | 7.585691 | 12.80 | 11.27 | 0.00800000 | 33059.8 | 40.00 | 20.76 | 0.00800000 | 60796.0 | 2.14405608 | 60.00 | 32.22 | 27.78 | 0.000 | 245103.78 | -6.30 | 0.00229779 | -6.30 | 0.00000000 | 0.0000 | 20.95 | 0.00743552 | 21.00 | 0.00743552 | 46.3933 | 171564.20 | 0.00 | 245899.87 | 245899.87 | 8.80680978 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.18 | 21.24 | 0.00800000 | 60981.4 | |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | PERIMETER_MID_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 160408.196 | 160408.196 | 4.964616 | 0.00140332 | 4229.593 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 21.59986053 | 54.44 | 82.22 | 27.78 | 2518943.24 | 6.3681 | 6.496235 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 160408.20 | 160408.20 | 1.0000 | 5.76380251 | 4.964616 | 12.80 | 11.27 | 0.00800000 | 33059.8 | 40.00 | 20.76 | 0.00800000 | 60796.0 | 1.40317772 | 60.00 | 32.22 | 27.78 | 0.000 | 160408.20 | -6.30 | 0.00229779 | -6.30 | 0.00000000 | 0.0000 | 20.95 | 0.00742697 | 21.00 | 0.00742697 | 46.3408 | 112279.75 | 0.00 | 160928.75 | 160928.75 | 5.76380251 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.18 | 21.24 | 0.00800000 | 60980.4 | |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | PERIMETER_MID_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 241668.014 | 241668.014 | 7.479186 | 0.00211422 | 6372.387 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 21.59986053 | 54.44 | 82.22 | 27.78 | 2518943.24 | 9.5940 | 9.787107 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 241668.01 | 241668.01 | 1.0000 | 8.68315962 | 7.479186 | 12.80 | 11.27 | 0.00800000 | 33059.8 | 40.00 | 20.76 | 0.00800000 | 60796.0 | 2.11400154 | 60.00 | 32.22 | 27.78 | 0.000 | 241668.01 | -6.30 | 0.00229779 | -6.30 | 0.00000000 | 0.0000 | 20.95 | 0.00742756 | 21.00 | 0.00742756 | 46.3442 | 169162.05 | 0.00 | 242453.43 | 242453.43 | 8.68315962 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.18 | 21.24 | 0.00800000 | 60982.1 | |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | PERIMETER_MID_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 155852.349 | 155852.349 | 4.823429 | 0.00136346 | 4109.537 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 21.59986053 | 54.44 | 82.22 | 27.78 | 2518943.24 | 6.1872 | 6.311732 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 155852.35 | 155852.35 | 1.0000 | 5.59988832 | 4.823429 | 12.80 | 11.27 | 0.00800000 | 33059.8 | 40.00 | 20.76 | 0.00800000 | 60796.0 | 1.36332525 | 60.00 | 32.22 | 27.78 | 0.000 | 155852.35 | -6.30 | 0.00229779 | -6.30 | 0.00000000 | 0.0000 | 20.95 | 0.00741025 | 21.00 | 0.00741025 | 46.2378 | 109094.23 | 0.00 | 156358.63 | 156358.63 | 5.59988832 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.18 | 21.24 | 0.00800000 | 60981.6 | |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | PERIMETER_TOP_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 30720.046 | 30720.046 | 0.951089 | 0.00026875 | 809.897 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 21.59986053 | 54.44 | 82.22 | 27.78 | 2518943.24 | 1.2196 | 1.244105 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 30720.05 | 30720.05 | 1.0000 | 1.10419243 | 0.951089 | 12.80 | 11.27 | 0.00800000 | 33059.8 | 40.00 | 20.76 | 0.00800000 | 60796.0 | 0.26872495 | 60.00 | 32.22 | 27.78 | 0.000 | 30720.05 | -6.30 | 0.00229779 | -6.30 | 0.00000000 | 0.0000 | 20.95 | 0.00744711 | 21.00 | 0.00744711 | 46.4659 | 21499.99 | 0.00 | 30818.88 | 30818.88 | 1.10419243 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.17 | 21.23 | 0.00800000 | 60970.6 | |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | PERIMETER_TOP_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 20042.609 | 20042.609 | 0.620532 | 0.00017534 | 528.394 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 21.59986053 | 54.44 | 82.22 | 27.78 | 2518943.24 | 0.7957 | 0.811689 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 20042.61 | 20042.61 | 1.0000 | 0.72042254 | 0.620532 | 12.80 | 11.27 | 0.00800000 | 33059.8 | 40.00 | 20.76 | 0.00800000 | 60796.0 | 0.17532360 | 60.00 | 32.22 | 27.78 | 0.000 | 20042.61 | -6.30 | 0.00229779 | -6.30 | 0.00000000 | 0.0000 | 20.95 | 0.00743631 | 21.00 | 0.00743631 | 46.3996 | 14027.22 | 0.00 | 20107.05 | 20107.05 | 0.72042254 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.17 | 21.23 | 0.00800000 | 60969.9 | |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | PERIMETER_TOP_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 30353.829 | 30353.829 | 0.939737 | 0.00026555 | 800.248 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 21.59986053 | 54.44 | 82.22 | 27.78 | 2518943.24 | 1.2050 | 1.229274 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 30353.83 | 30353.83 | 1.0000 | 1.09101264 | 0.939737 | 12.80 | 11.27 | 0.00800000 | 33059.8 | 40.00 | 20.76 | 0.00800000 | 60796.0 | 0.26552145 | 60.00 | 32.22 | 27.78 | 0.000 | 30353.83 | -6.30 | 0.00229779 | -6.30 | 0.00000000 | 0.0000 | 20.95 | 0.00744096 | 21.00 | 0.00744096 | 46.4280 | 21243.92 | 0.00 | 30451.52 | 30451.52 | 1.09101264 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.17 | 21.23 | 0.00800000 | 60971.1 | |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | PERIMETER_TOP_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 19757.339 | 19757.339 | 0.611693 | 0.00017285 | 520.875 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 21.59986053 | 54.44 | 82.22 | 27.78 | 2518943.24 | 0.7844 | 0.800136 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 19757.34 | 19757.34 | 1.0000 | 0.71016157 | 0.611693 | 12.80 | 11.27 | 0.00800000 | 33059.8 | 40.00 | 20.76 | 0.00800000 | 60796.0 | 0.17282819 | 60.00 | 32.22 | 27.78 | 0.000 | 19757.34 | -6.30 | 0.00229779 | -6.30 | 0.00000000 | 0.0000 | 20.95 | 0.00742897 | 21.00 | 0.00742897 | 46.3544 | 13827.72 | 0.00 | 19820.88 | 19820.88 | 0.71016157 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.17 | 21.23 | 0.00800000 | 60970.2 | |
VAV_BOT WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV_BOT WITH REHEAT | CORE_BOTTOM; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 242286.813 | -999.000 | 10.075991 | 0.01030744 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1024.0470 | 1004.8586 | 1.1610 | VAV_BOT WITH REHEAT FAN | Fan:VariableVolume | 10.075991 | 11.69798873 | 4197.9300 | 999.8980 | 126.11983640 | 12.27 | 6.67 | 5.60 | 2964876.57 | 8.1719 | 8.171902 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | Sensible | 242286.81 | 187471.49 | 1.0000 | 11.69798873 | 10.075991 | 26.71 | 18.41 | 0.01033215 | 53188.8 | 10.99 | 10.99 | 0.00850000 | 32476.9 | 10.30638965 | 6.67 | 12.27 | 5.60 | 21657.985 | 220628.83 | 34.40 | 0.01447326 | 23.54 | 2.53819000 | 25.1905 | 24.00 | 0.00887462 | 24.00 | 0.00887462 | 46.0359 | 129374.30 | 0.00 | 248147.72 | 182657.25 | 11.69798873 | 26.71 | 18.81 | 0.01033215 | 53188.8 | 11.46 | 11.14 | 0.00811253 | 31975.9 | |
VAV_BOT WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV_BOT WITH REHEAT | CORE_BOTTOM; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 56839.848 | 56839.848 | 3.022797 | 0.00049726 | 935.402 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | VAV_BOT WITH REHEAT FAN | Fan:VariableVolume | 10.075991 | 11.69798873 | 4197.9300 | 999.8980 | 21.59986053 | 54.44 | 82.22 | 27.78 | 2518943.24 | 2.2565 | 2.301909 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 56839.85 | 56839.85 | 1.0000 | 3.50939662 | 3.022797 | -3.32 | -3.62 | 0.00278205 | 3606.4 | 12.80 | 11.27 | 0.00800000 | 33059.8 | 0.49720906 | 60.00 | 32.22 | 27.78 | 0.000 | 56839.85 | -6.30 | 0.00229779 | -6.30 | 2.53819000 | 83.9683 | 12.30 | 0.00531841 | 21.02 | 0.00601079 | 37.5427 | 34802.34 | 0.00 | 52916.40 | 52916.40 | 3.50939662 | 2.80 | 0.20 | 0.00278205 | 9785.8 | 17.73 | 8.10 | 0.00278205 | 24864.3 | |
VAV_MID WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV_MID WITH REHEAT | CORE_MID; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 2354776.150 | -999.000 | 94.036032 | 0.10017762 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1024.4569 | 1004.8586 | 1.1610 | VAV_MID WITH REHEAT FAN | Fan:VariableVolume | 94.036032 | 109.17362721 | 4197.9300 | 999.8980 | 126.11983640 | 12.27 | 6.67 | 5.60 | 2964876.57 | 79.4224 | 79.422401 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | Sensible | 2354776.15 | 1781328.00 | 1.0000 | 109.17362721 | 94.036032 | 26.99 | 18.67 | 0.01055269 | 54036.9 | 10.98 | 10.98 | 0.00850000 | 32467.8 | 100.16740179 | 6.67 | 12.27 | 5.60 | 203206.858 | 2151569.29 | 34.40 | 0.01447326 | 23.54 | 25.38195000 | 26.9917 | 24.00 | 0.00897329 | 24.00 | 0.00897329 | 46.5413 | 1172846.59 | 0.00 | 2410437.32 | 1739582.96 | 109.17362721 | 26.99 | 19.07 | 0.01055269 | 54036.9 | 11.43 | 11.14 | 0.00811638 | 31958.0 | |
VAV_MID WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV_MID WITH REHEAT | CORE_MID; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 544940.174 | 544940.174 | 28.210810 | 0.00476737 | 8945.378 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | VAV_MID WITH REHEAT FAN | Fan:VariableVolume | 94.036032 | 109.17362721 | 4197.9300 | 999.8980 | 21.59986053 | 54.44 | 82.22 | 27.78 | 2518943.24 | 21.6337 | 22.069069 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 06:20:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 544940.17 | 544940.17 | 1.0000 | 32.75208816 | 28.210810 | -3.76 | -3.83 | 0.00281427 | 3242.6 | 12.80 | 11.27 | 0.00800000 | 33059.8 | 4.76688804 | 60.00 | 32.22 | 27.78 | 0.000 | 544940.17 | -6.30 | 0.00229779 | -6.30 | 25.38195000 | 89.9724 | 19.05 | 0.00744830 | 19.60 | 0.00713138 | 48.5308 | 411160.19 | 0.00 | 504716.89 | 504716.89 | 32.75208816 | 2.80 | 0.25 | 0.00281427 | 9866.5 | 18.06 | 8.29 | 0.00281427 | 25276.7 | |
VAV_TOP WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV_TOP WITH REHEAT | CORE_TOP; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 243642.385 | -999.000 | 10.197899 | 0.01036511 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1024.0276 | 1004.8586 | 1.1610 | VAV_TOP WITH REHEAT FAN | Fan:VariableVolume | 10.197899 | 11.83952188 | 4197.9300 | 999.8980 | 126.11983640 | 12.27 | 6.67 | 5.60 | 2964876.57 | 8.2176 | 8.217623 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:50:00 | Sensible | 243642.38 | 188481.55 | 1.0000 | 11.83952188 | 10.197899 | 26.60 | 18.37 | 0.01032177 | 53055.6 | 10.99 | 10.99 | 0.00850000 | 32476.9 | 10.36405293 | 6.67 | 12.27 | 5.60 | 21920.023 | 221722.36 | 34.40 | 0.01447326 | 23.54 | 2.53819000 | 24.8893 | 24.00 | 0.00893533 | 24.00 | 0.00893533 | 46.3474 | 134529.52 | 0.00 | 249559.29 | 183599.75 | 11.83952188 | 26.60 | 18.77 | 0.01032177 | 53055.6 | 11.46 | 11.14 | 0.00811296 | 31977.1 | |
VAV_TOP WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV_TOP WITH REHEAT | CORE_TOP; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 53637.388 | 53637.388 | 3.059370 | 0.00046924 | 888.202 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | VAV_TOP WITH REHEAT FAN | Fan:VariableVolume | 10.197899 | 11.83952188 | 4197.9300 | 999.8980 | 21.59986053 | 54.44 | 82.22 | 27.78 | 2518943.24 | 2.1294 | 2.172215 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 05:40:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 53637.39 | 53637.39 | 1.0000 | 3.55185656 | 3.059370 | -2.23 | -2.37 | 0.00316307 | 5658.5 | 12.80 | 11.27 | 0.00800000 | 33059.8 | 0.46919540 | 60.00 | 32.22 | 27.78 | 0.000 | 53637.39 | -6.30 | 0.00229779 | -6.30 | 2.53819000 | 82.9645 | 17.60 | 0.00737703 | 17.60 | 0.00716335 | 55.2617 | 51870.08 | 0.00 | 50582.92 | 50582.92 | 3.55185656 | 2.80 | 0.76 | 0.00316307 | 10740.7 | 16.89 | 8.15 | 0.00316307 | 24981.9 | |
CAV_BAS COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | CAV_BAS | BASEMENT | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 124171.224 | -999.000 | 6.086107 | 0.00528253 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1023.4755 | 1004.8586 | 1.1610 | CAV_BAS FAN | Fan:ConstantVolume | 6.086107 | 7.06582703 | 4197.9300 | 999.8980 | 126.11983640 | 12.27 | 6.67 | 5.60 | 2964876.57 | 4.1881 | 4.188074 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:20:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:20:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | Sensible | 124171.22 | 97239.51 | 1.0000 | 7.06582703 | 6.086107 | 24.79 | 17.54 | 0.01002476 | 50439.2 | 11.37 | 11.18 | 0.00850000 | 32865.7 | 5.28199203 | 6.67 | 12.27 | 5.60 | 10319.933 | 113851.29 | 27.97 | 0.01446155 | 21.78 | 1.20015641 | 19.7196 | 24.00 | 0.00892815 | 24.00 | 0.00892815 | 46.3094 | 80359.54 | 0.00 | 127479.11 | 94773.08 | 7.06582703 | 24.79 | 17.93 | 0.01002476 | 50439.2 | 11.68 | 11.32 | 0.00818988 | 32397.5 | |
CAV_BAS HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | CAV_BAS | BASEMENT | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 292827.055 | 292827.055 | 6.086107 | 0.00256178 | 6501.963 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | CAV_BAS FAN | Fan:ConstantVolume | 6.086107 | 7.06582703 | 4197.9300 | 999.8980 | 21.59986053 | 54.44 | 82.22 | 27.78 | 2518943.24 | 11.6250 | 11.858954 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 292827.06 | 292827.06 | 1.0000 | 7.06582703 | 6.086107 | -1.24 | -3.20 | 0.00229779 | 4493.0 | 40.00 | 20.76 | 0.00800000 | 60796.0 | 2.56151750 | 60.00 | 32.22 | 27.78 | 0.000 | 292827.06 | -6.30 | 0.00229779 | -6.30 | 1.20015641 | 19.7196 | 0.00 | 0.00229779 | 23.47 | 0.00229779 | 12.4368 | 0.00 | 0.00 | 244374.09 | 244374.09 | 7.06582703 | 12.80 | 5.08 | 0.00229779 | 18663.3 | 47.07 | 19.04 | 0.00229779 | 53248.6 | |
AIRLOOP DATACENTER BASEMENT COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | DATACENTER_BASEMENT_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 438414.063 | 303822.623 | 22.136565 | 0.01073673 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1020.8883 | 1004.8586 | 1.1610 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 07:10:00 | Sensible | 406380.19 | 398800.54 | 0.9269 | -999.0 | -999.0 | 28.56 | 17.68 | 0.00863298 | 50742.7 | 12.80 | 11.77 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 406380.19 | 34.40 | 0.01447326 | 23.54 | 0.33839277 | -999.0000 | 27.00 | 0.00854220 | 27.00 | 0.00854220 | 37.1020 | 371935.50 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BOT COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BOT | DATACENTER_BOT_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 9691.181 | 6727.905 | 0.492156 | 0.00023734 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1021.1508 | 1004.8586 | 1.1610 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:10:00 | Sensible | 8973.66 | 8626.58 | 0.9260 | -999.0 | -999.0 | 28.10 | 17.64 | 0.00877422 | 50635.3 | 12.80 | 11.77 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 8973.66 | 30.70 | 0.01446650 | 22.54 | 0.01563234 | -999.0000 | 27.00 | 0.00858744 | 27.00 | 0.00858744 | 37.2936 | 8278.52 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER MID COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER MID | DATACENTER_MID_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 92549.834 | 64188.782 | 4.691799 | 0.00226654 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1021.1755 | 1004.8586 | 1.1610 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:10:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:10:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:10:00 | Sensible | 85722.43 | 82252.88 | 0.9262 | -999.0 | -999.0 | 28.10 | 17.65 | 0.00878749 | 50669.0 | 12.80 | 11.77 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 85722.43 | 30.52 | 0.01446618 | 22.49 | 0.15632344 | -999.0000 | 27.00 | 0.00859177 | 27.00 | 0.00859177 | 37.3123 | 78935.52 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER TOP COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER TOP | DATACENTER_TOP_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 9422.961 | 6537.255 | 0.477940 | 0.00023077 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1021.1658 | 1004.8586 | 1.1610 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | Sensible | 8727.11 | 8380.12 | 0.9262 | -999.0 | -999.0 | 28.10 | 17.65 | 0.00878227 | 50659.4 | 12.80 | 11.77 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 8727.11 | 30.70 | 0.01446650 | 22.54 | 0.01563234 | -999.0000 | 27.00 | 0.00859007 | 27.00 | 0.00859007 | 37.3049 | 8040.96 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BASEMENT HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | DATACENTER_BASEMENT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 438414.063 | 438414.063 | 22.136565 | 0.01073673 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 1.1610 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 438414.06 | 438414.06 | 1.0000 | 25.70003315 | 22.136565 | -6.30 | -6.30 | 0.00229779 | -610.8 | 40.00 | 20.76 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 438414.06 | -6.30 | 0.00229779 | -6.30 | 0.33839277 | 1.5287 | 0.00 | 0.00850000 | 27.00 | 0.00850000 | 36.9155 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BOT HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BOT | DATACENTER_BOT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 9691.181 | 9691.181 | 0.492156 | 0.00023734 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 1.1610 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 9691.18 | 9691.18 | 1.0000 | 0.57138110 | 0.492156 | -6.30 | -6.30 | 0.00229779 | -610.8 | 40.00 | 20.76 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9691.18 | -6.30 | 0.00229779 | -6.30 | 0.01563234 | 3.1763 | 0.00 | 0.00732509 | 25.87 | 0.00732509 | 34.0766 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER MID HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER MID | DATACENTER_MID_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 92549.834 | 92549.834 | 4.691799 | 0.00226654 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 1.1610 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 92549.83 | 92549.83 | 1.0000 | 5.44706807 | 4.691799 | -6.30 | -6.30 | 0.00229779 | -610.8 | 40.00 | 20.76 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 92549.83 | -6.30 | 0.00229779 | -6.30 | 0.15632344 | 3.3318 | 0.00 | 0.00276482 | 23.96 | 0.00276482 | 14.5193 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER TOP HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER TOP | DATACENTER_TOP_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 9422.961 | 9422.961 | 0.477940 | 0.00023077 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 1.1610 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 9422.96 | 9422.96 | 1.0000 | 0.55487733 | 0.477940 | -6.30 | -6.30 | 0.00229779 | -610.8 | 40.00 | 20.76 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9422.96 | -6.30 | 0.00229779 | -6.30 | 0.01563234 | 3.2708 | 0.00 | 0.00276446 | 22.88 | 0.00276446 | 15.4880 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | DATACENTER_BASEMENT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 18278.075 | 18278.075 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | AIRLOOP DATACENTER BASEMENT SUPPLY FAN | Fan:OnOff | 22.136565 | 25.70003315 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 18278.08 | 18278.08 | 1.0000 | 25.70003315 | 22.136565 | -0.10 | -0.10 | 0.00840519 | 20922.6 | 40.00 | 20.76 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 18278.08 | -6.30 | 0.00229779 | -6.30 | 0.33839277 | 1.5287 | 0.00 | 0.00850000 | 27.00 | 0.00850000 | 36.9155 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BOT_SUPPHEATCOIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BOT | DATACENTER_BOT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 844.371 | 844.371 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | AIRLOOP DATACENTER BOT SUPPLY FAN | Fan:OnOff | 0.492156 | 0.57138110 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 844.37 | 844.37 | 1.0000 | 0.57138110 | 0.492156 | -0.20 | -0.20 | 0.00716540 | 17716.5 | 40.00 | 20.76 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 844.37 | -6.30 | 0.00229779 | -6.30 | 0.01563234 | 3.1763 | 0.00 | 0.00732509 | 25.87 | 0.00732509 | 34.0766 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER MID_SUPPHEATCOIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER MID | DATACENTER_MID_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 8443.713 | 8443.713 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | AIRLOOP DATACENTER MID SUPPLY FAN | Fan:OnOff | 4.691799 | 5.44706807 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 8443.71 | 8443.71 | 1.0000 | 5.44706807 | 4.691799 | -0.21 | -1.88 | 0.00274926 | 6663.7 | 40.00 | 20.76 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 8443.71 | -6.30 | 0.00229779 | -6.30 | 0.15632344 | 3.3318 | 0.00 | 0.00276482 | 23.96 | 0.00276482 | 14.5193 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER TOP_SUPPHEATCOIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER TOP | DATACENTER_TOP_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 844.371 | 844.371 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | AIRLOOP DATACENTER TOP SUPPLY FAN | Fan:OnOff | 0.477940 | 0.55487733 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 844.37 | 844.37 | 1.0000 | 0.55487733 | 0.477940 | -0.21 | -1.88 | 0.00274920 | 6667.5 | 40.00 | 20.76 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 844.37 | -6.30 | 0.00229779 | -6.30 | 0.01563234 | 3.2708 | 0.00 | 0.00276446 | 22.88 | 0.00276446 | 15.4880 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 08:43:24
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
VAV_BOT WITH REHEAT_OA_CONTROLLER | DifferentialEnthalpy | 2.54 | 10.08 | - | |||
VAV_MID WITH REHEAT_OA_CONTROLLER | DifferentialEnthalpy | 25.38 | 94.04 | - | |||
VAV_TOP WITH REHEAT_OA_CONTROLLER | DifferentialEnthalpy | 2.54 | 10.20 | - | |||
CAV_BAS_OA_CONTROLLER | DifferentialEnthalpy | 1.20 | 6.09 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
CORE_BOTTOM | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_MID | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_TOP | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
BASEMENT | 3682.67 | 1687.17 | 1157.83 |
CORE_BOTTOM | 3532.50 | 858.17 | 12.83 |
CORE_MID | 2298.50 | 2543.83 | 91.83 |
CORE_TOP | 2638.33 | 3076.00 | 480.33 |
PERIMETER_BOT_ZN_3 | 3058.00 | 2575.00 | 322.17 |
PERIMETER_BOT_ZN_2 | 2836.17 | 2704.67 | 319.17 |
PERIMETER_BOT_ZN_1 | 3316.50 | 2099.50 | 301.00 |
PERIMETER_BOT_ZN_4 | 3728.67 | 1750.00 | 317.83 |
PERIMETER_MID_ZN_3 | 3289.00 | 3438.00 | 1193.67 |
PERIMETER_MID_ZN_2 | 2678.67 | 2912.50 | 979.83 |
PERIMETER_MID_ZN_1 | 3261.50 | 2630.83 | 697.00 |
PERIMETER_MID_ZN_4 | 3193.67 | 3222.83 | 914.67 |
PERIMETER_TOP_ZN_3 | 3599.50 | 3628.83 | 1620.17 |
PERIMETER_TOP_ZN_2 | 3481.33 | 3468.83 | 1423.33 |
PERIMETER_TOP_ZN_1 | 3379.67 | 2962.00 | 1047.83 |
PERIMETER_TOP_ZN_4 | 3346.00 | 3440.17 | 1250.33 |
DATACENTER_BOT_ZN_6 | 5929.83 | 1370.67 | 1370.67 |
DATACENTER_MID_ZN_6 | 5661.17 | 295.17 | 253.50 |
DATACENTER_TOP_ZN_6 | 5376.33 | 716.00 | 543.50 |
DATACENTER_BASEMENT_ZN_6 | 5943.00 | 5685.17 | 5685.17 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
Facility | 5943.00 | 5940.50 | 5932.33 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
BASEMENT | 0.00 | 42.83 | 0.00 | 4.83 |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 0.33 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 6.67 | 0.00 | 1.33 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.33 | 1.17 | 0.00 | 1.17 |
PERIMETER_BOT_ZN_2 | 0.33 | 17.33 | 0.00 | 17.33 |
PERIMETER_BOT_ZN_1 | 0.50 | 30.50 | 0.00 | 30.17 |
PERIMETER_BOT_ZN_4 | 0.00 | 91.00 | 0.00 | 40.83 |
PERIMETER_MID_ZN_3 | 31.33 | 0.50 | 6.17 | 0.50 |
PERIMETER_MID_ZN_2 | 21.50 | 23.17 | 1.33 | 23.17 |
PERIMETER_MID_ZN_1 | 15.00 | 24.17 | 0.83 | 24.17 |
PERIMETER_MID_ZN_4 | 14.50 | 29.17 | 0.83 | 16.17 |
PERIMETER_TOP_ZN_3 | 113.50 | 5.50 | 31.83 | 4.00 |
PERIMETER_TOP_ZN_2 | 70.33 | 30.00 | 8.67 | 28.17 |
PERIMETER_TOP_ZN_1 | 57.50 | 24.33 | 9.83 | 22.50 |
PERIMETER_TOP_ZN_4 | 44.67 | 32.67 | 8.50 | 17.83 |
DATACENTER_BOT_ZN_6 | 0.00 | 43.00 | 0.00 | 43.00 |
DATACENTER_MID_ZN_6 | 0.00 | 39.83 | 0.00 | 39.83 |
DATACENTER_TOP_ZN_6 | 0.00 | 27.83 | 0.00 | 27.83 |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 464.67 | 0.00 | 413.33 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 121.50 | 670.83 | 32.33 | 532.33 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 08:43:24
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 62.11 | 149.60 | 6779.02 | 1.302 | 0.000 | 0.000 | 0.000 |
CORE_BOTTOM | 55.78 | 134.35 | 6849.35 | 0.858 | 0.000 | 0.000 | 0.000 |
CORE_MID | 55.78 | 134.35 | 6849.35 | 0.743 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 55.78 | 134.35 | 6849.35 | 0.731 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 7.00 | 16.87 | 860.00 | 0.839 | 0.043 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 4.51 | 10.87 | 554.22 | 1.158 | 0.045 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 7.00 | 16.87 | 860.02 | 1.112 | 0.043 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 4.51 | 10.87 | 554.22 | 1.628 | 0.045 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 7.00 | 16.87 | 860.00 | 0.793 | 0.101 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 3.94 | 10.87 | 554.22 | 1.109 | 0.111 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 7.00 | 16.87 | 860.02 | 1.048 | 0.102 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 4.51 | 10.87 | 554.22 | 1.274 | 0.105 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 7.00 | 16.87 | 860.00 | 0.805 | 0.126 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 4.51 | 10.87 | 554.22 | 1.201 | 0.130 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 7.00 | 16.87 | 860.02 | 1.036 | 0.126 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 4.51 | 10.87 | 554.22 | 1.304 | 0.130 | 0.000 | 0.000 |
DATACENTER_BOT_ZN_6 | 0.81 | 1.95 | 99.34 | 0.427 | 0.000 | 0.000 | 0.000 |
DATACENTER_MID_ZN_6 | 0.81 | 1.95 | 99.34 | 0.427 | 0.000 | 0.000 | 0.000 |
DATACENTER_TOP_ZN_6 | 0.81 | 1.95 | 99.34 | 0.427 | 0.000 | 0.000 | 0.000 |
DATACENTER_BASEMENT_ZN_6 | 17.51 | 42.18 | 1911.37 | 0.481 | 0.000 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 62.11 | 149.60 | 6779.02 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_BOTTOM | 55.78 | 134.35 | 6849.35 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_MID | 55.78 | 134.35 | 6849.35 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 55.78 | 134.35 | 6849.35 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 7.00 | 16.87 | 860.00 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 4.51 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 7.00 | 16.87 | 860.02 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 4.51 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 7.00 | 16.87 | 860.00 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 3.94 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 7.00 | 16.87 | 860.02 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 4.51 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 7.00 | 16.87 | 860.00 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 4.51 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 7.00 | 16.87 | 860.02 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 4.51 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
DATACENTER_BOT_ZN_6 | 0.81 | 1.95 | 99.34 | 0.000 | 0.000 | 0.000 | 0.000 |
DATACENTER_MID_ZN_6 | 0.81 | 1.95 | 99.34 | 0.000 | 0.000 | 0.000 | 0.000 |
DATACENTER_TOP_ZN_6 | 0.81 | 1.95 | 99.34 | 0.000 | 0.000 | 0.000 | 0.000 |
DATACENTER_BASEMENT_ZN_6 | 17.51 | 42.18 | 1911.37 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 08:43:24
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
BASEMENT | CAV_BAS | 62.11 | 149.60 | 6779.02 | 2779.43 | 1.2002 | 1.200 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | 55.78 | 134.35 | 6849.35 | 2496.12 | 0.0000 | 1.078 |
CORE_MID | VAV_MID WITH REHEAT | 55.78 | 134.35 | 6849.35 | 2496.12 | 0.0000 | 10.778 |
CORE_TOP | VAV_TOP WITH REHEAT | 55.78 | 134.35 | 6849.35 | 2496.12 | 0.0000 | 1.078 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | 7.00 | 16.87 | 860.00 | 313.41 | 0.0000 | 0.135 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | 4.51 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | 7.00 | 16.87 | 860.02 | 313.42 | 0.0000 | 0.135 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | 4.51 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | 7.00 | 16.87 | 860.00 | 313.41 | 0.0000 | 1.353 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | 3.94 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.872 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | 7.00 | 16.87 | 860.02 | 313.42 | 0.0000 | 1.353 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | 4.51 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.872 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | 7.00 | 16.87 | 860.00 | 313.41 | 0.0000 | 0.135 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | 4.51 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | 7.00 | 16.87 | 860.02 | 313.42 | 0.0000 | 0.135 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | 4.51 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | 0.81 | 1.95 | 99.34 | 36.20 | 0.0156 | 0.016 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | 0.81 | 1.95 | 99.34 | 36.20 | 0.1563 | 0.156 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | 0.81 | 1.95 | 99.34 | 36.20 | 0.0156 | 0.016 |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | 17.51 | 42.18 | 1911.37 | 783.68 | 0.3384 | 0.338 |
Total Facility | 1029.47 | 2493.19 | 126016.35 | 46320.38 | 1.7261 | 158.471 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
BASEMENT | 53346729.30 | 0.00 | 53346729.30 | 0.00 | 53346729.30 | 37848132.68 | 4044.71 | 1668.38 | 3046.92 | 232.06 |
CORE_BOTTOM | 35251440.05 | 0.00 | 35251440.05 | 0.00 | 35251440.05 | 33990283.35 | 4012.21 | 6.05 | 4741.74 | 148.14 |
CORE_MID | 0.30E+09 | 0.00 | 0.30E+09 | 0.00 | 0.30E+09 | 0.34E+09 | 4160.11 | 4.68 | 4595.21 | 133.83 |
CORE_TOP | 29802616.20 | 0.00 | 29802616.20 | 0.00 | 29802616.20 | 33990283.35 | 4217.27 | 4.45 | 4538.28 | 248.37 |
PERIMETER_BOT_ZN_3 | 4321992.54 | 0.00 | 4321992.54 | 439326.30 | 4761318.84 | 4267819.30 | 4015.15 | 4.32 | 4740.53 | 148.14 |
PERIMETER_BOT_ZN_2 | 3847978.88 | 0.00 | 3847978.88 | 292884.00 | 4140862.88 | 2750345.05 | 3975.45 | 2.27 | 4782.28 | 148.14 |
PERIMETER_BOT_ZN_1 | 5694328.46 | 0.00 | 5694328.46 | 439326.30 | 6133654.77 | 4267912.63 | 4009.74 | 4.28 | 4745.98 | 148.14 |
PERIMETER_BOT_ZN_4 | 5397933.36 | 0.00 | 5397933.36 | 292884.00 | 5690817.36 | 2750345.05 | 3956.11 | 0.00 | 4803.89 | 148.14 |
PERIMETER_MID_ZN_3 | 40578497.08 | 0.00 | 40578497.08 | 1030333.47 | 41608830.55 | 42678193.03 | 4124.37 | 6.73 | 4628.90 | 133.83 |
PERIMETER_MID_ZN_2 | 39550377.84 | 0.00 | 39550377.84 | 686888.51 | 40237266.35 | 27503450.52 | 4076.93 | 3.85 | 4679.22 | 1042.83 |
PERIMETER_MID_ZN_1 | 53287719.50 | 0.00 | 53287719.50 | 1030333.47 | 54318052.97 | 42679126.28 | 4143.09 | 4.81 | 4612.11 | 133.83 |
PERIMETER_MID_ZN_4 | 41958527.19 | 0.00 | 41958527.19 | 686888.51 | 42645415.70 | 27503450.52 | 4073.97 | 4.03 | 4682.00 | 133.83 |
PERIMETER_TOP_ZN_3 | 4134958.08 | 0.00 | 4134958.08 | 1279256.65 | 5414214.73 | 4267819.30 | 4151.82 | 6.51 | 4601.67 | 248.37 |
PERIMETER_TOP_ZN_2 | 3966626.33 | 0.00 | 3966626.33 | 852837.19 | 4819463.52 | 2750345.05 | 4090.87 | 7.09 | 4662.04 | 248.37 |
PERIMETER_TOP_ZN_1 | 5288939.32 | 0.00 | 5288939.32 | 1279256.65 | 6568195.97 | 4267912.63 | 4169.61 | 5.97 | 4584.41 | 248.37 |
PERIMETER_TOP_ZN_4 | 4305040.08 | 0.00 | 4305040.08 | 852837.19 | 5157877.27 | 2750345.05 | 4084.41 | 3.60 | 4671.99 | 248.37 |
DATACENTER_BOT_ZN_6 | 244296.02 | 0.00 | 244296.02 | 0.00 | 244296.02 | 492981.60 | 4419.00 | 4341.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 2442960.18 | 0.00 | 2442960.18 | 0.00 | 2442960.18 | 4929815.99 | 4419.00 | 4341.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 244296.02 | 0.00 | 244296.02 | 0.00 | 244296.02 | 492981.60 | 4419.00 | 4341.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 5288266.81 | 0.00 | 5288266.81 | 0.00 | 5288266.81 | 10671554.30 | 4419.00 | 4341.00 | 0.00 | 0.00 |
Total Facility | 0.50E+10 | 0.00 | 0.50E+10 | 40073047.80 | 0.50E+10 | 0.50E+10 | 4424.65 | 4387.41 | 4995.27 | 1364.69 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
BASEMENT | 2.4010 | 0.0000 | 2.4010 | 0.0000 | 2.4010 | 1.2002 | 1375.57 | 1666.72 | 2900.71 |
CORE_BOTTOM | 1.6006 | 0.0000 | 1.6006 | 0.0000 | 1.6006 | 1.0778 | 1325.02 | 4.67 | 4613.31 |
CORE_MID | 13.8885 | 0.0000 | 13.8885 | 0.0000 | 13.8885 | 10.7782 | 1391.33 | 2.21 | 4549.47 |
CORE_TOP | 1.3671 | 0.0000 | 1.3671 | 0.0000 | 1.3671 | 1.0778 | 1432.76 | 3.40 | 4506.84 |
PERIMETER_BOT_ZN_3 | 0.1968 | 0.0000 | 0.1968 | 0.0102 | 0.2070 | 0.1353 | 1328.05 | 2.82 | 4612.13 |
PERIMETER_BOT_ZN_2 | 0.1752 | 0.0000 | 0.1752 | 0.0068 | 0.1820 | 0.0872 | 1299.55 | 1.25 | 4642.20 |
PERIMETER_BOT_ZN_1 | 0.2608 | 0.0000 | 0.2608 | 0.0102 | 0.2710 | 0.1353 | 1323.43 | 3.81 | 4615.76 |
PERIMETER_BOT_ZN_4 | 0.2460 | 0.0000 | 0.2460 | 0.0068 | 0.2527 | 0.0872 | 1287.25 | 0.00 | 4655.75 |
PERIMETER_MID_ZN_3 | 1.8633 | 0.0000 | 1.8633 | 0.0239 | 1.8872 | 1.3533 | 1373.47 | 3.58 | 4565.95 |
PERIMETER_MID_ZN_2 | 1.6812 | 0.0000 | 1.6812 | 0.0169 | 1.6980 | 0.8721 | 1342.83 | 2.45 | 3688.73 |
PERIMETER_MID_ZN_1 | 2.4588 | 0.0000 | 2.4588 | 0.0239 | 2.4827 | 1.3533 | 1383.17 | 2.38 | 4557.44 |
PERIMETER_MID_ZN_4 | 1.9296 | 0.0000 | 1.9296 | 0.0159 | 1.9456 | 0.8721 | 1343.54 | 0.50 | 4598.96 |
PERIMETER_TOP_ZN_3 | 0.1893 | 0.0000 | 0.1893 | 0.0297 | 0.2190 | 0.1353 | 1390.35 | 4.17 | 4548.49 |
PERIMETER_TOP_ZN_2 | 0.1820 | 0.0000 | 0.1820 | 0.0198 | 0.2018 | 0.0872 | 1350.12 | 4.94 | 4587.94 |
PERIMETER_TOP_ZN_1 | 0.2433 | 0.0000 | 0.2433 | 0.0297 | 0.2730 | 0.1353 | 1404.75 | 3.81 | 4534.44 |
PERIMETER_TOP_ZN_4 | 0.1976 | 0.0000 | 0.1976 | 0.0198 | 0.2174 | 0.0872 | 1346.39 | 2.02 | 4594.58 |
DATACENTER_BOT_ZN_6 | 0.0114 | 0.0000 | 0.0114 | 0.0000 | 0.0114 | 0.0156 | 1602.00 | 4341.00 | 0.00 |
DATACENTER_MID_ZN_6 | 0.1142 | 0.0000 | 0.1142 | 0.0000 | 0.1142 | 0.1563 | 1602.00 | 4341.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 0.0114 | 0.0000 | 0.0114 | 0.0000 | 0.0114 | 0.0156 | 1602.00 | 4341.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.2472 | 0.0000 | 0.2472 | 0.0000 | 0.2472 | 0.3384 | 1602.00 | 4341.00 | 0.00 |
Total Facility | 226.6851 | 0.0000 | 226.6851 | 0.9383 | 227.6234 | 158.4706 | 1607.65 | 4367.06 | 4725.97 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
VAV_BOT WITH REHEAT | 73477291.63 | 0.00 | 73477291.63 | 48026705.38 | 3966.92 | 4.43 | 4788.65 | 148.14 |
VAV_MID WITH REHEAT | 0.64E+09 | 0.00 | 0.64E+09 | 0.48E+09 | 4085.98 | 4.02 | 4670.01 | 133.83 |
VAV_TOP WITH REHEAT | 64020844.76 | 0.00 | 64020844.76 | 48026705.38 | 4117.34 | 4.26 | 4638.40 | 248.37 |
CAV_BAS | 71904270.78 | 0.00 | 71904270.78 | 37848132.68 | 4008.13 | 2.44 | 4749.43 | 232.06 |
AIRLOOP DATACENTER BASEMENT | 7127877.82 | 0.00 | 7127877.82 | 10671554.30 | 4419.00 | 0.00 | 4341.00 | 0.00 |
AIRLOOP DATACENTER BOT | 329278.43 | 0.00 | 329278.43 | 492981.60 | 4419.00 | 0.00 | 4341.00 | 0.00 |
AIRLOOP DATACENTER MID | 3292784.26 | 0.00 | 3292784.26 | 4929815.99 | 4419.00 | 0.00 | 4341.00 | 0.00 |
AIRLOOP DATACENTER TOP | 329278.43 | 0.00 | 329278.43 | 492981.60 | 4419.00 | 0.00 | 4341.00 | 0.00 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
VAV_BOT WITH REHEAT | 3.3419 | 0.0000 | 3.3419 | 1.5229 | 1293.46 | 3.10 | 4646.44 |
VAV_MID WITH REHEAT | 29.5969 | 0.0000 | 29.5969 | 15.2292 | 1347.91 | 1.82 | 4593.27 |
VAV_TOP WITH REHEAT | 2.9375 | 0.0000 | 2.9375 | 1.5229 | 1366.19 | 2.72 | 4574.09 |
CAV_BAS | 3.2362 | 0.0000 | 3.2362 | 1.2002 | 1362.02 | 0.64 | 4580.35 |
AIRLOOP DATACENTER BASEMENT | 0.3332 | 0.0000 | 0.3332 | 0.3384 | 1602.00 | 0.00 | 4341.00 |
AIRLOOP DATACENTER BOT | 0.0154 | 0.0000 | 0.0154 | 0.0156 | 1602.00 | 0.00 | 4341.00 |
AIRLOOP DATACENTER MID | 0.1539 | 0.0000 | 0.1539 | 0.1563 | 1602.00 | 0.00 | 4341.00 |
AIRLOOP DATACENTER TOP | 0.0154 | 0.0000 | 0.0154 | 0.0156 | 1602.00 | 0.00 | 4341.00 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
VAV_BOT WITH REHEAT | 0.00 | 2416.31 | 2387.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
VAV_MID WITH REHEAT | 0.00 | 2641.24 | 2116.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
VAV_TOP WITH REHEAT | 0.00 | 2680.98 | 2230.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CAV_BAS | 0.00 | 1663.33 | 3161.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER BASEMENT | 0.00 | 4341.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER BOT | 0.00 | 4341.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER MID | 0.00 | 4341.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER TOP | 0.00 | 4341.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
VAV_BOT WITH REHEAT | 0.0000 | 3.4215 | 5.1785 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
VAV_MID WITH REHEAT | 0.0000 | 34.2145 | 43.1334 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
VAV_TOP WITH REHEAT | 0.0000 | 3.4224 | 4.1804 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
CAV_BAS | 0.0000 | 1.6180 | 5.6477 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
AIRLOOP DATACENTER BASEMENT | 0.0000 | 0.4562 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
AIRLOOP DATACENTER BOT | 0.0000 | 0.0211 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
AIRLOOP DATACENTER MID | 0.0000 | 0.2108 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
AIRLOOP DATACENTER TOP | 0.0000 | 0.0211 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 08:43:24
Surfaces by ClassTotal | Outdoors | |
Wall | 98 | 30 |
Floor | 41 | 0 |
Roof | 30 | 1 |
Internal Mass | 16 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 24 | 24 |
Door | 12 | 12 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 8 |
Conditioned Zones | 23 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 3 |
Count | |
IDF Objects | 1404 |
Defaulted Fields | 1182 |
Fields with Defaults | 3915 |
Autosized Fields | 338 |
Autosizable Fields | 414 |
Autocalculated Fields | 226 |
Autocalculatable Fields | 473 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 08:43:24
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 29915.83 | 363114.99 | 08-JAN-10:10 | 1957895.51 | 17-AUG-15:30 |
Electricity:Building | 18612.53 | 225715.65 | 21-MAY-17:10 | 1164206.62 | 06-DEC-08:10 |
Electricity:Zone:BASEMENT | 687.24 | 14732.47 | 01-JAN-00:10 | 36407.88 | 02-JAN-08:10 |
Electricity:SpaceType:GENERAL | 18612.53 | 225715.65 | 21-MAY-17:10 | 1164206.62 | 06-DEC-08:10 |
InteriorLights:Electricity | 3936.13 | 18459.50 | 01-JAN-11:20 | 385834.94 | 03-JAN-08:10 |
InteriorLights:Electricity:Zone:BASEMENT | 262.84 | 1274.92 | 01-JAN-00:10 | 22950.34 | 02-JAN-08:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 3936.13 | 18459.50 | 01-JAN-11:20 | 385834.94 | 03-JAN-08:10 |
LightsWired:InteriorLights:Electricity | 3936.13 | 18459.50 | 01-JAN-11:20 | 385834.94 | 03-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:BASEMENT | 262.84 | 1274.92 | 01-JAN-00:10 | 22950.34 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 3936.13 | 18459.50 | 01-JAN-11:20 | 385834.94 | 03-JAN-08:10 |
Electricity:Zone:CORE_BOTTOM | 525.67 | 5598.20 | 01-JAN-00:10 | 37817.64 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_BOTTOM | 236.05 | 1144.97 | 01-JAN-00:10 | 20611.01 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_BOTTOM | 236.05 | 1144.97 | 01-JAN-00:10 | 20611.01 | 02-JAN-08:10 |
Electricity:Zone:CORE_MID | 5256.66 | 55981.88 | 01-JAN-00:10 | 378175.77 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_MID | 2360.53 | 11449.71 | 01-JAN-00:10 | 206110.14 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_MID | 2360.53 | 11449.71 | 01-JAN-00:10 | 206110.14 | 02-JAN-08:10 |
Electricity:Zone:CORE_TOP | 525.67 | 5598.19 | 01-JAN-00:10 | 37817.58 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_TOP | 236.05 | 1144.97 | 01-JAN-00:10 | 20611.01 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_TOP | 236.05 | 1144.97 | 01-JAN-00:10 | 20611.01 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_3 | 54.08 | 627.57 | 16-APR-17:10 | 4748.47 | 03-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 17.72 | 68.40 | 01-JAN-11:20 | 2587.92 | 03-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 17.72 | 68.40 | 01-JAN-11:20 | 2587.92 | 03-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_2 | 34.62 | 404.43 | 23-APR-17:10 | 3060.10 | 03-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 11.19 | 44.08 | 01-JAN-09:10 | 1667.75 | 03-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 11.19 | 44.08 | 01-JAN-09:10 | 1667.75 | 03-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_1 | 53.57 | 627.58 | 12-MAR-17:10 | 4748.56 | 03-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 17.20 | 68.40 | 01-JAN-09:20 | 2587.98 | 03-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 17.20 | 68.40 | 01-JAN-09:20 | 2587.98 | 03-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_4 | 34.73 | 404.43 | 20-FEB-18:10 | 3060.09 | 03-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 11.29 | 44.08 | 01-JAN-11:00 | 1667.75 | 03-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 11.29 | 44.08 | 01-JAN-11:00 | 1667.75 | 03-JAN-08:10 |
Electricity:Zone:PERIMETER_MID_ZN_3 | 540.09 | 6275.73 | 16-APR-17:10 | 47484.70 | 03-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 176.43 | 684.02 | 01-JAN-11:10 | 25879.19 | 03-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 176.43 | 684.02 | 01-JAN-11:10 | 25879.19 | 03-JAN-08:10 |
Electricity:Zone:PERIMETER_MID_ZN_2 | 345.99 | 4044.32 | 23-APR-17:10 | 30600.95 | 03-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 111.63 | 440.81 | 01-JAN-09:10 | 16677.53 | 03-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 111.63 | 440.81 | 01-JAN-09:10 | 16677.53 | 03-JAN-08:10 |
Electricity:Zone:PERIMETER_MID_ZN_1 | 535.39 | 6275.83 | 12-MAR-17:10 | 47485.60 | 03-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 171.73 | 684.04 | 01-JAN-09:20 | 25879.75 | 03-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 171.73 | 684.04 | 01-JAN-09:20 | 25879.75 | 03-JAN-08:10 |
Electricity:Zone:PERIMETER_MID_ZN_4 | 346.94 | 4044.30 | 20-FEB-18:10 | 30600.86 | 03-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 112.59 | 440.81 | 01-JAN-11:00 | 16677.53 | 03-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 112.59 | 440.81 | 01-JAN-11:00 | 16677.53 | 03-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_3 | 54.01 | 627.57 | 16-APR-17:10 | 4748.47 | 03-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 17.64 | 68.40 | 01-JAN-11:10 | 2587.92 | 03-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 17.64 | 68.40 | 01-JAN-11:10 | 2587.92 | 03-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_2 | 34.60 | 404.43 | 23-APR-17:10 | 3060.10 | 03-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 11.16 | 44.08 | 01-JAN-09:10 | 1667.75 | 03-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 11.16 | 44.08 | 01-JAN-09:10 | 1667.75 | 03-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_1 | 53.54 | 627.58 | 12-MAR-17:10 | 4748.56 | 03-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 17.17 | 68.40 | 01-JAN-09:20 | 2587.98 | 03-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 17.17 | 68.40 | 01-JAN-09:20 | 2587.98 | 03-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_4 | 34.69 | 404.43 | 20-FEB-18:10 | 3060.09 | 03-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 11.26 | 44.08 | 01-JAN-10:50 | 1667.75 | 03-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 11.26 | 44.08 | 01-JAN-10:50 | 1667.75 | 03-JAN-08:10 |
Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 7568.97 | 95267.60 | 01-JAN-00:10 | 386103.53 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 74.11 | 359.47 | 01-JAN-00:10 | 6471.01 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 74.11 | 359.47 | 01-JAN-00:10 | 6471.01 | 02-JAN-08:10 |
Electricity:Zone:DATACENTER_BOT_ZN_6 | 160.51 | 1980.76 | 01-JAN-00:10 | 8373.14 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_BOT_ZN_6 | 6.63 | 32.15 | 01-JAN-00:10 | 578.72 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_BOT_ZN_6 | 6.63 | 32.15 | 01-JAN-00:10 | 578.72 | 02-JAN-08:10 |
Electricity:Zone:DATACENTER_MID_ZN_6 | 1605.09 | 19807.58 | 01-JAN-00:10 | 83731.41 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_MID_ZN_6 | 66.28 | 321.53 | 01-JAN-00:10 | 5787.18 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_MID_ZN_6 | 66.28 | 321.53 | 01-JAN-00:10 | 5787.18 | 02-JAN-08:10 |
Electricity:Zone:DATACENTER_TOP_ZN_6 | 160.51 | 1980.76 | 01-JAN-00:10 | 8373.14 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_TOP_ZN_6 | 6.63 | 32.15 | 01-JAN-00:10 | 578.72 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_TOP_ZN_6 | 6.63 | 32.15 | 01-JAN-00:10 | 578.72 | 02-JAN-08:10 |
InteriorEquipment:Electricity | 14676.40 | 207256.16 | 01-JAN-00:10 | 778371.69 | 03-APR-07:10 |
InteriorEquipment:Electricity:Zone:BASEMENT | 424.40 | 13457.54 | 01-JAN-00:10 | 13457.54 | 01-JAN-00:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 14676.40 | 207256.16 | 01-JAN-00:10 | 778371.69 | 03-APR-07:10 |
MiscPlug:InteriorEquipment:Electricity | 5334.97 | 88964.76 | 01-JAN-00:10 | 305206.10 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:BASEMENT | 424.40 | 13457.54 | 01-JAN-00:10 | 13457.54 | 01-JAN-00:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 5334.97 | 88964.76 | 01-JAN-00:10 | 305206.10 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 289.61 | 4453.23 | 01-JAN-00:10 | 17206.63 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 289.61 | 4453.23 | 01-JAN-00:10 | 17206.63 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_MID | 2896.13 | 44532.17 | 01-JAN-00:10 | 172065.63 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_MID | 2896.13 | 44532.17 | 01-JAN-00:10 | 172065.63 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_TOP | 289.61 | 4453.22 | 01-JAN-00:10 | 17206.56 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_TOP | 289.61 | 4453.22 | 01-JAN-00:10 | 17206.56 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 36.37 | 559.17 | 01-JAN-00:10 | 2160.55 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 36.37 | 559.17 | 01-JAN-00:10 | 2160.55 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.34 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.34 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 36.37 | 559.18 | 01-JAN-00:10 | 2160.58 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 36.37 | 559.18 | 01-JAN-00:10 | 2160.58 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.33 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.33 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 363.65 | 5591.71 | 01-JAN-00:10 | 21605.52 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 363.65 | 5591.71 | 01-JAN-00:10 | 21605.52 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 234.35 | 3603.51 | 01-JAN-00:10 | 13923.42 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 234.35 | 3603.51 | 01-JAN-00:10 | 13923.42 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 363.66 | 5591.79 | 01-JAN-00:10 | 21605.85 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 363.66 | 5591.79 | 01-JAN-00:10 | 21605.85 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 234.35 | 3603.49 | 01-JAN-00:10 | 13923.33 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 234.35 | 3603.49 | 01-JAN-00:10 | 13923.33 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 36.37 | 559.17 | 01-JAN-00:10 | 2160.55 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 36.37 | 559.17 | 01-JAN-00:10 | 2160.55 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.34 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.34 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 36.37 | 559.18 | 01-JAN-00:10 | 2160.58 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 36.37 | 559.18 | 01-JAN-00:10 | 2160.58 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.33 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.33 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 7494.86 | 94908.13 | 01-JAN-00:10 | 379632.52 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity | 9341.42 | 118291.40 | 01-JAN-00:10 | 473165.59 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 7494.86 | 94908.13 | 01-JAN-00:10 | 379632.52 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:SpaceType:GENERAL | 9341.42 | 118291.40 | 01-JAN-00:10 | 473165.59 | 31-MAR-23:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_BOT_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_BOT_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_MID_ZN_6 | 1538.81 | 19486.06 | 01-JAN-00:10 | 77944.22 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_MID_ZN_6 | 1538.81 | 19486.06 | 01-JAN-00:10 | 77944.22 | 31-MAR-23:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_TOP_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_TOP_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
Electricity:Plant | 3758.24 | 5958.24 | 07-JAN-17:40 | 444767.77 | 24-AUG-10:50 |
HeatRejection:Electricity | 1479.78 | 2321.47 | 14-JAN-08:00 | 92827.61 | 29-MAR-16:00 |
General:HeatRejection:Electricity | 1479.78 | 2321.47 | 14-JAN-08:00 | 92827.61 | 29-MAR-16:00 |
Electricity:HVAC | 4994.47 | 75010.99 | 08-JAN-23:30 | 352827.72 | 02-AUG-16:00 |
ExteriorEquipment:Electricity | 1934.80 | 28603.11 | 01-JAN-00:10 | 118535.44 | 03-JAN-08:20 |
Transformer:ExteriorEquipment:Electricity | 80.18 | 1421.04 | 01-JAN-00:10 | 5057.48 | 06-DEC-08:20 |
ElectricityPurchased:Facility | 29915.83 | 363114.99 | 08-JAN-10:10 | 1957895.51 | 17-AUG-15:30 |
ElectricityPurchased:Plant | 29915.83 | 363114.99 | 08-JAN-10:10 | 1957895.51 | 17-AUG-15:30 |
Cogeneration:ElectricityPurchased | 29915.83 | 363114.99 | 08-JAN-10:10 | 1957895.51 | 17-AUG-15:30 |
General:Cogeneration:ElectricityPurchased | 29915.83 | 363114.99 | 08-JAN-10:10 | 1957895.51 | 17-AUG-15:30 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 29915.83 | 363114.99 | 08-JAN-10:10 | 1957895.51 | 17-AUG-15:30 |
ElectricityNet:Plant | 29915.83 | 363114.99 | 08-JAN-10:10 | 1957895.51 | 17-AUG-15:30 |
Cogeneration:ElectricityNet | 29915.83 | 363114.99 | 08-JAN-10:10 | 1957895.51 | 17-AUG-15:30 |
General:Cogeneration:ElectricityNet | 29915.83 | 363114.99 | 08-JAN-10:10 | 1957895.51 | 17-AUG-15:30 |
Fans:Electricity | 2129.53 | 42850.60 | 23-JAN-04:40 | 173140.65 | 17-APR-15:10 |
General:Fans:Electricity | 2129.53 | 42850.60 | 23-JAN-04:40 | 173140.65 | 17-APR-15:10 |
ExteriorLights:Electricity | 695.97 | 0.00 | 01-JAN-07:50 | 57580.60 | 01-JAN-06:10 |
General:ExteriorLights:Electricity | 695.97 | 0.00 | 01-JAN-07:50 | 57580.60 | 01-JAN-06:10 |
ElevatorLift:ExteriorEquipment:Electricity | 1848.78 | 27144.47 | 01-JAN-00:10 | 113101.96 | 01-JAN-07:10 |
ElevatorLightsFan:ExteriorEquipment:Electricity | 5.83 | 37.60 | 01-JAN-00:10 | 376.00 | 01-JAN-07:10 |
HeatRecovery:Electricity | 52.13 | 0.00 | 01-JAN-00:10 | 5613.48 | 02-JAN-07:10 |
General:HeatRecovery:Electricity | 52.13 | 0.00 | 01-JAN-00:10 | 5613.48 | 02-JAN-07:10 |
Cooling:Electricity | 4405.04 | 28008.02 | 09-JAN-07:10 | 456876.80 | 17-AUG-15:30 |
General:Cooling:Electricity | 4405.04 | 28008.02 | 09-JAN-07:10 | 456876.80 | 17-AUG-15:30 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Humidifier:Electricity | 8.94 | 0.00 | 01-JAN-00:10 | 5868.03 | 05-JAN-18:10 |
General:Humidifier:Electricity | 8.94 | 0.00 | 01-JAN-00:10 | 5868.03 | 05-JAN-18:10 |
Boiler Parasitic:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Pumps:Electricity | 597.12 | 3435.87 | 01-JAN-00:40 | 61546.80 | 01-AUG-09:20 |
General:Pumps:Electricity | 597.12 | 3435.87 | 01-JAN-00:40 | 61546.80 | 01-AUG-09:20 |
WIRED_LTG_ELECTRICITY | 110.61 | 0.00 | 01-JAN-00:10 | 10841.96 | 03-JAN-08:20 |
WIRED_INT_EQUIP | 5334.97 | 88964.76 | 31-MAR-23:10 | 305206.10 | 03-APR-07:10 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 1693.23 | 8146.58 | 09-JUL-16:20 | 1803266.60 | 13-FEB-07:10 |
NaturalGas:Plant | 1693.23 | 8146.58 | 09-JUL-16:20 | 1803266.60 | 13-FEB-07:10 |
Heating:NaturalGas | 958.69 | 0.00 | 01-JAN-00:40 | 1771654.06 | 13-FEB-07:10 |
Boiler:Heating:NaturalGas | 958.69 | 0.00 | 01-JAN-00:40 | 1771654.06 | 13-FEB-07:10 |
WaterSystems:NaturalGas | 734.54 | 8146.58 | 02-JAN-06:10 | 82149.84 | 02-FEB-13:00 |
Water Heater:WaterSystems:NaturalGas | 734.54 | 8146.58 | 02-JAN-06:10 | 82149.84 | 02-FEB-13:00 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
PlantLoopCoolingDemand:Facility | 23285.21 | 137993.16 | 09-JAN-07:10 | 2645895.30 | 24-AUG-10:50 |
PlantLoopCoolingDemand:HVAC | 23285.21 | 137993.16 | 09-JAN-07:10 | 2645895.30 | 24-AUG-10:50 |
CoolingCoils:PlantLoopCoolingDemand | 23285.21 | 137993.16 | 09-JAN-07:10 | 2645895.30 | 24-AUG-10:50 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 11083.99 | 0.00 | 01-JAN-00:10 | 0.00 | 17-APR-14:40 |
Water:HVAC | 3.33 | 0.00 | 01-JAN-00:10 | 0.00 | 05-JAN-18:10 |
Humidifier:Water | 3.33 | 0.00 | 01-JAN-00:10 | 0.00 | 05-JAN-18:10 |
General:Humidifier:Water | 3.33 | 0.00 | 01-JAN-00:10 | 0.00 | 05-JAN-18:10 |
MainsWater:Facility | 11083.99 | 0.00 | 01-JAN-00:10 | 0.00 | 17-APR-14:40 |
MainsWater:HVAC | 3.33 | 0.00 | 01-JAN-00:10 | 0.00 | 05-JAN-18:10 |
Humidifier:MainsWater | 3.33 | 0.00 | 01-JAN-00:10 | 0.00 | 05-JAN-18:10 |
General:Humidifier:MainsWater | 3.33 | 0.00 | 01-JAN-00:10 | 0.00 | 05-JAN-18:10 |
Water:Plant | 11080.66 | 0.00 | 01-JAN-00:10 | 0.00 | 17-APR-14:40 |
WaterSystems:Water | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterUse:WaterSystems:Water | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
MainsWater:Plant | 11080.66 | 0.00 | 01-JAN-00:10 | 0.00 | 17-APR-14:40 |
WaterSystems:MainsWater | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterUse:WaterSystems:MainsWater | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water Heater:WaterSystems:Water | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:MainsWater | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
HeatRejection:Water | 8800.50 | 0.00 | 01-JAN-00:10 | 0.00 | 17-APR-14:40 |
General:HeatRejection:Water | 8800.50 | 0.00 | 01-JAN-00:10 | 0.00 | 17-APR-14:40 |
HeatRejection:MainsWater | 8800.50 | 0.00 | 01-JAN-00:10 | 0.00 | 17-APR-14:40 |
General:HeatRejection:MainsWater | 8800.50 | 0.00 | 01-JAN-00:10 | 0.00 | 17-APR-14:40 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 79800.47 | 212654.60 | 09-JAN-04:50 | 10239344.34 | 17-AUG-15:30 |
EnergyTransfer:Building | 20054.82 | 87784.68 | 14-JAN-18:40 | 1655260.46 | 02-AUG-16:00 |
EnergyTransfer:Zone:BASEMENT | 699.74 | 0.00 | 01-JAN-00:10 | 72612.43 | 10-OCT-05:10 |
Heating:EnergyTransfer | 347.38 | 0.00 | 19-JAN-18:20 | 1062292.26 | 09-JAN-05:10 |
Heating:EnergyTransfer:Zone:BASEMENT | 3.32 | 0.00 | 01-JAN-00:10 | 24297.13 | 08-JUL-16:10 |
General:Heating:EnergyTransfer | 347.38 | 0.00 | 19-JAN-18:20 | 1062292.26 | 09-JAN-05:10 |
General:Heating:EnergyTransfer:Zone:BASEMENT | 3.32 | 0.00 | 01-JAN-00:10 | 24297.13 | 08-JUL-16:10 |
Cooling:EnergyTransfer | 19707.45 | 84914.31 | 09-JAN-05:40 | 1655260.46 | 02-AUG-16:00 |
Cooling:EnergyTransfer:Zone:BASEMENT | 696.43 | 0.00 | 01-JAN-00:10 | 72612.43 | 10-OCT-05:10 |
General:Cooling:EnergyTransfer | 19707.45 | 84914.31 | 09-JAN-05:40 | 1655260.46 | 02-AUG-16:00 |
General:Cooling:EnergyTransfer:Zone:BASEMENT | 696.43 | 0.00 | 01-JAN-00:10 | 72612.43 | 10-OCT-05:10 |
EnergyTransfer:Zone:CORE_BOTTOM | 694.41 | 0.00 | 01-JAN-00:10 | 55504.08 | 14-APR-14:50 |
Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 694.41 | 0.00 | 01-JAN-00:10 | 55504.08 | 14-APR-14:50 |
General:Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 694.41 | 0.00 | 01-JAN-00:10 | 55504.08 | 14-APR-14:50 |
EnergyTransfer:Zone:CORE_MID | 5185.60 | 0.00 | 01-JAN-00:10 | 457157.82 | 17-AUG-16:00 |
Heating:EnergyTransfer:Zone:CORE_MID | 3.79 | 0.00 | 01-JAN-00:10 | 325463.72 | 09-JAN-05:10 |
General:Heating:EnergyTransfer:Zone:CORE_MID | 3.79 | 0.00 | 01-JAN-00:10 | 325463.72 | 09-JAN-05:10 |
Cooling:EnergyTransfer:Zone:CORE_MID | 5181.82 | 0.00 | 01-JAN-00:10 | 457157.82 | 17-AUG-16:00 |
General:Cooling:EnergyTransfer:Zone:CORE_MID | 5181.82 | 0.00 | 01-JAN-00:10 | 457157.82 | 17-AUG-16:00 |
EnergyTransfer:Zone:CORE_TOP | 504.89 | 0.00 | 01-JAN-00:40 | 73050.78 | 17-JAN-05:20 |
Heating:EnergyTransfer:Zone:CORE_TOP | 7.95 | 0.00 | 01-JAN-00:10 | 73050.78 | 17-JAN-05:20 |
General:Heating:EnergyTransfer:Zone:CORE_TOP | 7.95 | 0.00 | 01-JAN-00:10 | 73050.78 | 17-JAN-05:20 |
Cooling:EnergyTransfer:Zone:CORE_TOP | 496.94 | 0.00 | 01-JAN-00:40 | 53998.58 | 07-JUL-15:50 |
General:Cooling:EnergyTransfer:Zone:CORE_TOP | 496.94 | 0.00 | 01-JAN-00:40 | 53998.58 | 07-JUL-15:50 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 86.55 | 0.00 | 01-JAN-00:10 | 11008.58 | 09-AUG-14:40 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 0.55 | 0.00 | 01-JAN-00:10 | 6679.71 | 13-FEB-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 0.55 | 0.00 | 01-JAN-00:10 | 6679.71 | 13-FEB-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 86.00 | 0.00 | 01-JAN-00:10 | 11008.58 | 09-AUG-14:40 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 86.00 | 0.00 | 01-JAN-00:10 | 11008.58 | 09-AUG-14:40 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 74.16 | 0.00 | 01-JAN-00:10 | 12442.03 | 07-JUL-09:10 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 0.38 | 0.00 | 01-JAN-00:10 | 4760.39 | 13-FEB-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 0.38 | 0.00 | 01-JAN-00:10 | 4760.39 | 13-FEB-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 73.77 | 0.00 | 01-JAN-00:10 | 12442.03 | 07-JUL-09:10 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 73.77 | 0.00 | 01-JAN-00:10 | 12442.03 | 07-JUL-09:10 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 111.22 | 0.00 | 01-JAN-00:10 | 17305.42 | 10-OCT-13:40 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 0.68 | 0.00 | 01-JAN-00:10 | 9287.16 | 09-JAN-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 0.68 | 0.00 | 01-JAN-00:10 | 9287.16 | 09-JAN-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 110.53 | 0.00 | 01-JAN-00:10 | 17305.42 | 10-OCT-13:40 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 110.53 | 0.00 | 01-JAN-00:10 | 17305.42 | 10-OCT-13:40 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 108.83 | 0.00 | 01-JAN-00:10 | 16545.55 | 18-AUG-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 0.06 | 0.00 | 01-JAN-00:10 | 2319.54 | 09-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 0.06 | 0.00 | 01-JAN-00:10 | 2319.54 | 09-JAN-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 108.77 | 0.00 | 01-JAN-00:10 | 16545.55 | 18-AUG-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 108.77 | 0.00 | 01-JAN-00:10 | 16545.55 | 18-AUG-16:00 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 692.66 | 0.00 | 01-JAN-00:10 | 132790.48 | 13-FEB-05:20 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 82.91 | 0.00 | 01-JAN-00:10 | 132790.48 | 13-FEB-05:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 82.91 | 0.00 | 01-JAN-00:10 | 132790.48 | 13-FEB-05:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 609.76 | 0.00 | 01-JAN-00:10 | 103421.18 | 14-JUL-15:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 609.76 | 0.00 | 01-JAN-00:10 | 103421.18 | 14-JUL-15:00 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 647.46 | 0.00 | 01-JAN-00:10 | 131258.11 | 07-JUL-09:00 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 43.15 | 0.00 | 01-JAN-00:10 | 121631.84 | 13-FEB-05:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 43.15 | 0.00 | 01-JAN-00:10 | 121631.84 | 13-FEB-05:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 604.32 | 0.00 | 01-JAN-00:10 | 131258.11 | 07-JUL-09:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 604.32 | 0.00 | 01-JAN-00:10 | 131258.11 | 07-JUL-09:00 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 932.96 | 0.00 | 01-JAN-00:10 | 166479.16 | 10-OCT-13:40 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 40.77 | 0.00 | 01-JAN-00:10 | 150361.04 | 13-FEB-05:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 40.77 | 0.00 | 01-JAN-00:10 | 150361.04 | 13-FEB-05:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 892.19 | 0.00 | 01-JAN-00:10 | 166479.16 | 10-OCT-13:40 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 892.19 | 0.00 | 01-JAN-00:10 | 166479.16 | 10-OCT-13:40 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 682.56 | 0.00 | 01-JAN-00:10 | 133434.16 | 02-AUG-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 32.53 | 0.00 | 01-JAN-00:10 | 109725.12 | 13-FEB-05:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 32.53 | 0.00 | 01-JAN-00:10 | 109725.12 | 13-FEB-05:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 650.03 | 0.00 | 01-JAN-00:10 | 133434.16 | 02-AUG-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 650.03 | 0.00 | 01-JAN-00:10 | 133434.16 | 02-AUG-16:00 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 79.29 | 0.00 | 01-JAN-00:40 | 16305.95 | 13-FEB-04:10 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 19.38 | 0.00 | 01-JAN-00:40 | 16305.95 | 13-FEB-04:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 19.38 | 0.00 | 01-JAN-00:40 | 16305.95 | 13-FEB-04:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 59.91 | 0.00 | 01-JAN-00:10 | 11523.89 | 14-JUL-15:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 59.91 | 0.00 | 01-JAN-00:10 | 11523.89 | 14-JUL-15:00 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 69.69 | 0.00 | 01-JAN-00:40 | 14386.35 | 13-FEB-05:10 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 9.99 | 0.00 | 01-JAN-00:40 | 14386.35 | 13-FEB-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 9.99 | 0.00 | 01-JAN-00:40 | 14386.35 | 13-FEB-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 59.70 | 0.00 | 01-JAN-00:10 | 13542.71 | 07-JUL-09:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 59.70 | 0.00 | 01-JAN-00:10 | 13542.71 | 07-JUL-09:30 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 97.90 | 0.00 | 01-JAN-00:40 | 18142.62 | 13-FEB-04:10 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 10.98 | 0.00 | 01-JAN-00:40 | 18142.62 | 13-FEB-04:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 10.98 | 0.00 | 01-JAN-00:40 | 18142.62 | 13-FEB-04:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 86.92 | 0.00 | 01-JAN-00:10 | 17868.99 | 10-OCT-13:40 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 86.92 | 0.00 | 01-JAN-00:10 | 17868.99 | 10-OCT-13:40 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 72.71 | 0.00 | 01-JAN-00:40 | 14550.18 | 09-JAN-05:10 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 8.10 | 0.00 | 01-JAN-00:40 | 14550.18 | 09-JAN-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 8.10 | 0.00 | 01-JAN-00:40 | 14550.18 | 09-JAN-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 64.60 | 0.00 | 01-JAN-00:10 | 14161.61 | 02-AUG-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 64.60 | 0.00 | 01-JAN-00:10 | 14161.61 | 02-AUG-16:00 |
EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 69.97 | 0.00 | 01-JAN-00:10 | 8194.13 | 05-JUL-16:00 |
Heating:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 1.18 | 0.00 | 01-JAN-00:10 | 3209.84 | 17-DEC-13:20 |
General:Heating:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 1.18 | 0.00 | 01-JAN-00:10 | 3209.84 | 17-DEC-13:20 |
Cooling:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 68.79 | 0.00 | 01-JAN-00:10 | 8194.13 | 05-JUL-16:00 |
General:Cooling:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 68.79 | 0.00 | 01-JAN-00:10 | 8194.13 | 05-JUL-16:00 |
EnergyTransfer:Zone:MIDFLOOR_PLENUM | 518.93 | 0.00 | 01-JAN-00:10 | 92005.24 | 09-JAN-06:10 |
Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 52.01 | 0.00 | 01-JAN-00:10 | 92005.24 | 09-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 52.01 | 0.00 | 01-JAN-00:10 | 92005.24 | 09-JAN-06:10 |
Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 466.93 | 0.00 | 01-JAN-00:10 | 71888.96 | 18-AUG-16:00 |
General:Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 466.93 | 0.00 | 01-JAN-00:10 | 71888.96 | 18-AUG-16:00 |
EnergyTransfer:Zone:TOPFLOOR_PLENUM | 95.95 | 0.00 | 01-JAN-00:40 | 25871.17 | 13-FEB-05:40 |
Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 24.73 | 0.00 | 01-JAN-00:40 | 25871.17 | 13-FEB-05:40 |
General:Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 24.73 | 0.00 | 01-JAN-00:40 | 25871.17 | 13-FEB-05:40 |
Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 71.23 | 0.00 | 01-JAN-00:10 | 19740.61 | 07-JUL-15:10 |
General:Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 71.23 | 0.00 | 01-JAN-00:10 | 19740.61 | 07-JUL-15:10 |
EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 139.16 | 169.28 | 09-JAN-05:50 | 7933.39 | 09-APR-18:20 |
Heating:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 139.16 | 169.28 | 09-JAN-05:50 | 7933.39 | 09-APR-18:20 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 139.16 | 169.28 | 09-JAN-05:50 | 7933.39 | 09-APR-18:20 |
EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 1216.40 | 4.35 | 09-JAN-07:40 | 74668.91 | 14-APR-18:30 |
Heating:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 4.16 | 0.00 | 02-JAN-09:50 | 5473.67 | 16-JAN-03:20 |
General:Heating:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 4.16 | 0.00 | 02-JAN-09:50 | 5473.67 | 16-JAN-03:20 |
Cooling:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 1212.24 | 0.00 | 01-JAN-00:10 | 74668.91 | 14-APR-18:30 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 1212.24 | 0.00 | 01-JAN-00:10 | 74668.91 | 14-APR-18:30 |
EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 115.70 | 0.15 | 11-JAN-07:40 | 7653.22 | 13-AUG-18:50 |
Heating:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 0.77 | 0.00 | 02-JAN-13:10 | 599.64 | 22-JAN-19:10 |
General:Heating:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 0.77 | 0.00 | 02-JAN-13:10 | 599.64 | 22-JAN-19:10 |
Cooling:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 114.94 | 0.00 | 01-JAN-00:10 | 7653.22 | 13-AUG-18:50 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 114.94 | 0.00 | 01-JAN-00:10 | 7653.22 | 13-AUG-18:50 |
EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 7158.08 | 84704.80 | 09-JAN-05:00 | 369804.16 | 07-AUG-21:10 |
Heating:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 7158.08 | 84704.80 | 09-JAN-05:00 | 369804.16 | 07-AUG-21:10 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 7158.08 | 84704.80 | 09-JAN-05:00 | 369804.16 | 07-AUG-21:10 |
PlantLoopHeatingDemand:Facility | 1071.72 | 0.00 | 01-JAN-00:40 | 1515192.75 | 13-FEB-07:10 |
PlantLoopHeatingDemand:Plant | 371.93 | 0.00 | 01-JAN-00:10 | 47925.51 | 31-JAN-12:20 |
WaterSystems:PlantLoopHeatingDemand | 371.93 | 0.00 | 01-JAN-00:10 | 47925.51 | 31-JAN-12:20 |
General:WaterSystems:PlantLoopHeatingDemand | 371.93 | 0.00 | 01-JAN-00:10 | 47925.51 | 31-JAN-12:20 |
EnergyTransfer:HVAC | 23458.23 | 121975.26 | 09-JAN-04:50 | 2925379.07 | 10-AUG-16:00 |
HeatingCoils:EnergyTransfer | 699.79 | 0.00 | 01-JAN-00:40 | 1499298.85 | 13-FEB-07:10 |
PlantLoopHeatingDemand:HVAC | 699.79 | 0.00 | 01-JAN-00:40 | 1499298.85 | 13-FEB-07:10 |
HeatingCoils:PlantLoopHeatingDemand | 699.79 | 0.00 | 01-JAN-00:40 | 1499298.85 | 13-FEB-07:10 |
CoolingCoils:EnergyTransfer | 20561.51 | 109985.14 | 09-JAN-07:10 | 2489039.89 | 24-AUG-10:50 |
HeatRecoveryForHeating:EnergyTransfer | 689.01 | 0.00 | 01-JAN-00:10 | 724585.61 | 03-FEB-08:10 |
HeatRecoveryForCooling:EnergyTransfer | 1507.92 | 0.00 | 01-JAN-00:10 | 651624.31 | 07-JUL-12:00 |
EnergyTransfer:Plant | 36287.42 | 0.00 | 01-JAN-00:40 | 6279859.32 | 24-AUG-10:50 |
LoopToLoop:EnergyTransfer | 11192.38 | 0.00 | 01-JAN-00:10 | 1980599.88 | 24-AUG-10:50 |
WaterSystems:EnergyTransfer | 371.93 | 0.00 | 01-JAN-00:10 | 47925.51 | 31-JAN-12:20 |
WaterUse:WaterSystems:EnergyTransfer | 371.93 | 0.00 | 01-JAN-00:10 | 47925.51 | 31-JAN-12:20 |
Boilers:EnergyTransfer | 693.47 | 0.00 | 01-JAN-00:40 | 1471567.77 | 13-FEB-07:10 |
Chillers:EnergyTransfer | 11174.14 | 0.00 | 01-JAN-00:10 | 1988947.14 | 24-AUG-10:50 |
HeatRejection:EnergyTransfer | 12855.49 | 0.00 | 01-JAN-00:10 | 2281777.71 | 24-AUG-10:50 |
General:HeatRejection:EnergyTransfer | 12855.49 | 0.00 | 01-JAN-00:10 | 2281777.71 | 24-AUG-10:50 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 08:43:24
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
BASEMENT | 0.000 | 0.000 | 3.316 | -696.430 | 0.000 | 0.000 | 92.726 | 262.844 | 424.397 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -86.853 |
CORE_BOTTOM | 0.000 | 0.000 | 0.000 | -694.403 | 0.000 | 0.000 | 83.609 | 236.053 | 289.614 | 0.000 | 0.000 | 0.000 | 85.128 | 0.000 | 0.000 | 0.000 | 0.000 | -0.000 |
CORE_MID | 0.000 | 0.000 | 3.787 | -5181.789 | 0.000 | 0.000 | 856.533 | 2360.527 | 2896.128 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -935.186 |
CORE_TOP | 0.000 | 0.000 | 7.949 | -496.932 | 0.000 | 0.000 | 87.985 | 236.053 | 289.613 | 0.000 | 0.000 | 0.000 | 0.001 | 0.000 | 0.000 | 0.000 | 0.000 | -124.667 |
PERIMETER_BOT_ZN_3 | 0.000 | 0.000 | 0.550 | -85.997 | 0.000 | 0.000 | 10.858 | 17.718 | 36.365 | 30.229 | 0.000 | 0.237 | 54.383 | 0.000 | -59.484 | 0.000 | -4.860 | 0.000 |
PERIMETER_BOT_ZN_2 | 0.000 | 0.000 | 0.384 | -73.774 | 0.000 | 0.000 | 7.017 | 11.188 | 23.435 | 50.431 | 0.000 | 0.166 | 19.398 | 0.000 | -35.060 | 0.000 | -3.186 | 0.000 |
PERIMETER_BOT_ZN_1 | 0.000 | 0.000 | 0.684 | -110.533 | 0.000 | 0.000 | 10.727 | 17.199 | 36.366 | 88.593 | 0.000 | 0.226 | 14.542 | 0.000 | -52.867 | 0.000 | -4.936 | 0.000 |
PERIMETER_BOT_ZN_4 | 0.000 | 0.000 | 0.055 | -108.770 | 0.000 | 0.000 | 6.905 | 11.291 | 23.435 | 49.594 | 0.000 | 0.139 | 63.871 | 0.000 | -42.887 | 0.000 | -3.634 | 0.000 |
PERIMETER_MID_ZN_3 | 0.000 | 0.000 | 82.909 | -609.741 | 0.000 | 0.000 | 112.901 | 176.434 | 363.654 | 316.945 | 0.000 | 5.602 | 169.960 | 0.000 | -521.552 | 0.000 | -97.111 | 0.000 |
PERIMETER_MID_ZN_2 | 0.000 | 0.000 | 43.147 | -604.306 | 0.000 | 0.000 | 53.186 | 111.633 | 234.352 | 507.979 | 0.000 | 3.568 | 36.954 | 0.000 | -320.012 | 0.000 | -66.502 | -0.003 |
PERIMETER_MID_ZN_1 | 0.000 | 0.000 | 40.769 | -892.166 | 0.000 | 0.000 | 109.069 | 171.730 | 363.660 | 887.452 | 0.000 | 5.069 | 0.050 | 0.000 | -498.896 | 0.000 | -107.001 | -79.685 |
PERIMETER_MID_ZN_4 | 0.000 | 0.000 | 32.533 | -650.011 | 0.000 | 0.000 | 72.591 | 112.586 | 234.351 | 513.379 | 0.000 | 3.354 | 109.268 | 0.000 | -358.400 | 0.000 | -69.651 | 0.000 |
PERIMETER_TOP_ZN_3 | 0.000 | 0.000 | 19.383 | -59.906 | 0.000 | 0.000 | 11.408 | 17.640 | 36.365 | 31.844 | 0.000 | 0.665 | 3.319 | 0.000 | -49.351 | 0.000 | -11.368 | -0.000 |
PERIMETER_TOP_ZN_2 | 0.000 | 0.000 | 9.992 | -59.701 | 0.000 | 0.000 | 7.278 | 11.162 | 23.435 | 50.988 | 0.000 | 0.422 | 0.001 | 0.000 | -30.428 | 0.000 | -7.794 | -5.355 |
PERIMETER_TOP_ZN_1 | 0.000 | 0.000 | 10.980 | -86.922 | 0.000 | 0.000 | 11.058 | 17.171 | 36.366 | 89.197 | 0.000 | 0.603 | 0.000 | 0.000 | -47.151 | 0.000 | -12.427 | -18.875 |
PERIMETER_TOP_ZN_4 | 0.000 | 0.000 | 8.104 | -64.600 | 0.000 | 0.000 | 7.340 | 11.258 | 23.435 | 51.363 | 0.000 | 0.406 | 5.039 | 0.000 | -34.156 | 0.000 | -8.189 | -0.001 |
DATACENTER_BOT_ZN_6 | 0.000 | 0.000 | 0.000 | -139.158 | 0.000 | 0.000 | 0.949 | 6.628 | 153.881 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -22.299 |
DATACENTER_MID_ZN_6 | 0.000 | 0.000 | 4.160 | -1212.240 | 0.000 | 0.000 | 9.494 | 66.280 | 1538.806 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -406.499 |
DATACENTER_TOP_ZN_6 | 0.000 | 0.000 | 0.765 | -114.936 | 0.000 | 0.000 | 0.952 | 6.628 | 153.881 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -47.290 |
DATACENTER_BASEMENT_ZN_6 | 0.000 | 0.000 | 0.000 | -7158.088 | 0.000 | 0.000 | 20.231 | 74.111 | 7494.857 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -431.111 |
GROUNDFLOOR_PLENUM | 1.178 | -68.790 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.411 | 77.992 | 0.000 | 0.000 | 0.000 | -10.791 | 0.000 |
MIDFLOOR_PLENUM | 52.008 | -466.920 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 7.791 | 582.352 | 0.000 | 0.000 | 0.000 | -175.231 | -0.001 |
TOPFLOOR_PLENUM | 24.726 | -71.227 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.672 | 63.782 | 0.000 | 0.000 | 0.000 | -17.953 | -0.002 |
Total Facility | 77.912 | -606.937 | 269.468 | -19100.403 | 0.000 | 0.000 | 1572.816 | 3936.135 | 14676.396 | 2667.994 | 0.000 | 29.329 | 1286.040 | 0.000 | -2050.243 | 0.000 | -600.635 | -2157.828 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | 30-OCT-04:11 | 0.00 | 0.00 | 0.00 | -120458.27 | 0.00 | 0.00 | 0.00 | 2550.13 | 13457.54 | 0.00 | 0.00 | 0.00 | 104450.60 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 11-SEP-04:13 | 0.00 | 0.00 | 0.00 | -99844.02 | 0.00 | 0.00 | 0.00 | 2290.20 | 5937.65 | 0.00 | 0.00 | 0.00 | 91616.17 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 21-JUN-04:11 | 0.00 | 0.00 | 0.00 | -868940.60 | 0.00 | 0.00 | 0.00 | 22901.98 | 59376.23 | 0.00 | 0.00 | 0.00 | 786662.39 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 16-JUN-04:11 | 0.00 | 0.00 | 0.00 | -86134.56 | 0.00 | 0.00 | 0.00 | 2290.20 | 5937.62 | 0.00 | 0.00 | 0.00 | 77906.74 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 17-JUL-04:12 | 0.00 | 0.00 | 0.00 | -14290.65 | 0.00 | 0.00 | 0.00 | 287.56 | 745.56 | 0.00 | 0.00 | 0.00 | 14789.74 | 0.00 | -1494.53 | 0.00 | -37.68 | 0.00 |
PERIMETER_BOT_ZN_2 | 04-JUN-09:02 | 0.00 | 0.00 | 0.00 | -20027.50 | 0.00 | 0.00 | 22.31 | 44.08 | 464.11 | 13886.58 | 0.00 | 0.00 | 5642.38 | 0.00 | -0.00 | 0.00 | -31.97 | 0.00 |
PERIMETER_BOT_ZN_1 | 09-OCT-14:12 | 0.00 | 0.00 | 0.00 | -22775.84 | 0.00 | 0.00 | 35.69 | 68.40 | 720.19 | 15977.52 | 0.00 | 0.00 | 5995.51 | 0.00 | -0.00 | 0.00 | -21.49 | 0.00 |
PERIMETER_BOT_ZN_4 | 11-JUN-15:51 | 0.00 | 0.00 | 0.00 | -25887.97 | 0.00 | 0.00 | 20.11 | 44.08 | 464.11 | 13631.00 | 0.00 | 106.69 | 11621.98 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 25-JUN-16:11 | 0.00 | 0.00 | 0.00 | -163819.49 | 0.00 | 0.00 | 441.85 | 684.02 | 7201.84 | 50582.63 | 0.00 | 5845.73 | 99063.41 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 27-AUG-09:41 | 0.00 | 0.00 | 0.00 | -212991.46 | 0.00 | 0.00 | 213.19 | 440.81 | 4641.14 | 129270.69 | 0.00 | 0.00 | 78662.40 | 0.00 | -0.00 | 0.00 | -236.77 | 0.00 |
PERIMETER_MID_ZN_1 | 08-OCT-14:02 | 0.00 | 0.00 | 0.00 | -216591.69 | 0.00 | 0.00 | 359.29 | 684.04 | 7201.95 | 170022.78 | 0.00 | 0.00 | 39557.78 | 0.00 | -0.00 | 0.00 | -1234.15 | 0.00 |
PERIMETER_MID_ZN_4 | 23-JUL-17:11 | 0.00 | 0.00 | 0.00 | -229029.43 | 0.00 | 0.00 | 0.00 | 440.81 | 3603.49 | 124501.07 | 0.00 | 418.79 | 100065.27 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 25-JUN-16:11 | 0.00 | 0.00 | 0.00 | -19369.14 | 0.00 | 0.00 | 40.78 | 68.40 | 720.18 | 4810.08 | 0.00 | 639.73 | 13089.97 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 27-AUG-09:12 | 0.00 | 0.00 | 0.00 | -21241.64 | 0.00 | 0.00 | 21.78 | 44.08 | 464.11 | 13971.58 | 0.00 | 0.00 | 6757.86 | 0.00 | -0.00 | 0.00 | -17.78 | 0.00 |
PERIMETER_TOP_ZN_1 | 09-OCT-14:12 | 0.00 | 0.00 | 0.00 | -23883.83 | 0.00 | 0.00 | 36.10 | 68.40 | 720.19 | 15834.10 | 0.00 | 0.00 | 7294.40 | 0.00 | -0.00 | 0.00 | -69.37 | 0.00 |
PERIMETER_TOP_ZN_4 | 25-JUN-16:11 | 0.00 | 0.00 | 0.00 | -24612.80 | 0.00 | 0.00 | 19.04 | 44.08 | 464.11 | 12741.08 | 0.00 | 293.10 | 11051.39 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 09-APR-18:15 | 0.00 | 0.00 | 0.00 | -7933.39 | 0.00 | 0.00 | 0.00 | 32.15 | 7794.42 | 0.00 | 0.00 | 0.00 | 106.81 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 14-APR-18:30 | 0.00 | 0.00 | 0.00 | -74666.95 | 0.00 | 0.00 | 106.16 | 1929.04 | 77944.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -5312.47 |
DATACENTER_TOP_ZN_6 | 13-AUG-18:52 | 0.00 | 0.00 | 0.00 | -7660.98 | 0.00 | 0.00 | 0.00 | 32.15 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -165.60 |
DATACENTER_BASEMENT_ZN_6 | 07-AUG-21:14 | 0.00 | 0.00 | 0.00 | -370519.97 | 0.00 | 0.00 | 113.75 | 719.03 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -9945.33 |
GROUNDFLOOR_PLENUM | 05-SEP-05:02 | 0.00 | -12621.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12676.43 | 0.00 | -0.00 | 0.00 | -55.25 | 0.00 |
MIDFLOOR_PLENUM | 12-FEB-06:01 | 0.00 | -100658.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 172572.79 | 0.00 | -0.00 | 0.00 | -71913.83 | 0.00 |
TOPFLOOR_PLENUM | 07-JUL-15:10 | 0.00 | -19740.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 110.69 | 19629.43 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 17-AUG-04:12 | 0.00 | 55851.07 | 0.00 | -2017906.41 | 0.00 | 0.00 | 0.00 | 42872.09 | 587299.42 | 0.00 | 0.00 | 0.00 | 1388106.59 | 0.00 | -54098.94 | 0.00 | -2123.80 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | 08-JUL-16:01 | 0.00 | 0.00 | 25904.38 | 0.00 | 0.00 | 0.00 | 520.12 | 1274.92 | 13457.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -41156.97 |
CORE_BOTTOM | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 09-JAN-05:01 | 0.00 | 0.00 | 378434.73 | 0.00 | 0.00 | 0.00 | 0.00 | 22901.98 | 59376.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -460712.94 |
CORE_TOP | 09-JAN-04:11 | 0.00 | 0.00 | 80513.06 | 0.00 | 0.00 | 0.00 | 0.00 | 1144.97 | 5937.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -87595.66 |
PERIMETER_BOT_ZN_3 | 13-FEB-05:01 | 0.00 | 0.00 | 12406.37 | 0.00 | 0.00 | 0.00 | 0.00 | 287.56 | 745.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -6938.49 | 0.00 | -1340.17 | -5160.83 |
PERIMETER_BOT_ZN_2 | 09-JAN-05:01 | 0.00 | 0.00 | 9609.96 | 0.00 | 0.00 | 0.00 | 0.00 | 185.31 | 480.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3780.79 | 0.00 | -593.32 | -5901.63 |
PERIMETER_BOT_ZN_1 | 09-JAN-04:17 | 0.00 | 0.00 | 15051.78 | 0.00 | 0.00 | 0.00 | 0.00 | 143.77 | 745.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -5314.15 | 0.00 | -796.97 | -9830.00 |
PERIMETER_BOT_ZN_4 | 09-JAN-05:01 | 0.00 | 0.00 | 6766.46 | 0.00 | 0.00 | 0.00 | 0.00 | 185.31 | 480.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -4112.88 | 0.00 | -619.39 | -2699.96 |
PERIMETER_MID_ZN_3 | 12-FEB-06:01 | 0.00 | 0.00 | 150087.53 | 0.00 | 0.00 | 0.00 | 909.34 | 1437.63 | 7201.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -77734.49 | 0.00 | -40749.21 | -41152.63 |
PERIMETER_MID_ZN_2 | 12-FEB-06:01 | 0.00 | 0.00 | 158058.44 | 0.00 | 0.00 | 0.00 | 586.29 | 926.46 | 4641.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -49762.85 | 0.00 | -27528.39 | -86921.08 |
PERIMETER_MID_ZN_1 | 12-FEB-06:01 | 0.00 | 0.00 | 175451.53 | 0.00 | 0.00 | 0.00 | 906.88 | 1437.66 | 7201.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -75343.89 | 0.00 | -41082.82 | -68571.31 |
PERIMETER_MID_ZN_4 | 12-FEB-06:01 | 0.00 | 0.00 | 158031.42 | 0.00 | 0.00 | 0.00 | 580.66 | 926.46 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -52898.57 | 0.00 | -27806.67 | -83474.40 |
PERIMETER_TOP_ZN_3 | 12-FEB-00:02 | 0.00 | 0.00 | 17448.77 | 0.00 | 0.00 | 0.00 | 0.00 | 143.76 | 559.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -7034.88 | 0.00 | -4095.22 | -7021.60 |
PERIMETER_TOP_ZN_2 | 12-FEB-06:01 | 0.00 | 0.00 | 17540.19 | 0.00 | 0.00 | 0.00 | 59.96 | 92.65 | 464.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -4746.28 | 0.00 | -3335.14 | -10075.49 |
PERIMETER_TOP_ZN_1 | 12-FEB-06:01 | 0.00 | 0.00 | 19885.99 | 0.00 | 0.00 | 0.00 | 92.69 | 143.77 | 720.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -7173.53 | 0.00 | -4977.47 | -8691.65 |
PERIMETER_TOP_ZN_4 | 12-FEB-06:01 | 0.00 | 0.00 | 18938.25 | 0.00 | 0.00 | 0.00 | 59.47 | 92.65 | 464.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -5063.58 | 0.00 | -3384.54 | -11106.35 |
DATACENTER_BOT_ZN_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 16-JAN-03:20 | 0.00 | 0.00 | 5473.67 | 0.00 | 0.00 | 0.00 | 0.00 | 321.53 | 19486.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -25281.25 |
DATACENTER_TOP_ZN_6 | 15-JAN-18:45 | 0.00 | 0.00 | 601.45 | 0.00 | 0.00 | 0.00 | 0.00 | 32.15 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -2582.21 |
DATACENTER_BASEMENT_ZN_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 26-DEC-05:11 | 14272.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -2195.50 | -12076.88 |
MIDFLOOR_PLENUM | 06-JAN-12:00 | 140383.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -6815.93 | -133567.34 |
TOPFLOOR_PLENUM | 13-FEB-05:09 | 26966.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -4947.40 | -22019.44 |
Total Facility | 09-JAN-05:01 | -78909.11 | 107947.93 | 1128840.47 | -107947.93 | 0.00 | 0.00 | 0.00 | 42872.09 | 232425.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -209583.83 | 0.00 | -114244.94 | -1001399.90 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 08:43:24
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
VAV_BOT WITH REHEAT | 11.1711 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 10.0760 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_MID WITH REHEAT | 105.6802 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 94.0360 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_TOP WITH REHEAT | 10.8322 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 10.1979 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
CAV_BAS | 6.0861 | 0.0000 | 149.6021 | 1.0000 | Calculated from schedules | 1.2002 | 6.0861 | 0.1972 | 1.0000 | Not calculated | 1.2002 | 0.1972 | ||
AIRLOOP DATACENTER BASEMENT | 22.1364 | 0.0000 | 42.1814 | 1.0000 | Calculated from schedules | 0.3384 | 22.1366 | 0.0153 | 1.0000 | Not calculated | 0.3384 | 0.0153 | ||
AIRLOOP DATACENTER BOT | 0.4922 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.4922 | 0.0318 | 1.0000 | Not calculated | 0.0156 | 0.0318 | ||
AIRLOOP DATACENTER MID | 4.6918 | 0.0000 | 19.4861 | 1.0000 | Calculated from schedules | 0.1563 | 4.6918 | 0.0333 | 1.0000 | Not calculated | 0.1563 | 0.0333 | ||
AIRLOOP DATACENTER TOP | 0.4779 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.4779 | 0.0327 | 1.0000 | Not calculated | 0.0156 | 0.0327 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
VAV_BOT WITH REHEAT | 5.5856 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 2.9518 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_MID WITH REHEAT | 52.8401 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 28.7295 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_TOP WITH REHEAT | 5.4161 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 2.9650 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
CAV_BAS | 6.0861 | 0.0000 | 149.6021 | 1.0000 | Calculated from schedules | 1.2002 | 6.0861 | 1.0000 | 1.0000 | Not calculated | 1.2002 | 0.1972 | ||
AIRLOOP DATACENTER BASEMENT | 22.1364 | 0.0000 | 42.1814 | 1.0000 | Calculated from schedules | 0.3384 | 22.1364 | 1.0000 | 1.0000 | Not calculated | 0.3384 | 0.0153 | ||
AIRLOOP DATACENTER BOT | 0.4922 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.4922 | 1.0000 | 1.0000 | Not calculated | 0.0156 | 0.0318 | ||
AIRLOOP DATACENTER MID | 4.6918 | 0.0000 | 19.4861 | 1.0000 | Calculated from schedules | 0.1563 | 4.6918 | 1.0000 | 1.0000 | Not calculated | 0.1563 | 0.0333 | ||
AIRLOOP DATACENTER TOP | 0.4779 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.4779 | 1.0000 | 1.0000 | Not calculated | 0.0156 | 0.0327 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
BASEMENT | CAV_BAS | 0.000000 | 149.6021 | 0.000432 | 2779.43 | 1.2002 | 1.0000 | 1.2002 | 1.000 | 1.2002 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | 0.000000 | 134.3532 | 0.000432 | 2496.12 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_MID | VAV_MID WITH REHEAT | 0.000000 | 1343.5320 | 0.000432 | 24961.20 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_TOP | VAV_TOP WITH REHEAT | 0.000000 | 134.3532 | 0.000432 | 2496.12 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | 0.000000 | 16.8694 | 0.000432 | 313.41 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | 0.000000 | 16.8698 | 0.000432 | 313.42 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | 0.000000 | 168.6939 | 0.000432 | 3134.13 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | 0.000000 | 108.7127 | 0.000432 | 2019.75 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | 0.000000 | 168.6975 | 0.000432 | 3134.20 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | 0.000000 | 108.7127 | 0.000432 | 2019.75 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | 0.000000 | 16.8694 | 0.000432 | 313.41 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | 0.000000 | 16.8698 | 0.000432 | 313.42 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | 0.000000 | 1.9486 | 0.000432 | 36.20 | 0.0156 | 1.0000 | 0.0156 | 1.000 | 0.0156 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | 0.000000 | 19.4861 | 0.000432 | 362.03 | 0.1563 | 1.0000 | 0.1563 | 1.000 | 0.1563 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | 0.000000 | 1.9486 | 0.000432 | 36.20 | 0.0156 | 1.0000 | 0.0156 | 1.000 | 0.0156 |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | 0.000000 | 42.1814 | 0.000432 | 783.68 | 0.3384 | 1.0000 | 0.3384 | 1.000 | 0.3384 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
VAV_BOT WITH REHEAT | 0.00 | 0.000432 | 3526.9033 | 0.0000 | 0.0000 | 0.0000 | |
VAV_MID WITH REHEAT | 0.00 | 0.000432 | 35269.0328 | 0.0000 | 0.0000 | 0.0000 | |
VAV_TOP WITH REHEAT | 0.00 | 0.000432 | 3526.9033 | 0.0000 | 0.0000 | 0.0000 | |
CAV_BAS | 0.000000 | 149.60 | 0.000432 | 2779.4266 | 1.2002 | 1.2002 | 1.2002 |
AIRLOOP DATACENTER BASEMENT | 0.000000 | 42.18 | 0.000432 | 783.6794 | 0.3384 | 0.3384 | 0.3384 |
AIRLOOP DATACENTER BOT | 0.000000 | 1.95 | 0.000432 | 36.2027 | 0.0156 | 0.0156 | 0.0156 |
AIRLOOP DATACENTER MID | 0.000000 | 19.49 | 0.000432 | 362.0274 | 0.1563 | 0.1563 | 0.1563 |
AIRLOOP DATACENTER TOP | 0.000000 | 1.95 | 0.000432 | 36.2027 | 0.0156 | 0.0156 | 0.0156 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | CAV_BAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 6.0861 | 6.0861 | 6.0861 | No | 1.2002 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 6.3471 | 6.3471 | 1.9549 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 59.9690 | 59.9690 | 19.1901 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 5.9111 | 5.9111 | 1.9625 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.0690 | 1.0690 | 0.2459 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.1063 | 1.1063 | 0.2213 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.2535 | 1.2535 | 0.2507 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.3953 | 1.3953 | 0.2791 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 10.1372 | 10.1372 | 2.4127 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 11.4552 | 11.4552 | 2.2910 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 11.9730 | 11.9730 | 2.4066 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 12.1459 | 12.1459 | 2.4292 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.1421 | 1.1421 | 0.2467 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.1647 | 1.1647 | 0.2329 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.3165 | 1.3165 | 0.2633 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.2979 | 1.2979 | 0.2596 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.4922 | 0.4922 | 0.4922 | No | 0.0156 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 4.6918 | 4.6918 | 4.6918 | No | 0.1563 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.4779 | 0.4779 | 0.4779 | No | 0.0156 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 22.1364 | 22.1364 | 22.1364 | No | 0.3384 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
VAV_BOT WITH REHEAT | 11.1711 | 10.0760 | 11.1711 | 2.9518 | 0.0000 | 1.0000 |
VAV_MID WITH REHEAT | 105.6802 | 94.0360 | 105.6802 | 28.7295 | 0.0000 | 1.0000 |
VAV_TOP WITH REHEAT | 10.8322 | 10.1979 | 10.8322 | 2.9650 | 0.0000 | 1.0000 |
CAV_BAS | 6.0861 | 6.0861 | 6.0861 | 6.0861 | 1.2002 | 1.0000 |
AIRLOOP DATACENTER BASEMENT | 22.1364 | 22.1366 | 22.1364 | 22.1364 | 0.3384 | 1.0000 |
AIRLOOP DATACENTER BOT | 0.4922 | 0.4922 | 0.4922 | 0.4922 | 0.0156 | 1.0000 |
AIRLOOP DATACENTER MID | 4.6918 | 4.6918 | 4.6918 | 4.6918 | 0.1563 | 1.0000 |
AIRLOOP DATACENTER TOP | 0.4779 | 0.4779 | 0.4779 | 0.4779 | 0.0156 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | CAV_BAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 6.0861 | 6.0861 | 6.0861 | No | 1.2002 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 3.1735 | 3.1735 | 1.9549 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 29.9845 | 29.9845 | 19.1901 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.9555 | 2.9555 | 1.9625 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5345 | 0.5345 | 0.2459 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5532 | 0.5532 | 0.2213 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6267 | 0.6267 | 0.2507 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6976 | 0.6976 | 0.2791 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 5.0686 | 5.0686 | 2.4127 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 5.7276 | 5.7276 | 2.2910 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 5.9865 | 5.9865 | 2.4066 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 6.0729 | 6.0729 | 2.4292 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5710 | 0.5710 | 0.2467 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5823 | 0.5823 | 0.2329 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6583 | 0.6583 | 0.2633 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6489 | 0.6489 | 0.2596 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.4922 | 0.4922 | 0.4922 | No | 0.0156 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 4.6918 | 4.6918 | 4.6918 | No | 0.1563 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.4779 | 0.4779 | 0.4779 | No | 0.0156 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 22.1364 | 22.1364 | 22.1364 | No | 0.3384 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
VAV_BOT WITH REHEAT | 5.5856 | 2.9518 | 2.9518 | 2.9518 | 0.0000 | 1.0000 |
VAV_MID WITH REHEAT | 52.8401 | 28.7295 | 28.7295 | 28.7295 | 0.0000 | 1.0000 |
VAV_TOP WITH REHEAT | 5.4161 | 2.9650 | 2.9650 | 2.9650 | 0.0000 | 1.0000 |
CAV_BAS | 6.0861 | 6.0861 | 6.0861 | 6.0861 | 1.2002 | 1.0000 |
AIRLOOP DATACENTER BASEMENT | 22.1364 | 22.1364 | 22.1364 | 22.1364 | 0.3384 | 1.0000 |
AIRLOOP DATACENTER BOT | 0.4922 | 0.4922 | 0.4922 | 0.4922 | 0.0156 | 1.0000 |
AIRLOOP DATACENTER MID | 4.6918 | 4.6918 | 4.6918 | 4.6918 | 0.1563 | 1.0000 |
AIRLOOP DATACENTER TOP | 0.4779 | 0.4779 | 0.4779 | 0.4779 | 0.0156 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 08:43:24
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Atlanta-Hartsfield Jackson Intl AP GA USA TMY3 WMO#=722190 |
Total gross floor area [m2] | 46320.38 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
BASEMENT | 2779.43 | 2779.43 | 0.00 | 113.98 |
CORE_BOTTOM | 2496.12 | 2496.12 | 0.00 | 113.98 |
CORE_MID | 2496.12 | 2496.12 | 0.00 | 113.98 |
CORE_TOP | 2496.12 | 2496.12 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_3 | 313.41 | 313.41 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_2 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_1 | 313.42 | 313.42 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_4 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_MID_ZN_3 | 313.41 | 313.41 | 0.00 | 113.98 |
PERIMETER_MID_ZN_2 | 201.98 | 201.98 | 0.00 | 96.54 |
PERIMETER_MID_ZN_1 | 313.42 | 313.42 | 0.00 | 113.98 |
PERIMETER_MID_ZN_4 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_3 | 313.41 | 313.41 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_2 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_1 | 313.42 | 313.42 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_4 | 201.98 | 201.98 | 0.00 | 113.98 |
DATACENTER_BOT_ZN_6 | 36.20 | 36.20 | 0.00 | 113.98 |
DATACENTER_MID_ZN_6 | 36.20 | 36.20 | 0.00 | 113.98 |
DATACENTER_TOP_ZN_6 | 36.20 | 36.20 | 0.00 | 113.98 |
DATACENTER_BASEMENT_ZN_6 | 783.68 | 783.68 | 0.00 | 113.98 |
GROUNDFLOOR_PLENUM | 3563.11 | 3563.11 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 3563.11 | 3563.11 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 3563.11 | 3563.11 | 0.00 | 0.00 |
Totals | 46320.38 | 46320.38 | 0.00 |
Data | |
Number of hours heating loads not met | 32.33 |
Number of hours cooling loads not met | 532.33 |
Number of hours not met | 564.33 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler | 0.00 | 0.00 | 958.69 | 1771654.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 4405.04 | 456876.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 3936.13 | 385834.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 695.97 | 57580.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 5334.97 | 305206.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- DataCenterPlugLoads | 9341.42 | 473165.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Transformer | 80.18 | 5057.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLift | 1848.78 | 113101.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLightsFan | 5.83 | 376.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 2129.53 | 173140.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 597.12 | 61546.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- General | 1479.78 | 92827.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- General | 8.94 | 5868.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- General | 52.13 | 5613.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 0.00 | 0.00 | 734.54 | 82149.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 14676.40 | 29915.83 |
Natural Gas | 0.00 | 1693.23 |
Additional | 0.00 | 0.00 |
Total | 14676.40 | 31609.06 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 84.98 |
Space Heating | 0.00 |
Space Cooling | 95.10 |
Fans (All) | 45.97 |
Service Water Heating | 0.00 |
Receptacle Equipment | 316.85 |
Miscellaneous (All) | 645.85 |
Subtotal | 645.85 |
Natural Gas [MJ/m2] | |
Space Heating | 20.70 |
Service Water Heating | 15.86 |
Miscellaneous (All) | 36.55 |
Subtotal | 36.55 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 12.45 |
Space Heating | 3.03 |
Space Cooling | 13.94 |
Fans (All) | 6.74 |
Service Water Heating | 2.32 |
Receptacle Equipment | 46.43 |
Miscellaneous | 15.09 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 4472. | 4472. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 6752. | 8760. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 6828. | 8760. |
ALWAYS_OFF | 0. | 0. |
LTG_SCH_OFFICE | 2625. | 8760. |
LTG_SCH_DATACENTER | 2921. | 8760. |
EXTERIOR_LIGHT_SCH | 4380. | 4380. |
BLDG_EQUIP_SCH | 4049. | 8760. |
DATACENTER_EQUIP_SCH | 5478. | 8760. |
BLDG_OCC_SCH | 2528. | 5992. |
BLDG_OCC_SCH_W_SB | 1878. | 5056. |
BLDG_OCC_SCH_WO_SB | 2557. | 5992. |
BLDG_ELEVATORS | 2270. | 8760. |
ELEV_LIGHT_FAN_SCH_24_7 | 8760. | 8760. |
ELEV_LIGHT_FAN_SCH_ADD_DF | 2154. | 8760. |
BLDG_SWH_SCH | 1474. | 6570. |
WORK_EFF_SCH | 0. | 0. |
INFIL_SCH | 3976. | 3976. |
INFIL_SCH_PNNL | 5172. | 8760. |
INFIL_HALF_ON_SCH | 6368. | 8760. |
FAN_SCH | 8760. | 8760. |
REHEATCOILAVAILSCHED | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
MINOA_MOTORIZEDDAMPER_SCHED | 4472. | 4472. |
MINOA_SCHED | 8760. | 8760. |
CORE_BOTTOM SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_BOTTOM SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_MID SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_MID SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_TOP SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_TOP SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
SUPPLYFANSCH | 8760. | 8760. |
PERIMETER_MID_ZN_2_MDP_SCH | 1565. | 7824. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
HTGSETP_DC_SCH | DATACENTER COOLING SETPOINTS DUAL SP CONTROL | January | 18.00 | 365 | 18.00 | 365 |
CLGSETP_DC_SCH | DATACENTER COOLING SETPOINTS DUAL SP CONTROL | July | 27.00 | 365 | 27.00 | 365 |
HTGSETP_SCH_YES_OPTIMUM | CORE_BOTTOM DUAL SP CONTROL | January | 21.00 | 365 | 15.60 | 365 |
CLGSETP_SCH_YES_OPTIMUM | CORE_BOTTOM DUAL SP CONTROL | July | 24.00 | 365 | 26.70 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:43:24
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
BASEMENT | 7943.83 | 816.17 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 8710.33 | 49.67 | 0.00 | 0.00 | 0.00 |
CORE_MID | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 8745.67 | 14.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 8704.17 | 55.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 8700.83 | 59.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 8107.33 | 652.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 8749.50 | 10.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 8673.83 | 86.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 8688.00 | 72.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 8411.83 | 348.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 8732.83 | 27.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 8652.33 | 107.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 8678.17 | 81.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 8400.83 | 359.17 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 6750.50 | 2009.50 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 6715.17 | 2044.83 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 6695.00 | 2065.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 6620.33 | 2139.67 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 8653.67 | 106.33 | 0.00 | 0.00 | 0.00 |
Min | 6620.33 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 2139.67 | 0.00 | 0.00 | 0.00 |
Average | 8277.14 | 482.86 | 0.00 | 0.00 | 0.00 |
Sum | 190374.17 | 11105.83 | 0.00 | 0.00 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
BASEMENT | 366586.00 | 2030.00 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 330729.00 | 84.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 330813.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 330813.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 18354.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 1236.33 | 1031.67 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 1220.67 | 1047.33 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 1212.33 | 1055.67 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 61178.00 | 42217.00 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 366586.00 | 42217.00 | 0.00 | 0.00 | 0.00 |
Average | 78271.19 | 2063.72 | 0.00 | 0.00 | 0.00 |
Sum | 1800237.33 | 47465.67 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
BASEMENT | 6265.50 | 2494.50 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 8436.67 | 323.33 | 0.00 | 0.00 | 0.00 |
CORE_MID | 8732.33 | 27.67 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 8750.00 | 10.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 8447.17 | 312.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 8475.17 | 284.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 8374.00 | 386.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 7729.00 | 1031.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 7849.17 | 910.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 7836.17 | 923.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 7712.17 | 1047.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 7657.50 | 1102.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 7801.50 | 958.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 7793.83 | 966.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 7702.00 | 1058.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 7656.50 | 1103.50 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 7389.17 | 1370.83 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 7330.17 | 1429.83 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 7313.50 | 1446.50 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 7469.50 | 1290.50 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 8668.33 | 91.67 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 8433.17 | 326.83 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 8262.00 | 498.00 | 0.00 | 0.00 | 0.00 |
Min | 6265.50 | 10.00 | 0.00 | 0.00 | 0.00 |
Max | 8750.00 | 2494.50 | 0.00 | 0.00 | 0.00 |
Average | 7916.72 | 843.28 | 0.00 | 0.00 | 0.00 |
Sum | 182084.50 | 19395.50 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
BASEMENT | 345290.50 | 23325.50 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 330296.33 | 516.67 | 0.00 | 0.00 | 0.00 |
CORE_MID | 330703.00 | 110.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 330790.00 | 23.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 38922.17 | 2.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 18353.17 | 0.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 38922.67 | 2.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 24908.50 | 0.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 38920.00 | 5.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 24908.00 | 1.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 38921.67 | 3.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 24908.50 | 0.50 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 1469.33 | 798.67 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 1444.17 | 823.83 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 1430.50 | 837.50 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 75391.17 | 28003.83 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 345290.50 | 28003.83 | 0.00 | 0.00 | 0.00 |
Average | 77967.29 | 2367.62 | 0.00 | 0.00 | 0.00 |
Sum | 1793247.67 | 54455.33 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:43:24
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:43:24
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 0.00 | 8760.00 | 0.00 |
Average | 0.00 | 0.00 | 4570.43 | 0.00 |
Sum | 0.00 | 0.00 | 105120.00 | 0.00 |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 18354.00 | 0.00 |
PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 24909.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 0.00 | 38925.00 | 0.00 |
Average | 0.00 | 0.00 | 16367.35 | 0.00 |
Sum | 0.00 | 0.00 | 376449.00 | 0.00 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 3.965 |
February | 7.937 |
March | 13.764 |
April | 17.213 |
May | 20.837 |
June | 24.797 |
July | 26.063 |
August | 26.547 |
September | 22.525 |
October | 16.026 |
November | 11.940 |
December | 7.696 |
Annual Sum or Average | 16.653 |
Minimum of Months | 3.965 |
Maximum of Months | 26.547 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Environment
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 3.965 |
February | 7.937 |
March | 13.764 |
April | 17.213 |
May | 20.837 |
June | 24.797 |
July | 26.063 |
August | 26.547 |
September | 22.525 |
October | 16.026 |
November | 11.940 |
December | 7.696 |
Annual Sum or Average | 16.653 |
Minimum of Months | 3.965 |
Maximum of Months | 26.547 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2013
For: Environment
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 3.965 |
February | 7.937 |
March | 13.764 |
April | 17.213 |
May | 20.837 |
June | 24.797 |
July | 26.063 |
August | 26.547 |
September | 22.525 |
October | 16.026 |
November | 11.940 |
December | 7.696 |
Annual Sum or Average | 16.653 |
Minimum of Months | 3.965 |
Maximum of Months | 26.547 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 3.965 |
February | 7.937 |
March | 13.764 |
April | 17.213 |
May | 20.837 |
June | 24.797 |
July | 26.063 |
August | 26.547 |
September | 22.525 |
October | 16.026 |
November | 11.940 |
December | 7.696 |
Annual Sum or Average | 16.653 |
Minimum of Months | 3.965 |
Maximum of Months | 26.547 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICELARGE
For: Environment
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 3.965 |
February | 7.937 |
March | 13.764 |
April | 17.213 |
May | 20.837 |
June | 24.797 |
July | 26.063 |
August | 26.547 |
September | 22.525 |
October | 16.026 |
November | 11.940 |
December | 7.696 |
Annual Sum or Average | 16.653 |
Minimum of Months | 3.965 |
Maximum of Months | 26.547 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 3.965 |
February | 7.937 |
March | 13.764 |
April | 17.213 |
May | 20.837 |
June | 24.797 |
July | 26.063 |
August | 26.547 |
September | 22.525 |
October | 16.026 |
November | 11.940 |
December | 7.696 |
Annual Sum or Average | 16.653 |
Minimum of Months | 3.965 |
Maximum of Months | 26.547 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 3.965 |
February | 7.937 |
March | 13.764 |
April | 17.213 |
May | 20.837 |
June | 24.797 |
July | 26.063 |
August | 26.547 |
September | 22.525 |
October | 16.026 |
November | 11.940 |
December | 7.696 |
Annual Sum or Average | 16.653 |
Minimum of Months | 3.965 |
Maximum of Months | 26.547 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 3A
For: Environment
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 3.965 |
February | 7.937 |
March | 13.764 |
April | 17.213 |
May | 20.837 |
June | 24.797 |
July | 26.063 |
August | 26.547 |
September | 22.525 |
October | 16.026 |
November | 11.940 |
December | 7.696 |
Annual Sum or Average | 16.653 |
Minimum of Months | 3.965 |
Maximum of Months | 26.547 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_GA_ATLANTA
For: Environment
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 3.965 |
February | 7.937 |
March | 13.764 |
April | 17.213 |
May | 20.837 |
June | 24.797 |
July | 26.063 |
August | 26.547 |
September | 22.525 |
October | 16.026 |
November | 11.940 |
December | 7.696 |
Annual Sum or Average | 16.653 |
Minimum of Months | 3.965 |
Maximum of Months | 26.547 |
Report: ZoneCoolingSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.462637E+11 | 117755.26 | 02-JAN-05:11 | 3.30 | 2.57 | 0.565035E+10 | 7499.27 | 30-JAN-10:50 | 13.67 | 9.38 |
February | 0.436103E+11 | 119279.88 | 21-FEB-05:11 | 6.33 | 4.24 | 0.513087E+10 | 7499.15 | 28-FEB-14:30 | 25.00 | 13.71 |
March | 0.563288E+11 | 116375.27 | 06-MAR-05:11 | 4.03 | 0.98 | 0.613031E+10 | 7499.46 | 08-MAR-10:20 | 16.10 | 12.08 |
April | 0.518571E+11 | 113953.56 | 10-APR-04:12 | 8.90 | 6.08 | 0.544631E+10 | 7499.27 | 03-APR-09:20 | 8.90 | 6.08 |
May | 0.561563E+11 | 112130.78 | 15-MAY-04:12 | 12.60 | 11.09 | 0.589928E+10 | 7499.38 | 11-MAY-09:00 | 12.60 | 11.09 |
June | 0.609751E+11 | 111458.60 | 08-JUN-04:12 | 11.70 | 8.69 | 0.588183E+10 | 7499.07 | 09-JUN-09:00 | 24.40 | 15.46 |
July | 0.615275E+11 | 97170.68 | 03-JUL-04:23 | 17.80 | 16.55 | 0.547389E+10 | 7498.78 | 19-JUL-09:20 | 22.57 | 21.92 |
August | 0.700230E+11 | 93509.31 | 26-AUG-04:12 | 21.70 | 17.11 | 0.613872E+10 | 7499.01 | 25-AUG-09:39 | 21.70 | 17.11 |
September | 0.642037E+11 | 113311.09 | 14-SEP-04:12 | 12.60 | 11.28 | 0.545392E+10 | 7499.18 | 22-SEP-13:09 | 26.20 | 16.90 |
October | 0.649951E+11 | 120516.13 | 30-OCT-04:11 | 8.90 | 8.90 | 0.567142E+10 | 7498.98 | 31-OCT-09:00 | 10.60 | 9.10 |
November | 0.629710E+11 | 117080.44 | 06-NOV-05:12 | 9.80 | 9.21 | 0.561573E+10 | 7499.35 | 16-NOV-10:20 | 10.77 | 10.06 |
December | 0.575171E+11 | 119360.14 | 11-DEC-05:11 | 6.33 | 5.61 | 0.546904E+10 | 7499.27 | 11-DEC-10:00 | 15.00 | 12.11 |
Annual Sum or Average | 0.696429E+12 | 0.679617E+11 | ||||||||
Minimum of Months | 0.436103E+11 | 93509.31 | 3.30 | 0.98 | 0.513087E+10 | 7498.78 | 8.90 | 6.08 | ||
Maximum of Months | 0.700230E+11 | 120516.13 | 21.70 | 17.11 | 0.613872E+10 | 7499.46 | 26.20 | 21.92 |
Report: ZoneCoolingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.394615E+11 | 92999.03 | 02-JAN-05:11 | 3.30 | 2.57 | 0.498996E+10 | 6746.09 | 27-JAN-14:00 | 3.90 | -1.8 |
February | 0.408242E+11 | 92429.04 | 21-FEB-05:11 | 6.33 | 4.24 | 0.456138E+10 | 6748.62 | 02-FEB-14:50 | 6.33 | 4.24 |
March | 0.578367E+11 | 93461.30 | 06-MAR-05:11 | 4.03 | 0.98 | 0.548841E+10 | 6741.27 | 22-MAR-13:39 | 4.40 | 3.91 |
April | 0.606425E+11 | 95150.35 | 14-APR-04:13 | 13.53 | 10.31 | 0.487759E+10 | 6734.77 | 17-APR-13:50 | 28.72 | 16.68 |
May | 0.580105E+11 | 99086.11 | 30-MAY-04:13 | 19.43 | 17.60 | 0.527883E+10 | 6735.15 | 11-MAY-09:00 | 19.43 | 17.60 |
June | 0.660751E+11 | 99664.12 | 20-JUN-04:13 | 19.40 | 19.07 | 0.526535E+10 | 6734.77 | 09-JUN-09:00 | 19.40 | 19.07 |
July | 0.722353E+11 | 99025.80 | 01-JUL-04:13 | 21.70 | 20.50 | 0.488870E+10 | 6734.42 | 28-JUL-09:09 | 19.40 | 19.40 |
August | 0.827986E+11 | 81011.87 | 31-AUG-04:22 | 21.95 | 21.17 | 0.548899E+10 | 6734.41 | 24-AUG-09:09 | 21.95 | 21.17 |
September | 0.578771E+11 | 99855.04 | 11-SEP-04:13 | 20.20 | 19.05 | 0.487818E+10 | 6734.63 | 19-SEP-09:09 | 19.68 | 14.68 |
October | 0.562352E+11 | 97918.84 | 10-OCT-04:13 | 16.10 | 15.06 | 0.507169E+10 | 6734.63 | 30-OCT-09:00 | 11.10 | 11.10 |
November | 0.532143E+11 | 98819.34 | 13-NOV-05:11 | 4.23 | 1.45 | 0.502342E+10 | 6741.83 | 21-NOV-10:09 | 2.57 | -0.2 |
December | 0.491945E+11 | 94600.23 | 26-DEC-05:11 | 3.70 | 2.75 | 0.488745E+10 | 6734.83 | 11-DEC-10:00 | 3.70 | 2.75 |
Annual Sum or Average | 0.694405E+12 | 0.607000E+11 | ||||||||
Minimum of Months | 0.394615E+11 | 81011.87 | 3.30 | 0.98 | 0.456138E+10 | 6734.41 | 2.57 | -1.8 | ||
Maximum of Months | 0.827986E+11 | 99855.04 | 21.95 | 21.17 | 0.548899E+10 | 6748.62 | 28.72 | 21.17 |
Report: ZoneCoolingSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.298615E+11 | 71873.87 | 26-JAN-10:20 | -3.1 | -6.0 | 0.432600E+10 | 6754.15 | 26-JAN-10:39 | -3.0 | -5.9 |
February | 0.303885E+11 | 76309.38 | 28-FEB-06:02 | 10.78 | 5.86 | 0.412216E+10 | 6734.70 | 28-FEB-10:20 | 18.00 | 10.30 |
March | 0.418227E+11 | 83953.56 | 31-MAR-04:12 | 17.03 | 14.86 | 0.537301E+10 | 6734.99 | 08-MAR-10:20 | 17.03 | 14.86 |
April | 0.427796E+11 | 84631.49 | 19-APR-04:12 | 16.10 | 14.43 | 0.482560E+10 | 6734.75 | 12-APR-13:50 | 16.10 | 14.43 |
May | 0.498356E+11 | 85174.37 | 31-MAY-04:12 | 20.00 | 19.09 | 0.524942E+10 | 6735.11 | 11-MAY-09:00 | 20.00 | 19.09 |
June | 0.537568E+11 | 86897.76 | 21-JUN-04:11 | 19.80 | 18.77 | 0.524697E+10 | 6734.73 | 09-JUN-09:00 | 19.80 | 18.77 |
July | 0.538638E+11 | 86779.77 | 28-JUL-04:11 | 19.40 | 19.40 | 0.487417E+10 | 6734.43 | 18-JUL-13:09 | 19.40 | 19.40 |
August | 0.579936E+11 | 85261.99 | 25-AUG-04:12 | 19.80 | 18.06 | 0.547843E+10 | 6734.43 | 04-AUG-13:09 | 19.80 | 18.06 |
September | 0.485677E+11 | 86625.46 | 01-SEP-04:11 | 20.93 | 18.53 | 0.485037E+10 | 6734.60 | 19-SEP-09:09 | 19.68 | 14.68 |
October | 0.417563E+11 | 84030.19 | 19-OCT-04:12 | 21.50 | 21.50 | 0.498887E+10 | 6734.57 | 04-OCT-13:00 | 21.50 | 21.50 |
November | 0.356110E+11 | 78394.66 | 10-NOV-06:02 | 11.60 | 9.82 | 0.486885E+10 | 6734.88 | 16-NOV-10:09 | 10.68 | 10.03 |
December | 0.319447E+11 | 67912.21 | 14-DEC-06:03 | 6.60 | 5.31 | 0.445128E+10 | 6734.45 | 14-DEC-14:00 | 15.00 | 10.54 |
Annual Sum or Average | 0.518182E+12 | 0.586551E+11 | ||||||||
Minimum of Months | 0.298615E+11 | 67912.21 | -3.1 | -6.0 | 0.412216E+10 | 6734.43 | -3.0 | -5.9 | ||
Maximum of Months | 0.579936E+11 | 86897.76 | 21.50 | 21.50 | 0.547843E+10 | 6754.15 | 21.50 | 21.50 |
Report: ZoneCoolingSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.237192E+11 | 25778.01 | 20-JAN-17:00 | 16.70 | 11.48 | 0.396445E+10 | 6443.57 | 20-JAN-14:00 | 16.70 | 11.48 |
February | 0.253501E+11 | 35768.98 | 28-FEB-17:00 | 23.90 | 12.94 | 0.382085E+10 | 6734.65 | 22-FEB-14:00 | 23.90 | 12.94 |
March | 0.373756E+11 | 81761.47 | 31-MAR-05:02 | 16.78 | 15.18 | 0.506164E+10 | 6734.58 | 13-MAR-13:00 | 16.78 | 15.18 |
April | 0.403020E+11 | 81878.24 | 19-APR-05:02 | 16.02 | 14.35 | 0.469422E+10 | 6734.62 | 12-APR-09:30 | 16.02 | 14.35 |
May | 0.504345E+11 | 84727.51 | 19-MAY-04:12 | 16.70 | 15.65 | 0.522186E+10 | 6735.97 | 16-MAY-13:39 | 16.70 | 15.65 |
June | 0.573581E+11 | 86137.86 | 16-JUN-04:11 | 20.60 | 19.79 | 0.524238E+10 | 6734.68 | 09-JUN-09:00 | 20.60 | 19.79 |
July | 0.583366E+11 | 85688.56 | 12-JUL-04:12 | 20.60 | 19.95 | 0.487416E+10 | 6734.40 | 27-JUL-09:09 | 21.10 | 20.75 |
August | 0.627283E+11 | 84538.62 | 03-AUG-03:02 | 23.90 | 22.03 | 0.548000E+10 | 6734.41 | 24-AUG-09:09 | 23.40 | 22.97 |
September | 0.478812E+11 | 84678.66 | 06-SEP-04:12 | 21.50 | 20.31 | 0.481764E+10 | 6734.51 | 13-SEP-13:09 | 23.92 | 15.70 |
October | 0.375456E+11 | 83441.85 | 19-OCT-04:12 | 21.50 | 21.50 | 0.474016E+10 | 6734.50 | 04-OCT-13:00 | 21.50 | 21.50 |
November | 0.298134E+11 | 36812.64 | 04-NOV-05:03 | 16.60 | 15.28 | 0.440215E+10 | 6734.33 | 02-NOV-13:09 | 16.60 | 15.28 |
December | 0.260921E+11 | 32397.60 | 13-DEC-17:00 | 16.70 | 16.70 | 0.400381E+10 | 6734.35 | 13-DEC-14:09 | 16.70 | 16.70 |
Annual Sum or Average | 0.496937E+12 | 0.563233E+11 | ||||||||
Minimum of Months | 0.237192E+11 | 25778.01 | 16.02 | 11.48 | 0.382085E+10 | 6443.57 | 16.02 | 11.48 | ||
Maximum of Months | 0.627283E+11 | 86137.86 | 23.90 | 22.03 | 0.548000E+10 | 6735.97 | 23.92 | 22.97 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.256499E+10 | 3668.86 | 31-JAN-15:00 | 21.10 | 12.97 | 0.511853E+09 | 845.56 | 20-JAN-14:00 | 21.10 | 12.97 |
February | 0.335348E+10 | 6320.36 | 28-FEB-15:00 | 25.00 | 13.71 | 0.496985E+09 | 845.63 | 22-FEB-14:09 | 25.00 | 13.71 |
March | 0.576492E+10 | 7908.17 | 30-MAR-14:00 | 27.80 | 17.87 | 0.660267E+09 | 845.62 | 13-MAR-13:00 | 27.80 | 17.87 |
April | 0.708679E+10 | 8497.66 | 18-APR-14:00 | 27.20 | 15.86 | 0.601306E+09 | 845.64 | 17-APR-13:50 | 27.20 | 15.86 |
May | 0.814618E+10 | 13285.93 | 30-MAY-04:12 | 19.43 | 17.60 | 0.660204E+09 | 845.62 | 09-MAY-13:09 | 19.43 | 17.60 |
June | 0.110856E+11 | 13741.55 | 20-JUN-04:11 | 19.40 | 19.07 | 0.661657E+09 | 845.63 | 09-JUN-09:00 | 19.40 | 19.07 |
July | 0.121843E+11 | 14292.00 | 17-JUL-04:12 | 22.43 | 19.64 | 0.615235E+09 | 845.59 | 05-JUL-13:09 | 22.43 | 19.64 |
August | 0.135553E+11 | 13219.63 | 21-AUG-05:02 | 21.78 | 21.78 | 0.690239E+09 | 845.59 | 25-AUG-13:09 | 30.18 | 18.86 |
September | 0.780493E+10 | 13968.24 | 01-SEP-04:11 | 20.93 | 18.53 | 0.610213E+09 | 845.61 | 13-SEP-13:09 | 23.92 | 15.70 |
October | 0.583551E+10 | 13350.02 | 19-OCT-04:12 | 21.50 | 21.50 | 0.614631E+09 | 845.61 | 04-OCT-13:00 | 21.50 | 21.50 |
November | 0.466598E+10 | 5928.28 | 02-NOV-13:50 | 23.30 | 17.15 | 0.592963E+09 | 845.62 | 06-NOV-10:09 | 14.87 | 12.62 |
December | 0.395035E+10 | 5562.81 | 13-DEC-12:00 | 20.00 | 17.41 | 0.545539E+09 | 845.60 | 12-DEC-10:30 | 20.00 | 17.41 |
Annual Sum or Average | 0.859983E+11 | 0.726109E+10 | ||||||||
Minimum of Months | 0.256499E+10 | 3668.86 | 19.40 | 12.97 | 0.496985E+09 | 845.56 | 14.87 | 12.62 | ||
Maximum of Months | 0.135553E+11 | 14292.00 | 27.80 | 21.78 | 0.690239E+09 | 845.64 | 30.18 | 21.50 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.230147E+10 | 3174.77 | 24-JAN-10:30 | 6.10 | 2.41 | 0.331912E+09 | 537.08 | 24-JAN-10:30 | 6.10 | 2.41 |
February | 0.302437E+10 | 7192.47 | 27-FEB-09:40 | 12.23 | 5.46 | 0.321281E+09 | 544.96 | 28-FEB-10:00 | 20.60 | 11.95 |
March | 0.511502E+10 | 8589.53 | 26-MAR-10:23 | 13.30 | 7.32 | 0.422320E+09 | 545.00 | 08-MAR-10:09 | 13.30 | 7.32 |
April | 0.640824E+10 | 16930.54 | 16-APR-10:43 | 25.45 | 15.37 | 0.387196E+09 | 544.97 | 17-APR-13:50 | 28.72 | 16.68 |
May | 0.748111E+10 | 17635.52 | 29-MAY-09:43 | 24.45 | 19.91 | 0.424843E+09 | 545.01 | 11-MAY-09:00 | 24.45 | 19.91 |
June | 0.927972E+10 | 20029.05 | 04-JUN-09:02 | 24.78 | 18.48 | 0.425881E+09 | 544.97 | 09-JUN-09:00 | 24.40 | 15.46 |
July | 0.100622E+11 | 19452.84 | 23-JUL-09:22 | 26.95 | 22.77 | 0.395464E+09 | 544.93 | 03-JUL-13:09 | 26.95 | 22.77 |
August | 0.106328E+11 | 18414.67 | 13-AUG-08:32 | 25.53 | 22.81 | 0.443438E+09 | 544.93 | 25-AUG-13:09 | 30.18 | 18.86 |
September | 0.702049E+10 | 18504.47 | 24-SEP-09:02 | 23.77 | 18.55 | 0.391030E+09 | 544.95 | 15-SEP-09:00 | 23.77 | 18.55 |
October | 0.530049E+10 | 14006.48 | 09-OCT-10:13 | 22.93 | 17.62 | 0.393093E+09 | 544.95 | 05-OCT-09:00 | 22.93 | 17.62 |
November | 0.394580E+10 | 6772.69 | 06-NOV-09:25 | 13.30 | 11.71 | 0.376822E+09 | 544.96 | 06-NOV-10:09 | 14.87 | 12.62 |
December | 0.320252E+10 | 3613.65 | 08-DEC-10:10 | 8.58 | 4.06 | 0.346697E+09 | 544.96 | 11-DEC-10:00 | 15.00 | 12.11 |
Annual Sum or Average | 0.737743E+11 | 0.465998E+10 | ||||||||
Minimum of Months | 0.230147E+10 | 3174.77 | 6.10 | 2.41 | 0.321281E+09 | 537.08 | 6.10 | 2.41 | ||
Maximum of Months | 0.106328E+11 | 20029.05 | 26.95 | 22.81 | 0.443438E+09 | 545.01 | 30.18 | 22.77 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.448536E+10 | 17701.14 | 29-JAN-13:33 | 14.63 | 6.24 | 0.561521E+09 | 848.41 | 27-JAN-14:00 | 14.63 | 6.24 |
February | 0.546912E+10 | 22138.58 | 26-FEB-13:42 | 24.32 | 12.55 | 0.523728E+09 | 858.78 | 21-FEB-14:39 | 24.32 | 12.55 |
March | 0.849637E+10 | 20528.88 | 26-MAR-13:32 | 18.53 | 8.92 | 0.665654E+09 | 845.70 | 08-MAR-10:09 | 18.53 | 8.92 |
April | 0.895485E+10 | 15180.48 | 16-APR-13:23 | 28.60 | 16.10 | 0.600772E+09 | 845.71 | 17-APR-13:50 | 28.72 | 16.68 |
May | 0.897654E+10 | 15204.67 | 30-MAY-04:12 | 19.43 | 17.60 | 0.658434E+09 | 845.64 | 09-MAY-13:09 | 19.43 | 17.60 |
June | 0.112445E+11 | 15823.54 | 19-JUN-04:12 | 20.77 | 19.95 | 0.660953E+09 | 845.65 | 02-JUN-13:09 | 20.77 | 19.95 |
July | 0.126442E+11 | 17838.08 | 16-JUL-15:12 | 33.30 | 22.53 | 0.615260E+09 | 845.61 | 18-JUL-13:09 | 30.00 | 21.94 |
August | 0.155087E+11 | 21366.56 | 20-AUG-13:42 | 28.95 | 24.23 | 0.690706E+09 | 845.61 | 25-AUG-13:09 | 30.18 | 18.86 |
September | 0.104599E+11 | 21393.16 | 24-SEP-11:43 | 28.22 | 19.73 | 0.610539E+09 | 845.64 | 13-SEP-13:09 | 28.22 | 19.73 |
October | 0.979773E+10 | 22775.91 | 09-OCT-14:12 | 27.40 | 19.48 | 0.619640E+09 | 881.31 | 10-OCT-13:50 | 29.22 | 21.00 |
November | 0.787759E+10 | 22385.03 | 12-NOV-14:12 | 19.27 | 10.66 | 0.609076E+09 | 859.84 | 06-NOV-14:09 | 19.27 | 10.66 |
December | 0.661989E+10 | 21271.55 | 10-DEC-12:43 | 15.22 | 7.57 | 0.576231E+09 | 845.65 | 11-DEC-10:00 | 15.00 | 12.11 |
Annual Sum or Average | 0.110535E+12 | 0.739251E+10 | ||||||||
Minimum of Months | 0.448536E+10 | 15180.48 | 14.63 | 6.24 | 0.523728E+09 | 845.61 | 14.63 | 6.24 | ||
Maximum of Months | 0.155087E+11 | 22775.91 | 33.30 | 24.23 | 0.690706E+09 | 881.31 | 30.18 | 21.94 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.355910E+10 | 5620.44 | 23-JAN-16:30 | 10.00 | 3.54 | 0.339491E+09 | 544.91 | 20-JAN-14:00 | 10.00 | 3.54 |
February | 0.469667E+10 | 20885.02 | 26-FEB-15:42 | 24.50 | 12.42 | 0.333504E+09 | 544.96 | 22-FEB-14:09 | 24.50 | 12.42 |
March | 0.839345E+10 | 19572.29 | 30-MAR-04:12 | 17.40 | 15.44 | 0.437672E+09 | 544.98 | 08-MAR-10:30 | 17.40 | 15.44 |
April | 0.106985E+11 | 24158.98 | 09-APR-16:32 | 21.70 | 10.73 | 0.394685E+09 | 545.00 | 17-APR-13:50 | 28.72 | 16.68 |
May | 0.922475E+10 | 23702.32 | 29-MAY-15:42 | 29.90 | 20.57 | 0.425449E+09 | 544.95 | 09-MAY-13:09 | 29.90 | 20.57 |
June | 0.122603E+11 | 25886.29 | 11-JUN-15:51 | 32.80 | 21.45 | 0.427187E+09 | 544.96 | 09-JUN-09:00 | 32.80 | 21.45 |
July | 0.142015E+11 | 24824.01 | 09-JUL-16:41 | 33.40 | 22.81 | 0.397526E+09 | 544.93 | 05-JUL-13:09 | 33.40 | 22.81 |
August | 0.171678E+11 | 25616.70 | 13-AUG-16:31 | 30.73 | 22.34 | 0.446003E+09 | 544.93 | 25-AUG-13:09 | 30.18 | 18.86 |
September | 0.873578E+10 | 23593.98 | 04-SEP-17:02 | 28.12 | 21.99 | 0.393518E+09 | 544.95 | 19-SEP-09:09 | 19.68 | 14.68 |
October | 0.757430E+10 | 23735.94 | 22-OCT-15:32 | 23.30 | 14.86 | 0.401464E+09 | 544.95 | 04-OCT-13:00 | 23.30 | 14.86 |
November | 0.647381E+10 | 19654.22 | 12-NOV-14:52 | 20.00 | 10.89 | 0.396008E+09 | 544.96 | 06-NOV-10:09 | 20.00 | 10.89 |
December | 0.578485E+10 | 19745.06 | 13-DEC-05:12 | 17.03 | 15.54 | 0.379395E+09 | 544.96 | 11-DEC-10:00 | 17.03 | 15.54 |
Annual Sum or Average | 0.108771E+12 | 0.477190E+10 | ||||||||
Minimum of Months | 0.355910E+10 | 5620.44 | 10.00 | 3.54 | 0.333504E+09 | 544.91 | 10.00 | 3.54 | ||
Maximum of Months | 0.171678E+11 | 25886.29 | 33.40 | 22.81 | 0.446003E+09 | 545.00 | 33.40 | 22.81 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.638622E+09 | 2808.25 | 31-JAN-17:00 | 19.40 | 13.37 | 0.470757E+09 | 737.19 | 31-JAN-14:00 | 19.40 | 13.37 |
February | 0.145494E+10 | 4000.67 | 28-FEB-15:00 | 25.00 | 13.71 | 0.444700E+09 | 845.60 | 28-FEB-14:30 | 25.00 | 13.71 |
March | 0.381517E+10 | 6550.97 | 30-MAR-15:50 | 27.80 | 17.41 | 0.592411E+09 | 845.59 | 09-MAR-14:09 | 27.80 | 17.41 |
April | 0.470111E+10 | 7130.54 | 19-APR-14:30 | 26.15 | 17.54 | 0.567505E+09 | 845.63 | 12-APR-13:50 | 26.15 | 17.54 |
May | 0.678003E+10 | 8887.42 | 30-MAY-15:00 | 30.60 | 21.44 | 0.650099E+09 | 845.61 | 09-MAY-13:09 | 30.60 | 21.44 |
June | 0.925886E+10 | 16382.18 | 25-JUN-16:11 | 33.13 | 22.15 | 0.659959E+09 | 845.63 | 02-JUN-13:09 | 33.13 | 22.15 |
July | 0.963044E+10 | 15604.29 | 16-JUL-13:32 | 33.33 | 23.57 | 0.614432E+09 | 845.59 | 13-JUL-13:09 | 33.33 | 23.57 |
August | 0.100599E+11 | 12602.33 | 16-AUG-04:12 | 23.30 | 22.06 | 0.690095E+09 | 845.59 | 25-AUG-13:09 | 30.18 | 18.86 |
September | 0.642799E+10 | 11781.71 | 11-SEP-05:02 | 20.40 | 19.24 | 0.601315E+09 | 845.61 | 13-SEP-13:09 | 23.92 | 15.70 |
October | 0.411297E+10 | 6438.44 | 02-OCT-14:30 | 26.70 | 20.05 | 0.562362E+09 | 845.59 | 05-OCT-13:50 | 20.00 | 14.95 |
November | 0.271610E+10 | 3736.19 | 20-NOV-14:20 | 5.40 | 2.35 | 0.511260E+09 | 845.58 | 03-NOV-13:00 | 5.40 | 2.35 |
December | 0.137947E+10 | 3058.81 | 13-DEC-15:10 | 18.12 | 16.87 | 0.464382E+09 | 803.26 | 13-DEC-14:00 | 18.12 | 16.87 |
Annual Sum or Average | 0.609756E+11 | 0.682928E+10 | ||||||||
Minimum of Months | 0.638622E+09 | 2808.25 | 5.40 | 2.35 | 0.444700E+09 | 737.19 | 5.40 | 2.35 | ||
Maximum of Months | 0.100599E+11 | 16382.18 | 33.33 | 23.57 | 0.690095E+09 | 845.63 | 33.33 | 23.57 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.833616E+09 | 2772.50 | 11-JAN-10:15 | 0.93 | -1.3 | 0.222585E+09 | 439.28 | 31-JAN-11:50 | 16.73 | 13.07 |
February | 0.162569E+10 | 4966.52 | 27-FEB-10:00 | 12.80 | 5.65 | 0.216480E+09 | 521.21 | 28-FEB-11:09 | 20.87 | 12.02 |
March | 0.387052E+10 | 6442.37 | 13-MAR-10:20 | 14.23 | 6.73 | 0.289332E+09 | 521.23 | 08-MAR-09:00 | 14.23 | 6.73 |
April | 0.519866E+10 | 18169.77 | 16-APR-10:53 | 26.10 | 15.47 | 0.276400E+09 | 521.24 | 18-APR-14:30 | 26.40 | 16.44 |
May | 0.698407E+10 | 20007.62 | 07-MAY-09:02 | 23.58 | 19.38 | 0.307618E+09 | 521.27 | 11-MAY-10:09 | 17.67 | 13.57 |
June | 0.869086E+10 | 20935.64 | 04-JUN-09:52 | 26.70 | 19.39 | 0.312410E+09 | 521.23 | 09-JUN-10:09 | 24.78 | 15.66 |
July | 0.909329E+10 | 20750.77 | 04-JUL-09:42 | 26.83 | 23.40 | 0.291250E+09 | 521.20 | 20-JUL-10:20 | 28.17 | 22.11 |
August | 0.922299E+10 | 21300.62 | 27-AUG-09:41 | 26.83 | 21.78 | 0.326088E+09 | 521.20 | 18-AUG-12:09 | 26.83 | 21.78 |
September | 0.648218E+10 | 19578.18 | 24-SEP-10:12 | 26.67 | 18.72 | 0.283162E+09 | 521.21 | 15-SEP-10:20 | 26.67 | 18.72 |
October | 0.416065E+10 | 7520.66 | 11-OCT-10:10 | 23.27 | 19.04 | 0.272399E+09 | 521.21 | 05-OCT-10:20 | 23.27 | 19.04 |
November | 0.271517E+10 | 4173.29 | 06-NOV-09:50 | 14.03 | 12.24 | 0.245110E+09 | 521.19 | 06-NOV-09:00 | 14.40 | 12.50 |
December | 0.155409E+10 | 2801.80 | 07-DEC-10:25 | 7.80 | 5.02 | 0.220325E+09 | 470.79 | 07-DEC-09:00 | 7.80 | 5.02 |
Annual Sum or Average | 0.604318E+11 | 0.326316E+10 | ||||||||
Minimum of Months | 0.833616E+09 | 2772.50 | 0.93 | -1.3 | 0.216480E+09 | 439.28 | 7.80 | 5.02 | ||
Maximum of Months | 0.922299E+10 | 21300.62 | 26.83 | 23.40 | 0.326088E+09 | 521.27 | 28.17 | 22.11 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.315108E+10 | 16657.78 | 29-JAN-13:33 | 14.63 | 6.24 | 0.537906E+09 | 858.92 | 27-JAN-10:50 | 14.63 | 6.24 |
February | 0.398775E+10 | 20383.11 | 26-FEB-12:32 | 23.53 | 12.41 | 0.498699E+09 | 859.57 | 21-FEB-14:39 | 23.53 | 12.41 |
March | 0.672763E+10 | 15754.79 | 26-MAR-15:02 | 20.10 | 9.52 | 0.639824E+09 | 845.68 | 08-MAR-10:39 | 20.10 | 9.52 |
April | 0.674507E+10 | 20019.47 | 16-APR-13:32 | 28.70 | 16.13 | 0.585514E+09 | 845.71 | 12-APR-13:50 | 28.70 | 16.13 |
May | 0.783279E+10 | 13733.47 | 29-MAY-14:12 | 28.67 | 20.44 | 0.651506E+09 | 845.64 | 09-MAY-13:09 | 28.67 | 20.44 |
June | 0.954633E+10 | 19529.11 | 25-JUN-16:11 | 33.13 | 22.15 | 0.658887E+09 | 845.65 | 02-JUN-13:09 | 33.13 | 22.15 |
July | 0.101520E+11 | 18774.53 | 16-JUL-12:53 | 32.20 | 24.15 | 0.614597E+09 | 845.61 | 13-JUL-13:09 | 32.20 | 24.15 |
August | 0.121429E+11 | 20200.24 | 27-AUG-13:02 | 31.70 | 22.66 | 0.690963E+09 | 845.61 | 25-AUG-13:09 | 31.70 | 22.66 |
September | 0.949484E+10 | 21219.76 | 24-SEP-12:52 | 28.90 | 19.89 | 0.606465E+09 | 845.64 | 22-SEP-13:39 | 28.90 | 19.89 |
October | 0.844735E+10 | 21657.50 | 08-OCT-14:02 | 26.78 | 18.72 | 0.602662E+09 | 887.71 | 10-OCT-13:50 | 29.22 | 21.00 |
November | 0.628652E+10 | 20724.89 | 11-NOV-12:02 | 19.68 | 11.79 | 0.582840E+09 | 862.66 | 06-NOV-14:09 | 19.68 | 11.79 |
December | 0.470455E+10 | 20524.72 | 10-DEC-13:43 | 16.52 | 7.81 | 0.542971E+09 | 845.82 | 07-DEC-10:50 | 16.52 | 7.81 |
Annual Sum or Average | 0.892188E+11 | 0.721283E+10 | ||||||||
Minimum of Months | 0.315108E+10 | 13733.47 | 14.63 | 6.24 | 0.498699E+09 | 845.61 | 14.63 | 6.24 | ||
Maximum of Months | 0.121429E+11 | 21657.50 | 33.13 | 24.15 | 0.690963E+09 | 887.71 | 33.13 | 24.15 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.115895E+10 | 3098.85 | 10-JAN-17:33 | 3.33 | 1.20 | 0.308768E+09 | 505.17 | 11-JAN-16:49 | 6.28 | 1.74 |
February | 0.197806E+10 | 7654.55 | 27-FEB-17:00 | 22.20 | 11.44 | 0.292068E+09 | 544.93 | 28-FEB-14:39 | 25.00 | 13.71 |
March | 0.462903E+10 | 10689.31 | 30-MAR-16:00 | 27.80 | 17.47 | 0.384182E+09 | 544.93 | 08-MAR-14:00 | 27.80 | 17.47 |
April | 0.572827E+10 | 20108.12 | 09-APR-17:12 | 21.50 | 10.93 | 0.365362E+09 | 544.97 | 12-APR-13:50 | 28.72 | 17.01 |
May | 0.718451E+10 | 21588.44 | 21-MAY-17:22 | 26.15 | 19.60 | 0.414049E+09 | 544.95 | 09-MAY-13:09 | 26.15 | 19.60 |
June | 0.884839E+10 | 22533.81 | 25-JUN-16:11 | 33.13 | 22.15 | 0.423472E+09 | 544.96 | 02-JUN-13:09 | 33.13 | 22.15 |
July | 0.924811E+10 | 22898.99 | 23-JUL-17:11 | 29.63 | 23.03 | 0.395338E+09 | 544.93 | 13-JUL-13:09 | 29.63 | 23.03 |
August | 0.985750E+10 | 22052.04 | 27-AUG-16:21 | 31.40 | 21.35 | 0.444758E+09 | 544.93 | 25-AUG-13:09 | 31.40 | 21.35 |
September | 0.665933E+10 | 18045.08 | 24-SEP-16:52 | 27.80 | 19.57 | 0.383802E+09 | 544.94 | 13-SEP-13:09 | 27.80 | 19.57 |
October | 0.465771E+10 | 15664.16 | 08-OCT-16:42 | 26.78 | 18.71 | 0.361934E+09 | 544.93 | 19-OCT-13:09 | 22.48 | 19.30 |
November | 0.314387E+10 | 7067.99 | 06-NOV-16:00 | 20.60 | 10.48 | 0.335626E+09 | 544.92 | 15-NOV-14:00 | 21.70 | 11.58 |
December | 0.190882E+10 | 3795.86 | 11-DEC-15:50 | 21.10 | 15.67 | 0.308380E+09 | 537.93 | 12-DEC-14:00 | 22.80 | 16.17 |
Annual Sum or Average | 0.650026E+11 | 0.441774E+10 | ||||||||
Minimum of Months | 0.115895E+10 | 3098.85 | 3.33 | 1.20 | 0.292068E+09 | 505.17 | 6.28 | 1.74 | ||
Maximum of Months | 0.985750E+10 | 22898.99 | 33.13 | 23.03 | 0.444758E+09 | 544.97 | 33.13 | 23.03 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.472228E+09 | 2864.31 | 20-JAN-16:20 | 17.03 | 12.34 | 0.468166E+09 | 727.89 | 20-JAN-14:00 | 17.03 | 12.34 |
February | 0.112660E+10 | 3698.96 | 28-FEB-15:30 | 24.15 | 13.12 | 0.437948E+09 | 845.59 | 28-FEB-14:00 | 24.15 | 13.12 |
March | 0.321195E+10 | 7383.83 | 30-MAR-15:50 | 27.80 | 17.41 | 0.570714E+09 | 845.59 | 09-MAR-14:09 | 27.80 | 17.41 |
April | 0.445854E+10 | 7765.51 | 19-APR-14:30 | 26.15 | 17.54 | 0.550478E+09 | 845.60 | 20-APR-13:39 | 23.90 | 16.49 |
May | 0.693803E+10 | 10007.14 | 30-MAY-15:00 | 30.60 | 21.44 | 0.641847E+09 | 845.82 | 16-MAY-13:39 | 30.60 | 21.44 |
June | 0.982576E+10 | 19367.51 | 25-JUN-16:11 | 33.13 | 22.15 | 0.658058E+09 | 845.63 | 02-JUN-13:09 | 33.13 | 22.15 |
July | 0.103297E+11 | 18821.52 | 16-JUL-13:32 | 33.33 | 23.57 | 0.613838E+09 | 845.59 | 03-JUL-13:09 | 33.33 | 23.57 |
August | 0.107696E+11 | 17489.10 | 06-AUG-16:21 | 32.50 | 23.58 | 0.689745E+09 | 845.59 | 25-AUG-13:09 | 30.18 | 18.86 |
September | 0.643153E+10 | 13376.24 | 07-SEP-05:02 | 22.20 | 21.11 | 0.592720E+09 | 845.61 | 13-SEP-13:09 | 23.92 | 15.70 |
October | 0.348337E+10 | 6815.16 | 02-OCT-14:40 | 26.70 | 20.10 | 0.541569E+09 | 845.58 | 19-OCT-13:09 | 22.48 | 19.30 |
November | 0.195490E+10 | 3267.42 | 02-NOV-15:50 | 22.30 | 16.05 | 0.489884E+09 | 828.51 | 03-NOV-13:00 | 21.70 | 17.40 |
December | 0.905896E+09 | 3080.28 | 13-DEC-15:10 | 18.12 | 16.87 | 0.456327E+09 | 790.43 | 13-DEC-14:00 | 18.12 | 16.87 |
Annual Sum or Average | 0.599081E+11 | 0.671130E+10 | ||||||||
Minimum of Months | 0.472228E+09 | 2864.31 | 17.03 | 12.34 | 0.437948E+09 | 727.89 | 17.03 | 12.34 | ||
Maximum of Months | 0.107696E+11 | 19367.51 | 33.33 | 23.58 | 0.689745E+09 | 845.82 | 33.33 | 23.57 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.627989E+09 | 2573.30 | 31-JAN-15:00 | 21.10 | 12.97 | 0.301238E+09 | 454.19 | 31-JAN-14:00 | 21.10 | 12.97 |
February | 0.136844E+10 | 3534.90 | 27-FEB-10:40 | 14.27 | 6.32 | 0.291043E+09 | 544.95 | 28-FEB-10:00 | 20.60 | 11.95 |
March | 0.339962E+10 | 6076.56 | 30-MAR-11:00 | 22.20 | 17.83 | 0.387262E+09 | 544.99 | 08-MAR-10:09 | 22.20 | 17.83 |
April | 0.496646E+10 | 9778.77 | 14-APR-09:50 | 20.82 | 14.67 | 0.373083E+09 | 544.96 | 17-APR-09:09 | 20.47 | 14.59 |
May | 0.714682E+10 | 20211.71 | 07-MAY-09:12 | 23.87 | 19.51 | 0.417511E+09 | 545.12 | 16-MAY-13:39 | 28.30 | 17.68 |
June | 0.918280E+10 | 20031.35 | 25-JUN-08:52 | 26.70 | 22.00 | 0.425215E+09 | 544.97 | 09-JUN-09:00 | 26.70 | 22.00 |
July | 0.970650E+10 | 20519.48 | 23-JUL-08:32 | 25.77 | 22.55 | 0.394715E+09 | 544.93 | 03-JUL-13:09 | 25.77 | 22.55 |
August | 0.986836E+10 | 21239.66 | 27-AUG-09:12 | 25.73 | 21.64 | 0.443958E+09 | 544.93 | 01-AUG-13:09 | 25.73 | 21.64 |
September | 0.652370E+10 | 19734.57 | 04-SEP-09:22 | 25.85 | 21.92 | 0.383438E+09 | 544.95 | 13-SEP-13:09 | 23.92 | 15.70 |
October | 0.368612E+10 | 7336.15 | 11-OCT-10:20 | 23.73 | 19.29 | 0.365810E+09 | 544.94 | 05-OCT-09:00 | 23.73 | 19.29 |
November | 0.211368E+10 | 3026.61 | 06-NOV-10:30 | 15.80 | 12.82 | 0.321415E+09 | 532.69 | 06-NOV-10:39 | 16.27 | 12.91 |
December | 0.111176E+10 | 2736.13 | 13-DEC-15:00 | 18.30 | 16.86 | 0.294541E+09 | 480.10 | 13-DEC-14:00 | 18.30 | 16.86 |
Annual Sum or Average | 0.597022E+11 | 0.439923E+10 | ||||||||
Minimum of Months | 0.627989E+09 | 2573.30 | 14.27 | 6.32 | 0.291043E+09 | 454.19 | 16.27 | 11.95 | ||
Maximum of Months | 0.986836E+10 | 21239.66 | 26.70 | 22.55 | 0.443958E+09 | 545.12 | 28.30 | 22.55 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.268604E+10 | 10410.02 | 11-JAN-14:30 | 6.70 | 2.05 | 0.523901E+09 | 845.63 | 10-JAN-14:09 | 6.70 | 2.05 |
February | 0.340365E+10 | 20795.67 | 26-FEB-14:52 | 25.00 | 12.75 | 0.486554E+09 | 845.65 | 22-FEB-14:09 | 25.00 | 12.75 |
March | 0.593532E+10 | 16303.50 | 30-MAR-13:40 | 27.43 | 17.97 | 0.617276E+09 | 845.66 | 13-MAR-13:00 | 27.43 | 17.97 |
April | 0.652852E+10 | 13433.31 | 17-APR-14:00 | 28.90 | 16.63 | 0.569166E+09 | 845.64 | 07-APR-13:00 | 28.90 | 16.63 |
May | 0.809774E+10 | 19059.69 | 29-MAY-14:12 | 28.67 | 20.44 | 0.641801E+09 | 845.90 | 16-MAY-13:39 | 28.67 | 20.44 |
June | 0.102018E+11 | 22332.85 | 25-JUN-16:11 | 33.13 | 22.15 | 0.655715E+09 | 845.65 | 02-JUN-13:09 | 33.13 | 22.15 |
July | 0.109576E+11 | 21566.38 | 16-JUL-12:53 | 32.20 | 24.15 | 0.613215E+09 | 845.60 | 03-JUL-13:09 | 32.20 | 24.15 |
August | 0.129783E+11 | 22170.38 | 13-AUG-13:32 | 30.40 | 22.46 | 0.690188E+09 | 845.61 | 25-AUG-13:09 | 30.18 | 18.86 |
September | 0.957452E+10 | 21990.46 | 24-SEP-11:43 | 28.22 | 19.73 | 0.598909E+09 | 845.64 | 22-SEP-13:39 | 28.22 | 19.73 |
October | 0.761730E+10 | 23882.86 | 09-OCT-14:12 | 27.40 | 19.48 | 0.585014E+09 | 865.65 | 10-OCT-13:50 | 29.22 | 21.00 |
November | 0.516847E+10 | 22888.93 | 11-NOV-14:52 | 21.10 | 11.84 | 0.556471E+09 | 845.64 | 06-NOV-10:09 | 21.10 | 11.84 |
December | 0.377495E+10 | 12346.79 | 08-DEC-14:10 | 12.80 | 5.52 | 0.523993E+09 | 845.61 | 12-DEC-14:00 | 22.80 | 16.17 |
Annual Sum or Average | 0.869242E+11 | 0.706220E+10 | ||||||||
Minimum of Months | 0.268604E+10 | 10410.02 | 6.70 | 2.05 | 0.486554E+09 | 845.60 | 6.70 | 2.05 | ||
Maximum of Months | 0.129783E+11 | 23882.86 | 33.13 | 24.15 | 0.690188E+09 | 865.65 | 33.13 | 24.15 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.101431E+10 | 3209.56 | 20-JAN-16:40 | 16.87 | 11.91 | 0.305403E+09 | 485.24 | 11-JAN-16:49 | 16.87 | 11.91 |
February | 0.171892E+10 | 7566.54 | 27-FEB-17:00 | 22.20 | 11.44 | 0.287589E+09 | 544.88 | 28-FEB-14:00 | 25.00 | 13.71 |
March | 0.416218E+10 | 11234.20 | 30-MAR-16:00 | 27.80 | 17.47 | 0.372024E+09 | 544.92 | 08-MAR-14:00 | 27.80 | 17.47 |
April | 0.561931E+10 | 19237.61 | 09-APR-16:52 | 21.70 | 10.78 | 0.354123E+09 | 544.94 | 20-APR-13:39 | 23.90 | 16.49 |
May | 0.740119E+10 | 23134.91 | 21-MAY-17:22 | 26.15 | 19.60 | 0.406669E+09 | 545.11 | 16-MAY-13:39 | 26.15 | 19.60 |
June | 0.930550E+10 | 24611.65 | 25-JUN-16:11 | 33.13 | 22.15 | 0.420709E+09 | 544.96 | 02-JUN-13:09 | 33.13 | 22.15 |
July | 0.982973E+10 | 24417.85 | 23-JUL-17:11 | 29.63 | 23.03 | 0.393825E+09 | 544.93 | 03-JUL-13:09 | 29.63 | 23.03 |
August | 0.104395E+11 | 23215.85 | 13-AUG-16:51 | 31.10 | 22.45 | 0.443695E+09 | 544.93 | 25-AUG-13:09 | 30.18 | 18.86 |
September | 0.676243E+10 | 21909.53 | 04-SEP-17:02 | 28.12 | 21.99 | 0.376305E+09 | 544.94 | 13-SEP-13:09 | 23.92 | 15.70 |
October | 0.422383E+10 | 13150.64 | 09-OCT-16:12 | 27.43 | 19.51 | 0.350686E+09 | 544.92 | 19-OCT-13:30 | 23.05 | 19.50 |
November | 0.260413E+10 | 6783.81 | 06-NOV-16:00 | 20.60 | 10.48 | 0.324116E+09 | 544.88 | 06-NOV-14:00 | 20.60 | 10.48 |
December | 0.152072E+10 | 3407.64 | 11-DEC-16:00 | 21.10 | 15.91 | 0.301850E+09 | 525.48 | 12-DEC-14:00 | 22.80 | 16.17 |
Annual Sum or Average | 0.646018E+11 | 0.433699E+10 | ||||||||
Minimum of Months | 0.101431E+10 | 3209.56 | 16.87 | 10.48 | 0.287589E+09 | 485.24 | 16.87 | 10.48 | ||
Maximum of Months | 0.104395E+11 | 24611.65 | 33.13 | 23.03 | 0.443695E+09 | 545.11 | 33.13 | 23.03 |
Report: ZoneCoolingSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.122094E+10 | 6219.40 | 26-JAN-06:01 | -5.0 | -6.9 | 0.00 | 0.00 | 01-JAN-00:10 | -5.0 | -6.9 |
February | 0.202251E+10 | 6470.40 | 03-FEB-06:01 | -8.4 | -9.9 | 0.00 | 0.00 | 01-FEB-00:10 | -8.4 | -9.9 |
March | 0.467701E+10 | 6396.08 | 30-MAR-15:00 | 27.80 | 17.08 | 0.00 | 0.00 | 01-MAR-00:10 | 27.80 | 17.08 |
April | 0.597250E+10 | 8171.25 | 17-APR-15:30 | 28.90 | 16.41 | 0.00 | 0.00 | 01-APR-00:10 | 28.90 | 16.41 |
May | 0.665464E+10 | 10357.53 | 30-MAY-05:03 | 18.68 | 17.36 | 0.00 | 0.00 | 01-MAY-00:10 | 18.68 | 17.36 |
June | 0.873142E+10 | 10971.43 | 19-JUN-05:02 | 21.02 | 20.20 | 0.00 | 0.00 | 01-JUN-00:10 | 21.02 | 20.20 |
July | 0.948721E+10 | 9808.26 | 11-JUL-05:02 | 20.50 | 19.77 | 0.00 | 0.00 | 01-JUL-00:10 | 20.50 | 19.77 |
August | 0.107706E+11 | 9341.17 | 09-AUG-05:02 | 24.40 | 22.06 | 0.00 | 0.00 | 01-AUG-00:10 | 24.40 | 22.06 |
September | 0.723642E+10 | 12621.66 | 05-SEP-05:02 | 21.70 | 20.50 | 0.00 | 0.00 | 01-SEP-00:10 | 21.70 | 20.50 |
October | 0.539197E+10 | 7619.75 | 10-OCT-05:13 | 15.73 | 14.81 | 0.00 | 0.00 | 01-OCT-00:10 | 15.73 | 14.81 |
November | 0.398748E+10 | 5756.34 | 13-NOV-06:08 | 3.80 | 1.16 | 0.00 | 0.00 | 01-NOV-00:10 | 3.80 | 1.16 |
December | 0.263810E+10 | 4734.13 | 14-DEC-06:13 | 6.50 | 5.21 | 0.00 | 0.00 | 01-DEC-00:10 | 6.50 | 5.21 |
Annual Sum or Average | 0.687908E+11 | 0.00 | ||||||||
Minimum of Months | 0.122094E+10 | 4734.13 | -8.4 | -9.9 | 0.00 | 0.00 | -8.4 | -9.9 | ||
Maximum of Months | 0.107706E+11 | 12621.66 | 28.90 | 22.06 | 0.00 | 0.00 | 28.90 | 22.06 |
Report: ZoneCoolingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.490329E+09 | 7752.41 | 14-JAN-04:01 | -6.1 | -7.2 | 0.00 | 0.00 | 01-JAN-00:10 | -6.1 | -7.2 |
February | 0.927602E+09 | 10065.98 | 12-FEB-06:01 | -12.3 | -13.5 | 0.00 | 0.00 | 01-FEB-00:10 | -12.3 | -13.5 |
March | 0.245693E+10 | 5778.49 | 18-MAR-05:02 | 3.22 | 0.02 | 0.00 | 0.00 | 01-MAR-00:10 | 3.22 | 0.02 |
April | 0.364388E+10 | 6755.79 | 06-APR-05:03 | 0.18 | -0.9 | 0.00 | 0.00 | 01-APR-00:10 | 0.18 | -0.9 |
May | 0.506693E+10 | 5712.45 | 19-MAY-05:13 | 16.50 | 15.56 | 0.00 | 0.00 | 01-MAY-00:10 | 16.50 | 15.56 |
June | 0.693328E+10 | 6550.65 | 29-JUN-16:00 | 31.10 | 23.22 | 0.00 | 0.00 | 01-JUN-00:10 | 31.10 | 23.22 |
July | 0.750615E+10 | 9678.85 | 06-JUL-05:02 | 22.80 | 21.19 | 0.00 | 0.00 | 01-JUL-00:10 | 22.80 | 21.19 |
August | 0.811433E+10 | 10025.13 | 21-AUG-05:02 | 21.78 | 21.78 | 0.00 | 0.00 | 01-AUG-00:10 | 21.78 | 21.78 |
September | 0.568353E+10 | 6588.09 | 07-SEP-15:40 | 31.70 | 23.45 | 0.00 | 0.00 | 01-SEP-00:10 | 31.70 | 23.45 |
October | 0.325261E+10 | 5286.34 | 13-OCT-05:10 | 6.02 | 4.50 | 0.00 | 0.00 | 01-OCT-00:10 | 6.02 | 4.50 |
November | 0.172116E+10 | 8582.94 | 22-NOV-05:01 | -2.9 | -3.8 | 0.00 | 0.00 | 01-NOV-00:10 | -2.9 | -3.8 |
December | 0.895925E+09 | 8534.89 | 01-DEC-05:01 | -3.0 | -4.3 | 0.00 | 0.00 | 01-DEC-00:10 | -3.0 | -4.3 |
Annual Sum or Average | 0.466926E+11 | 0.00 | ||||||||
Minimum of Months | 0.490329E+09 | 5286.34 | -12.3 | -13.5 | 0.00 | 0.00 | -12.3 | -13.5 | ||
Maximum of Months | 0.811433E+10 | 10065.98 | 31.70 | 23.45 | 0.00 | 0.00 | 31.70 | 23.45 |
Report: ZoneCoolingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.177427E+09 | 2551.06 | 31-JAN-13:10 | 19.60 | 13.60 | 0.00 | 0.00 | 01-JAN-00:10 | 19.60 | 13.60 |
February | 0.844029E+09 | 6092.74 | 28-FEB-16:10 | 23.40 | 12.60 | 0.00 | 0.00 | 01-FEB-00:10 | 23.40 | 12.60 |
March | 0.303291E+10 | 13188.41 | 30-MAR-14:20 | 27.80 | 17.60 | 0.00 | 0.00 | 01-MAR-00:10 | 27.80 | 17.60 |
April | 0.553827E+10 | 16036.76 | 17-APR-14:40 | 28.90 | 16.48 | 0.00 | 0.00 | 01-APR-00:10 | 28.90 | 16.48 |
May | 0.890763E+10 | 17025.88 | 16-MAY-15:40 | 29.40 | 17.64 | 0.00 | 0.00 | 01-MAY-00:10 | 29.40 | 17.64 |
June | 0.124964E+11 | 17712.03 | 13-JUN-13:50 | 33.80 | 22.33 | 0.00 | 0.00 | 01-JUN-00:10 | 33.80 | 22.33 |
July | 0.132552E+11 | 19740.61 | 07-JUL-15:10 | 35.10 | 23.86 | 0.00 | 0.00 | 01-JUL-00:10 | 35.10 | 23.86 |
August | 0.138933E+11 | 19476.71 | 01-AUG-14:00 | 33.90 | 23.66 | 0.00 | 0.00 | 01-AUG-00:10 | 33.90 | 23.66 |
September | 0.774338E+10 | 16381.49 | 06-SEP-14:00 | 31.10 | 23.78 | 0.00 | 0.00 | 01-SEP-00:10 | 31.10 | 23.78 |
October | 0.369162E+10 | 12040.27 | 10-OCT-14:40 | 29.07 | 20.78 | 0.00 | 0.00 | 01-OCT-00:10 | 29.07 | 20.78 |
November | 0.129696E+10 | 5430.44 | 05-NOV-14:10 | 23.40 | 18.52 | 0.00 | 0.00 | 01-NOV-00:10 | 23.40 | 18.52 |
December | 0.351812E+09 | 3283.85 | 12-DEC-13:10 | 21.38 | 16.69 | 0.00 | 0.00 | 01-DEC-00:10 | 21.38 | 16.69 |
Annual Sum or Average | 0.712289E+11 | 0.00 | ||||||||
Minimum of Months | 0.177427E+09 | 2551.06 | 19.60 | 12.60 | 0.00 | 0.00 | 19.60 | 12.60 | ||
Maximum of Months | 0.138933E+11 | 19740.61 | 35.10 | 23.86 | 0.00 | 0.00 | 35.10 | 23.86 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.268804E+10 | 1910.36 | 23-JAN-17:00 | 10.00 | 3.54 | 95230840.26 | 126.84 | 19-JAN-10:30 | 10.00 | 3.54 |
February | 0.760594E+10 | 4019.05 | 24-FEB-17:50 | 15.18 | 6.70 | 86397279.15 | 126.84 | 17-FEB-14:00 | 15.18 | 6.70 |
March | 0.143887E+11 | 7150.58 | 31-MAR-24:00 | 12.10 | 7.93 | 0.103239E+09 | 126.84 | 28-MAR-09:09 | 12.10 | 7.93 |
April | 0.190008E+11 | 7933.39 | 09-APR-18:15 | 19.80 | 10.92 | 91606013.01 | 126.83 | 03-APR-09:39 | 19.80 | 10.92 |
May | 0.455130E+10 | 3485.90 | 31-MAY-24:00 | 21.00 | 18.72 | 99243266.80 | 126.86 | 23-MAY-13:30 | 21.00 | 18.72 |
June | 0.946048E+10 | 5395.09 | 30-JUN-24:00 | 22.30 | 21.46 | 98973899.05 | 126.86 | 23-JUN-09:09 | 22.30 | 21.46 |
July | 0.148075E+11 | 7228.22 | 31-JUL-24:00 | 25.20 | 21.98 | 91891347.74 | 126.85 | 26-JUL-09:09 | 25.20 | 21.98 |
August | 0.198849E+11 | 7907.71 | 13-AUG-19:23 | 29.70 | 21.78 | 0.104647E+09 | 134.75 | 02-AUG-13:00 | 29.70 | 21.78 |
September | 0.450462E+10 | 3184.82 | 30-SEP-24:00 | 16.80 | 15.75 | 91612531.98 | 126.86 | 01-SEP-13:20 | 16.80 | 15.75 |
October | 0.942464E+10 | 5103.99 | 31-OCT-24:00 | 9.70 | 6.26 | 95238265.13 | 126.87 | 19-OCT-09:30 | 9.70 | 6.26 |
November | 0.138387E+11 | 6014.36 | 06-NOV-17:00 | 18.90 | 9.61 | 94301942.12 | 126.84 | 02-NOV-09:20 | 18.90 | 9.61 |
December | 0.190024E+11 | 7807.88 | 19-DEC-17:00 | 13.90 | 5.19 | 91881254.02 | 126.83 | 06-DEC-14:00 | 13.90 | 5.19 |
Annual Sum or Average | 0.139158E+12 | 0.114426E+10 | ||||||||
Minimum of Months | 0.268804E+10 | 1910.36 | 9.70 | 3.54 | 86397279.15 | 126.83 | 9.70 | 3.54 | ||
Maximum of Months | 0.198849E+11 | 7933.39 | 29.70 | 21.98 | 0.104647E+09 | 134.75 | 29.70 | 21.98 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.670383E+09 | 1529.00 | 27-JAN-17:00 | 4.40 | -1.6 | 94702393.55 | 126.83 | 20-JAN-14:00 | 4.40 | -1.6 |
February | 0.536324E+10 | 3714.21 | 24-FEB-17:50 | 15.18 | 6.70 | 86397213.78 | 126.84 | 17-FEB-14:00 | 15.18 | 6.70 |
March | 0.126524E+11 | 6627.55 | 31-MAR-23:50 | 12.13 | 7.92 | 0.103239E+09 | 126.84 | 31-MAR-13:09 | 12.13 | 7.92 |
April | 0.175636E+11 | 7466.89 | 14-APR-18:30 | 23.35 | 14.91 | 91606202.75 | 126.83 | 03-APR-09:39 | 23.35 | 14.91 |
May | 0.392568E+10 | 3251.71 | 31-MAY-24:00 | 21.00 | 18.72 | 99238505.77 | 126.85 | 30-MAY-13:00 | 21.00 | 18.72 |
June | 0.884227E+10 | 5116.08 | 30-JUN-24:00 | 22.30 | 21.46 | 98974539.05 | 126.86 | 16-JUN-13:00 | 22.30 | 21.46 |
July | 0.140448E+11 | 6975.71 | 31-JUL-24:00 | 25.20 | 21.98 | 91892599.41 | 126.85 | 26-JUL-09:09 | 25.20 | 21.98 |
August | 0.188962E+11 | 7433.26 | 13-AUG-18:37 | 30.37 | 21.91 | 0.104551E+09 | 135.08 | 02-AUG-13:00 | 30.37 | 21.91 |
September | 0.384194E+10 | 2580.47 | 30-SEP-24:00 | 16.80 | 15.75 | 91609156.94 | 126.84 | 18-SEP-13:00 | 16.80 | 15.75 |
October | 0.795361E+10 | 4300.80 | 31-OCT-23:50 | 9.68 | 6.17 | 95237624.69 | 126.86 | 18-OCT-13:39 | 9.68 | 6.17 |
November | 0.117044E+11 | 5573.89 | 06-NOV-17:00 | 18.90 | 9.61 | 94301891.07 | 126.83 | 03-NOV-13:00 | 18.90 | 9.61 |
December | 0.157654E+11 | 7147.65 | 08-DEC-17:00 | 11.10 | 4.72 | 91881377.31 | 126.83 | 13-DEC-14:20 | 18.30 | 16.86 |
Annual Sum or Average | 0.121224E+12 | 0.114363E+10 | ||||||||
Minimum of Months | 0.670383E+09 | 1529.00 | 4.40 | -1.6 | 86397213.78 | 126.83 | 4.40 | -1.6 | ||
Maximum of Months | 0.188962E+11 | 7466.89 | 30.37 | 21.98 | 0.104551E+09 | 135.08 | 30.37 | 21.98 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.377397E+09 | 1506.78 | 20-JAN-17:00 | 16.70 | 11.48 | 92126198.28 | 127.94 | 18-JAN-10:30 | 16.70 | 11.48 |
February | 0.436029E+10 | 3666.30 | 28-FEB-17:00 | 23.90 | 12.94 | 86392106.47 | 126.84 | 17-FEB-14:00 | 23.90 | 12.94 |
March | 0.118314E+11 | 6362.44 | 31-MAR-23:20 | 12.23 | 7.91 | 0.103239E+09 | 126.84 | 31-MAR-13:09 | 12.23 | 7.91 |
April | 0.171141E+11 | 7550.07 | 14-APR-18:30 | 23.35 | 14.91 | 91606351.10 | 126.83 | 04-APR-09:50 | 23.35 | 14.91 |
May | 0.380841E+10 | 3207.37 | 31-MAY-24:00 | 21.00 | 18.72 | 99239872.54 | 126.86 | 30-MAY-13:09 | 21.00 | 18.72 |
June | 0.887647E+10 | 5077.78 | 30-JUN-24:00 | 22.30 | 21.46 | 98974424.49 | 126.86 | 26-JUN-09:00 | 22.30 | 21.46 |
July | 0.141226E+11 | 7019.30 | 31-JUL-24:00 | 25.20 | 21.98 | 91892388.71 | 126.85 | 26-JUL-09:09 | 25.20 | 21.98 |
August | 0.189944E+11 | 7660.98 | 13-AUG-18:52 | 30.00 | 21.93 | 0.104197E+09 | 133.68 | 02-AUG-13:00 | 30.00 | 21.93 |
September | 0.364741E+10 | 2084.04 | 08-SEP-18:10 | 28.80 | 21.95 | 91609261.08 | 126.84 | 18-SEP-13:00 | 25.00 | 18.13 |
October | 0.716882E+10 | 3849.39 | 11-OCT-17:30 | 23.30 | 13.67 | 95237698.24 | 126.86 | 18-OCT-13:00 | 25.00 | 22.63 |
November | 0.104721E+11 | 5559.44 | 06-NOV-17:00 | 18.90 | 9.61 | 94301931.13 | 126.83 | 27-NOV-14:00 | 22.20 | 17.55 |
December | 0.141624E+11 | 7039.49 | 07-DEC-17:00 | 14.40 | 6.55 | 91881445.73 | 126.83 | 13-DEC-14:30 | 18.30 | 16.86 |
Annual Sum or Average | 0.114936E+12 | 0.114070E+10 | ||||||||
Minimum of Months | 0.377397E+09 | 1506.78 | 12.23 | 6.55 | 86392106.47 | 126.83 | 12.23 | 7.91 | ||
Maximum of Months | 0.189944E+11 | 7660.98 | 30.00 | 21.98 | 0.104197E+09 | 133.68 | 30.00 | 22.63 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.235546E+12 | 91720.11 | 20-JAN-17:00 | 16.70 | 11.48 | 0.206171E+10 | 2747.21 | 12-JAN-10:00 | 16.70 | 11.48 |
February | 0.433150E+12 | 183494.40 | 28-FEB-17:00 | 23.90 | 12.94 | 0.187075E+10 | 2748.92 | 09-FEB-14:50 | 23.90 | 12.94 |
March | 0.726919E+12 | 358109.53 | 31-MAR-24:00 | 12.10 | 7.93 | 0.223509E+10 | 2747.33 | 20-MAR-13:09 | 12.10 | 7.93 |
April | 0.938907E+12 | 366259.93 | 20-APR-15:30 | 24.15 | 16.80 | 0.200651E+10 | 3009.21 | 12-APR-13:00 | 24.15 | 16.80 |
May | 0.239456E+12 | 175353.30 | 31-MAY-24:00 | 21.00 | 18.72 | 0.214857E+10 | 2746.54 | 25-MAY-13:00 | 21.00 | 18.72 |
June | 0.469880E+12 | 267496.00 | 30-JUN-24:00 | 22.30 | 21.46 | 0.214257E+10 | 2746.33 | 26-JUN-09:00 | 22.30 | 21.46 |
July | 0.731540E+12 | 359653.72 | 31-JUL-24:00 | 25.20 | 21.98 | 0.198919E+10 | 2745.89 | 26-JUL-09:09 | 25.20 | 21.98 |
August | 0.972908E+12 | 370531.17 | 07-AUG-21:14 | 22.60 | 21.54 | 0.254439E+10 | 3589.41 | 18-AUG-13:50 | 33.48 | 22.91 |
September | 0.237060E+12 | 175462.04 | 30-SEP-24:00 | 16.80 | 15.75 | 0.198355E+10 | 2746.98 | 28-SEP-13:00 | 16.80 | 15.75 |
October | 0.488154E+12 | 268176.51 | 31-OCT-24:00 | 9.70 | 6.26 | 0.206165E+10 | 2746.38 | 18-OCT-13:30 | 9.70 | 6.26 |
November | 0.709197E+12 | 277506.15 | 06-NOV-17:00 | 18.90 | 9.61 | 0.204176E+10 | 2747.81 | 22-NOV-14:09 | 11.28 | 3.90 |
December | 0.975361E+12 | 368470.04 | 13-DEC-17:00 | 16.70 | 16.70 | 0.198969E+10 | 2748.60 | 18-DEC-14:09 | 8.17 | 1.58 |
Annual Sum or Average | 0.715808E+13 | 0.250754E+11 | ||||||||
Minimum of Months | 0.235546E+12 | 91720.11 | 9.70 | 6.26 | 0.187075E+10 | 2745.89 | 8.17 | 1.58 | ||
Maximum of Months | 0.975361E+12 | 370531.17 | 25.20 | 21.98 | 0.254439E+10 | 3589.41 | 33.48 | 22.91 |
Report: ZoneHeatingSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.290766E+09 | 12674.25 | 20-JAN-05:25 | 12.80 |
February | 76328087.12 | 12672.94 | 23-FEB-05:15 | 5.93 |
March | 0.158861E+09 | 12636.24 | 15-MAR-04:15 | 8.30 |
April | 0.196656E+09 | 14548.07 | 15-APR-16:01 | 28.03 |
May | 0.282416E+09 | 16582.11 | 06-MAY-16:02 | 29.63 |
June | 0.261027E+09 | 21384.94 | 24-JUN-16:02 | 33.22 |
July | 0.402494E+09 | 25904.35 | 08-JUL-16:01 | 36.32 |
August | 0.435839E+09 | 20075.18 | 19-AUG-16:02 | 32.33 |
September | 0.383820E+09 | 15096.81 | 23-SEP-16:02 | 28.72 |
October | 0.347170E+09 | 14424.50 | 09-OCT-13:32 | 26.83 |
November | 0.340944E+09 | 14253.19 | 12-NOV-12:52 | 17.80 |
December | 0.139494E+09 | 12173.40 | 20-DEC-05:54 | 2.80 |
Annual Sum or Average | 0.331582E+10 | |||
Minimum of Months | 76328087.12 | 12173.40 | 2.80 | |
Maximum of Months | 0.435839E+09 | 25904.35 | 36.32 |
Report: ZoneHeatingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 5.70 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 9.92 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 15.32 |
April | 0.00 | 0.00 | 01-APR-00:10 | 12.05 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 16.68 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 20.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.28 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 21.40 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 16.85 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 9.70 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 1.80 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 1.80 | |
Maximum of Months | 0.00 | 0.00 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.233660E+09 | 37843.55 | 09-JAN-05:01 | -2.2 |
February | 0.141128E+09 | 36291.13 | 13-FEB-05:11 | -5.2 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 15.32 |
April | 0.00 | 0.00 | 01-APR-00:10 | 12.05 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 16.68 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 20.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.28 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 21.40 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 16.85 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 9.70 |
December | 3866396.02 | 29243.13 | 26-DEC-06:02 | 3.30 |
Annual Sum or Average | 0.378654E+09 | |||
Minimum of Months | 0.00 | 0.00 | -5.2 | |
Maximum of Months | 0.233660E+09 | 37843.55 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.395113E+10 | 80513.12 | 09-JAN-04:11 | -1.9 |
February | 0.183126E+10 | 80372.51 | 13-FEB-04:01 | -5.0 |
March | 25268174.43 | 64067.29 | 20-MAR-05:03 | 5.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 12.05 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 16.68 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 20.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.28 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 21.40 |
October | 22825175.75 | 64135.61 | 30-OCT-05:03 | 8.90 |
November | 0.164454E+09 | 66662.47 | 22-NOV-05:01 | -2.9 |
December | 0.195390E+10 | 78823.10 | 04-DEC-04:01 | -2.3 |
Annual Sum or Average | 0.794883E+10 | |||
Minimum of Months | 0.00 | 0.00 | -5.0 | |
Maximum of Months | 0.395113E+10 | 80513.12 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.382286E+09 | 12352.16 | 09-JAN-05:01 | -2.2 |
February | 0.147025E+09 | 12406.30 | 13-FEB-05:01 | -5.1 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 15.32 |
April | 0.00 | 0.00 | 01-APR-00:10 | 12.05 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 16.68 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 20.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.28 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 21.40 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 16.85 |
November | 4892765.45 | 9661.71 | 22-NOV-06:03 | -3.3 |
December | 15870535.51 | 11471.57 | 18-DEC-06:01 | -5.0 |
Annual Sum or Average | 0.550075E+09 | |||
Minimum of Months | 0.00 | 0.00 | -5.1 | |
Maximum of Months | 0.382286E+09 | 12406.30 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.258112E+09 | 9609.98 | 09-JAN-05:01 | -2.2 |
February | 93308130.06 | 9587.41 | 13-FEB-05:01 | -5.1 |
March | 30105.67 | 250.88 | 23-MAR-05:06 | 6.10 |
April | 0.00 | 0.00 | 01-APR-00:10 | 12.05 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 16.68 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 20.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.28 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 21.40 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 16.85 |
November | 6661116.87 | 8469.88 | 21-NOV-06:01 | -2.8 |
December | 26154761.60 | 8752.38 | 18-DEC-06:01 | -5.0 |
Annual Sum or Average | 0.384266E+09 | |||
Minimum of Months | 0.00 | 0.00 | -5.1 | |
Maximum of Months | 0.258112E+09 | 9609.98 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.443545E+09 | 15051.90 | 09-JAN-04:17 | -1.9 |
February | 0.174431E+09 | 14392.46 | 13-FEB-05:01 | -5.1 |
March | 6546.26 | 54.55 | 23-MAR-05:06 | 6.10 |
April | 0.00 | 0.00 | 01-APR-00:10 | 12.05 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 16.68 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 20.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.28 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 21.40 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 16.85 |
November | 12122811.15 | 12979.65 | 21-NOV-06:01 | -2.8 |
December | 53413591.95 | 13308.13 | 18-DEC-06:01 | -5.0 |
Annual Sum or Average | 0.683519E+09 | |||
Minimum of Months | 0.00 | 0.00 | -5.1 | |
Maximum of Months | 0.443545E+09 | 15051.90 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 48157805.05 | 6766.48 | 09-JAN-05:01 | -2.2 |
February | 7067877.89 | 6169.60 | 13-FEB-06:01 | -5.6 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 15.32 |
April | 0.00 | 0.00 | 01-APR-00:10 | 12.05 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 16.68 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 20.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.28 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 21.40 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 16.85 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 9.70 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 1.80 |
Annual Sum or Average | 55225682.94 | |||
Minimum of Months | 0.00 | 0.00 | -5.6 | |
Maximum of Months | 48157805.05 | 6766.48 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.387035E+10 | 14702.25 | 09-JAN-04:11 | -1.9 |
February | 0.220885E+10 | 15008.71 | 12-FEB-06:01 | -12.3 |
March | 0.155565E+09 | 12307.16 | 22-MAR-04:11 | 6.50 |
April | 35157692.42 | 11521.66 | 07-APR-05:02 | 3.22 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 16.68 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 20.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.28 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 21.40 |
October | 41774021.27 | 12142.07 | 26-OCT-04:11 | 2.60 |
November | 0.416088E+09 | 13171.01 | 21-NOV-05:01 | -2.3 |
December | 0.156305E+10 | 14379.15 | 18-DEC-04:01 | -4.1 |
Annual Sum or Average | 0.829083E+10 | |||
Minimum of Months | 0.00 | 0.00 | -12.3 | |
Maximum of Months | 0.387035E+10 | 15008.71 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.209554E+10 | 15468.92 | 09-JAN-04:11 | -1.9 |
February | 0.113367E+10 | 15805.76 | 12-FEB-06:01 | -12.3 |
March | 79077133.15 | 12844.23 | 22-MAR-04:11 | 6.50 |
April | 14766246.24 | 8958.08 | 06-APR-05:03 | 0.18 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 16.68 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 20.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.28 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 21.40 |
October | 29378820.60 | 12540.09 | 26-OCT-04:11 | 2.60 |
November | 0.189605E+09 | 13718.57 | 21-NOV-05:01 | -2.3 |
December | 0.772670E+09 | 14838.18 | 18-DEC-04:01 | -4.1 |
Annual Sum or Average | 0.431471E+10 | |||
Minimum of Months | 0.00 | 0.00 | -12.3 | |
Maximum of Months | 0.209554E+10 | 15805.76 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.201922E+10 | 17242.35 | 09-JAN-04:11 | -1.9 |
February | 0.108971E+10 | 17545.08 | 12-FEB-06:01 | -12.3 |
March | 64032674.75 | 14384.78 | 22-MAR-04:11 | 6.50 |
April | 17671139.75 | 13377.88 | 06-APR-05:03 | 0.18 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 16.68 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 20.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.28 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 21.40 |
October | 24189368.68 | 13011.09 | 26-OCT-05:03 | 2.20 |
November | 0.150938E+09 | 15206.17 | 21-NOV-05:01 | -2.3 |
December | 0.711073E+09 | 16422.15 | 26-DEC-05:11 | 3.70 |
Annual Sum or Average | 0.407684E+10 | |||
Minimum of Months | 0.00 | 0.00 | -12.3 | |
Maximum of Months | 0.201922E+10 | 17545.08 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.162149E+10 | 15515.32 | 09-JAN-04:11 | -1.9 |
February | 0.845812E+09 | 15803.06 | 12-FEB-06:01 | -12.3 |
March | 33910279.57 | 12511.53 | 22-MAR-04:11 | 6.50 |
April | 6059584.44 | 8398.71 | 06-APR-05:03 | 0.18 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 16.68 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 20.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.28 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 21.40 |
October | 12620500.97 | 8538.35 | 26-OCT-05:03 | 2.20 |
November | 0.150554E+09 | 13613.57 | 21-NOV-05:01 | -2.3 |
December | 0.582843E+09 | 14366.53 | 18-DEC-04:01 | -4.1 |
Annual Sum or Average | 0.325329E+10 | |||
Minimum of Months | 0.00 | 0.00 | -12.3 | |
Maximum of Months | 0.162149E+10 | 15803.06 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.769809E+10 | 17010.98 | 09-JAN-00:53 | -0.6 |
February | 0.447614E+10 | 17449.59 | 12-FEB-00:02 | -9.5 |
March | 0.752740E+09 | 15040.51 | 20-MAR-04:11 | 6.13 |
April | 0.210769E+09 | 14667.46 | 06-APR-04:01 | 0.92 |
May | 2789552.07 | 8432.97 | 11-MAY-05:02 | 8.22 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 20.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.28 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 21.40 |
October | 0.349743E+09 | 14958.68 | 26-OCT-04:11 | 2.60 |
November | 0.152036E+10 | 16195.55 | 21-NOV-04:01 | -1.8 |
December | 0.437222E+10 | 16957.74 | 17-DEC-08:62 | -2.1 |
Annual Sum or Average | 0.193828E+11 | |||
Minimum of Months | 0.00 | 0.00 | -9.5 | |
Maximum of Months | 0.769809E+10 | 17449.59 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.411756E+10 | 17120.37 | 09-JAN-04:11 | -1.9 |
February | 0.232788E+10 | 17540.01 | 12-FEB-06:01 | -12.3 |
March | 0.361293E+09 | 15145.34 | 22-MAR-04:11 | 6.50 |
April | 90010849.41 | 14642.04 | 06-APR-04:01 | 0.92 |
May | 1082154.92 | 3707.65 | 11-MAY-05:02 | 8.22 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 20.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.28 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 25.13 |
September | 91477.45 | 762.31 | 29-SEP-05:02 | 12.30 |
October | 0.199540E+09 | 15054.92 | 26-OCT-04:11 | 2.60 |
November | 0.710441E+09 | 16285.01 | 21-NOV-04:01 | -1.8 |
December | 0.218384E+10 | 16872.46 | 18-DEC-04:01 | -4.1 |
Annual Sum or Average | 0.999173E+10 | |||
Minimum of Months | 0.00 | 0.00 | -12.3 | |
Maximum of Months | 0.411756E+10 | 17540.01 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.452307E+10 | 19453.44 | 09-JAN-04:11 | -1.9 |
February | 0.262906E+10 | 19885.85 | 12-FEB-06:01 | -12.3 |
March | 0.431800E+09 | 17036.22 | 22-MAR-04:11 | 6.50 |
April | 0.147455E+09 | 16471.10 | 06-APR-04:01 | 0.92 |
May | 866725.27 | 3754.40 | 11-MAY-05:02 | 8.22 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 20.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.28 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 21.40 |
October | 0.212399E+09 | 16546.75 | 30-OCT-04:11 | 8.90 |
November | 0.751469E+09 | 18350.19 | 21-NOV-04:01 | -1.8 |
December | 0.228406E+10 | 19068.31 | 26-DEC-05:11 | 3.70 |
Annual Sum or Average | 0.109802E+11 | |||
Minimum of Months | 0.00 | 0.00 | -12.3 | |
Maximum of Months | 0.452307E+10 | 19885.85 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.355444E+10 | 18596.86 | 09-JAN-04:11 | -1.9 |
February | 0.188030E+10 | 18938.02 | 12-FEB-06:01 | -12.3 |
March | 0.224976E+09 | 15919.90 | 22-MAR-04:11 | 6.50 |
April | 64634545.69 | 15382.49 | 06-APR-04:01 | 0.92 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 16.68 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 20.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.28 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 25.13 |
September | 8368.66 | 69.74 | 29-SEP-05:04 | 12.30 |
October | 0.106415E+09 | 15615.87 | 26-OCT-04:11 | 2.60 |
November | 0.596058E+09 | 17513.42 | 22-NOV-04:11 | -2.8 |
December | 0.167740E+10 | 18188.24 | 18-DEC-04:01 | -4.1 |
Annual Sum or Average | 0.810423E+10 | |||
Minimum of Months | 0.00 | 0.00 | -12.3 | |
Maximum of Months | 0.355444E+10 | 18938.02 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.359083E+09 | 10879.37 | 19-JAN-06:02 | 12.30 |
February | 0.243663E+09 | 11522.57 | 08-FEB-06:02 | 7.38 |
March | 68523440.76 | 10910.95 | 22-MAR-04:11 | 6.50 |
April | 74348451.47 | 10215.66 | 04-APR-04:12 | 15.60 |
May | 37679064.37 | 9364.57 | 01-MAY-04:12 | 16.10 |
June | 45672135.53 | 7329.53 | 16-JUN-04:11 | 20.60 |
July | 53219837.64 | 8391.96 | 28-JUL-04:11 | 19.40 |
August | 42288011.00 | 7218.34 | 06-AUG-16:21 | 32.50 |
September | 38653522.34 | 8158.97 | 01-SEP-04:11 | 20.93 |
October | 67179024.45 | 10361.26 | 02-OCT-04:12 | 18.70 |
November | 75688621.38 | 11913.11 | 24-NOV-05:11 | 8.90 |
December | 71731238.02 | 14265.09 | 26-DEC-05:11 | 3.70 |
Annual Sum or Average | 0.117773E+10 | |||
Minimum of Months | 37679064.37 | 7218.34 | 3.70 | |
Maximum of Months | 0.359083E+09 | 14265.09 | 32.50 |
Report: ZoneHeatingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.243694E+10 | 14037.60 | 06-JAN-12:00 | -2.2 |
February | 0.125885E+10 | 10087.43 | 13-FEB-06:07 | -5.6 |
March | 0.117278E+09 | 6751.98 | 28-MAR-05:03 | 16.02 |
April | 29204226.44 | 7313.52 | 03-APR-05:02 | 17.75 |
May | 30629161.43 | 5343.29 | 15-MAY-05:02 | 12.30 |
June | 24678377.65 | 6156.10 | 25-JUN-16:11 | 33.13 |
July | 30684512.61 | 5247.85 | 31-JUL-04:11 | 20.93 |
August | 29374800.90 | 5250.51 | 06-AUG-16:21 | 32.50 |
September | 26520228.93 | 5593.79 | 27-SEP-04:11 | 22.80 |
October | 70043621.94 | 6776.48 | 24-OCT-05:02 | 11.02 |
November | 0.183354E+09 | 7033.66 | 02-NOV-05:02 | 13.90 |
December | 0.963146E+09 | 5829.91 | 10-DEC-13:43 | 16.52 |
Annual Sum or Average | 0.520070E+10 | |||
Minimum of Months | 24678377.65 | 5247.85 | -5.6 | |
Maximum of Months | 0.243694E+10 | 14037.60 | 33.13 |
Report: ZoneHeatingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.877517E+10 | 25122.57 | 09-JAN-05:09 | -2.2 |
February | 0.518052E+10 | 26966.89 | 13-FEB-05:09 | -5.1 |
March | 0.136885E+10 | 11891.68 | 31-MAR-05:02 | 16.78 |
April | 0.625163E+09 | 14383.00 | 14-APR-05:03 | 12.62 |
May | 0.150173E+09 | 13309.49 | 15-MAY-05:02 | 12.30 |
June | 68246777.31 | 15614.32 | 08-JUN-05:03 | 11.70 |
July | 38149936.84 | 10446.65 | 05-JUL-04:12 | 22.03 |
August | 36381133.85 | 9157.67 | 28-AUG-04:12 | 21.30 |
September | 0.121046E+09 | 14699.36 | 14-SEP-05:03 | 12.20 |
October | 0.985293E+09 | 14675.51 | 03-OCT-05:03 | 11.60 |
November | 0.219461E+10 | 16999.57 | 22-NOV-06:03 | -3.3 |
December | 0.518242E+10 | 25485.72 | 18-DEC-05:33 | -5.0 |
Annual Sum or Average | 0.247260E+11 | |||
Minimum of Months | 36381133.85 | 9157.67 | -5.1 | |
Maximum of Months | 0.877517E+10 | 26966.89 | 22.03 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 5.70 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 9.92 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 15.32 |
April | 0.00 | 0.00 | 01-APR-00:10 | 12.05 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 16.68 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 20.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.28 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 21.40 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 16.85 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 9.70 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 1.80 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 1.80 | |
Maximum of Months | 0.00 | 0.00 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.416005E+09 | 547.37 | 16-JAN-03:20 | -1.7 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 9.92 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 15.32 |
April | 0.00 | 0.00 | 01-APR-00:10 | 12.05 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 16.68 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 20.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.28 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 21.40 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 16.85 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 9.70 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 1.80 |
Annual Sum or Average | 0.416005E+09 | |||
Minimum of Months | 0.00 | 0.00 | -1.7 | |
Maximum of Months | 0.416005E+09 | 547.37 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.697636E+09 | 601.45 | 15-JAN-18:45 | 4.18 |
February | 67707861.03 | 548.27 | 12-FEB-07:45 | -12.3 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 15.32 |
April | 0.00 | 0.00 | 01-APR-00:10 | 12.05 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 16.68 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 20.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.28 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 21.40 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 16.85 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 9.70 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 1.80 |
Annual Sum or Average | 0.765344E+09 | |||
Minimum of Months | 0.00 | 0.00 | -12.3 | |
Maximum of Months | 0.697636E+09 | 601.45 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 5.70 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 9.92 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 15.32 |
April | 0.00 | 0.00 | 01-APR-00:10 | 12.05 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 16.68 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 20.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.28 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 21.40 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 16.85 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 9.70 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 1.80 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 1.80 | |
Maximum of Months | 0.00 | 0.00 | 25.13 |
Report: ZoneElectricSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.219312E+11 | 22950.34 | 02-JAN-08:09 | 0.360447E+11 | 13457.54 | 01-JAN-00:10 |
February | 0.198933E+11 | 22950.34 | 01-FEB-08:09 | 0.325565E+11 | 13457.54 | 01-FEB-00:10 |
March | 0.236388E+11 | 22950.34 | 01-MAR-08:09 | 0.360447E+11 | 13457.54 | 01-MAR-00:10 |
April | 0.211142E+11 | 22950.34 | 03-APR-07:10 | 0.348820E+11 | 13457.54 | 01-APR-00:10 |
May | 0.227850E+11 | 22950.34 | 01-MAY-07:10 | 0.360447E+11 | 13457.54 | 01-MAY-00:10 |
June | 0.226748E+11 | 22950.34 | 01-JUN-07:10 | 0.348820E+11 | 13457.54 | 01-JUN-00:10 |
July | 0.212244E+11 | 22950.34 | 03-JUL-07:10 | 0.360447E+11 | 13457.54 | 01-JUL-00:10 |
August | 0.236388E+11 | 22950.34 | 01-AUG-07:10 | 0.360447E+11 | 13457.54 | 01-AUG-00:10 |
September | 0.211142E+11 | 22950.34 | 01-SEP-07:10 | 0.348820E+11 | 13457.54 | 01-SEP-00:10 |
October | 0.219312E+11 | 22950.34 | 02-OCT-07:10 | 0.360447E+11 | 13457.54 | 01-OCT-00:10 |
November | 0.216742E+11 | 22950.34 | 01-NOV-07:10 | 0.348820E+11 | 13457.54 | 01-NOV-00:10 |
December | 0.212244E+11 | 22950.34 | 01-DEC-08:09 | 0.360447E+11 | 13457.54 | 01-DEC-00:10 |
Annual Sum or Average | 0.262844E+12 | 0.424397E+12 | ||||
Minimum of Months | 0.198933E+11 | 22950.34 | 0.325565E+11 | 13457.54 | ||
Maximum of Months | 0.236388E+11 | 22950.34 | 0.360447E+11 | 13457.54 |
Report: ZoneElectricSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.196958E+11 | 20611.01 | 02-JAN-08:09 | 0.243681E+11 | 17206.63 | 02-JAN-08:09 |
February | 0.178655E+11 | 20611.01 | 01-FEB-08:09 | 0.220609E+11 | 17206.63 | 01-FEB-08:09 |
March | 0.212293E+11 | 20611.01 | 01-MAR-08:09 | 0.253549E+11 | 17206.63 | 01-MAR-08:09 |
April | 0.189620E+11 | 20611.01 | 03-APR-07:10 | 0.235306E+11 | 17206.63 | 03-APR-07:10 |
May | 0.204625E+11 | 20611.01 | 01-MAY-07:10 | 0.248615E+11 | 17206.63 | 01-MAY-07:10 |
June | 0.203636E+11 | 20611.01 | 01-JUN-07:10 | 0.244160E+11 | 17206.63 | 01-JUN-07:10 |
July | 0.190610E+11 | 20611.01 | 03-JUL-07:10 | 0.239708E+11 | 17206.63 | 03-JUL-07:10 |
August | 0.212293E+11 | 20611.01 | 01-AUG-07:10 | 0.253549E+11 | 17206.63 | 01-AUG-07:10 |
September | 0.189620E+11 | 20611.01 | 01-SEP-07:10 | 0.235199E+11 | 17206.63 | 01-SEP-07:10 |
October | 0.196958E+11 | 20611.01 | 02-OCT-07:10 | 0.243735E+11 | 17206.63 | 02-OCT-07:10 |
November | 0.194649E+11 | 20611.01 | 01-NOV-07:10 | 0.238373E+11 | 17206.63 | 01-NOV-07:10 |
December | 0.190610E+11 | 20611.01 | 01-DEC-08:09 | 0.239654E+11 | 17206.63 | 01-DEC-08:09 |
Annual Sum or Average | 0.236053E+12 | 0.289614E+12 | ||||
Minimum of Months | 0.178655E+11 | 20611.01 | 0.220609E+11 | 17206.63 | ||
Maximum of Months | 0.212293E+11 | 20611.01 | 0.253549E+11 | 17206.63 |
Report: ZoneElectricSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.196958E+11 | 20611.01 | 02-JAN-08:09 | 0.243680E+11 | 17206.56 | 02-JAN-08:09 |
February | 0.178655E+11 | 20611.01 | 01-FEB-08:09 | 0.220609E+11 | 17206.56 | 01-FEB-08:09 |
March | 0.212293E+11 | 20611.01 | 01-MAR-08:09 | 0.253548E+11 | 17206.56 | 01-MAR-08:09 |
April | 0.189620E+11 | 20611.01 | 03-APR-07:10 | 0.235305E+11 | 17206.56 | 03-APR-07:10 |
May | 0.204625E+11 | 20611.01 | 01-MAY-07:10 | 0.248614E+11 | 17206.56 | 01-MAY-07:10 |
June | 0.203636E+11 | 20611.01 | 01-JUN-07:10 | 0.244159E+11 | 17206.56 | 01-JUN-07:10 |
July | 0.190610E+11 | 20611.01 | 03-JUL-07:10 | 0.239707E+11 | 17206.56 | 03-JUL-07:10 |
August | 0.212293E+11 | 20611.01 | 01-AUG-07:10 | 0.253548E+11 | 17206.56 | 01-AUG-07:10 |
September | 0.189620E+11 | 20611.01 | 01-SEP-07:10 | 0.235198E+11 | 17206.56 | 01-SEP-07:10 |
October | 0.196958E+11 | 20611.01 | 02-OCT-07:10 | 0.243734E+11 | 17206.56 | 02-OCT-07:10 |
November | 0.194649E+11 | 20611.01 | 01-NOV-07:10 | 0.238372E+11 | 17206.56 | 01-NOV-07:10 |
December | 0.190610E+11 | 20611.01 | 01-DEC-08:09 | 0.239653E+11 | 17206.56 | 01-DEC-08:09 |
Annual Sum or Average | 0.236053E+12 | 0.289613E+12 | ||||
Minimum of Months | 0.178655E+11 | 20611.01 | 0.220609E+11 | 17206.56 | ||
Maximum of Months | 0.212293E+11 | 20611.01 | 0.253548E+11 | 17206.56 |
Report: ZoneElectricSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.196958E+11 | 20611.01 | 02-JAN-08:09 | 0.243680E+11 | 17206.56 | 02-JAN-08:09 |
February | 0.178655E+11 | 20611.01 | 01-FEB-08:09 | 0.220609E+11 | 17206.56 | 01-FEB-08:09 |
March | 0.212293E+11 | 20611.01 | 01-MAR-08:09 | 0.253548E+11 | 17206.56 | 01-MAR-08:09 |
April | 0.189620E+11 | 20611.01 | 03-APR-07:10 | 0.235305E+11 | 17206.56 | 03-APR-07:10 |
May | 0.204625E+11 | 20611.01 | 01-MAY-07:10 | 0.248614E+11 | 17206.56 | 01-MAY-07:10 |
June | 0.203636E+11 | 20611.01 | 01-JUN-07:10 | 0.244159E+11 | 17206.56 | 01-JUN-07:10 |
July | 0.190610E+11 | 20611.01 | 03-JUL-07:10 | 0.239707E+11 | 17206.56 | 03-JUL-07:10 |
August | 0.212293E+11 | 20611.01 | 01-AUG-07:10 | 0.253548E+11 | 17206.56 | 01-AUG-07:10 |
September | 0.189620E+11 | 20611.01 | 01-SEP-07:10 | 0.235198E+11 | 17206.56 | 01-SEP-07:10 |
October | 0.196958E+11 | 20611.01 | 02-OCT-07:10 | 0.243734E+11 | 17206.56 | 02-OCT-07:10 |
November | 0.194649E+11 | 20611.01 | 01-NOV-07:10 | 0.238372E+11 | 17206.56 | 01-NOV-07:10 |
December | 0.190610E+11 | 20611.01 | 01-DEC-08:09 | 0.239653E+11 | 17206.56 | 01-DEC-08:09 |
Annual Sum or Average | 0.236053E+12 | 0.289613E+12 | ||||
Minimum of Months | 0.178655E+11 | 20611.01 | 0.220609E+11 | 17206.56 | ||
Maximum of Months | 0.212293E+11 | 20611.01 | 0.253548E+11 | 17206.56 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.164519E+10 | 2587.92 | 03-JAN-08:09 | 0.305979E+10 | 2160.55 | 02-JAN-08:09 |
February | 0.148700E+10 | 2587.92 | 01-FEB-08:09 | 0.277008E+10 | 2160.55 | 01-FEB-08:09 |
March | 0.156487E+10 | 2587.92 | 21-MAR-07:10 | 0.318369E+10 | 2160.55 | 01-MAR-08:09 |
April | 0.133785E+10 | 2255.20 | 03-APR-07:10 | 0.295462E+10 | 2160.55 | 03-APR-07:10 |
May | 0.138865E+10 | 1470.28 | 02-MAY-07:10 | 0.312174E+10 | 2160.55 | 01-MAY-07:10 |
June | 0.136362E+10 | 1470.28 | 23-JUN-07:10 | 0.306580E+10 | 2160.55 | 01-JUN-07:10 |
July | 0.129798E+10 | 1803.00 | 27-JUL-07:10 | 0.300989E+10 | 2160.55 | 03-JUL-07:10 |
August | 0.147313E+10 | 2255.20 | 24-AUG-07:10 | 0.318369E+10 | 2160.55 | 01-AUG-07:10 |
September | 0.138990E+10 | 2587.92 | 29-SEP-07:10 | 0.295328E+10 | 2160.55 | 01-SEP-07:10 |
October | 0.157657E+10 | 2587.92 | 19-OCT-07:10 | 0.306046E+10 | 2160.55 | 02-OCT-07:10 |
November | 0.158302E+10 | 2587.92 | 01-NOV-07:10 | 0.299314E+10 | 2160.55 | 01-NOV-07:10 |
December | 0.161015E+10 | 2587.92 | 06-DEC-08:09 | 0.300922E+10 | 2160.55 | 01-DEC-08:09 |
Annual Sum or Average | 0.177179E+11 | 0.363654E+11 | ||||
Minimum of Months | 0.129798E+10 | 1470.28 | 0.277008E+10 | 2160.55 | ||
Maximum of Months | 0.164519E+10 | 2587.92 | 0.318369E+10 | 2160.55 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.101471E+10 | 1667.75 | 03-JAN-08:09 | 0.197184E+10 | 1392.34 | 02-JAN-08:09 |
February | 0.918555E+09 | 1667.75 | 01-FEB-08:09 | 0.178515E+10 | 1392.34 | 01-FEB-08:09 |
March | 0.988585E+09 | 1667.75 | 21-MAR-07:10 | 0.205169E+10 | 1392.34 | 01-MAR-08:09 |
April | 0.858042E+09 | 1453.34 | 03-APR-07:10 | 0.190407E+10 | 1392.34 | 03-APR-07:10 |
May | 0.902214E+09 | 870.51 | 02-MAY-07:10 | 0.201177E+10 | 1392.34 | 01-MAY-07:10 |
June | 0.886900E+09 | 793.52 | 01-JUN-07:10 | 0.197572E+10 | 1392.34 | 01-JUN-07:10 |
July | 0.840993E+09 | 947.51 | 27-JUL-07:10 | 0.193969E+10 | 1392.34 | 03-JUL-07:10 |
August | 0.949747E+09 | 1453.34 | 24-AUG-07:10 | 0.205169E+10 | 1392.34 | 01-AUG-07:10 |
September | 0.880737E+09 | 1453.34 | 05-SEP-07:10 | 0.190321E+10 | 1392.34 | 01-SEP-07:10 |
October | 0.969692E+09 | 1667.75 | 19-OCT-07:10 | 0.197228E+10 | 1392.34 | 02-OCT-07:10 |
November | 0.989382E+09 | 1667.75 | 01-NOV-07:10 | 0.192889E+10 | 1392.34 | 01-NOV-07:10 |
December | 0.988938E+09 | 1667.75 | 06-DEC-08:09 | 0.193926E+10 | 1392.34 | 01-DEC-08:09 |
Annual Sum or Average | 0.111885E+11 | 0.234352E+11 | ||||
Minimum of Months | 0.840993E+09 | 793.52 | 0.178515E+10 | 1392.34 | ||
Maximum of Months | 0.101471E+10 | 1667.75 | 0.205169E+10 | 1392.34 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.151610E+10 | 2587.98 | 03-JAN-08:09 | 0.305983E+10 | 2160.58 | 02-JAN-08:09 |
February | 0.139430E+10 | 2587.98 | 01-FEB-08:09 | 0.277013E+10 | 2160.58 | 01-FEB-08:09 |
March | 0.153556E+10 | 2587.98 | 21-MAR-07:10 | 0.318374E+10 | 2160.58 | 01-MAR-08:09 |
April | 0.134267E+10 | 2255.25 | 03-APR-07:10 | 0.295467E+10 | 2160.58 | 03-APR-07:10 |
May | 0.141061E+10 | 1803.04 | 24-MAY-07:10 | 0.312179E+10 | 2160.58 | 01-MAY-07:10 |
June | 0.138612E+10 | 1470.31 | 23-JUN-07:10 | 0.306585E+10 | 2160.58 | 01-JUN-07:10 |
July | 0.131813E+10 | 1803.04 | 27-JUL-07:10 | 0.300994E+10 | 2160.58 | 03-JUL-07:10 |
August | 0.148201E+10 | 2255.25 | 24-AUG-07:10 | 0.318374E+10 | 2160.58 | 01-AUG-07:10 |
September | 0.137226E+10 | 2587.98 | 29-SEP-07:10 | 0.295333E+10 | 2160.58 | 01-SEP-07:10 |
October | 0.148633E+10 | 2587.98 | 19-OCT-07:10 | 0.306051E+10 | 2160.58 | 02-OCT-07:10 |
November | 0.148340E+10 | 2587.98 | 01-NOV-07:10 | 0.299318E+10 | 2160.58 | 01-NOV-07:10 |
December | 0.147188E+10 | 2587.98 | 06-DEC-08:09 | 0.300927E+10 | 2160.58 | 01-DEC-08:09 |
Annual Sum or Average | 0.171994E+11 | 0.363660E+11 | ||||
Minimum of Months | 0.131813E+10 | 1470.31 | 0.277013E+10 | 2160.58 | ||
Maximum of Months | 0.153556E+10 | 2587.98 | 0.318374E+10 | 2160.58 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.101481E+10 | 1667.75 | 03-JAN-08:09 | 0.197183E+10 | 1392.33 | 02-JAN-08:09 |
February | 0.932742E+09 | 1667.75 | 01-FEB-08:09 | 0.178514E+10 | 1392.33 | 01-FEB-08:09 |
March | 0.100688E+10 | 1667.75 | 16-MAR-07:10 | 0.205168E+10 | 1392.33 | 01-MAR-08:09 |
April | 0.867027E+09 | 1453.34 | 03-APR-07:10 | 0.190406E+10 | 1392.33 | 03-APR-07:10 |
May | 0.908560E+09 | 1453.34 | 24-MAY-07:10 | 0.201175E+10 | 1392.33 | 01-MAY-07:10 |
June | 0.890974E+09 | 1161.92 | 23-JUN-07:10 | 0.197570E+10 | 1392.33 | 01-JUN-07:10 |
July | 0.848381E+09 | 1453.34 | 27-JUL-07:10 | 0.193968E+10 | 1392.33 | 03-JUL-07:10 |
August | 0.958468E+09 | 1453.34 | 23-AUG-07:10 | 0.205168E+10 | 1392.33 | 01-AUG-07:10 |
September | 0.896243E+09 | 1667.75 | 29-SEP-07:10 | 0.190319E+10 | 1392.33 | 01-SEP-07:10 |
October | 0.999383E+09 | 1667.75 | 13-OCT-07:10 | 0.197226E+10 | 1392.33 | 02-OCT-07:10 |
November | 0.980521E+09 | 1667.75 | 01-NOV-07:10 | 0.192888E+10 | 1392.33 | 01-NOV-07:10 |
December | 0.987375E+09 | 1667.75 | 06-DEC-08:09 | 0.193924E+10 | 1392.33 | 01-DEC-08:09 |
Annual Sum or Average | 0.112914E+11 | 0.234351E+11 | ||||
Minimum of Months | 0.848381E+09 | 1161.92 | 0.178514E+10 | 1392.33 | ||
Maximum of Months | 0.101481E+10 | 1667.75 | 0.205168E+10 | 1392.33 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.163281E+10 | 2587.92 | 03-JAN-08:09 | 0.305979E+10 | 2160.55 | 02-JAN-08:09 |
February | 0.147900E+10 | 2587.92 | 01-FEB-08:09 | 0.277008E+10 | 2160.55 | 01-FEB-08:09 |
March | 0.155941E+10 | 2587.92 | 21-MAR-07:10 | 0.318369E+10 | 2160.55 | 01-MAR-08:09 |
April | 0.133433E+10 | 2255.20 | 03-APR-07:10 | 0.295462E+10 | 2160.55 | 03-APR-07:10 |
May | 0.138700E+10 | 1470.28 | 02-MAY-07:10 | 0.312174E+10 | 2160.55 | 01-MAY-07:10 |
June | 0.136191E+10 | 1470.28 | 23-JUN-07:10 | 0.306580E+10 | 2160.55 | 01-JUN-07:10 |
July | 0.129625E+10 | 1803.00 | 27-JUL-07:10 | 0.300989E+10 | 2160.55 | 03-JUL-07:10 |
August | 0.147090E+10 | 2255.20 | 24-AUG-07:10 | 0.318369E+10 | 2160.55 | 01-AUG-07:10 |
September | 0.138412E+10 | 2587.92 | 29-SEP-07:10 | 0.295328E+10 | 2160.55 | 01-SEP-07:10 |
October | 0.156565E+10 | 2587.92 | 19-OCT-07:10 | 0.306046E+10 | 2160.55 | 02-OCT-07:10 |
November | 0.157391E+10 | 2587.92 | 01-NOV-07:10 | 0.299314E+10 | 2160.55 | 01-NOV-07:10 |
December | 0.159810E+10 | 2587.92 | 06-DEC-08:09 | 0.300922E+10 | 2160.55 | 01-DEC-08:09 |
Annual Sum or Average | 0.176434E+11 | 0.363654E+11 | ||||
Minimum of Months | 0.129625E+10 | 1470.28 | 0.277008E+10 | 2160.55 | ||
Maximum of Months | 0.163281E+10 | 2587.92 | 0.318369E+10 | 2160.55 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.100989E+10 | 1667.75 | 03-JAN-08:09 | 0.197184E+10 | 1392.34 | 02-JAN-08:09 |
February | 0.915334E+09 | 1667.75 | 01-FEB-08:09 | 0.178515E+10 | 1392.34 | 01-FEB-08:09 |
March | 0.986649E+09 | 1667.75 | 21-MAR-07:10 | 0.205169E+10 | 1392.34 | 01-MAR-08:09 |
April | 0.856622E+09 | 1453.34 | 03-APR-07:10 | 0.190407E+10 | 1392.34 | 03-APR-07:10 |
May | 0.901322E+09 | 870.51 | 02-MAY-07:10 | 0.201177E+10 | 1392.34 | 01-MAY-07:10 |
June | 0.886119E+09 | 793.52 | 01-JUN-07:10 | 0.197572E+10 | 1392.34 | 01-JUN-07:10 |
July | 0.840347E+09 | 947.51 | 27-JUL-07:10 | 0.193969E+10 | 1392.34 | 03-JUL-07:10 |
August | 0.948789E+09 | 1453.34 | 24-AUG-07:10 | 0.205169E+10 | 1392.34 | 01-AUG-07:10 |
September | 0.879519E+09 | 1453.34 | 05-SEP-07:10 | 0.190321E+10 | 1392.34 | 01-SEP-07:10 |
October | 0.966687E+09 | 1667.75 | 19-OCT-07:10 | 0.197228E+10 | 1392.34 | 02-OCT-07:10 |
November | 0.985860E+09 | 1667.75 | 01-NOV-07:10 | 0.192889E+10 | 1392.34 | 01-NOV-07:10 |
December | 0.986180E+09 | 1667.75 | 06-DEC-08:09 | 0.193926E+10 | 1392.34 | 01-DEC-08:09 |
Annual Sum or Average | 0.111633E+11 | 0.234352E+11 | ||||
Minimum of Months | 0.840347E+09 | 793.52 | 0.178515E+10 | 1392.34 | ||
Maximum of Months | 0.100989E+10 | 1667.75 | 0.205169E+10 | 1392.34 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.151467E+10 | 2587.98 | 03-JAN-08:09 | 0.305983E+10 | 2160.58 | 02-JAN-08:09 |
February | 0.139281E+10 | 2587.98 | 01-FEB-08:09 | 0.277013E+10 | 2160.58 | 01-FEB-08:09 |
March | 0.153305E+10 | 2587.98 | 21-MAR-07:10 | 0.318374E+10 | 2160.58 | 01-MAR-08:09 |
April | 0.133946E+10 | 2255.25 | 03-APR-07:10 | 0.295467E+10 | 2160.58 | 03-APR-07:10 |
May | 0.140845E+10 | 1803.04 | 24-MAY-07:10 | 0.312179E+10 | 2160.58 | 01-MAY-07:10 |
June | 0.138378E+10 | 1470.31 | 23-JUN-07:10 | 0.306585E+10 | 2160.58 | 01-JUN-07:10 |
July | 0.131584E+10 | 1803.04 | 27-JUL-07:10 | 0.300994E+10 | 2160.58 | 03-JUL-07:10 |
August | 0.148015E+10 | 2255.25 | 24-AUG-07:10 | 0.318374E+10 | 2160.58 | 01-AUG-07:10 |
September | 0.137019E+10 | 2587.98 | 29-SEP-07:10 | 0.295333E+10 | 2160.58 | 01-SEP-07:10 |
October | 0.148476E+10 | 2587.98 | 19-OCT-07:10 | 0.306051E+10 | 2160.58 | 02-OCT-07:10 |
November | 0.148021E+10 | 2587.98 | 01-NOV-07:10 | 0.299318E+10 | 2160.58 | 01-NOV-07:10 |
December | 0.146964E+10 | 2587.98 | 06-DEC-08:09 | 0.300927E+10 | 2160.58 | 01-DEC-08:09 |
Annual Sum or Average | 0.171730E+11 | 0.363660E+11 | ||||
Minimum of Months | 0.131584E+10 | 1470.31 | 0.277013E+10 | 2160.58 | ||
Maximum of Months | 0.153305E+10 | 2587.98 | 0.318374E+10 | 2160.58 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.101166E+10 | 1667.75 | 03-JAN-08:09 | 0.197183E+10 | 1392.33 | 02-JAN-08:09 |
February | 0.929254E+09 | 1667.75 | 01-FEB-08:09 | 0.178514E+10 | 1392.33 | 01-FEB-08:09 |
March | 0.100366E+10 | 1667.75 | 16-MAR-07:10 | 0.205168E+10 | 1392.33 | 01-MAR-08:09 |
April | 0.865094E+09 | 1453.34 | 03-APR-07:10 | 0.190406E+10 | 1392.33 | 03-APR-07:10 |
May | 0.906387E+09 | 1453.34 | 24-MAY-07:19 | 0.201175E+10 | 1392.33 | 01-MAY-07:10 |
June | 0.889258E+09 | 1161.92 | 23-JUN-07:10 | 0.197570E+10 | 1392.33 | 01-JUN-07:10 |
July | 0.846935E+09 | 1453.34 | 27-JUL-07:10 | 0.193968E+10 | 1392.33 | 03-JUL-07:10 |
August | 0.956355E+09 | 1453.34 | 23-AUG-07:10 | 0.205168E+10 | 1392.33 | 01-AUG-07:10 |
September | 0.893970E+09 | 1667.75 | 29-SEP-07:10 | 0.190319E+10 | 1392.33 | 01-SEP-07:10 |
October | 0.994877E+09 | 1667.75 | 13-OCT-07:10 | 0.197226E+10 | 1392.33 | 02-OCT-07:10 |
November | 0.977743E+09 | 1667.75 | 01-NOV-07:10 | 0.192888E+10 | 1392.33 | 01-NOV-07:10 |
December | 0.983433E+09 | 1667.75 | 06-DEC-08:09 | 0.193924E+10 | 1392.33 | 01-DEC-08:09 |
Annual Sum or Average | 0.112586E+11 | 0.234351E+11 | ||||
Minimum of Months | 0.846935E+09 | 1161.92 | 0.178514E+10 | 1392.33 | ||
Maximum of Months | 0.101166E+10 | 1667.75 | 0.205168E+10 | 1392.33 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.163253E+10 | 2587.92 | 03-JAN-08:09 | 0.305979E+10 | 2160.55 | 02-JAN-08:09 |
February | 0.147861E+10 | 2587.92 | 01-FEB-08:09 | 0.277008E+10 | 2160.55 | 01-FEB-08:09 |
March | 0.155915E+10 | 2587.92 | 21-MAR-07:10 | 0.318369E+10 | 2160.55 | 01-MAR-08:09 |
April | 0.133425E+10 | 2255.20 | 03-APR-07:10 | 0.295462E+10 | 2160.55 | 03-APR-07:10 |
May | 0.138683E+10 | 1470.28 | 02-MAY-07:10 | 0.312174E+10 | 2160.55 | 01-MAY-07:10 |
June | 0.136189E+10 | 1470.28 | 23-JUN-07:10 | 0.306580E+10 | 2160.55 | 01-JUN-07:10 |
July | 0.129621E+10 | 1803.00 | 27-JUL-07:10 | 0.300989E+10 | 2160.55 | 03-JUL-07:10 |
August | 0.147061E+10 | 2255.20 | 24-AUG-07:10 | 0.318369E+10 | 2160.55 | 01-AUG-07:10 |
September | 0.138411E+10 | 2587.92 | 29-SEP-07:10 | 0.295328E+10 | 2160.55 | 01-SEP-07:10 |
October | 0.156494E+10 | 2587.92 | 19-OCT-07:10 | 0.306046E+10 | 2160.55 | 02-OCT-07:10 |
November | 0.157323E+10 | 2587.92 | 01-NOV-07:10 | 0.299314E+10 | 2160.55 | 01-NOV-07:10 |
December | 0.159788E+10 | 2587.92 | 06-DEC-08:09 | 0.300922E+10 | 2160.55 | 01-DEC-08:09 |
Annual Sum or Average | 0.176402E+11 | 0.363654E+11 | ||||
Minimum of Months | 0.129621E+10 | 1470.28 | 0.277008E+10 | 2160.55 | ||
Maximum of Months | 0.163253E+10 | 2587.92 | 0.318369E+10 | 2160.55 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.100985E+10 | 1667.75 | 03-JAN-08:09 | 0.197184E+10 | 1392.34 | 02-JAN-08:09 |
February | 0.914948E+09 | 1667.75 | 01-FEB-08:09 | 0.178515E+10 | 1392.34 | 01-FEB-08:09 |
March | 0.986409E+09 | 1667.75 | 21-MAR-07:10 | 0.205169E+10 | 1392.34 | 01-MAR-08:09 |
April | 0.856592E+09 | 1453.34 | 03-APR-07:10 | 0.190407E+10 | 1392.34 | 03-APR-07:10 |
May | 0.901263E+09 | 870.51 | 02-MAY-07:10 | 0.201177E+10 | 1392.34 | 01-MAY-07:10 |
June | 0.886119E+09 | 793.52 | 01-JUN-07:10 | 0.197572E+10 | 1392.34 | 01-JUN-07:10 |
July | 0.840205E+09 | 947.51 | 27-JUL-07:10 | 0.193969E+10 | 1392.34 | 03-JUL-07:10 |
August | 0.948730E+09 | 1453.34 | 24-AUG-07:10 | 0.205169E+10 | 1392.34 | 01-AUG-07:10 |
September | 0.879472E+09 | 1453.34 | 05-SEP-07:10 | 0.190321E+10 | 1392.34 | 01-SEP-07:10 |
October | 0.966567E+09 | 1667.75 | 19-OCT-07:10 | 0.197228E+10 | 1392.34 | 02-OCT-07:10 |
November | 0.985765E+09 | 1667.75 | 01-NOV-07:10 | 0.192889E+10 | 1392.34 | 01-NOV-07:10 |
December | 0.986046E+09 | 1667.75 | 06-DEC-08:09 | 0.193926E+10 | 1392.34 | 01-DEC-08:09 |
Annual Sum or Average | 0.111620E+11 | 0.234352E+11 | ||||
Minimum of Months | 0.840205E+09 | 793.52 | 0.178515E+10 | 1392.34 | ||
Maximum of Months | 0.100985E+10 | 1667.75 | 0.205169E+10 | 1392.34 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.151449E+10 | 2587.98 | 03-JAN-08:09 | 0.305983E+10 | 2160.58 | 02-JAN-08:09 |
February | 0.139239E+10 | 2587.98 | 01-FEB-08:09 | 0.277013E+10 | 2160.58 | 01-FEB-08:09 |
March | 0.153277E+10 | 2587.98 | 21-MAR-07:10 | 0.318374E+10 | 2160.58 | 01-MAR-08:09 |
April | 0.133924E+10 | 2255.25 | 03-APR-07:10 | 0.295467E+10 | 2160.58 | 03-APR-07:10 |
May | 0.140845E+10 | 1803.04 | 24-MAY-07:10 | 0.312179E+10 | 2160.58 | 01-MAY-07:10 |
June | 0.138356E+10 | 1470.31 | 23-JUN-07:10 | 0.306585E+10 | 2160.58 | 01-JUN-07:10 |
July | 0.131564E+10 | 1803.04 | 27-JUL-07:10 | 0.300994E+10 | 2160.58 | 03-JUL-07:10 |
August | 0.148013E+10 | 2255.25 | 24-AUG-07:10 | 0.318374E+10 | 2160.58 | 01-AUG-07:10 |
September | 0.137003E+10 | 2587.98 | 29-SEP-07:10 | 0.295333E+10 | 2160.58 | 01-SEP-07:10 |
October | 0.148469E+10 | 2587.98 | 19-OCT-07:10 | 0.306051E+10 | 2160.58 | 02-OCT-07:10 |
November | 0.148007E+10 | 2587.98 | 01-NOV-07:10 | 0.299318E+10 | 2160.58 | 01-NOV-07:10 |
December | 0.146956E+10 | 2587.98 | 06-DEC-08:09 | 0.300927E+10 | 2160.58 | 01-DEC-08:09 |
Annual Sum or Average | 0.171710E+11 | 0.363660E+11 | ||||
Minimum of Months | 0.131564E+10 | 1470.31 | 0.277013E+10 | 2160.58 | ||
Maximum of Months | 0.153277E+10 | 2587.98 | 0.318374E+10 | 2160.58 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.101165E+10 | 1667.75 | 03-JAN-08:09 | 0.197183E+10 | 1392.33 | 02-JAN-08:09 |
February | 0.929159E+09 | 1667.75 | 01-FEB-08:09 | 0.178514E+10 | 1392.33 | 01-FEB-08:09 |
March | 0.100346E+10 | 1667.75 | 16-MAR-07:10 | 0.205168E+10 | 1392.33 | 01-MAR-08:09 |
April | 0.865048E+09 | 1453.34 | 03-APR-07:10 | 0.190406E+10 | 1392.33 | 03-APR-07:10 |
May | 0.906497E+09 | 1453.34 | 24-MAY-07:19 | 0.201175E+10 | 1392.33 | 01-MAY-07:10 |
June | 0.889166E+09 | 1161.92 | 23-JUN-07:10 | 0.197570E+10 | 1392.33 | 01-JUN-07:10 |
July | 0.846873E+09 | 1453.34 | 27-JUL-07:10 | 0.193968E+10 | 1392.33 | 03-JUL-07:10 |
August | 0.956181E+09 | 1453.34 | 23-AUG-07:10 | 0.205168E+10 | 1392.33 | 01-AUG-07:10 |
September | 0.893967E+09 | 1667.75 | 29-SEP-07:10 | 0.190319E+10 | 1392.33 | 01-SEP-07:10 |
October | 0.994527E+09 | 1667.75 | 13-OCT-07:10 | 0.197226E+10 | 1392.33 | 02-OCT-07:10 |
November | 0.977696E+09 | 1667.75 | 01-NOV-07:10 | 0.192888E+10 | 1392.33 | 01-NOV-07:10 |
December | 0.983336E+09 | 1667.75 | 06-DEC-08:09 | 0.193924E+10 | 1392.33 | 01-DEC-08:09 |
Annual Sum or Average | 0.112576E+11 | 0.234351E+11 | ||||
Minimum of Months | 0.846873E+09 | 1161.92 | 0.178514E+10 | 1392.33 | ||
Maximum of Months | 0.101165E+10 | 1667.75 | 0.205168E+10 | 1392.33 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.553024E+09 | 578.72 | 02-JAN-08:09 | 0.521915E+10 | 1948.61 | 01-JAN-00:10 |
February | 0.501634E+09 | 578.72 | 01-FEB-08:09 | 0.942813E+10 | 3897.21 | 01-FEB-00:10 |
March | 0.596080E+09 | 578.72 | 01-MAR-08:09 | 0.156645E+11 | 7794.42 | 31-MAR-23:10 |
April | 0.532421E+09 | 578.72 | 03-APR-07:10 | 0.201821E+11 | 7794.42 | 01-APR-00:10 |
May | 0.574552E+09 | 578.72 | 01-MAY-07:10 | 0.522616E+10 | 3897.21 | 31-MAY-23:10 |
June | 0.571774E+09 | 578.72 | 01-JUN-07:10 | 0.101086E+11 | 5845.82 | 30-JUN-23:10 |
July | 0.535199E+09 | 578.72 | 03-JUL-07:10 | 0.156645E+11 | 7794.42 | 31-JUL-23:10 |
August | 0.596080E+09 | 578.72 | 01-AUG-07:10 | 0.208555E+11 | 7794.42 | 01-AUG-00:10 |
September | 0.532421E+09 | 578.72 | 01-SEP-07:10 | 0.505780E+10 | 3897.21 | 30-SEP-23:10 |
October | 0.553024E+09 | 578.72 | 02-OCT-07:10 | 0.104453E+11 | 5845.82 | 31-OCT-23:10 |
November | 0.546542E+09 | 578.72 | 01-NOV-07:10 | 0.151524E+11 | 5845.82 | 01-NOV-00:10 |
December | 0.535199E+09 | 578.72 | 01-DEC-08:09 | 0.208766E+11 | 7794.42 | 01-DEC-00:10 |
Annual Sum or Average | 0.662795E+10 | 0.153881E+12 | ||||
Minimum of Months | 0.501634E+09 | 578.72 | 0.505780E+10 | 1948.61 | ||
Maximum of Months | 0.596080E+09 | 578.72 | 0.208766E+11 | 7794.42 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.553024E+09 | 578.72 | 02-JAN-08:09 | 0.521915E+10 | 1948.61 | 01-JAN-00:10 |
February | 0.501634E+09 | 578.72 | 01-FEB-08:09 | 0.942813E+10 | 3897.21 | 01-FEB-00:10 |
March | 0.596080E+09 | 578.72 | 01-MAR-08:09 | 0.156645E+11 | 7794.42 | 31-MAR-23:10 |
April | 0.532421E+09 | 578.72 | 03-APR-07:10 | 0.201821E+11 | 7794.42 | 01-APR-00:10 |
May | 0.574552E+09 | 578.72 | 01-MAY-07:10 | 0.522616E+10 | 3897.21 | 31-MAY-23:10 |
June | 0.571774E+09 | 578.72 | 01-JUN-07:10 | 0.101086E+11 | 5845.82 | 30-JUN-23:10 |
July | 0.535199E+09 | 578.72 | 03-JUL-07:10 | 0.156645E+11 | 7794.42 | 31-JUL-23:10 |
August | 0.596080E+09 | 578.72 | 01-AUG-07:10 | 0.208555E+11 | 7794.42 | 01-AUG-00:10 |
September | 0.532421E+09 | 578.72 | 01-SEP-07:10 | 0.505780E+10 | 3897.21 | 30-SEP-23:10 |
October | 0.553024E+09 | 578.72 | 02-OCT-07:10 | 0.104453E+11 | 5845.82 | 31-OCT-23:10 |
November | 0.546542E+09 | 578.72 | 01-NOV-07:10 | 0.151524E+11 | 5845.82 | 01-NOV-00:10 |
December | 0.535199E+09 | 578.72 | 01-DEC-08:09 | 0.208766E+11 | 7794.42 | 01-DEC-00:10 |
Annual Sum or Average | 0.662795E+10 | 0.153881E+12 | ||||
Minimum of Months | 0.501634E+09 | 578.72 | 0.505780E+10 | 1948.61 | ||
Maximum of Months | 0.596080E+09 | 578.72 | 0.208766E+11 | 7794.42 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.553024E+09 | 578.72 | 02-JAN-08:09 | 0.521915E+10 | 1948.61 | 01-JAN-00:10 |
February | 0.501634E+09 | 578.72 | 01-FEB-08:09 | 0.942813E+10 | 3897.21 | 01-FEB-00:10 |
March | 0.596080E+09 | 578.72 | 01-MAR-08:09 | 0.156645E+11 | 7794.42 | 31-MAR-23:10 |
April | 0.532421E+09 | 578.72 | 03-APR-07:10 | 0.201821E+11 | 7794.42 | 01-APR-00:10 |
May | 0.574552E+09 | 578.72 | 01-MAY-07:10 | 0.522616E+10 | 3897.21 | 31-MAY-23:10 |
June | 0.571774E+09 | 578.72 | 01-JUN-07:10 | 0.101086E+11 | 5845.82 | 30-JUN-23:10 |
July | 0.535199E+09 | 578.72 | 03-JUL-07:10 | 0.156645E+11 | 7794.42 | 31-JUL-23:10 |
August | 0.596080E+09 | 578.72 | 01-AUG-07:10 | 0.208555E+11 | 7794.42 | 01-AUG-00:10 |
September | 0.532421E+09 | 578.72 | 01-SEP-07:10 | 0.505780E+10 | 3897.21 | 30-SEP-23:10 |
October | 0.553024E+09 | 578.72 | 02-OCT-07:10 | 0.104453E+11 | 5845.82 | 31-OCT-23:10 |
November | 0.546542E+09 | 578.72 | 01-NOV-07:10 | 0.151524E+11 | 5845.82 | 01-NOV-00:10 |
December | 0.535199E+09 | 578.72 | 01-DEC-08:09 | 0.208766E+11 | 7794.42 | 01-DEC-00:10 |
Annual Sum or Average | 0.662795E+10 | 0.153881E+12 | ||||
Minimum of Months | 0.501634E+09 | 578.72 | 0.505780E+10 | 1948.61 | ||
Maximum of Months | 0.596080E+09 | 578.72 | 0.208766E+11 | 7794.42 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.618367E+10 | 6471.01 | 02-JAN-08:09 | 0.254202E+12 | 94908.13 | 01-JAN-00:10 |
February | 0.560905E+10 | 6471.01 | 01-FEB-08:09 | 0.459203E+12 | 189816.26 | 01-FEB-00:10 |
March | 0.666512E+10 | 6471.01 | 01-MAR-08:09 | 0.762947E+12 | 379632.52 | 31-MAR-23:10 |
April | 0.595330E+10 | 6471.01 | 03-APR-07:10 | 0.982982E+12 | 379632.52 | 01-APR-00:10 |
May | 0.642439E+10 | 6471.01 | 01-MAY-07:10 | 0.254544E+12 | 189816.26 | 31-MAY-23:10 |
June | 0.639333E+10 | 6471.01 | 01-JUN-07:10 | 0.492345E+12 | 284724.39 | 30-JUN-23:10 |
July | 0.598436E+10 | 6471.01 | 03-JUL-07:10 | 0.762947E+12 | 379632.52 | 31-JUL-23:10 |
August | 0.666512E+10 | 6471.01 | 01-AUG-07:10 | 0.101578E+13 | 379632.52 | 01-AUG-00:10 |
September | 0.595330E+10 | 6471.01 | 01-SEP-07:10 | 0.246344E+12 | 189816.26 | 30-SEP-23:10 |
October | 0.618367E+10 | 6471.01 | 02-OCT-07:10 | 0.508746E+12 | 284724.39 | 31-OCT-23:10 |
November | 0.611120E+10 | 6471.01 | 01-NOV-07:10 | 0.738006E+12 | 284724.39 | 01-NOV-00:10 |
December | 0.598436E+10 | 6471.01 | 01-DEC-08:09 | 0.101681E+13 | 379632.52 | 01-DEC-00:10 |
Annual Sum or Average | 0.741109E+11 | 0.749486E+13 | ||||
Minimum of Months | 0.560905E+10 | 6471.01 | 0.246344E+12 | 94908.13 | ||
Maximum of Months | 0.666512E+10 | 6471.01 | 0.101681E+13 | 379632.52 |
Report: SpaceGainsMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.133902E+11 | 0.219312E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.121482E+11 | 0.198933E+11 | 0.325565E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.145160E+11 | 0.236388E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.128805E+11 | 0.211142E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.139531E+11 | 0.227850E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.139143E+11 | 0.226748E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.129193E+11 | 0.212244E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.145160E+11 | 0.236388E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.128805E+11 | 0.211142E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.133902E+11 | 0.219312E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.132595E+11 | 0.216742E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.129193E+11 | 0.212244E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.160687E+12 | 0.262844E+12 | 0.424397E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.121482E+11 | 0.198933E+11 | 0.325565E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.145160E+11 | 0.236388E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.120254E+11 | 0.196958E+11 | 0.243681E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.109099E+11 | 0.178655E+11 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.130364E+11 | 0.212293E+11 | 0.253549E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.115676E+11 | 0.189620E+11 | 0.235306E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.125309E+11 | 0.204625E+11 | 0.248615E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.124961E+11 | 0.203636E+11 | 0.244160E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.116025E+11 | 0.190610E+11 | 0.239708E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.130364E+11 | 0.212293E+11 | 0.253549E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.115676E+11 | 0.189620E+11 | 0.235199E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.120254E+11 | 0.196958E+11 | 0.243735E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.119080E+11 | 0.194649E+11 | 0.238373E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.116025E+11 | 0.190610E+11 | 0.239654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.144308E+12 | 0.236053E+12 | 0.289614E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.109099E+11 | 0.178655E+11 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.130364E+11 | 0.212293E+11 | 0.253549E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.120254E+11 | 0.196958E+11 | 0.243680E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.109099E+11 | 0.178655E+11 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.130364E+11 | 0.212293E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.115676E+11 | 0.189620E+11 | 0.235305E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.125309E+11 | 0.204625E+11 | 0.248614E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.124961E+11 | 0.203636E+11 | 0.244159E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.116025E+11 | 0.190610E+11 | 0.239707E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.130364E+11 | 0.212293E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.115676E+11 | 0.189620E+11 | 0.235198E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.120254E+11 | 0.196958E+11 | 0.243734E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.119080E+11 | 0.194649E+11 | 0.238372E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.116025E+11 | 0.190610E+11 | 0.239653E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.144308E+12 | 0.236053E+12 | 0.289613E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.109099E+11 | 0.178655E+11 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.130364E+11 | 0.212293E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.120254E+11 | 0.196958E+11 | 0.243680E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.109099E+11 | 0.178655E+11 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.130364E+11 | 0.212293E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.115676E+11 | 0.189620E+11 | 0.235305E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.125309E+11 | 0.204625E+11 | 0.248614E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.124961E+11 | 0.203636E+11 | 0.244159E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.116025E+11 | 0.190610E+11 | 0.239707E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.130364E+11 | 0.212293E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.115676E+11 | 0.189620E+11 | 0.235198E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.120254E+11 | 0.196958E+11 | 0.243734E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.119080E+11 | 0.194649E+11 | 0.238372E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.116025E+11 | 0.190610E+11 | 0.239653E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.144308E+12 | 0.236053E+12 | 0.289613E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.109099E+11 | 0.178655E+11 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.130364E+11 | 0.212293E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150991E+10 | 0.164519E+10 | 0.305979E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.946577E+09 |
February | 0.136985E+10 | 0.148700E+10 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 541198.99 | 0.803305E+09 |
March | 0.163685E+10 | 0.156487E+10 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1653898.63 | 0.524276E+09 |
April | 0.145243E+10 | 0.133785E+10 | 0.295462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4811543.39 | 0.315612E+09 |
May | 0.157338E+10 | 0.138865E+10 | 0.312174E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14574659.91 | 0.198107E+09 |
June | 0.156900E+10 | 0.136362E+10 | 0.306580E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 59755129.75 | 92246109.04 |
July | 0.145680E+10 | 0.129798E+10 | 0.300989E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 67147714.99 | 54954917.11 |
August | 0.163685E+10 | 0.147313E+10 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 65871487.11 | 24002661.81 |
September | 0.145243E+10 | 0.138990E+10 | 0.295328E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17999779.77 | 0.105152E+09 |
October | 0.150991E+10 | 0.157657E+10 | 0.306046E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4135042.33 | 0.357047E+09 |
November | 0.149516E+10 | 0.158302E+10 | 0.299314E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 51461.12 | 0.525925E+09 |
December | 0.145680E+10 | 0.161015E+10 | 0.300922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.912675E+09 |
Annual Sum or Average | 0.181194E+11 | 0.177179E+11 | 0.363654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.236542E+09 | 0.485988E+10 |
Minimum of Months | 0.136985E+10 | 0.129798E+10 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24002661.81 |
Maximum of Months | 0.163685E+10 | 0.164519E+10 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 67147714.99 | 0.946577E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.101471E+10 | 0.197184E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.633842E+09 |
February | 0.882782E+09 | 0.918555E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 222308.86 | 0.535074E+09 |
March | 0.105485E+10 | 0.988585E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1412059.46 | 0.342946E+09 |
April | 0.936002E+09 | 0.858042E+09 | 0.190407E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3463841.49 | 0.201557E+09 |
May | 0.101394E+10 | 0.902214E+09 | 0.201177E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9457020.99 | 0.133297E+09 |
June | 0.101113E+10 | 0.886900E+09 | 0.197572E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 40748178.28 | 58316025.48 |
July | 0.938820E+09 | 0.840993E+09 | 0.193969E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 47023787.78 | 32242372.02 |
August | 0.105485E+10 | 0.949747E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 48588105.39 | 10257757.29 |
September | 0.936002E+09 | 0.880737E+09 | 0.190321E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12178530.79 | 67341413.89 |
October | 0.973041E+09 | 0.969692E+09 | 0.197228E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2652629.22 | 0.233266E+09 |
November | 0.963541E+09 | 0.989382E+09 | 0.192889E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 207769.49 | 0.343797E+09 |
December | 0.938820E+09 | 0.988938E+09 | 0.193926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.594302E+09 |
Annual Sum or Average | 0.116768E+11 | 0.111885E+11 | 0.234352E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.165954E+09 | 0.318624E+10 |
Minimum of Months | 0.882782E+09 | 0.840993E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10257757.29 |
Maximum of Months | 0.105485E+10 | 0.101471E+10 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 48588105.39 | 0.633842E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150994E+10 | 0.151610E+10 | 0.305983E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.962914E+09 |
February | 0.136988E+10 | 0.139430E+10 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 95585.79 | 0.822281E+09 |
March | 0.163688E+10 | 0.153556E+10 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1573977.76 | 0.541889E+09 |
April | 0.145246E+10 | 0.134267E+10 | 0.295467E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4015536.40 | 0.315287E+09 |
May | 0.157341E+10 | 0.141061E+10 | 0.312179E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13765665.35 | 0.196853E+09 |
June | 0.156904E+10 | 0.138612E+10 | 0.306585E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 59686051.17 | 90550674.61 |
July | 0.145684E+10 | 0.131813E+10 | 0.300994E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 66119145.80 | 54231757.49 |
August | 0.163688E+10 | 0.148201E+10 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 62861588.06 | 25812415.96 |
September | 0.145246E+10 | 0.137226E+10 | 0.295333E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15112665.51 | 0.106124E+09 |
October | 0.150994E+10 | 0.148633E+10 | 0.306051E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2437398.94 | 0.367135E+09 |
November | 0.149520E+10 | 0.148340E+10 | 0.299318E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.541422E+09 |
December | 0.145684E+10 | 0.147188E+10 | 0.300927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.911908E+09 |
Annual Sum or Average | 0.181198E+11 | 0.171994E+11 | 0.363660E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.225668E+09 | 0.493641E+10 |
Minimum of Months | 0.136988E+10 | 0.131813E+10 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25812415.96 |
Maximum of Months | 0.163688E+10 | 0.153556E+10 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 66119145.80 | 0.962914E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.101481E+10 | 0.197183E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.663524E+09 |
February | 0.882782E+09 | 0.932742E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 81760.78 | 0.582401E+09 |
March | 0.105485E+10 | 0.100688E+10 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1037877.91 | 0.405812E+09 |
April | 0.936002E+09 | 0.867027E+09 | 0.190406E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2559684.70 | 0.250462E+09 |
May | 0.101394E+10 | 0.908560E+09 | 0.201175E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8571176.72 | 0.149428E+09 |
June | 0.101113E+10 | 0.890974E+09 | 0.197570E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 37070345.03 | 75486103.95 |
July | 0.938820E+09 | 0.848381E+09 | 0.193968E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 39804641.43 | 48025608.13 |
August | 0.105485E+10 | 0.958468E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 37421374.08 | 28214443.95 |
September | 0.936002E+09 | 0.896243E+09 | 0.190319E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10828959.70 | 81497113.87 |
October | 0.973041E+09 | 0.999383E+09 | 0.197226E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1783414.64 | 0.269078E+09 |
November | 0.963541E+09 | 0.980521E+09 | 0.192888E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.395297E+09 |
December | 0.938820E+09 | 0.987375E+09 | 0.193924E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.684507E+09 |
Annual Sum or Average | 0.116768E+11 | 0.112914E+11 | 0.234351E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.139159E+09 | 0.363373E+10 |
Minimum of Months | 0.882782E+09 | 0.848381E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28214443.95 |
Maximum of Months | 0.105485E+10 | 0.101481E+10 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 39804641.43 | 0.684507E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150991E+10 | 0.163281E+10 | 0.305979E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.190401E+10 |
February | 0.136985E+10 | 0.147900E+10 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4822054.68 | 0.161239E+10 |
March | 0.163685E+10 | 0.155941E+10 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5388019.74 | 0.103217E+10 |
April | 0.145243E+10 | 0.133433E+10 | 0.295462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14022526.76 | 0.652131E+09 |
May | 0.157338E+10 | 0.138700E+10 | 0.312174E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 35635418.87 | 0.423468E+09 |
June | 0.156900E+10 | 0.136191E+10 | 0.306580E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.138695E+09 | 0.213193E+09 |
July | 0.145680E+10 | 0.129625E+10 | 0.300989E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.152060E+09 | 0.139261E+09 |
August | 0.163685E+10 | 0.147090E+10 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.148203E+09 | 85932060.34 |
September | 0.145243E+10 | 0.138412E+10 | 0.295328E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 44287863.81 | 0.214098E+09 |
October | 0.150991E+10 | 0.156565E+10 | 0.306046E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16168730.43 | 0.697118E+09 |
November | 0.149516E+10 | 0.157391E+10 | 0.299314E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 929837.35 | 0.101044E+10 |
December | 0.145680E+10 | 0.159810E+10 | 0.300922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.172692E+10 |
Annual Sum or Average | 0.181194E+11 | 0.176434E+11 | 0.363654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.560214E+09 | 0.971114E+10 |
Minimum of Months | 0.136985E+10 | 0.129625E+10 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 85932060.34 |
Maximum of Months | 0.163685E+10 | 0.163281E+10 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.152060E+09 | 0.190401E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.715730E+09 | 0.100989E+10 | 0.197184E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.129399E+10 |
February | 0.649041E+09 | 0.915334E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1411073.03 | 0.110419E+10 |
March | 0.773965E+09 | 0.986649E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3994747.19 | 0.718482E+09 |
April | 0.688021E+09 | 0.856622E+09 | 0.190407E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7738401.72 | 0.451067E+09 |
May | 0.744847E+09 | 0.901322E+09 | 0.201177E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21031821.60 | 0.296463E+09 |
June | 0.742030E+09 | 0.886119E+09 | 0.197572E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 90737909.90 | 0.146646E+09 |
July | 0.690839E+09 | 0.840347E+09 | 0.193969E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 98648856.19 | 95841822.82 |
August | 0.773965E+09 | 0.948789E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 96891396.19 | 59247764.89 |
September | 0.688021E+09 | 0.879519E+09 | 0.190321E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 28045590.67 | 0.142391E+09 |
October | 0.715730E+09 | 0.966687E+09 | 0.197228E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7711151.99 | 0.480466E+09 |
November | 0.708685E+09 | 0.985860E+09 | 0.192889E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 550590.84 | 0.693749E+09 |
December | 0.690839E+09 | 0.986180E+09 | 0.193926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15698.23 | 0.116762E+10 |
Annual Sum or Average | 0.858171E+10 | 0.111633E+11 | 0.234352E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.356777E+09 | 0.665015E+10 |
Minimum of Months | 0.649041E+09 | 0.840347E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59247764.89 |
Maximum of Months | 0.773965E+09 | 0.100989E+10 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 98648856.19 | 0.129399E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150994E+10 | 0.151467E+10 | 0.305983E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.208251E+10 |
February | 0.136988E+10 | 0.139281E+10 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 191723.69 | 0.176988E+10 |
March | 0.163688E+10 | 0.153305E+10 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3508061.27 | 0.117818E+10 |
April | 0.145246E+10 | 0.133946E+10 | 0.295467E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8992357.79 | 0.696423E+09 |
May | 0.157341E+10 | 0.140845E+10 | 0.312179E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 31480345.01 | 0.434589E+09 |
June | 0.156904E+10 | 0.138378E+10 | 0.306585E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.137291E+09 | 0.211987E+09 |
July | 0.145684E+10 | 0.131584E+10 | 0.300994E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.147921E+09 | 0.140296E+09 |
August | 0.163688E+10 | 0.148015E+10 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.138420E+09 | 93690923.06 |
September | 0.145246E+10 | 0.137019E+10 | 0.295333E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 33882018.91 | 0.232481E+09 |
October | 0.150994E+10 | 0.148476E+10 | 0.306051E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5209991.58 | 0.798124E+09 |
November | 0.149520E+10 | 0.148021E+10 | 0.299318E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.116984E+10 |
December | 0.145684E+10 | 0.146964E+10 | 0.300927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.189215E+10 |
Annual Sum or Average | 0.181198E+11 | 0.171730E+11 | 0.363660E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.506896E+09 | 0.107001E+11 |
Minimum of Months | 0.136988E+10 | 0.131584E+10 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 93690923.06 |
Maximum of Months | 0.163688E+10 | 0.153305E+10 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.147921E+09 | 0.208251E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.101166E+10 | 0.197183E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.132885E+10 |
February | 0.882782E+09 | 0.929254E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1616975.14 | 0.113204E+10 |
March | 0.105485E+10 | 0.100366E+10 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2584508.70 | 0.770492E+09 |
April | 0.936002E+09 | 0.865094E+09 | 0.190406E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6953378.33 | 0.482279E+09 |
May | 0.101394E+10 | 0.906387E+09 | 0.201175E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20663468.98 | 0.309883E+09 |
June | 0.101113E+10 | 0.889258E+09 | 0.197570E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 87162730.41 | 0.159262E+09 |
July | 0.938820E+09 | 0.846935E+09 | 0.193968E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 94831823.78 | 0.105058E+09 |
August | 0.105485E+10 | 0.956355E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 89495916.23 | 74782601.94 |
September | 0.936002E+09 | 0.893970E+09 | 0.190319E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 26124917.96 | 0.156374E+09 |
October | 0.973041E+09 | 0.994877E+09 | 0.197226E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5967358.79 | 0.506638E+09 |
November | 0.963541E+09 | 0.977743E+09 | 0.192888E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.725781E+09 |
December | 0.938820E+09 | 0.983433E+09 | 0.193924E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.121369E+10 |
Annual Sum or Average | 0.116768E+11 | 0.112586E+11 | 0.234351E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.335401E+09 | 0.696512E+10 |
Minimum of Months | 0.882782E+09 | 0.846935E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 74782601.94 |
Maximum of Months | 0.105485E+10 | 0.101166E+10 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 94831823.78 | 0.132885E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150991E+10 | 0.163253E+10 | 0.305979E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.226724E+10 |
February | 0.136985E+10 | 0.147861E+10 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7890730.77 | 0.191893E+10 |
March | 0.163685E+10 | 0.155915E+10 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6925256.56 | 0.118972E+10 |
April | 0.145243E+10 | 0.133425E+10 | 0.295462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16824582.65 | 0.759529E+09 |
May | 0.157338E+10 | 0.138683E+10 | 0.312174E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 40787618.90 | 0.514544E+09 |
June | 0.156900E+10 | 0.136189E+10 | 0.306580E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.163939E+09 | 0.268014E+09 |
July | 0.145680E+10 | 0.129621E+10 | 0.300989E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.176552E+09 | 0.176301E+09 |
August | 0.163685E+10 | 0.147061E+10 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.172405E+09 | 0.112493E+09 |
September | 0.145243E+10 | 0.138411E+10 | 0.295328E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 52749913.82 | 0.250654E+09 |
October | 0.150991E+10 | 0.156494E+10 | 0.306046E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21973176.34 | 0.790676E+09 |
November | 0.149516E+10 | 0.157323E+10 | 0.299314E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4510173.26 | 0.113502E+10 |
December | 0.145680E+10 | 0.159788E+10 | 0.300922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 67616.00 | 0.198454E+10 |
Annual Sum or Average | 0.181194E+11 | 0.176402E+11 | 0.363654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.664625E+09 | 0.113677E+11 |
Minimum of Months | 0.136985E+10 | 0.129621E+10 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.112493E+09 |
Maximum of Months | 0.163685E+10 | 0.163253E+10 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.176552E+09 | 0.226724E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.100985E+10 | 0.197184E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.152700E+10 |
February | 0.882782E+09 | 0.914948E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2591352.44 | 0.130932E+10 |
March | 0.105485E+10 | 0.986409E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4882257.89 | 0.836878E+09 |
April | 0.936002E+09 | 0.856592E+09 | 0.190407E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8770595.79 | 0.532430E+09 |
May | 0.101394E+10 | 0.901263E+09 | 0.201177E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 24064274.18 | 0.363671E+09 |
June | 0.101113E+10 | 0.886119E+09 | 0.197572E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.107021E+09 | 0.185875E+09 |
July | 0.938820E+09 | 0.840205E+09 | 0.193969E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.115790E+09 | 0.121506E+09 |
August | 0.105485E+10 | 0.948730E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.113775E+09 | 77451441.88 |
September | 0.936002E+09 | 0.879472E+09 | 0.190321E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 33139732.04 | 0.169517E+09 |
October | 0.973041E+09 | 0.966567E+09 | 0.197228E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9824466.34 | 0.552912E+09 |
November | 0.963541E+09 | 0.985765E+09 | 0.192889E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2390178.40 | 0.784826E+09 |
December | 0.938820E+09 | 0.986046E+09 | 0.193926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2862.20 | 0.133264E+10 |
Annual Sum or Average | 0.116768E+11 | 0.111620E+11 | 0.234352E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.422251E+09 | 0.779403E+10 |
Minimum of Months | 0.882782E+09 | 0.840205E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 77451441.88 |
Maximum of Months | 0.105485E+10 | 0.100985E+10 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.115790E+09 | 0.152700E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150994E+10 | 0.151449E+10 | 0.305983E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.241732E+10 |
February | 0.136988E+10 | 0.139239E+10 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 201260.68 | 0.207901E+10 |
March | 0.163688E+10 | 0.153277E+10 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4150389.42 | 0.137141E+10 |
April | 0.145246E+10 | 0.133924E+10 | 0.295467E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10610695.71 | 0.813645E+09 |
May | 0.157341E+10 | 0.140845E+10 | 0.312179E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 36841778.18 | 0.526188E+09 |
June | 0.156904E+10 | 0.138356E+10 | 0.306585E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.163991E+09 | 0.265002E+09 |
July | 0.145684E+10 | 0.131564E+10 | 0.300994E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.175137E+09 | 0.175865E+09 |
August | 0.163688E+10 | 0.148013E+10 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.165140E+09 | 0.121127E+09 |
September | 0.145246E+10 | 0.137003E+10 | 0.295333E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 40602250.77 | 0.272972E+09 |
October | 0.150994E+10 | 0.148469E+10 | 0.306051E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6065262.70 | 0.919690E+09 |
November | 0.149520E+10 | 0.148007E+10 | 0.299318E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.132885E+10 |
December | 0.145684E+10 | 0.146956E+10 | 0.300927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.213638E+10 |
Annual Sum or Average | 0.181198E+11 | 0.171710E+11 | 0.363660E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.602740E+09 | 0.124275E+11 |
Minimum of Months | 0.136988E+10 | 0.131564E+10 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.121127E+09 |
Maximum of Months | 0.163688E+10 | 0.153277E+10 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.175137E+09 | 0.241732E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.101165E+10 | 0.197183E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.156195E+10 |
February | 0.882782E+09 | 0.929159E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2451607.15 | 0.134741E+10 |
March | 0.105485E+10 | 0.100346E+10 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3152611.10 | 0.907130E+09 |
April | 0.936002E+09 | 0.865048E+09 | 0.190406E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8521808.80 | 0.569673E+09 |
May | 0.101394E+10 | 0.906497E+09 | 0.201175E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 24812434.07 | 0.376774E+09 |
June | 0.101113E+10 | 0.889166E+09 | 0.197570E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.105350E+09 | 0.198258E+09 |
July | 0.938820E+09 | 0.846873E+09 | 0.193968E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.114046E+09 | 0.130628E+09 |
August | 0.105485E+10 | 0.956181E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.107888E+09 | 94814611.03 |
September | 0.936002E+09 | 0.893967E+09 | 0.190319E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 31960883.24 | 0.184975E+09 |
October | 0.973041E+09 | 0.994527E+09 | 0.197226E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7773898.91 | 0.589077E+09 |
November | 0.963541E+09 | 0.977696E+09 | 0.192888E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 25811.63 | 0.834272E+09 |
December | 0.938820E+09 | 0.983336E+09 | 0.193924E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.139403E+10 |
Annual Sum or Average | 0.116768E+11 | 0.112576E+11 | 0.234351E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.405983E+09 | 0.818900E+10 |
Minimum of Months | 0.882782E+09 | 0.846873E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 94814611.03 |
Maximum of Months | 0.105485E+10 | 0.101165E+10 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.114046E+09 | 0.156195E+10 |
Report: SpaceGainsMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.174411E+09 | 0.553024E+09 | 0.521915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.158233E+09 | 0.501634E+09 | 0.942813E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.189074E+09 | 0.596080E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.167772E+09 | 0.532421E+09 | 0.201821E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.181743E+09 | 0.574552E+09 | 0.522616E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.181238E+09 | 0.571774E+09 | 0.101086E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.168277E+09 | 0.535199E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.189074E+09 | 0.596080E+09 | 0.208555E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.167772E+09 | 0.532421E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.174411E+09 | 0.553024E+09 | 0.104453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.172708E+09 | 0.546542E+09 | 0.151524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.168277E+09 | 0.535199E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.209299E+10 | 0.662795E+10 | 0.153881E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.158233E+09 | 0.501634E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.189074E+09 | 0.596080E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.174411E+09 | 0.553024E+09 | 0.521915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.158233E+09 | 0.501634E+09 | 0.942813E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.189074E+09 | 0.596080E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.167772E+09 | 0.532421E+09 | 0.201821E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.181743E+09 | 0.574552E+09 | 0.522616E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.181238E+09 | 0.571774E+09 | 0.101086E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.168277E+09 | 0.535199E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.189074E+09 | 0.596080E+09 | 0.208555E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.167772E+09 | 0.532421E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.174411E+09 | 0.553024E+09 | 0.104453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.172708E+09 | 0.546542E+09 | 0.151524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.168277E+09 | 0.535199E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.209299E+10 | 0.662795E+10 | 0.153881E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.158233E+09 | 0.501634E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.189074E+09 | 0.596080E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.174411E+09 | 0.553024E+09 | 0.521915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.158233E+09 | 0.501634E+09 | 0.942813E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.189074E+09 | 0.596080E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.167772E+09 | 0.532421E+09 | 0.201821E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.181743E+09 | 0.574552E+09 | 0.522616E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.181238E+09 | 0.571774E+09 | 0.101086E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.168277E+09 | 0.535199E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.189074E+09 | 0.596080E+09 | 0.208555E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.167772E+09 | 0.532421E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.174411E+09 | 0.553024E+09 | 0.104453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.172708E+09 | 0.546542E+09 | 0.151524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.168277E+09 | 0.535199E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.209299E+10 | 0.662795E+10 | 0.153881E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.158233E+09 | 0.501634E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.189074E+09 | 0.596080E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.377547E+10 | 0.618367E+10 | 0.254202E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.342526E+10 | 0.560905E+10 | 0.459203E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.409289E+10 | 0.666512E+10 | 0.762947E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.363176E+10 | 0.595330E+10 | 0.982982E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.393418E+10 | 0.642439E+10 | 0.254544E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.392325E+10 | 0.639333E+10 | 0.492345E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.364269E+10 | 0.598436E+10 | 0.762947E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.409289E+10 | 0.666512E+10 | 0.101578E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.363176E+10 | 0.595330E+10 | 0.246344E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.377547E+10 | 0.618367E+10 | 0.508746E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.373861E+10 | 0.611120E+10 | 0.738006E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.364269E+10 | 0.598436E+10 | 0.101681E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.453069E+11 | 0.741109E+11 | 0.749486E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.342526E+10 | 0.560905E+10 | 0.246344E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.409289E+10 | 0.666512E+10 | 0.101681E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.210638E+10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 100294.51 | 0.179163E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2006555.40 | 0.116346E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6166342.42 | 0.693682E+09 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23510907.51 | 0.428281E+09 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.106370E+09 | 0.201599E+09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.124242E+09 | 0.126821E+09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.115203E+09 | 71202823.41 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28318173.24 | 0.229961E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4922915.38 | 0.789144E+09 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.116796E+10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.202070E+10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.410841E+09 | 0.107908E+11 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 71202823.41 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.124242E+09 | 0.210638E+10 |
Report: SpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.337170E+10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2439585.09 | 0.287469E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5060198.36 | 0.191158E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14947299.70 | 0.116050E+10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47552505.70 | 0.730562E+09 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.198605E+09 | 0.349472E+09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.228356E+09 | 0.225705E+09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.210828E+09 | 0.139007E+09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 56872091.53 | 0.383446E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13472605.07 | 0.129443E+10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 961807.57 | 0.188729E+10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.319475E+10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.779095E+09 | 0.175231E+11 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.139007E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.228356E+09 | 0.337170E+10 |
Report: SpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.341488E+10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2883919.90 | 0.296556E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3345712.65 | 0.199247E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7127160.41 | 0.124452E+10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27625936.85 | 0.818860E+09 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.176797E+09 | 0.395413E+09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.202975E+09 | 0.261722E+09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.192916E+09 | 0.164968E+09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46402936.34 | 0.398068E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9195120.03 | 0.131578E+10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2575902.35 | 0.186212E+10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.311870E+10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.671845E+09 | 0.179531E+11 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.164968E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.202975E+09 | 0.341488E+10 |
Report: PeakSpaceGainsMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 17832.21 | 02-JAN-10:09 | 22950.34 | 02-JAN-08:09 | 13457.54 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 17832.21 | 01-FEB-10:09 | 22950.34 | 01-FEB-08:09 | 13457.54 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 17832.21 | 01-MAR-10:09 | 22950.34 | 01-MAR-08:09 | 13457.54 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 17832.21 | 03-APR-09:09 | 22950.34 | 03-APR-07:10 | 13457.54 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 17832.21 | 01-MAY-09:09 | 22950.34 | 01-MAY-07:10 | 13457.54 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 17832.21 | 01-JUN-09:09 | 22950.34 | 01-JUN-07:10 | 13457.54 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 17832.21 | 03-JUL-09:09 | 22950.34 | 03-JUL-07:10 | 13457.54 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 17832.21 | 01-AUG-09:09 | 22950.34 | 01-AUG-07:10 | 13457.54 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 17832.21 | 01-SEP-09:09 | 22950.34 | 01-SEP-07:10 | 13457.54 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 17832.21 | 02-OCT-09:09 | 22950.34 | 02-OCT-07:10 | 13457.54 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 17832.21 | 01-NOV-09:09 | 22950.34 | 01-NOV-07:10 | 13457.54 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 17832.21 | 01-DEC-10:09 | 22950.34 | 01-DEC-08:09 | 13457.54 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 17832.21 | 22950.34 | 13457.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 17832.21 | 22950.34 | 13457.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 16014.58 | 02-JAN-10:09 | 20611.01 | 02-JAN-08:09 | 17206.63 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 16014.58 | 01-FEB-10:09 | 20611.01 | 01-FEB-08:09 | 17206.63 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 16014.58 | 01-MAR-10:09 | 20611.01 | 01-MAR-08:09 | 17206.63 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 16014.58 | 03-APR-09:09 | 20611.01 | 03-APR-07:10 | 17206.63 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 16014.58 | 01-MAY-09:09 | 20611.01 | 01-MAY-07:10 | 17206.63 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 16014.58 | 01-JUN-09:09 | 20611.01 | 01-JUN-07:10 | 17206.63 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 16014.58 | 03-JUL-09:09 | 20611.01 | 03-JUL-07:10 | 17206.63 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 16014.58 | 01-AUG-09:09 | 20611.01 | 01-AUG-07:10 | 17206.63 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 16014.58 | 01-SEP-09:09 | 20611.01 | 01-SEP-07:10 | 17206.63 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 16014.58 | 02-OCT-09:09 | 20611.01 | 02-OCT-07:10 | 17206.63 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 16014.58 | 01-NOV-09:09 | 20611.01 | 01-NOV-07:10 | 17206.63 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 16014.58 | 01-DEC-10:09 | 20611.01 | 01-DEC-08:09 | 17206.63 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 16014.58 | 20611.01 | 17206.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 16014.58 | 20611.01 | 17206.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 16014.58 | 02-JAN-10:09 | 20611.01 | 02-JAN-08:09 | 17206.56 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 16014.58 | 01-FEB-10:09 | 20611.01 | 01-FEB-08:09 | 17206.56 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 16014.58 | 01-MAR-10:09 | 20611.01 | 01-MAR-08:09 | 17206.56 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 16014.58 | 03-APR-09:09 | 20611.01 | 03-APR-07:10 | 17206.56 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 16014.58 | 01-MAY-09:09 | 20611.01 | 01-MAY-07:10 | 17206.56 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 16014.58 | 01-JUN-09:09 | 20611.01 | 01-JUN-07:10 | 17206.56 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 16014.58 | 03-JUL-09:09 | 20611.01 | 03-JUL-07:10 | 17206.56 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 16014.58 | 01-AUG-09:09 | 20611.01 | 01-AUG-07:10 | 17206.56 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 16014.58 | 01-SEP-09:09 | 20611.01 | 01-SEP-07:10 | 17206.56 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 16014.58 | 02-OCT-09:09 | 20611.01 | 02-OCT-07:10 | 17206.56 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 16014.58 | 01-NOV-09:09 | 20611.01 | 01-NOV-07:10 | 17206.56 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 16014.58 | 01-DEC-10:09 | 20611.01 | 01-DEC-08:09 | 17206.56 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 16014.58 | 20611.01 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 16014.58 | 20611.01 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 16014.58 | 02-JAN-10:09 | 20611.01 | 02-JAN-08:09 | 17206.56 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 16014.58 | 01-FEB-10:09 | 20611.01 | 01-FEB-08:09 | 17206.56 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 16014.58 | 01-MAR-10:09 | 20611.01 | 01-MAR-08:09 | 17206.56 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 16014.58 | 03-APR-09:09 | 20611.01 | 03-APR-07:10 | 17206.56 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 16014.58 | 01-MAY-09:09 | 20611.01 | 01-MAY-07:10 | 17206.56 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 16014.58 | 01-JUN-09:09 | 20611.01 | 01-JUN-07:10 | 17206.56 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 16014.58 | 03-JUL-09:09 | 20611.01 | 03-JUL-07:10 | 17206.56 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 16014.58 | 01-AUG-09:09 | 20611.01 | 01-AUG-07:10 | 17206.56 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 16014.58 | 01-SEP-09:09 | 20611.01 | 01-SEP-07:10 | 17206.56 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 16014.58 | 02-OCT-09:09 | 20611.01 | 02-OCT-07:10 | 17206.56 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 16014.58 | 01-NOV-09:09 | 20611.01 | 01-NOV-07:10 | 17206.56 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 16014.58 | 01-DEC-10:09 | 20611.01 | 01-DEC-08:09 | 17206.56 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 16014.58 | 20611.01 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 16014.58 | 20611.01 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.79 | 02-JAN-10:09 | 2587.92 | 03-JAN-08:09 | 2160.55 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 1685.23 | 07-JAN-18:10 |
February | 2010.79 | 01-FEB-10:09 | 2587.92 | 01-FEB-08:09 | 2160.55 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 45.67 | 26-FEB-14:50 | 2061.67 | 12-FEB-01:00 |
March | 2010.79 | 01-MAR-10:09 | 2587.92 | 21-MAR-07:10 | 2160.55 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 46.44 | 30-MAR-16:00 | 1357.21 | 22-MAR-03:00 |
April | 2010.79 | 03-APR-09:09 | 2255.20 | 03-APR-07:10 | 2160.55 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 79.82 | 16-APR-12:10 | 708.61 | 05-APR-04:53 |
May | 2010.79 | 01-MAY-09:09 | 1470.28 | 02-MAY-07:10 | 2160.55 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 108.30 | 07-MAY-12:10 | 540.55 | 10-MAY-04:00 |
June | 2010.79 | 01-JUN-09:09 | 1470.28 | 23-JUN-07:10 | 2160.55 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 320.83 | 11-JUN-15:00 | 394.38 | 07-JUN-03:00 |
July | 2010.79 | 03-JUL-09:09 | 1803.00 | 27-JUL-07:10 | 2160.55 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 308.83 | 08-JUL-18:53 | 293.54 | 28-JUL-22:00 |
August | 2010.79 | 01-AUG-09:09 | 2255.20 | 24-AUG-07:10 | 2160.55 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 317.55 | 06-AUG-14:00 | 157.48 | 31-AUG-05:00 |
September | 2010.79 | 01-SEP-09:09 | 2587.92 | 29-SEP-07:10 | 2160.55 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 124.85 | 17-SEP-15:00 | 372.63 | 29-SEP-05:00 |
October | 2010.79 | 02-OCT-09:09 | 2587.92 | 19-OCT-07:10 | 2160.55 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 102.61 | 08-OCT-14:00 | 806.07 | 28-OCT-04:00 |
November | 2010.79 | 01-NOV-09:09 | 2587.92 | 01-NOV-07:10 | 2160.55 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 29.89 | 19-NOV-15:00 | 1151.13 | 21-NOV-04:00 |
December | 2010.79 | 01-DEC-10:09 | 2587.92 | 06-DEC-08:09 | 2160.55 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 2016.81 | 17-DEC-03:53 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.79 | 1470.28 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 157.48 | |||||
Maximum of Months | 2010.79 | 2587.92 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 320.83 | 2061.67 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 1667.75 | 03-JAN-08:09 | 1392.34 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 1108.49 | 07-JAN-18:10 |
February | 1295.83 | 01-FEB-10:09 | 1667.75 | 01-FEB-08:09 | 1392.34 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 25.76 | 26-FEB-15:10 | 1358.90 | 12-FEB-01:00 |
March | 1295.83 | 01-MAR-10:09 | 1667.75 | 21-MAR-07:10 | 1392.34 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 34.91 | 11-MAR-18:20 | 869.81 | 22-MAR-03:00 |
April | 1295.83 | 03-APR-09:09 | 1453.34 | 03-APR-07:10 | 1392.34 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 43.34 | 02-APR-16:55 | 449.71 | 05-APR-04:53 |
May | 1295.83 | 01-MAY-09:09 | 870.51 | 02-MAY-07:10 | 1392.34 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 71.52 | 21-MAY-17:00 | 357.62 | 10-MAY-04:00 |
June | 1295.83 | 01-JUN-09:09 | 793.52 | 01-JUN-07:10 | 1392.34 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 211.02 | 11-JUN-15:00 | 259.45 | 07-JUN-03:00 |
July | 1295.83 | 03-JUL-09:09 | 947.51 | 27-JUL-07:10 | 1392.34 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 221.99 | 08-JUL-18:53 | 180.74 | 28-JUL-22:00 |
August | 1295.83 | 01-AUG-09:09 | 1453.34 | 24-AUG-07:10 | 1392.34 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 216.34 | 06-AUG-14:00 | 84.27 | 31-AUG-05:00 |
September | 1295.83 | 01-SEP-09:09 | 1453.34 | 05-SEP-07:10 | 1392.34 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 98.93 | 17-SEP-14:50 | 240.97 | 29-SEP-05:00 |
October | 1295.83 | 02-OCT-09:09 | 1667.75 | 19-OCT-07:10 | 1392.34 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 65.08 | 09-OCT-15:40 | 520.54 | 28-OCT-04:00 |
November | 1295.83 | 01-NOV-09:09 | 1667.75 | 01-NOV-07:10 | 1392.34 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 47.16 | 19-NOV-15:00 | 752.02 | 21-NOV-04:00 |
December | 1295.83 | 01-DEC-10:09 | 1667.75 | 06-DEC-08:09 | 1392.34 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1306.99 | 17-DEC-03:53 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 793.52 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 84.27 | |||||
Maximum of Months | 1295.83 | 1667.75 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 221.99 | 1358.90 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.83 | 02-JAN-10:09 | 2587.98 | 03-JAN-08:09 | 2160.58 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 1672.08 | 07-JAN-18:03 |
February | 2010.83 | 01-FEB-10:09 | 2587.98 | 01-FEB-08:09 | 2160.58 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 18.55 | 28-FEB-15:00 | 2047.61 | 11-FEB-18:55 |
March | 2010.83 | 01-MAR-10:09 | 2587.98 | 21-MAR-07:10 | 2160.58 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 46.44 | 30-MAR-16:00 | 1305.05 | 22-MAR-03:00 |
April | 2010.83 | 03-APR-09:09 | 2255.25 | 03-APR-07:10 | 2160.58 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 39.19 | 16-APR-14:08 | 692.45 | 05-APR-04:53 |
May | 2010.83 | 01-MAY-09:09 | 1803.04 | 24-MAY-07:10 | 2160.58 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 88.38 | 29-MAY-18:00 | 534.66 | 10-MAY-04:00 |
June | 2010.83 | 01-JUN-09:09 | 1470.31 | 23-JUN-07:10 | 2160.58 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 313.68 | 11-JUN-15:00 | 392.48 | 07-JUN-03:00 |
July | 2010.83 | 03-JUL-09:09 | 1803.04 | 27-JUL-07:10 | 2160.58 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 303.55 | 08-JUL-18:53 | 289.68 | 28-JUL-22:00 |
August | 2010.83 | 01-AUG-09:09 | 2255.25 | 24-AUG-07:10 | 2160.58 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 295.04 | 06-AUG-13:55 | 160.84 | 31-AUG-05:00 |
September | 2010.83 | 01-SEP-09:09 | 2587.98 | 29-SEP-07:10 | 2160.58 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 80.71 | 17-SEP-14:50 | 361.70 | 29-SEP-05:00 |
October | 2010.83 | 02-OCT-09:09 | 2587.98 | 19-OCT-07:10 | 2160.58 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 43.80 | 09-OCT-15:36 | 800.20 | 28-OCT-04:00 |
November | 2010.83 | 01-NOV-09:09 | 2587.98 | 01-NOV-07:10 | 2160.58 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1171.32 | 07-NOV-02:00 |
December | 2010.83 | 01-DEC-10:09 | 2587.98 | 06-DEC-08:09 | 2160.58 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1950.16 | 17-DEC-03:53 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.83 | 1470.31 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 160.84 | |||||
Maximum of Months | 2010.83 | 2587.98 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 313.68 | 2047.61 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 1667.75 | 03-JAN-08:09 | 1392.33 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 1160.85 | 07-JAN-18:10 |
February | 1295.83 | 01-FEB-10:09 | 1667.75 | 01-FEB-08:09 | 1392.33 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 14.12 | 26-FEB-13:10 | 1480.06 | 11-FEB-18:13 |
March | 1295.83 | 01-MAR-10:09 | 1667.75 | 16-MAR-07:10 | 1392.33 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 30.96 | 30-MAR-16:00 | 1005.27 | 22-MAR-03:00 |
April | 1295.83 | 03-APR-09:09 | 1453.34 | 03-APR-07:10 | 1392.33 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 36.10 | 16-APR-12:10 | 537.95 | 05-APR-04:53 |
May | 1295.83 | 01-MAY-09:09 | 1453.34 | 24-MAY-07:10 | 1392.33 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 80.12 | 07-MAY-12:10 | 390.11 | 10-MAY-04:00 |
June | 1295.83 | 01-JUN-09:09 | 1161.92 | 23-JUN-07:10 | 1392.33 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 181.99 | 25-JUN-16:00 | 305.79 | 07-JUN-03:00 |
July | 1295.83 | 03-JUL-09:09 | 1453.34 | 27-JUL-07:10 | 1392.33 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 176.35 | 08-JUL-18:50 | 234.58 | 28-JUL-22:00 |
August | 1295.83 | 01-AUG-09:09 | 1453.34 | 23-AUG-07:10 | 1392.33 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 196.98 | 06-AUG-13:55 | 152.35 | 31-AUG-05:00 |
September | 1295.83 | 01-SEP-09:09 | 1667.75 | 29-SEP-07:10 | 1392.33 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 78.65 | 17-SEP-12:10 | 270.84 | 30-SEP-19:00 |
October | 1295.83 | 02-OCT-09:09 | 1667.75 | 13-OCT-07:10 | 1392.33 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 32.93 | 09-OCT-14:56 | 599.63 | 28-OCT-04:00 |
November | 1295.83 | 01-NOV-09:09 | 1667.75 | 01-NOV-07:10 | 1392.33 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 859.44 | 07-NOV-02:00 |
December | 1295.83 | 01-DEC-10:09 | 1667.75 | 06-DEC-08:09 | 1392.33 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1485.47 | 17-DEC-03:53 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 1161.92 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 152.35 | |||||
Maximum of Months | 1295.83 | 1667.75 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 196.98 | 1485.47 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.79 | 02-JAN-10:09 | 2587.92 | 03-JAN-08:09 | 2160.55 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 3716.07 | 07-JAN-05:10 |
February | 2010.79 | 01-FEB-10:09 | 2587.92 | 01-FEB-08:09 | 2160.55 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 283.66 | 26-FEB-12:54 | 4433.01 | 12-FEB-01:00 |
March | 2010.79 | 01-MAR-10:09 | 2587.92 | 21-MAR-07:10 | 2160.55 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 162.34 | 11-MAR-18:03 | 2696.49 | 22-MAR-04:55 |
April | 2010.79 | 03-APR-09:09 | 2255.20 | 03-APR-07:10 | 2160.55 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 256.98 | 16-APR-12:00 | 1467.65 | 05-APR-04:53 |
May | 2010.79 | 01-MAY-09:09 | 1470.28 | 02-MAY-07:10 | 2160.55 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 300.72 | 07-MAY-11:53 | 1154.15 | 10-MAY-04:00 |
June | 2010.79 | 01-JUN-09:09 | 1470.28 | 23-JUN-07:10 | 2160.55 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 782.79 | 11-JUN-14:52 | 851.92 | 07-JUN-03:00 |
July | 2010.79 | 03-JUL-09:09 | 1803.00 | 27-JUL-07:10 | 2160.55 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 718.90 | 08-JUL-18:53 | 605.70 | 28-JUL-22:00 |
August | 2010.79 | 01-AUG-09:09 | 2255.20 | 24-AUG-07:10 | 2160.55 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 765.69 | 06-AUG-14:00 | 396.75 | 25-AUG-05:00 |
September | 2010.79 | 01-SEP-09:09 | 2587.92 | 29-SEP-07:10 | 2160.55 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 319.07 | 17-SEP-15:00 | 777.07 | 29-SEP-05:00 |
October | 2010.79 | 02-OCT-09:09 | 2587.92 | 19-OCT-07:10 | 2160.55 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 361.03 | 08-OCT-13:52 | 1542.77 | 28-OCT-04:00 |
November | 2010.79 | 01-NOV-09:09 | 2587.92 | 01-NOV-07:10 | 2160.55 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 160.64 | 19-NOV-14:55 | 2548.62 | 30-NOV-22:03 |
December | 2010.79 | 01-DEC-10:09 | 2587.92 | 06-DEC-08:09 | 2160.55 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 3746.34 | 17-DEC-03:53 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.79 | 1470.28 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 396.75 | |||||
Maximum of Months | 2010.79 | 2587.92 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 782.79 | 4433.01 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1239.33 | 02-JAN-08:09 | 1667.75 | 03-JAN-08:09 | 1392.34 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 2477.43 | 07-JAN-05:09 |
February | 1239.33 | 01-FEB-08:09 | 1667.75 | 01-FEB-08:09 | 1392.34 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 121.37 | 26-FEB-16:00 | 2955.49 | 12-FEB-01:00 |
March | 1239.33 | 01-MAR-08:09 | 1667.75 | 21-MAR-07:10 | 1392.34 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 116.58 | 11-MAR-18:03 | 1797.78 | 22-MAR-04:57 |
April | 1239.33 | 03-APR-07:10 | 1453.34 | 03-APR-07:10 | 1392.34 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 122.39 | 08-APR-17:10 | 972.55 | 05-APR-04:53 |
May | 1239.33 | 01-MAY-07:10 | 870.51 | 02-MAY-07:10 | 1392.34 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 167.15 | 29-MAY-18:00 | 773.13 | 10-MAY-04:00 |
June | 1239.33 | 01-JUN-07:10 | 793.52 | 01-JUN-07:10 | 1392.34 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 489.63 | 11-JUN-15:10 | 580.42 | 07-JUN-03:00 |
July | 1239.33 | 03-JUL-07:10 | 947.51 | 27-JUL-07:10 | 1392.34 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 498.72 | 08-JUL-18:53 | 396.27 | 01-JUL-20:00 |
August | 1239.33 | 01-AUG-07:10 | 1453.34 | 24-AUG-07:10 | 1392.34 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 475.00 | 06-AUG-14:00 | 257.72 | 25-AUG-05:00 |
September | 1239.33 | 01-SEP-07:10 | 1453.34 | 05-SEP-07:10 | 1392.34 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 236.58 | 17-SEP-15:20 | 507.28 | 29-SEP-05:00 |
October | 1239.33 | 02-OCT-07:10 | 1667.75 | 19-OCT-07:10 | 1392.34 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 192.02 | 09-OCT-15:50 | 1021.76 | 28-OCT-04:00 |
November | 1239.33 | 01-NOV-07:10 | 1667.75 | 01-NOV-07:10 | 1392.34 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 86.10 | 19-NOV-14:55 | 1697.50 | 30-NOV-22:03 |
December | 1239.33 | 01-DEC-08:09 | 1667.75 | 06-DEC-08:09 | 1392.34 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4.75 | 12-DEC-15:00 | 2494.57 | 17-DEC-03:53 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1239.33 | 793.52 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 257.72 | |||||
Maximum of Months | 1239.33 | 1667.75 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 498.72 | 2955.49 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.83 | 02-JAN-10:09 | 2587.98 | 03-JAN-08:09 | 2160.58 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 3716.15 | 07-JAN-05:09 |
February | 2010.83 | 01-FEB-10:09 | 2587.98 | 01-FEB-08:09 | 2160.58 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 38.76 | 28-FEB-15:00 | 4516.17 | 11-FEB-18:03 |
March | 2010.83 | 01-MAR-10:09 | 2587.98 | 21-MAR-07:10 | 2160.58 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 105.78 | 30-MAR-16:00 | 2696.55 | 22-MAR-04:57 |
April | 2010.83 | 03-APR-09:09 | 2255.25 | 03-APR-07:10 | 2160.58 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 96.86 | 08-APR-17:10 | 1478.01 | 05-APR-04:53 |
May | 2010.83 | 01-MAY-09:09 | 1803.04 | 24-MAY-07:10 | 2160.58 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 223.56 | 07-MAY-12:00 | 1172.73 | 10-MAY-04:00 |
June | 2010.83 | 01-JUN-09:09 | 1470.31 | 23-JUN-07:10 | 2160.58 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 731.61 | 11-JUN-15:10 | 857.88 | 07-JUN-03:00 |
July | 2010.83 | 03-JUL-09:09 | 1803.04 | 27-JUL-07:10 | 2160.58 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 701.95 | 08-JUL-18:53 | 609.42 | 28-JUL-22:00 |
August | 2010.83 | 01-AUG-09:09 | 2255.25 | 24-AUG-07:10 | 2160.58 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 679.56 | 06-AUG-13:55 | 406.90 | 25-AUG-05:00 |
September | 2010.83 | 01-SEP-09:09 | 2587.98 | 29-SEP-07:10 | 2160.58 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 158.82 | 06-SEP-12:00 | 782.78 | 29-SEP-05:00 |
October | 2010.83 | 02-OCT-09:09 | 2587.98 | 19-OCT-07:10 | 2160.58 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 93.08 | 09-OCT-15:45 | 1650.75 | 28-OCT-04:00 |
November | 2010.83 | 01-NOV-09:09 | 2587.98 | 01-NOV-07:10 | 2160.58 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 2550.07 | 30-NOV-22:03 |
December | 2010.83 | 01-DEC-10:09 | 2587.98 | 06-DEC-08:09 | 2160.58 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 3883.45 | 17-DEC-03:53 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.83 | 1470.31 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 406.90 | |||||
Maximum of Months | 2010.83 | 2587.98 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 731.61 | 4516.17 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 1667.75 | 03-JAN-08:09 | 1392.33 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 2477.44 | 07-JAN-05:10 |
February | 1295.83 | 01-FEB-10:09 | 1667.75 | 01-FEB-08:09 | 1392.33 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 184.25 | 26-FEB-12:52 | 3134.22 | 11-FEB-18:03 |
March | 1295.83 | 01-MAR-10:09 | 1667.75 | 16-MAR-07:10 | 1392.33 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 70.52 | 30-MAR-16:00 | 1797.67 | 22-MAR-04:57 |
April | 1295.83 | 03-APR-09:09 | 1453.34 | 03-APR-07:10 | 1392.33 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 169.24 | 16-APR-12:00 | 997.43 | 05-APR-04:53 |
May | 1295.83 | 01-MAY-09:09 | 1453.34 | 24-MAY-07:19 | 1392.33 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 228.23 | 07-MAY-11:53 | 808.93 | 10-MAY-04:00 |
June | 1295.83 | 01-JUN-09:09 | 1161.92 | 23-JUN-07:10 | 1392.33 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 426.97 | 11-JUN-15:05 | 605.57 | 07-JUN-03:00 |
July | 1295.83 | 03-JUL-09:09 | 1453.34 | 27-JUL-07:10 | 1392.33 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 429.56 | 08-JUL-19:10 | 414.68 | 28-JUL-22:00 |
August | 1295.83 | 01-AUG-09:09 | 1453.34 | 23-AUG-07:10 | 1392.33 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 490.26 | 06-AUG-14:00 | 287.13 | 25-AUG-05:00 |
September | 1295.83 | 01-SEP-09:09 | 1667.75 | 29-SEP-07:10 | 1392.33 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 215.91 | 17-SEP-12:00 | 515.43 | 29-SEP-05:00 |
October | 1295.83 | 02-OCT-09:09 | 1667.75 | 13-OCT-07:10 | 1392.33 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 163.74 | 08-OCT-13:52 | 1073.41 | 28-OCT-04:00 |
November | 1295.83 | 01-NOV-09:09 | 1667.75 | 01-NOV-07:10 | 1392.33 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1702.70 | 30-NOV-22:03 |
December | 1295.83 | 01-DEC-10:09 | 1667.75 | 06-DEC-08:09 | 1392.33 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 2576.22 | 17-DEC-03:53 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 1161.92 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 287.13 | |||||
Maximum of Months | 1295.83 | 1667.75 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 490.26 | 3134.22 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.79 | 02-JAN-10:09 | 2587.92 | 03-JAN-08:09 | 2160.55 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 4443.61 | 07-JAN-05:10 |
February | 2010.79 | 01-FEB-10:09 | 2587.92 | 01-FEB-08:09 | 2160.55 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 470.09 | 26-FEB-13:00 | 5527.79 | 12-FEB-01:00 |
March | 2010.79 | 01-MAR-10:09 | 2587.92 | 21-MAR-07:10 | 2160.55 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 223.50 | 11-MAR-18:03 | 3373.98 | 22-MAR-04:57 |
April | 2010.79 | 03-APR-09:09 | 2255.20 | 03-APR-07:10 | 2160.55 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 323.21 | 16-APR-11:58 | 1710.67 | 05-APR-04:53 |
May | 2010.79 | 01-MAY-09:09 | 1470.28 | 02-MAY-07:10 | 2160.55 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 318.50 | 07-MAY-12:00 | 1321.73 | 10-MAY-04:00 |
June | 2010.79 | 01-JUN-09:09 | 1470.28 | 23-JUN-07:10 | 2160.55 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 914.17 | 11-JUN-15:00 | 1043.53 | 07-JUN-03:00 |
July | 2010.79 | 03-JUL-09:09 | 1803.00 | 27-JUL-07:10 | 2160.55 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 791.98 | 08-JUL-18:53 | 719.81 | 01-JUL-20:00 |
August | 2010.79 | 01-AUG-09:09 | 2255.20 | 24-AUG-07:10 | 2160.55 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 857.29 | 06-AUG-14:00 | 473.70 | 25-AUG-05:00 |
September | 2010.79 | 01-SEP-09:09 | 2587.92 | 29-SEP-07:10 | 2160.55 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 374.78 | 17-SEP-14:50 | 871.08 | 29-SEP-04:53 |
October | 2010.79 | 02-OCT-09:09 | 2587.92 | 19-OCT-07:10 | 2160.55 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 491.43 | 08-OCT-14:00 | 1757.76 | 25-OCT-05:00 |
November | 2010.79 | 01-NOV-09:09 | 2587.92 | 01-NOV-07:10 | 2160.55 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 429.29 | 19-NOV-14:55 | 3154.69 | 30-NOV-22:03 |
December | 2010.79 | 01-DEC-10:09 | 2587.92 | 06-DEC-08:09 | 2160.55 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 28.88 | 10-DEC-15:40 | 4452.92 | 17-DEC-04:07 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.79 | 1470.28 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 473.70 | |||||
Maximum of Months | 2010.79 | 2587.92 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 914.17 | 5527.79 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 1667.75 | 03-JAN-08:09 | 1392.34 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 3092.27 | 07-JAN-05:09 |
February | 1295.83 | 01-FEB-10:09 | 1667.75 | 01-FEB-08:09 | 1392.34 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 193.79 | 26-FEB-15:42 | 3684.86 | 12-FEB-01:00 |
March | 1295.83 | 01-MAR-10:09 | 1667.75 | 21-MAR-07:10 | 1392.34 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 154.86 | 11-MAR-18:03 | 2249.35 | 22-MAR-04:57 |
April | 1295.83 | 03-APR-09:09 | 1453.34 | 03-APR-07:10 | 1392.34 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 138.28 | 08-APR-17:10 | 1135.26 | 05-APR-04:53 |
May | 1295.83 | 01-MAY-09:09 | 870.51 | 02-MAY-07:10 | 1392.34 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 181.94 | 29-MAY-17:42 | 888.24 | 10-MAY-04:00 |
June | 1295.83 | 01-JUN-09:09 | 793.52 | 01-JUN-07:10 | 1392.34 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 562.59 | 11-JUN-15:30 | 713.07 | 07-JUN-03:00 |
July | 1295.83 | 03-JUL-09:09 | 947.51 | 27-JUL-07:10 | 1392.34 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 554.28 | 08-JUL-18:50 | 511.27 | 01-JUL-20:00 |
August | 1295.83 | 01-AUG-09:09 | 1453.34 | 24-AUG-07:10 | 1392.34 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 561.94 | 06-AUG-13:50 | 308.55 | 25-AUG-05:00 |
September | 1295.83 | 01-SEP-09:09 | 1453.34 | 05-SEP-07:10 | 1392.34 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 279.43 | 17-SEP-14:50 | 571.82 | 29-SEP-04:53 |
October | 1295.83 | 02-OCT-09:09 | 1667.75 | 19-OCT-07:10 | 1392.34 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 233.00 | 09-OCT-15:40 | 1171.73 | 25-OCT-04:57 |
November | 1295.83 | 01-NOV-09:09 | 1667.75 | 01-NOV-07:10 | 1392.34 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 260.36 | 19-NOV-14:55 | 2100.64 | 30-NOV-22:03 |
December | 1295.83 | 01-DEC-10:09 | 1667.75 | 06-DEC-08:09 | 1392.34 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 12-DEC-14:00 | 2985.05 | 17-DEC-04:07 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 793.52 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 308.55 | |||||
Maximum of Months | 1295.83 | 1667.75 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 562.59 | 3684.86 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.83 | 02-JAN-10:09 | 2587.98 | 03-JAN-08:09 | 2160.58 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 4606.01 | 07-JAN-05:10 |
February | 2010.83 | 01-FEB-10:09 | 2587.98 | 01-FEB-08:09 | 2160.58 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 42.25 | 28-FEB-15:00 | 5527.34 | 12-FEB-01:00 |
March | 2010.83 | 01-MAR-10:09 | 2587.98 | 21-MAR-07:10 | 2160.58 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 127.46 | 30-MAR-16:00 | 3374.17 | 22-MAR-05:00 |
April | 2010.83 | 03-APR-09:09 | 2255.25 | 03-APR-07:10 | 2160.58 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 115.43 | 08-APR-17:10 | 1721.91 | 05-APR-04:53 |
May | 2010.83 | 01-MAY-09:09 | 1803.04 | 24-MAY-07:10 | 2160.58 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 250.37 | 07-MAY-12:20 | 1345.19 | 10-MAY-04:00 |
June | 2010.83 | 01-JUN-09:09 | 1470.31 | 23-JUN-07:10 | 2160.58 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 877.46 | 11-JUN-15:00 | 1051.10 | 07-JUN-03:00 |
July | 2010.83 | 03-JUL-09:09 | 1803.04 | 27-JUL-07:10 | 2160.58 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 787.38 | 08-JUL-18:53 | 721.06 | 01-JUL-20:00 |
August | 2010.83 | 01-AUG-09:09 | 2255.25 | 24-AUG-07:10 | 2160.58 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 829.16 | 06-AUG-13:55 | 485.56 | 25-AUG-05:00 |
September | 2010.83 | 01-SEP-09:09 | 2587.98 | 29-SEP-07:10 | 2160.58 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 196.03 | 17-SEP-14:50 | 876.98 | 29-SEP-04:53 |
October | 2010.83 | 02-OCT-09:09 | 2587.98 | 19-OCT-07:10 | 2160.58 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 102.19 | 10-OCT-16:00 | 1856.72 | 28-OCT-04:00 |
November | 2010.83 | 01-NOV-09:09 | 2587.98 | 01-NOV-07:10 | 2160.58 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 3156.42 | 30-NOV-22:03 |
December | 2010.83 | 01-DEC-10:09 | 2587.98 | 06-DEC-08:09 | 2160.58 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 4466.65 | 17-DEC-04:07 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.83 | 1470.31 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 485.56 | |||||
Maximum of Months | 2010.83 | 2587.98 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 877.46 | 5527.34 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 1667.75 | 03-JAN-08:09 | 1392.33 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 3092.20 | 07-JAN-05:10 |
February | 1295.83 | 01-FEB-10:09 | 1667.75 | 01-FEB-08:09 | 1392.33 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 286.93 | 26-FEB-13:00 | 3782.41 | 11-FEB-18:03 |
March | 1295.83 | 01-MAR-10:09 | 1667.75 | 16-MAR-07:10 | 1392.33 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 84.97 | 30-MAR-16:00 | 2249.50 | 22-MAR-05:00 |
April | 1295.83 | 03-APR-09:09 | 1453.34 | 03-APR-07:10 | 1392.33 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 212.74 | 16-APR-11:58 | 1166.87 | 05-APR-04:53 |
May | 1295.83 | 01-MAY-09:09 | 1453.34 | 24-MAY-07:19 | 1392.33 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 265.14 | 07-MAY-12:00 | 935.43 | 10-MAY-04:00 |
June | 1295.83 | 01-JUN-09:09 | 1161.92 | 23-JUN-07:10 | 1392.33 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 512.53 | 25-JUN-16:00 | 741.10 | 07-JUN-03:00 |
July | 1295.83 | 03-JUL-09:09 | 1453.34 | 27-JUL-07:10 | 1392.33 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 496.48 | 08-JUL-19:10 | 502.53 | 01-JUL-20:00 |
August | 1295.83 | 01-AUG-09:09 | 1453.34 | 23-AUG-07:10 | 1392.33 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 570.29 | 06-AUG-13:55 | 344.58 | 25-AUG-05:00 |
September | 1295.83 | 01-SEP-09:09 | 1667.75 | 29-SEP-07:10 | 1392.33 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 276.73 | 17-SEP-12:10 | 587.15 | 29-SEP-04:53 |
October | 1295.83 | 02-OCT-09:09 | 1667.75 | 13-OCT-07:10 | 1392.33 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 226.36 | 08-OCT-13:52 | 1217.47 | 28-OCT-04:00 |
November | 1295.83 | 01-NOV-09:09 | 1667.75 | 01-NOV-07:10 | 1392.33 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 35.72 | 11-NOV-13:00 | 2109.90 | 30-NOV-22:03 |
December | 1295.83 | 01-DEC-10:09 | 1667.75 | 06-DEC-08:09 | 1392.33 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 2962.33 | 17-DEC-04:07 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 1161.92 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 344.58 | |||||
Maximum of Months | 1295.83 | 1667.75 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 570.29 | 3782.41 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 232.27 | 02-JAN-10:09 | 578.72 | 02-JAN-08:09 | 1948.61 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 232.27 | 01-FEB-10:09 | 578.72 | 01-FEB-08:09 | 3897.21 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 232.27 | 01-MAR-10:09 | 578.72 | 01-MAR-08:09 | 7794.42 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 232.27 | 03-APR-09:09 | 578.72 | 03-APR-07:10 | 7794.42 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 232.27 | 01-MAY-09:09 | 578.72 | 01-MAY-07:10 | 3897.21 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 232.27 | 01-JUN-09:09 | 578.72 | 01-JUN-07:10 | 5845.82 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 232.27 | 03-JUL-09:09 | 578.72 | 03-JUL-07:10 | 7794.42 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 232.27 | 01-AUG-09:09 | 578.72 | 01-AUG-07:10 | 7794.42 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 232.27 | 01-SEP-09:09 | 578.72 | 01-SEP-07:10 | 3897.21 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 232.27 | 02-OCT-09:09 | 578.72 | 02-OCT-07:10 | 5845.82 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 232.27 | 01-NOV-09:09 | 578.72 | 01-NOV-07:10 | 5845.82 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 232.27 | 01-DEC-10:09 | 578.72 | 01-DEC-08:09 | 7794.42 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 232.27 | 578.72 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 232.27 | 578.72 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 232.27 | 02-JAN-10:09 | 578.72 | 02-JAN-08:09 | 1948.61 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 232.27 | 01-FEB-10:09 | 578.72 | 01-FEB-08:09 | 3897.21 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 232.27 | 01-MAR-10:09 | 578.72 | 01-MAR-08:09 | 7794.42 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 232.27 | 03-APR-09:09 | 578.72 | 03-APR-07:10 | 7794.42 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 232.27 | 01-MAY-09:09 | 578.72 | 01-MAY-07:10 | 3897.21 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 232.27 | 01-JUN-09:09 | 578.72 | 01-JUN-07:10 | 5845.82 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 232.27 | 03-JUL-09:09 | 578.72 | 03-JUL-07:10 | 7794.42 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 232.27 | 01-AUG-09:09 | 578.72 | 01-AUG-07:10 | 7794.42 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 232.27 | 01-SEP-09:09 | 578.72 | 01-SEP-07:10 | 3897.21 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 232.27 | 02-OCT-09:09 | 578.72 | 02-OCT-07:10 | 5845.82 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 232.27 | 01-NOV-09:09 | 578.72 | 01-NOV-07:10 | 5845.82 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 232.27 | 01-DEC-10:09 | 578.72 | 01-DEC-08:09 | 7794.42 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 232.27 | 578.72 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 232.27 | 578.72 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 232.27 | 02-JAN-10:09 | 578.72 | 02-JAN-08:09 | 1948.61 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 232.27 | 01-FEB-10:09 | 578.72 | 01-FEB-08:09 | 3897.21 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 232.27 | 01-MAR-10:09 | 578.72 | 01-MAR-08:09 | 7794.42 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 232.27 | 03-APR-09:09 | 578.72 | 03-APR-07:10 | 7794.42 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 232.27 | 01-MAY-09:09 | 578.72 | 01-MAY-07:10 | 3897.21 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 232.27 | 01-JUN-09:09 | 578.72 | 01-JUN-07:10 | 5845.82 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 232.27 | 03-JUL-09:09 | 578.72 | 03-JUL-07:10 | 7794.42 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 232.27 | 01-AUG-09:09 | 578.72 | 01-AUG-07:10 | 7794.42 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 232.27 | 01-SEP-09:09 | 578.72 | 01-SEP-07:10 | 3897.21 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 232.27 | 02-OCT-09:09 | 578.72 | 02-OCT-07:10 | 5845.82 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 232.27 | 01-NOV-09:09 | 578.72 | 01-NOV-07:10 | 5845.82 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 232.27 | 01-DEC-10:09 | 578.72 | 01-DEC-08:09 | 7794.42 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 232.27 | 578.72 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 232.27 | 578.72 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 5027.92 | 02-JAN-10:09 | 6471.01 | 02-JAN-08:09 | 94908.13 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 5027.92 | 01-FEB-10:09 | 6471.01 | 01-FEB-08:09 | 189816.26 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 5027.92 | 01-MAR-10:09 | 6471.01 | 01-MAR-08:09 | 379632.52 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 5027.92 | 03-APR-09:09 | 6471.01 | 03-APR-07:10 | 379632.52 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 5027.92 | 01-MAY-09:09 | 6471.01 | 01-MAY-07:10 | 189816.26 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5027.92 | 01-JUN-09:09 | 6471.01 | 01-JUN-07:10 | 284724.39 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 5027.92 | 03-JUL-09:09 | 6471.01 | 03-JUL-07:10 | 379632.52 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 5027.92 | 01-AUG-09:09 | 6471.01 | 01-AUG-07:10 | 379632.52 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 5027.92 | 01-SEP-09:09 | 6471.01 | 01-SEP-07:10 | 189816.26 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 5027.92 | 02-OCT-09:09 | 6471.01 | 02-OCT-07:10 | 284724.39 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5027.92 | 01-NOV-09:09 | 6471.01 | 01-NOV-07:10 | 284724.39 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 5027.92 | 01-DEC-10:09 | 6471.01 | 01-DEC-08:09 | 379632.52 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 5027.92 | 6471.01 | 94908.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 5027.92 | 6471.01 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 3762.98 | 07-JAN-18:03 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.95 | 26-FEB-14:52 | 4705.26 | 12-FEB-01:00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 73.55 | 30-MAR-16:00 | 3019.75 | 22-MAR-03:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 123.95 | 16-APR-13:52 | 1541.92 | 05-APR-04:57 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 209.21 | 07-MAY-11:53 | 1209.99 | 10-MAY-04:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 647.00 | 11-JUN-15:00 | 833.00 | 07-JUN-03:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 630.84 | 08-JUL-18:53 | 601.71 | 28-JUL-24:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 676.01 | 06-AUG-14:00 | 360.91 | 25-AUG-04:53 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 232.85 | 17-SEP-15:00 | 836.04 | 29-SEP-05:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 132.19 | 09-OCT-16:00 | 1769.90 | 28-OCT-04:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 2587.53 | 21-NOV-04:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 4553.54 | 17-DEC-03:53 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 360.91 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 676.01 | 4705.26 |
Report: PeakSpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 6390.87 | 07-JAN-18:03 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 177.11 | 26-FEB-15:00 | 7771.87 | 12-FEB-01:00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 168.15 | 11-MAR-16:00 | 4958.96 | 22-MAR-03:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 298.41 | 16-APR-12:00 | 2623.93 | 05-APR-04:53 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 428.89 | 07-MAY-12:10 | 2120.10 | 10-MAY-04:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1271.62 | 11-JUN-14:52 | 1444.00 | 07-JUN-03:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1168.22 | 08-JUL-18:53 | 1036.34 | 28-JUL-22:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1260.00 | 06-AUG-14:00 | 689.35 | 25-AUG-05:00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 482.31 | 17-SEP-15:00 | 1458.73 | 29-SEP-05:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 375.89 | 09-OCT-16:00 | 2934.26 | 28-OCT-04:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 223.12 | 19-NOV-14:55 | 4358.14 | 21-NOV-04:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 7423.67 | 17-DEC-03:53 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 689.35 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1271.62 | 7771.87 |
Report: PeakSpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 7063.63 | 07-JAN-18:03 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 213.36 | 26-FEB-13:13 | 8388.46 | 11-FEB-18:03 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 157.01 | 11-MAR-16:00 | 4822.65 | 22-MAR-05:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 223.37 | 16-APR-11:53 | 2764.26 | 05-APR-04:53 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 276.54 | 29-MAY-18:00 | 2092.49 | 10-MAY-04:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1087.20 | 11-JUN-15:00 | 1628.97 | 07-JUN-03:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1073.99 | 08-JUL-18:53 | 1128.03 | 01-JUL-20:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1035.65 | 06-AUG-14:00 | 731.62 | 23-AUG-05:00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 330.92 | 17-SEP-15:00 | 1359.63 | 29-SEP-04:53 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 314.49 | 08-OCT-14:00 | 2920.15 | 28-OCT-04:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 483.24 | 19-NOV-14:55 | 4564.25 | 30-NOV-22:03 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 7008.81 | 17-DEC-03:53 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 731.62 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1087.20 | 8388.46 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 117755.26 | 02-JAN-05:11 | 0.00 | 25501.32 | 134575.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 119279.88 | 21-FEB-05:11 | 0.00 | 20401.06 | 107660.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 116375.27 | 06-MAR-05:11 | 0.00 | 20401.06 | 107660.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 113953.56 | 10-APR-04:12 | 0.00 | 15300.79 | 80745.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 112130.78 | 15-MAY-04:12 | 0.00 | 10200.53 | 53830.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 111458.60 | 08-JUN-04:12 | 0.00 | 12750.66 | 67287.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 97170.68 | 03-JUL-04:23 | 0.00 | 7650.40 | 40372.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 93509.31 | 26-AUG-04:12 | 0.00 | 5099.69 | 53830.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 113311.09 | 14-SEP-04:12 | 0.00 | 12750.66 | 67287.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 120516.13 | 30-OCT-04:11 | 0.00 | 17850.93 | 94202.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 117080.44 | 06-NOV-05:12 | 0.00 | 15300.79 | 80745.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 119360.14 | 11-DEC-05:11 | 0.00 | 25501.32 | 134575.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 93509.31 | 0.00 | 5099.69 | 40372.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 120516.13 | 0.00 | 25501.32 | 134575.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 92999.03 | 02-JAN-05:11 | 0.00 | 22901.98 | 59376.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 92429.04 | 21-FEB-05:11 | 0.00 | 18321.59 | 47501.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 93461.30 | 06-MAR-05:11 | 0.00 | 18321.59 | 47501.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 95150.35 | 14-APR-04:13 | 0.00 | 16031.39 | 41563.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 99086.11 | 30-MAY-04:13 | 0.00 | 13741.19 | 35625.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 99664.12 | 20-JUN-04:13 | 0.00 | 16031.39 | 41563.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 99025.80 | 01-JUL-04:13 | 0.00 | 8014.80 | 31172.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 81011.87 | 31-AUG-04:22 | 0.00 | 11450.99 | 29688.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 99855.04 | 11-SEP-04:13 | 0.00 | 13741.19 | 35625.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 97918.84 | 10-OCT-04:13 | 0.00 | 13741.19 | 35625.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 98819.34 | 13-NOV-05:11 | 0.00 | 20611.78 | 53438.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 94600.23 | 26-DEC-05:11 | 0.00 | 22901.98 | 59376.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 81011.87 | 0.00 | 8014.80 | 29688.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 99855.04 | 0.00 | 22901.98 | 59376.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 71873.87 | 26-JAN-10:20 | 80072.90 | 103055.07 | 86032.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 76309.38 | 28-FEB-06:02 | 8061.19 | 11450.99 | 38236.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 83953.56 | 31-MAR-04:12 | 0.00 | 13741.19 | 35625.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 84631.49 | 19-APR-04:12 | 0.00 | 13741.19 | 35625.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 85174.37 | 31-MAY-04:12 | 0.00 | 11450.99 | 29688.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 86897.76 | 21-JUN-04:11 | 0.00 | 16031.39 | 41563.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 86779.77 | 28-JUL-04:11 | 0.00 | 16031.39 | 41563.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 85261.99 | 25-AUG-04:12 | 0.00 | 9160.79 | 23750.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 86625.46 | 01-SEP-04:11 | 0.00 | 16031.39 | 41563.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 84030.19 | 19-OCT-04:12 | 0.00 | 13741.19 | 35625.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 78394.66 | 10-NOV-06:02 | 8061.19 | 11450.99 | 38236.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 67912.21 | 14-DEC-06:03 | 6448.95 | 9160.79 | 30589.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 67912.21 | 0.00 | 9160.79 | 23750.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 86897.76 | 80072.90 | 103055.07 | 86032.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 25778.01 | 20-JAN-17:00 | 15316.26 | 20611.01 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 35768.98 | 28-FEB-17:00 | 15316.26 | 20611.01 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 81761.47 | 31-MAR-05:02 | 8061.19 | 11450.99 | 38236.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 81878.24 | 19-APR-05:02 | 8061.19 | 11450.99 | 38236.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 84727.51 | 19-MAY-04:12 | 0.00 | 11450.99 | 29688.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 86137.86 | 16-JUN-04:11 | 0.00 | 16031.39 | 41563.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 85688.56 | 12-JUL-04:12 | 0.00 | 13741.19 | 35625.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 84538.62 | 03-AUG-03:02 | 0.00 | 5724.85 | 29688.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 84678.66 | 06-SEP-04:12 | 0.00 | 13741.19 | 35625.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 83441.85 | 19-OCT-04:12 | 0.00 | 13741.19 | 35625.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 36812.64 | 04-NOV-05:03 | 6448.95 | 9160.79 | 30589.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 32397.60 | 13-DEC-17:00 | 15316.26 | 20611.01 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 25778.01 | 0.00 | 5724.85 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 86137.86 | 15316.26 | 20611.01 | 41563.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3668.86 | 31-JAN-15:00 | 2010.79 | 1350.81 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.97 |
February | 6320.36 | 28-FEB-15:00 | 2010.79 | 1231.33 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 18.55 | 0.00 |
March | 7908.17 | 30-MAR-14:00 | 2010.79 | 1231.33 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 36.77 | 0.00 |
April | 8497.66 | 18-APR-14:00 | 2010.79 | 1231.33 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 8.20 | 0.00 |
May | 13285.93 | 30-MAY-04:12 | 0.00 | 1725.34 | 4473.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 76.70 |
June | 13741.55 | 20-JUN-04:11 | 0.00 | 2012.90 | 5218.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 124.15 |
July | 14292.00 | 17-JUL-04:12 | 0.00 | 1725.34 | 4473.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37.68 |
August | 13219.63 | 21-AUG-05:02 | 1214.60 | 1725.34 | 5761.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.06 |
September | 13968.24 | 01-SEP-04:11 | 0.00 | 2012.90 | 5218.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 83.71 |
October | 13350.02 | 19-OCT-04:12 | 0.00 | 1725.34 | 4473.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 123.01 |
November | 5928.28 | 02-NOV-13:50 | 2010.79 | 1231.33 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.33 |
December | 5562.81 | 13-DEC-12:00 | 1923.11 | 1231.33 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.75 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3668.86 | 0.00 | 1231.33 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 14292.00 | 2010.79 | 2012.90 | 5761.47 | 0.00 | 0.00 | 0.00 | 0.00 | 36.77 | 124.15 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3174.77 | 24-JAN-10:30 | 1295.83 | 793.52 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 94.66 |
February | 7192.47 | 27-FEB-09:40 | 1239.33 | 793.52 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 63.24 |
March | 8589.53 | 26-MAR-10:23 | 260.91 | 176.32 | 1856.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 152.21 |
April | 16930.54 | 16-APR-10:43 | 260.91 | 176.32 | 1856.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.54 |
May | 17635.52 | 29-MAY-09:43 | 260.91 | 176.32 | 1856.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.49 |
June | 20029.05 | 04-JUN-09:02 | 391.37 | 264.49 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.97 |
July | 19452.84 | 23-JUL-09:22 | 326.14 | 220.40 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.17 |
August | 18414.67 | 13-AUG-08:32 | 260.91 | 176.32 | 1856.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.95 |
September | 18504.47 | 24-SEP-09:02 | 260.91 | 176.32 | 1856.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.01 |
October | 14006.48 | 09-OCT-10:13 | 260.91 | 176.32 | 1856.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 63.94 |
November | 6772.69 | 06-NOV-09:25 | 2478.65 | 1587.03 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 62.39 |
December | 3613.65 | 08-DEC-10:10 | 2591.66 | 1587.03 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 188.97 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3174.77 | 260.91 | 176.32 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.54 | |
Maximum of Months | 20029.05 | 2591.66 | 1587.03 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 188.97 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 17701.14 | 29-JAN-13:33 | 303.66 | 205.21 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 454.28 |
February | 22138.58 | 26-FEB-13:42 | 506.09 | 342.02 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 132.22 |
March | 20528.88 | 26-MAR-13:32 | 404.87 | 273.61 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 282.81 |
April | 15180.48 | 16-APR-13:23 | 404.87 | 273.61 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 25.39 | 0.00 |
May | 15204.67 | 30-MAY-04:12 | 0.00 | 1725.38 | 4473.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 75.39 |
June | 15823.54 | 19-JUN-04:12 | 0.00 | 1725.38 | 4473.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 99.37 |
July | 17838.08 | 16-JUL-15:12 | 607.31 | 410.42 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 158.25 | 0.00 |
August | 21366.56 | 20-AUG-13:42 | 506.09 | 342.02 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 66.88 | 0.00 |
September | 21393.16 | 24-SEP-11:43 | 404.87 | 273.61 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 23.17 | 0.00 |
October | 22775.91 | 09-OCT-14:12 | 607.31 | 410.42 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.49 |
November | 22385.03 | 12-NOV-14:12 | 506.09 | 342.02 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 129.27 |
December | 21271.55 | 10-DEC-12:43 | 404.87 | 273.61 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 172.85 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 15180.48 | 0.00 | 205.21 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 22775.91 | 607.31 | 1725.38 | 4473.43 | 0.00 | 0.00 | 0.00 | 0.00 | 158.25 | 454.28 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 5620.44 | 23-JAN-16:30 | 1239.33 | 793.52 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 104.29 |
February | 20885.02 | 26-FEB-15:42 | 326.14 | 220.40 | 2320.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57.62 |
March | 19572.29 | 30-MAR-04:12 | 0.00 | 1111.88 | 2882.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 141.24 |
April | 24158.98 | 09-APR-16:32 | 391.37 | 264.49 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41.12 |
May | 23702.32 | 29-MAY-15:42 | 326.14 | 220.40 | 2320.55 | 0.00 | 0.00 | 0.00 | 0.00 | 20.75 | 0.00 |
June | 25886.29 | 11-JUN-15:51 | 456.59 | 308.57 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 106.69 | 0.00 |
July | 24824.01 | 09-JUL-16:41 | 456.59 | 308.57 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 100.20 | 0.00 |
August | 25616.70 | 13-AUG-16:31 | 456.59 | 308.57 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 42.03 | 0.00 |
September | 23593.98 | 04-SEP-17:02 | 0.00 | 220.40 | 1801.74 | 0.00 | 0.00 | 0.00 | 0.00 | 9.43 | 0.00 |
October | 23735.94 | 22-OCT-15:32 | 326.14 | 220.40 | 2320.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 77.29 |
November | 19654.22 | 12-NOV-14:52 | 326.14 | 220.40 | 2320.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 66.62 |
December | 19745.06 | 13-DEC-05:12 | 0.00 | 1111.88 | 2882.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 149.67 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 5620.44 | 0.00 | 220.40 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 25886.29 | 1239.33 | 1111.88 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 106.69 | 149.67 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2808.25 | 31-JAN-17:00 | 1923.11 | 1803.00 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 49.75 |
February | 4000.67 | 28-FEB-15:00 | 2010.79 | 1231.33 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 38.76 | 0.00 |
March | 6550.97 | 30-MAR-15:50 | 1923.11 | 1231.33 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 104.55 | 0.00 |
April | 7130.54 | 19-APR-14:30 | 1923.11 | 1231.33 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 48.91 | 0.00 |
May | 8887.42 | 30-MAY-15:00 | 1923.11 | 1231.33 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 92.33 | 0.00 |
June | 16382.18 | 25-JUN-16:11 | 809.73 | 547.22 | 5761.47 | 0.00 | 0.00 | 0.00 | 0.00 | 584.57 | 0.00 |
July | 15604.29 | 16-JUL-13:32 | 404.87 | 273.61 | 2880.74 | 0.00 | 0.00 | 0.00 | 0.00 | 320.40 | 0.00 |
August | 12602.33 | 16-AUG-04:12 | 0.00 | 1437.79 | 3727.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 80.60 |
September | 11781.71 | 11-SEP-05:02 | 1012.16 | 1437.79 | 4801.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.61 |
October | 6438.44 | 02-OCT-14:30 | 1923.11 | 1231.33 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 53.21 | 0.00 |
November | 3736.19 | 20-NOV-14:20 | 2010.79 | 1231.33 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 557.09 |
December | 3058.81 | 13-DEC-15:10 | 1923.11 | 1470.28 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 68.08 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2808.25 | 0.00 | 273.61 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 16382.18 | 2010.79 | 1803.00 | 5761.47 | 0.00 | 0.00 | 0.00 | 0.00 | 584.57 | 557.09 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2772.50 | 11-JAN-10:15 | 0.00 | 1587.03 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 145.49 |
February | 4966.52 | 27-FEB-10:00 | 1239.33 | 793.52 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 130.58 |
March | 6442.37 | 13-MAR-10:20 | 1239.33 | 793.52 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 89.95 |
April | 18169.77 | 16-APR-10:53 | 260.91 | 176.32 | 1856.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.00 |
May | 20007.62 | 07-MAY-09:02 | 326.14 | 220.40 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 188.28 |
June | 20935.64 | 04-JUN-09:52 | 391.37 | 264.49 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37.13 |
July | 20750.77 | 04-JUL-09:42 | 391.37 | 264.49 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36.84 |
August | 21300.62 | 27-AUG-09:41 | 456.59 | 308.57 | 3248.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.68 |
September | 19578.18 | 24-SEP-10:12 | 326.14 | 220.40 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.55 |
October | 7520.66 | 11-OCT-10:10 | 1239.33 | 793.52 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.46 |
November | 4173.29 | 06-NOV-09:50 | 1239.33 | 793.52 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 152.35 |
December | 2801.80 | 07-DEC-10:25 | 0.00 | 1587.03 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 229.35 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2772.50 | 0.00 | 176.32 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.46 | |
Maximum of Months | 21300.62 | 1239.33 | 1587.03 | 3248.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 229.35 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 16657.78 | 29-JAN-13:33 | 303.66 | 205.21 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1073.94 |
February | 20383.11 | 26-FEB-12:32 | 404.87 | 273.61 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 412.42 |
March | 15754.79 | 26-MAR-15:02 | 404.87 | 273.61 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 673.17 |
April | 20019.47 | 16-APR-13:32 | 404.87 | 273.61 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 57.26 | 0.00 |
May | 13733.47 | 29-MAY-14:12 | 506.09 | 342.02 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 40.91 | 0.00 |
June | 19529.11 | 25-JUN-16:11 | 809.75 | 547.23 | 5761.56 | 0.00 | 0.00 | 0.00 | 0.00 | 572.26 | 0.00 |
July | 18774.53 | 16-JUL-12:53 | 404.87 | 273.61 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 438.56 | 0.00 |
August | 20200.24 | 27-AUG-13:02 | 404.87 | 273.61 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 332.55 | 0.00 |
September | 21219.76 | 24-SEP-12:52 | 506.09 | 342.02 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 65.93 | 0.00 |
October | 21657.50 | 08-OCT-14:02 | 506.09 | 342.02 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 123.41 |
November | 20724.89 | 11-NOV-12:02 | 404.87 | 273.61 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 613.03 |
December | 20524.72 | 10-DEC-13:43 | 404.87 | 273.61 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 386.88 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 13733.47 | 303.66 | 205.21 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 21657.50 | 809.75 | 547.23 | 5761.56 | 0.00 | 0.00 | 0.00 | 0.00 | 572.26 | 1073.94 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3098.85 | 10-JAN-17:33 | 1174.10 | 2779.57 | 2320.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 152.21 |
February | 7654.55 | 27-FEB-17:00 | 1239.33 | 793.52 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.89 |
March | 10689.31 | 30-MAR-16:00 | 1239.33 | 793.52 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 70.52 | 0.00 |
April | 20108.12 | 09-APR-17:12 | 0.00 | 264.49 | 2162.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 103.25 |
May | 21588.44 | 21-MAY-17:22 | 0.00 | 264.49 | 2162.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 131.84 |
June | 22533.81 | 25-JUN-16:11 | 521.82 | 352.65 | 3712.89 | 0.00 | 0.00 | 0.00 | 0.00 | 261.66 | 0.00 |
July | 22898.99 | 23-JUL-17:11 | 0.00 | 352.65 | 2882.79 | 0.00 | 0.00 | 0.00 | 0.00 | 41.88 | 0.00 |
August | 22052.04 | 27-AUG-16:21 | 456.59 | 308.57 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 159.02 | 0.00 |
September | 18045.08 | 24-SEP-16:52 | 391.37 | 264.49 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 19.20 | 0.00 |
October | 15664.16 | 08-OCT-16:42 | 391.37 | 264.49 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.53 |
November | 7067.99 | 06-NOV-16:00 | 1239.33 | 793.52 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 77.92 |
December | 3795.86 | 11-DEC-15:50 | 1239.33 | 793.52 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.81 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3098.85 | 0.00 | 264.49 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 22898.99 | 1239.33 | 2779.57 | 3712.89 | 0.00 | 0.00 | 0.00 | 0.00 | 261.66 | 152.21 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2864.31 | 20-JAN-16:20 | 1923.11 | 1350.81 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 167.27 |
February | 3698.96 | 28-FEB-15:30 | 1923.11 | 1231.33 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.99 |
March | 7383.83 | 30-MAR-15:50 | 1923.11 | 1231.33 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 125.98 | 0.00 |
April | 7765.51 | 19-APR-14:30 | 1923.11 | 1231.33 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 57.48 | 0.00 |
May | 10007.14 | 30-MAY-15:00 | 1923.11 | 1231.33 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 112.71 | 0.00 |
June | 19367.51 | 25-JUN-16:11 | 809.73 | 547.22 | 5761.47 | 0.00 | 0.00 | 0.00 | 0.00 | 639.73 | 0.00 |
July | 18821.52 | 16-JUL-13:32 | 404.87 | 273.61 | 2880.74 | 0.00 | 0.00 | 0.00 | 0.00 | 376.92 | 0.00 |
August | 17489.10 | 06-AUG-16:21 | 708.51 | 478.82 | 5041.29 | 0.00 | 0.00 | 0.00 | 0.00 | 616.77 | 0.00 |
September | 13376.24 | 07-SEP-05:02 | 1012.16 | 1437.79 | 4801.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.26 |
October | 6815.16 | 02-OCT-14:40 | 1923.11 | 1231.33 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 67.59 | 0.00 |
November | 3267.42 | 02-NOV-15:50 | 1923.11 | 1350.81 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 48.22 |
December | 3080.28 | 13-DEC-15:10 | 1923.11 | 1470.28 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 83.73 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2864.31 | 404.87 | 273.61 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 19367.51 | 1923.11 | 1470.28 | 5761.47 | 0.00 | 0.00 | 0.00 | 0.00 | 639.73 | 167.27 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2573.30 | 31-JAN-15:00 | 1295.83 | 793.52 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.47 |
February | 3534.90 | 27-FEB-10:40 | 1295.83 | 793.52 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 130.39 |
March | 6076.56 | 30-MAR-11:00 | 1239.33 | 793.52 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.68 |
April | 9778.77 | 14-APR-09:50 | 1295.83 | 793.52 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36.71 |
May | 20211.71 | 07-MAY-09:12 | 326.14 | 220.40 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 226.80 |
June | 20031.35 | 25-JUN-08:52 | 326.14 | 220.40 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.23 |
July | 20519.48 | 23-JUL-08:32 | 326.14 | 220.40 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 162.05 |
August | 21239.66 | 27-AUG-09:12 | 391.37 | 264.49 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.78 |
September | 19734.57 | 04-SEP-09:22 | 326.14 | 220.40 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 49.58 |
October | 7336.15 | 11-OCT-10:20 | 1239.33 | 793.52 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.15 |
November | 3026.61 | 06-NOV-10:30 | 1295.83 | 793.52 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 195.06 |
December | 2736.13 | 13-DEC-15:00 | 1295.83 | 947.51 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 48.84 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2573.30 | 326.14 | 220.40 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.15 | |
Maximum of Months | 21239.66 | 1295.83 | 947.51 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 226.80 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 10410.02 | 11-JAN-14:30 | 2010.83 | 1231.36 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 197.56 |
February | 20795.67 | 26-FEB-14:52 | 506.09 | 342.02 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 164.91 |
March | 16303.50 | 30-MAR-13:40 | 2010.83 | 1231.36 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 90.74 | 0.00 |
April | 13433.31 | 17-APR-14:00 | 2010.83 | 1231.36 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 34.71 | 0.00 |
May | 19059.69 | 29-MAY-14:12 | 506.09 | 342.02 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 47.01 | 0.00 |
June | 22332.85 | 25-JUN-16:11 | 809.75 | 547.23 | 5761.56 | 0.00 | 0.00 | 0.00 | 0.00 | 638.82 | 0.00 |
July | 21566.38 | 16-JUL-12:53 | 404.87 | 273.61 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 521.67 | 0.00 |
August | 22170.38 | 13-AUG-13:32 | 404.87 | 273.61 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 198.72 | 0.00 |
September | 21990.46 | 24-SEP-11:43 | 404.87 | 273.61 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 73.57 | 0.00 |
October | 23882.86 | 09-OCT-14:12 | 607.31 | 410.42 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 69.37 |
November | 22888.93 | 11-NOV-14:52 | 506.09 | 342.02 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 625.99 |
December | 12346.79 | 08-DEC-14:10 | 2010.83 | 1231.36 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 498.06 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 10410.02 | 404.87 | 273.61 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 23882.86 | 2010.83 | 1231.36 | 5761.56 | 0.00 | 0.00 | 0.00 | 0.00 | 638.82 | 625.99 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3209.56 | 20-JAN-16:40 | 1239.33 | 793.52 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 115.26 |
February | 7566.54 | 27-FEB-17:00 | 1239.33 | 793.52 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.29 |
March | 11234.20 | 30-MAR-16:00 | 1239.33 | 793.52 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 84.97 | 0.00 |
April | 19237.61 | 09-APR-16:52 | 326.14 | 220.40 | 2320.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 110.25 |
May | 23134.91 | 21-MAY-17:22 | 0.00 | 264.49 | 2162.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 176.92 |
June | 24611.65 | 25-JUN-16:11 | 521.82 | 352.65 | 3712.89 | 0.00 | 0.00 | 0.00 | 0.00 | 293.10 | 0.00 |
July | 24417.85 | 23-JUL-17:11 | 0.00 | 352.65 | 2882.79 | 0.00 | 0.00 | 0.00 | 0.00 | 26.76 | 0.00 |
August | 23215.85 | 13-AUG-16:51 | 456.59 | 308.57 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 134.65 | 0.00 |
September | 21909.53 | 04-SEP-17:02 | 0.00 | 220.40 | 1801.74 | 0.00 | 0.00 | 0.00 | 0.00 | 22.84 | 0.00 |
October | 13150.64 | 09-OCT-16:12 | 326.14 | 220.40 | 2320.55 | 0.00 | 0.00 | 0.00 | 0.00 | 22.96 | 0.00 |
November | 6783.81 | 06-NOV-16:00 | 1239.33 | 793.52 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 99.75 |
December | 3407.64 | 11-DEC-16:00 | 1239.33 | 793.52 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41.59 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3209.56 | 0.00 | 220.40 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 24611.65 | 1239.33 | 793.52 | 3712.89 | 0.00 | 0.00 | 0.00 | 0.00 | 293.10 | 176.92 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 6219.40 | 26-JAN-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 549.74 |
February | 6470.40 | 03-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 606.37 |
March | 6396.08 | 30-MAR-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 69.27 | 0.00 |
April | 8171.25 | 17-APR-15:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36.30 | 0.00 |
May | 10357.53 | 30-MAY-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40.01 |
June | 10971.43 | 19-JUN-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41.77 |
July | 9808.26 | 11-JUL-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36.13 |
August | 9341.17 | 09-AUG-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.12 |
September | 12621.66 | 05-SEP-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 55.25 |
October | 7619.75 | 10-OCT-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 98.62 |
November | 5756.34 | 13-NOV-06:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 332.01 |
December | 4734.13 | 14-DEC-06:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 320.45 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 4734.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 12621.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 69.27 | 606.37 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 7752.41 | 14-JAN-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4461.77 |
February | 10065.98 | 12-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7191.38 |
March | 5778.49 | 18-MAR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 789.89 |
April | 6755.79 | 06-APR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 512.78 |
May | 5712.45 | 19-MAY-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 6550.65 | 29-JUN-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 228.58 | 0.00 |
July | 9678.85 | 06-JUL-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.45 |
August | 10025.13 | 21-AUG-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 69.90 |
September | 6588.09 | 07-SEP-15:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 152.26 | 0.00 |
October | 5286.34 | 13-OCT-05:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 8582.94 | 22-NOV-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2887.12 |
December | 8534.89 | 01-DEC-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3037.56 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 5286.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 10065.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 228.58 | 7191.38 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2551.06 | 31-JAN-13:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 169.25 |
February | 6092.74 | 28-FEB-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 109.84 |
March | 13188.41 | 30-MAR-14:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 80.68 | 0.00 |
April | 16036.76 | 17-APR-14:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 52.77 | 0.00 |
May | 17025.88 | 16-MAY-15:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.24 | 0.00 |
June | 17712.03 | 13-JUN-13:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 86.46 | 0.00 |
July | 19740.61 | 07-JUL-15:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 110.69 | 0.00 |
August | 19476.71 | 01-AUG-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 195.94 | 0.00 |
September | 16381.49 | 06-SEP-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 129.92 | 0.00 |
October | 12040.27 | 10-OCT-14:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 75.77 | 0.00 |
November | 5430.44 | 05-NOV-14:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 49.95 |
December | 3283.85 | 12-DEC-13:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 130.49 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 2551.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 19740.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 195.94 | 169.25 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 1910.36 | 23-JAN-17:00 | 222.14 | 578.72 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 4019.05 | 24-FEB-17:50 | 70.15 | 321.51 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 7150.58 | 31-MAR-24:00 | 0.00 | 32.15 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 7933.39 | 09-APR-18:15 | 0.00 | 128.61 | 31177.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 3485.90 | 31-MAY-24:00 | 0.00 | 32.15 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5395.09 | 30-JUN-24:00 | 0.00 | 32.15 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 7228.22 | 31-JUL-24:00 | 0.00 | 64.31 | 15588.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 7907.71 | 13-AUG-19:23 | 0.00 | 128.61 | 31177.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 3184.82 | 30-SEP-24:00 | 0.00 | 32.15 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 5103.99 | 31-OCT-24:00 | 0.00 | 32.15 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6014.36 | 06-NOV-17:00 | 222.14 | 578.72 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 7807.88 | 19-DEC-17:00 | 222.14 | 578.72 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 1910.36 | 0.00 | 32.15 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 7933.39 | 222.14 | 578.72 | 31177.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 1529.00 | 27-JAN-17:00 | 222.14 | 578.72 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 3714.21 | 24-FEB-17:50 | 70.15 | 321.51 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6627.55 | 31-MAR-23:50 | 0.00 | 32.15 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 7466.89 | 14-APR-18:30 | 23.38 | 192.90 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 3251.71 | 31-MAY-24:00 | 0.00 | 32.15 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5116.08 | 30-JUN-24:00 | 0.00 | 32.15 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6975.71 | 31-JUL-24:00 | 0.00 | 64.31 | 15588.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 7433.26 | 13-AUG-18:37 | 0.00 | 192.92 | 46766.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 2580.47 | 30-SEP-24:00 | 0.00 | 32.15 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 4300.80 | 31-OCT-23:50 | 0.00 | 32.15 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5573.89 | 06-NOV-17:00 | 222.14 | 578.72 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 7147.65 | 08-DEC-17:00 | 222.14 | 578.72 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 1529.00 | 0.00 | 32.15 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 7466.89 | 222.14 | 578.72 | 46766.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 1506.78 | 20-JAN-17:00 | 222.14 | 578.72 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 3666.30 | 28-FEB-17:00 | 222.14 | 578.72 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6362.44 | 31-MAR-23:20 | 0.00 | 32.15 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 7550.07 | 14-APR-18:30 | 23.38 | 192.90 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 3207.37 | 31-MAY-24:00 | 0.00 | 32.15 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5077.78 | 30-JUN-24:00 | 0.00 | 32.15 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 7019.30 | 31-JUL-24:00 | 0.00 | 64.31 | 15588.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 7660.98 | 13-AUG-18:52 | 0.00 | 160.76 | 38972.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 2084.04 | 08-SEP-18:10 | 23.38 | 192.90 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 3849.39 | 11-OCT-17:30 | 23.38 | 192.90 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5559.44 | 06-NOV-17:00 | 222.14 | 578.72 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 7039.49 | 07-DEC-17:00 | 222.14 | 578.72 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 1506.78 | 0.00 | 32.15 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 7660.98 | 222.14 | 578.72 | 38972.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 91720.11 | 20-JAN-17:00 | 4808.68 | 6471.01 | 94908.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 183494.40 | 28-FEB-17:00 | 4808.68 | 6471.01 | 189816.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 358109.53 | 31-MAR-24:00 | 0.00 | 359.47 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 366259.93 | 20-APR-15:30 | 4808.68 | 6471.01 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 175353.30 | 31-MAY-24:00 | 0.00 | 359.47 | 189816.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 267496.00 | 30-JUN-24:00 | 0.00 | 359.47 | 284724.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 359653.72 | 31-JUL-24:00 | 0.00 | 718.95 | 759265.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 370531.17 | 07-AUG-21:14 | 1265.44 | 3595.14 | 1898162.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 175462.04 | 30-SEP-24:00 | 0.00 | 359.47 | 189816.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 268176.51 | 31-OCT-24:00 | 0.00 | 359.47 | 284724.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 277506.15 | 06-NOV-17:00 | 4808.68 | 6471.01 | 284724.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 368470.04 | 13-DEC-17:00 | 4808.68 | 6471.01 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 91720.11 | 0.00 | 359.47 | 94908.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 370531.17 | 4808.68 | 6471.01 | 1898162.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.164422E+13 | 1141961.03 | 19-JAN-16:49 | 0.455794E+12 | 1745683.16 | 09-JAN-07:10 |
February | 0.189246E+13 | 1336640.86 | 28-FEB-16:40 | 0.287453E+12 | 1803266.60 | 13-FEB-07:10 |
March | 0.262071E+13 | 1727321.56 | 30-MAR-15:20 | 0.113002E+12 | 617930.51 | 18-MAR-06:10 |
April | 0.296546E+13 | 1860481.66 | 12-APR-15:20 | 0.726603E+11 | 675857.02 | 06-APR-06:10 |
May | 0.202417E+13 | 1438935.00 | 16-MAY-15:50 | 0.627227E+11 | 111779.64 | 10-MAY-06:10 |
June | 0.253316E+13 | 1609872.22 | 29-JUN-15:00 | 0.576920E+11 | 72178.90 | 06-JUN-11:39 |
July | 0.304491E+13 | 1812595.22 | 07-JUL-15:00 | 0.548525E+11 | 69444.02 | 03-JUL-11:39 |
August | 0.359110E+13 | 1957895.51 | 17-AUG-15:30 | 0.577634E+11 | 69234.86 | 31-AUG-11:00 |
September | 0.201386E+13 | 1469680.56 | 07-SEP-15:00 | 0.555267E+11 | 82656.91 | 14-SEP-15:50 |
October | 0.225877E+13 | 1579317.54 | 10-OCT-15:30 | 0.835766E+11 | 649554.01 | 26-OCT-06:10 |
November | 0.247903E+13 | 1528139.27 | 27-NOV-16:00 | 0.133022E+12 | 1044356.64 | 22-NOV-07:10 |
December | 0.284797E+13 | 1621893.31 | 13-DEC-16:40 | 0.259165E+12 | 1314651.24 | 18-DEC-07:10 |
Annual Sum or Average | 0.299158E+14 | 0.169323E+13 | ||||
Minimum of Months | 0.164422E+13 | 1141961.03 | 0.548525E+11 | 69234.86 | ||
Maximum of Months | 0.359110E+13 | 1957895.51 | 0.455794E+12 | 1803266.60 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [J] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [J] | HUMIDIFIER:ELECTRICITY [J] | HEATRECOVERY:ELECTRICITY [J] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 0.333150E+12 | 0.718275E+11 | 0.766053E+12 | 0.164271E+12 | 0.165779E+12 | 0.208995E+11 | 0.00 | 0.951029E+11 | 0.190596E+11 | 0.261229E+10 | 0.546998E+10 | 0.00 | 0.00 |
February | 0.302520E+12 | 0.604208E+11 | 0.978954E+12 | 0.148384E+12 | 0.150648E+12 | 0.257607E+11 | 0.00 | 0.170122E+12 | 0.503996E+11 | 0.183348E+10 | 0.341492E+10 | 0.00 | 0.00 |
March | 0.353213E+12 | 0.604266E+11 | 0.141687E+13 | 0.164523E+12 | 0.172064E+12 | 0.388965E+11 | 0.00 | 0.306804E+12 | 0.105013E+12 | 0.937201E+09 | 0.196285E+10 | 0.00 | 0.00 |
April | 0.313757E+12 | 0.520179E+11 | 0.165903E+13 | 0.158945E+12 | 0.170672E+12 | 0.481356E+11 | 0.00 | 0.433966E+12 | 0.126919E+12 | 0.294732E+09 | 0.172475E+10 | 0.00 | 0.00 |
May | 0.336899E+12 | 0.481273E+11 | 0.774844E+12 | 0.164394E+12 | 0.184044E+12 | 0.562348E+11 | 0.00 | 0.306900E+12 | 0.147803E+12 | 52123678.84 | 0.487081E+10 | 0.00 | 0.00 |
June | 0.334552E+12 | 0.441063E+11 | 0.106252E+13 | 0.159182E+12 | 0.193740E+12 | 0.717709E+11 | 0.00 | 0.485144E+12 | 0.175702E+12 | 14739243.96 | 0.643360E+10 | 0.00 | 0.00 |
July | 0.313961E+12 | 0.465036E+11 | 0.139340E+13 | 0.164156E+12 | 0.199890E+12 | 0.827663E+11 | 0.00 | 0.638069E+12 | 0.198994E+12 | 0.00 | 0.716953E+10 | 0.00 | 0.00 |
August | 0.350489E+12 | 0.512022E+11 | 0.173200E+13 | 0.164521E+12 | 0.209604E+12 | 0.936219E+11 | 0.00 | 0.771267E+12 | 0.210542E+12 | 0.00 | 0.785437E+10 | 0.00 | 0.00 |
September | 0.315346E+12 | 0.556800E+11 | 0.740713E+12 | 0.158945E+12 | 0.182651E+12 | 0.600733E+11 | 0.00 | 0.335601E+12 | 0.160063E+12 | 0.00 | 0.479166E+10 | 0.00 | 0.00 |
October | 0.331263E+12 | 0.642269E+11 | 0.108340E+13 | 0.164271E+12 | 0.174032E+12 | 0.432393E+11 | 0.00 | 0.283344E+12 | 0.112300E+12 | 41761063.45 | 0.264732E+10 | 0.00 | 0.00 |
November | 0.328154E+12 | 0.680138E+11 | 0.135889E+13 | 0.159044E+12 | 0.162278E+12 | 0.328611E+11 | 0.00 | 0.275023E+12 | 0.912598E+11 | 0.121683E+10 | 0.228861E+10 | 0.00 | 0.00 |
December | 0.322831E+12 | 0.734167E+11 | 0.170972E+13 | 0.164159E+12 | 0.164132E+12 | 0.228577E+11 | 0.00 | 0.303697E+12 | 0.817214E+11 | 0.193551E+10 | 0.349944E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.393613E+13 | 0.695970E+12 | 0.146764E+14 | 0.193480E+13 | 0.212953E+13 | 0.597118E+12 | 0.00 | 0.440504E+13 | 0.147978E+13 | 0.893867E+10 | 0.521278E+11 | 0.00 | 0.00 |
Minimum of Months | 0.302520E+12 | 0.441063E+11 | 0.740713E+12 | 0.148384E+12 | 0.150648E+12 | 0.208995E+11 | 0.00 | 0.951029E+11 | 0.190596E+11 | 0.00 | 0.172475E+10 | 0.00 | 0.00 |
Maximum of Months | 0.353213E+12 | 0.734167E+11 | 0.173200E+13 | 0.164523E+12 | 0.209604E+12 | 0.936219E+11 | 0.00 | 0.771267E+12 | 0.210542E+12 | 0.261229E+10 | 0.785437E+10 | 0.00 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [J] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.00 | 0.00 | 0.387927E+12 | 0.00 | 0.678667E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.225817E+12 | 0.00 | 0.616363E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.435654E+11 | 0.00 | 0.694370E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.109828E+11 | 0.00 | 0.616774E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.100252E+10 | 0.00 | 0.617202E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.110688E+09 | 0.00 | 0.575813E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.548525E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.577634E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.201767E+09 | 0.00 | 0.553249E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.236563E+11 | 0.00 | 0.599202E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.713360E+11 | 0.00 | 0.616861E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.194094E+12 | 0.00 | 0.650708E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.958694E+12 | 0.00 | 0.734537E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.548525E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.387927E+12 | 0.00 | 0.694370E+11 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | EXTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum} [W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 385834.94 | 03-JAN-08:09 | 57580.60 | 01-JAN-06:10 | 423497.50 | 02-JAN-08:09 | 118535.44 | 03-JAN-08:20 | 101934.19 | 09-JAN-06:10 | 32653.89 | 10-JAN-06:19 | 0.00 | 01-JAN-00:10 |
February | 385834.94 | 01-FEB-08:09 | 57580.60 | 01-FEB-06:10 | 541788.89 | 01-FEB-08:09 | 118535.44 | 01-FEB-08:20 | 116669.53 | 03-FEB-11:50 | 32358.35 | 03-FEB-06:10 | 0.00 | 01-FEB-00:10 |
March | 385834.94 | 21-MAR-07:10 | 57580.60 | 01-MAR-06:10 | 660080.29 | 01-MAR-08:09 | 118535.44 | 21-MAR-07:19 | 136060.09 | 30-MAR-15:20 | 57943.14 | 30-MAR-15:09 | 0.00 | 01-MAR-00:10 |
April | 372703.55 | 03-APR-07:10 | 57580.60 | 01-APR-05:10 | 778371.69 | 03-APR-07:10 | 118525.16 | 03-APR-07:19 | 173140.65 | 17-APR-15:09 | 60075.36 | 12-APR-15:20 | 0.00 | 01-APR-00:10 |
May | 349940.27 | 24-MAY-07:19 | 57580.60 | 01-MAY-05:10 | 423497.50 | 01-MAY-07:10 | 118507.38 | 24-MAY-07:30 | 147401.22 | 16-MAY-15:50 | 59156.25 | 31-MAY-12:20 | 0.00 | 01-MAY-00:10 |
June | 342450.60 | 23-JUN-07:10 | 57580.60 | 01-JUN-05:10 | 541788.89 | 01-JUN-07:10 | 118501.55 | 23-JUN-07:19 | 139027.86 | 14-JUN-05:10 | 59748.80 | 27-JUN-11:39 | 0.00 | 01-JUN-00:10 |
July | 355780.78 | 27-JUL-07:10 | 57580.60 | 01-JUL-05:10 | 660080.29 | 03-JUL-07:10 | 118511.94 | 27-JUL-07:19 | 146082.58 | 07-JUL-15:00 | 61412.90 | 05-JUL-08:39 | 0.00 | 01-JUL-00:10 |
August | 372703.55 | 24-AUG-07:10 | 57580.60 | 01-AUG-05:10 | 778371.69 | 01-AUG-07:10 | 118525.16 | 24-AUG-07:19 | 150487.04 | 02-AUG-15:00 | 61546.80 | 01-AUG-09:20 | 0.00 | 01-AUG-00:10 |
September | 383261.93 | 29-SEP-07:10 | 57580.60 | 01-SEP-05:10 | 423497.50 | 01-SEP-07:10 | 118533.43 | 29-SEP-07:19 | 145176.20 | 07-SEP-15:30 | 60745.24 | 06-SEP-11:20 | 0.00 | 01-SEP-00:10 |
October | 385834.94 | 19-OCT-07:10 | 57580.60 | 01-OCT-05:10 | 541788.89 | 02-OCT-07:10 | 118535.44 | 19-OCT-07:19 | 125997.66 | 11-OCT-15:20 | 58544.59 | 18-OCT-14:39 | 0.00 | 01-OCT-00:10 |
November | 385834.94 | 01-NOV-07:10 | 57580.60 | 01-NOV-05:10 | 660080.29 | 01-NOV-07:10 | 118535.44 | 01-NOV-07:19 | 101604.18 | 06-NOV-14:00 | 31473.61 | 21-NOV-05:10 | 0.00 | 01-NOV-00:10 |
December | 385834.94 | 06-DEC-08:09 | 57580.60 | 01-DEC-06:10 | 778371.69 | 01-DEC-08:09 | 118535.44 | 06-DEC-08:20 | 90388.90 | 14-DEC-06:10 | 31932.08 | 18-DEC-06:00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 342450.60 | 57580.60 | 423497.50 | 118501.55 | 90388.90 | 31473.61 | 0.00 | |||||||
Maximum of Months | 385834.94 | 57580.60 | 778371.69 | 118535.44 | 173140.65 | 61546.80 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY {Maximum} [W] | HEATREJECTION:ELECTRICITY {TIMESTAMP} | HUMIDIFIER:ELECTRICITY {Maximum} [W] | HUMIDIFIER:ELECTRICITY {TIMESTAMP} | HEATRECOVERY:ELECTRICITY {Maximum} [W] | HEATRECOVERY:ELECTRICITY {TIMESTAMP} | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 118194.27 | 31-JAN-15:09 | 51419.24 | 19-JAN-21:00 | 5868.03 | 05-JAN-18:10 | 5613.48 | 02-JAN-07:10 | 0.00 | 0.00 |
February | 211381.48 | 28-FEB-14:00 | 51486.46 | 28-FEB-14:00 | 5743.06 | 03-FEB-18:00 | 5613.48 | 01-FEB-07:10 | 0.00 | 0.00 |
March | 362960.60 | 30-MAR-15:20 | 92827.61 | 29-MAR-15:00 | 5579.39 | 18-MAR-16:10 | 5613.48 | 01-MAR-07:10 | 0.00 | 0.00 |
April | 418262.84 | 18-APR-12:50 | 92827.61 | 04-APR-10:39 | 3958.09 | 05-APR-19:19 | 5613.48 | 04-APR-07:00 | 0.00 | 0.00 |
May | 319471.22 | 30-MAY-14:39 | 92827.61 | 02-MAY-12:20 | 2994.13 | 10-MAY-18:00 | 5613.48 | 01-MAY-13:50 | 0.00 | 0.00 |
June | 385409.73 | 27-JUN-12:09 | 92827.61 | 01-JUN-07:49 | 2978.25 | 10-JUN-16:00 | 5613.48 | 01-JUN-06:10 | 0.00 | 0.00 |
July | 432733.39 | 07-JUL-15:00 | 92827.61 | 01-JUL-06:30 | 0.00 | 01-JUL-00:10 | 5613.48 | 01-JUL-06:10 | 0.00 | 0.00 |
August | 456876.80 | 17-AUG-15:30 | 92827.61 | 01-AUG-06:19 | 0.00 | 01-AUG-00:10 | 5613.48 | 01-AUG-06:10 | 0.00 | 0.00 |
September | 330079.12 | 06-SEP-11:30 | 92827.61 | 01-SEP-09:20 | 0.00 | 01-SEP-00:10 | 5613.48 | 01-SEP-06:10 | 0.00 | 0.00 |
October | 349862.43 | 18-OCT-14:39 | 92827.61 | 02-OCT-08:00 | 2676.20 | 31-OCT-20:00 | 5613.48 | 02-OCT-07:10 | 0.00 | 0.00 |
November | 245216.55 | 02-NOV-13:09 | 71037.94 | 02-NOV-12:30 | 4324.26 | 22-NOV-18:10 | 5613.48 | 01-NOV-06:10 | 0.00 | 0.00 |
December | 260067.23 | 12-DEC-13:00 | 54527.02 | 13-DEC-11:09 | 5317.63 | 02-DEC-17:00 | 5613.48 | 01-DEC-07:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | ||||||||
Minimum of Months | 118194.27 | 51419.24 | 0.00 | 5613.48 | 0.00 | 0.00 | ||||
Maximum of Months | 456876.80 | 92827.61 | 5868.03 | 5613.48 | 0.00 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY {AT MAX/MIN} [W] | |
January | 1141961.03 | 19-JAN-16:49 | 363780.14 | 423497.50 | 0.00 | 84465.88 | 75247.91 | 29167.43 | 0.00 | 114588.71 | 51213.47 |
February | 1336640.86 | 28-FEB-16:40 | 333338.24 | 541788.89 | 0.00 | 84450.25 | 96127.73 | 29431.20 | 0.00 | 200594.06 | 50910.48 |
March | 1727321.56 | 30-MAR-15:20 | 332294.83 | 660080.29 | 0.00 | 84450.25 | 136060.09 | 56776.73 | 0.00 | 362960.60 | 92827.61 |
April | 1860481.66 | 12-APR-15:20 | 332294.83 | 778371.69 | 0.00 | 84450.25 | 116980.75 | 60075.36 | 0.00 | 391738.86 | 92827.61 |
May | 1438935.00 | 16-MAY-15:50 | 332294.83 | 423497.50 | 0.00 | 84450.25 | 147401.22 | 57437.94 | 0.00 | 299154.50 | 92827.61 |
June | 1609872.22 | 29-JUN-15:00 | 332294.83 | 541788.89 | 0.00 | 84450.25 | 137149.96 | 58006.53 | 0.00 | 357740.67 | 92827.61 |
July | 1812595.22 | 07-JUL-15:00 | 332294.83 | 660080.29 | 0.00 | 84450.25 | 146082.58 | 58512.80 | 0.00 | 432733.39 | 92827.61 |
August | 1957895.51 | 17-AUG-15:30 | 332294.83 | 778371.69 | 0.00 | 84450.25 | 148727.01 | 58733.85 | 0.00 | 456876.80 | 92827.61 |
September | 1469680.56 | 07-SEP-15:00 | 332294.83 | 423497.50 | 0.00 | 84450.25 | 143319.55 | 58434.89 | 0.00 | 329242.46 | 92827.61 |
October | 1579317.54 | 10-OCT-15:30 | 332294.83 | 541788.89 | 0.00 | 84450.25 | 122020.81 | 57082.05 | 0.00 | 343239.62 | 92827.61 |
November | 1528139.27 | 27-NOV-16:00 | 372703.55 | 660080.29 | 0.00 | 84479.04 | 76844.69 | 29557.29 | 0.00 | 227823.00 | 71037.94 |
December | 1621893.31 | 13-DEC-16:40 | 372703.55 | 778371.69 | 0.00 | 84479.10 | 81753.79 | 29418.31 | 0.00 | 222654.67 | 52512.21 |
Annual Sum or Average | |||||||||||
Minimum of Months | 1141961.03 | 332294.83 | 423497.50 | 0.00 | 84450.25 | 75247.91 | 29167.43 | 0.00 | 114588.71 | 50910.48 | |
Maximum of Months | 1957895.51 | 372703.55 | 778371.69 | 0.00 | 84479.10 | 148727.01 | 60075.36 | 0.00 | 456876.80 | 92827.61 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS {Maximum} [W] | WATERSYSTEMS:NATURALGAS {TIMESTAMP} | COGENERATION:NATURALGAS [] | |
January | 0.00 | 0.00 | 1714112.09 | 09-JAN-07:10 | 0.00 | 82139.73 | 30-JAN-12:20 | 0.00 |
February | 0.00 | 0.00 | 1771654.06 | 13-FEB-07:10 | 0.00 | 82149.84 | 02-FEB-12:00 | 0.00 |
March | 0.00 | 0.00 | 588186.92 | 18-MAR-06:10 | 0.00 | 81489.43 | 03-MAR-12:00 | 0.00 |
April | 0.00 | 0.00 | 654321.34 | 06-APR-06:10 | 0.00 | 79363.23 | 04-APR-11:30 | 0.00 |
May | 0.00 | 0.00 | 80886.69 | 10-MAY-06:10 | 0.00 | 76583.17 | 01-MAY-11:20 | 0.00 |
June | 0.00 | 0.00 | 37593.89 | 10-JUN-13:09 | 0.00 | 72178.90 | 06-JUN-11:39 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 69444.02 | 03-JUL-11:39 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 69234.86 | 31-AUG-11:00 | 0.00 |
September | 0.00 | 0.00 | 44355.23 | 14-SEP-15:50 | 0.00 | 72137.03 | 29-SEP-11:00 | 0.00 |
October | 0.00 | 0.00 | 621241.91 | 26-OCT-06:10 | 0.00 | 75596.26 | 27-OCT-11:50 | 0.00 |
November | 0.00 | 0.00 | 1013280.63 | 22-NOV-07:10 | 0.00 | 78954.05 | 27-NOV-12:30 | 0.00 |
December | 0.00 | 0.00 | 1284015.05 | 18-DEC-07:10 | 0.00 | 81288.37 | 29-DEC-12:30 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 69234.86 | 0.00 | ||
Maximum of Months | 0.00 | 0.00 | 1771654.06 | 0.00 | 82149.84 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 27.21 | 2.83 | 27.28 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 25.70 | 0.00 | 25.70 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 25.75 | 0.00 | 25.75 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 25.61 | 0.00 | 25.61 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 26.65 | 0.00 | 26.65 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 26.26 | 0.00 | 26.26 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 26.31 | 0.00 | 26.31 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 6.83 | 26.46 | 0.00 | 26.46 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 5.83 | 26.77 | 0.50 | 26.82 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 7.17 | 26.83 | 0.17 | 26.84 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 7.17 | 27.04 | 0.67 | 27.07 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 26.55 | 0.67 | 26.72 |
Annual Sum or Average | 0.00 | 0.00 | 42.83 | 26.72 | 4.83 | 26.79 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 25.61 | 0.00 | 25.61 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 7.17 | 27.21 | 2.83 | 27.28 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.17 | 19.25 | 0.00 | 19.25 | 0.00 | 19.25 | 0.00 | 19.25 |
February | 0.17 | 18.59 | 0.00 | 18.59 | 0.00 | 18.59 | 0.00 | 18.59 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.33 | 18.92 | 0.00 | 18.92 | 0.00 | 18.92 | 0.00 | 18.92 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.17 | 19.25 | 0.00 | 19.25 | 0.00 | 19.25 | 0.00 | 19.25 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 3.50 | 18.66 | 0.83 | 18.94 | 0.00 | 18.94 | 0.00 | 18.94 |
February | 1.67 | 18.78 | 0.33 | 19.01 | 0.00 | 19.01 | 0.00 | 19.01 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 1.50 | 18.91 | 0.17 | 19.02 | 0.00 | 19.02 | 0.00 | 19.02 |
Annual Sum or Average | 6.67 | 18.75 | 1.33 | 18.98 | 0.00 | 18.98 | 0.00 | 18.98 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 3.50 | 18.91 | 0.83 | 19.02 | 0.00 | 19.02 | 0.00 | 19.02 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.17 | 19.40 | 0.00 | 19.40 | 0.00 | 19.40 | 0.00 | 19.40 |
February | 0.17 | 19.26 | 0.00 | 19.26 | 0.00 | 19.26 | 0.00 | 19.26 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 27.34 | 1.17 | 27.34 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.33 | 19.33 | 0.00 | 19.33 | 1.17 | 25.56 | 1.17 | 26.34 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.17 | 19.40 | 0.00 | 19.40 | 1.17 | 27.34 | 1.17 | 27.34 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.17 | 19.32 | 0.00 | 19.32 | 0.00 | 19.32 | 0.00 | 19.32 |
February | 0.17 | 19.18 | 0.00 | 19.18 | 0.00 | 19.18 | 0.00 | 19.18 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.34 | 0.17 | 27.34 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 27.64 | 1.33 | 27.64 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 27.69 | 2.83 | 27.69 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 28.08 | 3.17 | 28.08 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 4.33 | 27.98 | 4.33 | 27.98 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 27.96 | 3.17 | 27.96 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 27.83 | 1.67 | 27.83 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.44 | 0.67 | 27.44 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.33 | 19.25 | 0.00 | 19.25 | 17.33 | 27.72 | 17.33 | 27.80 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.17 | 19.32 | 0.00 | 19.32 | 4.33 | 28.08 | 4.33 | 28.08 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.33 | 19.16 | 0.00 | 19.16 | 0.50 | 24.14 | 0.50 | 25.38 |
February | 0.17 | 19.07 | 0.00 | 19.07 | 3.00 | 27.28 | 3.00 | 27.50 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 27.44 | 1.83 | 27.44 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 27.59 | 1.17 | 27.59 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.28 | 0.17 | 27.28 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.28 | 0.33 | 27.28 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 27.43 | 3.17 | 27.44 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 5.67 | 27.59 | 5.50 | 27.62 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 27.62 | 3.00 | 27.62 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 5.83 | 27.89 | 5.83 | 27.89 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 4.33 | 27.90 | 4.33 | 27.90 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 27.74 | 1.33 | 27.74 |
Annual Sum or Average | 0.50 | 19.13 | 0.00 | 19.13 | 30.50 | 27.55 | 30.17 | 27.62 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 24.14 | 0.17 | 25.38 |
Maximum of Months | 0.33 | 19.16 | 0.00 | 19.16 | 5.83 | 27.90 | 5.83 | 27.90 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 27.82 | 1.33 | 27.82 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 4.17 | 27.99 | 3.00 | 27.98 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 10.50 | 27.55 | 4.50 | 27.72 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 28.08 | 2.00 | 28.10 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 12.50 | 27.55 | 5.00 | 27.73 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 22.83 | 27.62 | 7.83 | 27.80 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 23.50 | 27.51 | 7.17 | 27.71 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 5.83 | 27.63 | 4.00 | 27.71 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 4.00 | 27.92 | 3.17 | 27.99 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 27.84 | 2.33 | 27.84 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.06 | 0.50 | 27.27 |
Annual Sum or Average | 0.00 | 0.00 | 91.00 | 27.63 | 40.83 | 27.78 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 23.50 | 28.08 | 7.83 | 28.10 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 14.17 | 18.32 | 2.50 | 18.55 | 0.00 | 18.55 | 0.00 | 18.55 |
February | 11.83 | 17.15 | 3.17 | 17.32 | 0.00 | 17.32 | 0.00 | 17.32 |
March | 0.17 | 19.44 | 0.00 | 19.44 | 0.00 | 19.44 | 0.00 | 19.44 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.35 | 0.50 | 27.35 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.67 | 19.06 | 0.00 | 19.06 | 0.00 | 19.06 | 0.00 | 19.06 |
December | 4.50 | 18.75 | 0.50 | 18.87 | 0.00 | 18.87 | 0.00 | 18.87 |
Annual Sum or Average | 31.33 | 17.96 | 6.17 | 18.11 | 0.50 | 18.23 | 0.50 | 18.35 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 14.17 | 19.44 | 3.17 | 19.44 | 0.50 | 27.35 | 0.50 | 27.35 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 9.67 | 17.42 | 0.50 | 17.39 | 0.00 | 17.39 | 0.00 | 17.39 |
February | 7.33 | 16.42 | 0.50 | 16.29 | 0.00 | 16.29 | 0.00 | 16.29 |
March | 0.17 | 19.34 | 0.00 | 19.34 | 0.00 | 19.34 | 0.00 | 19.34 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 27.68 | 1.00 | 27.68 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 27.69 | 2.50 | 27.69 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 4.00 | 28.02 | 4.00 | 28.02 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 8.67 | 27.83 | 8.67 | 27.83 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 5.67 | 27.88 | 5.67 | 27.88 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 27.79 | 1.33 | 27.79 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.50 | 18.99 | 0.00 | 18.99 | 0.00 | 18.99 | 0.00 | 18.99 |
December | 3.83 | 18.75 | 0.33 | 18.88 | 0.00 | 18.88 | 0.00 | 18.88 |
Annual Sum or Average | 21.50 | 17.37 | 1.33 | 17.33 | 23.17 | 22.63 | 23.17 | 24.38 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 9.67 | 19.34 | 0.50 | 19.34 | 8.67 | 28.02 | 8.67 | 28.02 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 6.33 | 18.43 | 0.17 | 18.48 | 0.67 | 19.30 | 0.67 | 19.99 |
February | 5.83 | 17.18 | 0.67 | 17.05 | 2.33 | 19.88 | 2.33 | 21.53 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.32 | 0.67 | 27.32 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.51 | 0.83 | 27.51 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 27.43 | 2.00 | 27.43 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 4.83 | 27.60 | 4.83 | 27.60 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 27.64 | 2.67 | 27.64 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 5.50 | 27.89 | 5.50 | 27.89 |
November | 0.33 | 19.06 | 0.00 | 19.06 | 3.67 | 27.12 | 3.67 | 27.47 |
December | 2.50 | 18.91 | 0.00 | 18.91 | 1.00 | 21.44 | 1.00 | 22.85 |
Annual Sum or Average | 15.00 | 18.04 | 0.83 | 17.97 | 24.17 | 23.85 | 24.17 | 25.30 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 6.33 | 19.06 | 0.67 | 19.06 | 5.50 | 27.89 | 5.50 | 27.89 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 6.17 | 18.23 | 0.00 | 18.23 | 0.00 | 18.23 | 0.00 | 18.23 |
February | 5.17 | 16.82 | 0.83 | 16.51 | 0.00 | 16.51 | 0.00 | 16.51 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 27.83 | 1.33 | 27.80 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 27.95 | 1.50 | 27.95 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 5.67 | 28.07 | 3.00 | 28.10 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 8.83 | 28.26 | 4.33 | 28.29 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 6.00 | 28.24 | 3.33 | 28.29 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 27.81 | 1.83 | 27.80 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 27.76 | 0.83 | 27.77 |
November | 0.50 | 19.10 | 0.00 | 19.10 | 0.00 | 19.10 | 0.00 | 19.10 |
December | 2.67 | 18.76 | 0.00 | 18.76 | 0.00 | 18.76 | 0.00 | 18.76 |
Annual Sum or Average | 14.50 | 17.85 | 0.83 | 17.67 | 29.17 | 24.51 | 16.17 | 25.48 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 6.17 | 19.10 | 0.83 | 19.10 | 8.83 | 28.26 | 4.33 | 28.29 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 51.33 | 16.54 | 15.67 | 16.68 | 0.00 | 16.68 | 0.00 | 16.68 |
February | 29.50 | 16.37 | 9.00 | 16.51 | 0.00 | 16.51 | 0.00 | 16.51 |
March | 1.33 | 19.07 | 0.00 | 19.07 | 0.00 | 19.07 | 0.00 | 19.07 |
April | 0.33 | 19.15 | 0.00 | 19.15 | 0.00 | 19.15 | 0.00 | 19.15 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 27.46 | 0.83 | 27.45 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 27.57 | 2.33 | 27.57 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 27.41 | 0.83 | 27.43 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.50 | 19.20 | 0.00 | 19.20 | 0.00 | 19.20 | 0.00 | 19.20 |
November | 4.17 | 18.64 | 0.17 | 18.70 | 0.00 | 18.70 | 0.00 | 18.70 |
December | 26.33 | 16.90 | 7.00 | 17.08 | 0.00 | 17.08 | 0.00 | 17.08 |
Annual Sum or Average | 113.50 | 16.71 | 31.83 | 16.82 | 5.50 | 17.21 | 4.00 | 17.48 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 51.33 | 19.20 | 15.67 | 19.20 | 3.33 | 27.57 | 2.33 | 27.57 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 31.50 | 15.72 | 5.50 | 15.68 | 0.00 | 15.68 | 0.00 | 15.68 |
February | 17.17 | 15.85 | 2.00 | 15.84 | 0.00 | 15.84 | 0.00 | 15.84 |
March | 1.00 | 19.00 | 0.00 | 19.00 | 0.00 | 19.00 | 0.00 | 19.00 |
April | 0.17 | 19.03 | 0.00 | 19.03 | 0.67 | 25.89 | 0.67 | 26.65 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 27.69 | 2.17 | 27.69 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 6.00 | 27.92 | 5.67 | 27.93 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 12.33 | 27.88 | 11.33 | 27.89 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 7.67 | 27.90 | 7.17 | 27.92 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 27.73 | 1.17 | 27.73 |
October | 0.50 | 19.19 | 0.00 | 19.19 | 0.00 | 19.19 | 0.00 | 19.19 |
November | 3.17 | 18.49 | 0.00 | 18.49 | 0.00 | 18.49 | 0.00 | 18.49 |
December | 16.83 | 16.11 | 1.17 | 16.07 | 0.00 | 16.07 | 0.00 | 16.07 |
Annual Sum or Average | 70.33 | 16.05 | 8.67 | 15.99 | 30.00 | 19.26 | 28.17 | 21.03 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.68 | 0.00 | 15.68 |
Maximum of Months | 31.50 | 19.19 | 5.50 | 19.19 | 12.33 | 27.92 | 11.33 | 27.93 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 26.00 | 16.49 | 4.83 | 16.51 | 0.00 | 16.51 | 0.00 | 16.51 |
February | 14.33 | 16.51 | 2.83 | 16.58 | 1.17 | 17.29 | 1.17 | 17.91 |
March | 0.83 | 19.15 | 0.00 | 19.15 | 0.00 | 19.15 | 0.00 | 19.15 |
April | 0.17 | 19.15 | 0.00 | 19.15 | 0.83 | 26.12 | 0.83 | 26.76 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.28 | 0.33 | 27.28 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 27.49 | 2.00 | 27.50 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 27.58 | 4.33 | 27.58 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 6.00 | 27.75 | 5.17 | 27.77 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 27.71 | 2.50 | 27.71 |
October | 0.50 | 19.32 | 0.00 | 19.32 | 4.33 | 26.95 | 4.33 | 27.37 |
November | 2.17 | 18.39 | 0.17 | 18.54 | 1.83 | 22.60 | 1.83 | 24.17 |
December | 13.50 | 17.21 | 2.00 | 17.25 | 0.00 | 17.25 | 0.00 | 17.25 |
Annual Sum or Average | 57.50 | 16.81 | 9.83 | 16.83 | 24.33 | 19.71 | 22.50 | 21.28 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.51 | 0.00 | 16.51 |
Maximum of Months | 26.00 | 19.32 | 4.83 | 19.32 | 6.00 | 27.75 | 5.17 | 27.77 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 20.83 | 15.89 | 4.17 | 15.74 | 0.00 | 15.74 | 0.00 | 15.74 |
February | 11.67 | 15.92 | 2.50 | 15.73 | 0.00 | 15.73 | 0.00 | 15.73 |
March | 0.67 | 19.25 | 0.00 | 19.25 | 0.00 | 19.25 | 0.00 | 19.25 |
April | 0.17 | 19.29 | 0.00 | 19.29 | 2.17 | 27.24 | 1.50 | 27.47 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 28.06 | 1.50 | 28.08 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 6.33 | 28.15 | 3.33 | 28.20 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 10.00 | 28.38 | 4.83 | 28.41 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 7.33 | 28.26 | 4.00 | 28.30 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 27.84 | 1.83 | 27.88 |
October | 0.17 | 19.27 | 0.00 | 19.27 | 1.00 | 26.45 | 0.83 | 26.97 |
November | 2.00 | 18.24 | 0.00 | 18.24 | 0.00 | 18.24 | 0.00 | 18.24 |
December | 9.17 | 17.10 | 1.83 | 16.82 | 0.00 | 16.82 | 0.00 | 16.82 |
Annual Sum or Average | 44.67 | 16.33 | 8.50 | 16.12 | 32.67 | 20.71 | 17.83 | 22.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.73 | 0.00 | 15.73 |
Maximum of Months | 20.83 | 19.29 | 4.17 | 19.29 | 10.00 | 28.38 | 4.83 | 28.41 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 43.00 | 27.77 | 43.00 | 27.77 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 43.00 | 27.77 | 43.00 | 27.77 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 43.00 | 27.77 | 43.00 | 27.77 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 39.83 | 27.78 | 39.83 | 27.78 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 39.83 | 27.78 | 39.83 | 27.78 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 39.83 | 27.78 | 39.83 | 27.78 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 27.83 | 27.75 | 27.83 | 27.75 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 27.83 | 27.75 | 27.83 | 27.75 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 27.83 | 27.75 | 27.83 | 27.75 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 55.83 | 27.99 | 52.33 | 27.99 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 408.83 | 28.99 | 361.00 | 29.02 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 464.67 | 28.87 | 413.33 | 28.90 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 408.83 | 28.99 | 361.00 | 29.02 |
Report: ComfortReportSimple55Monthly
For: BASEMENT
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 229.33 | 23.98 | 65.17 | 24.26 | 0.00 | 24.26 |
February | 147.83 | 24.19 | 88.83 | 24.60 | 11.50 | 24.70 |
March | 54.50 | 24.01 | 178.67 | 24.68 | 1.00 | 24.68 |
April | 53.50 | 24.59 | 268.17 | 24.76 | 34.67 | 24.77 |
May | 146.33 | 24.61 | 437.50 | 24.55 | 140.83 | 24.57 |
June | 212.17 | 24.62 | 456.83 | 24.54 | 212.17 | 24.56 |
July | 284.67 | 25.06 | 497.00 | 24.78 | 284.67 | 24.85 |
August | 249.00 | 25.00 | 514.00 | 24.66 | 249.00 | 24.74 |
September | 156.33 | 25.27 | 476.67 | 24.75 | 156.33 | 24.85 |
October | 43.67 | 25.43 | 317.17 | 25.01 | 43.67 | 25.05 |
November | 36.33 | 25.14 | 220.00 | 25.29 | 22.83 | 25.33 |
December | 73.50 | 24.00 | 162.67 | 25.02 | 1.17 | 25.02 |
Annual Sum or Average | 1687.17 | 24.67 | 3682.67 | 24.71 | 1157.83 | 24.76 |
Minimum of Months | 36.33 | 23.98 | 65.17 | 24.26 | 0.00 | 24.26 |
Maximum of Months | 284.67 | 25.43 | 514.00 | 25.29 | 284.67 | 25.33 |
Report: ComfortReportSimple55Monthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 350.17 | 23.61 | 45.50 | 23.73 | 12.83 | 23.80 |
February | 206.50 | 23.62 | 54.33 | 23.87 | 0.00 | 23.87 |
March | 69.33 | 23.75 | 180.17 | 24.33 | 0.00 | 24.33 |
April | 13.00 | 23.79 | 293.00 | 24.39 | 0.00 | 24.39 |
May | 12.67 | 23.65 | 424.00 | 24.25 | 0.00 | 24.25 |
June | 2.83 | 23.68 | 447.50 | 24.21 | 0.00 | 24.21 |
July | 0.00 | 0.00 | 493.00 | 24.18 | 0.00 | 24.18 |
August | 0.00 | 0.00 | 514.00 | 24.11 | 0.00 | 24.11 |
September | 1.00 | 23.17 | 458.33 | 24.30 | 0.00 | 24.30 |
October | 17.17 | 23.58 | 304.33 | 24.49 | 0.00 | 24.49 |
November | 52.17 | 23.77 | 186.33 | 24.57 | 0.00 | 24.57 |
December | 133.33 | 23.72 | 132.00 | 24.36 | 0.00 | 24.36 |
Annual Sum or Average | 858.17 | 23.65 | 3532.50 | 24.21 | 12.83 | 24.22 |
Minimum of Months | 0.00 | 0.00 | 45.50 | 23.73 | 0.00 | 23.80 |
Maximum of Months | 350.17 | 23.79 | 514.00 | 24.57 | 12.83 | 24.57 |
Report: ComfortReportSimple55Monthly
For: CORE_MID
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 500.33 | 21.93 | 57.00 | 21.79 | 57.00 | 21.67 |
February | 430.00 | 22.40 | 35.67 | 22.27 | 34.00 | 22.15 |
March | 294.17 | 23.20 | 78.83 | 23.41 | 0.00 | 23.41 |
April | 155.50 | 23.26 | 158.33 | 23.81 | 0.00 | 23.81 |
May | 57.67 | 23.23 | 286.33 | 24.06 | 0.00 | 24.06 |
June | 41.67 | 23.29 | 356.83 | 24.11 | 0.00 | 24.11 |
July | 12.33 | 23.04 | 389.17 | 24.18 | 0.00 | 24.18 |
August | 11.17 | 23.20 | 422.33 | 24.15 | 0.00 | 24.15 |
September | 37.83 | 23.01 | 332.00 | 24.14 | 0.00 | 24.14 |
October | 191.17 | 23.11 | 131.33 | 23.58 | 0.00 | 23.58 |
November | 351.33 | 23.22 | 37.33 | 23.31 | 0.00 | 23.31 |
December | 460.67 | 22.55 | 13.33 | 22.58 | 0.83 | 22.58 |
Annual Sum or Average | 2543.83 | 22.70 | 2298.50 | 23.35 | 91.83 | 23.30 |
Minimum of Months | 11.17 | 21.93 | 13.33 | 21.79 | 0.00 | 21.67 |
Maximum of Months | 500.33 | 23.29 | 422.33 | 24.18 | 57.00 | 24.18 |
Report: ComfortReportSimple55Monthly
For: CORE_TOP
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 499.83 | 20.80 | 213.33 | 20.46 | 213.33 | 20.28 |
February | 444.50 | 21.54 | 90.50 | 21.25 | 89.67 | 21.05 |
March | 398.17 | 22.52 | 74.33 | 22.67 | 13.00 | 22.62 |
April | 242.83 | 22.88 | 135.33 | 23.35 | 0.00 | 23.35 |
May | 89.67 | 23.11 | 300.50 | 23.95 | 0.00 | 23.95 |
June | 36.00 | 23.24 | 373.33 | 24.14 | 0.00 | 24.14 |
July | 13.17 | 22.68 | 429.00 | 24.18 | 0.00 | 24.18 |
August | 2.00 | 23.22 | 447.33 | 24.19 | 0.00 | 24.19 |
September | 81.67 | 22.83 | 306.33 | 23.94 | 0.00 | 23.94 |
October | 329.83 | 22.52 | 85.67 | 22.85 | 0.00 | 22.85 |
November | 454.83 | 22.16 | 43.67 | 22.11 | 31.17 | 22.03 |
December | 483.50 | 21.28 | 139.00 | 21.02 | 133.17 | 20.83 |
Annual Sum or Average | 3076.00 | 21.91 | 2638.33 | 22.61 | 480.33 | 22.39 |
Minimum of Months | 2.00 | 20.80 | 43.67 | 20.46 | 0.00 | 20.28 |
Maximum of Months | 499.83 | 23.24 | 447.33 | 24.19 | 213.33 | 24.19 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 484.67 | 21.36 | 177.50 | 21.16 | 177.50 | 21.05 |
February | 415.33 | 21.96 | 88.33 | 21.74 | 83.17 | 21.56 |
March | 339.00 | 22.96 | 86.50 | 23.20 | 0.00 | 23.20 |
April | 144.50 | 23.15 | 208.50 | 23.81 | 0.00 | 23.81 |
May | 43.50 | 23.30 | 378.33 | 24.19 | 0.00 | 24.19 |
June | 8.50 | 24.12 | 452.83 | 24.32 | 2.17 | 24.33 |
July | 8.00 | 26.52 | 491.67 | 24.41 | 8.00 | 24.44 |
August | 2.50 | 26.88 | 511.50 | 24.27 | 2.50 | 24.28 |
September | 50.17 | 23.91 | 399.33 | 24.30 | 14.50 | 24.35 |
October | 255.83 | 23.05 | 158.00 | 23.51 | 6.17 | 23.53 |
November | 373.33 | 22.84 | 56.67 | 23.00 | 3.00 | 22.99 |
December | 449.67 | 22.22 | 48.83 | 22.23 | 25.17 | 22.16 |
Annual Sum or Average | 2575.00 | 22.41 | 3058.00 | 23.25 | 322.17 | 23.14 |
Minimum of Months | 2.50 | 21.36 | 48.83 | 21.16 | 0.00 | 21.05 |
Maximum of Months | 484.67 | 26.88 | 511.50 | 24.41 | 177.50 | 24.44 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 497.33 | 21.52 | 131.17 | 21.33 | 131.17 | 21.20 |
February | 392.83 | 21.84 | 64.83 | 21.78 | 52.33 | 21.65 |
March | 314.00 | 22.60 | 95.33 | 23.00 | 0.00 | 23.00 |
April | 157.00 | 22.85 | 213.50 | 23.64 | 3.17 | 23.67 |
May | 80.33 | 23.73 | 373.67 | 24.29 | 15.83 | 24.38 |
June | 27.67 | 25.44 | 439.00 | 24.40 | 17.17 | 24.49 |
July | 37.50 | 25.81 | 449.17 | 24.50 | 27.83 | 24.63 |
August | 28.67 | 25.52 | 455.00 | 24.32 | 18.67 | 24.41 |
September | 83.17 | 23.70 | 356.67 | 24.27 | 22.67 | 24.36 |
October | 241.33 | 22.68 | 173.50 | 23.39 | 8.33 | 23.43 |
November | 380.83 | 22.55 | 49.83 | 22.75 | 2.67 | 22.74 |
December | 464.00 | 21.98 | 34.50 | 22.00 | 19.33 | 21.95 |
Annual Sum or Average | 2704.67 | 22.37 | 2836.17 | 23.24 | 319.17 | 23.22 |
Minimum of Months | 27.67 | 21.52 | 34.50 | 21.33 | 0.00 | 21.20 |
Maximum of Months | 497.33 | 25.81 | 455.00 | 24.50 | 131.17 | 24.63 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 398.17 | 21.66 | 123.83 | 21.61 | 99.33 | 21.43 |
February | 334.33 | 22.17 | 79.83 | 22.30 | 43.67 | 22.20 |
March | 233.67 | 22.86 | 160.50 | 23.51 | 2.50 | 23.52 |
April | 133.50 | 23.09 | 250.33 | 23.90 | 3.67 | 23.93 |
May | 61.67 | 23.32 | 371.83 | 24.18 | 2.83 | 24.20 |
June | 20.67 | 24.41 | 440.17 | 24.32 | 7.17 | 24.35 |
July | 24.00 | 26.41 | 489.17 | 24.48 | 22.17 | 24.58 |
August | 23.33 | 26.84 | 512.17 | 24.41 | 23.33 | 24.52 |
September | 67.00 | 24.54 | 416.50 | 24.45 | 31.33 | 24.57 |
October | 195.83 | 23.32 | 259.83 | 23.98 | 28.50 | 24.13 |
November | 265.67 | 23.03 | 134.00 | 23.57 | 17.33 | 23.66 |
December | 341.67 | 22.30 | 78.33 | 22.57 | 19.17 | 22.50 |
Annual Sum or Average | 2099.50 | 22.68 | 3316.50 | 23.62 | 301.00 | 23.61 |
Minimum of Months | 20.67 | 21.66 | 78.33 | 21.61 | 2.50 | 21.43 |
Maximum of Months | 398.17 | 26.84 | 512.17 | 24.48 | 99.33 | 24.58 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 453.00 | 21.67 | 80.50 | 21.62 | 70.17 | 21.52 |
February | 322.67 | 22.26 | 73.17 | 22.51 | 24.50 | 22.44 |
March | 136.17 | 23.36 | 251.83 | 24.15 | 9.00 | 24.21 |
April | 43.00 | 25.25 | 395.50 | 24.67 | 23.67 | 24.79 |
May | 32.33 | 24.53 | 432.67 | 24.44 | 13.00 | 24.50 |
June | 31.17 | 26.73 | 483.67 | 24.60 | 28.83 | 24.73 |
July | 44.67 | 26.99 | 497.00 | 24.76 | 44.67 | 24.93 |
August | 46.50 | 26.87 | 514.00 | 24.66 | 46.50 | 24.83 |
September | 54.83 | 25.00 | 437.50 | 24.54 | 30.17 | 24.66 |
October | 136.50 | 23.45 | 290.33 | 24.24 | 19.00 | 24.35 |
November | 177.33 | 23.17 | 178.83 | 23.94 | 8.00 | 24.01 |
December | 271.83 | 23.01 | 93.67 | 23.44 | 0.33 | 23.44 |
Annual Sum or Average | 1750.00 | 23.02 | 3728.67 | 23.99 | 317.83 | 24.05 |
Minimum of Months | 31.17 | 21.67 | 73.17 | 21.62 | 0.33 | 21.52 |
Maximum of Months | 453.00 | 26.99 | 514.00 | 24.76 | 70.17 | 24.93 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.25 | 401.00 | 20.14 | 401.00 | 20.10 |
February | 450.83 | 20.83 | 218.00 | 20.60 | 218.00 | 20.48 |
March | 453.17 | 21.84 | 92.83 | 21.86 | 53.50 | 21.74 |
April | 302.33 | 22.49 | 108.50 | 22.86 | 12.33 | 22.83 |
May | 126.17 | 23.01 | 299.67 | 23.86 | 7.33 | 23.87 |
June | 36.67 | 24.06 | 422.33 | 24.27 | 13.83 | 24.30 |
July | 38.17 | 24.86 | 475.00 | 24.42 | 29.17 | 24.48 |
August | 20.50 | 25.30 | 502.00 | 24.34 | 19.83 | 24.38 |
September | 125.67 | 23.37 | 293.00 | 24.02 | 28.67 | 24.10 |
October | 406.00 | 22.08 | 83.17 | 22.36 | 21.00 | 22.39 |
November | 479.50 | 21.49 | 106.83 | 21.33 | 102.33 | 21.20 |
December | 497.00 | 20.59 | 286.67 | 20.39 | 286.67 | 20.30 |
Annual Sum or Average | 3438.00 | 21.51 | 3289.00 | 22.20 | 1193.67 | 21.96 |
Minimum of Months | 20.50 | 20.25 | 83.17 | 20.14 | 7.33 | 20.10 |
Maximum of Months | 502.00 | 25.30 | 502.00 | 24.42 | 401.00 | 24.48 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 427.00 | 20.32 | 319.33 | 20.20 | 319.33 | 20.15 |
February | 367.50 | 20.96 | 163.50 | 20.73 | 160.17 | 20.59 |
March | 353.83 | 21.98 | 59.00 | 22.12 | 21.83 | 22.04 |
April | 213.17 | 22.47 | 128.50 | 23.18 | 9.33 | 23.21 |
May | 130.33 | 23.32 | 257.33 | 24.13 | 23.00 | 24.25 |
June | 47.17 | 25.08 | 354.33 | 24.53 | 28.33 | 24.66 |
July | 75.50 | 25.55 | 381.33 | 24.77 | 58.17 | 24.96 |
August | 44.33 | 26.08 | 391.17 | 24.64 | 39.17 | 24.79 |
September | 137.83 | 23.29 | 249.50 | 24.06 | 33.17 | 24.20 |
October | 294.67 | 22.02 | 100.33 | 22.55 | 18.50 | 22.58 |
November | 399.17 | 21.58 | 56.33 | 21.50 | 50.83 | 21.39 |
December | 422.00 | 20.62 | 218.00 | 20.41 | 218.00 | 20.31 |
Annual Sum or Average | 2912.50 | 21.72 | 2678.67 | 22.44 | 979.83 | 22.28 |
Minimum of Months | 44.33 | 20.32 | 56.33 | 20.20 | 9.33 | 20.15 |
Maximum of Months | 427.00 | 26.08 | 391.17 | 24.77 | 319.33 | 24.96 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 428.67 | 21.05 | 226.33 | 20.82 | 215.67 | 20.64 |
February | 373.33 | 21.57 | 142.00 | 21.52 | 115.83 | 21.35 |
March | 301.00 | 22.30 | 136.50 | 22.82 | 19.50 | 22.74 |
April | 203.50 | 22.65 | 185.00 | 23.43 | 10.67 | 23.44 |
May | 111.33 | 23.03 | 322.17 | 23.96 | 8.33 | 23.98 |
June | 50.33 | 24.10 | 413.50 | 24.29 | 18.33 | 24.34 |
July | 48.00 | 25.38 | 469.67 | 24.52 | 40.33 | 24.61 |
August | 39.17 | 26.20 | 507.50 | 24.51 | 39.17 | 24.62 |
September | 99.50 | 24.11 | 368.67 | 24.37 | 41.00 | 24.51 |
October | 251.83 | 22.73 | 226.50 | 23.54 | 37.17 | 23.68 |
November | 335.67 | 22.39 | 114.67 | 22.81 | 35.00 | 22.80 |
December | 388.50 | 21.35 | 149.00 | 21.26 | 116.00 | 21.04 |
Annual Sum or Average | 2630.83 | 22.18 | 3261.50 | 23.07 | 697.00 | 22.94 |
Minimum of Months | 39.17 | 21.05 | 114.67 | 20.82 | 8.33 | 20.64 |
Maximum of Months | 428.67 | 26.20 | 507.50 | 24.52 | 215.67 | 24.62 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.61 | 311.17 | 20.41 | 311.17 | 20.33 |
February | 429.83 | 21.06 | 160.33 | 20.88 | 152.33 | 20.74 |
March | 374.17 | 21.91 | 103.33 | 22.27 | 23.50 | 22.20 |
April | 232.83 | 22.57 | 193.67 | 23.39 | 13.50 | 23.45 |
May | 129.83 | 23.11 | 329.17 | 23.99 | 16.83 | 24.07 |
June | 55.00 | 24.51 | 422.33 | 24.40 | 25.00 | 24.50 |
July | 54.17 | 25.37 | 462.83 | 24.56 | 40.67 | 24.69 |
August | 33.50 | 26.51 | 500.00 | 24.53 | 32.50 | 24.65 |
September | 135.67 | 23.41 | 323.50 | 24.12 | 36.17 | 24.26 |
October | 347.67 | 22.16 | 122.33 | 22.71 | 19.67 | 22.78 |
November | 437.83 | 21.65 | 75.33 | 21.64 | 56.50 | 21.54 |
December | 490.33 | 20.95 | 189.67 | 20.73 | 186.83 | 20.60 |
Annual Sum or Average | 3222.83 | 21.75 | 3193.67 | 22.59 | 914.67 | 22.43 |
Minimum of Months | 33.50 | 20.61 | 75.33 | 20.41 | 13.50 | 20.33 |
Maximum of Months | 502.00 | 26.51 | 500.00 | 24.56 | 311.17 | 24.69 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.99 | 423.83 | 19.89 | 423.83 | 19.85 |
February | 451.50 | 20.58 | 279.33 | 20.38 | 279.33 | 20.29 |
March | 459.67 | 21.42 | 152.50 | 21.37 | 114.50 | 21.20 |
April | 326.17 | 22.13 | 120.67 | 22.43 | 34.83 | 22.34 |
May | 155.17 | 22.75 | 289.83 | 23.69 | 10.50 | 23.70 |
June | 60.50 | 24.03 | 412.67 | 24.27 | 22.83 | 24.34 |
July | 62.67 | 24.90 | 466.33 | 24.47 | 46.33 | 24.57 |
August | 37.00 | 25.41 | 496.00 | 24.40 | 33.50 | 24.47 |
September | 177.33 | 23.03 | 278.17 | 23.80 | 30.50 | 23.87 |
October | 417.67 | 21.62 | 116.00 | 21.80 | 60.50 | 21.72 |
November | 482.17 | 20.95 | 207.67 | 20.72 | 207.00 | 20.59 |
December | 497.00 | 20.21 | 356.50 | 20.03 | 356.50 | 19.96 |
Annual Sum or Average | 3628.83 | 21.26 | 3599.50 | 21.89 | 1620.17 | 21.63 |
Minimum of Months | 37.00 | 19.99 | 116.00 | 19.89 | 10.50 | 19.85 |
Maximum of Months | 502.00 | 25.41 | 496.00 | 24.47 | 423.83 | 24.57 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.08 | 400.17 | 19.97 | 400.17 | 19.92 |
February | 447.67 | 20.84 | 229.00 | 20.57 | 229.00 | 20.43 |
March | 425.00 | 21.77 | 103.17 | 21.82 | 58.67 | 21.68 |
April | 253.50 | 22.25 | 169.17 | 22.94 | 22.83 | 22.89 |
May | 141.67 | 23.10 | 324.50 | 24.01 | 25.17 | 24.11 |
June | 63.17 | 24.86 | 431.67 | 24.46 | 36.33 | 24.59 |
July | 90.33 | 25.31 | 446.67 | 24.67 | 65.67 | 24.86 |
August | 60.33 | 25.77 | 470.33 | 24.57 | 49.17 | 24.72 |
September | 165.50 | 22.97 | 308.67 | 23.87 | 33.67 | 23.99 |
October | 344.33 | 21.70 | 137.83 | 22.15 | 42.50 | 22.07 |
November | 478.33 | 21.19 | 141.50 | 20.99 | 141.50 | 20.86 |
December | 497.00 | 20.28 | 318.67 | 20.07 | 318.67 | 19.98 |
Annual Sum or Average | 3468.83 | 21.47 | 3481.33 | 22.17 | 1423.33 | 21.96 |
Minimum of Months | 60.33 | 20.08 | 103.17 | 19.97 | 22.83 | 19.92 |
Maximum of Months | 502.00 | 25.77 | 470.33 | 24.67 | 400.17 | 24.86 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 453.17 | 20.66 | 279.00 | 20.37 | 274.67 | 20.21 |
February | 384.67 | 21.14 | 201.33 | 21.02 | 176.33 | 20.81 |
March | 331.50 | 21.84 | 159.00 | 22.21 | 59.33 | 22.02 |
April | 244.17 | 22.25 | 175.50 | 22.95 | 27.17 | 22.91 |
May | 148.00 | 22.78 | 303.83 | 23.78 | 13.00 | 23.80 |
June | 73.50 | 23.87 | 396.83 | 24.26 | 24.33 | 24.33 |
July | 71.50 | 25.05 | 451.00 | 24.53 | 52.67 | 24.65 |
August | 47.67 | 25.89 | 496.17 | 24.51 | 44.33 | 24.63 |
September | 138.83 | 23.49 | 336.00 | 24.15 | 42.33 | 24.29 |
October | 282.00 | 22.18 | 216.00 | 23.00 | 48.50 | 23.05 |
November | 364.50 | 21.71 | 149.67 | 21.91 | 87.67 | 21.74 |
December | 422.50 | 20.86 | 215.33 | 20.59 | 197.50 | 20.36 |
Annual Sum or Average | 2962.00 | 21.80 | 3379.67 | 22.61 | 1047.83 | 22.41 |
Minimum of Months | 47.67 | 20.66 | 149.67 | 20.37 | 13.00 | 20.21 |
Maximum of Months | 453.17 | 25.89 | 496.17 | 24.53 | 274.67 | 24.65 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.26 | 357.17 | 20.08 | 357.17 | 20.00 |
February | 434.00 | 20.81 | 214.83 | 20.62 | 207.83 | 20.49 |
March | 390.83 | 21.56 | 131.33 | 21.81 | 61.17 | 21.67 |
April | 269.17 | 22.24 | 178.33 | 23.00 | 26.00 | 23.03 |
May | 162.83 | 22.80 | 307.33 | 23.80 | 18.83 | 23.87 |
June | 77.83 | 24.04 | 405.33 | 24.34 | 28.83 | 24.46 |
July | 69.17 | 24.90 | 445.83 | 24.53 | 45.00 | 24.66 |
August | 46.17 | 26.01 | 483.83 | 24.54 | 39.33 | 24.68 |
September | 175.67 | 23.00 | 286.33 | 23.88 | 37.67 | 24.02 |
October | 368.50 | 21.79 | 120.00 | 22.32 | 26.33 | 22.36 |
November | 450.83 | 21.23 | 140.17 | 21.11 | 127.50 | 20.97 |
December | 493.17 | 20.54 | 275.50 | 20.29 | 274.67 | 20.17 |
Annual Sum or Average | 3440.17 | 21.48 | 3346.00 | 22.24 | 1250.33 | 22.04 |
Minimum of Months | 46.17 | 20.26 | 120.00 | 20.08 | 18.83 | 20.00 |
Maximum of Months | 502.00 | 26.01 | 483.83 | 24.54 | 357.17 | 24.68 |
Report: ComfortReportSimple55Monthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 488.83 | 27.00 | 0.00 | 27.00 |
February | 0.83 | 27.00 | 454.00 | 27.00 | 0.83 | 27.00 |
March | 54.00 | 27.00 | 514.00 | 27.00 | 54.00 | 27.00 |
April | 205.33 | 27.00 | 485.00 | 27.00 | 205.33 | 27.00 |
May | 18.50 | 27.00 | 508.00 | 27.00 | 18.50 | 27.00 |
June | 189.17 | 27.00 | 496.00 | 27.00 | 189.17 | 27.00 |
July | 268.33 | 27.00 | 497.00 | 27.00 | 268.33 | 27.00 |
August | 469.83 | 27.12 | 514.00 | 27.12 | 469.83 | 27.12 |
September | 57.83 | 27.00 | 485.00 | 27.00 | 57.83 | 27.00 |
October | 49.67 | 27.00 | 502.00 | 27.00 | 49.67 | 27.00 |
November | 29.33 | 27.00 | 489.00 | 27.00 | 29.33 | 27.00 |
December | 27.83 | 27.00 | 497.00 | 27.00 | 27.83 | 27.00 |
Annual Sum or Average | 1370.67 | 27.04 | 5929.83 | 27.02 | 1370.67 | 27.02 |
Minimum of Months | 0.00 | 0.00 | 454.00 | 27.00 | 0.00 | 27.00 |
Maximum of Months | 469.83 | 27.12 | 514.00 | 27.12 | 469.83 | 27.12 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 39.17 | 25.61 | 320.00 | 26.84 | 0.00 | 26.84 |
February | 2.50 | 27.00 | 381.17 | 27.00 | 0.00 | 27.00 |
March | 1.67 | 27.00 | 508.67 | 27.00 | 1.67 | 27.00 |
April | 10.67 | 27.00 | 485.00 | 27.00 | 10.67 | 27.00 |
May | 0.00 | 0.00 | 508.00 | 27.00 | 0.00 | 27.00 |
June | 16.17 | 27.00 | 496.00 | 27.00 | 16.17 | 27.00 |
July | 67.00 | 27.00 | 497.00 | 27.00 | 67.00 | 27.00 |
August | 147.67 | 27.36 | 514.00 | 27.16 | 147.67 | 27.20 |
September | 9.33 | 27.00 | 485.00 | 27.00 | 9.33 | 27.00 |
October | 1.00 | 27.00 | 502.00 | 27.00 | 1.00 | 27.00 |
November | 0.00 | 0.00 | 488.83 | 27.00 | 0.00 | 27.00 |
December | 0.00 | 0.00 | 475.50 | 27.00 | 0.00 | 27.00 |
Annual Sum or Average | 295.17 | 27.00 | 5661.17 | 27.01 | 253.50 | 27.02 |
Minimum of Months | 0.00 | 0.00 | 320.00 | 26.84 | 0.00 | 26.84 |
Maximum of Months | 147.67 | 27.36 | 514.00 | 27.16 | 147.67 | 27.20 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 161.17 | 24.58 | 246.67 | 25.75 | 26.83 | 25.55 |
February | 27.67 | 26.90 | 337.33 | 26.99 | 0.00 | 26.99 |
March | 6.00 | 27.00 | 485.83 | 27.00 | 6.00 | 27.00 |
April | 33.50 | 27.00 | 485.00 | 27.00 | 33.50 | 27.00 |
May | 14.50 | 27.00 | 508.00 | 27.00 | 14.50 | 27.00 |
June | 91.83 | 27.00 | 496.00 | 27.00 | 91.83 | 27.00 |
July | 142.17 | 27.00 | 497.00 | 27.00 | 142.17 | 27.00 |
August | 192.67 | 27.20 | 514.00 | 27.11 | 192.67 | 27.13 |
September | 29.83 | 27.00 | 485.00 | 27.00 | 29.83 | 27.00 |
October | 6.17 | 27.00 | 502.00 | 27.00 | 6.17 | 27.00 |
November | 0.00 | 0.00 | 444.17 | 27.00 | 0.00 | 27.00 |
December | 10.50 | 27.00 | 375.33 | 27.00 | 0.00 | 27.00 |
Annual Sum or Average | 716.00 | 26.51 | 5376.33 | 26.93 | 543.50 | 26.92 |
Minimum of Months | 0.00 | 0.00 | 246.67 | 25.75 | 0.00 | 25.55 |
Maximum of Months | 192.67 | 27.20 | 514.00 | 27.11 | 192.67 | 27.13 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 256.33 | 27.00 | 502.00 | 27.00 | 256.33 | 27.00 |
February | 454.00 | 27.00 | 454.00 | 27.00 | 454.00 | 27.00 |
March | 514.00 | 27.00 | 514.00 | 27.00 | 514.00 | 27.00 |
April | 485.00 | 27.13 | 485.00 | 27.13 | 485.00 | 27.13 |
May | 495.83 | 27.00 | 508.00 | 27.00 | 495.83 | 27.00 |
June | 496.00 | 27.00 | 496.00 | 27.00 | 496.00 | 27.00 |
July | 497.00 | 27.00 | 497.00 | 27.00 | 497.00 | 27.00 |
August | 514.00 | 28.49 | 514.00 | 28.49 | 514.00 | 28.49 |
September | 485.00 | 27.00 | 485.00 | 27.00 | 485.00 | 27.00 |
October | 502.00 | 27.00 | 502.00 | 27.00 | 502.00 | 27.00 |
November | 489.00 | 27.00 | 489.00 | 27.00 | 489.00 | 27.00 |
December | 497.00 | 27.01 | 497.00 | 27.01 | 497.00 | 27.01 |
Annual Sum or Average | 5685.17 | 27.15 | 5943.00 | 27.14 | 5685.17 | 27.15 |
Minimum of Months | 256.33 | 27.00 | 454.00 | 27.00 | 256.33 | 27.00 |
Maximum of Months | 514.00 | 28.49 | 514.00 | 28.49 | 514.00 | 28.49 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 27.00007 | 21.67254 | 0.71771 | 16.07520 |
February | 454.00000 | 27.00011 | 24.19899 | 0.80529 | 18.89424 |
March | 514.00000 | 27.00018 | 29.06260 | 0.93446 | 23.57957 |
April | 485.00000 | 27.00009 | 32.64999 | 1.01741 | 26.92487 |
May | 508.00000 | 27.00091 | 36.69868 | 0.29496 | 6.90963 |
June | 496.00000 | 27.00149 | 37.51801 | 0.37363 | 7.98892 |
July | 497.00000 | 27.00102 | 37.99668 | 0.42229 | 8.78240 |
August | 514.00000 | 27.11281 | 37.94602 | 0.50363 | 10.51052 |
September | 485.00000 | 27.00080 | 38.49236 | 0.32209 | 7.25163 |
October | 502.00000 | 27.00068 | 33.74169 | 0.95108 | 24.17771 |
November | 489.00000 | 27.00016 | 27.51402 | 0.91419 | 22.77901 |
December | 497.00000 | 27.00004 | 24.86604 | 0.89337 | 22.00005 |
Annual Sum or Average | 5943.00000 | 27.01022 | 31.91986 | 0.67781 | 16.28694 |
Minimum of Months | 454.00000 | 27.00004 | 21.67254 | 0.29496 | 6.90963 |
Maximum of Months | 514.00000 | 27.11281 | 38.49236 | 1.01741 | 26.92487 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 26.85130 | 22.01578 | 0.55787 | 12.14140 |
February | 454.00000 | 27.00010 | 24.20188 | 0.66223 | 14.52401 |
March | 514.00000 | 27.00018 | 29.03507 | 0.80887 | 19.01359 |
April | 485.00000 | 27.00010 | 32.61897 | 0.89636 | 22.09748 |
May | 508.00000 | 27.00056 | 36.84853 | 0.22319 | 6.18416 |
June | 496.00000 | 27.00152 | 37.56352 | 0.28958 | 6.87116 |
July | 497.00000 | 27.00110 | 38.02464 | 0.32269 | 7.26488 |
August | 514.00000 | 27.10336 | 37.96472 | 0.37918 | 8.22189 |
September | 485.00000 | 27.00045 | 38.74857 | 0.24361 | 6.38138 |
October | 502.00000 | 27.00063 | 33.78825 | 0.84597 | 20.23166 |
November | 489.00000 | 27.00016 | 27.49007 | 0.76366 | 17.47394 |
December | 497.00000 | 27.00005 | 24.84193 | 0.69176 | 15.27238 |
Annual Sum or Average | 5943.00000 | 26.99678 | 31.98558 | 0.55587 | 12.94832 |
Minimum of Months | 454.00000 | 26.85130 | 22.01578 | 0.22319 | 6.18416 |
Maximum of Months | 514.00000 | 27.10336 | 38.74857 | 0.89636 | 22.09748 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 26.18151 | 22.60851 | 0.37623 | 10.76108 |
February | 454.00000 | 26.99416 | 24.23323 | 0.61494 | 13.39375 |
March | 514.00000 | 27.00018 | 29.05853 | 0.76890 | 17.81870 |
April | 485.00000 | 27.00012 | 32.64023 | 0.87316 | 21.34605 |
May | 508.00000 | 27.00067 | 36.86787 | 0.22169 | 6.29024 |
June | 496.00000 | 27.00153 | 37.56400 | 0.30268 | 7.12113 |
July | 497.00000 | 27.00109 | 38.03624 | 0.33913 | 7.56945 |
August | 514.00000 | 27.07618 | 37.99872 | 0.38951 | 8.42334 |
September | 485.00000 | 27.00048 | 38.83428 | 0.23268 | 6.38387 |
October | 502.00000 | 27.00064 | 33.85901 | 0.80761 | 18.99784 |
November | 489.00000 | 27.00016 | 27.52193 | 0.70200 | 15.66940 |
December | 497.00000 | 27.00005 | 24.86063 | 0.62711 | 13.59290 |
Annual Sum or Average | 5943.00000 | 26.93742 | 32.06457 | 0.52019 | 12.26059 |
Minimum of Months | 454.00000 | 26.18151 | 22.60851 | 0.22169 | 6.29024 |
Maximum of Months | 514.00000 | 27.07618 | 38.83428 | 0.87316 | 21.34605 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 27.00090 | 30.99947 | 1.02117 | 27.05237 |
February | 454.00000 | 27.00241 | 31.23904 | 1.19137 | 34.84713 |
March | 514.00000 | 27.00230 | 32.57546 | 1.36444 | 43.63653 |
April | 485.00000 | 27.13275 | 33.84875 | 1.53080 | 52.57347 |
May | 508.00000 | 27.00201 | 36.15900 | 0.51086 | 10.52213 |
June | 496.00000 | 27.00190 | 37.16575 | 0.77032 | 17.54079 |
July | 497.00000 | 27.00107 | 37.69953 | 0.98316 | 25.44286 |
August | 514.00000 | 28.48862 | 36.73902 | 1.59914 | 56.04440 |
September | 485.00000 | 27.00271 | 37.30895 | 0.61177 | 12.90425 |
October | 502.00000 | 27.00090 | 34.06680 | 1.29130 | 39.83869 |
November | 489.00000 | 27.00339 | 32.03506 | 1.40886 | 45.99114 |
December | 497.00000 | 27.00517 | 31.28693 | 1.50930 | 51.40777 |
Annual Sum or Average | 5943.00000 | 27.14147 | 34.28224 | 1.14983 | 34.85151 |
Minimum of Months | 454.00000 | 27.00090 | 30.99947 | 0.51086 | 10.52213 |
Maximum of Months | 514.00000 | 28.48862 | 37.69953 | 1.59914 | 56.04440 |
Report: OccupantComfortDataSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.36501 | 22.36393 | 0.31302 | 7.54908 |
February | 454.00000 | 24.38965 | 25.99307 | 0.35060 | 8.24486 |
March | 514.00000 | 24.37470 | 32.42123 | 0.40741 | 8.90994 |
April | 485.00000 | 24.45602 | 39.77637 | 0.47666 | 10.32524 |
May | 508.00000 | 24.46158 | 52.94896 | -0.2810 | 7.64928 |
June | 496.00000 | 24.45601 | 56.65876 | -0.2363 | 7.10605 |
July | 497.00000 | 24.60972 | 62.38679 | -0.1428 | 6.87416 |
August | 514.00000 | 24.49134 | 61.22087 | -0.1740 | 6.83006 |
September | 485.00000 | 24.56908 | 56.76139 | -0.1835 | 7.25412 |
October | 502.00000 | 24.60040 | 41.94365 | 0.54978 | 12.18384 |
November | 489.00000 | 24.60343 | 29.95989 | 0.46280 | 10.31894 |
December | 497.00000 | 24.53872 | 26.24935 | 0.40893 | 9.24886 |
Annual Sum or Average | 5943.00000 | 24.49308 | 42.52726 | 0.16038 | 8.53693 |
Minimum of Months | 454.00000 | 24.36501 | 22.36393 | -0.2810 | 6.83006 |
Maximum of Months | 514.00000 | 24.60972 | 62.38679 | 0.54978 | 12.18384 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.78324 | 26.46314 | 0.20948 | 6.97336 |
February | 454.00000 | 23.96258 | 27.15449 | 0.27229 | 7.10850 |
March | 514.00000 | 24.18279 | 32.49899 | 0.39076 | 8.59233 |
April | 485.00000 | 24.24771 | 38.63013 | 0.46051 | 9.73983 |
May | 508.00000 | 24.19928 | 45.98984 | -0.3728 | 8.35320 |
June | 496.00000 | 24.19040 | 46.35196 | -0.3515 | 7.86332 |
July | 497.00000 | 24.17125 | 48.16986 | -0.3384 | 7.55699 |
August | 514.00000 | 24.11255 | 48.18771 | -0.3431 | 7.52655 |
September | 485.00000 | 24.26830 | 47.99087 | -0.3262 | 7.72809 |
October | 502.00000 | 24.29394 | 40.69145 | 0.47620 | 10.12693 |
November | 489.00000 | 24.31746 | 30.30199 | 0.40340 | 8.81547 |
December | 497.00000 | 24.27148 | 27.67430 | 0.36023 | 8.29695 |
Annual Sum or Average | 5943.00000 | 24.16738 | 38.43001 | 0.06763 | 8.22858 |
Minimum of Months | 454.00000 | 23.78324 | 26.46314 | -0.3728 | 6.97336 |
Maximum of Months | 514.00000 | 24.31746 | 48.18771 | 0.47620 | 10.12693 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.93798 | 28.69992 | -0.2567 | 7.66778 |
February | 454.00000 | 22.48776 | 29.62861 | -0.1021 | 6.96981 |
March | 514.00000 | 23.58349 | 34.54774 | 0.22174 | 6.76265 |
April | 485.00000 | 23.86032 | 40.25906 | 0.33932 | 7.88375 |
May | 508.00000 | 23.96318 | 47.00023 | -0.4744 | 10.21710 |
June | 496.00000 | 24.03291 | 47.26425 | -0.4314 | 9.38521 |
July | 497.00000 | 24.06601 | 49.12981 | -0.4081 | 8.88988 |
August | 514.00000 | 24.06618 | 49.11030 | -0.4018 | 8.72857 |
September | 485.00000 | 24.01712 | 49.18811 | -0.4361 | 9.53074 |
October | 502.00000 | 23.73028 | 42.71272 | 0.31649 | 7.55730 |
November | 489.00000 | 23.46394 | 32.83196 | 0.16793 | 6.28913 |
December | 497.00000 | 22.64653 | 31.52717 | -0.0540 | 6.05877 |
Annual Sum or Average | 5943.00000 | 23.49504 | 40.23947 | -0.1276 | 8.00371 |
Minimum of Months | 454.00000 | 21.93798 | 28.69992 | -0.4744 | 6.05877 |
Maximum of Months | 514.00000 | 24.06618 | 49.18811 | 0.33932 | 10.21710 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.80934 | 28.72600 | -0.5576 | 15.12663 |
February | 454.00000 | 21.58645 | 31.06820 | -0.3326 | 10.50043 |
March | 514.00000 | 22.85421 | 36.25807 | 0.04260 | 6.93090 |
April | 485.00000 | 23.47277 | 41.24926 | 0.24506 | 7.34281 |
May | 508.00000 | 23.90225 | 47.04670 | -0.4888 | 10.76858 |
June | 496.00000 | 24.06146 | 46.97994 | -0.4069 | 9.05451 |
July | 497.00000 | 24.12145 | 48.77097 | -0.3729 | 8.38074 |
August | 514.00000 | 24.12203 | 48.75331 | -0.3665 | 8.12753 |
September | 485.00000 | 23.87984 | 49.69923 | -0.4803 | 10.70282 |
October | 502.00000 | 23.02383 | 44.64758 | 0.14223 | 6.73990 |
November | 489.00000 | 22.27879 | 35.06833 | -0.1252 | 7.00452 |
December | 497.00000 | 21.34945 | 32.26713 | -0.3882 | 10.85762 |
Annual Sum or Average | 5943.00000 | 22.96593 | 40.95078 | -0.2574 | 9.28563 |
Minimum of Months | 454.00000 | 20.80934 | 28.72600 | -0.5576 | 6.73990 |
Maximum of Months | 514.00000 | 24.12203 | 49.69923 | 0.24506 | 15.12663 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.44517 | 26.02644 | -0.3942 | 10.22619 |
February | 454.00000 | 22.13236 | 28.07163 | -0.1965 | 8.50497 |
March | 514.00000 | 23.33182 | 33.36227 | 0.15446 | 6.85022 |
April | 485.00000 | 23.85314 | 39.02099 | 0.34353 | 8.36951 |
May | 508.00000 | 24.13418 | 45.91655 | -0.3971 | 9.15532 |
June | 496.00000 | 24.28463 | 45.82166 | -0.2869 | 7.32620 |
July | 497.00000 | 24.36701 | 47.77060 | -0.2340 | 6.87634 |
August | 514.00000 | 24.25229 | 47.71226 | -0.2635 | 6.92991 |
September | 485.00000 | 24.19875 | 48.73355 | -0.3574 | 8.65503 |
October | 502.00000 | 23.56857 | 42.47461 | 0.27592 | 7.59781 |
November | 489.00000 | 23.12390 | 32.02890 | 0.08182 | 6.59120 |
December | 497.00000 | 22.38344 | 28.66330 | -0.1275 | 6.97031 |
Annual Sum or Average | 5943.00000 | 23.43198 | 38.88074 | -0.1170 | 7.83079 |
Minimum of Months | 454.00000 | 21.44517 | 26.02644 | -0.3971 | 6.59120 |
Maximum of Months | 514.00000 | 24.36701 | 48.73355 | 0.34353 | 10.22619 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.54640 | 25.55450 | -0.3569 | 9.44227 |
February | 454.00000 | 22.16583 | 27.74172 | -0.1664 | 8.22317 |
March | 514.00000 | 23.19390 | 33.23176 | 0.15605 | 7.17042 |
April | 485.00000 | 23.67727 | 39.07604 | 0.34655 | 8.77535 |
May | 508.00000 | 24.13477 | 45.40917 | -0.3291 | 9.22318 |
June | 496.00000 | 24.25054 | 45.54044 | -0.2378 | 7.41681 |
July | 497.00000 | 24.29275 | 47.55075 | -0.2009 | 7.44055 |
August | 514.00000 | 24.13823 | 47.73362 | -0.2551 | 7.57296 |
September | 485.00000 | 24.06945 | 48.56365 | -0.3367 | 9.28187 |
October | 502.00000 | 23.43804 | 42.25437 | 0.28171 | 8.33179 |
November | 489.00000 | 22.91604 | 31.98182 | 0.05795 | 6.73277 |
December | 497.00000 | 22.11674 | 28.79215 | -0.1714 | 7.13316 |
Annual Sum or Average | 5943.00000 | 23.33696 | 38.69993 | -0.1012 | 8.05844 |
Minimum of Months | 454.00000 | 21.54640 | 25.55450 | -0.3569 | 6.73277 |
Maximum of Months | 514.00000 | 24.29275 | 48.56365 | 0.34655 | 9.44227 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.22903 | 25.01730 | -0.1893 | 9.47507 |
February | 454.00000 | 22.72550 | 27.16927 | -0.0295 | 8.60092 |
March | 514.00000 | 23.61768 | 32.47424 | 0.25808 | 8.31846 |
April | 485.00000 | 23.89926 | 38.62598 | 0.38085 | 9.30265 |
May | 508.00000 | 24.11506 | 45.84285 | -0.3874 | 9.37751 |
June | 496.00000 | 24.25841 | 45.87552 | -0.2940 | 7.63169 |
July | 497.00000 | 24.37700 | 47.70347 | -0.2235 | 7.02352 |
August | 514.00000 | 24.30225 | 47.38110 | -0.2115 | 6.81788 |
September | 485.00000 | 24.28298 | 48.15932 | -0.2756 | 8.29732 |
October | 502.00000 | 23.84233 | 41.22281 | 0.39380 | 10.21723 |
November | 489.00000 | 23.59185 | 30.64024 | 0.23467 | 8.56957 |
December | 497.00000 | 22.91128 | 27.65823 | 0.02965 | 7.65457 |
Annual Sum or Average | 5943.00000 | 23.68597 | 38.23055 | -0.0269 | 8.43699 |
Minimum of Months | 454.00000 | 22.22903 | 25.01730 | -0.3874 | 6.81788 |
Maximum of Months | 514.00000 | 24.37700 | 48.15932 | 0.39380 | 10.21723 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.92639 | 24.65961 | -0.2377 | 8.27388 |
February | 454.00000 | 22.84159 | 26.18181 | 0.02775 | 7.83035 |
March | 514.00000 | 24.07070 | 31.12653 | 0.41715 | 10.00181 |
April | 485.00000 | 24.46439 | 36.91212 | 0.60616 | 13.82173 |
May | 508.00000 | 24.28330 | 44.83521 | -0.2344 | 7.74339 |
June | 496.00000 | 24.44537 | 44.75390 | -0.0993 | 6.63156 |
July | 497.00000 | 24.55594 | 46.44242 | -0.0187 | 6.72352 |
August | 514.00000 | 24.46385 | 46.30391 | 0.00091 | 6.48688 |
September | 485.00000 | 24.35006 | 47.50629 | -0.1979 | 7.68036 |
October | 502.00000 | 24.07083 | 40.32136 | 0.46878 | 10.97784 |
November | 489.00000 | 23.94269 | 29.56873 | 0.34222 | 9.04876 |
December | 497.00000 | 23.62869 | 25.92400 | 0.22320 | 7.48319 |
Annual Sum or Average | 5943.00000 | 23.92714 | 37.12748 | 0.10805 | 8.55318 |
Minimum of Months | 454.00000 | 21.92639 | 24.65961 | -0.2377 | 6.48688 |
Maximum of Months | 514.00000 | 24.55594 | 47.50629 | 0.60616 | 13.82173 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.25330 | 27.77397 | -0.7602 | 19.87894 |
February | 454.00000 | 20.85511 | 29.96840 | -0.5604 | 14.60707 |
March | 514.00000 | 22.08364 | 35.86981 | -0.1585 | 7.84919 |
April | 485.00000 | 23.06987 | 41.67625 | 0.13938 | 7.35293 |
May | 508.00000 | 23.83616 | 47.75425 | -0.5151 | 11.92970 |
June | 496.00000 | 24.19949 | 47.57933 | -0.3364 | 8.21734 |
July | 497.00000 | 24.34162 | 50.38176 | -0.2623 | 7.36956 |
August | 514.00000 | 24.28396 | 50.42784 | -0.2812 | 7.29136 |
September | 485.00000 | 23.88503 | 51.36019 | -0.4779 | 11.29045 |
October | 502.00000 | 22.43596 | 46.11786 | -0.0032 | 6.91876 |
November | 489.00000 | 21.53213 | 35.48093 | -0.3174 | 8.96059 |
December | 497.00000 | 20.59376 | 31.59987 | -0.6068 | 15.19212 |
Annual Sum or Average | 5943.00000 | 22.62798 | 41.41554 | -0.3439 | 10.54002 |
Minimum of Months | 454.00000 | 20.25330 | 27.77397 | -0.7602 | 6.91876 |
Maximum of Months | 514.00000 | 24.34162 | 51.36019 | 0.13938 | 19.87894 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 427.00000 | 20.32353 | 26.50840 | -0.7247 | 18.24511 |
February | 385.00000 | 21.11268 | 28.81098 | -0.4758 | 13.18482 |
March | 433.00000 | 22.37014 | 34.32017 | -0.0665 | 7.36734 |
April | 410.00000 | 23.28614 | 40.46000 | 0.22967 | 8.27772 |
May | 430.00000 | 23.94008 | 46.55759 | -0.4189 | 11.81253 |
June | 418.00000 | 24.29729 | 46.70426 | -0.2469 | 8.16894 |
July | 422.00000 | 24.46251 | 49.30979 | -0.1639 | 8.13520 |
August | 433.00000 | 24.36645 | 49.53166 | -0.2014 | 7.70370 |
September | 410.00000 | 23.85254 | 50.71198 | -0.4306 | 12.00322 |
October | 427.00000 | 22.67655 | 44.55662 | 0.07882 | 7.65109 |
November | 417.00000 | 21.68813 | 34.14239 | -0.2606 | 8.16269 |
December | 422.00000 | 20.61985 | 30.65251 | -0.5799 | 14.04130 |
Annual Sum or Average | 5034.00000 | 22.75972 | 40.25605 | -0.2708 | 10.37567 |
Minimum of Months | 385.00000 | 20.32353 | 26.50840 | -0.7247 | 7.36734 |
Maximum of Months | 433.00000 | 24.46251 | 50.71198 | 0.22967 | 18.24511 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.55025 | 26.07725 | -0.3860 | 13.24962 |
February | 454.00000 | 22.06332 | 28.22362 | -0.2175 | 10.69157 |
March | 514.00000 | 23.11878 | 33.66648 | 0.12479 | 8.18720 |
April | 485.00000 | 23.53565 | 40.26936 | 0.27785 | 8.64981 |
May | 508.00000 | 23.92124 | 47.30635 | -0.4661 | 11.21744 |
June | 496.00000 | 24.18763 | 47.57305 | -0.3353 | 8.47137 |
July | 497.00000 | 24.37411 | 50.21453 | -0.2422 | 7.45323 |
August | 514.00000 | 24.36520 | 49.81409 | -0.2154 | 7.07509 |
September | 485.00000 | 24.14308 | 49.99414 | -0.3305 | 9.57700 |
October | 502.00000 | 23.43588 | 42.93505 | 0.28923 | 9.79448 |
November | 489.00000 | 22.98928 | 32.35145 | 0.07952 | 8.66822 |
December | 497.00000 | 21.97858 | 29.41043 | -0.2161 | 10.46460 |
Annual Sum or Average | 5943.00000 | 23.31463 | 39.90675 | -0.1365 | 9.44828 |
Minimum of Months | 454.00000 | 21.55025 | 26.07725 | -0.4661 | 7.07509 |
Maximum of Months | 514.00000 | 24.37411 | 50.21453 | 0.28923 | 13.24962 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.60633 | 26.68220 | -0.6359 | 16.04662 |
February | 454.00000 | 21.23215 | 28.81903 | -0.4286 | 12.14295 |
March | 514.00000 | 22.52294 | 34.36824 | -0.0060 | 7.82469 |
April | 485.00000 | 23.38968 | 40.33483 | 0.27542 | 8.93013 |
May | 508.00000 | 23.87247 | 46.89364 | -0.4193 | 11.13701 |
June | 496.00000 | 24.22491 | 46.84933 | -0.2472 | 8.09026 |
July | 497.00000 | 24.37104 | 49.40558 | -0.1735 | 7.55462 |
August | 514.00000 | 24.37387 | 49.14051 | -0.1633 | 7.09347 |
September | 485.00000 | 23.90541 | 50.40525 | -0.3931 | 11.06223 |
October | 502.00000 | 22.74896 | 44.45589 | 0.11400 | 7.86410 |
November | 489.00000 | 21.91383 | 34.01631 | -0.1910 | 8.04697 |
December | 497.00000 | 20.98304 | 30.42757 | -0.4775 | 12.02943 |
Annual Sum or Average | 5943.00000 | 22.85823 | 40.23185 | -0.2277 | 9.79622 |
Minimum of Months | 454.00000 | 20.60633 | 26.68220 | -0.6359 | 7.09347 |
Maximum of Months | 514.00000 | 24.37387 | 50.40525 | 0.27542 | 16.04662 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.99436 | 28.43147 | -0.8660 | 24.28191 |
February | 454.00000 | 20.60030 | 30.48864 | -0.6572 | 17.35031 |
March | 514.00000 | 21.68733 | 36.66528 | -0.2725 | 9.82289 |
April | 485.00000 | 22.73913 | 42.48850 | 0.05630 | 7.75167 |
May | 508.00000 | 23.70683 | 48.22068 | -0.5495 | 13.50574 |
June | 496.00000 | 24.16987 | 47.74964 | -0.3299 | 8.61798 |
July | 497.00000 | 24.33821 | 50.64352 | -0.2444 | 7.63701 |
August | 514.00000 | 24.29226 | 50.67368 | -0.2599 | 7.31092 |
September | 485.00000 | 23.70805 | 52.20617 | -0.5319 | 13.30045 |
October | 502.00000 | 22.00672 | 47.40071 | -0.1215 | 7.95076 |
November | 489.00000 | 20.98752 | 36.63588 | -0.4795 | 12.37905 |
December | 497.00000 | 20.21082 | 32.44203 | -0.7434 | 20.05506 |
Annual Sum or Average | 5943.00000 | 22.38475 | 42.08600 | -0.4150 | 12.45611 |
Minimum of Months | 454.00000 | 19.99436 | 28.43147 | -0.8660 | 7.31092 |
Maximum of Months | 514.00000 | 24.33821 | 52.20617 | 0.05630 | 24.28191 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.08261 | 27.83597 | -0.8123 | 22.09626 |
February | 454.00000 | 20.88816 | 29.60542 | -0.5532 | 15.18592 |
March | 514.00000 | 22.14543 | 35.41339 | -0.1296 | 8.21470 |
April | 485.00000 | 23.13674 | 41.13957 | 0.20009 | 8.48953 |
May | 508.00000 | 23.86408 | 46.93101 | -0.4160 | 11.95130 |
June | 496.00000 | 24.25189 | 46.75570 | -0.2211 | 7.98862 |
July | 497.00000 | 24.37288 | 49.46432 | -0.1496 | 8.24447 |
August | 514.00000 | 24.31551 | 49.57009 | -0.1748 | 7.45261 |
September | 485.00000 | 23.72550 | 51.12118 | -0.4510 | 12.88060 |
October | 502.00000 | 22.43385 | 45.57956 | 0.01222 | 8.13027 |
November | 489.00000 | 21.23634 | 35.55272 | -0.3903 | 10.29169 |
December | 497.00000 | 20.28094 | 31.87373 | -0.6929 | 18.25790 |
Annual Sum or Average | 5943.00000 | 22.57530 | 40.98360 | -0.3132 | 11.56378 |
Minimum of Months | 454.00000 | 20.08261 | 27.83597 | -0.8123 | 7.45261 |
Maximum of Months | 514.00000 | 24.37288 | 51.12118 | 0.20009 | 22.09626 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.01127 | 27.01383 | -0.5452 | 17.08823 |
February | 454.00000 | 21.64670 | 28.87392 | -0.3437 | 13.00255 |
March | 514.00000 | 22.70088 | 34.51703 | 0.00863 | 8.99760 |
April | 485.00000 | 23.18477 | 41.15501 | 0.19192 | 8.71749 |
May | 508.00000 | 23.75507 | 47.82174 | -0.5102 | 13.03155 |
June | 496.00000 | 24.12826 | 47.77078 | -0.3372 | 9.09613 |
July | 497.00000 | 24.33239 | 50.49808 | -0.2353 | 7.85034 |
August | 514.00000 | 24.34554 | 50.07221 | -0.2020 | 7.18075 |
September | 485.00000 | 23.95403 | 50.82652 | -0.3867 | 11.47175 |
October | 502.00000 | 23.03728 | 44.14645 | 0.17936 | 9.84088 |
November | 489.00000 | 22.38039 | 33.60542 | -0.0919 | 9.71830 |
December | 497.00000 | 21.35050 | 30.55240 | -0.3973 | 14.12640 |
Annual Sum or Average | 5943.00000 | 22.99643 | 40.65691 | -0.2220 | 10.82541 |
Minimum of Months | 454.00000 | 21.01127 | 27.01383 | -0.5452 | 7.18075 |
Maximum of Months | 514.00000 | 24.34554 | 50.82652 | 0.19192 | 17.08823 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.26331 | 27.43903 | -0.7535 | 20.43159 |
February | 454.00000 | 20.96351 | 29.28907 | -0.5198 | 14.46145 |
March | 514.00000 | 22.18579 | 35.07406 | -0.1015 | 8.93577 |
April | 485.00000 | 23.06313 | 41.13508 | 0.19683 | 8.96162 |
May | 508.00000 | 23.69685 | 47.43003 | -0.4651 | 12.94939 |
June | 496.00000 | 24.14997 | 47.10020 | -0.2542 | 8.82409 |
July | 497.00000 | 24.31490 | 49.73907 | -0.1716 | 8.08684 |
August | 514.00000 | 24.33707 | 49.42898 | -0.1558 | 7.32934 |
September | 485.00000 | 23.69183 | 51.23934 | -0.4554 | 13.20797 |
October | 502.00000 | 22.39299 | 45.49077 | 0.01660 | 8.20875 |
November | 489.00000 | 21.45563 | 34.93923 | -0.3260 | 10.04175 |
December | 497.00000 | 20.56368 | 31.24921 | -0.6096 | 16.06500 |
Annual Sum or Average | 5943.00000 | 22.60351 | 40.87780 | -0.2984 | 11.42931 |
Minimum of Months | 454.00000 | 20.26331 | 27.43903 | -0.7535 | 7.32934 |
Maximum of Months | 514.00000 | 24.33707 | 51.23934 | 0.19683 | 20.43159 |
Report: ChillerReportMonthly
For: COOLSYS1 CHILLER1
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportCHILLER ELECTRICITY ENERGY [J] | CHILLER ELECTRICITY RATE {Maximum} [W] | CHILLER ELECTRICITY RATE {TIMESTAMP} | CHILLER ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | CHILLER EVAPORATOR COOLING ENERGY [J] | CHILLER EVAPORATOR COOLING RATE [] | CHILLER CONDENSER HEAT TRANSFER ENERGY [J] | CHILLER COP [W/W] | CHILLER COP {Maximum} [W/W] | CHILLER COP {TIMESTAMP} | CHILLER PART LOAD RATIO [] | CHILLER PART LOAD RATIO [] | |
January | 0.909171E+10 | 77801.23 | 19-JAN-16:00 | 111.97 | 0.455573E+11 | 0.00 | 0.546490E+11 | 0.68 | 6.28 | 19-JAN-16:00 | 0.00 | 0.00 |
February | 0.253639E+11 | 125051.97 | 28-FEB-15:10 | 180.71 | 0.132335E+12 | 0.00 | 0.157699E+12 | 1.27 | 7.37 | 28-FEB-15:10 | 0.00 | 0.00 |
March | 0.640206E+11 | 205053.77 | 30-MAR-14:20 | 318.15 | 0.376158E+12 | 0.00 | 0.440178E+12 | 2.21 | 7.44 | 30-MAR-15:00 | 0.00 | 0.00 |
April | 0.106250E+12 | 205877.72 | 19-APR-14:30 | 415.67 | 0.684155E+12 | 0.00 | 0.790405E+12 | 3.27 | 7.56 | 13-APR-15:50 | 0.00 | 0.00 |
May | 0.177046E+12 | 212100.23 | 31-MAY-15:10 | 463.33 | 0.121691E+13 | 0.00 | 0.139395E+13 | 4.06 | 7.55 | 30-MAY-05:05 | 0.00 | 0.00 |
June | 0.209996E+12 | 217534.09 | 29-JUN-17:10 | 520.51 | 0.143789E+13 | 0.00 | 0.164789E+13 | 4.69 | 7.57 | 08-JUN-16:00 | 0.00 | 0.00 |
July | 0.235485E+12 | 219776.80 | 08-JUL-10:30 | 603.72 | 0.159202E+13 | 0.00 | 0.182750E+13 | 5.07 | 7.56 | 25-JUL-04:13 | 0.00 | 0.00 |
August | 0.250731E+12 | 220161.64 | 22-AUG-17:10 | 667.78 | 0.168477E+13 | 0.00 | 0.193550E+13 | 5.50 | 7.53 | 30-AUG-04:14 | 0.00 | 0.00 |
September | 0.184706E+12 | 214327.33 | 08-SEP-17:00 | 461.32 | 0.126856E+13 | 0.00 | 0.145327E+13 | 4.17 | 7.57 | 14-SEP-14:20 | 0.00 | 0.00 |
October | 0.953931E+11 | 215501.49 | 18-OCT-11:40 | 341.20 | 0.611798E+12 | 0.00 | 0.707191E+12 | 2.61 | 7.54 | 11-OCT-15:50 | 0.00 | 0.00 |
November | 0.454398E+11 | 129892.03 | 02-NOV-13:10 | 256.59 | 0.261590E+12 | 0.00 | 0.307030E+12 | 1.82 | 7.35 | 02-NOV-13:40 | 0.00 | 0.00 |
December | 0.170016E+11 | 113800.62 | 12-DEC-14:00 | 140.90 | 0.926918E+11 | 0.00 | 0.109693E+12 | 0.90 | 7.23 | 12-DEC-14:00 | 0.00 | 0.00 |
Annual Sum or Average | 0.142052E+13 | 4481.85 | 0.940444E+13 | 0.00 | 0.108250E+14 | 3.03 | 0.00 | 0.00 | ||||
Minimum of Months | 0.909171E+10 | 77801.23 | 111.97 | 0.455573E+11 | 0.00 | 0.546490E+11 | 0.68 | 6.28 | 0.00 | 0.00 | ||
Maximum of Months | 0.250731E+12 | 220161.64 | 667.78 | 0.168477E+13 | 0.00 | 0.193550E+13 | 5.50 | 7.57 | 0.00 | 0.00 |
Report: ChillerReportMonthly
For: COOLSYS1 CHILLER2
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportCHILLER ELECTRICITY ENERGY [J] | CHILLER ELECTRICITY RATE {Maximum} [W] | CHILLER ELECTRICITY RATE {TIMESTAMP} | CHILLER ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | CHILLER EVAPORATOR COOLING ENERGY [J] | CHILLER EVAPORATOR COOLING RATE [] | CHILLER CONDENSER HEAT TRANSFER ENERGY [J] | CHILLER COP [W/W] | CHILLER COP {Maximum} [W/W] | CHILLER COP {TIMESTAMP} | CHILLER PART LOAD RATIO [] | CHILLER PART LOAD RATIO [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
March | 0.221100E+09 | 115806.90 | 30-MAR-15:20 | 0.67 | 0.155040E+10 | 0.00 | 0.177150E+10 | 0.01 | 7.22 | 30-MAR-15:20 | 0.00 | 0.00 |
April | 0.889066E+09 | 126513.58 | 18-APR-12:50 | 2.67 | 0.623156E+10 | 0.00 | 0.712062E+10 | 0.02 | 7.36 | 17-APR-14:05 | 0.00 | 0.00 |
May | 0.125177E+11 | 128595.44 | 30-MAY-14:40 | 30.50 | 0.875754E+11 | 0.00 | 0.100093E+12 | 0.29 | 7.27 | 16-MAY-15:50 | 0.00 | 0.00 |
June | 0.533738E+11 | 165625.35 | 29-JUN-05:04 | 125.00 | 0.362713E+12 | 0.00 | 0.416087E+12 | 1.18 | 7.35 | 30-JUN-05:02 | 0.00 | 0.00 |
July | 0.671516E+11 | 152024.17 | 01-JUL-04:14 | 155.16 | 0.454189E+12 | 0.00 | 0.521340E+12 | 1.41 | 7.24 | 18-JUL-05:06 | 0.00 | 0.00 |
August | 0.890941E+11 | 175880.89 | 23-AUG-05:02 | 202.17 | 0.599587E+12 | 0.00 | 0.688681E+12 | 1.82 | 7.47 | 23-AUG-05:02 | 0.00 | 0.00 |
September | 0.298639E+11 | 145408.41 | 16-SEP-16:07 | 70.00 | 0.204394E+12 | 0.00 | 0.234257E+12 | 0.66 | 7.26 | 18-SEP-14:30 | 0.00 | 0.00 |
October | 0.771405E+10 | 154880.00 | 19-OCT-04:15 | 18.39 | 0.534671E+11 | 0.00 | 0.611811E+11 | 0.17 | 7.18 | 19-OCT-15:20 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.260825E+12 | 604.56 | 0.176971E+13 | 0.00 | 0.203053E+13 | 0.47 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.890941E+11 | 175880.89 | 202.17 | 0.599587E+12 | 0.00 | 0.688681E+12 | 1.82 | 7.47 | 0.00 | 0.00 |
Report: TowerReportMonthly
For: CENTRAL TOWER
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportCOOLING TOWER FAN ELECTRICITY ENERGY [J] | COOLING TOWER FAN ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | COOLING TOWER FAN ELECTRICITY RATE {Maximum} [W] | COOLING TOWER FAN ELECTRICITY RATE {TIMESTAMP} | COOLING TOWER HEAT TRANSFER RATE {Maximum} [W] | COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} | COOLING TOWER INLET TEMPERATURE [C] | COOLING TOWER OUTLET TEMPERATURE [C] | COOLING TOWER MASS FLOW RATE [kg/s] | |
January | 0.189564E+11 | 744.00 | 49248.27 | 19-JAN-12:00 | 333566.60 | 10-JAN-13:43 | 21.69 | 18.38 | 14.28 |
February | 0.502406E+11 | 672.00 | 49248.27 | 01-FEB-19:00 | 374846.03 | 09-FEB-11:05 | 25.12 | 18.91 | 14.32 |
March | 0.102535E+12 | 744.00 | 49248.27 | 01-MAR-00:10 | 596246.11 | 31-MAR-24:00 | 29.81 | 20.51 | 14.34 |
April | 0.120249E+12 | 720.00 | 49248.27 | 01-APR-09:30 | 675725.13 | 17-APR-16:10 | 35.97 | 23.65 | 14.35 |
May | 0.122364E+12 | 744.00 | 49248.27 | 01-MAY-00:03 | 340252.65 | 31-MAY-23:40 | 27.06 | 23.06 | 14.35 |
June | 0.126536E+12 | 720.00 | 49248.27 | 01-JUN-00:10 | 490663.24 | 30-JUN-24:00 | 35.33 | 28.14 | 14.35 |
July | 0.131907E+12 | 744.00 | 49248.27 | 01-JUL-00:10 | 653540.79 | 31-JUL-23:55 | 41.02 | 30.78 | 14.35 |
August | 0.131907E+12 | 744.00 | 49248.27 | 01-AUG-00:03 | 711405.54 | 11-AUG-16:30 | 45.79 | 32.65 | 14.35 |
September | 0.123479E+12 | 720.00 | 49248.27 | 01-SEP-00:03 | 317887.48 | 30-SEP-24:00 | 28.68 | 24.55 | 14.35 |
October | 0.101170E+12 | 744.00 | 49248.27 | 01-OCT-00:10 | 453545.61 | 31-OCT-24:00 | 27.71 | 21.05 | 14.33 |
November | 0.898704E+11 | 720.00 | 49248.27 | 01-NOV-10:35 | 513217.11 | 02-NOV-14:10 | 29.08 | 19.84 | 14.34 |
December | 0.814443E+11 | 744.00 | 49248.27 | 04-DEC-15:20 | 657176.30 | 12-DEC-15:10 | 30.61 | 18.86 | 14.34 |
Annual Sum or Average | 0.120066E+13 | 8760.00 | 31.53 | 23.40 | 14.34 | ||||
Minimum of Months | 0.189564E+11 | 672.00 | 49248.27 | 317887.48 | 21.69 | 18.38 | 14.28 | ||
Maximum of Months | 0.131907E+12 | 744.00 | 49248.27 | 711405.54 | 45.79 | 32.65 | 14.35 |
Report: TowerReportMonthly
For: TOWERWATERSYS COOLTOWER 1
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportCOOLING TOWER FAN ELECTRICITY ENERGY [J] | COOLING TOWER FAN ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | COOLING TOWER FAN ELECTRICITY RATE {Maximum} [W] | COOLING TOWER FAN ELECTRICITY RATE {TIMESTAMP} | COOLING TOWER HEAT TRANSFER RATE {Maximum} [W] | COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} | COOLING TOWER INLET TEMPERATURE [C] | COOLING TOWER OUTLET TEMPERATURE [C] | COOLING TOWER MASS FLOW RATE [kg/s] | |
January | 0.103156E+09 | 37.48 | 2170.97 | 19-JAN-22:00 | 581447.72 | 19-JAN-16:00 | 21.02 | 20.95 | 5.23 |
February | 0.158959E+09 | 104.16 | 2238.19 | 28-FEB-15:00 | 1062309.43 | 28-FEB-15:10 | 21.32 | 21.10 | 14.50 |
March | 0.239949E+10 | 213.49 | 21789.67 | 28-MAR-13:10 | 1564600.99 | 30-MAR-16:00 | 21.76 | 21.21 | 26.98 |
April | 0.622457E+10 | 339.10 | 21789.67 | 04-APR-08:20 | 1637424.26 | 19-APR-16:00 | 22.29 | 21.27 | 39.65 |
May | 0.206875E+11 | 449.61 | 21789.67 | 01-MAY-12:00 | 1554694.68 | 15-MAY-15:50 | 23.85 | 22.16 | 44.45 |
June | 0.320137E+11 | 509.99 | 21789.67 | 01-JUN-04:12 | 1602297.20 | 02-JUN-11:00 | 25.22 | 23.17 | 48.99 |
July | 0.436177E+11 | 603.41 | 21789.67 | 01-JUL-04:11 | 1430292.38 | 25-JUL-08:00 | 26.15 | 23.93 | 53.41 |
August | 0.505073E+11 | 667.78 | 21789.67 | 01-AUG-00:03 | 1498978.09 | 25-AUG-09:10 | 26.76 | 24.42 | 59.19 |
September | 0.262907E+11 | 451.30 | 21789.67 | 01-SEP-04:14 | 1615286.88 | 13-SEP-04:12 | 25.12 | 23.30 | 44.27 |
October | 0.796599E+10 | 277.81 | 21789.67 | 01-OCT-12:22 | 1416349.76 | 10-OCT-09:50 | 22.65 | 21.79 | 30.04 |
November | 0.138938E+10 | 165.07 | 21789.67 | 02-NOV-12:30 | 1099734.86 | 02-NOV-13:20 | 21.59 | 21.19 | 21.78 |
December | 0.277068E+09 | 52.60 | 5278.74 | 13-DEC-11:10 | 949970.27 | 12-DEC-14:00 | 21.14 | 21.00 | 8.74 |
Annual Sum or Average | 0.191636E+12 | 3871.81 | 23.25 | 22.13 | 33.19 | ||||
Minimum of Months | 0.103156E+09 | 37.48 | 2170.97 | 581447.72 | 21.02 | 20.95 | 5.23 | ||
Maximum of Months | 0.505073E+11 | 667.78 | 21789.67 | 1637424.26 | 26.76 | 24.42 | 59.19 |
Report: TowerReportMonthly
For: TOWERWATERSYS COOLTOWER 2
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportCOOLING TOWER FAN ELECTRICITY ENERGY [J] | COOLING TOWER FAN ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | COOLING TOWER FAN ELECTRICITY RATE {Maximum} [W] | COOLING TOWER FAN ELECTRICITY RATE {TIMESTAMP} | COOLING TOWER HEAT TRANSFER RATE {Maximum} [W] | COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} | COOLING TOWER INLET TEMPERATURE [C] | COOLING TOWER OUTLET TEMPERATURE [C] | COOLING TOWER MASS FLOW RATE [kg/s] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 21.02 | 21.02 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 21.32 | 21.32 | 0.00 |
March | 78442809.36 | 1.00 | 21789.67 | 29-MAR-16:00 | 1209209.25 | 30-MAR-15:20 | 21.76 | 21.76 | 0.07 |
April | 0.445583E+09 | 5.83 | 21789.67 | 04-APR-10:40 | 1313326.83 | 18-APR-12:40 | 22.29 | 22.25 | 0.41 |
May | 0.475102E+10 | 60.57 | 21789.67 | 02-MAY-12:20 | 1104530.38 | 18-MAY-15:20 | 23.85 | 23.51 | 4.62 |
June | 0.171526E+11 | 218.66 | 21789.67 | 01-JUN-07:50 | 1169423.25 | 02-JUN-15:50 | 25.22 | 24.11 | 18.12 |
July | 0.234699E+11 | 299.20 | 21789.67 | 01-JUL-04:11 | 1170728.84 | 01-JUL-04:13 | 26.15 | 24.64 | 23.00 |
August | 0.281283E+11 | 358.58 | 21789.67 | 01-AUG-06:20 | 1153288.63 | 24-AUG-10:50 | 26.76 | 25.01 | 28.32 |
September | 0.102932E+11 | 131.22 | 21789.67 | 01-SEP-09:20 | 1192206.19 | 12-SEP-04:13 | 25.12 | 24.43 | 10.48 |
October | 0.316386E+10 | 40.33 | 21789.67 | 02-OCT-09:00 | 1033705.77 | 19-OCT-15:10 | 22.65 | 22.43 | 2.97 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 21.59 | 21.59 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 21.14 | 21.14 | 0.00 |
Annual Sum or Average | 0.874829E+11 | 1115.40 | 23.25 | 22.77 | 7.40 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 21.02 | 21.02 | 0.00 | ||
Maximum of Months | 0.281283E+11 | 358.58 | 21789.67 | 1313326.83 | 26.76 | 25.01 | 28.32 |
Report: BoilerReportMonthly
For: HEATSYS1 BOILER
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportBOILER HEATING ENERGY [J] | BOILER GAS CONSUMPTION [] | BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] | BOILER HEATING RATE {Maximum} [W] | BOILER HEATING RATE {TIMESTAMP} | BOILER GAS CONSUMPTION RATE [] | BOILER INLET TEMPERATURE [C] | BOILER OUTLET TEMPERATURE [C] | BOILER MASS FLOW RATE [kg/s] | BOILER ANCILLARY ELECTRICITY RATE [W] | BOILER PART LOAD RATIO [] | BOILER PART LOAD RATIO {Maximum} [] | BOILER PART LOAD RATIO {TIMESTAMP} | |
January | 0.288624E+12 | 0.00 | 506.85 | 1701386.63 | 02-JAN-06:01 | 0.00 | 28.87 | 64.06 | 0.59 | 0.00 | 0.04 | 0.69 | 02-JAN-06:01 |
February | 0.164584E+12 | 0.00 | 360.28 | 1636699.86 | 06-FEB-06:02 | 0.00 | 25.49 | 54.12 | 0.36 | 0.00 | 0.03 | 0.66 | 06-FEB-06:02 |
March | 0.294795E+11 | 0.00 | 185.00 | 1531292.97 | 22-MAR-04:11 | 0.00 | 21.34 | 36.05 | 0.05 | 0.00 | 0.00 | 0.62 | 22-MAR-04:11 |
April | 0.743743E+10 | 0.00 | 86.01 | 1066652.84 | 06-APR-05:03 | 0.00 | 33.33 | 39.66 | 0.01 | 0.00 | 0.00 | 0.43 | 06-APR-05:03 |
May | 0.653512E+09 | 0.00 | 16.81 | 51824.29 | 10-MAY-06:10 | 0.00 | 29.12 | 30.35 | 0.00 | 0.00 | 0.00 | 0.02 | 10-MAY-06:10 |
June | 73318137.87 | 0.00 | 4.92 | 24086.49 | 10-JUN-13:10 | 0.00 | 40.18 | 40.49 | 0.00 | 0.00 | 0.00 | 0.01 | 10-JUN-13:10 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 41.86 | 41.86 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 41.86 | 41.86 | 0.00 | 0.00 | 0.00 | 0.00 | 01-AUG-00:03 |
September | 0.131175E+09 | 0.00 | 19.49 | 28418.50 | 14-SEP-15:50 | 0.00 | 41.78 | 42.96 | 0.00 | 0.00 | 0.00 | 0.01 | 14-SEP-15:50 |
October | 0.156607E+11 | 0.00 | 146.01 | 1092865.74 | 31-OCT-05:03 | 0.00 | 21.85 | 33.72 | 0.02 | 0.00 | 0.00 | 0.44 | 31-OCT-05:03 |
November | 0.489511E+11 | 0.00 | 264.50 | 1439935.14 | 25-NOV-05:01 | 0.00 | 21.28 | 42.88 | 0.09 | 0.00 | 0.01 | 0.58 | 25-NOV-05:01 |
December | 0.137879E+12 | 0.00 | 415.70 | 1556218.68 | 26-DEC-06:02 | 0.00 | 24.42 | 55.60 | 0.26 | 0.00 | 0.02 | 0.63 | 26-DEC-06:02 |
Annual Sum or Average | 0.693473E+12 | 0.00 | 2005.56 | 0.00 | 30.96 | 43.57 | 0.11 | 0.00 | 0.01 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.28 | 30.35 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.288624E+12 | 0.00 | 506.85 | 1701386.63 | 0.00 | 41.86 | 64.06 | 0.59 | 0.00 | 0.04 | 0.69 |
Report: BoilerReportMonthly
For: CENTRAL BOILER
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportBOILER HEATING ENERGY [J] | BOILER GAS CONSUMPTION [] | BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] | BOILER HEATING RATE {Maximum} [W] | BOILER HEATING RATE {TIMESTAMP} | BOILER GAS CONSUMPTION RATE [] | BOILER INLET TEMPERATURE [C] | BOILER OUTLET TEMPERATURE [C] | BOILER MASS FLOW RATE [kg/s] | BOILER ANCILLARY ELECTRICITY RATE [W] | BOILER PART LOAD RATIO [] | BOILER PART LOAD RATIO [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 21.69 | 21.69 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 25.12 | 25.12 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 29.81 | 29.81 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 35.97 | 35.97 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 27.06 | 27.06 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 35.33 | 35.33 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 41.02 | 41.02 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 45.79 | 45.79 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 28.68 | 28.68 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 27.71 | 27.71 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 29.08 | 29.08 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 30.61 | 30.61 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 31.53 | 31.53 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.69 | 21.69 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45.79 | 45.79 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: VAV_BOT WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.418628E+10 | 0.00 | 90.83 | 0.325438E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 49577.65 | 19-JAN-16:00 | 43463.20 | 31-JAN-15:00 | 0.00 | 0.00 | 0.00 |
February | 0.129807E+11 | 0.00 | 162.03 | 0.119387E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 87790.55 | 28-FEB-15:00 | 87790.55 | 28-FEB-15:00 | 0.00 | 0.00 | 0.00 |
March | 0.371894E+11 | 0.00 | 304.57 | 0.329776E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 128454.66 | 30-MAR-15:20 | 128454.66 | 30-MAR-15:20 | 0.00 | 0.00 | 0.00 |
April | 0.709594E+11 | 0.00 | 407.40 | 0.637861E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 167098.76 | 17-APR-15:30 | 167098.76 | 17-APR-15:30 | 0.00 | 0.00 | 0.00 |
May | 0.108026E+12 | 0.00 | 448.86 | 0.845171E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 193635.85 | 31-MAY-05:03 | 164835.26 | 30-MAY-04:12 | 0.00 | 0.00 | 0.00 |
June | 0.153777E+12 | 0.00 | 505.37 | 0.122204E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 213687.23 | 16-JUN-04:11 | 164037.60 | 20-JUN-04:11 | 0.00 | 0.00 | 0.00 |
July | 0.182750E+12 | 0.00 | 574.70 | 0.139273E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 214129.59 | 01-JUL-04:11 | 163114.09 | 01-JUL-04:11 | 0.00 | 0.00 | 0.00 |
August | 0.212940E+12 | 0.00 | 643.47 | 0.162510E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 185156.23 | 12-AUG-05:02 | 162289.96 | 07-AUG-05:02 | 0.00 | 0.00 | 0.00 |
September | 0.123099E+12 | 0.00 | 441.99 | 0.926115E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 208129.89 | 27-SEP-04:11 | 167778.20 | 05-SEP-04:12 | 0.00 | 0.00 | 0.00 |
October | 0.608539E+11 | 0.00 | 324.28 | 0.477557E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 235688.64 | 19-OCT-04:12 | 154541.19 | 19-OCT-04:12 | 0.00 | 0.00 | 0.00 |
November | 0.271954E+11 | 0.00 | 241.37 | 0.232311E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 114994.50 | 27-NOV-05:12 | 114994.50 | 27-NOV-05:12 | 0.00 | 0.00 | 0.00 |
December | 0.103734E+11 | 0.00 | 127.36 | 0.790705E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 98865.46 | 12-DEC-14:00 | 75959.05 | 12-DEC-14:10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.100433E+13 | 0.00 | 4272.25 | 0.791967E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.418628E+10 | 0.00 | 90.83 | 0.325438E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 49577.65 | 43463.20 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.212940E+12 | 0.00 | 643.47 | 0.162510E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 235688.64 | 167778.20 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: VAV_MID WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.349320E+11 | 0.00 | 71.03 | 0.269659E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 391845.64 | 19-JAN-22:00 | 308832.93 | 31-JAN-15:00 | 0.00 | 0.00 | 0.00 |
February | 0.101155E+12 | 0.00 | 150.98 | 0.918812E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 653877.50 | 28-FEB-15:00 | 653877.50 | 28-FEB-15:00 | 0.00 | 0.00 | 0.00 |
March | 0.282113E+12 | 0.00 | 289.02 | 0.250755E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1096174.49 | 30-MAR-15:20 | 1096174.49 | 30-MAR-15:20 | 0.00 | 0.00 | 0.00 |
April | 0.509438E+12 | 0.00 | 350.55 | 0.456356E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1289759.78 | 17-APR-14:30 | 1289759.78 | 17-APR-14:30 | 0.00 | 0.00 | 0.00 |
May | 0.944928E+12 | 0.00 | 436.82 | 0.725085E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1775638.32 | 31-MAY-05:03 | 1315432.83 | 30-MAY-05:03 | 0.00 | 0.00 | 0.00 |
June | 0.131898E+13 | 0.00 | 456.93 | 0.100441E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 2047154.54 | 30-JUN-05:02 | 1510650.96 | 29-JUN-05:02 | 0.00 | 0.00 | 0.00 |
July | 0.149738E+13 | 0.00 | 467.97 | 0.106167E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 2010011.17 | 14-JUL-04:12 | 1515440.38 | 14-JUL-04:12 | 0.00 | 0.00 | 0.00 |
August | 0.167177E+13 | 0.00 | 491.72 | 0.116374E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 2301627.01 | 23-AUG-05:02 | 1519502.39 | 17-AUG-04:12 | 0.00 | 0.00 | 0.00 |
September | 0.107676E+13 | 0.00 | 425.58 | 0.781454E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 2038906.50 | 27-SEP-04:11 | 1497019.37 | 11-SEP-05:02 | 0.00 | 0.00 | 0.00 |
October | 0.481617E+12 | 0.00 | 309.41 | 0.363932E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1941680.82 | 19-OCT-04:12 | 1107534.64 | 19-OCT-05:03 | 0.00 | 0.00 | 0.00 |
November | 0.196320E+12 | 0.00 | 228.14 | 0.164516E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 672240.39 | 04-NOV-05:03 | 527683.98 | 08-NOV-15:00 | 0.00 | 0.00 | 0.00 |
December | 0.683327E+11 | 0.00 | 121.28 | 0.516345E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 563451.24 | 12-DEC-14:00 | 453758.56 | 12-DEC-14:10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.818373E+13 | 0.00 | 3799.43 | 0.614239E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.349320E+11 | 0.00 | 71.03 | 0.269659E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 391845.64 | 308832.93 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.167177E+13 | 0.00 | 491.72 | 0.116374E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 2301627.01 | 1519502.39 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: VAV_TOP WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.349096E+10 | 0.00 | 93.75 | 0.267261E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 40197.45 | 19-JAN-22:00 | 31293.88 | 31-JAN-15:00 | 0.00 | 0.00 | 0.00 |
February | 0.973973E+10 | 0.00 | 154.09 | 0.879443E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 61977.71 | 28-FEB-15:30 | 61977.71 | 28-FEB-15:30 | 0.00 | 0.00 | 0.00 |
March | 0.277521E+11 | 0.00 | 284.39 | 0.245935E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 119355.63 | 30-MAR-14:20 | 119228.09 | 30-MAR-15:10 | 0.00 | 0.00 | 0.00 |
April | 0.522745E+11 | 0.00 | 344.33 | 0.469645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 128673.21 | 17-APR-15:50 | 128673.21 | 17-APR-15:50 | 0.00 | 0.00 | 0.00 |
May | 0.101586E+12 | 0.00 | 430.72 | 0.789405E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 158202.96 | 31-MAY-05:03 | 142063.45 | 16-MAY-16:00 | 0.00 | 0.00 | 0.00 |
June | 0.144690E+12 | 0.00 | 456.54 | 0.112237E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 224993.49 | 26-JUN-04:12 | 163604.83 | 26-JUN-04:12 | 0.00 | 0.00 | 0.00 |
July | 0.163866E+12 | 0.00 | 470.87 | 0.119373E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 220443.80 | 31-JUL-04:11 | 161631.89 | 14-JUL-04:12 | 0.00 | 0.00 | 0.00 |
August | 0.181702E+12 | 0.00 | 495.19 | 0.129900E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 256142.79 | 23-AUG-05:02 | 163986.73 | 23-AUG-05:02 | 0.00 | 0.00 | 0.00 |
September | 0.110976E+12 | 0.00 | 420.08 | 0.812888E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 206225.00 | 05-SEP-05:02 | 149821.54 | 07-SEP-05:02 | 0.00 | 0.00 | 0.00 |
October | 0.483804E+11 | 0.00 | 304.87 | 0.359076E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 202558.16 | 19-OCT-04:12 | 106497.60 | 18-OCT-05:02 | 0.00 | 0.00 | 0.00 |
November | 0.183911E+11 | 0.00 | 225.68 | 0.152563E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 63177.20 | 03-NOV-15:00 | 50665.94 | 02-NOV-14:30 | 0.00 | 0.00 | 0.00 |
December | 0.670704E+10 | 0.00 | 127.93 | 0.503672E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 56784.57 | 12-DEC-14:00 | 44815.95 | 12-DEC-14:00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.869555E+12 | 0.00 | 3808.47 | 0.660964E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.349096E+10 | 0.00 | 93.75 | 0.267261E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 40197.45 | 31293.88 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.181702E+12 | 0.00 | 495.19 | 0.129900E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 256142.79 | 163986.73 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: CAV_BAS COOLING COIL
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.577388E+09 | 0.00 | 14.48 | 0.561106E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 60662.59 | 20-JAN-05:23 | 30826.23 | 31-JAN-15:00 | 0.00 | 0.00 | 0.00 |
February | 0.423326E+10 | 0.00 | 45.75 | 0.421127E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 76165.51 | 18-FEB-06:02 | 62551.44 | 28-FEB-15:00 | 0.00 | 0.00 | 0.00 |
March | 0.135794E+11 | 0.00 | 139.75 | 0.135220E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 102769.19 | 30-MAR-05:03 | 81836.23 | 30-MAR-14:00 | 0.00 | 0.00 | 0.00 |
April | 0.290157E+11 | 0.00 | 221.89 | 0.285580E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 104988.40 | 03-APR-04:12 | 104988.40 | 03-APR-04:12 | 0.00 | 0.00 | 0.00 |
May | 0.516525E+11 | 0.00 | 341.25 | 0.475012E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 135025.59 | 31-MAY-04:12 | 93055.93 | 16-MAY-16:00 | 0.00 | 0.00 | 0.00 |
June | 0.893055E+11 | 0.00 | 393.62 | 0.760581E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 157713.48 | 23-JUN-04:12 | 118206.68 | 12-JUN-04:12 | 0.00 | 0.00 | 0.00 |
July | 0.100403E+12 | 0.00 | 397.56 | 0.807227E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 162673.87 | 08-JUL-03:02 | 98117.14 | 05-JUL-04:12 | 0.00 | 0.00 | 0.00 |
August | 0.120344E+12 | 0.00 | 452.56 | 0.945161E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 184663.80 | 06-AUG-17:31 | 102066.49 | 27-AUG-17:59 | 0.00 | 0.00 | 0.00 |
September | 0.758328E+11 | 0.00 | 371.00 | 0.647648E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 179768.22 | 10-SEP-15:52 | 106016.04 | 04-SEP-23:22 | 0.00 | 0.00 | 0.00 |
October | 0.329230E+11 | 0.00 | 211.87 | 0.278620E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 152244.76 | 19-OCT-04:53 | 109307.32 | 09-OCT-17:30 | 0.00 | 0.00 | 0.00 |
November | 0.105310E+11 | 0.00 | 116.31 | 0.993063E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 99535.69 | 27-NOV-06:03 | 75440.32 | 20-NOV-01:13 | 0.00 | 0.00 | 0.00 |
December | 0.307062E+10 | 0.00 | 35.75 | 0.283080E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 96908.29 | 13-DEC-06:03 | 51718.02 | 12-DEC-15:00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.531468E+12 | 0.00 | 2741.79 | 0.451039E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.577388E+09 | 0.00 | 14.48 | 0.561106E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 60662.59 | 30826.23 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.120344E+12 | 0.00 | 452.56 | 0.945161E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 184663.80 | 118206.68 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: AIRLOOP DATACENTER BASEMENT COOLING COIL
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.322755E+12 | 0.814821E+11 | 744.00 | 0.322249E+12 | 0.505033E+09 | 0.00 | 0.34 | 04-JAN-16:30 | 0.30 | 09-JAN-07:10 | 130240.38 | 19-JAN-17:00 | 125486.54 | 31-JAN-15:00 | 6032.09 | 19-JAN-17:10 | 37254.66 | 04-JAN-16:30 | 0.00 |
February | 0.513810E+12 | 0.125147E+12 | 672.00 | 0.513255E+12 | 0.554421E+09 | 0.00 | 0.59 | 28-FEB-14:10 | 0.51 | 13-FEB-07:10 | 220370.20 | 17-FEB-17:00 | 218908.00 | 28-FEB-15:00 | 5785.07 | 17-FEB-17:10 | 71132.19 | 28-FEB-14:20 | 0.00 |
March | 0.819754E+12 | 0.201093E+12 | 744.00 | 0.818178E+12 | 0.157580E+10 | 0.00 | 0.92 | 31-MAR-24:00 | 0.72 | 06-MAR-07:20 | 394618.19 | 31-MAR-24:00 | 394618.19 | 31-MAR-24:00 | 8575.26 | 31-MAR-11:50 | 107135.99 | 30-MAR-16:00 | 0.00 |
April | 0.103147E+13 | 0.268037E+12 | 720.00 | 0.102945E+13 | 0.201344E+10 | 0.00 | 1.00 | 02-APR-13:30 | 0.36 | 30-APR-24:00 | 407355.99 | 21-APR-15:00 | 403307.25 | 16-APR-18:35 | 7166.40 | 04-APR-10:00 | 137420.05 | 17-APR-16:00 | 0.00 |
May | 0.341365E+12 | 0.983718E+11 | 744.00 | 0.335009E+12 | 0.635622E+10 | 0.00 | 0.55 | 31-MAY-23:20 | 0.31 | 12-MAY-07:00 | 213304.05 | 31-MAY-23:10 | 211865.19 | 31-MAY-24:00 | 8649.07 | 23-MAY-14:00 | 60476.91 | 31-MAY-23:20 | 0.00 |
June | 0.573902E+12 | 0.181976E+12 | 720.00 | 0.564586E+12 | 0.931587E+10 | 0.00 | 0.77 | 30-JUN-24:00 | 0.53 | 10-JUN-06:30 | 304523.38 | 30-JUN-24:00 | 304005.18 | 30-JUN-24:00 | 13299.17 | 26-JUN-17:00 | 92992.99 | 06-JUN-15:00 | 0.00 |
July | 0.840997E+12 | 0.274004E+12 | 744.00 | 0.829881E+12 | 0.111163E+11 | 0.00 | 0.99 | 31-JUL-23:55 | 0.75 | 29-JUL-04:00 | 396982.36 | 31-JUL-23:55 | 396164.08 | 31-JUL-24:00 | 14048.46 | 25-JUL-16:50 | 135166.75 | 08-JUL-15:40 | 0.00 |
August | 0.108128E+13 | 0.350365E+12 | 744.00 | 0.107015E+13 | 0.111347E+11 | 0.00 | 1.00 | 01-AUG-07:05 | 0.38 | 31-AUG-24:00 | 423093.78 | 08-AUG-17:00 | 407845.40 | 07-AUG-21:04 | 19230.15 | 11-AUG-17:00 | 154125.23 | 01-AUG-16:10 | 0.00 |
September | 0.338494E+12 | 0.101446E+12 | 720.00 | 0.330100E+12 | 0.839407E+10 | 0.00 | 0.53 | 30-SEP-24:00 | 0.32 | 29-SEP-06:10 | 212230.89 | 30-SEP-23:20 | 211970.75 | 30-SEP-24:00 | 10513.00 | 28-SEP-13:20 | 53918.61 | 07-SEP-16:00 | 0.00 |
October | 0.584559E+12 | 0.151203E+12 | 744.00 | 0.580848E+12 | 0.371132E+10 | 0.00 | 0.74 | 31-OCT-24:00 | 0.53 | 31-OCT-07:00 | 304685.21 | 31-OCT-24:00 | 304685.21 | 31-OCT-24:00 | 11887.83 | 18-OCT-16:10 | 82951.75 | 10-OCT-16:00 | 0.00 |
November | 0.798455E+12 | 0.191654E+12 | 720.00 | 0.796979E+12 | 0.147654E+10 | 0.00 | 0.81 | 19-NOV-15:00 | 0.72 | 13-NOV-07:20 | 318078.77 | 27-NOV-17:00 | 311700.38 | 02-NOV-14:00 | 6787.60 | 27-NOV-17:10 | 98134.01 | 19-NOV-15:00 | 0.00 |
December | 0.106524E+13 | 0.239368E+12 | 744.00 | 0.106449E+13 | 0.756865E+09 | 0.00 | 0.99 | 12-DEC-14:40 | 0.90 | 01-DEC-07:10 | 408994.61 | 13-DEC-14:00 | 403104.88 | 12-DEC-15:00 | 7820.79 | 13-DEC-14:00 | 120514.49 | 12-DEC-14:40 | 0.00 |
Annual Sum or Average | 0.831209E+13 | 0.226415E+13 | 8760.00 | 0.825518E+13 | 0.569106E+11 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.322755E+12 | 0.814821E+11 | 672.00 | 0.322249E+12 | 0.505033E+09 | 0.00 | 0.34 | 0.30 | 130240.38 | 125486.54 | 5785.07 | 37254.66 | 0.00 | ||||||
Maximum of Months | 0.108128E+13 | 0.350365E+12 | 744.00 | 0.107015E+13 | 0.111347E+11 | 0.00 | 1.00 | 0.90 | 423093.78 | 407845.40 | 19230.15 | 154125.23 | 0.00 |
Report: DXReportMonthly
For: AIRLOOP DATACENTER BOT COOLING COIL
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.366635E+10 | 0.985252E+09 | 744.00 | 0.364720E+10 | 19148367.55 | 0.00 | 0.30 | 15-JAN-17:35 | 0.04 | 09-JAN-07:10 | 2321.85 | 20-JAN-17:00 | 2219.08 | 20-JAN-17:00 | 225.42 | 19-JAN-17:00 | 629.39 | 31-JAN-15:00 | 0.00 |
February | 0.857835E+10 | 0.215044E+10 | 672.00 | 0.855628E+10 | 22068999.61 | 0.00 | 0.58 | 26-FEB-17:42 | 0.31 | 13-FEB-07:10 | 4531.52 | 20-FEB-17:57 | 4498.52 | 20-FEB-17:57 | 230.38 | 17-FEB-17:00 | 1414.79 | 26-FEB-17:23 | 0.00 |
March | 0.156283E+11 | 0.384228E+10 | 744.00 | 0.155620E+11 | 66238327.54 | 0.00 | 0.84 | 31-MAR-24:00 | 0.58 | 22-MAR-07:00 | 7701.85 | 31-MAR-24:00 | 7701.85 | 31-MAR-24:00 | 305.77 | 31-MAR-11:40 | 2158.97 | 30-MAR-16:00 | 0.00 |
April | 0.203356E+11 | 0.523457E+10 | 720.00 | 0.202451E+11 | 90448678.44 | 0.00 | 0.99 | 08-APR-18:12 | 0.30 | 30-APR-24:00 | 8484.65 | 09-APR-18:15 | 8484.65 | 09-APR-18:15 | 332.42 | 04-APR-10:00 | 2867.52 | 17-APR-16:00 | 0.00 |
May | 0.616096E+10 | 0.175085E+10 | 744.00 | 0.592471E+10 | 0.236250E+09 | 0.00 | 0.49 | 31-MAY-24:00 | 0.20 | 11-MAY-06:05 | 4091.83 | 31-MAY-24:00 | 4037.42 | 31-MAY-24:00 | 341.10 | 31-MAY-11:00 | 1135.56 | 31-MAY-23:20 | 0.00 |
June | 0.112697E+11 | 0.350234E+10 | 720.00 | 0.108928E+11 | 0.376884E+09 | 0.00 | 0.69 | 30-JUN-24:00 | 0.43 | 10-JUN-06:50 | 5969.29 | 30-JUN-24:00 | 5946.40 | 30-JUN-24:00 | 491.42 | 26-JUN-16:20 | 1905.51 | 06-JUN-15:20 | 0.00 |
July | 0.167870E+11 | 0.535536E+10 | 744.00 | 0.163096E+11 | 0.477389E+09 | 0.00 | 0.90 | 31-JUL-23:55 | 0.66 | 29-JUL-06:10 | 7801.45 | 31-JUL-23:55 | 7779.54 | 31-JUL-24:00 | 549.02 | 26-JUL-09:00 | 2784.62 | 07-JUL-16:00 | 0.00 |
August | 0.219404E+11 | 0.706128E+10 | 744.00 | 0.213917E+11 | 0.548697E+09 | 0.00 | 1.00 | 01-AUG-10:20 | 0.31 | 31-AUG-24:00 | 8974.29 | 04-AUG-15:00 | 8471.10 | 13-AUG-19:23 | 649.99 | 11-AUG-17:00 | 3267.69 | 01-AUG-16:10 | 0.00 |
September | 0.617805E+10 | 0.182046E+10 | 720.00 | 0.586012E+10 | 0.317934E+09 | 0.00 | 0.44 | 30-SEP-24:00 | 0.21 | 29-SEP-06:50 | 3751.76 | 30-SEP-24:00 | 3736.09 | 30-SEP-24:00 | 420.30 | 05-SEP-11:00 | 1132.32 | 07-SEP-16:00 | 0.00 |
October | 0.108174E+11 | 0.276521E+10 | 744.00 | 0.106659E+11 | 0.151453E+09 | 0.00 | 0.65 | 31-OCT-24:00 | 0.38 | 26-OCT-07:00 | 5655.26 | 31-OCT-24:00 | 5655.26 | 31-OCT-24:00 | 505.78 | 18-OCT-16:00 | 1690.45 | 10-OCT-16:00 | 0.00 |
November | 0.150064E+11 | 0.362968E+10 | 720.00 | 0.149489E+11 | 57489217.58 | 0.00 | 0.78 | 19-NOV-17:03 | 0.58 | 30-NOV-22:00 | 6435.60 | 11-NOV-17:08 | 6435.60 | 11-NOV-17:08 | 281.96 | 27-NOV-17:00 | 1981.18 | 19-NOV-15:03 | 0.00 |
December | 0.201076E+11 | 0.459738E+10 | 744.00 | 0.200752E+11 | 32330737.13 | 0.00 | 0.97 | 10-DEC-16:53 | 0.74 | 01-DEC-07:10 | 8306.44 | 11-DEC-16:50 | 8118.35 | 19-DEC-17:00 | 330.90 | 13-DEC-16:00 | 2378.37 | 12-DEC-14:50 | 0.00 |
Annual Sum or Average | 0.156476E+12 | 0.426951E+11 | 8760.00 | 0.154080E+12 | 0.239633E+10 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.366635E+10 | 0.985252E+09 | 672.00 | 0.364720E+10 | 19148367.55 | 0.00 | 0.30 | 0.04 | 2321.85 | 2219.08 | 225.42 | 629.39 | 0.00 | ||||||
Maximum of Months | 0.219404E+11 | 0.706128E+10 | 744.00 | 0.213917E+11 | 0.548697E+09 | 0.00 | 1.00 | 0.74 | 8974.29 | 8484.65 | 649.99 | 3267.69 | 0.00 |
Report: DXReportMonthly
For: AIRLOOP DATACENTER MID COOLING COIL
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.116269E+11 | 0.336553E+10 | 563.99 | 0.114626E+11 | 0.164294E+09 | 0.00 | 0.24 | 20-JAN-17:00 | 0.00 | 01-JAN-00:05 | 18736.72 | 20-JAN-17:00 | 17679.15 | 20-JAN-17:00 | 2055.33 | 19-JAN-17:00 | 4750.18 | 31-JAN-15:20 | 0.00 |
February | 0.627246E+11 | 0.161028E+11 | 672.00 | 0.625139E+11 | 0.210704E+09 | 0.00 | 0.54 | 27-FEB-17:50 | 0.12 | 13-FEB-04:12 | 41041.90 | 28-FEB-17:00 | 41041.90 | 28-FEB-17:00 | 2225.17 | 17-FEB-17:00 | 12731.63 | 28-FEB-15:00 | 0.00 |
March | 0.138227E+12 | 0.343559E+11 | 744.00 | 0.137568E+12 | 0.658850E+09 | 0.00 | 0.82 | 31-MAR-23:50 | 0.50 | 22-MAR-06:20 | 71530.82 | 31-MAR-23:50 | 71530.82 | 31-MAR-23:50 | 3026.25 | 31-MAR-11:40 | 20467.78 | 30-MAR-16:00 | 0.00 |
April | 0.188317E+12 | 0.487538E+11 | 720.00 | 0.187412E+12 | 0.904094E+09 | 0.00 | 0.98 | 17-APR-16:00 | 0.25 | 30-APR-24:00 | 79656.72 | 04-APR-15:40 | 79257.41 | 14-APR-18:20 | 3326.03 | 04-APR-10:00 | 27167.03 | 17-APR-16:00 | 0.00 |
May | 0.546039E+11 | 0.156625E+11 | 744.00 | 0.523000E+11 | 0.230390E+10 | 0.00 | 0.48 | 31-MAY-23:40 | 0.16 | 10-MAY-07:00 | 38386.76 | 31-MAY-23:20 | 37775.33 | 31-MAY-24:00 | 3399.31 | 31-MAY-11:00 | 10669.08 | 31-MAY-23:20 | 0.00 |
June | 0.105820E+12 | 0.329702E+11 | 720.00 | 0.102079E+12 | 0.374103E+10 | 0.00 | 0.69 | 30-JUN-24:00 | 0.39 | 10-JUN-07:00 | 56649.66 | 30-JUN-24:00 | 56416.49 | 30-JUN-24:00 | 4880.15 | 26-JUN-16:20 | 18103.88 | 06-JUN-15:20 | 0.00 |
July | 0.159537E+12 | 0.509340E+11 | 744.00 | 0.154780E+12 | 0.475674E+10 | 0.00 | 0.91 | 31-JUL-23:55 | 0.63 | 29-JUL-06:10 | 75227.84 | 31-JUL-23:55 | 75012.98 | 31-JUL-24:00 | 5484.95 | 26-JUL-09:00 | 26589.57 | 07-JUL-16:00 | 0.00 |
August | 0.208831E+12 | 0.672347E+11 | 744.00 | 0.203345E+12 | 0.548595E+10 | 0.00 | 1.00 | 01-AUG-10:10 | 0.27 | 31-AUG-24:00 | 85091.30 | 04-AUG-14:50 | 79587.88 | 13-AUG-18:38 | 6392.04 | 11-AUG-16:50 | 31208.91 | 01-AUG-16:10 | 0.00 |
September | 0.544046E+11 | 0.161844E+11 | 720.00 | 0.513058E+11 | 0.309882E+10 | 0.00 | 0.39 | 07-SEP-16:00 | 0.15 | 30-SEP-17:00 | 31326.62 | 30-SEP-24:00 | 31060.97 | 30-SEP-24:00 | 4162.15 | 05-SEP-11:00 | 10731.03 | 07-SEP-16:00 | 0.00 |
October | 0.927509E+11 | 0.240325E+11 | 744.00 | 0.912602E+11 | 0.149072E+10 | 0.00 | 0.59 | 31-OCT-23:50 | 0.31 | 31-OCT-07:00 | 48263.33 | 31-OCT-23:50 | 48263.33 | 31-OCT-23:50 | 5033.26 | 18-OCT-16:00 | 15836.12 | 10-OCT-16:00 | 0.00 |
November | 0.128045E+12 | 0.314149E+11 | 720.00 | 0.127480E+12 | 0.565438E+09 | 0.00 | 0.76 | 08-NOV-17:00 | 0.49 | 22-NOV-07:10 | 59728.96 | 08-NOV-17:00 | 59728.96 | 08-NOV-17:00 | 2789.32 | 27-NOV-17:00 | 17636.45 | 19-NOV-16:55 | 0.00 |
December | 0.168017E+12 | 0.391340E+11 | 744.00 | 0.167694E+12 | 0.323265E+09 | 0.00 | 0.90 | 12-DEC-15:20 | 0.62 | 18-DEC-07:10 | 76467.37 | 11-DEC-17:00 | 74576.81 | 11-DEC-17:00 | 3289.40 | 13-DEC-16:00 | 22059.62 | 12-DEC-15:00 | 0.00 |
Annual Sum or Average | 0.137290E+13 | 0.380145E+12 | 8579.99 | 0.134920E+13 | 0.237038E+11 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.116269E+11 | 0.336553E+10 | 563.99 | 0.114626E+11 | 0.164294E+09 | 0.00 | 0.24 | 0.00 | 18736.72 | 17679.15 | 2055.33 | 4750.18 | 0.00 | ||||||
Maximum of Months | 0.208831E+12 | 0.672347E+11 | 744.00 | 0.203345E+12 | 0.548595E+10 | 0.00 | 1.00 | 0.63 | 85091.30 | 79587.88 | 6392.04 | 31208.91 | 0.00 |
Report: DXReportMonthly
For: AIRLOOP DATACENTER TOP COOLING COIL
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.621563E+09 | 0.178295E+09 | 302.22 | 0.605803E+09 | 15759481.41 | 0.00 | 0.24 | 20-JAN-17:00 | 0.00 | 01-JAN-00:05 | 1961.58 | 20-JAN-17:00 | 1852.68 | 20-JAN-17:00 | 213.15 | 19-JAN-16:40 | 480.74 | 20-JAN-17:00 | 0.00 |
February | 0.522525E+10 | 0.135738E+10 | 653.72 | 0.520456E+10 | 20686968.79 | 0.00 | 0.53 | 27-FEB-17:50 | 0.00 | 05-FEB-03:25 | 4144.17 | 28-FEB-17:00 | 4144.17 | 28-FEB-17:00 | 221.08 | 17-FEB-17:00 | 1281.52 | 28-FEB-17:00 | 0.00 |
March | 0.130275E+11 | 0.327179E+10 | 744.00 | 0.129621E+11 | 65372169.56 | 0.00 | 0.78 | 31-MAR-23:20 | 0.42 | 23-MAR-06:10 | 6897.78 | 31-MAR-23:20 | 6897.78 | 31-MAR-23:20 | 303.01 | 31-MAR-11:40 | 2083.08 | 30-MAR-16:00 | 0.00 |
April | 0.184072E+11 | 0.480100E+10 | 720.00 | 0.183172E+11 | 90021175.84 | 0.00 | 0.97 | 17-APR-16:00 | 0.23 | 30-APR-24:00 | 8065.77 | 17-APR-16:00 | 8030.10 | 17-APR-16:00 | 332.82 | 04-APR-10:00 | 2759.40 | 17-APR-16:00 | 0.00 |
May | 0.536898E+10 | 0.155142E+10 | 744.00 | 0.513908E+10 | 0.229905E+09 | 0.00 | 0.47 | 31-MAY-23:30 | 0.10 | 11-MAY-06:25 | 3812.03 | 31-MAY-23:10 | 3743.01 | 31-MAY-24:00 | 345.27 | 31-MAY-11:00 | 1061.85 | 31-MAY-23:20 | 0.00 |
June | 0.106418E+11 | 0.332565E+10 | 720.00 | 0.102675E+11 | 0.374313E+09 | 0.00 | 0.68 | 30-JUN-24:00 | 0.36 | 10-JUN-07:00 | 5636.86 | 30-JUN-24:00 | 5613.17 | 30-JUN-24:00 | 489.76 | 26-JUN-16:20 | 1856.85 | 06-JUN-15:20 | 0.00 |
July | 0.160576E+11 | 0.513926E+10 | 744.00 | 0.155821E+11 | 0.475481E+09 | 0.00 | 0.90 | 31-JUL-23:55 | 0.59 | 29-JUL-07:00 | 7576.32 | 31-JUL-23:55 | 7554.70 | 31-JUL-24:00 | 548.89 | 26-JUL-09:00 | 2718.45 | 07-JUL-16:00 | 0.00 |
August | 0.210087E+11 | 0.678092E+10 | 744.00 | 0.204599E+11 | 0.548762E+09 | 0.00 | 1.00 | 01-AUG-10:40 | 0.25 | 31-AUG-24:00 | 8629.02 | 04-AUG-14:50 | 8203.25 | 13-AUG-18:52 | 623.54 | 11-AUG-16:50 | 3177.33 | 01-AUG-16:10 | 0.00 |
September | 0.526916E+10 | 0.158102E+10 | 720.00 | 0.496154E+10 | 0.307620E+09 | 0.00 | 0.40 | 07-SEP-16:00 | 0.10 | 30-SEP-17:00 | 3066.46 | 07-SEP-16:00 | 2681.05 | 07-SEP-16:00 | 419.89 | 06-SEP-14:30 | 1109.33 | 07-SEP-16:00 | 0.00 |
October | 0.851575E+10 | 0.223668E+10 | 744.00 | 0.836752E+10 | 0.148224E+09 | 0.00 | 0.58 | 10-OCT-16:00 | 0.21 | 26-OCT-06:10 | 4639.91 | 18-OCT-16:00 | 4384.55 | 31-OCT-23:20 | 503.99 | 18-OCT-16:00 | 1611.05 | 10-OCT-16:00 | 0.00 |
November | 0.115970E+11 | 0.288425E+10 | 720.00 | 0.115411E+11 | 55811409.99 | 0.00 | 0.74 | 08-NOV-17:00 | 0.38 | 22-NOV-07:10 | 5986.35 | 02-NOV-16:00 | 5944.76 | 06-NOV-17:00 | 278.19 | 27-NOV-17:00 | 1733.15 | 08-NOV-17:00 | 0.00 |
December | 0.152248E+11 | 0.359626E+10 | 744.00 | 0.151927E+11 | 32068213.81 | 0.00 | 0.88 | 12-DEC-15:30 | 0.44 | 18-DEC-04:02 | 7609.60 | 13-DEC-16:00 | 7400.24 | 12-DEC-17:00 | 328.66 | 13-DEC-16:00 | 2202.28 | 12-DEC-15:00 | 0.00 |
Annual Sum or Average | 0.130965E+12 | 0.367039E+11 | 8299.94 | 0.128601E+12 | 0.236402E+10 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.621563E+09 | 0.178295E+09 | 302.22 | 0.605803E+09 | 15759481.41 | 0.00 | 0.24 | 0.00 | 1961.58 | 1852.68 | 213.15 | 480.74 | 0.00 | ||||||
Maximum of Months | 0.210087E+11 | 0.678092E+10 | 744.00 | 0.204599E+11 | 0.548762E+09 | 0.00 | 1.00 | 0.59 | 8629.02 | 8203.25 | 623.54 | 3177.33 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 98.96 | 0.00 | 98.96 | 8.30 | 820.85 | 0.00 | 0.00 | 0.00 |
February | 109.69 | 0.00 | 109.69 | 34.51 | 674.70 | 0.00 | 0.00 | 0.00 |
March | 154.00 | 0.00 | 154.00 | 84.86 | 426.91 | 0.00 | 0.00 | 0.00 |
April | 186.27 | 0.83 | 185.45 | 187.83 | 326.19 | 0.00 | 0.00 | 0.00 |
May | 222.78 | 7.11 | 215.67 | 304.95 | 201.21 | 0.00 | 0.00 | 0.00 |
June | 245.18 | 16.19 | 228.99 | 447.16 | 123.45 | 0.00 | 0.00 | 0.00 |
July | 231.33 | 11.24 | 220.08 | 450.25 | 85.55 | 0.00 | 0.00 | 0.00 |
August | 205.73 | 2.24 | 203.49 | 410.90 | 68.47 | 0.00 | 0.00 | 0.00 |
September | 155.51 | 0.02 | 155.49 | 227.73 | 176.34 | 0.00 | 0.00 | 0.00 |
October | 118.24 | 0.00 | 118.24 | 90.83 | 389.14 | 0.00 | 0.00 | 0.00 |
November | 105.82 | 0.00 | 105.82 | 35.95 | 543.75 | 0.00 | 0.00 | 0.00 |
December | 91.48 | 0.00 | 91.48 | 6.34 | 708.23 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 160.69 | 3.15 | 157.54 | 191.72 | 377.25 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 91.48 | 0.00 | 91.48 | 6.34 | 68.47 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 245.18 | 16.19 | 228.99 | 450.25 | 820.85 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 98.96 | 0.00 | 98.96 | 8.30 | 820.85 | 0.00 | 0.00 | 0.00 |
February | 109.69 | 0.00 | 109.69 | 34.51 | 674.70 | 0.00 | 0.00 | 0.00 |
March | 154.00 | 0.00 | 154.00 | 84.86 | 426.91 | 0.00 | 0.00 | 0.00 |
April | 186.27 | 0.83 | 185.45 | 187.83 | 326.19 | 0.00 | 0.00 | 0.00 |
May | 222.78 | 7.11 | 215.67 | 304.95 | 201.21 | 0.00 | 0.00 | 0.00 |
June | 245.18 | 16.19 | 228.99 | 447.16 | 123.45 | 0.00 | 0.00 | 0.00 |
July | 231.33 | 11.24 | 220.08 | 450.25 | 85.55 | 0.00 | 0.00 | 0.00 |
August | 205.73 | 2.24 | 203.49 | 410.90 | 68.47 | 0.00 | 0.00 | 0.00 |
September | 155.51 | 0.02 | 155.49 | 227.73 | 176.33 | 0.00 | 0.00 | 0.00 |
October | 118.24 | 0.00 | 118.24 | 90.83 | 389.14 | 0.00 | 0.00 | 0.00 |
November | 105.82 | 0.00 | 105.82 | 35.95 | 543.75 | 0.00 | 0.00 | 0.00 |
December | 91.48 | 0.00 | 91.48 | 6.34 | 708.23 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 160.69 | 3.15 | 157.54 | 191.72 | 377.25 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 91.48 | 0.00 | 91.48 | 6.34 | 68.47 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 245.18 | 16.19 | 228.99 | 450.25 | 820.85 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 98.96 | 0.00 | 98.96 | 8.30 | 820.85 | 0.00 | 0.00 | 0.00 |
February | 109.69 | 0.00 | 109.69 | 34.51 | 674.70 | 0.00 | 0.00 | 0.00 |
March | 154.00 | 0.00 | 154.00 | 84.86 | 426.91 | 0.00 | 0.00 | 0.00 |
April | 186.27 | 0.83 | 185.45 | 187.83 | 326.19 | 0.00 | 0.00 | 0.00 |
May | 222.78 | 7.11 | 215.67 | 304.95 | 201.21 | 0.00 | 0.00 | 0.00 |
June | 245.18 | 16.19 | 228.99 | 447.16 | 123.45 | 0.00 | 0.00 | 0.00 |
July | 231.33 | 11.24 | 220.08 | 450.25 | 85.55 | 0.00 | 0.00 | 0.00 |
August | 205.73 | 2.24 | 203.49 | 410.90 | 68.47 | 0.00 | 0.00 | 0.00 |
September | 155.51 | 0.02 | 155.49 | 227.73 | 176.34 | 0.00 | 0.00 | 0.00 |
October | 118.24 | 0.00 | 118.24 | 90.83 | 389.14 | 0.00 | 0.00 | 0.00 |
November | 105.82 | 0.00 | 105.82 | 35.95 | 543.75 | 0.00 | 0.00 | 0.00 |
December | 91.48 | 0.00 | 91.48 | 6.34 | 708.23 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 160.69 | 3.15 | 157.54 | 191.72 | 377.25 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 91.48 | 0.00 | 91.48 | 6.34 | 68.47 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 245.18 | 16.19 | 228.99 | 450.25 | 820.85 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 98.96 | 0.00 | 98.96 | 8.30 | 820.85 | 0.00 | 0.00 | 0.00 |
February | 109.69 | 0.00 | 109.69 | 34.51 | 674.70 | 0.00 | 0.00 | 0.00 |
March | 154.00 | 0.00 | 154.00 | 84.86 | 426.91 | 0.00 | 0.00 | 0.00 |
April | 186.27 | 0.83 | 185.45 | 187.83 | 326.19 | 0.00 | 0.00 | 0.00 |
May | 222.78 | 7.11 | 215.67 | 304.95 | 201.21 | 0.00 | 0.00 | 0.00 |
June | 245.18 | 16.19 | 228.99 | 447.16 | 123.45 | 0.00 | 0.00 | 0.00 |
July | 231.33 | 11.24 | 220.08 | 450.25 | 85.55 | 0.00 | 0.00 | 0.00 |
August | 205.73 | 2.24 | 203.49 | 410.90 | 68.47 | 0.00 | 0.00 | 0.00 |
September | 155.51 | 0.02 | 155.49 | 227.73 | 176.33 | 0.00 | 0.00 | 0.00 |
October | 118.24 | 0.00 | 118.24 | 90.83 | 389.14 | 0.00 | 0.00 | 0.00 |
November | 105.82 | 0.00 | 105.82 | 35.95 | 543.75 | 0.00 | 0.00 | 0.00 |
December | 91.48 | 0.00 | 91.48 | 6.34 | 708.23 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 160.69 | 3.15 | 157.54 | 191.72 | 377.25 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 91.48 | 0.00 | 91.48 | 6.34 | 68.47 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 245.18 | 16.19 | 228.99 | 450.25 | 820.85 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 98.96 | 0.00 | 98.96 | 8.30 | 820.82 | 0.00 | 0.00 | 0.00 |
February | 109.68 | 0.00 | 109.68 | 34.51 | 674.68 | 0.00 | 0.00 | 0.00 |
March | 153.99 | 0.00 | 153.99 | 84.86 | 426.89 | 0.00 | 0.00 | 0.00 |
April | 186.27 | 0.83 | 185.44 | 187.83 | 326.17 | 0.00 | 0.00 | 0.00 |
May | 222.77 | 7.11 | 215.66 | 304.94 | 201.20 | 0.00 | 0.00 | 0.00 |
June | 245.17 | 16.19 | 228.98 | 447.14 | 123.45 | 0.00 | 0.00 | 0.00 |
July | 231.32 | 11.24 | 220.07 | 450.23 | 85.55 | 0.00 | 0.00 | 0.00 |
August | 205.72 | 2.24 | 203.48 | 410.89 | 68.47 | 0.00 | 0.00 | 0.00 |
September | 155.50 | 0.02 | 155.48 | 227.72 | 176.33 | 0.00 | 0.00 | 0.00 |
October | 118.24 | 0.00 | 118.24 | 90.83 | 389.13 | 0.00 | 0.00 | 0.00 |
November | 105.82 | 0.00 | 105.82 | 35.95 | 543.73 | 0.00 | 0.00 | 0.00 |
December | 91.48 | 0.00 | 91.48 | 6.34 | 708.20 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 160.69 | 3.15 | 157.54 | 191.71 | 377.23 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 91.48 | 0.00 | 91.48 | 6.34 | 68.47 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 245.17 | 16.19 | 228.98 | 450.23 | 820.82 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 241.48 | 108.92 | 132.56 | 145.69 | 808.88 | 0.00 | 0.00 | 0.00 |
February | 304.43 | 163.57 | 140.86 | 270.09 | 659.89 | 0.00 | 0.00 | 0.00 |
March | 383.00 | 174.35 | 208.65 | 410.25 | 415.74 | 0.00 | 0.00 | 0.00 |
April | 463.15 | 211.18 | 251.97 | 626.63 | 322.36 | 0.00 | 0.00 | 0.00 |
May | 508.57 | 215.07 | 293.51 | 776.10 | 215.45 | 0.00 | 0.00 | 0.00 |
June | 526.54 | 220.69 | 305.86 | 929.46 | 130.91 | 0.00 | 0.00 | 0.00 |
July | 513.40 | 215.84 | 297.56 | 942.76 | 86.44 | 0.00 | 0.00 | 0.00 |
August | 469.59 | 186.30 | 283.29 | 879.95 | 62.97 | 0.00 | 0.00 | 0.00 |
September | 385.94 | 171.00 | 214.94 | 614.94 | 182.48 | 0.00 | 0.00 | 0.00 |
October | 329.24 | 171.31 | 157.93 | 406.37 | 383.83 | 0.00 | 0.00 | 0.00 |
November | 263.23 | 119.19 | 144.04 | 232.01 | 520.75 | 0.00 | 0.00 | 0.00 |
December | 228.01 | 103.94 | 124.07 | 145.72 | 674.76 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 385.10 | 171.75 | 213.35 | 533.06 | 370.58 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 228.01 | 103.94 | 124.07 | 145.69 | 62.97 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 526.54 | 220.69 | 305.86 | 942.76 | 808.88 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 241.48 | 108.92 | 132.56 | 145.69 | 808.88 | 0.00 | 0.00 | 0.00 |
February | 304.43 | 163.57 | 140.86 | 270.09 | 659.89 | 0.00 | 0.00 | 0.00 |
March | 383.00 | 174.35 | 208.65 | 410.25 | 415.74 | 0.00 | 0.00 | 0.00 |
April | 463.15 | 211.18 | 251.97 | 626.63 | 322.36 | 0.00 | 0.00 | 0.00 |
May | 508.57 | 215.07 | 293.51 | 776.10 | 215.45 | 0.00 | 0.00 | 0.00 |
June | 526.54 | 220.69 | 305.86 | 929.46 | 130.91 | 0.00 | 0.00 | 0.00 |
July | 513.40 | 215.84 | 297.56 | 942.76 | 86.44 | 0.00 | 0.00 | 0.00 |
August | 469.59 | 186.30 | 283.29 | 879.95 | 62.97 | 0.00 | 0.00 | 0.00 |
September | 385.94 | 171.00 | 214.94 | 614.94 | 182.48 | 0.00 | 0.00 | 0.00 |
October | 329.24 | 171.31 | 157.93 | 406.37 | 383.83 | 0.00 | 0.00 | 0.00 |
November | 263.23 | 119.19 | 144.04 | 232.01 | 520.75 | 0.00 | 0.00 | 0.00 |
December | 228.01 | 103.94 | 124.07 | 145.72 | 674.76 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 385.10 | 171.75 | 213.35 | 533.06 | 370.58 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 228.01 | 103.94 | 124.07 | 145.69 | 62.97 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 526.54 | 220.69 | 305.86 | 942.76 | 808.88 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 241.47 | 108.92 | 132.56 | 145.69 | 808.87 | 0.00 | 0.00 | 0.00 |
February | 304.42 | 163.56 | 140.86 | 270.08 | 659.88 | 0.00 | 0.00 | 0.00 |
March | 383.00 | 174.35 | 208.65 | 410.24 | 415.73 | 0.00 | 0.00 | 0.00 |
April | 463.14 | 211.18 | 251.96 | 626.62 | 322.36 | 0.00 | 0.00 | 0.00 |
May | 508.56 | 215.06 | 293.50 | 776.08 | 215.45 | 0.00 | 0.00 | 0.00 |
June | 526.53 | 220.68 | 305.85 | 929.44 | 130.91 | 0.00 | 0.00 | 0.00 |
July | 513.39 | 215.84 | 297.56 | 942.74 | 86.43 | 0.00 | 0.00 | 0.00 |
August | 469.58 | 186.30 | 283.28 | 879.93 | 62.97 | 0.00 | 0.00 | 0.00 |
September | 385.93 | 171.00 | 214.94 | 614.93 | 182.48 | 0.00 | 0.00 | 0.00 |
October | 329.24 | 171.31 | 157.93 | 406.37 | 383.82 | 0.00 | 0.00 | 0.00 |
November | 263.23 | 119.19 | 144.04 | 232.01 | 520.74 | 0.00 | 0.00 | 0.00 |
December | 228.00 | 103.93 | 124.07 | 145.72 | 674.75 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 385.09 | 171.75 | 213.35 | 533.05 | 370.58 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 228.00 | 103.93 | 124.07 | 145.69 | 62.97 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 526.53 | 220.68 | 305.85 | 942.74 | 808.87 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 529.26 | 369.00 | 160.26 | 569.73 | 657.49 | 0.00 | 0.00 | 0.00 |
February | 493.97 | 331.12 | 162.85 | 585.96 | 569.11 | 0.00 | 0.00 | 0.00 |
March | 444.25 | 231.52 | 212.73 | 576.98 | 396.05 | 0.00 | 0.00 | 0.00 |
April | 332.71 | 108.31 | 224.41 | 485.09 | 325.89 | 0.00 | 0.00 | 0.00 |
May | 268.82 | 31.24 | 237.57 | 420.82 | 210.84 | 0.00 | 0.00 | 0.00 |
June | 248.55 | 13.83 | 234.72 | 470.88 | 131.51 | 0.00 | 0.00 | 0.00 |
July | 251.28 | 18.74 | 232.54 | 502.30 | 89.73 | 0.00 | 0.00 | 0.00 |
August | 300.01 | 56.04 | 243.97 | 610.26 | 73.27 | 0.00 | 0.00 | 0.00 |
September | 329.94 | 122.72 | 207.22 | 563.89 | 177.13 | 0.00 | 0.00 | 0.00 |
October | 478.32 | 309.85 | 168.46 | 695.63 | 359.23 | 0.00 | 0.00 | 0.00 |
November | 514.58 | 341.47 | 173.11 | 659.98 | 471.84 | 0.00 | 0.00 | 0.00 |
December | 521.70 | 367.02 | 154.68 | 600.91 | 576.34 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 392.35 | 191.09 | 201.26 | 561.86 | 335.28 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 248.55 | 13.83 | 154.68 | 420.82 | 73.27 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 529.26 | 369.00 | 243.97 | 695.63 | 657.49 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 529.26 | 369.00 | 160.26 | 569.73 | 657.49 | 0.00 | 0.00 | 0.00 |
February | 493.97 | 331.12 | 162.85 | 585.96 | 569.11 | 0.00 | 0.00 | 0.00 |
March | 444.25 | 231.52 | 212.73 | 576.98 | 396.05 | 0.00 | 0.00 | 0.00 |
April | 332.71 | 108.31 | 224.41 | 485.09 | 325.89 | 0.00 | 0.00 | 0.00 |
May | 268.82 | 31.24 | 237.57 | 420.82 | 210.84 | 0.00 | 0.00 | 0.00 |
June | 248.55 | 13.83 | 234.72 | 470.88 | 131.51 | 0.00 | 0.00 | 0.00 |
July | 251.28 | 18.74 | 232.54 | 502.30 | 89.73 | 0.00 | 0.00 | 0.00 |
August | 300.01 | 56.04 | 243.97 | 610.26 | 73.27 | 0.00 | 0.00 | 0.00 |
September | 329.94 | 122.72 | 207.22 | 563.89 | 177.13 | 0.00 | 0.00 | 0.00 |
October | 478.32 | 309.85 | 168.46 | 695.63 | 359.23 | 0.00 | 0.00 | 0.00 |
November | 514.58 | 341.47 | 173.11 | 659.98 | 471.84 | 0.00 | 0.00 | 0.00 |
December | 521.70 | 367.02 | 154.68 | 600.91 | 576.34 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 392.35 | 191.09 | 201.26 | 561.86 | 335.28 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 248.55 | 13.83 | 154.68 | 420.82 | 73.27 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 529.26 | 369.00 | 243.97 | 695.63 | 657.49 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 529.26 | 369.00 | 160.26 | 569.73 | 657.49 | 0.00 | 0.00 | 0.00 |
February | 493.97 | 331.12 | 162.85 | 585.96 | 569.11 | 0.00 | 0.00 | 0.00 |
March | 444.25 | 231.52 | 212.73 | 576.98 | 396.05 | 0.00 | 0.00 | 0.00 |
April | 332.71 | 108.31 | 224.41 | 485.09 | 325.89 | 0.00 | 0.00 | 0.00 |
May | 268.82 | 31.24 | 237.57 | 420.82 | 210.84 | 0.00 | 0.00 | 0.00 |
June | 248.55 | 13.83 | 234.72 | 470.88 | 131.51 | 0.00 | 0.00 | 0.00 |
July | 251.28 | 18.74 | 232.54 | 502.30 | 89.73 | 0.00 | 0.00 | 0.00 |
August | 300.01 | 56.04 | 243.97 | 610.26 | 73.27 | 0.00 | 0.00 | 0.00 |
September | 329.94 | 122.72 | 207.22 | 563.89 | 177.13 | 0.00 | 0.00 | 0.00 |
October | 478.32 | 309.85 | 168.46 | 695.63 | 359.23 | 0.00 | 0.00 | 0.00 |
November | 514.58 | 341.47 | 173.11 | 659.98 | 471.84 | 0.00 | 0.00 | 0.00 |
December | 521.70 | 367.02 | 154.68 | 600.91 | 576.34 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 392.35 | 191.09 | 201.26 | 561.86 | 335.28 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 248.55 | 13.83 | 154.68 | 420.82 | 73.27 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 529.26 | 369.00 | 243.97 | 695.63 | 657.49 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 529.26 | 369.00 | 160.26 | 569.73 | 657.49 | 0.00 | 0.00 | 0.00 |
February | 493.97 | 331.12 | 162.85 | 585.96 | 569.11 | 0.00 | 0.00 | 0.00 |
March | 444.25 | 231.52 | 212.73 | 576.98 | 396.05 | 0.00 | 0.00 | 0.00 |
April | 332.71 | 108.31 | 224.41 | 485.09 | 325.89 | 0.00 | 0.00 | 0.00 |
May | 268.82 | 31.24 | 237.57 | 420.82 | 210.84 | 0.00 | 0.00 | 0.00 |
June | 248.55 | 13.83 | 234.72 | 470.88 | 131.51 | 0.00 | 0.00 | 0.00 |
July | 251.28 | 18.74 | 232.54 | 502.30 | 89.73 | 0.00 | 0.00 | 0.00 |
August | 300.01 | 56.04 | 243.97 | 610.26 | 73.27 | 0.00 | 0.00 | 0.00 |
September | 329.94 | 122.72 | 207.22 | 563.89 | 177.13 | 0.00 | 0.00 | 0.00 |
October | 478.32 | 309.85 | 168.46 | 695.63 | 359.23 | 0.00 | 0.00 | 0.00 |
November | 514.58 | 341.47 | 173.11 | 659.98 | 471.84 | 0.00 | 0.00 | 0.00 |
December | 521.70 | 367.02 | 154.68 | 600.91 | 576.34 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 392.35 | 191.09 | 201.26 | 561.86 | 335.28 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 248.55 | 13.83 | 154.68 | 420.82 | 73.27 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 529.26 | 369.00 | 243.97 | 695.63 | 657.49 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 529.24 | 368.98 | 160.25 | 569.71 | 657.46 | 0.00 | 0.00 | 0.00 |
February | 493.95 | 331.11 | 162.84 | 585.94 | 569.09 | 0.00 | 0.00 | 0.00 |
March | 444.23 | 231.51 | 212.72 | 576.96 | 396.03 | 0.00 | 0.00 | 0.00 |
April | 332.70 | 108.30 | 224.40 | 485.07 | 325.88 | 0.00 | 0.00 | 0.00 |
May | 268.81 | 31.24 | 237.57 | 420.81 | 210.84 | 0.00 | 0.00 | 0.00 |
June | 248.54 | 13.83 | 234.71 | 470.86 | 131.51 | 0.00 | 0.00 | 0.00 |
July | 251.27 | 18.74 | 232.53 | 502.28 | 89.72 | 0.00 | 0.00 | 0.00 |
August | 300.00 | 56.04 | 243.96 | 610.23 | 73.27 | 0.00 | 0.00 | 0.00 |
September | 329.92 | 122.71 | 207.21 | 563.87 | 177.13 | 0.00 | 0.00 | 0.00 |
October | 478.30 | 309.84 | 168.46 | 695.60 | 359.21 | 0.00 | 0.00 | 0.00 |
November | 514.56 | 341.45 | 173.11 | 659.96 | 471.82 | 0.00 | 0.00 | 0.00 |
December | 521.68 | 367.01 | 154.67 | 600.89 | 576.32 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 392.33 | 191.08 | 201.25 | 561.83 | 335.27 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 248.54 | 13.83 | 154.67 | 420.81 | 73.27 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 529.24 | 368.98 | 243.96 | 695.60 | 657.46 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 248.03 | 115.05 | 132.98 | 169.04 | 878.25 | 0.00 | 0.00 | 0.00 |
February | 284.74 | 133.13 | 151.61 | 260.12 | 761.65 | 0.00 | 0.00 | 0.00 |
March | 419.69 | 202.80 | 216.88 | 480.28 | 523.19 | 0.00 | 0.00 | 0.00 |
April | 472.14 | 216.05 | 256.09 | 632.56 | 424.90 | 0.00 | 0.00 | 0.00 |
May | 474.51 | 179.77 | 294.74 | 728.60 | 261.36 | 0.00 | 0.00 | 0.00 |
June | 499.01 | 191.97 | 307.05 | 873.09 | 177.33 | 0.00 | 0.00 | 0.00 |
July | 470.68 | 174.51 | 296.17 | 850.21 | 131.46 | 0.00 | 0.00 | 0.00 |
August | 461.20 | 172.47 | 288.73 | 837.98 | 118.90 | 0.00 | 0.00 | 0.00 |
September | 375.75 | 156.52 | 219.24 | 592.70 | 222.37 | 0.00 | 0.00 | 0.00 |
October | 334.75 | 173.77 | 160.98 | 431.58 | 473.28 | 0.00 | 0.00 | 0.00 |
November | 267.16 | 119.91 | 147.24 | 262.56 | 649.19 | 0.00 | 0.00 | 0.00 |
December | 220.40 | 96.40 | 124.00 | 154.68 | 836.77 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 377.81 | 161.15 | 216.66 | 524.20 | 453.31 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 220.40 | 96.40 | 124.00 | 154.68 | 118.90 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 499.01 | 216.05 | 307.05 | 873.09 | 878.25 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 248.03 | 115.05 | 132.98 | 169.04 | 878.25 | 0.00 | 0.00 | 0.00 |
February | 284.74 | 133.13 | 151.61 | 260.12 | 761.65 | 0.00 | 0.00 | 0.00 |
March | 419.69 | 202.80 | 216.88 | 480.28 | 523.19 | 0.00 | 0.00 | 0.00 |
April | 472.14 | 216.05 | 256.09 | 632.56 | 424.90 | 0.00 | 0.00 | 0.00 |
May | 474.51 | 179.77 | 294.74 | 728.60 | 261.36 | 0.00 | 0.00 | 0.00 |
June | 499.01 | 191.97 | 307.05 | 873.09 | 177.33 | 0.00 | 0.00 | 0.00 |
July | 470.68 | 174.51 | 296.17 | 850.21 | 131.46 | 0.00 | 0.00 | 0.00 |
August | 461.20 | 172.47 | 288.73 | 837.98 | 118.90 | 0.00 | 0.00 | 0.00 |
September | 375.75 | 156.52 | 219.24 | 592.70 | 222.37 | 0.00 | 0.00 | 0.00 |
October | 334.75 | 173.77 | 160.98 | 431.58 | 473.28 | 0.00 | 0.00 | 0.00 |
November | 267.16 | 119.91 | 147.24 | 262.56 | 649.19 | 0.00 | 0.00 | 0.00 |
December | 220.40 | 96.40 | 124.00 | 154.68 | 836.77 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 377.81 | 161.15 | 216.66 | 524.20 | 453.31 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 220.40 | 96.40 | 124.00 | 154.68 | 118.90 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 499.01 | 216.05 | 307.05 | 873.09 | 878.25 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 248.03 | 115.05 | 132.97 | 169.04 | 878.23 | 0.00 | 0.00 | 0.00 |
February | 284.73 | 133.13 | 151.60 | 260.11 | 761.63 | 0.00 | 0.00 | 0.00 |
March | 419.68 | 202.80 | 216.88 | 480.27 | 523.18 | 0.00 | 0.00 | 0.00 |
April | 472.13 | 216.04 | 256.09 | 632.55 | 424.89 | 0.00 | 0.00 | 0.00 |
May | 474.51 | 179.77 | 294.73 | 728.59 | 261.36 | 0.00 | 0.00 | 0.00 |
June | 499.00 | 191.96 | 307.04 | 873.08 | 177.32 | 0.00 | 0.00 | 0.00 |
July | 470.67 | 174.51 | 296.16 | 850.19 | 131.46 | 0.00 | 0.00 | 0.00 |
August | 461.19 | 172.47 | 288.73 | 837.97 | 118.90 | 0.00 | 0.00 | 0.00 |
September | 375.75 | 156.52 | 219.23 | 592.69 | 222.36 | 0.00 | 0.00 | 0.00 |
October | 334.75 | 173.77 | 160.98 | 431.57 | 473.27 | 0.00 | 0.00 | 0.00 |
November | 267.15 | 119.91 | 147.24 | 262.55 | 649.18 | 0.00 | 0.00 | 0.00 |
December | 220.40 | 96.40 | 124.00 | 154.67 | 836.76 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 377.81 | 161.15 | 216.66 | 524.19 | 453.31 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 220.40 | 96.40 | 124.00 | 154.67 | 118.90 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 499.00 | 216.04 | 307.04 | 873.08 | 878.23 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 494.80 | 0.00 | 494.80 | 67.62 | 3618.53 | 0.00 | 0.00 | 0.00 |
February | 548.44 | 0.00 | 548.44 | 226.63 | 2948.55 | 0.00 | 0.00 | 0.00 |
March | 769.98 | 0.00 | 769.98 | 505.89 | 1849.95 | 0.00 | 0.00 | 0.00 |
April | 931.36 | 4.13 | 927.23 | 1011.13 | 1463.35 | 0.00 | 0.00 | 0.00 |
May | 1113.89 | 35.55 | 1078.34 | 1554.53 | 941.58 | 0.00 | 0.00 | 0.00 |
June | 1225.88 | 80.94 | 1144.95 | 2259.93 | 593.62 | 0.00 | 0.00 | 0.00 |
July | 1156.62 | 56.22 | 1100.40 | 2273.74 | 424.86 | 0.00 | 0.00 | 0.00 |
August | 1028.63 | 11.21 | 1017.42 | 2082.17 | 349.03 | 0.00 | 0.00 | 0.00 |
September | 777.54 | 0.11 | 777.43 | 1172.59 | 797.91 | 0.00 | 0.00 | 0.00 |
October | 591.19 | 0.00 | 591.19 | 521.93 | 1678.93 | 0.00 | 0.00 | 0.00 |
November | 529.10 | 0.00 | 529.10 | 265.18 | 2317.87 | 0.00 | 0.00 | 0.00 |
December | 457.41 | 0.00 | 457.41 | 65.86 | 2940.57 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 803.45 | 15.75 | 787.71 | 1005.02 | 1653.83 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 457.41 | 0.00 | 457.41 | 65.86 | 349.03 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1225.88 | 80.94 | 1144.95 | 2273.74 | 3618.53 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 724.42 | 326.75 | 397.67 | 475.47 | 2161.23 | 0.00 | 0.00 | 0.00 |
February | 913.27 | 490.69 | 422.58 | 846.25 | 1775.69 | 0.00 | 0.00 | 0.00 |
March | 1149.00 | 523.06 | 625.94 | 1254.53 | 1138.15 | 0.00 | 0.00 | 0.00 |
April | 1389.44 | 633.55 | 755.89 | 1882.06 | 921.40 | 0.00 | 0.00 | 0.00 |
May | 1525.70 | 645.20 | 880.51 | 2316.15 | 621.07 | 0.00 | 0.00 | 0.00 |
June | 1579.62 | 662.06 | 917.56 | 2769.83 | 397.90 | 0.00 | 0.00 | 0.00 |
July | 1540.19 | 647.52 | 892.67 | 2803.47 | 286.61 | 0.00 | 0.00 | 0.00 |
August | 1408.77 | 558.91 | 849.86 | 2613.71 | 234.14 | 0.00 | 0.00 | 0.00 |
September | 1157.81 | 513.00 | 644.82 | 1845.26 | 511.97 | 0.00 | 0.00 | 0.00 |
October | 987.71 | 513.93 | 473.78 | 1240.08 | 1040.64 | 0.00 | 0.00 | 0.00 |
November | 789.68 | 357.57 | 432.12 | 751.69 | 1386.82 | 0.00 | 0.00 | 0.00 |
December | 684.02 | 311.80 | 372.22 | 483.00 | 1747.92 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1155.29 | 515.25 | 640.04 | 1610.79 | 1014.75 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 684.02 | 311.80 | 372.22 | 475.47 | 234.14 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1579.62 | 662.06 | 917.56 | 2803.47 | 2161.23 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 2646.25 | 1844.96 | 801.29 | 2860.62 | 3100.38 | 0.00 | 0.00 | 0.00 |
February | 2469.84 | 1655.60 | 814.24 | 2936.62 | 2666.05 | 0.00 | 0.00 | 0.00 |
March | 2221.22 | 1157.57 | 1063.65 | 2877.22 | 1867.14 | 0.00 | 0.00 | 0.00 |
April | 1663.55 | 541.52 | 1122.03 | 2430.47 | 1544.21 | 0.00 | 0.00 | 0.00 |
May | 1344.08 | 156.22 | 1187.86 | 2107.09 | 1010.31 | 0.00 | 0.00 | 0.00 |
June | 1242.74 | 69.15 | 1173.59 | 2368.93 | 636.50 | 0.00 | 0.00 | 0.00 |
July | 1256.39 | 93.68 | 1162.70 | 2525.20 | 448.85 | 0.00 | 0.00 | 0.00 |
August | 1500.04 | 280.21 | 1219.82 | 3058.05 | 379.01 | 0.00 | 0.00 | 0.00 |
September | 1649.67 | 613.59 | 1036.08 | 2811.86 | 846.78 | 0.00 | 0.00 | 0.00 |
October | 2391.55 | 1549.25 | 842.30 | 3461.69 | 1699.09 | 0.00 | 0.00 | 0.00 |
November | 2572.88 | 1707.32 | 865.56 | 3305.13 | 2217.01 | 0.00 | 0.00 | 0.00 |
December | 2608.47 | 1835.08 | 773.39 | 3027.11 | 2638.48 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1961.72 | 955.43 | 1006.30 | 2814.09 | 1581.99 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 1242.74 | 69.15 | 773.39 | 2107.09 | 379.01 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2646.25 | 1844.96 | 1219.82 | 3461.69 | 3100.38 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 744.08 | 345.16 | 398.93 | 550.57 | 2310.46 | 0.00 | 0.00 | 0.00 |
February | 854.20 | 399.39 | 454.81 | 840.82 | 1938.23 | 0.00 | 0.00 | 0.00 |
March | 1259.04 | 608.40 | 650.65 | 1514.37 | 1291.14 | 0.00 | 0.00 | 0.00 |
April | 1416.40 | 648.14 | 768.26 | 1978.18 | 1060.91 | 0.00 | 0.00 | 0.00 |
May | 1423.53 | 539.32 | 884.21 | 2211.06 | 709.27 | 0.00 | 0.00 | 0.00 |
June | 1497.02 | 575.90 | 921.13 | 2651.11 | 469.23 | 0.00 | 0.00 | 0.00 |
July | 1412.04 | 523.54 | 888.50 | 2599.77 | 337.53 | 0.00 | 0.00 | 0.00 |
August | 1383.59 | 517.41 | 866.19 | 2573.06 | 291.95 | 0.00 | 0.00 | 0.00 |
September | 1127.25 | 469.55 | 657.70 | 1809.13 | 576.98 | 0.00 | 0.00 | 0.00 |
October | 1004.25 | 521.31 | 482.93 | 1348.30 | 1179.86 | 0.00 | 0.00 | 0.00 |
November | 801.46 | 359.74 | 441.72 | 874.13 | 1574.55 | 0.00 | 0.00 | 0.00 |
December | 661.20 | 289.21 | 371.99 | 534.13 | 1947.33 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1133.43 | 483.44 | 649.98 | 1627.91 | 1136.48 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 661.20 | 289.21 | 371.99 | 534.13 | 291.95 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1497.02 | 648.14 | 921.13 | 2651.11 | 2310.46 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 494.80 | 0.00 | 494.80 | 79.37 | 3447.92 | 0.00 | 0.00 | 0.00 |
February | 548.44 | 0.00 | 548.44 | 242.49 | 2808.86 | 0.00 | 0.00 | 0.00 |
March | 769.98 | 0.00 | 769.98 | 535.30 | 1723.39 | 0.00 | 0.00 | 0.00 |
April | 931.36 | 4.13 | 927.23 | 1031.14 | 1390.93 | 0.00 | 0.00 | 0.00 |
May | 1113.89 | 35.55 | 1078.34 | 1545.00 | 925.80 | 0.00 | 0.00 | 0.00 |
June | 1225.88 | 80.94 | 1144.95 | 2232.59 | 600.17 | 0.00 | 0.00 | 0.00 |
July | 1156.62 | 56.22 | 1100.40 | 2239.23 | 435.37 | 0.00 | 0.00 | 0.00 |
August | 1028.63 | 11.21 | 1017.42 | 2048.58 | 361.13 | 0.00 | 0.00 | 0.00 |
September | 777.54 | 0.11 | 777.43 | 1172.18 | 767.06 | 0.00 | 0.00 | 0.00 |
October | 591.19 | 0.00 | 591.19 | 551.02 | 1549.59 | 0.00 | 0.00 | 0.00 |
November | 529.10 | 0.00 | 529.10 | 309.26 | 2124.17 | 0.00 | 0.00 | 0.00 |
December | 457.41 | 0.00 | 457.41 | 79.71 | 2720.45 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 803.45 | 15.75 | 787.71 | 1009.78 | 1564.91 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 457.41 | 0.00 | 457.41 | 79.37 | 361.13 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1225.88 | 80.94 | 1144.95 | 2239.23 | 3447.92 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 724.42 | 326.75 | 397.67 | 496.91 | 2050.50 | 0.00 | 0.00 | 0.00 |
February | 913.27 | 490.69 | 422.58 | 867.77 | 1690.21 | 0.00 | 0.00 | 0.00 |
March | 1149.00 | 523.06 | 625.94 | 1278.85 | 1072.19 | 0.00 | 0.00 | 0.00 |
April | 1389.44 | 633.55 | 755.89 | 1890.47 | 886.27 | 0.00 | 0.00 | 0.00 |
May | 1525.70 | 645.20 | 880.51 | 2304.24 | 616.66 | 0.00 | 0.00 | 0.00 |
June | 1579.62 | 662.06 | 917.56 | 2747.33 | 404.86 | 0.00 | 0.00 | 0.00 |
July | 1540.19 | 647.52 | 892.67 | 2777.75 | 294.07 | 0.00 | 0.00 | 0.00 |
August | 1408.77 | 558.91 | 849.86 | 2588.32 | 242.73 | 0.00 | 0.00 | 0.00 |
September | 1157.81 | 513.00 | 644.82 | 1840.04 | 498.30 | 0.00 | 0.00 | 0.00 |
October | 987.71 | 513.93 | 473.78 | 1260.32 | 973.46 | 0.00 | 0.00 | 0.00 |
November | 789.68 | 357.57 | 432.12 | 794.61 | 1279.85 | 0.00 | 0.00 | 0.00 |
December | 684.02 | 311.80 | 372.22 | 508.76 | 1613.92 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1155.29 | 515.25 | 640.04 | 1616.82 | 964.86 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 684.02 | 311.80 | 372.22 | 496.91 | 242.73 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1579.62 | 662.06 | 917.56 | 2777.75 | 2050.50 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 2646.25 | 1844.96 | 801.29 | 2917.58 | 2914.02 | 0.00 | 0.00 | 0.00 |
February | 2469.84 | 1655.60 | 814.24 | 2972.45 | 2521.39 | 0.00 | 0.00 | 0.00 |
March | 2221.22 | 1157.57 | 1063.65 | 2906.52 | 1751.59 | 0.00 | 0.00 | 0.00 |
April | 1663.55 | 541.52 | 1122.03 | 2445.33 | 1470.67 | 0.00 | 0.00 | 0.00 |
May | 1344.08 | 156.22 | 1187.86 | 2096.44 | 990.53 | 0.00 | 0.00 | 0.00 |
June | 1242.74 | 69.15 | 1173.59 | 2343.46 | 639.49 | 0.00 | 0.00 | 0.00 |
July | 1256.39 | 93.68 | 1162.70 | 2494.11 | 456.43 | 0.00 | 0.00 | 0.00 |
August | 1500.04 | 280.21 | 1219.82 | 3025.18 | 389.23 | 0.00 | 0.00 | 0.00 |
September | 1649.67 | 613.59 | 1036.08 | 2806.97 | 816.78 | 0.00 | 0.00 | 0.00 |
October | 2391.55 | 1549.25 | 842.30 | 3483.62 | 1586.40 | 0.00 | 0.00 | 0.00 |
November | 2572.88 | 1707.32 | 865.56 | 3363.98 | 2044.53 | 0.00 | 0.00 | 0.00 |
December | 2608.47 | 1835.08 | 773.39 | 3087.93 | 2427.41 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1961.72 | 955.43 | 1006.30 | 2828.42 | 1495.14 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 1242.74 | 69.15 | 773.39 | 2096.44 | 389.23 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2646.25 | 1844.96 | 1219.82 | 3483.62 | 2914.02 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 744.08 | 345.16 | 398.93 | 564.74 | 2191.53 | 0.00 | 0.00 | 0.00 |
February | 854.20 | 399.39 | 454.81 | 849.03 | 1854.56 | 0.00 | 0.00 | 0.00 |
March | 1259.04 | 608.40 | 650.65 | 1522.66 | 1221.09 | 0.00 | 0.00 | 0.00 |
April | 1416.40 | 648.14 | 768.26 | 1983.45 | 1016.83 | 0.00 | 0.00 | 0.00 |
May | 1423.53 | 539.32 | 884.21 | 2202.53 | 696.91 | 0.00 | 0.00 | 0.00 |
June | 1497.02 | 575.90 | 921.13 | 2631.47 | 469.93 | 0.00 | 0.00 | 0.00 |
July | 1412.04 | 523.54 | 888.50 | 2579.77 | 340.99 | 0.00 | 0.00 | 0.00 |
August | 1383.59 | 517.41 | 866.19 | 2552.40 | 296.63 | 0.00 | 0.00 | 0.00 |
September | 1127.25 | 469.55 | 657.70 | 1807.41 | 557.69 | 0.00 | 0.00 | 0.00 |
October | 1004.25 | 521.31 | 482.93 | 1357.79 | 1110.68 | 0.00 | 0.00 | 0.00 |
November | 801.46 | 359.74 | 441.72 | 896.18 | 1470.74 | 0.00 | 0.00 | 0.00 |
December | 661.20 | 289.21 | 371.99 | 547.63 | 1817.71 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1133.43 | 483.44 | 649.98 | 1628.72 | 1083.08 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 661.20 | 289.21 | 371.99 | 547.63 | 296.63 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1497.02 | 648.14 | 921.13 | 2631.47 | 2191.53 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.265058E+09 | 0.00 | 0.265058E+09 | 22227888.20 | 0.219857E+10 |
February | 0.265359E+09 | 0.00 | 0.265359E+09 | 83495965.94 | 0.163224E+10 |
March | 0.412466E+09 | 0.00 | 0.412466E+09 | 0.227285E+09 | 0.114344E+10 |
April | 0.482821E+09 | 2141454.47 | 0.480680E+09 | 0.486865E+09 | 0.845472E+09 |
May | 0.596695E+09 | 19043240.04 | 0.577652E+09 | 0.816775E+09 | 0.538919E+09 |
June | 0.635506E+09 | 41958388.76 | 0.593547E+09 | 0.115904E+10 | 0.319987E+09 |
July | 0.619587E+09 | 30118598.77 | 0.589469E+09 | 0.120595E+10 | 0.229149E+09 |
August | 0.551021E+09 | 6002513.07 | 0.545019E+09 | 0.110056E+10 | 0.183392E+09 |
September | 0.403084E+09 | 56742.98 | 0.403027E+09 | 0.590276E+09 | 0.457060E+09 |
October | 0.316694E+09 | 0.00 | 0.316694E+09 | 0.243291E+09 | 0.104228E+10 |
November | 0.274287E+09 | 0.00 | 0.274287E+09 | 93173326.51 | 0.140940E+10 |
December | 0.245026E+09 | 0.00 | 0.245026E+09 | 16985681.95 | 0.189693E+10 |
Annual Sum or Average | 0.506760E+10 | 99320938.09 | 0.496828E+10 | 0.604593E+10 | 0.118968E+11 |
Minimum of Months | 0.245026E+09 | 0.00 | 0.245026E+09 | 16985681.95 | 0.183392E+09 |
Maximum of Months | 0.635506E+09 | 41958388.76 | 0.593547E+09 | 0.120595E+10 | 0.219857E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.265057E+09 | 0.00 | 0.265057E+09 | 22227840.77 | 0.219857E+10 |
February | 0.265359E+09 | 0.00 | 0.265359E+09 | 83495860.33 | 0.163224E+10 |
March | 0.412465E+09 | 0.00 | 0.412465E+09 | 0.227285E+09 | 0.114344E+10 |
April | 0.482821E+09 | 2141451.90 | 0.480679E+09 | 0.486864E+09 | 0.845472E+09 |
May | 0.596695E+09 | 19043217.19 | 0.577651E+09 | 0.816775E+09 | 0.538919E+09 |
June | 0.635505E+09 | 41958338.42 | 0.593547E+09 | 0.115904E+10 | 0.319987E+09 |
July | 0.619587E+09 | 30118562.63 | 0.589468E+09 | 0.120595E+10 | 0.229149E+09 |
August | 0.551021E+09 | 6002505.87 | 0.545018E+09 | 0.110056E+10 | 0.183392E+09 |
September | 0.403084E+09 | 56742.91 | 0.403027E+09 | 0.590275E+09 | 0.457060E+09 |
October | 0.316693E+09 | 0.00 | 0.316693E+09 | 0.243291E+09 | 0.104228E+10 |
November | 0.274287E+09 | 0.00 | 0.274287E+09 | 93173178.34 | 0.140940E+10 |
December | 0.245026E+09 | 0.00 | 0.245026E+09 | 16985639.22 | 0.189693E+10 |
Annual Sum or Average | 0.506760E+10 | 99320818.92 | 0.496828E+10 | 0.604593E+10 | 0.118968E+11 |
Minimum of Months | 0.245026E+09 | 0.00 | 0.245026E+09 | 16985639.22 | 0.183392E+09 |
Maximum of Months | 0.635505E+09 | 41958338.42 | 0.593547E+09 | 0.120595E+10 | 0.219857E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.265058E+09 | 0.00 | 0.265058E+09 | 22227888.20 | 0.219857E+10 |
February | 0.265359E+09 | 0.00 | 0.265359E+09 | 83495965.94 | 0.163224E+10 |
March | 0.412466E+09 | 0.00 | 0.412466E+09 | 0.227285E+09 | 0.114344E+10 |
April | 0.482821E+09 | 2141454.47 | 0.480680E+09 | 0.486865E+09 | 0.845472E+09 |
May | 0.596695E+09 | 19043240.04 | 0.577652E+09 | 0.816775E+09 | 0.538919E+09 |
June | 0.635506E+09 | 41958388.76 | 0.593547E+09 | 0.115904E+10 | 0.319987E+09 |
July | 0.619587E+09 | 30118598.77 | 0.589469E+09 | 0.120595E+10 | 0.229149E+09 |
August | 0.551021E+09 | 6002513.07 | 0.545019E+09 | 0.110056E+10 | 0.183392E+09 |
September | 0.403084E+09 | 56742.98 | 0.403027E+09 | 0.590276E+09 | 0.457060E+09 |
October | 0.316694E+09 | 0.00 | 0.316694E+09 | 0.243291E+09 | 0.104228E+10 |
November | 0.274287E+09 | 0.00 | 0.274287E+09 | 93173326.51 | 0.140940E+10 |
December | 0.245026E+09 | 0.00 | 0.245026E+09 | 16985681.95 | 0.189693E+10 |
Annual Sum or Average | 0.506760E+10 | 99320938.09 | 0.496828E+10 | 0.604593E+10 | 0.118968E+11 |
Minimum of Months | 0.245026E+09 | 0.00 | 0.245026E+09 | 16985681.95 | 0.183392E+09 |
Maximum of Months | 0.635506E+09 | 41958388.76 | 0.593547E+09 | 0.120595E+10 | 0.219857E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.265057E+09 | 0.00 | 0.265057E+09 | 22227840.77 | 0.219857E+10 |
February | 0.265359E+09 | 0.00 | 0.265359E+09 | 83495860.33 | 0.163224E+10 |
March | 0.412465E+09 | 0.00 | 0.412465E+09 | 0.227285E+09 | 0.114344E+10 |
April | 0.482821E+09 | 2141451.90 | 0.480679E+09 | 0.486864E+09 | 0.845472E+09 |
May | 0.596695E+09 | 19043217.19 | 0.577651E+09 | 0.816775E+09 | 0.538919E+09 |
June | 0.635505E+09 | 41958338.42 | 0.593547E+09 | 0.115904E+10 | 0.319987E+09 |
July | 0.619587E+09 | 30118562.63 | 0.589468E+09 | 0.120595E+10 | 0.229149E+09 |
August | 0.551021E+09 | 6002505.87 | 0.545018E+09 | 0.110056E+10 | 0.183392E+09 |
September | 0.403084E+09 | 56742.91 | 0.403027E+09 | 0.590275E+09 | 0.457060E+09 |
October | 0.316693E+09 | 0.00 | 0.316693E+09 | 0.243291E+09 | 0.104228E+10 |
November | 0.274287E+09 | 0.00 | 0.274287E+09 | 93173178.34 | 0.140940E+10 |
December | 0.245026E+09 | 0.00 | 0.245026E+09 | 16985639.22 | 0.189693E+10 |
Annual Sum or Average | 0.506760E+10 | 99320818.92 | 0.496828E+10 | 0.604593E+10 | 0.118968E+11 |
Minimum of Months | 0.245026E+09 | 0.00 | 0.245026E+09 | 16985639.22 | 0.183392E+09 |
Maximum of Months | 0.635505E+09 | 41958338.42 | 0.593547E+09 | 0.120595E+10 | 0.219857E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.265047E+09 | 0.00 | 0.265047E+09 | 22226992.32 | 0.219848E+10 |
February | 0.265348E+09 | 0.00 | 0.265348E+09 | 83492600.69 | 0.163217E+10 |
March | 0.412449E+09 | 0.00 | 0.412449E+09 | 0.227276E+09 | 0.114339E+10 |
April | 0.482802E+09 | 2141368.16 | 0.480660E+09 | 0.486845E+09 | 0.845438E+09 |
May | 0.596671E+09 | 19042472.51 | 0.577629E+09 | 0.816742E+09 | 0.538897E+09 |
June | 0.635480E+09 | 41956697.65 | 0.593523E+09 | 0.115899E+10 | 0.319974E+09 |
July | 0.619563E+09 | 30117384.86 | 0.589445E+09 | 0.120590E+10 | 0.229140E+09 |
August | 0.550999E+09 | 6002271.14 | 0.544997E+09 | 0.110052E+10 | 0.183384E+09 |
September | 0.403068E+09 | 56740.69 | 0.403011E+09 | 0.590252E+09 | 0.457042E+09 |
October | 0.316681E+09 | 0.00 | 0.316681E+09 | 0.243281E+09 | 0.104224E+10 |
November | 0.274276E+09 | 0.00 | 0.274276E+09 | 93169571.22 | 0.140934E+10 |
December | 0.245016E+09 | 0.00 | 0.245016E+09 | 16984997.36 | 0.189685E+10 |
Annual Sum or Average | 0.506740E+10 | 99316935.02 | 0.496808E+10 | 0.604569E+10 | 0.118964E+11 |
Minimum of Months | 0.245016E+09 | 0.00 | 0.245016E+09 | 16984997.36 | 0.183384E+09 |
Maximum of Months | 0.635480E+09 | 41956697.65 | 0.593523E+09 | 0.120590E+10 | 0.219848E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.646771E+09 | 0.291727E+09 | 0.355045E+09 | 0.390226E+09 | 0.216651E+10 |
February | 0.736468E+09 | 0.395699E+09 | 0.340769E+09 | 0.653394E+09 | 0.159641E+10 |
March | 0.102584E+10 | 0.466991E+09 | 0.558846E+09 | 0.109881E+10 | 0.111352E+10 |
April | 0.120049E+10 | 0.547390E+09 | 0.653095E+09 | 0.162422E+10 | 0.835561E+09 |
May | 0.136216E+10 | 0.576039E+09 | 0.786124E+09 | 0.207870E+10 | 0.577072E+09 |
June | 0.136480E+10 | 0.572023E+09 | 0.792781E+09 | 0.240916E+10 | 0.339316E+09 |
July | 0.137510E+10 | 0.578110E+09 | 0.796986E+09 | 0.252509E+10 | 0.231509E+09 |
August | 0.125776E+10 | 0.498998E+09 | 0.758761E+09 | 0.235685E+10 | 0.168665E+09 |
September | 0.100036E+10 | 0.443234E+09 | 0.557127E+09 | 0.159393E+10 | 0.472996E+09 |
October | 0.881839E+09 | 0.458842E+09 | 0.422997E+09 | 0.108843E+10 | 0.102805E+10 |
November | 0.682295E+09 | 0.308940E+09 | 0.373354E+09 | 0.601382E+09 | 0.134979E+10 |
December | 0.610699E+09 | 0.278380E+09 | 0.332319E+09 | 0.390298E+09 | 0.180728E+10 |
Annual Sum or Average | 0.121446E+11 | 0.541637E+10 | 0.672820E+10 | 0.168105E+11 | 0.116867E+11 |
Minimum of Months | 0.610699E+09 | 0.278380E+09 | 0.332319E+09 | 0.390226E+09 | 0.168665E+09 |
Maximum of Months | 0.137510E+10 | 0.578110E+09 | 0.796986E+09 | 0.252509E+10 | 0.216651E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.646771E+09 | 0.291727E+09 | 0.355045E+09 | 0.390226E+09 | 0.216651E+10 |
February | 0.736468E+09 | 0.395699E+09 | 0.340769E+09 | 0.653394E+09 | 0.159641E+10 |
March | 0.102584E+10 | 0.466991E+09 | 0.558846E+09 | 0.109881E+10 | 0.111352E+10 |
April | 0.120049E+10 | 0.547390E+09 | 0.653095E+09 | 0.162422E+10 | 0.835561E+09 |
May | 0.136216E+10 | 0.576039E+09 | 0.786124E+09 | 0.207870E+10 | 0.577072E+09 |
June | 0.136480E+10 | 0.572023E+09 | 0.792781E+09 | 0.240916E+10 | 0.339316E+09 |
July | 0.137510E+10 | 0.578110E+09 | 0.796986E+09 | 0.252509E+10 | 0.231509E+09 |
August | 0.125776E+10 | 0.498998E+09 | 0.758761E+09 | 0.235685E+10 | 0.168665E+09 |
September | 0.100036E+10 | 0.443234E+09 | 0.557127E+09 | 0.159393E+10 | 0.472996E+09 |
October | 0.881839E+09 | 0.458842E+09 | 0.422997E+09 | 0.108843E+10 | 0.102805E+10 |
November | 0.682295E+09 | 0.308940E+09 | 0.373354E+09 | 0.601382E+09 | 0.134979E+10 |
December | 0.610699E+09 | 0.278380E+09 | 0.332319E+09 | 0.390298E+09 | 0.180728E+10 |
Annual Sum or Average | 0.121446E+11 | 0.541637E+10 | 0.672820E+10 | 0.168105E+11 | 0.116867E+11 |
Minimum of Months | 0.610699E+09 | 0.278380E+09 | 0.332319E+09 | 0.390226E+09 | 0.168665E+09 |
Maximum of Months | 0.137510E+10 | 0.578110E+09 | 0.796986E+09 | 0.252509E+10 | 0.216651E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.646759E+09 | 0.291721E+09 | 0.355038E+09 | 0.390219E+09 | 0.216647E+10 |
February | 0.736454E+09 | 0.395692E+09 | 0.340763E+09 | 0.653382E+09 | 0.159638E+10 |
March | 0.102582E+10 | 0.466982E+09 | 0.558836E+09 | 0.109879E+10 | 0.111350E+10 |
April | 0.120046E+10 | 0.547380E+09 | 0.653083E+09 | 0.162419E+10 | 0.835546E+09 |
May | 0.136214E+10 | 0.576029E+09 | 0.786110E+09 | 0.207866E+10 | 0.577062E+09 |
June | 0.136478E+10 | 0.572012E+09 | 0.792766E+09 | 0.240912E+10 | 0.339309E+09 |
July | 0.137507E+10 | 0.578100E+09 | 0.796972E+09 | 0.252505E+10 | 0.231504E+09 |
August | 0.125774E+10 | 0.498989E+09 | 0.758747E+09 | 0.235681E+10 | 0.168662E+09 |
September | 0.100034E+10 | 0.443226E+09 | 0.557117E+09 | 0.159390E+10 | 0.472987E+09 |
October | 0.881823E+09 | 0.458834E+09 | 0.422989E+09 | 0.108841E+10 | 0.102803E+10 |
November | 0.682282E+09 | 0.308935E+09 | 0.373347E+09 | 0.601371E+09 | 0.134976E+10 |
December | 0.610688E+09 | 0.278375E+09 | 0.332313E+09 | 0.390290E+09 | 0.180725E+10 |
Annual Sum or Average | 0.121444E+11 | 0.541627E+10 | 0.672808E+10 | 0.168102E+11 | 0.116865E+11 |
Minimum of Months | 0.610688E+09 | 0.278375E+09 | 0.332313E+09 | 0.390219E+09 | 0.168662E+09 |
Maximum of Months | 0.137507E+10 | 0.578100E+09 | 0.796972E+09 | 0.252505E+10 | 0.216647E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.141756E+10 | 0.988319E+09 | 0.429242E+09 | 0.152597E+10 | 0.176102E+10 |
February | 0.119502E+10 | 0.801056E+09 | 0.393966E+09 | 0.141756E+10 | 0.137679E+10 |
March | 0.118988E+10 | 0.620094E+09 | 0.569784E+09 | 0.154539E+10 | 0.106078E+10 |
April | 0.862392E+09 | 0.280727E+09 | 0.581665E+09 | 0.125735E+10 | 0.844704E+09 |
May | 0.720004E+09 | 83683975.89 | 0.636320E+09 | 0.112714E+10 | 0.564724E+09 |
June | 0.644245E+09 | 35849676.45 | 0.608395E+09 | 0.122053E+10 | 0.340884E+09 |
July | 0.673029E+09 | 50184911.53 | 0.622844E+09 | 0.134535E+10 | 0.240321E+09 |
August | 0.803549E+09 | 0.150106E+09 | 0.653443E+09 | 0.163451E+10 | 0.196251E+09 |
September | 0.855200E+09 | 0.318090E+09 | 0.537110E+09 | 0.146161E+10 | 0.459131E+09 |
October | 0.128112E+10 | 0.829913E+09 | 0.451210E+09 | 0.186317E+10 | 0.962152E+09 |
November | 0.133380E+10 | 0.885085E+09 | 0.448711E+09 | 0.171068E+10 | 0.122301E+10 |
December | 0.139732E+10 | 0.983028E+09 | 0.414296E+09 | 0.160948E+10 | 0.154367E+10 |
Annual Sum or Average | 0.123731E+11 | 0.602614E+10 | 0.634699E+10 | 0.177187E+11 | 0.105734E+11 |
Minimum of Months | 0.644245E+09 | 35849676.45 | 0.393966E+09 | 0.112714E+10 | 0.196251E+09 |
Maximum of Months | 0.141756E+10 | 0.988319E+09 | 0.653443E+09 | 0.186317E+10 | 0.176102E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.141756E+10 | 0.988318E+09 | 0.429242E+09 | 0.152597E+10 | 0.176102E+10 |
February | 0.119502E+10 | 0.801055E+09 | 0.393965E+09 | 0.141755E+10 | 0.137679E+10 |
March | 0.118988E+10 | 0.620094E+09 | 0.569783E+09 | 0.154539E+10 | 0.106078E+10 |
April | 0.862392E+09 | 0.280727E+09 | 0.581665E+09 | 0.125735E+10 | 0.844704E+09 |
May | 0.720003E+09 | 83683875.47 | 0.636320E+09 | 0.112713E+10 | 0.564724E+09 |
June | 0.644244E+09 | 35849633.43 | 0.608394E+09 | 0.122053E+10 | 0.340884E+09 |
July | 0.673029E+09 | 50184851.31 | 0.622844E+09 | 0.134535E+10 | 0.240321E+09 |
August | 0.803548E+09 | 0.150106E+09 | 0.653443E+09 | 0.163451E+10 | 0.196251E+09 |
September | 0.855199E+09 | 0.318089E+09 | 0.537109E+09 | 0.146161E+10 | 0.459131E+09 |
October | 0.128112E+10 | 0.829912E+09 | 0.451210E+09 | 0.186317E+10 | 0.962152E+09 |
November | 0.133379E+10 | 0.885084E+09 | 0.448711E+09 | 0.171068E+10 | 0.122301E+10 |
December | 0.139732E+10 | 0.983026E+09 | 0.414295E+09 | 0.160948E+10 | 0.154367E+10 |
Annual Sum or Average | 0.123731E+11 | 0.602613E+10 | 0.634698E+10 | 0.177187E+11 | 0.105734E+11 |
Minimum of Months | 0.644244E+09 | 35849633.43 | 0.393965E+09 | 0.112713E+10 | 0.196251E+09 |
Maximum of Months | 0.141756E+10 | 0.988318E+09 | 0.653443E+09 | 0.186317E+10 | 0.176102E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.141756E+10 | 0.988319E+09 | 0.429242E+09 | 0.152597E+10 | 0.176102E+10 |
February | 0.119502E+10 | 0.801056E+09 | 0.393966E+09 | 0.141756E+10 | 0.137679E+10 |
March | 0.118988E+10 | 0.620094E+09 | 0.569784E+09 | 0.154539E+10 | 0.106078E+10 |
April | 0.862392E+09 | 0.280727E+09 | 0.581665E+09 | 0.125735E+10 | 0.844704E+09 |
May | 0.720004E+09 | 83683975.89 | 0.636320E+09 | 0.112714E+10 | 0.564724E+09 |
June | 0.644245E+09 | 35849676.45 | 0.608395E+09 | 0.122053E+10 | 0.340884E+09 |
July | 0.673029E+09 | 50184911.53 | 0.622844E+09 | 0.134535E+10 | 0.240321E+09 |
August | 0.803549E+09 | 0.150106E+09 | 0.653443E+09 | 0.163451E+10 | 0.196251E+09 |
September | 0.855200E+09 | 0.318090E+09 | 0.537110E+09 | 0.146161E+10 | 0.459131E+09 |
October | 0.128112E+10 | 0.829913E+09 | 0.451210E+09 | 0.186317E+10 | 0.962152E+09 |
November | 0.133380E+10 | 0.885085E+09 | 0.448711E+09 | 0.171068E+10 | 0.122301E+10 |
December | 0.139732E+10 | 0.983028E+09 | 0.414296E+09 | 0.160948E+10 | 0.154367E+10 |
Annual Sum or Average | 0.123731E+11 | 0.602614E+10 | 0.634699E+10 | 0.177187E+11 | 0.105734E+11 |
Minimum of Months | 0.644245E+09 | 35849676.45 | 0.393966E+09 | 0.112714E+10 | 0.196251E+09 |
Maximum of Months | 0.141756E+10 | 0.988319E+09 | 0.653443E+09 | 0.186317E+10 | 0.176102E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.141756E+10 | 0.988318E+09 | 0.429242E+09 | 0.152597E+10 | 0.176102E+10 |
February | 0.119502E+10 | 0.801055E+09 | 0.393965E+09 | 0.141755E+10 | 0.137679E+10 |
March | 0.118988E+10 | 0.620094E+09 | 0.569783E+09 | 0.154539E+10 | 0.106078E+10 |
April | 0.862392E+09 | 0.280727E+09 | 0.581665E+09 | 0.125735E+10 | 0.844704E+09 |
May | 0.720003E+09 | 83683875.47 | 0.636320E+09 | 0.112713E+10 | 0.564724E+09 |
June | 0.644244E+09 | 35849633.43 | 0.608394E+09 | 0.122053E+10 | 0.340884E+09 |
July | 0.673029E+09 | 50184851.31 | 0.622844E+09 | 0.134535E+10 | 0.240321E+09 |
August | 0.803548E+09 | 0.150106E+09 | 0.653443E+09 | 0.163451E+10 | 0.196251E+09 |
September | 0.855199E+09 | 0.318089E+09 | 0.537109E+09 | 0.146161E+10 | 0.459131E+09 |
October | 0.128112E+10 | 0.829912E+09 | 0.451210E+09 | 0.186317E+10 | 0.962152E+09 |
November | 0.133379E+10 | 0.885084E+09 | 0.448711E+09 | 0.171068E+10 | 0.122301E+10 |
December | 0.139732E+10 | 0.983026E+09 | 0.414295E+09 | 0.160948E+10 | 0.154367E+10 |
Annual Sum or Average | 0.123731E+11 | 0.602613E+10 | 0.634698E+10 | 0.177187E+11 | 0.105734E+11 |
Minimum of Months | 0.644244E+09 | 35849633.43 | 0.393965E+09 | 0.112713E+10 | 0.196251E+09 |
Maximum of Months | 0.141756E+10 | 0.988318E+09 | 0.653443E+09 | 0.186317E+10 | 0.176102E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.141750E+10 | 0.988279E+09 | 0.429225E+09 | 0.152591E+10 | 0.176095E+10 |
February | 0.119497E+10 | 0.801023E+09 | 0.393950E+09 | 0.141750E+10 | 0.137674E+10 |
March | 0.118983E+10 | 0.620069E+09 | 0.569761E+09 | 0.154533E+10 | 0.106074E+10 |
April | 0.862358E+09 | 0.280716E+09 | 0.581642E+09 | 0.125730E+10 | 0.844670E+09 |
May | 0.719975E+09 | 83680603.05 | 0.636294E+09 | 0.112709E+10 | 0.564702E+09 |
June | 0.644219E+09 | 35848231.55 | 0.608370E+09 | 0.122048E+10 | 0.340870E+09 |
July | 0.673002E+09 | 50182888.86 | 0.622819E+09 | 0.134530E+10 | 0.240311E+09 |
August | 0.803517E+09 | 0.150100E+09 | 0.653417E+09 | 0.163444E+10 | 0.196243E+09 |
September | 0.855165E+09 | 0.318077E+09 | 0.537088E+09 | 0.146155E+10 | 0.459112E+09 |
October | 0.128107E+10 | 0.829879E+09 | 0.451192E+09 | 0.186310E+10 | 0.962113E+09 |
November | 0.133374E+10 | 0.885050E+09 | 0.448693E+09 | 0.171061E+10 | 0.122297E+10 |
December | 0.139727E+10 | 0.982988E+09 | 0.414279E+09 | 0.160942E+10 | 0.154361E+10 |
Annual Sum or Average | 0.123726E+11 | 0.602589E+10 | 0.634673E+10 | 0.177180E+11 | 0.105730E+11 |
Minimum of Months | 0.644219E+09 | 35848231.55 | 0.393950E+09 | 0.112709E+10 | 0.196243E+09 |
Maximum of Months | 0.141750E+10 | 0.988279E+09 | 0.653417E+09 | 0.186310E+10 | 0.176095E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.664324E+09 | 0.308160E+09 | 0.356164E+09 | 0.452758E+09 | 0.235230E+10 |
February | 0.688836E+09 | 0.322072E+09 | 0.366763E+09 | 0.629278E+09 | 0.184258E+10 |
March | 0.112409E+10 | 0.543184E+09 | 0.580902E+09 | 0.128637E+10 | 0.140132E+10 |
April | 0.122378E+10 | 0.559998E+09 | 0.663785E+09 | 0.163960E+10 | 0.110134E+10 |
May | 0.127094E+10 | 0.481508E+09 | 0.789429E+09 | 0.195149E+10 | 0.700029E+09 |
June | 0.129344E+10 | 0.497581E+09 | 0.795861E+09 | 0.226306E+10 | 0.459629E+09 |
July | 0.126068E+10 | 0.467417E+09 | 0.793262E+09 | 0.227720E+10 | 0.352103E+09 |
August | 0.123529E+10 | 0.461948E+09 | 0.773338E+09 | 0.224446E+10 | 0.318464E+09 |
September | 0.973955E+09 | 0.405695E+09 | 0.568260E+09 | 0.153629E+10 | 0.576377E+09 |
October | 0.896601E+09 | 0.465434E+09 | 0.431167E+09 | 0.115595E+10 | 0.126763E+10 |
November | 0.692470E+09 | 0.310816E+09 | 0.381654E+09 | 0.680547E+09 | 0.168271E+10 |
December | 0.590326E+09 | 0.258209E+09 | 0.332117E+09 | 0.414288E+09 | 0.224121E+10 |
Annual Sum or Average | 0.119147E+11 | 0.508202E+10 | 0.683270E+10 | 0.165313E+11 | 0.142957E+11 |
Minimum of Months | 0.590326E+09 | 0.258209E+09 | 0.332117E+09 | 0.414288E+09 | 0.318464E+09 |
Maximum of Months | 0.129344E+10 | 0.559998E+09 | 0.795861E+09 | 0.227720E+10 | 0.235230E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.664324E+09 | 0.308160E+09 | 0.356164E+09 | 0.452758E+09 | 0.235230E+10 |
February | 0.688836E+09 | 0.322072E+09 | 0.366763E+09 | 0.629278E+09 | 0.184258E+10 |
March | 0.112409E+10 | 0.543184E+09 | 0.580902E+09 | 0.128637E+10 | 0.140132E+10 |
April | 0.122378E+10 | 0.559998E+09 | 0.663785E+09 | 0.163960E+10 | 0.110134E+10 |
May | 0.127094E+10 | 0.481508E+09 | 0.789429E+09 | 0.195149E+10 | 0.700029E+09 |
June | 0.129344E+10 | 0.497581E+09 | 0.795861E+09 | 0.226306E+10 | 0.459629E+09 |
July | 0.126068E+10 | 0.467417E+09 | 0.793262E+09 | 0.227720E+10 | 0.352103E+09 |
August | 0.123529E+10 | 0.461948E+09 | 0.773338E+09 | 0.224446E+10 | 0.318464E+09 |
September | 0.973955E+09 | 0.405695E+09 | 0.568260E+09 | 0.153629E+10 | 0.576377E+09 |
October | 0.896601E+09 | 0.465434E+09 | 0.431167E+09 | 0.115595E+10 | 0.126763E+10 |
November | 0.692470E+09 | 0.310816E+09 | 0.381654E+09 | 0.680547E+09 | 0.168271E+10 |
December | 0.590326E+09 | 0.258209E+09 | 0.332117E+09 | 0.414288E+09 | 0.224121E+10 |
Annual Sum or Average | 0.119147E+11 | 0.508202E+10 | 0.683270E+10 | 0.165313E+11 | 0.142957E+11 |
Minimum of Months | 0.590326E+09 | 0.258209E+09 | 0.332117E+09 | 0.414288E+09 | 0.318464E+09 |
Maximum of Months | 0.129344E+10 | 0.559998E+09 | 0.795861E+09 | 0.227720E+10 | 0.235230E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.664312E+09 | 0.308155E+09 | 0.356157E+09 | 0.452750E+09 | 0.235226E+10 |
February | 0.688823E+09 | 0.322067E+09 | 0.366757E+09 | 0.629266E+09 | 0.184254E+10 |
March | 0.112407E+10 | 0.543174E+09 | 0.580892E+09 | 0.128635E+10 | 0.140130E+10 |
April | 0.122376E+10 | 0.559988E+09 | 0.663773E+09 | 0.163957E+10 | 0.110132E+10 |
May | 0.127091E+10 | 0.481499E+09 | 0.789415E+09 | 0.195145E+10 | 0.700016E+09 |
June | 0.129342E+10 | 0.497572E+09 | 0.795846E+09 | 0.226302E+10 | 0.459621E+09 |
July | 0.126066E+10 | 0.467408E+09 | 0.793247E+09 | 0.227715E+10 | 0.352096E+09 |
August | 0.123526E+10 | 0.461939E+09 | 0.773324E+09 | 0.224441E+10 | 0.318458E+09 |
September | 0.973937E+09 | 0.405687E+09 | 0.568250E+09 | 0.153626E+10 | 0.576366E+09 |
October | 0.896584E+09 | 0.465426E+09 | 0.431159E+09 | 0.115593E+10 | 0.126761E+10 |
November | 0.692457E+09 | 0.310810E+09 | 0.381647E+09 | 0.680535E+09 | 0.168268E+10 |
December | 0.590315E+09 | 0.258205E+09 | 0.332110E+09 | 0.414280E+09 | 0.224117E+10 |
Annual Sum or Average | 0.119145E+11 | 0.508193E+10 | 0.683258E+10 | 0.165310E+11 | 0.142954E+11 |
Minimum of Months | 0.590315E+09 | 0.258205E+09 | 0.332110E+09 | 0.414280E+09 | 0.318458E+09 |
Maximum of Months | 0.129342E+10 | 0.559988E+09 | 0.795846E+09 | 0.227715E+10 | 0.235226E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.132527E+10 | 0.00 | 0.132527E+10 | 0.181104E+09 | 0.969187E+10 |
February | 0.132678E+10 | 0.00 | 0.132678E+10 | 0.548263E+09 | 0.713312E+10 |
March | 0.206230E+10 | 0.00 | 0.206230E+10 | 0.135498E+10 | 0.495491E+10 |
April | 0.241408E+10 | 10707142.87 | 0.240337E+10 | 0.262085E+10 | 0.379300E+10 |
May | 0.298344E+10 | 95215048.85 | 0.288822E+10 | 0.416365E+10 | 0.252193E+10 |
June | 0.317749E+10 | 0.209789E+09 | 0.296770E+10 | 0.585773E+10 | 0.153865E+10 |
July | 0.309790E+10 | 0.150591E+09 | 0.294731E+10 | 0.608999E+10 | 0.113796E+10 |
August | 0.275507E+10 | 30012202.44 | 0.272506E+10 | 0.557687E+10 | 0.934833E+09 |
September | 0.201540E+10 | 283711.47 | 0.201511E+10 | 0.303936E+10 | 0.206818E+10 |
October | 0.158345E+10 | 0.00 | 0.158345E+10 | 0.139793E+10 | 0.449683E+10 |
November | 0.137142E+10 | 0.00 | 0.137142E+10 | 0.687335E+09 | 0.600792E+10 |
December | 0.122512E+10 | 0.00 | 0.122512E+10 | 0.176393E+09 | 0.787604E+10 |
Annual Sum or Average | 0.253377E+11 | 0.496599E+09 | 0.248411E+11 | 0.316945E+11 | 0.521552E+11 |
Minimum of Months | 0.122512E+10 | 0.00 | 0.122512E+10 | 0.176393E+09 | 0.934833E+09 |
Maximum of Months | 0.317749E+10 | 0.209789E+09 | 0.296770E+10 | 0.608999E+10 | 0.969187E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.194029E+10 | 0.875171E+09 | 0.106512E+10 | 0.127350E+10 | 0.578864E+10 |
February | 0.220938E+10 | 0.118708E+10 | 0.102230E+10 | 0.204724E+10 | 0.429575E+10 |
March | 0.307748E+10 | 0.140096E+10 | 0.167652E+10 | 0.336012E+10 | 0.304843E+10 |
April | 0.360142E+10 | 0.164215E+10 | 0.195927E+10 | 0.487829E+10 | 0.238827E+10 |
May | 0.408645E+10 | 0.172810E+10 | 0.235835E+10 | 0.620357E+10 | 0.166347E+10 |
June | 0.409437E+10 | 0.171605E+10 | 0.237832E+10 | 0.717939E+10 | 0.103134E+10 |
July | 0.412525E+10 | 0.173431E+10 | 0.239094E+10 | 0.750882E+10 | 0.767652E+09 |
August | 0.377324E+10 | 0.149698E+10 | 0.227626E+10 | 0.700055E+10 | 0.627127E+09 |
September | 0.300105E+10 | 0.132969E+10 | 0.167136E+10 | 0.478292E+10 | 0.132704E+10 |
October | 0.264549E+10 | 0.137651E+10 | 0.126898E+10 | 0.332144E+10 | 0.278725E+10 |
November | 0.204686E+10 | 0.926812E+09 | 0.112005E+10 | 0.194838E+10 | 0.359463E+10 |
December | 0.183208E+10 | 0.835132E+09 | 0.996946E+09 | 0.129367E+10 | 0.468163E+10 |
Annual Sum or Average | 0.364334E+11 | 0.162490E+11 | 0.201844E+11 | 0.507979E+11 | 0.320012E+11 |
Minimum of Months | 0.183208E+10 | 0.835132E+09 | 0.996946E+09 | 0.127350E+10 | 0.627127E+09 |
Maximum of Months | 0.412525E+10 | 0.173431E+10 | 0.239094E+10 | 0.750882E+10 | 0.578864E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.708772E+10 | 0.494154E+10 | 0.214619E+10 | 0.766188E+10 | 0.830407E+10 |
February | 0.597503E+10 | 0.400523E+10 | 0.196980E+10 | 0.710428E+10 | 0.644972E+10 |
March | 0.594932E+10 | 0.310043E+10 | 0.284888E+10 | 0.770635E+10 | 0.500094E+10 |
April | 0.431191E+10 | 0.140362E+10 | 0.290829E+10 | 0.629977E+10 | 0.400259E+10 |
May | 0.359998E+10 | 0.418415E+09 | 0.318156E+10 | 0.564362E+10 | 0.270602E+10 |
June | 0.322118E+10 | 0.179246E+09 | 0.304194E+10 | 0.614026E+10 | 0.164980E+10 |
July | 0.336511E+10 | 0.250922E+09 | 0.311418E+10 | 0.676351E+10 | 0.120220E+10 |
August | 0.401770E+10 | 0.750520E+09 | 0.326718E+10 | 0.819068E+10 | 0.101515E+10 |
September | 0.427595E+10 | 0.159043E+10 | 0.268552E+10 | 0.728834E+10 | 0.219485E+10 |
October | 0.640554E+10 | 0.414951E+10 | 0.225602E+10 | 0.927179E+10 | 0.455084E+10 |
November | 0.666890E+10 | 0.442537E+10 | 0.224353E+10 | 0.856688E+10 | 0.574650E+10 |
December | 0.698653E+10 | 0.491508E+10 | 0.207145E+10 | 0.810780E+10 | 0.706689E+10 |
Annual Sum or Average | 0.618649E+11 | 0.301303E+11 | 0.317346E+11 | 0.887452E+11 | 0.498896E+11 |
Minimum of Months | 0.322118E+10 | 0.179246E+09 | 0.196980E+10 | 0.564362E+10 | 0.101515E+10 |
Maximum of Months | 0.708772E+10 | 0.494154E+10 | 0.326718E+10 | 0.927179E+10 | 0.830407E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.199295E+10 | 0.924471E+09 | 0.106848E+10 | 0.147464E+10 | 0.618834E+10 |
February | 0.206649E+10 | 0.966207E+09 | 0.110028E+10 | 0.203411E+10 | 0.468896E+10 |
March | 0.337222E+10 | 0.162954E+10 | 0.174269E+10 | 0.405608E+10 | 0.345818E+10 |
April | 0.367131E+10 | 0.167998E+10 | 0.199134E+10 | 0.512744E+10 | 0.274987E+10 |
May | 0.381277E+10 | 0.144451E+10 | 0.236826E+10 | 0.592211E+10 | 0.189972E+10 |
June | 0.388029E+10 | 0.149273E+10 | 0.238756E+10 | 0.687168E+10 | 0.121624E+10 |
July | 0.378200E+10 | 0.140224E+10 | 0.237976E+10 | 0.696323E+10 | 0.904038E+09 |
August | 0.370582E+10 | 0.138583E+10 | 0.231999E+10 | 0.689167E+10 | 0.781965E+09 |
September | 0.292184E+10 | 0.121707E+10 | 0.170476E+10 | 0.468926E+10 | 0.149554E+10 |
October | 0.268978E+10 | 0.139629E+10 | 0.129349E+10 | 0.361130E+10 | 0.316013E+10 |
November | 0.207739E+10 | 0.932439E+09 | 0.114495E+10 | 0.226575E+10 | 0.408124E+10 |
December | 0.177096E+10 | 0.774620E+09 | 0.996339E+09 | 0.143061E+10 | 0.521573E+10 |
Annual Sum or Average | 0.357438E+11 | 0.152459E+11 | 0.204979E+11 | 0.513379E+11 | 0.358400E+11 |
Minimum of Months | 0.177096E+10 | 0.774620E+09 | 0.996339E+09 | 0.143061E+10 | 0.781965E+09 |
Maximum of Months | 0.388029E+10 | 0.167998E+10 | 0.238756E+10 | 0.696323E+10 | 0.618834E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.132527E+10 | 0.00 | 0.132527E+10 | 0.212577E+09 | 0.923491E+10 |
February | 0.132678E+10 | 0.00 | 0.132678E+10 | 0.586628E+09 | 0.679518E+10 |
March | 0.206230E+10 | 0.00 | 0.206230E+10 | 0.143374E+10 | 0.461593E+10 |
April | 0.241408E+10 | 10707142.87 | 0.240337E+10 | 0.267271E+10 | 0.360530E+10 |
May | 0.298344E+10 | 95215048.85 | 0.288822E+10 | 0.413813E+10 | 0.247965E+10 |
June | 0.317749E+10 | 0.209789E+09 | 0.296770E+10 | 0.578688E+10 | 0.155563E+10 |
July | 0.309790E+10 | 0.150591E+09 | 0.294731E+10 | 0.599755E+10 | 0.116610E+10 |
August | 0.275507E+10 | 30012202.44 | 0.272506E+10 | 0.548693E+10 | 0.967249E+09 |
September | 0.201540E+10 | 283711.47 | 0.201511E+10 | 0.303828E+10 | 0.198822E+10 |
October | 0.158345E+10 | 0.00 | 0.158345E+10 | 0.147586E+10 | 0.415041E+10 |
November | 0.137142E+10 | 0.00 | 0.137142E+10 | 0.801605E+09 | 0.550586E+10 |
December | 0.122512E+10 | 0.00 | 0.122512E+10 | 0.213499E+09 | 0.728646E+10 |
Annual Sum or Average | 0.253377E+11 | 0.496599E+09 | 0.248411E+11 | 0.318444E+11 | 0.493509E+11 |
Minimum of Months | 0.122512E+10 | 0.00 | 0.122512E+10 | 0.212577E+09 | 0.967249E+09 |
Maximum of Months | 0.317749E+10 | 0.209789E+09 | 0.296770E+10 | 0.599755E+10 | 0.923491E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.194029E+10 | 0.875171E+09 | 0.106512E+10 | 0.133093E+10 | 0.549205E+10 |
February | 0.220938E+10 | 0.118708E+10 | 0.102230E+10 | 0.209931E+10 | 0.408894E+10 |
March | 0.307748E+10 | 0.140096E+10 | 0.167652E+10 | 0.342528E+10 | 0.287175E+10 |
April | 0.360142E+10 | 0.164215E+10 | 0.195927E+10 | 0.490009E+10 | 0.229721E+10 |
May | 0.408645E+10 | 0.172810E+10 | 0.235835E+10 | 0.617167E+10 | 0.165166E+10 |
June | 0.409437E+10 | 0.171605E+10 | 0.237832E+10 | 0.712107E+10 | 0.104940E+10 |
July | 0.412525E+10 | 0.173431E+10 | 0.239094E+10 | 0.743994E+10 | 0.787632E+09 |
August | 0.377324E+10 | 0.149698E+10 | 0.227626E+10 | 0.693257E+10 | 0.650135E+09 |
September | 0.300105E+10 | 0.132969E+10 | 0.167136E+10 | 0.476939E+10 | 0.129159E+10 |
October | 0.264549E+10 | 0.137651E+10 | 0.126898E+10 | 0.337563E+10 | 0.260731E+10 |
November | 0.204686E+10 | 0.926812E+09 | 0.112005E+10 | 0.205963E+10 | 0.331736E+10 |
December | 0.183208E+10 | 0.835132E+09 | 0.996946E+09 | 0.136265E+10 | 0.432272E+10 |
Annual Sum or Average | 0.364334E+11 | 0.162490E+11 | 0.201844E+11 | 0.509882E+11 | 0.304278E+11 |
Minimum of Months | 0.183208E+10 | 0.835132E+09 | 0.996946E+09 | 0.133093E+10 | 0.650135E+09 |
Maximum of Months | 0.412525E+10 | 0.173431E+10 | 0.239094E+10 | 0.743994E+10 | 0.549205E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.708772E+10 | 0.494154E+10 | 0.214619E+10 | 0.781444E+10 | 0.780490E+10 |
February | 0.597503E+10 | 0.400523E+10 | 0.196980E+10 | 0.719095E+10 | 0.609976E+10 |
March | 0.594932E+10 | 0.310043E+10 | 0.284888E+10 | 0.778481E+10 | 0.469147E+10 |
April | 0.431191E+10 | 0.140362E+10 | 0.290829E+10 | 0.633830E+10 | 0.381196E+10 |
May | 0.359998E+10 | 0.418415E+09 | 0.318156E+10 | 0.561510E+10 | 0.265305E+10 |
June | 0.322118E+10 | 0.179246E+09 | 0.304194E+10 | 0.607425E+10 | 0.165756E+10 |
July | 0.336511E+10 | 0.250922E+09 | 0.311418E+10 | 0.668023E+10 | 0.122250E+10 |
August | 0.401770E+10 | 0.750520E+09 | 0.326718E+10 | 0.810263E+10 | 0.104252E+10 |
September | 0.427595E+10 | 0.159043E+10 | 0.268552E+10 | 0.727566E+10 | 0.211709E+10 |
October | 0.640554E+10 | 0.414951E+10 | 0.225602E+10 | 0.933052E+10 | 0.424902E+10 |
November | 0.666890E+10 | 0.442537E+10 | 0.224353E+10 | 0.871944E+10 | 0.529942E+10 |
December | 0.698653E+10 | 0.491508E+10 | 0.207145E+10 | 0.827071E+10 | 0.650157E+10 |
Annual Sum or Average | 0.618649E+11 | 0.301303E+11 | 0.317346E+11 | 0.891971E+11 | 0.471508E+11 |
Minimum of Months | 0.322118E+10 | 0.179246E+09 | 0.196980E+10 | 0.561510E+10 | 0.104252E+10 |
Maximum of Months | 0.708772E+10 | 0.494154E+10 | 0.326718E+10 | 0.933052E+10 | 0.780490E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.199295E+10 | 0.924471E+09 | 0.106848E+10 | 0.151259E+10 | 0.586978E+10 |
February | 0.206649E+10 | 0.966207E+09 | 0.110028E+10 | 0.205398E+10 | 0.448654E+10 |
March | 0.337222E+10 | 0.162954E+10 | 0.174269E+10 | 0.407831E+10 | 0.327057E+10 |
April | 0.367131E+10 | 0.167998E+10 | 0.199134E+10 | 0.514110E+10 | 0.263563E+10 |
May | 0.381277E+10 | 0.144451E+10 | 0.236826E+10 | 0.589926E+10 | 0.186661E+10 |
June | 0.388029E+10 | 0.149273E+10 | 0.238756E+10 | 0.682077E+10 | 0.121805E+10 |
July | 0.378200E+10 | 0.140224E+10 | 0.237976E+10 | 0.690967E+10 | 0.913304E+09 |
August | 0.370582E+10 | 0.138583E+10 | 0.231999E+10 | 0.683635E+10 | 0.794507E+09 |
September | 0.292184E+10 | 0.121707E+10 | 0.170476E+10 | 0.468481E+10 | 0.144554E+10 |
October | 0.268978E+10 | 0.139629E+10 | 0.129349E+10 | 0.363670E+10 | 0.297486E+10 |
November | 0.207739E+10 | 0.932439E+09 | 0.114495E+10 | 0.232290E+10 | 0.381215E+10 |
December | 0.177096E+10 | 0.774620E+09 | 0.996339E+09 | 0.146676E+10 | 0.486854E+10 |
Annual Sum or Average | 0.357438E+11 | 0.152459E+11 | 0.204979E+11 | 0.513632E+11 | 0.341561E+11 |
Minimum of Months | 0.177096E+10 | 0.774620E+09 | 0.996339E+09 | 0.146676E+10 | 0.794507E+09 |
Maximum of Months | 0.388029E+10 | 0.167998E+10 | 0.238756E+10 | 0.690967E+10 | 0.586978E+10 |
Report: WindowZoneSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 41.49 | 4104.23 | 494.80 | 0.00 | 494.80 | 0.00 | 0.00 |
February | 172.57 | 3373.48 | 548.44 | 0.00 | 548.44 | 0.00 | 0.00 |
March | 424.29 | 2134.54 | 769.98 | 0.00 | 769.98 | 0.00 | 0.00 |
April | 939.16 | 1630.91 | 931.36 | 4.13 | 927.23 | 0.00 | 0.00 |
May | 1524.73 | 1006.04 | 1113.89 | 35.55 | 1078.34 | 0.00 | 0.00 |
June | 2235.78 | 617.25 | 1225.89 | 80.94 | 1144.95 | 0.00 | 0.00 |
July | 2251.24 | 427.77 | 1156.63 | 56.22 | 1100.40 | 0.00 | 0.00 |
August | 2054.50 | 342.35 | 1028.63 | 11.21 | 1017.42 | 0.00 | 0.00 |
September | 1138.64 | 881.67 | 777.55 | 0.11 | 777.44 | 0.00 | 0.00 |
October | 454.17 | 1945.71 | 591.19 | 0.00 | 591.19 | 0.00 | 0.00 |
November | 179.73 | 2718.73 | 529.10 | 0.00 | 529.10 | 0.00 | 0.00 |
December | 31.71 | 3541.13 | 457.41 | 0.00 | 457.41 | 0.00 | 0.00 |
Annual Sum or Average | 958.57 | 1886.22 | 803.46 | 15.75 | 787.71 | 0.00 | 0.00 |
Minimum of Months | 31.71 | 342.35 | 457.41 | 0.00 | 457.41 | 0.00 | 0.00 |
Maximum of Months | 2251.24 | 4104.23 | 1225.89 | 80.94 | 1144.95 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 437.08 | 2426.63 | 724.43 | 326.75 | 397.67 | 0.00 | 0.00 |
February | 810.26 | 1979.66 | 913.27 | 490.69 | 422.58 | 0.00 | 0.00 |
March | 1230.74 | 1247.21 | 1149.00 | 523.06 | 625.94 | 0.00 | 0.00 |
April | 1879.87 | 967.08 | 1389.44 | 633.55 | 755.89 | 0.00 | 0.00 |
May | 2328.28 | 646.36 | 1525.71 | 645.20 | 880.51 | 0.00 | 0.00 |
June | 2788.36 | 392.72 | 1579.62 | 662.06 | 917.56 | 0.00 | 0.00 |
July | 2828.27 | 259.30 | 1540.20 | 647.52 | 892.68 | 0.00 | 0.00 |
August | 2639.83 | 188.92 | 1408.77 | 558.91 | 849.86 | 0.00 | 0.00 |
September | 1844.82 | 547.45 | 1157.82 | 513.00 | 644.82 | 0.00 | 0.00 |
October | 1219.11 | 1151.48 | 987.72 | 513.93 | 473.78 | 0.00 | 0.00 |
November | 696.04 | 1562.24 | 789.69 | 357.57 | 432.12 | 0.00 | 0.00 |
December | 437.16 | 2024.28 | 684.02 | 311.80 | 372.22 | 0.00 | 0.00 |
Annual Sum or Average | 1599.16 | 1111.74 | 1155.30 | 515.25 | 640.05 | 0.00 | 0.00 |
Minimum of Months | 437.08 | 188.92 | 684.02 | 311.80 | 372.22 | 0.00 | 0.00 |
Maximum of Months | 2828.27 | 2426.63 | 1579.62 | 662.06 | 917.56 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 2848.64 | 3287.43 | 2646.26 | 1844.96 | 801.30 | 0.00 | 0.00 |
February | 2929.78 | 2845.53 | 2469.85 | 1655.61 | 814.24 | 0.00 | 0.00 |
March | 2884.90 | 1980.24 | 2221.23 | 1157.57 | 1063.66 | 0.00 | 0.00 |
April | 2425.42 | 1629.43 | 1663.55 | 541.52 | 1122.03 | 0.00 | 0.00 |
May | 2104.10 | 1054.21 | 1344.08 | 156.22 | 1187.86 | 0.00 | 0.00 |
June | 2354.39 | 657.56 | 1242.75 | 69.15 | 1173.59 | 0.00 | 0.00 |
July | 2511.46 | 448.62 | 1256.39 | 93.68 | 1162.71 | 0.00 | 0.00 |
August | 3051.25 | 366.36 | 1500.04 | 280.21 | 1219.83 | 0.00 | 0.00 |
September | 2819.44 | 885.66 | 1649.68 | 613.59 | 1036.08 | 0.00 | 0.00 |
October | 3478.11 | 1796.12 | 2391.56 | 1549.26 | 842.31 | 0.00 | 0.00 |
November | 3299.89 | 2359.19 | 2572.89 | 1707.33 | 865.56 | 0.00 | 0.00 |
December | 3004.53 | 2881.68 | 2608.48 | 1835.09 | 773.40 | 0.00 | 0.00 |
Annual Sum or Average | 2809.26 | 1676.40 | 1961.73 | 955.43 | 1006.30 | 0.00 | 0.00 |
Minimum of Months | 2104.10 | 366.36 | 1242.75 | 69.15 | 773.40 | 0.00 | 0.00 |
Maximum of Months | 3478.11 | 3287.43 | 2646.26 | 1844.96 | 1219.83 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 507.12 | 2634.73 | 744.09 | 345.16 | 398.93 | 0.00 | 0.00 |
February | 780.35 | 2284.93 | 854.21 | 399.39 | 454.81 | 0.00 | 0.00 |
March | 1440.82 | 1569.57 | 1259.05 | 608.40 | 650.65 | 0.00 | 0.00 |
April | 1897.67 | 1274.69 | 1416.41 | 648.14 | 768.27 | 0.00 | 0.00 |
May | 2185.79 | 784.08 | 1423.53 | 539.32 | 884.21 | 0.00 | 0.00 |
June | 2619.27 | 531.98 | 1497.03 | 575.90 | 921.13 | 0.00 | 0.00 |
July | 2550.61 | 394.38 | 1412.04 | 523.54 | 888.50 | 0.00 | 0.00 |
August | 2513.94 | 356.70 | 1383.60 | 517.41 | 866.19 | 0.00 | 0.00 |
September | 1778.10 | 667.10 | 1127.26 | 469.55 | 657.70 | 0.00 | 0.00 |
October | 1294.74 | 1419.83 | 1004.25 | 521.32 | 482.93 | 0.00 | 0.00 |
November | 787.67 | 1947.57 | 801.47 | 359.74 | 441.73 | 0.00 | 0.00 |
December | 464.03 | 2510.30 | 661.20 | 289.21 | 371.99 | 0.00 | 0.00 |
Annual Sum or Average | 1572.60 | 1359.93 | 1133.43 | 483.45 | 649.99 | 0.00 | 0.00 |
Minimum of Months | 464.03 | 356.70 | 661.20 | 289.21 | 371.99 | 0.00 | 0.00 |
Maximum of Months | 2619.27 | 2634.73 | 1497.03 | 648.14 | 921.13 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 67.62 | 3618.53 | 494.80 | 0.00 | 494.80 | 0.00 | 0.00 |
February | 226.63 | 2948.55 | 548.44 | 0.00 | 548.44 | 0.00 | 0.00 |
March | 505.89 | 1849.95 | 769.98 | 0.00 | 769.98 | 0.00 | 0.00 |
April | 1011.13 | 1463.35 | 931.36 | 4.13 | 927.23 | 0.00 | 0.00 |
May | 1554.53 | 941.58 | 1113.89 | 35.55 | 1078.34 | 0.00 | 0.00 |
June | 2259.93 | 593.62 | 1225.88 | 80.94 | 1144.95 | 0.00 | 0.00 |
July | 2273.74 | 424.86 | 1156.62 | 56.22 | 1100.40 | 0.00 | 0.00 |
August | 2082.17 | 349.03 | 1028.63 | 11.21 | 1017.42 | 0.00 | 0.00 |
September | 1172.59 | 797.91 | 777.54 | 0.11 | 777.43 | 0.00 | 0.00 |
October | 521.93 | 1678.93 | 591.19 | 0.00 | 591.19 | 0.00 | 0.00 |
November | 265.18 | 2317.87 | 529.10 | 0.00 | 529.10 | 0.00 | 0.00 |
December | 65.86 | 2940.57 | 457.41 | 0.00 | 457.41 | 0.00 | 0.00 |
Annual Sum or Average | 1005.02 | 1653.83 | 803.45 | 15.75 | 787.71 | 0.00 | 0.00 |
Minimum of Months | 65.86 | 349.03 | 457.41 | 0.00 | 457.41 | 0.00 | 0.00 |
Maximum of Months | 2273.74 | 3618.53 | 1225.88 | 80.94 | 1144.95 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 475.47 | 2161.23 | 724.42 | 326.75 | 397.67 | 0.00 | 0.00 |
February | 846.25 | 1775.69 | 913.27 | 490.69 | 422.58 | 0.00 | 0.00 |
March | 1254.53 | 1138.15 | 1149.00 | 523.06 | 625.94 | 0.00 | 0.00 |
April | 1882.06 | 921.40 | 1389.44 | 633.55 | 755.89 | 0.00 | 0.00 |
May | 2316.15 | 621.07 | 1525.70 | 645.20 | 880.51 | 0.00 | 0.00 |
June | 2769.83 | 397.90 | 1579.62 | 662.06 | 917.56 | 0.00 | 0.00 |
July | 2803.47 | 286.61 | 1540.19 | 647.52 | 892.67 | 0.00 | 0.00 |
August | 2613.71 | 234.14 | 1408.77 | 558.91 | 849.86 | 0.00 | 0.00 |
September | 1845.26 | 511.97 | 1157.81 | 513.00 | 644.82 | 0.00 | 0.00 |
October | 1240.08 | 1040.64 | 987.71 | 513.93 | 473.78 | 0.00 | 0.00 |
November | 751.69 | 1386.82 | 789.68 | 357.57 | 432.12 | 0.00 | 0.00 |
December | 483.00 | 1747.92 | 684.02 | 311.80 | 372.22 | 0.00 | 0.00 |
Annual Sum or Average | 1610.79 | 1014.75 | 1155.29 | 515.25 | 640.04 | 0.00 | 0.00 |
Minimum of Months | 475.47 | 234.14 | 684.02 | 311.80 | 372.22 | 0.00 | 0.00 |
Maximum of Months | 2803.47 | 2161.23 | 1579.62 | 662.06 | 917.56 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 2860.62 | 3100.38 | 2646.25 | 1844.96 | 801.29 | 0.00 | 0.00 |
February | 2936.62 | 2666.05 | 2469.84 | 1655.60 | 814.24 | 0.00 | 0.00 |
March | 2877.22 | 1867.14 | 2221.22 | 1157.57 | 1063.65 | 0.00 | 0.00 |
April | 2430.47 | 1544.21 | 1663.55 | 541.52 | 1122.03 | 0.00 | 0.00 |
May | 2107.09 | 1010.31 | 1344.08 | 156.22 | 1187.86 | 0.00 | 0.00 |
June | 2368.93 | 636.50 | 1242.74 | 69.15 | 1173.59 | 0.00 | 0.00 |
July | 2525.20 | 448.85 | 1256.39 | 93.68 | 1162.70 | 0.00 | 0.00 |
August | 3058.05 | 379.01 | 1500.04 | 280.21 | 1219.82 | 0.00 | 0.00 |
September | 2811.86 | 846.78 | 1649.67 | 613.59 | 1036.08 | 0.00 | 0.00 |
October | 3461.69 | 1699.09 | 2391.55 | 1549.25 | 842.30 | 0.00 | 0.00 |
November | 3305.13 | 2217.01 | 2572.88 | 1707.32 | 865.56 | 0.00 | 0.00 |
December | 3027.11 | 2638.48 | 2608.47 | 1835.08 | 773.39 | 0.00 | 0.00 |
Annual Sum or Average | 2814.09 | 1581.99 | 1961.72 | 955.43 | 1006.30 | 0.00 | 0.00 |
Minimum of Months | 2107.09 | 379.01 | 1242.74 | 69.15 | 773.39 | 0.00 | 0.00 |
Maximum of Months | 3461.69 | 3100.38 | 2646.25 | 1844.96 | 1219.82 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 550.57 | 2310.46 | 744.08 | 345.16 | 398.93 | 0.00 | 0.00 |
February | 840.82 | 1938.23 | 854.20 | 399.39 | 454.81 | 0.00 | 0.00 |
March | 1514.37 | 1291.14 | 1259.04 | 608.40 | 650.65 | 0.00 | 0.00 |
April | 1978.18 | 1060.91 | 1416.40 | 648.14 | 768.26 | 0.00 | 0.00 |
May | 2211.06 | 709.27 | 1423.53 | 539.32 | 884.21 | 0.00 | 0.00 |
June | 2651.11 | 469.23 | 1497.02 | 575.90 | 921.13 | 0.00 | 0.00 |
July | 2599.77 | 337.53 | 1412.04 | 523.54 | 888.50 | 0.00 | 0.00 |
August | 2573.06 | 291.95 | 1383.59 | 517.41 | 866.19 | 0.00 | 0.00 |
September | 1809.13 | 576.98 | 1127.25 | 469.55 | 657.70 | 0.00 | 0.00 |
October | 1348.30 | 1179.86 | 1004.25 | 521.31 | 482.93 | 0.00 | 0.00 |
November | 874.13 | 1574.55 | 801.46 | 359.74 | 441.72 | 0.00 | 0.00 |
December | 534.13 | 1947.33 | 661.20 | 289.21 | 371.99 | 0.00 | 0.00 |
Annual Sum or Average | 1627.91 | 1136.48 | 1133.43 | 483.44 | 649.98 | 0.00 | 0.00 |
Minimum of Months | 534.13 | 291.95 | 661.20 | 289.21 | 371.99 | 0.00 | 0.00 |
Maximum of Months | 2651.11 | 2310.46 | 1497.02 | 648.14 | 921.13 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 79.37 | 3447.92 | 494.80 | 0.00 | 494.80 | 0.00 | 0.00 |
February | 242.49 | 2808.86 | 548.44 | 0.00 | 548.44 | 0.00 | 0.00 |
March | 535.30 | 1723.39 | 769.98 | 0.00 | 769.98 | 0.00 | 0.00 |
April | 1031.14 | 1390.93 | 931.36 | 4.13 | 927.23 | 0.00 | 0.00 |
May | 1545.00 | 925.80 | 1113.89 | 35.55 | 1078.34 | 0.00 | 0.00 |
June | 2232.59 | 600.17 | 1225.88 | 80.94 | 1144.95 | 0.00 | 0.00 |
July | 2239.23 | 435.37 | 1156.62 | 56.22 | 1100.40 | 0.00 | 0.00 |
August | 2048.58 | 361.13 | 1028.63 | 11.21 | 1017.42 | 0.00 | 0.00 |
September | 1172.18 | 767.06 | 777.54 | 0.11 | 777.43 | 0.00 | 0.00 |
October | 551.02 | 1549.59 | 591.19 | 0.00 | 591.19 | 0.00 | 0.00 |
November | 309.26 | 2124.17 | 529.10 | 0.00 | 529.10 | 0.00 | 0.00 |
December | 79.71 | 2720.45 | 457.41 | 0.00 | 457.41 | 0.00 | 0.00 |
Annual Sum or Average | 1009.78 | 1564.91 | 803.45 | 15.75 | 787.71 | 0.00 | 0.00 |
Minimum of Months | 79.37 | 361.13 | 457.41 | 0.00 | 457.41 | 0.00 | 0.00 |
Maximum of Months | 2239.23 | 3447.92 | 1225.88 | 80.94 | 1144.95 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 496.91 | 2050.50 | 724.42 | 326.75 | 397.67 | 0.00 | 0.00 |
February | 867.77 | 1690.21 | 913.27 | 490.69 | 422.58 | 0.00 | 0.00 |
March | 1278.85 | 1072.19 | 1149.00 | 523.06 | 625.94 | 0.00 | 0.00 |
April | 1890.47 | 886.27 | 1389.44 | 633.55 | 755.89 | 0.00 | 0.00 |
May | 2304.24 | 616.66 | 1525.70 | 645.20 | 880.51 | 0.00 | 0.00 |
June | 2747.33 | 404.86 | 1579.62 | 662.06 | 917.56 | 0.00 | 0.00 |
July | 2777.75 | 294.07 | 1540.19 | 647.52 | 892.67 | 0.00 | 0.00 |
August | 2588.32 | 242.73 | 1408.77 | 558.91 | 849.86 | 0.00 | 0.00 |
September | 1840.04 | 498.30 | 1157.81 | 513.00 | 644.82 | 0.00 | 0.00 |
October | 1260.32 | 973.46 | 987.71 | 513.93 | 473.78 | 0.00 | 0.00 |
November | 794.61 | 1279.85 | 789.68 | 357.57 | 432.12 | 0.00 | 0.00 |
December | 508.76 | 1613.92 | 684.02 | 311.80 | 372.22 | 0.00 | 0.00 |
Annual Sum or Average | 1616.82 | 964.86 | 1155.29 | 515.25 | 640.04 | 0.00 | 0.00 |
Minimum of Months | 496.91 | 242.73 | 684.02 | 311.80 | 372.22 | 0.00 | 0.00 |
Maximum of Months | 2777.75 | 2050.50 | 1579.62 | 662.06 | 917.56 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 2917.58 | 2914.02 | 2646.25 | 1844.96 | 801.29 | 0.00 | 0.00 |
February | 2972.45 | 2521.39 | 2469.84 | 1655.60 | 814.24 | 0.00 | 0.00 |
March | 2906.52 | 1751.59 | 2221.22 | 1157.57 | 1063.65 | 0.00 | 0.00 |
April | 2445.33 | 1470.67 | 1663.55 | 541.52 | 1122.03 | 0.00 | 0.00 |
May | 2096.44 | 990.53 | 1344.08 | 156.22 | 1187.86 | 0.00 | 0.00 |
June | 2343.46 | 639.49 | 1242.74 | 69.15 | 1173.59 | 0.00 | 0.00 |
July | 2494.11 | 456.43 | 1256.39 | 93.68 | 1162.70 | 0.00 | 0.00 |
August | 3025.18 | 389.23 | 1500.04 | 280.21 | 1219.82 | 0.00 | 0.00 |
September | 2806.97 | 816.78 | 1649.67 | 613.59 | 1036.08 | 0.00 | 0.00 |
October | 3483.62 | 1586.40 | 2391.55 | 1549.25 | 842.30 | 0.00 | 0.00 |
November | 3363.98 | 2044.53 | 2572.88 | 1707.32 | 865.56 | 0.00 | 0.00 |
December | 3087.93 | 2427.41 | 2608.47 | 1835.08 | 773.39 | 0.00 | 0.00 |
Annual Sum or Average | 2828.42 | 1495.14 | 1961.72 | 955.43 | 1006.30 | 0.00 | 0.00 |
Minimum of Months | 2096.44 | 389.23 | 1242.74 | 69.15 | 773.39 | 0.00 | 0.00 |
Maximum of Months | 3483.62 | 2914.02 | 2646.25 | 1844.96 | 1219.82 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 564.74 | 2191.53 | 744.08 | 345.16 | 398.93 | 0.00 | 0.00 |
February | 849.03 | 1854.56 | 854.20 | 399.39 | 454.81 | 0.00 | 0.00 |
March | 1522.66 | 1221.09 | 1259.04 | 608.40 | 650.65 | 0.00 | 0.00 |
April | 1983.45 | 1016.83 | 1416.40 | 648.14 | 768.26 | 0.00 | 0.00 |
May | 2202.53 | 696.91 | 1423.53 | 539.32 | 884.21 | 0.00 | 0.00 |
June | 2631.47 | 469.93 | 1497.02 | 575.90 | 921.13 | 0.00 | 0.00 |
July | 2579.77 | 340.99 | 1412.04 | 523.54 | 888.50 | 0.00 | 0.00 |
August | 2552.40 | 296.63 | 1383.59 | 517.41 | 866.19 | 0.00 | 0.00 |
September | 1807.41 | 557.69 | 1127.25 | 469.55 | 657.70 | 0.00 | 0.00 |
October | 1357.79 | 1110.68 | 1004.25 | 521.31 | 482.93 | 0.00 | 0.00 |
November | 896.18 | 1470.74 | 801.46 | 359.74 | 441.72 | 0.00 | 0.00 |
December | 547.63 | 1817.71 | 661.20 | 289.21 | 371.99 | 0.00 | 0.00 |
Annual Sum or Average | 1628.72 | 1083.08 | 1133.43 | 483.44 | 649.98 | 0.00 | 0.00 |
Minimum of Months | 547.63 | 296.63 | 661.20 | 289.21 | 371.99 | 0.00 | 0.00 |
Maximum of Months | 2631.47 | 2191.53 | 1497.02 | 648.14 | 921.13 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.111138E+09 | 0.109928E+11 | 0.132528E+10 | 0.00 | 0.132528E+10 | 0.00 | 0.00 |
February | 0.417476E+09 | 0.816113E+10 | 0.132678E+10 | 0.00 | 0.132678E+10 | 0.00 | 0.00 |
March | 0.113641E+10 | 0.571714E+10 | 0.206231E+10 | 0.00 | 0.206231E+10 | 0.00 | 0.00 |
April | 0.243430E+10 | 0.422733E+10 | 0.241409E+10 | 10707180.89 | 0.240338E+10 | 0.00 | 0.00 |
May | 0.408384E+10 | 0.269457E+10 | 0.298345E+10 | 95215386.96 | 0.288824E+10 | 0.00 | 0.00 |
June | 0.579515E+10 | 0.159992E+10 | 0.317750E+10 | 0.209790E+09 | 0.296771E+10 | 0.00 | 0.00 |
July | 0.602971E+10 | 0.114574E+10 | 0.309791E+10 | 0.150592E+09 | 0.294732E+10 | 0.00 | 0.00 |
August | 0.550278E+10 | 0.916951E+09 | 0.275508E+10 | 30012309.02 | 0.272507E+10 | 0.00 | 0.00 |
September | 0.295135E+10 | 0.228528E+10 | 0.201540E+10 | 283712.48 | 0.201512E+10 | 0.00 | 0.00 |
October | 0.121645E+10 | 0.521138E+10 | 0.158346E+10 | 0.00 | 0.158346E+10 | 0.00 | 0.00 |
November | 0.465863E+09 | 0.704695E+10 | 0.137142E+10 | 0.00 | 0.137142E+10 | 0.00 | 0.00 |
December | 84927639.70 | 0.948456E+10 | 0.122512E+10 | 0.00 | 0.122512E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.302294E+11 | 0.594837E+11 | 0.253378E+11 | 0.496600E+09 | 0.248412E+11 | 0.00 | 0.00 |
Minimum of Months | 84927639.70 | 0.916951E+09 | 0.122512E+10 | 0.00 | 0.122512E+10 | 0.00 | 0.00 |
Maximum of Months | 0.602971E+10 | 0.109928E+11 | 0.317750E+10 | 0.209790E+09 | 0.296771E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.117067E+10 | 0.649948E+10 | 0.194030E+10 | 0.875174E+09 | 0.106513E+10 | 0.00 | 0.00 |
February | 0.196017E+10 | 0.478920E+10 | 0.220939E+10 | 0.118709E+10 | 0.102230E+10 | 0.00 | 0.00 |
March | 0.329641E+10 | 0.334053E+10 | 0.307749E+10 | 0.140096E+10 | 0.167653E+10 | 0.00 | 0.00 |
April | 0.487262E+10 | 0.250667E+10 | 0.360143E+10 | 0.164216E+10 | 0.195927E+10 | 0.00 | 0.00 |
May | 0.623607E+10 | 0.173121E+10 | 0.408646E+10 | 0.172811E+10 | 0.235836E+10 | 0.00 | 0.00 |
June | 0.722743E+10 | 0.101794E+10 | 0.409439E+10 | 0.171606E+10 | 0.237833E+10 | 0.00 | 0.00 |
July | 0.757524E+10 | 0.694522E+09 | 0.412527E+10 | 0.173432E+10 | 0.239094E+10 | 0.00 | 0.00 |
August | 0.707052E+10 | 0.505993E+09 | 0.377325E+10 | 0.149698E+10 | 0.227627E+10 | 0.00 | 0.00 |
September | 0.478177E+10 | 0.141898E+10 | 0.300106E+10 | 0.132969E+10 | 0.167137E+10 | 0.00 | 0.00 |
October | 0.326527E+10 | 0.308412E+10 | 0.264550E+10 | 0.137652E+10 | 0.126898E+10 | 0.00 | 0.00 |
November | 0.180414E+10 | 0.404933E+10 | 0.204687E+10 | 0.926816E+09 | 0.112006E+10 | 0.00 | 0.00 |
December | 0.117089E+10 | 0.542182E+10 | 0.183209E+10 | 0.835135E+09 | 0.996950E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.504312E+11 | 0.350598E+11 | 0.364335E+11 | 0.162490E+11 | 0.201845E+11 | 0.00 | 0.00 |
Minimum of Months | 0.117067E+10 | 0.505993E+09 | 0.183209E+10 | 0.835135E+09 | 0.996950E+09 | 0.00 | 0.00 |
Maximum of Months | 0.757524E+10 | 0.649948E+10 | 0.412527E+10 | 0.173432E+10 | 0.239094E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.762978E+10 | 0.880504E+10 | 0.708775E+10 | 0.494155E+10 | 0.214619E+10 | 0.00 | 0.00 |
February | 0.708772E+10 | 0.688390E+10 | 0.597506E+10 | 0.400524E+10 | 0.196981E+10 | 0.00 | 0.00 |
March | 0.772691E+10 | 0.530386E+10 | 0.594934E+10 | 0.310044E+10 | 0.284889E+10 | 0.00 | 0.00 |
April | 0.628670E+10 | 0.422348E+10 | 0.431193E+10 | 0.140362E+10 | 0.290830E+10 | 0.00 | 0.00 |
May | 0.563563E+10 | 0.282360E+10 | 0.359999E+10 | 0.418416E+09 | 0.318157E+10 | 0.00 | 0.00 |
June | 0.610258E+10 | 0.170441E+10 | 0.322120E+10 | 0.179247E+09 | 0.304195E+10 | 0.00 | 0.00 |
July | 0.672670E+10 | 0.120159E+10 | 0.336512E+10 | 0.250922E+09 | 0.311420E+10 | 0.00 | 0.00 |
August | 0.817248E+10 | 0.981249E+09 | 0.401771E+10 | 0.750523E+09 | 0.326719E+10 | 0.00 | 0.00 |
September | 0.730799E+10 | 0.229564E+10 | 0.427596E+10 | 0.159044E+10 | 0.268553E+10 | 0.00 | 0.00 |
October | 0.931578E+10 | 0.481072E+10 | 0.640556E+10 | 0.414953E+10 | 0.225603E+10 | 0.00 | 0.00 |
November | 0.855332E+10 | 0.611502E+10 | 0.666893E+10 | 0.442539E+10 | 0.224354E+10 | 0.00 | 0.00 |
December | 0.804733E+10 | 0.771829E+10 | 0.698656E+10 | 0.491510E+10 | 0.207146E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.885929E+11 | 0.528668E+11 | 0.618651E+11 | 0.301304E+11 | 0.317347E+11 | 0.00 | 0.00 |
Minimum of Months | 0.563563E+10 | 0.981249E+09 | 0.322120E+10 | 0.179247E+09 | 0.196981E+10 | 0.00 | 0.00 |
Maximum of Months | 0.931578E+10 | 0.880504E+10 | 0.708775E+10 | 0.494155E+10 | 0.326719E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.135827E+10 | 0.705686E+10 | 0.199296E+10 | 0.924475E+09 | 0.106849E+10 | 0.00 | 0.00 |
February | 0.188782E+10 | 0.552770E+10 | 0.206649E+10 | 0.966211E+09 | 0.110028E+10 | 0.00 | 0.00 |
March | 0.385910E+10 | 0.420394E+10 | 0.337224E+10 | 0.162954E+10 | 0.174270E+10 | 0.00 | 0.00 |
April | 0.491877E+10 | 0.330400E+10 | 0.367133E+10 | 0.167999E+10 | 0.199134E+10 | 0.00 | 0.00 |
May | 0.585443E+10 | 0.210007E+10 | 0.381279E+10 | 0.144452E+10 | 0.236827E+10 | 0.00 | 0.00 |
June | 0.678914E+10 | 0.137888E+10 | 0.388030E+10 | 0.149273E+10 | 0.238757E+10 | 0.00 | 0.00 |
July | 0.683155E+10 | 0.105630E+10 | 0.378201E+10 | 0.140224E+10 | 0.237977E+10 | 0.00 | 0.00 |
August | 0.673333E+10 | 0.955386E+09 | 0.370583E+10 | 0.138584E+10 | 0.232000E+10 | 0.00 | 0.00 |
September | 0.460885E+10 | 0.172912E+10 | 0.292185E+10 | 0.121708E+10 | 0.170477E+10 | 0.00 | 0.00 |
October | 0.346782E+10 | 0.380288E+10 | 0.268979E+10 | 0.139629E+10 | 0.129349E+10 | 0.00 | 0.00 |
November | 0.204163E+10 | 0.504811E+10 | 0.207740E+10 | 0.932443E+09 | 0.114495E+10 | 0.00 | 0.00 |
December | 0.124286E+10 | 0.672359E+10 | 0.177097E+10 | 0.774623E+09 | 0.996344E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.495936E+11 | 0.428868E+11 | 0.357440E+11 | 0.152460E+11 | 0.204980E+11 | 0.00 | 0.00 |
Minimum of Months | 0.124286E+10 | 0.955386E+09 | 0.177097E+10 | 0.774623E+09 | 0.996344E+09 | 0.00 | 0.00 |
Maximum of Months | 0.683155E+10 | 0.705686E+10 | 0.388030E+10 | 0.167999E+10 | 0.238757E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.181104E+09 | 0.969187E+10 | 0.132527E+10 | 0.00 | 0.132527E+10 | 0.00 | 0.00 |
February | 0.548263E+09 | 0.713312E+10 | 0.132678E+10 | 0.00 | 0.132678E+10 | 0.00 | 0.00 |
March | 0.135498E+10 | 0.495491E+10 | 0.206230E+10 | 0.00 | 0.206230E+10 | 0.00 | 0.00 |
April | 0.262085E+10 | 0.379300E+10 | 0.241408E+10 | 10707142.87 | 0.240337E+10 | 0.00 | 0.00 |
May | 0.416365E+10 | 0.252193E+10 | 0.298344E+10 | 95215048.85 | 0.288822E+10 | 0.00 | 0.00 |
June | 0.585773E+10 | 0.153865E+10 | 0.317749E+10 | 0.209789E+09 | 0.296770E+10 | 0.00 | 0.00 |
July | 0.608999E+10 | 0.113796E+10 | 0.309790E+10 | 0.150591E+09 | 0.294731E+10 | 0.00 | 0.00 |
August | 0.557687E+10 | 0.934833E+09 | 0.275507E+10 | 30012202.44 | 0.272506E+10 | 0.00 | 0.00 |
September | 0.303936E+10 | 0.206818E+10 | 0.201540E+10 | 283711.47 | 0.201511E+10 | 0.00 | 0.00 |
October | 0.139793E+10 | 0.449683E+10 | 0.158345E+10 | 0.00 | 0.158345E+10 | 0.00 | 0.00 |
November | 0.687335E+09 | 0.600792E+10 | 0.137142E+10 | 0.00 | 0.137142E+10 | 0.00 | 0.00 |
December | 0.176393E+09 | 0.787604E+10 | 0.122512E+10 | 0.00 | 0.122512E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.316945E+11 | 0.521552E+11 | 0.253377E+11 | 0.496599E+09 | 0.248411E+11 | 0.00 | 0.00 |
Minimum of Months | 0.176393E+09 | 0.934833E+09 | 0.122512E+10 | 0.00 | 0.122512E+10 | 0.00 | 0.00 |
Maximum of Months | 0.608999E+10 | 0.969187E+10 | 0.317749E+10 | 0.209789E+09 | 0.296770E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.127350E+10 | 0.578864E+10 | 0.194029E+10 | 0.875171E+09 | 0.106512E+10 | 0.00 | 0.00 |
February | 0.204724E+10 | 0.429575E+10 | 0.220938E+10 | 0.118708E+10 | 0.102230E+10 | 0.00 | 0.00 |
March | 0.336012E+10 | 0.304843E+10 | 0.307748E+10 | 0.140096E+10 | 0.167652E+10 | 0.00 | 0.00 |
April | 0.487829E+10 | 0.238827E+10 | 0.360142E+10 | 0.164215E+10 | 0.195927E+10 | 0.00 | 0.00 |
May | 0.620357E+10 | 0.166347E+10 | 0.408645E+10 | 0.172810E+10 | 0.235835E+10 | 0.00 | 0.00 |
June | 0.717939E+10 | 0.103134E+10 | 0.409437E+10 | 0.171605E+10 | 0.237832E+10 | 0.00 | 0.00 |
July | 0.750882E+10 | 0.767652E+09 | 0.412525E+10 | 0.173431E+10 | 0.239094E+10 | 0.00 | 0.00 |
August | 0.700055E+10 | 0.627127E+09 | 0.377324E+10 | 0.149698E+10 | 0.227626E+10 | 0.00 | 0.00 |
September | 0.478292E+10 | 0.132704E+10 | 0.300105E+10 | 0.132969E+10 | 0.167136E+10 | 0.00 | 0.00 |
October | 0.332144E+10 | 0.278725E+10 | 0.264549E+10 | 0.137651E+10 | 0.126898E+10 | 0.00 | 0.00 |
November | 0.194838E+10 | 0.359463E+10 | 0.204686E+10 | 0.926812E+09 | 0.112005E+10 | 0.00 | 0.00 |
December | 0.129367E+10 | 0.468163E+10 | 0.183208E+10 | 0.835132E+09 | 0.996946E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.507979E+11 | 0.320012E+11 | 0.364334E+11 | 0.162490E+11 | 0.201844E+11 | 0.00 | 0.00 |
Minimum of Months | 0.127350E+10 | 0.627127E+09 | 0.183208E+10 | 0.835132E+09 | 0.996946E+09 | 0.00 | 0.00 |
Maximum of Months | 0.750882E+10 | 0.578864E+10 | 0.412525E+10 | 0.173431E+10 | 0.239094E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.766188E+10 | 0.830407E+10 | 0.708772E+10 | 0.494154E+10 | 0.214619E+10 | 0.00 | 0.00 |
February | 0.710428E+10 | 0.644972E+10 | 0.597503E+10 | 0.400523E+10 | 0.196980E+10 | 0.00 | 0.00 |
March | 0.770635E+10 | 0.500094E+10 | 0.594932E+10 | 0.310043E+10 | 0.284888E+10 | 0.00 | 0.00 |
April | 0.629977E+10 | 0.400259E+10 | 0.431191E+10 | 0.140362E+10 | 0.290829E+10 | 0.00 | 0.00 |
May | 0.564362E+10 | 0.270602E+10 | 0.359998E+10 | 0.418415E+09 | 0.318156E+10 | 0.00 | 0.00 |
June | 0.614026E+10 | 0.164980E+10 | 0.322118E+10 | 0.179246E+09 | 0.304194E+10 | 0.00 | 0.00 |
July | 0.676351E+10 | 0.120220E+10 | 0.336511E+10 | 0.250922E+09 | 0.311418E+10 | 0.00 | 0.00 |
August | 0.819068E+10 | 0.101515E+10 | 0.401770E+10 | 0.750520E+09 | 0.326718E+10 | 0.00 | 0.00 |
September | 0.728834E+10 | 0.219485E+10 | 0.427595E+10 | 0.159043E+10 | 0.268552E+10 | 0.00 | 0.00 |
October | 0.927179E+10 | 0.455084E+10 | 0.640554E+10 | 0.414951E+10 | 0.225602E+10 | 0.00 | 0.00 |
November | 0.856688E+10 | 0.574650E+10 | 0.666890E+10 | 0.442537E+10 | 0.224353E+10 | 0.00 | 0.00 |
December | 0.810780E+10 | 0.706689E+10 | 0.698653E+10 | 0.491508E+10 | 0.207145E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.887452E+11 | 0.498896E+11 | 0.618649E+11 | 0.301303E+11 | 0.317346E+11 | 0.00 | 0.00 |
Minimum of Months | 0.564362E+10 | 0.101515E+10 | 0.322118E+10 | 0.179246E+09 | 0.196980E+10 | 0.00 | 0.00 |
Maximum of Months | 0.927179E+10 | 0.830407E+10 | 0.708772E+10 | 0.494154E+10 | 0.326718E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.147464E+10 | 0.618834E+10 | 0.199295E+10 | 0.924471E+09 | 0.106848E+10 | 0.00 | 0.00 |
February | 0.203411E+10 | 0.468896E+10 | 0.206649E+10 | 0.966207E+09 | 0.110028E+10 | 0.00 | 0.00 |
March | 0.405608E+10 | 0.345818E+10 | 0.337222E+10 | 0.162954E+10 | 0.174269E+10 | 0.00 | 0.00 |
April | 0.512744E+10 | 0.274987E+10 | 0.367131E+10 | 0.167998E+10 | 0.199134E+10 | 0.00 | 0.00 |
May | 0.592211E+10 | 0.189972E+10 | 0.381277E+10 | 0.144451E+10 | 0.236826E+10 | 0.00 | 0.00 |
June | 0.687168E+10 | 0.121624E+10 | 0.388029E+10 | 0.149273E+10 | 0.238756E+10 | 0.00 | 0.00 |
July | 0.696323E+10 | 0.904038E+09 | 0.378200E+10 | 0.140224E+10 | 0.237976E+10 | 0.00 | 0.00 |
August | 0.689167E+10 | 0.781965E+09 | 0.370582E+10 | 0.138583E+10 | 0.231999E+10 | 0.00 | 0.00 |
September | 0.468926E+10 | 0.149554E+10 | 0.292184E+10 | 0.121707E+10 | 0.170476E+10 | 0.00 | 0.00 |
October | 0.361130E+10 | 0.316013E+10 | 0.268978E+10 | 0.139629E+10 | 0.129349E+10 | 0.00 | 0.00 |
November | 0.226575E+10 | 0.408124E+10 | 0.207739E+10 | 0.932439E+09 | 0.114495E+10 | 0.00 | 0.00 |
December | 0.143061E+10 | 0.521573E+10 | 0.177096E+10 | 0.774620E+09 | 0.996339E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.513379E+11 | 0.358400E+11 | 0.357438E+11 | 0.152459E+11 | 0.204979E+11 | 0.00 | 0.00 |
Minimum of Months | 0.143061E+10 | 0.781965E+09 | 0.177096E+10 | 0.774620E+09 | 0.996339E+09 | 0.00 | 0.00 |
Maximum of Months | 0.696323E+10 | 0.618834E+10 | 0.388029E+10 | 0.167998E+10 | 0.238756E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.212577E+09 | 0.923491E+10 | 0.132527E+10 | 0.00 | 0.132527E+10 | 0.00 | 0.00 |
February | 0.586628E+09 | 0.679518E+10 | 0.132678E+10 | 0.00 | 0.132678E+10 | 0.00 | 0.00 |
March | 0.143374E+10 | 0.461593E+10 | 0.206230E+10 | 0.00 | 0.206230E+10 | 0.00 | 0.00 |
April | 0.267271E+10 | 0.360530E+10 | 0.241408E+10 | 10707142.87 | 0.240337E+10 | 0.00 | 0.00 |
May | 0.413813E+10 | 0.247965E+10 | 0.298344E+10 | 95215048.85 | 0.288822E+10 | 0.00 | 0.00 |
June | 0.578688E+10 | 0.155563E+10 | 0.317749E+10 | 0.209789E+09 | 0.296770E+10 | 0.00 | 0.00 |
July | 0.599755E+10 | 0.116610E+10 | 0.309790E+10 | 0.150591E+09 | 0.294731E+10 | 0.00 | 0.00 |
August | 0.548693E+10 | 0.967249E+09 | 0.275507E+10 | 30012202.44 | 0.272506E+10 | 0.00 | 0.00 |
September | 0.303828E+10 | 0.198822E+10 | 0.201540E+10 | 283711.47 | 0.201511E+10 | 0.00 | 0.00 |
October | 0.147586E+10 | 0.415041E+10 | 0.158345E+10 | 0.00 | 0.158345E+10 | 0.00 | 0.00 |
November | 0.801605E+09 | 0.550586E+10 | 0.137142E+10 | 0.00 | 0.137142E+10 | 0.00 | 0.00 |
December | 0.213499E+09 | 0.728646E+10 | 0.122512E+10 | 0.00 | 0.122512E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.318444E+11 | 0.493509E+11 | 0.253377E+11 | 0.496599E+09 | 0.248411E+11 | 0.00 | 0.00 |
Minimum of Months | 0.212577E+09 | 0.967249E+09 | 0.122512E+10 | 0.00 | 0.122512E+10 | 0.00 | 0.00 |
Maximum of Months | 0.599755E+10 | 0.923491E+10 | 0.317749E+10 | 0.209789E+09 | 0.296770E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.133093E+10 | 0.549205E+10 | 0.194029E+10 | 0.875171E+09 | 0.106512E+10 | 0.00 | 0.00 |
February | 0.209931E+10 | 0.408894E+10 | 0.220938E+10 | 0.118708E+10 | 0.102230E+10 | 0.00 | 0.00 |
March | 0.342528E+10 | 0.287175E+10 | 0.307748E+10 | 0.140096E+10 | 0.167652E+10 | 0.00 | 0.00 |
April | 0.490009E+10 | 0.229721E+10 | 0.360142E+10 | 0.164215E+10 | 0.195927E+10 | 0.00 | 0.00 |
May | 0.617167E+10 | 0.165166E+10 | 0.408645E+10 | 0.172810E+10 | 0.235835E+10 | 0.00 | 0.00 |
June | 0.712107E+10 | 0.104940E+10 | 0.409437E+10 | 0.171605E+10 | 0.237832E+10 | 0.00 | 0.00 |
July | 0.743994E+10 | 0.787632E+09 | 0.412525E+10 | 0.173431E+10 | 0.239094E+10 | 0.00 | 0.00 |
August | 0.693257E+10 | 0.650135E+09 | 0.377324E+10 | 0.149698E+10 | 0.227626E+10 | 0.00 | 0.00 |
September | 0.476939E+10 | 0.129159E+10 | 0.300105E+10 | 0.132969E+10 | 0.167136E+10 | 0.00 | 0.00 |
October | 0.337563E+10 | 0.260731E+10 | 0.264549E+10 | 0.137651E+10 | 0.126898E+10 | 0.00 | 0.00 |
November | 0.205963E+10 | 0.331736E+10 | 0.204686E+10 | 0.926812E+09 | 0.112005E+10 | 0.00 | 0.00 |
December | 0.136265E+10 | 0.432272E+10 | 0.183208E+10 | 0.835132E+09 | 0.996946E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.509882E+11 | 0.304278E+11 | 0.364334E+11 | 0.162490E+11 | 0.201844E+11 | 0.00 | 0.00 |
Minimum of Months | 0.133093E+10 | 0.650135E+09 | 0.183208E+10 | 0.835132E+09 | 0.996946E+09 | 0.00 | 0.00 |
Maximum of Months | 0.743994E+10 | 0.549205E+10 | 0.412525E+10 | 0.173431E+10 | 0.239094E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.781444E+10 | 0.780490E+10 | 0.708772E+10 | 0.494154E+10 | 0.214619E+10 | 0.00 | 0.00 |
February | 0.719095E+10 | 0.609976E+10 | 0.597503E+10 | 0.400523E+10 | 0.196980E+10 | 0.00 | 0.00 |
March | 0.778481E+10 | 0.469147E+10 | 0.594932E+10 | 0.310043E+10 | 0.284888E+10 | 0.00 | 0.00 |
April | 0.633830E+10 | 0.381196E+10 | 0.431191E+10 | 0.140362E+10 | 0.290829E+10 | 0.00 | 0.00 |
May | 0.561510E+10 | 0.265305E+10 | 0.359998E+10 | 0.418415E+09 | 0.318156E+10 | 0.00 | 0.00 |
June | 0.607425E+10 | 0.165756E+10 | 0.322118E+10 | 0.179246E+09 | 0.304194E+10 | 0.00 | 0.00 |
July | 0.668023E+10 | 0.122250E+10 | 0.336511E+10 | 0.250922E+09 | 0.311418E+10 | 0.00 | 0.00 |
August | 0.810263E+10 | 0.104252E+10 | 0.401770E+10 | 0.750520E+09 | 0.326718E+10 | 0.00 | 0.00 |
September | 0.727566E+10 | 0.211709E+10 | 0.427595E+10 | 0.159043E+10 | 0.268552E+10 | 0.00 | 0.00 |
October | 0.933052E+10 | 0.424902E+10 | 0.640554E+10 | 0.414951E+10 | 0.225602E+10 | 0.00 | 0.00 |
November | 0.871944E+10 | 0.529942E+10 | 0.666890E+10 | 0.442537E+10 | 0.224353E+10 | 0.00 | 0.00 |
December | 0.827071E+10 | 0.650157E+10 | 0.698653E+10 | 0.491508E+10 | 0.207145E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.891971E+11 | 0.471508E+11 | 0.618649E+11 | 0.301303E+11 | 0.317346E+11 | 0.00 | 0.00 |
Minimum of Months | 0.561510E+10 | 0.104252E+10 | 0.322118E+10 | 0.179246E+09 | 0.196980E+10 | 0.00 | 0.00 |
Maximum of Months | 0.933052E+10 | 0.780490E+10 | 0.708772E+10 | 0.494154E+10 | 0.326718E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.151259E+10 | 0.586978E+10 | 0.199295E+10 | 0.924471E+09 | 0.106848E+10 | 0.00 | 0.00 |
February | 0.205398E+10 | 0.448654E+10 | 0.206649E+10 | 0.966207E+09 | 0.110028E+10 | 0.00 | 0.00 |
March | 0.407831E+10 | 0.327057E+10 | 0.337222E+10 | 0.162954E+10 | 0.174269E+10 | 0.00 | 0.00 |
April | 0.514110E+10 | 0.263563E+10 | 0.367131E+10 | 0.167998E+10 | 0.199134E+10 | 0.00 | 0.00 |
May | 0.589926E+10 | 0.186661E+10 | 0.381277E+10 | 0.144451E+10 | 0.236826E+10 | 0.00 | 0.00 |
June | 0.682077E+10 | 0.121805E+10 | 0.388029E+10 | 0.149273E+10 | 0.238756E+10 | 0.00 | 0.00 |
July | 0.690967E+10 | 0.913304E+09 | 0.378200E+10 | 0.140224E+10 | 0.237976E+10 | 0.00 | 0.00 |
August | 0.683635E+10 | 0.794507E+09 | 0.370582E+10 | 0.138583E+10 | 0.231999E+10 | 0.00 | 0.00 |
September | 0.468481E+10 | 0.144554E+10 | 0.292184E+10 | 0.121707E+10 | 0.170476E+10 | 0.00 | 0.00 |
October | 0.363670E+10 | 0.297486E+10 | 0.268978E+10 | 0.139629E+10 | 0.129349E+10 | 0.00 | 0.00 |
November | 0.232290E+10 | 0.381215E+10 | 0.207739E+10 | 0.932439E+09 | 0.114495E+10 | 0.00 | 0.00 |
December | 0.146676E+10 | 0.486854E+10 | 0.177096E+10 | 0.774620E+09 | 0.996339E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.513632E+11 | 0.341561E+11 | 0.357438E+11 | 0.152459E+11 | 0.204979E+11 | 0.00 | 0.00 |
Minimum of Months | 0.146676E+10 | 0.794507E+09 | 0.177096E+10 | 0.774620E+09 | 0.996339E+09 | 0.00 | 0.00 |
Maximum of Months | 0.690967E+10 | 0.586978E+10 | 0.388029E+10 | 0.167998E+10 | 0.238756E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 3.96 | 1.39 | -3.0 | 4.56 | -7.8 | 48.74 | 150.20 | 0.00 |
February | 7.94 | 4.18 | -1.3 | 5.19 | -4.0 | 51.84 | 169.20 | 0.00 |
March | 13.76 | 8.97 | 3.80 | 4.89 | 2.25 | 76.95 | 193.22 | 0.00 |
April | 17.21 | 12.54 | 8.82 | 3.95 | 6.45 | 95.37 | 211.82 | 0.00 |
May | 20.84 | 16.44 | 13.69 | 3.50 | 11.46 | 117.34 | 200.00 | 0.00 |
June | 24.80 | 19.35 | 16.45 | 3.85 | 15.08 | 121.81 | 213.08 | 0.00 |
July | 26.06 | 21.68 | 19.85 | 3.24 | 17.64 | 119.92 | 194.46 | 0.00 |
August | 26.55 | 22.42 | 20.72 | 3.39 | 18.21 | 115.12 | 179.15 | 0.00 |
September | 22.53 | 18.74 | 16.82 | 3.06 | 13.44 | 83.74 | 156.58 | 0.02 |
October | 16.03 | 13.02 | 10.77 | 4.05 | 5.85 | 53.01 | 190.38 | 0.00 |
November | 11.94 | 8.22 | 4.17 | 4.16 | 0.30 | 52.20 | 150.38 | 0.00 |
December | 7.70 | 4.64 | 0.26 | 4.69 | -4.1 | 44.81 | 142.03 | 0.00 |
Annual Sum or Average | 16.65 | 12.68 | 9.31 | 4.04 | 6.29 | 81.91 | 179.25 | 0.00 |
Minimum of Months | 3.96 | 1.39 | -3.0 | 3.06 | -7.8 | 44.81 | 142.03 | 0.00 |
Maximum of Months | 26.55 | 22.42 | 20.72 | 5.19 | 18.21 | 121.81 | 213.08 | 0.02 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 21.10 | 31-JAN-14:00 | 12.97 | 6.70 | 5.70 | 12.22 | 200.50 | 90.50 |
February | 25.00 | 26-FEB-14:00 | 12.75 | 1.70 | 4.10 | 8.15 | 91.50 | 816.00 |
March | 27.80 | 30-MAR-13:00 | 17.87 | 12.20 | 5.70 | 16.30 | 231.50 | 710.50 |
April | 28.90 | 17-APR-14:20 | 16.56 | 8.13 | 2.03 | 13.35 | 125.83 | 887.67 |
May | 30.60 | 19-MAY-13:00 | 18.49 | 11.70 | 4.60 | 15.76 | 140.00 | 875.50 |
June | 34.40 | 06-JUN-14:00 | 22.39 | 17.20 | 8.20 | 22.13 | 251.00 | 561.00 |
July | 36.70 | 08-JUL-14:00 | 23.91 | 18.90 | 2.10 | 24.66 | 274.00 | 567.00 |
August | 35.00 | 01-AUG-14:00 | 23.84 | 19.40 | 2.60 | 26.15 | 306.00 | 508.00 |
September | 31.70 | 07-SEP-15:09 | 23.05 | 19.60 | 4.02 | 22.55 | 218.67 | 591.33 |
October | 30.00 | 10-OCT-15:00 | 20.56 | 16.10 | 3.60 | 17.57 | 97.00 | 561.00 |
November | 24.40 | 05-NOV-15:00 | 17.95 | 14.40 | 2.10 | 14.10 | 117.50 | 361.50 |
December | 22.80 | 12-DEC-14:20 | 16.78 | 13.33 | 5.20 | 13.35 | 144.17 | 433.83 |
Annual Sum or Average | ||||||||
Minimum of Months | 21.10 | 12.75 | 1.70 | 2.03 | 8.15 | 91.50 | 90.50 | |
Maximum of Months | 36.70 | 23.91 | 19.60 | 8.20 | 26.15 | 306.00 | 887.67 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -6.7 | 14-JAN-06:10 | -7.8 | -10.6 | 4.95 | -24.7 | 0.00 | 0.00 |
February | -12.8 | 12-FEB-06:00 | -13.8 | -18.3 | 7.20 | -30.1 | 0.00 | 0.00 |
March | 1.10 | 19-MAR-06:00 | -1.5 | -6.1 | 0.00 | -16.2 | 17.00 | 290.50 |
April | 0.00 | 06-APR-04:00 | -1.1 | -2.8 | 3.10 | -16.5 | 0.00 | 0.00 |
May | 7.80 | 11-MAY-05:00 | 5.45 | 2.80 | 4.10 | -7.8 | 21.50 | 204.50 |
June | 11.10 | 10-JUN-04:00 | 8.73 | 6.70 | 0.00 | -2.5 | 0.00 | 0.00 |
July | 17.20 | 28-JUL-22:00 | 16.88 | 16.70 | 4.10 | 14.28 | 0.00 | 0.00 |
August | 18.30 | 25-AUG-05:00 | 17.20 | 16.70 | 3.60 | 5.13 | 0.00 | 0.00 |
September | 11.70 | 29-SEP-03:00 | 11.07 | 10.60 | 2.60 | -2.3 | 0.00 | 0.00 |
October | 2.20 | 26-OCT-04:00 | 1.95 | 1.70 | 3.10 | -13.4 | 0.00 | 0.00 |
November | -3.3 | 22-NOV-05:00 | -4.0 | -5.6 | 5.20 | -20.2 | 0.00 | 0.00 |
December | -5.6 | 18-DEC-07:00 | -7.3 | -11.7 | 2.60 | -22.7 | 17.00 | 320.50 |
Annual Sum or Average | ||||||||
Minimum of Months | -12.8 | -13.8 | -18.3 | 0.00 | -30.1 | 0.00 | 0.00 | |
Maximum of Months | 18.30 | 17.20 | 16.70 | 7.20 | 14.28 | 21.50 | 320.50 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 16.51 | 19-JAN-21:00 | 18.30 | 15.60 | 8.80 | 15.21 | 0.00 | 0.00 |
February | 15.81 | 18-FEB-15:00 | 17.20 | 15.00 | 5.20 | 13.91 | 73.00 | 1.00 |
March | 18.16 | 30-MAR-12:30 | 25.85 | 13.85 | 5.45 | 15.39 | 323.00 | 600.00 |
April | 20.01 | 04-APR-13:00 | 25.00 | 17.80 | 9.30 | 18.64 | 307.00 | 197.50 |
May | 22.34 | 30-MAY-17:00 | 27.80 | 20.00 | 4.10 | 21.96 | 97.50 | 79.50 |
June | 24.32 | 23-JUN-11:39 | 31.13 | 21.87 | 4.83 | 22.98 | 338.17 | 565.17 |
July | 25.06 | 07-JUL-11:00 | 33.30 | 22.20 | 3.60 | 20.75 | 116.50 | 900.00 |
August | 25.13 | 19-AUG-16:00 | 30.00 | 23.30 | 3.10 | 23.66 | 197.00 | 136.50 |
September | 24.10 | 09-SEP-10:00 | 30.60 | 21.70 | 2.60 | 21.27 | 236.00 | 482.00 |
October | 23.20 | 18-OCT-15:00 | 25.60 | 22.20 | 5.70 | 23.82 | 159.00 | 2.00 |
November | 18.88 | 19-NOV-14:00 | 24.40 | 16.10 | 8.20 | 13.91 | 143.00 | 384.50 |
December | 17.57 | 13-DEC-10:00 | 19.40 | 16.70 | 4.60 | 14.47 | 227.50 | 77.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 15.81 | 17.20 | 13.85 | 2.60 | 13.91 | 0.00 | 0.00 | |
Maximum of Months | 25.13 | 33.30 | 23.30 | 9.30 | 23.82 | 338.17 | 900.00 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 15.60 | 19-JAN-17:00 | 17.20 | 16.13 | 6.70 | 14.10 | 0.00 | 0.00 |
February | 15.00 | 18-FEB-16:19 | 17.20 | 15.81 | 5.53 | 13.91 | 50.33 | 1.00 |
March | 16.10 | 31-MAR-10:00 | 21.70 | 18.06 | 13.90 | 18.64 | 268.00 | 8.00 |
April | 17.80 | 04-APR-09:20 | 20.77 | 18.74 | 7.53 | 16.79 | 242.00 | 111.50 |
May | 20.60 | 30-MAY-19:00 | 25.00 | 21.79 | 2.60 | 12.41 | 0.00 | 0.00 |
June | 22.80 | 18-JUN-16:00 | 28.30 | 24.23 | 0.00 | 24.66 | 140.50 | 115.50 |
July | 23.30 | 26-JUL-09:00 | 26.10 | 24.10 | 3.60 | 24.66 | 338.00 | 251.50 |
August | 23.90 | 08-AUG-19:00 | 26.10 | 24.51 | 1.50 | 24.83 | 0.00 | 0.00 |
September | 23.30 | 16-SEP-16:00 | 25.60 | 23.89 | 2.10 | 22.13 | 108.00 | 57.50 |
October | 22.20 | 18-OCT-14:00 | 25.00 | 23.04 | 4.60 | 23.32 | 234.50 | 2.00 |
November | 17.20 | 04-NOV-13:00 | 17.80 | 17.48 | 3.60 | 15.02 | 276.50 | 2.50 |
December | 16.70 | 13-DEC-16:19 | 17.03 | 16.82 | 2.93 | 14.10 | 54.00 | 4.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 15.00 | 17.03 | 15.81 | 0.00 | 12.41 | 0.00 | 0.00 | |
Maximum of Months | 23.90 | 28.30 | 24.51 | 13.90 | 24.83 | 338.00 | 251.50 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 13.74 | 22.89 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 13.65 | 27.55 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 15.17 | 38.46 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 17.98 | 47.59 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 21.32 | 52.44 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 24.28 | 55.84 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 26.07 | 52.33 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 26.20 | 48.31 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 24.63 | 36.35 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 21.78 | 31.91 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 18.45 | 24.33 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 15.51 | 20.76 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 19.94 | 38.29 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 13.65 | 20.76 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 26.20 | 55.84 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.370227E+11 | -0.359921E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.103064E+10 | 58.98 | 0.00 | 0.00 |
February | 0.337056E+11 | -0.327761E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -929533593.6 | 58.98 | 0.00 | 0.00 |
March | 0.382785E+11 | -0.372504E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.102811E+10 | 58.97 | 0.00 | 0.00 |
April | 0.326110E+11 | -0.316189E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -992028196.4 | 58.97 | 0.00 | 0.00 |
May | 0.320793E+11 | -0.310544E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.102485E+10 | 58.98 | 0.00 | 0.00 |
June | 0.293159E+11 | -0.283256E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -990282606.4 | 58.97 | 0.00 | 0.00 |
July | 0.265558E+11 | -0.255378E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.101792E+10 | 58.98 | 0.00 | 0.00 |
August | 0.288958E+11 | -0.278741E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.102174E+10 | 58.97 | 0.00 | 0.00 |
September | 0.275016E+11 | -0.265154E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -986138382.1 | 58.98 | 0.00 | 0.00 |
October | 0.306267E+11 | -0.296087E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.101801E+10 | 58.97 | 0.00 | 0.00 |
November | 0.326200E+11 | -0.316343E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -985696876.1 | 58.98 | 0.00 | 0.00 |
December | 0.347711E+11 | -0.337498E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.102124E+10 | 58.97 | 0.00 | 0.00 |
Annual Sum or Average | 0.383984E+12 | -0.371938E+12 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.120462E+11 | 58.98 | 0.00 | 0.00 |
Minimum of Months | 0.265558E+11 | -0.372504E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -0.103064E+10 | 58.97 | 0.00 | 0.00 |
Maximum of Months | 0.382785E+11 | -0.255378E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -929533593.6 | 58.98 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_1_DAYLCTRL
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 290.67 | 0.51 | 0.48 | 01-JAN-09:20 | 5945.68 | 33.92 | 269.33 | 272.00 | 1631.30 | 26.38 | 200.33 | 250.33 |
February | 263.00 | 0.52 | 0.48 | 01-FEB-13:39 | 6968.32 | 33.91 | 233.50 | 247.50 | 1127.71 | 21.84 | 122.33 | 216.00 |
March | 351.67 | 0.52 | 0.48 | 01-MAR-08:50 | 1662.73 | 19.82 | 69.50 | 318.67 | 956.01 | 21.10 | 175.33 | 283.17 |
April | 369.33 | 0.53 | 0.48 | 01-APR-09:39 | 1383.80 | 19.41 | 41.00 | 325.50 | 781.56 | 20.73 | 172.67 | 281.17 |
May | 407.00 | 0.52 | 0.48 | 01-MAY-07:49 | 1260.26 | 19.56 | 21.67 | 360.33 | 698.97 | 20.90 | 218.50 | 312.50 |
June | 411.67 | 0.53 | 0.48 | 01-JUN-07:19 | 1175.02 | 19.29 | 7.83 | 361.33 | 658.94 | 20.65 | 201.00 | 313.33 |
July | 411.00 | 0.53 | 0.48 | 01-JUL-07:40 | 1236.36 | 19.46 | 24.17 | 364.67 | 684.23 | 20.79 | 227.83 | 314.67 |
August | 390.50 | 0.52 | 0.48 | 01-AUG-07:30 | 1501.65 | 20.09 | 77.33 | 350.67 | 812.40 | 21.41 | 266.00 | 312.50 |
September | 298.50 | 0.52 | 0.48 | 01-SEP-07:40 | 1595.76 | 20.20 | 72.17 | 308.83 | 882.31 | 21.28 | 179.00 | 268.83 |
October | 293.50 | 0.51 | 0.48 | 01-OCT-10:39 | 2842.85 | 25.09 | 143.17 | 292.67 | 1050.25 | 20.43 | 118.50 | 254.50 |
November | 299.00 | 0.52 | 0.48 | 01-NOV-08:30 | 5857.41 | 34.78 | 286.83 | 273.33 | 1154.52 | 23.39 | 181.33 | 248.17 |
December | 285.17 | 0.50 | 0.48 | 01-DEC-07:00 | 5601.77 | 34.66 | 273.00 | 267.83 | 1571.12 | 27.30 | 215.83 | 245.00 |
Annual Sum or Average | 4071.00 | 0.52 | 2802.11 | 24.16 | 1519.50 | 3743.33 | 961.60 | 21.99 | 2278.67 | 3300.17 | ||
Minimum of Months | 263.00 | 0.50 | 0.48 | 1175.02 | 19.29 | 7.83 | 247.50 | 658.94 | 20.43 | 118.50 | 216.00 | |
Maximum of Months | 411.67 | 0.53 | 0.48 | 6968.32 | 34.78 | 286.83 | 364.67 | 1631.30 | 27.30 | 266.00 | 314.67 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_2_DAYLCTRL
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 290.67 | 0.54 | 0.48 | 01-JAN-09:09 | 1428.07 | 21.44 | 82.83 | 245.17 | 721.12 | 21.53 | 102.17 | 187.00 |
February | 263.00 | 0.54 | 0.48 | 01-FEB-13:39 | 1952.98 | 22.73 | 75.67 | 229.50 | 1033.08 | 22.66 | 87.00 | 181.83 |
March | 351.67 | 0.52 | 0.48 | 01-MAR-08:39 | 2276.78 | 22.84 | 106.83 | 313.50 | 889.88 | 21.91 | 130.33 | 271.50 |
April | 369.33 | 0.52 | 0.48 | 01-APR-08:09 | 2195.61 | 22.44 | 97.17 | 327.50 | 1173.15 | 22.94 | 133.83 | 291.83 |
May | 407.00 | 0.51 | 0.48 | 01-MAY-07:10 | 2509.43 | 23.37 | 118.83 | 369.17 | 1037.43 | 22.67 | 152.50 | 332.33 |
June | 411.67 | 0.52 | 0.48 | 01-JUN-06:30 | 2541.88 | 23.46 | 123.67 | 371.00 | 1053.65 | 22.78 | 160.50 | 335.83 |
July | 411.00 | 0.52 | 0.48 | 01-JUL-05:00 | 2510.50 | 23.30 | 115.17 | 374.83 | 1060.48 | 22.75 | 169.83 | 334.67 |
August | 390.50 | 0.52 | 0.48 | 01-AUG-06:40 | 2299.73 | 23.15 | 104.17 | 352.33 | 1201.99 | 23.61 | 189.67 | 316.83 |
September | 298.50 | 0.53 | 0.48 | 01-SEP-07:10 | 2161.52 | 23.06 | 80.50 | 306.50 | 1131.33 | 23.38 | 121.50 | 262.50 |
October | 293.50 | 0.53 | 0.48 | 01-OCT-08:20 | 2539.48 | 23.97 | 101.67 | 271.17 | 956.15 | 22.48 | 101.00 | 221.33 |
November | 299.00 | 0.54 | 0.48 | 01-NOV-08:20 | 1728.05 | 23.33 | 103.00 | 249.67 | 924.21 | 23.37 | 115.67 | 205.67 |
December | 285.17 | 0.54 | 0.48 | 01-DEC-07:49 | 1492.52 | 22.86 | 86.83 | 241.50 | 775.41 | 22.82 | 112.50 | 183.67 |
Annual Sum or Average | 4071.00 | 0.53 | 2179.01 | 23.02 | 1196.33 | 3651.83 | 1008.24 | 22.75 | 1576.50 | 3125.00 | ||
Minimum of Months | 263.00 | 0.51 | 0.48 | 1428.07 | 21.44 | 75.67 | 229.50 | 721.12 | 21.53 | 87.00 | 181.83 | |
Maximum of Months | 411.67 | 0.54 | 0.48 | 2541.88 | 23.97 | 123.67 | 374.83 | 1201.99 | 23.61 | 189.67 | 335.83 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_3_DAYLCTRL
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 290.67 | 0.58 | 0.48 | 01-JAN-11:20 | 523.81 | 16.13 | 0.00 | 218.00 | 314.73 | 17.67 | 0.00 | 105.33 |
February | 263.00 | 0.58 | 0.48 | 01-FEB-13:50 | 558.57 | 16.30 | 0.00 | 198.17 | 345.32 | 17.80 | 0.00 | 123.33 |
March | 351.67 | 0.53 | 0.48 | 01-MAR-09:30 | 710.75 | 18.00 | 0.00 | 303.67 | 431.04 | 19.38 | 2.67 | 232.50 |
April | 369.33 | 0.52 | 0.48 | 01-APR-10:30 | 847.07 | 18.83 | 0.00 | 330.83 | 504.84 | 20.12 | 50.50 | 275.00 |
May | 407.00 | 0.50 | 0.48 | 01-MAY-07:40 | 1052.86 | 21.68 | 62.33 | 383.33 | 612.77 | 22.83 | 214.50 | 352.33 |
June | 411.67 | 0.50 | 0.48 | 01-JUN-06:00 | 1143.00 | 22.35 | 118.50 | 386.83 | 657.20 | 22.48 | 243.33 | 358.33 |
July | 411.00 | 0.51 | 0.48 | 01-JUL-06:19 | 1150.78 | 21.82 | 105.33 | 385.83 | 639.76 | 22.17 | 245.67 | 350.17 |
August | 390.50 | 0.51 | 0.48 | 01-AUG-07:10 | 1030.15 | 19.76 | 4.50 | 360.33 | 595.91 | 21.03 | 185.17 | 325.50 |
September | 298.50 | 0.53 | 0.48 | 01-SEP-07:49 | 787.85 | 18.64 | 0.00 | 303.83 | 473.72 | 19.93 | 27.83 | 224.67 |
October | 293.50 | 0.57 | 0.48 | 01-OCT-10:50 | 586.85 | 16.80 | 0.00 | 243.33 | 373.46 | 18.33 | 2.17 | 159.67 |
November | 299.00 | 0.58 | 0.48 | 01-NOV-09:00 | 542.20 | 16.41 | 0.00 | 229.33 | 327.41 | 17.90 | 0.00 | 134.50 |
December | 285.17 | 0.58 | 0.48 | 01-DEC-09:00 | 506.06 | 16.23 | 0.00 | 210.33 | 304.60 | 17.80 | 0.00 | 96.67 |
Annual Sum or Average | 4071.00 | 0.54 | 822.92 | 18.91 | 290.67 | 3553.83 | 484.33 | 20.07 | 971.83 | 2738.00 | ||
Minimum of Months | 263.00 | 0.50 | 0.48 | 506.06 | 16.13 | 0.00 | 198.17 | 304.60 | 17.67 | 0.00 | 96.67 | |
Maximum of Months | 411.67 | 0.58 | 0.48 | 1150.78 | 22.35 | 118.50 | 386.83 | 657.20 | 22.83 | 245.67 | 358.33 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_4_DAYLCTRL
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 290.67 | 0.54 | 0.48 | 01-JAN-10:00 | 1747.51 | 23.34 | 95.33 | 247.33 | 960.00 | 23.36 | 120.00 | 197.67 |
February | 263.00 | 0.55 | 0.48 | 01-FEB-13:39 | 1698.07 | 22.27 | 78.17 | 220.33 | 885.42 | 22.34 | 106.17 | 172.67 |
March | 351.67 | 0.52 | 0.48 | 01-MAR-11:39 | 2256.06 | 23.30 | 102.50 | 312.50 | 1188.61 | 23.52 | 150.50 | 271.33 |
April | 369.33 | 0.52 | 0.48 | 01-APR-10:39 | 2406.23 | 21.38 | 80.50 | 333.67 | 1314.25 | 21.99 | 124.33 | 293.33 |
May | 407.00 | 0.52 | 0.48 | 01-MAY-08:30 | 2419.02 | 20.10 | 52.83 | 366.67 | 1021.26 | 20.36 | 126.00 | 329.17 |
June | 411.67 | 0.52 | 0.48 | 01-JUN-07:49 | 2532.90 | 18.22 | 1.83 | 369.67 | 1079.37 | 20.30 | 130.83 | 334.50 |
July | 411.00 | 0.52 | 0.48 | 01-JUL-07:00 | 2514.56 | 20.04 | 55.00 | 370.00 | 1056.82 | 20.33 | 141.00 | 332.17 |
August | 390.50 | 0.51 | 0.48 | 01-AUG-07:00 | 2476.32 | 22.12 | 89.67 | 355.17 | 1069.77 | 20.96 | 170.00 | 321.67 |
September | 298.50 | 0.52 | 0.48 | 01-SEP-08:50 | 2216.99 | 23.78 | 92.67 | 307.50 | 1158.75 | 23.93 | 145.17 | 260.83 |
October | 293.50 | 0.54 | 0.48 | 01-OCT-10:39 | 2386.01 | 23.30 | 97.67 | 268.17 | 909.02 | 21.86 | 106.50 | 217.67 |
November | 299.00 | 0.54 | 0.48 | 01-NOV-09:00 | 1662.31 | 23.22 | 98.83 | 253.50 | 863.34 | 23.27 | 120.83 | 205.83 |
December | 285.17 | 0.54 | 0.48 | 01-DEC-09:00 | 1449.00 | 22.78 | 93.33 | 242.00 | 762.00 | 22.86 | 111.50 | 184.33 |
Annual Sum or Average | 4071.00 | 0.53 | 2195.20 | 21.78 | 938.33 | 3646.50 | 1035.50 | 21.93 | 1552.83 | 3121.17 | ||
Minimum of Months | 263.00 | 0.51 | 0.48 | 1449.00 | 18.22 | 1.83 | 220.33 | 762.00 | 20.30 | 106.17 | 172.67 | |
Maximum of Months | 411.67 | 0.55 | 0.48 | 2532.90 | 23.78 | 102.50 | 370.00 | 1314.25 | 23.93 | 170.00 | 334.50 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_1_DAYLCTRL
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 290.67 | 0.51 | 0.48 | 01-JAN-09:20 | 5987.89 | 33.13 | 257.50 | 272.00 | 1719.11 | 22.52 | 103.00 | 252.17 |
February | 263.00 | 0.52 | 0.48 | 01-FEB-13:39 | 7010.71 | 33.23 | 228.67 | 247.50 | 1212.66 | 17.00 | 25.83 | 217.83 |
March | 351.67 | 0.52 | 0.48 | 01-MAR-08:50 | 1699.03 | 13.35 | 6.67 | 319.67 | 1026.04 | 16.70 | 0.00 | 287.33 |
April | 369.33 | 0.52 | 0.48 | 01-APR-08:30 | 1409.68 | 13.23 | 0.00 | 326.67 | 835.75 | 16.71 | 0.00 | 288.33 |
May | 407.00 | 0.52 | 0.48 | 01-MAY-07:49 | 1279.31 | 13.56 | 0.00 | 360.67 | 744.61 | 16.99 | 0.00 | 317.83 |
June | 411.67 | 0.52 | 0.48 | 01-JUN-07:10 | 1192.90 | 13.40 | 0.00 | 361.67 | 701.67 | 16.82 | 0.00 | 320.17 |
July | 411.00 | 0.52 | 0.48 | 01-JUL-07:30 | 1254.18 | 13.57 | 0.00 | 365.67 | 728.44 | 16.96 | 0.00 | 319.50 |
August | 390.50 | 0.52 | 0.48 | 01-AUG-07:30 | 1522.25 | 14.14 | 0.00 | 351.17 | 865.05 | 17.53 | 0.00 | 316.50 |
September | 298.50 | 0.52 | 0.48 | 01-SEP-07:40 | 1623.15 | 14.21 | 6.50 | 309.17 | 943.12 | 17.30 | 0.00 | 274.17 |
October | 293.50 | 0.51 | 0.48 | 01-OCT-10:39 | 2895.94 | 20.63 | 117.00 | 292.83 | 1137.87 | 15.80 | 2.00 | 258.17 |
November | 299.00 | 0.51 | 0.48 | 01-NOV-08:30 | 5898.26 | 34.28 | 282.83 | 273.50 | 1263.72 | 20.89 | 81.67 | 255.00 |
December | 285.17 | 0.50 | 0.48 | 01-DEC-07:00 | 5641.57 | 34.04 | 265.33 | 268.33 | 1658.94 | 23.60 | 115.67 | 248.33 |
Annual Sum or Average | 4071.00 | 0.52 | 2832.46 | 19.73 | 1164.50 | 3748.83 | 1027.67 | 18.05 | 328.17 | 3355.33 | ||
Minimum of Months | 263.00 | 0.50 | 0.48 | 1192.90 | 13.23 | 0.00 | 247.50 | 701.67 | 15.80 | 0.00 | 217.83 | |
Maximum of Months | 411.67 | 0.52 | 0.48 | 7010.71 | 34.28 | 282.83 | 365.67 | 1719.11 | 23.60 | 115.67 | 320.17 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_2_DAYLCTRL
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 290.67 | 0.54 | 0.48 | 01-JAN-09:09 | 1455.35 | 18.53 | 71.50 | 247.67 | 756.42 | 19.31 | 45.83 | 195.50 |
February | 263.00 | 0.54 | 0.48 | 01-FEB-13:39 | 1991.77 | 19.81 | 71.17 | 230.67 | 1079.35 | 20.39 | 48.33 | 187.17 |
March | 351.67 | 0.52 | 0.48 | 01-MAR-08:39 | 2319.43 | 19.95 | 105.50 | 314.67 | 938.39 | 19.33 | 47.33 | 276.33 |
April | 369.33 | 0.52 | 0.48 | 01-APR-08:09 | 2233.24 | 19.24 | 92.83 | 328.50 | 1227.99 | 20.42 | 67.00 | 297.67 |
May | 407.00 | 0.51 | 0.48 | 01-MAY-07:10 | 2530.78 | 19.65 | 108.33 | 369.33 | 1095.76 | 19.96 | 57.50 | 335.83 |
June | 411.67 | 0.51 | 0.48 | 01-JUN-06:30 | 2576.60 | 20.44 | 122.67 | 371.50 | 1111.72 | 20.14 | 64.00 | 339.33 |
July | 411.00 | 0.52 | 0.48 | 01-JUL-05:00 | 2534.57 | 19.58 | 105.00 | 375.17 | 1118.95 | 20.07 | 58.33 | 337.33 |
August | 390.50 | 0.51 | 0.48 | 01-AUG-06:40 | 2327.33 | 20.07 | 103.33 | 353.00 | 1257.67 | 21.20 | 73.33 | 321.50 |
September | 298.50 | 0.52 | 0.48 | 01-SEP-07:10 | 2205.84 | 19.97 | 78.83 | 307.83 | 1185.43 | 20.99 | 55.83 | 268.17 |
October | 293.50 | 0.53 | 0.48 | 01-OCT-08:09 | 2561.91 | 20.29 | 90.50 | 272.67 | 1006.41 | 20.07 | 50.00 | 229.00 |
November | 299.00 | 0.54 | 0.48 | 01-NOV-08:20 | 1755.94 | 20.64 | 97.00 | 251.17 | 961.50 | 21.41 | 71.33 | 212.00 |
December | 285.17 | 0.53 | 0.48 | 01-DEC-07:49 | 1490.99 | 19.14 | 73.00 | 242.67 | 811.28 | 20.79 | 57.17 | 190.33 |
Annual Sum or Average | 4071.00 | 0.52 | 2208.10 | 19.79 | 1119.67 | 3664.83 | 1058.70 | 20.33 | 696.00 | 3190.17 | ||
Minimum of Months | 263.00 | 0.51 | 0.48 | 1455.35 | 18.53 | 71.17 | 230.67 | 756.42 | 19.31 | 45.83 | 187.17 | |
Maximum of Months | 411.67 | 0.54 | 0.48 | 2576.60 | 20.64 | 122.67 | 375.17 | 1257.67 | 21.41 | 73.33 | 339.33 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_3_DAYLCTRL
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 290.67 | 0.57 | 0.48 | 01-JAN-11:09 | 532.34 | 10.01 | 0.00 | 220.17 | 335.04 | 13.66 | 0.00 | 128.00 |
February | 263.00 | 0.58 | 0.48 | 01-FEB-13:39 | 568.96 | 10.34 | 0.00 | 199.83 | 368.09 | 13.95 | 0.00 | 136.00 |
March | 351.67 | 0.53 | 0.48 | 01-MAR-09:20 | 724.10 | 12.41 | 0.00 | 304.67 | 459.44 | 15.91 | 0.00 | 243.50 |
April | 369.33 | 0.52 | 0.48 | 01-APR-10:09 | 863.58 | 13.25 | 0.00 | 331.33 | 538.28 | 16.73 | 0.00 | 284.33 |
May | 407.00 | 0.50 | 0.48 | 01-MAY-07:40 | 1072.07 | 16.73 | 51.67 | 383.83 | 652.38 | 19.86 | 52.50 | 356.33 |
June | 411.67 | 0.50 | 0.48 | 01-JUN-06:49 | 1164.00 | 17.56 | 66.50 | 387.33 | 708.28 | 20.63 | 68.17 | 366.67 |
July | 411.00 | 0.51 | 0.48 | 01-JUL-06:10 | 1170.72 | 16.88 | 53.00 | 386.17 | 685.71 | 19.98 | 53.83 | 357.00 |
August | 390.50 | 0.51 | 0.48 | 01-AUG-06:00 | 1048.02 | 14.22 | 0.00 | 360.50 | 634.35 | 17.64 | 0.00 | 331.67 |
September | 298.50 | 0.53 | 0.48 | 01-SEP-07:49 | 802.39 | 13.32 | 0.00 | 304.83 | 504.80 | 16.74 | 0.00 | 239.00 |
October | 293.50 | 0.56 | 0.48 | 01-OCT-10:39 | 599.08 | 11.12 | 0.00 | 246.50 | 398.51 | 14.77 | 0.00 | 175.33 |
November | 299.00 | 0.57 | 0.48 | 01-NOV-09:00 | 550.83 | 10.46 | 0.00 | 231.00 | 348.50 | 14.04 | 0.00 | 150.33 |
December | 285.17 | 0.58 | 0.48 | 01-DEC-09:50 | 513.57 | 10.05 | 0.00 | 211.83 | 324.09 | 13.75 | 0.00 | 117.33 |
Annual Sum or Average | 4071.00 | 0.53 | 837.73 | 13.42 | 171.17 | 3568.00 | 517.19 | 16.84 | 174.50 | 2885.50 | ||
Minimum of Months | 263.00 | 0.50 | 0.48 | 513.57 | 10.01 | 0.00 | 199.83 | 324.09 | 13.66 | 0.00 | 117.33 | |
Maximum of Months | 411.67 | 0.58 | 0.48 | 1170.72 | 17.56 | 66.50 | 387.33 | 708.28 | 20.63 | 68.17 | 366.67 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_4_DAYLCTRL
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 290.67 | 0.53 | 0.48 | 01-JAN-10:00 | 1776.27 | 20.67 | 89.17 | 248.33 | 997.74 | 21.39 | 67.17 | 204.67 |
February | 263.00 | 0.55 | 0.48 | 01-FEB-13:39 | 1711.20 | 18.31 | 63.83 | 221.50 | 929.96 | 20.01 | 46.83 | 178.67 |
March | 351.67 | 0.52 | 0.48 | 01-MAR-09:30 | 2303.69 | 20.28 | 98.00 | 313.83 | 1241.81 | 21.17 | 72.33 | 277.00 |
April | 369.33 | 0.52 | 0.48 | 01-APR-10:20 | 2444.01 | 17.93 | 78.33 | 334.17 | 1369.62 | 19.26 | 51.17 | 297.17 |
May | 407.00 | 0.51 | 0.48 | 01-MAY-08:20 | 2445.92 | 16.17 | 50.50 | 368.83 | 1076.47 | 17.07 | 0.00 | 333.67 |
June | 411.67 | 0.52 | 0.48 | 01-JUN-07:49 | 2564.48 | 13.69 | 1.67 | 370.50 | 1134.55 | 17.02 | 0.00 | 338.83 |
July | 411.00 | 0.52 | 0.48 | 01-JUL-07:49 | 2540.49 | 16.18 | 51.67 | 370.83 | 1111.20 | 17.07 | 0.00 | 336.00 |
August | 390.50 | 0.51 | 0.48 | 01-AUG-07:49 | 2495.75 | 18.81 | 89.00 | 356.67 | 1125.51 | 17.82 | 7.67 | 325.00 |
September | 298.50 | 0.52 | 0.48 | 01-SEP-08:39 | 2262.12 | 20.88 | 90.83 | 308.00 | 1212.84 | 21.59 | 62.67 | 266.67 |
October | 293.50 | 0.53 | 0.48 | 01-OCT-10:39 | 2428.80 | 20.49 | 93.17 | 270.00 | 957.80 | 19.31 | 42.50 | 224.83 |
November | 299.00 | 0.54 | 0.48 | 01-NOV-09:50 | 1691.70 | 20.58 | 96.00 | 254.17 | 900.94 | 21.25 | 67.50 | 211.83 |
December | 285.17 | 0.53 | 0.48 | 01-DEC-09:39 | 1474.95 | 20.11 | 85.17 | 243.17 | 796.84 | 20.87 | 59.33 | 193.17 |
Annual Sum or Average | 4071.00 | 0.52 | 2226.38 | 18.40 | 887.33 | 3660.00 | 1085.31 | 19.26 | 477.17 | 3187.50 | ||
Minimum of Months | 263.00 | 0.51 | 0.48 | 1474.95 | 13.69 | 1.67 | 221.50 | 796.84 | 17.02 | 0.00 | 178.67 | |
Maximum of Months | 411.67 | 0.55 | 0.48 | 2564.48 | 20.88 | 98.00 | 370.83 | 1369.62 | 21.59 | 72.33 | 338.83 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_1_DAYLCTRL
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 290.67 | 0.51 | 0.48 | 01-JAN-09:20 | 5989.36 | 33.12 | 257.33 | 272.00 | 1720.73 | 22.51 | 103.00 | 252.50 |
February | 263.00 | 0.52 | 0.48 | 01-FEB-13:39 | 7012.56 | 33.22 | 228.67 | 247.50 | 1214.13 | 16.99 | 25.83 | 217.83 |
March | 351.67 | 0.52 | 0.48 | 01-MAR-08:50 | 1701.35 | 13.32 | 6.67 | 319.83 | 1027.50 | 16.68 | 0.00 | 287.33 |
April | 369.33 | 0.52 | 0.48 | 01-APR-08:30 | 1411.70 | 13.20 | 0.00 | 326.83 | 836.97 | 16.69 | 0.00 | 288.50 |
May | 407.00 | 0.52 | 0.48 | 01-MAY-07:49 | 1281.16 | 13.53 | 0.00 | 360.67 | 745.74 | 16.98 | 0.00 | 317.83 |
June | 411.67 | 0.52 | 0.48 | 01-JUN-07:10 | 1194.55 | 13.37 | 0.00 | 362.00 | 702.71 | 16.81 | 0.00 | 320.33 |
July | 411.00 | 0.52 | 0.48 | 01-JUL-07:30 | 1255.97 | 13.54 | 0.00 | 365.83 | 729.54 | 16.95 | 0.00 | 319.83 |
August | 390.50 | 0.52 | 0.48 | 01-AUG-07:30 | 1524.56 | 14.11 | 0.00 | 351.17 | 866.44 | 17.52 | 0.00 | 316.50 |
September | 298.50 | 0.52 | 0.48 | 01-SEP-07:40 | 1625.51 | 14.18 | 6.50 | 309.17 | 944.57 | 17.28 | 0.00 | 274.67 |
October | 293.50 | 0.51 | 0.48 | 01-OCT-10:39 | 2897.95 | 20.60 | 117.00 | 292.83 | 1139.24 | 15.78 | 2.00 | 258.17 |
November | 299.00 | 0.51 | 0.48 | 01-NOV-08:30 | 5900.01 | 34.27 | 282.83 | 273.50 | 1265.37 | 20.88 | 81.67 | 255.17 |
December | 285.17 | 0.50 | 0.48 | 01-DEC-07:00 | 5642.89 | 34.03 | 265.17 | 268.50 | 1660.58 | 23.59 | 115.67 | 248.50 |
Annual Sum or Average | 4071.00 | 0.52 | 2834.36 | 19.71 | 1164.17 | 3749.83 | 1029.02 | 18.04 | 328.17 | 3357.17 | ||
Minimum of Months | 263.00 | 0.50 | 0.48 | 1194.55 | 13.20 | 0.00 | 247.50 | 702.71 | 15.78 | 0.00 | 217.83 | |
Maximum of Months | 411.67 | 0.52 | 0.48 | 7012.56 | 34.27 | 282.83 | 365.83 | 1720.73 | 23.59 | 115.67 | 320.33 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_2_DAYLCTRL
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 290.67 | 0.54 | 0.48 | 01-JAN-09:09 | 1456.26 | 18.50 | 71.50 | 247.67 | 757.24 | 19.30 | 45.83 | 195.67 |
February | 263.00 | 0.54 | 0.48 | 01-FEB-13:39 | 1992.59 | 19.79 | 71.17 | 231.17 | 1080.11 | 20.38 | 48.33 | 187.17 |
March | 351.67 | 0.52 | 0.48 | 01-MAR-08:39 | 2320.71 | 19.93 | 105.50 | 314.83 | 939.45 | 19.31 | 47.33 | 276.83 |
April | 369.33 | 0.52 | 0.48 | 01-APR-08:09 | 2234.75 | 19.22 | 92.83 | 328.67 | 1229.16 | 20.41 | 67.00 | 297.67 |
May | 407.00 | 0.51 | 0.48 | 01-MAY-07:10 | 2532.51 | 19.62 | 108.33 | 369.33 | 1097.10 | 19.95 | 57.50 | 335.83 |
June | 411.67 | 0.51 | 0.48 | 01-JUN-06:30 | 2578.34 | 20.42 | 122.67 | 371.50 | 1113.06 | 20.13 | 64.00 | 339.33 |
July | 411.00 | 0.52 | 0.48 | 01-JUL-05:00 | 2536.35 | 19.56 | 104.83 | 375.17 | 1120.36 | 20.06 | 58.33 | 337.83 |
August | 390.50 | 0.51 | 0.48 | 01-AUG-06:40 | 2329.22 | 20.04 | 103.33 | 353.00 | 1259.13 | 21.18 | 73.33 | 321.67 |
September | 298.50 | 0.52 | 0.48 | 01-SEP-07:10 | 2207.17 | 19.94 | 78.83 | 307.83 | 1186.61 | 20.98 | 55.83 | 268.33 |
October | 293.50 | 0.53 | 0.48 | 01-OCT-08:09 | 2562.82 | 20.26 | 90.50 | 272.67 | 1007.27 | 20.06 | 50.00 | 229.17 |
November | 299.00 | 0.54 | 0.48 | 01-NOV-08:20 | 1756.85 | 20.62 | 97.00 | 251.17 | 962.36 | 21.40 | 71.33 | 212.33 |
December | 285.17 | 0.53 | 0.48 | 01-DEC-07:49 | 1491.81 | 19.11 | 73.00 | 242.83 | 812.05 | 20.78 | 57.17 | 190.67 |
Annual Sum or Average | 4071.00 | 0.52 | 2209.46 | 19.76 | 1119.50 | 3665.83 | 1059.83 | 20.31 | 696.00 | 3192.50 | ||
Minimum of Months | 263.00 | 0.51 | 0.48 | 1456.26 | 18.50 | 71.17 | 231.17 | 757.24 | 19.30 | 45.83 | 187.17 | |
Maximum of Months | 411.67 | 0.54 | 0.48 | 2578.34 | 20.62 | 122.67 | 375.17 | 1259.13 | 21.40 | 73.33 | 339.33 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_3_DAYLCTRL
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 290.67 | 0.57 | 0.48 | 01-JAN-11:09 | 532.87 | 9.98 | 0.00 | 220.17 | 335.48 | 13.64 | 0.00 | 128.33 |
February | 263.00 | 0.58 | 0.48 | 01-FEB-13:39 | 569.47 | 10.31 | 0.00 | 200.17 | 368.54 | 13.93 | 0.00 | 136.17 |
March | 351.67 | 0.53 | 0.48 | 01-MAR-09:20 | 724.80 | 12.38 | 0.00 | 304.83 | 460.02 | 15.90 | 0.00 | 243.50 |
April | 369.33 | 0.52 | 0.48 | 01-APR-10:09 | 864.50 | 13.22 | 0.00 | 331.33 | 538.99 | 16.72 | 0.00 | 284.33 |
May | 407.00 | 0.50 | 0.48 | 01-MAY-07:40 | 1073.32 | 16.70 | 51.67 | 384.00 | 653.29 | 19.84 | 52.50 | 356.67 |
June | 411.67 | 0.50 | 0.48 | 01-JUN-06:49 | 1165.36 | 17.53 | 66.50 | 387.33 | 709.26 | 20.61 | 68.17 | 366.83 |
July | 411.00 | 0.51 | 0.48 | 01-JUL-06:10 | 1172.05 | 16.85 | 53.00 | 386.17 | 686.68 | 19.97 | 53.83 | 357.00 |
August | 390.50 | 0.51 | 0.48 | 01-AUG-06:00 | 1049.22 | 14.19 | 0.00 | 360.50 | 635.25 | 17.63 | 0.00 | 331.83 |
September | 298.50 | 0.53 | 0.48 | 01-SEP-07:49 | 803.16 | 13.29 | 0.00 | 304.83 | 505.45 | 16.72 | 0.00 | 239.17 |
October | 293.50 | 0.56 | 0.48 | 01-OCT-10:39 | 599.54 | 11.08 | 0.00 | 246.50 | 398.96 | 14.76 | 0.00 | 176.00 |
November | 299.00 | 0.57 | 0.48 | 01-NOV-09:00 | 551.34 | 10.43 | 0.00 | 231.17 | 348.95 | 14.02 | 0.00 | 150.50 |
December | 285.17 | 0.58 | 0.48 | 01-DEC-09:50 | 514.06 | 10.02 | 0.00 | 211.83 | 324.51 | 13.73 | 0.00 | 117.83 |
Annual Sum or Average | 4071.00 | 0.53 | 838.61 | 13.39 | 171.17 | 3568.83 | 517.88 | 16.82 | 174.50 | 2888.17 | ||
Minimum of Months | 263.00 | 0.50 | 0.48 | 514.06 | 9.98 | 0.00 | 200.17 | 324.51 | 13.64 | 0.00 | 117.83 | |
Maximum of Months | 411.67 | 0.58 | 0.48 | 1172.05 | 17.53 | 66.50 | 387.33 | 709.26 | 20.61 | 68.17 | 366.83 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_4_DAYLCTRL
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 290.67 | 0.53 | 0.48 | 01-JAN-10:50 | 1777.18 | 20.65 | 89.00 | 248.33 | 998.56 | 21.37 | 67.17 | 204.83 |
February | 263.00 | 0.55 | 0.48 | 01-FEB-13:39 | 1712.19 | 18.28 | 63.83 | 221.50 | 930.87 | 19.99 | 46.83 | 178.83 |
March | 351.67 | 0.52 | 0.48 | 01-MAR-09:30 | 2304.92 | 20.25 | 98.00 | 313.83 | 1242.93 | 21.16 | 72.33 | 277.67 |
April | 369.33 | 0.52 | 0.48 | 01-APR-10:20 | 2445.54 | 17.90 | 78.33 | 334.17 | 1370.84 | 19.25 | 51.17 | 297.33 |
May | 407.00 | 0.51 | 0.48 | 01-MAY-08:20 | 2437.54 | 16.14 | 50.50 | 368.00 | 1077.82 | 17.06 | 0.00 | 333.83 |
June | 411.67 | 0.52 | 0.48 | 01-JUN-07:40 | 2566.24 | 13.65 | 1.67 | 370.50 | 1135.91 | 17.00 | 0.00 | 339.00 |
July | 411.00 | 0.52 | 0.48 | 01-JUL-07:49 | 2542.31 | 16.15 | 51.67 | 371.00 | 1112.59 | 17.06 | 0.00 | 336.00 |
August | 390.50 | 0.51 | 0.48 | 01-AUG-07:49 | 2497.72 | 18.78 | 89.00 | 356.67 | 1127.02 | 17.81 | 7.67 | 325.00 |
September | 298.50 | 0.52 | 0.48 | 01-SEP-08:39 | 2263.73 | 20.86 | 90.83 | 308.00 | 1214.15 | 21.58 | 62.67 | 266.83 |
October | 293.50 | 0.53 | 0.48 | 01-OCT-10:39 | 2429.77 | 20.46 | 93.17 | 270.00 | 958.71 | 19.30 | 42.50 | 225.00 |
November | 299.00 | 0.54 | 0.48 | 01-NOV-09:50 | 1692.64 | 20.56 | 96.00 | 254.17 | 901.81 | 21.24 | 67.50 | 211.83 |
December | 285.17 | 0.53 | 0.48 | 01-DEC-09:39 | 1475.78 | 20.08 | 85.17 | 243.17 | 797.62 | 20.86 | 59.33 | 193.67 |
Annual Sum or Average | 4071.00 | 0.52 | 2226.78 | 18.38 | 887.17 | 3659.33 | 1086.47 | 19.24 | 477.17 | 3189.83 | ||
Minimum of Months | 263.00 | 0.51 | 0.48 | 1475.78 | 13.65 | 1.67 | 221.50 | 797.62 | 17.00 | 0.00 | 178.83 | |
Maximum of Months | 411.67 | 0.55 | 0.48 | 2566.24 | 20.86 | 98.00 | 371.00 | 1370.84 | 21.58 | 72.33 | 339.00 |
Report: CoilReportMonthly
For: VAV_BOT WITH REHEAT HEATING COIL
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.617294E+09 | 51267.35 | 27-JAN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.510014E+09 | 55874.14 | 03-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.184652E+09 | 22570.86 | 18-MAR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.174134E+09 | 27263.41 | 06-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 16828398.72 | 3639.68 | 16-MAY-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 3975658.35 | 1833.55 | 10-JUN-16:35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 3131721.70 | 2562.15 | 14-SEP-15:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 83624418.08 | 24474.53 | 26-OCT-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.241672E+09 | 40670.39 | 22-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.526512E+09 | 45707.23 | 18-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.236184E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.617294E+09 | 55874.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_BOTTOM VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.142487E+10 | 16287.69 | 12-JAN-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.580827E+09 | 16124.69 | 03-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 1537312.50 | 540.90 | 18-MAR-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 36033.36 | 60.06 | 06-APR-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 2696431.80 | 619.62 | 26-OCT-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 43319595.67 | 13477.59 | 22-NOV-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.159479E+09 | 15981.43 | 18-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.221276E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.142487E+10 | 16287.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.119287E+10 | 13538.54 | 12-JAN-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.559225E+09 | 13400.74 | 13-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 36214619.67 | 2388.95 | 23-MAR-05:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 10565802.89 | 1639.28 | 06-APR-05:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 10259847.07 | 2055.08 | 26-OCT-05:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 79942894.46 | 13291.83 | 21-NOV-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.309698E+09 | 13284.69 | 19-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.219877E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.119287E+10 | 13538.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.120099E+10 | 18504.43 | 05-JAN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.513461E+09 | 18411.72 | 13-FEB-05:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 18931173.62 | 2477.00 | 23-MAR-05:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 8265811.51 | 1733.76 | 06-APR-05:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 7721130.10 | 1604.21 | 26-OCT-05:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 61250170.09 | 18262.68 | 21-NOV-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.259219E+09 | 18452.85 | 18-DEC-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.206984E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.120099E+10 | 18504.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.734922E+09 | 12306.55 | 23-JAN-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.146744E+09 | 12299.79 | 03-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 2660909.57 | 570.51 | 22-NOV-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 517520.28 | 221.64 | 01-DEC-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.884845E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.734922E+09 | 12306.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV_MID WITH REHEAT HEATING COIL
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.299659E+11 | 514746.89 | 27-JAN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.128535E+11 | 558569.01 | 03-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.469222E+10 | 240291.43 | 18-MAR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.167532E+10 | 286821.63 | 06-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.409918E+09 | 40551.67 | 15-MAY-18:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 32653803.07 | 8841.59 | 10-JUN-13:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 48386671.38 | 24095.30 | 14-SEP-15:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.133033E+10 | 259471.82 | 26-OCT-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.404417E+10 | 421737.34 | 22-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.883385E+10 | 453348.43 | 18-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.638862E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.299659E+11 | 558569.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_MID VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.186566E+11 | 569202.58 | 02-JAN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.843316E+10 | 568715.68 | 06-FEB-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.190783E+10 | 566726.95 | 26-DEC-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.289976E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.186566E+11 | 569202.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.686012E+11 | 163271.54 | 02-JAN-06:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.415086E+11 | 163100.32 | 11-FEB-05:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.662537E+10 | 162488.11 | 22-MAR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.144216E+10 | 161460.06 | 06-APR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 22824.60 | 38.04 | 11-MAY-05:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.307371E+10 | 163020.22 | 31-OCT-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.125535E+11 | 162631.76 | 24-NOV-05:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.364514E+11 | 163382.42 | 26-DEC-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.170256E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.686012E+11 | 163382.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.457294E+11 | 173262.84 | 11-JAN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.277731E+11 | 173236.91 | 08-FEB-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.498493E+10 | 172952.71 | 22-MAR-04:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.901354E+09 | 127737.26 | 06-APR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 22403338.82 | 11616.34 | 11-MAY-05:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 15415404.19 | 3710.68 | 29-SEP-05:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.354001E+10 | 172979.33 | 26-OCT-04:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.874012E+10 | 173083.02 | 24-NOV-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.246607E+11 | 173142.68 | 28-DEC-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.116367E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.457294E+11 | 173262.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.368598E+11 | 192802.45 | 02-JAN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.225112E+11 | 192656.78 | 11-FEB-05:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.320641E+10 | 191595.99 | 23-MAR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.876730E+09 | 190696.33 | 06-APR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.142130E+10 | 185490.24 | 26-OCT-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.463861E+10 | 191677.06 | 25-NOV-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.159826E+11 | 192981.47 | 26-DEC-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.854967E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.368598E+11 | 192981.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.399627E+11 | 176086.83 | 11-JAN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.239527E+11 | 175946.86 | 13-FEB-05:52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.413019E+10 | 175755.64 | 22-MAR-04:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.746159E+09 | 119710.33 | 06-APR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 7016221.87 | 2764.22 | 29-SEP-05:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.242852E+10 | 121731.07 | 26-OCT-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.820117E+10 | 175730.20 | 21-NOV-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.218353E+11 | 175855.22 | 26-DEC-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.101264E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.399627E+11 | 176086.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV_TOP WITH REHEAT HEATING COIL
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.388684E+09 | 48914.22 | 27-JAN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.309434E+09 | 55008.75 | 03-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.133710E+09 | 24573.72 | 18-MAR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.138376E+09 | 29495.44 | 06-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 29738423.31 | 5181.01 | 15-MAY-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 1316040.15 | 467.54 | 10-JUN-16:25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 133851.62 | 161.71 | 22-SEP-15:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 75864361.36 | 26403.64 | 26-OCT-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.201460E+09 | 40297.94 | 22-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.342885E+09 | 42952.86 | 18-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.162160E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.388684E+09 | 55008.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_TOP VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.131676E+11 | 91193.36 | 02-JAN-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.654993E+10 | 91050.34 | 06-FEB-04:33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.532839E+09 | 90827.59 | 20-MAR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 26397337.14 | 4439.68 | 07-APR-05:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.347282E+09 | 91042.03 | 30-OCT-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.182827E+10 | 91022.66 | 27-NOV-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.774482E+10 | 91139.77 | 26-DEC-05:16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.301971E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.131676E+11 | 91193.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.116095E+11 | 18448.53 | 18-JAN-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.705884E+10 | 18452.69 | 08-FEB-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.181297E+10 | 18367.32 | 24-MAR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.527157E+09 | 18292.28 | 07-APR-04:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 30076555.10 | 12063.61 | 11-MAY-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 11475468.17 | 1810.50 | 29-SEP-05:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.116350E+10 | 18436.68 | 31-OCT-04:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.318199E+10 | 18457.30 | 24-NOV-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.738521E+10 | 18433.71 | 12-DEC-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.327807E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.116095E+11 | 18457.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.730160E+10 | 18752.80 | 19-JAN-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.437168E+10 | 18745.76 | 11-FEB-05:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.111571E+10 | 18684.71 | 22-MAR-04:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.297077E+09 | 18611.97 | 06-APR-04:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 19258085.21 | 5953.24 | 11-MAY-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 43226403.85 | 3023.17 | 29-SEP-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.853477E+09 | 18681.66 | 30-OCT-04:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.198202E+10 | 18691.76 | 24-NOV-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.459391E+10 | 18753.14 | 23-DEC-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.205780E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.730160E+10 | 18753.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.717491E+10 | 21163.94 | 09-JAN-04:25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.444734E+10 | 21233.86 | 11-FEB-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.113695E+10 | 21159.82 | 22-MAR-04:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.400895E+09 | 21030.54 | 06-APR-04:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 32749172.57 | 6293.67 | 11-MAY-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 11262480.37 | 2425.55 | 29-SEP-05:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.742879E+09 | 21225.08 | 30-OCT-04:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.162865E+10 | 21160.54 | 24-NOV-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.405364E+10 | 21177.10 | 26-DEC-05:54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.196293E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.717491E+10 | 21233.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.672471E+10 | 20392.84 | 11-JAN-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.399884E+10 | 20405.42 | 07-FEB-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.109863E+10 | 20388.49 | 22-MAR-04:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.301443E+09 | 20344.64 | 06-APR-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 22857073.63 | 2226.71 | 10-MAY-05:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 29099922.70 | 2590.67 | 29-SEP-05:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.802321E+09 | 20384.78 | 30-OCT-04:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.191645E+10 | 20389.28 | 22-NOV-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.409321E+10 | 20386.16 | 02-DEC-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.189876E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.672471E+10 | 20405.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CAV_BAS HEATING COIL
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BASEMENT HEATING COIL
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BOT HEATING COIL
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER MID HEATING COIL
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER TOP HEATING COIL
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BOT_SUPPHEATCOIL
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER MID_SUPPHEATCOIL
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER TOP_SUPPHEATCOIL
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV_BOT WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.418628E+10 | 0.325438E+10 | 49577.65 | 19-JAN-16:00 | 29173.45 | 0.05 |
February | 0.00 | 0.00 | 0.129807E+11 | 0.119387E+11 | 87790.55 | 28-FEB-15:00 | 87790.55 | 0.08 |
March | 0.00 | 0.00 | 0.371894E+11 | 0.329776E+11 | 128454.66 | 30-MAR-15:20 | 128454.66 | 0.20 |
April | 0.00 | 0.00 | 0.709594E+11 | 0.637861E+11 | 167098.76 | 17-APR-15:30 | 167098.76 | 0.44 |
May | 0.00 | 0.00 | 0.108026E+12 | 0.845171E+11 | 193635.85 | 31-MAY-05:03 | 155604.38 | 0.56 |
June | 0.00 | 0.00 | 0.153777E+12 | 0.122204E+12 | 213687.23 | 16-JUN-04:11 | 162669.77 | 0.65 |
July | 0.00 | 0.00 | 0.182750E+12 | 0.139273E+12 | 214129.59 | 01-JUL-04:11 | 163114.09 | 0.77 |
August | 0.00 | 0.00 | 0.212940E+12 | 0.162510E+12 | 185156.23 | 12-AUG-05:02 | 157356.77 | 0.86 |
September | 0.00 | 0.00 | 0.123099E+12 | 0.926115E+11 | 208129.89 | 27-SEP-04:11 | 163231.01 | 0.61 |
October | 0.00 | 0.00 | 0.608539E+11 | 0.477557E+11 | 235688.64 | 19-OCT-04:12 | 154541.19 | 0.33 |
November | 0.00 | 0.00 | 0.271954E+11 | 0.232311E+11 | 114994.50 | 27-NOV-05:12 | 114994.50 | 0.15 |
December | 0.00 | 0.00 | 0.103734E+11 | 0.790705E+10 | 98865.46 | 12-DEC-14:00 | 75587.09 | 0.08 |
Annual Sum or Average | 0.00 | 0.00 | 0.100433E+13 | 0.791967E+12 | 0.40 | |||
Minimum of Months | 0.00 | 0.00 | 0.418628E+10 | 0.325438E+10 | 49577.65 | 29173.45 | 0.05 | |
Maximum of Months | 0.00 | 0.00 | 0.212940E+12 | 0.162510E+12 | 235688.64 | 167098.76 | 0.86 |
Report: CoilReportMonthly
For: VAV_MID WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.349320E+11 | 0.269659E+11 | 391845.64 | 19-JAN-22:00 | 219275.79 | 0.05 |
February | 0.00 | 0.00 | 0.101155E+12 | 0.918812E+11 | 653877.50 | 28-FEB-15:00 | 653877.50 | 0.07 |
March | 0.00 | 0.00 | 0.282113E+12 | 0.250755E+12 | 1096174.49 | 30-MAR-15:20 | 1096174.49 | 0.19 |
April | 0.00 | 0.00 | 0.509438E+12 | 0.456356E+12 | 1289759.78 | 17-APR-14:30 | 1289759.78 | 0.37 |
May | 0.00 | 0.00 | 0.944928E+12 | 0.725085E+12 | 1775638.32 | 31-MAY-05:03 | 1301195.11 | 0.54 |
June | 0.00 | 0.00 | 0.131898E+13 | 0.100441E+13 | 2047154.54 | 30-JUN-05:02 | 1507820.86 | 0.59 |
July | 0.00 | 0.00 | 0.149738E+13 | 0.106167E+13 | 2010011.17 | 14-JUL-04:12 | 1515440.38 | 0.63 |
August | 0.00 | 0.00 | 0.167177E+13 | 0.116374E+13 | 2301627.01 | 23-AUG-05:02 | 1514799.68 | 0.66 |
September | 0.00 | 0.00 | 0.107676E+13 | 0.781454E+12 | 2038906.50 | 27-SEP-04:11 | 1457272.90 | 0.59 |
October | 0.00 | 0.00 | 0.481617E+12 | 0.363932E+12 | 1941680.82 | 19-OCT-04:12 | 1049398.91 | 0.31 |
November | 0.00 | 0.00 | 0.196320E+12 | 0.164516E+12 | 672240.39 | 04-NOV-05:03 | 359905.29 | 0.14 |
December | 0.00 | 0.00 | 0.683327E+11 | 0.516345E+11 | 563451.24 | 12-DEC-14:00 | 453293.67 | 0.08 |
Annual Sum or Average | 0.00 | 0.00 | 0.818373E+13 | 0.614239E+13 | 0.35 | |||
Minimum of Months | 0.00 | 0.00 | 0.349320E+11 | 0.269659E+11 | 391845.64 | 219275.79 | 0.05 | |
Maximum of Months | 0.00 | 0.00 | 0.167177E+13 | 0.116374E+13 | 2301627.01 | 1515440.38 | 0.66 |
Report: CoilReportMonthly
For: VAV_TOP WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.349096E+10 | 0.267261E+10 | 40197.45 | 19-JAN-22:00 | 22843.57 | 0.05 |
February | 0.00 | 0.00 | 0.973973E+10 | 0.879443E+10 | 61977.71 | 28-FEB-15:30 | 61977.71 | 0.07 |
March | 0.00 | 0.00 | 0.277521E+11 | 0.245935E+11 | 119355.63 | 30-MAR-14:20 | 117252.05 | 0.19 |
April | 0.00 | 0.00 | 0.522745E+11 | 0.469645E+11 | 128673.21 | 17-APR-15:50 | 128673.21 | 0.36 |
May | 0.00 | 0.00 | 0.101586E+12 | 0.789405E+11 | 158202.96 | 31-MAY-05:03 | 111731.64 | 0.53 |
June | 0.00 | 0.00 | 0.144690E+12 | 0.112237E+12 | 224993.49 | 26-JUN-04:12 | 163604.83 | 0.59 |
July | 0.00 | 0.00 | 0.163866E+12 | 0.119373E+12 | 220443.80 | 31-JUL-04:11 | 146829.49 | 0.63 |
August | 0.00 | 0.00 | 0.181702E+12 | 0.129900E+12 | 256142.79 | 23-AUG-05:02 | 163986.73 | 0.67 |
September | 0.00 | 0.00 | 0.110976E+12 | 0.812888E+11 | 206225.00 | 05-SEP-05:02 | 146916.31 | 0.58 |
October | 0.00 | 0.00 | 0.483804E+11 | 0.359076E+11 | 202558.16 | 19-OCT-04:12 | 102982.15 | 0.30 |
November | 0.00 | 0.00 | 0.183911E+11 | 0.152563E+11 | 63177.20 | 03-NOV-15:00 | 41720.57 | 0.14 |
December | 0.00 | 0.00 | 0.670704E+10 | 0.503672E+10 | 56784.57 | 12-DEC-14:00 | 44815.95 | 0.08 |
Annual Sum or Average | 0.00 | 0.00 | 0.869555E+12 | 0.660964E+12 | 0.35 | |||
Minimum of Months | 0.00 | 0.00 | 0.349096E+10 | 0.267261E+10 | 40197.45 | 22843.57 | 0.05 | |
Maximum of Months | 0.00 | 0.00 | 0.181702E+12 | 0.129900E+12 | 256142.79 | 163986.73 | 0.67 |
Report: CoilReportMonthly
For: CAV_BAS COOLING COIL
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.577388E+09 | 0.561106E+09 | 60662.59 | 20-JAN-05:23 | 27351.39 | 0.02 |
February | 0.00 | 0.00 | 0.423326E+10 | 0.421127E+10 | 76165.51 | 18-FEB-06:02 | 31522.39 | 0.01 |
March | 0.00 | 0.00 | 0.135794E+11 | 0.135220E+11 | 102769.19 | 30-MAR-05:03 | 51120.82 | 0.13 |
April | 0.00 | 0.00 | 0.290157E+11 | 0.285580E+11 | 104988.40 | 03-APR-04:12 | 104988.40 | 0.25 |
May | 0.00 | 0.00 | 0.516525E+11 | 0.475012E+11 | 135025.59 | 31-MAY-04:12 | 53806.43 | 0.43 |
June | 0.00 | 0.00 | 0.893055E+11 | 0.760581E+11 | 157713.48 | 23-JUN-04:12 | 91831.30 | 0.52 |
July | 0.00 | 0.00 | 0.100403E+12 | 0.807227E+11 | 162673.87 | 08-JUL-03:02 | 95553.97 | 0.53 |
August | 0.00 | 0.00 | 0.120344E+12 | 0.945161E+11 | 184663.80 | 06-AUG-17:31 | 94456.21 | 0.61 |
September | 0.00 | 0.00 | 0.758328E+11 | 0.647648E+11 | 179768.22 | 10-SEP-15:52 | 98091.15 | 0.51 |
October | 0.00 | 0.00 | 0.329230E+11 | 0.278620E+11 | 152244.76 | 19-OCT-04:53 | 92825.50 | 0.21 |
November | 0.00 | 0.00 | 0.105310E+11 | 0.993063E+10 | 99535.69 | 27-NOV-06:03 | 48476.86 | 0.08 |
December | 0.00 | 0.00 | 0.307062E+10 | 0.283080E+10 | 96908.29 | 13-DEC-06:03 | 44950.97 | 0.04 |
Annual Sum or Average | 0.00 | 0.00 | 0.531468E+12 | 0.451039E+12 | 0.28 | |||
Minimum of Months | 0.00 | 0.00 | 0.577388E+09 | 0.561106E+09 | 60662.59 | 27351.39 | 0.01 | |
Maximum of Months | 0.00 | 0.00 | 0.120344E+12 | 0.945161E+11 | 184663.80 | 104988.40 | 0.61 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BASEMENT COOLING COIL
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.322755E+12 | 0.322249E+12 | 130240.38 | 19-JAN-17:00 | 124214.82 | 0.00 |
February | 0.00 | 0.00 | 0.513810E+12 | 0.513255E+12 | 220370.20 | 17-FEB-17:00 | 214654.59 | 0.00 |
March | 0.00 | 0.00 | 0.819754E+12 | 0.818178E+12 | 394618.19 | 31-MAR-24:00 | 394618.19 | 0.00 |
April | 0.00 | 0.00 | 0.103147E+13 | 0.102945E+13 | 407355.99 | 21-APR-15:00 | 400897.14 | 0.00 |
May | 0.00 | 0.00 | 0.341365E+12 | 0.335009E+12 | 213304.05 | 31-MAY-23:10 | 211304.73 | 0.00 |
June | 0.00 | 0.00 | 0.573902E+12 | 0.564586E+12 | 304523.38 | 30-JUN-24:00 | 304005.18 | 0.00 |
July | 0.00 | 0.00 | 0.840997E+12 | 0.829881E+12 | 396982.36 | 31-JUL-23:55 | 396160.59 | 0.00 |
August | 0.00 | 0.00 | 0.108128E+13 | 0.107015E+13 | 423093.78 | 08-AUG-17:00 | 404508.70 | 0.00 |
September | 0.00 | 0.00 | 0.338494E+12 | 0.330100E+12 | 212230.89 | 30-SEP-23:20 | 211708.01 | 0.00 |
October | 0.00 | 0.00 | 0.584559E+12 | 0.580848E+12 | 304685.21 | 31-OCT-24:00 | 304685.21 | 0.00 |
November | 0.00 | 0.00 | 0.798455E+12 | 0.796979E+12 | 318078.77 | 27-NOV-17:00 | 311414.03 | 0.00 |
December | 0.00 | 0.00 | 0.106524E+13 | 0.106449E+13 | 408994.61 | 13-DEC-14:00 | 401173.82 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.831209E+13 | 0.825518E+13 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.322755E+12 | 0.322249E+12 | 130240.38 | 124214.82 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.108128E+13 | 0.107015E+13 | 423093.78 | 404508.70 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BOT COOLING COIL
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.366635E+10 | 0.364720E+10 | 2321.85 | 20-JAN-17:00 | 2219.08 | 0.00 |
February | 0.00 | 0.00 | 0.857835E+10 | 0.855628E+10 | 4531.52 | 20-FEB-17:57 | 4498.52 | 0.00 |
March | 0.00 | 0.00 | 0.156283E+11 | 0.155620E+11 | 7701.85 | 31-MAR-24:00 | 7701.85 | 0.00 |
April | 0.00 | 0.00 | 0.203356E+11 | 0.202451E+11 | 8484.65 | 09-APR-18:15 | 8484.65 | 0.00 |
May | 0.00 | 0.00 | 0.616096E+10 | 0.592471E+10 | 4091.83 | 31-MAY-24:00 | 4037.42 | 0.00 |
June | 0.00 | 0.00 | 0.112697E+11 | 0.108928E+11 | 5969.29 | 30-JUN-24:00 | 5946.40 | 0.00 |
July | 0.00 | 0.00 | 0.167870E+11 | 0.163096E+11 | 7801.45 | 31-JUL-23:55 | 7779.43 | 0.00 |
August | 0.00 | 0.00 | 0.219404E+11 | 0.213917E+11 | 8974.29 | 04-AUG-15:00 | 8353.13 | 0.00 |
September | 0.00 | 0.00 | 0.617805E+10 | 0.586012E+10 | 3751.76 | 30-SEP-24:00 | 3736.09 | 0.00 |
October | 0.00 | 0.00 | 0.108174E+11 | 0.106659E+11 | 5655.26 | 31-OCT-24:00 | 5655.26 | 0.00 |
November | 0.00 | 0.00 | 0.150064E+11 | 0.149489E+11 | 6435.60 | 11-NOV-17:08 | 6435.60 | 0.00 |
December | 0.00 | 0.00 | 0.201076E+11 | 0.200752E+11 | 8306.44 | 11-DEC-16:50 | 8117.81 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.156476E+12 | 0.154080E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.366635E+10 | 0.364720E+10 | 2321.85 | 2219.08 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.219404E+11 | 0.213917E+11 | 8974.29 | 8484.65 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER MID COOLING COIL
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.116269E+11 | 0.114626E+11 | 18736.72 | 20-JAN-17:00 | 17679.15 | 0.00 |
February | 0.00 | 0.00 | 0.627246E+11 | 0.625139E+11 | 41041.90 | 28-FEB-17:00 | 41041.90 | 0.00 |
March | 0.00 | 0.00 | 0.138227E+12 | 0.137568E+12 | 71530.82 | 31-MAR-23:50 | 71530.82 | 0.00 |
April | 0.00 | 0.00 | 0.188317E+12 | 0.187412E+12 | 79656.72 | 04-APR-15:40 | 76735.48 | 0.00 |
May | 0.00 | 0.00 | 0.546039E+11 | 0.523000E+11 | 38386.76 | 31-MAY-23:20 | 37449.74 | 0.00 |
June | 0.00 | 0.00 | 0.105820E+12 | 0.102079E+12 | 56649.66 | 30-JUN-24:00 | 56416.49 | 0.00 |
July | 0.00 | 0.00 | 0.159537E+12 | 0.154780E+12 | 75227.84 | 31-JUL-23:55 | 75011.84 | 0.00 |
August | 0.00 | 0.00 | 0.208831E+12 | 0.203345E+12 | 85091.30 | 04-AUG-14:50 | 79002.59 | 0.00 |
September | 0.00 | 0.00 | 0.544046E+11 | 0.513058E+11 | 31326.62 | 30-SEP-24:00 | 31060.97 | 0.00 |
October | 0.00 | 0.00 | 0.927509E+11 | 0.912602E+11 | 48263.33 | 31-OCT-23:50 | 48263.33 | 0.00 |
November | 0.00 | 0.00 | 0.128045E+12 | 0.127480E+12 | 59728.96 | 08-NOV-17:00 | 59728.96 | 0.00 |
December | 0.00 | 0.00 | 0.168017E+12 | 0.167694E+12 | 76467.37 | 11-DEC-17:00 | 74576.81 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.137290E+13 | 0.134920E+13 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.116269E+11 | 0.114626E+11 | 18736.72 | 17679.15 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.208831E+12 | 0.203345E+12 | 85091.30 | 79002.59 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER TOP COOLING COIL
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.621563E+09 | 0.605803E+09 | 1961.58 | 20-JAN-17:00 | 1852.68 | 0.00 |
February | 0.00 | 0.00 | 0.522525E+10 | 0.520456E+10 | 4144.17 | 28-FEB-17:00 | 4144.17 | 0.00 |
March | 0.00 | 0.00 | 0.130275E+11 | 0.129621E+11 | 6897.78 | 31-MAR-23:20 | 6897.78 | 0.00 |
April | 0.00 | 0.00 | 0.184072E+11 | 0.183172E+11 | 8065.77 | 17-APR-16:00 | 8030.10 | 0.00 |
May | 0.00 | 0.00 | 0.536898E+10 | 0.513908E+10 | 3812.03 | 31-MAY-23:10 | 3702.08 | 0.00 |
June | 0.00 | 0.00 | 0.106418E+11 | 0.102675E+11 | 5636.86 | 30-JUN-24:00 | 5613.17 | 0.00 |
July | 0.00 | 0.00 | 0.160576E+11 | 0.155821E+11 | 7576.32 | 31-JUL-23:55 | 7554.58 | 0.00 |
August | 0.00 | 0.00 | 0.210087E+11 | 0.204599E+11 | 8629.02 | 04-AUG-14:50 | 8026.21 | 0.00 |
September | 0.00 | 0.00 | 0.526916E+10 | 0.496154E+10 | 3066.46 | 07-SEP-16:00 | 2681.05 | 0.00 |
October | 0.00 | 0.00 | 0.851575E+10 | 0.836752E+10 | 4639.91 | 18-OCT-16:00 | 4135.92 | 0.00 |
November | 0.00 | 0.00 | 0.115970E+11 | 0.115411E+11 | 5986.35 | 02-NOV-16:00 | 5801.33 | 0.00 |
December | 0.00 | 0.00 | 0.152248E+11 | 0.151927E+11 | 7609.60 | 13-DEC-16:00 | 7280.94 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.130965E+12 | 0.128601E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.621563E+09 | 0.605803E+09 | 1961.58 | 1852.68 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.210087E+11 | 0.204599E+11 | 8629.02 | 8030.10 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 107759.68 | 1701386.63 | 02-JAN-06:01 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 68032.45 | 1636699.86 | 06-FEB-06:02 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 11006.38 | 1531292.97 | 22-MAR-04:11 |
April | 0.00 | 0.00 | 01-APR-00:10 | 2869.38 | 1066652.84 | 06-APR-05:03 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 243.99 | 51824.29 | 10-MAY-06:10 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 28.29 | 24086.49 | 10-JUN-13:10 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 01-AUG-00:03 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 50.61 | 28418.50 | 14-SEP-15:50 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 5847.03 | 1092865.74 | 31-OCT-05:03 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 18885.44 | 1439935.14 | 25-NOV-05:01 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 51478.09 | 1556218.68 | 26-DEC-06:02 |
Annual Sum or Average | 0.00 | 21989.89 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.00 | 0.00 | 107759.68 | 1701386.63 |
Report: PlantLoopDemandReportMonthly
For: COOLSYS1_SUPPLY
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 17009.14 | 488358.06 | 19-JAN-16:00 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 54701.82 | 921414.49 | 28-FEB-15:10 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 141123.94 | 1671097.78 | 30-MAR-15:20 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 267702.78 | 1906410.30 | 19-APR-14:50 | 0.00 | 0.00 | 01-APR-00:10 |
May | 490744.05 | 1801466.89 | 23-MAY-13:50 | 0.00 | 0.00 | 01-MAY-00:03 |
June | 709297.85 | 2392722.91 | 29-JUN-05:04 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 778281.20 | 2174380.29 | 01-JUL-04:14 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 870530.71 | 2626680.08 | 23-AUG-05:02 | 0.00 | 0.00 | 01-AUG-00:03 |
September | 577925.15 | 1995435.85 | 16-SEP-16:07 | 0.00 | 0.00 | 01-SEP-00:03 |
October | 252402.85 | 2203332.40 | 19-OCT-04:15 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 100922.14 | 954441.18 | 02-NOV-13:10 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 34607.14 | 822898.89 | 12-DEC-14:00 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 359815.78 | 0.00 | ||||
Minimum of Months | 17009.14 | 488358.06 | 0.00 | 0.00 | ||
Maximum of Months | 870530.71 | 2626680.08 | 0.00 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: COOLSYS1_DEMAND
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 16055.10 | 516312.01 | 31-JAN-15:10 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 53010.66 | 919275.08 | 28-FEB-15:00 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 138450.63 | 1668459.68 | 30-MAR-15:10 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 264660.88 | 2148705.67 | 17-APR-13:30 | 0.00 | 0.00 | 01-APR-00:10 |
May | 487045.83 | 3161330.38 | 31-MAY-05:03 | 0.00 | 0.00 | 01-MAY-00:03 |
June | 706507.76 | 3877694.25 | 23-JUN-05:03 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 774668.38 | 3697342.95 | 14-JUL-04:12 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 866204.06 | 3967123.13 | 12-AUG-05:02 | 0.00 | 0.00 | 01-AUG-00:03 |
September | 575205.69 | 3790786.16 | 05-SEP-05:02 | 0.00 | 0.00 | 01-SEP-00:03 |
October | 249339.60 | 3450528.93 | 19-OCT-05:03 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 98694.54 | 958289.25 | 04-NOV-05:03 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 33410.21 | 819965.94 | 12-DEC-14:00 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 357141.79 | 0.00 | ||||
Minimum of Months | 16055.10 | 516312.01 | 0.00 | 0.00 | ||
Maximum of Months | 866204.06 | 3967123.13 | 0.00 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SINGLE WATER PLANT LOOP
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 164780.08 | 419385.64 | 31-JAN-15:00 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 338212.29 | 861722.75 | 28-FEB-15:00 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 577006.00 | 1257343.65 | 30-MAR-16:00 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 892545.52 | 1531128.30 | 17-APR-16:00 | 0.00 | 0.00 | 01-APR-00:10 |
May | 438384.66 | 967370.60 | 30-MAY-15:00 | 0.00 | 0.00 | 01-MAY-00:03 |
June | 859896.46 | 1416932.73 | 06-JUN-15:00 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 1153484.39 | 1776718.29 | 08-JUL-16:00 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 1401418.32 | 1887269.42 | 01-AUG-16:10 | 0.00 | 0.00 | 01-AUG-00:03 |
September | 520479.85 | 1042735.33 | 07-SEP-16:00 | 0.00 | 0.00 | 01-SEP-00:03 |
October | 470403.28 | 1165752.88 | 10-OCT-16:00 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 539997.72 | 1036569.58 | 05-NOV-16:00 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 617356.57 | 1186294.93 | 12-DEC-15:00 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 666754.42 | 0.00 | ||||
Minimum of Months | 164780.08 | 419385.64 | 0.00 | 0.00 | ||
Maximum of Months | 1401418.32 | 1887269.42 | 0.00 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 14850.00 | 49687.18 | 30-JAN-12:40 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 14960.05 | 49691.65 | 01-FEB-12:40 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 15317.31 | 48919.31 | 01-MAR-12:50 |
April | 0.00 | 0.00 | 01-APR-00:10 | 13611.95 | 46270.62 | 03-APR-11:50 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 13012.53 | 43150.94 | 01-MAY-11:40 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12345.19 | 39646.21 | 01-JUN-11:30 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 10959.34 | 36965.52 | 03-JUL-12:00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 11824.71 | 36815.48 | 31-AUG-11:50 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 11655.39 | 39093.32 | 29-SEP-11:30 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 12475.73 | 42640.11 | 31-OCT-12:00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 13623.08 | 46035.21 | 30-NOV-13:00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 14016.97 | 48586.36 | 29-DEC-12:15 |
Annual Sum or Average | 0.00 | 13211.24 | ||||
Minimum of Months | 0.00 | 0.00 | 10959.34 | 36815.48 | ||
Maximum of Months | 0.00 | 0.00 | 15317.31 | 49691.65 |
Report: PlantLoopDemandReportMonthly
For: TOWERWATERSYS
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 19123.76 | 581447.72 | 19-JAN-16:00 | 4167.44 | 172700.19 | 06-JAN-12:20 |
February | 63714.38 | 1062309.43 | 28-FEB-15:10 | 3556.55 | 190795.46 | 12-FEB-04:02 |
March | 170952.14 | 2870371.58 | 30-MAR-15:20 | 2367.55 | 175814.57 | 06-MAR-07:30 |
April | 337949.50 | 3071546.89 | 18-APR-12:40 | 960.77 | 109042.00 | 25-APR-20:00 |
May | 759604.36 | 4375444.07 | 31-MAY-12:50 | 119.99 | 77238.55 | 09-MAY-21:00 |
June | 1558598.35 | 5563746.26 | 27-JUN-12:10 | 108.53 | 83178.82 | 10-JUN-06:30 |
July | 1960824.18 | 5919948.60 | 07-JUL-12:10 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 2363658.45 | 6143653.85 | 10-AUG-16:00 | 0.00 | 0.00 | 01-AUG-00:03 |
September | 1127570.91 | 5424044.31 | 06-SEP-14:00 | 92.07 | 59446.62 | 14-SEP-06:50 |
October | 401795.52 | 5016578.85 | 18-OCT-16:00 | 1177.66 | 126607.26 | 25-OCT-11:00 |
November | 117614.70 | 1278596.61 | 02-NOV-13:10 | 2376.44 | 164125.37 | 21-NOV-07:00 |
December | 35999.26 | 949970.27 | 12-DEC-14:00 | 2955.42 | 184336.09 | 01-DEC-09:30 |
Annual Sum or Average | 748237.52 | 1479.86 | ||||
Minimum of Months | 19123.76 | 581447.72 | 0.00 | 0.00 | ||
Maximum of Months | 2363658.45 | 6143653.85 | 4167.44 | 190795.46 |
Report: FanReportMonthly
For: CAV_BAS FAN
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.153072E+11 | 0.80 | 10319.93 | 01-JAN-00:50 | 1.44 |
February | 0.136018E+11 | 0.79 | 10319.93 | 01-FEB-05:01 | 1.44 |
March | 0.161156E+11 | 0.84 | 10319.93 | 01-MAR-05:12 | 1.44 |
April | 0.147431E+11 | 0.79 | 10319.93 | 01-APR-04:12 | 1.44 |
May | 0.155883E+11 | 0.80 | 10319.93 | 01-MAY-04:12 | 1.43 |
June | 0.155171E+11 | 0.83 | 10319.93 | 01-JUN-04:12 | 1.43 |
July | 0.153962E+11 | 0.79 | 10319.93 | 01-JUL-04:11 | 1.43 |
August | 0.171714E+11 | 0.88 | 10319.93 | 01-AUG-03:02 | 1.43 |
September | 0.162821E+11 | 0.87 | 10319.93 | 01-SEP-04:11 | 1.43 |
October | 0.161420E+11 | 0.84 | 10319.93 | 01-OCT-24:00 | 1.42 |
November | 0.157980E+11 | 0.85 | 10319.93 | 01-NOV-04:12 | 1.43 |
December | 0.152441E+11 | 0.79 | 10319.93 | 01-DEC-04:01 | 1.44 |
Annual Sum or Average | 0.186907E+12 | 0.82 | |||
Minimum of Months | 0.136018E+11 | 0.79 | 10319.93 | 1.42 | |
Maximum of Months | 0.171714E+11 | 0.88 | 10319.93 | 1.44 |
Report: FanReportMonthly
For: VAV_BOT WITH REHEAT FAN
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.294665E+10 | 0.29 | 12997.31 | 05-JAN-13:07 | 1.33 |
February | 0.317851E+10 | 0.31 | 18211.61 | 02-FEB-16:30 | 1.64 |
March | 0.477753E+10 | 0.37 | 13469.25 | 30-MAR-04:12 | 1.34 |
April | 0.550538E+10 | 0.40 | 16859.04 | 17-APR-15:30 | 1.55 |
May | 0.530270E+10 | 0.38 | 21649.32 | 30-MAY-04:12 | 1.81 |
June | 0.678805E+10 | 0.46 | 21649.32 | 05-JUN-04:12 | 1.81 |
July | 0.746000E+10 | 0.50 | 21649.32 | 01-JUL-04:11 | 1.81 |
August | 0.891571E+10 | 0.57 | 21649.32 | 12-AUG-05:02 | 1.81 |
September | 0.556656E+10 | 0.39 | 21649.32 | 05-SEP-04:12 | 1.81 |
October | 0.491238E+10 | 0.36 | 21649.32 | 19-OCT-04:12 | 1.81 |
November | 0.427493E+10 | 0.34 | 13012.85 | 21-NOV-09:50 | 1.33 |
December | 0.383480E+10 | 0.31 | 13469.25 | 13-DEC-05:12 | 1.34 |
Annual Sum or Average | 0.634632E+11 | 0.39 | |||
Minimum of Months | 0.294665E+10 | 0.29 | 12997.31 | 1.33 | |
Maximum of Months | 0.891571E+10 | 0.57 | 21649.32 | 1.81 |
Report: FanReportMonthly
For: VAV_MID WITH REHEAT FAN
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.291286E+11 | 0.31 | 90861.50 | 06-JAN-12:00 | 1.12 |
February | 0.272292E+11 | 0.32 | 100578.83 | 03-FEB-11:45 | 1.19 |
March | 0.332390E+11 | 0.32 | 95861.59 | 03-MAR-06:02 | 1.15 |
April | 0.359464E+11 | 0.32 | 107741.82 | 17-APR-14:30 | 1.23 |
May | 0.439145E+11 | 0.36 | 160310.60 | 30-MAY-05:03 | 1.57 |
June | 0.545407E+11 | 0.41 | 203125.57 | 13-JUN-05:02 | 1.82 |
July | 0.561742E+11 | 0.40 | 203125.57 | 05-JUL-04:12 | 1.82 |
August | 0.620613E+11 | 0.43 | 203125.57 | 09-AUG-05:02 | 1.82 |
September | 0.453198E+11 | 0.36 | 203125.57 | 05-SEP-05:02 | 1.82 |
October | 0.349541E+11 | 0.31 | 106610.03 | 19-OCT-05:03 | 1.21 |
November | 0.283959E+11 | 0.29 | 112935.04 | 07-NOV-06:02 | 1.27 |
December | 0.271162E+11 | 0.29 | 72216.39 | 14-DEC-06:03 | 0.97 |
Annual Sum or Average | 0.478020E+12 | 0.34 | |||
Minimum of Months | 0.271162E+11 | 0.29 | 72216.39 | 0.97 | |
Maximum of Months | 0.620613E+11 | 0.43 | 203125.57 | 1.82 |
Report: FanReportMonthly
For: VAV_TOP WITH REHEAT FAN
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.362515E+10 | 0.37 | 4566.97 | 02-JAN-05:21 | 0.72 |
February | 0.297419E+10 | 0.34 | 4566.97 | 02-FEB-06:02 | 0.72 |
March | 0.316029E+10 | 0.31 | 7913.07 | 29-MAR-05:03 | 0.96 |
April | 0.340795E+10 | 0.31 | 8405.49 | 17-APR-14:40 | 1.00 |
May | 0.446797E+10 | 0.35 | 12872.50 | 30-MAY-05:03 | 1.30 |
June | 0.582535E+10 | 0.41 | 21911.26 | 13-JUN-05:02 | 1.81 |
July | 0.608836E+10 | 0.41 | 21911.26 | 05-JUL-04:12 | 1.81 |
August | 0.668440E+10 | 0.43 | 21911.26 | 05-AUG-04:12 | 1.81 |
September | 0.441418E+10 | 0.35 | 21911.26 | 07-SEP-05:02 | 1.81 |
October | 0.325250E+10 | 0.30 | 9224.16 | 18-OCT-05:02 | 1.06 |
November | 0.274053E+10 | 0.29 | 4566.97 | 21-NOV-06:02 | 0.72 |
December | 0.316605E+10 | 0.33 | 4566.97 | 01-DEC-06:02 | 0.72 |
Annual Sum or Average | 0.498069E+11 | 0.35 | |||
Minimum of Months | 0.274053E+10 | 0.29 | 4566.97 | 0.72 | |
Maximum of Months | 0.668440E+10 | 0.43 | 21911.26 | 1.81 |
Report: FanReportMonthly
For: AIRLOOP DATACENTER BASEMENT SUPPLY FAN
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.977848E+11 | 1.40 | 36508.66 | 01-JAN-00:10 | 1.39 |
February | 0.883218E+11 | 1.40 | 36508.66 | 01-FEB-00:10 | 1.39 |
March | 0.977848E+11 | 1.39 | 36508.66 | 01-MAR-00:10 | 1.40 |
April | 0.946305E+11 | 1.39 | 36508.66 | 01-APR-00:10 | 1.39 |
May | 0.977848E+11 | 1.39 | 36508.66 | 01-MAY-00:03 | 1.39 |
June | 0.946305E+11 | 1.39 | 36508.66 | 01-JUN-00:10 | 1.39 |
July | 0.977848E+11 | 1.39 | 36508.66 | 01-JUL-00:10 | 1.39 |
August | 0.977848E+11 | 1.39 | 36508.66 | 01-AUG-00:03 | 1.39 |
September | 0.946305E+11 | 1.39 | 36508.66 | 01-SEP-00:03 | 1.39 |
October | 0.977848E+11 | 1.39 | 36508.66 | 01-OCT-00:10 | 1.39 |
November | 0.946305E+11 | 1.39 | 36508.66 | 01-NOV-00:10 | 1.40 |
December | 0.977848E+11 | 1.40 | 36508.66 | 01-DEC-00:10 | 1.39 |
Annual Sum or Average | 0.115134E+13 | 1.39 | |||
Minimum of Months | 0.883218E+11 | 1.39 | 36508.66 | 1.39 | |
Maximum of Months | 0.977848E+11 | 1.40 | 36508.66 | 1.40 |
Report: FanReportMonthly
For: AIRLOOP DATACENTER BOT SUPPLY FAN
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.147651E+10 | 0.95 | 551.27 | 01-JAN-00:05 | 0.95 |
February | 0.133363E+10 | 0.95 | 551.27 | 01-FEB-00:10 | 0.95 |
March | 0.147651E+10 | 0.95 | 551.27 | 01-MAR-00:10 | 0.95 |
April | 0.142889E+10 | 0.95 | 551.27 | 01-APR-00:10 | 0.95 |
May | 0.147651E+10 | 0.95 | 551.27 | 01-MAY-00:03 | 0.95 |
June | 0.142889E+10 | 0.95 | 551.27 | 01-JUN-00:10 | 0.95 |
July | 0.147651E+10 | 0.95 | 551.27 | 01-JUL-00:10 | 0.95 |
August | 0.147651E+10 | 0.94 | 551.27 | 01-AUG-00:03 | 0.95 |
September | 0.142889E+10 | 0.95 | 551.27 | 01-SEP-00:03 | 0.95 |
October | 0.147651E+10 | 0.95 | 551.27 | 01-OCT-00:10 | 0.95 |
November | 0.142889E+10 | 0.95 | 551.27 | 01-NOV-00:10 | 0.95 |
December | 0.147651E+10 | 0.95 | 551.27 | 01-DEC-00:10 | 0.95 |
Annual Sum or Average | 0.173848E+11 | 0.95 | |||
Minimum of Months | 0.133363E+10 | 0.94 | 551.27 | 0.95 | |
Maximum of Months | 0.147651E+10 | 0.95 | 551.27 | 0.95 |
Report: FanReportMonthly
For: AIRLOOP DATACENTER MID SUPPLY FAN
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.140759E+11 | 0.95 | 5255.32 | 01-JAN-00:05 | 0.95 |
February | 0.127137E+11 | 0.95 | 5255.32 | 01-FEB-00:10 | 0.95 |
March | 0.140759E+11 | 0.95 | 5255.32 | 01-MAR-00:10 | 0.95 |
April | 0.136218E+11 | 0.95 | 5255.32 | 01-APR-00:10 | 0.95 |
May | 0.140759E+11 | 0.95 | 5255.32 | 01-MAY-00:03 | 0.95 |
June | 0.136218E+11 | 0.95 | 5255.32 | 01-JUN-00:10 | 0.95 |
July | 0.140759E+11 | 0.95 | 5255.32 | 01-JUL-00:10 | 0.95 |
August | 0.140759E+11 | 0.94 | 5255.32 | 01-AUG-00:03 | 0.95 |
September | 0.136218E+11 | 0.94 | 5255.32 | 01-SEP-00:03 | 0.95 |
October | 0.140759E+11 | 0.95 | 5255.32 | 01-OCT-00:10 | 0.95 |
November | 0.136218E+11 | 0.95 | 5255.32 | 01-NOV-00:10 | 0.95 |
December | 0.140759E+11 | 0.95 | 5255.32 | 01-DEC-00:10 | 0.95 |
Annual Sum or Average | 0.165732E+12 | 0.95 | |||
Minimum of Months | 0.127137E+11 | 0.94 | 5255.32 | 0.95 | |
Maximum of Months | 0.140759E+11 | 0.95 | 5255.32 | 0.95 |
Report: FanReportMonthly
For: AIRLOOP DATACENTER TOP SUPPLY FAN
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.143387E+10 | 0.95 | 535.34 | 01-JAN-00:05 | 0.95 |
February | 0.129511E+10 | 0.95 | 535.34 | 01-FEB-00:10 | 0.95 |
March | 0.143387E+10 | 0.95 | 535.34 | 01-MAR-00:10 | 0.95 |
April | 0.138761E+10 | 0.95 | 535.34 | 01-APR-00:10 | 0.95 |
May | 0.143387E+10 | 0.95 | 535.34 | 01-MAY-00:03 | 0.95 |
June | 0.138761E+10 | 0.95 | 535.34 | 01-JUN-00:10 | 0.95 |
July | 0.143387E+10 | 0.95 | 535.34 | 01-JUL-00:10 | 0.95 |
August | 0.143387E+10 | 0.94 | 535.34 | 01-AUG-00:03 | 0.95 |
September | 0.138761E+10 | 0.94 | 535.34 | 01-SEP-00:03 | 0.95 |
October | 0.143387E+10 | 0.95 | 535.34 | 01-OCT-00:10 | 0.95 |
November | 0.138761E+10 | 0.95 | 535.34 | 01-NOV-00:20 | 0.95 |
December | 0.143387E+10 | 0.95 | 535.34 | 01-DEC-00:10 | 0.95 |
Annual Sum or Average | 0.168826E+11 | 0.95 | |||
Minimum of Months | 0.129511E+10 | 0.94 | 535.34 | 0.95 | |
Maximum of Months | 0.143387E+10 | 0.95 | 535.34 | 0.95 |
Report: PumpReportMonthly
For: HEATSYS1 PUMP
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.130260E+10 | 0.117234E+10 | 4990.39 | 09-JAN-06:03 | 4491.36 | 4491.36 | 49.51 | 11.40 |
February | 0.737916E+09 | 0.664125E+09 | 4990.08 | 13-FEB-06:02 | 4491.07 | 4491.07 | 49.60 | 11.40 |
March | 0.118708E+09 | 0.106837E+09 | 3988.95 | 23-MAR-05:02 | 3590.06 | 3590.06 | 34.18 | 6.39 |
April | 32645315.37 | 29380783.83 | 3587.23 | 06-APR-05:03 | 3228.51 | 3228.51 | 33.95 | 5.31 |
May | 3012892.32 | 2711603.09 | 260.87 | 15-MAY-18:40 | 234.78 | 234.78 | 37.73 | 0.27 |
June | 388939.35 | 350045.42 | 126.86 | 10-JUN-13:10 | 114.17 | 114.17 | 37.65 | 0.13 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 41.86 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 41.86 | 0.00 |
September | 727293.36 | 654564.03 | 159.99 | 14-SEP-15:50 | 143.99 | 143.99 | 40.56 | 0.16 |
October | 61104158.78 | 54993742.90 | 3695.76 | 26-OCT-05:03 | 3326.18 | 3326.18 | 37.39 | 5.57 |
November | 0.204455E+09 | 0.184009E+09 | 4248.53 | 22-NOV-06:03 | 3823.68 | 3823.68 | 46.65 | 7.21 |
December | 0.609077E+09 | 0.548169E+09 | 4957.28 | 26-DEC-06:02 | 4461.55 | 4461.55 | 48.48 | 11.10 |
Annual Sum or Average | 0.307064E+10 | 0.276358E+10 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.95 | 0.00 | |
Maximum of Months | 0.130260E+10 | 0.117234E+10 | 4990.39 | 4491.36 | 4491.36 | 49.60 | 11.40 |
Report: PumpReportMonthly
For: COOLSYS1 PUMP SECONDARY
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 17337048.45 | 15603343.61 | 434.43 | 31-JAN-14:50 | 390.99 | 390.99 | 6.70 | 23.12 |
February | 39962620.40 | 35966358.36 | 492.35 | 28-FEB-15:30 | 443.12 | 443.12 | 6.70 | 24.62 |
March | 0.221621E+09 | 0.199459E+09 | 3413.46 | 30-MAR-15:10 | 3072.12 | 3072.12 | 6.71 | 60.19 |
April | 0.659342E+09 | 0.593408E+09 | 7345.92 | 13-APR-14:30 | 6611.32 | 6611.32 | 7.69 | 83.15 |
May | 0.132381E+10 | 0.119143E+10 | 14051.91 | 31-MAY-05:03 | 12646.72 | 12646.72 | 8.43 | 108.16 |
June | 0.238730E+10 | 0.214857E+10 | 20715.12 | 14-JUN-05:03 | 18643.61 | 18643.61 | 8.92 | 126.12 |
July | 0.277818E+10 | 0.250036E+10 | 19962.01 | 19-JUL-05:02 | 17965.81 | 17965.81 | 8.68 | 124.28 |
August | 0.330033E+10 | 0.297030E+10 | 20715.12 | 12-AUG-05:02 | 18643.61 | 18643.61 | 8.65 | 126.12 |
September | 0.177654E+10 | 0.159889E+10 | 20678.00 | 27-SEP-05:03 | 18610.20 | 18610.20 | 8.95 | 126.01 |
October | 0.664975E+09 | 0.598478E+09 | 17420.87 | 19-OCT-05:03 | 15678.78 | 15678.78 | 8.71 | 117.79 |
November | 0.110893E+09 | 99803947.38 | 937.25 | 04-NOV-05:03 | 843.53 | 843.53 | 6.70 | 33.62 |
December | 37300854.42 | 33570768.98 | 578.01 | 12-DEC-14:00 | 520.21 | 520.21 | 6.70 | 26.65 |
Annual Sum or Average | 0.133176E+11 | 0.119858E+11 | ||||||
Minimum of Months | 17337048.45 | 15603343.61 | 434.43 | 390.99 | 390.99 | 6.70 | 23.12 | |
Maximum of Months | 0.330033E+10 | 0.297030E+10 | 20715.12 | 18643.61 | 18643.61 | 8.95 | 126.12 |
Report: PumpReportMonthly
For: COOLSYS1 CHILLER1 PUMP
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.287349E+10 | 0.258614E+10 | 7128.83 | 01-JAN-01:10 | 6415.94 | 6415.94 | 6.72 | 63.06 |
February | 0.463759E+10 | 0.417383E+10 | 7128.83 | 01-FEB-06:02 | 6415.94 | 6415.94 | 7.00 | 63.06 |
March | 0.816493E+10 | 0.734844E+10 | 7128.83 | 01-MAR-05:12 | 6415.94 | 6415.94 | 7.33 | 63.06 |
April | 0.106678E+11 | 0.960100E+10 | 7128.83 | 01-APR-04:12 | 6415.94 | 6415.94 | 6.87 | 63.06 |
May | 0.118907E+11 | 0.107017E+11 | 7128.83 | 01-MAY-00:03 | 6415.94 | 6415.94 | 6.89 | 63.06 |
June | 0.133584E+11 | 0.120225E+11 | 7128.83 | 01-JUN-04:12 | 6415.94 | 6415.94 | 11.21 | 63.06 |
July | 0.154936E+11 | 0.139443E+11 | 7128.83 | 01-JUL-04:11 | 6415.94 | 6415.94 | 12.12 | 63.06 |
August | 0.171378E+11 | 0.154240E+11 | 7128.83 | 01-AUG-00:03 | 6415.94 | 6415.94 | 6.90 | 63.06 |
September | 0.118393E+11 | 0.106553E+11 | 7128.83 | 01-SEP-00:52 | 6415.94 | 6415.94 | 6.92 | 63.06 |
October | 0.875656E+10 | 0.788091E+10 | 7128.83 | 01-OCT-12:22 | 6415.94 | 6415.94 | 7.68 | 63.06 |
November | 0.658511E+10 | 0.592660E+10 | 7128.83 | 01-NOV-04:12 | 6415.94 | 6415.94 | 6.86 | 63.06 |
December | 0.361597E+10 | 0.325437E+10 | 7128.83 | 01-DEC-04:08 | 6415.94 | 6415.94 | 6.72 | 63.06 |
Annual Sum or Average | 0.115021E+12 | 0.103519E+12 | ||||||
Minimum of Months | 0.287349E+10 | 0.258614E+10 | 7128.83 | 6415.94 | 6415.94 | 6.72 | 63.06 | |
Maximum of Months | 0.171378E+11 | 0.154240E+11 | 7128.83 | 6415.94 | 6415.94 | 12.12 | 63.06 |
Report: PumpReportMonthly
For: COOLSYS1 CHILLER2 PUMP
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 6.72 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 7.16 | 0.00 |
March | 17109186.03 | 15398267.42 | 7128.83 | 30-MAR-14:40 | 6415.94 | 6415.94 | 12.69 | 31.53 |
April | 94100523.15 | 84690470.83 | 7128.83 | 04-APR-13:20 | 6415.94 | 6415.94 | 12.42 | 31.53 |
May | 0.902510E+09 | 0.812259E+09 | 7128.83 | 03-MAY-13:30 | 6415.94 | 6415.94 | 12.46 | 31.53 |
June | 0.368269E+10 | 0.331442E+10 | 7128.83 | 01-JUN-08:30 | 6415.94 | 6415.94 | 12.40 | 31.53 |
July | 0.445474E+10 | 0.400927E+10 | 7128.83 | 01-JUL-04:13 | 6415.94 | 6415.94 | 12.95 | 31.53 |
August | 0.575952E+10 | 0.518357E+10 | 7128.83 | 01-AUG-07:10 | 6415.94 | 6415.94 | 12.42 | 31.53 |
September | 0.210635E+10 | 0.189572E+10 | 7128.83 | 01-SEP-10:00 | 6415.94 | 6415.94 | 12.42 | 31.53 |
October | 0.608802E+09 | 0.547922E+09 | 7128.83 | 02-OCT-10:00 | 6415.94 | 6415.94 | 12.38 | 31.53 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 6.86 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 6.72 | 0.00 |
Annual Sum or Average | 0.176258E+11 | 0.158632E+11 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.72 | 0.00 | |
Maximum of Months | 0.575952E+10 | 0.518357E+10 | 7128.83 | 6415.94 | 6415.94 | 12.95 | 31.53 |
Report: PumpReportMonthly
For: PLANT CIRC PUMP
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.920265E+10 | 0.828238E+10 | 3435.87 | 01-JAN-00:05 | 3092.29 | 3092.29 | 21.55 | 14.35 |
February | 0.831207E+10 | 0.748086E+10 | 3435.87 | 01-FEB-00:10 | 3092.29 | 3092.29 | 24.23 | 14.35 |
March | 0.920265E+10 | 0.828238E+10 | 3435.87 | 01-MAR-00:10 | 3092.29 | 3092.29 | 28.06 | 14.35 |
April | 0.890579E+10 | 0.801521E+10 | 3435.87 | 01-APR-00:10 | 3092.29 | 3092.29 | 30.19 | 14.35 |
May | 0.920265E+10 | 0.828238E+10 | 3435.87 | 01-MAY-00:03 | 3092.29 | 3092.29 | 22.63 | 14.35 |
June | 0.890579E+10 | 0.801521E+10 | 3435.87 | 01-JUN-00:10 | 3092.29 | 3092.29 | 30.76 | 14.35 |
July | 0.920265E+10 | 0.828238E+10 | 3435.87 | 01-JUL-00:10 | 3092.29 | 3092.29 | 36.43 | 14.35 |
August | 0.920265E+10 | 0.828238E+10 | 3435.87 | 01-AUG-00:03 | 3092.29 | 3092.29 | 43.92 | 14.35 |
September | 0.890579E+10 | 0.801521E+10 | 3435.87 | 01-SEP-00:03 | 3092.29 | 3092.29 | 27.68 | 14.35 |
October | 0.920265E+10 | 0.828238E+10 | 3435.87 | 01-OCT-00:10 | 3092.29 | 3092.29 | 26.05 | 14.35 |
November | 0.890579E+10 | 0.801521E+10 | 3435.87 | 01-NOV-00:10 | 3092.29 | 3092.29 | 27.38 | 14.35 |
December | 0.920265E+10 | 0.828238E+10 | 3435.87 | 01-DEC-00:10 | 3092.29 | 3092.29 | 29.69 | 14.35 |
Annual Sum or Average | 0.108354E+12 | 0.975184E+11 | ||||||
Minimum of Months | 0.831207E+10 | 0.748086E+10 | 3435.87 | 3092.29 | 3092.29 | 21.55 | 14.35 | |
Maximum of Months | 0.920265E+10 | 0.828238E+10 | 3435.87 | 3092.29 | 3092.29 | 43.92 | 14.35 |
Report: PumpReportMonthly
For: SWHSYS1 PUMP
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.112905E+09 | 33871561.48 | 56.21 | 01-JAN-06:10 | 16.86 | 16.86 | 55.73 | 0.44 |
February | 0.101979E+09 | 30593668.43 | 56.21 | 01-FEB-06:02 | 16.86 | 16.86 | 56.47 | 0.44 |
March | 0.112905E+09 | 33871561.48 | 56.21 | 01-MAR-06:03 | 16.86 | 16.86 | 56.70 | 0.44 |
April | 0.109263E+09 | 32778930.46 | 56.21 | 01-APR-05:02 | 16.86 | 16.86 | 55.79 | 0.44 |
May | 0.112905E+09 | 33871561.48 | 56.21 | 01-MAY-05:03 | 16.86 | 16.86 | 57.31 | 0.44 |
June | 0.109263E+09 | 32778930.46 | 56.21 | 01-JUN-05:03 | 16.86 | 16.86 | 56.98 | 0.44 |
July | 0.112905E+09 | 33871561.48 | 56.21 | 01-JUL-05:03 | 16.86 | 16.86 | 57.05 | 0.44 |
August | 0.112905E+09 | 33871561.48 | 56.21 | 01-AUG-05:03 | 16.86 | 16.86 | 57.01 | 0.44 |
September | 0.109263E+09 | 32778930.46 | 56.21 | 01-SEP-05:03 | 16.86 | 16.86 | 57.03 | 0.44 |
October | 0.112905E+09 | 33871561.48 | 56.21 | 01-OCT-05:10 | 16.86 | 16.86 | 56.52 | 0.44 |
November | 0.109263E+09 | 32778930.46 | 56.21 | 01-NOV-05:03 | 16.86 | 16.86 | 57.10 | 0.44 |
December | 0.112905E+09 | 33871561.48 | 56.21 | 01-DEC-06:01 | 16.86 | 16.86 | 56.07 | 0.44 |
Annual Sum or Average | 0.132937E+10 | 0.398810E+09 | ||||||
Minimum of Months | 0.101979E+09 | 30593668.43 | 56.21 | 16.86 | 16.86 | 55.73 | 0.44 | |
Maximum of Months | 0.112905E+09 | 33871561.48 | 56.21 | 16.86 | 16.86 | 57.31 | 0.44 |
Report: PumpReportMonthly
For: TOWERWATERSYS PUMP
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.739055E+10 | 0.665150E+10 | 18355.67 | 19-JAN-16:00 | 16520.11 | 16520.11 | 22.97 | 74.29 |
February | 0.119312E+11 | 0.107381E+11 | 18376.14 | 28-FEB-15:10 | 16538.53 | 16538.53 | 24.52 | 74.29 |
March | 0.210586E+11 | 0.189527E+11 | 36787.33 | 30-MAR-15:20 | 33108.60 | 33108.60 | 25.72 | 148.58 |
April | 0.276667E+11 | 0.249000E+11 | 36797.32 | 18-APR-12:40 | 33117.59 | 33117.59 | 26.05 | 148.58 |
May | 0.327991E+11 | 0.295192E+11 | 36862.20 | 31-MAY-12:50 | 33175.98 | 33175.98 | 28.15 | 148.58 |
June | 0.433271E+11 | 0.389944E+11 | 36882.70 | 12-JUN-09:50 | 33194.43 | 33194.43 | 28.93 | 148.58 |
July | 0.507242E+11 | 0.456517E+11 | 36882.70 | 05-JUL-08:70 | 33194.43 | 33194.43 | 28.94 | 148.58 |
August | 0.581087E+11 | 0.522978E+11 | 36882.70 | 01-AUG-09:30 | 33194.43 | 33194.43 | 29.72 | 148.58 |
September | 0.353353E+11 | 0.318018E+11 | 36882.70 | 05-SEP-12:10 | 33194.43 | 33194.43 | 28.83 | 148.58 |
October | 0.238323E+11 | 0.214491E+11 | 36882.70 | 18-OCT-14:40 | 33194.43 | 33194.43 | 29.00 | 148.58 |
November | 0.169456E+11 | 0.152510E+11 | 18385.84 | 02-NOV-13:10 | 16547.25 | 16547.25 | 25.22 | 74.29 |
December | 0.927982E+10 | 0.835184E+10 | 18371.36 | 12-DEC-14:00 | 16534.22 | 16534.22 | 24.16 | 74.29 |
Annual Sum or Average | 0.338399E+12 | 0.304559E+12 | ||||||
Minimum of Months | 0.739055E+10 | 0.665150E+10 | 18355.67 | 16520.11 | 16520.11 | 22.97 | 74.29 | |
Maximum of Months | 0.581087E+11 | 0.522978E+11 | 36882.70 | 33194.43 | 33194.43 | 29.72 | 148.58 |
Report: CondLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 28.49 | 82.00 | 107759.68 | 1701386.63 | 02-JAN-06:01 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 18.65 | 18.65 | 68032.45 | 1636699.86 | 06-FEB-06:02 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 19.20 | 19.20 | 11006.38 | 1531292.97 | 22-MAR-04:11 |
April | 0.00 | 0.00 | 01-APR-00:10 | 25.20 | 25.20 | 2869.38 | 1066652.84 | 06-APR-05:03 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 21.33 | 21.33 | 243.99 | 51824.29 | 10-MAY-06:10 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 35.23 | 35.23 | 28.29 | 24086.49 | 10-JUN-13:10 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 41.86 | 41.86 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 41.86 | 41.86 | 0.00 | 0.00 | 01-AUG-00:03 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 41.86 | 41.86 | 50.61 | 28418.50 | 14-SEP-15:50 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 35.13 | 35.13 | 5847.03 | 1092865.74 | 31-OCT-05:03 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 18.64 | 18.64 | 18885.44 | 1439935.14 | 25-NOV-05:01 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 25.82 | 25.82 | 51478.09 | 1556218.68 | 26-DEC-06:02 |
Annual Sum or Average | 0.00 | 21989.89 | ||||||
Minimum of Months | 0.00 | 0.00 | 18.64 | 18.64 | 0.00 | 0.00 | ||
Maximum of Months | 0.00 | 0.00 | 41.86 | 82.00 | 107759.68 | 1701386.63 |
Report: CondLoopDemandReportMonthly
For: COOLSYS1_SUPPLY
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 17009.14 | 488358.06 | 19-JAN-16:00 | 8.55 | 6.70 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 54701.82 | 921414.49 | 28-FEB-15:10 | 10.19 | 6.70 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 141123.94 | 1671097.78 | 30-MAR-15:20 | 9.86 | 6.70 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 267702.78 | 1906410.30 | 19-APR-14:50 | 10.31 | 8.12 | 0.00 | 0.00 | 01-APR-00:10 |
May | 490744.05 | 1801466.89 | 23-MAY-13:50 | 10.11 | 6.70 | 0.00 | 0.00 | 01-MAY-00:03 |
June | 709297.85 | 2392722.91 | 29-JUN-05:04 | 11.23 | 6.70 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 778281.20 | 2174380.29 | 01-JUL-04:14 | 10.81 | 6.70 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 870530.71 | 2626680.08 | 23-AUG-05:02 | 11.67 | 6.70 | 0.00 | 0.00 | 01-AUG-00:03 |
September | 577925.15 | 1995435.85 | 16-SEP-16:07 | 10.48 | 6.70 | 0.00 | 0.00 | 01-SEP-00:03 |
October | 252402.85 | 2203332.40 | 19-OCT-04:15 | 10.87 | 6.70 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 100922.14 | 954441.18 | 02-NOV-13:10 | 10.31 | 6.70 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 34607.14 | 822898.89 | 12-DEC-14:00 | 9.81 | 6.70 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 359815.78 | 0.00 | ||||||
Minimum of Months | 17009.14 | 488358.06 | 8.55 | 6.70 | 0.00 | 0.00 | ||
Maximum of Months | 870530.71 | 2626680.08 | 11.67 | 8.12 | 0.00 | 0.00 |
Report: CondLoopDemandReportMonthly
For: COOLSYS1_DEMAND
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 16055.10 | 516312.01 | 31-JAN-15:10 | 12.33 | 6.70 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 53010.66 | 919275.08 | 28-FEB-15:00 | 15.72 | 6.70 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 138450.63 | 1668459.68 | 30-MAR-15:10 | 13.32 | 6.70 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 264660.88 | 2148705.67 | 17-APR-13:30 | 13.66 | 7.70 | 0.00 | 0.00 | 01-APR-00:10 |
May | 487045.83 | 3161330.38 | 31-MAY-05:03 | 13.68 | 9.60 | 0.00 | 0.00 | 01-MAY-00:03 |
June | 706507.76 | 3877694.25 | 23-JUN-05:03 | 14.04 | 10.36 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 774668.38 | 3697342.95 | 14-JUL-04:12 | 13.89 | 10.19 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 866204.06 | 3967123.13 | 12-AUG-05:02 | 14.21 | 10.45 | 0.00 | 0.00 | 01-AUG-00:03 |
September | 575205.69 | 3790786.16 | 05-SEP-05:02 | 13.90 | 10.28 | 0.00 | 0.00 | 01-SEP-00:03 |
October | 249339.60 | 3450528.93 | 19-OCT-05:03 | 13.70 | 9.94 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 98694.54 | 958289.25 | 04-NOV-05:03 | 13.51 | 6.70 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 33410.21 | 819965.94 | 12-DEC-14:00 | 14.05 | 6.70 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 357141.79 | 0.00 | ||||||
Minimum of Months | 16055.10 | 516312.01 | 12.33 | 6.70 | 0.00 | 0.00 | ||
Maximum of Months | 866204.06 | 3967123.13 | 15.72 | 10.45 | 0.00 | 0.00 |
Report: CondLoopDemandReportMonthly
For: SINGLE WATER PLANT LOOP
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 164780.08 | 419385.64 | 31-JAN-15:00 | 26.70 | 22.84 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 338212.29 | 861722.75 | 28-FEB-15:00 | 35.39 | 28.26 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 577006.00 | 1257343.65 | 30-MAR-16:00 | 43.04 | 32.62 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 892545.52 | 1531128.30 | 17-APR-16:00 | 48.28 | 35.06 | 0.00 | 0.00 | 01-APR-00:10 |
May | 438384.66 | 967370.60 | 30-MAY-15:00 | 37.45 | 32.75 | 0.00 | 0.00 | 01-MAY-00:03 |
June | 859896.46 | 1416932.73 | 06-JUN-15:00 | 46.10 | 38.11 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 1153484.39 | 1776718.29 | 08-JUL-16:00 | 52.93 | 41.89 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 1401418.32 | 1887269.42 | 01-AUG-16:10 | 55.02 | 41.41 | 0.00 | 0.00 | 01-AUG-00:03 |
September | 520479.85 | 1042735.33 | 07-SEP-16:00 | 38.91 | 33.97 | 0.00 | 0.00 | 01-SEP-00:03 |
October | 470403.28 | 1165752.88 | 10-OCT-16:00 | 41.28 | 33.56 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 539997.72 | 1036569.58 | 05-NOV-16:00 | 38.79 | 28.93 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 617356.57 | 1186294.93 | 12-DEC-15:00 | 41.68 | 28.76 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 666754.42 | 0.00 | ||||||
Minimum of Months | 164780.08 | 419385.64 | 26.70 | 22.84 | 0.00 | 0.00 | ||
Maximum of Months | 1401418.32 | 1887269.42 | 55.02 | 41.89 | 0.00 | 0.00 |
Report: CondLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 56.55 | 56.55 | 14850.00 | 49687.18 | 30-JAN-12:40 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 57.00 | 57.00 | 14960.05 | 49691.65 | 01-FEB-12:40 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 57.24 | 57.24 | 15317.31 | 48919.31 | 01-MAR-12:50 |
April | 0.00 | 0.00 | 01-APR-00:10 | 56.29 | 56.29 | 13611.95 | 46270.62 | 03-APR-11:50 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 58.03 | 58.03 | 13012.53 | 43150.94 | 01-MAY-11:40 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 57.47 | 57.47 | 12345.19 | 39646.21 | 01-JUN-11:30 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 57.49 | 57.49 | 10959.34 | 36965.52 | 03-JUL-12:00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 57.39 | 57.39 | 11824.71 | 36815.48 | 31-AUG-11:50 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 57.43 | 57.43 | 11655.39 | 39093.32 | 29-SEP-11:30 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 57.38 | 57.38 | 12475.73 | 42640.11 | 31-OCT-12:00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 57.45 | 57.45 | 13623.08 | 46035.21 | 30-NOV-13:00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 56.45 | 56.45 | 14016.97 | 48586.36 | 29-DEC-12:15 |
Annual Sum or Average | 0.00 | 13211.24 | ||||||
Minimum of Months | 0.00 | 0.00 | 56.29 | 56.29 | 10959.34 | 36815.48 | ||
Maximum of Months | 0.00 | 0.00 | 58.03 | 58.03 | 15317.31 | 49691.65 |
Report: CondLoopDemandReportMonthly
For: TOWERWATERSYS
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 19123.76 | 581447.72 | 19-JAN-16:00 | 22.97 | 21.10 | 4167.44 | 172700.19 | 06-JAN-12:20 |
February | 63714.38 | 1062309.43 | 28-FEB-15:10 | 24.52 | 21.10 | 3556.55 | 190795.46 | 12-FEB-04:02 |
March | 170952.14 | 2870371.58 | 30-MAR-15:20 | 25.72 | 21.83 | 2367.55 | 175814.57 | 06-MAR-07:30 |
April | 337949.50 | 3071546.89 | 18-APR-12:40 | 26.05 | 21.82 | 960.77 | 109042.00 | 25-APR-20:00 |
May | 759604.36 | 4375444.07 | 31-MAY-12:50 | 28.15 | 24.98 | 119.99 | 77238.55 | 09-MAY-21:00 |
June | 1558598.35 | 5563746.26 | 27-JUN-12:10 | 30.06 | 26.81 | 108.53 | 83178.82 | 10-JUN-06:30 |
July | 1960824.18 | 5919948.60 | 07-JUL-12:10 | 30.63 | 27.45 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 2363658.45 | 6143653.85 | 10-AUG-16:00 | 30.99 | 27.66 | 0.00 | 0.00 | 01-AUG-00:03 |
September | 1127570.91 | 5424044.31 | 06-SEP-14:00 | 29.83 | 26.55 | 92.07 | 59446.62 | 14-SEP-06:50 |
October | 401795.52 | 5016578.85 | 18-OCT-16:00 | 29.18 | 25.99 | 1177.66 | 126607.26 | 25-OCT-11:00 |
November | 117614.70 | 1278596.61 | 02-NOV-13:10 | 25.22 | 21.70 | 2376.44 | 164125.37 | 21-NOV-07:00 |
December | 35999.26 | 949970.27 | 12-DEC-14:00 | 24.16 | 21.10 | 2955.42 | 184336.09 | 01-DEC-09:30 |
Annual Sum or Average | 748237.52 | 1479.86 | ||||||
Minimum of Months | 19123.76 | 581447.72 | 22.97 | 21.10 | 0.00 | 0.00 | ||
Maximum of Months | 2363658.45 | 6143653.85 | 30.99 | 27.66 | 4167.44 | 190795.46 |
Report: ZoneTemperatureOscillationReportMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV_BOT WITH REHEAT
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.517093E+10 | 0.00 | 0.418628E+10 | 0.294665E+10 | 0.00 | 0.00 |
February | 0.231027E+10 | 0.00 | 0.129807E+11 | 0.317851E+10 | 0.00 | 0.00 |
March | 0.241335E+09 | 0.00 | 0.371894E+11 | 0.477753E+10 | 0.00 | 0.00 |
April | 0.193001E+09 | 0.00 | 0.709594E+11 | 0.550538E+10 | 0.00 | 0.00 |
May | 16828398.72 | 0.00 | 0.108026E+12 | 0.530270E+10 | 0.00 | 0.00 |
June | 3975658.35 | 0.00 | 0.153777E+12 | 0.678805E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.182750E+12 | 0.746000E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.212940E+12 | 0.891571E+10 | 0.00 | 0.00 |
September | 3131721.70 | 0.00 | 0.123099E+12 | 0.556656E+10 | 0.00 | 0.00 |
October | 0.104302E+09 | 0.00 | 0.608539E+11 | 0.491238E+10 | 0.00 | 0.00 |
November | 0.428846E+09 | 0.00 | 0.271954E+11 | 0.427493E+10 | 0.00 | 0.00 |
December | 0.125543E+10 | 0.00 | 0.103734E+11 | 0.383480E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.972805E+10 | 0.00 | 0.100433E+13 | 0.634632E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.418628E+10 | 0.294665E+10 | 0.00 | 0.00 |
Maximum of Months | 0.517093E+10 | 0.00 | 0.212940E+12 | 0.891571E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV_MID WITH REHEAT
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.239776E+12 | 0.00 | 0.349320E+11 | 0.291286E+11 | 0.00 | 0.00 |
February | 0.137032E+12 | 0.00 | 0.101155E+12 | 0.272292E+11 | 0.00 | 0.00 |
March | 0.236391E+11 | 0.00 | 0.282113E+12 | 0.332390E+11 | 0.00 | 0.00 |
April | 0.564171E+10 | 0.00 | 0.509438E+12 | 0.359464E+11 | 0.00 | 0.00 |
May | 0.432344E+09 | 0.00 | 0.944928E+12 | 0.439145E+11 | 0.00 | 0.00 |
June | 32653803.07 | 0.00 | 0.131898E+13 | 0.545407E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.149738E+13 | 0.561742E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.167177E+13 | 0.620613E+11 | 0.00 | 0.00 |
September | 70818297.44 | 0.00 | 0.107676E+13 | 0.453198E+11 | 0.00 | 0.00 |
October | 0.117939E+11 | 0.00 | 0.481617E+12 | 0.349541E+11 | 0.00 | 0.00 |
November | 0.381775E+11 | 0.00 | 0.196320E+12 | 0.283959E+11 | 0.00 | 0.00 |
December | 0.109672E+12 | 0.00 | 0.683327E+11 | 0.271162E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.566268E+12 | 0.00 | 0.818373E+13 | 0.478020E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.349320E+11 | 0.271162E+11 | 0.00 | 0.00 |
Maximum of Months | 0.239776E+12 | 0.00 | 0.167177E+13 | 0.620613E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV_TOP WITH REHEAT
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.463670E+11 | 0.00 | 0.349096E+10 | 0.362515E+10 | 0.00 | 0.00 |
February | 0.267361E+11 | 0.00 | 0.973973E+10 | 0.297419E+10 | 0.00 | 0.00 |
March | 0.583080E+10 | 0.00 | 0.277521E+11 | 0.316029E+10 | 0.00 | 0.00 |
April | 0.169135E+10 | 0.00 | 0.522745E+11 | 0.340795E+10 | 0.00 | 0.00 |
May | 0.134679E+09 | 0.00 | 0.101586E+12 | 0.446797E+10 | 0.00 | 0.00 |
June | 1316040.15 | 0.00 | 0.144690E+12 | 0.582535E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.163866E+12 | 0.608836E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.181702E+12 | 0.668440E+10 | 0.00 | 0.00 |
September | 95198126.71 | 0.00 | 0.110976E+12 | 0.441418E+10 | 0.00 | 0.00 |
October | 0.398533E+10 | 0.00 | 0.483804E+11 | 0.325250E+10 | 0.00 | 0.00 |
November | 0.107389E+11 | 0.00 | 0.183911E+11 | 0.274053E+10 | 0.00 | 0.00 |
December | 0.282137E+11 | 0.00 | 0.670704E+10 | 0.316605E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.123794E+12 | 0.00 | 0.869555E+12 | 0.498069E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.349096E+10 | 0.274053E+10 | 0.00 | 0.00 |
Maximum of Months | 0.463670E+11 | 0.00 | 0.181702E+12 | 0.668440E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: CAV_BAS
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.577388E+09 | 0.153072E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.423326E+10 | 0.136018E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.135794E+11 | 0.161156E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.290157E+11 | 0.147431E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.516525E+11 | 0.155883E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.893055E+11 | 0.155171E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.100403E+12 | 0.153962E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.120344E+12 | 0.171714E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.758328E+11 | 0.162821E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.329230E+11 | 0.161420E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.105310E+11 | 0.157980E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.307062E+10 | 0.152441E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.531468E+12 | 0.186907E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.577388E+09 | 0.136018E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.120344E+12 | 0.171714E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER BASEMENT
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.404237E+12 | 0.181879E+12 | 0.00 | 0.97 |
February | 0.00 | 0.00 | 0.638957E+12 | 0.215302E+12 | 0.00 | 0.68 |
March | 0.00 | 0.00 | 0.102085E+13 | 0.299815E+12 | 0.00 | 0.35 |
April | 0.00 | 0.00 | 0.129951E+13 | 0.362962E+12 | 0.00 | 0.11 |
May | 0.00 | 0.00 | 0.439737E+12 | 0.196209E+12 | 0.00 | 0.02 |
June | 0.00 | 0.00 | 0.755878E+12 | 0.276621E+12 | 0.00 | 0.01 |
July | 0.00 | 0.00 | 0.111500E+13 | 0.371789E+12 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.143165E+13 | 0.448150E+12 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.439940E+12 | 0.196076E+12 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.735762E+12 | 0.249030E+12 | 0.00 | 0.02 |
November | 0.00 | 0.00 | 0.990110E+12 | 0.287501E+12 | 0.00 | 0.45 |
December | 0.00 | 0.00 | 0.130461E+13 | 0.339088E+12 | 0.00 | 0.72 |
Annual Sum or Average | 0.00 | 0.00 | 0.105762E+14 | 0.342442E+13 | 0.00 | 3.33 |
Minimum of Months | 0.00 | 0.00 | 0.404237E+12 | 0.181879E+12 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.143165E+13 | 0.448150E+12 | 0.00 | 0.97 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER BOT
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.465160E+10 | 0.246177E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.107288E+11 | 0.348406E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.194705E+11 | 0.531880E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.255702E+11 | 0.666346E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.791182E+10 | 0.322737E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.147720E+11 | 0.493122E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.221424E+11 | 0.683188E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.290017E+11 | 0.853779E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.799851E+10 | 0.324934E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.135826E+11 | 0.424172E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.186361E+11 | 0.505856E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.247049E+11 | 0.607389E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.199171E+12 | 0.600799E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.465160E+10 | 0.246177E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.290017E+11 | 0.853779E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER MID
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.149924E+11 | 0.174414E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.788274E+11 | 0.288165E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.172583E+12 | 0.484318E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.237070E+12 | 0.623756E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.702664E+11 | 0.297384E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.138790E+12 | 0.465920E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.210471E+12 | 0.650099E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.276066E+12 | 0.813106E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.705890E+11 | 0.298062E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.116783E+12 | 0.381083E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.159460E+12 | 0.450367E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.207151E+12 | 0.532099E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.175305E+13 | 0.545877E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.149924E+11 | 0.174414E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.276066E+12 | 0.813106E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER TOP
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.799858E+09 | 0.161216E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.658263E+10 | 0.265248E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.162993E+11 | 0.470566E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.232082E+11 | 0.618861E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.692040E+10 | 0.298528E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.139675E+11 | 0.471326E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.211969E+11 | 0.657313E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.277896E+11 | 0.821479E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.685018E+10 | 0.296864E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.107524E+11 | 0.367055E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.144812E+11 | 0.427186E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.188210E+11 | 0.503012E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.167669E+12 | 0.535865E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.799858E+09 | 0.161216E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.277896E+11 | 0.821479E+10 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV_BOT WITH REHEAT
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.294665E+10 | 0.418628E+10 | 0.517093E+10 | 0.219159E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.317851E+10 | 0.129807E+11 | 0.231027E+10 | 0.110953E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.477753E+10 | 0.371894E+11 | 0.241335E+09 | 0.124455E+10 | 0.288708E+09 | 0.00 | 0.00 | 0.00 |
April | 0.550538E+10 | 0.709594E+11 | 0.193001E+09 | 0.381926E+09 | 0.593199E+09 | 0.00 | 0.00 | 0.00 |
May | 0.530270E+10 | 0.108026E+12 | 16828398.72 | 20702869.22 | 0.586447E+10 | 0.00 | 0.00 | 0.00 |
June | 0.678805E+10 | 0.153777E+12 | 3975658.35 | 0.00 | 0.266036E+11 | 0.00 | 0.00 | 0.00 |
July | 0.746000E+10 | 0.182750E+12 | 0.00 | 0.00 | 0.350468E+11 | 0.00 | 0.00 | 0.00 |
August | 0.891571E+10 | 0.212940E+12 | 0.00 | 0.00 | 0.429384E+11 | 0.00 | 0.00 | 0.00 |
September | 0.556656E+10 | 0.123099E+12 | 3131721.70 | 0.00 | 0.127434E+11 | 0.00 | 0.00 | 0.00 |
October | 0.491238E+10 | 0.608539E+11 | 0.104302E+09 | 0.466104E+09 | 0.238418E+10 | 0.00 | 0.00 | 0.00 |
November | 0.427493E+10 | 0.271954E+11 | 0.428846E+09 | 0.254092E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.383480E+10 | 0.103734E+11 | 0.125543E+10 | 0.551441E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.634632E+11 | 0.100433E+13 | 0.972805E+10 | 0.431798E+11 | 0.126463E+12 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.294665E+10 | 0.418628E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.891571E+10 | 0.212940E+12 | 0.517093E+10 | 0.219159E+11 | 0.429384E+11 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV_MID WITH REHEAT
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.291286E+11 | 0.349320E+11 | 0.239776E+12 | 0.250737E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.272292E+11 | 0.101156E+12 | 0.137032E+12 | 0.139373E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.332390E+11 | 0.282113E+12 | 0.236391E+11 | 0.246696E+11 | 0.381183E+10 | 0.00 | 0.00 | 0.00 |
April | 0.359464E+11 | 0.509438E+12 | 0.564171E+10 | 0.740231E+10 | 0.704296E+10 | 0.00 | 0.00 | 0.00 |
May | 0.439145E+11 | 0.944928E+12 | 0.432344E+09 | 0.322125E+09 | 0.605772E+11 | 0.00 | 0.00 | 0.00 |
June | 0.545407E+11 | 0.131898E+13 | 32653803.07 | 0.00 | 0.264944E+12 | 0.00 | 0.00 | 0.00 |
July | 0.561742E+11 | 0.149738E+13 | 0.00 | 0.00 | 0.348924E+12 | 0.00 | 0.00 | 0.00 |
August | 0.620613E+11 | 0.167177E+13 | 0.00 | 0.00 | 0.422334E+12 | 0.00 | 0.00 | 0.00 |
September | 0.453198E+11 | 0.107676E+13 | 70818297.44 | 0.00 | 0.129927E+12 | 0.00 | 0.00 | 0.00 |
October | 0.349541E+11 | 0.481617E+12 | 0.117939E+11 | 0.108467E+11 | 0.257868E+11 | 0.00 | 0.00 | 0.00 |
November | 0.283959E+11 | 0.196320E+12 | 0.381775E+11 | 0.522625E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.271162E+11 | 0.683327E+11 | 0.109672E+12 | 0.974947E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.478020E+12 | 0.818373E+13 | 0.566268E+12 | 0.583108E+12 | 0.126335E+13 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.271162E+11 | 0.349320E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.620613E+11 | 0.167177E+13 | 0.239776E+12 | 0.250737E+12 | 0.422334E+12 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV_TOP WITH REHEAT
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.362515E+10 | 0.349096E+10 | 0.463670E+11 | 0.268717E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.297419E+10 | 0.973973E+10 | 0.267361E+11 | 0.147281E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.316029E+10 | 0.277521E+11 | 0.583080E+10 | 0.315261E+10 | 0.196546E+09 | 0.00 | 0.00 | 0.00 |
April | 0.340795E+10 | 0.522745E+11 | 0.169135E+10 | 0.873114E+09 | 0.289121E+09 | 0.00 | 0.00 | 0.00 |
May | 0.446797E+10 | 0.101586E+12 | 0.134679E+09 | 35126206.38 | 0.450587E+10 | 0.00 | 0.00 | 0.00 |
June | 0.582535E+10 | 0.144690E+12 | 1316040.15 | 0.00 | 0.248203E+11 | 0.00 | 0.00 | 0.00 |
July | 0.608836E+10 | 0.163866E+12 | 0.00 | 0.00 | 0.335697E+11 | 0.00 | 0.00 | 0.00 |
August | 0.668440E+10 | 0.181702E+12 | 0.00 | 0.00 | 0.409296E+11 | 0.00 | 0.00 | 0.00 |
September | 0.441418E+10 | 0.110976E+12 | 95198126.71 | 0.00 | 0.122063E+11 | 0.00 | 0.00 | 0.00 |
October | 0.325250E+10 | 0.483804E+11 | 0.398533E+10 | 0.127834E+10 | 0.158903E+10 | 0.00 | 0.00 | 0.00 |
November | 0.274053E+10 | 0.183911E+11 | 0.107389E+11 | 0.559773E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.316605E+10 | 0.670704E+10 | 0.282137E+11 | 0.101870E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.498069E+11 | 0.869555E+12 | 0.123794E+12 | 0.627237E+11 | 0.118107E+12 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.274053E+10 | 0.349096E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.668440E+10 | 0.181702E+12 | 0.463670E+11 | 0.268717E+11 | 0.409296E+11 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: CAV_BAS
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.153072E+11 | 0.577388E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.136018E+11 | 0.423326E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.161156E+11 | 0.135794E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.147431E+11 | 0.290157E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.155883E+11 | 0.516525E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.155171E+11 | 0.893055E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.153962E+11 | 0.100403E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.171714E+11 | 0.120344E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.162821E+11 | 0.758328E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.161420E+11 | 0.329230E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.157980E+11 | 0.105310E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.152441E+11 | 0.307062E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.186907E+12 | 0.531468E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.136018E+11 | 0.577388E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.171714E+11 | 0.120344E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER BASEMENT
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.977848E+11 | 0.322755E+12 | 0.00 | 0.00 | 0.00 | 0.260059E+10 | 0.00 | 0.00 |
February | 0.883218E+11 | 0.513810E+12 | 0.00 | 0.00 | 0.00 | 0.182526E+10 | 0.00 | 0.00 |
March | 0.977848E+11 | 0.819754E+12 | 0.00 | 0.00 | 0.00 | 0.933001E+09 | 0.00 | 0.00 |
April | 0.946305E+11 | 0.103147E+13 | 0.00 | 0.00 | 0.00 | 0.293411E+09 | 0.00 | 0.00 |
May | 0.977848E+11 | 0.341365E+12 | 0.00 | 0.00 | 0.00 | 51890100.47 | 0.00 | 0.00 |
June | 0.946305E+11 | 0.573902E+12 | 0.00 | 0.00 | 0.00 | 14673193.97 | 0.00 | 0.00 |
July | 0.977848E+11 | 0.840997E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.977848E+11 | 0.108128E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.946305E+11 | 0.338494E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.977848E+11 | 0.584559E+12 | 0.00 | 0.00 | 0.00 | 41573922.38 | 0.00 | 0.00 |
November | 0.946305E+11 | 0.798455E+12 | 0.00 | 0.00 | 0.00 | 0.121137E+10 | 0.00 | 0.00 |
December | 0.977848E+11 | 0.106524E+13 | 0.00 | 0.00 | 0.00 | 0.192684E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.115134E+13 | 0.831209E+13 | 0.00 | 0.00 | 0.00 | 0.889861E+10 | 0.00 | 0.00 |
Minimum of Months | 0.883218E+11 | 0.322755E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.977848E+11 | 0.108128E+13 | 0.00 | 0.00 | 0.00 | 0.260059E+10 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER BOT
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.147651E+10 | 0.366635E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.133363E+10 | 0.857835E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.147651E+10 | 0.156283E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.142889E+10 | 0.203356E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.147651E+10 | 0.616096E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.142889E+10 | 0.112697E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.147651E+10 | 0.167870E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.147651E+10 | 0.219404E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.142889E+10 | 0.617805E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.147651E+10 | 0.108174E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.142889E+10 | 0.150064E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.147651E+10 | 0.201076E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.173848E+11 | 0.156476E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.133363E+10 | 0.366635E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.147651E+10 | 0.219404E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER MID
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.140759E+11 | 0.116269E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.127137E+11 | 0.627246E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.140759E+11 | 0.138227E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.136218E+11 | 0.188317E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.140759E+11 | 0.546039E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.136218E+11 | 0.105820E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.140759E+11 | 0.159537E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.140759E+11 | 0.208831E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.136218E+11 | 0.544046E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.140759E+11 | 0.927509E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.136218E+11 | 0.128045E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.140759E+11 | 0.168017E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.165732E+12 | 0.137290E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.127137E+11 | 0.116269E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.140759E+11 | 0.208831E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER TOP
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.143387E+10 | 0.621563E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.129511E+10 | 0.522525E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.143387E+10 | 0.130275E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.138761E+10 | 0.184072E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.143387E+10 | 0.536898E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.138761E+10 | 0.106418E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.143387E+10 | 0.160576E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.143387E+10 | 0.210087E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.138761E+10 | 0.526916E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.143387E+10 | 0.851575E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.138761E+10 | 0.115970E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.143387E+10 | 0.152248E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.168826E+11 | 0.130965E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.129511E+10 | 0.621563E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.143387E+10 | 0.210087E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV_BOT WITH REHEAT
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.294665E+10 | 0.517093E+10 | 0.418628E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.317851E+10 | 0.231027E+10 | 0.129807E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.477753E+10 | 0.241335E+09 | 0.371894E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.550538E+10 | 0.193001E+09 | 0.709594E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.530270E+10 | 16828398.72 | 0.108026E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.678805E+10 | 3975658.35 | 0.153777E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.746000E+10 | 0.00 | 0.182750E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.891571E+10 | 0.00 | 0.212940E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.556656E+10 | 3131721.70 | 0.123099E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.491238E+10 | 0.104302E+09 | 0.608539E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.427493E+10 | 0.428846E+09 | 0.271954E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.383480E+10 | 0.125543E+10 | 0.103734E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.634632E+11 | 0.972805E+10 | 0.100433E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.294665E+10 | 0.00 | 0.418628E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.891571E+10 | 0.517093E+10 | 0.212940E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV_MID WITH REHEAT
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.291286E+11 | 0.239776E+12 | 0.349320E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.272292E+11 | 0.137032E+12 | 0.101155E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.332390E+11 | 0.236391E+11 | 0.282113E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.359464E+11 | 0.564171E+10 | 0.509438E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.439145E+11 | 0.432344E+09 | 0.944928E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.545407E+11 | 32653803.07 | 0.131898E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.561742E+11 | 0.00 | 0.149738E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.620613E+11 | 0.00 | 0.167177E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.453198E+11 | 70818297.44 | 0.107676E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.349541E+11 | 0.117939E+11 | 0.481617E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.283959E+11 | 0.381775E+11 | 0.196320E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.271162E+11 | 0.109672E+12 | 0.683327E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.478020E+12 | 0.566268E+12 | 0.818373E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.271162E+11 | 0.00 | 0.349320E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.620613E+11 | 0.239776E+12 | 0.167177E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV_TOP WITH REHEAT
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.362515E+10 | 0.463670E+11 | 0.349096E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.297419E+10 | 0.267361E+11 | 0.973973E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.316029E+10 | 0.583080E+10 | 0.277521E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.340795E+10 | 0.169135E+10 | 0.522745E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.446797E+10 | 0.134679E+09 | 0.101586E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.582535E+10 | 1316040.15 | 0.144690E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.608836E+10 | 0.00 | 0.163866E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.668440E+10 | 0.00 | 0.181702E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.441418E+10 | 95198126.71 | 0.110976E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.325250E+10 | 0.398533E+10 | 0.483804E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.274053E+10 | 0.107389E+11 | 0.183911E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.316605E+10 | 0.282137E+11 | 0.670704E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.498069E+11 | 0.123794E+12 | 0.869555E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.274053E+10 | 0.00 | 0.349096E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.668440E+10 | 0.463670E+11 | 0.181702E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: CAV_BAS
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.153072E+11 | 0.00 | 0.577388E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.136018E+11 | 0.00 | 0.423326E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.161156E+11 | 0.00 | 0.135794E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.147431E+11 | 0.00 | 0.290157E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.155883E+11 | 0.00 | 0.516525E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.155171E+11 | 0.00 | 0.893055E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.153962E+11 | 0.00 | 0.100403E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.171714E+11 | 0.00 | 0.120344E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.162821E+11 | 0.00 | 0.758328E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.161420E+11 | 0.00 | 0.329230E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.157980E+11 | 0.00 | 0.105310E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.152441E+11 | 0.00 | 0.307062E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.186907E+12 | 0.00 | 0.531468E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.136018E+11 | 0.00 | 0.577388E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.171714E+11 | 0.00 | 0.120344E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER BASEMENT
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.977848E+11 | 0.00 | 0.404237E+12 | 0.00 | 0.814821E+11 | 0.00 | 0.00 | 0.00 | 0.261229E+10 | 0.00 | 0.00 | 0.00 |
February | 0.883218E+11 | 0.00 | 0.638957E+12 | 0.00 | 0.125147E+12 | 0.00 | 0.00 | 0.00 | 0.183348E+10 | 0.00 | 0.00 | 0.00 |
March | 0.977848E+11 | 0.00 | 0.102085E+13 | 0.00 | 0.201093E+12 | 0.00 | 0.00 | 0.00 | 0.937201E+09 | 0.00 | 0.00 | 0.00 |
April | 0.946305E+11 | 0.00 | 0.129951E+13 | 0.00 | 0.268037E+12 | 0.00 | 0.00 | 0.00 | 0.294732E+09 | 0.00 | 0.00 | 0.00 |
May | 0.977848E+11 | 0.00 | 0.439737E+12 | 0.00 | 0.983718E+11 | 0.00 | 0.00 | 0.00 | 52123678.84 | 0.00 | 0.00 | 0.00 |
June | 0.946305E+11 | 0.00 | 0.755878E+12 | 0.00 | 0.181976E+12 | 0.00 | 0.00 | 0.00 | 14739243.96 | 0.00 | 0.00 | 0.00 |
July | 0.977848E+11 | 0.00 | 0.111500E+13 | 0.00 | 0.274004E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.977848E+11 | 0.00 | 0.143165E+13 | 0.00 | 0.350365E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.946305E+11 | 0.00 | 0.439940E+12 | 0.00 | 0.101446E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.977848E+11 | 0.00 | 0.735762E+12 | 0.00 | 0.151203E+12 | 0.00 | 0.00 | 0.00 | 41761063.45 | 0.00 | 0.00 | 0.00 |
November | 0.946305E+11 | 0.00 | 0.990110E+12 | 0.00 | 0.191654E+12 | 0.00 | 0.00 | 0.00 | 0.121683E+10 | 0.00 | 0.00 | 0.00 |
December | 0.977848E+11 | 0.00 | 0.130461E+13 | 0.00 | 0.239368E+12 | 0.00 | 0.00 | 0.00 | 0.193551E+10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.115134E+13 | 0.00 | 0.105762E+14 | 0.00 | 0.226415E+13 | 0.00 | 0.00 | 0.00 | 0.893867E+10 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.883218E+11 | 0.00 | 0.404237E+12 | 0.00 | 0.814821E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.977848E+11 | 0.00 | 0.143165E+13 | 0.00 | 0.350365E+12 | 0.00 | 0.00 | 0.00 | 0.261229E+10 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER BOT
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.147651E+10 | 0.00 | 0.465160E+10 | 0.00 | 0.985252E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.133363E+10 | 0.00 | 0.107288E+11 | 0.00 | 0.215044E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.147651E+10 | 0.00 | 0.194705E+11 | 0.00 | 0.384228E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.142889E+10 | 0.00 | 0.255702E+11 | 0.00 | 0.523457E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.147651E+10 | 0.00 | 0.791182E+10 | 0.00 | 0.175085E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.142889E+10 | 0.00 | 0.147720E+11 | 0.00 | 0.350234E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.147651E+10 | 0.00 | 0.221424E+11 | 0.00 | 0.535536E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.147651E+10 | 0.00 | 0.290017E+11 | 0.00 | 0.706128E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.142889E+10 | 0.00 | 0.799851E+10 | 0.00 | 0.182046E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.147651E+10 | 0.00 | 0.135826E+11 | 0.00 | 0.276521E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.142889E+10 | 0.00 | 0.186361E+11 | 0.00 | 0.362968E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.147651E+10 | 0.00 | 0.247049E+11 | 0.00 | 0.459738E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.173848E+11 | 0.00 | 0.199171E+12 | 0.00 | 0.426951E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.133363E+10 | 0.00 | 0.465160E+10 | 0.00 | 0.985252E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.147651E+10 | 0.00 | 0.290017E+11 | 0.00 | 0.706128E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER MID
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.140759E+11 | 0.00 | 0.149924E+11 | 0.00 | 0.336553E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.127137E+11 | 0.00 | 0.788274E+11 | 0.00 | 0.161028E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.140759E+11 | 0.00 | 0.172583E+12 | 0.00 | 0.343559E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.136218E+11 | 0.00 | 0.237070E+12 | 0.00 | 0.487538E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.140759E+11 | 0.00 | 0.702664E+11 | 0.00 | 0.156625E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.136218E+11 | 0.00 | 0.138790E+12 | 0.00 | 0.329702E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.140759E+11 | 0.00 | 0.210471E+12 | 0.00 | 0.509340E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.140759E+11 | 0.00 | 0.276066E+12 | 0.00 | 0.672347E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.136218E+11 | 0.00 | 0.705890E+11 | 0.00 | 0.161844E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.140759E+11 | 0.00 | 0.116783E+12 | 0.00 | 0.240325E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.136218E+11 | 0.00 | 0.159460E+12 | 0.00 | 0.314149E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.140759E+11 | 0.00 | 0.207151E+12 | 0.00 | 0.391340E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.165732E+12 | 0.00 | 0.175305E+13 | 0.00 | 0.380145E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.127137E+11 | 0.00 | 0.149924E+11 | 0.00 | 0.336553E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.140759E+11 | 0.00 | 0.276066E+12 | 0.00 | 0.672347E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER TOP
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.143387E+10 | 0.00 | 0.799858E+09 | 0.00 | 0.178295E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.129511E+10 | 0.00 | 0.658263E+10 | 0.00 | 0.135738E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.143387E+10 | 0.00 | 0.162993E+11 | 0.00 | 0.327179E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.138761E+10 | 0.00 | 0.232082E+11 | 0.00 | 0.480100E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.143387E+10 | 0.00 | 0.692040E+10 | 0.00 | 0.155142E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.138761E+10 | 0.00 | 0.139675E+11 | 0.00 | 0.332565E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.143387E+10 | 0.00 | 0.211969E+11 | 0.00 | 0.513926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.143387E+10 | 0.00 | 0.277896E+11 | 0.00 | 0.678092E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.138761E+10 | 0.00 | 0.685018E+10 | 0.00 | 0.158102E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.143387E+10 | 0.00 | 0.107524E+11 | 0.00 | 0.223668E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.138761E+10 | 0.00 | 0.144812E+11 | 0.00 | 0.288425E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.143387E+10 | 0.00 | 0.188210E+11 | 0.00 | 0.359626E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.168826E+11 | 0.00 | 0.167669E+12 | 0.00 | 0.367039E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.129511E+10 | 0.00 | 0.799858E+09 | 0.00 | 0.178295E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.143387E+10 | 0.00 | 0.277896E+11 | 0.00 | 0.678092E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.101900E+10 | 0.00 | 0.00 | 0.105820E+09 | 0.00 | 0.00 | 0.653207E+11 | 0.00 | 0.64 |
February | 0.330723E+09 | 449176.32 | 0.00 | 94928724.33 | 0.00 | 0.00 | 0.578316E+11 | 0.00 | 0.87 |
March | 0.150949E+09 | 0.107966E+09 | 0.00 | 0.113496E+09 | 670166.99 | 0.00 | 0.648323E+11 | 0.00 | 1.27 |
April | 73321821.64 | 0.321667E+09 | 0.00 | 91661575.80 | 10030843.58 | 0.00 | 0.428988E+11 | 0.00 | 1.24 |
May | 33795339.86 | 0.220005E+10 | 0.00 | 77506168.95 | 21605051.33 | 0.00 | 0.278055E+11 | 0.00 | 1.22 |
June | 10244523.16 | 0.145259E+11 | 0.00 | 33388678.96 | 71580483.94 | 0.00 | 0.726278E+10 | 0.00 | 0.63 |
July | 25015359.81 | 0.211916E+11 | 0.00 | 16152730.07 | 0.227921E+09 | 0.00 | 0.283546E+10 | 0.00 | 0.42 |
August | 9405084.40 | 0.281582E+11 | 0.00 | 5889383.19 | 0.185172E+09 | 0.00 | 0.791382E+09 | 0.00 | 0.39 |
September | 0.159215E+09 | 0.880009E+10 | 0.00 | 63747298.40 | 71545933.63 | 0.00 | 0.185187E+11 | 0.00 | 0.96 |
October | 0.224534E+09 | 0.245005E+10 | 0.00 | 0.113123E+09 | 0.00 | 0.00 | 0.560769E+11 | 0.00 | 1.19 |
November | 0.300342E+09 | 802498.52 | 0.00 | 0.138650E+09 | 0.00 | 0.00 | 0.731505E+11 | 0.00 | 1.26 |
December | 0.482178E+09 | 0.00 | 0.00 | 0.135464E+09 | 0.00 | 0.00 | 0.744840E+11 | 0.00 | 0.93 |
Annual Sum or Average | 0.281873E+10 | 0.777568E+11 | 0.00 | 0.989828E+09 | 0.588525E+09 | 0.00 | 0.491808E+12 | 0.00 | 0.92 |
Minimum of Months | 9405084.40 | 0.00 | 0.00 | 5889383.19 | 0.00 | 0.00 | 0.791382E+09 | 0.00 | 0.39 |
Maximum of Months | 0.101900E+10 | 0.281582E+11 | 0.00 | 0.138650E+09 | 0.227921E+09 | 0.00 | 0.744840E+11 | 0.00 | 1.27 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.144991E+11 | 0.00 | 0.00 | 46415631.92 | 0.00 | 0.00 | 0.289492E+11 | 0.00 | 0.50 |
February | 0.877179E+10 | 0.00 | 0.00 | 57113447.95 | 0.00 | 0.00 | 0.312294E+11 | 0.00 | 0.61 |
March | 0.411254E+10 | 0.244120E+09 | 0.00 | 92868929.30 | 406571.68 | 0.00 | 0.426588E+11 | 0.00 | 0.79 |
April | 0.274881E+10 | 0.919056E+09 | 0.00 | 88702607.47 | 67574580.62 | 0.00 | 0.277810E+11 | 0.00 | 0.80 |
May | 0.706555E+09 | 0.486296E+10 | 0.00 | 42677073.43 | 90257903.97 | 0.00 | 0.902903E+10 | 0.00 | 0.60 |
June | 0.315377E+09 | 0.135287E+11 | 0.00 | 18238571.93 | 0.155556E+09 | 0.00 | 0.400054E+10 | 0.00 | 0.50 |
July | 15912228.91 | 0.185859E+11 | 0.00 | 815707.57 | 0.406328E+09 | 0.00 | 21568629.94 | 0.00 | 0.38 |
August | 0.00 | 0.233016E+11 | 0.00 | 0.00 | 0.215716E+09 | 0.00 | 0.00 | 0.00 | 0.41 |
September | 0.340680E+09 | 0.108176E+11 | 0.00 | 34306787.52 | 0.302448E+09 | 0.00 | 0.638039E+10 | 0.00 | 0.55 |
October | 0.125223E+10 | 0.408789E+10 | 0.00 | 74230729.98 | 27314227.34 | 0.00 | 0.333522E+11 | 0.00 | 0.68 |
November | 0.208216E+10 | 0.274471E+09 | 0.00 | 93815634.48 | 27784916.62 | 0.00 | 0.445919E+11 | 0.00 | 0.73 |
December | 0.339536E+10 | 11052516.58 | 0.00 | 89929754.46 | 0.00 | 0.00 | 0.477826E+11 | 0.00 | 0.63 |
Annual Sum or Average | 0.382405E+11 | 0.766334E+11 | 0.00 | 0.639115E+09 | 0.129339E+10 | 0.00 | 0.275777E+12 | 0.00 | 0.60 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.38 |
Maximum of Months | 0.144991E+11 | 0.233016E+11 | 0.00 | 93815634.48 | 0.406328E+09 | 0.00 | 0.477826E+11 | 0.00 | 0.80 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.334023E+12 | 0.00 | 0.00 | 9026289.66 | 0.190565E+09 | 0.326975E+10 | 0.184095E+11 | 0.00 | 0.48 |
February | 0.246467E+12 | 0.00 | 0.00 | 92014225.46 | 0.00 | 0.203494E+10 | 0.563092E+11 | 0.00 | 0.52 |
March | 0.130778E+12 | 0.130248E+10 | 0.00 | 0.374773E+09 | 0.805599E+09 | 0.00 | 0.199533E+12 | 0.00 | 0.61 |
April | 0.625592E+11 | 0.681159E+10 | 0.00 | 0.423873E+09 | 0.293669E+10 | 0.00 | 0.151895E+12 | 0.00 | 0.62 |
May | 0.164444E+11 | 0.432833E+11 | 0.00 | 0.258364E+09 | 0.451859E+10 | 0.00 | 0.653370E+11 | 0.00 | 0.55 |
June | 0.454693E+10 | 0.128011E+12 | 0.00 | 0.117558E+09 | 0.481967E+10 | 0.00 | 0.311376E+11 | 0.00 | 0.48 |
July | 0.169530E+09 | 0.172359E+12 | 0.00 | 5040012.76 | 0.122279E+11 | 0.00 | 0.229960E+09 | 0.00 | 0.38 |
August | 21882970.72 | 0.221797E+12 | 0.00 | 8378952.15 | 0.813834E+10 | 0.00 | 44761612.29 | 0.00 | 0.42 |
September | 0.949570E+10 | 0.946962E+11 | 0.00 | 0.217887E+09 | 0.126819E+11 | 0.00 | 0.467783E+11 | 0.00 | 0.52 |
October | 0.876430E+11 | 0.350594E+11 | 0.00 | 0.319954E+09 | 0.320519E+10 | 0.00 | 0.163595E+12 | 0.00 | 0.55 |
November | 0.134234E+12 | 0.707273E+09 | 0.00 | 0.294093E+09 | 0.335383E+10 | 0.00 | 0.173032E+12 | 0.00 | 0.54 |
December | 0.262178E+12 | 24700114.97 | 0.00 | 86061920.22 | 0.00 | 41633170.62 | 0.731915E+11 | 0.00 | 0.49 |
Annual Sum or Average | 0.128856E+13 | 0.704052E+12 | 0.00 | 0.220702E+10 | 0.528782E+11 | 0.534632E+10 | 0.979493E+12 | 0.00 | 0.51 |
Minimum of Months | 21882970.72 | 0.00 | 0.00 | 5040012.76 | 0.00 | 0.00 | 44761612.29 | 0.00 | 0.38 |
Maximum of Months | 0.334023E+12 | 0.221797E+12 | 0.00 | 0.423873E+09 | 0.126819E+11 | 0.326975E+10 | 0.199533E+12 | 0.00 | 0.62 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.276033E+11 | 0.00 | 0.00 | 281951.57 | 19702421.96 | 0.363730E+10 | 0.382454E+09 | 0.00 | 0.49 |
February | 0.237196E+11 | 0.00 | 0.00 | 3152817.27 | 1692341.95 | 0.135960E+10 | 0.185255E+10 | 0.00 | 0.51 |
March | 0.192416E+11 | 0.106864E+09 | 0.00 | 17733968.69 | 67864604.28 | 52247763.72 | 0.936386E+10 | 0.00 | 0.58 |
April | 0.879558E+10 | 0.575288E+09 | 0.00 | 31749370.91 | 0.352524E+09 | 0.00 | 0.101289E+11 | 0.00 | 0.60 |
May | 0.242596E+10 | 0.412716E+10 | 0.00 | 21616360.17 | 0.668751E+09 | 0.00 | 0.464066E+10 | 0.00 | 0.54 |
June | 0.941974E+09 | 0.129850E+11 | 0.00 | 10124200.07 | 0.317470E+09 | 0.00 | 0.227199E+10 | 0.00 | 0.48 |
July | 8602387.56 | 0.172847E+11 | 0.00 | 354237.70 | 0.106986E+10 | 0.00 | 12251189.56 | 0.00 | 0.38 |
August | 5947.66 | 0.224566E+11 | 0.00 | 0.00 | 0.328044E+09 | 0.00 | 0.00 | 0.00 | 0.42 |
September | 0.165672E+10 | 0.868933E+10 | 0.00 | 17148842.89 | 0.210450E+10 | 0.00 | 0.294241E+10 | 0.00 | 0.51 |
October | 0.136693E+11 | 0.368982E+10 | 0.00 | 13250298.16 | 0.484792E+09 | 29530077.42 | 0.761415E+10 | 0.00 | 0.52 |
November | 0.220898E+11 | 266259.81 | 0.00 | 6580797.07 | 0.484253E+09 | 0.370712E+09 | 0.367214E+10 | 0.00 | 0.52 |
December | 0.281610E+11 | 4070059.83 | 0.00 | 1769390.94 | 0.00 | 0.146825E+10 | 0.877486E+09 | 0.00 | 0.50 |
Annual Sum or Average | 0.148313E+12 | 0.699190E+11 | 0.00 | 0.123762E+09 | 0.589946E+10 | 0.691764E+10 | 0.437588E+11 | 0.00 | 0.50 |
Minimum of Months | 5947.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.38 |
Maximum of Months | 0.281610E+11 | 0.224566E+11 | 0.00 | 31749370.91 | 0.210450E+10 | 0.363730E+10 | 0.101289E+11 | 0.00 | 0.60 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.384064E+10 | 0.00 | 0.00 | 259021.66 | 0.00 | 0.863978E+09 | 0.179688E+09 | 0.00 | 0.45 |
February | 0.341301E+10 | 0.00 | 0.00 | 1141663.58 | 0.00 | 0.293812E+09 | 0.548899E+09 | 0.00 | 0.52 |
March | 0.277702E+10 | 34041146.64 | 0.00 | 3728352.76 | 51133.21 | 0.00 | 0.187012E+10 | 0.00 | 0.66 |
April | 0.149578E+10 | 0.137253E+09 | 0.00 | 5660214.50 | 8498636.60 | 0.00 | 0.165899E+10 | 0.00 | 0.75 |
May | 0.418589E+09 | 0.763428E+09 | 0.00 | 2897850.25 | 12550063.92 | 0.00 | 0.666715E+09 | 0.00 | 0.64 |
June | 0.138814E+09 | 0.243804E+10 | 0.00 | 1709903.22 | 19563727.36 | 0.00 | 0.374718E+09 | 0.00 | 0.68 |
July | 2591290.25 | 0.336761E+10 | 0.00 | 41934.49 | 51102543.29 | 0.00 | 1828583.84 | 0.00 | 0.55 |
August | 0.00 | 0.400830E+10 | 0.00 | 0.00 | 27129843.19 | 0.00 | 0.00 | 0.00 | 0.58 |
September | 0.305528E+09 | 0.155684E+10 | 0.00 | 2379377.13 | 38313063.99 | 0.00 | 0.421783E+09 | 0.00 | 0.58 |
October | 0.203161E+10 | 0.543163E+09 | 0.00 | 2407015.40 | 3435222.09 | 0.00 | 0.130479E+10 | 0.00 | 0.56 |
November | 0.291050E+10 | 26306272.71 | 0.00 | 2505039.97 | 8481743.19 | 23445406.04 | 0.138300E+10 | 0.00 | 0.55 |
December | 0.421012E+10 | 1239430.61 | 0.00 | 907882.58 | 0.00 | 94932130.17 | 0.581842E+09 | 0.00 | 0.48 |
Annual Sum or Average | 0.215442E+11 | 0.128762E+11 | 0.00 | 23638255.53 | 0.169126E+09 | 0.127617E+10 | 0.899238E+10 | 0.00 | 0.58 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.45 |
Maximum of Months | 0.421012E+10 | 0.400830E+10 | 0.00 | 5660214.50 | 51102543.29 | 0.863978E+09 | 0.187012E+10 | 0.00 | 0.75 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.353347E+10 | 0.00 | 0.00 | 124878.40 | 0.00 | 0.685894E+09 | 0.174228E+09 | 0.00 | 0.62 |
February | 0.292530E+10 | 0.00 | 0.00 | 1683526.52 | 0.00 | 0.239690E+09 | 0.830163E+09 | 0.00 | 0.74 |
March | 0.248815E+10 | 21637344.48 | 0.00 | 3974071.44 | 3738605.96 | 376917.98 | 0.199921E+10 | 0.00 | 0.94 |
April | 0.133563E+10 | 87549845.32 | 0.00 | 6138805.72 | 10354542.40 | 0.00 | 0.191722E+10 | 0.00 | 1.09 |
May | 0.387859E+09 | 0.632486E+09 | 0.00 | 3331424.48 | 34756520.20 | 0.00 | 0.819409E+09 | 0.00 | 0.95 |
June | 0.141462E+09 | 0.192766E+10 | 0.00 | 1996633.46 | 18939204.27 | 0.00 | 0.446610E+09 | 0.00 | 0.89 |
July | 2644300.55 | 0.269734E+10 | 0.00 | 9120.04 | 63974644.42 | 0.00 | 1046984.01 | 0.00 | 0.69 |
August | 0.00 | 0.294878E+10 | 0.00 | 0.00 | 62259346.13 | 0.00 | 0.00 | 0.00 | 0.68 |
September | 0.332003E+09 | 0.131492E+10 | 0.00 | 2373138.04 | 69215902.66 | 0.00 | 0.442369E+09 | 0.00 | 0.83 |
October | 0.177092E+10 | 0.399761E+09 | 0.00 | 3122182.50 | 16995274.48 | 0.00 | 0.157231E+10 | 0.00 | 0.82 |
November | 0.261332E+10 | 7473494.48 | 0.00 | 2144655.74 | 20712936.68 | 29347596.19 | 0.128499E+10 | 0.00 | 0.76 |
December | 0.376762E+10 | 717349.01 | 0.00 | 766704.00 | 0.00 | 0.112513E+09 | 0.512085E+09 | 0.00 | 0.66 |
Annual Sum or Average | 0.192984E+11 | 0.100383E+11 | 0.00 | 25665140.33 | 0.300947E+09 | 0.106782E+10 | 0.999964E+10 | 0.00 | 0.81 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.62 |
Maximum of Months | 0.376762E+10 | 0.294878E+10 | 0.00 | 6138805.72 | 69215902.66 | 0.685894E+09 | 0.199921E+10 | 0.00 | 1.09 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.267327E+10 | 0.00 | 0.00 | 4786404.97 | 0.00 | 0.786006E+09 | 0.299978E+10 | 0.00 | 0.57 |
February | 0.255573E+10 | 0.00 | 0.00 | 6971240.62 | 0.00 | 0.259894E+09 | 0.297532E+10 | 0.00 | 0.75 |
March | 0.223076E+10 | 49068997.11 | 0.00 | 9129526.37 | 52139.14 | 427055.04 | 0.405838E+10 | 0.00 | 0.95 |
April | 0.151588E+10 | 0.151580E+09 | 0.00 | 8198566.82 | 8665829.33 | 0.00 | 0.223358E+10 | 0.00 | 0.95 |
May | 0.508005E+09 | 0.841848E+09 | 0.00 | 2895990.56 | 15617793.71 | 0.00 | 0.642247E+09 | 0.00 | 0.71 |
June | 0.204712E+09 | 0.244208E+10 | 0.00 | 1478228.40 | 19948602.39 | 0.00 | 0.292481E+09 | 0.00 | 0.68 |
July | 2683031.55 | 0.343320E+10 | 0.00 | 35103.63 | 54639906.37 | 0.00 | 1694201.40 | 0.00 | 0.57 |
August | 0.00 | 0.452746E+10 | 0.00 | 0.00 | 27663565.57 | 0.00 | 0.00 | 0.00 | 0.67 |
September | 0.320567E+09 | 0.194977E+10 | 0.00 | 3676755.27 | 39582794.95 | 0.00 | 0.559458E+09 | 0.00 | 0.78 |
October | 0.155666E+10 | 0.721265E+09 | 0.00 | 8970598.55 | 4503173.40 | 0.00 | 0.372159E+10 | 0.00 | 0.94 |
November | 0.199718E+10 | 23451877.66 | 0.00 | 11371052.49 | 12688282.81 | 38564034.54 | 0.469575E+10 | 0.00 | 0.92 |
December | 0.277962E+10 | 1399896.62 | 0.00 | 8375833.62 | 0.00 | 0.174292E+09 | 0.453659E+10 | 0.00 | 0.76 |
Annual Sum or Average | 0.163451E+11 | 0.141411E+11 | 0.00 | 65889301.29 | 0.183362E+09 | 0.125918E+10 | 0.267169E+11 | 0.00 | 0.77 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.57 |
Maximum of Months | 0.277962E+10 | 0.452746E+10 | 0.00 | 11371052.49 | 54639906.37 | 0.786006E+09 | 0.469575E+10 | 0.00 | 0.95 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.461399E+10 | 0.00 | 0.00 | 844530.57 | 0.00 | 0.273996E+09 | 0.708400E+09 | 0.00 | 0.79 |
February | 0.324862E+10 | 0.00 | 0.00 | 3378919.96 | 0.00 | 61070993.61 | 0.176582E+10 | 0.00 | 0.98 |
March | 0.140220E+10 | 51153279.86 | 0.00 | 10677433.85 | 58036.76 | 0.00 | 0.473793E+10 | 0.00 | 1.43 |
April | 0.527004E+09 | 0.181771E+09 | 0.00 | 14417221.78 | 6769504.37 | 0.00 | 0.396066E+10 | 0.00 | 1.72 |
May | 0.336493E+09 | 0.803330E+09 | 0.00 | 3929876.24 | 4040789.94 | 0.00 | 0.945352E+09 | 0.00 | 1.15 |
June | 73113113.30 | 0.255440E+10 | 0.00 | 2408226.82 | 15970952.68 | 0.00 | 0.516933E+09 | 0.00 | 1.16 |
July | 1766263.39 | 0.375742E+10 | 0.00 | 102894.12 | 39159920.92 | 0.00 | 3823712.28 | 0.00 | 0.97 |
August | 0.00 | 0.501801E+10 | 0.00 | 0.00 | 5988520.16 | 0.00 | 0.00 | 0.00 | 1.12 |
September | 0.255545E+09 | 0.165805E+10 | 0.00 | 3033593.67 | 34193409.49 | 0.00 | 0.549499E+09 | 0.00 | 1.01 |
October | 0.134361E+10 | 0.590040E+09 | 0.00 | 6025621.10 | 3899015.48 | 0.00 | 0.288430E+10 | 0.00 | 1.13 |
November | 0.160307E+10 | 36625756.10 | 0.00 | 7354991.88 | 3966204.82 | 0.00 | 0.390325E+10 | 0.00 | 1.14 |
December | 0.232418E+10 | 1463339.73 | 0.00 | 5695307.36 | 0.00 | 0.00 | 0.386880E+10 | 0.00 | 0.98 |
Annual Sum or Average | 0.157296E+11 | 0.146523E+11 | 0.00 | 57868617.35 | 0.114046E+09 | 0.335067E+09 | 0.238448E+11 | 0.00 | 1.13 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.79 |
Maximum of Months | 0.461399E+10 | 0.501801E+10 | 0.00 | 14417221.78 | 39159920.92 | 0.273996E+09 | 0.473793E+10 | 0.00 | 1.72 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.113106E+11 | 0.00 | 0.00 | 0.00 | 23958586.77 | 0.360140E+11 | 0.00 | 0.00 | 0.50 |
February | 0.182706E+11 | 0.00 | 0.00 | 1030496.20 | 0.00 | 0.208976E+11 | 0.212356E+09 | 0.00 | 0.52 |
March | 0.328112E+11 | 0.158008E+09 | 0.00 | 6113292.49 | 0.119211E+09 | 0.348863E+10 | 0.230064E+10 | 0.00 | 0.57 |
April | 0.183231E+11 | 0.104215E+10 | 0.00 | 20080858.13 | 0.218072E+09 | 0.837846E+09 | 0.467529E+10 | 0.00 | 0.58 |
May | 0.595310E+10 | 0.666324E+10 | 0.00 | 14512373.27 | 0.453034E+09 | 0.00 | 0.318644E+10 | 0.00 | 0.58 |
June | 0.208103E+10 | 0.236251E+11 | 0.00 | 11312415.78 | 0.210952E+09 | 0.00 | 0.210392E+10 | 0.00 | 0.65 |
July | 25213263.32 | 0.321937E+11 | 0.00 | 148465.72 | 0.932550E+09 | 0.00 | 20972161.53 | 0.00 | 0.56 |
August | 6909279.29 | 0.390100E+11 | 0.00 | 217289.18 | 0.289087E+09 | 0.00 | 1467270.32 | 0.00 | 0.59 |
September | 0.435589E+10 | 0.135813E+11 | 0.00 | 13569499.52 | 0.139373E+10 | 0.00 | 0.193483E+10 | 0.00 | 0.53 |
October | 0.255790E+11 | 0.404562E+10 | 0.00 | 3763131.37 | 0.769246E+09 | 0.102775E+10 | 0.184855E+10 | 0.00 | 0.50 |
November | 0.293103E+11 | 6492177.09 | 0.00 | 1070936.13 | 0.502260E+09 | 0.726676E+10 | 0.446097E+09 | 0.00 | 0.51 |
December | 0.228211E+11 | 0.00 | 0.00 | 68230.84 | 2906370.04 | 0.200308E+11 | 55575039.40 | 0.00 | 0.49 |
Annual Sum or Average | 0.170848E+12 | 0.120326E+12 | 0.00 | 71886988.64 | 0.491500E+10 | 0.895634E+11 | 0.167861E+11 | 0.00 | 0.55 |
Minimum of Months | 6909279.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.49 |
Maximum of Months | 0.328112E+11 | 0.390100E+11 | 0.00 | 20080858.13 | 0.139373E+10 | 0.360140E+11 | 0.467529E+10 | 0.00 | 0.65 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.177868E+11 | 0.00 | 0.00 | 0.00 | 22750881.58 | 0.253929E+11 | 0.00 | 0.00 | 0.71 |
February | 0.184764E+11 | 0.00 | 0.00 | 6054561.99 | 0.00 | 0.154777E+11 | 0.287644E+10 | 0.00 | 0.76 |
March | 0.252186E+11 | 0.112591E+09 | 0.00 | 18525938.41 | 0.134924E+09 | 0.234161E+10 | 0.101970E+11 | 0.00 | 0.86 |
April | 0.125188E+11 | 0.641730E+09 | 0.00 | 43731113.98 | 0.427055E+09 | 0.559659E+09 | 0.132896E+11 | 0.00 | 0.98 |
May | 0.447424E+10 | 0.628414E+10 | 0.00 | 25702511.13 | 0.656557E+09 | 0.00 | 0.637935E+10 | 0.00 | 0.95 |
June | 0.158264E+10 | 0.208374E+11 | 0.00 | 17546836.74 | 0.412886E+09 | 0.00 | 0.385115E+10 | 0.00 | 0.95 |
July | 32163231.12 | 0.295536E+11 | 0.00 | 117841.95 | 0.145233E+10 | 0.00 | 10961765.72 | 0.00 | 0.80 |
August | 7115670.59 | 0.344046E+11 | 0.00 | 122870.74 | 0.742814E+09 | 0.00 | 633026.75 | 0.00 | 0.82 |
September | 0.384688E+10 | 0.115171E+11 | 0.00 | 19238156.03 | 0.310961E+10 | 0.00 | 0.332381E+10 | 0.00 | 0.85 |
October | 0.193891E+11 | 0.290030E+10 | 0.00 | 17650453.53 | 0.142445E+10 | 0.100585E+10 | 0.868361E+10 | 0.00 | 0.78 |
November | 0.279680E+11 | 6121592.34 | 0.00 | 3362845.81 | 0.476943E+09 | 0.472451E+10 | 0.243633E+10 | 0.00 | 0.75 |
December | 0.269540E+11 | 0.00 | 0.00 | 0.00 | 2759865.65 | 0.131409E+11 | 0.00 | 0.00 | 0.71 |
Annual Sum or Average | 0.158255E+12 | 0.106258E+12 | 0.00 | 0.152053E+09 | 0.886307E+10 | 0.626431E+11 | 0.510489E+11 | 0.00 | 0.83 |
Minimum of Months | 7115670.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.71 |
Maximum of Months | 0.279680E+11 | 0.344046E+11 | 0.00 | 43731113.98 | 0.310961E+10 | 0.253929E+11 | 0.132896E+11 | 0.00 | 0.98 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.186278E+11 | 0.00 | 0.00 | 33572525.09 | 23898205.96 | 0.170015E+11 | 0.201364E+11 | 0.00 | 0.58 |
February | 0.179685E+11 | 0.00 | 0.00 | 45660063.61 | 0.00 | 0.110410E+11 | 0.196618E+11 | 0.00 | 0.69 |
March | 0.227405E+11 | 0.400531E+09 | 0.00 | 63082865.07 | 46188359.24 | 0.175470E+10 | 0.257576E+11 | 0.00 | 0.82 |
April | 0.137574E+11 | 0.140857E+10 | 0.00 | 54997841.56 | 0.113862E+09 | 0.535631E+09 | 0.140101E+11 | 0.00 | 0.79 |
May | 0.564277E+10 | 0.783374E+10 | 0.00 | 19967441.80 | 0.383141E+09 | 0.00 | 0.422083E+10 | 0.00 | 0.66 |
June | 0.230425E+10 | 0.239868E+11 | 0.00 | 11048055.37 | 0.229599E+09 | 0.00 | 0.190586E+10 | 0.00 | 0.66 |
July | 25149720.46 | 0.336014E+11 | 0.00 | 170462.56 | 0.878086E+09 | 0.00 | 21341590.03 | 0.00 | 0.58 |
August | 6148673.21 | 0.458794E+11 | 0.00 | 342291.86 | 0.286689E+09 | 0.00 | 2444488.85 | 0.00 | 0.70 |
September | 0.356620E+10 | 0.192343E+11 | 0.00 | 31654591.04 | 0.706662E+09 | 0.00 | 0.430584E+10 | 0.00 | 0.77 |
October | 0.156245E+11 | 0.689934E+10 | 0.00 | 73412700.69 | 0.210943E+09 | 0.874961E+09 | 0.283568E+11 | 0.00 | 0.88 |
November | 0.200591E+11 | 0.113696E+09 | 0.00 | 86759942.82 | 0.406081E+09 | 0.257390E+10 | 0.319558E+11 | 0.00 | 0.82 |
December | 0.218850E+11 | 4348126.16 | 0.00 | 55902246.14 | 0.00 | 0.805870E+10 | 0.277483E+11 | 0.00 | 0.68 |
Annual Sum or Average | 0.142207E+12 | 0.139362E+12 | 0.00 | 0.476571E+09 | 0.328515E+10 | 0.418403E+11 | 0.178083E+12 | 0.00 | 0.72 |
Minimum of Months | 6148673.21 | 0.00 | 0.00 | 170462.56 | 0.00 | 0.00 | 2444488.85 | 0.00 | 0.58 |
Maximum of Months | 0.227405E+11 | 0.458794E+11 | 0.00 | 86759942.82 | 0.878086E+09 | 0.170015E+11 | 0.319558E+11 | 0.00 | 0.88 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.209423E+11 | 0.00 | 0.00 | 180635.31 | 24122653.32 | 0.238991E+11 | 0.620246E+09 | 0.00 | 0.75 |
February | 0.235573E+11 | 0.00 | 0.00 | 5942814.44 | 0.00 | 0.132377E+11 | 0.222690E+10 | 0.00 | 0.82 |
March | 0.307270E+11 | 0.293303E+09 | 0.00 | 21209275.71 | 67454286.22 | 0.158362E+10 | 0.874992E+10 | 0.00 | 0.98 |
April | 0.160007E+11 | 0.106875E+10 | 0.00 | 41089732.32 | 0.207346E+09 | 0.270998E+09 | 0.977803E+10 | 0.00 | 1.06 |
May | 0.590072E+10 | 0.634558E+10 | 0.00 | 17860098.03 | 0.542934E+09 | 0.00 | 0.415957E+10 | 0.00 | 0.97 |
June | 0.234341E+10 | 0.211106E+11 | 0.00 | 11518613.60 | 0.395929E+09 | 0.00 | 0.191214E+10 | 0.00 | 0.97 |
July | 23311871.51 | 0.291039E+11 | 0.00 | 321197.49 | 0.110821E+10 | 0.00 | 25452938.93 | 0.00 | 0.81 |
August | 6206420.37 | 0.374574E+11 | 0.00 | 358267.12 | 0.176458E+09 | 0.00 | 2451737.20 | 0.00 | 0.89 |
September | 0.413034E+10 | 0.124564E+11 | 0.00 | 15999562.01 | 0.223703E+10 | 0.00 | 0.224027E+10 | 0.00 | 0.87 |
October | 0.231652E+11 | 0.369687E+10 | 0.00 | 17135779.73 | 0.873619E+09 | 0.762941E+09 | 0.671730E+10 | 0.00 | 0.86 |
November | 0.289109E+11 | 6490695.72 | 0.00 | 9943868.61 | 0.505700E+09 | 0.451985E+10 | 0.457502E+10 | 0.00 | 0.82 |
December | 0.304185E+11 | 357143.43 | 0.00 | 1940436.40 | 2569129.21 | 0.106590E+11 | 0.128138E+10 | 0.00 | 0.75 |
Annual Sum or Average | 0.186126E+12 | 0.111540E+12 | 0.00 | 0.143500E+09 | 0.614137E+10 | 0.549332E+11 | 0.422887E+11 | 0.00 | 0.88 |
Minimum of Months | 6206420.37 | 0.00 | 0.00 | 180635.31 | 0.00 | 0.00 | 2451737.20 | 0.00 | 0.75 |
Maximum of Months | 0.307270E+11 | 0.374574E+11 | 0.00 | 41089732.32 | 0.223703E+10 | 0.238991E+11 | 0.977803E+10 | 0.00 | 1.06 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.760539E+09 | 0.00 | 0.00 | 0.00 | 2476606.06 | 0.368876E+10 | 0.00 | 0.00 | 0.54 |
February | 0.127070E+10 | 0.00 | 0.00 | 72349.40 | 212728.38 | 0.233630E+10 | 19490586.21 | 0.00 | 0.54 |
March | 0.258180E+10 | 13100304.85 | 0.00 | 626191.52 | 9495890.03 | 0.758295E+09 | 0.218217E+09 | 0.00 | 0.57 |
April | 0.164041E+10 | 79925862.27 | 0.00 | 2271845.32 | 39987103.67 | 0.191753E+09 | 0.438425E+09 | 0.00 | 0.59 |
May | 0.516778E+09 | 0.638657E+09 | 0.00 | 1458861.29 | 67304440.36 | 8635099.22 | 0.310040E+09 | 0.00 | 0.58 |
June | 0.183822E+09 | 0.228769E+10 | 0.00 | 1113306.21 | 51577844.25 | 0.00 | 0.209223E+09 | 0.00 | 0.65 |
July | 1805904.40 | 0.309793E+10 | 0.00 | 8161.34 | 0.136414E+09 | 0.00 | 623413.40 | 0.00 | 0.55 |
August | 747.62 | 0.379892E+10 | 0.00 | 0.00 | 45705502.72 | 0.00 | 0.00 | 0.00 | 0.58 |
September | 0.354404E+09 | 0.119009E+10 | 0.00 | 1350312.89 | 0.302098E+09 | 0.00 | 0.200385E+09 | 0.00 | 0.53 |
October | 0.193874E+10 | 0.422140E+09 | 0.00 | 271388.43 | 0.109819E+09 | 0.512365E+09 | 0.150273E+09 | 0.00 | 0.51 |
November | 0.212686E+10 | 31037.10 | 7902260.32 | 90295.68 | 52957244.90 | 0.121409E+10 | 16330361.21 | 11430.60 | 0.52 |
December | 0.141975E+10 | 0.00 | 0.00 | 0.00 | 511608.92 | 0.267515E+10 | 0.00 | 0.00 | 0.52 |
Annual Sum or Average | 0.127956E+11 | 0.115285E+11 | 7902260.32 | 7262712.08 | 0.818560E+09 | 0.113853E+11 | 0.156301E+10 | 11430.60 | 0.56 |
Minimum of Months | 747.62 | 0.00 | 0.00 | 0.00 | 212728.38 | 0.00 | 0.00 | 0.00 | 0.51 |
Maximum of Months | 0.258180E+10 | 0.379892E+10 | 7902260.32 | 2271845.32 | 0.302098E+09 | 0.368876E+10 | 0.438425E+09 | 11430.60 | 0.65 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.125457E+10 | 0.00 | 0.00 | 0.00 | 2338558.53 | 0.265074E+10 | 0.00 | 0.00 | 0.74 |
February | 0.149296E+10 | 0.00 | 0.00 | 303191.28 | 200870.77 | 0.161228E+10 | 0.166354E+09 | 0.00 | 0.76 |
March | 0.217119E+10 | 7861279.62 | 0.00 | 1390451.91 | 12926567.39 | 0.494969E+09 | 0.707929E+09 | 0.00 | 0.84 |
April | 0.113781E+10 | 49039145.23 | 0.00 | 4348587.44 | 55447342.84 | 0.108097E+09 | 0.115363E+10 | 0.00 | 0.98 |
May | 0.362612E+09 | 0.611628E+09 | 0.00 | 2576862.04 | 83542728.47 | 5401867.30 | 0.601508E+09 | 0.00 | 0.94 |
June | 0.129398E+09 | 0.202676E+10 | 0.00 | 1719066.00 | 71820929.34 | 0.00 | 0.375177E+09 | 0.00 | 0.95 |
July | 1846678.23 | 0.286277E+10 | 0.00 | 7238.20 | 0.178478E+09 | 0.00 | 405717.02 | 0.00 | 0.80 |
August | 705.95 | 0.334085E+10 | 0.00 | 0.00 | 0.114992E+09 | 0.00 | 0.00 | 0.00 | 0.82 |
September | 0.287899E+09 | 0.113829E+10 | 0.00 | 1960505.48 | 0.341427E+09 | 365214.92 | 0.347618E+09 | 0.00 | 0.86 |
October | 0.146133E+10 | 0.345631E+09 | 0.00 | 1324836.80 | 0.139890E+09 | 0.395714E+09 | 0.699053E+09 | 0.00 | 0.77 |
November | 0.229094E+10 | 29307.08 | 7467788.59 | 100855.05 | 50005375.76 | 0.742900E+09 | 82126305.21 | 4788.36 | 0.75 |
December | 0.186860E+10 | 0.00 | 0.00 | 0.00 | 483091.53 | 0.183099E+10 | 0.00 | 0.00 | 0.74 |
Annual Sum or Average | 0.124592E+11 | 0.103829E+11 | 7467788.59 | 13731594.19 | 0.105155E+10 | 0.784146E+10 | 0.413380E+10 | 4788.36 | 0.83 |
Minimum of Months | 705.95 | 0.00 | 0.00 | 0.00 | 200870.77 | 0.00 | 0.00 | 0.00 | 0.74 |
Maximum of Months | 0.229094E+10 | 0.334085E+10 | 7467788.59 | 4348587.44 | 0.341427E+09 | 0.265074E+10 | 0.115363E+10 | 4788.36 | 0.98 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.153874E+10 | 0.00 | 0.00 | 2203079.03 | 2643492.79 | 0.213411E+10 | 0.137244E+10 | 0.00 | 0.60 |
February | 0.152635E+10 | 0.00 | 0.00 | 3342448.02 | 227063.14 | 0.139640E+10 | 0.147805E+10 | 0.00 | 0.69 |
March | 0.200798E+10 | 27919969.90 | 0.00 | 5279906.54 | 5343576.21 | 0.526122E+09 | 0.212493E+10 | 0.00 | 0.80 |
April | 0.133490E+10 | 0.107761E+09 | 0.00 | 5838904.32 | 30215512.01 | 0.149449E+09 | 0.134337E+10 | 0.00 | 0.81 |
May | 0.526044E+09 | 0.738478E+09 | 0.00 | 1996679.63 | 73363409.51 | 7256215.69 | 0.428981E+09 | 0.00 | 0.67 |
June | 0.220218E+09 | 0.227345E+10 | 0.00 | 1107206.84 | 0.105031E+09 | 0.00 | 0.200204E+09 | 0.00 | 0.67 |
July | 1927595.72 | 0.320848E+10 | 0.00 | 9336.05 | 0.170033E+09 | 0.00 | 661934.75 | 0.00 | 0.58 |
August | 798.00 | 0.445002E+10 | 0.00 | 0.00 | 36671243.00 | 0.00 | 0.00 | 0.00 | 0.69 |
September | 0.303571E+09 | 0.172367E+10 | 0.00 | 3243468.63 | 0.257155E+09 | 0.00 | 0.480776E+09 | 0.00 | 0.78 |
October | 0.137347E+10 | 0.742325E+09 | 0.00 | 6016052.13 | 45966225.54 | 0.339005E+09 | 0.241497E+10 | 0.00 | 0.85 |
November | 0.182971E+10 | 2748701.84 | 0.00 | 6215211.66 | 62297276.20 | 0.598300E+09 | 0.226051E+10 | 0.00 | 0.77 |
December | 0.194023E+10 | 530108.21 | 0.00 | 3620017.19 | 15975.61 | 0.127295E+10 | 0.190318E+10 | 0.00 | 0.66 |
Annual Sum or Average | 0.126031E+11 | 0.132754E+11 | 0.00 | 38872310.05 | 0.788962E+09 | 0.642359E+10 | 0.140081E+11 | 0.00 | 0.71 |
Minimum of Months | 798.00 | 0.00 | 0.00 | 0.00 | 15975.61 | 0.00 | 0.00 | 0.00 | 0.58 |
Maximum of Months | 0.200798E+10 | 0.445002E+10 | 0.00 | 6215211.66 | 0.257155E+09 | 0.213411E+10 | 0.241497E+10 | 0.00 | 0.85 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.163768E+10 | 0.00 | 0.00 | 4810.43 | 2606046.83 | 0.259778E+10 | 26179879.96 | 0.00 | 0.81 |
February | 0.186785E+10 | 0.00 | 0.00 | 525895.05 | 223846.71 | 0.155193E+10 | 0.223292E+09 | 0.00 | 0.86 |
March | 0.259962E+10 | 19405782.56 | 0.00 | 2039469.88 | 8510560.77 | 0.447519E+09 | 0.869308E+09 | 0.00 | 1.00 |
April | 0.148774E+10 | 75530094.03 | 0.00 | 4591124.95 | 47316142.11 | 0.104126E+09 | 0.100122E+10 | 0.00 | 1.10 |
May | 0.542481E+09 | 0.590344E+09 | 0.00 | 1760187.64 | 92115350.35 | 0.00 | 0.433980E+09 | 0.00 | 0.98 |
June | 0.222822E+09 | 0.196905E+10 | 0.00 | 1174150.69 | 0.113162E+09 | 0.00 | 0.201025E+09 | 0.00 | 0.96 |
July | 1374586.43 | 0.271678E+10 | 0.00 | 21703.26 | 0.207527E+09 | 0.00 | 1284390.59 | 0.00 | 0.79 |
August | 786.70 | 0.357666E+10 | 0.00 | 0.00 | 53939667.73 | 0.00 | 0.00 | 0.00 | 0.86 |
September | 0.365403E+09 | 0.111705E+10 | 0.00 | 1636116.79 | 0.370267E+09 | 410861.12 | 0.229554E+09 | 0.00 | 0.89 |
October | 0.200001E+10 | 0.370328E+09 | 0.00 | 1515971.93 | 0.150002E+09 | 0.267427E+09 | 0.640230E+09 | 0.00 | 0.88 |
November | 0.240858E+10 | 0.00 | 0.00 | 723449.18 | 64085037.99 | 0.752663E+09 | 0.358661E+09 | 0.00 | 0.86 |
December | 0.236863E+10 | 0.00 | 0.00 | 98324.86 | 538348.36 | 0.159754E+10 | 0.101103E+09 | 0.00 | 0.82 |
Annual Sum or Average | 0.155022E+11 | 0.104351E+11 | 0.00 | 14091204.66 | 0.111029E+10 | 0.731938E+10 | 0.408584E+10 | 0.00 | 0.90 |
Minimum of Months | 786.70 | 0.00 | 0.00 | 0.00 | 223846.71 | 0.00 | 0.00 | 0.00 | 0.79 |
Maximum of Months | 0.259962E+10 | 0.357666E+10 | 0.00 | 4591124.95 | 0.370267E+09 | 0.259778E+10 | 0.100122E+10 | 0.00 | 1.10 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 2985069.95 | 0.00 | 0.00 | 0.593193E+09 | 0.00 | 0.28 |
February | 0.00 | 0.00 | 0.00 | 7287001.97 | 0.00 | 0.00 | 0.445068E+09 | 0.00 | 0.28 |
March | 0.00 | 4205937.51 | 0.00 | 12520530.61 | 0.00 | 0.00 | 0.341130E+09 | 0.00 | 0.31 |
April | 0.00 | 11255691.21 | 0.00 | 14844507.70 | 0.00 | 0.00 | 0.186766E+09 | 0.00 | 0.29 |
May | 0.00 | 66282343.21 | 0.00 | 1516838.38 | 0.00 | 0.00 | 59851022.92 | 0.00 | 0.29 |
June | 0.00 | 0.278410E+09 | 0.00 | 1376396.46 | 0.00 | 0.00 | 27282702.27 | 0.00 | 0.30 |
July | 0.00 | 0.391564E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.28 |
August | 0.00 | 0.478785E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.31 |
September | 0.00 | 0.156693E+09 | 0.00 | 1328307.93 | 0.00 | 0.00 | 34063940.61 | 0.00 | 0.29 |
October | 0.00 | 50408222.30 | 0.00 | 6252557.83 | 0.00 | 0.00 | 0.241334E+09 | 0.00 | 0.28 |
November | 0.00 | 3556099.57 | 0.00 | 11458387.86 | 0.00 | 0.00 | 0.355680E+09 | 0.00 | 0.28 |
December | 0.00 | 434846.03 | 0.00 | 17067722.40 | 0.00 | 0.00 | 0.448696E+09 | 0.00 | 0.28 |
Annual Sum or Average | 0.00 | 0.144160E+10 | 0.00 | 76637321.08 | 0.00 | 0.00 | 0.273306E+10 | 0.00 | 0.29 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.28 |
Maximum of Months | 0.00 | 0.478785E+09 | 0.00 | 17067722.40 | 0.00 | 0.00 | 0.593193E+09 | 0.00 | 0.31 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.127517E+10 | 0.00 | 0.00 | 11786393.98 | 0.00 | 0.00 | 0.468203E+10 | 0.00 | 0.28 |
February | 0.00 | 0.00 | 0.00 | 56261327.58 | 0.00 | 0.00 | 0.447031E+10 | 0.00 | 0.28 |
March | 0.00 | 41554197.43 | 0.00 | 0.111639E+09 | 0.00 | 0.00 | 0.342167E+10 | 0.00 | 0.31 |
April | 0.00 | 0.112492E+09 | 0.00 | 0.137928E+09 | 0.00 | 0.00 | 0.187499E+10 | 0.00 | 0.29 |
May | 0.00 | 0.640525E+09 | 0.00 | 13482174.83 | 0.00 | 0.00 | 0.605212E+09 | 0.00 | 0.29 |
June | 0.00 | 0.277319E+10 | 0.00 | 12687002.36 | 0.00 | 0.00 | 0.273147E+09 | 0.00 | 0.30 |
July | 0.00 | 0.390855E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.28 |
August | 0.00 | 0.478983E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.31 |
September | 0.00 | 0.153530E+10 | 0.00 | 11462839.67 | 0.00 | 0.00 | 0.353462E+09 | 0.00 | 0.29 |
October | 0.00 | 0.496963E+09 | 0.00 | 53452284.70 | 0.00 | 0.00 | 0.242463E+10 | 0.00 | 0.28 |
November | 0.00 | 34111087.17 | 0.00 | 0.100168E+09 | 0.00 | 0.00 | 0.356901E+10 | 0.00 | 0.28 |
December | 0.00 | 4161205.74 | 0.00 | 0.147249E+09 | 0.00 | 0.00 | 0.450785E+10 | 0.00 | 0.28 |
Annual Sum or Average | 0.127517E+10 | 0.143367E+11 | 0.00 | 0.656116E+09 | 0.00 | 0.00 | 0.261823E+11 | 0.00 | 0.29 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.28 |
Maximum of Months | 0.127517E+10 | 0.478983E+10 | 0.00 | 0.147249E+09 | 0.00 | 0.00 | 0.468203E+10 | 0.00 | 0.31 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.292152E+09 | 0.00 | 0.00 | 686512.98 | 0.00 | 0.00 | 0.294338E+09 | 0.00 | 0.28 |
February | 0.00 | 0.00 | 0.00 | 5022627.45 | 0.00 | 0.00 | 0.447900E+09 | 0.00 | 0.28 |
March | 0.00 | 4141332.66 | 0.00 | 10568256.36 | 0.00 | 0.00 | 0.343094E+09 | 0.00 | 0.31 |
April | 0.00 | 11182355.56 | 0.00 | 13489959.92 | 0.00 | 0.00 | 0.188028E+09 | 0.00 | 0.29 |
May | 0.00 | 64114165.42 | 0.00 | 1264859.81 | 0.00 | 0.00 | 60939979.22 | 0.00 | 0.29 |
June | 0.00 | 0.277440E+09 | 0.00 | 1244317.39 | 0.00 | 0.00 | 27391107.84 | 0.00 | 0.30 |
July | 0.00 | 0.390705E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.28 |
August | 0.00 | 0.480578E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.31 |
September | 0.00 | 0.153175E+09 | 0.00 | 1045305.93 | 0.00 | 0.00 | 36382817.43 | 0.00 | 0.29 |
October | 0.00 | 49487137.66 | 0.00 | 4851921.71 | 0.00 | 0.00 | 0.243728E+09 | 0.00 | 0.28 |
November | 0.00 | 3342404.21 | 0.00 | 9257967.30 | 0.00 | 0.00 | 0.358007E+09 | 0.00 | 0.28 |
December | 0.00 | 401911.81 | 0.00 | 13875433.63 | 0.00 | 0.00 | 0.451869E+09 | 0.00 | 0.28 |
Annual Sum or Average | 0.292152E+09 | 0.143457E+10 | 0.00 | 61307162.47 | 0.00 | 0.00 | 0.245168E+10 | 0.00 | 0.29 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.28 |
Maximum of Months | 0.292152E+09 | 0.480578E+09 | 0.00 | 13875433.63 | 0.00 | 0.00 | 0.451869E+09 | 0.00 | 0.31 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.224391E+09 | 0.00 | 0.00 | 0.151337E+11 | 0.00 | 0.32 |
February | 0.00 | 0.00 | 0.00 | 0.401576E+09 | 0.00 | 0.00 | 0.111504E+11 | 0.00 | 0.32 |
March | 0.00 | 83261267.55 | 0.00 | 0.624859E+09 | 0.00 | 0.00 | 0.797142E+10 | 0.00 | 0.34 |
April | 0.00 | 0.231501E+09 | 0.00 | 0.737887E+09 | 0.00 | 0.00 | 0.407270E+10 | 0.00 | 0.32 |
May | 0.00 | 0.173291E+10 | 0.00 | 75128874.77 | 0.00 | 0.00 | 0.128652E+10 | 0.00 | 0.33 |
June | 0.00 | 0.626850E+10 | 0.00 | 67339950.91 | 0.00 | 0.00 | 0.580050E+09 | 0.00 | 0.34 |
July | 0.00 | 0.864008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.31 |
August | 0.00 | 0.877330E+10 | 0.00 | 14583.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.35 |
September | 0.00 | 0.379914E+10 | 0.00 | 64989747.14 | 0.00 | 0.00 | 0.639806E+09 | 0.00 | 0.33 |
October | 0.00 | 0.116770E+10 | 0.00 | 0.323047E+09 | 0.00 | 0.00 | 0.515485E+10 | 0.00 | 0.32 |
November | 0.00 | 68581306.14 | 0.00 | 0.580469E+09 | 0.00 | 0.00 | 0.853266E+10 | 0.00 | 0.32 |
December | 0.00 | 9692320.10 | 0.00 | 0.866386E+09 | 0.00 | 0.00 | 0.110352E+11 | 0.00 | 0.31 |
Annual Sum or Average | 0.00 | 0.307747E+11 | 0.00 | 0.396609E+10 | 0.00 | 0.00 | 0.655574E+11 | 0.00 | 0.33 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.31 |
Maximum of Months | 0.00 | 0.877330E+10 | 0.00 | 0.866386E+09 | 0.00 | 0.00 | 0.151337E+11 | 0.00 | 0.35 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 08:43:24
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.330345E+12 | 0.277659E+11 | 0.00 | 0.219420E+13 | 0.611975E+12 |
February | 0.332320E+12 | 0.242877E+11 | 0.00 | 0.196816E+13 | 0.102696E+13 |
March | 0.489799E+12 | 0.157002E+11 | 0.00 | 0.208653E+13 | 0.182873E+13 |
April | 0.554557E+12 | 0.796012E+10 | 0.00 | 0.150483E+13 | 0.256763E+13 |
May | 0.613963E+12 | 0.191403E+10 | 0.00 | 0.569718E+12 | 0.220174E+13 |
June | 0.598113E+12 | -0.688634E+10 | 0.00 | -0.305599E+12 | 0.321289E+13 |
July | 0.576822E+12 | -0.122047E+11 | 0.00 | -0.815755E+12 | 0.398364E+13 |
August | 0.534724E+12 | -0.148145E+11 | 0.00 | -0.101450E+13 | 0.467824E+13 |
September | 0.409785E+12 | -0.278838E+10 | 0.00 | 0.308203E+11 | 0.240964E+13 |
October | 0.386376E+12 | 0.775894E+10 | 0.00 | 0.155483E+13 | 0.179531E+13 |
November | 0.280764E+12 | 0.141026E+11 | 0.00 | 0.201683E+13 | 0.163797E+13 |
December | 0.266659E+12 | 0.258457E+11 | 0.00 | 0.231049E+13 | 0.183495E+13 |
Annual Sum or Average | 0.537423E+13 | 0.886411E+11 | 0.00 | 0.121006E+14 | 0.277897E+14 |
Minimum of Months | 0.266659E+12 | -0.148145E+11 | 0.00 | -0.101450E+13 | 0.611975E+12 |
Maximum of Months | 0.613963E+12 | 0.277659E+11 | 0.00 | 0.231049E+13 | 0.467824E+13 |