Table of Contents

Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:43

Tabular Output Report in Format: HTML

Building: OfficeLarge

Environment: RUNPERIOD 1 ** New York-John F Kennedy Intl AP NY USA TMY3 WMO#=744860

Simulation Timestamp: 2023-10-16 08:43:34


Table of Contents

Report: Annual Building Utility Performance Summary

For: Entire Facility

Timestamp: 2023-10-16 08:43:34

Values gathered over 8760.00 hours



Site and Source Energy

Total Energy [GJ] Energy Per Total Building Area [MJ/m2] Energy Per Conditioned Building Area [MJ/m2]
Total Site Energy 31226.82 674.15 674.15
Net Site Energy 31226.82 674.15 674.15
Total Source Energy 94440.48 2038.85 2038.85
Net Source Energy 94440.48 2038.85 2038.85


Site to Source Energy Conversion Factors

Site=>Source Conversion Factor
Electricity 3.167
Natural Gas 1.084
District Cooling 1.056
District Heating 3.613
Steam 1.200
Gasoline 1.050
Diesel 1.050
Coal 1.050
Fuel Oil No 1 1.050
Fuel Oil No 2 1.050
Propane 1.050
Other Fuel 1 1.000
Other Fuel 2 1.000


Building Area

Area [m2]
Total Building Area 46320.38
Net Conditioned Building Area 46320.38
Unconditioned Building Area 0.00


End Uses

Electricity [GJ] Natural Gas [GJ] Gasoline [GJ] Diesel [GJ] Coal [GJ] Fuel Oil No 1 [GJ] Fuel Oil No 2 [GJ] Propane [GJ] Other Fuel 1 [GJ] Other Fuel 2 [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating 0.00 1354.97 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 3703.58 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 3930.81 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 698.54 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 14676.40 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 1934.79 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 2439.82 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 476.45 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 1159.17 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 5725.91
Humidification 14.23 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 5.30
Heat Recovery 54.36 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 783.71 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 2280.17
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                           
Total End Uses 29088.15 2138.67 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 8011.37
Note: Natural gas appears to be the principal heating source based on energy usage.

End Uses By Subcategory

Subcategory Electricity [GJ] Natural Gas [GJ] Gasoline [GJ] Diesel [GJ] Coal [GJ] Fuel Oil No 1 [GJ] Fuel Oil No 2 [GJ] Propane [GJ] Other Fuel 1 [GJ] Other Fuel 2 [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Boiler 0.00 1354.97 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Boiler Parasitic 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling General 3703.58 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting LightsWired 3930.81 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting General 698.54 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment MiscPlug 5334.97 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  DataCenterPlugLoads 9341.42 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment Transformer 80.18 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  ElevatorLift 1848.78 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  ElevatorLightsFan 5.83 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans General 2439.82 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps General 476.45 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection General 1159.17 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 5725.91
Humidification General 14.23 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 5.30
Heat Recovery General 54.36 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  WaterUse 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 2280.17
  Water Heater 0.00 783.71 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


End Uses By Space Type

Space Type Electricity [GJ] Natural Gas [GJ] Gasoline [GJ] Diesel [GJ] Coal [GJ] Fuel Oil No 1 [GJ] Fuel Oil No 2 [GJ] Propane [GJ] Other Fuel 1 [GJ] Other Fuel 2 [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating Unassigned 0.00 1354.97 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling Unassigned 3703.58 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting GENERAL 3930.81 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting Unassigned 698.54 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment GENERAL 14676.40 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment Unassigned 1934.79 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans Unassigned 2439.82 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps Unassigned 476.45 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection Unassigned 1159.17 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 5725.91
Humidification Unassigned 14.23 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 5.30
Heat Recovery Unassigned 54.36 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems Unassigned 0.00 783.71 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 2280.17
Refrigeration Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Normalized Metrics

Utility Use Per Conditioned Floor Area

Electricity Intensity [MJ/m2] Natural Gas Intensity [MJ/m2] Gasoline Intensity [MJ/m2] Diesel Intensity [MJ/m2] Coal Intensity [MJ/m2] Fuel Oil No 1 Intensity [MJ/m2] Fuel Oil No 2 Intensity [MJ/m2] Propane Intensity [MJ/m2] Other Fuel 1 Intensity [MJ/m2] Other Fuel 2 Intensity [MJ/m2] District Cooling Intensity [MJ/m2] District Heating Intensity [MJ/m2] Water Intensity [m3/m2]
Lighting 99.94 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
HVAC 168.25 46.17 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.17
Other 359.79 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total 627.98 46.17 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.17


Utility Use Per Total Floor Area

Electricity Intensity [MJ/m2] Natural Gas Intensity [MJ/m2] Gasoline Intensity [MJ/m2] Diesel Intensity [MJ/m2] Coal Intensity [MJ/m2] Fuel Oil No 1 Intensity [MJ/m2] Fuel Oil No 2 Intensity [MJ/m2] Propane Intensity [MJ/m2] Other Fuel 1 Intensity [MJ/m2] Other Fuel 2 Intensity [MJ/m2] District Cooling Intensity [MJ/m2] District Heating Intensity [MJ/m2] Water Intensity [m3/m2]
Lighting 99.94 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
HVAC 168.25 46.17 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.17
Other 359.79 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total 627.98 46.17 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.17


Electric Loads Satisfied

Electricity [GJ] Percent Electricity [%]
Fuel-Fired Power Generation 0.000 0.00
High Temperature Geothermal* 0.000 0.00
Photovoltaic Power 0.000 0.00
Wind Power 0.000 0.00
Power Conversion 0.000 0.00
Net Decrease in On-Site Storage 0.000 0.00
Total On-Site Electric Sources 0.000 0.00
     
Electricity Coming From Utility 29088.146 100.00
Surplus Electricity Going To Utility 0.000 0.00
Net Electricity From Utility 29088.146 100.00
     
Total On-Site and Utility Electric Sources 29088.146 100.00
Total Electricity End Uses 29088.146 100.00


On-Site Thermal Sources

Heat [GJ] Percent Heat [%]
Water-Side Heat Recovery 0.00 0.00
Air to Air Heat Recovery for Cooling 722.04 25.53
Air to Air Heat Recovery for Heating 2106.45 74.47
High-Temperature Geothermal* 0.00 0.00
Solar Water Thermal 0.00 0.00
Solar Air Thermal 0.00 0.00
Total On-Site Thermal Sources 2828.49 100.00


Water Source Summary

Water [m3] Percent Water [%]
Rainwater Collection 0.00 0.00
Condensate Collection 0.00 0.00
Groundwater Well 0.00 0.00
Total On Site Water Sources 0.00 0.00
- - -
Initial Storage 0.00 0.00
Final Storage 0.00 0.00
Change in Storage 0.00 0.00
- - -
Water Supplied by Utility 8011.37 100.00
- - -
Total On Site, Change in Storage, and Utility Water Sources 8011.37 100.00
Total Water End Uses 8011.37 100.00


Setpoint Not Met Criteria

Degrees [deltaC]
Tolerance for Zone Heating Setpoint Not Met Time 0.56
Tolerance for Zone Cooling Setpoint Not Met Time 0.56


Comfort and Setpoint Not Met Summary

Facility [Hours]
Time Setpoint Not Met During Occupied Heating 43.83
Time Setpoint Not Met During Occupied Cooling 465.83
Time Not Comfortable Based on Simple ASHRAE 55-2004 5943.00


Note 1: An asterisk (*) indicates that the feature is not yet implemented.

Table of Contents

Top
Annual Building Utility Performance Summary
Input Verification and Results Summary
Demand End Use Components Summary
Source Energy End Use Components Summary
Component Sizing Summary
Surface Shadowing Summary
Adaptive Comfort Summary
Initialization Summary
Annual Heat Emissions Summary
Climatic Data Summary
Envelope Summary
Shading Summary
Lighting Summary
Equipment Summary
HVAC Sizing Summary
Coil Sizing Details
System Summary
Outdoor Air Summary
Outdoor Air Details
Object Count Summary
Energy Meters
Sensible Heat Gain Summary
Standard 62.1 Summary
LEED Summary
Annual Thermal Resilience Summary
Annual CO2 Resilience Summary
Annual Visual Resilience Summary

NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR

| Environment |

NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901

| Environment |

NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2013

| Environment |

NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND

| Environment |

NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICELARGE

| Environment |

NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL

| Environment |

NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL

| Environment |

NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 4A

| Environment |

NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_NY_NEWYORK

| Environment |

ZoneCoolingSummaryMonthly

| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |

ZoneHeatingSummaryMonthly

| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |

ZoneElectricSummaryMonthly

| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |

SpaceGainsMonthly

| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |

PeakSpaceGainsMonthly

| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |

SpaceGainComponentsAtCoolingPeakMonthly

| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |

EnergyConsumptionElectricityNaturalGasMonthly

| Meter |

EndUseEnergyConsumptionElectricityMonthly

| Meter |

EndUseEnergyConsumptionNaturalGasMonthly

| Meter |

PeakEnergyEndUseElectricityPart1Monthly

| Meter |

PeakEnergyEndUseElectricityPart2Monthly

| Meter |

ElectricComponentsOfPeakDemandMonthly

| Meter |

PeakEnergyEndUseNaturalGasMonthly

| Meter |

SetpointsNotMetWithTemperaturesMonthly

| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |

ComfortReportSimple55Monthly

| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |

OccupantComfortDataSummaryMonthly

| DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 | BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 |

ChillerReportMonthly

| COOLSYS1 CHILLER1 | COOLSYS1 CHILLER2 |

TowerReportMonthly

| CENTRAL TOWER | TOWERWATERSYS COOLTOWER 1 | TOWERWATERSYS COOLTOWER 2 |

BoilerReportMonthly

| HEATSYS1 BOILER | CENTRAL BOILER |

DXReportMonthly

| VAV_BOT WITH REHEAT COOLING COIL | VAV_MID WITH REHEAT COOLING COIL | VAV_TOP WITH REHEAT COOLING COIL | CAV_BAS COOLING COIL | AIRLOOP DATACENTER BASEMENT COOLING COIL | AIRLOOP DATACENTER BOT COOLING COIL | AIRLOOP DATACENTER MID COOLING COIL | AIRLOOP DATACENTER TOP COOLING COIL |

WindowReportMonthly

| PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW |

WindowEnergyReportMonthly

| PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW |

WindowZoneSummaryMonthly

| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |

WindowEnergyZoneSummaryMonthly

| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |

AverageOutdoorConditionsMonthly

| Environment |

OutdoorConditionsMaximumDryBulbMonthly

| Environment |

OutdoorConditionsMinimumDryBulbMonthly

| Environment |

OutdoorConditionsMaximumWetBulbMonthly

| Environment |

OutdoorConditionsMaximumDewPointMonthly

| Environment |

OutdoorGroundConditionsMonthly

| Environment |

WaterHeaterReportMonthly

| SWHSYS1 WATER HEATER |

DaylightingReportMonthly

| PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_4_DAYLCTRL |

CoilReportMonthly

| VAV_BOT WITH REHEAT HEATING COIL | CORE_BOTTOM VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | VAV_MID WITH REHEAT HEATING COIL | CORE_MID VAV BOX REHEAT COIL | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | VAV_TOP WITH REHEAT HEATING COIL | CORE_TOP VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | CAV_BAS HEATING COIL | AIRLOOP DATACENTER BASEMENT HEATING COIL | AIRLOOP DATACENTER BOT HEATING COIL | AIRLOOP DATACENTER MID HEATING COIL | AIRLOOP DATACENTER TOP HEATING COIL | AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | AIRLOOP DATACENTER BOT_SUPPHEATCOIL | AIRLOOP DATACENTER MID_SUPPHEATCOIL | AIRLOOP DATACENTER TOP_SUPPHEATCOIL | VAV_BOT WITH REHEAT COOLING COIL | VAV_MID WITH REHEAT COOLING COIL | VAV_TOP WITH REHEAT COOLING COIL | CAV_BAS COOLING COIL | AIRLOOP DATACENTER BASEMENT COOLING COIL | AIRLOOP DATACENTER BOT COOLING COIL | AIRLOOP DATACENTER MID COOLING COIL | AIRLOOP DATACENTER TOP COOLING COIL |

PlantLoopDemandReportMonthly

| HEATSYS1 | COOLSYS1_SUPPLY | COOLSYS1_DEMAND | SINGLE WATER PLANT LOOP | SWHSYS1 | TOWERWATERSYS |

FanReportMonthly

| CAV_BAS FAN | VAV_BOT WITH REHEAT FAN | VAV_MID WITH REHEAT FAN | VAV_TOP WITH REHEAT FAN | AIRLOOP DATACENTER BASEMENT SUPPLY FAN | AIRLOOP DATACENTER BOT SUPPLY FAN | AIRLOOP DATACENTER MID SUPPLY FAN | AIRLOOP DATACENTER TOP SUPPLY FAN |

PumpReportMonthly

| HEATSYS1 PUMP | COOLSYS1 PUMP SECONDARY | COOLSYS1 CHILLER1 PUMP | COOLSYS1 CHILLER2 PUMP | PLANT CIRC PUMP | SWHSYS1 PUMP | TOWERWATERSYS PUMP |

CondLoopDemandReportMonthly

| HEATSYS1 | COOLSYS1_SUPPLY | COOLSYS1_DEMAND | SINGLE WATER PLANT LOOP | SWHSYS1 | TOWERWATERSYS |

ZoneTemperatureOscillationReportMonthly

| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |

AirLoopSystemEnergyAndWaterUseMonthly

| VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | CAV_BAS | AIRLOOP DATACENTER BASEMENT | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |

AirLoopSystemComponentLoadsMonthly

| VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | CAV_BAS | AIRLOOP DATACENTER BASEMENT | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |

AirLoopSystemComponentEnergyUseMonthly

| VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | CAV_BAS | AIRLOOP DATACENTER BASEMENT | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |

MechanicalVentilationLoadsMonthly

| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |

HeatEmissionsReportMonthly

| Environment |

Table of Contents

Report: Input Verification and Results Summary

For: Entire Facility

Timestamp: 2023-10-16 08:43:34

General

Value
Program Version and Build EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:43
RunPeriod RUNPERIOD 1
Weather File New York-John F Kennedy Intl AP NY USA TMY3 WMO#=744860
Latitude [deg] 40.65
Longitude [deg] -73.8
Elevation [m] 5.00
Time Zone -5.0
North Axis Angle [deg] 0.00
Rotation for Appendix G [deg] 0.00
Hours Simulated [hrs] 8760.00


ENVELOPE

Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [m2] 12183.89 3655.17 2436.78 3655.17 2436.78
Above Ground Wall Area [m2] 11589.54 3476.86 2317.91 3476.86 2317.91
Window Opening Area [m2] 4635.80 1390.74 927.16 1390.74 927.16
Gross Window-Wall Ratio [%] 38.05 38.05 38.05 38.05 38.05
Above Ground Window-Wall Ratio [%] 40.00 40.00 40.00 40.00 40.00


Conditioned Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [m2] 12183.89 3655.17 2436.78 3655.17 2436.78
Above Ground Wall Area [m2] 11589.54 3476.86 2317.91 3476.86 2317.91
Window Opening Area [m2] 4635.80 1390.74 927.16 1390.74 927.16
Gross Window-Wall Ratio [%] 38.05 38.05 38.05 38.05 38.05
Above Ground Window-Wall Ratio [%] 40.00 40.00 40.00 40.00 40.00


Skylight-Roof Ratio

Total
Gross Roof Area [m2] 3563.11
Skylight Area [m2] 0.00
Skylight-Roof Ratio [%] 0.00


PERFORMANCE

Zone Summary

Area [m2] Conditioned (Y/N) Part of Total Floor Area (Y/N) Volume [m3] Multipliers Above Ground Gross Wall Area [m2] Underground Gross Wall Area [m2] Window Glass Area [m2] Opening Area [m2] Lighting [W/m2] People [m2 per person] Plug and Process [W/m2]
BASEMENT 2779.43 Yes Yes 6779.02 1.00 0.00 397.05 0.00 0.00 10.2732 18.58 4.8418
CORE_BOTTOM 2496.12 Yes Yes 6849.35 1.00 0.00 0.00 0.00 0.00 10.2732 18.58 8.0697
CORE_MID 2496.12 Yes Yes 6849.35 10.00 0.00 0.00 0.00 0.00 10.2732 18.58 8.0696
CORE_TOP 2496.12 Yes Yes 6849.35 1.00 0.00 0.00 0.00 0.00 10.2732 18.58 8.0696
PERIMETER_BOT_ZN_3 313.41 Yes Yes 860.00 1.00 200.61 0.00 115.90 115.90 10.2732 18.58 8.0700
PERIMETER_BOT_ZN_2 201.98 Yes Yes 554.22 1.00 133.74 0.00 77.26 77.26 10.2732 18.58 8.0700
PERIMETER_BOT_ZN_1 313.42 Yes Yes 860.02 1.00 200.61 0.00 115.90 115.90 10.2732 18.58 8.0699
PERIMETER_BOT_ZN_4 201.98 Yes Yes 554.22 1.00 133.74 0.00 77.26 77.26 10.2732 18.58 8.0699
PERIMETER_MID_ZN_3 313.41 Yes Yes 860.00 10.00 200.61 0.00 115.90 115.90 10.2732 18.58 8.0700
PERIMETER_MID_ZN_2 201.98 Yes Yes 554.22 10.00 133.74 0.00 77.26 77.26 10.2732 18.58 8.0700
PERIMETER_MID_ZN_1 313.42 Yes Yes 860.02 10.00 200.61 0.00 115.90 115.90 10.2732 18.58 8.0699
PERIMETER_MID_ZN_4 201.98 Yes Yes 554.22 10.00 133.74 0.00 77.26 77.26 10.2732 18.58 8.0699
PERIMETER_TOP_ZN_3 313.41 Yes Yes 860.00 1.00 200.61 0.00 115.90 115.90 10.2732 18.58 8.0700
PERIMETER_TOP_ZN_2 201.98 Yes Yes 554.22 1.00 133.74 0.00 77.26 77.26 10.2732 18.58 8.0700
PERIMETER_TOP_ZN_1 313.42 Yes Yes 860.02 1.00 200.61 0.00 115.90 115.90 10.2732 18.58 8.0699
PERIMETER_TOP_ZN_4 201.98 Yes Yes 554.22 1.00 133.74 0.00 77.26 77.26 10.2732 18.58 8.0699
GROUNDFLOOR_PLENUM 3563.11 Yes No 4344.14 1.00 297.11 0.00 0.00 0.00 0.0000   0.0000
MIDFLOOR_PLENUM 3563.11 Yes No 4344.14 10.00 297.11 0.00 0.00 0.00 0.0000   0.0000
TOPFLOOR_PLENUM 3563.11 Yes No 4344.14 1.00 297.11 0.00 0.00 0.00 0.0000   0.0000
DATACENTER_BOT_ZN_6 36.20 Yes Yes 99.34 1.00 0.00 0.00 0.00 0.00 17.8735 18.58 215.2992
DATACENTER_MID_ZN_6 36.20 Yes Yes 99.34 10.00 0.00 0.00 0.00 0.00 17.8735 18.58 215.2992
DATACENTER_TOP_ZN_6 36.20 Yes Yes 99.34 1.00 0.00 0.00 0.00 0.00 17.8735 18.58 215.2992
DATACENTER_BASEMENT_ZN_6 783.68 Yes Yes 1911.37 1.00 0.00 197.31 0.00 0.00 10.2732 18.58 484.4232
Total 46320.38     126016.35   8024.24 594.36 4635.80 4635.80 10.3445 18.58 17.8789
Conditioned Total 46320.38     126016.35   8024.24 594.36 4635.80 4635.80 10.3445 18.58 17.8789
Unconditioned Total 0.00     0.00   0.00 0.00 0.00 0.00      
Not Part of Total 42757.27     52129.67   3565.29 0.00 0.00 0.00 0.0000   0.0000


Space Summary

Area [m2] Conditioned (Y/N) Part of Total Floor Area (Y/N) Multipliers Zone Name Space Type Radiant/Solar Enclosure Name Lighting [W/m2] People [m2 per person] Plug and Process [W/m2] Tags
BASEMENT 2779.43 Yes Yes 1.00 BASEMENT GENERAL BASEMENT 10.2732 18.58 4.8418  
CORE_BOTTOM 2496.12 Yes Yes 1.00 CORE_BOTTOM GENERAL CORE_BOTTOM 10.2732 18.58 8.0697  
CORE_MID 2496.12 Yes Yes 10.00 CORE_MID GENERAL CORE_MID 10.2732 18.58 8.0696  
CORE_TOP 2496.12 Yes Yes 1.00 CORE_TOP GENERAL CORE_TOP 10.2732 18.58 8.0696  
PERIMETER_BOT_ZN_3 313.41 Yes Yes 1.00 PERIMETER_BOT_ZN_3 GENERAL PERIMETER_BOT_ZN_3 10.2732 18.58 8.0700  
PERIMETER_BOT_ZN_2 201.98 Yes Yes 1.00 PERIMETER_BOT_ZN_2 GENERAL PERIMETER_BOT_ZN_2 10.2732 18.58 8.0700  
PERIMETER_BOT_ZN_1 313.42 Yes Yes 1.00 PERIMETER_BOT_ZN_1 GENERAL PERIMETER_BOT_ZN_1 10.2732 18.58 8.0699  
PERIMETER_BOT_ZN_4 201.98 Yes Yes 1.00 PERIMETER_BOT_ZN_4 GENERAL PERIMETER_BOT_ZN_4 10.2732 18.58 8.0699  
PERIMETER_MID_ZN_3 313.41 Yes Yes 10.00 PERIMETER_MID_ZN_3 GENERAL PERIMETER_MID_ZN_3 10.2732 18.58 8.0700  
PERIMETER_MID_ZN_2 201.98 Yes Yes 10.00 PERIMETER_MID_ZN_2 GENERAL PERIMETER_MID_ZN_2 10.2732 18.58 8.0700  
PERIMETER_MID_ZN_1 313.42 Yes Yes 10.00 PERIMETER_MID_ZN_1 GENERAL PERIMETER_MID_ZN_1 10.2732 18.58 8.0699  
PERIMETER_MID_ZN_4 201.98 Yes Yes 10.00 PERIMETER_MID_ZN_4 GENERAL PERIMETER_MID_ZN_4 10.2732 18.58 8.0699  
PERIMETER_TOP_ZN_3 313.41 Yes Yes 1.00 PERIMETER_TOP_ZN_3 GENERAL PERIMETER_TOP_ZN_3 10.2732 18.58 8.0700  
PERIMETER_TOP_ZN_2 201.98 Yes Yes 1.00 PERIMETER_TOP_ZN_2 GENERAL PERIMETER_TOP_ZN_2 10.2732 18.58 8.0700  
PERIMETER_TOP_ZN_1 313.42 Yes Yes 1.00 PERIMETER_TOP_ZN_1 GENERAL PERIMETER_TOP_ZN_1 10.2732 18.58 8.0699  
PERIMETER_TOP_ZN_4 201.98 Yes Yes 1.00 PERIMETER_TOP_ZN_4 GENERAL PERIMETER_TOP_ZN_4 10.2732 18.58 8.0699  
GROUNDFLOOR_PLENUM 3563.11 Yes No 1.00 GROUNDFLOOR_PLENUM GENERAL GROUNDFLOOR_PLENUM 0.0000 0.00 0.0000  
MIDFLOOR_PLENUM 3563.11 Yes No 10.00 MIDFLOOR_PLENUM GENERAL MIDFLOOR_PLENUM 0.0000 0.00 0.0000  
TOPFLOOR_PLENUM 3563.11 Yes No 1.00 TOPFLOOR_PLENUM GENERAL TOPFLOOR_PLENUM 0.0000 0.00 0.0000  
DATACENTER_BOT_ZN_6 36.20 Yes Yes 1.00 DATACENTER_BOT_ZN_6 GENERAL DATACENTER_BOT_ZN_6 17.8735 18.58 215.2992  
DATACENTER_MID_ZN_6 36.20 Yes Yes 10.00 DATACENTER_MID_ZN_6 GENERAL DATACENTER_MID_ZN_6 17.8735 18.58 215.2992  
DATACENTER_TOP_ZN_6 36.20 Yes Yes 1.00 DATACENTER_TOP_ZN_6 GENERAL DATACENTER_TOP_ZN_6 17.8735 18.58 215.2992  
DATACENTER_BASEMENT_ZN_6 783.68 Yes Yes 1.00 DATACENTER_BASEMENT_ZN_6 GENERAL DATACENTER_BASEMENT_ZN_6 10.2732 18.58 484.4232  
Total 46320.38             10.3445 9.29 17.8789  
Conditioned Total 46320.38             10.3445 9.29 17.8789  
Unconditioned Total 0.00             0.0000 0.00 0.0000  
Not Part of Total 42757.27             0.0000 0.00 0.0000  


Space Type Summary

Total Area [m2] Conditioned Area [m2] Unconditioned Area [m2] Not Part of Total Area [m2] Lighting [W/m2] People [m2 per person] Plug and Process [W/m2]
GENERAL 46320.38 46320.38 0.00 42757.27 3.1788 60.38 10.8345
Total 46320.38 46320.38 0.00 42757.27      



Table of Contents

Report: Demand End Use Components Summary

For: Entire Facility

Timestamp: 2023-10-16 08:43:34

End Uses

Electricity [W] Natural Gas [W] Gasoline [W] Diesel [W] Coal [W] Fuel Oil No 1 [W] Fuel Oil No 2 [W] Propane [W] Other Fuel 1 [W] Other Fuel 2 [W] District Cooling [W] Steam [W] Water [m3/s]
Time of Peak 16-AUG-15:20 02-JAN-05:10 - - - - - - - - - - 24-AUG-16:40
Heating 0.00 1892175.57 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 494854.71 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 332294.83 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 778371.69 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 84450.25 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 265704.45 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 58466.29 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 93402.74 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 5613.48 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 8146.58 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                           
Total End Uses 2113158.43 1900322.15 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


End Uses By Subcategory

Subcategory Electricity [W] Natural Gas [W] Gasoline [W] Diesel [W] Coal [W] Fuel Oil No 1 [W] Fuel Oil No 2 [W] Propane [W] Other Fuel 1 [W] Other Fuel 2 [W] District Cooling [W] Steam [W] Water [m3/s]
Heating General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Boiler 0.00 1892175.57 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Boiler Parasitic 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling General 494854.71 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting LightsWired 332294.83 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment MiscPlug 305206.10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  DataCenterPlugLoads 473165.59 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment Transformer 5015.67 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  ElevatorLift 79171.38 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  ElevatorLightsFan 263.20 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans General 265704.45 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps General 58466.29 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection General 93402.74 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery General 5613.48 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  WaterUse 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Water Heater 0.00 8146.58 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: Source Energy End Use Components Summary

For: Entire Facility

Timestamp: 2023-10-16 08:43:34

Values gathered over 8760.00 hours



Source Energy End Use Components Summary

Source Electricity [GJ] Source Natural Gas [GJ] Source Gasoline [GJ] Source Diesel [GJ] Source Coal [GJ] Source Fuel Oil No 1 [GJ] Source Fuel Oil No 2 [GJ] Source Propane [GJ] Source Other Fuel 1 [GJ] Source Other Fuel 2 [GJ] Source District Cooling [GJ] Source District Heating [GJ]
Heating 0.00 1468.78 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 11729.22 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 12448.86 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 2212.28 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 46480.15 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 6127.49 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 7726.91 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 1508.92 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 3671.08 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 45.08 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 172.17 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 849.54 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Total Source Energy End Use Components 92122.16 2318.32 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Normalized Metrics

Source Energy End Use Components Per Conditioned Floor Area

Source Electricity [MJ/m2] Source Natural Gas [MJ/m2] Source Gasoline [MJ/m2] Source Diesel [MJ/m2] Source Coal [MJ/m2] Source Fuel Oil No 1 [MJ/m2] Source Fuel Oil No 2 [MJ/m2] Source Propane [MJ/m2] Source Other Fuel 1 [MJ/m2] Source Other Fuel 2 [MJ/m2] Source District Cooling [MJ/m2] Source District Heating [MJ/m2]
Heating 0.00 31.71 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 253.22 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 268.76 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 47.76 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 1003.45 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 132.28 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 166.81 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 32.58 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 79.25 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.97 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 3.72 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 18.34 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Total Source Energy End Use Components 1988.80 50.05 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Source Energy End Use Components Per Total Floor Area

Source Electricity [MJ/m2] Source Natural Gas [MJ/m2] Source Gasoline [MJ/m2] Source Diesel [MJ/m2] Source Coal [MJ/m2] Source Fuel Oil No 1 [MJ/m2] Source Fuel Oil No 2 [MJ/m2] Source Propane [MJ/m2] Source Other Fuel 1 [MJ/m2] Source Other Fuel 2 [MJ/m2] Source District Cooling [MJ/m2] Source District Heating [MJ/m2]
Heating 0.00 31.71 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 253.22 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 268.76 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 47.76 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 1003.45 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 132.28 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 166.81 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 32.58 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 79.25 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.97 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 3.72 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 18.34 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Total Source Energy End Use Components 1988.80 50.05 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: Component Sizing Summary

For: Entire Facility

Timestamp: 2023-10-16 08:43:34

AirTerminal:SingleDuct:ConstantVolume:NoReheat

Design Size Maximum Air Flow Rate [m3/s]
BASEMENT DIRECT AIR 5.96
DATACENTER_BOT_ZN_6 DIRECT AIR 0.493358
DATACENTER_MID_ZN_6 DIRECT AIR 4.73
DATACENTER_TOP_ZN_6 DIRECT AIR 0.481181
DATACENTER_BASEMENT_ZN_6 DIRECT AIR 21.41
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

AirTerminal:SingleDuct:VAV:Reheat

Design Size Maximum Air Flow Rate [m3/s] Design Size Constant Minimum Air Flow Fraction User-Specified Constant Minimum Air Flow Fraction Design Size Minimum Air Flow Rate [m3/s] Design Size Maximum Flow Fraction during Reheat [] User-Specified Maximum Flow Fraction during Reheat [] Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] Design Size Maximum Reheat Water Flow Rate [m3/s] Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] Design Size Reheat Coil Sizing Inlet Air Temperature [C] Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir]
CORE_BOTTOM VAV BOX COMPONENT 6.19 0.307300 0.319000 1.97 0.819467 0.500000 0.001240 0.000174 1.97 12.80 0.008000
CORE_MID VAV BOX COMPONENT 58.40 0.325706 0.332000 19.39 0.868550 0.500000 0.001170 0.004395 19.39 12.80 0.008000
CORE_TOP VAV BOX COMPONENT 5.92 0.321462 0.336000 1.99 0.857232 0.500000 0.001185 0.000792 2.70 12.80 0.008000
PERIMETER_BOT_ZN_3 VAV BOX COMPONENT 1.09 0.219486 0.228000 0.248084 0.585296 0.500000 0.001736 0.000145 0.495461 12.80 0.008000
PERIMETER_BOT_ZN_2 VAV BOX COMPONENT 1.34 0.114500 0.200000 0.268830 0.305333 0.500000 0.003328 0.000099 0.336569 12.80 0.008000
PERIMETER_BOT_ZN_1 VAV BOX COMPONENT 1.56 0.153532 0.200000 0.311108 0.409419 0.500000 0.002482 0.000159 0.542355 12.80 0.008000
PERIMETER_BOT_ZN_4 VAV BOX COMPONENT 1.63 0.094640 0.200000 0.325244 0.300000 0.500000 0.004026 0.000085 0.325244 12.80 0.008000
PERIMETER_MID_ZN_3 VAV BOX COMPONENT 10.47 0.228157 0.233000 2.44 0.608419 0.500000 0.001670 0.002460 8.40 12.80 0.008000
PERIMETER_MID_ZN_2 VAV BOX COMPONENT 14.36 0.107147 0.200000 2.87 0.300000 0.500000 0.003556 0.001612 5.50 12.80 0.008000
PERIMETER_MID_ZN_1 VAV BOX COMPONENT 15.53 0.153787 0.200000 3.11 0.410098 0.500000 0.002477 0.002429 8.29 12.80 0.008000
PERIMETER_MID_ZN_4 VAV BOX COMPONENT 15.05 0.102295 0.200000 3.01 0.300000 0.500000 0.003725 0.001574 5.37 12.80 0.008000
PERIMETER_TOP_ZN_3 VAV BOX COMPONENT 1.18 0.202870 0.212000 0.249569 0.540986 0.500000 0.001878 0.000307 1.05 12.80 0.008000
PERIMETER_TOP_ZN_2 VAV BOX COMPONENT 1.46 0.105463 0.200000 0.291866 0.300000 0.500000 0.003613 0.000201 0.685245 12.80 0.008000
PERIMETER_TOP_ZN_1 VAV BOX COMPONENT 1.67 0.142627 0.200000 0.334897 0.380338 0.500000 0.002671 0.000304 1.04 12.80 0.008000
PERIMETER_TOP_ZN_4 VAV BOX COMPONENT 1.59 0.096813 0.200000 0.317942 0.300000 0.500000 0.003935 0.000198 0.677576 12.80 0.008000
User-Specified values were used. Design Size values were used if no User-Specified values were provided. Design Size values may be derived from alternate User-Specified values.

Coil:Heating:Water

Design Size Rated Capacity [W] Design Size Maximum Water Flow Rate [m3/s] Design Size U-Factor Times Area Value [W/K]
CORE_BOTTOM VAV BOX REHEAT COIL 19871.01 0.000174 400.58
CORE_MID VAV BOX REHEAT COIL 502362.85 0.004395 12020.25
CORE_TOP VAV BOX REHEAT COIL 90567.17 0.000792 2390.90
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL 16611.22 0.000145 438.18
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL 11282.69 0.000099 297.61
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL 18180.52 0.000159 479.54
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL 9669.44 0.000085 242.60
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL 281179.94 0.002460 7413.08
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL 184302.05 0.001612 4858.90
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL 277679.97 0.002429 7320.87
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL 179958.26 0.001574 4744.43
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL 35087.95 0.000307 924.93
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL 22938.67 0.000201 604.66
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL 34713.48 0.000304 915.06
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL 22682.07 0.000198 597.90
VAV_BOT WITH REHEAT HEATING COIL 72503.51 0.000634 1172.86
VAV_MID WITH REHEAT HEATING COIL 691595.11 0.006050 11173.04
VAV_TOP WITH REHEAT HEATING COIL 68252.18 0.000597 1113.66
CAV_BAS HEATING COIL 303799.48 0.002658 6686.54
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

AirLoopHVAC

Sum of Air Terminal Maximum Heating Flow Rates [m3/s] Sum of Air Terminal Minimum Heating Flow Rates [m3/s] Sum of Air Terminal Maximum Flow Rates [m3/s] Adjusted Heating Design Air Flow Rate [m3/s] Adjusted Cooling Design Air Flow Rate [m3/s] Adjusted Main Design Air Flow Rate [m3/s] User Heating Air Flow Ratio [] Calculated Heating Air Flow Ratio [] Design Supply Air Flow Rate [m3/s]
VAV_BOT WITH REHEAT 5.90 3.13 11.80 3.13 10.39 10.39 0.300000 0.300988 10.39
VAV_MID WITH REHEAT 56.90 30.81 113.80 40.54 97.93 97.93 0.300000 0.413984 97.93
VAV_TOP WITH REHEAT 5.91 3.18 11.82 6.14 10.67 10.67 0.300000 0.576134 10.67
CAV_BAS 5.96 5.96 5.96 5.96 5.96 5.96 1.00 1.00 5.96
AIRLOOP DATACENTER BASEMENT 21.41 21.41 21.41 21.41 21.41 21.41 1.00 0.999991 21.41
AIRLOOP DATACENTER BOT 0.493358 0.493358 0.493358 0.493358 0.493358 0.493358 1.00 1.00 0.493358
AIRLOOP DATACENTER MID 4.73 4.73 4.73 4.73 4.73 4.73 1.00 1.00 4.73
AIRLOOP DATACENTER TOP 0.481181 0.481181 0.481181 0.481181 0.481181 0.481181 1.00 1.00 0.481181
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Controller:OutdoorAir

Maximum Outdoor Air Flow Rate [m3/s] Minimum Outdoor Air Flow Rate [m3/s]
VAV_BOT WITH REHEAT_OA_CONTROLLER 10.39 2.54
VAV_MID WITH REHEAT_OA_CONTROLLER 97.93 25.38
VAV_TOP WITH REHEAT_OA_CONTROLLER 10.67 2.54
CAV_BAS_OA_CONTROLLER 5.96 1.20
AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER 21.41 0.338393
AIRLOOP DATACENTER BOT_OA_CONTROLLER 0.493358 0.015632
AIRLOOP DATACENTER MID_OA_CONTROLLER 4.73 0.156323
AIRLOOP DATACENTER TOP_OA_CONTROLLER 0.481181 0.015632
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

HeatExchanger:AirToAir:SensibleAndLatent

Design Size Nominal Supply Air Flow Rate [m3/s]
VAV_BOT WITH REHEAT OA HEAT RECOVERY 2.54
VAV_MID WITH REHEAT OA HEAT RECOVERY 25.38
VAV_TOP WITH REHEAT OA HEAT RECOVERY 2.54
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Coil:Cooling:Water

Design Size Design Inlet Air Temperature [C] Design Size Design Inlet Water Temperature [C] Design Size Design Outlet Air Temperature [C] Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] Design Size Design Coil Load [W] Design Size Design Water Flow Rate [m3/s] Design Size Design Air Flow Rate [m3/s]
VAV_BOT WITH REHEAT COOLING COIL 26.03 6.67 11.06 0.010185 0.008500 244927.46 0.010420 10.39
VAV_MID WITH REHEAT COOLING COIL 26.20 6.67 10.96 0.010372 0.008500 2396783.59 0.101965 97.93
VAV_TOP WITH REHEAT COOLING COIL 25.93 6.67 11.06 0.010171 0.008500 249517.12 0.010615 10.67
CAV_BAS COOLING COIL 24.58 6.67 11.42 0.009967 0.008500 123071.04 0.005236 5.96
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Fan:VariableVolume

Design Size Maximum Flow Rate [m3/s]
VAV_BOT WITH REHEAT FAN 10.39
VAV_MID WITH REHEAT FAN 97.93
VAV_TOP WITH REHEAT FAN 10.67
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Controller:WaterCoil

Maximum Actuated Flow [m3/s] Controller Convergence Tolerance
VAV_BOT WITH REHEAT_COOLC_CONTROLLER 0.010420 0.000046
VAV_BOT WITH REHEAT_HEATC_CONTROLLER 0.000634  
VAV_MID WITH REHEAT_COOLC_CONTROLLER 0.101965 0.000005
VAV_MID WITH REHEAT_HEATC_CONTROLLER 0.006050  
VAV_TOP WITH REHEAT_COOLC_CONTROLLER 0.010615 0.000045
VAV_TOP WITH REHEAT_HEATC_CONTROLLER 0.000597  
CAV_BAS_COOLC_CONTROLLER 0.005236 0.000091
CAV_BAS_HEATC_CONTROLLER 0.002658  
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Fan:ConstantVolume

Design Size Maximum Flow Rate [m3/s]
CAV_BAS FAN 5.96
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT

Design Size Rated Air Flow Rate [m3/s] Design Size Rated Total Cooling Capacity [W] Design Size Rated Sensible Cooling Capacity [W] Design Size Rated Water Flow Rate [m3/s]
AIRLOOP DATACENTER BASEMENT COOLING COIL 21.41 433170.49 312730.66 0.010608
AIRLOOP DATACENTER BOT COOLING COIL 0.493358 9910.60 7177.44 0.000243
AIRLOOP DATACENTER MID COOLING COIL 4.73 95118.13 68824.67 0.002329
AIRLOOP DATACENTER TOP COOLING COIL 0.481181 9678.21 7004.39 0.000237
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

AirLoopHVAC:UnitaryHeatPump:WaterToAir

Supply Air Flow Rate [m3/s] Supply Air Flow Rate During Heating Operation [m3/s] Supply Air Flow Rate During Cooling Operation [m3/s] Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] Nominal Heating Capacity [W] Nominal Cooling Capacity [W] Supplemental Heating Coil Nominal Capacity [W] Fraction of Supply Air Flow That Goes Through the Controlling Zone
AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP 21.41 21.41 21.41 21.41 433170.49 433170.49 20749.82 1.00
AIRLOOP DATACENTER BOT DXAC HEAT PUMP 0.493358 0.493358 0.493358 0.493358 9910.60 9910.60 958.56 1.00
AIRLOOP DATACENTER MID DXAC HEAT PUMP 4.73 4.73 4.73 4.73 95118.13 95118.13 9585.56 1.00
AIRLOOP DATACENTER TOP DXAC HEAT PUMP 0.481181 0.481181 0.481181 0.481181 9678.21 9678.21 958.56 1.00
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Fan:OnOff

Design Size Maximum Flow Rate [m3/s]
AIRLOOP DATACENTER BASEMENT SUPPLY FAN 21.41
AIRLOOP DATACENTER BOT SUPPLY FAN 0.493358
AIRLOOP DATACENTER MID SUPPLY FAN 4.73
AIRLOOP DATACENTER TOP SUPPLY FAN 0.481181
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT

Design Size Rated Air Flow Rate [m3/s] Design Size Rated Heating Capacity [W] Design Size Rated Water Flow Rate [m3/s]
AIRLOOP DATACENTER BASEMENT HEATING COIL 21.41 433170.49 0.010608
AIRLOOP DATACENTER BOT HEATING COIL 0.493358 9910.60 0.000243
AIRLOOP DATACENTER MID HEATING COIL 4.73 95118.13 0.002329
AIRLOOP DATACENTER TOP HEATING COIL 0.481181 9678.21 0.000237
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Coil:Heating:Electric

Design Size Nominal Capacity [W]
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL 20749.82
AIRLOOP DATACENTER BOT_SUPPHEATCOIL 958.56
AIRLOOP DATACENTER MID_SUPPHEATCOIL 9585.56
AIRLOOP DATACENTER TOP_SUPPHEATCOIL 958.56
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Humidifier:Steam:Electric

Design Size Nominal Capacity Volume [m3/s] User-Specified Nominal Capacity Volume [m3/s] Design Size Rated Power [W] User-Specified Rated Power [W]
DATACENTER_BASEMENT_ZN_6 HUMIDIFIER 0.000174 0.000037 96450.70 100000.00
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Pump:VariableSpeed

Design Flow Rate [m3/s] Design Power Consumption [W] Design Minimum Flow Rate [m3/s]
COOLSYS1 PUMP SECONDARY 0.128235 20936.90  
HEATSYS1 PUMP 0.024874 7490.92 0.000000
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

PlantLoop

Maximum Loop Flow Rate [m3/s] Plant Loop Volume [m3]
COOLSYS1_DEMAND 0.128235 15.39
HEATSYS1 0.024874 2.98
COOLSYS1_SUPPLY 0.128235 15.39
SINGLE WATER PLANT LOOP 0.013417 1.61
SWHSYS1 0.000440 0.052800
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

HeatExchanger:FluidToFluid

Loop Supply Side Design Fluid Flow Rate [m3/s] Loop Demand Side Design Fluid Flow Rate [m3/s] Heat Exchanger U-Factor Times Area Value [W/C] Loop-to-loop Temperature Difference Used to Size Heat Exchanger U-Factor Times Area Value [C]
BYPASS HEAT EXCHANGER 0.128235 0.128235 538267.72 5.60
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Boiler:HotWater

Design Size Nominal Capacity [W] User-Specified Nominal Capacity [W] Design Size Design Water Flow Rate [m3/s]
HEATSYS1 BOILER 2843237.57 2843237.57 0.024874
CENTRAL BOILER 552685.27 542032.73 0.013417
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Pump:ConstantSpeed

Design Flow Rate [m3/s] Design Power Consumption [W]
COOLSYS1 CHILLER1 PUMP 0.064118 7247.66
COOLSYS1 CHILLER2 PUMP 0.064118 7247.66
PLANT CIRC PUMP 0.013417 3422.13
SWHSYS1 PUMP 0.000440 56.21
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Chiller:Electric:ReformulatedEIR

Design Size Reference Chilled Water Flow Rate [m3/s] User-Specified Reference Chilled Water Flow Rate [m3/s] Design Size Reference Capacity [W] User-Specified Reference Capacity [W] Design Size Reference Condenser Water Flow Rate [m3/s]
COOLSYS1 CHILLER1 0.128235 0.064505 1519979.80 1527224.44 0.075577
COOLSYS1 CHILLER2 0.128235 0.064505 1519979.80 1527224.44 0.075577
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

FluidCooler:TwoSpeed

Design Water Flow Rate [m3/s] Air Flow Rate at High Fan Speed [m3/s] Fluid cooler UA value at high fan speed based on nominal capacity input [W/K] Air Flow Rate at Low Fan Speed [m3/s] Fan Power at Low Fan Speed [W] U-factor Times Area Value at Low Fan Speed [W/C]
CENTRAL TOWER 0.013417 139666.47 58790.17 69833.23 7879.72 21366.71
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

WaterHeater:Mixed

Use Side Design Flow Rate [m3/s]
SWHSYS1 WATER HEATER 0.000440
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

CondenserLoop

Maximum Loop Flow Rate [m3/s] Condenser Loop Volume [m3]
TOWERWATERSYS 0.151153 18.14
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

HeaderedPumps:VariableSpeed

Design Flow Rate [m3/s] Design Power Consumption [W]
TOWERWATERSYS PUMP 0.151153 37422.23
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

CoolingTower:VariableSpeed

Design Air Flow Rate [m3/s] Nominal Capacity [W] Air Flow Rate in free convection regime [m3/s] Tower capacity in free convection regime at design conditions [W]
TOWERWATERSYS COOLTOWER 1 58.13 1812006.78 11.63 226500.85
TOWERWATERSYS COOLTOWER 2 58.13 1812006.78 11.63 226500.85
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

PlantEquipmentOperation:ComponentSetPoint

Design Water Flow Rate [m3/s] Equipment # 47
WSHPPLANT OPERATION SCHEME 0.078500
User-Specified values were used. Design Size values were used if no User-Specified values were provided.


Table of Contents

Report: Surface Shadowing Summary

For: Entire Facility

Timestamp: 2023-10-16 08:43:34

Surfaces (Walls, Roofs, etc) that may be Shadowed by Other Surfaces

None


Subsurfaces (Windows and Doors) that may be Shadowed by Surfaces

Possible Shadow Receivers
PERIMETER_BOT_ZN_3_WALL_NORTH PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 |
PERIMETER_BOT_ZN_2_WALL_EAST PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 |
PERIMETER_BOT_ZN_1_WALL_SOUTH PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 |
PERIMETER_BOT_ZN_4_WALL_WEST PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 |
PERIMETER_MID_ZN_3_WALL_NORTH PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW |
PERIMETER_MID_ZN_2_WALL_EAST PERIMETER_MID_ZN_2_WALL_EAST_WINDOW |
PERIMETER_MID_ZN_1_WALL_SOUTH PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW |
PERIMETER_MID_ZN_4_WALL_WEST PERIMETER_MID_ZN_4_WALL_WEST_WINDOW |
PERIMETER_TOP_ZN_3_WALL_NORTH PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW |
PERIMETER_TOP_ZN_2_WALL_EAST PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW |
PERIMETER_TOP_ZN_1_WALL_SOUTH PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW |
PERIMETER_TOP_ZN_4_WALL_WEST PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW |



Table of Contents

Report: Adaptive Comfort Summary

For: Entire Facility

Timestamp: 2023-10-16 08:43:34

Time Not Meeting the Adaptive Comfort Models during Occupied Hours

ASHRAE55 90% Acceptability Limits [Hours] ASHRAE55 80% Acceptability Limits [Hours] CEN15251 Category I Acceptability Limits [Hours] CEN15251 Category II Acceptability Limits [Hours] CEN15251 Category III Acceptability Limits [Hours]



Table of Contents

Report: Initialization Summary

For: Entire Facility

Timestamp: 2023-10-16 08:43:34

Version

Version ID
1 22.1.0


Timesteps per Hour

#TimeSteps Minutes per TimeStep {minutes}
1 6 10


System Convergence Limits

Minimum System TimeStep {minutes} Max HVAC Iterations Minimum Plant Iterations Maximum Plant Iterations
1 1 20 2 8


Simulation Control

Do Zone Sizing Do System Sizing Do Plant Sizing Do Design Days Do Weather Simulation Do HVAC Sizing Simulation
1 Yes Yes Yes No Yes No


Performance Precision Tradeoffs

Use Coil Direct Simulation Zone Radiant Exchange Algorithm Override Mode Number of Timestep In Hour Force Euler Method Minimum Number of Warmup Days Force Suppress All Begin Environment Resets Minimum System Timestep MaxZoneTempDiff MaxAllowedDelTemp
1 No ScriptF Normal 6 No 1 No 1.0 0.300 2.0000E-003


Output Reporting Tolerances

Tolerance for Time Heating Setpoint Not Met Tolerance for Zone Cooling Setpoint Not Met Time
1 0.556 0.556


Site:GroundTemperature:BuildingSurface

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00


Site:GroundTemperature:FCfactorMethod

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 14.00 7.30 3.30 1.20 -0.20 5.60 10.90 16.10 21.70 25.00 24.80 19.90


Site:GroundTemperature:Shallow

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00


Site:GroundTemperature:Deep

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00


Site:GroundReflectance

Jan{dimensionless} Feb{dimensionless} Mar{dimensionless} Apr{dimensionless} May{dimensionless} Jun{dimensionless} Jul{dimensionless} Aug{dimensionless} Sep{dimensionless} Oct{dimensionless} Nov{dimensionless} Dec{dimensionless}
1 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20


Site:GroundReflectance:SnowModifier

Normal Daylighting {dimensionless}
1 1.000 1.000


Site:GroundReflectance:Snow

Jan{dimensionless} Feb{dimensionless} Mar{dimensionless} Apr{dimensionless} May{dimensionless} Jun{dimensionless} Jul{dimensionless} Aug{dimensionless} Sep{dimensionless} Oct{dimensionless} Nov{dimensionless} Dec{dimensionless}
1 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20


Site:GroundReflectance:Snow:Daylighting

Jan{dimensionless} Feb{dimensionless} Mar{dimensionless} Apr{dimensionless} May{dimensionless} Jun{dimensionless} Jul{dimensionless} Aug{dimensionless} Sep{dimensionless} Oct{dimensionless} Nov{dimensionless} Dec{dimensionless}
1 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20


Environment:Weather Station

Wind Sensor Height Above Ground {m} Wind Speed Profile Exponent {} Wind Speed Profile Boundary Layer Thickness {m} Air Temperature Sensor Height Above Ground {m} Wind Speed Modifier Coefficient-Internal Temperature Modifier Coefficient-Internal
1 10.000 0.140 270.000 1.500 1.586 9.750E-003


Site:Location

Location Name Latitude {N+/S- Deg} Longitude {E+/W- Deg} Time Zone Number {GMT+/-} Elevation {m} Standard Pressure at Elevation {Pa} Standard RhoAir at Elevation
1 New York-John F Kennedy Intl AP NY USA TMY3 WMO#=744860 40.65 -73.80 -5.00 5.00 101265 1.2036


Site Water Mains Temperature Information

Calculation Method{} Water Mains Temperature Schedule Name{} Annual Average Outdoor Air Temperature{C} Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} Fixed Default Water Mains Temperature{C}
1 Correlation NA 12.47 25.20 NA


Building Information

Building Name North Axis {deg} Terrain Loads Convergence Tolerance Value Temperature Convergence Tolerance Value Solar Distribution Maximum Number of Warmup Days Minimum Number of Warmup Days
1 OfficeLarge 0.000 City 4.00000E-002 0.20000 FullInteriorAndExterior 25 6


Inside Convection Algorithm

Algorithm {Simple
TARP
CeilingDiffuser
AdaptiveConvectionAlgorithm}
1 TARP


Outside Convection Algorithm

Algorithm {SimpleCombined
TARP
MoWitt
DOE-2
AdaptiveConvectionAlgorithm}
1 TARP


Sky Radiance Distribution

Value {Anisotropic}
1 Anisotropic


Zone Air Solution Algorithm

Value {ThirdOrderBackwardDifference
AnalyticalSolution
EulerMethod}
1 ThirdOrderBackwardDifference


Zone Air Carbon Dioxide Balance Simulation

Simulation {Yes/No} Carbon Dioxide Concentration
1 No N/A


Zone Air Generic Contaminant Balance Simulation

Simulation {Yes/No} Generic Contaminant Concentration
1 No N/A


Zone Air Mass Flow Balance Simulation

Enforce Mass Balance



Adjust Zone Mixing and Return {AdjustMixingOnly
AdjustReturnOnly
AdjustMixingThenReturn
AdjustReturnThenMixing
None}
Adjust Zone Infiltration {AddInfiltration
AdjustInfiltration
None}

Infiltration Zones {MixingSourceZonesOnly
AllZones}


1 No N/A N/A N/A


HVACSystemRootFindingAlgorithm

Value {RegulaFalsi
Bisection
BisectionThenRegulaFalsi
RegulaFalsiThenBisection}
1 RegulaFalsi


Environment:Site Atmospheric Variation

Wind Speed Profile Exponent {} Wind Speed Profile Boundary Layer Thickness {m} Air Temperature Gradient Coefficient {K/m}
1 0.330 460.000 6.500000E-003


Surface Geometry

Starting Corner Vertex Input Direction Coordinate System Daylight Reference Point Coordinate System Rectangular (Simple) Surface Coordinate System
1 UpperLeftCorner Counterclockwise RelativeCoordinateSystem RelativeCoordinateSystem RelativeToZoneOrigin


Surface Heat Transfer Algorithm

Value {CTF - ConductionTransferFunction
EMPD - MoisturePenetrationDepthConductionTransferFunction
CondFD - ConductionFiniteDifference
HAMT - CombinedHeatAndMoistureFiniteElement} - Description
Inside Surface Max Temperature Limit{C}


Surface Convection Coefficient Lower Limit {W/m2-K}


Surface Convection Coefficient Upper Limit {W/m2-K}


1 CTF - ConductionTransferFunction 200 0.10 1000.0


Shading Summary

Number of Fixed Detached Shades Number of Building Detached Shades Number of Attached Shades
1 0 0 0


Zone Summary

Number of Zones Number of Zone Surfaces Number of SubSurfaces
1 23 221 36


Zone Information

Zone Name North Axis {deg} Origin X-Coordinate {m} Origin Y-Coordinate {m} Origin Z-Coordinate {m} Centroid X-Coordinate {m} Centroid Y-Coordinate {m} Centroid Z-Coordinate {m} Type Zone Multiplier Zone List Multiplier Minimum X {m} Maximum X {m} Minimum Y {m} Maximum Y {m} Minimum Z {m} Maximum Z {m} Ceiling Height {m} Volume {m3} Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} Floor Area {m2} Exterior Gross Wall Area {m2} Exterior Net Wall Area {m2} Exterior Window Area {m2} Number of Surfaces Number of SubSurfaces Number of Shading SubSurfaces Part of Total Building Area
1 BASEMENT 0.0 0.00 0.00 0.00 44.59 24.37 -1.22 1 1 1 16.08 73.11 0.00 48.74 -2.44 0.00 2.44 6779.02 TARP TARP 2779.43 0.00 0.00 0.00 9 0 0 Yes
2 CORE_BOTTOM 0.0 0.00 0.00 0.00 37.01 24.37 1.37 1 1 1 5.49 68.53 4.57 44.17 0.00 2.74 2.74 6849.35 TARP TARP 2496.12 0.00 0.00 0.00 7 0 0 Yes
3 CORE_MID 0.0 0.00 0.00 0.00 37.01 24.37 18.14 1 10 1 5.49 68.53 4.57 44.17 16.77 19.51 2.74 6849.35 TARP TARP 2496.12 0.00 0.00 0.00 6 0 0 Yes
4 CORE_TOP 0.0 0.00 0.00 0.00 37.01 24.37 34.91 1 1 1 5.49 68.53 4.57 44.17 33.54 36.28 2.74 6849.35 TARP TARP 2496.12 0.00 0.00 0.00 6 0 0 Yes
5 PERIMETER_BOT_ZN_3 0.0 0.00 0.00 0.00 36.55 46.54 1.37 1 1 1 0.00 73.11 44.17 48.74 0.00 2.74 2.74 860.00 TARP TARP 313.41 200.61 76.91 115.90 8 9 0 Yes
6 PERIMETER_BOT_ZN_2 0.0 0.00 0.00 0.00 70.95 24.37 1.37 1 1 1 68.53 73.11 0.00 48.74 0.00 2.74 2.74 554.22 TARP TARP 201.98 133.74 52.57 77.26 6 5 0 Yes
7 PERIMETER_BOT_ZN_1 0.0 0.00 0.00 0.00 36.55 2.20 1.37 1 1 1 0.00 73.11 0.00 4.57 0.00 2.74 2.74 860.02 TARP TARP 313.42 200.61 76.91 115.90 8 9 0 Yes
8 PERIMETER_BOT_ZN_4 0.0 0.00 0.00 0.00 2.16 24.37 1.37 1 1 1 0.00 4.57 0.00 48.74 0.00 2.74 2.74 554.22 TARP TARP 201.98 133.74 52.57 77.26 6 5 0 Yes
9 PERIMETER_MID_ZN_3 0.0 0.00 0.00 0.00 36.55 46.54 18.14 1 10 1 0.00 73.11 44.17 48.74 16.77 19.51 2.74 860.00 TARP TARP 313.41 200.61 84.71 115.90 7 1 0 Yes
10 PERIMETER_MID_ZN_2 0.0 0.00 0.00 0.00 70.95 24.37 18.14 1 10 1 68.53 73.11 0.00 48.74 16.77 19.51 2.74 554.22 TARP TARP 201.98 133.74 56.47 77.26 6 1 0 Yes
11 PERIMETER_MID_ZN_1 0.0 0.00 0.00 0.00 36.55 2.20 18.14 1 10 1 0.00 73.11 0.00 4.57 16.77 19.51 2.74 860.02 TARP TARP 313.42 200.61 84.71 115.90 7 1 0 Yes
12 PERIMETER_MID_ZN_4 0.0 0.00 0.00 0.00 2.16 24.37 18.14 1 10 1 0.00 4.57 0.00 48.74 16.77 19.51 2.74 554.22 TARP TARP 201.98 133.74 56.47 77.26 6 1 0 Yes
13 PERIMETER_TOP_ZN_3 0.0 0.00 0.00 0.00 36.55 46.54 34.91 1 1 1 0.00 73.11 44.17 48.74 33.54 36.28 2.74 860.00 TARP TARP 313.41 200.61 84.71 115.90 7 1 0 Yes
14 PERIMETER_TOP_ZN_2 0.0 0.00 0.00 0.00 70.95 24.37 34.91 1 1 1 68.53 73.11 0.00 48.74 33.54 36.28 2.74 554.22 TARP TARP 201.98 133.74 56.47 77.26 6 1 0 Yes
15 PERIMETER_TOP_ZN_1 0.0 0.00 0.00 0.00 36.55 2.20 34.91 1 1 1 0.00 73.11 0.00 4.57 33.54 36.28 2.74 860.02 TARP TARP 313.42 200.61 84.71 115.90 7 1 0 Yes
16 PERIMETER_TOP_ZN_4 0.0 0.00 0.00 0.00 2.16 24.37 34.91 1 1 1 0.00 4.57 0.00 48.74 33.54 36.28 2.74 554.22 TARP TARP 201.98 133.74 56.47 77.26 6 1 0 Yes
17 GROUNDFLOOR_PLENUM 0.0 0.00 0.00 0.00 36.55 24.37 3.35 1 1 1 0.00 73.11 0.00 48.74 2.74 3.96 1.22 4344.14 TARP TARP 3563.11 297.11 297.11 0.00 11 0 0 No
18 MIDFLOOR_PLENUM 0.0 0.00 0.00 0.00 36.55 24.37 20.12 1 10 1 0.00 73.11 0.00 48.74 19.51 20.73 1.22 4344.14 TARP TARP 3563.11 297.11 297.11 0.00 11 0 0 No
19 TOPFLOOR_PLENUM 0.0 0.00 0.00 0.00 36.55 24.37 36.89 1 1 1 0.00 73.11 0.00 48.74 36.28 37.50 1.22 4344.14 TARP TARP 3563.11 297.11 297.11 0.00 11 0 0 No
20 DATACENTER_BOT_ZN_6 0.0 5.49 44.17 0.00 5.03 24.37 1.37 1 1 1 4.57 5.49 4.57 44.17 0.00 2.74 2.74 99.34 TARP TARP 36.20 0.00 0.00 0.00 6 0 0 Yes
21 DATACENTER_MID_ZN_6 0.0 4.57 4.57 16.77 5.03 24.37 18.14 1 10 1 4.57 5.49 4.57 44.17 16.77 19.51 2.74 99.34 TARP TARP 36.20 0.00 0.00 0.00 6 0 0 Yes
22 DATACENTER_TOP_ZN_6 0.0 4.57 4.57 33.54 5.03 24.37 34.91 1 1 1 4.57 5.49 4.57 44.17 33.54 36.28 2.74 99.34 TARP TARP 36.20 0.00 0.00 0.00 6 0 0 Yes
23 DATACENTER_BASEMENT_ZN_6 0.0 16.08 0.00 -2.44 8.04 24.37 -1.22 1 1 1 0.00 16.08 0.00 48.74 -2.44 0.00 2.44 1911.37 TARP TARP 783.68 0.00 0.00 0.00 10 0 0 Yes


Zone Internal Gains Nominal

Zone Name Floor Area {m2} # Occupants Area per Occupant {m2/person} Occupant per Area {person/m2} Interior Lighting {W/m2} Electric Load {W/m2} Gas Load {W/m2} Other Load {W/m2} Hot Water Eq {W/m2} Steam Equipment {W/m2} Sum Loads per Area {W/m2} Outdoor Controlled Baseboard Heat
1 BASEMENT 2779.43 149.6 18.579 5.382E-002 10.273 4.842 0.000 0.000 0.000 0.000 15.115 No
2 CORE_BOTTOM 2496.12 134.4 18.579 5.382E-002 10.273 8.070 0.000 0.000 0.000 0.000 18.343 No
3 CORE_MID 2496.12 134.4 18.579 5.382E-002 10.273 8.070 0.000 0.000 0.000 0.000 18.343 No
4 CORE_TOP 2496.12 134.4 18.579 5.382E-002 10.273 8.070 0.000 0.000 0.000 0.000 18.343 No
5 PERIMETER_BOT_ZN_3 313.41 16.9 18.579 5.382E-002 10.273 8.070 0.000 0.000 0.000 0.000 18.343 No
6 PERIMETER_BOT_ZN_2 201.98 10.9 18.579 5.382E-002 10.273 8.070 0.000 0.000 0.000 0.000 18.343 No
7 PERIMETER_BOT_ZN_1 313.42 16.9 18.579 5.382E-002 10.273 8.070 0.000 0.000 0.000 0.000 18.343 No
8 PERIMETER_BOT_ZN_4 201.98 10.9 18.579 5.382E-002 10.273 8.070 0.000 0.000 0.000 0.000 18.343 No
9 PERIMETER_MID_ZN_3 313.41 16.9 18.579 5.382E-002 10.273 8.070 0.000 0.000 0.000 0.000 18.343 No
10 PERIMETER_MID_ZN_2 201.98 10.9 18.579 5.382E-002 10.273 8.070 0.000 0.000 0.000 0.000 18.343 No
11 PERIMETER_MID_ZN_1 313.42 16.9 18.579 5.382E-002 10.273 8.070 0.000 0.000 0.000 0.000 18.343 No
12 PERIMETER_MID_ZN_4 201.98 10.9 18.579 5.382E-002 10.273 8.070 0.000 0.000 0.000 0.000 18.343 No
13 PERIMETER_TOP_ZN_3 313.41 16.9 18.579 5.382E-002 10.273 8.070 0.000 0.000 0.000 0.000 18.343 No
14 PERIMETER_TOP_ZN_2 201.98 10.9 18.579 5.382E-002 10.273 8.070 0.000 0.000 0.000 0.000 18.343 No
15 PERIMETER_TOP_ZN_1 313.42 16.9 18.579 5.382E-002 10.273 8.070 0.000 0.000 0.000 0.000 18.343 No
16 PERIMETER_TOP_ZN_4 201.98 10.9 18.579 5.382E-002 10.273 8.070 0.000 0.000 0.000 0.000 18.343 No
17 GROUNDFLOOR_PLENUM 3563.11 0.0 N/A 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 No
18 MIDFLOOR_PLENUM 3563.11 0.0 N/A 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 No
19 TOPFLOOR_PLENUM 3563.11 0.0 N/A 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 No
20 DATACENTER_BOT_ZN_6 36.20 1.9 18.579 5.382E-002 17.873 215.299 0.000 0.000 0.000 0.000 233.173 No
21 DATACENTER_MID_ZN_6 36.20 1.9 18.579 5.382E-002 17.873 215.299 0.000 0.000 0.000 0.000 233.173 No
22 DATACENTER_TOP_ZN_6 36.20 1.9 18.579 5.382E-002 17.873 215.299 0.000 0.000 0.000 0.000 233.173 No
23 DATACENTER_BASEMENT_ZN_6 783.68 42.2 18.579 5.382E-002 10.273 484.423 0.000 0.000 0.000 0.000 494.696 No


People Internal Gains Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Number of People {} People/Floor Area {person/m2} Floor Area per person {m2/person} Fraction Radiant Fraction Convected Sensible Fraction Calculation Activity level ASHRAE 55 Warnings Carbon Dioxide Generation Rate Nominal Minimum Number of People Nominal Maximum Number of People MRT Calculation Type Work Efficiency Clothing Insulation Calculation Method Clothing Insulation Calculation Method Schedule Clothing Air Velocity Fanger Calculation Pierce Calculation KSU Calculation Cooling Effect Calculation Ankle Draft Calculation
1 DATACENTER_BOT_ZN_6 BLDG_OCC_SCH_WO_SB DATACENTER_BOT_ZN_6 36.20 1.9 1.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
2 DATACENTER_MID_ZN_6 BLDG_OCC_SCH_WO_SB DATACENTER_MID_ZN_6 36.20 1.9 1.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
3 DATACENTER_TOP_ZN_6 BLDG_OCC_SCH_WO_SB DATACENTER_TOP_ZN_6 36.20 1.9 1.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
4 DATACENTER_BASEMENT_ZN_6 BLDG_OCC_SCH_WO_SB DATACENTER_BASEMENT_ZN_6 783.68 42.2 42.2 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 42 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
5 BASEMENT BLDG_OCC_SCH_WO_SB BASEMENT 2779.43 149.6 149.6 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 150 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
6 CORE_BOTTOM BLDG_OCC_SCH_WO_SB CORE_BOTTOM 2496.12 134.4 134.4 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 134 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
7 CORE_MID BLDG_OCC_SCH_WO_SB CORE_MID 2496.12 134.4 134.4 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 134 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
8 CORE_TOP BLDG_OCC_SCH_WO_SB CORE_TOP 2496.12 134.4 134.4 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 134 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
9 PERIMETER_BOT_ZN_3 BLDG_OCC_SCH_WO_SB PERIMETER_BOT_ZN_3 313.41 16.9 16.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 17 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
10 PERIMETER_BOT_ZN_2 BLDG_OCC_SCH_WO_SB PERIMETER_BOT_ZN_2 201.98 10.9 10.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 11 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
11 PERIMETER_BOT_ZN_1 BLDG_OCC_SCH_WO_SB PERIMETER_BOT_ZN_1 313.42 16.9 16.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 17 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
12 PERIMETER_BOT_ZN_4 BLDG_OCC_SCH_WO_SB PERIMETER_BOT_ZN_4 201.98 10.9 10.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 11 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
13 PERIMETER_MID_ZN_3 BLDG_OCC_SCH_WO_SB PERIMETER_MID_ZN_3 313.41 16.9 16.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 17 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
14 PERIMETER_MID_ZN_2 BLDG_OCC_SCH_W_SB PERIMETER_MID_ZN_2 201.98 10.9 10.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 11 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
15 PERIMETER_MID_ZN_1 BLDG_OCC_SCH_WO_SB PERIMETER_MID_ZN_1 313.42 16.9 16.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 17 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
16 PERIMETER_MID_ZN_4 BLDG_OCC_SCH_WO_SB PERIMETER_MID_ZN_4 201.98 10.9 10.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 11 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
17 PERIMETER_TOP_ZN_3 BLDG_OCC_SCH_WO_SB PERIMETER_TOP_ZN_3 313.41 16.9 16.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 17 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
18 PERIMETER_TOP_ZN_2 BLDG_OCC_SCH_WO_SB PERIMETER_TOP_ZN_2 201.98 10.9 10.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 11 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
19 PERIMETER_TOP_ZN_1 BLDG_OCC_SCH_WO_SB PERIMETER_TOP_ZN_1 313.42 16.9 16.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 17 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
20 PERIMETER_TOP_ZN_4 BLDG_OCC_SCH_WO_SB PERIMETER_TOP_ZN_4 201.98 10.9 10.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 11 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No


Lights Internal Gains Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Lighting Level {W} Lights/Floor Area {W/m2} Lights per person {W/person} Fraction Return Air Fraction Radiant Fraction Short Wave Fraction Convected Fraction Replaceable End-Use Category Nominal Minimum Lighting Level {W} Nominal Maximum Lighting Level {W}
1 BASEMENT_LIGHTS LTG_SCH_OFFICE BASEMENT 2779.43 149.6 28553.717 10.273 190.864 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 28553.717
2 CORE_BOTTOM_LIGHTS LTG_SCH_OFFICE CORE_BOTTOM 2496.12 134.4 25643.245 10.273 190.864 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 25643.245
3 CORE_MID_LIGHTS LTG_SCH_OFFICE CORE_MID 2496.12 134.4 25643.245 10.273 190.864 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 25643.245
4 CORE_TOP_LIGHTS LTG_SCH_OFFICE CORE_TOP 2496.12 134.4 25643.245 10.273 190.864 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 25643.245
5 PERIMETER_BOT_ZN_3_LIGHTS LTG_SCH_OFFICE PERIMETER_BOT_ZN_3 313.41 16.9 3219.765 10.273 190.864 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 3219.765
6 PERIMETER_BOT_ZN_2_LIGHTS LTG_SCH_OFFICE PERIMETER_BOT_ZN_2 201.98 10.9 2074.939 10.273 190.864 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 2074.939
7 PERIMETER_BOT_ZN_1_LIGHTS LTG_SCH_OFFICE PERIMETER_BOT_ZN_1 313.42 16.9 3219.836 10.273 190.864 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 3219.836
8 PERIMETER_BOT_ZN_4_LIGHTS LTG_SCH_OFFICE PERIMETER_BOT_ZN_4 201.98 10.9 2074.939 10.273 190.864 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 2074.939
9 PERIMETER_MID_ZN_3_LIGHTS LTG_SCH_OFFICE PERIMETER_MID_ZN_3 313.41 16.9 3219.765 10.273 190.864 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 3219.765
10 PERIMETER_MID_ZN_2_LIGHTS LTG_SCH_OFFICE PERIMETER_MID_ZN_2 201.98 10.9 2074.939 10.273 190.864 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 2074.939
11 PERIMETER_MID_ZN_1_LIGHTS LTG_SCH_OFFICE PERIMETER_MID_ZN_1 313.42 16.9 3219.836 10.273 190.864 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 3219.836
12 PERIMETER_MID_ZN_4_LIGHTS LTG_SCH_OFFICE PERIMETER_MID_ZN_4 201.98 10.9 2074.939 10.273 190.864 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 2074.939
13 PERIMETER_TOP_ZN_3_LIGHTS LTG_SCH_OFFICE PERIMETER_TOP_ZN_3 313.41 16.9 3219.765 10.273 190.864 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 3219.765
14 PERIMETER_TOP_ZN_2_LIGHTS LTG_SCH_OFFICE PERIMETER_TOP_ZN_2 201.98 10.9 2074.939 10.273 190.864 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 2074.939
15 PERIMETER_TOP_ZN_1_LIGHTS LTG_SCH_OFFICE PERIMETER_TOP_ZN_1 313.42 16.9 3219.836 10.273 190.864 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 3219.836
16 PERIMETER_TOP_ZN_4_LIGHTS LTG_SCH_OFFICE PERIMETER_TOP_ZN_4 201.98 10.9 2074.939 10.273 190.864 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 2074.939
17 DATACENTER_BASEMENT_LIGHTS LTG_SCH_OFFICE DATACENTER_BASEMENT_ZN_6 783.68 42.2 8050.927 10.273 190.864 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 8050.927
18 DATACENTER_BOT_LIGHTS LTG_SCH_DATACENTER DATACENTER_BOT_ZN_6 36.20 1.9 647.068 17.873 332.067 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 647.068
19 DATACENTER_MID_LIGHTS LTG_SCH_DATACENTER DATACENTER_MID_ZN_6 36.20 1.9 647.068 17.873 332.067 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 647.068
20 DATACENTER_TOP_LIGHTS LTG_SCH_DATACENTER DATACENTER_TOP_ZN_6 36.20 1.9 647.068 17.873 332.067 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 647.068


ElectricEquipment Internal Gains Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Equipment Level {W} Equipment/Floor Area {W/m2} Equipment per person {W/person} Fraction Latent Fraction Radiant Fraction Lost Fraction Convected End-Use SubCategory Nominal Minimum Equipment Level {W} Nominal Maximum Equipment Level {W}
1 BASEMENT_MISCPLUG_EQUIP ALWAYS_ON BASEMENT 2779.43 149.6 13457.544 4.842 89.956 0.000 0.500 0.000 0.500 MiscPlug 13457.544 13457.544
2 CORE_BOTTOM_MISCPLUG_EQUIP BLDG_EQUIP_SCH CORE_BOTTOM 2496.12 134.4 20142.877 8.070 149.925 0.000 0.500 0.000 0.500 MiscPlug 0.000 20142.877
3 CORE_MID_MISCPLUG_EQUIP BLDG_EQUIP_SCH CORE_MID 2496.12 134.4 20142.800 8.070 149.924 0.000 0.500 0.000 0.500 MiscPlug 0.000 20142.800
4 CORE_TOP_MISCPLUG_EQUIP BLDG_EQUIP_SCH CORE_TOP 2496.12 134.4 20142.800 8.070 149.924 0.000 0.500 0.000 0.500 MiscPlug 0.000 20142.800
5 PERIMETER_BOT_ZN_3_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_BOT_ZN_3 313.41 16.9 2529.242 8.070 149.931 0.000 0.500 0.000 0.500 MiscPlug 0.000 2529.242
6 PERIMETER_BOT_ZN_2_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_BOT_ZN_2 201.98 10.9 1629.940 8.070 149.931 0.000 0.500 0.000 0.500 MiscPlug 0.000 1629.940
7 PERIMETER_BOT_ZN_1_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_BOT_ZN_1 313.42 16.9 2529.281 8.070 149.930 0.000 0.500 0.000 0.500 MiscPlug 0.000 2529.281
8 PERIMETER_BOT_ZN_4_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_BOT_ZN_4 201.98 10.9 1629.929 8.070 149.930 0.000 0.500 0.000 0.500 MiscPlug 0.000 1629.929
9 PERIMETER_MID_ZN_3_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_MID_ZN_3 313.41 16.9 2529.242 8.070 149.931 0.000 0.500 0.000 0.500 MiscPlug 0.000 2529.242
10 PERIMETER_MID_ZN_2_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_MID_ZN_2 201.98 10.9 1629.940 8.070 149.931 0.000 0.500 0.000 0.500 MiscPlug 0.000 1629.940
11 PERIMETER_MID_ZN_1_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_MID_ZN_1 313.42 16.9 2529.281 8.070 149.930 0.000 0.500 0.000 0.500 MiscPlug 0.000 2529.281
12 PERIMETER_MID_ZN_4_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_MID_ZN_4 201.98 10.9 1629.929 8.070 149.930 0.000 0.500 0.000 0.500 MiscPlug 0.000 1629.929
13 PERIMETER_TOP_ZN_3_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_TOP_ZN_3 313.41 16.9 2529.242 8.070 149.931 0.000 0.500 0.000 0.500 MiscPlug 0.000 2529.242
14 PERIMETER_TOP_ZN_2_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_TOP_ZN_2 201.98 10.9 1629.940 8.070 149.931 0.000 0.500 0.000 0.500 MiscPlug 0.000 1629.940
15 PERIMETER_TOP_ZN_1_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_TOP_ZN_1 313.42 16.9 2529.281 8.070 149.930 0.000 0.500 0.000 0.500 MiscPlug 0.000 2529.281
16 PERIMETER_TOP_ZN_4_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_TOP_ZN_4 201.98 10.9 1629.929 8.070 149.930 0.000 0.500 0.000 0.500 MiscPlug 0.000 1629.929
17 DATACENTER_BASEMENT_MISCPLUG_EQUIP DATACENTER_EQUIP_SCH DATACENTER_BASEMENT_ZN_6 783.68 42.2 379632.522 484.423 9000.000 0.000 0.100 0.000 0.900 DataCenterPlugLoads 94908.130 379632.522
18 DATACENTER_BOT_MISCPLUG_EQUIP DATACENTER_EQUIP_SCH DATACENTER_BOT_ZN_6 36.20 1.9 7794.422 215.299 4000.000 0.000 0.100 0.000 0.900 DataCenterPlugLoads 1948.606 7794.422
19 DATACENTER_MID_MISCPLUG_EQUIP DATACENTER_EQUIP_SCH DATACENTER_MID_ZN_6 36.20 1.9 7794.422 215.299 4000.000 0.000 0.100 0.000 0.900 DataCenterPlugLoads 1948.606 7794.422
20 DATACENTER_TOP_MISCPLUG_EQUIP DATACENTER_EQUIP_SCH DATACENTER_TOP_ZN_6 36.20 1.9 7794.422 215.299 4000.000 0.000 0.100 0.000 0.900 DataCenterPlugLoads 1948.606 7794.422


Construction CTF

Construction Name Index #Layers #CTFs Time Step {hours} ThermalConductance {w/m2-K} OuterThermalAbsorptance InnerThermalAbsorptance OuterSolarAbsorptance InnerSolarAbsorptance Roughness
1 SWINGING DOOR_CON 1 1 1 0.167 2.839 0.900 0.900 0.700 0.700 MediumRough
2 INTERIORFURNISHINGS 2 1 9 0.167 0.8000 0.900 0.900 0.700 0.700 MediumSmooth
3 DROPCEILING 4 1 3 0.167 4.488 0.900 0.900 0.700 0.700 MediumSmooth
4 INT_WALL 7 2 4 0.167 6.299 0.900 0.900 0.700 0.700 Smooth
5 EXT_SLAB_8IN_WITH_CARPET 8 2 7 0.167 3.285 0.900 0.900 0.700 0.700 MediumRough
6 INT_SLAB_FLOOR 12 2 7 0.167 3.839 0.900 0.900 0.700 0.700 MediumRough
7 INT_SLAB_CEILING 13 2 7 0.167 3.839 0.900 0.900 0.700 0.700 VeryRough
8 NONRES_ROOF 17 3 3 0.167 0.1864 0.900 0.900 0.700 0.700 Rough
9 NONRES_EXT_WALL_GRD 20 3 9 0.167 1.075 0.900 0.900 0.700 0.700 MediumRough
10 NONRES_EXT_WALL_MID 21 3 9 0.167 1.028 0.900 0.900 0.700 0.700 MediumRough
11 NONRES_EXT_WALL_TOP 22 3 9 0.167 1.266 0.900 0.900 0.700 0.700 MediumRough
12 BASEMENT_WALL_EAST_CFACTOR 39 2 7 0.167 0.4185 0.000 0.900 0.000 0.700 MediumRough
13 BASEMENT_WALL_SOUTH_CFACTOR 40 2 7 0.167 0.4185 0.000 0.900 0.000 0.700 MediumRough
14 BASEMENT_WALL_NORTH_CFACTOR 41 2 7 0.167 0.4185 0.000 0.900 0.000 0.700 MediumRough
15 DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR 42 2 7 0.167 0.4185 0.000 0.900 0.000 0.700 MediumRough
16 DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR 43 2 7 0.167 0.4185 0.000 0.900 0.000 0.700 MediumRough
17 DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR 44 2 7 0.167 0.4185 0.000 0.900 0.000 0.700 MediumRough


Material CTF Summary

Material Name Thickness {m} Conductivity {w/m-K} Density {kg/m3} Specific Heat {J/kg-K} ThermalResistance {m2-K/w}
1 OPAQUE DOOR PANEL_CON 0.0000 0.000 0.000 0.000 0.3522
2 STD WOOD 6INCH 0.1500 0.120 540.000 1210.000 1.250
3 AC02 ACOUSTIC CEILING 0.0127 0.057 288.000 1339.000 0.2228
4 G01 13MM GYPSUM BOARD 0.0127 0.160 800.000 1090.000 0.7937E-01
5 G01 13MM GYPSUM BOARD 0.0127 0.160 800.000 1090.000 0.7937E-01
6 200MM NORMALWEIGHT CONCRETE FLOOR 0.2032 2.310 2322.000 832.000 0.8797E-01
7 CP02 CARPET PAD 0.0000 0.000 0.000 0.000 0.2165
8 100MM NORMALWEIGHT CONCRETE FLOOR 0.1016 2.310 2322.000 832.000 0.4398E-01
9 CP02 CARPET PAD 0.0000 0.000 0.000 0.000 0.2165
10 CP02 CARPET PAD 0.0000 0.000 0.000 0.000 0.2165
11 100MM NORMALWEIGHT CONCRETE FLOOR 0.1016 2.310 2322.000 832.000 0.4398E-01
12 F13 BUILT-UP ROOFING 0.0095 0.160 1120.000 1460.000 0.5938E-01
13 NONRES_ROOF_INSULATION 0.0000 0.000 0.000 0.000 5.307
14 F08 METAL SURFACE 0.0008 45.280 7824.000 500.000 0.1767E-04
15 200MM NORMALWEIGHT CONCRETE WALL 0.2032 2.310 2322.000 832.000 0.8797E-01
16 NONRES_EXTERIOR_WALL_INSULATION_GRD 0.0000 0.000 0.000 0.000 0.7632
17 G01 13MM GYPSUM BOARD 0.0127 0.160 800.000 1090.000 0.7937E-01
18 200MM NORMALWEIGHT CONCRETE WALL 0.2032 2.310 2322.000 832.000 0.8797E-01
19 NONRES_EXTERIOR_WALL_INSULATION_MID 0.0000 0.000 0.000 0.000 0.8055
20 G01 13MM GYPSUM BOARD 0.0127 0.160 800.000 1090.000 0.7937E-01
21 200MM NORMALWEIGHT CONCRETE WALL 0.2032 2.310 2322.000 832.000 0.8797E-01
22 NONRES_EXTERIOR_WALL_INSULATION_TOP 0.0000 0.000 0.000 0.000 0.6228
23 G01 13MM GYPSUM BOARD 0.0127 0.160 800.000 1090.000 0.7937E-01
24 ~FC_Insulation_1 0.0000 0.000 0.000 0.000 2.312
25 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
26 ~FC_Insulation_2 0.0000 0.000 0.000 0.000 2.312
27 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
28 ~FC_Insulation_3 0.0000 0.000 0.000 0.000 2.312
29 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
30 ~FC_Insulation_4 0.0000 0.000 0.000 0.000 2.312
31 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
32 ~FC_Insulation_5 0.0000 0.000 0.000 0.000 2.312
33 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
34 ~FC_Insulation_6 0.0000 0.000 0.000 0.000 2.312
35 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01


CTF

Time Outside Cross Inside Flux (except final one)
1 1 0.0000000 0.0000000 -0.0000000 -0.0000000
2 0 2.8391315 2.8391315 2.8391315  
3 9 -0.27580628E-02 0.97439125E-12 -0.27580628E-02 0.28516790E-03
4 8 0.73590997E-01 0.21837543E-08 0.73590997E-01 -0.77836043E-02
5 7 -0.82599318 0.23162835E-06 -0.82599318 0.89703933E-01
6 6 5.1113916 0.48671053E-05 5.1113916 -0.57224845
7 5 -19.214933 0.30163627E-04 -19.214933 2.2266322
8 4 45.557404 0.63181060E-04 45.557404 -5.4853312
9 3 -68.275533 0.44785456E-04 -68.275533 8.5710568
10 2 62.555368 0.93952058E-05 62.555368 -8.2111738
11 1 -31.904423 0.39200004E-06 -31.904423 4.3886678
12 0 6.9260389 0.77047546E-09 6.9260389  
13 3 -0.21589802E-09 0.15643069E-09 -0.21589802E-09 0.12999471E-21
14 2 0.50772448E-02 0.30006816E-02 0.50772448E-02 -0.13693132E-08
15 1 -2.5944910 1.4597758 -2.5944910 0.76344767E-02
16 0 7.0433378 2.9911476 7.0433378  
17 4 0.68458728E-09 0.26079551E-09 0.68458728E-09 -0.34507121E-18
18 3 -0.72180374E-03 0.24295686E-03 -0.72180374E-03 0.69691454E-09
19 2 0.83054762 0.27682775 0.83054762 -0.35168967E-03
20 1 -12.650482 3.3590720 -12.650482 0.19281313
21 0 16.907513 1.4507143 16.907513  
22 7 -0.18651654E-16 -0.16428647E-15 -0.26578847E-08 -0.25364002E-17
23 6 0.67402962E-01 0.99142722E-07 0.38101547E-02 -0.76639482E-03
24 5 -1.8580732 0.49502125E-04 -0.10651409 0.21891119E-01
25 4 18.220105 0.12801333E-02 1.0775450 -0.22586539
26 3 -79.928293 0.66708484E-02 -4.9803755 1.0625663
27 2 166.43177 0.75131194E-02 11.128837 -2.4125483
28 1 -159.97298 0.18548900E-02 -11.587784 2.5494418
29 0 57.057412 0.52755123E-04 4.4818272  
30 7 0.43260499E-16 0.34524919E-16 0.52793240E-17 0.0000000
31 6 0.69434179E-09 0.98085174E-11 0.18162501E-10 -0.40870994E-12
32 5 -0.12888762E-04 0.28373718E-06 -0.16918523E-06 0.92361873E-08
33 4 0.25174112E-01 0.33697681E-03 0.22646198E-03 -0.31467795E-04
34 3 -3.7600775 0.27170599E-01 -0.48495626E-01 0.94171705E-02
35 2 51.553741 0.22121684 1.2284947 -0.25833933
36 1 -128.86110 0.21944682 -5.1479470 1.1228340
37 0 81.526494 0.16043334E-01 4.4519351  
38 7 0.52793240E-17 0.34524919E-16 0.43260499E-16 0.0000000
39 6 0.18162501E-10 0.98085174E-11 0.69434179E-09 -0.40870994E-12
40 5 -0.16918523E-06 0.28373718E-06 -0.12888762E-04 0.92361873E-08
41 4 0.22646198E-03 0.33697681E-03 0.25174112E-01 -0.31467795E-04
42 3 -0.48495626E-01 0.27170599E-01 -3.7600775 0.94171705E-02
43 2 1.2284947 0.22121684 51.553741 -0.25833933
44 1 -5.1479470 0.21944682 -128.86110 1.1228340
45 0 4.4519351 0.16043334E-01 81.526494  
46 3 -0.62854340E-06 0.84784826E-09 -0.38512804E-05 0.91756347E-17
47 2 0.78257096 0.11428808E-02 1.0614277 -0.73836085E-06
48 1 -21.991499 0.76199851E-01 -6.3161914 0.20349372
49 0 21.357363 0.71091016E-01 5.4032014  
50 9 -0.34463022E-15 0.36894385E-16 -0.14288780E-09 0.12757077E-17
51 8 0.20913840E-07 0.14359092E-12 0.36762620E-03 -0.23779757E-09
52 7 -0.11937955E-01 0.75343451E-08 -0.22648608E-01 0.13573889E-03
53 6 0.39710065 0.26364580E-05 0.46505929 -0.46505182E-02
54 5 -5.1100523 0.98937734E-04 -4.3872286 0.62185548E-01
55 4 32.646709 0.81302423E-03 21.229086 -0.41739428
56 3 -110.46842 0.17791168E-02 -55.206350 1.5042464
57 2 196.38009 0.10043743E-02 77.491871 -2.8887901
58 1 -170.88709 0.10757908E-03 -55.143519 2.7407251
59 0 57.057407 0.61468164E-06 15.577169  
60 9 -0.22955380E-15 0.37743381E-16 -0.14509256E-09 0.32676096E-18
61 8 0.21224167E-07 0.13772622E-12 0.37092755E-03 -0.24132609E-09
62 7 -0.12036605E-01 0.72012381E-08 -0.22790691E-01 0.13686058E-03
63 6 0.39978134 0.25163753E-05 0.46734577 -0.46821170E-02
64 5 -5.1362151 0.94318005E-04 -4.4048053 0.62509952E-01
65 4 32.762449 0.77422319E-03 21.297824 -0.41893096
66 3 -110.71472 0.16925811E-02 -55.342260 1.5078047
67 2 196.62425 0.95470525E-03 77.616458 -2.8926672
68 1 -170.97729 0.10217823E-03 -55.179630 2.7423060
69 0 57.057407 0.58332056E-06 15.571109  
70 9 0.11276195E-14 0.47405760E-16 -0.13382366E-09 -0.64614724E-17
71 8 0.19634610E-07 0.16705312E-12 0.35383761E-03 -0.22325229E-09
72 7 -0.11525316E-01 0.88979655E-08 -0.22054087E-01 0.13104703E-03
73 6 0.38588679 0.31323747E-05 0.45547913 -0.45183345E-02
74 5 -5.0005974 0.11815564E-03 -4.3135163 0.60828376E-01
75 4 32.162433 0.97545471E-03 20.940665 -0.41096462
76 3 -109.43770 0.21433374E-02 -54.636007 1.4893559
77 2 195.35810 0.12144036E-02 76.969321 -2.8725616
78 1 -170.50942 0.13051365E-03 -54.992579 2.7341060
79 0 57.057407 0.74839837E-06 15.602923  
80 7 -0.98583555E-09 -0.79843648E-16 0.12056005E-14 0.46388562E-17
81 6 0.11736010E-04 0.80964505E-08 0.31724491E-02 -0.26613162E-04
82 5 -0.85155955E-03 0.48044989E-05 -0.22273424 0.19474091E-02
83 4 0.19629464E-01 0.21887653E-03 4.8130477 -0.45106395E-01
84 3 -0.17247723 0.17421542E-02 -37.928201 0.39762344
85 2 0.61254091 0.29000861E-02 116.30250 -1.4155123
86 1 -0.88416489 0.88473762E-03 -143.80049 2.0472841
87 0 0.43108349 0.21254961E-04 60.838472  
88 7 -0.98583555E-09 -0.79843648E-16 0.12056005E-14 0.46388562E-17
89 6 0.11736010E-04 0.80964505E-08 0.31724491E-02 -0.26613162E-04
90 5 -0.85155955E-03 0.48044989E-05 -0.22273424 0.19474091E-02
91 4 0.19629464E-01 0.21887653E-03 4.8130477 -0.45106395E-01
92 3 -0.17247723 0.17421542E-02 -37.928201 0.39762344
93 2 0.61254091 0.29000861E-02 116.30250 -1.4155123
94 1 -0.88416489 0.88473762E-03 -143.80049 2.0472841
95 0 0.43108349 0.21254961E-04 60.838472  
96 7 -0.98583555E-09 -0.79843648E-16 0.12056005E-14 0.46388562E-17
97 6 0.11736010E-04 0.80964505E-08 0.31724491E-02 -0.26613162E-04
98 5 -0.85155955E-03 0.48044989E-05 -0.22273424 0.19474091E-02
99 4 0.19629464E-01 0.21887653E-03 4.8130477 -0.45106395E-01
100 3 -0.17247723 0.17421542E-02 -37.928201 0.39762344
101 2 0.61254091 0.29000861E-02 116.30250 -1.4155123
102 1 -0.88416489 0.88473762E-03 -143.80049 2.0472841
103 0 0.43108349 0.21254961E-04 60.838472  
104 7 -0.98583555E-09 -0.79843648E-16 0.12056005E-14 0.46388562E-17
105 6 0.11736010E-04 0.80964505E-08 0.31724491E-02 -0.26613162E-04
106 5 -0.85155955E-03 0.48044989E-05 -0.22273424 0.19474091E-02
107 4 0.19629464E-01 0.21887653E-03 4.8130477 -0.45106395E-01
108 3 -0.17247723 0.17421542E-02 -37.928201 0.39762344
109 2 0.61254091 0.29000861E-02 116.30250 -1.4155123
110 1 -0.88416489 0.88473762E-03 -143.80049 2.0472841
111 0 0.43108349 0.21254961E-04 60.838472  
112 7 -0.98583555E-09 -0.79843648E-16 0.12056005E-14 0.46388562E-17
113 6 0.11736010E-04 0.80964505E-08 0.31724491E-02 -0.26613162E-04
114 5 -0.85155955E-03 0.48044989E-05 -0.22273424 0.19474091E-02
115 4 0.19629464E-01 0.21887653E-03 4.8130477 -0.45106395E-01
116 3 -0.17247723 0.17421542E-02 -37.928201 0.39762344
117 2 0.61254091 0.29000861E-02 116.30250 -1.4155123
118 1 -0.88416489 0.88473762E-03 -143.80049 2.0472841
119 0 0.43108349 0.21254961E-04 60.838472  
120 7 -0.98583555E-09 -0.79843648E-16 0.12056005E-14 0.46388562E-17
121 6 0.11736010E-04 0.80964505E-08 0.31724491E-02 -0.26613162E-04
122 5 -0.85155955E-03 0.48044989E-05 -0.22273424 0.19474091E-02
123 4 0.19629464E-01 0.21887653E-03 4.8130477 -0.45106395E-01
124 3 -0.17247723 0.17421542E-02 -37.928201 0.39762344
125 2 0.61254091 0.29000861E-02 116.30250 -1.4155123
126 1 -0.88416489 0.88473762E-03 -143.80049 2.0472841
127 0 0.43108349 0.21254961E-04 60.838472  


WindowConstruction

Construction Name Index #Layers Roughness Conductance {W/m2-K} Conductance (Before Adjusted) {W/m2-K} Convection Coefficient Adjustment Ratio SHGC Solar Transmittance at Normal Incidence Visible Transmittance at Normal Incidence
1 WINDOW_U_0.42_SHGC_EAST_0.4 35 1 VerySmooth 2.387 2.387 1.000 0.401    
2 WINDOW_U_0.42_SHGC_SOUTH_0.4 36 1 VerySmooth 2.387 2.387 1.000 0.401    
3 WINDOW_U_0.42_SHGC_WEST_0.4 37 1 VerySmooth 2.387 2.387 1.000 0.401    
4 WINDOW_U_0.42_SHGC_NORTH_0.4 38 1 VerySmooth 2.387 2.387 1.000 0.401    


WindowMaterial:Glazing

Material Name Optical Data Type Spectral Data Set Name Thickness {m} Solar Transmittance Front Solar Reflectance Back Solar Reflectance Visible Transmittance Front Visible Reflectance Back Visible Reflectance Infrared Transmittance Front Thermal Emissivity Back Thermal Emissivity Conductivity {W/m-K} Dirt Factor Solar Diffusing
1 GLAZING LAYER EAST SpectralAverage   3.02786E-002 0.31435 0.47495 0.47495 0.44000 0.13397 0.17027 0.00000 0.84000 0.84000 0.12239 1.00000 No
2 GLAZING LAYER SOUTH SpectralAverage   3.02786E-002 0.31435 0.47495 0.47495 0.44000 0.13397 0.17027 0.00000 0.84000 0.84000 0.12239 1.00000 No
3 GLAZING LAYER WEST SpectralAverage   3.02786E-002 0.31435 0.47495 0.47495 0.44000 0.13397 0.17027 0.00000 0.84000 0.84000 0.12239 1.00000 No
4 GLAZING LAYER NORTH SpectralAverage   3.02786E-002 0.31435 0.47495 0.47495 0.44000 0.13397 0.17027 0.00000 0.84000 0.84000 0.12239 1.00000 No


Shadowing/Sun Position Calculations Annual Simulations

Shading Calculation Method Shading Calculation Update Frequency Method Shading Calculation Update Frequency {days} Maximum Figures in Shadow Overlap Calculations {} Polygon Clipping Algorithm Pixel Counting Resolution Sky Diffuse Modeling Algorithm Output External Shading Calculation Results Disable Self-Shading Within Shading Zone Groups Disable Self-Shading From Shading Zone Groups to Other Zones
1 PolygonClipping Periodic 30 15000 SutherlandHodgman 512 SimpleSkyDiffuseModeling No No No


Enclosure/Window Adjacency Daylighting Counts

Enclosure Name Number of Exterior Windows Number of Exterior Windows in Adjacent Enclosures
1 PERIMETER_BOT_ZN_3 5 0
2 PERIMETER_BOT_ZN_2 3 0
3 PERIMETER_BOT_ZN_1 5 0
4 PERIMETER_BOT_ZN_4 3 0
5 PERIMETER_MID_ZN_3 1 0
6 PERIMETER_MID_ZN_2 1 0
7 PERIMETER_MID_ZN_1 1 0
8 PERIMETER_MID_ZN_4 1 0
9 PERIMETER_TOP_ZN_3 1 0
10 PERIMETER_TOP_ZN_2 1 0
11 PERIMETER_TOP_ZN_1 1 0
12 PERIMETER_TOP_ZN_4 1 0


Enclosure/Window Adjacency Daylighting Matrix

Enclosure Name Number of Adjacent Enclosures with Windows Adjacent Enclosure Names - 1st 100 (max)
1 PERIMETER_BOT_ZN_3 0  
2 PERIMETER_BOT_ZN_2 0  
3 PERIMETER_BOT_ZN_1 0  
4 PERIMETER_BOT_ZN_4 0  
5 PERIMETER_MID_ZN_3 0  
6 PERIMETER_MID_ZN_2 0  
7 PERIMETER_MID_ZN_1 0  
8 PERIMETER_MID_ZN_4 0  
9 PERIMETER_TOP_ZN_3 0  
10 PERIMETER_TOP_ZN_2 0  
11 PERIMETER_TOP_ZN_1 0  
12 PERIMETER_TOP_ZN_4 0  


Water Heater Information

Type Name Volume {m3} Maximum Capacity {W} Standard Rated Recovery Efficiency Standard Rated Energy Factor
1 WaterHeater:Mixed SWHSYS1 WATER HEATER 1.1356 87921.3 0.481 5.5005E-002


Surface Convection Parameters

Surface Name Outside Model Assignment Outside Area [m2] Outside Perimeter [m] Outside Height [m] Inside Model Assignment Inside Height [m] Inside Perimeter Envelope [m] Inside Hydraulic Diameter [m] Window Wall Ratio Window Location Near Radiant {Yes/No} Has Active HVAC {Yes/No}
1 BASEMENT_WALL_EAST 0 0.00 0.00 0.00 0 2.44 0.00 52.56 -999.00 0 No No
2 BASEMENT_WALL_SOUTH 0 0.00 0.00 0.00 0 2.44 0.00 52.56 -999.00 0 No No
3 BASEMENT_WALL_NORTH 0 0.00 0.00 0.00 0 2.44 0.00 52.56 -999.00 0 No No
4 BASEMENT_WALL_WEST 0 0.00 0.00 0.00 0 2.44 0.00 52.56 -999.00 0 No No
5 BASEMENT_FLOOR 0 0.00 0.00 0.00 0 2.44 0.00 52.56 -999.00 0 No No
6 PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.44 0.00 52.56 -999.00 0 No No
7 PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.44 0.00 52.56 -999.00 0 No No
8 CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.44 0.00 52.56 -999.00 0 No No
9 PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.44 0.00 52.56 -999.00 0 No No
10 BASEMENT_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.44 0.00 52.56 -999.00 0 No No
11 CORE_BOT_ZN_5_WALL_SOUTH 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
12 CORE_BOT_ZN_5_WALL_WEST 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
13 CORE_BOT_ZN_5_WALL_NORTH 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
14 CORE_BOT_ZN_5_WALL_EAST 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
15 DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
16 CORE_BOT_ZN_5_FLOOR 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
17 CORE_BOT_ZN_5_CEILING 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
18 CORE_BOTTOM_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
19 CORE_MID_ZN_5_WALL_SOUTH 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
20 CORE_MID_ZN_5_WALL_WEST 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
21 CORE_MID_ZN_5_WALL_NORTH 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
22 CORE_MID_ZN_5_WALL_EAST 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
23 CORE_MID_ZN_5_FLOOR 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
24 CORE_MID_ZN_5_CEILING 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
25 CORE_MID_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
26 CORE_TOP_ZN_5_WALL_SOUTH 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
27 CORE_TOP_ZN_5_WALL_WEST 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
28 CORE_TOP_ZN_5_WALL_NORTH 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
29 CORE_TOP_ZN_5_WALL_EAST 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
30 CORE_TOP_ZN_5_FLOOR 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
31 CORE_TOP_ZN_5_CEILING 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
32 CORE_TOP_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
33 PERIMETER_BOT_ZN_3_WALL_NORTH 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.58 3 No No
34 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.58 5 No No
35 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.58 5 No No
36 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.58 5 No No
37 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.58 5 No No
38 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.58 5 No No
39 PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.58 0 No No
40 PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.58 0 No No
41 PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.58 0 No No
42 PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.58 0 No No
43 PERIMETER_BOT_ZN_3_WALL_WEST 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
44 CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
45 PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
46 DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
47 PERIMETER_BOT_ZN_3_FLOOR 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
48 DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
49 PERIMETER_BOT_ZN_3_CEILING 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
50 PERIMETER_BOT_ZN_3_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
51 PERIMETER_BOT_ZN_2_WALL_EAST 0 579.48 250.73 37.50 0 2.74 48.74 7.58 0.58 3 No No
52 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 0 579.48 250.73 37.50 0 2.74 48.74 7.58 0.58 5 No No
53 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 0 579.48 250.73 37.50 0 2.74 48.74 7.58 0.58 5 No No
54 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 0 579.48 250.73 37.50 0 2.74 48.74 7.58 0.58 5 No No
55 PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 0 579.48 250.73 37.50 0 2.74 48.74 7.58 0.58 0 No No
56 PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 0 579.48 250.73 37.50 0 2.74 48.74 7.58 0.58 0 No No
57 PERIMETER_BOT_ZN_2_WALL_NORTH 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
58 CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
59 PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
60 PERIMETER_BOT_ZN_2_FLOOR 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
61 PERIMETER_BOT_ZN_2_CEILING 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
62 PERIMETER_BOT_ZN_2_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
63 PERIMETER_BOT_ZN_1_WALL_SOUTH 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.58 3 No No
64 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.58 5 No No
65 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.58 5 No No
66 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.58 5 No No
67 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.58 5 No No
68 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.58 5 No No
69 PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.58 0 No No
70 PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.58 0 No No
71 PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.58 0 No No
72 PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.58 0 No No
73 PERIMETER_BOT_ZN_1_WALL_EAST 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
74 DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
75 PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
76 CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
77 DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
78 PERIMETER_BOT_ZN_1_FLOOR 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
79 PERIMETER_BOT_ZN_1_CEILING 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
80 PERIMETER_BOT_ZN_1_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
81 PERIMETER_BOT_ZN_4_WALL_WEST 0 579.48 172.48 37.50 0 2.74 48.74 7.58 0.58 3 No No
82 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 0 579.48 172.48 37.50 0 2.74 48.74 7.58 0.58 5 No No
83 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 0 579.48 172.48 37.50 0 2.74 48.74 7.58 0.58 5 No No
84 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 0 579.48 172.48 37.50 0 2.74 48.74 7.58 0.58 5 No No
85 PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 0 579.48 172.48 37.50 0 2.74 48.74 7.58 0.58 0 No No
86 PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 0 579.48 172.48 37.50 0 2.74 48.74 7.58 0.58 0 No No
87 PERIMETER_BOT_ZN_4_WALL_SOUTH 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
88 DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
89 PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
90 PERIMETER_BOT_ZN_4_FLOOR 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
91 PERIMETER_BOT_ZN_4_CEILING 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
92 PERIMETER_BOT_ZN_4_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
93 PERIMETER_MID_ZN_3_WALL_NORTH 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.58 3 No No
94 PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.58 5 No No
95 PERIMETER_MID_ZN_3_WALL_WEST 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
96 CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
97 PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
98 DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
99 PERIMETER_MID_ZN_3_FLOOR 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
100 PERIMETER_MID_ZN_3_CEILING 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
101 PERIMETER_MID_ZN_3_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
102 PERIMETER_MID_ZN_2_WALL_EAST 0 579.48 250.73 37.50 0 2.74 48.74 7.58 0.58 3 No No
103 PERIMETER_MID_ZN_2_WALL_EAST_WINDOW 0 579.48 250.73 37.50 0 2.74 48.74 7.58 0.58 5 No No
104 PERIMETER_MID_ZN_2_WALL_NORTH 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
105 CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
106 PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
107 PERIMETER_MID_ZN_2_FLOOR 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
108 PERIMETER_MID_ZN_2_CEILING 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
109 PERIMETER_MID_ZN_2_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
110 PERIMETER_MID_ZN_1_WALL_EAST 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
111 PERIMETER_MID_ZN_1_WALL_SOUTH 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.58 3 No No
112 PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.58 5 No No
113 DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
114 PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
115 CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
116 PERIMETER_MID_ZN_1_FLOOR 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
117 PERIMETER_MID_ZN_1_CEILING 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
118 PERIMETER_MID_ZN_1_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
119 PERIMETER_MID_ZN_4_WALL_WEST 0 579.48 172.48 37.50 0 2.74 48.74 7.58 0.58 3 No No
120 PERIMETER_MID_ZN_4_WALL_WEST_WINDOW 0 579.48 172.48 37.50 0 2.74 48.74 7.58 0.58 5 No No
121 PERIMETER_MID_ZN_4_WALL_SOUTH 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
122 DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
123 PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
124 PERIMETER_MID_ZN_4_FLOOR 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
125 PERIMETER_MID_ZN_4_CEILING 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
126 PERIMETER_MID_ZN_4_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
127 PERIMETER_TOP_ZN_3_WALL_NORTH 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.58 3 No No
128 PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.58 5 No No
129 PERIMETER_TOP_ZN_3_WALL_WEST 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
130 CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
131 PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
132 DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
133 PERIMETER_TOP_ZN_3_FLOOR 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
134 PERIMETER_TOP_ZN_3_CEILING 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
135 PERIMETER_TOP_ZN_3_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
136 PERIMETER_TOP_ZN_2_WALL_EAST 0 579.48 250.73 37.50 0 2.74 48.74 7.58 0.58 3 No No
137 PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW 0 579.48 250.73 37.50 0 2.74 48.74 7.58 0.58 5 No No
138 PERIMETER_TOP_ZN_2_WALL_NORTH 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
139 CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
140 INT-PER3S-NE-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
141 PERIMETER_TOP_ZN_2_FLOOR 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
142 PERIMETER_TOP_ZN_2_CEILING 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
143 PERIMETER_TOP_ZN_2_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
144 PERIMETER_TOP_ZN_1_WALL_SOUTH 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.58 3 No No
145 PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.58 5 No No
146 INT-PER3S-NE 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
147 DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
148 PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
149 CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
150 PERIMETER_TOP_ZN_1_FLOOR 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
151 PERIMETER_TOP_ZN_1_CEILING 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
152 PERIMETER_TOP_ZN_1_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
153 PERIMETER_TOP_ZN_4_WALL_WEST 0 579.48 172.48 37.50 0 2.74 48.74 7.58 0.58 3 No No
154 PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW 0 579.48 172.48 37.50 0 2.74 48.74 7.58 0.58 5 No No
155 PERIMETER_TOP_ZN_4_WALL_SOUTH 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
156 DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
157 PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
158 PERIMETER_TOP_ZN_4_FLOOR 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
159 PERIMETER_TOP_ZN_4_CEILING 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
160 PERIMETER_TOP_ZN_4_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
161 GROUNDFLOOR_PLENUM_WALL_NORTH 0 869.22 250.73 37.50 0 1.22 243.69 58.49 0.00 0 No No
162 GROUNDFLOOR_PLENUM_WEST 0 579.48 172.48 37.50 0 1.22 243.69 58.49 0.00 0 No No
163 GROUNDFLOOR_PLENUM_WALL_SOUTH 0 869.22 221.21 37.50 0 1.22 243.69 58.49 0.00 0 No No
164 GROUNDFLOOR_PLENUM_WALL_EAST 0 579.48 250.73 37.50 0 1.22 243.69 58.49 0.00 0 No No
165 iz-CORE_BOT_ZN_5_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
166 iz-PERIMETER_BOT_ZN_3_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
167 iz-PERIMETER_BOT_ZN_2_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
168 iz-PERIMETER_BOT_ZN_1_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
169 iz-PERIMETER_BOT_ZN_4_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
170 iz-DATACENTER_BOT_ZN_6_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
171 GROUNDFLOOR_PLENUM_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
172 MIDFLOOR_PLENUM_WALL_NORTH 0 869.22 250.73 37.50 0 1.22 243.69 58.49 0.00 0 No No
173 MIDFLOOR_PLENUM_WALL_WEST 0 579.48 172.48 37.50 0 1.22 243.69 58.49 0.00 0 No No
174 MIDFLOOR_PLENUM_WALL_SOUTH 0 869.22 221.21 37.50 0 1.22 243.69 58.49 0.00 0 No No
175 MIDFLOOR_PLENUM_WALL_EAST 0 579.48 250.73 37.50 0 1.22 243.69 58.49 0.00 0 No No
176 iz-CORE_MID_ZN_5_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
177 iz-PERIMETER_MID_ZN_3_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
178 iz-PERIMETER_MID_ZN_2_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
179 iz-PERIMETER_MID_ZN_1_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
180 iz-PERIMETER_MID_ZN_4_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
181 iz-DATACENTER_MID_ZN_6_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
182 MIDFLOOR_PLENUM_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
183 TOPFLOOR_PLENUM_WALL_NORTH 0 869.22 221.21 37.50 0 1.22 243.69 58.49 0.00 0 No No
184 TOPFLOOR_PLENUM_WALL_EAST 0 579.48 250.73 37.50 0 1.22 243.69 58.49 0.00 0 No No
185 TOPFLOOR_PLENUM_WALL_WEST 0 579.48 172.48 37.50 0 1.22 243.69 58.49 0.00 0 No No
186 TOPFLOOR_PLENUM_WALL_SOUTH 0 869.22 250.73 37.50 0 1.22 243.69 58.49 0.00 0 No No
187 iz-CORE_TOP_ZN_5_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
188 iz-PERIMETER_TOP_ZN_3_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
189 iz-PERIMETER_TOP_ZN_2_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
190 iz-PERIMETER_TOP_ZN_1_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
191 iz-PERIMETER_TOP_ZN_4_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
192 iz-DATACENTER_TOP_ZN_6_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
193 BUILDING_ROOF 0 3563.11 268.06 0.00 0 1.22 243.69 58.49 0.00 0 No No
194 DATACENTER_BOT_ZN_6_WALL_NORTH 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
195 DATACENTER_BOT_ZN_6_WALL_SOUTH 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
196 DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
197 DATACENTER_BOT_ZN_6_WALL_WEST 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
198 DATACENTER_BOT_ZN_6_FLOOR 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
199 DATACENTER_BOT_ZN_6_CEILING 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
200 DATACENTER_MID_ZN_6_WALL_WEST 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
201 DATACENTER_MID_ZN_6_WALL_SOUTH 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
202 DATACENTER_MID_ZN_6_WALL_EAST 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
203 DATACENTER_MID_ZN_6_WALL_NORTH 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
204 DATACENTER_MID_ZN_6_FLOOR 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
205 DATACENTER_MID_ZN_6_CEILING 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
206 DATACENTER_TOP_ZN_6_WALL_EAST 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
207 DATACENTER_TOP_ZN_6_WALL_WEST 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
208 DATACENTER_TOP_ZN_6_WALL_SOUTH 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
209 DATACENTER_TOP_ZN_6_WALL_NORTH 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
210 DATACENTER_TOP_ZN_6_FLOOR 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
211 DATACENTER_TOP_ZN_6_CEILING 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
212 DATACENTER_BASEMENT_ZN_6_WALL_NORTH 0 0.00 0.00 0.00 0 2.44 0.00 24.18 -999.00 0 No No
213 DATACENTER_BASEMENT_ZN_6_WALL_SOUTH 0 0.00 0.00 0.00 0 2.44 0.00 24.18 -999.00 0 No No
214 DATACENTER_BASEMENT_ZN_6_WALL_WEST 0 0.00 0.00 0.00 0 2.44 0.00 24.18 -999.00 0 No No
215 DATACENTER_BASEMENT_ZN_6_WALL_EAST 0 0.00 0.00 0.00 0 2.44 0.00 24.18 -999.00 0 No No
216 DATACENTER_BASEMENT_ZN_6_FLOOR 0 0.00 0.00 0.00 0 2.44 0.00 24.18 -999.00 0 No No
217 DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.44 0.00 24.18 -999.00 0 No No
218 DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 0 0.00 0.00 0.00 0 2.44 0.00 24.18 -999.00 0 No No
219 PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.44 0.00 24.18 -999.00 0 No No
220 DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 0 0.00 0.00 0.00 0 2.44 0.00 24.18 -999.00 0 No No
221 DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 0 0.00 0.00 0.00 0 2.44 0.00 24.18 -999.00 0 No No


ZoneInfiltration Airflow Stats Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Design Volume Flow Rate {m3/s} Volume Flow Rate/Floor Area {m3/s-m2} Volume Flow Rate/Exterior Surface Area {m3/s-m2} ACH - Air Changes per Hour Equation A - Constant Term Coefficient {} Equation B - Temperature Term Coefficient {1/C} Equation C - Velocity Term Coefficient {s/m} Equation D - Velocity Squared Term Coefficient {s2/m2}
1 PERIMETER_BOT_ZN_3_INFILTRATION INFIL_SCH_PNNL PERIMETER_BOT_ZN_3 313.41 16.9 0.114 3.646E-004 5.482E-004 0.478 0.000 0.000 0.224 0.000
2 PERIMETER_BOT_ZN_2_INFILTRATION INFIL_SCH_PNNL PERIMETER_BOT_ZN_2 201.98 10.9 7.617E-002 3.771E-004 5.534E-004 0.495 0.000 0.000 0.224 0.000
3 PERIMETER_BOT_ZN_1_INFILTRATION INFIL_SCH_PNNL PERIMETER_BOT_ZN_1 313.42 16.9 0.114 3.646E-004 5.482E-004 0.478 0.000 0.000 0.224 0.000
4 PERIMETER_BOT_ZN_4_INFILTRATION INFIL_SCH_PNNL PERIMETER_BOT_ZN_4 201.98 10.9 7.617E-002 3.771E-004 5.534E-004 0.495 0.000 0.000 0.224 0.000
5 PERIMETER_MID_ZN_3_INFILTRATION INFIL_SCH_PNNL PERIMETER_MID_ZN_3 313.41 16.9 0.114 3.646E-004 5.696E-004 0.478 0.000 0.000 0.224 0.000
6 PERIMETER_MID_ZN_2_INFILTRATION INFIL_SCH_PNNL PERIMETER_MID_ZN_2 201.98 10.9 7.617E-002 3.771E-004 5.696E-004 0.495 0.000 0.000 0.224 0.000
7 PERIMETER_MID_ZN_1_INFILTRATION INFIL_SCH_PNNL PERIMETER_MID_ZN_1 313.42 16.9 0.114 3.646E-004 5.696E-004 0.478 0.000 0.000 0.224 0.000
8 PERIMETER_MID_ZN_4_INFILTRATION INFIL_SCH_PNNL PERIMETER_MID_ZN_4 201.98 10.9 7.617E-002 3.771E-004 5.696E-004 0.495 0.000 0.000 0.224 0.000
9 PERIMETER_TOP_ZN_3_INFILTRATION INFIL_SCH_PNNL PERIMETER_TOP_ZN_3 313.41 16.9 0.114 3.646E-004 5.696E-004 0.478 0.000 0.000 0.224 0.000
10 PERIMETER_TOP_ZN_2_INFILTRATION INFIL_SCH_PNNL PERIMETER_TOP_ZN_2 201.98 10.9 7.617E-002 3.771E-004 5.696E-004 0.495 0.000 0.000 0.224 0.000
11 PERIMETER_TOP_ZN_1_INFILTRATION INFIL_SCH_PNNL PERIMETER_TOP_ZN_1 313.42 16.9 0.114 3.646E-004 5.696E-004 0.478 0.000 0.000 0.224 0.000
12 PERIMETER_TOP_ZN_4_INFILTRATION INFIL_SCH_PNNL PERIMETER_TOP_ZN_4 201.98 10.9 7.617E-002 3.771E-004 5.696E-004 0.495 0.000 0.000 0.224 0.000
13 GROUNDFLOOR_PLENUM_INFILTRATION INFIL_SCH_PNNL GROUNDFLOOR_PLENUM 3563.11 0.0 0.169 4.749E-005 5.696E-004 0.140 0.000 0.000 0.224 0.000
14 MIDFLOOR_PLENUM_INFILTRATION INFIL_SCH_PNNL MIDFLOOR_PLENUM 3563.11 0.0 0.169 4.749E-005 5.696E-004 0.140 0.000 0.000 0.224 0.000
15 TOPFLOOR_PLENUM_INFILTRATION INFIL_SCH_PNNL TOPFLOOR_PLENUM 3563.11 0.0 0.169 4.749E-005 4.384E-005 0.140 0.000 0.000 0.224 0.000


AirFlow Model

Simple
1 Simple


RoomAir Model

Zone Name Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined
1 BASEMENT Mixing/Well-Stirred
2 CORE_BOTTOM Mixing/Well-Stirred
3 CORE_MID Mixing/Well-Stirred
4 CORE_TOP Mixing/Well-Stirred
5 PERIMETER_BOT_ZN_3 Mixing/Well-Stirred
6 PERIMETER_BOT_ZN_2 Mixing/Well-Stirred
7 PERIMETER_BOT_ZN_1 Mixing/Well-Stirred
8 PERIMETER_BOT_ZN_4 Mixing/Well-Stirred
9 PERIMETER_MID_ZN_3 Mixing/Well-Stirred
10 PERIMETER_MID_ZN_2 Mixing/Well-Stirred
11 PERIMETER_MID_ZN_1 Mixing/Well-Stirred
12 PERIMETER_MID_ZN_4 Mixing/Well-Stirred
13 PERIMETER_TOP_ZN_3 Mixing/Well-Stirred
14 PERIMETER_TOP_ZN_2 Mixing/Well-Stirred
15 PERIMETER_TOP_ZN_1 Mixing/Well-Stirred
16 PERIMETER_TOP_ZN_4 Mixing/Well-Stirred
17 GROUNDFLOOR_PLENUM Mixing/Well-Stirred
18 MIDFLOOR_PLENUM Mixing/Well-Stirred
19 TOPFLOOR_PLENUM Mixing/Well-Stirred
20 DATACENTER_BOT_ZN_6 Mixing/Well-Stirred
21 DATACENTER_MID_ZN_6 Mixing/Well-Stirred
22 DATACENTER_TOP_ZN_6 Mixing/Well-Stirred
23 DATACENTER_BASEMENT_ZN_6 Mixing/Well-Stirred


AirflowNetwork Model:Control

No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation
1 NoMultizoneOrDistribution


Zone Volume Capacitance Multiplier

Sensible Heat Capacity Multiplier Moisture Capacity Multiplier Carbon Dioxide Capacity Multiplier Generic Contaminant Capacity Multiplier
1 1.000 1.000 1.000 1.000


Load Timesteps in Zone Design Calculation Averaging Window

Value
1 6


Heating Sizing Factor Information

Sizing Factor ID Value
1 Global 1.0000


Cooling Sizing Factor Information

Sizing Factor ID Value
1 Global 1.0000


Sky Daylight Factors

Sky Type MonthAndDay Daylighting Control Name Enclosure Name Window Name Reference Point Daylight Factor
1 Clear Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 PERIMETER_BOT_ZN_1_DAYLREFPT1 7.0772E-003
2 Clear Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 PERIMETER_BOT_ZN_1_DAYLREFPT2 7.0795E-003
3 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 PERIMETER_BOT_ZN_1_DAYLREFPT1 7.7388E-003
4 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 PERIMETER_BOT_ZN_1_DAYLREFPT2 7.7407E-003
5 Intermediate Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 PERIMETER_BOT_ZN_1_DAYLREFPT1 5.0382E-003
6 Intermediate Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 PERIMETER_BOT_ZN_1_DAYLREFPT2 5.0397E-003
7 Overcast Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 PERIMETER_BOT_ZN_1_DAYLREFPT1 2.7740E-003
8 Overcast Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 PERIMETER_BOT_ZN_1_DAYLREFPT2 2.7748E-003
9 Clear Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 PERIMETER_BOT_ZN_1_DAYLREFPT1 7.1309E-003
10 Clear Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 PERIMETER_BOT_ZN_1_DAYLREFPT2 7.2904E-003
11 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 PERIMETER_BOT_ZN_1_DAYLREFPT1 7.7841E-003
12 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 PERIMETER_BOT_ZN_1_DAYLREFPT2 7.9236E-003
13 Intermediate Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 PERIMETER_BOT_ZN_1_DAYLREFPT1 5.0771E-003
14 Intermediate Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 PERIMETER_BOT_ZN_1_DAYLREFPT2 5.1924E-003
15 Overcast Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 PERIMETER_BOT_ZN_1_DAYLREFPT1 2.7969E-003
16 Overcast Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 PERIMETER_BOT_ZN_1_DAYLREFPT2 2.8551E-003
17 Clear Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 PERIMETER_BOT_ZN_1_DAYLREFPT1 0.1759
18 Clear Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 PERIMETER_BOT_ZN_1_DAYLREFPT2 8.4610E-002
19 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 PERIMETER_BOT_ZN_1_DAYLREFPT1 0.1986
20 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 PERIMETER_BOT_ZN_1_DAYLREFPT2 9.4910E-002
21 Intermediate Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 PERIMETER_BOT_ZN_1_DAYLREFPT1 0.1242
22 Intermediate Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 PERIMETER_BOT_ZN_1_DAYLREFPT2 4.9187E-002
23 Overcast Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 PERIMETER_BOT_ZN_1_DAYLREFPT1 5.0165E-002
24 Overcast Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 PERIMETER_BOT_ZN_1_DAYLREFPT2 1.7447E-002
25 Clear Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 PERIMETER_BOT_ZN_1_DAYLREFPT1 7.1339E-003
26 Clear Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 PERIMETER_BOT_ZN_1_DAYLREFPT2 7.3044E-003
27 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 PERIMETER_BOT_ZN_1_DAYLREFPT1 7.7871E-003
28 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 PERIMETER_BOT_ZN_1_DAYLREFPT2 7.9381E-003
29 Intermediate Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 PERIMETER_BOT_ZN_1_DAYLREFPT1 5.0796E-003
30 Intermediate Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 PERIMETER_BOT_ZN_1_DAYLREFPT2 5.2023E-003
31 Overcast Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 PERIMETER_BOT_ZN_1_DAYLREFPT1 2.7974E-003
32 Overcast Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 PERIMETER_BOT_ZN_1_DAYLREFPT2 2.8568E-003
33 Clear Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 PERIMETER_BOT_ZN_1_DAYLREFPT1 7.0769E-003
34 Clear Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 PERIMETER_BOT_ZN_1_DAYLREFPT2 7.0794E-003
35 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 PERIMETER_BOT_ZN_1_DAYLREFPT1 7.7385E-003
36 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 PERIMETER_BOT_ZN_1_DAYLREFPT2 7.7405E-003
37 Intermediate Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 PERIMETER_BOT_ZN_1_DAYLREFPT1 5.0380E-003
38 Intermediate Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 PERIMETER_BOT_ZN_1_DAYLREFPT2 5.0396E-003
39 Overcast Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 PERIMETER_BOT_ZN_1_DAYLREFPT1 2.7739E-003
40 Overcast Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 PERIMETER_BOT_ZN_1_DAYLREFPT2 2.7747E-003
41 Clear Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 PERIMETER_BOT_ZN_2_DAYLREFPT1 6.0703E-003
42 Clear Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 PERIMETER_BOT_ZN_2_DAYLREFPT2 6.3899E-003
43 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 PERIMETER_BOT_ZN_2_DAYLREFPT1 5.7465E-003
44 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 PERIMETER_BOT_ZN_2_DAYLREFPT2 6.0949E-003
45 Intermediate Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 PERIMETER_BOT_ZN_2_DAYLREFPT1 5.5174E-003
46 Intermediate Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 PERIMETER_BOT_ZN_2_DAYLREFPT2 5.6581E-003
47 Overcast Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 PERIMETER_BOT_ZN_2_DAYLREFPT1 4.7428E-003
48 Overcast Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 PERIMETER_BOT_ZN_2_DAYLREFPT2 4.7830E-003
49 Clear Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 PERIMETER_BOT_ZN_2_DAYLREFPT1 6.6877E-002
50 Clear Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 PERIMETER_BOT_ZN_2_DAYLREFPT2 3.2674E-002
51 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 PERIMETER_BOT_ZN_2_DAYLREFPT1 6.1771E-002
52 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 PERIMETER_BOT_ZN_2_DAYLREFPT2 2.9361E-002
53 Intermediate Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 PERIMETER_BOT_ZN_2_DAYLREFPT1 6.5526E-002
54 Intermediate Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 PERIMETER_BOT_ZN_2_DAYLREFPT2 2.7164E-002
55 Overcast Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 PERIMETER_BOT_ZN_2_DAYLREFPT1 5.2230E-002
56 Overcast Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 PERIMETER_BOT_ZN_2_DAYLREFPT2 1.9536E-002
57 Clear Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 PERIMETER_BOT_ZN_2_DAYLREFPT1 5.9733E-003
58 Clear Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 PERIMETER_BOT_ZN_2_DAYLREFPT2 6.0857E-003
59 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 PERIMETER_BOT_ZN_2_DAYLREFPT1 5.6211E-003
60 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 PERIMETER_BOT_ZN_2_DAYLREFPT2 5.7024E-003
61 Intermediate Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 PERIMETER_BOT_ZN_2_DAYLREFPT1 5.4726E-003
62 Intermediate Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 PERIMETER_BOT_ZN_2_DAYLREFPT2 5.5039E-003
63 Overcast Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 PERIMETER_BOT_ZN_2_DAYLREFPT1 4.7430E-003
64 Overcast Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 PERIMETER_BOT_ZN_2_DAYLREFPT2 4.7836E-003
65 Clear Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 PERIMETER_BOT_ZN_3_DAYLREFPT1 2.8807E-003
66 Clear Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 PERIMETER_BOT_ZN_3_DAYLREFPT2 2.8829E-003
67 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 PERIMETER_BOT_ZN_3_DAYLREFPT1 2.4468E-003
68 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 PERIMETER_BOT_ZN_3_DAYLREFPT2 2.4486E-003
69 Intermediate Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 PERIMETER_BOT_ZN_3_DAYLREFPT1 2.1669E-003
70 Intermediate Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 PERIMETER_BOT_ZN_3_DAYLREFPT2 2.1682E-003
71 Overcast Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 PERIMETER_BOT_ZN_3_DAYLREFPT1 2.7740E-003
72 Overcast Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 PERIMETER_BOT_ZN_3_DAYLREFPT2 2.7749E-003
73 Clear Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 PERIMETER_BOT_ZN_3_DAYLREFPT1 2.9309E-003
74 Clear Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 PERIMETER_BOT_ZN_3_DAYLREFPT2 3.0616E-003
75 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 PERIMETER_BOT_ZN_3_DAYLREFPT1 2.4876E-003
76 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 PERIMETER_BOT_ZN_3_DAYLREFPT2 2.5906E-003
77 Intermediate Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 PERIMETER_BOT_ZN_3_DAYLREFPT1 2.1998E-003
78 Intermediate Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 PERIMETER_BOT_ZN_3_DAYLREFPT2 2.2729E-003
79 Overcast Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 PERIMETER_BOT_ZN_3_DAYLREFPT1 2.7975E-003
80 Overcast Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 PERIMETER_BOT_ZN_3_DAYLREFPT2 2.8569E-003
81 Clear Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 PERIMETER_BOT_ZN_3_DAYLREFPT1 4.6029E-002
82 Clear Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 PERIMETER_BOT_ZN_3_DAYLREFPT2 2.4286E-002
83 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 PERIMETER_BOT_ZN_3_DAYLREFPT1 3.5233E-002
84 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 PERIMETER_BOT_ZN_3_DAYLREFPT2 1.8359E-002
85 Intermediate Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 PERIMETER_BOT_ZN_3_DAYLREFPT1 3.1815E-002
86 Intermediate Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 PERIMETER_BOT_ZN_3_DAYLREFPT2 1.2394E-002
87 Overcast Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 PERIMETER_BOT_ZN_3_DAYLREFPT1 5.0165E-002
88 Overcast Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 PERIMETER_BOT_ZN_3_DAYLREFPT2 1.7442E-002
89 Clear Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 PERIMETER_BOT_ZN_3_DAYLREFPT1 2.9295E-003
90 Clear Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 PERIMETER_BOT_ZN_3_DAYLREFPT2 3.0586E-003
91 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 PERIMETER_BOT_ZN_3_DAYLREFPT1 2.4862E-003
92 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 PERIMETER_BOT_ZN_3_DAYLREFPT2 2.5871E-003
93 Intermediate Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 PERIMETER_BOT_ZN_3_DAYLREFPT1 2.1978E-003
94 Intermediate Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 PERIMETER_BOT_ZN_3_DAYLREFPT2 2.2668E-003
95 Overcast Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 PERIMETER_BOT_ZN_3_DAYLREFPT1 2.7969E-003
96 Overcast Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 PERIMETER_BOT_ZN_3_DAYLREFPT2 2.8551E-003
97 Clear Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 PERIMETER_BOT_ZN_3_DAYLREFPT1 2.8805E-003
98 Clear Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 PERIMETER_BOT_ZN_3_DAYLREFPT2 2.8827E-003
99 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 PERIMETER_BOT_ZN_3_DAYLREFPT1 2.4467E-003
100 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 PERIMETER_BOT_ZN_3_DAYLREFPT2 2.4485E-003
101 Intermediate Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 PERIMETER_BOT_ZN_3_DAYLREFPT1 2.1668E-003
102 Intermediate Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 PERIMETER_BOT_ZN_3_DAYLREFPT2 2.1680E-003
103 Overcast Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 PERIMETER_BOT_ZN_3_DAYLREFPT1 2.7739E-003
104 Overcast Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 PERIMETER_BOT_ZN_3_DAYLREFPT2 2.7748E-003
105 Clear Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 PERIMETER_BOT_ZN_4_DAYLREFPT1 5.8035E-003
106 Clear Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 PERIMETER_BOT_ZN_4_DAYLREFPT2 5.9170E-003
107 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 PERIMETER_BOT_ZN_4_DAYLREFPT1 5.4090E-003
108 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 PERIMETER_BOT_ZN_4_DAYLREFPT2 5.4909E-003
109 Intermediate Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 PERIMETER_BOT_ZN_4_DAYLREFPT1 5.3354E-003
110 Intermediate Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 PERIMETER_BOT_ZN_4_DAYLREFPT2 5.3661E-003
111 Overcast Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 PERIMETER_BOT_ZN_4_DAYLREFPT1 4.7431E-003
112 Overcast Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 PERIMETER_BOT_ZN_4_DAYLREFPT2 4.7837E-003
113 Clear Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 PERIMETER_BOT_ZN_4_DAYLREFPT1 6.3917E-002
114 Clear Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 PERIMETER_BOT_ZN_4_DAYLREFPT2 3.1506E-002
115 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 PERIMETER_BOT_ZN_4_DAYLREFPT1 5.8101E-002
116 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 PERIMETER_BOT_ZN_4_DAYLREFPT2 2.7911E-002
117 Intermediate Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 PERIMETER_BOT_ZN_4_DAYLREFPT1 6.2992E-002
118 Intermediate Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 PERIMETER_BOT_ZN_4_DAYLREFPT2 2.6159E-002
119 Overcast Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 PERIMETER_BOT_ZN_4_DAYLREFPT1 5.2230E-002
120 Overcast Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 PERIMETER_BOT_ZN_4_DAYLREFPT2 1.9536E-002
121 Clear Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 PERIMETER_BOT_ZN_4_DAYLREFPT1 5.8947E-003
122 Clear Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 PERIMETER_BOT_ZN_4_DAYLREFPT2 6.1922E-003
123 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 PERIMETER_BOT_ZN_4_DAYLREFPT1 5.5272E-003
124 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 PERIMETER_BOT_ZN_4_DAYLREFPT2 5.8477E-003
125 Intermediate Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 PERIMETER_BOT_ZN_4_DAYLREFPT1 5.3793E-003
126 Intermediate Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 PERIMETER_BOT_ZN_4_DAYLREFPT2 5.5162E-003
127 Overcast Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 PERIMETER_BOT_ZN_4_DAYLREFPT1 4.7428E-003
128 Overcast Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 PERIMETER_BOT_ZN_4_DAYLREFPT2 4.7829E-003
129 Clear Sky 01/21 PERIMETER_MID_ZN_1_DAYLCTRL PERIMETER_MID_ZN_1 PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW PERIMETER_MID_ZN_1_DAYLREFPT1 0.1711
130 Clear Sky 01/21 PERIMETER_MID_ZN_1_DAYLCTRL PERIMETER_MID_ZN_1 PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW PERIMETER_MID_ZN_1_DAYLREFPT2 0.1160
131 Clear Turbid Sky 01/21 PERIMETER_MID_ZN_1_DAYLCTRL PERIMETER_MID_ZN_1 PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW PERIMETER_MID_ZN_1_DAYLREFPT1 0.1867
132 Clear Turbid Sky 01/21 PERIMETER_MID_ZN_1_DAYLCTRL PERIMETER_MID_ZN_1 PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW PERIMETER_MID_ZN_1_DAYLREFPT2 0.1285
133 Intermediate Sky 01/21 PERIMETER_MID_ZN_1_DAYLCTRL PERIMETER_MID_ZN_1 PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW PERIMETER_MID_ZN_1_DAYLREFPT1 0.1363
134 Intermediate Sky 01/21 PERIMETER_MID_ZN_1_DAYLCTRL PERIMETER_MID_ZN_1 PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW PERIMETER_MID_ZN_1_DAYLREFPT2 7.2625E-002
135 Overcast Sky 01/21 PERIMETER_MID_ZN_1_DAYLCTRL PERIMETER_MID_ZN_1 PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW PERIMETER_MID_ZN_1_DAYLREFPT1 6.1425E-002
136 Overcast Sky 01/21 PERIMETER_MID_ZN_1_DAYLCTRL PERIMETER_MID_ZN_1 PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW PERIMETER_MID_ZN_1_DAYLREFPT2 3.0380E-002
137 Clear Sky 01/21 PERIMETER_MID_ZN_2_DAYLCTRL PERIMETER_MID_ZN_2 PERIMETER_MID_ZN_2_WALL_EAST_WINDOW PERIMETER_MID_ZN_2_DAYLREFPT1 7.9842E-002
138 Clear Sky 01/21 PERIMETER_MID_ZN_2_DAYLCTRL PERIMETER_MID_ZN_2 PERIMETER_MID_ZN_2_WALL_EAST_WINDOW PERIMETER_MID_ZN_2_DAYLREFPT2 4.7197E-002
139 Clear Turbid Sky 01/21 PERIMETER_MID_ZN_2_DAYLCTRL PERIMETER_MID_ZN_2 PERIMETER_MID_ZN_2_WALL_EAST_WINDOW PERIMETER_MID_ZN_2_DAYLREFPT1 7.4134E-002
140 Clear Turbid Sky 01/21 PERIMETER_MID_ZN_2_DAYLCTRL PERIMETER_MID_ZN_2 PERIMETER_MID_ZN_2_WALL_EAST_WINDOW PERIMETER_MID_ZN_2_DAYLREFPT2 4.3141E-002
141 Intermediate Sky 01/21 PERIMETER_MID_ZN_2_DAYLCTRL PERIMETER_MID_ZN_2 PERIMETER_MID_ZN_2_WALL_EAST_WINDOW PERIMETER_MID_ZN_2_DAYLREFPT1 7.7835E-002
142 Intermediate Sky 01/21 PERIMETER_MID_ZN_2_DAYLCTRL PERIMETER_MID_ZN_2 PERIMETER_MID_ZN_2_WALL_EAST_WINDOW PERIMETER_MID_ZN_2_DAYLREFPT2 4.0225E-002
143 Overcast Sky 01/21 PERIMETER_MID_ZN_2_DAYLCTRL PERIMETER_MID_ZN_2 PERIMETER_MID_ZN_2_WALL_EAST_WINDOW PERIMETER_MID_ZN_2_DAYLREFPT1 6.2997E-002
144 Overcast Sky 01/21 PERIMETER_MID_ZN_2_DAYLCTRL PERIMETER_MID_ZN_2 PERIMETER_MID_ZN_2_WALL_EAST_WINDOW PERIMETER_MID_ZN_2_DAYLREFPT2 3.0728E-002
145 Clear Sky 01/21 PERIMETER_MID_ZN_3_DAYLCTRL PERIMETER_MID_ZN_3 PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW PERIMETER_MID_ZN_3_DAYLREFPT1 5.7236E-002
146 Clear Sky 01/21 PERIMETER_MID_ZN_3_DAYLCTRL PERIMETER_MID_ZN_3 PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW PERIMETER_MID_ZN_3_DAYLREFPT2 3.8152E-002
147 Clear Turbid Sky 01/21 PERIMETER_MID_ZN_3_DAYLCTRL PERIMETER_MID_ZN_3 PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW PERIMETER_MID_ZN_3_DAYLREFPT1 4.5008E-002
148 Clear Turbid Sky 01/21 PERIMETER_MID_ZN_3_DAYLCTRL PERIMETER_MID_ZN_3 PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW PERIMETER_MID_ZN_3_DAYLREFPT2 3.0057E-002
149 Intermediate Sky 01/21 PERIMETER_MID_ZN_3_DAYLCTRL PERIMETER_MID_ZN_3 PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW PERIMETER_MID_ZN_3_DAYLREFPT1 4.1263E-002
150 Intermediate Sky 01/21 PERIMETER_MID_ZN_3_DAYLCTRL PERIMETER_MID_ZN_3 PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW PERIMETER_MID_ZN_3_DAYLREFPT2 2.2593E-002
151 Overcast Sky 01/21 PERIMETER_MID_ZN_3_DAYLCTRL PERIMETER_MID_ZN_3 PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW PERIMETER_MID_ZN_3_DAYLREFPT1 6.1425E-002
152 Overcast Sky 01/21 PERIMETER_MID_ZN_3_DAYLCTRL PERIMETER_MID_ZN_3 PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW PERIMETER_MID_ZN_3_DAYLREFPT2 3.0375E-002
153 Clear Sky 01/21 PERIMETER_MID_ZN_4_DAYLCTRL PERIMETER_MID_ZN_4 PERIMETER_MID_ZN_4_WALL_WEST_WINDOW PERIMETER_MID_ZN_4_DAYLREFPT1 7.6493E-002
154 Clear Sky 01/21 PERIMETER_MID_ZN_4_DAYLCTRL PERIMETER_MID_ZN_4 PERIMETER_MID_ZN_4_WALL_WEST_WINDOW PERIMETER_MID_ZN_4_DAYLREFPT2 4.5585E-002
155 Clear Turbid Sky 01/21 PERIMETER_MID_ZN_4_DAYLCTRL PERIMETER_MID_ZN_4 PERIMETER_MID_ZN_4_WALL_WEST_WINDOW PERIMETER_MID_ZN_4_DAYLREFPT1 6.9979E-002
156 Clear Turbid Sky 01/21 PERIMETER_MID_ZN_4_DAYLCTRL PERIMETER_MID_ZN_4 PERIMETER_MID_ZN_4_WALL_WEST_WINDOW PERIMETER_MID_ZN_4_DAYLREFPT2 4.1135E-002
157 Intermediate Sky 01/21 PERIMETER_MID_ZN_4_DAYLCTRL PERIMETER_MID_ZN_4 PERIMETER_MID_ZN_4_WALL_WEST_WINDOW PERIMETER_MID_ZN_4_DAYLREFPT1 7.4995E-002
158 Intermediate Sky 01/21 PERIMETER_MID_ZN_4_DAYLCTRL PERIMETER_MID_ZN_4 PERIMETER_MID_ZN_4_WALL_WEST_WINDOW PERIMETER_MID_ZN_4_DAYLREFPT2 3.8888E-002
159 Overcast Sky 01/21 PERIMETER_MID_ZN_4_DAYLCTRL PERIMETER_MID_ZN_4 PERIMETER_MID_ZN_4_WALL_WEST_WINDOW PERIMETER_MID_ZN_4_DAYLREFPT1 6.2997E-002
160 Overcast Sky 01/21 PERIMETER_MID_ZN_4_DAYLCTRL PERIMETER_MID_ZN_4 PERIMETER_MID_ZN_4_WALL_WEST_WINDOW PERIMETER_MID_ZN_4_DAYLREFPT2 3.0728E-002
161 Clear Sky 01/21 PERIMETER_TOP_ZN_1_DAYLCTRL PERIMETER_TOP_ZN_1 PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW PERIMETER_TOP_ZN_1_DAYLREFPT1 0.1712
162 Clear Sky 01/21 PERIMETER_TOP_ZN_1_DAYLCTRL PERIMETER_TOP_ZN_1 PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW PERIMETER_TOP_ZN_1_DAYLREFPT2 0.1162
163 Clear Turbid Sky 01/21 PERIMETER_TOP_ZN_1_DAYLCTRL PERIMETER_TOP_ZN_1 PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW PERIMETER_TOP_ZN_1_DAYLREFPT1 0.1868
164 Clear Turbid Sky 01/21 PERIMETER_TOP_ZN_1_DAYLCTRL PERIMETER_TOP_ZN_1 PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW PERIMETER_TOP_ZN_1_DAYLREFPT2 0.1288
165 Intermediate Sky 01/21 PERIMETER_TOP_ZN_1_DAYLCTRL PERIMETER_TOP_ZN_1 PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW PERIMETER_TOP_ZN_1_DAYLREFPT1 0.1365
166 Intermediate Sky 01/21 PERIMETER_TOP_ZN_1_DAYLCTRL PERIMETER_TOP_ZN_1 PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW PERIMETER_TOP_ZN_1_DAYLREFPT2 7.2805E-002
167 Overcast Sky 01/21 PERIMETER_TOP_ZN_1_DAYLCTRL PERIMETER_TOP_ZN_1 PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW PERIMETER_TOP_ZN_1_DAYLREFPT1 6.1557E-002
168 Overcast Sky 01/21 PERIMETER_TOP_ZN_1_DAYLCTRL PERIMETER_TOP_ZN_1 PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW PERIMETER_TOP_ZN_1_DAYLREFPT2 3.0447E-002
169 Clear Sky 01/21 PERIMETER_TOP_ZN_2_DAYLCTRL PERIMETER_TOP_ZN_2 PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW PERIMETER_TOP_ZN_2_DAYLREFPT1 7.9898E-002
170 Clear Sky 01/21 PERIMETER_TOP_ZN_2_DAYLCTRL PERIMETER_TOP_ZN_2 PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW PERIMETER_TOP_ZN_2_DAYLREFPT2 4.7269E-002
171 Clear Turbid Sky 01/21 PERIMETER_TOP_ZN_2_DAYLCTRL PERIMETER_TOP_ZN_2 PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW PERIMETER_TOP_ZN_2_DAYLREFPT1 7.4196E-002
172 Clear Turbid Sky 01/21 PERIMETER_TOP_ZN_2_DAYLCTRL PERIMETER_TOP_ZN_2 PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW PERIMETER_TOP_ZN_2_DAYLREFPT2 4.3209E-002
173 Intermediate Sky 01/21 PERIMETER_TOP_ZN_2_DAYLCTRL PERIMETER_TOP_ZN_2 PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW PERIMETER_TOP_ZN_2_DAYLREFPT1 7.7956E-002
174 Intermediate Sky 01/21 PERIMETER_TOP_ZN_2_DAYLCTRL PERIMETER_TOP_ZN_2 PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW PERIMETER_TOP_ZN_2_DAYLREFPT2 4.0310E-002
175 Overcast Sky 01/21 PERIMETER_TOP_ZN_2_DAYLCTRL PERIMETER_TOP_ZN_2 PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW PERIMETER_TOP_ZN_2_DAYLREFPT1 6.3129E-002
176 Overcast Sky 01/21 PERIMETER_TOP_ZN_2_DAYLCTRL PERIMETER_TOP_ZN_2 PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW PERIMETER_TOP_ZN_2_DAYLREFPT2 3.0795E-002
177 Clear Sky 01/21 PERIMETER_TOP_ZN_3_DAYLCTRL PERIMETER_TOP_ZN_3 PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW PERIMETER_TOP_ZN_3_DAYLREFPT1 5.7240E-002
178 Clear Sky 01/21 PERIMETER_TOP_ZN_3_DAYLCTRL PERIMETER_TOP_ZN_3 PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW PERIMETER_TOP_ZN_3_DAYLREFPT2 3.8195E-002
179 Clear Turbid Sky 01/21 PERIMETER_TOP_ZN_3_DAYLCTRL PERIMETER_TOP_ZN_3 PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW PERIMETER_TOP_ZN_3_DAYLREFPT1 4.5016E-002
180 Clear Turbid Sky 01/21 PERIMETER_TOP_ZN_3_DAYLCTRL PERIMETER_TOP_ZN_3 PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW PERIMETER_TOP_ZN_3_DAYLREFPT2 3.0091E-002
181 Intermediate Sky 01/21 PERIMETER_TOP_ZN_3_DAYLCTRL PERIMETER_TOP_ZN_3 PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW PERIMETER_TOP_ZN_3_DAYLREFPT1 4.1328E-002
182 Intermediate Sky 01/21 PERIMETER_TOP_ZN_3_DAYLCTRL PERIMETER_TOP_ZN_3 PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW PERIMETER_TOP_ZN_3_DAYLREFPT2 2.2634E-002
183 Overcast Sky 01/21 PERIMETER_TOP_ZN_3_DAYLCTRL PERIMETER_TOP_ZN_3 PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW PERIMETER_TOP_ZN_3_DAYLREFPT1 6.1557E-002
184 Overcast Sky 01/21 PERIMETER_TOP_ZN_3_DAYLCTRL PERIMETER_TOP_ZN_3 PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW PERIMETER_TOP_ZN_3_DAYLREFPT2 3.0442E-002
185 Clear Sky 01/21 PERIMETER_TOP_ZN_4_DAYLCTRL PERIMETER_TOP_ZN_4 PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW PERIMETER_TOP_ZN_4_DAYLREFPT1 7.6543E-002
186 Clear Sky 01/21 PERIMETER_TOP_ZN_4_DAYLCTRL PERIMETER_TOP_ZN_4 PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW PERIMETER_TOP_ZN_4_DAYLREFPT2 4.5653E-002
187 Clear Turbid Sky 01/21 PERIMETER_TOP_ZN_4_DAYLCTRL PERIMETER_TOP_ZN_4 PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW PERIMETER_TOP_ZN_4_DAYLREFPT1 7.0035E-002
188 Clear Turbid Sky 01/21 PERIMETER_TOP_ZN_4_DAYLCTRL PERIMETER_TOP_ZN_4 PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW PERIMETER_TOP_ZN_4_DAYLREFPT2 4.1198E-002
189 Intermediate Sky 01/21 PERIMETER_TOP_ZN_4_DAYLCTRL PERIMETER_TOP_ZN_4 PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW PERIMETER_TOP_ZN_4_DAYLREFPT1 7.5112E-002
190 Intermediate Sky 01/21 PERIMETER_TOP_ZN_4_DAYLCTRL PERIMETER_TOP_ZN_4 PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW PERIMETER_TOP_ZN_4_DAYLREFPT2 3.8969E-002
191 Overcast Sky 01/21 PERIMETER_TOP_ZN_4_DAYLCTRL PERIMETER_TOP_ZN_4 PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW PERIMETER_TOP_ZN_4_DAYLREFPT1 6.3129E-002
192 Overcast Sky 01/21 PERIMETER_TOP_ZN_4_DAYLCTRL PERIMETER_TOP_ZN_4 PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW PERIMETER_TOP_ZN_4_DAYLREFPT2 3.0795E-002


Zone Sizing Information

Zone Name Load Type Calc Des Load {W} User Des Load {W} Calc Des Air Flow Rate {m3/s} User Des Air Flow Rate {m3/s} Design Day Name Date/Time of Peak Temperature at Peak {C} Humidity Ratio at Peak {kgWater/kgDryAir} Floor Area {m2} # Occupants Calc Outdoor Air Flow Rate {m3/s} Calc DOAS Heat Addition Rate {W}
1 BASEMENT Cooling 82706.27984 82706.27984 5.95870 5.95870 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 26.62400 1.41098E-002 2779.42662 149.60210 1.20016 0.00000
2 BASEMENT Heating 0.00000 0.00000 0.00000 1.20016 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:50:00 -10.70000 1.50390E-003 2779.42662 149.60210 1.20016 0.00000
3 CORE_BOTTOM Cooling 85919.09180 85919.09180 6.18953 6.18953 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 26.62400 1.41098E-002 2496.12046 134.35320 1.07782 0.00000
4 CORE_BOTTOM Heating 0.00000 0.00000 0.00000 1.07782 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 05:40:00 -10.70000 1.50390E-003 2496.12046 134.35320 1.07782 0.00000
5 CORE_MID Cooling 810828.86430 810828.86430 58.39750 58.39750 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 26.62400 1.41098E-002 2496.12046 134.35320 10.77825 0.00000
6 CORE_MID Heating 307241.87732 307241.87732 12.97616 12.97616 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -10.70000 1.50390E-003 2496.12046 134.35320 10.77825 0.00000
7 CORE_TOP Cooling 82145.87372 82145.87372 5.91685 5.91685 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 26.62400 1.41098E-002 2496.12046 134.35320 1.07782 0.00000
8 CORE_TOP Heating 63427.13332 63427.13332 2.69674 2.69674 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -10.70000 1.50390E-003 2496.12046 134.35320 1.07782 0.00000
9 PERIMETER_BOT_ZN_3 Cooling 14968.16714 14968.16714 1.08809 1.08809 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:10:00 32.10000 1.41196E-002 313.41284 16.86939 0.13533 0.00000
10 PERIMETER_BOT_ZN_3 Heating 11633.54118 11633.54118 0.49546 0.49546 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -10.70000 1.50390E-003 313.41284 16.86939 0.13533 0.00000
11 PERIMETER_BOT_ZN_2 Cooling 18490.81847 18490.81847 1.34415 1.34415 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 08:50:00 27.79567 1.41119E-002 201.97515 10.87127 8.72129E-002 0.00000
12 PERIMETER_BOT_ZN_2 Heating 7900.93797 7900.93797 0.33657 0.33657 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -10.70000 1.50390E-003 201.97515 10.87127 8.72129E-002 0.00000
13 PERIMETER_BOT_ZN_1 Cooling 21398.73843 21398.73843 1.55554 1.55554 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 13:00:00 31.73000 1.41190E-002 313.41969 16.86975 0.13533 0.00000
14 PERIMETER_BOT_ZN_1 Heating 12730.23090 12730.23090 0.54236 0.54236 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -10.70000 1.50390E-003 313.41969 16.86975 0.13533 0.00000
15 PERIMETER_BOT_ZN_4 Cooling 22371.18356 22371.18356 1.62622 1.62622 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 16:30:00 31.36000 1.41183E-002 201.97515 10.87127 8.72129E-002 0.00000
16 PERIMETER_BOT_ZN_4 Heating 6403.53247 6403.53247 0.27253 0.27253 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -10.70000 1.50390E-003 201.97515 10.87127 8.72129E-002 0.00000
17 PERIMETER_MID_ZN_3 Cooling 143982.75189 143982.75189 10.46738 10.46738 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:20:00 32.10000 1.41196E-002 313.41284 16.86939 1.35332 0.00000
18 PERIMETER_MID_ZN_3 Heating 196842.26325 196842.26325 8.39677 8.39677 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -10.70000 1.50390E-003 313.41284 16.86939 1.35332 0.00000
19 PERIMETER_MID_ZN_2 Cooling 197582.57744 197582.57744 14.36387 14.36387 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 09:10:00 28.23967 1.41127E-002 201.97515 10.87127 0.87213 0.00000
20 PERIMETER_MID_ZN_2 Heating 129022.03650 129022.03650 5.50393 5.50393 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -10.70000 1.50390E-003 201.97515 10.87127 0.87213 0.00000
21 PERIMETER_MID_ZN_1 Cooling 213617.96061 213617.96061 15.52967 15.52967 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 13:10:00 31.79167 1.41191E-002 313.41969 16.86975 1.35335 0.00000
22 PERIMETER_MID_ZN_1 Heating 194394.91186 194394.91186 8.29211 8.29211 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -10.70000 1.50390E-003 313.41969 16.86975 1.35335 0.00000
23 PERIMETER_MID_ZN_4 Cooling 206955.43684 206955.43684 15.04525 15.04525 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 16:40:00 31.26133 1.41181E-002 201.97515 10.87127 0.87213 0.00000
24 PERIMETER_MID_ZN_4 Heating 125984.42832 125984.42832 5.37408 5.37408 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -10.70000 1.50390E-003 201.97515 10.87127 0.87213 0.00000
25 PERIMETER_TOP_ZN_3 Cooling 16192.56765 16192.56765 1.17721 1.17721 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:40:00 32.10000 1.41196E-002 313.41284 16.86939 0.13533 0.00000
26 PERIMETER_TOP_ZN_3 Heating 24561.08233 24561.08233 1.04815 1.04815 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -10.70000 1.50390E-003 313.41284 16.86939 0.13533 0.00000
27 PERIMETER_TOP_ZN_2 Cooling 20073.27968 20073.27968 1.45933 1.45933 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 09:20:00 28.44933 1.41131E-002 201.97515 10.87127 8.72129E-002 0.00000
28 PERIMETER_TOP_ZN_2 Heating 16056.84738 16056.84738 0.68524 0.68524 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -10.70000 1.50390E-003 201.97515 10.87127 8.72129E-002 0.00000
29 PERIMETER_TOP_ZN_1 Cooling 23032.68587 23032.68587 1.67448 1.67448 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 13:20:00 31.85333 1.41192E-002 313.41969 16.86975 0.13533 0.00000
30 PERIMETER_TOP_ZN_1 Heating 24299.21325 24299.21325 1.03695 1.03695 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -10.70000 1.50390E-003 313.41969 16.86975 0.13533 0.00000
31 PERIMETER_TOP_ZN_4 Cooling 21866.74424 21866.74424 1.58971 1.58971 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 16:40:00 31.26133 1.41181E-002 201.97515 10.87127 8.72129E-002 0.00000
32 PERIMETER_TOP_ZN_4 Heating 15877.37330 15877.37330 0.67758 0.67758 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -10.70000 1.50390E-003 201.97515 10.87127 8.72129E-002 0.00000
33 DATACENTER_BOT_ZN_6 Cooling 8605.13191 8605.13191 0.49336 0.49336 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 18:40:00 29.58400 1.41151E-002 36.20274 1.94861 1.56323E-002 0.00000
34 DATACENTER_BOT_ZN_6 Heating 0.00000 0.00000 0.00000 1.56323E-002 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 05:30:00 -10.70000 1.50390E-003 36.20274 1.94861 1.56323E-002 0.00000
35 DATACENTER_MID_ZN_6 Cooling 82450.39246 82450.39246 4.72715 4.72715 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 18:40:00 29.58400 1.41151E-002 36.20274 1.94861 0.15632 0.00000
36 DATACENTER_MID_ZN_6 Heating 0.00000 0.00000 0.00000 0.15632 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 05:40:00 -10.70000 1.50390E-003 36.20274 1.94861 0.15632 0.00000
37 DATACENTER_TOP_ZN_6 Cooling 8392.71837 8392.71837 0.48118 0.48118 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 18:40:00 29.58400 1.41151E-002 36.20274 1.94861 1.56323E-002 0.00000
38 DATACENTER_TOP_ZN_6 Heating 0.00000 0.00000 0.00000 1.56323E-002 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 05:40:00 -10.70000 1.50390E-003 36.20274 1.94861 1.56323E-002 0.00000
39 DATACENTER_BASEMENT_ZN_6 Cooling 373462.70268 373462.70268 21.41146 21.41146 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 07:00:00 25.36600 1.41076E-002 783.67941 42.18139 0.33839 0.00000
40 DATACENTER_BASEMENT_ZN_6 Heating 0.00000 0.00000 0.00000 0.33839 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 01:30:00 -10.70000 1.50390E-003 783.67941 42.18139 0.33839 0.00000


System Sizing Information

System Name Load Type Peak Load Kind User Design Capacity Calc Des Air Flow Rate [m3/s] User Des Air Flow Rate [m3/s] Design Day Name Date/Time of Peak
1 VAV_BOT WITH REHEAT Cooling Sensible 161657.33 10.39152 10.39152 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 00:00:00
2 VAV_BOT WITH REHEAT Heating Sensible 72209.72 2.72474 2.72474 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 07:50:00
3 VAV_MID WITH REHEAT Cooling Sensible 1511134.52 97.93377 97.93377 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 00:00:00
4 VAV_MID WITH REHEAT Heating Sensible 715277.65 40.54305 40.54305 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 06:10:00
5 VAV_TOP WITH REHEAT Cooling Sensible 169316.13 10.66535 10.66535 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 00:00:00
6 VAV_TOP WITH REHEAT Heating Sensible 72033.05 6.14467 6.14467 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 05:20:00
7 CAV_BAS Cooling Sensible 84876.02 5.95870 5.95870 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 05:00:00
8 CAV_BAS Heating Sensible 73592.09 1.20016 1.20016 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00
9 AIRLOOP DATACENTER BASEMENT Cooling Sensible 369389.80 21.41165 21.41165 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 05:00:00
10 AIRLOOP DATACENTER BASEMENT Heating Sensible 20749.82 0.33839 0.33839 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00
11 AIRLOOP DATACENTER BOT Cooling Sensible 8520.95 0.49336 0.49336 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 05:00:00
12 AIRLOOP DATACENTER BOT Heating Sensible 958.56 1.56323E-002 1.56323E-002 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00
13 AIRLOOP DATACENTER MID Cooling Sensible 81664.28 4.72715 4.72715 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 05:00:00
14 AIRLOOP DATACENTER MID Heating Sensible 9585.56 0.15632 0.15632 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00
15 AIRLOOP DATACENTER TOP Cooling Sensible 8314.66 0.48118 0.48118 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 05:00:00
16 AIRLOOP DATACENTER TOP Heating Sensible 958.56 1.56323E-002 1.56323E-002 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00


Component Sizing Information

Component Type Component Name Input Field Description Value
1 AirTerminal:SingleDuct:ConstantVolume:NoReheat BASEMENT DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 5.95870
2 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 6.18953
3 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.30730
4 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.31900
5 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 1.97446
6 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.81947
7 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
8 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.23983E-003
9 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.73840E-004
10 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 1.97446
11 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
12 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
13 Coil:Heating:Water CORE_BOTTOM VAV BOX REHEAT COIL Design Size Rated Capacity [W] 19871.00530
14 Coil:Heating:Water CORE_BOTTOM VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.73840E-004
15 Coil:Heating:Water CORE_BOTTOM VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 400.58387
16 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 58.39750
17 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.32571
18 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.33200
19 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 19.38797
20 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.86855
21 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
22 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.16977E-003
23 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 4.39489E-003
24 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 19.38797
25 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
26 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
27 Coil:Heating:Water CORE_MID VAV BOX REHEAT COIL Design Size Rated Capacity [W] 502362.84978
28 Coil:Heating:Water CORE_MID VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 4.39489E-003
29 Coil:Heating:Water CORE_MID VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 12020.25096
30 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 5.91685
31 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.32146
32 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.33600
33 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 1.98806
34 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.85723
35 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
36 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.18521E-003
37 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 7.92321E-004
38 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 2.69674
39 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
40 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
41 Coil:Heating:Water CORE_TOP VAV BOX REHEAT COIL Design Size Rated Capacity [W] 90567.17287
42 Coil:Heating:Water CORE_TOP VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 7.92321E-004
43 Coil:Heating:Water CORE_TOP VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 2390.90404
44 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 1.08809
45 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.21949
46 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.22800
47 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.24808
48 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.58530
49 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
50 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.73587E-003
51 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.45322E-004
52 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.49546
53 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
54 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
55 Coil:Heating:Water PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 16611.22422
56 Coil:Heating:Water PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.45322E-004
57 Coil:Heating:Water PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 438.18153
58 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 1.34415
59 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.11450
60 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.20000
61 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.26883
62 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.30533
63 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
64 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 3.32752E-003
65 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 9.87059E-005
66 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.33657
67 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
68 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
69 Coil:Heating:Water PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 11282.69198
70 Coil:Heating:Water PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 9.87059E-005
71 Coil:Heating:Water PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 297.60531
72 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 1.55554
73 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.15353
74 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.20000
75 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.31111
76 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.40942
77 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
78 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 2.48156E-003
79 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.59051E-004
80 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.54236
81 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
82 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
83 Coil:Heating:Water PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 18180.51980
84 Coil:Heating:Water PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.59051E-004
85 Coil:Heating:Water PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 479.54210
86 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 1.62622
87 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 9.46397E-002
88 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.20000
89 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.32524
90 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.30000
91 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
92 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 4.02579E-003
93 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 8.45925E-005
94 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.32524
95 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
96 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
97 Coil:Heating:Water PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 9669.43793
98 Coil:Heating:Water PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 8.45925E-005
99 Coil:Heating:Water PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 242.59568
100 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 10.46738
101 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.22816
102 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.23300
103 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 2.43890
104 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.60842
105 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
106 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.66990E-003
107 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 2.45988E-003
108 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 8.39677
109 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
110 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
111 Coil:Heating:Water PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 281179.94216
112 Coil:Heating:Water PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 2.45988E-003
113 Coil:Heating:Water PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 7413.08367
114 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_2 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 14.36387
115 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_2 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.10715
116 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_2 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.20000
117 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_2 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 2.87277
118 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_2 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.30000
119 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_2 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
120 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_2 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 3.55585E-003
121 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_2 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.61235E-003
122 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 5.50393
123 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
124 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
125 Coil:Heating:Water PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 184302.04581
126 Coil:Heating:Water PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.61235E-003
127 Coil:Heating:Water PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 4858.90051
128 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 15.52967
129 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.15379
130 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.20000
131 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 3.10593
132 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.41010
133 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
134 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 2.47746E-003
135 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 2.42927E-003
136 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 8.29211
137 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
138 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
139 Coil:Heating:Water PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 277679.96566
140 Coil:Heating:Water PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 2.42927E-003
141 Coil:Heating:Water PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 7320.86528
142 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 15.04525
143 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.10229
144 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.20000
145 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 3.00905
146 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.30000
147 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
148 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 3.72453E-003
149 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.57435E-003
150 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 5.37408
151 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
152 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
153 Coil:Heating:Water PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 179958.25521
154 Coil:Heating:Water PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.57435E-003
155 Coil:Heating:Water PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 4744.43369
156 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 1.17721
157 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.20287
158 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.21200
159 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.24957
160 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.54099
161 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
162 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.87805E-003
163 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 3.06965E-004
164 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 1.04815
165 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
166 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
167 Coil:Heating:Water PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 35087.95332
168 Coil:Heating:Water PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 3.06965E-004
169 Coil:Heating:Water PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 924.93159
170 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 1.45933
171 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.10546
172 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.20000
173 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.29187
174 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.30000
175 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
176 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 3.61265E-003
177 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 2.00678E-004
178 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.68524
179 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
180 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
181 Coil:Heating:Water PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 22938.67402
182 Coil:Heating:Water PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 2.00678E-004
183 Coil:Heating:Water PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 604.66475
184 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 1.67448
185 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.14263
186 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.20000
187 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.33490
188 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.38034
189 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
190 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 2.67131E-003
191 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 3.03689E-004
192 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 1.03695
193 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
194 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
195 Coil:Heating:Water PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 34713.48113
196 Coil:Heating:Water PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 3.03689E-004
197 Coil:Heating:Water PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 915.06484
198 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 1.58971
199 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 9.68132E-002
200 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.20000
201 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.31794
202 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.30000
203 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
204 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 3.93541E-003
205 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.98433E-004
206 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.67758
207 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
208 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
209 Coil:Heating:Water PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 22682.07048
210 Coil:Heating:Water PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.98433E-004
211 Coil:Heating:Water PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 597.90186
212 AirTerminal:SingleDuct:ConstantVolume:NoReheat DATACENTER_BOT_ZN_6 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 0.49336
213 AirTerminal:SingleDuct:ConstantVolume:NoReheat DATACENTER_MID_ZN_6 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 4.72715
214 AirTerminal:SingleDuct:ConstantVolume:NoReheat DATACENTER_TOP_ZN_6 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 0.48118
215 AirTerminal:SingleDuct:ConstantVolume:NoReheat DATACENTER_BASEMENT_ZN_6 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 21.41146
216 AirLoopHVAC VAV_BOT WITH REHEAT Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 5.90177
217 AirLoopHVAC VAV_BOT WITH REHEAT Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 3.12773
218 AirLoopHVAC VAV_BOT WITH REHEAT Sum of Air Terminal Maximum Flow Rates [m3/s] 11.80353
219 AirLoopHVAC VAV_BOT WITH REHEAT Adjusted Heating Design Air Flow Rate [m3/s] 3.12773
220 AirLoopHVAC VAV_BOT WITH REHEAT Adjusted Cooling Design Air Flow Rate [m3/s] 10.39152
221 AirLoopHVAC VAV_BOT WITH REHEAT Adjusted Main Design Air Flow Rate [m3/s] 10.39152
222 AirLoopHVAC VAV_BOT WITH REHEAT User Heating Air Flow Ratio [] 0.30000
223 AirLoopHVAC VAV_BOT WITH REHEAT Calculated Heating Air Flow Ratio [] 0.30099
224 AirLoopHVAC VAV_MID WITH REHEAT Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 56.90184
225 AirLoopHVAC VAV_MID WITH REHEAT Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 30.81463
226 AirLoopHVAC VAV_MID WITH REHEAT Sum of Air Terminal Maximum Flow Rates [m3/s] 113.80367
227 AirLoopHVAC VAV_MID WITH REHEAT Adjusted Heating Design Air Flow Rate [m3/s] 40.54305
228 AirLoopHVAC VAV_MID WITH REHEAT Adjusted Cooling Design Air Flow Rate [m3/s] 97.93377
229 AirLoopHVAC VAV_MID WITH REHEAT Adjusted Main Design Air Flow Rate [m3/s] 97.93377
230 AirLoopHVAC VAV_MID WITH REHEAT User Heating Air Flow Ratio [] 0.30000
231 AirLoopHVAC VAV_MID WITH REHEAT Calculated Heating Air Flow Ratio [] 0.41398
232 AirLoopHVAC VAV_TOP WITH REHEAT Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 5.90879
233 AirLoopHVAC VAV_TOP WITH REHEAT Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 3.18234
234 AirLoopHVAC VAV_TOP WITH REHEAT Sum of Air Terminal Maximum Flow Rates [m3/s] 11.81759
235 AirLoopHVAC VAV_TOP WITH REHEAT Adjusted Heating Design Air Flow Rate [m3/s] 6.14467
236 AirLoopHVAC VAV_TOP WITH REHEAT Adjusted Cooling Design Air Flow Rate [m3/s] 10.66535
237 AirLoopHVAC VAV_TOP WITH REHEAT Adjusted Main Design Air Flow Rate [m3/s] 10.66535
238 AirLoopHVAC VAV_TOP WITH REHEAT User Heating Air Flow Ratio [] 0.30000
239 AirLoopHVAC VAV_TOP WITH REHEAT Calculated Heating Air Flow Ratio [] 0.57613
240 AirLoopHVAC CAV_BAS Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 5.95870
241 AirLoopHVAC CAV_BAS Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 5.95870
242 AirLoopHVAC CAV_BAS Sum of Air Terminal Maximum Flow Rates [m3/s] 5.95870
243 AirLoopHVAC CAV_BAS Adjusted Heating Design Air Flow Rate [m3/s] 5.95870
244 AirLoopHVAC CAV_BAS Adjusted Cooling Design Air Flow Rate [m3/s] 5.95870
245 AirLoopHVAC CAV_BAS Adjusted Main Design Air Flow Rate [m3/s] 5.95870
246 AirLoopHVAC CAV_BAS User Heating Air Flow Ratio [] 1.00000
247 AirLoopHVAC CAV_BAS Calculated Heating Air Flow Ratio [] 1.00000
248 AirLoopHVAC AIRLOOP DATACENTER BASEMENT Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 21.41146
249 AirLoopHVAC AIRLOOP DATACENTER BASEMENT Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 21.41146
250 AirLoopHVAC AIRLOOP DATACENTER BASEMENT Sum of Air Terminal Maximum Flow Rates [m3/s] 21.41146
251 AirLoopHVAC AIRLOOP DATACENTER BASEMENT Adjusted Heating Design Air Flow Rate [m3/s] 21.41146
252 AirLoopHVAC AIRLOOP DATACENTER BASEMENT Adjusted Cooling Design Air Flow Rate [m3/s] 21.41165
253 AirLoopHVAC AIRLOOP DATACENTER BASEMENT Adjusted Main Design Air Flow Rate [m3/s] 21.41165
254 AirLoopHVAC AIRLOOP DATACENTER BASEMENT User Heating Air Flow Ratio [] 1.00000
255 AirLoopHVAC AIRLOOP DATACENTER BASEMENT Calculated Heating Air Flow Ratio [] 0.99999
256 AirLoopHVAC AIRLOOP DATACENTER BOT Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 0.49336
257 AirLoopHVAC AIRLOOP DATACENTER BOT Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 0.49336
258 AirLoopHVAC AIRLOOP DATACENTER BOT Sum of Air Terminal Maximum Flow Rates [m3/s] 0.49336
259 AirLoopHVAC AIRLOOP DATACENTER BOT Adjusted Heating Design Air Flow Rate [m3/s] 0.49336
260 AirLoopHVAC AIRLOOP DATACENTER BOT Adjusted Cooling Design Air Flow Rate [m3/s] 0.49336
261 AirLoopHVAC AIRLOOP DATACENTER BOT Adjusted Main Design Air Flow Rate [m3/s] 0.49336
262 AirLoopHVAC AIRLOOP DATACENTER BOT User Heating Air Flow Ratio [] 1.00000
263 AirLoopHVAC AIRLOOP DATACENTER BOT Calculated Heating Air Flow Ratio [] 1.00000
264 AirLoopHVAC AIRLOOP DATACENTER MID Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 4.72715
265 AirLoopHVAC AIRLOOP DATACENTER MID Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 4.72715
266 AirLoopHVAC AIRLOOP DATACENTER MID Sum of Air Terminal Maximum Flow Rates [m3/s] 4.72715
267 AirLoopHVAC AIRLOOP DATACENTER MID Adjusted Heating Design Air Flow Rate [m3/s] 4.72715
268 AirLoopHVAC AIRLOOP DATACENTER MID Adjusted Cooling Design Air Flow Rate [m3/s] 4.72715
269 AirLoopHVAC AIRLOOP DATACENTER MID Adjusted Main Design Air Flow Rate [m3/s] 4.72715
270 AirLoopHVAC AIRLOOP DATACENTER MID User Heating Air Flow Ratio [] 1.00000
271 AirLoopHVAC AIRLOOP DATACENTER MID Calculated Heating Air Flow Ratio [] 1.00000
272 AirLoopHVAC AIRLOOP DATACENTER TOP Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 0.48118
273 AirLoopHVAC AIRLOOP DATACENTER TOP Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 0.48118
274 AirLoopHVAC AIRLOOP DATACENTER TOP Sum of Air Terminal Maximum Flow Rates [m3/s] 0.48118
275 AirLoopHVAC AIRLOOP DATACENTER TOP Adjusted Heating Design Air Flow Rate [m3/s] 0.48118
276 AirLoopHVAC AIRLOOP DATACENTER TOP Adjusted Cooling Design Air Flow Rate [m3/s] 0.48118
277 AirLoopHVAC AIRLOOP DATACENTER TOP Adjusted Main Design Air Flow Rate [m3/s] 0.48118
278 AirLoopHVAC AIRLOOP DATACENTER TOP User Heating Air Flow Ratio [] 1.00000
279 AirLoopHVAC AIRLOOP DATACENTER TOP Calculated Heating Air Flow Ratio [] 1.00000
280 AirLoopHVAC VAV_BOT WITH REHEAT Design Supply Air Flow Rate [m3/s] 10.39152
281 AirLoopHVAC VAV_MID WITH REHEAT Design Supply Air Flow Rate [m3/s] 97.93377
282 AirLoopHVAC VAV_TOP WITH REHEAT Design Supply Air Flow Rate [m3/s] 10.66535
283 AirLoopHVAC CAV_BAS Design Supply Air Flow Rate [m3/s] 5.95870
284 AirLoopHVAC AIRLOOP DATACENTER BASEMENT Design Supply Air Flow Rate [m3/s] 21.41165
285 AirLoopHVAC AIRLOOP DATACENTER BOT Design Supply Air Flow Rate [m3/s] 0.49336
286 AirLoopHVAC AIRLOOP DATACENTER MID Design Supply Air Flow Rate [m3/s] 4.72715
287 AirLoopHVAC AIRLOOP DATACENTER TOP Design Supply Air Flow Rate [m3/s] 0.48118
288 Controller:OutdoorAir VAV_BOT WITH REHEAT_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 10.39152
289 Controller:OutdoorAir VAV_BOT WITH REHEAT_OA_CONTROLLER Minimum Outdoor Air Flow Rate [m3/s] 2.53819
290 HeatExchanger:AirToAir:SensibleAndLatent VAV_BOT WITH REHEAT OA HEAT RECOVERY Design Size Nominal Supply Air Flow Rate [m3/s] 2.53819
291 Coil:Cooling:Water VAV_BOT WITH REHEAT COOLING COIL Design Size Design Inlet Air Temperature [C] 26.03459
292 Coil:Cooling:Water VAV_BOT WITH REHEAT COOLING COIL Design Size Design Inlet Water Temperature [C] 6.67000
293 Coil:Cooling:Water VAV_BOT WITH REHEAT COOLING COIL Design Size Design Outlet Air Temperature [C] 11.05560
294 Coil:Cooling:Water VAV_BOT WITH REHEAT COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 1.01847E-002
295 Coil:Cooling:Water VAV_BOT WITH REHEAT COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 8.50000E-003
296 Coil:Cooling:Water VAV_BOT WITH REHEAT COOLING COIL Design Size Design Coil Load [W] 244927.46361
297 Coil:Cooling:Water VAV_BOT WITH REHEAT COOLING COIL Design Size Design Water Flow Rate [m3/s] 1.04198E-002
298 Coil:Cooling:Water VAV_BOT WITH REHEAT COOLING COIL Design Size Design Air Flow Rate [m3/s] 10.39152
299 Coil:Heating:Water VAV_BOT WITH REHEAT HEATING COIL Design Size Rated Capacity [W] 72503.50700
300 Coil:Heating:Water VAV_BOT WITH REHEAT HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 6.34292E-004
301 Coil:Heating:Water VAV_BOT WITH REHEAT HEATING COIL Design Size U-Factor Times Area Value [W/K] 1172.86192
302 Fan:VariableVolume VAV_BOT WITH REHEAT FAN Design Size Maximum Flow Rate [m3/s] 10.39152
303 Controller:WaterCoil VAV_BOT WITH REHEAT_COOLC_CONTROLLER Maximum Actuated Flow [m3/s] 1.04198E-002
304 Controller:WaterCoil VAV_BOT WITH REHEAT_COOLC_CONTROLLER Controller Convergence Tolerance 4.57006E-005
305 Controller:WaterCoil VAV_BOT WITH REHEAT_HEATC_CONTROLLER Maximum Actuated Flow [m3/s] 6.34292E-004
306 Controller:OutdoorAir VAV_MID WITH REHEAT_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 97.93377
307 Controller:OutdoorAir VAV_MID WITH REHEAT_OA_CONTROLLER Minimum Outdoor Air Flow Rate [m3/s] 25.38195
308 HeatExchanger:AirToAir:SensibleAndLatent VAV_MID WITH REHEAT OA HEAT RECOVERY Design Size Nominal Supply Air Flow Rate [m3/s] 25.38195
309 Coil:Cooling:Water VAV_MID WITH REHEAT COOLING COIL Design Size Design Inlet Air Temperature [C] 26.20428
310 Coil:Cooling:Water VAV_MID WITH REHEAT COOLING COIL Design Size Design Inlet Water Temperature [C] 6.67000
311 Coil:Cooling:Water VAV_MID WITH REHEAT COOLING COIL Design Size Design Outlet Air Temperature [C] 10.95711
312 Coil:Cooling:Water VAV_MID WITH REHEAT COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 1.03715E-002
313 Coil:Cooling:Water VAV_MID WITH REHEAT COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 8.50000E-003
314 Coil:Cooling:Water VAV_MID WITH REHEAT COOLING COIL Design Size Design Coil Load [W] 2396783.59285
315 Coil:Cooling:Water VAV_MID WITH REHEAT COOLING COIL Design Size Design Water Flow Rate [m3/s] 0.10196
316 Coil:Cooling:Water VAV_MID WITH REHEAT COOLING COIL Design Size Design Air Flow Rate [m3/s] 97.93377
317 Coil:Heating:Water VAV_MID WITH REHEAT HEATING COIL Design Size Rated Capacity [W] 691595.11298
318 Coil:Heating:Water VAV_MID WITH REHEAT HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 6.05038E-003
319 Coil:Heating:Water VAV_MID WITH REHEAT HEATING COIL Design Size U-Factor Times Area Value [W/K] 11173.04151
320 Fan:VariableVolume VAV_MID WITH REHEAT FAN Design Size Maximum Flow Rate [m3/s] 97.93377
321 Controller:WaterCoil VAV_MID WITH REHEAT_COOLC_CONTROLLER Maximum Actuated Flow [m3/s] 0.10196
322 Controller:WaterCoil VAV_MID WITH REHEAT_COOLC_CONTROLLER Controller Convergence Tolerance 4.67015E-006
323 Controller:WaterCoil VAV_MID WITH REHEAT_HEATC_CONTROLLER Maximum Actuated Flow [m3/s] 6.05038E-003
324 Controller:OutdoorAir VAV_TOP WITH REHEAT_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 10.66535
325 Controller:OutdoorAir VAV_TOP WITH REHEAT_OA_CONTROLLER Minimum Outdoor Air Flow Rate [m3/s] 2.53819
326 HeatExchanger:AirToAir:SensibleAndLatent VAV_TOP WITH REHEAT OA HEAT RECOVERY Design Size Nominal Supply Air Flow Rate [m3/s] 2.53819
327 Coil:Cooling:Water VAV_TOP WITH REHEAT COOLING COIL Design Size Design Inlet Air Temperature [C] 25.92617
328 Coil:Cooling:Water VAV_TOP WITH REHEAT COOLING COIL Design Size Design Inlet Water Temperature [C] 6.67000
329 Coil:Cooling:Water VAV_TOP WITH REHEAT COOLING COIL Design Size Design Outlet Air Temperature [C] 11.05556
330 Coil:Cooling:Water VAV_TOP WITH REHEAT COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 1.01712E-002
331 Coil:Cooling:Water VAV_TOP WITH REHEAT COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 8.50000E-003
332 Coil:Cooling:Water VAV_TOP WITH REHEAT COOLING COIL Design Size Design Coil Load [W] 249517.11946
333 Coil:Cooling:Water VAV_TOP WITH REHEAT COOLING COIL Design Size Design Water Flow Rate [m3/s] 1.06150E-002
334 Coil:Cooling:Water VAV_TOP WITH REHEAT COOLING COIL Design Size Design Air Flow Rate [m3/s] 10.66535
335 Coil:Heating:Water VAV_TOP WITH REHEAT HEATING COIL Design Size Rated Capacity [W] 68252.18145
336 Coil:Heating:Water VAV_TOP WITH REHEAT HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 5.97100E-004
337 Coil:Heating:Water VAV_TOP WITH REHEAT HEATING COIL Design Size U-Factor Times Area Value [W/K] 1113.65689
338 Fan:VariableVolume VAV_TOP WITH REHEAT FAN Design Size Maximum Flow Rate [m3/s] 10.66535
339 Controller:WaterCoil VAV_TOP WITH REHEAT_COOLC_CONTROLLER Maximum Actuated Flow [m3/s] 1.06150E-002
340 Controller:WaterCoil VAV_TOP WITH REHEAT_COOLC_CONTROLLER Controller Convergence Tolerance 4.48600E-005
341 Controller:WaterCoil VAV_TOP WITH REHEAT_HEATC_CONTROLLER Maximum Actuated Flow [m3/s] 5.97100E-004
342 Controller:OutdoorAir CAV_BAS_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 5.95870
343 Controller:OutdoorAir CAV_BAS_OA_CONTROLLER Minimum Outdoor Air Flow Rate [m3/s] 1.20016
344 Coil:Cooling:Water CAV_BAS COOLING COIL Design Size Design Inlet Air Temperature [C] 24.57737
345 Coil:Cooling:Water CAV_BAS COOLING COIL Design Size Design Inlet Water Temperature [C] 6.67000
346 Coil:Cooling:Water CAV_BAS COOLING COIL Design Size Design Outlet Air Temperature [C] 11.42334
347 Coil:Cooling:Water CAV_BAS COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 9.96654E-003
348 Coil:Cooling:Water CAV_BAS COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 8.50000E-003
349 Coil:Cooling:Water CAV_BAS COOLING COIL Design Size Design Coil Load [W] 123071.04313
350 Coil:Cooling:Water CAV_BAS COOLING COIL Design Size Design Water Flow Rate [m3/s] 5.23573E-003
351 Coil:Cooling:Water CAV_BAS COOLING COIL Design Size Design Air Flow Rate [m3/s] 5.95870
352 Coil:Heating:Water CAV_BAS HEATING COIL Design Size Rated Capacity [W] 303799.48141
353 Coil:Heating:Water CAV_BAS HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 2.65777E-003
354 Coil:Heating:Water CAV_BAS HEATING COIL Design Size U-Factor Times Area Value [W/K] 6686.53745
355 Fan:ConstantVolume CAV_BAS FAN Design Size Maximum Flow Rate [m3/s] 5.95870
356 Controller:WaterCoil CAV_BAS_COOLC_CONTROLLER Maximum Actuated Flow [m3/s] 5.23573E-003
357 Controller:WaterCoil CAV_BAS_COOLC_CONTROLLER Controller Convergence Tolerance 9.09502E-005
358 Controller:WaterCoil CAV_BAS_HEATC_CONTROLLER Maximum Actuated Flow [m3/s] 2.65777E-003
359 Controller:OutdoorAir AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 21.41165
360 Controller:OutdoorAir AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER Minimum Outdoor Air Flow Rate [m3/s] 0.33839
361 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER BASEMENT COOLING COIL Design Size Rated Air Flow Rate [m3/s] 21.41165
362 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER BASEMENT COOLING COIL Design Size Rated Total Cooling Capacity [W] 433170.49266
363 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER BASEMENT COOLING COIL Design Size Rated Sensible Cooling Capacity [W] 312730.65740
364 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER BASEMENT COOLING COIL Design Size Rated Water Flow Rate [m3/s] 1.06083E-002
365 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP Supply Air Flow Rate [m3/s] 21.41165
366 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP Supply Air Flow Rate During Heating Operation [m3/s] 21.41165
367 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP Supply Air Flow Rate During Cooling Operation [m3/s] 21.41165
368 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] 21.41165
369 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP Nominal Heating Capacity [W] 433170.49266
370 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP Nominal Cooling Capacity [W] 433170.49266
371 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP Supplemental Heating Coil Nominal Capacity [W] 20749.82071
372 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
373 Fan:OnOff AIRLOOP DATACENTER BASEMENT SUPPLY FAN Design Size Maximum Flow Rate [m3/s] 21.41165
374 COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER BASEMENT HEATING COIL Design Size Rated Air Flow Rate [m3/s] 21.41165
375 COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER BASEMENT HEATING COIL Design Size Rated Heating Capacity [W] 433170.49266
376 COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER BASEMENT HEATING COIL Design Size Rated Water Flow Rate [m3/s] 1.06083E-002
377 Coil:Heating:Electric AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL Design Size Nominal Capacity [W] 20749.82071
378 Humidifier:Steam:Electric DATACENTER_BASEMENT_ZN_6 HUMIDIFIER Design Size Nominal Capacity Volume [m3/s] 1.73598E-004
379 Humidifier:Steam:Electric DATACENTER_BASEMENT_ZN_6 HUMIDIFIER User-Specified Nominal Capacity Volume [m3/s] 3.72000E-005
380 Humidifier:Steam:Electric DATACENTER_BASEMENT_ZN_6 HUMIDIFIER Design Size Rated Power [W] 96450.69782
381 Humidifier:Steam:Electric DATACENTER_BASEMENT_ZN_6 HUMIDIFIER User-Specified Rated Power [W] 100000.00000
382 Controller:OutdoorAir AIRLOOP DATACENTER BOT_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 0.49336
383 Controller:OutdoorAir AIRLOOP DATACENTER BOT_OA_CONTROLLER Minimum Outdoor Air Flow Rate [m3/s] 1.56323E-002
384 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER BOT COOLING COIL Design Size Rated Air Flow Rate [m3/s] 0.49336
385 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER BOT COOLING COIL Design Size Rated Total Cooling Capacity [W] 9910.60002
386 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER BOT COOLING COIL Design Size Rated Sensible Cooling Capacity [W] 7177.44013
387 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER BOT COOLING COIL Design Size Rated Water Flow Rate [m3/s] 2.42710E-004
388 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BOT DXAC HEAT PUMP Supply Air Flow Rate [m3/s] 0.49336
389 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BOT DXAC HEAT PUMP Supply Air Flow Rate During Heating Operation [m3/s] 0.49336
390 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BOT DXAC HEAT PUMP Supply Air Flow Rate During Cooling Operation [m3/s] 0.49336
391 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BOT DXAC HEAT PUMP Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] 0.49336
392 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BOT DXAC HEAT PUMP Nominal Heating Capacity [W] 9910.60002
393 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BOT DXAC HEAT PUMP Nominal Cooling Capacity [W] 9910.60002
394 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BOT DXAC HEAT PUMP Supplemental Heating Coil Nominal Capacity [W] 958.55576
395 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BOT DXAC HEAT PUMP Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
396 Fan:OnOff AIRLOOP DATACENTER BOT SUPPLY FAN Design Size Maximum Flow Rate [m3/s] 0.49336
397 COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER BOT HEATING COIL Design Size Rated Air Flow Rate [m3/s] 0.49336
398 COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER BOT HEATING COIL Design Size Rated Heating Capacity [W] 9910.60002
399 COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER BOT HEATING COIL Design Size Rated Water Flow Rate [m3/s] 2.42710E-004
400 Coil:Heating:Electric AIRLOOP DATACENTER BOT_SUPPHEATCOIL Design Size Nominal Capacity [W] 958.55576
401 Controller:OutdoorAir AIRLOOP DATACENTER MID_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 4.72715
402 Controller:OutdoorAir AIRLOOP DATACENTER MID_OA_CONTROLLER Minimum Outdoor Air Flow Rate [m3/s] 0.15632
403 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER MID COOLING COIL Design Size Rated Air Flow Rate [m3/s] 4.72715
404 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER MID COOLING COIL Design Size Rated Total Cooling Capacity [W] 95118.13171
405 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER MID COOLING COIL Design Size Rated Sensible Cooling Capacity [W] 68824.67173
406 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER MID COOLING COIL Design Size Rated Water Flow Rate [m3/s] 2.32944E-003
407 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER MID DXAC HEAT PUMP Supply Air Flow Rate [m3/s] 4.72715
408 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER MID DXAC HEAT PUMP Supply Air Flow Rate During Heating Operation [m3/s] 4.72715
409 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER MID DXAC HEAT PUMP Supply Air Flow Rate During Cooling Operation [m3/s] 4.72715
410 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER MID DXAC HEAT PUMP Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] 4.72715
411 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER MID DXAC HEAT PUMP Nominal Heating Capacity [W] 95118.13171
412 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER MID DXAC HEAT PUMP Nominal Cooling Capacity [W] 95118.13171
413 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER MID DXAC HEAT PUMP Supplemental Heating Coil Nominal Capacity [W] 9585.55755
414 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER MID DXAC HEAT PUMP Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
415 Fan:OnOff AIRLOOP DATACENTER MID SUPPLY FAN Design Size Maximum Flow Rate [m3/s] 4.72715
416 COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER MID HEATING COIL Design Size Rated Air Flow Rate [m3/s] 4.72715
417 COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER MID HEATING COIL Design Size Rated Heating Capacity [W] 95118.13171
418 COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER MID HEATING COIL Design Size Rated Water Flow Rate [m3/s] 2.32944E-003
419 Coil:Heating:Electric AIRLOOP DATACENTER MID_SUPPHEATCOIL Design Size Nominal Capacity [W] 9585.55755
420 Controller:OutdoorAir AIRLOOP DATACENTER TOP_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 0.48118
421 Controller:OutdoorAir AIRLOOP DATACENTER TOP_OA_CONTROLLER Minimum Outdoor Air Flow Rate [m3/s] 1.56323E-002
422 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER TOP COOLING COIL Design Size Rated Air Flow Rate [m3/s] 0.48118
423 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER TOP COOLING COIL Design Size Rated Total Cooling Capacity [W] 9678.20690
424 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER TOP COOLING COIL Design Size Rated Sensible Cooling Capacity [W] 7004.39140
425 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER TOP COOLING COIL Design Size Rated Water Flow Rate [m3/s] 2.37019E-004
426 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER TOP DXAC HEAT PUMP Supply Air Flow Rate [m3/s] 0.48118
427 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER TOP DXAC HEAT PUMP Supply Air Flow Rate During Heating Operation [m3/s] 0.48118
428 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER TOP DXAC HEAT PUMP Supply Air Flow Rate During Cooling Operation [m3/s] 0.48118
429 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER TOP DXAC HEAT PUMP Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] 0.48118
430 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER TOP DXAC HEAT PUMP Nominal Heating Capacity [W] 9678.20690
431 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER TOP DXAC HEAT PUMP Nominal Cooling Capacity [W] 9678.20690
432 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER TOP DXAC HEAT PUMP Supplemental Heating Coil Nominal Capacity [W] 958.55576
433 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER TOP DXAC HEAT PUMP Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
434 Fan:OnOff AIRLOOP DATACENTER TOP SUPPLY FAN Design Size Maximum Flow Rate [m3/s] 0.48118
435 COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER TOP HEATING COIL Design Size Rated Air Flow Rate [m3/s] 0.48118
436 COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER TOP HEATING COIL Design Size Rated Heating Capacity [W] 9678.20690
437 COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER TOP HEATING COIL Design Size Rated Water Flow Rate [m3/s] 2.37019E-004
438 Coil:Heating:Electric AIRLOOP DATACENTER TOP_SUPPHEATCOIL Design Size Nominal Capacity [W] 958.55576
439 Pump:VariableSpeed COOLSYS1 PUMP SECONDARY Design Flow Rate [m3/s] 0.12824
440 Pump:VariableSpeed COOLSYS1 PUMP SECONDARY Design Power Consumption [W] 20936.89902
441 PlantLoop COOLSYS1_DEMAND Maximum Loop Flow Rate [m3/s] 0.12824
442 PlantLoop COOLSYS1_DEMAND Plant Loop Volume [m3] 15.38823
443 HeatExchanger:FluidToFluid BYPASS HEAT EXCHANGER Loop Supply Side Design Fluid Flow Rate [m3/s] 0.12824
444 HeatExchanger:FluidToFluid BYPASS HEAT EXCHANGER Loop Demand Side Design Fluid Flow Rate [m3/s] 0.12824
445 HeatExchanger:FluidToFluid BYPASS HEAT EXCHANGER Heat Exchanger U-Factor Times Area Value [W/C] 538267.71769
446 HeatExchanger:FluidToFluid BYPASS HEAT EXCHANGER Loop-to-loop Temperature Difference Used to Size Heat Exchanger U-Factor Times Area Value [C] 5.60000
447 PlantLoop HEATSYS1 Maximum Loop Flow Rate [m3/s] 2.48739E-002
448 PlantLoop HEATSYS1 Plant Loop Volume [m3] 2.98487
449 Pump:VariableSpeed HEATSYS1 PUMP Design Flow Rate [m3/s] 2.48739E-002
450 Pump:VariableSpeed HEATSYS1 PUMP Design Power Consumption [W] 7490.92111
451 Pump:VariableSpeed HEATSYS1 PUMP Design Minimum Flow Rate [m3/s] 0.00000
452 Boiler:HotWater HEATSYS1 BOILER Design Size Nominal Capacity [W] 2843237.57251
453 Boiler:HotWater HEATSYS1 BOILER User-Specified Nominal Capacity [W] 2843237.57000
454 Boiler:HotWater HEATSYS1 BOILER Design Size Design Water Flow Rate [m3/s] 2.48739E-002
455 PlantLoop COOLSYS1_SUPPLY Maximum Loop Flow Rate [m3/s] 0.12824
456 PlantLoop COOLSYS1_SUPPLY Plant Loop Volume [m3] 15.38823
457 Pump:ConstantSpeed COOLSYS1 CHILLER1 PUMP Design Flow Rate [m3/s] 6.41176E-002
458 Pump:ConstantSpeed COOLSYS1 CHILLER1 PUMP Design Power Consumption [W] 7247.66063
459 Pump:ConstantSpeed COOLSYS1 CHILLER2 PUMP Design Flow Rate [m3/s] 6.41176E-002
460 Pump:ConstantSpeed COOLSYS1 CHILLER2 PUMP Design Power Consumption [W] 7247.66063
461 Chiller:Electric:ReformulatedEIR COOLSYS1 CHILLER1 Design Size Reference Chilled Water Flow Rate [m3/s] 0.12824
462 Chiller:Electric:ReformulatedEIR COOLSYS1 CHILLER1 User-Specified Reference Chilled Water Flow Rate [m3/s] 6.45050E-002
463 Chiller:Electric:ReformulatedEIR COOLSYS1 CHILLER1 Design Size Reference Capacity [W] 1519979.80211
464 Chiller:Electric:ReformulatedEIR COOLSYS1 CHILLER1 User-Specified Reference Capacity [W] 1527224.44000
465 Chiller:Electric:ReformulatedEIR COOLSYS1 CHILLER1 Design Size Reference Condenser Water Flow Rate [m3/s] 7.55767E-002
466 Chiller:Electric:ReformulatedEIR COOLSYS1 CHILLER2 Design Size Reference Chilled Water Flow Rate [m3/s] 0.12824
467 Chiller:Electric:ReformulatedEIR COOLSYS1 CHILLER2 User-Specified Reference Chilled Water Flow Rate [m3/s] 6.45050E-002
468 Chiller:Electric:ReformulatedEIR COOLSYS1 CHILLER2 Design Size Reference Capacity [W] 1519979.80211
469 Chiller:Electric:ReformulatedEIR COOLSYS1 CHILLER2 User-Specified Reference Capacity [W] 1527224.44000
470 Chiller:Electric:ReformulatedEIR COOLSYS1 CHILLER2 Design Size Reference Condenser Water Flow Rate [m3/s] 7.55767E-002
471 PlantLoop SINGLE WATER PLANT LOOP Maximum Loop Flow Rate [m3/s] 1.34175E-002
472 PlantLoop SINGLE WATER PLANT LOOP Plant Loop Volume [m3] 1.61010
473 Pump:ConstantSpeed PLANT CIRC PUMP Design Flow Rate [m3/s] 1.34175E-002
474 Pump:ConstantSpeed PLANT CIRC PUMP Design Power Consumption [W] 3422.12915
475 FluidCooler:TwoSpeed CENTRAL TOWER Design Water Flow Rate [m3/s] 1.34175E-002
476 FluidCooler:TwoSpeed CENTRAL TOWER Air Flow Rate at High Fan Speed [m3/s] 139666.46671
477 FluidCooler:TwoSpeed CENTRAL TOWER Fluid cooler UA value at high fan speed based on nominal capacity input [W/K] 58790.17342
478 FluidCooler:TwoSpeed CENTRAL TOWER Air Flow Rate at Low Fan Speed [m3/s] 69833.23335
479 FluidCooler:TwoSpeed CENTRAL TOWER Fan Power at Low Fan Speed [W] 7879.72339
480 FluidCooler:TwoSpeed CENTRAL TOWER U-factor Times Area Value at Low Fan Speed [W/C] 21366.70827
481 Boiler:HotWater CENTRAL BOILER Design Size Nominal Capacity [W] 552685.27210
482 Boiler:HotWater CENTRAL BOILER User-Specified Nominal Capacity [W] 542032.73000
483 Boiler:HotWater CENTRAL BOILER Design Size Design Water Flow Rate [m3/s] 1.34175E-002
484 PlantLoop SWHSYS1 Maximum Loop Flow Rate [m3/s] 4.40000E-004
485 PlantLoop SWHSYS1 Plant Loop Volume [m3] 5.28000E-002
486 Pump:ConstantSpeed SWHSYS1 PUMP Design Flow Rate [m3/s] 4.40000E-004
487 Pump:ConstantSpeed SWHSYS1 PUMP Design Power Consumption [W] 56.20530
488 WaterHeater:Mixed SWHSYS1 WATER HEATER Use Side Design Flow Rate [m3/s] 4.40000E-004
489 CondenserLoop TOWERWATERSYS Maximum Loop Flow Rate [m3/s] 0.15115
490 CondenserLoop TOWERWATERSYS Condenser Loop Volume [m3] 18.13840
491 HeaderedPumps:VariableSpeed TOWERWATERSYS PUMP Design Flow Rate [m3/s] 0.15115
492 HeaderedPumps:VariableSpeed TOWERWATERSYS PUMP Design Power Consumption [W] 37422.22632
493 CoolingTower:VariableSpeed TOWERWATERSYS COOLTOWER 1 Design Air Flow Rate [m3/s] 58.13244
494 CoolingTower:VariableSpeed TOWERWATERSYS COOLTOWER 1 Nominal Capacity [W] 1812006.77778
495 CoolingTower:VariableSpeed TOWERWATERSYS COOLTOWER 1 Air Flow Rate in free convection regime [m3/s] 11.62649
496 CoolingTower:VariableSpeed TOWERWATERSYS COOLTOWER 1 Tower capacity in free convection regime at design conditions [W] 226500.84722
497 CoolingTower:VariableSpeed TOWERWATERSYS COOLTOWER 2 Design Air Flow Rate [m3/s] 58.13244
498 CoolingTower:VariableSpeed TOWERWATERSYS COOLTOWER 2 Nominal Capacity [W] 1812006.77778
499 CoolingTower:VariableSpeed TOWERWATERSYS COOLTOWER 2 Air Flow Rate in free convection regime [m3/s] 11.62649
500 CoolingTower:VariableSpeed TOWERWATERSYS COOLTOWER 2 Tower capacity in free convection regime at design conditions [W] 226500.84722
501 PlantEquipmentOperation:ComponentSetPoint WSHPPLANT OPERATION SCHEME Design Water Flow Rate [m3/s] Equipment # 47 7.85000E-002
502 PlantEquipmentOperation:ComponentSetPoint WSHPPLANT OPERATION SCHEME Design Water Flow Rate [m3/s] Equipment # 47 7.85000E-002


Water Heating Coil Capacity Information

Component Type Name Nominal Total Capacity {W}
1 Coil:Heating:Water CORE_BOTTOM VAV BOX REHEAT COIL 18841.58
2 Coil:Heating:Water CORE_MID VAV BOX REHEAT COIL 475897.95
3 Coil:Heating:Water CORE_TOP VAV BOX REHEAT COIL 85822.05
4 Coil:Heating:Water PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL 15738.62
5 Coil:Heating:Water PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL 10689.89
6 Coil:Heating:Water PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL 17225.24
7 Coil:Heating:Water PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL 9157.63
8 Coil:Heating:Water PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL 266381.97
9 Coil:Heating:Water PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL 174602.07
10 Coil:Heating:Water PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL 263066.56
11 Coil:Heating:Water PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL 170487.24
12 Coil:Heating:Water PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL 33240.44
13 Coil:Heating:Water PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL 21730.82
14 Coil:Heating:Water PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL 32885.71
15 Coil:Heating:Water PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL 21487.73
16 Coil:Heating:Water VAV_BOT WITH REHEAT HEATING COIL 53835.22
17 Coil:Heating:Water VAV_MID WITH REHEAT HEATING COIL 512152.08
18 Coil:Heating:Water VAV_TOP WITH REHEAT HEATING COIL 51603.64
19 Coil:Heating:Water CAV_BAS HEATING COIL 237476.32


Water Cooling Coil Capacity Information

Component Type Name Nominal Total Capacity {W} Nominal Sensible Capacity {W} Nominal Latent Capacity {W} Nominal Sensible Heat Ratio Nominal Coil UA Value {W/C} Nominal Coil Surface Area {m2}
1 Coil:Cooling:Water VAV_BOT WITH REHEAT COOLING COIL 268186.13 184453.65 83732.48 0.69 27653.98 280.48
2 Coil:Cooling:Water VAV_MID WITH REHEAT COOLING COIL 2575166.49 1761486.35 813680.14 0.68 267330.97 2711.42
3 Coil:Cooling:Water VAV_TOP WITH REHEAT COOLING COIL 274476.69 188952.96 85523.73 0.69 28308.92 287.12
4 Coil:Cooling:Water CAV_BAS COOLING COIL 144069.09 101074.35 42994.75 0.70 14644.17 148.53


Chiller Standard Rating Information

Component Type Component Name IPLV in SI Units {W/W} IPLV in IP Units {Btu/W-h}
1 Chiller:Electric:ReformulatedEIR COOLSYS1 CHILLER1 6.84 23.33
2 Chiller:Electric:ReformulatedEIR COOLSYS1 CHILLER2 6.84 23.33


Zone Surfaces

Zone Name # Surfaces
1 BASEMENT 10
2 CORE_BOTTOM 8
3 CORE_MID 7
4 CORE_TOP 7
5 PERIMETER_BOT_ZN_3 18
6 PERIMETER_BOT_ZN_2 12
7 PERIMETER_BOT_ZN_1 18
8 PERIMETER_BOT_ZN_4 12
9 PERIMETER_MID_ZN_3 9
10 PERIMETER_MID_ZN_2 8
11 PERIMETER_MID_ZN_1 9
12 PERIMETER_MID_ZN_4 8
13 PERIMETER_TOP_ZN_3 9
14 PERIMETER_TOP_ZN_2 8
15 PERIMETER_TOP_ZN_1 9
16 PERIMETER_TOP_ZN_4 8
17 GROUNDFLOOR_PLENUM 11
18 MIDFLOOR_PLENUM 11
19 TOPFLOOR_PLENUM 11
20 DATACENTER_BOT_ZN_6 6
21 DATACENTER_MID_ZN_6 6
22 DATACENTER_TOP_ZN_6 6
23 DATACENTER_BASEMENT_ZN_6 10


HeatTransfer Surface

Surface Name Surface Class Base Surface Heat Transfer Algorithm Construction Nominal U (w/o film coefs) {W/m2-K} Nominal U (with film coefs) {W/m2-K} Solar Diffusing Area (Net) {m2} Area (Gross) {m2} Area (Sunlit Calc) {m2} Azimuth {deg} Tilt {deg} ~Width {m} ~Height {m} Reveal {m} ExtBoundCondition ExtConvCoeffCalc IntConvCoeffCalc SunExposure WindExposure ViewFactorToGround ViewFactorToSky ViewFactorToGround-IR ViewFactorToSky-IR #Sides
1 BASEMENT_WALL_EAST Wall   CTF - ConductionTransferFunction BASEMENT_WALL_EAST_CFACTOR 0.419 0.394   118.87 118.87 118.87 90.00 90.00 48.74 2.44 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
2 BASEMENT_WALL_SOUTH Wall   CTF - ConductionTransferFunction BASEMENT_WALL_SOUTH_CFACTOR 0.419 0.394   139.09 139.09 139.09 180.00 90.00 57.03 2.44 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
3 BASEMENT_WALL_NORTH Wall   CTF - ConductionTransferFunction BASEMENT_WALL_NORTH_CFACTOR 0.419 0.394   139.09 139.09 139.09 0.00 90.00 57.03 2.44 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
4 BASEMENT_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   118.87 118.87 118.87 270.00 90.00 48.74 2.44 0.00 DATACENTER_BASEMENT_ZN_6_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
5 BASEMENT_FLOOR Floor   CTF - ConductionTransferFunction EXT_SLAB_8IN_WITH_CARPET 3.285 1.827   2779.43 2779.43 2779.43 0.00 180.00 57.03 48.74 0.00 BASEMENT_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.00 1.00 0.00 4
6 PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   201.98 201.98 201.98 225.00 0.00 6.47 39.59 0.00 PERIMETER_BOT_ZN_2_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
7 PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   250.34 250.34 250.34 180.00 0.00 57.03 4.57 0.00 PERIMETER_BOT_ZN_1_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
8 CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   2076.77 2076.77 2076.77 180.00 0.00 52.45 39.59 0.00 CORE_BOT_ZN_5_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
9 PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   250.34 250.34 250.34 180.00 0.00 52.45 4.57 0.00 PERIMETER_BOT_ZN_3_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
10 BASEMENT_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   7126.21 7126.21 7126.21 0.00 90.00 7126.21 1.00 0.00 BASEMENT_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
11 CORE_BOT_ZN_5_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   173.00 173.00 173.00 180.00 90.00 63.05 2.74 0.00 CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
12 CORE_BOT_ZN_5_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 270.00 90.00 39.59 2.74 0.00 DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
13 CORE_BOT_ZN_5_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   173.00 173.00 173.00 0.00 90.00 63.05 2.74 0.00 CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
14 CORE_BOT_ZN_5_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 90.00 90.00 39.59 2.74 0.00 CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
15 DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   419.30 419.30 419.30 0.00 180.00 10.59 39.59 0.00 DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.00 1.00 0.00 4
16 CORE_BOT_ZN_5_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   2076.82 2076.82 2076.82 0.00 180.00 52.46 39.59 0.00 CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.00 1.00 0.00 4
17 CORE_BOT_ZN_5_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   2496.12 2496.12 2496.12 180.00 0.00 63.05 39.59 0.00 iz-CORE_BOT_ZN_5_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
18 CORE_BOTTOM_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   5064.65 5064.65 5064.65 0.00 90.00 5064.65 1.00 0.00 CORE_BOTTOM_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
19 CORE_MID_ZN_5_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   173.00 173.00 173.00 180.00 90.00 63.05 2.74 0.00 CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
20 CORE_MID_ZN_5_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 270.00 90.00 39.59 2.74 0.00 DATACENTER_MID_ZN_6_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
21 CORE_MID_ZN_5_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   173.00 173.00 173.00 0.00 90.00 63.05 2.74 0.00 CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
22 CORE_MID_ZN_5_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 90.00 90.00 39.59 2.74 0.00 CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
23 CORE_MID_ZN_5_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   2496.12 2496.12 2496.12 0.00 180.00 63.05 39.59 0.00 CORE_MID_ZN_5_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
24 CORE_MID_ZN_5_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   2496.12 2496.12 2496.12 180.00 0.00 63.05 39.59 0.00 iz-CORE_MID_ZN_5_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
25 CORE_MID_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   5064.65 5064.65 5064.65 0.00 90.00 5064.65 1.00 0.00 CORE_MID_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
26 CORE_TOP_ZN_5_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   173.00 173.00 173.00 180.00 90.00 63.05 2.74 0.00 CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
27 CORE_TOP_ZN_5_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 270.00 90.00 39.59 2.74 0.00 DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
28 CORE_TOP_ZN_5_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   173.00 173.00 173.00 0.00 90.00 63.05 2.74 0.00 CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
29 CORE_TOP_ZN_5_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 90.00 90.00 39.59 2.74 0.00 CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
30 CORE_TOP_ZN_5_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   2496.12 2496.12 2496.12 0.00 180.00 63.05 39.59 0.00 CORE_TOP_ZN_5_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
31 CORE_TOP_ZN_5_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   2496.12 2496.12 2496.12 180.00 0.00 63.05 39.59 0.00 iz-CORE_TOP_ZN_5_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
32 CORE_TOP_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   5064.65 5064.65 5064.65 0.00 90.00 5064.65 1.00 0.00 CORE_TOP_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
33 PERIMETER_BOT_ZN_3_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 1.075 0.926   76.91 200.61 76.91 0.00 90.00 73.11 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
34 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 Window PERIMETER_BOT_ZN_3_WALL_NORTH Window5 Detailed Fenestration WINDOW_U_0.42_SHGC_NORTH_0.4 N/A 2.387 No 23.18 23.18 23.18 0.00 90.00 13.65 1.70 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
35 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 Window PERIMETER_BOT_ZN_3_WALL_NORTH Window5 Detailed Fenestration WINDOW_U_0.42_SHGC_NORTH_0.4 N/A 2.387 No 23.18 23.18 23.18 0.00 90.00 13.65 1.70 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
36 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 Window PERIMETER_BOT_ZN_3_WALL_NORTH Window5 Detailed Fenestration WINDOW_U_0.42_SHGC_NORTH_0.4 N/A 2.387 No 23.18 23.18 23.18 0.00 90.00 13.65 1.70 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
37 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 Window PERIMETER_BOT_ZN_3_WALL_NORTH Window5 Detailed Fenestration WINDOW_U_0.42_SHGC_NORTH_0.4 N/A 2.387 No 23.18 23.18 23.18 0.00 90.00 13.65 1.70 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
38 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 Window PERIMETER_BOT_ZN_3_WALL_NORTH Window5 Detailed Fenestration WINDOW_U_0.42_SHGC_NORTH_0.4 N/A 2.387 No 23.18 23.18 23.18 0.00 90.00 13.65 1.70 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
39 PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 Door PERIMETER_BOT_ZN_3_WALL_NORTH CTF - ConductionTransferFunction SWINGING DOOR_CON 2.839 2.839   1.95 1.95 1.95 0.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
40 PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 Door PERIMETER_BOT_ZN_3_WALL_NORTH CTF - ConductionTransferFunction SWINGING DOOR_CON 2.839 2.839   1.95 1.95 1.95 0.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
41 PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 Door PERIMETER_BOT_ZN_3_WALL_NORTH CTF - ConductionTransferFunction SWINGING DOOR_CON 2.839 2.839   1.95 1.95 1.95 0.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
42 PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 Door PERIMETER_BOT_ZN_3_WALL_NORTH CTF - ConductionTransferFunction SWINGING DOOR_CON 2.839 2.839   1.95 1.95 1.95 0.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
43 PERIMETER_BOT_ZN_3_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 225.00 90.00 6.47 2.74 0.00 PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
44 CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   173.00 173.00 173.00 180.00 90.00 63.05 2.74 0.00 CORE_BOT_ZN_5_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
45 PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 135.00 90.00 6.47 2.74 0.00 PERIMETER_BOT_ZN_2_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
46 DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   2.51 2.51 2.51 180.00 90.00 0.91 2.74 0.00 DATACENTER_BOT_ZN_6_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
47 PERIMETER_BOT_ZN_3_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   250.34 250.34 250.34 0.00 180.00 52.46 6.47 0.00 PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
48 DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   63.07 63.07 63.07 0.00 180.00 11.51 4.57 0.00 DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.00 1.00 0.00 4
49 PERIMETER_BOT_ZN_3_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   313.41 313.41 313.41 180.00 0.00 63.96 6.47 0.00 iz-PERIMETER_BOT_ZN_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
50 PERIMETER_BOT_ZN_3_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   626.83 626.83 626.83 0.00 90.00 626.83 1.00 0.00 PERIMETER_BOT_ZN_3_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
51 PERIMETER_BOT_ZN_2_WALL_EAST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 1.075 0.926   52.57 133.74 52.57 90.00 90.00 48.74 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
52 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 Window PERIMETER_BOT_ZN_2_WALL_EAST Window5 Detailed Fenestration WINDOW_U_0.42_SHGC_EAST_0.4 N/A 2.387 No 25.75 25.75 25.75 90.00 90.00 15.43 1.67 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
53 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 Window PERIMETER_BOT_ZN_2_WALL_EAST Window5 Detailed Fenestration WINDOW_U_0.42_SHGC_EAST_0.4 N/A 2.387 No 25.75 25.75 25.75 90.00 90.00 15.43 1.67 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
54 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 Window PERIMETER_BOT_ZN_2_WALL_EAST Window5 Detailed Fenestration WINDOW_U_0.42_SHGC_EAST_0.4 N/A 2.387 No 25.75 25.75 25.75 90.00 90.00 15.43 1.67 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
55 PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 Door PERIMETER_BOT_ZN_2_WALL_EAST CTF - ConductionTransferFunction SWINGING DOOR_CON 2.839 2.839   1.95 1.95 1.95 90.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
56 PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 Door PERIMETER_BOT_ZN_2_WALL_EAST CTF - ConductionTransferFunction SWINGING DOOR_CON 2.839 2.839   1.95 1.95 1.95 90.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
57 PERIMETER_BOT_ZN_2_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 315.00 90.00 6.47 2.74 0.00 PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
58 CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 270.00 90.00 39.59 2.74 0.00 CORE_BOT_ZN_5_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
59 PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 225.00 90.00 6.47 2.74 0.00 PERIMETER_BOT_ZN_1_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
60 PERIMETER_BOT_ZN_2_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   201.98 201.98 201.98 45.00 180.00 6.47 48.74 0.00 PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
61 PERIMETER_BOT_ZN_2_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   201.98 201.98 201.98 225.00 0.00 6.47 39.59 0.00 iz-PERIMETER_BOT_ZN_2_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
62 PERIMETER_BOT_ZN_2_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   403.95 403.95 403.95 0.00 90.00 403.95 1.00 0.00 PERIMETER_BOT_ZN_2_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
63 PERIMETER_BOT_ZN_1_WALL_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 1.075 0.926   76.91 200.61 76.91 180.00 90.00 73.11 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
64 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 Window PERIMETER_BOT_ZN_1_WALL_SOUTH Window5 Detailed Fenestration WINDOW_U_0.42_SHGC_SOUTH_0.4 N/A 2.387 No 23.18 23.18 23.18 180.00 90.00 13.65 1.70 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
65 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 Window PERIMETER_BOT_ZN_1_WALL_SOUTH Window5 Detailed Fenestration WINDOW_U_0.42_SHGC_SOUTH_0.4 N/A 2.387 No 23.18 23.18 23.18 180.00 90.00 13.65 1.70 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
66 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 Window PERIMETER_BOT_ZN_1_WALL_SOUTH Window5 Detailed Fenestration WINDOW_U_0.42_SHGC_SOUTH_0.4 N/A 2.387 No 23.18 23.18 23.18 180.00 90.00 13.65 1.70 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
67 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 Window PERIMETER_BOT_ZN_1_WALL_SOUTH Window5 Detailed Fenestration WINDOW_U_0.42_SHGC_SOUTH_0.4 N/A 2.387 No 23.18 23.18 23.18 180.00 90.00 13.65 1.70 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
68 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 Window PERIMETER_BOT_ZN_1_WALL_SOUTH Window5 Detailed Fenestration WINDOW_U_0.42_SHGC_SOUTH_0.4 N/A 2.387 No 23.18 23.18 23.18 180.00 90.00 13.65 1.70 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
69 PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 Door PERIMETER_BOT_ZN_1_WALL_SOUTH CTF - ConductionTransferFunction SWINGING DOOR_CON 2.839 2.839   1.95 1.95 1.95 180.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
70 PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 Door PERIMETER_BOT_ZN_1_WALL_SOUTH CTF - ConductionTransferFunction SWINGING DOOR_CON 2.839 2.839   1.95 1.95 1.95 180.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
71 PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 Door PERIMETER_BOT_ZN_1_WALL_SOUTH CTF - ConductionTransferFunction SWINGING DOOR_CON 2.839 2.839   1.95 1.95 1.95 180.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
72 PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 Door PERIMETER_BOT_ZN_1_WALL_SOUTH CTF - ConductionTransferFunction SWINGING DOOR_CON 2.839 2.839   1.95 1.95 1.95 180.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
73 PERIMETER_BOT_ZN_1_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 45.00 90.00 6.47 2.74 0.00 PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
74 DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   2.51 2.51 2.51 0.00 90.00 0.91 2.74 0.00 DATACENTER_BOT_ZN_6_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
75 PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 315.00 90.00 6.47 2.74 0.00 PERIMETER_BOT_ZN_4_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
76 CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   173.00 173.00 173.00 0.00 90.00 63.05 2.74 0.00 CORE_BOT_ZN_5_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
77 DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   63.07 63.07 63.07 0.00 180.00 16.08 4.57 0.00 DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.00 1.00 0.00 4
78 PERIMETER_BOT_ZN_1_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   250.35 250.35 250.35 0.00 180.00 57.03 6.47 0.00 PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.00 1.00 0.00 4
79 PERIMETER_BOT_ZN_1_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   313.42 313.42 313.42 180.00 0.00 73.11 6.47 0.00 iz-PERIMETER_BOT_ZN_1_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
80 PERIMETER_BOT_ZN_1_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   626.84 626.84 626.84 0.00 90.00 626.84 1.00 0.00 PERIMETER_BOT_ZN_1_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
81 PERIMETER_BOT_ZN_4_WALL_WEST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 1.075 0.926   52.57 133.74 52.57 270.00 90.00 48.74 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
82 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 Window PERIMETER_BOT_ZN_4_WALL_WEST Window5 Detailed Fenestration WINDOW_U_0.42_SHGC_WEST_0.4 N/A 2.387 No 25.75 25.75 25.75 270.00 90.00 15.43 1.67 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
83 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 Window PERIMETER_BOT_ZN_4_WALL_WEST Window5 Detailed Fenestration WINDOW_U_0.42_SHGC_WEST_0.4 N/A 2.387 No 25.75 25.75 25.75 270.00 90.00 15.43 1.67 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
84 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 Window PERIMETER_BOT_ZN_4_WALL_WEST Window5 Detailed Fenestration WINDOW_U_0.42_SHGC_WEST_0.4 N/A 2.387 No 25.75 25.75 25.75 270.00 90.00 15.43 1.67 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
85 PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 Door PERIMETER_BOT_ZN_4_WALL_WEST CTF - ConductionTransferFunction SWINGING DOOR_CON 2.839 2.839   1.95 1.95 1.95 270.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
86 PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 Door PERIMETER_BOT_ZN_4_WALL_WEST CTF - ConductionTransferFunction SWINGING DOOR_CON 2.839 2.839   1.95 1.95 1.95 270.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
87 PERIMETER_BOT_ZN_4_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 135.00 90.00 6.47 2.74 0.00 PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
88 DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 90.00 90.00 39.59 2.74 0.00 DATACENTER_BOT_ZN_6_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
89 PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 45.00 90.00 6.47 2.74 0.00 PERIMETER_BOT_ZN_3_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
90 PERIMETER_BOT_ZN_4_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   201.98 201.98 201.98 315.00 180.00 6.47 39.59 0.00 PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.00 1.00 0.00 4
91 PERIMETER_BOT_ZN_4_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   201.98 201.98 201.98 135.00 0.00 6.47 48.74 0.00 iz-PERIMETER_BOT_ZN_4_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
92 PERIMETER_BOT_ZN_4_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   403.95 403.95 403.95 0.00 90.00 403.95 1.00 0.00 PERIMETER_BOT_ZN_4_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
93 PERIMETER_MID_ZN_3_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 1.028 0.891   84.71 200.61 84.71 0.00 90.00 73.11 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
94 PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW Window PERIMETER_MID_ZN_3_WALL_NORTH Window5 Detailed Fenestration WINDOW_U_0.42_SHGC_NORTH_0.4 N/A 2.387 No 115.90 115.90 115.90 0.00 90.00 73.11 1.59 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
95 PERIMETER_MID_ZN_3_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 225.00 90.00 6.47 2.74 0.00 PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
96 CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   173.00 173.00 173.00 180.00 90.00 63.05 2.74 0.00 CORE_MID_ZN_5_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
97 PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 135.00 90.00 6.47 2.74 0.00 PERIMETER_MID_ZN_2_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
98 DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   2.51 2.51 2.51 180.00 90.00 0.91 2.74 0.00 DATACENTER_MID_ZN_6_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
99 PERIMETER_MID_ZN_3_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   313.41 313.41 313.41 0.00 180.00 63.96 6.47 0.00 PERIMETER_MID_ZN_3_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
100 PERIMETER_MID_ZN_3_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   313.41 313.41 313.41 180.00 0.00 63.96 6.47 0.00 iz-PERIMETER_MID_ZN_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
101 PERIMETER_MID_ZN_3_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   626.83 626.83 626.83 0.00 90.00 626.83 1.00 0.00 PERIMETER_MID_ZN_3_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
102 PERIMETER_MID_ZN_2_WALL_EAST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 1.028 0.891   56.47 133.74 56.47 90.00 90.00 48.74 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
103 PERIMETER_MID_ZN_2_WALL_EAST_WINDOW Window PERIMETER_MID_ZN_2_WALL_EAST Window5 Detailed Fenestration WINDOW_U_0.42_SHGC_EAST_0.4 N/A 2.387 No 77.26 77.26 77.26 90.00 90.00 48.74 1.59 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
104 PERIMETER_MID_ZN_2_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 315.00 90.00 6.47 2.74 0.00 PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
105 CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 270.00 90.00 39.59 2.74 0.00 CORE_MID_ZN_5_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
106 PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 225.00 90.00 6.47 2.74 0.00 PERIMETER_MID_ZN_1_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
107 PERIMETER_MID_ZN_2_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   201.98 201.98 201.98 45.00 180.00 6.47 48.74 0.00 PERIMETER_MID_ZN_2_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
108 PERIMETER_MID_ZN_2_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   201.98 201.98 201.98 225.00 0.00 6.47 39.59 0.00 iz-PERIMETER_MID_ZN_2_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
109 PERIMETER_MID_ZN_2_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   403.95 403.95 403.95 0.00 90.00 403.95 1.00 0.00 PERIMETER_MID_ZN_2_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
110 PERIMETER_MID_ZN_1_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 45.00 90.00 6.47 2.74 0.00 PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
111 PERIMETER_MID_ZN_1_WALL_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 1.028 0.891   84.71 200.61 84.71 180.00 90.00 73.11 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
112 PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW Window PERIMETER_MID_ZN_1_WALL_SOUTH Window5 Detailed Fenestration WINDOW_U_0.42_SHGC_SOUTH_0.4 N/A 2.387 No 115.90 115.90 115.90 180.00 90.00 73.11 1.59 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
113 DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   2.51 2.51 2.51 0.00 90.00 0.91 2.74 0.00 DATACENTER_MID_ZN_6_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
114 PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 315.00 90.00 6.47 2.74 0.00 PERIMETER_MID_ZN_4_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
115 CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   173.00 173.00 173.00 0.00 90.00 63.05 2.74 0.00 CORE_MID_ZN_5_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
116 PERIMETER_MID_ZN_1_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   313.42 313.42 313.42 0.00 180.00 73.11 6.47 0.00 PERIMETER_MID_ZN_1_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
117 PERIMETER_MID_ZN_1_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   313.42 313.42 313.42 180.00 0.00 73.11 6.47 0.00 iz-PERIMETER_MID_ZN_1_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
118 PERIMETER_MID_ZN_1_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   626.84 626.84 626.84 0.00 90.00 626.84 1.00 0.00 PERIMETER_MID_ZN_1_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
119 PERIMETER_MID_ZN_4_WALL_WEST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 1.028 0.891   56.47 133.74 56.47 270.00 90.00 48.74 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
120 PERIMETER_MID_ZN_4_WALL_WEST_WINDOW Window PERIMETER_MID_ZN_4_WALL_WEST Window5 Detailed Fenestration WINDOW_U_0.42_SHGC_WEST_0.4 N/A 2.387 No 77.26 77.26 77.26 270.00 90.00 48.74 1.59 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
121 PERIMETER_MID_ZN_4_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 135.00 90.00 6.47 2.74 0.00 PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
122 DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 90.00 90.00 39.59 2.74 0.00 DATACENTER_MID_ZN_6_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
123 PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 45.00 90.00 6.47 2.74 0.00 PERIMETER_MID_ZN_3_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
124 PERIMETER_MID_ZN_4_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   201.98 201.98 201.98 315.00 180.00 6.47 39.59 0.00 PERIMETER_MID_ZN_4_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
125 PERIMETER_MID_ZN_4_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   201.98 201.98 201.98 135.00 0.00 6.47 48.74 0.00 iz-PERIMETER_MID_ZN_4_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
126 PERIMETER_MID_ZN_4_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   403.95 403.95 403.95 0.00 90.00 403.95 1.00 0.00 PERIMETER_MID_ZN_4_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
127 PERIMETER_TOP_ZN_3_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.266 1.064   84.71 200.61 84.71 0.00 90.00 73.11 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
128 PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW Window PERIMETER_TOP_ZN_3_WALL_NORTH Window5 Detailed Fenestration WINDOW_U_0.42_SHGC_NORTH_0.4 N/A 2.387 No 115.90 115.90 115.90 0.00 90.00 73.11 1.59 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
129 PERIMETER_TOP_ZN_3_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 225.00 90.00 6.47 2.74 0.00 PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
130 CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   173.00 173.00 173.00 180.00 90.00 63.05 2.74 0.00 CORE_TOP_ZN_5_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
131 PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 135.00 90.00 6.47 2.74 0.00 PERIMETER_TOP_ZN_2_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
132 DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   2.51 2.51 2.51 180.00 90.00 0.91 2.74 0.00 DATACENTER_TOP_ZN_6_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
133 PERIMETER_TOP_ZN_3_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   313.41 313.41 313.41 0.00 180.00 63.96 6.47 0.00 PERIMETER_TOP_ZN_3_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
134 PERIMETER_TOP_ZN_3_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   313.41 313.41 313.41 180.00 0.00 63.96 6.47 0.00 iz-PERIMETER_TOP_ZN_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
135 PERIMETER_TOP_ZN_3_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   626.83 626.83 626.83 0.00 90.00 626.83 1.00 0.00 PERIMETER_TOP_ZN_3_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
136 PERIMETER_TOP_ZN_2_WALL_EAST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.266 1.064   56.47 133.74 56.47 90.00 90.00 48.74 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
137 PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW Window PERIMETER_TOP_ZN_2_WALL_EAST Window5 Detailed Fenestration WINDOW_U_0.42_SHGC_EAST_0.4 N/A 2.387 No 77.26 77.26 77.26 90.00 90.00 48.74 1.59 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
138 PERIMETER_TOP_ZN_2_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 315.00 90.00 6.47 2.74 0.00 PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
139 CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 270.00 90.00 39.59 2.74 0.00 CORE_TOP_ZN_5_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
140 INT-PER3S-NE-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 225.00 90.00 6.47 2.74 0.00 INT-PER3S-NE Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
141 PERIMETER_TOP_ZN_2_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   201.98 201.98 201.98 45.00 180.00 6.47 48.74 0.00 PERIMETER_TOP_ZN_2_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
142 PERIMETER_TOP_ZN_2_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   201.98 201.98 201.98 225.00 0.00 6.47 39.59 0.00 iz-PERIMETER_TOP_ZN_2_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
143 PERIMETER_TOP_ZN_2_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   403.95 403.95 403.95 0.00 90.00 403.95 1.00 0.00 PERIMETER_TOP_ZN_2_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
144 PERIMETER_TOP_ZN_1_WALL_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.266 1.064   84.71 200.61 84.71 180.00 90.00 73.11 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
145 PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW Window PERIMETER_TOP_ZN_1_WALL_SOUTH Window5 Detailed Fenestration WINDOW_U_0.42_SHGC_SOUTH_0.4 N/A 2.387 No 115.90 115.90 115.90 180.00 90.00 73.11 1.59 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
146 INT-PER3S-NE Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 45.00 90.00 6.47 2.74 0.00 INT-PER3S-NE-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
147 DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   2.51 2.51 2.51 0.00 90.00 0.91 2.74 0.00 DATACENTER_TOP_ZN_6_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
148 PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 315.00 90.00 6.47 2.74 0.00 PERIMETER_TOP_ZN_4_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
149 CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   173.00 173.00 173.00 0.00 90.00 63.05 2.74 0.00 CORE_TOP_ZN_5_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
150 PERIMETER_TOP_ZN_1_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   313.42 313.42 313.42 0.00 180.00 73.11 6.47 0.00 PERIMETER_TOP_ZN_1_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
151 PERIMETER_TOP_ZN_1_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   313.42 313.42 313.42 180.00 0.00 73.11 6.47 0.00 iz-PERIMETER_TOP_ZN_1_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
152 PERIMETER_TOP_ZN_1_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   626.84 626.84 626.84 0.00 90.00 626.84 1.00 0.00 PERIMETER_TOP_ZN_1_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
153 PERIMETER_TOP_ZN_4_WALL_WEST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.266 1.064   56.47 133.74 56.47 270.00 90.00 48.74 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
154 PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW Window PERIMETER_TOP_ZN_4_WALL_WEST Window5 Detailed Fenestration WINDOW_U_0.42_SHGC_WEST_0.4 N/A 2.387 No 77.26 77.26 77.26 270.00 90.00 48.74 1.59 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
155 PERIMETER_TOP_ZN_4_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 135.00 90.00 6.47 2.74 0.00 PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
156 DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 90.00 90.00 39.59 2.74 0.00 DATACENTER_TOP_ZN_6_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
157 PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 45.00 90.00 6.47 2.74 0.00 PERIMETER_TOP_ZN_3_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
158 PERIMETER_TOP_ZN_4_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   201.98 201.98 201.98 315.00 180.00 6.47 39.59 0.00 PERIMETER_TOP_ZN_4_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
159 PERIMETER_TOP_ZN_4_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   201.98 201.98 201.98 135.00 0.00 6.47 48.74 0.00 iz-PERIMETER_TOP_ZN_4_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
160 PERIMETER_TOP_ZN_4_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   403.95 403.95 403.95 0.00 90.00 403.95 1.00 0.00 PERIMETER_TOP_ZN_4_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
161 GROUNDFLOOR_PLENUM_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 1.075 0.926   89.13 89.13 89.13 0.00 90.00 73.11 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
162 GROUNDFLOOR_PLENUM_WEST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 1.075 0.926   59.42 59.42 59.42 270.00 90.00 48.74 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
163 GROUNDFLOOR_PLENUM_WALL_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 1.075 0.926   89.13 89.13 89.13 180.00 90.00 73.11 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
164 GROUNDFLOOR_PLENUM_WALL_EAST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 1.075 0.926   59.42 59.42 59.42 90.00 90.00 48.74 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
165 iz-CORE_BOT_ZN_5_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   2496.12 2496.12 2496.12 0.00 180.00 63.05 39.59 0.00 CORE_BOT_ZN_5_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
166 iz-PERIMETER_BOT_ZN_3_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   313.41 313.41 313.41 0.00 180.00 63.96 6.47 0.00 PERIMETER_BOT_ZN_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
167 iz-PERIMETER_BOT_ZN_2_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   201.98 201.98 201.98 45.00 180.00 6.47 48.74 0.00 PERIMETER_BOT_ZN_2_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
168 iz-PERIMETER_BOT_ZN_1_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   313.42 313.42 313.42 0.00 180.00 73.11 6.47 0.00 PERIMETER_BOT_ZN_1_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
169 iz-PERIMETER_BOT_ZN_4_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   201.98 201.98 201.98 315.00 180.00 6.47 39.59 0.00 PERIMETER_BOT_ZN_4_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
170 iz-DATACENTER_BOT_ZN_6_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   36.20 36.20 36.20 0.00 180.00 0.91 39.59 0.00 DATACENTER_BOT_ZN_6_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
171 GROUNDFLOOR_PLENUM_CEILING Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   3563.11 3563.11 3563.11 180.00 0.00 73.11 48.74 0.00 GROUNDFLOOR_PLENUM_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
172 MIDFLOOR_PLENUM_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 1.028 0.891   89.13 89.13 89.13 0.00 90.00 73.11 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
173 MIDFLOOR_PLENUM_WALL_WEST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 1.028 0.891   59.42 59.42 59.42 270.00 90.00 48.74 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
174 MIDFLOOR_PLENUM_WALL_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 1.028 0.891   89.13 89.13 89.13 180.00 90.00 73.11 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
175 MIDFLOOR_PLENUM_WALL_EAST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 1.028 0.891   59.42 59.42 59.42 90.00 90.00 48.74 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
176 iz-CORE_MID_ZN_5_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   2496.12 2496.12 2496.12 0.00 180.00 63.05 39.59 0.00 CORE_MID_ZN_5_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
177 iz-PERIMETER_MID_ZN_3_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   313.41 313.41 313.41 0.00 180.00 63.96 6.47 0.00 PERIMETER_MID_ZN_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
178 iz-PERIMETER_MID_ZN_2_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   201.98 201.98 201.98 45.00 180.00 6.47 48.74 0.00 PERIMETER_MID_ZN_2_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
179 iz-PERIMETER_MID_ZN_1_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   313.42 313.42 313.42 0.00 180.00 73.11 6.47 0.00 PERIMETER_MID_ZN_1_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
180 iz-PERIMETER_MID_ZN_4_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   201.98 201.98 201.98 315.00 180.00 6.47 39.59 0.00 PERIMETER_MID_ZN_4_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
181 iz-DATACENTER_MID_ZN_6_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   36.20 36.20 36.20 0.00 180.00 0.91 39.59 0.00 DATACENTER_MID_ZN_6_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
182 MIDFLOOR_PLENUM_CEILING Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   3563.11 3563.11 3563.11 180.00 0.00 73.11 48.74 0.00 MIDFLOOR_PLENUM_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
183 TOPFLOOR_PLENUM_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.266 1.064   89.13 89.13 89.13 180.00 90.00 73.11 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
184 TOPFLOOR_PLENUM_WALL_EAST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.266 1.064   59.42 59.42 59.42 90.00 90.00 48.74 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
185 TOPFLOOR_PLENUM_WALL_WEST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.266 1.064   59.42 59.42 59.42 270.00 90.00 48.74 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
186 TOPFLOOR_PLENUM_WALL_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.266 1.064   89.13 89.13 89.13 0.00 90.00 73.11 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
187 iz-CORE_TOP_ZN_5_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   2496.12 2496.12 2496.12 0.00 180.00 63.05 39.59 0.00 CORE_TOP_ZN_5_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
188 iz-PERIMETER_TOP_ZN_3_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   313.41 313.41 313.41 0.00 180.00 63.96 6.47 0.00 PERIMETER_TOP_ZN_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
189 iz-PERIMETER_TOP_ZN_2_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   201.98 201.98 201.98 45.00 180.00 6.47 48.74 0.00 PERIMETER_TOP_ZN_2_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
190 iz-PERIMETER_TOP_ZN_1_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   313.42 313.42 313.42 0.00 180.00 73.11 6.47 0.00 PERIMETER_TOP_ZN_1_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
191 iz-PERIMETER_TOP_ZN_4_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   201.98 201.98 201.98 315.00 180.00 6.47 39.59 0.00 PERIMETER_TOP_ZN_4_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
192 iz-DATACENTER_TOP_ZN_6_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   36.20 36.20 36.20 0.00 180.00 0.91 39.59 0.00 DATACENTER_TOP_ZN_6_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
193 BUILDING_ROOF Roof   CTF - ConductionTransferFunction NONRES_ROOF 0.186 0.180   3563.11 3563.11 3563.11 180.00 0.00 73.11 48.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 4
194 DATACENTER_BOT_ZN_6_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   2.51 2.51 2.51 0.00 90.00 0.91 2.74 0.00 DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
195 DATACENTER_BOT_ZN_6_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   2.51 2.51 2.51 180.00 90.00 0.91 2.74 0.00 DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
196 DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 90.00 90.00 39.59 2.74 0.00 CORE_BOT_ZN_5_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
197 DATACENTER_BOT_ZN_6_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 270.00 90.00 39.59 2.74 0.00 DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
198 DATACENTER_BOT_ZN_6_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   36.20 36.20 36.20 0.00 180.00 0.91 39.59 0.00 DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.00 1.00 0.00 4
199 DATACENTER_BOT_ZN_6_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   36.20 36.20 36.20 180.00 0.00 0.91 39.59 0.00 iz-DATACENTER_BOT_ZN_6_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
200 DATACENTER_MID_ZN_6_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 270.00 90.00 39.59 2.74 0.00 DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
201 DATACENTER_MID_ZN_6_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   2.51 2.51 2.51 180.00 90.00 0.91 2.74 0.00 DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
202 DATACENTER_MID_ZN_6_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 90.00 90.00 39.59 2.74 0.00 CORE_MID_ZN_5_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
203 DATACENTER_MID_ZN_6_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   2.51 2.51 2.51 0.00 90.00 0.91 2.74 0.00 DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
204 DATACENTER_MID_ZN_6_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   36.20 36.20 36.20 0.00 180.00 0.91 39.59 0.00 DATACENTER_MID_ZN_6_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.00 1.00 0.00 4
205 DATACENTER_MID_ZN_6_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   36.20 36.20 36.20 180.00 0.00 0.91 39.59 0.00 iz-DATACENTER_MID_ZN_6_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
206 DATACENTER_TOP_ZN_6_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 90.00 90.00 39.59 2.74 0.00 CORE_TOP_ZN_5_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
207 DATACENTER_TOP_ZN_6_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 270.00 90.00 39.59 2.74 0.00 DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
208 DATACENTER_TOP_ZN_6_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   2.51 2.51 2.51 180.00 90.00 0.91 2.74 0.00 DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
209 DATACENTER_TOP_ZN_6_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   2.51 2.51 2.51 0.00 90.00 0.91 2.74 0.00 DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
210 DATACENTER_TOP_ZN_6_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   36.20 36.20 36.20 0.00 180.00 0.91 39.59 0.00 DATACENTER_TOP_ZN_6_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.00 1.00 0.00 4
211 DATACENTER_TOP_ZN_6_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   36.20 36.20 36.20 180.00 0.00 0.91 39.59 0.00 iz-DATACENTER_TOP_ZN_6_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
212 DATACENTER_BASEMENT_ZN_6_WALL_NORTH Wall   CTF - ConductionTransferFunction DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR 0.419 0.394   39.22 39.22 39.22 0.00 90.00 16.08 2.44 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
213 DATACENTER_BASEMENT_ZN_6_WALL_SOUTH Wall   CTF - ConductionTransferFunction DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR 0.419 0.394   39.22 39.22 39.22 180.00 90.00 16.08 2.44 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
214 DATACENTER_BASEMENT_ZN_6_WALL_WEST Wall   CTF - ConductionTransferFunction DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR 0.419 0.394   118.87 118.87 118.87 270.00 90.00 48.74 2.44 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
215 DATACENTER_BASEMENT_ZN_6_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   118.87 118.87 118.87 90.00 90.00 48.74 2.44 0.00 BASEMENT_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
216 DATACENTER_BASEMENT_ZN_6_FLOOR Floor   CTF - ConductionTransferFunction EXT_SLAB_8IN_WITH_CARPET 3.285 1.827   783.68 783.68 783.68 0.00 180.00 16.08 48.74 0.00 DATACENTER_BASEMENT_ZN_6_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.00 1.00 0.00 4
217 DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   36.20 36.20 36.20 180.00 0.00 0.91 39.59 0.00 DATACENTER_BOT_ZN_6_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
218 DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   419.35 419.35 419.35 180.00 0.00 10.59 39.59 0.00 DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
219 PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   201.98 201.98 201.98 135.00 0.00 6.47 48.74 0.00 PERIMETER_BOT_ZN_4_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
220 DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   63.08 63.08 63.08 180.00 0.00 16.08 6.47 0.00 DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
221 DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   63.07 63.07 63.07 180.00 0.00 11.51 6.47 0.00 DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4


Environment

Environment Name Environment Type Start Date End Date Start DayOfWeek Duration {#days} Source:Start DayOfWeek Use Daylight Saving Use Holidays Apply Weekend Holiday Rule Use Rain Values Use Snow Values Sky Temperature Model
1 RUNPERIOD 1 WeatherFileRunPeriod 01/01/2017 12/31/2017 Sunday 365 Use RunPeriod Specified Day No No No Yes Yes Clark and Allen


Environment:Special Days

Special Day Name Special Day Type Source Start Date Duration {#days}
1 NEW YEARS DAY Holiday InputFile 01/01 1Environment:Special Days


Environment:Daylight Saving

Daylight Saving Indicator Source Start Date End Date
1 Yes InputFile 03/12 11/05


Tabular Report

Style Unit Conversion
1 Commaandhtml commaandhtml


Warmup Convergence Information

Zone Name Environment Type/Name Average Warmup Temperature Difference {deltaC} Std Dev Warmup Temperature Difference {deltaC} Max Temperature Pass/Fail Convergence Min Temperature Pass/Fail Convergence Average Warmup Load Difference {W} Std Dev Warmup Load Difference {W} Heating Load Pass/Fail Convergence Cooling Load Pass/Fail Convergence
1 BASEMENT RunPeriod: RUNPERIOD 1 2.0502332858E-003 1.5106649061E-003 Pass Pass 0.0000000000 0.0000000000 Pass Pass
2 CORE_BOTTOM RunPeriod: RUNPERIOD 1 5.4819744593E-003 6.2793829457E-003 Pass Pass 0.0000000000 0.0000000000 Pass Pass
3 CORE_MID RunPeriod: RUNPERIOD 1 2.2427394940E-002 1.3942131033E-002 Pass Pass 0.4851555726 0.4916712295 Pass Pass
4 CORE_TOP RunPeriod: RUNPERIOD 1 6.8224349798E-002 8.9594937271E-002 Pass Pass 1.9162773145 10.9419735062 Pass Pass
5 PERIMETER_BOT_ZN_3 RunPeriod: RUNPERIOD 1 3.5532505947E-002 2.5374120989E-002 Pass Pass 0.0000000000 0.0000000000 Pass Pass
6 PERIMETER_BOT_ZN_2 RunPeriod: RUNPERIOD 1 7.0946013324E-002 9.0633118368E-002 Pass Pass 0.0000000000 0.0000000000 Pass Pass
7 PERIMETER_BOT_ZN_1 RunPeriod: RUNPERIOD 1 0.1159308160 0.1303249404 Pass Pass 0.0000000000 0.0000000000 Pass Pass
8 PERIMETER_BOT_ZN_4 RunPeriod: RUNPERIOD 1 5.2446844100E-002 4.7196499291E-002 Pass Pass 0.0000000000 0.0000000000 Pass Pass
9 PERIMETER_MID_ZN_3 RunPeriod: RUNPERIOD 1 0.6648806623 0.6197184340 Pass Pass 0.7130336706 0.6181169518 Pass Pass
10 PERIMETER_MID_ZN_2 RunPeriod: RUNPERIOD 1 0.5612507664 0.6477395688 Pass Pass 0.7978847355 0.8060915534 Pass Pass
11 PERIMETER_MID_ZN_1 RunPeriod: RUNPERIOD 1 0.4639223146 0.5421971033 Pass Pass 5.3867249299 56.0096904265 Pass Pass
12 PERIMETER_MID_ZN_4 RunPeriod: RUNPERIOD 1 0.5706336752 0.6064839475 Pass Pass 0.7540863485 0.7357796871 Pass Pass
13 PERIMETER_TOP_ZN_3 RunPeriod: RUNPERIOD 1 0.8569177081 0.7705114977 Pass Pass 0.6791987308 0.5941191079 Pass Pass
14 PERIMETER_TOP_ZN_2 RunPeriod: RUNPERIOD 1 0.7528265192 0.8166152514 Pass Pass 0.7032714080 0.6254072103 Pass Pass
15 PERIMETER_TOP_ZN_1 RunPeriod: RUNPERIOD 1 0.6036151140 0.7175658152 Pass Pass 3.0428838732 24.1918313062 Pass Pass
16 PERIMETER_TOP_ZN_4 RunPeriod: RUNPERIOD 1 0.7693440408 0.8030661093 Pass Pass 0.7185138026 0.6508051496 Pass Pass
17 GROUNDFLOOR_PLENUM RunPeriod: RUNPERIOD 1 1.0391554141E-002 7.0227468347E-003 Pass Pass 0.0000000000 0.0000000000 Pass Pass
18 MIDFLOOR_PLENUM RunPeriod: RUNPERIOD 1 9.2167790481E-002 5.8701523921E-002 Pass Pass 0.4878593072 0.4862872943 Pass Pass
19 TOPFLOOR_PLENUM RunPeriod: RUNPERIOD 1 0.1814227663 0.1349570728 Pass Pass 0.4978443881 0.4942413574 Pass Pass
20 DATACENTER_BOT_ZN_6 RunPeriod: RUNPERIOD 1 3.6330824800E-003 2.1857459724E-002 Pass Pass 0.5140294814 3.0601305421 Pass Pass
21 DATACENTER_MID_ZN_6 RunPeriod: RUNPERIOD 1 1.3791015542E-002 1.1244650792E-002 Pass Pass 5.2927477664E-003 6.5721860593E-003 Pass Pass
22 DATACENTER_TOP_ZN_6 RunPeriod: RUNPERIOD 1 1.8813458972E-002 1.4722877632E-002 Pass Pass 7.0342600313E-003 8.4365582068E-003 Pass Pass
23 DATACENTER_BASEMENT_ZN_6 RunPeriod: RUNPERIOD 1 1.3199864724E-005 2.1525735672E-005 Pass Pass 1.0119359308E-004 1.1353274545E-004 Pass Pass



Table of Contents

Report: Annual Heat Emissions Summary

For: Entire Facility

Timestamp: 2023-10-16 08:43:34

Heat Emission by Components

Envelope Convection Zone Exfiltration Zone Exhaust Air HVAC Relief Air HVAC Reject Heat Total
Heat Emissions [GJ] 6816.44 221.76 0.00 17648.29 23276.99 47963.48



Table of Contents

Report: Climatic Data Summary

For: Entire Facility

Timestamp: 2023-10-16 08:43:34

SizingPeriod:DesignDay

Maximum Dry Bulb [C] Daily Temperature Range [deltaC] Humidity Value Humidity Type Wind Speed [m/s] Wind Direction
NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB -10.70 0.00 -10.70 Wetbulb [C] 7.50 320.00
NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 32.10 7.40 23.10 Wetbulb [C] 5.60 230.00


Monthly Precipitation Summary

Monthly Total Precipitation from .epw [mm] Monthly Total Hours of Rain from .epw Monthly Total Precipitation in Site:Precipitation [mm] Monthly Total Roof Irrigation Depth [mm] Monthly Total Rain Collection Volume [m3]
Jan 172.00 59      
Feb 49.00 37      
Mar 40.00 38      
Apr 70.00 48      
May 70.00 36      
Jun 25.00 15      
Jul 64.00 20      
Aug 2.00 4      
Sep 73.00 32      
Oct 7.00 8      
Nov 88.00 34      
Dec 62.00 39      


Weather Statistics File

Value
None  



Table of Contents

Report: Envelope Summary

For: Entire Facility

Timestamp: 2023-10-16 08:43:34

Opaque Exterior

Construction Reflectance U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Net Area [m2] Azimuth [deg] Tilt [deg] Cardinal Direction
BASEMENT_WALL_EAST BASEMENT_WALL_EAST_CFACTOR 1.00 0.399 0.419 118.87 118.87 90.00 90.00 E
BASEMENT_WALL_SOUTH BASEMENT_WALL_SOUTH_CFACTOR 1.00 0.399 0.419 139.09 139.09 180.00 90.00 S
BASEMENT_WALL_NORTH BASEMENT_WALL_NORTH_CFACTOR 1.00 0.399 0.419 139.09 139.09 0.00 90.00 N
PERIMETER_BOT_ZN_3_WALL_NORTH NONRES_EXT_WALL_GRD 0.30 0.926 1.075 200.61 76.91 0.00 90.00 N
PERIMETER_BOT_ZN_2_WALL_EAST NONRES_EXT_WALL_GRD 0.30 0.926 1.075 133.74 52.57 90.00 90.00 E
PERIMETER_BOT_ZN_1_WALL_SOUTH NONRES_EXT_WALL_GRD 0.30 0.926 1.075 200.61 76.91 180.00 90.00 S
PERIMETER_BOT_ZN_4_WALL_WEST NONRES_EXT_WALL_GRD 0.30 0.926 1.075 133.74 52.57 270.00 90.00 W
PERIMETER_MID_ZN_3_WALL_NORTH NONRES_EXT_WALL_MID 0.30 0.891 1.028 2006.06 847.11 0.00 90.00 N
PERIMETER_MID_ZN_2_WALL_EAST NONRES_EXT_WALL_MID 0.30 0.891 1.028 1337.37 564.74 90.00 90.00 E
PERIMETER_MID_ZN_1_WALL_SOUTH NONRES_EXT_WALL_MID 0.30 0.891 1.028 2006.06 847.11 180.00 90.00 S
PERIMETER_MID_ZN_4_WALL_WEST NONRES_EXT_WALL_MID 0.30 0.891 1.028 1337.37 564.74 270.00 90.00 W
PERIMETER_TOP_ZN_3_WALL_NORTH NONRES_EXT_WALL_TOP 0.30 1.064 1.266 200.61 84.71 0.00 90.00 N
PERIMETER_TOP_ZN_2_WALL_EAST NONRES_EXT_WALL_TOP 0.30 1.064 1.266 133.74 56.47 90.00 90.00 E
PERIMETER_TOP_ZN_1_WALL_SOUTH NONRES_EXT_WALL_TOP 0.30 1.064 1.266 200.61 84.71 180.00 90.00 S
PERIMETER_TOP_ZN_4_WALL_WEST NONRES_EXT_WALL_TOP 0.30 1.064 1.266 133.74 56.47 270.00 90.00 W
GROUNDFLOOR_PLENUM_WALL_NORTH NONRES_EXT_WALL_GRD 0.30 0.926 1.075 89.13 89.13 0.00 90.00 N
GROUNDFLOOR_PLENUM_WEST NONRES_EXT_WALL_GRD 0.30 0.926 1.075 59.42 59.42 270.00 90.00 W
GROUNDFLOOR_PLENUM_WALL_SOUTH NONRES_EXT_WALL_GRD 0.30 0.926 1.075 89.13 89.13 180.00 90.00 S
GROUNDFLOOR_PLENUM_WALL_EAST NONRES_EXT_WALL_GRD 0.30 0.926 1.075 59.42 59.42 90.00 90.00 E
MIDFLOOR_PLENUM_WALL_NORTH NONRES_EXT_WALL_MID 0.30 0.891 1.028 891.32 891.32 0.00 90.00 N
MIDFLOOR_PLENUM_WALL_WEST NONRES_EXT_WALL_MID 0.30 0.891 1.028 594.21 594.21 270.00 90.00 W
MIDFLOOR_PLENUM_WALL_SOUTH NONRES_EXT_WALL_MID 0.30 0.891 1.028 891.32 891.32 180.00 90.00 S
MIDFLOOR_PLENUM_WALL_EAST NONRES_EXT_WALL_MID 0.30 0.891 1.028 594.21 594.21 90.00 90.00 E
TOPFLOOR_PLENUM_WALL_NORTH NONRES_EXT_WALL_TOP 0.30 1.064 1.266 89.13 89.13 180.00 90.00 S
TOPFLOOR_PLENUM_WALL_EAST NONRES_EXT_WALL_TOP 0.30 1.064 1.266 59.42 59.42 90.00 90.00 E
TOPFLOOR_PLENUM_WALL_WEST NONRES_EXT_WALL_TOP 0.30 1.064 1.266 59.42 59.42 270.00 90.00 W
TOPFLOOR_PLENUM_WALL_SOUTH NONRES_EXT_WALL_TOP 0.30 1.064 1.266 89.13 89.13 0.00 90.00 N
BUILDING_ROOF NONRES_ROOF 0.30 0.182 0.186 3563.11 3563.11 180.00 0.00  
DATACENTER_BASEMENT_ZN_6_WALL_NORTH DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR 1.00 0.399 0.419 39.22 39.22 0.00 90.00 N
DATACENTER_BASEMENT_ZN_6_WALL_SOUTH DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR 1.00 0.399 0.419 39.22 39.22 180.00 90.00 S
DATACENTER_BASEMENT_ZN_6_WALL_WEST DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR 1.00 0.399 0.419 118.87 118.87 270.00 90.00 W


Opaque Interior

Construction Reflectance U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Net Area [m2] Azimuth [deg] Tilt [deg] Cardinal Direction
BASEMENT_WALL_WEST INT_WALL 0.30 2.511 6.299 118.87 118.87 270.00 90.00 W
BASEMENT_FLOOR EXT_SLAB_8IN_WITH_CARPET 0.30 1.591 3.285 2779.43 2779.43 0.00 180.00  
PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER INT_SLAB_CEILING 0.30 1.887 3.839 201.98 201.98 225.00 0.00  
PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER INT_SLAB_CEILING 0.30 1.887 3.839 250.34 250.34 180.00 0.00  
CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER INT_SLAB_CEILING 0.30 1.887 3.839 2076.77 2076.77 180.00 0.00  
PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER INT_SLAB_CEILING 0.30 1.887 3.839 250.34 250.34 180.00 0.00  
CORE_BOT_ZN_5_WALL_SOUTH INT_WALL 0.30 2.511 6.299 173.00 173.00 180.00 90.00 S
CORE_BOT_ZN_5_WALL_WEST INT_WALL 0.30 2.511 6.299 108.64 108.64 270.00 90.00 W
CORE_BOT_ZN_5_WALL_NORTH INT_WALL 0.30 2.511 6.299 173.00 173.00 0.00 90.00 N
CORE_BOT_ZN_5_WALL_EAST INT_WALL 0.30 2.511 6.299 108.64 108.64 90.00 90.00 E
DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER INT_SLAB_FLOOR 0.30 1.887 3.839 419.30 419.30 0.00 180.00  
CORE_BOT_ZN_5_FLOOR INT_SLAB_FLOOR 0.30 1.887 3.839 2076.82 2076.82 0.00 180.00  
CORE_BOT_ZN_5_CEILING DROPCEILING 0.30 2.031 4.488 2496.12 2496.12 180.00 0.00  
CORE_MID_ZN_5_WALL_SOUTH INT_WALL 0.30 2.511 6.299 1729.99 1729.99 180.00 90.00 S
CORE_MID_ZN_5_WALL_WEST INT_WALL 0.30 2.511 6.299 1086.40 1086.40 270.00 90.00 W
CORE_MID_ZN_5_WALL_NORTH INT_WALL 0.30 2.511 6.299 1729.99 1729.99 0.00 90.00 N
CORE_MID_ZN_5_WALL_EAST INT_WALL 0.30 2.511 6.299 1086.40 1086.40 90.00 90.00 E
CORE_MID_ZN_5_FLOOR INT_SLAB_FLOOR 0.30 1.711 3.839 24961.20 24961.20 0.00 180.00  
CORE_MID_ZN_5_CEILING DROPCEILING 0.30 2.031 4.488 24961.20 24961.20 180.00 0.00  
CORE_TOP_ZN_5_WALL_SOUTH INT_WALL 0.30 2.511 6.299 173.00 173.00 180.00 90.00 S
CORE_TOP_ZN_5_WALL_WEST INT_WALL 0.30 2.511 6.299 108.64 108.64 270.00 90.00 W
CORE_TOP_ZN_5_WALL_NORTH INT_WALL 0.30 2.511 6.299 173.00 173.00 0.00 90.00 N
CORE_TOP_ZN_5_WALL_EAST INT_WALL 0.30 2.511 6.299 108.64 108.64 90.00 90.00 E
CORE_TOP_ZN_5_FLOOR INT_SLAB_FLOOR 0.30 1.711 3.839 2496.12 2496.12 0.00 180.00  
CORE_TOP_ZN_5_CEILING DROPCEILING 0.30 2.031 4.488 2496.12 2496.12 180.00 0.00  
PERIMETER_BOT_ZN_3_WALL_WEST INT_WALL 0.30 2.511 6.299 17.75 17.75 225.00 90.00 W
CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 173.00 173.00 180.00 90.00 S
PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 17.75 17.75 135.00 90.00 S
DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 2.51 2.51 180.00 90.00 S
PERIMETER_BOT_ZN_3_FLOOR INT_SLAB_FLOOR 0.30 1.887 3.839 250.34 250.34 0.00 180.00  
DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER INT_SLAB_FLOOR 0.30 1.887 3.839 63.07 63.07 0.00 180.00  
PERIMETER_BOT_ZN_3_CEILING DROPCEILING 0.30 2.031 4.488 313.41 313.41 180.00 0.00  
PERIMETER_BOT_ZN_2_WALL_NORTH INT_WALL 0.30 2.511 6.299 17.75 17.75 315.00 90.00 N
CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 108.64 108.64 270.00 90.00 W
PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 17.75 17.75 225.00 90.00 W
PERIMETER_BOT_ZN_2_FLOOR INT_SLAB_FLOOR 0.30 1.887 3.839 201.98 201.98 45.00 180.00  
PERIMETER_BOT_ZN_2_CEILING DROPCEILING 0.30 2.031 4.488 201.98 201.98 225.00 0.00  
PERIMETER_BOT_ZN_1_WALL_EAST INT_WALL 0.30 2.511 6.299 17.75 17.75 45.00 90.00 E
DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 2.51 2.51 0.00 90.00 N
PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 17.75 17.75 315.00 90.00 N
CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 173.00 173.00 0.00 90.00 N
DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER INT_SLAB_FLOOR 0.30 1.887 3.839 63.07 63.07 0.00 180.00  
PERIMETER_BOT_ZN_1_FLOOR INT_SLAB_FLOOR 0.30 1.887 3.839 250.35 250.35 0.00 180.00  
PERIMETER_BOT_ZN_1_CEILING DROPCEILING 0.30 2.031 4.488 313.42 313.42 180.00 0.00  
PERIMETER_BOT_ZN_4_WALL_SOUTH INT_WALL 0.30 2.511 6.299 17.75 17.75 135.00 90.00 S
DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 108.64 108.64 90.00 90.00 E
PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 17.75 17.75 45.00 90.00 E
PERIMETER_BOT_ZN_4_FLOOR INT_SLAB_FLOOR 0.30 1.887 3.839 201.98 201.98 315.00 180.00  
PERIMETER_BOT_ZN_4_CEILING DROPCEILING 0.30 2.031 4.488 201.98 201.98 135.00 0.00  
PERIMETER_MID_ZN_3_WALL_WEST INT_WALL 0.30 2.511 6.299 177.47 177.47 225.00 90.00 W
CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 1729.99 1729.99 180.00 90.00 S
PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 177.47 177.47 135.00 90.00 S
DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 25.09 25.09 180.00 90.00 S
PERIMETER_MID_ZN_3_FLOOR INT_SLAB_FLOOR 0.30 1.711 3.839 3134.13 3134.13 0.00 180.00  
PERIMETER_MID_ZN_3_CEILING DROPCEILING 0.30 2.031 4.488 3134.13 3134.13 180.00 0.00  
PERIMETER_MID_ZN_2_WALL_NORTH INT_WALL 0.30 2.511 6.299 177.47 177.47 315.00 90.00 N
CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 1086.40 1086.40 270.00 90.00 W
PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 177.47 177.47 225.00 90.00 W
PERIMETER_MID_ZN_2_FLOOR INT_SLAB_FLOOR 0.30 1.711 3.839 2019.75 2019.75 45.00 180.00  
PERIMETER_MID_ZN_2_CEILING DROPCEILING 0.30 2.031 4.488 2019.75 2019.75 225.00 0.00  
PERIMETER_MID_ZN_1_WALL_EAST INT_WALL 0.30 2.511 6.299 177.47 177.47 45.00 90.00 E
DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 25.09 25.09 0.00 90.00 N
PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 177.47 177.47 315.00 90.00 N
CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 1729.99 1729.99 0.00 90.00 N
PERIMETER_MID_ZN_1_FLOOR INT_SLAB_FLOOR 0.30 1.711 3.839 3134.20 3134.20 0.00 180.00  
PERIMETER_MID_ZN_1_CEILING DROPCEILING 0.30 2.031 4.488 3134.20 3134.20 180.00 0.00  
PERIMETER_MID_ZN_4_WALL_SOUTH INT_WALL 0.30 2.511 6.299 177.47 177.47 135.00 90.00 S
DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 1086.40 1086.40 90.00 90.00 E
PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 177.47 177.47 45.00 90.00 E
PERIMETER_MID_ZN_4_FLOOR INT_SLAB_FLOOR 0.30 1.711 3.839 2019.75 2019.75 315.00 180.00  
PERIMETER_MID_ZN_4_CEILING DROPCEILING 0.30 2.031 4.488 2019.75 2019.75 135.00 0.00  
PERIMETER_TOP_ZN_3_WALL_WEST INT_WALL 0.30 2.511 6.299 17.75 17.75 225.00 90.00 W
CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 173.00 173.00 180.00 90.00 S
PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 17.75 17.75 135.00 90.00 S
DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 2.51 2.51 180.00 90.00 S
PERIMETER_TOP_ZN_3_FLOOR INT_SLAB_FLOOR 0.30 1.711 3.839 313.41 313.41 0.00 180.00  
PERIMETER_TOP_ZN_3_CEILING DROPCEILING 0.30 2.031 4.488 313.41 313.41 180.00 0.00  
PERIMETER_TOP_ZN_2_WALL_NORTH INT_WALL 0.30 2.511 6.299 17.75 17.75 315.00 90.00 N
CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 108.64 108.64 270.00 90.00 W
INT-PER3S-NE-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 17.75 17.75 225.00 90.00 W
PERIMETER_TOP_ZN_2_FLOOR INT_SLAB_FLOOR 0.30 1.711 3.839 201.98 201.98 45.00 180.00  
PERIMETER_TOP_ZN_2_CEILING DROPCEILING 0.30 2.031 4.488 201.98 201.98 225.00 0.00  
INT-PER3S-NE INT_WALL 0.30 2.511 6.299 17.75 17.75 45.00 90.00 E
DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 2.51 2.51 0.00 90.00 N
PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 17.75 17.75 315.00 90.00 N
CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 173.00 173.00 0.00 90.00 N
PERIMETER_TOP_ZN_1_FLOOR INT_SLAB_FLOOR 0.30 1.711 3.839 313.42 313.42 0.00 180.00  
PERIMETER_TOP_ZN_1_CEILING DROPCEILING 0.30 2.031 4.488 313.42 313.42 180.00 0.00  
PERIMETER_TOP_ZN_4_WALL_SOUTH INT_WALL 0.30 2.511 6.299 17.75 17.75 135.00 90.00 S
DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 108.64 108.64 90.00 90.00 E
PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 17.75 17.75 45.00 90.00 E
PERIMETER_TOP_ZN_4_FLOOR INT_SLAB_FLOOR 0.30 1.711 3.839 201.98 201.98 315.00 180.00  
PERIMETER_TOP_ZN_4_CEILING DROPCEILING 0.30 2.031 4.488 201.98 201.98 135.00 0.00  
iz-CORE_BOT_ZN_5_CEILING DROPCEILING 0.30 2.031 4.488 2496.12 2496.12 0.00 180.00  
iz-PERIMETER_BOT_ZN_3_CEILING DROPCEILING 0.30 2.031 4.488 313.41 313.41 0.00 180.00  
iz-PERIMETER_BOT_ZN_2_CEILING DROPCEILING 0.30 2.031 4.488 201.98 201.98 45.00 180.00  
iz-PERIMETER_BOT_ZN_1_CEILING DROPCEILING 0.30 2.031 4.488 313.42 313.42 0.00 180.00  
iz-PERIMETER_BOT_ZN_4_CEILING DROPCEILING 0.30 2.031 4.488 201.98 201.98 315.00 180.00  
iz-DATACENTER_BOT_ZN_6_CEILING DROPCEILING 0.30 2.031 4.488 36.20 36.20 0.00 180.00  
GROUNDFLOOR_PLENUM_CEILING INT_SLAB_CEILING 0.30 2.104 3.839 3563.11 3563.11 180.00 0.00  
iz-CORE_MID_ZN_5_CEILING DROPCEILING 0.30 2.031 4.488 24961.20 24961.20 0.00 180.00  
iz-PERIMETER_MID_ZN_3_CEILING DROPCEILING 0.30 2.031 4.488 3134.13 3134.13 0.00 180.00  
iz-PERIMETER_MID_ZN_2_CEILING DROPCEILING 0.30 2.031 4.488 2019.75 2019.75 45.00 180.00  
iz-PERIMETER_MID_ZN_1_CEILING DROPCEILING 0.30 2.031 4.488 3134.20 3134.20 0.00 180.00  
iz-PERIMETER_MID_ZN_4_CEILING DROPCEILING 0.30 2.031 4.488 2019.75 2019.75 315.00 180.00  
iz-DATACENTER_MID_ZN_6_CEILING DROPCEILING 0.30 2.031 4.488 362.03 362.03 0.00 180.00  
MIDFLOOR_PLENUM_CEILING INT_SLAB_CEILING 0.30 2.104 3.839 35631.06 35631.06 180.00 0.00  
iz-CORE_TOP_ZN_5_CEILING DROPCEILING 0.30 2.031 4.488 2496.12 2496.12 0.00 180.00  
iz-PERIMETER_TOP_ZN_3_CEILING DROPCEILING 0.30 2.031 4.488 313.41 313.41 0.00 180.00  
iz-PERIMETER_TOP_ZN_2_CEILING DROPCEILING 0.30 2.031 4.488 201.98 201.98 45.00 180.00  
iz-PERIMETER_TOP_ZN_1_CEILING DROPCEILING 0.30 2.031 4.488 313.42 313.42 0.00 180.00  
iz-PERIMETER_TOP_ZN_4_CEILING DROPCEILING 0.30 2.031 4.488 201.98 201.98 315.00 180.00  
iz-DATACENTER_TOP_ZN_6_CEILING DROPCEILING 0.30 2.031 4.488 36.20 36.20 0.00 180.00  
DATACENTER_BOT_ZN_6_WALL_NORTH INT_WALL 0.30 2.511 6.299 2.51 2.51 0.00 90.00 N
DATACENTER_BOT_ZN_6_WALL_SOUTH INT_WALL 0.30 2.511 6.299 2.51 2.51 180.00 90.00 S
DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 108.64 108.64 90.00 90.00 E
DATACENTER_BOT_ZN_6_WALL_WEST INT_WALL 0.30 2.511 6.299 108.64 108.64 270.00 90.00 W
DATACENTER_BOT_ZN_6_FLOOR INT_SLAB_FLOOR 0.30 1.887 3.839 36.20 36.20 0.00 180.00  
DATACENTER_BOT_ZN_6_CEILING DROPCEILING 0.30 2.031 4.488 36.20 36.20 180.00 0.00  
DATACENTER_MID_ZN_6_WALL_WEST INT_WALL 0.30 2.511 6.299 1086.40 1086.40 270.00 90.00 W
DATACENTER_MID_ZN_6_WALL_SOUTH INT_WALL 0.30 2.511 6.299 25.09 25.09 180.00 90.00 S
DATACENTER_MID_ZN_6_WALL_EAST INT_WALL 0.30 2.511 6.299 1086.40 1086.40 90.00 90.00 E
DATACENTER_MID_ZN_6_WALL_NORTH INT_WALL 0.30 2.511 6.299 25.09 25.09 0.00 90.00 N
DATACENTER_MID_ZN_6_FLOOR INT_SLAB_FLOOR 0.30 1.711 3.839 362.03 362.03 0.00 180.00  
DATACENTER_MID_ZN_6_CEILING DROPCEILING 0.30 2.031 4.488 362.03 362.03 180.00 0.00  
DATACENTER_TOP_ZN_6_WALL_EAST INT_WALL 0.30 2.511 6.299 108.64 108.64 90.00 90.00 E
DATACENTER_TOP_ZN_6_WALL_WEST INT_WALL 0.30 2.511 6.299 108.64 108.64 270.00 90.00 W
DATACENTER_TOP_ZN_6_WALL_SOUTH INT_WALL 0.30 2.511 6.299 2.51 2.51 180.00 90.00 S
DATACENTER_TOP_ZN_6_WALL_NORTH INT_WALL 0.30 2.511 6.299 2.51 2.51 0.00 90.00 N
DATACENTER_TOP_ZN_6_FLOOR INT_SLAB_FLOOR 0.30 1.711 3.839 36.20 36.20 0.00 180.00  
DATACENTER_TOP_ZN_6_CEILING DROPCEILING 0.30 2.031 4.488 36.20 36.20 180.00 0.00  
DATACENTER_BASEMENT_ZN_6_WALL_EAST INT_WALL 0.30 2.511 6.299 118.87 118.87 90.00 90.00 E
DATACENTER_BASEMENT_ZN_6_FLOOR EXT_SLAB_8IN_WITH_CARPET 0.30 1.591 3.285 783.68 783.68 0.00 180.00  
DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER INT_SLAB_CEILING 0.30 1.887 3.839 36.20 36.20 180.00 0.00  
DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 INT_SLAB_CEILING 0.30 1.887 3.839 419.35 419.35 180.00 0.00  
PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER INT_SLAB_CEILING 0.30 1.887 3.839 201.98 201.98 135.00 0.00  
DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 INT_SLAB_CEILING 0.30 1.887 3.839 63.08 63.08 180.00 0.00  
DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 INT_SLAB_CEILING 0.30 1.887 3.839 63.07 63.07 180.00 0.00  
BASEMENT_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 7126.21   0.00 90.00 N
CORE_BOTTOM_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 5064.65   0.00 90.00 N
CORE_MID_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 50646.53   0.00 90.00 N
CORE_TOP_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 5064.65   0.00 90.00 N
PERIMETER_BOT_ZN_3_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 626.83   0.00 90.00 N
PERIMETER_BOT_ZN_2_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 403.95   0.00 90.00 N
PERIMETER_BOT_ZN_1_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 626.84   0.00 90.00 N
PERIMETER_BOT_ZN_4_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 403.95   0.00 90.00 N
PERIMETER_MID_ZN_3_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 6268.26   0.00 90.00 N
PERIMETER_MID_ZN_2_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 4039.50   0.00 90.00 N
PERIMETER_MID_ZN_1_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 6268.35   0.00 90.00 N
PERIMETER_MID_ZN_4_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 4039.48   0.00 90.00 N
PERIMETER_TOP_ZN_3_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 626.83   0.00 90.00 N
PERIMETER_TOP_ZN_2_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 403.95   0.00 90.00 N
PERIMETER_TOP_ZN_1_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 626.84   0.00 90.00 N
PERIMETER_TOP_ZN_4_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 403.95   0.00 90.00 N


Exterior Fenestration

Construction Frame and Divider Glass Area [m2] Frame Area [m2] Divider Area [m2] Area of One Opening [m2] Area of Multiplied Openings [m2] Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance Frame Conductance [W/m2-K] Divider Conductance [W/m2-K] NFRC Product Type Assembly U-Factor [W/m2-K] Assembly SHGC Assembly Visible Transmittance Shade Control Parent Surface Azimuth [deg] Tilt [deg] Cardinal Direction
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 WINDOW_U_0.42_SHGC_NORTH_0.4   23.18 0.00 0.00 23.18 23.18 2.387 0.401 0.442             No PERIMETER_BOT_ZN_3_WALL_NORTH 0.00 90.00 N
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 WINDOW_U_0.42_SHGC_NORTH_0.4   23.18 0.00 0.00 23.18 23.18 2.387 0.401 0.442             No PERIMETER_BOT_ZN_3_WALL_NORTH 0.00 90.00 N
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 WINDOW_U_0.42_SHGC_NORTH_0.4   23.18 0.00 0.00 23.18 23.18 2.387 0.401 0.442             No PERIMETER_BOT_ZN_3_WALL_NORTH 0.00 90.00 N
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 WINDOW_U_0.42_SHGC_NORTH_0.4   23.18 0.00 0.00 23.18 23.18 2.387 0.401 0.442             No PERIMETER_BOT_ZN_3_WALL_NORTH 0.00 90.00 N
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 WINDOW_U_0.42_SHGC_NORTH_0.4   23.18 0.00 0.00 23.18 23.18 2.387 0.401 0.442             No PERIMETER_BOT_ZN_3_WALL_NORTH 0.00 90.00 N
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 WINDOW_U_0.42_SHGC_EAST_0.4   25.75 0.00 0.00 25.75 25.75 2.387 0.401 0.442             No PERIMETER_BOT_ZN_2_WALL_EAST 90.00 90.00 E
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 WINDOW_U_0.42_SHGC_EAST_0.4   25.75 0.00 0.00 25.75 25.75 2.387 0.401 0.442             No PERIMETER_BOT_ZN_2_WALL_EAST 90.00 90.00 E
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 WINDOW_U_0.42_SHGC_EAST_0.4   25.75 0.00 0.00 25.75 25.75 2.387 0.401 0.442             No PERIMETER_BOT_ZN_2_WALL_EAST 90.00 90.00 E
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 WINDOW_U_0.42_SHGC_SOUTH_0.4   23.18 0.00 0.00 23.18 23.18 2.387 0.401 0.442             No PERIMETER_BOT_ZN_1_WALL_SOUTH 180.00 90.00 S
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 WINDOW_U_0.42_SHGC_SOUTH_0.4   23.18 0.00 0.00 23.18 23.18 2.387 0.401 0.442             No PERIMETER_BOT_ZN_1_WALL_SOUTH 180.00 90.00 S
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 WINDOW_U_0.42_SHGC_SOUTH_0.4   23.18 0.00 0.00 23.18 23.18 2.387 0.401 0.442             No PERIMETER_BOT_ZN_1_WALL_SOUTH 180.00 90.00 S
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 WINDOW_U_0.42_SHGC_SOUTH_0.4   23.18 0.00 0.00 23.18 23.18 2.387 0.401 0.442             No PERIMETER_BOT_ZN_1_WALL_SOUTH 180.00 90.00 S
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 WINDOW_U_0.42_SHGC_SOUTH_0.4   23.18 0.00 0.00 23.18 23.18 2.387 0.401 0.442             No PERIMETER_BOT_ZN_1_WALL_SOUTH 180.00 90.00 S
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 WINDOW_U_0.42_SHGC_WEST_0.4   25.75 0.00 0.00 25.75 25.75 2.387 0.401 0.442             No PERIMETER_BOT_ZN_4_WALL_WEST 270.00 90.00 W
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 WINDOW_U_0.42_SHGC_WEST_0.4   25.75 0.00 0.00 25.75 25.75 2.387 0.401 0.442             No PERIMETER_BOT_ZN_4_WALL_WEST 270.00 90.00 W
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 WINDOW_U_0.42_SHGC_WEST_0.4   25.75 0.00 0.00 25.75 25.75 2.387 0.401 0.442             No PERIMETER_BOT_ZN_4_WALL_WEST 270.00 90.00 W
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW WINDOW_U_0.42_SHGC_NORTH_0.4   115.90 0.00 0.00 115.90 1158.95 2.387 0.401 0.442             No PERIMETER_MID_ZN_3_WALL_NORTH 0.00 90.00 N
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW WINDOW_U_0.42_SHGC_EAST_0.4   77.26 0.00 0.00 77.26 772.63 2.387 0.401 0.442             No PERIMETER_MID_ZN_2_WALL_EAST 90.00 90.00 E
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW WINDOW_U_0.42_SHGC_SOUTH_0.4   115.90 0.00 0.00 115.90 1158.95 2.387 0.401 0.442             No PERIMETER_MID_ZN_1_WALL_SOUTH 180.00 90.00 S
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW WINDOW_U_0.42_SHGC_WEST_0.4   77.26 0.00 0.00 77.26 772.63 2.387 0.401 0.442             No PERIMETER_MID_ZN_4_WALL_WEST 270.00 90.00 W
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW WINDOW_U_0.42_SHGC_NORTH_0.4   115.90 0.00 0.00 115.90 115.90 2.387 0.401 0.442             No PERIMETER_TOP_ZN_3_WALL_NORTH 0.00 90.00 N
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW WINDOW_U_0.42_SHGC_EAST_0.4   77.26 0.00 0.00 77.26 77.26 2.387 0.401 0.442             No PERIMETER_TOP_ZN_2_WALL_EAST 90.00 90.00 E
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW WINDOW_U_0.42_SHGC_SOUTH_0.4   115.90 0.00 0.00 115.90 115.90 2.387 0.401 0.442             No PERIMETER_TOP_ZN_1_WALL_SOUTH 180.00 90.00 S
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW WINDOW_U_0.42_SHGC_WEST_0.4   77.26 0.00 0.00 77.26 77.26 2.387 0.401 0.442             No PERIMETER_TOP_ZN_4_WALL_WEST 270.00 90.00 W
Total or Average             4635.80 2.387 0.401 0.442                      
North Total or Average             1390.74 2.387 0.401 0.442                      
Non-North Total or Average             3245.06 2.387 0.401 0.442                      


Exterior Fenestration Shaded State

Frame and Divider Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance NFRC Product Type Assembly U-Factor [W/m2-K] Assembly SHGC Assembly Visible Transmittance
None                


Interior Fenestration

Construction Area of One Opening [m2] Area of Openings [m2] Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance
Total or Average     0.00 - - -


Exterior Door

Construction U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Parent Surface
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 SWINGING DOOR_CON 1.992 2.839 1.95 PERIMETER_BOT_ZN_3_WALL_NORTH
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 SWINGING DOOR_CON 1.992 2.839 1.95 PERIMETER_BOT_ZN_3_WALL_NORTH
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 SWINGING DOOR_CON 1.992 2.839 1.95 PERIMETER_BOT_ZN_3_WALL_NORTH
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 SWINGING DOOR_CON 1.992 2.839 1.95 PERIMETER_BOT_ZN_3_WALL_NORTH
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 SWINGING DOOR_CON 1.992 2.839 1.95 PERIMETER_BOT_ZN_2_WALL_EAST
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 SWINGING DOOR_CON 1.992 2.839 1.95 PERIMETER_BOT_ZN_2_WALL_EAST
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 SWINGING DOOR_CON 1.992 2.839 1.95 PERIMETER_BOT_ZN_1_WALL_SOUTH
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 SWINGING DOOR_CON 1.992 2.839 1.95 PERIMETER_BOT_ZN_1_WALL_SOUTH
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 SWINGING DOOR_CON 1.992 2.839 1.95 PERIMETER_BOT_ZN_1_WALL_SOUTH
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 SWINGING DOOR_CON 1.992 2.839 1.95 PERIMETER_BOT_ZN_1_WALL_SOUTH
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 SWINGING DOOR_CON 1.992 2.839 1.95 PERIMETER_BOT_ZN_4_WALL_WEST
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 SWINGING DOOR_CON 1.992 2.839 1.95 PERIMETER_BOT_ZN_4_WALL_WEST


Interior Door

Construction U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Parent Surface
None          



Table of Contents

Report: Shading Summary

For: Entire Facility

Timestamp: 2023-10-16 08:43:34

Sunlit Fraction

March 21 9am March 21 noon March 21 3pm June 21 9am June 21 noon June 21 3pm December 21 9am December 21 noon December 21 3pm
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00


Window Control

Name Type Shaded Construction Control Glare Control
None          



Table of Contents

Report: Lighting Summary

For: Entire Facility

Timestamp: 2023-10-16 08:43:34

Interior Lighting

Zone Name Space Name Space Type Lighting Power Density [W/m2] Space Area [m2] Total Power [W] End Use Subcategory Schedule Name Scheduled Hours/Week [hr] Hours/Week > 1% [hr] Full Load Hours/Week [hr] Return Air Fraction Conditioned (Y/N) Consumption [GJ]
BASEMENT_LIGHTS BASEMENT BASEMENT GENERAL 10.2732 2779.43 28553.72 LightsWired LTG_SCH_OFFICE 50.34 168.00 49.04 0.0000 Y 262.84
CORE_BOTTOM_LIGHTS CORE_BOTTOM CORE_BOTTOM GENERAL 10.2732 2496.12 25643.24 LightsWired LTG_SCH_OFFICE 50.34 168.00 49.04 0.0000 Y 236.05
CORE_MID_LIGHTS CORE_MID CORE_MID GENERAL 10.2732 24961.20 256432.45 LightsWired LTG_SCH_OFFICE 50.34 168.00 49.04 0.0000 Y 2360.52
CORE_TOP_LIGHTS CORE_TOP CORE_TOP GENERAL 10.2732 2496.12 25643.24 LightsWired LTG_SCH_OFFICE 50.34 168.00 49.04 0.0000 Y 236.05
PERIMETER_BOT_ZN_3_LIGHTS PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3 GENERAL 10.2732 313.41 3219.77 LightsWired LTG_SCH_OFFICE 50.34 168.00 28.85 0.0000 Y 17.44
PERIMETER_BOT_ZN_2_LIGHTS PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2 GENERAL 10.2732 201.98 2074.94 LightsWired LTG_SCH_OFFICE 50.34 168.00 28.72 0.0000 Y 11.19
PERIMETER_BOT_ZN_1_LIGHTS PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1 GENERAL 10.2732 313.42 3219.84 LightsWired LTG_SCH_OFFICE 50.34 168.00 28.41 0.0000 Y 17.17
PERIMETER_BOT_ZN_4_LIGHTS PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4 GENERAL 10.2732 201.98 2074.94 LightsWired LTG_SCH_OFFICE 50.34 168.00 28.48 0.0000 Y 11.09
PERIMETER_MID_ZN_3_LIGHTS PERIMETER_MID_ZN_3 PERIMETER_MID_ZN_3 GENERAL 10.2732 3134.13 32197.65 LightsWired LTG_SCH_OFFICE 50.34 168.00 28.79 0.0000 Y 174.00
PERIMETER_MID_ZN_2_LIGHTS PERIMETER_MID_ZN_2 PERIMETER_MID_ZN_2 GENERAL 10.2732 2019.75 20749.39 LightsWired LTG_SCH_OFFICE 50.34 168.00 28.68 0.0000 Y 111.71
PERIMETER_MID_ZN_1_LIGHTS PERIMETER_MID_ZN_1 PERIMETER_MID_ZN_1 GENERAL 10.2732 3134.20 32198.36 LightsWired LTG_SCH_OFFICE 50.34 168.00 28.38 0.0000 Y 171.53
PERIMETER_MID_ZN_4_LIGHTS PERIMETER_MID_ZN_4 PERIMETER_MID_ZN_4 GENERAL 10.2732 2019.75 20749.39 LightsWired LTG_SCH_OFFICE 50.34 168.00 28.44 0.0000 Y 110.76
PERIMETER_TOP_ZN_3_LIGHTS PERIMETER_TOP_ZN_3 PERIMETER_TOP_ZN_3 GENERAL 10.2732 313.41 3219.77 LightsWired LTG_SCH_OFFICE 50.34 168.00 28.79 0.0000 Y 17.40
PERIMETER_TOP_ZN_2_LIGHTS PERIMETER_TOP_ZN_2 PERIMETER_TOP_ZN_2 GENERAL 10.2732 201.98 2074.94 LightsWired LTG_SCH_OFFICE 50.34 168.00 28.68 0.0000 Y 11.17
PERIMETER_TOP_ZN_1_LIGHTS PERIMETER_TOP_ZN_1 PERIMETER_TOP_ZN_1 GENERAL 10.2732 313.42 3219.84 LightsWired LTG_SCH_OFFICE 50.34 168.00 28.38 0.0000 Y 17.15
PERIMETER_TOP_ZN_4_LIGHTS PERIMETER_TOP_ZN_4 PERIMETER_TOP_ZN_4 GENERAL 10.2732 201.98 2074.94 LightsWired LTG_SCH_OFFICE 50.34 168.00 28.44 0.0000 Y 11.08
DATACENTER_BASEMENT_LIGHTS DATACENTER_BASEMENT_ZN_6 DATACENTER_BASEMENT_ZN_6 GENERAL 10.2732 783.68 8050.93 LightsWired LTG_SCH_OFFICE 50.34 168.00 49.04 0.0000 Y 74.11
DATACENTER_BOT_LIGHTS DATACENTER_BOT_ZN_6 DATACENTER_BOT_ZN_6 GENERAL 17.8735 36.20 647.07 LightsWired LTG_SCH_DATACENTER 56.02 168.00 54.57 0.0000 Y 6.63
DATACENTER_MID_LIGHTS DATACENTER_MID_ZN_6 DATACENTER_MID_ZN_6 GENERAL 17.8735 362.03 6470.68 LightsWired LTG_SCH_DATACENTER 56.02 168.00 54.57 0.0000 Y 66.28
DATACENTER_TOP_LIGHTS DATACENTER_TOP_ZN_6 DATACENTER_TOP_ZN_6 GENERAL 17.8735 36.20 647.07 LightsWired LTG_SCH_DATACENTER 56.02 168.00 54.57 0.0000 Y 6.63
Interior Lighting Total       10.3445 46320.38 479162.15               1235.48


Daylighting

Zone Control Name Daylighting Method Control Type Fraction Controlled Lighting Installed in Zone [W] Lighting Controlled [W]
PERIMETER_BOT_ZN_1_DAYLREFPT1 PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_DAYLCTRL SplitFlux Stepped 0.39 3219.84 1241.89
PERIMETER_BOT_ZN_1_DAYLREFPT2 PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_DAYLCTRL SplitFlux Stepped 0.14 3219.84 445.95
PERIMETER_BOT_ZN_2_DAYLREFPT1 PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_DAYLCTRL SplitFlux Stepped 0.39 2074.94 800.30
PERIMETER_BOT_ZN_2_DAYLREFPT2 PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_DAYLCTRL SplitFlux Stepped 0.14 2074.94 287.38
PERIMETER_BOT_ZN_3_DAYLREFPT1 PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_DAYLCTRL SplitFlux Stepped 0.39 3219.77 1241.86
PERIMETER_BOT_ZN_3_DAYLREFPT2 PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_DAYLCTRL SplitFlux Stepped 0.14 3219.77 445.94
PERIMETER_BOT_ZN_4_DAYLREFPT1 PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_DAYLCTRL SplitFlux Stepped 0.39 2074.94 800.30
PERIMETER_BOT_ZN_4_DAYLREFPT2 PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_DAYLCTRL SplitFlux Stepped 0.14 2074.94 287.38
PERIMETER_MID_ZN_1_DAYLREFPT1 PERIMETER_MID_ZN_1 PERIMETER_MID_ZN_1_DAYLCTRL SplitFlux Stepped 0.39 3219.84 1241.89
PERIMETER_MID_ZN_1_DAYLREFPT2 PERIMETER_MID_ZN_1 PERIMETER_MID_ZN_1_DAYLCTRL SplitFlux Stepped 0.14 3219.84 445.95
PERIMETER_MID_ZN_2_DAYLREFPT1 PERIMETER_MID_ZN_2 PERIMETER_MID_ZN_2_DAYLCTRL SplitFlux Stepped 0.39 2074.94 800.30
PERIMETER_MID_ZN_2_DAYLREFPT2 PERIMETER_MID_ZN_2 PERIMETER_MID_ZN_2_DAYLCTRL SplitFlux Stepped 0.14 2074.94 287.38
PERIMETER_MID_ZN_3_DAYLREFPT1 PERIMETER_MID_ZN_3 PERIMETER_MID_ZN_3_DAYLCTRL SplitFlux Stepped 0.39 3219.77 1241.86
PERIMETER_MID_ZN_3_DAYLREFPT2 PERIMETER_MID_ZN_3 PERIMETER_MID_ZN_3_DAYLCTRL SplitFlux Stepped 0.14 3219.77 445.94
PERIMETER_MID_ZN_4_DAYLREFPT1 PERIMETER_MID_ZN_4 PERIMETER_MID_ZN_4_DAYLCTRL SplitFlux Stepped 0.39 2074.94 800.30
PERIMETER_MID_ZN_4_DAYLREFPT2 PERIMETER_MID_ZN_4 PERIMETER_MID_ZN_4_DAYLCTRL SplitFlux Stepped 0.14 2074.94 287.38
PERIMETER_TOP_ZN_1_DAYLREFPT1 PERIMETER_TOP_ZN_1 PERIMETER_TOP_ZN_1_DAYLCTRL SplitFlux Stepped 0.39 3219.84 1241.89
PERIMETER_TOP_ZN_1_DAYLREFPT2 PERIMETER_TOP_ZN_1 PERIMETER_TOP_ZN_1_DAYLCTRL SplitFlux Stepped 0.14 3219.84 445.95
PERIMETER_TOP_ZN_2_DAYLREFPT1 PERIMETER_TOP_ZN_2 PERIMETER_TOP_ZN_2_DAYLCTRL SplitFlux Stepped 0.39 2074.94 800.30
PERIMETER_TOP_ZN_2_DAYLREFPT2 PERIMETER_TOP_ZN_2 PERIMETER_TOP_ZN_2_DAYLCTRL SplitFlux Stepped 0.14 2074.94 287.38
PERIMETER_TOP_ZN_3_DAYLREFPT1 PERIMETER_TOP_ZN_3 PERIMETER_TOP_ZN_3_DAYLCTRL SplitFlux Stepped 0.39 3219.77 1241.86
PERIMETER_TOP_ZN_3_DAYLREFPT2 PERIMETER_TOP_ZN_3 PERIMETER_TOP_ZN_3_DAYLCTRL SplitFlux Stepped 0.14 3219.77 445.94
PERIMETER_TOP_ZN_4_DAYLREFPT1 PERIMETER_TOP_ZN_4 PERIMETER_TOP_ZN_4_DAYLCTRL SplitFlux Stepped 0.39 2074.94 800.30
PERIMETER_TOP_ZN_4_DAYLREFPT2 PERIMETER_TOP_ZN_4 PERIMETER_TOP_ZN_4_DAYLCTRL SplitFlux Stepped 0.14 2074.94 287.38


Exterior Lighting

Total Watts Astronomical Clock/Schedule Schedule Name Scheduled Hours/Week [hr] Hours/Week > 1% [hr] Full Load Hours/Week [hr] Consumption [GJ]
EXTERIOR_LIGHTS_A 13279.00 AstronomicalClock -   42.43 42.43 105.78
EXTERIOR_LIGHTS_B 44301.60 AstronomicalClock -   83.64 71.28 592.77
Exterior Lighting Total 57580.60           698.54



Table of Contents

Report: Equipment Summary

For: Entire Facility

Timestamp: 2023-10-16 08:43:34

Central Plant

Type Reference Capacity [W] Reference Efficiency [W/W] Rated Capacity [W] Rated Efficiency [W/W] IPLV in SI Units [W/W] IPLV in IP Units [Btu/W-h]
BYPASS HEAT EXCHANGER HeatExchanger:FluidToFluid 3007367.22          
HEATSYS1 BOILER Boiler:HotWater 2843237.57 0.81        
COOLSYS1 CHILLER1 Chiller:Electric:ReformulatedEIR 1527224.44 6.28 1461747.96 5.98 6.84 23.33
COOLSYS1 CHILLER2 Chiller:Electric:ReformulatedEIR 1527224.44 6.28 1461747.96 5.98 6.84 23.33
CENTRAL TOWER FluidCooler:TwoSpeed 582060.00          
CENTRAL BOILER Boiler:HotWater 542032.73 0.80        
TOWERWATERSYS COOLTOWER 1 CoolingTower:VariableSpeed 1812006.78          
TOWERWATERSYS COOLTOWER 2 CoolingTower:VariableSpeed 1812006.78          


Cooling Coils

Type Design Coil Load [W] Nominal Total Capacity [W] Nominal Sensible Capacity [W] Nominal Latent Capacity [W] Nominal Sensible Heat Ratio Nominal Efficiency [W/W] Nominal Coil UA Value [W/C] Nominal Coil Surface Area [m2]
VAV_BOT WITH REHEAT COOLING COIL Coil:Cooling:Water 244927.46 268186.13 184453.65 83732.48 0.69 - 27653.98 280.48
VAV_MID WITH REHEAT COOLING COIL Coil:Cooling:Water 2396783.59 2575166.49 1761486.35 813680.14 0.68 - 267330.97 2711.42
VAV_TOP WITH REHEAT COOLING COIL Coil:Cooling:Water 249517.12 274476.69 188952.96 85523.73 0.69 - 28308.92 287.12
CAV_BAS COOLING COIL Coil:Cooling:Water 123071.04 144069.09 101074.35 42994.75 0.70 - 14644.17 148.53
AIRLOOP DATACENTER BASEMENT COOLING COIL Coil:Cooling:WaterToAirHeatPump:EquationFit   433170.49 312730.66 120439.84 0.72 0.00    
AIRLOOP DATACENTER BOT COOLING COIL Coil:Cooling:WaterToAirHeatPump:EquationFit   9910.60 7177.44 2733.16 0.72 0.00    
AIRLOOP DATACENTER MID COOLING COIL Coil:Cooling:WaterToAirHeatPump:EquationFit   95118.13 68824.67 26293.46 0.72 0.00    
AIRLOOP DATACENTER TOP COOLING COIL Coil:Cooling:WaterToAirHeatPump:EquationFit   9678.21 7004.39 2673.82 0.72 0.00    
Nominal values are gross at rated conditions, i.e., the supply air fan heat and electric power NOT accounted for.

DX Cooling Coils

DX Cooling Coil Type Standard Rated Net Cooling Capacity [W] Standard Rated Net COP [W/W] EER [Btu/W-h] SEER User [Btu/W-h] SEER Standard [Btu/W-h] IEER [Btu/W-h]
None              


DX Cooling Coil ASHRAE 127 Standard Ratings Report

DX Cooling Coil Type Rated Net Cooling Capacity Test A [W] Rated Electric Power Test A [W] Rated Net Cooling Capacity Test B [W] Rated Electric Power Test B [W] Rated Net Cooling Capacity Test C [W] Rated Electric Power Test C [W] Rated Net Cooling Capacity Test D [W] Rated Electric Power Test D [W]
None                  


DX Heating Coils

DX Heating Coil Type High Temperature Heating (net) Rating Capacity [W] Low Temperature Heating (net) Rating Capacity [W] HSPF [Btu/W-h] Region Number
None          


Heating Coils

Type Design Coil Load [W] Nominal Total Capacity [W] Nominal Efficiency [W/W]
CORE_BOTTOM VAV BOX REHEAT COIL Coil:Heating:Water 19871.01 18841.58 -
CORE_MID VAV BOX REHEAT COIL Coil:Heating:Water 502362.85 475897.95 -
CORE_TOP VAV BOX REHEAT COIL Coil:Heating:Water 90567.17 85822.05 -
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL Coil:Heating:Water 16611.22 15738.62 -
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL Coil:Heating:Water 11282.69 10689.89 -
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL Coil:Heating:Water 18180.52 17225.24 -
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL Coil:Heating:Water 9669.44 9157.63 -
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL Coil:Heating:Water 281179.94 266381.97 -
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL Coil:Heating:Water 184302.05 174602.07 -
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL Coil:Heating:Water 277679.97 263066.56 -
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL Coil:Heating:Water 179958.26 170487.24 -
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL Coil:Heating:Water 35087.95 33240.44 -
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL Coil:Heating:Water 22938.67 21730.82 -
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL Coil:Heating:Water 34713.48 32885.71 -
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL Coil:Heating:Water 22682.07 21487.73 -
VAV_BOT WITH REHEAT HEATING COIL Coil:Heating:Water 72503.51 53835.22 -
VAV_MID WITH REHEAT HEATING COIL Coil:Heating:Water 691595.11 512152.08 -
VAV_TOP WITH REHEAT HEATING COIL Coil:Heating:Water 68252.18 51603.64 -
CAV_BAS HEATING COIL Coil:Heating:Water 303799.48 237476.32 -
AIRLOOP DATACENTER BASEMENT HEATING COIL Coil:Heating:WaterToAirHeatPump:EquationFit   433170.49 0.00
AIRLOOP DATACENTER BOT HEATING COIL Coil:Heating:WaterToAirHeatPump:EquationFit   9910.60 0.00
AIRLOOP DATACENTER MID HEATING COIL Coil:Heating:WaterToAirHeatPump:EquationFit   95118.13 0.00
AIRLOOP DATACENTER TOP HEATING COIL Coil:Heating:WaterToAirHeatPump:EquationFit   9678.21 0.00
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL Coil:Heating:Electric   20749.82 1.00
AIRLOOP DATACENTER BOT_SUPPHEATCOIL Coil:Heating:Electric   958.56 1.00
AIRLOOP DATACENTER MID_SUPPHEATCOIL Coil:Heating:Electric   9585.56 1.00
AIRLOOP DATACENTER TOP_SUPPHEATCOIL Coil:Heating:Electric   958.56 1.00
Nominal values are gross at rated conditions, i.e., the supply air fan heat and electric power NOT accounted for.

Fans

Type Total Efficiency [W/W] Delta Pressure [pa] Max Air Flow Rate [m3/s] Rated Electricity Rate [W] Rated Power Per Max Air Flow Rate [W-s/m3] Motor Heat In Air Fraction Fan Energy Index End Use Subcategory Design Day Name for Fan Sizing Peak Date/Time for Fan Sizing Peak
VAV_BOT WITH REHEAT FAN Fan:VariableVolume 0.61 1314.72 10.39 22336.20 2149.46 1.00 1.12 General NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00
VAV_MID WITH REHEAT FAN Fan:VariableVolume 0.61 1389.42 97.93 222465.69 2271.59 1.00 1.08 General NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00
VAV_TOP WITH REHEAT FAN Fan:VariableVolume 0.61 1314.72 10.67 22924.78 2149.46 1.00 1.12 General NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00
CAV_BAS FAN Fan:ConstantVolume 0.60 1018.41 5.96 10103.89 1695.65 1.00 1.15 General NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00
AIRLOOP DATACENTER BASEMENT SUPPLY FAN Fan:OnOff 0.61 1018.41 21.41 35499.94 1657.97 1.00 1.13 General NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 07:10:00
AIRLOOP DATACENTER BOT SUPPLY FAN Fan:OnOff 0.56 622.50 0.49 552.61 1120.11 1.00 1.61 General NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00
AIRLOOP DATACENTER MID SUPPLY FAN Fan:OnOff 0.56 622.50 4.73 5294.92 1120.11 1.00 1.16 General NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00
AIRLOOP DATACENTER TOP SUPPLY FAN Fan:OnOff 0.56 622.50 0.48 538.97 1120.11 1.00 1.62 General NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00


Pumps

Type Control Head [pa] Water Flow [m3/s] Electricity Rate [W] Power Per Water Flow Rate [W-s/m3] Motor Efficiency [W/W] End Use Subcategory
COOLSYS1 PUMP SECONDARY Pump:VariableSpeed Intermittent 105797.75 0.128235 20936.90 163269.45 0.90 General
HEATSYS1 PUMP Pump:VariableSpeed Intermittent 180705.70 0.024874 7490.92 301156.09 0.90 General
COOLSYS1 CHILLER1 PUMP Pump:ConstantSpeed Intermittent 73247.35 0.064118 7247.66 113036.94 0.90 General
COOLSYS1 CHILLER2 PUMP Pump:ConstantSpeed Intermittent 73247.35 0.064118 7247.66 113036.94 0.90 General
PLANT CIRC PUMP Pump:ConstantSpeed Intermittent 179045.11 0.013417 3422.13 255050.01 0.90 General
SWHSYS1 PUMP Pump:ConstantSpeed Intermittent 29891.00 0.000440 56.21 127739.32 0.30 General
TOWERWATERSYS PUMP HeaderedPumps:VariableSpeed Intermittent 148556.62 0.151153 37422.23 247577.87 0.90 General


Service Water Heating

Type Storage Volume [m3] Input [W] Thermal Efficiency [W/W] Recovery Efficiency [W/W] Energy Factor
SWHSYS1 WATER HEATER WaterHeater:Mixed 1.14 87921.32 0.80 0.48 0.06



Table of Contents

Report: HVAC Sizing Summary

For: Entire Facility

Timestamp: 2023-10-16 08:43:34

Zone Sensible Cooling

Calculated Design Load [W] User Design Load [W] User Design Load per Area [W/m2] Calculated Design Air Flow [m3/s] User Design Air Flow [m3/s] Design Day Name Date/Time Of Peak {TIMESTAMP} Thermostat Setpoint Temperature at Peak Load [C] Indoor Temperature at Peak Load [C] Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] Outdoor Temperature at Peak Load [C] Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] Minimum Outdoor Air Flow Rate [m3/s] Heat Gain Rate from DOAS [W]
BASEMENT 82706.28 82706.28 29.76 5.959 5.959 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 24.00 24.00 0.00892 26.62 0.01411 1.200 0.00
CORE_BOTTOM 85919.09 85919.09 34.42 6.190 6.190 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 24.00 24.00 0.00886 26.62 0.01411 1.078 0.00
CORE_MID 810828.86 810828.86 324.84 58.398 58.398 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 24.00 24.00 0.00889 26.62 0.01411 10.778 0.00
CORE_TOP 82145.87 82145.87 32.91 5.917 5.917 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 24.00 24.00 0.00888 26.62 0.01411 1.078 0.00
PERIMETER_BOT_ZN_3 14968.17 14968.17 47.76 1.088 1.088 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:10:00 24.00 24.00 0.00891 32.10 0.01412 0.135 0.00
PERIMETER_BOT_ZN_2 18490.82 18490.82 91.55 1.344 1.344 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 08:50:00 24.00 24.00 0.00872 27.80 0.01411 0.087 0.00
PERIMETER_BOT_ZN_1 21398.74 21398.74 68.28 1.556 1.556 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 13:00:00 24.00 24.00 0.00879 31.73 0.01412 0.135 0.00
PERIMETER_BOT_ZN_4 22371.18 22371.18 110.76 1.626 1.626 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 16:30:00 24.00 24.00 0.00868 31.36 0.01412 0.087 0.00
PERIMETER_MID_ZN_3 143982.75 143982.75 459.40 10.467 10.467 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:20:00 24.00 24.00 0.00912 32.10 0.01412 1.353 0.00
PERIMETER_MID_ZN_2 197582.58 197582.58 978.25 14.364 14.364 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 09:10:00 24.00 24.00 0.00881 28.24 0.01411 0.872 0.00
PERIMETER_MID_ZN_1 213617.96 213617.96 681.57 15.530 15.530 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 13:10:00 24.00 24.00 0.00892 31.79 0.01412 1.353 0.00
PERIMETER_MID_ZN_4 206955.44 206955.44 1024.66 15.045 15.045 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 16:40:00 24.00 24.00 0.00879 31.26 0.01412 0.872 0.00
PERIMETER_TOP_ZN_3 16192.57 16192.57 51.67 1.177 1.177 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:40:00 24.00 24.00 0.00912 32.10 0.01412 0.135 0.00
PERIMETER_TOP_ZN_2 20073.28 20073.28 99.38 1.459 1.459 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 09:20:00 24.00 24.00 0.00884 28.45 0.01411 0.087 0.00
PERIMETER_TOP_ZN_1 23032.69 23032.69 73.49 1.674 1.674 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 13:20:00 24.00 24.00 0.00895 31.85 0.01412 0.135 0.00
PERIMETER_TOP_ZN_4 21866.74 21866.74 108.26 1.590 1.590 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 16:40:00 24.00 24.00 0.00881 31.26 0.01412 0.087 0.00
DATACENTER_BOT_ZN_6 8605.13 8605.13 237.69 0.493 0.493 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 18:40:00 27.00 27.00 0.00858 29.58 0.01412 0.016 0.00
DATACENTER_MID_ZN_6 82450.39 82450.39 2277.46 4.727 4.727 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 18:40:00 27.00 27.00 0.00859 29.58 0.01412 0.156 0.00
DATACENTER_TOP_ZN_6 8392.72 8392.72 231.83 0.481 0.481 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 18:40:00 27.00 27.00 0.00859 29.58 0.01412 0.016 0.00
DATACENTER_BASEMENT_ZN_6 373462.70 373462.70 476.55 21.411 21.411 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 07:00:00 27.00 27.00 0.00854 25.37 0.01411 0.338 0.00
The Design Load is the zone sensible load only. It does not include any system effects or ventilation loads.

Zone Sensible Heating

Calculated Design Load [W] User Design Load [W] User Design Load per Area [W/m2] Calculated Design Air Flow [m3/s] User Design Air Flow [m3/s] Design Day Name Date/Time Of Peak {TIMESTAMP} Thermostat Setpoint Temperature at Peak Load [C] Indoor Temperature at Peak Load [C] Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] Outdoor Temperature at Peak Load [C] Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] Minimum Outdoor Air Flow Rate [m3/s] Heat Gain Rate from DOAS [W]
BASEMENT 0.00 0.00 0.00 0.000 1.200 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:50:00 21.00 23.62 0.00150 -10.70 0.00150 1.200 0.00
CORE_BOTTOM 0.00 0.00 0.00 0.000 1.078 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 05:40:00 17.60 21.02 0.00150 -10.70 0.00150 1.078 0.00
CORE_MID 307241.88 307241.88 123.09 12.976 12.976 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00800 -10.70 0.00150 10.778 0.00
CORE_TOP 63427.13 63427.13 25.41 2.697 2.697 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00800 -10.70 0.00150 1.078 0.00
PERIMETER_BOT_ZN_3 11633.54 11633.54 37.12 0.495 0.495 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00724 -10.70 0.00150 0.135 0.00
PERIMETER_BOT_ZN_2 7900.94 7900.94 39.12 0.337 0.337 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00729 -10.70 0.00150 0.087 0.00
PERIMETER_BOT_ZN_1 12730.23 12730.23 40.62 0.542 0.542 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00736 -10.70 0.00150 0.135 0.00
PERIMETER_BOT_ZN_4 6403.53 6403.53 31.70 0.273 0.273 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00699 -10.70 0.00150 0.087 0.00
PERIMETER_MID_ZN_3 196842.26 196842.26 628.06 8.397 8.397 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00719 -10.70 0.00150 1.353 0.00
PERIMETER_MID_ZN_2 129022.04 129022.04 638.80 5.504 5.504 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00718 -10.70 0.00150 0.872 0.00
PERIMETER_MID_ZN_1 194394.91 194394.91 620.24 8.292 8.292 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00718 -10.70 0.00150 1.353 0.00
PERIMETER_MID_ZN_4 125984.43 125984.43 623.76 5.374 5.374 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00716 -10.70 0.00150 0.872 0.00
PERIMETER_TOP_ZN_3 24561.08 24561.08 78.37 1.048 1.048 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00720 -10.70 0.00150 0.135 0.00
PERIMETER_TOP_ZN_2 16056.85 16056.85 79.50 0.685 0.685 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 20.99 0.00719 -10.70 0.00150 0.087 0.00
PERIMETER_TOP_ZN_1 24299.21 24299.21 77.53 1.037 1.037 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00719 -10.70 0.00150 0.135 0.00
PERIMETER_TOP_ZN_4 15877.37 15877.37 78.61 0.678 0.678 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 20.99 0.00718 -10.70 0.00150 0.087 0.00
DATACENTER_BOT_ZN_6 0.00 0.00 0.00 0.000 0.016 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 05:30:00 18.00 25.15 0.00525 -10.70 0.00150 0.016 0.00
DATACENTER_MID_ZN_6 0.00 0.00 0.00 0.000 0.156 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 05:40:00 18.00 22.65 0.00200 -10.70 0.00150 0.156 0.00
DATACENTER_TOP_ZN_6 0.00 0.00 0.00 0.000 0.016 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 05:40:00 18.00 20.81 0.00199 -10.70 0.00150 0.016 0.00
DATACENTER_BASEMENT_ZN_6 0.00 0.00 0.00 0.000 0.338 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 01:30:00 18.00 27.00 0.00850 -10.70 0.00150 0.338 0.00
The Design Load is the zone sensible load only. It does not include any system effects or ventilation loads.

System Design Air Flow Rates

Calculated cooling [m3/s] User cooling [m3/s] Calculated heating [m3/s] User heating [m3/s] Adjusted cooling [m3/s] Adjusted heating [m3/s] Adjusted main [m3/s] Calculated Heating Air Flow Ratio [] User Heating Air Flow Ratio []
VAV_BOT WITH REHEAT 10.39 10.39 2.72 2.72 10.3915 3.1277 10.3915 0.3010 0.3000
VAV_MID WITH REHEAT 97.93 97.93 40.54 40.54 97.9338 40.5431 97.9338 0.4140 0.3000
VAV_TOP WITH REHEAT 10.67 10.67 6.14 6.14 10.6653 6.1447 10.6653 0.5761 0.3000
CAV_BAS 5.96 5.96 1.20 1.20 5.9587 5.9587 5.9587 1.0000 1.0000
AIRLOOP DATACENTER BASEMENT 21.41 21.41 0.34 0.34 21.4116 21.4115 21.4116 1.0000 1.0000
AIRLOOP DATACENTER BOT 0.49 0.49 0.02 0.02 0.4934 0.4934 0.4934 1.0000 1.0000
AIRLOOP DATACENTER MID 4.73 4.73 0.16 0.16 4.7272 4.7272 4.7272 1.0000 1.0000
AIRLOOP DATACENTER TOP 0.48 0.48 0.02 0.02 0.4812 0.4812 0.4812 1.0000 1.0000


Plant Loop Coincident Design Fluid Flow Rate Adjustments

Previous Design Volume Flow Rate [m3/s] Algorithm Volume Flow Rate [m3/s] Coincident Design Volume Flow Rate [m3/s] Coincident Size Adjusted Peak Sizing Period Name Peak Day into Period {TIMESTAMP}[day] Peak Hour Of Day {TIMESTAMP}[hr] Peak Step Start Minute {TIMESTAMP}[min]
None                


Coil Sizing Summary

Coil Type HVAC Type HVAC Name Coil Final Gross Total Capacity [W] Coil Final Gross Sensible Capacity [W] Coil Final Reference Air Volume Flow Rate [m3/s] Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] Coil U-value Times Area Value [W/K] Design Day Name at Sensible Ideal Loads Peak Date/Time at Sensible Ideal Loads Peak Design Day Name at Air Flow Ideal Loads Peak Date/Time at Air Flow Ideal Loads Peak Coil Total Capacity at Ideal Loads Peak [W] Coil Sensible Capacity at Ideal Loads Peak [W] Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] Coil Entering Air Drybulb at Ideal Loads Peak [C] Coil Entering Air Wetbulb at Ideal Loads Peak [C] Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Coil Leaving Air Drybulb at Ideal Loads Peak [C] Coil Leaving Air Wetbulb at Ideal Loads Peak [C] Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Outdoor Air Drybulb at Ideal Loads Peak [C] Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Outdoor Air Wetbulb at Ideal Loads Peak [C] Outdoor Air Flow Percentage at Ideal Loads Peak [%] Zone Air Drybulb at Ideal Loads Peak [C] Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Zone Air Relative Humidity at Ideal Loads Peak [%] Zone Sensible Heat Gain at Ideal Loads Peak [W] Zone Latent Heat Gain at Ideal Loads Peak [W] Coil Total Capacity at Rating Conditions [W] Coil Sensible Capacity at Rating Conditions [W]
CORE_BOTTOM VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT CORE_BOTTOM VAV BOX 19871.005 19871.005 1.974460 0.00017384 400.584 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 05:40:00 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 05:40:00 19871.01 19871.01 1.974460 12.80 11.59 0.00800000 40.00 21.18 0.00800000 -10.70 0.00150390 -10.70 0.0000 21.00 0.00800000 51.6928 0.00 0.00 19944.27 19944.27
CORE_MID VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT CORE_MID VAV BOX 502362.850 502362.850 19.387971 0.00439489 12020.251 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 502362.85 502362.85 19.387971 12.80 11.59 0.00800000 40.00 21.18 0.00800000 -10.70 0.00150390 -10.70 0.0000 21.00 0.00800000 51.6928 307241.88 0.00 503994.47 503994.47
CORE_TOP VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT CORE_TOP VAV BOX 90567.173 90567.173 2.696739 0.00079232 2390.904 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 90567.17 90567.17 2.696739 12.80 11.59 0.00800000 40.00 21.18 0.00800000 -10.70 0.00150390 -10.70 0.0000 21.00 0.00800000 51.6928 63427.13 0.00 90881.63 90881.63
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_BOT_ZN_3 VAV BOX 16611.224 16611.224 0.495461 0.00014532 438.182 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 16611.22 16611.22 0.495461 12.80 11.59 0.00800000 40.00 21.18 0.00800000 -10.70 0.00150390 -10.70 0.0000 21.00 0.00724006 46.8471 11633.54 0.00 16666.44 16666.44
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_BOT_ZN_2 VAV BOX 11282.692 11282.692 0.336569 0.00009871 297.605 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 11282.69 11282.69 0.336569 12.80 11.59 0.00800000 40.00 21.18 0.00800000 -10.70 0.00150390 -10.70 0.0000 21.00 0.00729331 47.1873 7900.94 0.00 11320.08 11320.08
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_BOT_ZN_1 VAV BOX 18180.520 18180.520 0.542355 0.00015905 479.542 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 18180.52 18180.52 0.542355 12.80 11.59 0.00800000 40.00 21.18 0.00800000 -10.70 0.00150390 -10.70 0.0000 21.00 0.00736272 47.6304 12730.23 0.00 18240.70 18240.70
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_BOT_ZN_4 VAV BOX 9669.438 9669.438 0.325244 0.00008459 242.596 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 9669.44 9669.44 0.325244 12.80 11.59 0.00800000 40.00 21.18 0.00800000 -10.70 0.00150390 -10.70 0.0000 21.00 0.00699009 45.2490 6403.53 0.00 9699.52 9699.52
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_MID_ZN_3 VAV BOX 281179.942 281179.942 8.396771 0.00245988 7413.084 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 281179.94 281179.94 8.396771 12.80 11.59 0.00800000 40.00 21.18 0.00800000 -10.70 0.00150390 -10.70 0.0000 21.00 0.00719408 46.5569 196842.26 0.00 282085.34 282085.34
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_MID_ZN_2 VAV BOX 184302.046 184302.046 5.503929 0.00161235 4858.901 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 184302.05 184302.05 5.503929 12.80 11.59 0.00800000 40.00 21.18 0.00800000 -10.70 0.00150390 -10.70 0.0000 21.00 0.00718268 46.4843 129022.04 0.00 184894.96 184894.96
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_MID_ZN_1 VAV BOX 277679.966 277679.966 8.292115 0.00242927 7320.865 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 277679.97 277679.97 8.292115 12.80 11.59 0.00800000 40.00 21.18 0.00800000 -10.70 0.00150390 -10.70 0.0000 21.00 0.00718478 46.4974 194394.91 0.00 278574.50 278574.50
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_MID_ZN_4 VAV BOX 179958.255 179958.255 5.374079 0.00157435 4744.434 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 179958.26 179958.26 5.374079 12.80 11.59 0.00800000 40.00 21.18 0.00800000 -10.70 0.00150390 -10.70 0.0000 21.00 0.00716477 46.3697 125984.43 0.00 180537.57 180537.57
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_TOP_ZN_3 VAV BOX 35087.953 35087.953 1.048151 0.00030696 924.932 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 35087.95 35087.95 1.048151 12.80 11.59 0.00800000 40.00 21.18 0.00800000 -10.70 0.00150390 -10.70 0.0000 21.00 0.00720101 46.6034 24561.08 0.00 35199.97 35199.97
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_TOP_ZN_2 VAV BOX 22938.674 22938.674 0.685245 0.00020068 604.665 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 22938.67 22938.67 0.685245 12.80 11.59 0.00800000 40.00 21.18 0.00800000 -10.70 0.00150390 -10.70 0.0000 20.99 0.00718716 46.5151 16056.85 0.00 23011.85 23011.85
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_TOP_ZN_1 VAV BOX 34713.481 34713.481 1.036954 0.00030369 915.065 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 34713.48 34713.48 1.036954 12.80 11.59 0.00800000 40.00 21.18 0.00800000 -10.70 0.00150390 -10.70 0.0000 21.00 0.00719340 46.5547 24299.21 0.00 34824.33 34824.33
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_TOP_ZN_4 VAV BOX 22682.070 22682.070 0.677576 0.00019843 597.902 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 22682.07 22682.07 0.677576 12.80 11.59 0.00800000 40.00 21.18 0.00800000 -10.70 0.00150390 -10.70 0.0000 20.99 0.00717948 46.4660 15877.37 0.00 22754.44 22754.44
VAV_BOT WITH REHEAT COOLING COIL Coil:Cooling:Water AirLoopHVAC VAV_BOT WITH REHEAT 244927.464 -999.000 10.391517 0.01041978 -999.000 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:50:00 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 244927.46 189669.10 10.391517 26.03 18.47 0.01018467 11.06 11.06 0.00850000 32.10 0.01411964 23.13 24.4256 24.00 0.00886377 47.6684 138935.92 0.00 245231.41 182737.35
VAV_BOT WITH REHEAT HEATING COIL Coil:Heating:Water AirLoopHVAC VAV_BOT WITH REHEAT 72503.507 72503.507 3.117455 0.00063429 1172.862 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 07:50:00 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 72503.51 72503.51 3.117455 -6.43 -6.54 0.00212979 12.80 11.59 0.00800000 -10.70 0.00150390 -10.70 81.4187 21.02 0.00556581 36.0618 37219.18 0.00 65112.73 65112.73
VAV_MID WITH REHEAT COOLING COIL Coil:Cooling:Water AirLoopHVAC VAV_MID WITH REHEAT 2396783.593 -999.000 97.933768 0.10196471 -999.000 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 2396783.59 1815827.55 97.933768 26.20 18.67 0.01037155 10.96 10.96 0.00850000 32.10 0.01411964 23.13 25.9175 24.00 0.00896902 48.2276 1282250.96 0.00 2399946.43 1752373.90
VAV_MID WITH REHEAT HEATING COIL Coil:Heating:Water AirLoopHVAC VAV_MID WITH REHEAT 691595.113 691595.113 29.380131 0.00605038 11173.042 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 06:10:00 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 691595.11 691595.11 29.380131 -6.66 -6.66 0.00227778 12.80 11.59 0.00800000 -10.70 0.00150390 -10.70 86.3915 19.35 0.00677832 48.5850 468575.93 0.00 619456.56 619456.56
VAV_TOP WITH REHEAT COOLING COIL Coil:Cooling:Water AirLoopHVAC VAV_TOP WITH REHEAT 249517.119 -999.000 10.665346 0.01061503 -999.000 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 249517.12 193247.82 10.665346 25.93 18.42 0.01017121 11.06 11.06 0.00850000 32.10 0.01411964 23.13 23.7985 24.00 0.00893808 48.0639 146713.40 0.00 249825.60 186122.94
VAV_TOP WITH REHEAT HEATING COIL Coil:Heating:Water AirLoopHVAC VAV_TOP WITH REHEAT 68252.181 68252.181 3.199604 0.00059710 1113.657 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 05:20:00 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 68252.18 68252.18 3.199604 -4.84 -4.84 0.00266231 12.80 11.59 0.00800000 -10.70 0.00150390 -10.70 79.3283 17.60 0.00668685 53.5154 50510.79 0.00 62426.48 62426.48
CAV_BAS COOLING COIL Coil:Cooling:Water AirLoopHVAC CAV_BAS 123071.043 -999.000 5.958699 0.00523573 -999.000 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 123071.04 96015.84 5.958699 24.58 17.81 0.00996654 11.42 11.42 0.00850000 26.62 0.01410980 21.57 20.1412 24.00 0.00892156 47.9745 82706.28 0.00 123247.42 92547.42
CAV_BAS HEATING COIL Coil:Heating:Water AirLoopHVAC CAV_BAS 303799.481 303799.481 5.958699 0.00265777 6686.537 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 303799.48 303799.48 5.958699 -2.16 -4.93 0.00150390 40.00 21.18 0.00800000 -10.70 0.00150390 -10.70 20.1412 23.73 0.00150390 8.3149 0.00 0.00 250775.49 250775.49
AIRLOOP DATACENTER BASEMENT COOLING COIL COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoopHVAC AIRLOOP DATACENTER BASEMENT 433170.493 312730.657 21.411648 0.01060832 -999.000 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 07:10:00 405440.55 397761.15 -999.0 28.48 18.03 0.00863030 12.80 12.09 0.00850000 32.10 0.01411964 23.13 -999.0000 27.00 0.00854207 38.4633 373070.39 0.00 -999.00 -999.00
AIRLOOP DATACENTER BOT COOLING COIL COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoopHVAC AIRLOOP DATACENTER BOT 9910.600 7177.440 0.493358 0.00024271 -999.000 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 18:40:00 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 18:40:00 9264.45 8912.59 -999.0 28.03 17.99 0.00875940 12.80 12.09 0.00850000 29.58 0.01411511 22.43 -999.0000 27.00 0.00858414 38.6477 8605.13 0.00 -999.00 -999.00
AIRLOOP DATACENTER MID COOLING COIL COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoopHVAC AIRLOOP DATACENTER MID 95118.132 68824.672 4.727151 0.00232944 -999.000 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 18:40:00 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 18:40:00 88941.31 85424.47 -999.0 28.03 18.00 0.00877056 12.80 12.09 0.00850000 29.58 0.01411511 22.43 -999.0000 27.00 0.00858778 38.6640 82450.39 0.00 -999.00 -999.00
AIRLOOP DATACENTER TOP COOLING COIL COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoopHVAC AIRLOOP DATACENTER TOP 9678.207 7004.391 0.481181 0.00023702 -999.000 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 18:30:00 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 18:40:00 9049.14 8697.49 -999.0 28.04 18.00 0.00876579 12.80 12.09 0.00850000 29.77 0.01411544 22.48 -999.0000 27.00 0.00858614 38.6567 8392.04 0.00 -999.00 -999.00
AIRLOOP DATACENTER BASEMENT HEATING COIL COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoopHVAC AIRLOOP DATACENTER BASEMENT 433170.493 433170.493 21.411648 0.01060832 -999.000 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 433170.49 433170.49 21.411648 -10.70 -10.70 0.00150390 40.00 21.18 0.00800000 -10.70 0.00150390 -10.70 1.5804 27.00 0.00850000 38.2706 0.00 0.00 -999.00 -999.00
AIRLOOP DATACENTER BOT HEATING COIL COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoopHVAC AIRLOOP DATACENTER BOT 9910.600 9910.600 0.493358 0.00024271 -999.000 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 9910.60 9910.60 0.493358 -10.70 -10.70 0.00150390 40.00 21.18 0.00800000 -10.70 0.00150390 -10.70 3.1686 25.81 0.00525217 25.4929 0.00 0.00 -999.00 -999.00
AIRLOOP DATACENTER MID HEATING COIL COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoopHVAC AIRLOOP DATACENTER MID 95118.132 95118.132 4.727151 0.00232944 -999.000 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 95118.13 95118.13 4.727151 -10.70 -10.70 0.00150390 40.00 21.18 0.00800000 -10.70 0.00150390 -10.70 3.3069 23.81 0.00199515 10.9742 0.00 0.00 -999.00 -999.00
AIRLOOP DATACENTER TOP HEATING COIL COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoopHVAC AIRLOOP DATACENTER TOP 9678.207 9678.207 0.481181 0.00023702 -999.000 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 9678.21 9678.21 0.481181 -10.70 -10.70 0.00150390 40.00 21.18 0.00800000 -10.70 0.00150390 -10.70 3.2487 22.76 0.00199483 11.6897 0.00 0.00 -999.00 -999.00
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL Coil:Heating:Electric AirLoopHVAC AIRLOOP DATACENTER BASEMENT 20749.821 20749.821 -999.0 -999.0 -999.000 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 20749.82 20749.82 21.411648 -0.17 -0.17 0.00838943 40.00 21.18 0.00800000 -10.70 0.00150390 -10.70 1.5804 27.00 0.00850000 38.2706 0.00 0.00 -999.00 -999.00
AIRLOOP DATACENTER BOT_SUPPHEATCOIL Coil:Heating:Electric AirLoopHVAC AIRLOOP DATACENTER BOT 958.556 958.556 -999.0 -999.0 -999.000 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 958.56 958.56 0.493358 -0.34 -0.34 0.00513340 40.00 21.18 0.00800000 -10.70 0.00150390 -10.70 3.1686 25.81 0.00525217 25.4929 0.00 0.00 -999.00 -999.00
AIRLOOP DATACENTER MID_SUPPHEATCOIL Coil:Heating:Electric AirLoopHVAC AIRLOOP DATACENTER MID 9585.558 9585.558 -999.0 -999.0 -999.000 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 9585.56 9585.56 4.727151 -0.35 -3.02 0.00197890 40.00 21.18 0.00800000 -10.70 0.00150390 -10.70 3.3069 23.81 0.00199515 10.9742 0.00 0.00 -999.00 -999.00
AIRLOOP DATACENTER TOP_SUPPHEATCOIL Coil:Heating:Electric AirLoopHVAC AIRLOOP DATACENTER TOP 958.556 958.556 -999.0 -999.0 -999.000 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 958.56 958.56 0.481181 -0.35 -3.02 0.00197888 40.00 21.18 0.00800000 -10.70 0.00150390 -10.70 3.2487 22.76 0.00199483 11.6897 0.00 0.00 -999.00 -999.00



Table of Contents

Report: Coil Sizing Details

For: Entire Facility

Timestamp: 2023-10-16 08:43:34

Coils

Coil Type Coil Location HVAC Type HVAC Name Zone Name(s) System Sizing Method Concurrence System Sizing Method Capacity System Sizing Method Air Flow Autosized Coil Capacity? Autosized Coil Airflow? Autosized Coil Water Flow? OA Pretreated prior to coil inlet? Coil Final Gross Total Capacity [W] Coil Final Gross Sensible Capacity [W] Coil Final Reference Air Volume Flow Rate [m3/s] Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] Coil U-value Times Area Value [W/K] Terminal Unit Reheat Coil Multiplier DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio Moist Air Heat Capacity [J/kg-K] Dry Air Heat Capacity [J/kg-K] Standard Air Density Adjusted for Elevation [kg/m3] Supply Fan Name for Coil Supply Fan Type for Coil Supply Fan Maximum Air Volume Flow Rate [m3/s] Supply Fan Maximum Air Mass Flow Rate [kg/s] Plant Name for Coil Plant Fluid Specific Heat Capacity [J/kg-K] Plant Fluid Density [kg/m3] Plant Maximum Fluid Mass Flow Rate [kg/s] Plant Design Fluid Return Temperature [C] Plant Design Fluid Supply Temperature [C] Plant Design Fluid Temperature Difference [deltaC] Plant Design Capacity [W] Coil Capacity Percentage of Plant Design Capacity [%] Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] Design Day Name at Sensible Ideal Loads Peak Date/Time at Sensible Ideal Loads Peak Design Day Name at Total Ideal Loads Peak Date/Time at Total Ideal Loads Peak Design Day Name at Air Flow Ideal Loads Peak Date/Time at Air Flow Ideal Loads Peak Peak Load Type to Size On Coil Total Capacity at Ideal Loads Peak [W] Coil Sensible Capacity at Ideal Loads Peak [W] Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] Coil Entering Air Drybulb at Ideal Loads Peak [C] Coil Entering Air Wetbulb at Ideal Loads Peak [C] Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] Coil Leaving Air Drybulb at Ideal Loads Peak [C] Coil Leaving Air Wetbulb at Ideal Loads Peak [C] Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] Supply Fan Air Heat Gain at Ideal Loads Peak [W] Coil and Fan Net Total Capacity at Ideal Loads Peak [W] Outdoor Air Drybulb at Ideal Loads Peak [C] Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Outdoor Air Wetbulb at Ideal Loads Peak [C] Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] Outdoor Air Flow Percentage at Ideal Loads Peak [%] System Return Air Drybulb at Ideal Loads Peak [C] System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Zone Air Drybulb at Ideal Loads Peak [C] Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Zone Air Relative Humidity at Ideal Loads Peak [%] Zone Sensible Heat Gain at Ideal Loads Peak [W] Zone Latent Heat Gain at Ideal Loads Peak [W] Coil Total Capacity at Rating Conditions [W] Coil Sensible Capacity at Rating Conditions [W] Coil Air Mass Flow Rate at Rating Conditions [kg/s] Coil Entering Air Drybulb at Rating Conditions [C] Coil Entering Air Wetbulb at Rating Conditions [C] Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] Coil Leaving Air Drybulb at Rating Conditions [C] Coil Leaving Air Wetbulb at Rating Conditions [C] Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K]
CORE_BOTTOM VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT CORE_BOTTOM VAV BOX CORE_BOTTOM N/A N/A N/A Yes Yes Yes No 19871.005 19871.005 1.974460 0.00017384 400.584 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2036 unknown unknown -999.0 -999.0   4197.9300 999.8980 24.87134522 54.44 82.22 27.78 2900458.86 0.6851 0.698887 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 05:40:00 unknown unknown NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 05:40:00 Sensible 19871.01 19871.01 1.0000 2.37644970 1.974460 12.80 11.59 0.00800000 33059.8 40.00 21.18 0.00800000 60796.0 0.17382249 60.00 32.22 27.78 0.000 19871.01 -10.70 0.00150390 -10.70 0.00000000 0.0000 21.00 0.00800000 21.00 0.00800000 51.6928 0.00 0.00 19944.27 19944.27 2.37644970 12.80 11.60 0.00800000 33059.8 21.03 14.86 0.00800000 41452.3
CORE_MID VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT CORE_MID VAV BOX CORE_MID N/A N/A N/A Yes Yes Yes No 502362.850 502362.850 19.387971 0.00439489 12020.251 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2036 unknown unknown -999.0 -999.0   4197.9300 999.8980 24.87134522 54.44 82.22 27.78 2900458.86 17.3201 17.668691 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 502362.85 502362.85 1.0000 23.33526513 19.387971 12.80 11.59 0.00800000 33059.8 40.00 21.18 0.00800000 60796.0 4.39444104 60.00 32.22 27.78 0.000 502362.85 -10.70 0.00150390 -10.70 0.00000000 0.0000 20.87 0.00800000 21.00 0.00800000 51.6928 307241.88 0.00 503994.47 503994.47 23.33526513 12.80 11.60 0.00800000 33059.8 33.98 19.33 0.00800000 54657.8
CORE_TOP VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT CORE_TOP VAV BOX CORE_TOP N/A N/A N/A Yes Yes Yes No 90567.173 90567.173 2.696739 0.00079232 2390.904 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2036 unknown unknown -999.0 -999.0   4197.9300 999.8980 24.87134522 54.44 82.22 27.78 2900458.86 3.1225 3.185354 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 90567.17 90567.17 1.0000 3.24578138 2.696739 12.80 11.59 0.00800000 33059.8 40.00 21.18 0.00800000 60796.0 0.79224031 60.00 32.22 27.78 0.000 90567.17 -10.70 0.00150390 -10.70 0.00000000 0.0000 20.91 0.00800000 21.00 0.00800000 51.6928 63427.13 0.00 90881.63 90881.63 3.24578138 12.80 11.60 0.00800000 33059.8 40.26 21.26 0.00800000 61059.8
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_BOT_ZN_3 VAV BOX PERIMETER_BOT_ZN_3 N/A N/A N/A Yes Yes Yes No 16611.224 16611.224 0.495461 0.00014532 438.182 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2036 unknown unknown -999.0 -999.0   4197.9300 999.8980 24.87134522 54.44 82.22 27.78 2900458.86 0.5727 0.584236 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 16611.22 16611.22 1.0000 0.59633417 0.495461 12.80 11.59 0.00800000 33059.8 40.00 21.18 0.00800000 60796.0 0.14530741 60.00 32.22 27.78 0.000 16611.22 -10.70 0.00150390 -10.70 0.00000000 0.0000 20.95 0.00724006 21.00 0.00724006 46.8471 11633.54 0.00 16666.44 16666.44 0.59633417 12.80 11.60 0.00800000 33059.8 40.21 21.24 0.00800000 61008.0
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_BOT_ZN_2 VAV BOX PERIMETER_BOT_ZN_2 N/A N/A N/A Yes Yes Yes No 11282.692 11282.692 0.336569 0.00009871 297.605 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2036 unknown unknown -999.0 -999.0   4197.9300 999.8980 24.87134522 54.44 82.22 27.78 2900458.86 0.3890 0.396826 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 11282.69 11282.69 1.0000 0.40509258 0.336569 12.80 11.59 0.00800000 33059.8 40.00 21.18 0.00800000 60796.0 0.09869584 60.00 32.22 27.78 0.000 11282.69 -10.70 0.00150390 -10.70 0.00000000 0.0000 20.95 0.00729331 21.00 0.00729331 47.1873 7900.94 0.00 11320.08 11320.08 0.40509258 12.80 11.60 0.00800000 33059.8 40.20 21.24 0.00800000 61004.2
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_BOT_ZN_1 VAV BOX PERIMETER_BOT_ZN_1 N/A N/A N/A Yes Yes Yes No 18180.520 18180.520 0.542355 0.00015905 479.542 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2036 unknown unknown -999.0 -999.0   4197.9300 999.8980 24.87134522 54.44 82.22 27.78 2900458.86 0.6268 0.639430 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 18180.52 18180.52 1.0000 0.65277611 0.542355 12.80 11.59 0.00800000 33059.8 40.00 21.18 0.00800000 60796.0 0.15903489 60.00 32.22 27.78 0.000 18180.52 -10.70 0.00150390 -10.70 0.00000000 0.0000 20.95 0.00736272 21.00 0.00736272 47.6304 12730.23 0.00 18240.70 18240.70 0.65277611 12.80 11.60 0.00800000 33059.8 40.20 21.24 0.00800000 61003.1
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_BOT_ZN_4 VAV BOX PERIMETER_BOT_ZN_4 N/A N/A N/A Yes Yes Yes No 9669.438 9669.438 0.325244 0.00008459 242.596 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2036 unknown unknown -999.0 -999.0   4197.9300 999.8980 24.87134522 54.44 82.22 27.78 2900458.86 0.3334 0.340085 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 9669.44 9669.44 1.0000 0.39146216 0.325244 12.80 11.59 0.00800000 33059.8 40.00 21.18 0.00800000 60796.0 0.08458383 60.00 32.22 27.78 0.000 9669.44 -10.70 0.00150390 -10.70 0.00000000 0.0000 20.91 0.00699009 21.00 0.00699009 45.2490 6403.53 0.00 9699.52 9699.52 0.39146216 12.80 11.60 0.00800000 33059.8 37.10 20.31 0.00800000 57837.5
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_MID_ZN_3 VAV BOX PERIMETER_MID_ZN_3 N/A N/A N/A Yes Yes Yes No 281179.942 281179.942 8.396771 0.00245988 7413.084 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2036 unknown unknown -999.0 -999.0   4197.9300 999.8980 24.87134522 54.44 82.22 27.78 2900458.86 9.6943 9.889428 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 281179.94 281179.94 1.0000 10.10631168 8.396771 12.80 11.59 0.00800000 33059.8 40.00 21.18 0.00800000 60796.0 2.45963386 60.00 32.22 27.78 0.000 281179.94 -10.70 0.00150390 -10.70 0.00000000 0.0000 20.94 0.00719408 21.00 0.00719408 46.5569 196842.26 0.00 282085.34 282085.34 10.10631168 12.80 11.60 0.00800000 33059.8 40.17 21.23 0.00800000 60971.6
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_MID_ZN_2 VAV BOX PERIMETER_MID_ZN_2 N/A N/A N/A Yes Yes Yes No 184302.046 184302.046 5.503929 0.00161235 4858.901 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2036 unknown unknown -999.0 -999.0   4197.9300 999.8980 24.87134522 54.44 82.22 27.78 2900458.86 6.3542 6.482119 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 184302.05 184302.05 1.0000 6.62450157 5.503929 12.80 11.59 0.00800000 33059.8 40.00 21.18 0.00800000 60796.0 1.61219022 60.00 32.22 27.78 0.000 184302.05 -10.70 0.00150390 -10.70 0.00000000 0.0000 20.94 0.00718268 21.00 0.00718268 46.4843 129022.04 0.00 184894.96 184894.96 6.62450157 12.80 11.60 0.00800000 33059.8 40.17 21.23 0.00800000 60970.6
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_MID_ZN_1 VAV BOX PERIMETER_MID_ZN_1 N/A N/A N/A Yes Yes Yes No 277679.966 277679.966 8.292115 0.00242927 7320.865 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2036 unknown unknown -999.0 -999.0   4197.9300 999.8980 24.87134522 54.44 82.22 27.78 2900458.86 9.5737 9.766330 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 277679.97 277679.97 1.0000 9.98034753 8.292115 12.80 11.59 0.00800000 33059.8 40.00 21.18 0.00800000 60796.0 2.42901766 60.00 32.22 27.78 0.000 277679.97 -10.70 0.00150390 -10.70 0.00000000 0.0000 20.95 0.00718478 21.00 0.00718478 46.4974 194394.91 0.00 278574.50 278574.50 9.98034753 12.80 11.60 0.00800000 33059.8 40.17 21.23 0.00800000 60972.1
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_MID_ZN_4 VAV BOX PERIMETER_MID_ZN_4 N/A N/A N/A Yes Yes Yes No 179958.255 179958.255 5.374079 0.00157435 4744.434 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2036 unknown unknown -999.0 -999.0   4197.9300 999.8980 24.87134522 54.44 82.22 27.78 2900458.86 6.2045 6.329343 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 179958.26 179958.26 1.0000 6.46821444 5.374079 12.80 11.59 0.00800000 33059.8 40.00 21.18 0.00800000 60796.0 1.57419272 60.00 32.22 27.78 0.000 179958.26 -10.70 0.00150390 -10.70 0.00000000 0.0000 20.94 0.00716477 21.00 0.00716477 46.3697 125984.43 0.00 180537.57 180537.57 6.46821444 12.80 11.60 0.00800000 33059.8 40.17 21.23 0.00800000 60971.3
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_TOP_ZN_3 VAV BOX PERIMETER_TOP_ZN_3 N/A N/A N/A Yes Yes Yes No 35087.953 35087.953 1.048151 0.00030696 924.932 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2036 unknown unknown -999.0 -999.0   4197.9300 999.8980 24.87134522 54.44 82.22 27.78 2900458.86 1.2097 1.234084 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 35087.95 35087.95 1.0000 1.26154959 1.048151 12.80 11.59 0.00800000 33059.8 40.00 21.18 0.00800000 60796.0 0.30693341 60.00 32.22 27.78 0.000 35087.95 -10.70 0.00150390 -10.70 0.00000000 0.0000 20.94 0.00720101 21.00 0.00720101 46.6034 24561.08 0.00 35199.97 35199.97 1.26154959 12.80 11.60 0.00800000 33059.8 40.16 21.23 0.00800000 60962.0
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_TOP_ZN_2 VAV BOX PERIMETER_TOP_ZN_2 N/A N/A N/A Yes Yes Yes No 22938.674 22938.674 0.685245 0.00020068 604.665 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2036 unknown unknown -999.0 -999.0   4197.9300 999.8980 24.87134522 54.44 82.22 27.78 2900458.86 0.7909 0.806780 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 22938.67 22938.67 1.0000 0.82475711 0.685245 12.80 11.59 0.00800000 33059.8 40.00 21.18 0.00800000 60796.0 0.20065706 60.00 32.22 27.78 0.000 22938.67 -10.70 0.00150390 -10.70 0.00000000 0.0000 20.94 0.00718716 20.99 0.00718716 46.5151 16056.85 0.00 23011.85 23011.85 0.82475711 12.80 11.60 0.00800000 33059.8 40.16 21.23 0.00800000 60961.2
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_TOP_ZN_1 VAV BOX PERIMETER_TOP_ZN_1 N/A N/A N/A Yes Yes Yes No 34713.481 34713.481 1.036954 0.00030369 915.065 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2036 unknown unknown -999.0 -999.0   4197.9300 999.8980 24.87134522 54.44 82.22 27.78 2900458.86 1.1968 1.220914 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 34713.48 34713.48 1.0000 1.24807249 1.036954 12.80 11.59 0.00800000 33059.8 40.00 21.18 0.00800000 60796.0 0.30365770 60.00 32.22 27.78 0.000 34713.48 -10.70 0.00150390 -10.70 0.00000000 0.0000 20.94 0.00719340 21.00 0.00719340 46.5547 24299.21 0.00 34824.33 34824.33 1.24807249 12.80 11.60 0.00800000 33059.8 40.16 21.23 0.00800000 60962.3
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_TOP_ZN_4 VAV BOX PERIMETER_TOP_ZN_4 N/A N/A N/A Yes Yes Yes No 22682.070 22682.070 0.677576 0.00019843 597.902 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2036 unknown unknown -999.0 -999.0   4197.9300 999.8980 24.87134522 54.44 82.22 27.78 2900458.86 0.7820 0.797755 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 22682.07 22682.07 1.0000 0.81552741 0.677576 12.80 11.59 0.00800000 33059.8 40.00 21.18 0.00800000 60796.0 0.19841241 60.00 32.22 27.78 0.000 22682.07 -10.70 0.00150390 -10.70 0.00000000 0.0000 20.94 0.00717948 20.99 0.00717948 46.4660 15877.37 0.00 22754.44 22754.44 0.81552741 12.80 11.60 0.00800000 33059.8 40.16 21.23 0.00800000 60961.3
VAV_BOT WITH REHEAT COOLING COIL Coil:Cooling:Water AirLoop AirLoopHVAC VAV_BOT WITH REHEAT CORE_BOTTOM; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_4; Coincident CoolingDesignCapacity N/A Yes Yes Yes No 244927.464 -999.000 10.391517 0.01041978 -999.000 -999.0000 1.00000 1.00000 1023.7728 1004.8586 1.2036 VAV_BOT WITH REHEAT FAN Fan:VariableVolume 10.391517 12.50717726   4197.9300 999.8980 128.22217562 12.27 6.67 5.60 3014299.22 8.1255 8.125519 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:50:00 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:50:00 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 Sensible 244927.46 189669.10 1.0000 12.50717726 10.391517 26.03 18.47 0.01018467 52124.7 11.06 11.06 0.00850000 32541.8 10.41871758 6.67 12.27 5.60 22336.197 222591.27 32.10 0.01411964 23.13 2.53819000 24.4256 24.00 0.00886377 24.00 0.00886377 47.6684 138935.92 0.00 245231.41 182737.35 12.50717726 26.03 18.48 0.01018467 52124.7 11.76 11.37 0.00820407 32517.5
VAV_BOT WITH REHEAT HEATING COIL Coil:Heating:Water AirLoop AirLoopHVAC VAV_BOT WITH REHEAT CORE_BOTTOM; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_4; Coincident HeatingDesignCapacity N/A Yes Yes Yes No 72503.507 72503.507 3.117455 0.00063429 1172.862 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.2036 VAV_BOT WITH REHEAT FAN Fan:VariableVolume 10.391517 12.50717726   4197.9300 999.8980 24.87134522 54.44 82.22 27.78 2900458.86 2.4997 2.550033 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 07:50:00 unknown unknown NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 72503.51 72503.51 1.0000 3.75215318 3.117455 -6.43 -6.54 0.00212979 -1159.8 12.80 11.59 0.00800000 33059.8 0.63422760 60.00 32.22 27.78 0.000 72503.51 -10.70 0.00150390 -10.70 2.53819000 81.4187 12.28 0.00487231 21.02 0.00556581 36.0618 37219.18 0.00 65112.73 65112.73 3.75215318 2.80 -0.98 0.00212979 8151.1 20.00 8.41 0.00212979 25504.6
VAV_MID WITH REHEAT COOLING COIL Coil:Cooling:Water AirLoop AirLoopHVAC VAV_MID WITH REHEAT CORE_MID; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_4; Coincident CoolingDesignCapacity N/A Yes Yes Yes No 2396783.593 -999.000 97.933768 0.10196471 -999.000 -999.0000 1.00000 1.00000 1024.1202 1004.8586 1.2036 VAV_MID WITH REHEAT FAN Fan:VariableVolume 97.933768 117.87259222   4197.9300 999.8980 128.22217562 12.27 6.67 5.60 3014299.22 79.5138 79.513791 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 Sensible 2396783.59 1815827.55 1.0000 117.87259222 97.933768 26.20 18.67 0.01037155 52774.9 10.96 10.96 0.00850000 32441.3 101.95431323 6.67 12.27 5.60 222465.686 2174317.91 32.10 0.01411964 23.13 25.38195000 25.9175 24.00 0.00896902 24.00 0.00896902 48.2276 1282250.96 0.00 2399946.43 1752373.90 117.87259222 26.20 18.68 0.01037155 52774.9 11.69 11.32 0.00819376 32414.4
VAV_MID WITH REHEAT HEATING COIL Coil:Heating:Water AirLoop AirLoopHVAC VAV_MID WITH REHEAT CORE_MID; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_4; Coincident HeatingDesignCapacity N/A Yes Yes Yes No 691595.113 691595.113 29.380131 0.00605038 11173.042 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.2036 VAV_MID WITH REHEAT FAN Fan:VariableVolume 97.933768 117.87259222   4197.9300 999.8980 24.87134522 54.44 82.22 27.78 2900458.86 23.8443 24.324211 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 06:10:00 unknown unknown NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 691595.11 691595.11 1.0000 35.36177767 29.380131 -6.66 -6.66 0.00227778 -1027.0 12.80 11.59 0.00800000 33059.8 6.04975855 60.00 32.22 27.78 0.000 691595.11 -10.70 0.00150390 -10.70 25.38195000 86.3915 18.96 0.00719069 19.35 0.00677832 48.5850 468575.93 0.00 619456.56 619456.56 35.36177767 2.80 -0.75 0.00227778 8522.0 20.16 8.66 0.00227778 26039.7
VAV_TOP WITH REHEAT COOLING COIL Coil:Cooling:Water AirLoop AirLoopHVAC VAV_TOP WITH REHEAT CORE_TOP; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_4; Coincident CoolingDesignCapacity N/A Yes Yes Yes No 249517.119 -999.000 10.665346 0.01061503 -999.000 -999.0000 1.00000 1.00000 1023.7478 1004.8586 1.2036 VAV_TOP WITH REHEAT FAN Fan:VariableVolume 10.665346 12.83675683   4197.9300 999.8980 128.22217562 12.27 6.67 5.60 3014299.22 8.2778 8.277782 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 Sensible 249517.12 193247.82 1.0000 12.83675683 10.665346 25.93 18.42 0.01017121 51979.5 11.06 11.06 0.00850000 32541.7 10.61395223 6.67 12.27 5.60 22924.783 226592.34 32.10 0.01411964 23.13 2.53819000 23.7985 24.00 0.00893808 24.00 0.00893808 48.0639 146713.40 0.00 249825.60 186122.94 12.83675683 25.93 18.43 0.01017121 51979.5 11.76 11.37 0.00820415 32517.7
VAV_TOP WITH REHEAT HEATING COIL Coil:Heating:Water AirLoop AirLoopHVAC VAV_TOP WITH REHEAT CORE_TOP; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_4; Coincident HeatingDesignCapacity N/A Yes Yes Yes No 68252.181 68252.181 3.199604 0.00059710 1113.657 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.2036 VAV_TOP WITH REHEAT FAN Fan:VariableVolume 10.665346 12.83675683   4197.9300 999.8980 24.87134522 54.44 82.22 27.78 2900458.86 2.3532 2.400509 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 05:20:00 unknown unknown NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 68252.18 68252.18 1.0000 3.85102705 3.199604 -4.84 -4.84 0.00266231 1773.5 12.80 11.59 0.00800000 33059.8 0.59703895 60.00 32.22 27.78 0.000 68252.18 -10.70 0.00150390 -10.70 2.53819000 79.3283 17.66 0.00710772 17.60 0.00668685 53.5154 50510.79 0.00 62426.48 62426.48 3.85102705 2.80 0.03 0.00266231 9485.7 18.85 8.49 0.00266231 25696.0
CAV_BAS COOLING COIL Coil:Cooling:Water AirLoop AirLoopHVAC CAV_BAS BASEMENT Coincident CoolingDesignCapacity N/A Yes Yes Yes No 123071.043 -999.000 5.958699 0.00523573 -999.000 -999.0000 1.00000 1.00000 1023.3673 1004.8586 1.2036 CAV_BAS FAN Fan:ConstantVolume 5.958699 7.17186018   4197.9300 999.8980 128.22217562 12.27 6.67 5.60 3014299.22 4.0829 4.082907 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 Sensible 123071.04 96015.84 1.0000 7.17186018 5.958699 24.58 17.81 0.00996654 50077.4 11.42 11.42 0.00850000 32917.1 5.23519258 6.67 12.27 5.60 10103.894 112967.15 26.62 0.01410980 21.57 1.20015641 20.1412 24.06 0.00892156 24.00 0.00892156 47.9745 82706.28 0.00 123247.42 92547.42 7.17186018 24.58 17.82 0.00996654 50077.4 11.97 11.52 0.00827003 32892.5
CAV_BAS HEATING COIL Coil:Heating:Water AirLoop AirLoopHVAC CAV_BAS BASEMENT Coincident HeatingDesignCapacity N/A Yes Yes Yes No 303799.481 303799.481 5.958699 0.00265777 6686.537 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.2036 CAV_BAS FAN Fan:ConstantVolume 5.958699 7.17186018   4197.9300 999.8980 24.87134522 54.44 82.22 27.78 2900458.86 10.4742 10.684984 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 unknown unknown NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 Sensible 303799.48 303799.48 1.0000 7.17186018 5.958699 -2.16 -4.93 0.00150390 1589.6 40.00 21.18 0.00800000 60796.0 2.65749927 60.00 32.22 27.78 0.000 303799.48 -10.70 0.00150390 -10.70 1.20015641 20.1412 0.00 0.00150390 23.73 0.00150390 8.3149 0.00 0.00 250775.49 250775.49 7.17186018 12.80 4.04 0.00150390 16658.9 47.50 18.54 0.00150390 51625.5
AIRLOOP DATACENTER BASEMENT COOLING COIL COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoop AirLoopHVAC AIRLOOP DATACENTER BASEMENT DATACENTER_BASEMENT_ZN_6 Coincident CoolingDesignCapacity N/A Yes No unknown No 433170.493 312730.657 21.411648 0.01060832 -999.000 -999.0000 -999.00000 -999.00000 1020.8833 1004.8586 1.2036 unknown unknown -999.0 -999.0   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 07:10:00 Sensible 405440.55 397761.15 0.9360 -999.0 -999.0 28.48 18.03 0.00863030 50657.8 12.80 12.09 0.00850000 34322.2 -999.0 -999.00 -999.00 -999.00 0.000 405440.55 32.10 0.01411964 23.13 0.33839277 -999.0000 27.00 0.00854207 27.00 0.00854207 38.4633 373070.39 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
AIRLOOP DATACENTER BOT COOLING COIL COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoop AirLoopHVAC AIRLOOP DATACENTER BOT DATACENTER_BOT_ZN_6 Coincident CoolingDesignCapacity N/A Yes No unknown No 9910.600 7177.440 0.493358 0.00024271 -999.000 -999.0000 -999.00000 -999.00000 1021.1233 1004.8586 1.2036 unknown unknown -999.0 -999.0   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 18:40:00 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 18:40:00 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 18:40:00 Sensible 9264.45 8912.59 0.9348 -999.0 -999.0 28.03 17.99 0.00875940 50525.7 12.80 12.09 0.00850000 34322.2 -999.0 -999.00 -999.00 -999.00 0.000 9264.45 29.58 0.01411511 22.43 0.01563234 -999.0000 27.00 0.00858414 27.00 0.00858414 38.6477 8605.13 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
AIRLOOP DATACENTER MID COOLING COIL COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoop AirLoopHVAC AIRLOOP DATACENTER MID DATACENTER_MID_ZN_6 Coincident CoolingDesignCapacity N/A Yes No unknown No 95118.132 68824.672 4.727151 0.00232944 -999.000 -999.0000 -999.00000 -999.00000 1021.1440 1004.8586 1.2036 unknown unknown -999.0 -999.0   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 18:40:00 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 18:40:00 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 18:40:00 Sensible 88941.31 85424.47 0.9351 -999.0 -999.0 28.03 18.00 0.00877056 50557.8 12.80 12.09 0.00850000 34322.2 -999.0 -999.00 -999.00 -999.00 0.000 88941.31 29.58 0.01411511 22.43 0.15632344 -999.0000 27.00 0.00858778 27.00 0.00858778 38.6640 82450.39 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
AIRLOOP DATACENTER TOP COOLING COIL COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoop AirLoopHVAC AIRLOOP DATACENTER TOP DATACENTER_TOP_ZN_6 Coincident CoolingDesignCapacity N/A Yes No unknown No 9678.207 7004.391 0.481181 0.00023702 -999.000 -999.0000 -999.00000 -999.00000 1021.1352 1004.8586 1.2036 unknown unknown -999.0 -999.0   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 18:30:00 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 18:30:00 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 18:40:00 Sensible 9049.14 8697.49 0.9350 -999.0 -999.0 28.04 18.00 0.00876579 50550.2 12.80 12.09 0.00850000 34322.2 -999.0 -999.00 -999.00 -999.00 0.000 9049.14 29.77 0.01411544 22.48 0.01563234 -999.0000 27.00 0.00858614 27.00 0.00858614 38.6567 8392.04 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
AIRLOOP DATACENTER BASEMENT HEATING COIL COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoop AirLoopHVAC AIRLOOP DATACENTER BASEMENT DATACENTER_BASEMENT_ZN_6 Coincident HeatingDesignCapacity N/A Yes No unknown No 433170.493 433170.493 21.411648 0.01060832 -999.000 -999.0000 -999.00000 -999.00000 1019.7116 1004.8586 1.2036 unknown unknown -999.0 -999.0   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 unknown unknown NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 Sensible 433170.49 433170.49 1.0000 25.77095206 21.411648 -10.70 -10.70 0.00150390 -7020.5 40.00 21.18 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 433170.49 -10.70 0.00150390 -10.70 0.33839277 1.5804 0.00 0.00850000 27.00 0.00850000 38.2706 0.00 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
AIRLOOP DATACENTER BOT HEATING COIL COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoop AirLoopHVAC AIRLOOP DATACENTER BOT DATACENTER_BOT_ZN_6 Coincident HeatingDesignCapacity N/A Yes No unknown No 9910.600 9910.600 0.493358 0.00024271 -999.000 -999.0000 -999.00000 -999.00000 1019.7116 1004.8586 1.2036 unknown unknown -999.0 -999.0   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 unknown unknown NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 Sensible 9910.60 9910.60 1.0000 0.59380328 0.493358 -10.70 -10.70 0.00150390 -7020.5 40.00 21.18 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 9910.60 -10.70 0.00150390 -10.70 0.01563234 3.1686 0.00 0.00525217 25.81 0.00525217 25.4929 0.00 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
AIRLOOP DATACENTER MID HEATING COIL COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoop AirLoopHVAC AIRLOOP DATACENTER MID DATACENTER_MID_ZN_6 Coincident HeatingDesignCapacity N/A Yes No unknown No 95118.132 95118.132 4.727151 0.00232944 -999.000 -999.0000 -999.00000 -999.00000 1019.7116 1004.8586 1.2036 unknown unknown -999.0 -999.0   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 unknown unknown NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 Sensible 95118.13 95118.13 1.0000 5.68957549 4.727151 -10.70 -10.70 0.00150390 -7020.5 40.00 21.18 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 95118.13 -10.70 0.00150390 -10.70 0.15632344 3.3069 0.00 0.00199515 23.81 0.00199515 10.9742 0.00 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
AIRLOOP DATACENTER TOP HEATING COIL COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoop AirLoopHVAC AIRLOOP DATACENTER TOP DATACENTER_TOP_ZN_6 Coincident HeatingDesignCapacity N/A Yes No unknown No 9678.207 9678.207 0.481181 0.00023702 -999.000 -999.0000 -999.00000 -999.00000 1019.7116 1004.8586 1.2036 unknown unknown -999.0 -999.0   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 unknown unknown NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 Sensible 9678.21 9678.21 1.0000 0.57914680 0.481181 -10.70 -10.70 0.00150390 -7020.5 40.00 21.18 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 9678.21 -10.70 0.00150390 -10.70 0.01563234 3.2487 0.00 0.00199483 22.76 0.00199483 11.6897 0.00 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL Coil:Heating:Electric AirLoop AirLoopHVAC AIRLOOP DATACENTER BASEMENT DATACENTER_BASEMENT_ZN_6 Coincident HeatingDesignCapacity N/A Yes No unknown No 20749.821 20749.821 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.2036 AIRLOOP DATACENTER BASEMENT SUPPLY FAN Fan:OnOff 21.411648 25.77095206   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 unknown unknown NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 Sensible 20749.82 20749.82 1.0000 25.77095206 21.411648 -0.17 -0.17 0.00838943 20808.9 40.00 21.18 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 20749.82 -10.70 0.00150390 -10.70 0.33839277 1.5804 0.00 0.00850000 27.00 0.00850000 38.2706 0.00 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
AIRLOOP DATACENTER BOT_SUPPHEATCOIL Coil:Heating:Electric AirLoop AirLoopHVAC AIRLOOP DATACENTER BOT DATACENTER_BOT_ZN_6 Coincident HeatingDesignCapacity N/A Yes No unknown No 958.556 958.556 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.2036 AIRLOOP DATACENTER BOT SUPPLY FAN Fan:OnOff 0.493358 0.59380328   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 unknown unknown NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 Sensible 958.56 958.56 1.0000 0.59380328 0.493358 -0.34 -0.34 0.00513340 12494.4 40.00 21.18 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 958.56 -10.70 0.00150390 -10.70 0.01563234 3.1686 0.00 0.00525217 25.81 0.00525217 25.4929 0.00 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
AIRLOOP DATACENTER MID_SUPPHEATCOIL Coil:Heating:Electric AirLoop AirLoopHVAC AIRLOOP DATACENTER MID DATACENTER_MID_ZN_6 Coincident HeatingDesignCapacity N/A Yes No unknown No 9585.558 9585.558 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.2036 AIRLOOP DATACENTER MID SUPPLY FAN Fan:OnOff 4.727151 5.68957549   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 unknown unknown NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 Sensible 9585.56 9585.56 1.0000 5.68957549 4.727151 -0.35 -3.02 0.00197890 4592.3 40.00 21.18 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 9585.56 -10.70 0.00150390 -10.70 0.15632344 3.3069 0.00 0.00199515 23.81 0.00199515 10.9742 0.00 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
AIRLOOP DATACENTER TOP_SUPPHEATCOIL Coil:Heating:Electric AirLoop AirLoopHVAC AIRLOOP DATACENTER TOP DATACENTER_TOP_ZN_6 Coincident HeatingDesignCapacity N/A Yes No unknown No 958.556 958.556 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.2036 AIRLOOP DATACENTER TOP SUPPLY FAN Fan:OnOff 0.481181 0.57914680   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 unknown unknown NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 Sensible 958.56 958.56 1.0000 0.57914680 0.481181 -0.35 -3.02 0.00197888 4598.5 40.00 21.18 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 958.56 -10.70 0.00150390 -10.70 0.01563234 3.2487 0.00 0.00199483 22.76 0.00199483 11.6897 0.00 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0



Table of Contents

Report: System Summary

For: Entire Facility

Timestamp: 2023-10-16 08:43:34

Economizer

High Limit Shutoff Control Minimum Outdoor Air [m3/s] Maximum Outdoor Air [m3/s] Return Air Temp Limit Return Air Enthalpy Limit Outdoor Air Temperature Limit [C] Outdoor Air Enthalpy Limit [C]
VAV_BOT WITH REHEAT_OA_CONTROLLER DifferentialEnthalpy 2.54 10.39 -      
VAV_MID WITH REHEAT_OA_CONTROLLER DifferentialEnthalpy 25.38 97.93 -      
VAV_TOP WITH REHEAT_OA_CONTROLLER DifferentialEnthalpy 2.54 10.67 -      
CAV_BAS_OA_CONTROLLER DifferentialEnthalpy 1.20 5.96 -      


Demand Controlled Ventilation using Controller:MechanicalVentilation

Controller:MechanicalVentilation Name Outdoor Air Per Person [m3/s-person] Outdoor Air Per Area [m3/s-m2] Outdoor Air Per Zone [m3/s] Outdoor Air ACH [ach] Outdoor Air Method Outdoor Air Schedule Name Air Distribution Effectiveness in Cooling Mode Air Distribution Effectiveness in Heating Mode Air Distribution Effectiveness Schedule Name
CORE_BOTTOM VAV_BOT WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
CORE_MID VAV_MID WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
CORE_TOP VAV_TOP WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_BOT_ZN_3 VAV_BOT WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_BOT_ZN_2 VAV_BOT WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_BOT_ZN_1 VAV_BOT WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_BOT_ZN_4 VAV_BOT WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_MID_ZN_3 VAV_MID WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_MID_ZN_2 VAV_MID WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_MID_ZN_1 VAV_MID WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_MID_ZN_4 VAV_MID WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_TOP_ZN_3 VAV_TOP WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_TOP_ZN_2 VAV_TOP WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_TOP_ZN_1 VAV_TOP WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_TOP_ZN_4 VAV_TOP WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  


Time Not Comfortable Based on Simple ASHRAE 55-2004

Winter Clothes [hr] Summer Clothes [hr] Summer or Winter Clothes [hr]
BASEMENT 3105.00 1357.33 580.33
CORE_BOTTOM 2886.50 1024.50 0.00
CORE_MID 2374.50 2697.67 115.83
CORE_TOP 2704.67 3224.17 619.17
PERIMETER_BOT_ZN_3 2686.83 2967.67 391.83
PERIMETER_BOT_ZN_2 2787.00 2995.67 467.83
PERIMETER_BOT_ZN_1 3152.00 2472.17 453.83
PERIMETER_BOT_ZN_4 3264.50 2202.00 419.33
PERIMETER_MID_ZN_3 3539.33 3667.17 1713.00
PERIMETER_MID_ZN_2 2937.00 3127.50 1371.33
PERIMETER_MID_ZN_1 3431.50 2954.00 1052.83
PERIMETER_MID_ZN_4 3412.83 3478.50 1356.83
PERIMETER_TOP_ZN_3 3934.50 3860.50 2222.00
PERIMETER_TOP_ZN_2 3788.50 3714.00 1895.17
PERIMETER_TOP_ZN_1 3666.67 3204.67 1479.00
PERIMETER_TOP_ZN_4 3686.33 3700.00 1800.17
DATACENTER_BOT_ZN_6 5911.83 1362.67 1362.67
DATACENTER_MID_ZN_6 5534.00 538.33 475.50
DATACENTER_TOP_ZN_6 5083.00 888.00 691.00
DATACENTER_BASEMENT_ZN_6 5943.00 5746.83 5746.83
GROUNDFLOOR_PLENUM 0.00 0.00 0.00
MIDFLOOR_PLENUM 0.00 0.00 0.00
TOPFLOOR_PLENUM 0.00 0.00 0.00
Facility 5943.00 5943.00 5943.00
Aggregated over the RunPeriods for Weather

Time Setpoint Not Met

During Heating [hr] During Cooling [hr] During Occupied Heating [hr] During Occupied Cooling [hr]
BASEMENT 0.00 44.83 0.00 1.33
CORE_BOTTOM 0.00 0.17 0.00 0.00
CORE_MID 2.17 1.17 1.17 1.17
CORE_TOP 6.67 0.00 0.50 0.00
PERIMETER_BOT_ZN_3 1.00 5.50 0.17 5.00
PERIMETER_BOT_ZN_2 1.17 30.83 0.00 30.83
PERIMETER_BOT_ZN_1 1.83 49.33 0.17 48.17
PERIMETER_BOT_ZN_4 0.67 89.00 0.00 42.67
PERIMETER_MID_ZN_3 57.33 3.67 13.50 3.67
PERIMETER_MID_ZN_2 38.50 34.17 3.67 34.17
PERIMETER_MID_ZN_1 29.67 57.83 2.17 56.83
PERIMETER_MID_ZN_4 31.17 31.67 3.67 21.33
PERIMETER_TOP_ZN_3 158.50 11.00 40.17 9.00
PERIMETER_TOP_ZN_2 108.83 36.67 18.50 36.17
PERIMETER_TOP_ZN_1 84.83 42.33 10.00 39.83
PERIMETER_TOP_ZN_4 80.00 35.17 15.00 23.50
DATACENTER_BOT_ZN_6 0.00 1.00 0.00 1.00
DATACENTER_MID_ZN_6 0.00 0.00 0.00 0.00
DATACENTER_TOP_ZN_6 0.00 0.00 0.00 0.00
DATACENTER_BASEMENT_ZN_6 0.00 327.50 0.00 295.33
GROUNDFLOOR_PLENUM 0.00 0.00 0.00 0.00
MIDFLOOR_PLENUM 0.00 0.00 0.00 0.00
TOPFLOOR_PLENUM 0.00 0.00 0.00 0.00
Facility 182.17 593.67 43.83 465.83
Aggregated over the RunPeriods for Weather


Table of Contents

Report: Outdoor Air Summary

For: Entire Facility

Timestamp: 2023-10-16 08:43:34

Average Outdoor Air During Occupied Hours

Average Number of Occupants Nominal Number of Occupants Zone Volume [m3] Mechanical Ventilation [ach] Infiltration [ach] AFN Infiltration [ach] Simple Ventilation [ach]
BASEMENT 62.32 149.60 6779.02 1.220 0.000 0.000 0.000
CORE_BOTTOM 55.97 134.35 6849.35 0.965 0.000 0.000 0.000
CORE_MID 55.97 134.35 6849.35 0.800 0.000 0.000 0.000
CORE_TOP 55.97 134.35 6849.35 0.782 0.000 0.000 0.000
PERIMETER_BOT_ZN_3 7.03 16.87 860.00 0.929 0.055 0.000 0.000
PERIMETER_BOT_ZN_2 4.53 10.87 554.22 1.448 0.057 0.000 0.000
PERIMETER_BOT_ZN_1 7.03 16.87 860.02 1.501 0.055 0.000 0.000
PERIMETER_BOT_ZN_4 4.53 10.87 554.22 1.979 0.057 0.000 0.000
PERIMETER_MID_ZN_3 7.03 16.87 860.00 0.855 0.129 0.000 0.000
PERIMETER_MID_ZN_2 3.96 10.87 554.22 1.441 0.142 0.000 0.000
PERIMETER_MID_ZN_1 7.03 16.87 860.02 1.502 0.129 0.000 0.000
PERIMETER_MID_ZN_4 4.53 10.87 554.22 1.642 0.133 0.000 0.000
PERIMETER_TOP_ZN_3 7.03 16.87 860.00 0.869 0.159 0.000 0.000
PERIMETER_TOP_ZN_2 4.53 10.87 554.22 1.556 0.165 0.000 0.000
PERIMETER_TOP_ZN_1 7.03 16.87 860.02 1.502 0.160 0.000 0.000
PERIMETER_TOP_ZN_4 4.53 10.87 554.22 1.683 0.165 0.000 0.000
DATACENTER_BOT_ZN_6 0.81 1.95 99.34 0.427 0.000 0.000 0.000
DATACENTER_MID_ZN_6 0.81 1.95 99.34 0.427 0.000 0.000 0.000
DATACENTER_TOP_ZN_6 0.81 1.95 99.34 0.427 0.000 0.000 0.000
DATACENTER_BASEMENT_ZN_6 17.57 42.18 1911.37 0.481 0.000 0.000 0.000
Values shown for a single zone without multipliers

Minimum Outdoor Air During Occupied Hours

Average Number of Occupants Nominal Number of Occupants Zone Volume [m3] Mechanical Ventilation [ach] Infiltration [ach] AFN Infiltration [ach] Simple Ventilation [ach]
BASEMENT 62.32 149.60 6779.02 0.000 0.000 0.000 0.000
CORE_BOTTOM 55.97 134.35 6849.35 0.000 0.000 0.000 0.000
CORE_MID 55.97 134.35 6849.35 0.000 0.000 0.000 0.000
CORE_TOP 55.97 134.35 6849.35 0.000 0.000 0.000 0.000
PERIMETER_BOT_ZN_3 7.03 16.87 860.00 0.000 0.000 0.000 0.000
PERIMETER_BOT_ZN_2 4.53 10.87 554.22 0.000 0.000 0.000 0.000
PERIMETER_BOT_ZN_1 7.03 16.87 860.02 0.000 0.000 0.000 0.000
PERIMETER_BOT_ZN_4 4.53 10.87 554.22 0.000 0.000 0.000 0.000
PERIMETER_MID_ZN_3 7.03 16.87 860.00 0.000 0.000 0.000 0.000
PERIMETER_MID_ZN_2 3.96 10.87 554.22 0.000 0.000 0.000 0.000
PERIMETER_MID_ZN_1 7.03 16.87 860.02 0.000 0.000 0.000 0.000
PERIMETER_MID_ZN_4 4.53 10.87 554.22 0.000 0.000 0.000 0.000
PERIMETER_TOP_ZN_3 7.03 16.87 860.00 0.000 0.000 0.000 0.000
PERIMETER_TOP_ZN_2 4.53 10.87 554.22 0.000 0.000 0.000 0.000
PERIMETER_TOP_ZN_1 7.03 16.87 860.02 0.000 0.000 0.000 0.000
PERIMETER_TOP_ZN_4 4.53 10.87 554.22 0.000 0.000 0.000 0.000
DATACENTER_BOT_ZN_6 0.81 1.95 99.34 0.000 0.000 0.000 0.000
DATACENTER_MID_ZN_6 0.81 1.95 99.34 0.000 0.000 0.000 0.000
DATACENTER_TOP_ZN_6 0.81 1.95 99.34 0.000 0.000 0.000 0.000
DATACENTER_BASEMENT_ZN_6 17.57 42.18 1911.37 0.000 0.000 0.000 0.000
Values shown for a single zone without multipliers


Table of Contents

Report: Outdoor Air Details

For: Entire Facility

Timestamp: 2023-10-16 08:43:34

Mechanical Ventilation Parameters by Zone

AirLoop Name Average Number of Occupants Nominal Number of Occupants Zone Volume [m3] Zone Area [m2] Design Zone Outdoor Airflow - Voz [m3/s] Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s]
BASEMENT CAV_BAS 62.32 149.60 6779.02 2779.43 1.2002 1.200
CORE_BOTTOM VAV_BOT WITH REHEAT 55.97 134.35 6849.35 2496.12 0.0000 1.078
CORE_MID VAV_MID WITH REHEAT 55.97 134.35 6849.35 2496.12 0.0000 10.778
CORE_TOP VAV_TOP WITH REHEAT 55.97 134.35 6849.35 2496.12 0.0000 1.078
PERIMETER_BOT_ZN_3 VAV_BOT WITH REHEAT 7.03 16.87 860.00 313.41 0.0000 0.135
PERIMETER_BOT_ZN_2 VAV_BOT WITH REHEAT 4.53 10.87 554.22 201.98 0.0000 0.087
PERIMETER_BOT_ZN_1 VAV_BOT WITH REHEAT 7.03 16.87 860.02 313.42 0.0000 0.135
PERIMETER_BOT_ZN_4 VAV_BOT WITH REHEAT 4.53 10.87 554.22 201.98 0.0000 0.087
PERIMETER_MID_ZN_3 VAV_MID WITH REHEAT 7.03 16.87 860.00 313.41 0.0000 1.353
PERIMETER_MID_ZN_2 VAV_MID WITH REHEAT 3.96 10.87 554.22 201.98 0.0000 0.872
PERIMETER_MID_ZN_1 VAV_MID WITH REHEAT 7.03 16.87 860.02 313.42 0.0000 1.353
PERIMETER_MID_ZN_4 VAV_MID WITH REHEAT 4.53 10.87 554.22 201.98 0.0000 0.872
PERIMETER_TOP_ZN_3 VAV_TOP WITH REHEAT 7.03 16.87 860.00 313.41 0.0000 0.135
PERIMETER_TOP_ZN_2 VAV_TOP WITH REHEAT 4.53 10.87 554.22 201.98 0.0000 0.087
PERIMETER_TOP_ZN_1 VAV_TOP WITH REHEAT 7.03 16.87 860.02 313.42 0.0000 0.135
PERIMETER_TOP_ZN_4 VAV_TOP WITH REHEAT 4.53 10.87 554.22 201.98 0.0000 0.087
DATACENTER_BOT_ZN_6 AIRLOOP DATACENTER BOT 0.81 1.95 99.34 36.20 0.0156 0.016
DATACENTER_MID_ZN_6 AIRLOOP DATACENTER MID 0.81 1.95 99.34 36.20 0.1563 0.156
DATACENTER_TOP_ZN_6 AIRLOOP DATACENTER TOP 0.81 1.95 99.34 36.20 0.0156 0.016
DATACENTER_BASEMENT_ZN_6 AIRLOOP DATACENTER BASEMENT 17.57 42.18 1911.37 783.68 0.3384 0.338
Total Facility   1032.96 2493.19 126016.35 46320.38 1.7261 158.471


Total Outdoor Air by Zone

Mechanical Ventilation [m3] Natural Ventilation [m3] Total Ventilation [m3] Infiltration [m3] Total Ventilation and Infiltration [m3] Dynamic Target Ventilation - Voz-dyn [m3] Time Below Voz-dyn [hr] Time At Voz-dyn [hr] Time Above Voz-dyn [hr] Time Above Zero When Unoccupied [hr]
BASEMENT 50308765.04 0.00 50308765.04 0.00 50308765.04 37848132.68 4017.88 1222.03 3520.10 286.64
CORE_BOTTOM 39977784.77 0.00 39977784.77 0.00 39977784.77 33990283.35 3923.28 11.24 4825.48 236.04
CORE_MID 0.33E+09 0.00 0.33E+09 0.00 0.33E+09 0.34E+09 4151.67 9.54 4598.79 224.41
CORE_TOP 31815218.37 0.00 31815218.37 0.00 31815218.37 33990283.35 4180.14 8.50 4571.36 330.14
PERIMETER_BOT_ZN_3 4824169.87 0.00 4824169.87 542909.24 5367079.11 4267819.30 4399.21 52.77 4308.02 236.04
PERIMETER_BOT_ZN_2 4864635.27 0.00 4864635.27 361939.24 5226574.52 2750345.05 3789.52 4.57 4965.90 236.04
PERIMETER_BOT_ZN_1 7739635.65 0.00 7739635.65 542909.24 8282544.89 4267912.63 3883.49 6.08 4870.42 236.04
PERIMETER_BOT_ZN_4 6628004.61 0.00 6628004.61 361939.24 6989943.85 2750345.05 3762.48 3.82 4993.70 236.04
PERIMETER_MID_ZN_3 43870350.29 0.00 43870350.29 1273269.14 45143619.44 42678193.03 4139.09 12.84 4608.07 224.41
PERIMETER_MID_ZN_2 51196753.00 0.00 51196753.00 848845.52 52045598.52 27503450.52 3961.11 10.96 4787.93 1133.41
PERIMETER_MID_ZN_1 76504320.32 0.00 76504320.32 1273269.14 77777589.46 42679126.28 4068.89 3.83 4687.28 224.41
PERIMETER_MID_ZN_4 54283623.26 0.00 54283623.26 848845.52 55132468.78 27503450.52 3947.31 7.93 4804.76 224.41
PERIMETER_TOP_ZN_3 4442092.05 0.00 4442092.05 1580892.99 6022985.04 4267819.30 4149.24 4.80 4605.96 330.14
PERIMETER_TOP_ZN_2 5120750.89 0.00 5120750.89 1053927.94 6174678.83 2750345.05 4075.79 2.78 4681.44 330.14
PERIMETER_TOP_ZN_1 7637648.10 0.00 7637648.10 1580892.99 9218541.09 4267912.63 4126.81 1.75 4631.44 330.14
PERIMETER_TOP_ZN_4 5544290.92 0.00 5544290.92 1053927.94 6598218.86 2750345.05 4066.17 4.76 4689.07 330.14
DATACENTER_BOT_ZN_6 244296.02 0.00 244296.02 0.00 244296.02 492981.60 4419.00 4341.00 0.00 0.00
DATACENTER_MID_ZN_6 2442960.18 0.00 2442960.18 0.00 2442960.18 4929815.99 4419.00 4341.00 0.00 0.00
DATACENTER_TOP_ZN_6 244296.02 0.00 244296.02 0.00 244296.02 492981.60 4419.00 4341.00 0.00 0.00
DATACENTER_BASEMENT_ZN_6 5288266.81 0.00 5288266.81 0.00 5288266.81 10671554.30 4419.00 4341.00 0.00 0.00
Total Facility 0.57E+10 0.00 0.57E+10 49521632.03 0.58E+10 0.50E+10 4924.37 4396.07 5173.41 1561.04


Average Outdoor Air During Occupancy by Zone - Flow Rates

Mechanical Ventilation [m3/s] Natural Ventilation [m3/s] Total Ventilation [m3/s] Infiltration [m3/s] Total Ventilation and Infiltration [m3/s] Dynamic Target Ventilation - Voz-dyn [m3/s] Time Below Voz-dyn [hr] Time At Voz-dyn [hr] Time Above Voz-dyn [hr]
BASEMENT 2.2492 0.0000 2.2492 0.0000 2.2492 1.2002 1360.35 1219.88 3362.77
CORE_BOTTOM 1.7990 0.0000 1.7990 0.0000 1.7990 1.0778 1284.53 9.85 4648.62
CORE_MID 14.9288 0.0000 14.9288 0.0000 14.9288 10.7782 1396.72 9.54 4536.74
CORE_TOP 1.4608 0.0000 1.4608 0.0000 1.4608 1.0778 1405.56 8.50 4528.94
PERIMETER_BOT_ZN_3 0.2176 0.0000 0.2176 0.0129 0.2305 0.1353 1758.07 51.14 4133.79
PERIMETER_BOT_ZN_2 0.2189 0.0000 0.2189 0.0086 0.2275 0.0872 1193.84 3.29 4745.88
PERIMETER_BOT_ZN_1 0.3519 0.0000 0.3519 0.0129 0.3648 0.1353 1266.42 4.77 4671.80
PERIMETER_BOT_ZN_4 0.2987 0.0000 0.2987 0.0086 0.3073 0.0872 1172.16 3.35 4767.50
PERIMETER_MID_ZN_3 2.0068 0.0000 2.0068 0.0303 2.0371 1.3533 1393.13 12.52 4537.35
PERIMETER_MID_ZN_2 2.1821 0.0000 2.1821 0.0215 2.2037 0.8721 1256.14 7.07 3770.79
PERIMETER_MID_ZN_1 3.5222 0.0000 3.5222 0.0303 3.5525 1.3533 1324.25 2.13 4616.62
PERIMETER_MID_ZN_4 2.4840 0.0000 2.4840 0.0202 2.5043 0.8721 1250.05 3.15 4689.80
PERIMETER_TOP_ZN_3 0.2040 0.0000 0.2040 0.0377 0.2416 0.1353 1380.35 4.45 4558.20
PERIMETER_TOP_ZN_2 0.2355 0.0000 0.2355 0.0251 0.2606 0.0872 1327.72 1.48 4613.80
PERIMETER_TOP_ZN_1 0.3524 0.0000 0.3524 0.0377 0.3901 0.1353 1360.44 1.23 4581.33
PERIMETER_TOP_ZN_4 0.2547 0.0000 0.2547 0.0251 0.2798 0.0872 1320.02 3.29 4619.70
DATACENTER_BOT_ZN_6 0.0114 0.0000 0.0114 0.0000 0.0114 0.0156 1602.00 4341.00 0.00
DATACENTER_MID_ZN_6 0.1142 0.0000 0.1142 0.0000 0.1142 0.1563 1602.00 4341.00 0.00
DATACENTER_TOP_ZN_6 0.0114 0.0000 0.0114 0.0000 0.0114 0.0156 1602.00 4341.00 0.00
DATACENTER_BASEMENT_ZN_6 0.2472 0.0000 0.2472 0.0000 0.2472 0.3384 1602.00 4341.00 0.00
Total Facility 260.2933 0.0000 260.2933 1.1927 261.4860 158.4706 2107.37 4375.92 4842.13


Total Outdoor Air by AirLoop

Mechanical Ventilation [m3] Natural Ventilation [m3/s] Total Ventilation [m3/s] Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] Time Below Voz-sum-dyn [hr] Time At Voz-sum-dyn [hr] Time Above Voz-sum-dyn [hr] Time Above Zero When Unoccupied [hr]
VAV_BOT WITH REHEAT 92761581.57 0.00 92761581.57 48026705.38 3785.98 3.22 4970.81 236.04
VAV_MID WITH REHEAT 0.80E+09 0.00 0.80E+09 0.48E+09 4000.69 4.30 4755.01 224.41
VAV_TOP WITH REHEAT 79036193.73 0.00 79036193.73 48026705.38 4097.67 2.84 4659.49 330.14
CAV_BAS 72879333.64 0.00 72879333.64 37848132.68 3953.05 3.35 4803.60 286.64
AIRLOOP DATACENTER BASEMENT 7660799.48 0.00 7660799.48 10671554.30 4419.00 0.00 4341.00 0.00
AIRLOOP DATACENTER BOT 353897.20 0.00 353897.20 492981.60 4419.00 0.00 4341.00 0.00
AIRLOOP DATACENTER MID 3538971.99 0.00 3538971.99 4929815.99 4419.00 0.00 4341.00 0.00
AIRLOOP DATACENTER TOP 353897.20 0.00 353897.20 492981.60 4419.00 0.00 4341.00 0.00


Average Outdoor Air During Occupancy by AirLoop

Mechanical Ventilation [m3/s] Natural Ventilation [m3/s] Total Ventilation [m3/s] Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] Time Below Voz-sum-dyn [hr] Time At Voz-sum-dyn [hr] Time Above Voz-sum-dyn [hr]
VAV_BOT WITH REHEAT 4.1809 0.0000 4.1809 1.5229 1188.00 2.21 4752.79
VAV_MID WITH REHEAT 36.6227 0.0000 36.6227 15.2292 1279.66 2.59 4660.75
VAV_TOP WITH REHEAT 3.6323 0.0000 3.6323 1.5229 1339.97 2.36 4600.67
CAV_BAS 3.2583 0.0000 3.2583 1.2002 1338.38 0.40 4604.22
AIRLOOP DATACENTER BASEMENT 0.3581 0.0000 0.3581 0.3384 1602.00 0.00 4341.00
AIRLOOP DATACENTER BOT 0.0165 0.0000 0.0165 0.0156 1602.00 0.00 4341.00
AIRLOOP DATACENTER MID 0.1654 0.0000 0.1654 0.1563 1602.00 0.00 4341.00
AIRLOOP DATACENTER TOP 0.0165 0.0000 0.0165 0.0156 1602.00 0.00 4341.00


Outdoor Air Controller Limiting Factors by AirLoop

No Limiting Factor [hr] Limits and Scheduled Limits [hr] Economizer [hr] Exhaust Flow [hr] Mixed Air Flow [hr] High Humidity [hr] Demand Controlled Ventilation [hr] Night Ventilation [hr] Demand Limiting [hr] Energy Management System [hr]
VAV_BOT WITH REHEAT 0.00 2365.41 2653.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
VAV_MID WITH REHEAT 0.00 2757.68 2220.63 0.00 0.00 0.00 0.00 0.00 0.00 0.00
VAV_TOP WITH REHEAT 0.00 2950.96 2162.31 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CAV_BAS 0.00 1213.44 3688.40 0.00 0.00 0.00 0.00 0.00 0.00 0.00
AIRLOOP DATACENTER BASEMENT 0.00 4341.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
AIRLOOP DATACENTER BOT 0.00 4341.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
AIRLOOP DATACENTER MID 0.00 4341.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
AIRLOOP DATACENTER TOP 0.00 4341.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Average Outdoor Air for Limiting Factors During Occupancy

No Limiting Factor [m3/s] Limits and Scheduled Limits [m3/s] Economizer [m3/s] Exhaust Flow [m3/s] Mixed Air Flow [m3/s] High Humidity [m3/s] Demand Controlled Ventilation [m3/s] Night Ventilation [m3/s] Demand Limiting [m3/s] Energy Management System [m3/s]
VAV_BOT WITH REHEAT 0.0000 3.6840 6.6781 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
VAV_MID WITH REHEAT 0.0000 36.8417 58.1544 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
VAV_TOP WITH REHEAT 0.0000 3.6802 5.8571 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
CAV_BAS 0.0000 1.7392 5.0733 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
AIRLOOP DATACENTER BASEMENT 0.0000 0.4903 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
AIRLOOP DATACENTER BOT 0.0000 0.0227 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
AIRLOOP DATACENTER MID 0.0000 0.2265 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
AIRLOOP DATACENTER TOP 0.0000 0.0227 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000



Table of Contents

Report: Object Count Summary

For: Entire Facility

Timestamp: 2023-10-16 08:43:34

Surfaces by Class

Total Outdoors
Wall 98 30
Floor 41 0
Roof 30 1
Internal Mass 16 0
Building Detached Shading 0 0
Fixed Detached Shading 0 0
Window 24 24
Door 12 12
Glass Door 0 0
Shading 0 0
Overhang 0 0
Fin 0 0
Tubular Daylighting Device Dome 0 0
Tubular Daylighting Device Diffuser 0 0


HVAC

Count
HVAC Air Loops 8
Conditioned Zones 23
Unconditioned Zones 0
Supply Plenums 0
Return Plenums 3


Input Fields

Count
IDF Objects 1401
Defaulted Fields 1182
Fields with Defaults 3927
Autosized Fields 338
Autosizable Fields 414
Autocalculated Fields 226
Autocalculatable Fields 473



Table of Contents

Report: Energy Meters

For: Entire Facility

Timestamp: 2023-10-16 08:43:34

Annual and Peak Values - Electricity

Electricity Annual Value [GJ] Electricity Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Electricity Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
Electricity:Facility 29088.15 360707.16 14-MAY-05:00 2113158.43 16-AUG-15:20
Electricity:Building 18607.20 225715.65 14-MAY-17:10 1164206.62 01-DEC-16:30
Electricity:Zone:BASEMENT 687.24 14732.47 01-JAN-00:10 36407.88 02-JAN-08:10
Electricity:SpaceType:GENERAL 18607.20 225715.65 14-MAY-17:10 1164206.62 01-DEC-16:30
InteriorLights:Electricity 3930.81 18459.50 01-JAN-08:50 385834.94 02-JAN-16:30
InteriorLights:Electricity:Zone:BASEMENT 262.84 1274.92 01-JAN-00:10 22950.34 02-JAN-08:10
InteriorLights:Electricity:SpaceType:GENERAL 3930.81 18459.50 01-JAN-08:50 385834.94 02-JAN-16:30
LightsWired:InteriorLights:Electricity 3930.81 18459.50 01-JAN-08:50 385834.94 02-JAN-16:30
LightsWired:InteriorLights:Electricity:Zone:BASEMENT 262.84 1274.92 01-JAN-00:10 22950.34 02-JAN-08:10
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL 3930.81 18459.50 01-JAN-08:50 385834.94 02-JAN-16:30
Electricity:Zone:CORE_BOTTOM 525.67 5598.20 01-JAN-00:10 37817.64 02-JAN-08:10
InteriorLights:Electricity:Zone:CORE_BOTTOM 236.05 1144.97 01-JAN-00:10 20611.01 02-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:CORE_BOTTOM 236.05 1144.97 01-JAN-00:10 20611.01 02-JAN-08:10
Electricity:Zone:CORE_MID 5256.66 55981.88 01-JAN-00:10 378175.77 02-JAN-08:10
InteriorLights:Electricity:Zone:CORE_MID 2360.53 11449.71 01-JAN-00:10 206110.14 02-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:CORE_MID 2360.53 11449.71 01-JAN-00:10 206110.14 02-JAN-08:10
Electricity:Zone:CORE_TOP 525.67 5598.19 01-JAN-00:10 37817.58 02-JAN-08:10
InteriorLights:Electricity:Zone:CORE_TOP 236.05 1144.97 01-JAN-00:10 20611.01 02-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:CORE_TOP 236.05 1144.97 01-JAN-00:10 20611.01 02-JAN-08:10
Electricity:Zone:PERIMETER_BOT_ZN_3 53.80 627.57 02-APR-17:10 4748.47 02-JAN-16:20
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 17.44 68.40 01-JAN-08:50 2587.92 02-JAN-16:20
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 17.44 68.40 01-JAN-08:50 2587.92 02-JAN-16:20
Electricity:Zone:PERIMETER_BOT_ZN_2 34.62 404.43 16-APR-17:10 3060.10 02-JAN-16:20
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 11.19 44.08 01-JAN-07:50 1667.75 02-JAN-16:20
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 11.19 44.08 01-JAN-07:50 1667.75 02-JAN-16:20
Electricity:Zone:PERIMETER_BOT_ZN_1 53.54 627.58 19-MAR-17:10 4748.56 02-JAN-16:30
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 17.17 68.40 01-JAN-07:50 2587.98 02-JAN-16:30
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 17.17 68.40 01-JAN-07:50 2587.98 02-JAN-16:30
Electricity:Zone:PERIMETER_BOT_ZN_4 34.53 404.43 12-MAR-17:10 3060.09 02-JAN-16:30
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 11.09 44.08 01-JAN-08:50 1667.75 02-JAN-16:30
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 11.09 44.08 01-JAN-08:50 1667.75 02-JAN-16:30
Electricity:Zone:PERIMETER_MID_ZN_3 537.66 6275.73 02-APR-17:10 47484.70 02-JAN-16:20
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 174.00 684.02 01-JAN-08:40 25879.19 02-JAN-16:20
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 174.00 684.02 01-JAN-08:40 25879.19 02-JAN-16:20
Electricity:Zone:PERIMETER_MID_ZN_2 346.07 4044.32 09-APR-17:10 30600.95 02-JAN-16:20
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 111.71 440.81 01-JAN-07:50 16677.53 02-JAN-16:20
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 111.71 440.81 01-JAN-07:50 16677.53 02-JAN-16:20
Electricity:Zone:PERIMETER_MID_ZN_1 535.19 6275.83 19-MAR-17:10 47485.60 02-JAN-16:30
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 171.53 684.04 01-JAN-07:50 25879.75 02-JAN-16:30
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 171.53 684.04 01-JAN-07:50 25879.75 02-JAN-16:30
Electricity:Zone:PERIMETER_MID_ZN_4 345.11 4044.30 12-MAR-17:10 30600.86 02-JAN-16:30
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 110.76 440.81 01-JAN-08:40 16677.53 02-JAN-16:30
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 110.76 440.81 01-JAN-08:40 16677.53 02-JAN-16:30
Electricity:Zone:PERIMETER_TOP_ZN_3 53.76 627.57 02-APR-17:10 4748.47 02-JAN-16:20
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 17.40 68.40 01-JAN-08:40 2587.92 02-JAN-16:20
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 17.40 68.40 01-JAN-08:40 2587.92 02-JAN-16:20
Electricity:Zone:PERIMETER_TOP_ZN_2 34.61 404.43 09-APR-17:10 3060.10 02-JAN-16:20
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 11.17 44.08 01-JAN-07:50 1667.75 02-JAN-16:20
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 11.17 44.08 01-JAN-07:50 1667.75 02-JAN-16:20
Electricity:Zone:PERIMETER_TOP_ZN_1 53.52 627.58 19-MAR-17:10 4748.56 02-JAN-16:30
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 17.15 68.40 01-JAN-07:50 2587.98 02-JAN-16:30
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 17.15 68.40 01-JAN-07:50 2587.98 02-JAN-16:30
Electricity:Zone:PERIMETER_TOP_ZN_4 34.51 404.43 12-MAR-17:10 3060.09 02-JAN-16:30
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 11.08 44.08 01-JAN-08:40 1667.75 02-JAN-16:30
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 11.08 44.08 01-JAN-08:40 1667.75 02-JAN-16:30
Electricity:Zone:DATACENTER_BASEMENT_ZN_6 7568.97 95267.60 01-JAN-00:10 386103.53 03-APR-07:10
InteriorLights:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 74.11 359.47 01-JAN-00:10 6471.01 02-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 74.11 359.47 01-JAN-00:10 6471.01 02-JAN-08:10
Electricity:Zone:DATACENTER_BOT_ZN_6 160.51 1980.76 01-JAN-00:10 8373.14 03-APR-07:10
InteriorLights:Electricity:Zone:DATACENTER_BOT_ZN_6 6.63 32.15 01-JAN-00:10 578.72 02-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_BOT_ZN_6 6.63 32.15 01-JAN-00:10 578.72 02-JAN-08:10
Electricity:Zone:DATACENTER_MID_ZN_6 1605.09 19807.58 01-JAN-00:10 83731.41 03-APR-07:10
InteriorLights:Electricity:Zone:DATACENTER_MID_ZN_6 66.28 321.53 01-JAN-00:10 5787.18 02-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_MID_ZN_6 66.28 321.53 01-JAN-00:10 5787.18 02-JAN-08:10
Electricity:Zone:DATACENTER_TOP_ZN_6 160.51 1980.76 01-JAN-00:10 8373.14 03-APR-07:10
InteriorLights:Electricity:Zone:DATACENTER_TOP_ZN_6 6.63 32.15 01-JAN-00:10 578.72 02-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_TOP_ZN_6 6.63 32.15 01-JAN-00:10 578.72 02-JAN-08:10
InteriorEquipment:Electricity 14676.40 207256.16 01-JAN-00:10 778371.69 03-APR-07:10
InteriorEquipment:Electricity:Zone:BASEMENT 424.40 13457.54 01-JAN-00:10 13457.54 01-JAN-00:10
InteriorEquipment:Electricity:SpaceType:GENERAL 14676.40 207256.16 01-JAN-00:10 778371.69 03-APR-07:10
MiscPlug:InteriorEquipment:Electricity 5334.97 88964.76 01-JAN-00:10 305206.10 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:BASEMENT 424.40 13457.54 01-JAN-00:10 13457.54 01-JAN-00:10
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL 5334.97 88964.76 01-JAN-00:10 305206.10 02-JAN-08:10
InteriorEquipment:Electricity:Zone:CORE_BOTTOM 289.61 4453.23 01-JAN-00:10 17206.63 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_BOTTOM 289.61 4453.23 01-JAN-00:10 17206.63 02-JAN-08:10
InteriorEquipment:Electricity:Zone:CORE_MID 2896.13 44532.17 01-JAN-00:10 172065.63 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_MID 2896.13 44532.17 01-JAN-00:10 172065.63 02-JAN-08:10
InteriorEquipment:Electricity:Zone:CORE_TOP 289.61 4453.22 01-JAN-00:10 17206.56 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_TOP 289.61 4453.22 01-JAN-00:10 17206.56 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 36.37 559.17 01-JAN-00:10 2160.55 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 36.37 559.17 01-JAN-00:10 2160.55 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 23.44 360.35 01-JAN-00:10 1392.34 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 23.44 360.35 01-JAN-00:10 1392.34 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 36.37 559.18 01-JAN-00:10 2160.58 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 36.37 559.18 01-JAN-00:10 2160.58 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 23.44 360.35 01-JAN-00:10 1392.33 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 23.44 360.35 01-JAN-00:10 1392.33 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 363.65 5591.71 01-JAN-00:10 21605.52 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 363.65 5591.71 01-JAN-00:10 21605.52 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 234.35 3603.51 01-JAN-00:10 13923.42 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 234.35 3603.51 01-JAN-00:10 13923.42 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 363.66 5591.79 01-JAN-00:10 21605.85 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 363.66 5591.79 01-JAN-00:10 21605.85 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 234.35 3603.49 01-JAN-00:10 13923.33 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 234.35 3603.49 01-JAN-00:10 13923.33 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 36.37 559.17 01-JAN-00:10 2160.55 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 36.37 559.17 01-JAN-00:10 2160.55 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 23.44 360.35 01-JAN-00:10 1392.34 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 23.44 360.35 01-JAN-00:10 1392.34 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 36.37 559.18 01-JAN-00:10 2160.58 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 36.37 559.18 01-JAN-00:10 2160.58 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 23.44 360.35 01-JAN-00:10 1392.33 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 23.44 360.35 01-JAN-00:10 1392.33 02-JAN-08:10
InteriorEquipment:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 7494.86 94908.13 01-JAN-00:10 379632.52 31-MAR-23:10
DataCenterPlugLoads:InteriorEquipment:Electricity 9341.42 118291.40 01-JAN-00:10 473165.59 31-MAR-23:10
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 7494.86 94908.13 01-JAN-00:10 379632.52 31-MAR-23:10
DataCenterPlugLoads:InteriorEquipment:Electricity:SpaceType:GENERAL 9341.42 118291.40 01-JAN-00:10 473165.59 31-MAR-23:10
InteriorEquipment:Electricity:Zone:DATACENTER_BOT_ZN_6 153.88 1948.61 01-JAN-00:10 7794.42 31-MAR-23:10
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_BOT_ZN_6 153.88 1948.61 01-JAN-00:10 7794.42 31-MAR-23:10
InteriorEquipment:Electricity:Zone:DATACENTER_MID_ZN_6 1538.81 19486.06 01-JAN-00:10 77944.22 31-MAR-23:10
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_MID_ZN_6 1538.81 19486.06 01-JAN-00:10 77944.22 31-MAR-23:10
InteriorEquipment:Electricity:Zone:DATACENTER_TOP_ZN_6 153.88 1948.61 01-JAN-00:10 7794.42 31-MAR-23:10
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_TOP_ZN_6 153.88 1948.61 01-JAN-00:10 7794.42 31-MAR-23:10
Electricity:Plant 2798.58 5505.22 02-JAN-04:40 522586.34 24-AUG-16:40
HeatRejection:Electricity 1159.17 1876.90 02-JAN-07:20 93402.74 07-APR-14:20
General:HeatRejection:Electricity 1159.17 1876.90 02-JAN-07:20 93402.74 07-APR-14:20
Electricity:HVAC 5129.21 73005.40 01-JAN-24:00 492954.89 24-AUG-16:40
ExteriorEquipment:Electricity 1934.79 28603.11 01-JAN-00:10 118525.16 03-JAN-08:20
Transformer:ExteriorEquipment:Electricity 80.18 1421.04 01-JAN-00:10 5057.48 01-DEC-16:40
ElectricityPurchased:Facility 29088.15 360707.16 14-MAY-05:00 2113158.43 16-AUG-15:20
ElectricityPurchased:Plant 29088.15 360707.16 14-MAY-05:00 2113158.43 16-AUG-15:20
Cogeneration:ElectricityPurchased 29088.15 360707.16 14-MAY-05:00 2113158.43 16-AUG-15:20
General:Cogeneration:ElectricityPurchased 29088.15 360707.16 14-MAY-05:00 2113158.43 16-AUG-15:20
ElectricitySurplusSold:Facility 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
ElectricitySurplusSold:Plant 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cogeneration:ElectricitySurplusSold 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Cogeneration:ElectricitySurplusSold 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
ElectricityNet:Facility 29088.15 360707.16 14-MAY-05:00 2113158.43 16-AUG-15:20
ElectricityNet:Plant 29088.15 360707.16 14-MAY-05:00 2113158.43 16-AUG-15:20
Cogeneration:ElectricityNet 29088.15 360707.16 14-MAY-05:00 2113158.43 16-AUG-15:20
General:Cogeneration:ElectricityNet 29088.15 360707.16 14-MAY-05:00 2113158.43 16-AUG-15:20
Fans:Electricity 2439.82 41886.45 03-JAN-23:10 314543.08 11-JUL-14:30
General:Fans:Electricity 2439.82 41886.45 03-JAN-23:10 314543.08 11-JUL-14:30
ExteriorLights:Electricity 698.54 0.00 01-JAN-07:30 57580.60 01-JAN-06:10
General:ExteriorLights:Electricity 698.54 0.00 01-JAN-07:30 57580.60 01-JAN-06:10
ElevatorLift:ExteriorEquipment:Electricity 1848.78 27144.47 01-JAN-00:10 113101.96 01-JAN-07:10
ElevatorLightsFan:ExteriorEquipment:Electricity 5.83 37.60 01-JAN-00:10 376.00 01-JAN-07:10
HeatRecovery:Electricity 54.36 0.00 01-JAN-00:10 5613.48 02-JAN-07:10
General:HeatRecovery:Electricity 54.36 0.00 01-JAN-00:10 5613.48 02-JAN-07:10
Cooling:Electricity 3703.58 26286.35 02-JAN-07:20 548047.79 24-AUG-16:40
General:Cooling:Electricity 3703.58 26286.35 02-JAN-07:20 548047.79 24-AUG-16:40
Heating:Electricity 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:Electricity 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Humidifier:Electricity 14.23 0.00 01-JAN-00:10 6186.06 02-JAN-20:00
General:Humidifier:Electricity 14.23 0.00 01-JAN-00:10 6186.06 02-JAN-20:00
Boiler Parasitic:Heating:Electricity 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Pumps:Electricity 476.45 3422.13 01-JAN-00:40 68118.46 30-AUG-13:40
General:Pumps:Electricity 476.45 3422.13 01-JAN-00:40 68118.46 30-AUG-13:40
WIRED_LTG_ELECTRICITY 110.46 0.00 01-JAN-00:10 10841.96 02-JAN-16:40
WIRED_INT_EQUIP 5334.97 88964.76 31-MAR-23:10 305206.10 03-APR-07:10


Annual and Peak Values - Natural Gas

Natural Gas Annual Value [GJ] Natural Gas Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Natural Gas Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
NaturalGas:Facility 2138.67 8146.58 02-JAN-04:40 1900322.15 02-JAN-05:10
NaturalGas:Plant 2138.67 8146.58 02-JAN-04:40 1900322.15 02-JAN-05:10
Heating:NaturalGas 1354.97 0.00 01-JAN-00:40 1892175.57 02-JAN-05:10
Boiler:Heating:NaturalGas 1354.97 0.00 01-JAN-00:40 1892175.57 02-JAN-05:10
WaterSystems:NaturalGas 783.71 8146.58 02-JAN-04:40 84953.67 08-FEB-12:40
Water Heater:WaterSystems:NaturalGas 783.71 8146.58 02-JAN-04:40 84953.67 08-FEB-12:40


Annual and Peak Values - Cooling

Cooling Annual Value [GJ] Cooling Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Cooling Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
PlantLoopCoolingDemand:Facility 20005.08 131105.71 02-JAN-07:20 3391520.44 24-AUG-16:40
PlantLoopCoolingDemand:HVAC 20005.08 131105.71 02-JAN-07:20 3391520.44 24-AUG-16:40
CoolingCoils:PlantLoopCoolingDemand 20005.08 131105.71 02-JAN-07:20 3391520.44 24-AUG-16:40


Annual and Peak Values - Water

Annual Value [m3] Minimum Value [m3/s] Timestamp of Minimum {TIMESTAMP} Maximum Value [m3/s] Timestamp of Maximum {TIMESTAMP}
Water:Facility 8011.37 0.00 01-JAN-00:10 0.00 24-AUG-16:40
Water:HVAC 5.30 0.00 01-JAN-00:10 0.00 02-JAN-20:00
Humidifier:Water 5.30 0.00 01-JAN-00:10 0.00 02-JAN-20:00
General:Humidifier:Water 5.30 0.00 01-JAN-00:10 0.00 02-JAN-20:00
MainsWater:Facility 8011.37 0.00 01-JAN-00:10 0.00 24-AUG-16:40
MainsWater:HVAC 5.30 0.00 01-JAN-00:10 0.00 02-JAN-20:00
Humidifier:MainsWater 5.30 0.00 01-JAN-00:10 0.00 02-JAN-20:00
General:Humidifier:MainsWater 5.30 0.00 01-JAN-00:10 0.00 02-JAN-20:00
Water:Plant 8006.08 0.00 01-JAN-00:10 0.00 24-AUG-16:40
WaterSystems:Water 2280.17 0.00 01-JAN-00:10 0.00 02-JAN-12:10
WaterUse:WaterSystems:Water 2280.17 0.00 01-JAN-00:10 0.00 02-JAN-12:10
MainsWater:Plant 8006.08 0.00 01-JAN-00:10 0.00 24-AUG-16:40
WaterSystems:MainsWater 2280.17 0.00 01-JAN-00:10 0.00 02-JAN-12:10
WaterUse:WaterSystems:MainsWater 2280.17 0.00 01-JAN-00:10 0.00 02-JAN-12:10
Water Heater:WaterSystems:Water 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Water Heater:WaterSystems:MainsWater 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
HeatRejection:Water 5725.91 0.00 01-JAN-00:10 0.00 24-AUG-16:40
General:HeatRejection:Water 5725.91 0.00 01-JAN-00:10 0.00 24-AUG-16:40
HeatRejection:MainsWater 5725.91 0.00 01-JAN-00:10 0.00 24-AUG-16:40
General:HeatRejection:MainsWater 5725.91 0.00 01-JAN-00:10 0.00 24-AUG-16:40


Annual and Peak Values - Other by Weight/Mass

Annual Value [kg] Minimum Value [kg/s] Timestamp of Minimum {TIMESTAMP} Maximum Value [kg/s] Timestamp of Maximum {TIMESTAMP}
Carbon Equivalent:Facility 0.00 0.000 01-JAN-00:10 0.000 01-JAN-00:10
CarbonEquivalentEmissions:Carbon Equivalent 0.00 0.000 01-JAN-00:10 0.000 01-JAN-00:10


Annual and Peak Values - Other Volumetric

Annual Value [m3] Minimum Value [m3/s] Timestamp of Minimum {TIMESTAMP} Maximum Value [m3/s] Timestamp of Maximum {TIMESTAMP}
None          


Annual and Peak Values - Other Liquid/Gas

Annual Value [L] Minimum Value [L] Timestamp of Minimum {TIMESTAMP} Maximum Value [L] Timestamp of Maximum {TIMESTAMP}
None          


Annual and Peak Values - Other

Annual Value [GJ] Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
EnergyTransfer:Facility 66911.41 210779.62 02-JAN-06:00 13384092.89 24-AUG-16:40
EnergyTransfer:Building 19898.15 88500.14 07-JAN-18:10 1794304.76 18-AUG-14:50
EnergyTransfer:Zone:BASEMENT 719.54 0.00 01-JAN-00:10 76238.17 13-NOV-06:10
Heating:EnergyTransfer 598.16 0.00 19-JAN-22:10 1482935.63 02-JAN-05:10
Heating:EnergyTransfer:Zone:BASEMENT 2.74 0.00 01-JAN-00:10 12516.71 12-AUG-16:10
General:Heating:EnergyTransfer 598.16 0.00 19-JAN-22:10 1482935.63 02-JAN-05:10
General:Heating:EnergyTransfer:Zone:BASEMENT 2.74 0.00 01-JAN-00:10 12516.71 12-AUG-16:10
Cooling:EnergyTransfer 19299.99 84485.83 02-JAN-04:40 1794304.76 18-AUG-14:50
Cooling:EnergyTransfer:Zone:BASEMENT 716.80 0.00 01-JAN-00:10 76238.17 13-NOV-06:10
General:Cooling:EnergyTransfer 19299.99 84485.83 02-JAN-04:40 1794304.76 18-AUG-14:50
General:Cooling:EnergyTransfer:Zone:BASEMENT 716.80 0.00 01-JAN-00:10 76238.17 13-NOV-06:10
EnergyTransfer:Zone:CORE_BOTTOM 656.15 0.00 01-JAN-00:10 58747.51 25-AUG-15:50
Heating:EnergyTransfer:Zone:CORE_BOTTOM 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:CORE_BOTTOM 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:CORE_BOTTOM 656.15 0.00 01-JAN-00:10 58747.51 25-AUG-15:50
General:Cooling:EnergyTransfer:Zone:CORE_BOTTOM 656.15 0.00 01-JAN-00:10 58747.51 25-AUG-15:50
EnergyTransfer:Zone:CORE_MID 4712.32 0.00 01-JAN-00:40 495094.74 17-MAR-13:00
Heating:EnergyTransfer:Zone:CORE_MID 10.92 0.00 01-JAN-00:20 479962.79 02-JAN-05:30
General:Heating:EnergyTransfer:Zone:CORE_MID 10.92 0.00 01-JAN-00:20 479962.79 02-JAN-05:30
Cooling:EnergyTransfer:Zone:CORE_MID 4701.39 0.00 01-JAN-00:40 495094.74 17-MAR-13:00
General:Cooling:EnergyTransfer:Zone:CORE_MID 4701.39 0.00 01-JAN-00:40 495094.74 17-MAR-13:00
EnergyTransfer:Zone:CORE_TOP 445.83 0.00 01-JAN-00:40 76529.92 02-JAN-05:30
Heating:EnergyTransfer:Zone:CORE_TOP 10.02 0.00 01-JAN-00:40 76529.92 02-JAN-05:30
General:Heating:EnergyTransfer:Zone:CORE_TOP 10.02 0.00 01-JAN-00:40 76529.92 02-JAN-05:30
Cooling:EnergyTransfer:Zone:CORE_TOP 435.81 0.00 01-JAN-00:20 55526.94 11-JUL-15:00
General:Cooling:EnergyTransfer:Zone:CORE_TOP 435.81 0.00 01-JAN-00:20 55526.94 11-JUL-15:00
EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 78.01 0.00 01-JAN-00:10 12236.63 19-JUN-14:30
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 0.69 0.00 01-JAN-00:10 9899.54 02-JAN-06:10
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 0.69 0.00 01-JAN-00:10 9899.54 02-JAN-06:10
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 77.32 0.00 01-JAN-00:10 12236.63 19-JUN-14:30
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 77.32 0.00 01-JAN-00:10 12236.63 19-JUN-14:30
EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 74.21 0.00 01-JAN-00:10 16048.13 26-JUN-08:10
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 0.49 0.00 01-JAN-00:10 6891.48 02-JAN-06:10
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 0.49 0.00 01-JAN-00:10 6891.48 02-JAN-06:10
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 73.73 0.00 01-JAN-00:10 16048.13 26-JUN-08:10
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 73.73 0.00 01-JAN-00:10 16048.13 26-JUN-08:10
EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 124.96 0.00 01-JAN-00:10 22662.02 28-SEP-12:40
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 0.92 0.00 01-JAN-00:10 11808.65 02-JAN-06:10
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 0.92 0.00 01-JAN-00:10 11808.65 02-JAN-06:10
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 124.04 0.00 01-JAN-00:10 22662.02 28-SEP-12:40
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 124.04 0.00 01-JAN-00:10 22662.02 28-SEP-12:40
EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 109.25 0.00 01-JAN-00:10 20776.49 15-AUG-16:00
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 0.10 0.00 01-JAN-00:10 5148.31 02-JAN-06:10
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 0.10 0.00 01-JAN-00:10 5148.31 02-JAN-06:10
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 109.15 0.00 01-JAN-00:10 20776.49 15-AUG-16:00
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 109.15 0.00 01-JAN-00:10 20776.49 15-AUG-16:00
EnergyTransfer:Zone:PERIMETER_MID_ZN_3 670.81 0.00 01-JAN-00:40 151672.14 06-FEB-04:10
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 130.18 0.00 01-JAN-00:40 151672.14 06-FEB-04:10
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 130.18 0.00 01-JAN-00:40 151672.14 06-FEB-04:10
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 540.62 0.00 01-JAN-00:10 116777.69 19-JUN-14:30
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 540.62 0.00 01-JAN-00:10 116777.69 19-JUN-14:30
EnergyTransfer:Zone:PERIMETER_MID_ZN_2 689.16 0.00 01-JAN-00:40 173098.59 26-JUN-08:30
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 69.16 0.00 01-JAN-00:40 145277.53 02-JAN-05:10
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 69.16 0.00 01-JAN-00:40 145277.53 02-JAN-05:10
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 620.00 0.00 01-JAN-00:10 173098.59 26-JUN-08:30
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 620.00 0.00 01-JAN-00:10 173098.59 26-JUN-08:30
EnergyTransfer:Zone:PERIMETER_MID_ZN_1 1146.00 0.00 01-JAN-00:40 236099.66 28-SEP-13:10
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 70.72 0.00 01-JAN-00:40 196075.08 02-JAN-05:10
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 70.72 0.00 01-JAN-00:40 196075.08 02-JAN-05:10
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 1075.27 0.00 01-JAN-00:10 236099.66 28-SEP-13:10
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 1075.27 0.00 01-JAN-00:10 236099.66 28-SEP-13:10
EnergyTransfer:Zone:PERIMETER_MID_ZN_4 734.02 0.00 01-JAN-00:40 187141.62 15-AUG-16:00
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 56.77 0.00 01-JAN-00:40 138943.96 02-JAN-05:10
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 56.77 0.00 01-JAN-00:40 138943.96 02-JAN-05:10
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 677.25 0.00 01-JAN-00:20 187141.62 15-AUG-16:00
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 677.25 0.00 01-JAN-00:20 187141.62 15-AUG-16:00
EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 80.72 0.00 01-JAN-00:40 18233.71 06-FEB-04:20
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 28.80 0.00 01-JAN-00:40 18233.71 06-FEB-04:20
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 28.80 0.00 01-JAN-00:40 18233.71 06-FEB-04:20
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 51.92 0.00 01-JAN-00:10 12987.42 19-JUN-14:30
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 51.92 0.00 01-JAN-00:10 12987.42 19-JUN-14:30
EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 75.08 0.00 01-JAN-00:40 18534.59 06-FEB-05:10
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 15.34 0.00 01-JAN-00:40 18534.59 06-FEB-05:10
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 15.34 0.00 01-JAN-00:40 18534.59 06-FEB-05:10
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 59.75 0.00 01-JAN-00:10 17572.25 26-JUN-08:30
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 59.75 0.00 01-JAN-00:10 17572.25 26-JUN-08:30
EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 119.56 0.00 01-JAN-00:40 24828.24 28-SEP-13:20
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 17.65 0.00 01-JAN-00:40 23794.02 06-FEB-04:20
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 17.65 0.00 01-JAN-00:40 23794.02 06-FEB-04:20
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 101.91 0.00 01-JAN-00:10 24828.24 28-SEP-13:20
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 101.91 0.00 01-JAN-00:10 24828.24 28-SEP-13:20
EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 78.38 0.00 01-JAN-00:40 19318.69 15-AUG-16:00
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 12.75 0.00 01-JAN-00:40 18793.92 06-FEB-05:10
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 12.75 0.00 01-JAN-00:40 18793.92 06-FEB-05:10
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 65.63 0.00 01-JAN-00:10 19318.69 15-AUG-16:00
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 65.63 0.00 01-JAN-00:10 19318.69 15-AUG-16:00
EnergyTransfer:Zone:GROUNDFLOOR_PLENUM 70.10 0.00 01-JAN-00:10 10873.18 14-AUG-14:40
Heating:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM 2.85 0.00 01-JAN-00:10 6120.80 17-JAN-10:10
General:Heating:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM 2.85 0.00 01-JAN-00:10 6120.80 17-JAN-10:10
Cooling:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM 67.26 0.00 01-JAN-00:10 10873.18 14-AUG-14:40
General:Cooling:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM 67.26 0.00 01-JAN-00:10 10873.18 14-AUG-14:40
EnergyTransfer:Zone:MIDFLOOR_PLENUM 568.76 0.00 01-JAN-00:40 200121.12 02-JAN-06:20
Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM 123.17 0.00 01-JAN-00:40 200121.12 02-JAN-06:20
General:Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM 123.17 0.00 01-JAN-00:40 200121.12 02-JAN-06:20
Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM 445.59 0.00 01-JAN-00:10 91379.36 10-JUL-15:30
General:Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM 445.59 0.00 01-JAN-00:10 91379.36 10-JUL-15:30
EnergyTransfer:Zone:TOPFLOOR_PLENUM 109.24 0.00 01-JAN-00:40 31579.93 06-FEB-05:10
Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM 39.72 0.00 01-JAN-00:40 31579.93 06-FEB-05:10
General:Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM 39.72 0.00 01-JAN-00:40 31579.93 06-FEB-05:10
Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM 69.52 0.00 01-JAN-00:10 23583.74 19-JUN-13:30
General:Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM 69.52 0.00 01-JAN-00:10 23583.74 19-JUN-13:30
EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 138.98 5.08 02-JAN-07:00 8426.30 23-APR-17:50
Heating:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 0.01 0.00 01-JAN-09:30 187.43 01-JAN-09:00
General:Heating:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 0.01 0.00 01-JAN-09:30 187.43 01-JAN-09:00
Cooling:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 138.97 0.00 01-JAN-00:10 8426.30 23-APR-17:50
General:Cooling:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 138.97 0.00 01-JAN-00:10 8426.30 23-APR-17:50
EnergyTransfer:Zone:DATACENTER_MID_ZN_6 1201.83 5.17 25-JAN-03:00 79872.37 31-AUG-17:30
Heating:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 4.39 0.00 02-JAN-07:20 5714.34 15-JAN-18:00
General:Heating:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 4.39 0.00 02-JAN-07:20 5714.34 15-JAN-18:00
Cooling:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 1197.45 0.00 01-JAN-00:10 79872.37 31-AUG-17:30
General:Cooling:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 1197.45 0.00 01-JAN-00:10 79872.37 31-AUG-17:30
EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 111.98 0.42 28-JAN-14:40 8099.81 31-AUG-17:30
Heating:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 0.79 0.00 02-JAN-07:20 610.16 16-JAN-18:00
General:Heating:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 0.79 0.00 02-JAN-07:20 610.16 16-JAN-18:00
Cooling:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 111.19 0.00 01-JAN-00:10 8099.81 31-AUG-17:30
General:Cooling:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 111.19 0.00 01-JAN-00:10 8099.81 31-AUG-17:30
EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 7183.26 84470.28 02-JAN-05:00 370376.88 18-AUG-23:10
Heating:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 7183.26 84470.28 02-JAN-05:00 370376.88 18-AUG-23:10
General:Cooling:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 7183.26 84470.28 02-JAN-05:00 370376.88 18-AUG-23:10
PlantLoopHeatingDemand:Facility 1387.78 0.00 01-JAN-00:40 1545097.39 02-JAN-06:20
PlantLoopHeatingDemand:Plant 411.41 0.00 01-JAN-00:10 52104.84 08-FEB-12:20
WaterSystems:PlantLoopHeatingDemand 411.41 0.00 01-JAN-00:10 52104.84 08-FEB-12:20
General:WaterSystems:PlantLoopHeatingDemand 411.41 0.00 01-JAN-00:10 52104.84 08-FEB-12:20
EnergyTransfer:HVAC 21269.33 120391.67 02-JAN-04:40 3440594.58 24-AUG-16:40
HeatingCoils:EnergyTransfer 976.38 0.00 01-JAN-00:40 1538901.04 02-JAN-06:20
PlantLoopHeatingDemand:HVAC 976.38 0.00 01-JAN-00:40 1538901.04 02-JAN-06:20
HeatingCoils:PlantLoopHeatingDemand 976.38 0.00 01-JAN-00:40 1538901.04 02-JAN-06:20
CoolingCoils:EnergyTransfer 17464.46 104819.36 02-JAN-07:20 3206364.35 24-AUG-16:40
HeatRecoveryForHeating:EnergyTransfer 2106.45 0.00 01-JAN-00:10 869446.64 06-FEB-07:10
HeatRecoveryForCooling:EnergyTransfer 722.04 0.00 01-JAN-00:10 686377.87 04-AUG-14:00
EnergyTransfer:Plant 25743.93 0.00 01-JAN-00:40 8531484.10 24-AUG-16:40
LoopToLoop:EnergyTransfer 7755.34 0.00 01-JAN-00:10 2740148.84 24-AUG-16:40
WaterSystems:EnergyTransfer 411.41 0.00 01-JAN-00:10 52104.84 08-FEB-12:20
WaterUse:WaterSystems:EnergyTransfer 411.41 0.00 01-JAN-00:10 52104.84 08-FEB-12:20
Boilers:EnergyTransfer 967.40 0.00 01-JAN-00:40 1574263.18 02-JAN-05:10
Chillers:EnergyTransfer 7723.41 0.00 01-JAN-00:10 2628013.84 24-AUG-16:40
HeatRejection:EnergyTransfer 8886.37 0.00 01-JAN-00:10 2990905.55 24-AUG-16:40
General:HeatRejection:EnergyTransfer 8886.37 0.00 01-JAN-00:10 2990905.55 24-AUG-16:40
Water Heater:WaterSystems:PlantLoopHeatingDemand 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10



Table of Contents

Report: Sensible Heat Gain Summary

For: Entire Facility

Timestamp: 2023-10-16 08:43:34

Annual Building Sensible Heat Gain Components

HVAC Zone Eq & Other Sensible Air Heating [GJ] HVAC Zone Eq & Other Sensible Air Cooling [GJ] HVAC Terminal Unit Sensible Air Heating [GJ] HVAC Terminal Unit Sensible Air Cooling [GJ] HVAC Input Heated Surface Heating [GJ] HVAC Input Cooled Surface Cooling [GJ] People Sensible Heat Addition [GJ] Lights Sensible Heat Addition [GJ] Equipment Sensible Heat Addition [GJ] Window Heat Addition [GJ] Interzone Air Transfer Heat Addition [GJ] Infiltration Heat Addition [GJ] Opaque Surface Conduction and Other Heat Addition [GJ] Equipment Sensible Heat Removal [GJ] Window Heat Removal [GJ] Interzone Air Transfer Heat Removal [GJ] Infiltration Heat Removal [GJ] Opaque Surface Conduction and Other Heat Removal [GJ]
BASEMENT 0.000 0.000 2.740 -716.798 0.000 0.000 92.743 262.844 424.397 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 -65.927
CORE_BOTTOM 0.000 0.000 0.000 -656.152 0.000 0.000 83.491 236.053 289.614 0.000 0.000 0.000 46.995 0.000 0.000 0.000 0.000 -0.008
CORE_MID 0.000 0.000 10.921 -4701.370 0.000 0.000 850.858 2360.527 2896.128 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 -1417.064
CORE_TOP 0.000 0.000 10.018 -435.805 0.000 0.000 87.484 236.053 289.613 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 -187.362
PERIMETER_BOT_ZN_3 0.000 0.000 0.687 -77.322 0.000 0.000 10.862 17.435 36.365 35.004 0.000 0.115 51.464 0.000 -66.145 0.000 -8.466 0.000
PERIMETER_BOT_ZN_2 0.000 0.000 0.488 -73.726 0.000 0.000 7.037 11.188 23.435 64.425 0.000 0.086 12.960 0.000 -40.342 0.000 -5.550 0.000
PERIMETER_BOT_ZN_1 0.000 0.000 0.922 -124.041 0.000 0.000 10.750 17.172 36.366 131.565 0.000 0.114 0.001 0.000 -60.111 0.000 -8.523 -4.213
PERIMETER_BOT_ZN_4 0.000 0.000 0.096 -109.152 0.000 0.000 6.898 11.091 23.435 64.210 0.000 0.071 56.229 0.000 -46.712 0.000 -6.167 0.000
PERIMETER_MID_ZN_3 0.000 0.000 130.182 -540.617 0.000 0.000 113.427 174.001 363.654 361.682 0.000 2.511 153.807 0.000 -585.696 0.000 -172.950 -0.015
PERIMETER_MID_ZN_2 0.000 0.000 69.163 -619.993 0.000 0.000 53.458 111.713 234.352 646.274 0.000 1.697 0.000 0.000 -369.825 0.000 -117.226 -9.615
PERIMETER_MID_ZN_1 0.000 0.000 70.723 -1075.261 0.000 0.000 109.395 171.527 363.660 1312.004 0.000 2.429 0.021 0.000 -568.723 0.000 -185.612 -200.142
PERIMETER_MID_ZN_4 0.000 0.000 56.767 -677.247 0.000 0.000 72.929 110.759 234.351 656.793 0.000 1.662 61.015 0.000 -395.743 0.000 -121.287 -0.012
PERIMETER_TOP_ZN_3 0.000 0.000 28.804 -51.917 0.000 0.000 11.462 17.399 36.365 36.523 0.000 0.294 0.001 0.000 -55.295 0.000 -20.339 -3.297
PERIMETER_TOP_ZN_2 0.000 0.000 15.337 -59.745 0.000 0.000 7.315 11.171 23.435 64.891 0.000 0.199 0.001 0.000 -35.058 0.000 -13.828 -13.717
PERIMETER_TOP_ZN_1 0.000 0.000 17.651 -101.911 0.000 0.000 11.082 17.151 36.366 131.632 0.000 0.289 0.001 0.000 -53.672 0.000 -21.745 -36.844
PERIMETER_TOP_ZN_4 0.000 0.000 12.748 -65.634 0.000 0.000 7.365 11.075 23.435 65.789 0.000 0.199 0.001 0.000 -37.667 0.000 -14.339 -2.972
DATACENTER_BOT_ZN_6 0.000 0.000 0.006 -138.973 0.000 0.000 0.950 6.628 153.881 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 -22.492
DATACENTER_MID_ZN_6 0.000 0.000 4.385 -1197.448 0.000 0.000 9.512 66.280 1538.806 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 -421.534
DATACENTER_TOP_ZN_6 0.000 0.000 0.791 -111.193 0.000 0.000 0.953 6.628 153.881 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 -51.059
DATACENTER_BASEMENT_ZN_6 0.000 0.000 0.000 -7183.265 0.000 0.000 20.329 74.111 7494.857 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 -406.031
GROUNDFLOOR_PLENUM 2.846 -67.255 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.193 82.640 0.000 0.000 0.000 -18.424 0.000
MIDFLOOR_PLENUM 123.168 -445.585 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 3.439 624.529 0.000 0.000 0.000 -305.550 -0.002
TOPFLOOR_PLENUM 39.719 -69.516 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.286 61.661 0.000 0.000 0.000 -32.150 -0.003
Total Facility 165.733 -582.357 432.428 -18717.571 0.000 0.000 1568.300 3930.806 14676.396 3570.792 0.000 13.586 1151.326 0.000 -2314.989 0.000 -1052.156 -2842.309


Peak Cooling Sensible Heat Gain Components

Time of Peak {TIMESTAMP} HVAC Zone Eq & Other Sensible Air Heating [W] HVAC Zone Eq & Other Sensible Air Cooling [W] HVAC Terminal Unit Sensible Air Heating [W] HVAC Terminal Unit Sensible Air Cooling [W] HVAC Input Heated Surface Heating [W] HVAC Input Cooled Surface Cooling [W] People Sensible Heat Addition [W] Lights Sensible Heat Addition [W] Equipment Sensible Heat Addition [W] Window Heat Addition [W] Interzone Air Transfer Heat Addition [W] Infiltration Heat Addition [W] Opaque Surface Conduction and Other Heat Addition [W] Equipment Sensible Heat Removal [W] Window Heat Removal [W] Interzone Air Transfer Heat Removal [W] Infiltration Heat Removal [W] Opaque Surface Conduction and Other Heat Removal [W]
BASEMENT 05-JUN-04:11 0.00 0.00 0.00 -122948.44 0.00 0.00 0.00 2550.13 13457.54 0.00 0.00 0.00 106940.76 0.00 -0.00 0.00 0.00 0.00
CORE_BOTTOM 13-NOV-05:11 0.00 0.00 0.00 -102630.42 0.00 0.00 0.00 2290.20 5937.65 0.00 0.00 0.00 94402.58 0.00 -0.00 0.00 0.00 0.00
CORE_MID 07-AUG-04:12 0.00 0.00 0.00 -936204.77 0.00 0.00 0.00 22901.98 59376.23 0.00 0.00 0.00 853926.56 0.00 -0.00 0.00 0.00 0.00
CORE_TOP 07-AUG-04:12 0.00 0.00 0.00 -96572.98 0.00 0.00 0.00 2290.20 5937.62 0.00 0.00 0.00 88345.16 0.00 -0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_3 09-JUL-15:01 0.00 0.00 0.00 -19023.50 0.00 0.00 41.35 68.40 720.18 6988.81 0.00 0.00 11214.44 0.00 -0.00 0.00 -9.68 0.00
PERIMETER_BOT_ZN_2 04-SEP-08:41 0.00 0.00 0.00 -27245.44 0.00 0.00 18.45 44.08 464.11 19583.64 0.00 0.00 7194.30 0.00 -0.00 0.00 -59.15 0.00
PERIMETER_BOT_ZN_1 04-SEP-14:01 0.00 0.00 0.00 -30703.37 0.00 0.00 30.83 68.40 720.19 19622.54 0.00 0.00 10387.17 0.00 -0.00 0.00 -125.77 0.00
PERIMETER_BOT_ZN_4 18-JUN-15:41 0.00 0.00 0.00 -34127.53 0.00 0.00 15.68 44.08 464.11 21004.65 0.00 0.00 12737.50 0.00 -0.00 0.00 -138.50 0.00
PERIMETER_MID_ZN_3 13-AUG-15:01 0.00 0.00 0.00 -183285.25 0.00 0.00 413.77 684.02 7201.84 60567.90 0.00 1740.16 112677.56 0.00 -0.00 0.00 0.00 0.00
PERIMETER_MID_ZN_2 02-JUL-08:51 0.00 0.00 0.00 -304661.97 0.00 0.00 162.82 440.81 4641.14 198188.67 0.00 0.00 103052.11 0.00 -0.00 0.00 -1823.59 0.00
PERIMETER_MID_ZN_1 04-SEP-12:11 0.00 0.00 0.00 -324519.62 0.00 0.00 276.28 684.04 7201.95 257896.05 0.00 0.00 60943.70 0.00 -0.00 0.00 -2482.40 0.00
PERIMETER_MID_ZN_4 18-JUN-16:21 0.00 0.00 0.00 -317076.39 0.00 0.00 160.02 440.81 4641.11 186743.89 0.00 0.00 128709.75 0.00 -0.00 0.00 -3619.20 0.00
PERIMETER_TOP_ZN_3 13-AUG-15:01 0.00 0.00 0.00 -21288.83 0.00 0.00 39.10 68.40 720.18 5904.66 0.00 177.66 14378.82 0.00 -0.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_2 25-JUN-08:31 0.00 0.00 0.00 -29310.54 0.00 0.00 18.65 44.08 464.11 20411.40 0.00 0.00 8620.83 0.00 -0.00 0.00 -248.53 0.00
PERIMETER_TOP_ZN_1 10-SEP-14:41 0.00 0.00 0.00 -32973.35 0.00 0.00 30.75 68.40 720.19 15637.45 0.00 0.00 17227.94 0.00 -0.00 0.00 -711.39 0.00
PERIMETER_TOP_ZN_4 02-JUL-16:21 0.00 0.00 0.00 -33289.06 0.00 0.00 14.92 44.08 464.11 19652.74 0.00 0.00 13712.41 0.00 -0.00 0.00 -599.21 0.00
DATACENTER_BOT_ZN_6 23-APR-17:41 0.00 0.00 0.00 -8426.30 0.00 0.00 0.00 32.15 7794.42 0.00 0.00 0.00 599.73 0.00 -0.00 0.00 0.00 0.00
DATACENTER_MID_ZN_6 31-AUG-17:30 0.00 0.00 0.00 -79871.86 0.00 0.00 104.77 1929.04 77944.22 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 0.00 -106.17
DATACENTER_TOP_ZN_6 31-AUG-17:30 0.00 0.00 0.00 -8099.66 0.00 0.00 10.57 192.90 7794.42 0.00 0.00 0.00 101.77 0.00 -0.00 0.00 0.00 0.00
DATACENTER_BASEMENT_ZN_6 18-AUG-23:03 0.00 0.00 0.00 -370528.12 0.00 0.00 0.00 359.47 379632.52 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 0.00 -9463.87
GROUNDFLOOR_PLENUM 05-SEP-05:02 0.00 -14473.37 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 14522.36 0.00 -0.00 0.00 -48.98 0.00
MIDFLOOR_PLENUM 31-JAN-04:01 0.00 -113478.05 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 178813.14 0.00 -0.00 0.00 -65335.09 0.00
TOPFLOOR_PLENUM 19-JUN-13:30 0.00 -23582.80 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 317.73 23265.07 0.00 -0.00 0.00 0.00 0.00
Total Facility 28-AUG-04:12 0.00 65859.70 0.00 -2223433.24 0.00 0.00 0.00 42872.09 587299.42 0.00 0.00 0.00 1616090.57 0.00 -70062.34 0.00 -18626.19 0.00


Peak Heating Sensible Heat Gain Components

Time of Peak {TIMESTAMP} HVAC Zone Eq & Other Sensible Air Heating [W] HVAC Zone Eq & Other Sensible Air Cooling [W] HVAC Terminal Unit Sensible Air Heating [W] HVAC Terminal Unit Sensible Air Cooling [W] HVAC Input Heated Surface Heating [W] HVAC Input Cooled Surface Cooling [W] People Sensible Heat Addition [W] Lights Sensible Heat Addition [W] Equipment Sensible Heat Addition [W] Window Heat Addition [W] Interzone Air Transfer Heat Addition [W] Infiltration Heat Addition [W] Opaque Surface Conduction and Other Heat Addition [W] Equipment Sensible Heat Removal [W] Window Heat Removal [W] Interzone Air Transfer Heat Removal [W] Infiltration Heat Removal [W] Opaque Surface Conduction and Other Heat Removal [W]
BASEMENT 21-JUL-03:53 0.00 0.00 14212.29 0.00 0.00 0.00 0.00 1274.92 13457.54 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 0.00 -28944.76
CORE_BOTTOM - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CORE_MID 02-JAN-04:01 0.00 0.00 562841.91 0.00 0.00 0.00 0.00 11449.71 59376.23 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 0.00 -633667.85
CORE_TOP 02-JAN-04:01 0.00 0.00 87214.16 0.00 0.00 0.00 0.00 1144.97 5937.62 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 0.00 -94296.75
PERIMETER_BOT_ZN_3 02-JAN-04:01 0.00 0.00 14699.60 0.00 0.00 0.00 0.00 143.76 745.56 0.00 0.00 0.00 0.00 0.00 -7080.70 0.00 -633.68 -7874.54
PERIMETER_BOT_ZN_2 06-FEB-05:01 0.00 0.00 12722.63 0.00 0.00 0.00 0.00 185.31 480.47 0.00 0.00 0.00 0.00 0.00 -5010.79 0.00 -1370.03 -7007.59
PERIMETER_BOT_ZN_1 02-JAN-04:01 0.00 0.00 19849.78 0.00 0.00 0.00 0.00 143.77 745.57 0.00 0.00 0.00 0.00 0.00 -6704.68 0.00 -616.36 -13418.08
PERIMETER_BOT_ZN_4 02-JAN-05:01 0.00 0.00 10935.72 0.00 0.00 0.00 0.00 185.31 480.46 0.00 0.00 0.00 0.00 0.00 -4879.49 0.00 -467.69 -6254.31
PERIMETER_MID_ZN_3 02-JAN-02:42 0.00 0.00 165653.63 0.00 0.00 0.00 0.00 1437.63 7455.61 0.00 0.00 0.00 0.00 0.00 -62114.72 0.00 -15101.20 -97330.94
PERIMETER_MID_ZN_2 01-JAN-05:22 0.00 0.00 212558.59 0.00 0.00 0.00 0.00 926.46 3603.51 0.00 0.00 0.00 0.00 0.00 -28215.10 0.00 -18122.83 -170750.63
PERIMETER_MID_ZN_1 01-JAN-05:22 0.00 0.00 240706.05 0.00 0.00 0.00 0.00 1437.66 5591.79 0.00 0.00 0.00 0.00 0.00 -44145.16 0.00 -26817.92 -176772.43
PERIMETER_MID_ZN_4 02-JAN-02:42 0.00 0.00 213340.01 0.00 0.00 0.00 0.00 926.46 4804.65 0.00 0.00 0.00 0.00 0.00 -41957.88 0.00 -10452.23 -166661.01
PERIMETER_TOP_ZN_3 06-FEB-04:11 0.00 0.00 19760.55 0.00 0.00 0.00 0.00 143.76 745.56 0.00 0.00 0.00 0.00 0.00 -6558.78 0.00 -4570.96 -9520.13
PERIMETER_TOP_ZN_2 06-FEB-04:11 0.00 0.00 24041.38 0.00 0.00 0.00 0.00 92.65 480.47 0.00 0.00 0.00 0.00 0.00 -4238.00 0.00 -3113.18 -17263.32
PERIMETER_TOP_ZN_1 06-FEB-04:11 0.00 0.00 27555.87 0.00 0.00 0.00 0.00 143.77 745.57 0.00 0.00 0.00 0.00 0.00 -6434.67 0.00 -4674.38 -17336.15
PERIMETER_TOP_ZN_4 06-FEB-04:11 0.00 0.00 25735.01 0.00 0.00 0.00 0.00 92.65 480.46 0.00 0.00 0.00 0.00 0.00 -4472.76 0.00 -3166.67 -18668.69
DATACENTER_BOT_ZN_6 01-JAN-20:42 0.00 0.00 453.39 0.00 0.00 0.00 0.00 32.15 1948.61 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 0.00 -2434.15
DATACENTER_MID_ZN_6 15-JAN-18:00 0.00 0.00 5714.38 0.00 0.00 0.00 55.60 321.53 19486.06 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 0.00 -25577.56
DATACENTER_TOP_ZN_6 16-JAN-18:00 0.00 0.00 610.17 0.00 0.00 0.00 6.35 32.15 1948.61 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 0.00 -2597.27
DATACENTER_BASEMENT_ZN_6 - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
GROUNDFLOOR_PLENUM 26-DEC-05:11 13699.66 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 -1038.26 -12661.40
MIDFLOOR_PLENUM 02-JAN-06:12 205003.51 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 -6446.28 -198557.23
TOPFLOOR_PLENUM 06-FEB-05:09 33599.83 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 -7910.90 -25688.93
Total Facility 02-JAN-05:21 51517.39 101080.11 1534222.61 -101080.11 0.00 0.00 0.00 42872.09 232425.23 0.00 0.00 0.00 0.00 0.00 -263064.03 0.00 -94827.10 -1503146.19



Table of Contents

Report: Standard 62.1 Summary

For: Entire Facility

Timestamp: 2023-10-16 08:43:34

System Ventilation Requirements for Cooling

Sum of Zone Primary Air Flow - Vpz-sum [m3/s] System Population - Ps Sum of Zone Population - Pz-sum Occupant Diversity - D Origin of D Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] System Primary Airflow - Vps [m3/s] Average Outdoor Air Fraction - Xs System Ventilation Efficiency - Ev Calculation Method for Ev Outdoor Air Intake Flow - Vot [m3/s] Percent Outdoor Air - %OA Environment Name of Peak System Population - Ps Date and Time of Last Peak System Population - Ps
VAV_BOT WITH REHEAT 11.8035 0.0000 0.0000 1.0000 Calculated from schedules 0.0000 10.3915 0.0000 1.0000 Not calculated 0.0000 0.0000    
VAV_MID WITH REHEAT 113.8037 0.0000 0.0000 1.0000 Calculated from schedules 0.0000 97.9338 0.0000 1.0000 Not calculated 0.0000 0.0000    
VAV_TOP WITH REHEAT 11.8176 0.0000 0.0000 1.0000 Calculated from schedules 0.0000 10.6653 0.0000 1.0000 Not calculated 0.0000 0.0000    
CAV_BAS 5.9587 0.0000 149.6021 1.0000 Calculated from schedules 1.2002 5.9587 0.2014 1.0000 Not calculated 1.2002 0.2014    
AIRLOOP DATACENTER BASEMENT 21.4115 0.0000 42.1814 1.0000 Calculated from schedules 0.3384 21.4116 0.0158 1.0000 Not calculated 0.3384 0.0158    
AIRLOOP DATACENTER BOT 0.4934 0.0000 1.9486 1.0000 Calculated from schedules 0.0156 0.4934 0.0317 1.0000 Not calculated 0.0156 0.0317    
AIRLOOP DATACENTER MID 4.7272 0.0000 19.4861 1.0000 Calculated from schedules 0.1563 4.7272 0.0331 1.0000 Not calculated 0.1563 0.0331    
AIRLOOP DATACENTER TOP 0.4812 0.0000 1.9486 1.0000 Calculated from schedules 0.0156 0.4812 0.0325 1.0000 Not calculated 0.0156 0.0325    


System Ventilation Requirements for Heating

Sum of Zone Primary Air Flow - Vpz-sum [m3/s] System Population - Ps Sum of Zone Population - Pz-sum Occupant Diversity - D Origin of D Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] System Primary Airflow - Vps [m3/s] Average Outdoor Air Fraction - Xs System Ventilation Efficiency - Ev Calculation Method for Ev Outdoor Air Intake Flow Vot [m3/s] Percent Outdoor Air - %OA Environment Name of Peak System Population - Ps Date and Time of Last Peak System Population - Ps
VAV_BOT WITH REHEAT 5.9018 0.0000 0.0000 1.0000 Calculated from schedules 0.0000 3.1277 0.0000 1.0000 Not calculated 0.0000 0.0000    
VAV_MID WITH REHEAT 56.9018 0.0000 0.0000 1.0000 Calculated from schedules 0.0000 30.8146 0.0000 1.0000 Not calculated 0.0000 0.0000    
VAV_TOP WITH REHEAT 5.9088 0.0000 0.0000 1.0000 Calculated from schedules 0.0000 3.1823 0.0000 1.0000 Not calculated 0.0000 0.0000    
CAV_BAS 5.9587 0.0000 149.6021 1.0000 Calculated from schedules 1.2002 5.9587 1.0000 1.0000 Not calculated 1.2002 0.2014    
AIRLOOP DATACENTER BASEMENT 21.4115 0.0000 42.1814 1.0000 Calculated from schedules 0.3384 21.4115 1.0000 1.0000 Not calculated 0.3384 0.0158    
AIRLOOP DATACENTER BOT 0.4934 0.0000 1.9486 1.0000 Calculated from schedules 0.0156 0.4934 1.0000 1.0000 Not calculated 0.0156 0.0317    
AIRLOOP DATACENTER MID 4.7272 0.0000 19.4861 1.0000 Calculated from schedules 0.1563 4.7272 1.0000 1.0000 Not calculated 0.1563 0.0331    
AIRLOOP DATACENTER TOP 0.4812 0.0000 1.9486 1.0000 Calculated from schedules 0.0156 0.4812 1.0000 1.0000 Not calculated 0.0156 0.0325    


Zone Ventilation Parameters

AirLoop Name People Outdoor Air Rate - Rp [m3/s-person] Zone Population - Pz Area Outdoor Air Rate - Ra [m3/s-m2] Zone Floor Area - Az [m2] Breathing Zone Outdoor Airflow - Vbz [m3/s] Cooling Zone Air Distribution Effectiveness - Ez-clg Cooling Zone Outdoor Airflow - Voz-clg [m3/s] Heating Zone Air Distribution Effectiveness - Ez-htg Heating Zone Outdoor Airflow - Voz-htg [m3/s]
BASEMENT CAV_BAS 0.000000 149.6021 0.000432 2779.43 1.2002 1.0000 1.2002 1.000 1.2002
CORE_BOTTOM VAV_BOT WITH REHEAT 0.000000 134.3532 0.000432 2496.12 0.0000 1.0000 0.0000 1.000 0.0000
CORE_MID VAV_MID WITH REHEAT 0.000000 1343.5320 0.000432 24961.20 0.0000 1.0000 0.0000 1.000 0.0000
CORE_TOP VAV_TOP WITH REHEAT 0.000000 134.3532 0.000432 2496.12 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_BOT_ZN_3 VAV_BOT WITH REHEAT 0.000000 16.8694 0.000432 313.41 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_BOT_ZN_2 VAV_BOT WITH REHEAT 0.000000 10.8713 0.000432 201.98 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_BOT_ZN_1 VAV_BOT WITH REHEAT 0.000000 16.8698 0.000432 313.42 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_BOT_ZN_4 VAV_BOT WITH REHEAT 0.000000 10.8713 0.000432 201.98 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_MID_ZN_3 VAV_MID WITH REHEAT 0.000000 168.6939 0.000432 3134.13 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_MID_ZN_2 VAV_MID WITH REHEAT 0.000000 108.7127 0.000432 2019.75 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_MID_ZN_1 VAV_MID WITH REHEAT 0.000000 168.6975 0.000432 3134.20 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_MID_ZN_4 VAV_MID WITH REHEAT 0.000000 108.7127 0.000432 2019.75 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_TOP_ZN_3 VAV_TOP WITH REHEAT 0.000000 16.8694 0.000432 313.41 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_TOP_ZN_2 VAV_TOP WITH REHEAT 0.000000 10.8713 0.000432 201.98 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_TOP_ZN_1 VAV_TOP WITH REHEAT 0.000000 16.8698 0.000432 313.42 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_TOP_ZN_4 VAV_TOP WITH REHEAT 0.000000 10.8713 0.000432 201.98 0.0000 1.0000 0.0000 1.000 0.0000
DATACENTER_BOT_ZN_6 AIRLOOP DATACENTER BOT 0.000000 1.9486 0.000432 36.20 0.0156 1.0000 0.0156 1.000 0.0156
DATACENTER_MID_ZN_6 AIRLOOP DATACENTER MID 0.000000 19.4861 0.000432 362.03 0.1563 1.0000 0.1563 1.000 0.1563
DATACENTER_TOP_ZN_6 AIRLOOP DATACENTER TOP 0.000000 1.9486 0.000432 36.20 0.0156 1.0000 0.0156 1.000 0.0156
DATACENTER_BASEMENT_ZN_6 AIRLOOP DATACENTER BASEMENT 0.000000 42.1814 0.000432 783.68 0.3384 1.0000 0.3384 1.000 0.3384


System Ventilation Parameters

People Outdoor Air Rate - Rp [m3/s-person] Sum of Zone Population - Pz-sum Area Outdoor Air Rate - Ra [m3/s-m2] Sum of Zone Floor Area - Az-sum [m2] Breathing Zone Outdoor Airflow - Vbz [m3/s] Cooling Zone Outdoor Airflow - Voz-clg [m3/s] Heating Zone Outdoor Airflow - Voz-htg [m3/s]
VAV_BOT WITH REHEAT   0.00 0.000432 3526.9033 0.0000 0.0000 0.0000
VAV_MID WITH REHEAT   0.00 0.000432 35269.0328 0.0000 0.0000 0.0000
VAV_TOP WITH REHEAT   0.00 0.000432 3526.9033 0.0000 0.0000 0.0000
CAV_BAS 0.000000 149.60 0.000432 2779.4266 1.2002 1.2002 1.2002
AIRLOOP DATACENTER BASEMENT 0.000000 42.18 0.000432 783.6794 0.3384 0.3384 0.3384
AIRLOOP DATACENTER BOT 0.000000 1.95 0.000432 36.2027 0.0156 0.0156 0.0156
AIRLOOP DATACENTER MID 0.000000 19.49 0.000432 362.0274 0.1563 0.1563 0.1563
AIRLOOP DATACENTER TOP 0.000000 1.95 0.000432 36.2027 0.0156 0.0156 0.0156


Zone Ventilation Calculations for Cooling Design

AirLoop Name Box Type Zone Primary Airflow - Vpz [m3/s] Zone Discharge Airflow - Vdz [m3/s] Minimum Zone Primary Airflow - Vpz-min [m3/s] Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? Zone Outdoor Airflow Cooling - Voz-clg [m3/s] Primary Outdoor Air Fraction - Zpz Primary Air Fraction - Ep Secondary Recirculation Fraction- Er Supply Air Fraction- Fa Mixed Air Fraction - Fb Outdoor Air Fraction - Fc Zone Ventilation Efficiency - Evz
BASEMENT CAV_BAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 5.9587 5.9587 5.9587 No 1.2002 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CORE_BOTTOM VAV_BOT WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 6.1895 6.1895 1.9745 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CORE_MID VAV_MID WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 58.3975 58.3975 19.3880 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CORE_TOP VAV_TOP WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 5.9169 5.9169 1.9881 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_BOT_ZN_3 VAV_BOT WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.0881 1.0881 0.2481 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_BOT_ZN_2 VAV_BOT WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.3442 1.3442 0.2688 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_BOT_ZN_1 VAV_BOT WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.5555 1.5555 0.3111 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_BOT_ZN_4 VAV_BOT WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.6262 1.6262 0.3252 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_MID_ZN_3 VAV_MID WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 10.4674 10.4674 2.4389 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_MID_ZN_2 VAV_MID WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 14.3639 14.3639 2.8728 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_MID_ZN_1 VAV_MID WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 15.5297 15.5297 3.1059 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_MID_ZN_4 VAV_MID WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 15.0452 15.0452 3.0090 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_TOP_ZN_3 VAV_TOP WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.1772 1.1772 0.2496 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_TOP_ZN_2 VAV_TOP WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.4593 1.4593 0.2919 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_TOP_ZN_1 VAV_TOP WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.6745 1.6745 0.3349 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_TOP_ZN_4 VAV_TOP WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.5897 1.5897 0.3179 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
DATACENTER_BOT_ZN_6 AIRLOOP DATACENTER BOT AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.4934 0.4934 0.4934 No 0.0156 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
DATACENTER_MID_ZN_6 AIRLOOP DATACENTER MID AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 4.7272 4.7272 4.7272 No 0.1563 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
DATACENTER_TOP_ZN_6 AIRLOOP DATACENTER TOP AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.4812 0.4812 0.4812 No 0.0156 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
DATACENTER_BASEMENT_ZN_6 AIRLOOP DATACENTER BASEMENT AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 21.4115 21.4115 21.4115 No 0.3384 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000


System Ventilation Calculations for Cooling Design

Sum of Zone Primary Airflow - Vpz-sum [m3/s] System Primary Airflow - Vps [m3/s] Sum of Zone Discharge Airflow - Vdz-sum [m3/s] Sum of Min Zone Primary Airflow - Vpz-min [m3/s] Zone Outdoor Airflow Cooling - Voz-clg [m3/s] Zone Ventilation Efficiency - Evz-min
VAV_BOT WITH REHEAT 11.8035 10.3915 11.8035 3.1277 0.0000 1.0000
VAV_MID WITH REHEAT 113.8037 97.9338 113.8037 30.8146 0.0000 1.0000
VAV_TOP WITH REHEAT 11.8176 10.6653 11.8176 3.1823 0.0000 1.0000
CAV_BAS 5.9587 5.9587 5.9587 5.9587 1.2002 1.0000
AIRLOOP DATACENTER BASEMENT 21.4115 21.4116 21.4115 21.4115 0.3384 1.0000
AIRLOOP DATACENTER BOT 0.4934 0.4934 0.4934 0.4934 0.0156 1.0000
AIRLOOP DATACENTER MID 4.7272 4.7272 4.7272 4.7272 0.1563 1.0000
AIRLOOP DATACENTER TOP 0.4812 0.4812 0.4812 0.4812 0.0156 1.0000


Zone Ventilation Calculations for Heating Design

AirLoop Name Box Type Zone Primary Airflow - Vpz [m3/s] Zone Discharge Airflow - Vdz [m3/s] Minimum Zone Primary Airflow - Vpz-min [m3/s] Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? Zone Outdoor Airflow Heating - Voz-htg [m3/s] Primary Outdoor Air Fraction - Zpz Primary Air Fraction - Ep Secondary Recirculation Fraction- Er Supply Air Fraction- Fa Mixed Air Fraction - Fb Outdoor Air Fraction - Fc Zone Ventilation Efficiency - Evz
BASEMENT CAV_BAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 5.9587 5.9587 5.9587 No 1.2002 1.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CORE_BOTTOM VAV_BOT WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 3.0948 3.0948 1.9745 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CORE_MID VAV_MID WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 29.1988 29.1988 19.3880 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CORE_TOP VAV_TOP WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 2.9584 2.9584 1.9881 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_BOT_ZN_3 VAV_BOT WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.5440 0.5440 0.2481 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_BOT_ZN_2 VAV_BOT WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.6721 0.6721 0.2688 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_BOT_ZN_1 VAV_BOT WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.7778 0.7778 0.3111 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_BOT_ZN_4 VAV_BOT WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.8131 0.8131 0.3252 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_MID_ZN_3 VAV_MID WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 5.2337 5.2337 2.4389 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_MID_ZN_2 VAV_MID WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 7.1819 7.1819 2.8728 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_MID_ZN_1 VAV_MID WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 7.7648 7.7648 3.1059 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_MID_ZN_4 VAV_MID WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 7.5226 7.5226 3.0090 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_TOP_ZN_3 VAV_TOP WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.5886 0.5886 0.2496 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_TOP_ZN_2 VAV_TOP WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.7297 0.7297 0.2919 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_TOP_ZN_1 VAV_TOP WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.8372 0.8372 0.3349 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_TOP_ZN_4 VAV_TOP WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.7949 0.7949 0.3179 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
DATACENTER_BOT_ZN_6 AIRLOOP DATACENTER BOT AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.4934 0.4934 0.4934 No 0.0156 1.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
DATACENTER_MID_ZN_6 AIRLOOP DATACENTER MID AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 4.7272 4.7272 4.7272 No 0.1563 1.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
DATACENTER_TOP_ZN_6 AIRLOOP DATACENTER TOP AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.4812 0.4812 0.4812 No 0.0156 1.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
DATACENTER_BASEMENT_ZN_6 AIRLOOP DATACENTER BASEMENT AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 21.4115 21.4115 21.4115 No 0.3384 1.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000


System Ventilation Calculations for Heating Design

Sum of Zone Primary Airflow - Vpz-sum [m3/s] System Primary Airflow - Vps [m3/s] Sum of Zone Discharge Airflow - Vdz-sum [m3/s] Sum of Min Zone Primary Airflow - Vpz-min [m3/s] Zone Outdoor Airflow Heating - Voz-htg [m3/s] Zone Ventilation Efficiency - Evz-min
VAV_BOT WITH REHEAT 5.9018 3.1277 3.1277 3.1277 0.0000 1.0000
VAV_MID WITH REHEAT 56.9018 30.8146 30.8146 30.8146 0.0000 1.0000
VAV_TOP WITH REHEAT 5.9088 3.1823 3.1823 3.1823 0.0000 1.0000
CAV_BAS 5.9587 5.9587 5.9587 5.9587 1.2002 1.0000
AIRLOOP DATACENTER BASEMENT 21.4115 21.4115 21.4115 21.4115 0.3384 1.0000
AIRLOOP DATACENTER BOT 0.4934 0.4934 0.4934 0.4934 0.0156 1.0000
AIRLOOP DATACENTER MID 4.7272 4.7272 4.7272 4.7272 0.1563 1.0000
AIRLOOP DATACENTER TOP 0.4812 0.4812 0.4812 0.4812 0.0156 1.0000



Table of Contents

Report: LEED Summary

For: Entire Facility

Timestamp: 2023-10-16 08:43:34

Sec1.1A-General Information

Data
Weather File RUNPERIOD 1 ** New York-John F Kennedy Intl AP NY USA TMY3 WMO#=744860
Total gross floor area [m2] 46320.38
Principal Heating Source Natural Gas


EAp2-1. Space Usage Type

Space Area [m2] Regularly Occupied Area [m2] Unconditioned Area [m2] Typical Hours/Week in Operation [hr/wk]
BASEMENT 2779.43 2779.43 0.00 113.98
CORE_BOTTOM 2496.12 2496.12 0.00 113.98
CORE_MID 2496.12 2496.12 0.00 113.98
CORE_TOP 2496.12 2496.12 0.00 113.98
PERIMETER_BOT_ZN_3 313.41 313.41 0.00 113.98
PERIMETER_BOT_ZN_2 201.98 201.98 0.00 113.98
PERIMETER_BOT_ZN_1 313.42 313.42 0.00 113.98
PERIMETER_BOT_ZN_4 201.98 201.98 0.00 113.98
PERIMETER_MID_ZN_3 313.41 313.41 0.00 113.98
PERIMETER_MID_ZN_2 201.98 201.98 0.00 96.54
PERIMETER_MID_ZN_1 313.42 313.42 0.00 113.98
PERIMETER_MID_ZN_4 201.98 201.98 0.00 113.98
PERIMETER_TOP_ZN_3 313.41 313.41 0.00 113.98
PERIMETER_TOP_ZN_2 201.98 201.98 0.00 113.98
PERIMETER_TOP_ZN_1 313.42 313.42 0.00 113.98
PERIMETER_TOP_ZN_4 201.98 201.98 0.00 113.98
DATACENTER_BOT_ZN_6 36.20 36.20 0.00 113.98
DATACENTER_MID_ZN_6 36.20 36.20 0.00 113.98
DATACENTER_TOP_ZN_6 36.20 36.20 0.00 113.98
DATACENTER_BASEMENT_ZN_6 783.68 783.68 0.00 113.98
GROUNDFLOOR_PLENUM 3563.11 3563.11 0.00 0.00
MIDFLOOR_PLENUM 3563.11 3563.11 0.00 0.00
TOPFLOOR_PLENUM 3563.11 3563.11 0.00 0.00
Totals 46320.38 46320.38 0.00  


EAp2-2. Advisory Messages

Data
Number of hours heating loads not met 43.83
Number of hours cooling loads not met 465.83
Number of hours not met 509.67


EAp2-3. Energy Type Summary

Utility Rate Virtual Rate [$/unit energy] Units of Energy Units of Demand
None        


EAp2-4/5. Performance Rating Method Compliance

Electricity Energy Use [GJ] Electricity Demand [W] Natural Gas Energy Use [GJ] Natural Gas Demand [W] Gasoline Use [GJ] Gasoline Demand [W] Diesel Use [GJ] Diesel Demand [W] Coal Use [GJ] Coal Demand [W] Fuel Oil No 1 Use [GJ] Fuel Oil No 1 Demand [W] Fuel Oil No 2 Use [GJ] Fuel Oil No 2 Demand [W] Propane Use [GJ] Propane Demand [W] Other Fuel 1 Use [GJ] Other Fuel 1 Demand [W] Other Fuel 2 Use [GJ] Other Fuel 2 Demand [W] District Cooling Use [GJ] District Cooling Demand [W] District Heating Use [GJ] District Heating Demand [W]
Heating -- General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heating -- Boiler 0.00 0.00 1354.97 1892175.57 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heating -- Boiler Parasitic 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling -- General 3703.58 548047.79 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting -- LightsWired 3930.81 385834.94 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting -- General 698.54 57580.60 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- MiscPlug 5334.97 305206.10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- DataCenterPlugLoads 9341.42 473165.59 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment -- Transformer 80.18 5057.48 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment -- ElevatorLift 1848.78 113101.96 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment -- ElevatorLightsFan 5.83 376.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans -- General 2439.82 314543.08 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps -- General 476.45 68118.46 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection -- General 1159.17 93402.74 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification -- General 14.23 6186.06 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery -- General 54.36 5613.48 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems -- General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems -- WaterUse 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems -- Water Heater 0.00 0.00 783.71 84953.67 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration -- Not Subdivided 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators -- General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


EAp2-6. Energy Use Summary

Process Subtotal [GJ] Total Energy Use [GJ]
Electricity 14676.40 29088.15
Natural Gas 0.00 2138.67
Additional 0.00 0.00
Total 14676.40 31226.82


EAp2-7. Energy Cost Summary

Process Subtotal [$] Total Energy Cost [$]
Electricity 0.00  
Natural Gas 0.00  
Additional 0.00  
Total 0.00  
Process energy cost based on ratio of process to total energy.

L-1. Renewable Energy Source Summary

Rated Capacity [kW] Annual Energy Generated [GJ]
Photovoltaic 0.00 0.00
Wind 0.00 0.00


EAp2-17a. Energy Use Intensity - Electricity

Electricty [MJ/m2]
Interior Lighting (All) 84.86
Space Heating 0.00
Space Cooling 79.96
Fans (All) 52.67
Service Water Heating 0.00
Receptacle Equipment 316.85
Miscellaneous (All) 627.98
Subtotal 627.98


EAp2-17b. Energy Use Intensity - Natural Gas

Natural Gas [MJ/m2]
Space Heating 29.25
Service Water Heating 16.92
Miscellaneous (All) 46.17
Subtotal 46.17


EAp2-17c. Energy Use Intensity - Additional

Additional [MJ/m2]
Subtotal 0.00
Miscellaneous 0.00


EAp2-18. End Use Percentage

Percent [%]
Interior Lighting (All) 12.59
Space Heating 4.34
Space Cooling 11.86
Fans (All) 7.81
Service Water Heating 2.51
Receptacle Equipment 47.00
Miscellaneous 13.89


Schedules-Equivalent Full Load Hours (Schedule Type=Fraction)

Equivalent Full Load Hours of Operation Per Year [hr] Hours > 1% [hr]
EXTERIOR_LIGHTING_SCHEDULE_A 6570. 6570.
EXTERIOR_LIGHTING_SCHEDULE_B 8103. 8760.
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 4472. 4472.
EXTERIOR_LIGHTING_SCHEDULE_B_2016 7665. 8760.
EXTERIOR_LIGHTING_SCHEDULE_C_2016 6752. 8760.
ALWAYS_ON 8760. 8760.
EXTERIOR_LGT_ALWAYS_ON 8760. 8760.
EXTERIOR_LGT_189_1 6828. 8760.
ALWAYS_OFF 0. 0.
LTG_SCH_OFFICE 2625. 8760.
LTG_SCH_DATACENTER 2921. 8760.
EXTERIOR_LIGHT_SCH 4380. 4380.
BLDG_EQUIP_SCH 4049. 8760.
DATACENTER_EQUIP_SCH 5478. 8760.
BLDG_OCC_SCH 2528. 5992.
BLDG_OCC_SCH_W_SB 1878. 5056.
BLDG_OCC_SCH_WO_SB 2557. 5992.
BLDG_ELEVATORS 2270. 8760.
ELEV_LIGHT_FAN_SCH_24_7 8760. 8760.
ELEV_LIGHT_FAN_SCH_ADD_DF 2154. 8760.
BLDG_SWH_SCH 1474. 6570.
WORK_EFF_SCH 0. 0.
INFIL_SCH 3976. 3976.
INFIL_SCH_PNNL 5172. 8760.
INFIL_HALF_ON_SCH 6368. 8760.
FAN_SCH 8760. 8760.
REHEATCOILAVAILSCHED 8760. 8760.
COOLINGCOILAVAILSCHED 8760. 8760.
MINOA_MOTORIZEDDAMPER_SCHED 4472. 4472.
MINOA_SCHED 8760. 8760.
CORE_BOTTOM SUB CAT LATENT FRACT SCHED 438. 8760.
CORE_BOTTOM SUB CAT SENSIBLE FRACT SCHED 1752. 8760.
CORE_MID SUB CAT LATENT FRACT SCHED 438. 8760.
CORE_MID SUB CAT SENSIBLE FRACT SCHED 1752. 8760.
CORE_TOP SUB CAT LATENT FRACT SCHED 438. 8760.
CORE_TOP SUB CAT SENSIBLE FRACT SCHED 1752. 8760.
SUPPLYFANSCH 8760. 8760.
PERIMETER_MID_ZN_2_MDP_SCH 1565. 7824.


Schedules-SetPoints (Schedule Type=Temperature)

First Object Used Month Assumed 11am First Wednesday [C] Days with Same 11am Value 11pm First Wednesday [C] Days with Same 11pm Value
HTGSETP_DC_SCH DATACENTER COOLING SETPOINTS DUAL SP CONTROL January 18.00 365 18.00 365
CLGSETP_DC_SCH DATACENTER COOLING SETPOINTS DUAL SP CONTROL July 27.00 365 27.00 365
HTGSETP_SCH_YES_OPTIMUM CORE_BOTTOM DUAL SP CONTROL January 21.00 365 15.60 365
CLGSETP_SCH_YES_OPTIMUM CORE_BOTTOM DUAL SP CONTROL July 24.00 365 26.70 365



Table of Contents

Report: Annual Thermal Resilience Summary

For: Entire Facility

Timestamp: 2023-10-16 08:43:34

Heat Index Hours

Safe (≤ 26.7°C) [hr] Caution (> 26.7, ≤ 32.2°C) [hr] Extreme Caution (> 32.2, ≤ 39.4°C) [hr] Danger (> 39.4, ≤ 51.7°C) [hr] Extreme Danger (> 51.7°C) [hr]
BASEMENT 8146.33 613.67 0.00 0.00 0.00
CORE_BOTTOM 8716.83 43.17 0.00 0.00 0.00
CORE_MID 8754.83 5.17 0.00 0.00 0.00
CORE_TOP 8745.67 14.33 0.00 0.00 0.00
PERIMETER_BOT_ZN_3 8736.33 23.67 0.00 0.00 0.00
PERIMETER_BOT_ZN_2 8700.83 59.17 0.00 0.00 0.00
PERIMETER_BOT_ZN_1 8675.50 84.50 0.00 0.00 0.00
PERIMETER_BOT_ZN_4 8256.83 503.17 0.00 0.00 0.00
PERIMETER_MID_ZN_3 8708.83 51.17 0.00 0.00 0.00
PERIMETER_MID_ZN_2 8646.33 113.67 0.00 0.00 0.00
PERIMETER_MID_ZN_1 8610.33 149.67 0.00 0.00 0.00
PERIMETER_MID_ZN_4 8404.00 356.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_3 8670.50 89.50 0.00 0.00 0.00
PERIMETER_TOP_ZN_2 8624.50 135.50 0.00 0.00 0.00
PERIMETER_TOP_ZN_1 8597.67 162.33 0.00 0.00 0.00
PERIMETER_TOP_ZN_4 8425.33 334.67 0.00 0.00 0.00
DATACENTER_BOT_ZN_6 6096.17 2663.83 0.00 0.00 0.00
DATACENTER_MID_ZN_6 6097.83 2662.17 0.00 0.00 0.00
DATACENTER_TOP_ZN_6 6072.33 2687.67 0.00 0.00 0.00
DATACENTER_BASEMENT_ZN_6 5895.83 2864.17 0.00 0.00 0.00
GROUNDFLOOR_PLENUM 8760.00 0.00 0.00 0.00 0.00
MIDFLOOR_PLENUM 8760.00 0.00 0.00 0.00 0.00
TOPFLOOR_PLENUM 8650.67 109.33 0.00 0.00 0.00
Min 5895.83 0.00 0.00 0.00 0.00
Max 8760.00 2864.17 0.00 0.00 0.00
Average 8163.20 596.80 0.00 0.00 0.00
Sum 187753.50 13726.50 0.00 0.00 0.00


Heat Index OccupantHours

Safe (≤ 26.7°C) [hr] Caution (> 26.7, ≤ 32.2°C) [hr] Extreme Caution (> 32.2, ≤ 39.4°C) [hr] Danger (> 39.4, ≤ 51.7°C) [hr] Extreme Danger (> 51.7°C) [hr]
BASEMENT 367029.33 1586.67 0.00 0.00 0.00
CORE_BOTTOM 330772.00 41.00 0.00 0.00 0.00
CORE_MID 330813.00 0.00 0.00 0.00 0.00
CORE_TOP 330794.00 19.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_3 38925.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_2 24909.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_1 38925.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_4 24909.00 0.00 0.00 0.00 0.00
PERIMETER_MID_ZN_3 38925.00 0.00 0.00 0.00 0.00
PERIMETER_MID_ZN_2 18354.00 0.00 0.00 0.00 0.00
PERIMETER_MID_ZN_1 38925.00 0.00 0.00 0.00 0.00
PERIMETER_MID_ZN_4 24909.00 0.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_3 38925.00 0.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_2 24909.00 0.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_1 38925.00 0.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_4 24909.00 0.00 0.00 0.00 0.00
DATACENTER_BOT_ZN_6 1299.33 968.67 0.00 0.00 0.00
DATACENTER_MID_ZN_6 1294.83 973.17 0.00 0.00 0.00
DATACENTER_TOP_ZN_6 1291.83 976.17 0.00 0.00 0.00
DATACENTER_BASEMENT_ZN_6 60904.17 42490.83 0.00 0.00 0.00
GROUNDFLOOR_PLENUM 0.00 0.00 0.00 0.00 0.00
MIDFLOOR_PLENUM 0.00 0.00 0.00 0.00 0.00
TOPFLOOR_PLENUM 0.00 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00 0.00
Max 367029.33 42490.83 0.00 0.00 0.00
Average 78289.02 2045.89 0.00 0.00 0.00
Sum 1800647.50 47055.50 0.00 0.00 0.00


Humidex Hours

Little to no Discomfort (≤ 29) [hr] Some Discomfort (> 29, ≤ 40) [hr] Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] Dangerous (> 45, ≤ 50) [hr] Heat Stroke Quite Possible (> 50) [hr]
BASEMENT 7093.17 1666.83 0.00 0.00 0.00
CORE_BOTTOM 8013.50 746.50 0.00 0.00 0.00
CORE_MID 7887.83 872.17 0.00 0.00 0.00
CORE_TOP 7957.33 802.67 0.00 0.00 0.00
PERIMETER_BOT_ZN_3 7886.67 873.33 0.00 0.00 0.00
PERIMETER_BOT_ZN_2 8242.00 518.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_1 7903.50 856.50 0.00 0.00 0.00
PERIMETER_BOT_ZN_4 7564.33 1195.67 0.00 0.00 0.00
PERIMETER_MID_ZN_3 7867.33 892.67 0.00 0.00 0.00
PERIMETER_MID_ZN_2 7896.83 863.17 0.00 0.00 0.00
PERIMETER_MID_ZN_1 7773.67 986.33 0.00 0.00 0.00
PERIMETER_MID_ZN_4 7766.33 993.67 0.00 0.00 0.00
PERIMETER_TOP_ZN_3 7867.67 892.33 0.00 0.00 0.00
PERIMETER_TOP_ZN_2 7895.00 865.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_1 7816.33 943.67 0.00 0.00 0.00
PERIMETER_TOP_ZN_4 7807.33 952.67 0.00 0.00 0.00
DATACENTER_BOT_ZN_6 7298.00 1462.00 0.00 0.00 0.00
DATACENTER_MID_ZN_6 7275.83 1484.17 0.00 0.00 0.00
DATACENTER_TOP_ZN_6 7257.00 1503.00 0.00 0.00 0.00
DATACENTER_BASEMENT_ZN_6 7255.50 1504.50 0.00 0.00 0.00
GROUNDFLOOR_PLENUM 7652.50 1107.50 0.00 0.00 0.00
MIDFLOOR_PLENUM 7706.17 1053.83 0.00 0.00 0.00
TOPFLOOR_PLENUM 7322.33 1437.67 0.00 0.00 0.00
Min 7093.17 518.00 0.00 0.00 0.00
Max 8242.00 1666.83 0.00 0.00 0.00
Average 7695.92 1064.08 0.00 0.00 0.00
Sum 177006.17 24473.83 0.00 0.00 0.00


Humidex OccupantHours

Little to no Discomfort (≤ 29) [hr] Some Discomfort (> 29, ≤ 40) [hr] Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] Dangerous (> 45, ≤ 50) [hr] Heat Stroke Quite Possible (> 50) [hr]
BASEMENT 354893.67 13722.33 0.00 0.00 0.00
CORE_BOTTOM 329643.00 1170.00 0.00 0.00 0.00
CORE_MID 329626.00 1187.00 0.00 0.00 0.00
CORE_TOP 329581.50 1231.50 0.00 0.00 0.00
PERIMETER_BOT_ZN_3 38924.67 0.33 0.00 0.00 0.00
PERIMETER_BOT_ZN_2 24909.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_1 38924.83 0.17 0.00 0.00 0.00
PERIMETER_BOT_ZN_4 24909.00 0.00 0.00 0.00 0.00
PERIMETER_MID_ZN_3 38907.17 17.83 0.00 0.00 0.00
PERIMETER_MID_ZN_2 18350.83 3.17 0.00 0.00 0.00
PERIMETER_MID_ZN_1 38913.50 11.50 0.00 0.00 0.00
PERIMETER_MID_ZN_4 24907.50 1.50 0.00 0.00 0.00
PERIMETER_TOP_ZN_3 38901.33 23.67 0.00 0.00 0.00
PERIMETER_TOP_ZN_2 24903.83 5.17 0.00 0.00 0.00
PERIMETER_TOP_ZN_1 38911.67 13.33 0.00 0.00 0.00
PERIMETER_TOP_ZN_4 24906.67 2.33 0.00 0.00 0.00
DATACENTER_BOT_ZN_6 1459.83 808.17 0.00 0.00 0.00
DATACENTER_MID_ZN_6 1444.33 823.67 0.00 0.00 0.00
DATACENTER_TOP_ZN_6 1436.50 831.50 0.00 0.00 0.00
DATACENTER_BASEMENT_ZN_6 72545.67 30849.33 0.00 0.00 0.00
GROUNDFLOOR_PLENUM 0.00 0.00 0.00 0.00 0.00
MIDFLOOR_PLENUM 0.00 0.00 0.00 0.00 0.00
TOPFLOOR_PLENUM 0.00 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00 0.00
Max 354893.67 30849.33 0.00 0.00 0.00
Average 78130.46 2204.46 0.00 0.00 0.00
Sum 1797000.50 50702.50 0.00 0.00 0.00


Heating SET Hours

SET ≤ 12.2°C Hours (°C) SET ≤ 12.2°C OccupantHours (°C) Longest SET ≤ 12.2°C Duration [hr] Start Time of the Longest SET ≤ 12.2°C Duration
None        


Cooling SET Hours

SET > 30°C Hours (°C) SET > 30°C OccupantHours (°C) Longest SET > 30°C Duration [hr] Start Time of the Longest SET > 30°C Duration
None        



Table of Contents

Report: Annual CO2 Resilience Summary

For: Entire Facility

Timestamp: 2023-10-16 08:43:34

CO2 Level Hours

Safe (<= 1000 ppm) [hr] Caution (> 1000, <= 5000 ppm) [hr] Hazard (> 5000 ppm) [hr]
None      


CO2 Level OccupantHours

Safe (<= 1000 ppm) [hr] Caution (> 1000, <= 5000 ppm) [hr] Hazard (> 5000 ppm) [hr]
None      



Table of Contents

Report: Annual Visual Resilience Summary

For: Entire Facility

Timestamp: 2023-10-16 08:43:34

Illuminance Level Hours

A Bit Dark (<= 100 lux) [hr] Dim (> 100, <= 300 lux) [hr] Adequate (> 300, <= 500 lux) [hr] Bright (>500 lux) [hr]
BASEMENT 0.00 0.00 0.00 0.00
CORE_BOTTOM 0.00 0.00 0.00 0.00
CORE_MID 0.00 0.00 0.00 0.00
CORE_TOP 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_3 0.00 0.00 8760.00 0.00
PERIMETER_BOT_ZN_2 0.00 0.00 8760.00 0.00
PERIMETER_BOT_ZN_1 0.00 0.00 8760.00 0.00
PERIMETER_BOT_ZN_4 0.00 0.00 8760.00 0.00
PERIMETER_MID_ZN_3 0.00 0.00 8760.00 0.00
PERIMETER_MID_ZN_2 0.00 0.00 8760.00 0.00
PERIMETER_MID_ZN_1 0.00 0.00 8760.00 0.00
PERIMETER_MID_ZN_4 0.00 0.00 8760.00 0.00
PERIMETER_TOP_ZN_3 0.00 0.00 8760.00 0.00
PERIMETER_TOP_ZN_2 0.00 0.00 8760.00 0.00
PERIMETER_TOP_ZN_1 0.00 0.00 8760.00 0.00
PERIMETER_TOP_ZN_4 0.00 0.00 8760.00 0.00
DATACENTER_BOT_ZN_6 0.00 0.00 0.00 0.00
DATACENTER_MID_ZN_6 0.00 0.00 0.00 0.00
DATACENTER_TOP_ZN_6 0.00 0.00 0.00 0.00
DATACENTER_BASEMENT_ZN_6 0.00 0.00 0.00 0.00
GROUNDFLOOR_PLENUM 0.00 0.00 0.00 0.00
MIDFLOOR_PLENUM 0.00 0.00 0.00 0.00
TOPFLOOR_PLENUM 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00
Max 0.00 0.00 8760.00 0.00
Average 0.00 0.00 4570.43 0.00
Sum 0.00 0.00 105120.00 0.00


Illuminance Level OccupantHours

A Bit Dark (<= 100 lux) [hr] Dim (> 100, <= 300 lux) [hr] Adequate (> 300, <= 500 lux) [hr] Bright (>500 lux) [hr]
BASEMENT 0.00 0.00 0.00 0.00
CORE_BOTTOM 0.00 0.00 0.00 0.00
CORE_MID 0.00 0.00 0.00 0.00
CORE_TOP 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_3 0.00 0.00 38925.00 0.00
PERIMETER_BOT_ZN_2 0.00 0.00 24909.00 0.00
PERIMETER_BOT_ZN_1 0.00 0.00 38925.00 0.00
PERIMETER_BOT_ZN_4 0.00 0.00 24909.00 0.00
PERIMETER_MID_ZN_3 0.00 0.00 38925.00 0.00
PERIMETER_MID_ZN_2 0.00 0.00 18354.00 0.00
PERIMETER_MID_ZN_1 0.00 0.00 38925.00 0.00
PERIMETER_MID_ZN_4 0.00 0.00 24909.00 0.00
PERIMETER_TOP_ZN_3 0.00 0.00 38925.00 0.00
PERIMETER_TOP_ZN_2 0.00 0.00 24909.00 0.00
PERIMETER_TOP_ZN_1 0.00 0.00 38925.00 0.00
PERIMETER_TOP_ZN_4 0.00 0.00 24909.00 0.00
DATACENTER_BOT_ZN_6 0.00 0.00 0.00 0.00
DATACENTER_MID_ZN_6 0.00 0.00 0.00 0.00
DATACENTER_TOP_ZN_6 0.00 0.00 0.00 0.00
DATACENTER_BASEMENT_ZN_6 0.00 0.00 0.00 0.00
GROUNDFLOOR_PLENUM 0.00 0.00 0.00 0.00
MIDFLOOR_PLENUM 0.00 0.00 0.00 0.00
TOPFLOOR_PLENUM 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00
Max 0.00 0.00 38925.00 0.00
Average 0.00 0.00 16367.35 0.00
Sum 0.00 0.00 376449.00 0.00



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR

For: Environment

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 1.168
February -0.18
March 5.585
April 10.941
May 16.049
June 21.711
July 25.046
August 24.788
September 19.956
October 14.024
November 7.310
December 3.332
   
Annual Sum or Average 12.554
Minimum of Months -0.18
Maximum of Months 25.046



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901

For: Environment

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 1.168
February -0.18
March 5.585
April 10.941
May 16.049
June 21.711
July 25.046
August 24.788
September 19.956
October 14.024
November 7.310
December 3.332
   
Annual Sum or Average 12.554
Minimum of Months -0.18
Maximum of Months 25.046



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2013

For: Environment

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 1.168
February -0.18
March 5.585
April 10.941
May 16.049
June 21.711
July 25.046
August 24.788
September 19.956
October 14.024
November 7.310
December 3.332
   
Annual Sum or Average 12.554
Minimum of Months -0.18
Maximum of Months 25.046



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND

For: Environment

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 1.168
February -0.18
March 5.585
April 10.941
May 16.049
June 21.711
July 25.046
August 24.788
September 19.956
October 14.024
November 7.310
December 3.332
   
Annual Sum or Average 12.554
Minimum of Months -0.18
Maximum of Months 25.046



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICELARGE

For: Environment

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 1.168
February -0.18
March 5.585
April 10.941
May 16.049
June 21.711
July 25.046
August 24.788
September 19.956
October 14.024
November 7.310
December 3.332
   
Annual Sum or Average 12.554
Minimum of Months -0.18
Maximum of Months 25.046



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL

For: Environment

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 1.168
February -0.18
March 5.585
April 10.941
May 16.049
June 21.711
July 25.046
August 24.788
September 19.956
October 14.024
November 7.310
December 3.332
   
Annual Sum or Average 12.554
Minimum of Months -0.18
Maximum of Months 25.046



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL

For: Environment

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 1.168
February -0.18
March 5.585
April 10.941
May 16.049
June 21.711
July 25.046
August 24.788
September 19.956
October 14.024
November 7.310
December 3.332
   
Annual Sum or Average 12.554
Minimum of Months -0.18
Maximum of Months 25.046



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 4A

For: Environment

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 1.168
February -0.18
March 5.585
April 10.941
May 16.049
June 21.711
July 25.046
August 24.788
September 19.956
October 14.024
November 7.310
December 3.332
   
Annual Sum or Average 12.554
Minimum of Months -0.18
Maximum of Months 25.046



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_NY_NEWYORK

For: Environment

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 1.168
February -0.18
March 5.585
April 10.941
May 16.049
June 21.711
July 25.046
August 24.788
September 19.956
October 14.024
November 7.310
December 3.332
   
Annual Sum or Average 12.554
Minimum of Months -0.18
Maximum of Months 25.046



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: BASEMENT

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.469702E+11 115457.96 23-JAN-05:11 5.60 5.60 0.563628E+10 7499.24 31-JAN-14:30 -2.0 -6.3
February 0.453699E+11 120325.68 21-FEB-05:11 2.20 1.34 0.512539E+10 7499.22 22-FEB-10:50 1.93 -2.3
March 0.585304E+11 118973.77 06-MAR-05:11 8.70 8.70 0.613057E+10 7499.20 23-MAR-13:50 5.10 0.90
April 0.564152E+11 118499.74 17-APR-04:12 12.43 10.77 0.544782E+10 7499.24 05-APR-09:30 12.43 10.77
May 0.597193E+11 118736.47 01-MAY-04:12 6.50 4.55 0.590054E+10 7499.54 25-MAY-09:20 16.87 13.21
June 0.635157E+11 122957.68 05-JUN-04:11 14.40 11.39 0.588258E+10 7499.30 23-JUN-09:00 30.00 18.39
July 0.641050E+11 102133.86 11-JUL-04:12 19.80 15.19 0.547462E+10 7499.17 12-JUL-09:50 27.70 18.43
August 0.722504E+11 113881.28 08-AUG-04:12 15.40 12.62 0.613899E+10 7499.20 25-AUG-13:50 26.42 15.19
September 0.645197E+11 116677.48 11-SEP-04:12 12.60 9.24 0.545323E+10 7499.25 19-SEP-09:20 18.87 14.31
October 0.671931E+11 120071.76 23-OCT-04:12 12.97 10.92 0.567218E+10 7499.50 16-OCT-09:20 12.97 10.92
November 0.610493E+11 120869.60 13-NOV-05:11 5.60 4.52 0.561391E+10 7499.13 09-NOV-14:00 5.60 4.52
December 0.571583E+11 120497.18 04-DEC-05:11 5.60 5.31 0.546816E+10 7499.15 29-DEC-10:09 2.88 0.57
                     
Annual Sum or Average 0.716797E+12         0.679443E+11        
Minimum of Months 0.453699E+11 102133.86   2.20 1.34 0.512539E+10 7499.13   -2.0 -6.3
Maximum of Months 0.722504E+11 122957.68   19.80 15.19 0.613899E+10 7499.54   30.00 18.43



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: CORE_BOTTOM

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.354237E+11 86971.60 21-JAN-06:02 -0.5 -0.5 0.502211E+10 6897.23 31-JAN-10:20 -6.3 -9.2
February 0.359825E+11 92221.29 21-FEB-05:11 2.20 1.34 0.458474E+10 6924.10 03-FEB-10:09 2.20 1.34
March 0.513003E+11 94989.40 06-MAR-05:11 8.70 8.70 0.549847E+10 6789.81 20-MAR-09:20 3.17 0.82
April 0.552809E+11 97257.76 10-APR-04:12 13.13 12.29 0.488109E+10 6734.87 26-APR-09:00 16.10 12.59
May 0.557985E+11 102334.13 30-MAY-04:13 17.80 14.10 0.528540E+10 6812.52 30-MAY-13:30 29.70 17.47
June 0.640848E+11 102372.51 12-JUN-04:13 18.70 17.72 0.526968E+10 6794.39 01-JUN-13:00 18.70 17.72
July 0.708970E+11 92555.96 01-JUL-04:12 20.00 19.55 0.489288E+10 6768.44 11-JUL-13:09 27.98 17.98
August 0.795905E+11 94411.35 08-AUG-04:12 15.40 12.62 0.549351E+10 6735.62 25-AUG-13:50 26.42 15.19
September 0.563461E+11 100351.35 18-SEP-04:12 17.07 16.12 0.488247E+10 6734.98 19-SEP-09:09 18.58 14.06
October 0.566296E+11 100419.95 23-OCT-04:12 12.97 10.92 0.507793E+10 6735.15 16-OCT-09:09 12.97 10.92
November 0.482537E+11 102646.78 13-NOV-05:11 5.60 4.52 0.503190E+10 6788.32 22-NOV-10:20 0.20 -2.5
December 0.465660E+11 95348.26 26-DEC-05:11 5.77 4.97 0.489775E+10 6831.65 22-DEC-10:30 5.77 4.97
                     
Annual Sum or Average 0.656154E+12         0.608179E+11        
Minimum of Months 0.354237E+11 86971.60   -0.5 -0.5 0.458474E+10 6734.87   -6.3 -9.2
Maximum of Months 0.795905E+11 102646.78   20.00 19.55 0.549847E+10 6924.10   29.70 17.98



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: CORE_MID

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.243492E+11 69970.00 31-JAN-18:12 -2.4 -6.3 0.450056E+10 6794.37 13-JAN-14:30 -2.4 -6.3
February 0.248318E+11 70235.30 03-FEB-16:57 -2.8 -5.4 0.421084E+10 6790.88 23-FEB-14:00 5.00 3.30
March 0.329286E+11 78814.94 17-MAR-12:55 -1.1 -2.0 0.535695E+10 7046.28 17-MAR-12:00 -1.1 -2.0
April 0.356705E+11 85004.74 10-APR-05:02 15.10 13.73 0.481190E+10 6746.48 14-APR-09:00 8.30 5.71
May 0.455192E+11 87932.60 31-MAY-04:12 16.10 14.49 0.526623E+10 6744.06 30-MAY-13:30 16.10 14.49
June 0.514077E+11 89525.06 12-JUN-04:12 18.70 17.72 0.526578E+10 6767.04 22-JUN-13:30 29.15 17.46
July 0.526971E+11 87855.61 11-JUL-04:12 19.80 15.19 0.489141E+10 6770.57 11-JUL-13:39 28.53 17.90
August 0.564429E+11 93640.06 07-AUG-04:12 18.67 17.05 0.549605E+10 6734.78 08-AUG-13:30 26.40 17.05
September 0.466328E+11 89072.01 18-SEP-04:12 17.07 16.12 0.487162E+10 6734.96 19-SEP-09:09 18.58 14.06
October 0.420243E+11 86193.25 06-OCT-04:12 19.40 18.28 0.504922E+10 6752.27 31-OCT-09:09 8.48 4.89
November 0.301123E+11 80312.48 03-NOV-05:02 9.22 6.42 0.487751E+10 6784.72 16-NOV-10:00 6.10 3.00
December 0.275233E+11 56198.90 22-DEC-13:47 1.02 -2.8 0.462463E+10 6760.53 21-DEC-10:30 1.02 -2.8
                     
Annual Sum or Average 0.470139E+12         0.592227E+11        
Minimum of Months 0.243492E+11 56198.90   -2.8 -6.3 0.421084E+10 6734.78   -2.4 -6.3
Maximum of Months 0.564429E+11 93640.06   19.80 18.28 0.549605E+10 7046.28   29.15 17.90



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: CORE_TOP

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.193201E+11 21768.40 20-JAN-17:00 5.60 3.19 0.415310E+10 6589.90 20-JAN-14:00 5.60 3.19
February 0.186824E+11 22156.72 17-FEB-17:00 5.60 1.58 0.381363E+10 6626.91 02-FEB-14:00 5.60 1.58
March 0.271582E+11 36117.19 03-MAR-17:00 14.00 7.84 0.497713E+10 6734.67 29-MAR-13:50 7.80 5.47
April 0.314462E+11 78803.82 27-APR-05:02 11.70 10.21 0.464050E+10 6734.74 26-APR-09:00 11.70 10.21
May 0.434314E+11 89098.37 30-MAY-04:12 17.80 14.10 0.521372E+10 6812.82 30-MAY-13:30 29.70 17.47
June 0.533799E+11 89700.02 12-JUN-04:12 18.70 17.72 0.526161E+10 6819.83 22-JUN-13:09 28.58 17.26
July 0.568907E+11 89325.98 11-JUL-04:12 19.80 15.19 0.489524E+10 6809.43 11-JUL-13:39 28.53 17.90
August 0.599635E+11 96592.68 07-AUG-04:12 18.67 17.05 0.549604E+10 6747.23 09-AUG-13:30 26.15 17.99
September 0.451723E+11 88690.51 06-SEP-04:12 21.30 18.82 0.484704E+10 6737.01 01-SEP-13:39 21.30 18.82
October 0.363250E+11 83459.63 06-OCT-05:03 19.40 18.22 0.492611E+10 6735.01 16-OCT-09:09 16.88 14.11
November 0.234755E+11 36101.10 03-NOV-16:00 15.00 10.26 0.448535E+10 6734.79 09-NOV-14:00 13.90 12.65
December 0.205634E+11 20288.84 20-DEC-17:00 6.70 3.52 0.411480E+10 6592.15 20-DEC-14:00 6.70 3.52
                     
Annual Sum or Average 0.435808E+12         0.568243E+11        
Minimum of Months 0.186824E+11 20288.84   5.60 1.58 0.381363E+10 6589.90   5.60 1.58
Maximum of Months 0.599635E+11 96592.68   21.30 18.82 0.549604E+10 6819.83   29.70 18.82



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.200364E+10 2916.26 31-JAN-13:20 -3.3 -7.2 0.521553E+09 807.90 20-JAN-14:50 -3.3 -7.2
February 0.200890E+10 3124.32 20-FEB-14:02 8.80 4.54 0.479794E+09 822.98 24-FEB-14:20 9.03 2.95
March 0.382215E+10 6676.56 27-MAR-13:30 20.85 16.76 0.646918E+09 845.63 06-MAR-14:09 20.85 16.76
April 0.548236E+10 8174.60 26-APR-13:40 18.30 12.75 0.599037E+09 845.64 26-APR-09:00 18.30 12.75
May 0.746578E+10 14546.99 30-MAY-04:12 17.80 14.10 0.661166E+09 866.81 30-MAY-13:30 29.70 17.47
June 0.107247E+11 15761.96 18-JUN-17:01 24.72 21.89 0.662265E+09 864.17 01-JUN-13:00 24.72 21.89
July 0.126690E+11 19026.12 09-JUL-15:01 27.20 24.06 0.616067E+09 858.14 11-JUL-13:09 27.98 17.98
August 0.133361E+11 18328.45 13-AUG-15:11 30.40 20.77 0.690564E+09 845.81 25-AUG-13:50 26.42 15.19
September 0.760392E+10 14071.81 02-SEP-04:11 22.60 16.46 0.611356E+09 845.65 19-SEP-09:09 18.58 14.06
October 0.585916E+10 7765.67 04-OCT-13:10 24.90 18.61 0.629030E+09 845.67 16-OCT-09:09 16.88 14.11
November 0.346542E+10 5310.01 03-NOV-13:30 17.50 10.63 0.595071E+09 845.64 09-NOV-14:00 13.90 12.65
December 0.288150E+10 3046.73 17-DEC-12:51 12.20 4.95 0.544105E+09 845.61 20-DEC-14:09 9.72 5.77
                     
Annual Sum or Average 0.773226E+11         0.725692E+10        
Minimum of Months 0.200364E+10 2916.26   -3.3 -7.2 0.479794E+09 807.90   -3.3 -7.2
Maximum of Months 0.133361E+11 19026.12   30.40 24.06 0.690564E+09 866.81   29.70 21.89



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.206141E+10 5015.29 19-JAN-09:30 6.10 3.63 0.336501E+09 544.96 30-JAN-10:20 -1.1 -3.4
February 0.222473E+10 7063.99 22-FEB-09:15 0.20 -3.3 0.314830E+09 545.16 03-FEB-10:09 0.20 -3.3
March 0.435355E+10 10496.21 29-MAR-08:35 5.20 2.69 0.410996E+09 545.84 13-MAR-09:30 5.20 2.69
April 0.576919E+10 23826.63 16-APR-09:22 16.40 11.79 0.378884E+09 544.98 26-APR-09:50 16.38 12.56
May 0.775231E+10 24889.16 21-MAY-08:62 17.38 10.46 0.423149E+09 553.89 30-MAY-13:50 29.50 17.11
June 0.917539E+10 23652.77 25-JUN-08:42 25.40 23.51 0.425860E+09 557.56 22-JUN-09:30 25.40 23.51
July 0.107123E+11 26506.09 09-JUL-08:21 27.75 25.12 0.396372E+09 549.91 12-JUL-09:39 27.60 18.47
August 0.120799E+11 23925.38 20-AUG-10:12 24.63 15.66 0.444253E+09 546.67 02-AUG-09:50 24.63 15.66
September 0.742018E+10 27251.42 04-SEP-08:41 23.72 18.57 0.392511E+09 545.95 06-SEP-09:30 26.15 19.35
October 0.609689E+10 15635.08 22-OCT-10:02 19.60 16.35 0.403501E+09 545.00 16-OCT-09:09 19.60 16.35
November 0.341770E+10 7339.98 02-NOV-08:50 10.82 5.71 0.374518E+09 544.95 08-NOV-14:50 13.68 11.16
December 0.266320E+10 5451.50 20-DEC-09:30 7.20 4.58 0.338632E+09 544.95 15-DEC-10:09 7.20 4.58
                     
Annual Sum or Average 0.737268E+11         0.464001E+10        
Minimum of Months 0.206141E+10 5015.29   0.20 -3.3 0.314830E+09 544.95   -1.1 -3.4
Maximum of Months 0.120799E+11 27251.42   27.75 25.12 0.444253E+09 557.56   29.50 23.51



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.469314E+10 22452.08 31-JAN-13:30 -3.0 -7.0 0.559507E+09 887.66 31-JAN-10:00 -3.0 -7.0
February 0.537790E+10 26807.62 19-FEB-12:32 8.13 4.20 0.524936E+09 896.82 09-FEB-10:50 8.13 4.20
March 0.863086E+10 20727.07 01-MAR-13:05 13.90 6.68 0.650938E+09 847.75 28-MAR-13:09 13.80 8.65
April 0.865727E+10 26736.12 16-APR-12:02 20.68 13.16 0.592386E+09 847.88 07-APR-13:00 20.68 13.16
May 0.942798E+10 26768.21 29-MAY-12:02 28.62 18.20 0.657118E+09 887.62 30-MAY-13:30 29.70 17.47
June 0.122094E+11 26774.79 18-JUN-14:21 26.10 22.41 0.661867E+09 866.48 01-JUN-13:00 26.10 22.41
July 0.150074E+11 28633.46 30-JUL-14:21 26.40 23.20 0.616026E+09 869.82 11-JUL-13:09 26.40 23.20
August 0.188364E+11 29120.78 20-AUG-13:31 28.53 15.31 0.691331E+09 866.78 30-AUG-13:09 27.48 15.59
September 0.133878E+11 30707.67 04-SEP-14:01 25.92 18.50 0.612660E+09 900.91 28-SEP-13:09 22.98 13.55
October 0.140597E+11 30462.60 22-OCT-12:41 22.02 16.80 0.633862E+09 892.38 04-OCT-13:09 22.02 16.80
November 0.752495E+10 21842.62 02-NOV-12:40 15.40 8.14 0.605355E+09 870.77 02-NOV-13:09 15.68 8.29
December 0.622937E+10 29868.57 17-DEC-12:51 12.20 4.95 0.563944E+09 846.42 21-DEC-14:20 3.30 -1.7
                     
Annual Sum or Average 0.124042E+12         0.736993E+10        
Minimum of Months 0.469314E+10 20727.07   -3.0 -7.0 0.524936E+09 846.42   -3.0 -7.0
Maximum of Months 0.188364E+11 30707.67   28.62 23.20 0.691331E+09 900.91   29.70 23.20



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.319706E+10 7402.59 20-JAN-15:30 7.50 3.89 0.345367E+09 544.96 31-JAN-14:30 -2.0 -6.3
February 0.377540E+10 10474.83 24-FEB-15:30 8.05 2.04 0.328457E+09 545.51 14-FEB-14:00 8.05 2.04
March 0.723619E+10 18716.27 26-MAR-16:22 11.15 9.79 0.433251E+09 544.96 01-MAR-14:00 11.15 9.79
April 0.947588E+10 30167.89 09-APR-16:21 16.65 13.97 0.393695E+09 544.97 26-APR-09:50 16.38 12.56
May 0.936352E+10 30583.14 21-MAY-15:21 20.00 13.23 0.426068E+09 557.98 30-MAY-13:50 29.50 17.11
June 0.131048E+11 34144.98 18-JUN-15:41 25.68 22.17 0.427650E+09 556.05 01-JUN-15:09 25.68 22.17
July 0.156664E+11 33886.28 04-JUL-16:21 25.55 18.12 0.397921E+09 559.23 11-JUL-15:20 28.30 17.46
August 0.188146E+11 30332.61 13-AUG-15:51 30.00 20.46 0.446181E+09 546.89 22-AUG-15:30 29.70 17.33
September 0.937485E+10 33073.52 10-SEP-15:31 23.67 13.25 0.394372E+09 544.98 11-SEP-13:09 20.60 12.01
October 0.880115E+10 23533.52 15-OCT-15:12 20.20 12.62 0.408546E+09 544.99 16-OCT-09:09 16.88 14.11
November 0.536013E+10 11173.36 02-NOV-14:30 16.40 8.87 0.395969E+09 544.97 09-NOV-14:00 13.90 12.65
December 0.498195E+10 16338.00 17-DEC-14:12 12.20 5.36 0.380941E+09 544.95 18-DEC-14:00 6.10 2.61
                     
Annual Sum or Average 0.109152E+12         0.477842E+10        
Minimum of Months 0.319706E+10 7402.59   7.50 2.04 0.328457E+09 544.95   -2.0 -6.3
Maximum of Months 0.188146E+11 34144.98   30.00 22.17 0.446181E+09 559.23   29.70 22.17



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.425767E+09 3054.42 20-JAN-16:50 5.87 3.30 0.467237E+09 682.17 20-JAN-14:00 5.87 3.30
February 0.488025E+09 3000.58 01-FEB-14:50 7.88 3.68 0.425910E+09 695.55 24-FEB-14:00 8.30 2.27
March 0.190305E+10 3962.33 14-MAR-10:13 2.60 -2.2 0.553022E+09 845.60 28-MAR-13:30 13.60 8.55
April 0.315113E+10 6381.65 07-APR-14:30 25.85 15.95 0.548542E+09 845.63 10-APR-13:09 20.10 10.10
May 0.590483E+10 13259.58 31-MAY-05:03 16.38 14.99 0.649682E+09 853.46 30-MAY-13:50 16.38 14.99
June 0.897739E+10 13941.27 22-JUN-05:03 22.88 15.44 0.661252E+09 862.76 22-JUN-13:30 29.15 17.46
July 0.103632E+11 18243.26 09-JUL-15:01 27.20 24.06 0.616112E+09 857.60 11-JUL-13:39 28.53 17.90
August 0.102656E+11 18331.24 13-AUG-15:01 30.50 20.85 0.690597E+09 845.65 08-AUG-13:30 30.50 20.85
September 0.624323E+10 13446.21 02-SEP-05:03 22.12 16.30 0.604828E+09 845.65 19-SEP-09:09 18.58 14.06
October 0.404065E+10 6524.44 05-OCT-14:00 23.30 18.86 0.599077E+09 845.61 16-OCT-13:30 19.15 16.04
November 0.167461E+10 3064.79 02-NOV-14:20 16.30 8.82 0.507777E+09 845.59 03-NOV-13:00 17.80 10.67
December 0.624946E+09 2258.67 20-DEC-13:10 9.50 5.64 0.452640E+09 695.95 20-DEC-14:09 9.72 5.77
                     
Annual Sum or Average 0.540624E+11         0.677668E+10        
Minimum of Months 0.425767E+09 2258.67   2.60 -2.2 0.425910E+09 682.17   5.87 2.27
Maximum of Months 0.103632E+11 18331.24   30.50 24.06 0.690597E+09 862.76   30.50 20.85



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.687904E+09 4421.12 19-JAN-09:35 6.67 3.82 0.223375E+09 493.53 27-JAN-09:00 4.40 1.46
February 0.103913E+10 5109.34 22-FEB-10:25 1.40 -2.7 0.206139E+09 520.82 22-FEB-09:30 1.40 -2.7
March 0.288908E+10 12606.41 29-MAR-08:35 5.20 2.69 0.275156E+09 563.73 22-MAR-10:20 5.20 2.69
April 0.449464E+10 19087.67 23-APR-09:32 13.17 8.83 0.264469E+09 568.83 12-APR-07:40 13.17 8.83
May 0.740400E+10 29732.80 29-MAY-08:31 25.37 16.74 0.303544E+09 553.00 30-MAY-10:39 28.53 17.44
June 0.877186E+10 28777.49 25-JUN-08:31 25.20 23.38 0.311767E+09 543.05 22-JUN-15:50 25.20 23.38
July 0.999832E+10 30479.45 02-JUL-08:51 25.60 21.66 0.292487E+09 526.57 11-JUL-14:30 28.60 17.71
August 0.111886E+11 27071.23 20-AUG-09:41 23.53 15.29 0.326854E+09 528.96 25-AUG-14:09 26.70 15.29
September 0.708078E+10 29202.11 04-SEP-08:51 23.90 18.54 0.284499E+09 521.61 06-SEP-08:00 25.60 19.05
October 0.526169E+10 14597.97 15-OCT-10:22 18.85 13.18 0.286307E+09 521.23 16-OCT-08:00 16.70 14.03
November 0.213175E+10 5354.32 02-NOV-09:00 11.10 5.86 0.242919E+09 522.32 01-NOV-08:39 11.10 5.86
December 0.105247E+10 3219.89 20-DEC-09:35 7.57 4.72 0.218394E+09 515.11 20-DEC-09:39 7.57 4.72
                     
Annual Sum or Average 0.620002E+11         0.323591E+10        
Minimum of Months 0.687904E+09 3219.89   1.40 -2.7 0.206139E+09 493.53   1.40 -2.7
Maximum of Months 0.111886E+11 30479.45   25.60 23.38 0.326854E+09 568.83   28.60 23.38



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.347893E+10 22142.64 31-JAN-13:37 -2.8 -6.8 0.532076E+09 868.91 30-JAN-10:00 -2.8 -6.8
February 0.440250E+10 26741.27 20-FEB-13:43 8.98 4.49 0.499713E+09 910.14 22-FEB-10:09 0.87 -3.0
March 0.721338E+10 21344.53 01-MAR-13:30 13.90 6.36 0.618062E+09 881.11 07-MAR-10:30 7.80 3.53
April 0.685726E+10 22806.45 09-APR-13:23 19.40 15.51 0.566556E+09 868.55 07-APR-13:50 19.40 15.51
May 0.852542E+10 28678.09 29-MAY-12:32 27.77 17.46 0.646112E+09 884.39 30-MAY-13:50 29.50 17.11
June 0.107894E+11 26951.82 25-JUN-12:32 26.50 23.06 0.660147E+09 869.41 22-JUN-13:30 26.50 23.06
July 0.127692E+11 28695.27 09-JUL-13:41 31.70 24.87 0.616267E+09 875.32 11-JUL-13:39 28.53 17.90
August 0.162821E+11 29642.71 20-AUG-13:01 27.98 15.69 0.692249E+09 904.98 30-AUG-13:00 28.90 15.47
September 0.130962E+11 32458.84 04-SEP-12:11 26.10 17.96 0.610496E+09 945.88 28-SEP-13:20 23.17 13.55
October 0.135595E+11 30923.59 22-OCT-12:11 21.47 16.46 0.627960E+09 930.14 04-OCT-13:20 21.47 16.46
November 0.612965E+10 22420.09 02-NOV-13:10 15.68 8.29 0.578832E+09 898.10 02-NOV-13:20 15.77 8.37
December 0.442395E+10 27326.17 17-DEC-13:02 12.20 5.01 0.531759E+09 860.68 15-DEC-14:39 12.20 5.01
                     
Annual Sum or Average 0.107527E+12         0.718023E+10        
Minimum of Months 0.347893E+10 21344.53   -2.8 -6.8 0.499713E+09 860.68   -2.8 -6.8
Maximum of Months 0.162821E+11 32458.84   31.70 24.87 0.692249E+09 945.88   29.50 23.06



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.918481E+09 4414.00 31-JAN-16:00 -1.1 -5.7 0.310131E+09 536.53 19-JAN-14:00 -1.1 -5.7
February 0.122811E+10 7424.12 22-FEB-16:00 4.40 -0.8 0.286002E+09 544.93 17-FEB-14:00 4.40 -0.8
March 0.359134E+10 11835.40 29-MAR-16:00 7.20 4.88 0.366415E+09 544.95 01-MAR-14:00 7.20 4.88
April 0.501728E+10 28381.53 09-APR-16:01 17.02 14.08 0.350391E+09 544.96 10-APR-13:09 20.10 10.10
May 0.742263E+10 27596.76 28-MAY-14:51 26.70 15.43 0.409664E+09 546.61 30-MAY-13:30 29.70 17.47
June 0.988673E+10 31717.99 18-JUN-16:21 25.30 22.03 0.424992E+09 582.31 22-JUN-15:50 29.60 17.59
July 0.107410E+11 31518.25 02-JUL-16:11 24.80 20.74 0.397019E+09 554.00 11-JUL-13:39 28.53 17.90
August 0.120909E+11 30766.99 13-AUG-15:41 30.10 20.54 0.445343E+09 545.00 25-AUG-13:50 26.42 15.19
September 0.743515E+10 29048.97 03-SEP-16:11 24.80 16.47 0.385076E+09 544.97 11-SEP-13:09 20.60 12.01
October 0.594074E+10 23816.39 15-OCT-15:41 19.60 12.30 0.380513E+09 544.95 19-OCT-13:00 15.60 10.54
November 0.223420E+10 7651.24 03-NOV-15:30 16.10 10.65 0.327289E+09 544.96 08-NOV-14:50 13.68 11.16
December 0.121839E+10 4619.76 18-DEC-16:25 4.45 1.67 0.301055E+09 539.79 21-DEC-14:00 3.30 -1.8
                     
Annual Sum or Average 0.677249E+11         0.438389E+10        
Minimum of Months 0.918481E+09 4414.00   -1.1 -5.7 0.286002E+09 536.53   -1.1 -5.7
Maximum of Months 0.120909E+11 31717.99   30.10 22.03 0.445343E+09 582.31   29.70 17.90



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.214490E+09 1767.58 20-JAN-15:30 7.50 3.89 0.464060E+09 653.61 20-JAN-14:00 7.50 3.89
February 0.219384E+09 1796.74 24-FEB-15:40 7.97 1.96 0.421653E+09 657.77 17-FEB-14:00 7.97 1.96
March 0.127304E+10 3007.20 28-MAR-14:00 13.30 8.41 0.534777E+09 845.60 28-MAR-13:50 13.30 8.41
April 0.271830E+10 7032.72 07-APR-14:00 26.10 15.95 0.527677E+09 845.63 07-APR-13:09 26.10 15.95
May 0.567878E+10 15032.18 30-MAY-05:03 18.17 14.31 0.636057E+09 861.07 30-MAY-13:30 29.70 17.47
June 0.921048E+10 20119.21 25-JUN-16:31 25.77 22.57 0.660162E+09 851.24 22-JUN-13:09 25.77 22.57
July 0.109427E+11 19966.86 16-JUL-17:42 29.40 22.00 0.616203E+09 855.37 11-JUL-13:39 29.40 22.00
August 0.107796E+11 21291.44 13-AUG-15:01 30.50 20.85 0.690004E+09 847.73 09-AUG-13:30 30.50 20.85
September 0.609570E+10 14444.35 02-SEP-04:11 22.60 16.46 0.597633E+09 846.19 01-SEP-13:39 22.60 16.46
October 0.352158E+10 6886.71 04-OCT-13:40 24.60 18.82 0.575633E+09 845.61 13-OCT-13:50 21.70 17.50
November 0.110115E+10 2956.24 02-NOV-13:40 15.93 8.54 0.485025E+09 827.04 03-NOV-13:00 17.80 10.67
December 0.162807E+09 1753.66 20-DEC-13:40 9.80 5.81 0.448021E+09 649.32 20-DEC-14:09 9.72 5.77
                     
Annual Sum or Average 0.519181E+11         0.665691E+10        
Minimum of Months 0.162807E+09 1753.66   7.50 1.96 0.421653E+09 649.32   7.50 1.96
Maximum of Months 0.109427E+11 21291.44   30.50 22.57 0.690004E+09 861.07   30.50 22.57



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.458069E+09 2578.11 19-JAN-10:10 7.80 4.25 0.301955E+09 487.67 19-JAN-10:30 7.80 4.48
February 0.653188E+09 2705.88 22-FEB-10:10 0.87 -3.0 0.276617E+09 506.29 22-FEB-10:20 1.13 -2.8
March 0.225703E+10 7846.48 29-MAR-09:30 6.15 3.19 0.369940E+09 544.96 22-MAR-09:30 6.15 3.19
April 0.401724E+10 12496.28 28-APR-08:50 15.82 8.80 0.356543E+09 544.98 26-APR-09:50 15.82 8.80
May 0.721559E+10 27920.97 28-MAY-09:01 20.87 12.95 0.409306E+09 549.35 30-MAY-13:39 29.60 17.29
June 0.904306E+10 29309.58 25-JUN-08:31 25.20 23.38 0.424045E+09 546.06 26-JUN-09:00 26.10 20.11
July 0.105152E+11 27955.45 02-JUL-08:21 25.00 21.47 0.396752E+09 554.03 12-JUL-09:50 27.70 18.43
August 0.116902E+11 26543.13 13-AUG-09:01 27.98 19.16 0.444807E+09 546.51 09-AUG-13:30 27.98 19.16
September 0.700383E+10 28523.96 10-SEP-08:41 19.82 13.57 0.385156E+09 546.00 06-SEP-09:50 19.82 13.57
October 0.473229E+10 10499.54 05-OCT-09:10 19.08 16.88 0.385570E+09 544.99 16-OCT-09:09 16.88 14.11
November 0.157055E+10 3975.14 03-NOV-09:30 13.05 8.24 0.320278E+09 544.94 03-NOV-09:00 13.30 8.39
December 0.589402E+09 2571.03 20-DEC-09:35 7.57 4.72 0.291058E+09 490.39 20-DEC-10:09 8.40 5.03
                     
Annual Sum or Average 0.597456E+11         0.436202E+10        
Minimum of Months 0.458069E+09 2571.03   0.87 -3.0 0.276617E+09 487.67   1.13 -2.8
Maximum of Months 0.116902E+11 29309.58   27.98 23.38 0.444807E+09 554.03   29.60 20.11



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.277006E+10 16346.22 19-JAN-13:30 9.40 3.94 0.521948E+09 845.65 31-JAN-14:30 -2.0 -6.3
February 0.346236E+10 17017.25 22-FEB-13:30 4.45 -1.1 0.485232E+09 845.65 22-FEB-10:50 4.45 -1.1
March 0.607263E+10 21616.86 01-MAR-13:30 13.90 6.36 0.599605E+09 846.52 03-MAR-14:50 15.00 8.43
April 0.623948E+10 20168.71 07-APR-12:30 26.15 15.90 0.549451E+09 857.84 07-APR-13:30 26.40 16.17
May 0.835095E+10 29193.99 28-MAY-13:02 25.10 14.62 0.630939E+09 886.16 30-MAY-13:00 29.40 16.93
June 0.110991E+11 29240.85 25-JUN-13:12 26.70 23.10 0.657738E+09 863.15 22-JUN-13:09 26.70 23.10
July 0.134301E+11 29112.64 30-JUL-13:12 27.20 24.02 0.615958E+09 876.59 11-JUL-13:39 27.20 24.02
August 0.169104E+11 32715.92 13-AUG-15:01 30.50 20.85 0.690674E+09 874.33 30-AUG-13:00 28.90 15.47
September 0.129590E+11 32971.64 10-SEP-14:41 24.40 14.04 0.603499E+09 923.04 01-SEP-13:00 24.40 14.04
October 0.124710E+11 32583.50 15-OCT-12:51 20.60 12.82 0.613431E+09 903.56 04-OCT-13:20 20.60 12.82
November 0.493761E+10 23028.14 02-NOV-13:10 15.68 8.29 0.556028E+09 853.23 02-NOV-13:20 15.77 8.37
December 0.320941E+10 29913.33 17-DEC-12:51 12.20 4.95 0.513321E+09 845.64 14-DEC-14:09 12.20 4.95
                     
Annual Sum or Average 0.101912E+12         0.703782E+10        
Minimum of Months 0.277006E+10 16346.22   4.45 -1.1 0.485232E+09 845.64   -2.0 -6.3
Maximum of Months 0.169104E+11 32971.64   30.50 24.02 0.690674E+09 923.04   29.40 24.02



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.675384E+09 3805.89 19-JAN-15:40 8.50 3.16 0.307135E+09 529.19 19-JAN-14:00 8.50 3.16
February 0.895453E+09 5823.67 22-FEB-16:10 4.22 -0.7 0.282933E+09 544.84 17-FEB-14:00 4.22 -0.7
March 0.297399E+10 11619.50 29-MAR-16:00 7.20 4.88 0.358429E+09 544.95 01-MAR-14:00 7.20 4.88
April 0.461878E+10 28759.00 09-APR-16:11 16.83 14.03 0.339756E+09 544.96 10-APR-13:09 20.10 10.10
May 0.733852E+10 29241.87 28-MAY-15:01 26.23 15.49 0.399768E+09 550.91 30-MAY-13:00 29.40 16.93
June 0.100883E+11 31661.76 25-JUN-16:31 25.77 22.57 0.422867E+09 545.73 22-JUN-13:09 25.77 22.57
July 0.111744E+11 33303.94 02-JUL-16:21 24.70 20.69 0.396650E+09 553.92 11-JUL-13:39 28.53 17.90
August 0.124962E+11 33171.55 13-AUG-15:41 30.10 20.54 0.444393E+09 551.42 22-AUG-15:20 29.80 17.39
September 0.740269E+10 32126.79 10-SEP-16:41 22.88 12.73 0.379072E+09 545.86 01-SEP-13:39 22.88 12.73
October 0.550253E+10 24777.89 15-OCT-14:52 20.60 12.83 0.368197E+09 544.96 13-OCT-13:50 20.60 12.83
November 0.172103E+10 7330.69 03-NOV-15:30 16.10 10.65 0.316760E+09 544.96 08-NOV-14:50 13.68 11.16
December 0.747325E+09 3322.13 17-DEC-14:12 12.20 5.36 0.295888E+09 518.91 08-DEC-15:50 12.20 5.36
                     
Annual Sum or Average 0.656346E+11         0.431185E+10        
Minimum of Months 0.675384E+09 3322.13   4.22 -0.7 0.282933E+09 518.91   4.22 -0.7
Maximum of Months 0.124962E+11 33303.94   30.10 22.57 0.444393E+09 553.92   29.80 22.57



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: GROUNDFLOOR_PLENUM

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.713887E+09 6002.89 31-JAN-06:01 -8.4 -10.7 0.00 0.00 01-JAN-00:10 -8.4 -10.7
February 0.881171E+09 7677.68 06-FEB-05:01 -13.2 -14.5 0.00 0.00 01-FEB-00:10 -13.2 -14.5
March 0.278934E+10 4921.16 29-MAR-05:08 2.12 0.18 0.00 0.00 01-MAR-00:10 2.12 0.18
April 0.488819E+10 7790.25 10-APR-14:20 20.40 10.84 0.00 0.00 01-APR-00:10 20.40 10.84
May 0.642507E+10 11632.15 30-MAY-05:15 18.53 14.51 0.00 0.00 01-MAY-00:10 18.53 14.51
June 0.942963E+10 10353.64 26-JUN-05:15 20.97 17.23 0.00 0.00 01-JUN-00:10 20.97 17.23
July 0.107562E+11 12769.28 10-JUL-05:15 26.10 20.74 0.00 0.00 01-JUL-00:10 26.10 20.74
August 0.121971E+11 10873.18 14-AUG-14:40 28.87 23.11 0.00 0.00 01-AUG-00:10 28.87 23.11
September 0.781819E+10 14473.71 05-SEP-05:02 20.60 18.00 0.00 0.00 01-SEP-00:10 20.60 18.00
October 0.645040E+10 8020.32 16-OCT-05:15 8.90 8.42 0.00 0.00 01-OCT-00:10 8.90 8.42
November 0.306018E+10 6663.34 13-NOV-06:08 5.68 4.62 0.00 0.00 01-NOV-00:10 5.68 4.62
December 0.184584E+10 4151.74 21-DEC-06:07 -0.1 -2.9 0.00 0.00 01-DEC-00:10 -0.1 -2.9
                     
Annual Sum or Average 0.672552E+11         0.00        
Minimum of Months 0.713887E+09 4151.74   -13.2 -14.5 0.00 0.00   -13.2 -14.5
Maximum of Months 0.121971E+11 14473.71   28.87 23.11 0.00 0.00   28.87 23.11



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: MIDFLOOR_PLENUM

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.396647E+09 11347.95 31-JAN-04:01 -7.3 -10.1 0.00 0.00 01-JAN-00:10 -7.3 -10.1
February 0.395346E+09 10120.40 09-FEB-04:01 -8.3 -10.1 0.00 0.00 01-FEB-00:10 -8.3 -10.1
March 0.859845E+09 9919.97 17-MAR-04:01 -1.6 -2.4 0.00 0.00 01-MAR-00:10 -1.6 -2.4
April 0.209787E+10 7295.08 21-APR-04:11 5.60 5.12 0.00 0.00 01-APR-00:10 5.60 5.12
May 0.426347E+10 8351.10 30-MAY-13:20 29.80 17.64 0.00 0.00 01-MAY-00:10 29.80 17.64
June 0.732440E+10 9559.18 01-JUN-15:17 29.23 16.60 0.00 0.00 01-JUN-00:10 29.23 16.60
July 0.864998E+10 9780.27 11-JUL-15:40 28.30 17.32 0.00 0.00 01-JUL-00:10 28.30 17.32
August 0.958415E+10 9701.29 22-AUG-15:17 29.80 17.39 0.00 0.00 01-AUG-00:10 29.80 17.39
September 0.599385E+10 8494.89 05-SEP-15:30 25.85 21.60 0.00 0.00 01-SEP-00:10 25.85 21.60
October 0.367782E+10 5817.57 05-OCT-15:40 21.87 19.18 0.00 0.00 01-OCT-00:10 21.87 19.18
November 0.956860E+09 8957.21 24-NOV-04:01 -3.4 -5.8 0.00 0.00 01-NOV-00:10 -3.4 -5.8
December 0.358703E+09 9183.24 23-DEC-05:11 2.97 2.63 0.00 0.00 01-DEC-00:10 2.97 2.63
                     
Annual Sum or Average 0.445589E+11         0.00        
Minimum of Months 0.358703E+09 5817.57   -8.3 -10.1 0.00 0.00   -8.3 -10.1
Maximum of Months 0.958415E+10 11347.95   29.80 21.60 0.00 0.00   29.80 21.60



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: TOPFLOOR_PLENUM

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 320172.40 222.15 19-JAN-13:10 9.40 4.10 0.00 0.00 01-JAN-00:10 9.40 4.10
February 27666681.41 1372.05 17-FEB-13:05 6.70 1.67 0.00 0.00 01-FEB-00:10 6.70 1.67
March 0.111157E+10 7767.60 03-MAR-14:40 15.00 8.47 0.00 0.00 01-MAR-00:10 15.00 8.47
April 0.345272E+10 15777.25 07-APR-13:20 26.50 16.25 0.00 0.00 01-APR-00:10 26.50 16.25
May 0.759420E+10 23266.47 30-MAY-13:30 29.70 17.47 0.00 0.00 01-MAY-00:10 29.70 17.47
June 0.126316E+11 23583.74 19-JUN-13:30 34.70 23.81 0.00 0.00 01-JUN-00:10 34.70 23.81
July 0.151958E+11 22411.20 10-JUL-13:50 32.70 20.82 0.00 0.00 01-JUL-00:10 32.70 20.82
August 0.162284E+11 22147.74 22-AUG-14:25 30.55 18.03 0.00 0.00 01-AUG-00:10 30.55 18.03
September 0.832939E+10 20649.57 01-SEP-13:30 30.85 17.87 0.00 0.00 01-SEP-00:10 30.85 17.87
October 0.446830E+10 12957.92 04-OCT-15:10 23.72 19.12 0.00 0.00 01-OCT-00:10 23.72 19.12
November 0.473242E+09 5286.92 03-NOV-14:20 17.60 10.78 0.00 0.00 01-NOV-00:10 17.60 10.78
December 4245631.23 1358.75 17-DEC-13:44 12.20 5.23 0.00 0.00 01-DEC-00:10 12.20 5.23
                     
Annual Sum or Average 0.695175E+11         0.00        
Minimum of Months 320172.40 222.15   6.70 1.67 0.00 0.00   6.70 1.67
Maximum of Months 0.162284E+11 23583.74   34.70 23.81 0.00 0.00   34.70 23.81



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.255320E+10 2224.97 20-JAN-16:30 6.40 3.51 95229351.94 126.83 24-JAN-14:00 11.00 11.00
February 0.739324E+10 4400.05 14-FEB-17:00 0.00 -4.1 86396469.43 126.82 02-FEB-14:50 0.00 -4.1
March 0.141946E+11 6951.38 31-MAR-24:00 5.40 5.40 0.103237E+09 126.83 06-MAR-14:00 5.40 5.40
April 0.189150E+11 8426.30 23-APR-17:44 12.38 8.83 91605427.93 126.83 17-APR-09:00 12.38 8.83
May 0.456517E+10 3550.57 31-MAY-24:00 18.50 16.73 99238778.91 126.85 31-MAY-13:20 18.50 16.73
June 0.956943E+10 5370.07 30-JUN-24:00 20.00 19.21 98972884.23 126.86 21-JUN-09:09 20.00 19.21
July 0.149403E+11 7261.65 31-JUL-23:53 23.90 22.01 91891777.92 126.85 18-JUL-09:09 23.90 22.01
August 0.201022E+11 8334.58 31-AUG-17:40 25.20 22.10 0.103475E+09 130.35 16-AUG-13:00 25.20 22.10
September 0.456143E+10 3408.96 30-SEP-24:00 12.60 11.96 91611682.33 126.86 05-SEP-09:39 12.60 11.96
October 0.962265E+10 5150.22 31-OCT-24:00 10.60 9.48 95237596.65 126.86 06-OCT-09:30 10.60 9.48
November 0.136408E+11 6139.89 03-NOV-16:00 15.00 10.26 94301156.05 126.84 10-NOV-10:30 15.85 15.19
December 0.189151E+11 8043.24 08-DEC-16:00 6.10 1.88 91880797.12 126.82 21-DEC-10:09 0.78 -2.5
                     
Annual Sum or Average 0.138973E+12         0.114308E+10        
Minimum of Months 0.255320E+10 2224.97   0.00 -4.1 86396469.43 126.82   0.00 -4.1
Maximum of Months 0.201022E+11 8426.30   25.20 22.10 0.103475E+09 130.35   25.20 22.10



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: DATACENTER_MID_ZN_6

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.718544E+09 1900.36 20-JAN-16:30 6.40 3.51 94061946.88 126.83 24-JAN-14:00 11.00 11.00
February 0.496175E+10 3922.03 22-FEB-17:00 3.30 -0.7 86396476.48 126.82 02-FEB-14:50 3.30 -0.7
March 0.119287E+11 6034.63 31-MAR-23:30 5.80 5.80 0.103237E+09 126.83 27-MAR-13:00 5.80 5.80
April 0.169524E+11 7746.05 09-APR-17:31 15.37 13.32 91605541.94 126.83 17-APR-09:00 13.30 12.36
May 0.380285E+10 3370.79 31-MAY-24:00 18.50 16.73 99236530.09 126.85 31-MAY-13:00 18.50 16.73
June 0.895667E+10 5053.02 30-JUN-24:00 20.00 19.21 98973757.06 126.86 15-JUN-13:30 20.00 19.21
July 0.142343E+11 6981.10 31-JUL-24:00 23.90 22.01 91893281.13 126.85 18-JUL-09:00 23.90 22.01
August 0.191366E+11 7987.24 31-AUG-17:30 25.30 22.17 0.103358E+09 129.19 16-AUG-13:00 25.30 22.17
September 0.392196E+10 3066.13 30-SEP-23:30 13.00 12.21 91609882.69 126.85 06-SEP-13:00 13.00 12.21
October 0.833493E+10 4392.31 31-OCT-24:00 10.60 9.48 95237465.91 126.85 24-OCT-13:00 10.60 9.48
November 0.111704E+11 5743.49 03-NOV-16:00 15.00 10.26 94301133.35 126.84 10-NOV-10:50 15.68 14.79
December 0.156258E+11 7377.63 08-DEC-16:10 5.92 1.77 91880825.03 126.82 21-DEC-10:09 0.78 -2.5
                     
Annual Sum or Average 0.119745E+12         0.114179E+10        
Minimum of Months 0.718544E+09 1900.36   3.30 -0.7 86396476.48 126.82   0.78 -2.5
Maximum of Months 0.191366E+11 7987.24   25.30 22.17 0.103358E+09 129.19   25.30 22.17



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.409138E+09 1852.20 20-JAN-16:40 6.13 3.40 92150719.64 126.82 18-JAN-14:00 6.13 3.40
February 0.352429E+10 3860.49 22-FEB-17:00 3.30 -0.7 86396224.61 126.82 02-FEB-14:50 3.30 -0.7
March 0.106653E+11 5929.46 29-MAR-17:20 5.73 4.14 0.103237E+09 126.83 27-MAR-13:00 5.73 4.14
April 0.161064E+11 7769.57 09-APR-17:22 15.55 13.44 91605570.91 126.83 17-APR-09:00 13.30 12.36
May 0.343096E+10 3324.43 31-MAY-24:00 18.50 16.73 99236174.84 126.86 31-MAY-13:09 18.50 16.73
June 0.891785E+10 4965.05 30-JUN-24:00 20.00 19.21 98973565.47 126.86 27-JUN-09:00 20.00 19.21
July 0.143168E+11 6975.58 31-JUL-24:00 23.90 22.01 91893117.60 126.85 18-JUL-09:00 23.90 22.01
August 0.191797E+11 8099.81 31-AUG-17:30 25.30 22.17 0.103325E+09 128.63 16-AUG-13:00 25.30 22.17
September 0.366808E+10 2827.51 10-SEP-17:33 22.07 11.96 91610068.09 126.86 06-SEP-13:09 22.07 11.96
October 0.750175E+10 4229.43 04-OCT-16:30 22.25 18.94 95237463.03 126.85 24-OCT-13:00 22.20 19.22
November 0.969161E+10 5729.08 03-NOV-16:00 15.00 10.26 94301144.10 126.84 10-NOV-10:50 15.68 14.79
December 0.137812E+11 7251.82 08-DEC-16:10 5.92 1.77 91880833.18 126.82 21-DEC-10:09 0.78 -2.5
                     
Annual Sum or Average 0.111193E+12         0.113985E+10        
Minimum of Months 0.409138E+09 1852.20   3.30 -0.7 86396224.61 126.82   0.78 -2.5
Maximum of Months 0.191797E+11 8099.81   25.30 22.17 0.103325E+09 128.63   25.30 22.17



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.236644E+12 92483.74 20-JAN-17:00 5.60 3.19 0.206163E+10 2746.93 26-JAN-10:00 3.30 -0.4
February 0.434893E+12 183910.69 22-FEB-17:00 3.30 -0.7 0.187117E+10 2748.98 07-FEB-10:30 3.30 -0.7
March 0.729779E+12 358621.43 31-MAR-24:00 5.40 5.40 0.223541E+10 2748.51 23-MAR-13:09 5.40 5.40
April 0.943799E+12 368668.45 10-APR-16:00 20.00 11.13 0.198557E+10 2952.07 07-APR-13:39 20.00 11.13
May 0.241691E+12 176659.38 31-MAY-24:00 18.50 16.73 0.214835E+10 2746.49 18-MAY-13:00 18.50 16.73
June 0.472103E+12 268222.88 30-JUN-24:00 20.00 19.21 0.214254E+10 2746.52 15-JUN-13:00 20.00 19.21
July 0.733910E+12 360444.63 31-JUL-23:53 23.90 22.01 0.198919E+10 2745.89 18-JUL-09:00 23.90 22.01
August 0.977146E+12 370533.07 18-AUG-23:03 23.22 17.14 0.246759E+10 3496.85 16-AUG-13:00 23.22 17.14
September 0.237705E+12 176650.77 30-SEP-24:00 12.60 11.96 0.198338E+10 2746.90 14-SEP-09:00 12.60 11.96
October 0.489760E+12 268524.87 31-OCT-24:00 10.60 9.48 0.206178E+10 2747.18 26-OCT-13:09 10.60 9.48
November 0.709230E+12 277669.41 03-NOV-16:00 15.00 10.26 0.204171E+10 2747.96 24-NOV-14:09 1.78 -1.8
December 0.976601E+12 368701.89 21-DEC-17:00 1.70 -2.8 0.198998E+10 2748.07 21-DEC-14:00 1.70 -2.8
                     
Annual Sum or Average 0.718326E+13         0.249783E+11        
Minimum of Months 0.236644E+12 92483.74   1.70 -2.8 0.187117E+10 2745.89   1.70 -2.8
Maximum of Months 0.977146E+12 370533.07   23.90 22.01 0.246759E+10 3496.85   23.90 22.01



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: BASEMENT

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 77939384.89 12221.65 03-JAN-06:05 4.27
February 79453654.81 11846.75 09-FEB-05:03 -8.3
March 96368140.14 12473.27 04-MAR-05:15 7.60
April 98246921.19 12492.73 06-APR-04:15 10.00
May 0.205789E+09 12532.19 25-MAY-04:15 12.60
June 0.244027E+09 11761.59 22-JUN-03:04 24.22
July 0.409428E+09 14217.44 21-JUL-03:53 24.40
August 0.387246E+09 13821.83 12-AUG-16:02 27.80
September 0.329996E+09 14197.00 03-SEP-19:53 22.20
October 0.392998E+09 12379.78 10-OCT-04:15 10.40
November 0.271046E+09 12777.16 20-NOV-04:07 0.60
December 0.147508E+09 12274.54 19-DEC-05:54 3.30
         
Annual Sum or Average 0.274005E+10      
Minimum of Months 77939384.89 11761.59   -8.3
Maximum of Months 0.409428E+09 14217.44   27.80



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: CORE_BOTTOM

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:01 -9.6
February 0.00 0.00 01-FEB-00:10 -1.1
March 0.00 0.00 01-MAR-00:10 5.52
April 0.00 0.00 01-APR-00:10 5.27
May 0.00 0.00 01-MAY-00:10 10.33
June 0.00 0.00 01-JUN-00:10 18.37
July 0.00 0.00 01-JUL-00:10 20.00
August 0.00 0.00 01-AUG-00:03 23.90
September 0.00 0.00 01-SEP-00:03 23.43
October 0.00 0.00 01-OCT-00:10 12.47
November 0.00 0.00 01-NOV-00:10 10.40
December 0.00 0.00 01-DEC-00:10 5.97
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   -9.6
Maximum of Months 0.00 0.00   23.90



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: CORE_MID

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.944669E+09 56284.26 02-JAN-04:01 -11.8
February 0.127737E+09 45720.55 06-FEB-05:01 -13.2
March 16673551.77 10018.78 17-MAR-13:28 -0.9
April 0.00 0.00 01-APR-00:10 5.27
May 0.00 0.00 01-MAY-00:10 10.33
June 0.00 0.00 01-JUN-00:10 18.37
July 0.00 0.00 01-JUL-00:10 20.00
August 0.00 0.00 01-AUG-00:03 23.90
September 0.00 0.00 01-SEP-00:03 23.43
October 0.00 0.00 01-OCT-00:10 12.47
November 1348361.37 8989.08 24-NOV-08:35 -2.4
December 1681099.35 2632.30 21-DEC-10:15 0.97
         
Annual Sum or Average 0.109211E+10      
Minimum of Months 0.00 0.00   -13.2
Maximum of Months 0.944669E+09 56284.26   23.90



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: CORE_TOP

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.412603E+10 87214.25 02-JAN-04:01 -11.8
February 0.275088E+10 86127.74 06-FEB-04:11 -13.3
March 0.562179E+09 78087.41 20-MAR-04:01 -0.8
April 96827710.63 73588.98 03-APR-04:11 2.80
May 0.00 0.00 01-MAY-00:10 10.33
June 0.00 0.00 01-JUN-00:10 18.37
July 0.00 0.00 01-JUL-00:10 20.00
August 0.00 0.00 01-AUG-00:03 23.90
September 0.00 0.00 01-SEP-00:03 23.43
October 8819474.47 35557.23 30-OCT-05:03 11.93
November 0.107484E+10 80056.22 24-NOV-04:01 -3.4
December 0.139792E+10 82426.34 26-DEC-05:11 5.77
         
Annual Sum or Average 0.100175E+11      
Minimum of Months 0.00 0.00   -13.3
Maximum of Months 0.412603E+10 87214.25   23.90



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.393289E+09 14699.54 02-JAN-04:01 -11.8
February 0.285910E+09 14285.66 06-FEB-05:01 -13.2
March 918915.77 7368.47 17-MAR-05:01 -1.1
April 0.00 0.00 01-APR-00:10 5.27
May 0.00 0.00 01-MAY-00:10 10.33
June 0.00 0.00 01-JUN-00:10 18.37
July 0.00 0.00 01-JUL-00:10 20.00
August 0.00 0.00 01-AUG-00:03 23.90
September 0.00 0.00 01-SEP-00:03 23.43
October 0.00 0.00 01-OCT-00:10 12.47
November 4104693.91 12401.05 22-NOV-06:01 -2.2
December 2720585.62 10141.82 02-DEC-06:01 1.10
         
Annual Sum or Average 0.686943E+09      
Minimum of Months 0.00 0.00   -13.2
Maximum of Months 0.393289E+09 14699.54   23.90



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.272042E+09 12658.61 02-JAN-05:21 -11.9
February 0.176842E+09 12723.43 06-FEB-05:01 -13.2
March 8445952.18 9498.81 17-MAR-05:01 -1.1
April 0.00 0.00 01-APR-00:10 5.27
May 0.00 0.00 01-MAY-00:10 10.33
June 0.00 0.00 01-JUN-00:10 18.37
July 0.00 0.00 01-JUL-00:10 20.00
August 0.00 0.00 01-AUG-00:03 23.90
September 0.00 0.00 01-SEP-00:03 23.43
October 0.00 0.00 01-OCT-00:10 12.47
November 9342605.79 9580.19 22-NOV-06:01 -2.2
December 20828396.26 9578.85 02-DEC-06:01 1.10
         
Annual Sum or Average 0.487501E+09      
Minimum of Months 0.00 0.00   -13.2
Maximum of Months 0.272042E+09 12723.43   23.90



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.524788E+09 19849.68 02-JAN-04:01 -11.8
February 0.312635E+09 19373.81 06-FEB-04:01 -13.3
March 20150477.70 14887.04 17-MAR-05:01 -1.1
April 0.00 0.00 01-APR-00:10 5.27
May 0.00 0.00 01-MAY-00:10 10.33
June 0.00 0.00 01-JUN-00:10 18.37
July 0.00 0.00 01-JUL-00:10 20.00
August 0.00 0.00 01-AUG-00:03 23.90
September 0.00 0.00 01-SEP-00:03 23.43
October 0.00 0.00 01-OCT-00:10 12.47
November 23439006.08 14970.26 24-NOV-06:01 -4.4
December 40621971.06 14954.13 07-DEC-06:01 0.10
         
Annual Sum or Average 0.921635E+09      
Minimum of Months 0.00 0.00   -13.3
Maximum of Months 0.524788E+09 19849.68   23.90



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 65763144.82 10933.79 02-JAN-05:01 -12.1
February 30556664.87 10697.52 06-FEB-05:01 -13.2
March 0.00 0.00 01-MAR-00:10 5.52
April 0.00 0.00 01-APR-00:10 5.27
May 0.00 0.00 01-MAY-00:10 10.33
June 0.00 0.00 01-JUN-00:10 18.37
July 0.00 0.00 01-JUL-00:10 20.00
August 0.00 0.00 01-AUG-00:03 23.90
September 0.00 0.00 01-SEP-00:03 23.43
October 0.00 0.00 01-OCT-00:10 12.47
November 0.00 0.00 01-NOV-00:10 10.40
December 0.00 0.00 01-DEC-00:10 5.97
         
Annual Sum or Average 96319809.69      
Minimum of Months 0.00 0.00   -13.2
Maximum of Months 65763144.82 10933.79   23.90



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.492051E+10 16565.65 02-JAN-02:42 -11.7
February 0.387991E+10 16210.15 06-FEB-01:21 -13.3
March 0.890794E+09 14482.35 13-MAR-03:02 0.50
April 0.160241E+09 13643.32 03-APR-04:11 2.80
May 0.00 0.00 01-MAY-00:10 10.33
June 0.00 0.00 01-JUN-00:10 18.37
July 0.00 0.00 01-JUL-00:10 20.00
August 0.00 0.00 01-AUG-00:03 23.90
September 0.00 0.00 01-SEP-00:03 23.43
October 16347443.22 12340.49 28-OCT-05:03 3.90
November 0.930910E+09 15272.01 24-NOV-04:01 -3.4
December 0.221939E+10 16474.00 31-DEC-22:02 -7.3
         
Annual Sum or Average 0.130181E+11      
Minimum of Months 0.00 0.00   -13.3
Maximum of Months 0.492051E+10 16565.65   23.90



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.276241E+10 21255.76 01-JAN-05:22 -3.6
February 0.185872E+10 20925.22 06-FEB-01:21 -13.3
March 0.459594E+09 17916.56 22-MAR-04:11 -1.9
April 94938633.47 17200.45 03-APR-04:11 2.80
May 0.00 0.00 01-MAY-00:10 10.33
June 0.00 0.00 01-JUN-00:10 18.37
July 0.00 0.00 01-JUL-00:10 20.00
August 0.00 0.00 01-AUG-00:03 23.90
September 0.00 0.00 01-SEP-00:03 23.43
October 8261258.61 9301.30 28-OCT-05:03 3.90
November 0.492068E+09 19526.72 24-NOV-04:01 -3.4
December 0.124027E+10 20960.60 31-DEC-22:02 -7.3
         
Annual Sum or Average 0.691627E+10      
Minimum of Months 0.00 0.00   -13.3
Maximum of Months 0.276241E+10 21255.76   23.90



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.297249E+10 24070.38 01-JAN-05:22 -3.6
February 0.181883E+10 23553.87 06-FEB-04:01 -13.3
March 0.501861E+09 20254.63 17-MAR-04:01 -1.6
April 0.119347E+09 19321.51 22-APR-04:11 5.60
May 0.00 0.00 01-MAY-00:10 10.33
June 0.00 0.00 01-JUN-00:10 18.37
July 0.00 0.00 01-JUL-00:10 20.00
August 0.00 0.00 01-AUG-00:03 23.90
September 0.00 0.00 01-SEP-00:03 23.43
October 988307.38 4170.23 28-OCT-05:03 3.90
November 0.440499E+09 20434.03 27-NOV-05:11 6.30
December 0.121825E+10 21272.94 11-DEC-04:51 1.70
         
Annual Sum or Average 0.707226E+10      
Minimum of Months 0.00 0.00   -13.3
Maximum of Months 0.297249E+10 24070.38   23.90



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.234649E+10 21334.13 02-JAN-02:42 -11.7
February 0.165602E+10 21012.46 06-FEB-00:41 -13.3
March 0.313554E+09 17756.37 22-MAR-04:11 -1.9
April 52658834.12 16209.91 21-APR-04:11 5.60
May 0.00 0.00 01-MAY-00:10 10.33
June 0.00 0.00 01-JUN-00:10 18.37
July 0.00 0.00 01-JUL-00:10 20.00
August 0.00 0.00 01-AUG-00:03 23.90
September 0.00 0.00 01-SEP-00:03 23.43
October 3650338.88 6409.21 27-OCT-05:02 6.02
November 0.398116E+09 18978.53 24-NOV-04:01 -3.4
December 0.906153E+09 17948.04 07-DEC-05:01 0.00
         
Annual Sum or Average 0.567664E+10      
Minimum of Months 0.00 0.00   -13.3
Maximum of Months 0.234649E+10 21334.13   23.90



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.871736E+10 19018.57 01-JAN-04:42 -3.3
February 0.768108E+10 19761.05 06-FEB-04:11 -13.3
March 0.262320E+10 17675.91 13-MAR-03:11 0.40
April 0.783058E+09 17425.11 03-APR-04:11 2.80
May 28700195.27 14546.38 01-MAY-04:12 6.50
June 0.00 0.00 01-JUN-00:10 18.37
July 0.00 0.00 01-JUL-00:10 20.00
August 0.00 0.00 01-AUG-00:03 23.90
September 0.00 0.00 01-SEP-00:03 23.43
October 0.264024E+09 15297.57 28-OCT-04:11 4.23
November 0.287892E+10 18118.52 23-NOV-23:23 -3.0
December 0.582791E+10 18542.68 31-DEC-19:02 -5.7
         
Annual Sum or Average 0.288043E+11      
Minimum of Months 0.00 0.00   -13.3
Maximum of Months 0.871736E+10 19761.05   23.90



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.492549E+10 22883.76 01-JAN-05:22 -3.6
February 0.386548E+10 24042.65 06-FEB-04:11 -13.3
March 0.130305E+10 21453.32 13-MAR-03:11 0.40
April 0.432623E+09 20856.21 03-APR-04:11 2.80
May 15025988.73 12685.75 01-MAY-04:12 6.50
June 0.00 0.00 01-JUN-00:10 18.37
July 0.00 0.00 01-JUL-00:10 20.00
August 0.00 0.00 01-AUG-00:03 23.90
September 0.00 0.00 01-SEP-00:03 23.43
October 0.132610E+09 18275.93 28-OCT-04:11 4.23
November 0.148651E+10 21559.40 24-NOV-04:01 -3.4
December 0.317572E+10 22213.22 31-DEC-19:02 -5.7
         
Annual Sum or Average 0.153365E+11      
Minimum of Months 0.00 0.00   -13.3
Maximum of Months 0.492549E+10 24042.65   23.90



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.574624E+10 26497.55 01-JAN-05:22 -3.6
February 0.434953E+10 27557.06 06-FEB-04:11 -13.3
March 0.163549E+10 24688.21 13-MAR-03:11 0.40
April 0.629106E+09 23662.41 03-APR-04:11 2.80
May 32120403.70 16396.83 01-MAY-04:12 6.50
June 0.00 0.00 01-JUN-00:10 18.37
July 0.00 0.00 01-JUL-00:10 20.00
August 0.00 0.00 01-AUG-00:03 23.90
September 0.00 0.00 01-SEP-00:03 23.43
October 0.101658E+09 20534.01 28-OCT-04:11 4.23
November 0.160173E+10 24720.50 24-NOV-04:01 -3.4
December 0.355494E+10 25514.26 31-DEC-22:22 -7.5
         
Annual Sum or Average 0.176508E+11      
Minimum of Months 0.00 0.00   -13.3
Maximum of Months 0.574624E+10 27557.06   23.90



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.435311E+10 24703.75 01-JAN-05:22 -3.6
February 0.342324E+10 25736.32 06-FEB-04:11 -13.3
March 0.963266E+09 22891.66 13-MAR-03:11 0.40
April 0.279584E+09 21067.41 03-APR-04:11 2.80
May 6387190.26 8682.67 01-MAY-05:03 6.28
June 0.00 0.00 01-JUN-00:10 18.37
July 0.00 0.00 01-JUL-00:10 20.00
August 0.00 0.00 01-AUG-00:03 23.90
September 0.00 0.00 01-SEP-00:03 23.43
October 79791001.17 18590.89 28-OCT-04:11 4.23
November 0.122844E+10 23042.75 24-NOV-04:01 -3.4
December 0.241451E+10 23674.12 31-DEC-22:22 -7.5
         
Annual Sum or Average 0.127483E+11      
Minimum of Months 0.00 0.00   -13.3
Maximum of Months 0.435311E+10 25736.32   23.90



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: GROUNDFLOOR_PLENUM

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.112759E+10 11612.18 18-JAN-06:03 7.38
February 0.714105E+09 11262.35 02-FEB-06:02 4.32
March 0.107194E+09 12285.89 13-MAR-04:01 -0.1
April 0.142885E+09 12508.84 17-APR-04:12 12.43
May 81816426.79 9455.78 01-MAY-04:12 6.50
June 80685376.18 9687.79 12-JUN-04:12 18.70
July 0.116205E+09 11451.14 09-JUL-14:21 29.45
August 80093101.92 11744.35 13-AUG-15:11 30.40
September 74281026.94 9581.78 10-SEP-14:51 24.40
October 94221229.65 9983.34 10-OCT-04:12 10.40
November 85429681.14 13049.61 27-NOV-05:11 6.30
December 0.141091E+09 13698.71 26-DEC-05:11 5.77
         
Annual Sum or Average 0.284560E+10      
Minimum of Months 74281026.94 9455.78   -0.1
Maximum of Months 0.112759E+10 13698.71   30.40



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: MIDFLOOR_PLENUM

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.483298E+10 20500.35 02-JAN-06:12 -11.7
February 0.281496E+10 14690.39 09-FEB-19:23 -2.2
March 0.127618E+10 10908.53 17-MAR-14:00 -0.6
April 0.367635E+09 10046.98 23-APR-16:21 13.30
May 72023813.83 11136.45 28-MAY-14:51 26.70
June 52494633.19 8622.79 04-JUN-14:01 24.32
July 78832594.12 11091.05 09-JUL-14:21 29.45
August 57727063.63 12710.51 13-AUG-14:21 31.15
September 66381022.11 10057.14 10-SEP-15:02 24.22
October 83872094.18 9774.16 15-OCT-15:01 20.40
November 0.902825E+09 6519.12 10-NOV-06:03 14.60
December 0.171069E+10 10113.63 03-DEC-12:43 8.22
         
Annual Sum or Average 0.123166E+11      
Minimum of Months 52494633.19 6519.12   -11.7
Maximum of Months 0.483298E+10 20500.35   31.15



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: TOPFLOOR_PLENUM

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.111106E+11 30649.77 02-JAN-05:09 -12.1
February 0.925362E+10 33599.84 06-FEB-05:09 -13.2
March 0.390535E+10 20889.90 13-MAR-05:01 -0.6
April 0.159122E+10 16807.03 03-APR-05:03 2.70
May 0.263424E+09 14991.97 11-MAY-05:02 10.78
June 58814913.58 14595.56 03-JUN-05:03 13.48
July 44472102.98 11079.98 05-JUL-04:12 20.60
August 55048042.86 12736.82 08-AUG-04:12 15.40
September 0.149123E+09 15178.17 29-SEP-05:03 11.78
October 0.869196E+09 14072.79 26-OCT-05:03 12.12
November 0.441169E+10 25979.85 24-NOV-06:12 -4.4
December 0.800570E+10 23994.13 11-DEC-05:22 1.70
         
Annual Sum or Average 0.397183E+11      
Minimum of Months 44472102.98 11079.98   -13.2
Maximum of Months 0.111106E+11 33599.84   20.60



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 6438388.47 453.39 01-JAN-20:42 -8.0
February 0.00 0.00 01-FEB-00:10 -1.1
March 0.00 0.00 01-MAR-00:10 5.52
April 0.00 0.00 01-APR-00:10 5.27
May 0.00 0.00 01-MAY-00:10 10.33
June 0.00 0.00 01-JUN-00:10 18.37
July 0.00 0.00 01-JUL-00:10 20.00
August 0.00 0.00 01-AUG-00:03 23.90
September 0.00 0.00 01-SEP-00:03 23.43
October 0.00 0.00 01-OCT-00:10 12.47
November 0.00 0.00 01-NOV-00:10 10.40
December 0.00 0.00 01-DEC-00:10 5.97
         
Annual Sum or Average 6438388.47      
Minimum of Months 0.00 0.00   -8.0
Maximum of Months 6438388.47 453.39   23.90



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: DATACENTER_MID_ZN_6

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.438504E+09 571.43 15-JAN-18:00 1.70
February 0.00 0.00 01-FEB-00:10 -1.1
March 0.00 0.00 01-MAR-00:10 5.52
April 0.00 0.00 01-APR-00:10 5.27
May 0.00 0.00 01-MAY-00:10 10.33
June 0.00 0.00 01-JUN-00:10 18.37
July 0.00 0.00 01-JUL-00:10 20.00
August 0.00 0.00 01-AUG-00:03 23.90
September 0.00 0.00 01-SEP-00:03 23.43
October 0.00 0.00 01-OCT-00:10 12.47
November 0.00 0.00 01-NOV-00:10 10.40
December 0.00 0.00 01-DEC-00:10 5.97
         
Annual Sum or Average 0.438504E+09      
Minimum of Months 0.00 0.00   -1.1
Maximum of Months 0.438504E+09 571.43   23.90



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.727768E+09 610.16 16-JAN-18:00 3.90
February 61818739.82 551.83 05-FEB-23:10 -12.4
March 0.00 0.00 01-MAR-00:10 5.52
April 0.00 0.00 01-APR-00:10 5.27
May 950905.18 367.74 01-MAY-03:35 7.00
June 0.00 0.00 01-JUN-00:10 18.37
July 0.00 0.00 01-JUL-00:10 20.00
August 0.00 0.00 01-AUG-00:03 23.90
September 0.00 0.00 01-SEP-00:03 23.43
October 0.00 0.00 01-OCT-00:10 12.47
November 0.00 0.00 01-NOV-00:10 10.40
December 0.00 0.00 01-DEC-00:10 5.97
         
Annual Sum or Average 0.790537E+09      
Minimum of Months 0.00 0.00   -12.4
Maximum of Months 0.727768E+09 610.16   23.90



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:01 -9.6
February 0.00 0.00 01-FEB-00:10 -1.1
March 0.00 0.00 01-MAR-00:10 5.52
April 0.00 0.00 01-APR-00:10 5.27
May 0.00 0.00 01-MAY-00:10 10.33
June 0.00 0.00 01-JUN-00:10 18.37
July 0.00 0.00 01-JUL-00:10 20.00
August 0.00 0.00 01-AUG-00:03 23.90
September 0.00 0.00 01-SEP-00:03 23.43
October 0.00 0.00 01-OCT-00:10 12.47
November 0.00 0.00 01-NOV-00:10 10.40
December 0.00 0.00 01-DEC-00:10 5.97
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   -9.6
Maximum of Months 0.00 0.00   23.90



Table of Contents

Report: ZoneElectricSummaryMonthly

For: BASEMENT

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.219312E+11 22950.34 02-JAN-08:09 0.360447E+11 13457.54 01-JAN-00:10
February 0.198933E+11 22950.34 01-FEB-08:09 0.325565E+11 13457.54 01-FEB-00:10
March 0.236388E+11 22950.34 01-MAR-08:09 0.360447E+11 13457.54 01-MAR-00:10
April 0.211142E+11 22950.34 03-APR-07:10 0.348820E+11 13457.54 01-APR-00:10
May 0.227850E+11 22950.34 01-MAY-07:10 0.360447E+11 13457.54 01-MAY-00:10
June 0.226748E+11 22950.34 01-JUN-07:10 0.348820E+11 13457.54 01-JUN-00:10
July 0.212244E+11 22950.34 03-JUL-07:10 0.360447E+11 13457.54 01-JUL-00:10
August 0.236388E+11 22950.34 01-AUG-07:10 0.360447E+11 13457.54 01-AUG-00:10
September 0.211142E+11 22950.34 01-SEP-07:10 0.348820E+11 13457.54 01-SEP-00:10
October 0.219312E+11 22950.34 02-OCT-07:10 0.360447E+11 13457.54 01-OCT-00:10
November 0.216742E+11 22950.34 01-NOV-07:10 0.348820E+11 13457.54 01-NOV-00:10
December 0.212244E+11 22950.34 01-DEC-08:09 0.360447E+11 13457.54 01-DEC-00:10
             
Annual Sum or Average 0.262844E+12     0.424397E+12    
Minimum of Months 0.198933E+11 22950.34   0.325565E+11 13457.54  
Maximum of Months 0.236388E+11 22950.34   0.360447E+11 13457.54  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: CORE_BOTTOM

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.196958E+11 20611.01 02-JAN-08:09 0.243681E+11 17206.63 02-JAN-08:09
February 0.178655E+11 20611.01 01-FEB-08:09 0.220609E+11 17206.63 01-FEB-08:09
March 0.212293E+11 20611.01 01-MAR-08:09 0.253549E+11 17206.63 01-MAR-08:09
April 0.189620E+11 20611.01 03-APR-07:10 0.235306E+11 17206.63 03-APR-07:10
May 0.204625E+11 20611.01 01-MAY-07:10 0.248615E+11 17206.63 01-MAY-07:10
June 0.203636E+11 20611.01 01-JUN-07:10 0.244160E+11 17206.63 01-JUN-07:10
July 0.190610E+11 20611.01 03-JUL-07:10 0.239708E+11 17206.63 03-JUL-07:10
August 0.212293E+11 20611.01 01-AUG-07:10 0.253549E+11 17206.63 01-AUG-07:10
September 0.189620E+11 20611.01 01-SEP-07:10 0.235199E+11 17206.63 01-SEP-07:10
October 0.196958E+11 20611.01 02-OCT-07:10 0.243735E+11 17206.63 02-OCT-07:10
November 0.194649E+11 20611.01 01-NOV-07:10 0.238373E+11 17206.63 01-NOV-07:10
December 0.190610E+11 20611.01 01-DEC-08:09 0.239654E+11 17206.63 01-DEC-08:09
             
Annual Sum or Average 0.236053E+12     0.289614E+12    
Minimum of Months 0.178655E+11 20611.01   0.220609E+11 17206.63  
Maximum of Months 0.212293E+11 20611.01   0.253549E+11 17206.63  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: CORE_MID

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.196958E+11 20611.01 02-JAN-08:09 0.243680E+11 17206.56 02-JAN-08:09
February 0.178655E+11 20611.01 01-FEB-08:09 0.220609E+11 17206.56 01-FEB-08:09
March 0.212293E+11 20611.01 01-MAR-08:09 0.253548E+11 17206.56 01-MAR-08:09
April 0.189620E+11 20611.01 03-APR-07:10 0.235305E+11 17206.56 03-APR-07:10
May 0.204625E+11 20611.01 01-MAY-07:10 0.248614E+11 17206.56 01-MAY-07:10
June 0.203636E+11 20611.01 01-JUN-07:10 0.244159E+11 17206.56 01-JUN-07:10
July 0.190610E+11 20611.01 03-JUL-07:10 0.239707E+11 17206.56 03-JUL-07:10
August 0.212293E+11 20611.01 01-AUG-07:10 0.253548E+11 17206.56 01-AUG-07:10
September 0.189620E+11 20611.01 01-SEP-07:10 0.235198E+11 17206.56 01-SEP-07:10
October 0.196958E+11 20611.01 02-OCT-07:10 0.243734E+11 17206.56 02-OCT-07:10
November 0.194649E+11 20611.01 01-NOV-07:10 0.238372E+11 17206.56 01-NOV-07:10
December 0.190610E+11 20611.01 01-DEC-08:09 0.239653E+11 17206.56 01-DEC-08:09
             
Annual Sum or Average 0.236053E+12     0.289613E+12    
Minimum of Months 0.178655E+11 20611.01   0.220609E+11 17206.56  
Maximum of Months 0.212293E+11 20611.01   0.253548E+11 17206.56  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: CORE_TOP

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.196958E+11 20611.01 02-JAN-08:09 0.243680E+11 17206.56 02-JAN-08:09
February 0.178655E+11 20611.01 01-FEB-08:09 0.220609E+11 17206.56 01-FEB-08:09
March 0.212293E+11 20611.01 01-MAR-08:09 0.253548E+11 17206.56 01-MAR-08:09
April 0.189620E+11 20611.01 03-APR-07:10 0.235305E+11 17206.56 03-APR-07:10
May 0.204625E+11 20611.01 01-MAY-07:10 0.248614E+11 17206.56 01-MAY-07:10
June 0.203636E+11 20611.01 01-JUN-07:10 0.244159E+11 17206.56 01-JUN-07:10
July 0.190610E+11 20611.01 03-JUL-07:10 0.239707E+11 17206.56 03-JUL-07:10
August 0.212293E+11 20611.01 01-AUG-07:10 0.253548E+11 17206.56 01-AUG-07:10
September 0.189620E+11 20611.01 01-SEP-07:10 0.235198E+11 17206.56 01-SEP-07:10
October 0.196958E+11 20611.01 02-OCT-07:10 0.243734E+11 17206.56 02-OCT-07:10
November 0.194649E+11 20611.01 01-NOV-07:10 0.238372E+11 17206.56 01-NOV-07:10
December 0.190610E+11 20611.01 01-DEC-08:09 0.239653E+11 17206.56 01-DEC-08:09
             
Annual Sum or Average 0.236053E+12     0.289613E+12    
Minimum of Months 0.178655E+11 20611.01   0.220609E+11 17206.56  
Maximum of Months 0.212293E+11 20611.01   0.253548E+11 17206.56  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.166708E+10 2587.92 02-JAN-16:19 0.305979E+10 2160.55 02-JAN-08:09
February 0.139589E+10 2587.92 01-FEB-16:49 0.277008E+10 2160.55 01-FEB-08:09
March 0.154660E+10 1803.00 02-MAR-16:30 0.318369E+10 2160.55 01-MAR-08:09
April 0.131787E+10 1350.81 14-APR-07:10 0.295462E+10 2160.55 03-APR-07:10
May 0.138455E+10 1350.81 04-MAY-07:10 0.312174E+10 2160.55 01-MAY-07:10
June 0.135468E+10 1350.81 16-JUN-07:10 0.306580E+10 2160.55 01-JUN-07:10
July 0.128005E+10 1350.81 24-JUL-07:10 0.300989E+10 2160.55 03-JUL-07:10
August 0.144587E+10 1470.28 16-AUG-07:10 0.318369E+10 2160.55 01-AUG-07:10
September 0.134568E+10 1803.00 27-SEP-07:10 0.295328E+10 2160.55 01-SEP-07:10
October 0.145981E+10 2255.20 06-OCT-07:10 0.306046E+10 2160.55 02-OCT-07:10
November 0.158993E+10 2587.92 06-NOV-16:19 0.299314E+10 2160.55 01-NOV-07:10
December 0.164721E+10 2587.92 01-DEC-16:10 0.300922E+10 2160.55 01-DEC-08:09
             
Annual Sum or Average 0.174352E+11     0.363654E+11    
Minimum of Months 0.128005E+10 1350.81   0.277008E+10 2160.55  
Maximum of Months 0.166708E+10 2587.92   0.318369E+10 2160.55  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.105752E+10 1667.75 02-JAN-16:19 0.197184E+10 1392.34 02-JAN-08:09
February 0.890082E+09 1667.75 01-FEB-16:49 0.178515E+10 1392.34 01-FEB-08:09
March 0.993363E+09 1453.34 02-MAR-16:49 0.205169E+10 1392.34 01-MAR-08:09
April 0.850718E+09 870.51 05-APR-15:00 0.190407E+10 1392.34 03-APR-07:10
May 0.897753E+09 870.51 08-MAY-07:10 0.201177E+10 1392.34 01-MAY-07:10
June 0.879630E+09 793.52 01-JUN-07:10 0.197572E+10 1392.34 01-JUN-07:10
July 0.830291E+09 793.52 03-JUL-07:10 0.193969E+10 1392.34 03-JUL-07:10
August 0.935442E+09 870.51 16-AUG-07:10 0.205169E+10 1392.34 01-AUG-07:10
September 0.866147E+09 947.51 22-SEP-15:00 0.190321E+10 1392.34 01-SEP-07:10
October 0.935286E+09 1453.34 31-OCT-15:50 0.197228E+10 1392.34 02-OCT-07:10
November 0.101639E+10 1667.75 06-NOV-16:19 0.192889E+10 1392.34 01-NOV-07:10
December 0.103495E+10 1667.75 01-DEC-16:10 0.193926E+10 1392.34 01-DEC-08:09
             
Annual Sum or Average 0.111876E+11     0.234352E+11    
Minimum of Months 0.830291E+09 793.52   0.178515E+10 1392.34  
Maximum of Months 0.105752E+10 1667.75   0.205169E+10 1392.34  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.159588E+10 2587.98 02-JAN-16:30 0.305983E+10 2160.58 02-JAN-08:09
February 0.135323E+10 2587.98 01-FEB-16:00 0.277013E+10 2160.58 01-FEB-08:09
March 0.153012E+10 1803.04 02-MAR-16:40 0.318374E+10 2160.58 01-MAR-08:09
April 0.131948E+10 1350.84 14-APR-07:10 0.295467E+10 2160.58 03-APR-07:10
May 0.139165E+10 1350.84 04-MAY-07:10 0.312179E+10 2160.58 01-MAY-07:10
June 0.136612E+10 1350.84 16-JUN-07:10 0.306585E+10 2160.58 01-JUN-07:10
July 0.128953E+10 1350.84 05-JUL-07:10 0.300994E+10 2160.58 03-JUL-07:10
August 0.145133E+10 1470.31 16-AUG-07:10 0.318374E+10 2160.58 01-AUG-07:10
September 0.134045E+10 1470.31 21-SEP-07:10 0.295333E+10 2160.58 01-SEP-07:10
October 0.143607E+10 2255.25 31-OCT-15:00 0.306051E+10 2160.58 02-OCT-07:10
November 0.154352E+10 2587.98 06-NOV-16:40 0.299318E+10 2160.58 01-NOV-07:10
December 0.155441E+10 2587.98 01-DEC-16:30 0.300927E+10 2160.58 01-DEC-08:09
             
Annual Sum or Average 0.171718E+11     0.363660E+11    
Minimum of Months 0.128953E+10 1350.84   0.277013E+10 2160.58  
Maximum of Months 0.159588E+10 2587.98   0.318374E+10 2160.58  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.104145E+10 1667.75 02-JAN-16:30 0.197183E+10 1392.33 02-JAN-08:09
February 0.877688E+09 1667.75 15-FEB-16:00 0.178514E+10 1392.33 01-FEB-08:09
March 0.983977E+09 1161.92 06-MAR-08:09 0.205168E+10 1392.33 01-MAR-08:09
April 0.849086E+09 947.51 14-APR-07:10 0.190406E+10 1392.33 03-APR-07:10
May 0.890661E+09 947.51 04-MAY-07:10 0.201175E+10 1392.33 01-MAY-07:10
June 0.874073E+09 870.51 12-JUN-07:10 0.197570E+10 1392.33 01-JUN-07:10
July 0.826626E+09 870.51 05-JUL-07:10 0.193968E+10 1392.33 03-JUL-07:10
August 0.930786E+09 947.51 16-AUG-07:10 0.205168E+10 1392.33 01-AUG-07:10
September 0.864640E+09 1161.92 26-SEP-07:10 0.190319E+10 1392.33 01-SEP-07:10
October 0.928958E+09 1453.34 06-OCT-07:10 0.197226E+10 1392.33 02-OCT-07:10
November 0.100055E+10 1667.75 06-NOV-16:40 0.192888E+10 1392.33 01-NOV-07:10
December 0.102279E+10 1667.75 01-DEC-16:30 0.193924E+10 1392.33 01-DEC-08:09
             
Annual Sum or Average 0.110913E+11     0.234351E+11    
Minimum of Months 0.826626E+09 870.51   0.178514E+10 1392.33  
Maximum of Months 0.104145E+10 1667.75   0.205168E+10 1392.33  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.166102E+10 2587.92 02-JAN-16:19 0.305979E+10 2160.55 02-JAN-08:09
February 0.139087E+10 2587.92 01-FEB-16:49 0.277008E+10 2160.55 01-FEB-08:09
March 0.154399E+10 1803.00 02-MAR-16:30 0.318369E+10 2160.55 01-MAR-08:09
April 0.131652E+10 1350.81 14-APR-07:10 0.295462E+10 2160.55 03-APR-07:10
May 0.138331E+10 1350.81 04-MAY-07:10 0.312174E+10 2160.55 01-MAY-07:10
June 0.135382E+10 1350.81 16-JUN-07:10 0.306580E+10 2160.55 01-JUN-07:10
July 0.127888E+10 1350.81 24-JUL-07:10 0.300989E+10 2160.55 03-JUL-07:10
August 0.144515E+10 1350.81 16-AUG-07:10 0.318369E+10 2160.55 01-AUG-07:10
September 0.134367E+10 1803.00 27-SEP-07:10 0.295328E+10 2160.55 01-SEP-07:10
October 0.145717E+10 2255.20 06-OCT-07:10 0.306046E+10 2160.55 02-OCT-07:10
November 0.158547E+10 2587.92 06-NOV-16:19 0.299314E+10 2160.55 01-NOV-07:10
December 0.164026E+10 2587.92 01-DEC-16:10 0.300922E+10 2160.55 01-DEC-08:09
             
Annual Sum or Average 0.174001E+11     0.363654E+11    
Minimum of Months 0.127888E+10 1350.81   0.277008E+10 2160.55  
Maximum of Months 0.166102E+10 2587.92   0.318369E+10 2160.55  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.105442E+10 1667.75 02-JAN-16:19 0.197184E+10 1392.34 02-JAN-08:09
February 0.888210E+09 1667.75 01-FEB-16:49 0.178515E+10 1392.34 01-FEB-08:09
March 0.991628E+09 1453.34 02-MAR-16:00 0.205169E+10 1392.34 01-MAR-08:09
April 0.849912E+09 870.51 05-APR-15:00 0.190407E+10 1392.34 03-APR-07:10
May 0.897039E+09 870.51 08-MAY-07:10 0.201177E+10 1392.34 01-MAY-07:10
June 0.878849E+09 793.52 01-JUN-07:10 0.197572E+10 1392.34 01-JUN-07:10
July 0.829792E+09 793.52 03-JUL-07:10 0.193969E+10 1392.34 03-JUL-07:10
August 0.935021E+09 870.51 16-AUG-07:10 0.205169E+10 1392.34 01-AUG-07:10
September 0.865370E+09 947.51 22-SEP-15:00 0.190321E+10 1392.34 01-SEP-07:10
October 0.934135E+09 1453.34 31-OCT-15:50 0.197228E+10 1392.34 02-OCT-07:10
November 0.101476E+10 1667.75 06-NOV-16:19 0.192889E+10 1392.34 01-NOV-07:10
December 0.103220E+10 1667.75 01-DEC-16:10 0.193926E+10 1392.34 01-DEC-08:09
             
Annual Sum or Average 0.111713E+11     0.234352E+11    
Minimum of Months 0.829792E+09 793.52   0.178515E+10 1392.34  
Maximum of Months 0.105442E+10 1667.75   0.205169E+10 1392.34  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.159302E+10 2587.98 02-JAN-16:30 0.305983E+10 2160.58 02-JAN-08:09
February 0.135135E+10 2587.98 01-FEB-16:00 0.277013E+10 2160.58 01-FEB-08:09
March 0.152657E+10 1803.04 02-MAR-16:00 0.318374E+10 2160.58 01-MAR-08:09
April 0.131824E+10 1350.84 14-APR-07:10 0.295467E+10 2160.58 03-APR-07:10
May 0.139067E+10 1350.84 04-MAY-07:10 0.312179E+10 2160.58 01-MAY-07:10
June 0.136518E+10 1350.84 16-JUN-07:10 0.306585E+10 2160.58 01-JUN-07:10
July 0.128851E+10 1350.84 24-JUL-07:10 0.300994E+10 2160.58 03-JUL-07:10
August 0.145046E+10 1350.84 16-AUG-07:10 0.318374E+10 2160.58 01-AUG-07:10
September 0.133902E+10 1470.31 22-SEP-07:10 0.295333E+10 2160.58 01-SEP-07:10
October 0.143488E+10 2255.25 31-OCT-15:00 0.306051E+10 2160.58 02-OCT-07:10
November 0.154184E+10 2587.98 06-NOV-16:40 0.299318E+10 2160.58 01-NOV-07:10
December 0.155295E+10 2587.98 01-DEC-16:30 0.300927E+10 2160.58 01-DEC-08:09
             
Annual Sum or Average 0.171527E+11     0.363660E+11    
Minimum of Months 0.128851E+10 1350.84   0.277013E+10 2160.58  
Maximum of Months 0.159302E+10 2587.98   0.318374E+10 2160.58  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.103928E+10 1667.75 02-JAN-16:30 0.197183E+10 1392.33 02-JAN-08:09
February 0.875804E+09 1667.75 15-FEB-16:00 0.178514E+10 1392.33 01-FEB-08:09
March 0.982928E+09 1161.92 06-MAR-08:09 0.205168E+10 1392.33 01-MAR-08:09
April 0.848223E+09 947.51 14-APR-07:10 0.190406E+10 1392.33 03-APR-07:10
May 0.890059E+09 947.51 08-MAY-07:10 0.201175E+10 1392.33 01-MAY-07:10
June 0.873321E+09 870.51 16-JUN-07:10 0.197570E+10 1392.33 01-JUN-07:10
July 0.825783E+09 870.51 05-JUL-07:10 0.193968E+10 1392.33 03-JUL-07:10
August 0.930341E+09 947.51 16-AUG-07:10 0.205168E+10 1392.33 01-AUG-07:10
September 0.863542E+09 1161.92 26-SEP-07:10 0.190319E+10 1392.33 01-SEP-07:10
October 0.927841E+09 1453.34 06-OCT-07:10 0.197226E+10 1392.33 02-OCT-07:10
November 0.998952E+09 1667.75 06-NOV-16:40 0.192888E+10 1392.33 01-NOV-07:10
December 0.101984E+10 1667.75 01-DEC-16:30 0.193924E+10 1392.33 01-DEC-08:09
             
Annual Sum or Average 0.110759E+11     0.234351E+11    
Minimum of Months 0.825783E+09 870.51   0.178514E+10 1392.33  
Maximum of Months 0.103928E+10 1667.75   0.205168E+10 1392.33  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.166091E+10 2587.92 02-JAN-16:19 0.305979E+10 2160.55 02-JAN-08:09
February 0.139051E+10 2587.92 01-FEB-16:49 0.277008E+10 2160.55 01-FEB-08:09
March 0.154397E+10 1803.00 02-MAR-16:30 0.318369E+10 2160.55 01-MAR-08:09
April 0.131648E+10 1350.81 14-APR-07:10 0.295462E+10 2160.55 03-APR-07:10
May 0.138328E+10 1350.81 04-MAY-07:10 0.312174E+10 2160.55 01-MAY-07:10
June 0.135382E+10 1350.81 16-JUN-07:10 0.306580E+10 2160.55 01-JUN-07:10
July 0.127885E+10 1350.81 24-JUL-07:10 0.300989E+10 2160.55 03-JUL-07:10
August 0.144513E+10 1350.81 16-AUG-07:10 0.318369E+10 2160.55 01-AUG-07:10
September 0.134358E+10 1803.00 27-SEP-07:10 0.295328E+10 2160.55 01-SEP-07:10
October 0.145696E+10 2255.20 06-OCT-07:10 0.306046E+10 2160.55 02-OCT-07:10
November 0.158531E+10 2587.92 06-NOV-16:19 0.299314E+10 2160.55 01-NOV-07:10
December 0.164008E+10 2587.92 01-DEC-16:10 0.300922E+10 2160.55 01-DEC-08:09
             
Annual Sum or Average 0.173989E+11     0.363654E+11    
Minimum of Months 0.127885E+10 1350.81   0.277008E+10 2160.55  
Maximum of Months 0.166091E+10 2587.92   0.318369E+10 2160.55  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.105424E+10 1667.75 02-JAN-16:19 0.197184E+10 1392.34 02-JAN-08:09
February 0.888210E+09 1667.75 01-FEB-16:49 0.178515E+10 1392.34 01-FEB-08:09
March 0.991623E+09 1453.34 02-MAR-16:00 0.205169E+10 1392.34 01-MAR-08:09
April 0.849912E+09 870.51 05-APR-15:00 0.190407E+10 1392.34 03-APR-07:10
May 0.897034E+09 870.51 08-MAY-07:10 0.201177E+10 1392.34 01-MAY-07:10
June 0.878799E+09 793.52 01-JUN-07:10 0.197572E+10 1392.34 01-JUN-07:10
July 0.829746E+09 793.52 03-JUL-07:10 0.193969E+10 1392.34 03-JUL-07:10
August 0.934960E+09 870.51 16-AUG-07:10 0.205169E+10 1392.34 01-AUG-07:10
September 0.865213E+09 947.51 22-SEP-15:00 0.190321E+10 1392.34 01-SEP-07:10
October 0.934132E+09 1453.34 31-OCT-15:50 0.197228E+10 1392.34 02-OCT-07:10
November 0.101458E+10 1667.75 06-NOV-16:19 0.192889E+10 1392.34 01-NOV-07:10
December 0.103219E+10 1667.75 01-DEC-16:10 0.193926E+10 1392.34 01-DEC-08:09
             
Annual Sum or Average 0.111706E+11     0.234352E+11    
Minimum of Months 0.829746E+09 793.52   0.178515E+10 1392.34  
Maximum of Months 0.105424E+10 1667.75   0.205169E+10 1392.34  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.159265E+10 2587.98 02-JAN-16:30 0.305983E+10 2160.58 02-JAN-08:09
February 0.135127E+10 2587.98 01-FEB-16:00 0.277013E+10 2160.58 01-FEB-08:09
March 0.152655E+10 1803.04 02-MAR-16:00 0.318374E+10 2160.58 01-MAR-08:09
April 0.131824E+10 1350.84 14-APR-07:10 0.295467E+10 2160.58 03-APR-07:10
May 0.139062E+10 1350.84 04-MAY-07:10 0.312179E+10 2160.58 01-MAY-07:10
June 0.136502E+10 1350.84 16-JUN-07:10 0.306585E+10 2160.58 01-JUN-07:10
July 0.128847E+10 1350.84 24-JUL-07:10 0.300994E+10 2160.58 03-JUL-07:10
August 0.145044E+10 1350.84 16-AUG-07:10 0.318374E+10 2160.58 01-AUG-07:10
September 0.133899E+10 1470.31 22-SEP-07:10 0.295333E+10 2160.58 01-SEP-07:10
October 0.143488E+10 2255.25 31-OCT-15:00 0.306051E+10 2160.58 02-OCT-07:10
November 0.154169E+10 2587.98 06-NOV-16:40 0.299318E+10 2160.58 01-NOV-07:10
December 0.155266E+10 2587.98 01-DEC-16:30 0.300927E+10 2160.58 01-DEC-08:09
             
Annual Sum or Average 0.171515E+11     0.363660E+11    
Minimum of Months 0.128847E+10 1350.84   0.277013E+10 2160.58  
Maximum of Months 0.159265E+10 2587.98   0.318374E+10 2160.58  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.103923E+10 1667.75 02-JAN-16:30 0.197183E+10 1392.33 02-JAN-08:09
February 0.875715E+09 1667.75 15-FEB-16:00 0.178514E+10 1392.33 01-FEB-08:09
March 0.982823E+09 1161.92 06-MAR-08:09 0.205168E+10 1392.33 01-MAR-08:09
April 0.848218E+09 947.51 14-APR-07:10 0.190406E+10 1392.33 03-APR-07:10
May 0.890037E+09 947.51 08-MAY-07:10 0.201175E+10 1392.33 01-MAY-07:10
June 0.873308E+09 870.51 16-JUN-07:10 0.197570E+10 1392.33 01-JUN-07:10
July 0.825677E+09 870.51 05-JUL-07:10 0.193968E+10 1392.33 03-JUL-07:10
August 0.930333E+09 947.51 16-AUG-07:10 0.205168E+10 1392.33 01-AUG-07:10
September 0.863542E+09 1161.92 26-SEP-07:10 0.190319E+10 1392.33 01-SEP-07:10
October 0.927841E+09 1453.34 06-OCT-07:10 0.197226E+10 1392.33 02-OCT-07:10
November 0.998907E+09 1667.75 06-NOV-16:40 0.192888E+10 1392.33 01-NOV-07:10
December 0.101975E+10 1667.75 01-DEC-16:30 0.193924E+10 1392.33 01-DEC-08:09
             
Annual Sum or Average 0.110754E+11     0.234351E+11    
Minimum of Months 0.825677E+09 870.51   0.178514E+10 1392.33  
Maximum of Months 0.103923E+10 1667.75   0.205168E+10 1392.33  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.553024E+09 578.72 02-JAN-08:09 0.521915E+10 1948.61 01-JAN-00:10
February 0.501634E+09 578.72 01-FEB-08:09 0.942813E+10 3897.21 01-FEB-00:10
March 0.596080E+09 578.72 01-MAR-08:09 0.156645E+11 7794.42 31-MAR-23:10
April 0.532421E+09 578.72 03-APR-07:10 0.201821E+11 7794.42 01-APR-00:10
May 0.574552E+09 578.72 01-MAY-07:10 0.522616E+10 3897.21 31-MAY-23:10
June 0.571774E+09 578.72 01-JUN-07:10 0.101086E+11 5845.82 30-JUN-23:10
July 0.535199E+09 578.72 03-JUL-07:10 0.156645E+11 7794.42 31-JUL-23:10
August 0.596080E+09 578.72 01-AUG-07:10 0.208555E+11 7794.42 01-AUG-00:10
September 0.532421E+09 578.72 01-SEP-07:10 0.505780E+10 3897.21 30-SEP-23:10
October 0.553024E+09 578.72 02-OCT-07:10 0.104453E+11 5845.82 31-OCT-23:10
November 0.546542E+09 578.72 01-NOV-07:10 0.151524E+11 5845.82 01-NOV-00:10
December 0.535199E+09 578.72 01-DEC-08:09 0.208766E+11 7794.42 01-DEC-00:10
             
Annual Sum or Average 0.662795E+10     0.153881E+12    
Minimum of Months 0.501634E+09 578.72   0.505780E+10 1948.61  
Maximum of Months 0.596080E+09 578.72   0.208766E+11 7794.42  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: DATACENTER_MID_ZN_6

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.553024E+09 578.72 02-JAN-08:09 0.521915E+10 1948.61 01-JAN-00:10
February 0.501634E+09 578.72 01-FEB-08:09 0.942813E+10 3897.21 01-FEB-00:10
March 0.596080E+09 578.72 01-MAR-08:09 0.156645E+11 7794.42 31-MAR-23:10
April 0.532421E+09 578.72 03-APR-07:10 0.201821E+11 7794.42 01-APR-00:10
May 0.574552E+09 578.72 01-MAY-07:10 0.522616E+10 3897.21 31-MAY-23:10
June 0.571774E+09 578.72 01-JUN-07:10 0.101086E+11 5845.82 30-JUN-23:10
July 0.535199E+09 578.72 03-JUL-07:10 0.156645E+11 7794.42 31-JUL-23:10
August 0.596080E+09 578.72 01-AUG-07:10 0.208555E+11 7794.42 01-AUG-00:10
September 0.532421E+09 578.72 01-SEP-07:10 0.505780E+10 3897.21 30-SEP-23:10
October 0.553024E+09 578.72 02-OCT-07:10 0.104453E+11 5845.82 31-OCT-23:10
November 0.546542E+09 578.72 01-NOV-07:10 0.151524E+11 5845.82 01-NOV-00:10
December 0.535199E+09 578.72 01-DEC-08:09 0.208766E+11 7794.42 01-DEC-00:10
             
Annual Sum or Average 0.662795E+10     0.153881E+12    
Minimum of Months 0.501634E+09 578.72   0.505780E+10 1948.61  
Maximum of Months 0.596080E+09 578.72   0.208766E+11 7794.42  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.553024E+09 578.72 02-JAN-08:09 0.521915E+10 1948.61 01-JAN-00:10
February 0.501634E+09 578.72 01-FEB-08:09 0.942813E+10 3897.21 01-FEB-00:10
March 0.596080E+09 578.72 01-MAR-08:09 0.156645E+11 7794.42 31-MAR-23:10
April 0.532421E+09 578.72 03-APR-07:10 0.201821E+11 7794.42 01-APR-00:10
May 0.574552E+09 578.72 01-MAY-07:10 0.522616E+10 3897.21 31-MAY-23:10
June 0.571774E+09 578.72 01-JUN-07:10 0.101086E+11 5845.82 30-JUN-23:10
July 0.535199E+09 578.72 03-JUL-07:10 0.156645E+11 7794.42 31-JUL-23:10
August 0.596080E+09 578.72 01-AUG-07:10 0.208555E+11 7794.42 01-AUG-00:10
September 0.532421E+09 578.72 01-SEP-07:10 0.505780E+10 3897.21 30-SEP-23:10
October 0.553024E+09 578.72 02-OCT-07:10 0.104453E+11 5845.82 31-OCT-23:10
November 0.546542E+09 578.72 01-NOV-07:10 0.151524E+11 5845.82 01-NOV-00:10
December 0.535199E+09 578.72 01-DEC-08:09 0.208766E+11 7794.42 01-DEC-00:10
             
Annual Sum or Average 0.662795E+10     0.153881E+12    
Minimum of Months 0.501634E+09 578.72   0.505780E+10 1948.61  
Maximum of Months 0.596080E+09 578.72   0.208766E+11 7794.42  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.618367E+10 6471.01 02-JAN-08:09 0.254202E+12 94908.13 01-JAN-00:10
February 0.560905E+10 6471.01 01-FEB-08:09 0.459203E+12 189816.26 01-FEB-00:10
March 0.666512E+10 6471.01 01-MAR-08:09 0.762947E+12 379632.52 31-MAR-23:10
April 0.595330E+10 6471.01 03-APR-07:10 0.982982E+12 379632.52 01-APR-00:10
May 0.642439E+10 6471.01 01-MAY-07:10 0.254544E+12 189816.26 31-MAY-23:10
June 0.639333E+10 6471.01 01-JUN-07:10 0.492345E+12 284724.39 30-JUN-23:10
July 0.598436E+10 6471.01 03-JUL-07:10 0.762947E+12 379632.52 31-JUL-23:10
August 0.666512E+10 6471.01 01-AUG-07:10 0.101578E+13 379632.52 01-AUG-00:10
September 0.595330E+10 6471.01 01-SEP-07:10 0.246344E+12 189816.26 30-SEP-23:10
October 0.618367E+10 6471.01 02-OCT-07:10 0.508746E+12 284724.39 31-OCT-23:10
November 0.611120E+10 6471.01 01-NOV-07:10 0.738006E+12 284724.39 01-NOV-00:10
December 0.598436E+10 6471.01 01-DEC-08:09 0.101681E+13 379632.52 01-DEC-00:10
             
Annual Sum or Average 0.741109E+11     0.749486E+13    
Minimum of Months 0.560905E+10 6471.01   0.246344E+12 94908.13  
Maximum of Months 0.666512E+10 6471.01   0.101681E+13 379632.52  



Table of Contents

Report: SpaceGainsMonthly

For: BASEMENT

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.133902E+11 0.219312E+11 0.360447E+11 0.00 0.00 0.00 0.00 0.00 0.00
February 0.121482E+11 0.198933E+11 0.325565E+11 0.00 0.00 0.00 0.00 0.00 0.00
March 0.145160E+11 0.236388E+11 0.360447E+11 0.00 0.00 0.00 0.00 0.00 0.00
April 0.128805E+11 0.211142E+11 0.348820E+11 0.00 0.00 0.00 0.00 0.00 0.00
May 0.139531E+11 0.227850E+11 0.360447E+11 0.00 0.00 0.00 0.00 0.00 0.00
June 0.139143E+11 0.226748E+11 0.348820E+11 0.00 0.00 0.00 0.00 0.00 0.00
July 0.129193E+11 0.212244E+11 0.360447E+11 0.00 0.00 0.00 0.00 0.00 0.00
August 0.145160E+11 0.236388E+11 0.360447E+11 0.00 0.00 0.00 0.00 0.00 0.00
September 0.128805E+11 0.211142E+11 0.348820E+11 0.00 0.00 0.00 0.00 0.00 0.00
October 0.133902E+11 0.219312E+11 0.360447E+11 0.00 0.00 0.00 0.00 0.00 0.00
November 0.132595E+11 0.216742E+11 0.348820E+11 0.00 0.00 0.00 0.00 0.00 0.00
December 0.129193E+11 0.212244E+11 0.360447E+11 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.160687E+12 0.262844E+12 0.424397E+12 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.121482E+11 0.198933E+11 0.325565E+11 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.145160E+11 0.236388E+11 0.360447E+11 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: CORE_BOTTOM

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.120254E+11 0.196958E+11 0.243681E+11 0.00 0.00 0.00 0.00 0.00 0.00
February 0.109099E+11 0.178655E+11 0.220609E+11 0.00 0.00 0.00 0.00 0.00 0.00
March 0.130364E+11 0.212293E+11 0.253549E+11 0.00 0.00 0.00 0.00 0.00 0.00
April 0.115676E+11 0.189620E+11 0.235306E+11 0.00 0.00 0.00 0.00 0.00 0.00
May 0.125309E+11 0.204625E+11 0.248615E+11 0.00 0.00 0.00 0.00 0.00 0.00
June 0.124961E+11 0.203636E+11 0.244160E+11 0.00 0.00 0.00 0.00 0.00 0.00
July 0.116025E+11 0.190610E+11 0.239708E+11 0.00 0.00 0.00 0.00 0.00 0.00
August 0.130364E+11 0.212293E+11 0.253549E+11 0.00 0.00 0.00 0.00 0.00 0.00
September 0.115676E+11 0.189620E+11 0.235199E+11 0.00 0.00 0.00 0.00 0.00 0.00
October 0.120254E+11 0.196958E+11 0.243735E+11 0.00 0.00 0.00 0.00 0.00 0.00
November 0.119080E+11 0.194649E+11 0.238373E+11 0.00 0.00 0.00 0.00 0.00 0.00
December 0.116025E+11 0.190610E+11 0.239654E+11 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.144308E+12 0.236053E+12 0.289614E+12 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.109099E+11 0.178655E+11 0.220609E+11 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.130364E+11 0.212293E+11 0.253549E+11 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: CORE_MID

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.120254E+11 0.196958E+11 0.243680E+11 0.00 0.00 0.00 0.00 0.00 0.00
February 0.109099E+11 0.178655E+11 0.220609E+11 0.00 0.00 0.00 0.00 0.00 0.00
March 0.130364E+11 0.212293E+11 0.253548E+11 0.00 0.00 0.00 0.00 0.00 0.00
April 0.115676E+11 0.189620E+11 0.235305E+11 0.00 0.00 0.00 0.00 0.00 0.00
May 0.125309E+11 0.204625E+11 0.248614E+11 0.00 0.00 0.00 0.00 0.00 0.00
June 0.124961E+11 0.203636E+11 0.244159E+11 0.00 0.00 0.00 0.00 0.00 0.00
July 0.116025E+11 0.190610E+11 0.239707E+11 0.00 0.00 0.00 0.00 0.00 0.00
August 0.130364E+11 0.212293E+11 0.253548E+11 0.00 0.00 0.00 0.00 0.00 0.00
September 0.115676E+11 0.189620E+11 0.235198E+11 0.00 0.00 0.00 0.00 0.00 0.00
October 0.120254E+11 0.196958E+11 0.243734E+11 0.00 0.00 0.00 0.00 0.00 0.00
November 0.119080E+11 0.194649E+11 0.238372E+11 0.00 0.00 0.00 0.00 0.00 0.00
December 0.116025E+11 0.190610E+11 0.239653E+11 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.144308E+12 0.236053E+12 0.289613E+12 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.109099E+11 0.178655E+11 0.220609E+11 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.130364E+11 0.212293E+11 0.253548E+11 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: CORE_TOP

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.120254E+11 0.196958E+11 0.243680E+11 0.00 0.00 0.00 0.00 0.00 0.00
February 0.109099E+11 0.178655E+11 0.220609E+11 0.00 0.00 0.00 0.00 0.00 0.00
March 0.130364E+11 0.212293E+11 0.253548E+11 0.00 0.00 0.00 0.00 0.00 0.00
April 0.115676E+11 0.189620E+11 0.235305E+11 0.00 0.00 0.00 0.00 0.00 0.00
May 0.125309E+11 0.204625E+11 0.248614E+11 0.00 0.00 0.00 0.00 0.00 0.00
June 0.124961E+11 0.203636E+11 0.244159E+11 0.00 0.00 0.00 0.00 0.00 0.00
July 0.116025E+11 0.190610E+11 0.239707E+11 0.00 0.00 0.00 0.00 0.00 0.00
August 0.130364E+11 0.212293E+11 0.253548E+11 0.00 0.00 0.00 0.00 0.00 0.00
September 0.115676E+11 0.189620E+11 0.235198E+11 0.00 0.00 0.00 0.00 0.00 0.00
October 0.120254E+11 0.196958E+11 0.243734E+11 0.00 0.00 0.00 0.00 0.00 0.00
November 0.119080E+11 0.194649E+11 0.238372E+11 0.00 0.00 0.00 0.00 0.00 0.00
December 0.116025E+11 0.190610E+11 0.239653E+11 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.144308E+12 0.236053E+12 0.289613E+12 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.109099E+11 0.178655E+11 0.220609E+11 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.130364E+11 0.212293E+11 0.253548E+11 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.150991E+10 0.166708E+10 0.305979E+10 0.00 0.00 0.00 0.00 0.00 0.146380E+10
February 0.136985E+10 0.139589E+10 0.277008E+10 0.00 0.00 0.00 0.00 0.00 0.128430E+10
March 0.163685E+10 0.154660E+10 0.318369E+10 0.00 0.00 0.00 0.00 0.00 0.107703E+10
April 0.145243E+10 0.131787E+10 0.295462E+10 0.00 0.00 0.00 0.00 503686.13 0.723464E+09
May 0.157338E+10 0.138455E+10 0.312174E+10 0.00 0.00 0.00 0.00 2151602.94 0.409731E+09
June 0.156900E+10 0.135468E+10 0.306580E+10 0.00 0.00 0.00 0.00 16314407.72 0.206750E+09
July 0.145680E+10 0.128005E+10 0.300989E+10 0.00 0.00 0.00 0.00 39965860.52 60614089.78
August 0.163685E+10 0.144587E+10 0.318369E+10 0.00 0.00 0.00 0.00 50209992.79 77866150.82
September 0.145243E+10 0.134568E+10 0.295328E+10 0.00 0.00 0.00 0.00 5810103.86 0.224264E+09
October 0.150991E+10 0.145981E+10 0.306046E+10 0.00 0.00 0.00 0.00 95390.07 0.565210E+09
November 0.149516E+10 0.158993E+10 0.299314E+10 0.00 0.00 0.00 0.00 0.00 0.108224E+10
December 0.145680E+10 0.164721E+10 0.300922E+10 0.00 0.00 0.00 0.00 0.00 0.129082E+10
                   
Annual Sum or Average 0.181194E+11 0.174352E+11 0.363654E+11 0.00 0.00 0.00 0.00 0.115051E+09 0.846610E+10
Minimum of Months 0.136985E+10 0.128005E+10 0.277008E+10 0.00 0.00 0.00 0.00 0.00 60614089.78
Maximum of Months 0.163685E+10 0.166708E+10 0.318369E+10 0.00 0.00 0.00 0.00 50209992.79 0.146380E+10



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.973041E+09 0.105752E+10 0.197184E+10 0.00 0.00 0.00 0.00 0.00 0.970945E+09
February 0.882782E+09 0.890082E+09 0.178515E+10 0.00 0.00 0.00 0.00 0.00 0.860167E+09
March 0.105485E+10 0.993363E+09 0.205169E+10 0.00 0.00 0.00 0.00 0.00 0.705256E+09
April 0.936002E+09 0.850718E+09 0.190407E+10 0.00 0.00 0.00 0.00 335988.48 0.471095E+09
May 0.101394E+10 0.897753E+09 0.201177E+10 0.00 0.00 0.00 0.00 1327457.08 0.270865E+09
June 0.101113E+10 0.879630E+09 0.197572E+10 0.00 0.00 0.00 0.00 11780671.84 0.129146E+09
July 0.938820E+09 0.830291E+09 0.193969E+10 0.00 0.00 0.00 0.00 30987129.88 29530152.80
August 0.105485E+10 0.935442E+09 0.205169E+10 0.00 0.00 0.00 0.00 37942176.88 41298595.09
September 0.936002E+09 0.866147E+09 0.190321E+10 0.00 0.00 0.00 0.00 3971661.95 0.148746E+09
October 0.973041E+09 0.935286E+09 0.197228E+10 0.00 0.00 0.00 0.00 63581.21 0.373472E+09
November 0.963541E+09 0.101639E+10 0.192889E+10 0.00 0.00 0.00 0.00 0.00 0.708280E+09
December 0.938820E+09 0.103495E+10 0.193926E+10 0.00 0.00 0.00 0.00 0.00 0.840935E+09
                   
Annual Sum or Average 0.116768E+11 0.111876E+11 0.234352E+11 0.00 0.00 0.00 0.00 86408667.31 0.554974E+10
Minimum of Months 0.882782E+09 0.830291E+09 0.178515E+10 0.00 0.00 0.00 0.00 0.00 29530152.80
Maximum of Months 0.105485E+10 0.105752E+10 0.205169E+10 0.00 0.00 0.00 0.00 37942176.88 0.970945E+09



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.150994E+10 0.159588E+10 0.305983E+10 0.00 0.00 0.00 0.00 0.00 0.145928E+10
February 0.136988E+10 0.135323E+10 0.277013E+10 0.00 0.00 0.00 0.00 0.00 0.131751E+10
March 0.163688E+10 0.153012E+10 0.318374E+10 0.00 0.00 0.00 0.00 0.00 0.107767E+10
April 0.145246E+10 0.131948E+10 0.295467E+10 0.00 0.00 0.00 0.00 500160.32 0.718152E+09
May 0.157341E+10 0.139165E+10 0.312179E+10 0.00 0.00 0.00 0.00 1857379.37 0.405145E+09
June 0.156904E+10 0.136612E+10 0.306585E+10 0.00 0.00 0.00 0.00 16295184.49 0.203096E+09
July 0.145684E+10 0.128953E+10 0.300994E+10 0.00 0.00 0.00 0.00 40326105.26 58373547.69
August 0.163688E+10 0.145133E+10 0.318374E+10 0.00 0.00 0.00 0.00 49665669.89 79221971.75
September 0.145246E+10 0.134045E+10 0.295333E+10 0.00 0.00 0.00 0.00 5717930.32 0.236332E+09
October 0.150994E+10 0.143607E+10 0.306051E+10 0.00 0.00 0.00 0.00 56422.46 0.594860E+09
November 0.149520E+10 0.154352E+10 0.299318E+10 0.00 0.00 0.00 0.00 0.00 0.108306E+10
December 0.145684E+10 0.155441E+10 0.300927E+10 0.00 0.00 0.00 0.00 0.00 0.129042E+10
                   
Annual Sum or Average 0.181198E+11 0.171718E+11 0.363660E+11 0.00 0.00 0.00 0.00 0.114419E+09 0.852312E+10
Minimum of Months 0.136988E+10 0.128953E+10 0.277013E+10 0.00 0.00 0.00 0.00 0.00 58373547.69
Maximum of Months 0.163688E+10 0.159588E+10 0.318374E+10 0.00 0.00 0.00 0.00 49665669.89 0.145928E+10



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.973041E+09 0.104145E+10 0.197183E+10 0.00 0.00 0.00 0.00 0.00 0.101682E+10
February 0.882782E+09 0.877688E+09 0.178514E+10 0.00 0.00 0.00 0.00 0.00 0.909250E+09
March 0.105485E+10 0.983977E+09 0.205168E+10 0.00 0.00 0.00 0.00 0.00 0.786020E+09
April 0.936002E+09 0.849086E+09 0.190406E+10 0.00 0.00 0.00 0.00 330720.96 0.544908E+09
May 0.101394E+10 0.890661E+09 0.201175E+10 0.00 0.00 0.00 0.00 1593215.84 0.296134E+09
June 0.101113E+10 0.874073E+09 0.197570E+10 0.00 0.00 0.00 0.00 10562939.65 0.161987E+09
July 0.938820E+09 0.826626E+09 0.193968E+10 0.00 0.00 0.00 0.00 24983800.05 57199120.21
August 0.105485E+10 0.930786E+09 0.205168E+10 0.00 0.00 0.00 0.00 29970474.85 70065416.18
September 0.936002E+09 0.864640E+09 0.190319E+10 0.00 0.00 0.00 0.00 3891384.94 0.169151E+09
October 0.973041E+09 0.928958E+09 0.197226E+10 0.00 0.00 0.00 0.00 63611.42 0.419107E+09
November 0.963541E+09 0.100055E+10 0.192888E+10 0.00 0.00 0.00 0.00 0.00 0.786645E+09
December 0.938820E+09 0.102279E+10 0.193924E+10 0.00 0.00 0.00 0.00 0.00 0.949857E+09
                   
Annual Sum or Average 0.116768E+11 0.110913E+11 0.234351E+11 0.00 0.00 0.00 0.00 71396147.72 0.616714E+10
Minimum of Months 0.882782E+09 0.826626E+09 0.178514E+10 0.00 0.00 0.00 0.00 0.00 57199120.21
Maximum of Months 0.105485E+10 0.104145E+10 0.205168E+10 0.00 0.00 0.00 0.00 29970474.85 0.101682E+10



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.150991E+10 0.166102E+10 0.305979E+10 0.00 0.00 0.00 0.00 0.00 0.300014E+10
February 0.136985E+10 0.139087E+10 0.277008E+10 0.00 0.00 0.00 0.00 0.00 0.267262E+10
March 0.163685E+10 0.154399E+10 0.318369E+10 0.00 0.00 0.00 0.00 0.00 0.217702E+10
April 0.145243E+10 0.131652E+10 0.295462E+10 0.00 0.00 0.00 0.00 1102574.16 0.144982E+10
May 0.157338E+10 0.138331E+10 0.312174E+10 0.00 0.00 0.00 0.00 5355525.56 0.880805E+09
June 0.156900E+10 0.135382E+10 0.306580E+10 0.00 0.00 0.00 0.00 36991764.77 0.463308E+09
July 0.145680E+10 0.127888E+10 0.300989E+10 0.00 0.00 0.00 0.00 86966601.71 0.165674E+09
August 0.163685E+10 0.144515E+10 0.318369E+10 0.00 0.00 0.00 0.00 0.107416E+09 0.208557E+09
September 0.145243E+10 0.134367E+10 0.295328E+10 0.00 0.00 0.00 0.00 13047396.89 0.472974E+09
October 0.150991E+10 0.145717E+10 0.306046E+10 0.00 0.00 0.00 0.00 173072.85 0.114736E+10
November 0.149516E+10 0.158547E+10 0.299314E+10 0.00 0.00 0.00 0.00 0.00 0.211370E+10
December 0.145680E+10 0.164026E+10 0.300922E+10 0.00 0.00 0.00 0.00 0.00 0.254301E+10
                   
Annual Sum or Average 0.181194E+11 0.174001E+11 0.363654E+11 0.00 0.00 0.00 0.00 0.251053E+09 0.172950E+11
Minimum of Months 0.136985E+10 0.127888E+10 0.277008E+10 0.00 0.00 0.00 0.00 0.00 0.165674E+09
Maximum of Months 0.163685E+10 0.166102E+10 0.318369E+10 0.00 0.00 0.00 0.00 0.107416E+09 0.300014E+10



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.715730E+09 0.105442E+10 0.197184E+10 0.00 0.00 0.00 0.00 0.00 0.200795E+10
February 0.649041E+09 0.888210E+09 0.178515E+10 0.00 0.00 0.00 0.00 0.00 0.181179E+10
March 0.773965E+09 0.991628E+09 0.205169E+10 0.00 0.00 0.00 0.00 0.00 0.147923E+10
April 0.688021E+09 0.849912E+09 0.190407E+10 0.00 0.00 0.00 0.00 737589.10 0.100326E+10
May 0.744847E+09 0.897039E+09 0.201177E+10 0.00 0.00 0.00 0.00 2804129.02 0.592967E+09
June 0.742030E+09 0.878849E+09 0.197572E+10 0.00 0.00 0.00 0.00 25443772.67 0.307288E+09
July 0.690839E+09 0.829792E+09 0.193969E+10 0.00 0.00 0.00 0.00 60422533.68 0.108053E+09
August 0.773965E+09 0.935021E+09 0.205169E+10 0.00 0.00 0.00 0.00 71496495.94 0.143598E+09
September 0.688021E+09 0.865370E+09 0.190321E+10 0.00 0.00 0.00 0.00 8718966.20 0.327964E+09
October 0.715730E+09 0.934135E+09 0.197228E+10 0.00 0.00 0.00 0.00 115270.55 0.790984E+09
November 0.708685E+09 0.101476E+10 0.192889E+10 0.00 0.00 0.00 0.00 0.00 0.143650E+10
December 0.690839E+09 0.103220E+10 0.193926E+10 0.00 0.00 0.00 0.00 0.00 0.171303E+10
                   
Annual Sum or Average 0.858171E+10 0.111713E+11 0.234352E+11 0.00 0.00 0.00 0.00 0.169739E+09 0.117226E+11
Minimum of Months 0.649041E+09 0.829792E+09 0.178515E+10 0.00 0.00 0.00 0.00 0.00 0.108053E+09
Maximum of Months 0.773965E+09 0.105442E+10 0.205169E+10 0.00 0.00 0.00 0.00 71496495.94 0.200795E+10



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.150994E+10 0.159302E+10 0.305983E+10 0.00 0.00 0.00 0.00 0.00 0.313493E+10
February 0.136988E+10 0.135135E+10 0.277013E+10 0.00 0.00 0.00 0.00 0.00 0.288090E+10
March 0.163688E+10 0.152657E+10 0.318374E+10 0.00 0.00 0.00 0.00 0.00 0.233150E+10
April 0.145246E+10 0.131824E+10 0.295467E+10 0.00 0.00 0.00 0.00 1075683.38 0.154402E+10
May 0.157341E+10 0.139067E+10 0.312179E+10 0.00 0.00 0.00 0.00 4145921.69 0.898037E+09
June 0.156904E+10 0.136518E+10 0.306585E+10 0.00 0.00 0.00 0.00 36363312.81 0.465368E+09
July 0.145684E+10 0.128851E+10 0.300994E+10 0.00 0.00 0.00 0.00 85823256.50 0.171379E+09
August 0.163688E+10 0.145046E+10 0.318374E+10 0.00 0.00 0.00 0.00 0.102867E+09 0.228574E+09
September 0.145246E+10 0.133902E+10 0.295333E+10 0.00 0.00 0.00 0.00 12513283.85 0.534500E+09
October 0.150994E+10 0.143488E+10 0.306051E+10 0.00 0.00 0.00 0.00 79961.87 0.132484E+10
November 0.149520E+10 0.154184E+10 0.299318E+10 0.00 0.00 0.00 0.00 0.00 0.230415E+10
December 0.145684E+10 0.155295E+10 0.300927E+10 0.00 0.00 0.00 0.00 0.00 0.274300E+10
                   
Annual Sum or Average 0.181198E+11 0.171527E+11 0.363660E+11 0.00 0.00 0.00 0.00 0.242868E+09 0.185612E+11
Minimum of Months 0.136988E+10 0.128851E+10 0.277013E+10 0.00 0.00 0.00 0.00 0.00 0.171379E+09
Maximum of Months 0.163688E+10 0.159302E+10 0.318374E+10 0.00 0.00 0.00 0.00 0.102867E+09 0.313493E+10



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.973041E+09 0.103928E+10 0.197183E+10 0.00 0.00 0.00 0.00 0.00 0.204969E+10
February 0.882782E+09 0.875804E+09 0.178514E+10 0.00 0.00 0.00 0.00 0.00 0.184187E+10
March 0.105485E+10 0.982928E+09 0.205168E+10 0.00 0.00 0.00 0.00 0.00 0.154180E+10
April 0.936002E+09 0.848223E+09 0.190406E+10 0.00 0.00 0.00 0.00 750420.74 0.103922E+10
May 0.101394E+10 0.890059E+09 0.201175E+10 0.00 0.00 0.00 0.00 3996671.32 0.620895E+09
June 0.101113E+10 0.873321E+09 0.197570E+10 0.00 0.00 0.00 0.00 24716985.34 0.343065E+09
July 0.938820E+09 0.825783E+09 0.193968E+10 0.00 0.00 0.00 0.00 58583614.93 0.138732E+09
August 0.105485E+10 0.930341E+09 0.205168E+10 0.00 0.00 0.00 0.00 69238955.96 0.168614E+09
September 0.936002E+09 0.863542E+09 0.190319E+10 0.00 0.00 0.00 0.00 8829956.54 0.343899E+09
October 0.973041E+09 0.927841E+09 0.197226E+10 0.00 0.00 0.00 0.00 116623.00 0.828415E+09
November 0.963541E+09 0.998952E+09 0.192888E+10 0.00 0.00 0.00 0.00 0.00 0.145213E+10
December 0.938820E+09 0.101984E+10 0.193924E+10 0.00 0.00 0.00 0.00 0.00 0.176036E+10
                   
Annual Sum or Average 0.116768E+11 0.110759E+11 0.234351E+11 0.00 0.00 0.00 0.00 0.166233E+09 0.121287E+11
Minimum of Months 0.882782E+09 0.825783E+09 0.178514E+10 0.00 0.00 0.00 0.00 0.00 0.138732E+09
Maximum of Months 0.105485E+10 0.103928E+10 0.205168E+10 0.00 0.00 0.00 0.00 69238955.96 0.204969E+10



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.150991E+10 0.166091E+10 0.305979E+10 0.00 0.00 0.00 0.00 0.00 0.361961E+10
February 0.136985E+10 0.139051E+10 0.277008E+10 0.00 0.00 0.00 0.00 0.00 0.321121E+10
March 0.163685E+10 0.154397E+10 0.318369E+10 0.00 0.00 0.00 0.00 0.00 0.252861E+10
April 0.145243E+10 0.131648E+10 0.295462E+10 0.00 0.00 0.00 0.00 1282600.04 0.166304E+10
May 0.157338E+10 0.138328E+10 0.312174E+10 0.00 0.00 0.00 0.00 6002890.37 0.104203E+10
June 0.156900E+10 0.135382E+10 0.306580E+10 0.00 0.00 0.00 0.00 43482826.10 0.572894E+09
July 0.145680E+10 0.127885E+10 0.300989E+10 0.00 0.00 0.00 0.00 0.101120E+09 0.218247E+09
August 0.163685E+10 0.144513E+10 0.318369E+10 0.00 0.00 0.00 0.00 0.127103E+09 0.261964E+09
September 0.145243E+10 0.134358E+10 0.295328E+10 0.00 0.00 0.00 0.00 15304226.59 0.559948E+09
October 0.150991E+10 0.145696E+10 0.306046E+10 0.00 0.00 0.00 0.00 160868.49 0.129614E+10
November 0.149516E+10 0.158531E+10 0.299314E+10 0.00 0.00 0.00 0.00 0.00 0.239637E+10
December 0.145680E+10 0.164008E+10 0.300922E+10 0.00 0.00 0.00 0.00 0.00 0.296907E+10
                   
Annual Sum or Average 0.181194E+11 0.173989E+11 0.363654E+11 0.00 0.00 0.00 0.00 0.294456E+09 0.203391E+11
Minimum of Months 0.136985E+10 0.127885E+10 0.277008E+10 0.00 0.00 0.00 0.00 0.00 0.218247E+09
Maximum of Months 0.163685E+10 0.166091E+10 0.318369E+10 0.00 0.00 0.00 0.00 0.127103E+09 0.361961E+10



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.973041E+09 0.105424E+10 0.197184E+10 0.00 0.00 0.00 0.00 0.00 0.242323E+10
February 0.882782E+09 0.888210E+09 0.178515E+10 0.00 0.00 0.00 0.00 0.00 0.216937E+10
March 0.105485E+10 0.991623E+09 0.205169E+10 0.00 0.00 0.00 0.00 0.00 0.172378E+10
April 0.936002E+09 0.849912E+09 0.190407E+10 0.00 0.00 0.00 0.00 850453.58 0.116697E+10
May 0.101394E+10 0.897034E+09 0.201177E+10 0.00 0.00 0.00 0.00 3310138.33 0.708235E+09
June 0.101113E+10 0.878799E+09 0.197572E+10 0.00 0.00 0.00 0.00 29677740.22 0.380678E+09
July 0.938820E+09 0.829746E+09 0.193969E+10 0.00 0.00 0.00 0.00 70145994.46 0.141814E+09
August 0.105485E+10 0.934960E+09 0.205169E+10 0.00 0.00 0.00 0.00 84901183.56 0.180728E+09
September 0.936002E+09 0.865213E+09 0.190321E+10 0.00 0.00 0.00 0.00 10280357.27 0.393113E+09
October 0.973041E+09 0.934132E+09 0.197228E+10 0.00 0.00 0.00 0.00 107195.65 0.909592E+09
November 0.963541E+09 0.101458E+10 0.192889E+10 0.00 0.00 0.00 0.00 0.00 0.163282E+10
December 0.938820E+09 0.103219E+10 0.193926E+10 0.00 0.00 0.00 0.00 0.00 0.199768E+10
                   
Annual Sum or Average 0.116768E+11 0.111706E+11 0.234352E+11 0.00 0.00 0.00 0.00 0.199273E+09 0.138280E+11
Minimum of Months 0.882782E+09 0.829746E+09 0.178515E+10 0.00 0.00 0.00 0.00 0.00 0.141814E+09
Maximum of Months 0.105485E+10 0.105424E+10 0.205169E+10 0.00 0.00 0.00 0.00 84901183.56 0.242323E+10



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.150994E+10 0.159265E+10 0.305983E+10 0.00 0.00 0.00 0.00 0.00 0.373976E+10
February 0.136988E+10 0.135127E+10 0.277013E+10 0.00 0.00 0.00 0.00 0.00 0.341171E+10
March 0.163688E+10 0.152655E+10 0.318374E+10 0.00 0.00 0.00 0.00 0.00 0.271177E+10
April 0.145246E+10 0.131824E+10 0.295467E+10 0.00 0.00 0.00 0.00 1267393.97 0.178353E+10
May 0.157341E+10 0.139062E+10 0.312179E+10 0.00 0.00 0.00 0.00 4954934.12 0.106102E+10
June 0.156904E+10 0.136502E+10 0.306585E+10 0.00 0.00 0.00 0.00 43177360.98 0.571340E+09
July 0.145684E+10 0.128847E+10 0.300994E+10 0.00 0.00 0.00 0.00 0.101574E+09 0.221155E+09
August 0.163688E+10 0.145044E+10 0.318374E+10 0.00 0.00 0.00 0.00 0.123368E+09 0.284982E+09
September 0.145246E+10 0.133899E+10 0.295333E+10 0.00 0.00 0.00 0.00 14948735.12 0.636172E+09
October 0.150994E+10 0.143488E+10 0.306051E+10 0.00 0.00 0.00 0.00 71335.54 0.154291E+10
November 0.149520E+10 0.154169E+10 0.299318E+10 0.00 0.00 0.00 0.00 0.00 0.260698E+10
December 0.145684E+10 0.155266E+10 0.300927E+10 0.00 0.00 0.00 0.00 0.00 0.317354E+10
                   
Annual Sum or Average 0.181198E+11 0.171515E+11 0.363660E+11 0.00 0.00 0.00 0.00 0.289363E+09 0.217449E+11
Minimum of Months 0.136988E+10 0.128847E+10 0.277013E+10 0.00 0.00 0.00 0.00 0.00 0.221155E+09
Maximum of Months 0.163688E+10 0.159265E+10 0.318374E+10 0.00 0.00 0.00 0.00 0.123368E+09 0.373976E+10



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.973041E+09 0.103923E+10 0.197183E+10 0.00 0.00 0.00 0.00 0.00 0.246052E+10
February 0.882782E+09 0.875715E+09 0.178514E+10 0.00 0.00 0.00 0.00 0.00 0.221153E+10
March 0.105485E+10 0.982823E+09 0.205168E+10 0.00 0.00 0.00 0.00 0.00 0.181103E+10
April 0.936002E+09 0.848218E+09 0.190406E+10 0.00 0.00 0.00 0.00 886440.61 0.121571E+10
May 0.101394E+10 0.890037E+09 0.201175E+10 0.00 0.00 0.00 0.00 4855521.69 0.739560E+09
June 0.101113E+10 0.873308E+09 0.197570E+10 0.00 0.00 0.00 0.00 29542785.24 0.420975E+09
July 0.938820E+09 0.825677E+09 0.193968E+10 0.00 0.00 0.00 0.00 69483351.29 0.175630E+09
August 0.105485E+10 0.930333E+09 0.205168E+10 0.00 0.00 0.00 0.00 83227038.89 0.209240E+09
September 0.936002E+09 0.863542E+09 0.190319E+10 0.00 0.00 0.00 0.00 10504446.46 0.410112E+09
October 0.973041E+09 0.927841E+09 0.197226E+10 0.00 0.00 0.00 0.00 110196.07 0.960396E+09
November 0.963541E+09 0.998907E+09 0.192888E+10 0.00 0.00 0.00 0.00 0.00 0.166723E+10
December 0.938820E+09 0.101975E+10 0.193924E+10 0.00 0.00 0.00 0.00 0.00 0.205712E+10
                   
Annual Sum or Average 0.116768E+11 0.110754E+11 0.234351E+11 0.00 0.00 0.00 0.00 0.198610E+09 0.143390E+11
Minimum of Months 0.882782E+09 0.825677E+09 0.178514E+10 0.00 0.00 0.00 0.00 0.00 0.175630E+09
Maximum of Months 0.105485E+10 0.103923E+10 0.205168E+10 0.00 0.00 0.00 0.00 83227038.89 0.246052E+10



Table of Contents

Report: SpaceGainsMonthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.174411E+09 0.553024E+09 0.521915E+10 0.00 0.00 0.00 0.00 0.00 0.00
February 0.158233E+09 0.501634E+09 0.942813E+10 0.00 0.00 0.00 0.00 0.00 0.00
March 0.189074E+09 0.596080E+09 0.156645E+11 0.00 0.00 0.00 0.00 0.00 0.00
April 0.167772E+09 0.532421E+09 0.201821E+11 0.00 0.00 0.00 0.00 0.00 0.00
May 0.181743E+09 0.574552E+09 0.522616E+10 0.00 0.00 0.00 0.00 0.00 0.00
June 0.181238E+09 0.571774E+09 0.101086E+11 0.00 0.00 0.00 0.00 0.00 0.00
July 0.168277E+09 0.535199E+09 0.156645E+11 0.00 0.00 0.00 0.00 0.00 0.00
August 0.189074E+09 0.596080E+09 0.208555E+11 0.00 0.00 0.00 0.00 0.00 0.00
September 0.167772E+09 0.532421E+09 0.505780E+10 0.00 0.00 0.00 0.00 0.00 0.00
October 0.174411E+09 0.553024E+09 0.104453E+11 0.00 0.00 0.00 0.00 0.00 0.00
November 0.172708E+09 0.546542E+09 0.151524E+11 0.00 0.00 0.00 0.00 0.00 0.00
December 0.168277E+09 0.535199E+09 0.208766E+11 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.209299E+10 0.662795E+10 0.153881E+12 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.158233E+09 0.501634E+09 0.505780E+10 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.189074E+09 0.596080E+09 0.208766E+11 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: DATACENTER_MID_ZN_6

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.174411E+09 0.553024E+09 0.521915E+10 0.00 0.00 0.00 0.00 0.00 0.00
February 0.158233E+09 0.501634E+09 0.942813E+10 0.00 0.00 0.00 0.00 0.00 0.00
March 0.189074E+09 0.596080E+09 0.156645E+11 0.00 0.00 0.00 0.00 0.00 0.00
April 0.167772E+09 0.532421E+09 0.201821E+11 0.00 0.00 0.00 0.00 0.00 0.00
May 0.181743E+09 0.574552E+09 0.522616E+10 0.00 0.00 0.00 0.00 0.00 0.00
June 0.181238E+09 0.571774E+09 0.101086E+11 0.00 0.00 0.00 0.00 0.00 0.00
July 0.168277E+09 0.535199E+09 0.156645E+11 0.00 0.00 0.00 0.00 0.00 0.00
August 0.189074E+09 0.596080E+09 0.208555E+11 0.00 0.00 0.00 0.00 0.00 0.00
September 0.167772E+09 0.532421E+09 0.505780E+10 0.00 0.00 0.00 0.00 0.00 0.00
October 0.174411E+09 0.553024E+09 0.104453E+11 0.00 0.00 0.00 0.00 0.00 0.00
November 0.172708E+09 0.546542E+09 0.151524E+11 0.00 0.00 0.00 0.00 0.00 0.00
December 0.168277E+09 0.535199E+09 0.208766E+11 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.209299E+10 0.662795E+10 0.153881E+12 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.158233E+09 0.501634E+09 0.505780E+10 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.189074E+09 0.596080E+09 0.208766E+11 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.174411E+09 0.553024E+09 0.521915E+10 0.00 0.00 0.00 0.00 0.00 0.00
February 0.158233E+09 0.501634E+09 0.942813E+10 0.00 0.00 0.00 0.00 0.00 0.00
March 0.189074E+09 0.596080E+09 0.156645E+11 0.00 0.00 0.00 0.00 0.00 0.00
April 0.167772E+09 0.532421E+09 0.201821E+11 0.00 0.00 0.00 0.00 0.00 0.00
May 0.181743E+09 0.574552E+09 0.522616E+10 0.00 0.00 0.00 0.00 0.00 0.00
June 0.181238E+09 0.571774E+09 0.101086E+11 0.00 0.00 0.00 0.00 0.00 0.00
July 0.168277E+09 0.535199E+09 0.156645E+11 0.00 0.00 0.00 0.00 0.00 0.00
August 0.189074E+09 0.596080E+09 0.208555E+11 0.00 0.00 0.00 0.00 0.00 0.00
September 0.167772E+09 0.532421E+09 0.505780E+10 0.00 0.00 0.00 0.00 0.00 0.00
October 0.174411E+09 0.553024E+09 0.104453E+11 0.00 0.00 0.00 0.00 0.00 0.00
November 0.172708E+09 0.546542E+09 0.151524E+11 0.00 0.00 0.00 0.00 0.00 0.00
December 0.168277E+09 0.535199E+09 0.208766E+11 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.209299E+10 0.662795E+10 0.153881E+12 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.158233E+09 0.501634E+09 0.505780E+10 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.189074E+09 0.596080E+09 0.208766E+11 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.377547E+10 0.618367E+10 0.254202E+12 0.00 0.00 0.00 0.00 0.00 0.00
February 0.342526E+10 0.560905E+10 0.459203E+12 0.00 0.00 0.00 0.00 0.00 0.00
March 0.409289E+10 0.666512E+10 0.762947E+12 0.00 0.00 0.00 0.00 0.00 0.00
April 0.363176E+10 0.595330E+10 0.982982E+12 0.00 0.00 0.00 0.00 0.00 0.00
May 0.393418E+10 0.642439E+10 0.254544E+12 0.00 0.00 0.00 0.00 0.00 0.00
June 0.392325E+10 0.639333E+10 0.492345E+12 0.00 0.00 0.00 0.00 0.00 0.00
July 0.364269E+10 0.598436E+10 0.762947E+12 0.00 0.00 0.00 0.00 0.00 0.00
August 0.409289E+10 0.666512E+10 0.101578E+13 0.00 0.00 0.00 0.00 0.00 0.00
September 0.363176E+10 0.595330E+10 0.246344E+12 0.00 0.00 0.00 0.00 0.00 0.00
October 0.377547E+10 0.618367E+10 0.508746E+12 0.00 0.00 0.00 0.00 0.00 0.00
November 0.373861E+10 0.611120E+10 0.738006E+12 0.00 0.00 0.00 0.00 0.00 0.00
December 0.364269E+10 0.598436E+10 0.101681E+13 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.453069E+11 0.741109E+11 0.749486E+13 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.342526E+10 0.560905E+10 0.246344E+12 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.409289E+10 0.666512E+10 0.101681E+13 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: GROUNDFLOOR_PLENUM

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.320749E+10
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.282118E+10
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.232339E+10
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 636063.92 0.155189E+10
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 4198601.89 0.869327E+09
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 27612000.70 0.437891E+09
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 70154733.60 0.133882E+09
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 82598818.32 0.181889E+09
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 7863430.23 0.483637E+09
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 9751.04 0.123331E+10
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.234983E+10
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.283047E+10
                   
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.193073E+09 0.184242E+11
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.133882E+09
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 82598818.32 0.320749E+10



Table of Contents

Report: SpaceGainsMonthly

For: MIDFLOOR_PLENUM

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.514996E+10
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.468204E+10
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.388301E+10
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1279084.05 0.258257E+10
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 9225354.02 0.150014E+10
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 50226166.59 0.765021E+09
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.125622E+09 0.247161E+09
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.143667E+09 0.341820E+09
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 13819806.52 0.832204E+09
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 23182.60 0.210092E+10
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.386487E+10
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.460533E+10
                   
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.343862E+09 0.305550E+11
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.247161E+09
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.143667E+09 0.514996E+10



Table of Contents

Report: SpaceGainsMonthly

For: TOPFLOOR_PLENUM

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.544123E+10
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.490589E+10
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.409563E+10
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 312425.37 0.273434E+10
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 3511219.23 0.168890E+10
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 40051851.74 0.910515E+09
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 99064749.22 0.328524E+09
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.131757E+09 0.403331E+09
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 11570836.16 0.924158E+09
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.219486E+10
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.388494E+10
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.463746E+10
                   
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.286268E+09 0.321498E+11
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.328524E+09
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.131757E+09 0.544123E+10



Table of Contents

Report: PeakSpaceGainsMonthly

For: BASEMENT

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 17832.21 02-JAN-10:09 22950.34 02-JAN-08:09 13457.54 01-JAN-00:10 0.00 0.00 0.00 0.00 0.00 0.00
February 17832.21 01-FEB-10:09 22950.34 01-FEB-08:09 13457.54 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00 0.00
March 17832.21 01-MAR-10:09 22950.34 01-MAR-08:09 13457.54 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00 0.00
April 17832.21 03-APR-09:09 22950.34 03-APR-07:10 13457.54 01-APR-00:10 0.00 0.00 0.00 0.00 0.00 0.00
May 17832.21 01-MAY-09:09 22950.34 01-MAY-07:10 13457.54 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00 0.00
June 17832.21 01-JUN-09:09 22950.34 01-JUN-07:10 13457.54 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00 0.00
July 17832.21 03-JUL-09:09 22950.34 03-JUL-07:10 13457.54 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00 0.00
August 17832.21 01-AUG-09:09 22950.34 01-AUG-07:10 13457.54 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00 0.00
September 17832.21 01-SEP-09:09 22950.34 01-SEP-07:10 13457.54 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00 0.00
October 17832.21 02-OCT-09:09 22950.34 02-OCT-07:10 13457.54 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00 0.00
November 17832.21 01-NOV-09:09 22950.34 01-NOV-07:10 13457.54 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00 0.00
December 17832.21 01-DEC-10:09 22950.34 01-DEC-08:09 13457.54 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average             0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 17832.21   22950.34   13457.54   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 17832.21   22950.34   13457.54   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: CORE_BOTTOM

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 16014.58 02-JAN-10:09 20611.01 02-JAN-08:09 17206.63 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 0.00
February 16014.58 01-FEB-10:09 20611.01 01-FEB-08:09 17206.63 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 0.00
March 16014.58 01-MAR-10:09 20611.01 01-MAR-08:09 17206.63 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 0.00
April 16014.58 03-APR-09:09 20611.01 03-APR-07:10 17206.63 03-APR-07:10 0.00 0.00 0.00 0.00 0.00 0.00
May 16014.58 01-MAY-09:09 20611.01 01-MAY-07:10 17206.63 01-MAY-07:10 0.00 0.00 0.00 0.00 0.00 0.00
June 16014.58 01-JUN-09:09 20611.01 01-JUN-07:10 17206.63 01-JUN-07:10 0.00 0.00 0.00 0.00 0.00 0.00
July 16014.58 03-JUL-09:09 20611.01 03-JUL-07:10 17206.63 03-JUL-07:10 0.00 0.00 0.00 0.00 0.00 0.00
August 16014.58 01-AUG-09:09 20611.01 01-AUG-07:10 17206.63 01-AUG-07:10 0.00 0.00 0.00 0.00 0.00 0.00
September 16014.58 01-SEP-09:09 20611.01 01-SEP-07:10 17206.63 01-SEP-07:10 0.00 0.00 0.00 0.00 0.00 0.00
October 16014.58 02-OCT-09:09 20611.01 02-OCT-07:10 17206.63 02-OCT-07:10 0.00 0.00 0.00 0.00 0.00 0.00
November 16014.58 01-NOV-09:09 20611.01 01-NOV-07:10 17206.63 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 0.00
December 16014.58 01-DEC-10:09 20611.01 01-DEC-08:09 17206.63 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average             0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 16014.58   20611.01   17206.63   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 16014.58   20611.01   17206.63   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: CORE_MID

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 16014.58 02-JAN-10:09 20611.01 02-JAN-08:09 17206.56 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 0.00
February 16014.58 01-FEB-10:09 20611.01 01-FEB-08:09 17206.56 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 0.00
March 16014.58 01-MAR-10:09 20611.01 01-MAR-08:09 17206.56 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 0.00
April 16014.58 03-APR-09:09 20611.01 03-APR-07:10 17206.56 03-APR-07:10 0.00 0.00 0.00 0.00 0.00 0.00
May 16014.58 01-MAY-09:09 20611.01 01-MAY-07:10 17206.56 01-MAY-07:10 0.00 0.00 0.00 0.00 0.00 0.00
June 16014.58 01-JUN-09:09 20611.01 01-JUN-07:10 17206.56 01-JUN-07:10 0.00 0.00 0.00 0.00 0.00 0.00
July 16014.58 03-JUL-09:09 20611.01 03-JUL-07:10 17206.56 03-JUL-07:10 0.00 0.00 0.00 0.00 0.00 0.00
August 16014.58 01-AUG-09:09 20611.01 01-AUG-07:10 17206.56 01-AUG-07:10 0.00 0.00 0.00 0.00 0.00 0.00
September 16014.58 01-SEP-09:09 20611.01 01-SEP-07:10 17206.56 01-SEP-07:10 0.00 0.00 0.00 0.00 0.00 0.00
October 16014.58 02-OCT-09:09 20611.01 02-OCT-07:10 17206.56 02-OCT-07:10 0.00 0.00 0.00 0.00 0.00 0.00
November 16014.58 01-NOV-09:09 20611.01 01-NOV-07:10 17206.56 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 0.00
December 16014.58 01-DEC-10:09 20611.01 01-DEC-08:09 17206.56 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average             0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 16014.58   20611.01   17206.56   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 16014.58   20611.01   17206.56   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: CORE_TOP

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 16014.58 02-JAN-10:09 20611.01 02-JAN-08:09 17206.56 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 0.00
February 16014.58 01-FEB-10:09 20611.01 01-FEB-08:09 17206.56 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 0.00
March 16014.58 01-MAR-10:09 20611.01 01-MAR-08:09 17206.56 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 0.00
April 16014.58 03-APR-09:09 20611.01 03-APR-07:10 17206.56 03-APR-07:10 0.00 0.00 0.00 0.00 0.00 0.00
May 16014.58 01-MAY-09:09 20611.01 01-MAY-07:10 17206.56 01-MAY-07:10 0.00 0.00 0.00 0.00 0.00 0.00
June 16014.58 01-JUN-09:09 20611.01 01-JUN-07:10 17206.56 01-JUN-07:10 0.00 0.00 0.00 0.00 0.00 0.00
July 16014.58 03-JUL-09:09 20611.01 03-JUL-07:10 17206.56 03-JUL-07:10 0.00 0.00 0.00 0.00 0.00 0.00
August 16014.58 01-AUG-09:09 20611.01 01-AUG-07:10 17206.56 01-AUG-07:10 0.00 0.00 0.00 0.00 0.00 0.00
September 16014.58 01-SEP-09:09 20611.01 01-SEP-07:10 17206.56 01-SEP-07:10 0.00 0.00 0.00 0.00 0.00 0.00
October 16014.58 02-OCT-09:09 20611.01 02-OCT-07:10 17206.56 02-OCT-07:10 0.00 0.00 0.00 0.00 0.00 0.00
November 16014.58 01-NOV-09:09 20611.01 01-NOV-07:10 17206.56 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 0.00
December 16014.58 01-DEC-10:09 20611.01 01-DEC-08:09 17206.56 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average             0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 16014.58   20611.01   17206.56   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 16014.58   20611.01   17206.56   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 2010.79 02-JAN-10:09 2587.92 02-JAN-16:19 2160.55 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:01 2448.12 31-JAN-01:00
February 2010.79 01-FEB-10:09 2587.92 01-FEB-16:49 2160.55 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 2441.33 05-FEB-07:55
March 2010.79 01-MAR-10:09 1803.00 02-MAR-16:30 2160.55 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 1970.10 12-MAR-10:00
April 2010.79 03-APR-09:09 1350.81 14-APR-07:10 2160.55 03-APR-07:10 0.00 0.00 0.00 0.00 29.53 07-APR-13:00 1529.98 11-APR-04:00
May 2010.79 01-MAY-09:09 1350.81 04-MAY-07:10 2160.55 01-MAY-07:10 0.00 0.00 0.00 0.00 101.14 29-MAY-12:10 909.70 03-MAY-04:00
June 2010.79 01-JUN-09:09 1350.81 16-JUN-07:10 2160.55 01-JUN-07:10 0.00 0.00 0.00 0.00 199.76 19-JUN-21:02 519.66 02-JUN-22:00
July 2010.79 03-JUL-09:09 1350.81 24-JUL-07:10 2160.55 03-JUL-07:10 0.00 0.00 0.00 0.00 198.64 09-JUL-13:52 226.14 02-JUL-18:30
August 2010.79 01-AUG-09:09 1470.28 16-AUG-07:10 2160.55 01-AUG-07:10 0.00 0.00 0.00 0.00 276.57 04-AUG-21:01 342.03 20-AUG-06:00
September 2010.79 01-SEP-09:09 1803.00 27-SEP-07:10 2160.55 01-SEP-07:10 0.00 0.00 0.00 0.00 77.01 14-SEP-14:00 476.80 17-SEP-10:00
October 2010.79 02-OCT-09:09 2255.20 06-OCT-07:10 2160.55 02-OCT-07:10 0.00 0.00 0.00 0.00 13.53 25-OCT-11:00 1322.25 08-OCT-08:00
November 2010.79 01-NOV-09:09 2587.92 06-NOV-16:19 2160.55 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 2035.56 23-NOV-02:00
December 2010.79 01-DEC-10:09 2587.92 01-DEC-16:10 2160.55 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 2626.48 31-DEC-21:52
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 2010.79   1350.81   2160.55   0.00 0.00 0.00 0.00 0.00   226.14  
Maximum of Months 2010.79   2587.92   2160.55   0.00 0.00 0.00 0.00 276.57   2626.48  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 1295.83 02-JAN-10:09 1667.75 02-JAN-16:19 1392.34 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:01 1627.64 31-JAN-01:00
February 1295.83 01-FEB-10:09 1667.75 01-FEB-16:49 1392.34 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 1785.92 05-FEB-08:50
March 1295.83 01-MAR-10:09 1453.34 02-MAR-16:49 1392.34 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 1488.49 12-MAR-10:00
April 1295.83 03-APR-09:09 870.51 05-APR-15:00 1392.34 03-APR-07:10 0.00 0.00 0.00 0.00 19.69 07-APR-13:00 993.62 11-APR-04:00
May 1295.83 01-MAY-09:09 870.51 08-MAY-07:10 1392.34 01-MAY-07:10 0.00 0.00 0.00 0.00 73.27 29-MAY-12:08 599.88 03-MAY-04:00
June 1295.83 01-JUN-09:09 793.52 01-JUN-07:10 1392.34 01-JUN-07:10 0.00 0.00 0.00 0.00 133.22 19-JUN-21:02 338.66 02-JUN-22:00
July 1295.83 03-JUL-09:09 793.52 03-JUL-07:10 1392.34 03-JUL-07:10 0.00 0.00 0.00 0.00 149.24 09-JUL-13:44 142.54 02-JUL-18:30
August 1295.83 01-AUG-09:09 870.51 16-AUG-07:10 1392.34 01-AUG-07:10 0.00 0.00 0.00 0.00 202.57 12-AUG-19:10 225.95 20-AUG-06:00
September 1295.83 01-SEP-09:09 947.51 22-SEP-15:00 1392.34 01-SEP-07:10 0.00 0.00 0.00 0.00 51.34 14-SEP-14:00 327.54 10-SEP-08:10
October 1295.83 02-OCT-09:09 1453.34 31-OCT-15:50 1392.34 02-OCT-07:10 0.00 0.00 0.00 0.00 9.02 25-OCT-11:00 1010.93 08-OCT-08:30
November 1295.83 01-NOV-09:09 1667.75 06-NOV-16:19 1392.34 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 1339.73 23-NOV-02:00
December 1295.83 01-DEC-10:09 1667.75 01-DEC-16:10 1392.34 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 1728.20 31-DEC-21:52
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 1295.83   793.52   1392.34   0.00 0.00 0.00 0.00 0.00   142.54  
Maximum of Months 1295.83   1667.75   1392.34   0.00 0.00 0.00 0.00 202.57   1785.92  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 2010.83 02-JAN-10:09 2587.98 02-JAN-16:30 2160.58 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:01 2471.51 31-JAN-01:00
February 2010.83 01-FEB-10:09 2587.98 01-FEB-16:00 2160.58 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 2546.67 05-FEB-10:00
March 2010.83 01-MAR-10:09 1803.04 02-MAR-16:40 2160.58 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 2175.74 12-MAR-10:00
April 2010.83 03-APR-09:09 1350.84 14-APR-07:10 2160.58 03-APR-07:10 0.00 0.00 0.00 0.00 29.43 07-APR-13:00 1519.78 11-APR-04:00
May 2010.83 01-MAY-09:09 1350.84 04-MAY-07:10 2160.58 01-MAY-07:10 0.00 0.00 0.00 0.00 95.65 29-MAY-12:04 900.77 03-MAY-04:00
June 2010.83 01-JUN-09:09 1350.84 16-JUN-07:10 2160.58 01-JUN-07:10 0.00 0.00 0.00 0.00 199.36 19-JUN-21:02 519.81 02-JUN-22:00
July 2010.83 03-JUL-09:09 1350.84 05-JUL-07:10 2160.58 03-JUL-07:10 0.00 0.00 0.00 0.00 205.64 09-JUL-13:44 228.43 02-JUL-18:30
August 2010.83 01-AUG-09:09 1470.31 16-AUG-07:10 2160.58 01-AUG-07:10 0.00 0.00 0.00 0.00 275.64 04-AUG-21:01 339.21 20-AUG-06:00
September 2010.83 01-SEP-09:09 1470.31 21-SEP-07:10 2160.58 01-SEP-07:10 0.00 0.00 0.00 0.00 76.89 14-SEP-14:00 470.55 30-SEP-24:00
October 2010.83 02-OCT-09:09 2255.25 31-OCT-15:00 2160.58 02-OCT-07:10 0.00 0.00 0.00 0.00 13.05 25-OCT-11:00 1390.77 08-OCT-08:00
November 2010.83 01-NOV-09:09 2587.98 06-NOV-16:40 2160.58 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 2025.71 23-NOV-02:00
December 2010.83 01-DEC-10:09 2587.98 01-DEC-16:30 2160.58 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 2604.61 31-DEC-21:52
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 2010.83   1350.84   2160.58   0.00 0.00 0.00 0.00 0.00   228.43  
Maximum of Months 2010.83   2587.98   2160.58   0.00 0.00 0.00 0.00 275.64   2604.61  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 1295.83 02-JAN-10:09 1667.75 02-JAN-16:30 1392.33 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:01 1697.00 31-JAN-01:00
February 1295.83 01-FEB-10:09 1667.75 15-FEB-16:00 1392.33 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 1710.24 05-FEB-07:55
March 1295.83 01-MAR-10:09 1161.92 06-MAR-08:09 1392.33 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 1465.50 12-MAR-10:00
April 1295.83 03-APR-09:09 947.51 14-APR-07:10 1392.33 03-APR-07:10 0.00 0.00 0.00 0.00 19.69 07-APR-13:00 1155.03 11-APR-04:00
May 1295.83 01-MAY-09:09 947.51 04-MAY-07:10 1392.33 01-MAY-07:10 0.00 0.00 0.00 0.00 90.64 29-MAY-12:10 670.92 03-MAY-04:00
June 1295.83 01-JUN-09:09 870.51 12-JUN-07:10 1392.33 01-JUN-07:10 0.00 0.00 0.00 0.00 127.90 19-JUN-21:02 408.56 02-JUN-22:00
July 1295.83 03-JUL-09:09 870.51 05-JUL-07:10 1392.33 03-JUL-07:10 0.00 0.00 0.00 0.00 134.71 09-JUL-13:44 248.85 02-JUL-17:50
August 1295.83 01-AUG-09:09 947.51 16-AUG-07:10 1392.33 01-AUG-07:10 0.00 0.00 0.00 0.00 178.58 04-AUG-21:01 279.33 20-AUG-06:00
September 1295.83 01-SEP-09:09 1161.92 26-SEP-07:10 1392.33 01-SEP-07:10 0.00 0.00 0.00 0.00 51.34 14-SEP-14:00 350.86 17-SEP-10:00
October 1295.83 02-OCT-09:09 1453.34 06-OCT-07:10 1392.33 02-OCT-07:10 0.00 0.00 0.00 0.00 9.02 25-OCT-11:00 954.20 08-OCT-08:00
November 1295.83 01-NOV-09:09 1667.75 06-NOV-16:40 1392.33 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 1462.62 23-NOV-02:00
December 1295.83 01-DEC-10:09 1667.75 01-DEC-16:30 1392.33 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 1919.45 31-DEC-21:52
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 1295.83   870.51   1392.33   0.00 0.00 0.00 0.00 0.00   248.85  
Maximum of Months 1295.83   1667.75   1392.33   0.00 0.00 0.00 0.00 178.58   1919.45  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 2010.79 02-JAN-10:09 2587.92 02-JAN-16:19 2160.55 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:01 5125.74 14-JAN-05:51
February 2010.79 01-FEB-10:09 2587.92 01-FEB-16:49 2160.55 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 5380.42 06-FEB-00:54
March 2010.79 01-MAR-10:09 1803.00 02-MAR-16:30 2160.55 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 4083.27 21-MAR-21:02
April 2010.79 03-APR-09:09 1350.81 14-APR-07:10 2160.55 03-APR-07:10 0.00 0.00 0.00 0.00 66.46 07-APR-13:00 3053.02 11-APR-04:00
May 2010.79 01-MAY-09:09 1350.81 04-MAY-07:10 2160.55 01-MAY-07:10 0.00 0.00 0.00 0.00 280.89 29-MAY-12:00 1824.75 03-MAY-04:00
June 2010.79 01-JUN-09:09 1350.81 16-JUN-07:10 2160.55 01-JUN-07:10 0.00 0.00 0.00 0.00 459.04 19-JUN-21:02 1126.86 02-JUN-22:00
July 2010.79 03-JUL-09:09 1350.81 24-JUL-07:10 2160.55 03-JUL-07:10 0.00 0.00 0.00 0.00 459.32 09-JUL-13:46 518.99 11-JUL-04:53
August 2010.79 01-AUG-09:09 1350.81 16-AUG-07:10 2160.55 01-AUG-07:10 0.00 0.00 0.00 0.00 641.58 04-AUG-21:01 738.67 20-AUG-06:00
September 2010.79 01-SEP-09:09 1803.00 27-SEP-07:10 2160.55 01-SEP-07:10 0.00 0.00 0.00 0.00 177.62 14-SEP-14:00 951.38 23-SEP-04:00
October 2010.79 02-OCT-09:09 2255.20 06-OCT-07:10 2160.55 02-OCT-07:10 0.00 0.00 0.00 0.00 28.29 25-OCT-11:00 2539.00 17-OCT-24:00
November 2010.79 01-NOV-09:09 2587.92 06-NOV-16:19 2160.55 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 3996.11 22-NOV-22:02
December 2010.79 01-DEC-10:09 2587.92 01-DEC-16:10 2160.55 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 5259.89 31-DEC-21:52
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 2010.79   1350.81   2160.55   0.00 0.00 0.00 0.00 0.00   518.99  
Maximum of Months 2010.79   2587.92   2160.55   0.00 0.00 0.00 0.00 641.58   5380.42  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 1239.33 02-JAN-08:09 1667.75 02-JAN-16:19 1392.34 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:01 3429.14 14-JAN-05:51
February 1239.33 01-FEB-08:09 1667.75 01-FEB-16:49 1392.34 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 3586.92 06-FEB-01:00
March 1239.33 01-MAR-08:09 1453.34 02-MAR-16:00 1392.34 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 2864.48 12-MAR-10:00
April 1239.33 03-APR-07:10 870.51 05-APR-15:00 1392.34 03-APR-07:10 0.00 0.00 0.00 0.00 44.30 07-APR-13:00 2035.84 11-APR-04:00
May 1239.33 01-MAY-07:10 870.51 08-MAY-07:10 1392.34 01-MAY-07:10 0.00 0.00 0.00 0.00 169.42 29-MAY-11:55 1222.22 03-MAY-04:00
June 1239.33 01-JUN-07:10 793.52 01-JUN-07:10 1392.34 01-JUN-07:10 0.00 0.00 0.00 0.00 304.72 19-JUN-21:02 744.63 02-JUN-22:00
July 1239.33 03-JUL-07:10 793.52 03-JUL-07:10 1392.34 03-JUL-07:10 0.00 0.00 0.00 0.00 323.09 09-JUL-13:44 348.21 11-JUL-04:53
August 1239.33 01-AUG-07:10 870.51 16-AUG-07:10 1392.34 01-AUG-07:10 0.00 0.00 0.00 0.00 456.49 12-AUG-18:53 530.07 20-AUG-06:00
September 1239.33 01-SEP-07:10 947.51 22-SEP-15:00 1392.34 01-SEP-07:10 0.00 0.00 0.00 0.00 118.41 14-SEP-14:00 741.65 10-SEP-08:20
October 1239.33 02-OCT-07:10 1453.34 31-OCT-15:50 1392.34 02-OCT-07:10 0.00 0.00 0.00 0.00 18.84 25-OCT-11:00 2029.72 08-OCT-08:30
November 1239.33 01-NOV-07:10 1667.75 06-NOV-16:19 1392.34 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 2677.06 23-NOV-02:00
December 1239.33 01-DEC-08:09 1667.75 01-DEC-16:10 1392.34 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 3508.54 31-DEC-21:52
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 1239.33   793.52   1392.34   0.00 0.00 0.00 0.00 0.00   348.21  
Maximum of Months 1239.33   1667.75   1392.34   0.00 0.00 0.00 0.00 456.49   3586.92  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 2010.83 02-JAN-10:09 2587.98 02-JAN-16:30 2160.58 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:01 5216.55 31-JAN-01:00
February 2010.83 01-FEB-10:09 2587.98 01-FEB-16:00 2160.58 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 5380.31 06-FEB-00:56
March 2010.83 01-MAR-10:09 1803.04 02-MAR-16:00 2160.58 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 4361.41 12-MAR-10:00
April 2010.83 03-APR-09:09 1350.84 14-APR-07:10 2160.58 03-APR-07:10 0.00 0.00 0.00 0.00 66.31 07-APR-13:00 3149.00 11-APR-04:00
May 2010.83 01-MAY-09:09 1350.84 04-MAY-07:10 2160.58 01-MAY-07:10 0.00 0.00 0.00 0.00 202.99 29-MAY-11:53 1874.14 03-MAY-04:00
June 2010.83 01-JUN-09:09 1350.84 16-JUN-07:10 2160.58 01-JUN-07:10 0.00 0.00 0.00 0.00 458.17 19-JUN-21:02 1130.15 02-JUN-22:00
July 2010.83 03-JUL-09:09 1350.84 24-JUL-07:10 2160.58 03-JUL-07:10 0.00 0.00 0.00 0.00 477.79 09-JUL-13:44 516.15 02-JUL-18:50
August 2010.83 01-AUG-09:09 1350.84 16-AUG-07:10 2160.58 01-AUG-07:10 0.00 0.00 0.00 0.00 639.10 04-AUG-21:01 765.18 20-AUG-05:53
September 2010.83 01-SEP-09:09 1470.31 22-SEP-07:10 2160.58 01-SEP-07:10 0.00 0.00 0.00 0.00 177.38 14-SEP-14:00 1062.50 30-SEP-24:00
October 2010.83 02-OCT-09:09 2255.25 31-OCT-15:00 2160.58 02-OCT-07:10 0.00 0.00 0.00 0.00 27.58 25-OCT-11:00 2992.86 08-OCT-10:00
November 2010.83 01-NOV-09:09 2587.98 06-NOV-16:40 2160.58 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 4187.18 23-NOV-02:00
December 2010.83 01-DEC-10:09 2587.98 01-DEC-16:30 2160.58 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 5308.31 31-DEC-21:52
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 2010.83   1350.84   2160.58   0.00 0.00 0.00 0.00 0.00   516.15  
Maximum of Months 2010.83   2587.98   2160.58   0.00 0.00 0.00 0.00 639.10   5380.31  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 1295.83 02-JAN-10:09 1667.75 02-JAN-16:30 1392.33 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:01 3433.44 14-JAN-05:51
February 1295.83 01-FEB-10:09 1667.75 15-FEB-16:00 1392.33 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 3586.93 06-FEB-00:57
March 1295.83 01-MAR-10:09 1161.92 06-MAR-08:09 1392.33 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 2743.50 21-MAR-21:02
April 1295.83 03-APR-09:09 947.51 14-APR-07:10 1392.33 03-APR-07:10 0.00 0.00 0.00 0.00 44.31 07-APR-13:00 2143.48 11-APR-04:00
May 1295.83 01-MAY-09:09 947.51 08-MAY-07:10 1392.33 01-MAY-07:10 0.00 0.00 0.00 0.00 253.39 29-MAY-12:00 1301.14 03-MAY-04:00
June 1295.83 01-JUN-09:09 870.51 16-JUN-07:10 1392.33 01-JUN-07:10 0.00 0.00 0.00 0.00 298.62 19-JUN-21:02 936.37 03-JUN-17:40
July 1295.83 03-JUL-09:09 870.51 05-JUL-07:10 1392.33 03-JUL-07:10 0.00 0.00 0.00 0.00 304.18 09-JUL-13:44 575.81 02-JUL-17:30
August 1295.83 01-AUG-09:09 947.51 16-AUG-07:10 1392.33 01-AUG-07:10 0.00 0.00 0.00 0.00 422.92 04-AUG-21:01 549.95 20-AUG-05:53
September 1295.83 01-SEP-09:09 1161.92 26-SEP-07:10 1392.33 01-SEP-07:10 0.00 0.00 0.00 0.00 118.41 14-SEP-14:00 700.11 30-SEP-24:00
October 1295.83 02-OCT-09:09 1453.34 06-OCT-07:10 1392.33 02-OCT-07:10 0.00 0.00 0.00 0.00 18.86 25-OCT-11:00 1771.70 17-OCT-22:00
November 1295.83 01-NOV-09:09 1667.75 06-NOV-16:40 1392.33 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 2715.78 23-NOV-02:00
December 1295.83 01-DEC-10:09 1667.75 01-DEC-16:30 1392.33 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 3525.07 31-DEC-21:52
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 1295.83   870.51   1392.33   0.00 0.00 0.00 0.00 0.00   549.95  
Maximum of Months 1295.83   1667.75   1392.33   0.00 0.00 0.00 0.00 422.92   3586.93  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 2010.79 02-JAN-10:09 2587.92 02-JAN-16:19 2160.55 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:01 6165.11 01-JAN-21:00
February 2010.79 01-FEB-10:09 2587.92 01-FEB-16:49 2160.55 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 6704.78 06-FEB-01:00
March 2010.79 01-MAR-10:09 1803.00 02-MAR-16:30 2160.55 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 5064.94 21-MAR-21:02
April 2010.79 03-APR-09:09 1350.81 14-APR-07:10 2160.55 03-APR-07:10 0.00 0.00 0.00 0.00 79.04 07-APR-13:00 3455.84 11-APR-04:00
May 2010.79 01-MAY-09:09 1350.81 04-MAY-07:10 2160.55 01-MAY-07:10 0.00 0.00 0.00 0.00 281.60 29-MAY-12:10 2067.72 03-MAY-04:00
June 2010.79 01-JUN-09:09 1350.81 16-JUN-07:10 2160.55 01-JUN-07:10 0.00 0.00 0.00 0.00 553.16 19-JUN-21:02 1352.00 02-JUN-22:00
July 2010.79 03-JUL-09:09 1350.81 24-JUL-07:10 2160.55 03-JUL-07:10 0.00 0.00 0.00 0.00 609.77 09-JUL-13:56 717.87 02-JUL-19:00
August 2010.79 01-AUG-09:09 1350.81 16-AUG-07:10 2160.55 01-AUG-07:10 0.00 0.00 0.00 0.00 782.89 04-AUG-21:01 857.94 20-AUG-06:00
September 2010.79 01-SEP-09:09 1803.00 27-SEP-07:10 2160.55 01-SEP-07:10 0.00 0.00 0.00 0.00 216.83 14-SEP-14:00 1098.20 23-SEP-04:00
October 2010.79 02-OCT-09:09 2255.20 06-OCT-07:10 2160.55 02-OCT-07:10 0.00 0.00 0.00 0.00 30.84 25-OCT-11:00 2905.11 17-OCT-22:00
November 2010.79 01-NOV-09:09 2587.92 06-NOV-16:19 2160.55 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 4955.28 22-NOV-22:02
December 2010.79 01-DEC-10:09 2587.92 01-DEC-16:10 2160.55 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 6671.01 31-DEC-21:56
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 2010.79   1350.81   2160.55   0.00 0.00 0.00 0.00 0.00   717.87  
Maximum of Months 2010.79   2587.92   2160.55   0.00 0.00 0.00 0.00 782.89   6704.78  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 1295.83 02-JAN-10:09 1667.75 02-JAN-16:19 1392.34 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:01 4247.48 14-JAN-05:51
February 1295.83 01-FEB-10:09 1667.75 01-FEB-16:49 1392.34 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 4470.41 06-FEB-00:56
March 1295.83 01-MAR-10:09 1453.34 02-MAR-16:00 1392.34 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 3383.02 21-MAR-21:02
April 1295.83 03-APR-09:09 870.51 05-APR-15:00 1392.34 03-APR-07:10 0.00 0.00 0.00 0.00 52.69 07-APR-13:00 2311.92 11-APR-04:14
May 1295.83 01-MAY-09:09 870.51 08-MAY-07:10 1392.34 01-MAY-07:10 0.00 0.00 0.00 0.00 191.20 29-MAY-12:06 1390.15 03-MAY-04:00
June 1295.83 01-JUN-09:09 793.52 01-JUN-07:10 1392.34 01-JUN-07:10 0.00 0.00 0.00 0.00 366.99 19-JUN-21:02 897.18 02-JUN-22:00
July 1295.83 03-JUL-09:09 793.52 03-JUL-07:10 1392.34 03-JUL-07:10 0.00 0.00 0.00 0.00 419.57 09-JUL-13:56 496.85 02-JUL-19:00
August 1295.83 01-AUG-09:09 870.51 16-AUG-07:10 1392.34 01-AUG-07:10 0.00 0.00 0.00 0.00 536.30 12-AUG-18:53 618.42 20-AUG-06:00
September 1295.83 01-SEP-09:09 947.51 22-SEP-15:00 1392.34 01-SEP-07:10 0.00 0.00 0.00 0.00 144.55 14-SEP-14:00 967.69 10-SEP-08:00
October 1295.83 02-OCT-09:09 1453.34 31-OCT-15:50 1392.34 02-OCT-07:10 0.00 0.00 0.00 0.00 20.54 25-OCT-11:00 2155.03 08-OCT-08:30
November 1295.83 01-NOV-09:09 1667.75 06-NOV-16:19 1392.34 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 3306.29 22-NOV-22:02
December 1295.83 01-DEC-10:09 1667.75 01-DEC-16:10 1392.34 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 4447.23 31-DEC-21:58
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 1295.83   793.52   1392.34   0.00 0.00 0.00 0.00 0.00   496.85  
Maximum of Months 1295.83   1667.75   1392.34   0.00 0.00 0.00 0.00 536.30   4470.41  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 2010.83 02-JAN-10:09 2587.98 02-JAN-16:30 2160.58 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:01 6376.03 14-JAN-05:51
February 2010.83 01-FEB-10:09 2587.98 01-FEB-16:00 2160.58 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 6705.66 06-FEB-00:57
March 2010.83 01-MAR-10:09 1803.04 02-MAR-16:00 2160.58 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 5097.41 21-MAR-21:02
April 2010.83 03-APR-09:09 1350.84 14-APR-07:10 2160.58 03-APR-07:10 0.00 0.00 0.00 0.00 78.82 07-APR-13:00 3576.48 11-APR-04:00
May 2010.83 01-MAY-09:09 1350.84 04-MAY-07:10 2160.58 01-MAY-07:10 0.00 0.00 0.00 0.00 249.50 29-MAY-12:04 2130.90 03-MAY-04:00
June 2010.83 01-JUN-09:09 1350.84 16-JUN-07:10 2160.58 01-JUN-07:10 0.00 0.00 0.00 0.00 552.00 19-JUN-21:02 1355.35 02-JUN-22:00
July 2010.83 03-JUL-09:09 1350.84 24-JUL-07:10 2160.58 03-JUL-07:10 0.00 0.00 0.00 0.00 604.99 09-JUL-13:56 734.15 02-JUL-19:00
August 2010.83 01-AUG-09:09 1350.84 16-AUG-07:10 2160.58 01-AUG-07:10 0.00 0.00 0.00 0.00 779.73 04-AUG-21:01 892.67 20-AUG-05:53
September 2010.83 01-SEP-09:09 1470.31 22-SEP-07:10 2160.58 01-SEP-07:10 0.00 0.00 0.00 0.00 216.50 14-SEP-14:00 1234.55 30-SEP-24:00
October 2010.83 02-OCT-09:09 2255.25 31-OCT-15:00 2160.58 02-OCT-07:10 0.00 0.00 0.00 0.00 30.58 25-OCT-11:00 3225.22 08-OCT-10:00
November 2010.83 01-NOV-09:09 2587.98 06-NOV-16:40 2160.58 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 4977.30 22-NOV-22:02
December 2010.83 01-DEC-10:09 2587.98 01-DEC-16:30 2160.58 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 6671.01 31-DEC-22:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 2010.83   1350.84   2160.58   0.00 0.00 0.00 0.00 0.00   734.15  
Maximum of Months 2010.83   2587.98   2160.58   0.00 0.00 0.00 0.00 779.73   6705.66  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 1295.83 02-JAN-10:09 1667.75 02-JAN-16:30 1392.33 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:01 4254.83 14-JAN-05:51
February 1295.83 01-FEB-10:09 1667.75 15-FEB-16:00 1392.33 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 4470.47 06-FEB-01:00
March 1295.83 01-MAR-10:09 1161.92 06-MAR-08:09 1392.33 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 3403.22 21-MAR-21:02
April 1295.83 03-APR-09:09 947.51 14-APR-07:10 1392.33 03-APR-07:10 0.00 0.00 0.00 0.00 52.70 07-APR-13:00 2450.05 11-APR-04:00
May 1295.83 01-MAY-09:09 947.51 08-MAY-07:10 1392.33 01-MAY-07:10 0.00 0.00 0.00 0.00 290.85 29-MAY-12:10 1494.95 03-MAY-04:00
June 1295.83 01-JUN-09:09 870.51 16-JUN-07:10 1392.33 01-JUN-07:10 0.00 0.00 0.00 0.00 359.48 19-JUN-21:02 1169.60 03-JUN-17:40
July 1295.83 03-JUL-09:09 870.51 05-JUL-07:10 1392.33 03-JUL-07:10 0.00 0.00 0.00 0.00 406.15 09-JUL-13:54 746.89 02-JUL-17:40
August 1295.83 01-AUG-09:09 947.51 16-AUG-07:10 1392.33 01-AUG-07:10 0.00 0.00 0.00 0.00 515.90 04-AUG-21:01 645.84 20-AUG-05:53
September 1295.83 01-SEP-09:09 1161.92 26-SEP-07:10 1392.33 01-SEP-07:10 0.00 0.00 0.00 0.00 144.55 14-SEP-14:00 869.72 10-SEP-20:00
October 1295.83 02-OCT-09:09 1453.34 06-OCT-07:10 1392.33 02-OCT-07:10 0.00 0.00 0.00 0.00 20.57 25-OCT-11:00 2063.15 17-OCT-22:00
November 1295.83 01-NOV-09:09 1667.75 06-NOV-16:40 1392.33 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 3310.96 22-NOV-22:02
December 1295.83 01-DEC-10:09 1667.75 01-DEC-16:30 1392.33 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 4447.24 31-DEC-21:58
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 1295.83   870.51   1392.33   0.00 0.00 0.00 0.00 0.00   645.84  
Maximum of Months 1295.83   1667.75   1392.33   0.00 0.00 0.00 0.00 515.90   4470.47  



Table of Contents

Report: PeakSpaceGainsMonthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 232.27 02-JAN-10:09 578.72 02-JAN-08:09 1948.61 01-JAN-00:10 0.00 0.00 0.00 0.00 0.00 0.00
February 232.27 01-FEB-10:09 578.72 01-FEB-08:09 3897.21 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00 0.00
March 232.27 01-MAR-10:09 578.72 01-MAR-08:09 7794.42 31-MAR-23:10 0.00 0.00 0.00 0.00 0.00 0.00
April 232.27 03-APR-09:09 578.72 03-APR-07:10 7794.42 01-APR-00:10 0.00 0.00 0.00 0.00 0.00 0.00
May 232.27 01-MAY-09:09 578.72 01-MAY-07:10 3897.21 31-MAY-23:10 0.00 0.00 0.00 0.00 0.00 0.00
June 232.27 01-JUN-09:09 578.72 01-JUN-07:10 5845.82 30-JUN-23:10 0.00 0.00 0.00 0.00 0.00 0.00
July 232.27 03-JUL-09:09 578.72 03-JUL-07:10 7794.42 31-JUL-23:10 0.00 0.00 0.00 0.00 0.00 0.00
August 232.27 01-AUG-09:09 578.72 01-AUG-07:10 7794.42 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00 0.00
September 232.27 01-SEP-09:09 578.72 01-SEP-07:10 3897.21 30-SEP-23:10 0.00 0.00 0.00 0.00 0.00 0.00
October 232.27 02-OCT-09:09 578.72 02-OCT-07:10 5845.82 31-OCT-23:10 0.00 0.00 0.00 0.00 0.00 0.00
November 232.27 01-NOV-09:09 578.72 01-NOV-07:10 5845.82 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00 0.00
December 232.27 01-DEC-10:09 578.72 01-DEC-08:09 7794.42 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average             0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 232.27   578.72   1948.61   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 232.27   578.72   7794.42   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: DATACENTER_MID_ZN_6

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 232.27 02-JAN-10:09 578.72 02-JAN-08:09 1948.61 01-JAN-00:10 0.00 0.00 0.00 0.00 0.00 0.00
February 232.27 01-FEB-10:09 578.72 01-FEB-08:09 3897.21 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00 0.00
March 232.27 01-MAR-10:09 578.72 01-MAR-08:09 7794.42 31-MAR-23:10 0.00 0.00 0.00 0.00 0.00 0.00
April 232.27 03-APR-09:09 578.72 03-APR-07:10 7794.42 01-APR-00:10 0.00 0.00 0.00 0.00 0.00 0.00
May 232.27 01-MAY-09:09 578.72 01-MAY-07:10 3897.21 31-MAY-23:10 0.00 0.00 0.00 0.00 0.00 0.00
June 232.27 01-JUN-09:09 578.72 01-JUN-07:10 5845.82 30-JUN-23:10 0.00 0.00 0.00 0.00 0.00 0.00
July 232.27 03-JUL-09:09 578.72 03-JUL-07:10 7794.42 31-JUL-23:10 0.00 0.00 0.00 0.00 0.00 0.00
August 232.27 01-AUG-09:09 578.72 01-AUG-07:10 7794.42 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00 0.00
September 232.27 01-SEP-09:09 578.72 01-SEP-07:10 3897.21 30-SEP-23:10 0.00 0.00 0.00 0.00 0.00 0.00
October 232.27 02-OCT-09:09 578.72 02-OCT-07:10 5845.82 31-OCT-23:10 0.00 0.00 0.00 0.00 0.00 0.00
November 232.27 01-NOV-09:09 578.72 01-NOV-07:10 5845.82 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00 0.00
December 232.27 01-DEC-10:09 578.72 01-DEC-08:09 7794.42 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average             0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 232.27   578.72   1948.61   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 232.27   578.72   7794.42   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 232.27 02-JAN-10:09 578.72 02-JAN-08:09 1948.61 01-JAN-00:10 0.00 0.00 0.00 0.00 0.00 0.00
February 232.27 01-FEB-10:09 578.72 01-FEB-08:09 3897.21 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00 0.00
March 232.27 01-MAR-10:09 578.72 01-MAR-08:09 7794.42 31-MAR-23:10 0.00 0.00 0.00 0.00 0.00 0.00
April 232.27 03-APR-09:09 578.72 03-APR-07:10 7794.42 01-APR-00:10 0.00 0.00 0.00 0.00 0.00 0.00
May 232.27 01-MAY-09:09 578.72 01-MAY-07:10 3897.21 31-MAY-23:10 0.00 0.00 0.00 0.00 0.00 0.00
June 232.27 01-JUN-09:09 578.72 01-JUN-07:10 5845.82 30-JUN-23:10 0.00 0.00 0.00 0.00 0.00 0.00
July 232.27 03-JUL-09:09 578.72 03-JUL-07:10 7794.42 31-JUL-23:10 0.00 0.00 0.00 0.00 0.00 0.00
August 232.27 01-AUG-09:09 578.72 01-AUG-07:10 7794.42 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00 0.00
September 232.27 01-SEP-09:09 578.72 01-SEP-07:10 3897.21 30-SEP-23:10 0.00 0.00 0.00 0.00 0.00 0.00
October 232.27 02-OCT-09:09 578.72 02-OCT-07:10 5845.82 31-OCT-23:10 0.00 0.00 0.00 0.00 0.00 0.00
November 232.27 01-NOV-09:09 578.72 01-NOV-07:10 5845.82 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00 0.00
December 232.27 01-DEC-10:09 578.72 01-DEC-08:09 7794.42 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average             0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 232.27   578.72   1948.61   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 232.27   578.72   7794.42   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 5027.92 02-JAN-10:09 6471.01 02-JAN-08:09 94908.13 01-JAN-00:10 0.00 0.00 0.00 0.00 0.00 0.00
February 5027.92 01-FEB-10:09 6471.01 01-FEB-08:09 189816.26 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00 0.00
March 5027.92 01-MAR-10:09 6471.01 01-MAR-08:09 379632.52 31-MAR-23:10 0.00 0.00 0.00 0.00 0.00 0.00
April 5027.92 03-APR-09:09 6471.01 03-APR-07:10 379632.52 01-APR-00:10 0.00 0.00 0.00 0.00 0.00 0.00
May 5027.92 01-MAY-09:09 6471.01 01-MAY-07:10 189816.26 31-MAY-23:10 0.00 0.00 0.00 0.00 0.00 0.00
June 5027.92 01-JUN-09:09 6471.01 01-JUN-07:10 284724.39 30-JUN-23:10 0.00 0.00 0.00 0.00 0.00 0.00
July 5027.92 03-JUL-09:09 6471.01 03-JUL-07:10 379632.52 31-JUL-23:10 0.00 0.00 0.00 0.00 0.00 0.00
August 5027.92 01-AUG-09:09 6471.01 01-AUG-07:10 379632.52 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00 0.00
September 5027.92 01-SEP-09:09 6471.01 01-SEP-07:10 189816.26 30-SEP-23:10 0.00 0.00 0.00 0.00 0.00 0.00
October 5027.92 02-OCT-09:09 6471.01 02-OCT-07:10 284724.39 31-OCT-23:10 0.00 0.00 0.00 0.00 0.00 0.00
November 5027.92 01-NOV-09:09 6471.01 01-NOV-07:10 284724.39 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00 0.00
December 5027.92 01-DEC-10:09 6471.01 01-DEC-08:09 379632.52 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average             0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 5027.92   6471.01   94908.13   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 5027.92   6471.01   379632.52   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: GROUNDFLOOR_PLENUM

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-JAN-00:01 5504.37 31-JAN-01:00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 5504.57 06-FEB-00:51
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 4113.53 12-MAR-10:00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 44.98 07-APR-13:00 3361.47 11-APR-04:00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 238.47 29-MAY-11:52 1989.60 03-MAY-04:00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 327.09 19-JUN-21:02 1086.85 02-JUN-22:00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 436.54 09-JUL-14:00 465.80 11-JUL-04:53
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 532.85 12-AUG-18:53 712.18 20-AUG-06:00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 135.23 14-SEP-14:00 973.91 23-SEP-04:00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 8.59 25-OCT-11:00 2884.70 08-OCT-08:00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 4581.18 23-NOV-02:00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 5880.42 31-DEC-21:52
                       
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00        
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00   465.80  
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 532.85   5880.42  



Table of Contents

Report: PeakSpaceGainsMonthly

For: MIDFLOOR_PLENUM

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-JAN-00:01 9210.61 31-JAN-01:00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 8980.65 05-FEB-07:55
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 6816.94 21-MAR-21:02
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 87.17 07-APR-13:00 5737.18 11-APR-04:00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 492.31 29-MAY-12:00 3377.59 03-MAY-04:00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 583.44 19-JUN-21:02 1912.70 02-JUN-22:00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 790.61 09-JUL-14:00 849.21 11-JUL-04:57
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 987.42 12-AUG-18:53 1276.69 20-AUG-05:53
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 241.47 14-SEP-14:00 1699.15 23-SEP-04:00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 18.61 25-OCT-11:00 4886.56 08-OCT-07:55
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 7662.30 23-NOV-02:00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 9270.64 31-DEC-21:52
                       
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00        
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00   849.21  
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 987.42   9270.64  



Table of Contents

Report: PeakSpaceGainsMonthly

For: TOPFLOOR_PLENUM

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-JAN-00:01 9487.95 31-JAN-01:00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 9159.44 06-FEB-01:00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 7718.30 21-MAR-21:02
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 40.84 08-APR-10:00 5752.48 11-APR-04:00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 224.20 29-MAY-11:52 3457.49 03-MAY-04:00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 679.34 19-JUN-21:02 2003.20 02-JUN-22:00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 600.73 07-JUL-22:00 1063.20 02-JUL-19:00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1065.89 12-AUG-18:53 1283.08 20-AUG-05:53
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 238.90 14-SEP-14:00 1762.49 23-SEP-04:00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 4801.94 17-OCT-24:00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 7748.23 23-NOV-02:00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 9205.92 31-DEC-21:54
                       
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00        
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00   1063.20  
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1065.89   9487.95  



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: BASEMENT

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 115457.96 23-JAN-05:11 0.00 25501.32 134575.44 0.00 0.00 0.00 0.00 0.00 0.00
February 120325.68 21-FEB-05:11 0.00 20401.06 107660.35 0.00 0.00 0.00 0.00 0.00 0.00
March 118973.77 06-MAR-05:11 0.00 25501.32 134575.44 0.00 0.00 0.00 0.00 0.00 0.00
April 118499.74 17-APR-04:12 0.00 15300.79 80745.26 0.00 0.00 0.00 0.00 0.00 0.00
May 118736.47 01-MAY-04:12 0.00 12750.66 67287.72 0.00 0.00 0.00 0.00 0.00 0.00
June 122957.68 05-JUN-04:11 0.00 20401.06 107660.35 0.00 0.00 0.00 0.00 0.00 0.00
July 102133.86 11-JUL-04:12 0.00 10200.53 53830.18 0.00 0.00 0.00 0.00 0.00 0.00
August 113881.28 08-AUG-04:12 0.00 15300.79 80745.26 0.00 0.00 0.00 0.00 0.00 0.00
September 116677.48 11-SEP-04:12 0.00 15300.79 80745.26 0.00 0.00 0.00 0.00 0.00 0.00
October 120071.76 23-OCT-04:12 0.00 15300.79 80745.26 0.00 0.00 0.00 0.00 0.00 0.00
November 120869.60 13-NOV-05:11 0.00 25501.32 134575.44 0.00 0.00 0.00 0.00 0.00 0.00
December 120497.18 04-DEC-05:11 0.00 25501.32 134575.44 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 102133.86   0.00 10200.53 53830.18 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 122957.68   0.00 25501.32 134575.44 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: CORE_BOTTOM

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 86971.60 21-JAN-06:02 9673.43 13741.19 45884.34 0.00 0.00 0.00 0.00 0.00 0.00
February 92221.29 21-FEB-05:11 0.00 18321.59 47501.16 0.00 0.00 0.00 0.00 0.00 0.00
March 94989.40 06-MAR-05:11 0.00 22901.98 59376.45 0.00 0.00 0.00 0.00 0.00 0.00
April 97257.76 10-APR-04:12 0.00 13741.19 35625.87 0.00 0.00 0.00 0.00 0.00 0.00
May 102334.13 30-MAY-04:13 0.00 13741.19 35625.87 0.00 0.00 0.00 0.00 0.00 0.00
June 102372.51 12-JUN-04:13 0.00 13741.19 35625.87 0.00 0.00 0.00 0.00 0.00 0.00
July 92555.96 01-JUL-04:12 0.00 6869.83 26719.40 0.00 0.00 0.00 0.00 0.00 0.00
August 94411.35 08-AUG-04:12 0.00 13741.19 35625.87 0.00 0.00 0.00 0.00 0.00 0.00
September 100351.35 18-SEP-04:12 0.00 13741.19 35625.87 0.00 0.00 0.00 0.00 0.00 0.00
October 100419.95 23-OCT-04:12 0.00 13741.19 35625.87 0.00 0.00 0.00 0.00 0.00 0.00
November 102646.78 13-NOV-05:11 0.00 22901.98 59376.45 0.00 0.00 0.00 0.00 0.00 0.00
December 95348.26 26-DEC-05:11 0.00 22901.98 59376.45 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 86971.60   0.00 6869.83 26719.40 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 102646.78   9673.43 22901.98 59376.45 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: CORE_MID

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 69970.00 31-JAN-18:12 6448.95 27481.35 30589.44 0.00 0.00 0.00 0.00 0.00 0.00
February 70235.30 03-FEB-16:57 61265.06 82444.06 68826.25 0.00 0.00 0.00 0.00 0.00 0.00
March 78814.94 17-MAR-12:55 30632.53 41222.03 34413.13 0.00 0.00 0.00 0.00 0.00 0.00
April 85004.74 10-APR-05:02 8061.19 11450.99 38236.81 0.00 0.00 0.00 0.00 0.00 0.00
May 87932.60 31-MAY-04:12 0.00 11450.99 29688.11 0.00 0.00 0.00 0.00 0.00 0.00
June 89525.06 12-JUN-04:12 0.00 13741.19 35625.74 0.00 0.00 0.00 0.00 0.00 0.00
July 87855.61 11-JUL-04:12 0.00 9160.79 23750.49 0.00 0.00 0.00 0.00 0.00 0.00
August 93640.06 07-AUG-04:12 0.00 13741.19 35625.74 0.00 0.00 0.00 0.00 0.00 0.00
September 89072.01 18-SEP-04:12 0.00 13741.19 35625.74 0.00 0.00 0.00 0.00 0.00 0.00
October 86193.25 06-OCT-04:12 0.00 11450.99 29688.11 0.00 0.00 0.00 0.00 0.00 0.00
November 80312.48 03-NOV-05:02 8061.19 11450.99 38236.81 0.00 0.00 0.00 0.00 0.00 0.00
December 56198.90 22-DEC-13:47 45948.79 61833.04 51619.69 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 56198.90   0.00 9160.79 23750.49 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 93640.06   61265.06 82444.06 68826.25 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: CORE_TOP

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 21768.40 20-JAN-17:00 30632.53 41222.03 34413.13 0.00 0.00 0.00 0.00 0.00 0.00
February 22156.72 17-FEB-17:00 15316.26 20611.01 17206.56 0.00 0.00 0.00 0.00 0.00 0.00
March 36117.19 03-MAR-17:00 15316.26 20611.01 17206.56 0.00 0.00 0.00 0.00 0.00 0.00
April 78803.82 27-APR-05:02 8061.19 11450.99 38236.81 0.00 0.00 0.00 0.00 0.00 0.00
May 89098.37 30-MAY-04:12 0.00 13741.19 35625.74 0.00 0.00 0.00 0.00 0.00 0.00
June 89700.02 12-JUN-04:12 0.00 13741.19 35625.74 0.00 0.00 0.00 0.00 0.00 0.00
July 89325.98 11-JUL-04:12 0.00 9160.79 23750.49 0.00 0.00 0.00 0.00 0.00 0.00
August 96592.68 07-AUG-04:12 0.00 13741.19 35625.74 0.00 0.00 0.00 0.00 0.00 0.00
September 88690.51 06-SEP-04:12 0.00 13741.19 35625.74 0.00 0.00 0.00 0.00 0.00 0.00
October 83459.63 06-OCT-05:03 6448.95 9160.79 30589.44 0.00 0.00 0.00 0.00 0.00 0.00
November 36101.10 03-NOV-16:00 15316.26 20611.01 17206.56 0.00 0.00 0.00 0.00 0.00 0.00
December 20288.84 20-DEC-17:00 30632.53 41222.03 34413.13 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 20288.84   0.00 9160.79 17206.56 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 96592.68   30632.53 41222.03 38236.81 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 2916.26 31-JAN-13:20 5769.33 3693.99 6481.66 0.00 0.00 0.00 0.00 0.00 245.28
February 3124.32 20-FEB-14:02 404.87 273.61 2880.74 0.00 0.00 0.00 0.00 0.00 494.30
March 6676.56 27-MAR-13:30 2010.79 1231.33 2160.55 0.00 0.00 0.00 0.00 0.00 29.38
April 8174.60 26-APR-13:40 2010.79 1231.33 2160.55 0.00 0.00 0.00 0.00 0.00 52.11
May 14546.99 30-MAY-04:12 0.00 1725.34 4473.37 0.00 0.00 0.00 0.00 0.00 115.93
June 15761.96 18-JUN-17:01 0.00 684.02 5591.71 0.00 0.00 0.00 0.00 0.00 93.62
July 19026.12 09-JUL-15:01 910.95 615.62 6481.66 0.00 0.00 0.00 0.00 0.00 9.68
August 18328.45 13-AUG-15:11 708.51 478.82 5041.29 0.00 0.00 0.00 0.00 95.22 0.00
September 14071.81 02-SEP-04:11 0.00 1006.34 3914.20 0.00 0.00 0.00 0.00 0.00 82.86
October 7765.67 04-OCT-13:10 2010.79 1231.33 2160.55 0.00 0.00 0.00 0.00 8.05 0.00
November 5310.01 03-NOV-13:30 2010.79 1231.33 2160.55 0.00 0.00 0.00 0.00 0.00 36.83
December 3046.73 17-DEC-12:51 708.51 478.82 5041.29 0.00 0.00 0.00 0.00 0.00 284.98
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 2916.26   0.00 273.61 2160.55 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 19026.12   5769.33 3693.99 6481.66 0.00 0.00 0.00 0.00 95.22 494.30



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 5015.29 19-JAN-09:30 2478.65 1587.03 2784.68 0.00 0.00 0.00 0.00 0.00 127.68
February 7063.99 22-FEB-09:15 2478.65 1587.03 2784.68 0.00 0.00 0.00 0.00 0.00 211.55
March 10496.21 29-MAR-08:35 4957.30 3174.07 5569.37 0.00 0.00 0.00 0.00 0.00 108.34
April 23826.63 16-APR-09:22 326.14 220.40 2320.57 0.00 0.00 0.00 0.00 0.00 329.96
May 24889.16 21-MAY-08:62 391.37 264.49 2784.68 0.00 0.00 0.00 0.00 0.00 248.36
June 23652.77 25-JUN-08:42 326.14 220.40 2320.57 0.00 0.00 0.00 0.00 0.00 35.81
July 26506.09 09-JUL-08:21 587.05 396.73 4177.03 0.00 0.00 0.00 0.00 0.00 14.25
August 23925.38 20-AUG-10:12 391.37 264.49 2784.68 0.00 0.00 0.00 0.00 0.00 67.73
September 27251.42 04-SEP-08:41 587.05 396.73 4177.03 0.00 0.00 0.00 0.00 0.00 59.15
October 15635.08 22-OCT-10:02 326.14 220.40 2320.57 0.00 0.00 0.00 0.00 0.00 87.39
November 7339.98 02-NOV-08:50 1239.33 793.52 1392.34 0.00 0.00 0.00 0.00 0.00 134.99
December 5451.50 20-DEC-09:30 1239.33 793.52 1392.34 0.00 0.00 0.00 0.00 0.00 44.41
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 5015.29   326.14 220.40 1392.34 0.00 0.00 0.00 0.00 0.00 14.25
Maximum of Months 27251.42   4957.30 3174.07 5569.37 0.00 0.00 0.00 0.00 0.00 329.96



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 22452.08 31-JAN-13:30 5769.46 3694.08 6481.75 0.00 0.00 0.00 0.00 0.00 254.10
February 26807.62 19-FEB-12:32 404.87 273.61 2880.78 0.00 0.00 0.00 0.00 0.00 515.05
March 20727.07 01-MAR-13:05 3846.30 2462.72 4321.17 0.00 0.00 0.00 0.00 0.00 86.57
April 26736.12 16-APR-12:02 404.87 273.61 2880.78 0.00 0.00 0.00 0.00 0.00 356.11
May 26768.21 29-MAY-12:02 506.09 342.02 3600.97 0.00 0.00 0.00 0.00 72.83 0.00
June 26774.79 18-JUN-14:21 708.53 478.83 5041.36 0.00 0.00 0.00 0.00 0.00 37.85
July 28633.46 30-JUL-14:21 809.75 547.23 5761.56 0.00 0.00 0.00 0.00 0.00 77.79
August 29120.78 20-AUG-13:31 708.53 478.83 5041.36 0.00 0.00 0.00 0.00 1.22 0.00
September 30707.67 04-SEP-14:01 809.75 547.23 5761.56 0.00 0.00 0.00 0.00 0.00 125.77
October 30462.60 22-OCT-12:41 708.53 478.83 5041.36 0.00 0.00 0.00 0.00 0.00 29.21
November 21842.62 02-NOV-12:40 1923.15 1231.36 2160.58 0.00 0.00 0.00 0.00 0.00 107.41
December 29868.57 17-DEC-12:51 708.53 478.83 5041.36 0.00 0.00 0.00 0.00 0.00 436.43
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 20727.07   404.87 273.61 2160.58 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 30707.67   5769.46 3694.08 6481.75 0.00 0.00 0.00 0.00 72.83 515.05



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 7402.59 20-JAN-15:30 1239.33 793.52 1392.33 0.00 0.00 0.00 0.00 0.00 80.18
February 10474.83 24-FEB-15:30 1239.33 793.52 1392.33 0.00 0.00 0.00 0.00 0.00 185.05
March 18716.27 26-MAR-16:22 326.14 220.40 2320.55 0.00 0.00 0.00 0.00 0.00 325.59
April 30167.89 09-APR-16:21 456.59 308.57 3248.78 0.00 0.00 0.00 0.00 0.00 182.63
May 30583.14 21-MAY-15:21 456.59 308.57 3248.78 0.00 0.00 0.00 0.00 0.00 247.93
June 34144.98 18-JUN-15:41 652.28 440.81 4641.11 0.00 0.00 0.00 0.00 0.00 138.50
July 33886.28 04-JUL-16:21 652.28 440.81 4641.11 0.00 0.00 0.00 0.00 0.00 113.04
August 30332.61 13-AUG-15:51 456.59 308.57 3248.78 0.00 0.00 0.00 0.00 33.65 0.00
September 33073.52 10-SEP-15:31 587.05 396.73 4177.00 0.00 0.00 0.00 0.00 0.00 175.17
October 23533.52 15-OCT-15:12 326.14 220.40 2320.55 0.00 0.00 0.00 0.00 0.00 276.43
November 11173.36 02-NOV-14:30 1239.33 793.52 1392.33 0.00 0.00 0.00 0.00 0.00 64.56
December 16338.00 17-DEC-14:12 391.37 264.49 2784.67 0.00 0.00 0.00 0.00 0.00 383.66
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 7402.59   326.14 220.40 1392.33 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 34144.98   1239.33 793.52 4641.11 0.00 0.00 0.00 0.00 33.65 383.66



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 3054.42 20-JAN-16:50 3846.22 5175.84 4321.10 0.00 0.00 0.00 0.00 0.00 306.45
February 3000.58 01-FEB-14:50 4021.58 2462.66 4321.10 0.00 0.00 0.00 0.00 0.00 265.42
March 3962.33 14-MAR-10:13 5769.33 3693.99 6481.66 0.00 0.00 0.00 0.00 0.00 350.75
April 6381.65 07-APR-14:30 1923.11 1231.33 2160.55 0.00 0.00 0.00 0.00 50.09 0.00
May 13259.58 31-MAY-05:03 809.73 547.28 3840.98 0.00 0.00 0.00 0.00 0.00 0.00
June 13941.27 22-JUN-05:03 809.73 547.28 3840.98 0.00 0.00 0.00 0.00 0.00 40.55
July 18243.26 09-JUL-15:01 910.95 615.62 6481.66 0.00 0.00 0.00 0.00 0.00 33.23
August 18331.24 13-AUG-15:01 1012.16 684.02 7201.84 0.00 0.00 0.00 0.00 174.02 0.00
September 13446.21 02-SEP-05:03 809.73 1150.23 3840.98 0.00 0.00 0.00 0.00 0.00 45.05
October 6524.44 05-OCT-14:00 2010.79 1231.33 2160.55 0.00 0.00 0.00 0.00 0.00 17.60
November 3064.79 02-NOV-14:20 1923.11 1231.33 2160.55 0.00 0.00 0.00 0.00 0.00 204.22
December 2258.67 20-DEC-13:10 1923.11 1231.33 2160.55 0.00 0.00 0.00 0.00 0.00 209.67
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 2258.67   809.73 547.28 2160.55 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 18331.24   5769.33 5175.84 7201.84 0.00 0.00 0.00 0.00 174.02 350.75



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 4421.12 19-JAN-09:35 2478.65 1587.03 2784.68 0.00 0.00 0.00 0.00 0.00 297.79
February 5109.34 22-FEB-10:25 0.00 3174.07 5569.37 0.00 0.00 0.00 0.00 0.00 417.00
March 12606.41 29-MAR-08:35 4957.30 3174.07 5569.37 0.00 0.00 0.00 0.00 0.00 250.90
April 19087.67 23-APR-09:32 260.91 176.32 1856.46 0.00 0.00 0.00 0.00 0.00 795.91
May 29732.80 29-MAY-08:31 587.05 396.73 4177.03 0.00 0.00 0.00 0.00 0.00 177.79
June 28777.49 25-JUN-08:31 521.82 352.65 3712.91 0.00 0.00 0.00 0.00 0.00 193.55
July 30479.45 02-JUL-08:51 652.28 440.81 4641.14 0.00 0.00 0.00 0.00 0.00 182.36
August 27071.23 20-AUG-09:41 456.59 308.57 3248.80 0.00 0.00 0.00 0.00 0.00 277.92
September 29202.11 04-SEP-08:51 587.05 396.73 4177.03 0.00 0.00 0.00 0.00 0.00 166.82
October 14597.97 15-OCT-10:22 391.37 264.49 2784.68 0.00 0.00 0.00 0.00 0.00 609.23
November 5354.32 02-NOV-09:00 1239.33 793.52 1392.34 0.00 0.00 0.00 0.00 0.00 334.91
December 3219.89 20-DEC-09:35 2478.65 1587.03 2784.68 0.00 0.00 0.00 0.00 0.00 101.16
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 3219.89   0.00 176.32 1392.34 0.00 0.00 0.00 0.00 0.00 101.16
Maximum of Months 30479.45   4957.30 3174.07 5569.37 0.00 0.00 0.00 0.00 0.00 795.91



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 22142.64 31-JAN-13:37 11538.91 7388.15 12963.51 0.00 0.00 0.00 0.00 0.00 578.30
February 26741.27 20-FEB-13:43 404.87 273.61 2880.78 0.00 0.00 0.00 0.00 0.00 1433.23
March 21344.53 01-MAR-13:30 3846.30 2462.72 4321.17 0.00 0.00 0.00 0.00 0.00 207.13
April 22806.45 09-APR-13:23 404.87 273.61 2880.78 0.00 0.00 0.00 0.00 0.00 692.20
May 28678.09 29-MAY-12:32 607.31 410.42 4321.17 0.00 0.00 0.00 0.00 0.00 46.04
June 26951.82 25-JUN-12:32 506.09 342.02 3600.97 0.00 0.00 0.00 0.00 0.00 81.49
July 28695.27 09-JUL-13:41 708.53 478.83 5041.36 0.00 0.00 0.00 0.00 292.81 0.00
August 29642.71 20-AUG-13:01 708.53 478.83 5041.36 0.00 0.00 0.00 0.00 0.00 48.29
September 32458.84 04-SEP-12:11 910.97 615.63 6481.75 0.00 0.00 0.00 0.00 0.00 248.24
October 30923.59 22-OCT-12:11 708.53 478.83 5041.36 0.00 0.00 0.00 0.00 0.00 310.14
November 22420.09 02-NOV-13:10 2010.83 1231.36 2160.58 0.00 0.00 0.00 0.00 0.00 245.98
December 27326.17 17-DEC-13:02 506.09 342.02 3600.97 0.00 0.00 0.00 0.00 0.00 1018.42
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 21344.53   404.87 273.61 2160.58 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 32458.84   11538.91 7388.15 12963.51 0.00 0.00 0.00 0.00 292.81 1433.23



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 4414.00 31-JAN-16:00 1239.33 793.52 1392.33 0.00 0.00 0.00 0.00 0.00 0.00
February 7424.12 22-FEB-16:00 3717.98 2380.55 4177.00 0.00 0.00 0.00 0.00 0.00 270.89
March 11835.40 29-MAR-16:00 1239.33 793.52 1392.33 0.00 0.00 0.00 0.00 0.00 314.09
April 28381.53 09-APR-16:01 456.59 308.57 3248.78 0.00 0.00 0.00 0.00 0.00 535.88
May 27596.76 28-MAY-14:51 456.59 308.57 3248.78 0.00 0.00 0.00 0.00 0.00 79.17
June 31717.99 18-JUN-16:21 652.28 440.81 4641.11 0.00 0.00 0.00 0.00 0.00 361.92
July 31518.25 02-JUL-16:11 652.28 440.81 4641.11 0.00 0.00 0.00 0.00 0.00 442.90
August 30766.99 13-AUG-15:41 652.28 440.81 4641.11 0.00 0.00 0.00 0.00 3.98 0.00
September 29048.97 03-SEP-16:11 521.82 352.65 3712.89 0.00 0.00 0.00 0.00 0.00 163.40
October 23816.39 15-OCT-15:41 456.59 308.57 3248.78 0.00 0.00 0.00 0.00 0.00 597.34
November 7651.24 03-NOV-15:30 1239.33 793.52 1392.33 0.00 0.00 0.00 0.00 0.00 71.24
December 4619.76 18-DEC-16:25 2478.65 3335.51 2784.67 0.00 0.00 0.00 0.00 0.00 260.46
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 4414.00   456.59 308.57 1392.33 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 31717.99   3717.98 3335.51 4641.11 0.00 0.00 0.00 0.00 3.98 597.34



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 1767.58 20-JAN-15:30 1923.11 1231.33 2160.55 0.00 0.00 0.00 0.00 0.00 299.93
February 1796.74 24-FEB-15:40 1923.11 1231.33 2160.55 0.00 0.00 0.00 0.00 0.00 697.37
March 3007.20 28-MAR-14:00 2010.79 1231.33 2160.55 0.00 0.00 0.00 0.00 0.00 429.30
April 7032.72 07-APR-14:00 2010.79 1231.33 2160.55 0.00 0.00 0.00 0.00 69.70 0.00
May 15032.18 30-MAY-05:03 809.73 547.28 3840.98 0.00 0.00 0.00 0.00 0.00 68.59
June 20119.21 25-JUN-16:31 910.95 615.62 6481.66 0.00 0.00 0.00 0.00 0.00 230.74
July 19966.86 16-JUL-17:42 0.00 342.01 2795.85 0.00 0.00 0.00 0.00 180.38 0.00
August 21291.44 13-AUG-15:01 1012.16 684.02 7201.84 0.00 0.00 0.00 0.00 177.66 0.00
September 14444.35 02-SEP-04:11 0.00 1006.34 3914.20 0.00 0.00 0.00 0.00 0.00 228.61
October 6886.71 04-OCT-13:40 2010.79 1231.33 2160.55 0.00 0.00 0.00 0.00 8.89 0.00
November 2956.24 02-NOV-13:40 2010.79 1231.33 2160.55 0.00 0.00 0.00 0.00 0.00 238.38
December 1753.66 20-DEC-13:40 1923.11 1231.33 2160.55 0.00 0.00 0.00 0.00 0.00 298.41
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 1753.66   0.00 342.01 2160.55 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 21291.44   2010.79 1231.33 7201.84 0.00 0.00 0.00 0.00 180.38 697.37



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 2578.11 19-JAN-10:10 1295.83 793.52 1392.34 0.00 0.00 0.00 0.00 0.00 410.62
February 2705.88 22-FEB-10:10 1295.83 793.52 1392.34 0.00 0.00 0.00 0.00 0.00 526.15
March 7846.48 29-MAR-09:30 1295.83 793.52 1392.34 0.00 0.00 0.00 0.00 0.00 277.35
April 12496.28 28-APR-08:50 1239.33 793.52 1392.34 0.00 0.00 0.00 0.00 0.00 146.21
May 27920.97 28-MAY-09:01 456.59 308.57 3248.80 0.00 0.00 0.00 0.00 0.00 540.87
June 29309.58 25-JUN-08:31 521.82 352.65 3712.91 0.00 0.00 0.00 0.00 0.00 248.53
July 27955.45 02-JUL-08:21 587.05 396.73 4177.03 0.00 0.00 0.00 0.00 0.00 153.64
August 26543.13 13-AUG-09:01 456.59 308.57 3248.80 0.00 0.00 0.00 0.00 11.21 0.00
September 28523.96 10-SEP-08:41 521.82 352.65 3712.91 0.00 0.00 0.00 0.00 0.00 693.93
October 10499.54 05-OCT-09:10 1295.83 793.52 1392.34 0.00 0.00 0.00 0.00 0.00 83.34
November 3975.14 03-NOV-09:30 1295.83 793.52 1392.34 0.00 0.00 0.00 0.00 0.00 155.31
December 2571.03 20-DEC-09:35 2478.65 1587.03 2784.68 0.00 0.00 0.00 0.00 0.00 118.93
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 2571.03   456.59 308.57 1392.34 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 29309.58   2478.65 1587.03 4177.03 0.00 0.00 0.00 0.00 11.21 693.93



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 16346.22 19-JAN-13:30 1923.15 1231.36 2160.58 0.00 0.00 0.00 0.00 0.00 705.69
February 17017.25 22-FEB-13:30 1923.15 1231.36 2160.58 0.00 0.00 0.00 0.00 0.00 538.57
March 21616.86 01-MAR-13:30 3846.30 2462.72 4321.17 0.00 0.00 0.00 0.00 0.00 257.41
April 20168.71 07-APR-12:30 1923.15 1231.36 2160.58 0.00 0.00 0.00 0.00 61.23 0.00
May 29193.99 28-MAY-13:02 506.09 342.02 3600.97 0.00 0.00 0.00 0.00 0.00 235.48
June 29240.85 25-JUN-13:12 506.09 342.02 3600.97 0.00 0.00 0.00 0.00 0.00 140.89
July 29112.64 30-JUL-13:12 506.09 342.02 3600.97 0.00 0.00 0.00 0.00 0.00 4.79
August 32715.92 13-AUG-15:01 1012.19 684.04 7201.95 0.00 0.00 0.00 0.00 89.57 0.00
September 32971.64 10-SEP-14:41 809.75 547.23 5761.56 0.00 0.00 0.00 0.00 0.00 711.39
October 32583.50 15-OCT-12:51 708.53 478.83 5041.36 0.00 0.00 0.00 0.00 0.00 1632.27
November 23028.14 02-NOV-13:10 2010.83 1231.36 2160.58 0.00 0.00 0.00 0.00 0.00 290.22
December 29913.33 17-DEC-12:51 708.53 478.83 5041.36 0.00 0.00 0.00 0.00 0.00 1204.16
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 16346.22   506.09 342.02 2160.58 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 32971.64   3846.30 2462.72 7201.95 0.00 0.00 0.00 0.00 89.57 1632.27



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 3805.89 19-JAN-15:40 1239.33 793.52 1392.33 0.00 0.00 0.00 0.00 0.00 522.88
February 5823.67 22-FEB-16:10 1239.33 793.52 1392.33 0.00 0.00 0.00 0.00 0.00 341.36
March 11619.50 29-MAR-16:00 1239.33 793.52 1392.33 0.00 0.00 0.00 0.00 0.00 392.49
April 28759.00 09-APR-16:11 652.28 440.81 4641.11 0.00 0.00 0.00 0.00 0.00 579.70
May 29241.87 28-MAY-15:01 456.59 308.57 3248.78 0.00 0.00 0.00 0.00 0.00 143.89
June 31661.76 25-JUN-16:31 587.05 396.73 4177.00 0.00 0.00 0.00 0.00 0.00 382.74
July 33303.94 02-JUL-16:21 652.28 440.81 4641.11 0.00 0.00 0.00 0.00 0.00 599.21
August 33171.55 13-AUG-15:41 652.28 440.81 4641.11 0.00 0.00 0.00 0.00 0.00 15.77
September 32126.79 10-SEP-16:41 587.05 396.73 4177.00 0.00 0.00 0.00 0.00 0.00 623.77
October 24777.89 15-OCT-14:52 391.37 264.49 2784.67 0.00 0.00 0.00 0.00 0.00 840.84
November 7330.69 03-NOV-15:30 1239.33 793.52 1392.33 0.00 0.00 0.00 0.00 0.00 89.65
December 3322.13 17-DEC-14:12 391.37 264.49 2784.67 0.00 0.00 0.00 0.00 0.00 728.18
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 3322.13   391.37 264.49 1392.33 0.00 0.00 0.00 0.00 0.00 15.77
Maximum of Months 33303.94   1239.33 793.52 4641.11 0.00 0.00 0.00 0.00 0.00 840.84



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: GROUNDFLOOR_PLENUM

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 6002.89 31-JAN-06:01 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 760.67
February 7677.68 06-FEB-05:01 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 4461.76
March 4921.16 29-MAR-05:08 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 441.86
April 7790.25 10-APR-14:20 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 123.07
May 11632.15 30-MAY-05:15 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 51.55
June 10353.64 26-JUN-05:15 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 70.61
July 12769.28 10-JUL-05:15 0.00 0.00 0.00 0.00 0.00 0.00 0.00 12.68 0.00
August 10873.18 14-AUG-14:40 0.00 0.00 0.00 0.00 0.00 0.00 0.00 81.85 0.00
September 14473.71 05-SEP-05:02 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 48.98
October 8020.32 16-OCT-05:15 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 177.68
November 6663.34 13-NOV-06:08 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 228.36
December 4151.74 21-DEC-06:07 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 392.26
                       
Annual Sum or Average     0.00 0.00 0.00 0.00 0.00 0.00 0.00    
Minimum of Months 4151.74   0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 14473.71   0.00 0.00 0.00 0.00 0.00 0.00 0.00 81.85 4461.76



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: MIDFLOOR_PLENUM

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 11347.95 31-JAN-04:01 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 6533.51
February 10120.40 09-FEB-04:01 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 5375.61
March 9919.97 17-MAR-04:01 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 4010.64
April 7295.08 21-APR-04:11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 4525.06
May 8351.10 30-MAY-13:20 0.00 0.00 0.00 0.00 0.00 0.00 0.00 157.76 0.00
June 9559.18 01-JUN-15:17 0.00 0.00 0.00 0.00 0.00 0.00 0.00 236.28 0.00
July 9780.27 11-JUL-15:40 0.00 0.00 0.00 0.00 0.00 0.00 0.00 84.65 0.00
August 9701.29 22-AUG-15:17 0.00 0.00 0.00 0.00 0.00 0.00 0.00 204.70 0.00
September 8494.89 05-SEP-15:30 0.00 0.00 0.00 0.00 0.00 0.00 0.00 38.35 0.00
October 5817.57 05-OCT-15:40 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 126.41
November 8957.21 24-NOV-04:01 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 2540.95
December 9183.24 23-DEC-05:11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 3772.04
                       
Annual Sum or Average     0.00 0.00 0.00 0.00 0.00 0.00 0.00    
Minimum of Months 5817.57   0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 11347.95   0.00 0.00 0.00 0.00 0.00 0.00 0.00 236.28 6533.51



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: TOPFLOOR_PLENUM

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 222.15 19-JAN-13:10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1036.09
February 1372.05 17-FEB-13:05 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 509.99
March 7767.60 03-MAR-14:40 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 714.48
April 15777.25 07-APR-13:20 0.00 0.00 0.00 0.00 0.00 0.00 0.00 33.46 0.00
May 23266.47 30-MAY-13:30 0.00 0.00 0.00 0.00 0.00 0.00 0.00 139.68 0.00
June 23583.74 19-JUN-13:30 0.00 0.00 0.00 0.00 0.00 0.00 0.00 317.73 0.00
July 22411.20 10-JUL-13:50 0.00 0.00 0.00 0.00 0.00 0.00 0.00 352.77 0.00
August 22147.74 22-AUG-14:25 0.00 0.00 0.00 0.00 0.00 0.00 0.00 254.61 0.00
September 20649.57 01-SEP-13:30 0.00 0.00 0.00 0.00 0.00 0.00 0.00 184.74 0.00
October 12957.92 04-OCT-15:10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 78.17
November 5286.92 03-NOV-14:20 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 143.11
December 1358.75 17-DEC-13:44 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1387.36
                       
Annual Sum or Average     0.00 0.00 0.00 0.00 0.00 0.00 0.00    
Minimum of Months 222.15   0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 23583.74   0.00 0.00 0.00 0.00 0.00 0.00 0.00 352.77 1387.36



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 2224.97 20-JAN-16:30 222.14 578.72 1948.61 0.00 0.00 0.00 0.00 0.00 0.00
February 4400.05 14-FEB-17:00 222.14 578.72 3897.21 0.00 0.00 0.00 0.00 0.00 0.00
March 6951.38 31-MAR-24:00 0.00 32.15 7794.42 0.00 0.00 0.00 0.00 0.00 0.00
April 8426.30 23-APR-17:44 0.00 225.07 54560.95 0.00 0.00 0.00 0.00 0.00 0.00
May 3550.57 31-MAY-24:00 0.00 32.15 3897.21 0.00 0.00 0.00 0.00 0.00 0.00
June 5370.07 30-JUN-24:00 0.00 32.15 5845.82 0.00 0.00 0.00 0.00 0.00 0.00
July 7261.65 31-JUL-23:53 0.00 96.46 23383.27 0.00 0.00 0.00 0.00 0.00 0.00
August 8334.58 31-AUG-17:40 23.38 192.90 7794.42 0.00 0.00 0.00 0.00 0.00 0.00
September 3408.96 30-SEP-24:00 0.00 32.15 3897.21 0.00 0.00 0.00 0.00 0.00 0.00
October 5150.22 31-OCT-24:00 0.00 32.15 5845.82 0.00 0.00 0.00 0.00 0.00 0.00
November 6139.89 03-NOV-16:00 222.14 578.72 5845.82 0.00 0.00 0.00 0.00 0.00 0.00
December 8043.24 08-DEC-16:00 222.14 578.72 7794.42 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 2224.97   0.00 32.15 1948.61 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 8426.30   222.14 578.72 54560.95 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: DATACENTER_MID_ZN_6

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 1900.36 20-JAN-16:30 222.14 578.72 1948.61 0.00 0.00 0.00 0.00 0.00 0.00
February 3922.03 22-FEB-17:00 222.14 578.72 3897.21 0.00 0.00 0.00 0.00 0.00 0.00
March 6034.63 31-MAR-23:30 0.00 32.15 7794.42 0.00 0.00 0.00 0.00 0.00 0.00
April 7746.05 09-APR-17:31 0.00 225.07 54560.95 0.00 0.00 0.00 0.00 0.00 0.00
May 3370.79 31-MAY-24:00 0.00 32.15 3897.21 0.00 0.00 0.00 0.00 0.00 0.00
June 5053.02 30-JUN-24:00 0.00 32.15 5845.82 0.00 0.00 0.00 0.00 0.00 0.00
July 6981.10 31-JUL-24:00 0.00 96.46 23383.27 0.00 0.00 0.00 0.00 0.00 0.00
August 7987.24 31-AUG-17:30 23.38 192.90 7794.42 0.00 0.00 0.00 0.00 0.00 0.00
September 3066.13 30-SEP-23:30 0.00 32.15 3897.21 0.00 0.00 0.00 0.00 0.00 0.00
October 4392.31 31-OCT-24:00 0.00 32.15 5845.82 0.00 0.00 0.00 0.00 0.00 0.00
November 5743.49 03-NOV-16:00 222.14 578.72 5845.82 0.00 0.00 0.00 0.00 0.00 0.00
December 7377.63 08-DEC-16:10 222.14 578.72 7794.42 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 1900.36   0.00 32.15 1948.61 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 7987.24   222.14 578.72 54560.95 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 1852.20 20-JAN-16:40 222.14 578.72 1948.61 0.00 0.00 0.00 0.00 0.00 0.00
February 3860.49 22-FEB-17:00 222.14 578.72 3897.21 0.00 0.00 0.00 0.00 0.00 0.00
March 5929.46 29-MAR-17:20 23.38 192.90 5845.82 0.00 0.00 0.00 0.00 0.00 0.00
April 7769.57 09-APR-17:22 0.00 160.76 38972.11 0.00 0.00 0.00 0.00 0.00 0.00
May 3324.43 31-MAY-24:00 0.00 32.15 3897.21 0.00 0.00 0.00 0.00 0.00 0.00
June 4965.05 30-JUN-24:00 0.00 32.15 5845.82 0.00 0.00 0.00 0.00 0.00 0.00
July 6975.58 31-JUL-24:00 0.00 96.46 23383.27 0.00 0.00 0.00 0.00 0.00 0.00
August 8099.81 31-AUG-17:30 23.38 192.90 7794.42 0.00 0.00 0.00 0.00 0.00 0.00
September 2827.51 10-SEP-17:33 0.00 225.07 13640.24 0.00 0.00 0.00 0.00 0.00 0.00
October 4229.43 04-OCT-16:30 70.15 321.51 3897.21 0.00 0.00 0.00 0.00 0.00 0.00
November 5729.08 03-NOV-16:00 222.14 578.72 5845.82 0.00 0.00 0.00 0.00 0.00 0.00
December 7251.82 08-DEC-16:10 222.14 578.72 7794.42 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 1852.20   0.00 32.15 1948.61 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 8099.81   222.14 578.72 38972.11 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 92483.74 20-JAN-17:00 9617.36 12942.03 189816.26 0.00 0.00 0.00 0.00 0.00 0.00
February 183910.69 22-FEB-17:00 4808.68 6471.01 189816.26 0.00 0.00 0.00 0.00 0.00 0.00
March 358621.43 31-MAR-24:00 0.00 359.47 379632.52 0.00 0.00 0.00 0.00 0.00 0.00
April 368668.45 10-APR-16:00 4808.68 6471.01 379632.52 0.00 0.00 0.00 0.00 0.00 0.00
May 176659.38 31-MAY-24:00 0.00 359.47 189816.26 0.00 0.00 0.00 0.00 0.00 0.00
June 268222.88 30-JUN-24:00 0.00 359.47 284724.39 0.00 0.00 0.00 0.00 0.00 0.00
July 360444.63 31-JUL-23:53 0.00 1078.42 1138897.57 0.00 0.00 0.00 0.00 0.00 0.00
August 370533.07 18-AUG-23:03 0.00 1437.90 1518530.09 0.00 0.00 0.00 0.00 0.00 0.00
September 176650.77 30-SEP-24:00 0.00 359.47 189816.26 0.00 0.00 0.00 0.00 0.00 0.00
October 268524.87 31-OCT-24:00 0.00 359.47 284724.39 0.00 0.00 0.00 0.00 0.00 0.00
November 277669.41 03-NOV-16:00 4808.68 6471.01 284724.39 0.00 0.00 0.00 0.00 0.00 0.00
December 368701.89 21-DEC-17:00 4808.68 6471.01 379632.52 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 92483.74   0.00 359.47 189816.26 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 370533.07   9617.36 12942.03 1518530.09 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: EnergyConsumptionElectricityNaturalGasMonthly

For: Meter

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

ELECTRICITY:FACILITY [J] ELECTRICITY:FACILITY {Maximum} [W] ELECTRICITY:FACILITY {TIMESTAMP} NATURALGAS:FACILITY [J] NATURALGAS:FACILITY {Maximum} [W] NATURALGAS:FACILITY {TIMESTAMP}
January 0.163328E+13 1107154.96 26-JAN-16:00 0.491174E+12 1900322.15 02-JAN-05:10
February 0.182495E+13 1187529.27 03-FEB-14:00 0.396519E+12 1884600.36 13-FEB-07:10
March 0.247390E+13 1491498.96 27-MAR-15:00 0.213244E+12 1231628.06 23-MAR-06:10
April 0.279670E+13 1956306.22 07-APR-15:39 0.112489E+12 759651.11 01-APR-06:10
May 0.184255E+13 1583885.77 30-MAY-10:50 0.681729E+11 183708.76 04-MAY-06:10
June 0.249776E+13 1756565.62 20-JUN-15:09 0.642444E+11 240557.90 01-JUN-15:20
July 0.309244E+13 1931810.05 20-JUL-15:09 0.597116E+11 128721.99 12-JUL-11:20
August 0.355746E+13 2113158.43 16-AUG-15:20 0.649183E+11 274060.18 24-AUG-16:40
September 0.194616E+13 1544841.87 07-SEP-15:30 0.591871E+11 135177.99 01-SEP-13:00
October 0.222786E+13 1634849.50 04-OCT-15:00 0.727948E+11 614671.87 28-OCT-06:10
November 0.238835E+13 1442835.99 03-NOV-15:09 0.190289E+12 1303672.14 24-NOV-07:10
December 0.280673E+13 1559486.95 07-DEC-16:00 0.345929E+12 1262120.21 22-DEC-07:10
             
Annual Sum or Average 0.290881E+14     0.213867E+13    
Minimum of Months 0.163328E+13 1107154.96   0.591871E+11 128721.99  
Maximum of Months 0.355746E+13 2113158.43   0.491174E+12 1900322.15  



Table of Contents

Report: EndUseEnergyConsumptionElectricityMonthly

For: Meter

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

INTERIORLIGHTS:ELECTRICITY [J] EXTERIORLIGHTS:ELECTRICITY [J] INTERIOREQUIPMENT:ELECTRICITY [J] EXTERIOREQUIPMENT:ELECTRICITY [J] FANS:ELECTRICITY [J] PUMPS:ELECTRICITY [J] HEATING:ELECTRICITY [J] COOLING:ELECTRICITY [J] HEATREJECTION:ELECTRICITY [J] HUMIDIFIER:ELECTRICITY [J] HEATRECOVERY:ELECTRICITY [J] WATERSYSTEMS:ELECTRICITY [] COGENERATION:ELECTRICITY []
January 0.335287E+12 0.757660E+11 0.766053E+12 0.164272E+12 0.171442E+12 0.158730E+11 0.00 0.846001E+11 0.102807E+11 0.294124E+10 0.676542E+10 0.00 0.00
February 0.299993E+12 0.623901E+11 0.978954E+12 0.148382E+12 0.155886E+12 0.154921E+11 0.00 0.139859E+12 0.144266E+11 0.344346E+10 0.612279E+10 0.00 0.00
March 0.352758E+12 0.607720E+11 0.141687E+13 0.164522E+12 0.179471E+12 0.172474E+11 0.00 0.225813E+12 0.491611E+11 0.199087E+10 0.529439E+10 0.00 0.00
April 0.313000E+12 0.504978E+11 0.165903E+13 0.158945E+12 0.183784E+12 0.222401E+11 0.00 0.307466E+12 0.978482E+11 0.799829E+09 0.309172E+10 0.00 0.00
May 0.336391E+12 0.458469E+11 0.774844E+12 0.164394E+12 0.211004E+12 0.413328E+11 0.00 0.177708E+12 0.901171E+11 0.169066E+09 0.746592E+09 0.00 0.00
June 0.333950E+12 0.412145E+11 0.106252E+13 0.159182E+12 0.242169E+12 0.668399E+11 0.00 0.423114E+12 0.164057E+12 0.00 0.471167E+10 0.00 0.00
July 0.313042E+12 0.436305E+11 0.139340E+13 0.164155E+12 0.261576E+12 0.849942E+11 0.00 0.625407E+12 0.199262E+12 0.00 0.697044E+10 0.00 0.00
August 0.349342E+12 0.488980E+11 0.173200E+13 0.164521E+12 0.279286E+12 0.878284E+11 0.00 0.704023E+12 0.185869E+12 0.00 0.569590E+10 0.00 0.00
September 0.313945E+12 0.551618E+11 0.740713E+12 0.158944E+12 0.215410E+12 0.550675E+11 0.00 0.269272E+12 0.134781E+12 25412889.31 0.283873E+10 0.00 0.00
October 0.328155E+12 0.656434E+11 0.108340E+13 0.164268E+12 0.201391E+12 0.354297E+11 0.00 0.246471E+12 0.100713E+12 0.671699E+09 0.171941E+10 0.00 0.00
November 0.329624E+12 0.711231E+11 0.135889E+13 0.159045E+12 0.169105E+12 0.161137E+11 0.00 0.218607E+12 0.603453E+11 0.124655E+10 0.424871E+10 0.00 0.00
December 0.325319E+12 0.775971E+11 0.170972E+13 0.164161E+12 0.169297E+12 0.179912E+11 0.00 0.281233E+12 0.523061E+11 0.294612E+10 0.615832E+10 0.00 0.00
                           
Annual Sum or Average 0.393081E+13 0.698541E+12 0.146764E+14 0.193479E+13 0.243982E+13 0.476450E+12 0.00 0.370358E+13 0.115917E+13 0.142343E+11 0.543641E+11 0.00 0.00
Minimum of Months 0.299993E+12 0.412145E+11 0.740713E+12 0.148382E+12 0.155886E+12 0.154921E+11 0.00 0.846001E+11 0.102807E+11 0.00 0.746592E+09 0.00 0.00
Maximum of Months 0.352758E+12 0.775971E+11 0.173200E+13 0.164522E+12 0.279286E+12 0.878284E+11 0.00 0.704023E+12 0.199262E+12 0.344346E+10 0.697044E+10 0.00 0.00



Table of Contents

Report: EndUseEnergyConsumptionNaturalGasMonthly

For: Meter

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

INTERIOREQUIPMENT:NATURALGAS [] EXTERIOREQUIPMENT:NATURALGAS [] HEATING:NATURALGAS [J] COOLING:NATURALGAS [] WATERSYSTEMS:NATURALGAS [J] COGENERATION:NATURALGAS [] HUMIDIFIER:NATURALGAS []
January 0.00 0.00 0.419622E+12 0.00 0.715525E+11 0.00 0.00
February 0.00 0.00 0.331187E+12 0.00 0.653314E+11 0.00 0.00
March 0.00 0.00 0.139014E+12 0.00 0.742292E+11 0.00 0.00
April 0.00 0.00 0.461638E+11 0.00 0.663249E+11 0.00 0.00
May 0.00 0.00 0.136112E+10 0.00 0.668118E+11 0.00 0.00
June 0.00 0.00 0.171207E+10 0.00 0.625324E+11 0.00 0.00
July 0.00 0.00 0.447481E+09 0.00 0.592641E+11 0.00 0.00
August 0.00 0.00 0.275238E+10 0.00 0.621659E+11 0.00 0.00
September 0.00 0.00 0.278408E+09 0.00 0.589087E+11 0.00 0.00
October 0.00 0.00 0.949061E+10 0.00 0.633042E+11 0.00 0.00
November 0.00 0.00 0.125381E+12 0.00 0.649082E+11 0.00 0.00
December 0.00 0.00 0.277555E+12 0.00 0.683732E+11 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.135497E+13 0.00 0.783707E+12 0.00 0.00
Minimum of Months 0.00 0.00 0.278408E+09 0.00 0.589087E+11 0.00 0.00
Maximum of Months 0.00 0.00 0.419622E+12 0.00 0.742292E+11 0.00 0.00



Table of Contents

Report: PeakEnergyEndUseElectricityPart1Monthly

For: Meter

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

INTERIORLIGHTS:ELECTRICITY {Maximum} [W] INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} EXTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] EXTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} FANS:ELECTRICITY {Maximum} [W] FANS:ELECTRICITY {TIMESTAMP} PUMPS:ELECTRICITY {Maximum} [W] PUMPS:ELECTRICITY {TIMESTAMP} HEATING:ELECTRICITY {Maximum} [W] HEATING:ELECTRICITY {TIMESTAMP}
January 385834.94 02-JAN-16:30 57580.60 01-JAN-06:10 423497.50 02-JAN-08:09 118525.16 03-JAN-08:20 140487.95 27-JAN-14:39 32291.38 11-JAN-06:10 0.00 01-JAN-00:10
February 385834.94 15-FEB-16:00 57580.60 01-FEB-06:10 541788.89 01-FEB-08:09 118506.10 28-FEB-08:20 197817.67 03-FEB-14:00 33428.28 06-FEB-06:00 0.00 01-FEB-00:10
March 353932.91 02-MAR-16:00 57580.60 01-MAR-06:10 660080.29 01-MAR-08:09 118509.21 16-MAR-07:19 260515.70 17-MAR-15:30 32009.84 17-MAR-10:39 0.00 01-MAR-00:10
April 337087.14 21-APR-07:10 57580.60 01-APR-05:10 778371.69 03-APR-07:10 118497.37 21-APR-07:19 248610.52 07-APR-14:50 65858.97 07-APR-14:50 0.00 01-APR-00:10
May 337934.08 08-MAY-07:10 57580.60 01-MAY-18:49 423497.50 01-MAY-07:10 118498.03 08-MAY-07:19 302144.59 30-MAY-10:50 62689.98 30-MAY-13:30 0.00 01-MAY-00:10
June 336086.21 16-JUN-07:10 57580.60 01-JUN-19:19 541788.89 01-JUN-07:10 118496.59 16-JUN-07:19 313357.58 20-JUN-14:00 62861.84 22-JUN-15:50 0.00 01-JUN-00:10
July 336086.21 24-JUL-07:10 57580.60 01-JUL-19:30 660080.29 03-JUL-07:10 118496.59 24-JUL-07:19 314543.08 11-JUL-14:30 59449.90 11-JUL-15:50 0.00 01-JUL-00:10
August 338173.03 16-AUG-07:10 57580.60 01-AUG-19:10 778371.69 01-AUG-07:10 118498.21 16-AUG-07:19 312055.81 08-AUG-14:30 68118.46 30-AUG-13:39 0.00 01-AUG-00:10
September 348291.11 27-SEP-07:10 57580.60 01-SEP-05:10 423497.50 01-SEP-07:10 118506.10 27-SEP-07:19 241554.97 05-SEP-15:30 64267.98 01-SEP-13:50 0.00 01-SEP-00:10
October 369498.02 31-OCT-15:00 57580.60 01-OCT-05:10 541788.89 02-OCT-07:10 118518.28 06-OCT-07:19 202855.57 05-OCT-15:39 60299.82 24-OCT-13:50 0.00 01-OCT-00:10
November 385834.94 06-NOV-16:40 57580.60 01-NOV-05:10 660080.29 01-NOV-07:10 118525.16 30-NOV-08:20 170069.98 07-NOV-08:50 32148.59 24-NOV-06:19 0.00 01-NOV-00:10
December 385834.94 01-DEC-16:30 57580.60 01-DEC-06:10 778371.69 01-DEC-08:09 118525.16 11-DEC-08:20 134787.65 21-DEC-10:20 31675.51 22-DEC-14:09 0.00 01-DEC-00:10
                             
Annual Sum or Average                            
Minimum of Months 336086.21   57580.60   423497.50   118496.59   134787.65   31675.51   0.00  
Maximum of Months 385834.94   57580.60   778371.69   118525.16   314543.08   68118.46   0.00  



Table of Contents

Report: PeakEnergyEndUseElectricityPart2Monthly

For: Meter

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

COOLING:ELECTRICITY {Maximum} [W] COOLING:ELECTRICITY {TIMESTAMP} HEATREJECTION:ELECTRICITY {Maximum} [W] HEATREJECTION:ELECTRICITY {TIMESTAMP} HUMIDIFIER:ELECTRICITY {Maximum} [W] HUMIDIFIER:ELECTRICITY {TIMESTAMP} HEATRECOVERY:ELECTRICITY {Maximum} [W] HEATRECOVERY:ELECTRICITY {TIMESTAMP} WATERSYSTEMS:ELECTRICITY [] COGENERATION:ELECTRICITY []
January 37334.66 20-JAN-16:49 9619.51 24-JAN-11:00 6186.06 02-JAN-19:00 5613.48 02-JAN-07:10 0.00 0.00
February 68521.36 02-FEB-13:30 17272.33 20-FEB-11:00 6169.59 02-FEB-18:00 5613.48 01-FEB-07:10 0.00 0.00
March 208963.12 27-MAR-15:00 52200.58 27-MAR-15:00 6022.20 22-MAR-17:10 5613.48 01-MAR-07:10 0.00 0.00
April 409591.35 07-APR-14:20 93402.74 07-APR-14:20 5704.48 11-APR-18:00 5613.48 01-APR-06:10 0.00 0.00
May 380732.40 30-MAY-13:30 93402.74 30-MAY-08:00 3341.90 01-MAY-17:00 5613.48 01-MAY-06:10 0.00 0.00
June 407149.79 22-JUN-15:50 93402.74 01-JUN-10:09 0.00 01-JUN-00:10 5613.48 01-JUN-09:00 0.00 0.00
July 455308.70 20-JUL-14:30 93402.74 01-JUL-08:30 0.00 01-JUL-00:10 5613.48 01-JUL-06:10 0.00 0.00
August 548047.79 24-AUG-16:40 93402.74 01-AUG-07:10 0.00 01-AUG-00:10 5613.48 01-AUG-06:10 0.00 0.00
September 360493.53 01-SEP-13:50 93402.74 01-SEP-07:10 1980.27 23-SEP-13:00 5613.48 01-SEP-06:10 0.00 0.00
October 340658.34 04-OCT-13:50 93402.74 03-OCT-10:30 4834.64 28-OCT-16:30 5613.48 03-OCT-11:39 0.00 0.00
November 160959.12 03-NOV-13:00 50020.90 10-NOV-09:00 4840.94 22-NOV-19:00 5613.48 01-NOV-06:10 0.00 0.00
December 114624.57 21-DEC-11:50 45594.72 17-DEC-14:00 6019.12 14-DEC-21:00 5613.48 01-DEC-07:10 0.00 0.00
                     
Annual Sum or Average                 0.00 0.00
Minimum of Months 37334.66   9619.51   0.00   5613.48   0.00 0.00
Maximum of Months 548047.79   93402.74   6186.06   5613.48   0.00 0.00



Table of Contents

Report: ElectricComponentsOfPeakDemandMonthly

For: Meter

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

ELECTRICITY:FACILITY {Maximum} [W] ELECTRICITY:FACILITY {TIMESTAMP} INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] EXTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] FANS:ELECTRICITY {AT MAX/MIN} [W] PUMPS:ELECTRICITY {AT MAX/MIN} [W] HEATING:ELECTRICITY {AT MAX/MIN} [W] COOLING:ELECTRICITY {AT MAX/MIN} [W] HEATREJECTION:ELECTRICITY {AT MAX/MIN} [W]
January 1107154.96 26-JAN-16:00 385834.94 423497.50 57580.60 84492.05 78924.68 29790.03 0.00 36255.25 4551.11
February 1187529.27 03-FEB-14:00 332294.83 541788.89 0.00 39059.06 197817.67 4941.96 0.00 59584.07 5350.72
March 1491498.96 27-MAR-15:00 332294.83 660080.29 0.00 84450.25 123869.47 29640.41 0.00 208963.12 52200.58
April 1956306.22 07-APR-15:39 332294.83 778371.69 0.00 84450.25 219327.00 57829.57 0.00 386887.82 93402.74
May 1583885.77 30-MAY-10:50 332294.83 423497.50 0.00 39059.06 302144.59 60332.55 0.00 332218.93 93402.74
June 1756565.62 20-JUN-15:09 332294.83 541788.89 0.00 84450.25 307311.20 58018.80 0.00 339298.91 93402.74
July 1931810.05 20-JUL-15:09 332294.83 660080.29 0.00 84450.25 247848.09 58237.71 0.00 449882.67 93402.74
August 2113158.43 16-AUG-15:20 332294.83 778371.69 0.00 84450.25 265704.45 58466.29 0.00 494854.71 93402.74
September 1544841.87 07-SEP-15:30 332294.83 423497.50 0.00 84450.25 236960.33 57517.67 0.00 311105.08 93402.74
October 1634849.50 04-OCT-15:00 332294.83 541788.89 0.00 84450.25 201229.88 56648.03 0.00 319421.41 93402.74
November 1442835.99 03-NOV-15:09 332294.83 660080.29 0.00 84450.25 139077.03 29346.59 0.00 148169.40 49417.59
December 1559486.95 07-DEC-16:00 385834.94 778371.69 57580.60 84492.05 86301.94 30509.44 0.00 108384.49 22647.28
                       
Annual Sum or Average                      
Minimum of Months 1107154.96   332294.83 423497.50 0.00 39059.06 78924.68 4941.96 0.00 36255.25 4551.11
Maximum of Months 2113158.43   385834.94 778371.69 57580.60 84492.05 307311.20 60332.55 0.00 494854.71 93402.74



Table of Contents

Report: PeakEnergyEndUseNaturalGasMonthly

For: Meter

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

INTERIOREQUIPMENT:NATURALGAS [] EXTERIOREQUIPMENT:NATURALGAS [] HEATING:NATURALGAS {Maximum} [W] HEATING:NATURALGAS {TIMESTAMP} COOLING:NATURALGAS [] WATERSYSTEMS:NATURALGAS {Maximum} [W] WATERSYSTEMS:NATURALGAS {TIMESTAMP} COGENERATION:NATURALGAS []
January 0.00 0.00 1892175.57 02-JAN-05:10 0.00 84910.61 31-JAN-12:39 0.00
February 0.00 0.00 1852536.05 13-FEB-07:10 0.00 84953.67 08-FEB-12:39 0.00
March 0.00 0.00 1199755.61 23-MAR-06:10 0.00 84722.76 01-MAR-12:00 0.00
April 0.00 0.00 729643.14 01-APR-06:10 0.00 83247.68 03-APR-11:50 0.00
May 0.00 0.00 152255.19 04-MAY-06:10 0.00 80936.25 03-MAY-11:30 0.00
June 0.00 0.00 185804.79 01-JUN-15:20 0.00 78141.29 01-JUN-11:00 0.00
July 0.00 0.00 60549.01 11-JUL-13:39 0.00 75189.07 05-JUL-11:39 0.00
August 0.00 0.00 241481.87 24-AUG-16:40 0.00 74284.35 31-AUG-11:00 0.00
September 0.00 0.00 100434.11 01-SEP-13:00 0.00 76272.18 29-SEP-11:00 0.00
October 0.00 0.00 606525.29 28-OCT-06:10 0.00 78700.02 30-OCT-11:30 0.00
November 0.00 0.00 1272131.74 24-NOV-07:10 0.00 81991.02 30-NOV-12:00 0.00
December 0.00 0.00 1230301.73 22-DEC-07:10 0.00 83894.27 29-DEC-12:20 0.00
                 
Annual Sum or Average 0.00 0.00     0.00     0.00
Minimum of Months 0.00 0.00 60549.01   0.00 74284.35   0.00
Maximum of Months 0.00 0.00 1892175.57   0.00 84953.67   0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: BASEMENT

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.17 25.88 0.00 25.88
February 0.00 0.00 0.00 0.00 0.83 25.82 0.00 25.82
March 0.00 0.00 0.00 0.00 0.83 25.69 0.00 25.69
April 0.00 0.00 0.00 0.00 1.33 26.30 0.00 26.30
May 0.00 0.00 0.00 0.00 3.00 26.80 0.00 26.80
June 0.00 0.00 0.00 0.00 4.17 26.72 0.17 26.64
July 0.00 0.00 0.00 0.00 4.00 26.27 0.00 26.27
August 0.00 0.00 0.00 0.00 7.17 26.42 0.17 26.44
September 0.00 0.00 0.00 0.00 5.67 26.94 0.17 26.95
October 0.00 0.00 0.00 0.00 9.50 26.90 0.17 26.90
November 0.00 0.00 0.00 0.00 5.67 26.99 0.67 27.04
December 0.00 0.00 0.00 0.00 2.50 26.50 0.00 26.50
                 
Annual Sum or Average 0.00   0.00   44.83 26.67 1.33 26.68
Minimum of Months 0.00 0.00 0.00 0.00 0.17 25.69 0.00 25.69
Maximum of Months 0.00 0.00 0.00 0.00 9.50 26.99 0.67 27.04



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: CORE_BOTTOM

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.17 25.57 0.00 25.57
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.17 25.57 0.00 25.57
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.17 25.57 0.00 25.57



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: CORE_MID

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 2.17 19.32 1.17 19.51 0.33 19.98 0.33 20.36
February 0.00 0.00 0.00 0.00 0.67 24.59 0.67 24.59
March 0.00 0.00 0.00 0.00 0.17 24.73 0.17 24.73
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 2.17 19.32 1.17 19.51 1.17 20.84 1.17 21.62
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 2.17 19.32 1.17 19.51 0.67 24.73 0.67 24.73



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: CORE_TOP

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 3.33 18.81 0.50 18.94 0.00 18.94 0.00 18.94
February 1.83 18.26 0.00 18.26 0.00 18.26 0.00 18.26
March 0.17 19.42 0.00 19.42 0.00 19.42 0.00 19.42
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.67 19.21 0.00 19.21 0.00 19.21 0.00 19.21
December 0.67 18.59 0.00 18.59 0.00 18.59 0.00 18.59
                 
Annual Sum or Average 6.67 18.69 0.50 18.77 0.00 18.77 0.00 18.77
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 3.33 19.42 0.50 19.42 0.00 19.42 0.00 19.42



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.50 19.29 0.17 19.56 0.00 19.56 0.00 19.56
February 0.50 19.05 0.00 19.05 0.00 19.05 0.00 19.05
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 4.00 27.24 3.67 27.31
August 0.00 0.00 0.00 0.00 1.50 27.44 1.33 27.45
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 1.00 19.17 0.17 19.34 5.50 25.90 5.00 26.54
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.50 19.29 0.17 19.56 4.00 27.44 3.67 27.45



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.50 18.96 0.00 18.96 0.00 18.96 0.00 18.96
February 0.67 19.10 0.00 19.10 0.00 19.10 0.00 19.10
March 0.00 0.00 0.00 0.00 0.17 27.35 0.17 27.35
April 0.00 0.00 0.00 0.00 2.33 28.01 2.33 28.01
May 0.00 0.00 0.00 0.00 6.50 28.19 6.50 28.19
June 0.00 0.00 0.00 0.00 3.33 27.99 3.33 27.99
July 0.00 0.00 0.00 0.00 7.33 28.10 7.33 28.10
August 0.00 0.00 0.00 0.00 4.33 27.97 4.33 27.97
September 0.00 0.00 0.00 0.00 5.33 28.21 5.33 28.21
October 0.00 0.00 0.00 0.00 1.50 27.58 1.50 27.58
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 1.17 19.04 0.00 19.04 30.83 27.74 30.83 27.90
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.67 19.10 0.00 19.10 7.33 28.21 7.33 28.21



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 1.17 18.93 0.17 19.11 0.33 20.78 0.33 21.89
February 0.67 18.96 0.00 18.96 1.50 25.05 1.50 26.16
March 0.00 0.00 0.00 0.00 0.33 27.64 0.33 27.64
April 0.00 0.00 0.00 0.00 2.50 27.60 2.50 27.60
May 0.00 0.00 0.00 0.00 3.67 27.83 3.67 27.83
June 0.00 0.00 0.00 0.00 3.50 27.61 3.50 27.61
July 0.00 0.00 0.00 0.00 9.17 27.73 8.67 27.78
August 0.00 0.00 0.00 0.00 6.33 28.01 5.83 28.05
September 0.00 0.00 0.00 0.00 8.83 27.58 8.67 27.58
October 0.00 0.00 0.00 0.00 9.33 27.58 9.33 27.58
November 0.00 0.00 0.00 0.00 0.67 27.52 0.67 27.52
December 0.00 0.00 0.00 0.00 3.17 27.89 3.17 27.89
                 
Annual Sum or Average 1.83 18.94 0.17 19.06 49.33 27.37 48.17 27.55
Minimum of Months 0.00 0.00 0.00 0.00 0.33 20.78 0.33 21.89
Maximum of Months 1.17 18.96 0.17 19.11 9.33 28.01 9.33 28.05



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.33 19.11 0.00 19.11 0.00 19.11 0.00 19.11
February 0.33 19.36 0.00 19.36 0.33 23.41 0.33 24.75
March 0.00 0.00 0.00 0.00 1.50 28.02 1.33 28.02
April 0.00 0.00 0.00 0.00 8.50 27.90 5.00 28.04
May 0.00 0.00 0.00 0.00 6.67 28.10 4.50 28.18
June 0.00 0.00 0.00 0.00 12.67 27.59 5.17 27.83
July 0.00 0.00 0.00 0.00 29.33 27.50 11.50 27.70
August 0.00 0.00 0.00 0.00 21.00 27.39 7.67 27.60
September 0.00 0.00 0.00 0.00 5.33 28.19 3.67 28.35
October 0.00 0.00 0.00 0.00 3.00 28.13 2.83 28.14
November 0.00 0.00 0.00 0.00 0.17 27.27 0.17 27.27
December 0.00 0.00 0.00 0.00 0.50 27.51 0.50 27.51
                 
Annual Sum or Average 0.67 19.24 0.00 19.24 89.00 27.58 42.67 27.79
Minimum of Months 0.00 0.00 0.00 0.00 0.00 19.11 0.00 19.11
Maximum of Months 0.33 19.36 0.00 19.36 29.33 28.19 11.50 28.35



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 24.33 16.81 7.33 16.89 0.00 16.89 0.00 16.89
February 21.00 17.19 5.50 17.36 0.00 17.36 0.00 17.36
March 2.50 18.86 0.17 18.96 0.00 18.96 0.00 18.96
April 0.17 19.38 0.00 19.38 0.00 19.38 0.00 19.38
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 2.17 27.42 2.17 27.42
August 0.00 0.00 0.00 0.00 1.50 27.45 1.50 27.45
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 3.33 18.84 0.33 18.98 0.00 18.98 0.00 18.98
December 6.00 17.70 0.17 17.63 0.00 17.63 0.00 17.63
                 
Annual Sum or Average 57.33 17.26 13.50 17.32 3.67 17.82 3.67 18.27
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 24.33 19.38 7.33 19.38 2.17 27.45 2.17 27.45



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 17.17 16.18 2.83 16.05 0.00 16.05 0.00 16.05
February 11.17 16.80 0.83 16.83 0.00 16.83 0.00 16.83
March 1.83 18.81 0.00 18.81 0.00 18.81 0.00 18.81
April 0.33 19.38 0.00 19.38 1.50 26.27 1.50 26.96
May 0.00 0.00 0.00 0.00 6.67 28.25 6.67 28.25
June 0.00 0.00 0.00 0.00 4.67 27.97 4.67 27.97
July 0.00 0.00 0.00 0.00 9.67 28.20 9.67 28.20
August 0.00 0.00 0.00 0.00 6.00 28.11 6.00 28.11
September 0.00 0.00 0.00 0.00 5.33 28.31 5.33 28.31
October 0.00 0.00 0.00 0.00 0.33 27.44 0.33 27.44
November 2.50 18.55 0.00 18.55 0.00 18.55 0.00 18.55
December 5.50 17.84 0.00 17.84 0.00 17.84 0.00 17.84
                 
Annual Sum or Average 38.50 16.90 3.67 16.80 34.17 21.88 34.17 23.82
Minimum of Months 0.00 0.00 0.00 0.00 0.00 16.05 0.00 16.05
Maximum of Months 17.17 19.38 2.83 19.38 9.67 28.31 9.67 28.31



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 14.83 16.49 1.83 16.45 0.17 16.53 0.17 16.61
February 8.33 17.73 0.33 17.83 1.33 19.15 1.33 20.16
March 1.17 18.70 0.00 18.70 0.33 20.31 0.33 21.34
April 0.00 0.00 0.00 0.00 0.83 27.58 0.83 27.58
May 0.00 0.00 0.00 0.00 3.67 27.79 3.67 27.79
June 0.00 0.00 0.00 0.00 3.17 27.62 3.17 27.62
July 0.00 0.00 0.00 0.00 8.33 27.85 8.00 27.86
August 0.00 0.00 0.00 0.00 7.67 27.39 7.33 27.38
September 0.00 0.00 0.00 0.00 13.00 27.03 12.67 27.03
October 0.00 0.00 0.00 0.00 15.67 26.44 15.67 26.44
November 2.00 18.98 0.00 18.98 1.50 21.53 1.50 22.55
December 3.33 18.49 0.00 18.49 2.17 22.32 2.17 23.98
                 
Annual Sum or Average 29.67 17.32 2.17 17.28 57.83 23.63 56.83 24.98
Minimum of Months 0.00 0.00 0.00 0.00 0.17 16.53 0.17 16.61
Maximum of Months 14.83 18.98 1.83 18.98 15.67 27.85 15.67 27.86



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 15.17 16.15 3.17 15.94 0.00 15.94 0.00 15.94
February 9.00 17.11 0.50 17.09 0.00 17.09 0.00 17.09
March 1.17 18.73 0.00 18.73 0.00 18.73 0.00 18.73
April 0.00 0.00 0.00 0.00 2.17 28.13 1.50 28.17
May 0.00 0.00 0.00 0.00 5.17 28.08 3.67 28.14
June 0.00 0.00 0.00 0.00 5.67 28.32 3.33 28.42
July 0.00 0.00 0.00 0.00 9.33 28.40 5.67 28.46
August 0.00 0.00 0.00 0.00 4.83 28.06 3.67 28.07
September 0.00 0.00 0.00 0.00 3.83 28.62 2.83 28.70
October 0.00 0.00 0.00 0.00 0.67 28.04 0.67 28.04
November 1.67 18.56 0.00 18.56 0.00 18.56 0.00 18.56
December 4.17 18.14 0.00 18.14 0.00 18.14 0.00 18.14
                 
Annual Sum or Average 31.17 16.92 3.67 16.74 31.67 22.23 21.33 23.74
Minimum of Months 0.00 0.00 0.00 0.00 0.00 15.94 0.00 15.94
Maximum of Months 15.17 18.73 3.17 18.73 9.33 28.62 5.67 28.70



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 59.00 16.04 16.17 16.10 0.00 16.10 0.00 16.10
February 49.17 16.33 16.17 16.47 0.00 16.47 0.00 16.47
March 10.33 17.99 0.83 18.08 0.00 18.08 0.00 18.08
April 1.50 18.89 0.00 18.89 0.00 18.89 0.00 18.89
May 0.00 0.00 0.00 0.00 0.17 27.33 0.17 27.33
June 0.00 0.00 0.00 0.00 1.33 27.34 1.17 27.35
July 0.00 0.00 0.00 0.00 7.33 27.43 5.83 27.48
August 0.00 0.00 0.00 0.00 2.17 27.64 1.83 27.66
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.67 19.32 0.00 19.32 0.00 19.32 0.00 19.32
November 14.83 17.01 2.17 17.04 0.00 17.04 0.00 17.04
December 23.00 16.50 4.83 16.37 0.00 16.37 0.00 16.37
                 
Annual Sum or Average 158.50 16.45 40.17 16.48 11.00 17.06 9.00 17.49
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 59.00 19.32 16.17 19.32 7.33 27.64 5.83 27.66



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 42.67 15.27 8.83 15.21 0.00 15.21 0.00 15.21
February 29.17 15.54 5.67 15.42 0.00 15.42 0.00 15.42
March 6.83 17.80 0.00 17.80 0.00 17.80 0.00 17.80
April 1.50 19.01 0.00 19.01 0.17 19.85 0.17 20.53
May 0.00 0.00 0.00 0.00 6.67 28.24 6.67 28.24
June 0.00 0.00 0.00 0.00 4.67 28.03 4.67 28.03
July 0.00 0.00 0.00 0.00 12.33 28.18 12.00 28.19
August 0.00 0.00 0.00 0.00 7.00 28.13 6.83 28.13
September 0.00 0.00 0.00 0.00 5.83 28.19 5.83 28.19
October 0.50 19.32 0.00 19.32 0.00 19.32 0.00 19.32
November 9.50 16.36 0.83 16.24 0.00 16.24 0.00 16.24
December 18.67 16.20 3.17 15.98 0.00 15.98 0.00 15.98
                 
Annual Sum or Average 108.83 15.82 18.50 15.68 36.67 18.47 36.17 20.22
Minimum of Months 0.00 0.00 0.00 0.00 0.00 15.21 0.00 15.21
Maximum of Months 42.67 19.32 8.83 19.32 12.33 28.24 12.00 28.24



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 33.00 15.68 6.33 15.60 0.00 15.60 0.00 15.60
February 24.33 16.17 2.50 16.15 0.00 16.15 0.00 16.15
March 5.00 18.09 0.00 18.09 0.00 18.09 0.00 18.09
April 1.33 19.07 0.00 19.07 0.33 20.76 0.33 21.89
May 0.00 0.00 0.00 0.00 3.83 27.89 3.83 27.89
June 0.00 0.00 0.00 0.00 3.50 27.74 3.50 27.74
July 0.00 0.00 0.00 0.00 10.17 27.92 8.83 27.97
August 0.00 0.00 0.00 0.00 6.17 28.29 5.50 28.34
September 0.00 0.00 0.00 0.00 9.83 27.38 9.33 27.38
October 0.00 0.00 0.00 0.00 7.33 27.12 7.33 27.12
November 6.17 17.26 0.33 17.14 0.00 17.14 0.00 17.14
December 15.00 16.66 0.83 16.54 1.17 17.31 1.17 17.97
                 
Annual Sum or Average 84.83 16.31 10.00 16.20 42.33 19.74 39.83 21.54
Minimum of Months 0.00 0.00 0.00 0.00 0.00 15.60 0.00 15.60
Maximum of Months 33.00 19.07 6.33 19.07 10.17 28.29 9.33 28.34



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 33.83 15.42 8.67 15.30 0.00 15.30 0.00 15.30
February 22.33 15.76 4.17 15.60 0.00 15.60 0.00 15.60
March 4.33 18.34 0.00 18.34 0.00 18.34 0.00 18.34
April 0.83 19.12 0.00 19.12 2.17 25.53 1.50 26.39
May 0.00 0.00 0.00 0.00 5.83 28.07 4.00 28.16
June 0.00 0.00 0.00 0.00 6.00 28.49 3.50 28.57
July 0.00 0.00 0.00 0.00 10.50 28.47 6.33 28.54
August 0.00 0.00 0.00 0.00 6.00 28.13 4.50 28.14
September 0.00 0.00 0.00 0.00 4.00 28.69 3.00 28.75
October 0.33 19.41 0.00 19.41 0.67 25.07 0.67 26.21
November 6.00 16.88 0.33 16.78 0.00 16.78 0.00 16.78
December 12.33 16.80 1.83 16.53 0.00 16.53 0.00 16.53
                 
Annual Sum or Average 80.00 16.05 15.00 15.85 35.17 19.22 23.50 20.64
Minimum of Months 0.00 0.00 0.00 0.00 0.00 15.30 0.00 15.30
Maximum of Months 33.83 19.41 8.67 19.41 10.50 28.69 6.33 28.75



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: GROUNDFLOOR_PLENUM

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: MIDFLOOR_PLENUM

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: TOPFLOOR_PLENUM

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 1.00 27.59 1.00 27.59
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   1.00 27.59 1.00 27.59
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 1.00 27.59 1.00 27.59



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: DATACENTER_MID_ZN_6

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 2.67 27.77 2.67 27.77
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 324.83 28.61 292.67 28.65
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   327.50 28.61 295.33 28.64
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 324.83 28.61 292.67 28.65



Table of Contents

Report: ComfortReportSimple55Monthly

For: BASEMENT

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 219.33 23.89 60.67 24.20 0.00 24.20
February 258.67 23.96 51.00 24.32 0.00 24.32
March 98.67 24.00 102.67 24.80 0.00 24.80
April 29.50 24.00 168.83 25.11 0.00 25.11
May 27.33 24.00 288.50 24.76 24.17 24.71
June 144.00 24.89 443.83 24.61 144.00 24.67
July 225.33 25.30 497.00 24.83 225.33 24.94
August 107.67 25.29 483.17 24.67 107.67 24.76
September 54.83 25.21 410.17 24.73 54.83 24.78
October 38.00 24.54 351.33 24.82 24.33 24.82
November 31.17 24.00 154.33 25.45 0.00 25.45
December 122.83 24.01 93.50 25.03 0.00 25.03
             
Annual Sum or Average 1357.33 24.45 3105.00 24.74 580.33 24.78
Minimum of Months 27.33 23.89 51.00 24.20 0.00 24.20
Maximum of Months 258.67 25.30 497.00 25.45 225.33 25.45



Table of Contents

Report: ComfortReportSimple55Monthly

For: CORE_BOTTOM

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 355.67 23.72 18.83 23.75 0.00 23.75
February 282.83 23.86 6.50 23.91 0.00 23.91
March 106.00 23.95 87.67 24.48 0.00 24.48
April 27.17 23.92 172.83 24.65 0.00 24.65
May 6.50 23.92 277.33 24.42 0.00 24.42
June 0.00 0.00 440.83 24.28 0.00 24.28
July 0.00 0.00 497.00 24.23 0.00 24.23
August 0.00 0.00 490.17 24.19 0.00 24.19
September 2.67 23.87 402.83 24.37 0.00 24.37
October 29.83 23.99 317.17 24.44 0.00 24.44
November 56.50 23.94 123.33 24.87 0.00 24.87
December 157.33 23.95 52.00 24.40 0.00 24.40
             
Annual Sum or Average 1024.50 23.85 2886.50 24.28 0.00 24.28
Minimum of Months 0.00 0.00 6.50 23.75 0.00 23.75
Maximum of Months 355.67 23.99 497.00 24.87 0.00 24.87



Table of Contents

Report: ComfortReportSimple55Monthly

For: CORE_MID

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 498.83 22.18 80.83 21.87 80.83 21.63
February 453.83 22.68 28.83 22.57 28.83 22.47
March 426.17 23.41 8.33 23.42 0.00 23.42
April 247.67 23.36 45.17 23.53 0.00 23.53
May 87.17 23.66 195.67 24.10 0.00 24.10
June 7.33 23.69 424.00 24.22 0.00 24.22
July 0.00 0.00 494.33 24.21 0.00 24.21
August 0.00 0.00 461.50 24.25 0.00 24.25
September 31.67 23.59 352.83 24.21 0.00 24.21
October 121.00 23.71 231.50 24.06 0.00 24.06
November 329.33 23.21 45.33 23.37 0.00 23.37
December 494.67 22.96 6.17 22.93 6.17 22.91
             
Annual Sum or Average 2697.67 22.97 2374.50 23.48 115.83 23.41
Minimum of Months 0.00 0.00 6.17 21.87 0.00 21.63
Maximum of Months 498.83 23.71 494.33 24.25 80.83 24.25



Table of Contents

Report: ComfortReportSimple55Monthly

For: CORE_TOP

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 502.00 21.12 183.00 20.72 183.00 20.49
February 454.00 21.40 165.50 21.07 165.50 20.88
March 481.67 22.41 38.67 22.29 36.00 22.17
April 334.50 22.65 48.33 22.69 15.17 22.60
May 166.67 23.35 167.00 23.77 0.00 23.77
June 13.00 23.55 418.83 24.20 0.00 24.20
July 0.00 0.00 497.00 24.27 0.00 24.27
August 0.00 0.00 463.50 24.28 0.00 24.28
September 70.17 23.19 332.17 24.03 0.00 24.03
October 255.17 22.88 173.33 23.31 8.33 23.27
November 450.00 22.19 74.17 21.94 68.00 21.73
December 497.00 21.45 143.17 21.09 143.17 20.87
             
Annual Sum or Average 3224.17 22.02 2704.67 22.58 619.17 22.33
Minimum of Months 0.00 0.00 38.67 20.72 0.00 20.49
Maximum of Months 502.00 23.55 497.00 24.28 183.00 24.28



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 502.00 21.40 169.50 21.16 169.50 21.02
February 454.00 21.64 130.00 21.42 130.00 21.28
March 459.50 22.77 15.00 22.77 6.33 22.74
April 278.17 23.22 77.00 23.46 0.00 23.46
May 74.33 23.62 229.50 24.16 1.00 24.17
June 12.67 25.89 456.17 24.38 11.67 24.42
July 30.67 26.70 497.00 24.57 30.67 24.69
August 9.50 26.70 490.33 24.34 9.50 24.39
September 46.50 23.65 354.33 24.25 2.00 24.26
October 193.17 23.34 224.17 23.77 0.00 23.77
November 410.17 22.79 23.33 22.78 10.67 22.73
December 497.00 22.22 20.50 22.16 20.50 22.10
             
Annual Sum or Average 2967.67 22.46 2686.83 23.12 391.83 23.01
Minimum of Months 9.50 21.40 15.00 21.16 0.00 21.02
Maximum of Months 502.00 26.70 497.00 24.57 169.50 24.69



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 495.00 21.31 151.67 21.10 151.67 20.98
February 438.17 21.68 108.67 21.52 105.33 21.39
March 408.83 22.25 40.50 22.32 15.33 22.28
April 276.00 22.68 123.50 23.23 8.17 23.31
May 136.50 23.78 282.33 24.23 24.00 24.39
June 25.00 25.99 454.67 24.37 20.17 24.46
July 40.17 26.81 493.83 24.54 40.17 24.70
August 23.00 26.26 477.83 24.30 19.33 24.39
September 85.33 24.10 361.33 24.35 22.83 24.48
October 189.67 23.02 218.00 23.68 5.83 23.73
November 395.33 22.32 30.50 22.37 12.67 22.32
December 482.67 21.79 44.17 21.72 42.33 21.65
             
Annual Sum or Average 2995.67 22.28 2787.00 23.06 467.83 23.02
Minimum of Months 23.00 21.31 30.50 21.10 5.83 20.98
Maximum of Months 495.00 26.81 493.83 24.54 151.67 24.70



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 425.50 21.42 155.67 21.27 134.33 21.08
February 348.33 21.89 114.33 21.90 82.83 21.73
March 347.83 22.49 101.33 22.74 19.00 22.67
April 251.00 22.88 133.50 23.42 10.17 23.48
May 127.00 23.61 260.83 24.12 13.50 24.22
June 24.50 25.65 461.67 24.38 17.17 24.46
July 39.17 26.87 497.00 24.61 39.17 24.76
August 23.50 27.01 497.33 24.45 23.50 24.56
September 65.00 24.88 406.50 24.52 27.17 24.66
October 132.67 23.95 327.50 24.33 27.33 24.47
November 302.17 22.53 113.00 22.90 16.50 22.83
December 385.50 22.11 83.33 22.28 43.17 22.24
             
Annual Sum or Average 2472.17 22.55 3152.00 23.39 453.83 23.35
Minimum of Months 23.50 21.42 83.33 21.27 10.17 21.08
Maximum of Months 425.50 27.01 497.33 24.61 134.33 24.76



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 478.33 21.70 89.67 21.56 85.83 21.44
February 400.17 22.21 43.83 22.20 31.83 22.11
March 233.50 23.22 117.50 23.64 4.83 23.69
April 83.17 24.18 268.00 24.58 18.67 24.70
May 62.00 24.57 369.17 24.48 22.50 24.60
June 41.33 26.67 482.67 24.67 41.33 24.81
July 87.50 26.40 497.00 24.87 87.50 25.07
August 90.67 25.78 514.00 24.67 90.67 24.81
September 44.17 25.21 410.00 24.55 23.50 24.66
October 88.83 23.87 329.83 24.37 11.83 24.44
November 229.33 23.04 112.50 23.60 0.50 23.60
December 363.00 23.16 30.33 23.34 0.33 23.35
             
Annual Sum or Average 2202.00 23.11 3264.50 23.88 419.33 23.95
Minimum of Months 41.33 21.70 30.33 21.56 0.33 21.44
Maximum of Months 478.33 26.67 514.00 24.87 90.67 25.07



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_MID_ZN_3

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 502.00 20.11 387.83 19.98 387.83 19.93
February 454.00 20.29 376.00 20.20 376.00 20.17
March 509.83 21.22 172.17 21.00 169.67 20.86
April 403.67 22.01 68.67 21.97 43.17 21.84
May 204.67 23.10 144.67 23.58 0.00 23.58
June 40.17 25.06 434.17 24.33 28.83 24.41
July 69.83 26.03 497.00 24.65 69.83 24.80
August 36.67 25.79 474.00 24.45 32.67 24.55
September 128.17 23.23 284.50 23.90 11.83 23.93
October 332.17 22.37 131.00 22.65 23.83 22.54
November 489.00 21.21 165.83 20.91 165.83 20.73
December 497.00 20.37 403.50 20.29 403.50 20.26
             
Annual Sum or Average 3667.17 21.38 3539.33 21.90 1713.00 21.64
Minimum of Months 36.67 20.11 68.67 19.98 0.00 19.93
Maximum of Months 509.83 26.03 497.00 24.65 403.50 24.80



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_MID_ZN_2

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 427.00 20.04 317.83 19.87 317.83 19.80
February 384.83 20.48 271.33 20.30 271.33 20.22
March 404.33 21.27 122.00 21.06 115.67 20.90
April 302.33 21.98 91.00 22.37 26.83 22.35
May 206.83 23.14 174.17 23.83 23.33 24.02
June 55.17 25.01 349.33 24.47 32.33 24.61
July 76.50 26.44 416.83 24.85 76.50 25.06
August 44.33 26.32 401.50 24.64 40.50 24.80
September 139.00 23.52 251.17 24.14 31.33 24.31
October 263.83 22.32 120.17 22.81 15.67 22.78
November 401.33 21.15 126.83 20.89 125.17 20.71
December 422.00 20.46 294.83 20.30 294.83 20.24
             
Annual Sum or Average 3127.50 21.52 2937.00 22.09 1371.33 21.89
Minimum of Months 44.33 20.04 91.00 19.87 15.67 19.80
Maximum of Months 427.00 26.44 416.83 24.85 317.83 25.06



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_MID_ZN_1

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 439.17 20.62 256.17 20.39 237.50 20.19
February 370.33 21.21 212.50 21.08 184.50 20.88
March 380.00 21.61 156.00 21.75 85.67 21.56
April 322.50 22.13 130.17 22.56 32.17 22.48
May 205.33 23.10 207.67 23.74 12.67 23.84
June 50.83 24.78 431.83 24.34 28.50 24.43
July 76.00 26.22 496.17 24.71 76.00 24.89
August 47.33 26.30 490.17 24.59 42.83 24.74
September 104.50 24.30 372.50 24.42 41.00 24.58
October 189.17 23.41 298.50 24.06 36.33 24.20
November 351.33 21.70 149.83 21.85 73.00 21.62
December 417.50 21.25 230.00 21.15 202.67 20.99
             
Annual Sum or Average 2954.00 21.99 3431.50 22.75 1052.83 22.58
Minimum of Months 47.33 20.62 130.17 20.39 12.67 20.19
Maximum of Months 439.17 26.30 496.17 24.71 237.50 24.89



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_MID_ZN_4

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 498.50 20.38 318.00 20.17 318.00 20.08
February 443.00 20.68 283.67 20.48 283.67 20.39
March 439.67 21.37 137.00 21.39 102.67 21.25
April 353.83 22.00 110.33 22.38 27.50 22.34
May 211.00 23.08 212.50 23.73 18.83 23.87
June 52.33 25.20 442.67 24.44 34.17 24.57
July 70.67 26.38 493.83 24.74 70.67 24.92
August 54.33 25.98 496.67 24.59 51.00 24.72
September 129.00 23.28 314.83 24.01 22.83 24.13
October 263.00 22.31 183.17 23.00 12.00 22.98
November 467.83 21.23 127.00 21.01 122.33 20.86
December 495.33 20.73 293.17 20.56 293.17 20.48
             
Annual Sum or Average 3478.50 21.57 3412.83 22.26 1356.83 22.06
Minimum of Months 52.33 20.38 110.33 20.17 12.00 20.08
Maximum of Months 498.50 26.38 496.67 24.74 318.00 24.92



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 502.00 19.87 434.00 19.78 434.00 19.75
February 454.00 20.00 420.33 19.96 420.33 19.95
March 511.83 20.78 267.17 20.53 267.00 20.40
April 413.33 21.50 140.33 21.34 111.83 21.13
May 254.50 22.73 139.00 23.27 4.17 23.27
June 57.33 24.61 417.17 24.30 34.17 24.38
July 84.33 26.02 497.00 24.69 84.33 24.86
August 55.00 25.36 463.83 24.46 40.83 24.58
September 165.50 22.83 265.83 23.66 16.33 23.66
October 376.67 21.79 162.00 21.83 81.17 21.57
November 489.00 20.59 262.00 20.30 262.00 20.16
December 497.00 19.96 465.83 19.92 465.83 19.91
             
Annual Sum or Average 3860.50 21.07 3934.50 21.54 2222.00 21.27
Minimum of Months 55.00 19.87 139.00 19.78 4.17 19.75
Maximum of Months 511.83 26.02 497.00 24.69 465.83 24.86



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 502.00 19.94 399.33 19.80 399.33 19.74
February 454.00 20.23 360.17 20.11 360.17 20.06
March 483.33 21.04 183.00 20.70 181.17 20.50
April 343.00 21.55 167.67 21.84 80.83 21.64
May 248.83 22.81 222.67 23.60 25.67 23.77
June 77.33 24.53 419.33 24.34 38.50 24.47
July 88.83 26.28 487.67 24.77 87.50 24.97
August 56.00 25.95 476.67 24.55 46.67 24.71
September 171.33 23.21 304.17 23.94 36.50 24.08
October 312.00 21.90 166.50 22.36 37.50 22.21
November 480.33 20.76 204.50 20.42 204.50 20.24
December 497.00 20.10 396.83 19.98 396.83 19.93
             
Annual Sum or Average 3714.00 21.24 3788.50 21.81 1895.17 21.57
Minimum of Months 56.00 19.94 166.50 19.80 25.67 19.74
Maximum of Months 502.00 26.28 487.67 24.77 399.33 24.97



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 451.50 20.30 302.83 20.03 293.00 19.87
February 387.83 20.75 269.00 20.56 249.83 20.39
March 395.17 21.08 223.83 21.09 161.83 20.86
April 336.33 21.57 174.50 21.88 83.33 21.68
May 253.67 22.71 191.00 23.41 18.50 23.51
June 76.67 24.24 408.83 24.27 34.83 24.37
July 82.50 26.12 492.00 24.71 81.83 24.89
August 56.50 25.87 474.67 24.57 45.83 24.73
September 134.00 23.63 344.17 24.17 40.67 24.32
October 212.17 22.53 288.83 23.42 44.33 23.40
November 384.50 21.12 199.33 21.03 146.83 20.77
December 433.83 20.64 297.67 20.45 278.17 20.28
             
Annual Sum or Average 3204.67 21.55 3666.67 22.24 1479.00 21.99
Minimum of Months 56.50 20.30 174.50 20.03 18.50 19.87
Maximum of Months 451.50 26.12 492.00 24.71 293.00 24.89



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 499.00 20.11 363.83 19.92 363.83 19.84
February 443.83 20.37 331.17 20.19 331.17 20.12
March 446.83 20.99 205.17 20.89 176.83 20.73
April 369.33 21.59 146.33 21.85 69.50 21.70
May 263.33 22.72 194.83 23.44 20.00 23.58
June 75.67 24.57 421.50 24.37 41.17 24.51
July 84.50 26.14 487.67 24.75 83.00 24.93
August 69.33 25.52 481.33 24.58 59.33 24.71
September 168.50 22.92 279.00 23.78 26.17 23.90
October 308.83 21.84 186.50 22.36 43.50 22.20
November 473.83 20.74 209.83 20.48 206.50 20.33
December 497.00 20.32 379.17 20.18 379.17 20.12
             
Annual Sum or Average 3700.00 21.29 3686.33 21.89 1800.17 21.66
Minimum of Months 69.33 20.11 146.33 19.92 20.00 19.84
Maximum of Months 499.00 26.14 487.67 24.75 379.17 24.93



Table of Contents

Report: ComfortReportSimple55Monthly

For: GROUNDFLOOR_PLENUM

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00
             
Annual Sum or Average 0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: ComfortReportSimple55Monthly

For: MIDFLOOR_PLENUM

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00
             
Annual Sum or Average 0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: ComfortReportSimple55Monthly

For: TOPFLOOR_PLENUM

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00
             
Annual Sum or Average 0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: ComfortReportSimple55Monthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 470.83 27.00 0.00 27.00
February 0.00 0.00 454.00 27.00 0.00 27.00
March 24.83 27.00 514.00 27.00 24.83 27.00
April 136.33 27.00 485.00 27.00 136.33 27.00
May 27.83 27.00 508.00 27.00 27.83 27.00
June 202.83 27.00 496.00 27.00 202.83 27.00
July 308.67 27.00 497.00 27.00 308.67 27.00
August 472.83 27.02 514.00 27.02 472.83 27.02
September 84.00 27.00 485.00 27.00 84.00 27.00
October 83.00 27.00 502.00 27.00 83.00 27.00
November 17.00 27.00 489.00 27.00 17.00 27.00
December 5.33 27.00 497.00 27.00 5.33 27.00
             
Annual Sum or Average 1362.67 27.01 5911.83 27.00 1362.67 27.00
Minimum of Months 0.00 0.00 454.00 27.00 0.00 27.00
Maximum of Months 472.83 27.02 514.00 27.02 472.83 27.02



Table of Contents

Report: ComfortReportSimple55Monthly

For: DATACENTER_MID_ZN_6

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 73.33 25.02 328.00 26.52 10.50 26.42
February 0.00 0.00 312.00 27.00 0.00 27.00
March 3.00 27.00 500.33 27.00 3.00 27.00
April 17.83 27.00 485.00 27.00 17.83 27.00
May 11.67 27.00 508.00 27.00 11.67 27.00
June 66.33 27.00 496.00 27.00 66.33 27.00
July 119.50 27.00 497.00 27.00 119.50 27.00
August 189.50 27.03 514.00 27.01 189.50 27.02
September 30.50 27.00 485.00 27.00 30.50 27.00
October 26.50 27.00 502.00 27.00 26.50 27.00
November 0.17 27.00 454.50 27.00 0.17 27.00
December 0.00 0.00 452.17 27.00 0.00 27.00
             
Annual Sum or Average 538.33 26.74 5534.00 26.97 475.50 26.97
Minimum of Months 0.00 0.00 312.00 26.52 0.00 26.42
Maximum of Months 189.50 27.03 514.00 27.01 189.50 27.02



Table of Contents

Report: ComfortReportSimple55Monthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 153.33 24.48 254.33 25.64 36.83 25.38
February 49.17 27.00 206.33 27.00 0.00 27.00
March 3.17 27.00 448.67 27.00 3.17 27.00
April 26.50 27.00 472.33 27.00 26.50 27.00
May 22.33 27.00 508.00 27.00 22.33 27.00
June 106.33 27.00 496.00 27.00 106.33 27.00
July 181.00 27.00 497.00 27.00 181.00 27.00
August 234.00 27.01 514.00 27.01 234.00 27.01
September 48.67 27.00 485.00 27.00 48.67 27.00
October 32.17 27.00 475.33 27.00 32.17 27.00
November 7.67 27.00 407.50 27.00 0.00 27.00
December 23.67 27.00 318.50 27.00 0.00 27.00
             
Annual Sum or Average 888.00 26.57 5083.00 26.91 691.00 26.89
Minimum of Months 3.17 24.48 206.33 25.64 0.00 25.38
Maximum of Months 234.00 27.01 514.00 27.01 234.00 27.01



Table of Contents

Report: ComfortReportSimple55Monthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 305.83 27.00 502.00 27.00 305.83 27.00
February 454.00 27.00 454.00 27.00 454.00 27.00
March 514.00 27.00 514.00 27.00 514.00 27.00
April 485.00 27.01 485.00 27.01 485.00 27.01
May 508.00 27.00 508.00 27.00 508.00 27.00
June 496.00 27.00 496.00 27.00 496.00 27.00
July 497.00 27.00 497.00 27.00 497.00 27.00
August 514.00 28.01 514.00 28.01 514.00 28.01
September 485.00 27.00 485.00 27.00 485.00 27.00
October 502.00 27.00 502.00 27.00 502.00 27.00
November 489.00 27.00 489.00 27.00 489.00 27.00
December 497.00 27.01 497.00 27.01 497.00 27.01
             
Annual Sum or Average 5746.83 27.09 5943.00 27.09 5746.83 27.09
Minimum of Months 305.83 27.00 454.00 27.00 305.83 27.00
Maximum of Months 514.00 28.01 514.00 28.01 514.00 28.01



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 26.99990 20.69869 0.70799 15.75880
February 454.00000 27.00000 17.43314 0.73958 16.65086
March 514.00000 27.00003 24.61185 0.88708 21.76031
April 485.00000 27.00003 29.83808 0.98454 25.59094
May 508.00000 27.00050 34.26953 0.28374 6.80730
June 496.00000 27.00138 38.11325 0.39540 8.35122
July 497.00000 27.00110 39.26888 0.45233 9.35256
August 514.00000 27.01825 38.56935 0.50780 10.51572
September 485.00000 27.00065 37.68858 0.32715 7.39348
October 502.00000 27.00067 31.80648 0.95738 24.54030
November 489.00000 27.00006 27.08299 0.89911 22.23377
December 497.00000 26.99999 20.22192 0.85010 20.34491
           
Annual Sum or Average 5943.00000 27.00194 30.05577 0.66501 15.75117
Minimum of Months 454.00000 26.99990 17.43314 0.28374 6.80730
Maximum of Months 514.00000 27.01825 39.26888 0.98454 25.59094



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: DATACENTER_MID_ZN_6

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 26.68140 20.78711 0.51310 11.94636
February 454.00000 27.00000 17.43004 0.59116 12.53404
March 514.00000 27.00003 24.59469 0.74138 16.81174
April 485.00000 27.00003 29.80476 0.83924 20.09246
May 508.00000 27.00033 34.34018 0.20209 6.06989
June 496.00000 27.00144 38.15497 0.31589 7.21440
July 497.00000 27.00119 39.29392 0.36278 7.84861
August 514.00000 27.00940 38.56945 0.39571 8.41094
September 485.00000 27.00048 37.80648 0.25254 6.57581
October 502.00000 27.00067 31.81563 0.86474 21.06621
November 489.00000 27.00006 27.06288 0.73852 16.75682
December 497.00000 26.99999 20.20742 0.65099 14.05089
           
Annual Sum or Average 5943.00000 26.97426 30.07794 0.53817 12.43502
Minimum of Months 454.00000 26.68140 17.43004 0.20209 6.06989
Maximum of Months 514.00000 27.00940 39.29392 0.86474 21.06621



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 26.17702 21.14076 0.36740 10.79481
February 454.00000 27.00002 17.42982 0.52844 11.15986
March 514.00000 27.00003 24.60726 0.68826 15.34659
April 485.00000 27.00004 29.81964 0.80050 18.91758
May 508.00000 27.00030 34.40577 0.18269 6.08942
June 496.00000 27.00143 38.16172 0.32170 7.37933
July 497.00000 27.00119 39.29920 0.37963 8.17006
August 514.00000 27.00625 38.58331 0.40547 8.64404
September 485.00000 27.00049 37.84222 0.23817 6.58021
October 502.00000 27.00066 31.85734 0.82652 19.88723
November 489.00000 27.00006 27.08122 0.67337 14.92845
December 497.00000 27.00000 20.21345 0.57551 12.19823
           
Annual Sum or Average 5943.00000 26.93138 30.12637 0.49833 11.66805
Minimum of Months 454.00000 26.17702 17.42982 0.18269 6.08942
Maximum of Months 514.00000 27.00625 39.29920 0.82652 19.88723



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 27.00067 30.96843 1.03685 27.72828
February 454.00000 27.00419 30.20542 1.20019 35.26709
March 514.00000 27.00415 30.86978 1.37338 44.10613
April 485.00000 27.00928 32.74904 1.53135 52.60718
May 508.00000 27.00113 34.78324 0.53945 11.15009
June 496.00000 27.00174 37.73394 0.80451 18.68005
July 497.00000 27.00112 38.92646 1.02001 26.99430
August 514.00000 28.00630 37.81477 1.50204 51.01441
September 485.00000 27.00185 37.25475 0.62037 13.15729
October 502.00000 27.00178 34.58532 1.31067 40.83917
November 489.00000 27.00321 31.63583 1.40563 45.81985
December 497.00000 27.00738 30.27776 1.50981 51.43460
           
Annual Sum or Average 5943.00000 27.09004 34.01098 1.15474 34.92082
Minimum of Months 454.00000 27.00067 30.20542 0.53945 11.15009
Maximum of Months 514.00000 28.00630 38.92646 1.53135 52.60718



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: BASEMENT

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 24.30337 21.40665 0.29442 7.18229
February 454.00000 24.39505 17.19359 0.29363 7.21626
March 514.00000 24.37826 24.73208 0.35941 8.09178
April 485.00000 24.47985 31.04754 0.43113 9.45774
May 508.00000 24.48060 40.44849 -0.3532 8.47519
June 496.00000 24.46714 55.57694 -0.2321 7.19170
July 497.00000 24.61868 61.35938 -0.1413 6.91814
August 514.00000 24.49451 55.54516 -0.2070 7.13395
September 485.00000 24.55963 49.30967 -0.2399 7.52797
October 502.00000 24.60946 40.54326 0.54536 12.09558
November 489.00000 24.57497 26.98885 0.43113 9.56171
December 497.00000 24.52556 19.39465 0.35516 8.14503
           
Annual Sum or Average 5943.00000 24.49067 37.11708 0.12595 8.25380
Minimum of Months 454.00000 24.30337 17.19359 -0.3532 6.91814
Maximum of Months 514.00000 24.61868 61.35938 0.54536 12.09558



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: CORE_BOTTOM

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 23.87893 24.92828 0.20732 6.25701
February 454.00000 24.10698 19.28825 0.23560 6.37221
March 514.00000 24.26585 26.25007 0.34928 7.83649
April 485.00000 24.29292 32.32979 0.41732 8.99785
May 508.00000 24.25851 41.38517 -0.3926 8.71932
June 496.00000 24.25201 51.69443 -0.2959 7.19349
July 497.00000 24.22825 55.43582 -0.2684 6.69096
August 514.00000 24.18076 51.68693 -0.2944 6.97914
September 485.00000 24.31695 47.88550 -0.3153 7.64028
October 502.00000 24.35516 39.97545 0.48926 10.52689
November 489.00000 24.41113 28.86810 0.40121 8.87947
December 497.00000 24.31489 21.42509 0.31855 7.36741
           
Annual Sum or Average 5943.00000 24.23872 36.89770 0.06887 7.79567
Minimum of Months 454.00000 23.87893 19.28825 -0.3926 6.25701
Maximum of Months 514.00000 24.41113 55.43582 0.48926 10.52689



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: CORE_MID

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 22.19092 26.28059 -0.2314 8.87975
February 454.00000 22.68497 21.11555 -0.1336 6.46796
March 514.00000 23.52050 28.64925 0.13612 5.93394
April 485.00000 23.75111 34.41891 0.25070 6.88697
May 508.00000 24.05909 42.20532 -0.4909 10.51245
June 496.00000 24.18822 52.31098 -0.3506 7.91544
July 497.00000 24.21176 56.05184 -0.3118 7.30878
August 514.00000 24.22848 52.16702 -0.3268 7.60211
September 485.00000 24.16994 48.49727 -0.3951 8.76477
October 502.00000 24.03913 41.19083 0.38427 8.65733
November 489.00000 23.54253 31.85479 0.16014 6.56627
December 497.00000 22.96486 24.44785 -0.0396 5.80322
           
Annual Sum or Average 5943.00000 23.63615 38.39524 -0.1130 7.61949
Minimum of Months 454.00000 22.19092 21.11555 -0.4909 5.80322
Maximum of Months 514.00000 24.22848 56.05184 0.38427 10.51245



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: CORE_TOP

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 21.12114 27.99545 -0.5024 14.02675
February 454.00000 21.40414 22.70596 -0.4598 11.96445
March 514.00000 22.51057 30.91983 -0.1151 7.04527
April 485.00000 23.08576 36.09463 0.08478 7.03445
May 508.00000 23.84853 43.00801 -0.5633 12.60170
June 496.00000 24.17388 52.40054 -0.3438 7.87299
July 497.00000 24.27133 55.85457 -0.2738 6.89081
August 514.00000 24.24607 52.13911 -0.3060 7.39229
September 485.00000 24.01327 49.17760 -0.4472 10.04261
October 502.00000 23.44622 42.90141 0.23539 8.00642
November 489.00000 22.32966 34.66388 -0.1440 8.03681
December 497.00000 21.45030 27.13478 -0.4185 11.06940
           
Annual Sum or Average 5943.00000 23.00427 39.70775 -0.2703 9.31494
Minimum of Months 454.00000 21.12114 22.70596 -0.5633 6.89081
Maximum of Months 514.00000 24.27133 55.85457 0.23539 14.02675



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 21.40278 25.40469 -0.4143 10.25513
February 454.00000 21.64297 20.17251 -0.3828 9.35048
March 514.00000 22.89704 27.65890 -0.0136 6.21912
April 485.00000 23.61541 32.91554 0.22222 7.00794
May 508.00000 24.10898 40.99883 -0.4530 10.15534
June 496.00000 24.31125 51.23344 -0.2412 6.85656
July 497.00000 24.43954 54.71055 -0.1437 6.42046
August 514.00000 24.28296 50.91219 -0.2237 6.68379
September 485.00000 24.19799 47.89379 -0.3656 8.64950
October 502.00000 23.80742 40.25859 0.32566 8.28986
November 489.00000 22.99729 30.38204 0.02534 6.51800
December 497.00000 22.21833 23.17825 -0.2168 6.88581
           
Annual Sum or Average 5943.00000 23.33869 37.27176 -0.1559 7.76391
Minimum of Months 454.00000 21.40278 20.17251 -0.4530 6.21912
Maximum of Months 514.00000 24.43954 54.71055 0.32566 10.25513



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 21.34745 24.89826 -0.4100 10.12076
February 454.00000 21.78262 19.41580 -0.3268 8.92801
March 514.00000 22.62392 27.40296 -0.0326 6.87710
April 485.00000 23.31727 33.04171 0.20751 8.24091
May 508.00000 24.02739 40.97405 -0.3878 10.93798
June 496.00000 24.22350 51.26112 -0.2072 7.19975
July 497.00000 24.34727 54.67284 -0.1109 6.99165
August 514.00000 24.16912 50.93452 -0.1727 6.92699
September 485.00000 24.14647 47.69212 -0.3015 9.33113
October 502.00000 23.68363 40.16542 0.35138 9.27857
November 489.00000 22.66446 30.32492 -0.0214 6.89588
December 497.00000 21.86272 22.88432 -0.2799 7.84765
           
Annual Sum or Average 5943.00000 23.19309 37.10470 -0.1402 8.29283
Minimum of Months 454.00000 21.34745 19.41580 -0.4100 6.87710
Maximum of Months 514.00000 24.34727 54.67284 0.35138 10.93798



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 21.85301 24.45083 -0.2762 10.41198
February 454.00000 22.48531 18.77823 -0.1395 9.22717
March 514.00000 23.00273 26.75992 0.07496 7.48107
April 485.00000 23.51064 32.73030 0.24387 8.49232
May 508.00000 24.01080 41.14326 -0.4449 11.10639
June 496.00000 24.29033 51.15196 -0.2216 6.99166
July 497.00000 24.43027 54.50932 -0.1066 6.65057
August 514.00000 24.31818 50.49160 -0.1164 6.51539
September 485.00000 24.32490 47.17775 -0.2070 8.31294
October 502.00000 24.15514 38.93697 0.51949 12.73538
November 489.00000 23.18706 29.43070 0.12665 7.95155
December 497.00000 22.58660 22.12456 -0.0862 8.35423
           
Annual Sum or Average 5943.00000 23.51993 36.60769 -0.0529 8.68407
Minimum of Months 454.00000 21.85301 18.77823 -0.4449 6.51539
Maximum of Months 514.00000 24.43027 54.50932 0.51949 12.73538



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 21.82673 23.94824 -0.2718 8.35542
February 454.00000 22.47339 18.36432 -0.1305 7.23820
March 514.00000 23.77553 25.25271 0.28393 7.96071
April 485.00000 24.30771 30.88920 0.50303 11.64750
May 508.00000 24.25696 40.27459 -0.2704 8.44173
June 496.00000 24.48234 50.20510 -0.0193 6.71945
July 497.00000 24.59760 53.58696 0.08965 7.28005
August 514.00000 24.47515 49.83098 0.08241 6.74005
September 485.00000 24.34862 46.95759 -0.1819 7.67386
October 502.00000 24.25166 38.70284 0.53351 12.32373
November 489.00000 23.73423 28.16182 0.25978 7.75762
December 497.00000 23.50883 20.53944 0.14055 6.41382
           
Annual Sum or Average 5943.00000 23.84556 35.69075 0.08592 8.21381
Minimum of Months 454.00000 21.82673 18.36432 -0.2718 6.41382
Maximum of Months 514.00000 24.59760 53.58696 0.53351 12.32373



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 20.10773 27.09494 -0.8002 21.19632
February 454.00000 20.28773 21.35717 -0.7756 19.73716
March 514.00000 21.23743 30.32359 -0.4309 10.62007
April 485.00000 22.34871 35.80475 -0.0981 7.62827
May 508.00000 23.70352 42.33335 -0.6112 14.52250
June 496.00000 24.22513 52.58758 -0.2910 7.48468
July 497.00000 24.45881 56.73994 -0.1549 6.65908
August 514.00000 24.31155 52.29616 -0.2476 7.16404
September 485.00000 23.88605 49.25991 -0.4904 11.51005
October 502.00000 22.88896 42.55018 0.09410 7.67724
November 489.00000 21.20597 33.81701 -0.4231 11.32205
December 497.00000 20.36971 25.73973 -0.7109 17.10180
           
Annual Sum or Average 5943.00000 22.43607 39.28969 -0.4093 11.83136
Minimum of Months 454.00000 20.10773 21.35717 -0.8002 6.65908
Maximum of Months 514.00000 24.45881 56.73994 0.09410 21.19632



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 427.00000 20.04092 25.87055 -0.7951 21.36007
February 385.00000 20.47821 20.01202 -0.6957 17.62573
March 433.00000 21.46056 28.96720 -0.3427 10.10052
April 410.00000 22.56271 34.48252 0.00201 8.58029
May 430.00000 23.65497 41.93624 -0.5275 15.70496
June 418.00000 24.21385 52.21936 -0.2274 8.19253
July 422.00000 24.54234 56.06481 -0.0577 7.69792
August 433.00000 24.39106 51.81319 -0.1220 7.27952
September 410.00000 23.90792 48.84109 -0.3993 12.28369
October 427.00000 22.97914 41.39413 0.16471 8.32913
November 417.00000 21.26089 32.70657 -0.3839 10.75213
December 422.00000 20.45987 24.55130 -0.6691 16.11253
           
Annual Sum or Average 5034.00000 22.50897 38.35640 -0.3357 11.96906
Minimum of Months 385.00000 20.04092 20.01202 -0.7951 7.27952
Maximum of Months 433.00000 24.54234 56.06481 0.16471 21.36007



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 21.06621 25.49685 -0.4961 16.13952
February 454.00000 21.79453 19.41244 -0.3258 12.82927
March 514.00000 22.25821 28.08770 -0.1121 9.19286
April 485.00000 22.82609 34.23629 0.06906 8.71358
May 508.00000 23.70530 42.07491 -0.5555 14.47613
June 496.00000 24.20121 52.40394 -0.2641 7.75367
July 497.00000 24.47431 56.25976 -0.1056 6.90394
August 514.00000 24.39576 51.56010 -0.1101 6.85545
September 485.00000 24.19232 47.85585 -0.2516 9.69491
October 502.00000 23.88595 39.56127 0.45669 12.52802
November 489.00000 22.39883 31.18000 -0.0685 9.41107
December 497.00000 21.73007 23.60872 -0.3164 12.09203
           
Annual Sum or Average 5943.00000 23.08724 37.78128 -0.1728 10.53933
Minimum of Months 454.00000 21.06621 19.41244 -0.5555 6.85545
Maximum of Months 514.00000 24.47431 56.25976 0.45669 16.13952



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 20.40860 25.96402 -0.6934 18.17746
February 454.00000 20.75851 20.18806 -0.6182 15.88850
March 514.00000 21.76573 28.63495 -0.2474 9.17947
April 485.00000 22.57256 34.56947 0.02459 8.54924
May 508.00000 23.64006 42.09744 -0.5200 14.42007
June 496.00000 24.25939 51.90576 -0.1639 7.64162
July 497.00000 24.50108 55.78537 -0.0333 7.25723
August 514.00000 24.40997 51.46622 -0.0675 6.89199
September 485.00000 23.86333 48.74223 -0.3899 11.50149
October 502.00000 23.10692 41.37476 0.22060 8.96045
November 489.00000 21.34255 32.75894 -0.3565 10.06962
December 497.00000 20.74238 24.46797 -0.5893 13.88215
           
Annual Sum or Average 5943.00000 22.62985 38.29436 -0.2837 10.99914
Minimum of Months 454.00000 20.40860 20.18806 -0.6934 6.89199
Maximum of Months 514.00000 24.50108 55.78537 0.22060 18.17746



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 19.86897 27.58059 -0.8994 25.23002
February 454.00000 20.00295 22.10711 -0.8935 24.41864
March 514.00000 20.79269 31.45742 -0.5676 14.42952
April 485.00000 21.86806 36.90229 -0.2270 9.73609
May 508.00000 23.42261 43.18811 -0.7049 18.49958
June 496.00000 24.17610 52.94458 -0.2968 7.90969
July 497.00000 24.47069 56.99966 -0.1326 6.78031
August 514.00000 24.29301 52.56484 -0.2396 7.36781
September 485.00000 23.68165 50.09168 -0.5564 14.04017
October 502.00000 22.31029 44.02408 -0.0506 9.36681
November 489.00000 20.59370 35.42457 -0.6017 15.94541
December 497.00000 19.95522 27.22999 -0.8610 23.25159
           
Annual Sum or Average 5943.00000 22.13714 40.17273 -0.4999 14.67830
Minimum of Months 454.00000 19.86897 22.10711 -0.8994 6.78031
Maximum of Months 514.00000 24.47069 56.99966 -0.0506 25.23002



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 19.94124 26.86294 -0.8519 23.76850
February 454.00000 20.23471 21.27927 -0.7888 20.85718
March 514.00000 21.21592 30.22184 -0.4210 12.54941
April 485.00000 22.32727 35.26248 -0.0639 9.60574
May 508.00000 23.47206 42.64800 -0.5747 17.64269
June 496.00000 24.13993 52.54274 -0.2188 8.14434
July 497.00000 24.46540 56.16244 -0.0407 7.55978
August 514.00000 24.31779 51.82882 -0.1017 7.14724
September 485.00000 23.75806 49.32021 -0.4299 13.30375
October 502.00000 22.69019 42.57297 0.09752 9.17717
November 489.00000 20.81323 34.34383 -0.5150 14.21243
December 497.00000 20.09530 26.40492 -0.7963 20.97842
           
Annual Sum or Average 5943.00000 22.30604 39.25134 -0.3893 13.69317
Minimum of Months 454.00000 19.94124 21.27927 -0.8519 7.14724
Maximum of Months 514.00000 24.46540 56.16244 0.09752 23.76850



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 20.67555 26.15222 -0.6239 19.82593
February 454.00000 21.27025 20.34153 -0.4881 16.55005
March 514.00000 21.77375 29.29126 -0.2541 11.90391
April 485.00000 22.37989 35.30743 -0.0524 10.09119
May 508.00000 23.39724 42.98293 -0.6561 18.66962
June 496.00000 24.11785 52.85158 -0.2795 8.44767
July 497.00000 24.45893 56.58872 -0.0915 7.11759
August 514.00000 24.35552 51.87835 -0.1082 7.16607
September 485.00000 23.98964 48.66787 -0.3159 11.65835
October 502.00000 23.48445 40.66298 0.34801 12.20295
November 489.00000 21.74077 32.81887 -0.2529 12.03121
December 497.00000 21.11977 25.27447 -0.5022 16.63578
           
Annual Sum or Average 5943.00000 22.74218 38.70261 -0.2719 12.67131
Minimum of Months 454.00000 20.67555 20.34153 -0.6561 7.11759
Maximum of Months 514.00000 24.45893 56.58872 0.34801 19.82593



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 20.13081 26.50765 -0.7950 21.96511
February 454.00000 20.45071 20.98152 -0.7290 19.77984
March 514.00000 21.38906 29.64524 -0.3617 11.65895
April 485.00000 22.18846 35.50195 -0.0796 9.80468
May 508.00000 23.35802 42.91375 -0.6104 18.16041
June 496.00000 24.17185 52.35379 -0.1804 8.29133
July 497.00000 24.47799 56.12668 -0.0226 7.56039
August 514.00000 24.36894 51.77689 -0.0665 7.21775
September 485.00000 23.64310 49.57706 -0.4576 13.93895
October 502.00000 22.65404 42.57841 0.10597 9.53803
November 489.00000 20.84301 34.14274 -0.5023 13.50624
December 497.00000 20.32120 25.94074 -0.7284 18.68551
           
Annual Sum or Average 5943.00000 22.34950 39.13378 -0.3661 13.29289
Minimum of Months 454.00000 20.13081 20.98152 -0.7950 7.21775
Maximum of Months 514.00000 24.47799 56.12668 0.10597 21.96511



Table of Contents

Report: ChillerReportMonthly

For: COOLSYS1 CHILLER1

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

CHILLER ELECTRICITY ENERGY [J] CHILLER ELECTRICITY RATE {Maximum} [W] CHILLER ELECTRICITY RATE {TIMESTAMP} CHILLER ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] CHILLER EVAPORATOR COOLING ENERGY [J] CHILLER EVAPORATOR COOLING RATE [] CHILLER CONDENSER HEAT TRANSFER ENERGY [J] CHILLER COP [W/W] CHILLER COP {Maximum} [W/W] CHILLER COP {TIMESTAMP} CHILLER PART LOAD RATIO [] CHILLER PART LOAD RATIO []
January 0.317615E+09 5643.35 24-JAN-06:03 55.72 0.135962E+10 0.00 0.167723E+10 0.32 4.29 09-JAN-19:40 0.00 0.00
February 0.485763E+09 8860.25 02-FEB-13:30 64.77 0.207950E+10 0.00 0.256526E+10 0.41 4.29 05-FEB-12:30 0.00 0.00
March 0.294652E+10 98893.54 27-MAR-16:00 81.02 0.151159E+11 0.00 0.180625E+11 0.48 6.93 27-MAR-16:00 0.00 0.00
April 0.228192E+11 200716.79 07-APR-14:00 138.66 0.131882E+12 0.00 0.154701E+12 0.96 7.54 07-APR-13:50 0.00 0.00
May 0.703544E+11 206508.91 30-MAY-08:20 328.91 0.420979E+12 0.00 0.491333E+12 2.35 7.56 30-MAY-14:05 0.00 0.00
June 0.183862E+12 219646.15 19-JUN-17:10 508.45 0.124515E+13 0.00 0.142901E+13 4.45 7.57 23-JUN-05:04 0.00 0.00
July 0.227262E+12 224732.66 20-JUL-17:10 619.51 0.152649E+13 0.00 0.175375E+13 5.14 7.56 12-JUL-04:13 0.00 0.00
August 0.220934E+12 227440.61 04-AUG-16:20 650.72 0.148820E+13 0.00 0.170913E+13 5.30 7.57 30-AUG-13:00 0.00 0.00
September 0.135709E+12 213363.08 14-SEP-04:12 427.23 0.894267E+12 0.00 0.102998E+13 3.57 7.57 02-SEP-04:13 0.00 0.00
October 0.670584E+11 210070.58 03-OCT-12:00 254.87 0.424136E+12 0.00 0.491195E+12 1.90 7.55 13-OCT-14:00 0.00 0.00
November 0.353632E+10 63749.35 03-NOV-14:00 72.56 0.155281E+11 0.00 0.190644E+11 0.43 5.43 03-NOV-14:00 0.00 0.00
December 0.569409E+09 9119.73 21-DEC-11:50 83.99 0.243777E+10 0.00 0.300718E+10 0.48 4.29 06-DEC-06:40 0.00 0.00
                         
Annual Sum or Average 0.935854E+12     3286.41 0.616763E+13 0.00 0.710348E+13 2.16     0.00 0.00
Minimum of Months 0.317615E+09 5643.35   55.72 0.135962E+10 0.00 0.167723E+10 0.32 4.29   0.00 0.00
Maximum of Months 0.227262E+12 227440.61   650.72 0.152649E+13 0.00 0.175375E+13 5.30 7.57   0.00 0.00



Table of Contents

Report: ChillerReportMonthly

For: COOLSYS1 CHILLER2

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

CHILLER ELECTRICITY ENERGY [J] CHILLER ELECTRICITY RATE {Maximum} [W] CHILLER ELECTRICITY RATE {TIMESTAMP} CHILLER ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] CHILLER EVAPORATOR COOLING ENERGY [J] CHILLER EVAPORATOR COOLING RATE [] CHILLER CONDENSER HEAT TRANSFER ENERGY [J] CHILLER COP [W/W] CHILLER COP {Maximum} [W/W] CHILLER COP {TIMESTAMP} CHILLER PART LOAD RATIO [] CHILLER PART LOAD RATIO []
January 0.00 0.00 01-JAN-00:01 0.00 0.00 0.00 0.00 0.00 0.00 01-JAN-00:01 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 0.00 0.00
April 0.383913E+09 125894.85 07-APR-14:20 1.17 0.265030E+10 0.00 0.303421E+10 0.01 7.34 07-APR-14:20 0.00 0.00
May 0.489044E+10 181079.10 30-MAY-13:25 12.00 0.345478E+11 0.00 0.394382E+11 0.11 7.42 30-MAY-13:55 0.00 0.00
June 0.404272E+11 206016.84 22-JUN-15:43 93.01 0.279970E+12 0.00 0.320397E+12 0.89 7.43 01-JUN-15:00 0.00 0.00
July 0.762592E+11 215501.28 28-JUL-05:04 166.44 0.517211E+12 0.00 0.593470E+12 1.52 7.39 11-JUL-15:33 0.00 0.00
August 0.743046E+11 190567.16 24-AUG-16:23 159.34 0.506553E+12 0.00 0.580857E+12 1.46 7.53 25-AUG-13:33 0.00 0.00
September 0.231479E+11 160163.00 14-SEP-04:15 53.32 0.160342E+12 0.00 0.183490E+12 0.51 7.40 01-SEP-13:55 0.00 0.00
October 0.769429E+10 128291.12 24-OCT-14:00 18.67 0.545117E+11 0.00 0.622060E+11 0.18 7.26 04-OCT-10:20 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 0.00 0.00
                         
Annual Sum or Average 0.227108E+12     503.94 0.155578E+13 0.00 0.178289E+13 0.39     0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00 0.00   0.00 0.00
Maximum of Months 0.762592E+11 215501.28   166.44 0.517211E+12 0.00 0.593470E+12 1.52 7.53   0.00 0.00



Table of Contents

Report: TowerReportMonthly

For: CENTRAL TOWER

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

COOLING TOWER FAN ELECTRICITY ENERGY [J] COOLING TOWER FAN ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] COOLING TOWER FAN ELECTRICITY RATE {Maximum} [W] COOLING TOWER FAN ELECTRICITY RATE {TIMESTAMP} COOLING TOWER HEAT TRANSFER RATE {Maximum} [W] COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} COOLING TOWER INLET TEMPERATURE [C] COOLING TOWER OUTLET TEMPERATURE [C] COOLING TOWER MASS FLOW RATE [kg/s]
January 0.102807E+11 744.00 9619.51 24-JAN-12:00 184421.00 20-JAN-16:30 21.55 18.33 14.29
February 0.144266E+11 672.00 17274.24 20-FEB-12:00 325533.38 22-FEB-17:00 24.38 18.33 14.29
March 0.491207E+11 744.00 49248.27 02-MAR-15:30 586052.29 31-MAR-24:00 27.46 18.41 14.29
April 0.973042E+11 720.00 49248.27 05-APR-10:30 672205.22 07-APR-17:20 31.51 19.54 14.29
May 0.861885E+11 744.00 49248.27 01-MAY-10:40 336992.25 31-MAY-23:40 23.54 19.72 14.29
June 0.127086E+12 720.00 49248.27 01-JUN-00:10 480455.87 30-JUN-24:00 31.92 24.89 14.29
July 0.131907E+12 744.00 49248.27 01-JUL-00:10 644005.09 31-JUL-24:00 39.87 29.68 14.29
August 0.131907E+12 744.00 49248.27 01-AUG-00:03 707239.95 04-AUG-21:01 43.78 30.75 14.29
September 0.114943E+12 720.00 49248.27 01-SEP-00:03 320172.78 30-SEP-24:00 26.26 22.24 14.29
October 0.934124E+11 744.00 49248.27 02-OCT-08:65 451960.46 31-OCT-24:00 26.32 19.68 14.29
November 0.603337E+11 720.00 49248.27 01-NOV-13:50 486161.43 03-NOV-15:10 27.48 18.42 14.29
December 0.523061E+11 744.00 45600.62 17-DEC-15:00 603996.67 08-DEC-16:10 30.01 18.33 14.29
                   
Annual Sum or Average 0.969215E+12 8760.00         29.55 21.56 14.29
Minimum of Months 0.102807E+11 672.00 9619.51   184421.00   21.55 18.33 14.29
Maximum of Months 0.131907E+12 744.00 49248.27   707239.95   43.78 30.75 14.29



Table of Contents

Report: TowerReportMonthly

For: TOWERWATERSYS COOLTOWER 1

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

COOLING TOWER FAN ELECTRICITY ENERGY [J] COOLING TOWER FAN ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] COOLING TOWER FAN ELECTRICITY RATE {Maximum} [W] COOLING TOWER FAN ELECTRICITY RATE {TIMESTAMP} COOLING TOWER HEAT TRANSFER RATE {Maximum} [W] COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} COOLING TOWER INLET TEMPERATURE [C] COOLING TOWER OUTLET TEMPERATURE [C] COOLING TOWER MASS FLOW RATE [kg/s]
January 0.00 0.00 0.00 01-JAN-00:01 291664.63 31-JAN-15:07 20.97 20.96 0.46
February 0.00 0.00 0.00 01-FEB-00:10 291655.69 03-FEB-17:03 20.95 20.95 0.38
March 40373788.64 7.50 2952.31 27-MAR-16:00 789610.47 27-MAR-16:00 20.96 20.94 2.13
April 0.517503E+09 84.36 22077.24 07-APR-12:30 1615303.24 07-APR-14:00 21.22 21.02 10.98
May 0.302789E+10 247.96 22077.24 18-MAY-09:50 1685430.90 30-MAY-08:20 21.81 21.21 30.20
June 0.265833E+11 481.14 22077.24 01-JUN-09:30 1593260.06 08-JUN-13:20 24.21 22.44 50.46
July 0.458066E+11 616.66 22077.24 01-JUL-04:12 1540844.96 11-JUL-09:40 26.06 23.94 57.38
August 0.360518E+11 609.87 22077.24 01-AUG-00:23 1694933.54 30-AUG-11:00 25.17 23.09 60.85
September 0.137802E+11 382.81 22077.24 01-SEP-04:12 1526031.50 28-SEP-14:20 23.33 22.04 42.14
October 0.577696E+10 210.61 22077.24 02-OCT-12:30 1596203.26 12-OCT-13:50 21.89 21.29 24.16
November 11645760.32 14.75 772.63 10-NOV-10:00 425360.47 03-NOV-14:00 20.98 20.95 3.19
December 0.00 0.00 0.00 01-DEC-00:10 292079.51 21-DEC-10:50 20.92 20.91 0.61
                   
Annual Sum or Average 0.131596E+12 2655.66         22.38 21.65 23.74
Minimum of Months 0.00 0.00 0.00   291655.69   20.92 20.91 0.38
Maximum of Months 0.458066E+11 616.66 22077.24   1694933.54   26.06 23.94 60.85



Table of Contents

Report: TowerReportMonthly

For: TOWERWATERSYS COOLTOWER 2

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

COOLING TOWER FAN ELECTRICITY ENERGY [J] COOLING TOWER FAN ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] COOLING TOWER FAN ELECTRICITY RATE {Maximum} [W] COOLING TOWER FAN ELECTRICITY RATE {TIMESTAMP} COOLING TOWER HEAT TRANSFER RATE {Maximum} [W] COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} COOLING TOWER INLET TEMPERATURE [C] COOLING TOWER OUTLET TEMPERATURE [C] COOLING TOWER MASS FLOW RATE [kg/s]
January 0.00 0.00 0.00 01-JAN-00:01 0.00 01-JAN-00:01 20.97 20.97 0.00
February 0.00 0.00 0.00 01-FEB-00:10 0.00 01-FEB-00:10 20.95 20.95 0.00
March 0.00 0.00 0.00 01-MAR-00:10 0.00 01-MAR-00:10 20.96 20.96 0.00
April 26492682.97 0.33 22077.24 07-APR-14:20 1383239.73 07-APR-14:20 21.22 21.22 0.03
May 0.900751E+09 11.33 22077.24 30-MAY-09:00 1356189.10 30-MAY-13:25 21.81 21.76 1.13
June 0.103874E+11 130.77 22077.24 01-JUN-10:10 1527016.53 22-JUN-15:43 24.21 23.57 11.67
July 0.215483E+11 271.12 22077.24 01-JUL-08:30 1404326.98 28-JUL-05:04 26.06 24.76 22.17
August 0.179110E+11 228.99 22077.24 01-AUG-07:10 1562963.95 30-AUG-16:00 25.17 24.06 19.48
September 0.605733E+10 76.21 22077.24 01-SEP-04:14 1257409.06 01-SEP-13:50 23.33 22.95 6.77
October 0.152333E+10 19.17 22077.24 03-OCT-10:30 1139262.37 13-OCT-13:40 21.89 21.80 1.88
November 0.00 0.00 0.00 01-NOV-00:10 0.00 01-NOV-00:10 20.98 20.98 0.00
December 0.00 0.00 0.00 01-DEC-00:10 0.00 01-DEC-00:10 20.92 20.92 0.00
                   
Annual Sum or Average 0.583546E+11 737.92         22.38 22.08 5.31
Minimum of Months 0.00 0.00 0.00   0.00   20.92 20.92 0.00
Maximum of Months 0.215483E+11 271.12 22077.24   1562963.95   26.06 24.76 22.17



Table of Contents

Report: BoilerReportMonthly

For: HEATSYS1 BOILER

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

BOILER HEATING ENERGY [J] BOILER GAS CONSUMPTION [] BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] BOILER HEATING RATE {Maximum} [W] BOILER HEATING RATE {TIMESTAMP} BOILER GAS CONSUMPTION RATE [] BOILER INLET TEMPERATURE [C] BOILER OUTLET TEMPERATURE [C] BOILER MASS FLOW RATE [kg/s] BOILER ANCILLARY ELECTRICITY RATE [W] BOILER PART LOAD RATIO [] BOILER PART LOAD RATIO {Maximum} [] BOILER PART LOAD RATIO {TIMESTAMP}
January 0.308529E+12 0.00 544.38 2390801.66 03-JAN-05:11 0.00 30.59 67.47 0.63 0.00 0.04 0.84 03-JAN-05:11
February 0.239172E+12 0.00 474.57 1914634.47 13-FEB-05:01 0.00 29.65 65.34 0.53 0.00 0.03 0.67 13-FEB-05:01
March 0.970796E+11 0.00 379.78 1557624.50 10-MAR-05:01 0.00 26.92 53.47 0.19 0.00 0.01 0.55 10-MAR-05:01
April 0.312574E+11 0.00 212.14 1578629.89 21-APR-04:11 0.00 26.35 42.53 0.06 0.00 0.00 0.56 21-APR-04:11
May 0.880534E+09 0.00 40.58 113040.46 01-MAY-05:03 0.00 23.89 27.07 0.00 0.00 0.00 0.04 01-MAY-05:03
June 0.111670E+10 0.00 11.49 169659.24 01-JUN-15:17 0.00 50.23 50.77 0.00 0.00 0.00 0.06 01-JUN-15:17
July 0.291686E+09 0.00 6.60 44378.54 11-JUL-13:25 0.00 49.14 49.41 0.00 0.00 0.00 0.02 11-JUL-13:25
August 0.178042E+10 0.00 19.64 154717.99 24-AUG-16:40 0.00 46.72 47.66 0.00 0.00 0.00 0.05 24-AUG-16:40
September 0.178404E+09 0.00 12.29 69336.09 01-SEP-13:55 0.00 38.56 39.31 0.00 0.00 0.00 0.02 01-SEP-13:55
October 0.637853E+10 0.00 90.97 763841.34 28-OCT-05:03 0.00 27.28 34.07 0.01 0.00 0.00 0.27 28-OCT-05:03
November 0.867319E+11 0.00 335.43 1650922.48 27-NOV-05:11 0.00 26.30 51.24 0.17 0.00 0.01 0.58 27-NOV-05:11
December 0.194007E+12 0.00 476.94 1609875.83 26-DEC-05:11 0.00 29.27 61.60 0.38 0.00 0.03 0.57 26-DEC-05:11
                           
Annual Sum or Average 0.967403E+12 0.00 2604.80     0.00 33.76 49.06 0.16 0.00 0.01    
Minimum of Months 0.178404E+09 0.00 6.60 44378.54   0.00 23.89 27.07 0.00 0.00 0.00 0.02  
Maximum of Months 0.308529E+12 0.00 544.38 2390801.66   0.00 50.23 67.47 0.63 0.00 0.04 0.84  



Table of Contents

Report: BoilerReportMonthly

For: CENTRAL BOILER

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

BOILER HEATING ENERGY [J] BOILER GAS CONSUMPTION [] BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] BOILER HEATING RATE {Maximum} [W] BOILER HEATING RATE {TIMESTAMP} BOILER GAS CONSUMPTION RATE [] BOILER INLET TEMPERATURE [C] BOILER OUTLET TEMPERATURE [C] BOILER MASS FLOW RATE [kg/s] BOILER ANCILLARY ELECTRICITY RATE [W] BOILER PART LOAD RATIO [] BOILER PART LOAD RATIO []
January 0.00 0.00 0.00 0.00 01-JAN-00:01 0.00 21.55 21.55 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 01-FEB-00:10 0.00 24.38 24.38 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 01-MAR-00:10 0.00 27.46 27.46 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 01-APR-00:10 0.00 31.51 31.51 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 01-MAY-00:10 0.00 23.54 23.54 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 01-JUN-00:10 0.00 31.92 31.92 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 01-JUL-00:10 0.00 39.87 39.87 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 01-AUG-00:03 0.00 43.78 43.78 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 01-SEP-00:03 0.00 26.26 26.26 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 01-OCT-00:10 0.00 26.32 26.32 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 01-NOV-00:10 0.00 27.48 27.48 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 01-DEC-00:10 0.00 30.01 30.01 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.00 0.00 0.00     0.00 29.55 29.55 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00   0.00 21.55 21.55 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00   0.00 43.78 43.78 0.00 0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: VAV_BOT WITH REHEAT COOLING COIL

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 30689871.65 0.00 26.53 30689871.65 0.00 0.00 0.00 0.00 9748.83 31-JAN-15:20 9748.83 31-JAN-15:20 0.00 0.00 0.00
February 33164750.17 0.00 16.64 33164750.17 0.00 0.00 0.00 0.00 8367.16 03-FEB-12:00 8367.16 03-FEB-12:00 0.00 0.00 0.00
March 0.153871E+10 0.00 42.41 0.148852E+10 0.00 0.00 0.00 0.00 76666.58 27-MAR-16:00 76666.58 27-MAR-16:00 0.00 0.00 0.00
April 0.138862E+11 0.00 115.78 0.138775E+11 0.00 0.00 0.00 0.00 137783.56 07-APR-14:50 137783.56 07-APR-14:50 0.00 0.00 0.00
May 0.403927E+11 0.00 311.40 0.361379E+11 0.00 0.00 0.00 0.00 209454.68 30-MAY-10:55 209454.68 30-MAY-10:55 0.00 0.00 0.00
June 0.136685E+12 0.00 492.39 0.108156E+12 0.00 0.00 0.00 0.00 229985.90 17-JUN-04:11 198372.53 22-JUN-15:07 0.00 0.00 0.00
July 0.187238E+12 0.00 589.50 0.149756E+12 0.00 0.00 0.00 0.00 243308.66 10-JUL-04:23 178205.55 11-JUL-14:00 0.00 0.00 0.00
August 0.190024E+12 0.00 630.78 0.164056E+12 0.00 0.00 0.00 0.00 231242.36 14-AUG-05:03 207471.63 22-AUG-14:15 0.00 0.00 0.00
September 0.913896E+11 0.00 411.98 0.762071E+11 0.00 0.00 0.00 0.00 234345.79 14-SEP-04:12 189272.69 01-SEP-14:00 0.00 0.00 0.00
October 0.443280E+11 0.00 243.54 0.330422E+11 0.00 0.00 0.00 0.00 174198.93 06-OCT-04:12 113324.71 04-OCT-14:50 0.00 0.00 0.00
November 0.144257E+10 0.00 39.50 0.134262E+10 0.00 0.00 0.00 0.00 59107.71 10-NOV-06:03 34990.11 03-NOV-14:00 0.00 0.00 0.00
December 33420230.76 0.00 17.50 33420230.76 0.00 0.00 0.00 0.00 5720.14 21-DEC-09:40 5720.14 21-DEC-09:40 0.00 0.00 0.00
                               
Annual Sum or Average 0.707021E+12 0.00 2937.94 0.584161E+12 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 30689871.65 0.00 16.64 30689871.65 0.00 0.00 0.00 0.00 5720.14   5720.14   0.00 0.00 0.00
Maximum of Months 0.190024E+12 0.00 630.78 0.164056E+12 0.00 0.00 0.00 0.00 243308.66   209454.68   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: VAV_MID WITH REHEAT COOLING COIL

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 83389854.80 0.00 37.22 83389854.80 0.00 0.00 0.00 0.00 34434.83 13-JAN-14:25 34434.83 13-JAN-14:25 0.00 0.00 0.00
February 0.500964E+09 0.00 47.49 0.500964E+09 0.00 0.00 0.00 0.00 48871.94 01-FEB-13:55 48871.94 01-FEB-13:55 0.00 0.00 0.00
March 0.103138E+11 0.00 48.04 0.102482E+11 0.00 0.00 0.00 0.00 519836.80 27-MAR-16:00 519836.80 27-MAR-16:00 0.00 0.00 0.00
April 0.100759E+12 0.00 112.15 0.100734E+12 0.00 0.00 0.00 0.00 1198849.58 07-APR-14:50 1198849.58 07-APR-14:50 0.00 0.00 0.00
May 0.351039E+12 0.00 309.30 0.314517E+12 0.00 0.00 0.00 0.00 1738838.52 30-MAY-13:20 1738838.52 30-MAY-13:20 0.00 0.00 0.00
June 0.116555E+13 0.00 447.60 0.893492E+12 0.00 0.00 0.00 0.00 2207889.43 19-JUN-04:12 1792242.23 22-JUN-13:20 0.00 0.00 0.00
July 0.154987E+13 0.00 473.05 0.117139E+13 0.00 0.00 0.00 0.00 2684825.51 28-JUL-05:02 1700093.20 11-JUL-15:20 0.00 0.00 0.00
August 0.151033E+13 0.00 478.51 0.126034E+13 0.00 0.00 0.00 0.00 2511481.48 24-AUG-16:27 2511481.48 24-AUG-16:27 0.00 0.00 0.00
September 0.810218E+12 0.00 398.30 0.663230E+12 0.00 0.00 0.00 0.00 2236703.19 07-SEP-04:11 1732149.78 01-SEP-13:50 0.00 0.00 0.00
October 0.363990E+12 0.00 241.67 0.270151E+12 0.00 0.00 0.00 0.00 1493825.61 06-OCT-05:03 1013691.40 04-OCT-15:00 0.00 0.00 0.00
November 0.112321E+11 0.00 52.47 0.106716E+11 0.00 0.00 0.00 0.00 535021.37 10-NOV-06:03 274576.24 03-NOV-14:00 0.00 0.00 0.00
December 0.362224E+09 0.00 56.11 0.362224E+09 0.00 0.00 0.00 0.00 95587.30 22-DEC-13:23 95587.30 22-DEC-13:23 0.00 0.00 0.00
                               
Annual Sum or Average 0.587425E+13 0.00 2701.92 0.469572E+13 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 83389854.80 0.00 37.22 83389854.80 0.00 0.00 0.00 0.00 34434.83   34434.83   0.00 0.00 0.00
Maximum of Months 0.154987E+13 0.00 478.51 0.126034E+13 0.00 0.00 0.00 0.00 2684825.51   2511481.48   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: VAV_TOP WITH REHEAT COOLING COIL

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 20382840.87 0.00 28.25 20382840.87 0.00 0.00 0.00 0.00 1314.90 15-JAN-10:40 1314.90 15-JAN-10:40 0.00 0.00 0.00
February 30258728.19 0.00 35.40 30258728.19 0.00 0.00 0.00 0.00 1320.52 10-FEB-11:30 1320.52 10-FEB-11:30 0.00 0.00 0.00
March 0.810308E+09 0.00 62.65 0.808680E+09 0.00 0.00 0.00 0.00 45828.42 27-MAR-16:00 45828.42 27-MAR-16:00 0.00 0.00 0.00
April 0.101328E+11 0.00 113.92 0.101328E+11 0.00 0.00 0.00 0.00 122817.13 07-APR-14:40 122817.13 07-APR-14:40 0.00 0.00 0.00
May 0.360933E+11 0.00 299.86 0.326655E+11 0.00 0.00 0.00 0.00 214974.71 30-MAY-13:35 197995.91 30-MAY-13:45 0.00 0.00 0.00
June 0.123930E+12 0.00 445.17 0.963734E+11 0.00 0.00 0.00 0.00 237098.65 19-JUN-04:12 204220.97 22-JUN-15:07 0.00 0.00 0.00
July 0.169467E+12 0.00 474.36 0.129606E+12 0.00 0.00 0.00 0.00 278650.31 28-JUL-05:02 199398.08 11-JUL-15:37 0.00 0.00 0.00
August 0.163785E+12 0.00 480.15 0.137925E+12 0.00 0.00 0.00 0.00 250972.32 22-AUG-14:07 247917.80 22-AUG-14:07 0.00 0.00 0.00
September 0.822274E+11 0.00 393.07 0.673085E+11 0.00 0.00 0.00 0.00 222420.20 08-SEP-05:02 210020.78 01-SEP-13:55 0.00 0.00 0.00
October 0.340670E+11 0.00 230.63 0.253589E+11 0.00 0.00 0.00 0.00 148453.68 06-OCT-05:03 113417.17 04-OCT-14:50 0.00 0.00 0.00
November 0.856459E+09 0.00 51.92 0.816618E+09 0.00 0.00 0.00 0.00 21636.91 03-NOV-14:00 21636.91 03-NOV-14:00 0.00 0.00 0.00
December 31298225.53 0.00 63.10 31298225.53 0.00 0.00 0.00 0.00 1628.38 21-DEC-11:00 1628.38 21-DEC-11:00 0.00 0.00 0.00
                               
Annual Sum or Average 0.621451E+12 0.00 2678.48 0.501078E+12 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 20382840.87 0.00 28.25 20382840.87 0.00 0.00 0.00 0.00 1314.90   1314.90   0.00 0.00 0.00
Maximum of Months 0.169467E+12 0.00 480.15 0.137925E+12 0.00 0.00 0.00 0.00 278650.31   247917.80   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: CAV_BAS COOLING COIL

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 8365601.80 0.00 0.97 3695369.92 0.00 0.00 0.00 0.00 41279.37 24-JAN-06:03 18154.89 24-JAN-06:03 0.00 0.00 0.00
February 205417.82 0.00 1.80 205417.82 0.00 0.00 0.00 0.00 141.10 07-FEB-11:40 141.10 07-FEB-11:40 0.00 0.00 0.00
March 0.668977E+09 0.00 8.71 0.668977E+09 0.00 0.00 0.00 0.00 46134.71 27-MAR-16:00 46134.71 27-MAR-16:00 0.00 0.00 0.00
April 0.616579E+10 0.00 71.64 0.613196E+10 0.00 0.00 0.00 0.00 73829.54 07-APR-13:50 73829.54 07-APR-13:50 0.00 0.00 0.00
May 0.182068E+11 0.00 188.41 0.172011E+11 0.00 0.00 0.00 0.00 117771.82 29-MAY-10:00 117771.82 29-MAY-10:00 0.00 0.00 0.00
June 0.742961E+11 0.00 389.35 0.621839E+11 0.00 0.00 0.00 0.00 155875.05 19-JUN-04:53 109164.97 12-JUN-04:12 0.00 0.00 0.00
July 0.104256E+12 0.00 410.12 0.826540E+11 0.00 0.00 0.00 0.00 181931.03 09-JUL-16:11 112271.17 04-JUL-14:11 0.00 0.00 0.00
August 0.105313E+12 0.00 447.10 0.887778E+11 0.00 0.00 0.00 0.00 158344.91 13-AUG-15:38 134585.25 13-AUG-13:34 0.00 0.00 0.00
September 0.555445E+11 0.00 336.51 0.486349E+11 0.00 0.00 0.00 0.00 148449.35 14-SEP-04:53 111811.99 01-SEP-13:45 0.00 0.00 0.00
October 0.214916E+11 0.00 177.95 0.177560E+11 0.00 0.00 0.00 0.00 123504.17 06-OCT-04:53 64273.33 25-OCT-14:00 0.00 0.00 0.00
November 0.201819E+09 0.00 7.66 0.181230E+09 0.00 0.00 0.00 0.00 81721.74 10-NOV-06:03 33042.34 10-NOV-06:03 0.00 0.00 0.00
December 424.63 0.00 0.17 424.63 0.00 0.00 0.00 0.00 0.71 30-DEC-16:40 0.71 30-DEC-16:40 0.00 0.00 0.00
                               
Annual Sum or Average 0.386153E+12 0.00 2040.41 0.324194E+12 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 424.63 0.00 0.17 424.63 0.00 0.00 0.00 0.00 0.71   0.71   0.00 0.00 0.00
Maximum of Months 0.105313E+12 0.00 447.10 0.887778E+11 0.00 0.00 0.00 0.00 181931.03   134585.25   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: AIRLOOP DATACENTER BASEMENT COOLING COIL

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [J] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [J] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION {Maximum} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL RUNTIME FRACTION {MINIMUM} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE {Maximum} [W] COOLING COIL LATENT COOLING RATE {TIMESTAMP} COOLING COIL ELECTRICITY RATE {Maximum} [W] COOLING COIL ELECTRICITY RATE {TIMESTAMP} COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.318840E+12 0.800311E+11 744.00 0.318713E+12 0.126539E+09 0.00 0.34 20-JAN-22:03 0.28 02-JAN-07:15 124757.31 20-JAN-22:10 124757.31 20-JAN-22:10 2528.07 24-JAN-15:20 31264.51 20-JAN-22:03 0.00
February 0.508268E+12 0.121428E+12 672.00 0.508268E+12 -0.0 0.00 0.55 21-FEB-22:03 0.51 06-FEB-07:05 216019.57 17-FEB-22:03 216019.57 17-FEB-22:03 0.00 03-FEB-19:10 51416.34 21-FEB-22:03 0.00
March 0.813321E+12 0.186236E+12 744.00 0.813107E+12 0.214130E+09 0.00 0.92 31-MAR-24:00 0.72 07-MAR-07:05 394121.37 31-MAR-24:00 394121.37 31-MAR-24:00 5587.55 27-MAR-15:00 89622.12 27-MAR-16:00 0.00
April 0.102827E+13 0.234302E+12 720.00 0.102784E+13 0.433613E+09 0.00 1.00 07-APR-11:40 0.36 30-APR-24:00 405377.02 27-APR-15:50 402547.56 07-APR-17:30 5608.82 27-APR-16:00 129533.13 07-APR-13:00 0.00
May 0.333982E+12 0.864955E+11 744.00 0.331409E+12 0.257338E+10 0.00 0.54 31-MAY-23:20 0.31 20-MAY-07:00 213626.53 31-MAY-24:00 212162.78 31-MAY-24:00 7395.54 19-MAY-15:00 55845.43 31-MAY-23:20 0.00
June 0.570037E+12 0.162982E+12 720.00 0.561976E+12 0.806052E+10 0.00 0.76 30-JUN-24:00 0.53 02-JUN-06:20 304106.66 30-JUN-24:00 303723.20 30-JUN-24:00 12601.08 15-JUN-14:00 97242.37 19-JUN-12:00 0.00
July 0.839828E+12 0.262291E+12 744.00 0.828742E+12 0.110861E+11 0.00 0.98 31-JUL-24:00 0.76 02-JUL-03:00 395944.57 31-JUL-24:00 395944.57 31-JUL-24:00 13743.72 20-JUL-15:00 125821.15 07-JUL-12:00 0.00
August 0.107870E+13 0.331609E+12 744.00 0.107113E+13 0.757088E+10 0.00 1.00 01-AUG-06:50 0.38 31-AUG-24:00 413977.40 18-AUG-19:00 406446.63 18-AUG-23:03 13644.45 03-AUG-16:10 149169.84 24-AUG-16:00 0.00
September 0.332361E+12 0.924229E+11 720.00 0.326697E+12 0.566353E+10 0.00 0.53 30-SEP-24:00 0.31 30-SEP-06:30 212150.71 30-SEP-24:00 212150.71 30-SEP-24:00 10791.17 07-SEP-15:00 51359.31 01-SEP-13:55 0.00
October 0.582945E+12 0.142957E+12 744.00 0.578946E+12 0.399843E+10 0.00 0.73 31-OCT-24:00 0.53 21-OCT-06:40 304024.81 31-OCT-24:00 304024.81 31-OCT-24:00 8431.51 06-OCT-09:30 70498.77 25-OCT-11:00 0.00
November 0.792092E+12 0.180738E+12 720.00 0.791701E+12 0.390511E+09 0.00 0.77 03-NOV-14:00 0.72 01-NOV-06:10 313407.53 10-NOV-10:40 309601.48 02-NOV-21:03 6447.33 10-NOV-08:45 79609.62 03-NOV-14:00 0.00
December 0.105960E+13 0.234034E+12 744.00 0.105960E+13 -0.0 0.00 0.95 29-DEC-22:02 0.92 04-DEC-17:10 401184.24 14-DEC-22:02 401184.24 14-DEC-22:02 0.00 03-DEC-15:08 88463.12 29-DEC-22:02 0.00
                                       
Annual Sum or Average 0.825824E+13 0.211553E+13 8760.00 0.821812E+13 0.401176E+11 0.00                         0.00
Minimum of Months 0.318840E+12 0.800311E+11 672.00 0.318713E+12 -0.0 0.00 0.34   0.28   124757.31   124757.31   0.00   31264.51   0.00
Maximum of Months 0.107870E+13 0.331609E+12 744.00 0.107113E+13 0.110861E+11 0.00 1.00   0.92   413977.40   406446.63   13743.72   149169.84   0.00



Table of Contents

Report: DXReportMonthly

For: AIRLOOP DATACENTER BOT COOLING COIL

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [J] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [J] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION {Maximum} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL RUNTIME FRACTION {MINIMUM} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE {Maximum} [W] COOLING COIL LATENT COOLING RATE {TIMESTAMP} COOLING COIL ELECTRICITY RATE {Maximum} [W] COOLING COIL ELECTRICITY RATE {TIMESTAMP} COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.342463E+10 0.925890E+09 742.86 0.341956E+10 5067435.31 0.00 0.30 20-JAN-16:30 0.00 01-JAN-08:55 2385.29 20-JAN-16:30 2385.29 20-JAN-16:30 101.21 24-JAN-15:20 607.12 20-JAN-16:30 0.00
February 0.814537E+10 0.206965E+10 672.00 0.814537E+10 -0.0 0.00 0.55 14-FEB-17:00 0.27 06-FEB-07:05 4447.60 22-FEB-17:00 4447.60 22-FEB-17:00 0.00 05-FEB-07:00 1112.32 14-FEB-17:00 0.00
March 0.151389E+11 0.353414E+10 744.00 0.151279E+11 11012221.15 0.00 0.79 31-MAR-24:00 0.56 01-MAR-07:05 7503.99 31-MAR-24:00 7503.99 31-MAR-24:00 217.78 27-MAR-15:00 1845.53 27-MAR-17:00 0.00
April 0.199996E+11 0.456226E+10 720.00 0.199776E+11 22030708.34 0.00 0.95 12-APR-17:40 0.30 30-APR-24:00 8978.91 23-APR-17:44 8978.91 23-APR-17:44 219.30 27-APR-16:00 2654.77 07-APR-17:00 0.00
May 0.589798E+10 0.151864E+10 744.00 0.579716E+10 0.100816E+09 0.00 0.47 31-MAY-23:30 0.19 04-MAY-07:00 4156.55 31-MAY-24:00 4103.44 31-MAY-24:00 289.72 18-MAY-15:30 1065.38 31-MAY-23:20 0.00
June 0.112284E+11 0.315223E+10 720.00 0.109028E+11 0.325641E+09 0.00 0.66 30-JUN-24:00 0.43 02-JUN-06:30 5941.84 30-JUN-24:00 5922.71 30-JUN-24:00 525.02 15-JUN-14:00 1995.91 19-JUN-12:10 0.00
July 0.168872E+11 0.517643E+10 744.00 0.164088E+11 0.478405E+09 0.00 0.87 31-JUL-24:00 0.66 02-JUL-03:10 7814.26 31-JUL-24:00 7814.26 31-JUL-24:00 608.83 20-JUL-15:00 2579.93 10-JUL-15:00 0.00
August 0.219419E+11 0.671031E+10 744.00 0.215709E+11 0.370984E+09 0.00 1.00 01-AUG-13:30 0.31 31-AUG-24:00 9206.20 31-AUG-18:00 8860.32 31-AUG-17:50 612.73 03-AUG-15:00 3271.57 24-AUG-16:00 0.00
September 0.606806E+10 0.166769E+10 720.00 0.585412E+10 0.213932E+09 0.00 0.45 30-SEP-24:00 0.20 30-SEP-06:55 3961.58 30-SEP-24:00 3961.58 30-SEP-24:00 456.47 07-SEP-15:00 1056.55 14-SEP-14:00 0.00
October 0.109845E+11 0.269473E+10 744.00 0.108290E+11 0.155444E+09 0.00 0.61 31-OCT-24:00 0.39 28-OCT-06:55 5704.42 31-OCT-24:00 5702.84 31-OCT-24:00 346.33 05-OCT-16:00 1459.18 04-OCT-16:00 0.00
November 0.146481E+11 0.338272E+10 720.00 0.146299E+11 18187496.52 0.00 0.71 23-NOV-15:55 0.57 21-NOV-07:10 6462.81 03-NOV-16:00 6462.81 03-NOV-16:00 256.69 10-NOV-10:30 1558.49 03-NOV-14:00 0.00
December 0.198312E+11 0.455704E+10 744.00 0.198312E+11 -0.0 0.00 0.93 03-DEC-15:43 0.76 30-DEC-08:00 8316.29 17-DEC-15:57 8316.29 17-DEC-15:57 0.00 05-DEC-06:05 1899.84 17-DEC-15:53 0.00
                                       
Annual Sum or Average 0.154196E+12 0.399517E+11 8758.86 0.152494E+12 0.170152E+10 0.00                         0.00
Minimum of Months 0.342463E+10 0.925890E+09 672.00 0.341956E+10 -0.0 0.00 0.30   0.00   2385.29   2385.29   0.00   607.12   0.00
Maximum of Months 0.219419E+11 0.671031E+10 744.00 0.215709E+11 0.478405E+09 0.00 1.00   0.76   9206.20   8978.91   612.73   3271.57   0.00



Table of Contents

Report: DXReportMonthly

For: AIRLOOP DATACENTER MID COOLING COIL

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [J] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [J] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION {Maximum} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL RUNTIME FRACTION {MINIMUM} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE {Maximum} [W] COOLING COIL LATENT COOLING RATE {TIMESTAMP} COOLING COIL ELECTRICITY RATE {Maximum} [W] COOLING COIL ELECTRICITY RATE {TIMESTAMP} COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.109744E+11 0.316970E+10 523.23 0.109332E+11 41168153.50 0.00 0.27 20-JAN-16:30 0.00 01-JAN-00:01 20375.77 20-JAN-16:30 20375.77 20-JAN-16:30 890.95 24-JAN-15:20 5237.00 20-JAN-16:30 0.00
February 0.565800E+11 0.147630E+11 672.00 0.565800E+11 0.00 0.00 0.51 22-FEB-17:00 0.10 06-FEB-07:05 40011.90 22-FEB-17:00 40011.90 22-FEB-17:00 0.00 17-FEB-08:47 9902.91 22-FEB-17:00 0.00
March 0.128112E+12 0.303267E+11 744.00 0.128001E+12 0.111058E+09 0.00 0.73 27-MAR-17:10 0.46 01-MAR-07:05 65641.23 31-MAR-23:30 65641.23 31-MAR-23:30 2161.45 27-MAR-15:00 17281.69 27-MAR-17:00 0.00
April 0.179774E+12 0.414119E+11 720.00 0.179551E+12 0.222664E+09 0.00 0.94 12-APR-17:40 0.21 30-APR-24:00 82909.69 09-APR-17:33 82755.57 09-APR-17:31 2176.92 27-APR-16:00 25269.68 07-APR-17:00 0.00
May 0.507124E+11 0.132065E+11 744.00 0.497287E+11 0.983724E+09 0.00 0.47 31-MAY-23:20 0.13 01-MAY-06:05 39585.26 31-MAY-23:20 39005.50 31-MAY-24:00 2864.34 18-MAY-15:30 10158.83 31-MAY-23:20 0.00
June 0.105533E+12 0.297148E+11 720.00 0.102301E+12 0.323171E+10 0.00 0.65 30-JUN-24:00 0.40 03-JUN-06:50 56019.59 30-JUN-24:00 55825.39 30-JUN-24:00 5211.90 15-JUN-14:00 19080.79 19-JUN-12:10 0.00
July 0.161178E+12 0.494342E+11 744.00 0.156408E+12 0.476930E+10 0.00 0.87 31-JUL-24:00 0.64 01-JUL-06:10 75105.91 31-JUL-24:00 75105.91 31-JUL-24:00 6072.99 20-JUL-15:00 24600.55 10-JUL-15:00 0.00
August 0.209148E+12 0.640253E+11 744.00 0.205438E+12 0.371090E+10 0.00 1.00 01-AUG-14:00 0.28 31-AUG-24:00 88339.46 31-AUG-17:50 84893.17 31-AUG-17:50 6177.80 03-AUG-15:00 31394.67 24-AUG-16:00 0.00
September 0.536416E+11 0.148871E+11 720.00 0.515465E+11 0.209506E+10 0.00 0.42 30-SEP-23:30 0.15 30-SEP-06:55 35956.23 30-SEP-23:30 35956.23 30-SEP-23:30 4523.66 07-SEP-15:00 10018.73 14-SEP-14:00 0.00
October 0.963262E+11 0.238592E+11 744.00 0.947939E+11 0.153230E+10 0.00 0.58 04-OCT-16:00 0.33 28-OCT-06:55 49248.16 31-OCT-23:50 49218.19 31-OCT-24:00 3447.63 05-OCT-16:00 13877.76 04-OCT-16:00 0.00
November 0.121178E+12 0.284177E+11 720.00 0.120997E+12 0.180980E+09 0.00 0.69 03-NOV-16:00 0.43 24-NOV-07:10 60432.81 03-NOV-16:00 60432.81 03-NOV-16:00 2554.88 10-NOV-10:30 14584.06 03-NOV-14:00 0.00
December 0.164801E+12 0.385875E+11 744.00 0.164801E+12 -0.0 0.00 0.87 15-DEC-16:00 0.58 31-DEC-23:56 75055.53 08-DEC-16:10 75055.53 08-DEC-16:10 0.00 11-DEC-22:30 17042.33 15-DEC-16:00 0.00
                                       
Annual Sum or Average 0.133796E+13 0.351804E+12 8539.23 0.132108E+13 0.168789E+11 0.00                         0.00
Minimum of Months 0.109744E+11 0.316970E+10 523.23 0.109332E+11 -0.0 0.00 0.27   0.00   20375.77   20375.77   0.00   5237.00   0.00
Maximum of Months 0.209148E+12 0.640253E+11 744.00 0.205438E+12 0.476930E+10 0.00 1.00   0.64   88339.46   84893.17   6177.80   31394.67   0.00



Table of Contents

Report: DXReportMonthly

For: AIRLOOP DATACENTER TOP COOLING COIL

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [J] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [J] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION {Maximum} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL RUNTIME FRACTION {MINIMUM} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE {Maximum} [W] COOLING COIL LATENT COOLING RATE {TIMESTAMP} COOLING COIL ELECTRICITY RATE {Maximum} [W] COOLING COIL ELECTRICITY RATE {TIMESTAMP} COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.531228E+09 0.155722E+09 285.78 0.527819E+09 3409048.95 0.00 0.26 20-JAN-16:30 0.00 01-JAN-00:01 2026.86 19-JAN-16:30 2026.86 19-JAN-16:30 84.10 24-JAN-15:20 515.01 19-JAN-16:30 0.00
February 0.418180E+10 0.111269E+10 656.90 0.418180E+10 -0.0 0.00 0.49 02-FEB-16:50 0.00 05-FEB-03:05 3949.14 22-FEB-17:00 3949.14 22-FEB-17:00 0.00 05-FEB-01:50 983.37 02-FEB-16:50 0.00
March 0.115731E+11 0.277005E+10 744.00 0.115622E+11 10891345.77 0.00 0.72 27-MAR-17:10 0.33 13-MAR-03:30 6369.83 27-MAR-17:20 6263.28 27-MAR-17:20 217.12 27-MAR-15:00 1733.22 27-MAR-17:00 0.00
April 0.171558E+11 0.398694E+10 720.00 0.171337E+11 22097225.48 0.00 0.93 07-APR-16:00 0.12 30-APR-24:00 8323.78 09-APR-17:24 8308.57 09-APR-17:22 218.02 27-APR-16:00 2562.14 07-APR-17:00 0.00
May 0.472261E+10 0.124286E+10 743.92 0.462547E+10 97145600.66 0.00 0.46 31-MAY-23:20 0.00 01-MAY-03:35 3925.87 31-MAY-23:20 3863.69 31-MAY-24:00 287.04 18-MAY-15:30 1009.89 31-MAY-23:20 0.00
June 0.105389E+11 0.297683E+10 720.00 0.102159E+11 0.323013E+09 0.00 0.63 30-JUN-24:00 0.36 03-JUN-06:40 5523.92 30-JUN-24:00 5504.06 30-JUN-24:00 523.72 15-JUN-14:00 1951.34 19-JUN-12:10 0.00
July 0.162256E+11 0.498488E+10 744.00 0.157487E+11 0.476871E+09 0.00 0.86 31-JUL-24:00 0.62 01-JUL-06:10 7514.56 31-JUL-24:00 7514.56 31-JUL-24:00 608.24 20-JUL-15:00 2508.55 10-JUL-15:00 0.00
August 0.209833E+11 0.643973E+10 744.00 0.206124E+11 0.370900E+09 0.00 1.00 01-AUG-14:10 0.28 31-AUG-24:00 8969.18 31-AUG-17:40 8617.17 31-AUG-17:40 621.13 03-AUG-15:00 3194.15 24-AUG-16:00 0.00
September 0.513398E+10 0.143752E+10 720.00 0.492541E+10 0.208575E+09 0.00 0.41 10-SEP-17:31 0.10 24-SEP-06:40 3386.89 10-SEP-17:31 3366.59 10-SEP-17:33 457.08 07-SEP-15:00 1032.37 14-SEP-14:10 0.00
October 0.882384E+10 0.220733E+10 744.00 0.867162E+10 0.152218E+09 0.00 0.58 04-OCT-16:00 0.23 29-OCT-07:20 4994.23 04-OCT-16:00 4678.87 04-OCT-16:30 345.31 05-OCT-16:00 1411.81 04-OCT-16:00 0.00
November 0.106634E+11 0.253254E+10 720.00 0.106455E+11 17892133.06 0.00 0.68 03-NOV-16:00 0.28 24-NOV-04:13 6038.37 03-NOV-16:00 6038.37 03-NOV-16:00 256.14 10-NOV-10:30 1457.62 03-NOV-14:00 0.00
December 0.146609E+11 0.348499E+10 744.00 0.146609E+11 -0.0 0.00 0.84 21-DEC-16:10 0.44 31-DEC-23:52 7389.27 08-DEC-16:10 7389.27 08-DEC-16:10 0.00 20-DEC-11:50 1677.71 21-DEC-16:10 0.00
                                       
Annual Sum or Average 0.125194E+12 0.333321E+11 8286.60 0.123511E+12 0.168301E+10 0.00                         0.00
Minimum of Months 0.531228E+09 0.155722E+09 285.78 0.527819E+09 -0.0 0.00 0.26   0.00   2026.86   2026.86   0.00   515.01   0.00
Maximum of Months 0.209833E+11 0.643973E+10 744.00 0.206124E+11 0.476871E+09 0.00 1.00   0.62   8969.18   8617.17   621.13   3194.15   0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 134.44 0.00 134.44 3.07 800.36 0.00 0.00 0.00
February 183.97 0.00 183.97 10.04 826.48 0.00 0.00 0.00
March 255.12 0.00 255.12 69.46 569.45 0.00 0.00 0.00
April 306.44 0.87 305.57 165.82 407.00 0.00 0.00 0.00
May 406.55 13.55 393.00 355.36 234.48 0.00 0.00 0.00
June 431.14 23.17 407.97 508.24 125.97 0.00 0.00 0.00
July 416.65 15.07 401.59 567.30 67.72 0.00 0.00 0.00
August 369.13 4.39 364.74 494.67 92.02 0.00 0.00 0.00
September 278.27 0.05 278.21 280.37 196.19 0.00 0.00 0.00
October 240.82 0.00 240.82 158.42 367.19 0.00 0.00 0.00
November 168.91 0.00 168.91 32.38 594.41 0.00 0.00 0.00
December 117.27 0.00 117.27 1.48 780.55 0.00 0.00 0.00
                 
Annual Sum or Average 276.26 4.78 271.47 221.99 419.49 0.00 0.00 0.00
Minimum of Months 117.27 0.00 117.27 1.48 67.72 0.00 0.00 0.00
Maximum of Months 431.14 23.17 407.97 567.30 826.48 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 134.44 0.00 134.44 3.07 800.36 0.00 0.00 0.00
February 183.97 0.00 183.97 10.04 826.49 0.00 0.00 0.00
March 255.12 0.00 255.12 69.46 569.45 0.00 0.00 0.00
April 306.44 0.87 305.57 165.82 407.00 0.00 0.00 0.00
May 406.55 13.55 393.00 355.36 234.48 0.00 0.00 0.00
June 431.14 23.17 407.97 508.23 125.97 0.00 0.00 0.00
July 416.65 15.07 401.58 567.30 67.72 0.00 0.00 0.00
August 369.13 4.39 364.74 494.67 92.02 0.00 0.00 0.00
September 278.27 0.05 278.21 280.37 196.19 0.00 0.00 0.00
October 240.82 0.00 240.82 158.42 367.19 0.00 0.00 0.00
November 168.91 0.00 168.91 32.38 594.41 0.00 0.00 0.00
December 117.27 0.00 117.27 1.48 780.55 0.00 0.00 0.00
                 
Annual Sum or Average 276.26 4.78 271.47 221.99 419.49 0.00 0.00 0.00
Minimum of Months 117.27 0.00 117.27 1.48 67.72 0.00 0.00 0.00
Maximum of Months 431.14 23.17 407.97 567.30 826.49 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 134.44 0.00 134.44 3.07 800.36 0.00 0.00 0.00
February 183.97 0.00 183.97 10.04 826.48 0.00 0.00 0.00
March 255.12 0.00 255.12 69.46 569.45 0.00 0.00 0.00
April 306.44 0.87 305.57 165.82 407.00 0.00 0.00 0.00
May 406.55 13.55 393.00 355.36 234.48 0.00 0.00 0.00
June 431.14 23.17 407.97 508.24 125.97 0.00 0.00 0.00
July 416.65 15.07 401.59 567.30 67.72 0.00 0.00 0.00
August 369.13 4.39 364.74 494.67 92.02 0.00 0.00 0.00
September 278.27 0.05 278.21 280.37 196.19 0.00 0.00 0.00
October 240.82 0.00 240.82 158.42 367.19 0.00 0.00 0.00
November 168.91 0.00 168.91 32.38 594.41 0.00 0.00 0.00
December 117.27 0.00 117.27 1.48 780.55 0.00 0.00 0.00
                 
Annual Sum or Average 276.26 4.78 271.47 221.99 419.49 0.00 0.00 0.00
Minimum of Months 117.27 0.00 117.27 1.48 67.72 0.00 0.00 0.00
Maximum of Months 431.14 23.17 407.97 567.30 826.48 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 134.44 0.00 134.44 3.07 800.36 0.00 0.00 0.00
February 183.97 0.00 183.97 10.04 826.49 0.00 0.00 0.00
March 255.12 0.00 255.12 69.46 569.45 0.00 0.00 0.00
April 306.44 0.87 305.57 165.82 407.00 0.00 0.00 0.00
May 406.55 13.55 393.00 355.36 234.48 0.00 0.00 0.00
June 431.14 23.17 407.97 508.23 125.97 0.00 0.00 0.00
July 416.65 15.07 401.58 567.30 67.72 0.00 0.00 0.00
August 369.13 4.39 364.74 494.67 92.02 0.00 0.00 0.00
September 278.27 0.05 278.21 280.37 196.19 0.00 0.00 0.00
October 240.82 0.00 240.82 158.42 367.19 0.00 0.00 0.00
November 168.91 0.00 168.91 32.38 594.41 0.00 0.00 0.00
December 117.27 0.00 117.27 1.48 780.55 0.00 0.00 0.00
                 
Annual Sum or Average 276.26 4.78 271.47 221.99 419.49 0.00 0.00 0.00
Minimum of Months 117.27 0.00 117.27 1.48 67.72 0.00 0.00 0.00
Maximum of Months 431.14 23.17 407.97 567.30 826.49 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 134.43 0.00 134.43 3.07 800.32 0.00 0.00 0.00
February 183.97 0.00 183.97 10.04 826.45 0.00 0.00 0.00
March 255.11 0.00 255.11 69.46 569.43 0.00 0.00 0.00
April 306.43 0.87 305.55 165.81 406.99 0.00 0.00 0.00
May 406.53 13.55 392.98 355.34 234.47 0.00 0.00 0.00
June 431.12 23.17 407.95 508.21 125.97 0.00 0.00 0.00
July 416.64 15.07 401.57 567.28 67.71 0.00 0.00 0.00
August 369.12 4.39 364.73 494.65 92.01 0.00 0.00 0.00
September 278.25 0.05 278.20 280.36 196.18 0.00 0.00 0.00
October 240.81 0.00 240.81 158.41 367.18 0.00 0.00 0.00
November 168.90 0.00 168.90 32.38 594.38 0.00 0.00 0.00
December 117.26 0.00 117.26 1.48 780.52 0.00 0.00 0.00
                 
Annual Sum or Average 276.24 4.78 271.46 221.99 419.47 0.00 0.00 0.00
Minimum of Months 117.26 0.00 117.26 1.48 67.71 0.00 0.00 0.00
Maximum of Months 431.12 23.17 407.95 567.28 826.45 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 312.03 125.10 186.93 172.18 817.02 0.00 0.00 0.00
February 483.89 225.73 258.15 308.93 815.10 0.00 0.00 0.00
March 617.29 262.54 354.75 502.05 587.69 0.00 0.00 0.00
April 740.79 324.49 416.30 707.94 415.75 0.00 0.00 0.00
May 898.42 359.06 539.36 994.80 259.60 0.00 0.00 0.00
June 832.65 301.41 531.23 1046.66 136.29 0.00 0.00 0.00
July 836.29 301.80 534.49 1144.15 66.73 0.00 0.00 0.00
August 941.69 424.61 517.08 1280.90 90.81 0.00 0.00 0.00
September 702.31 315.10 387.21 840.02 205.33 0.00 0.00 0.00
October 636.70 288.57 348.13 670.47 383.02 0.00 0.00 0.00
November 393.75 151.20 242.55 286.72 595.68 0.00 0.00 0.00
December 306.75 144.03 162.72 185.88 770.22 0.00 0.00 0.00
                 
Annual Sum or Average 642.90 268.94 373.96 680.97 426.42 0.00 0.00 0.00
Minimum of Months 306.75 125.10 162.72 172.18 66.73 0.00 0.00 0.00
Maximum of Months 941.69 424.61 539.36 1280.90 817.02 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 312.03 125.10 186.93 172.18 817.02 0.00 0.00 0.00
February 483.89 225.73 258.15 308.93 815.10 0.00 0.00 0.00
March 617.29 262.54 354.75 502.05 587.69 0.00 0.00 0.00
April 740.79 324.49 416.30 707.94 415.75 0.00 0.00 0.00
May 898.42 359.06 539.36 994.80 259.60 0.00 0.00 0.00
June 832.65 301.41 531.23 1046.66 136.29 0.00 0.00 0.00
July 836.29 301.80 534.49 1144.15 66.73 0.00 0.00 0.00
August 941.69 424.61 517.08 1280.90 90.81 0.00 0.00 0.00
September 702.31 315.10 387.21 840.02 205.33 0.00 0.00 0.00
October 636.70 288.57 348.13 670.47 383.02 0.00 0.00 0.00
November 393.75 151.20 242.55 286.72 595.68 0.00 0.00 0.00
December 306.75 144.03 162.72 185.88 770.22 0.00 0.00 0.00
                 
Annual Sum or Average 642.90 268.94 373.96 680.97 426.42 0.00 0.00 0.00
Minimum of Months 306.75 125.10 162.72 172.18 66.73 0.00 0.00 0.00
Maximum of Months 941.69 424.61 539.36 1280.90 817.02 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 312.02 125.10 186.93 172.17 817.01 0.00 0.00 0.00
February 483.88 225.73 258.15 308.92 815.09 0.00 0.00 0.00
March 617.28 262.53 354.74 502.05 587.68 0.00 0.00 0.00
April 740.78 324.48 416.29 707.93 415.75 0.00 0.00 0.00
May 898.41 359.06 539.35 994.78 259.60 0.00 0.00 0.00
June 832.63 301.41 531.22 1046.65 136.29 0.00 0.00 0.00
July 836.28 301.79 534.49 1144.13 66.73 0.00 0.00 0.00
August 941.67 424.60 517.07 1280.87 90.81 0.00 0.00 0.00
September 702.30 315.09 387.21 840.01 205.32 0.00 0.00 0.00
October 636.69 288.57 348.12 670.46 383.01 0.00 0.00 0.00
November 393.74 151.20 242.54 286.71 595.67 0.00 0.00 0.00
December 306.75 144.03 162.72 185.87 770.20 0.00 0.00 0.00
                 
Annual Sum or Average 642.89 268.94 373.95 680.96 426.41 0.00 0.00 0.00
Minimum of Months 306.75 125.10 162.72 172.17 66.73 0.00 0.00 0.00
Maximum of Months 941.67 424.60 539.35 1280.87 817.01 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 695.48 455.40 240.07 646.95 689.56 0.00 0.00 0.00
February 917.31 607.18 310.13 868.57 698.06 0.00 0.00 0.00
March 827.59 459.33 368.26 832.31 528.62 0.00 0.00 0.00
April 642.18 253.94 388.24 664.05 400.00 0.00 0.00 0.00
May 562.77 117.39 445.39 623.53 246.65 0.00 0.00 0.00
June 528.15 80.73 447.41 680.37 133.41 0.00 0.00 0.00
July 553.60 96.16 457.44 793.42 68.88 0.00 0.00 0.00
August 739.28 274.21 465.07 1067.87 97.28 0.00 0.00 0.00
September 802.13 414.89 387.24 1026.54 198.38 0.00 0.00 0.00
October 1098.85 689.06 409.79 1308.95 357.46 0.00 0.00 0.00
November 761.96 457.59 304.37 767.38 525.30 0.00 0.00 0.00
December 753.79 535.14 218.65 729.58 653.11 0.00 0.00 0.00
                 
Annual Sum or Average 739.42 368.89 370.54 834.39 381.22 0.00 0.00 0.00
Minimum of Months 528.15 80.73 218.65 623.53 68.88 0.00 0.00 0.00
Maximum of Months 1098.85 689.06 465.07 1308.95 698.06 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 695.48 455.40 240.07 646.95 689.56 0.00 0.00 0.00
February 917.31 607.18 310.13 868.57 698.06 0.00 0.00 0.00
March 827.59 459.32 368.26 832.31 528.62 0.00 0.00 0.00
April 642.18 253.94 388.24 664.05 400.00 0.00 0.00 0.00
May 562.77 117.39 445.39 623.53 246.65 0.00 0.00 0.00
June 528.15 80.73 447.41 680.37 133.41 0.00 0.00 0.00
July 553.60 96.16 457.44 793.42 68.88 0.00 0.00 0.00
August 739.28 274.21 465.07 1067.87 97.28 0.00 0.00 0.00
September 802.13 414.89 387.24 1026.54 198.38 0.00 0.00 0.00
October 1098.85 689.06 409.79 1308.95 357.46 0.00 0.00 0.00
November 761.96 457.59 304.37 767.38 525.30 0.00 0.00 0.00
December 753.79 535.14 218.65 729.58 653.11 0.00 0.00 0.00
                 
Annual Sum or Average 739.42 368.88 370.54 834.39 381.22 0.00 0.00 0.00
Minimum of Months 528.15 80.73 218.65 623.53 68.88 0.00 0.00 0.00
Maximum of Months 1098.85 689.06 465.07 1308.95 698.06 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 695.48 455.40 240.07 646.95 689.56 0.00 0.00 0.00
February 917.31 607.18 310.13 868.57 698.06 0.00 0.00 0.00
March 827.59 459.33 368.26 832.31 528.62 0.00 0.00 0.00
April 642.18 253.94 388.24 664.05 400.00 0.00 0.00 0.00
May 562.77 117.39 445.39 623.53 246.65 0.00 0.00 0.00
June 528.15 80.73 447.41 680.37 133.41 0.00 0.00 0.00
July 553.60 96.16 457.44 793.42 68.88 0.00 0.00 0.00
August 739.28 274.21 465.07 1067.87 97.28 0.00 0.00 0.00
September 802.13 414.89 387.24 1026.54 198.38 0.00 0.00 0.00
October 1098.85 689.06 409.79 1308.95 357.46 0.00 0.00 0.00
November 761.96 457.59 304.37 767.38 525.30 0.00 0.00 0.00
December 753.79 535.14 218.65 729.58 653.11 0.00 0.00 0.00
                 
Annual Sum or Average 739.42 368.89 370.54 834.39 381.22 0.00 0.00 0.00
Minimum of Months 528.15 80.73 218.65 623.53 68.88 0.00 0.00 0.00
Maximum of Months 1098.85 689.06 465.07 1308.95 698.06 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 695.48 455.40 240.07 646.95 689.56 0.00 0.00 0.00
February 917.31 607.18 310.13 868.57 698.06 0.00 0.00 0.00
March 827.59 459.32 368.26 832.31 528.62 0.00 0.00 0.00
April 642.18 253.94 388.24 664.05 400.00 0.00 0.00 0.00
May 562.77 117.39 445.39 623.53 246.65 0.00 0.00 0.00
June 528.15 80.73 447.41 680.37 133.41 0.00 0.00 0.00
July 553.60 96.16 457.44 793.42 68.88 0.00 0.00 0.00
August 739.28 274.21 465.07 1067.87 97.28 0.00 0.00 0.00
September 802.13 414.89 387.24 1026.54 198.38 0.00 0.00 0.00
October 1098.85 689.06 409.79 1308.95 357.46 0.00 0.00 0.00
November 761.96 457.59 304.37 767.38 525.30 0.00 0.00 0.00
December 753.79 535.14 218.65 729.58 653.11 0.00 0.00 0.00
                 
Annual Sum or Average 739.42 368.88 370.54 834.39 381.22 0.00 0.00 0.00
Minimum of Months 528.15 80.73 218.65 623.53 68.88 0.00 0.00 0.00
Maximum of Months 1098.85 689.06 465.07 1308.95 698.06 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 695.45 455.38 240.06 646.93 689.54 0.00 0.00 0.00
February 917.27 607.16 310.11 868.54 698.03 0.00 0.00 0.00
March 827.55 459.31 368.25 832.28 528.60 0.00 0.00 0.00
April 642.15 253.93 388.23 664.03 399.98 0.00 0.00 0.00
May 562.75 117.38 445.37 623.50 246.64 0.00 0.00 0.00
June 528.13 80.73 447.40 680.34 133.41 0.00 0.00 0.00
July 553.58 96.16 457.42 793.39 68.88 0.00 0.00 0.00
August 739.25 274.20 465.05 1067.83 97.27 0.00 0.00 0.00
September 802.10 414.88 387.22 1026.50 198.37 0.00 0.00 0.00
October 1098.81 689.03 409.78 1308.90 357.44 0.00 0.00 0.00
November 761.93 457.57 304.35 767.35 525.28 0.00 0.00 0.00
December 753.76 535.12 218.64 729.55 653.08 0.00 0.00 0.00
                 
Annual Sum or Average 739.39 368.87 370.52 834.35 381.21 0.00 0.00 0.00
Minimum of Months 528.13 80.73 218.64 623.50 68.88 0.00 0.00 0.00
Maximum of Months 1098.81 689.03 465.05 1308.90 698.03 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 308.04 126.17 181.87 168.88 877.31 0.00 0.00 0.00
February 454.25 199.51 254.74 279.04 910.85 0.00 0.00 0.00
March 670.75 309.67 361.09 546.99 660.58 0.00 0.00 0.00
April 733.10 313.68 419.43 681.53 507.69 0.00 0.00 0.00
May 853.99 324.31 529.68 935.21 294.99 0.00 0.00 0.00
June 934.67 376.98 557.69 1164.61 174.03 0.00 0.00 0.00
July 875.37 329.64 545.73 1170.02 103.45 0.00 0.00 0.00
August 968.39 448.30 520.09 1294.48 140.48 0.00 0.00 0.00
September 687.48 300.43 387.05 820.51 241.58 0.00 0.00 0.00
October 681.59 331.44 350.15 717.42 442.36 0.00 0.00 0.00
November 320.07 92.50 227.57 180.75 695.97 0.00 0.00 0.00
December 284.70 123.19 161.51 150.47 904.56 0.00 0.00 0.00
                 
Annual Sum or Average 649.06 273.61 375.45 678.69 493.75 0.00 0.00 0.00
Minimum of Months 284.70 92.50 161.51 150.47 103.45 0.00 0.00 0.00
Maximum of Months 968.39 448.30 557.69 1294.48 910.85 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 308.04 126.17 181.87 168.88 877.31 0.00 0.00 0.00
February 454.25 199.51 254.74 279.04 910.85 0.00 0.00 0.00
March 670.75 309.67 361.09 546.99 660.58 0.00 0.00 0.00
April 733.10 313.68 419.43 681.53 507.69 0.00 0.00 0.00
May 853.99 324.31 529.68 935.21 294.99 0.00 0.00 0.00
June 934.67 376.98 557.69 1164.61 174.03 0.00 0.00 0.00
July 875.37 329.64 545.73 1170.02 103.45 0.00 0.00 0.00
August 968.39 448.30 520.09 1294.48 140.48 0.00 0.00 0.00
September 687.48 300.43 387.05 820.51 241.58 0.00 0.00 0.00
October 681.59 331.44 350.15 717.42 442.36 0.00 0.00 0.00
November 320.07 92.50 227.57 180.75 695.97 0.00 0.00 0.00
December 284.70 123.19 161.51 150.47 904.56 0.00 0.00 0.00
                 
Annual Sum or Average 649.06 273.61 375.45 678.69 493.75 0.00 0.00 0.00
Minimum of Months 284.70 92.50 161.51 150.47 103.45 0.00 0.00 0.00
Maximum of Months 968.39 448.30 557.69 1294.48 910.85 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 308.03 126.17 181.86 168.87 877.30 0.00 0.00 0.00
February 454.24 199.50 254.74 279.04 910.84 0.00 0.00 0.00
March 670.74 309.66 361.08 546.98 660.57 0.00 0.00 0.00
April 733.09 313.67 419.42 681.52 507.68 0.00 0.00 0.00
May 853.98 324.31 529.67 935.19 294.99 0.00 0.00 0.00
June 934.65 376.97 557.68 1164.59 174.02 0.00 0.00 0.00
July 875.35 329.63 545.72 1170.00 103.45 0.00 0.00 0.00
August 968.38 448.29 520.08 1294.45 140.48 0.00 0.00 0.00
September 687.47 300.42 387.05 820.50 241.58 0.00 0.00 0.00
October 681.58 331.43 350.14 717.41 442.35 0.00 0.00 0.00
November 320.07 92.50 227.56 180.75 695.95 0.00 0.00 0.00
December 284.69 123.19 161.50 150.47 904.55 0.00 0.00 0.00
                 
Annual Sum or Average 649.05 273.61 375.44 678.68 493.74 0.00 0.00 0.00
Minimum of Months 284.69 92.50 161.50 150.47 103.45 0.00 0.00 0.00
Maximum of Months 968.38 448.29 557.68 1294.45 910.84 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 672.18 0.00 672.18 40.01 3551.72 0.00 0.00 0.00
February 919.85 0.00 919.85 80.13 3704.57 0.00 0.00 0.00
March 1275.60 0.00 1275.60 427.17 2486.35 0.00 0.00 0.00
April 1532.17 4.36 1527.82 917.32 1770.27 0.00 0.00 0.00
May 2032.71 67.73 1964.98 1808.18 1095.59 0.00 0.00 0.00
June 2155.66 115.83 2039.83 2549.44 600.30 0.00 0.00 0.00
July 2083.24 75.34 2007.90 2841.02 337.81 0.00 0.00 0.00
August 1845.65 21.97 1823.68 2490.35 454.46 0.00 0.00 0.00
September 1391.31 0.26 1391.05 1426.07 904.56 0.00 0.00 0.00
October 1204.08 0.00 1204.08 851.76 1639.10 0.00 0.00 0.00
November 844.55 0.00 844.55 220.24 2531.25 0.00 0.00 0.00
December 586.32 0.00 586.32 24.65 3337.20 0.00 0.00 0.00
                 
Annual Sum or Average 1381.26 23.92 1357.34 1146.88 1857.23 0.00 0.00 0.00
Minimum of Months 586.32 0.00 586.32 24.65 337.81 0.00 0.00 0.00
Maximum of Months 2155.66 115.83 2039.83 2841.02 3704.57 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 936.07 375.29 560.78 548.66 2204.80 0.00 0.00 0.00
February 1451.64 677.19 774.45 963.46 2232.22 0.00 0.00 0.00
March 1851.85 787.60 1064.24 1528.87 1604.68 0.00 0.00 0.00
April 2222.34 973.46 1248.89 2139.28 1145.56 0.00 0.00 0.00
May 2695.24 1077.18 1618.06 2974.41 737.40 0.00 0.00 0.00
June 2497.91 904.23 1593.69 3117.67 404.84 0.00 0.00 0.00
July 2508.85 905.38 1603.47 3401.78 225.40 0.00 0.00 0.00
August 2825.03 1273.80 1551.22 3807.46 306.03 0.00 0.00 0.00
September 2106.92 945.29 1161.63 2510.87 583.05 0.00 0.00 0.00
October 1910.08 865.71 1044.37 2022.09 1061.29 0.00 0.00 0.00
November 1181.24 453.61 727.63 899.45 1583.67 0.00 0.00 0.00
December 920.25 432.09 488.16 587.93 2054.68 0.00 0.00 0.00
                 
Annual Sum or Average 1928.68 806.82 1121.86 2049.32 1172.71 0.00 0.00 0.00
Minimum of Months 920.25 375.29 488.16 548.66 225.40 0.00 0.00 0.00
Maximum of Months 2825.03 1273.80 1618.06 3807.46 2232.22 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 3477.34 2276.99 1200.36 3243.51 3234.82 0.00 0.00 0.00
February 4586.50 3035.89 1550.61 4335.93 3322.65 0.00 0.00 0.00
March 4137.89 2296.60 1841.29 4149.56 2483.36 0.00 0.00 0.00
April 3210.85 1269.67 1941.19 3327.48 1859.65 0.00 0.00 0.00
May 2813.84 586.92 2226.91 3105.99 1182.18 0.00 0.00 0.00
June 2640.70 403.66 2237.04 3387.41 645.02 0.00 0.00 0.00
July 2767.98 480.80 2287.19 3950.45 351.07 0.00 0.00 0.00
August 3696.34 1371.03 2325.30 5314.87 497.52 0.00 0.00 0.00
September 4010.60 2074.45 1936.15 5099.16 961.34 0.00 0.00 0.00
October 5494.18 3445.25 2048.94 6495.25 1727.92 0.00 0.00 0.00
November 3809.75 2287.93 1521.81 3843.16 2446.88 0.00 0.00 0.00
December 3768.92 2675.68 1093.24 3656.55 3033.57 0.00 0.00 0.00
                 
Annual Sum or Average 3697.07 1844.40 1852.67 4160.34 1803.41 0.00 0.00 0.00
Minimum of Months 2640.70 403.66 1093.24 3105.99 351.07 0.00 0.00 0.00
Maximum of Months 5494.18 3445.25 2325.30 6495.25 3322.65 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 924.11 378.52 545.59 538.11 2307.68 0.00 0.00 0.00
February 1362.73 598.52 764.22 881.41 2389.67 0.00 0.00 0.00
March 2012.24 929.00 1083.25 1714.47 1656.56 0.00 0.00 0.00
April 2199.29 941.02 1258.27 2133.60 1237.14 0.00 0.00 0.00
May 2561.95 972.93 1589.02 2835.22 800.76 0.00 0.00 0.00
June 2803.98 1130.92 1673.05 3511.37 463.91 0.00 0.00 0.00
July 2626.07 988.90 1637.17 3539.22 271.54 0.00 0.00 0.00
August 2905.15 1344.89 1560.26 3924.20 363.99 0.00 0.00 0.00
September 2062.43 901.28 1161.15 2486.15 641.39 0.00 0.00 0.00
October 2044.74 994.31 1050.43 2204.82 1146.36 0.00 0.00 0.00
November 960.20 277.51 682.70 613.82 1676.79 0.00 0.00 0.00
December 854.08 369.56 484.52 506.87 2180.48 0.00 0.00 0.00
                 
Annual Sum or Average 1947.16 820.83 1126.33 2082.68 1254.89 0.00 0.00 0.00
Minimum of Months 854.08 277.51 484.52 506.87 271.54 0.00 0.00 0.00
Maximum of Months 2905.15 1344.89 1673.05 3924.20 2389.67 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 672.18 0.00 672.18 46.86 3413.76 0.00 0.00 0.00
February 919.85 0.00 919.85 94.35 3531.49 0.00 0.00 0.00
March 1275.60 0.00 1275.60 456.54 2321.59 0.00 0.00 0.00
April 1532.17 4.36 1527.82 955.64 1646.54 0.00 0.00 0.00
May 2032.71 67.73 1964.98 1824.09 1047.48 0.00 0.00 0.00
June 2155.66 115.83 2039.83 2531.55 593.29 0.00 0.00 0.00
July 2083.24 75.34 2007.90 2811.02 345.42 0.00 0.00 0.00
August 1845.65 21.97 1823.68 2469.81 454.57 0.00 0.00 0.00
September 1391.31 0.26 1391.05 1430.72 864.51 0.00 0.00 0.00
October 1204.08 0.00 1204.08 895.63 1511.57 0.00 0.00 0.00
November 844.55 0.00 844.55 258.40 2322.92 0.00 0.00 0.00
December 586.32 0.00 586.32 37.53 3108.45 0.00 0.00 0.00
                 
Annual Sum or Average 1381.26 23.92 1357.34 1158.13 1753.39 0.00 0.00 0.00
Minimum of Months 586.32 0.00 586.32 37.53 345.42 0.00 0.00 0.00
Maximum of Months 2155.66 115.83 2039.83 2811.02 3531.49 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 936.07 375.29 560.78 559.76 2117.59 0.00 0.00 0.00
February 1451.64 677.19 774.45 987.21 2126.09 0.00 0.00 0.00
March 1851.85 787.60 1064.24 1550.26 1505.55 0.00 0.00 0.00
April 2222.34 973.46 1248.89 2158.95 1078.34 0.00 0.00 0.00
May 2695.24 1077.18 1618.06 2975.91 710.44 0.00 0.00 0.00
June 2497.91 904.23 1593.69 3103.05 401.75 0.00 0.00 0.00
July 2508.85 905.38 1603.47 3380.33 230.89 0.00 0.00 0.00
August 2825.03 1273.80 1551.22 3789.50 307.03 0.00 0.00 0.00
September 2106.92 945.29 1161.63 2509.16 562.69 0.00 0.00 0.00
October 1910.08 865.71 1044.37 2044.41 991.66 0.00 0.00 0.00
November 1181.24 453.61 727.63 934.20 1462.30 0.00 0.00 0.00
December 920.25 432.09 488.16 611.26 1913.64 0.00 0.00 0.00
                 
Annual Sum or Average 1928.68 806.82 1121.86 2057.69 1111.68 0.00 0.00 0.00
Minimum of Months 920.25 375.29 488.16 559.76 230.89 0.00 0.00 0.00
Maximum of Months 2825.03 1273.80 1618.06 3789.50 2126.09 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 3477.34 2276.99 1200.36 3265.09 3085.75 0.00 0.00 0.00
February 4586.50 3035.89 1550.61 4375.96 3143.91 0.00 0.00 0.00
March 4137.89 2296.60 1841.29 4177.37 2321.90 0.00 0.00 0.00
April 3210.85 1269.67 1941.19 3355.67 1739.68 0.00 0.00 0.00
May 2813.84 586.92 2226.91 3114.67 1128.89 0.00 0.00 0.00
June 2640.70 403.66 2237.04 3368.04 635.93 0.00 0.00 0.00
July 2767.98 480.80 2287.19 3919.65 357.31 0.00 0.00 0.00
August 3696.34 1371.03 2325.30 5289.06 496.50 0.00 0.00 0.00
September 4010.60 2074.45 1936.15 5095.71 924.69 0.00 0.00 0.00
October 5494.18 3445.25 2048.94 6515.13 1621.06 0.00 0.00 0.00
November 3809.75 2287.93 1521.81 3895.17 2251.73 0.00 0.00 0.00
December 3768.92 2675.68 1093.24 3704.61 2814.95 0.00 0.00 0.00
                 
Annual Sum or Average 3697.07 1844.40 1852.67 4174.02 1701.94 0.00 0.00 0.00
Minimum of Months 2640.70 403.66 1093.24 3114.67 357.31 0.00 0.00 0.00
Maximum of Months 5494.18 3445.25 2325.30 6515.13 3143.91 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 924.11 378.52 545.59 544.15 2217.43 0.00 0.00 0.00
February 1362.73 598.52 764.22 889.23 2288.47 0.00 0.00 0.00
March 2012.24 929.00 1083.25 1727.11 1564.82 0.00 0.00 0.00
April 2199.29 941.02 1258.27 2147.91 1168.11 0.00 0.00 0.00
May 2561.95 972.93 1589.02 2838.49 769.41 0.00 0.00 0.00
June 2803.98 1130.92 1673.05 3496.32 457.54 0.00 0.00 0.00
July 2626.07 988.90 1637.17 3518.35 273.54 0.00 0.00 0.00
August 2905.15 1344.89 1560.26 3907.69 362.34 0.00 0.00 0.00
September 2062.43 901.28 1161.15 2485.97 618.04 0.00 0.00 0.00
October 2044.74 994.31 1050.43 2222.21 1077.54 0.00 0.00 0.00
November 960.20 277.51 682.70 635.34 1563.03 0.00 0.00 0.00
December 854.08 369.56 484.52 519.00 2047.27 0.00 0.00 0.00
                 
Annual Sum or Average 1947.16 820.83 1126.33 2086.17 1194.41 0.00 0.00 0.00
Minimum of Months 854.08 277.51 484.52 519.00 273.54 0.00 0.00 0.00
Maximum of Months 2905.15 1344.89 1673.05 3907.69 2288.47 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.360079E+09 0.00 0.360079E+09 8234065.16 0.214367E+10
February 0.445067E+09 0.00 0.445067E+09 24290906.89 0.199943E+10
March 0.683324E+09 0.00 0.683324E+09 0.186047E+09 0.152523E+10
April 0.794289E+09 2259203.19 0.792030E+09 0.429794E+09 0.105495E+10
May 0.108889E+10 36282574.26 0.105261E+10 0.951793E+09 0.628039E+09
June 0.111751E+10 60048419.49 0.105746E+10 0.131735E+10 0.326516E+09
July 0.111596E+10 40356945.80 0.107561E+10 0.151946E+10 0.181373E+09
August 0.988690E+09 11766801.23 0.976923E+09 0.132493E+10 0.246461E+09
September 0.721266E+09 135063.77 0.721131E+09 0.726720E+09 0.508529E+09
October 0.645010E+09 0.00 0.645010E+09 0.424316E+09 0.983484E+09
November 0.437819E+09 0.00 0.437819E+09 83932529.86 0.154071E+10
December 0.314084E+09 0.00 0.314084E+09 3952282.95 0.209064E+10
           
Annual Sum or Average 0.871199E+10 0.150849E+09 0.856114E+10 0.700081E+10 0.132290E+11
Minimum of Months 0.314084E+09 0.00 0.314084E+09 3952282.95 0.181373E+09
Maximum of Months 0.111751E+10 60048419.49 0.107561E+10 0.151946E+10 0.214367E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.360079E+09 0.00 0.360079E+09 8233999.79 0.214367E+10
February 0.445067E+09 0.00 0.445067E+09 24290816.20 0.199943E+10
March 0.683323E+09 0.00 0.683323E+09 0.186047E+09 0.152523E+10
April 0.794288E+09 2259200.48 0.792029E+09 0.429793E+09 0.105495E+10
May 0.108889E+10 36282530.72 0.105261E+10 0.951791E+09 0.628039E+09
June 0.111751E+10 60048347.43 0.105746E+10 0.131734E+10 0.326516E+09
July 0.111596E+10 40356897.38 0.107560E+10 0.151946E+10 0.181373E+09
August 0.988689E+09 11766787.11 0.976922E+09 0.132493E+10 0.246461E+09
September 0.721265E+09 135063.61 0.721130E+09 0.726719E+09 0.508529E+09
October 0.645010E+09 0.00 0.645010E+09 0.424315E+09 0.983484E+09
November 0.437819E+09 0.00 0.437819E+09 83932320.03 0.154071E+10
December 0.314084E+09 0.00 0.314084E+09 3952253.49 0.209064E+10
           
Annual Sum or Average 0.871199E+10 0.150849E+09 0.856114E+10 0.700081E+10 0.132290E+11
Minimum of Months 0.314084E+09 0.00 0.314084E+09 3952253.49 0.181373E+09
Maximum of Months 0.111751E+10 60048347.43 0.107560E+10 0.151946E+10 0.214367E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.360079E+09 0.00 0.360079E+09 8234065.16 0.214367E+10
February 0.445067E+09 0.00 0.445067E+09 24290906.89 0.199943E+10
March 0.683324E+09 0.00 0.683324E+09 0.186047E+09 0.152523E+10
April 0.794289E+09 2259203.19 0.792030E+09 0.429794E+09 0.105495E+10
May 0.108889E+10 36282574.26 0.105261E+10 0.951793E+09 0.628039E+09
June 0.111751E+10 60048419.49 0.105746E+10 0.131735E+10 0.326516E+09
July 0.111596E+10 40356945.80 0.107561E+10 0.151946E+10 0.181373E+09
August 0.988690E+09 11766801.23 0.976923E+09 0.132493E+10 0.246461E+09
September 0.721266E+09 135063.77 0.721131E+09 0.726720E+09 0.508529E+09
October 0.645010E+09 0.00 0.645010E+09 0.424316E+09 0.983484E+09
November 0.437819E+09 0.00 0.437819E+09 83932529.86 0.154071E+10
December 0.314084E+09 0.00 0.314084E+09 3952282.95 0.209064E+10
           
Annual Sum or Average 0.871199E+10 0.150849E+09 0.856114E+10 0.700081E+10 0.132290E+11
Minimum of Months 0.314084E+09 0.00 0.314084E+09 3952282.95 0.181373E+09
Maximum of Months 0.111751E+10 60048419.49 0.107561E+10 0.151946E+10 0.214367E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.360079E+09 0.00 0.360079E+09 8233999.79 0.214367E+10
February 0.445067E+09 0.00 0.445067E+09 24290816.20 0.199943E+10
March 0.683323E+09 0.00 0.683323E+09 0.186047E+09 0.152523E+10
April 0.794288E+09 2259200.48 0.792029E+09 0.429793E+09 0.105495E+10
May 0.108889E+10 36282530.72 0.105261E+10 0.951791E+09 0.628039E+09
June 0.111751E+10 60048347.43 0.105746E+10 0.131734E+10 0.326516E+09
July 0.111596E+10 40356897.38 0.107560E+10 0.151946E+10 0.181373E+09
August 0.988689E+09 11766787.11 0.976922E+09 0.132493E+10 0.246461E+09
September 0.721265E+09 135063.61 0.721130E+09 0.726719E+09 0.508529E+09
October 0.645010E+09 0.00 0.645010E+09 0.424315E+09 0.983484E+09
November 0.437819E+09 0.00 0.437819E+09 83932320.03 0.154071E+10
December 0.314084E+09 0.00 0.314084E+09 3952253.49 0.209064E+10
           
Annual Sum or Average 0.871199E+10 0.150849E+09 0.856114E+10 0.700081E+10 0.132290E+11
Minimum of Months 0.314084E+09 0.00 0.314084E+09 3952253.49 0.181373E+09
Maximum of Months 0.111751E+10 60048347.43 0.107560E+10 0.151946E+10 0.214367E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.360064E+09 0.00 0.360064E+09 8233733.29 0.214358E+10
February 0.445049E+09 0.00 0.445049E+09 24289927.86 0.199935E+10
March 0.683296E+09 0.00 0.683296E+09 0.186040E+09 0.152517E+10
April 0.794257E+09 2259112.14 0.791998E+09 0.429776E+09 0.105491E+10
May 0.108885E+10 36281111.91 0.105257E+10 0.951754E+09 0.628013E+09
June 0.111746E+10 60045999.27 0.105742E+10 0.131729E+10 0.326503E+09
July 0.111592E+10 40355319.24 0.107556E+10 0.151940E+10 0.181365E+09
August 0.988650E+09 11766326.98 0.976884E+09 0.132488E+10 0.246451E+09
September 0.721237E+09 135058.33 0.721101E+09 0.726691E+09 0.508509E+09
October 0.644984E+09 0.00 0.644984E+09 0.424298E+09 0.983444E+09
November 0.437801E+09 0.00 0.437801E+09 83929147.00 0.154065E+10
December 0.314072E+09 0.00 0.314072E+09 3952123.66 0.209055E+10
           
Annual Sum or Average 0.871164E+10 0.150843E+09 0.856080E+10 0.700053E+10 0.132285E+11
Minimum of Months 0.314072E+09 0.00 0.314072E+09 3952123.66 0.181365E+09
Maximum of Months 0.111746E+10 60045999.27 0.107556E+10 0.151940E+10 0.214358E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.835733E+09 0.335062E+09 0.500672E+09 0.461154E+09 0.218832E+10
February 0.117062E+10 0.546094E+09 0.624524E+09 0.747362E+09 0.197189E+10
March 0.165335E+10 0.703179E+09 0.950166E+09 0.134470E+10 0.157406E+10
April 0.192013E+10 0.841074E+09 0.107905E+10 0.183499E+10 0.107763E+10
May 0.240633E+10 0.961716E+09 0.144462E+10 0.266446E+10 0.695321E+09
June 0.215822E+10 0.781260E+09 0.137696E+10 0.271295E+10 0.353267E+09
July 0.223992E+10 0.808333E+09 0.143159E+10 0.306449E+10 0.178736E+09
August 0.252221E+10 0.113726E+10 0.138494E+10 0.343075E+10 0.243224E+09
September 0.182040E+10 0.816741E+09 0.100366E+10 0.217734E+10 0.532208E+09
October 0.170534E+10 0.772916E+09 0.932420E+09 0.179580E+10 0.102588E+10
November 0.102060E+10 0.391920E+09 0.628678E+09 0.743167E+09 0.154399E+10
December 0.821608E+09 0.385777E+09 0.435831E+09 0.497856E+09 0.206294E+10
           
Annual Sum or Average 0.202744E+11 0.848134E+10 0.117931E+11 0.214750E+11 0.134475E+11
Minimum of Months 0.821608E+09 0.335062E+09 0.435831E+09 0.461154E+09 0.178736E+09
Maximum of Months 0.252221E+10 0.113726E+10 0.144462E+10 0.343075E+10 0.218832E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.835733E+09 0.335062E+09 0.500672E+09 0.461154E+09 0.218832E+10
February 0.117062E+10 0.546094E+09 0.624524E+09 0.747362E+09 0.197189E+10
March 0.165335E+10 0.703179E+09 0.950166E+09 0.134470E+10 0.157406E+10
April 0.192013E+10 0.841074E+09 0.107905E+10 0.183499E+10 0.107763E+10
May 0.240633E+10 0.961716E+09 0.144462E+10 0.266446E+10 0.695321E+09
June 0.215822E+10 0.781260E+09 0.137696E+10 0.271295E+10 0.353267E+09
July 0.223992E+10 0.808333E+09 0.143159E+10 0.306449E+10 0.178736E+09
August 0.252221E+10 0.113726E+10 0.138494E+10 0.343075E+10 0.243224E+09
September 0.182040E+10 0.816741E+09 0.100366E+10 0.217734E+10 0.532208E+09
October 0.170534E+10 0.772916E+09 0.932420E+09 0.179580E+10 0.102588E+10
November 0.102060E+10 0.391920E+09 0.628678E+09 0.743167E+09 0.154399E+10
December 0.821608E+09 0.385777E+09 0.435831E+09 0.497856E+09 0.206294E+10
           
Annual Sum or Average 0.202744E+11 0.848134E+10 0.117931E+11 0.214750E+11 0.134475E+11
Minimum of Months 0.821608E+09 0.335062E+09 0.435831E+09 0.461154E+09 0.178736E+09
Maximum of Months 0.252221E+10 0.113726E+10 0.144462E+10 0.343075E+10 0.218832E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.835718E+09 0.335055E+09 0.500662E+09 0.461146E+09 0.218828E+10
February 0.117060E+10 0.546084E+09 0.624513E+09 0.747349E+09 0.197185E+10
March 0.165332E+10 0.703167E+09 0.950149E+09 0.134468E+10 0.157403E+10
April 0.192009E+10 0.841059E+09 0.107903E+10 0.183496E+10 0.107761E+10
May 0.240629E+10 0.961698E+09 0.144459E+10 0.266441E+10 0.695308E+09
June 0.215818E+10 0.781246E+09 0.137693E+10 0.271290E+10 0.353261E+09
July 0.223988E+10 0.808318E+09 0.143156E+10 0.306443E+10 0.178733E+09
August 0.252216E+10 0.113724E+10 0.138492E+10 0.343069E+10 0.243220E+09
September 0.182036E+10 0.816726E+09 0.100364E+10 0.217730E+10 0.532199E+09
October 0.170530E+10 0.772902E+09 0.932403E+09 0.179577E+10 0.102586E+10
November 0.102058E+10 0.391913E+09 0.628667E+09 0.743153E+09 0.154397E+10
December 0.821593E+09 0.385770E+09 0.435823E+09 0.497847E+09 0.206291E+10
           
Annual Sum or Average 0.202741E+11 0.848118E+10 0.117929E+11 0.214746E+11 0.134472E+11
Minimum of Months 0.821593E+09 0.335055E+09 0.435823E+09 0.461146E+09 0.178733E+09
Maximum of Months 0.252216E+10 0.113724E+10 0.144459E+10 0.343069E+10 0.218828E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.186277E+10 0.121975E+10 0.643014E+09 0.173280E+10 0.184693E+10
February 0.221916E+10 0.146890E+10 0.750255E+09 0.210125E+10 0.168874E+10
March 0.221661E+10 0.123026E+10 0.986353E+09 0.222927E+10 0.141586E+10
April 0.166453E+10 0.658204E+09 0.100632E+10 0.172122E+10 0.103680E+10
May 0.150733E+10 0.314406E+09 0.119293E+10 0.167005E+10 0.660627E+09
June 0.136896E+10 0.209259E+09 0.115970E+10 0.176351E+10 0.345807E+09
July 0.148277E+10 0.257557E+09 0.122521E+10 0.212510E+10 0.184487E+09
August 0.198008E+10 0.734444E+09 0.124563E+10 0.286018E+10 0.260543E+09
September 0.207912E+10 0.107541E+10 0.100371E+10 0.266079E+10 0.514205E+09
October 0.294316E+10 0.184557E+10 0.109759E+10 0.350589E+10 0.957417E+09
November 0.197500E+10 0.118608E+10 0.788917E+09 0.198904E+10 0.136159E+10
December 0.201896E+10 0.143333E+10 0.585633E+09 0.195410E+10 0.174928E+10
           
Annual Sum or Average 0.233184E+11 0.116332E+11 0.116853E+11 0.263132E+11 0.120223E+11
Minimum of Months 0.136896E+10 0.209259E+09 0.585633E+09 0.167005E+10 0.184487E+09
Maximum of Months 0.294316E+10 0.184557E+10 0.124563E+10 0.350589E+10 0.184693E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.186276E+10 0.121975E+10 0.643014E+09 0.173280E+10 0.184693E+10
February 0.221915E+10 0.146890E+10 0.750255E+09 0.210125E+10 0.168874E+10
March 0.221661E+10 0.123026E+10 0.986352E+09 0.222926E+10 0.141586E+10
April 0.166452E+10 0.658203E+09 0.100632E+10 0.172122E+10 0.103680E+10
May 0.150733E+10 0.314406E+09 0.119293E+10 0.167005E+10 0.660627E+09
June 0.136896E+10 0.209259E+09 0.115970E+10 0.176351E+10 0.345807E+09
July 0.148277E+10 0.257557E+09 0.122521E+10 0.212510E+10 0.184487E+09
August 0.198008E+10 0.734443E+09 0.124563E+10 0.286018E+10 0.260543E+09
September 0.207912E+10 0.107541E+10 0.100371E+10 0.266079E+10 0.514204E+09
October 0.294316E+10 0.184557E+10 0.109759E+10 0.350589E+10 0.957417E+09
November 0.197499E+10 0.118608E+10 0.788916E+09 0.198904E+10 0.136159E+10
December 0.201896E+10 0.143332E+10 0.585632E+09 0.195410E+10 0.174928E+10
           
Annual Sum or Average 0.233184E+11 0.116332E+11 0.116853E+11 0.263132E+11 0.120223E+11
Minimum of Months 0.136896E+10 0.209259E+09 0.585632E+09 0.167005E+10 0.184487E+09
Maximum of Months 0.294316E+10 0.184557E+10 0.124563E+10 0.350589E+10 0.184693E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.186277E+10 0.121975E+10 0.643014E+09 0.173280E+10 0.184693E+10
February 0.221916E+10 0.146890E+10 0.750255E+09 0.210125E+10 0.168874E+10
March 0.221661E+10 0.123026E+10 0.986353E+09 0.222927E+10 0.141586E+10
April 0.166453E+10 0.658204E+09 0.100632E+10 0.172122E+10 0.103680E+10
May 0.150733E+10 0.314406E+09 0.119293E+10 0.167005E+10 0.660627E+09
June 0.136896E+10 0.209259E+09 0.115970E+10 0.176351E+10 0.345807E+09
July 0.148277E+10 0.257557E+09 0.122521E+10 0.212510E+10 0.184487E+09
August 0.198008E+10 0.734444E+09 0.124563E+10 0.286018E+10 0.260543E+09
September 0.207912E+10 0.107541E+10 0.100371E+10 0.266079E+10 0.514205E+09
October 0.294316E+10 0.184557E+10 0.109759E+10 0.350589E+10 0.957417E+09
November 0.197500E+10 0.118608E+10 0.788917E+09 0.198904E+10 0.136159E+10
December 0.201896E+10 0.143333E+10 0.585633E+09 0.195410E+10 0.174928E+10
           
Annual Sum or Average 0.233184E+11 0.116332E+11 0.116853E+11 0.263132E+11 0.120223E+11
Minimum of Months 0.136896E+10 0.209259E+09 0.585633E+09 0.167005E+10 0.184487E+09
Maximum of Months 0.294316E+10 0.184557E+10 0.124563E+10 0.350589E+10 0.184693E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.186276E+10 0.121975E+10 0.643014E+09 0.173280E+10 0.184693E+10
February 0.221915E+10 0.146890E+10 0.750255E+09 0.210125E+10 0.168874E+10
March 0.221661E+10 0.123026E+10 0.986352E+09 0.222926E+10 0.141586E+10
April 0.166452E+10 0.658203E+09 0.100632E+10 0.172122E+10 0.103680E+10
May 0.150733E+10 0.314406E+09 0.119293E+10 0.167005E+10 0.660627E+09
June 0.136896E+10 0.209259E+09 0.115970E+10 0.176351E+10 0.345807E+09
July 0.148277E+10 0.257557E+09 0.122521E+10 0.212510E+10 0.184487E+09
August 0.198008E+10 0.734443E+09 0.124563E+10 0.286018E+10 0.260543E+09
September 0.207912E+10 0.107541E+10 0.100371E+10 0.266079E+10 0.514204E+09
October 0.294316E+10 0.184557E+10 0.109759E+10 0.350589E+10 0.957417E+09
November 0.197499E+10 0.118608E+10 0.788916E+09 0.198904E+10 0.136159E+10
December 0.201896E+10 0.143332E+10 0.585632E+09 0.195410E+10 0.174928E+10
           
Annual Sum or Average 0.233184E+11 0.116332E+11 0.116853E+11 0.263132E+11 0.120223E+11
Minimum of Months 0.136896E+10 0.209259E+09 0.585632E+09 0.167005E+10 0.184487E+09
Maximum of Months 0.294316E+10 0.184557E+10 0.124563E+10 0.350589E+10 0.184693E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.186269E+10 0.121970E+10 0.642988E+09 0.173273E+10 0.184685E+10
February 0.221907E+10 0.146884E+10 0.750225E+09 0.210117E+10 0.168867E+10
March 0.221652E+10 0.123021E+10 0.986313E+09 0.222918E+10 0.141580E+10
April 0.166446E+10 0.658177E+09 0.100628E+10 0.172115E+10 0.103676E+10
May 0.150727E+10 0.314393E+09 0.119288E+10 0.166999E+10 0.660600E+09
June 0.136890E+10 0.209251E+09 0.115965E+10 0.176344E+10 0.345793E+09
July 0.148271E+10 0.257547E+09 0.122517E+10 0.212501E+10 0.184480E+09
August 0.198000E+10 0.734414E+09 0.124558E+10 0.286007E+10 0.260532E+09
September 0.207904E+10 0.107536E+10 0.100367E+10 0.266069E+10 0.514184E+09
October 0.294304E+10 0.184550E+10 0.109754E+10 0.350575E+10 0.957378E+09
November 0.197492E+10 0.118603E+10 0.788885E+09 0.198896E+10 0.136153E+10
December 0.201888E+10 0.143327E+10 0.585609E+09 0.195403E+10 0.174921E+10
           
Annual Sum or Average 0.233175E+11 0.116327E+11 0.116848E+11 0.263122E+11 0.120218E+11
Minimum of Months 0.136890E+10 0.209251E+09 0.585609E+09 0.166999E+10 0.184480E+09
Maximum of Months 0.294304E+10 0.184550E+10 0.124558E+10 0.350575E+10 0.184685E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.825055E+09 0.337945E+09 0.487110E+09 0.452323E+09 0.234980E+10
February 0.109892E+10 0.482650E+09 0.616270E+09 0.675062E+09 0.220353E+10
March 0.179655E+10 0.829418E+09 0.967132E+09 0.146506E+10 0.176931E+10
April 0.190020E+10 0.813049E+09 0.108716E+10 0.176653E+10 0.131593E+10
May 0.228733E+10 0.868639E+09 0.141869E+10 0.250487E+10 0.790104E+09
June 0.242266E+10 0.977128E+09 0.144553E+10 0.301867E+10 0.451076E+09
July 0.234458E+10 0.882898E+09 0.146168E+10 0.313379E+10 0.277093E+09
August 0.259375E+10 0.120073E+10 0.139301E+10 0.346713E+10 0.376264E+09
September 0.178195E+10 0.778710E+09 0.100324E+10 0.212677E+10 0.626181E+09
October 0.182556E+10 0.887727E+09 0.937837E+09 0.192155E+10 0.118481E+10
November 0.829624E+09 0.239767E+09 0.589857E+09 0.468514E+09 0.180394E+10
December 0.762532E+09 0.329950E+09 0.432582E+09 0.403025E+09 0.242278E+10
           
Annual Sum or Average 0.204687E+11 0.862861E+10 0.118401E+11 0.214033E+11 0.155708E+11
Minimum of Months 0.762532E+09 0.239767E+09 0.432582E+09 0.403025E+09 0.277093E+09
Maximum of Months 0.259375E+10 0.120073E+10 0.146168E+10 0.346713E+10 0.242278E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.825055E+09 0.337945E+09 0.487110E+09 0.452323E+09 0.234980E+10
February 0.109892E+10 0.482650E+09 0.616270E+09 0.675062E+09 0.220353E+10
March 0.179655E+10 0.829418E+09 0.967132E+09 0.146506E+10 0.176931E+10
April 0.190020E+10 0.813049E+09 0.108716E+10 0.176653E+10 0.131593E+10
May 0.228733E+10 0.868639E+09 0.141869E+10 0.250487E+10 0.790104E+09
June 0.242266E+10 0.977128E+09 0.144553E+10 0.301867E+10 0.451076E+09
July 0.234458E+10 0.882898E+09 0.146168E+10 0.313379E+10 0.277093E+09
August 0.259375E+10 0.120073E+10 0.139301E+10 0.346713E+10 0.376264E+09
September 0.178195E+10 0.778710E+09 0.100324E+10 0.212677E+10 0.626181E+09
October 0.182556E+10 0.887727E+09 0.937837E+09 0.192155E+10 0.118481E+10
November 0.829624E+09 0.239767E+09 0.589857E+09 0.468514E+09 0.180394E+10
December 0.762532E+09 0.329950E+09 0.432582E+09 0.403025E+09 0.242278E+10
           
Annual Sum or Average 0.204687E+11 0.862861E+10 0.118401E+11 0.214033E+11 0.155708E+11
Minimum of Months 0.762532E+09 0.239767E+09 0.432582E+09 0.403025E+09 0.277093E+09
Maximum of Months 0.259375E+10 0.120073E+10 0.146168E+10 0.346713E+10 0.242278E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.825040E+09 0.337939E+09 0.487101E+09 0.452314E+09 0.234976E+10
February 0.109890E+10 0.482641E+09 0.616259E+09 0.675050E+09 0.220349E+10
March 0.179652E+10 0.829403E+09 0.967114E+09 0.146504E+10 0.176927E+10
April 0.190017E+10 0.813034E+09 0.108714E+10 0.176650E+10 0.131591E+10
May 0.228729E+10 0.868624E+09 0.141866E+10 0.250482E+10 0.790089E+09
June 0.242262E+10 0.977110E+09 0.144550E+10 0.301862E+10 0.451068E+09
July 0.234454E+10 0.882881E+09 0.146166E+10 0.313374E+10 0.277088E+09
August 0.259370E+10 0.120071E+10 0.139299E+10 0.346707E+10 0.376257E+09
September 0.178192E+10 0.778696E+09 0.100323E+10 0.212673E+10 0.626170E+09
October 0.182553E+10 0.887711E+09 0.937820E+09 0.192151E+10 0.118479E+10
November 0.829609E+09 0.239763E+09 0.589846E+09 0.468506E+09 0.180391E+10
December 0.762518E+09 0.329944E+09 0.432574E+09 0.403018E+09 0.242273E+10
           
Annual Sum or Average 0.204683E+11 0.862846E+10 0.118399E+11 0.214029E+11 0.155705E+11
Minimum of Months 0.762518E+09 0.239763E+09 0.432574E+09 0.403018E+09 0.277088E+09
Maximum of Months 0.259370E+10 0.120071E+10 0.146166E+10 0.346707E+10 0.242273E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.180037E+10 0.00 0.180037E+10 0.107162E+09 0.951294E+10
February 0.222531E+10 0.00 0.222531E+10 0.193854E+09 0.896210E+10
March 0.341658E+10 0.00 0.341658E+10 0.114412E+10 0.665944E+10
April 0.397140E+10 11295879.38 0.396010E+10 0.237770E+10 0.458854E+10
May 0.544441E+10 0.181411E+09 0.526300E+10 0.484302E+10 0.293443E+10
June 0.558748E+10 0.300238E+09 0.528724E+10 0.660814E+10 0.155598E+10
July 0.557975E+10 0.201782E+09 0.537796E+10 0.760938E+10 0.904778E+09
August 0.494339E+10 58833294.74 0.488456E+10 0.667016E+10 0.121723E+10
September 0.360628E+10 675310.70 0.360561E+10 0.369638E+10 0.234461E+10
October 0.322501E+10 0.00 0.322501E+10 0.228134E+10 0.439017E+10
November 0.218907E+10 0.00 0.218907E+10 0.570869E+09 0.656101E+10
December 0.157040E+10 0.00 0.157040E+10 66020005.66 0.893834E+10
           
Annual Sum or Average 0.435594E+11 0.754236E+09 0.428052E+11 0.361682E+11 0.585696E+11
Minimum of Months 0.157040E+10 0.00 0.157040E+10 66020005.66 0.904778E+09
Maximum of Months 0.558748E+10 0.300238E+09 0.537796E+10 0.760938E+10 0.951294E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.250717E+10 0.100517E+10 0.150200E+10 0.146953E+10 0.590533E+10
February 0.351182E+10 0.163827E+10 0.187355E+10 0.233080E+10 0.540018E+10
March 0.495999E+10 0.210952E+10 0.285047E+10 0.409493E+10 0.429797E+10
April 0.576032E+10 0.252320E+10 0.323712E+10 0.554501E+10 0.296928E+10
May 0.721893E+10 0.288512E+10 0.433381E+10 0.796667E+10 0.197505E+10
June 0.647459E+10 0.234376E+10 0.413084E+10 0.808101E+10 0.104934E+10
July 0.671970E+10 0.242497E+10 0.429473E+10 0.911132E+10 0.603701E+09
August 0.756655E+10 0.341176E+10 0.415479E+10 0.101979E+11 0.819666E+09
September 0.546114E+10 0.245020E+10 0.301094E+10 0.650818E+10 0.151128E+10
October 0.511596E+10 0.231873E+10 0.279723E+10 0.541596E+10 0.284255E+10
November 0.306176E+10 0.117575E+10 0.188601E+10 0.233138E+10 0.410488E+10
December 0.246480E+10 0.115732E+10 0.130748E+10 0.157472E+10 0.550326E+10
           
Annual Sum or Average 0.608227E+11 0.254438E+11 0.353790E+11 0.646274E+11 0.369825E+11
Minimum of Months 0.246480E+10 0.100517E+10 0.130748E+10 0.146953E+10 0.603701E+09
Maximum of Months 0.756655E+10 0.341176E+10 0.433381E+10 0.101979E+11 0.590533E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.931372E+10 0.609868E+10 0.321503E+10 0.868742E+10 0.866413E+10
February 0.110957E+11 0.734442E+10 0.375123E+10 0.104895E+11 0.803817E+10
March 0.110829E+11 0.615121E+10 0.493170E+10 0.111142E+11 0.665142E+10
April 0.832253E+10 0.329098E+10 0.503155E+10 0.862483E+10 0.482022E+10
May 0.753658E+10 0.157201E+10 0.596457E+10 0.831908E+10 0.316634E+10
June 0.684470E+10 0.104628E+10 0.579842E+10 0.878016E+10 0.167188E+10
July 0.741377E+10 0.128777E+10 0.612600E+10 0.105809E+11 0.940300E+09
August 0.990027E+10 0.367217E+10 0.622810E+10 0.142353E+11 0.133257E+10
September 0.103955E+11 0.537697E+10 0.501851E+10 0.132170E+11 0.249179E+10
October 0.147156E+11 0.922775E+10 0.548787E+10 0.173969E+11 0.462806E+10
November 0.987486E+10 0.593033E+10 0.394454E+10 0.996146E+10 0.634230E+10
December 0.100947E+11 0.716654E+10 0.292813E+10 0.979370E+10 0.812511E+10
           
Annual Sum or Average 0.116591E+12 0.581651E+11 0.584256E+11 0.131200E+12 0.568723E+11
Minimum of Months 0.684470E+10 0.104628E+10 0.292813E+10 0.831908E+10 0.940300E+09
Maximum of Months 0.147156E+11 0.922775E+10 0.622810E+10 0.173969E+11 0.866413E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.247514E+10 0.101382E+10 0.146131E+10 0.144127E+10 0.618090E+10
February 0.329673E+10 0.144793E+10 0.184879E+10 0.213230E+10 0.578109E+10
March 0.538959E+10 0.248823E+10 0.290137E+10 0.459203E+10 0.443694E+10
April 0.570056E+10 0.243912E+10 0.326143E+10 0.553030E+10 0.320666E+10
May 0.686192E+10 0.260589E+10 0.425603E+10 0.759386E+10 0.214475E+10
June 0.726790E+10 0.293135E+10 0.433655E+10 0.910146E+10 0.120245E+10
July 0.703367E+10 0.264867E+10 0.438501E+10 0.947946E+10 0.727301E+09
August 0.778116E+10 0.360216E+10 0.417899E+10 0.105106E+11 0.974917E+09
September 0.534581E+10 0.233611E+10 0.300970E+10 0.644411E+10 0.166249E+10
October 0.547664E+10 0.266315E+10 0.281348E+10 0.590538E+10 0.307042E+10
November 0.248885E+10 0.719294E+09 0.176955E+10 0.159102E+10 0.434625E+10
December 0.228757E+10 0.989839E+09 0.129773E+10 0.135760E+10 0.584019E+10
           
Annual Sum or Average 0.614055E+11 0.258856E+11 0.355200E+11 0.656793E+11 0.395743E+11
Minimum of Months 0.228757E+10 0.719294E+09 0.129773E+10 0.135760E+10 0.727301E+09
Maximum of Months 0.778116E+10 0.360216E+10 0.438501E+10 0.105106E+11 0.618090E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.180037E+10 0.00 0.180037E+10 0.125523E+09 0.914341E+10
February 0.222531E+10 0.00 0.222531E+10 0.228263E+09 0.854339E+10
March 0.341658E+10 0.00 0.341658E+10 0.122279E+10 0.621816E+10
April 0.397140E+10 11295879.38 0.396010E+10 0.247702E+10 0.426784E+10
May 0.544441E+10 0.181411E+09 0.526300E+10 0.488564E+10 0.280556E+10
June 0.558748E+10 0.300238E+09 0.528724E+10 0.656178E+10 0.153782E+10
July 0.557975E+10 0.201782E+09 0.537796E+10 0.752904E+10 0.925163E+09
August 0.494339E+10 58833294.74 0.488456E+10 0.661513E+10 0.121751E+10
September 0.360628E+10 675310.70 0.360561E+10 0.370842E+10 0.224081E+10
October 0.322501E+10 0.00 0.322501E+10 0.239885E+10 0.404860E+10
November 0.218907E+10 0.00 0.218907E+10 0.669771E+09 0.602102E+10
December 0.157040E+10 0.00 0.157040E+10 0.100523E+09 0.832568E+10
           
Annual Sum or Average 0.435594E+11 0.754236E+09 0.428052E+11 0.365227E+11 0.552950E+11
Minimum of Months 0.157040E+10 0.00 0.157040E+10 0.100523E+09 0.925163E+09
Maximum of Months 0.558748E+10 0.300238E+09 0.537796E+10 0.752904E+10 0.914341E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.250717E+10 0.100517E+10 0.150200E+10 0.149927E+10 0.567175E+10
February 0.351182E+10 0.163827E+10 0.187355E+10 0.238826E+10 0.514344E+10
March 0.495999E+10 0.210952E+10 0.285047E+10 0.415223E+10 0.403248E+10
April 0.576032E+10 0.252320E+10 0.323712E+10 0.559601E+10 0.279507E+10
May 0.721893E+10 0.288512E+10 0.433381E+10 0.797069E+10 0.190283E+10
June 0.647459E+10 0.234376E+10 0.413084E+10 0.804310E+10 0.104133E+10
July 0.671970E+10 0.242497E+10 0.429473E+10 0.905386E+10 0.618403E+09
August 0.756655E+10 0.341176E+10 0.415479E+10 0.101498E+11 0.822347E+09
September 0.546114E+10 0.245020E+10 0.301094E+10 0.650374E+10 0.145849E+10
October 0.511596E+10 0.231873E+10 0.279723E+10 0.547574E+10 0.265605E+10
November 0.306176E+10 0.117575E+10 0.188601E+10 0.242144E+10 0.379028E+10
December 0.246480E+10 0.115732E+10 0.130748E+10 0.163720E+10 0.512550E+10
           
Annual Sum or Average 0.608227E+11 0.254438E+11 0.353790E+11 0.648913E+11 0.350580E+11
Minimum of Months 0.246480E+10 0.100517E+10 0.130748E+10 0.149927E+10 0.618403E+09
Maximum of Months 0.756655E+10 0.341176E+10 0.433381E+10 0.101498E+11 0.567175E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.931372E+10 0.609868E+10 0.321503E+10 0.874521E+10 0.826486E+10
February 0.110957E+11 0.734442E+10 0.375123E+10 0.105863E+11 0.760574E+10
March 0.110829E+11 0.615121E+10 0.493170E+10 0.111887E+11 0.621898E+10
April 0.832253E+10 0.329098E+10 0.503155E+10 0.869789E+10 0.450925E+10
May 0.753658E+10 0.157201E+10 0.596457E+10 0.834232E+10 0.302362E+10
June 0.684470E+10 0.104628E+10 0.579842E+10 0.872996E+10 0.164833E+10
July 0.741377E+10 0.128777E+10 0.612600E+10 0.104984E+11 0.957008E+09
August 0.990027E+10 0.367217E+10 0.622810E+10 0.141662E+11 0.132982E+10
September 0.103955E+11 0.537697E+10 0.501851E+10 0.132081E+11 0.239679E+10
October 0.147156E+11 0.922775E+10 0.548787E+10 0.174501E+11 0.434185E+10
November 0.987486E+10 0.593033E+10 0.394454E+10 0.100963E+11 0.583647E+10
December 0.100947E+11 0.716654E+10 0.292813E+10 0.992242E+10 0.753957E+10
           
Annual Sum or Average 0.116591E+12 0.581651E+11 0.584256E+11 0.131632E+12 0.536723E+11
Minimum of Months 0.684470E+10 0.104628E+10 0.292813E+10 0.834232E+10 0.957008E+09
Maximum of Months 0.147156E+11 0.922775E+10 0.622810E+10 0.174501E+11 0.826486E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.247514E+10 0.101382E+10 0.146131E+10 0.145744E+10 0.593915E+10
February 0.329673E+10 0.144793E+10 0.184879E+10 0.215124E+10 0.553626E+10
March 0.538959E+10 0.248823E+10 0.290137E+10 0.462588E+10 0.419121E+10
April 0.570056E+10 0.243912E+10 0.326143E+10 0.556738E+10 0.302775E+10
May 0.686192E+10 0.260589E+10 0.425603E+10 0.760262E+10 0.206078E+10
June 0.726790E+10 0.293135E+10 0.433655E+10 0.906246E+10 0.118594E+10
July 0.703367E+10 0.264867E+10 0.438501E+10 0.942356E+10 0.732658E+09
August 0.778116E+10 0.360216E+10 0.417899E+10 0.104664E+11 0.970485E+09
September 0.534581E+10 0.233611E+10 0.300970E+10 0.644364E+10 0.160196E+10
October 0.547664E+10 0.266315E+10 0.281348E+10 0.595196E+10 0.288609E+10
November 0.248885E+10 0.719294E+09 0.176955E+10 0.164679E+10 0.405136E+10
December 0.228757E+10 0.989839E+09 0.129773E+10 0.139008E+10 0.548341E+10
           
Annual Sum or Average 0.614055E+11 0.258856E+11 0.355200E+11 0.657894E+11 0.376671E+11
Minimum of Months 0.228757E+10 0.719294E+09 0.129773E+10 0.139008E+10 0.732658E+09
Maximum of Months 0.778116E+10 0.360216E+10 0.438501E+10 0.104664E+11 0.593915E+10



Table of Contents

Report: WindowZoneSummaryMonthly

For: BASEMENT

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: CORE_BOTTOM

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: CORE_MID

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: CORE_TOP

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 15.37 4001.74 672.18 0.00 672.18 0.00 0.00
February 50.20 4132.39 919.86 0.00 919.86 0.00 0.00
March 347.31 2847.25 1275.61 0.00 1275.61 0.00 0.00
April 829.07 2035.00 1532.18 4.36 1527.82 0.00 0.00
May 1776.78 1172.40 2032.72 67.73 1964.98 0.00 0.00
June 2541.16 629.85 2155.67 115.83 2039.84 0.00 0.00
July 2836.48 338.58 2083.25 75.34 2007.91 0.00 0.00
August 2473.34 460.09 1845.66 21.97 1823.69 0.00 0.00
September 1401.84 980.95 1391.32 0.26 1391.06 0.00 0.00
October 792.10 1835.94 1204.09 0.00 1204.09 0.00 0.00
November 161.91 2972.02 844.55 0.00 844.55 0.00 0.00
December 7.38 3902.74 586.32 0.00 586.32 0.00 0.00
               
Annual Sum or Average 1109.96 2097.43 1381.27 23.92 1357.35 0.00 0.00
Minimum of Months 7.38 338.58 586.32 0.00 586.32 0.00 0.00
Maximum of Months 2836.48 4132.39 2155.67 115.83 2039.84 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 516.52 2451.06 936.08 375.29 560.78 0.00 0.00
February 926.78 2445.29 1451.65 677.20 774.45 0.00 0.00
March 1506.16 1763.05 1851.85 787.61 1064.25 0.00 0.00
April 2123.82 1247.25 2222.35 973.46 1248.89 0.00 0.00
May 2984.37 778.80 2695.25 1077.18 1618.07 0.00 0.00
June 3139.97 408.87 2497.92 904.23 1593.69 0.00 0.00
July 3432.43 200.20 2508.86 905.39 1603.47 0.00 0.00
August 3842.66 272.43 2825.04 1273.81 1551.23 0.00 0.00
September 2520.06 615.98 2106.93 945.30 1161.63 0.00 0.00
October 2011.41 1149.05 1910.09 865.72 1044.37 0.00 0.00
November 860.14 1787.02 1181.24 453.61 727.63 0.00 0.00
December 557.63 2310.63 920.25 432.09 488.16 0.00 0.00
               
Annual Sum or Average 2042.89 1279.24 1928.68 806.82 1121.86 0.00 0.00
Minimum of Months 516.52 200.20 920.25 375.29 488.16 0.00 0.00
Maximum of Months 3842.66 2451.06 2825.04 1273.81 1618.07 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 3234.75 3447.79 3477.36 2277.00 1200.36 0.00 0.00
February 4342.83 3490.25 4586.51 3035.90 1550.61 0.00 0.00
March 4161.53 2643.08 4137.90 2296.61 1841.29 0.00 0.00
April 3320.23 1999.99 3210.86 1269.67 1941.19 0.00 0.00
May 3117.60 1233.24 2813.85 586.92 2226.92 0.00 0.00
June 3401.80 667.06 2640.71 403.66 2237.05 0.00 0.00
July 3967.07 344.40 2767.99 480.80 2287.19 0.00 0.00
August 5339.31 486.37 3696.35 1371.04 2325.31 0.00 0.00
September 5132.66 991.90 4010.62 2074.45 1936.16 0.00 0.00
October 6544.70 1787.28 5494.20 3445.26 2048.94 0.00 0.00
November 3836.85 2626.50 3809.76 2287.94 1521.82 0.00 0.00
December 3647.86 3265.50 3768.93 2675.69 1093.24 0.00 0.00
               
Annual Sum or Average 4171.90 1906.10 3697.08 1844.41 1852.67 0.00 0.00
Minimum of Months 3117.60 344.40 2640.71 403.66 1093.24 0.00 0.00
Maximum of Months 6544.70 3490.25 5494.20 3445.26 2325.31 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 506.63 2631.93 924.11 378.52 545.59 0.00 0.00
February 837.13 2732.54 1362.74 598.52 764.22 0.00 0.00
March 1640.96 1981.74 2012.25 929.00 1083.25 0.00 0.00
April 2044.58 1523.06 2199.30 941.02 1258.27 0.00 0.00
May 2805.62 884.97 2561.96 972.93 1589.03 0.00 0.00
June 3493.81 522.08 2803.99 1130.93 1673.06 0.00 0.00
July 3510.05 310.36 2626.08 988.90 1637.18 0.00 0.00
August 3883.41 421.44 2905.16 1344.90 1560.26 0.00 0.00
September 2461.53 724.74 2062.44 901.28 1161.16 0.00 0.00
October 2152.26 1327.07 2044.75 994.31 1050.44 0.00 0.00
November 542.26 2087.88 960.21 277.51 682.70 0.00 0.00
December 451.41 2713.67 854.08 369.57 484.52 0.00 0.00
               
Annual Sum or Average 2036.07 1481.23 1947.16 820.83 1126.34 0.00 0.00
Minimum of Months 451.41 310.36 854.08 277.51 484.52 0.00 0.00
Maximum of Months 3883.41 2732.54 2905.16 1344.90 1673.06 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 40.01 3551.72 672.18 0.00 672.18 0.00 0.00
February 80.13 3704.57 919.85 0.00 919.85 0.00 0.00
March 427.17 2486.35 1275.60 0.00 1275.60 0.00 0.00
April 917.32 1770.27 1532.17 4.36 1527.82 0.00 0.00
May 1808.18 1095.59 2032.71 67.73 1964.98 0.00 0.00
June 2549.44 600.30 2155.66 115.83 2039.83 0.00 0.00
July 2841.02 337.81 2083.24 75.34 2007.90 0.00 0.00
August 2490.35 454.46 1845.65 21.97 1823.68 0.00 0.00
September 1426.07 904.56 1391.31 0.26 1391.05 0.00 0.00
October 851.76 1639.10 1204.08 0.00 1204.08 0.00 0.00
November 220.24 2531.25 844.55 0.00 844.55 0.00 0.00
December 24.65 3337.20 586.32 0.00 586.32 0.00 0.00
               
Annual Sum or Average 1146.88 1857.23 1381.26 23.92 1357.34 0.00 0.00
Minimum of Months 24.65 337.81 586.32 0.00 586.32 0.00 0.00
Maximum of Months 2841.02 3704.57 2155.66 115.83 2039.83 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 548.66 2204.80 936.07 375.29 560.78 0.00 0.00
February 963.46 2232.22 1451.64 677.19 774.45 0.00 0.00
March 1528.87 1604.68 1851.85 787.60 1064.24 0.00 0.00
April 2139.28 1145.56 2222.34 973.46 1248.89 0.00 0.00
May 2974.41 737.40 2695.24 1077.18 1618.06 0.00 0.00
June 3117.67 404.84 2497.91 904.23 1593.69 0.00 0.00
July 3401.78 225.40 2508.85 905.38 1603.47 0.00 0.00
August 3807.46 306.03 2825.03 1273.80 1551.22 0.00 0.00
September 2510.87 583.05 2106.92 945.29 1161.63 0.00 0.00
October 2022.09 1061.29 1910.08 865.71 1044.37 0.00 0.00
November 899.45 1583.67 1181.24 453.61 727.63 0.00 0.00
December 587.93 2054.68 920.25 432.09 488.16 0.00 0.00
               
Annual Sum or Average 2049.32 1172.71 1928.68 806.82 1121.86 0.00 0.00
Minimum of Months 548.66 225.40 920.25 375.29 488.16 0.00 0.00
Maximum of Months 3807.46 2232.22 2825.03 1273.80 1618.06 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 3243.51 3234.82 3477.34 2276.99 1200.36 0.00 0.00
February 4335.93 3322.65 4586.50 3035.89 1550.61 0.00 0.00
March 4149.56 2483.36 4137.89 2296.60 1841.29 0.00 0.00
April 3327.48 1859.65 3210.85 1269.67 1941.19 0.00 0.00
May 3105.99 1182.18 2813.84 586.92 2226.91 0.00 0.00
June 3387.41 645.02 2640.70 403.66 2237.04 0.00 0.00
July 3950.45 351.07 2767.98 480.80 2287.19 0.00 0.00
August 5314.87 497.52 3696.34 1371.03 2325.30 0.00 0.00
September 5099.16 961.34 4010.60 2074.45 1936.15 0.00 0.00
October 6495.25 1727.92 5494.18 3445.25 2048.94 0.00 0.00
November 3843.16 2446.88 3809.75 2287.93 1521.81 0.00 0.00
December 3656.55 3033.57 3768.92 2675.68 1093.24 0.00 0.00
               
Annual Sum or Average 4160.34 1803.41 3697.07 1844.40 1852.67 0.00 0.00
Minimum of Months 3105.99 351.07 2640.70 403.66 1093.24 0.00 0.00
Maximum of Months 6495.25 3322.65 5494.18 3445.25 2325.30 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 538.11 2307.68 924.11 378.52 545.59 0.00 0.00
February 881.41 2389.67 1362.73 598.52 764.22 0.00 0.00
March 1714.47 1656.56 2012.24 929.00 1083.25 0.00 0.00
April 2133.60 1237.14 2199.29 941.02 1258.27 0.00 0.00
May 2835.22 800.76 2561.95 972.93 1589.02 0.00 0.00
June 3511.37 463.91 2803.98 1130.92 1673.05 0.00 0.00
July 3539.22 271.54 2626.07 988.90 1637.17 0.00 0.00
August 3924.20 363.99 2905.15 1344.89 1560.26 0.00 0.00
September 2486.15 641.39 2062.43 901.28 1161.15 0.00 0.00
October 2204.82 1146.36 2044.74 994.31 1050.43 0.00 0.00
November 613.82 1676.79 960.20 277.51 682.70 0.00 0.00
December 506.87 2180.48 854.08 369.56 484.52 0.00 0.00
               
Annual Sum or Average 2082.68 1254.89 1947.16 820.83 1126.33 0.00 0.00
Minimum of Months 506.87 271.54 854.08 277.51 484.52 0.00 0.00
Maximum of Months 3924.20 2389.67 2905.15 1344.89 1673.05 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 46.86 3413.76 672.18 0.00 672.18 0.00 0.00
February 94.35 3531.49 919.85 0.00 919.85 0.00 0.00
March 456.54 2321.59 1275.60 0.00 1275.60 0.00 0.00
April 955.64 1646.54 1532.17 4.36 1527.82 0.00 0.00
May 1824.09 1047.48 2032.71 67.73 1964.98 0.00 0.00
June 2531.55 593.29 2155.66 115.83 2039.83 0.00 0.00
July 2811.02 345.42 2083.24 75.34 2007.90 0.00 0.00
August 2469.81 454.57 1845.65 21.97 1823.68 0.00 0.00
September 1430.72 864.51 1391.31 0.26 1391.05 0.00 0.00
October 895.63 1511.57 1204.08 0.00 1204.08 0.00 0.00
November 258.40 2322.92 844.55 0.00 844.55 0.00 0.00
December 37.53 3108.45 586.32 0.00 586.32 0.00 0.00
               
Annual Sum or Average 1158.13 1753.39 1381.26 23.92 1357.34 0.00 0.00
Minimum of Months 37.53 345.42 586.32 0.00 586.32 0.00 0.00
Maximum of Months 2811.02 3531.49 2155.66 115.83 2039.83 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 559.76 2117.59 936.07 375.29 560.78 0.00 0.00
February 987.21 2126.09 1451.64 677.19 774.45 0.00 0.00
March 1550.26 1505.55 1851.85 787.60 1064.24 0.00 0.00
April 2158.95 1078.34 2222.34 973.46 1248.89 0.00 0.00
May 2975.91 710.44 2695.24 1077.18 1618.06 0.00 0.00
June 3103.05 401.75 2497.91 904.23 1593.69 0.00 0.00
July 3380.33 230.89 2508.85 905.38 1603.47 0.00 0.00
August 3789.50 307.03 2825.03 1273.80 1551.22 0.00 0.00
September 2509.16 562.69 2106.92 945.29 1161.63 0.00 0.00
October 2044.41 991.66 1910.08 865.71 1044.37 0.00 0.00
November 934.20 1462.30 1181.24 453.61 727.63 0.00 0.00
December 611.26 1913.64 920.25 432.09 488.16 0.00 0.00
               
Annual Sum or Average 2057.69 1111.68 1928.68 806.82 1121.86 0.00 0.00
Minimum of Months 559.76 230.89 920.25 375.29 488.16 0.00 0.00
Maximum of Months 3789.50 2126.09 2825.03 1273.80 1618.06 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 3265.09 3085.75 3477.34 2276.99 1200.36 0.00 0.00
February 4375.96 3143.91 4586.50 3035.89 1550.61 0.00 0.00
March 4177.37 2321.90 4137.89 2296.60 1841.29 0.00 0.00
April 3355.67 1739.68 3210.85 1269.67 1941.19 0.00 0.00
May 3114.67 1128.89 2813.84 586.92 2226.91 0.00 0.00
June 3368.04 635.93 2640.70 403.66 2237.04 0.00 0.00
July 3919.65 357.31 2767.98 480.80 2287.19 0.00 0.00
August 5289.06 496.50 3696.34 1371.03 2325.30 0.00 0.00
September 5095.71 924.69 4010.60 2074.45 1936.15 0.00 0.00
October 6515.13 1621.06 5494.18 3445.25 2048.94 0.00 0.00
November 3895.17 2251.73 3809.75 2287.93 1521.81 0.00 0.00
December 3704.61 2814.95 3768.92 2675.68 1093.24 0.00 0.00
               
Annual Sum or Average 4174.02 1701.94 3697.07 1844.40 1852.67 0.00 0.00
Minimum of Months 3114.67 357.31 2640.70 403.66 1093.24 0.00 0.00
Maximum of Months 6515.13 3143.91 5494.18 3445.25 2325.30 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 544.15 2217.43 924.11 378.52 545.59 0.00 0.00
February 889.23 2288.47 1362.73 598.52 764.22 0.00 0.00
March 1727.11 1564.82 2012.24 929.00 1083.25 0.00 0.00
April 2147.91 1168.11 2199.29 941.02 1258.27 0.00 0.00
May 2838.49 769.41 2561.95 972.93 1589.02 0.00 0.00
June 3496.32 457.54 2803.98 1130.92 1673.05 0.00 0.00
July 3518.35 273.54 2626.07 988.90 1637.17 0.00 0.00
August 3907.69 362.34 2905.15 1344.89 1560.26 0.00 0.00
September 2485.97 618.04 2062.43 901.28 1161.15 0.00 0.00
October 2222.21 1077.54 2044.74 994.31 1050.43 0.00 0.00
November 635.34 1563.03 960.20 277.51 682.70 0.00 0.00
December 519.00 2047.27 854.08 369.56 484.52 0.00 0.00
               
Annual Sum or Average 2086.17 1194.41 1947.16 820.83 1126.33 0.00 0.00
Minimum of Months 519.00 273.54 854.08 277.51 484.52 0.00 0.00
Maximum of Months 3907.69 2288.47 2905.15 1344.89 1673.05 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: GROUNDFLOOR_PLENUM

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: MIDFLOOR_PLENUM

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: TOPFLOOR_PLENUM

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: DATACENTER_MID_ZN_6

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: BASEMENT

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: CORE_BOTTOM

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: CORE_MID

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: CORE_TOP

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 41169863.20 0.107183E+11 0.180038E+10 0.00 0.180038E+10 0.00 0.00
February 0.121453E+09 0.999708E+10 0.222532E+10 0.00 0.222532E+10 0.00 0.00
March 0.930228E+09 0.762607E+10 0.341659E+10 0.00 0.341659E+10 0.00 0.00
April 0.214895E+10 0.527472E+10 0.397141E+10 11295919.49 0.396012E+10 0.00 0.00
May 0.475892E+10 0.314017E+10 0.544443E+10 0.181411E+09 0.526301E+10 0.00 0.00
June 0.658668E+10 0.163257E+10 0.558750E+10 0.300240E+09 0.528726E+10 0.00 0.00
July 0.759723E+10 0.906856E+09 0.557977E+10 0.201783E+09 0.537798E+10 0.00 0.00
August 0.662460E+10 0.123230E+10 0.494341E+10 58833503.66 0.488457E+10 0.00 0.00
September 0.363357E+10 0.254263E+10 0.360630E+10 675313.09 0.360562E+10 0.00 0.00
October 0.212156E+10 0.491738E+10 0.322503E+10 0.00 0.322503E+10 0.00 0.00
November 0.419659E+09 0.770348E+10 0.218908E+10 0.00 0.218908E+10 0.00 0.00
December 19761196.54 0.104531E+11 0.157041E+10 0.00 0.157041E+10 0.00 0.00
               
Annual Sum or Average 0.350038E+11 0.661446E+11 0.435596E+11 0.754239E+09 0.428054E+11 0.00 0.00
Minimum of Months 19761196.54 0.906856E+09 0.157041E+10 0.00 0.157041E+10 0.00 0.00
Maximum of Months 0.759723E+10 0.107183E+11 0.558750E+10 0.300240E+09 0.537798E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.138345E+10 0.656492E+10 0.250718E+10 0.100518E+10 0.150201E+10 0.00 0.00
February 0.224207E+10 0.591564E+10 0.351183E+10 0.163827E+10 0.187356E+10 0.00 0.00
March 0.403409E+10 0.472216E+10 0.496001E+10 0.210953E+10 0.285048E+10 0.00 0.00
April 0.550493E+10 0.323287E+10 0.576034E+10 0.252321E+10 0.323713E+10 0.00 0.00
May 0.799334E+10 0.208595E+10 0.721896E+10 0.288513E+10 0.433383E+10 0.00 0.00
June 0.813881E+10 0.105980E+10 0.647462E+10 0.234377E+10 0.413085E+10 0.00 0.00
July 0.919341E+10 0.536205E+09 0.671973E+10 0.242498E+10 0.429475E+10 0.00 0.00
August 0.102922E+11 0.729668E+09 0.756658E+10 0.341177E+10 0.415481E+10 0.00 0.00
September 0.653199E+10 0.159662E+10 0.546116E+10 0.245021E+10 0.301095E+10 0.00 0.00
October 0.538737E+10 0.307762E+10 0.511598E+10 0.231873E+10 0.279724E+10 0.00 0.00
November 0.222949E+10 0.463195E+10 0.306178E+10 0.117575E+10 0.188602E+10 0.00 0.00
December 0.149356E+10 0.618880E+10 0.246481E+10 0.115732E+10 0.130749E+10 0.00 0.00
               
Annual Sum or Average 0.644247E+11 0.403422E+11 0.608230E+11 0.254439E+11 0.353791E+11 0.00 0.00
Minimum of Months 0.138345E+10 0.536205E+09 0.246481E+10 0.100518E+10 0.130749E+10 0.00 0.00
Maximum of Months 0.102922E+11 0.656492E+10 0.756658E+10 0.341177E+10 0.433383E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.866394E+10 0.923456E+10 0.931375E+10 0.609870E+10 0.321504E+10 0.00 0.00
February 0.105062E+11 0.844361E+10 0.110957E+11 0.734445E+10 0.375125E+10 0.00 0.00
March 0.111462E+11 0.707924E+10 0.110830E+11 0.615123E+10 0.493172E+10 0.00 0.00
April 0.860605E+10 0.518397E+10 0.832256E+10 0.329099E+10 0.503157E+10 0.00 0.00
May 0.835019E+10 0.330311E+10 0.753661E+10 0.157202E+10 0.596459E+10 0.00 0.00
June 0.881747E+10 0.172902E+10 0.684472E+10 0.104629E+10 0.579844E+10 0.00 0.00
July 0.106254E+11 0.922429E+09 0.741380E+10 0.128777E+10 0.612602E+10 0.00 0.00
August 0.143008E+11 0.130270E+10 0.990031E+10 0.367219E+10 0.622812E+10 0.00 0.00
September 0.133039E+11 0.257100E+10 0.103955E+11 0.537699E+10 0.501853E+10 0.00 0.00
October 0.175293E+11 0.478704E+10 0.147157E+11 0.922779E+10 0.548789E+10 0.00 0.00
November 0.994512E+10 0.680788E+10 0.987490E+10 0.593035E+10 0.394455E+10 0.00 0.00
December 0.977044E+10 0.874631E+10 0.100947E+11 0.716657E+10 0.292814E+10 0.00 0.00
               
Annual Sum or Average 0.131565E+12 0.601109E+11 0.116591E+12 0.581653E+11 0.584259E+11 0.00 0.00
Minimum of Months 0.835019E+10 0.922429E+09 0.684472E+10 0.104629E+10 0.292814E+10 0.00 0.00
Maximum of Months 0.175293E+11 0.923456E+10 0.147157E+11 0.922779E+10 0.622812E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.135696E+10 0.704935E+10 0.247515E+10 0.101383E+10 0.146132E+10 0.00 0.00
February 0.202517E+10 0.661056E+10 0.329674E+10 0.144794E+10 0.184880E+10 0.00 0.00
March 0.439516E+10 0.530789E+10 0.538962E+10 0.248824E+10 0.290138E+10 0.00 0.00
April 0.529955E+10 0.394776E+10 0.570058E+10 0.243913E+10 0.326145E+10 0.00 0.00
May 0.751457E+10 0.237030E+10 0.686195E+10 0.260590E+10 0.425605E+10 0.00 0.00
June 0.905597E+10 0.135322E+10 0.726793E+10 0.293137E+10 0.433657E+10 0.00 0.00
July 0.940132E+10 0.831275E+09 0.703370E+10 0.264868E+10 0.438503E+10 0.00 0.00
August 0.104013E+11 0.112879E+10 0.778119E+10 0.360218E+10 0.417901E+10 0.00 0.00
September 0.638028E+10 0.187853E+10 0.534583E+10 0.233612E+10 0.300972E+10 0.00 0.00
October 0.576461E+10 0.355441E+10 0.547666E+10 0.266317E+10 0.281349E+10 0.00 0.00
November 0.140553E+10 0.541179E+10 0.248886E+10 0.719297E+09 0.176956E+10 0.00 0.00
December 0.120907E+10 0.726829E+10 0.228758E+10 0.989843E+09 0.129774E+10 0.00 0.00
               
Annual Sum or Average 0.642095E+11 0.467122E+11 0.614058E+11 0.258857E+11 0.355201E+11 0.00 0.00
Minimum of Months 0.120907E+10 0.831275E+09 0.228758E+10 0.719297E+09 0.129774E+10 0.00 0.00
Maximum of Months 0.104013E+11 0.726829E+10 0.778119E+10 0.360218E+10 0.438503E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.107162E+09 0.951294E+10 0.180037E+10 0.00 0.180037E+10 0.00 0.00
February 0.193854E+09 0.896210E+10 0.222531E+10 0.00 0.222531E+10 0.00 0.00
March 0.114412E+10 0.665944E+10 0.341658E+10 0.00 0.341658E+10 0.00 0.00
April 0.237770E+10 0.458854E+10 0.397140E+10 11295879.38 0.396010E+10 0.00 0.00
May 0.484302E+10 0.293443E+10 0.544441E+10 0.181411E+09 0.526300E+10 0.00 0.00
June 0.660814E+10 0.155598E+10 0.558748E+10 0.300238E+09 0.528724E+10 0.00 0.00
July 0.760938E+10 0.904778E+09 0.557975E+10 0.201782E+09 0.537796E+10 0.00 0.00
August 0.667016E+10 0.121723E+10 0.494339E+10 58833294.74 0.488456E+10 0.00 0.00
September 0.369638E+10 0.234461E+10 0.360628E+10 675310.70 0.360561E+10 0.00 0.00
October 0.228134E+10 0.439017E+10 0.322501E+10 0.00 0.322501E+10 0.00 0.00
November 0.570869E+09 0.656101E+10 0.218907E+10 0.00 0.218907E+10 0.00 0.00
December 66020005.66 0.893834E+10 0.157040E+10 0.00 0.157040E+10 0.00 0.00
               
Annual Sum or Average 0.361682E+11 0.585696E+11 0.435594E+11 0.754236E+09 0.428052E+11 0.00 0.00
Minimum of Months 66020005.66 0.904778E+09 0.157040E+10 0.00 0.157040E+10 0.00 0.00
Maximum of Months 0.760938E+10 0.951294E+10 0.558748E+10 0.300238E+09 0.537796E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.146953E+10 0.590533E+10 0.250717E+10 0.100517E+10 0.150200E+10 0.00 0.00
February 0.233080E+10 0.540018E+10 0.351182E+10 0.163827E+10 0.187355E+10 0.00 0.00
March 0.409493E+10 0.429797E+10 0.495999E+10 0.210952E+10 0.285047E+10 0.00 0.00
April 0.554501E+10 0.296928E+10 0.576032E+10 0.252320E+10 0.323712E+10 0.00 0.00
May 0.796667E+10 0.197505E+10 0.721893E+10 0.288512E+10 0.433381E+10 0.00 0.00
June 0.808101E+10 0.104934E+10 0.647459E+10 0.234376E+10 0.413084E+10 0.00 0.00
July 0.911132E+10 0.603701E+09 0.671970E+10 0.242497E+10 0.429473E+10 0.00 0.00
August 0.101979E+11 0.819666E+09 0.756655E+10 0.341176E+10 0.415479E+10 0.00 0.00
September 0.650818E+10 0.151128E+10 0.546114E+10 0.245020E+10 0.301094E+10 0.00 0.00
October 0.541596E+10 0.284255E+10 0.511596E+10 0.231873E+10 0.279723E+10 0.00 0.00
November 0.233138E+10 0.410488E+10 0.306176E+10 0.117575E+10 0.188601E+10 0.00 0.00
December 0.157472E+10 0.550326E+10 0.246480E+10 0.115732E+10 0.130748E+10 0.00 0.00
               
Annual Sum or Average 0.646274E+11 0.369825E+11 0.608227E+11 0.254438E+11 0.353790E+11 0.00 0.00
Minimum of Months 0.146953E+10 0.603701E+09 0.246480E+10 0.100517E+10 0.130748E+10 0.00 0.00
Maximum of Months 0.101979E+11 0.590533E+10 0.756655E+10 0.341176E+10 0.433381E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.868742E+10 0.866413E+10 0.931372E+10 0.609868E+10 0.321503E+10 0.00 0.00
February 0.104895E+11 0.803817E+10 0.110957E+11 0.734442E+10 0.375123E+10 0.00 0.00
March 0.111142E+11 0.665142E+10 0.110829E+11 0.615121E+10 0.493170E+10 0.00 0.00
April 0.862483E+10 0.482022E+10 0.832253E+10 0.329098E+10 0.503155E+10 0.00 0.00
May 0.831908E+10 0.316634E+10 0.753658E+10 0.157201E+10 0.596457E+10 0.00 0.00
June 0.878016E+10 0.167188E+10 0.684470E+10 0.104628E+10 0.579842E+10 0.00 0.00
July 0.105809E+11 0.940300E+09 0.741377E+10 0.128777E+10 0.612600E+10 0.00 0.00
August 0.142353E+11 0.133257E+10 0.990027E+10 0.367217E+10 0.622810E+10 0.00 0.00
September 0.132170E+11 0.249179E+10 0.103955E+11 0.537697E+10 0.501851E+10 0.00 0.00
October 0.173969E+11 0.462806E+10 0.147156E+11 0.922775E+10 0.548787E+10 0.00 0.00
November 0.996146E+10 0.634230E+10 0.987486E+10 0.593033E+10 0.394454E+10 0.00 0.00
December 0.979370E+10 0.812511E+10 0.100947E+11 0.716654E+10 0.292813E+10 0.00 0.00
               
Annual Sum or Average 0.131200E+12 0.568723E+11 0.116591E+12 0.581651E+11 0.584256E+11 0.00 0.00
Minimum of Months 0.831908E+10 0.940300E+09 0.684470E+10 0.104628E+10 0.292813E+10 0.00 0.00
Maximum of Months 0.173969E+11 0.866413E+10 0.147156E+11 0.922775E+10 0.622810E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.144127E+10 0.618090E+10 0.247514E+10 0.101382E+10 0.146131E+10 0.00 0.00
February 0.213230E+10 0.578109E+10 0.329673E+10 0.144793E+10 0.184879E+10 0.00 0.00
March 0.459203E+10 0.443694E+10 0.538959E+10 0.248823E+10 0.290137E+10 0.00 0.00
April 0.553030E+10 0.320666E+10 0.570056E+10 0.243912E+10 0.326143E+10 0.00 0.00
May 0.759386E+10 0.214475E+10 0.686192E+10 0.260589E+10 0.425603E+10 0.00 0.00
June 0.910146E+10 0.120245E+10 0.726790E+10 0.293135E+10 0.433655E+10 0.00 0.00
July 0.947946E+10 0.727301E+09 0.703367E+10 0.264867E+10 0.438501E+10 0.00 0.00
August 0.105106E+11 0.974917E+09 0.778116E+10 0.360216E+10 0.417899E+10 0.00 0.00
September 0.644411E+10 0.166249E+10 0.534581E+10 0.233611E+10 0.300970E+10 0.00 0.00
October 0.590538E+10 0.307042E+10 0.547664E+10 0.266315E+10 0.281348E+10 0.00 0.00
November 0.159102E+10 0.434625E+10 0.248885E+10 0.719294E+09 0.176955E+10 0.00 0.00
December 0.135760E+10 0.584019E+10 0.228757E+10 0.989839E+09 0.129773E+10 0.00 0.00
               
Annual Sum or Average 0.656793E+11 0.395743E+11 0.614055E+11 0.258856E+11 0.355200E+11 0.00 0.00
Minimum of Months 0.135760E+10 0.727301E+09 0.228757E+10 0.719294E+09 0.129773E+10 0.00 0.00
Maximum of Months 0.105106E+11 0.618090E+10 0.778116E+10 0.360216E+10 0.438501E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.125523E+09 0.914341E+10 0.180037E+10 0.00 0.180037E+10 0.00 0.00
February 0.228263E+09 0.854339E+10 0.222531E+10 0.00 0.222531E+10 0.00 0.00
March 0.122279E+10 0.621816E+10 0.341658E+10 0.00 0.341658E+10 0.00 0.00
April 0.247702E+10 0.426784E+10 0.397140E+10 11295879.38 0.396010E+10 0.00 0.00
May 0.488564E+10 0.280556E+10 0.544441E+10 0.181411E+09 0.526300E+10 0.00 0.00
June 0.656178E+10 0.153782E+10 0.558748E+10 0.300238E+09 0.528724E+10 0.00 0.00
July 0.752904E+10 0.925163E+09 0.557975E+10 0.201782E+09 0.537796E+10 0.00 0.00
August 0.661513E+10 0.121751E+10 0.494339E+10 58833294.74 0.488456E+10 0.00 0.00
September 0.370842E+10 0.224081E+10 0.360628E+10 675310.70 0.360561E+10 0.00 0.00
October 0.239885E+10 0.404860E+10 0.322501E+10 0.00 0.322501E+10 0.00 0.00
November 0.669771E+09 0.602102E+10 0.218907E+10 0.00 0.218907E+10 0.00 0.00
December 0.100523E+09 0.832568E+10 0.157040E+10 0.00 0.157040E+10 0.00 0.00
               
Annual Sum or Average 0.365227E+11 0.552950E+11 0.435594E+11 0.754236E+09 0.428052E+11 0.00 0.00
Minimum of Months 0.100523E+09 0.925163E+09 0.157040E+10 0.00 0.157040E+10 0.00 0.00
Maximum of Months 0.752904E+10 0.914341E+10 0.558748E+10 0.300238E+09 0.537796E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.149927E+10 0.567175E+10 0.250717E+10 0.100517E+10 0.150200E+10 0.00 0.00
February 0.238826E+10 0.514344E+10 0.351182E+10 0.163827E+10 0.187355E+10 0.00 0.00
March 0.415223E+10 0.403248E+10 0.495999E+10 0.210952E+10 0.285047E+10 0.00 0.00
April 0.559601E+10 0.279507E+10 0.576032E+10 0.252320E+10 0.323712E+10 0.00 0.00
May 0.797069E+10 0.190283E+10 0.721893E+10 0.288512E+10 0.433381E+10 0.00 0.00
June 0.804310E+10 0.104133E+10 0.647459E+10 0.234376E+10 0.413084E+10 0.00 0.00
July 0.905386E+10 0.618403E+09 0.671970E+10 0.242497E+10 0.429473E+10 0.00 0.00
August 0.101498E+11 0.822347E+09 0.756655E+10 0.341176E+10 0.415479E+10 0.00 0.00
September 0.650374E+10 0.145849E+10 0.546114E+10 0.245020E+10 0.301094E+10 0.00 0.00
October 0.547574E+10 0.265605E+10 0.511596E+10 0.231873E+10 0.279723E+10 0.00 0.00
November 0.242144E+10 0.379028E+10 0.306176E+10 0.117575E+10 0.188601E+10 0.00 0.00
December 0.163720E+10 0.512550E+10 0.246480E+10 0.115732E+10 0.130748E+10 0.00 0.00
               
Annual Sum or Average 0.648913E+11 0.350580E+11 0.608227E+11 0.254438E+11 0.353790E+11 0.00 0.00
Minimum of Months 0.149927E+10 0.618403E+09 0.246480E+10 0.100517E+10 0.130748E+10 0.00 0.00
Maximum of Months 0.101498E+11 0.567175E+10 0.756655E+10 0.341176E+10 0.433381E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.874521E+10 0.826486E+10 0.931372E+10 0.609868E+10 0.321503E+10 0.00 0.00
February 0.105863E+11 0.760574E+10 0.110957E+11 0.734442E+10 0.375123E+10 0.00 0.00
March 0.111887E+11 0.621898E+10 0.110829E+11 0.615121E+10 0.493170E+10 0.00 0.00
April 0.869789E+10 0.450925E+10 0.832253E+10 0.329098E+10 0.503155E+10 0.00 0.00
May 0.834232E+10 0.302362E+10 0.753658E+10 0.157201E+10 0.596457E+10 0.00 0.00
June 0.872996E+10 0.164833E+10 0.684470E+10 0.104628E+10 0.579842E+10 0.00 0.00
July 0.104984E+11 0.957008E+09 0.741377E+10 0.128777E+10 0.612600E+10 0.00 0.00
August 0.141662E+11 0.132982E+10 0.990027E+10 0.367217E+10 0.622810E+10 0.00 0.00
September 0.132081E+11 0.239679E+10 0.103955E+11 0.537697E+10 0.501851E+10 0.00 0.00
October 0.174501E+11 0.434185E+10 0.147156E+11 0.922775E+10 0.548787E+10 0.00 0.00
November 0.100963E+11 0.583647E+10 0.987486E+10 0.593033E+10 0.394454E+10 0.00 0.00
December 0.992242E+10 0.753957E+10 0.100947E+11 0.716654E+10 0.292813E+10 0.00 0.00
               
Annual Sum or Average 0.131632E+12 0.536723E+11 0.116591E+12 0.581651E+11 0.584256E+11 0.00 0.00
Minimum of Months 0.834232E+10 0.957008E+09 0.684470E+10 0.104628E+10 0.292813E+10 0.00 0.00
Maximum of Months 0.174501E+11 0.826486E+10 0.147156E+11 0.922775E+10 0.622810E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.145744E+10 0.593915E+10 0.247514E+10 0.101382E+10 0.146131E+10 0.00 0.00
February 0.215124E+10 0.553626E+10 0.329673E+10 0.144793E+10 0.184879E+10 0.00 0.00
March 0.462588E+10 0.419121E+10 0.538959E+10 0.248823E+10 0.290137E+10 0.00 0.00
April 0.556738E+10 0.302775E+10 0.570056E+10 0.243912E+10 0.326143E+10 0.00 0.00
May 0.760262E+10 0.206078E+10 0.686192E+10 0.260589E+10 0.425603E+10 0.00 0.00
June 0.906246E+10 0.118594E+10 0.726790E+10 0.293135E+10 0.433655E+10 0.00 0.00
July 0.942356E+10 0.732658E+09 0.703367E+10 0.264867E+10 0.438501E+10 0.00 0.00
August 0.104664E+11 0.970485E+09 0.778116E+10 0.360216E+10 0.417899E+10 0.00 0.00
September 0.644364E+10 0.160196E+10 0.534581E+10 0.233611E+10 0.300970E+10 0.00 0.00
October 0.595196E+10 0.288609E+10 0.547664E+10 0.266315E+10 0.281348E+10 0.00 0.00
November 0.164679E+10 0.405136E+10 0.248885E+10 0.719294E+09 0.176955E+10 0.00 0.00
December 0.139008E+10 0.548341E+10 0.228757E+10 0.989839E+09 0.129773E+10 0.00 0.00
               
Annual Sum or Average 0.657894E+11 0.376671E+11 0.614055E+11 0.258856E+11 0.355200E+11 0.00 0.00
Minimum of Months 0.139008E+10 0.732658E+09 0.228757E+10 0.719294E+09 0.129773E+10 0.00 0.00
Maximum of Months 0.104664E+11 0.593915E+10 0.778116E+10 0.360216E+10 0.438501E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: GROUNDFLOOR_PLENUM

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: MIDFLOOR_PLENUM

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: TOPFLOOR_PLENUM

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: DATACENTER_MID_ZN_6

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AverageOutdoorConditionsMonthly

For: Environment

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] SITE OUTDOOR AIR WETBULB TEMPERATURE [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] SITE WIND SPEED [m/s] SITE SKY TEMPERATURE [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] SITE RAIN STATUS []
January 1.17 -0.7 -4.4 5.65 -10.4 36.91 88.07 0.05
February -0.2 -2.6 -7.5 5.07 -13.4 46.98 136.68 0.04
March 5.59 3.43 0.29 5.58 -4.1 68.24 153.73 0.03
April 10.94 8.00 4.75 4.99 0.53 82.64 161.98 0.05
May 16.05 12.31 9.14 4.42 7.77 109.28 173.60 0.03
June 21.71 18.08 15.84 4.92 13.23 112.36 186.51 0.01
July 25.05 21.76 20.26 4.06 17.39 114.46 172.96 0.02
August 24.79 19.84 17.14 4.19 14.42 95.56 226.16 0.00
September 19.96 15.96 13.24 3.91 10.59 73.65 166.08 0.03
October 14.02 11.03 7.95 4.86 2.64 61.34 179.75 0.00
November 7.31 4.98 2.14 5.60 -4.0 48.23 90.71 0.03
December 3.33 0.91 -2.8 5.64 -8.5 30.23 98.59 0.04
                 
Annual Sum or Average 12.55 9.49 6.43 4.91 2.28 73.48 153.05 0.03
Minimum of Months -0.2 -2.6 -7.5 3.91 -13.4 30.23 88.07 0.00
Maximum of Months 25.05 21.76 20.26 5.65 17.39 114.46 226.16 0.05



Table of Contents

Report: OutdoorConditionsMaximumDryBulbMonthly

For: Environment

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] SITE WIND SPEED {AT MAX/MIN} [m/s] SITE SKY TEMPERATURE {AT MAX/MIN} [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2]
January 12.20 24-JAN-12:20 11.81 11.50 1.00 8.15 93.67 0.00
February 10.00 20-FEB-11:00 4.36 -3.3 2.60 -3.9 151.50 540.00
March 22.20 27-MAR-15:00 16.34 12.80 6.70 11.65 136.50 590.00
April 26.70 07-APR-12:00 16.40 9.40 6.20 11.65 179.00 713.50
May 30.00 30-MAY-12:00 18.00 10.60 5.20 17.39 233.50 730.00
June 36.70 19-JUN-11:00 24.28 19.40 5.20 24.83 185.00 771.50
July 33.90 07-JUL-11:00 23.31 18.90 3.60 23.82 331.00 570.00
August 33.90 24-AUG-14:00 20.23 12.80 8.80 21.61 240.00 432.00
September 31.10 01-SEP-13:00 17.34 8.30 4.60 18.46 182.00 662.00
October 25.00 04-OCT-12:00 18.54 15.00 5.20 11.27 171.50 695.00
November 17.80 04-NOV-12:20 12.57 8.50 3.60 6.15 182.50 595.67
December 12.20 17-DEC-12:20 4.65 -6.1 4.27 -4.7 53.17 801.67
                 
Annual Sum or Average                
Minimum of Months 10.00   4.36 -6.1 1.00 -4.7 53.17 0.00
Maximum of Months 36.70   24.28 19.40 8.80 24.83 331.00 801.67



Table of Contents

Report: OutdoorConditionsMinimumDryBulbMonthly

For: Environment

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] SITE WIND SPEED {AT MAX/MIN} [m/s] SITE SKY TEMPERATURE {AT MAX/MIN} [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2]
January -12.2 02-JAN-04:00 -13.6 -19.4 2.60 -30.7 0.00 0.00
February -13.9 06-FEB-02:00 -15.3 -22.8 7.20 -34.1 0.00 0.00
March -5.0 23-MAR-03:00 -7.6 -14.4 1.50 -23.9 0.00 0.00
April 2.20 01-APR-03:00 0.57 -1.7 3.10 -6.6 0.00 0.00
May 6.10 01-MAY-04:00 4.33 2.20 3.60 -9.7 25.50 0.00
June 13.30 03-JUN-02:00 9.35 5.60 4.60 -2.1 0.00 0.00
July 18.30 02-JUL-02:00 17.54 17.20 0.00 5.33 0.00 0.00
August 15.00 08-AUG-04:00 12.47 10.60 3.10 3.06 0.00 0.00
September 10.00 24-SEP-05:00 8.56 7.20 2.60 -3.4 18.50 158.50
October 2.20 09-OCT-03:00 1.71 1.10 0.00 -13.7 0.00 0.00
November -4.4 24-NOV-05:00 -6.2 -10.0 1.50 -19.7 0.00 0.00
December -8.3 31-DEC-23:00 -10.6 -18.9 9.30 -26.2 0.00 0.00
                 
Annual Sum or Average                
Minimum of Months -13.9   -15.3 -22.8 0.00 -34.1 0.00 0.00
Maximum of Months 18.30   17.54 17.20 9.30 5.33 25.50 158.50



Table of Contents

Report: OutdoorConditionsMaximumWetBulbMonthly

For: Environment

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

SITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] SITE WIND SPEED {AT MAX/MIN} [m/s] SITE SKY TEMPERATURE {AT MAX/MIN} [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2]
January 11.93 24-JAN-11:00 12.20 11.70 1.50 8.15 103.00 0.00
February 6.67 28-FEB-09:00 7.20 6.10 4.10 2.01 101.50 0.00
March 16.99 27-MAR-12:00 20.60 15.00 3.60 10.50 295.50 565.50
April 17.70 09-APR-10:00 21.70 15.60 4.10 14.84 244.50 281.50
May 20.43 31-MAY-12:00 26.10 17.80 4.10 17.03 214.00 772.00
June 24.96 15-JUN-11:00 31.10 22.80 5.20 22.47 380.00 460.00
July 26.10 08-JUL-11:00 32.20 23.90 5.20 22.47 354.00 501.50
August 25.84 03-AUG-13:00 30.00 24.40 6.20 20.57 298.00 500.00
September 23.57 07-SEP-13:00 27.20 22.20 6.20 15.02 148.00 730.50
October 19.76 25-OCT-10:00 25.00 17.20 7.70 14.84 189.00 308.50
November 16.10 10-NOV-07:00 16.10 16.10 8.20 12.98 71.50 0.00
December 10.26 25-DEC-08:00 10.60 10.00 3.60 6.15 43.00 0.00
                 
Annual Sum or Average                
Minimum of Months 6.67   7.20 6.10 1.50 2.01 43.00 0.00
Maximum of Months 26.10   32.20 24.40 8.20 22.47 380.00 772.00



Table of Contents

Report: OutdoorConditionsMaximumDewPointMonthly

For: Environment

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

SITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] SITE WIND SPEED {AT MAX/MIN} [m/s] SITE SKY TEMPERATURE {AT MAX/MIN} [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2]
January 11.70 18-JAN-15:00 12.20 11.93 14.90 8.15 22.00 2.00
February 6.10 28-FEB-10:20 7.03 6.58 3.43 1.87 109.83 0.00
March 15.00 27-MAR-12:20 18.00 16.18 3.93 10.11 271.83 611.17
April 15.60 09-APR-10:00 21.70 17.70 4.10 14.84 244.50 281.50
May 18.00 18-MAY-09:00 18.00 18.00 4.60 15.39 265.50 12.00
June 22.80 15-JUN-11:00 31.10 24.96 5.20 22.47 380.00 460.00
July 24.40 09-JUL-07:00 27.20 25.17 2.10 15.39 195.00 504.00
August 25.00 03-AUG-19:00 26.10 25.32 5.70 19.35 0.00 0.00
September 22.20 07-SEP-13:00 27.20 23.57 6.20 15.02 148.00 730.50
October 18.30 05-OCT-18:00 19.40 18.62 7.70 6.55 0.00 0.00
November 16.10 10-NOV-07:00 16.10 16.10 8.20 12.98 71.50 0.00
December 10.00 25-DEC-08:00 10.60 10.26 3.60 6.15 43.00 0.00
                 
Annual Sum or Average                
Minimum of Months 6.10   7.03 6.58 2.10 1.87 0.00 0.00
Maximum of Months 25.00   31.10 25.32 14.90 22.47 380.00 730.50



Table of Contents

Report: OutdoorGroundConditionsMonthly

For: Environment

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

SITE GROUND TEMPERATURE [C] SITE SURFACE GROUND TEMPERATURE [C] SITE DEEP GROUND TEMPERATURE [C] SITE MAINS WATER TEMPERATURE [C] SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] SITE SNOW ON GROUND STATUS []
January 18.00 13.00 16.00 10.03 13.58 0.00
February 18.00 13.00 16.00 9.54 21.42 0.00
March 18.00 13.00 16.00 10.65 30.29 0.00
April 18.00 13.00 16.00 13.15 37.02 0.00
May 18.00 13.00 16.00 16.36 45.86 0.00
June 18.00 13.00 16.00 19.42 49.74 0.00
July 18.00 13.00 16.00 21.50 48.12 0.00
August 18.00 13.00 16.00 22.05 49.54 0.00
September 18.00 13.00 16.00 20.89 34.71 0.00
October 18.00 13.00 16.00 18.36 29.93 0.00
November 18.00 13.00 16.00 15.14 17.00 0.00
December 18.00 13.00 16.00 12.10 12.41 0.00
             
Annual Sum or Average 18.00 13.00 16.00 15.80 32.53 0.00
Minimum of Months 18.00 13.00 16.00 9.54 12.41 0.00
Maximum of Months 18.00 13.00 16.00 22.05 49.74 0.00



Table of Contents

Report: WaterHeaterReportMonthly

For: SWHSYS1 WATER HEATER

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] WATER HEATER BURNER HEATING ENERGY [] WATER HEATER GAS CONSUMPTION [] WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] WATER HEATER LOSS DEMAND ENERGY [] WATER HEATER HEAT LOSS ENERGY [J] WATER HEATER TANK TEMPERATURE [C] WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] WATER HEATER SOURCE ENERGY []
January 0.399857E+11 -0.389532E+11 0.00 0.00 744.00 0.00 -0.103253E+10 58.98 0.00 0.00
February 0.366808E+11 -0.357524E+11 0.00 0.00 672.00 0.00 -928483805.0 58.97 0.00 0.00
March 0.421312E+11 -0.411034E+11 0.00 0.00 744.00 0.00 -0.102774E+10 58.98 0.00 0.00
April 0.363438E+11 -0.353535E+11 0.00 0.00 720.00 0.00 -990243303.9 58.98 0.00 0.00
May 0.361669E+11 -0.351435E+11 0.00 0.00 744.00 0.00 -0.102340E+10 58.98 0.00 0.00
June 0.332947E+11 -0.323051E+11 0.00 0.00 720.00 0.00 -989622210.2 58.97 0.00 0.00
July 0.301081E+11 -0.290903E+11 0.00 0.00 744.00 0.00 -0.101781E+10 58.98 0.00 0.00
August 0.324325E+11 -0.314107E+11 0.00 0.00 744.00 0.00 -0.102172E+10 58.98 0.00 0.00
September 0.303804E+11 -0.293942E+11 0.00 0.00 720.00 0.00 -986202277.1 58.97 0.00 0.00
October 0.333536E+11 -0.323360E+11 0.00 0.00 744.00 0.00 -0.101767E+10 58.98 0.00 0.00
November 0.352065E+11 -0.342194E+11 0.00 0.00 720.00 0.00 -987101806.4 58.98 0.00 0.00
December 0.374224E+11 -0.364002E+11 0.00 0.00 744.00 0.00 -0.102221E+10 58.98 0.00 0.00
                     
Annual Sum or Average 0.423507E+12 -0.411462E+12 0.00 0.00 8760.00 0.00 -0.120447E+11 58.98 0.00 0.00
Minimum of Months 0.301081E+11 -0.411034E+11 0.00 0.00 672.00 0.00 -0.103253E+10 58.97 0.00 0.00
Maximum of Months 0.421312E+11 -0.290903E+11 0.00 0.00 744.00 0.00 -928483805.0 58.98 0.00 0.00



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_BOT_ZN_1_DAYLCTRL

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 199.50 0.51 0.48 01-JAN-07:49 7259.88 37.23 196.83 248.67 3733.60 34.03 202.17 203.67
February 216.00 0.50 0.48 01-FEB-07:49 10325.15 38.10 213.67 262.00 2346.39 28.29 215.67 240.50
March 275.00 0.51 0.48 01-MAR-07:10 3954.73 25.30 175.17 321.50 1751.81 22.95 237.17 292.67
April 261.17 0.51 0.48 01-APR-14:39 2355.62 20.96 123.50 346.67 1369.32 22.37 247.33 307.33
May 372.00 0.51 0.48 01-MAY-05:00 2065.87 20.82 184.17 396.17 1145.74 22.20 297.17 358.33
June 351.83 0.51 0.48 01-JUN-05:49 1975.78 20.80 168.00 389.67 1112.22 22.23 294.17 349.33
July 365.17 0.50 0.48 01-JUL-05:49 2174.40 21.07 199.17 398.67 1196.94 22.50 309.00 354.33
August 389.17 0.51 0.48 01-AUG-06:10 2402.08 21.04 208.33 375.00 1370.87 22.44 314.67 347.50
September 285.33 0.51 0.48 01-SEP-06:19 4269.94 23.18 176.17 329.33 1619.65 22.70 251.00 295.67
October 305.50 0.50 0.48 01-OCT-14:39 11301.74 36.76 285.17 309.67 2243.39 24.63 276.00 293.00
November 240.83 0.50 0.48 01-NOV-06:00 7204.97 37.01 236.83 260.33 2486.40 29.80 239.17 240.00
December 211.17 0.51 0.48 01-DEC-07:40 6789.77 38.25 207.83 249.00 5980.53 39.43 218.50 221.50
                         
Annual Sum or Average 3472.67 0.51     4726.58 27.03 2374.83 3886.67 1983.59 25.22 3102.00 3503.83
Minimum of Months 199.50 0.50 0.48   1975.78 20.80 123.50 248.67 1112.22 22.20 202.17 203.67
Maximum of Months 389.17 0.51 0.48   11301.74 38.25 285.17 398.67 5980.53 39.43 314.67 358.33



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_BOT_ZN_2_DAYLCTRL

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 199.50 0.53 0.48 01-JAN-07:49 2307.85 25.28 97.17 233.00 1259.43 25.26 130.83 170.67
February 216.00 0.51 0.48 01-FEB-07:40 3181.34 26.23 103.00 253.50 1819.25 26.22 155.50 217.83
March 275.00 0.52 0.48 01-MAR-06:49 3308.26 23.99 103.33 317.50 1833.22 24.44 180.17 278.83
April 261.17 0.50 0.48 01-APR-06:19 4369.67 26.11 101.17 348.17 1745.89 24.94 198.83 313.50
May 372.00 0.51 0.48 01-MAY-05:40 3600.73 23.91 110.00 401.00 1936.70 24.49 255.33 365.33
June 351.83 0.50 0.48 01-JUN-04:00 3236.83 23.93 105.67 395.33 1790.00 24.73 256.50 362.00
July 365.17 0.50 0.48 01-JUL-04:49 3335.03 24.32 125.67 404.67 1795.50 24.95 278.50 367.67
August 389.17 0.51 0.48 01-AUG-05:40 4427.23 25.75 152.67 378.67 1835.08 24.87 268.17 353.67
September 285.33 0.51 0.48 01-SEP-05:49 3865.28 25.60 112.50 328.33 1673.14 24.74 206.17 295.33
October 305.50 0.51 0.48 01-OCT-14:39 3425.37 25.72 152.33 300.17 1797.86 25.84 223.67 276.00
November 240.83 0.52 0.48 01-NOV-06:49 2336.52 25.33 127.00 250.83 1195.35 25.11 165.33 212.00
December 211.17 0.54 0.48 01-DEC-07:30 2149.50 25.63 100.50 231.33 1232.69 25.58 120.50 174.50
                         
Annual Sum or Average 3472.67 0.51     3393.24 25.06 1391.00 3842.50 1698.75 25.04 2439.50 3387.33
Minimum of Months 199.50 0.50 0.48   2149.50 23.91 97.17 231.33 1195.35 24.44 120.50 170.67
Maximum of Months 389.17 0.54 0.48   4427.23 26.23 152.67 404.67 1936.70 26.22 278.50 367.67



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_BOT_ZN_3_DAYLCTRL

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 199.50 0.55 0.48 01-JAN-08:50 739.08 17.74 0.00 219.17 444.09 19.36 14.83 138.50
February 216.00 0.53 0.48 01-FEB-08:50 807.74 18.63 0.00 241.33 513.97 20.33 40.00 183.33
March 275.00 0.52 0.48 01-MAR-07:30 1064.65 19.32 1.33 313.50 654.13 20.78 136.00 259.50
April 261.17 0.50 0.48 01-APR-14:39 1199.27 20.23 28.83 350.50 739.99 21.64 162.67 307.67
May 372.00 0.50 0.48 01-MAY-05:49 1531.49 21.01 128.83 407.17 871.42 22.28 296.83 371.67
June 351.83 0.49 0.48 01-JUN-05:10 1724.83 23.99 190.17 406.17 951.03 23.73 329.17 375.17
July 365.17 0.49 0.48 01-JUL-05:10 1702.45 22.78 184.50 414.17 941.76 22.61 314.50 375.00
August 389.17 0.51 0.48 01-AUG-05:00 1408.17 20.60 105.83 381.67 839.48 22.00 302.67 356.83
September 285.33 0.51 0.48 01-SEP-06:19 1100.54 19.84 5.00 326.67 684.94 21.33 150.00 282.50
October 305.50 0.51 0.48 01-OCT-14:39 1001.50 19.55 0.00 295.00 634.28 21.18 185.33 257.17
November 240.83 0.53 0.48 01-NOV-07:30 822.23 18.42 0.00 242.50 484.67 19.93 46.67 176.67
December 211.17 0.57 0.48 01-DEC-08:00 598.73 16.87 0.00 210.83 370.09 18.61 2.17 113.67
                         
Annual Sum or Average 3472.67 0.51     1214.80 20.27 644.50 3808.67 715.94 21.41 1980.83 3197.67
Minimum of Months 199.50 0.49 0.48   598.73 16.87 0.00 210.83 370.09 18.61 2.17 113.67
Maximum of Months 389.17 0.57 0.48   1724.83 23.99 190.17 414.17 951.03 23.73 329.17 375.17



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_BOT_ZN_4_DAYLCTRL

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 199.50 0.52 0.48 01-JAN-08:50 2235.08 25.49 94.17 237.00 1246.75 25.48 130.17 174.83
February 216.00 0.51 0.48 01-FEB-08:50 2527.05 25.17 100.83 252.00 1328.81 25.19 144.83 217.67
March 275.00 0.51 0.48 01-MAR-07:30 3596.61 26.10 124.17 323.83 2011.25 26.33 204.33 290.00
April 261.17 0.51 0.48 01-APR-14:39 4120.05 24.66 88.83 348.50 1687.38 23.75 186.83 311.50
May 372.00 0.50 0.48 01-MAY-06:19 3866.05 22.34 79.00 401.00 1706.21 21.67 247.00 369.50
June 351.83 0.50 0.48 01-JUN-05:00 3749.36 19.74 34.00 397.83 2015.61 21.87 234.33 363.67
July 365.17 0.50 0.48 01-JUL-05:00 3533.74 21.86 79.00 404.00 1879.50 21.95 259.50 365.83
August 389.17 0.51 0.48 01-AUG-06:19 4509.11 23.25 112.83 378.33 1953.32 22.02 253.67 354.83
September 285.33 0.51 0.48 01-SEP-06:49 3660.02 25.22 117.50 329.50 1901.29 25.31 202.33 295.33
October 305.50 0.50 0.48 01-OCT-14:39 3940.33 27.51 170.83 307.17 1666.83 26.13 244.33 286.00
November 240.83 0.51 0.48 01-NOV-07:30 1936.30 25.06 120.17 251.33 1028.13 25.14 169.50 217.67
December 211.17 0.54 0.48 01-DEC-08:50 1814.36 25.12 97.67 230.67 996.40 24.92 125.17 178.67
                         
Annual Sum or Average 3472.67 0.51     3443.15 24.01 1219.00 3861.17 1678.72 23.85 2402.00 3425.50
Minimum of Months 199.50 0.50 0.48   1814.36 19.74 34.00 230.67 996.40 21.67 125.17 174.83
Maximum of Months 389.17 0.54 0.48   4509.11 27.51 170.83 404.00 2015.61 26.33 259.50 369.50



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_MID_ZN_1_DAYLCTRL

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 199.50 0.51 0.48 01-JAN-07:49 7313.99 36.81 196.50 248.83 3865.55 32.11 144.33 209.17
February 216.00 0.49 0.48 01-FEB-07:49 10396.75 37.61 210.00 262.17 2494.23 24.38 80.50 242.17
March 275.00 0.51 0.48 01-MAR-07:10 4070.19 20.51 91.33 324.67 1880.02 18.57 30.33 296.50
April 261.17 0.51 0.48 01-APR-14:39 2407.82 14.79 0.00 347.17 1468.24 18.33 2.83 311.67
May 372.00 0.51 0.48 01-MAY-05:00 2097.62 14.87 0.00 396.17 1221.80 18.26 0.00 362.50
June 351.83 0.51 0.48 01-JUN-05:49 2006.37 14.86 0.00 389.67 1185.67 18.32 0.00 354.00
July 365.17 0.50 0.48 01-JUL-05:49 2204.38 15.03 0.00 399.17 1275.01 18.48 0.00 358.00
August 389.17 0.51 0.48 01-AUG-05:00 2448.23 15.08 0.00 375.00 1466.54 18.54 9.17 350.50
September 285.33 0.51 0.48 01-SEP-06:19 4337.01 17.45 29.50 330.00 1738.96 18.39 12.17 299.33
October 305.50 0.49 0.48 01-OCT-14:39 11386.07 35.99 283.50 310.50 2493.94 20.47 34.50 294.67
November 240.83 0.50 0.48 01-NOV-06:49 7243.01 36.59 236.67 260.33 3095.16 29.32 144.50 244.00
December 211.17 0.51 0.48 01-DEC-07:40 6855.36 37.85 207.83 249.33 6110.83 39.12 208.00 224.17
                         
Annual Sum or Average 3472.67 0.50     4781.59 23.00 1255.33 3893.00 2134.46 21.77 666.33 3546.67
Minimum of Months 199.50 0.49 0.48   2006.37 14.79 0.00 248.83 1185.67 18.26 0.00 209.17
Maximum of Months 389.17 0.51 0.48   11386.07 37.85 283.50 399.17 6110.83 39.12 208.00 362.50



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_MID_ZN_2_DAYLCTRL

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 199.50 0.53 0.48 01-JAN-07:49 2343.45 22.99 72.83 234.00 1309.77 23.53 75.00 176.33
February 216.00 0.51 0.48 01-FEB-07:40 3228.63 23.88 81.00 254.50 1883.30 24.44 67.33 222.00
March 275.00 0.52 0.48 01-MAR-06:49 3376.86 21.10 71.50 318.17 1911.47 22.22 53.83 286.67
April 261.17 0.50 0.48 01-APR-06:10 4436.68 23.42 92.67 349.00 1834.04 22.47 50.17 317.17
May 372.00 0.51 0.48 01-MAY-05:40 3645.81 20.81 99.50 401.17 2022.20 22.04 72.83 369.00
June 351.83 0.50 0.48 01-JUN-04:00 3286.03 20.74 88.67 396.33 1872.58 22.32 69.00 366.00
July 365.17 0.50 0.48 01-JUL-04:49 3376.26 20.67 89.83 404.50 1880.69 22.52 70.17 370.50
August 389.17 0.51 0.48 01-AUG-05:30 4481.31 22.87 128.17 378.83 1924.17 22.42 70.67 356.17
September 285.33 0.51 0.48 01-SEP-05:49 3909.61 21.86 82.67 328.00 1756.71 22.33 49.50 300.00
October 305.50 0.51 0.48 01-OCT-14:39 3476.69 22.84 91.17 300.83 1875.34 23.86 90.00 278.83
November 240.83 0.51 0.48 01-NOV-06:49 2357.57 21.83 73.33 251.50 1251.01 23.18 86.50 215.00
December 211.17 0.53 0.48 01-DEC-07:30 2182.07 23.43 83.17 232.17 1277.43 23.99 83.67 180.17
                         
Annual Sum or Average 3472.67 0.51     3440.51 22.05 1054.50 3849.00 1775.18 22.82 838.67 3437.83
Minimum of Months 199.50 0.50 0.48   2182.07 20.67 71.50 232.17 1251.01 22.04 49.50 176.33
Maximum of Months 389.17 0.53 0.48   4481.31 23.88 128.17 404.50 2022.20 24.44 90.00 370.50



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_MID_ZN_3_DAYLCTRL

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 199.50 0.54 0.48 01-JAN-08:39 748.15 12.12 0.00 219.83 471.90 15.64 0.00 145.50
February 216.00 0.53 0.48 01-FEB-08:39 820.44 13.15 0.00 242.00 547.19 16.83 0.00 192.00
March 275.00 0.52 0.48 01-MAR-07:30 1083.01 14.03 0.00 313.50 696.79 17.47 0.00 270.17
April 261.17 0.50 0.48 01-APR-14:39 1223.12 14.95 0.00 350.50 789.20 18.45 1.83 313.00
May 372.00 0.50 0.48 01-MAY-05:49 1557.69 15.40 3.17 407.83 928.79 18.82 25.83 375.50
June 351.83 0.49 0.48 01-JUN-05:10 1755.42 19.47 73.83 406.33 1022.85 21.47 62.83 380.33
July 365.17 0.49 0.48 01-JUL-04:00 1731.36 17.77 41.67 414.17 1012.11 20.97 55.33 383.33
August 389.17 0.50 0.48 01-AUG-05:49 1434.68 15.33 0.00 381.83 894.92 18.79 8.17 360.00
September 285.33 0.51 0.48 01-SEP-06:19 1121.21 14.61 0.00 327.17 730.07 18.11 0.00 288.00
October 305.50 0.51 0.48 01-OCT-14:39 1017.05 14.34 0.00 295.50 675.26 17.89 0.00 263.67
November 240.83 0.53 0.48 01-NOV-07:30 832.74 12.67 0.00 242.50 514.97 16.17 0.00 185.50
December 211.17 0.57 0.48 01-DEC-08:50 605.90 11.07 0.00 211.00 393.31 14.76 0.00 126.50
                         
Annual Sum or Average 3472.67 0.51     1235.51 14.97 118.67 3812.17 764.54 18.30 154.00 3283.50
Minimum of Months 199.50 0.49 0.48   605.90 11.07 0.00 211.00 393.31 14.76 0.00 126.50
Maximum of Months 389.17 0.57 0.48   1755.42 19.47 73.83 414.17 1022.85 21.47 62.83 383.33



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_MID_ZN_4_DAYLCTRL

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 199.50 0.52 0.48 01-JAN-08:39 2269.38 23.25 73.50 238.00 1295.40 23.81 71.67 178.50
February 216.00 0.51 0.48 01-FEB-08:39 2538.81 21.29 57.00 252.33 1392.53 23.21 54.33 222.17
March 275.00 0.51 0.48 01-MAR-07:30 3667.64 23.48 96.00 324.17 2092.64 24.33 78.00 293.83
April 261.17 0.50 0.48 01-APR-14:39 4185.30 21.67 76.83 348.83 1774.84 21.09 37.17 314.50
May 372.00 0.50 0.48 01-MAY-06:19 3911.09 18.79 69.33 401.83 1789.05 18.40 0.00 373.50
June 351.83 0.50 0.48 01-JUN-05:00 3790.33 15.16 1.83 398.83 2109.00 18.54 0.00 368.50
July 365.17 0.50 0.48 01-JUL-05:00 3575.48 18.02 49.00 405.00 1967.93 18.69 0.00 369.00
August 389.17 0.51 0.48 01-AUG-06:10 4570.05 19.92 86.33 378.50 2044.36 18.86 8.50 357.00
September 285.33 0.50 0.48 01-SEP-06:40 3713.58 22.14 85.50 329.67 1983.35 23.05 63.17 299.50
October 305.50 0.50 0.48 01-OCT-14:39 3982.26 24.28 111.83 307.17 1747.11 24.08 87.67 288.50
November 240.83 0.51 0.48 01-NOV-07:30 1965.83 22.42 79.83 251.83 1075.16 23.32 81.67 222.33
December 211.17 0.54 0.48 01-DEC-08:50 1807.90 21.34 68.50 231.33 1039.58 23.28 72.50 185.67
                         
Annual Sum or Average 3472.67 0.51     3486.32 20.63 855.50 3867.50 1756.03 21.30 554.67 3473.00
Minimum of Months 199.50 0.50 0.48   1807.90 15.16 1.83 231.33 1039.58 18.40 0.00 178.50
Maximum of Months 389.17 0.54 0.48   4570.05 24.28 111.83 405.00 2109.00 24.33 87.67 373.50



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_TOP_ZN_1_DAYLCTRL

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 199.50 0.51 0.48 01-JAN-07:49 7315.84 36.80 196.50 249.00 3868.34 32.10 144.33 209.33
February 216.00 0.49 0.48 01-FEB-07:49 10399.00 37.60 210.00 262.17 2497.06 24.37 80.50 242.33
March 275.00 0.51 0.48 01-MAR-07:10 4073.84 20.49 91.33 324.67 1882.65 18.55 30.00 296.67
April 261.17 0.51 0.48 01-APR-14:39 2410.98 14.76 0.00 347.17 1470.26 18.31 2.83 311.67
May 372.00 0.51 0.48 01-MAY-05:00 2100.64 14.84 0.00 396.17 1223.67 18.24 0.00 362.67
June 351.83 0.51 0.48 01-JUN-05:49 2009.12 14.83 0.00 390.00 1187.41 18.31 0.00 354.17
July 365.17 0.50 0.48 01-JUL-05:49 2207.60 15.00 0.00 399.17 1276.98 18.47 0.00 358.17
August 389.17 0.51 0.48 01-AUG-05:00 2451.53 15.06 0.00 375.00 1468.64 18.52 9.00 350.50
September 285.33 0.51 0.48 01-SEP-06:19 4340.60 17.43 29.50 330.00 1741.36 18.37 11.50 299.67
October 305.50 0.49 0.48 01-OCT-14:39 11389.52 35.98 283.50 310.50 2497.26 20.46 34.00 294.67
November 240.83 0.50 0.48 01-NOV-06:49 7245.25 36.58 236.67 260.50 3098.24 29.31 144.50 244.17
December 211.17 0.51 0.48 01-DEC-07:40 6856.25 37.84 207.83 249.50 6113.10 39.11 208.00 224.33
                         
Annual Sum or Average 3472.67 0.50     4784.48 22.98 1255.33 3893.83 2136.82 21.75 664.67 3548.33
Minimum of Months 199.50 0.49 0.48   2009.12 14.76 0.00 249.00 1187.41 18.24 0.00 209.33
Maximum of Months 389.17 0.51 0.48   11389.52 37.84 283.50 399.17 6113.10 39.11 208.00 362.67



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_TOP_ZN_2_DAYLCTRL

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 199.50 0.53 0.48 01-JAN-07:49 2344.55 22.97 72.83 234.00 1311.03 23.52 74.50 176.67
February 216.00 0.51 0.48 01-FEB-07:40 3229.68 23.86 81.00 254.50 1884.67 24.42 66.83 222.00
March 275.00 0.52 0.48 01-MAR-06:49 3378.36 21.07 71.50 318.17 1913.24 22.21 53.50 286.83
April 261.17 0.50 0.48 01-APR-06:10 4438.57 23.39 92.67 349.00 1835.84 22.45 50.17 317.17
May 372.00 0.51 0.48 01-MAY-05:40 3648.36 20.78 99.50 401.17 2024.31 22.03 72.83 369.17
June 351.83 0.50 0.48 01-JUN-04:00 3288.40 20.72 88.67 396.50 1874.51 22.30 69.00 366.00
July 365.17 0.50 0.48 01-JUL-04:49 3379.05 20.65 89.83 404.50 1882.85 22.50 70.17 370.83
August 389.17 0.51 0.48 01-AUG-05:30 4483.66 22.85 128.17 379.00 1926.23 22.40 70.67 356.33
September 285.33 0.51 0.48 01-SEP-05:49 3911.37 21.83 82.67 328.00 1758.45 22.32 49.50 300.33
October 305.50 0.51 0.48 01-OCT-14:39 3478.07 22.82 91.17 300.83 1877.11 23.84 88.33 278.83
November 240.83 0.51 0.48 01-NOV-06:49 2358.99 21.81 73.33 251.50 1252.50 23.17 85.33 215.33
December 211.17 0.53 0.48 01-DEC-07:30 2182.81 23.41 83.17 232.17 1278.40 23.98 83.67 180.33
                         
Annual Sum or Average 3472.67 0.51     3442.38 22.02 1054.50 3849.33 1776.96 22.81 834.50 3439.83
Minimum of Months 199.50 0.50 0.48   2182.81 20.65 71.50 232.17 1252.50 22.03 49.50 176.67
Maximum of Months 389.17 0.53 0.48   4483.66 23.86 128.17 404.50 2024.31 24.42 88.33 370.83



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_TOP_ZN_3_DAYLCTRL

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 199.50 0.54 0.48 01-JAN-08:39 748.78 12.09 0.00 219.83 472.52 15.63 0.00 145.50
February 216.00 0.53 0.48 01-FEB-08:39 820.93 13.12 0.00 242.17 547.81 16.81 0.00 192.17
March 275.00 0.52 0.48 01-MAR-07:30 1083.91 14.00 0.00 313.50 697.65 17.45 0.00 270.33
April 261.17 0.50 0.48 01-APR-14:39 1224.11 14.91 0.00 350.50 790.15 18.44 1.67 313.17
May 372.00 0.50 0.48 01-MAY-05:49 1559.35 15.37 3.17 407.83 930.10 18.80 25.33 375.83
June 351.83 0.49 0.48 01-JUN-05:10 1757.14 19.45 73.83 406.33 1024.23 21.46 62.33 380.33
July 365.17 0.49 0.48 01-JUL-04:00 1733.16 17.74 41.67 414.17 1013.52 20.96 54.50 383.50
August 389.17 0.50 0.48 01-AUG-05:49 1435.91 15.30 0.00 381.83 896.04 18.77 8.17 360.17
September 285.33 0.51 0.48 01-SEP-06:19 1122.08 14.58 0.00 327.17 730.94 18.10 0.00 288.17
October 305.50 0.51 0.48 01-OCT-14:39 1017.66 14.31 0.00 295.50 676.02 17.87 0.00 264.00
November 240.83 0.53 0.48 01-NOV-07:30 833.54 12.64 0.00 242.67 515.69 16.16 0.00 185.83
December 211.17 0.57 0.48 01-DEC-08:50 606.31 11.03 0.00 211.00 393.79 14.74 0.00 126.83
                         
Annual Sum or Average 3472.67 0.51     1236.60 14.94 118.67 3812.50 765.53 18.28 152.00 3285.83
Minimum of Months 199.50 0.49 0.48   606.31 11.03 0.00 211.00 393.79 14.74 0.00 126.83
Maximum of Months 389.17 0.57 0.48   1757.14 19.45 73.83 414.17 1024.23 21.46 62.33 383.50



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_TOP_ZN_4_DAYLCTRL

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 199.50 0.52 0.48 01-JAN-08:39 2270.42 23.22 73.50 238.00 1296.60 23.80 71.50 178.50
February 216.00 0.51 0.48 01-FEB-08:39 2539.87 21.26 57.00 252.50 1393.85 23.20 54.00 222.33
March 275.00 0.51 0.48 01-MAR-07:30 3669.21 23.45 96.00 324.33 2094.45 24.32 77.50 294.17
April 261.17 0.50 0.48 01-APR-14:39 4153.81 21.64 76.83 348.67 1776.67 21.07 37.17 314.67
May 372.00 0.50 0.48 01-MAY-06:19 3913.63 18.76 69.33 402.00 1791.11 18.38 0.00 373.50
June 351.83 0.50 0.48 01-JUN-05:00 3793.10 15.12 1.83 398.83 2111.28 18.52 0.00 368.50
July 365.17 0.50 0.48 01-JUL-05:00 3578.37 17.99 49.00 405.33 1970.19 18.68 0.00 369.17
August 389.17 0.51 0.48 01-AUG-06:10 4572.41 19.89 86.33 378.50 2046.43 18.84 8.50 357.00
September 285.33 0.50 0.48 01-SEP-06:40 3715.39 22.11 85.50 329.67 1985.15 23.04 63.00 299.50
October 305.50 0.50 0.48 01-OCT-14:39 3983.79 24.25 111.83 307.17 1748.87 24.07 86.00 288.50
November 240.83 0.51 0.48 01-NOV-07:30 1967.24 22.40 79.83 252.00 1076.51 23.31 80.67 222.33
December 211.17 0.54 0.48 01-DEC-08:50 1808.67 21.32 68.50 231.33 1040.53 23.26 72.50 186.00
                         
Annual Sum or Average 3472.67 0.51     3485.75 20.60 855.50 3868.33 1757.84 21.28 550.83 3474.17
Minimum of Months 199.50 0.50 0.48   1808.67 15.12 1.83 231.33 1040.53 18.38 0.00 178.50
Maximum of Months 389.17 0.54 0.48   4572.41 24.25 111.83 405.33 2111.28 24.32 86.00 373.50



Table of Contents

Report: CoilReportMonthly

For: VAV_BOT WITH REHEAT HEATING COIL

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.173220E+10 56404.29 11-JAN-07:10 0.00 0.00 0.00 0.00 0.00
February 0.248463E+10 69024.56 13-FEB-07:10 0.00 0.00 0.00 0.00 0.00
March 0.136587E+10 54857.77 23-MAR-06:10 0.00 0.00 0.00 0.00 0.00
April 0.270784E+09 33062.03 01-APR-06:10 0.00 0.00 0.00 0.00 0.00
May 42558236.87 19069.41 30-MAY-13:40 0.00 0.00 0.00 0.00 0.00
June 88512668.17 17468.63 22-JUN-15:48 0.00 0.00 0.00 0.00 0.00
July 32794241.12 8046.06 11-JUL-16:15 0.00 0.00 0.00 0.00 0.00
August 0.143217E+09 18713.24 24-AUG-18:40 0.00 0.00 0.00 0.00 0.00
September 27708109.04 8195.47 01-SEP-17:10 0.00 0.00 0.00 0.00 0.00
October 96942328.96 26898.99 28-OCT-06:10 0.00 0.00 0.00 0.00 0.00
November 0.799768E+09 53944.51 24-NOV-07:10 0.00 0.00 0.00 0.00 0.00
December 0.180288E+10 53264.29 22-DEC-07:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.888788E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 27708109.04 8046.06   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.248463E+10 69024.56   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: CORE_BOTTOM VAV BOX REHEAT COIL

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:01 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:03 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.972979E+09 17285.56 30-JAN-06:01 0.00 0.00 0.00 0.00 0.00
February 0.720073E+09 17302.82 04-FEB-06:01 0.00 0.00 0.00 0.00 0.00
March 29277952.84 10314.13 17-MAR-05:01 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:03 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 35725387.16 17299.04 22-NOV-06:01 0.00 0.00 0.00 0.00 0.00
December 38957428.98 14188.91 02-DEC-06:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.179701E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.972979E+09 17302.82   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.101701E+10 15459.79 30-JAN-06:01 0.00 0.00 0.00 0.00 0.00
February 0.708394E+09 15479.45 03-FEB-06:01 0.00 0.00 0.00 0.00 0.00
March 0.136551E+09 15481.28 17-MAR-05:01 0.00 0.00 0.00 0.00 0.00
April 12449977.27 1561.07 22-APR-05:05 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:03 0.00 0.00 0.00 0.00 0.00
October 196221.40 106.66 28-OCT-06:30 0.00 0.00 0.00 0.00 0.00
November 0.109177E+09 15510.86 25-NOV-06:01 0.00 0.00 0.00 0.00 0.00
December 0.384400E+09 15521.98 22-DEC-06:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.236818E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.101701E+10 15521.98   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.118829E+10 21804.20 30-JAN-06:02 0.00 0.00 0.00 0.00 0.00
February 0.784180E+09 21693.47 22-FEB-06:01 0.00 0.00 0.00 0.00 0.00
March 0.148412E+09 21740.24 13-MAR-05:01 0.00 0.00 0.00 0.00 0.00
April 11783137.98 1854.26 22-APR-05:05 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:03 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.110123E+09 21750.22 20-NOV-06:02 0.00 0.00 0.00 0.00 0.00
December 0.328007E+09 21745.81 11-DEC-06:02 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.257080E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.118829E+10 21804.20   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.511602E+09 13778.04 02-JAN-06:02 0.00 0.00 0.00 0.00 0.00
February 0.193542E+09 13773.40 06-FEB-05:02 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:03 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.705145E+09     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.511602E+09 13778.04   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: VAV_MID WITH REHEAT HEATING COIL

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.320401E+11 647206.67 06-JAN-15:10 0.00 0.00 0.00 0.00 0.00
February 0.406783E+11 695134.46 13-FEB-07:10 0.00 0.00 0.00 0.00 0.00
March 0.286478E+11 692185.59 17-MAR-10:40 0.00 0.00 0.00 0.00 0.00
April 0.851238E+10 341857.12 01-APR-06:10 0.00 0.00 0.00 0.00 0.00
May 0.159006E+09 70691.33 04-MAY-06:10 0.00 0.00 0.00 0.00 0.00
June 0.982523E+09 223115.94 01-JUN-15:07 0.00 0.00 0.00 0.00 0.00
July 0.231969E+09 72729.07 11-JUL-16:05 0.00 0.00 0.00 0.00 0.00
August 0.162206E+10 234230.23 24-AUG-16:40 0.00 0.00 0.00 0.00 0.00
September 0.129535E+09 60394.17 30-SEP-06:10 0.00 0.00 0.00 0.00 0.00
October 0.198327E+10 289925.42 28-OCT-06:10 0.00 0.00 0.00 0.00 0.00
November 0.162760E+11 550972.78 24-NOV-07:10 0.00 0.00 0.00 0.00 0.00
December 0.417913E+11 566967.98 22-DEC-07:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.173054E+12     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.129535E+09 60394.17   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.417913E+11 695134.46   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: CORE_MID VAV BOX REHEAT COIL

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.213439E+11 588541.37 17-JAN-06:05 0.00 0.00 0.00 0.00 0.00
February 0.392210E+10 587047.64 07-FEB-06:02 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:03 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.141072E+09 50018.87 27-NOV-06:20 0.00 0.00 0.00 0.00 0.00
December 0.112090E+09 38678.09 26-DEC-08:00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.255191E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.213439E+11 588541.37   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.695633E+11 157316.30 09-JAN-06:05 0.00 0.00 0.00 0.00 0.00
February 0.568297E+11 156464.17 21-FEB-06:02 0.00 0.00 0.00 0.00 0.00
March 0.178135E+11 168415.76 29-MAR-05:02 0.00 0.00 0.00 0.00 0.00
April 0.442664E+10 170084.70 12-APR-05:03 0.00 0.00 0.00 0.00 0.00
May 5010349.73 6910.15 01-MAY-05:05 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:03 0.00 0.00 0.00 0.00 0.00
October 0.893429E+09 170659.75 27-OCT-05:02 0.00 0.00 0.00 0.00 0.00
November 0.176899E+11 169130.44 01-NOV-05:02 0.00 0.00 0.00 0.00 0.00
December 0.400286E+11 156505.22 30-DEC-05:13 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.207250E+12     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.695633E+11 170659.75   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.488294E+11 204338.79 10-JAN-06:03 0.00 0.00 0.00 0.00 0.00
February 0.351356E+11 204230.88 07-FEB-06:03 0.00 0.00 0.00 0.00 0.00
March 0.135726E+11 209593.82 29-MAR-05:02 0.00 0.00 0.00 0.00 0.00
April 0.501919E+10 203825.90 22-APR-04:11 0.00 0.00 0.00 0.00 0.00
May 71996189.48 18906.17 04-MAY-05:05 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:03 0.00 0.00 0.00 0.00 0.00
October 0.858010E+09 130023.20 28-OCT-05:03 0.00 0.00 0.00 0.00 0.00
November 0.137798E+11 204338.27 27-NOV-05:12 0.00 0.00 0.00 0.00 0.00
December 0.306934E+11 204246.44 26-DEC-05:12 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.147960E+12     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.488294E+11 209593.82   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.449121E+11 232772.81 04-JAN-06:04 0.00 0.00 0.00 0.00 0.00
February 0.295742E+11 231505.95 06-FEB-06:14 0.00 0.00 0.00 0.00 0.00
March 0.108486E+11 231309.10 17-MAR-04:03 0.00 0.00 0.00 0.00 0.00
April 0.424674E+10 232857.41 19-APR-05:02 0.00 0.00 0.00 0.00 0.00
May 32084922.51 17697.82 01-MAY-05:05 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:03 0.00 0.00 0.00 0.00 0.00
October 0.248823E+09 70498.78 28-OCT-05:03 0.00 0.00 0.00 0.00 0.00
November 0.946764E+10 232515.61 27-NOV-05:12 0.00 0.00 0.00 0.00 0.00
December 0.239039E+11 231426.67 26-DEC-05:12 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.123234E+12     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.449121E+11 232857.41   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.442383E+11 206367.10 03-JAN-05:32 0.00 0.00 0.00 0.00 0.00
February 0.338528E+11 206224.42 13-FEB-05:03 0.00 0.00 0.00 0.00 0.00
March 0.109663E+11 205736.84 10-MAR-05:01 0.00 0.00 0.00 0.00 0.00
April 0.357849E+10 198232.86 21-APR-04:11 0.00 0.00 0.00 0.00 0.00
May 29490857.03 8471.11 04-MAY-05:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:03 0.00 0.00 0.00 0.00 0.00
October 0.654917E+09 92537.04 27-OCT-05:02 0.00 0.00 0.00 0.00 0.00
November 0.134060E+11 206021.51 21-NOV-05:02 0.00 0.00 0.00 0.00 0.00
December 0.274666E+11 206150.07 30-DEC-05:12 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.134193E+12     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.442383E+11 206367.10   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: VAV_TOP WITH REHEAT HEATING COIL

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.338916E+10 57633.64 11-JAN-07:10 0.00 0.00 0.00 0.00 0.00
February 0.289492E+10 70787.88 13-FEB-07:10 0.00 0.00 0.00 0.00 0.00
March 0.742457E+09 57675.51 23-MAR-06:10 0.00 0.00 0.00 0.00 0.00
April 0.284068E+09 35725.85 01-APR-06:10 0.00 0.00 0.00 0.00 0.00
May 34288663.86 7575.11 04-MAY-06:10 0.00 0.00 0.00 0.00 0.00
June 59466027.53 15924.05 22-JUN-16:00 0.00 0.00 0.00 0.00 0.00
July 47933129.61 8037.10 11-JUL-16:15 0.00 0.00 0.00 0.00 0.00
August 0.106413E+09 17239.94 24-AUG-16:45 0.00 0.00 0.00 0.00 0.00
September 8075541.16 6733.82 30-SEP-06:10 0.00 0.00 0.00 0.00 0.00
October 0.169932E+09 30610.31 28-OCT-06:10 0.00 0.00 0.00 0.00 0.00
November 0.543217E+09 56001.10 24-NOV-07:10 0.00 0.00 0.00 0.00 0.00
December 0.898605E+09 58136.10 22-DEC-07:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.917853E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 8075541.16 6733.82   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.338916E+10 70787.88   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: CORE_TOP VAV BOX REHEAT COIL

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.849744E+10 88567.49 23-JAN-06:04 0.00 0.00 0.00 0.00 0.00
February 0.624469E+10 88362.69 21-FEB-06:04 0.00 0.00 0.00 0.00 0.00
March 0.160764E+10 88157.06 20-MAR-04:04 0.00 0.00 0.00 0.00 0.00
April 0.322135E+09 87546.02 03-APR-05:03 0.00 0.00 0.00 0.00 0.00
May 288688.36 962.29 01-MAY-06:00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:03 0.00 0.00 0.00 0.00 0.00
October 79225676.65 48590.94 30-OCT-05:03 0.00 0.00 0.00 0.00 0.00
November 0.266802E+10 88559.14 27-NOV-05:14 0.00 0.00 0.00 0.00 0.00
December 0.453051E+10 88565.84 26-DEC-06:05 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.239499E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.849744E+10 88567.49   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.111736E+11 17679.50 23-JAN-05:53 0.00 0.00 0.00 0.00 0.00
February 0.992140E+10 17667.83 16-FEB-06:04 0.00 0.00 0.00 0.00 0.00
March 0.418623E+10 17622.71 20-MAR-04:33 0.00 0.00 0.00 0.00 0.00
April 0.141805E+10 17582.70 03-APR-05:05 0.00 0.00 0.00 0.00 0.00
May 78133321.99 17553.40 01-MAY-05:03 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 5275391.15 1154.68 30-SEP-05:08 0.00 0.00 0.00 0.00 0.00
October 0.530849E+09 17560.06 28-OCT-04:13 0.00 0.00 0.00 0.00 0.00
November 0.430223E+10 17679.77 13-NOV-06:04 0.00 0.00 0.00 0.00 0.00
December 0.821200E+10 17672.78 30-DEC-06:04 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.398278E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.111736E+11 17679.77   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.733526E+10 21778.49 04-JAN-05:02 0.00 0.00 0.00 0.00 0.00
February 0.587683E+10 21781.34 22-FEB-05:02 0.00 0.00 0.00 0.00 0.00
March 0.265098E+10 21777.76 17-MAR-05:02 0.00 0.00 0.00 0.00 0.00
April 0.111940E+10 21769.56 03-APR-04:12 0.00 0.00 0.00 0.00 0.00
May 71943513.89 15397.80 01-MAY-04:12 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 9316113.90 1469.35 30-SEP-05:08 0.00 0.00 0.00 0.00 0.00
October 0.361808E+09 21752.21 10-OCT-04:12 0.00 0.00 0.00 0.00 0.00
November 0.283951E+10 21855.79 27-NOV-05:13 0.00 0.00 0.00 0.00 0.00
December 0.539651E+10 21777.23 06-DEC-06:02 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.256616E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.733526E+10 21855.79   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.788261E+10 25108.81 23-JAN-05:23 0.00 0.00 0.00 0.00 0.00
February 0.603014E+10 25097.89 28-FEB-05:03 0.00 0.00 0.00 0.00 0.00
March 0.291407E+10 25075.18 06-MAR-05:13 0.00 0.00 0.00 0.00 0.00
April 0.135689E+10 24997.80 14-APR-04:12 0.00 0.00 0.00 0.00 0.00
May 0.112237E+09 19919.03 01-MAY-04:12 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:03 0.00 0.00 0.00 0.00 0.00
October 0.277336E+09 24732.49 28-OCT-04:11 0.00 0.00 0.00 0.00 0.00
November 0.265641E+10 25096.32 27-NOV-05:33 0.00 0.00 0.00 0.00 0.00
December 0.535177E+10 25100.95 11-DEC-04:53 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.265814E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.788261E+10 25108.81   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.683434E+10 23730.07 24-JAN-05:11 0.00 0.00 0.00 0.00 0.00
February 0.555338E+10 23677.39 04-FEB-06:02 0.00 0.00 0.00 0.00 0.00
March 0.237478E+10 23655.08 09-MAR-05:12 0.00 0.00 0.00 0.00 0.00
April 0.950064E+09 23674.09 03-APR-04:12 0.00 0.00 0.00 0.00 0.00
May 74704365.47 11110.00 01-MAY-05:03 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 5517094.93 542.53 30-SEP-05:40 0.00 0.00 0.00 0.00 0.00
October 0.341841E+09 22521.86 28-OCT-04:11 0.00 0.00 0.00 0.00 0.00
November 0.271991E+10 23745.62 27-NOV-05:12 0.00 0.00 0.00 0.00 0.00
December 0.478341E+10 23663.62 26-DEC-05:12 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.236379E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.683434E+10 23745.62   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: CAV_BAS HEATING COIL

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:01 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:03 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: AIRLOOP DATACENTER BASEMENT HEATING COIL

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:01 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:03 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: AIRLOOP DATACENTER BOT HEATING COIL

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:01 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:03 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: AIRLOOP DATACENTER MID HEATING COIL

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:01 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:03 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: AIRLOOP DATACENTER TOP HEATING COIL

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:01 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:03 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:01 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:03 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: AIRLOOP DATACENTER BOT_SUPPHEATCOIL

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:01 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:03 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: AIRLOOP DATACENTER MID_SUPPHEATCOIL

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:01 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:03 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: AIRLOOP DATACENTER TOP_SUPPHEATCOIL

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:01 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:03 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: VAV_BOT WITH REHEAT COOLING COIL

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 30689871.65 30689871.65 9748.83 31-JAN-15:20 9748.83 0.00
February 0.00 0.00 33164750.17 33164750.17 8367.16 03-FEB-12:00 8367.16 0.00
March 0.00 0.00 0.153871E+10 0.148852E+10 76666.58 27-MAR-16:00 76666.58 0.02
April 0.00 0.00 0.138862E+11 0.138775E+11 137783.56 07-APR-14:50 137783.56 0.12
May 0.00 0.00 0.403927E+11 0.361379E+11 209454.68 30-MAY-10:55 209454.68 0.29
June 0.00 0.00 0.136685E+12 0.108156E+12 229985.90 17-JUN-04:11 161190.49 0.65
July 0.00 0.00 0.187238E+12 0.149756E+12 243308.66 10-JUL-04:23 172505.61 0.79
August 0.00 0.00 0.190024E+12 0.164056E+12 231242.36 14-AUG-05:03 165280.18 0.83
September 0.00 0.00 0.913896E+11 0.762071E+11 234345.79 14-SEP-04:12 151827.02 0.52
October 0.00 0.00 0.443280E+11 0.330422E+11 174198.93 06-OCT-04:12 73910.25 0.29
November 0.00 0.00 0.144257E+10 0.134262E+10 59107.71 10-NOV-06:03 22960.24 0.02
December 0.00 0.00 33420230.76 33420230.76 5720.14 21-DEC-09:40 5720.14 0.00
                 
Annual Sum or Average 0.00 0.00 0.707021E+12 0.584161E+12       0.30
Minimum of Months 0.00 0.00 30689871.65 30689871.65 5720.14   5720.14 0.00
Maximum of Months 0.00 0.00 0.190024E+12 0.164056E+12 243308.66   209454.68 0.83



Table of Contents

Report: CoilReportMonthly

For: VAV_MID WITH REHEAT COOLING COIL

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 83389854.80 83389854.80 34434.83 13-JAN-14:25 34434.83 0.00
February 0.00 0.00 0.500964E+09 0.500964E+09 48871.94 01-FEB-13:55 48871.94 0.00
March 0.00 0.00 0.103138E+11 0.102482E+11 519836.80 27-MAR-16:00 519836.80 0.02
April 0.00 0.00 0.100759E+12 0.100734E+12 1198849.58 07-APR-14:50 1198849.58 0.11
May 0.00 0.00 0.351039E+12 0.314517E+12 1738838.52 30-MAY-13:20 1738838.52 0.29
June 0.00 0.00 0.116555E+13 0.893492E+12 2207889.43 19-JUN-04:12 1425350.15 0.58
July 0.00 0.00 0.154987E+13 0.117139E+13 2684825.51 28-JUL-05:02 1534865.18 0.64
August 0.00 0.00 0.151033E+13 0.126034E+13 2511481.48 24-AUG-16:27 2511481.48 0.62
September 0.00 0.00 0.810218E+12 0.663230E+12 2236703.19 07-SEP-04:11 1474119.34 0.50
October 0.00 0.00 0.363990E+12 0.270151E+12 1493825.61 06-OCT-05:03 639692.78 0.28
November 0.00 0.00 0.112321E+11 0.106716E+11 535021.37 10-NOV-06:03 207379.73 0.02
December 0.00 0.00 0.362224E+09 0.362224E+09 95587.30 22-DEC-13:23 95587.30 0.00
                 
Annual Sum or Average 0.00 0.00 0.587425E+13 0.469572E+13       0.26
Minimum of Months 0.00 0.00 83389854.80 83389854.80 34434.83   34434.83 0.00
Maximum of Months 0.00 0.00 0.154987E+13 0.126034E+13 2684825.51   2511481.48 0.64



Table of Contents

Report: CoilReportMonthly

For: VAV_TOP WITH REHEAT COOLING COIL

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 20382840.87 20382840.87 1314.90 15-JAN-10:40 1314.90 0.00
February 0.00 0.00 30258728.19 30258728.19 1320.52 10-FEB-11:30 1320.52 0.00
March 0.00 0.00 0.810308E+09 0.808680E+09 45828.42 27-MAR-16:00 45828.42 0.02
April 0.00 0.00 0.101328E+11 0.101328E+11 122817.13 07-APR-14:40 122817.13 0.11
May 0.00 0.00 0.360933E+11 0.326655E+11 214974.71 30-MAY-13:35 195045.21 0.28
June 0.00 0.00 0.123930E+12 0.963734E+11 237098.65 19-JUN-04:12 151158.46 0.58
July 0.00 0.00 0.169467E+12 0.129606E+12 278650.31 28-JUL-05:02 153896.17 0.64
August 0.00 0.00 0.163785E+12 0.137925E+12 250972.32 22-AUG-14:07 247917.80 0.62
September 0.00 0.00 0.822274E+11 0.673085E+11 222420.20 08-SEP-05:02 136068.59 0.50
October 0.00 0.00 0.340670E+11 0.253589E+11 148453.68 06-OCT-05:03 63607.97 0.28
November 0.00 0.00 0.856459E+09 0.816618E+09 21636.91 03-NOV-14:00 21636.91 0.02
December 0.00 0.00 31298225.53 31298225.53 1628.38 21-DEC-11:00 1628.38 0.00
                 
Annual Sum or Average 0.00 0.00 0.621451E+12 0.501078E+12       0.26
Minimum of Months 0.00 0.00 20382840.87 20382840.87 1314.90   1314.90 0.00
Maximum of Months 0.00 0.00 0.169467E+12 0.137925E+12 278650.31   247917.80 0.64



Table of Contents

Report: CoilReportMonthly

For: CAV_BAS COOLING COIL

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 8365601.80 3695369.92 41279.37 24-JAN-06:03 18154.89 0.00
February 0.00 0.00 205417.82 205417.82 141.10 07-FEB-11:40 141.10 0.00
March 0.00 0.00 0.668977E+09 0.668977E+09 46134.71 27-MAR-16:00 46134.71 0.01
April 0.00 0.00 0.616579E+10 0.613196E+10 73829.54 07-APR-13:50 73829.54 0.07
May 0.00 0.00 0.182068E+11 0.172011E+11 117771.82 29-MAY-10:00 117771.82 0.17
June 0.00 0.00 0.742961E+11 0.621839E+11 155875.05 19-JUN-04:53 90785.54 0.52
July 0.00 0.00 0.104256E+12 0.826540E+11 181931.03 09-JUL-16:11 92211.54 0.55
August 0.00 0.00 0.105313E+12 0.887778E+11 158344.91 13-AUG-15:38 100610.89 0.59
September 0.00 0.00 0.555445E+11 0.486349E+11 148449.35 14-SEP-04:53 91029.38 0.44
October 0.00 0.00 0.214916E+11 0.177560E+11 123504.17 06-OCT-04:53 52401.80 0.22
November 0.00 0.00 0.201819E+09 0.181230E+09 81721.74 10-NOV-06:03 33042.34 0.00
December 0.00 0.00 424.63 424.63 0.71 30-DEC-16:40 0.71 0.00
                 
Annual Sum or Average 0.00 0.00 0.386153E+12 0.324194E+12       0.22
Minimum of Months 0.00 0.00 424.63 424.63 0.71   0.71 0.00
Maximum of Months 0.00 0.00 0.105313E+12 0.887778E+11 181931.03   117771.82 0.59



Table of Contents

Report: CoilReportMonthly

For: AIRLOOP DATACENTER BASEMENT COOLING COIL

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.318840E+12 0.318713E+12 124757.31 20-JAN-22:10 124757.31 0.00
February 0.00 0.00 0.508268E+12 0.508268E+12 216019.57 17-FEB-22:03 216019.57 0.00
March 0.00 0.00 0.813321E+12 0.813107E+12 394121.37 31-MAR-24:00 394121.37 0.00
April 0.00 0.00 0.102827E+13 0.102784E+13 405377.02 27-APR-15:50 399882.10 0.00
May 0.00 0.00 0.333982E+12 0.331409E+12 213626.53 31-MAY-24:00 212162.78 0.00
June 0.00 0.00 0.570037E+12 0.561976E+12 304106.66 30-JUN-24:00 303723.20 0.00
July 0.00 0.00 0.839828E+12 0.828742E+12 395944.57 31-JUL-24:00 395944.57 0.00
August 0.00 0.00 0.107870E+13 0.107113E+13 413977.40 18-AUG-19:00 404268.40 0.00
September 0.00 0.00 0.332361E+12 0.326697E+12 212150.71 30-SEP-24:00 212150.71 0.00
October 0.00 0.00 0.582945E+12 0.578946E+12 304024.81 31-OCT-24:00 304024.81 0.00
November 0.00 0.00 0.792092E+12 0.791701E+12 313407.53 10-NOV-10:40 307199.90 0.00
December 0.00 0.00 0.105960E+13 0.105960E+13 401184.24 14-DEC-22:02 401184.24 0.00
                 
Annual Sum or Average 0.00 0.00 0.825824E+13 0.821812E+13       0.00
Minimum of Months 0.00 0.00 0.318840E+12 0.318713E+12 124757.31   124757.31 0.00
Maximum of Months 0.00 0.00 0.107870E+13 0.107113E+13 413977.40   404268.40 0.00



Table of Contents

Report: CoilReportMonthly

For: AIRLOOP DATACENTER BOT COOLING COIL

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.342463E+10 0.341956E+10 2385.29 20-JAN-16:30 2385.29 0.00
February 0.00 0.00 0.814537E+10 0.814537E+10 4447.60 22-FEB-17:00 4447.60 0.00
March 0.00 0.00 0.151389E+11 0.151279E+11 7503.99 31-MAR-24:00 7503.99 0.00
April 0.00 0.00 0.199996E+11 0.199776E+11 8978.91 23-APR-17:44 8978.91 0.00
May 0.00 0.00 0.589798E+10 0.579716E+10 4156.55 31-MAY-24:00 4103.44 0.00
June 0.00 0.00 0.112284E+11 0.109028E+11 5941.84 30-JUN-24:00 5922.71 0.00
July 0.00 0.00 0.168872E+11 0.164088E+11 7814.26 31-JUL-24:00 7814.26 0.00
August 0.00 0.00 0.219419E+11 0.215709E+11 9206.20 31-AUG-18:00 8853.52 0.00
September 0.00 0.00 0.606806E+10 0.585412E+10 3961.58 30-SEP-24:00 3961.58 0.00
October 0.00 0.00 0.109845E+11 0.108290E+11 5704.42 31-OCT-24:00 5702.84 0.00
November 0.00 0.00 0.146481E+11 0.146299E+11 6462.81 03-NOV-16:00 6462.81 0.00
December 0.00 0.00 0.198312E+11 0.198312E+11 8316.29 17-DEC-15:57 8316.29 0.00
                 
Annual Sum or Average 0.00 0.00 0.154196E+12 0.152494E+12       0.00
Minimum of Months 0.00 0.00 0.342463E+10 0.341956E+10 2385.29   2385.29 0.00
Maximum of Months 0.00 0.00 0.219419E+11 0.215709E+11 9206.20   8978.91 0.00



Table of Contents

Report: CoilReportMonthly

For: AIRLOOP DATACENTER MID COOLING COIL

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.109744E+11 0.109332E+11 20375.77 20-JAN-16:30 20375.77 0.00
February 0.00 0.00 0.565800E+11 0.565800E+11 40011.90 22-FEB-17:00 40011.90 0.00
March 0.00 0.00 0.128112E+12 0.128001E+12 65641.23 31-MAR-23:30 65641.23 0.00
April 0.00 0.00 0.179774E+12 0.179551E+12 82909.69 09-APR-17:33 82755.50 0.00
May 0.00 0.00 0.507124E+11 0.497287E+11 39585.26 31-MAY-23:20 38764.21 0.00
June 0.00 0.00 0.105533E+12 0.102301E+12 56019.59 30-JUN-24:00 55825.39 0.00
July 0.00 0.00 0.161178E+12 0.156408E+12 75105.91 31-JUL-24:00 75105.91 0.00
August 0.00 0.00 0.209148E+12 0.205438E+12 88339.46 31-AUG-17:50 84893.17 0.00
September 0.00 0.00 0.536416E+11 0.515465E+11 35956.23 30-SEP-23:30 35956.23 0.00
October 0.00 0.00 0.963262E+11 0.947939E+11 49248.16 31-OCT-23:50 49216.05 0.00
November 0.00 0.00 0.121178E+12 0.120997E+12 60432.81 03-NOV-16:00 60432.81 0.00
December 0.00 0.00 0.164801E+12 0.164801E+12 75055.53 08-DEC-16:10 75055.53 0.00
                 
Annual Sum or Average 0.00 0.00 0.133796E+13 0.132108E+13       0.00
Minimum of Months 0.00 0.00 0.109744E+11 0.109332E+11 20375.77   20375.77 0.00
Maximum of Months 0.00 0.00 0.209148E+12 0.205438E+12 88339.46   84893.17 0.00



Table of Contents

Report: CoilReportMonthly

For: AIRLOOP DATACENTER TOP COOLING COIL

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.531228E+09 0.527819E+09 2026.86 19-JAN-16:30 2026.86 0.00
February 0.00 0.00 0.418180E+10 0.418180E+10 3949.14 22-FEB-17:00 3949.14 0.00
March 0.00 0.00 0.115731E+11 0.115622E+11 6369.83 27-MAR-17:20 6263.28 0.00
April 0.00 0.00 0.171558E+11 0.171337E+11 8323.78 09-APR-17:24 8308.55 0.00
May 0.00 0.00 0.472261E+10 0.462547E+10 3925.87 31-MAY-23:20 3843.07 0.00
June 0.00 0.00 0.105389E+11 0.102159E+11 5523.92 30-JUN-24:00 5504.06 0.00
July 0.00 0.00 0.162256E+11 0.157487E+11 7514.56 31-JUL-24:00 7514.56 0.00
August 0.00 0.00 0.209833E+11 0.206124E+11 8969.18 31-AUG-17:40 8617.17 0.00
September 0.00 0.00 0.513398E+10 0.492541E+10 3386.89 10-SEP-17:31 3366.52 0.00
October 0.00 0.00 0.882384E+10 0.867162E+10 4994.23 04-OCT-16:00 4670.73 0.00
November 0.00 0.00 0.106634E+11 0.106455E+11 6038.37 03-NOV-16:00 6038.37 0.00
December 0.00 0.00 0.146609E+11 0.146609E+11 7389.27 08-DEC-16:10 7389.27 0.00
                 
Annual Sum or Average 0.00 0.00 0.125194E+12 0.123511E+12       0.00
Minimum of Months 0.00 0.00 0.531228E+09 0.527819E+09 2026.86   2026.86 0.00
Maximum of Months 0.00 0.00 0.209833E+11 0.206124E+11 8969.18   8617.17 0.00



Table of Contents

Report: PlantLoopDemandReportMonthly

For: HEATSYS1

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 0.00 0.00 01-JAN-00:01 115191.41 2390801.66 03-JAN-05:11
February 0.00 0.00 01-FEB-00:10 98864.28 1914634.47 13-FEB-05:01
March 0.00 0.00 01-MAR-00:10 36245.37 1557624.50 10-MAR-05:01
April 0.00 0.00 01-APR-00:10 12059.17 1578629.89 21-APR-04:11
May 0.00 0.00 01-MAY-00:10 328.75 113040.46 01-MAY-05:03
June 0.00 0.00 01-JUN-00:10 430.82 169659.24 01-JUN-15:17
July 0.00 0.00 01-JUL-00:10 108.90 44378.54 11-JUL-13:25
August 0.00 0.00 01-AUG-00:03 664.73 154717.99 24-AUG-16:40
September 0.00 0.00 01-SEP-00:03 68.83 69336.09 01-SEP-13:55
October 0.00 0.00 01-OCT-00:10 2381.47 763841.34 28-OCT-05:03
November 0.00 0.00 01-NOV-00:10 33461.38 1650922.48 27-NOV-05:11
December 0.00 0.00 01-DEC-00:10 72433.80 1609875.83 26-DEC-05:11
             
Annual Sum or Average 0.00     30676.15    
Minimum of Months 0.00 0.00   68.83 44378.54  
Maximum of Months 0.00 0.00   115191.41 2390801.66  



Table of Contents

Report: PlantLoopDemandReportMonthly

For: COOLSYS1_SUPPLY

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 507.62 24120.88 24-JAN-06:03 0.00 0.00 01-JAN-00:01
February 860.39 37880.21 02-FEB-13:30 0.00 0.00 01-FEB-00:10
March 5646.03 684939.75 27-MAR-16:00 0.00 0.00 01-MAR-00:10
April 52366.25 1849376.51 07-APR-14:20 0.00 0.00 01-APR-00:10
May 171326.88 2684622.31 30-MAY-13:25 0.00 0.00 01-MAY-00:10
June 602833.14 3290120.64 22-JUN-15:43 0.00 0.00 01-JUN-00:10
July 779933.84 3495743.97 28-JUL-05:04 0.00 0.00 01-JUL-00:10
August 763479.23 2775753.03 24-AUG-16:23 0.00 0.00 01-AUG-00:03
September 415904.83 2247396.78 14-SEP-04:15 0.00 0.00 01-SEP-00:03
October 182713.16 1839173.28 04-OCT-10:20 0.00 0.00 01-OCT-00:10
November 5990.78 346212.32 03-NOV-14:00 0.00 0.00 01-NOV-00:10
December 913.68 39053.00 21-DEC-11:50 0.00 0.00 01-DEC-00:10
             
Annual Sum or Average 250348.15     0.00    
Minimum of Months 507.62 24120.88   0.00 0.00  
Maximum of Months 779933.84 3495743.97   0.00 0.00  



Table of Contents

Report: PlantLoopDemandReportMonthly

For: COOLSYS1_DEMAND

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 19.41 29002.44 24-JAN-06:03 0.00 0.00 01-JAN-00:01
February 230.84 31373.85 02-FEB-13:30 0.00 0.00 01-FEB-00:10
March 4936.08 688684.48 27-MAR-16:00 0.00 0.00 01-MAR-00:10
April 51592.02 2410225.22 07-APR-14:50 0.00 0.00 01-APR-00:10
May 168480.53 2637854.55 30-MAY-13:20 0.00 0.00 01-MAY-00:10
June 599147.61 5010734.98 19-JUN-04:12 0.00 0.00 01-JUN-00:10
July 774359.29 4862483.15 24-JUL-04:12 0.00 0.00 01-JUL-00:10
August 756757.80 4692669.91 12-AUG-05:02 0.00 0.00 01-AUG-00:03
September 412677.64 4811608.54 07-SEP-04:11 0.00 0.00 01-SEP-00:03
October 180526.13 2897255.13 06-OCT-05:03 0.00 0.00 01-OCT-00:10
November 5334.72 600728.67 10-NOV-06:03 0.00 0.00 01-NOV-00:10
December 175.09 49258.84 22-DEC-13:23 0.00 0.00 01-DEC-00:10
             
Annual Sum or Average 247977.83     0.00    
Minimum of Months 19.41 29002.44   0.00 0.00  
Maximum of Months 774359.29 5010734.98   0.00 0.00  



Table of Contents

Report: PlantLoopDemandReportMonthly

For: SINGLE WATER PLANT LOOP

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 159656.67 184421.00 20-JAN-16:30 0.00 0.00 01-JAN-00:01
February 301029.79 325533.38 22-FEB-17:00 0.00 0.00 01-FEB-00:10
March 455826.68 918622.82 27-MAR-16:00 0.00 0.00 01-MAR-00:10
April 660962.40 1386045.76 07-APR-13:00 0.00 0.00 01-APR-00:10
May 259373.20 910734.83 30-MAY-13:00 0.00 0.00 01-MAY-00:10
June 682210.05 1538598.21 19-JUN-12:00 0.00 0.00 01-JUN-00:10
July 1088830.89 1615325.29 07-JUL-12:00 0.00 0.00 01-JUL-00:10
August 1291102.59 1814055.03 24-AUG-16:00 0.00 0.00 01-AUG-00:03
September 396204.91 986728.62 01-SEP-14:00 0.00 0.00 01-SEP-00:03
October 398773.52 872644.22 04-OCT-13:00 0.00 0.00 01-OCT-00:10
November 456810.81 672553.36 03-NOV-14:00 0.00 0.00 01-NOV-00:10
December 584470.89 603996.67 08-DEC-16:10 0.00 0.00 01-DEC-00:10
             
Annual Sum or Average 563543.96     0.00    
Minimum of Months 159656.67 184421.00   0.00 0.00  
Maximum of Months 1291102.59 1814055.03   0.00 0.00  



Table of Contents

Report: PlantLoopDemandReportMonthly

For: SWHSYS1

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 0.00 0.00 01-JAN-00:01 15951.97 53796.66 31-JAN-12:10
February 0.00 0.00 01-FEB-00:10 16182.20 53908.21 10-FEB-12:18
March 0.00 0.00 01-MAR-00:10 16752.17 53446.57 01-MAR-12:30
April 0.00 0.00 01-APR-00:10 15050.70 51234.06 03-APR-11:20
May 0.00 0.00 01-MAY-00:10 14532.57 48313.27 01-MAY-11:30
June 0.00 0.00 01-JUN-00:10 13875.17 44826.85 01-JUN-11:30
July 0.00 0.00 01-JUL-00:10 12276.31 41917.20 03-JUL-11:20
August 0.00 0.00 01-AUG-00:03 13140.47 40964.16 31-AUG-11:30
September 0.00 0.00 01-SEP-00:03 12759.37 42848.14 29-SEP-11:30
October 0.00 0.00 01-OCT-00:10 13491.20 46124.96 31-OCT-11:50
November 0.00 0.00 01-NOV-00:10 14616.00 49562.63 30-NOV-12:30
December 0.00 0.00 01-DEC-00:10 15003.77 52219.04 29-DEC-12:40
             
Annual Sum or Average 0.00     14459.56    
Minimum of Months 0.00 0.00   12276.31 40964.16  
Maximum of Months 0.00 0.00   16752.17 53908.21  



Table of Contents

Report: PlantLoopDemandReportMonthly

For: TOWERWATERSYS

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 31.33 21428.67 23-JAN-17:10 3557.85 180032.30 31-JAN-13:30
February 33.55 32563.91 02-FEB-11:20 5032.20 190860.23 05-FEB-18:41
March 5117.29 789610.47 27-MAR-16:00 3736.84 174757.79 23-MAR-07:08
April 62150.38 3000754.95 07-APR-14:20 1826.12 154056.59 01-APR-07:50
May 221106.90 3610171.36 30-MAY-13:25 1185.75 125678.98 13-MAY-05:30
June 1139990.34 6166419.36 19-JUN-08:40 184.81 96839.21 02-JUN-07:30
July 2001309.72 6947310.87 20-JUL-14:40 4.36 19727.44 11-JUL-03:50
August 1735896.80 7297216.65 02-AUG-15:00 206.70 48994.00 20-AUG-05:12
September 714620.54 5720479.17 07-SEP-14:00 458.91 103680.77 23-SEP-11:30
October 249888.43 3286446.44 04-OCT-13:40 550.13 117667.92 31-OCT-09:50
November 5946.70 425360.47 03-NOV-14:00 2771.25 196109.22 24-NOV-04:01
December 52.57 22788.34 08-DEC-11:10 5852.36 179823.19 28-DEC-11:20
             
Annual Sum or Average 515884.03     2098.76    
Minimum of Months 31.33 21428.67   4.36 19727.44  
Maximum of Months 2001309.72 7297216.65   5852.36 196109.22  



Table of Contents

Report: FanReportMonthly

For: CAV_BAS FAN

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.145144E+11 0.75 10103.89 02-JAN-06:01 1.39
February 0.134485E+11 0.77 10103.89 01-FEB-05:11 1.40
March 0.159212E+11 0.82 10103.89 01-MAR-05:11 1.39
April 0.145132E+11 0.77 10103.89 01-APR-04:11 1.39
May 0.156173E+11 0.80 10103.89 01-MAY-04:12 1.39
June 0.155782E+11 0.82 10103.89 01-JUN-04:12 1.38
July 0.157418E+11 0.80 10103.89 01-JUL-04:12 1.38
August 0.171532E+11 0.87 10103.89 01-AUG-03:02 1.38
September 0.159599E+11 0.84 10103.89 01-SEP-04:12 1.38
October 0.162209E+11 0.83 10103.89 01-OCT-18:20 1.38
November 0.153069E+11 0.81 10103.89 01-NOV-04:12 1.39
December 0.149719E+11 0.77 10103.89 01-DEC-05:11 1.39
           
Annual Sum or Average 0.184948E+12 0.80      
Minimum of Months 0.134485E+11 0.75 10103.89   1.38
Maximum of Months 0.171532E+11 0.87 10103.89   1.40



Table of Contents

Report: FanReportMonthly

For: VAV_BOT WITH REHEAT FAN

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.390265E+10 0.30 18411.18 31-JAN-15:03 1.57
February 0.419016E+10 0.32 19462.78 13-FEB-15:40 1.62
March 0.651145E+10 0.39 18663.28 18-MAR-10:05 1.57
April 0.808852E+10 0.44 18509.25 07-APR-14:50 1.56
May 0.841322E+10 0.44 22327.26 30-MAY-11:00 1.75
June 0.116895E+11 0.56 22327.26 01-JUN-13:50 1.75
July 0.134503E+11 0.63 22327.26 05-JUL-05:02 1.75
August 0.157286E+11 0.70 22327.26 08-AUG-14:30 1.75
September 0.891517E+10 0.46 22327.26 02-SEP-04:11 1.75
October 0.839899E+10 0.43 18277.71 28-OCT-08:27 1.55
November 0.578395E+10 0.35 18277.71 18-NOV-08:47 1.55
December 0.532493E+10 0.34 15336.23 09-DEC-11:35 1.39
           
Annual Sum or Average 0.100397E+12 0.45      
Minimum of Months 0.390265E+10 0.30 15336.23   1.39
Maximum of Months 0.157286E+11 0.70 22327.26   1.75



Table of Contents

Report: FanReportMonthly

For: VAV_MID WITH REHEAT FAN

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.367687E+11 0.35 138437.41 27-JAN-14:40 1.38
February 0.333472E+11 0.34 200225.79 22-FEB-15:57 1.75
March 0.411791E+11 0.34 200225.79 17-MAR-15:30 1.74
April 0.484202E+11 0.36 164557.32 07-APR-14:50 1.53
May 0.686515E+11 0.42 222376.70 30-MAY-05:03 1.85
June 0.969604E+11 0.51 222376.70 01-JUN-14:30 1.85
July 0.109197E+12 0.54 222376.70 05-JUL-04:12 1.85
August 0.122056E+12 0.57 222376.70 03-AUG-03:02 1.84
September 0.751998E+11 0.44 222376.70 02-SEP-04:11 1.85
October 0.596910E+11 0.38 125551.85 05-OCT-15:40 1.29
November 0.361736E+11 0.31 185291.35 07-NOV-08:45 1.66
December 0.332394E+11 0.31 124055.29 21-DEC-10:20 1.29
           
Annual Sum or Average 0.760884E+12 0.41      
Minimum of Months 0.332394E+11 0.31 124055.29   1.29
Maximum of Months 0.122056E+12 0.57 222376.70   1.85



Table of Contents

Report: FanReportMonthly

For: VAV_TOP WITH REHEAT FAN

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.406726E+10 0.37 5218.88 02-JAN-04:01 0.73
February 0.356873E+10 0.36 5218.88 03-FEB-06:01 0.73
March 0.367027E+10 0.32 6389.42 29-MAR-15:20 0.81
April 0.419230E+10 0.32 13563.61 07-APR-14:40 1.26
May 0.613333E+10 0.37 22915.61 30-MAY-10:25 1.75
June 0.937143E+10 0.47 22915.61 01-JUN-14:40 1.75
July 0.109977E+11 0.50 22915.61 11-JUL-13:40 1.75
August 0.121598E+11 0.53 22915.61 16-AUG-04:12 1.75
September 0.676501E+10 0.39 22915.61 02-SEP-04:11 1.75
October 0.489145E+10 0.33 12822.27 04-OCT-16:00 1.21
November 0.327108E+10 0.30 5522.48 03-NOV-14:40 0.75
December 0.357227E+10 0.33 5218.88 02-DEC-06:01 0.73
           
Annual Sum or Average 0.726607E+11 0.38      
Minimum of Months 0.327108E+10 0.30 5218.88   0.73
Maximum of Months 0.121598E+11 0.53 22915.61   1.75



Table of Contents

Report: FanReportMonthly

For: AIRLOOP DATACENTER BASEMENT SUPPLY FAN

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.950830E+11 1.35 35499.94 01-JAN-00:01 1.35
February 0.858814E+11 1.35 35499.94 01-FEB-00:10 1.35
March 0.950830E+11 1.35 35499.94 01-MAR-00:10 1.35
April 0.920158E+11 1.35 35499.94 01-APR-00:10 1.35
May 0.950830E+11 1.35 35499.94 01-MAY-00:10 1.35
June 0.920158E+11 1.35 35499.94 01-JUN-00:20 1.35
July 0.950830E+11 1.35 35499.94 01-JUL-00:10 1.35
August 0.950830E+11 1.35 35499.94 01-AUG-00:03 1.35
September 0.920158E+11 1.35 35499.94 01-SEP-00:03 1.35
October 0.950830E+11 1.35 35499.94 01-OCT-00:10 1.35
November 0.920158E+11 1.35 35499.94 01-NOV-00:10 1.35
December 0.950830E+11 1.35 35499.94 01-DEC-00:10 1.35
           
Annual Sum or Average 0.111953E+13 1.35      
Minimum of Months 0.858814E+11 1.35 35499.94   1.35
Maximum of Months 0.950830E+11 1.35 35499.94   1.35



Table of Contents

Report: FanReportMonthly

For: AIRLOOP DATACENTER BOT SUPPLY FAN

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.148012E+10 0.92 552.61 01-JAN-00:01 0.92
February 0.133688E+10 0.92 552.61 01-FEB-00:10 0.92
March 0.148012E+10 0.92 552.61 01-MAR-00:10 0.92
April 0.143238E+10 0.92 552.61 01-APR-00:10 0.91
May 0.148012E+10 0.91 552.61 01-MAY-00:30 0.91
June 0.143238E+10 0.91 552.61 01-JUN-00:10 0.91
July 0.148012E+10 0.91 552.61 01-JUL-00:10 0.91
August 0.148012E+10 0.91 552.61 01-AUG-00:03 0.91
September 0.143238E+10 0.91 552.61 01-SEP-00:03 0.91
October 0.148012E+10 0.91 552.61 01-OCT-00:10 0.91
November 0.143238E+10 0.92 552.61 01-NOV-00:10 0.91
December 0.148012E+10 0.92 552.61 01-DEC-00:10 0.92
           
Annual Sum or Average 0.174272E+11 0.92      
Minimum of Months 0.133688E+10 0.91 552.61   0.91
Maximum of Months 0.148012E+10 0.92 552.61   0.92



Table of Contents

Report: FanReportMonthly

For: AIRLOOP DATACENTER MID SUPPLY FAN

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.141819E+11 0.92 5294.92 01-JAN-00:01 0.92
February 0.128095E+11 0.92 5294.92 01-FEB-00:10 0.92
March 0.141819E+11 0.92 5294.92 01-MAR-00:10 0.92
April 0.137244E+11 0.92 5294.92 01-APR-00:10 0.91
May 0.141819E+11 0.91 5294.92 01-MAY-00:10 0.91
June 0.137244E+11 0.91 5294.92 01-JUN-00:10 0.91
July 0.141819E+11 0.91 5294.92 01-JUL-00:10 0.91
August 0.141819E+11 0.91 5294.92 01-AUG-00:03 0.91
September 0.137244E+11 0.91 5294.92 01-SEP-00:03 0.91
October 0.141819E+11 0.91 5294.92 01-OCT-00:10 0.91
November 0.137244E+11 0.92 5294.92 01-NOV-00:10 0.91
December 0.141819E+11 0.92 5294.92 01-DEC-00:10 0.92
           
Annual Sum or Average 0.166981E+12 0.92      
Minimum of Months 0.128095E+11 0.91 5294.92   0.91
Maximum of Months 0.141819E+11 0.92 5294.92   0.92



Table of Contents

Report: FanReportMonthly

For: AIRLOOP DATACENTER TOP SUPPLY FAN

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.144359E+10 0.92 538.97 01-JAN-00:01 0.92
February 0.130389E+10 0.92 538.97 01-FEB-00:10 0.92
March 0.144359E+10 0.92 538.97 01-MAR-00:10 0.92
April 0.139702E+10 0.92 538.97 01-APR-00:10 0.91
May 0.144359E+10 0.91 538.97 01-MAY-00:10 0.91
June 0.139702E+10 0.91 538.97 01-JUN-00:10 0.91
July 0.144359E+10 0.91 538.97 01-JUL-00:10 0.91
August 0.144359E+10 0.91 538.97 01-AUG-00:03 0.91
September 0.139702E+10 0.91 538.97 01-SEP-00:03 0.91
October 0.144359E+10 0.91 538.97 01-OCT-00:10 0.91
November 0.139702E+10 0.92 538.97 01-NOV-00:10 0.91
December 0.144359E+10 0.92 538.97 01-DEC-00:10 0.92
           
Annual Sum or Average 0.169971E+11 0.92      
Minimum of Months 0.130389E+10 0.91 538.97   0.91
Maximum of Months 0.144359E+10 0.92 538.97   0.92



Table of Contents

Report: PumpReportMonthly

For: HEATSYS1 PUMP

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

PUMP ELECTRICITY ENERGY [J] PUMP FLUID HEAT GAIN ENERGY [J] PUMP ELECTRICITY RATE {Maximum} [W] PUMP ELECTRICITY RATE {TIMESTAMP} PUMP SHAFT POWER {AT MAX/MIN} [W] PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s]
January 0.141529E+10 0.127376E+10 5658.54 02-JAN-05:22 5092.69 5092.69 50.57 12.35
February 0.109945E+10 0.989502E+09 5656.52 06-FEB-05:02 5090.87 5090.87 49.32 12.34
March 0.451417E+09 0.406275E+09 4730.96 17-MAR-05:01 4257.86 4257.86 41.30 7.77
April 0.135332E+09 0.121799E+09 4374.44 21-APR-04:11 3937.00 3937.00 26.06 6.75
May 3835701.28 3452131.16 449.79 01-MAY-05:03 404.81 404.81 24.62 0.47
June 7224815.88 6502334.29 962.55 01-JUN-15:07 866.30 866.30 44.07 1.04
July 2311041.46 2079937.31 336.97 11-JUL-16:05 303.28 303.28 57.02 0.35
August 11634701.08 10471230.97 1090.54 24-AUG-18:37 981.49 981.49 51.06 1.18
September 959775.83 863798.25 363.94 01-SEP-13:55 327.54 327.54 38.09 0.38
October 26529259.97 23876333.97 2876.75 28-OCT-05:03 2589.07 2589.07 31.94 3.65
November 0.386345E+09 0.347711E+09 4753.48 22-NOV-06:01 4278.13 4278.13 44.44 7.83
December 0.910413E+09 0.819371E+09 4740.30 02-DEC-06:01 4266.27 4266.27 43.28 7.79
                 
Annual Sum or Average 0.445074E+10 0.400566E+10            
Minimum of Months 959775.83 863798.25 336.97   303.28 303.28 24.62 0.35
Maximum of Months 0.141529E+10 0.127376E+10 5658.54   5092.69 5092.69 57.02 12.35



Table of Contents

Report: PumpReportMonthly

For: COOLSYS1 PUMP SECONDARY

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

PUMP ELECTRICITY ENERGY [J] PUMP FLUID HEAT GAIN ENERGY [J] PUMP ELECTRICITY RATE {Maximum} [W] PUMP ELECTRICITY RATE {TIMESTAMP} PUMP SHAFT POWER {AT MAX/MIN} [W] PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s]
January 32352.58 29117.32 27.04 24-JAN-06:03 24.33 24.33 6.70 4.60
February 171816.70 154635.03 11.70 02-FEB-13:40 10.53 10.53 6.70 2.50
March 3452182.52 3106964.27 307.78 27-MAR-16:00 277.00 277.00 6.70 19.55
April 0.101023E+09 90920902.11 11354.22 07-APR-13:50 10218.80 10218.80 9.69 100.28
May 0.294559E+09 0.265103E+09 9343.35 30-MAY-13:25 8409.01 8409.01 7.24 92.67
June 0.123402E+10 0.111062E+10 21060.43 15-JUN-05:03 18954.38 18954.38 9.37 128.22
July 0.173385E+10 0.156046E+10 21060.43 01-JUL-05:03 18954.38 18954.38 9.27 128.22
August 0.217543E+10 0.195788E+10 21060.43 04-AUG-05:03 18954.38 18954.38 9.43 128.22
September 0.951083E+09 0.855974E+09 21060.43 05-SEP-05:02 18954.38 18954.38 8.94 128.22
October 0.462959E+09 0.416663E+09 9387.18 06-OCT-05:03 8448.46 8448.46 7.97 92.84
November 3175567.47 2858010.73 621.74 10-NOV-06:03 559.57 559.57 6.70 27.85
December 94476.05 85028.44 10.47 22-DEC-13:23 9.42 9.42 6.70 2.29
                 
Annual Sum or Average 0.695984E+10 0.626386E+10            
Minimum of Months 32352.58 29117.32 10.47   9.42 9.42 6.70 2.29
Maximum of Months 0.217543E+10 0.195788E+10 21060.43   18954.38 18954.38 9.69 128.22



Table of Contents

Report: PumpReportMonthly

For: COOLSYS1 CHILLER1 PUMP

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

PUMP ELECTRICITY ENERGY [J] PUMP FLUID HEAT GAIN ENERGY [J] PUMP ELECTRICITY RATE {Maximum} [W] PUMP ELECTRICITY RATE {TIMESTAMP} PUMP SHAFT POWER {AT MAX/MIN} [W] PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s]
January 0.145379E+10 0.130841E+10 7247.66 03-JAN-19:30 6522.89 6522.89 6.72 64.11
February 0.169225E+10 0.152303E+10 7247.66 01-FEB-13:45 6522.89 6522.89 6.72 64.11
March 0.211904E+10 0.190713E+10 7247.66 01-MAR-08:50 6522.89 6522.89 6.72 64.11
April 0.361794E+10 0.325614E+10 7247.66 01-APR-04:30 6522.89 6522.89 6.72 64.11
May 0.858165E+10 0.772349E+10 7247.66 01-MAY-07:50 6522.89 6522.89 6.73 64.11
June 0.132663E+11 0.119397E+11 7247.66 01-JUN-04:12 6522.89 6522.89 9.12 64.11
July 0.161640E+11 0.145476E+11 7247.66 01-JUL-04:12 6522.89 6522.89 10.79 64.11
August 0.169783E+11 0.152805E+11 7247.66 01-AUG-00:23 6522.89 6522.89 6.89 64.11
September 0.111472E+11 0.100325E+11 7247.66 01-SEP-00:03 6522.89 6522.89 6.87 64.11
October 0.665154E+10 0.598639E+10 7247.66 02-OCT-00:25 6522.89 6522.89 6.87 64.11
November 0.189311E+10 0.170380E+10 7247.66 01-NOV-05:04 6522.89 6522.89 6.72 64.11
December 0.219804E+10 0.197824E+10 7247.66 01-DEC-09:05 6522.89 6522.89 6.72 64.11
                 
Annual Sum or Average 0.857632E+11 0.771869E+11            
Minimum of Months 0.145379E+10 0.130841E+10 7247.66   6522.89 6522.89 6.72 64.11
Maximum of Months 0.169783E+11 0.152805E+11 7247.66   6522.89 6522.89 10.79 64.11



Table of Contents

Report: PumpReportMonthly

For: COOLSYS1 CHILLER2 PUMP

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

PUMP ELECTRICITY ENERGY [J] PUMP FLUID HEAT GAIN ENERGY [J] PUMP ELECTRICITY RATE {Maximum} [W] PUMP ELECTRICITY RATE {TIMESTAMP} PUMP SHAFT POWER {AT MAX/MIN} [W] PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s]
January 0.00 0.00 0.00 01-JAN-00:01 0.00 0.00 6.70 0.00
February 0.00 0.00 0.00 01-FEB-00:10 0.00 0.00 6.72 0.00
March 0.00 0.00 0.00 01-MAR-00:10 0.00 0.00 6.72 0.00
April 39137367.41 35223630.67 7247.66 07-APR-13:40 6522.89 6522.89 12.23 32.06
May 0.343539E+09 0.309185E+09 7247.66 30-MAY-08:30 6522.89 6522.89 12.68 32.06
June 0.293001E+10 0.263701E+10 7247.66 01-JUN-10:00 6522.89 6522.89 12.00 32.06
July 0.495718E+10 0.446146E+10 7247.66 03-JUL-07:20 6522.89 6522.89 11.86 32.06
August 0.482941E+10 0.434647E+10 7247.66 01-AUG-07:20 6522.89 6522.89 12.03 32.06
September 0.170878E+10 0.153790E+10 7247.66 01-SEP-04:14 6522.89 6522.89 12.59 32.06
October 0.613152E+09 0.551837E+09 7247.66 03-OCT-10:30 6522.89 6522.89 12.52 32.06
November 0.00 0.00 0.00 01-NOV-00:10 0.00 0.00 6.72 0.00
December 0.00 0.00 0.00 01-DEC-00:10 0.00 0.00 6.72 0.00
                 
Annual Sum or Average 0.154212E+11 0.138791E+11            
Minimum of Months 0.00 0.00 0.00   0.00 0.00 6.70 0.00
Maximum of Months 0.495718E+10 0.446146E+10 7247.66   6522.89 6522.89 12.68 32.06



Table of Contents

Report: PumpReportMonthly

For: PLANT CIRC PUMP

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

PUMP ELECTRICITY ENERGY [J] PUMP FLUID HEAT GAIN ENERGY [J] PUMP ELECTRICITY RATE {Maximum} [W] PUMP ELECTRICITY RATE {TIMESTAMP} PUMP SHAFT POWER {AT MAX/MIN} [W] PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s]
January 0.916583E+10 0.824925E+10 3422.13 01-JAN-00:01 3079.92 3079.92 21.43 14.29
February 0.827881E+10 0.745093E+10 3422.13 01-FEB-00:10 3079.92 3079.92 24.15 14.29
March 0.916583E+10 0.824925E+10 3422.13 01-MAR-00:10 3079.92 3079.92 26.87 14.29
April 0.887016E+10 0.798314E+10 3422.13 01-APR-00:10 3079.92 3079.92 30.04 14.29
May 0.916583E+10 0.824925E+10 3422.13 01-MAY-00:10 3079.92 3079.92 22.33 14.29
June 0.887016E+10 0.798314E+10 3422.13 01-JUN-00:10 3079.92 3079.92 28.10 14.29
July 0.916583E+10 0.824925E+10 3422.13 01-JUL-00:10 3079.92 3079.92 33.87 14.29
August 0.916583E+10 0.824925E+10 3422.13 01-AUG-00:03 3079.92 3079.92 42.42 14.29
September 0.887016E+10 0.798314E+10 3422.13 01-SEP-00:03 3079.92 3079.92 29.94 14.29
October 0.916583E+10 0.824925E+10 3422.13 01-OCT-00:10 3079.92 3079.92 24.76 14.29
November 0.887016E+10 0.798314E+10 3422.13 01-NOV-00:10 3079.92 3079.92 27.38 14.29
December 0.916583E+10 0.824925E+10 3422.13 01-DEC-00:10 3079.92 3079.92 29.77 14.29
                 
Annual Sum or Average 0.107920E+12 0.971282E+11            
Minimum of Months 0.827881E+10 0.745093E+10 3422.13   3079.92 3079.92 21.43 14.29
Maximum of Months 0.916583E+10 0.824925E+10 3422.13   3079.92 3079.92 42.42 14.29



Table of Contents

Report: PumpReportMonthly

For: SWHSYS1 PUMP

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

PUMP ELECTRICITY ENERGY [J] PUMP FLUID HEAT GAIN ENERGY [J] PUMP ELECTRICITY RATE {Maximum} [W] PUMP ELECTRICITY RATE {TIMESTAMP} PUMP SHAFT POWER {AT MAX/MIN} [W] PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s]
January 0.112905E+09 33871561.48 56.21 01-JAN-06:02 16.86 16.86 56.24 0.44
February 0.101979E+09 30593668.43 56.21 01-FEB-06:02 16.86 16.86 56.27 0.44
March 0.112905E+09 33871561.48 56.21 01-MAR-06:03 16.86 16.86 55.58 0.44
April 0.109263E+09 32778930.46 56.21 01-APR-05:03 16.86 16.86 56.34 0.44
May 0.112905E+09 33871561.48 56.21 01-MAY-05:03 16.86 16.86 56.85 0.44
June 0.109263E+09 32778930.46 56.21 01-JUN-05:03 16.86 16.86 55.76 0.44
July 0.112905E+09 33871561.48 56.21 01-JUL-05:03 16.86 16.86 56.11 0.44
August 0.112905E+09 33871561.48 56.21 01-AUG-05:03 16.86 16.86 56.89 0.44
September 0.109263E+09 32778930.46 56.21 01-SEP-05:03 16.86 16.86 57.02 0.44
October 0.112905E+09 33871561.48 56.21 01-OCT-05:10 16.86 16.86 55.89 0.44
November 0.109263E+09 32778930.46 56.21 01-NOV-05:02 16.86 16.86 56.96 0.44
December 0.112905E+09 33871561.48 56.21 01-DEC-06:03 16.86 16.86 56.28 0.44
                 
Annual Sum or Average 0.132937E+10 0.398810E+09            
Minimum of Months 0.101979E+09 30593668.43 56.21   16.86 16.86 55.58 0.44
Maximum of Months 0.112905E+09 33871561.48 56.21   16.86 16.86 57.02 0.44



Table of Contents

Report: PumpReportMonthly

For: TOWERWATERSYS PUMP

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

PUMP ELECTRICITY ENERGY [J] PUMP FLUID HEAT GAIN ENERGY [J] PUMP ELECTRICITY RATE {Maximum} [W] PUMP ELECTRICITY RATE {TIMESTAMP} PUMP SHAFT POWER {AT MAX/MIN} [W] PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s]
January 0.372514E+10 0.335263E+10 18574.00 23-JAN-17:10 16716.60 16716.60 21.17 75.27
February 0.431940E+10 0.388746E+10 18574.47 02-FEB-11:20 16717.02 16717.02 21.20 75.27
March 0.539481E+10 0.485533E+10 18606.64 27-MAR-16:00 16745.98 16745.98 23.61 75.27
April 0.936726E+10 0.843053E+10 37277.80 07-APR-14:20 33550.02 33550.02 25.87 150.54
May 0.228304E+11 0.205474E+11 37308.09 30-MAY-13:25 33577.28 33577.28 26.84 150.54
June 0.404229E+11 0.363806E+11 37369.84 15-JUN-09:50 33632.85 33632.85 28.90 150.54
July 0.528581E+11 0.475723E+11 37369.84 05-JUL-13:50 33632.85 33632.85 28.82 150.54
August 0.545549E+11 0.490994E+11 37369.84 01-AUG-09:20 33632.85 33632.85 28.85 150.54
September 0.322801E+11 0.290521E+11 37369.84 07-SEP-12:20 33632.85 33632.85 28.97 150.54
October 0.183968E+11 0.165571E+11 37291.99 04-OCT-13:40 33562.80 33562.80 26.32 150.54
November 0.485169E+10 0.436652E+10 18591.15 03-NOV-14:00 16732.03 16732.03 22.45 75.27
December 0.560388E+10 0.504349E+10 18574.05 08-DEC-11:10 16716.65 16716.65 21.17 75.27
                 
Annual Sum or Average 0.254605E+12 0.229145E+12            
Minimum of Months 0.372514E+10 0.335263E+10 18574.00   16716.60 16716.60 21.17 75.27
Maximum of Months 0.545549E+11 0.490994E+11 37369.84   33632.85 33632.85 28.97 150.54



Table of Contents

Report: CondLoopDemandReportMonthly

For: HEATSYS1

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 0.00 0.00 01-JAN-00:01 43.92 43.92 115191.41 2390801.66 03-JAN-05:11
February 0.00 0.00 01-FEB-00:10 28.78 28.78 98864.28 1914634.47 13-FEB-05:01
March 0.00 0.00 01-MAR-00:10 25.14 25.14 36245.37 1557624.50 10-MAR-05:01
April 0.00 0.00 01-APR-00:10 21.28 21.28 12059.17 1578629.89 21-APR-04:11
May 0.00 0.00 01-MAY-00:10 22.99 22.99 328.75 113040.46 01-MAY-05:03
June 0.00 0.00 01-JUN-00:10 51.20 51.20 430.82 169659.24 01-JUN-15:17
July 0.00 0.00 01-JUL-00:10 50.92 50.92 108.90 44378.54 11-JUL-13:25
August 0.00 0.00 01-AUG-00:03 48.11 48.11 664.73 154717.99 24-AUG-16:40
September 0.00 0.00 01-SEP-00:03 36.71 36.71 68.83 69336.09 01-SEP-13:55
October 0.00 0.00 01-OCT-00:10 35.87 35.87 2381.47 763841.34 28-OCT-05:03
November 0.00 0.00 01-NOV-00:10 26.15 26.15 33461.38 1650922.48 27-NOV-05:11
December 0.00 0.00 01-DEC-00:10 23.29 23.29 72433.80 1609875.83 26-DEC-05:11
                 
Annual Sum or Average 0.00         30676.15    
Minimum of Months 0.00 0.00   21.28 21.28 68.83 44378.54  
Maximum of Months 0.00 0.00   51.20 51.20 115191.41 2390801.66  



Table of Contents

Report: CondLoopDemandReportMonthly

For: COOLSYS1_SUPPLY

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 507.62 24120.88 24-JAN-06:03 6.79 6.70 0.00 0.00 01-JAN-00:01
February 860.39 37880.21 02-FEB-13:30 6.84 6.70 0.00 0.00 01-FEB-00:10
March 5646.03 684939.75 27-MAR-16:00 9.25 6.70 0.00 0.00 01-MAR-00:10
April 52366.25 1849376.51 07-APR-14:20 10.14 6.70 0.00 0.00 01-APR-00:10
May 171326.88 2684622.31 30-MAY-13:25 11.70 6.70 0.00 0.00 01-MAY-00:10
June 602833.14 3290120.64 22-JUN-15:43 12.83 7.14 0.00 0.00 01-JUN-00:10
July 779933.84 3495743.97 28-JUL-05:04 13.21 7.52 0.00 0.00 01-JUL-00:10
August 763479.23 2775753.03 24-AUG-16:23 11.87 6.70 0.00 0.00 01-AUG-00:03
September 415904.83 2247396.78 14-SEP-04:15 10.88 6.70 0.00 0.00 01-SEP-00:03
October 182713.16 1839173.28 04-OCT-10:20 10.12 6.70 0.00 0.00 01-OCT-00:10
November 5990.78 346212.32 03-NOV-14:00 7.99 6.70 0.00 0.00 01-NOV-00:10
December 913.68 39053.00 21-DEC-11:50 6.85 6.70 0.00 0.00 01-DEC-00:10
                 
Annual Sum or Average 250348.15         0.00    
Minimum of Months 507.62 24120.88   6.79 6.70 0.00 0.00  
Maximum of Months 779933.84 3495743.97   13.21 7.52 0.00 0.00  



Table of Contents

Report: CondLoopDemandReportMonthly

For: COOLSYS1_DEMAND

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 19.41 29002.44 24-JAN-06:03 8.20 6.70 0.00 0.00 01-JAN-00:01
February 230.84 31373.85 02-FEB-13:30 9.72 6.70 0.00 0.00 01-FEB-00:10
March 4936.08 688684.48 27-MAR-16:00 15.12 6.70 0.00 0.00 01-MAR-00:10
April 51592.02 2410225.22 07-APR-14:50 12.65 8.70 0.00 0.00 01-APR-00:10
May 168480.53 2637854.55 30-MAY-13:20 13.72 8.70 0.00 0.00 01-MAY-00:10
June 599147.61 5010734.98 19-JUN-04:12 16.04 11.36 0.00 0.00 01-JUN-00:10
July 774359.29 4862483.15 24-JUL-04:12 15.76 11.22 0.00 0.00 01-JUL-00:10
August 756757.80 4692669.91 12-AUG-05:02 15.45 11.06 0.00 0.00 01-AUG-00:03
September 412677.64 4811608.54 07-SEP-04:11 15.67 11.17 0.00 0.00 01-SEP-00:03
October 180526.13 2897255.13 06-OCT-05:03 14.16 9.00 0.00 0.00 01-OCT-00:10
November 5334.72 600728.67 10-NOV-06:03 11.85 6.70 0.00 0.00 01-NOV-00:10
December 175.09 49258.84 22-DEC-13:23 11.84 6.70 0.00 0.00 01-DEC-00:10
                 
Annual Sum or Average 247977.83         0.00    
Minimum of Months 19.41 29002.44   8.20 6.70 0.00 0.00  
Maximum of Months 774359.29 5010734.98   16.04 11.36 0.00 0.00  



Table of Contents

Report: CondLoopDemandReportMonthly

For: SINGLE WATER PLANT LOOP

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 159656.67 184421.00 20-JAN-16:30 22.04 18.33 0.00 0.00 01-JAN-00:01
February 301029.79 325533.38 22-FEB-17:00 24.87 18.33 0.00 0.00 01-FEB-00:10
March 455826.68 918622.82 27-MAR-16:00 36.57 26.67 0.00 0.00 01-MAR-00:10
April 660962.40 1386045.76 07-APR-13:00 45.62 32.65 0.00 0.00 01-APR-00:10
May 259373.20 910734.83 30-MAY-13:00 36.42 32.00 0.00 0.00 01-MAY-00:10
June 682210.05 1538598.21 19-JUN-12:00 48.54 40.43 0.00 0.00 01-JUN-00:10
July 1088830.89 1615325.29 07-JUL-12:00 50.00 38.99 0.00 0.00 01-JUL-00:10
August 1291102.59 1814055.03 24-AUG-16:00 53.77 40.20 0.00 0.00 01-AUG-00:03
September 396204.91 986728.62 01-SEP-14:00 37.90 33.22 0.00 0.00 01-SEP-00:03
October 398773.52 872644.22 04-OCT-13:00 35.67 28.32 0.00 0.00 01-OCT-00:10
November 456810.81 672553.36 03-NOV-14:00 31.75 22.12 0.00 0.00 01-NOV-00:10
December 584470.89 603996.67 08-DEC-16:10 30.39 18.33 0.00 0.00 01-DEC-00:10
                 
Annual Sum or Average 563543.96         0.00    
Minimum of Months 159656.67 184421.00   22.04 18.33 0.00 0.00  
Maximum of Months 1291102.59 1814055.03   53.77 40.43 0.00 0.00  



Table of Contents

Report: CondLoopDemandReportMonthly

For: SWHSYS1

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 0.00 0.00 01-JAN-00:01 57.43 57.43 15951.97 53796.66 31-JAN-12:10
February 0.00 0.00 01-FEB-00:10 56.84 56.84 16182.20 53908.21 10-FEB-12:18
March 0.00 0.00 01-MAR-00:10 56.27 56.27 16752.17 53446.57 01-MAR-12:30
April 0.00 0.00 01-APR-00:10 56.95 56.95 15050.70 51234.06 03-APR-11:20
May 0.00 0.00 01-MAY-00:10 57.65 57.65 14532.57 48313.27 01-MAY-11:30
June 0.00 0.00 01-JUN-00:10 56.32 56.32 13875.17 44826.85 01-JUN-11:30
July 0.00 0.00 01-JUL-00:10 56.62 56.62 12276.31 41917.20 03-JUL-11:20
August 0.00 0.00 01-AUG-00:03 57.34 57.34 13140.47 40964.16 31-AUG-11:30
September 0.00 0.00 01-SEP-00:03 57.14 57.14 12759.37 42848.14 29-SEP-11:30
October 0.00 0.00 01-OCT-00:10 56.46 56.46 13491.20 46124.96 31-OCT-11:50
November 0.00 0.00 01-NOV-00:10 57.40 57.40 14616.00 49562.63 30-NOV-12:30
December 0.00 0.00 01-DEC-00:10 56.92 56.92 15003.77 52219.04 29-DEC-12:40
                 
Annual Sum or Average 0.00         14459.56    
Minimum of Months 0.00 0.00   56.27 56.27 12276.31 40964.16  
Maximum of Months 0.00 0.00   57.65 57.65 16752.17 53908.21  



Table of Contents

Report: CondLoopDemandReportMonthly

For: TOWERWATERSYS

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 31.33 21428.67 23-JAN-17:10 21.17 20.61 3557.85 180032.30 31-JAN-13:30
February 33.55 32563.91 02-FEB-11:20 21.20 20.34 5032.20 190860.23 05-FEB-18:41
March 5117.29 789610.47 27-MAR-16:00 23.61 21.10 3736.84 174757.79 23-MAR-07:08
April 62150.38 3000754.95 07-APR-14:20 25.87 21.47 1826.12 154056.59 01-APR-07:50
May 221106.90 3610171.36 30-MAY-13:25 26.84 22.53 1185.75 125678.98 13-MAY-05:30
June 1139990.34 6166419.36 19-JUN-08:40 30.90 27.47 184.81 96839.21 02-JUN-07:30
July 2001309.72 6947310.87 20-JUL-14:40 32.14 28.32 4.36 19727.44 11-JUL-03:50
August 1735896.80 7297216.65 02-AUG-15:00 32.70 28.73 206.70 48994.00 20-AUG-05:12
September 714620.54 5720479.17 07-SEP-14:00 30.19 26.65 458.91 103680.77 23-SEP-11:30
October 249888.43 3286446.44 04-OCT-13:40 26.32 22.80 550.13 117667.92 31-OCT-09:50
November 5946.70 425360.47 03-NOV-14:00 22.45 21.10 2771.25 196109.22 24-NOV-04:01
December 52.57 22788.34 08-DEC-11:10 21.17 20.38 5852.36 179823.19 28-DEC-11:20
                 
Annual Sum or Average 515884.03         2098.76    
Minimum of Months 31.33 21428.67   21.17 20.34 4.36 19727.44  
Maximum of Months 2001309.72 7297216.65   32.70 28.73 5852.36 196109.22  



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: BASEMENT

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: CORE_BOTTOM

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: CORE_MID

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: CORE_TOP

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: GROUNDFLOOR_PLENUM

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00 0.00
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: MIDFLOOR_PLENUM

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00 0.00
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: TOPFLOOR_PLENUM

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00 0.00
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: DATACENTER_MID_ZN_6

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: VAV_BOT WITH REHEAT

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.542208E+10 0.00 30689871.65 0.390265E+10 0.00 0.00
February 0.489082E+10 0.00 33164750.17 0.419016E+10 0.00 0.00
March 0.168011E+10 0.00 0.153871E+10 0.651145E+10 0.00 0.00
April 0.295018E+09 0.00 0.138862E+11 0.808852E+10 0.00 0.00
May 42558236.87 0.00 0.403927E+11 0.841322E+10 0.00 0.00
June 88512668.17 0.00 0.136685E+12 0.116895E+11 0.00 0.00
July 32794241.12 0.00 0.187238E+12 0.134503E+11 0.00 0.00
August 0.143217E+09 0.00 0.190024E+12 0.157286E+11 0.00 0.00
September 27708109.04 0.00 0.913896E+11 0.891517E+10 0.00 0.00
October 97138550.36 0.00 0.443280E+11 0.839899E+10 0.00 0.00
November 0.105479E+10 0.00 0.144257E+10 0.578395E+10 0.00 0.00
December 0.255425E+10 0.00 33420230.76 0.532493E+10 0.00 0.00
             
Annual Sum or Average 0.163290E+11 0.00 0.707021E+12 0.100397E+12 0.00 0.00
Minimum of Months 27708109.04 0.00 30689871.65 0.390265E+10 0.00 0.00
Maximum of Months 0.542208E+10 0.00 0.190024E+12 0.157286E+11 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: VAV_MID WITH REHEAT

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.260927E+12 0.00 83389854.80 0.367687E+11 0.00 0.00
February 0.199993E+12 0.00 0.500964E+09 0.333472E+11 0.00 0.00
March 0.818488E+11 0.00 0.103138E+11 0.411791E+11 0.00 0.00
April 0.257834E+11 0.00 0.100759E+12 0.484202E+11 0.00 0.00
May 0.297589E+09 0.00 0.351039E+12 0.686515E+11 0.00 0.00
June 0.982523E+09 0.00 0.116555E+13 0.969604E+11 0.00 0.00
July 0.231969E+09 0.00 0.154987E+13 0.109197E+12 0.00 0.00
August 0.162206E+10 0.00 0.151033E+13 0.122056E+12 0.00 0.00
September 0.129535E+09 0.00 0.810218E+12 0.751998E+11 0.00 0.00
October 0.463845E+10 0.00 0.363990E+12 0.596910E+11 0.00 0.00
November 0.707604E+11 0.00 0.112321E+11 0.361736E+11 0.00 0.00
December 0.163996E+12 0.00 0.362224E+09 0.332394E+11 0.00 0.00
             
Annual Sum or Average 0.811210E+12 0.00 0.587425E+13 0.760884E+12 0.00 0.00
Minimum of Months 0.129535E+09 0.00 83389854.80 0.332394E+11 0.00 0.00
Maximum of Months 0.260927E+12 0.00 0.154987E+13 0.122056E+12 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: VAV_TOP WITH REHEAT

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.451124E+11 0.00 20382840.87 0.406726E+10 0.00 0.00
February 0.365214E+11 0.00 30258728.19 0.356873E+10 0.00 0.00
March 0.144762E+11 0.00 0.810308E+09 0.367027E+10 0.00 0.00
April 0.545060E+10 0.00 0.101328E+11 0.419230E+10 0.00 0.00
May 0.371595E+09 0.00 0.360933E+11 0.613333E+10 0.00 0.00
June 59466027.53 0.00 0.123930E+12 0.937143E+10 0.00 0.00
July 47933129.61 0.00 0.169467E+12 0.109977E+11 0.00 0.00
August 0.106413E+09 0.00 0.163785E+12 0.121598E+11 0.00 0.00
September 28184141.14 0.00 0.822274E+11 0.676501E+10 0.00 0.00
October 0.176099E+10 0.00 0.340670E+11 0.489145E+10 0.00 0.00
November 0.157293E+11 0.00 0.856459E+09 0.327108E+10 0.00 0.00
December 0.291728E+11 0.00 31298225.53 0.357227E+10 0.00 0.00
             
Annual Sum or Average 0.148837E+12 0.00 0.621451E+12 0.726607E+11 0.00 0.00
Minimum of Months 28184141.14 0.00 20382840.87 0.327108E+10 0.00 0.00
Maximum of Months 0.451124E+11 0.00 0.169467E+12 0.121598E+11 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: CAV_BAS

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.00 0.00 8365601.80 0.145144E+11 0.00 0.00
February 0.00 0.00 205417.82 0.134485E+11 0.00 0.00
March 0.00 0.00 0.668977E+09 0.159212E+11 0.00 0.00
April 0.00 0.00 0.616579E+10 0.145132E+11 0.00 0.00
May 0.00 0.00 0.182068E+11 0.156173E+11 0.00 0.00
June 0.00 0.00 0.742961E+11 0.155782E+11 0.00 0.00
July 0.00 0.00 0.104256E+12 0.157418E+11 0.00 0.00
August 0.00 0.00 0.105313E+12 0.171532E+11 0.00 0.00
September 0.00 0.00 0.555445E+11 0.159599E+11 0.00 0.00
October 0.00 0.00 0.214916E+11 0.162209E+11 0.00 0.00
November 0.00 0.00 0.201819E+09 0.153069E+11 0.00 0.00
December 0.00 0.00 424.63 0.149719E+11 0.00 0.00
             
Annual Sum or Average 0.00 0.00 0.386153E+12 0.184948E+12 0.00 0.00
Minimum of Months 0.00 0.00 424.63 0.134485E+11 0.00 0.00
Maximum of Months 0.00 0.00 0.105313E+12 0.171532E+11 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: AIRLOOP DATACENTER BASEMENT

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.00 0.00 0.398871E+12 0.178055E+12 0.00 1.09
February 0.00 0.00 0.629697E+12 0.210753E+12 0.00 1.28
March 0.00 0.00 0.999557E+12 0.283310E+12 0.00 0.74
April 0.00 0.00 0.126257E+13 0.327118E+12 0.00 0.30
May 0.00 0.00 0.420477E+12 0.181748E+12 0.00 0.06
June 0.00 0.00 0.733019E+12 0.254997E+12 0.00 0.00
July 0.00 0.00 0.110212E+13 0.357374E+12 0.00 0.00
August 0.00 0.00 0.141031E+13 0.426692E+12 0.00 0.00
September 0.00 0.00 0.424784E+12 0.184464E+12 0.00 0.01
October 0.00 0.00 0.725902E+12 0.238712E+12 0.00 0.25
November 0.00 0.00 0.972830E+12 0.274000E+12 0.00 0.46
December 0.00 0.00 0.129363E+13 0.332063E+12 0.00 1.10
             
Annual Sum or Average 0.00 0.00 0.103738E+14 0.324929E+13 0.00 5.30
Minimum of Months 0.00 0.00 0.398871E+12 0.178055E+12 0.00 0.00
Maximum of Months 0.00 0.00 0.141031E+13 0.426692E+12 0.00 1.28



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: AIRLOOP DATACENTER BOT

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.00 0.00 0.435052E+10 0.240601E+10 0.00 0.00
February 0.00 0.00 0.102150E+11 0.340654E+10 0.00 0.00
March 0.00 0.00 0.186731E+11 0.501426E+10 0.00 0.00
April 0.00 0.00 0.245619E+11 0.599464E+10 0.00 0.00
May 0.00 0.00 0.741662E+10 0.299876E+10 0.00 0.00
June 0.00 0.00 0.143807E+11 0.458461E+10 0.00 0.00
July 0.00 0.00 0.220636E+11 0.665655E+10 0.00 0.00
August 0.00 0.00 0.286522E+11 0.819043E+10 0.00 0.00
September 0.00 0.00 0.773575E+10 0.310007E+10 0.00 0.00
October 0.00 0.00 0.136792E+11 0.417485E+10 0.00 0.00
November 0.00 0.00 0.180308E+11 0.481510E+10 0.00 0.00
December 0.00 0.00 0.243882E+11 0.603716E+10 0.00 0.00
             
Annual Sum or Average 0.00 0.00 0.194148E+12 0.573790E+11 0.00 0.00
Minimum of Months 0.00 0.00 0.435052E+10 0.240601E+10 0.00 0.00
Maximum of Months 0.00 0.00 0.286522E+11 0.819043E+10 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: AIRLOOP DATACENTER MID

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.00 0.00 0.141441E+11 0.173516E+11 0.00 0.00
February 0.00 0.00 0.713430E+11 0.275725E+11 0.00 0.00
March 0.00 0.00 0.158439E+12 0.445086E+11 0.00 0.00
April 0.00 0.00 0.221186E+12 0.551363E+11 0.00 0.00
May 0.00 0.00 0.639190E+11 0.273885E+11 0.00 0.00
June 0.00 0.00 0.135247E+12 0.434392E+11 0.00 0.00
July 0.00 0.00 0.210612E+12 0.636161E+11 0.00 0.00
August 0.00 0.00 0.273174E+12 0.782073E+11 0.00 0.00
September 0.00 0.00 0.685287E+11 0.286115E+11 0.00 0.00
October 0.00 0.00 0.120185E+12 0.380411E+11 0.00 0.00
November 0.00 0.00 0.149596E+12 0.421421E+11 0.00 0.00
December 0.00 0.00 0.203388E+12 0.527694E+11 0.00 0.00
             
Annual Sum or Average 0.00 0.00 0.168976E+13 0.518784E+12 0.00 0.00
Minimum of Months 0.00 0.00 0.141441E+11 0.173516E+11 0.00 0.00
Maximum of Months 0.00 0.00 0.273174E+12 0.782073E+11 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: AIRLOOP DATACENTER TOP

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.00 0.00 0.686950E+09 0.159931E+10 0.00 0.00
February 0.00 0.00 0.529449E+10 0.241658E+10 0.00 0.00
March 0.00 0.00 0.143431E+11 0.421364E+10 0.00 0.00
April 0.00 0.00 0.211427E+11 0.538397E+10 0.00 0.00
May 0.00 0.00 0.596547E+10 0.268645E+10 0.00 0.00
June 0.00 0.00 0.135157E+11 0.437385E+10 0.00 0.00
July 0.00 0.00 0.212104E+11 0.642847E+10 0.00 0.00
August 0.00 0.00 0.274231E+11 0.788332E+10 0.00 0.00
September 0.00 0.00 0.657151E+10 0.283454E+10 0.00 0.00
October 0.00 0.00 0.110312E+11 0.365092E+10 0.00 0.00
November 0.00 0.00 0.131960E+11 0.392956E+10 0.00 0.00
December 0.00 0.00 0.181458E+11 0.492858E+10 0.00 0.00
             
Annual Sum or Average 0.00 0.00 0.158526E+12 0.503292E+11 0.00 0.00
Minimum of Months 0.00 0.00 0.686950E+09 0.159931E+10 0.00 0.00
Maximum of Months 0.00 0.00 0.274231E+11 0.788332E+10 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: VAV_BOT WITH REHEAT

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.390265E+10 30689871.65 0.542208E+10 0.374918E+11 0.00 0.00 0.00 0.00
February 0.419016E+10 33164750.17 0.489082E+10 0.328010E+11 0.00 0.00 0.00 0.00
March 0.651145E+10 0.153871E+10 0.168011E+10 0.141132E+11 0.00 0.00 0.00 0.00
April 0.808852E+10 0.138862E+11 0.295018E+09 0.398833E+10 21530376.72 0.00 0.00 0.00
May 0.841322E+10 0.403927E+11 42558236.87 58139894.94 0.441311E+09 0.00 0.00 0.00
June 0.116895E+11 0.136685E+12 88512668.17 0.00 0.631439E+10 0.00 0.00 0.00
July 0.134503E+11 0.187238E+12 32794241.12 0.00 0.255750E+11 0.00 0.00 0.00
August 0.157286E+11 0.190024E+12 0.143217E+09 0.00 0.253915E+11 0.00 0.00 0.00
September 0.891517E+10 0.913896E+11 27708109.04 3591235.49 0.360062E+10 0.00 0.00 0.00
October 0.839899E+10 0.443280E+11 97138550.36 0.721147E+09 39269874.85 0.00 0.00 0.00
November 0.578395E+10 0.144257E+10 0.105479E+10 0.880171E+10 0.00 0.00 0.00 0.00
December 0.532493E+10 33420230.76 0.255425E+10 0.190119E+11 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.100397E+12 0.707021E+12 0.163290E+11 0.116991E+12 0.613836E+11 0.00 0.00 0.00
Minimum of Months 0.390265E+10 30689871.65 27708109.04 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.157286E+11 0.190024E+12 0.542208E+10 0.374918E+11 0.255750E+11 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: VAV_MID WITH REHEAT

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.367687E+11 83389854.80 0.260927E+12 0.463762E+12 0.00 0.00 0.00 0.00
February 0.333472E+11 0.500964E+09 0.199993E+12 0.437678E+12 0.00 0.00 0.00 0.00
March 0.411791E+11 0.103138E+11 0.818488E+11 0.249147E+12 0.00 0.00 0.00 0.00
April 0.484202E+11 0.100759E+12 0.257834E+11 0.821958E+11 0.255700E+09 0.00 0.00 0.00
May 0.686515E+11 0.351039E+12 0.297589E+09 0.363253E+10 0.440299E+10 0.00 0.00 0.00
June 0.969604E+11 0.116555E+13 0.982523E+09 0.00 0.626279E+11 0.00 0.00 0.00
July 0.109197E+12 0.154987E+13 0.231969E+09 0.00 0.251559E+12 0.00 0.00 0.00
August 0.122056E+12 0.151033E+13 0.162206E+10 0.00 0.249599E+12 0.00 0.00 0.00
September 0.751998E+11 0.810218E+12 0.129535E+09 0.274906E+09 0.369823E+11 0.00 0.00 0.00
October 0.596910E+11 0.363990E+12 0.463845E+10 0.187030E+11 0.532142E+09 0.00 0.00 0.00
November 0.361736E+11 0.112321E+11 0.707604E+11 0.183026E+12 0.00 0.00 0.00 0.00
December 0.332394E+11 0.362224E+09 0.163996E+12 0.346672E+12 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.760884E+12 0.587425E+13 0.811210E+12 0.178509E+13 0.605960E+12 0.00 0.00 0.00
Minimum of Months 0.332394E+11 83389854.80 0.129535E+09 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.122056E+12 0.154987E+13 0.260927E+12 0.463762E+12 0.251559E+12 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: VAV_TOP WITH REHEAT

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.406726E+10 20382840.87 0.451124E+11 0.480416E+11 0.00 0.00 0.00 0.00
February 0.356873E+10 30258728.19 0.365214E+11 0.471892E+11 0.00 0.00 0.00 0.00
March 0.367027E+10 0.810308E+09 0.144762E+11 0.306047E+11 0.00 0.00 0.00 0.00
April 0.419230E+10 0.101328E+11 0.545060E+10 0.110022E+11 5481747.66 0.00 0.00 0.00
May 0.613333E+10 0.360933E+11 0.371595E+09 0.475162E+09 0.306566E+09 0.00 0.00 0.00
June 0.937143E+10 0.123930E+12 59466027.53 0.00 0.531715E+10 0.00 0.00 0.00
July 0.109977E+11 0.169467E+12 47933129.61 0.00 0.228735E+11 0.00 0.00 0.00
August 0.121598E+11 0.163785E+12 0.106413E+09 0.00 0.232158E+11 0.00 0.00 0.00
September 0.676501E+10 0.822274E+11 28184141.14 36655375.93 0.297751E+10 0.00 0.00 0.00
October 0.489145E+10 0.340670E+11 0.176099E+10 0.271961E+10 0.00 0.00 0.00 0.00
November 0.327108E+10 0.856459E+09 0.157293E+11 0.219921E+11 0.00 0.00 0.00 0.00
December 0.357227E+10 31298225.53 0.291728E+11 0.423057E+11 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.726607E+11 0.621451E+12 0.148837E+12 0.204367E+12 0.546960E+11 0.00 0.00 0.00
Minimum of Months 0.327108E+10 20382840.87 28184141.14 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.121598E+11 0.169467E+12 0.451124E+11 0.480416E+11 0.232158E+11 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: CAV_BAS

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.145144E+11 8365601.80 0.00 0.00 0.00 0.00 0.00 0.00
February 0.134485E+11 205417.82 0.00 0.00 0.00 0.00 0.00 0.00
March 0.159212E+11 0.668977E+09 0.00 0.00 0.00 0.00 0.00 0.00
April 0.145132E+11 0.616579E+10 0.00 0.00 0.00 0.00 0.00 0.00
May 0.156173E+11 0.182068E+11 0.00 0.00 0.00 0.00 0.00 0.00
June 0.155782E+11 0.742961E+11 0.00 0.00 0.00 0.00 0.00 0.00
July 0.157418E+11 0.104256E+12 0.00 0.00 0.00 0.00 0.00 0.00
August 0.171532E+11 0.105313E+12 0.00 0.00 0.00 0.00 0.00 0.00
September 0.159599E+11 0.555445E+11 0.00 0.00 0.00 0.00 0.00 0.00
October 0.162209E+11 0.214916E+11 0.00 0.00 0.00 0.00 0.00 0.00
November 0.153069E+11 0.201819E+09 0.00 0.00 0.00 0.00 0.00 0.00
December 0.149719E+11 424.63 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.184948E+12 0.386153E+12 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.134485E+11 424.63 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.171532E+11 0.105313E+12 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: AIRLOOP DATACENTER BASEMENT

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.950830E+11 0.318840E+12 0.00 0.00 0.00 0.292806E+10 0.00 0.00
February 0.858814E+11 0.508268E+12 0.00 0.00 0.00 0.342803E+10 0.00 0.00
March 0.950830E+11 0.813321E+12 0.00 0.00 0.00 0.198195E+10 0.00 0.00
April 0.920158E+11 0.102827E+13 0.00 0.00 0.00 0.796245E+09 0.00 0.00
May 0.950830E+11 0.333982E+12 0.00 0.00 0.00 0.168309E+09 0.00 0.00
June 0.920158E+11 0.570037E+12 0.00 0.00 0.00 0.00 0.00 0.00
July 0.950830E+11 0.839828E+12 0.00 0.00 0.00 0.00 0.00 0.00
August 0.950830E+11 0.107870E+13 0.00 0.00 0.00 0.00 0.00 0.00
September 0.920158E+11 0.332361E+12 0.00 0.00 0.00 25299008.22 0.00 0.00
October 0.950830E+11 0.582945E+12 0.00 0.00 0.00 0.668689E+09 0.00 0.00
November 0.920158E+11 0.792092E+12 0.00 0.00 0.00 0.124096E+10 0.00 0.00
December 0.950830E+11 0.105960E+13 0.00 0.00 0.00 0.293292E+10 0.00 0.00
                 
Annual Sum or Average 0.111953E+13 0.825824E+13 0.00 0.00 0.00 0.141705E+11 0.00 0.00
Minimum of Months 0.858814E+11 0.318840E+12 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.950830E+11 0.107870E+13 0.00 0.00 0.00 0.342803E+10 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: AIRLOOP DATACENTER BOT

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.148012E+10 0.342463E+10 0.00 0.00 0.00 0.00 0.00 0.00
February 0.133688E+10 0.814537E+10 0.00 0.00 0.00 0.00 0.00 0.00
March 0.148012E+10 0.151389E+11 0.00 0.00 0.00 0.00 0.00 0.00
April 0.143238E+10 0.199996E+11 0.00 0.00 0.00 0.00 0.00 0.00
May 0.148012E+10 0.589798E+10 0.00 0.00 0.00 0.00 0.00 0.00
June 0.143238E+10 0.112284E+11 0.00 0.00 0.00 0.00 0.00 0.00
July 0.148012E+10 0.168872E+11 0.00 0.00 0.00 0.00 0.00 0.00
August 0.148012E+10 0.219419E+11 0.00 0.00 0.00 0.00 0.00 0.00
September 0.143238E+10 0.606806E+10 0.00 0.00 0.00 0.00 0.00 0.00
October 0.148012E+10 0.109845E+11 0.00 0.00 0.00 0.00 0.00 0.00
November 0.143238E+10 0.146481E+11 0.00 0.00 0.00 0.00 0.00 0.00
December 0.148012E+10 0.198312E+11 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.174272E+11 0.154196E+12 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.133688E+10 0.342463E+10 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.148012E+10 0.219419E+11 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: AIRLOOP DATACENTER MID

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.141819E+11 0.109744E+11 0.00 0.00 0.00 0.00 0.00 0.00
February 0.128095E+11 0.565800E+11 0.00 0.00 0.00 0.00 0.00 0.00
March 0.141819E+11 0.128112E+12 0.00 0.00 0.00 0.00 0.00 0.00
April 0.137244E+11 0.179774E+12 0.00 0.00 0.00 0.00 0.00 0.00
May 0.141819E+11 0.507124E+11 0.00 0.00 0.00 0.00 0.00 0.00
June 0.137244E+11 0.105533E+12 0.00 0.00 0.00 0.00 0.00 0.00
July 0.141819E+11 0.161178E+12 0.00 0.00 0.00 0.00 0.00 0.00
August 0.141819E+11 0.209148E+12 0.00 0.00 0.00 0.00 0.00 0.00
September 0.137244E+11 0.536416E+11 0.00 0.00 0.00 0.00 0.00 0.00
October 0.141819E+11 0.963262E+11 0.00 0.00 0.00 0.00 0.00 0.00
November 0.137244E+11 0.121178E+12 0.00 0.00 0.00 0.00 0.00 0.00
December 0.141819E+11 0.164801E+12 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.166981E+12 0.133796E+13 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.128095E+11 0.109744E+11 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.141819E+11 0.209148E+12 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: AIRLOOP DATACENTER TOP

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.144359E+10 0.531228E+09 0.00 0.00 0.00 0.00 0.00 0.00
February 0.130389E+10 0.418180E+10 0.00 0.00 0.00 0.00 0.00 0.00
March 0.144359E+10 0.115731E+11 0.00 0.00 0.00 0.00 0.00 0.00
April 0.139702E+10 0.171558E+11 0.00 0.00 0.00 0.00 0.00 0.00
May 0.144359E+10 0.472261E+10 0.00 0.00 0.00 0.00 0.00 0.00
June 0.139702E+10 0.105389E+11 0.00 0.00 0.00 0.00 0.00 0.00
July 0.144359E+10 0.162256E+11 0.00 0.00 0.00 0.00 0.00 0.00
August 0.144359E+10 0.209833E+11 0.00 0.00 0.00 0.00 0.00 0.00
September 0.139702E+10 0.513398E+10 0.00 0.00 0.00 0.00 0.00 0.00
October 0.144359E+10 0.882384E+10 0.00 0.00 0.00 0.00 0.00 0.00
November 0.139702E+10 0.106634E+11 0.00 0.00 0.00 0.00 0.00 0.00
December 0.144359E+10 0.146609E+11 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.169971E+11 0.125194E+12 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.130389E+10 0.531228E+09 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.144359E+10 0.209833E+11 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: VAV_BOT WITH REHEAT

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.390265E+10 0.542208E+10 30689871.65 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.419016E+10 0.489082E+10 33164750.17 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.651145E+10 0.168011E+10 0.153871E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.808852E+10 0.295018E+09 0.138862E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.841322E+10 42558236.87 0.403927E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.116895E+11 88512668.17 0.136685E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.134503E+11 32794241.12 0.187238E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.157286E+11 0.143217E+09 0.190024E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.891517E+10 27708109.04 0.913896E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.839899E+10 97138550.36 0.443280E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.578395E+10 0.105479E+10 0.144257E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.532493E+10 0.255425E+10 33420230.76 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.100397E+12 0.163290E+11 0.707021E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.390265E+10 27708109.04 30689871.65 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.157286E+11 0.542208E+10 0.190024E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: VAV_MID WITH REHEAT

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.367687E+11 0.260927E+12 83389854.80 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.333472E+11 0.199993E+12 0.500964E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.411791E+11 0.818488E+11 0.103138E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.484202E+11 0.257834E+11 0.100759E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.686515E+11 0.297589E+09 0.351039E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.969604E+11 0.982523E+09 0.116555E+13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.109197E+12 0.231969E+09 0.154987E+13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.122056E+12 0.162206E+10 0.151033E+13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.751998E+11 0.129535E+09 0.810218E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.596910E+11 0.463845E+10 0.363990E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.361736E+11 0.707604E+11 0.112321E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.332394E+11 0.163996E+12 0.362224E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.760884E+12 0.811210E+12 0.587425E+13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.332394E+11 0.129535E+09 83389854.80 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.122056E+12 0.260927E+12 0.154987E+13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: VAV_TOP WITH REHEAT

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.406726E+10 0.451124E+11 20382840.87 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.356873E+10 0.365214E+11 30258728.19 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.367027E+10 0.144762E+11 0.810308E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.419230E+10 0.545060E+10 0.101328E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.613333E+10 0.371595E+09 0.360933E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.937143E+10 59466027.53 0.123930E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.109977E+11 47933129.61 0.169467E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.121598E+11 0.106413E+09 0.163785E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.676501E+10 28184141.14 0.822274E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.489145E+10 0.176099E+10 0.340670E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.327108E+10 0.157293E+11 0.856459E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.357227E+10 0.291728E+11 31298225.53 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.726607E+11 0.148837E+12 0.621451E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.327108E+10 28184141.14 20382840.87 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.121598E+11 0.451124E+11 0.169467E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: CAV_BAS

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.145144E+11 0.00 8365601.80 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.134485E+11 0.00 205417.82 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.159212E+11 0.00 0.668977E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.145132E+11 0.00 0.616579E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.156173E+11 0.00 0.182068E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.155782E+11 0.00 0.742961E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.157418E+11 0.00 0.104256E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.171532E+11 0.00 0.105313E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.159599E+11 0.00 0.555445E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.162209E+11 0.00 0.214916E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.153069E+11 0.00 0.201819E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.149719E+11 0.00 424.63 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.184948E+12 0.00 0.386153E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.134485E+11 0.00 424.63 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.171532E+11 0.00 0.105313E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: AIRLOOP DATACENTER BASEMENT

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.950830E+11 0.00 0.398871E+12 0.00 0.800311E+11 0.00 0.00 0.00 0.294124E+10 0.00 0.00 0.00
February 0.858814E+11 0.00 0.629697E+12 0.00 0.121428E+12 0.00 0.00 0.00 0.344346E+10 0.00 0.00 0.00
March 0.950830E+11 0.00 0.999557E+12 0.00 0.186236E+12 0.00 0.00 0.00 0.199087E+10 0.00 0.00 0.00
April 0.920158E+11 0.00 0.126257E+13 0.00 0.234302E+12 0.00 0.00 0.00 0.799829E+09 0.00 0.00 0.00
May 0.950830E+11 0.00 0.420477E+12 0.00 0.864955E+11 0.00 0.00 0.00 0.169066E+09 0.00 0.00 0.00
June 0.920158E+11 0.00 0.733019E+12 0.00 0.162982E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.950830E+11 0.00 0.110212E+13 0.00 0.262291E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.950830E+11 0.00 0.141031E+13 0.00 0.331609E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.920158E+11 0.00 0.424784E+12 0.00 0.924229E+11 0.00 0.00 0.00 25412889.31 0.00 0.00 0.00
October 0.950830E+11 0.00 0.725902E+12 0.00 0.142957E+12 0.00 0.00 0.00 0.671699E+09 0.00 0.00 0.00
November 0.920158E+11 0.00 0.972830E+12 0.00 0.180738E+12 0.00 0.00 0.00 0.124655E+10 0.00 0.00 0.00
December 0.950830E+11 0.00 0.129363E+13 0.00 0.234034E+12 0.00 0.00 0.00 0.294612E+10 0.00 0.00 0.00
                         
Annual Sum or Average 0.111953E+13 0.00 0.103738E+14 0.00 0.211553E+13 0.00 0.00 0.00 0.142343E+11 0.00 0.00 0.00
Minimum of Months 0.858814E+11 0.00 0.398871E+12 0.00 0.800311E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.950830E+11 0.00 0.141031E+13 0.00 0.331609E+12 0.00 0.00 0.00 0.344346E+10 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: AIRLOOP DATACENTER BOT

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.148012E+10 0.00 0.435052E+10 0.00 0.925890E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.133688E+10 0.00 0.102150E+11 0.00 0.206965E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.148012E+10 0.00 0.186731E+11 0.00 0.353414E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.143238E+10 0.00 0.245619E+11 0.00 0.456226E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.148012E+10 0.00 0.741662E+10 0.00 0.151864E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.143238E+10 0.00 0.143807E+11 0.00 0.315223E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.148012E+10 0.00 0.220636E+11 0.00 0.517643E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.148012E+10 0.00 0.286522E+11 0.00 0.671031E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.143238E+10 0.00 0.773575E+10 0.00 0.166769E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.148012E+10 0.00 0.136792E+11 0.00 0.269473E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.143238E+10 0.00 0.180308E+11 0.00 0.338272E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.148012E+10 0.00 0.243882E+11 0.00 0.455704E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.174272E+11 0.00 0.194148E+12 0.00 0.399517E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.133688E+10 0.00 0.435052E+10 0.00 0.925890E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.148012E+10 0.00 0.286522E+11 0.00 0.671031E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: AIRLOOP DATACENTER MID

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.141819E+11 0.00 0.141441E+11 0.00 0.316970E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.128095E+11 0.00 0.713430E+11 0.00 0.147630E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.141819E+11 0.00 0.158439E+12 0.00 0.303267E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.137244E+11 0.00 0.221186E+12 0.00 0.414119E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.141819E+11 0.00 0.639190E+11 0.00 0.132065E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.137244E+11 0.00 0.135247E+12 0.00 0.297148E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.141819E+11 0.00 0.210612E+12 0.00 0.494342E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.141819E+11 0.00 0.273174E+12 0.00 0.640253E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.137244E+11 0.00 0.685287E+11 0.00 0.148871E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.141819E+11 0.00 0.120185E+12 0.00 0.238592E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.137244E+11 0.00 0.149596E+12 0.00 0.284177E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.141819E+11 0.00 0.203388E+12 0.00 0.385875E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.166981E+12 0.00 0.168976E+13 0.00 0.351804E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.128095E+11 0.00 0.141441E+11 0.00 0.316970E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.141819E+11 0.00 0.273174E+12 0.00 0.640253E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: AIRLOOP DATACENTER TOP

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.144359E+10 0.00 0.686950E+09 0.00 0.155722E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.130389E+10 0.00 0.529449E+10 0.00 0.111269E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.144359E+10 0.00 0.143431E+11 0.00 0.277005E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.139702E+10 0.00 0.211427E+11 0.00 0.398694E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.144359E+10 0.00 0.596547E+10 0.00 0.124286E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.139702E+10 0.00 0.135157E+11 0.00 0.297683E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.144359E+10 0.00 0.212104E+11 0.00 0.498488E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.144359E+10 0.00 0.274231E+11 0.00 0.643973E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.139702E+10 0.00 0.657151E+10 0.00 0.143752E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.144359E+10 0.00 0.110312E+11 0.00 0.220733E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.139702E+10 0.00 0.131960E+11 0.00 0.253254E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.144359E+10 0.00 0.181458E+11 0.00 0.348499E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.169971E+11 0.00 0.158526E+12 0.00 0.333321E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.130389E+10 0.00 0.686950E+09 0.00 0.155722E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.144359E+10 0.00 0.274231E+11 0.00 0.643973E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: BASEMENT

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.223151E+10 0.00 0.00 0.104269E+09 0.00 0.00 0.650022E+11 0.00 0.50
February 0.584341E+09 0.00 0.00 0.111565E+09 0.00 0.00 0.631266E+11 0.00 0.48
March 0.393806E+09 0.00 0.00 0.142807E+09 0.00 0.00 0.793304E+11 0.00 0.76
April 0.389750E+09 18383513.62 0.00 0.118375E+09 0.00 0.00 0.697398E+11 0.00 1.01
May 0.182600E+09 0.240169E+09 0.00 0.110689E+09 0.00 0.00 0.628199E+11 0.00 1.41
June 0.135901E+09 0.676799E+10 0.00 59784995.65 37159442.28 0.00 0.170506E+11 0.00 0.99
July 53054693.04 0.207295E+11 0.00 13439183.17 0.122957E+09 0.00 0.149585E+10 0.00 0.40
August 60559898.56 0.174555E+11 0.00 45061011.06 0.145293E+09 0.00 0.737775E+10 0.00 0.74
September 0.251588E+09 0.449041E+10 0.00 93660091.90 4261879.20 0.00 0.345547E+11 0.00 1.23
October 0.488546E+09 0.221182E+09 0.00 0.139910E+09 0.00 0.00 0.669948E+11 0.00 1.35
November 0.467843E+09 0.00 0.00 0.143788E+09 0.00 0.00 0.812251E+11 0.00 0.90
December 0.598474E+09 0.00 0.00 0.142211E+09 0.00 0.00 0.767439E+11 0.00 0.60
                   
Annual Sum or Average 0.583798E+10 0.499232E+11 0.00 0.122556E+10 0.309671E+09 0.00 0.625461E+12 0.00 0.87
Minimum of Months 53054693.04 0.00 0.00 13439183.17 0.00 0.00 0.149585E+10 0.00 0.40
Maximum of Months 0.223151E+10 0.207295E+11 0.00 0.143788E+09 0.145293E+09 0.00 0.812251E+11 0.00 1.41



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: CORE_BOTTOM

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.785269E+10 0.00 0.00 53182381.06 0.00 0.00 0.339682E+11 0.00 0.46
February 0.392957E+10 0.00 0.00 66930753.20 0.00 0.00 0.392150E+11 0.00 0.47
March 0.218277E+10 0.00 0.00 0.112874E+09 0.00 0.00 0.596888E+11 0.00 0.64
April 0.447241E+10 14451316.18 0.00 0.102234E+09 0.00 0.00 0.560444E+11 0.00 0.86
May 0.280399E+10 0.213160E+09 0.00 91209888.56 0.00 0.00 0.444126E+11 0.00 0.98
June 0.144743E+10 0.758754E+10 0.00 42875133.09 0.153906E+09 0.00 0.991810E+10 0.00 0.75
July 0.224601E+09 0.149611E+11 0.00 3214905.70 0.256672E+09 0.00 0.317863E+09 0.00 0.41
August 0.227568E+10 0.989599E+10 0.00 32132068.35 0.215124E+09 0.00 0.471203E+10 0.00 0.70
September 0.196891E+10 0.497651E+10 0.00 63859085.76 48287869.25 0.00 0.216691E+11 0.00 0.81
October 0.351492E+10 0.774774E+09 0.00 98899465.52 0.00 0.00 0.426845E+11 0.00 0.88
November 0.166466E+10 0.00 0.00 0.101588E+09 0.00 0.00 0.570998E+11 0.00 0.67
December 0.236404E+10 0.00 0.00 0.100043E+09 0.00 0.00 0.540578E+11 0.00 0.52
                   
Annual Sum or Average 0.347017E+11 0.384235E+11 0.00 0.869043E+09 0.673989E+09 0.00 0.423788E+12 0.00 0.68
Minimum of Months 0.224601E+09 0.00 0.00 3214905.70 0.00 0.00 0.317863E+09 0.00 0.41
Maximum of Months 0.785269E+10 0.149611E+11 0.00 0.112874E+09 0.256672E+09 0.00 0.596888E+11 0.00 0.98



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: CORE_MID

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.223248E+12 0.00 0.00 62174518.74 0.00 0.797225E+10 0.602430E+11 0.00 0.43
February 0.212729E+12 0.00 0.00 89795321.47 0.00 0.154051E+10 0.833543E+11 0.00 0.44
March 0.152506E+12 0.00 0.00 0.359908E+09 0.00 0.00 0.240031E+12 0.00 0.49
April 0.930510E+11 91849433.86 0.00 0.450410E+09 0.00 0.00 0.290124E+12 0.00 0.60
May 0.345919E+11 0.198918E+10 0.00 0.635673E+09 0.00 0.00 0.338789E+12 0.00 0.81
June 0.907450E+10 0.709451E+11 0.00 0.346288E+09 0.153249E+10 0.00 0.798795E+11 0.00 0.65
July 0.291724E+09 0.141925E+12 0.00 28094714.04 0.252975E+10 0.00 0.334509E+10 0.00 0.38
August 0.457208E+10 0.916847E+11 0.00 0.283629E+09 0.202693E+10 0.00 0.415516E+11 0.00 0.57
September 0.227481E+11 0.475365E+11 0.00 0.460108E+09 0.498147E+09 0.00 0.163550E+12 0.00 0.69
October 0.472636E+11 0.722881E+10 0.00 0.574056E+09 0.00 0.00 0.281261E+12 0.00 0.67
November 0.121104E+12 0.00 0.00 0.317694E+09 0.00 0.00 0.237608E+12 0.00 0.50
December 0.192193E+12 0.00 0.00 0.156358E+09 0.00 0.00 0.143077E+12 0.00 0.43
                   
Annual Sum or Average 0.111337E+13 0.361401E+12 0.00 0.376419E+10 0.658732E+10 0.951276E+10 0.196281E+13 0.00 0.56
Minimum of Months 0.291724E+09 0.00 0.00 28094714.04 0.00 0.00 0.334509E+10 0.00 0.38
Maximum of Months 0.223248E+12 0.141925E+12 0.00 0.635673E+09 0.252975E+10 0.797225E+10 0.338789E+12 0.00 0.81



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: CORE_TOP

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.209173E+11 0.00 0.00 713555.92 0.00 0.207057E+10 0.843243E+09 0.00 0.41
February 0.194906E+11 0.00 0.00 1121448.38 0.00 0.139004E+10 0.154562E+10 0.00 0.41
March 0.203118E+11 0.00 0.00 11948342.44 0.00 0.330139E+09 0.110455E+11 0.00 0.47
April 0.126723E+11 1775784.20 0.00 28604151.06 0.00 87345756.86 0.205790E+11 0.00 0.58
May 0.821150E+10 0.185915E+09 0.00 49879185.31 0.00 0.00 0.275503E+11 0.00 0.79
June 0.120249E+10 0.697714E+10 0.00 31601015.11 0.142153E+09 0.00 0.804123E+10 0.00 0.66
July 0.110681E+09 0.146176E+11 0.00 3267105.13 0.254559E+09 0.00 0.325561E+09 0.00 0.40
August 0.570441E+09 0.925328E+10 0.00 28275892.71 0.212666E+09 0.00 0.399499E+10 0.00 0.60
September 0.451040E+10 0.475442E+10 0.00 35367335.84 43318310.50 0.00 0.127781E+11 0.00 0.67
October 0.103336E+11 0.523346E+09 0.00 33952821.85 0.00 2961045.13 0.172111E+11 0.00 0.62
November 0.178389E+11 0.00 0.00 9502031.88 0.00 0.619890E+09 0.906338E+10 0.00 0.45
December 0.215869E+11 0.00 0.00 1015094.88 0.00 0.779873E+09 0.170404E+10 0.00 0.42
                   
Annual Sum or Average 0.137757E+12 0.363135E+11 0.00 0.235248E+09 0.652697E+09 0.528081E+10 0.114682E+12 0.00 0.54
Minimum of Months 0.110681E+09 0.00 0.00 713555.92 0.00 0.00 0.325561E+09 0.00 0.40
Maximum of Months 0.215869E+11 0.146176E+11 0.00 49879185.31 0.254559E+09 0.207057E+10 0.275503E+11 0.00 0.79



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.342079E+10 0.00 0.00 0.00 0.00 0.654196E+09 0.00 0.00 0.37
February 0.336968E+10 0.00 0.00 11962.52 0.00 0.475552E+09 37861754.68 0.00 0.36
March 0.328352E+10 0.00 0.00 2544114.56 0.00 2000058.19 0.192944E+10 0.00 0.45
April 0.213822E+10 2278046.06 0.00 6065072.59 0.00 0.00 0.385431E+10 0.00 0.74
May 0.883457E+09 41089584.14 0.00 9656731.86 0.00 0.00 0.495981E+10 0.00 1.04
June 0.225368E+09 0.138533E+10 0.00 5657381.63 19337736.91 0.00 0.140009E+10 0.00 0.97
July 27663942.81 0.282021E+10 0.00 692078.33 32250001.84 0.00 51612295.70 0.00 0.61
August 0.310687E+09 0.187703E+10 0.00 4355680.09 27029608.52 0.00 0.604500E+09 0.00 0.92
September 0.606956E+09 0.738549E+09 0.00 6059576.03 6067212.97 0.00 0.211088E+10 0.00 0.84
October 0.149780E+10 0.110776E+09 0.00 6238006.68 0.00 0.00 0.299232E+10 0.00 0.74
November 0.273964E+10 0.00 0.00 2351964.13 0.00 16756722.20 0.198145E+10 0.00 0.45
December 0.407171E+10 0.00 0.00 267127.63 0.00 4896682.81 0.325624E+09 0.00 0.34
                   
Annual Sum or Average 0.225755E+11 0.697527E+10 0.00 43899696.05 84684560.23 0.115340E+10 0.202479E+11 0.00 0.65
Minimum of Months 27663942.81 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.34
Maximum of Months 0.407171E+10 0.282021E+10 0.00 9656731.86 32250001.84 0.654196E+09 0.495981E+10 0.00 1.04



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.348587E+10 0.00 0.00 542698.60 0.00 0.687353E+09 0.306601E+09 0.00 0.63
February 0.338362E+10 0.00 0.00 901205.23 0.00 0.459283E+09 0.480886E+09 0.00 0.61
March 0.331328E+10 0.00 0.00 5076995.25 0.00 65850317.47 0.290238E+10 0.00 0.80
April 0.264591E+10 1693712.29 0.00 7526818.44 0.00 0.00 0.402570E+10 0.00 1.23
May 0.121646E+10 37283423.62 0.00 12055996.41 0.00 0.00 0.515803E+10 0.00 1.68
June 0.250724E+09 0.103990E+10 0.00 5522998.69 24810717.00 0.00 0.153236E+10 0.00 1.34
July 32929124.25 0.214582E+10 0.00 579239.00 34946880.44 0.00 63902933.60 0.00 0.78
August 0.356422E+09 0.152467E+10 0.00 4543008.20 29289936.23 0.00 0.717811E+09 0.00 1.33
September 0.746937E+09 0.584189E+09 0.00 8132274.15 20467953.63 0.00 0.232436E+10 0.00 1.30
October 0.181894E+10 89063529.13 0.00 7046336.49 0.00 0.00 0.327032E+10 0.00 1.22
November 0.328000E+10 0.00 0.00 2474576.29 0.00 43242952.57 0.172224E+10 0.00 0.72
December 0.420472E+10 0.00 0.00 744936.89 0.00 99381088.75 0.536128E+09 0.00 0.58
                   
Annual Sum or Average 0.247358E+11 0.542262E+10 0.00 55147083.64 0.109515E+09 0.135511E+10 0.230407E+11 0.00 1.02
Minimum of Months 32929124.25 0.00 0.00 542698.60 0.00 0.00 63902933.60 0.00 0.58
Maximum of Months 0.420472E+10 0.214582E+10 0.00 12055996.41 34946880.44 0.687353E+09 0.515803E+10 0.00 1.68



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.295015E+10 0.00 0.00 6579953.54 0.00 0.754239E+09 0.374688E+10 0.00 0.62
February 0.253336E+10 0.00 0.00 9173754.96 0.00 0.511055E+09 0.486206E+10 0.00 0.66
March 0.312015E+10 0.00 0.00 13327722.00 0.00 0.110646E+09 0.807377E+10 0.00 0.95
April 0.270992E+10 4321470.69 0.00 11282007.24 0.00 0.00 0.654000E+10 0.00 1.18
May 0.158324E+10 52705859.36 0.00 11999118.89 0.00 0.00 0.566691E+10 0.00 1.32
June 0.328538E+09 0.155237E+10 0.00 6027825.61 24250348.82 0.00 0.146065E+10 0.00 1.10
July 37019049.18 0.317285E+10 0.00 928316.36 40442881.06 0.00 46920157.35 0.00 0.71
August 0.383239E+09 0.250967E+10 0.00 7169528.13 33896284.66 0.00 0.783277E+09 0.00 1.28
September 0.681767E+09 0.104830E+10 0.00 18096943.68 7608544.45 0.00 0.405747E+10 0.00 1.48
October 0.115960E+10 0.293554E+09 0.00 23165643.22 0.00 0.00 0.910037E+10 0.00 1.68
November 0.253039E+10 0.00 0.00 10813969.81 0.00 85415977.00 0.712812E+10 0.00 0.93
December 0.331679E+10 0.00 0.00 10205545.29 0.00 0.197397E+09 0.527375E+10 0.00 0.64
                   
Annual Sum or Average 0.213342E+11 0.863377E+10 0.00 0.128770E+09 0.106198E+09 0.165875E+10 0.567402E+11 0.00 1.05
Minimum of Months 37019049.18 0.00 0.00 928316.36 0.00 0.00 46920157.35 0.00 0.62
Maximum of Months 0.331679E+10 0.317285E+10 0.00 23165643.22 40442881.06 0.754239E+09 0.910037E+10 0.00 1.68



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.440861E+10 0.00 0.00 1050003.13 0.00 0.304139E+09 0.818056E+09 0.00 0.77
February 0.368733E+10 0.00 0.00 2341327.17 0.00 80991778.91 0.187024E+10 0.00 0.79
March 0.192357E+10 0.00 0.00 10423209.52 0.00 0.00 0.706085E+10 0.00 1.19
April 0.878140E+09 4402934.85 0.00 17143319.86 0.00 0.00 0.901782E+10 0.00 1.90
May 0.796794E+09 53334656.94 0.00 14111171.02 0.00 0.00 0.648161E+10 0.00 2.01
June 0.211874E+09 0.163897E+10 0.00 8077309.28 18648586.54 0.00 0.174730E+10 0.00 1.82
July 28500983.93 0.332598E+10 0.00 1772132.48 21226024.93 0.00 62095421.86 0.00 1.13
August 0.307727E+09 0.259738E+10 0.00 7830729.93 15044343.52 0.00 0.924234E+09 0.00 1.98
September 0.565114E+09 0.853055E+09 0.00 10124401.45 5998959.97 0.00 0.282168E+10 0.00 1.62
October 0.955917E+09 0.172821E+09 0.00 12318975.54 0.00 0.00 0.563264E+10 0.00 1.69
November 0.197609E+10 0.00 0.00 6166554.23 0.00 0.00 0.486715E+10 0.00 1.01
December 0.270280E+10 0.00 0.00 4609098.26 0.00 0.00 0.378994E+10 0.00 0.77
                   
Annual Sum or Average 0.184425E+11 0.864594E+10 0.00 95968231.86 60917914.96 0.385131E+09 0.450936E+11 0.00 1.39
Minimum of Months 28500983.93 0.00 0.00 1050003.13 0.00 0.00 62095421.86 0.00 0.77
Maximum of Months 0.440861E+10 0.332598E+10 0.00 17143319.86 21226024.93 0.304139E+09 0.901782E+10 0.00 2.01



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.107008E+11 0.00 0.00 0.00 0.00 0.274471E+11 0.00 0.00 0.44
February 0.127285E+11 0.00 0.00 0.00 0.00 0.256816E+11 0.00 0.00 0.44
March 0.327187E+11 0.00 0.00 1352861.89 0.00 0.101018E+11 0.121676E+10 0.00 0.44
April 0.276838E+11 14357528.59 0.00 17868400.50 0.00 0.275131E+10 0.105714E+11 0.00 0.54
May 0.144760E+11 0.410057E+09 0.00 61992682.48 0.00 0.00 0.302262E+11 0.00 0.84
June 0.182420E+10 0.134926E+11 0.00 44584262.88 0.192779E+09 0.00 0.109423E+11 0.00 0.87
July 63946864.42 0.283499E+11 0.00 3839303.70 0.318229E+09 0.00 0.490612E+09 0.00 0.62
August 0.111705E+10 0.186209E+11 0.00 34091436.87 0.254977E+09 0.00 0.477175E+10 0.00 0.79
September 0.951942E+10 0.701542E+10 0.00 37740780.70 76944488.88 0.00 0.119763E+11 0.00 0.71
October 0.226992E+11 0.987833E+09 0.00 21364590.34 0.00 0.555975E+09 0.986836E+10 0.00 0.56
November 0.278580E+11 0.00 0.00 929808.14 0.00 0.969922E+10 0.140309E+10 0.00 0.43
December 0.189638E+11 0.00 0.00 0.00 0.00 0.222038E+11 0.00 0.00 0.42
                   
Annual Sum or Average 0.180353E+12 0.688910E+11 0.00 0.223764E+09 0.842929E+09 0.984408E+11 0.814668E+11 0.00 0.59
Minimum of Months 63946864.42 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.42
Maximum of Months 0.327187E+11 0.283499E+11 0.00 61992682.48 0.318229E+09 0.274471E+11 0.302262E+11 0.00 0.87



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.175146E+11 0.00 0.00 13573.58 0.00 0.255285E+11 67652727.70 0.00 0.77
February 0.220184E+11 0.00 0.00 782537.62 0.00 0.209254E+11 0.599728E+09 0.00 0.78
March 0.332892E+11 0.00 0.00 23476852.03 0.00 0.792131E+10 0.144138E+11 0.00 0.86
April 0.262675E+11 14582584.53 0.00 52615619.62 0.00 0.280912E+10 0.278857E+11 0.00 1.14
May 0.192101E+11 0.413540E+09 0.00 0.101324E+09 0.00 0.00 0.406813E+11 0.00 1.63
June 0.237187E+10 0.110201E+11 0.00 57596953.87 0.588984E+09 0.00 0.146295E+11 0.00 1.39
July 86735075.65 0.248372E+11 0.00 5148923.64 0.520687E+09 0.00 0.744119E+09 0.00 0.90
August 0.115860E+10 0.181530E+11 0.00 51693906.27 0.300336E+09 0.00 0.779906E+10 0.00 1.39
September 0.103561E+11 0.580439E+10 0.00 73470335.23 0.767780E+09 0.00 0.182895E+11 0.00 1.28
October 0.214904E+11 0.927778E+09 0.00 45809519.97 4232687.10 0.436908E+09 0.222460E+11 0.00 1.14
November 0.323320E+11 0.00 0.00 6002563.55 0.00 0.851512E+10 0.537618E+10 0.00 0.79
December 0.266839E+11 0.00 0.00 176915.18 0.00 0.212309E+11 0.170383E+09 0.00 0.77
                   
Annual Sum or Average 0.212779E+12 0.611706E+11 0.00 0.418111E+09 0.218202E+10 0.873673E+11 0.152903E+12 0.00 1.07
Minimum of Months 86735075.65 0.00 0.00 13573.58 0.00 0.00 67652727.70 0.00 0.77
Maximum of Months 0.332892E+11 0.248372E+11 0.00 0.101324E+09 0.767780E+09 0.255285E+11 0.406813E+11 0.00 1.63



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.188255E+11 0.00 0.00 52110493.11 0.00 0.178341E+11 0.262968E+11 0.00 0.69
February 0.190409E+11 0.00 0.00 75957922.43 0.00 0.143011E+11 0.379606E+11 0.00 0.77
March 0.278594E+11 0.00 0.00 0.109529E+09 0.00 0.661377E+10 0.647593E+11 0.00 0.96
April 0.269106E+11 39427086.90 0.00 82461725.39 0.00 0.285431E+10 0.460087E+11 0.00 1.04
May 0.194421E+11 0.552986E+09 0.00 95863082.02 0.00 0.00 0.444842E+11 0.00 1.20
June 0.379436E+10 0.156922E+11 0.00 51971608.10 0.247878E+09 0.00 0.116900E+11 0.00 1.04
July 93278568.04 0.330721E+11 0.00 6580648.67 0.410749E+09 0.00 0.456496E+09 0.00 0.73
August 0.139346E+10 0.268910E+11 0.00 67176030.43 0.324712E+09 0.00 0.702830E+10 0.00 1.23
September 0.872514E+10 0.110096E+11 0.00 0.181147E+09 0.189915E+09 0.00 0.353480E+11 0.00 1.46
October 0.133392E+11 0.338202E+10 0.00 0.221457E+09 0.00 16598119.44 0.803649E+11 0.00 1.63
November 0.233863E+11 0.00 0.00 83403669.82 0.00 0.528861E+10 0.538998E+11 0.00 0.92
December 0.219085E+11 0.00 0.00 71991204.47 0.00 0.143143E+11 0.383016E+11 0.00 0.72
                   
Annual Sum or Average 0.184719E+12 0.906394E+11 0.00 0.109965E+10 0.117325E+10 0.612228E+11 0.446599E+12 0.00 1.03
Minimum of Months 93278568.04 0.00 0.00 6580648.67 0.00 0.00 0.456496E+09 0.00 0.69
Maximum of Months 0.278594E+11 0.330721E+11 0.00 0.221457E+09 0.410749E+09 0.178341E+11 0.803649E+11 0.00 1.63



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.211075E+11 0.00 0.00 1705793.39 0.00 0.227015E+11 0.138121E+10 0.00 0.81
February 0.232227E+11 0.00 0.00 5121660.84 0.00 0.196621E+11 0.365655E+10 0.00 0.83
March 0.369170E+11 0.00 0.00 27328873.06 0.00 0.676081E+10 0.188083E+11 0.00 0.97
April 0.305743E+11 21661045.88 0.00 56323669.29 0.00 0.194738E+10 0.282619E+11 0.00 1.25
May 0.187253E+11 0.524857E+09 0.00 87865898.38 0.00 0.00 0.386349E+11 0.00 1.63
June 0.317417E+10 0.143338E+11 0.00 51008452.89 0.176154E+09 0.00 0.109564E+11 0.00 1.48
July 66300652.10 0.280023E+11 0.00 7833281.16 0.236792E+09 0.00 0.373887E+09 0.00 0.96
August 0.122908E+10 0.215356E+11 0.00 38932105.34 0.214368E+09 0.00 0.493686E+10 0.00 1.45
September 0.115755E+11 0.761789E+10 0.00 64666626.51 0.256018E+09 0.00 0.154572E+11 0.00 1.34
October 0.252886E+11 0.158451E+10 0.00 45153546.66 0.00 0.257504E+09 0.212145E+11 0.00 1.25
November 0.351968E+11 0.00 0.00 6135124.16 0.00 0.833908E+10 0.535938E+10 0.00 0.84
December 0.311476E+11 0.00 0.00 1236533.18 0.00 0.180150E+11 0.118505E+10 0.00 0.80
                   
Annual Sum or Average 0.238225E+12 0.736206E+11 0.00 0.393312E+09 0.883333E+09 0.776833E+11 0.150226E+12 0.00 1.14
Minimum of Months 66300652.10 0.00 0.00 1236533.18 0.00 0.00 0.373887E+09 0.00 0.80
Maximum of Months 0.369170E+11 0.280023E+11 0.00 87865898.38 0.256018E+09 0.227015E+11 0.386349E+11 0.00 1.63



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.601158E+09 0.00 0.00 0.00 0.00 0.266677E+10 0.00 0.00 0.44
February 0.589367E+09 0.00 0.00 0.00 0.00 0.251907E+10 0.00 0.00 0.45
March 0.221531E+10 0.00 0.00 87203.11 0.00 0.157176E+10 0.108741E+09 0.00 0.46
April 0.237642E+10 264862.58 0.00 1685429.53 0.00 0.567034E+09 0.944645E+09 0.00 0.55
May 0.164097E+10 36587827.91 0.00 5572000.41 0.00 31507453.66 0.279957E+10 0.00 0.83
June 0.255193E+09 0.128636E+10 0.00 4419778.73 20727277.86 0.00 0.110897E+10 0.00 0.88
July 11089814.69 0.283371E+10 0.00 928655.31 31955754.77 0.00 55455845.19 0.00 0.62
August 0.126208E+09 0.181882E+10 0.00 3884647.37 29921145.19 0.00 0.505957E+09 0.00 0.83
September 0.948081E+09 0.680389E+09 0.00 3357641.17 21004500.14 0.00 0.113371E+10 0.00 0.70
October 0.211080E+10 70097116.32 0.00 1683734.50 315463.13 0.185627E+09 0.752947E+09 0.00 0.56
November 0.197135E+10 0.00 0.00 22066.25 0.00 0.139974E+10 30297381.94 0.00 0.44
December 0.633756E+09 0.00 0.00 0.00 0.00 0.255560E+10 0.00 0.00 0.43
                   
Annual Sum or Average 0.134797E+11 0.672622E+10 0.00 21641156.38 0.103924E+09 0.114971E+11 0.744029E+10 0.00 0.60
Minimum of Months 11089814.69 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.43
Maximum of Months 0.237642E+10 0.283371E+10 0.00 5572000.41 31955754.77 0.266677E+10 0.279957E+10 0.00 0.88



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.113282E+10 0.00 0.00 0.00 0.00 0.240074E+10 0.00 0.00 0.75
February 0.139594E+10 0.00 0.00 111.08 0.00 0.192354E+10 3175435.06 0.00 0.75
March 0.249301E+10 0.00 0.00 1500834.55 0.00 0.117512E+10 0.982655E+09 0.00 0.85
April 0.215177E+10 270101.99 0.00 4454833.54 0.00 0.549261E+09 0.252024E+10 0.00 1.13
May 0.191984E+10 36436582.65 0.00 10317229.79 0.00 26649490.25 0.400661E+10 0.00 1.63
June 0.240205E+09 0.106120E+10 0.00 5695177.54 72790884.53 0.00 0.152016E+10 0.00 1.42
July 14147597.25 0.248115E+10 0.00 863281.75 67994356.54 0.00 83855242.38 0.00 0.92
August 0.126646E+09 0.179098E+10 0.00 5992131.60 32515015.46 0.00 0.808787E+09 0.00 1.45
September 0.946205E+09 0.581343E+09 0.00 7309462.74 88205286.93 0.00 0.179647E+10 0.00 1.29
October 0.191322E+10 66960967.19 0.00 3934086.03 776402.07 0.143028E+09 0.186297E+10 0.00 1.11
November 0.255311E+10 0.00 0.00 214700.68 0.00 0.112276E+10 0.222143E+09 0.00 0.79
December 0.147264E+10 0.00 0.00 0.00 0.00 0.208422E+10 0.00 0.00 0.76
                   
Annual Sum or Average 0.163596E+11 0.601834E+10 0.00 40281849.30 0.262282E+09 0.942532E+10 0.138071E+11 0.00 1.07
Minimum of Months 14147597.25 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.75
Maximum of Months 0.255311E+10 0.248115E+10 0.00 10317229.79 88205286.93 0.240074E+10 0.400661E+10 0.00 1.63



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.129916E+10 0.00 0.00 3946466.57 0.00 0.194933E+10 0.202590E+10 0.00 0.67
February 0.137325E+10 0.00 0.00 5367346.60 0.00 0.145536E+10 0.266974E+10 0.00 0.72
March 0.207425E+10 0.00 0.00 9116004.42 0.00 0.102277E+10 0.582367E+10 0.00 0.95
April 0.230564E+10 756402.75 0.00 7497204.68 0.00 0.632224E+09 0.452754E+10 0.00 1.06
May 0.225996E+10 47835916.83 0.00 9724069.38 0.00 48447146.25 0.440738E+10 0.00 1.22
June 0.406139E+09 0.146317E+10 0.00 5289559.80 47451844.32 0.00 0.132474E+10 0.00 1.07
July 14983846.47 0.326947E+10 0.00 1340292.25 56278911.46 0.00 61262990.19 0.00 0.74
August 0.164945E+09 0.258410E+10 0.00 7819725.36 36683586.57 0.00 0.811886E+09 0.00 1.29
September 0.912913E+09 0.106552E+10 0.00 19851236.06 37414624.10 0.00 0.369065E+10 0.00 1.48
October 0.127702E+10 0.238014E+09 0.00 18938935.78 0.00 0.131718E+09 0.750005E+10 0.00 1.61
November 0.192136E+10 0.00 0.00 6082307.96 0.00 0.863048E+09 0.409163E+10 0.00 0.87
December 0.152221E+10 0.00 0.00 4421711.23 0.00 0.165589E+10 0.214669E+10 0.00 0.69
                   
Annual Sum or Average 0.155318E+11 0.866886E+10 0.00 99394860.09 0.177829E+09 0.775879E+10 0.390811E+11 0.00 1.03
Minimum of Months 14983846.47 0.00 0.00 1340292.25 0.00 0.00 61262990.19 0.00 0.67
Maximum of Months 0.230564E+10 0.326947E+10 0.00 19851236.06 56278911.46 0.194933E+10 0.750005E+10 0.00 1.61



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.134957E+10 0.00 0.00 131900.91 0.00 0.235858E+10 0.123795E+09 0.00 0.81
February 0.141114E+10 0.00 0.00 398131.47 0.00 0.196627E+10 0.304840E+09 0.00 0.83
March 0.288064E+10 0.00 0.00 2424566.98 0.00 0.932534E+09 0.182132E+10 0.00 1.01
April 0.269950E+10 274391.77 0.00 5360715.80 0.00 0.435592E+09 0.282262E+10 0.00 1.29
May 0.221003E+10 46044998.61 0.00 9062765.36 0.00 23931709.46 0.378559E+10 0.00 1.68
June 0.333324E+09 0.132917E+10 0.00 5404367.71 33104797.34 0.00 0.122457E+10 0.00 1.50
July 10668029.53 0.275072E+10 0.00 1951854.66 44183010.17 0.00 56438432.21 0.00 0.96
August 0.167625E+09 0.206139E+10 0.00 4453534.40 24285803.68 0.00 0.506057E+09 0.00 1.49
September 0.118516E+10 0.724800E+09 0.00 7408663.90 56828440.84 0.00 0.157712E+10 0.00 1.38
October 0.235623E+10 0.113766E+09 0.00 4192507.83 0.00 0.143925E+09 0.200127E+10 0.00 1.28
November 0.276938E+10 0.00 0.00 447326.71 0.00 0.115129E+10 0.389716E+09 0.00 0.87
December 0.170730E+10 0.00 0.00 45079.81 0.00 0.207023E+10 84022665.38 0.00 0.82
                   
Annual Sum or Average 0.190806E+11 0.702617E+10 0.00 41281415.55 0.158402E+09 0.908234E+10 0.146974E+11 0.00 1.16
Minimum of Months 10668029.53 0.00 0.00 45079.81 0.00 0.00 56438432.21 0.00 0.81
Maximum of Months 0.288064E+10 0.275072E+10 0.00 9062765.36 56828440.84 0.235858E+10 0.378559E+10 0.00 1.68



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 546193.92 0.00 0.00 3144825.15 0.00 0.00 0.697130E+09 0.00 0.28
February 0.00 0.00 0.00 8043549.95 0.00 0.00 0.659146E+09 0.00 0.29
March 0.00 0.00 0.00 16064124.50 0.00 0.00 0.623763E+09 0.00 0.30
April 0.00 0.00 0.00 17338911.03 0.00 0.00 0.424853E+09 0.00 0.29
May 0.00 4532990.99 0.00 3945983.76 0.00 0.00 0.256613E+09 0.00 0.29
June 0.00 0.147414E+09 0.00 2708681.44 0.00 0.00 44413710.81 0.00 0.31
July 0.00 0.358956E+09 0.00 354317.54 0.00 0.00 969228.36 0.00 0.28
August 0.00 0.283634E+09 0.00 4438499.43 0.00 0.00 21411671.78 0.00 0.31
September 0.00 76335434.43 0.00 2449887.94 0.00 0.00 0.116197E+09 0.00 0.29
October 0.00 11869375.30 0.00 7227638.02 0.00 0.00 0.239585E+09 0.00 0.28
November 0.00 0.00 0.00 13165787.46 0.00 0.00 0.512375E+09 0.00 0.28
December 0.00 0.00 0.00 18679979.72 0.00 0.00 0.638300E+09 0.00 0.28
                   
Annual Sum or Average 546193.92 0.882742E+09 0.00 97562185.95 0.00 0.00 0.423476E+10 0.00 0.29
Minimum of Months 0.00 0.00 0.00 354317.54 0.00 0.00 969228.36 0.00 0.28
Maximum of Months 546193.92 0.358956E+09 0.00 18679979.72 0.00 0.00 0.697130E+09 0.00 0.31



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: DATACENTER_MID_ZN_6

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.143605E+10 0.00 0.00 13255075.22 0.00 0.00 0.551375E+10 0.00 0.28
February 0.00 0.00 0.00 61139634.85 0.00 0.00 0.661162E+10 0.00 0.29
March 0.00 0.00 0.00 0.139686E+09 0.00 0.00 0.625692E+10 0.00 0.30
April 0.00 0.00 0.00 0.158243E+09 0.00 0.00 0.425974E+10 0.00 0.29
May 0.00 43983778.77 0.00 34363351.93 0.00 0.00 0.258470E+10 0.00 0.29
June 0.00 0.146508E+10 0.00 25570567.89 0.00 0.00 0.445190E+09 0.00 0.31
July 0.00 0.358292E+10 0.00 3405596.33 0.00 0.00 9749584.76 0.00 0.28
August 0.00 0.284025E+10 0.00 42320482.26 0.00 0.00 0.214761E+09 0.00 0.31
September 0.00 0.749484E+09 0.00 21309723.47 0.00 0.00 0.117144E+10 0.00 0.29
October 0.00 0.115502E+09 0.00 64411991.40 0.00 0.00 0.240582E+10 0.00 0.28
November 0.00 0.00 0.00 0.112648E+09 0.00 0.00 0.514135E+10 0.00 0.28
December 0.00 0.00 0.00 0.161362E+09 0.00 0.00 0.640766E+10 0.00 0.28
                   
Annual Sum or Average 0.143605E+10 0.879723E+10 0.00 0.837715E+09 0.00 0.00 0.410227E+11 0.00 0.29
Minimum of Months 0.00 0.00 0.00 3405596.33 0.00 0.00 9749584.76 0.00 0.28
Maximum of Months 0.143605E+10 0.358292E+10 0.00 0.161362E+09 0.00 0.00 0.661162E+10 0.00 0.31



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.301773E+09 0.00 0.00 795909.13 0.00 0.00 0.386174E+09 0.00 0.28
February 0.00 0.00 0.00 5232280.76 0.00 0.00 0.661984E+09 0.00 0.29
March 0.00 0.00 0.00 13064073.35 0.00 0.00 0.626771E+09 0.00 0.30
April 0.00 0.00 0.00 15339056.15 0.00 0.00 0.426648E+09 0.00 0.29
May 1171673.53 4425749.84 0.00 3238670.80 0.00 0.00 0.258464E+09 0.00 0.29
June 0.00 0.146497E+09 0.00 2562464.64 0.00 0.00 44566540.00 0.00 0.31
July 0.00 0.358257E+09 0.00 341553.77 0.00 0.00 976933.59 0.00 0.28
August 0.00 0.284119E+09 0.00 4242750.52 0.00 0.00 21510632.88 0.00 0.31
September 0.00 74961249.92 0.00 2003204.51 0.00 0.00 0.117707E+09 0.00 0.29
October 0.00 11455403.09 0.00 5999897.77 0.00 0.00 0.241498E+09 0.00 0.28
November 0.00 0.00 0.00 10361165.42 0.00 0.00 0.515266E+09 0.00 0.28
December 0.00 0.00 0.00 15044299.59 0.00 0.00 0.641890E+09 0.00 0.28
                   
Annual Sum or Average 0.302944E+09 0.879715E+09 0.00 78225326.40 0.00 0.00 0.394345E+10 0.00 0.29
Minimum of Months 0.00 0.00 0.00 341553.77 0.00 0.00 976933.59 0.00 0.28
Maximum of Months 0.301773E+09 0.358257E+09 0.00 15339056.15 0.00 0.00 0.661984E+09 0.00 0.31



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.00 0.00 0.00 0.233614E+09 0.00 0.00 0.176974E+11 0.00 0.32
February 0.00 0.00 0.00 0.449707E+09 0.00 0.00 0.173491E+11 0.00 0.32
March 0.00 0.00 0.00 0.812970E+09 0.00 0.00 0.149426E+11 0.00 0.34
April 0.00 0.00 0.00 0.860129E+09 0.00 0.00 0.957547E+10 0.00 0.32
May 0.00 0.135523E+09 0.00 0.196985E+09 0.00 0.00 0.552377E+10 0.00 0.33
June 0.00 0.339686E+10 0.00 0.126352E+09 0.00 0.00 0.918788E+09 0.00 0.34
July 0.00 0.795039E+10 0.00 14390933.98 0.00 0.00 16088691.56 0.00 0.31
August 0.00 0.507054E+10 0.00 0.242489E+09 0.00 0.00 0.502555E+09 0.00 0.35
September 0.00 0.188772E+10 0.00 0.124472E+09 0.00 0.00 0.244918E+10 0.00 0.32
October 0.00 0.301727E+09 0.00 0.353831E+09 0.00 0.00 0.562261E+10 0.00 0.32
November 0.00 0.00 0.00 0.675798E+09 0.00 0.00 0.118605E+11 0.00 0.32
December 0.00 0.00 0.00 0.953392E+09 0.00 0.00 0.160262E+11 0.00 0.32
                   
Annual Sum or Average 0.00 0.187428E+11 0.00 0.504413E+10 0.00 0.00 0.102484E+12 0.00 0.33
Minimum of Months 0.00 0.00 0.00 14390933.98 0.00 0.00 16088691.56 0.00 0.31
Maximum of Months 0.00 0.795039E+10 0.00 0.953392E+09 0.00 0.00 0.176974E+11 0.00 0.35



Table of Contents

Report: HeatEmissionsReportMonthly

For: Environment

Timestamp: 2023-10-16 08:43:34

Custom Monthly Report

SITE TOTAL SURFACE HEAT EMISSION TO AIR [J] SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J]
January 0.238954E+12 0.436468E+11 0.00 0.194939E+13 0.553364E+12
February 0.382163E+12 0.394897E+11 0.00 0.198519E+13 0.838025E+12
March 0.638287E+12 0.322491E+11 0.00 0.232234E+13 0.132380E+13
April 0.681601E+12 0.211963E+11 0.00 0.215636E+13 0.183240E+13
May 0.866571E+12 0.121683E+11 0.00 0.200862E+13 0.114902E+13
June 0.846094E+12 0.197116E+09 0.00 0.406019E+12 0.285559E+13
July 0.826560E+12 -0.113132E+11 0.00 -0.607482E+12 0.397348E+13
August 0.791108E+12 -0.563844E+10 0.00 -0.167846E+12 0.430136E+13
September 0.557262E+12 0.458783E+10 0.00 0.105851E+13 0.189338E+13
October 0.528958E+12 0.165392E+11 0.00 0.213044E+13 0.155466E+13
November 0.264763E+12 0.312429E+11 0.00 0.224439E+13 0.129482E+13
December 0.194118E+12 0.373991E+11 0.00 0.216234E+13 0.170707E+13
           
Annual Sum or Average 0.681644E+13 0.221765E+12 0.00 0.176483E+14 0.232770E+14
Minimum of Months 0.194118E+12 -0.113132E+11 0.00 -0.607482E+12 0.553364E+12
Maximum of Months 0.866571E+12 0.436468E+11 0.00 0.232234E+13 0.430136E+13