Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:43
Tabular Output Report in Format: HTML
Building: OfficeLarge
Environment: RUNPERIOD 1 ** Rochester International Arpt MN USA TMY3 WMO#=726440
Simulation Timestamp: 2023-10-16 08:43:43
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 08:43:43
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 32884.81 | 709.94 | 709.94 |
Net Site Energy | 32884.81 | 709.94 | 709.94 |
Total Source Energy | 94124.61 | 2032.03 | 2032.03 |
Net Source Energy | 94124.61 | 2032.03 | 2032.03 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 46320.38 |
Net Conditioned Building Area | 46320.38 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 3954.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 1808.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 3931.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 697.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 14676.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 1934.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 2486.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 402.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 584.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3912.94 |
Humidification | 1498.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 557.61 |
Heat Recovery | 52.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 856.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2280.17 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 28073.68 | 4811.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6750.72 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler | 0.00 | 3954.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 1808.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 3931.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 697.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 5334.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DataCenterPlugLoads | 9341.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 80.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 1848.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 5.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | General | 2486.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 402.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 584.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3912.94 |
Humidification | General | 1498.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 557.61 |
Heat Recovery | General | 52.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2280.17 | |
Water Heater | 0.00 | 856.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 3954.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 1808.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 3931.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 697.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 14676.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 1934.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 2486.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 402.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 584.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3912.94 |
Humidification | Unassigned | 1498.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 557.61 |
Heat Recovery | Unassigned | 52.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 0.00 | 856.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2280.17 |
Refrigeration | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 99.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 146.40 | 103.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.15 |
Other | 359.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 606.08 | 103.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.15 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 99.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 146.40 | 103.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.15 |
Other | 359.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 606.08 | 103.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.15 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 28073.681 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 28073.681 | 100.00 |
Total On-Site and Utility Electric Sources | 28073.681 | 100.00 |
Total Electricity End Uses | 28073.681 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | 0.00 |
Air to Air Heat Recovery for Cooling | 313.07 | 7.12 |
Air to Air Heat Recovery for Heating | 4083.94 | 92.88 |
High-Temperature Geothermal* | 0.00 | 0.00 |
Solar Water Thermal | 0.00 | 0.00 |
Solar Air Thermal | 0.00 | 0.00 |
Total On-Site Thermal Sources | 4397.01 | 100.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 6750.72 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 6750.72 | 100.00 |
Total Water End Uses | 6750.72 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 182.50 |
Time Setpoint Not Met During Occupied Cooling | 469.83 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 5943.00 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2013
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICELARGE
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 6A
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_MN_ROCHESTER
| Environment |ZoneCoolingSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |ZoneHeatingSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |ZoneElectricSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |SpaceGainsMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |PeakSpaceGainsMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |SpaceGainComponentsAtCoolingPeakMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |ComfortReportSimple55Monthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |OccupantComfortDataSummaryMonthly
| DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 | BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 |ChillerReportMonthly
| COOLSYS1 CHILLER1 | COOLSYS1 CHILLER2 |TowerReportMonthly
| CENTRAL TOWER | TOWERWATERSYS COOLTOWER 1 | TOWERWATERSYS COOLTOWER 2 |BoilerReportMonthly
| HEATSYS1 BOILER | CENTRAL BOILER |DXReportMonthly
| VAV_BOT WITH REHEAT COOLING COIL | VAV_MID WITH REHEAT COOLING COIL | VAV_TOP WITH REHEAT COOLING COIL | CAV_BAS COOLING COIL | AIRLOOP DATACENTER BASEMENT COOLING COIL | AIRLOOP DATACENTER BOT COOLING COIL | AIRLOOP DATACENTER MID COOLING COIL | AIRLOOP DATACENTER TOP COOLING COIL |WindowReportMonthly
| PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW |WindowEnergyReportMonthly
| PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW |WindowZoneSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |WindowEnergyZoneSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWHSYS1 WATER HEATER |DaylightingReportMonthly
| PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_4_DAYLCTRL |CoilReportMonthly
| VAV_BOT WITH REHEAT HEATING COIL | CORE_BOTTOM VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | VAV_MID WITH REHEAT HEATING COIL | CORE_MID VAV BOX REHEAT COIL | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | VAV_TOP WITH REHEAT HEATING COIL | CORE_TOP VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | CAV_BAS HEATING COIL | AIRLOOP DATACENTER BASEMENT HEATING COIL | AIRLOOP DATACENTER BOT HEATING COIL | AIRLOOP DATACENTER MID HEATING COIL | AIRLOOP DATACENTER TOP HEATING COIL | AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | AIRLOOP DATACENTER BOT_SUPPHEATCOIL | AIRLOOP DATACENTER MID_SUPPHEATCOIL | AIRLOOP DATACENTER TOP_SUPPHEATCOIL | VAV_BOT WITH REHEAT COOLING COIL | VAV_MID WITH REHEAT COOLING COIL | VAV_TOP WITH REHEAT COOLING COIL | CAV_BAS COOLING COIL | AIRLOOP DATACENTER BASEMENT COOLING COIL | AIRLOOP DATACENTER BOT COOLING COIL | AIRLOOP DATACENTER MID COOLING COIL | AIRLOOP DATACENTER TOP COOLING COIL |PlantLoopDemandReportMonthly
| HEATSYS1 | COOLSYS1_SUPPLY | COOLSYS1_DEMAND | SINGLE WATER PLANT LOOP | SWHSYS1 | TOWERWATERSYS |FanReportMonthly
| CAV_BAS FAN | VAV_BOT WITH REHEAT FAN | VAV_MID WITH REHEAT FAN | VAV_TOP WITH REHEAT FAN | AIRLOOP DATACENTER BASEMENT SUPPLY FAN | AIRLOOP DATACENTER BOT SUPPLY FAN | AIRLOOP DATACENTER MID SUPPLY FAN | AIRLOOP DATACENTER TOP SUPPLY FAN |PumpReportMonthly
| HEATSYS1 PUMP | COOLSYS1 PUMP SECONDARY | COOLSYS1 CHILLER1 PUMP | COOLSYS1 CHILLER2 PUMP | PLANT CIRC PUMP | SWHSYS1 PUMP | TOWERWATERSYS PUMP |CondLoopDemandReportMonthly
| HEATSYS1 | COOLSYS1_SUPPLY | COOLSYS1_DEMAND | SINGLE WATER PLANT LOOP | SWHSYS1 | TOWERWATERSYS |ZoneTemperatureOscillationReportMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |AirLoopSystemEnergyAndWaterUseMonthly
| VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | CAV_BAS | AIRLOOP DATACENTER BASEMENT | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |AirLoopSystemComponentLoadsMonthly
| VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | CAV_BAS | AIRLOOP DATACENTER BASEMENT | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |AirLoopSystemComponentEnergyUseMonthly
| VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | CAV_BAS | AIRLOOP DATACENTER BASEMENT | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |MechanicalVentilationLoadsMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 08:43:43
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:43 |
RunPeriod | RUNPERIOD 1 |
Weather File | Rochester International Arpt MN USA TMY3 WMO#=726440 |
Latitude [deg] | 43.90 |
Longitude [deg] | -92.5 |
Elevation [m] | 398.00 |
Time Zone | -6.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 12183.89 | 3655.17 | 2436.78 | 3655.17 | 2436.78 |
Above Ground Wall Area [m2] | 11589.54 | 3476.86 | 2317.91 | 3476.86 | 2317.91 |
Window Opening Area [m2] | 4635.80 | 1390.74 | 927.16 | 1390.74 | 927.16 |
Gross Window-Wall Ratio [%] | 38.05 | 38.05 | 38.05 | 38.05 | 38.05 |
Above Ground Window-Wall Ratio [%] | 40.00 | 40.00 | 40.00 | 40.00 | 40.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 12183.89 | 3655.17 | 2436.78 | 3655.17 | 2436.78 |
Above Ground Wall Area [m2] | 11589.54 | 3476.86 | 2317.91 | 3476.86 | 2317.91 |
Window Opening Area [m2] | 4635.80 | 1390.74 | 927.16 | 1390.74 | 927.16 |
Gross Window-Wall Ratio [%] | 38.05 | 38.05 | 38.05 | 38.05 | 38.05 |
Above Ground Window-Wall Ratio [%] | 40.00 | 40.00 | 40.00 | 40.00 | 40.00 |
Total | |
Gross Roof Area [m2] | 3563.11 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
BASEMENT | 2779.43 | Yes | Yes | 6779.02 | 1.00 | 0.00 | 397.05 | 0.00 | 0.00 | 10.2732 | 18.58 | 4.8418 |
CORE_BOTTOM | 2496.12 | Yes | Yes | 6849.35 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.2732 | 18.58 | 8.0697 |
CORE_MID | 2496.12 | Yes | Yes | 6849.35 | 10.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.2732 | 18.58 | 8.0696 |
CORE_TOP | 2496.12 | Yes | Yes | 6849.35 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.2732 | 18.58 | 8.0696 |
PERIMETER_BOT_ZN_3 | 313.41 | Yes | Yes | 860.00 | 1.00 | 200.61 | 0.00 | 115.90 | 115.90 | 10.2732 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_2 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 77.26 | 77.26 | 10.2732 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_1 | 313.42 | Yes | Yes | 860.02 | 1.00 | 200.61 | 0.00 | 115.90 | 115.90 | 10.2732 | 18.58 | 8.0699 |
PERIMETER_BOT_ZN_4 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 77.26 | 77.26 | 10.2732 | 18.58 | 8.0699 |
PERIMETER_MID_ZN_3 | 313.41 | Yes | Yes | 860.00 | 10.00 | 200.61 | 0.00 | 115.90 | 115.90 | 10.2732 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_2 | 201.98 | Yes | Yes | 554.22 | 10.00 | 133.74 | 0.00 | 77.26 | 77.26 | 10.2732 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_1 | 313.42 | Yes | Yes | 860.02 | 10.00 | 200.61 | 0.00 | 115.90 | 115.90 | 10.2732 | 18.58 | 8.0699 |
PERIMETER_MID_ZN_4 | 201.98 | Yes | Yes | 554.22 | 10.00 | 133.74 | 0.00 | 77.26 | 77.26 | 10.2732 | 18.58 | 8.0699 |
PERIMETER_TOP_ZN_3 | 313.41 | Yes | Yes | 860.00 | 1.00 | 200.61 | 0.00 | 115.90 | 115.90 | 10.2732 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_2 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 77.26 | 77.26 | 10.2732 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_1 | 313.42 | Yes | Yes | 860.02 | 1.00 | 200.61 | 0.00 | 115.90 | 115.90 | 10.2732 | 18.58 | 8.0699 |
PERIMETER_TOP_ZN_4 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 77.26 | 77.26 | 10.2732 | 18.58 | 8.0699 |
GROUNDFLOOR_PLENUM | 3563.11 | Yes | No | 4344.14 | 1.00 | 297.11 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
MIDFLOOR_PLENUM | 3563.11 | Yes | No | 4344.14 | 10.00 | 297.11 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
TOPFLOOR_PLENUM | 3563.11 | Yes | No | 4344.14 | 1.00 | 297.11 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
DATACENTER_BOT_ZN_6 | 36.20 | Yes | Yes | 99.34 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.8735 | 18.58 | 215.2992 |
DATACENTER_MID_ZN_6 | 36.20 | Yes | Yes | 99.34 | 10.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.8735 | 18.58 | 215.2992 |
DATACENTER_TOP_ZN_6 | 36.20 | Yes | Yes | 99.34 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.8735 | 18.58 | 215.2992 |
DATACENTER_BASEMENT_ZN_6 | 783.68 | Yes | Yes | 1911.37 | 1.00 | 0.00 | 197.31 | 0.00 | 0.00 | 10.2732 | 18.58 | 484.4232 |
Total | 46320.38 | 126016.35 | 8024.24 | 594.36 | 4635.80 | 4635.80 | 10.3445 | 18.58 | 17.8789 | |||
Conditioned Total | 46320.38 | 126016.35 | 8024.24 | 594.36 | 4635.80 | 4635.80 | 10.3445 | 18.58 | 17.8789 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 42757.27 | 52129.67 | 3565.29 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
BASEMENT | 2779.43 | Yes | Yes | 1.00 | BASEMENT | GENERAL | BASEMENT | 10.2732 | 18.58 | 4.8418 | |
CORE_BOTTOM | 2496.12 | Yes | Yes | 1.00 | CORE_BOTTOM | GENERAL | CORE_BOTTOM | 10.2732 | 18.58 | 8.0697 | |
CORE_MID | 2496.12 | Yes | Yes | 10.00 | CORE_MID | GENERAL | CORE_MID | 10.2732 | 18.58 | 8.0696 | |
CORE_TOP | 2496.12 | Yes | Yes | 1.00 | CORE_TOP | GENERAL | CORE_TOP | 10.2732 | 18.58 | 8.0696 | |
PERIMETER_BOT_ZN_3 | 313.41 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_3 | GENERAL | PERIMETER_BOT_ZN_3 | 10.2732 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_2 | 201.98 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_2 | GENERAL | PERIMETER_BOT_ZN_2 | 10.2732 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_1 | 313.42 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_1 | GENERAL | PERIMETER_BOT_ZN_1 | 10.2732 | 18.58 | 8.0699 | |
PERIMETER_BOT_ZN_4 | 201.98 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_4 | GENERAL | PERIMETER_BOT_ZN_4 | 10.2732 | 18.58 | 8.0699 | |
PERIMETER_MID_ZN_3 | 313.41 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_3 | GENERAL | PERIMETER_MID_ZN_3 | 10.2732 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_2 | 201.98 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_2 | GENERAL | PERIMETER_MID_ZN_2 | 10.2732 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_1 | 313.42 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_1 | GENERAL | PERIMETER_MID_ZN_1 | 10.2732 | 18.58 | 8.0699 | |
PERIMETER_MID_ZN_4 | 201.98 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_4 | GENERAL | PERIMETER_MID_ZN_4 | 10.2732 | 18.58 | 8.0699 | |
PERIMETER_TOP_ZN_3 | 313.41 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_3 | GENERAL | PERIMETER_TOP_ZN_3 | 10.2732 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_2 | 201.98 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_2 | GENERAL | PERIMETER_TOP_ZN_2 | 10.2732 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_1 | 313.42 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_1 | GENERAL | PERIMETER_TOP_ZN_1 | 10.2732 | 18.58 | 8.0699 | |
PERIMETER_TOP_ZN_4 | 201.98 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_4 | GENERAL | PERIMETER_TOP_ZN_4 | 10.2732 | 18.58 | 8.0699 | |
GROUNDFLOOR_PLENUM | 3563.11 | Yes | No | 1.00 | GROUNDFLOOR_PLENUM | GENERAL | GROUNDFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
MIDFLOOR_PLENUM | 3563.11 | Yes | No | 10.00 | MIDFLOOR_PLENUM | GENERAL | MIDFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
TOPFLOOR_PLENUM | 3563.11 | Yes | No | 1.00 | TOPFLOOR_PLENUM | GENERAL | TOPFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
DATACENTER_BOT_ZN_6 | 36.20 | Yes | Yes | 1.00 | DATACENTER_BOT_ZN_6 | GENERAL | DATACENTER_BOT_ZN_6 | 17.8735 | 18.58 | 215.2992 | |
DATACENTER_MID_ZN_6 | 36.20 | Yes | Yes | 10.00 | DATACENTER_MID_ZN_6 | GENERAL | DATACENTER_MID_ZN_6 | 17.8735 | 18.58 | 215.2992 | |
DATACENTER_TOP_ZN_6 | 36.20 | Yes | Yes | 1.00 | DATACENTER_TOP_ZN_6 | GENERAL | DATACENTER_TOP_ZN_6 | 17.8735 | 18.58 | 215.2992 | |
DATACENTER_BASEMENT_ZN_6 | 783.68 | Yes | Yes | 1.00 | DATACENTER_BASEMENT_ZN_6 | GENERAL | DATACENTER_BASEMENT_ZN_6 | 10.2732 | 18.58 | 484.4232 | |
Total | 46320.38 | 10.3445 | 9.29 | 17.8789 | |||||||
Conditioned Total | 46320.38 | 10.3445 | 9.29 | 17.8789 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 42757.27 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 46320.38 | 46320.38 | 0.00 | 42757.27 | 3.1788 | 60.38 | 10.8345 |
Total | 46320.38 | 46320.38 | 0.00 | 42757.27 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:43:43
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 04-AUG-15:30 | 30-JAN-07:10 | - | - | - | - | - | - | - | - | - | - | 07-SEP-12:50 |
Heating | 0.00 | 3355734.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 527699.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 332294.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 778371.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 84450.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 302996.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 59159.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 93806.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 5613.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 33330.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 2184392.29 | 3389064.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler | 0.00 | 3355734.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 527699.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 332294.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 305206.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DataCenterPlugLoads | 473165.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 5015.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 79171.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 263.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | General | 302996.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 59159.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 93806.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 5613.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Water Heater | 0.00 | 33330.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:43:43
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 4287.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 5726.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 12450.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 2208.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 46480.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 6127.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 7876.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 1276.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 1851.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 4747.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 164.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 928.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 88909.35 | 5215.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 92.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 123.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 268.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 47.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1003.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 132.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 170.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 27.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 39.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 102.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 3.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 20.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1919.44 | 112.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 92.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 123.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 268.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 47.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1003.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 132.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 170.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 27.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 39.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 102.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 3.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 20.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1919.44 | 112.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:43:43
AirTerminal:SingleDuct:ConstantVolume:NoReheatDesign Size Maximum Air Flow Rate [m3/s] | |
BASEMENT DIRECT AIR | 6.24 |
DATACENTER_BOT_ZN_6 DIRECT AIR | 0.532608 |
DATACENTER_MID_ZN_6 DIRECT AIR | 5.12 |
DATACENTER_TOP_ZN_6 DIRECT AIR | 0.520142 |
DATACENTER_BASEMENT_ZN_6 DIRECT AIR | 22.44 |
Design Size Maximum Air Flow Rate [m3/s] | Design Size Constant Minimum Air Flow Fraction | User-Specified Constant Minimum Air Flow Fraction | Design Size Minimum Air Flow Rate [m3/s] | Design Size Maximum Flow Fraction during Reheat [] | User-Specified Maximum Flow Fraction during Reheat [] | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | Design Size Maximum Reheat Water Flow Rate [m3/s] | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | |
CORE_BOTTOM VAV BOX COMPONENT | 6.46 | 0.294407 | 0.308000 | 1.99 | 0.785087 | 0.500000 | 0.001294 | 0.000254 | 1.99 | 12.80 | 0.008000 |
CORE_MID VAV BOX COMPONENT | 60.83 | 0.312676 | 0.321000 | 19.53 | 0.833803 | 0.500000 | 0.001219 | 0.004994 | 19.53 | 12.80 | 0.008000 |
CORE_TOP VAV BOX COMPONENT | 6.04 | 0.314785 | 0.331000 | 2.00 | 0.839428 | 0.500000 | 0.001210 | 0.001002 | 3.58 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | 1.08 | 0.220438 | 0.230000 | 0.249180 | 0.587834 | 0.500000 | 0.001728 | 0.000210 | 0.749819 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | 1.48 | 0.103975 | 0.200000 | 0.296043 | 0.300000 | 0.500000 | 0.003664 | 0.000141 | 0.502501 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | 1.68 | 0.142353 | 0.200000 | 0.335541 | 0.379608 | 0.500000 | 0.002676 | 0.000221 | 0.788655 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | 1.78 | 0.086248 | 0.200000 | 0.356888 | 0.300000 | 0.500000 | 0.004417 | 0.000122 | 0.435247 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_3 VAV BOX COMPONENT | 11.14 | 0.214452 | 0.237000 | 2.64 | 0.571873 | 0.500000 | 0.001777 | 0.003112 | 11.14 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_2 VAV BOX COMPONENT | 15.73 | 0.097839 | 0.200000 | 3.15 | 0.300000 | 0.500000 | 0.003894 | 0.002032 | 7.27 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_1 VAV BOX COMPONENT | 16.92 | 0.141115 | 0.200000 | 3.38 | 0.376306 | 0.500000 | 0.002700 | 0.003063 | 10.96 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_4 VAV BOX COMPONENT | 16.75 | 0.091901 | 0.200000 | 3.35 | 0.300000 | 0.500000 | 0.004146 | 0.002017 | 7.22 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | 1.39 | 0.171995 | 0.216000 | 0.299923 | 0.458654 | 0.500000 | 0.002215 | 0.000388 | 1.39 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | 1.58 | 0.097311 | 0.200000 | 0.316315 | 0.300000 | 0.500000 | 0.003915 | 0.000253 | 0.904767 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | 1.81 | 0.131696 | 0.200000 | 0.362692 | 0.351190 | 0.500000 | 0.002893 | 0.000383 | 1.37 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | 1.76 | 0.087580 | 0.200000 | 0.351462 | 0.300000 | 0.500000 | 0.004350 | 0.000254 | 0.907578 | 12.80 | 0.008000 |
Design Size Rated Capacity [W] | Design Size Maximum Water Flow Rate [m3/s] | Design Size U-Factor Times Area Value [W/K] | |
CORE_BOTTOM VAV BOX REHEAT COIL | 29028.74 | 0.000254 | 616.75 |
CORE_MID VAV BOX REHEAT COIL | 570892.97 | 0.004994 | 14491.92 |
CORE_TOP VAV BOX REHEAT COIL | 114582.06 | 0.001002 | 3023.60 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | 23970.80 | 0.000210 | 632.09 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | 16063.24 | 0.000141 | 423.56 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | 25210.56 | 0.000221 | 664.76 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | 13916.90 | 0.000122 | 367.01 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | 355759.67 | 0.003112 | 9378.05 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | 232324.53 | 0.002032 | 6124.16 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | 350087.60 | 0.003063 | 9228.60 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | 230500.91 | 0.002017 | 6076.10 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | 44347.66 | 0.000388 | 1168.91 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | 28896.45 | 0.000253 | 761.64 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | 43732.98 | 0.000383 | 1152.71 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | 28986.02 | 0.000254 | 764.00 |
VAV_BOT WITH REHEAT HEATING COIL | 109143.00 | 0.000955 | 1667.90 |
VAV_MID WITH REHEAT HEATING COIL | 1114716.08 | 0.009752 | 16651.03 |
VAV_TOP WITH REHEAT HEATING COIL | 109771.99 | 0.000960 | 1686.85 |
CAV_BAS HEATING COIL | 324321.77 | 0.002837 | 6941.86 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT | 6.24 | 3.23 | 12.49 | 3.55 | 10.71 | 10.71 | 0.300000 | 0.331952 | 10.71 |
VAV_MID WITH REHEAT | 60.68 | 32.05 | 121.37 | 53.60 | 100.09 | 100.09 | 0.300000 | 0.535568 | 100.09 |
VAV_TOP WITH REHEAT | 6.29 | 3.33 | 12.58 | 8.15 | 11.01 | 11.01 | 0.300000 | 0.740324 | 11.01 |
CAV_BAS | 6.24 | 6.24 | 6.24 | 6.24 | 6.24 | 6.24 | 1.00 | 1.00 | 6.24 |
AIRLOOP DATACENTER BASEMENT | 22.44 | 22.44 | 22.44 | 22.44 | 22.44 | 22.44 | 1.00 | 0.999995 | 22.44 |
AIRLOOP DATACENTER BOT | 0.532608 | 0.532608 | 0.532608 | 0.532608 | 0.532608 | 0.532608 | 1.00 | 1.00 | 0.532608 |
AIRLOOP DATACENTER MID | 5.12 | 5.12 | 5.12 | 5.12 | 5.12 | 5.12 | 1.00 | 1.00 | 5.12 |
AIRLOOP DATACENTER TOP | 0.520142 | 0.520142 | 0.520142 | 0.520142 | 0.520142 | 0.520142 | 1.00 | 1.00 | 0.520142 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT_OA_CONTROLLER | 10.71 | 2.54 |
VAV_MID WITH REHEAT_OA_CONTROLLER | 100.09 | 25.38 |
VAV_TOP WITH REHEAT_OA_CONTROLLER | 11.01 | 2.54 |
CAV_BAS_OA_CONTROLLER | 6.24 | 1.20 |
AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER | 22.44 | 0.338393 |
AIRLOOP DATACENTER BOT_OA_CONTROLLER | 0.532608 | 0.015632 |
AIRLOOP DATACENTER MID_OA_CONTROLLER | 5.12 | 0.156323 |
AIRLOOP DATACENTER TOP_OA_CONTROLLER | 0.520142 | 0.015632 |
Design Size Nominal Supply Air Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT OA HEAT RECOVERY | 2.54 |
VAV_MID WITH REHEAT OA HEAT RECOVERY | 25.38 |
VAV_TOP WITH REHEAT OA HEAT RECOVERY | 2.54 |
Design Size Design Inlet Air Temperature [C] | Design Size Design Inlet Water Temperature [C] | Design Size Design Outlet Air Temperature [C] | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | Design Size Design Coil Load [W] | Design Size Design Water Flow Rate [m3/s] | Design Size Design Air Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT COOLING COIL | 25.75 | 6.67 | 10.87 | 0.010462 | 0.008500 | 248199.41 | 0.010559 | 10.71 |
VAV_MID WITH REHEAT COOLING COIL | 25.89 | 6.67 | 10.87 | 0.010698 | 0.008500 | 2406793.33 | 0.102391 | 100.09 |
VAV_TOP WITH REHEAT COOLING COIL | 25.66 | 6.67 | 10.87 | 0.010472 | 0.008500 | 254402.44 | 0.010823 | 11.01 |
CAV_BAS COOLING COIL | 25.24 | 6.67 | 11.36 | 0.010318 | 0.008500 | 134691.93 | 0.005730 | 6.24 |
Design Size Maximum Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT FAN | 10.71 |
VAV_MID WITH REHEAT FAN | 100.09 |
VAV_TOP WITH REHEAT FAN | 11.01 |
Maximum Actuated Flow [m3/s] | Controller Convergence Tolerance | |
VAV_BOT WITH REHEAT_COOLC_CONTROLLER | 0.010559 | 0.000045 |
VAV_BOT WITH REHEAT_HEATC_CONTROLLER | 0.000955 | |
VAV_MID WITH REHEAT_COOLC_CONTROLLER | 0.102391 | 0.000005 |
VAV_MID WITH REHEAT_HEATC_CONTROLLER | 0.009752 | |
VAV_TOP WITH REHEAT_COOLC_CONTROLLER | 0.010823 | 0.000044 |
VAV_TOP WITH REHEAT_HEATC_CONTROLLER | 0.000960 | |
CAV_BAS_COOLC_CONTROLLER | 0.005730 | 0.000083 |
CAV_BAS_HEATC_CONTROLLER | 0.002837 |
Design Size Maximum Flow Rate [m3/s] | |
CAV_BAS FAN | 6.24 |
Design Size Rated Air Flow Rate [m3/s] | Design Size Rated Total Cooling Capacity [W] | Design Size Rated Sensible Cooling Capacity [W] | Design Size Rated Water Flow Rate [m3/s] | |
AIRLOOP DATACENTER BASEMENT COOLING COIL | 22.44 | 441003.93 | 302154.35 | 0.010800 |
AIRLOOP DATACENTER BOT COOLING COIL | 0.532608 | 10359.22 | 7125.89 | 0.000254 |
AIRLOOP DATACENTER MID COOLING COIL | 5.12 | 99679.44 | 68510.11 | 0.002441 |
AIRLOOP DATACENTER TOP COOLING COIL | 0.520142 | 10125.79 | 6961.86 | 0.000248 |
Supply Air Flow Rate [m3/s] | Supply Air Flow Rate During Heating Operation [m3/s] | Supply Air Flow Rate During Cooling Operation [m3/s] | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | Nominal Heating Capacity [W] | Nominal Cooling Capacity [W] | Supplemental Heating Coil Nominal Capacity [W] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | 22.44 | 22.44 | 22.44 | 22.44 | 441003.93 | 441003.93 | 25854.50 | 1.00 |
AIRLOOP DATACENTER BOT DXAC HEAT PUMP | 0.532608 | 0.532608 | 0.532608 | 0.532608 | 10359.22 | 10359.22 | 1194.37 | 1.00 |
AIRLOOP DATACENTER MID DXAC HEAT PUMP | 5.12 | 5.12 | 5.12 | 5.12 | 99679.44 | 99679.44 | 11943.71 | 1.00 |
AIRLOOP DATACENTER TOP DXAC HEAT PUMP | 0.520142 | 0.520142 | 0.520142 | 0.520142 | 10125.79 | 10125.79 | 1194.37 | 1.00 |
Design Size Maximum Flow Rate [m3/s] | |
AIRLOOP DATACENTER BASEMENT SUPPLY FAN | 22.44 |
AIRLOOP DATACENTER BOT SUPPLY FAN | 0.532608 |
AIRLOOP DATACENTER MID SUPPLY FAN | 5.12 |
AIRLOOP DATACENTER TOP SUPPLY FAN | 0.520142 |
Design Size Rated Air Flow Rate [m3/s] | Design Size Rated Heating Capacity [W] | Design Size Rated Water Flow Rate [m3/s] | |
AIRLOOP DATACENTER BASEMENT HEATING COIL | 22.44 | 441003.93 | 0.010800 |
AIRLOOP DATACENTER BOT HEATING COIL | 0.532608 | 10359.22 | 0.000254 |
AIRLOOP DATACENTER MID HEATING COIL | 5.12 | 99679.44 | 0.002441 |
AIRLOOP DATACENTER TOP HEATING COIL | 0.520142 | 10125.79 | 0.000248 |
Design Size Nominal Capacity [W] | |
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | 25854.50 |
AIRLOOP DATACENTER BOT_SUPPHEATCOIL | 1194.37 |
AIRLOOP DATACENTER MID_SUPPHEATCOIL | 11943.71 |
AIRLOOP DATACENTER TOP_SUPPHEATCOIL | 1194.37 |
Design Size Nominal Capacity Volume [m3/s] | User-Specified Nominal Capacity Volume [m3/s] | Design Size Rated Power [W] | User-Specified Rated Power [W] | |
DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | 0.000202 | 0.000037 | 96450.70 | 100000.00 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | Design Minimum Flow Rate [m3/s] | |
COOLSYS1 PUMP SECONDARY | 0.129503 | 21143.80 | |
HEATSYS1 PUMP | 0.032949 | 9922.74 | 0.000000 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
COOLSYS1_DEMAND | 0.129503 | 15.54 |
HEATSYS1 | 0.032949 | 3.95 |
COOLSYS1_SUPPLY | 0.129503 | 15.54 |
SINGLE WATER PLANT LOOP | 0.013743 | 1.65 |
SWHSYS1 | 0.000440 | 0.052800 |
Loop Supply Side Design Fluid Flow Rate [m3/s] | Loop Demand Side Design Fluid Flow Rate [m3/s] | Heat Exchanger U-Factor Times Area Value [W/C] | Loop-to-loop Temperature Difference Used to Size Heat Exchanger U-Factor Times Area Value [C] | |
BYPASS HEAT EXCHANGER | 0.129503 | 0.129503 | 543586.98 | 5.60 |
Design Size Nominal Capacity [W] | User-Specified Nominal Capacity [W] | Design Size Design Water Flow Rate [m3/s] | |
HEATSYS1 BOILER | 3766253.92 | 3766253.92 | 0.032949 |
CENTRAL BOILER | 566092.86 | 554972.71 | 0.013743 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
COOLSYS1 CHILLER1 PUMP | 0.064751 | 7319.28 |
COOLSYS1 CHILLER2 PUMP | 0.064751 | 7319.28 |
PLANT CIRC PUMP | 0.013743 | 3505.15 |
SWHSYS1 PUMP | 0.000440 | 56.21 |
Design Size Reference Chilled Water Flow Rate [m3/s] | User-Specified Reference Chilled Water Flow Rate [m3/s] | Design Size Reference Capacity [W] | User-Specified Reference Capacity [W] | Design Size Reference Condenser Water Flow Rate [m3/s] | |
COOLSYS1 CHILLER1 | 0.129503 | 0.065095 | 1533882.42 | 1541163.98 | 0.076266 |
COOLSYS1 CHILLER2 | 0.129503 | 0.065095 | 1533882.42 | 1541163.98 | 0.076266 |
Design Water Flow Rate [m3/s] | Air Flow Rate at High Fan Speed [m3/s] | Fluid cooler UA value at high fan speed based on nominal capacity input [W/K] | Air Flow Rate at Low Fan Speed [m3/s] | Fan Power at Low Fan Speed [W] | U-factor Times Area Value at Low Fan Speed [W/C] | |
CENTRAL TOWER | 0.013743 | 139666.47 | 57601.40 | 69833.23 | 7879.72 | 21245.38 |
Use Side Design Flow Rate [m3/s] | |
SWHSYS1 WATER HEATER | 0.000440 |
Maximum Loop Flow Rate [m3/s] | Condenser Loop Volume [m3] | |
TOWERWATERSYS | 0.152533 | 18.30 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
TOWERWATERSYS PUMP | 0.152533 | 37763.79 |
Design Air Flow Rate [m3/s] | Nominal Capacity [W] | Air Flow Rate in free convection regime [m3/s] | Tower capacity in free convection regime at design conditions [W] | |
TOWERWATERSYS COOLTOWER 1 | 61.47 | 1828568.75 | 12.29 | 228571.09 |
TOWERWATERSYS COOLTOWER 2 | 61.47 | 1828568.75 | 12.29 | 228571.09 |
Design Water Flow Rate [m3/s] Equipment # 47 | |
WSHPPLANT OPERATION SCHEME | 0.079217 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:43:43
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
PERIMETER_BOT_ZN_3_WALL_NORTH | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | |
PERIMETER_BOT_ZN_2_WALL_EAST | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | |
PERIMETER_BOT_ZN_1_WALL_SOUTH | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | |
PERIMETER_BOT_ZN_4_WALL_WEST | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | |
PERIMETER_MID_ZN_3_WALL_NORTH | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_MID_ZN_2_WALL_EAST | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_MID_ZN_1_WALL_SOUTH | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_MID_ZN_4_WALL_WEST | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | |
PERIMETER_TOP_ZN_3_WALL_NORTH | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_TOP_ZN_2_WALL_EAST | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_TOP_ZN_1_WALL_SOUTH | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_TOP_ZN_4_WALL_WEST | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 08:43:43
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 08:43:43
VersionVersion ID | |
1 | 22.1.0 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 7.40 | -0.00 | -7.60 | -12.60 | -7.70 | 0.30 | 7.00 | 14.20 | 19.20 | 20.90 | 20.00 | 15.40 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Rochester International Arpt MN USA TMY3 WMO#=726440 | 43.90 | -92.50 | -6.00 | 398.00 | 96634 | 1.1486 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 6.38 | 33.50 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | OfficeLarge | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 23 | 221 | 36 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | BASEMENT | 0.0 | 0.00 | 0.00 | 0.00 | 44.59 | 24.37 | -1.22 | 1 | 1 | 1 | 16.08 | 73.11 | 0.00 | 48.74 | -2.44 | 0.00 | 2.44 | 6779.02 | TARP | TARP | 2779.43 | 0.00 | 0.00 | 0.00 | 9 | 0 | 0 | Yes |
2 | CORE_BOTTOM | 0.0 | 0.00 | 0.00 | 0.00 | 37.01 | 24.37 | 1.37 | 1 | 1 | 1 | 5.49 | 68.53 | 4.57 | 44.17 | 0.00 | 2.74 | 2.74 | 6849.35 | TARP | TARP | 2496.12 | 0.00 | 0.00 | 0.00 | 7 | 0 | 0 | Yes |
3 | CORE_MID | 0.0 | 0.00 | 0.00 | 0.00 | 37.01 | 24.37 | 18.14 | 1 | 10 | 1 | 5.49 | 68.53 | 4.57 | 44.17 | 16.77 | 19.51 | 2.74 | 6849.35 | TARP | TARP | 2496.12 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
4 | CORE_TOP | 0.0 | 0.00 | 0.00 | 0.00 | 37.01 | 24.37 | 34.91 | 1 | 1 | 1 | 5.49 | 68.53 | 4.57 | 44.17 | 33.54 | 36.28 | 2.74 | 6849.35 | TARP | TARP | 2496.12 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
5 | PERIMETER_BOT_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 46.54 | 1.37 | 1 | 1 | 1 | 0.00 | 73.11 | 44.17 | 48.74 | 0.00 | 2.74 | 2.74 | 860.00 | TARP | TARP | 313.41 | 200.61 | 76.91 | 115.90 | 8 | 9 | 0 | Yes |
6 | PERIMETER_BOT_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 70.95 | 24.37 | 1.37 | 1 | 1 | 1 | 68.53 | 73.11 | 0.00 | 48.74 | 0.00 | 2.74 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 52.57 | 77.26 | 6 | 5 | 0 | Yes |
7 | PERIMETER_BOT_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 2.20 | 1.37 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 4.57 | 0.00 | 2.74 | 2.74 | 860.02 | TARP | TARP | 313.42 | 200.61 | 76.91 | 115.90 | 8 | 9 | 0 | Yes |
8 | PERIMETER_BOT_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.16 | 24.37 | 1.37 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 48.74 | 0.00 | 2.74 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 52.57 | 77.26 | 6 | 5 | 0 | Yes |
9 | PERIMETER_MID_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 46.54 | 18.14 | 1 | 10 | 1 | 0.00 | 73.11 | 44.17 | 48.74 | 16.77 | 19.51 | 2.74 | 860.00 | TARP | TARP | 313.41 | 200.61 | 84.71 | 115.90 | 7 | 1 | 0 | Yes |
10 | PERIMETER_MID_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 70.95 | 24.37 | 18.14 | 1 | 10 | 1 | 68.53 | 73.11 | 0.00 | 48.74 | 16.77 | 19.51 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 56.47 | 77.26 | 6 | 1 | 0 | Yes |
11 | PERIMETER_MID_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 2.20 | 18.14 | 1 | 10 | 1 | 0.00 | 73.11 | 0.00 | 4.57 | 16.77 | 19.51 | 2.74 | 860.02 | TARP | TARP | 313.42 | 200.61 | 84.71 | 115.90 | 7 | 1 | 0 | Yes |
12 | PERIMETER_MID_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.16 | 24.37 | 18.14 | 1 | 10 | 1 | 0.00 | 4.57 | 0.00 | 48.74 | 16.77 | 19.51 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 56.47 | 77.26 | 6 | 1 | 0 | Yes |
13 | PERIMETER_TOP_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 46.54 | 34.91 | 1 | 1 | 1 | 0.00 | 73.11 | 44.17 | 48.74 | 33.54 | 36.28 | 2.74 | 860.00 | TARP | TARP | 313.41 | 200.61 | 84.71 | 115.90 | 7 | 1 | 0 | Yes |
14 | PERIMETER_TOP_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 70.95 | 24.37 | 34.91 | 1 | 1 | 1 | 68.53 | 73.11 | 0.00 | 48.74 | 33.54 | 36.28 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 56.47 | 77.26 | 6 | 1 | 0 | Yes |
15 | PERIMETER_TOP_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 2.20 | 34.91 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 4.57 | 33.54 | 36.28 | 2.74 | 860.02 | TARP | TARP | 313.42 | 200.61 | 84.71 | 115.90 | 7 | 1 | 0 | Yes |
16 | PERIMETER_TOP_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.16 | 24.37 | 34.91 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 48.74 | 33.54 | 36.28 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 56.47 | 77.26 | 6 | 1 | 0 | Yes |
17 | GROUNDFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 24.37 | 3.35 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 48.74 | 2.74 | 3.96 | 1.22 | 4344.14 | TARP | TARP | 3563.11 | 297.11 | 297.11 | 0.00 | 11 | 0 | 0 | No |
18 | MIDFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 24.37 | 20.12 | 1 | 10 | 1 | 0.00 | 73.11 | 0.00 | 48.74 | 19.51 | 20.73 | 1.22 | 4344.14 | TARP | TARP | 3563.11 | 297.11 | 297.11 | 0.00 | 11 | 0 | 0 | No |
19 | TOPFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 24.37 | 36.89 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 48.74 | 36.28 | 37.50 | 1.22 | 4344.14 | TARP | TARP | 3563.11 | 297.11 | 297.11 | 0.00 | 11 | 0 | 0 | No |
20 | DATACENTER_BOT_ZN_6 | 0.0 | 5.49 | 44.17 | 0.00 | 5.03 | 24.37 | 1.37 | 1 | 1 | 1 | 4.57 | 5.49 | 4.57 | 44.17 | 0.00 | 2.74 | 2.74 | 99.34 | TARP | TARP | 36.20 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
21 | DATACENTER_MID_ZN_6 | 0.0 | 4.57 | 4.57 | 16.77 | 5.03 | 24.37 | 18.14 | 1 | 10 | 1 | 4.57 | 5.49 | 4.57 | 44.17 | 16.77 | 19.51 | 2.74 | 99.34 | TARP | TARP | 36.20 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
22 | DATACENTER_TOP_ZN_6 | 0.0 | 4.57 | 4.57 | 33.54 | 5.03 | 24.37 | 34.91 | 1 | 1 | 1 | 4.57 | 5.49 | 4.57 | 44.17 | 33.54 | 36.28 | 2.74 | 99.34 | TARP | TARP | 36.20 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
23 | DATACENTER_BASEMENT_ZN_6 | 0.0 | 16.08 | 0.00 | -2.44 | 8.04 | 24.37 | -1.22 | 1 | 1 | 1 | 0.00 | 16.08 | 0.00 | 48.74 | -2.44 | 0.00 | 2.44 | 1911.37 | TARP | TARP | 783.68 | 0.00 | 0.00 | 0.00 | 10 | 0 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | BASEMENT | 2779.43 | 149.6 | 18.579 | 5.382E-002 | 10.273 | 4.842 | 0.000 | 0.000 | 0.000 | 0.000 | 15.115 | No |
2 | CORE_BOTTOM | 2496.12 | 134.4 | 18.579 | 5.382E-002 | 10.273 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 18.343 | No |
3 | CORE_MID | 2496.12 | 134.4 | 18.579 | 5.382E-002 | 10.273 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 18.343 | No |
4 | CORE_TOP | 2496.12 | 134.4 | 18.579 | 5.382E-002 | 10.273 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 18.343 | No |
5 | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 18.579 | 5.382E-002 | 10.273 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 18.343 | No |
6 | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 10.273 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 18.343 | No |
7 | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 18.579 | 5.382E-002 | 10.273 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 18.343 | No |
8 | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 10.273 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 18.343 | No |
9 | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 18.579 | 5.382E-002 | 10.273 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 18.343 | No |
10 | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 10.273 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 18.343 | No |
11 | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 18.579 | 5.382E-002 | 10.273 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 18.343 | No |
12 | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 10.273 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 18.343 | No |
13 | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 18.579 | 5.382E-002 | 10.273 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 18.343 | No |
14 | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 10.273 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 18.343 | No |
15 | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 18.579 | 5.382E-002 | 10.273 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 18.343 | No |
16 | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 10.273 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 18.343 | No |
17 | GROUNDFLOOR_PLENUM | 3563.11 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
18 | MIDFLOOR_PLENUM | 3563.11 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
19 | TOPFLOOR_PLENUM | 3563.11 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
20 | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 18.579 | 5.382E-002 | 17.873 | 215.299 | 0.000 | 0.000 | 0.000 | 0.000 | 233.173 | No |
21 | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 18.579 | 5.382E-002 | 17.873 | 215.299 | 0.000 | 0.000 | 0.000 | 0.000 | 233.173 | No |
22 | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 18.579 | 5.382E-002 | 17.873 | 215.299 | 0.000 | 0.000 | 0.000 | 0.000 | 233.173 | No |
23 | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 18.579 | 5.382E-002 | 10.273 | 484.423 | 0.000 | 0.000 | 0.000 | 0.000 | 494.696 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | DATACENTER_BOT_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 1.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | DATACENTER_MID_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 1.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
3 | DATACENTER_TOP_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 1.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
4 | DATACENTER_BASEMENT_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 42.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 42 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
5 | BASEMENT | BLDG_OCC_SCH_WO_SB | BASEMENT | 2779.43 | 149.6 | 149.6 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 150 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
6 | CORE_BOTTOM | BLDG_OCC_SCH_WO_SB | CORE_BOTTOM | 2496.12 | 134.4 | 134.4 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 134 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
7 | CORE_MID | BLDG_OCC_SCH_WO_SB | CORE_MID | 2496.12 | 134.4 | 134.4 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 134 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
8 | CORE_TOP | BLDG_OCC_SCH_WO_SB | CORE_TOP | 2496.12 | 134.4 | 134.4 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 134 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
9 | PERIMETER_BOT_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
10 | PERIMETER_BOT_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
11 | PERIMETER_BOT_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
12 | PERIMETER_BOT_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
13 | PERIMETER_MID_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
14 | PERIMETER_MID_ZN_2 | BLDG_OCC_SCH_W_SB | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
15 | PERIMETER_MID_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
16 | PERIMETER_MID_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
17 | PERIMETER_TOP_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
18 | PERIMETER_TOP_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
19 | PERIMETER_TOP_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
20 | PERIMETER_TOP_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | BASEMENT_LIGHTS | LTG_SCH_OFFICE | BASEMENT | 2779.43 | 149.6 | 28553.717 | 10.273 | 190.864 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 28553.717 |
2 | CORE_BOTTOM_LIGHTS | LTG_SCH_OFFICE | CORE_BOTTOM | 2496.12 | 134.4 | 25643.245 | 10.273 | 190.864 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 25643.245 |
3 | CORE_MID_LIGHTS | LTG_SCH_OFFICE | CORE_MID | 2496.12 | 134.4 | 25643.245 | 10.273 | 190.864 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 25643.245 |
4 | CORE_TOP_LIGHTS | LTG_SCH_OFFICE | CORE_TOP | 2496.12 | 134.4 | 25643.245 | 10.273 | 190.864 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 25643.245 |
5 | PERIMETER_BOT_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 3219.765 | 10.273 | 190.864 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3219.765 |
6 | PERIMETER_BOT_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 2074.939 | 10.273 | 190.864 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2074.939 |
7 | PERIMETER_BOT_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 3219.836 | 10.273 | 190.864 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3219.836 |
8 | PERIMETER_BOT_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 2074.939 | 10.273 | 190.864 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2074.939 |
9 | PERIMETER_MID_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 3219.765 | 10.273 | 190.864 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3219.765 |
10 | PERIMETER_MID_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 2074.939 | 10.273 | 190.864 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2074.939 |
11 | PERIMETER_MID_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 3219.836 | 10.273 | 190.864 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3219.836 |
12 | PERIMETER_MID_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 2074.939 | 10.273 | 190.864 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2074.939 |
13 | PERIMETER_TOP_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 3219.765 | 10.273 | 190.864 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3219.765 |
14 | PERIMETER_TOP_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 2074.939 | 10.273 | 190.864 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2074.939 |
15 | PERIMETER_TOP_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 3219.836 | 10.273 | 190.864 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3219.836 |
16 | PERIMETER_TOP_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 2074.939 | 10.273 | 190.864 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2074.939 |
17 | DATACENTER_BASEMENT_LIGHTS | LTG_SCH_OFFICE | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 8050.927 | 10.273 | 190.864 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 8050.927 |
18 | DATACENTER_BOT_LIGHTS | LTG_SCH_DATACENTER | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 647.068 | 17.873 | 332.067 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 647.068 |
19 | DATACENTER_MID_LIGHTS | LTG_SCH_DATACENTER | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 647.068 | 17.873 | 332.067 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 647.068 |
20 | DATACENTER_TOP_LIGHTS | LTG_SCH_DATACENTER | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 647.068 | 17.873 | 332.067 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 647.068 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | BASEMENT_MISCPLUG_EQUIP | ALWAYS_ON | BASEMENT | 2779.43 | 149.6 | 13457.544 | 4.842 | 89.956 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 13457.544 | 13457.544 |
2 | CORE_BOTTOM_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_BOTTOM | 2496.12 | 134.4 | 20142.877 | 8.070 | 149.925 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 20142.877 |
3 | CORE_MID_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_MID | 2496.12 | 134.4 | 20142.800 | 8.070 | 149.924 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 20142.800 |
4 | CORE_TOP_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_TOP | 2496.12 | 134.4 | 20142.800 | 8.070 | 149.924 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 20142.800 |
5 | PERIMETER_BOT_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 2529.242 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.242 |
6 | PERIMETER_BOT_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 1629.940 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.940 |
7 | PERIMETER_BOT_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 2529.281 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.281 |
8 | PERIMETER_BOT_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 1629.929 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.929 |
9 | PERIMETER_MID_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 2529.242 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.242 |
10 | PERIMETER_MID_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 1629.940 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.940 |
11 | PERIMETER_MID_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 2529.281 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.281 |
12 | PERIMETER_MID_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 1629.929 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.929 |
13 | PERIMETER_TOP_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 2529.242 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.242 |
14 | PERIMETER_TOP_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 1629.940 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.940 |
15 | PERIMETER_TOP_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 2529.281 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.281 |
16 | PERIMETER_TOP_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 1629.929 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.929 |
17 | DATACENTER_BASEMENT_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 379632.522 | 484.423 | 9000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 94908.130 | 379632.522 |
18 | DATACENTER_BOT_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 7794.422 | 215.299 | 4000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 1948.606 | 7794.422 |
19 | DATACENTER_MID_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 7794.422 | 215.299 | 4000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 1948.606 | 7794.422 |
20 | DATACENTER_TOP_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 7794.422 | 215.299 | 4000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 1948.606 | 7794.422 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 2.839 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | INTERIORFURNISHINGS | 2 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
3 | DROPCEILING | 4 | 1 | 3 | 0.167 | 4.488 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
4 | INT_WALL | 7 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | EXT_SLAB_8IN_WITH_CARPET | 8 | 2 | 7 | 0.167 | 3.285 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
6 | INT_SLAB_FLOOR | 12 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
7 | INT_SLAB_CEILING | 13 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | VeryRough |
8 | NONRES_ROOF | 17 | 3 | 3 | 0.167 | 0.1864 | 0.900 | 0.900 | 0.700 | 0.700 | Rough |
9 | NONRES_EXT_WALL_GRD | 20 | 3 | 9 | 0.167 | 0.8952 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
10 | NONRES_EXT_WALL_MID | 21 | 3 | 9 | 0.167 | 0.8506 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
11 | NONRES_EXT_WALL_TOP | 22 | 3 | 9 | 0.167 | 1.077 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
12 | BASEMENT_WALL_EAST_CFACTOR | 39 | 2 | 7 | 0.167 | 0.3542 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | BASEMENT_WALL_SOUTH_CFACTOR | 40 | 2 | 7 | 0.167 | 0.3542 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | BASEMENT_WALL_NORTH_CFACTOR | 41 | 2 | 7 | 0.167 | 0.3542 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR | 42 | 2 | 7 | 0.167 | 0.3542 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
16 | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR | 43 | 2 | 7 | 0.167 | 0.3542 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
17 | DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR | 44 | 2 | 7 | 0.167 | 0.3542 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.3522 |
2 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
3 | AC02 ACOUSTIC CEILING | 0.0127 | 0.057 | 288.000 | 1339.000 | 0.2228 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | 200MM NORMALWEIGHT CONCRETE FLOOR | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
7 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
8 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
9 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
10 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
11 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
12 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
13 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 5.307 |
14 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
15 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
16 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9497 |
17 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
18 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
19 | NONRES_EXTERIOR_WALL_INSULATION_MID | 0.0000 | 0.000 | 0.000 | 0.000 | 1.008 |
20 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
21 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
22 | NONRES_EXTERIOR_WALL_INSULATION_TOP | 0.0000 | 0.000 | 0.000 | 0.000 | 0.7608 |
23 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
24 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.747 |
25 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
26 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.747 |
27 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
28 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.747 |
29 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
30 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.747 |
31 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
32 | ~FC_Insulation_5 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.747 |
33 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
34 | ~FC_Insulation_6 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.747 |
35 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 2.8391315 | 2.8391315 | 2.8391315 | |
3 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
4 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
5 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
6 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
7 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
8 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
9 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
10 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
11 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
12 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
13 | 3 | -0.21589802E-09 | 0.15643069E-09 | -0.21589802E-09 | 0.12999471E-21 |
14 | 2 | 0.50772448E-02 | 0.30006816E-02 | 0.50772448E-02 | -0.13693132E-08 |
15 | 1 | -2.5944910 | 1.4597758 | -2.5944910 | 0.76344767E-02 |
16 | 0 | 7.0433378 | 2.9911476 | 7.0433378 | |
17 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
18 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
19 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
20 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
21 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
22 | 7 | -0.18651654E-16 | -0.16428647E-15 | -0.26578847E-08 | -0.25364002E-17 |
23 | 6 | 0.67402962E-01 | 0.99142722E-07 | 0.38101547E-02 | -0.76639482E-03 |
24 | 5 | -1.8580732 | 0.49502125E-04 | -0.10651409 | 0.21891119E-01 |
25 | 4 | 18.220105 | 0.12801333E-02 | 1.0775450 | -0.22586539 |
26 | 3 | -79.928293 | 0.66708484E-02 | -4.9803755 | 1.0625663 |
27 | 2 | 166.43177 | 0.75131194E-02 | 11.128837 | -2.4125483 |
28 | 1 | -159.97298 | 0.18548900E-02 | -11.587784 | 2.5494418 |
29 | 0 | 57.057412 | 0.52755123E-04 | 4.4818272 | |
30 | 7 | 0.43260499E-16 | 0.34524919E-16 | 0.52793240E-17 | 0.0000000 |
31 | 6 | 0.69434179E-09 | 0.98085174E-11 | 0.18162501E-10 | -0.40870994E-12 |
32 | 5 | -0.12888762E-04 | 0.28373718E-06 | -0.16918523E-06 | 0.92361873E-08 |
33 | 4 | 0.25174112E-01 | 0.33697681E-03 | 0.22646198E-03 | -0.31467795E-04 |
34 | 3 | -3.7600775 | 0.27170599E-01 | -0.48495626E-01 | 0.94171705E-02 |
35 | 2 | 51.553741 | 0.22121684 | 1.2284947 | -0.25833933 |
36 | 1 | -128.86110 | 0.21944682 | -5.1479470 | 1.1228340 |
37 | 0 | 81.526494 | 0.16043334E-01 | 4.4519351 | |
38 | 7 | 0.52793240E-17 | 0.34524919E-16 | 0.43260499E-16 | 0.0000000 |
39 | 6 | 0.18162501E-10 | 0.98085174E-11 | 0.69434179E-09 | -0.40870994E-12 |
40 | 5 | -0.16918523E-06 | 0.28373718E-06 | -0.12888762E-04 | 0.92361873E-08 |
41 | 4 | 0.22646198E-03 | 0.33697681E-03 | 0.25174112E-01 | -0.31467795E-04 |
42 | 3 | -0.48495626E-01 | 0.27170599E-01 | -3.7600775 | 0.94171705E-02 |
43 | 2 | 1.2284947 | 0.22121684 | 51.553741 | -0.25833933 |
44 | 1 | -5.1479470 | 0.21944682 | -128.86110 | 1.1228340 |
45 | 0 | 4.4519351 | 0.16043334E-01 | 81.526494 | |
46 | 3 | -0.62854340E-06 | 0.84784826E-09 | -0.38512804E-05 | 0.91756347E-17 |
47 | 2 | 0.78257096 | 0.11428808E-02 | 1.0614277 | -0.73836085E-06 |
48 | 1 | -21.991499 | 0.76199851E-01 | -6.3161914 | 0.20349372 |
49 | 0 | 21.357363 | 0.71091016E-01 | 5.4032014 | |
50 | 9 | -0.25194710E-14 | 0.31545203E-16 | -0.15133332E-09 | 0.44281407E-16 |
51 | 8 | 0.22101568E-07 | 0.12077324E-12 | 0.38017447E-03 | -0.25130244E-09 |
52 | 7 | -0.12312625E-01 | 0.62550027E-08 | -0.23188143E-01 | 0.13999903E-03 |
53 | 6 | 0.40728147 | 0.21773539E-05 | 0.47373573 | -0.47705255E-02 |
54 | 5 | -5.2094091 | 0.81341902E-04 | -4.4538940 | 0.63417525E-01 |
55 | 4 | 33.086216 | 0.66572093E-03 | 21.489723 | -0.42322968 |
56 | 3 | -111.40360 | 0.14515221E-02 | -55.721658 | 1.5177572 |
57 | 2 | 197.30704 | 0.81680373E-03 | 77.964377 | -2.9035099 |
58 | 1 | -171.22951 | 0.87228510E-04 | -55.280715 | 2.7467265 |
59 | 0 | 57.057407 | 0.49677855E-06 | 15.554344 | |
60 | 9 | -0.24471812E-14 | 0.33150161E-16 | -0.15341684E-09 | 0.41895861E-16 |
61 | 8 | 0.22394247E-07 | 0.11501389E-12 | 0.38323131E-03 | -0.25463030E-09 |
62 | 7 | -0.12403778E-01 | 0.59379868E-08 | -0.23319368E-01 | 0.14103548E-03 |
63 | 6 | 0.40975819 | 0.20644311E-05 | 0.47584355 | -0.47997200E-02 |
64 | 5 | -5.2335779 | 0.77040749E-04 | -4.4700764 | 0.63717207E-01 |
65 | 4 | 33.193114 | 0.62990908E-03 | 21.552961 | -0.42464900 |
66 | 3 | -111.63102 | 0.13722529E-02 | -55.846672 | 1.5210429 |
67 | 2 | 197.53241 | 0.77160263E-03 | 78.079059 | -2.9070889 |
68 | 1 | -171.31275 | 0.82342669E-04 | -55.314112 | 2.7481854 |
69 | 0 | 57.057407 | 0.46858505E-06 | 15.548868 | |
70 | 9 | -0.15654789E-15 | 0.36780279E-16 | -0.14275499E-09 | -0.53833073E-18 |
71 | 8 | 0.20895136E-07 | 0.14393424E-12 | 0.36742668E-03 | -0.23758489E-09 |
72 | 7 | -0.11931991E-01 | 0.75543961E-08 | -0.22640018E-01 | 0.13567108E-03 |
73 | 6 | 0.39693859 | 0.26436989E-05 | 0.46492102 | -0.46486079E-02 |
74 | 5 | -5.1084706 | 0.99216708E-04 | -4.3861655 | 0.62165936E-01 |
75 | 4 | 32.639712 | 0.81537030E-03 | 21.224928 | -0.41730137 |
76 | 3 | -110.45353 | 0.17843548E-02 | -55.198128 | 1.5040313 |
77 | 2 | 196.36533 | 0.10073836E-02 | 77.484335 | -2.8885557 |
78 | 1 | -170.88163 | 0.10790658E-03 | -55.141337 | 2.7406295 |
79 | 0 | 57.057407 | 0.61658484E-06 | 15.577537 | |
80 | 7 | -0.11729247E-08 | -0.12287178E-15 | 0.68000855E-14 | -0.85819789E-16 |
81 | 6 | 0.99010087E-05 | 0.68275672E-08 | 0.31776201E-02 | -0.26656541E-04 |
82 | 5 | -0.71743827E-03 | 0.40498262E-05 | -0.22302824 | 0.19500041E-02 |
83 | 4 | 0.16534150E-01 | 0.18445051E-03 | 4.8179460 | -0.45153479E-01 |
84 | 3 | -0.14527752 | 0.14677644E-02 | -37.955880 | 0.39792938 |
85 | 2 | 0.51595076 | 0.24428280E-02 | 116.35639 | -1.4162330 |
86 | 1 | -0.74475336 | 0.74501918E-03 | -143.83221 | 2.0478056 |
87 | 0 | 0.36311555 | 0.17917760E-04 | 60.838472 | |
88 | 7 | -0.11729247E-08 | -0.12287178E-15 | 0.68000855E-14 | -0.85819789E-16 |
89 | 6 | 0.99010087E-05 | 0.68275672E-08 | 0.31776201E-02 | -0.26656541E-04 |
90 | 5 | -0.71743827E-03 | 0.40498262E-05 | -0.22302824 | 0.19500041E-02 |
91 | 4 | 0.16534150E-01 | 0.18445051E-03 | 4.8179460 | -0.45153479E-01 |
92 | 3 | -0.14527752 | 0.14677644E-02 | -37.955880 | 0.39792938 |
93 | 2 | 0.51595076 | 0.24428280E-02 | 116.35639 | -1.4162330 |
94 | 1 | -0.74475336 | 0.74501918E-03 | -143.83221 | 2.0478056 |
95 | 0 | 0.36311555 | 0.17917760E-04 | 60.838472 | |
96 | 7 | -0.11729247E-08 | -0.12287178E-15 | 0.68000855E-14 | -0.85819789E-16 |
97 | 6 | 0.99010087E-05 | 0.68275672E-08 | 0.31776201E-02 | -0.26656541E-04 |
98 | 5 | -0.71743827E-03 | 0.40498262E-05 | -0.22302824 | 0.19500041E-02 |
99 | 4 | 0.16534150E-01 | 0.18445051E-03 | 4.8179460 | -0.45153479E-01 |
100 | 3 | -0.14527752 | 0.14677644E-02 | -37.955880 | 0.39792938 |
101 | 2 | 0.51595076 | 0.24428280E-02 | 116.35639 | -1.4162330 |
102 | 1 | -0.74475336 | 0.74501918E-03 | -143.83221 | 2.0478056 |
103 | 0 | 0.36311555 | 0.17917760E-04 | 60.838472 | |
104 | 7 | -0.11729247E-08 | -0.12287178E-15 | 0.68000855E-14 | -0.85819789E-16 |
105 | 6 | 0.99010087E-05 | 0.68275672E-08 | 0.31776201E-02 | -0.26656541E-04 |
106 | 5 | -0.71743827E-03 | 0.40498262E-05 | -0.22302824 | 0.19500041E-02 |
107 | 4 | 0.16534150E-01 | 0.18445051E-03 | 4.8179460 | -0.45153479E-01 |
108 | 3 | -0.14527752 | 0.14677644E-02 | -37.955880 | 0.39792938 |
109 | 2 | 0.51595076 | 0.24428280E-02 | 116.35639 | -1.4162330 |
110 | 1 | -0.74475336 | 0.74501918E-03 | -143.83221 | 2.0478056 |
111 | 0 | 0.36311555 | 0.17917760E-04 | 60.838472 | |
112 | 7 | -0.11729247E-08 | -0.12287178E-15 | 0.68000855E-14 | -0.85819789E-16 |
113 | 6 | 0.99010087E-05 | 0.68275672E-08 | 0.31776201E-02 | -0.26656541E-04 |
114 | 5 | -0.71743827E-03 | 0.40498262E-05 | -0.22302824 | 0.19500041E-02 |
115 | 4 | 0.16534150E-01 | 0.18445051E-03 | 4.8179460 | -0.45153479E-01 |
116 | 3 | -0.14527752 | 0.14677644E-02 | -37.955880 | 0.39792938 |
117 | 2 | 0.51595076 | 0.24428280E-02 | 116.35639 | -1.4162330 |
118 | 1 | -0.74475336 | 0.74501918E-03 | -143.83221 | 2.0478056 |
119 | 0 | 0.36311555 | 0.17917760E-04 | 60.838472 | |
120 | 7 | -0.11729247E-08 | -0.12287178E-15 | 0.68000855E-14 | -0.85819789E-16 |
121 | 6 | 0.99010087E-05 | 0.68275672E-08 | 0.31776201E-02 | -0.26656541E-04 |
122 | 5 | -0.71743827E-03 | 0.40498262E-05 | -0.22302824 | 0.19500041E-02 |
123 | 4 | 0.16534150E-01 | 0.18445051E-03 | 4.8179460 | -0.45153479E-01 |
124 | 3 | -0.14527752 | 0.14677644E-02 | -37.955880 | 0.39792938 |
125 | 2 | 0.51595076 | 0.24428280E-02 | 116.35639 | -1.4162330 |
126 | 1 | -0.74475336 | 0.74501918E-03 | -143.83221 | 2.0478056 |
127 | 0 | 0.36311555 | 0.17917760E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | WINDOW_U_0.419_SHGC_EAST_0.4 | 35 | 1 | VerySmooth | 2.381 | 2.381 | 1.000 | 0.401 | ||
2 | WINDOW_U_0.419_SHGC_SOUTH_0.4 | 36 | 1 | VerySmooth | 2.381 | 2.381 | 1.000 | 0.401 | ||
3 | WINDOW_U_0.419_SHGC_WEST_0.4 | 37 | 1 | VerySmooth | 2.381 | 2.381 | 1.000 | 0.401 | ||
4 | WINDOW_U_0.419_SHGC_NORTH_0.4 | 38 | 1 | VerySmooth | 2.381 | 2.381 | 1.000 | 0.401 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | GLAZING LAYER EAST | SpectralAverage | 3.03930E-002 | 0.31435 | 0.47506 | 0.47506 | 0.44000 | 0.13397 | 0.17027 | 0.00000 | 0.84000 | 0.84000 | 0.12237 | 1.00000 | No | |
2 | GLAZING LAYER SOUTH | SpectralAverage | 3.03930E-002 | 0.31435 | 0.47506 | 0.47506 | 0.44000 | 0.13397 | 0.17027 | 0.00000 | 0.84000 | 0.84000 | 0.12237 | 1.00000 | No | |
3 | GLAZING LAYER WEST | SpectralAverage | 3.03930E-002 | 0.31435 | 0.47506 | 0.47506 | 0.44000 | 0.13397 | 0.17027 | 0.00000 | 0.84000 | 0.84000 | 0.12237 | 1.00000 | No | |
4 | GLAZING LAYER NORTH | SpectralAverage | 3.03930E-002 | 0.31435 | 0.47506 | 0.47506 | 0.44000 | 0.13397 | 0.17027 | 0.00000 | 0.84000 | 0.84000 | 0.12237 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 30 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Enclosure Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Enclosures | |
1 | PERIMETER_BOT_ZN_3 | 5 | 0 |
2 | PERIMETER_BOT_ZN_2 | 3 | 0 |
3 | PERIMETER_BOT_ZN_1 | 5 | 0 |
4 | PERIMETER_BOT_ZN_4 | 3 | 0 |
5 | PERIMETER_MID_ZN_3 | 1 | 0 |
6 | PERIMETER_MID_ZN_2 | 1 | 0 |
7 | PERIMETER_MID_ZN_1 | 1 | 0 |
8 | PERIMETER_MID_ZN_4 | 1 | 0 |
9 | PERIMETER_TOP_ZN_3 | 1 | 0 |
10 | PERIMETER_TOP_ZN_2 | 1 | 0 |
11 | PERIMETER_TOP_ZN_1 | 1 | 0 |
12 | PERIMETER_TOP_ZN_4 | 1 | 0 |
Enclosure Name | Number of Adjacent Enclosures with Windows | Adjacent Enclosure Names - 1st 100 (max) | |
1 | PERIMETER_BOT_ZN_3 | 0 | |
2 | PERIMETER_BOT_ZN_2 | 0 | |
3 | PERIMETER_BOT_ZN_1 | 0 | |
4 | PERIMETER_BOT_ZN_4 | 0 | |
5 | PERIMETER_MID_ZN_3 | 0 | |
6 | PERIMETER_MID_ZN_2 | 0 | |
7 | PERIMETER_MID_ZN_1 | 0 | |
8 | PERIMETER_MID_ZN_4 | 0 | |
9 | PERIMETER_TOP_ZN_3 | 0 | |
10 | PERIMETER_TOP_ZN_2 | 0 | |
11 | PERIMETER_TOP_ZN_1 | 0 | |
12 | PERIMETER_TOP_ZN_4 | 0 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 1.1356 | 87921.3 | 0.481 | 5.5005E-002 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | BASEMENT_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
2 | BASEMENT_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
3 | BASEMENT_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
4 | BASEMENT_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
5 | BASEMENT_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
6 | PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
7 | PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
8 | CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
9 | PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
10 | BASEMENT_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
11 | CORE_BOT_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
12 | CORE_BOT_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
13 | CORE_BOT_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
14 | CORE_BOT_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
15 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
16 | CORE_BOT_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
17 | CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
18 | CORE_BOTTOM_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
19 | CORE_MID_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
20 | CORE_MID_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
21 | CORE_MID_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
22 | CORE_MID_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
23 | CORE_MID_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
24 | CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
25 | CORE_MID_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
26 | CORE_TOP_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
27 | CORE_TOP_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
28 | CORE_TOP_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
29 | CORE_TOP_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
30 | CORE_TOP_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
31 | CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
32 | CORE_TOP_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
33 | PERIMETER_BOT_ZN_3_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
34 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
35 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
36 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
37 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
38 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
39 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
40 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
41 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
42 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
43 | PERIMETER_BOT_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
44 | CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
45 | PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
46 | DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
47 | PERIMETER_BOT_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
48 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
49 | PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
50 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
51 | PERIMETER_BOT_ZN_2_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
52 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
53 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
54 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
55 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
56 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
57 | PERIMETER_BOT_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
58 | CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
59 | PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
60 | PERIMETER_BOT_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
61 | PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
62 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
63 | PERIMETER_BOT_ZN_1_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
64 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
65 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
66 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
67 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
68 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
69 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
70 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
71 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
72 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
73 | PERIMETER_BOT_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
74 | DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
75 | PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
76 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
77 | DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
78 | PERIMETER_BOT_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
79 | PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
80 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
81 | PERIMETER_BOT_ZN_4_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
82 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
83 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
84 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
85 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
86 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
87 | PERIMETER_BOT_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
88 | DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
89 | PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
90 | PERIMETER_BOT_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
91 | PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
92 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
93 | PERIMETER_MID_ZN_3_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
94 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
95 | PERIMETER_MID_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
96 | CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
97 | PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
98 | DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
99 | PERIMETER_MID_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
100 | PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
101 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
102 | PERIMETER_MID_ZN_2_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
103 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
104 | PERIMETER_MID_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
105 | CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
106 | PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
107 | PERIMETER_MID_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
108 | PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
109 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
110 | PERIMETER_MID_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
111 | PERIMETER_MID_ZN_1_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
112 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
113 | DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
114 | PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
115 | CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
116 | PERIMETER_MID_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
117 | PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
118 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
119 | PERIMETER_MID_ZN_4_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
120 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
121 | PERIMETER_MID_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
122 | DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
123 | PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
124 | PERIMETER_MID_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
125 | PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
126 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
127 | PERIMETER_TOP_ZN_3_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
128 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
129 | PERIMETER_TOP_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
130 | CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
131 | PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
132 | DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
133 | PERIMETER_TOP_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
134 | PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
135 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
136 | PERIMETER_TOP_ZN_2_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
137 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
138 | PERIMETER_TOP_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
139 | CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
140 | INT-PER3S-NE-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
141 | PERIMETER_TOP_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
142 | PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
143 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
144 | PERIMETER_TOP_ZN_1_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
145 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
146 | INT-PER3S-NE | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
147 | DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
148 | PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
149 | CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
150 | PERIMETER_TOP_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
151 | PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
152 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
153 | PERIMETER_TOP_ZN_4_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
154 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
155 | PERIMETER_TOP_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
156 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
157 | PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
158 | PERIMETER_TOP_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
159 | PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
160 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
161 | GROUNDFLOOR_PLENUM_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
162 | GROUNDFLOOR_PLENUM_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
163 | GROUNDFLOOR_PLENUM_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
164 | GROUNDFLOOR_PLENUM_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
165 | iz-CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
166 | iz-PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
167 | iz-PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
168 | iz-PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
169 | iz-PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
170 | iz-DATACENTER_BOT_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
171 | GROUNDFLOOR_PLENUM_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
172 | MIDFLOOR_PLENUM_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
173 | MIDFLOOR_PLENUM_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
174 | MIDFLOOR_PLENUM_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
175 | MIDFLOOR_PLENUM_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
176 | iz-CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
177 | iz-PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
178 | iz-PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
179 | iz-PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
180 | iz-PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
181 | iz-DATACENTER_MID_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
182 | MIDFLOOR_PLENUM_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
183 | TOPFLOOR_PLENUM_WALL_NORTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
184 | TOPFLOOR_PLENUM_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
185 | TOPFLOOR_PLENUM_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
186 | TOPFLOOR_PLENUM_WALL_SOUTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
187 | iz-CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
188 | iz-PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
189 | iz-PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
190 | iz-PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
191 | iz-PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
192 | iz-DATACENTER_TOP_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
193 | BUILDING_ROOF | 0 | 3563.11 | 268.06 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
194 | DATACENTER_BOT_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
195 | DATACENTER_BOT_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
196 | DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
197 | DATACENTER_BOT_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
198 | DATACENTER_BOT_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
199 | DATACENTER_BOT_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
200 | DATACENTER_MID_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
201 | DATACENTER_MID_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
202 | DATACENTER_MID_ZN_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
203 | DATACENTER_MID_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
204 | DATACENTER_MID_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
205 | DATACENTER_MID_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
206 | DATACENTER_TOP_ZN_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
207 | DATACENTER_TOP_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
208 | DATACENTER_TOP_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
209 | DATACENTER_TOP_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
210 | DATACENTER_TOP_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
211 | DATACENTER_TOP_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
212 | DATACENTER_BASEMENT_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
213 | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
214 | DATACENTER_BASEMENT_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
215 | DATACENTER_BASEMENT_ZN_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
216 | DATACENTER_BASEMENT_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
217 | DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
218 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
219 | PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
220 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
221 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | PERIMETER_BOT_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 0.114 | 3.646E-004 | 5.482E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | PERIMETER_BOT_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 7.617E-002 | 3.771E-004 | 5.534E-004 | 0.495 | 0.000 | 0.000 | 0.224 | 0.000 |
3 | PERIMETER_BOT_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 0.114 | 3.646E-004 | 5.482E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | PERIMETER_BOT_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 7.617E-002 | 3.771E-004 | 5.534E-004 | 0.495 | 0.000 | 0.000 | 0.224 | 0.000 |
5 | PERIMETER_MID_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 0.114 | 3.646E-004 | 5.696E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
6 | PERIMETER_MID_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 7.617E-002 | 3.771E-004 | 5.696E-004 | 0.495 | 0.000 | 0.000 | 0.224 | 0.000 |
7 | PERIMETER_MID_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 0.114 | 3.646E-004 | 5.696E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
8 | PERIMETER_MID_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 7.617E-002 | 3.771E-004 | 5.696E-004 | 0.495 | 0.000 | 0.000 | 0.224 | 0.000 |
9 | PERIMETER_TOP_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 0.114 | 3.646E-004 | 5.696E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
10 | PERIMETER_TOP_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 7.617E-002 | 3.771E-004 | 5.696E-004 | 0.495 | 0.000 | 0.000 | 0.224 | 0.000 |
11 | PERIMETER_TOP_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 0.114 | 3.646E-004 | 5.696E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
12 | PERIMETER_TOP_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 7.617E-002 | 3.771E-004 | 5.696E-004 | 0.495 | 0.000 | 0.000 | 0.224 | 0.000 |
13 | GROUNDFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | GROUNDFLOOR_PLENUM | 3563.11 | 0.0 | 0.169 | 4.749E-005 | 5.696E-004 | 0.140 | 0.000 | 0.000 | 0.224 | 0.000 |
14 | MIDFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | MIDFLOOR_PLENUM | 3563.11 | 0.0 | 0.169 | 4.749E-005 | 5.696E-004 | 0.140 | 0.000 | 0.000 | 0.224 | 0.000 |
15 | TOPFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | TOPFLOOR_PLENUM | 3563.11 | 0.0 | 0.169 | 4.749E-005 | 4.384E-005 | 0.140 | 0.000 | 0.000 | 0.224 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | BASEMENT | Mixing/Well-Stirred |
2 | CORE_BOTTOM | Mixing/Well-Stirred |
3 | CORE_MID | Mixing/Well-Stirred |
4 | CORE_TOP | Mixing/Well-Stirred |
5 | PERIMETER_BOT_ZN_3 | Mixing/Well-Stirred |
6 | PERIMETER_BOT_ZN_2 | Mixing/Well-Stirred |
7 | PERIMETER_BOT_ZN_1 | Mixing/Well-Stirred |
8 | PERIMETER_BOT_ZN_4 | Mixing/Well-Stirred |
9 | PERIMETER_MID_ZN_3 | Mixing/Well-Stirred |
10 | PERIMETER_MID_ZN_2 | Mixing/Well-Stirred |
11 | PERIMETER_MID_ZN_1 | Mixing/Well-Stirred |
12 | PERIMETER_MID_ZN_4 | Mixing/Well-Stirred |
13 | PERIMETER_TOP_ZN_3 | Mixing/Well-Stirred |
14 | PERIMETER_TOP_ZN_2 | Mixing/Well-Stirred |
15 | PERIMETER_TOP_ZN_1 | Mixing/Well-Stirred |
16 | PERIMETER_TOP_ZN_4 | Mixing/Well-Stirred |
17 | GROUNDFLOOR_PLENUM | Mixing/Well-Stirred |
18 | MIDFLOOR_PLENUM | Mixing/Well-Stirred |
19 | TOPFLOOR_PLENUM | Mixing/Well-Stirred |
20 | DATACENTER_BOT_ZN_6 | Mixing/Well-Stirred |
21 | DATACENTER_MID_ZN_6 | Mixing/Well-Stirred |
22 | DATACENTER_TOP_ZN_6 | Mixing/Well-Stirred |
23 | DATACENTER_BASEMENT_ZN_6 | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sky Type | MonthAndDay | Daylighting Control Name | Enclosure Name | Window Name | Reference Point | Daylight Factor | |
1 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 7.4596E-003 |
2 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 7.4620E-003 |
3 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 8.2632E-003 |
4 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 8.2651E-003 |
5 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 5.0368E-003 |
6 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 5.0383E-003 |
7 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.7740E-003 |
8 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.7748E-003 |
9 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 7.5132E-003 |
10 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 7.6704E-003 |
11 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 8.3084E-003 |
12 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 8.4453E-003 |
13 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 5.0752E-003 |
14 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 5.1886E-003 |
15 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.7969E-003 |
16 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.8551E-003 |
17 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 0.1799 |
18 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 9.2440E-002 |
19 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 0.2047 |
20 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 0.1055 |
21 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 0.1228 |
22 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.9791E-002 |
23 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 5.0165E-002 |
24 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.7447E-002 |
25 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 7.5206E-003 |
26 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 7.7084E-003 |
27 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 8.3163E-003 |
28 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 8.4868E-003 |
29 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 5.0816E-003 |
30 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 5.2133E-003 |
31 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.7974E-003 |
32 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.8568E-003 |
33 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 7.4594E-003 |
34 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 7.4620E-003 |
35 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 8.2629E-003 |
36 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 8.2651E-003 |
37 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 5.0367E-003 |
38 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 5.0384E-003 |
39 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.7739E-003 |
40 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.7747E-003 |
41 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 6.4568E-003 |
42 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 6.8498E-003 |
43 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 6.2220E-003 |
44 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 6.6661E-003 |
45 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 5.7453E-003 |
46 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 5.8947E-003 |
47 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 4.7428E-003 |
48 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 4.7830E-003 |
49 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 7.2950E-002 |
50 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.5489E-002 |
51 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 6.9225E-002 |
52 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.2751E-002 |
53 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 6.9709E-002 |
54 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 2.8992E-002 |
55 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 5.2230E-002 |
56 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 1.9536E-002 |
57 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 6.3331E-003 |
58 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 6.4495E-003 |
59 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 6.0604E-003 |
60 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 6.1452E-003 |
61 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 5.6983E-003 |
62 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 5.7317E-003 |
63 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 4.7430E-003 |
64 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 4.7836E-003 |
65 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.9585E-003 |
66 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.9608E-003 |
67 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.5094E-003 |
68 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.5113E-003 |
69 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.2088E-003 |
70 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.2102E-003 |
71 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.7740E-003 |
72 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.7749E-003 |
73 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.0109E-003 |
74 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 3.1451E-003 |
75 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.5526E-003 |
76 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.6601E-003 |
77 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.2444E-003 |
78 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.3235E-003 |
79 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.7975E-003 |
80 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.8569E-003 |
81 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 4.8063E-002 |
82 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.5388E-002 |
83 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.6867E-002 |
84 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.9237E-002 |
85 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.3089E-002 |
86 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.2866E-002 |
87 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 5.0165E-002 |
88 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.7442E-002 |
89 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.0087E-003 |
90 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 3.1436E-003 |
91 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.5497E-003 |
92 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.6551E-003 |
93 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.2393E-003 |
94 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.3080E-003 |
95 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.7969E-003 |
96 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.8551E-003 |
97 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.9583E-003 |
98 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.9606E-003 |
99 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.5093E-003 |
100 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.5111E-003 |
101 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.2086E-003 |
102 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.2099E-003 |
103 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.7739E-003 |
104 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.7748E-003 |
105 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 5.7519E-003 |
106 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 5.8722E-003 |
107 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 5.3242E-003 |
108 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 5.4111E-003 |
109 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 5.2601E-003 |
110 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 5.2911E-003 |
111 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 4.7431E-003 |
112 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 4.7837E-003 |
113 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 6.2813E-002 |
114 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.1406E-002 |
115 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 5.6472E-002 |
116 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.7601E-002 |
117 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 6.1608E-002 |
118 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.5730E-002 |
119 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 5.2230E-002 |
120 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 1.9536E-002 |
121 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 5.8513E-003 |
122 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 6.1534E-003 |
123 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 5.4549E-003 |
124 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 5.7822E-003 |
125 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 5.3043E-003 |
126 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 5.4402E-003 |
127 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 4.7428E-003 |
128 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 4.7829E-003 |
129 | Clear Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 0.1791 |
130 | Clear Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 0.1262 |
131 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 0.1977 |
132 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 0.1423 |
133 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 0.1362 |
134 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 7.3357E-002 |
135 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 6.1425E-002 |
136 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 3.0380E-002 |
137 | Clear Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 8.6718E-002 |
138 | Clear Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 5.1010E-002 |
139 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 8.2579E-002 |
140 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 4.7764E-002 |
141 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 8.2507E-002 |
142 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 4.2602E-002 |
143 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 6.2997E-002 |
144 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 3.0728E-002 |
145 | Clear Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 5.9517E-002 |
146 | Clear Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 3.9644E-002 |
147 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 4.6848E-002 |
148 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 3.1251E-002 |
149 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 4.2723E-002 |
150 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 2.3273E-002 |
151 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 6.1425E-002 |
152 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 3.0375E-002 |
153 | Clear Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 7.5252E-002 |
154 | Clear Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 4.5376E-002 |
155 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 6.8142E-002 |
156 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 4.0644E-002 |
157 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 7.3433E-002 |
158 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 3.8279E-002 |
159 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 6.2997E-002 |
160 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 3.0728E-002 |
161 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 0.1791 |
162 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 0.1264 |
163 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 0.1978 |
164 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 0.1426 |
165 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 0.1364 |
166 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 7.3537E-002 |
167 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 6.1557E-002 |
168 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 3.0447E-002 |
169 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 8.6778E-002 |
170 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 5.1089E-002 |
171 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 8.2648E-002 |
172 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 4.7841E-002 |
173 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 8.2633E-002 |
174 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 4.2693E-002 |
175 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 6.3129E-002 |
176 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 3.0795E-002 |
177 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 5.9521E-002 |
178 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 3.9689E-002 |
179 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 4.6856E-002 |
180 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 3.1287E-002 |
181 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 4.2791E-002 |
182 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 2.3317E-002 |
183 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 6.1557E-002 |
184 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 3.0442E-002 |
185 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 7.5294E-002 |
186 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 4.5442E-002 |
187 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 6.8190E-002 |
188 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 4.0704E-002 |
189 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 7.3545E-002 |
190 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 3.8358E-002 |
191 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 6.3129E-002 |
192 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 3.0795E-002 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | BASEMENT | Cooling | 82624.53127 | 82624.53127 | 6.23910 | 6.23910 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 23.35600 | 1.53506E-002 | 2779.42662 | 149.60210 | 1.20016 | 0.00000 |
2 | BASEMENT | Heating | 0.00000 | 0.00000 | 0.00000 | 1.20016 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -26.20000 | 3.61342E-004 | 2779.42662 | 149.60210 | 1.20016 | 0.00000 |
3 | CORE_BOTTOM | Cooling | 85568.35145 | 85568.35145 | 6.46058 | 6.46058 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 23.35600 | 1.53506E-002 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 |
4 | CORE_BOTTOM | Heating | 9918.52332 | 9918.52332 | 0.43914 | 1.07782 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -26.20000 | 3.61342E-004 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 |
5 | CORE_MID | Cooling | 805876.83084 | 805876.83084 | 60.83111 | 60.83111 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 23.35600 | 1.53506E-002 | 2496.12046 | 134.35320 | 10.77825 | 0.00000 |
6 | CORE_MID | Heating | 383361.52675 | 383361.52675 | 17.01974 | 17.01974 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -26.20000 | 3.61342E-004 | 2496.12046 | 134.35320 | 10.77825 | 0.00000 |
7 | CORE_TOP | Cooling | 80045.98570 | 80045.98570 | 6.04235 | 6.04235 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 23.35600 | 1.53506E-002 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 |
8 | CORE_TOP | Heating | 80213.96264 | 80213.96264 | 3.57859 | 3.57859 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -26.20000 | 3.61342E-004 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 |
9 | PERIMETER_BOT_ZN_3 | Cooling | 14221.61517 | 14221.61517 | 1.08339 | 1.08339 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 | 31.20000 | 1.53651E-002 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
10 | PERIMETER_BOT_ZN_3 | Heating | 16776.69055 | 16776.69055 | 0.74982 | 0.74982 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -26.20000 | 3.61342E-004 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
11 | PERIMETER_BOT_ZN_2 | Cooling | 19431.04775 | 19431.04775 | 1.48022 | 1.48022 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:30:00 | 24.36300 | 1.53525E-002 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
12 | PERIMETER_BOT_ZN_2 | Heating | 11241.98593 | 11241.98593 | 0.50250 | 0.50250 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -26.20000 | 3.61342E-004 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
13 | PERIMETER_BOT_ZN_1 | Cooling | 22023.27209 | 22023.27209 | 1.67770 | 1.67770 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:10:00 | 30.75833 | 1.53643E-002 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
14 | PERIMETER_BOT_ZN_1 | Heating | 17643.48391 | 17643.48391 | 0.78866 | 0.78866 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -26.20000 | 3.61342E-004 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
15 | PERIMETER_BOT_ZN_4 | Cooling | 23424.65464 | 23424.65464 | 1.78444 | 1.78444 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 | 29.53933 | 1.53620E-002 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
16 | PERIMETER_BOT_ZN_4 | Heating | 9741.54554 | 9741.54554 | 0.43525 | 0.43525 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -26.20000 | 3.61342E-004 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
17 | PERIMETER_MID_ZN_3 | Cooling | 135743.57250 | 135743.57250 | 10.34190 | 10.34190 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 31.20000 | 1.53651E-002 | 313.41284 | 16.86939 | 1.35332 | 0.00000 |
18 | PERIMETER_MID_ZN_3 | Heating | 248978.33875 | 248978.33875 | 11.13630 | 11.13630 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -26.20000 | 3.61342E-004 | 313.41284 | 16.86939 | 1.35332 | 0.00000 |
19 | PERIMETER_MID_ZN_2 | Cooling | 206474.21323 | 206474.21323 | 15.73044 | 15.73044 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:10:00 | 25.67033 | 1.53549E-002 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
20 | PERIMETER_MID_ZN_2 | Heating | 162593.03967 | 162593.03967 | 7.27259 | 7.27259 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -26.20000 | 3.61342E-004 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
21 | PERIMETER_MID_ZN_1 | Cooling | 222142.42936 | 222142.42936 | 16.92421 | 16.92421 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 30.93500 | 1.53646E-002 | 313.41969 | 16.86975 | 1.35335 | 0.00000 |
22 | PERIMETER_MID_ZN_1 | Heating | 245012.15303 | 245012.15303 | 10.95858 | 10.95858 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -26.20000 | 3.61342E-004 | 313.41969 | 16.86975 | 1.35335 | 0.00000 |
23 | PERIMETER_MID_ZN_4 | Cooling | 219816.01568 | 219816.01568 | 16.74685 | 16.74685 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:20:00 | 29.36267 | 1.53617E-002 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
24 | PERIMETER_MID_ZN_4 | Heating | 161317.63962 | 161317.63962 | 7.21549 | 7.21549 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -26.20000 | 3.61342E-004 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
25 | PERIMETER_TOP_ZN_3 | Cooling | 15271.66939 | 15271.66939 | 1.16355 | 1.16355 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | 31.20000 | 1.53651E-002 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
26 | PERIMETER_TOP_ZN_3 | Heating | 31034.82592 | 31034.82592 | 1.38853 | 1.38853 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -26.20000 | 3.61342E-004 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
27 | PERIMETER_TOP_ZN_2 | Cooling | 20758.56037 | 20758.56037 | 1.58158 | 1.58158 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:20:00 | 25.97067 | 1.53554E-002 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
28 | PERIMETER_TOP_ZN_2 | Heating | 20222.12659 | 20222.12659 | 0.90477 | 0.90477 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -26.20000 | 3.61342E-004 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
29 | PERIMETER_TOP_ZN_1 | Cooling | 23802.06567 | 23802.06567 | 1.81346 | 1.81346 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 30.93500 | 1.53646E-002 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
30 | PERIMETER_TOP_ZN_1 | Heating | 30604.97758 | 30604.97758 | 1.36927 | 1.36927 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -26.20000 | 3.61342E-004 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
31 | PERIMETER_TOP_ZN_4 | Cooling | 23065.26279 | 23065.26279 | 1.75731 | 1.75731 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:20:00 | 29.36267 | 1.53617E-002 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
32 | PERIMETER_TOP_ZN_4 | Heating | 20284.73531 | 20284.73531 | 0.90758 | 0.90758 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -26.20000 | 3.61342E-004 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
33 | DATACENTER_BOT_ZN_6 | Cooling | 8864.92465 | 8864.92465 | 0.53261 | 0.53261 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:10:00 | 26.87167 | 1.53571E-002 | 36.20274 | 1.94861 | 1.56323E-002 | 0.00000 |
34 | DATACENTER_BOT_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 1.56323E-002 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 05:30:00 | -26.20000 | 3.61342E-004 | 36.20274 | 1.94861 | 1.56323E-002 | 0.00000 |
35 | DATACENTER_MID_ZN_6 | Cooling | 85172.53835 | 85172.53835 | 5.11722 | 5.11722 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:10:00 | 26.87167 | 1.53571E-002 | 36.20274 | 1.94861 | 0.15632 | 0.00000 |
36 | DATACENTER_MID_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 0.15632 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 05:40:00 | -26.20000 | 3.61342E-004 | 36.20274 | 1.94861 | 0.15632 | 0.00000 |
37 | DATACENTER_TOP_ZN_6 | Cooling | 8657.41438 | 8657.41438 | 0.52014 | 0.52014 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:10:00 | 26.87167 | 1.53571E-002 | 36.20274 | 1.94861 | 1.56323E-002 | 0.00000 |
38 | DATACENTER_TOP_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 1.56323E-002 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 05:30:00 | -26.20000 | 3.61342E-004 | 36.20274 | 1.94861 | 1.56323E-002 | 0.00000 |
39 | DATACENTER_BASEMENT_ZN_6 | Cooling | 373483.52459 | 373483.52459 | 22.43880 | 22.43880 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 07:00:00 | 21.55400 | 1.53473E-002 | 783.67941 | 42.18139 | 0.33839 | 0.00000 |
40 | DATACENTER_BASEMENT_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 0.33839 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 07:00:00 | -26.20000 | 3.61342E-004 | 783.67941 | 42.18139 | 0.33839 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | VAV_BOT WITH REHEAT | Cooling | Sensible | 156265.36 | 10.70650 | 10.70650 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
2 | VAV_BOT WITH REHEAT | Heating | Sensible | 114240.98 | 3.55405 | 3.55405 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 06:20:00 |
3 | VAV_MID WITH REHEAT | Cooling | Sensible | 1456346.65 | 100.08575 | 100.08575 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
4 | VAV_MID WITH REHEAT | Heating | Sensible | 1138921.66 | 53.60271 | 53.60271 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 05:10:00 |
5 | VAV_TOP WITH REHEAT | Cooling | Sensible | 163136.87 | 11.00699 | 11.00699 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
6 | VAV_TOP WITH REHEAT | Heating | Sensible | 114160.08 | 8.14874 | 8.14874 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
7 | CAV_BAS | Cooling | Sensible | 81058.74 | 6.23910 | 6.23910 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
8 | CAV_BAS | Heating | Sensible | 91696.53 | 1.20016 | 1.20016 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
9 | AIRLOOP DATACENTER BASEMENT | Cooling | Sensible | 368915.88 | 22.43891 | 22.43891 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
10 | AIRLOOP DATACENTER BASEMENT | Heating | Sensible | 25854.50 | 0.33839 | 0.33839 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
11 | AIRLOOP DATACENTER BOT | Cooling | Sensible | 8725.56 | 0.53261 | 0.53261 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
12 | AIRLOOP DATACENTER BOT | Heating | Sensible | 1194.37 | 1.56323E-002 | 1.56323E-002 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
13 | AIRLOOP DATACENTER MID | Cooling | Sensible | 83832.62 | 5.11722 | 5.11722 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
14 | AIRLOOP DATACENTER MID | Heating | Sensible | 11943.71 | 0.15632 | 0.15632 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
15 | AIRLOOP DATACENTER TOP | Cooling | Sensible | 8521.25 | 0.52014 | 0.52014 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
16 | AIRLOOP DATACENTER TOP | Heating | Sensible | 1194.37 | 1.56323E-002 | 1.56323E-002 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | BASEMENT DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 6.23910 |
2 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 6.46058 |
3 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.29441 |
4 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30800 |
5 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.98986 |
6 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.78509 |
7 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
8 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.29412E-003 |
9 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.53956E-004 |
10 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.98986 |
11 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
12 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
13 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 29028.74453 |
14 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.53956E-004 |
15 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 616.74605 |
16 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 60.83111 |
17 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.31268 |
18 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.32100 |
19 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 19.52679 |
20 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.83380 |
21 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
22 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.21851E-003 |
23 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 4.99442E-003 |
24 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 19.52679 |
25 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
26 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
27 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 570892.97079 |
28 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 4.99442E-003 |
29 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 14491.92158 |
30 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 6.04235 |
31 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.31479 |
32 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.33100 |
33 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.00002 |
34 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.83943 |
35 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
36 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.21035E-003 |
37 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.00241E-003 |
38 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 3.57859 |
39 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
40 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
41 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 114582.06016 |
42 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.00241E-003 |
43 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 3023.60408 |
44 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.08339 |
45 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.22044 |
46 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.23000 |
47 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.24918 |
48 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.58783 |
49 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
50 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.72838E-003 |
51 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.09707E-004 |
52 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.74982 |
53 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
54 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
55 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 23970.79731 |
56 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.09707E-004 |
57 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 632.09207 |
58 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.48022 |
59 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.10397 |
60 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
61 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.29604 |
62 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
63 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
64 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.66435E-003 |
65 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.40528E-004 |
66 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.50250 |
67 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
68 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
69 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 16063.23965 |
70 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.40528E-004 |
71 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 423.56220 |
72 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.67770 |
73 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.14235 |
74 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
75 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.33554 |
76 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.37961 |
77 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
78 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.67645E-003 |
79 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.20553E-004 |
80 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.78866 |
81 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
82 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
83 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 25210.56156 |
84 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.20553E-004 |
85 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 664.76223 |
86 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.78444 |
87 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 8.62483E-002 |
88 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
89 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.35689 |
90 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
91 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
92 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 4.41748E-003 |
93 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.21751E-004 |
94 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.43525 |
95 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
96 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
97 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 13916.89802 |
98 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.21751E-004 |
99 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 367.00946 |
100 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 11.13630 |
101 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.21445 |
102 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.23700 |
103 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.63930 |
104 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.57187 |
105 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
106 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.77662E-003 |
107 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 3.11234E-003 |
108 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 11.13630 |
109 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
110 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
111 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 355759.66972 |
112 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.11234E-003 |
113 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 9378.05464 |
114 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 15.73044 |
115 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 9.78390E-002 |
116 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
117 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 3.14609 |
118 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
119 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
120 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.89415E-003 |
121 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.03248E-003 |
122 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 7.27259 |
123 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
124 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
125 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 232324.52674 |
126 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.03248E-003 |
127 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 6124.16254 |
128 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 16.92421 |
129 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.14111 |
130 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
131 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 3.38484 |
132 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.37631 |
133 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
134 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.69993E-003 |
135 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 3.06272E-003 |
136 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 10.95858 |
137 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
138 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
139 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 350087.60121 |
140 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.06272E-003 |
141 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 9228.60052 |
142 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 16.74685 |
143 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 9.19009E-002 |
144 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
145 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 3.34937 |
146 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
147 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
148 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 4.14577E-003 |
149 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.01652E-003 |
150 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 7.21549 |
151 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
152 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
153 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 230500.90640 |
154 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.01652E-003 |
155 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 6076.09707 |
156 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.38853 |
157 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.17200 |
158 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.21600 |
159 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.29992 |
160 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.45865 |
161 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
162 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.21518E-003 |
163 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 3.87973E-004 |
164 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.38853 |
165 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
166 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
167 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 44347.66332 |
168 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.87973E-004 |
169 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 1168.90995 |
170 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.58158 |
171 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 9.73112E-002 |
172 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
173 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.31632 |
174 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
175 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
176 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.91527E-003 |
177 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.52799E-004 |
178 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.90477 |
179 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
180 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
181 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 28896.44754 |
182 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.52799E-004 |
183 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 761.64259 |
184 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.81346 |
185 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.13170 |
186 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
187 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.36269 |
188 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.35119 |
189 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
190 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.89302E-003 |
191 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 3.82595E-004 |
192 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.36927 |
193 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
194 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
195 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 43732.97721 |
196 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.82595E-004 |
197 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 1152.71311 |
198 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.75731 |
199 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 8.75798E-002 |
200 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
201 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.35146 |
202 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
203 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
204 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 4.35032E-003 |
205 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.53582E-004 |
206 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.90758 |
207 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
208 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
209 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 28986.02084 |
210 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.53582E-004 |
211 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 764.00128 |
212 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DATACENTER_BOT_ZN_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.53261 |
213 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DATACENTER_MID_ZN_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 5.11722 |
214 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DATACENTER_TOP_ZN_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.52014 |
215 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DATACENTER_BASEMENT_ZN_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 22.43880 |
216 | AirLoopHVAC | VAV_BOT WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 6.24317 |
217 | AirLoopHVAC | VAV_BOT WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 3.22751 |
218 | AirLoopHVAC | VAV_BOT WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 12.48634 |
219 | AirLoopHVAC | VAV_BOT WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 3.55405 |
220 | AirLoopHVAC | VAV_BOT WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 10.70650 |
221 | AirLoopHVAC | VAV_BOT WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 10.70650 |
222 | AirLoopHVAC | VAV_BOT WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
223 | AirLoopHVAC | VAV_BOT WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.33195 |
224 | AirLoopHVAC | VAV_MID WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 60.68446 |
225 | AirLoopHVAC | VAV_MID WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 32.04639 |
226 | AirLoopHVAC | VAV_MID WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 121.36891 |
227 | AirLoopHVAC | VAV_MID WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 53.60271 |
228 | AirLoopHVAC | VAV_MID WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 100.08575 |
229 | AirLoopHVAC | VAV_MID WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 100.08575 |
230 | AirLoopHVAC | VAV_MID WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
231 | AirLoopHVAC | VAV_MID WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.53557 |
232 | AirLoopHVAC | VAV_TOP WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 6.29162 |
233 | AirLoopHVAC | VAV_TOP WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 3.33041 |
234 | AirLoopHVAC | VAV_TOP WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 12.58323 |
235 | AirLoopHVAC | VAV_TOP WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 8.14874 |
236 | AirLoopHVAC | VAV_TOP WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 11.00699 |
237 | AirLoopHVAC | VAV_TOP WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 11.00699 |
238 | AirLoopHVAC | VAV_TOP WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
239 | AirLoopHVAC | VAV_TOP WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.74032 |
240 | AirLoopHVAC | CAV_BAS | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 6.23910 |
241 | AirLoopHVAC | CAV_BAS | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 6.23910 |
242 | AirLoopHVAC | CAV_BAS | Sum of Air Terminal Maximum Flow Rates [m3/s] | 6.23910 |
243 | AirLoopHVAC | CAV_BAS | Adjusted Heating Design Air Flow Rate [m3/s] | 6.23910 |
244 | AirLoopHVAC | CAV_BAS | Adjusted Cooling Design Air Flow Rate [m3/s] | 6.23910 |
245 | AirLoopHVAC | CAV_BAS | Adjusted Main Design Air Flow Rate [m3/s] | 6.23910 |
246 | AirLoopHVAC | CAV_BAS | User Heating Air Flow Ratio [] | 1.00000 |
247 | AirLoopHVAC | CAV_BAS | Calculated Heating Air Flow Ratio [] | 1.00000 |
248 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 22.43880 |
249 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 22.43880 |
250 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 22.43880 |
251 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Adjusted Heating Design Air Flow Rate [m3/s] | 22.43880 |
252 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Adjusted Cooling Design Air Flow Rate [m3/s] | 22.43891 |
253 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Adjusted Main Design Air Flow Rate [m3/s] | 22.43891 |
254 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | User Heating Air Flow Ratio [] | 1.00000 |
255 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Calculated Heating Air Flow Ratio [] | 0.99999 |
256 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.53261 |
257 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.53261 |
258 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.53261 |
259 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Adjusted Heating Design Air Flow Rate [m3/s] | 0.53261 |
260 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.53261 |
261 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Adjusted Main Design Air Flow Rate [m3/s] | 0.53261 |
262 | AirLoopHVAC | AIRLOOP DATACENTER BOT | User Heating Air Flow Ratio [] | 1.00000 |
263 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Calculated Heating Air Flow Ratio [] | 1.00000 |
264 | AirLoopHVAC | AIRLOOP DATACENTER MID | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 5.11722 |
265 | AirLoopHVAC | AIRLOOP DATACENTER MID | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 5.11722 |
266 | AirLoopHVAC | AIRLOOP DATACENTER MID | Sum of Air Terminal Maximum Flow Rates [m3/s] | 5.11722 |
267 | AirLoopHVAC | AIRLOOP DATACENTER MID | Adjusted Heating Design Air Flow Rate [m3/s] | 5.11722 |
268 | AirLoopHVAC | AIRLOOP DATACENTER MID | Adjusted Cooling Design Air Flow Rate [m3/s] | 5.11722 |
269 | AirLoopHVAC | AIRLOOP DATACENTER MID | Adjusted Main Design Air Flow Rate [m3/s] | 5.11722 |
270 | AirLoopHVAC | AIRLOOP DATACENTER MID | User Heating Air Flow Ratio [] | 1.00000 |
271 | AirLoopHVAC | AIRLOOP DATACENTER MID | Calculated Heating Air Flow Ratio [] | 1.00000 |
272 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.52014 |
273 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.52014 |
274 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.52014 |
275 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Adjusted Heating Design Air Flow Rate [m3/s] | 0.52014 |
276 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.52014 |
277 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Adjusted Main Design Air Flow Rate [m3/s] | 0.52014 |
278 | AirLoopHVAC | AIRLOOP DATACENTER TOP | User Heating Air Flow Ratio [] | 1.00000 |
279 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Calculated Heating Air Flow Ratio [] | 1.00000 |
280 | AirLoopHVAC | VAV_BOT WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 10.70650 |
281 | AirLoopHVAC | VAV_MID WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 100.08575 |
282 | AirLoopHVAC | VAV_TOP WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 11.00699 |
283 | AirLoopHVAC | CAV_BAS | Design Supply Air Flow Rate [m3/s] | 6.23910 |
284 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Design Supply Air Flow Rate [m3/s] | 22.43891 |
285 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Design Supply Air Flow Rate [m3/s] | 0.53261 |
286 | AirLoopHVAC | AIRLOOP DATACENTER MID | Design Supply Air Flow Rate [m3/s] | 5.11722 |
287 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Design Supply Air Flow Rate [m3/s] | 0.52014 |
288 | Controller:OutdoorAir | VAV_BOT WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 10.70650 |
289 | Controller:OutdoorAir | VAV_BOT WITH REHEAT_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 2.53819 |
290 | HeatExchanger:AirToAir:SensibleAndLatent | VAV_BOT WITH REHEAT OA HEAT RECOVERY | Design Size Nominal Supply Air Flow Rate [m3/s] | 2.53819 |
291 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Inlet Air Temperature [C] | 25.74617 |
292 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
293 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Outlet Air Temperature [C] | 10.86911 |
294 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 1.04615E-002 |
295 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
296 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Coil Load [W] | 248199.40761 |
297 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 1.05590E-002 |
298 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 10.70650 |
299 | Coil:Heating:Water | VAV_BOT WITH REHEAT HEATING COIL | Design Size Rated Capacity [W] | 109143.00321 |
300 | Coil:Heating:Water | VAV_BOT WITH REHEAT HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 9.54831E-004 |
301 | Coil:Heating:Water | VAV_BOT WITH REHEAT HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 1667.89830 |
302 | Fan:VariableVolume | VAV_BOT WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 10.70650 |
303 | Controller:WaterCoil | VAV_BOT WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 1.05590E-002 |
304 | Controller:WaterCoil | VAV_BOT WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 4.50982E-005 |
305 | Controller:WaterCoil | VAV_BOT WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 9.54831E-004 |
306 | Controller:OutdoorAir | VAV_MID WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 100.08575 |
307 | Controller:OutdoorAir | VAV_MID WITH REHEAT_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 25.38195 |
308 | HeatExchanger:AirToAir:SensibleAndLatent | VAV_MID WITH REHEAT OA HEAT RECOVERY | Design Size Nominal Supply Air Flow Rate [m3/s] | 25.38195 |
309 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Inlet Air Temperature [C] | 25.89487 |
310 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
311 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Outlet Air Temperature [C] | 10.86994 |
312 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 1.06976E-002 |
313 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
314 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Coil Load [W] | 2406793.32897 |
315 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 0.10239 |
316 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 100.08575 |
317 | Coil:Heating:Water | VAV_MID WITH REHEAT HEATING COIL | Design Size Rated Capacity [W] | 1114716.07538 |
318 | Coil:Heating:Water | VAV_MID WITH REHEAT HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 9.75202E-003 |
319 | Coil:Heating:Water | VAV_MID WITH REHEAT HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 16651.03156 |
320 | Fan:VariableVolume | VAV_MID WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 100.08575 |
321 | Controller:WaterCoil | VAV_MID WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 0.10239 |
322 | Controller:WaterCoil | VAV_MID WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 4.65073E-006 |
323 | Controller:WaterCoil | VAV_MID WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 9.75202E-003 |
324 | Controller:OutdoorAir | VAV_TOP WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 11.00699 |
325 | Controller:OutdoorAir | VAV_TOP WITH REHEAT_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 2.53819 |
326 | HeatExchanger:AirToAir:SensibleAndLatent | VAV_TOP WITH REHEAT OA HEAT RECOVERY | Design Size Nominal Supply Air Flow Rate [m3/s] | 2.53819 |
327 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Inlet Air Temperature [C] | 25.66097 |
328 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
329 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Outlet Air Temperature [C] | 10.86915 |
330 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 1.04721E-002 |
331 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
332 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Coil Load [W] | 254402.43596 |
333 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 1.08229E-002 |
334 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 11.00699 |
335 | Coil:Heating:Water | VAV_TOP WITH REHEAT HEATING COIL | Design Size Rated Capacity [W] | 109771.98532 |
336 | Coil:Heating:Water | VAV_TOP WITH REHEAT HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 9.60333E-004 |
337 | Coil:Heating:Water | VAV_TOP WITH REHEAT HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 1686.85418 |
338 | Fan:VariableVolume | VAV_TOP WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 11.00699 |
339 | Controller:WaterCoil | VAV_TOP WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 1.08229E-002 |
340 | Controller:WaterCoil | VAV_TOP WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 4.39985E-005 |
341 | Controller:WaterCoil | VAV_TOP WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 9.60333E-004 |
342 | Controller:OutdoorAir | CAV_BAS_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 6.23910 |
343 | Controller:OutdoorAir | CAV_BAS_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.20016 |
344 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Inlet Air Temperature [C] | 25.23619 |
345 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
346 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Outlet Air Temperature [C] | 11.35829 |
347 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 1.03179E-002 |
348 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
349 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Coil Load [W] | 134691.93490 |
350 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 5.73011E-003 |
351 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 6.23910 |
352 | Coil:Heating:Water | CAV_BAS HEATING COIL | Design Size Rated Capacity [W] | 324321.76664 |
353 | Coil:Heating:Water | CAV_BAS HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.83731E-003 |
354 | Coil:Heating:Water | CAV_BAS HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 6941.86305 |
355 | Fan:ConstantVolume | CAV_BAS FAN | Design Size Maximum Flow Rate [m3/s] | 6.23910 |
356 | Controller:WaterCoil | CAV_BAS_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 5.73011E-003 |
357 | Controller:WaterCoil | CAV_BAS_COOLC_CONTROLLER | Controller Convergence Tolerance | 8.31033E-005 |
358 | Controller:WaterCoil | CAV_BAS_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 2.83731E-003 |
359 | Controller:OutdoorAir | AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 22.43891 |
360 | Controller:OutdoorAir | AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.33839 |
361 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 22.43891 |
362 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Rated Total Cooling Capacity [W] | 441003.93415 |
363 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Rated Sensible Cooling Capacity [W] | 302154.35358 |
364 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Rated Water Flow Rate [m3/s] | 1.08002E-002 |
365 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 22.43891 |
366 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 22.43891 |
367 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 22.43891 |
368 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 22.43891 |
369 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Nominal Heating Capacity [W] | 441003.93415 |
370 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 441003.93415 |
371 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 25854.49862 |
372 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
373 | Fan:OnOff | AIRLOOP DATACENTER BASEMENT SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 22.43891 |
374 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 22.43891 |
375 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT HEATING COIL | Design Size Rated Heating Capacity [W] | 441003.93415 |
376 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT HEATING COIL | Design Size Rated Water Flow Rate [m3/s] | 1.08002E-002 |
377 | Coil:Heating:Electric | AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 25854.49862 |
378 | Humidifier:Steam:Electric | DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | Design Size Nominal Capacity Volume [m3/s] | 2.02014E-004 |
379 | Humidifier:Steam:Electric | DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | User-Specified Nominal Capacity Volume [m3/s] | 3.72000E-005 |
380 | Humidifier:Steam:Electric | DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | Design Size Rated Power [W] | 96450.69782 |
381 | Humidifier:Steam:Electric | DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | User-Specified Rated Power [W] | 100000.00000 |
382 | Controller:OutdoorAir | AIRLOOP DATACENTER BOT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.53261 |
383 | Controller:OutdoorAir | AIRLOOP DATACENTER BOT_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.56323E-002 |
384 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.53261 |
385 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT COOLING COIL | Design Size Rated Total Cooling Capacity [W] | 10359.22070 |
386 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT COOLING COIL | Design Size Rated Sensible Cooling Capacity [W] | 7125.88934 |
387 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT COOLING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.53697E-004 |
388 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 0.53261 |
389 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 0.53261 |
390 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 0.53261 |
391 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 0.53261 |
392 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Nominal Heating Capacity [W] | 10359.22070 |
393 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 10359.22070 |
394 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 1194.37073 |
395 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
396 | Fan:OnOff | AIRLOOP DATACENTER BOT SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.53261 |
397 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.53261 |
398 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT HEATING COIL | Design Size Rated Heating Capacity [W] | 10359.22070 |
399 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT HEATING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.53697E-004 |
400 | Coil:Heating:Electric | AIRLOOP DATACENTER BOT_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 1194.37073 |
401 | Controller:OutdoorAir | AIRLOOP DATACENTER MID_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 5.11722 |
402 | Controller:OutdoorAir | AIRLOOP DATACENTER MID_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.15632 |
403 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 5.11722 |
404 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID COOLING COIL | Design Size Rated Total Cooling Capacity [W] | 99679.44455 |
405 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID COOLING COIL | Design Size Rated Sensible Cooling Capacity [W] | 68510.10517 |
406 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID COOLING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.44114E-003 |
407 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 5.11722 |
408 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 5.11722 |
409 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 5.11722 |
410 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 5.11722 |
411 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Nominal Heating Capacity [W] | 99679.44455 |
412 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 99679.44455 |
413 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 11943.70727 |
414 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
415 | Fan:OnOff | AIRLOOP DATACENTER MID SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 5.11722 |
416 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 5.11722 |
417 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID HEATING COIL | Design Size Rated Heating Capacity [W] | 99679.44455 |
418 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID HEATING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.44114E-003 |
419 | Coil:Heating:Electric | AIRLOOP DATACENTER MID_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 11943.70727 |
420 | Controller:OutdoorAir | AIRLOOP DATACENTER TOP_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.52014 |
421 | Controller:OutdoorAir | AIRLOOP DATACENTER TOP_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.56323E-002 |
422 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.52014 |
423 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP COOLING COIL | Design Size Rated Total Cooling Capacity [W] | 10125.78575 |
424 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP COOLING COIL | Design Size Rated Sensible Cooling Capacity [W] | 6961.85750 |
425 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP COOLING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.47980E-004 |
426 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 0.52014 |
427 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 0.52014 |
428 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 0.52014 |
429 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 0.52014 |
430 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Nominal Heating Capacity [W] | 10125.78575 |
431 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 10125.78575 |
432 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 1194.37073 |
433 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
434 | Fan:OnOff | AIRLOOP DATACENTER TOP SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.52014 |
435 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.52014 |
436 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP HEATING COIL | Design Size Rated Heating Capacity [W] | 10125.78575 |
437 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP HEATING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.47980E-004 |
438 | Coil:Heating:Electric | AIRLOOP DATACENTER TOP_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 1194.37073 |
439 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Flow Rate [m3/s] | 0.12950 |
440 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Power Consumption [W] | 21143.80151 |
441 | PlantLoop | COOLSYS1_DEMAND | Maximum Loop Flow Rate [m3/s] | 0.12950 |
442 | PlantLoop | COOLSYS1_DEMAND | Plant Loop Volume [m3] | 15.54030 |
443 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Loop Supply Side Design Fluid Flow Rate [m3/s] | 0.12950 |
444 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Loop Demand Side Design Fluid Flow Rate [m3/s] | 0.12950 |
445 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Heat Exchanger U-Factor Times Area Value [W/C] | 543586.98347 |
446 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Loop-to-loop Temperature Difference Used to Size Heat Exchanger U-Factor Times Area Value [C] | 5.60000 |
447 | PlantLoop | HEATSYS1 | Maximum Loop Flow Rate [m3/s] | 3.29488E-002 |
448 | PlantLoop | HEATSYS1 | Plant Loop Volume [m3] | 3.95386 |
449 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Flow Rate [m3/s] | 3.29488E-002 |
450 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Power Consumption [W] | 9922.74133 |
451 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Minimum Flow Rate [m3/s] | 0.00000 |
452 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Nominal Capacity [W] | 3766253.91555 |
453 | Boiler:HotWater | HEATSYS1 BOILER | User-Specified Nominal Capacity [W] | 3766253.92000 |
454 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Design Water Flow Rate [m3/s] | 3.29488E-002 |
455 | PlantLoop | COOLSYS1_SUPPLY | Maximum Loop Flow Rate [m3/s] | 0.12950 |
456 | PlantLoop | COOLSYS1_SUPPLY | Plant Loop Volume [m3] | 15.54030 |
457 | Pump:ConstantSpeed | COOLSYS1 CHILLER1 PUMP | Design Flow Rate [m3/s] | 6.47513E-002 |
458 | Pump:ConstantSpeed | COOLSYS1 CHILLER1 PUMP | Design Power Consumption [W] | 7319.28342 |
459 | Pump:ConstantSpeed | COOLSYS1 CHILLER2 PUMP | Design Flow Rate [m3/s] | 6.47513E-002 |
460 | Pump:ConstantSpeed | COOLSYS1 CHILLER2 PUMP | Design Power Consumption [W] | 7319.28342 |
461 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | Design Size Reference Chilled Water Flow Rate [m3/s] | 0.12950 |
462 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | User-Specified Reference Chilled Water Flow Rate [m3/s] | 6.50950E-002 |
463 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | Design Size Reference Capacity [W] | 1533882.41560 |
464 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | User-Specified Reference Capacity [W] | 1541163.98000 |
465 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | Design Size Reference Condenser Water Flow Rate [m3/s] | 7.62665E-002 |
466 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | Design Size Reference Chilled Water Flow Rate [m3/s] | 0.12950 |
467 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | User-Specified Reference Chilled Water Flow Rate [m3/s] | 6.50950E-002 |
468 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | Design Size Reference Capacity [W] | 1533882.41560 |
469 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | User-Specified Reference Capacity [W] | 1541163.98000 |
470 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | Design Size Reference Condenser Water Flow Rate [m3/s] | 7.62665E-002 |
471 | PlantLoop | SINGLE WATER PLANT LOOP | Maximum Loop Flow Rate [m3/s] | 1.37430E-002 |
472 | PlantLoop | SINGLE WATER PLANT LOOP | Plant Loop Volume [m3] | 1.64916 |
473 | Pump:ConstantSpeed | PLANT CIRC PUMP | Design Flow Rate [m3/s] | 1.37430E-002 |
474 | Pump:ConstantSpeed | PLANT CIRC PUMP | Design Power Consumption [W] | 3505.14655 |
475 | FluidCooler:TwoSpeed | CENTRAL TOWER | Design Water Flow Rate [m3/s] | 1.37430E-002 |
476 | FluidCooler:TwoSpeed | CENTRAL TOWER | Air Flow Rate at High Fan Speed [m3/s] | 139666.46671 |
477 | FluidCooler:TwoSpeed | CENTRAL TOWER | Fluid cooler UA value at high fan speed based on nominal capacity input [W/K] | 57601.40386 |
478 | FluidCooler:TwoSpeed | CENTRAL TOWER | Air Flow Rate at Low Fan Speed [m3/s] | 69833.23335 |
479 | FluidCooler:TwoSpeed | CENTRAL TOWER | Fan Power at Low Fan Speed [W] | 7879.72339 |
480 | FluidCooler:TwoSpeed | CENTRAL TOWER | U-factor Times Area Value at Low Fan Speed [W/C] | 21245.38230 |
481 | Boiler:HotWater | CENTRAL BOILER | Design Size Nominal Capacity [W] | 566092.85933 |
482 | Boiler:HotWater | CENTRAL BOILER | User-Specified Nominal Capacity [W] | 554972.71000 |
483 | Boiler:HotWater | CENTRAL BOILER | Design Size Design Water Flow Rate [m3/s] | 1.37430E-002 |
484 | PlantLoop | SWHSYS1 | Maximum Loop Flow Rate [m3/s] | 4.40000E-004 |
485 | PlantLoop | SWHSYS1 | Plant Loop Volume [m3] | 5.28000E-002 |
486 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Flow Rate [m3/s] | 4.40000E-004 |
487 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Power Consumption [W] | 56.20530 |
488 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | Use Side Design Flow Rate [m3/s] | 4.40000E-004 |
489 | CondenserLoop | TOWERWATERSYS | Maximum Loop Flow Rate [m3/s] | 0.15253 |
490 | CondenserLoop | TOWERWATERSYS | Condenser Loop Volume [m3] | 18.30396 |
491 | HeaderedPumps:VariableSpeed | TOWERWATERSYS PUMP | Design Flow Rate [m3/s] | 0.15253 |
492 | HeaderedPumps:VariableSpeed | TOWERWATERSYS PUMP | Design Power Consumption [W] | 37763.79277 |
493 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Design Air Flow Rate [m3/s] | 61.47497 |
494 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Nominal Capacity [W] | 1828568.75056 |
495 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Air Flow Rate in free convection regime [m3/s] | 12.29499 |
496 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Tower capacity in free convection regime at design conditions [W] | 228571.09382 |
497 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Design Air Flow Rate [m3/s] | 61.47497 |
498 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Nominal Capacity [W] | 1828568.75056 |
499 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Air Flow Rate in free convection regime [m3/s] | 12.29499 |
500 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Tower capacity in free convection regime at design conditions [W] | 228571.09382 |
501 | PlantEquipmentOperation:ComponentSetPoint | WSHPPLANT OPERATION SCHEME | Design Water Flow Rate [m3/s] Equipment # 47 | 7.92175E-002 |
502 | PlantEquipmentOperation:ComponentSetPoint | WSHPPLANT OPERATION SCHEME | Design Water Flow Rate [m3/s] Equipment # 47 | 7.92175E-002 |
Component Type | Name | Nominal Total Capacity {W} | |
1 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | 27517.82 |
2 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | 540714.21 |
3 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | 108580.01 |
4 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | 22712.12 |
5 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | 15219.69 |
6 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | 23886.64 |
7 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | 13186.35 |
8 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | 337058.56 |
9 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | 220111.57 |
10 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | 331685.09 |
11 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | 218383.86 |
12 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | 42015.62 |
13 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | 27376.87 |
14 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | 41433.29 |
15 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | 27461.72 |
16 | Coil:Heating:Water | VAV_BOT WITH REHEAT HEATING COIL | 72731.02 |
17 | Coil:Heating:Water | VAV_MID WITH REHEAT HEATING COIL | 722965.68 |
18 | Coil:Heating:Water | VAV_TOP WITH REHEAT HEATING COIL | 73625.83 |
19 | Coil:Heating:Water | CAV_BAS HEATING COIL | 245312.06 |
Component Type | Name | Nominal Total Capacity {W} | Nominal Sensible Capacity {W} | Nominal Latent Capacity {W} | Nominal Sensible Heat Ratio | Nominal Coil UA Value {W/C} | Nominal Coil Surface Area {m2} | |
1 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | 282122.08 | 187095.26 | 95026.82 | 0.66 | 30552.16 | 309.88 |
2 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | 2676071.22 | 1766429.60 | 909641.63 | 0.66 | 290147.16 | 2942.83 |
3 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | 289783.17 | 192236.59 | 97546.58 | 0.66 | 31397.88 | 318.45 |
4 | Coil:Cooling:Water | CAV_BAS COOLING COIL | 157427.78 | 105734.63 | 51693.14 | 0.67 | 16614.98 | 168.52 |
Component Type | Component Name | IPLV in SI Units {W/W} | IPLV in IP Units {Btu/W-h} | |
1 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | 6.84 | 23.33 |
2 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | 6.84 | 23.33 |
Zone Name | # Surfaces | |
1 | BASEMENT | 10 |
2 | CORE_BOTTOM | 8 |
3 | CORE_MID | 7 |
4 | CORE_TOP | 7 |
5 | PERIMETER_BOT_ZN_3 | 18 |
6 | PERIMETER_BOT_ZN_2 | 12 |
7 | PERIMETER_BOT_ZN_1 | 18 |
8 | PERIMETER_BOT_ZN_4 | 12 |
9 | PERIMETER_MID_ZN_3 | 9 |
10 | PERIMETER_MID_ZN_2 | 8 |
11 | PERIMETER_MID_ZN_1 | 9 |
12 | PERIMETER_MID_ZN_4 | 8 |
13 | PERIMETER_TOP_ZN_3 | 9 |
14 | PERIMETER_TOP_ZN_2 | 8 |
15 | PERIMETER_TOP_ZN_1 | 9 |
16 | PERIMETER_TOP_ZN_4 | 8 |
17 | GROUNDFLOOR_PLENUM | 11 |
18 | MIDFLOOR_PLENUM | 11 |
19 | TOPFLOOR_PLENUM | 11 |
20 | DATACENTER_BOT_ZN_6 | 6 |
21 | DATACENTER_MID_ZN_6 | 6 |
22 | DATACENTER_TOP_ZN_6 | 6 |
23 | DATACENTER_BASEMENT_ZN_6 | 10 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | BASEMENT_WALL_EAST | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_EAST_CFACTOR | 0.354 | 0.336 | 118.87 | 118.87 | 118.87 | 90.00 | 90.00 | 48.74 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | BASEMENT_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_SOUTH_CFACTOR | 0.354 | 0.336 | 139.09 | 139.09 | 139.09 | 180.00 | 90.00 | 57.03 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
3 | BASEMENT_WALL_NORTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_NORTH_CFACTOR | 0.354 | 0.336 | 139.09 | 139.09 | 139.09 | 0.00 | 90.00 | 57.03 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | BASEMENT_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.87 | 118.87 | 118.87 | 270.00 | 90.00 | 48.74 | 2.44 | 0.00 | DATACENTER_BASEMENT_ZN_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
5 | BASEMENT_FLOOR | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 2779.43 | 2779.43 | 2779.43 | 0.00 | 180.00 | 57.03 | 48.74 | 0.00 | BASEMENT_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
6 | PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | PERIMETER_BOT_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
7 | PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 250.34 | 250.34 | 250.34 | 180.00 | 0.00 | 57.03 | 4.57 | 0.00 | PERIMETER_BOT_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
8 | CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 2076.77 | 2076.77 | 2076.77 | 180.00 | 0.00 | 52.45 | 39.59 | 0.00 | CORE_BOT_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
9 | PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 250.34 | 250.34 | 250.34 | 180.00 | 0.00 | 52.45 | 4.57 | 0.00 | PERIMETER_BOT_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
10 | BASEMENT_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 7126.21 | 7126.21 | 7126.21 | 0.00 | 90.00 | 7126.21 | 1.00 | 0.00 | BASEMENT_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
11 | CORE_BOT_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
12 | CORE_BOT_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
13 | CORE_BOT_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
14 | CORE_BOT_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
15 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 419.30 | 419.30 | 419.30 | 0.00 | 180.00 | 10.59 | 39.59 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
16 | CORE_BOT_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 2076.82 | 2076.82 | 2076.82 | 0.00 | 180.00 | 52.46 | 39.59 | 0.00 | CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
17 | CORE_BOT_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 2496.12 | 2496.12 | 2496.12 | 180.00 | 0.00 | 63.05 | 39.59 | 0.00 | iz-CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
18 | CORE_BOTTOM_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 5064.65 | 5064.65 | 5064.65 | 0.00 | 90.00 | 5064.65 | 1.00 | 0.00 | CORE_BOTTOM_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
19 | CORE_MID_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
20 | CORE_MID_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
21 | CORE_MID_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
22 | CORE_MID_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
23 | CORE_MID_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_MID_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
24 | CORE_MID_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 2496.12 | 2496.12 | 2496.12 | 180.00 | 0.00 | 63.05 | 39.59 | 0.00 | iz-CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
25 | CORE_MID_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 5064.65 | 5064.65 | 5064.65 | 0.00 | 90.00 | 5064.65 | 1.00 | 0.00 | CORE_MID_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
26 | CORE_TOP_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
27 | CORE_TOP_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
28 | CORE_TOP_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
29 | CORE_TOP_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
30 | CORE_TOP_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_TOP_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
31 | CORE_TOP_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 2496.12 | 2496.12 | 2496.12 | 180.00 | 0.00 | 63.05 | 39.59 | 0.00 | iz-CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
32 | CORE_TOP_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 5064.65 | 5064.65 | 5064.65 | 0.00 | 90.00 | 5064.65 | 1.00 | 0.00 | CORE_TOP_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
33 | PERIMETER_BOT_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.895 | 0.789 | 76.91 | 200.61 | 76.91 | 0.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
34 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.419_SHGC_NORTH_0.4 | N/A | 2.381 | No | 23.18 | 23.18 | 23.18 | 0.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
35 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.419_SHGC_NORTH_0.4 | N/A | 2.381 | No | 23.18 | 23.18 | 23.18 | 0.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
36 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.419_SHGC_NORTH_0.4 | N/A | 2.381 | No | 23.18 | 23.18 | 23.18 | 0.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
37 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.419_SHGC_NORTH_0.4 | N/A | 2.381 | No | 23.18 | 23.18 | 23.18 | 0.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
38 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.419_SHGC_NORTH_0.4 | N/A | 2.381 | No | 23.18 | 23.18 | 23.18 | 0.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
39 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.839 | 2.839 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
40 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.839 | 2.839 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
41 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.839 | 2.839 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
42 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.839 | 2.839 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
43 | PERIMETER_BOT_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
44 | CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
45 | PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
46 | DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
47 | PERIMETER_BOT_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 250.34 | 250.34 | 250.34 | 0.00 | 180.00 | 52.46 | 6.47 | 0.00 | PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
48 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 63.07 | 63.07 | 63.07 | 0.00 | 180.00 | 11.51 | 4.57 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
49 | PERIMETER_BOT_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.41 | 313.41 | 313.41 | 180.00 | 0.00 | 63.96 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
50 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.83 | 626.83 | 626.83 | 0.00 | 90.00 | 626.83 | 1.00 | 0.00 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
51 | PERIMETER_BOT_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.895 | 0.789 | 52.57 | 133.74 | 52.57 | 90.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
52 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.419_SHGC_EAST_0.4 | N/A | 2.381 | No | 25.75 | 25.75 | 25.75 | 90.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
53 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.419_SHGC_EAST_0.4 | N/A | 2.381 | No | 25.75 | 25.75 | 25.75 | 90.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
54 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.419_SHGC_EAST_0.4 | N/A | 2.381 | No | 25.75 | 25.75 | 25.75 | 90.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
55 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | Door | PERIMETER_BOT_ZN_2_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.839 | 2.839 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
56 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | Door | PERIMETER_BOT_ZN_2_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.839 | 2.839 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
57 | PERIMETER_BOT_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
58 | CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
59 | PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
60 | PERIMETER_BOT_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
61 | PERIMETER_BOT_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | iz-PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
62 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
63 | PERIMETER_BOT_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.895 | 0.789 | 76.91 | 200.61 | 76.91 | 180.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
64 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.419_SHGC_SOUTH_0.4 | N/A | 2.381 | No | 23.18 | 23.18 | 23.18 | 180.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
65 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.419_SHGC_SOUTH_0.4 | N/A | 2.381 | No | 23.18 | 23.18 | 23.18 | 180.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
66 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.419_SHGC_SOUTH_0.4 | N/A | 2.381 | No | 23.18 | 23.18 | 23.18 | 180.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
67 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.419_SHGC_SOUTH_0.4 | N/A | 2.381 | No | 23.18 | 23.18 | 23.18 | 180.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
68 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.419_SHGC_SOUTH_0.4 | N/A | 2.381 | No | 23.18 | 23.18 | 23.18 | 180.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
69 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.839 | 2.839 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
70 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.839 | 2.839 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
71 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.839 | 2.839 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
72 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.839 | 2.839 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
73 | PERIMETER_BOT_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
74 | DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
75 | PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
76 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
77 | DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 63.07 | 63.07 | 63.07 | 0.00 | 180.00 | 16.08 | 4.57 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
78 | PERIMETER_BOT_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 250.35 | 250.35 | 250.35 | 0.00 | 180.00 | 57.03 | 6.47 | 0.00 | PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
79 | PERIMETER_BOT_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.42 | 313.42 | 313.42 | 180.00 | 0.00 | 73.11 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
80 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.84 | 626.84 | 626.84 | 0.00 | 90.00 | 626.84 | 1.00 | 0.00 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
81 | PERIMETER_BOT_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.895 | 0.789 | 52.57 | 133.74 | 52.57 | 270.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
82 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.419_SHGC_WEST_0.4 | N/A | 2.381 | No | 25.75 | 25.75 | 25.75 | 270.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
83 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.419_SHGC_WEST_0.4 | N/A | 2.381 | No | 25.75 | 25.75 | 25.75 | 270.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
84 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.419_SHGC_WEST_0.4 | N/A | 2.381 | No | 25.75 | 25.75 | 25.75 | 270.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
85 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | Door | PERIMETER_BOT_ZN_4_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.839 | 2.839 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
86 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | Door | PERIMETER_BOT_ZN_4_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.839 | 2.839 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
87 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
88 | DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
89 | PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
90 | PERIMETER_BOT_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
91 | PERIMETER_BOT_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | iz-PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
92 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
93 | PERIMETER_MID_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.851 | 0.755 | 84.71 | 200.61 | 84.71 | 0.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
94 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_MID_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.419_SHGC_NORTH_0.4 | N/A | 2.381 | No | 115.90 | 115.90 | 115.90 | 0.00 | 90.00 | 73.11 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
95 | PERIMETER_MID_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
96 | CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
97 | PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
98 | DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
99 | PERIMETER_MID_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
100 | PERIMETER_MID_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.41 | 313.41 | 313.41 | 180.00 | 0.00 | 63.96 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
101 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.83 | 626.83 | 626.83 | 0.00 | 90.00 | 626.83 | 1.00 | 0.00 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
102 | PERIMETER_MID_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.851 | 0.755 | 56.47 | 133.74 | 56.47 | 90.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
103 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_MID_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.419_SHGC_EAST_0.4 | N/A | 2.381 | No | 77.26 | 77.26 | 77.26 | 90.00 | 90.00 | 48.74 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
104 | PERIMETER_MID_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
105 | CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
106 | PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
107 | PERIMETER_MID_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_MID_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
108 | PERIMETER_MID_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | iz-PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
109 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
110 | PERIMETER_MID_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
111 | PERIMETER_MID_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.851 | 0.755 | 84.71 | 200.61 | 84.71 | 180.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
112 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_MID_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.419_SHGC_SOUTH_0.4 | N/A | 2.381 | No | 115.90 | 115.90 | 115.90 | 180.00 | 90.00 | 73.11 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
113 | DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
114 | PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
115 | CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
116 | PERIMETER_MID_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
117 | PERIMETER_MID_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.42 | 313.42 | 313.42 | 180.00 | 0.00 | 73.11 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
118 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.84 | 626.84 | 626.84 | 0.00 | 90.00 | 626.84 | 1.00 | 0.00 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
119 | PERIMETER_MID_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.851 | 0.755 | 56.47 | 133.74 | 56.47 | 270.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
120 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_MID_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.419_SHGC_WEST_0.4 | N/A | 2.381 | No | 77.26 | 77.26 | 77.26 | 270.00 | 90.00 | 48.74 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
121 | PERIMETER_MID_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
122 | DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
123 | PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
124 | PERIMETER_MID_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_MID_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
125 | PERIMETER_MID_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | iz-PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
126 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
127 | PERIMETER_TOP_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.077 | 0.928 | 84.71 | 200.61 | 84.71 | 0.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
128 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_TOP_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.419_SHGC_NORTH_0.4 | N/A | 2.381 | No | 115.90 | 115.90 | 115.90 | 0.00 | 90.00 | 73.11 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
129 | PERIMETER_TOP_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
130 | CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
131 | PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
132 | DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
133 | PERIMETER_TOP_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_TOP_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
134 | PERIMETER_TOP_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.41 | 313.41 | 313.41 | 180.00 | 0.00 | 63.96 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
135 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.83 | 626.83 | 626.83 | 0.00 | 90.00 | 626.83 | 1.00 | 0.00 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
136 | PERIMETER_TOP_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.077 | 0.928 | 56.47 | 133.74 | 56.47 | 90.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
137 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_TOP_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.419_SHGC_EAST_0.4 | N/A | 2.381 | No | 77.26 | 77.26 | 77.26 | 90.00 | 90.00 | 48.74 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
138 | PERIMETER_TOP_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
139 | CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
140 | INT-PER3S-NE-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | INT-PER3S-NE | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
141 | PERIMETER_TOP_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_TOP_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
142 | PERIMETER_TOP_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | iz-PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
143 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
144 | PERIMETER_TOP_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.077 | 0.928 | 84.71 | 200.61 | 84.71 | 180.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
145 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_TOP_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.419_SHGC_SOUTH_0.4 | N/A | 2.381 | No | 115.90 | 115.90 | 115.90 | 180.00 | 90.00 | 73.11 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
146 | INT-PER3S-NE | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | INT-PER3S-NE-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
147 | DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
148 | PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
149 | CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
150 | PERIMETER_TOP_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_TOP_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
151 | PERIMETER_TOP_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.42 | 313.42 | 313.42 | 180.00 | 0.00 | 73.11 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
152 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.84 | 626.84 | 626.84 | 0.00 | 90.00 | 626.84 | 1.00 | 0.00 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
153 | PERIMETER_TOP_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.077 | 0.928 | 56.47 | 133.74 | 56.47 | 270.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
154 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_TOP_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.419_SHGC_WEST_0.4 | N/A | 2.381 | No | 77.26 | 77.26 | 77.26 | 270.00 | 90.00 | 48.74 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
155 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
156 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
157 | PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
158 | PERIMETER_TOP_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_TOP_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
159 | PERIMETER_TOP_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | iz-PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
160 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
161 | GROUNDFLOOR_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.895 | 0.789 | 89.13 | 89.13 | 89.13 | 0.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
162 | GROUNDFLOOR_PLENUM_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.895 | 0.789 | 59.42 | 59.42 | 59.42 | 270.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
163 | GROUNDFLOOR_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.895 | 0.789 | 89.13 | 89.13 | 89.13 | 180.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
164 | GROUNDFLOOR_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.895 | 0.789 | 59.42 | 59.42 | 59.42 | 90.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
165 | iz-CORE_BOT_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
166 | iz-PERIMETER_BOT_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
167 | iz-PERIMETER_BOT_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
168 | iz-PERIMETER_BOT_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
169 | iz-PERIMETER_BOT_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
170 | iz-DATACENTER_BOT_ZN_6_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_BOT_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
171 | GROUNDFLOOR_PLENUM_CEILING | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 3563.11 | 3563.11 | 3563.11 | 180.00 | 0.00 | 73.11 | 48.74 | 0.00 | GROUNDFLOOR_PLENUM_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
172 | MIDFLOOR_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.851 | 0.755 | 89.13 | 89.13 | 89.13 | 0.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
173 | MIDFLOOR_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.851 | 0.755 | 59.42 | 59.42 | 59.42 | 270.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
174 | MIDFLOOR_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.851 | 0.755 | 89.13 | 89.13 | 89.13 | 180.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
175 | MIDFLOOR_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.851 | 0.755 | 59.42 | 59.42 | 59.42 | 90.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
176 | iz-CORE_MID_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
177 | iz-PERIMETER_MID_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
178 | iz-PERIMETER_MID_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
179 | iz-PERIMETER_MID_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
180 | iz-PERIMETER_MID_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
181 | iz-DATACENTER_MID_ZN_6_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_MID_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
182 | MIDFLOOR_PLENUM_CEILING | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 3563.11 | 3563.11 | 3563.11 | 180.00 | 0.00 | 73.11 | 48.74 | 0.00 | MIDFLOOR_PLENUM_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
183 | TOPFLOOR_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.077 | 0.928 | 89.13 | 89.13 | 89.13 | 180.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
184 | TOPFLOOR_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.077 | 0.928 | 59.42 | 59.42 | 59.42 | 90.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
185 | TOPFLOOR_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.077 | 0.928 | 59.42 | 59.42 | 59.42 | 270.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
186 | TOPFLOOR_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.077 | 0.928 | 89.13 | 89.13 | 89.13 | 0.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
187 | iz-CORE_TOP_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
188 | iz-PERIMETER_TOP_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
189 | iz-PERIMETER_TOP_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
190 | iz-PERIMETER_TOP_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
191 | iz-PERIMETER_TOP_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
192 | iz-DATACENTER_TOP_ZN_6_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_TOP_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
193 | BUILDING_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 3563.11 | 3563.11 | 3563.11 | 180.00 | 0.00 | 73.11 | 48.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
194 | DATACENTER_BOT_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
195 | DATACENTER_BOT_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
196 | DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
197 | DATACENTER_BOT_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
198 | DATACENTER_BOT_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
199 | DATACENTER_BOT_ZN_6_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | iz-DATACENTER_BOT_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
200 | DATACENTER_MID_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
201 | DATACENTER_MID_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
202 | DATACENTER_MID_ZN_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
203 | DATACENTER_MID_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
204 | DATACENTER_MID_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_MID_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
205 | DATACENTER_MID_ZN_6_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | iz-DATACENTER_MID_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
206 | DATACENTER_TOP_ZN_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
207 | DATACENTER_TOP_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
208 | DATACENTER_TOP_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
209 | DATACENTER_TOP_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
210 | DATACENTER_TOP_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_TOP_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
211 | DATACENTER_TOP_ZN_6_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | iz-DATACENTER_TOP_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
212 | DATACENTER_BASEMENT_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR | 0.354 | 0.336 | 39.22 | 39.22 | 39.22 | 0.00 | 90.00 | 16.08 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
213 | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR | 0.354 | 0.336 | 39.22 | 39.22 | 39.22 | 180.00 | 90.00 | 16.08 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
214 | DATACENTER_BASEMENT_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR | 0.354 | 0.336 | 118.87 | 118.87 | 118.87 | 270.00 | 90.00 | 48.74 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
215 | DATACENTER_BASEMENT_ZN_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.87 | 118.87 | 118.87 | 90.00 | 90.00 | 48.74 | 2.44 | 0.00 | BASEMENT_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
216 | DATACENTER_BASEMENT_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 783.68 | 783.68 | 783.68 | 0.00 | 180.00 | 16.08 | 48.74 | 0.00 | DATACENTER_BASEMENT_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
217 | DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | DATACENTER_BOT_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
218 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 419.35 | 419.35 | 419.35 | 180.00 | 0.00 | 10.59 | 39.59 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
219 | PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | PERIMETER_BOT_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
220 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 63.08 | 63.08 | 63.08 | 180.00 | 0.00 | 16.08 | 6.47 | 0.00 | DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
221 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 63.07 | 63.07 | 63.07 | 180.00 | 0.00 | 11.51 | 6.47 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | BASEMENT | RunPeriod: RUNPERIOD 1 | 9.4345532065E-004 | 1.4522451558E-003 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
2 | CORE_BOTTOM | RunPeriod: RUNPERIOD 1 | 3.2536364821E-003 | 6.1213181781E-003 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
3 | CORE_MID | RunPeriod: RUNPERIOD 1 | 3.3570414451E-002 | 1.8618654563E-002 | Pass | Pass | 0.4825424822 | 0.4895750324 | Pass | Pass |
4 | CORE_TOP | RunPeriod: RUNPERIOD 1 | 5.0489733282E-002 | 5.9995210263E-002 | Pass | Pass | 4.6762552531 | 20.7016859997 | Pass | Pass |
5 | PERIMETER_BOT_ZN_3 | RunPeriod: RUNPERIOD 1 | 2.1659882045E-002 | 1.8086637800E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
6 | PERIMETER_BOT_ZN_2 | RunPeriod: RUNPERIOD 1 | 2.7083659137E-002 | 3.7406060802E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
7 | PERIMETER_BOT_ZN_1 | RunPeriod: RUNPERIOD 1 | 3.8494970677E-002 | 6.3306485906E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
8 | PERIMETER_BOT_ZN_4 | RunPeriod: RUNPERIOD 1 | 2.2591381557E-002 | 1.9114221228E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
9 | PERIMETER_MID_ZN_3 | RunPeriod: RUNPERIOD 1 | 0.3948041736 | 0.3867735321 | Pass | Pass | 21.8364095982 | 148.2103725515 | Pass | Pass |
10 | PERIMETER_MID_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.4253449646 | 0.4231532938 | Pass | Pass | 1.1215110529 | 1.4174945041 | Pass | Pass |
11 | PERIMETER_MID_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.3651358191 | 0.3865223355 | Pass | Pass | 406.9690319767 | 4853.4420377830 | Pass | Pass |
12 | PERIMETER_MID_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.3175302122 | 0.3224376235 | Pass | Pass | 1.1918467838 | 1.6074290328 | Pass | Pass |
13 | PERIMETER_TOP_ZN_3 | RunPeriod: RUNPERIOD 1 | 0.5655413154 | 0.5362140711 | Pass | Pass | 9.0849780536 | 43.4755759435 | Pass | Pass |
14 | PERIMETER_TOP_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.5979004997 | 0.5847700495 | Pass | Pass | 4.8598871810 | 30.0844746600 | Pass | Pass |
15 | PERIMETER_TOP_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.5355446522 | 0.5414411231 | Pass | Pass | 7.5610762356 | 52.9429474642 | Pass | Pass |
16 | PERIMETER_TOP_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.5013218978 | 0.4927872388 | Pass | Pass | 3.6918909900 | 17.9970516465 | Pass | Pass |
17 | GROUNDFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 5.4972884681E-003 | 5.6166820813E-003 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
18 | MIDFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 5.8378113896E-002 | 3.1352109907E-002 | Pass | Pass | 0.4918661019 | 0.4694023309 | Pass | Pass |
19 | TOPFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 0.1479935746 | 0.1001201398 | Pass | Pass | 0.4889384610 | 0.4795523654 | Pass | Pass |
20 | DATACENTER_BOT_ZN_6 | RunPeriod: RUNPERIOD 1 | 1.5202503954E-007 | 3.0692303085E-007 | Pass | Pass | 7.9136707296E-003 | 6.6869559055E-003 | Pass | Pass |
21 | DATACENTER_MID_ZN_6 | RunPeriod: RUNPERIOD 1 | 5.3057607739E-003 | 4.8021229213E-003 | Pass | Pass | 2.1643414468E-003 | 2.0756706309E-003 | Pass | Pass |
22 | DATACENTER_TOP_ZN_6 | RunPeriod: RUNPERIOD 1 | 8.1507253358E-003 | 7.4703810912E-003 | Pass | Pass | 3.5220485021E-003 | 3.1572665755E-003 | Pass | Pass |
23 | DATACENTER_BASEMENT_ZN_6 | RunPeriod: RUNPERIOD 1 | 8.4311488455E-006 | 4.7828836284E-006 | Pass | Pass | 4.5029641630E-005 | 1.1032294283E-004 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 08:43:43
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 6893.39 | 393.80 | 0.00 | 29046.67 | 12429.57 | 48763.43 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 08:43:43
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | -26.20 | 0.00 | -26.20 | Wetbulb [C] | 5.70 | 310.00 |
ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 31.20 | 10.60 | 23.10 | Wetbulb [C] | 6.70 | 200.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 26.00 | 35 | |||
Feb | 0.00 | 0 | |||
Mar | 0.00 | 0 | |||
Apr | 29.00 | 23 | |||
May | 0.00 | 0 | |||
Jun | 107.00 | 45 | |||
Jul | 72.00 | 29 | |||
Aug | 0.00 | 0 | |||
Sep | 20.00 | 11 | |||
Oct | 0.00 | 0 | |||
Nov | 0.00 | 0 | |||
Dec | 4.00 | 8 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 08:43:43
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BASEMENT_WALL_EAST | BASEMENT_WALL_EAST_CFACTOR | 1.00 | 0.340 | 0.354 | 118.87 | 118.87 | 90.00 | 90.00 | E |
BASEMENT_WALL_SOUTH | BASEMENT_WALL_SOUTH_CFACTOR | 1.00 | 0.340 | 0.354 | 139.09 | 139.09 | 180.00 | 90.00 | S |
BASEMENT_WALL_NORTH | BASEMENT_WALL_NORTH_CFACTOR | 1.00 | 0.340 | 0.354 | 139.09 | 139.09 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_3_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.789 | 0.895 | 200.61 | 76.91 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_2_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.789 | 0.895 | 133.74 | 52.57 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.789 | 0.895 | 200.61 | 76.91 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_4_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.789 | 0.895 | 133.74 | 52.57 | 270.00 | 90.00 | W |
PERIMETER_MID_ZN_3_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.755 | 0.851 | 2006.06 | 847.11 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_2_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 0.755 | 0.851 | 1337.37 | 564.74 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.755 | 0.851 | 2006.06 | 847.11 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_4_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 0.755 | 0.851 | 1337.37 | 564.74 | 270.00 | 90.00 | W |
PERIMETER_TOP_ZN_3_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 0.928 | 1.077 | 200.61 | 84.71 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_2_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 0.928 | 1.077 | 133.74 | 56.47 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 0.928 | 1.077 | 200.61 | 84.71 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_4_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 0.928 | 1.077 | 133.74 | 56.47 | 270.00 | 90.00 | W |
GROUNDFLOOR_PLENUM_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.789 | 0.895 | 89.13 | 89.13 | 0.00 | 90.00 | N |
GROUNDFLOOR_PLENUM_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.789 | 0.895 | 59.42 | 59.42 | 270.00 | 90.00 | W |
GROUNDFLOOR_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.789 | 0.895 | 89.13 | 89.13 | 180.00 | 90.00 | S |
GROUNDFLOOR_PLENUM_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.789 | 0.895 | 59.42 | 59.42 | 90.00 | 90.00 | E |
MIDFLOOR_PLENUM_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.755 | 0.851 | 891.32 | 891.32 | 0.00 | 90.00 | N |
MIDFLOOR_PLENUM_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 0.755 | 0.851 | 594.21 | 594.21 | 270.00 | 90.00 | W |
MIDFLOOR_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.755 | 0.851 | 891.32 | 891.32 | 180.00 | 90.00 | S |
MIDFLOOR_PLENUM_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 0.755 | 0.851 | 594.21 | 594.21 | 90.00 | 90.00 | E |
TOPFLOOR_PLENUM_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 0.928 | 1.077 | 89.13 | 89.13 | 180.00 | 90.00 | S |
TOPFLOOR_PLENUM_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 0.928 | 1.077 | 59.42 | 59.42 | 90.00 | 90.00 | E |
TOPFLOOR_PLENUM_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 0.928 | 1.077 | 59.42 | 59.42 | 270.00 | 90.00 | W |
TOPFLOOR_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 0.928 | 1.077 | 89.13 | 89.13 | 0.00 | 90.00 | N |
BUILDING_ROOF | NONRES_ROOF | 0.30 | 0.182 | 0.186 | 3563.11 | 3563.11 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_WALL_NORTH | DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR | 1.00 | 0.340 | 0.354 | 39.22 | 39.22 | 0.00 | 90.00 | N |
DATACENTER_BASEMENT_ZN_6_WALL_SOUTH | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR | 1.00 | 0.340 | 0.354 | 39.22 | 39.22 | 180.00 | 90.00 | S |
DATACENTER_BASEMENT_ZN_6_WALL_WEST | DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR | 1.00 | 0.340 | 0.354 | 118.87 | 118.87 | 270.00 | 90.00 | W |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BASEMENT_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 118.87 | 118.87 | 270.00 | 90.00 | W |
BASEMENT_FLOOR | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 2779.43 | 2779.43 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 225.00 | 0.00 | |
PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 250.34 | 250.34 | 180.00 | 0.00 | |
CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 2076.77 | 2076.77 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 250.34 | 250.34 | 180.00 | 0.00 | |
CORE_BOT_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
CORE_BOT_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
CORE_BOT_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 419.30 | 419.30 | 0.00 | 180.00 | |
CORE_BOT_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 2076.82 | 2076.82 | 0.00 | 180.00 | |
CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 180.00 | 0.00 | |
CORE_MID_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 180.00 | 90.00 | S |
CORE_MID_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 270.00 | 90.00 | W |
CORE_MID_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 0.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 90.00 | 90.00 | E |
CORE_MID_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 24961.20 | 24961.20 | 0.00 | 180.00 | |
CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 24961.20 | 24961.20 | 180.00 | 0.00 | |
CORE_TOP_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
CORE_TOP_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
CORE_TOP_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
CORE_TOP_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 2496.12 | 2496.12 | 0.00 | 180.00 | |
CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 250.34 | 250.34 | 0.00 | 180.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 63.07 | 63.07 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
PERIMETER_BOT_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 45.00 | 180.00 | |
PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 225.00 | 0.00 | |
PERIMETER_BOT_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 63.07 | 63.07 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 250.35 | 250.35 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
PERIMETER_BOT_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 315.00 | 180.00 | |
PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 135.00 | 0.00 | |
PERIMETER_MID_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 225.00 | 90.00 | W |
CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 135.00 | 90.00 | S |
DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 3134.13 | 3134.13 | 0.00 | 180.00 | |
PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.13 | 3134.13 | 180.00 | 0.00 | |
PERIMETER_MID_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 315.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 270.00 | 90.00 | W |
PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 225.00 | 90.00 | W |
PERIMETER_MID_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 2019.75 | 2019.75 | 45.00 | 180.00 | |
PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 225.00 | 0.00 | |
PERIMETER_MID_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 45.00 | 90.00 | E |
DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 315.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 3134.20 | 3134.20 | 0.00 | 180.00 | |
PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.20 | 3134.20 | 180.00 | 0.00 | |
PERIMETER_MID_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 135.00 | 90.00 | S |
DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 45.00 | 90.00 | E |
PERIMETER_MID_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 2019.75 | 2019.75 | 315.00 | 180.00 | |
PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 135.00 | 0.00 | |
PERIMETER_TOP_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 313.41 | 313.41 | 0.00 | 180.00 | |
PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 180.00 | 0.00 | |
PERIMETER_TOP_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
INT-PER3S-NE-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
PERIMETER_TOP_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 201.98 | 201.98 | 45.00 | 180.00 | |
PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 225.00 | 0.00 | |
INT-PER3S-NE | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 313.42 | 313.42 | 0.00 | 180.00 | |
PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 180.00 | 0.00 | |
PERIMETER_TOP_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
PERIMETER_TOP_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 201.98 | 201.98 | 315.00 | 180.00 | |
PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 135.00 | 0.00 | |
iz-CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 45.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 315.00 | 180.00 | |
iz-DATACENTER_BOT_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 0.00 | 180.00 | |
GROUNDFLOOR_PLENUM_CEILING | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 3563.11 | 3563.11 | 180.00 | 0.00 | |
iz-CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 24961.20 | 24961.20 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.13 | 3134.13 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 45.00 | 180.00 | |
iz-PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.20 | 3134.20 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 315.00 | 180.00 | |
iz-DATACENTER_MID_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 362.03 | 362.03 | 0.00 | 180.00 | |
MIDFLOOR_PLENUM_CEILING | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 35631.06 | 35631.06 | 180.00 | 0.00 | |
iz-CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 45.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 315.00 | 180.00 | |
iz-DATACENTER_TOP_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 0.00 | 180.00 | |
DATACENTER_BOT_ZN_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
DATACENTER_BOT_ZN_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
DATACENTER_BOT_ZN_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
DATACENTER_BOT_ZN_6_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 36.20 | 36.20 | 0.00 | 180.00 | |
DATACENTER_BOT_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 180.00 | 0.00 | |
DATACENTER_MID_ZN_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 270.00 | 90.00 | W |
DATACENTER_MID_ZN_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 180.00 | 90.00 | S |
DATACENTER_MID_ZN_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 90.00 | 90.00 | E |
DATACENTER_MID_ZN_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 0.00 | 90.00 | N |
DATACENTER_MID_ZN_6_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 362.03 | 362.03 | 0.00 | 180.00 | |
DATACENTER_MID_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 362.03 | 362.03 | 180.00 | 0.00 | |
DATACENTER_TOP_ZN_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
DATACENTER_TOP_ZN_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
DATACENTER_TOP_ZN_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
DATACENTER_TOP_ZN_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
DATACENTER_TOP_ZN_6_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 36.20 | 36.20 | 0.00 | 180.00 | |
DATACENTER_TOP_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 118.87 | 118.87 | 90.00 | 90.00 | E |
DATACENTER_BASEMENT_ZN_6_FLOOR | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 783.68 | 783.68 | 0.00 | 180.00 | |
DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 36.20 | 36.20 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 419.35 | 419.35 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 135.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 63.08 | 63.08 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 63.07 | 63.07 | 180.00 | 0.00 | |
BASEMENT_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 7126.21 | 0.00 | 90.00 | N | ||
CORE_BOTTOM_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 5064.65 | 0.00 | 90.00 | N | ||
CORE_MID_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 50646.53 | 0.00 | 90.00 | N | ||
CORE_TOP_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 5064.65 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.83 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.84 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 6268.26 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 4039.50 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 6268.35 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 4039.48 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.83 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.84 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | WINDOW_U_0.419_SHGC_NORTH_0.4 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.381 | 0.401 | 0.442 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | WINDOW_U_0.419_SHGC_NORTH_0.4 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.381 | 0.401 | 0.442 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | WINDOW_U_0.419_SHGC_NORTH_0.4 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.381 | 0.401 | 0.442 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | WINDOW_U_0.419_SHGC_NORTH_0.4 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.381 | 0.401 | 0.442 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | WINDOW_U_0.419_SHGC_NORTH_0.4 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.381 | 0.401 | 0.442 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | WINDOW_U_0.419_SHGC_EAST_0.4 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 2.381 | 0.401 | 0.442 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | WINDOW_U_0.419_SHGC_EAST_0.4 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 2.381 | 0.401 | 0.442 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | WINDOW_U_0.419_SHGC_EAST_0.4 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 2.381 | 0.401 | 0.442 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | WINDOW_U_0.419_SHGC_SOUTH_0.4 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.381 | 0.401 | 0.442 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | WINDOW_U_0.419_SHGC_SOUTH_0.4 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.381 | 0.401 | 0.442 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | WINDOW_U_0.419_SHGC_SOUTH_0.4 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.381 | 0.401 | 0.442 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | WINDOW_U_0.419_SHGC_SOUTH_0.4 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.381 | 0.401 | 0.442 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | WINDOW_U_0.419_SHGC_SOUTH_0.4 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.381 | 0.401 | 0.442 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | WINDOW_U_0.419_SHGC_WEST_0.4 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 2.381 | 0.401 | 0.442 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | WINDOW_U_0.419_SHGC_WEST_0.4 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 2.381 | 0.401 | 0.442 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | WINDOW_U_0.419_SHGC_WEST_0.4 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 2.381 | 0.401 | 0.442 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.419_SHGC_NORTH_0.4 | 115.90 | 0.00 | 0.00 | 115.90 | 1158.95 | 2.381 | 0.401 | 0.442 | No | PERIMETER_MID_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.419_SHGC_EAST_0.4 | 77.26 | 0.00 | 0.00 | 77.26 | 772.63 | 2.381 | 0.401 | 0.442 | No | PERIMETER_MID_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.419_SHGC_SOUTH_0.4 | 115.90 | 0.00 | 0.00 | 115.90 | 1158.95 | 2.381 | 0.401 | 0.442 | No | PERIMETER_MID_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.419_SHGC_WEST_0.4 | 77.26 | 0.00 | 0.00 | 77.26 | 772.63 | 2.381 | 0.401 | 0.442 | No | PERIMETER_MID_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.419_SHGC_NORTH_0.4 | 115.90 | 0.00 | 0.00 | 115.90 | 115.90 | 2.381 | 0.401 | 0.442 | No | PERIMETER_TOP_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.419_SHGC_EAST_0.4 | 77.26 | 0.00 | 0.00 | 77.26 | 77.26 | 2.381 | 0.401 | 0.442 | No | PERIMETER_TOP_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.419_SHGC_SOUTH_0.4 | 115.90 | 0.00 | 0.00 | 115.90 | 115.90 | 2.381 | 0.401 | 0.442 | No | PERIMETER_TOP_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.419_SHGC_WEST_0.4 | 77.26 | 0.00 | 0.00 | 77.26 | 77.26 | 2.381 | 0.401 | 0.442 | No | PERIMETER_TOP_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
Total or Average | 4635.80 | 2.381 | 0.401 | 0.442 | |||||||||||||||||
North Total or Average | 1390.74 | 2.381 | 0.401 | 0.442 | |||||||||||||||||
Non-North Total or Average | 3245.06 | 2.381 | 0.401 | 0.442 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | SWINGING DOOR_CON | 1.992 | 2.839 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | SWINGING DOOR_CON | 1.992 | 2.839 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | SWINGING DOOR_CON | 1.992 | 2.839 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | SWINGING DOOR_CON | 1.992 | 2.839 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | SWINGING DOOR_CON | 1.992 | 2.839 | 1.95 | PERIMETER_BOT_ZN_2_WALL_EAST |
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | SWINGING DOOR_CON | 1.992 | 2.839 | 1.95 | PERIMETER_BOT_ZN_2_WALL_EAST |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | SWINGING DOOR_CON | 1.992 | 2.839 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | SWINGING DOOR_CON | 1.992 | 2.839 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | SWINGING DOOR_CON | 1.992 | 2.839 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | SWINGING DOOR_CON | 1.992 | 2.839 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | SWINGING DOOR_CON | 1.992 | 2.839 | 1.95 | PERIMETER_BOT_ZN_4_WALL_WEST |
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | SWINGING DOOR_CON | 1.992 | 2.839 | 1.95 | PERIMETER_BOT_ZN_4_WALL_WEST |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 08:43:43
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 08:43:43
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
BASEMENT_LIGHTS | BASEMENT | BASEMENT | GENERAL | 10.2732 | 2779.43 | 28553.72 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 49.04 | 0.0000 | Y | 262.84 |
CORE_BOTTOM_LIGHTS | CORE_BOTTOM | CORE_BOTTOM | GENERAL | 10.2732 | 2496.12 | 25643.24 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 49.04 | 0.0000 | Y | 236.05 |
CORE_MID_LIGHTS | CORE_MID | CORE_MID | GENERAL | 10.2732 | 24961.20 | 256432.45 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 49.04 | 0.0000 | Y | 2360.52 |
CORE_TOP_LIGHTS | CORE_TOP | CORE_TOP | GENERAL | 10.2732 | 2496.12 | 25643.24 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 49.04 | 0.0000 | Y | 236.05 |
PERIMETER_BOT_ZN_3_LIGHTS | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3 | GENERAL | 10.2732 | 313.41 | 3219.77 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 28.94 | 0.0000 | Y | 17.49 |
PERIMETER_BOT_ZN_2_LIGHTS | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2 | GENERAL | 10.2732 | 201.98 | 2074.94 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 28.68 | 0.0000 | Y | 11.17 |
PERIMETER_BOT_ZN_1_LIGHTS | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1 | GENERAL | 10.2732 | 313.42 | 3219.84 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 28.39 | 0.0000 | Y | 17.16 |
PERIMETER_BOT_ZN_4_LIGHTS | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4 | GENERAL | 10.2732 | 201.98 | 2074.94 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 28.58 | 0.0000 | Y | 11.13 |
PERIMETER_MID_ZN_3_LIGHTS | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3 | GENERAL | 10.2732 | 3134.13 | 32197.65 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 28.87 | 0.0000 | Y | 174.48 |
PERIMETER_MID_ZN_2_LIGHTS | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2 | GENERAL | 10.2732 | 2019.75 | 20749.39 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 28.63 | 0.0000 | Y | 111.53 |
PERIMETER_MID_ZN_1_LIGHTS | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1 | GENERAL | 10.2732 | 3134.20 | 32198.36 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 28.36 | 0.0000 | Y | 171.40 |
PERIMETER_MID_ZN_4_LIGHTS | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4 | GENERAL | 10.2732 | 2019.75 | 20749.39 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 28.53 | 0.0000 | Y | 111.13 |
PERIMETER_TOP_ZN_3_LIGHTS | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3 | GENERAL | 10.2732 | 313.41 | 3219.77 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 28.87 | 0.0000 | Y | 17.45 |
PERIMETER_TOP_ZN_2_LIGHTS | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2 | GENERAL | 10.2732 | 201.98 | 2074.94 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 28.63 | 0.0000 | Y | 11.15 |
PERIMETER_TOP_ZN_1_LIGHTS | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1 | GENERAL | 10.2732 | 313.42 | 3219.84 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 28.36 | 0.0000 | Y | 17.14 |
PERIMETER_TOP_ZN_4_LIGHTS | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4 | GENERAL | 10.2732 | 201.98 | 2074.94 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 28.53 | 0.0000 | Y | 11.11 |
DATACENTER_BASEMENT_LIGHTS | DATACENTER_BASEMENT_ZN_6 | DATACENTER_BASEMENT_ZN_6 | GENERAL | 10.2732 | 783.68 | 8050.93 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 49.04 | 0.0000 | Y | 74.11 |
DATACENTER_BOT_LIGHTS | DATACENTER_BOT_ZN_6 | DATACENTER_BOT_ZN_6 | GENERAL | 17.8735 | 36.20 | 647.07 | LightsWired | LTG_SCH_DATACENTER | 56.02 | 168.00 | 54.57 | 0.0000 | Y | 6.63 |
DATACENTER_MID_LIGHTS | DATACENTER_MID_ZN_6 | DATACENTER_MID_ZN_6 | GENERAL | 17.8735 | 362.03 | 6470.68 | LightsWired | LTG_SCH_DATACENTER | 56.02 | 168.00 | 54.57 | 0.0000 | Y | 66.28 |
DATACENTER_TOP_LIGHTS | DATACENTER_TOP_ZN_6 | DATACENTER_TOP_ZN_6 | GENERAL | 17.8735 | 36.20 | 647.07 | LightsWired | LTG_SCH_DATACENTER | 56.02 | 168.00 | 54.57 | 0.0000 | Y | 6.63 |
Interior Lighting Total | 10.3445 | 46320.38 | 479162.15 | 1235.65 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
PERIMETER_BOT_ZN_1_DAYLREFPT1 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_DAYLCTRL | SplitFlux | Stepped | 0.39 | 3219.84 | 1241.89 |
PERIMETER_BOT_ZN_1_DAYLREFPT2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_DAYLCTRL | SplitFlux | Stepped | 0.14 | 3219.84 | 445.95 |
PERIMETER_BOT_ZN_2_DAYLREFPT1 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_DAYLCTRL | SplitFlux | Stepped | 0.39 | 2074.94 | 800.30 |
PERIMETER_BOT_ZN_2_DAYLREFPT2 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_DAYLCTRL | SplitFlux | Stepped | 0.14 | 2074.94 | 287.38 |
PERIMETER_BOT_ZN_3_DAYLREFPT1 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_DAYLCTRL | SplitFlux | Stepped | 0.39 | 3219.77 | 1241.86 |
PERIMETER_BOT_ZN_3_DAYLREFPT2 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_DAYLCTRL | SplitFlux | Stepped | 0.14 | 3219.77 | 445.94 |
PERIMETER_BOT_ZN_4_DAYLREFPT1 | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_DAYLCTRL | SplitFlux | Stepped | 0.39 | 2074.94 | 800.30 |
PERIMETER_BOT_ZN_4_DAYLREFPT2 | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_DAYLCTRL | SplitFlux | Stepped | 0.14 | 2074.94 | 287.38 |
PERIMETER_MID_ZN_1_DAYLREFPT1 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_DAYLCTRL | SplitFlux | Stepped | 0.39 | 3219.84 | 1241.89 |
PERIMETER_MID_ZN_1_DAYLREFPT2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_DAYLCTRL | SplitFlux | Stepped | 0.14 | 3219.84 | 445.95 |
PERIMETER_MID_ZN_2_DAYLREFPT1 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_DAYLCTRL | SplitFlux | Stepped | 0.39 | 2074.94 | 800.30 |
PERIMETER_MID_ZN_2_DAYLREFPT2 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_DAYLCTRL | SplitFlux | Stepped | 0.14 | 2074.94 | 287.38 |
PERIMETER_MID_ZN_3_DAYLREFPT1 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_DAYLCTRL | SplitFlux | Stepped | 0.39 | 3219.77 | 1241.86 |
PERIMETER_MID_ZN_3_DAYLREFPT2 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_DAYLCTRL | SplitFlux | Stepped | 0.14 | 3219.77 | 445.94 |
PERIMETER_MID_ZN_4_DAYLREFPT1 | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_DAYLCTRL | SplitFlux | Stepped | 0.39 | 2074.94 | 800.30 |
PERIMETER_MID_ZN_4_DAYLREFPT2 | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_DAYLCTRL | SplitFlux | Stepped | 0.14 | 2074.94 | 287.38 |
PERIMETER_TOP_ZN_1_DAYLREFPT1 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_DAYLCTRL | SplitFlux | Stepped | 0.39 | 3219.84 | 1241.89 |
PERIMETER_TOP_ZN_1_DAYLREFPT2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_DAYLCTRL | SplitFlux | Stepped | 0.14 | 3219.84 | 445.95 |
PERIMETER_TOP_ZN_2_DAYLREFPT1 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_DAYLCTRL | SplitFlux | Stepped | 0.39 | 2074.94 | 800.30 |
PERIMETER_TOP_ZN_2_DAYLREFPT2 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_DAYLCTRL | SplitFlux | Stepped | 0.14 | 2074.94 | 287.38 |
PERIMETER_TOP_ZN_3_DAYLREFPT1 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_DAYLCTRL | SplitFlux | Stepped | 0.39 | 3219.77 | 1241.86 |
PERIMETER_TOP_ZN_3_DAYLREFPT2 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_DAYLCTRL | SplitFlux | Stepped | 0.14 | 3219.77 | 445.94 |
PERIMETER_TOP_ZN_4_DAYLREFPT1 | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_DAYLCTRL | SplitFlux | Stepped | 0.39 | 2074.94 | 800.30 |
PERIMETER_TOP_ZN_4_DAYLREFPT2 | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_DAYLCTRL | SplitFlux | Stepped | 0.14 | 2074.94 | 287.38 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS_A | 13279.00 | AstronomicalClock | - | 42.24 | 42.24 | 105.29 | |
EXTERIOR_LIGHTS_B | 44301.60 | AstronomicalClock | - | 83.63 | 71.21 | 592.21 | |
Exterior Lighting Total | 57580.60 | 697.49 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 08:43:43
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
BYPASS HEAT EXCHANGER | HeatExchanger:FluidToFluid | 3037086.61 | |||||
HEATSYS1 BOILER | Boiler:HotWater | 3766253.92 | 0.81 | ||||
COOLSYS1 CHILLER1 | Chiller:Electric:ReformulatedEIR | 1541163.98 | 6.28 | 1475094.83 | 5.98 | 6.84 | 23.33 |
COOLSYS1 CHILLER2 | Chiller:Electric:ReformulatedEIR | 1541163.98 | 6.28 | 1475094.83 | 5.98 | 6.84 | 23.33 |
CENTRAL TOWER | FluidCooler:TwoSpeed | 582060.00 | |||||
CENTRAL BOILER | Boiler:HotWater | 554972.71 | 0.80 | ||||
TOWERWATERSYS COOLTOWER 1 | CoolingTower:VariableSpeed | 1828568.75 | |||||
TOWERWATERSYS COOLTOWER 2 | CoolingTower:VariableSpeed | 1828568.75 |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
VAV_BOT WITH REHEAT COOLING COIL | Coil:Cooling:Water | 248199.41 | 282122.08 | 187095.26 | 95026.82 | 0.66 | - | 30552.16 | 309.88 |
VAV_MID WITH REHEAT COOLING COIL | Coil:Cooling:Water | 2406793.33 | 2676071.22 | 1766429.60 | 909641.63 | 0.66 | - | 290147.16 | 2942.83 |
VAV_TOP WITH REHEAT COOLING COIL | Coil:Cooling:Water | 254402.44 | 289783.17 | 192236.59 | 97546.58 | 0.66 | - | 31397.88 | 318.45 |
CAV_BAS COOLING COIL | Coil:Cooling:Water | 134691.93 | 157427.78 | 105734.63 | 51693.14 | 0.67 | - | 16614.98 | 168.52 |
AIRLOOP DATACENTER BASEMENT COOLING COIL | Coil:Cooling:WaterToAirHeatPump:EquationFit | 441003.93 | 302154.35 | 138849.58 | 0.69 | 0.00 | |||
AIRLOOP DATACENTER BOT COOLING COIL | Coil:Cooling:WaterToAirHeatPump:EquationFit | 10359.22 | 7125.89 | 3233.33 | 0.69 | 0.00 | |||
AIRLOOP DATACENTER MID COOLING COIL | Coil:Cooling:WaterToAirHeatPump:EquationFit | 99679.44 | 68510.11 | 31169.34 | 0.69 | 0.00 | |||
AIRLOOP DATACENTER TOP COOLING COIL | Coil:Cooling:WaterToAirHeatPump:EquationFit | 10125.79 | 6961.86 | 3163.93 | 0.69 | 0.00 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
None |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
None |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Water | 29028.74 | 27517.82 | - |
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Water | 570892.97 | 540714.21 | - |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Water | 114582.06 | 108580.01 | - |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 23970.80 | 22712.12 | - |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 16063.24 | 15219.69 | - |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 25210.56 | 23886.64 | - |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 13916.90 | 13186.35 | - |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 355759.67 | 337058.56 | - |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 232324.53 | 220111.57 | - |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 350087.60 | 331685.09 | - |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 230500.91 | 218383.86 | - |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 44347.66 | 42015.62 | - |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 28896.45 | 27376.87 | - |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 43732.98 | 41433.29 | - |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 28986.02 | 27461.72 | - |
VAV_BOT WITH REHEAT HEATING COIL | Coil:Heating:Water | 109143.00 | 72731.02 | - |
VAV_MID WITH REHEAT HEATING COIL | Coil:Heating:Water | 1114716.08 | 722965.68 | - |
VAV_TOP WITH REHEAT HEATING COIL | Coil:Heating:Water | 109771.99 | 73625.83 | - |
CAV_BAS HEATING COIL | Coil:Heating:Water | 324321.77 | 245312.06 | - |
AIRLOOP DATACENTER BASEMENT HEATING COIL | Coil:Heating:WaterToAirHeatPump:EquationFit | 441003.93 | 0.00 | |
AIRLOOP DATACENTER BOT HEATING COIL | Coil:Heating:WaterToAirHeatPump:EquationFit | 10359.22 | 0.00 | |
AIRLOOP DATACENTER MID HEATING COIL | Coil:Heating:WaterToAirHeatPump:EquationFit | 99679.44 | 0.00 | |
AIRLOOP DATACENTER TOP HEATING COIL | Coil:Heating:WaterToAirHeatPump:EquationFit | 10125.79 | 0.00 | |
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | Coil:Heating:Electric | 25854.50 | 1.00 | |
AIRLOOP DATACENTER BOT_SUPPHEATCOIL | Coil:Heating:Electric | 1194.37 | 1.00 | |
AIRLOOP DATACENTER MID_SUPPHEATCOIL | Coil:Heating:Electric | 11943.71 | 1.00 | |
AIRLOOP DATACENTER TOP_SUPPHEATCOIL | Coil:Heating:Electric | 1194.37 | 1.00 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
VAV_BOT WITH REHEAT FAN | Fan:VariableVolume | 0.61 | 1389.42 | 10.71 | 24320.82 | 2271.59 | 1.00 | 1.12 | General | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 |
VAV_MID WITH REHEAT FAN | Fan:VariableVolume | 0.61 | 1389.42 | 100.09 | 227354.10 | 2271.59 | 1.00 | 1.08 | General | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 |
VAV_TOP WITH REHEAT FAN | Fan:VariableVolume | 0.61 | 1389.42 | 11.01 | 25003.40 | 2271.59 | 1.00 | 1.12 | General | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 |
CAV_BAS FAN | Fan:ConstantVolume | 0.60 | 1018.41 | 6.24 | 10579.36 | 1695.65 | 1.00 | 1.15 | General | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
AIRLOOP DATACENTER BASEMENT SUPPLY FAN | Fan:OnOff | 0.62 | 1018.41 | 22.44 | 37007.31 | 1649.25 | 1.00 | 1.14 | General | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 07:10:00 |
AIRLOOP DATACENTER BOT SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.53 | 596.58 | 1120.11 | 1.00 | 1.58 | General | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
AIRLOOP DATACENTER MID SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 5.12 | 5731.84 | 1120.11 | 1.00 | 1.15 | General | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
AIRLOOP DATACENTER TOP SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.52 | 582.62 | 1120.11 | 1.00 | 1.59 | General | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
COOLSYS1 PUMP SECONDARY | Pump:VariableSpeed | Intermittent | 105797.75 | 0.129503 | 21143.80 | 163269.45 | 0.90 | General |
HEATSYS1 PUMP | Pump:VariableSpeed | Intermittent | 180705.70 | 0.032949 | 9922.74 | 301156.09 | 0.90 | General |
COOLSYS1 CHILLER1 PUMP | Pump:ConstantSpeed | Intermittent | 73247.35 | 0.064751 | 7319.28 | 113036.94 | 0.90 | General |
COOLSYS1 CHILLER2 PUMP | Pump:ConstantSpeed | Intermittent | 73247.35 | 0.064751 | 7319.28 | 113036.94 | 0.90 | General |
PLANT CIRC PUMP | Pump:ConstantSpeed | Intermittent | 179045.11 | 0.013743 | 3505.15 | 255050.01 | 0.90 | General |
SWHSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 29891.00 | 0.000440 | 56.21 | 127739.32 | 0.30 | General |
TOWERWATERSYS PUMP | HeaderedPumps:VariableSpeed | Intermittent | 148556.62 | 0.152533 | 37763.79 | 247577.87 | 0.90 | General |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 1.14 | 87921.32 | 0.80 | 0.48 | 0.06 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:43:43
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 82624.53 | 82624.53 | 29.73 | 6.239 | 6.239 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 24.00 | 24.00 | 0.00892 | 23.36 | 0.01535 | 1.200 | 0.00 |
CORE_BOTTOM | 85568.35 | 85568.35 | 34.28 | 6.461 | 6.461 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 24.00 | 24.00 | 0.00886 | 23.36 | 0.01535 | 1.078 | 0.00 |
CORE_MID | 805876.83 | 805876.83 | 322.85 | 60.831 | 60.831 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 24.00 | 24.00 | 0.00889 | 23.36 | 0.01535 | 10.778 | 0.00 |
CORE_TOP | 80045.99 | 80045.99 | 32.07 | 6.042 | 6.042 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 24.00 | 24.00 | 0.00889 | 23.36 | 0.01535 | 1.078 | 0.00 |
PERIMETER_BOT_ZN_3 | 14221.62 | 14221.62 | 45.38 | 1.083 | 1.083 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 | 24.00 | 24.00 | 0.00899 | 31.20 | 0.01537 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_2 | 19431.05 | 19431.05 | 96.21 | 1.480 | 1.480 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:30:00 | 24.00 | 24.00 | 0.00874 | 24.36 | 0.01535 | 0.087 | 0.00 |
PERIMETER_BOT_ZN_1 | 22023.27 | 22023.27 | 70.27 | 1.678 | 1.678 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:10:00 | 24.00 | 24.00 | 0.00882 | 30.76 | 0.01536 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_4 | 23424.65 | 23424.65 | 115.98 | 1.784 | 1.784 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 | 24.00 | 24.00 | 0.00870 | 29.54 | 0.01536 | 0.087 | 0.00 |
PERIMETER_MID_ZN_3 | 135743.57 | 135743.57 | 433.11 | 10.342 | 10.342 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 24.00 | 24.00 | 0.00930 | 31.20 | 0.01537 | 1.353 | 0.00 |
PERIMETER_MID_ZN_2 | 206474.21 | 206474.21 | 1022.28 | 15.730 | 15.730 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:10:00 | 24.00 | 24.00 | 0.00887 | 25.67 | 0.01535 | 0.872 | 0.00 |
PERIMETER_MID_ZN_1 | 222142.43 | 222142.43 | 708.77 | 16.924 | 16.924 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 24.00 | 24.00 | 0.00900 | 30.93 | 0.01536 | 1.353 | 0.00 |
PERIMETER_MID_ZN_4 | 219816.02 | 219816.02 | 1088.33 | 16.747 | 16.747 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:20:00 | 24.00 | 24.00 | 0.00884 | 29.36 | 0.01536 | 0.872 | 0.00 |
PERIMETER_TOP_ZN_3 | 15271.67 | 15271.67 | 48.73 | 1.164 | 1.164 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | 24.00 | 24.00 | 0.00932 | 31.20 | 0.01537 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_2 | 20758.56 | 20758.56 | 102.78 | 1.582 | 1.582 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:20:00 | 24.00 | 24.00 | 0.00892 | 25.97 | 0.01536 | 0.087 | 0.00 |
PERIMETER_TOP_ZN_1 | 23802.07 | 23802.07 | 75.94 | 1.813 | 1.813 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 24.00 | 24.00 | 0.00904 | 30.93 | 0.01536 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_4 | 23065.26 | 23065.26 | 114.20 | 1.757 | 1.757 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:20:00 | 24.00 | 24.00 | 0.00888 | 29.36 | 0.01536 | 0.087 | 0.00 |
DATACENTER_BOT_ZN_6 | 8864.92 | 8864.92 | 244.87 | 0.533 | 0.533 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:10:00 | 27.00 | 27.00 | 0.00858 | 26.87 | 0.01536 | 0.016 | 0.00 |
DATACENTER_MID_ZN_6 | 85172.54 | 85172.54 | 2352.65 | 5.117 | 5.117 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:10:00 | 27.00 | 27.00 | 0.00858 | 26.87 | 0.01536 | 0.156 | 0.00 |
DATACENTER_TOP_ZN_6 | 8657.41 | 8657.41 | 239.14 | 0.520 | 0.520 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:10:00 | 27.00 | 27.00 | 0.00858 | 26.87 | 0.01536 | 0.016 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 373483.52 | 373483.52 | 476.58 | 22.439 | 22.439 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 07:00:00 | 27.00 | 27.00 | 0.00854 | 21.55 | 0.01535 | 0.338 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.000 | 1.200 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 22.67 | 0.00036 | -26.20 | 0.00036 | 1.200 | 0.00 |
CORE_BOTTOM | 9918.52 | 9918.52 | 3.97 | 0.439 | 1.078 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00800 | -26.20 | 0.00036 | 1.078 | 0.00 |
CORE_MID | 383361.53 | 383361.53 | 153.58 | 17.020 | 17.020 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00800 | -26.20 | 0.00036 | 10.778 | 0.00 |
CORE_TOP | 80213.96 | 80213.96 | 32.14 | 3.579 | 3.579 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00800 | -26.20 | 0.00036 | 1.078 | 0.00 |
PERIMETER_BOT_ZN_3 | 16776.69 | 16776.69 | 53.53 | 0.750 | 0.750 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00760 | -26.20 | 0.00036 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_2 | 11241.99 | 11241.99 | 55.66 | 0.503 | 0.503 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00760 | -26.20 | 0.00036 | 0.087 | 0.00 |
PERIMETER_BOT_ZN_1 | 17643.48 | 17643.48 | 56.29 | 0.789 | 0.789 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00762 | -26.20 | 0.00036 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_4 | 9741.55 | 9741.55 | 48.23 | 0.435 | 0.435 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00753 | -26.20 | 0.00036 | 0.087 | 0.00 |
PERIMETER_MID_ZN_3 | 248978.34 | 248978.34 | 794.41 | 11.136 | 11.136 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00740 | -26.20 | 0.00036 | 1.353 | 0.00 |
PERIMETER_MID_ZN_2 | 162593.04 | 162593.04 | 805.02 | 7.273 | 7.273 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00738 | -26.20 | 0.00036 | 0.872 | 0.00 |
PERIMETER_MID_ZN_1 | 245012.15 | 245012.15 | 781.74 | 10.959 | 10.959 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00739 | -26.20 | 0.00036 | 1.353 | 0.00 |
PERIMETER_MID_ZN_4 | 161317.64 | 161317.64 | 798.70 | 7.215 | 7.215 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00738 | -26.20 | 0.00036 | 0.872 | 0.00 |
PERIMETER_TOP_ZN_3 | 31034.83 | 31034.83 | 99.02 | 1.389 | 1.389 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00740 | -26.20 | 0.00036 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_2 | 20222.13 | 20222.13 | 100.12 | 0.905 | 0.905 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00738 | -26.20 | 0.00036 | 0.087 | 0.00 |
PERIMETER_TOP_ZN_1 | 30604.98 | 30604.98 | 97.65 | 1.369 | 1.369 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00739 | -26.20 | 0.00036 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_4 | 20284.74 | 20284.74 | 100.43 | 0.908 | 0.908 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00739 | -26.20 | 0.00036 | 0.087 | 0.00 |
DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.016 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 05:30:00 | 18.00 | 24.07 | 0.00100 | -26.20 | 0.00036 | 0.016 | 0.00 |
DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.156 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 05:40:00 | 18.00 | 21.96 | 0.00100 | -26.20 | 0.00036 | 0.156 | 0.00 |
DATACENTER_TOP_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.016 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 05:30:00 | 18.00 | 19.62 | 0.00100 | -26.20 | 0.00036 | 0.016 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.338 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 07:00:00 | 18.00 | 27.00 | 0.00850 | -26.20 | 0.00036 | 0.338 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
VAV_BOT WITH REHEAT | 10.71 | 10.71 | 3.55 | 3.55 | 10.7065 | 3.5540 | 10.7065 | 0.3320 | 0.3000 |
VAV_MID WITH REHEAT | 100.09 | 100.09 | 53.60 | 53.60 | 100.0857 | 53.6027 | 100.0857 | 0.5356 | 0.3000 |
VAV_TOP WITH REHEAT | 11.01 | 11.01 | 8.15 | 8.15 | 11.0070 | 8.1487 | 11.0070 | 0.7403 | 0.3000 |
CAV_BAS | 6.24 | 6.24 | 1.20 | 1.20 | 6.2391 | 6.2391 | 6.2391 | 1.0000 | 1.0000 |
AIRLOOP DATACENTER BASEMENT | 22.44 | 22.44 | 0.34 | 0.34 | 22.4389 | 22.4388 | 22.4389 | 1.0000 | 1.0000 |
AIRLOOP DATACENTER BOT | 0.53 | 0.53 | 0.02 | 0.02 | 0.5326 | 0.5326 | 0.5326 | 1.0000 | 1.0000 |
AIRLOOP DATACENTER MID | 5.12 | 5.12 | 0.16 | 0.16 | 5.1172 | 5.1172 | 5.1172 | 1.0000 | 1.0000 |
AIRLOOP DATACENTER TOP | 0.52 | 0.52 | 0.02 | 0.02 | 0.5201 | 0.5201 | 0.5201 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | 29028.745 | 29028.745 | 1.989859 | 0.00025396 | 616.746 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 29028.74 | 29028.74 | 1.989859 | 12.80 | 11.18 | 0.00800000 | 40.00 | 20.63 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 0.0000 | 21.00 | 0.00799994 | 49.3286 | 9918.52 | 0.00 | 29131.08 | 29131.08 |
CORE_MID VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | 570892.971 | 570892.971 | 19.526786 | 0.00499442 | 14491.922 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 570892.97 | 570892.97 | 19.526786 | 12.80 | 11.18 | 0.00800000 | 40.00 | 20.63 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 0.0000 | 21.00 | 0.00800000 | 49.3289 | 383361.53 | 0.00 | 572658.51 | 572658.51 |
CORE_TOP VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | 114582.060 | 114582.060 | 3.578592 | 0.00100241 | 3023.604 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 114582.06 | 114582.06 | 3.578592 | 12.80 | 11.18 | 0.00800000 | 40.00 | 20.63 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 0.0000 | 21.00 | 0.00800000 | 49.3289 | 80213.96 | 0.00 | 114970.75 | 114970.75 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | 23970.797 | 23970.797 | 0.749819 | 0.00020971 | 632.092 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 23970.80 | 23970.80 | 0.749819 | 12.80 | 11.18 | 0.00800000 | 40.00 | 20.63 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 0.0000 | 21.00 | 0.00759678 | 46.8783 | 16776.69 | 0.00 | 24048.86 | 24048.86 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | 16063.240 | 16063.240 | 0.502501 | 0.00014053 | 423.562 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 16063.24 | 16063.24 | 0.502501 | 12.80 | 11.18 | 0.00800000 | 40.00 | 20.63 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 0.0000 | 21.00 | 0.00760094 | 46.9037 | 11241.99 | 0.00 | 16115.45 | 16115.45 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | 25210.562 | 25210.562 | 0.788655 | 0.00022055 | 664.762 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 25210.56 | 25210.56 | 0.788655 | 12.80 | 11.18 | 0.00800000 | 40.00 | 20.63 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 0.0000 | 21.00 | 0.00761884 | 47.0126 | 17643.48 | 0.00 | 25292.50 | 25292.50 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | 13916.898 | 13916.898 | 0.435247 | 0.00012175 | 367.009 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 13916.90 | 13916.90 | 0.435247 | 12.80 | 11.18 | 0.00800000 | 40.00 | 20.63 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 0.0000 | 21.00 | 0.00752969 | 46.4697 | 9741.55 | 0.00 | 13962.44 | 13962.44 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | 355759.670 | 355759.670 | 11.136305 | 0.00311234 | 9378.055 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 355759.67 | 354763.95 | 11.136305 | 12.80 | 11.18 | 0.00800000 | 40.00 | 20.63 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 0.0000 | 21.00 | 0.00739553 | 45.6566 | 248978.34 | 0.00 | 356896.09 | 356896.09 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | 232324.527 | 232324.527 | 7.272590 | 0.00203248 | 6124.163 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 232324.53 | 232324.53 | 7.272590 | 12.80 | 11.18 | 0.00800000 | 40.00 | 20.63 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 0.0000 | 21.00 | 0.00738392 | 45.5861 | 162593.04 | 0.00 | 233066.21 | 233066.21 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | 350087.601 | 350087.601 | 10.958583 | 0.00306272 | 9228.601 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 350087.60 | 350087.60 | 10.958583 | 12.80 | 11.18 | 0.00800000 | 40.00 | 20.63 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 0.0000 | 21.00 | 0.00738647 | 45.6014 | 245012.15 | 0.00 | 351206.38 | 351206.38 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | 230500.906 | 230500.906 | 7.215489 | 0.00201652 | 6076.097 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 230500.91 | 230500.91 | 7.215489 | 12.80 | 11.18 | 0.00800000 | 40.00 | 20.63 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 0.0000 | 21.00 | 0.00737968 | 45.5603 | 161317.64 | 0.00 | 231236.81 | 231236.81 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | 44347.663 | 44347.663 | 1.388530 | 0.00038797 | 1168.910 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 44347.66 | 44233.74 | 1.388530 | 12.80 | 11.18 | 0.00800000 | 40.00 | 20.63 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 0.0000 | 21.00 | 0.00739649 | 45.6646 | 31034.83 | 0.00 | 44488.44 | 44488.44 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | 28896.448 | 28896.448 | 0.904767 | 0.00025280 | 761.643 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 28896.45 | 28896.45 | 0.904767 | 12.80 | 11.18 | 0.00800000 | 40.00 | 20.63 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 0.0000 | 21.00 | 0.00738352 | 45.5858 | 20222.13 | 0.00 | 28988.13 | 28988.13 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | 43732.977 | 43732.977 | 1.369271 | 0.00038260 | 1152.713 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 43732.98 | 43732.98 | 1.369271 | 12.80 | 11.18 | 0.00800000 | 40.00 | 20.63 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 0.0000 | 21.00 | 0.00738873 | 45.6173 | 30604.98 | 0.00 | 43871.84 | 43871.84 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | 28986.021 | 28986.021 | 0.907578 | 0.00025358 | 764.001 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 28986.02 | 28986.02 | 0.907578 | 12.80 | 11.18 | 0.00800000 | 40.00 | 20.63 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 0.0000 | 21.00 | 0.00738568 | 45.5990 | 20284.74 | 0.00 | 29077.97 | 29077.97 |
VAV_BOT WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | VAV_BOT WITH REHEAT | 248199.408 | -999.000 | 10.706505 | 0.01055898 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 248199.41 | 186667.92 | 10.706505 | 25.75 | 18.09 | 0.01046154 | 10.87 | 10.87 | 0.00850000 | 31.20 | 0.01536508 | 23.13 | 23.7070 | 24.00 | 0.00889009 | 45.6222 | 137291.80 | 0.00 | 256058.88 | 182047.17 |
VAV_BOT WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoopHVAC | VAV_BOT WITH REHEAT | 109143.003 | 109143.003 | 3.211951 | 0.00095483 | 1667.898 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 06:20:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 109143.00 | 109143.00 | 3.211951 | -16.64 | -16.64 | 0.00187603 | 12.80 | 11.18 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 79.0233 | 19.77 | 0.00751155 | 50.0198 | 37211.16 | 0.00 | 87967.97 | 87967.97 |
VAV_MID WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | VAV_MID WITH REHEAT | 2406793.329 | -999.000 | 100.085745 | 0.10239055 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 2406793.33 | 1762330.81 | 100.085745 | 25.89 | 18.32 | 0.01069764 | 10.87 | 10.87 | 0.00850000 | 31.20 | 0.01536508 | 23.13 | 25.3602 | 24.00 | 0.00902860 | 46.3244 | 1264923.51 | 0.00 | 2481381.88 | 1722702.31 |
VAV_MID WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoopHVAC | VAV_MID WITH REHEAT | 1114716.075 | 1114716.075 | 30.025724 | 0.00975202 | 16651.032 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 05:10:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 1114716.08 | 1114716.08 | 30.025724 | -19.37 | -19.37 | 0.00142384 | 12.80 | 11.18 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 84.5340 | 17.60 | 0.00722954 | 55.1653 | 428412.45 | 0.00 | 874229.00 | 874229.00 |
VAV_TOP WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | VAV_TOP WITH REHEAT | 254402.436 | -999.000 | 11.006988 | 0.01082287 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | 254402.44 | 190806.62 | 11.006988 | 25.66 | 18.07 | 0.01047212 | 10.87 | 10.87 | 0.00850000 | 31.20 | 0.01536508 | 23.13 | 23.0598 | 24.00 | 0.00900280 | 46.1944 | 144269.04 | 0.00 | 262474.32 | 186081.74 |
VAV_TOP WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoopHVAC | VAV_TOP WITH REHEAT | 109771.985 | 109771.985 | 3.302096 | 0.00096033 | 1686.854 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 109771.99 | 109771.99 | 3.302096 | -16.00 | -16.00 | 0.00191406 | 12.80 | 11.18 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 76.8660 | 16.35 | 0.00723794 | 59.7667 | 42169.50 | 0.00 | 89053.33 | 89053.33 |
CAV_BAS COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | CAV_BAS | 134691.935 | -999.000 | 6.239103 | 0.00573011 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 12:00:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 134691.93 | 102331.56 | 6.239103 | 25.24 | 17.81 | 0.01031789 | 11.36 | 11.08 | 0.00850000 | 29.82 | 0.01536253 | 22.76 | 19.2360 | 24.00 | 0.00895655 | 45.9577 | 75613.31 | 0.00 | 139118.33 | 100330.21 |
CAV_BAS HEATING COIL | Coil:Heating:Water | AirLoopHVAC | CAV_BAS | 324321.767 | 324321.767 | 6.239103 | 0.00283731 | 6941.863 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 324321.77 | 324321.77 | 6.239103 | -5.04 | -9.12 | 0.00036134 | 40.00 | 20.63 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 19.2360 | 22.79 | 0.00036134 | 2.0225 | 0.00 | 0.00 | 258828.11 | 258828.11 |
AIRLOOP DATACENTER BASEMENT COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | 441003.934 | 302154.354 | 22.438911 | 0.01080016 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 07:10:00 | 407476.71 | 399257.84 | -999.0 | 28.52 | 17.56 | 0.00864508 | 12.80 | 11.68 | 0.00850000 | 31.20 | 0.01536508 | 23.13 | -999.0000 | 27.00 | 0.00854207 | 36.7046 | 373043.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BOT COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER BOT | 10359.221 | 7125.889 | 0.532608 | 0.00025370 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:10:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:10:00 | 9553.78 | 9177.33 | -999.0 | 27.99 | 17.49 | 0.00878043 | 12.80 | 11.68 | 0.00850000 | 26.87 | 0.01535708 | 21.94 | -999.0000 | 27.00 | 0.00858156 | 36.8695 | 8864.92 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER MID COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER MID | 99679.445 | 68510.105 | 5.117223 | 0.00244114 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:10:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:10:00 | 91951.94 | 88188.59 | -999.0 | 27.99 | 17.50 | 0.00879174 | 12.80 | 11.68 | 0.00850000 | 26.87 | 0.01535708 | 21.94 | -999.0000 | 27.00 | 0.00858486 | 36.8836 | 85172.54 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER TOP COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER TOP | 10125.786 | 6961.858 | 0.520142 | 0.00024798 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:10:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:10:00 | 9339.86 | 8963.39 | -999.0 | 27.99 | 17.50 | 0.00878715 | 12.80 | 11.68 | 0.00850000 | 26.87 | 0.01535708 | 21.94 | -999.0000 | 27.00 | 0.00858358 | 36.8781 | 8657.41 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BASEMENT HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | 441003.934 | 441003.934 | 22.438911 | 0.01080016 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 441003.93 | 441003.93 | 22.438911 | -26.20 | -26.20 | 0.00036134 | 40.00 | 20.63 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 1.5081 | 27.00 | 0.00850000 | 36.5206 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BOT HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER BOT | 10359.221 | 10359.221 | 0.532608 | 0.00025370 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 10359.22 | 10359.22 | 0.532608 | -26.20 | -26.20 | 0.00036134 | 40.00 | 20.63 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 2.9351 | 24.79 | 0.00100469 | 4.9795 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER MID HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER MID | 99679.445 | 99679.445 | 5.117223 | 0.00244114 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 99679.44 | 99679.44 | 5.117223 | -26.20 | -26.20 | 0.00036134 | 40.00 | 20.63 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 3.0548 | 23.25 | 0.00100470 | 5.4605 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER TOP HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER TOP | 10125.786 | 10125.786 | 0.520142 | 0.00024798 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 10125.79 | 10125.79 | 0.520142 | -26.20 | -26.20 | 0.00036134 | 40.00 | 20.63 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 3.0054 | 21.87 | 0.00100404 | 5.9367 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | 25854.499 | 25854.499 | -999.0 | -999.0 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 25854.50 | 25854.50 | 22.438911 | -0.40 | -0.40 | 0.00837726 | 40.00 | 20.63 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 1.5081 | 27.00 | 0.00850000 | 36.5206 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BOT_SUPPHEATCOIL | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER BOT | 1194.371 | 1194.371 | -999.0 | -999.0 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 1194.37 | 1194.37 | 0.532608 | -0.77 | -5.18 | 0.00098581 | 40.00 | 20.63 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 2.9351 | 24.79 | 0.00100469 | 4.9795 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER MID_SUPPHEATCOIL | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER MID | 11943.707 | 11943.707 | -999.0 | -999.0 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 11943.71 | 11943.71 | 5.117223 | -0.80 | -5.20 | 0.00098505 | 40.00 | 20.63 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 3.0548 | 23.25 | 0.00100470 | 5.4605 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER TOP_SUPPHEATCOIL | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER TOP | 1194.371 | 1194.371 | -999.0 | -999.0 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 1194.37 | 1194.37 | 0.520142 | -0.79 | -5.19 | 0.00098472 | 40.00 | 20.63 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 3.0054 | 21.87 | 0.00100404 | 5.9367 | 0.00 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 08:43:43
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
CORE_BOTTOM VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | CORE_BOTTOM | N/A | N/A | N/A | Yes | Yes | Yes | No | 29028.745 | 29028.745 | 1.989859 | 0.00025396 | 616.746 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 32.94547112 | 54.44 | 82.22 | 27.78 | 3842051.27 | 0.7556 | 0.770759 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 29028.74 | 29028.74 | 1.0000 | 2.28546470 | 1.989859 | 12.80 | 11.18 | 0.00800000 | 33059.8 | 40.00 | 20.63 | 0.00800000 | 60796.0 | 0.25393021 | 60.00 | 32.22 | 27.78 | 0.000 | 29028.74 | -26.20 | 0.00036134 | -26.20 | 0.00000000 | 0.0000 | 20.76 | 0.00799994 | 21.00 | 0.00799994 | 49.3286 | 9918.52 | 0.00 | 29131.08 | 29131.08 | 2.28546470 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 25.30 | 16.42 | 0.00800000 | 45806.1 | |
CORE_MID VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | CORE_MID | N/A | N/A | N/A | Yes | Yes | Yes | No | 570892.971 | 570892.971 | 19.526786 | 0.00499442 | 14491.922 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 32.94547112 | 54.44 | 82.22 | 27.78 | 3842051.27 | 14.8591 | 15.158112 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 570892.97 | 570892.97 | 1.0000 | 22.42760433 | 19.526786 | 12.80 | 11.18 | 0.00800000 | 33059.8 | 40.00 | 20.63 | 0.00800000 | 60796.0 | 4.99391127 | 60.00 | 32.22 | 27.78 | 0.000 | 570892.97 | -26.20 | 0.00036134 | -26.20 | 0.00000000 | 0.0000 | 20.86 | 0.00800000 | 21.00 | 0.00800000 | 49.3289 | 383361.53 | 0.00 | 572658.51 | 572658.51 | 22.42760433 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 37.84 | 20.53 | 0.00800000 | 58593.5 | |
CORE_TOP VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | CORE_TOP | N/A | N/A | N/A | Yes | Yes | Yes | No | 114582.060 | 114582.060 | 3.578592 | 0.00100241 | 3023.604 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 32.94547112 | 54.44 | 82.22 | 27.78 | 3842051.27 | 2.9823 | 3.042335 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 114582.06 | 114582.06 | 1.0000 | 4.11021254 | 3.578592 | 12.80 | 11.18 | 0.00800000 | 33059.8 | 40.00 | 20.63 | 0.00800000 | 60796.0 | 1.00231159 | 60.00 | 32.22 | 27.78 | 0.000 | 114582.06 | -26.20 | 0.00036134 | -26.20 | 0.00000000 | 0.0000 | 20.91 | 0.00800000 | 21.00 | 0.00800000 | 49.3289 | 80213.96 | 0.00 | 114970.75 | 114970.75 | 4.11021254 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.23 | 21.25 | 0.00800000 | 61031.8 | |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | PERIMETER_BOT_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 23970.797 | 23970.797 | 0.749819 | 0.00020971 | 632.092 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 32.94547112 | 54.44 | 82.22 | 27.78 | 3842051.27 | 0.6239 | 0.636463 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 23970.80 | 23970.80 | 1.0000 | 0.86120891 | 0.749819 | 12.80 | 11.18 | 0.00800000 | 33059.8 | 40.00 | 20.63 | 0.00800000 | 60796.0 | 0.20968560 | 60.00 | 32.22 | 27.78 | 0.000 | 23970.80 | -26.20 | 0.00036134 | -26.20 | 0.00000000 | 0.0000 | 20.95 | 0.00759678 | 21.00 | 0.00759678 | 46.8783 | 16776.69 | 0.00 | 24048.86 | 24048.86 | 0.86120891 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.18 | 21.24 | 0.00800000 | 60984.4 | |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | PERIMETER_BOT_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 16063.240 | 16063.240 | 0.502501 | 0.00014053 | 423.562 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 32.94547112 | 54.44 | 82.22 | 27.78 | 3842051.27 | 0.4181 | 0.426504 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 16063.24 | 16063.24 | 1.0000 | 0.57715090 | 0.502501 | 12.80 | 11.18 | 0.00800000 | 33059.8 | 40.00 | 20.63 | 0.00800000 | 60796.0 | 0.14051389 | 60.00 | 32.22 | 27.78 | 0.000 | 16063.24 | -26.20 | 0.00036134 | -26.20 | 0.00000000 | 0.0000 | 20.95 | 0.00760094 | 21.00 | 0.00760094 | 46.9037 | 11241.99 | 0.00 | 16115.45 | 16115.45 | 0.57715090 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.18 | 21.24 | 0.00800000 | 60982.3 | |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | PERIMETER_BOT_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 25210.562 | 25210.562 | 0.788655 | 0.00022055 | 664.762 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 32.94547112 | 54.44 | 82.22 | 27.78 | 3842051.27 | 0.6562 | 0.669380 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 25210.56 | 25210.56 | 1.0000 | 0.90581453 | 0.788655 | 12.80 | 11.18 | 0.00800000 | 33059.8 | 40.00 | 20.63 | 0.00800000 | 60796.0 | 0.22053049 | 60.00 | 32.22 | 27.78 | 0.000 | 25210.56 | -26.20 | 0.00036134 | -26.20 | 0.00000000 | 0.0000 | 20.95 | 0.00761884 | 21.00 | 0.00761884 | 47.0126 | 17643.48 | 0.00 | 25292.50 | 25292.50 | 0.90581453 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.18 | 21.24 | 0.00800000 | 60982.2 | |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | PERIMETER_BOT_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 13916.898 | 13916.898 | 0.435247 | 0.00012175 | 367.009 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 32.94547112 | 54.44 | 82.22 | 27.78 | 3842051.27 | 0.3622 | 0.369516 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 13916.90 | 13916.90 | 1.0000 | 0.49990519 | 0.435247 | 12.80 | 11.18 | 0.00800000 | 33059.8 | 40.00 | 20.63 | 0.00800000 | 60796.0 | 0.12173868 | 60.00 | 32.22 | 27.78 | 0.000 | 13916.90 | -26.20 | 0.00036134 | -26.20 | 0.00000000 | 0.0000 | 20.95 | 0.00752969 | 21.00 | 0.00752969 | 46.4697 | 9741.55 | 0.00 | 13962.44 | 13962.44 | 0.49990519 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.19 | 21.24 | 0.00800000 | 60990.0 | |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | PERIMETER_MID_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 355759.670 | 355759.670 | 11.136305 | 0.00311234 | 9378.055 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 32.94547112 | 54.44 | 82.22 | 27.78 | 3842051.27 | 9.2596 | 9.445982 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 355759.67 | 354763.95 | 1.0000 | 12.79066772 | 11.136305 | 12.80 | 11.18 | 0.00800000 | 33059.8 | 40.00 | 20.63 | 0.00800000 | 60796.0 | 3.11202330 | 60.00 | 32.22 | 27.78 | 0.000 | 355759.67 | -26.20 | 0.00036134 | -26.20 | 0.00000000 | 0.0000 | 20.94 | 0.00739553 | 21.00 | 0.00739553 | 45.6566 | 248978.34 | 0.00 | 356896.09 | 356896.09 | 12.79066772 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.16 | 21.23 | 0.00800000 | 60962.7 | |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | PERIMETER_MID_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 232324.527 | 232324.527 | 7.272590 | 0.00203248 | 6124.163 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 32.94547112 | 54.44 | 82.22 | 27.78 | 3842051.27 | 6.0469 | 6.168584 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 232324.53 | 232324.53 | 1.0000 | 8.35297532 | 7.272590 | 12.80 | 11.18 | 0.00800000 | 33059.8 | 40.00 | 20.63 | 0.00800000 | 60796.0 | 2.03226898 | 60.00 | 32.22 | 27.78 | 0.000 | 232324.53 | -26.20 | 0.00036134 | -26.20 | 0.00000000 | 0.0000 | 20.94 | 0.00738392 | 21.00 | 0.00738392 | 45.5861 | 162593.04 | 0.00 | 233066.21 | 233066.21 | 8.35297532 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.16 | 21.23 | 0.00800000 | 60962.0 | |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | PERIMETER_MID_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 350087.601 | 350087.601 | 10.958583 | 0.00306272 | 9228.601 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 32.94547112 | 54.44 | 82.22 | 27.78 | 3842051.27 | 9.1120 | 9.295380 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 350087.60 | 350087.60 | 1.0000 | 12.58654421 | 10.958583 | 12.80 | 11.18 | 0.00800000 | 33059.8 | 40.00 | 20.63 | 0.00800000 | 60796.0 | 3.06240663 | 60.00 | 32.22 | 27.78 | 0.000 | 350087.60 | -26.20 | 0.00036134 | -26.20 | 0.00000000 | 0.0000 | 20.94 | 0.00738647 | 21.00 | 0.00738647 | 45.6014 | 245012.15 | 0.00 | 351206.38 | 351206.38 | 12.58654421 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.16 | 21.23 | 0.00800000 | 60963.1 | |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | PERIMETER_MID_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 230500.906 | 230500.906 | 7.215489 | 0.00201652 | 6076.097 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 32.94547112 | 54.44 | 82.22 | 27.78 | 3842051.27 | 5.9994 | 6.120164 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 230500.91 | 230500.91 | 1.0000 | 8.28739155 | 7.215489 | 12.80 | 11.18 | 0.00800000 | 33059.8 | 40.00 | 20.63 | 0.00800000 | 60796.0 | 2.01631678 | 60.00 | 32.22 | 27.78 | 0.000 | 230500.91 | -26.20 | 0.00036134 | -26.20 | 0.00000000 | 0.0000 | 20.94 | 0.00737968 | 21.00 | 0.00737968 | 45.5603 | 161317.64 | 0.00 | 231236.81 | 231236.81 | 8.28739155 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.16 | 21.23 | 0.00800000 | 60962.1 | |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | PERIMETER_TOP_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 44347.663 | 44347.663 | 1.388530 | 0.00038797 | 1168.910 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 32.94547112 | 54.44 | 82.22 | 27.78 | 3842051.27 | 1.1543 | 1.177501 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 44347.66 | 44233.74 | 1.0000 | 1.59480444 | 1.388530 | 12.80 | 11.18 | 0.00800000 | 33059.8 | 40.00 | 20.63 | 0.00800000 | 60796.0 | 0.38793313 | 60.00 | 32.22 | 27.78 | 0.000 | 44347.66 | -26.20 | 0.00036134 | -26.20 | 0.00000000 | 0.0000 | 20.94 | 0.00739649 | 21.00 | 0.00739649 | 45.6646 | 31034.83 | 0.00 | 44488.44 | 44488.44 | 1.59480444 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.16 | 21.23 | 0.00800000 | 60955.7 | |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | PERIMETER_TOP_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 28896.448 | 28896.448 | 0.904767 | 0.00025280 | 761.643 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 32.94547112 | 54.44 | 82.22 | 27.78 | 3842051.27 | 0.7521 | 0.767246 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 28896.45 | 28896.45 | 1.0000 | 1.03917556 | 0.904767 | 12.80 | 11.18 | 0.00800000 | 33059.8 | 40.00 | 20.63 | 0.00800000 | 60796.0 | 0.25277294 | 60.00 | 32.22 | 27.78 | 0.000 | 28896.45 | -26.20 | 0.00036134 | -26.20 | 0.00000000 | 0.0000 | 20.94 | 0.00738352 | 21.00 | 0.00738352 | 45.5858 | 20222.13 | 0.00 | 28988.13 | 28988.13 | 1.03917556 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.16 | 21.23 | 0.00800000 | 60955.1 | |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | PERIMETER_TOP_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 43732.977 | 43732.977 | 1.369271 | 0.00038260 | 1152.713 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 32.94547112 | 54.44 | 82.22 | 27.78 | 3842051.27 | 1.1383 | 1.161180 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 43732.98 | 43732.98 | 1.0000 | 1.57268458 | 1.369271 | 12.80 | 11.18 | 0.00800000 | 33059.8 | 40.00 | 20.63 | 0.00800000 | 60796.0 | 0.38255613 | 60.00 | 32.22 | 27.78 | 0.000 | 43732.98 | -26.20 | 0.00036134 | -26.20 | 0.00000000 | 0.0000 | 20.94 | 0.00738873 | 21.00 | 0.00738873 | 45.6173 | 30604.98 | 0.00 | 43871.84 | 43871.84 | 1.57268458 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.16 | 21.23 | 0.00800000 | 60956.0 | |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | PERIMETER_TOP_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 28986.021 | 28986.021 | 0.907578 | 0.00025358 | 764.001 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 32.94547112 | 54.44 | 82.22 | 27.78 | 3842051.27 | 0.7544 | 0.769625 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 28986.02 | 28986.02 | 1.0000 | 1.04240352 | 0.907578 | 12.80 | 11.18 | 0.00800000 | 33059.8 | 40.00 | 20.63 | 0.00800000 | 60796.0 | 0.25355649 | 60.00 | 32.22 | 27.78 | 0.000 | 28986.02 | -26.20 | 0.00036134 | -26.20 | 0.00000000 | 0.0000 | 20.94 | 0.00738568 | 21.00 | 0.00738568 | 45.5990 | 20284.74 | 0.00 | 29077.97 | 29077.97 | 1.04240352 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.16 | 21.23 | 0.00800000 | 60954.9 | |
VAV_BOT WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV_BOT WITH REHEAT | CORE_BOTTOM; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 248199.408 | -999.000 | 10.706505 | 0.01055898 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1024.2875 | 1004.8586 | 1.1486 | VAV_BOT WITH REHEAT FAN | Fan:VariableVolume | 10.706505 | 12.29701846 | 4197.9300 | 999.8980 | 129.48929198 | 12.27 | 6.67 | 5.60 | 3044087.11 | 8.1535 | 8.153492 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | Sensible | 248199.41 | 186667.92 | 1.0000 | 12.29701846 | 10.706505 | 25.75 | 18.09 | 0.01046154 | 52535.2 | 10.87 | 10.87 | 0.00850000 | 32351.5 | 10.55789944 | 6.67 | 12.27 | 5.60 | 24320.824 | 223878.58 | 31.20 | 0.01536508 | 23.13 | 2.53819000 | 23.7070 | 24.00 | 0.00889009 | 24.00 | 0.00889009 | 45.6222 | 137291.80 | 0.00 | 256058.88 | 182047.17 | 12.29701846 | 25.75 | 18.60 | 0.01046154 | 52535.2 | 11.29 | 11.03 | 0.00807501 | 31712.3 | |
VAV_BOT WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV_BOT WITH REHEAT | CORE_BOTTOM; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 109143.003 | 109143.003 | 3.211951 | 0.00095483 | 1667.898 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | VAV_BOT WITH REHEAT FAN | Fan:VariableVolume | 10.706505 | 12.29701846 | 4197.9300 | 999.8980 | 32.94547112 | 54.44 | 82.22 | 27.78 | 3842051.27 | 2.8407 | 2.897919 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 06:20:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 109143.00 | 109143.00 | 1.0000 | 3.68910554 | 3.211951 | -16.64 | -16.64 | 0.00187603 | -12088.9 | 12.80 | 11.18 | 0.00800000 | 33059.8 | 0.95473320 | 60.00 | 32.22 | 27.78 | 0.000 | 109143.00 | -26.20 | 0.00036134 | -26.20 | 2.53819000 | 79.0233 | 19.36 | 0.00758215 | 19.77 | 0.00751155 | 50.0198 | 37211.16 | 0.00 | 87967.97 | 87967.97 | 3.68910554 | 2.80 | -1.38 | 0.00187603 | 7515.2 | 26.45 | 11.01 | 0.00187603 | 31360.5 | |
VAV_MID WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV_MID WITH REHEAT | CORE_MID; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 2406793.329 | -999.000 | 100.085745 | 0.10239055 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1024.7264 | 1004.8586 | 1.1486 | VAV_MID WITH REHEAT FAN | Fan:VariableVolume | 100.085745 | 114.95406607 | 4197.9300 | 999.8980 | 129.48929198 | 12.27 | 6.67 | 5.60 | 3044087.11 | 79.0645 | 79.064535 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | Sensible | 2406793.33 | 1762330.81 | 1.0000 | 114.95406607 | 100.085745 | 25.89 | 18.32 | 0.01069764 | 53289.3 | 10.87 | 10.87 | 0.00850000 | 32352.3 | 102.38010711 | 6.67 | 12.27 | 5.60 | 227354.102 | 2179439.23 | 31.20 | 0.01536508 | 23.13 | 25.38195000 | 25.3602 | 24.00 | 0.00902860 | 24.00 | 0.00902860 | 46.3244 | 1264923.51 | 0.00 | 2481381.88 | 1722702.31 | 114.95406607 | 25.89 | 18.83 | 0.01069764 | 53289.3 | 11.27 | 11.03 | 0.00808061 | 31703.4 | |
VAV_MID WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV_MID WITH REHEAT | CORE_MID; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 1114716.075 | 1114716.075 | 30.025724 | 0.00975202 | 16651.032 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | VAV_MID WITH REHEAT FAN | Fan:VariableVolume | 100.085745 | 114.95406607 | 4197.9300 | 999.8980 | 32.94547112 | 54.44 | 82.22 | 27.78 | 3842051.27 | 29.0136 | 29.597475 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 05:10:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 1114716.08 | 1114716.08 | 1.0000 | 34.48621982 | 30.025724 | -19.37 | -19.37 | 0.00142384 | -15951.3 | 12.80 | 11.18 | 0.00800000 | 33059.8 | 9.75102770 | 60.00 | 32.22 | 27.78 | 0.000 | 1114716.08 | -26.20 | 0.00036134 | -26.20 | 25.38195000 | 84.5340 | 17.98 | 0.00723125 | 17.60 | 0.00722954 | 55.1653 | 428412.45 | 0.00 | 874229.00 | 874229.00 | 34.48621982 | 2.80 | -2.10 | 0.00142384 | 6381.9 | 27.96 | 11.18 | 0.00142384 | 31732.0 | |
VAV_TOP WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV_TOP WITH REHEAT | CORE_TOP; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 254402.436 | -999.000 | 11.006988 | 0.01082287 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1024.3072 | 1004.8586 | 1.1486 | VAV_TOP WITH REHEAT FAN | Fan:VariableVolume | 11.006988 | 12.64213998 | 4197.9300 | 999.8980 | 129.48929198 | 12.27 | 6.67 | 5.60 | 3044087.11 | 8.3573 | 8.357265 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | Sensible | 254402.44 | 190806.62 | 1.0000 | 12.64213998 | 11.006988 | 25.66 | 18.07 | 0.01047212 | 52474.9 | 10.87 | 10.87 | 0.00850000 | 32351.5 | 10.82176368 | 6.67 | 12.27 | 5.60 | 25003.399 | 229399.04 | 31.20 | 0.01536508 | 23.13 | 2.53819000 | 23.0598 | 24.00 | 0.00900280 | 24.00 | 0.00900280 | 46.1944 | 144269.04 | 0.00 | 262474.32 | 186081.74 | 12.64213998 | 25.66 | 18.58 | 0.01047212 | 52474.9 | 11.29 | 11.03 | 0.00807606 | 31713.0 | |
VAV_TOP WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV_TOP WITH REHEAT | CORE_TOP; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 109771.985 | 109771.985 | 3.302096 | 0.00096033 | 1686.854 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | VAV_TOP WITH REHEAT FAN | Fan:VariableVolume | 11.006988 | 12.64213998 | 4197.9300 | 999.8980 | 32.94547112 | 54.44 | 82.22 | 27.78 | 3842051.27 | 2.8571 | 2.914620 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 109771.99 | 109771.99 | 1.0000 | 3.79264199 | 3.302096 | -16.00 | -16.00 | 0.00191406 | -11350.9 | 12.80 | 11.18 | 0.00800000 | 33059.8 | 0.96023525 | 60.00 | 32.22 | 27.78 | 0.000 | 109771.99 | -26.20 | 0.00036134 | -26.20 | 2.53819000 | 76.8660 | 17.88 | 0.00707320 | 16.35 | 0.00723794 | 59.7667 | 42169.50 | 0.00 | 89053.33 | 89053.33 | 3.79264199 | 2.80 | -1.32 | 0.00191406 | 7610.5 | 26.09 | 10.90 | 0.00191406 | 31091.0 | |
CAV_BAS COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | CAV_BAS | BASEMENT | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 134691.935 | -999.000 | 6.239103 | 0.00573011 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1024.0204 | 1004.8586 | 1.1486 | CAV_BAS FAN | Fan:ConstantVolume | 6.239103 | 7.16595843 | 4197.9300 | 999.8980 | 129.48929198 | 12.27 | 6.67 | 5.60 | 3044087.11 | 4.4247 | 4.424707 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 12:00:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 11:00:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | Sensible | 134691.93 | 102331.56 | 1.0000 | 7.16595843 | 6.239103 | 25.24 | 17.81 | 0.01031789 | 51646.8 | 11.36 | 11.08 | 0.00850000 | 32850.7 | 5.72952175 | 6.67 | 12.27 | 5.60 | 10579.363 | 124112.57 | 29.82 | 0.01536253 | 22.76 | 1.20015641 | 19.2360 | 24.00 | 0.00895655 | 24.00 | 0.00895655 | 45.9577 | 75613.31 | 0.00 | 139118.33 | 100330.21 | 7.16595843 | 25.24 | 18.32 | 0.01031789 | 51646.8 | 11.56 | 11.25 | 0.00817202 | 32233.0 | |
CAV_BAS HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | CAV_BAS | BASEMENT | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 324321.767 | 324321.767 | 6.239103 | 0.00283731 | 6941.863 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | CAV_BAS FAN | Fan:ConstantVolume | 6.239103 | 7.16595843 | 4197.9300 | 999.8980 | 32.94547112 | 54.44 | 82.22 | 27.78 | 3842051.27 | 8.4414 | 8.611256 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 324321.77 | 324321.77 | 1.0000 | 7.16595843 | 6.239103 | -5.04 | -9.12 | 0.00036134 | -4163.9 | 40.00 | 20.63 | 0.00800000 | 60796.0 | 2.83701886 | 60.00 | 32.22 | 27.78 | 0.000 | 324321.77 | -26.20 | 0.00036134 | -26.20 | 1.20015641 | 19.2360 | 0.00 | 0.00036134 | 22.79 | 0.00036134 | 2.0225 | 0.00 | 0.00 | 258828.11 | 258828.11 | 7.16595843 | 12.80 | 2.49 | 0.00036134 | 13774.2 | 48.72 | 18.00 | 0.00036134 | 49893.4 | |
AIRLOOP DATACENTER BASEMENT COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | DATACENTER_BASEMENT_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 441003.934 | 302154.354 | 22.438911 | 0.01080016 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1020.9108 | 1004.8586 | 1.1486 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 07:10:00 | Sensible | 407476.71 | 399257.84 | 0.9240 | -999.0 | -999.0 | 28.52 | 17.56 | 0.00864508 | 50738.4 | 12.80 | 11.68 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 407476.71 | 31.20 | 0.01536508 | 23.13 | 0.33839277 | -999.0000 | 27.00 | 0.00854207 | 27.00 | 0.00854207 | 36.7046 | 373043.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BOT COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BOT | DATACENTER_BOT_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 10359.221 | 7125.889 | 0.532608 | 0.00025370 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1021.1624 | 1004.8586 | 1.1486 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:10:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:10:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:10:00 | Sensible | 9553.78 | 9177.33 | 0.9222 | -999.0 | -999.0 | 27.99 | 17.49 | 0.00878043 | 50537.9 | 12.80 | 11.68 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9553.78 | 26.87 | 0.01535708 | 21.94 | 0.01563234 | -999.0000 | 27.00 | 0.00858156 | 27.00 | 0.00858156 | 36.8695 | 8864.92 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER MID COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER MID | DATACENTER_MID_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 99679.445 | 68510.105 | 5.117223 | 0.00244114 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1021.1834 | 1004.8586 | 1.1486 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:10:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:10:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:10:00 | Sensible | 91951.94 | 88188.59 | 0.9225 | -999.0 | -999.0 | 27.99 | 17.50 | 0.00879174 | 50566.6 | 12.80 | 11.68 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 91951.94 | 26.87 | 0.01535708 | 21.94 | 0.15632344 | -999.0000 | 27.00 | 0.00858486 | 27.00 | 0.00858486 | 36.8836 | 85172.54 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER TOP COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER TOP | DATACENTER_TOP_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 10125.786 | 6961.858 | 0.520142 | 0.00024798 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1021.1749 | 1004.8586 | 1.1486 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:10:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:10:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:10:00 | Sensible | 9339.86 | 8963.39 | 0.9224 | -999.0 | -999.0 | 27.99 | 17.50 | 0.00878715 | 50555.0 | 12.80 | 11.68 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9339.86 | 26.87 | 0.01535708 | 21.94 | 0.01563234 | -999.0000 | 27.00 | 0.00858358 | 27.00 | 0.00858358 | 36.8781 | 8657.41 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BASEMENT HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | DATACENTER_BASEMENT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 441003.934 | 441003.934 | 22.438911 | 0.01080016 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 1.1486 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 441003.93 | 441003.93 | 1.0000 | 25.77234231 | 22.438911 | -26.20 | -26.20 | 0.00036134 | -25440.7 | 40.00 | 20.63 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 441003.93 | -26.20 | 0.00036134 | -26.20 | 0.33839277 | 1.5081 | 0.00 | 0.00850000 | 27.00 | 0.00850000 | 36.5206 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BOT HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BOT | DATACENTER_BOT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 10359.221 | 10359.221 | 0.532608 | 0.00025370 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 1.1486 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 10359.22 | 10359.22 | 1.0000 | 0.61173043 | 0.532608 | -26.20 | -26.20 | 0.00036134 | -25440.7 | 40.00 | 20.63 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 10359.22 | -26.20 | 0.00036134 | -26.20 | 0.01563234 | 2.9351 | 0.00 | 0.00100469 | 24.79 | 0.00100469 | 4.9795 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER MID HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER MID | DATACENTER_MID_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 99679.445 | 99679.445 | 5.117223 | 0.00244114 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 1.1486 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 99679.44 | 99679.44 | 1.0000 | 5.87741642 | 5.117223 | -26.20 | -26.20 | 0.00036134 | -25440.7 | 40.00 | 20.63 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 99679.44 | -26.20 | 0.00036134 | -26.20 | 0.15632344 | 3.0548 | 0.00 | 0.00100470 | 23.25 | 0.00100470 | 5.4605 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER TOP HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER TOP | DATACENTER_TOP_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 10125.786 | 10125.786 | 0.520142 | 0.00024798 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 1.1486 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 10125.79 | 10125.79 | 1.0000 | 0.59741222 | 0.520142 | -26.20 | -26.20 | 0.00036134 | -25440.7 | 40.00 | 20.63 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 10125.79 | -26.20 | 0.00036134 | -26.20 | 0.01563234 | 3.0054 | 0.00 | 0.00100404 | 21.87 | 0.00100404 | 5.9367 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | DATACENTER_BASEMENT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 25854.499 | 25854.499 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | AIRLOOP DATACENTER BASEMENT SUPPLY FAN | Fan:OnOff | 22.438911 | 25.77234231 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 25854.50 | 25854.50 | 1.0000 | 25.77234231 | 22.438911 | -0.40 | -0.40 | 0.00837726 | 20547.9 | 40.00 | 20.63 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 25854.50 | -26.20 | 0.00036134 | -26.20 | 0.33839277 | 1.5081 | 0.00 | 0.00850000 | 27.00 | 0.00850000 | 36.5206 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BOT_SUPPHEATCOIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BOT | DATACENTER_BOT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 1194.371 | 1194.371 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | AIRLOOP DATACENTER BOT SUPPLY FAN | Fan:OnOff | 0.532608 | 0.61173043 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 1194.37 | 1194.37 | 1.0000 | 0.61173043 | 0.532608 | -0.77 | -5.18 | 0.00098581 | 1691.3 | 40.00 | 20.63 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 1194.37 | -26.20 | 0.00036134 | -26.20 | 0.01563234 | 2.9351 | 0.00 | 0.00100469 | 24.79 | 0.00100469 | 4.9795 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER MID_SUPPHEATCOIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER MID | DATACENTER_MID_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 11943.707 | 11943.707 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | AIRLOOP DATACENTER MID SUPPLY FAN | Fan:OnOff | 5.117223 | 5.87741642 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 11943.71 | 11943.71 | 1.0000 | 5.87741642 | 5.117223 | -0.80 | -5.20 | 0.00098505 | 1657.8 | 40.00 | 20.63 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 11943.71 | -26.20 | 0.00036134 | -26.20 | 0.15632344 | 3.0548 | 0.00 | 0.00100470 | 23.25 | 0.00100470 | 5.4605 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER TOP_SUPPHEATCOIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER TOP | DATACENTER_TOP_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 1194.371 | 1194.371 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | AIRLOOP DATACENTER TOP SUPPLY FAN | Fan:OnOff | 0.520142 | 0.59741222 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 1194.37 | 1194.37 | 1.0000 | 0.59741222 | 0.520142 | -0.79 | -5.19 | 0.00098472 | 1670.1 | 40.00 | 20.63 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 1194.37 | -26.20 | 0.00036134 | -26.20 | 0.01563234 | 3.0054 | 0.00 | 0.00100404 | 21.87 | 0.00100404 | 5.9367 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 08:43:43
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
VAV_BOT WITH REHEAT_OA_CONTROLLER | DifferentialDryBulb | 2.54 | 10.71 | - | |||
VAV_MID WITH REHEAT_OA_CONTROLLER | DifferentialDryBulb | 25.38 | 100.09 | - | |||
VAV_TOP WITH REHEAT_OA_CONTROLLER | DifferentialDryBulb | 2.54 | 11.01 | - | |||
CAV_BAS_OA_CONTROLLER | DifferentialDryBulb | 1.20 | 6.24 | - | |||
AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER | DifferentialDryBulb | 0.34 | 22.44 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
CORE_BOTTOM | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_MID | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_TOP | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
BASEMENT | 2624.33 | 2257.17 | 557.00 |
CORE_BOTTOM | 2453.50 | 1862.17 | 36.33 |
CORE_MID | 2445.00 | 3180.17 | 523.00 |
CORE_TOP | 3060.50 | 3706.67 | 1325.00 |
PERIMETER_BOT_ZN_3 | 3133.50 | 3511.83 | 1255.50 |
PERIMETER_BOT_ZN_2 | 3228.17 | 3616.00 | 1394.67 |
PERIMETER_BOT_ZN_1 | 3310.17 | 3156.50 | 1190.67 |
PERIMETER_BOT_ZN_4 | 3148.33 | 3039.50 | 895.00 |
PERIMETER_MID_ZN_3 | 3945.17 | 4123.00 | 2436.83 |
PERIMETER_MID_ZN_2 | 3275.50 | 3511.17 | 2024.83 |
PERIMETER_MID_ZN_1 | 3584.50 | 3590.50 | 1763.83 |
PERIMETER_MID_ZN_4 | 3768.50 | 4012.33 | 2138.67 |
PERIMETER_TOP_ZN_3 | 4168.17 | 4376.67 | 2827.67 |
PERIMETER_TOP_ZN_2 | 4061.33 | 4177.50 | 2566.17 |
PERIMETER_TOP_ZN_1 | 3762.50 | 3867.17 | 2139.33 |
PERIMETER_TOP_ZN_4 | 3946.33 | 4196.67 | 2476.00 |
DATACENTER_BOT_ZN_6 | 5663.50 | 1110.00 | 1105.83 |
DATACENTER_MID_ZN_6 | 4776.50 | 660.67 | 354.00 |
DATACENTER_TOP_ZN_6 | 4377.00 | 1094.33 | 551.33 |
DATACENTER_BASEMENT_ZN_6 | 5943.00 | 5498.67 | 5498.67 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
Facility | 5943.00 | 5943.00 | 5943.00 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
BASEMENT | 0.00 | 30.17 | 0.00 | 0.83 |
CORE_BOTTOM | 0.00 | 0.33 | 0.00 | 0.00 |
CORE_MID | 2.67 | 0.00 | 0.33 | 0.00 |
CORE_TOP | 25.50 | 0.00 | 4.50 | 0.00 |
PERIMETER_BOT_ZN_3 | 27.67 | 5.33 | 5.83 | 3.50 |
PERIMETER_BOT_ZN_2 | 22.83 | 26.67 | 1.17 | 26.67 |
PERIMETER_BOT_ZN_1 | 21.67 | 40.83 | 2.00 | 39.83 |
PERIMETER_BOT_ZN_4 | 8.67 | 74.00 | 0.17 | 36.00 |
PERIMETER_MID_ZN_3 | 295.00 | 3.17 | 111.67 | 1.83 |
PERIMETER_MID_ZN_2 | 167.83 | 26.17 | 30.33 | 25.83 |
PERIMETER_MID_ZN_1 | 145.50 | 38.50 | 19.00 | 37.00 |
PERIMETER_MID_ZN_4 | 138.50 | 35.33 | 24.50 | 19.33 |
PERIMETER_TOP_ZN_3 | 469.17 | 5.67 | 166.33 | 3.50 |
PERIMETER_TOP_ZN_2 | 297.67 | 27.83 | 66.33 | 26.50 |
PERIMETER_TOP_ZN_1 | 277.67 | 28.67 | 58.50 | 26.00 |
PERIMETER_TOP_ZN_4 | 233.00 | 33.00 | 50.17 | 18.17 |
DATACENTER_BOT_ZN_6 | 0.00 | 3.00 | 0.00 | 3.00 |
DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 410.50 | 0.00 | 349.83 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 546.67 | 598.67 | 182.50 | 469.83 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 08:43:43
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 62.22 | 149.60 | 6779.02 | 1.256 | 0.000 | 0.000 | 0.000 |
CORE_BOTTOM | 55.88 | 134.35 | 6849.35 | 1.036 | 0.000 | 0.000 | 0.000 |
CORE_MID | 55.88 | 134.35 | 6849.35 | 0.838 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 55.88 | 134.35 | 6849.35 | 0.814 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 7.02 | 16.87 | 860.00 | 0.990 | 0.064 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 4.52 | 10.87 | 554.22 | 1.646 | 0.066 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 7.02 | 16.87 | 860.02 | 1.493 | 0.064 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 4.52 | 10.87 | 554.22 | 2.172 | 0.066 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 7.02 | 16.87 | 860.00 | 0.929 | 0.148 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 3.95 | 10.87 | 554.22 | 1.605 | 0.163 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 7.02 | 16.87 | 860.02 | 1.456 | 0.149 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 4.52 | 10.87 | 554.22 | 1.773 | 0.154 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 7.02 | 16.87 | 860.00 | 1.010 | 0.184 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 4.52 | 10.87 | 554.22 | 1.718 | 0.190 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 7.02 | 16.87 | 860.02 | 1.474 | 0.184 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 4.52 | 10.87 | 554.22 | 1.826 | 0.190 | 0.000 | 0.000 |
DATACENTER_BOT_ZN_6 | 0.81 | 1.95 | 99.34 | 0.427 | 0.000 | 0.000 | 0.000 |
DATACENTER_MID_ZN_6 | 0.81 | 1.95 | 99.34 | 0.427 | 0.000 | 0.000 | 0.000 |
DATACENTER_TOP_ZN_6 | 0.81 | 1.95 | 99.34 | 0.427 | 0.000 | 0.000 | 0.000 |
DATACENTER_BASEMENT_ZN_6 | 17.54 | 42.18 | 1911.37 | 24.636 | 0.000 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 62.22 | 149.60 | 6779.02 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_BOTTOM | 55.88 | 134.35 | 6849.35 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_MID | 55.88 | 134.35 | 6849.35 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 55.88 | 134.35 | 6849.35 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 7.02 | 16.87 | 860.00 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 4.52 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 7.02 | 16.87 | 860.02 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 4.52 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 7.02 | 16.87 | 860.00 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 3.95 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 7.02 | 16.87 | 860.02 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 4.52 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 7.02 | 16.87 | 860.00 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 4.52 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 7.02 | 16.87 | 860.02 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 4.52 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
DATACENTER_BOT_ZN_6 | 0.81 | 1.95 | 99.34 | 0.000 | 0.000 | 0.000 | 0.000 |
DATACENTER_MID_ZN_6 | 0.81 | 1.95 | 99.34 | 0.000 | 0.000 | 0.000 | 0.000 |
DATACENTER_TOP_ZN_6 | 0.81 | 1.95 | 99.34 | 0.000 | 0.000 | 0.000 | 0.000 |
DATACENTER_BASEMENT_ZN_6 | 17.54 | 42.18 | 1911.37 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 08:43:43
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
BASEMENT | CAV_BAS | 62.22 | 149.60 | 6779.02 | 2779.43 | 1.2002 | 1.200 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | 55.88 | 134.35 | 6849.35 | 2496.12 | 0.0000 | 1.078 |
CORE_MID | VAV_MID WITH REHEAT | 55.88 | 134.35 | 6849.35 | 2496.12 | 0.0000 | 10.778 |
CORE_TOP | VAV_TOP WITH REHEAT | 55.88 | 134.35 | 6849.35 | 2496.12 | 0.0000 | 1.078 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | 7.02 | 16.87 | 860.00 | 313.41 | 0.0000 | 0.135 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | 4.52 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | 7.02 | 16.87 | 860.02 | 313.42 | 0.0000 | 0.135 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | 4.52 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | 7.02 | 16.87 | 860.00 | 313.41 | 0.0000 | 1.353 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | 3.95 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.872 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | 7.02 | 16.87 | 860.02 | 313.42 | 0.0000 | 1.353 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | 4.52 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.872 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | 7.02 | 16.87 | 860.00 | 313.41 | 0.0000 | 0.135 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | 4.52 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | 7.02 | 16.87 | 860.02 | 313.42 | 0.0000 | 0.135 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | 4.52 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | 0.81 | 1.95 | 99.34 | 36.20 | 0.0156 | 0.016 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | 0.81 | 1.95 | 99.34 | 36.20 | 0.1563 | 0.156 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | 0.81 | 1.95 | 99.34 | 36.20 | 0.0156 | 0.016 |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | 17.54 | 42.18 | 1911.37 | 783.68 | 0.3384 | 0.338 |
Total Facility | 1031.21 | 2493.19 | 126016.35 | 46320.38 | 1.7261 | 158.471 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
BASEMENT | 51645001.16 | 0.00 | 51645001.16 | 0.00 | 51645001.16 | 37848132.68 | 4020.46 | 1353.67 | 3385.87 | 278.72 |
CORE_BOTTOM | 43838060.18 | 0.00 | 43838060.18 | 0.00 | 43838060.18 | 33990283.35 | 3733.26 | 6.43 | 5020.31 | 480.24 |
CORE_MID | 0.35E+09 | 0.00 | 0.35E+09 | 0.00 | 0.35E+09 | 0.34E+09 | 4082.50 | 14.41 | 4663.08 | 601.63 |
CORE_TOP | 33311187.42 | 0.00 | 33311187.42 | 0.00 | 33311187.42 | 33990283.35 | 4118.62 | 10.44 | 4630.94 | 463.04 |
PERIMETER_BOT_ZN_3 | 5261934.42 | 0.00 | 5261934.42 | 650322.70 | 5912257.12 | 4267819.30 | 4266.90 | 56.17 | 4436.93 | 480.24 |
PERIMETER_BOT_ZN_2 | 5679725.53 | 0.00 | 5679725.53 | 433548.17 | 6113273.70 | 2750345.05 | 3601.93 | 8.24 | 5149.83 | 480.24 |
PERIMETER_BOT_ZN_1 | 7890030.81 | 0.00 | 7890030.81 | 650322.70 | 8540353.51 | 4267912.63 | 3676.48 | 7.93 | 5075.58 | 480.24 |
PERIMETER_BOT_ZN_4 | 7487237.07 | 0.00 | 7487237.07 | 433548.17 | 7920785.24 | 2750345.05 | 3523.93 | 9.01 | 5227.06 | 480.24 |
PERIMETER_MID_ZN_3 | 48446918.21 | 0.00 | 48446918.21 | 1525195.93 | 49972114.14 | 42678193.03 | 4042.64 | 11.31 | 4706.05 | 601.63 |
PERIMETER_MID_ZN_2 | 57543336.80 | 0.00 | 57543336.80 | 1016796.59 | 58560133.39 | 27503450.52 | 3902.30 | 5.40 | 4852.29 | 1510.63 |
PERIMETER_MID_ZN_1 | 75187925.65 | 0.00 | 75187925.65 | 1525195.93 | 76713121.58 | 42679126.28 | 3984.63 | 2.76 | 4772.61 | 601.63 |
PERIMETER_MID_ZN_4 | 59662920.15 | 0.00 | 59662920.15 | 1016796.59 | 60679716.74 | 27503450.52 | 3892.96 | 4.22 | 4862.83 | 601.63 |
PERIMETER_TOP_ZN_3 | 5211197.90 | 0.00 | 5211197.90 | 1893702.01 | 7104899.91 | 4267819.30 | 4055.78 | 1.73 | 4702.49 | 463.04 |
PERIMETER_TOP_ZN_2 | 5690451.58 | 0.00 | 5690451.58 | 1262467.14 | 6952918.73 | 2750345.05 | 3998.97 | 1.27 | 4759.76 | 463.04 |
PERIMETER_TOP_ZN_1 | 7546950.65 | 0.00 | 7546950.65 | 1893702.01 | 9440652.66 | 4267912.63 | 4033.31 | 2.39 | 4724.30 | 463.04 |
PERIMETER_TOP_ZN_4 | 6077890.26 | 0.00 | 6077890.26 | 1262467.14 | 7340357.40 | 2750345.05 | 3989.48 | 1.87 | 4768.65 | 463.04 |
DATACENTER_BOT_ZN_6 | 244296.02 | 0.00 | 244296.02 | 0.00 | 244296.02 | 492981.60 | 4419.00 | 4341.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 2442960.18 | 0.00 | 2442960.18 | 0.00 | 2442960.18 | 4929815.99 | 4419.00 | 4341.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 244296.02 | 0.00 | 244296.02 | 0.00 | 244296.02 | 492981.60 | 4419.00 | 4341.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.39E+09 | 0.00 | 0.39E+09 | 0.00 | 0.39E+09 | 10671554.30 | 40.48 | 129.17 | 8590.36 | 2806.50 |
Total Facility | 0.65E+10 | 0.00 | 0.65E+10 | 59319930.40 | 0.65E+10 | 0.50E+10 | 5008.03 | 4399.73 | 8721.13 | 3715.50 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
BASEMENT | 2.3101 | 0.0000 | 2.3101 | 0.0000 | 2.3101 | 1.2002 | 1365.06 | 1352.23 | 3225.70 |
CORE_BOTTOM | 1.9268 | 0.0000 | 1.9268 | 0.0000 | 1.9268 | 1.0778 | 1238.14 | 5.62 | 4699.25 |
CORE_MID | 15.6077 | 0.0000 | 15.6077 | 0.0000 | 15.6077 | 10.7782 | 1372.63 | 13.83 | 4556.55 |
CORE_TOP | 1.5169 | 0.0000 | 1.5169 | 0.0000 | 1.5169 | 1.0778 | 1386.57 | 10.31 | 4546.12 |
PERIMETER_BOT_ZN_3 | 0.2315 | 0.0000 | 0.2315 | 0.0149 | 0.2464 | 0.1353 | 1769.63 | 54.90 | 4118.48 |
PERIMETER_BOT_ZN_2 | 0.2484 | 0.0000 | 0.2484 | 0.0100 | 0.2584 | 0.0872 | 1147.40 | 6.63 | 4788.97 |
PERIMETER_BOT_ZN_1 | 0.3494 | 0.0000 | 0.3494 | 0.0149 | 0.3643 | 0.1353 | 1203.80 | 4.86 | 4734.34 |
PERIMETER_BOT_ZN_4 | 0.3273 | 0.0000 | 0.3273 | 0.0100 | 0.3373 | 0.0872 | 1089.46 | 4.84 | 4848.70 |
PERIMETER_MID_ZN_3 | 2.1802 | 0.0000 | 2.1802 | 0.0351 | 2.2153 | 1.3533 | 1339.64 | 10.46 | 4592.91 |
PERIMETER_MID_ZN_2 | 2.4273 | 0.0000 | 2.4273 | 0.0248 | 2.4521 | 0.8721 | 1239.03 | 1.34 | 3793.63 |
PERIMETER_MID_ZN_1 | 3.4105 | 0.0000 | 3.4105 | 0.0351 | 3.4455 | 1.3533 | 1288.08 | 2.17 | 4652.75 |
PERIMETER_MID_ZN_4 | 2.6798 | 0.0000 | 2.6798 | 0.0234 | 2.7031 | 0.8721 | 1233.65 | 2.36 | 4706.99 |
PERIMETER_TOP_ZN_3 | 0.2373 | 0.0000 | 0.2373 | 0.0435 | 0.2808 | 0.1353 | 1330.17 | 1.19 | 4611.64 |
PERIMETER_TOP_ZN_2 | 0.2596 | 0.0000 | 0.2596 | 0.0290 | 0.2886 | 0.0872 | 1291.91 | 0.81 | 4650.28 |
PERIMETER_TOP_ZN_1 | 0.3453 | 0.0000 | 0.3453 | 0.0435 | 0.3888 | 0.1353 | 1312.34 | 0.99 | 4629.68 |
PERIMETER_TOP_ZN_4 | 0.2760 | 0.0000 | 0.2760 | 0.0290 | 0.3050 | 0.0872 | 1285.66 | 0.65 | 4656.70 |
DATACENTER_BOT_ZN_6 | 0.0114 | 0.0000 | 0.0114 | 0.0000 | 0.0114 | 0.0156 | 1602.00 | 4341.00 | 0.00 |
DATACENTER_MID_ZN_6 | 0.1142 | 0.0000 | 0.1142 | 0.0000 | 0.1142 | 0.1563 | 1602.00 | 4341.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 0.0114 | 0.0000 | 0.0114 | 0.0000 | 0.0114 | 0.0156 | 1602.00 | 4341.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 12.6248 | 0.0000 | 12.6248 | 0.0000 | 12.6248 | 0.3384 | 29.98 | 129.17 | 5783.86 |
Total Facility | 284.8725 | 0.0000 | 284.8725 | 1.3774 | 286.2499 | 158.4706 | 2191.03 | 4376.96 | 5914.63 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
VAV_BOT WITH REHEAT | 92550892.91 | 0.00 | 92550892.91 | 48026705.38 | 3612.06 | 5.18 | 5142.76 | 480.24 |
VAV_MID WITH REHEAT | 0.77E+09 | 0.00 | 0.77E+09 | 0.48E+09 | 3973.29 | 5.06 | 4781.64 | 601.63 |
VAV_TOP WITH REHEAT | 76298179.80 | 0.00 | 76298179.80 | 48026705.38 | 4023.55 | 3.23 | 4733.22 | 462.97 |
CAV_BAS | 68129077.92 | 0.00 | 68129077.92 | 37848132.68 | 3960.55 | 2.86 | 4796.59 | 278.72 |
AIRLOOP DATACENTER BASEMENT | 0.52E+09 | 0.00 | 0.52E+09 | 10671554.30 | 40.48 | 0.00 | 8719.52 | 2806.50 |
AIRLOOP DATACENTER BOT | 322270.54 | 0.00 | 322270.54 | 492981.60 | 4419.00 | 0.00 | 4341.00 | 0.00 |
AIRLOOP DATACENTER MID | 3222705.41 | 0.00 | 3222705.41 | 4929815.99 | 4419.00 | 0.00 | 4341.00 | 0.00 |
AIRLOOP DATACENTER TOP | 322270.54 | 0.00 | 322270.54 | 492981.60 | 4419.00 | 0.00 | 4341.00 | 0.00 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
VAV_BOT WITH REHEAT | 4.0677 | 0.0000 | 4.0677 | 1.5229 | 1146.10 | 3.86 | 4793.04 |
VAV_MID WITH REHEAT | 34.9230 | 0.0000 | 34.9230 | 15.2292 | 1276.43 | 3.85 | 4662.73 |
VAV_TOP WITH REHEAT | 3.4762 | 0.0000 | 3.4762 | 1.5229 | 1305.41 | 1.41 | 4636.18 |
CAV_BAS | 3.0475 | 0.0000 | 3.0475 | 1.2002 | 1334.23 | 1.11 | 4607.66 |
AIRLOOP DATACENTER BASEMENT | 16.6544 | 0.0000 | 16.6544 | 0.3384 | 29.98 | 0.00 | 5913.02 |
AIRLOOP DATACENTER BOT | 0.0151 | 0.0000 | 0.0151 | 0.0156 | 1602.00 | 0.00 | 4341.00 |
AIRLOOP DATACENTER MID | 0.1506 | 0.0000 | 0.1506 | 0.1563 | 1602.00 | 0.00 | 4341.00 |
AIRLOOP DATACENTER TOP | 0.0151 | 0.0000 | 0.0151 | 0.0156 | 1602.00 | 0.00 | 4341.00 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
VAV_BOT WITH REHEAT | 0.00 | 2331.48 | 3060.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
VAV_MID WITH REHEAT | 0.00 | 2626.86 | 2916.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
VAV_TOP WITH REHEAT | 0.00 | 2768.83 | 2609.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CAV_BAS | 0.00 | 1338.96 | 3593.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER BASEMENT | 0.00 | 129.17 | 8590.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER BOT | 0.00 | 4341.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER MID | 0.00 | 4341.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER TOP | 0.00 | 4341.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
VAV_BOT WITH REHEAT | 0.0000 | 3.3492 | 6.3439 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
VAV_MID WITH REHEAT | 0.0000 | 33.4959 | 51.6799 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
VAV_TOP WITH REHEAT | 0.0000 | 3.3493 | 5.3066 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
CAV_BAS | 0.0000 | 1.5844 | 4.8239 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
AIRLOOP DATACENTER BASEMENT | 0.0000 | 0.4470 | 17.1052 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
AIRLOOP DATACENTER BOT | 0.0000 | 0.0206 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
AIRLOOP DATACENTER MID | 0.0000 | 0.2063 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
AIRLOOP DATACENTER TOP | 0.0000 | 0.0206 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 08:43:43
Surfaces by ClassTotal | Outdoors | |
Wall | 98 | 30 |
Floor | 41 | 0 |
Roof | 30 | 1 |
Internal Mass | 16 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 24 | 24 |
Door | 12 | 12 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 8 |
Conditioned Zones | 23 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 3 |
Count | |
IDF Objects | 1401 |
Defaulted Fields | 1182 |
Fields with Defaults | 3927 |
Autosized Fields | 338 |
Autosizable Fields | 414 |
Autocalculated Fields | 226 |
Autocalculatable Fields | 473 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 08:43:43
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 28073.68 | 331495.99 | 28-MAY-05:00 | 2184392.29 | 04-AUG-15:30 |
Electricity:Building | 18607.86 | 225715.65 | 07-MAY-17:10 | 1164206.62 | 01-DEC-16:30 |
Electricity:Zone:BASEMENT | 687.24 | 14732.47 | 01-JAN-00:10 | 36407.88 | 02-JAN-08:10 |
Electricity:SpaceType:GENERAL | 18607.86 | 225715.65 | 07-MAY-17:10 | 1164206.62 | 01-DEC-16:30 |
InteriorLights:Electricity | 3931.47 | 18459.50 | 01-JAN-10:10 | 385834.94 | 02-JAN-16:40 |
InteriorLights:Electricity:Zone:BASEMENT | 262.84 | 1274.92 | 01-JAN-00:10 | 22950.34 | 02-JAN-08:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 3931.47 | 18459.50 | 01-JAN-10:10 | 385834.94 | 02-JAN-16:40 |
LightsWired:InteriorLights:Electricity | 3931.47 | 18459.50 | 01-JAN-10:10 | 385834.94 | 02-JAN-16:40 |
LightsWired:InteriorLights:Electricity:Zone:BASEMENT | 262.84 | 1274.92 | 01-JAN-00:10 | 22950.34 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 3931.47 | 18459.50 | 01-JAN-10:10 | 385834.94 | 02-JAN-16:40 |
Electricity:Zone:CORE_BOTTOM | 525.67 | 5598.20 | 01-JAN-00:10 | 37817.64 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_BOTTOM | 236.05 | 1144.97 | 01-JAN-00:10 | 20611.01 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_BOTTOM | 236.05 | 1144.97 | 01-JAN-00:10 | 20611.01 | 02-JAN-08:10 |
Electricity:Zone:CORE_MID | 5256.66 | 55981.88 | 01-JAN-00:10 | 378175.77 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_MID | 2360.53 | 11449.71 | 01-JAN-00:10 | 206110.14 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_MID | 2360.53 | 11449.71 | 01-JAN-00:10 | 206110.14 | 02-JAN-08:10 |
Electricity:Zone:CORE_TOP | 525.67 | 5598.19 | 01-JAN-00:10 | 37817.58 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_TOP | 236.05 | 1144.97 | 01-JAN-00:10 | 20611.01 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_TOP | 236.05 | 1144.97 | 01-JAN-00:10 | 20611.01 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_3 | 53.86 | 627.57 | 09-APR-17:10 | 4748.47 | 02-JAN-16:20 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 17.49 | 68.40 | 01-JAN-10:10 | 2587.92 | 02-JAN-16:20 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 17.49 | 68.40 | 01-JAN-10:10 | 2587.92 | 02-JAN-16:20 |
Electricity:Zone:PERIMETER_BOT_ZN_2 | 34.61 | 404.43 | 09-APR-17:10 | 3060.10 | 02-JAN-16:20 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 11.17 | 44.08 | 01-JAN-09:40 | 1667.75 | 02-JAN-16:20 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 11.17 | 44.08 | 01-JAN-09:40 | 1667.75 | 02-JAN-16:20 |
Electricity:Zone:PERIMETER_BOT_ZN_1 | 53.53 | 627.58 | 26-MAR-17:10 | 4748.56 | 02-JAN-16:40 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 17.16 | 68.40 | 01-JAN-09:40 | 2587.98 | 02-JAN-16:40 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 17.16 | 68.40 | 01-JAN-09:40 | 2587.98 | 02-JAN-16:40 |
Electricity:Zone:PERIMETER_BOT_ZN_4 | 34.57 | 404.43 | 12-MAR-17:10 | 3060.09 | 02-JAN-16:40 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 11.13 | 44.08 | 01-JAN-10:00 | 1667.75 | 02-JAN-16:40 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 11.13 | 44.08 | 01-JAN-10:00 | 1667.75 | 02-JAN-16:40 |
Electricity:Zone:PERIMETER_MID_ZN_3 | 538.14 | 6275.73 | 26-MAR-17:10 | 47484.70 | 02-JAN-16:20 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 174.48 | 684.02 | 01-JAN-10:00 | 25879.19 | 02-JAN-16:20 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 174.48 | 684.02 | 01-JAN-10:00 | 25879.19 | 02-JAN-16:20 |
Electricity:Zone:PERIMETER_MID_ZN_2 | 345.88 | 4044.32 | 09-APR-17:10 | 30600.95 | 02-JAN-16:20 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 111.53 | 440.81 | 01-JAN-09:40 | 16677.53 | 02-JAN-16:20 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 111.53 | 440.81 | 01-JAN-09:40 | 16677.53 | 02-JAN-16:20 |
Electricity:Zone:PERIMETER_MID_ZN_1 | 535.06 | 6275.83 | 26-MAR-17:10 | 47485.60 | 02-JAN-16:40 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 171.40 | 684.04 | 01-JAN-09:40 | 25879.75 | 02-JAN-16:40 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 171.40 | 684.04 | 01-JAN-09:40 | 25879.75 | 02-JAN-16:40 |
Electricity:Zone:PERIMETER_MID_ZN_4 | 345.49 | 4044.30 | 12-MAR-17:10 | 30600.86 | 02-JAN-16:40 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 111.13 | 440.81 | 01-JAN-10:00 | 16677.53 | 02-JAN-16:40 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 111.13 | 440.81 | 01-JAN-10:00 | 16677.53 | 02-JAN-16:40 |
Electricity:Zone:PERIMETER_TOP_ZN_3 | 53.81 | 627.57 | 26-MAR-17:10 | 4748.47 | 02-JAN-16:20 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 17.45 | 68.40 | 01-JAN-10:00 | 2587.92 | 02-JAN-16:20 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 17.45 | 68.40 | 01-JAN-10:00 | 2587.92 | 02-JAN-16:20 |
Electricity:Zone:PERIMETER_TOP_ZN_2 | 34.59 | 404.43 | 09-APR-17:10 | 3060.10 | 02-JAN-16:20 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 11.15 | 44.08 | 01-JAN-09:40 | 1667.75 | 02-JAN-16:20 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 11.15 | 44.08 | 01-JAN-09:40 | 1667.75 | 02-JAN-16:20 |
Electricity:Zone:PERIMETER_TOP_ZN_1 | 53.51 | 627.58 | 26-MAR-17:10 | 4748.56 | 02-JAN-16:40 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 17.14 | 68.40 | 01-JAN-09:40 | 2587.98 | 02-JAN-16:40 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 17.14 | 68.40 | 01-JAN-09:40 | 2587.98 | 02-JAN-16:40 |
Electricity:Zone:PERIMETER_TOP_ZN_4 | 34.55 | 404.43 | 12-MAR-17:10 | 3060.09 | 02-JAN-16:40 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 11.11 | 44.08 | 01-JAN-10:00 | 1667.75 | 02-JAN-16:40 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 11.11 | 44.08 | 01-JAN-10:00 | 1667.75 | 02-JAN-16:40 |
Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 7568.97 | 95267.60 | 01-JAN-00:10 | 386103.53 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 74.11 | 359.47 | 01-JAN-00:10 | 6471.01 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 74.11 | 359.47 | 01-JAN-00:10 | 6471.01 | 02-JAN-08:10 |
Electricity:Zone:DATACENTER_BOT_ZN_6 | 160.51 | 1980.76 | 01-JAN-00:10 | 8373.14 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_BOT_ZN_6 | 6.63 | 32.15 | 01-JAN-00:10 | 578.72 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_BOT_ZN_6 | 6.63 | 32.15 | 01-JAN-00:10 | 578.72 | 02-JAN-08:10 |
Electricity:Zone:DATACENTER_MID_ZN_6 | 1605.09 | 19807.58 | 01-JAN-00:10 | 83731.41 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_MID_ZN_6 | 66.28 | 321.53 | 01-JAN-00:10 | 5787.18 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_MID_ZN_6 | 66.28 | 321.53 | 01-JAN-00:10 | 5787.18 | 02-JAN-08:10 |
Electricity:Zone:DATACENTER_TOP_ZN_6 | 160.51 | 1980.76 | 01-JAN-00:10 | 8373.14 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_TOP_ZN_6 | 6.63 | 32.15 | 01-JAN-00:10 | 578.72 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_TOP_ZN_6 | 6.63 | 32.15 | 01-JAN-00:10 | 578.72 | 02-JAN-08:10 |
InteriorEquipment:Electricity | 14676.40 | 207256.16 | 01-JAN-00:10 | 778371.69 | 03-APR-07:10 |
InteriorEquipment:Electricity:Zone:BASEMENT | 424.40 | 13457.54 | 01-JAN-00:10 | 13457.54 | 01-JAN-00:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 14676.40 | 207256.16 | 01-JAN-00:10 | 778371.69 | 03-APR-07:10 |
MiscPlug:InteriorEquipment:Electricity | 5334.97 | 88964.76 | 01-JAN-00:10 | 305206.10 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:BASEMENT | 424.40 | 13457.54 | 01-JAN-00:10 | 13457.54 | 01-JAN-00:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 5334.97 | 88964.76 | 01-JAN-00:10 | 305206.10 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 289.61 | 4453.23 | 01-JAN-00:10 | 17206.63 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 289.61 | 4453.23 | 01-JAN-00:10 | 17206.63 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_MID | 2896.13 | 44532.17 | 01-JAN-00:10 | 172065.63 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_MID | 2896.13 | 44532.17 | 01-JAN-00:10 | 172065.63 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_TOP | 289.61 | 4453.22 | 01-JAN-00:10 | 17206.56 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_TOP | 289.61 | 4453.22 | 01-JAN-00:10 | 17206.56 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 36.37 | 559.17 | 01-JAN-00:10 | 2160.55 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 36.37 | 559.17 | 01-JAN-00:10 | 2160.55 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.34 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.34 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 36.37 | 559.18 | 01-JAN-00:10 | 2160.58 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 36.37 | 559.18 | 01-JAN-00:10 | 2160.58 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.33 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.33 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 363.65 | 5591.71 | 01-JAN-00:10 | 21605.52 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 363.65 | 5591.71 | 01-JAN-00:10 | 21605.52 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 234.35 | 3603.51 | 01-JAN-00:10 | 13923.42 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 234.35 | 3603.51 | 01-JAN-00:10 | 13923.42 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 363.66 | 5591.79 | 01-JAN-00:10 | 21605.85 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 363.66 | 5591.79 | 01-JAN-00:10 | 21605.85 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 234.35 | 3603.49 | 01-JAN-00:10 | 13923.33 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 234.35 | 3603.49 | 01-JAN-00:10 | 13923.33 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 36.37 | 559.17 | 01-JAN-00:10 | 2160.55 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 36.37 | 559.17 | 01-JAN-00:10 | 2160.55 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.34 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.34 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 36.37 | 559.18 | 01-JAN-00:10 | 2160.58 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 36.37 | 559.18 | 01-JAN-00:10 | 2160.58 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.33 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.33 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 7494.86 | 94908.13 | 01-JAN-00:10 | 379632.52 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity | 9341.42 | 118291.40 | 01-JAN-00:10 | 473165.59 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 7494.86 | 94908.13 | 01-JAN-00:10 | 379632.52 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:SpaceType:GENERAL | 9341.42 | 118291.40 | 01-JAN-00:10 | 473165.59 | 31-MAR-23:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_BOT_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_BOT_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_MID_ZN_6 | 1538.81 | 19486.06 | 01-JAN-00:10 | 77944.22 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_MID_ZN_6 | 1538.81 | 19486.06 | 01-JAN-00:10 | 77944.22 | 31-MAR-23:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_TOP_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_TOP_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
Electricity:Plant | 1773.53 | 3569.56 | 31-JAN-00:50 | 634321.48 | 04-AUG-07:10 |
HeatRejection:Electricity | 584.47 | 58.96 | 31-JAN-04:00 | 93806.32 | 18-APR-09:10 |
General:HeatRejection:Electricity | 584.47 | 58.96 | 31-JAN-04:00 | 93806.32 | 18-APR-09:10 |
Electricity:HVAC | 5140.18 | 50696.35 | 14-MAY-06:00 | 515394.23 | 04-AUG-15:20 |
ExteriorEquipment:Electricity | 1934.79 | 28603.11 | 01-JAN-00:10 | 118535.44 | 17-JAN-08:20 |
Transformer:ExteriorEquipment:Electricity | 80.18 | 1421.04 | 01-JAN-00:10 | 5057.48 | 01-DEC-16:40 |
ElectricityPurchased:Facility | 28073.68 | 331495.99 | 28-MAY-05:00 | 2184392.29 | 04-AUG-15:30 |
ElectricityPurchased:Plant | 28073.68 | 331495.99 | 28-MAY-05:00 | 2184392.29 | 04-AUG-15:30 |
Cogeneration:ElectricityPurchased | 28073.68 | 331495.99 | 28-MAY-05:00 | 2184392.29 | 04-AUG-15:30 |
General:Cogeneration:ElectricityPurchased | 28073.68 | 331495.99 | 28-MAY-05:00 | 2184392.29 | 04-AUG-15:30 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 28073.68 | 331495.99 | 28-MAY-05:00 | 2184392.29 | 04-AUG-15:30 |
ElectricityNet:Plant | 28073.68 | 331495.99 | 28-MAY-05:00 | 2184392.29 | 04-AUG-15:30 |
Cogeneration:ElectricityNet | 28073.68 | 331495.99 | 28-MAY-05:00 | 2184392.29 | 04-AUG-15:30 |
General:Cogeneration:ElectricityNet | 28073.68 | 331495.99 | 28-MAY-05:00 | 2184392.29 | 04-AUG-15:30 |
Fans:Electricity | 2486.89 | 43918.34 | 10-JAN-01:20 | 307984.46 | 04-AUG-15:20 |
General:Fans:Electricity | 2486.89 | 43918.34 | 10-JAN-01:20 | 307984.46 | 04-AUG-15:20 |
ExteriorLights:Electricity | 697.49 | 0.00 | 01-JAN-08:00 | 57580.60 | 01-JAN-06:10 |
General:ExteriorLights:Electricity | 697.49 | 0.00 | 01-JAN-08:00 | 57580.60 | 01-JAN-06:10 |
ElevatorLift:ExteriorEquipment:Electricity | 1848.78 | 27144.47 | 01-JAN-00:10 | 113101.96 | 01-JAN-07:10 |
ElevatorLightsFan:ExteriorEquipment:Electricity | 5.83 | 37.60 | 01-JAN-00:10 | 376.00 | 01-JAN-07:10 |
HeatRecovery:Electricity | 52.05 | 0.00 | 01-JAN-00:10 | 5613.48 | 02-JAN-07:10 |
General:HeatRecovery:Electricity | 52.05 | 0.00 | 01-JAN-00:10 | 5613.48 | 02-JAN-07:10 |
Cooling:Electricity | 1808.25 | 1420.09 | 30-JAN-08:10 | 638501.30 | 04-AUG-07:10 |
General:Cooling:Electricity | 1808.25 | 1420.09 | 30-JAN-08:10 | 638501.30 | 04-AUG-07:10 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Humidifier:Electricity | 1498.95 | 0.00 | 19-MAR-11:40 | 100000.00 | 14-FEB-14:30 |
General:Humidifier:Electricity | 1498.95 | 0.00 | 19-MAR-11:40 | 100000.00 | 14-FEB-14:30 |
Boiler Parasitic:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Pumps:Electricity | 402.91 | 3505.15 | 06-JAN-00:20 | 65178.11 | 04-AUG-07:20 |
General:Pumps:Electricity | 402.91 | 3505.15 | 06-JAN-00:20 | 65178.11 | 04-AUG-07:20 |
WIRED_LTG_ELECTRICITY | 110.47 | 0.00 | 01-JAN-00:10 | 10841.96 | 02-JAN-16:50 |
WIRED_INT_EQUIP | 5334.97 | 88964.76 | 31-MAR-23:10 | 305206.10 | 03-APR-07:10 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 4811.13 | 8146.58 | 05-JAN-22:20 | 3389064.52 | 30-JAN-07:10 |
NaturalGas:Plant | 4811.13 | 8146.58 | 05-JAN-22:20 | 3389064.52 | 30-JAN-07:10 |
Heating:NaturalGas | 3954.87 | 0.00 | 01-JAN-00:40 | 3355734.44 | 30-JAN-07:10 |
Boiler:Heating:NaturalGas | 3954.87 | 0.00 | 01-JAN-00:40 | 3355734.44 | 30-JAN-07:10 |
WaterSystems:NaturalGas | 856.26 | 8146.58 | 02-JAN-05:20 | 88693.35 | 21-FEB-12:40 |
Water Heater:WaterSystems:NaturalGas | 856.26 | 8146.58 | 02-JAN-05:20 | 88693.35 | 21-FEB-12:40 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
PlantLoopCoolingDemand:Facility | 9722.36 | 3166.37 | 30-JAN-08:10 | 3893355.62 | 04-AUG-07:20 |
PlantLoopCoolingDemand:HVAC | 9722.36 | 3166.37 | 30-JAN-08:10 | 3893355.62 | 04-AUG-07:20 |
CoolingCoils:PlantLoopCoolingDemand | 9722.36 | 3166.37 | 30-JAN-08:10 | 3893355.62 | 04-AUG-07:20 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 6750.72 | 0.00 | 19-MAR-23:10 | 0.00 | 07-SEP-12:50 |
Water:HVAC | 557.61 | 0.00 | 19-MAR-11:40 | 0.00 | 01-MAR-04:10 |
Humidifier:Water | 557.61 | 0.00 | 19-MAR-11:40 | 0.00 | 01-MAR-04:10 |
General:Humidifier:Water | 557.61 | 0.00 | 19-MAR-11:40 | 0.00 | 01-MAR-04:10 |
MainsWater:Facility | 6750.72 | 0.00 | 19-MAR-23:10 | 0.00 | 07-SEP-12:50 |
MainsWater:HVAC | 557.61 | 0.00 | 19-MAR-11:40 | 0.00 | 01-MAR-04:10 |
Humidifier:MainsWater | 557.61 | 0.00 | 19-MAR-11:40 | 0.00 | 01-MAR-04:10 |
General:Humidifier:MainsWater | 557.61 | 0.00 | 19-MAR-11:40 | 0.00 | 01-MAR-04:10 |
Water:Plant | 6193.11 | 0.00 | 01-JAN-00:10 | 0.00 | 07-SEP-12:50 |
WaterSystems:Water | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterUse:WaterSystems:Water | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
MainsWater:Plant | 6193.11 | 0.00 | 01-JAN-00:10 | 0.00 | 07-SEP-12:50 |
WaterSystems:MainsWater | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterUse:WaterSystems:MainsWater | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water Heater:WaterSystems:Water | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:MainsWater | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
HeatRejection:Water | 3912.94 | 0.00 | 01-JAN-00:10 | 0.00 | 07-SEP-13:10 |
General:HeatRejection:Water | 3912.94 | 0.00 | 01-JAN-00:10 | 0.00 | 07-SEP-13:10 |
HeatRejection:MainsWater | 3912.94 | 0.00 | 01-JAN-00:10 | 0.00 | 07-SEP-13:10 |
General:HeatRejection:MainsWater | 3912.94 | 0.00 | 01-JAN-00:10 | 0.00 | 07-SEP-13:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 55575.16 | 93182.04 | 23-JAN-03:50 | 14916292.99 | 04-AUG-07:20 |
EnergyTransfer:Building | 19641.68 | 88588.34 | 11-JAN-22:10 | 1844796.15 | 11-DEC-06:10 |
EnergyTransfer:Zone:BASEMENT | 686.02 | 0.00 | 01-JAN-00:10 | 68219.07 | 24-JUL-05:10 |
Heating:EnergyTransfer | 1909.15 | 0.00 | 01-FEB-22:10 | 1552171.83 | 30-JAN-05:10 |
Heating:EnergyTransfer:Zone:BASEMENT | 2.59 | 0.00 | 01-JAN-00:10 | 16279.68 | 15-APR-16:10 |
General:Heating:EnergyTransfer | 1909.15 | 0.00 | 01-FEB-22:10 | 1552171.83 | 30-JAN-05:10 |
General:Heating:EnergyTransfer:Zone:BASEMENT | 2.59 | 0.00 | 01-JAN-00:10 | 16279.68 | 15-APR-16:10 |
Cooling:EnergyTransfer | 17732.54 | 82694.58 | 30-JAN-06:00 | 1778961.62 | 04-AUG-15:20 |
Cooling:EnergyTransfer:Zone:BASEMENT | 683.43 | 0.00 | 01-JAN-00:10 | 68219.07 | 24-JUL-05:10 |
General:Cooling:EnergyTransfer | 17732.54 | 82694.58 | 30-JAN-06:00 | 1778961.62 | 04-AUG-15:20 |
General:Cooling:EnergyTransfer:Zone:BASEMENT | 683.43 | 0.00 | 01-JAN-00:10 | 68219.07 | 24-JUL-05:10 |
EnergyTransfer:Zone:CORE_BOTTOM | 601.86 | 0.00 | 01-JAN-00:10 | 56145.41 | 04-AUG-16:00 |
Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.00 | 0.00 | 01-JAN-00:10 | 4015.57 | 06-FEB-06:10 |
General:Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.00 | 0.00 | 01-JAN-00:10 | 4015.57 | 06-FEB-06:10 |
Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 601.86 | 0.00 | 01-JAN-00:10 | 56145.41 | 04-AUG-16:00 |
General:Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 601.86 | 0.00 | 01-JAN-00:10 | 56145.41 | 04-AUG-16:00 |
EnergyTransfer:Zone:CORE_MID | 4315.82 | 0.00 | 01-JAN-00:40 | 560742.28 | 02-JAN-05:10 |
Heating:EnergyTransfer:Zone:CORE_MID | 34.23 | 0.00 | 01-JAN-00:10 | 560742.28 | 02-JAN-05:10 |
General:Heating:EnergyTransfer:Zone:CORE_MID | 34.23 | 0.00 | 01-JAN-00:10 | 560742.28 | 02-JAN-05:10 |
Cooling:EnergyTransfer:Zone:CORE_MID | 4281.60 | 0.00 | 01-JAN-00:40 | 456141.75 | 27-JUN-16:00 |
General:Cooling:EnergyTransfer:Zone:CORE_MID | 4281.60 | 0.00 | 01-JAN-00:40 | 456141.75 | 27-JUN-16:00 |
EnergyTransfer:Zone:CORE_TOP | 400.57 | 0.00 | 01-JAN-00:40 | 75501.35 | 30-JAN-05:10 |
Heating:EnergyTransfer:Zone:CORE_TOP | 29.76 | 0.00 | 01-JAN-00:40 | 75501.35 | 30-JAN-05:10 |
General:Heating:EnergyTransfer:Zone:CORE_TOP | 29.76 | 0.00 | 01-JAN-00:40 | 75501.35 | 30-JAN-05:10 |
Cooling:EnergyTransfer:Zone:CORE_TOP | 370.82 | 0.00 | 01-JAN-00:20 | 52930.57 | 04-AUG-15:20 |
General:Cooling:EnergyTransfer:Zone:CORE_TOP | 370.82 | 0.00 | 01-JAN-00:20 | 52930.57 | 04-AUG-15:20 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 70.19 | 0.00 | 01-JAN-00:10 | 13670.00 | 30-JAN-05:30 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 9.70 | 0.00 | 01-JAN-00:10 | 13670.00 | 30-JAN-05:30 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 9.70 | 0.00 | 01-JAN-00:10 | 13670.00 | 30-JAN-05:30 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 60.48 | 0.00 | 01-JAN-00:10 | 11536.05 | 04-AUG-15:10 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 60.48 | 0.00 | 01-JAN-00:10 | 11536.05 | 04-AUG-15:10 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 67.92 | 0.00 | 01-JAN-00:10 | 15480.19 | 05-JUL-08:30 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 6.56 | 0.00 | 01-JAN-00:10 | 12641.85 | 02-FEB-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 6.56 | 0.00 | 01-JAN-00:10 | 12641.85 | 02-FEB-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 61.37 | 0.00 | 01-JAN-00:10 | 15480.19 | 05-JUL-08:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 61.37 | 0.00 | 01-JAN-00:10 | 15480.19 | 05-JUL-08:30 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 107.30 | 0.00 | 01-JAN-00:10 | 22700.88 | 07-SEP-13:00 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 8.19 | 0.00 | 01-JAN-00:10 | 18691.60 | 19-JAN-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 8.19 | 0.00 | 01-JAN-00:10 | 18691.60 | 19-JAN-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 99.11 | 0.00 | 01-JAN-00:10 | 22700.88 | 07-SEP-13:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 99.11 | 0.00 | 01-JAN-00:10 | 22700.88 | 07-SEP-13:00 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 96.87 | 0.00 | 01-JAN-00:10 | 20674.88 | 02-AUG-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 2.31 | 0.00 | 01-JAN-00:10 | 10372.55 | 19-JAN-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 2.31 | 0.00 | 01-JAN-00:10 | 10372.55 | 19-JAN-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 94.56 | 0.00 | 01-JAN-00:10 | 20674.88 | 02-AUG-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 94.56 | 0.00 | 01-JAN-00:10 | 20674.88 | 02-AUG-16:00 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 859.57 | 0.00 | 01-JAN-00:40 | 168024.62 | 30-JAN-04:20 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 450.59 | 0.00 | 01-JAN-00:40 | 168024.62 | 30-JAN-04:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 450.59 | 0.00 | 01-JAN-00:40 | 168024.62 | 30-JAN-04:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 408.98 | 0.00 | 01-JAN-00:10 | 107869.15 | 26-JUN-14:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 408.98 | 0.00 | 01-JAN-00:10 | 107869.15 | 26-JUN-14:30 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 772.56 | 0.00 | 01-JAN-00:40 | 204935.51 | 09-DEC-05:10 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 266.52 | 0.00 | 01-JAN-00:40 | 204935.51 | 09-DEC-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 266.52 | 0.00 | 01-JAN-00:40 | 204935.51 | 09-DEC-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 506.05 | 0.00 | 01-JAN-00:20 | 164366.25 | 02-AUG-09:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 506.05 | 0.00 | 01-JAN-00:20 | 164366.25 | 02-AUG-09:00 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 1120.51 | 0.00 | 01-JAN-00:40 | 240414.00 | 19-JAN-04:20 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 284.35 | 0.00 | 01-JAN-00:40 | 240414.00 | 19-JAN-04:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 284.35 | 0.00 | 01-JAN-00:40 | 240414.00 | 19-JAN-04:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 836.15 | 0.00 | 01-JAN-00:20 | 235411.99 | 07-SEP-13:10 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 836.15 | 0.00 | 01-JAN-00:20 | 235411.99 | 07-SEP-13:10 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 783.53 | 0.00 | 01-JAN-00:40 | 214057.54 | 09-DEC-05:10 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 225.89 | 0.00 | 01-JAN-00:40 | 214057.54 | 09-DEC-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 225.89 | 0.00 | 01-JAN-00:40 | 214057.54 | 09-DEC-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 557.64 | 0.00 | 01-JAN-00:20 | 183991.61 | 25-JUN-17:10 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 557.64 | 0.00 | 01-JAN-00:20 | 183991.61 | 25-JUN-17:10 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 114.05 | 0.00 | 01-JAN-00:40 | 22192.87 | 09-DEC-02:10 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 74.77 | 0.00 | 01-JAN-00:40 | 22192.87 | 09-DEC-02:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 74.77 | 0.00 | 01-JAN-00:40 | 22192.87 | 09-DEC-02:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 39.28 | 0.00 | 01-JAN-00:10 | 11885.25 | 26-JUN-14:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 39.28 | 0.00 | 01-JAN-00:10 | 11885.25 | 26-JUN-14:30 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 92.11 | 0.00 | 01-JAN-00:40 | 22258.96 | 19-JAN-04:10 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 44.23 | 0.00 | 01-JAN-00:40 | 22258.96 | 19-JAN-04:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 44.23 | 0.00 | 01-JAN-00:40 | 22258.96 | 19-JAN-04:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 47.89 | 0.00 | 01-JAN-00:20 | 16555.11 | 26-JUN-08:40 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 47.89 | 0.00 | 01-JAN-00:20 | 16555.11 | 26-JUN-08:40 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 129.85 | 0.00 | 01-JAN-00:40 | 27674.35 | 09-DEC-02:10 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 51.91 | 0.00 | 01-JAN-00:40 | 27674.35 | 09-DEC-02:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 51.91 | 0.00 | 01-JAN-00:40 | 27674.35 | 09-DEC-02:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 77.94 | 0.00 | 01-JAN-00:20 | 24836.52 | 07-SEP-13:20 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 77.94 | 0.00 | 01-JAN-00:20 | 24836.52 | 07-SEP-13:20 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 91.25 | 0.00 | 01-JAN-00:40 | 23027.02 | 19-JAN-05:30 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 38.02 | 0.00 | 01-JAN-00:40 | 23027.02 | 19-JAN-05:30 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 38.02 | 0.00 | 01-JAN-00:40 | 23027.02 | 19-JAN-05:30 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 53.23 | 0.00 | 01-JAN-00:20 | 18509.97 | 25-JUN-16:50 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 53.23 | 0.00 | 01-JAN-00:20 | 18509.97 | 25-JUN-16:50 |
EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 61.70 | 0.00 | 01-JAN-00:10 | 9953.19 | 03-JUL-15:10 |
Heating:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 9.35 | 0.00 | 01-JAN-00:10 | 8187.83 | 30-JAN-13:40 |
General:Heating:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 9.35 | 0.00 | 01-JAN-00:10 | 8187.83 | 30-JAN-13:40 |
Cooling:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 52.34 | 0.00 | 01-JAN-00:10 | 9953.19 | 03-JUL-15:10 |
General:Cooling:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 52.34 | 0.00 | 01-JAN-00:10 | 9953.19 | 03-JUL-15:10 |
EnergyTransfer:Zone:MIDFLOOR_PLENUM | 615.03 | 0.00 | 01-JAN-00:40 | 198803.09 | 02-JAN-06:20 |
Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 273.47 | 0.00 | 01-JAN-00:40 | 198803.09 | 02-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 273.47 | 0.00 | 01-JAN-00:40 | 198803.09 | 02-JAN-06:20 |
Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 341.56 | 0.00 | 01-JAN-00:10 | 83275.47 | 04-AUG-15:20 |
General:Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 341.56 | 0.00 | 01-JAN-00:10 | 83275.47 | 04-AUG-15:20 |
EnergyTransfer:Zone:TOPFLOOR_PLENUM | 138.59 | 0.00 | 01-JAN-00:40 | 37476.58 | 30-JAN-05:20 |
Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 87.95 | 0.00 | 01-JAN-00:40 | 37476.58 | 30-JAN-05:20 |
General:Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 87.95 | 0.00 | 01-JAN-00:40 | 37476.58 | 30-JAN-05:20 |
Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 50.64 | 0.00 | 01-JAN-00:10 | 21353.58 | 26-JUN-13:30 |
General:Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 50.64 | 0.00 | 01-JAN-00:10 | 21353.58 | 26-JUN-13:30 |
EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 133.84 | 0.35 | 28-JAN-07:00 | 8539.08 | 16-APR-18:00 |
Heating:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 0.11 | 0.00 | 01-JAN-00:10 | 604.81 | 31-JAN-04:00 |
General:Heating:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 0.11 | 0.00 | 01-JAN-00:10 | 604.81 | 31-JAN-04:00 |
Cooling:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 133.73 | 0.00 | 06-JAN-05:20 | 8539.08 | 16-APR-18:00 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 133.73 | 0.00 | 06-JAN-05:20 | 8539.08 | 16-APR-18:00 |
EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 1124.46 | 1.18 | 09-JAN-09:30 | 81089.96 | 29-AUG-17:40 |
Heating:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 7.63 | 0.00 | 02-JAN-07:50 | 6292.39 | 29-JAN-17:20 |
General:Heating:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 7.63 | 0.00 | 02-JAN-07:50 | 6292.39 | 29-JAN-17:20 |
Cooling:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 1116.83 | 0.00 | 01-JAN-00:10 | 81089.96 | 29-AUG-17:40 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 1116.83 | 0.00 | 01-JAN-00:10 | 81089.96 | 29-AUG-17:40 |
EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 102.89 | 0.25 | 17-JAN-11:10 | 8221.11 | 16-APR-18:00 |
Heating:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 1.04 | 0.00 | 02-JAN-07:40 | 643.00 | 29-JAN-17:20 |
General:Heating:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 1.04 | 0.00 | 02-JAN-07:40 | 643.00 | 29-JAN-17:20 |
Cooling:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 101.84 | 0.00 | 01-JAN-00:10 | 8221.11 | 16-APR-18:00 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 101.84 | 0.00 | 01-JAN-00:10 | 8221.11 | 16-APR-18:00 |
EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 7155.20 | 82667.07 | 30-JAN-05:00 | 381135.77 | 04-AUG-19:00 |
Heating:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 7155.20 | 82667.07 | 30-JAN-05:00 | 381135.77 | 04-AUG-19:00 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 7155.20 | 82667.07 | 30-JAN-05:00 | 381135.77 | 04-AUG-19:00 |
PlantLoopHeatingDemand:Facility | 3499.03 | 0.00 | 01-JAN-00:40 | 2764844.54 | 30-JAN-07:10 |
PlantLoopHeatingDemand:Plant | 469.59 | 0.00 | 01-JAN-00:10 | 58753.98 | 22-FEB-12:30 |
WaterSystems:PlantLoopHeatingDemand | 469.59 | 0.00 | 01-JAN-00:10 | 58753.98 | 22-FEB-12:30 |
General:WaterSystems:PlantLoopHeatingDemand | 469.59 | 0.00 | 01-JAN-00:10 | 58753.98 | 22-FEB-12:30 |
EnergyTransfer:HVAC | 16126.71 | 2018.96 | 18-JAN-01:00 | 3732281.15 | 04-AUG-07:20 |
HeatingCoils:EnergyTransfer | 3029.44 | 0.00 | 01-JAN-00:40 | 2745466.39 | 30-JAN-07:10 |
PlantLoopHeatingDemand:HVAC | 3029.44 | 0.00 | 01-JAN-00:40 | 2745466.39 | 30-JAN-07:10 |
HeatingCoils:PlantLoopHeatingDemand | 3029.44 | 0.00 | 01-JAN-00:40 | 2745466.39 | 30-JAN-07:10 |
CoolingCoils:EnergyTransfer | 8700.26 | 1746.29 | 30-JAN-08:10 | 3732281.15 | 04-AUG-07:20 |
HeatRecoveryForHeating:EnergyTransfer | 4083.94 | 0.00 | 01-JAN-00:10 | 1203801.93 | 05-JAN-18:50 |
HeatRecoveryForCooling:EnergyTransfer | 313.07 | 0.00 | 01-JAN-00:10 | 751931.02 | 04-AUG-13:00 |
EnergyTransfer:Plant | 19806.76 | 0.00 | 01-JAN-00:40 | 9824839.52 | 04-AUG-07:20 |
LoopToLoop:EnergyTransfer | 5178.61 | 0.00 | 01-JAN-00:10 | 3171761.94 | 04-AUG-07:20 |
WaterSystems:EnergyTransfer | 469.59 | 0.00 | 01-JAN-00:10 | 58753.98 | 22-FEB-12:30 |
WaterUse:WaterSystems:EnergyTransfer | 469.59 | 0.00 | 01-JAN-00:10 | 58753.98 | 22-FEB-12:30 |
Boilers:EnergyTransfer | 3002.10 | 0.00 | 01-JAN-00:40 | 2763128.00 | 30-JAN-07:10 |
Chillers:EnergyTransfer | 5185.16 | 0.00 | 01-JAN-00:10 | 3082327.96 | 04-AUG-07:10 |
HeatRejection:EnergyTransfer | 5971.30 | 0.00 | 01-JAN-00:10 | 3561006.01 | 04-AUG-07:10 |
General:HeatRejection:EnergyTransfer | 5971.30 | 0.00 | 01-JAN-00:10 | 3561006.01 | 04-AUG-07:10 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 08:43:43
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
BASEMENT | 0.000 | 0.000 | 2.586 | -683.431 | 0.000 | 0.000 | 93.893 | 262.844 | 424.397 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -100.289 |
CORE_BOTTOM | 0.000 | 0.000 | 0.004 | -601.855 | 0.000 | 0.000 | 83.912 | 236.053 | 289.614 | 0.000 | 0.000 | 0.000 | 0.009 | 0.000 | 0.000 | 0.000 | 0.000 | -7.727 |
CORE_MID | 0.000 | 0.000 | 34.226 | -4281.583 | 0.000 | 0.000 | 866.836 | 2360.527 | 2896.128 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -1876.134 |
CORE_TOP | 0.000 | 0.000 | 29.758 | -370.814 | 0.000 | 0.000 | 89.258 | 236.053 | 289.613 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -273.867 |
PERIMETER_BOT_ZN_3 | 0.000 | 0.000 | 9.701 | -60.484 | 0.000 | 0.000 | 11.166 | 17.490 | 36.365 | 28.960 | 0.000 | 0.082 | 67.676 | 0.000 | -97.594 | 0.000 | -13.363 | 0.000 |
PERIMETER_BOT_ZN_2 | 0.000 | 0.000 | 6.555 | -61.368 | 0.000 | 0.000 | 7.243 | 11.171 | 23.435 | 58.120 | 0.000 | 0.061 | 22.634 | 0.000 | -59.053 | 0.000 | -8.800 | 0.000 |
PERIMETER_BOT_ZN_1 | 0.000 | 0.000 | 8.190 | -99.114 | 0.000 | 0.000 | 10.995 | 17.160 | 36.366 | 120.187 | 0.000 | 0.080 | 5.169 | 0.000 | -85.602 | 0.000 | -13.430 | -0.001 |
PERIMETER_BOT_ZN_4 | 0.000 | 0.000 | 2.310 | -94.565 | 0.000 | 0.000 | 7.080 | 11.131 | 23.435 | 59.580 | 0.000 | 0.051 | 67.122 | 0.000 | -66.608 | 0.000 | -9.536 | 0.000 |
PERIMETER_MID_ZN_3 | 0.000 | 0.000 | 450.586 | -408.977 | 0.000 | 0.000 | 115.923 | 174.482 | 363.654 | 301.818 | 0.000 | 1.983 | 182.893 | 0.000 | -899.146 | 0.000 | -283.216 | -0.003 |
PERIMETER_MID_ZN_2 | 0.000 | 0.000 | 266.516 | -506.046 | 0.000 | 0.000 | 54.764 | 111.527 | 234.352 | 583.681 | 0.000 | 1.345 | 0.863 | 0.000 | -555.590 | 0.000 | -191.412 | -0.002 |
PERIMETER_MID_ZN_1 | 0.000 | 0.000 | 284.353 | -836.147 | 0.000 | 0.000 | 112.227 | 171.400 | 363.660 | 1199.821 | 0.000 | 1.788 | 0.012 | 0.000 | -822.162 | 0.000 | -297.208 | -177.732 |
PERIMETER_MID_ZN_4 | 0.000 | 0.000 | 225.893 | -557.635 | 0.000 | 0.000 | 74.727 | 111.135 | 234.351 | 610.418 | 0.000 | 1.214 | 87.326 | 0.000 | -591.707 | 0.000 | -195.721 | -0.010 |
PERIMETER_TOP_ZN_3 | 0.000 | 0.000 | 74.770 | -39.280 | 0.000 | 0.000 | 11.732 | 17.446 | 36.365 | 30.658 | 0.000 | 0.235 | 0.000 | 0.000 | -86.827 | 0.000 | -34.069 | -11.030 |
PERIMETER_TOP_ZN_2 | 0.000 | 0.000 | 44.225 | -47.885 | 0.000 | 0.000 | 7.486 | 11.152 | 23.435 | 58.646 | 0.000 | 0.153 | 0.000 | 0.000 | -53.810 | 0.000 | -23.122 | -20.280 |
PERIMETER_TOP_ZN_1 | 0.000 | 0.000 | 51.907 | -77.943 | 0.000 | 0.000 | 11.378 | 17.140 | 36.366 | 120.546 | 0.000 | 0.211 | 0.000 | 0.000 | -79.088 | 0.000 | -35.603 | -44.915 |
PERIMETER_TOP_ZN_4 | 0.000 | 0.000 | 38.018 | -53.229 | 0.000 | 0.000 | 7.542 | 11.112 | 23.435 | 61.166 | 0.000 | 0.146 | 0.000 | 0.000 | -57.390 | 0.000 | -23.626 | -7.175 |
DATACENTER_BOT_ZN_6 | 0.000 | 0.000 | 0.109 | -133.727 | 0.000 | 0.000 | 0.950 | 6.628 | 153.881 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -27.841 |
DATACENTER_MID_ZN_6 | 0.000 | 0.000 | 7.628 | -1116.830 | 0.000 | 0.000 | 9.551 | 66.280 | 1538.806 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -505.435 |
DATACENTER_TOP_ZN_6 | 0.000 | 0.000 | 1.045 | -101.844 | 0.000 | 0.000 | 0.960 | 6.628 | 153.881 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -60.669 |
DATACENTER_BASEMENT_ZN_6 | 0.000 | 0.000 | 0.000 | -7155.198 | 0.000 | 0.000 | 20.067 | 74.111 | 7494.857 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -433.838 |
GROUNDFLOOR_PLENUM | 9.354 | -52.342 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.155 | 71.736 | 0.000 | 0.000 | 0.000 | -28.904 | 0.000 |
MIDFLOOR_PLENUM | 273.471 | -341.557 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 3.013 | 548.000 | 0.000 | 0.000 | 0.000 | -482.926 | -0.038 |
TOPFLOOR_PLENUM | 87.947 | -50.643 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.205 | 14.369 | 0.000 | 0.000 | 0.000 | -51.879 | -0.010 |
Total Facility | 370.772 | -444.542 | 1538.380 | -17287.957 | 0.000 | 0.000 | 1597.692 | 3931.469 | 14676.396 | 3233.601 | 0.000 | 10.722 | 1067.810 | 0.000 | -3454.577 | 0.000 | -1692.814 | -3546.995 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | 30-OCT-04:11 | 0.00 | 0.00 | 0.00 | -120117.79 | 0.00 | 0.00 | 0.00 | 2550.13 | 13457.54 | 0.00 | 0.00 | 0.00 | 104110.11 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 11-SEP-04:13 | 0.00 | 0.00 | 0.00 | -101978.62 | 0.00 | 0.00 | 0.00 | 2290.20 | 5937.65 | 0.00 | 0.00 | 0.00 | 93750.78 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 28-JUN-04:12 | 0.00 | 0.00 | 0.00 | -886720.38 | 0.00 | 0.00 | 0.00 | 22901.98 | 59376.23 | 0.00 | 0.00 | 0.00 | 804442.17 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 12-JUN-04:13 | 0.00 | 0.00 | 0.00 | -90329.73 | 0.00 | 0.00 | 0.00 | 2290.20 | 5937.62 | 0.00 | 0.00 | 0.00 | 82101.91 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 25-JUN-18:11 | 0.00 | 0.00 | 0.00 | -18311.80 | 0.00 | 0.00 | 0.00 | 68.40 | 559.17 | 7659.65 | 0.00 | 170.64 | 9853.94 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 25-JUN-08:11 | 0.00 | 0.00 | 0.00 | -28680.55 | 0.00 | 0.00 | 18.36 | 44.08 | 464.11 | 21683.08 | 0.00 | 0.00 | 6638.62 | 0.00 | -0.00 | 0.00 | -167.70 | 0.00 |
PERIMETER_BOT_ZN_1 | 04-SEP-13:11 | 0.00 | 0.00 | 0.00 | -32219.03 | 0.00 | 0.00 | 30.08 | 68.40 | 720.19 | 27302.92 | 0.00 | 0.00 | 4259.30 | 0.00 | -0.00 | 0.00 | -161.87 | 0.00 |
PERIMETER_BOT_ZN_4 | 02-JUL-16:31 | 0.00 | 0.00 | 0.00 | -36521.97 | 0.00 | 0.00 | 12.72 | 44.08 | 464.11 | 21989.45 | 0.00 | 0.00 | 14058.99 | 0.00 | -0.00 | 0.00 | -47.37 | 0.00 |
PERIMETER_MID_ZN_3 | 25-JUN-18:22 | 0.00 | 0.00 | 0.00 | -189061.32 | 0.00 | 0.00 | 0.00 | 684.02 | 5591.71 | 75145.29 | 0.00 | 4534.16 | 103106.14 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 02-JUL-09:11 | 0.00 | 0.00 | 0.00 | -315122.87 | 0.00 | 0.00 | 164.87 | 440.81 | 4641.14 | 189465.04 | 0.00 | 0.00 | 122958.68 | 0.00 | -0.00 | 0.00 | -2547.66 | 0.00 |
PERIMETER_MID_ZN_1 | 17-SEP-13:31 | 0.00 | 0.00 | 0.00 | -330890.46 | 0.00 | 0.00 | 285.52 | 684.04 | 7201.95 | 246642.50 | 0.00 | 0.00 | 81576.09 | 0.00 | -0.00 | 0.00 | -5499.63 | 0.00 |
PERIMETER_MID_ZN_4 | 25-JUN-17:01 | 0.00 | 0.00 | 0.00 | -343350.96 | 0.00 | 0.00 | 0.00 | 440.81 | 3603.49 | 219133.82 | 0.00 | 704.93 | 119467.92 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 11-JUN-15:21 | 0.00 | 0.00 | 0.00 | -22542.52 | 0.00 | 0.00 | 38.68 | 68.40 | 720.18 | 7409.44 | 0.00 | 1121.43 | 13184.38 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 11-JUN-08:61 | 0.00 | 0.00 | 0.00 | -29949.74 | 0.00 | 0.00 | 18.84 | 44.08 | 464.11 | 20322.03 | 0.00 | 0.00 | 9336.93 | 0.00 | -0.00 | 0.00 | -236.25 | 0.00 |
PERIMETER_TOP_ZN_1 | 16-APR-13:41 | 0.00 | 0.00 | 0.00 | -34158.35 | 0.00 | 0.00 | 30.15 | 68.40 | 720.19 | 22898.70 | 0.00 | 0.00 | 10872.60 | 0.00 | -0.00 | 0.00 | -431.69 | 0.00 |
PERIMETER_TOP_ZN_4 | 23-JUL-16:51 | 0.00 | 0.00 | 0.00 | -35065.76 | 0.00 | 0.00 | 15.73 | 44.08 | 464.11 | 20232.09 | 0.00 | 0.00 | 14457.12 | 0.00 | -0.00 | 0.00 | -147.37 | 0.00 |
DATACENTER_BOT_ZN_6 | 16-APR-17:52 | 0.00 | 0.00 | 0.00 | -8539.08 | 0.00 | 0.00 | 0.00 | 32.15 | 7794.42 | 0.00 | 0.00 | 0.00 | 712.51 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 29-AUG-17:40 | 0.00 | 0.00 | 0.00 | -81087.16 | 0.00 | 0.00 | 106.16 | 1929.04 | 77944.22 | 0.00 | 0.00 | 0.00 | 1107.74 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 16-APR-17:52 | 0.00 | 0.00 | 0.00 | -8221.11 | 0.00 | 0.00 | 0.00 | 32.15 | 7794.42 | 0.00 | 0.00 | 0.00 | 394.54 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 04-AUG-17:53 | 0.00 | 0.00 | 0.00 | -389467.94 | 0.00 | 0.00 | 148.40 | 2157.00 | 379632.52 | 0.00 | 0.00 | 0.00 | 7530.01 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 19-JAN-04:01 | 0.00 | -11006.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18402.08 | 0.00 | -0.00 | 0.00 | -7396.01 | 0.00 |
MIDFLOOR_PLENUM | 09-DEC-03:41 | 0.00 | -134355.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 259942.09 | 0.00 | -0.00 | 0.00 | -125586.12 | 0.00 |
TOPFLOOR_PLENUM | 26-JUN-13:30 | 0.00 | -21353.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 207.25 | 21145.89 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 03-JUL-04:12 | 0.00 | 48380.84 | 0.00 | -1891181.53 | 0.00 | 0.00 | 0.00 | 42872.09 | 469008.02 | 0.00 | 0.00 | 0.00 | 1438832.97 | 0.00 | -79615.70 | 0.00 | -28296.70 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | 15-APR-16:01 | 0.00 | 0.00 | 17634.11 | 0.00 | 0.00 | 0.00 | 520.13 | 1274.92 | 13457.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -32886.70 |
CORE_BOTTOM | 06-FEB-06:01 | 0.00 | 0.00 | 16353.96 | 0.00 | 0.00 | 0.00 | 1134.54 | 2290.20 | 7647.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -27426.09 |
CORE_MID | 02-JAN-04:01 | 0.00 | 0.00 | 648370.15 | 0.00 | 0.00 | 0.00 | 0.00 | 11449.71 | 59376.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -719196.09 |
CORE_TOP | 30-JAN-04:11 | 0.00 | 0.00 | 86538.18 | 0.00 | 0.00 | 0.00 | 0.00 | 1144.97 | 5937.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -93620.77 |
PERIMETER_BOT_ZN_3 | 30-JAN-04:01 | 0.00 | 0.00 | 15530.14 | 0.00 | 0.00 | 0.00 | 0.00 | 143.76 | 745.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -9973.26 | 0.00 | -2185.92 | -4260.29 |
PERIMETER_BOT_ZN_2 | 02-FEB-04:01 | 0.00 | 0.00 | 18919.63 | 0.00 | 0.00 | 0.00 | 0.00 | 92.65 | 480.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -7620.99 | 0.00 | -1583.29 | -10288.46 |
PERIMETER_BOT_ZN_1 | 30-JAN-04:01 | 0.00 | 0.00 | 23842.15 | 0.00 | 0.00 | 0.00 | 0.00 | 143.77 | 745.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -9654.05 | 0.00 | -2197.79 | -12879.64 |
PERIMETER_BOT_ZN_4 | 30-JAN-04:01 | 0.00 | 0.00 | 18223.89 | 0.00 | 0.00 | 0.00 | 0.00 | 92.65 | 480.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -6811.32 | 0.00 | -1490.16 | -10495.51 |
PERIMETER_MID_ZN_3 | 19-JAN-04:11 | 0.00 | 0.00 | 181925.29 | 0.00 | 0.00 | 0.00 | 0.00 | 1437.63 | 7455.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -98114.89 | 0.00 | -71835.45 | -20868.19 |
PERIMETER_MID_ZN_2 | 19-JAN-04:11 | 0.00 | 0.00 | 251700.81 | 0.00 | 0.00 | 0.00 | 0.00 | 926.46 | 4804.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -62626.83 | 0.00 | -48574.78 | -146230.33 |
PERIMETER_MID_ZN_1 | 19-JAN-04:11 | 0.00 | 0.00 | 272604.31 | 0.00 | 0.00 | 0.00 | 0.00 | 1437.66 | 7455.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -94344.20 | 0.00 | -72576.94 | -114576.56 |
PERIMETER_MID_ZN_4 | 19-JAN-04:11 | 0.00 | 0.00 | 266387.97 | 0.00 | 0.00 | 0.00 | 0.00 | 926.46 | 4804.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -65694.10 | 0.00 | -48837.52 | -157587.47 |
PERIMETER_TOP_ZN_3 | 09-DEC-02:61 | 0.00 | 0.00 | 24429.83 | 0.00 | 0.00 | 0.00 | 0.00 | 143.76 | 559.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -8662.60 | 0.00 | -11898.39 | -4571.77 |
PERIMETER_TOP_ZN_2 | 09-DEC-02:61 | 0.00 | 0.00 | 27114.51 | 0.00 | 0.00 | 0.00 | 0.00 | 92.65 | 360.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -5533.24 | 0.00 | -8116.90 | -13917.37 |
PERIMETER_TOP_ZN_1 | 09-DEC-02:61 | 0.00 | 0.00 | 31216.55 | 0.00 | 0.00 | 0.00 | 0.00 | 143.77 | 559.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -8332.23 | 0.00 | -12132.78 | -11454.49 |
PERIMETER_TOP_ZN_4 | 09-DEC-02:61 | 0.00 | 0.00 | 29691.55 | 0.00 | 0.00 | 0.00 | 0.00 | 92.65 | 360.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -5882.81 | 0.00 | -8230.80 | -16030.94 |
DATACENTER_BOT_ZN_6 | 29-JAN-20:37 | 0.00 | 0.00 | 605.61 | 0.00 | 0.00 | 0.00 | 0.00 | 32.15 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -2586.36 |
DATACENTER_MID_ZN_6 | 29-JAN-17:57 | 0.00 | 0.00 | 6327.70 | 0.00 | 0.00 | 0.00 | 60.06 | 321.53 | 19486.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -26195.34 |
DATACENTER_TOP_ZN_6 | 28-JAN-19:15 | 0.00 | 0.00 | 649.41 | 0.00 | 0.00 | 0.00 | 0.00 | 32.15 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -2630.17 |
DATACENTER_BASEMENT_ZN_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 05-DEC-05:01 | 14535.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -3971.98 | -10563.35 |
MIDFLOOR_PLENUM | 02-JAN-06:12 | 214650.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -10750.20 | -203900.65 |
TOPFLOOR_PLENUM | 02-FEB-05:12 | 39724.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -7114.07 | -32609.97 |
Total Facility | 02-JAN-06:01 | -42616.07 | 212272.02 | 1636501.53 | -212272.02 | 0.00 | 0.00 | 22700.53 | 42872.09 | 261414.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -203641.52 | 0.00 | -39273.08 | -1677958.44 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 08:43:43
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
VAV_BOT WITH REHEAT | 12.4863 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 10.7065 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_MID WITH REHEAT | 121.3689 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 100.0857 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_TOP WITH REHEAT | 12.5832 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 11.0070 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
CAV_BAS | 6.2391 | 0.0000 | 149.6021 | 1.0000 | Calculated from schedules | 1.2002 | 6.2391 | 0.1924 | 1.0000 | Not calculated | 1.2002 | 0.1924 | ||
AIRLOOP DATACENTER BASEMENT | 22.4388 | 0.0000 | 42.1814 | 1.0000 | Calculated from schedules | 0.3384 | 22.4389 | 0.0151 | 1.0000 | Not calculated | 0.3384 | 0.0151 | ||
AIRLOOP DATACENTER BOT | 0.5326 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.5326 | 0.0294 | 1.0000 | Not calculated | 0.0156 | 0.0294 | ||
AIRLOOP DATACENTER MID | 5.1172 | 0.0000 | 19.4861 | 1.0000 | Calculated from schedules | 0.1563 | 5.1172 | 0.0305 | 1.0000 | Not calculated | 0.1563 | 0.0305 | ||
AIRLOOP DATACENTER TOP | 0.5201 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.5201 | 0.0301 | 1.0000 | Not calculated | 0.0156 | 0.0301 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
VAV_BOT WITH REHEAT | 6.2432 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 3.2275 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_MID WITH REHEAT | 60.6845 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 32.0464 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_TOP WITH REHEAT | 6.2916 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 3.3304 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
CAV_BAS | 6.2391 | 0.0000 | 149.6021 | 1.0000 | Calculated from schedules | 1.2002 | 6.2391 | 1.0000 | 1.0000 | Not calculated | 1.2002 | 0.1924 | ||
AIRLOOP DATACENTER BASEMENT | 22.4388 | 0.0000 | 42.1814 | 1.0000 | Calculated from schedules | 0.3384 | 22.4388 | 1.0000 | 1.0000 | Not calculated | 0.3384 | 0.0151 | ||
AIRLOOP DATACENTER BOT | 0.5326 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.5326 | 1.0000 | 1.0000 | Not calculated | 0.0156 | 0.0294 | ||
AIRLOOP DATACENTER MID | 5.1172 | 0.0000 | 19.4861 | 1.0000 | Calculated from schedules | 0.1563 | 5.1172 | 1.0000 | 1.0000 | Not calculated | 0.1563 | 0.0305 | ||
AIRLOOP DATACENTER TOP | 0.5201 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.5201 | 1.0000 | 1.0000 | Not calculated | 0.0156 | 0.0301 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
BASEMENT | CAV_BAS | 0.000000 | 149.6021 | 0.000432 | 2779.43 | 1.2002 | 1.0000 | 1.2002 | 1.000 | 1.2002 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | 0.000000 | 134.3532 | 0.000432 | 2496.12 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_MID | VAV_MID WITH REHEAT | 0.000000 | 1343.5320 | 0.000432 | 24961.20 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_TOP | VAV_TOP WITH REHEAT | 0.000000 | 134.3532 | 0.000432 | 2496.12 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | 0.000000 | 16.8694 | 0.000432 | 313.41 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | 0.000000 | 16.8698 | 0.000432 | 313.42 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | 0.000000 | 168.6939 | 0.000432 | 3134.13 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | 0.000000 | 108.7127 | 0.000432 | 2019.75 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | 0.000000 | 168.6975 | 0.000432 | 3134.20 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | 0.000000 | 108.7127 | 0.000432 | 2019.75 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | 0.000000 | 16.8694 | 0.000432 | 313.41 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | 0.000000 | 16.8698 | 0.000432 | 313.42 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | 0.000000 | 1.9486 | 0.000432 | 36.20 | 0.0156 | 1.0000 | 0.0156 | 1.000 | 0.0156 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | 0.000000 | 19.4861 | 0.000432 | 362.03 | 0.1563 | 1.0000 | 0.1563 | 1.000 | 0.1563 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | 0.000000 | 1.9486 | 0.000432 | 36.20 | 0.0156 | 1.0000 | 0.0156 | 1.000 | 0.0156 |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | 0.000000 | 42.1814 | 0.000432 | 783.68 | 0.3384 | 1.0000 | 0.3384 | 1.000 | 0.3384 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
VAV_BOT WITH REHEAT | 0.00 | 0.000432 | 3526.9033 | 0.0000 | 0.0000 | 0.0000 | |
VAV_MID WITH REHEAT | 0.00 | 0.000432 | 35269.0328 | 0.0000 | 0.0000 | 0.0000 | |
VAV_TOP WITH REHEAT | 0.00 | 0.000432 | 3526.9033 | 0.0000 | 0.0000 | 0.0000 | |
CAV_BAS | 0.000000 | 149.60 | 0.000432 | 2779.4266 | 1.2002 | 1.2002 | 1.2002 |
AIRLOOP DATACENTER BASEMENT | 0.000000 | 42.18 | 0.000432 | 783.6794 | 0.3384 | 0.3384 | 0.3384 |
AIRLOOP DATACENTER BOT | 0.000000 | 1.95 | 0.000432 | 36.2027 | 0.0156 | 0.0156 | 0.0156 |
AIRLOOP DATACENTER MID | 0.000000 | 19.49 | 0.000432 | 362.0274 | 0.1563 | 0.1563 | 0.1563 |
AIRLOOP DATACENTER TOP | 0.000000 | 1.95 | 0.000432 | 36.2027 | 0.0156 | 0.0156 | 0.0156 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | CAV_BAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 6.2391 | 6.2391 | 6.2391 | No | 1.2002 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 6.4606 | 6.4606 | 1.9899 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 60.8311 | 60.8311 | 19.5268 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 6.0424 | 6.0424 | 2.0000 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.0834 | 1.0834 | 0.2492 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.4802 | 1.4802 | 0.2960 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.6777 | 1.6777 | 0.3355 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.7844 | 1.7844 | 0.3569 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 11.1363 | 11.1363 | 2.6393 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 15.7304 | 15.7304 | 3.1461 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 16.9242 | 16.9242 | 3.3848 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 16.7469 | 16.7469 | 3.3494 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.3885 | 1.3885 | 0.2999 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.5816 | 1.5816 | 0.3163 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.8135 | 1.8135 | 0.3627 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.7573 | 1.7573 | 0.3515 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.5326 | 0.5326 | 0.5326 | No | 0.0156 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 5.1172 | 5.1172 | 5.1172 | No | 0.1563 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.5201 | 0.5201 | 0.5201 | No | 0.0156 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 22.4388 | 22.4388 | 22.4388 | No | 0.3384 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
VAV_BOT WITH REHEAT | 12.4863 | 10.7065 | 12.4863 | 3.2275 | 0.0000 | 1.0000 |
VAV_MID WITH REHEAT | 121.3689 | 100.0857 | 121.3689 | 32.0464 | 0.0000 | 1.0000 |
VAV_TOP WITH REHEAT | 12.5832 | 11.0070 | 12.5832 | 3.3304 | 0.0000 | 1.0000 |
CAV_BAS | 6.2391 | 6.2391 | 6.2391 | 6.2391 | 1.2002 | 1.0000 |
AIRLOOP DATACENTER BASEMENT | 22.4388 | 22.4389 | 22.4388 | 22.4388 | 0.3384 | 1.0000 |
AIRLOOP DATACENTER BOT | 0.5326 | 0.5326 | 0.5326 | 0.5326 | 0.0156 | 1.0000 |
AIRLOOP DATACENTER MID | 5.1172 | 5.1172 | 5.1172 | 5.1172 | 0.1563 | 1.0000 |
AIRLOOP DATACENTER TOP | 0.5201 | 0.5201 | 0.5201 | 0.5201 | 0.0156 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | CAV_BAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 6.2391 | 6.2391 | 6.2391 | No | 1.2002 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 3.2303 | 3.2303 | 1.9899 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 30.4156 | 30.4156 | 19.5268 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 3.0212 | 3.0212 | 2.0000 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5417 | 0.5417 | 0.2492 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7401 | 0.7401 | 0.2960 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8389 | 0.8389 | 0.3355 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8922 | 0.8922 | 0.3569 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 5.5682 | 5.5682 | 2.6393 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 7.8652 | 7.8652 | 3.1461 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 8.4621 | 8.4621 | 3.3848 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 8.3734 | 8.3734 | 3.3494 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6943 | 0.6943 | 0.2999 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7908 | 0.7908 | 0.3163 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.9067 | 0.9067 | 0.3627 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8787 | 0.8787 | 0.3515 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.5326 | 0.5326 | 0.5326 | No | 0.0156 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 5.1172 | 5.1172 | 5.1172 | No | 0.1563 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.5201 | 0.5201 | 0.5201 | No | 0.0156 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 22.4388 | 22.4388 | 22.4388 | No | 0.3384 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
VAV_BOT WITH REHEAT | 6.2432 | 3.2275 | 3.2275 | 3.2275 | 0.0000 | 1.0000 |
VAV_MID WITH REHEAT | 60.6845 | 32.0464 | 32.0464 | 32.0464 | 0.0000 | 1.0000 |
VAV_TOP WITH REHEAT | 6.2916 | 3.3304 | 3.3304 | 3.3304 | 0.0000 | 1.0000 |
CAV_BAS | 6.2391 | 6.2391 | 6.2391 | 6.2391 | 1.2002 | 1.0000 |
AIRLOOP DATACENTER BASEMENT | 22.4388 | 22.4388 | 22.4388 | 22.4388 | 0.3384 | 1.0000 |
AIRLOOP DATACENTER BOT | 0.5326 | 0.5326 | 0.5326 | 0.5326 | 0.0156 | 1.0000 |
AIRLOOP DATACENTER MID | 5.1172 | 5.1172 | 5.1172 | 5.1172 | 0.1563 | 1.0000 |
AIRLOOP DATACENTER TOP | 0.5201 | 0.5201 | 0.5201 | 0.5201 | 0.0156 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 08:43:43
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Rochester International Arpt MN USA TMY3 WMO#=726440 |
Total gross floor area [m2] | 46320.38 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
BASEMENT | 2779.43 | 2779.43 | 0.00 | 113.98 |
CORE_BOTTOM | 2496.12 | 2496.12 | 0.00 | 113.98 |
CORE_MID | 2496.12 | 2496.12 | 0.00 | 113.98 |
CORE_TOP | 2496.12 | 2496.12 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_3 | 313.41 | 313.41 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_2 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_1 | 313.42 | 313.42 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_4 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_MID_ZN_3 | 313.41 | 313.41 | 0.00 | 113.98 |
PERIMETER_MID_ZN_2 | 201.98 | 201.98 | 0.00 | 96.54 |
PERIMETER_MID_ZN_1 | 313.42 | 313.42 | 0.00 | 113.98 |
PERIMETER_MID_ZN_4 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_3 | 313.41 | 313.41 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_2 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_1 | 313.42 | 313.42 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_4 | 201.98 | 201.98 | 0.00 | 113.98 |
DATACENTER_BOT_ZN_6 | 36.20 | 36.20 | 0.00 | 113.98 |
DATACENTER_MID_ZN_6 | 36.20 | 36.20 | 0.00 | 113.98 |
DATACENTER_TOP_ZN_6 | 36.20 | 36.20 | 0.00 | 113.98 |
DATACENTER_BASEMENT_ZN_6 | 783.68 | 783.68 | 0.00 | 113.98 |
GROUNDFLOOR_PLENUM | 3563.11 | 3563.11 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 3563.11 | 3563.11 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 3563.11 | 3563.11 | 0.00 | 0.00 |
Totals | 46320.38 | 46320.38 | 0.00 |
Data | |
Number of hours heating loads not met | 182.50 |
Number of hours cooling loads not met | 469.83 |
Number of hours not met | 651.67 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler | 0.00 | 0.00 | 3954.87 | 3355734.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 1808.25 | 638501.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 3931.47 | 385834.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 697.49 | 57580.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 5334.97 | 305206.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- DataCenterPlugLoads | 9341.42 | 473165.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Transformer | 80.18 | 5057.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLift | 1848.78 | 113101.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLightsFan | 5.83 | 376.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 2486.89 | 307984.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 402.91 | 65178.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- General | 584.47 | 93806.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- General | 1498.95 | 100000.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- General | 52.05 | 5613.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 0.00 | 0.00 | 856.26 | 88693.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 14676.40 | 28073.68 |
Natural Gas | 0.00 | 4811.13 |
Additional | 0.00 | 0.00 |
Total | 14676.40 | 32884.81 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 84.88 |
Space Heating | 0.00 |
Space Cooling | 39.04 |
Fans (All) | 53.69 |
Service Water Heating | 0.00 |
Receptacle Equipment | 316.85 |
Miscellaneous (All) | 606.08 |
Subtotal | 606.08 |
Natural Gas [MJ/m2] | |
Space Heating | 85.38 |
Service Water Heating | 18.49 |
Miscellaneous (All) | 103.87 |
Subtotal | 103.87 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 11.96 |
Space Heating | 12.03 |
Space Cooling | 5.50 |
Fans (All) | 7.56 |
Service Water Heating | 2.60 |
Receptacle Equipment | 44.63 |
Miscellaneous | 15.72 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 4472. | 4472. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 6752. | 8760. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 6828. | 8760. |
ALWAYS_OFF | 0. | 0. |
LTG_SCH_OFFICE | 2625. | 8760. |
LTG_SCH_DATACENTER | 2921. | 8760. |
EXTERIOR_LIGHT_SCH | 4380. | 4380. |
BLDG_EQUIP_SCH | 4049. | 8760. |
DATACENTER_EQUIP_SCH | 5478. | 8760. |
BLDG_OCC_SCH | 2528. | 5992. |
BLDG_OCC_SCH_W_SB | 1878. | 5056. |
BLDG_OCC_SCH_WO_SB | 2557. | 5992. |
BLDG_ELEVATORS | 2270. | 8760. |
ELEV_LIGHT_FAN_SCH_24_7 | 8760. | 8760. |
ELEV_LIGHT_FAN_SCH_ADD_DF | 2154. | 8760. |
BLDG_SWH_SCH | 1474. | 6570. |
WORK_EFF_SCH | 0. | 0. |
INFIL_SCH | 3976. | 3976. |
INFIL_SCH_PNNL | 5172. | 8760. |
INFIL_HALF_ON_SCH | 6368. | 8760. |
FAN_SCH | 8760. | 8760. |
REHEATCOILAVAILSCHED | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
MINOA_MOTORIZEDDAMPER_SCHED | 4472. | 4472. |
MINOA_SCHED | 8760. | 8760. |
CORE_BOTTOM SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_BOTTOM SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_MID SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_MID SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_TOP SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_TOP SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
SUPPLYFANSCH | 8760. | 8760. |
PERIMETER_MID_ZN_2_MDP_SCH | 1565. | 7824. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
HTGSETP_DC_SCH | DATACENTER COOLING SETPOINTS DUAL SP CONTROL | January | 18.00 | 365 | 18.00 | 365 |
CLGSETP_DC_SCH | DATACENTER COOLING SETPOINTS DUAL SP CONTROL | July | 27.00 | 365 | 27.00 | 365 |
HTGSETP_SCH_YES_OPTIMUM | CORE_BOTTOM DUAL SP CONTROL | January | 21.00 | 365 | 15.60 | 365 |
CLGSETP_SCH_YES_OPTIMUM | CORE_BOTTOM DUAL SP CONTROL | July | 24.00 | 365 | 26.70 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:43:43
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
BASEMENT | 8275.33 | 484.67 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 8741.67 | 18.33 | 0.00 | 0.00 | 0.00 |
CORE_MID | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 8733.67 | 26.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 8697.33 | 62.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 8679.67 | 80.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 8288.50 | 471.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 8746.00 | 14.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 8679.83 | 80.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 8672.83 | 87.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 8586.50 | 173.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 8740.50 | 19.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 8677.67 | 82.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 8679.50 | 80.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 8599.00 | 161.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 8024.83 | 735.17 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 7997.17 | 762.83 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 7984.33 | 775.67 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 6339.67 | 2341.83 | 72.67 | 5.83 | 0.00 |
GROUNDFLOOR_PLENUM | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 8695.00 | 65.00 | 0.00 | 0.00 | 0.00 |
Min | 6339.67 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 2341.83 | 72.67 | 5.83 | 0.00 |
Average | 8473.00 | 283.59 | 3.16 | 0.25 | 0.00 |
Sum | 194879.00 | 6522.50 | 72.67 | 5.83 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
BASEMENT | 367249.83 | 1366.17 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 330812.00 | 1.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 330813.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 330813.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 18354.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 1817.17 | 450.83 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 1802.50 | 465.50 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 1792.83 | 475.17 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 73297.67 | 28424.33 | 1470.67 | 202.33 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 367249.83 | 28424.33 | 1470.67 | 202.33 | 0.00 |
Average | 78906.39 | 1355.78 | 63.94 | 8.80 | 0.00 |
Sum | 1814847.00 | 31183.00 | 1470.67 | 202.33 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
BASEMENT | 7489.67 | 1270.33 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 8074.33 | 685.67 | 0.00 | 0.00 | 0.00 |
CORE_MID | 8142.33 | 617.67 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 8200.50 | 559.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 8171.83 | 588.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 8423.33 | 336.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 8242.83 | 517.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 7799.67 | 960.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 8222.67 | 537.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 8233.83 | 526.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 8181.50 | 578.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 8055.50 | 704.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 8282.00 | 478.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 8253.33 | 506.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 8220.33 | 539.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 8115.33 | 644.67 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 8435.00 | 325.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 8418.17 | 341.83 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 8412.17 | 347.83 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 6604.17 | 2129.00 | 23.00 | 3.83 | 0.00 |
GROUNDFLOOR_PLENUM | 7956.50 | 803.50 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 8094.67 | 665.33 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 7852.00 | 908.00 | 0.00 | 0.00 | 0.00 |
Min | 6604.17 | 325.00 | 0.00 | 0.00 | 0.00 |
Max | 8435.00 | 2129.00 | 23.00 | 3.83 | 0.00 |
Average | 8081.81 | 677.02 | 1.00 | 0.17 | 0.00 |
Sum | 185881.67 | 15571.50 | 23.00 | 3.83 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
BASEMENT | 360963.00 | 7653.00 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 329754.00 | 1059.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 330011.00 | 802.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 330059.00 | 754.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 38920.00 | 5.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 18353.00 | 1.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 38922.67 | 2.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 24908.50 | 0.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 38920.17 | 4.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 24907.67 | 1.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 38922.83 | 2.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 24908.50 | 0.50 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 2034.67 | 233.33 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 2022.83 | 245.17 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 2016.17 | 251.83 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 76301.00 | 26328.00 | 633.00 | 133.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 360963.00 | 26328.00 | 633.00 | 133.00 | 0.00 |
Average | 78677.96 | 1623.65 | 27.52 | 5.78 | 0.00 |
Sum | 1809593.00 | 37344.00 | 633.00 | 133.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:43:43
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:43:43
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 0.00 | 8760.00 | 0.00 |
Average | 0.00 | 0.00 | 4570.43 | 0.00 |
Sum | 0.00 | 0.00 | 105120.00 | 0.00 |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 18354.00 | 0.00 |
PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 24909.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 0.00 | 38925.00 | 0.00 |
Average | 0.00 | 0.00 | 16367.35 | 0.00 |
Sum | 0.00 | 0.00 | 376449.00 | 0.00 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -12.56 |
February | -7.67 |
March | 0.331 |
April | 7.021 |
May | 14.194 |
June | 19.161 |
July | 20.915 |
August | 20.049 |
September | 15.390 |
October | 7.428 |
November | -0.02 |
December | -7.58 |
Annual Sum or Average | 6.460 |
Minimum of Months | -12.56 |
Maximum of Months | 20.915 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Environment
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -12.56 |
February | -7.67 |
March | 0.331 |
April | 7.021 |
May | 14.194 |
June | 19.161 |
July | 20.915 |
August | 20.049 |
September | 15.390 |
October | 7.428 |
November | -0.02 |
December | -7.58 |
Annual Sum or Average | 6.460 |
Minimum of Months | -12.56 |
Maximum of Months | 20.915 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2013
For: Environment
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -12.56 |
February | -7.67 |
March | 0.331 |
April | 7.021 |
May | 14.194 |
June | 19.161 |
July | 20.915 |
August | 20.049 |
September | 15.390 |
October | 7.428 |
November | -0.02 |
December | -7.58 |
Annual Sum or Average | 6.460 |
Minimum of Months | -12.56 |
Maximum of Months | 20.915 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -12.56 |
February | -7.67 |
March | 0.331 |
April | 7.021 |
May | 14.194 |
June | 19.161 |
July | 20.915 |
August | 20.049 |
September | 15.390 |
October | 7.428 |
November | -0.02 |
December | -7.58 |
Annual Sum or Average | 6.460 |
Minimum of Months | -12.56 |
Maximum of Months | 20.915 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICELARGE
For: Environment
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -12.56 |
February | -7.67 |
March | 0.331 |
April | 7.021 |
May | 14.194 |
June | 19.161 |
July | 20.915 |
August | 20.049 |
September | 15.390 |
October | 7.428 |
November | -0.02 |
December | -7.58 |
Annual Sum or Average | 6.460 |
Minimum of Months | -12.56 |
Maximum of Months | 20.915 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -12.56 |
February | -7.67 |
March | 0.331 |
April | 7.021 |
May | 14.194 |
June | 19.161 |
July | 20.915 |
August | 20.049 |
September | 15.390 |
October | 7.428 |
November | -0.02 |
December | -7.58 |
Annual Sum or Average | 6.460 |
Minimum of Months | -12.56 |
Maximum of Months | 20.915 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -12.56 |
February | -7.67 |
March | 0.331 |
April | 7.021 |
May | 14.194 |
June | 19.161 |
July | 20.915 |
August | 20.049 |
September | 15.390 |
October | 7.428 |
November | -0.02 |
December | -7.58 |
Annual Sum or Average | 6.460 |
Minimum of Months | -12.56 |
Maximum of Months | 20.915 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 6A
For: Environment
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -12.56 |
February | -7.67 |
March | 0.331 |
April | 7.021 |
May | 14.194 |
June | 19.161 |
July | 20.915 |
August | 20.049 |
September | 15.390 |
October | 7.428 |
November | -0.02 |
December | -7.58 |
Annual Sum or Average | 6.460 |
Minimum of Months | -12.56 |
Maximum of Months | 20.915 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_MN_ROCHESTER
For: Environment
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -12.56 |
February | -7.67 |
March | 0.331 |
April | 7.021 |
May | 14.194 |
June | 19.161 |
July | 20.915 |
August | 20.049 |
September | 15.390 |
October | 7.428 |
November | -0.02 |
December | -7.58 |
Annual Sum or Average | 6.460 |
Minimum of Months | -12.56 |
Maximum of Months | 20.915 |
Report: ZoneCoolingSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.510011E+11 | 110847.12 | 02-JAN-05:01 | -4.5 | -5.4 | 0.498024E+10 | 7499.21 | 12-JAN-14:30 | 2.50 | 0.82 |
February | 0.422052E+11 | 111715.39 | 27-FEB-05:01 | -2.3 | -2.5 | 0.482059E+10 | 7499.21 | 08-FEB-10:20 | -2.3 | -2.5 |
March | 0.529484E+11 | 118206.48 | 27-MAR-03:51 | 1.70 | 0.37 | 0.611637E+10 | 7499.23 | 16-MAR-13:20 | 1.70 | 0.37 |
April | 0.523210E+11 | 117134.11 | 10-APR-04:11 | 6.70 | 4.36 | 0.544439E+10 | 7499.36 | 13-APR-09:09 | 11.97 | 9.98 |
May | 0.577953E+11 | 117109.78 | 01-MAY-04:12 | 5.93 | 3.78 | 0.589982E+10 | 7499.18 | 05-MAY-09:20 | 18.50 | 14.75 |
June | 0.626134E+11 | 119047.89 | 19-JUN-04:12 | 12.03 | 10.64 | 0.588220E+10 | 7499.06 | 09-JUN-09:39 | 12.03 | 10.64 |
July | 0.639311E+11 | 118169.23 | 24-JUL-04:12 | 10.00 | 9.40 | 0.547441E+10 | 7499.16 | 21-JUL-09:20 | 10.00 | 9.40 |
August | 0.720949E+11 | 119789.80 | 06-AUG-15:00 | 19.40 | 12.05 | 0.613846E+10 | 7499.54 | 08-AUG-09:20 | 20.57 | 15.69 |
September | 0.620591E+11 | 119631.48 | 04-SEP-08:29 | 14.70 | 12.46 | 0.545315E+10 | 7499.06 | 06-SEP-09:00 | 25.60 | 18.61 |
October | 0.602287E+11 | 120117.77 | 30-OCT-04:11 | 9.73 | 5.50 | 0.566837E+10 | 7499.08 | 17-OCT-09:20 | 9.73 | 5.50 |
November | 0.550452E+11 | 119543.22 | 06-NOV-05:11 | 10.60 | 9.72 | 0.558583E+10 | 7499.23 | 20-NOV-10:09 | 13.15 | 11.78 |
December | 0.511890E+11 | 117527.69 | 04-DEC-04:01 | -8.5 | -8.8 | 0.532999E+10 | 7499.16 | 14-DEC-10:09 | -1.7 | -2.3 |
Annual Sum or Average | 0.683432E+12 | 0.667938E+11 | ||||||||
Minimum of Months | 0.422052E+11 | 110847.12 | -8.5 | -8.8 | 0.482059E+10 | 7499.06 | -2.3 | -2.5 | ||
Maximum of Months | 0.720949E+11 | 120117.77 | 19.40 | 12.46 | 0.613846E+10 | 7499.54 | 25.60 | 18.61 |
Report: ZoneCoolingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.294352E+11 | 80459.41 | 14-JAN-06:01 | -3.4 | -4.1 | 0.484055E+10 | 6816.41 | 13-JAN-10:00 | -3.4 | -4.1 |
February | 0.324861E+11 | 87368.66 | 25-FEB-06:01 | 0.00 | -0.6 | 0.441271E+10 | 6891.04 | 17-FEB-14:39 | 0.00 | -0.6 |
March | 0.460266E+11 | 93506.02 | 27-MAR-03:51 | 1.70 | 0.37 | 0.548838E+10 | 6947.20 | 13-MAR-09:00 | 1.70 | 0.37 |
April | 0.525852E+11 | 96859.26 | 19-APR-04:12 | 6.67 | 5.57 | 0.487858E+10 | 6928.97 | 03-APR-13:30 | 6.67 | 5.57 |
May | 0.544006E+11 | 99110.54 | 30-MAY-04:12 | 14.40 | 14.40 | 0.528354E+10 | 6734.90 | 05-MAY-09:09 | 14.40 | 14.40 |
June | 0.617445E+11 | 97663.60 | 19-JUN-04:12 | 12.03 | 10.64 | 0.527012E+10 | 6734.85 | 01-JUN-09:00 | 12.03 | 10.64 |
July | 0.679452E+11 | 98355.68 | 10-JUL-04:13 | 17.20 | 16.88 | 0.489526E+10 | 6734.73 | 18-JUL-09:00 | 22.20 | 15.19 |
August | 0.753349E+11 | 99567.91 | 07-AUG-04:12 | 8.50 | 7.60 | 0.549690E+10 | 6735.21 | 08-AUG-09:09 | 20.28 | 15.58 |
September | 0.529704E+11 | 102001.89 | 11-SEP-04:13 | 20.40 | 17.35 | 0.488145E+10 | 6734.72 | 25-SEP-09:09 | 8.07 | 5.03 |
October | 0.484205E+11 | 95787.71 | 10-OCT-04:11 | 11.43 | 10.68 | 0.507548E+10 | 6736.32 | 13-OCT-09:30 | 4.05 | 2.13 |
November | 0.427794E+11 | 95961.10 | 06-NOV-05:11 | 10.60 | 9.72 | 0.501295E+10 | 6853.79 | 21-NOV-10:00 | -7.8 | -9.3 |
December | 0.377275E+11 | 86729.23 | 05-DEC-06:02 | -3.8 | -5.4 | 0.486081E+10 | 6918.34 | 05-DEC-10:09 | -5.9 | -8.1 |
Annual Sum or Average | 0.601856E+12 | 0.603967E+11 | ||||||||
Minimum of Months | 0.294352E+11 | 80459.41 | -3.8 | -5.4 | 0.441271E+10 | 6734.72 | -7.8 | -9.3 | ||
Maximum of Months | 0.753349E+11 | 102001.89 | 20.40 | 17.35 | 0.549690E+10 | 6947.20 | 22.20 | 15.58 |
Report: ZoneCoolingSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.230655E+11 | 30404.80 | 13-JAN-14:45 | 3.90 | 1.72 | 0.416450E+10 | 6631.58 | 13-JAN-14:39 | 3.90 | 1.72 |
February | 0.226068E+11 | 27458.69 | 10-FEB-16:40 | 0.00 | -1.2 | 0.395941E+10 | 6734.64 | 10-FEB-14:39 | 0.00 | -1.2 |
March | 0.298278E+11 | 76722.13 | 21-MAR-11:00 | -2.8 | -5.2 | 0.514611E+10 | 6840.90 | 30-MAR-09:09 | 1.10 | 0.61 |
April | 0.334693E+11 | 84248.69 | 17-APR-05:02 | 11.42 | 9.68 | 0.474832E+10 | 7051.62 | 27-APR-13:50 | 1.02 | 0.57 |
May | 0.433067E+11 | 85831.27 | 31-MAY-04:12 | 16.50 | 15.12 | 0.526031E+10 | 6734.87 | 05-MAY-09:09 | 16.50 | 15.12 |
June | 0.489268E+11 | 88688.62 | 28-JUN-04:12 | 17.60 | 16.08 | 0.526110E+10 | 6734.81 | 01-JUN-09:00 | 17.60 | 16.08 |
July | 0.498905E+11 | 87748.46 | 10-JUL-04:12 | 17.20 | 16.88 | 0.489113E+10 | 6734.69 | 18-JUL-09:00 | 22.20 | 15.19 |
August | 0.516887E+11 | 87575.00 | 02-AUG-04:12 | 16.83 | 16.24 | 0.549356E+10 | 6735.14 | 08-AUG-09:09 | 20.28 | 15.58 |
September | 0.422598E+11 | 87092.06 | 12-SEP-04:12 | 16.83 | 16.52 | 0.485784E+10 | 6734.73 | 29-SEP-09:09 | 8.77 | 4.97 |
October | 0.320332E+11 | 77588.77 | 04-OCT-05:02 | 7.97 | 6.70 | 0.498350E+10 | 6842.32 | 27-OCT-09:30 | 5.35 | 2.50 |
November | 0.271053E+11 | 74788.47 | 04-NOV-05:02 | 1.10 | -0.6 | 0.463171E+10 | 7067.72 | 10-NOV-14:09 | -0.4 | -1.7 |
December | 0.239794E+11 | 80368.12 | 01-DEC-17:57 | -4.4 | -5.6 | 0.422734E+10 | 6734.66 | 07-DEC-14:50 | -3.3 | -7.2 |
Annual Sum or Average | 0.428160E+12 | 0.576248E+11 | ||||||||
Minimum of Months | 0.226068E+11 | 27458.69 | -4.4 | -5.6 | 0.395941E+10 | 6631.58 | -3.3 | -7.2 | ||
Maximum of Months | 0.516887E+11 | 88688.62 | 17.60 | 16.88 | 0.549356E+10 | 7067.72 | 22.20 | 16.08 |
Report: ZoneCoolingSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.133676E+11 | 18665.30 | 13-JAN-17:00 | 2.20 | 0.77 | 0.389288E+10 | 6346.31 | 13-JAN-14:00 | 2.20 | 0.77 |
February | 0.157536E+11 | 20870.37 | 02-FEB-16:40 | -29.2 | -29.5 | 0.366694E+10 | 6472.15 | 08-FEB-14:00 | 2.20 | 0.97 |
March | 0.228957E+11 | 33393.37 | 24-MAR-16:00 | 10.60 | 5.50 | 0.473845E+10 | 6734.50 | 28-MAR-13:50 | 16.52 | 10.22 |
April | 0.285577E+11 | 83111.07 | 17-APR-05:02 | 11.42 | 9.68 | 0.450407E+10 | 6734.79 | 25-APR-13:00 | 6.70 | 2.10 |
May | 0.405581E+11 | 84346.47 | 30-MAY-04:12 | 14.40 | 14.40 | 0.519274E+10 | 6734.85 | 05-MAY-09:09 | 14.40 | 14.40 |
June | 0.490791E+11 | 90354.15 | 12-JUN-04:13 | 18.13 | 17.48 | 0.523493E+10 | 6742.13 | 02-JUN-09:00 | 18.13 | 17.48 |
July | 0.508929E+11 | 88291.20 | 26-JUL-04:12 | 22.20 | 19.58 | 0.488345E+10 | 6734.68 | 19-JUL-09:09 | 22.20 | 19.58 |
August | 0.513514E+11 | 86888.00 | 28-AUG-04:12 | 18.30 | 17.97 | 0.548001E+10 | 6735.09 | 08-AUG-09:09 | 18.30 | 17.97 |
September | 0.375560E+11 | 87532.89 | 11-SEP-04:12 | 20.40 | 17.35 | 0.476063E+10 | 6734.74 | 06-SEP-09:39 | 20.40 | 17.35 |
October | 0.247309E+11 | 35534.68 | 20-OCT-16:00 | 21.30 | 12.72 | 0.462051E+10 | 6734.61 | 18-OCT-13:00 | 21.30 | 12.72 |
November | 0.202281E+11 | 34224.39 | 03-NOV-16:00 | 15.00 | 9.33 | 0.424778E+10 | 6734.53 | 02-NOV-13:00 | 15.00 | 9.33 |
December | 0.158456E+11 | 18167.13 | 01-DEC-16:40 | -3.2 | -5.0 | 0.382849E+10 | 6248.01 | 01-DEC-14:00 | -3.2 | -5.0 |
Annual Sum or Average | 0.370817E+12 | 0.550509E+11 | ||||||||
Minimum of Months | 0.133676E+11 | 18167.13 | -29.2 | -29.5 | 0.366694E+10 | 6248.01 | -3.2 | -5.0 | ||
Maximum of Months | 0.513514E+11 | 90354.15 | 22.20 | 19.58 | 0.548001E+10 | 6742.13 | 22.20 | 19.58 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.340788E+09 | 2216.43 | 13-JAN-11:50 | 3.62 | 1.34 | 0.470095E+09 | 746.67 | 13-JAN-14:30 | 3.90 | 1.72 |
February | 0.114185E+10 | 2664.03 | 24-FEB-13:30 | 7.25 | 4.63 | 0.449964E+09 | 793.49 | 24-FEB-14:00 | 8.30 | 5.62 |
March | 0.279781E+10 | 5014.29 | 28-MAR-14:30 | 16.95 | 10.50 | 0.603870E+09 | 845.62 | 28-MAR-13:09 | 16.95 | 10.50 |
April | 0.460021E+10 | 17720.32 | 16-APR-15:51 | 28.90 | 20.59 | 0.582283E+09 | 845.64 | 11-APR-13:09 | 28.90 | 20.59 |
May | 0.672024E+10 | 10948.54 | 31-MAY-05:03 | 16.38 | 14.96 | 0.658407E+09 | 845.64 | 05-MAY-09:09 | 16.38 | 14.96 |
June | 0.968765E+10 | 18314.39 | 25-JUN-18:11 | 30.53 | 21.69 | 0.661046E+09 | 846.17 | 26-JUN-13:20 | 31.30 | 21.65 |
July | 0.107473E+11 | 18208.55 | 02-JUL-18:31 | 27.57 | 20.99 | 0.615318E+09 | 846.21 | 03-JUL-13:00 | 29.40 | 24.07 |
August | 0.110475E+11 | 11536.05 | 04-AUG-15:10 | 33.90 | 25.49 | 0.689959E+09 | 845.82 | 03-AUG-13:39 | 33.90 | 25.49 |
September | 0.609548E+10 | 13749.71 | 11-SEP-04:12 | 20.40 | 17.35 | 0.603008E+09 | 845.62 | 05-SEP-13:09 | 20.40 | 17.35 |
October | 0.370416E+10 | 5946.75 | 10-OCT-13:30 | 16.65 | 13.06 | 0.603753E+09 | 845.62 | 10-OCT-09:39 | 16.65 | 13.06 |
November | 0.250042E+10 | 4729.64 | 07-NOV-13:30 | 12.80 | 11.17 | 0.547543E+09 | 845.61 | 03-NOV-09:50 | 12.80 | 11.17 |
December | 0.110064E+10 | 2793.73 | 05-DEC-13:30 | -3.9 | -7.3 | 0.468371E+09 | 729.67 | 04-DEC-14:20 | -3.9 | -7.3 |
Annual Sum or Average | 0.604840E+11 | 0.695362E+10 | ||||||||
Minimum of Months | 0.340788E+09 | 2216.43 | -3.9 | -7.3 | 0.449964E+09 | 729.67 | -3.9 | -7.3 | ||
Maximum of Months | 0.110475E+11 | 18314.39 | 33.90 | 25.49 | 0.689959E+09 | 846.21 | 33.90 | 25.49 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.536383E+09 | 3027.09 | 13-JAN-10:40 | 1.47 | -0.2 | 0.305529E+09 | 526.94 | 13-JAN-10:50 | 1.83 | 0.23 |
February | 0.134004E+10 | 7620.85 | 24-FEB-09:15 | 3.33 | 0.76 | 0.292215E+09 | 544.98 | 08-FEB-10:20 | 3.33 | 0.76 |
March | 0.323926E+10 | 9839.18 | 28-MAR-08:55 | 7.20 | 4.38 | 0.389508E+09 | 565.93 | 13-MAR-09:00 | 7.20 | 4.38 |
April | 0.508161E+10 | 19477.15 | 30-APR-08:52 | 10.00 | 5.13 | 0.363330E+09 | 546.08 | 06-APR-09:09 | 10.00 | 5.13 |
May | 0.730964E+10 | 20814.26 | 21-MAY-08:52 | 13.30 | 8.28 | 0.423261E+09 | 545.78 | 31-MAY-09:20 | 26.47 | 19.61 |
June | 0.947218E+10 | 28696.46 | 25-JUN-08:11 | 24.63 | 20.73 | 0.422821E+09 | 546.16 | 26-JUN-09:20 | 27.57 | 22.45 |
July | 0.104511E+11 | 28679.97 | 02-JUL-09:11 | 25.97 | 21.17 | 0.395592E+09 | 545.34 | 05-JUL-09:09 | 23.07 | 20.39 |
August | 0.993498E+10 | 27102.74 | 20-AUG-08:51 | 20.60 | 18.33 | 0.442586E+09 | 546.01 | 02-AUG-09:39 | 20.60 | 18.33 |
September | 0.687749E+10 | 25418.20 | 03-SEP-09:52 | 18.30 | 13.33 | 0.384684E+09 | 544.96 | 06-SEP-09:09 | 23.27 | 17.32 |
October | 0.394283E+10 | 9267.92 | 20-OCT-09:00 | 12.20 | 8.72 | 0.380970E+09 | 544.96 | 20-OCT-09:09 | 12.70 | 8.99 |
November | 0.226958E+10 | 7199.07 | 04-NOV-08:40 | 4.47 | 1.99 | 0.333911E+09 | 544.44 | 03-NOV-09:00 | 4.47 | 1.99 |
December | 0.912932E+09 | 3644.12 | 01-DEC-10:25 | -2.8 | -4.4 | 0.299055E+09 | 544.22 | 05-DEC-10:09 | -5.9 | -8.1 |
Annual Sum or Average | 0.613680E+11 | 0.443346E+10 | ||||||||
Minimum of Months | 0.536383E+09 | 3027.09 | -2.8 | -4.4 | 0.292215E+09 | 526.94 | -5.9 | -8.1 | ||
Maximum of Months | 0.104511E+11 | 28696.46 | 25.97 | 21.17 | 0.442586E+09 | 565.93 | 27.57 | 22.45 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.271036E+10 | 16438.43 | 04-JAN-12:00 | -10.0 | -11.2 | 0.528585E+09 | 860.32 | 13-JAN-10:00 | 2.20 | 0.51 |
February | 0.381514E+10 | 20204.16 | 16-FEB-13:30 | -8.9 | -10.4 | 0.500054E+09 | 908.57 | 17-FEB-14:39 | -6.9 | -8.5 |
March | 0.620264E+10 | 27522.32 | 19-MAR-12:23 | 15.85 | 12.02 | 0.623788E+09 | 891.69 | 07-MAR-14:00 | 15.85 | 12.02 |
April | 0.829692E+10 | 30525.77 | 16-APR-13:11 | 27.07 | 20.09 | 0.573587E+09 | 853.54 | 04-APR-13:39 | 27.07 | 20.09 |
May | 0.909572E+10 | 26608.00 | 29-MAY-12:53 | 25.00 | 19.70 | 0.653236E+09 | 846.62 | 30-MAY-13:50 | 26.70 | 19.86 |
June | 0.115638E+11 | 29009.42 | 25-JUN-12:52 | 31.70 | 22.71 | 0.657646E+09 | 846.49 | 30-JUN-13:39 | 29.40 | 21.96 |
July | 0.135529E+11 | 30118.89 | 30-JUL-13:01 | 26.78 | 20.36 | 0.614718E+09 | 846.63 | 31-JUL-13:00 | 26.10 | 21.45 |
August | 0.154070E+11 | 27694.61 | 13-AUG-13:22 | 25.55 | 19.87 | 0.689398E+09 | 851.92 | 29-AUG-13:39 | 23.70 | 16.28 |
September | 0.117033E+11 | 32217.79 | 04-SEP-13:11 | 21.30 | 14.06 | 0.601563E+09 | 872.94 | 07-SEP-13:09 | 31.78 | 18.11 |
October | 0.863718E+10 | 28275.07 | 01-OCT-13:42 | 18.95 | 12.28 | 0.608423E+09 | 860.41 | 20-OCT-13:09 | 21.93 | 12.68 |
November | 0.468403E+10 | 28707.23 | 05-NOV-14:02 | 15.10 | 10.18 | 0.560739E+09 | 870.98 | 21-NOV-14:20 | -6.3 | -8.1 |
December | 0.344597E+10 | 27349.39 | 03-DEC-12:13 | 5.20 | 2.37 | 0.512613E+09 | 883.79 | 07-DEC-10:00 | -8.3 | -10.6 |
Annual Sum or Average | 0.991149E+11 | 0.712435E+10 | ||||||||
Minimum of Months | 0.271036E+10 | 16438.43 | -10.0 | -11.2 | 0.500054E+09 | 846.49 | -8.3 | -10.6 | ||
Maximum of Months | 0.154070E+11 | 32217.79 | 31.70 | 22.71 | 0.689398E+09 | 908.57 | 31.78 | 21.96 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.122868E+10 | 5563.87 | 12-JAN-15:20 | 2.80 | 1.13 | 0.313128E+09 | 544.94 | 12-JAN-14:00 | 2.80 | 1.13 |
February | 0.290675E+10 | 10493.97 | 24-FEB-16:20 | 7.93 | 5.63 | 0.308217E+09 | 544.95 | 21-FEB-14:00 | 7.93 | 5.63 |
March | 0.566289E+10 | 12915.49 | 19-MAR-15:02 | 18.40 | 13.72 | 0.409982E+09 | 557.44 | 07-MAR-14:00 | 18.40 | 13.72 |
April | 0.930425E+10 | 36156.69 | 16-APR-16:31 | 28.50 | 20.39 | 0.389114E+09 | 550.60 | 04-APR-13:39 | 28.50 | 20.39 |
May | 0.876240E+10 | 31098.09 | 14-MAY-16:41 | 21.70 | 15.70 | 0.422890E+09 | 544.97 | 08-MAY-13:00 | 21.70 | 15.70 |
June | 0.124166E+11 | 36342.73 | 25-JUN-16:51 | 31.70 | 21.68 | 0.426564E+09 | 544.98 | 20-JUN-13:00 | 31.70 | 21.68 |
July | 0.151644E+11 | 36533.68 | 02-JUL-16:31 | 29.07 | 21.24 | 0.397667E+09 | 544.96 | 18-JUL-09:00 | 22.20 | 15.19 |
August | 0.165915E+11 | 31823.97 | 13-AUG-16:01 | 25.50 | 20.53 | 0.445985E+09 | 545.00 | 08-AUG-09:09 | 25.50 | 20.53 |
September | 0.845074E+10 | 33988.79 | 04-SEP-16:31 | 22.20 | 14.41 | 0.386070E+09 | 544.95 | 05-SEP-13:09 | 27.20 | 16.61 |
October | 0.618018E+10 | 19028.56 | 01-OCT-15:02 | 19.18 | 12.23 | 0.393080E+09 | 544.95 | 10-OCT-09:39 | 13.53 | 11.84 |
November | 0.444222E+10 | 24605.25 | 05-NOV-14:42 | 15.50 | 10.67 | 0.369432E+09 | 544.96 | 21-NOV-14:00 | -6.7 | -8.4 |
December | 0.345398E+10 | 7525.38 | 01-DEC-15:30 | -1.4 | -3.8 | 0.334513E+09 | 544.96 | 14-DEC-14:39 | 1.50 | 0.38 |
Annual Sum or Average | 0.945646E+11 | 0.459664E+10 | ||||||||
Minimum of Months | 0.122868E+10 | 5563.87 | -1.4 | -3.8 | 0.308217E+09 | 544.94 | -6.7 | -8.4 | ||
Maximum of Months | 0.165915E+11 | 36533.68 | 31.70 | 21.68 | 0.445985E+09 | 557.44 | 31.70 | 21.68 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 38713361.92 | 1555.62 | 14-JAN-17:02 | -7.4 | -8.6 | 0.460133E+09 | 626.04 | 30-JAN-14:20 | -24.2 | -24.6 |
February | 93965254.44 | 2324.27 | 24-FEB-13:50 | 7.62 | 4.99 | 0.419131E+09 | 641.58 | 24-FEB-14:00 | 8.30 | 5.62 |
March | 0.102468E+10 | 4537.77 | 30-MAR-12:05 | 1.70 | 1.01 | 0.525590E+09 | 792.13 | 28-MAR-13:00 | 1.70 | 1.01 |
April | 0.253363E+10 | 8467.11 | 18-APR-15:00 | 28.30 | 20.65 | 0.508778E+09 | 845.60 | 19-APR-13:09 | 10.60 | 7.03 |
May | 0.519958E+10 | 9180.71 | 31-MAY-15:00 | 30.00 | 19.70 | 0.636171E+09 | 845.64 | 05-MAY-09:09 | 30.00 | 19.70 |
June | 0.799486E+10 | 18911.86 | 25-JUN-18:22 | 30.25 | 21.63 | 0.653352E+09 | 845.64 | 20-JUN-13:50 | 30.25 | 21.63 |
July | 0.833286E+10 | 18270.11 | 02-JUL-18:31 | 27.57 | 20.99 | 0.613719E+09 | 845.62 | 18-JUL-09:00 | 22.20 | 15.19 |
August | 0.783083E+10 | 11267.01 | 04-AUG-05:03 | 22.80 | 22.80 | 0.685135E+09 | 845.66 | 08-AUG-09:09 | 20.28 | 15.58 |
September | 0.475438E+10 | 9379.79 | 11-SEP-14:00 | 28.90 | 20.23 | 0.574736E+09 | 845.62 | 06-SEP-09:20 | 28.90 | 20.23 |
October | 0.211566E+10 | 3323.91 | 26-OCT-16:10 | 6.70 | 3.71 | 0.520559E+09 | 842.30 | 02-OCT-13:00 | 6.70 | 3.71 |
November | 0.961403E+09 | 3959.96 | 09-NOV-17:05 | 1.60 | 0.33 | 0.483664E+09 | 803.78 | 07-NOV-14:39 | 1.60 | 0.33 |
December | 17430856.58 | 1566.39 | 30-DEC-17:02 | -1.1 | -1.6 | 0.446108E+09 | 625.93 | 27-DEC-10:39 | -1.1 | -1.6 |
Annual Sum or Average | 0.408980E+11 | 0.652708E+10 | ||||||||
Minimum of Months | 17430856.58 | 1555.62 | -7.4 | -8.6 | 0.419131E+09 | 625.93 | -24.2 | -24.6 | ||
Maximum of Months | 0.833286E+10 | 18911.86 | 30.25 | 22.80 | 0.685135E+09 | 845.66 | 30.25 | 21.63 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.111136E+09 | 2569.57 | 13-JAN-11:50 | 3.62 | 1.34 | 0.218565E+09 | 414.12 | 12-JAN-09:00 | 3.62 | 1.34 |
February | 0.404454E+09 | 4028.93 | 24-FEB-09:55 | 4.40 | 1.36 | 0.201390E+09 | 521.19 | 24-FEB-09:00 | 4.40 | 1.36 |
March | 0.182150E+10 | 9650.14 | 31-MAR-09:50 | 3.72 | 1.12 | 0.258418E+09 | 542.22 | 21-MAR-10:30 | 3.72 | 1.12 |
April | 0.367142E+10 | 17268.28 | 30-APR-09:32 | 10.73 | 5.66 | 0.246865E+09 | 543.49 | 26-APR-08:20 | 10.73 | 5.66 |
May | 0.673150E+10 | 28014.35 | 21-MAY-08:41 | 12.85 | 8.05 | 0.303199E+09 | 534.66 | 03-MAY-07:40 | 12.85 | 8.05 |
June | 0.920035E+10 | 31413.69 | 25-JUN-09:01 | 26.38 | 21.26 | 0.305419E+09 | 521.66 | 09-JUN-08:00 | 26.38 | 21.26 |
July | 0.980100E+10 | 31526.21 | 02-JUL-09:11 | 25.97 | 21.17 | 0.290770E+09 | 522.04 | 05-JUL-08:00 | 22.80 | 20.41 |
August | 0.879339E+10 | 28810.42 | 20-AUG-08:41 | 20.22 | 18.09 | 0.322935E+09 | 521.56 | 01-AUG-08:50 | 20.22 | 18.09 |
September | 0.623583E+10 | 28533.32 | 04-SEP-09:01 | 16.47 | 13.08 | 0.273445E+09 | 521.24 | 08-SEP-07:10 | 17.03 | 15.57 |
October | 0.270619E+10 | 7684.77 | 20-OCT-09:00 | 12.20 | 8.72 | 0.249648E+09 | 521.49 | 16-OCT-10:20 | 12.20 | 8.72 |
November | 0.101625E+10 | 3627.90 | 04-NOV-09:30 | 7.50 | 4.04 | 0.223384E+09 | 499.11 | 03-NOV-10:00 | 7.50 | 4.04 |
December | 0.111719E+09 | 3021.26 | 01-DEC-17:57 | -4.4 | -5.6 | 0.211237E+09 | 407.11 | 05-DEC-09:00 | -6.1 | -8.3 |
Annual Sum or Average | 0.506047E+11 | 0.310527E+10 | ||||||||
Minimum of Months | 0.111136E+09 | 2569.57 | -4.4 | -5.6 | 0.201390E+09 | 407.11 | -6.1 | -8.3 | ||
Maximum of Months | 0.980100E+10 | 31526.21 | 26.38 | 21.26 | 0.322935E+09 | 543.49 | 26.38 | 21.26 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.218377E+10 | 19182.49 | 12-JAN-14:30 | 2.50 | 0.82 | 0.514806E+09 | 867.91 | 12-JAN-14:09 | 2.50 | 0.82 |
February | 0.293215E+10 | 23544.19 | 08-FEB-13:10 | 2.30 | 1.25 | 0.481043E+09 | 875.77 | 08-FEB-14:30 | 2.50 | 1.16 |
March | 0.472755E+10 | 23049.45 | 10-MAR-13:50 | -1.2 | -3.2 | 0.587949E+09 | 891.60 | 16-MAR-15:09 | -4.2 | -6.8 |
April | 0.648742E+10 | 28867.57 | 16-APR-13:22 | 27.25 | 20.22 | 0.538875E+09 | 859.57 | 03-APR-15:39 | 27.25 | 20.22 |
May | 0.809584E+10 | 21566.23 | 14-MAY-12:32 | 20.20 | 14.62 | 0.639629E+09 | 846.51 | 30-MAY-13:50 | 26.70 | 19.86 |
June | 0.103422E+11 | 29540.89 | 25-JUN-12:22 | 31.15 | 22.56 | 0.649336E+09 | 846.53 | 30-JUN-13:00 | 29.40 | 21.96 |
July | 0.115219E+11 | 31214.31 | 30-JUL-13:01 | 26.78 | 20.36 | 0.612455E+09 | 846.39 | 31-JUL-13:00 | 26.10 | 21.45 |
August | 0.127718E+11 | 30303.17 | 13-AUG-13:12 | 25.37 | 19.81 | 0.685083E+09 | 864.16 | 29-AUG-13:50 | 23.80 | 16.18 |
September | 0.112669E+11 | 33092.95 | 17-SEP-13:31 | 26.67 | 18.01 | 0.589991E+09 | 898.84 | 07-SEP-13:20 | 26.67 | 18.01 |
October | 0.764803E+10 | 31662.69 | 01-OCT-12:51 | 18.70 | 12.19 | 0.581851E+09 | 888.84 | 20-OCT-13:30 | 22.20 | 12.82 |
November | 0.331557E+10 | 27785.34 | 05-NOV-13:32 | 14.80 | 9.85 | 0.523238E+09 | 858.49 | 16-NOV-14:20 | 7.40 | 2.82 |
December | 0.232217E+10 | 22288.87 | 01-DEC-11:54 | -1.7 | -3.7 | 0.492763E+09 | 890.64 | 01-DEC-11:50 | -1.7 | -3.7 |
Annual Sum or Average | 0.836154E+11 | 0.689702E+10 | ||||||||
Minimum of Months | 0.218377E+10 | 19182.49 | -1.7 | -3.7 | 0.481043E+09 | 846.39 | -4.2 | -6.8 | ||
Maximum of Months | 0.127718E+11 | 33092.95 | 31.15 | 22.56 | 0.685083E+09 | 898.84 | 29.40 | 21.96 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.278105E+09 | 4471.38 | 13-JAN-14:45 | 3.90 | 1.72 | 0.300584E+09 | 491.72 | 12-JAN-16:10 | 3.90 | 1.72 |
February | 0.703878E+09 | 7254.60 | 24-FEB-16:30 | 7.75 | 5.51 | 0.278566E+09 | 543.48 | 24-FEB-14:00 | 7.75 | 5.51 |
March | 0.204414E+10 | 8848.60 | 21-MAR-15:50 | -0.5 | -4.1 | 0.345788E+09 | 544.57 | 10-MAR-14:00 | -0.5 | -4.1 |
April | 0.474912E+10 | 29323.02 | 16-APR-16:01 | 28.80 | 20.54 | 0.332290E+09 | 605.30 | 03-APR-15:39 | 28.80 | 20.54 |
May | 0.676649E+10 | 32255.13 | 14-MAY-17:11 | 21.13 | 15.93 | 0.399362E+09 | 544.97 | 08-MAY-13:00 | 21.13 | 15.93 |
June | 0.943840E+10 | 34350.60 | 25-JUN-17:01 | 31.60 | 21.70 | 0.414284E+09 | 544.97 | 20-JUN-13:50 | 31.60 | 21.70 |
July | 0.103929E+11 | 33705.13 | 02-JUL-16:31 | 29.07 | 21.24 | 0.393749E+09 | 544.95 | 18-JUL-09:00 | 22.20 | 15.19 |
August | 0.979972E+10 | 29887.05 | 13-AUG-16:31 | 25.20 | 20.49 | 0.438833E+09 | 544.97 | 30-AUG-13:39 | 23.33 | 17.60 |
September | 0.646351E+10 | 31742.37 | 04-SEP-16:21 | 22.20 | 14.41 | 0.360405E+09 | 544.95 | 05-SEP-13:09 | 27.20 | 16.61 |
October | 0.336793E+10 | 11596.29 | 11-OCT-16:00 | 17.80 | 11.96 | 0.338069E+09 | 544.93 | 11-OCT-13:00 | 17.80 | 11.96 |
November | 0.140529E+10 | 7710.07 | 03-NOV-15:30 | 15.55 | 9.47 | 0.310054E+09 | 540.82 | 03-NOV-13:00 | 15.55 | 9.47 |
December | 0.354308E+09 | 3582.73 | 01-DEC-17:57 | -4.4 | -5.6 | 0.292113E+09 | 496.99 | 01-DEC-15:00 | -4.4 | -5.6 |
Annual Sum or Average | 0.557638E+11 | 0.420410E+10 | ||||||||
Minimum of Months | 0.278105E+09 | 3582.73 | -4.4 | -5.6 | 0.278566E+09 | 491.72 | -4.4 | -5.6 | ||
Maximum of Months | 0.103929E+11 | 34350.60 | 31.60 | 21.70 | 0.438833E+09 | 605.30 | 31.60 | 21.70 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 16202079.65 | 1728.33 | 14-JAN-17:02 | -7.4 | -8.6 | 0.458549E+09 | 626.01 | 25-JAN-10:30 | -15.6 | -15.9 |
February | 60971705.33 | 2206.17 | 24-FEB-14:30 | 8.05 | 5.40 | 0.417781E+09 | 632.59 | 24-FEB-14:00 | 8.30 | 5.62 |
March | 0.688909E+09 | 2647.79 | 28-MAR-15:30 | 16.40 | 10.50 | 0.514423E+09 | 750.97 | 28-MAR-13:00 | 16.40 | 10.50 |
April | 0.215260E+10 | 21796.80 | 16-APR-15:41 | 28.80 | 20.54 | 0.491229E+09 | 845.60 | 13-APR-13:00 | 28.80 | 20.54 |
May | 0.506657E+10 | 10074.56 | 31-MAY-15:00 | 30.00 | 19.70 | 0.615352E+09 | 845.63 | 09-MAY-13:09 | 30.00 | 19.70 |
June | 0.817129E+10 | 22550.57 | 11-JUN-15:21 | 33.05 | 24.40 | 0.643792E+09 | 845.63 | 16-JUN-13:50 | 23.80 | 17.54 |
July | 0.853795E+10 | 22381.28 | 04-JUL-18:41 | 25.28 | 21.09 | 0.611078E+09 | 845.62 | 18-JUL-09:00 | 22.20 | 15.19 |
August | 0.789667E+10 | 11547.25 | 03-AUG-05:03 | 23.30 | 22.56 | 0.677946E+09 | 845.65 | 30-AUG-13:39 | 23.33 | 17.60 |
September | 0.447990E+10 | 9828.94 | 11-SEP-14:00 | 28.90 | 20.23 | 0.551575E+09 | 845.62 | 06-SEP-09:39 | 28.90 | 20.23 |
October | 0.153100E+10 | 3547.38 | 20-OCT-14:00 | 22.60 | 13.03 | 0.491704E+09 | 793.91 | 11-OCT-13:00 | 22.60 | 13.03 |
November | 0.664019E+09 | 3107.47 | 03-NOV-13:30 | 15.85 | 10.76 | 0.468840E+09 | 746.90 | 03-NOV-13:00 | 16.10 | 10.47 |
December | 14436809.52 | 1749.90 | 30-DEC-17:02 | -1.1 | -1.6 | 0.445101E+09 | 625.93 | 04-DEC-10:09 | -1.1 | -1.6 |
Annual Sum or Average | 0.392805E+11 | 0.638737E+10 | ||||||||
Minimum of Months | 14436809.52 | 1728.33 | -7.4 | -8.6 | 0.417781E+09 | 625.93 | -15.6 | -15.9 | ||
Maximum of Months | 0.853795E+10 | 22550.57 | 33.05 | 24.40 | 0.677946E+09 | 845.65 | 30.00 | 20.54 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 70844198.13 | 2107.08 | 13-JAN-06:04 | -1.7 | -2.4 | 0.298208E+09 | 408.08 | 12-JAN-10:39 | -1.7 | -2.4 |
February | 0.302987E+09 | 2962.26 | 24-FEB-09:55 | 4.40 | 1.36 | 0.273944E+09 | 532.97 | 24-FEB-10:30 | 5.00 | 1.88 |
March | 0.138444E+10 | 6067.53 | 28-MAR-09:45 | 9.53 | 5.99 | 0.347187E+09 | 544.95 | 28-MAR-09:00 | 10.00 | 6.30 |
April | 0.314267E+10 | 23389.66 | 16-APR-15:41 | 28.80 | 20.54 | 0.332149E+09 | 544.97 | 13-APR-09:09 | 28.80 | 20.54 |
May | 0.639579E+10 | 26899.09 | 14-MAY-08:31 | 15.03 | 12.87 | 0.409245E+09 | 545.92 | 31-MAY-09:50 | 27.02 | 19.46 |
June | 0.928455E+10 | 29967.56 | 11-JUN-08:61 | 24.37 | 20.62 | 0.413201E+09 | 546.01 | 26-JUN-09:39 | 27.93 | 22.45 |
July | 0.989630E+10 | 28550.63 | 23-JUL-09:31 | 19.63 | 14.53 | 0.393918E+09 | 546.15 | 05-JUL-09:09 | 19.63 | 14.53 |
August | 0.881885E+10 | 21860.02 | 27-AUG-09:32 | 23.87 | 19.50 | 0.439139E+09 | 546.19 | 02-AUG-09:00 | 23.87 | 19.50 |
September | 0.579133E+10 | 19231.28 | 04-SEP-09:22 | 17.20 | 13.02 | 0.367764E+09 | 544.97 | 06-SEP-09:39 | 24.67 | 18.11 |
October | 0.205231E+10 | 6448.87 | 20-OCT-09:40 | 14.20 | 9.74 | 0.328179E+09 | 544.96 | 20-OCT-09:09 | 14.20 | 9.74 |
November | 0.696906E+09 | 3179.85 | 03-NOV-13:30 | 15.85 | 10.76 | 0.300560E+09 | 474.51 | 03-NOV-10:00 | 15.85 | 10.76 |
December | 48186256.86 | 1821.75 | 30-DEC-17:02 | -1.1 | -1.6 | 0.287814E+09 | 403.38 | 26-DEC-10:00 | -1.1 | -1.6 |
Annual Sum or Average | 0.478852E+11 | 0.419131E+10 | ||||||||
Minimum of Months | 48186256.86 | 1821.75 | -1.7 | -2.4 | 0.273944E+09 | 403.38 | -1.7 | -2.4 | ||
Maximum of Months | 0.989630E+10 | 29967.56 | 28.80 | 20.62 | 0.439139E+09 | 546.19 | 28.80 | 22.45 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.173541E+10 | 13186.18 | 12-JAN-12:40 | 2.03 | 0.42 | 0.504912E+09 | 845.65 | 12-JAN-14:30 | 2.50 | 0.82 |
February | 0.250022E+10 | 20170.01 | 24-FEB-13:40 | 7.43 | 4.81 | 0.469267E+09 | 845.65 | 24-FEB-14:09 | 7.88 | 5.25 |
March | 0.385062E+10 | 18154.79 | 24-MAR-13:20 | 12.57 | 6.49 | 0.572424E+09 | 845.78 | 24-MAR-13:00 | 13.30 | 6.51 |
April | 0.575013E+10 | 34172.94 | 16-APR-13:41 | 27.62 | 20.47 | 0.524548E+09 | 846.37 | 18-APR-13:39 | 27.93 | 20.65 |
May | 0.774827E+10 | 17966.18 | 30-MAY-13:20 | 26.70 | 19.86 | 0.623591E+09 | 846.19 | 30-MAY-13:39 | 26.70 | 19.86 |
June | 0.104908E+11 | 30275.67 | 11-JUN-14:41 | 33.03 | 24.69 | 0.639494E+09 | 846.63 | 26-JUN-13:20 | 31.30 | 21.65 |
July | 0.116812E+11 | 30720.14 | 30-JUL-13:12 | 26.87 | 20.18 | 0.608885E+09 | 846.52 | 31-JUL-13:00 | 26.10 | 21.45 |
August | 0.127812E+11 | 32354.06 | 13-AUG-13:42 | 25.92 | 19.97 | 0.678852E+09 | 849.14 | 29-AUG-13:50 | 23.80 | 16.18 |
September | 0.106195E+11 | 32141.73 | 17-SEP-13:42 | 26.93 | 18.07 | 0.573734E+09 | 884.48 | 07-SEP-13:39 | 26.93 | 18.07 |
October | 0.631220E+10 | 30885.03 | 01-OCT-14:01 | 19.07 | 12.30 | 0.558843E+09 | 855.00 | 20-OCT-13:30 | 22.20 | 12.82 |
November | 0.261086E+10 | 21651.92 | 03-NOV-13:30 | 15.85 | 10.76 | 0.501944E+09 | 845.74 | 03-NOV-13:00 | 16.10 | 10.47 |
December | 0.186357E+10 | 15343.22 | 01-DEC-13:25 | -0.9 | -3.3 | 0.484778E+09 | 845.65 | 05-DEC-14:00 | -3.9 | -7.4 |
Annual Sum or Average | 0.779440E+11 | 0.674127E+10 | ||||||||
Minimum of Months | 0.173541E+10 | 13186.18 | -0.9 | -3.3 | 0.469267E+09 | 845.65 | -3.9 | -7.4 | ||
Maximum of Months | 0.127812E+11 | 34172.94 | 33.03 | 24.69 | 0.678852E+09 | 884.48 | 31.30 | 21.65 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.203633E+09 | 3040.95 | 12-JAN-15:50 | 2.80 | 1.13 | 0.299706E+09 | 475.08 | 12-JAN-15:00 | 2.80 | 1.13 |
February | 0.576333E+09 | 7172.28 | 24-FEB-16:30 | 7.75 | 5.51 | 0.277151E+09 | 543.77 | 24-FEB-14:00 | 7.75 | 5.51 |
March | 0.162794E+10 | 7526.15 | 21-MAR-16:00 | -0.6 | -4.1 | 0.340922E+09 | 528.79 | 28-MAR-13:00 | 16.70 | 10.30 |
April | 0.425217E+10 | 34301.96 | 16-APR-16:21 | 28.60 | 20.44 | 0.324798E+09 | 544.94 | 13-APR-13:00 | 28.60 | 20.44 |
May | 0.659333E+10 | 33646.81 | 14-MAY-17:11 | 21.13 | 15.93 | 0.388241E+09 | 544.96 | 08-MAY-13:00 | 21.13 | 15.93 |
June | 0.952746E+10 | 32446.09 | 25-JUN-17:11 | 31.50 | 21.73 | 0.408032E+09 | 544.96 | 16-JUN-13:50 | 31.50 | 21.73 |
July | 0.105005E+11 | 35065.65 | 23-JUL-16:51 | 22.80 | 15.36 | 0.390702E+09 | 544.95 | 18-JUL-09:00 | 22.80 | 15.36 |
August | 0.981661E+10 | 33587.53 | 13-AUG-15:41 | 25.68 | 20.51 | 0.433580E+09 | 544.97 | 30-AUG-13:39 | 23.33 | 17.60 |
September | 0.613192E+10 | 29430.48 | 04-SEP-16:42 | 22.20 | 14.41 | 0.349804E+09 | 544.95 | 05-SEP-13:20 | 27.20 | 16.61 |
October | 0.267606E+10 | 11507.45 | 11-OCT-16:00 | 17.80 | 11.96 | 0.328574E+09 | 544.91 | 11-OCT-13:00 | 17.80 | 11.96 |
November | 0.104733E+10 | 7462.43 | 03-NOV-15:30 | 15.55 | 9.47 | 0.303122E+09 | 537.28 | 03-NOV-13:00 | 15.55 | 9.47 |
December | 0.276299E+09 | 3076.85 | 01-DEC-15:50 | -1.6 | -4.0 | 0.290051E+09 | 479.78 | 01-DEC-15:00 | -1.7 | -4.1 |
Annual Sum or Average | 0.532296E+11 | 0.413468E+10 | ||||||||
Minimum of Months | 0.203633E+09 | 3040.95 | -1.6 | -4.1 | 0.277151E+09 | 475.08 | -1.7 | -4.1 | ||
Maximum of Months | 0.105005E+11 | 35065.65 | 31.50 | 21.73 | 0.433580E+09 | 544.97 | 31.50 | 21.73 |
Report: ZoneCoolingSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.185341E+09 | 11005.79 | 19-JAN-04:01 | -26.3 | -26.6 | 0.00 | 0.00 | 01-JAN-00:10 | -26.3 | -26.6 |
February | 0.421062E+09 | 9605.21 | 02-FEB-04:01 | -35.2 | -35.3 | 0.00 | 0.00 | 01-FEB-00:10 | -35.2 | -35.3 |
March | 0.168142E+10 | 7410.01 | 06-MAR-05:01 | -15.4 | -15.9 | 0.00 | 0.00 | 01-MAR-00:10 | -15.4 | -15.9 |
April | 0.397845E+10 | 8558.67 | 18-APR-15:10 | 27.75 | 20.46 | 0.00 | 0.00 | 01-APR-00:10 | 27.75 | 20.46 |
May | 0.570262E+10 | 9175.75 | 30-MAY-05:15 | 14.60 | 14.60 | 0.00 | 0.00 | 01-MAY-00:10 | 14.60 | 14.60 |
June | 0.860864E+10 | 9937.75 | 26-JUN-15:40 | 31.50 | 22.02 | 0.00 | 0.00 | 01-JUN-00:10 | 31.50 | 22.02 |
July | 0.963213E+10 | 10861.90 | 03-JUL-05:15 | 18.50 | 17.39 | 0.00 | 0.00 | 01-JUL-00:10 | 18.50 | 17.39 |
August | 0.102821E+11 | 10004.01 | 21-AUG-05:13 | 15.93 | 15.21 | 0.00 | 0.00 | 01-AUG-00:10 | 15.93 | 15.21 |
September | 0.631641E+10 | 10301.68 | 11-SEP-05:15 | 19.80 | 17.33 | 0.00 | 0.00 | 01-SEP-00:10 | 19.80 | 17.33 |
October | 0.338118E+10 | 4830.79 | 12-OCT-05:15 | 6.10 | 2.83 | 0.00 | 0.00 | 01-OCT-00:10 | 6.10 | 2.83 |
November | 0.179685E+10 | 7350.75 | 28-NOV-05:01 | -21.1 | -21.4 | 0.00 | 0.00 | 01-NOV-00:10 | -21.1 | -21.4 |
December | 0.356178E+09 | 8539.77 | 09-DEC-04:01 | -22.8 | -23.0 | 0.00 | 0.00 | 01-DEC-00:10 | -22.8 | -23.0 |
Annual Sum or Average | 0.523424E+11 | 0.00 | ||||||||
Minimum of Months | 0.185341E+09 | 4830.79 | -35.2 | -35.3 | 0.00 | 0.00 | -35.2 | -35.3 | ||
Maximum of Months | 0.102821E+11 | 11005.79 | 31.50 | 22.02 | 0.00 | 0.00 | 31.50 | 22.02 |
Report: ZoneCoolingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.526220E+09 | 12053.25 | 07-JAN-04:11 | -24.8 | -25.1 | 0.00 | 0.00 | 01-JAN-00:10 | -24.8 | -25.1 |
February | 0.413657E+09 | 12391.55 | 18-FEB-04:01 | -15.6 | -16.0 | 0.00 | 0.00 | 01-FEB-00:10 | -15.6 | -16.0 |
March | 0.600338E+09 | 11724.30 | 21-MAR-03:01 | -6.7 | -7.9 | 0.00 | 0.00 | 01-MAR-00:10 | -6.7 | -7.9 |
April | 0.177273E+10 | 11748.27 | 03-APR-03:01 | -6.2 | -7.2 | 0.00 | 0.00 | 01-APR-00:10 | -6.2 | -7.2 |
May | 0.347687E+10 | 6744.05 | 02-MAY-04:11 | 2.60 | 0.50 | 0.00 | 0.00 | 01-MAY-00:10 | 2.60 | 0.50 |
June | 0.642028E+10 | 8552.53 | 30-JUN-05:15 | 21.10 | 19.18 | 0.00 | 0.00 | 01-JUN-00:10 | 21.10 | 19.18 |
July | 0.706007E+10 | 7939.31 | 05-JUL-15:20 | 27.80 | 20.26 | 0.00 | 0.00 | 01-JUL-00:10 | 27.80 | 20.26 |
August | 0.696043E+10 | 8327.55 | 04-AUG-15:20 | 33.90 | 25.66 | 0.00 | 0.00 | 01-AUG-00:10 | 33.90 | 25.66 |
September | 0.442485E+10 | 9483.37 | 30-SEP-04:01 | -0.5 | -1.9 | 0.00 | 0.00 | 01-SEP-00:10 | -0.5 | -1.9 |
October | 0.122172E+10 | 10636.06 | 23-OCT-04:01 | -1.9 | -2.9 | 0.00 | 0.00 | 01-OCT-00:10 | -1.9 | -2.9 |
November | 0.781846E+09 | 11360.62 | 26-NOV-00:41 | -24.4 | -24.7 | 0.00 | 0.00 | 01-NOV-00:10 | -24.4 | -24.7 |
December | 0.496935E+09 | 13435.68 | 09-DEC-03:41 | -22.7 | -23.0 | 0.00 | 0.00 | 01-DEC-00:10 | -22.7 | -23.0 |
Annual Sum or Average | 0.341559E+11 | 0.00 | ||||||||
Minimum of Months | 0.413657E+09 | 6744.05 | -24.8 | -25.1 | 0.00 | 0.00 | -24.8 | -25.1 | ||
Maximum of Months | 0.706007E+10 | 13435.68 | 33.90 | 25.66 | 0.00 | 0.00 | 33.90 | 25.66 |
Report: ZoneCoolingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:02 | -2.8 | -3.2 | 0.00 | 0.00 | 01-JAN-00:10 | -2.8 | -3.2 |
February | 15801220.36 | 1307.40 | 24-FEB-14:00 | 7.80 | 5.17 | 0.00 | 0.00 | 01-FEB-00:10 | 7.80 | 5.17 |
March | 0.414985E+09 | 5356.00 | 24-MAR-14:30 | 13.05 | 6.50 | 0.00 | 0.00 | 01-MAR-00:10 | 13.05 | 6.50 |
April | 0.273947E+10 | 16400.26 | 18-APR-15:00 | 28.30 | 20.65 | 0.00 | 0.00 | 01-APR-00:10 | 28.30 | 20.65 |
May | 0.631099E+10 | 18839.03 | 31-MAY-14:00 | 29.40 | 19.44 | 0.00 | 0.00 | 01-MAY-00:10 | 29.40 | 19.44 |
June | 0.110728E+11 | 21353.58 | 26-JUN-13:30 | 31.40 | 21.76 | 0.00 | 0.00 | 01-JUN-00:10 | 31.40 | 21.76 |
July | 0.120836E+11 | 20313.91 | 05-JUL-14:00 | 27.20 | 19.77 | 0.00 | 0.00 | 01-JUL-00:10 | 27.20 | 19.77 |
August | 0.112005E+11 | 21269.99 | 04-AUG-15:20 | 33.90 | 25.66 | 0.00 | 0.00 | 01-AUG-00:10 | 33.90 | 25.66 |
September | 0.572088E+10 | 17862.57 | 07-SEP-15:00 | 31.70 | 18.53 | 0.00 | 0.00 | 01-SEP-00:10 | 31.70 | 18.53 |
October | 0.906406E+09 | 7873.45 | 20-OCT-15:10 | 22.97 | 13.26 | 0.00 | 0.00 | 01-OCT-00:10 | 22.97 | 13.26 |
November | 0.177883E+09 | 4582.36 | 03-NOV-14:30 | 16.10 | 10.04 | 0.00 | 0.00 | 01-NOV-00:10 | 16.10 | 10.04 |
December | 0.00 | 0.00 | 01-DEC-00:10 | -0.7 | -1.3 | 0.00 | 0.00 | 01-DEC-00:10 | -0.7 | -1.3 |
Annual Sum or Average | 0.506434E+11 | 0.00 | ||||||||
Minimum of Months | 0.00 | 0.00 | -2.8 | -3.2 | 0.00 | 0.00 | -2.8 | -3.2 | ||
Maximum of Months | 0.120836E+11 | 21353.58 | 33.90 | 25.66 | 0.00 | 0.00 | 33.90 | 25.66 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.138341E+10 | 2075.13 | 12-JAN-16:30 | 2.25 | 0.82 | 95034525.63 | 126.82 | 02-JAN-10:09 | 2.25 | 0.82 |
February | 0.656480E+10 | 4421.47 | 24-FEB-17:00 | 7.20 | 5.13 | 86396448.25 | 126.82 | 14-FEB-14:09 | 7.20 | 5.13 |
March | 0.136599E+11 | 6927.14 | 31-MAR-24:00 | -1.0 | -2.0 | 0.103236E+09 | 126.83 | 29-MAR-13:00 | -1.0 | -2.0 |
April | 0.187729E+11 | 8539.08 | 16-APR-17:52 | 26.70 | 19.84 | 91605571.72 | 126.83 | 11-APR-13:00 | 26.70 | 19.84 |
May | 0.444344E+10 | 3529.44 | 31-MAY-24:00 | 15.10 | 10.22 | 99242256.45 | 126.85 | 30-MAY-13:50 | 15.10 | 10.22 |
June | 0.952464E+10 | 5380.07 | 30-JUN-24:00 | 19.10 | 15.95 | 98970591.02 | 126.86 | 13-JUN-09:00 | 19.10 | 15.95 |
July | 0.150109E+11 | 7261.24 | 31-JUL-24:00 | 18.20 | 17.87 | 91890689.12 | 126.85 | 06-JUL-09:39 | 18.20 | 17.87 |
August | 0.201101E+11 | 8484.84 | 29-AUG-17:50 | 21.38 | 14.81 | 0.103335E+09 | 132.70 | 04-AUG-13:00 | 21.38 | 14.81 |
September | 0.435701E+10 | 3010.69 | 30-SEP-24:00 | 3.90 | 1.09 | 91611048.88 | 126.86 | 11-SEP-09:50 | 3.90 | 1.09 |
October | 0.905212E+10 | 5015.89 | 31-OCT-24:00 | 1.50 | -0.9 | 95230742.17 | 126.84 | 02-OCT-13:00 | 1.50 | -0.9 |
November | 0.130070E+11 | 6198.07 | 05-NOV-16:17 | 13.70 | 9.80 | 94301215.60 | 126.83 | 08-NOV-10:30 | 13.60 | 12.33 |
December | 0.178406E+11 | 7976.10 | 05-DEC-16:10 | -5.1 | -8.3 | 91880818.71 | 126.82 | 05-DEC-10:09 | -5.1 | -8.3 |
Annual Sum or Average | 0.133727E+12 | 0.114274E+10 | ||||||||
Minimum of Months | 0.138341E+10 | 2075.13 | -5.1 | -8.3 | 86396448.25 | 126.82 | -5.1 | -8.3 | ||
Maximum of Months | 0.201101E+11 | 8539.08 | 26.70 | 19.84 | 0.103335E+09 | 132.70 | 26.70 | 19.84 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.395470E+09 | 1703.52 | 12-JAN-16:40 | 2.07 | 0.72 | 90270846.61 | 126.82 | 12-JAN-14:20 | 2.07 | 0.72 |
February | 0.401022E+10 | 3995.35 | 24-FEB-17:00 | 7.20 | 5.13 | 86396463.91 | 126.82 | 14-FEB-14:09 | 7.20 | 5.13 |
March | 0.109090E+11 | 6032.93 | 31-MAR-23:20 | -0.3 | -1.4 | 0.103236E+09 | 126.83 | 29-MAR-13:00 | -0.3 | -1.4 |
April | 0.165395E+11 | 7942.89 | 16-APR-17:42 | 26.97 | 19.92 | 91605710.01 | 126.83 | 11-APR-13:00 | 26.97 | 19.92 |
May | 0.358701E+10 | 3334.66 | 31-MAY-24:00 | 15.10 | 10.22 | 99239356.05 | 126.85 | 30-MAY-13:09 | 15.10 | 10.22 |
June | 0.874603E+10 | 5232.27 | 30-JUN-24:00 | 19.10 | 15.95 | 98971065.22 | 126.86 | 13-JUN-13:30 | 19.10 | 15.95 |
July | 0.141437E+11 | 6892.90 | 31-JUL-24:00 | 18.20 | 17.87 | 91892288.42 | 126.85 | 07-JUL-09:00 | 18.20 | 17.87 |
August | 0.188641E+11 | 8109.00 | 29-AUG-17:40 | 21.67 | 14.89 | 0.103261E+09 | 127.15 | 04-AUG-13:00 | 21.67 | 14.89 |
September | 0.348477E+10 | 2641.94 | 04-SEP-17:50 | 20.87 | 14.10 | 91610061.32 | 126.85 | 11-SEP-13:00 | 28.90 | 20.23 |
October | 0.704149E+10 | 4215.60 | 31-OCT-23:30 | 1.05 | -1.2 | 95230713.68 | 126.84 | 02-OCT-13:00 | 1.05 | -1.2 |
November | 0.100341E+11 | 5746.21 | 03-NOV-16:00 | 15.00 | 9.33 | 94301151.65 | 126.83 | 08-NOV-10:00 | 13.90 | 12.62 |
December | 0.139277E+11 | 7209.24 | 01-DEC-16:20 | -2.4 | -4.5 | 91880835.00 | 126.82 | 05-DEC-10:09 | -5.9 | -8.1 |
Annual Sum or Average | 0.111683E+12 | 0.113790E+10 | ||||||||
Minimum of Months | 0.395470E+09 | 1703.52 | -2.4 | -4.5 | 86396463.91 | 126.82 | -5.9 | -8.1 | ||
Maximum of Months | 0.188641E+11 | 8109.00 | 26.97 | 19.92 | 0.103261E+09 | 127.15 | 28.90 | 20.23 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.294843E+09 | 1609.45 | 12-JAN-16:40 | 2.07 | 0.72 | 85676866.05 | 127.26 | 12-JAN-10:00 | 2.07 | 0.72 |
February | 0.281590E+10 | 4007.90 | 24-FEB-17:00 | 7.20 | 5.13 | 86375519.93 | 126.82 | 14-FEB-14:09 | 7.20 | 5.13 |
March | 0.956443E+10 | 5805.51 | 21-MAR-17:40 | -1.8 | -4.9 | 0.103236E+09 | 126.83 | 29-MAR-13:00 | 8.90 | 7.98 |
April | 0.155165E+11 | 8221.11 | 16-APR-17:52 | 26.70 | 19.84 | 91605745.37 | 126.83 | 11-APR-13:00 | 26.70 | 19.84 |
May | 0.314233E+10 | 3297.44 | 31-MAY-23:30 | 16.30 | 11.24 | 99238673.24 | 126.86 | 30-MAY-13:00 | 16.30 | 11.24 |
June | 0.854963E+10 | 5206.12 | 30-JUN-24:00 | 19.10 | 15.95 | 98970891.36 | 126.87 | 13-JUN-13:39 | 19.10 | 15.95 |
July | 0.140736E+11 | 6786.35 | 31-JUL-24:00 | 18.20 | 17.87 | 91892063.81 | 126.85 | 07-JUL-09:00 | 18.20 | 17.87 |
August | 0.187301E+11 | 8169.03 | 29-AUG-17:40 | 21.67 | 14.89 | 0.103260E+09 | 126.96 | 04-AUG-13:00 | 21.67 | 14.89 |
September | 0.294680E+10 | 2652.10 | 04-SEP-17:50 | 20.87 | 14.10 | 91594777.81 | 126.85 | 11-SEP-13:00 | 28.90 | 20.23 |
October | 0.556831E+10 | 4205.90 | 11-OCT-17:00 | 16.70 | 11.06 | 95230694.42 | 126.84 | 02-OCT-13:00 | 16.70 | 11.06 |
November | 0.839641E+10 | 5740.39 | 03-NOV-16:00 | 15.00 | 9.33 | 94301151.63 | 126.83 | 08-NOV-10:00 | 13.90 | 12.62 |
December | 0.122455E+11 | 7087.52 | 01-DEC-16:20 | -2.4 | -4.5 | 91880839.99 | 126.82 | 05-DEC-10:09 | -5.9 | -8.1 |
Annual Sum or Average | 0.101844E+12 | 0.113326E+10 | ||||||||
Minimum of Months | 0.294843E+09 | 1609.45 | -2.4 | -4.9 | 85676866.05 | 126.82 | -5.9 | -8.1 | ||
Maximum of Months | 0.187301E+11 | 8221.11 | 26.70 | 19.84 | 0.103260E+09 | 127.26 | 28.90 | 20.23 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.232405E+12 | 91529.91 | 13-JAN-17:00 | 2.20 | 0.77 | 0.206144E+10 | 2745.29 | 09-JAN-14:20 | 2.20 | 0.77 |
February | 0.431477E+12 | 183532.78 | 24-FEB-17:00 | 7.20 | 5.13 | 0.187027E+10 | 2745.50 | 06-FEB-10:00 | 7.20 | 5.13 |
March | 0.727051E+12 | 358422.09 | 31-MAR-24:00 | -1.0 | -2.0 | 0.223478E+10 | 2745.56 | 28-MAR-13:00 | -1.0 | -2.0 |
April | 0.941434E+12 | 371580.41 | 18-APR-17:45 | 24.18 | 17.54 | 0.200618E+10 | 3674.45 | 18-APR-13:00 | 24.18 | 17.54 |
May | 0.240976E+12 | 176492.67 | 31-MAY-24:00 | 15.10 | 10.22 | 0.214807E+10 | 2746.78 | 04-MAY-13:30 | 15.10 | 10.22 |
June | 0.471672E+12 | 268583.40 | 30-JUN-24:00 | 19.10 | 15.95 | 0.214255E+10 | 2748.75 | 13-JUN-13:09 | 19.10 | 15.95 |
July | 0.732823E+12 | 360918.16 | 31-JUL-24:00 | 18.20 | 17.87 | 0.208156E+10 | 4041.93 | 26-JUL-15:09 | 18.20 | 17.87 |
August | 0.974904E+12 | 389338.94 | 04-AUG-17:53 | 20.60 | 19.43 | 0.262014E+10 | 5027.92 | 04-AUG-13:09 | 20.60 | 19.43 |
September | 0.236959E+12 | 175361.13 | 30-SEP-24:00 | 3.90 | 1.09 | 0.198303E+10 | 2746.65 | 11-SEP-13:30 | 3.90 | 1.09 |
October | 0.486989E+12 | 268259.93 | 31-OCT-24:00 | 1.50 | -0.9 | 0.206144E+10 | 2745.50 | 11-OCT-09:09 | 1.50 | -0.9 |
November | 0.706338E+12 | 277322.07 | 03-NOV-16:00 | 15.00 | 9.33 | 0.204130E+10 | 2746.31 | 02-NOV-13:09 | 15.00 | 9.33 |
December | 0.972167E+12 | 367947.76 | 05-DEC-17:00 | -5.6 | -8.5 | 0.198896E+10 | 2745.46 | 14-DEC-10:00 | -1.7 | -2.6 |
Annual Sum or Average | 0.715520E+13 | 0.252397E+11 | ||||||||
Minimum of Months | 0.232405E+12 | 91529.91 | -5.6 | -8.5 | 0.187027E+10 | 2745.29 | -1.7 | -2.6 | ||
Maximum of Months | 0.974904E+12 | 389338.94 | 24.18 | 19.43 | 0.262014E+10 | 5027.92 | 24.18 | 19.43 |
Report: ZoneHeatingSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.118121E+09 | 12403.51 | 14-JAN-05:03 | -2.0 |
February | 0.271648E+09 | 12547.92 | 21-FEB-05:03 | -6.6 |
March | 0.105590E+09 | 12953.08 | 29-MAR-04:15 | 7.80 |
April | 0.146138E+09 | 17634.23 | 15-APR-16:01 | 30.00 |
May | 0.145438E+09 | 13024.15 | 16-MAY-04:15 | 10.40 |
June | 0.256608E+09 | 14364.77 | 25-JUN-20:12 | 27.43 |
July | 0.385550E+09 | 14740.11 | 16-JUL-19:12 | 23.17 |
August | 0.344846E+09 | 14178.88 | 13-AUG-20:23 | 18.85 |
September | 0.386954E+09 | 15334.61 | 16-SEP-16:01 | 28.62 |
October | 0.168552E+09 | 12975.31 | 31-OCT-03:15 | 0.00 |
November | 0.185976E+09 | 12966.07 | 03-NOV-04:15 | 11.10 |
December | 70538218.19 | 12707.85 | 27-DEC-05:04 | -9.0 |
Annual Sum or Average | 0.258596E+10 | |||
Minimum of Months | 70538218.19 | 12403.51 | -9.0 | |
Maximum of Months | 0.386954E+09 | 17634.23 | 30.00 |
Report: ZoneHeatingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 992494.14 | 14887.41 | 30-JAN-06:01 | -28.4 |
February | 2709657.46 | 16354.10 | 06-FEB-06:01 | -15.0 |
March | 0.00 | 0.00 | 01-MAR-00:05 | -11.0 |
April | 0.00 | 0.00 | 01-APR-00:10 | -1.2 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 8.22 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 14.70 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 18.93 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.15 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 3.92 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 1.65 |
December | 0.00 | 0.00 | 01-DEC-00:10 | -0.7 |
Annual Sum or Average | 3702151.60 | |||
Minimum of Months | 0.00 | 0.00 | -28.4 | |
Maximum of Months | 2709657.46 | 16354.10 | 18.93 |
Report: ZoneHeatingSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.182057E+10 | 64837.21 | 02-JAN-04:01 | -4.0 |
February | 0.492659E+09 | 59014.02 | 06-FEB-05:01 | -14.5 |
March | 0.134936E+09 | 55037.19 | 06-MAR-05:01 | -15.4 |
April | 9665522.47 | 50636.21 | 03-APR-05:01 | -7.2 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 8.22 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 14.70 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 18.93 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.15 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 3.92 |
November | 0.298895E+09 | 58551.03 | 27-NOV-05:01 | -9.4 |
December | 0.665821E+09 | 58860.30 | 11-DEC-05:01 | -22.2 |
Annual Sum or Average | 0.342255E+10 | |||
Minimum of Months | 0.00 | 0.00 | -22.2 | |
Maximum of Months | 0.182057E+10 | 64837.21 | 18.93 |
Report: ZoneHeatingSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.102256E+11 | 86536.72 | 30-JAN-04:11 | -27.4 |
February | 0.578505E+10 | 84962.63 | 06-FEB-04:01 | -14.4 |
March | 0.213234E+10 | 83291.34 | 06-MAR-04:01 | -16.0 |
April | 0.657275E+09 | 81823.76 | 03-APR-03:11 | -6.3 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 8.22 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 14.70 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 18.93 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.15 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 16.07 |
October | 0.336925E+09 | 75207.29 | 16-OCT-04:11 | 1.57 |
November | 0.382361E+10 | 84905.92 | 27-NOV-04:01 | -10.4 |
December | 0.679729E+10 | 85271.18 | 11-DEC-04:01 | -21.8 |
Annual Sum or Average | 0.297581E+11 | |||
Minimum of Months | 0.00 | 0.00 | -27.4 | |
Maximum of Months | 0.102256E+11 | 86536.72 | 18.93 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.486471E+10 | 15530.12 | 30-JAN-04:01 | -27.3 |
February | 0.267313E+10 | 15497.36 | 02-FEB-04:01 | -35.2 |
March | 0.226733E+09 | 13650.66 | 06-MAR-05:01 | -15.4 |
April | 12837157.53 | 12275.60 | 03-APR-05:01 | -7.2 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 8.22 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 14.70 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 18.93 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.15 |
September | 15719.86 | 52.40 | 30-SEP-09:00 | 6.10 |
October | 45723.32 | 150.61 | 14-OCT-09:27 | 4.45 |
November | 0.492495E+09 | 14085.11 | 27-NOV-04:01 | -10.4 |
December | 0.143130E+10 | 15027.70 | 11-DEC-04:01 | -21.8 |
Annual Sum or Average | 0.970127E+10 | |||
Minimum of Months | 0.00 | 0.00 | -35.2 | |
Maximum of Months | 0.486471E+10 | 15530.12 | 18.93 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.294648E+10 | 18915.01 | 30-JAN-04:01 | -27.3 |
February | 0.159603E+10 | 18919.60 | 02-FEB-04:01 | -35.2 |
March | 0.222483E+09 | 16370.60 | 06-MAR-05:01 | -15.4 |
April | 20404501.63 | 14443.63 | 03-APR-05:01 | -7.2 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 8.22 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 14.70 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 18.93 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.15 |
September | 22130.01 | 258.18 | 30-SEP-05:03 | 0.10 |
October | 861845.62 | 3857.36 | 27-OCT-05:01 | 0.00 |
November | 0.391881E+09 | 17472.59 | 27-NOV-04:01 | -10.4 |
December | 0.137721E+10 | 18302.22 | 11-DEC-04:01 | -21.8 |
Annual Sum or Average | 0.655537E+10 | |||
Minimum of Months | 0.00 | 0.00 | -35.2 | |
Maximum of Months | 0.294648E+10 | 18919.60 | 18.93 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.360890E+10 | 23842.11 | 30-JAN-04:01 | -27.3 |
February | 0.169887E+10 | 23656.58 | 02-FEB-04:01 | -35.2 |
March | 0.404454E+09 | 20980.94 | 06-MAR-05:01 | -15.4 |
April | 55037158.46 | 20586.96 | 03-APR-04:01 | -6.8 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 8.22 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 14.70 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 18.93 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.15 |
September | 570620.19 | 5918.51 | 30-SEP-05:01 | 0.10 |
October | 6933578.36 | 11297.87 | 27-OCT-05:01 | 0.00 |
November | 0.566455E+09 | 23085.68 | 27-NOV-04:01 | -10.4 |
December | 0.184847E+10 | 23252.50 | 09-DEC-04:01 | -22.8 |
Annual Sum or Average | 0.818969E+10 | |||
Minimum of Months | 0.00 | 0.00 | -35.2 | |
Maximum of Months | 0.360890E+10 | 23842.11 | 18.93 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.146795E+10 | 18223.84 | 30-JAN-04:01 | -27.3 |
February | 0.638720E+09 | 17918.48 | 02-FEB-04:01 | -35.2 |
March | 12919936.68 | 14526.17 | 06-MAR-05:01 | -15.4 |
April | 338782.63 | 5081.74 | 03-APR-05:01 | -7.2 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 8.22 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 14.70 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 18.93 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.15 |
September | 36167.20 | 89.20 | 30-SEP-09:00 | 6.10 |
October | 11808.99 | 59.04 | 14-OCT-09:27 | 4.45 |
November | 44964355.60 | 14805.07 | 27-NOV-05:01 | -9.4 |
December | 0.144627E+09 | 15765.33 | 09-DEC-05:01 | -22.8 |
Annual Sum or Average | 0.230956E+10 | |||
Minimum of Months | 0.00 | 0.00 | -35.2 | |
Maximum of Months | 0.146795E+10 | 18223.84 | 18.93 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.153606E+11 | 18193.01 | 19-JAN-04:11 | -26.5 |
February | 0.885492E+10 | 17942.05 | 02-FEB-04:11 | -35.4 |
March | 0.380225E+10 | 16588.87 | 05-MAR-19:42 | -14.3 |
April | 0.883063E+09 | 15846.35 | 03-APR-03:01 | -6.2 |
May | 28649581.38 | 13342.95 | 02-MAY-04:11 | 2.60 |
June | 181680.79 | 1211.21 | 02-JUN-05:03 | 7.20 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 18.93 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.15 |
September | 73362675.12 | 13385.63 | 30-SEP-04:01 | -0.5 |
October | 0.533590E+09 | 14154.57 | 16-OCT-04:11 | 1.57 |
November | 0.486336E+10 | 16691.74 | 26-NOV-04:01 | -25.0 |
December | 0.106586E+11 | 18050.97 | 09-DEC-05:01 | -22.8 |
Annual Sum or Average | 0.450586E+11 | |||
Minimum of Months | 0.00 | 0.00 | -35.4 | |
Maximum of Months | 0.153606E+11 | 18193.01 | 18.93 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.925484E+10 | 25171.96 | 19-JAN-04:11 | -26.5 |
February | 0.490100E+10 | 24810.05 | 02-FEB-04:11 | -35.4 |
March | 0.202758E+10 | 22745.41 | 06-MAR-04:21 | -15.9 |
April | 0.507397E+09 | 21908.26 | 03-APR-03:01 | -6.2 |
May | 11843469.39 | 18143.00 | 02-MAY-04:11 | 2.60 |
June | 224986.09 | 1499.91 | 02-JUN-05:03 | 7.20 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 18.93 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.15 |
September | 41198570.74 | 16870.26 | 30-SEP-04:01 | -0.5 |
October | 0.299908E+09 | 19177.71 | 24-OCT-04:11 | 1.93 |
November | 0.298541E+10 | 22910.17 | 26-NOV-04:01 | -25.0 |
December | 0.662228E+10 | 24022.83 | 09-DEC-05:01 | -22.8 |
Annual Sum or Average | 0.266517E+11 | |||
Minimum of Months | 0.00 | 0.00 | -35.4 | |
Maximum of Months | 0.925484E+10 | 25171.96 | 18.93 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.964831E+10 | 27261.87 | 19-JAN-04:11 | -26.5 |
February | 0.484462E+10 | 26724.18 | 02-FEB-04:11 | -35.4 |
March | 0.240243E+10 | 24358.29 | 06-MAR-04:21 | -15.9 |
April | 0.634753E+09 | 23824.09 | 03-APR-03:01 | -6.2 |
May | 19221210.80 | 19693.55 | 02-MAY-04:11 | 2.60 |
June | 133275.60 | 888.50 | 02-JUN-05:03 | 7.20 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 18.93 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.15 |
September | 46603078.00 | 19789.51 | 30-SEP-04:01 | -0.5 |
October | 0.279438E+09 | 20615.64 | 16-OCT-04:11 | 1.57 |
November | 0.315579E+10 | 24787.38 | 27-NOV-04:01 | -10.4 |
December | 0.740398E+10 | 26047.87 | 09-DEC-05:01 | -22.8 |
Annual Sum or Average | 0.284353E+11 | |||
Minimum of Months | 0.00 | 0.00 | -35.4 | |
Maximum of Months | 0.964831E+10 | 27261.87 | 18.93 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.832626E+10 | 26640.89 | 19-JAN-04:11 | -26.5 |
February | 0.419876E+10 | 26160.67 | 02-FEB-04:11 | -35.4 |
March | 0.163346E+10 | 23671.20 | 06-MAR-04:21 | -15.9 |
April | 0.324431E+09 | 22979.16 | 03-APR-03:01 | -6.2 |
May | 11913435.32 | 14308.75 | 02-MAY-04:11 | 2.60 |
June | 304288.57 | 2028.59 | 02-JUN-05:03 | 7.20 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 18.93 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.15 |
September | 39566417.13 | 19319.93 | 30-SEP-04:01 | -0.5 |
October | 0.223319E+09 | 20324.53 | 16-OCT-04:11 | 1.57 |
November | 0.240463E+10 | 24126.70 | 26-NOV-04:01 | -25.0 |
December | 0.542665E+10 | 25408.49 | 09-DEC-05:01 | -22.8 |
Annual Sum or Average | 0.225893E+11 | |||
Minimum of Months | 0.00 | 0.00 | -35.4 | |
Maximum of Months | 0.832626E+10 | 26640.89 | 18.93 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.219190E+11 | 23985.43 | 30-JAN-04:11 | -27.4 |
February | 0.141281E+11 | 23254.96 | 02-FEB-04:11 | -35.4 |
March | 0.723747E+10 | 21909.26 | 06-MAR-04:21 | -15.9 |
April | 0.251197E+10 | 20855.19 | 02-APR-21:52 | -3.9 |
May | 0.151341E+09 | 17957.15 | 02-MAY-04:11 | 2.60 |
June | 27675888.85 | 15481.25 | 05-JUN-05:03 | 9.32 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 18.93 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.15 |
September | 0.402166E+09 | 17618.15 | 29-SEP-04:01 | 0.68 |
October | 0.203520E+10 | 19317.17 | 23-OCT-03:01 | -1.2 |
November | 0.918794E+10 | 21358.15 | 26-NOV-04:01 | -25.0 |
December | 0.171691E+11 | 24430.90 | 09-DEC-02:61 | -22.7 |
Annual Sum or Average | 0.747699E+11 | |||
Minimum of Months | 0.00 | 0.00 | -35.4 | |
Maximum of Months | 0.219190E+11 | 24430.90 | 18.93 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.134251E+11 | 26182.81 | 30-JAN-04:11 | -27.4 |
February | 0.802254E+10 | 25900.46 | 02-FEB-04:11 | -35.4 |
March | 0.387675E+10 | 24134.30 | 06-MAR-04:21 | -15.9 |
April | 0.140751E+10 | 23015.83 | 02-APR-21:52 | -3.9 |
May | 55250109.19 | 19891.88 | 02-MAY-04:11 | 2.60 |
June | 15088274.43 | 8528.46 | 02-JUN-05:03 | 7.20 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 18.93 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.15 |
September | 0.204728E+09 | 19506.09 | 29-SEP-04:01 | 0.68 |
October | 0.103085E+10 | 21565.70 | 23-OCT-03:01 | -1.2 |
November | 0.555397E+10 | 23830.48 | 26-NOV-04:01 | -25.0 |
December | 0.106337E+11 | 27116.74 | 09-DEC-02:61 | -22.7 |
Annual Sum or Average | 0.442255E+11 | |||
Minimum of Months | 0.00 | 0.00 | -35.4 | |
Maximum of Months | 0.134251E+11 | 27116.74 | 18.93 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.152974E+11 | 30161.40 | 19-JAN-04:01 | -26.3 |
February | 0.885883E+10 | 29598.58 | 02-FEB-04:11 | -35.4 |
March | 0.505144E+10 | 27683.64 | 06-MAR-04:21 | -15.9 |
April | 0.199806E+10 | 26803.03 | 02-APR-21:52 | -3.9 |
May | 0.117218E+09 | 22879.27 | 02-MAY-04:11 | 2.60 |
June | 27399960.61 | 15994.55 | 03-JUN-05:03 | 5.78 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 18.93 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.15 |
September | 0.281909E+09 | 22581.02 | 29-SEP-04:01 | 0.68 |
October | 0.120247E+10 | 24971.58 | 16-OCT-04:11 | 1.57 |
November | 0.641798E+10 | 27355.71 | 26-NOV-04:01 | -25.0 |
December | 0.126548E+11 | 31218.40 | 09-DEC-02:61 | -22.7 |
Annual Sum or Average | 0.519075E+11 | |||
Minimum of Months | 0.00 | 0.00 | -35.4 | |
Maximum of Months | 0.152974E+11 | 31218.40 | 18.93 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.125533E+11 | 28880.67 | 19-JAN-04:01 | -26.3 |
February | 0.684929E+10 | 28428.43 | 02-FEB-04:11 | -35.4 |
March | 0.328702E+10 | 26094.94 | 06-MAR-04:21 | -15.9 |
April | 0.977354E+09 | 25093.36 | 03-APR-03:11 | -6.3 |
May | 56616674.86 | 21697.33 | 02-MAY-04:11 | 2.60 |
June | 9988338.42 | 8464.51 | 02-JUN-05:03 | 7.20 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 18.93 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.15 |
September | 0.186526E+09 | 21500.70 | 29-SEP-04:01 | 0.68 |
October | 0.802240E+09 | 23844.58 | 16-OCT-04:11 | 1.57 |
November | 0.446215E+10 | 25998.21 | 26-NOV-04:01 | -25.0 |
December | 0.883395E+10 | 29694.12 | 09-DEC-02:61 | -22.7 |
Annual Sum or Average | 0.380184E+11 | |||
Minimum of Months | 0.00 | 0.00 | -35.4 | |
Maximum of Months | 0.125533E+11 | 29694.12 | 18.93 |
Report: ZoneHeatingSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.340152E+10 | 9035.75 | 03-JAN-10:50 | -16.1 |
February | 0.209492E+10 | 11731.57 | 10-FEB-06:02 | 3.40 |
March | 0.643892E+09 | 12012.24 | 14-MAR-05:01 | 1.10 |
April | 0.213725E+09 | 14015.63 | 24-APR-04:11 | 11.70 |
May | 84953629.09 | 10473.34 | 01-MAY-04:12 | 5.93 |
June | 94934508.70 | 12473.84 | 25-JUN-15:31 | 32.20 |
July | 0.130435E+09 | 12983.59 | 02-JUL-15:11 | 29.40 |
August | 0.121053E+09 | 11282.60 | 13-AUG-15:21 | 25.85 |
September | 83062380.54 | 9936.55 | 04-SEP-15:11 | 22.20 |
October | 0.121451E+09 | 11983.78 | 01-OCT-15:02 | 19.18 |
November | 0.739512E+09 | 13356.87 | 13-NOV-05:01 | -2.9 |
December | 0.162442E+10 | 14534.57 | 05-DEC-05:01 | 0.37 |
Annual Sum or Average | 0.935388E+10 | |||
Minimum of Months | 83062380.54 | 9035.75 | -16.1 | |
Maximum of Months | 0.340152E+10 | 14534.57 | 32.20 |
Report: ZoneHeatingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.869542E+10 | 21465.10 | 02-JAN-06:12 | -5.2 |
February | 0.506692E+10 | 16700.94 | 06-FEB-06:06 | -15.0 |
March | 0.286219E+10 | 15812.25 | 16-MAR-15:30 | -3.9 |
April | 0.933011E+09 | 14500.17 | 03-APR-15:35 | -3.0 |
May | 0.130851E+09 | 10620.79 | 21-MAY-14:42 | 17.70 |
June | 68696092.92 | 15061.09 | 11-JUN-15:11 | 33.13 |
July | 89061632.56 | 13299.93 | 02-JUL-15:51 | 29.40 |
August | 53458630.30 | 10587.43 | 13-AUG-15:51 | 25.60 |
September | 80421158.41 | 12093.76 | 17-SEP-14:11 | 27.20 |
October | 0.644017E+09 | 10277.20 | 29-OCT-13:12 | 13.17 |
November | 0.288203E+10 | 16214.04 | 27-NOV-06:11 | -9.4 |
December | 0.584057E+10 | 16254.44 | 01-DEC-17:00 | -3.9 |
Annual Sum or Average | 0.273466E+11 | |||
Minimum of Months | 53458630.30 | 10277.20 | -15.0 | |
Maximum of Months | 0.869542E+10 | 21465.10 | 33.13 |
Report: ZoneHeatingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.240595E+11 | 38408.53 | 30-JAN-04:32 | -27.6 |
February | 0.158492E+11 | 39724.03 | 02-FEB-05:12 | -36.3 |
March | 0.859580E+10 | 35162.62 | 06-MAR-05:09 | -15.4 |
April | 0.366049E+10 | 28388.08 | 03-APR-04:12 | -6.9 |
May | 0.560190E+09 | 14889.65 | 06-MAY-05:03 | 9.40 |
June | 0.212552E+09 | 16534.40 | 22-JUN-05:03 | 9.68 |
July | 91410990.55 | 15077.25 | 24-JUL-05:02 | 10.28 |
August | 0.128259E+09 | 15273.43 | 17-AUG-05:03 | 10.68 |
September | 0.100823E+10 | 14718.14 | 02-SEP-05:03 | 9.40 |
October | 0.320261E+10 | 17455.52 | 23-OCT-05:03 | -2.7 |
November | 0.110054E+11 | 32257.72 | 28-NOV-06:12 | -18.1 |
December | 0.195733E+11 | 35400.53 | 11-DEC-05:07 | -22.2 |
Annual Sum or Average | 0.879471E+11 | |||
Minimum of Months | 91410990.55 | 14718.14 | -36.3 | |
Maximum of Months | 0.240595E+11 | 39724.03 | 10.68 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.108885E+09 | 605.61 | 29-JAN-20:37 | -23.9 |
February | 0.00 | 0.00 | 01-FEB-00:03 | -24.1 |
March | 0.00 | 0.00 | 01-MAR-00:05 | -11.0 |
April | 0.00 | 0.00 | 01-APR-00:10 | -1.2 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 8.22 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 14.70 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 18.93 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.15 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 3.92 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 1.65 |
December | 0.00 | 0.00 | 01-DEC-00:10 | -0.7 |
Annual Sum or Average | 0.108885E+09 | |||
Minimum of Months | 0.00 | 0.00 | -24.1 | |
Maximum of Months | 0.108885E+09 | 605.61 | 18.93 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.759647E+09 | 632.77 | 29-JAN-17:57 | -22.8 |
February | 3171287.77 | 180.21 | 06-FEB-03:45 | -14.7 |
March | 0.00 | 0.00 | 01-MAR-00:05 | -11.0 |
April | 0.00 | 0.00 | 01-APR-00:10 | -1.2 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 8.22 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 14.70 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 18.93 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.15 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 3.92 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 1.65 |
December | 0.00 | 0.00 | 01-DEC-00:10 | -0.7 |
Annual Sum or Average | 0.762818E+09 | |||
Minimum of Months | 0.00 | 0.00 | -22.8 | |
Maximum of Months | 0.759647E+09 | 632.77 | 18.93 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.817703E+09 | 649.41 | 28-JAN-19:15 | -7.6 |
February | 0.193738E+09 | 614.45 | 05-FEB-19:10 | -19.0 |
March | 0.00 | 0.00 | 01-MAR-00:05 | -11.0 |
April | 0.00 | 0.00 | 01-APR-00:10 | -1.2 |
May | 6104395.68 | 472.19 | 01-MAY-04:12 | 5.93 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 14.70 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 18.93 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.15 |
September | 27216112.09 | 596.00 | 30-SEP-03:45 | -0.5 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 3.92 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 1.65 |
December | 0.00 | 0.00 | 01-DEC-00:10 | -0.7 |
Annual Sum or Average | 0.104476E+10 | |||
Minimum of Months | 0.00 | 0.00 | -19.0 | |
Maximum of Months | 0.817703E+09 | 649.41 | 18.93 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:02 | -2.8 |
February | 0.00 | 0.00 | 01-FEB-00:03 | -24.1 |
March | 0.00 | 0.00 | 01-MAR-00:05 | -11.0 |
April | 0.00 | 0.00 | 01-APR-00:10 | -1.2 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 8.22 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 14.70 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 18.93 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.15 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 3.92 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 1.65 |
December | 0.00 | 0.00 | 01-DEC-00:10 | -0.7 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | -24.1 | |
Maximum of Months | 0.00 | 0.00 | 18.93 |
Report: ZoneElectricSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.219312E+11 | 22950.34 | 02-JAN-08:09 | 0.360447E+11 | 13457.54 | 01-JAN-00:10 |
February | 0.198933E+11 | 22950.34 | 01-FEB-08:09 | 0.325565E+11 | 13457.54 | 01-FEB-00:10 |
March | 0.236388E+11 | 22950.34 | 01-MAR-08:09 | 0.360447E+11 | 13457.54 | 01-MAR-00:10 |
April | 0.211142E+11 | 22950.34 | 03-APR-07:10 | 0.348820E+11 | 13457.54 | 01-APR-00:10 |
May | 0.227850E+11 | 22950.34 | 01-MAY-07:10 | 0.360447E+11 | 13457.54 | 01-MAY-00:10 |
June | 0.226748E+11 | 22950.34 | 01-JUN-07:10 | 0.348820E+11 | 13457.54 | 01-JUN-00:10 |
July | 0.212244E+11 | 22950.34 | 03-JUL-07:10 | 0.360447E+11 | 13457.54 | 01-JUL-00:10 |
August | 0.236388E+11 | 22950.34 | 01-AUG-07:10 | 0.360447E+11 | 13457.54 | 01-AUG-00:10 |
September | 0.211142E+11 | 22950.34 | 01-SEP-07:10 | 0.348820E+11 | 13457.54 | 01-SEP-00:10 |
October | 0.219312E+11 | 22950.34 | 02-OCT-07:10 | 0.360447E+11 | 13457.54 | 01-OCT-00:10 |
November | 0.216742E+11 | 22950.34 | 01-NOV-07:10 | 0.348820E+11 | 13457.54 | 01-NOV-00:10 |
December | 0.212244E+11 | 22950.34 | 01-DEC-08:09 | 0.360447E+11 | 13457.54 | 01-DEC-00:10 |
Annual Sum or Average | 0.262844E+12 | 0.424397E+12 | ||||
Minimum of Months | 0.198933E+11 | 22950.34 | 0.325565E+11 | 13457.54 | ||
Maximum of Months | 0.236388E+11 | 22950.34 | 0.360447E+11 | 13457.54 |
Report: ZoneElectricSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.196958E+11 | 20611.01 | 02-JAN-08:09 | 0.243681E+11 | 17206.63 | 02-JAN-08:09 |
February | 0.178655E+11 | 20611.01 | 01-FEB-08:09 | 0.220609E+11 | 17206.63 | 01-FEB-08:09 |
March | 0.212293E+11 | 20611.01 | 01-MAR-08:09 | 0.253549E+11 | 17206.63 | 01-MAR-08:09 |
April | 0.189620E+11 | 20611.01 | 03-APR-07:10 | 0.235306E+11 | 17206.63 | 03-APR-07:10 |
May | 0.204625E+11 | 20611.01 | 01-MAY-07:10 | 0.248615E+11 | 17206.63 | 01-MAY-07:10 |
June | 0.203636E+11 | 20611.01 | 01-JUN-07:10 | 0.244160E+11 | 17206.63 | 01-JUN-07:10 |
July | 0.190610E+11 | 20611.01 | 03-JUL-07:10 | 0.239708E+11 | 17206.63 | 03-JUL-07:10 |
August | 0.212293E+11 | 20611.01 | 01-AUG-07:10 | 0.253549E+11 | 17206.63 | 01-AUG-07:10 |
September | 0.189620E+11 | 20611.01 | 01-SEP-07:10 | 0.235199E+11 | 17206.63 | 01-SEP-07:10 |
October | 0.196958E+11 | 20611.01 | 02-OCT-07:10 | 0.243735E+11 | 17206.63 | 02-OCT-07:10 |
November | 0.194649E+11 | 20611.01 | 01-NOV-07:10 | 0.238373E+11 | 17206.63 | 01-NOV-07:10 |
December | 0.190610E+11 | 20611.01 | 01-DEC-08:09 | 0.239654E+11 | 17206.63 | 01-DEC-08:09 |
Annual Sum or Average | 0.236053E+12 | 0.289614E+12 | ||||
Minimum of Months | 0.178655E+11 | 20611.01 | 0.220609E+11 | 17206.63 | ||
Maximum of Months | 0.212293E+11 | 20611.01 | 0.253549E+11 | 17206.63 |
Report: ZoneElectricSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.196958E+11 | 20611.01 | 02-JAN-08:09 | 0.243680E+11 | 17206.56 | 02-JAN-08:09 |
February | 0.178655E+11 | 20611.01 | 01-FEB-08:09 | 0.220609E+11 | 17206.56 | 01-FEB-08:09 |
March | 0.212293E+11 | 20611.01 | 01-MAR-08:09 | 0.253548E+11 | 17206.56 | 01-MAR-08:09 |
April | 0.189620E+11 | 20611.01 | 03-APR-07:10 | 0.235305E+11 | 17206.56 | 03-APR-07:10 |
May | 0.204625E+11 | 20611.01 | 01-MAY-07:10 | 0.248614E+11 | 17206.56 | 01-MAY-07:10 |
June | 0.203636E+11 | 20611.01 | 01-JUN-07:10 | 0.244159E+11 | 17206.56 | 01-JUN-07:10 |
July | 0.190610E+11 | 20611.01 | 03-JUL-07:10 | 0.239707E+11 | 17206.56 | 03-JUL-07:10 |
August | 0.212293E+11 | 20611.01 | 01-AUG-07:10 | 0.253548E+11 | 17206.56 | 01-AUG-07:10 |
September | 0.189620E+11 | 20611.01 | 01-SEP-07:10 | 0.235198E+11 | 17206.56 | 01-SEP-07:10 |
October | 0.196958E+11 | 20611.01 | 02-OCT-07:10 | 0.243734E+11 | 17206.56 | 02-OCT-07:10 |
November | 0.194649E+11 | 20611.01 | 01-NOV-07:10 | 0.238372E+11 | 17206.56 | 01-NOV-07:10 |
December | 0.190610E+11 | 20611.01 | 01-DEC-08:09 | 0.239653E+11 | 17206.56 | 01-DEC-08:09 |
Annual Sum or Average | 0.236053E+12 | 0.289613E+12 | ||||
Minimum of Months | 0.178655E+11 | 20611.01 | 0.220609E+11 | 17206.56 | ||
Maximum of Months | 0.212293E+11 | 20611.01 | 0.253548E+11 | 17206.56 |
Report: ZoneElectricSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.196958E+11 | 20611.01 | 02-JAN-08:09 | 0.243680E+11 | 17206.56 | 02-JAN-08:09 |
February | 0.178655E+11 | 20611.01 | 01-FEB-08:09 | 0.220609E+11 | 17206.56 | 01-FEB-08:09 |
March | 0.212293E+11 | 20611.01 | 01-MAR-08:09 | 0.253548E+11 | 17206.56 | 01-MAR-08:09 |
April | 0.189620E+11 | 20611.01 | 03-APR-07:10 | 0.235305E+11 | 17206.56 | 03-APR-07:10 |
May | 0.204625E+11 | 20611.01 | 01-MAY-07:10 | 0.248614E+11 | 17206.56 | 01-MAY-07:10 |
June | 0.203636E+11 | 20611.01 | 01-JUN-07:10 | 0.244159E+11 | 17206.56 | 01-JUN-07:10 |
July | 0.190610E+11 | 20611.01 | 03-JUL-07:10 | 0.239707E+11 | 17206.56 | 03-JUL-07:10 |
August | 0.212293E+11 | 20611.01 | 01-AUG-07:10 | 0.253548E+11 | 17206.56 | 01-AUG-07:10 |
September | 0.189620E+11 | 20611.01 | 01-SEP-07:10 | 0.235198E+11 | 17206.56 | 01-SEP-07:10 |
October | 0.196958E+11 | 20611.01 | 02-OCT-07:10 | 0.243734E+11 | 17206.56 | 02-OCT-07:10 |
November | 0.194649E+11 | 20611.01 | 01-NOV-07:10 | 0.238372E+11 | 17206.56 | 01-NOV-07:10 |
December | 0.190610E+11 | 20611.01 | 01-DEC-08:09 | 0.239653E+11 | 17206.56 | 01-DEC-08:09 |
Annual Sum or Average | 0.236053E+12 | 0.289613E+12 | ||||
Minimum of Months | 0.178655E+11 | 20611.01 | 0.220609E+11 | 17206.56 | ||
Maximum of Months | 0.212293E+11 | 20611.01 | 0.253548E+11 | 17206.56 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.166983E+10 | 2587.92 | 02-JAN-16:19 | 0.305979E+10 | 2160.55 | 02-JAN-08:09 |
February | 0.139976E+10 | 2255.20 | 01-FEB-16:49 | 0.277008E+10 | 2160.55 | 01-FEB-08:09 |
March | 0.152300E+10 | 1803.00 | 01-MAR-16:49 | 0.318369E+10 | 2160.55 | 01-MAR-08:09 |
April | 0.132292E+10 | 1803.00 | 10-APR-07:10 | 0.295462E+10 | 2160.55 | 03-APR-07:10 |
May | 0.136569E+10 | 1231.33 | 01-MAY-07:10 | 0.312174E+10 | 2160.55 | 01-MAY-07:10 |
June | 0.134831E+10 | 1470.28 | 13-JUN-07:10 | 0.306580E+10 | 2160.55 | 01-JUN-07:10 |
July | 0.127316E+10 | 1470.28 | 20-JUL-07:10 | 0.300989E+10 | 2160.55 | 03-JUL-07:10 |
August | 0.142863E+10 | 1350.81 | 28-AUG-07:10 | 0.318369E+10 | 2160.55 | 01-AUG-07:10 |
September | 0.134363E+10 | 1803.00 | 21-SEP-07:10 | 0.295328E+10 | 2160.55 | 01-SEP-07:10 |
October | 0.147648E+10 | 2587.92 | 30-OCT-07:10 | 0.306046E+10 | 2160.55 | 02-OCT-07:10 |
November | 0.161916E+10 | 2587.92 | 01-NOV-07:10 | 0.299314E+10 | 2160.55 | 01-NOV-07:10 |
December | 0.171905E+10 | 2587.92 | 01-DEC-16:10 | 0.300922E+10 | 2160.55 | 01-DEC-08:09 |
Annual Sum or Average | 0.174896E+11 | 0.363654E+11 | ||||
Minimum of Months | 0.127316E+10 | 1231.33 | 0.277008E+10 | 2160.55 | ||
Maximum of Months | 0.171905E+10 | 2587.92 | 0.318369E+10 | 2160.55 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.104961E+10 | 1667.75 | 02-JAN-16:19 | 0.197184E+10 | 1392.34 | 02-JAN-08:09 |
February | 0.886186E+09 | 1453.34 | 01-FEB-16:49 | 0.178515E+10 | 1392.34 | 01-FEB-08:09 |
March | 0.977170E+09 | 1161.92 | 01-MAR-16:40 | 0.205169E+10 | 1392.34 | 01-MAR-08:09 |
April | 0.850785E+09 | 947.51 | 10-APR-07:10 | 0.190407E+10 | 1392.34 | 03-APR-07:10 |
May | 0.887448E+09 | 870.51 | 09-MAY-15:20 | 0.201177E+10 | 1392.34 | 01-MAY-07:10 |
June | 0.874159E+09 | 870.51 | 05-JUN-15:30 | 0.197572E+10 | 1392.34 | 01-JUN-07:10 |
July | 0.824127E+09 | 870.51 | 20-JUL-07:10 | 0.193969E+10 | 1392.34 | 03-JUL-07:10 |
August | 0.925015E+09 | 793.52 | 01-AUG-07:10 | 0.205169E+10 | 1392.34 | 01-AUG-07:10 |
September | 0.865179E+09 | 947.51 | 13-SEP-15:39 | 0.190321E+10 | 1392.34 | 01-SEP-07:10 |
October | 0.935136E+09 | 1667.75 | 31-OCT-07:10 | 0.197228E+10 | 1392.34 | 02-OCT-07:10 |
November | 0.102542E+10 | 1667.75 | 01-NOV-07:10 | 0.192889E+10 | 1392.34 | 01-NOV-07:10 |
December | 0.107057E+10 | 1667.75 | 01-DEC-16:10 | 0.193926E+10 | 1392.34 | 01-DEC-08:09 |
Annual Sum or Average | 0.111708E+11 | 0.234352E+11 | ||||
Minimum of Months | 0.824127E+09 | 793.52 | 0.178515E+10 | 1392.34 | ||
Maximum of Months | 0.107057E+10 | 1667.75 | 0.205169E+10 | 1392.34 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.158770E+10 | 2587.98 | 02-JAN-16:40 | 0.305983E+10 | 2160.58 | 02-JAN-08:09 |
February | 0.134917E+10 | 2255.25 | 14-FEB-16:49 | 0.277013E+10 | 2160.58 | 01-FEB-08:09 |
March | 0.150997E+10 | 1803.04 | 01-MAR-16:00 | 0.318374E+10 | 2160.58 | 01-MAR-08:09 |
April | 0.132148E+10 | 1803.04 | 10-APR-07:10 | 0.295467E+10 | 2160.58 | 03-APR-07:10 |
May | 0.137659E+10 | 1231.36 | 01-MAY-07:10 | 0.312179E+10 | 2160.58 | 01-MAY-07:10 |
June | 0.135914E+10 | 1470.31 | 13-JUN-07:10 | 0.306585E+10 | 2160.58 | 01-JUN-07:10 |
July | 0.128094E+10 | 1470.31 | 20-JUL-07:10 | 0.300994E+10 | 2160.58 | 03-JUL-07:10 |
August | 0.143640E+10 | 1350.84 | 28-AUG-07:10 | 0.318374E+10 | 2160.58 | 01-AUG-07:10 |
September | 0.133700E+10 | 1803.04 | 21-SEP-07:10 | 0.295333E+10 | 2160.58 | 01-SEP-07:10 |
October | 0.143656E+10 | 2587.98 | 31-OCT-07:10 | 0.306051E+10 | 2160.58 | 02-OCT-07:10 |
November | 0.155825E+10 | 2587.98 | 01-NOV-07:10 | 0.299318E+10 | 2160.58 | 01-NOV-07:10 |
December | 0.160679E+10 | 2587.98 | 01-DEC-16:30 | 0.300927E+10 | 2160.58 | 01-DEC-08:09 |
Annual Sum or Average | 0.171600E+11 | 0.363660E+11 | ||||
Minimum of Months | 0.128094E+10 | 1231.36 | 0.277013E+10 | 2160.58 | ||
Maximum of Months | 0.160679E+10 | 2587.98 | 0.318374E+10 | 2160.58 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.104479E+10 | 1667.75 | 02-JAN-16:40 | 0.197183E+10 | 1392.33 | 02-JAN-08:09 |
February | 0.880112E+09 | 1453.34 | 14-FEB-08:09 | 0.178514E+10 | 1392.33 | 01-FEB-08:09 |
March | 0.976611E+09 | 1161.92 | 13-MAR-07:10 | 0.205168E+10 | 1392.33 | 01-MAR-08:09 |
April | 0.849998E+09 | 1161.92 | 10-APR-07:10 | 0.190406E+10 | 1392.33 | 03-APR-07:10 |
May | 0.881374E+09 | 870.51 | 15-MAY-08:20 | 0.201175E+10 | 1392.33 | 01-MAY-07:10 |
June | 0.869761E+09 | 947.51 | 13-JUN-07:10 | 0.197570E+10 | 1392.33 | 01-JUN-07:10 |
July | 0.822244E+09 | 947.51 | 20-JUL-07:10 | 0.193968E+10 | 1392.33 | 03-JUL-07:10 |
August | 0.921203E+09 | 870.51 | 23-AUG-07:10 | 0.205168E+10 | 1392.33 | 01-AUG-07:10 |
September | 0.860378E+09 | 1161.92 | 12-SEP-07:10 | 0.190319E+10 | 1392.33 | 01-SEP-07:10 |
October | 0.942337E+09 | 1667.75 | 30-OCT-07:10 | 0.197226E+10 | 1392.33 | 02-OCT-07:10 |
November | 0.101791E+10 | 1667.75 | 01-NOV-07:10 | 0.192888E+10 | 1392.33 | 01-NOV-07:10 |
December | 0.106447E+10 | 1667.75 | 01-DEC-16:30 | 0.193924E+10 | 1392.33 | 01-DEC-08:09 |
Annual Sum or Average | 0.111312E+11 | 0.234351E+11 | ||||
Minimum of Months | 0.822244E+09 | 870.51 | 0.178514E+10 | 1392.33 | ||
Maximum of Months | 0.106447E+10 | 1667.75 | 0.205168E+10 | 1392.33 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.166426E+10 | 2587.92 | 02-JAN-16:19 | 0.305979E+10 | 2160.55 | 02-JAN-08:09 |
February | 0.139499E+10 | 2255.20 | 01-FEB-16:00 | 0.277008E+10 | 2160.55 | 01-FEB-08:09 |
March | 0.152050E+10 | 1803.00 | 01-MAR-16:49 | 0.318369E+10 | 2160.55 | 01-MAR-08:09 |
April | 0.132038E+10 | 1803.00 | 10-APR-07:10 | 0.295462E+10 | 2160.55 | 03-APR-07:10 |
May | 0.136493E+10 | 1231.33 | 01-MAY-07:10 | 0.312174E+10 | 2160.55 | 01-MAY-07:10 |
June | 0.134699E+10 | 1350.81 | 05-JUN-07:10 | 0.306580E+10 | 2160.55 | 01-JUN-07:10 |
July | 0.127196E+10 | 1350.81 | 20-JUL-07:10 | 0.300989E+10 | 2160.55 | 03-JUL-07:10 |
August | 0.142739E+10 | 1350.81 | 31-AUG-07:10 | 0.318369E+10 | 2160.55 | 01-AUG-07:10 |
September | 0.134089E+10 | 1803.00 | 21-SEP-07:10 | 0.295328E+10 | 2160.55 | 01-SEP-07:10 |
October | 0.147234E+10 | 2587.92 | 30-OCT-07:10 | 0.306046E+10 | 2160.55 | 02-OCT-07:10 |
November | 0.161355E+10 | 2587.92 | 01-NOV-07:10 | 0.299314E+10 | 2160.55 | 01-NOV-07:10 |
December | 0.171000E+10 | 2587.92 | 01-DEC-16:10 | 0.300922E+10 | 2160.55 | 01-DEC-08:09 |
Annual Sum or Average | 0.174482E+11 | 0.363654E+11 | ||||
Minimum of Months | 0.127196E+10 | 1231.33 | 0.277008E+10 | 2160.55 | ||
Maximum of Months | 0.171000E+10 | 2587.92 | 0.318369E+10 | 2160.55 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.104672E+10 | 1667.75 | 02-JAN-16:19 | 0.197184E+10 | 1392.34 | 02-JAN-08:09 |
February | 0.884646E+09 | 1453.34 | 01-FEB-16:00 | 0.178515E+10 | 1392.34 | 01-FEB-08:09 |
March | 0.976021E+09 | 1161.92 | 01-MAR-16:40 | 0.205169E+10 | 1392.34 | 01-MAR-08:09 |
April | 0.849832E+09 | 947.51 | 10-APR-07:10 | 0.190407E+10 | 1392.34 | 03-APR-07:10 |
May | 0.886612E+09 | 870.51 | 09-MAY-15:20 | 0.201177E+10 | 1392.34 | 01-MAY-07:10 |
June | 0.873576E+09 | 870.51 | 09-JUN-15:50 | 0.197572E+10 | 1392.34 | 01-JUN-07:10 |
July | 0.823561E+09 | 870.51 | 20-JUL-07:10 | 0.193969E+10 | 1392.34 | 03-JUL-07:10 |
August | 0.924481E+09 | 793.52 | 01-AUG-07:10 | 0.205169E+10 | 1392.34 | 01-AUG-07:10 |
September | 0.863724E+09 | 947.51 | 13-SEP-15:50 | 0.190321E+10 | 1392.34 | 01-SEP-07:10 |
October | 0.934043E+09 | 1667.75 | 31-OCT-07:10 | 0.197228E+10 | 1392.34 | 02-OCT-07:10 |
November | 0.102284E+10 | 1667.75 | 01-NOV-07:10 | 0.192889E+10 | 1392.34 | 01-NOV-07:10 |
December | 0.106660E+10 | 1667.75 | 01-DEC-16:10 | 0.193926E+10 | 1392.34 | 01-DEC-08:09 |
Annual Sum or Average | 0.111527E+11 | 0.234352E+11 | ||||
Minimum of Months | 0.823561E+09 | 793.52 | 0.178515E+10 | 1392.34 | ||
Maximum of Months | 0.106660E+10 | 1667.75 | 0.205169E+10 | 1392.34 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.158657E+10 | 2587.98 | 02-JAN-16:40 | 0.305983E+10 | 2160.58 | 02-JAN-08:09 |
February | 0.134530E+10 | 2255.25 | 14-FEB-16:49 | 0.277013E+10 | 2160.58 | 01-FEB-08:09 |
March | 0.150872E+10 | 1803.04 | 01-MAR-16:00 | 0.318374E+10 | 2160.58 | 01-MAR-08:09 |
April | 0.131876E+10 | 1803.04 | 10-APR-07:10 | 0.295467E+10 | 2160.58 | 03-APR-07:10 |
May | 0.137571E+10 | 1231.36 | 01-MAY-07:10 | 0.312179E+10 | 2160.58 | 01-MAY-07:10 |
June | 0.135807E+10 | 1470.31 | 13-JUN-07:10 | 0.306585E+10 | 2160.58 | 01-JUN-07:10 |
July | 0.127992E+10 | 1470.31 | 20-JUL-07:10 | 0.300994E+10 | 2160.58 | 03-JUL-07:10 |
August | 0.143533E+10 | 1350.84 | 31-AUG-07:10 | 0.318374E+10 | 2160.58 | 01-AUG-07:10 |
September | 0.133572E+10 | 1803.04 | 21-SEP-07:10 | 0.295333E+10 | 2160.58 | 01-SEP-07:10 |
October | 0.143536E+10 | 2587.98 | 31-OCT-07:10 | 0.306051E+10 | 2160.58 | 02-OCT-07:10 |
November | 0.155711E+10 | 2587.98 | 01-NOV-07:10 | 0.299318E+10 | 2160.58 | 01-NOV-07:10 |
December | 0.160346E+10 | 2587.98 | 01-DEC-16:30 | 0.300927E+10 | 2160.58 | 01-DEC-08:09 |
Annual Sum or Average | 0.171400E+11 | 0.363660E+11 | ||||
Minimum of Months | 0.127992E+10 | 1231.36 | 0.277013E+10 | 2160.58 | ||
Maximum of Months | 0.160346E+10 | 2587.98 | 0.318374E+10 | 2160.58 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.104217E+10 | 1667.75 | 02-JAN-16:40 | 0.197183E+10 | 1392.33 | 02-JAN-08:09 |
February | 0.878318E+09 | 1453.34 | 14-FEB-08:09 | 0.178514E+10 | 1392.33 | 01-FEB-08:09 |
March | 0.975279E+09 | 1161.92 | 13-MAR-07:10 | 0.205168E+10 | 1392.33 | 01-MAR-08:09 |
April | 0.848577E+09 | 1161.92 | 10-APR-07:10 | 0.190406E+10 | 1392.33 | 03-APR-07:10 |
May | 0.880717E+09 | 870.51 | 15-MAY-08:30 | 0.201175E+10 | 1392.33 | 01-MAY-07:10 |
June | 0.868973E+09 | 947.51 | 13-JUN-07:10 | 0.197570E+10 | 1392.33 | 01-JUN-07:10 |
July | 0.821305E+09 | 947.51 | 20-JUL-07:10 | 0.193968E+10 | 1392.33 | 03-JUL-07:10 |
August | 0.920617E+09 | 870.51 | 23-AUG-07:10 | 0.205168E+10 | 1392.33 | 01-AUG-07:10 |
September | 0.859385E+09 | 1161.92 | 21-SEP-07:10 | 0.190319E+10 | 1392.33 | 01-SEP-07:10 |
October | 0.940481E+09 | 1667.75 | 30-OCT-07:10 | 0.197226E+10 | 1392.33 | 02-OCT-07:10 |
November | 0.101601E+10 | 1667.75 | 01-NOV-07:10 | 0.192888E+10 | 1392.33 | 01-NOV-07:10 |
December | 0.106163E+10 | 1667.75 | 01-DEC-16:30 | 0.193924E+10 | 1392.33 | 01-DEC-08:09 |
Annual Sum or Average | 0.111135E+11 | 0.234351E+11 | ||||
Minimum of Months | 0.821305E+09 | 870.51 | 0.178514E+10 | 1392.33 | ||
Maximum of Months | 0.106163E+10 | 1667.75 | 0.205168E+10 | 1392.33 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.166419E+10 | 2587.92 | 02-JAN-16:19 | 0.305979E+10 | 2160.55 | 02-JAN-08:09 |
February | 0.139478E+10 | 2255.20 | 01-FEB-16:00 | 0.277008E+10 | 2160.55 | 01-FEB-08:09 |
March | 0.152027E+10 | 1803.00 | 01-MAR-16:49 | 0.318369E+10 | 2160.55 | 01-MAR-08:09 |
April | 0.132038E+10 | 1803.00 | 10-APR-07:10 | 0.295462E+10 | 2160.55 | 03-APR-07:10 |
May | 0.136493E+10 | 1231.33 | 01-MAY-07:10 | 0.312174E+10 | 2160.55 | 01-MAY-07:10 |
June | 0.134699E+10 | 1350.81 | 05-JUN-07:10 | 0.306580E+10 | 2160.55 | 01-JUN-07:10 |
July | 0.127187E+10 | 1350.81 | 20-JUL-07:10 | 0.300989E+10 | 2160.55 | 03-JUL-07:10 |
August | 0.142732E+10 | 1350.81 | 31-AUG-07:10 | 0.318369E+10 | 2160.55 | 01-AUG-07:10 |
September | 0.134058E+10 | 1803.00 | 21-SEP-07:10 | 0.295328E+10 | 2160.55 | 01-SEP-07:10 |
October | 0.147223E+10 | 2587.92 | 30-OCT-07:10 | 0.306046E+10 | 2160.55 | 02-OCT-07:10 |
November | 0.161313E+10 | 2587.92 | 01-NOV-07:10 | 0.299314E+10 | 2160.55 | 01-NOV-07:10 |
December | 0.170954E+10 | 2587.92 | 01-DEC-16:10 | 0.300922E+10 | 2160.55 | 01-DEC-08:09 |
Annual Sum or Average | 0.174462E+11 | 0.363654E+11 | ||||
Minimum of Months | 0.127187E+10 | 1231.33 | 0.277008E+10 | 2160.55 | ||
Maximum of Months | 0.170954E+10 | 2587.92 | 0.318369E+10 | 2160.55 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.104671E+10 | 1667.75 | 02-JAN-16:19 | 0.197184E+10 | 1392.34 | 02-JAN-08:09 |
February | 0.884553E+09 | 1453.34 | 01-FEB-16:00 | 0.178515E+10 | 1392.34 | 01-FEB-08:09 |
March | 0.975944E+09 | 1161.92 | 01-MAR-16:40 | 0.205169E+10 | 1392.34 | 01-MAR-08:09 |
April | 0.849822E+09 | 947.51 | 10-APR-07:10 | 0.190407E+10 | 1392.34 | 03-APR-07:10 |
May | 0.886540E+09 | 870.51 | 09-MAY-15:20 | 0.201177E+10 | 1392.34 | 01-MAY-07:10 |
June | 0.873561E+09 | 870.51 | 09-JUN-15:50 | 0.197572E+10 | 1392.34 | 01-JUN-07:10 |
July | 0.823561E+09 | 870.51 | 20-JUL-07:10 | 0.193969E+10 | 1392.34 | 03-JUL-07:10 |
August | 0.924481E+09 | 793.52 | 01-AUG-07:10 | 0.205169E+10 | 1392.34 | 01-AUG-07:10 |
September | 0.863668E+09 | 947.51 | 13-SEP-15:50 | 0.190321E+10 | 1392.34 | 01-SEP-07:10 |
October | 0.933946E+09 | 1667.75 | 31-OCT-07:10 | 0.197228E+10 | 1392.34 | 02-OCT-07:10 |
November | 0.102284E+10 | 1667.75 | 01-NOV-07:10 | 0.192889E+10 | 1392.34 | 01-NOV-07:10 |
December | 0.106647E+10 | 1667.75 | 01-DEC-16:10 | 0.193926E+10 | 1392.34 | 01-DEC-08:09 |
Annual Sum or Average | 0.111521E+11 | 0.234352E+11 | ||||
Minimum of Months | 0.823561E+09 | 793.52 | 0.178515E+10 | 1392.34 | ||
Maximum of Months | 0.106647E+10 | 1667.75 | 0.205169E+10 | 1392.34 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.158650E+10 | 2587.98 | 02-JAN-16:40 | 0.305983E+10 | 2160.58 | 02-JAN-08:09 |
February | 0.134524E+10 | 2255.25 | 14-FEB-16:49 | 0.277013E+10 | 2160.58 | 01-FEB-08:09 |
March | 0.150854E+10 | 1803.04 | 01-MAR-16:00 | 0.318374E+10 | 2160.58 | 01-MAR-08:09 |
April | 0.131864E+10 | 1803.04 | 10-APR-07:10 | 0.295467E+10 | 2160.58 | 03-APR-07:10 |
May | 0.137566E+10 | 1231.36 | 01-MAY-07:10 | 0.312179E+10 | 2160.58 | 01-MAY-07:10 |
June | 0.135807E+10 | 1470.31 | 13-JUN-07:10 | 0.306585E+10 | 2160.58 | 01-JUN-07:10 |
July | 0.127979E+10 | 1470.31 | 20-JUL-07:10 | 0.300994E+10 | 2160.58 | 03-JUL-07:10 |
August | 0.143533E+10 | 1350.84 | 31-AUG-07:10 | 0.318374E+10 | 2160.58 | 01-AUG-07:10 |
September | 0.133553E+10 | 1803.04 | 21-SEP-07:10 | 0.295333E+10 | 2160.58 | 01-SEP-07:10 |
October | 0.143532E+10 | 2587.98 | 31-OCT-07:10 | 0.306051E+10 | 2160.58 | 02-OCT-07:10 |
November | 0.155663E+10 | 2587.98 | 01-NOV-07:10 | 0.299318E+10 | 2160.58 | 01-NOV-07:10 |
December | 0.160436E+10 | 2587.98 | 01-DEC-16:30 | 0.300927E+10 | 2160.58 | 01-DEC-08:09 |
Annual Sum or Average | 0.171396E+11 | 0.363660E+11 | ||||
Minimum of Months | 0.127979E+10 | 1231.36 | 0.277013E+10 | 2160.58 | ||
Maximum of Months | 0.160436E+10 | 2587.98 | 0.318374E+10 | 2160.58 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.104180E+10 | 1667.75 | 02-JAN-16:40 | 0.197183E+10 | 1392.33 | 02-JAN-08:09 |
February | 0.878311E+09 | 1453.34 | 14-FEB-08:09 | 0.178514E+10 | 1392.33 | 01-FEB-08:09 |
March | 0.975147E+09 | 1161.92 | 13-MAR-07:10 | 0.205168E+10 | 1392.33 | 01-MAR-08:09 |
April | 0.848577E+09 | 1161.92 | 10-APR-07:10 | 0.190406E+10 | 1392.33 | 03-APR-07:10 |
May | 0.880653E+09 | 870.51 | 15-MAY-08:30 | 0.201175E+10 | 1392.33 | 01-MAY-07:10 |
June | 0.868968E+09 | 947.51 | 13-JUN-07:10 | 0.197570E+10 | 1392.33 | 01-JUN-07:10 |
July | 0.821279E+09 | 947.51 | 20-JUL-07:10 | 0.193968E+10 | 1392.33 | 03-JUL-07:10 |
August | 0.920558E+09 | 870.51 | 23-AUG-07:10 | 0.205168E+10 | 1392.33 | 01-AUG-07:10 |
September | 0.859365E+09 | 1161.92 | 21-SEP-07:10 | 0.190319E+10 | 1392.33 | 01-SEP-07:10 |
October | 0.940389E+09 | 1667.75 | 30-OCT-07:10 | 0.197226E+10 | 1392.33 | 02-OCT-07:10 |
November | 0.101598E+10 | 1667.75 | 01-NOV-07:10 | 0.192888E+10 | 1392.33 | 01-NOV-07:10 |
December | 0.106140E+10 | 1667.75 | 01-DEC-16:30 | 0.193924E+10 | 1392.33 | 01-DEC-08:09 |
Annual Sum or Average | 0.111124E+11 | 0.234351E+11 | ||||
Minimum of Months | 0.821279E+09 | 870.51 | 0.178514E+10 | 1392.33 | ||
Maximum of Months | 0.106140E+10 | 1667.75 | 0.205168E+10 | 1392.33 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.553024E+09 | 578.72 | 02-JAN-08:09 | 0.521915E+10 | 1948.61 | 01-JAN-00:10 |
February | 0.501634E+09 | 578.72 | 01-FEB-08:09 | 0.942813E+10 | 3897.21 | 01-FEB-00:10 |
March | 0.596080E+09 | 578.72 | 01-MAR-08:09 | 0.156645E+11 | 7794.42 | 31-MAR-23:10 |
April | 0.532421E+09 | 578.72 | 03-APR-07:10 | 0.201821E+11 | 7794.42 | 01-APR-00:10 |
May | 0.574552E+09 | 578.72 | 01-MAY-07:10 | 0.522616E+10 | 3897.21 | 31-MAY-23:10 |
June | 0.571774E+09 | 578.72 | 01-JUN-07:10 | 0.101086E+11 | 5845.82 | 30-JUN-23:10 |
July | 0.535199E+09 | 578.72 | 03-JUL-07:10 | 0.156645E+11 | 7794.42 | 31-JUL-23:10 |
August | 0.596080E+09 | 578.72 | 01-AUG-07:10 | 0.208555E+11 | 7794.42 | 01-AUG-00:10 |
September | 0.532421E+09 | 578.72 | 01-SEP-07:10 | 0.505780E+10 | 3897.21 | 30-SEP-23:10 |
October | 0.553024E+09 | 578.72 | 02-OCT-07:10 | 0.104453E+11 | 5845.82 | 31-OCT-23:10 |
November | 0.546542E+09 | 578.72 | 01-NOV-07:10 | 0.151524E+11 | 5845.82 | 01-NOV-00:10 |
December | 0.535199E+09 | 578.72 | 01-DEC-08:09 | 0.208766E+11 | 7794.42 | 01-DEC-00:10 |
Annual Sum or Average | 0.662795E+10 | 0.153881E+12 | ||||
Minimum of Months | 0.501634E+09 | 578.72 | 0.505780E+10 | 1948.61 | ||
Maximum of Months | 0.596080E+09 | 578.72 | 0.208766E+11 | 7794.42 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.553024E+09 | 578.72 | 02-JAN-08:09 | 0.521915E+10 | 1948.61 | 01-JAN-00:10 |
February | 0.501634E+09 | 578.72 | 01-FEB-08:09 | 0.942813E+10 | 3897.21 | 01-FEB-00:10 |
March | 0.596080E+09 | 578.72 | 01-MAR-08:09 | 0.156645E+11 | 7794.42 | 31-MAR-23:10 |
April | 0.532421E+09 | 578.72 | 03-APR-07:10 | 0.201821E+11 | 7794.42 | 01-APR-00:10 |
May | 0.574552E+09 | 578.72 | 01-MAY-07:10 | 0.522616E+10 | 3897.21 | 31-MAY-23:10 |
June | 0.571774E+09 | 578.72 | 01-JUN-07:10 | 0.101086E+11 | 5845.82 | 30-JUN-23:10 |
July | 0.535199E+09 | 578.72 | 03-JUL-07:10 | 0.156645E+11 | 7794.42 | 31-JUL-23:10 |
August | 0.596080E+09 | 578.72 | 01-AUG-07:10 | 0.208555E+11 | 7794.42 | 01-AUG-00:10 |
September | 0.532421E+09 | 578.72 | 01-SEP-07:10 | 0.505780E+10 | 3897.21 | 30-SEP-23:10 |
October | 0.553024E+09 | 578.72 | 02-OCT-07:10 | 0.104453E+11 | 5845.82 | 31-OCT-23:10 |
November | 0.546542E+09 | 578.72 | 01-NOV-07:10 | 0.151524E+11 | 5845.82 | 01-NOV-00:10 |
December | 0.535199E+09 | 578.72 | 01-DEC-08:09 | 0.208766E+11 | 7794.42 | 01-DEC-00:10 |
Annual Sum or Average | 0.662795E+10 | 0.153881E+12 | ||||
Minimum of Months | 0.501634E+09 | 578.72 | 0.505780E+10 | 1948.61 | ||
Maximum of Months | 0.596080E+09 | 578.72 | 0.208766E+11 | 7794.42 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.553024E+09 | 578.72 | 02-JAN-08:09 | 0.521915E+10 | 1948.61 | 01-JAN-00:10 |
February | 0.501634E+09 | 578.72 | 01-FEB-08:09 | 0.942813E+10 | 3897.21 | 01-FEB-00:10 |
March | 0.596080E+09 | 578.72 | 01-MAR-08:09 | 0.156645E+11 | 7794.42 | 31-MAR-23:10 |
April | 0.532421E+09 | 578.72 | 03-APR-07:10 | 0.201821E+11 | 7794.42 | 01-APR-00:10 |
May | 0.574552E+09 | 578.72 | 01-MAY-07:10 | 0.522616E+10 | 3897.21 | 31-MAY-23:10 |
June | 0.571774E+09 | 578.72 | 01-JUN-07:10 | 0.101086E+11 | 5845.82 | 30-JUN-23:10 |
July | 0.535199E+09 | 578.72 | 03-JUL-07:10 | 0.156645E+11 | 7794.42 | 31-JUL-23:10 |
August | 0.596080E+09 | 578.72 | 01-AUG-07:10 | 0.208555E+11 | 7794.42 | 01-AUG-00:10 |
September | 0.532421E+09 | 578.72 | 01-SEP-07:10 | 0.505780E+10 | 3897.21 | 30-SEP-23:10 |
October | 0.553024E+09 | 578.72 | 02-OCT-07:10 | 0.104453E+11 | 5845.82 | 31-OCT-23:10 |
November | 0.546542E+09 | 578.72 | 01-NOV-07:10 | 0.151524E+11 | 5845.82 | 01-NOV-00:10 |
December | 0.535199E+09 | 578.72 | 01-DEC-08:09 | 0.208766E+11 | 7794.42 | 01-DEC-00:10 |
Annual Sum or Average | 0.662795E+10 | 0.153881E+12 | ||||
Minimum of Months | 0.501634E+09 | 578.72 | 0.505780E+10 | 1948.61 | ||
Maximum of Months | 0.596080E+09 | 578.72 | 0.208766E+11 | 7794.42 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.618367E+10 | 6471.01 | 02-JAN-08:09 | 0.254202E+12 | 94908.13 | 01-JAN-00:10 |
February | 0.560905E+10 | 6471.01 | 01-FEB-08:09 | 0.459203E+12 | 189816.26 | 01-FEB-00:10 |
March | 0.666512E+10 | 6471.01 | 01-MAR-08:09 | 0.762947E+12 | 379632.52 | 31-MAR-23:10 |
April | 0.595330E+10 | 6471.01 | 03-APR-07:10 | 0.982982E+12 | 379632.52 | 01-APR-00:10 |
May | 0.642439E+10 | 6471.01 | 01-MAY-07:10 | 0.254544E+12 | 189816.26 | 31-MAY-23:10 |
June | 0.639333E+10 | 6471.01 | 01-JUN-07:10 | 0.492345E+12 | 284724.39 | 30-JUN-23:10 |
July | 0.598436E+10 | 6471.01 | 03-JUL-07:10 | 0.762947E+12 | 379632.52 | 31-JUL-23:10 |
August | 0.666512E+10 | 6471.01 | 01-AUG-07:10 | 0.101578E+13 | 379632.52 | 01-AUG-00:10 |
September | 0.595330E+10 | 6471.01 | 01-SEP-07:10 | 0.246344E+12 | 189816.26 | 30-SEP-23:10 |
October | 0.618367E+10 | 6471.01 | 02-OCT-07:10 | 0.508746E+12 | 284724.39 | 31-OCT-23:10 |
November | 0.611120E+10 | 6471.01 | 01-NOV-07:10 | 0.738006E+12 | 284724.39 | 01-NOV-00:10 |
December | 0.598436E+10 | 6471.01 | 01-DEC-08:09 | 0.101681E+13 | 379632.52 | 01-DEC-00:10 |
Annual Sum or Average | 0.741109E+11 | 0.749486E+13 | ||||
Minimum of Months | 0.560905E+10 | 6471.01 | 0.246344E+12 | 94908.13 | ||
Maximum of Months | 0.666512E+10 | 6471.01 | 0.101681E+13 | 379632.52 |
Report: SpaceGainsMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.133902E+11 | 0.219312E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.121482E+11 | 0.198933E+11 | 0.325565E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.145160E+11 | 0.236388E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.128805E+11 | 0.211142E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.139531E+11 | 0.227850E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.139143E+11 | 0.226748E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.129193E+11 | 0.212244E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.145160E+11 | 0.236388E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.128805E+11 | 0.211142E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.133902E+11 | 0.219312E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.132595E+11 | 0.216742E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.129193E+11 | 0.212244E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.160687E+12 | 0.262844E+12 | 0.424397E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.121482E+11 | 0.198933E+11 | 0.325565E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.145160E+11 | 0.236388E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.120254E+11 | 0.196958E+11 | 0.243681E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.109099E+11 | 0.178655E+11 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.130364E+11 | 0.212293E+11 | 0.253549E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.115676E+11 | 0.189620E+11 | 0.235306E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.125309E+11 | 0.204625E+11 | 0.248615E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.124961E+11 | 0.203636E+11 | 0.244160E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.116025E+11 | 0.190610E+11 | 0.239708E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.130364E+11 | 0.212293E+11 | 0.253549E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.115676E+11 | 0.189620E+11 | 0.235199E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.120254E+11 | 0.196958E+11 | 0.243735E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.119080E+11 | 0.194649E+11 | 0.238373E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.116025E+11 | 0.190610E+11 | 0.239654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.144308E+12 | 0.236053E+12 | 0.289614E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.109099E+11 | 0.178655E+11 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.130364E+11 | 0.212293E+11 | 0.253549E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.120254E+11 | 0.196958E+11 | 0.243680E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.109099E+11 | 0.178655E+11 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.130364E+11 | 0.212293E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.115676E+11 | 0.189620E+11 | 0.235305E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.125309E+11 | 0.204625E+11 | 0.248614E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.124961E+11 | 0.203636E+11 | 0.244159E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.116025E+11 | 0.190610E+11 | 0.239707E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.130364E+11 | 0.212293E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.115676E+11 | 0.189620E+11 | 0.235198E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.120254E+11 | 0.196958E+11 | 0.243734E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.119080E+11 | 0.194649E+11 | 0.238372E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.116025E+11 | 0.190610E+11 | 0.239653E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.144308E+12 | 0.236053E+12 | 0.289613E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.109099E+11 | 0.178655E+11 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.130364E+11 | 0.212293E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.120254E+11 | 0.196958E+11 | 0.243680E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.109099E+11 | 0.178655E+11 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.130364E+11 | 0.212293E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.115676E+11 | 0.189620E+11 | 0.235305E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.125309E+11 | 0.204625E+11 | 0.248614E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.124961E+11 | 0.203636E+11 | 0.244159E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.116025E+11 | 0.190610E+11 | 0.239707E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.130364E+11 | 0.212293E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.115676E+11 | 0.189620E+11 | 0.235198E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.120254E+11 | 0.196958E+11 | 0.243734E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.119080E+11 | 0.194649E+11 | 0.238372E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.116025E+11 | 0.190610E+11 | 0.239653E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.144308E+12 | 0.236053E+12 | 0.289613E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.109099E+11 | 0.178655E+11 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.130364E+11 | 0.212293E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150991E+10 | 0.166983E+10 | 0.305979E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.236180E+10 |
February | 0.136985E+10 | 0.139976E+10 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.179424E+10 |
March | 0.163685E+10 | 0.152300E+10 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.161494E+10 |
April | 0.145243E+10 | 0.132292E+10 | 0.295462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7383301.75 | 0.103531E+10 |
May | 0.157338E+10 | 0.136569E+10 | 0.312174E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2803425.48 | 0.548189E+09 |
June | 0.156900E+10 | 0.134831E+10 | 0.306580E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 35729220.12 | 0.316631E+09 |
July | 0.145680E+10 | 0.127316E+10 | 0.300989E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12336814.06 | 0.221199E+09 |
August | 0.163685E+10 | 0.142863E+10 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13587113.60 | 0.305439E+09 |
September | 0.145243E+10 | 0.134363E+10 | 0.295328E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10401342.79 | 0.499606E+09 |
October | 0.150991E+10 | 0.147648E+10 | 0.306046E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.100931E+10 |
November | 0.149516E+10 | 0.161916E+10 | 0.299314E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.159588E+10 |
December | 0.145680E+10 | 0.171905E+10 | 0.300922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.206007E+10 |
Annual Sum or Average | 0.181194E+11 | 0.174896E+11 | 0.363654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 82241217.80 | 0.133626E+11 |
Minimum of Months | 0.136985E+10 | 0.127316E+10 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.221199E+09 |
Maximum of Months | 0.163685E+10 | 0.171905E+10 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 35729220.12 | 0.236180E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.104961E+10 | 0.197184E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.157193E+10 |
February | 0.882782E+09 | 0.886186E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.119270E+10 |
March | 0.105485E+10 | 0.977170E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.106719E+10 |
April | 0.936002E+09 | 0.850785E+09 | 0.190407E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6287038.39 | 0.674069E+09 |
May | 0.101394E+10 | 0.887448E+09 | 0.201177E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1870089.34 | 0.363388E+09 |
June | 0.101113E+10 | 0.874159E+09 | 0.197572E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 26166712.80 | 0.203716E+09 |
July | 0.938820E+09 | 0.824127E+09 | 0.193969E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9311224.16 | 0.134451E+09 |
August | 0.105485E+10 | 0.925015E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10099289.55 | 0.183280E+09 |
September | 0.936002E+09 | 0.865179E+09 | 0.190321E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7616511.01 | 0.331643E+09 |
October | 0.973041E+09 | 0.935136E+09 | 0.197228E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.670094E+09 |
November | 0.963541E+09 | 0.102542E+10 | 0.192889E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.104640E+10 |
December | 0.938820E+09 | 0.107057E+10 | 0.193926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.136083E+10 |
Annual Sum or Average | 0.116768E+11 | 0.111708E+11 | 0.234352E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 61350865.25 | 0.879968E+10 |
Minimum of Months | 0.882782E+09 | 0.824127E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.134451E+09 |
Maximum of Months | 0.105485E+10 | 0.107057E+10 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 26166712.80 | 0.157193E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150994E+10 | 0.158770E+10 | 0.305983E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.237945E+10 |
February | 0.136988E+10 | 0.134917E+10 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.181494E+10 |
March | 0.163688E+10 | 0.150997E+10 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.162125E+10 |
April | 0.145246E+10 | 0.132148E+10 | 0.295467E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6534538.57 | 0.102718E+10 |
May | 0.157341E+10 | 0.137659E+10 | 0.312179E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2802968.91 | 0.545909E+09 |
June | 0.156904E+10 | 0.135914E+10 | 0.306585E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 35883505.95 | 0.308484E+09 |
July | 0.145684E+10 | 0.128094E+10 | 0.300994E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12045505.79 | 0.215390E+09 |
August | 0.163688E+10 | 0.143640E+10 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13491503.60 | 0.305015E+09 |
September | 0.145246E+10 | 0.133700E+10 | 0.295333E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8778837.20 | 0.516067E+09 |
October | 0.150994E+10 | 0.143656E+10 | 0.306051E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.102897E+10 |
November | 0.149520E+10 | 0.155825E+10 | 0.299318E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.159145E+10 |
December | 0.145684E+10 | 0.160679E+10 | 0.300927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.207572E+10 |
Annual Sum or Average | 0.181198E+11 | 0.171600E+11 | 0.363660E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 79536860.03 | 0.134298E+11 |
Minimum of Months | 0.136988E+10 | 0.128094E+10 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.215390E+09 |
Maximum of Months | 0.163688E+10 | 0.160679E+10 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 35883505.95 | 0.237945E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.104479E+10 | 0.197183E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.162064E+10 |
February | 0.882782E+09 | 0.880112E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.125692E+10 |
March | 0.105485E+10 | 0.976611E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.115926E+10 |
April | 0.936002E+09 | 0.849998E+09 | 0.190406E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3914855.19 | 0.771940E+09 |
May | 0.101394E+10 | 0.881374E+09 | 0.201175E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1869527.65 | 0.391973E+09 |
June | 0.101113E+10 | 0.869761E+09 | 0.197570E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22209355.64 | 0.235010E+09 |
July | 0.938820E+09 | 0.822244E+09 | 0.193968E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7631317.91 | 0.173159E+09 |
August | 0.105485E+10 | 0.921203E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8955105.25 | 0.239852E+09 |
September | 0.936002E+09 | 0.860378E+09 | 0.190319E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6075485.96 | 0.362520E+09 |
October | 0.973041E+09 | 0.942337E+09 | 0.197226E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.726143E+09 |
November | 0.963541E+09 | 0.101791E+10 | 0.192888E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.113317E+10 |
December | 0.938820E+09 | 0.106447E+10 | 0.193924E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.146537E+10 |
Annual Sum or Average | 0.116768E+11 | 0.111312E+11 | 0.234351E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 50655647.61 | 0.953595E+10 |
Minimum of Months | 0.882782E+09 | 0.822244E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.173159E+09 |
Maximum of Months | 0.105485E+10 | 0.106447E+10 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22209355.64 | 0.162064E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150991E+10 | 0.166426E+10 | 0.305979E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.525644E+10 |
February | 0.136985E+10 | 0.139499E+10 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.386090E+10 |
March | 0.163685E+10 | 0.152050E+10 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.333580E+10 |
April | 0.145243E+10 | 0.132038E+10 | 0.295462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20456662.22 | 0.207601E+10 |
May | 0.157338E+10 | 0.136493E+10 | 0.312174E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6293043.30 | 0.116913E+10 |
June | 0.156900E+10 | 0.134699E+10 | 0.306580E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 83606693.39 | 0.690439E+09 |
July | 0.145680E+10 | 0.127196E+10 | 0.300989E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 29088038.46 | 0.499967E+09 |
August | 0.163685E+10 | 0.142739E+10 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 31913502.12 | 0.673679E+09 |
September | 0.145243E+10 | 0.134089E+10 | 0.295328E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 26937160.77 | 0.104404E+10 |
October | 0.150991E+10 | 0.147234E+10 | 0.306046E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.199028E+10 |
November | 0.149516E+10 | 0.161355E+10 | 0.299314E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.330370E+10 |
December | 0.145680E+10 | 0.171000E+10 | 0.300922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.442119E+10 |
Annual Sum or Average | 0.181194E+11 | 0.174482E+11 | 0.363654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.198295E+09 | 0.283216E+11 |
Minimum of Months | 0.136985E+10 | 0.127196E+10 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.499967E+09 |
Maximum of Months | 0.163685E+10 | 0.171000E+10 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 83606693.39 | 0.525644E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.715730E+09 | 0.104672E+10 | 0.197184E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.352506E+10 |
February | 0.649041E+09 | 0.884646E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.259493E+10 |
March | 0.773965E+09 | 0.976021E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.225755E+10 |
April | 0.688021E+09 | 0.849832E+09 | 0.190407E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14222559.77 | 0.143140E+10 |
May | 0.744847E+09 | 0.886612E+09 | 0.201177E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4209982.94 | 0.799075E+09 |
June | 0.742030E+09 | 0.873576E+09 | 0.197572E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 57902260.00 | 0.464012E+09 |
July | 0.690839E+09 | 0.823561E+09 | 0.193969E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19109421.35 | 0.335009E+09 |
August | 0.773965E+09 | 0.924481E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21816579.79 | 0.449481E+09 |
September | 0.688021E+09 | 0.863724E+09 | 0.190321E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17247341.20 | 0.722427E+09 |
October | 0.715730E+09 | 0.934043E+09 | 0.197228E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.137868E+10 |
November | 0.708685E+09 | 0.102284E+10 | 0.192889E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.221673E+10 |
December | 0.690839E+09 | 0.106660E+10 | 0.193926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.296689E+10 |
Annual Sum or Average | 0.858171E+10 | 0.111527E+11 | 0.234352E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.134508E+09 | 0.191412E+11 |
Minimum of Months | 0.649041E+09 | 0.823561E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.335009E+09 |
Maximum of Months | 0.773965E+09 | 0.106660E+10 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 57902260.00 | 0.352506E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150994E+10 | 0.158657E+10 | 0.305983E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.536401E+10 |
February | 0.136988E+10 | 0.134530E+10 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.403248E+10 |
March | 0.163688E+10 | 0.150872E+10 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.352044E+10 |
April | 0.145246E+10 | 0.131876E+10 | 0.295467E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14589955.48 | 0.221895E+10 |
May | 0.157341E+10 | 0.137571E+10 | 0.312179E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6292623.53 | 0.121217E+10 |
June | 0.156904E+10 | 0.135807E+10 | 0.306585E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 81681472.70 | 0.691548E+09 |
July | 0.145684E+10 | 0.127992E+10 | 0.300994E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 26465082.62 | 0.507811E+09 |
August | 0.163688E+10 | 0.143533E+10 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 30497123.43 | 0.713525E+09 |
September | 0.145246E+10 | 0.133572E+10 | 0.295333E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19298504.09 | 0.115666E+10 |
October | 0.150994E+10 | 0.143536E+10 | 0.306051E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.224248E+10 |
November | 0.149520E+10 | 0.155711E+10 | 0.299318E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.347009E+10 |
December | 0.145684E+10 | 0.160346E+10 | 0.300927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.459062E+10 |
Annual Sum or Average | 0.181198E+11 | 0.171400E+11 | 0.363660E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.178825E+09 | 0.297208E+11 |
Minimum of Months | 0.136988E+10 | 0.127992E+10 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.507811E+09 |
Maximum of Months | 0.163688E+10 | 0.160346E+10 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 81681472.70 | 0.536401E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.104217E+10 | 0.197183E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.353848E+10 |
February | 0.882782E+09 | 0.878318E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.264221E+10 |
March | 0.105485E+10 | 0.975279E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.230028E+10 |
April | 0.936002E+09 | 0.848577E+09 | 0.190406E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9427879.57 | 0.149805E+10 |
May | 0.101394E+10 | 0.880717E+09 | 0.201175E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4251986.76 | 0.824029E+09 |
June | 0.101113E+10 | 0.868973E+09 | 0.197570E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 53634298.25 | 0.486880E+09 |
July | 0.938820E+09 | 0.821305E+09 | 0.193968E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18184327.98 | 0.374925E+09 |
August | 0.105485E+10 | 0.920617E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20938393.81 | 0.499173E+09 |
September | 0.936002E+09 | 0.859385E+09 | 0.190319E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14978668.60 | 0.752832E+09 |
October | 0.973041E+09 | 0.940481E+09 | 0.197226E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.140358E+10 |
November | 0.963541E+09 | 0.101601E+10 | 0.192888E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.225419E+10 |
December | 0.938820E+09 | 0.106163E+10 | 0.193924E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.299750E+10 |
Annual Sum or Average | 0.116768E+11 | 0.111135E+11 | 0.234351E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.121416E+09 | 0.195721E+11 |
Minimum of Months | 0.882782E+09 | 0.821305E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.374925E+09 |
Maximum of Months | 0.105485E+10 | 0.106163E+10 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 53634298.25 | 0.353848E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150991E+10 | 0.166419E+10 | 0.305979E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.647348E+10 |
February | 0.136985E+10 | 0.139478E+10 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.473884E+10 |
March | 0.163685E+10 | 0.152027E+10 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.398261E+10 |
April | 0.145243E+10 | 0.132038E+10 | 0.295462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22535963.03 | 0.243342E+10 |
May | 0.157338E+10 | 0.136493E+10 | 0.312174E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7470554.70 | 0.137801E+10 |
June | 0.156900E+10 | 0.134699E+10 | 0.306580E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 99207644.59 | 0.820700E+09 |
July | 0.145680E+10 | 0.127187E+10 | 0.300989E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 34219585.49 | 0.606924E+09 |
August | 0.163685E+10 | 0.142732E+10 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 38047450.85 | 0.809935E+09 |
September | 0.145243E+10 | 0.134058E+10 | 0.295328E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 33064741.53 | 0.121038E+10 |
October | 0.150991E+10 | 0.147223E+10 | 0.306046E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.220869E+10 |
November | 0.149516E+10 | 0.161313E+10 | 0.299314E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.398235E+10 |
December | 0.145680E+10 | 0.170954E+10 | 0.300922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.542404E+10 |
Annual Sum or Average | 0.181194E+11 | 0.174462E+11 | 0.363654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.234546E+09 | 0.340694E+11 |
Minimum of Months | 0.136985E+10 | 0.127187E+10 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.606924E+09 |
Maximum of Months | 0.163685E+10 | 0.170954E+10 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 99207644.59 | 0.647348E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.104671E+10 | 0.197184E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.435731E+10 |
February | 0.882782E+09 | 0.884553E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.317710E+10 |
March | 0.105485E+10 | 0.975944E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.269756E+10 |
April | 0.936002E+09 | 0.849822E+09 | 0.190407E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15517462.97 | 0.169823E+10 |
May | 0.101394E+10 | 0.886540E+09 | 0.201177E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4980904.39 | 0.958688E+09 |
June | 0.101113E+10 | 0.873561E+09 | 0.197572E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 66615079.32 | 0.558457E+09 |
July | 0.938820E+09 | 0.823561E+09 | 0.193969E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21736464.78 | 0.413652E+09 |
August | 0.105485E+10 | 0.924481E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 25171161.66 | 0.548705E+09 |
September | 0.936002E+09 | 0.863668E+09 | 0.190321E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19291121.29 | 0.855470E+09 |
October | 0.973041E+09 | 0.933946E+09 | 0.197228E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.154696E+10 |
November | 0.963541E+09 | 0.102284E+10 | 0.192889E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.267047E+10 |
December | 0.938820E+09 | 0.106647E+10 | 0.193926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.363951E+10 |
Annual Sum or Average | 0.116768E+11 | 0.111521E+11 | 0.234352E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.153312E+09 | 0.231221E+11 |
Minimum of Months | 0.882782E+09 | 0.823561E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.413652E+09 |
Maximum of Months | 0.105485E+10 | 0.106647E+10 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 66615079.32 | 0.435731E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150994E+10 | 0.158650E+10 | 0.305983E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.658540E+10 |
February | 0.136988E+10 | 0.134524E+10 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.487353E+10 |
March | 0.163688E+10 | 0.150854E+10 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.418488E+10 |
April | 0.145246E+10 | 0.131864E+10 | 0.295467E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16794689.13 | 0.261783E+10 |
May | 0.157341E+10 | 0.137566E+10 | 0.312179E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7470349.28 | 0.144055E+10 |
June | 0.156904E+10 | 0.135807E+10 | 0.306585E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 96550353.62 | 0.824563E+09 |
July | 0.145684E+10 | 0.127979E+10 | 0.300994E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 31131633.96 | 0.619641E+09 |
August | 0.163688E+10 | 0.143533E+10 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 36379067.64 | 0.863998E+09 |
September | 0.145246E+10 | 0.133553E+10 | 0.295333E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23146781.39 | 0.136410E+10 |
October | 0.150994E+10 | 0.143532E+10 | 0.306051E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.253932E+10 |
November | 0.149520E+10 | 0.155663E+10 | 0.299318E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.412882E+10 |
December | 0.145684E+10 | 0.160436E+10 | 0.300927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.556024E+10 |
Annual Sum or Average | 0.181198E+11 | 0.171396E+11 | 0.363660E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.211473E+09 | 0.356029E+11 |
Minimum of Months | 0.136988E+10 | 0.127979E+10 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.619641E+09 |
Maximum of Months | 0.163688E+10 | 0.160436E+10 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 96550353.62 | 0.658540E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.104180E+10 | 0.197183E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.437113E+10 |
February | 0.882782E+09 | 0.878311E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.321649E+10 |
March | 0.105485E+10 | 0.975147E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.275560E+10 |
April | 0.936002E+09 | 0.848577E+09 | 0.190406E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11120654.71 | 0.177817E+10 |
May | 0.101394E+10 | 0.880653E+09 | 0.201175E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5029010.66 | 0.984355E+09 |
June | 0.101113E+10 | 0.868968E+09 | 0.197570E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 64063973.25 | 0.585189E+09 |
July | 0.938820E+09 | 0.821279E+09 | 0.193968E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21831071.89 | 0.458788E+09 |
August | 0.105485E+10 | 0.920558E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 25169942.28 | 0.606532E+09 |
September | 0.936002E+09 | 0.859365E+09 | 0.190319E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18373524.64 | 0.892654E+09 |
October | 0.973041E+09 | 0.940389E+09 | 0.197226E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.160430E+10 |
November | 0.963541E+09 | 0.101598E+10 | 0.192888E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.270858E+10 |
December | 0.938820E+09 | 0.106140E+10 | 0.193924E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.366385E+10 |
Annual Sum or Average | 0.116768E+11 | 0.111124E+11 | 0.234351E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.145588E+09 | 0.236256E+11 |
Minimum of Months | 0.882782E+09 | 0.821279E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.458788E+09 |
Maximum of Months | 0.105485E+10 | 0.106140E+10 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 64063973.25 | 0.437113E+10 |
Report: SpaceGainsMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.174411E+09 | 0.553024E+09 | 0.521915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.158233E+09 | 0.501634E+09 | 0.942813E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.189074E+09 | 0.596080E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.167772E+09 | 0.532421E+09 | 0.201821E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.181743E+09 | 0.574552E+09 | 0.522616E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.181238E+09 | 0.571774E+09 | 0.101086E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.168277E+09 | 0.535199E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.189074E+09 | 0.596080E+09 | 0.208555E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.167772E+09 | 0.532421E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.174411E+09 | 0.553024E+09 | 0.104453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.172708E+09 | 0.546542E+09 | 0.151524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.168277E+09 | 0.535199E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.209299E+10 | 0.662795E+10 | 0.153881E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.158233E+09 | 0.501634E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.189074E+09 | 0.596080E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.174411E+09 | 0.553024E+09 | 0.521915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.158233E+09 | 0.501634E+09 | 0.942813E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.189074E+09 | 0.596080E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.167772E+09 | 0.532421E+09 | 0.201821E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.181743E+09 | 0.574552E+09 | 0.522616E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.181238E+09 | 0.571774E+09 | 0.101086E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.168277E+09 | 0.535199E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.189074E+09 | 0.596080E+09 | 0.208555E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.167772E+09 | 0.532421E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.174411E+09 | 0.553024E+09 | 0.104453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.172708E+09 | 0.546542E+09 | 0.151524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.168277E+09 | 0.535199E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.209299E+10 | 0.662795E+10 | 0.153881E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.158233E+09 | 0.501634E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.189074E+09 | 0.596080E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.174411E+09 | 0.553024E+09 | 0.521915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.158233E+09 | 0.501634E+09 | 0.942813E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.189074E+09 | 0.596080E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.167772E+09 | 0.532421E+09 | 0.201821E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.181743E+09 | 0.574552E+09 | 0.522616E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.181238E+09 | 0.571774E+09 | 0.101086E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.168277E+09 | 0.535199E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.189074E+09 | 0.596080E+09 | 0.208555E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.167772E+09 | 0.532421E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.174411E+09 | 0.553024E+09 | 0.104453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.172708E+09 | 0.546542E+09 | 0.151524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.168277E+09 | 0.535199E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.209299E+10 | 0.662795E+10 | 0.153881E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.158233E+09 | 0.501634E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.189074E+09 | 0.596080E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.377547E+10 | 0.618367E+10 | 0.254202E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.342526E+10 | 0.560905E+10 | 0.459203E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.409289E+10 | 0.666512E+10 | 0.762947E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.363176E+10 | 0.595330E+10 | 0.982982E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.393418E+10 | 0.642439E+10 | 0.254544E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.392325E+10 | 0.639333E+10 | 0.492345E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.364269E+10 | 0.598436E+10 | 0.762947E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.409289E+10 | 0.666512E+10 | 0.101578E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.363176E+10 | 0.595330E+10 | 0.246344E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.377547E+10 | 0.618367E+10 | 0.508746E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.373861E+10 | 0.611120E+10 | 0.738006E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.364269E+10 | 0.598436E+10 | 0.101681E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.453069E+11 | 0.741109E+11 | 0.749486E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.342526E+10 | 0.560905E+10 | 0.246344E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.409289E+10 | 0.666512E+10 | 0.101681E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.509902E+10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.387566E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.349057E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15260430.05 | 0.223058E+10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4128319.96 | 0.116808E+10 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 75389300.19 | 0.666418E+09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21648351.83 | 0.472779E+09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20912676.38 | 0.662018E+09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18047454.71 | 0.107810E+10 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.218777E+10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.348074E+10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.449187E+10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.155387E+09 | 0.289036E+11 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.472779E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 75389300.19 | 0.509902E+10 |
Report: SpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.854057E+10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.649722E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.576936E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34062091.09 | 0.370388E+10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7645483.75 | 0.201035E+10 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.143171E+09 | 0.115498E+10 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41047708.40 | 0.828876E+09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38956900.57 | 0.115496E+10 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36394818.95 | 0.185302E+10 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.363571E+10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.574056E+10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.740312E+10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.301278E+09 | 0.482926E+11 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.828876E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.143171E+09 | 0.854057E+10 |
Report: SpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.935917E+10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.703171E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.616731E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18167867.11 | 0.392173E+10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5612006.35 | 0.224596E+10 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.106317E+09 | 0.128694E+10 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21702671.97 | 0.957718E+09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30514930.39 | 0.131186E+10 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22858992.01 | 0.198326E+10 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.365393E+10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.600706E+10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.795195E+10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.205174E+09 | 0.518786E+11 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.957718E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.106317E+09 | 0.935917E+10 |
Report: PeakSpaceGainsMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 17832.21 | 02-JAN-10:09 | 22950.34 | 02-JAN-08:09 | 13457.54 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 17832.21 | 01-FEB-10:09 | 22950.34 | 01-FEB-08:09 | 13457.54 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 17832.21 | 01-MAR-10:09 | 22950.34 | 01-MAR-08:09 | 13457.54 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 17832.21 | 03-APR-09:09 | 22950.34 | 03-APR-07:10 | 13457.54 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 17832.21 | 01-MAY-09:09 | 22950.34 | 01-MAY-07:10 | 13457.54 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 17832.21 | 01-JUN-09:09 | 22950.34 | 01-JUN-07:10 | 13457.54 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 17832.21 | 03-JUL-09:09 | 22950.34 | 03-JUL-07:10 | 13457.54 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 17832.21 | 01-AUG-09:09 | 22950.34 | 01-AUG-07:10 | 13457.54 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 17832.21 | 01-SEP-09:09 | 22950.34 | 01-SEP-07:10 | 13457.54 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 17832.21 | 02-OCT-09:09 | 22950.34 | 02-OCT-07:10 | 13457.54 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 17832.21 | 01-NOV-09:09 | 22950.34 | 01-NOV-07:10 | 13457.54 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 17832.21 | 01-DEC-10:09 | 22950.34 | 01-DEC-08:09 | 13457.54 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 17832.21 | 22950.34 | 13457.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 17832.21 | 22950.34 | 13457.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 16014.58 | 02-JAN-10:09 | 20611.01 | 02-JAN-08:09 | 17206.63 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 16014.58 | 01-FEB-10:09 | 20611.01 | 01-FEB-08:09 | 17206.63 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 16014.58 | 01-MAR-10:09 | 20611.01 | 01-MAR-08:09 | 17206.63 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 16014.58 | 03-APR-09:09 | 20611.01 | 03-APR-07:10 | 17206.63 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 16014.58 | 01-MAY-09:09 | 20611.01 | 01-MAY-07:10 | 17206.63 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 16014.58 | 01-JUN-09:09 | 20611.01 | 01-JUN-07:10 | 17206.63 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 16014.58 | 03-JUL-09:09 | 20611.01 | 03-JUL-07:10 | 17206.63 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 16014.58 | 01-AUG-09:09 | 20611.01 | 01-AUG-07:10 | 17206.63 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 16014.58 | 01-SEP-09:09 | 20611.01 | 01-SEP-07:10 | 17206.63 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 16014.58 | 02-OCT-09:09 | 20611.01 | 02-OCT-07:10 | 17206.63 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 16014.58 | 01-NOV-09:09 | 20611.01 | 01-NOV-07:10 | 17206.63 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 16014.58 | 01-DEC-10:09 | 20611.01 | 01-DEC-08:09 | 17206.63 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 16014.58 | 20611.01 | 17206.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 16014.58 | 20611.01 | 17206.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 16014.58 | 02-JAN-10:09 | 20611.01 | 02-JAN-08:09 | 17206.56 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 16014.58 | 01-FEB-10:09 | 20611.01 | 01-FEB-08:09 | 17206.56 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 16014.58 | 01-MAR-10:09 | 20611.01 | 01-MAR-08:09 | 17206.56 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 16014.58 | 03-APR-09:09 | 20611.01 | 03-APR-07:10 | 17206.56 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 16014.58 | 01-MAY-09:09 | 20611.01 | 01-MAY-07:10 | 17206.56 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 16014.58 | 01-JUN-09:09 | 20611.01 | 01-JUN-07:10 | 17206.56 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 16014.58 | 03-JUL-09:09 | 20611.01 | 03-JUL-07:10 | 17206.56 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 16014.58 | 01-AUG-09:09 | 20611.01 | 01-AUG-07:10 | 17206.56 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 16014.58 | 01-SEP-09:09 | 20611.01 | 01-SEP-07:10 | 17206.56 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 16014.58 | 02-OCT-09:09 | 20611.01 | 02-OCT-07:10 | 17206.56 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 16014.58 | 01-NOV-09:09 | 20611.01 | 01-NOV-07:10 | 17206.56 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 16014.58 | 01-DEC-10:09 | 20611.01 | 01-DEC-08:09 | 17206.56 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 16014.58 | 20611.01 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 16014.58 | 20611.01 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 16014.58 | 02-JAN-10:09 | 20611.01 | 02-JAN-08:09 | 17206.56 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 16014.58 | 01-FEB-10:09 | 20611.01 | 01-FEB-08:09 | 17206.56 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 16014.58 | 01-MAR-10:09 | 20611.01 | 01-MAR-08:09 | 17206.56 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 16014.58 | 03-APR-09:09 | 20611.01 | 03-APR-07:10 | 17206.56 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 16014.58 | 01-MAY-09:09 | 20611.01 | 01-MAY-07:10 | 17206.56 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 16014.58 | 01-JUN-09:09 | 20611.01 | 01-JUN-07:10 | 17206.56 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 16014.58 | 03-JUL-09:09 | 20611.01 | 03-JUL-07:10 | 17206.56 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 16014.58 | 01-AUG-09:09 | 20611.01 | 01-AUG-07:10 | 17206.56 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 16014.58 | 01-SEP-09:09 | 20611.01 | 01-SEP-07:10 | 17206.56 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 16014.58 | 02-OCT-09:09 | 20611.01 | 02-OCT-07:10 | 17206.56 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 16014.58 | 01-NOV-09:09 | 20611.01 | 01-NOV-07:10 | 17206.56 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 16014.58 | 01-DEC-10:09 | 20611.01 | 01-DEC-08:09 | 17206.56 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 16014.58 | 20611.01 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 16014.58 | 20611.01 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.79 | 02-JAN-10:09 | 2587.92 | 02-JAN-16:19 | 2160.55 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 4371.69 | 29-JAN-10:51 |
February | 2010.79 | 01-FEB-10:09 | 2255.20 | 01-FEB-16:49 | 2160.55 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 3095.21 | 10-FEB-22:01 |
March | 2010.79 | 01-MAR-10:09 | 1803.00 | 01-MAR-16:49 | 2160.55 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 2788.12 | 12-MAR-15:53 |
April | 2010.79 | 03-APR-09:09 | 1803.00 | 10-APR-07:10 | 2160.55 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 362.52 | 15-APR-17:01 | 2086.78 | 02-APR-23:52 |
May | 2010.79 | 01-MAY-09:09 | 1231.33 | 01-MAY-07:10 | 2160.55 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 61.81 | 31-MAY-13:00 | 1347.09 | 01-MAY-24:00 |
June | 2010.79 | 01-JUN-09:09 | 1470.28 | 13-JUN-07:10 | 2160.55 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 479.39 | 11-JUN-14:55 | 1090.08 | 02-JUN-05:00 |
July | 2010.79 | 03-JUL-09:09 | 1470.28 | 20-JUL-07:10 | 2160.55 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 136.45 | 02-JUL-15:20 | 471.14 | 09-JUL-21:00 |
August | 2010.79 | 01-AUG-09:09 | 1350.81 | 28-AUG-07:10 | 2160.55 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 95.45 | 04-AUG-16:35 | 638.30 | 06-AUG-09:00 |
September | 2010.79 | 01-SEP-09:09 | 1803.00 | 21-SEP-07:10 | 2160.55 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 135.41 | 17-SEP-15:10 | 958.00 | 18-SEP-23:00 |
October | 2010.79 | 02-OCT-09:09 | 2587.92 | 30-OCT-07:10 | 2160.55 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 1495.97 | 24-OCT-05:00 |
November | 2010.79 | 01-NOV-09:09 | 2587.92 | 01-NOV-07:10 | 2160.55 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 3388.54 | 20-NOV-22:01 |
December | 2010.79 | 01-DEC-10:09 | 2587.92 | 01-DEC-16:10 | 2160.55 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 5179.08 | 09-DEC-01:51 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.79 | 1231.33 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 471.14 | |||||
Maximum of Months | 2010.79 | 2587.92 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 479.39 | 5179.08 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 1667.75 | 02-JAN-16:19 | 1392.34 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 3030.19 | 29-JAN-10:51 |
February | 1295.83 | 01-FEB-10:09 | 1453.34 | 01-FEB-16:49 | 1392.34 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 2061.09 | 10-FEB-22:01 |
March | 1295.83 | 01-MAR-10:09 | 1161.92 | 01-MAR-16:40 | 1392.34 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 1916.73 | 05-MAR-09:55 |
April | 1295.83 | 03-APR-09:09 | 947.51 | 10-APR-07:10 | 1392.34 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 294.23 | 15-APR-17:10 | 1357.98 | 02-APR-23:52 |
May | 1295.83 | 01-MAY-09:09 | 870.51 | 09-MAY-15:20 | 1392.34 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 41.20 | 31-MAY-13:00 | 890.20 | 01-MAY-24:00 |
June | 1295.83 | 01-JUN-09:09 | 870.51 | 05-JUN-15:30 | 1392.34 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 330.86 | 18-JUN-15:50 | 709.60 | 02-JUN-05:00 |
July | 1295.83 | 03-JUL-09:09 | 870.51 | 20-JUL-07:10 | 1392.34 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 115.77 | 02-JUL-16:00 | 313.83 | 09-JUL-10:10 |
August | 1295.83 | 01-AUG-09:09 | 793.52 | 01-AUG-07:10 | 1392.34 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 63.64 | 04-AUG-16:35 | 406.46 | 06-AUG-09:00 |
September | 1295.83 | 01-SEP-09:09 | 947.51 | 13-SEP-15:39 | 1392.34 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 113.19 | 17-SEP-15:10 | 628.09 | 18-SEP-23:00 |
October | 1295.83 | 02-OCT-09:09 | 1667.75 | 31-OCT-07:10 | 1392.34 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 985.87 | 29-OCT-09:00 |
November | 1295.83 | 01-NOV-09:09 | 1667.75 | 01-NOV-07:10 | 1392.34 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 2255.87 | 20-NOV-22:01 |
December | 1295.83 | 01-DEC-10:09 | 1667.75 | 01-DEC-16:10 | 1392.34 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 3406.53 | 09-DEC-01:51 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 793.52 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 313.83 | |||||
Maximum of Months | 1295.83 | 1667.75 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 330.86 | 3406.53 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.83 | 02-JAN-10:09 | 2587.98 | 02-JAN-16:40 | 2160.58 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 4898.27 | 29-JAN-12:51 |
February | 2010.83 | 01-FEB-10:09 | 2255.25 | 14-FEB-16:49 | 2160.58 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 3092.70 | 10-FEB-22:01 |
March | 2010.83 | 01-MAR-10:09 | 1803.04 | 01-MAR-16:00 | 2160.58 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 2964.23 | 05-MAR-13:55 |
April | 2010.83 | 03-APR-09:09 | 1803.04 | 10-APR-07:10 | 2160.58 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 311.80 | 15-APR-17:10 | 1951.03 | 02-APR-23:52 |
May | 2010.83 | 01-MAY-09:09 | 1231.36 | 01-MAY-07:10 | 2160.58 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 61.81 | 31-MAY-13:00 | 1329.42 | 01-MAY-24:00 |
June | 2010.83 | 01-JUN-09:09 | 1470.31 | 13-JUN-07:10 | 2160.58 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 484.93 | 11-JUN-14:55 | 1059.34 | 02-JUN-05:00 |
July | 2010.83 | 03-JUL-09:09 | 1470.31 | 20-JUL-07:10 | 2160.58 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 145.86 | 02-JUL-15:14 | 466.53 | 09-JUL-21:00 |
August | 2010.83 | 01-AUG-09:09 | 1350.84 | 28-AUG-07:10 | 2160.58 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 95.45 | 04-AUG-16:35 | 672.37 | 06-AUG-13:40 |
September | 2010.83 | 01-SEP-09:09 | 1803.04 | 21-SEP-07:10 | 2160.58 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 85.18 | 06-SEP-16:00 | 1010.83 | 24-SEP-13:00 |
October | 2010.83 | 02-OCT-09:09 | 2587.98 | 31-OCT-07:10 | 2160.58 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 1467.04 | 24-OCT-05:00 |
November | 2010.83 | 01-NOV-09:09 | 2587.98 | 01-NOV-07:10 | 2160.58 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 3385.21 | 20-NOV-22:01 |
December | 2010.83 | 01-DEC-10:09 | 2587.98 | 01-DEC-16:30 | 2160.58 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 5083.84 | 09-DEC-01:51 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.83 | 1231.36 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 466.53 | |||||
Maximum of Months | 2010.83 | 2587.98 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 484.93 | 5083.84 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 1667.75 | 02-JAN-16:40 | 1392.33 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 2938.88 | 29-JAN-10:51 |
February | 1295.83 | 01-FEB-10:09 | 1453.34 | 14-FEB-08:09 | 1392.33 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 2079.59 | 10-FEB-22:10 |
March | 1295.83 | 01-MAR-10:09 | 1161.92 | 13-MAR-07:10 | 1392.33 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 2028.72 | 12-MAR-15:53 |
April | 1295.83 | 03-APR-09:09 | 1161.92 | 10-APR-07:10 | 1392.33 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 166.53 | 15-APR-17:10 | 1506.71 | 02-APR-23:52 |
May | 1295.83 | 01-MAY-09:09 | 870.51 | 15-MAY-08:20 | 1392.33 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 41.20 | 31-MAY-13:00 | 946.44 | 01-MAY-24:00 |
June | 1295.83 | 01-JUN-09:09 | 947.51 | 13-JUN-07:10 | 1392.33 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 310.47 | 11-JUN-14:53 | 768.06 | 02-JUN-05:00 |
July | 1295.83 | 03-JUL-09:09 | 947.51 | 20-JUL-07:10 | 1392.33 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 82.23 | 02-JUL-11:20 | 374.69 | 09-JUL-21:00 |
August | 1295.83 | 01-AUG-09:09 | 870.51 | 23-AUG-07:10 | 1392.33 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 63.64 | 04-AUG-16:35 | 513.25 | 06-AUG-06:00 |
September | 1295.83 | 01-SEP-09:09 | 1161.92 | 12-SEP-07:10 | 1392.33 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 67.70 | 17-SEP-11:50 | 714.71 | 24-SEP-16:20 |
October | 1295.83 | 02-OCT-09:09 | 1667.75 | 30-OCT-07:10 | 1392.33 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 1056.77 | 24-OCT-05:00 |
November | 1295.83 | 01-NOV-09:09 | 1667.75 | 01-NOV-07:10 | 1392.33 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 2304.87 | 20-NOV-22:10 |
December | 1295.83 | 01-DEC-10:09 | 1667.75 | 01-DEC-16:30 | 1392.33 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 3617.36 | 09-DEC-01:51 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 870.51 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 374.69 | |||||
Maximum of Months | 1295.83 | 1667.75 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 310.47 | 3617.36 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.79 | 02-JAN-10:09 | 2587.92 | 02-JAN-16:19 | 2160.55 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 10077.45 | 29-JAN-11:00 |
February | 2010.79 | 01-FEB-10:09 | 2255.20 | 01-FEB-16:00 | 2160.55 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 7203.73 | 10-FEB-22:01 |
March | 2010.79 | 01-MAR-10:09 | 1803.00 | 01-MAR-16:49 | 2160.55 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 5488.77 | 06-MAR-06:00 |
April | 2010.79 | 03-APR-09:09 | 1803.00 | 10-APR-07:10 | 2160.55 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 959.22 | 15-APR-17:01 | 4101.13 | 02-APR-23:58 |
May | 2010.79 | 01-MAY-09:09 | 1231.33 | 01-MAY-07:10 | 2160.55 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 142.32 | 31-MAY-13:00 | 2720.90 | 01-MAY-24:00 |
June | 2010.79 | 01-JUN-09:09 | 1350.81 | 05-JUN-07:10 | 2160.55 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1032.20 | 18-JUN-16:04 | 2242.92 | 02-JUN-05:00 |
July | 2010.79 | 03-JUL-09:09 | 1350.81 | 20-JUL-07:10 | 2160.55 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 336.19 | 02-JUL-16:00 | 1031.31 | 09-JUL-10:00 |
August | 2010.79 | 01-AUG-09:09 | 1350.81 | 31-AUG-07:10 | 2160.55 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 220.32 | 04-AUG-16:35 | 1372.78 | 06-AUG-09:00 |
September | 2010.79 | 01-SEP-09:09 | 1803.00 | 21-SEP-07:10 | 2160.55 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 410.39 | 17-SEP-15:00 | 2018.79 | 18-SEP-23:00 |
October | 2010.79 | 02-OCT-09:09 | 2587.92 | 30-OCT-07:10 | 2160.55 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 3299.87 | 24-OCT-04:58 |
November | 2010.79 | 01-NOV-09:09 | 2587.92 | 01-NOV-07:10 | 2160.55 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 7885.69 | 20-NOV-22:01 |
December | 2010.79 | 01-DEC-10:09 | 2587.92 | 01-DEC-16:10 | 2160.55 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 12059.25 | 09-DEC-02:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.79 | 1231.33 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1031.31 | |||||
Maximum of Months | 2010.79 | 2587.92 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 1032.20 | 12059.25 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1239.33 | 02-JAN-08:09 | 1667.75 | 02-JAN-16:19 | 1392.34 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 6855.27 | 29-JAN-10:54 |
February | 1239.33 | 01-FEB-08:09 | 1453.34 | 01-FEB-16:00 | 1392.34 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 4801.59 | 10-FEB-22:01 |
March | 1239.33 | 01-MAR-08:09 | 1161.92 | 01-MAR-16:40 | 1392.34 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 3925.33 | 06-MAR-06:00 |
April | 1239.33 | 03-APR-07:10 | 947.51 | 10-APR-07:10 | 1392.34 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 692.01 | 15-APR-17:01 | 2734.09 | 02-APR-23:56 |
May | 1239.33 | 01-MAY-07:10 | 870.51 | 09-MAY-15:20 | 1392.34 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 94.88 | 31-MAY-13:00 | 1834.25 | 01-MAY-24:00 |
June | 1239.33 | 01-JUN-07:10 | 870.51 | 09-JUN-15:50 | 1392.34 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 775.70 | 18-JUN-16:10 | 1488.85 | 02-JUN-05:00 |
July | 1239.33 | 03-JUL-07:10 | 870.51 | 20-JUL-07:10 | 1392.34 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 239.45 | 02-JUL-15:54 | 752.84 | 04-JUL-10:00 |
August | 1239.33 | 01-AUG-07:10 | 793.52 | 01-AUG-07:10 | 1392.34 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 146.88 | 04-AUG-16:35 | 942.15 | 06-AUG-09:00 |
September | 1239.33 | 01-SEP-07:10 | 947.51 | 13-SEP-15:50 | 1392.34 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 252.43 | 17-SEP-15:00 | 1332.67 | 18-SEP-23:00 |
October | 1239.33 | 02-OCT-07:10 | 1667.75 | 31-OCT-07:10 | 1392.34 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 2199.95 | 24-OCT-04:58 |
November | 1239.33 | 01-NOV-07:10 | 1667.75 | 01-NOV-07:10 | 1392.34 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 5255.64 | 20-NOV-22:01 |
December | 1239.33 | 01-DEC-08:09 | 1667.75 | 01-DEC-16:10 | 1392.34 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 8039.76 | 09-DEC-01:53 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1239.33 | 793.52 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 752.84 | |||||
Maximum of Months | 1239.33 | 1667.75 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 775.70 | 8039.76 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.83 | 02-JAN-10:09 | 2587.98 | 02-JAN-16:40 | 2160.58 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 10557.37 | 29-JAN-12:51 |
February | 2010.83 | 01-FEB-10:09 | 2255.25 | 14-FEB-16:49 | 2160.58 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 7209.14 | 10-FEB-22:01 |
March | 2010.83 | 01-MAR-10:09 | 1803.04 | 01-MAR-16:00 | 2160.58 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 6356.13 | 05-MAR-14:20 |
April | 2010.83 | 03-APR-09:09 | 1803.04 | 10-APR-07:10 | 2160.58 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 696.37 | 15-APR-17:10 | 4101.26 | 02-APR-23:52 |
May | 2010.83 | 01-MAY-09:09 | 1231.36 | 01-MAY-07:10 | 2160.58 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 142.32 | 31-MAY-13:00 | 2794.80 | 01-MAY-24:00 |
June | 2010.83 | 01-JUN-09:09 | 1470.31 | 13-JUN-07:10 | 2160.58 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1067.34 | 18-JUN-16:04 | 2248.36 | 02-JUN-05:00 |
July | 2010.83 | 03-JUL-09:09 | 1470.31 | 20-JUL-07:10 | 2160.58 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 333.39 | 02-JUL-15:14 | 1072.92 | 09-JUL-10:00 |
August | 2010.83 | 01-AUG-09:09 | 1350.84 | 31-AUG-07:10 | 2160.58 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 220.33 | 04-AUG-16:35 | 1563.66 | 06-AUG-13:40 |
September | 2010.83 | 01-SEP-09:09 | 1803.04 | 21-SEP-07:10 | 2160.58 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 196.08 | 06-SEP-16:00 | 2280.22 | 24-SEP-13:15 |
October | 2010.83 | 02-OCT-09:09 | 2587.98 | 31-OCT-07:10 | 2160.58 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 3299.77 | 24-OCT-04:56 |
November | 2010.83 | 01-NOV-09:09 | 2587.98 | 01-NOV-07:10 | 2160.58 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 7894.86 | 20-NOV-22:01 |
December | 2010.83 | 01-DEC-10:09 | 2587.98 | 01-DEC-16:30 | 2160.58 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 12059.53 | 09-DEC-01:58 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.83 | 1231.36 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1072.92 | |||||
Maximum of Months | 2010.83 | 2587.98 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 1067.34 | 12059.53 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 1667.75 | 02-JAN-16:40 | 1392.33 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 6855.29 | 29-JAN-10:58 |
February | 1295.83 | 01-FEB-10:09 | 1453.34 | 14-FEB-08:09 | 1392.33 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 4804.18 | 10-FEB-22:01 |
March | 1295.83 | 01-MAR-10:09 | 1161.92 | 13-MAR-07:10 | 1392.33 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 3925.40 | 06-MAR-06:00 |
April | 1295.83 | 03-APR-09:09 | 1161.92 | 10-APR-07:10 | 1392.33 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 376.45 | 15-APR-17:10 | 2734.17 | 02-APR-23:52 |
May | 1295.83 | 01-MAY-09:09 | 870.51 | 15-MAY-08:30 | 1392.33 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 94.88 | 31-MAY-13:00 | 1855.34 | 01-MAY-24:00 |
June | 1295.83 | 01-JUN-09:09 | 947.51 | 13-JUN-07:10 | 1392.33 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 692.62 | 11-JUN-15:13 | 1482.89 | 02-JUN-05:00 |
July | 1295.83 | 03-JUL-09:09 | 947.51 | 20-JUL-07:10 | 1392.33 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 227.41 | 02-JUL-11:20 | 767.40 | 09-JUL-10:00 |
August | 1295.83 | 01-AUG-09:09 | 870.51 | 23-AUG-07:10 | 1392.33 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 146.89 | 04-AUG-16:35 | 996.73 | 06-AUG-09:00 |
September | 1295.83 | 01-SEP-09:09 | 1161.92 | 21-SEP-07:10 | 1392.33 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 224.95 | 17-SEP-11:40 | 1572.34 | 24-SEP-16:30 |
October | 1295.83 | 02-OCT-09:09 | 1667.75 | 30-OCT-07:10 | 1392.33 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 2199.92 | 24-OCT-05:00 |
November | 1295.83 | 01-NOV-09:09 | 1667.75 | 01-NOV-07:10 | 1392.33 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 5260.69 | 20-NOV-22:01 |
December | 1295.83 | 01-DEC-10:09 | 1667.75 | 01-DEC-16:30 | 1392.33 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 8039.71 | 09-DEC-01:53 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 870.51 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 767.40 | |||||
Maximum of Months | 1295.83 | 1667.75 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 692.62 | 8039.71 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.79 | 02-JAN-10:09 | 2587.92 | 02-JAN-16:19 | 2160.55 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 12174.10 | 29-JAN-11:00 |
February | 2010.79 | 01-FEB-10:09 | 2255.20 | 01-FEB-16:00 | 2160.55 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 8937.55 | 10-FEB-22:01 |
March | 2010.79 | 01-MAR-10:09 | 1803.00 | 01-MAR-16:49 | 2160.55 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 6777.36 | 20-MAR-21:02 |
April | 2010.79 | 03-APR-09:09 | 1803.00 | 10-APR-07:10 | 2160.55 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1132.16 | 15-APR-17:01 | 5117.98 | 02-APR-23:58 |
May | 2010.79 | 01-MAY-09:09 | 1231.33 | 01-MAY-07:10 | 2160.55 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 173.43 | 31-MAY-13:00 | 3141.19 | 01-MAY-24:00 |
June | 2010.79 | 01-JUN-09:09 | 1350.81 | 05-JUN-07:10 | 2160.55 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1289.14 | 18-JUN-16:04 | 2646.36 | 02-JUN-04:57 |
July | 2010.79 | 03-JUL-09:09 | 1350.81 | 20-JUL-07:10 | 2160.55 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 415.54 | 02-JUL-15:30 | 1239.21 | 09-JUL-21:00 |
August | 2010.79 | 01-AUG-09:09 | 1350.81 | 31-AUG-07:10 | 2160.55 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 269.16 | 04-AUG-16:35 | 1610.16 | 06-AUG-09:00 |
September | 2010.79 | 01-SEP-09:09 | 1803.00 | 21-SEP-07:10 | 2160.55 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 499.32 | 17-SEP-15:10 | 2343.10 | 18-SEP-23:00 |
October | 2010.79 | 02-OCT-09:09 | 2587.92 | 30-OCT-07:10 | 2160.55 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 4121.89 | 24-OCT-05:00 |
November | 2010.79 | 01-NOV-09:09 | 2587.92 | 01-NOV-07:10 | 2160.55 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 9786.34 | 20-NOV-22:01 |
December | 2010.79 | 01-DEC-10:09 | 2587.92 | 01-DEC-16:10 | 2160.55 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 14538.76 | 09-DEC-01:51 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.79 | 1231.33 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1239.21 | |||||
Maximum of Months | 2010.79 | 2587.92 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 1289.14 | 14538.76 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 1667.75 | 02-JAN-16:19 | 1392.34 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 8536.48 | 29-JAN-10:57 |
February | 1295.83 | 01-FEB-10:09 | 1453.34 | 01-FEB-16:00 | 1392.34 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 5955.68 | 10-FEB-22:01 |
March | 1295.83 | 01-MAR-10:09 | 1161.92 | 01-MAR-16:40 | 1392.34 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 4888.72 | 06-MAR-06:00 |
April | 1295.83 | 03-APR-09:09 | 947.51 | 10-APR-07:10 | 1392.34 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 790.61 | 15-APR-17:01 | 3424.15 | 02-APR-23:54 |
May | 1295.83 | 01-MAY-09:09 | 870.51 | 09-MAY-15:20 | 1392.34 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 115.62 | 31-MAY-13:00 | 2130.95 | 01-MAY-24:00 |
June | 1295.83 | 01-JUN-09:09 | 870.51 | 09-JUN-15:50 | 1392.34 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 931.45 | 18-JUN-16:10 | 1764.38 | 02-JUN-05:00 |
July | 1295.83 | 03-JUL-09:09 | 870.51 | 20-JUL-07:10 | 1392.34 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 287.28 | 02-JUL-15:24 | 950.90 | 04-JUL-10:00 |
August | 1295.83 | 01-AUG-09:09 | 793.52 | 01-AUG-07:10 | 1392.34 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 179.44 | 04-AUG-16:35 | 1108.47 | 06-AUG-09:00 |
September | 1295.83 | 01-SEP-09:09 | 947.51 | 13-SEP-15:50 | 1392.34 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 254.97 | 10-SEP-15:10 | 1553.54 | 18-SEP-23:00 |
October | 1295.83 | 02-OCT-09:09 | 1667.75 | 31-OCT-07:10 | 1392.34 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 2747.84 | 24-OCT-04:58 |
November | 1295.83 | 01-NOV-09:09 | 1667.75 | 01-NOV-07:10 | 1392.34 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 6521.91 | 20-NOV-22:01 |
December | 1295.83 | 01-DEC-10:09 | 1667.75 | 01-DEC-16:10 | 1392.34 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 9841.76 | 09-DEC-01:51 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 793.52 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 950.90 | |||||
Maximum of Months | 1295.83 | 1667.75 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 931.45 | 9841.76 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.83 | 02-JAN-10:09 | 2587.98 | 02-JAN-16:40 | 2160.58 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 12811.14 | 29-JAN-10:53 |
February | 2010.83 | 01-FEB-10:09 | 2255.25 | 14-FEB-16:49 | 2160.58 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 8944.37 | 10-FEB-22:01 |
March | 2010.83 | 01-MAR-10:09 | 1803.04 | 01-MAR-16:00 | 2160.58 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 7362.21 | 05-MAR-14:20 |
April | 2010.83 | 03-APR-09:09 | 1803.04 | 10-APR-07:10 | 2160.58 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 791.75 | 15-APR-17:10 | 5118.06 | 02-APR-23:58 |
May | 2010.83 | 01-MAY-09:09 | 1231.36 | 01-MAY-07:10 | 2160.58 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 173.43 | 31-MAY-13:00 | 3237.95 | 01-MAY-24:00 |
June | 2010.83 | 01-JUN-09:09 | 1470.31 | 13-JUN-07:10 | 2160.58 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1329.11 | 18-JUN-16:04 | 2646.60 | 02-JUN-05:00 |
July | 2010.83 | 03-JUL-09:09 | 1470.31 | 20-JUL-07:10 | 2160.58 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 399.32 | 02-JUL-16:04 | 1270.68 | 09-JUL-21:00 |
August | 2010.83 | 01-AUG-09:09 | 1350.84 | 31-AUG-07:10 | 2160.58 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 269.16 | 04-AUG-16:35 | 1951.96 | 06-AUG-13:50 |
September | 2010.83 | 01-SEP-09:09 | 1803.04 | 21-SEP-07:10 | 2160.58 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 239.60 | 06-SEP-16:00 | 2614.94 | 24-SEP-13:50 |
October | 2010.83 | 02-OCT-09:09 | 2587.98 | 31-OCT-07:10 | 2160.58 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 4121.79 | 24-OCT-04:58 |
November | 2010.83 | 01-NOV-09:09 | 2587.98 | 01-NOV-07:10 | 2160.58 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 9797.29 | 20-NOV-22:01 |
December | 2010.83 | 01-DEC-10:09 | 2587.98 | 01-DEC-16:30 | 2160.58 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 14773.95 | 09-DEC-01:51 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.83 | 1231.36 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1270.68 | |||||
Maximum of Months | 2010.83 | 2587.98 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 1329.11 | 14773.95 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 1667.75 | 02-JAN-16:40 | 1392.33 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 8536.48 | 29-JAN-10:56 |
February | 1295.83 | 01-FEB-10:09 | 1453.34 | 14-FEB-08:09 | 1392.33 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 5961.49 | 10-FEB-22:01 |
March | 1295.83 | 01-MAR-10:09 | 1161.92 | 13-MAR-07:10 | 1392.33 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 4889.40 | 06-MAR-06:00 |
April | 1295.83 | 03-APR-09:09 | 1161.92 | 10-APR-07:10 | 1392.33 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 449.88 | 15-APR-17:10 | 3426.05 | 02-APR-23:54 |
May | 1295.83 | 01-MAY-09:09 | 870.51 | 15-MAY-08:30 | 1392.33 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 115.62 | 31-MAY-13:00 | 2162.68 | 01-MAY-24:00 |
June | 1295.83 | 01-JUN-09:09 | 947.51 | 13-JUN-07:10 | 1392.33 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 836.65 | 11-JUN-15:00 | 1764.28 | 02-JUN-04:57 |
July | 1295.83 | 03-JUL-09:09 | 947.51 | 20-JUL-07:10 | 1392.33 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 292.98 | 02-JUL-11:00 | 931.96 | 09-JUL-21:00 |
August | 1295.83 | 01-AUG-09:09 | 870.51 | 23-AUG-07:10 | 1392.33 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 179.44 | 04-AUG-16:35 | 1175.39 | 06-AUG-09:00 |
September | 1295.83 | 01-SEP-09:09 | 1161.92 | 21-SEP-07:10 | 1392.33 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 317.00 | 17-SEP-11:50 | 1875.85 | 24-SEP-16:30 |
October | 1295.83 | 02-OCT-09:09 | 1667.75 | 30-OCT-07:10 | 1392.33 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 2747.90 | 24-OCT-04:56 |
November | 1295.83 | 01-NOV-09:09 | 1667.75 | 01-NOV-07:10 | 1392.33 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 6530.17 | 20-NOV-22:01 |
December | 1295.83 | 01-DEC-10:09 | 1667.75 | 01-DEC-16:30 | 1392.33 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 9849.27 | 09-DEC-01:51 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 870.51 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 931.96 | |||||
Maximum of Months | 1295.83 | 1667.75 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 836.65 | 9849.27 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 232.27 | 02-JAN-10:09 | 578.72 | 02-JAN-08:09 | 1948.61 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 232.27 | 01-FEB-10:09 | 578.72 | 01-FEB-08:09 | 3897.21 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 232.27 | 01-MAR-10:09 | 578.72 | 01-MAR-08:09 | 7794.42 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 232.27 | 03-APR-09:09 | 578.72 | 03-APR-07:10 | 7794.42 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 232.27 | 01-MAY-09:09 | 578.72 | 01-MAY-07:10 | 3897.21 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 232.27 | 01-JUN-09:09 | 578.72 | 01-JUN-07:10 | 5845.82 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 232.27 | 03-JUL-09:09 | 578.72 | 03-JUL-07:10 | 7794.42 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 232.27 | 01-AUG-09:09 | 578.72 | 01-AUG-07:10 | 7794.42 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 232.27 | 01-SEP-09:09 | 578.72 | 01-SEP-07:10 | 3897.21 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 232.27 | 02-OCT-09:09 | 578.72 | 02-OCT-07:10 | 5845.82 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 232.27 | 01-NOV-09:09 | 578.72 | 01-NOV-07:10 | 5845.82 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 232.27 | 01-DEC-10:09 | 578.72 | 01-DEC-08:09 | 7794.42 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 232.27 | 578.72 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 232.27 | 578.72 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 232.27 | 02-JAN-10:09 | 578.72 | 02-JAN-08:09 | 1948.61 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 232.27 | 01-FEB-10:09 | 578.72 | 01-FEB-08:09 | 3897.21 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 232.27 | 01-MAR-10:09 | 578.72 | 01-MAR-08:09 | 7794.42 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 232.27 | 03-APR-09:09 | 578.72 | 03-APR-07:10 | 7794.42 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 232.27 | 01-MAY-09:09 | 578.72 | 01-MAY-07:10 | 3897.21 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 232.27 | 01-JUN-09:09 | 578.72 | 01-JUN-07:10 | 5845.82 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 232.27 | 03-JUL-09:09 | 578.72 | 03-JUL-07:10 | 7794.42 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 232.27 | 01-AUG-09:09 | 578.72 | 01-AUG-07:10 | 7794.42 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 232.27 | 01-SEP-09:09 | 578.72 | 01-SEP-07:10 | 3897.21 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 232.27 | 02-OCT-09:09 | 578.72 | 02-OCT-07:10 | 5845.82 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 232.27 | 01-NOV-09:09 | 578.72 | 01-NOV-07:10 | 5845.82 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 232.27 | 01-DEC-10:09 | 578.72 | 01-DEC-08:09 | 7794.42 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 232.27 | 578.72 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 232.27 | 578.72 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 232.27 | 02-JAN-10:09 | 578.72 | 02-JAN-08:09 | 1948.61 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 232.27 | 01-FEB-10:09 | 578.72 | 01-FEB-08:09 | 3897.21 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 232.27 | 01-MAR-10:09 | 578.72 | 01-MAR-08:09 | 7794.42 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 232.27 | 03-APR-09:09 | 578.72 | 03-APR-07:10 | 7794.42 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 232.27 | 01-MAY-09:09 | 578.72 | 01-MAY-07:10 | 3897.21 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 232.27 | 01-JUN-09:09 | 578.72 | 01-JUN-07:10 | 5845.82 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 232.27 | 03-JUL-09:09 | 578.72 | 03-JUL-07:10 | 7794.42 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 232.27 | 01-AUG-09:09 | 578.72 | 01-AUG-07:10 | 7794.42 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 232.27 | 01-SEP-09:09 | 578.72 | 01-SEP-07:10 | 3897.21 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 232.27 | 02-OCT-09:09 | 578.72 | 02-OCT-07:10 | 5845.82 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 232.27 | 01-NOV-09:09 | 578.72 | 01-NOV-07:10 | 5845.82 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 232.27 | 01-DEC-10:09 | 578.72 | 01-DEC-08:09 | 7794.42 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 232.27 | 578.72 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 232.27 | 578.72 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 5027.92 | 02-JAN-10:09 | 6471.01 | 02-JAN-08:09 | 94908.13 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 5027.92 | 01-FEB-10:09 | 6471.01 | 01-FEB-08:09 | 189816.26 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 5027.92 | 01-MAR-10:09 | 6471.01 | 01-MAR-08:09 | 379632.52 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 5027.92 | 03-APR-09:09 | 6471.01 | 03-APR-07:10 | 379632.52 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 5027.92 | 01-MAY-09:09 | 6471.01 | 01-MAY-07:10 | 189816.26 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5027.92 | 01-JUN-09:09 | 6471.01 | 01-JUN-07:10 | 284724.39 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 5027.92 | 03-JUL-09:09 | 6471.01 | 03-JUL-07:10 | 379632.52 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 5027.92 | 01-AUG-09:09 | 6471.01 | 01-AUG-07:10 | 379632.52 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 5027.92 | 01-SEP-09:09 | 6471.01 | 01-SEP-07:10 | 189816.26 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 5027.92 | 02-OCT-09:09 | 6471.01 | 02-OCT-07:10 | 284724.39 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5027.92 | 01-NOV-09:09 | 6471.01 | 01-NOV-07:10 | 284724.39 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 5027.92 | 01-DEC-10:09 | 6471.01 | 01-DEC-08:09 | 379632.52 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 5027.92 | 6471.01 | 94908.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 5027.92 | 6471.01 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 9538.54 | 29-JAN-10:51 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 6703.71 | 10-FEB-22:01 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 5911.82 | 12-MAR-15:53 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 726.45 | 15-APR-17:01 | 4617.58 | 02-APR-23:52 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 107.22 | 31-MAY-13:00 | 2947.78 | 01-MAY-24:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 975.15 | 11-JUN-15:00 | 2412.94 | 02-JUN-05:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 297.46 | 02-JUL-15:00 | 931.70 | 09-JUL-21:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 166.91 | 04-AUG-16:35 | 1323.42 | 06-AUG-06:06 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 269.06 | 17-SEP-14:51 | 2091.85 | 18-SEP-23:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 3365.82 | 24-OCT-05:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 7293.61 | 20-NOV-22:01 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 11737.44 | 09-DEC-01:51 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 931.70 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 975.15 | 11737.44 |
Report: PeakSpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 16184.33 | 29-JAN-11:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 11535.73 | 10-FEB-22:01 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 9449.21 | 12-MAR-15:53 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1472.99 | 15-APR-17:01 | 7406.45 | 02-APR-23:52 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 194.42 | 31-MAY-13:00 | 4944.26 | 01-MAY-24:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1839.15 | 11-JUN-15:00 | 4209.60 | 02-JUN-05:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 571.95 | 02-JUL-15:00 | 1623.92 | 09-JUL-21:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 296.01 | 04-AUG-16:35 | 2291.95 | 06-AUG-06:00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 567.54 | 17-SEP-14:50 | 3645.14 | 18-SEP-23:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 5626.52 | 24-OCT-04:52 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 12198.26 | 20-NOV-22:01 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 19890.24 | 09-DEC-02:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1623.92 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1839.15 | 19890.24 |
Report: PeakSpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 17624.51 | 18-JAN-23:51 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 12909.09 | 10-FEB-22:01 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 10244.59 | 20-MAR-21:02 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1291.74 | 15-APR-17:01 | 7152.18 | 02-APR-24:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 185.24 | 31-MAY-13:00 | 5159.27 | 01-MAY-24:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1515.40 | 11-JUN-15:00 | 4287.99 | 02-JUN-05:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 308.21 | 02-JUL-15:50 | 1883.61 | 09-JUL-21:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 311.49 | 04-AUG-16:30 | 2544.01 | 06-AUG-09:00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 285.97 | 06-SEP-16:00 | 3771.12 | 18-SEP-23:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 5585.38 | 24-OCT-05:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 13875.28 | 20-NOV-22:01 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 21094.03 | 09-DEC-01:51 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1883.61 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1515.40 | 21094.03 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 110847.12 | 02-JAN-05:01 | 0.00 | 20401.06 | 107660.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 111715.39 | 27-FEB-05:01 | 0.00 | 17850.93 | 94202.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 118206.48 | 27-MAR-03:51 | 0.00 | 10199.39 | 107660.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 117134.11 | 10-APR-04:11 | 0.00 | 25501.32 | 134575.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 117109.78 | 01-MAY-04:12 | 0.00 | 15300.79 | 80745.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 119047.89 | 19-JUN-04:12 | 0.00 | 15300.79 | 80745.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 118169.23 | 24-JUL-04:12 | 0.00 | 15300.79 | 80745.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 119789.80 | 06-AUG-15:00 | 8078.51 | 11474.31 | 121117.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 119631.48 | 04-SEP-08:29 | 7180.90 | 10199.39 | 107660.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 120117.77 | 30-OCT-04:11 | 0.00 | 25501.32 | 134575.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 119543.22 | 06-NOV-05:11 | 0.00 | 20401.06 | 107660.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 117527.69 | 04-DEC-04:01 | 0.00 | 12749.23 | 134575.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 110847.12 | 0.00 | 10199.39 | 80745.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 120117.77 | 8078.51 | 25501.32 | 134575.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 80459.41 | 14-JAN-06:01 | 12897.91 | 18321.59 | 61179.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 87368.66 | 25-FEB-06:01 | 11285.67 | 16031.39 | 53531.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 93506.02 | 27-MAR-03:51 | 0.00 | 9159.77 | 47501.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 96859.26 | 19-APR-04:12 | 0.00 | 11450.99 | 29688.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 99110.54 | 30-MAY-04:12 | 0.00 | 13741.19 | 35625.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 97663.60 | 19-JUN-04:12 | 0.00 | 13741.19 | 35625.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 98355.68 | 10-JUL-04:13 | 0.00 | 13741.19 | 35625.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 99567.91 | 07-AUG-04:12 | 0.00 | 13741.19 | 35625.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 102001.89 | 11-SEP-04:13 | 0.00 | 13741.19 | 35625.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 95787.71 | 10-OCT-04:11 | 0.00 | 16031.39 | 41563.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 95961.10 | 06-NOV-05:11 | 0.00 | 18321.59 | 47501.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 86729.23 | 05-DEC-06:02 | 16122.38 | 22901.98 | 76473.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 80459.41 | 0.00 | 9159.77 | 29688.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 102001.89 | 16122.38 | 22901.98 | 76473.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 30404.80 | 13-JAN-14:45 | 32029.16 | 41222.03 | 34413.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 27458.69 | 10-FEB-16:40 | 15316.26 | 20611.01 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 76722.13 | 21-MAR-11:00 | 45948.79 | 61833.04 | 51619.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 84248.69 | 17-APR-05:02 | 8061.19 | 11450.99 | 38236.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 85831.27 | 31-MAY-04:12 | 0.00 | 11450.99 | 29688.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 88688.62 | 28-JUN-04:12 | 0.00 | 13741.19 | 35625.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 87748.46 | 10-JUL-04:12 | 0.00 | 13741.19 | 35625.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 87575.00 | 02-AUG-04:12 | 0.00 | 13741.19 | 35625.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 87092.06 | 12-SEP-04:12 | 0.00 | 11450.99 | 29688.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 77588.77 | 04-OCT-05:02 | 8061.19 | 11450.99 | 38236.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 74788.47 | 04-NOV-05:02 | 8061.19 | 11450.99 | 38236.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 80368.12 | 01-DEC-17:57 | 14510.15 | 34351.43 | 28677.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 27458.69 | 0.00 | 11450.99 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 88688.62 | 45948.79 | 61833.04 | 51619.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 18665.30 | 13-JAN-17:00 | 30632.53 | 41222.03 | 34413.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 20870.37 | 02-FEB-16:40 | 30632.53 | 41222.03 | 34413.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 33393.37 | 24-MAR-16:00 | 15316.26 | 20611.01 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 83111.07 | 17-APR-05:02 | 8061.19 | 11450.99 | 38236.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 84346.47 | 30-MAY-04:12 | 0.00 | 13741.19 | 35625.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 90354.15 | 12-JUN-04:13 | 0.00 | 16031.39 | 41563.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 88291.20 | 26-JUL-04:12 | 0.00 | 13741.19 | 35625.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 86888.00 | 28-AUG-04:12 | 0.00 | 13741.19 | 35625.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 87532.89 | 11-SEP-04:12 | 0.00 | 13741.19 | 35625.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 35534.68 | 20-OCT-16:00 | 15316.26 | 20611.01 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 34224.39 | 03-NOV-16:00 | 15316.26 | 20611.01 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 18167.13 | 01-DEC-16:40 | 30632.53 | 41222.03 | 34413.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 18167.13 | 0.00 | 11450.99 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 90354.15 | 30632.53 | 41222.03 | 41563.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2216.43 | 13-JAN-11:50 | 1923.11 | 1231.33 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 223.10 |
February | 2664.03 | 24-FEB-13:30 | 1923.11 | 1231.33 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 145.99 |
March | 5014.29 | 28-MAR-14:30 | 1923.11 | 1231.33 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 143.83 |
April | 17720.32 | 16-APR-15:51 | 1012.16 | 684.02 | 7201.84 | 0.00 | 0.00 | 0.00 | 0.00 | 176.13 | 0.00 |
May | 10948.54 | 31-MAY-05:03 | 809.73 | 547.28 | 3840.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 54.72 |
June | 18314.39 | 25-JUN-18:11 | 0.00 | 684.02 | 5591.71 | 0.00 | 0.00 | 0.00 | 0.00 | 170.64 | 0.00 |
July | 18208.55 | 02-JUL-18:31 | 0.00 | 684.02 | 5591.71 | 0.00 | 0.00 | 0.00 | 0.00 | 3.95 | 0.00 |
August | 11536.05 | 04-AUG-15:10 | 1923.11 | 1231.33 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 74.42 | 0.00 |
September | 13749.71 | 11-SEP-04:12 | 0.00 | 1725.34 | 4473.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 224.54 |
October | 5946.75 | 10-OCT-13:30 | 2010.79 | 1231.33 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 79.41 |
November | 4729.64 | 07-NOV-13:30 | 1923.11 | 1231.33 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.46 |
December | 2793.73 | 05-DEC-13:30 | 5769.33 | 3693.99 | 6481.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 618.81 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2216.43 | 0.00 | 547.28 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 18314.39 | 5769.33 | 3693.99 | 7201.84 | 0.00 | 0.00 | 0.00 | 0.00 | 176.13 | 618.81 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3027.09 | 13-JAN-10:40 | 2591.66 | 1587.03 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 158.31 |
February | 7620.85 | 24-FEB-09:15 | 2478.65 | 1587.03 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 125.36 |
March | 9839.18 | 28-MAR-08:55 | 2478.65 | 1587.03 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 237.74 |
April | 19477.15 | 30-APR-08:52 | 326.14 | 220.40 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 169.10 |
May | 20814.26 | 21-MAY-08:52 | 326.14 | 220.40 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 167.88 |
June | 28696.46 | 25-JUN-08:11 | 587.05 | 396.73 | 4177.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 167.70 |
July | 28679.97 | 02-JUL-09:11 | 652.28 | 440.81 | 4641.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 92.49 |
August | 27102.74 | 20-AUG-08:51 | 456.59 | 308.57 | 3248.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 163.95 |
September | 25418.20 | 03-SEP-09:52 | 391.37 | 264.49 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 290.20 |
October | 9267.92 | 20-OCT-09:00 | 1239.33 | 793.52 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57.08 |
November | 7199.07 | 04-NOV-08:40 | 1174.10 | 793.52 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 78.70 |
December | 3644.12 | 01-DEC-10:25 | 2591.66 | 1587.03 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 302.07 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3027.09 | 326.14 | 220.40 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57.08 | |
Maximum of Months | 28696.46 | 2591.66 | 1587.03 | 4641.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 302.07 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 16438.43 | 04-JAN-12:00 | 3846.30 | 2462.72 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 302.65 |
February | 20204.16 | 16-FEB-13:30 | 5769.46 | 3694.08 | 6481.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 375.62 |
March | 27522.32 | 19-MAR-12:23 | 404.87 | 273.61 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 602.00 |
April | 30525.77 | 16-APR-13:11 | 708.53 | 478.83 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 144.24 |
May | 26608.00 | 29-MAY-12:53 | 404.87 | 273.61 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 52.42 |
June | 29009.42 | 25-JUN-12:52 | 607.31 | 410.42 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 204.82 | 0.00 |
July | 30118.89 | 30-JUL-13:01 | 708.53 | 478.83 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40.89 |
August | 27694.61 | 13-AUG-13:22 | 506.09 | 342.02 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 76.31 |
September | 32217.79 | 04-SEP-13:11 | 809.75 | 547.23 | 5761.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 161.87 |
October | 28275.07 | 01-OCT-13:42 | 506.09 | 342.02 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 455.90 |
November | 28707.23 | 05-NOV-14:02 | 506.09 | 342.02 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 346.76 |
December | 27349.39 | 03-DEC-12:13 | 404.87 | 273.61 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1621.70 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 16438.43 | 404.87 | 273.61 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 32217.79 | 5769.46 | 3694.08 | 6481.75 | 0.00 | 0.00 | 0.00 | 0.00 | 204.82 | 1621.70 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 5563.87 | 12-JAN-15:20 | 1239.33 | 793.52 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 162.22 |
February | 10493.97 | 24-FEB-16:20 | 1239.33 | 793.52 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 102.23 |
March | 12915.49 | 19-MAR-15:02 | 260.91 | 176.32 | 1856.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 337.36 |
April | 36156.69 | 16-APR-16:31 | 652.28 | 440.81 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 110.00 |
May | 31098.09 | 14-MAY-16:41 | 456.59 | 308.57 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 68.71 |
June | 36342.73 | 25-JUN-16:51 | 652.28 | 440.81 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 50.20 | 0.00 |
July | 36533.68 | 02-JUL-16:31 | 652.28 | 440.81 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47.37 |
August | 31823.97 | 13-AUG-16:01 | 456.59 | 308.57 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 82.83 |
September | 33988.79 | 04-SEP-16:31 | 587.05 | 396.73 | 4177.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 68.38 |
October | 19028.56 | 01-OCT-15:02 | 326.14 | 220.40 | 2320.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 270.05 |
November | 24605.25 | 05-NOV-14:42 | 326.14 | 220.40 | 2320.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 174.96 |
December | 7525.38 | 01-DEC-15:30 | 1239.33 | 793.52 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 113.13 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 5563.87 | 260.91 | 176.32 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 36533.68 | 1239.33 | 793.52 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 50.20 | 337.36 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1555.62 | 14-JAN-17:02 | 607.30 | 862.58 | 4321.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 813.43 |
February | 2324.27 | 24-FEB-13:50 | 1923.11 | 1231.33 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 312.67 |
March | 4537.77 | 30-MAR-12:05 | 7692.44 | 4925.33 | 8642.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1089.07 |
April | 8467.11 | 18-APR-15:00 | 1923.11 | 1231.33 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 210.65 | 0.00 |
May | 9180.71 | 31-MAY-15:00 | 1923.11 | 1231.33 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 130.70 | 0.00 |
June | 18911.86 | 25-JUN-18:22 | 0.00 | 684.02 | 5591.71 | 0.00 | 0.00 | 0.00 | 0.00 | 453.42 | 0.00 |
July | 18270.11 | 02-JUL-18:31 | 0.00 | 684.02 | 5591.71 | 0.00 | 0.00 | 0.00 | 0.00 | 22.23 | 0.00 |
August | 11267.01 | 04-AUG-05:03 | 809.73 | 1150.23 | 3840.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.08 |
September | 9379.79 | 11-SEP-14:00 | 2010.79 | 1231.33 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 174.85 | 0.00 |
October | 3323.91 | 26-OCT-16:10 | 1214.60 | 1500.89 | 2400.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 215.36 |
November | 3959.96 | 09-NOV-17:05 | 1214.60 | 2875.44 | 2400.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1013.19 |
December | 1566.39 | 30-DEC-17:02 | 607.30 | 862.58 | 4321.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 398.05 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1555.62 | 0.00 | 684.02 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 18911.86 | 7692.44 | 4925.33 | 8642.21 | 0.00 | 0.00 | 0.00 | 0.00 | 453.42 | 1089.07 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2569.57 | 13-JAN-11:50 | 1239.33 | 793.52 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 328.21 |
February | 4028.93 | 24-FEB-09:55 | 2478.65 | 1587.03 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 256.96 |
March | 9650.14 | 31-MAR-09:50 | 0.00 | 1587.03 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 508.57 |
April | 17268.28 | 30-APR-09:32 | 326.14 | 220.40 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 439.87 |
May | 28014.35 | 21-MAY-08:41 | 456.59 | 308.57 | 3248.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 444.49 |
June | 31413.69 | 25-JUN-09:01 | 652.28 | 440.81 | 4641.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 344.06 |
July | 31526.21 | 02-JUL-09:11 | 652.28 | 440.81 | 4641.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 254.77 |
August | 28810.42 | 20-AUG-08:41 | 456.59 | 308.57 | 3248.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 419.08 |
September | 28533.32 | 04-SEP-09:01 | 456.59 | 308.57 | 3248.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 310.12 |
October | 7684.77 | 20-OCT-09:00 | 1239.33 | 793.52 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 135.11 |
November | 3627.90 | 04-NOV-09:30 | 0.00 | 264.51 | 773.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 208.91 |
December | 3021.26 | 01-DEC-17:57 | 1174.10 | 2779.57 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 157.87 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2569.57 | 0.00 | 220.40 | 773.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 135.11 | |
Maximum of Months | 31526.21 | 2478.65 | 2779.57 | 4641.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 508.57 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 19182.49 | 12-JAN-14:30 | 4021.67 | 2462.72 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 576.34 |
February | 23544.19 | 08-FEB-13:10 | 3846.30 | 2462.72 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 678.70 |
March | 23049.45 | 10-MAR-13:50 | 5769.46 | 3694.08 | 6481.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 629.28 |
April | 28867.57 | 16-APR-13:22 | 506.09 | 342.02 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.98 |
May | 21566.23 | 14-MAY-12:32 | 404.87 | 273.61 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 244.56 |
June | 29540.89 | 25-JUN-12:22 | 607.31 | 410.42 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 424.49 | 0.00 |
July | 31214.31 | 30-JUL-13:01 | 708.53 | 478.83 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 111.07 |
August | 30303.17 | 13-AUG-13:12 | 607.31 | 410.42 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 358.76 |
September | 33092.95 | 17-SEP-13:31 | 910.97 | 615.63 | 6481.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 549.96 |
October | 31662.69 | 01-OCT-12:51 | 708.53 | 478.83 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1334.06 |
November | 27785.34 | 05-NOV-13:32 | 404.87 | 273.61 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1011.11 |
December | 22288.87 | 01-DEC-11:54 | 9615.76 | 6156.79 | 10802.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 700.87 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 19182.49 | 404.87 | 273.61 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 33092.95 | 9615.76 | 6156.79 | 10802.92 | 0.00 | 0.00 | 0.00 | 0.00 | 424.49 | 1334.06 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4471.38 | 13-JAN-14:45 | 2591.66 | 1587.03 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 301.66 |
February | 7254.60 | 24-FEB-16:30 | 1239.33 | 793.52 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 235.92 |
March | 8848.60 | 21-MAR-15:50 | 1239.33 | 793.52 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 640.07 |
April | 29323.02 | 16-APR-16:01 | 456.59 | 308.57 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 122.29 | 0.00 |
May | 32255.13 | 14-MAY-17:11 | 0.00 | 396.73 | 3243.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 305.02 |
June | 34350.60 | 25-JUN-17:01 | 0.00 | 440.81 | 3603.49 | 0.00 | 0.00 | 0.00 | 0.00 | 70.49 | 0.00 |
July | 33705.13 | 02-JUL-16:31 | 652.28 | 440.81 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 106.27 |
August | 29887.05 | 13-AUG-16:31 | 652.28 | 440.81 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 214.62 |
September | 31742.37 | 04-SEP-16:21 | 587.05 | 396.73 | 4177.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 161.15 |
October | 11596.29 | 11-OCT-16:00 | 1239.33 | 793.52 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 133.59 |
November | 7710.07 | 03-NOV-15:30 | 1239.33 | 793.52 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 145.93 |
December | 3582.73 | 01-DEC-17:57 | 1174.10 | 2779.57 | 2320.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 163.68 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3582.73 | 0.00 | 308.57 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 34350.60 | 2591.66 | 2779.57 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 122.29 | 640.07 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1728.33 | 14-JAN-17:02 | 607.30 | 862.58 | 4321.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1009.83 |
February | 2206.17 | 24-FEB-14:30 | 4021.58 | 2462.66 | 4321.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 373.87 |
March | 2647.79 | 28-MAR-15:30 | 1923.11 | 1231.33 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 424.93 |
April | 21796.80 | 16-APR-15:41 | 1012.16 | 684.02 | 7201.84 | 0.00 | 0.00 | 0.00 | 0.00 | 511.15 | 0.00 |
May | 10074.56 | 31-MAY-15:00 | 1923.11 | 1231.33 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 159.28 | 0.00 |
June | 22550.57 | 11-JUN-15:21 | 910.95 | 615.62 | 6481.66 | 0.00 | 0.00 | 0.00 | 0.00 | 1121.43 | 0.00 |
July | 22381.28 | 04-JUL-18:41 | 0.00 | 547.22 | 4473.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 118.22 |
August | 11547.25 | 03-AUG-05:03 | 809.73 | 1150.23 | 3840.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.80 |
September | 9828.94 | 11-SEP-14:00 | 2010.79 | 1231.33 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 212.15 | 0.00 |
October | 3547.38 | 20-OCT-14:00 | 2010.79 | 1231.33 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.69 |
November | 3107.47 | 03-NOV-13:30 | 2010.79 | 1231.33 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 248.76 |
December | 1749.90 | 30-DEC-17:02 | 607.30 | 862.58 | 4321.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 494.72 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1728.33 | 0.00 | 547.22 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 22550.57 | 4021.58 | 2462.66 | 7201.84 | 0.00 | 0.00 | 0.00 | 0.00 | 1121.43 | 1009.83 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2107.08 | 13-JAN-06:04 | 1043.64 | 1482.50 | 4950.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 312.74 |
February | 2962.26 | 24-FEB-09:55 | 2478.65 | 1587.03 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 315.20 |
March | 6067.53 | 28-MAR-09:45 | 2591.66 | 1587.03 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 577.96 |
April | 23389.66 | 16-APR-15:41 | 652.28 | 440.81 | 4641.14 | 0.00 | 0.00 | 0.00 | 0.00 | 335.94 | 0.00 |
May | 26899.09 | 14-MAY-08:31 | 456.59 | 308.57 | 3248.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 668.60 |
June | 29967.56 | 11-JUN-08:61 | 521.82 | 352.65 | 3712.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 236.25 |
July | 28550.63 | 23-JUL-09:31 | 456.59 | 308.57 | 3248.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 290.48 |
August | 21860.02 | 27-AUG-09:32 | 326.14 | 220.40 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 123.44 |
September | 19231.28 | 04-SEP-09:22 | 326.14 | 220.40 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 386.97 |
October | 6448.87 | 20-OCT-09:40 | 1295.83 | 793.52 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 162.81 |
November | 3179.85 | 03-NOV-13:30 | 1295.83 | 793.52 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 159.73 |
December | 1821.75 | 30-DEC-17:02 | 391.37 | 555.88 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 328.84 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1821.75 | 326.14 | 220.40 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 29967.56 | 2591.66 | 1587.03 | 4950.55 | 0.00 | 0.00 | 0.00 | 0.00 | 335.94 | 668.60 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 13186.18 | 12-JAN-12:40 | 1058.33 | 1231.36 | 1920.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 526.52 |
February | 20170.01 | 24-FEB-13:40 | 1923.15 | 1231.36 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 467.26 |
March | 18154.79 | 24-MAR-13:20 | 2010.83 | 1231.36 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 672.77 |
April | 34172.94 | 16-APR-13:41 | 809.75 | 547.23 | 5761.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 431.69 |
May | 17966.18 | 30-MAY-13:20 | 2010.83 | 1231.36 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 46.33 | 0.00 |
June | 30275.67 | 11-JUN-14:41 | 910.97 | 615.63 | 6481.75 | 0.00 | 0.00 | 0.00 | 0.00 | 953.20 | 0.00 |
July | 30720.14 | 30-JUL-13:12 | 506.09 | 342.02 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.69 |
August | 32354.06 | 13-AUG-13:42 | 607.31 | 410.42 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 402.21 |
September | 32141.73 | 17-SEP-13:42 | 607.31 | 410.42 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 266.76 |
October | 30885.03 | 01-OCT-14:01 | 809.75 | 547.23 | 5761.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1361.02 |
November | 21651.92 | 03-NOV-13:30 | 2010.83 | 1231.36 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 297.17 |
December | 15343.22 | 01-DEC-13:25 | 3846.30 | 2462.72 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 736.45 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 13186.18 | 506.09 | 342.02 | 1920.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 34172.94 | 3846.30 | 2462.72 | 6481.75 | 0.00 | 0.00 | 0.00 | 0.00 | 953.20 | 1361.02 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3040.95 | 12-JAN-15:50 | 1239.33 | 793.52 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 530.97 |
February | 7172.28 | 24-FEB-16:30 | 1239.33 | 793.52 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 294.87 |
March | 7526.15 | 21-MAR-16:00 | 1239.33 | 793.52 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 834.56 |
April | 34301.96 | 16-APR-16:21 | 652.28 | 440.81 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 269.06 |
May | 33646.81 | 14-MAY-17:11 | 0.00 | 396.73 | 3243.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 378.89 |
June | 32446.09 | 25-JUN-17:11 | 0.00 | 352.65 | 2882.79 | 0.00 | 0.00 | 0.00 | 0.00 | 306.06 | 0.00 |
July | 35065.65 | 23-JUL-16:51 | 652.28 | 440.81 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 147.37 |
August | 33587.53 | 13-AUG-15:41 | 587.05 | 396.73 | 4177.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 361.99 |
September | 29430.48 | 04-SEP-16:42 | 391.37 | 264.49 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 148.28 |
October | 11507.45 | 11-OCT-16:00 | 1239.33 | 793.52 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 168.73 |
November | 7462.43 | 03-NOV-15:30 | 1239.33 | 793.52 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 183.49 |
December | 3076.85 | 01-DEC-15:50 | 1239.33 | 793.52 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 293.91 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3040.95 | 0.00 | 264.49 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 35065.65 | 1239.33 | 793.52 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 306.06 | 834.56 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 11005.79 | 19-JAN-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7396.01 |
February | 9605.21 | 02-FEB-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5077.62 |
March | 7410.01 | 06-MAR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4341.34 |
April | 8558.67 | 18-APR-15:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 124.58 | 0.00 |
May | 9175.75 | 30-MAY-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 145.18 |
June | 9937.75 | 26-JUN-15:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 115.14 | 0.00 |
July | 10861.90 | 03-JUL-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 139.76 |
August | 10004.01 | 21-AUG-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 105.04 |
September | 10301.68 | 11-SEP-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 110.07 |
October | 4830.79 | 12-OCT-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 310.03 |
November | 7350.75 | 28-NOV-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1139.76 |
December | 8539.77 | 09-DEC-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7652.17 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 4830.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 11005.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 124.58 | 7652.17 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 12053.25 | 07-JAN-04:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4055.17 |
February | 12391.55 | 18-FEB-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2750.89 |
March | 11724.30 | 21-MAR-03:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8765.58 |
April | 11748.27 | 03-APR-03:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5334.86 |
May | 6744.05 | 02-MAY-04:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3936.80 |
June | 8552.53 | 30-JUN-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 84.17 |
July | 7939.31 | 05-JUL-15:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43.14 | 0.00 |
August | 8327.55 | 04-AUG-15:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 244.40 | 0.00 |
September | 9483.37 | 30-SEP-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2878.69 |
October | 10636.06 | 23-OCT-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2790.22 |
November | 11360.62 | 26-NOV-00:41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6735.01 |
December | 13435.68 | 09-DEC-03:41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12558.61 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 6744.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 13435.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 244.40 | 12558.61 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2979.41 |
February | 1307.40 | 24-FEB-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 709.29 |
March | 5356.00 | 24-MAR-14:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1216.40 |
April | 16400.26 | 18-APR-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 247.43 | 0.00 |
May | 18839.03 | 31-MAY-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 146.31 | 0.00 |
June | 21353.58 | 26-JUN-13:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 207.25 | 0.00 |
July | 20313.91 | 05-JUL-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.78 | 0.00 |
August | 21269.99 | 04-AUG-15:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 264.30 | 0.00 |
September | 17862.57 | 07-SEP-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 62.07 | 0.00 |
October | 7873.45 | 20-OCT-15:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 119.49 |
November | 4582.36 | 03-NOV-14:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 446.33 |
December | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4093.09 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 21353.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 264.30 | 4093.09 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 2075.13 | 12-JAN-16:30 | 222.14 | 578.72 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 4421.47 | 24-FEB-17:00 | 222.14 | 578.72 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6927.14 | 31-MAR-24:00 | 0.00 | 32.15 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 8539.08 | 16-APR-17:52 | 0.00 | 257.22 | 62355.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 3529.44 | 31-MAY-24:00 | 0.00 | 32.15 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5380.07 | 30-JUN-24:00 | 0.00 | 32.15 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 7261.24 | 31-JUL-24:00 | 0.00 | 32.15 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 8484.84 | 29-AUG-17:50 | 23.38 | 192.90 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 3010.69 | 30-SEP-24:00 | 0.00 | 32.15 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 5015.89 | 31-OCT-24:00 | 0.00 | 32.15 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6198.07 | 05-NOV-16:17 | 35.07 | 96.46 | 17537.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 7976.10 | 05-DEC-16:10 | 222.14 | 578.72 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 2075.13 | 0.00 | 32.15 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 8539.08 | 222.14 | 578.72 | 62355.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 1703.52 | 12-JAN-16:40 | 222.14 | 578.72 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 3995.35 | 24-FEB-17:00 | 222.14 | 578.72 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6032.93 | 31-MAR-23:20 | 0.00 | 32.15 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 7942.89 | 16-APR-17:42 | 0.00 | 321.53 | 77944.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 3334.66 | 31-MAY-24:00 | 0.00 | 32.15 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5232.27 | 30-JUN-24:00 | 0.00 | 32.15 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6892.90 | 31-JUL-24:00 | 0.00 | 32.15 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 8109.00 | 29-AUG-17:40 | 23.38 | 192.90 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 2641.94 | 04-SEP-17:50 | 0.00 | 225.07 | 13640.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 4215.60 | 31-OCT-23:30 | 0.00 | 32.15 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5746.21 | 03-NOV-16:00 | 222.14 | 578.72 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 7209.24 | 01-DEC-16:20 | 222.14 | 578.72 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 1703.52 | 0.00 | 32.15 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 8109.00 | 222.14 | 578.72 | 77944.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 1609.45 | 12-JAN-16:40 | 222.14 | 578.72 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 4007.90 | 24-FEB-17:00 | 222.14 | 578.72 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 5805.51 | 21-MAR-17:40 | 23.38 | 192.90 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 8221.11 | 16-APR-17:52 | 0.00 | 257.22 | 62355.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 3297.44 | 31-MAY-23:30 | 0.00 | 32.15 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5206.12 | 30-JUN-24:00 | 0.00 | 32.15 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6786.35 | 31-JUL-24:00 | 0.00 | 32.15 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 8169.03 | 29-AUG-17:40 | 23.38 | 192.90 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 2652.10 | 04-SEP-17:50 | 0.00 | 225.07 | 13640.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 4205.90 | 11-OCT-17:00 | 70.15 | 321.51 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5740.39 | 03-NOV-16:00 | 222.14 | 578.72 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 7087.52 | 01-DEC-16:20 | 222.14 | 578.72 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 1609.45 | 0.00 | 32.15 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 8221.11 | 222.14 | 578.72 | 62355.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 91529.91 | 13-JAN-17:00 | 9617.36 | 12942.03 | 189816.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 183532.78 | 24-FEB-17:00 | 4808.68 | 6471.01 | 189816.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 358422.09 | 31-MAR-24:00 | 0.00 | 359.47 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 371580.41 | 18-APR-17:45 | 1012.35 | 4314.01 | 759265.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 176492.67 | 31-MAY-24:00 | 0.00 | 359.47 | 189816.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 268583.40 | 30-JUN-24:00 | 0.00 | 359.47 | 284724.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 360918.16 | 31-JUL-24:00 | 0.00 | 359.47 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 389338.94 | 04-AUG-17:53 | 2024.71 | 8628.02 | 1518530.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 175361.13 | 30-SEP-24:00 | 0.00 | 359.47 | 189816.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 268259.93 | 31-OCT-24:00 | 0.00 | 359.47 | 284724.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 277322.07 | 03-NOV-16:00 | 4808.68 | 6471.01 | 284724.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 367947.76 | 05-DEC-17:00 | 4808.68 | 6471.01 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 91529.91 | 0.00 | 359.47 | 189816.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 389338.94 | 9617.36 | 12942.03 | 1518530.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.169113E+13 | 1125577.10 | 02-JAN-16:40 | 0.135234E+13 | 3389064.52 | 30-JAN-07:10 |
February | 0.189668E+13 | 1207287.27 | 14-FEB-08:09 | 0.972021E+12 | 3296034.41 | 02-FEB-07:10 |
March | 0.250398E+13 | 1459174.73 | 23-MAR-15:00 | 0.424874E+12 | 1778970.67 | 13-MAR-06:10 |
April | 0.274353E+13 | 2018504.32 | 18-APR-15:09 | 0.202967E+12 | 1543645.52 | 03-APR-06:10 |
May | 0.173672E+13 | 1530922.83 | 31-MAY-15:09 | 0.817674E+11 | 674060.81 | 02-MAY-06:10 |
June | 0.228319E+13 | 1844319.80 | 26-JUN-07:49 | 0.715397E+11 | 357595.61 | 02-JUN-06:10 |
July | 0.287990E+13 | 1980038.24 | 03-JUL-15:20 | 0.655389E+11 | 81584.64 | 03-JUL-11:00 |
August | 0.332174E+13 | 2184392.29 | 04-AUG-15:30 | 0.684018E+11 | 80041.72 | 02-AUG-11:50 |
September | 0.174712E+13 | 1552180.99 | 08-SEP-15:00 | 0.825302E+11 | 818940.94 | 29-SEP-06:10 |
October | 0.208008E+13 | 1423749.12 | 20-OCT-15:09 | 0.160213E+12 | 1035864.33 | 23-OCT-06:10 |
November | 0.237621E+13 | 1444327.64 | 03-NOV-15:09 | 0.479758E+12 | 1969864.74 | 24-NOV-07:10 |
December | 0.281340E+13 | 1576624.09 | 01-DEC-16:00 | 0.849173E+12 | 1941288.14 | 26-DEC-07:10 |
Annual Sum or Average | 0.280737E+14 | 0.481113E+13 | ||||
Minimum of Months | 0.169113E+13 | 1125577.10 | 0.655389E+11 | 80041.72 | ||
Maximum of Months | 0.332174E+13 | 2184392.29 | 0.135234E+13 | 3389064.52 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [J] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [J] | HUMIDIFIER:ELECTRICITY [J] | HEATRECOVERY:ELECTRICITY [J] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 0.335189E+12 | 0.777007E+11 | 0.766053E+12 | 0.164272E+12 | 0.191768E+12 | 0.204962E+11 | 0.00 | 0.594405E+10 | 0.410648E+09 | 0.122075E+12 | 0.721856E+10 | 0.00 | 0.00 |
February | 0.299959E+12 | 0.634957E+11 | 0.978954E+12 | 0.148382E+12 | 0.167080E+12 | 0.159196E+11 | 0.00 | 0.207536E+11 | 0.192332E+10 | 0.193720E+12 | 0.648703E+10 | 0.00 | 0.00 |
March | 0.351980E+12 | 0.610484E+11 | 0.141687E+13 | 0.164522E+12 | 0.187429E+12 | 0.185673E+11 | 0.00 | 0.447467E+11 | 0.805745E+10 | 0.244194E+12 | 0.656816E+10 | 0.00 | 0.00 |
April | 0.313059E+12 | 0.495995E+11 | 0.165903E+13 | 0.158945E+12 | 0.190877E+12 | 0.254130E+11 | 0.00 | 0.118343E+12 | 0.331010E+11 | 0.190871E+12 | 0.429764E+10 | 0.00 | 0.00 |
May | 0.335753E+12 | 0.437130E+11 | 0.774844E+12 | 0.164393E+12 | 0.213765E+12 | 0.364852E+11 | 0.00 | 0.844159E+11 | 0.417626E+11 | 0.400873E+11 | 0.150151E+10 | 0.00 | 0.00 |
June | 0.333668E+12 | 0.388732E+11 | 0.106252E+13 | 0.159182E+12 | 0.249311E+12 | 0.543568E+11 | 0.00 | 0.271120E+12 | 0.109088E+12 | 0.287819E+10 | 0.220011E+10 | 0.00 | 0.00 |
July | 0.312727E+12 | 0.413344E+11 | 0.139340E+13 | 0.164155E+12 | 0.259445E+12 | 0.722767E+11 | 0.00 | 0.479450E+12 | 0.154887E+12 | 415210.40 | 0.221845E+10 | 0.00 | 0.00 |
August | 0.348705E+12 | 0.476091E+11 | 0.173200E+13 | 0.164521E+12 | 0.264909E+12 | 0.713224E+11 | 0.00 | 0.533817E+12 | 0.152333E+12 | 0.420235E+10 | 0.232061E+10 | 0.00 | 0.00 |
September | 0.313804E+12 | 0.548509E+11 | 0.740713E+12 | 0.158944E+12 | 0.213355E+12 | 0.377276E+11 | 0.00 | 0.118984E+12 | 0.610446E+11 | 0.450499E+11 | 0.264468E+10 | 0.00 | 0.00 |
October | 0.328495E+12 | 0.664725E+11 | 0.108340E+13 | 0.164269E+12 | 0.186133E+12 | 0.192378E+11 | 0.00 | 0.390458E+11 | 0.112611E+11 | 0.177710E+12 | 0.405256E+10 | 0.00 | 0.00 |
November | 0.330448E+12 | 0.727815E+11 | 0.135889E+13 | 0.159045E+12 | 0.177064E+12 | 0.160993E+11 | 0.00 | 0.399375E+11 | 0.621946E+10 | 0.210325E+12 | 0.539608E+10 | 0.00 | 0.00 |
December | 0.327682E+12 | 0.800155E+11 | 0.170972E+13 | 0.164163E+12 | 0.185759E+12 | 0.150122E+11 | 0.00 | 0.516868E+11 | 0.438106E+10 | 0.267840E+12 | 0.714539E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.393147E+13 | 0.697494E+12 | 0.146764E+14 | 0.193479E+13 | 0.248689E+13 | 0.402914E+12 | 0.00 | 0.180825E+13 | 0.584469E+12 | 0.149895E+13 | 0.520508E+11 | 0.00 | 0.00 |
Minimum of Months | 0.299959E+12 | 0.388732E+11 | 0.740713E+12 | 0.148382E+12 | 0.167080E+12 | 0.150122E+11 | 0.00 | 0.594405E+10 | 0.410648E+09 | 415210.40 | 0.150151E+10 | 0.00 | 0.00 |
Maximum of Months | 0.351980E+12 | 0.800155E+11 | 0.173200E+13 | 0.164522E+12 | 0.264909E+12 | 0.722767E+11 | 0.00 | 0.533817E+12 | 0.154887E+12 | 0.267840E+12 | 0.721856E+10 | 0.00 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [J] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.00 | 0.00 | 0.127506E+13 | 0.00 | 0.772830E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.900945E+12 | 0.00 | 0.710764E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.343317E+12 | 0.00 | 0.815569E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.129658E+12 | 0.00 | 0.733089E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.747431E+10 | 0.00 | 0.742931E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.187541E+10 | 0.00 | 0.696643E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 31968.45 | 0.00 | 0.655389E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 56518575.98 | 0.00 | 0.683452E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.185801E+11 | 0.00 | 0.639501E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.920276E+11 | 0.00 | 0.681855E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.410091E+12 | 0.00 | 0.696668E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.775781E+12 | 0.00 | 0.733922E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.395487E+13 | 0.00 | 0.856261E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 31968.45 | 0.00 | 0.639501E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.127506E+13 | 0.00 | 0.815569E+11 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | EXTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum} [W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 385834.94 | 02-JAN-16:40 | 57580.60 | 01-JAN-06:10 | 423497.50 | 02-JAN-08:09 | 118535.44 | 17-JAN-08:20 | 113765.48 | 02-JAN-06:19 | 35585.66 | 02-JAN-07:19 | 0.00 | 01-JAN-00:10 |
February | 372703.55 | 14-FEB-16:00 | 57580.60 | 01-FEB-06:10 | 541788.89 | 01-FEB-08:09 | 118518.19 | 22-FEB-08:20 | 113286.80 | 06-FEB-06:10 | 35169.38 | 01-FEB-06:10 | 0.00 | 01-FEB-00:10 |
March | 352283.84 | 01-MAR-16:00 | 57580.60 | 01-MAR-06:10 | 660080.29 | 01-MAR-08:09 | 118503.54 | 13-MAR-07:19 | 200982.95 | 10-MAR-15:30 | 34246.31 | 13-MAR-05:10 | 0.00 | 01-MAR-00:10 |
April | 352283.84 | 10-APR-07:10 | 57580.60 | 01-APR-05:10 | 778371.69 | 03-APR-07:10 | 118509.21 | 10-APR-07:19 | 261924.54 | 18-APR-15:09 | 58486.39 | 18-APR-12:39 | 0.00 | 01-APR-00:10 |
May | 333218.76 | 09-MAY-15:20 | 57580.60 | 01-MAY-19:10 | 423497.50 | 01-MAY-07:10 | 118494.36 | 25-MAY-07:19 | 245479.05 | 31-MAY-14:00 | 57730.58 | 30-MAY-10:00 | 0.00 | 01-MAY-00:10 |
June | 339487.29 | 13-JUN-07:10 | 57580.60 | 01-JUN-19:40 | 541788.89 | 01-JUN-07:10 | 118499.24 | 13-JUN-07:19 | 281882.05 | 26-JUN-15:30 | 60668.28 | 26-JUN-07:49 | 0.00 | 01-JUN-00:10 |
July | 339487.29 | 20-JUL-07:10 | 57580.60 | 01-JUL-19:00 | 660080.29 | 03-JUL-07:10 | 118499.24 | 20-JUL-07:19 | 271656.82 | 03-JUL-15:20 | 60287.14 | 05-JUL-10:30 | 0.00 | 01-JUL-00:10 |
August | 336086.21 | 31-AUG-07:10 | 57580.60 | 01-AUG-19:40 | 778371.69 | 01-AUG-07:10 | 118496.59 | 31-AUG-07:19 | 307984.46 | 04-AUG-15:20 | 65178.11 | 04-AUG-07:19 | 0.00 | 01-AUG-00:10 |
September | 352283.84 | 21-SEP-07:10 | 57580.60 | 01-SEP-05:10 | 423497.50 | 01-SEP-07:10 | 118509.21 | 21-SEP-07:19 | 273284.00 | 08-SEP-15:00 | 59493.25 | 07-SEP-12:00 | 0.00 | 01-SEP-00:10 |
October | 385834.94 | 31-OCT-07:10 | 57580.60 | 01-OCT-05:10 | 541788.89 | 02-OCT-07:10 | 118535.44 | 31-OCT-07:19 | 200702.63 | 23-OCT-09:50 | 31156.21 | 27-OCT-05:10 | 0.00 | 01-OCT-00:10 |
November | 385834.94 | 01-NOV-07:10 | 57580.60 | 01-NOV-05:10 | 660080.29 | 01-NOV-07:10 | 118535.44 | 01-NOV-07:19 | 162041.98 | 10-NOV-15:39 | 33682.49 | 21-NOV-06:10 | 0.00 | 01-NOV-00:10 |
December | 385834.94 | 01-DEC-16:30 | 57580.60 | 01-DEC-06:10 | 778371.69 | 01-DEC-08:09 | 118535.44 | 20-DEC-08:20 | 132250.30 | 01-DEC-17:00 | 34093.43 | 12-DEC-06:40 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 333218.76 | 57580.60 | 423497.50 | 118494.36 | 113286.80 | 31156.21 | 0.00 | |||||||
Maximum of Months | 385834.94 | 57580.60 | 778371.69 | 118535.44 | 307984.46 | 65178.11 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY {Maximum} [W] | HEATREJECTION:ELECTRICITY {TIMESTAMP} | HUMIDIFIER:ELECTRICITY {Maximum} [W] | HUMIDIFIER:ELECTRICITY {TIMESTAMP} | HEATRECOVERY:ELECTRICITY {Maximum} [W] | HEATRECOVERY:ELECTRICITY {TIMESTAMP} | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 8840.25 | 12-JAN-16:49 | 945.19 | 12-JAN-16:19 | 53579.64 | 22-JAN-10:00 | 5613.48 | 02-JAN-07:10 | 0.00 | 0.00 |
February | 15516.51 | 17-FEB-16:49 | 2603.65 | 24-FEB-16:40 | 100000.00 | 14-FEB-14:30 | 5613.48 | 01-FEB-07:10 | 0.00 | 0.00 |
March | 99163.29 | 25-MAR-14:00 | 49612.69 | 19-MAR-14:09 | 100000.00 | 01-MAR-00:30 | 5613.48 | 01-MAR-07:10 | 0.00 | 0.00 |
April | 425397.32 | 18-APR-12:30 | 93806.32 | 18-APR-09:09 | 100000.00 | 01-APR-03:09 | 5613.48 | 01-APR-06:10 | 0.00 | 0.00 |
May | 309248.37 | 30-MAY-13:20 | 93806.32 | 12-MAY-13:30 | 100000.00 | 05-MAY-16:30 | 5613.48 | 01-MAY-06:10 | 0.00 | 0.00 |
June | 509376.46 | 26-JUN-07:49 | 93806.32 | 09-JUN-09:00 | 35870.93 | 01-JUN-03:00 | 5613.48 | 01-JUN-17:00 | 0.00 | 0.00 |
July | 527446.12 | 07-JUL-10:00 | 93806.32 | 03-JUL-07:19 | 692.02 | 18-JUL-07:00 | 5613.48 | 01-JUL-09:50 | 0.00 | 0.00 |
August | 638501.30 | 04-AUG-07:10 | 93806.32 | 01-AUG-07:40 | 100000.00 | 07-AUG-10:00 | 5613.48 | 01-AUG-09:30 | 0.00 | 0.00 |
September | 337947.26 | 11-SEP-09:39 | 93806.32 | 05-SEP-13:20 | 100000.00 | 15-SEP-14:00 | 5613.48 | 02-SEP-06:10 | 0.00 | 0.00 |
October | 186662.04 | 20-OCT-14:00 | 51676.39 | 20-OCT-14:00 | 100000.00 | 08-OCT-13:00 | 5613.48 | 03-OCT-06:10 | 0.00 | 0.00 |
November | 89192.88 | 03-NOV-13:00 | 32710.85 | 03-NOV-14:30 | 100000.00 | 03-NOV-21:10 | 5613.48 | 01-NOV-06:10 | 0.00 | 0.00 |
December | 24879.71 | 07-DEC-15:20 | 3503.09 | 02-DEC-13:00 | 100000.00 | 01-DEC-04:10 | 5613.48 | 01-DEC-07:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | ||||||||
Minimum of Months | 8840.25 | 945.19 | 692.02 | 5613.48 | 0.00 | 0.00 | ||||
Maximum of Months | 638501.30 | 93806.32 | 100000.00 | 5613.48 | 0.00 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY {AT MAX/MIN} [W] | |
January | 1125577.10 | 02-JAN-16:40 | 385834.94 | 423497.50 | 57580.60 | 84486.19 | 80696.96 | 30777.71 | 0.00 | 6064.84 | 323.15 |
February | 1207287.27 | 14-FEB-08:09 | 358473.27 | 541788.89 | 0.00 | 118332.99 | 79817.77 | 4780.18 | 0.00 | 7983.89 | 720.42 |
March | 1459174.73 | 23-MAR-15:00 | 332294.83 | 660080.29 | 0.00 | 84450.25 | 122303.67 | 29663.79 | 0.00 | 81044.04 | 49337.87 |
April | 2018504.32 | 18-APR-15:09 | 332294.83 | 778371.69 | 0.00 | 84450.25 | 261924.54 | 57370.52 | 0.00 | 404672.70 | 93806.32 |
May | 1530922.83 | 31-MAY-15:09 | 332294.83 | 423497.50 | 0.00 | 84450.25 | 244671.27 | 57252.45 | 0.00 | 289336.73 | 93806.32 |
June | 1844319.80 | 26-JUN-07:49 | 332294.83 | 541788.89 | 0.00 | 118493.64 | 187891.39 | 60668.28 | 0.00 | 509376.46 | 93806.32 |
July | 1980038.24 | 03-JUL-15:20 | 332294.83 | 660080.29 | 0.00 | 84450.25 | 271656.82 | 58464.33 | 0.00 | 473671.92 | 93806.32 |
August | 2184392.29 | 04-AUG-15:30 | 332294.83 | 778371.69 | 0.00 | 84450.25 | 302996.25 | 59159.97 | 0.00 | 527699.51 | 93806.32 |
September | 1552180.99 | 08-SEP-15:00 | 332294.83 | 423497.50 | 0.00 | 84450.25 | 273284.00 | 57401.78 | 0.00 | 281832.84 | 93806.32 |
October | 1423749.12 | 20-OCT-15:09 | 332294.83 | 541788.89 | 0.00 | 84450.25 | 137573.72 | 30092.49 | 0.00 | 180651.29 | 51545.06 |
November | 1444327.64 | 03-NOV-15:09 | 332294.83 | 660080.29 | 0.00 | 84450.25 | 149286.34 | 29651.65 | 0.00 | 59567.95 | 28996.34 |
December | 1576624.09 | 01-DEC-16:00 | 385834.94 | 778371.69 | 57580.60 | 84492.05 | 116761.87 | 22132.87 | 0.00 | 23681.55 | 2155.06 |
Annual Sum or Average | |||||||||||
Minimum of Months | 1125577.10 | 332294.83 | 423497.50 | 0.00 | 84450.25 | 79817.77 | 4780.18 | 0.00 | 6064.84 | 323.15 | |
Maximum of Months | 2184392.29 | 385834.94 | 778371.69 | 57580.60 | 118493.64 | 302996.25 | 60668.28 | 0.00 | 527699.51 | 93806.32 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS {Maximum} [W] | WATERSYSTEMS:NATURALGAS {TIMESTAMP} | COGENERATION:NATURALGAS [] | |
January | 0.00 | 0.00 | 3355734.44 | 30-JAN-07:10 | 0.00 | 88470.00 | 31-JAN-12:20 | 0.00 |
February | 0.00 | 0.00 | 3271177.54 | 02-FEB-07:10 | 0.00 | 88693.35 | 21-FEB-12:39 | 0.00 |
March | 0.00 | 0.00 | 1746226.03 | 13-MAR-06:10 | 0.00 | 88588.73 | 01-MAR-12:00 | 0.00 |
April | 0.00 | 0.00 | 1511057.68 | 03-APR-06:10 | 0.00 | 87751.18 | 03-APR-11:50 | 0.00 |
May | 0.00 | 0.00 | 641780.03 | 02-MAY-06:10 | 0.00 | 86265.81 | 01-MAY-11:39 | 0.00 |
June | 0.00 | 0.00 | 339846.96 | 03-JUN-06:10 | 0.00 | 83993.49 | 01-JUN-11:30 | 0.00 |
July | 0.00 | 0.00 | 53.28 | 24-JUL-06:10 | 0.00 | 81584.64 | 03-JUL-11:00 | 0.00 |
August | 0.00 | 0.00 | 28868.98 | 17-AUG-06:10 | 0.00 | 80041.72 | 02-AUG-11:50 | 0.00 |
September | 0.00 | 0.00 | 796954.49 | 29-SEP-06:10 | 0.00 | 80976.47 | 29-SEP-11:39 | 0.00 |
October | 0.00 | 0.00 | 1004166.59 | 23-OCT-06:10 | 0.00 | 83193.66 | 31-OCT-11:20 | 0.00 |
November | 0.00 | 0.00 | 1937746.29 | 24-NOV-07:10 | 0.00 | 85479.14 | 30-NOV-12:30 | 0.00 |
December | 0.00 | 0.00 | 1908820.79 | 26-DEC-07:10 | 0.00 | 87273.13 | 29-DEC-12:39 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 53.28 | 0.00 | 80041.72 | 0.00 | ||
Maximum of Months | 0.00 | 0.00 | 3355734.44 | 0.00 | 88693.35 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 25.69 | 0.00 | 25.69 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 25.72 | 0.00 | 25.72 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 25.84 | 0.00 | 25.84 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 25.71 | 0.00 | 25.71 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 25.93 | 0.00 | 25.93 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 26.54 | 0.00 | 26.54 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 3.83 | 26.62 | 0.00 | 26.62 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 7.83 | 26.38 | 0.00 | 26.38 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 26.82 | 0.00 | 26.82 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 3.83 | 26.44 | 0.83 | 26.62 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 26.75 | 0.00 | 26.75 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 25.69 | 0.00 | 25.69 |
Annual Sum or Average | 0.00 | 0.00 | 30.17 | 26.47 | 0.83 | 26.49 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 25.69 | 0.00 | 25.69 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 7.83 | 26.82 | 0.83 | 26.82 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 25.72 | 0.00 | 25.72 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 25.60 | 0.00 | 25.60 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.33 | 25.66 | 0.00 | 25.66 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 25.72 | 0.00 | 25.72 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 1.83 | 19.20 | 0.33 | 19.31 | 0.00 | 19.31 | 0.00 | 19.31 |
February | 0.33 | 19.24 | 0.00 | 19.24 | 0.00 | 19.24 | 0.00 | 19.24 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.17 | 19.16 | 0.00 | 19.16 | 0.00 | 19.16 | 0.00 | 19.16 |
December | 0.33 | 19.11 | 0.00 | 19.11 | 0.00 | 19.11 | 0.00 | 19.11 |
Annual Sum or Average | 2.67 | 19.19 | 0.33 | 19.28 | 0.00 | 19.28 | 0.00 | 19.28 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1.83 | 19.24 | 0.33 | 19.31 | 0.00 | 19.31 | 0.00 | 19.31 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 9.67 | 18.74 | 2.00 | 18.97 | 0.00 | 18.97 | 0.00 | 18.97 |
February | 4.00 | 18.61 | 0.50 | 18.74 | 0.00 | 18.74 | 0.00 | 18.74 |
March | 1.33 | 18.07 | 0.00 | 18.07 | 0.00 | 18.07 | 0.00 | 18.07 |
April | 0.50 | 18.14 | 0.00 | 18.14 | 0.00 | 18.14 | 0.00 | 18.14 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.17 | 19.26 | 0.00 | 19.26 | 0.00 | 19.26 | 0.00 | 19.26 |
November | 4.00 | 18.94 | 0.83 | 19.13 | 0.00 | 19.13 | 0.00 | 19.13 |
December | 5.83 | 18.82 | 1.17 | 18.99 | 0.00 | 18.99 | 0.00 | 18.99 |
Annual Sum or Average | 25.50 | 18.72 | 4.50 | 18.91 | 0.00 | 18.91 | 0.00 | 18.91 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 9.67 | 19.26 | 2.00 | 19.26 | 0.00 | 19.26 | 0.00 | 19.26 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 15.50 | 17.88 | 3.50 | 18.18 | 0.00 | 18.18 | 0.00 | 18.18 |
February | 8.00 | 18.15 | 1.67 | 18.44 | 0.00 | 18.44 | 0.00 | 18.44 |
March | 0.33 | 18.60 | 0.00 | 18.60 | 0.00 | 18.60 | 0.00 | 18.60 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 4.00 | 27.44 | 2.83 | 27.43 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 27.38 | 0.67 | 27.37 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 1.00 | 19.12 | 0.17 | 19.31 | 0.00 | 19.31 | 0.00 | 19.31 |
December | 2.83 | 18.47 | 0.50 | 18.72 | 0.00 | 18.72 | 0.00 | 18.72 |
Annual Sum or Average | 27.67 | 18.07 | 5.83 | 18.36 | 5.33 | 19.60 | 3.50 | 20.25 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 15.50 | 19.12 | 3.50 | 19.31 | 4.00 | 27.44 | 2.83 | 27.43 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 12.00 | 17.10 | 0.67 | 17.13 | 0.00 | 17.13 | 0.00 | 17.13 |
February | 5.50 | 17.14 | 0.33 | 17.31 | 0.00 | 17.31 | 0.00 | 17.31 |
March | 0.67 | 18.96 | 0.00 | 18.96 | 0.00 | 18.96 | 0.00 | 18.96 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 27.80 | 3.00 | 27.80 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 28.14 | 5.17 | 28.14 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 6.00 | 28.16 | 6.00 | 28.16 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 6.83 | 28.30 | 6.83 | 28.30 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 28.33 | 2.17 | 28.33 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 28.24 | 3.50 | 28.24 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 1.50 | 18.73 | 0.00 | 18.73 | 0.00 | 18.73 | 0.00 | 18.73 |
December | 3.17 | 18.26 | 0.17 | 18.36 | 0.00 | 18.36 | 0.00 | 18.36 |
Annual Sum or Average | 22.83 | 17.43 | 1.17 | 17.49 | 26.67 | 23.11 | 26.67 | 24.86 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 12.00 | 18.96 | 0.67 | 18.96 | 6.83 | 28.33 | 6.83 | 28.33 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 11.00 | 17.65 | 1.33 | 17.72 | 0.00 | 17.72 | 0.00 | 17.72 |
February | 5.00 | 17.80 | 0.33 | 17.94 | 0.83 | 19.07 | 0.83 | 19.93 |
March | 0.67 | 18.81 | 0.00 | 18.81 | 1.33 | 24.72 | 1.33 | 25.90 |
April | 0.17 | 19.19 | 0.00 | 19.19 | 4.50 | 27.61 | 4.33 | 27.77 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 27.59 | 2.67 | 27.59 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 4.67 | 27.93 | 4.50 | 27.94 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 6.33 | 27.92 | 5.83 | 27.95 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 5.67 | 27.94 | 5.67 | 27.94 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 7.00 | 28.15 | 6.83 | 28.16 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 4.00 | 28.09 | 4.00 | 28.09 |
November | 1.67 | 18.73 | 0.17 | 18.88 | 2.50 | 24.00 | 2.50 | 25.37 |
December | 3.17 | 18.25 | 0.17 | 18.34 | 1.33 | 20.80 | 1.33 | 22.17 |
Annual Sum or Average | 21.67 | 17.90 | 2.00 | 17.99 | 40.83 | 24.25 | 39.83 | 25.64 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.72 | 0.00 | 17.72 |
Maximum of Months | 11.00 | 19.19 | 1.33 | 19.19 | 7.00 | 28.15 | 6.83 | 28.16 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 5.17 | 18.45 | 0.00 | 18.45 | 0.00 | 18.45 | 0.00 | 18.45 |
February | 2.67 | 18.15 | 0.17 | 18.28 | 0.00 | 18.28 | 0.00 | 18.28 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.70 | 0.67 | 27.75 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 8.33 | 28.48 | 4.67 | 28.57 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 5.67 | 28.40 | 3.17 | 28.45 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 10.50 | 28.26 | 5.17 | 28.40 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 22.00 | 28.06 | 9.00 | 28.23 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 18.50 | 27.61 | 7.00 | 27.83 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 6.00 | 28.26 | 4.17 | 28.33 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 27.88 | 1.50 | 27.88 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 28.07 | 0.67 | 28.07 |
December | 0.83 | 18.77 | 0.00 | 18.77 | 0.00 | 18.77 | 0.00 | 18.77 |
Annual Sum or Average | 8.67 | 18.39 | 0.17 | 18.42 | 74.00 | 27.03 | 36.00 | 27.48 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.28 | 0.00 | 18.28 |
Maximum of Months | 5.17 | 18.77 | 0.17 | 18.77 | 22.00 | 28.48 | 9.00 | 28.57 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 121.67 | 16.39 | 50.83 | 16.73 | 0.00 | 16.73 | 0.00 | 16.73 |
February | 56.67 | 16.84 | 23.00 | 17.20 | 0.00 | 17.20 | 0.00 | 17.20 |
March | 21.83 | 17.03 | 6.33 | 17.13 | 0.00 | 17.13 | 0.00 | 17.13 |
April | 4.17 | 17.87 | 0.33 | 18.03 | 0.00 | 18.03 | 0.00 | 18.03 |
May | 0.17 | 19.42 | 0.00 | 19.42 | 0.00 | 19.42 | 0.00 | 19.42 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 27.45 | 1.83 | 27.45 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.32 | 0.00 | 27.32 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.17 | 19.39 | 0.00 | 19.39 | 0.00 | 19.39 | 0.00 | 19.39 |
October | 1.50 | 19.27 | 0.00 | 19.27 | 0.00 | 19.27 | 0.00 | 19.27 |
November | 27.00 | 16.59 | 8.00 | 16.81 | 0.00 | 16.81 | 0.00 | 16.81 |
December | 61.83 | 16.58 | 23.17 | 16.85 | 0.00 | 16.85 | 0.00 | 16.85 |
Annual Sum or Average | 295.00 | 16.62 | 111.67 | 16.91 | 3.17 | 16.99 | 1.83 | 17.03 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 121.67 | 19.42 | 50.83 | 19.42 | 3.00 | 27.45 | 1.83 | 27.45 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 63.00 | 14.99 | 12.67 | 14.91 | 0.00 | 14.91 | 0.00 | 14.91 |
February | 28.83 | 15.53 | 5.00 | 15.53 | 0.00 | 15.53 | 0.00 | 15.53 |
March | 13.50 | 16.56 | 0.50 | 16.50 | 0.00 | 16.50 | 0.00 | 16.50 |
April | 3.17 | 17.02 | 0.00 | 17.02 | 1.17 | 19.94 | 1.17 | 21.62 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 28.15 | 5.00 | 28.15 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 6.17 | 28.39 | 5.83 | 28.42 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 7.67 | 28.43 | 7.67 | 28.43 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 28.20 | 2.83 | 28.20 |
September | 0.17 | 19.42 | 0.00 | 19.42 | 3.33 | 27.79 | 3.33 | 27.99 |
October | 1.33 | 19.26 | 0.00 | 19.26 | 0.00 | 19.26 | 0.00 | 19.26 |
November | 18.00 | 15.48 | 3.17 | 15.36 | 0.00 | 15.36 | 0.00 | 15.36 |
December | 39.83 | 15.37 | 9.00 | 15.26 | 0.00 | 15.26 | 0.00 | 15.26 |
Annual Sum or Average | 167.83 | 15.43 | 30.33 | 15.33 | 26.17 | 16.84 | 25.83 | 18.03 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.91 | 0.00 | 14.91 |
Maximum of Months | 63.00 | 19.42 | 12.67 | 19.42 | 7.67 | 28.43 | 7.67 | 28.43 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 54.67 | 15.53 | 8.33 | 15.52 | 0.00 | 15.52 | 0.00 | 15.52 |
February | 26.50 | 16.15 | 2.67 | 16.24 | 0.00 | 16.24 | 0.00 | 16.24 |
March | 11.33 | 17.12 | 0.50 | 17.02 | 1.83 | 18.24 | 1.83 | 19.18 |
April | 2.67 | 17.24 | 0.00 | 17.24 | 3.17 | 23.07 | 3.00 | 24.75 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 27.61 | 2.17 | 27.61 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 4.83 | 27.97 | 4.17 | 28.01 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 6.00 | 27.95 | 5.50 | 27.97 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 27.89 | 5.17 | 27.89 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 9.33 | 27.02 | 9.17 | 27.01 |
October | 0.67 | 19.34 | 0.00 | 19.34 | 4.00 | 26.86 | 4.00 | 27.44 |
November | 16.67 | 15.93 | 2.83 | 15.87 | 1.50 | 16.73 | 1.50 | 17.47 |
December | 33.00 | 15.93 | 4.67 | 15.85 | 0.50 | 15.99 | 0.50 | 16.13 |
Annual Sum or Average | 145.50 | 15.95 | 19.00 | 15.92 | 38.50 | 18.13 | 37.00 | 19.60 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.52 | 0.00 | 15.52 |
Maximum of Months | 54.67 | 19.34 | 8.33 | 19.34 | 9.33 | 27.97 | 9.17 | 28.01 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 53.83 | 15.08 | 11.00 | 14.99 | 0.00 | 14.99 | 0.00 | 14.99 |
February | 25.17 | 15.74 | 3.83 | 15.74 | 0.00 | 15.74 | 0.00 | 15.74 |
March | 10.67 | 17.01 | 1.17 | 16.81 | 0.00 | 16.81 | 0.00 | 16.81 |
April | 1.17 | 18.43 | 0.00 | 18.43 | 4.00 | 25.88 | 2.50 | 26.54 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 4.50 | 28.41 | 2.00 | 28.46 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 6.67 | 28.77 | 3.33 | 28.86 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 10.83 | 28.74 | 5.00 | 28.78 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 28.28 | 3.17 | 28.28 |
September | 0.17 | 19.38 | 0.00 | 19.38 | 4.00 | 27.98 | 3.00 | 28.16 |
October | 0.67 | 19.27 | 0.00 | 19.27 | 0.33 | 21.97 | 0.33 | 23.32 |
November | 16.67 | 15.63 | 3.17 | 15.50 | 0.00 | 15.50 | 0.00 | 15.50 |
December | 30.17 | 15.65 | 5.33 | 15.51 | 0.00 | 15.51 | 0.00 | 15.51 |
Annual Sum or Average | 138.50 | 15.59 | 24.50 | 15.48 | 35.33 | 17.80 | 19.33 | 18.75 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.99 | 0.00 | 14.99 |
Maximum of Months | 53.83 | 19.38 | 11.00 | 19.38 | 10.83 | 28.77 | 5.00 | 28.86 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 155.00 | 15.67 | 66.50 | 16.00 | 0.00 | 16.00 | 0.00 | 16.00 |
February | 94.33 | 16.00 | 35.33 | 16.33 | 0.00 | 16.33 | 0.00 | 16.33 |
March | 34.50 | 16.36 | 7.67 | 16.47 | 0.00 | 16.47 | 0.00 | 16.47 |
April | 12.50 | 16.62 | 3.67 | 16.41 | 0.00 | 16.41 | 0.00 | 16.41 |
May | 0.50 | 19.14 | 0.00 | 19.14 | 0.00 | 19.14 | 0.00 | 19.14 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 4.50 | 27.65 | 2.83 | 27.64 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 27.40 | 0.67 | 27.39 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 1.00 | 18.98 | 0.00 | 18.98 | 0.00 | 18.98 | 0.00 | 18.98 |
October | 5.67 | 18.30 | 0.00 | 18.30 | 0.00 | 18.30 | 0.00 | 18.30 |
November | 58.50 | 15.70 | 17.83 | 15.85 | 0.00 | 15.85 | 0.00 | 15.85 |
December | 107.17 | 15.76 | 35.33 | 15.99 | 0.00 | 15.99 | 0.00 | 15.99 |
Annual Sum or Average | 469.17 | 15.88 | 166.33 | 16.12 | 5.67 | 16.22 | 3.50 | 16.28 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 155.00 | 19.14 | 66.50 | 19.14 | 4.50 | 27.65 | 2.83 | 27.64 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 88.33 | 14.67 | 25.00 | 14.64 | 0.00 | 14.64 | 0.00 | 14.64 |
February | 57.50 | 14.95 | 11.67 | 14.89 | 0.00 | 14.89 | 0.00 | 14.89 |
March | 24.83 | 15.63 | 2.67 | 15.52 | 0.00 | 15.52 | 0.00 | 15.52 |
April | 10.67 | 16.05 | 3.17 | 15.76 | 1.33 | 16.79 | 1.33 | 17.65 |
May | 0.33 | 19.13 | 0.00 | 19.13 | 4.83 | 27.38 | 4.83 | 27.65 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 7.50 | 28.36 | 6.50 | 28.41 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 8.50 | 28.34 | 8.17 | 28.36 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 28.05 | 2.83 | 28.05 |
September | 1.00 | 19.02 | 0.00 | 19.02 | 2.83 | 25.70 | 2.83 | 26.70 |
October | 4.83 | 18.28 | 0.00 | 18.28 | 0.00 | 18.28 | 0.00 | 18.28 |
November | 41.83 | 14.92 | 9.00 | 14.89 | 0.00 | 14.89 | 0.00 | 14.89 |
December | 68.33 | 14.81 | 14.83 | 14.75 | 0.00 | 14.75 | 0.00 | 14.75 |
Annual Sum or Average | 297.67 | 15.00 | 66.33 | 14.92 | 27.83 | 15.86 | 26.50 | 16.64 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.64 | 0.00 | 14.64 |
Maximum of Months | 88.33 | 19.13 | 25.00 | 19.13 | 8.50 | 28.36 | 8.17 | 28.41 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 90.50 | 15.32 | 23.00 | 15.45 | 0.00 | 15.45 | 0.00 | 15.45 |
February | 52.50 | 15.61 | 10.33 | 15.72 | 0.00 | 15.72 | 0.00 | 15.72 |
March | 22.50 | 16.14 | 2.00 | 16.16 | 0.00 | 16.16 | 0.00 | 16.16 |
April | 10.33 | 16.21 | 3.00 | 15.90 | 2.33 | 17.73 | 2.17 | 19.01 |
May | 0.17 | 18.91 | 0.00 | 18.91 | 1.33 | 26.66 | 1.33 | 27.12 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 5.83 | 28.08 | 4.33 | 28.15 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 6.50 | 28.01 | 5.67 | 28.04 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 27.90 | 5.00 | 27.90 |
September | 0.67 | 18.94 | 0.00 | 18.94 | 5.67 | 27.36 | 5.50 | 27.84 |
October | 4.17 | 18.57 | 0.00 | 18.57 | 2.00 | 21.59 | 2.00 | 23.13 |
November | 37.33 | 15.37 | 7.33 | 15.37 | 0.00 | 15.37 | 0.00 | 15.37 |
December | 59.50 | 15.34 | 12.83 | 15.40 | 0.00 | 15.40 | 0.00 | 15.40 |
Annual Sum or Average | 277.67 | 15.55 | 58.50 | 15.60 | 28.67 | 16.58 | 26.00 | 17.34 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.37 | 0.00 | 15.37 |
Maximum of Months | 90.50 | 18.94 | 23.00 | 18.94 | 6.50 | 28.08 | 5.67 | 28.15 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 79.67 | 14.69 | 22.00 | 14.65 | 0.00 | 14.65 | 0.00 | 14.65 |
February | 41.50 | 15.01 | 8.50 | 14.93 | 0.00 | 14.93 | 0.00 | 14.93 |
March | 19.67 | 15.94 | 2.00 | 15.79 | 0.00 | 15.79 | 0.00 | 15.79 |
April | 6.67 | 16.64 | 0.50 | 16.53 | 3.00 | 20.08 | 1.83 | 21.39 |
May | 0.17 | 18.95 | 0.00 | 18.95 | 4.17 | 28.05 | 2.17 | 28.17 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 6.67 | 28.97 | 3.33 | 29.04 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 11.00 | 28.82 | 5.00 | 28.88 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 4.67 | 28.37 | 3.00 | 28.41 |
September | 0.50 | 18.74 | 0.00 | 18.74 | 3.50 | 27.24 | 2.83 | 27.75 |
October | 3.67 | 18.60 | 0.00 | 18.60 | 0.00 | 18.60 | 0.00 | 18.60 |
November | 31.17 | 15.05 | 6.00 | 15.02 | 0.00 | 15.02 | 0.00 | 15.02 |
December | 50.00 | 14.91 | 11.17 | 14.82 | 0.00 | 14.82 | 0.00 | 14.82 |
Annual Sum or Average | 233.00 | 15.08 | 50.17 | 14.98 | 33.00 | 16.41 | 18.17 | 17.08 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.65 | 0.00 | 14.65 |
Maximum of Months | 79.67 | 18.95 | 22.00 | 18.95 | 11.00 | 28.97 | 5.00 | 29.04 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 27.84 | 3.00 | 27.84 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 3.00 | 27.84 | 3.00 | 27.84 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 27.84 | 3.00 | 27.84 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 30.83 | 29.60 | 25.17 | 29.68 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 96.67 | 29.13 | 88.00 | 29.19 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 283.00 | 30.30 | 236.67 | 30.35 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 410.50 | 29.97 | 349.83 | 30.02 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 283.00 | 30.30 | 236.67 | 30.35 |
Report: ComfortReportSimple55Monthly
For: BASEMENT
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 455.67 | 22.78 | 13.83 | 22.85 | 12.83 | 22.91 |
February | 322.83 | 23.16 | 18.83 | 23.23 | 5.50 | 23.20 |
March | 260.00 | 23.92 | 50.50 | 24.26 | 0.00 | 24.26 |
April | 129.17 | 23.99 | 136.67 | 24.62 | 11.17 | 24.59 |
May | 33.33 | 24.62 | 336.33 | 24.69 | 26.33 | 24.70 |
June | 156.50 | 24.88 | 451.50 | 24.60 | 156.50 | 24.66 |
July | 171.00 | 24.75 | 494.33 | 24.65 | 171.00 | 24.67 |
August | 169.00 | 25.01 | 510.00 | 24.62 | 169.00 | 24.70 |
September | 15.33 | 24.29 | 289.83 | 24.88 | 4.67 | 24.88 |
October | 38.00 | 24.00 | 152.50 | 25.39 | 0.00 | 25.39 |
November | 154.17 | 23.84 | 141.00 | 24.56 | 0.00 | 24.56 |
December | 352.17 | 23.64 | 29.00 | 23.83 | 0.00 | 23.83 |
Annual Sum or Average | 2257.17 | 23.76 | 2624.33 | 24.32 | 557.00 | 24.37 |
Minimum of Months | 15.33 | 22.78 | 13.83 | 22.85 | 0.00 | 22.91 |
Maximum of Months | 455.67 | 25.01 | 510.00 | 25.39 | 171.00 | 25.39 |
Report: ComfortReportSimple55Monthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 489.17 | 23.17 | 18.00 | 23.17 | 18.00 | 23.16 |
February | 363.83 | 23.28 | 19.17 | 23.17 | 18.33 | 23.08 |
March | 242.00 | 23.89 | 36.17 | 24.10 | 0.00 | 24.10 |
April | 88.67 | 23.96 | 122.50 | 24.33 | 0.00 | 24.33 |
May | 12.67 | 23.93 | 321.83 | 24.33 | 0.00 | 24.33 |
June | 0.00 | 0.00 | 464.00 | 24.28 | 0.00 | 24.28 |
July | 0.00 | 0.00 | 495.33 | 24.28 | 0.00 | 24.28 |
August | 0.00 | 0.00 | 508.50 | 24.25 | 0.00 | 24.25 |
September | 23.17 | 23.89 | 286.00 | 24.45 | 0.00 | 24.45 |
October | 76.67 | 23.94 | 97.33 | 24.66 | 0.00 | 24.66 |
November | 191.83 | 23.86 | 83.50 | 24.06 | 0.00 | 24.06 |
December | 374.17 | 23.80 | 1.17 | 23.81 | 0.00 | 23.81 |
Annual Sum or Average | 1862.17 | 23.57 | 2453.50 | 24.01 | 36.33 | 24.00 |
Minimum of Months | 0.00 | 0.00 | 1.17 | 23.17 | 0.00 | 23.08 |
Maximum of Months | 489.17 | 23.96 | 508.50 | 24.66 | 18.33 | 24.66 |
Report: ComfortReportSimple55Monthly
For: CORE_MID
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 21.30 | 217.33 | 20.97 | 217.33 | 20.80 |
February | 454.00 | 21.95 | 121.67 | 21.67 | 121.67 | 21.48 |
March | 470.83 | 22.86 | 22.17 | 22.75 | 22.17 | 22.65 |
April | 311.83 | 23.20 | 51.00 | 23.32 | 2.00 | 23.30 |
May | 90.67 | 23.59 | 249.50 | 24.02 | 0.00 | 24.02 |
June | 13.17 | 23.48 | 426.17 | 24.17 | 0.00 | 24.17 |
July | 0.00 | 0.00 | 479.50 | 24.22 | 0.00 | 24.22 |
August | 0.00 | 0.00 | 491.67 | 24.20 | 0.00 | 24.20 |
September | 77.17 | 23.48 | 205.67 | 24.09 | 0.00 | 24.09 |
October | 355.17 | 23.45 | 6.67 | 23.46 | 0.00 | 23.46 |
November | 408.33 | 22.54 | 63.17 | 22.37 | 49.33 | 22.20 |
December | 497.00 | 21.86 | 110.50 | 21.58 | 110.50 | 21.38 |
Annual Sum or Average | 3180.17 | 22.42 | 2445.00 | 22.84 | 523.00 | 22.63 |
Minimum of Months | 0.00 | 0.00 | 6.67 | 20.97 | 0.00 | 20.80 |
Maximum of Months | 502.00 | 23.59 | 491.67 | 24.22 | 217.33 | 24.22 |
Report: ComfortReportSimple55Monthly
For: CORE_TOP
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.46 | 364.33 | 20.25 | 364.33 | 20.16 |
February | 454.00 | 20.92 | 248.67 | 20.60 | 248.67 | 20.45 |
March | 502.17 | 21.90 | 110.33 | 21.62 | 110.33 | 21.42 |
April | 381.50 | 22.29 | 104.17 | 22.24 | 51.67 | 22.01 |
May | 168.17 | 23.14 | 208.83 | 23.68 | 2.17 | 23.68 |
June | 54.00 | 23.05 | 382.17 | 24.05 | 1.50 | 24.05 |
July | 9.67 | 23.33 | 463.67 | 24.18 | 0.00 | 24.18 |
August | 14.50 | 23.43 | 459.50 | 24.15 | 2.00 | 24.15 |
September | 190.67 | 23.03 | 168.50 | 23.60 | 0.00 | 23.60 |
October | 466.67 | 22.36 | 66.50 | 22.13 | 64.17 | 21.95 |
November | 466.33 | 21.37 | 179.50 | 20.97 | 175.83 | 20.73 |
December | 497.00 | 20.68 | 304.33 | 20.42 | 304.33 | 20.30 |
Annual Sum or Average | 3706.67 | 21.59 | 3060.50 | 21.95 | 1325.00 | 21.64 |
Minimum of Months | 9.67 | 20.46 | 66.50 | 20.25 | 0.00 | 20.16 |
Maximum of Months | 502.17 | 23.43 | 463.67 | 24.18 | 364.33 | 24.18 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.36 | 433.67 | 20.29 | 433.67 | 20.26 |
February | 454.00 | 20.93 | 246.17 | 20.72 | 246.17 | 20.62 |
March | 475.83 | 22.04 | 91.50 | 21.83 | 89.83 | 21.66 |
April | 350.33 | 22.82 | 68.67 | 23.03 | 11.50 | 23.04 |
May | 127.67 | 23.46 | 237.67 | 23.97 | 2.17 | 23.99 |
June | 49.00 | 24.81 | 425.33 | 24.38 | 22.33 | 24.48 |
July | 16.50 | 26.56 | 494.67 | 24.44 | 16.50 | 24.50 |
August | 9.17 | 25.89 | 484.83 | 24.28 | 7.00 | 24.31 |
September | 174.17 | 23.17 | 202.17 | 23.83 | 1.50 | 23.84 |
October | 421.17 | 22.86 | 16.83 | 22.91 | 0.00 | 22.91 |
November | 435.00 | 21.71 | 132.17 | 21.45 | 125.00 | 21.26 |
December | 497.00 | 20.83 | 299.83 | 20.68 | 299.83 | 20.62 |
Annual Sum or Average | 3511.83 | 21.80 | 3133.50 | 22.27 | 1255.50 | 22.01 |
Minimum of Months | 9.17 | 20.36 | 16.83 | 20.29 | 0.00 | 20.26 |
Maximum of Months | 502.00 | 26.56 | 494.67 | 24.44 | 433.67 | 24.50 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.40 | 427.50 | 20.32 | 427.50 | 20.29 |
February | 448.33 | 20.94 | 231.00 | 20.73 | 231.00 | 20.63 |
March | 445.67 | 21.75 | 112.00 | 21.64 | 99.33 | 21.50 |
April | 340.17 | 22.29 | 120.67 | 22.74 | 31.67 | 22.74 |
May | 155.50 | 23.56 | 277.17 | 24.12 | 25.17 | 24.27 |
June | 78.83 | 24.31 | 397.83 | 24.34 | 29.50 | 24.48 |
July | 41.00 | 26.16 | 471.33 | 24.47 | 33.67 | 24.61 |
August | 43.00 | 24.17 | 436.83 | 24.14 | 13.67 | 24.22 |
September | 194.33 | 23.04 | 233.83 | 23.83 | 16.67 | 23.94 |
October | 397.17 | 22.43 | 34.17 | 22.60 | 2.00 | 22.59 |
November | 473.67 | 21.48 | 139.33 | 21.23 | 138.00 | 21.07 |
December | 496.33 | 20.75 | 346.50 | 20.63 | 346.50 | 20.58 |
Annual Sum or Average | 3616.00 | 21.70 | 3228.17 | 22.21 | 1394.67 | 22.00 |
Minimum of Months | 41.00 | 20.40 | 34.17 | 20.32 | 2.00 | 20.29 |
Maximum of Months | 502.00 | 26.16 | 471.33 | 24.47 | 427.50 | 24.61 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 461.33 | 20.76 | 337.67 | 20.54 | 328.00 | 20.42 |
February | 394.67 | 21.33 | 210.83 | 21.14 | 187.83 | 20.95 |
March | 390.33 | 21.98 | 143.00 | 22.03 | 92.83 | 21.88 |
April | 301.00 | 22.44 | 156.17 | 22.92 | 43.00 | 22.88 |
May | 154.17 | 23.28 | 263.83 | 23.97 | 12.67 | 24.05 |
June | 76.33 | 24.12 | 392.33 | 24.29 | 22.67 | 24.41 |
July | 34.33 | 26.26 | 477.00 | 24.49 | 28.67 | 24.62 |
August | 40.17 | 25.54 | 480.83 | 24.37 | 25.17 | 24.49 |
September | 173.17 | 23.49 | 263.33 | 24.15 | 26.67 | 24.31 |
October | 315.00 | 22.82 | 117.50 | 23.26 | 17.00 | 23.34 |
November | 383.00 | 21.66 | 162.00 | 21.60 | 126.50 | 21.38 |
December | 433.00 | 21.06 | 305.67 | 20.98 | 279.67 | 20.85 |
Annual Sum or Average | 3156.50 | 21.97 | 3310.17 | 22.57 | 1190.67 | 22.35 |
Minimum of Months | 34.33 | 20.76 | 117.50 | 20.54 | 12.67 | 20.42 |
Maximum of Months | 461.33 | 26.26 | 480.83 | 24.49 | 328.00 | 24.62 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 497.83 | 20.76 | 343.50 | 20.63 | 343.50 | 20.57 |
February | 419.17 | 21.51 | 135.00 | 21.37 | 121.33 | 21.22 |
March | 357.67 | 22.53 | 77.50 | 22.84 | 12.17 | 22.81 |
April | 177.83 | 23.69 | 209.00 | 24.20 | 27.00 | 24.36 |
May | 104.67 | 23.80 | 327.33 | 24.25 | 22.50 | 24.37 |
June | 59.50 | 25.52 | 461.67 | 24.60 | 45.17 | 24.73 |
July | 93.33 | 26.04 | 497.00 | 24.82 | 93.33 | 24.98 |
August | 80.67 | 25.86 | 514.00 | 24.66 | 80.67 | 24.80 |
September | 155.17 | 23.45 | 288.00 | 24.17 | 23.33 | 24.30 |
October | 279.00 | 23.01 | 109.17 | 23.45 | 3.50 | 23.48 |
November | 345.33 | 22.19 | 103.83 | 22.35 | 42.17 | 22.21 |
December | 469.33 | 21.83 | 82.33 | 21.65 | 80.33 | 21.51 |
Annual Sum or Average | 3039.50 | 22.41 | 3148.33 | 23.09 | 895.00 | 23.01 |
Minimum of Months | 59.50 | 20.76 | 77.50 | 20.63 | 3.50 | 20.57 |
Maximum of Months | 497.83 | 26.04 | 514.00 | 24.82 | 343.50 | 24.98 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.65 | 495.33 | 19.64 | 495.33 | 19.64 |
February | 454.00 | 19.88 | 420.50 | 19.84 | 420.50 | 19.82 |
March | 514.00 | 20.76 | 322.17 | 20.58 | 322.17 | 20.50 |
April | 425.00 | 21.29 | 177.17 | 21.21 | 140.83 | 21.00 |
May | 254.33 | 22.72 | 176.67 | 23.26 | 4.50 | 23.23 |
June | 110.00 | 23.73 | 365.67 | 24.15 | 36.83 | 24.26 |
July | 49.83 | 24.83 | 461.50 | 24.34 | 36.67 | 24.41 |
August | 62.33 | 23.44 | 408.17 | 24.04 | 16.33 | 24.06 |
September | 268.67 | 22.37 | 166.00 | 22.97 | 13.67 | 22.91 |
October | 496.83 | 21.34 | 144.17 | 21.10 | 142.17 | 20.94 |
November | 489.00 | 20.41 | 310.83 | 20.13 | 310.83 | 20.00 |
December | 497.00 | 19.81 | 497.00 | 19.81 | 497.00 | 19.81 |
Annual Sum or Average | 4123.00 | 20.89 | 3945.17 | 21.25 | 2436.83 | 20.98 |
Minimum of Months | 49.83 | 19.65 | 144.17 | 19.64 | 4.50 | 19.64 |
Maximum of Months | 514.00 | 24.83 | 497.00 | 24.34 | 497.00 | 24.41 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 427.00 | 19.54 | 415.17 | 19.52 | 415.17 | 19.52 |
February | 384.33 | 19.88 | 339.00 | 19.79 | 339.00 | 19.76 |
March | 418.50 | 20.81 | 231.17 | 20.59 | 228.83 | 20.47 |
April | 328.67 | 21.41 | 159.83 | 21.59 | 105.17 | 21.42 |
May | 213.83 | 22.95 | 182.50 | 23.68 | 26.33 | 23.85 |
June | 118.00 | 23.59 | 297.33 | 24.21 | 35.17 | 24.40 |
July | 72.33 | 25.61 | 378.67 | 24.65 | 54.67 | 24.85 |
August | 82.67 | 23.80 | 326.67 | 24.14 | 26.33 | 24.26 |
September | 218.00 | 22.45 | 170.00 | 23.33 | 24.17 | 23.44 |
October | 409.83 | 21.42 | 92.17 | 21.28 | 87.00 | 21.16 |
November | 416.00 | 20.29 | 266.33 | 20.06 | 266.33 | 19.96 |
December | 422.00 | 19.72 | 416.67 | 19.71 | 416.67 | 19.71 |
Annual Sum or Average | 3511.17 | 20.98 | 3275.50 | 21.38 | 2024.83 | 21.14 |
Minimum of Months | 72.33 | 19.54 | 92.17 | 19.52 | 24.17 | 19.52 |
Maximum of Months | 427.00 | 25.61 | 416.67 | 24.65 | 416.67 | 24.85 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 467.17 | 20.14 | 385.83 | 19.93 | 379.67 | 19.84 |
February | 406.50 | 20.68 | 284.67 | 20.45 | 266.67 | 20.28 |
March | 424.50 | 21.25 | 245.00 | 21.18 | 205.50 | 21.01 |
April | 341.00 | 21.60 | 193.33 | 21.92 | 100.83 | 21.73 |
May | 211.83 | 22.75 | 222.17 | 23.56 | 13.17 | 23.62 |
June | 126.67 | 23.47 | 350.50 | 24.09 | 33.50 | 24.21 |
July | 73.50 | 24.92 | 447.33 | 24.44 | 46.67 | 24.57 |
August | 79.00 | 24.37 | 431.17 | 24.29 | 37.17 | 24.41 |
September | 216.33 | 22.99 | 247.50 | 23.81 | 35.50 | 23.96 |
October | 363.67 | 22.11 | 150.00 | 22.46 | 61.83 | 22.41 |
November | 429.67 | 20.95 | 243.00 | 20.78 | 214.33 | 20.56 |
December | 450.67 | 20.38 | 384.00 | 20.26 | 369.00 | 20.17 |
Annual Sum or Average | 3590.50 | 21.43 | 3584.50 | 21.93 | 1763.83 | 21.67 |
Minimum of Months | 73.50 | 20.14 | 150.00 | 19.93 | 13.17 | 19.84 |
Maximum of Months | 467.17 | 24.92 | 447.33 | 24.44 | 379.67 | 24.57 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.83 | 469.00 | 19.78 | 469.00 | 19.76 |
February | 446.67 | 20.26 | 352.83 | 20.12 | 351.17 | 20.07 |
March | 480.83 | 20.94 | 254.83 | 20.78 | 246.33 | 20.67 |
April | 364.17 | 21.47 | 177.83 | 21.77 | 93.83 | 21.63 |
May | 256.17 | 22.64 | 206.33 | 23.36 | 17.83 | 23.46 |
June | 124.00 | 23.25 | 365.67 | 24.09 | 28.00 | 24.21 |
July | 79.50 | 25.09 | 448.67 | 24.52 | 56.00 | 24.67 |
August | 72.67 | 23.98 | 439.67 | 24.22 | 29.00 | 24.31 |
September | 264.67 | 22.38 | 202.00 | 23.22 | 25.67 | 23.31 |
October | 444.17 | 21.38 | 117.00 | 21.36 | 91.50 | 21.23 |
November | 480.50 | 20.54 | 278.50 | 20.30 | 274.17 | 20.18 |
December | 497.00 | 20.05 | 456.17 | 19.99 | 456.17 | 19.96 |
Annual Sum or Average | 4012.33 | 21.08 | 3768.50 | 21.54 | 2138.67 | 21.30 |
Minimum of Months | 72.67 | 19.83 | 117.00 | 19.78 | 17.83 | 19.76 |
Maximum of Months | 502.00 | 25.09 | 469.00 | 24.52 | 469.00 | 24.67 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.52 | 498.67 | 19.51 | 498.67 | 19.51 |
February | 454.00 | 19.74 | 438.67 | 19.71 | 438.67 | 19.71 |
March | 514.00 | 20.43 | 389.33 | 20.31 | 389.33 | 20.26 |
April | 434.50 | 20.89 | 241.83 | 20.77 | 210.67 | 20.58 |
May | 305.17 | 22.27 | 169.00 | 22.77 | 21.00 | 22.68 |
June | 153.17 | 23.16 | 344.00 | 23.90 | 42.17 | 24.01 |
July | 91.17 | 24.19 | 432.83 | 24.24 | 50.33 | 24.33 |
August | 125.50 | 23.14 | 367.33 | 23.86 | 25.67 | 23.89 |
September | 309.17 | 21.91 | 181.83 | 22.43 | 46.50 | 22.28 |
October | 502.00 | 20.66 | 250.50 | 20.37 | 250.50 | 20.22 |
November | 489.00 | 20.00 | 357.17 | 19.79 | 357.17 | 19.70 |
December | 497.00 | 19.65 | 497.00 | 19.65 | 497.00 | 19.65 |
Annual Sum or Average | 4376.67 | 20.67 | 4168.17 | 20.98 | 2827.67 | 20.73 |
Minimum of Months | 91.17 | 19.52 | 169.00 | 19.51 | 21.00 | 19.51 |
Maximum of Months | 514.00 | 24.19 | 498.67 | 24.24 | 498.67 | 24.33 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.68 | 486.83 | 19.66 | 486.83 | 19.65 |
February | 454.00 | 19.88 | 404.83 | 19.80 | 404.83 | 19.77 |
March | 500.50 | 20.64 | 299.50 | 20.41 | 299.50 | 20.31 |
April | 391.67 | 21.24 | 215.83 | 21.30 | 159.00 | 21.12 |
May | 245.33 | 22.67 | 224.17 | 23.47 | 28.50 | 23.58 |
June | 147.17 | 23.25 | 358.00 | 24.02 | 39.67 | 24.20 |
July | 92.83 | 25.03 | 442.67 | 24.50 | 59.17 | 24.68 |
August | 111.67 | 23.55 | 392.67 | 24.03 | 32.00 | 24.14 |
September | 252.17 | 22.12 | 218.50 | 23.02 | 40.33 | 23.02 |
October | 494.17 | 21.00 | 179.00 | 20.73 | 177.00 | 20.56 |
November | 489.00 | 20.06 | 345.33 | 19.86 | 345.33 | 19.77 |
December | 497.00 | 19.74 | 494.00 | 19.73 | 494.00 | 19.73 |
Annual Sum or Average | 4177.50 | 20.84 | 4061.33 | 21.24 | 2566.17 | 21.00 |
Minimum of Months | 92.83 | 19.68 | 179.00 | 19.66 | 28.50 | 19.65 |
Maximum of Months | 502.00 | 25.03 | 494.00 | 24.50 | 494.00 | 24.68 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 475.00 | 19.91 | 405.67 | 19.72 | 402.17 | 19.64 |
February | 420.00 | 20.35 | 321.67 | 20.12 | 307.83 | 19.97 |
March | 435.83 | 20.82 | 292.17 | 20.73 | 259.50 | 20.56 |
April | 354.50 | 21.21 | 240.67 | 21.44 | 153.50 | 21.20 |
May | 252.50 | 22.34 | 213.00 | 23.12 | 27.00 | 23.09 |
June | 162.50 | 23.06 | 325.50 | 23.86 | 40.67 | 23.98 |
July | 108.33 | 24.24 | 421.00 | 24.33 | 53.50 | 24.47 |
August | 119.17 | 23.72 | 395.17 | 24.13 | 42.83 | 24.26 |
September | 243.50 | 22.50 | 246.50 | 23.36 | 51.83 | 23.41 |
October | 379.33 | 21.32 | 216.17 | 21.48 | 138.50 | 21.26 |
November | 453.33 | 20.52 | 283.00 | 20.27 | 266.33 | 20.08 |
December | 463.17 | 20.08 | 402.00 | 19.93 | 395.67 | 19.86 |
Annual Sum or Average | 3867.17 | 21.10 | 3762.50 | 21.52 | 2139.33 | 21.25 |
Minimum of Months | 108.33 | 19.91 | 213.00 | 19.72 | 27.00 | 19.64 |
Maximum of Months | 475.00 | 24.24 | 421.00 | 24.33 | 402.17 | 24.47 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.73 | 478.00 | 19.69 | 478.00 | 19.68 |
February | 448.67 | 20.03 | 384.83 | 19.93 | 383.17 | 19.88 |
March | 484.83 | 20.66 | 307.17 | 20.51 | 301.00 | 20.42 |
April | 370.67 | 21.11 | 223.17 | 21.32 | 145.00 | 21.12 |
May | 291.67 | 22.30 | 186.00 | 23.01 | 27.00 | 23.08 |
June | 156.33 | 22.93 | 345.33 | 23.89 | 36.17 | 24.02 |
July | 110.50 | 24.50 | 427.50 | 24.42 | 66.83 | 24.57 |
August | 108.83 | 23.49 | 408.67 | 24.07 | 35.83 | 24.18 |
September | 291.83 | 22.04 | 203.50 | 22.83 | 45.00 | 22.84 |
October | 452.17 | 20.89 | 194.00 | 20.74 | 173.17 | 20.57 |
November | 482.17 | 20.17 | 320.50 | 19.95 | 317.17 | 19.85 |
December | 497.00 | 19.84 | 467.67 | 19.79 | 467.67 | 19.77 |
Annual Sum or Average | 4196.67 | 20.86 | 3946.33 | 21.27 | 2476.00 | 21.03 |
Minimum of Months | 108.83 | 19.73 | 186.00 | 19.69 | 27.00 | 19.68 |
Maximum of Months | 502.00 | 24.50 | 478.00 | 24.42 | 478.00 | 24.57 |
Report: ComfortReportSimple55Monthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 4.17 | 25.99 | 312.00 | 26.99 | 0.00 | 26.99 |
February | 2.33 | 27.00 | 390.83 | 27.00 | 2.33 | 27.00 |
March | 4.33 | 27.00 | 514.00 | 27.00 | 4.33 | 27.00 |
April | 105.50 | 27.00 | 485.00 | 27.00 | 105.50 | 27.00 |
May | 25.17 | 27.00 | 508.00 | 27.00 | 25.17 | 27.00 |
June | 166.50 | 27.00 | 496.00 | 27.00 | 166.50 | 27.00 |
July | 299.17 | 27.00 | 497.00 | 27.00 | 299.17 | 27.00 |
August | 425.00 | 27.01 | 514.00 | 27.01 | 425.00 | 27.01 |
September | 56.67 | 27.00 | 485.00 | 27.00 | 56.67 | 27.00 |
October | 15.33 | 27.00 | 502.00 | 27.00 | 15.33 | 27.00 |
November | 5.00 | 27.00 | 475.00 | 27.00 | 5.00 | 27.00 |
December | 0.83 | 27.00 | 484.67 | 27.00 | 0.83 | 27.00 |
Annual Sum or Average | 1110.00 | 27.00 | 5663.50 | 27.00 | 1105.83 | 27.00 |
Minimum of Months | 0.83 | 25.99 | 312.00 | 26.99 | 0.00 | 26.99 |
Maximum of Months | 425.00 | 27.01 | 514.00 | 27.01 | 425.00 | 27.01 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 239.83 | 25.25 | 79.67 | 25.69 | 0.00 | 25.69 |
February | 26.83 | 27.00 | 224.67 | 27.00 | 0.00 | 27.00 |
March | 0.00 | 0.00 | 419.67 | 27.00 | 0.00 | 27.00 |
April | 19.50 | 27.00 | 467.83 | 27.00 | 19.50 | 27.00 |
May | 12.67 | 27.00 | 508.00 | 27.00 | 12.67 | 27.00 |
June | 65.50 | 27.00 | 496.00 | 27.00 | 65.50 | 27.00 |
July | 95.17 | 27.00 | 497.00 | 27.00 | 95.17 | 27.00 |
August | 128.17 | 27.01 | 514.00 | 27.00 | 128.17 | 27.00 |
September | 28.50 | 27.00 | 485.00 | 27.00 | 28.50 | 27.00 |
October | 3.67 | 27.00 | 501.00 | 27.00 | 3.67 | 27.00 |
November | 14.83 | 27.00 | 352.67 | 27.00 | 0.83 | 27.00 |
December | 26.00 | 27.00 | 231.00 | 27.00 | 0.00 | 27.00 |
Annual Sum or Average | 660.67 | 26.37 | 4776.50 | 26.92 | 354.00 | 26.93 |
Minimum of Months | 0.00 | 0.00 | 79.67 | 25.69 | 0.00 | 25.69 |
Maximum of Months | 239.83 | 27.01 | 514.00 | 27.00 | 128.17 | 27.00 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 351.83 | 24.53 | 125.50 | 24.44 | 74.50 | 24.15 |
February | 89.83 | 26.93 | 162.33 | 26.97 | 0.00 | 26.97 |
March | 22.67 | 27.00 | 340.00 | 27.00 | 0.00 | 27.00 |
April | 35.83 | 27.00 | 425.33 | 27.00 | 23.00 | 27.00 |
May | 20.00 | 27.00 | 508.00 | 27.00 | 20.00 | 27.00 |
June | 99.17 | 27.00 | 496.00 | 27.00 | 99.17 | 27.00 |
July | 133.33 | 27.00 | 497.00 | 27.00 | 133.33 | 27.00 |
August | 157.67 | 27.00 | 514.00 | 27.00 | 157.67 | 27.00 |
September | 39.33 | 27.00 | 478.33 | 27.00 | 39.33 | 27.00 |
October | 3.50 | 27.00 | 420.17 | 27.00 | 3.50 | 27.00 |
November | 58.00 | 27.00 | 277.17 | 27.00 | 0.83 | 27.00 |
December | 83.17 | 27.00 | 133.17 | 27.00 | 0.00 | 27.00 |
Annual Sum or Average | 1094.33 | 26.20 | 4377.00 | 26.78 | 551.33 | 26.74 |
Minimum of Months | 3.50 | 24.53 | 125.50 | 24.44 | 0.00 | 24.15 |
Maximum of Months | 351.83 | 27.00 | 514.00 | 27.00 | 157.67 | 27.00 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 64.83 | 27.00 | 502.00 | 27.00 | 64.83 | 27.00 |
February | 446.83 | 27.00 | 454.00 | 27.00 | 446.83 | 27.00 |
March | 514.00 | 27.00 | 514.00 | 27.00 | 514.00 | 27.00 |
April | 485.00 | 27.15 | 485.00 | 27.15 | 485.00 | 27.15 |
May | 508.00 | 27.00 | 508.00 | 27.00 | 508.00 | 27.00 |
June | 496.00 | 27.00 | 496.00 | 27.00 | 496.00 | 27.00 |
July | 497.00 | 27.42 | 497.00 | 27.42 | 497.00 | 27.42 |
August | 514.00 | 28.60 | 514.00 | 28.60 | 514.00 | 28.60 |
September | 485.00 | 27.00 | 485.00 | 27.00 | 485.00 | 27.00 |
October | 502.00 | 27.00 | 502.00 | 27.00 | 502.00 | 27.00 |
November | 489.00 | 27.00 | 489.00 | 27.00 | 489.00 | 27.00 |
December | 497.00 | 27.00 | 497.00 | 27.00 | 497.00 | 27.00 |
Annual Sum or Average | 5498.67 | 27.20 | 5943.00 | 27.19 | 5498.67 | 27.20 |
Minimum of Months | 64.83 | 27.00 | 454.00 | 27.00 | 64.83 | 27.00 |
Maximum of Months | 514.00 | 28.60 | 514.00 | 28.60 | 514.00 | 28.60 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 26.97899 | 13.07989 | 0.57436 | 12.13398 |
February | 454.00000 | 27.00000 | 15.50934 | 0.67588 | 14.91629 |
March | 514.00000 | 27.00000 | 19.80037 | 0.81128 | 19.07243 |
April | 485.00000 | 27.00004 | 25.12042 | 0.93259 | 23.58287 |
May | 508.00000 | 27.00078 | 32.97522 | 0.25610 | 6.51911 |
June | 496.00000 | 27.00115 | 35.66299 | 0.36829 | 7.95605 |
July | 497.00000 | 27.00091 | 36.22753 | 0.42929 | 8.94105 |
August | 514.00000 | 27.00677 | 35.89196 | 0.47664 | 9.87111 |
September | 485.00000 | 27.00051 | 32.68069 | 0.26188 | 6.69794 |
October | 502.00000 | 27.00006 | 25.52558 | 0.86109 | 20.79563 |
November | 489.00000 | 27.00007 | 21.32266 | 0.80931 | 19.12023 |
December | 497.00000 | 27.00000 | 14.24017 | 0.73137 | 16.41606 |
Annual Sum or Average | 5943.00000 | 26.99910 | 25.74963 | 0.59804 | 13.81054 |
Minimum of Months | 454.00000 | 26.97899 | 13.07989 | 0.25610 | 6.51911 |
Maximum of Months | 514.00000 | 27.00677 | 36.22753 | 0.93259 | 23.58287 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 26.09433 | 13.27846 | 0.28107 | 8.18436 |
February | 454.00000 | 27.00000 | 15.48895 | 0.53095 | 11.23566 |
March | 514.00000 | 27.00000 | 19.79400 | 0.64953 | 14.15426 |
April | 485.00000 | 27.00005 | 25.10002 | 0.77640 | 18.09379 |
May | 508.00000 | 27.00059 | 33.06547 | 0.16621 | 5.83147 |
June | 496.00000 | 27.00118 | 35.69820 | 0.27394 | 6.79765 |
July | 497.00000 | 27.00102 | 36.24531 | 0.32121 | 7.30224 |
August | 514.00000 | 27.00186 | 35.90184 | 0.33359 | 7.50437 |
September | 485.00000 | 27.00045 | 32.71630 | 0.16637 | 5.98629 |
October | 502.00000 | 27.00005 | 25.50158 | 0.73510 | 16.60600 |
November | 489.00000 | 27.00007 | 21.29324 | 0.63475 | 13.92228 |
December | 497.00000 | 27.00000 | 14.22612 | 0.52585 | 11.01256 |
Annual Sum or Average | 5943.00000 | 26.92394 | 25.77291 | 0.44850 | 10.53367 |
Minimum of Months | 454.00000 | 26.09433 | 13.27846 | 0.16621 | 5.83147 |
Maximum of Months | 514.00000 | 27.00186 | 36.24531 | 0.77640 | 18.09379 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 25.20774 | 13.47167 | 0.06799 | 8.49643 |
February | 454.00000 | 26.98595 | 15.49269 | 0.47391 | 10.20076 |
March | 514.00000 | 27.00000 | 19.79726 | 0.59624 | 12.85060 |
April | 485.00000 | 27.00005 | 25.11291 | 0.73137 | 16.89939 |
May | 508.00000 | 27.00046 | 33.11481 | 0.13989 | 5.85735 |
June | 496.00000 | 27.00117 | 35.71998 | 0.26708 | 6.91630 |
July | 497.00000 | 27.00101 | 36.26519 | 0.32190 | 7.41863 |
August | 514.00000 | 27.00175 | 35.92618 | 0.32728 | 7.53756 |
September | 485.00000 | 26.99697 | 32.76773 | 0.12685 | 6.03300 |
October | 502.00000 | 27.00005 | 25.52088 | 0.67160 | 14.87772 |
November | 489.00000 | 27.00007 | 21.31444 | 0.56880 | 12.37391 |
December | 497.00000 | 27.00000 | 14.23184 | 0.46411 | 9.81574 |
Annual Sum or Average | 5943.00000 | 26.84768 | 25.80870 | 0.39537 | 9.92580 |
Minimum of Months | 454.00000 | 25.20774 | 13.47167 | 0.06799 | 5.85735 |
Maximum of Months | 514.00000 | 27.00175 | 36.26519 | 0.73137 | 16.89939 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 26.99997 | 29.99929 | 0.97146 | 24.97153 |
February | 454.00000 | 27.00047 | 29.99732 | 1.15848 | 33.28526 |
March | 514.00000 | 27.00026 | 26.97198 | 1.31590 | 41.10461 |
April | 485.00000 | 27.14783 | 27.01377 | 1.49610 | 50.54724 |
May | 508.00000 | 26.99997 | 37.36202 | 0.54764 | 11.40851 |
June | 496.00000 | 27.00208 | 41.25311 | 0.82745 | 19.56516 |
July | 497.00000 | 27.42443 | 44.23597 | 1.18538 | 34.85936 |
August | 514.00000 | 28.60247 | 37.70864 | 1.67847 | 55.45334 |
September | 485.00000 | 27.00034 | 34.91715 | 0.58611 | 12.35033 |
October | 502.00000 | 27.00024 | 30.34946 | 1.24929 | 37.70365 |
November | 489.00000 | 27.00004 | 28.05679 | 1.34922 | 42.85151 |
December | 497.00000 | 27.00015 | 22.06093 | 1.40387 | 45.72621 |
Annual Sum or Average | 5943.00000 | 27.18644 | 32.52683 | 1.14841 | 34.19415 |
Minimum of Months | 454.00000 | 26.99997 | 22.06093 | 0.54764 | 11.40851 |
Maximum of Months | 514.00000 | 28.60247 | 44.23597 | 1.67847 | 55.45334 |
Report: OccupantComfortDataSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.97246 | 13.66113 | -0.0619 | 6.73975 |
February | 454.00000 | 23.62705 | 15.48012 | 0.09302 | 6.97200 |
March | 514.00000 | 24.28511 | 19.76295 | 0.28959 | 7.12419 |
April | 485.00000 | 24.43021 | 27.17084 | 0.38167 | 8.61334 |
May | 508.00000 | 24.47043 | 41.68036 | -0.3534 | 8.61927 |
June | 496.00000 | 24.46220 | 51.88220 | -0.2629 | 7.53174 |
July | 497.00000 | 24.61886 | 56.87526 | -0.1747 | 6.87880 |
August | 514.00000 | 24.48995 | 55.84721 | -0.2062 | 7.08093 |
September | 485.00000 | 24.55653 | 38.16354 | -0.3286 | 8.68291 |
October | 502.00000 | 24.55306 | 25.28921 | 0.40924 | 9.06922 |
November | 489.00000 | 24.41940 | 21.59161 | 0.34210 | 8.10816 |
December | 497.00000 | 24.07736 | 13.97146 | 0.19932 | 6.57026 |
Annual Sum or Average | 5943.00000 | 24.25051 | 31.93810 | 0.02605 | 7.66531 |
Minimum of Months | 454.00000 | 22.97246 | 13.66113 | -0.3534 | 6.57026 |
Maximum of Months | 514.00000 | 24.61886 | 56.87526 | 0.40924 | 9.06922 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.20068 | 18.40492 | -0.0231 | 6.12666 |
February | 454.00000 | 23.49341 | 17.81533 | 0.06463 | 6.59516 |
March | 514.00000 | 24.15755 | 21.58474 | 0.27593 | 6.90212 |
April | 485.00000 | 24.23956 | 28.20653 | 0.36701 | 8.15668 |
May | 508.00000 | 24.22723 | 42.70499 | -0.3983 | 8.79700 |
June | 496.00000 | 24.26110 | 50.09540 | -0.3099 | 7.37662 |
July | 497.00000 | 24.27615 | 54.45173 | -0.2625 | 6.72200 |
August | 514.00000 | 24.24298 | 52.76872 | -0.2723 | 6.82190 |
September | 485.00000 | 24.30019 | 39.25163 | -0.3941 | 8.92803 |
October | 502.00000 | 24.31376 | 27.29336 | 0.36596 | 8.11783 |
November | 489.00000 | 24.19864 | 23.82884 | 0.29737 | 7.28955 |
December | 497.00000 | 23.99520 | 16.59969 | 0.17892 | 6.03868 |
Annual Sum or Average | 5943.00000 | 24.07923 | 32.89078 | -0.0104 | 7.32282 |
Minimum of Months | 454.00000 | 23.20068 | 16.59969 | -0.3983 | 6.03868 |
Maximum of Months | 514.00000 | 24.31376 | 54.45173 | 0.36701 | 8.92803 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.30120 | 16.87811 | -0.5174 | 12.88918 |
February | 454.00000 | 21.94947 | 19.90478 | -0.3303 | 9.15573 |
March | 514.00000 | 22.96157 | 24.24103 | -0.0427 | 6.47511 |
April | 485.00000 | 23.50677 | 30.61205 | 0.15603 | 6.52839 |
May | 508.00000 | 24.01268 | 43.73094 | -0.5043 | 10.90945 |
June | 496.00000 | 24.14739 | 50.91665 | -0.3850 | 8.42644 |
July | 497.00000 | 24.20476 | 55.34963 | -0.3297 | 7.55920 |
August | 514.00000 | 24.18880 | 54.05387 | -0.3434 | 7.75116 |
September | 485.00000 | 24.06795 | 40.17461 | -0.5062 | 11.14813 |
October | 502.00000 | 23.64147 | 29.38889 | 0.17294 | 6.11739 |
November | 489.00000 | 22.78785 | 26.27377 | -0.0737 | 7.50403 |
December | 497.00000 | 21.86465 | 19.39945 | -0.3573 | 9.54460 |
Annual Sum or Average | 5943.00000 | 23.22911 | 34.37760 | -0.2551 | 8.66145 |
Minimum of Months | 454.00000 | 21.30120 | 16.87811 | -0.5174 | 6.11739 |
Maximum of Months | 514.00000 | 24.20476 | 55.34963 | 0.17294 | 12.88918 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.46458 | 17.61175 | -0.7534 | 20.31387 |
February | 454.00000 | 20.92003 | 20.81408 | -0.6057 | 16.12058 |
March | 514.00000 | 21.95283 | 25.99694 | -0.3018 | 9.38036 |
April | 485.00000 | 22.66883 | 32.10092 | -0.0545 | 8.52290 |
May | 508.00000 | 23.74535 | 44.51670 | -0.6001 | 14.02385 |
June | 496.00000 | 24.02890 | 51.34354 | -0.4192 | 9.63469 |
July | 497.00000 | 24.16155 | 55.57007 | -0.3351 | 7.68536 |
August | 514.00000 | 24.11282 | 54.41037 | -0.3649 | 8.13119 |
September | 485.00000 | 23.68146 | 41.39374 | -0.6492 | 15.99299 |
October | 502.00000 | 22.46940 | 31.85775 | -0.1216 | 7.45972 |
November | 489.00000 | 21.48621 | 28.08425 | -0.4055 | 13.05268 |
December | 497.00000 | 20.68376 | 20.19946 | -0.6740 | 17.58139 |
Annual Sum or Average | 5943.00000 | 22.54485 | 35.45837 | -0.4393 | 12.28260 |
Minimum of Months | 454.00000 | 20.46458 | 17.61175 | -0.7534 | 7.45972 |
Maximum of Months | 514.00000 | 24.16155 | 55.57007 | -0.0545 | 20.31387 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.35624 | 16.78492 | -0.7951 | 20.04924 |
February | 454.00000 | 20.93183 | 18.85525 | -0.6041 | 14.88187 |
March | 514.00000 | 22.19125 | 23.10235 | -0.2247 | 8.19801 |
April | 485.00000 | 23.18833 | 29.14649 | 0.08256 | 7.33831 |
May | 508.00000 | 23.96784 | 42.44337 | -0.5061 | 11.77342 |
June | 496.00000 | 24.25449 | 49.55073 | -0.2934 | 8.04016 |
July | 497.00000 | 24.36583 | 53.78506 | -0.2098 | 6.68527 |
August | 514.00000 | 24.22709 | 52.34071 | -0.2726 | 7.10999 |
September | 485.00000 | 23.85495 | 39.58581 | -0.5729 | 14.34493 |
October | 502.00000 | 23.05302 | 28.59390 | 0.02929 | 6.21747 |
November | 489.00000 | 21.96210 | 25.26512 | -0.2702 | 9.93646 |
December | 497.00000 | 20.82877 | 17.99105 | -0.6177 | 14.23004 |
Annual Sum or Average | 5943.00000 | 22.77917 | 33.25242 | -0.3530 | 10.69318 |
Minimum of Months | 454.00000 | 20.35624 | 16.78492 | -0.7951 | 6.21747 |
Maximum of Months | 514.00000 | 24.36583 | 53.78506 | 0.08256 | 20.04924 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.40290 | 15.95569 | -0.7727 | 19.40369 |
February | 454.00000 | 20.97732 | 18.07460 | -0.5742 | 14.25859 |
March | 514.00000 | 22.06827 | 22.52629 | -0.2212 | 8.55735 |
April | 485.00000 | 22.86987 | 29.05090 | 0.05951 | 8.86132 |
May | 508.00000 | 23.93348 | 42.25057 | -0.4205 | 11.94056 |
June | 496.00000 | 24.12159 | 49.56298 | -0.2429 | 9.08878 |
July | 497.00000 | 24.26307 | 53.82228 | -0.1457 | 7.54400 |
August | 514.00000 | 24.01034 | 52.72399 | -0.2668 | 8.07426 |
September | 485.00000 | 23.73487 | 39.31651 | -0.5127 | 15.33684 |
October | 502.00000 | 22.81148 | 28.28575 | 0.01136 | 6.83680 |
November | 489.00000 | 21.56378 | 25.27879 | -0.3480 | 10.32733 |
December | 497.00000 | 20.75487 | 17.29107 | -0.6423 | 15.01223 |
Annual Sum or Average | 5943.00000 | 22.63943 | 32.98050 | -0.3381 | 11.23426 |
Minimum of Months | 454.00000 | 20.40290 | 15.95569 | -0.7727 | 6.83680 |
Maximum of Months | 514.00000 | 24.26307 | 53.82228 | 0.05951 | 19.40369 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.02422 | 15.75312 | -0.5848 | 16.86139 |
February | 454.00000 | 21.71336 | 17.57402 | -0.3681 | 12.58911 |
March | 514.00000 | 22.50020 | 22.08796 | -0.1110 | 8.98922 |
April | 485.00000 | 23.12386 | 28.61579 | 0.11939 | 9.64510 |
May | 508.00000 | 23.89409 | 42.38532 | -0.4804 | 12.72646 |
June | 496.00000 | 24.14239 | 49.66861 | -0.2957 | 8.95769 |
July | 497.00000 | 24.33225 | 53.70391 | -0.1708 | 7.08766 |
August | 514.00000 | 24.22533 | 52.06361 | -0.1953 | 7.27629 |
September | 485.00000 | 23.96049 | 38.85584 | -0.4216 | 14.01193 |
October | 502.00000 | 23.31470 | 27.38015 | 0.15880 | 8.34809 |
November | 489.00000 | 22.24898 | 24.57656 | -0.1752 | 10.80421 |
December | 497.00000 | 21.48616 | 16.81537 | -0.4421 | 13.79427 |
Annual Sum or Average | 5943.00000 | 23.00743 | 32.59340 | -0.2467 | 10.89927 |
Minimum of Months | 454.00000 | 21.02422 | 15.75312 | -0.5848 | 7.08766 |
Maximum of Months | 514.00000 | 24.33225 | 53.70391 | 0.15880 | 16.86139 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.78903 | 15.44128 | -0.6355 | 15.18355 |
February | 454.00000 | 21.73041 | 17.03459 | -0.3448 | 10.41027 |
March | 514.00000 | 23.07252 | 20.96271 | 0.05882 | 7.51783 |
April | 485.00000 | 24.02977 | 26.94758 | 0.40445 | 10.75237 |
May | 508.00000 | 24.07468 | 41.74514 | -0.3397 | 10.07924 |
June | 496.00000 | 24.40895 | 48.62392 | -0.0766 | 7.59156 |
July | 497.00000 | 24.58635 | 52.64085 | 0.06791 | 7.41669 |
August | 514.00000 | 24.47294 | 51.06482 | 0.04216 | 6.76384 |
September | 485.00000 | 24.00797 | 38.61911 | -0.3830 | 12.49782 |
October | 502.00000 | 23.56501 | 26.73708 | 0.22758 | 7.58406 |
November | 489.00000 | 22.76054 | 23.33512 | -0.0213 | 8.18218 |
December | 497.00000 | 21.95846 | 15.96493 | -0.2873 | 8.54623 |
Annual Sum or Average | 5943.00000 | 23.29925 | 31.72828 | -0.1059 | 9.35438 |
Minimum of Months | 454.00000 | 20.78903 | 15.44128 | -0.6355 | 6.76384 |
Maximum of Months | 514.00000 | 24.58635 | 52.64085 | 0.40445 | 15.18355 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.64726 | 15.90840 | -1.0773 | 31.77284 |
February | 454.00000 | 19.88150 | 19.66559 | -0.9424 | 26.41304 |
March | 514.00000 | 20.75883 | 25.03310 | -0.6234 | 15.39454 |
April | 485.00000 | 21.64901 | 31.82920 | -0.3065 | 11.15939 |
May | 508.00000 | 23.38084 | 43.98027 | -0.7226 | 18.85134 |
June | 496.00000 | 24.00565 | 50.76837 | -0.4017 | 10.59503 |
July | 497.00000 | 24.23124 | 55.22661 | -0.2855 | 7.51263 |
August | 514.00000 | 23.99335 | 54.20047 | -0.3904 | 9.01657 |
September | 485.00000 | 23.15867 | 41.14695 | -0.8247 | 23.42715 |
October | 502.00000 | 21.36473 | 31.52989 | -0.3846 | 9.92925 |
November | 489.00000 | 20.41387 | 27.41104 | -0.7016 | 19.73378 |
December | 497.00000 | 19.80718 | 18.97791 | -0.9843 | 27.79772 |
Annual Sum or Average | 5943.00000 | 21.87486 | 34.77510 | -0.6347 | 17.54643 |
Minimum of Months | 454.00000 | 19.64726 | 15.90840 | -1.0773 | 7.51263 |
Maximum of Months | 514.00000 | 24.23124 | 55.22661 | -0.2855 | 31.77284 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 427.00000 | 19.54441 | 15.32269 | -1.0728 | 31.84237 |
February | 385.00000 | 19.88906 | 18.79140 | -0.9039 | 25.25534 |
March | 433.00000 | 20.91764 | 23.95478 | -0.5505 | 14.47969 |
April | 410.00000 | 21.99934 | 30.18722 | -0.1822 | 11.74188 |
May | 430.00000 | 23.53174 | 43.01991 | -0.5759 | 17.40241 |
June | 418.00000 | 23.95686 | 50.30900 | -0.3171 | 12.16271 |
July | 422.00000 | 24.32914 | 54.43098 | -0.1445 | 8.59762 |
August | 433.00000 | 23.95427 | 53.70586 | -0.3129 | 9.48856 |
September | 410.00000 | 23.27877 | 40.11887 | -0.6935 | 22.49768 |
October | 427.00000 | 21.53614 | 30.06445 | -0.3173 | 8.95018 |
November | 417.00000 | 20.29819 | 26.40012 | -0.7165 | 19.31490 |
December | 422.00000 | 19.71747 | 18.15022 | -0.9879 | 28.03616 |
Annual Sum or Average | 5034.00000 | 21.92628 | 33.81673 | -0.5624 | 17.40942 |
Minimum of Months | 385.00000 | 19.54441 | 15.32269 | -1.0728 | 8.59762 |
Maximum of Months | 433.00000 | 24.32914 | 54.43098 | -0.1445 | 31.84237 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.40586 | 15.18071 | -0.7779 | 23.86569 |
February | 454.00000 | 21.04806 | 18.17296 | -0.5550 | 17.89218 |
March | 514.00000 | 21.74655 | 23.22502 | -0.3168 | 12.14943 |
April | 485.00000 | 22.39401 | 30.04761 | -0.0702 | 11.62222 |
May | 508.00000 | 23.55899 | 43.28120 | -0.6021 | 16.79546 |
June | 496.00000 | 23.92974 | 50.68418 | -0.3801 | 11.29727 |
July | 497.00000 | 24.24489 | 54.87739 | -0.2190 | 7.97674 |
August | 514.00000 | 24.09842 | 53.41820 | -0.2612 | 8.58650 |
September | 485.00000 | 23.67624 | 39.46019 | -0.5185 | 17.96797 |
October | 502.00000 | 22.67485 | 28.61398 | 0.00448 | 9.32714 |
November | 489.00000 | 21.38687 | 25.86467 | -0.4101 | 15.37316 |
December | 497.00000 | 20.73207 | 17.73761 | -0.6807 | 20.71792 |
Annual Sum or Average | 5943.00000 | 22.50371 | 33.51927 | -0.3979 | 14.42195 |
Minimum of Months | 454.00000 | 20.40586 | 15.18071 | -0.7779 | 7.97674 |
Maximum of Months | 514.00000 | 24.24489 | 54.87739 | 0.00448 | 23.86569 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.83080 | 15.32976 | -0.9872 | 28.35318 |
February | 454.00000 | 20.31832 | 18.61798 | -0.7823 | 21.27327 |
March | 514.00000 | 21.13856 | 23.79847 | -0.4826 | 12.97780 |
April | 485.00000 | 22.13486 | 30.32696 | -0.1159 | 11.14266 |
May | 508.00000 | 23.30801 | 43.76548 | -0.6394 | 18.53485 |
June | 496.00000 | 23.91634 | 50.51731 | -0.3095 | 11.61615 |
July | 497.00000 | 24.29077 | 54.56740 | -0.1295 | 8.26683 |
August | 514.00000 | 24.05941 | 53.50015 | -0.2331 | 8.47005 |
September | 485.00000 | 23.18519 | 40.51382 | -0.7048 | 22.70644 |
October | 502.00000 | 21.69428 | 30.08137 | -0.2562 | 9.02652 |
November | 489.00000 | 20.60407 | 26.58201 | -0.6189 | 16.94599 |
December | 497.00000 | 20.05224 | 18.14993 | -0.8833 | 24.03531 |
Annual Sum or Average | 5943.00000 | 22.05939 | 33.95033 | -0.5098 | 16.04943 |
Minimum of Months | 454.00000 | 19.83080 | 15.32976 | -0.9872 | 8.26683 |
Maximum of Months | 514.00000 | 24.29077 | 54.56740 | -0.1159 | 28.35318 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.51669 | 15.84165 | -1.1596 | 35.23152 |
February | 454.00000 | 19.73668 | 19.75309 | -1.0296 | 30.13804 |
March | 514.00000 | 20.43230 | 25.69427 | -0.7406 | 19.02952 |
April | 485.00000 | 21.23369 | 32.77342 | -0.4313 | 14.34448 |
May | 508.00000 | 22.97799 | 44.87667 | -0.8571 | 24.57866 |
June | 496.00000 | 23.78663 | 51.38127 | -0.4668 | 13.37996 |
July | 497.00000 | 24.11305 | 55.73993 | -0.3148 | 8.35261 |
August | 514.00000 | 23.81839 | 54.86700 | -0.4416 | 10.66575 |
September | 485.00000 | 22.71567 | 42.16131 | -0.9834 | 30.55792 |
October | 502.00000 | 20.65994 | 33.05426 | -0.5811 | 14.97038 |
November | 489.00000 | 20.00023 | 28.34055 | -0.8466 | 24.42773 |
December | 497.00000 | 19.65019 | 18.93071 | -1.0799 | 31.85243 |
Annual Sum or Average | 5943.00000 | 21.57006 | 35.42281 | -0.7419 | 21.36539 |
Minimum of Months | 454.00000 | 19.51669 | 15.84165 | -1.1596 | 8.35261 |
Maximum of Months | 514.00000 | 24.11305 | 55.73993 | -0.3148 | 35.23152 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.67977 | 15.57240 | -1.0918 | 32.46547 |
February | 454.00000 | 19.88283 | 19.38979 | -0.9492 | 27.31474 |
March | 514.00000 | 20.73111 | 24.84971 | -0.6215 | 16.71425 |
April | 485.00000 | 21.80919 | 31.32923 | -0.2488 | 13.02112 |
May | 508.00000 | 23.39184 | 43.60074 | -0.6173 | 18.76207 |
June | 496.00000 | 23.81146 | 50.74647 | -0.3381 | 13.27744 |
July | 497.00000 | 24.22910 | 54.79092 | -0.1465 | 8.57993 |
August | 514.00000 | 23.87689 | 54.09963 | -0.3110 | 9.74037 |
September | 485.00000 | 23.10887 | 40.75992 | -0.7514 | 25.02449 |
October | 502.00000 | 21.04877 | 31.83141 | -0.4531 | 11.77702 |
November | 489.00000 | 20.06010 | 27.89701 | -0.8119 | 22.88048 |
December | 497.00000 | 19.73747 | 18.56267 | -1.0393 | 30.19621 |
Annual Sum or Average | 5943.00000 | 21.79717 | 34.58870 | -0.6122 | 19.05392 |
Minimum of Months | 454.00000 | 19.67977 | 15.57240 | -1.0918 | 8.57993 |
Maximum of Months | 514.00000 | 24.22910 | 54.79092 | -0.1465 | 32.46547 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.13170 | 15.34106 | -0.8886 | 27.86157 |
February | 454.00000 | 20.62284 | 18.67235 | -0.6959 | 22.09008 |
March | 514.00000 | 21.32772 | 24.08315 | -0.4498 | 15.15028 |
April | 485.00000 | 22.02808 | 30.99689 | -0.1845 | 13.84283 |
May | 508.00000 | 23.24712 | 44.04443 | -0.7113 | 21.23465 |
June | 496.00000 | 23.72096 | 51.31534 | -0.4422 | 14.00527 |
July | 497.00000 | 24.12977 | 55.39141 | -0.2471 | 8.96124 |
August | 514.00000 | 23.94971 | 54.02107 | -0.3047 | 10.00444 |
September | 485.00000 | 23.35148 | 40.29218 | -0.6427 | 22.95122 |
October | 502.00000 | 22.02830 | 30.09177 | -0.1777 | 11.57673 |
November | 489.00000 | 20.79624 | 27.03186 | -0.5888 | 19.02056 |
December | 497.00000 | 20.34626 | 18.05085 | -0.8199 | 25.12813 |
Annual Sum or Average | 5943.00000 | 22.15343 | 34.25066 | -0.5114 | 17.59698 |
Minimum of Months | 454.00000 | 20.13170 | 15.34106 | -0.8886 | 8.96124 |
Maximum of Months | 514.00000 | 24.12977 | 55.39141 | -0.1777 | 27.86157 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.73206 | 15.44406 | -1.0618 | 31.43861 |
February | 454.00000 | 20.07851 | 19.02448 | -0.8781 | 25.05384 |
March | 514.00000 | 20.85033 | 24.53963 | -0.5829 | 15.78860 |
April | 485.00000 | 21.82037 | 31.24832 | -0.2132 | 13.36516 |
May | 508.00000 | 23.00943 | 44.48741 | -0.7416 | 22.89295 |
June | 496.00000 | 23.73297 | 51.07823 | -0.3632 | 13.98732 |
July | 497.00000 | 24.17358 | 55.08091 | -0.1580 | 9.17990 |
August | 514.00000 | 23.90474 | 54.10116 | -0.2776 | 9.81574 |
September | 485.00000 | 22.87880 | 41.30586 | -0.8201 | 27.76951 |
October | 502.00000 | 21.20646 | 31.34293 | -0.3995 | 12.15715 |
November | 489.00000 | 20.22381 | 27.55058 | -0.7458 | 21.11186 |
December | 497.00000 | 19.83629 | 18.38311 | -0.9804 | 28.04648 |
Annual Sum or Average | 5943.00000 | 21.80257 | 34.60417 | -0.5995 | 19.14235 |
Minimum of Months | 454.00000 | 19.73206 | 15.44406 | -1.0618 | 9.17990 |
Maximum of Months | 514.00000 | 24.17358 | 55.08091 | -0.1580 | 31.43861 |
Report: ChillerReportMonthly
For: COOLSYS1 CHILLER1
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportCHILLER ELECTRICITY ENERGY [J] | CHILLER ELECTRICITY RATE {Maximum} [W] | CHILLER ELECTRICITY RATE {TIMESTAMP} | CHILLER ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | CHILLER EVAPORATOR COOLING ENERGY [J] | CHILLER EVAPORATOR COOLING RATE [] | CHILLER CONDENSER HEAT TRANSFER ENERGY [J] | CHILLER COP [W/W] | CHILLER COP {Maximum} [W/W] | CHILLER COP {TIMESTAMP} | CHILLER PART LOAD RATIO [] | CHILLER PART LOAD RATIO [] | |
January | 0.384520E+09 | 1855.78 | 12-JAN-14:40 | 69.26 | 0.164578E+10 | 0.00 | 0.203030E+10 | 0.40 | 4.29 | 18-JAN-23:10 | 0.00 | 0.00 |
February | 0.256420E+09 | 2862.35 | 17-FEB-16:30 | 45.60 | 0.109759E+10 | 0.00 | 0.135401E+10 | 0.29 | 4.29 | 22-FEB-08:50 | 0.00 | 0.00 |
March | 0.193818E+10 | 50994.05 | 25-MAR-15:00 | 84.28 | 0.827208E+10 | 0.00 | 0.102103E+11 | 0.48 | 4.29 | 05-MAR-04:40 | 0.00 | 0.00 |
April | 0.215108E+11 | 204452.90 | 18-APR-15:50 | 161.44 | 0.131581E+12 | 0.00 | 0.153092E+12 | 1.11 | 7.38 | 18-APR-08:40 | 0.00 | 0.00 |
May | 0.553639E+11 | 207885.42 | 30-MAY-13:00 | 271.19 | 0.325220E+12 | 0.00 | 0.380583E+12 | 1.86 | 7.51 | 05-MAY-16:10 | 0.00 | 0.00 |
June | 0.132966E+12 | 215043.22 | 27-JUN-11:20 | 404.81 | 0.884162E+12 | 0.00 | 0.101713E+13 | 3.44 | 7.57 | 20-JUN-15:30 | 0.00 | 0.00 |
July | 0.181089E+12 | 219976.23 | 26-JUL-16:20 | 555.01 | 0.120757E+13 | 0.00 | 0.138865E+13 | 4.49 | 7.57 | 28-JUL-05:04 | 0.00 | 0.00 |
August | 0.171437E+12 | 239339.02 | 04-AUG-07:10 | 544.06 | 0.114675E+13 | 0.00 | 0.131818E+13 | 4.36 | 7.57 | 29-AUG-15:50 | 0.00 | 0.00 |
September | 0.738958E+11 | 210424.30 | 05-SEP-13:40 | 270.52 | 0.480399E+12 | 0.00 | 0.554295E+12 | 2.17 | 7.57 | 01-SEP-14:40 | 0.00 | 0.00 |
October | 0.860519E+10 | 128970.76 | 20-OCT-15:00 | 100.86 | 0.438108E+11 | 0.00 | 0.524160E+11 | 0.61 | 7.38 | 20-OCT-15:00 | 0.00 | 0.00 |
November | 0.135764E+10 | 63311.07 | 03-NOV-13:20 | 58.52 | 0.579686E+10 | 0.00 | 0.715450E+10 | 0.35 | 4.44 | 03-NOV-13:20 | 0.00 | 0.00 |
December | 0.169204E+09 | 3003.99 | 15-DEC-13:10 | 29.65 | 0.724285E+09 | 0.00 | 0.893489E+09 | 0.17 | 4.29 | 18-DEC-21:00 | 0.00 | 0.00 |
Annual Sum or Average | 0.648974E+12 | 2595.22 | 0.423702E+13 | 0.00 | 0.488599E+13 | 1.65 | 0.00 | 0.00 | ||||
Minimum of Months | 0.169204E+09 | 1855.78 | 29.65 | 0.724285E+09 | 0.00 | 0.893489E+09 | 0.17 | 4.29 | 0.00 | 0.00 | ||
Maximum of Months | 0.181089E+12 | 239339.02 | 555.01 | 0.120757E+13 | 0.00 | 0.138865E+13 | 4.49 | 7.57 | 0.00 | 0.00 |
Report: ChillerReportMonthly
For: COOLSYS1 CHILLER2
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportCHILLER ELECTRICITY ENERGY [J] | CHILLER ELECTRICITY RATE {Maximum} [W] | CHILLER ELECTRICITY RATE {TIMESTAMP} | CHILLER ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | CHILLER EVAPORATOR COOLING ENERGY [J] | CHILLER EVAPORATOR COOLING RATE [] | CHILLER CONDENSER HEAT TRANSFER ENERGY [J] | CHILLER COP [W/W] | CHILLER COP {Maximum} [W/W] | CHILLER COP {TIMESTAMP} | CHILLER PART LOAD RATIO [] | CHILLER PART LOAD RATIO [] | |
January | 0.00 | 0.00 | 01-JAN-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 |
April | 0.255574E+10 | 141820.07 | 18-APR-09:05 | 6.00 | 0.177535E+11 | 0.00 | 0.203093E+11 | 0.06 | 7.24 | 18-APR-09:05 | 0.00 | 0.00 |
May | 0.515722E+10 | 128311.47 | 30-MAY-11:00 | 12.50 | 0.361805E+11 | 0.00 | 0.413377E+11 | 0.12 | 7.17 | 31-MAY-08:20 | 0.00 | 0.00 |
June | 0.294904E+11 | 196898.30 | 26-JUN-07:50 | 64.90 | 0.204299E+12 | 0.00 | 0.233789E+12 | 0.62 | 7.32 | 27-JUN-04:15 | 0.00 | 0.00 |
July | 0.441280E+11 | 187155.45 | 07-JUL-11:00 | 96.83 | 0.305102E+12 | 0.00 | 0.349230E+12 | 0.90 | 7.26 | 18-JUL-16:00 | 0.00 | 0.00 |
August | 0.452591E+11 | 239339.02 | 04-AUG-07:10 | 97.00 | 0.310435E+12 | 0.00 | 0.355694E+12 | 0.89 | 7.22 | 22-AUG-07:40 | 0.00 | 0.00 |
September | 0.105777E+11 | 147122.14 | 11-SEP-09:40 | 25.17 | 0.743682E+11 | 0.00 | 0.849460E+11 | 0.24 | 7.24 | 05-SEP-14:30 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.137168E+12 | 302.40 | 0.948138E+12 | 0.00 | 0.108531E+13 | 0.24 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.452591E+11 | 239339.02 | 97.00 | 0.310435E+12 | 0.00 | 0.355694E+12 | 0.90 | 7.32 | 0.00 | 0.00 |
Report: TowerReportMonthly
For: CENTRAL TOWER
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportCOOLING TOWER FAN ELECTRICITY ENERGY [J] | COOLING TOWER FAN ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | COOLING TOWER FAN ELECTRICITY RATE {Maximum} [W] | COOLING TOWER FAN ELECTRICITY RATE {TIMESTAMP} | COOLING TOWER HEAT TRANSFER RATE {Maximum} [W] | COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} | COOLING TOWER INLET TEMPERATURE [C] | COOLING TOWER OUTLET TEMPERATURE [C] | COOLING TOWER MASS FLOW RATE [kg/s] | |
January | 0.410648E+09 | 744.00 | 945.19 | 12-JAN-16:20 | 34805.27 | 12-JAN-16:40 | 18.51 | 18.33 | 14.64 |
February | 0.192332E+10 | 672.00 | 2603.65 | 24-FEB-16:40 | 71357.53 | 24-FEB-17:00 | 19.11 | 18.33 | 14.64 |
March | 0.805427E+10 | 744.00 | 49248.27 | 19-MAR-13:02 | 244131.78 | 19-MAR-16:03 | 19.90 | 18.35 | 14.64 |
April | 0.303561E+11 | 720.00 | 49248.27 | 10-APR-11:50 | 720376.13 | 16-APR-17:41 | 22.86 | 19.41 | 14.64 |
May | 0.367548E+11 | 744.00 | 49248.27 | 04-MAY-09:30 | 273179.45 | 30-MAY-14:10 | 19.97 | 19.17 | 14.64 |
June | 0.853616E+11 | 720.00 | 49248.27 | 07-JUN-09:50 | 682974.47 | 13-JUN-12:10 | 26.37 | 22.78 | 14.64 |
July | 0.119076E+12 | 744.00 | 49248.27 | 01-JUL-00:10 | 755065.86 | 26-JUL-19:00 | 33.89 | 25.45 | 14.64 |
August | 0.120416E+12 | 744.00 | 49248.27 | 01-AUG-00:10 | 796733.35 | 04-AUG-16:15 | 36.42 | 25.79 | 14.64 |
September | 0.530591E+11 | 720.00 | 49248.27 | 01-SEP-08:40 | 289119.97 | 11-SEP-10:50 | 21.48 | 20.37 | 14.64 |
October | 0.112033E+11 | 744.00 | 49248.27 | 01-OCT-11:43 | 239416.87 | 20-OCT-15:00 | 19.49 | 18.39 | 14.64 |
November | 0.621740E+10 | 720.00 | 32559.56 | 03-NOV-14:30 | 134285.08 | 03-NOV-14:30 | 19.79 | 18.33 | 14.64 |
December | 0.438106E+10 | 744.00 | 3503.09 | 02-DEC-14:00 | 119923.49 | 01-DEC-16:10 | 20.20 | 18.33 | 14.64 |
Annual Sum or Average | 0.477214E+12 | 8760.00 | 23.20 | 20.27 | 14.64 | ||||
Minimum of Months | 0.410648E+09 | 672.00 | 945.19 | 34805.27 | 18.51 | 18.33 | 14.64 | ||
Maximum of Months | 0.120416E+12 | 744.00 | 49248.27 | 796733.35 | 36.42 | 25.79 | 14.64 |
Report: TowerReportMonthly
For: TOWERWATERSYS COOLTOWER 1
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportCOOLING TOWER FAN ELECTRICITY ENERGY [J] | COOLING TOWER FAN ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | COOLING TOWER FAN ELECTRICITY RATE {Maximum} [W] | COOLING TOWER FAN ELECTRICITY RATE {TIMESTAMP} | COOLING TOWER HEAT TRANSFER RATE {Maximum} [W] | COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} | COOLING TOWER INLET TEMPERATURE [C] | COOLING TOWER OUTLET TEMPERATURE [C] | COOLING TOWER MASS FLOW RATE [kg/s] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 291945.84 | 04-JAN-02:13 | 20.93 | 20.92 | 0.49 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 291740.35 | 27-FEB-05:01 | 20.92 | 20.92 | 0.38 |
March | 3180284.05 | 5.94 | 372.37 | 19-MAR-14:05 | 292022.01 | 21-MAR-06:20 | 20.96 | 20.95 | 1.92 |
April | 0.225033E+10 | 67.28 | 22279.02 | 15-APR-10:00 | 1400094.08 | 18-APR-08:50 | 21.22 | 21.02 | 9.94 |
May | 0.396514E+10 | 201.90 | 22279.02 | 04-MAY-13:20 | 1534044.41 | 04-MAY-15:40 | 21.67 | 21.21 | 24.93 |
June | 0.176613E+11 | 373.33 | 22279.02 | 08-JUN-15:40 | 1629886.86 | 20-JUN-15:50 | 23.19 | 21.93 | 40.87 |
July | 0.258168E+11 | 503.21 | 22279.02 | 01-JUL-07:50 | 1537056.24 | 19-JUL-10:50 | 23.83 | 22.17 | 53.86 |
August | 0.221618E+11 | 461.16 | 22279.02 | 01-AUG-07:05 | 1767753.44 | 04-AUG-07:20 | 23.60 | 22.02 | 51.60 |
September | 0.586008E+10 | 220.49 | 22279.02 | 01-SEP-14:50 | 1684293.28 | 05-SEP-13:10 | 22.02 | 21.33 | 26.55 |
October | 57814437.87 | 33.57 | 2428.12 | 20-OCT-15:00 | 1097104.99 | 20-OCT-15:00 | 21.09 | 21.02 | 5.55 |
November | 2060067.55 | 3.50 | 229.12 | 03-NOV-13:20 | 359616.98 | 03-NOV-13:20 | 20.92 | 20.91 | 1.23 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 292130.36 | 26-DEC-07:20 | 20.98 | 20.97 | 0.21 |
Annual Sum or Average | 0.777785E+11 | 1870.39 | 21.78 | 21.28 | 18.26 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 291740.35 | 20.92 | 20.91 | 0.21 | ||
Maximum of Months | 0.258168E+11 | 503.21 | 22279.02 | 1767753.44 | 23.83 | 22.17 | 53.86 |
Report: TowerReportMonthly
For: TOWERWATERSYS COOLTOWER 2
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportCOOLING TOWER FAN ELECTRICITY ENERGY [J] | COOLING TOWER FAN ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | COOLING TOWER FAN ELECTRICITY RATE {Maximum} [W] | COOLING TOWER FAN ELECTRICITY RATE {TIMESTAMP} | COOLING TOWER HEAT TRANSFER RATE {Maximum} [W] | COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} | COOLING TOWER INLET TEMPERATURE [C] | COOLING TOWER OUTLET TEMPERATURE [C] | COOLING TOWER MASS FLOW RATE [kg/s] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 | 20.93 | 20.93 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 20.92 | 20.92 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 | 20.96 | 20.96 | 0.00 |
April | 0.494594E+09 | 6.17 | 22279.02 | 18-APR-09:05 | 1160934.36 | 18-APR-09:05 | 21.22 | 21.19 | 0.64 |
May | 0.104266E+10 | 13.00 | 22279.02 | 12-MAY-13:30 | 1059497.42 | 30-MAY-11:00 | 21.67 | 21.62 | 1.30 |
June | 0.606461E+10 | 76.04 | 22279.02 | 09-JUN-10:00 | 1546160.23 | 26-JUN-07:50 | 23.19 | 22.83 | 7.41 |
July | 0.999432E+10 | 124.89 | 22279.02 | 03-JUL-07:20 | 1482621.79 | 07-JUL-11:00 | 23.83 | 23.24 | 11.35 |
August | 0.975561E+10 | 121.91 | 22279.02 | 01-AUG-07:30 | 1767753.44 | 04-AUG-07:20 | 23.60 | 23.02 | 11.14 |
September | 0.212542E+10 | 26.50 | 22279.02 | 05-SEP-13:20 | 1230233.86 | 05-SEP-15:50 | 22.02 | 21.90 | 2.74 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 21.09 | 21.09 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 20.92 | 20.92 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 20.98 | 20.98 | 0.00 |
Annual Sum or Average | 0.294772E+11 | 368.50 | 21.78 | 21.64 | 2.91 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 20.92 | 20.92 | 0.00 | ||
Maximum of Months | 0.999432E+10 | 124.89 | 22279.02 | 1767753.44 | 23.83 | 23.24 | 11.35 |
Report: BoilerReportMonthly
For: HEATSYS1 BOILER
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportBOILER HEATING ENERGY [J] | BOILER GAS CONSUMPTION [] | BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] | BOILER HEATING RATE {Maximum} [W] | BOILER HEATING RATE {TIMESTAMP} | BOILER GAS CONSUMPTION RATE [] | BOILER INLET TEMPERATURE [C] | BOILER OUTLET TEMPERATURE [C] | BOILER MASS FLOW RATE [kg/s] | BOILER ANCILLARY ELECTRICITY RATE [W] | BOILER PART LOAD RATIO [] | BOILER PART LOAD RATIO {Maximum} [] | BOILER PART LOAD RATIO {TIMESTAMP} | |
January | 0.100068E+13 | 0.00 | 670.07 | 2863880.51 | 30-JAN-07:02 | 0.00 | 36.02 | 77.10 | 2.29 | 0.00 | 0.10 | 0.76 | 30-JAN-07:02 |
February | 0.702818E+12 | 0.00 | 558.74 | 2858859.26 | 02-FEB-07:02 | 0.00 | 34.01 | 73.05 | 1.95 | 0.00 | 0.08 | 0.76 | 02-FEB-07:02 |
March | 0.244686E+12 | 0.00 | 483.17 | 2089523.17 | 07-MAR-06:01 | 0.00 | 29.31 | 61.91 | 0.49 | 0.00 | 0.02 | 0.55 | 07-MAR-06:01 |
April | 0.891709E+11 | 0.00 | 310.46 | 1927689.98 | 03-APR-05:01 | 0.00 | 28.42 | 51.29 | 0.17 | 0.00 | 0.01 | 0.51 | 03-APR-05:01 |
May | 0.507629E+10 | 0.00 | 81.91 | 1559900.23 | 02-MAY-04:11 | 0.00 | 24.72 | 30.98 | 0.01 | 0.00 | 0.00 | 0.41 | 02-MAY-04:11 |
June | 0.123705E+10 | 0.00 | 29.33 | 238739.65 | 02-JUN-05:03 | 0.00 | 25.34 | 27.63 | 0.00 | 0.00 | 0.00 | 0.06 | 02-JUN-05:03 |
July | 20753.57 | 0.00 | 0.17 | 37.07 | 24-JUL-06:10 | 0.00 | 25.33 | 25.34 | 0.00 | 0.00 | 0.00 | 0.00 | 24-JUL-06:10 |
August | 39572087.13 | 0.00 | 2.42 | 26212.05 | 16-AUG-06:15 | 0.00 | 25.50 | 25.69 | 0.00 | 0.00 | 0.00 | 0.01 | 16-AUG-06:15 |
September | 0.125561E+11 | 0.00 | 116.32 | 1537769.58 | 30-SEP-04:01 | 0.00 | 25.07 | 34.22 | 0.02 | 0.00 | 0.00 | 0.41 | 30-SEP-04:01 |
October | 0.625748E+11 | 0.00 | 308.36 | 1874152.86 | 16-OCT-04:11 | 0.00 | 24.40 | 47.56 | 0.11 | 0.00 | 0.01 | 0.50 | 16-OCT-04:11 |
November | 0.300056E+12 | 0.00 | 493.29 | 2026568.60 | 13-NOV-06:01 | 0.00 | 29.40 | 64.16 | 0.62 | 0.00 | 0.03 | 0.54 | 13-NOV-06:01 |
December | 0.583210E+12 | 0.00 | 625.14 | 2280148.89 | 18-DEC-05:01 | 0.00 | 33.26 | 73.91 | 1.19 | 0.00 | 0.06 | 0.61 | 18-DEC-05:01 |
Annual Sum or Average | 0.300210E+13 | 0.00 | 3679.39 | 0.00 | 28.37 | 49.26 | 0.56 | 0.00 | 0.03 | ||||
Minimum of Months | 20753.57 | 0.00 | 0.17 | 37.07 | 0.00 | 24.40 | 25.34 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.100068E+13 | 0.00 | 670.07 | 2863880.51 | 0.00 | 36.02 | 77.10 | 2.29 | 0.00 | 0.10 | 0.76 |
Report: BoilerReportMonthly
For: CENTRAL BOILER
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportBOILER HEATING ENERGY [J] | BOILER GAS CONSUMPTION [] | BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] | BOILER HEATING RATE {Maximum} [W] | BOILER HEATING RATE {TIMESTAMP} | BOILER GAS CONSUMPTION RATE [] | BOILER INLET TEMPERATURE [C] | BOILER OUTLET TEMPERATURE [C] | BOILER MASS FLOW RATE [kg/s] | BOILER ANCILLARY ELECTRICITY RATE [W] | BOILER PART LOAD RATIO [] | BOILER PART LOAD RATIO [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 0.00 | 18.51 | 18.51 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 19.11 | 19.11 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 19.90 | 19.90 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 22.86 | 22.86 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 19.97 | 19.97 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 26.37 | 26.37 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 33.89 | 33.89 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 36.42 | 36.42 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 21.48 | 21.48 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 19.49 | 19.49 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 19.79 | 19.79 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 20.20 | 20.20 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 23.20 | 23.20 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.51 | 18.51 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36.42 | 36.42 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: VAV_BOT WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 9072185.77 | 0.00 | 5.15 | 9072185.77 | 0.00 | 0.00 | 0.00 | 0.00 | 6820.68 | 12-JAN-15:50 | 6820.68 | 12-JAN-15:50 | 0.00 | 0.00 | 0.00 |
February | 30375945.91 | 0.00 | 18.21 | 30375945.91 | 0.00 | 0.00 | 0.00 | 0.00 | 20986.37 | 17-FEB-16:30 | 20986.37 | 17-FEB-16:30 | 0.00 | 0.00 | 0.00 |
March | 0.756454E+09 | 0.00 | 42.14 | 0.756454E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 24746.07 | 28-MAR-14:40 | 24746.07 | 28-MAR-14:40 | 0.00 | 0.00 | 0.00 |
April | 0.151676E+11 | 0.00 | 110.53 | 0.137049E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 193752.86 | 18-APR-09:30 | 136327.72 | 18-APR-15:10 | 0.00 | 0.00 | 0.00 |
May | 0.328973E+11 | 0.00 | 252.81 | 0.286590E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 173213.39 | 30-MAY-11:00 | 124590.08 | 30-MAY-15:20 | 0.00 | 0.00 | 0.00 |
June | 0.992520E+11 | 0.00 | 387.11 | 0.782513E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 264450.79 | 26-JUN-05:03 | 135756.52 | 26-JUN-15:40 | 0.00 | 0.00 | 0.00 |
July | 0.147030E+12 | 0.00 | 533.14 | 0.103351E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 251431.88 | 03-JUL-08:50 | 139217.05 | 03-JUL-15:10 | 0.00 | 0.00 | 0.00 |
August | 0.149682E+12 | 0.00 | 529.86 | 0.106036E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 345947.82 | 04-AUG-05:03 | 150727.75 | 04-AUG-14:50 | 0.00 | 0.00 | 0.00 |
September | 0.487271E+11 | 0.00 | 251.70 | 0.459849E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 202661.59 | 11-SEP-09:50 | 131901.95 | 06-SEP-15:50 | 0.00 | 0.00 | 0.00 |
October | 0.425736E+10 | 0.00 | 58.34 | 0.425736E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 89851.30 | 20-OCT-15:00 | 89851.30 | 20-OCT-15:00 | 0.00 | 0.00 | 0.00 |
November | 0.433232E+09 | 0.00 | 24.12 | 0.433232E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 28302.27 | 03-NOV-13:40 | 28302.27 | 03-NOV-13:40 | 0.00 | 0.00 | 0.00 |
December | 21023358.35 | 0.00 | 6.33 | 21023358.35 | 0.00 | 0.00 | 0.00 | 0.00 | 12793.81 | 07-DEC-13:30 | 12793.81 | 07-DEC-13:30 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.498263E+12 | 0.00 | 2219.43 | 0.381495E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 9072185.77 | 0.00 | 5.15 | 9072185.77 | 0.00 | 0.00 | 0.00 | 0.00 | 6820.68 | 6820.68 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.149682E+12 | 0.00 | 533.14 | 0.106036E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 345947.82 | 150727.75 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: VAV_MID WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 29315269.17 | 0.00 | 65.89 | 29315269.17 | 0.00 | 0.00 | 0.00 | 0.00 | 54938.69 | 12-JAN-14:40 | 54938.69 | 12-JAN-14:40 | 0.00 | 0.00 | 0.00 |
February | 27029005.22 | 0.00 | 38.14 | 27029005.22 | 0.00 | 0.00 | 0.00 | 0.00 | 13290.72 | 17-FEB-16:20 | 13290.72 | 17-FEB-16:20 | 0.00 | 0.00 | 0.00 |
March | 0.522420E+10 | 0.00 | 50.91 | 0.522420E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 191380.67 | 21-MAR-10:40 | 191380.67 | 21-MAR-10:40 | 0.00 | 0.00 | 0.00 |
April | 0.112402E+12 | 0.00 | 111.81 | 0.100644E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1417926.50 | 18-APR-09:25 | 1130603.38 | 18-APR-15:10 | 0.00 | 0.00 | 0.00 |
May | 0.279891E+12 | 0.00 | 252.92 | 0.245636E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1396174.04 | 30-MAY-11:00 | 1125245.91 | 31-MAY-15:00 | 0.00 | 0.00 | 0.00 |
June | 0.833663E+12 | 0.00 | 363.77 | 0.666256E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 2360031.57 | 26-JUN-04:12 | 1294381.61 | 25-JUN-17:01 | 0.00 | 0.00 | 0.00 |
July | 0.114616E+13 | 0.00 | 451.88 | 0.829211E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 2078522.09 | 26-JUL-05:03 | 1291236.12 | 02-JUL-16:31 | 0.00 | 0.00 | 0.00 |
August | 0.109160E+13 | 0.00 | 436.19 | 0.802374E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 3402686.59 | 04-AUG-05:03 | 1324857.74 | 04-AUG-15:20 | 0.00 | 0.00 | 0.00 |
September | 0.425327E+12 | 0.00 | 246.96 | 0.401357E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1645837.54 | 11-SEP-09:40 | 1219207.90 | 07-SEP-16:00 | 0.00 | 0.00 | 0.00 |
October | 0.325785E+11 | 0.00 | 72.86 | 0.325785E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 750682.04 | 20-OCT-15:00 | 750682.04 | 20-OCT-15:00 | 0.00 | 0.00 | 0.00 |
November | 0.360259E+10 | 0.00 | 41.98 | 0.360259E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 236915.10 | 03-NOV-13:40 | 236915.10 | 03-NOV-13:40 | 0.00 | 0.00 | 0.00 |
December | 8640854.02 | 0.00 | 23.07 | 8640854.02 | 0.00 | 0.00 | 0.00 | 0.00 | 6258.19 | 02-DEC-14:20 | 6258.19 | 02-DEC-14:20 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.393051E+13 | 0.00 | 2156.39 | 0.308695E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 8640854.02 | 0.00 | 23.07 | 8640854.02 | 0.00 | 0.00 | 0.00 | 0.00 | 6258.19 | 6258.19 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.114616E+13 | 0.00 | 451.88 | 0.829211E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 3402686.59 | 1324857.74 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: VAV_TOP WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 3479025.07 | 0.00 | 5.37 | 3479025.07 | 0.00 | 0.00 | 0.00 | 0.00 | 1749.41 | 25-JAN-06:04 | 1749.41 | 25-JAN-06:04 | 0.00 | 0.00 | 0.00 |
February | 4713850.52 | 0.00 | 18.14 | 4713850.52 | 0.00 | 0.00 | 0.00 | 0.00 | 842.62 | 08-FEB-11:20 | 842.62 | 08-FEB-11:20 | 0.00 | 0.00 | 0.00 |
March | 0.452687E+09 | 0.00 | 56.82 | 0.452687E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 17733.46 | 25-MAR-15:00 | 17733.46 | 25-MAR-15:00 | 0.00 | 0.00 | 0.00 |
April | 0.121570E+11 | 0.00 | 124.11 | 0.108027E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 209257.50 | 16-APR-15:41 | 152316.96 | 16-APR-15:41 | 0.00 | 0.00 | 0.00 |
May | 0.297247E+11 | 0.00 | 244.13 | 0.261336E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 148133.49 | 30-MAY-12:00 | 135646.94 | 31-MAY-15:00 | 0.00 | 0.00 | 0.00 |
June | 0.912012E+11 | 0.00 | 356.64 | 0.731301E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 242633.38 | 26-JUN-04:12 | 163887.48 | 11-JUN-14:41 | 0.00 | 0.00 | 0.00 |
July | 0.124036E+12 | 0.00 | 446.88 | 0.892989E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 266083.58 | 04-JUL-17:21 | 156683.53 | 04-JUL-16:01 | 0.00 | 0.00 | 0.00 |
August | 0.114658E+12 | 0.00 | 429.43 | 0.852281E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 347748.56 | 03-AUG-05:03 | 159379.52 | 04-AUG-15:20 | 0.00 | 0.00 | 0.00 |
September | 0.440558E+11 | 0.00 | 243.02 | 0.416307E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 175908.34 | 11-SEP-10:00 | 144063.40 | 07-SEP-16:00 | 0.00 | 0.00 | 0.00 |
October | 0.279138E+10 | 0.00 | 81.42 | 0.279138E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 73234.38 | 20-OCT-15:00 | 73234.38 | 20-OCT-15:00 | 0.00 | 0.00 | 0.00 |
November | 0.197745E+09 | 0.00 | 32.96 | 0.197745E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 17530.07 | 03-NOV-14:00 | 17530.07 | 03-NOV-14:00 | 0.00 | 0.00 | 0.00 |
December | 2632868.35 | 0.00 | 4.15 | 2632868.35 | 0.00 | 0.00 | 0.00 | 0.00 | 1112.30 | 12-DEC-23:53 | 1112.30 | 12-DEC-23:53 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.419285E+12 | 0.00 | 2043.07 | 0.329677E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 2632868.35 | 0.00 | 4.15 | 2632868.35 | 0.00 | 0.00 | 0.00 | 0.00 | 842.62 | 842.62 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.124036E+12 | 0.00 | 446.88 | 0.892989E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 347748.56 | 163887.48 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: CAV_BAS COOLING COIL
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 83777.90 | 0.00 | 1.39 | 83777.90 | 0.00 | 0.00 | 0.00 | 0.00 | 107.29 | 02-JAN-16:40 | 107.29 | 02-JAN-16:40 | 0.00 | 0.00 | 0.00 |
February | 367811.27 | 0.00 | 0.83 | 367811.27 | 0.00 | 0.00 | 0.00 | 0.00 | 425.89 | 09-FEB-08:30 | 425.89 | 09-FEB-08:30 | 0.00 | 0.00 | 0.00 |
March | 26256360.24 | 0.00 | 4.50 | 26256360.24 | 0.00 | 0.00 | 0.00 | 0.00 | 5855.96 | 28-MAR-15:00 | 5855.96 | 28-MAR-15:00 | 0.00 | 0.00 | 0.00 |
April | 0.574840E+10 | 0.00 | 49.45 | 0.538173E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 82590.97 | 18-APR-09:20 | 66387.68 | 18-APR-14:00 | 0.00 | 0.00 | 0.00 |
May | 0.145144E+11 | 0.00 | 142.59 | 0.134037E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 109683.37 | 30-MAY-11:00 | 71499.98 | 30-MAY-13:10 | 0.00 | 0.00 | 0.00 |
June | 0.501647E+11 | 0.00 | 288.09 | 0.414531E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 172459.73 | 26-JUN-07:20 | 78807.54 | 25-JUN-20:10 | 0.00 | 0.00 | 0.00 |
July | 0.731938E+11 | 0.00 | 358.48 | 0.553452E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 183753.85 | 04-JUL-17:29 | 110722.09 | 30-JUL-16:27 | 0.00 | 0.00 | 0.00 |
August | 0.777734E+11 | 0.00 | 377.74 | 0.581813E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 200880.14 | 04-AUG-05:15 | 102400.93 | 27-AUG-16:01 | 0.00 | 0.00 | 0.00 |
September | 0.277808E+11 | 0.00 | 184.38 | 0.265798E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 131978.81 | 11-SEP-09:00 | 105326.86 | 10-SEP-15:05 | 0.00 | 0.00 | 0.00 |
October | 0.188053E+10 | 0.00 | 34.21 | 0.187338E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 53319.10 | 20-OCT-15:00 | 53319.10 | 20-OCT-15:00 | 0.00 | 0.00 | 0.00 |
November | 61208898.32 | 0.00 | 2.73 | 40910278.63 | 0.00 | 0.00 | 0.00 | 0.00 | 71031.87 | 09-NOV-05:12 | 42622.45 | 09-NOV-05:12 | 0.00 | 0.00 | 0.00 |
December | 126762.73 | 0.00 | 1.48 | 126762.73 | 0.00 | 0.00 | 0.00 | 0.00 | 124.15 | 15-DEC-13:10 | 124.15 | 15-DEC-13:10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.251144E+12 | 0.00 | 1445.87 | 0.202286E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 83777.90 | 0.00 | 0.83 | 83777.90 | 0.00 | 0.00 | 0.00 | 0.00 | 107.29 | 107.29 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.777734E+11 | 0.00 | 377.74 | 0.581813E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 200880.14 | 110722.09 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: AIRLOOP DATACENTER BASEMENT COOLING COIL
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.595031E+10 | 0.415777E+10 | 744.00 | 0.595022E+10 | 91958.80 | 0.00 | 0.02 | 22-JAN-11:00 | 0.01 | 18-JAN-01:00 | 2610.47 | 22-JAN-11:00 | 2610.47 | 22-JAN-11:00 | 12.23 | 18-JAN-01:40 | 1660.06 | 22-JAN-11:00 | 0.00 |
February | 0.100733E+11 | 0.516669E+10 | 672.00 | 0.991145E+10 | 0.161888E+09 | 0.00 | 0.03 | 20-FEB-17:15 | 0.02 | 24-FEB-16:00 | 5127.24 | 20-FEB-17:43 | 5127.24 | 20-FEB-17:43 | 156.27 | 02-FEB-05:51 | 2425.77 | 20-FEB-17:15 | 0.00 |
March | 0.169035E+11 | 0.769461E+10 | 730.32 | 0.161339E+11 | 0.769591E+09 | 0.00 | 0.35 | 19-MAR-15:57 | 0.01 | 26-MAR-01:10 | 124324.68 | 19-MAR-15:53 | 100852.24 | 25-MAR-15:00 | 29695.01 | 19-MAR-15:53 | 35838.41 | 19-MAR-16:00 | 0.00 |
April | 0.139867E+12 | 0.437382E+11 | 706.95 | 0.105300E+12 | 0.345670E+11 | 0.00 | 1.00 | 15-APR-09:40 | 0.01 | 17-APR-05:02 | 438586.94 | 18-APR-09:55 | 399264.59 | 15-APR-17:43 | 194619.70 | 18-APR-08:20 | 142450.17 | 15-APR-15:00 | 0.00 |
May | 0.180099E+11 | 0.835365E+10 | 454.68 | 0.150271E+11 | 0.298279E+10 | 0.00 | 0.44 | 30-MAY-14:10 | 0.00 | 24-MAY-06:00 | 171118.86 | 30-MAY-14:10 | 131528.80 | 05-MAY-16:30 | 48082.02 | 30-MAY-18:00 | 54264.17 | 30-MAY-14:10 | 0.00 |
June | 0.233604E+12 | 0.748487E+11 | 509.44 | 0.169240E+12 | 0.643642E+11 | 0.00 | 1.00 | 13-JUN-12:10 | 0.00 | 01-JUN-21:00 | 467179.35 | 13-JUN-12:00 | 224158.66 | 26-JUN-16:00 | 253364.20 | 13-JUN-12:00 | 135022.92 | 13-JUN-12:10 | 0.00 |
July | 0.699123E+12 | 0.200453E+12 | 702.83 | 0.392450E+12 | 0.306673E+12 | 0.00 | 1.00 | 02-JUL-08:62 | 0.01 | 24-JUL-03:00 | 491902.06 | 26-JUL-19:00 | 345003.97 | 02-JUL-14:02 | 332794.75 | 26-JUL-19:00 | 145503.20 | 26-JUL-15:10 | 0.00 |
August | 0.881150E+12 | 0.249058E+12 | 736.97 | 0.498873E+12 | 0.382277E+12 | 0.00 | 1.00 | 01-AUG-06:55 | 0.01 | 31-AUG-23:30 | 483459.47 | 04-AUG-13:00 | 400742.95 | 10-AUG-16:10 | 346753.09 | 04-AUG-07:00 | 156713.75 | 04-AUG-16:00 | 0.00 |
September | 0.468914E+11 | 0.186612E+11 | 519.25 | 0.427932E+11 | 0.409819E+10 | 0.00 | 0.47 | 11-SEP-10:50 | 0.00 | 02-SEP-05:50 | 188273.03 | 11-SEP-10:50 | 133563.86 | 07-SEP-16:00 | 61569.00 | 11-SEP-10:50 | 58265.88 | 11-SEP-10:50 | 0.00 |
October | 0.116167E+11 | 0.598312E+10 | 685.37 | 0.113259E+11 | 0.290873E+09 | 0.00 | 0.38 | 20-OCT-15:00 | 0.00 | 02-OCT-03:50 | 128590.30 | 20-OCT-15:00 | 128590.30 | 20-OCT-15:00 | 10676.95 | 21-OCT-15:00 | 43148.14 | 20-OCT-15:00 | 0.00 |
November | 0.118511E+11 | 0.606837E+10 | 638.02 | 0.115945E+11 | 0.256653E+09 | 0.00 | 0.12 | 03-NOV-14:30 | 0.01 | 06-NOV-03:20 | 35107.17 | 03-NOV-14:00 | 33703.68 | 03-NOV-15:00 | 3811.64 | 03-NOV-13:30 | 11221.01 | 03-NOV-14:30 | 0.00 |
December | 0.150260E+11 | 0.753774E+10 | 744.00 | 0.150070E+11 | 18978494.00 | 0.00 | 0.03 | 07-DEC-14:35 | 0.03 | 05-DEC-05:12 | 5963.84 | 02-DEC-19:10 | 5686.17 | 03-DEC-08:43 | 355.52 | 02-DEC-19:00 | 2932.72 | 07-DEC-14:35 | 0.00 |
Annual Sum or Average | 0.209007E+13 | 0.631721E+12 | 7843.83 | 0.129361E+13 | 0.796460E+12 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.595031E+10 | 0.415777E+10 | 454.68 | 0.595022E+10 | 91958.80 | 0.00 | 0.02 | 0.00 | 2610.47 | 2610.47 | 12.23 | 1660.06 | 0.00 | ||||||
Maximum of Months | 0.881150E+12 | 0.249058E+12 | 744.00 | 0.498873E+12 | 0.382277E+12 | 0.00 | 1.00 | 0.03 | 491902.06 | 400742.95 | 346753.09 | 156713.75 | 0.00 |
Report: DXReportMonthly
For: AIRLOOP DATACENTER BOT COOLING COIL
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.193716E+10 | 0.573297E+09 | 697.17 | 0.193716E+10 | -0.0 | 0.00 | 0.27 | 12-JAN-16:30 | 0.00 | 06-JAN-04:43 | 2221.98 | 12-JAN-16:30 | 2221.98 | 12-JAN-16:30 | 0.00 | 11-JAN-02:20 | 576.34 | 12-JAN-16:30 | 0.00 |
February | 0.726866E+10 | 0.189943E+10 | 672.00 | 0.726866E+10 | -0.0 | 0.00 | 0.55 | 19-FEB-17:03 | 0.16 | 02-FEB-07:02 | 4657.26 | 24-FEB-17:00 | 4657.26 | 24-FEB-17:00 | 0.00 | 24-FEB-07:10 | 1171.90 | 19-FEB-17:03 | 0.00 |
March | 0.146001E+11 | 0.352818E+10 | 744.00 | 0.145991E+11 | 980332.09 | 0.00 | 0.81 | 31-MAR-24:00 | 0.50 | 06-MAR-07:05 | 7523.72 | 31-MAR-24:00 | 7523.72 | 31-MAR-24:00 | 75.78 | 29-MAR-16:00 | 1726.73 | 31-MAR-24:00 | 0.00 |
April | 0.199062E+11 | 0.467651E+10 | 720.00 | 0.198720E+11 | 34275241.24 | 0.00 | 1.00 | 16-APR-17:41 | 0.30 | 30-APR-24:00 | 9135.66 | 16-APR-17:52 | 9135.66 | 16-APR-17:52 | 352.80 | 18-APR-15:50 | 3100.69 | 15-APR-17:41 | 0.00 |
May | 0.588705E+10 | 0.150536E+10 | 744.00 | 0.576820E+10 | 0.118856E+09 | 0.00 | 0.45 | 31-MAY-23:10 | 0.16 | 02-MAY-06:10 | 4214.80 | 31-MAY-23:10 | 4126.45 | 31-MAY-24:00 | 291.20 | 12-MAY-16:00 | 1051.27 | 31-MAY-15:00 | 0.00 |
June | 0.111715E+11 | 0.301160E+10 | 720.00 | 0.109160E+11 | 0.255589E+09 | 0.00 | 0.64 | 30-JUN-23:10 | 0.38 | 03-JUN-06:40 | 6014.31 | 30-JUN-23:05 | 5976.74 | 30-JUN-24:00 | 473.16 | 13-JUN-15:00 | 1897.01 | 25-JUN-18:21 | 0.00 |
July | 0.168711E+11 | 0.470876E+10 | 744.00 | 0.165148E+11 | 0.356227E+09 | 0.00 | 0.82 | 31-JUL-24:00 | 0.60 | 22-JUL-06:40 | 7857.82 | 31-JUL-24:00 | 7857.82 | 31-JUL-24:00 | 604.30 | 26-JUL-19:00 | 2658.68 | 26-JUL-16:00 | 0.00 |
August | 0.219404E+11 | 0.598186E+10 | 744.00 | 0.215938E+11 | 0.346580E+09 | 0.00 | 1.00 | 03-AUG-15:20 | 0.29 | 31-AUG-24:00 | 9326.77 | 04-AUG-17:07 | 9005.98 | 05-AUG-18:40 | 645.16 | 04-AUG-17:13 | 3493.90 | 04-AUG-16:00 | 0.00 |
September | 0.575813E+10 | 0.154183E+10 | 720.00 | 0.567373E+10 | 84393356.79 | 0.00 | 0.43 | 30-SEP-24:00 | 0.13 | 30-SEP-06:55 | 3607.27 | 30-SEP-24:00 | 3607.27 | 30-SEP-24:00 | 267.53 | 11-SEP-11:00 | 1157.10 | 06-SEP-15:10 | 0.00 |
October | 0.102315E+11 | 0.250067E+10 | 744.00 | 0.102215E+11 | 10001549.28 | 0.00 | 0.63 | 31-OCT-24:00 | 0.35 | 23-OCT-06:30 | 5612.47 | 31-OCT-24:00 | 5612.47 | 31-OCT-24:00 | 186.25 | 02-OCT-15:30 | 1341.29 | 31-OCT-24:00 | 0.00 |
November | 0.139936E+11 | 0.336352E+10 | 720.00 | 0.139776E+11 | 16062522.30 | 0.00 | 0.74 | 05-NOV-16:13 | 0.49 | 28-NOV-07:03 | 6794.65 | 05-NOV-16:17 | 6794.65 | 05-NOV-16:17 | 162.11 | 08-NOV-12:00 | 1587.50 | 05-NOV-16:13 | 0.00 |
December | 0.186451E+11 | 0.449279E+10 | 744.00 | 0.186451E+11 | -0.0 | 0.00 | 0.89 | 25-DEC-16:02 | 0.67 | 11-DEC-07:03 | 8006.44 | 01-DEC-16:10 | 8006.44 | 01-DEC-16:10 | 0.00 | 15-DEC-03:25 | 1885.20 | 25-DEC-16:02 | 0.00 |
Annual Sum or Average | 0.148211E+12 | 0.377838E+11 | 8713.17 | 0.146988E+12 | 0.122296E+10 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.193716E+10 | 0.573297E+09 | 672.00 | 0.193716E+10 | -0.0 | 0.00 | 0.27 | 0.00 | 2221.98 | 2221.98 | 0.00 | 576.34 | 0.00 | ||||||
Maximum of Months | 0.219404E+11 | 0.598186E+10 | 744.00 | 0.215938E+11 | 0.356227E+09 | 0.00 | 1.00 | 0.67 | 9326.77 | 9135.66 | 645.16 | 3493.90 | 0.00 |
Report: DXReportMonthly
For: AIRLOOP DATACENTER MID COOLING COIL
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.248695E+10 | 0.788806E+09 | 172.09 | 0.248695E+10 | 0.00 | 0.00 | 0.23 | 12-JAN-16:40 | 0.00 | 01-JAN-00:02 | 18236.71 | 12-JAN-16:40 | 18236.71 | 12-JAN-16:40 | 0.00 | 26-JAN-22:40 | 4790.52 | 12-JAN-16:40 | 0.00 |
February | 0.465433E+11 | 0.125319E+11 | 672.00 | 0.465433E+11 | -0.0 | 0.00 | 0.49 | 24-FEB-17:00 | 0.05 | 02-FEB-07:02 | 42077.58 | 24-FEB-17:00 | 42077.58 | 24-FEB-17:00 | 0.00 | 27-FEB-16:30 | 10051.70 | 24-FEB-17:00 | 0.00 |
March | 0.117867E+12 | 0.289829E+11 | 744.00 | 0.117857E+12 | 10263890.06 | 0.00 | 0.75 | 31-MAR-23:20 | 0.34 | 06-MAR-07:05 | 66061.16 | 31-MAR-23:20 | 66061.16 | 31-MAR-23:20 | 756.40 | 29-MAR-16:00 | 15348.43 | 31-MAR-23:20 | 0.00 |
April | 0.176123E+12 | 0.418736E+11 | 720.00 | 0.175780E+12 | 0.343009E+09 | 0.00 | 0.97 | 15-APR-17:55 | 0.19 | 30-APR-24:00 | 85472.73 | 15-APR-18:10 | 85160.70 | 16-APR-17:42 | 3505.17 | 18-APR-15:50 | 29224.53 | 15-APR-17:41 | 0.00 |
May | 0.496606E+11 | 0.128497E+11 | 744.00 | 0.484908E+11 | 0.116977E+10 | 0.00 | 0.45 | 31-MAY-23:10 | 0.07 | 02-MAY-06:10 | 40093.83 | 31-MAY-23:10 | 39082.86 | 31-MAY-24:00 | 2887.81 | 12-MAY-16:00 | 9974.94 | 31-MAY-15:00 | 0.00 |
June | 0.103303E+12 | 0.280282E+11 | 720.00 | 0.100767E+12 | 0.253637E+10 | 0.00 | 0.65 | 30-JUN-23:13 | 0.33 | 03-JUN-07:00 | 58377.22 | 30-JUN-23:05 | 58055.35 | 30-JUN-24:00 | 4709.92 | 13-JUN-15:00 | 18060.67 | 25-JUN-18:01 | 0.00 |
July | 0.159395E+12 | 0.446071E+11 | 744.00 | 0.155850E+12 | 0.354547E+10 | 0.00 | 0.81 | 31-JUL-24:00 | 0.57 | 22-JUL-06:40 | 74660.85 | 31-JUL-24:00 | 74660.85 | 31-JUL-24:00 | 6002.86 | 26-JUL-19:00 | 25221.32 | 26-JUL-16:00 | 0.00 |
August | 0.206314E+12 | 0.564429E+11 | 744.00 | 0.202854E+12 | 0.345960E+10 | 0.00 | 1.00 | 04-AUG-13:40 | 0.24 | 31-AUG-24:00 | 87836.10 | 01-AUG-18:30 | 85845.59 | 29-AUG-17:40 | 6382.77 | 04-AUG-13:00 | 33596.61 | 04-AUG-16:00 | 0.00 |
September | 0.482370E+11 | 0.131230E+11 | 720.00 | 0.474086E+11 | 0.828331E+09 | 0.00 | 0.39 | 06-SEP-17:30 | 0.06 | 30-SEP-06:10 | 32298.39 | 04-SEP-17:43 | 32152.30 | 04-SEP-17:43 | 2671.59 | 11-SEP-11:00 | 11048.32 | 06-SEP-17:00 | 0.00 |
October | 0.815834E+11 | 0.202663E+11 | 744.00 | 0.814825E+11 | 0.100937E+09 | 0.00 | 0.57 | 31-OCT-23:30 | 0.25 | 23-OCT-06:10 | 47887.83 | 31-OCT-23:30 | 47887.83 | 31-OCT-23:30 | 1854.35 | 02-OCT-15:30 | 12027.82 | 20-OCT-15:00 | 0.00 |
November | 0.109602E+12 | 0.268314E+11 | 720.00 | 0.109441E+12 | 0.161105E+09 | 0.00 | 0.68 | 05-NOV-16:23 | 0.31 | 27-NOV-03:50 | 61386.30 | 03-NOV-16:00 | 61001.06 | 03-NOV-16:00 | 1617.46 | 08-NOV-12:00 | 13936.33 | 05-NOV-16:23 | 0.00 |
December | 0.146696E+12 | 0.362285E+11 | 744.00 | 0.146696E+12 | 0.00 | 0.00 | 0.84 | 07-DEC-16:10 | 0.52 | 11-DEC-07:03 | 72528.96 | 01-DEC-16:10 | 72528.96 | 01-DEC-16:10 | 0.00 | 25-DEC-07:40 | 17125.19 | 07-DEC-16:10 | 0.00 |
Annual Sum or Average | 0.124781E+13 | 0.322554E+12 | 8188.09 | 0.123566E+13 | 0.121549E+11 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.248695E+10 | 0.788806E+09 | 172.09 | 0.248695E+10 | -0.0 | 0.00 | 0.23 | 0.00 | 18236.71 | 18236.71 | 0.00 | 4790.52 | 0.00 | ||||||
Maximum of Months | 0.206314E+12 | 0.564429E+11 | 744.00 | 0.202854E+12 | 0.354547E+10 | 0.00 | 1.00 | 0.57 | 87836.10 | 85845.59 | 6382.77 | 33596.61 | 0.00 |
Report: DXReportMonthly
For: AIRLOOP DATACENTER TOP COOLING COIL
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.128632E+09 | 39656275.72 | 74.96 | 0.128632E+09 | -0.0 | 0.00 | 0.22 | 12-JAN-16:40 | 0.00 | 01-JAN-00:02 | 1739.05 | 12-JAN-16:40 | 1739.05 | 12-JAN-16:40 | 0.00 | 12-JAN-11:30 | 459.53 | 12-JAN-16:40 | 0.00 |
February | 0.329231E+10 | 0.899114E+09 | 627.80 | 0.329231E+10 | 0.00 | 0.00 | 0.48 | 24-FEB-17:00 | 0.00 | 01-FEB-00:03 | 4229.75 | 24-FEB-17:00 | 4229.75 | 24-FEB-17:00 | 0.00 | 20-FEB-03:25 | 1011.56 | 24-FEB-17:00 | 0.00 |
March | 0.104674E+11 | 0.260278E+10 | 744.00 | 0.104664E+11 | 995976.57 | 0.00 | 0.69 | 31-MAR-23:10 | 0.20 | 06-MAR-04:01 | 6146.51 | 31-MAR-23:10 | 6146.51 | 31-MAR-23:10 | 75.15 | 29-MAR-16:00 | 1443.45 | 31-MAR-23:10 | 0.00 |
April | 0.166136E+11 | 0.398825E+10 | 720.00 | 0.165795E+11 | 34154434.67 | 0.00 | 0.99 | 16-APR-17:51 | 0.15 | 30-APR-24:00 | 8803.73 | 16-APR-17:52 | 8803.73 | 16-APR-17:52 | 351.05 | 18-APR-15:50 | 2975.83 | 15-APR-17:41 | 0.00 |
May | 0.453993E+10 | 0.118611E+10 | 743.11 | 0.442359E+10 | 0.116335E+09 | 0.00 | 0.44 | 31-MAY-23:10 | 0.00 | 01-MAY-04:12 | 3991.86 | 31-MAY-23:10 | 3880.76 | 31-MAY-23:30 | 290.54 | 12-MAY-16:00 | 1033.27 | 31-MAY-15:00 | 0.00 |
June | 0.101582E+11 | 0.277534E+10 | 720.00 | 0.990476E+10 | 0.253415E+09 | 0.00 | 0.64 | 25-JUN-18:41 | 0.26 | 03-JUN-06:10 | 5827.08 | 30-JUN-23:05 | 5788.82 | 30-JUN-24:00 | 473.10 | 13-JUN-15:00 | 1916.67 | 25-JUN-18:11 | 0.00 |
July | 0.158942E+11 | 0.446484E+10 | 744.00 | 0.155401E+11 | 0.354068E+09 | 0.00 | 0.82 | 02-JUL-18:31 | 0.53 | 12-JUL-06:05 | 7368.97 | 31-JUL-24:00 | 7368.97 | 31-JUL-24:00 | 599.81 | 26-JUL-19:00 | 2562.27 | 26-JUL-16:00 | 0.00 |
August | 0.205221E+11 | 0.563742E+10 | 744.00 | 0.201767E+11 | 0.345432E+09 | 0.00 | 1.00 | 04-AUG-13:50 | 0.22 | 31-AUG-24:00 | 8865.83 | 04-AUG-16:35 | 8654.03 | 29-AUG-17:40 | 638.80 | 04-AUG-13:00 | 3412.73 | 04-AUG-16:00 | 0.00 |
September | 0.428272E+10 | 0.118467E+10 | 712.26 | 0.420044E+10 | 82274977.39 | 0.00 | 0.40 | 06-SEP-17:30 | 0.00 | 23-SEP-04:53 | 3282.87 | 06-SEP-17:30 | 3234.82 | 04-SEP-17:43 | 269.18 | 11-SEP-11:00 | 1139.13 | 06-SEP-17:00 | 0.00 |
October | 0.671026E+10 | 0.169052E+10 | 744.00 | 0.670038E+10 | 9887786.33 | 0.00 | 0.51 | 11-OCT-16:50 | 0.10 | 16-OCT-04:13 | 4664.34 | 11-OCT-16:50 | 4601.67 | 11-OCT-16:50 | 186.40 | 02-OCT-15:30 | 1214.88 | 20-OCT-15:00 | 0.00 |
November | 0.934680E+10 | 0.231662E+10 | 720.00 | 0.933088E+10 | 15919609.79 | 0.00 | 0.65 | 03-NOV-16:00 | 0.18 | 27-NOV-01:35 | 6142.13 | 03-NOV-16:00 | 6103.73 | 03-NOV-16:00 | 161.69 | 08-NOV-12:00 | 1371.43 | 03-NOV-16:00 | 0.00 |
December | 0.130127E+11 | 0.325856E+10 | 744.00 | 0.130127E+11 | 0.00 | 0.00 | 0.80 | 07-DEC-16:10 | 0.38 | 11-DEC-03:33 | 7141.05 | 01-DEC-16:10 | 7141.05 | 01-DEC-16:10 | 0.00 | 07-DEC-23:30 | 1670.10 | 01-DEC-16:10 | 0.00 |
Annual Sum or Average | 0.114969E+12 | 0.300439E+11 | 8038.13 | 0.113756E+12 | 0.121248E+10 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.128632E+09 | 39656275.72 | 74.96 | 0.128632E+09 | -0.0 | 0.00 | 0.22 | 0.00 | 1739.05 | 1739.05 | 0.00 | 459.53 | 0.00 | ||||||
Maximum of Months | 0.205221E+11 | 0.563742E+10 | 744.00 | 0.201767E+11 | 0.354068E+09 | 0.00 | 1.00 | 0.53 | 8865.83 | 8803.73 | 638.80 | 3412.73 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 138.52 | 0.00 | 138.52 | 0.00 | 1323.17 | 0.00 | 0.00 | 0.00 |
February | 175.61 | 0.00 | 175.61 | 2.47 | 1094.02 | 0.00 | 0.00 | 0.00 |
March | 263.19 | 0.00 | 263.19 | 49.37 | 733.90 | 0.00 | 0.00 | 0.00 |
April | 303.84 | 1.50 | 302.34 | 131.56 | 520.87 | 0.00 | 0.00 | 0.00 |
May | 396.21 | 14.89 | 381.32 | 309.03 | 277.95 | 0.00 | 0.00 | 0.00 |
June | 463.08 | 42.03 | 421.05 | 496.75 | 191.06 | 0.00 | 0.00 | 0.00 |
July | 434.29 | 29.05 | 405.25 | 489.93 | 160.79 | 0.00 | 0.00 | 0.00 |
August | 363.63 | 6.44 | 357.19 | 405.44 | 192.74 | 0.00 | 0.00 | 0.00 |
September | 278.80 | 0.07 | 278.73 | 234.07 | 344.08 | 0.00 | 0.00 | 0.00 |
October | 207.29 | 0.00 | 207.29 | 61.80 | 557.12 | 0.00 | 0.00 | 0.00 |
November | 145.00 | 0.00 | 145.00 | 10.47 | 855.04 | 0.00 | 0.00 | 0.00 |
December | 94.06 | 0.00 | 94.06 | 0.00 | 1204.31 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 272.47 | 7.86 | 264.61 | 183.66 | 618.94 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 94.06 | 0.00 | 94.06 | 0.00 | 160.79 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 463.08 | 42.03 | 421.05 | 496.75 | 1323.17 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 138.52 | 0.00 | 138.52 | 0.00 | 1323.17 | 0.00 | 0.00 | 0.00 |
February | 175.61 | 0.00 | 175.61 | 2.47 | 1094.02 | 0.00 | 0.00 | 0.00 |
March | 263.19 | 0.00 | 263.19 | 49.37 | 733.90 | 0.00 | 0.00 | 0.00 |
April | 303.84 | 1.50 | 302.34 | 131.56 | 520.87 | 0.00 | 0.00 | 0.00 |
May | 396.21 | 14.89 | 381.32 | 309.03 | 277.95 | 0.00 | 0.00 | 0.00 |
June | 463.08 | 42.03 | 421.05 | 496.74 | 191.06 | 0.00 | 0.00 | 0.00 |
July | 434.29 | 29.05 | 405.25 | 489.93 | 160.79 | 0.00 | 0.00 | 0.00 |
August | 363.63 | 6.44 | 357.19 | 405.44 | 192.74 | 0.00 | 0.00 | 0.00 |
September | 278.80 | 0.07 | 278.73 | 234.07 | 344.08 | 0.00 | 0.00 | 0.00 |
October | 207.29 | 0.00 | 207.29 | 61.80 | 557.12 | 0.00 | 0.00 | 0.00 |
November | 145.00 | 0.00 | 145.00 | 10.47 | 855.04 | 0.00 | 0.00 | 0.00 |
December | 94.06 | 0.00 | 94.06 | 0.00 | 1204.31 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 272.47 | 7.86 | 264.61 | 183.66 | 618.94 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 94.06 | 0.00 | 94.06 | 0.00 | 160.79 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 463.08 | 42.03 | 421.05 | 496.74 | 1323.17 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 138.52 | 0.00 | 138.52 | 0.00 | 1323.17 | 0.00 | 0.00 | 0.00 |
February | 175.61 | 0.00 | 175.61 | 2.47 | 1094.02 | 0.00 | 0.00 | 0.00 |
March | 263.19 | 0.00 | 263.19 | 49.37 | 733.90 | 0.00 | 0.00 | 0.00 |
April | 303.84 | 1.50 | 302.34 | 131.56 | 520.87 | 0.00 | 0.00 | 0.00 |
May | 396.21 | 14.89 | 381.32 | 309.03 | 277.95 | 0.00 | 0.00 | 0.00 |
June | 463.08 | 42.03 | 421.05 | 496.75 | 191.06 | 0.00 | 0.00 | 0.00 |
July | 434.29 | 29.05 | 405.25 | 489.93 | 160.79 | 0.00 | 0.00 | 0.00 |
August | 363.63 | 6.44 | 357.19 | 405.44 | 192.74 | 0.00 | 0.00 | 0.00 |
September | 278.80 | 0.07 | 278.73 | 234.07 | 344.08 | 0.00 | 0.00 | 0.00 |
October | 207.29 | 0.00 | 207.29 | 61.80 | 557.12 | 0.00 | 0.00 | 0.00 |
November | 145.00 | 0.00 | 145.00 | 10.47 | 855.04 | 0.00 | 0.00 | 0.00 |
December | 94.06 | 0.00 | 94.06 | 0.00 | 1204.31 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 272.47 | 7.86 | 264.61 | 183.66 | 618.94 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 94.06 | 0.00 | 94.06 | 0.00 | 160.79 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 463.08 | 42.03 | 421.05 | 496.75 | 1323.17 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 138.52 | 0.00 | 138.52 | 0.00 | 1323.17 | 0.00 | 0.00 | 0.00 |
February | 175.61 | 0.00 | 175.61 | 2.47 | 1094.02 | 0.00 | 0.00 | 0.00 |
March | 263.19 | 0.00 | 263.19 | 49.37 | 733.90 | 0.00 | 0.00 | 0.00 |
April | 303.84 | 1.50 | 302.34 | 131.56 | 520.87 | 0.00 | 0.00 | 0.00 |
May | 396.21 | 14.89 | 381.32 | 309.03 | 277.95 | 0.00 | 0.00 | 0.00 |
June | 463.08 | 42.03 | 421.05 | 496.74 | 191.06 | 0.00 | 0.00 | 0.00 |
July | 434.29 | 29.05 | 405.25 | 489.93 | 160.79 | 0.00 | 0.00 | 0.00 |
August | 363.63 | 6.44 | 357.19 | 405.44 | 192.74 | 0.00 | 0.00 | 0.00 |
September | 278.80 | 0.07 | 278.73 | 234.07 | 344.08 | 0.00 | 0.00 | 0.00 |
October | 207.29 | 0.00 | 207.29 | 61.80 | 557.12 | 0.00 | 0.00 | 0.00 |
November | 145.00 | 0.00 | 145.00 | 10.47 | 855.04 | 0.00 | 0.00 | 0.00 |
December | 94.06 | 0.00 | 94.06 | 0.00 | 1204.31 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 272.47 | 7.86 | 264.61 | 183.66 | 618.94 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 94.06 | 0.00 | 94.06 | 0.00 | 160.79 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 463.08 | 42.03 | 421.05 | 496.74 | 1323.17 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 138.51 | 0.00 | 138.51 | 0.00 | 1323.12 | 0.00 | 0.00 | 0.00 |
February | 175.61 | 0.00 | 175.61 | 2.47 | 1093.98 | 0.00 | 0.00 | 0.00 |
March | 263.18 | 0.00 | 263.18 | 49.36 | 733.87 | 0.00 | 0.00 | 0.00 |
April | 303.83 | 1.50 | 302.33 | 131.56 | 520.85 | 0.00 | 0.00 | 0.00 |
May | 396.19 | 14.89 | 381.30 | 309.02 | 277.94 | 0.00 | 0.00 | 0.00 |
June | 463.06 | 42.03 | 421.03 | 496.73 | 191.05 | 0.00 | 0.00 | 0.00 |
July | 434.28 | 29.05 | 405.23 | 489.91 | 160.78 | 0.00 | 0.00 | 0.00 |
August | 363.62 | 6.44 | 357.17 | 405.42 | 192.74 | 0.00 | 0.00 | 0.00 |
September | 278.79 | 0.07 | 278.72 | 234.06 | 344.06 | 0.00 | 0.00 | 0.00 |
October | 207.29 | 0.00 | 207.29 | 61.80 | 557.10 | 0.00 | 0.00 | 0.00 |
November | 145.00 | 0.00 | 145.00 | 10.47 | 855.00 | 0.00 | 0.00 | 0.00 |
December | 94.05 | 0.00 | 94.05 | 0.00 | 1204.26 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 272.46 | 7.86 | 264.60 | 183.66 | 618.92 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 94.05 | 0.00 | 94.05 | 0.00 | 160.78 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 463.06 | 42.03 | 421.03 | 496.73 | 1323.12 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 329.80 | 135.71 | 194.08 | 118.55 | 1320.56 | 0.00 | 0.00 | 0.00 |
February | 437.14 | 192.22 | 244.92 | 215.06 | 1068.77 | 0.00 | 0.00 | 0.00 |
March | 593.94 | 235.75 | 358.19 | 398.53 | 727.50 | 0.00 | 0.00 | 0.00 |
April | 729.31 | 319.39 | 409.92 | 645.50 | 526.86 | 0.00 | 0.00 | 0.00 |
May | 915.95 | 400.23 | 515.72 | 973.58 | 302.98 | 0.00 | 0.00 | 0.00 |
June | 1007.98 | 438.96 | 569.02 | 1215.07 | 206.73 | 0.00 | 0.00 | 0.00 |
July | 1018.81 | 470.10 | 548.71 | 1264.59 | 169.43 | 0.00 | 0.00 | 0.00 |
August | 858.84 | 370.26 | 488.57 | 1066.73 | 198.37 | 0.00 | 0.00 | 0.00 |
September | 766.00 | 361.98 | 404.03 | 864.24 | 356.71 | 0.00 | 0.00 | 0.00 |
October | 488.15 | 203.90 | 284.25 | 379.95 | 558.16 | 0.00 | 0.00 | 0.00 |
November | 288.01 | 93.55 | 194.46 | 122.42 | 860.20 | 0.00 | 0.00 | 0.00 |
December | 223.10 | 95.80 | 127.29 | 81.69 | 1219.39 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 639.08 | 276.88 | 362.20 | 614.33 | 624.19 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 223.10 | 93.55 | 127.29 | 81.69 | 169.43 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1018.81 | 470.10 | 569.02 | 1264.59 | 1320.56 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 329.80 | 135.71 | 194.08 | 118.55 | 1320.56 | 0.00 | 0.00 | 0.00 |
February | 437.14 | 192.22 | 244.92 | 215.06 | 1068.77 | 0.00 | 0.00 | 0.00 |
March | 593.94 | 235.75 | 358.19 | 398.53 | 727.50 | 0.00 | 0.00 | 0.00 |
April | 729.31 | 319.39 | 409.92 | 645.50 | 526.86 | 0.00 | 0.00 | 0.00 |
May | 915.95 | 400.23 | 515.72 | 973.58 | 302.98 | 0.00 | 0.00 | 0.00 |
June | 1007.98 | 438.96 | 569.02 | 1215.07 | 206.73 | 0.00 | 0.00 | 0.00 |
July | 1018.81 | 470.10 | 548.71 | 1264.59 | 169.43 | 0.00 | 0.00 | 0.00 |
August | 858.84 | 370.26 | 488.57 | 1066.73 | 198.37 | 0.00 | 0.00 | 0.00 |
September | 766.00 | 361.98 | 404.03 | 864.24 | 356.71 | 0.00 | 0.00 | 0.00 |
October | 488.15 | 203.90 | 284.25 | 379.95 | 558.16 | 0.00 | 0.00 | 0.00 |
November | 288.01 | 93.55 | 194.46 | 122.42 | 860.20 | 0.00 | 0.00 | 0.00 |
December | 223.10 | 95.80 | 127.29 | 81.69 | 1219.39 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 639.08 | 276.88 | 362.20 | 614.33 | 624.19 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 223.10 | 93.55 | 127.29 | 81.69 | 169.43 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1018.81 | 470.10 | 569.02 | 1264.59 | 1320.56 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 329.79 | 135.71 | 194.08 | 118.55 | 1320.53 | 0.00 | 0.00 | 0.00 |
February | 437.14 | 192.22 | 244.92 | 215.06 | 1068.75 | 0.00 | 0.00 | 0.00 |
March | 593.93 | 235.75 | 358.18 | 398.52 | 727.49 | 0.00 | 0.00 | 0.00 |
April | 729.29 | 319.38 | 409.91 | 645.48 | 526.85 | 0.00 | 0.00 | 0.00 |
May | 915.93 | 400.22 | 515.71 | 973.56 | 302.98 | 0.00 | 0.00 | 0.00 |
June | 1007.96 | 438.95 | 569.01 | 1215.05 | 206.73 | 0.00 | 0.00 | 0.00 |
July | 1018.79 | 470.09 | 548.70 | 1264.57 | 169.43 | 0.00 | 0.00 | 0.00 |
August | 858.82 | 370.26 | 488.56 | 1066.72 | 198.37 | 0.00 | 0.00 | 0.00 |
September | 765.99 | 361.97 | 404.02 | 864.22 | 356.70 | 0.00 | 0.00 | 0.00 |
October | 488.14 | 203.89 | 284.25 | 379.94 | 558.15 | 0.00 | 0.00 | 0.00 |
November | 288.01 | 93.55 | 194.46 | 122.42 | 860.19 | 0.00 | 0.00 | 0.00 |
December | 223.09 | 95.80 | 127.29 | 81.69 | 1219.37 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 639.07 | 276.88 | 362.19 | 614.32 | 624.18 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 223.09 | 93.55 | 127.29 | 81.69 | 169.43 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1018.79 | 470.09 | 569.01 | 1264.57 | 1320.53 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 861.44 | 589.51 | 271.94 | 701.88 | 1058.43 | 0.00 | 0.00 | 0.00 |
February | 923.02 | 623.60 | 299.42 | 784.97 | 871.92 | 0.00 | 0.00 | 0.00 |
March | 803.24 | 422.96 | 380.28 | 716.58 | 652.23 | 0.00 | 0.00 | 0.00 |
April | 723.66 | 338.33 | 385.34 | 735.81 | 501.76 | 0.00 | 0.00 | 0.00 |
May | 599.53 | 162.54 | 436.99 | 651.17 | 296.98 | 0.00 | 0.00 | 0.00 |
June | 582.05 | 118.51 | 463.54 | 714.94 | 202.85 | 0.00 | 0.00 | 0.00 |
July | 616.14 | 155.25 | 460.89 | 794.75 | 170.43 | 0.00 | 0.00 | 0.00 |
August | 694.19 | 248.95 | 445.24 | 912.28 | 204.02 | 0.00 | 0.00 | 0.00 |
September | 841.21 | 443.25 | 397.96 | 1026.67 | 339.50 | 0.00 | 0.00 | 0.00 |
October | 878.40 | 551.07 | 327.33 | 916.21 | 505.28 | 0.00 | 0.00 | 0.00 |
November | 662.75 | 414.90 | 247.86 | 570.89 | 723.99 | 0.00 | 0.00 | 0.00 |
December | 706.73 | 535.34 | 171.39 | 622.75 | 1006.11 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 739.96 | 382.31 | 357.64 | 762.23 | 542.89 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 582.05 | 118.51 | 171.39 | 570.89 | 170.43 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 923.02 | 623.60 | 463.54 | 1026.67 | 1058.43 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 861.44 | 589.50 | 271.94 | 701.88 | 1058.43 | 0.00 | 0.00 | 0.00 |
February | 923.02 | 623.60 | 299.42 | 784.97 | 871.92 | 0.00 | 0.00 | 0.00 |
March | 803.24 | 422.96 | 380.28 | 716.58 | 652.23 | 0.00 | 0.00 | 0.00 |
April | 723.66 | 338.33 | 385.34 | 735.81 | 501.76 | 0.00 | 0.00 | 0.00 |
May | 599.53 | 162.54 | 436.99 | 651.17 | 296.98 | 0.00 | 0.00 | 0.00 |
June | 582.05 | 118.51 | 463.54 | 714.94 | 202.85 | 0.00 | 0.00 | 0.00 |
July | 616.14 | 155.25 | 460.89 | 794.75 | 170.43 | 0.00 | 0.00 | 0.00 |
August | 694.19 | 248.95 | 445.24 | 912.28 | 204.02 | 0.00 | 0.00 | 0.00 |
September | 841.21 | 443.25 | 397.96 | 1026.67 | 339.50 | 0.00 | 0.00 | 0.00 |
October | 878.40 | 551.07 | 327.33 | 916.21 | 505.28 | 0.00 | 0.00 | 0.00 |
November | 662.75 | 414.89 | 247.86 | 570.89 | 723.99 | 0.00 | 0.00 | 0.00 |
December | 706.73 | 535.34 | 171.39 | 622.75 | 1006.11 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 739.96 | 382.31 | 357.64 | 762.23 | 542.89 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 582.05 | 118.51 | 171.39 | 570.89 | 170.43 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 923.02 | 623.60 | 463.54 | 1026.67 | 1058.43 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 861.44 | 589.51 | 271.94 | 701.88 | 1058.43 | 0.00 | 0.00 | 0.00 |
February | 923.02 | 623.60 | 299.42 | 784.97 | 871.92 | 0.00 | 0.00 | 0.00 |
March | 803.24 | 422.96 | 380.28 | 716.58 | 652.23 | 0.00 | 0.00 | 0.00 |
April | 723.66 | 338.33 | 385.34 | 735.81 | 501.76 | 0.00 | 0.00 | 0.00 |
May | 599.53 | 162.54 | 436.99 | 651.17 | 296.98 | 0.00 | 0.00 | 0.00 |
June | 582.05 | 118.51 | 463.54 | 714.94 | 202.85 | 0.00 | 0.00 | 0.00 |
July | 616.14 | 155.25 | 460.89 | 794.75 | 170.43 | 0.00 | 0.00 | 0.00 |
August | 694.19 | 248.95 | 445.24 | 912.28 | 204.02 | 0.00 | 0.00 | 0.00 |
September | 841.21 | 443.25 | 397.96 | 1026.67 | 339.50 | 0.00 | 0.00 | 0.00 |
October | 878.40 | 551.07 | 327.33 | 916.21 | 505.28 | 0.00 | 0.00 | 0.00 |
November | 662.75 | 414.90 | 247.86 | 570.89 | 723.99 | 0.00 | 0.00 | 0.00 |
December | 706.73 | 535.34 | 171.39 | 622.75 | 1006.11 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 739.96 | 382.31 | 357.64 | 762.23 | 542.89 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 582.05 | 118.51 | 171.39 | 570.89 | 170.43 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 923.02 | 623.60 | 463.54 | 1026.67 | 1058.43 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 861.44 | 589.50 | 271.94 | 701.88 | 1058.43 | 0.00 | 0.00 | 0.00 |
February | 923.02 | 623.60 | 299.42 | 784.97 | 871.92 | 0.00 | 0.00 | 0.00 |
March | 803.24 | 422.96 | 380.28 | 716.58 | 652.23 | 0.00 | 0.00 | 0.00 |
April | 723.66 | 338.33 | 385.34 | 735.81 | 501.76 | 0.00 | 0.00 | 0.00 |
May | 599.53 | 162.54 | 436.99 | 651.17 | 296.98 | 0.00 | 0.00 | 0.00 |
June | 582.05 | 118.51 | 463.54 | 714.94 | 202.85 | 0.00 | 0.00 | 0.00 |
July | 616.14 | 155.25 | 460.89 | 794.75 | 170.43 | 0.00 | 0.00 | 0.00 |
August | 694.19 | 248.95 | 445.24 | 912.28 | 204.02 | 0.00 | 0.00 | 0.00 |
September | 841.21 | 443.25 | 397.96 | 1026.67 | 339.50 | 0.00 | 0.00 | 0.00 |
October | 878.40 | 551.07 | 327.33 | 916.21 | 505.28 | 0.00 | 0.00 | 0.00 |
November | 662.75 | 414.89 | 247.86 | 570.89 | 723.99 | 0.00 | 0.00 | 0.00 |
December | 706.73 | 535.34 | 171.39 | 622.75 | 1006.11 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 739.96 | 382.31 | 357.64 | 762.23 | 542.89 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 582.05 | 118.51 | 171.39 | 570.89 | 170.43 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 923.02 | 623.60 | 463.54 | 1026.67 | 1058.43 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 861.41 | 589.48 | 271.93 | 701.85 | 1058.38 | 0.00 | 0.00 | 0.00 |
February | 922.99 | 623.58 | 299.41 | 784.94 | 871.89 | 0.00 | 0.00 | 0.00 |
March | 803.20 | 422.94 | 380.26 | 716.55 | 652.21 | 0.00 | 0.00 | 0.00 |
April | 723.63 | 338.31 | 385.32 | 735.78 | 501.74 | 0.00 | 0.00 | 0.00 |
May | 599.51 | 162.53 | 436.97 | 651.14 | 296.96 | 0.00 | 0.00 | 0.00 |
June | 582.03 | 118.50 | 463.52 | 714.91 | 202.84 | 0.00 | 0.00 | 0.00 |
July | 616.12 | 155.25 | 460.87 | 794.71 | 170.42 | 0.00 | 0.00 | 0.00 |
August | 694.16 | 248.94 | 445.22 | 912.24 | 204.02 | 0.00 | 0.00 | 0.00 |
September | 841.18 | 443.23 | 397.95 | 1026.63 | 339.48 | 0.00 | 0.00 | 0.00 |
October | 878.37 | 551.05 | 327.31 | 916.18 | 505.26 | 0.00 | 0.00 | 0.00 |
November | 662.73 | 414.88 | 247.85 | 570.86 | 723.96 | 0.00 | 0.00 | 0.00 |
December | 706.70 | 535.32 | 171.38 | 622.73 | 1006.07 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 739.93 | 382.30 | 357.63 | 762.20 | 542.87 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 582.03 | 118.50 | 171.38 | 570.86 | 170.42 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 922.99 | 623.58 | 463.52 | 1026.63 | 1058.38 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 327.08 | 132.34 | 194.74 | 121.93 | 1397.14 | 0.00 | 0.00 | 0.00 |
February | 479.60 | 236.33 | 243.27 | 265.97 | 1168.20 | 0.00 | 0.00 | 0.00 |
March | 572.54 | 213.02 | 359.53 | 358.65 | 824.76 | 0.00 | 0.00 | 0.00 |
April | 835.17 | 412.98 | 422.19 | 779.74 | 634.87 | 0.00 | 0.00 | 0.00 |
May | 837.59 | 334.60 | 502.99 | 881.01 | 348.25 | 0.00 | 0.00 | 0.00 |
June | 982.81 | 425.93 | 556.88 | 1175.04 | 255.53 | 0.00 | 0.00 | 0.00 |
July | 1055.24 | 501.25 | 553.98 | 1301.24 | 224.78 | 0.00 | 0.00 | 0.00 |
August | 922.54 | 423.39 | 499.16 | 1136.41 | 266.75 | 0.00 | 0.00 | 0.00 |
September | 746.77 | 354.46 | 392.32 | 837.75 | 405.45 | 0.00 | 0.00 | 0.00 |
October | 520.38 | 231.36 | 289.03 | 422.12 | 640.18 | 0.00 | 0.00 | 0.00 |
November | 311.48 | 115.19 | 196.30 | 152.76 | 962.42 | 0.00 | 0.00 | 0.00 |
December | 239.55 | 112.93 | 126.62 | 103.01 | 1347.14 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 653.26 | 291.20 | 362.05 | 629.76 | 704.04 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 239.55 | 112.93 | 126.62 | 103.01 | 224.78 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1055.24 | 501.25 | 556.88 | 1301.24 | 1397.14 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 327.08 | 132.34 | 194.74 | 121.93 | 1397.14 | 0.00 | 0.00 | 0.00 |
February | 479.60 | 236.33 | 243.27 | 265.97 | 1168.20 | 0.00 | 0.00 | 0.00 |
March | 572.54 | 213.02 | 359.53 | 358.65 | 824.76 | 0.00 | 0.00 | 0.00 |
April | 835.17 | 412.98 | 422.19 | 779.74 | 634.87 | 0.00 | 0.00 | 0.00 |
May | 837.59 | 334.60 | 502.99 | 881.01 | 348.25 | 0.00 | 0.00 | 0.00 |
June | 982.81 | 425.93 | 556.88 | 1175.04 | 255.53 | 0.00 | 0.00 | 0.00 |
July | 1055.24 | 501.25 | 553.98 | 1301.24 | 224.78 | 0.00 | 0.00 | 0.00 |
August | 922.54 | 423.39 | 499.16 | 1136.41 | 266.75 | 0.00 | 0.00 | 0.00 |
September | 746.77 | 354.46 | 392.32 | 837.75 | 405.45 | 0.00 | 0.00 | 0.00 |
October | 520.38 | 231.36 | 289.03 | 422.12 | 640.18 | 0.00 | 0.00 | 0.00 |
November | 311.48 | 115.19 | 196.30 | 152.76 | 962.42 | 0.00 | 0.00 | 0.00 |
December | 239.55 | 112.93 | 126.62 | 103.01 | 1347.14 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 653.26 | 291.20 | 362.05 | 629.76 | 704.04 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 239.55 | 112.93 | 126.62 | 103.01 | 224.78 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1055.24 | 501.25 | 556.88 | 1301.24 | 1397.14 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 327.07 | 132.34 | 194.73 | 121.93 | 1397.11 | 0.00 | 0.00 | 0.00 |
February | 479.59 | 236.33 | 243.26 | 265.96 | 1168.18 | 0.00 | 0.00 | 0.00 |
March | 572.53 | 213.01 | 359.52 | 358.64 | 824.74 | 0.00 | 0.00 | 0.00 |
April | 835.16 | 412.97 | 422.19 | 779.73 | 634.86 | 0.00 | 0.00 | 0.00 |
May | 837.57 | 334.59 | 502.98 | 881.00 | 348.24 | 0.00 | 0.00 | 0.00 |
June | 982.79 | 425.92 | 556.87 | 1175.02 | 255.52 | 0.00 | 0.00 | 0.00 |
July | 1055.22 | 501.25 | 553.97 | 1301.22 | 224.77 | 0.00 | 0.00 | 0.00 |
August | 922.53 | 423.38 | 499.15 | 1136.39 | 266.75 | 0.00 | 0.00 | 0.00 |
September | 746.76 | 354.45 | 392.31 | 837.73 | 405.44 | 0.00 | 0.00 | 0.00 |
October | 520.37 | 231.35 | 289.02 | 422.11 | 640.17 | 0.00 | 0.00 | 0.00 |
November | 311.48 | 115.18 | 196.29 | 152.76 | 962.40 | 0.00 | 0.00 | 0.00 |
December | 239.54 | 112.92 | 126.62 | 103.00 | 1347.12 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 653.24 | 291.20 | 362.05 | 629.74 | 704.03 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 239.54 | 112.92 | 126.62 | 103.00 | 224.77 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1055.22 | 501.25 | 556.87 | 1301.22 | 1397.11 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 692.58 | 0.00 | 692.58 | 0.20 | 6335.07 | 0.00 | 0.00 | 0.00 |
February | 878.06 | 0.00 | 878.06 | 29.77 | 5125.72 | 0.00 | 0.00 | 0.00 |
March | 1315.95 | 0.00 | 1315.95 | 315.41 | 3309.82 | 0.00 | 0.00 | 0.00 |
April | 1519.17 | 7.48 | 1511.68 | 742.06 | 2282.99 | 0.00 | 0.00 | 0.00 |
May | 1981.02 | 74.46 | 1906.56 | 1592.47 | 1293.98 | 0.00 | 0.00 | 0.00 |
June | 2315.36 | 210.15 | 2105.21 | 2505.45 | 899.25 | 0.00 | 0.00 | 0.00 |
July | 2171.45 | 145.25 | 2026.20 | 2473.41 | 769.74 | 0.00 | 0.00 | 0.00 |
August | 1818.14 | 32.22 | 1785.92 | 2063.37 | 906.06 | 0.00 | 0.00 | 0.00 |
September | 1393.99 | 0.35 | 1393.65 | 1216.30 | 1584.85 | 0.00 | 0.00 | 0.00 |
October | 1036.46 | 0.00 | 1036.46 | 397.35 | 2444.49 | 0.00 | 0.00 | 0.00 |
November | 725.01 | 0.00 | 725.01 | 82.35 | 3821.25 | 0.00 | 0.00 | 0.00 |
December | 470.29 | 0.00 | 470.29 | 0.00 | 5570.15 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1362.34 | 39.31 | 1323.03 | 957.06 | 2851.17 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 470.29 | 0.00 | 470.29 | 0.00 | 769.74 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2315.36 | 210.15 | 2105.21 | 2505.45 | 6335.07 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 989.38 | 407.13 | 582.25 | 363.44 | 3810.82 | 0.00 | 0.00 | 0.00 |
February | 1311.42 | 576.66 | 734.76 | 664.42 | 3028.07 | 0.00 | 0.00 | 0.00 |
March | 1781.81 | 707.26 | 1074.56 | 1230.23 | 2017.74 | 0.00 | 0.00 | 0.00 |
April | 2187.90 | 958.15 | 1229.75 | 1952.58 | 1451.94 | 0.00 | 0.00 | 0.00 |
May | 2747.82 | 1200.67 | 1547.15 | 2908.86 | 863.96 | 0.00 | 0.00 | 0.00 |
June | 3023.91 | 1316.86 | 1707.04 | 3627.77 | 598.94 | 0.00 | 0.00 | 0.00 |
July | 3056.39 | 1410.29 | 1646.10 | 3766.60 | 512.15 | 0.00 | 0.00 | 0.00 |
August | 2576.48 | 1110.78 | 1465.70 | 3181.36 | 598.88 | 0.00 | 0.00 | 0.00 |
September | 2297.99 | 1085.92 | 1212.07 | 2592.75 | 1010.62 | 0.00 | 0.00 | 0.00 |
October | 1464.44 | 611.68 | 852.75 | 1187.52 | 1520.52 | 0.00 | 0.00 | 0.00 |
November | 864.03 | 280.65 | 583.38 | 397.10 | 2364.81 | 0.00 | 0.00 | 0.00 |
December | 669.29 | 287.41 | 381.88 | 260.29 | 3432.98 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1917.23 | 830.65 | 1086.58 | 1850.84 | 1761.76 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 669.29 | 280.65 | 381.88 | 260.29 | 512.15 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 3056.39 | 1410.29 | 1707.04 | 3766.60 | 3810.82 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 4307.17 | 2947.49 | 1359.68 | 3496.51 | 5166.06 | 0.00 | 0.00 | 0.00 |
February | 4615.06 | 3117.97 | 1497.09 | 3908.69 | 4220.78 | 0.00 | 0.00 | 0.00 |
March | 4016.13 | 2114.76 | 1901.37 | 3585.88 | 3101.31 | 0.00 | 0.00 | 0.00 |
April | 3618.27 | 1691.61 | 1926.66 | 3676.24 | 2350.51 | 0.00 | 0.00 | 0.00 |
May | 2997.61 | 812.69 | 2184.92 | 3243.10 | 1428.64 | 0.00 | 0.00 | 0.00 |
June | 2910.23 | 592.54 | 2317.69 | 3570.46 | 972.43 | 0.00 | 0.00 | 0.00 |
July | 3080.68 | 776.25 | 2304.43 | 3965.20 | 832.42 | 0.00 | 0.00 | 0.00 |
August | 3470.90 | 1244.75 | 2226.15 | 4547.06 | 993.60 | 0.00 | 0.00 | 0.00 |
September | 4206.00 | 2216.22 | 1989.78 | 5104.54 | 1645.47 | 0.00 | 0.00 | 0.00 |
October | 4391.95 | 2755.33 | 1636.62 | 4570.35 | 2410.79 | 0.00 | 0.00 | 0.00 |
November | 3313.72 | 2074.45 | 1239.27 | 2869.34 | 3438.65 | 0.00 | 0.00 | 0.00 |
December | 3533.60 | 2676.66 | 856.94 | 3128.05 | 4815.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 3699.75 | 1911.55 | 1788.20 | 3804.61 | 2607.06 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 2910.23 | 592.54 | 856.94 | 2869.34 | 832.42 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 4615.06 | 3117.97 | 2317.69 | 5104.54 | 5166.06 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 981.22 | 397.01 | 584.21 | 379.90 | 3944.87 | 0.00 | 0.00 | 0.00 |
February | 1438.79 | 708.99 | 729.80 | 830.39 | 3209.68 | 0.00 | 0.00 | 0.00 |
March | 1717.61 | 639.05 | 1078.57 | 1154.62 | 2138.54 | 0.00 | 0.00 | 0.00 |
April | 2505.49 | 1238.92 | 1266.57 | 2407.59 | 1582.15 | 0.00 | 0.00 | 0.00 |
May | 2512.74 | 1003.78 | 1508.96 | 2680.77 | 951.53 | 0.00 | 0.00 | 0.00 |
June | 2948.40 | 1277.76 | 1670.63 | 3559.70 | 679.04 | 0.00 | 0.00 | 0.00 |
July | 3165.68 | 1503.75 | 1661.93 | 3940.70 | 607.75 | 0.00 | 0.00 | 0.00 |
August | 2767.60 | 1270.15 | 1497.45 | 3464.85 | 691.32 | 0.00 | 0.00 | 0.00 |
September | 2240.30 | 1063.36 | 1176.94 | 2548.70 | 1102.03 | 0.00 | 0.00 | 0.00 |
October | 1561.13 | 694.06 | 867.07 | 1344.06 | 1645.17 | 0.00 | 0.00 | 0.00 |
November | 934.44 | 345.56 | 588.88 | 509.73 | 2472.85 | 0.00 | 0.00 | 0.00 |
December | 718.63 | 338.77 | 379.86 | 340.89 | 3565.74 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1959.75 | 873.60 | 1086.15 | 1935.62 | 1876.29 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 718.63 | 338.77 | 379.86 | 340.89 | 607.75 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 3165.68 | 1503.75 | 1670.63 | 3940.70 | 3944.87 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 692.58 | 0.00 | 692.58 | 0.25 | 6245.92 | 0.00 | 0.00 | 0.00 |
February | 878.06 | 0.00 | 878.06 | 33.37 | 5017.21 | 0.00 | 0.00 | 0.00 |
March | 1315.95 | 0.00 | 1315.95 | 338.60 | 3175.71 | 0.00 | 0.00 | 0.00 |
April | 1519.17 | 7.48 | 1511.68 | 768.55 | 2150.02 | 0.00 | 0.00 | 0.00 |
May | 1981.02 | 74.46 | 1906.56 | 1622.19 | 1232.93 | 0.00 | 0.00 | 0.00 |
June | 2315.36 | 210.15 | 2105.21 | 2508.04 | 866.76 | 0.00 | 0.00 | 0.00 |
July | 2171.45 | 145.25 | 2026.20 | 2465.53 | 755.76 | 0.00 | 0.00 | 0.00 |
August | 1818.14 | 32.22 | 1785.92 | 2063.74 | 882.04 | 0.00 | 0.00 | 0.00 |
September | 1393.99 | 0.35 | 1393.65 | 1244.16 | 1493.92 | 0.00 | 0.00 | 0.00 |
October | 1036.46 | 0.00 | 1036.46 | 453.08 | 2244.22 | 0.00 | 0.00 | 0.00 |
November | 725.01 | 0.00 | 725.01 | 101.08 | 3652.62 | 0.00 | 0.00 | 0.00 |
December | 470.29 | 0.00 | 470.29 | 0.01 | 5449.17 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1362.34 | 39.31 | 1323.03 | 972.15 | 2753.26 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 470.29 | 0.00 | 470.29 | 0.01 | 755.76 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2315.36 | 210.15 | 2105.21 | 2508.04 | 6245.92 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 989.38 | 407.13 | 582.25 | 366.56 | 3760.12 | 0.00 | 0.00 | 0.00 |
February | 1311.42 | 576.66 | 734.76 | 673.83 | 2957.75 | 0.00 | 0.00 | 0.00 |
March | 1781.81 | 707.26 | 1074.56 | 1252.20 | 1937.17 | 0.00 | 0.00 | 0.00 |
April | 2187.90 | 958.15 | 1229.75 | 1966.80 | 1379.63 | 0.00 | 0.00 | 0.00 |
May | 2747.82 | 1200.67 | 1547.15 | 2913.22 | 834.30 | 0.00 | 0.00 | 0.00 |
June | 3023.91 | 1316.86 | 1707.04 | 3620.87 | 583.34 | 0.00 | 0.00 | 0.00 |
July | 3056.39 | 1410.29 | 1646.10 | 3753.64 | 507.72 | 0.00 | 0.00 | 0.00 |
August | 2576.48 | 1110.78 | 1465.70 | 3173.52 | 589.57 | 0.00 | 0.00 | 0.00 |
September | 2297.99 | 1085.92 | 1212.07 | 2601.71 | 966.89 | 0.00 | 0.00 | 0.00 |
October | 1464.44 | 611.68 | 852.75 | 1233.12 | 1407.27 | 0.00 | 0.00 | 0.00 |
November | 864.03 | 280.65 | 583.38 | 417.22 | 2263.58 | 0.00 | 0.00 | 0.00 |
December | 669.29 | 287.41 | 381.88 | 266.04 | 3356.98 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1917.23 | 830.65 | 1086.58 | 1859.65 | 1706.32 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 669.29 | 280.65 | 381.88 | 266.04 | 507.72 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 3056.39 | 1410.29 | 1707.04 | 3753.64 | 3760.12 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 4307.17 | 2947.49 | 1359.68 | 3511.94 | 5072.82 | 0.00 | 0.00 | 0.00 |
February | 4615.06 | 3117.97 | 1497.09 | 3937.40 | 4087.23 | 0.00 | 0.00 | 0.00 |
March | 4016.13 | 2114.76 | 1901.37 | 3614.64 | 2965.66 | 0.00 | 0.00 | 0.00 |
April | 3618.27 | 1691.61 | 1926.66 | 3693.73 | 2221.92 | 0.00 | 0.00 | 0.00 |
May | 2997.61 | 812.69 | 2184.92 | 3254.17 | 1367.38 | 0.00 | 0.00 | 0.00 |
June | 2910.23 | 592.54 | 2317.69 | 3566.21 | 938.99 | 0.00 | 0.00 | 0.00 |
July | 3080.68 | 776.25 | 2304.43 | 3951.23 | 818.51 | 0.00 | 0.00 | 0.00 |
August | 3470.90 | 1244.75 | 2226.15 | 4536.41 | 970.62 | 0.00 | 0.00 | 0.00 |
September | 4206.00 | 2216.22 | 1989.78 | 5116.45 | 1567.35 | 0.00 | 0.00 | 0.00 |
October | 4391.95 | 2755.33 | 1636.62 | 4627.06 | 2230.25 | 0.00 | 0.00 | 0.00 |
November | 3313.72 | 2074.45 | 1239.27 | 2918.61 | 3266.18 | 0.00 | 0.00 | 0.00 |
December | 3533.60 | 2676.66 | 856.94 | 3153.44 | 4674.70 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 3699.75 | 1911.55 | 1788.20 | 3822.50 | 2507.87 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 2910.23 | 592.54 | 856.94 | 2918.61 | 818.51 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 4615.06 | 3117.97 | 2317.69 | 5116.45 | 5072.82 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 981.22 | 397.01 | 584.21 | 379.85 | 3892.34 | 0.00 | 0.00 | 0.00 |
February | 1438.79 | 708.99 | 729.80 | 833.73 | 3138.25 | 0.00 | 0.00 | 0.00 |
March | 1717.61 | 639.05 | 1078.57 | 1163.75 | 2061.42 | 0.00 | 0.00 | 0.00 |
April | 2505.49 | 1238.92 | 1266.57 | 2412.39 | 1506.16 | 0.00 | 0.00 | 0.00 |
May | 2512.74 | 1003.78 | 1508.96 | 2686.29 | 914.81 | 0.00 | 0.00 | 0.00 |
June | 2948.40 | 1277.76 | 1670.63 | 3553.86 | 659.90 | 0.00 | 0.00 | 0.00 |
July | 3165.68 | 1503.75 | 1661.93 | 3929.44 | 598.57 | 0.00 | 0.00 | 0.00 |
August | 2767.60 | 1270.15 | 1497.45 | 3457.76 | 677.36 | 0.00 | 0.00 | 0.00 |
September | 2240.30 | 1063.36 | 1176.94 | 2556.60 | 1054.89 | 0.00 | 0.00 | 0.00 |
October | 1561.13 | 694.06 | 867.07 | 1368.33 | 1539.95 | 0.00 | 0.00 | 0.00 |
November | 934.44 | 345.56 | 588.88 | 523.24 | 2377.11 | 0.00 | 0.00 | 0.00 |
December | 718.63 | 338.77 | 379.86 | 344.00 | 3490.49 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1959.75 | 873.60 | 1086.15 | 1939.56 | 1819.82 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 718.63 | 338.77 | 379.86 | 344.00 | 598.57 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 3165.68 | 1503.75 | 1670.63 | 3929.44 | 3892.34 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.371008E+09 | 0.00 | 0.371008E+09 | 0.00 | 0.354398E+10 |
February | 0.424847E+09 | 0.00 | 0.424847E+09 | 5983512.46 | 0.264666E+10 |
March | 0.704934E+09 | 0.00 | 0.704934E+09 | 0.132222E+09 | 0.196568E+10 |
April | 0.787546E+09 | 3880204.98 | 0.783666E+09 | 0.341006E+09 | 0.135009E+10 |
May | 0.106121E+10 | 39888353.73 | 0.102132E+10 | 0.827717E+09 | 0.744474E+09 |
June | 0.120030E+10 | 0.108943E+09 | 0.109136E+10 | 0.128756E+10 | 0.495223E+09 |
July | 0.116322E+10 | 77806368.86 | 0.108541E+10 | 0.131223E+10 | 0.430656E+09 |
August | 0.973952E+09 | 17261160.59 | 0.956691E+09 | 0.108592E+10 | 0.516245E+09 |
September | 0.722654E+09 | 179185.83 | 0.722474E+09 | 0.606700E+09 | 0.891849E+09 |
October | 0.555217E+09 | 0.00 | 0.555217E+09 | 0.165535E+09 | 0.149220E+10 |
November | 0.375852E+09 | 0.00 | 0.375852E+09 | 27133354.17 | 0.221626E+10 |
December | 0.251926E+09 | 0.00 | 0.251926E+09 | 0.00 | 0.322563E+10 |
Annual Sum or Average | 0.859266E+10 | 0.247958E+09 | 0.834470E+10 | 0.579201E+10 | 0.195189E+11 |
Minimum of Months | 0.251926E+09 | 0.00 | 0.251926E+09 | 0.00 | 0.430656E+09 |
Maximum of Months | 0.120030E+10 | 0.108943E+09 | 0.109136E+10 | 0.131223E+10 | 0.354398E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.371008E+09 | 0.00 | 0.371008E+09 | 0.00 | 0.354398E+10 |
February | 0.424846E+09 | 0.00 | 0.424846E+09 | 5983476.82 | 0.264666E+10 |
March | 0.704933E+09 | 0.00 | 0.704933E+09 | 0.132221E+09 | 0.196568E+10 |
April | 0.787546E+09 | 3880200.32 | 0.783666E+09 | 0.341005E+09 | 0.135009E+10 |
May | 0.106121E+10 | 39888305.87 | 0.102132E+10 | 0.827716E+09 | 0.744474E+09 |
June | 0.120030E+10 | 0.108943E+09 | 0.109136E+10 | 0.128756E+10 | 0.495223E+09 |
July | 0.116321E+10 | 77806275.50 | 0.108541E+10 | 0.131222E+10 | 0.430656E+09 |
August | 0.973952E+09 | 17261139.88 | 0.956691E+09 | 0.108592E+10 | 0.516245E+09 |
September | 0.722653E+09 | 179185.62 | 0.722474E+09 | 0.606700E+09 | 0.891849E+09 |
October | 0.555216E+09 | 0.00 | 0.555216E+09 | 0.165534E+09 | 0.149220E+10 |
November | 0.375851E+09 | 0.00 | 0.375851E+09 | 27133264.31 | 0.221626E+10 |
December | 0.251926E+09 | 0.00 | 0.251926E+09 | 0.00 | 0.322563E+10 |
Annual Sum or Average | 0.859265E+10 | 0.247958E+09 | 0.834469E+10 | 0.579200E+10 | 0.195189E+11 |
Minimum of Months | 0.251926E+09 | 0.00 | 0.251926E+09 | 0.00 | 0.430656E+09 |
Maximum of Months | 0.120030E+10 | 0.108943E+09 | 0.109136E+10 | 0.131222E+10 | 0.354398E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.371008E+09 | 0.00 | 0.371008E+09 | 0.00 | 0.354398E+10 |
February | 0.424847E+09 | 0.00 | 0.424847E+09 | 5983512.46 | 0.264666E+10 |
March | 0.704934E+09 | 0.00 | 0.704934E+09 | 0.132222E+09 | 0.196568E+10 |
April | 0.787546E+09 | 3880204.98 | 0.783666E+09 | 0.341006E+09 | 0.135009E+10 |
May | 0.106121E+10 | 39888353.73 | 0.102132E+10 | 0.827717E+09 | 0.744474E+09 |
June | 0.120030E+10 | 0.108943E+09 | 0.109136E+10 | 0.128756E+10 | 0.495223E+09 |
July | 0.116322E+10 | 77806368.86 | 0.108541E+10 | 0.131223E+10 | 0.430656E+09 |
August | 0.973952E+09 | 17261160.59 | 0.956691E+09 | 0.108592E+10 | 0.516245E+09 |
September | 0.722654E+09 | 179185.83 | 0.722474E+09 | 0.606700E+09 | 0.891849E+09 |
October | 0.555217E+09 | 0.00 | 0.555217E+09 | 0.165535E+09 | 0.149220E+10 |
November | 0.375852E+09 | 0.00 | 0.375852E+09 | 27133354.17 | 0.221626E+10 |
December | 0.251926E+09 | 0.00 | 0.251926E+09 | 0.00 | 0.322563E+10 |
Annual Sum or Average | 0.859266E+10 | 0.247958E+09 | 0.834470E+10 | 0.579201E+10 | 0.195189E+11 |
Minimum of Months | 0.251926E+09 | 0.00 | 0.251926E+09 | 0.00 | 0.430656E+09 |
Maximum of Months | 0.120030E+10 | 0.108943E+09 | 0.109136E+10 | 0.131223E+10 | 0.354398E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.371008E+09 | 0.00 | 0.371008E+09 | 0.00 | 0.354398E+10 |
February | 0.424846E+09 | 0.00 | 0.424846E+09 | 5983476.82 | 0.264666E+10 |
March | 0.704933E+09 | 0.00 | 0.704933E+09 | 0.132221E+09 | 0.196568E+10 |
April | 0.787546E+09 | 3880200.32 | 0.783666E+09 | 0.341005E+09 | 0.135009E+10 |
May | 0.106121E+10 | 39888305.87 | 0.102132E+10 | 0.827716E+09 | 0.744474E+09 |
June | 0.120030E+10 | 0.108943E+09 | 0.109136E+10 | 0.128756E+10 | 0.495223E+09 |
July | 0.116321E+10 | 77806275.50 | 0.108541E+10 | 0.131222E+10 | 0.430656E+09 |
August | 0.973952E+09 | 17261139.88 | 0.956691E+09 | 0.108592E+10 | 0.516245E+09 |
September | 0.722653E+09 | 179185.62 | 0.722474E+09 | 0.606700E+09 | 0.891849E+09 |
October | 0.555216E+09 | 0.00 | 0.555216E+09 | 0.165534E+09 | 0.149220E+10 |
November | 0.375851E+09 | 0.00 | 0.375851E+09 | 27133264.31 | 0.221626E+10 |
December | 0.251926E+09 | 0.00 | 0.251926E+09 | 0.00 | 0.322563E+10 |
Annual Sum or Average | 0.859265E+10 | 0.247958E+09 | 0.834469E+10 | 0.579200E+10 | 0.195189E+11 |
Minimum of Months | 0.251926E+09 | 0.00 | 0.251926E+09 | 0.00 | 0.430656E+09 |
Maximum of Months | 0.120030E+10 | 0.108943E+09 | 0.109136E+10 | 0.131222E+10 | 0.354398E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.370993E+09 | 0.00 | 0.370993E+09 | 0.00 | 0.354383E+10 |
February | 0.424830E+09 | 0.00 | 0.424830E+09 | 5983271.29 | 0.264656E+10 |
March | 0.704906E+09 | 0.00 | 0.704906E+09 | 0.132216E+09 | 0.196560E+10 |
April | 0.787515E+09 | 3880048.59 | 0.783635E+09 | 0.340992E+09 | 0.135004E+10 |
May | 0.106117E+10 | 39886746.06 | 0.102128E+10 | 0.827684E+09 | 0.744444E+09 |
June | 0.120025E+10 | 0.108938E+09 | 0.109131E+10 | 0.128751E+10 | 0.495203E+09 |
July | 0.116317E+10 | 77803232.92 | 0.108537E+10 | 0.131217E+10 | 0.430639E+09 |
August | 0.973913E+09 | 17260464.89 | 0.956653E+09 | 0.108588E+10 | 0.516224E+09 |
September | 0.722625E+09 | 179178.61 | 0.722445E+09 | 0.606676E+09 | 0.891813E+09 |
October | 0.555194E+09 | 0.00 | 0.555194E+09 | 0.165528E+09 | 0.149214E+10 |
November | 0.375836E+09 | 0.00 | 0.375836E+09 | 27132260.58 | 0.221617E+10 |
December | 0.251916E+09 | 0.00 | 0.251916E+09 | 0.00 | 0.322550E+10 |
Annual Sum or Average | 0.859231E+10 | 0.247948E+09 | 0.834436E+10 | 0.579177E+10 | 0.195182E+11 |
Minimum of Months | 0.251916E+09 | 0.00 | 0.251916E+09 | 0.00 | 0.430639E+09 |
Maximum of Months | 0.120025E+10 | 0.108938E+09 | 0.109131E+10 | 0.131217E+10 | 0.354383E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.883326E+09 | 0.363492E+09 | 0.519835E+09 | 0.317532E+09 | 0.353698E+10 |
February | 0.105754E+10 | 0.465020E+09 | 0.592516E+09 | 0.520280E+09 | 0.258558E+10 |
March | 0.159082E+10 | 0.631444E+09 | 0.959376E+09 | 0.106742E+10 | 0.194853E+10 |
April | 0.189036E+10 | 0.827850E+09 | 0.106251E+10 | 0.167312E+10 | 0.136561E+10 |
May | 0.245328E+10 | 0.107197E+10 | 0.138131E+10 | 0.260764E+10 | 0.811509E+09 |
June | 0.261268E+10 | 0.113778E+10 | 0.147490E+10 | 0.314947E+10 | 0.535845E+09 |
July | 0.272878E+10 | 0.125912E+10 | 0.146966E+10 | 0.338708E+10 | 0.453800E+09 |
August | 0.230031E+10 | 0.991713E+09 | 0.130859E+10 | 0.285714E+10 | 0.531322E+09 |
September | 0.198548E+10 | 0.938245E+09 | 0.104724E+10 | 0.224010E+10 | 0.924593E+09 |
October | 0.130746E+10 | 0.546118E+09 | 0.761346E+09 | 0.101765E+10 | 0.149497E+10 |
November | 0.746531E+09 | 0.242487E+09 | 0.504044E+09 | 0.317313E+09 | 0.222964E+10 |
December | 0.597545E+09 | 0.256601E+09 | 0.340945E+09 | 0.218798E+09 | 0.326603E+10 |
Annual Sum or Average | 0.201541E+11 | 0.873185E+10 | 0.114223E+11 | 0.193735E+11 | 0.196844E+11 |
Minimum of Months | 0.597545E+09 | 0.242487E+09 | 0.340945E+09 | 0.218798E+09 | 0.453800E+09 |
Maximum of Months | 0.272878E+10 | 0.125912E+10 | 0.147490E+10 | 0.338708E+10 | 0.353698E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.883326E+09 | 0.363492E+09 | 0.519835E+09 | 0.317532E+09 | 0.353698E+10 |
February | 0.105754E+10 | 0.465020E+09 | 0.592516E+09 | 0.520280E+09 | 0.258558E+10 |
March | 0.159082E+10 | 0.631444E+09 | 0.959376E+09 | 0.106742E+10 | 0.194853E+10 |
April | 0.189036E+10 | 0.827850E+09 | 0.106251E+10 | 0.167312E+10 | 0.136561E+10 |
May | 0.245328E+10 | 0.107197E+10 | 0.138131E+10 | 0.260764E+10 | 0.811509E+09 |
June | 0.261268E+10 | 0.113778E+10 | 0.147490E+10 | 0.314947E+10 | 0.535845E+09 |
July | 0.272878E+10 | 0.125912E+10 | 0.146966E+10 | 0.338708E+10 | 0.453800E+09 |
August | 0.230031E+10 | 0.991713E+09 | 0.130859E+10 | 0.285714E+10 | 0.531322E+09 |
September | 0.198548E+10 | 0.938245E+09 | 0.104724E+10 | 0.224010E+10 | 0.924593E+09 |
October | 0.130746E+10 | 0.546118E+09 | 0.761346E+09 | 0.101765E+10 | 0.149497E+10 |
November | 0.746531E+09 | 0.242487E+09 | 0.504044E+09 | 0.317313E+09 | 0.222964E+10 |
December | 0.597545E+09 | 0.256601E+09 | 0.340945E+09 | 0.218798E+09 | 0.326603E+10 |
Annual Sum or Average | 0.201541E+11 | 0.873185E+10 | 0.114223E+11 | 0.193735E+11 | 0.196844E+11 |
Minimum of Months | 0.597545E+09 | 0.242487E+09 | 0.340945E+09 | 0.218798E+09 | 0.453800E+09 |
Maximum of Months | 0.272878E+10 | 0.125912E+10 | 0.147490E+10 | 0.338708E+10 | 0.353698E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.883310E+09 | 0.363485E+09 | 0.519825E+09 | 0.317527E+09 | 0.353692E+10 |
February | 0.105752E+10 | 0.465012E+09 | 0.592506E+09 | 0.520271E+09 | 0.258553E+10 |
March | 0.159079E+10 | 0.631432E+09 | 0.959358E+09 | 0.106740E+10 | 0.194850E+10 |
April | 0.189033E+10 | 0.827835E+09 | 0.106249E+10 | 0.167309E+10 | 0.136559E+10 |
May | 0.245324E+10 | 0.107195E+10 | 0.138128E+10 | 0.260759E+10 | 0.811494E+09 |
June | 0.261263E+10 | 0.113776E+10 | 0.147487E+10 | 0.314941E+10 | 0.535835E+09 |
July | 0.272873E+10 | 0.125910E+10 | 0.146963E+10 | 0.338702E+10 | 0.453791E+09 |
August | 0.230026E+10 | 0.991695E+09 | 0.130857E+10 | 0.285709E+10 | 0.531313E+09 |
September | 0.198545E+10 | 0.938228E+09 | 0.104722E+10 | 0.224006E+10 | 0.924576E+09 |
October | 0.130744E+10 | 0.546108E+09 | 0.761332E+09 | 0.101763E+10 | 0.149494E+10 |
November | 0.746517E+09 | 0.242483E+09 | 0.504035E+09 | 0.317307E+09 | 0.222960E+10 |
December | 0.597534E+09 | 0.256596E+09 | 0.340939E+09 | 0.218794E+09 | 0.326597E+10 |
Annual Sum or Average | 0.201537E+11 | 0.873169E+10 | 0.114221E+11 | 0.193732E+11 | 0.196840E+11 |
Minimum of Months | 0.597534E+09 | 0.242483E+09 | 0.340939E+09 | 0.218794E+09 | 0.453791E+09 |
Maximum of Months | 0.272873E+10 | 0.125910E+10 | 0.147487E+10 | 0.338702E+10 | 0.353692E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.230729E+10 | 0.157893E+10 | 0.728362E+09 | 0.187992E+10 | 0.283489E+10 |
February | 0.223298E+10 | 0.150862E+10 | 0.724360E+09 | 0.189901E+10 | 0.210936E+10 |
March | 0.215139E+10 | 0.113285E+10 | 0.101854E+10 | 0.191929E+10 | 0.174694E+10 |
April | 0.187573E+10 | 0.876943E+09 | 0.998791E+09 | 0.190723E+10 | 0.130057E+10 |
May | 0.160578E+10 | 0.435349E+09 | 0.117043E+10 | 0.174408E+10 | 0.795421E+09 |
June | 0.150868E+10 | 0.307176E+09 | 0.120150E+10 | 0.185312E+10 | 0.525791E+09 |
July | 0.165028E+10 | 0.415827E+09 | 0.123445E+10 | 0.212865E+10 | 0.456482E+09 |
August | 0.185932E+10 | 0.666796E+09 | 0.119252E+10 | 0.244345E+10 | 0.546456E+09 |
September | 0.218042E+10 | 0.114890E+10 | 0.103152E+10 | 0.266112E+10 | 0.879977E+09 |
October | 0.235271E+10 | 0.147599E+10 | 0.876715E+09 | 0.245398E+10 | 0.135334E+10 |
November | 0.171785E+10 | 0.107541E+10 | 0.642445E+09 | 0.147974E+10 | 0.187658E+10 |
December | 0.189290E+10 | 0.143385E+10 | 0.459052E+09 | 0.166798E+10 | 0.269476E+10 |
Annual Sum or Average | 0.233353E+11 | 0.120566E+11 | 0.112787E+11 | 0.240376E+11 | 0.171206E+11 |
Minimum of Months | 0.150868E+10 | 0.307176E+09 | 0.459052E+09 | 0.147974E+10 | 0.456482E+09 |
Maximum of Months | 0.235271E+10 | 0.157893E+10 | 0.123445E+10 | 0.266112E+10 | 0.283489E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.230729E+10 | 0.157893E+10 | 0.728362E+09 | 0.187991E+10 | 0.283489E+10 |
February | 0.223297E+10 | 0.150861E+10 | 0.724359E+09 | 0.189901E+10 | 0.210936E+10 |
March | 0.215139E+10 | 0.113285E+10 | 0.101854E+10 | 0.191929E+10 | 0.174694E+10 |
April | 0.187573E+10 | 0.876941E+09 | 0.998790E+09 | 0.190723E+10 | 0.130057E+10 |
May | 0.160578E+10 | 0.435349E+09 | 0.117043E+10 | 0.174408E+10 | 0.795421E+09 |
June | 0.150868E+10 | 0.307175E+09 | 0.120150E+10 | 0.185312E+10 | 0.525791E+09 |
July | 0.165028E+10 | 0.415826E+09 | 0.123445E+10 | 0.212865E+10 | 0.456482E+09 |
August | 0.185931E+10 | 0.666795E+09 | 0.119252E+10 | 0.244345E+10 | 0.546456E+09 |
September | 0.218042E+10 | 0.114890E+10 | 0.103152E+10 | 0.266112E+10 | 0.879976E+09 |
October | 0.235271E+10 | 0.147599E+10 | 0.876714E+09 | 0.245398E+10 | 0.135334E+10 |
November | 0.171785E+10 | 0.107541E+10 | 0.642444E+09 | 0.147973E+10 | 0.187658E+10 |
December | 0.189290E+10 | 0.143385E+10 | 0.459051E+09 | 0.166797E+10 | 0.269476E+10 |
Annual Sum or Average | 0.233353E+11 | 0.120566E+11 | 0.112787E+11 | 0.240375E+11 | 0.171206E+11 |
Minimum of Months | 0.150868E+10 | 0.307175E+09 | 0.459051E+09 | 0.147973E+10 | 0.456482E+09 |
Maximum of Months | 0.235271E+10 | 0.157893E+10 | 0.123445E+10 | 0.266112E+10 | 0.283489E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.230729E+10 | 0.157893E+10 | 0.728362E+09 | 0.187992E+10 | 0.283489E+10 |
February | 0.223298E+10 | 0.150862E+10 | 0.724360E+09 | 0.189901E+10 | 0.210936E+10 |
March | 0.215139E+10 | 0.113285E+10 | 0.101854E+10 | 0.191929E+10 | 0.174694E+10 |
April | 0.187573E+10 | 0.876943E+09 | 0.998791E+09 | 0.190723E+10 | 0.130057E+10 |
May | 0.160578E+10 | 0.435349E+09 | 0.117043E+10 | 0.174408E+10 | 0.795421E+09 |
June | 0.150868E+10 | 0.307176E+09 | 0.120150E+10 | 0.185312E+10 | 0.525791E+09 |
July | 0.165028E+10 | 0.415827E+09 | 0.123445E+10 | 0.212865E+10 | 0.456482E+09 |
August | 0.185932E+10 | 0.666796E+09 | 0.119252E+10 | 0.244345E+10 | 0.546456E+09 |
September | 0.218042E+10 | 0.114890E+10 | 0.103152E+10 | 0.266112E+10 | 0.879977E+09 |
October | 0.235271E+10 | 0.147599E+10 | 0.876715E+09 | 0.245398E+10 | 0.135334E+10 |
November | 0.171785E+10 | 0.107541E+10 | 0.642445E+09 | 0.147974E+10 | 0.187658E+10 |
December | 0.189290E+10 | 0.143385E+10 | 0.459052E+09 | 0.166798E+10 | 0.269476E+10 |
Annual Sum or Average | 0.233353E+11 | 0.120566E+11 | 0.112787E+11 | 0.240376E+11 | 0.171206E+11 |
Minimum of Months | 0.150868E+10 | 0.307176E+09 | 0.459052E+09 | 0.147974E+10 | 0.456482E+09 |
Maximum of Months | 0.235271E+10 | 0.157893E+10 | 0.123445E+10 | 0.266112E+10 | 0.283489E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.230729E+10 | 0.157893E+10 | 0.728362E+09 | 0.187991E+10 | 0.283489E+10 |
February | 0.223297E+10 | 0.150861E+10 | 0.724359E+09 | 0.189901E+10 | 0.210936E+10 |
March | 0.215139E+10 | 0.113285E+10 | 0.101854E+10 | 0.191929E+10 | 0.174694E+10 |
April | 0.187573E+10 | 0.876941E+09 | 0.998790E+09 | 0.190723E+10 | 0.130057E+10 |
May | 0.160578E+10 | 0.435349E+09 | 0.117043E+10 | 0.174408E+10 | 0.795421E+09 |
June | 0.150868E+10 | 0.307175E+09 | 0.120150E+10 | 0.185312E+10 | 0.525791E+09 |
July | 0.165028E+10 | 0.415826E+09 | 0.123445E+10 | 0.212865E+10 | 0.456482E+09 |
August | 0.185931E+10 | 0.666795E+09 | 0.119252E+10 | 0.244345E+10 | 0.546456E+09 |
September | 0.218042E+10 | 0.114890E+10 | 0.103152E+10 | 0.266112E+10 | 0.879976E+09 |
October | 0.235271E+10 | 0.147599E+10 | 0.876714E+09 | 0.245398E+10 | 0.135334E+10 |
November | 0.171785E+10 | 0.107541E+10 | 0.642444E+09 | 0.147973E+10 | 0.187658E+10 |
December | 0.189290E+10 | 0.143385E+10 | 0.459051E+09 | 0.166797E+10 | 0.269476E+10 |
Annual Sum or Average | 0.233353E+11 | 0.120566E+11 | 0.112787E+11 | 0.240375E+11 | 0.171206E+11 |
Minimum of Months | 0.150868E+10 | 0.307175E+09 | 0.459051E+09 | 0.147973E+10 | 0.456482E+09 |
Maximum of Months | 0.235271E+10 | 0.157893E+10 | 0.123445E+10 | 0.266112E+10 | 0.283489E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.230720E+10 | 0.157887E+10 | 0.728333E+09 | 0.187984E+10 | 0.283478E+10 |
February | 0.223289E+10 | 0.150856E+10 | 0.724330E+09 | 0.189893E+10 | 0.210928E+10 |
March | 0.215130E+10 | 0.113280E+10 | 0.101850E+10 | 0.191922E+10 | 0.174687E+10 |
April | 0.187566E+10 | 0.876907E+09 | 0.998751E+09 | 0.190715E+10 | 0.130051E+10 |
May | 0.160572E+10 | 0.435331E+09 | 0.117038E+10 | 0.174401E+10 | 0.795389E+09 |
June | 0.150862E+10 | 0.307163E+09 | 0.120146E+10 | 0.185305E+10 | 0.525769E+09 |
July | 0.165021E+10 | 0.415810E+09 | 0.123440E+10 | 0.212856E+10 | 0.456464E+09 |
August | 0.185924E+10 | 0.666769E+09 | 0.119247E+10 | 0.244335E+10 | 0.546434E+09 |
September | 0.218033E+10 | 0.114886E+10 | 0.103148E+10 | 0.266102E+10 | 0.879941E+09 |
October | 0.235261E+10 | 0.147594E+10 | 0.876680E+09 | 0.245389E+10 | 0.135329E+10 |
November | 0.171778E+10 | 0.107537E+10 | 0.642419E+09 | 0.147968E+10 | 0.187650E+10 |
December | 0.189283E+10 | 0.143379E+10 | 0.459033E+09 | 0.166791E+10 | 0.269465E+10 |
Annual Sum or Average | 0.233344E+11 | 0.120562E+11 | 0.112782E+11 | 0.240366E+11 | 0.171199E+11 |
Minimum of Months | 0.150862E+10 | 0.307163E+09 | 0.459033E+09 | 0.147968E+10 | 0.456464E+09 |
Maximum of Months | 0.235261E+10 | 0.157887E+10 | 0.123440E+10 | 0.266102E+10 | 0.283478E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.876043E+09 | 0.354458E+09 | 0.521585E+09 | 0.326572E+09 | 0.374210E+10 |
February | 0.116025E+10 | 0.571736E+09 | 0.588513E+09 | 0.643429E+09 | 0.282610E+10 |
March | 0.153350E+10 | 0.570547E+09 | 0.962955E+09 | 0.960599E+09 | 0.220903E+10 |
April | 0.216476E+10 | 0.107044E+10 | 0.109433E+10 | 0.202109E+10 | 0.164557E+10 |
May | 0.224339E+10 | 0.896183E+09 | 0.134721E+10 | 0.235971E+10 | 0.932755E+09 |
June | 0.254744E+10 | 0.110400E+10 | 0.144344E+10 | 0.304571E+10 | 0.662322E+09 |
July | 0.282635E+10 | 0.134256E+10 | 0.148379E+10 | 0.348524E+10 | 0.602043E+09 |
August | 0.247094E+10 | 0.113400E+10 | 0.133694E+10 | 0.304376E+10 | 0.714476E+09 |
September | 0.193564E+10 | 0.918753E+09 | 0.101688E+10 | 0.217144E+10 | 0.105092E+10 |
October | 0.139379E+10 | 0.619664E+09 | 0.774128E+09 | 0.113060E+10 | 0.171467E+10 |
November | 0.807364E+09 | 0.298563E+09 | 0.508802E+09 | 0.395957E+09 | 0.249459E+10 |
December | 0.641602E+09 | 0.302460E+09 | 0.339141E+09 | 0.275890E+09 | 0.360818E+10 |
Annual Sum or Average | 0.206011E+11 | 0.918336E+10 | 0.114177E+11 | 0.198600E+11 | 0.222028E+11 |
Minimum of Months | 0.641602E+09 | 0.298563E+09 | 0.339141E+09 | 0.275890E+09 | 0.602043E+09 |
Maximum of Months | 0.282635E+10 | 0.134256E+10 | 0.148379E+10 | 0.348524E+10 | 0.374210E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.876043E+09 | 0.354458E+09 | 0.521585E+09 | 0.326572E+09 | 0.374210E+10 |
February | 0.116025E+10 | 0.571736E+09 | 0.588513E+09 | 0.643429E+09 | 0.282610E+10 |
March | 0.153350E+10 | 0.570547E+09 | 0.962955E+09 | 0.960599E+09 | 0.220903E+10 |
April | 0.216476E+10 | 0.107044E+10 | 0.109433E+10 | 0.202109E+10 | 0.164557E+10 |
May | 0.224339E+10 | 0.896183E+09 | 0.134721E+10 | 0.235971E+10 | 0.932755E+09 |
June | 0.254744E+10 | 0.110400E+10 | 0.144344E+10 | 0.304571E+10 | 0.662322E+09 |
July | 0.282635E+10 | 0.134256E+10 | 0.148379E+10 | 0.348524E+10 | 0.602043E+09 |
August | 0.247094E+10 | 0.113400E+10 | 0.133694E+10 | 0.304376E+10 | 0.714476E+09 |
September | 0.193564E+10 | 0.918753E+09 | 0.101688E+10 | 0.217144E+10 | 0.105092E+10 |
October | 0.139379E+10 | 0.619664E+09 | 0.774128E+09 | 0.113060E+10 | 0.171467E+10 |
November | 0.807364E+09 | 0.298563E+09 | 0.508802E+09 | 0.395957E+09 | 0.249459E+10 |
December | 0.641602E+09 | 0.302460E+09 | 0.339141E+09 | 0.275890E+09 | 0.360818E+10 |
Annual Sum or Average | 0.206011E+11 | 0.918336E+10 | 0.114177E+11 | 0.198600E+11 | 0.222028E+11 |
Minimum of Months | 0.641602E+09 | 0.298563E+09 | 0.339141E+09 | 0.275890E+09 | 0.602043E+09 |
Maximum of Months | 0.282635E+10 | 0.134256E+10 | 0.148379E+10 | 0.348524E+10 | 0.374210E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.876027E+09 | 0.354451E+09 | 0.521576E+09 | 0.326566E+09 | 0.374203E+10 |
February | 0.116023E+10 | 0.571726E+09 | 0.588503E+09 | 0.643417E+09 | 0.282605E+10 |
March | 0.153347E+10 | 0.570536E+09 | 0.962937E+09 | 0.960581E+09 | 0.220899E+10 |
April | 0.216472E+10 | 0.107042E+10 | 0.109431E+10 | 0.202105E+10 | 0.164554E+10 |
May | 0.224335E+10 | 0.896166E+09 | 0.134719E+10 | 0.235967E+10 | 0.932738E+09 |
June | 0.254739E+10 | 0.110398E+10 | 0.144342E+10 | 0.304565E+10 | 0.662310E+09 |
July | 0.282630E+10 | 0.134254E+10 | 0.148376E+10 | 0.348518E+10 | 0.602032E+09 |
August | 0.247090E+10 | 0.113398E+10 | 0.133692E+10 | 0.304370E+10 | 0.714463E+09 |
September | 0.193560E+10 | 0.918736E+09 | 0.101687E+10 | 0.217141E+10 | 0.105090E+10 |
October | 0.139377E+10 | 0.619653E+09 | 0.774114E+09 | 0.113057E+10 | 0.171464E+10 |
November | 0.807350E+09 | 0.298557E+09 | 0.508792E+09 | 0.395950E+09 | 0.249454E+10 |
December | 0.641590E+09 | 0.302455E+09 | 0.339135E+09 | 0.275885E+09 | 0.360812E+10 |
Annual Sum or Average | 0.206007E+11 | 0.918319E+10 | 0.114175E+11 | 0.198596E+11 | 0.222024E+11 |
Minimum of Months | 0.641590E+09 | 0.298557E+09 | 0.339135E+09 | 0.275885E+09 | 0.602032E+09 |
Maximum of Months | 0.282630E+10 | 0.134254E+10 | 0.148376E+10 | 0.348518E+10 | 0.374203E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.185502E+10 | 0.00 | 0.185502E+10 | 533378.66 | 0.169678E+11 |
February | 0.212421E+10 | 0.00 | 0.212421E+10 | 72010807.17 | 0.124001E+11 |
March | 0.352463E+10 | 0.00 | 0.352463E+10 | 0.844786E+09 | 0.886502E+10 |
April | 0.393768E+10 | 19400790.29 | 0.391828E+10 | 0.192343E+10 | 0.591750E+10 |
May | 0.530598E+10 | 0.199439E+09 | 0.510654E+10 | 0.426528E+10 | 0.346580E+10 |
June | 0.600142E+10 | 0.544707E+09 | 0.545672E+10 | 0.649412E+10 | 0.233084E+10 |
July | 0.581601E+10 | 0.389027E+09 | 0.542698E+10 | 0.662478E+10 | 0.206168E+10 |
August | 0.486970E+10 | 86304759.35 | 0.478340E+10 | 0.552653E+10 | 0.242680E+10 |
September | 0.361322E+10 | 895918.34 | 0.361233E+10 | 0.315264E+10 | 0.410794E+10 |
October | 0.277605E+10 | 0.00 | 0.277605E+10 | 0.106427E+10 | 0.654731E+10 |
November | 0.187923E+10 | 0.00 | 0.187923E+10 | 0.213446E+09 | 0.990467E+10 |
December | 0.125962E+10 | 0.00 | 0.125962E+10 | 0.00 | 0.149191E+11 |
Annual Sum or Average | 0.429628E+11 | 0.123978E+10 | 0.417230E+11 | 0.301818E+11 | 0.899146E+11 |
Minimum of Months | 0.125962E+10 | 0.00 | 0.125962E+10 | 0.00 | 0.206168E+10 |
Maximum of Months | 0.600142E+10 | 0.544707E+09 | 0.545672E+10 | 0.662478E+10 | 0.169678E+11 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.264995E+10 | 0.109046E+10 | 0.155949E+10 | 0.973426E+09 | 0.102069E+11 |
February | 0.317258E+10 | 0.139505E+10 | 0.177753E+10 | 0.160738E+10 | 0.732552E+10 |
March | 0.477241E+10 | 0.189431E+10 | 0.287810E+10 | 0.329504E+10 | 0.540431E+10 |
April | 0.567103E+10 | 0.248353E+10 | 0.318750E+10 | 0.506108E+10 | 0.376342E+10 |
May | 0.735977E+10 | 0.321589E+10 | 0.414388E+10 | 0.779108E+10 | 0.231402E+10 |
June | 0.783796E+10 | 0.341331E+10 | 0.442465E+10 | 0.940318E+10 | 0.155245E+10 |
July | 0.818625E+10 | 0.377732E+10 | 0.440893E+10 | 0.100885E+11 | 0.137175E+10 |
August | 0.690085E+10 | 0.297511E+10 | 0.392574E+10 | 0.852096E+10 | 0.160403E+10 |
September | 0.595639E+10 | 0.281471E+10 | 0.314169E+10 | 0.672042E+10 | 0.261954E+10 |
October | 0.392235E+10 | 0.163834E+10 | 0.228401E+10 | 0.318065E+10 | 0.407257E+10 |
November | 0.223957E+10 | 0.727454E+09 | 0.151212E+10 | 0.102929E+10 | 0.612959E+10 |
December | 0.179262E+10 | 0.769794E+09 | 0.102282E+10 | 0.697173E+09 | 0.919490E+10 |
Annual Sum or Average | 0.604617E+11 | 0.261953E+11 | 0.342665E+11 | 0.583681E+11 | 0.555590E+11 |
Minimum of Months | 0.179262E+10 | 0.727454E+09 | 0.102282E+10 | 0.697173E+09 | 0.137175E+10 |
Maximum of Months | 0.818625E+10 | 0.377732E+10 | 0.442465E+10 | 0.100885E+11 | 0.102069E+11 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.115363E+11 | 0.789456E+10 | 0.364177E+10 | 0.936504E+10 | 0.138368E+11 |
February | 0.111647E+11 | 0.754299E+10 | 0.362175E+10 | 0.945589E+10 | 0.102109E+11 |
March | 0.107568E+11 | 0.566418E+10 | 0.509263E+10 | 0.960441E+10 | 0.830654E+10 |
April | 0.937855E+10 | 0.438466E+10 | 0.499390E+10 | 0.952880E+10 | 0.609253E+10 |
May | 0.802881E+10 | 0.217672E+10 | 0.585209E+10 | 0.868633E+10 | 0.382646E+10 |
June | 0.754331E+10 | 0.153586E+10 | 0.600745E+10 | 0.925463E+10 | 0.252055E+10 |
July | 0.825130E+10 | 0.207911E+10 | 0.617219E+10 | 0.106204E+11 | 0.222956E+10 |
August | 0.929647E+10 | 0.333394E+10 | 0.596253E+10 | 0.121789E+11 | 0.266127E+10 |
September | 0.109020E+11 | 0.574444E+10 | 0.515752E+10 | 0.132310E+11 | 0.426505E+10 |
October | 0.117634E+11 | 0.737988E+10 | 0.438352E+10 | 0.122412E+11 | 0.645706E+10 |
November | 0.858916E+10 | 0.537698E+10 | 0.321218E+10 | 0.743734E+10 | 0.891297E+10 |
December | 0.946440E+10 | 0.716917E+10 | 0.229523E+10 | 0.837817E+10 | 0.128965E+11 |
Annual Sum or Average | 0.116675E+12 | 0.602825E+11 | 0.563928E+11 | 0.119982E+12 | 0.822162E+11 |
Minimum of Months | 0.754331E+10 | 0.153586E+10 | 0.229523E+10 | 0.743734E+10 | 0.222956E+10 |
Maximum of Months | 0.117634E+11 | 0.789456E+10 | 0.617219E+10 | 0.132310E+11 | 0.138368E+11 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.262810E+10 | 0.106336E+10 | 0.156474E+10 | 0.101753E+10 | 0.105659E+11 |
February | 0.348071E+10 | 0.171519E+10 | 0.176552E+10 | 0.200888E+10 | 0.776486E+10 |
March | 0.460046E+10 | 0.171162E+10 | 0.288883E+10 | 0.309252E+10 | 0.572786E+10 |
April | 0.649422E+10 | 0.321128E+10 | 0.328294E+10 | 0.624048E+10 | 0.410094E+10 |
May | 0.673011E+10 | 0.268852E+10 | 0.404159E+10 | 0.718018E+10 | 0.254858E+10 |
June | 0.764225E+10 | 0.331196E+10 | 0.433028E+10 | 0.922675E+10 | 0.176007E+10 |
July | 0.847896E+10 | 0.402764E+10 | 0.445132E+10 | 0.105548E+11 | 0.162779E+10 |
August | 0.741275E+10 | 0.340197E+10 | 0.401078E+10 | 0.928025E+10 | 0.185164E+10 |
September | 0.580685E+10 | 0.275623E+10 | 0.305062E+10 | 0.660624E+10 | 0.285646E+10 |
October | 0.418133E+10 | 0.185897E+10 | 0.232236E+10 | 0.359993E+10 | 0.440643E+10 |
November | 0.242207E+10 | 0.895679E+09 | 0.152639E+10 | 0.132122E+10 | 0.640964E+10 |
December | 0.192479E+10 | 0.907372E+09 | 0.101741E+10 | 0.913031E+09 | 0.955047E+10 |
Annual Sum or Average | 0.618026E+11 | 0.275498E+11 | 0.342528E+11 | 0.610418E+11 | 0.591707E+11 |
Minimum of Months | 0.192479E+10 | 0.895679E+09 | 0.101741E+10 | 0.913031E+09 | 0.162779E+10 |
Maximum of Months | 0.847896E+10 | 0.402764E+10 | 0.445132E+10 | 0.105548E+11 | 0.105659E+11 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.185502E+10 | 0.00 | 0.185502E+10 | 676757.84 | 0.167291E+11 |
February | 0.212421E+10 | 0.00 | 0.212421E+10 | 80725830.91 | 0.121376E+11 |
March | 0.352463E+10 | 0.00 | 0.352463E+10 | 0.906914E+09 | 0.850581E+10 |
April | 0.393768E+10 | 19400790.29 | 0.391828E+10 | 0.199209E+10 | 0.557285E+10 |
May | 0.530598E+10 | 0.199439E+09 | 0.510654E+10 | 0.434486E+10 | 0.330227E+10 |
June | 0.600142E+10 | 0.544707E+09 | 0.545672E+10 | 0.650083E+10 | 0.224663E+10 |
July | 0.581601E+10 | 0.389027E+09 | 0.542698E+10 | 0.660367E+10 | 0.202423E+10 |
August | 0.486970E+10 | 86304759.35 | 0.478340E+10 | 0.552753E+10 | 0.236246E+10 |
September | 0.361322E+10 | 895918.34 | 0.361233E+10 | 0.322485E+10 | 0.387224E+10 |
October | 0.277605E+10 | 0.00 | 0.277605E+10 | 0.121353E+10 | 0.601093E+10 |
November | 0.187923E+10 | 0.00 | 0.187923E+10 | 0.261989E+09 | 0.946759E+10 |
December | 0.125962E+10 | 0.00 | 0.125962E+10 | 22842.20 | 0.145951E+11 |
Annual Sum or Average | 0.429628E+11 | 0.123978E+10 | 0.417230E+11 | 0.306577E+11 | 0.868268E+11 |
Minimum of Months | 0.125962E+10 | 0.00 | 0.125962E+10 | 22842.20 | 0.202423E+10 |
Maximum of Months | 0.600142E+10 | 0.544707E+09 | 0.545672E+10 | 0.660367E+10 | 0.167291E+11 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.264995E+10 | 0.109046E+10 | 0.155949E+10 | 0.981799E+09 | 0.100711E+11 |
February | 0.317258E+10 | 0.139505E+10 | 0.177753E+10 | 0.163014E+10 | 0.715539E+10 |
March | 0.477241E+10 | 0.189431E+10 | 0.287810E+10 | 0.335390E+10 | 0.518851E+10 |
April | 0.567103E+10 | 0.248353E+10 | 0.318750E+10 | 0.509794E+10 | 0.357599E+10 |
May | 0.735977E+10 | 0.321589E+10 | 0.414388E+10 | 0.780276E+10 | 0.223459E+10 |
June | 0.783796E+10 | 0.341331E+10 | 0.442465E+10 | 0.938530E+10 | 0.151202E+10 |
July | 0.818625E+10 | 0.377732E+10 | 0.440893E+10 | 0.100537E+11 | 0.135987E+10 |
August | 0.690085E+10 | 0.297511E+10 | 0.392574E+10 | 0.849994E+10 | 0.157911E+10 |
September | 0.595639E+10 | 0.281471E+10 | 0.314169E+10 | 0.674363E+10 | 0.250618E+10 |
October | 0.392235E+10 | 0.163834E+10 | 0.228401E+10 | 0.330279E+10 | 0.376923E+10 |
November | 0.223957E+10 | 0.727454E+09 | 0.151212E+10 | 0.108144E+10 | 0.586719E+10 |
December | 0.179262E+10 | 0.769794E+09 | 0.102282E+10 | 0.712558E+09 | 0.899134E+10 |
Annual Sum or Average | 0.604617E+11 | 0.261953E+11 | 0.342665E+11 | 0.586459E+11 | 0.538105E+11 |
Minimum of Months | 0.179262E+10 | 0.727454E+09 | 0.102282E+10 | 0.712558E+09 | 0.135987E+10 |
Maximum of Months | 0.818625E+10 | 0.377732E+10 | 0.442465E+10 | 0.100537E+11 | 0.100711E+11 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.115363E+11 | 0.789456E+10 | 0.364177E+10 | 0.940639E+10 | 0.135870E+11 |
February | 0.111647E+11 | 0.754299E+10 | 0.362175E+10 | 0.952537E+10 | 0.988782E+10 |
March | 0.107568E+11 | 0.566418E+10 | 0.509263E+10 | 0.968146E+10 | 0.794322E+10 |
April | 0.937855E+10 | 0.438466E+10 | 0.499390E+10 | 0.957414E+10 | 0.575922E+10 |
May | 0.802881E+10 | 0.217672E+10 | 0.585209E+10 | 0.871596E+10 | 0.366238E+10 |
June | 0.754331E+10 | 0.153586E+10 | 0.600745E+10 | 0.924363E+10 | 0.243386E+10 |
July | 0.825130E+10 | 0.207911E+10 | 0.617219E+10 | 0.105830E+11 | 0.219231E+10 |
August | 0.929647E+10 | 0.333394E+10 | 0.596253E+10 | 0.121503E+11 | 0.259971E+10 |
September | 0.109020E+11 | 0.574444E+10 | 0.515752E+10 | 0.132619E+11 | 0.406257E+10 |
October | 0.117634E+11 | 0.737988E+10 | 0.438352E+10 | 0.123931E+11 | 0.597351E+10 |
November | 0.858916E+10 | 0.537698E+10 | 0.321218E+10 | 0.756503E+10 | 0.846593E+10 |
December | 0.946440E+10 | 0.716917E+10 | 0.229523E+10 | 0.844618E+10 | 0.125207E+11 |
Annual Sum or Average | 0.116675E+12 | 0.602825E+11 | 0.563928E+11 | 0.120546E+12 | 0.790883E+11 |
Minimum of Months | 0.754331E+10 | 0.153586E+10 | 0.229523E+10 | 0.756503E+10 | 0.219231E+10 |
Maximum of Months | 0.117634E+11 | 0.789456E+10 | 0.617219E+10 | 0.132619E+11 | 0.135870E+11 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.262810E+10 | 0.106336E+10 | 0.156474E+10 | 0.101739E+10 | 0.104252E+11 |
February | 0.348071E+10 | 0.171519E+10 | 0.176552E+10 | 0.201695E+10 | 0.759205E+10 |
March | 0.460046E+10 | 0.171162E+10 | 0.288883E+10 | 0.311699E+10 | 0.552130E+10 |
April | 0.649422E+10 | 0.321128E+10 | 0.328294E+10 | 0.625293E+10 | 0.390397E+10 |
May | 0.673011E+10 | 0.268852E+10 | 0.404159E+10 | 0.719497E+10 | 0.245022E+10 |
June | 0.764225E+10 | 0.331196E+10 | 0.433028E+10 | 0.921160E+10 | 0.171046E+10 |
July | 0.847896E+10 | 0.402764E+10 | 0.445132E+10 | 0.105246E+11 | 0.160320E+10 |
August | 0.741275E+10 | 0.340197E+10 | 0.401078E+10 | 0.926126E+10 | 0.181424E+10 |
September | 0.580685E+10 | 0.275623E+10 | 0.305062E+10 | 0.662670E+10 | 0.273428E+10 |
October | 0.418133E+10 | 0.185897E+10 | 0.232236E+10 | 0.366493E+10 | 0.412459E+10 |
November | 0.242207E+10 | 0.895679E+09 | 0.152639E+10 | 0.135623E+10 | 0.616148E+10 |
December | 0.192479E+10 | 0.907372E+09 | 0.101741E+10 | 0.921379E+09 | 0.934893E+10 |
Annual Sum or Average | 0.618026E+11 | 0.275498E+11 | 0.342528E+11 | 0.611659E+11 | 0.573900E+11 |
Minimum of Months | 0.192479E+10 | 0.895679E+09 | 0.101741E+10 | 0.921379E+09 | 0.160320E+10 |
Maximum of Months | 0.847896E+10 | 0.402764E+10 | 0.445132E+10 | 0.105246E+11 | 0.104252E+11 |
Report: WindowZoneSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 6615.79 | 692.59 | 0.00 | 692.59 | 0.00 | 0.00 |
February | 12.37 | 5470.07 | 878.07 | 0.00 | 878.07 | 0.00 | 0.00 |
March | 246.83 | 3669.47 | 1315.95 | 0.00 | 1315.95 | 0.00 | 0.00 |
April | 657.80 | 2604.32 | 1519.17 | 7.48 | 1511.69 | 0.00 | 0.00 |
May | 1545.16 | 1389.76 | 1981.03 | 74.46 | 1906.57 | 0.00 | 0.00 |
June | 2483.71 | 955.28 | 2315.37 | 210.15 | 2105.22 | 0.00 | 0.00 |
July | 2449.62 | 803.94 | 2171.46 | 145.25 | 2026.21 | 0.00 | 0.00 |
August | 2027.17 | 963.71 | 1818.15 | 32.22 | 1785.92 | 0.00 | 0.00 |
September | 1170.32 | 1720.37 | 1394.00 | 0.35 | 1393.65 | 0.00 | 0.00 |
October | 309.01 | 2785.60 | 1036.46 | 0.00 | 1036.46 | 0.00 | 0.00 |
November | 52.34 | 4275.16 | 725.02 | 0.00 | 725.02 | 0.00 | 0.00 |
December | 0.00 | 6021.52 | 470.29 | 0.00 | 470.29 | 0.00 | 0.00 |
Annual Sum or Average | 918.31 | 3094.68 | 1362.35 | 39.31 | 1323.03 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 803.94 | 470.29 | 0.00 | 470.29 | 0.00 | 0.00 |
Maximum of Months | 2483.71 | 6615.79 | 2315.37 | 210.15 | 2105.22 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 355.66 | 3961.65 | 989.38 | 407.13 | 582.25 | 0.00 | 0.00 |
February | 645.18 | 3206.30 | 1311.42 | 576.66 | 734.76 | 0.00 | 0.00 |
March | 1195.58 | 2182.48 | 1781.82 | 707.26 | 1074.56 | 0.00 | 0.00 |
April | 1936.47 | 1580.56 | 2187.91 | 958.15 | 1229.75 | 0.00 | 0.00 |
May | 2920.73 | 908.94 | 2747.84 | 1200.68 | 1547.16 | 0.00 | 0.00 |
June | 3645.19 | 620.19 | 3023.92 | 1316.87 | 1707.05 | 0.00 | 0.00 |
July | 3793.75 | 508.28 | 3056.41 | 1410.30 | 1646.11 | 0.00 | 0.00 |
August | 3200.19 | 595.12 | 2576.49 | 1110.78 | 1465.71 | 0.00 | 0.00 |
September | 2592.69 | 1070.12 | 2298.00 | 1085.93 | 1212.08 | 0.00 | 0.00 |
October | 1139.83 | 1674.46 | 1464.44 | 611.69 | 852.76 | 0.00 | 0.00 |
November | 367.26 | 2580.59 | 864.04 | 280.65 | 583.38 | 0.00 | 0.00 |
December | 245.07 | 3658.16 | 669.29 | 287.41 | 381.88 | 0.00 | 0.00 |
Annual Sum or Average | 1842.98 | 1872.55 | 1917.24 | 830.65 | 1086.59 | 0.00 | 0.00 |
Minimum of Months | 245.07 | 508.28 | 669.29 | 280.65 | 381.88 | 0.00 | 0.00 |
Maximum of Months | 3793.75 | 3961.65 | 3056.41 | 1410.30 | 1707.05 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 3509.37 | 5292.09 | 4307.19 | 2947.50 | 1359.69 | 0.00 | 0.00 |
February | 3924.83 | 4359.59 | 4615.07 | 3117.98 | 1497.09 | 0.00 | 0.00 |
March | 3582.88 | 3261.14 | 4016.15 | 2114.77 | 1901.38 | 0.00 | 0.00 |
April | 3679.04 | 2508.79 | 3618.28 | 1691.62 | 1926.66 | 0.00 | 0.00 |
May | 3255.80 | 1484.87 | 2997.62 | 812.70 | 2184.93 | 0.00 | 0.00 |
June | 3574.67 | 1014.25 | 2910.24 | 592.54 | 2317.70 | 0.00 | 0.00 |
July | 3973.70 | 852.15 | 3080.69 | 776.25 | 2304.44 | 0.00 | 0.00 |
August | 4561.36 | 1020.11 | 3470.92 | 1244.75 | 2226.16 | 0.00 | 0.00 |
September | 5133.30 | 1697.47 | 4206.02 | 2216.23 | 1989.79 | 0.00 | 0.00 |
October | 4581.03 | 2526.38 | 4391.97 | 2755.34 | 1636.63 | 0.00 | 0.00 |
November | 2854.41 | 3619.91 | 3313.73 | 2074.46 | 1239.27 | 0.00 | 0.00 |
December | 3113.73 | 5030.50 | 3533.62 | 2676.67 | 856.94 | 0.00 | 0.00 |
Annual Sum or Average | 3811.10 | 2714.43 | 3699.76 | 1911.55 | 1788.21 | 0.00 | 0.00 |
Minimum of Months | 2854.41 | 852.15 | 2910.24 | 592.54 | 856.94 | 0.00 | 0.00 |
Maximum of Months | 5133.30 | 5292.09 | 4615.07 | 3117.98 | 2317.70 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 365.78 | 4191.39 | 981.22 | 397.02 | 584.21 | 0.00 | 0.00 |
February | 797.90 | 3504.57 | 1438.79 | 708.99 | 729.80 | 0.00 | 0.00 |
March | 1075.93 | 2474.26 | 1717.62 | 639.05 | 1078.57 | 0.00 | 0.00 |
April | 2339.21 | 1904.59 | 2505.50 | 1238.93 | 1266.57 | 0.00 | 0.00 |
May | 2643.03 | 1044.75 | 2512.75 | 1003.78 | 1508.96 | 0.00 | 0.00 |
June | 3525.11 | 766.57 | 2948.41 | 1277.77 | 1670.64 | 0.00 | 0.00 |
July | 3903.70 | 674.33 | 3165.70 | 1503.76 | 1661.94 | 0.00 | 0.00 |
August | 3409.21 | 800.26 | 2767.61 | 1270.15 | 1497.46 | 0.00 | 0.00 |
September | 2513.23 | 1216.34 | 2240.31 | 1063.36 | 1176.94 | 0.00 | 0.00 |
October | 1266.34 | 1920.54 | 1561.14 | 694.06 | 867.07 | 0.00 | 0.00 |
November | 458.28 | 2887.24 | 934.44 | 345.56 | 588.89 | 0.00 | 0.00 |
December | 309.02 | 4041.40 | 718.64 | 338.78 | 379.86 | 0.00 | 0.00 |
Annual Sum or Average | 1889.26 | 2112.12 | 1959.76 | 873.60 | 1086.15 | 0.00 | 0.00 |
Minimum of Months | 309.02 | 674.33 | 718.64 | 338.78 | 379.86 | 0.00 | 0.00 |
Maximum of Months | 3903.70 | 4191.39 | 3165.70 | 1503.76 | 1670.64 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.20 | 6335.07 | 692.58 | 0.00 | 692.58 | 0.00 | 0.00 |
February | 29.77 | 5125.72 | 878.06 | 0.00 | 878.06 | 0.00 | 0.00 |
March | 315.41 | 3309.82 | 1315.95 | 0.00 | 1315.95 | 0.00 | 0.00 |
April | 742.06 | 2282.99 | 1519.17 | 7.48 | 1511.68 | 0.00 | 0.00 |
May | 1592.47 | 1293.98 | 1981.02 | 74.46 | 1906.56 | 0.00 | 0.00 |
June | 2505.45 | 899.25 | 2315.36 | 210.15 | 2105.21 | 0.00 | 0.00 |
July | 2473.41 | 769.74 | 2171.45 | 145.25 | 2026.20 | 0.00 | 0.00 |
August | 2063.37 | 906.06 | 1818.14 | 32.22 | 1785.92 | 0.00 | 0.00 |
September | 1216.30 | 1584.85 | 1393.99 | 0.35 | 1393.65 | 0.00 | 0.00 |
October | 397.35 | 2444.49 | 1036.46 | 0.00 | 1036.46 | 0.00 | 0.00 |
November | 82.35 | 3821.25 | 725.01 | 0.00 | 725.01 | 0.00 | 0.00 |
December | 0.00 | 5570.15 | 470.29 | 0.00 | 470.29 | 0.00 | 0.00 |
Annual Sum or Average | 957.06 | 2851.17 | 1362.34 | 39.31 | 1323.03 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 769.74 | 470.29 | 0.00 | 470.29 | 0.00 | 0.00 |
Maximum of Months | 2505.45 | 6335.07 | 2315.36 | 210.15 | 2105.21 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 363.44 | 3810.82 | 989.38 | 407.13 | 582.25 | 0.00 | 0.00 |
February | 664.42 | 3028.07 | 1311.42 | 576.66 | 734.76 | 0.00 | 0.00 |
March | 1230.23 | 2017.74 | 1781.81 | 707.26 | 1074.56 | 0.00 | 0.00 |
April | 1952.58 | 1451.94 | 2187.90 | 958.15 | 1229.75 | 0.00 | 0.00 |
May | 2908.86 | 863.96 | 2747.82 | 1200.67 | 1547.15 | 0.00 | 0.00 |
June | 3627.77 | 598.94 | 3023.91 | 1316.86 | 1707.04 | 0.00 | 0.00 |
July | 3766.60 | 512.15 | 3056.39 | 1410.29 | 1646.10 | 0.00 | 0.00 |
August | 3181.36 | 598.88 | 2576.48 | 1110.78 | 1465.70 | 0.00 | 0.00 |
September | 2592.75 | 1010.62 | 2297.99 | 1085.92 | 1212.07 | 0.00 | 0.00 |
October | 1187.52 | 1520.52 | 1464.44 | 611.68 | 852.75 | 0.00 | 0.00 |
November | 397.10 | 2364.81 | 864.03 | 280.65 | 583.38 | 0.00 | 0.00 |
December | 260.29 | 3432.98 | 669.29 | 287.41 | 381.88 | 0.00 | 0.00 |
Annual Sum or Average | 1850.84 | 1761.76 | 1917.23 | 830.65 | 1086.58 | 0.00 | 0.00 |
Minimum of Months | 260.29 | 512.15 | 669.29 | 280.65 | 381.88 | 0.00 | 0.00 |
Maximum of Months | 3766.60 | 3810.82 | 3056.39 | 1410.29 | 1707.04 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 3496.51 | 5166.06 | 4307.17 | 2947.49 | 1359.68 | 0.00 | 0.00 |
February | 3908.69 | 4220.78 | 4615.06 | 3117.97 | 1497.09 | 0.00 | 0.00 |
March | 3585.88 | 3101.31 | 4016.13 | 2114.76 | 1901.37 | 0.00 | 0.00 |
April | 3676.24 | 2350.51 | 3618.27 | 1691.61 | 1926.66 | 0.00 | 0.00 |
May | 3243.10 | 1428.64 | 2997.61 | 812.69 | 2184.92 | 0.00 | 0.00 |
June | 3570.46 | 972.43 | 2910.23 | 592.54 | 2317.69 | 0.00 | 0.00 |
July | 3965.20 | 832.42 | 3080.68 | 776.25 | 2304.43 | 0.00 | 0.00 |
August | 4547.06 | 993.60 | 3470.90 | 1244.75 | 2226.15 | 0.00 | 0.00 |
September | 5104.54 | 1645.47 | 4206.00 | 2216.22 | 1989.78 | 0.00 | 0.00 |
October | 4570.35 | 2410.79 | 4391.95 | 2755.33 | 1636.62 | 0.00 | 0.00 |
November | 2869.34 | 3438.65 | 3313.72 | 2074.45 | 1239.27 | 0.00 | 0.00 |
December | 3128.05 | 4815.00 | 3533.60 | 2676.66 | 856.94 | 0.00 | 0.00 |
Annual Sum or Average | 3804.61 | 2607.06 | 3699.75 | 1911.55 | 1788.20 | 0.00 | 0.00 |
Minimum of Months | 2869.34 | 832.42 | 2910.23 | 592.54 | 856.94 | 0.00 | 0.00 |
Maximum of Months | 5104.54 | 5166.06 | 4615.06 | 3117.97 | 2317.69 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 379.90 | 3944.87 | 981.22 | 397.01 | 584.21 | 0.00 | 0.00 |
February | 830.39 | 3209.68 | 1438.79 | 708.99 | 729.80 | 0.00 | 0.00 |
March | 1154.62 | 2138.54 | 1717.61 | 639.05 | 1078.57 | 0.00 | 0.00 |
April | 2407.59 | 1582.15 | 2505.49 | 1238.92 | 1266.57 | 0.00 | 0.00 |
May | 2680.77 | 951.53 | 2512.74 | 1003.78 | 1508.96 | 0.00 | 0.00 |
June | 3559.70 | 679.04 | 2948.40 | 1277.76 | 1670.63 | 0.00 | 0.00 |
July | 3940.70 | 607.75 | 3165.68 | 1503.75 | 1661.93 | 0.00 | 0.00 |
August | 3464.85 | 691.32 | 2767.60 | 1270.15 | 1497.45 | 0.00 | 0.00 |
September | 2548.70 | 1102.03 | 2240.30 | 1063.36 | 1176.94 | 0.00 | 0.00 |
October | 1344.06 | 1645.17 | 1561.13 | 694.06 | 867.07 | 0.00 | 0.00 |
November | 509.73 | 2472.85 | 934.44 | 345.56 | 588.88 | 0.00 | 0.00 |
December | 340.89 | 3565.74 | 718.63 | 338.77 | 379.86 | 0.00 | 0.00 |
Annual Sum or Average | 1935.62 | 1876.29 | 1959.75 | 873.60 | 1086.15 | 0.00 | 0.00 |
Minimum of Months | 340.89 | 607.75 | 718.63 | 338.77 | 379.86 | 0.00 | 0.00 |
Maximum of Months | 3940.70 | 3944.87 | 3165.68 | 1503.75 | 1670.63 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.25 | 6245.92 | 692.58 | 0.00 | 692.58 | 0.00 | 0.00 |
February | 33.37 | 5017.21 | 878.06 | 0.00 | 878.06 | 0.00 | 0.00 |
March | 338.60 | 3175.71 | 1315.95 | 0.00 | 1315.95 | 0.00 | 0.00 |
April | 768.55 | 2150.02 | 1519.17 | 7.48 | 1511.68 | 0.00 | 0.00 |
May | 1622.19 | 1232.93 | 1981.02 | 74.46 | 1906.56 | 0.00 | 0.00 |
June | 2508.04 | 866.76 | 2315.36 | 210.15 | 2105.21 | 0.00 | 0.00 |
July | 2465.53 | 755.76 | 2171.45 | 145.25 | 2026.20 | 0.00 | 0.00 |
August | 2063.74 | 882.04 | 1818.14 | 32.22 | 1785.92 | 0.00 | 0.00 |
September | 1244.16 | 1493.92 | 1393.99 | 0.35 | 1393.65 | 0.00 | 0.00 |
October | 453.08 | 2244.22 | 1036.46 | 0.00 | 1036.46 | 0.00 | 0.00 |
November | 101.08 | 3652.62 | 725.01 | 0.00 | 725.01 | 0.00 | 0.00 |
December | 0.01 | 5449.17 | 470.29 | 0.00 | 470.29 | 0.00 | 0.00 |
Annual Sum or Average | 972.15 | 2753.26 | 1362.34 | 39.31 | 1323.03 | 0.00 | 0.00 |
Minimum of Months | 0.01 | 755.76 | 470.29 | 0.00 | 470.29 | 0.00 | 0.00 |
Maximum of Months | 2508.04 | 6245.92 | 2315.36 | 210.15 | 2105.21 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 366.56 | 3760.12 | 989.38 | 407.13 | 582.25 | 0.00 | 0.00 |
February | 673.83 | 2957.75 | 1311.42 | 576.66 | 734.76 | 0.00 | 0.00 |
March | 1252.20 | 1937.17 | 1781.81 | 707.26 | 1074.56 | 0.00 | 0.00 |
April | 1966.80 | 1379.63 | 2187.90 | 958.15 | 1229.75 | 0.00 | 0.00 |
May | 2913.22 | 834.30 | 2747.82 | 1200.67 | 1547.15 | 0.00 | 0.00 |
June | 3620.87 | 583.34 | 3023.91 | 1316.86 | 1707.04 | 0.00 | 0.00 |
July | 3753.64 | 507.72 | 3056.39 | 1410.29 | 1646.10 | 0.00 | 0.00 |
August | 3173.52 | 589.57 | 2576.48 | 1110.78 | 1465.70 | 0.00 | 0.00 |
September | 2601.71 | 966.89 | 2297.99 | 1085.92 | 1212.07 | 0.00 | 0.00 |
October | 1233.12 | 1407.27 | 1464.44 | 611.68 | 852.75 | 0.00 | 0.00 |
November | 417.22 | 2263.58 | 864.03 | 280.65 | 583.38 | 0.00 | 0.00 |
December | 266.04 | 3356.98 | 669.29 | 287.41 | 381.88 | 0.00 | 0.00 |
Annual Sum or Average | 1859.65 | 1706.32 | 1917.23 | 830.65 | 1086.58 | 0.00 | 0.00 |
Minimum of Months | 266.04 | 507.72 | 669.29 | 280.65 | 381.88 | 0.00 | 0.00 |
Maximum of Months | 3753.64 | 3760.12 | 3056.39 | 1410.29 | 1707.04 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 3511.94 | 5072.82 | 4307.17 | 2947.49 | 1359.68 | 0.00 | 0.00 |
February | 3937.40 | 4087.23 | 4615.06 | 3117.97 | 1497.09 | 0.00 | 0.00 |
March | 3614.64 | 2965.66 | 4016.13 | 2114.76 | 1901.37 | 0.00 | 0.00 |
April | 3693.73 | 2221.92 | 3618.27 | 1691.61 | 1926.66 | 0.00 | 0.00 |
May | 3254.17 | 1367.38 | 2997.61 | 812.69 | 2184.92 | 0.00 | 0.00 |
June | 3566.21 | 938.99 | 2910.23 | 592.54 | 2317.69 | 0.00 | 0.00 |
July | 3951.23 | 818.51 | 3080.68 | 776.25 | 2304.43 | 0.00 | 0.00 |
August | 4536.41 | 970.62 | 3470.90 | 1244.75 | 2226.15 | 0.00 | 0.00 |
September | 5116.45 | 1567.35 | 4206.00 | 2216.22 | 1989.78 | 0.00 | 0.00 |
October | 4627.06 | 2230.25 | 4391.95 | 2755.33 | 1636.62 | 0.00 | 0.00 |
November | 2918.61 | 3266.18 | 3313.72 | 2074.45 | 1239.27 | 0.00 | 0.00 |
December | 3153.44 | 4674.70 | 3533.60 | 2676.66 | 856.94 | 0.00 | 0.00 |
Annual Sum or Average | 3822.50 | 2507.87 | 3699.75 | 1911.55 | 1788.20 | 0.00 | 0.00 |
Minimum of Months | 2918.61 | 818.51 | 2910.23 | 592.54 | 856.94 | 0.00 | 0.00 |
Maximum of Months | 5116.45 | 5072.82 | 4615.06 | 3117.97 | 2317.69 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 379.85 | 3892.34 | 981.22 | 397.01 | 584.21 | 0.00 | 0.00 |
February | 833.73 | 3138.25 | 1438.79 | 708.99 | 729.80 | 0.00 | 0.00 |
March | 1163.75 | 2061.42 | 1717.61 | 639.05 | 1078.57 | 0.00 | 0.00 |
April | 2412.39 | 1506.16 | 2505.49 | 1238.92 | 1266.57 | 0.00 | 0.00 |
May | 2686.29 | 914.81 | 2512.74 | 1003.78 | 1508.96 | 0.00 | 0.00 |
June | 3553.86 | 659.90 | 2948.40 | 1277.76 | 1670.63 | 0.00 | 0.00 |
July | 3929.44 | 598.57 | 3165.68 | 1503.75 | 1661.93 | 0.00 | 0.00 |
August | 3457.76 | 677.36 | 2767.60 | 1270.15 | 1497.45 | 0.00 | 0.00 |
September | 2556.60 | 1054.89 | 2240.30 | 1063.36 | 1176.94 | 0.00 | 0.00 |
October | 1368.33 | 1539.95 | 1561.13 | 694.06 | 867.07 | 0.00 | 0.00 |
November | 523.24 | 2377.11 | 934.44 | 345.56 | 588.88 | 0.00 | 0.00 |
December | 344.00 | 3490.49 | 718.63 | 338.77 | 379.86 | 0.00 | 0.00 |
Annual Sum or Average | 1939.56 | 1819.82 | 1959.75 | 873.60 | 1086.15 | 0.00 | 0.00 |
Minimum of Months | 344.00 | 598.57 | 718.63 | 338.77 | 379.86 | 0.00 | 0.00 |
Maximum of Months | 3929.44 | 3892.34 | 3165.68 | 1503.75 | 1670.63 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.177197E+11 | 0.185503E+10 | 0.00 | 0.185503E+10 | 0.00 | 0.00 |
February | 29917249.85 | 0.132332E+11 | 0.212422E+10 | 0.00 | 0.212422E+10 | 0.00 | 0.00 |
March | 0.661103E+09 | 0.982830E+10 | 0.352464E+10 | 0.00 | 0.352464E+10 | 0.00 | 0.00 |
April | 0.170501E+10 | 0.675041E+10 | 0.393770E+10 | 19400859.18 | 0.391830E+10 | 0.00 | 0.00 |
May | 0.413855E+10 | 0.372234E+10 | 0.530599E+10 | 0.199440E+09 | 0.510655E+10 | 0.00 | 0.00 |
June | 0.643776E+10 | 0.247610E+10 | 0.600145E+10 | 0.544709E+09 | 0.545674E+10 | 0.00 | 0.00 |
July | 0.656107E+10 | 0.215326E+10 | 0.581603E+10 | 0.389029E+09 | 0.542700E+10 | 0.00 | 0.00 |
August | 0.542956E+10 | 0.258120E+10 | 0.486972E+10 | 86305065.82 | 0.478342E+10 | 0.00 | 0.00 |
September | 0.303348E+10 | 0.445921E+10 | 0.361324E+10 | 895921.52 | 0.361234E+10 | 0.00 | 0.00 |
October | 0.827665E+09 | 0.746096E+10 | 0.277606E+10 | 0.00 | 0.277606E+10 | 0.00 | 0.00 |
November | 0.135665E+09 | 0.110812E+11 | 0.187924E+10 | 0.00 | 0.187924E+10 | 0.00 | 0.00 |
December | 0.00 | 0.161280E+11 | 0.125962E+10 | 0.00 | 0.125962E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.289598E+11 | 0.975939E+11 | 0.429629E+11 | 0.123978E+10 | 0.417232E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.215326E+10 | 0.125962E+10 | 0.00 | 0.125962E+10 | 0.00 | 0.00 |
Maximum of Months | 0.656107E+10 | 0.177197E+11 | 0.600145E+10 | 0.544709E+09 | 0.545674E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.952591E+09 | 0.106109E+11 | 0.264996E+10 | 0.109047E+10 | 0.155949E+10 | 0.00 | 0.00 |
February | 0.156083E+10 | 0.775668E+10 | 0.317259E+10 | 0.139505E+10 | 0.177754E+10 | 0.00 | 0.00 |
March | 0.320225E+10 | 0.584556E+10 | 0.477243E+10 | 0.189432E+10 | 0.287811E+10 | 0.00 | 0.00 |
April | 0.501934E+10 | 0.409682E+10 | 0.567105E+10 | 0.248354E+10 | 0.318752E+10 | 0.00 | 0.00 |
May | 0.782287E+10 | 0.243451E+10 | 0.735980E+10 | 0.321590E+10 | 0.414390E+10 | 0.00 | 0.00 |
June | 0.944834E+10 | 0.160753E+10 | 0.783800E+10 | 0.341333E+10 | 0.442467E+10 | 0.00 | 0.00 |
July | 0.101612E+11 | 0.136139E+10 | 0.818628E+10 | 0.377734E+10 | 0.440894E+10 | 0.00 | 0.00 |
August | 0.857138E+10 | 0.159396E+10 | 0.690088E+10 | 0.297512E+10 | 0.392576E+10 | 0.00 | 0.00 |
September | 0.672026E+10 | 0.277376E+10 | 0.595642E+10 | 0.281472E+10 | 0.314170E+10 | 0.00 | 0.00 |
October | 0.305292E+10 | 0.448488E+10 | 0.392237E+10 | 0.163834E+10 | 0.228402E+10 | 0.00 | 0.00 |
November | 0.951934E+09 | 0.668888E+10 | 0.223958E+10 | 0.727457E+09 | 0.151212E+10 | 0.00 | 0.00 |
December | 0.656389E+09 | 0.979802E+10 | 0.179262E+10 | 0.769797E+09 | 0.102283E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.581203E+11 | 0.590529E+11 | 0.604620E+11 | 0.261954E+11 | 0.342666E+11 | 0.00 | 0.00 |
Minimum of Months | 0.656389E+09 | 0.136139E+10 | 0.179262E+10 | 0.727457E+09 | 0.102283E+10 | 0.00 | 0.00 |
Maximum of Months | 0.101612E+11 | 0.106109E+11 | 0.818628E+10 | 0.377734E+10 | 0.442467E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.939950E+10 | 0.141743E+11 | 0.115364E+11 | 0.789459E+10 | 0.364178E+10 | 0.00 | 0.00 |
February | 0.949496E+10 | 0.105467E+11 | 0.111648E+11 | 0.754302E+10 | 0.362177E+10 | 0.00 | 0.00 |
March | 0.959639E+10 | 0.873464E+10 | 0.107569E+11 | 0.566420E+10 | 0.509265E+10 | 0.00 | 0.00 |
April | 0.953607E+10 | 0.650277E+10 | 0.937859E+10 | 0.438468E+10 | 0.499391E+10 | 0.00 | 0.00 |
May | 0.872034E+10 | 0.397707E+10 | 0.802884E+10 | 0.217673E+10 | 0.585211E+10 | 0.00 | 0.00 |
June | 0.926554E+10 | 0.262893E+10 | 0.754333E+10 | 0.153587E+10 | 0.600747E+10 | 0.00 | 0.00 |
July | 0.106432E+11 | 0.228239E+10 | 0.825133E+10 | 0.207912E+10 | 0.617221E+10 | 0.00 | 0.00 |
August | 0.122172E+11 | 0.273226E+10 | 0.929650E+10 | 0.333395E+10 | 0.596255E+10 | 0.00 | 0.00 |
September | 0.133055E+11 | 0.439985E+10 | 0.109020E+11 | 0.574446E+10 | 0.515754E+10 | 0.00 | 0.00 |
October | 0.122698E+11 | 0.676665E+10 | 0.117634E+11 | 0.737991E+10 | 0.438354E+10 | 0.00 | 0.00 |
November | 0.739862E+10 | 0.938281E+10 | 0.858919E+10 | 0.537700E+10 | 0.321220E+10 | 0.00 | 0.00 |
December | 0.833981E+10 | 0.134737E+11 | 0.946443E+10 | 0.716920E+10 | 0.229524E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.120187E+12 | 0.856021E+11 | 0.116676E+12 | 0.602827E+11 | 0.563930E+11 | 0.00 | 0.00 |
Minimum of Months | 0.739862E+10 | 0.228239E+10 | 0.754333E+10 | 0.153587E+10 | 0.229524E+10 | 0.00 | 0.00 |
Maximum of Months | 0.133055E+11 | 0.141743E+11 | 0.117634E+11 | 0.789459E+10 | 0.617221E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.979709E+09 | 0.112262E+11 | 0.262811E+10 | 0.106337E+10 | 0.156475E+10 | 0.00 | 0.00 |
February | 0.193027E+10 | 0.847826E+10 | 0.348073E+10 | 0.171520E+10 | 0.176553E+10 | 0.00 | 0.00 |
March | 0.288178E+10 | 0.662706E+10 | 0.460048E+10 | 0.171163E+10 | 0.288885E+10 | 0.00 | 0.00 |
April | 0.606323E+10 | 0.493669E+10 | 0.649425E+10 | 0.321129E+10 | 0.328296E+10 | 0.00 | 0.00 |
May | 0.707909E+10 | 0.279825E+10 | 0.673014E+10 | 0.268853E+10 | 0.404161E+10 | 0.00 | 0.00 |
June | 0.913708E+10 | 0.198695E+10 | 0.764228E+10 | 0.331198E+10 | 0.433030E+10 | 0.00 | 0.00 |
July | 0.104557E+11 | 0.180612E+10 | 0.847900E+10 | 0.402766E+10 | 0.445134E+10 | 0.00 | 0.00 |
August | 0.913122E+10 | 0.214341E+10 | 0.741278E+10 | 0.340198E+10 | 0.401080E+10 | 0.00 | 0.00 |
September | 0.651430E+10 | 0.315274E+10 | 0.580687E+10 | 0.275624E+10 | 0.305063E+10 | 0.00 | 0.00 |
October | 0.339177E+10 | 0.514398E+10 | 0.418135E+10 | 0.185898E+10 | 0.232237E+10 | 0.00 | 0.00 |
November | 0.118786E+10 | 0.748373E+10 | 0.242208E+10 | 0.895683E+09 | 0.152640E+10 | 0.00 | 0.00 |
December | 0.827666E+09 | 0.108245E+11 | 0.192479E+10 | 0.907376E+09 | 0.101742E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.595796E+11 | 0.666079E+11 | 0.618029E+11 | 0.275499E+11 | 0.342529E+11 | 0.00 | 0.00 |
Minimum of Months | 0.827666E+09 | 0.180612E+10 | 0.192479E+10 | 0.895683E+09 | 0.101742E+10 | 0.00 | 0.00 |
Maximum of Months | 0.104557E+11 | 0.112262E+11 | 0.847900E+10 | 0.402766E+10 | 0.445134E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 533378.66 | 0.169678E+11 | 0.185502E+10 | 0.00 | 0.185502E+10 | 0.00 | 0.00 |
February | 72010807.17 | 0.124001E+11 | 0.212421E+10 | 0.00 | 0.212421E+10 | 0.00 | 0.00 |
March | 0.844786E+09 | 0.886502E+10 | 0.352463E+10 | 0.00 | 0.352463E+10 | 0.00 | 0.00 |
April | 0.192343E+10 | 0.591750E+10 | 0.393768E+10 | 19400790.29 | 0.391828E+10 | 0.00 | 0.00 |
May | 0.426528E+10 | 0.346580E+10 | 0.530598E+10 | 0.199439E+09 | 0.510654E+10 | 0.00 | 0.00 |
June | 0.649412E+10 | 0.233084E+10 | 0.600142E+10 | 0.544707E+09 | 0.545672E+10 | 0.00 | 0.00 |
July | 0.662478E+10 | 0.206168E+10 | 0.581601E+10 | 0.389027E+09 | 0.542698E+10 | 0.00 | 0.00 |
August | 0.552653E+10 | 0.242680E+10 | 0.486970E+10 | 86304759.35 | 0.478340E+10 | 0.00 | 0.00 |
September | 0.315264E+10 | 0.410794E+10 | 0.361322E+10 | 895918.34 | 0.361233E+10 | 0.00 | 0.00 |
October | 0.106427E+10 | 0.654731E+10 | 0.277605E+10 | 0.00 | 0.277605E+10 | 0.00 | 0.00 |
November | 0.213446E+09 | 0.990467E+10 | 0.187923E+10 | 0.00 | 0.187923E+10 | 0.00 | 0.00 |
December | 0.00 | 0.149191E+11 | 0.125962E+10 | 0.00 | 0.125962E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.301818E+11 | 0.899146E+11 | 0.429628E+11 | 0.123978E+10 | 0.417230E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.206168E+10 | 0.125962E+10 | 0.00 | 0.125962E+10 | 0.00 | 0.00 |
Maximum of Months | 0.662478E+10 | 0.169678E+11 | 0.600142E+10 | 0.544707E+09 | 0.545672E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.973426E+09 | 0.102069E+11 | 0.264995E+10 | 0.109046E+10 | 0.155949E+10 | 0.00 | 0.00 |
February | 0.160738E+10 | 0.732552E+10 | 0.317258E+10 | 0.139505E+10 | 0.177753E+10 | 0.00 | 0.00 |
March | 0.329504E+10 | 0.540431E+10 | 0.477241E+10 | 0.189431E+10 | 0.287810E+10 | 0.00 | 0.00 |
April | 0.506108E+10 | 0.376342E+10 | 0.567103E+10 | 0.248353E+10 | 0.318750E+10 | 0.00 | 0.00 |
May | 0.779108E+10 | 0.231402E+10 | 0.735977E+10 | 0.321589E+10 | 0.414388E+10 | 0.00 | 0.00 |
June | 0.940318E+10 | 0.155245E+10 | 0.783796E+10 | 0.341331E+10 | 0.442465E+10 | 0.00 | 0.00 |
July | 0.100885E+11 | 0.137175E+10 | 0.818625E+10 | 0.377732E+10 | 0.440893E+10 | 0.00 | 0.00 |
August | 0.852096E+10 | 0.160403E+10 | 0.690085E+10 | 0.297511E+10 | 0.392574E+10 | 0.00 | 0.00 |
September | 0.672042E+10 | 0.261954E+10 | 0.595639E+10 | 0.281471E+10 | 0.314169E+10 | 0.00 | 0.00 |
October | 0.318065E+10 | 0.407257E+10 | 0.392235E+10 | 0.163834E+10 | 0.228401E+10 | 0.00 | 0.00 |
November | 0.102929E+10 | 0.612959E+10 | 0.223957E+10 | 0.727454E+09 | 0.151212E+10 | 0.00 | 0.00 |
December | 0.697173E+09 | 0.919490E+10 | 0.179262E+10 | 0.769794E+09 | 0.102282E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.583681E+11 | 0.555590E+11 | 0.604617E+11 | 0.261953E+11 | 0.342665E+11 | 0.00 | 0.00 |
Minimum of Months | 0.697173E+09 | 0.137175E+10 | 0.179262E+10 | 0.727454E+09 | 0.102282E+10 | 0.00 | 0.00 |
Maximum of Months | 0.100885E+11 | 0.102069E+11 | 0.818625E+10 | 0.377732E+10 | 0.442465E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.936504E+10 | 0.138368E+11 | 0.115363E+11 | 0.789456E+10 | 0.364177E+10 | 0.00 | 0.00 |
February | 0.945589E+10 | 0.102109E+11 | 0.111647E+11 | 0.754299E+10 | 0.362175E+10 | 0.00 | 0.00 |
March | 0.960441E+10 | 0.830654E+10 | 0.107568E+11 | 0.566418E+10 | 0.509263E+10 | 0.00 | 0.00 |
April | 0.952880E+10 | 0.609253E+10 | 0.937855E+10 | 0.438466E+10 | 0.499390E+10 | 0.00 | 0.00 |
May | 0.868633E+10 | 0.382646E+10 | 0.802881E+10 | 0.217672E+10 | 0.585209E+10 | 0.00 | 0.00 |
June | 0.925463E+10 | 0.252055E+10 | 0.754331E+10 | 0.153586E+10 | 0.600745E+10 | 0.00 | 0.00 |
July | 0.106204E+11 | 0.222956E+10 | 0.825130E+10 | 0.207911E+10 | 0.617219E+10 | 0.00 | 0.00 |
August | 0.121789E+11 | 0.266127E+10 | 0.929647E+10 | 0.333394E+10 | 0.596253E+10 | 0.00 | 0.00 |
September | 0.132310E+11 | 0.426505E+10 | 0.109020E+11 | 0.574444E+10 | 0.515752E+10 | 0.00 | 0.00 |
October | 0.122412E+11 | 0.645706E+10 | 0.117634E+11 | 0.737988E+10 | 0.438352E+10 | 0.00 | 0.00 |
November | 0.743734E+10 | 0.891297E+10 | 0.858916E+10 | 0.537698E+10 | 0.321218E+10 | 0.00 | 0.00 |
December | 0.837817E+10 | 0.128965E+11 | 0.946440E+10 | 0.716917E+10 | 0.229523E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.119982E+12 | 0.822162E+11 | 0.116675E+12 | 0.602825E+11 | 0.563928E+11 | 0.00 | 0.00 |
Minimum of Months | 0.743734E+10 | 0.222956E+10 | 0.754331E+10 | 0.153586E+10 | 0.229523E+10 | 0.00 | 0.00 |
Maximum of Months | 0.132310E+11 | 0.138368E+11 | 0.117634E+11 | 0.789456E+10 | 0.617219E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.101753E+10 | 0.105659E+11 | 0.262810E+10 | 0.106336E+10 | 0.156474E+10 | 0.00 | 0.00 |
February | 0.200888E+10 | 0.776486E+10 | 0.348071E+10 | 0.171519E+10 | 0.176552E+10 | 0.00 | 0.00 |
March | 0.309252E+10 | 0.572786E+10 | 0.460046E+10 | 0.171162E+10 | 0.288883E+10 | 0.00 | 0.00 |
April | 0.624048E+10 | 0.410094E+10 | 0.649422E+10 | 0.321128E+10 | 0.328294E+10 | 0.00 | 0.00 |
May | 0.718018E+10 | 0.254858E+10 | 0.673011E+10 | 0.268852E+10 | 0.404159E+10 | 0.00 | 0.00 |
June | 0.922675E+10 | 0.176007E+10 | 0.764225E+10 | 0.331196E+10 | 0.433028E+10 | 0.00 | 0.00 |
July | 0.105548E+11 | 0.162779E+10 | 0.847896E+10 | 0.402764E+10 | 0.445132E+10 | 0.00 | 0.00 |
August | 0.928025E+10 | 0.185164E+10 | 0.741275E+10 | 0.340197E+10 | 0.401078E+10 | 0.00 | 0.00 |
September | 0.660624E+10 | 0.285646E+10 | 0.580685E+10 | 0.275623E+10 | 0.305062E+10 | 0.00 | 0.00 |
October | 0.359993E+10 | 0.440643E+10 | 0.418133E+10 | 0.185897E+10 | 0.232236E+10 | 0.00 | 0.00 |
November | 0.132122E+10 | 0.640964E+10 | 0.242207E+10 | 0.895679E+09 | 0.152639E+10 | 0.00 | 0.00 |
December | 0.913031E+09 | 0.955047E+10 | 0.192479E+10 | 0.907372E+09 | 0.101741E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.610418E+11 | 0.591707E+11 | 0.618026E+11 | 0.275498E+11 | 0.342528E+11 | 0.00 | 0.00 |
Minimum of Months | 0.913031E+09 | 0.162779E+10 | 0.192479E+10 | 0.895679E+09 | 0.101741E+10 | 0.00 | 0.00 |
Maximum of Months | 0.105548E+11 | 0.105659E+11 | 0.847896E+10 | 0.402764E+10 | 0.445132E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 676757.84 | 0.167291E+11 | 0.185502E+10 | 0.00 | 0.185502E+10 | 0.00 | 0.00 |
February | 80725830.91 | 0.121376E+11 | 0.212421E+10 | 0.00 | 0.212421E+10 | 0.00 | 0.00 |
March | 0.906914E+09 | 0.850581E+10 | 0.352463E+10 | 0.00 | 0.352463E+10 | 0.00 | 0.00 |
April | 0.199209E+10 | 0.557285E+10 | 0.393768E+10 | 19400790.29 | 0.391828E+10 | 0.00 | 0.00 |
May | 0.434486E+10 | 0.330227E+10 | 0.530598E+10 | 0.199439E+09 | 0.510654E+10 | 0.00 | 0.00 |
June | 0.650083E+10 | 0.224663E+10 | 0.600142E+10 | 0.544707E+09 | 0.545672E+10 | 0.00 | 0.00 |
July | 0.660367E+10 | 0.202423E+10 | 0.581601E+10 | 0.389027E+09 | 0.542698E+10 | 0.00 | 0.00 |
August | 0.552753E+10 | 0.236246E+10 | 0.486970E+10 | 86304759.35 | 0.478340E+10 | 0.00 | 0.00 |
September | 0.322485E+10 | 0.387224E+10 | 0.361322E+10 | 895918.34 | 0.361233E+10 | 0.00 | 0.00 |
October | 0.121353E+10 | 0.601093E+10 | 0.277605E+10 | 0.00 | 0.277605E+10 | 0.00 | 0.00 |
November | 0.261989E+09 | 0.946759E+10 | 0.187923E+10 | 0.00 | 0.187923E+10 | 0.00 | 0.00 |
December | 22842.20 | 0.145951E+11 | 0.125962E+10 | 0.00 | 0.125962E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.306577E+11 | 0.868268E+11 | 0.429628E+11 | 0.123978E+10 | 0.417230E+11 | 0.00 | 0.00 |
Minimum of Months | 22842.20 | 0.202423E+10 | 0.125962E+10 | 0.00 | 0.125962E+10 | 0.00 | 0.00 |
Maximum of Months | 0.660367E+10 | 0.167291E+11 | 0.600142E+10 | 0.544707E+09 | 0.545672E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.981799E+09 | 0.100711E+11 | 0.264995E+10 | 0.109046E+10 | 0.155949E+10 | 0.00 | 0.00 |
February | 0.163014E+10 | 0.715539E+10 | 0.317258E+10 | 0.139505E+10 | 0.177753E+10 | 0.00 | 0.00 |
March | 0.335390E+10 | 0.518851E+10 | 0.477241E+10 | 0.189431E+10 | 0.287810E+10 | 0.00 | 0.00 |
April | 0.509794E+10 | 0.357599E+10 | 0.567103E+10 | 0.248353E+10 | 0.318750E+10 | 0.00 | 0.00 |
May | 0.780276E+10 | 0.223459E+10 | 0.735977E+10 | 0.321589E+10 | 0.414388E+10 | 0.00 | 0.00 |
June | 0.938530E+10 | 0.151202E+10 | 0.783796E+10 | 0.341331E+10 | 0.442465E+10 | 0.00 | 0.00 |
July | 0.100537E+11 | 0.135987E+10 | 0.818625E+10 | 0.377732E+10 | 0.440893E+10 | 0.00 | 0.00 |
August | 0.849994E+10 | 0.157911E+10 | 0.690085E+10 | 0.297511E+10 | 0.392574E+10 | 0.00 | 0.00 |
September | 0.674363E+10 | 0.250618E+10 | 0.595639E+10 | 0.281471E+10 | 0.314169E+10 | 0.00 | 0.00 |
October | 0.330279E+10 | 0.376923E+10 | 0.392235E+10 | 0.163834E+10 | 0.228401E+10 | 0.00 | 0.00 |
November | 0.108144E+10 | 0.586719E+10 | 0.223957E+10 | 0.727454E+09 | 0.151212E+10 | 0.00 | 0.00 |
December | 0.712558E+09 | 0.899134E+10 | 0.179262E+10 | 0.769794E+09 | 0.102282E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.586459E+11 | 0.538105E+11 | 0.604617E+11 | 0.261953E+11 | 0.342665E+11 | 0.00 | 0.00 |
Minimum of Months | 0.712558E+09 | 0.135987E+10 | 0.179262E+10 | 0.727454E+09 | 0.102282E+10 | 0.00 | 0.00 |
Maximum of Months | 0.100537E+11 | 0.100711E+11 | 0.818625E+10 | 0.377732E+10 | 0.442465E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.940639E+10 | 0.135870E+11 | 0.115363E+11 | 0.789456E+10 | 0.364177E+10 | 0.00 | 0.00 |
February | 0.952537E+10 | 0.988782E+10 | 0.111647E+11 | 0.754299E+10 | 0.362175E+10 | 0.00 | 0.00 |
March | 0.968146E+10 | 0.794322E+10 | 0.107568E+11 | 0.566418E+10 | 0.509263E+10 | 0.00 | 0.00 |
April | 0.957414E+10 | 0.575922E+10 | 0.937855E+10 | 0.438466E+10 | 0.499390E+10 | 0.00 | 0.00 |
May | 0.871596E+10 | 0.366238E+10 | 0.802881E+10 | 0.217672E+10 | 0.585209E+10 | 0.00 | 0.00 |
June | 0.924363E+10 | 0.243386E+10 | 0.754331E+10 | 0.153586E+10 | 0.600745E+10 | 0.00 | 0.00 |
July | 0.105830E+11 | 0.219231E+10 | 0.825130E+10 | 0.207911E+10 | 0.617219E+10 | 0.00 | 0.00 |
August | 0.121503E+11 | 0.259971E+10 | 0.929647E+10 | 0.333394E+10 | 0.596253E+10 | 0.00 | 0.00 |
September | 0.132619E+11 | 0.406257E+10 | 0.109020E+11 | 0.574444E+10 | 0.515752E+10 | 0.00 | 0.00 |
October | 0.123931E+11 | 0.597351E+10 | 0.117634E+11 | 0.737988E+10 | 0.438352E+10 | 0.00 | 0.00 |
November | 0.756503E+10 | 0.846593E+10 | 0.858916E+10 | 0.537698E+10 | 0.321218E+10 | 0.00 | 0.00 |
December | 0.844618E+10 | 0.125207E+11 | 0.946440E+10 | 0.716917E+10 | 0.229523E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.120546E+12 | 0.790883E+11 | 0.116675E+12 | 0.602825E+11 | 0.563928E+11 | 0.00 | 0.00 |
Minimum of Months | 0.756503E+10 | 0.219231E+10 | 0.754331E+10 | 0.153586E+10 | 0.229523E+10 | 0.00 | 0.00 |
Maximum of Months | 0.132619E+11 | 0.135870E+11 | 0.117634E+11 | 0.789456E+10 | 0.617219E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.101739E+10 | 0.104252E+11 | 0.262810E+10 | 0.106336E+10 | 0.156474E+10 | 0.00 | 0.00 |
February | 0.201695E+10 | 0.759205E+10 | 0.348071E+10 | 0.171519E+10 | 0.176552E+10 | 0.00 | 0.00 |
March | 0.311699E+10 | 0.552130E+10 | 0.460046E+10 | 0.171162E+10 | 0.288883E+10 | 0.00 | 0.00 |
April | 0.625293E+10 | 0.390397E+10 | 0.649422E+10 | 0.321128E+10 | 0.328294E+10 | 0.00 | 0.00 |
May | 0.719497E+10 | 0.245022E+10 | 0.673011E+10 | 0.268852E+10 | 0.404159E+10 | 0.00 | 0.00 |
June | 0.921160E+10 | 0.171046E+10 | 0.764225E+10 | 0.331196E+10 | 0.433028E+10 | 0.00 | 0.00 |
July | 0.105246E+11 | 0.160320E+10 | 0.847896E+10 | 0.402764E+10 | 0.445132E+10 | 0.00 | 0.00 |
August | 0.926126E+10 | 0.181424E+10 | 0.741275E+10 | 0.340197E+10 | 0.401078E+10 | 0.00 | 0.00 |
September | 0.662670E+10 | 0.273428E+10 | 0.580685E+10 | 0.275623E+10 | 0.305062E+10 | 0.00 | 0.00 |
October | 0.366493E+10 | 0.412459E+10 | 0.418133E+10 | 0.185897E+10 | 0.232236E+10 | 0.00 | 0.00 |
November | 0.135623E+10 | 0.616148E+10 | 0.242207E+10 | 0.895679E+09 | 0.152639E+10 | 0.00 | 0.00 |
December | 0.921379E+09 | 0.934893E+10 | 0.192479E+10 | 0.907372E+09 | 0.101741E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.611659E+11 | 0.573900E+11 | 0.618026E+11 | 0.275498E+11 | 0.342528E+11 | 0.00 | 0.00 |
Minimum of Months | 0.921379E+09 | 0.160320E+10 | 0.192479E+10 | 0.895679E+09 | 0.101741E+10 | 0.00 | 0.00 |
Maximum of Months | 0.105246E+11 | 0.104252E+11 | 0.847896E+10 | 0.402764E+10 | 0.445132E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | -12.6 | -13.1 | -15.2 | 6.10 | -26.1 | 37.55 | 107.22 | 0.02 |
February | -7.7 | -8.6 | -10.9 | 6.39 | -21.3 | 45.57 | 135.04 | 0.00 |
March | 0.33 | -1.4 | -4.2 | 6.99 | -10.6 | 74.69 | 127.11 | 0.00 |
April | 7.02 | 4.40 | 1.63 | 6.38 | -3.6 | 77.59 | 184.47 | 0.02 |
May | 14.19 | 11.30 | 8.94 | 5.14 | 4.70 | 102.33 | 182.89 | 0.00 |
June | 19.16 | 15.71 | 13.79 | 4.87 | 8.84 | 110.26 | 213.51 | 0.04 |
July | 20.92 | 17.87 | 16.31 | 4.22 | 9.95 | 102.99 | 231.93 | 0.03 |
August | 20.05 | 17.00 | 15.28 | 4.97 | 11.01 | 95.97 | 190.14 | 0.00 |
September | 15.39 | 11.24 | 8.10 | 4.97 | 3.18 | 72.67 | 177.74 | 0.01 |
October | 7.43 | 4.69 | 1.56 | 5.55 | -3.9 | 55.50 | 131.91 | 0.00 |
November | -0.0 | -1.5 | -3.9 | 6.30 | -10.9 | 41.35 | 79.05 | 0.00 |
December | -7.6 | -8.4 | -10.6 | 6.09 | -20.0 | 22.97 | 92.59 | 0.00 |
Annual Sum or Average | 6.46 | 4.16 | 1.81 | 5.66 | -4.8 | 70.09 | 154.52 | 0.01 |
Minimum of Months | -12.6 | -13.1 | -15.2 | 4.22 | -26.1 | 22.97 | 79.05 | 0.00 |
Maximum of Months | 20.92 | 17.87 | 16.31 | 6.99 | 11.01 | 110.26 | 231.93 | 0.04 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 6.10 | 17-JAN-23:19 | 3.74 | 0.93 | 10.63 | -0.4 | 0.00 | 0.00 |
February | 8.30 | 24-FEB-14:00 | 5.62 | 2.80 | 5.20 | -7.3 | 71.00 | 794.50 |
March | 18.90 | 19-MAR-15:00 | 13.93 | 10.60 | 8.80 | 7.95 | 139.50 | 237.50 |
April | 30.00 | 15-APR-15:20 | 19.12 | 13.53 | 12.70 | 15.70 | 115.83 | 790.83 |
May | 30.00 | 31-MAY-12:00 | 19.70 | 14.40 | 6.20 | 19.52 | 251.00 | 580.50 |
June | 33.30 | 11-JUN-14:00 | 24.81 | 21.70 | 10.30 | 24.50 | 281.00 | 458.50 |
July | 30.00 | 26-JUL-15:20 | 25.67 | 24.23 | 5.13 | 20.98 | 260.33 | 436.00 |
August | 33.90 | 04-AUG-14:00 | 25.31 | 22.20 | 4.60 | 23.82 | 194.50 | 612.00 |
September | 32.20 | 06-SEP-13:00 | 21.19 | 16.10 | 6.20 | 18.28 | 135.00 | 769.00 |
October | 23.30 | 20-OCT-14:00 | 13.36 | 5.60 | 7.20 | 7.35 | 55.00 | 745.50 |
November | 16.10 | 03-NOV-13:00 | 10.47 | 5.60 | 6.70 | 0.51 | 82.00 | 691.00 |
December | 7.20 | 02-DEC-13:00 | 3.94 | 0.00 | 7.70 | -3.9 | 75.00 | 301.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 6.10 | 3.74 | 0.00 | 4.60 | -7.3 | 0.00 | 0.00 | |
Maximum of Months | 33.90 | 25.67 | 24.23 | 12.70 | 24.50 | 281.00 | 794.50 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -31.1 | 31-JAN-03:00 | -31.3 | -34.4 | 4.60 | -46.7 | 0.00 | 0.00 |
February | -36.7 | 02-FEB-05:00 | -36.8 | -40.2 | 3.10 | -59.6 | 0.00 | 0.00 |
March | -17.2 | 06-MAR-00:00 | -17.6 | -20.0 | 5.20 | -36.8 | 0.00 | 0.00 |
April | -7.2 | 03-APR-05:19 | -8.0 | -9.8 | 7.37 | -15.9 | 0.00 | 0.00 |
May | 0.60 | 03-MAY-02:00 | -0.1 | -1.1 | 1.50 | -15.5 | 0.00 | 0.00 |
June | 5.00 | 01-JUN-04:00 | 5.00 | 5.00 | 3.10 | -7.8 | 30.50 | 132.50 |
July | 10.00 | 23-JUL-03:00 | 9.66 | 9.40 | 2.60 | -4.3 | 0.00 | 0.00 |
August | 8.30 | 07-AUG-03:00 | 7.41 | 6.70 | 3.10 | -3.2 | 0.00 | 0.00 |
September | -1.1 | 30-SEP-00:00 | -2.4 | -4.4 | 4.10 | -17.8 | 0.00 | 0.00 |
October | -3.3 | 23-OCT-05:00 | -4.2 | -6.1 | 3.60 | -19.1 | 0.00 | 0.00 |
November | -28.9 | 26-NOV-06:00 | -29.0 | -30.6 | 1.50 | -50.2 | 0.00 | 0.00 |
December | -22.8 | 09-DEC-00:20 | -23.0 | -25.0 | 13.40 | -37.7 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -36.7 | -36.8 | -40.2 | 1.50 | -59.6 | 0.00 | 0.00 | |
Maximum of Months | 10.00 | 9.66 | 9.40 | 13.40 | -3.2 | 30.50 | 132.50 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 5.60 | 18-JAN-00:00 | 5.60 | 5.60 | 7.70 | 0.30 | 0.00 | 0.00 |
February | 5.88 | 24-FEB-15:00 | 8.30 | 3.30 | 5.70 | -7.3 | 54.50 | 665.50 |
March | 13.93 | 19-MAR-15:00 | 18.90 | 10.60 | 8.80 | 7.95 | 139.50 | 237.50 |
April | 20.94 | 18-APR-11:00 | 27.80 | 17.80 | 13.90 | 17.57 | 334.00 | 447.00 |
May | 19.93 | 29-MAY-13:00 | 23.30 | 18.30 | 6.20 | 20.75 | 379.00 | 52.00 |
June | 24.81 | 11-JUN-14:00 | 33.30 | 21.70 | 10.30 | 24.50 | 281.00 | 458.50 |
July | 26.15 | 26-JUL-18:00 | 27.80 | 25.60 | 3.10 | 19.35 | 33.50 | 51.00 |
August | 26.64 | 04-AUG-12:00 | 31.70 | 25.00 | 4.60 | 25.66 | 235.00 | 593.50 |
September | 21.19 | 06-SEP-13:00 | 32.20 | 16.10 | 6.20 | 18.28 | 135.00 | 769.00 |
October | 14.84 | 02-OCT-14:00 | 18.30 | 12.80 | 3.60 | 12.41 | 202.00 | 164.00 |
November | 13.04 | 09-NOV-04:00 | 15.00 | 11.70 | 10.30 | 10.88 | 0.00 | 0.00 |
December | 3.94 | 02-DEC-13:00 | 7.20 | 0.00 | 7.70 | -3.9 | 75.00 | 301.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 3.94 | 5.60 | 0.00 | 3.10 | -7.3 | 0.00 | 0.00 | |
Maximum of Months | 26.64 | 33.30 | 25.60 | 13.90 | 25.66 | 379.00 | 769.00 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 5.60 | 18-JAN-00:00 | 5.60 | 5.60 | 7.70 | 0.30 | 0.00 | 0.00 |
February | 3.30 | 24-FEB-15:00 | 8.30 | 5.88 | 5.70 | -7.3 | 54.50 | 665.50 |
March | 11.10 | 26-MAR-05:00 | 13.30 | 12.04 | 8.20 | 9.13 | 0.00 | 0.00 |
April | 18.30 | 18-APR-09:00 | 25.60 | 20.52 | 14.40 | 15.57 | 196.00 | 741.50 |
May | 18.30 | 29-MAY-13:00 | 23.30 | 19.93 | 6.20 | 20.75 | 379.00 | 52.00 |
June | 22.20 | 13-JUN-11:00 | 26.70 | 23.35 | 8.80 | 16.85 | 273.50 | 600.50 |
July | 25.60 | 26-JUL-18:00 | 27.80 | 26.15 | 3.10 | 19.35 | 33.50 | 51.00 |
August | 25.00 | 04-AUG-12:00 | 31.70 | 26.64 | 4.60 | 25.66 | 235.00 | 593.50 |
September | 18.30 | 12-SEP-02:00 | 18.90 | 18.46 | 5.70 | 14.28 | 0.00 | 0.00 |
October | 12.80 | 02-OCT-13:00 | 17.40 | 14.50 | 3.40 | 11.65 | 249.50 | 141.50 |
November | 11.70 | 08-NOV-10:00 | 13.90 | 12.62 | 7.20 | 9.91 | 158.00 | 0.50 |
December | 0.00 | 02-DEC-11:00 | 5.00 | 2.79 | 7.20 | -8.3 | 115.50 | 562.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 0.00 | 5.00 | 2.79 | 3.10 | -8.3 | 0.00 | 0.00 | |
Maximum of Months | 25.60 | 31.70 | 26.64 | 14.40 | 25.66 | 379.00 | 741.50 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 4.29 | 14.52 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 3.18 | 19.75 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 3.75 | 28.43 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 5.88 | 38.20 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 9.06 | 44.89 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 12.40 | 51.07 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 15.02 | 51.61 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 16.22 | 43.31 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 15.63 | 34.41 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 13.44 | 22.83 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 10.25 | 13.98 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 6.92 | 10.24 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 9.71 | 31.16 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 3.18 | 10.24 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 16.22 | 51.61 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.445947E+11 | -0.435237E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.107102E+10 | 58.98 | 0.00 | 0.00 |
February | 0.412989E+11 | -0.403473E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -951539621.3 | 58.99 | 0.00 | 0.00 |
March | 0.480212E+11 | -0.469889E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.103235E+10 | 58.98 | 0.00 | 0.00 |
April | 0.419558E+11 | -0.409629E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -992986358.5 | 58.98 | 0.00 | 0.00 |
May | 0.421884E+11 | -0.411642E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.102419E+10 | 58.98 | 0.00 | 0.00 |
June | 0.390328E+11 | -0.380428E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -989999402.7 | 58.97 | 0.00 | 0.00 |
July | 0.351431E+11 | -0.341257E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.101740E+10 | 58.97 | 0.00 | 0.00 |
August | 0.374004E+11 | -0.363791E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.102132E+10 | 58.97 | 0.00 | 0.00 |
September | 0.344374E+11 | -0.334508E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -986603690.6 | 58.97 | 0.00 | 0.00 |
October | 0.372722E+11 | -0.362515E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.102072E+10 | 58.98 | 0.00 | 0.00 |
November | 0.390342E+11 | -0.380410E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -993210104.2 | 58.98 | 0.00 | 0.00 |
December | 0.414646E+11 | -0.404272E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.103737E+10 | 58.98 | 0.00 | 0.00 |
Annual Sum or Average | 0.481844E+12 | -0.469705E+12 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.121387E+11 | 58.98 | 0.00 | 0.00 |
Minimum of Months | 0.344374E+11 | -0.469889E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -0.107102E+10 | 58.97 | 0.00 | 0.00 |
Maximum of Months | 0.480212E+11 | -0.334508E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -951539621.3 | 58.99 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_1_DAYLCTRL
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 214.17 | 0.50 | 0.48 | 01-JAN-09:39 | 7570.71 | 37.78 | 207.00 | 246.50 | 6192.03 | 38.38 | 212.50 | 223.17 |
February | 226.83 | 0.50 | 0.48 | 01-FEB-08:09 | 8960.92 | 37.94 | 225.00 | 256.17 | 2468.89 | 27.74 | 198.50 | 234.00 |
March | 334.33 | 0.50 | 0.48 | 01-MAR-07:00 | 8195.58 | 31.14 | 285.00 | 329.50 | 1549.77 | 22.79 | 248.17 | 297.00 |
April | 285.17 | 0.51 | 0.48 | 01-APR-07:19 | 2501.97 | 20.99 | 143.17 | 348.83 | 1468.26 | 22.39 | 218.17 | 308.50 |
May | 428.67 | 0.51 | 0.48 | 01-MAY-06:49 | 1942.38 | 20.59 | 171.17 | 399.33 | 1072.58 | 21.98 | 290.83 | 357.00 |
June | 400.67 | 0.51 | 0.48 | 01-JUN-05:49 | 1988.62 | 20.78 | 184.00 | 401.17 | 1115.46 | 22.20 | 306.33 | 362.00 |
July | 414.00 | 0.50 | 0.48 | 01-JUL-05:00 | 2062.98 | 21.08 | 201.67 | 411.17 | 1167.38 | 22.49 | 317.00 | 371.33 |
August | 410.83 | 0.51 | 0.48 | 01-AUG-06:19 | 2273.24 | 21.02 | 219.00 | 382.33 | 1258.46 | 22.42 | 303.83 | 349.83 |
September | 326.50 | 0.50 | 0.48 | 01-SEP-06:30 | 3269.48 | 22.69 | 188.00 | 335.50 | 1580.11 | 22.95 | 266.83 | 306.50 |
October | 325.17 | 0.50 | 0.48 | 01-OCT-06:49 | 7730.02 | 33.80 | 296.33 | 307.33 | 2046.30 | 24.18 | 242.50 | 285.83 |
November | 254.83 | 0.50 | 0.48 | 01-NOV-07:49 | 5415.63 | 33.37 | 241.00 | 249.17 | 2911.06 | 31.55 | 241.00 | 228.67 |
December | 186.17 | 0.50 | 0.48 | 01-DEC-07:00 | 6640.26 | 38.76 | 184.00 | 225.33 | 5990.63 | 39.93 | 184.50 | 189.33 |
Annual Sum or Average | 3807.33 | 0.50 | 4392.12 | 26.72 | 2545.33 | 3892.33 | 2040.38 | 25.26 | 3030.17 | 3513.17 | ||
Minimum of Months | 186.17 | 0.50 | 0.48 | 1942.38 | 20.59 | 143.17 | 225.33 | 1072.58 | 21.98 | 184.50 | 189.33 | |
Maximum of Months | 428.67 | 0.51 | 0.48 | 8960.92 | 38.76 | 296.33 | 411.17 | 6192.03 | 39.93 | 317.00 | 371.33 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_2_DAYLCTRL
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 214.17 | 0.52 | 0.48 | 01-JAN-09:39 | 2027.97 | 24.41 | 100.50 | 233.67 | 1024.84 | 24.18 | 140.17 | 194.50 |
February | 226.83 | 0.52 | 0.48 | 01-FEB-07:49 | 2501.08 | 25.41 | 105.67 | 246.50 | 1368.67 | 25.42 | 148.33 | 212.83 |
March | 334.33 | 0.50 | 0.48 | 01-MAR-07:00 | 3209.50 | 25.20 | 166.83 | 325.67 | 1347.83 | 24.49 | 218.00 | 288.00 |
April | 285.17 | 0.51 | 0.48 | 01-APR-06:49 | 3768.78 | 24.72 | 104.83 | 351.67 | 2215.67 | 25.35 | 171.83 | 318.83 |
May | 428.67 | 0.50 | 0.48 | 01-MAY-05:19 | 3887.80 | 24.67 | 155.50 | 407.67 | 1665.59 | 24.17 | 239.00 | 368.33 |
June | 400.67 | 0.50 | 0.48 | 01-JUN-04:00 | 3541.93 | 24.25 | 124.50 | 408.50 | 1923.14 | 24.87 | 264.83 | 381.17 |
July | 414.00 | 0.50 | 0.48 | 01-JUL-05:40 | 4445.06 | 24.98 | 136.50 | 418.67 | 1927.25 | 24.59 | 250.67 | 386.00 |
August | 410.83 | 0.50 | 0.48 | 01-AUG-05:40 | 3576.50 | 24.81 | 163.67 | 387.00 | 1598.16 | 24.49 | 258.67 | 360.33 |
September | 326.50 | 0.51 | 0.48 | 01-SEP-05:00 | 3583.19 | 24.84 | 130.83 | 333.67 | 1996.37 | 25.25 | 206.00 | 305.00 |
October | 325.17 | 0.51 | 0.48 | 01-OCT-06:40 | 2273.63 | 24.39 | 140.00 | 296.83 | 1219.48 | 24.65 | 201.17 | 267.83 |
November | 254.83 | 0.52 | 0.48 | 01-NOV-07:49 | 1767.54 | 23.69 | 105.83 | 238.00 | 932.19 | 23.92 | 150.83 | 199.67 |
December | 186.17 | 0.53 | 0.48 | 01-DEC-07:00 | 1613.63 | 25.12 | 84.50 | 205.67 | 841.25 | 24.57 | 94.17 | 136.50 |
Annual Sum or Average | 3807.33 | 0.51 | 3205.60 | 24.70 | 1519.17 | 3853.50 | 1574.31 | 24.65 | 2343.67 | 3419.00 | ||
Minimum of Months | 186.17 | 0.50 | 0.48 | 1613.63 | 23.69 | 84.50 | 205.67 | 841.25 | 23.92 | 94.17 | 136.50 | |
Maximum of Months | 428.67 | 0.53 | 0.48 | 4445.06 | 25.41 | 166.83 | 418.67 | 2215.67 | 25.42 | 264.83 | 386.00 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_3_DAYLCTRL
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 214.17 | 0.55 | 0.48 | 01-JAN-10:09 | 728.52 | 17.75 | 0.00 | 217.67 | 440.97 | 19.44 | 27.83 | 147.67 |
February | 226.83 | 0.54 | 0.48 | 01-FEB-09:20 | 770.59 | 18.07 | 0.00 | 233.50 | 475.85 | 19.72 | 35.33 | 179.17 |
March | 334.33 | 0.51 | 0.48 | 01-MAR-08:20 | 1036.90 | 19.46 | 0.00 | 321.50 | 600.27 | 20.87 | 129.00 | 272.17 |
April | 285.17 | 0.51 | 0.48 | 01-APR-07:19 | 1230.15 | 20.27 | 41.17 | 351.50 | 753.95 | 21.66 | 181.50 | 301.67 |
May | 428.67 | 0.49 | 0.48 | 01-MAY-06:40 | 1380.63 | 21.58 | 121.83 | 417.67 | 779.18 | 22.79 | 295.83 | 382.17 |
June | 400.67 | 0.49 | 0.48 | 01-JUN-04:00 | 1666.38 | 24.10 | 202.83 | 417.00 | 931.92 | 23.60 | 330.67 | 392.17 |
July | 414.00 | 0.49 | 0.48 | 01-JUL-05:40 | 1568.89 | 22.35 | 174.17 | 425.33 | 893.52 | 22.72 | 327.17 | 397.50 |
August | 410.83 | 0.50 | 0.48 | 01-AUG-05:00 | 1287.66 | 20.61 | 75.50 | 391.33 | 757.05 | 21.95 | 288.50 | 363.33 |
September | 326.50 | 0.51 | 0.48 | 01-SEP-06:19 | 1086.93 | 20.02 | 1.67 | 333.83 | 663.70 | 21.44 | 191.17 | 292.17 |
October | 325.17 | 0.53 | 0.48 | 01-OCT-07:30 | 851.71 | 18.56 | 0.00 | 287.00 | 501.63 | 20.06 | 56.83 | 236.00 |
November | 254.83 | 0.54 | 0.48 | 01-NOV-08:30 | 718.86 | 17.64 | 0.00 | 227.50 | 406.51 | 19.09 | 4.00 | 157.67 |
December | 186.17 | 0.58 | 0.48 | 01-DEC-10:09 | 533.23 | 16.47 | 0.00 | 183.83 | 332.51 | 18.26 | 0.00 | 80.50 |
Annual Sum or Average | 3807.33 | 0.51 | 1150.57 | 20.21 | 617.17 | 3807.67 | 670.21 | 21.33 | 1867.83 | 3202.17 | ||
Minimum of Months | 186.17 | 0.49 | 0.48 | 533.23 | 16.47 | 0.00 | 183.83 | 332.51 | 18.26 | 0.00 | 80.50 | |
Maximum of Months | 428.67 | 0.58 | 0.48 | 1666.38 | 24.10 | 202.83 | 425.33 | 931.92 | 23.60 | 330.67 | 397.50 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_4_DAYLCTRL
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 214.17 | 0.52 | 0.48 | 01-JAN-09:00 | 2200.57 | 25.89 | 105.83 | 232.50 | 1259.22 | 25.74 | 140.50 | 194.17 |
February | 226.83 | 0.52 | 0.48 | 01-FEB-09:20 | 2576.28 | 25.32 | 102.33 | 245.83 | 1397.07 | 25.20 | 154.50 | 215.17 |
March | 334.33 | 0.50 | 0.48 | 01-MAR-08:30 | 2720.81 | 23.90 | 150.83 | 327.50 | 1457.65 | 24.37 | 206.50 | 293.00 |
April | 285.17 | 0.50 | 0.48 | 02-APR-14:39 | 4853.88 | 24.94 | 103.17 | 353.33 | 2007.86 | 23.92 | 150.50 | 308.33 |
May | 428.67 | 0.50 | 0.48 | 01-MAY-06:00 | 2930.59 | 20.98 | 74.50 | 407.33 | 1585.28 | 21.37 | 216.83 | 375.33 |
June | 400.67 | 0.50 | 0.48 | 01-JUN-05:00 | 3732.27 | 21.44 | 69.17 | 408.67 | 1697.52 | 21.83 | 242.33 | 375.17 |
July | 414.00 | 0.49 | 0.48 | 01-JUL-06:10 | 4174.31 | 21.90 | 85.17 | 417.17 | 1820.92 | 22.06 | 239.33 | 385.17 |
August | 410.83 | 0.50 | 0.48 | 01-AUG-06:30 | 3484.63 | 23.00 | 123.83 | 390.50 | 1939.94 | 23.67 | 242.33 | 359.83 |
September | 326.50 | 0.50 | 0.48 | 01-SEP-07:19 | 3650.48 | 25.17 | 129.17 | 338.50 | 2104.10 | 25.63 | 214.33 | 308.67 |
October | 325.17 | 0.51 | 0.48 | 01-OCT-07:40 | 2330.76 | 24.43 | 137.83 | 297.17 | 1242.58 | 24.60 | 204.00 | 265.83 |
November | 254.83 | 0.52 | 0.48 | 01-NOV-08:30 | 1826.31 | 23.59 | 103.17 | 239.33 | 981.42 | 23.76 | 146.67 | 201.33 |
December | 186.17 | 0.54 | 0.48 | 01-DEC-10:09 | 1718.76 | 24.65 | 75.83 | 209.00 | 943.55 | 24.40 | 86.83 | 136.17 |
Annual Sum or Average | 3807.33 | 0.51 | 3150.78 | 23.44 | 1260.83 | 3866.83 | 1595.30 | 23.62 | 2244.67 | 3418.17 | ||
Minimum of Months | 186.17 | 0.49 | 0.48 | 1718.76 | 20.98 | 69.17 | 209.00 | 943.55 | 21.37 | 86.83 | 136.17 | |
Maximum of Months | 428.67 | 0.54 | 0.48 | 4853.88 | 25.89 | 150.83 | 417.17 | 2104.10 | 25.74 | 242.33 | 385.17 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_1_DAYLCTRL
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 214.17 | 0.50 | 0.48 | 01-JAN-09:39 | 7621.70 | 37.17 | 205.17 | 246.50 | 6338.63 | 37.82 | 200.17 | 225.17 |
February | 226.83 | 0.50 | 0.48 | 01-FEB-07:00 | 9023.97 | 37.52 | 222.33 | 256.50 | 2716.72 | 26.30 | 105.67 | 241.67 |
March | 334.33 | 0.50 | 0.48 | 01-MAR-07:00 | 8232.51 | 29.60 | 250.83 | 329.50 | 1657.54 | 18.10 | 5.83 | 300.17 |
April | 285.17 | 0.51 | 0.48 | 01-APR-07:10 | 2557.09 | 14.83 | 0.00 | 349.17 | 1576.39 | 18.34 | 17.83 | 315.50 |
May | 428.67 | 0.51 | 0.48 | 01-MAY-06:40 | 1972.64 | 14.42 | 0.00 | 399.50 | 1144.46 | 17.86 | 0.00 | 361.00 |
June | 400.67 | 0.51 | 0.48 | 01-JUN-05:40 | 2020.19 | 14.91 | 0.00 | 401.17 | 1189.74 | 18.35 | 0.00 | 367.00 |
July | 414.00 | 0.50 | 0.48 | 01-JUL-05:00 | 2096.97 | 15.22 | 0.00 | 411.50 | 1246.34 | 18.68 | 2.00 | 376.00 |
August | 410.83 | 0.51 | 0.48 | 01-AUG-06:19 | 2308.77 | 14.92 | 0.00 | 382.83 | 1344.17 | 18.37 | 4.83 | 354.17 |
September | 326.50 | 0.50 | 0.48 | 01-SEP-06:19 | 3323.82 | 16.87 | 26.00 | 335.50 | 1694.00 | 18.74 | 28.67 | 309.17 |
October | 325.17 | 0.50 | 0.48 | 01-OCT-06:49 | 7771.71 | 32.85 | 291.00 | 307.50 | 2160.89 | 19.58 | 31.17 | 287.50 |
November | 254.83 | 0.50 | 0.48 | 01-NOV-07:49 | 5446.59 | 32.70 | 232.33 | 249.17 | 3010.29 | 29.73 | 184.83 | 230.33 |
December | 186.17 | 0.50 | 0.48 | 01-DEC-07:00 | 6700.65 | 38.32 | 183.83 | 225.50 | 6128.94 | 39.60 | 184.17 | 194.83 |
Annual Sum or Average | 3807.33 | 0.50 | 4433.62 | 22.81 | 1411.50 | 3894.33 | 2147.65 | 21.82 | 765.17 | 3562.50 | ||
Minimum of Months | 186.17 | 0.50 | 0.48 | 1972.64 | 14.42 | 0.00 | 225.50 | 1144.46 | 17.86 | 0.00 | 194.83 | |
Maximum of Months | 428.67 | 0.51 | 0.48 | 9023.97 | 38.32 | 291.00 | 411.50 | 6338.63 | 39.60 | 200.17 | 376.00 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_2_DAYLCTRL
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 214.17 | 0.52 | 0.48 | 01-JAN-09:39 | 2061.17 | 21.93 | 66.17 | 235.17 | 1073.26 | 22.33 | 76.83 | 199.50 |
February | 226.83 | 0.52 | 0.48 | 01-FEB-07:49 | 2543.05 | 22.98 | 78.50 | 246.83 | 1424.50 | 23.57 | 73.33 | 216.33 |
March | 334.33 | 0.50 | 0.48 | 01-MAR-07:00 | 3263.96 | 22.61 | 117.83 | 326.17 | 1413.72 | 22.21 | 68.00 | 291.67 |
April | 285.17 | 0.51 | 0.48 | 01-APR-06:49 | 3789.97 | 20.90 | 77.33 | 351.50 | 2301.90 | 23.12 | 65.17 | 322.17 |
May | 428.67 | 0.50 | 0.48 | 01-MAY-05:19 | 3937.82 | 21.70 | 135.67 | 408.00 | 1744.41 | 21.60 | 78.00 | 372.50 |
June | 400.67 | 0.50 | 0.48 | 01-JUN-04:00 | 3580.38 | 20.38 | 95.67 | 409.00 | 2012.99 | 22.38 | 78.00 | 383.33 |
July | 414.00 | 0.50 | 0.48 | 01-JUL-05:40 | 4496.25 | 22.03 | 124.33 | 419.33 | 2019.08 | 22.02 | 70.00 | 389.00 |
August | 410.83 | 0.50 | 0.48 | 01-AUG-05:40 | 3631.71 | 21.93 | 127.50 | 387.67 | 1676.12 | 21.98 | 72.33 | 363.33 |
September | 326.50 | 0.50 | 0.48 | 01-SEP-05:00 | 3649.18 | 21.96 | 96.67 | 334.67 | 2076.54 | 22.99 | 73.33 | 308.17 |
October | 325.17 | 0.51 | 0.48 | 01-OCT-06:40 | 2315.93 | 21.69 | 100.17 | 297.67 | 1274.42 | 22.59 | 77.67 | 270.50 |
November | 254.83 | 0.52 | 0.48 | 01-NOV-07:49 | 1795.48 | 21.03 | 82.17 | 238.83 | 971.46 | 22.03 | 74.33 | 204.00 |
December | 186.17 | 0.53 | 0.48 | 01-DEC-07:00 | 1614.36 | 21.56 | 64.17 | 206.50 | 880.39 | 22.97 | 66.83 | 145.67 |
Annual Sum or Average | 3807.33 | 0.51 | 3248.71 | 21.70 | 1166.17 | 3861.33 | 1645.43 | 22.39 | 873.83 | 3466.17 | ||
Minimum of Months | 186.17 | 0.50 | 0.48 | 1614.36 | 20.38 | 64.17 | 206.50 | 880.39 | 21.60 | 65.17 | 145.67 | |
Maximum of Months | 428.67 | 0.53 | 0.48 | 4496.25 | 22.98 | 135.67 | 419.33 | 2301.90 | 23.57 | 78.00 | 389.00 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_3_DAYLCTRL
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 214.17 | 0.55 | 0.48 | 01-JAN-09:00 | 737.38 | 12.02 | 0.00 | 218.17 | 468.53 | 15.65 | 0.00 | 157.00 |
February | 226.83 | 0.54 | 0.48 | 01-FEB-09:09 | 782.20 | 12.48 | 0.00 | 233.83 | 506.30 | 16.10 | 0.00 | 186.83 |
March | 334.33 | 0.51 | 0.48 | 01-MAR-08:20 | 1052.43 | 13.81 | 0.00 | 321.67 | 638.45 | 17.23 | 0.00 | 277.83 |
April | 285.17 | 0.50 | 0.48 | 01-APR-07:19 | 1253.89 | 15.04 | 0.00 | 351.67 | 804.09 | 18.52 | 13.33 | 309.67 |
May | 428.67 | 0.49 | 0.48 | 01-MAY-06:40 | 1403.87 | 16.22 | 29.33 | 417.67 | 830.20 | 19.48 | 39.33 | 386.33 |
June | 400.67 | 0.49 | 0.48 | 01-JUN-04:00 | 1696.48 | 19.58 | 84.83 | 417.17 | 1026.22 | 21.77 | 89.33 | 397.50 |
July | 414.00 | 0.49 | 0.48 | 01-JUL-05:40 | 1600.27 | 17.20 | 30.67 | 425.33 | 980.00 | 20.54 | 69.17 | 403.33 |
August | 410.83 | 0.50 | 0.48 | 01-AUG-05:00 | 1324.96 | 15.15 | 0.00 | 393.50 | 806.47 | 18.61 | 9.17 | 367.00 |
September | 326.50 | 0.50 | 0.48 | 01-SEP-06:19 | 1105.78 | 14.86 | 0.00 | 334.00 | 707.08 | 18.30 | 0.00 | 298.17 |
October | 325.17 | 0.52 | 0.48 | 01-OCT-07:30 | 863.71 | 12.87 | 0.00 | 287.67 | 533.43 | 16.37 | 0.00 | 243.17 |
November | 254.83 | 0.54 | 0.48 | 01-NOV-08:30 | 727.40 | 11.63 | 0.00 | 227.83 | 431.69 | 15.10 | 0.00 | 168.50 |
December | 186.17 | 0.57 | 0.48 | 01-DEC-09:00 | 539.36 | 10.34 | 0.00 | 184.83 | 353.36 | 14.15 | 0.00 | 88.83 |
Annual Sum or Average | 3807.33 | 0.51 | 1171.64 | 14.81 | 144.83 | 3813.33 | 720.23 | 18.13 | 220.33 | 3284.17 | ||
Minimum of Months | 186.17 | 0.49 | 0.48 | 539.36 | 10.34 | 0.00 | 184.83 | 353.36 | 14.15 | 0.00 | 88.83 | |
Maximum of Months | 428.67 | 0.57 | 0.48 | 1696.48 | 19.58 | 84.83 | 425.33 | 1026.22 | 21.77 | 89.33 | 403.33 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_4_DAYLCTRL
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 214.17 | 0.52 | 0.48 | 01-JAN-09:00 | 2234.93 | 23.76 | 84.50 | 233.17 | 1307.61 | 24.17 | 87.33 | 198.50 |
February | 226.83 | 0.52 | 0.48 | 01-FEB-09:09 | 2625.04 | 22.82 | 74.50 | 246.67 | 1458.07 | 23.29 | 66.67 | 218.33 |
March | 334.33 | 0.50 | 0.48 | 01-MAR-08:30 | 2769.31 | 21.02 | 94.17 | 328.17 | 1519.20 | 22.17 | 76.17 | 295.83 |
April | 285.17 | 0.50 | 0.48 | 02-APR-14:39 | 4924.94 | 21.93 | 84.50 | 353.50 | 2103.84 | 21.20 | 39.17 | 313.33 |
May | 428.67 | 0.50 | 0.48 | 01-MAY-06:00 | 2967.99 | 17.05 | 50.17 | 407.67 | 1658.29 | 18.10 | 0.00 | 379.00 |
June | 400.67 | 0.50 | 0.48 | 01-JUN-05:00 | 3785.46 | 17.52 | 50.33 | 409.33 | 1784.24 | 18.50 | 0.00 | 377.83 |
July | 414.00 | 0.49 | 0.48 | 01-JUL-06:10 | 4229.44 | 18.01 | 56.00 | 417.50 | 1914.32 | 18.73 | 2.17 | 389.67 |
August | 410.83 | 0.50 | 0.48 | 01-AUG-06:19 | 3529.74 | 19.56 | 84.33 | 390.83 | 2021.86 | 20.97 | 55.00 | 362.83 |
September | 326.50 | 0.50 | 0.48 | 01-SEP-06:00 | 3718.50 | 22.18 | 99.50 | 338.33 | 2184.66 | 23.40 | 75.00 | 312.83 |
October | 325.17 | 0.51 | 0.48 | 01-OCT-07:30 | 2825.66 | 22.00 | 112.33 | 297.83 | 1300.12 | 22.49 | 79.50 | 269.83 |
November | 254.83 | 0.52 | 0.48 | 01-NOV-08:30 | 1852.83 | 20.90 | 83.50 | 239.67 | 1023.16 | 21.82 | 70.33 | 205.00 |
December | 186.17 | 0.53 | 0.48 | 01-DEC-09:50 | 1703.49 | 20.82 | 56.33 | 209.33 | 983.66 | 22.75 | 57.50 | 143.50 |
Annual Sum or Average | 3807.33 | 0.51 | 3234.99 | 20.22 | 930.17 | 3872.00 | 1667.17 | 21.07 | 608.83 | 3466.50 | ||
Minimum of Months | 186.17 | 0.49 | 0.48 | 1703.49 | 17.05 | 50.17 | 209.33 | 983.66 | 18.10 | 0.00 | 143.50 | |
Maximum of Months | 428.67 | 0.53 | 0.48 | 4924.94 | 23.76 | 112.33 | 417.50 | 2184.66 | 24.17 | 87.33 | 389.67 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_1_DAYLCTRL
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 214.17 | 0.50 | 0.48 | 01-JAN-09:39 | 7623.01 | 37.16 | 205.17 | 246.50 | 6341.28 | 37.82 | 200.17 | 225.17 |
February | 226.83 | 0.50 | 0.48 | 01-FEB-07:00 | 9025.88 | 37.51 | 222.33 | 256.50 | 2719.41 | 26.29 | 105.67 | 241.67 |
March | 334.33 | 0.50 | 0.48 | 01-MAR-07:00 | 8236.34 | 29.59 | 250.67 | 329.50 | 1660.21 | 18.09 | 5.67 | 300.50 |
April | 285.17 | 0.51 | 0.48 | 01-APR-07:10 | 2560.38 | 14.80 | 0.00 | 349.50 | 1578.51 | 18.32 | 17.50 | 315.67 |
May | 428.67 | 0.51 | 0.48 | 01-MAY-06:40 | 1975.57 | 14.39 | 0.00 | 399.50 | 1146.24 | 17.84 | 0.00 | 361.17 |
June | 400.67 | 0.51 | 0.48 | 01-JUN-05:40 | 2023.01 | 14.88 | 0.00 | 401.17 | 1191.51 | 18.34 | 0.00 | 367.00 |
July | 414.00 | 0.50 | 0.48 | 01-JUL-05:00 | 2099.84 | 15.19 | 0.00 | 411.67 | 1248.15 | 18.66 | 1.83 | 376.00 |
August | 410.83 | 0.51 | 0.48 | 01-AUG-06:19 | 2312.14 | 14.89 | 0.00 | 382.83 | 1346.25 | 18.36 | 3.83 | 354.17 |
September | 326.50 | 0.50 | 0.48 | 01-SEP-06:19 | 3327.36 | 16.84 | 26.00 | 335.83 | 1696.45 | 18.72 | 27.83 | 309.33 |
October | 325.17 | 0.50 | 0.48 | 01-OCT-06:49 | 7774.38 | 32.84 | 291.00 | 307.50 | 2163.44 | 19.57 | 30.83 | 287.50 |
November | 254.83 | 0.50 | 0.48 | 01-NOV-07:49 | 5447.97 | 32.52 | 230.50 | 249.17 | 3012.62 | 29.72 | 184.83 | 230.33 |
December | 186.17 | 0.50 | 0.48 | 01-DEC-07:00 | 6675.76 | 37.06 | 176.67 | 224.67 | 6130.82 | 39.60 | 184.17 | 194.83 |
Annual Sum or Average | 3807.33 | 0.50 | 4435.10 | 22.71 | 1402.33 | 3894.33 | 2149.84 | 21.81 | 762.33 | 3563.33 | ||
Minimum of Months | 186.17 | 0.50 | 0.48 | 1975.57 | 14.39 | 0.00 | 224.67 | 1146.24 | 17.84 | 0.00 | 194.83 | |
Maximum of Months | 428.67 | 0.51 | 0.48 | 9025.88 | 37.51 | 291.00 | 411.67 | 6341.28 | 39.60 | 200.17 | 376.00 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_2_DAYLCTRL
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 214.17 | 0.52 | 0.48 | 01-JAN-09:39 | 2062.20 | 21.90 | 66.17 | 235.17 | 1074.47 | 22.32 | 76.83 | 199.67 |
February | 226.83 | 0.52 | 0.48 | 01-FEB-07:49 | 2544.17 | 22.95 | 78.50 | 246.83 | 1425.77 | 23.56 | 72.50 | 216.33 |
March | 334.33 | 0.50 | 0.48 | 01-MAR-07:00 | 3265.97 | 22.58 | 117.83 | 326.17 | 1415.40 | 22.20 | 67.67 | 292.00 |
April | 285.17 | 0.51 | 0.48 | 01-APR-06:49 | 3791.68 | 20.87 | 77.33 | 351.50 | 2303.66 | 23.10 | 65.17 | 322.50 |
May | 428.67 | 0.50 | 0.48 | 01-MAY-05:19 | 3940.27 | 21.68 | 135.67 | 408.00 | 1746.32 | 21.59 | 78.00 | 372.83 |
June | 400.67 | 0.50 | 0.48 | 01-JUN-04:00 | 3582.92 | 20.35 | 95.67 | 409.00 | 2015.10 | 22.36 | 78.00 | 383.50 |
July | 414.00 | 0.50 | 0.48 | 01-JUL-05:40 | 4498.47 | 22.01 | 124.33 | 419.33 | 2021.11 | 22.00 | 70.00 | 389.00 |
August | 410.83 | 0.50 | 0.48 | 01-AUG-05:40 | 3633.86 | 21.90 | 127.50 | 387.67 | 1678.02 | 21.97 | 72.33 | 363.33 |
September | 326.50 | 0.50 | 0.48 | 01-SEP-05:00 | 3650.89 | 21.93 | 96.67 | 334.67 | 2078.37 | 22.98 | 73.33 | 308.17 |
October | 325.17 | 0.51 | 0.48 | 01-OCT-06:40 | 2317.40 | 21.66 | 100.17 | 297.83 | 1275.78 | 22.57 | 77.33 | 270.50 |
November | 254.83 | 0.52 | 0.48 | 01-NOV-07:49 | 1796.83 | 21.01 | 82.17 | 238.83 | 972.62 | 22.01 | 74.00 | 204.00 |
December | 186.17 | 0.53 | 0.48 | 01-DEC-07:00 | 1615.02 | 21.53 | 64.17 | 206.50 | 881.20 | 22.96 | 66.17 | 145.83 |
Annual Sum or Average | 3807.33 | 0.51 | 3250.56 | 21.67 | 1166.17 | 3861.50 | 1647.11 | 22.38 | 871.33 | 3467.67 | ||
Minimum of Months | 186.17 | 0.50 | 0.48 | 1615.02 | 20.35 | 64.17 | 206.50 | 881.20 | 21.59 | 65.17 | 145.83 | |
Maximum of Months | 428.67 | 0.53 | 0.48 | 4498.47 | 22.95 | 135.67 | 419.33 | 2303.66 | 23.56 | 78.00 | 389.00 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_3_DAYLCTRL
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 214.17 | 0.55 | 0.48 | 01-JAN-09:00 | 737.97 | 11.99 | 0.00 | 218.17 | 469.14 | 15.64 | 0.00 | 157.17 |
February | 226.83 | 0.54 | 0.48 | 01-FEB-09:09 | 782.79 | 12.45 | 0.00 | 233.83 | 506.92 | 16.09 | 0.00 | 187.17 |
March | 334.33 | 0.51 | 0.48 | 01-MAR-08:20 | 1053.62 | 13.78 | 0.00 | 321.67 | 639.37 | 17.22 | 0.00 | 278.33 |
April | 285.17 | 0.50 | 0.48 | 01-APR-07:19 | 1254.93 | 15.01 | 0.00 | 351.67 | 805.07 | 18.50 | 13.00 | 309.67 |
May | 428.67 | 0.49 | 0.48 | 01-MAY-06:40 | 1405.46 | 16.19 | 29.33 | 417.67 | 831.39 | 19.46 | 38.67 | 386.33 |
June | 400.67 | 0.49 | 0.48 | 01-JUN-04:00 | 1698.14 | 19.55 | 84.83 | 417.17 | 1027.57 | 21.76 | 88.67 | 397.50 |
July | 414.00 | 0.49 | 0.48 | 01-JUL-05:40 | 1601.74 | 17.18 | 30.67 | 425.33 | 981.26 | 20.52 | 68.67 | 403.83 |
August | 410.83 | 0.50 | 0.48 | 01-AUG-05:00 | 1326.33 | 15.12 | 0.00 | 393.50 | 807.58 | 18.60 | 8.83 | 367.17 |
September | 326.50 | 0.50 | 0.48 | 01-SEP-06:19 | 1106.72 | 14.83 | 0.00 | 334.00 | 707.96 | 18.28 | 0.00 | 298.83 |
October | 325.17 | 0.52 | 0.48 | 01-OCT-07:30 | 864.59 | 12.84 | 0.00 | 287.67 | 534.17 | 16.35 | 0.00 | 243.50 |
November | 254.83 | 0.54 | 0.48 | 01-NOV-08:30 | 728.27 | 11.60 | 0.00 | 227.83 | 432.35 | 15.09 | 0.00 | 169.33 |
December | 186.17 | 0.57 | 0.48 | 01-DEC-09:00 | 539.71 | 10.31 | 0.00 | 185.17 | 353.79 | 14.13 | 0.00 | 88.83 |
Annual Sum or Average | 3807.33 | 0.51 | 1172.78 | 14.78 | 144.83 | 3813.67 | 721.19 | 18.12 | 217.83 | 3287.67 | ||
Minimum of Months | 186.17 | 0.49 | 0.48 | 539.71 | 10.31 | 0.00 | 185.17 | 353.79 | 14.13 | 0.00 | 88.83 | |
Maximum of Months | 428.67 | 0.57 | 0.48 | 1698.14 | 19.55 | 84.83 | 425.33 | 1027.57 | 21.76 | 88.67 | 403.83 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_4_DAYLCTRL
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 214.17 | 0.52 | 0.48 | 01-JAN-09:00 | 2236.00 | 23.73 | 84.50 | 233.17 | 1308.78 | 24.16 | 87.00 | 198.83 |
February | 226.83 | 0.52 | 0.48 | 01-FEB-09:09 | 2626.08 | 22.80 | 74.50 | 246.67 | 1459.32 | 23.28 | 66.17 | 218.33 |
March | 334.33 | 0.50 | 0.48 | 01-MAR-08:30 | 2771.30 | 21.00 | 94.17 | 328.17 | 1520.88 | 22.16 | 75.83 | 296.00 |
April | 285.17 | 0.50 | 0.48 | 02-APR-14:39 | 4926.78 | 21.90 | 84.50 | 353.50 | 2105.73 | 21.18 | 39.17 | 313.33 |
May | 428.67 | 0.50 | 0.48 | 01-MAY-06:00 | 2970.30 | 17.02 | 50.17 | 407.67 | 1660.09 | 18.08 | 0.00 | 379.33 |
June | 400.67 | 0.50 | 0.48 | 01-JUN-05:00 | 3787.82 | 17.49 | 50.33 | 409.33 | 1786.28 | 18.49 | 0.00 | 378.00 |
July | 414.00 | 0.49 | 0.48 | 01-JUL-06:10 | 4231.77 | 17.98 | 56.00 | 417.67 | 1916.42 | 18.71 | 2.17 | 389.67 |
August | 410.83 | 0.50 | 0.48 | 01-AUG-06:19 | 3532.01 | 19.53 | 84.33 | 391.00 | 2023.84 | 20.95 | 55.00 | 362.83 |
September | 326.50 | 0.50 | 0.48 | 01-SEP-06:00 | 3720.24 | 22.16 | 99.50 | 338.33 | 2186.37 | 23.39 | 75.00 | 313.00 |
October | 325.17 | 0.51 | 0.48 | 01-OCT-07:30 | 2827.12 | 21.98 | 112.33 | 297.83 | 1301.51 | 22.48 | 79.50 | 270.00 |
November | 254.83 | 0.52 | 0.48 | 01-NOV-08:30 | 1854.15 | 20.88 | 83.50 | 239.67 | 1024.32 | 21.81 | 70.33 | 205.00 |
December | 186.17 | 0.53 | 0.48 | 01-DEC-09:50 | 1704.09 | 20.79 | 56.33 | 209.33 | 984.43 | 22.74 | 57.17 | 143.67 |
Annual Sum or Average | 3807.33 | 0.51 | 3236.83 | 20.19 | 930.17 | 3872.33 | 1668.84 | 21.05 | 607.33 | 3468.00 | ||
Minimum of Months | 186.17 | 0.49 | 0.48 | 1704.09 | 17.02 | 50.17 | 209.33 | 984.43 | 18.08 | 0.00 | 143.67 | |
Maximum of Months | 428.67 | 0.53 | 0.48 | 4926.78 | 23.73 | 112.33 | 417.67 | 2186.37 | 24.16 | 87.00 | 389.67 |
Report: CoilReportMonthly
For: VAV_BOT WITH REHEAT HEATING COIL
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.193754E+11 | 110819.18 | 30-JAN-07:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.216457E+11 | 115105.64 | 02-FEB-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.293809E+10 | 71130.31 | 08-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.101118E+10 | 58901.93 | 03-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.104490E+09 | 28189.70 | 02-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 25271107.16 | 14255.32 | 03-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.180856E+09 | 37184.84 | 29-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.704508E+09 | 41720.21 | 28-OCT-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.239199E+10 | 78481.03 | 24-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.537070E+10 | 79505.18 | 22-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.537482E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.216457E+11 | 115105.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_BOTTOM VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 63070432.37 | 34247.39 | 30-JAN-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.148270E+09 | 34374.58 | 06-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.211340E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.148270E+09 | 34374.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.705594E+10 | 17584.35 | 30-JAN-08:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.416370E+10 | 19811.27 | 02-FEB-08:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.581240E+09 | 16638.98 | 17-MAR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 39643107.09 | 15278.54 | 03-APR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 595520.05 | 240.30 | 30-SEP-06:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 3421090.39 | 836.55 | 28-OCT-05:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.924144E+09 | 16683.41 | 13-NOV-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.261939E+10 | 16624.96 | 04-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.153881E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.705594E+10 | 19811.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.525900E+10 | 19323.77 | 14-JAN-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.318009E+10 | 19343.44 | 09-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.853330E+09 | 19365.04 | 17-MAR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.173465E+09 | 18809.69 | 03-APR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 11714888.37 | 3077.39 | 30-SEP-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 82875792.40 | 6505.40 | 27-OCT-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.115704E+10 | 19368.02 | 13-NOV-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.312635E+10 | 19347.19 | 04-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.138439E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.525900E+10 | 19368.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.558046E+10 | 25668.97 | 14-JAN-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.294919E+10 | 25825.73 | 23-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.977163E+09 | 25849.68 | 15-MAR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.193770E+09 | 24082.10 | 04-APR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 500457.81 | 443.38 | 02-MAY-05:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 20939108.91 | 8966.15 | 30-SEP-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 89137892.08 | 15862.81 | 27-OCT-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.118105E+10 | 25845.09 | 10-NOV-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.336713E+10 | 25702.64 | 04-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.143593E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.558046E+10 | 25849.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.375600E+10 | 18755.07 | 30-JAN-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.171905E+10 | 18714.74 | 28-FEB-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 94846724.68 | 18692.66 | 06-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 2063609.52 | 7290.46 | 03-APR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 1475473.34 | 373.90 | 30-SEP-06:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.261953E+09 | 18691.88 | 28-NOV-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.580744E+09 | 18712.14 | 09-DEC-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.641613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.375600E+10 | 18755.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV_MID WITH REHEAT HEATING COIL
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.245052E+12 | 1191139.34 | 30-JAN-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.231396E+12 | 1217582.01 | 02-FEB-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.345361E+11 | 923775.68 | 21-MAR-10:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.197984E+11 | 725016.00 | 21-APR-12:35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.160087E+10 | 316673.92 | 02-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.505971E+09 | 177701.48 | 03-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 22712.32 | 43.95 | 24-JUL-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 32106182.68 | 28296.69 | 16-AUG-06:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.211163E+10 | 380409.54 | 29-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.122859E+11 | 474457.42 | 23-OCT-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.376613E+11 | 775511.04 | 24-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.585964E+11 | 796317.99 | 22-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.643577E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 22712.32 | 43.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.245052E+12 | 1217582.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_MID VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.521259E+11 | 684085.46 | 02-JAN-05:24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.237505E+11 | 682939.53 | 06-FEB-06:14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.366175E+10 | 683301.12 | 06-MAR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.523681E+09 | 680327.39 | 03-APR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.961850E+10 | 683344.55 | 27-NOV-05:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.194534E+11 | 683776.39 | 26-DEC-06:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.109134E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.521259E+11 | 684085.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.185101E+12 | 177336.05 | 30-JAN-08:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.117217E+12 | 200933.07 | 02-FEB-09:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.561195E+11 | 159026.81 | 13-MAR-05:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.161798E+11 | 166394.95 | 20-APR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.661756E+09 | 165988.47 | 03-MAY-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 10613935.42 | 33582.28 | 02-JUN-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.189505E+10 | 165488.06 | 25-SEP-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.120245E+11 | 171584.37 | 20-OCT-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.655617E+11 | 171207.67 | 04-NOV-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.133770E+12 | 159552.46 | 27-DEC-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.588541E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.185101E+12 | 200933.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.122504E+12 | 224833.53 | 18-JAN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.750592E+11 | 223941.77 | 06-FEB-05:24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.375248E+11 | 224801.50 | 07-MAR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.138377E+11 | 223913.81 | 03-APR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.328440E+09 | 219894.01 | 02-MAY-04:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.112975E+09 | 40561.43 | 02-JUN-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.190907E+10 | 204185.81 | 30-SEP-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.103046E+11 | 222659.96 | 30-OCT-04:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.491289E+11 | 224211.12 | 20-NOV-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.942305E+11 | 224875.71 | 14-DEC-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.404940E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.122504E+12 | 224875.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.122162E+12 | 242814.04 | 30-JAN-07:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.684093E+11 | 242193.24 | 02-FEB-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.384724E+11 | 241736.84 | 07-MAR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.134454E+11 | 240927.13 | 03-APR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.625347E+09 | 238700.25 | 02-MAY-04:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 27689141.39 | 36418.32 | 02-JUN-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.149413E+10 | 238722.80 | 30-SEP-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.703424E+10 | 238726.88 | 27-OCT-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.459074E+11 | 241498.49 | 20-NOV-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.982224E+11 | 241814.44 | 14-DEC-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.395800E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.122162E+12 | 242814.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.113205E+12 | 238592.29 | 03-JAN-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.676456E+11 | 238665.02 | 21-FEB-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.346834E+11 | 237801.99 | 06-MAR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.104427E+11 | 238665.74 | 03-APR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.636786E+09 | 173577.50 | 02-MAY-04:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.125244E+09 | 47485.21 | 02-JUN-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.229702E+10 | 233560.66 | 30-SEP-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.908175E+10 | 236318.97 | 16-OCT-04:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.422975E+11 | 238651.34 | 13-NOV-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.818308E+11 | 238676.96 | 04-DEC-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.362245E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.113205E+12 | 238676.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV_TOP WITH REHEAT HEATING COIL
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.313097E+11 | 124001.85 | 30-JAN-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.257894E+11 | 124559.68 | 02-FEB-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.294869E+10 | 73543.58 | 08-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.871263E+09 | 59872.07 | 03-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.113066E+09 | 33107.35 | 02-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 47608787.40 | 19004.09 | 03-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 1902.11 | 6.34 | 24-JUL-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 1970283.49 | 2903.10 | 17-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.176239E+09 | 39962.65 | 29-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.547301E+09 | 49083.32 | 23-OCT-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.477940E+10 | 79378.78 | 24-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.118479E+11 | 80993.55 | 22-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.784325E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 1902.11 | 6.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.313097E+11 | 124559.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_TOP VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.195416E+11 | 86092.85 | 17-JAN-05:34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.128236E+11 | 86139.76 | 14-FEB-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.523727E+10 | 86097.60 | 07-MAR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.160992E+10 | 85804.32 | 03-APR-04:34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 35679492.86 | 9868.74 | 30-SEP-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.110249E+10 | 85771.04 | 16-OCT-04:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.751341E+10 | 86404.77 | 20-NOV-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.139637E+11 | 86134.38 | 30-DEC-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.618276E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.195416E+11 | 86404.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.257191E+11 | 22089.37 | 30-JAN-09:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.176338E+11 | 24717.41 | 02-FEB-09:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.981462E+10 | 19825.17 | 03-MAR-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.386545E+10 | 19865.38 | 24-APR-04:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.318967E+09 | 19739.14 | 02-MAY-04:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 90596926.93 | 19788.85 | 05-JUN-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 1045345.75 | 1348.98 | 07-AUG-05:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.805185E+09 | 19741.16 | 30-SEP-04:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.347911E+10 | 19943.27 | 23-OCT-05:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.115164E+11 | 19878.86 | 20-NOV-05:44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.204879E+11 | 19824.41 | 04-DEC-04:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.937322E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.257191E+11 | 24717.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.166216E+11 | 22580.49 | 18-JAN-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.108448E+11 | 22515.15 | 11-FEB-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.593816E+10 | 22583.96 | 10-MAR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.262227E+10 | 22545.35 | 24-APR-04:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.166524E+09 | 22435.35 | 02-MAY-04:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 94435915.21 | 10915.47 | 02-JUN-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 1498876.95 | 1469.17 | 07-AUG-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.521235E+09 | 22415.08 | 27-SEP-04:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.219783E+10 | 22591.69 | 16-OCT-04:32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.778804E+10 | 22578.76 | 17-NOV-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.136612E+11 | 22587.70 | 30-DEC-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.604575E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.166216E+11 | 22591.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.183866E+11 | 27318.71 | 31-JAN-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.113553E+11 | 30226.13 | 02-FEB-07:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.707728E+10 | 25897.83 | 03-MAR-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.325039E+10 | 25892.09 | 05-APR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.312264E+09 | 25743.47 | 02-MAY-04:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.108742E+09 | 20452.92 | 03-JUN-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.607606E+09 | 25765.21 | 30-SEP-04:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.209332E+10 | 25943.42 | 16-OCT-04:14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.843073E+10 | 25894.28 | 16-NOV-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.156208E+11 | 25888.56 | 18-DEC-04:23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.672430E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.183866E+11 | 30226.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.158990E+11 | 25094.38 | 18-JAN-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.977813E+10 | 24979.49 | 11-FEB-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.559736E+10 | 24941.57 | 18-MAR-04:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.215366E+10 | 24951.70 | 29-APR-04:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.245181E+09 | 24797.32 | 02-MAY-04:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 92191811.54 | 10838.15 | 02-JUN-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.624501E+09 | 24801.12 | 30-SEP-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.209263E+10 | 25105.16 | 23-OCT-04:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.671298E+10 | 24978.10 | 30-NOV-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.118767E+11 | 24973.06 | 15-DEC-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.550724E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.158990E+11 | 25105.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CAV_BAS HEATING COIL
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.998648E+09 | 29814.35 | 31-JAN-07:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.347387E+10 | 48203.31 | 02-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.447252E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.347387E+10 | 48203.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BASEMENT HEATING COIL
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BOT HEATING COIL
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER MID HEATING COIL
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER TOP HEATING COIL
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BOT_SUPPHEATCOIL
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER MID_SUPPHEATCOIL
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER TOP_SUPPHEATCOIL
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV_BOT WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 9072185.77 | 9072185.77 | 6820.68 | 12-JAN-15:50 | 6820.68 | 0.00 |
February | 0.00 | 0.00 | 30375945.91 | 30375945.91 | 20986.37 | 17-FEB-16:30 | 20986.37 | 0.00 |
March | 0.00 | 0.00 | 0.756454E+09 | 0.756454E+09 | 24746.07 | 28-MAR-14:40 | 24746.07 | 0.00 |
April | 0.00 | 0.00 | 0.151676E+11 | 0.137049E+11 | 193752.86 | 18-APR-09:30 | 115217.81 | 0.12 |
May | 0.00 | 0.00 | 0.328973E+11 | 0.286590E+11 | 173213.39 | 30-MAY-11:00 | 106465.67 | 0.28 |
June | 0.00 | 0.00 | 0.992520E+11 | 0.782513E+11 | 264450.79 | 26-JUN-05:03 | 105504.27 | 0.54 |
July | 0.00 | 0.00 | 0.147030E+12 | 0.103351E+12 | 251431.88 | 03-JUL-08:50 | 116930.54 | 0.72 |
August | 0.00 | 0.00 | 0.149682E+12 | 0.106036E+12 | 345947.82 | 04-AUG-05:03 | 109532.29 | 0.70 |
September | 0.00 | 0.00 | 0.487271E+11 | 0.459849E+11 | 202661.59 | 11-SEP-09:50 | 119917.30 | 0.29 |
October | 0.00 | 0.00 | 0.425736E+10 | 0.425736E+10 | 89851.30 | 20-OCT-15:00 | 89851.30 | 0.04 |
November | 0.00 | 0.00 | 0.433232E+09 | 0.433232E+09 | 28302.27 | 03-NOV-13:40 | 28302.27 | 0.01 |
December | 0.00 | 0.00 | 21023358.35 | 21023358.35 | 12793.81 | 07-DEC-13:30 | 12793.81 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.498263E+12 | 0.381495E+12 | 0.23 | |||
Minimum of Months | 0.00 | 0.00 | 9072185.77 | 9072185.77 | 6820.68 | 6820.68 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.149682E+12 | 0.106036E+12 | 345947.82 | 119917.30 | 0.72 |
Report: CoilReportMonthly
For: VAV_MID WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 29315269.17 | 29315269.17 | 54938.69 | 12-JAN-14:40 | 54938.69 | 0.00 |
February | 0.00 | 0.00 | 27029005.22 | 27029005.22 | 13290.72 | 17-FEB-16:20 | 13290.72 | 0.00 |
March | 0.00 | 0.00 | 0.522420E+10 | 0.522420E+10 | 191380.67 | 21-MAR-10:40 | 191380.67 | 0.00 |
April | 0.00 | 0.00 | 0.112402E+12 | 0.100644E+12 | 1417926.50 | 18-APR-09:25 | 866610.00 | 0.10 |
May | 0.00 | 0.00 | 0.279891E+12 | 0.245636E+12 | 1396174.04 | 30-MAY-11:00 | 874972.56 | 0.28 |
June | 0.00 | 0.00 | 0.833663E+12 | 0.666256E+12 | 2360031.57 | 26-JUN-04:12 | 926135.11 | 0.51 |
July | 0.00 | 0.00 | 0.114616E+13 | 0.829211E+12 | 2078522.09 | 26-JUL-05:03 | 999571.75 | 0.61 |
August | 0.00 | 0.00 | 0.109160E+13 | 0.802374E+12 | 3402686.59 | 04-AUG-05:03 | 1073393.51 | 0.58 |
September | 0.00 | 0.00 | 0.425327E+12 | 0.401357E+12 | 1645837.54 | 11-SEP-09:40 | 979371.50 | 0.28 |
October | 0.00 | 0.00 | 0.325785E+11 | 0.325785E+11 | 750682.04 | 20-OCT-15:00 | 750682.04 | 0.04 |
November | 0.00 | 0.00 | 0.360259E+10 | 0.360259E+10 | 236915.10 | 03-NOV-13:40 | 236915.10 | 0.00 |
December | 0.00 | 0.00 | 8640854.02 | 8640854.02 | 6258.19 | 02-DEC-14:20 | 6258.19 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.393051E+13 | 0.308695E+13 | 0.20 | |||
Minimum of Months | 0.00 | 0.00 | 8640854.02 | 8640854.02 | 6258.19 | 6258.19 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.114616E+13 | 0.829211E+12 | 3402686.59 | 1073393.51 | 0.61 |
Report: CoilReportMonthly
For: VAV_TOP WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 3479025.07 | 3479025.07 | 1749.41 | 25-JAN-06:04 | 1749.41 | 0.00 |
February | 0.00 | 0.00 | 4713850.52 | 4713850.52 | 842.62 | 08-FEB-11:20 | 842.62 | 0.00 |
March | 0.00 | 0.00 | 0.452687E+09 | 0.452687E+09 | 17733.46 | 25-MAR-15:00 | 17733.46 | 0.00 |
April | 0.00 | 0.00 | 0.121570E+11 | 0.108027E+11 | 209257.50 | 16-APR-15:41 | 152316.96 | 0.10 |
May | 0.00 | 0.00 | 0.297247E+11 | 0.261336E+11 | 148133.49 | 30-MAY-12:00 | 104083.03 | 0.27 |
June | 0.00 | 0.00 | 0.912012E+11 | 0.731301E+11 | 242633.38 | 26-JUN-04:12 | 95173.34 | 0.50 |
July | 0.00 | 0.00 | 0.124036E+12 | 0.892989E+11 | 266083.58 | 04-JUL-17:21 | 144682.34 | 0.60 |
August | 0.00 | 0.00 | 0.114658E+12 | 0.852281E+11 | 347748.56 | 03-AUG-05:03 | 120028.97 | 0.57 |
September | 0.00 | 0.00 | 0.440558E+11 | 0.416307E+11 | 175908.34 | 11-SEP-10:00 | 107194.82 | 0.28 |
October | 0.00 | 0.00 | 0.279138E+10 | 0.279138E+10 | 73234.38 | 20-OCT-15:00 | 73234.38 | 0.04 |
November | 0.00 | 0.00 | 0.197745E+09 | 0.197745E+09 | 17530.07 | 03-NOV-14:00 | 17530.07 | 0.00 |
December | 0.00 | 0.00 | 2632868.35 | 2632868.35 | 1112.30 | 12-DEC-23:53 | 1112.30 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.419285E+12 | 0.329677E+12 | 0.20 | |||
Minimum of Months | 0.00 | 0.00 | 2632868.35 | 2632868.35 | 842.62 | 842.62 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.124036E+12 | 0.892989E+11 | 347748.56 | 152316.96 | 0.60 |
Report: CoilReportMonthly
For: CAV_BAS COOLING COIL
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 83777.90 | 83777.90 | 107.29 | 02-JAN-16:40 | 107.29 | 0.00 |
February | 0.00 | 0.00 | 367811.27 | 367811.27 | 425.89 | 09-FEB-08:30 | 425.89 | 0.00 |
March | 0.00 | 0.00 | 26256360.24 | 26256360.24 | 5855.96 | 28-MAR-15:00 | 5855.96 | 0.00 |
April | 0.00 | 0.00 | 0.574840E+10 | 0.538173E+10 | 82590.97 | 18-APR-09:20 | 58242.22 | 0.06 |
May | 0.00 | 0.00 | 0.145144E+11 | 0.134037E+11 | 109683.37 | 30-MAY-11:00 | 68872.78 | 0.17 |
June | 0.00 | 0.00 | 0.501647E+11 | 0.414531E+11 | 172459.73 | 26-JUN-07:20 | 72080.71 | 0.40 |
July | 0.00 | 0.00 | 0.731938E+11 | 0.553452E+11 | 183753.85 | 04-JUL-17:29 | 102358.10 | 0.48 |
August | 0.00 | 0.00 | 0.777734E+11 | 0.581813E+11 | 200880.14 | 04-AUG-05:15 | 62715.98 | 0.50 |
September | 0.00 | 0.00 | 0.277808E+11 | 0.265798E+11 | 131978.81 | 11-SEP-09:00 | 73485.27 | 0.21 |
October | 0.00 | 0.00 | 0.188053E+10 | 0.187338E+10 | 53319.10 | 20-OCT-15:00 | 53319.10 | 0.02 |
November | 0.00 | 0.00 | 61208898.32 | 40910278.63 | 71031.87 | 09-NOV-05:12 | 42622.45 | 0.00 |
December | 0.00 | 0.00 | 126762.73 | 126762.73 | 124.15 | 15-DEC-13:10 | 124.15 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.251144E+12 | 0.202286E+12 | 0.16 | |||
Minimum of Months | 0.00 | 0.00 | 83777.90 | 83777.90 | 107.29 | 107.29 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.777734E+11 | 0.581813E+11 | 200880.14 | 102358.10 | 0.50 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BASEMENT COOLING COIL
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.595031E+10 | 0.595022E+10 | 2610.47 | 22-JAN-11:00 | 2610.47 | 0.00 |
February | 0.00 | 0.00 | 0.100733E+11 | 0.991145E+10 | 5127.24 | 20-FEB-17:43 | 5127.24 | 0.00 |
March | 0.00 | 0.00 | 0.169035E+11 | 0.161339E+11 | 124324.68 | 19-MAR-15:53 | 94629.67 | 0.00 |
April | 0.00 | 0.00 | 0.139867E+12 | 0.105300E+12 | 438586.94 | 18-APR-09:55 | 267115.47 | 0.00 |
May | 0.00 | 0.00 | 0.180099E+11 | 0.150271E+11 | 171118.86 | 30-MAY-14:10 | 126831.06 | 0.00 |
June | 0.00 | 0.00 | 0.233604E+12 | 0.169240E+12 | 467179.35 | 13-JUN-12:00 | 213815.15 | 0.00 |
July | 0.00 | 0.00 | 0.699123E+12 | 0.392450E+12 | 491902.06 | 26-JUL-19:00 | 159107.31 | 0.00 |
August | 0.00 | 0.00 | 0.881150E+12 | 0.498873E+12 | 483459.47 | 04-AUG-13:00 | 233650.78 | 0.00 |
September | 0.00 | 0.00 | 0.468914E+11 | 0.427932E+11 | 188273.03 | 11-SEP-10:50 | 126704.03 | 0.00 |
October | 0.00 | 0.00 | 0.116167E+11 | 0.113259E+11 | 128590.30 | 20-OCT-15:00 | 128590.30 | 0.00 |
November | 0.00 | 0.00 | 0.118511E+11 | 0.115945E+11 | 35107.17 | 03-NOV-14:00 | 31826.97 | 0.00 |
December | 0.00 | 0.00 | 0.150260E+11 | 0.150070E+11 | 5963.84 | 02-DEC-19:10 | 5609.60 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.209007E+13 | 0.129361E+13 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.595031E+10 | 0.595022E+10 | 2610.47 | 2610.47 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.881150E+12 | 0.498873E+12 | 491902.06 | 267115.47 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BOT COOLING COIL
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.193716E+10 | 0.193716E+10 | 2221.98 | 12-JAN-16:30 | 2221.98 | 0.00 |
February | 0.00 | 0.00 | 0.726866E+10 | 0.726866E+10 | 4657.26 | 24-FEB-17:00 | 4657.26 | 0.00 |
March | 0.00 | 0.00 | 0.146001E+11 | 0.145991E+11 | 7523.72 | 31-MAR-24:00 | 7523.72 | 0.00 |
April | 0.00 | 0.00 | 0.199062E+11 | 0.198720E+11 | 9135.66 | 16-APR-17:52 | 9135.66 | 0.00 |
May | 0.00 | 0.00 | 0.588705E+10 | 0.576820E+10 | 4214.80 | 31-MAY-23:10 | 4094.64 | 0.00 |
June | 0.00 | 0.00 | 0.111715E+11 | 0.109160E+11 | 6014.31 | 30-JUN-23:05 | 5958.66 | 0.00 |
July | 0.00 | 0.00 | 0.168711E+11 | 0.165148E+11 | 7857.82 | 31-JUL-24:00 | 7857.82 | 0.00 |
August | 0.00 | 0.00 | 0.219404E+11 | 0.215938E+11 | 9326.77 | 04-AUG-17:07 | 8693.22 | 0.00 |
September | 0.00 | 0.00 | 0.575813E+10 | 0.567373E+10 | 3607.27 | 30-SEP-24:00 | 3607.27 | 0.00 |
October | 0.00 | 0.00 | 0.102315E+11 | 0.102215E+11 | 5612.47 | 31-OCT-24:00 | 5612.47 | 0.00 |
November | 0.00 | 0.00 | 0.139936E+11 | 0.139776E+11 | 6794.65 | 05-NOV-16:17 | 6794.65 | 0.00 |
December | 0.00 | 0.00 | 0.186451E+11 | 0.186451E+11 | 8006.44 | 01-DEC-16:10 | 8006.44 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.148211E+12 | 0.146988E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.193716E+10 | 0.193716E+10 | 2221.98 | 2221.98 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.219404E+11 | 0.215938E+11 | 9326.77 | 9135.66 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER MID COOLING COIL
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.248695E+10 | 0.248695E+10 | 18236.71 | 12-JAN-16:40 | 18236.71 | 0.00 |
February | 0.00 | 0.00 | 0.465433E+11 | 0.465433E+11 | 42077.58 | 24-FEB-17:00 | 42077.58 | 0.00 |
March | 0.00 | 0.00 | 0.117867E+12 | 0.117857E+12 | 66061.16 | 31-MAR-23:20 | 66061.16 | 0.00 |
April | 0.00 | 0.00 | 0.176123E+12 | 0.175780E+12 | 85472.73 | 15-APR-18:10 | 85141.16 | 0.00 |
May | 0.00 | 0.00 | 0.496606E+11 | 0.484908E+11 | 40093.83 | 31-MAY-23:10 | 38871.52 | 0.00 |
June | 0.00 | 0.00 | 0.103303E+12 | 0.100767E+12 | 58377.22 | 30-JUN-23:05 | 57814.68 | 0.00 |
July | 0.00 | 0.00 | 0.159395E+12 | 0.155850E+12 | 74660.85 | 31-JUL-24:00 | 74660.85 | 0.00 |
August | 0.00 | 0.00 | 0.206314E+12 | 0.202854E+12 | 87836.10 | 01-AUG-18:30 | 84576.03 | 0.00 |
September | 0.00 | 0.00 | 0.482370E+11 | 0.474086E+11 | 32298.39 | 04-SEP-17:43 | 32152.30 | 0.00 |
October | 0.00 | 0.00 | 0.815834E+11 | 0.814825E+11 | 47887.83 | 31-OCT-23:30 | 47887.83 | 0.00 |
November | 0.00 | 0.00 | 0.109602E+12 | 0.109441E+12 | 61386.30 | 03-NOV-16:00 | 61001.06 | 0.00 |
December | 0.00 | 0.00 | 0.146696E+12 | 0.146696E+12 | 72528.96 | 01-DEC-16:10 | 72528.96 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.124781E+13 | 0.123566E+13 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.248695E+10 | 0.248695E+10 | 18236.71 | 18236.71 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.206314E+12 | 0.202854E+12 | 87836.10 | 85141.16 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER TOP COOLING COIL
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.128632E+09 | 0.128632E+09 | 1739.05 | 12-JAN-16:40 | 1739.05 | 0.00 |
February | 0.00 | 0.00 | 0.329231E+10 | 0.329231E+10 | 4229.75 | 24-FEB-17:00 | 4229.75 | 0.00 |
March | 0.00 | 0.00 | 0.104674E+11 | 0.104664E+11 | 6146.51 | 31-MAR-23:10 | 6146.51 | 0.00 |
April | 0.00 | 0.00 | 0.166136E+11 | 0.165795E+11 | 8803.73 | 16-APR-17:52 | 8803.73 | 0.00 |
May | 0.00 | 0.00 | 0.453993E+10 | 0.442359E+10 | 3991.86 | 31-MAY-23:10 | 3869.98 | 0.00 |
June | 0.00 | 0.00 | 0.101582E+11 | 0.990476E+10 | 5827.08 | 30-JUN-23:05 | 5770.51 | 0.00 |
July | 0.00 | 0.00 | 0.158942E+11 | 0.155401E+11 | 7368.97 | 31-JUL-24:00 | 7368.97 | 0.00 |
August | 0.00 | 0.00 | 0.205221E+11 | 0.201767E+11 | 8865.83 | 04-AUG-16:35 | 8259.04 | 0.00 |
September | 0.00 | 0.00 | 0.428272E+10 | 0.420044E+10 | 3282.87 | 06-SEP-17:30 | 3055.07 | 0.00 |
October | 0.00 | 0.00 | 0.671026E+10 | 0.670038E+10 | 4664.34 | 11-OCT-16:50 | 4601.67 | 0.00 |
November | 0.00 | 0.00 | 0.934680E+10 | 0.933088E+10 | 6142.13 | 03-NOV-16:00 | 6103.73 | 0.00 |
December | 0.00 | 0.00 | 0.130127E+11 | 0.130127E+11 | 7141.05 | 01-DEC-16:10 | 7141.05 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.114969E+12 | 0.113756E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.128632E+09 | 0.128632E+09 | 1739.05 | 1739.05 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.205221E+11 | 0.201767E+11 | 8865.83 | 8803.73 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:02 | 373611.28 | 2863880.51 | 30-JAN-07:02 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 290516.59 | 2858859.26 | 02-FEB-07:02 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 91355.26 | 2089523.17 | 07-MAR-06:01 |
April | 0.00 | 0.00 | 01-APR-00:10 | 34402.36 | 1927689.98 | 03-APR-05:01 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 1895.27 | 1559900.23 | 02-MAY-04:11 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 477.26 | 238739.65 | 02-JUN-05:03 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.01 | 37.07 | 24-JUL-06:10 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 14.77 | 26212.05 | 16-AUG-06:15 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 4844.17 | 1537769.58 | 30-SEP-04:01 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 23362.75 | 1874152.86 | 16-OCT-04:11 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 115762.19 | 2026568.60 | 13-NOV-06:01 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 217745.66 | 2280148.89 | 18-DEC-05:01 |
Annual Sum or Average | 0.00 | 95196.11 | ||||
Minimum of Months | 0.00 | 0.00 | 0.01 | 37.07 | ||
Maximum of Months | 0.00 | 0.00 | 373611.28 | 2863880.51 |
Report: PlantLoopDemandReportMonthly
For: COOLSYS1_SUPPLY
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 614.46 | 7946.17 | 12-JAN-14:40 | 0.00 | 0.00 | 01-JAN-00:02 |
February | 453.70 | 12263.64 | 17-FEB-16:30 | 0.00 | 0.00 | 01-FEB-00:03 |
March | 3090.36 | 216788.82 | 25-MAR-15:00 | 0.00 | 0.00 | 01-MAR-00:05 |
April | 58147.33 | 2054305.85 | 18-APR-09:05 | 0.00 | 0.00 | 01-APR-00:10 |
May | 138735.35 | 1832607.15 | 30-MAY-11:00 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 425932.97 | 2691029.02 | 26-JUN-07:50 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 575588.73 | 2557779.33 | 07-JUL-11:00 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 554621.25 | 3815992.82 | 04-AUG-07:20 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 216907.44 | 2102867.85 | 11-SEP-09:40 | 0.00 | 0.00 | 01-SEP-00:03 |
October | 16357.09 | 951674.01 | 20-OCT-15:00 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 2236.44 | 281291.88 | 03-NOV-13:20 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 270.42 | 12849.72 | 15-DEC-13:10 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 167334.34 | 0.00 | ||||
Minimum of Months | 270.42 | 7946.17 | 0.00 | 0.00 | ||
Maximum of Months | 575588.73 | 3815992.82 | 0.00 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: COOLSYS1_DEMAND
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 1.51 | 2144.04 | 12-JAN-14:40 | 0.00 | 0.00 | 01-JAN-00:02 |
February | 6.74 | 7409.20 | 17-FEB-16:30 | 0.00 | 0.00 | 01-FEB-00:03 |
March | 2342.67 | 213455.35 | 25-MAR-15:00 | 0.00 | 0.00 | 01-MAR-00:05 |
April | 56594.02 | 1848835.45 | 16-APR-15:22 | 0.00 | 0.00 | 01-APR-00:10 |
May | 135957.11 | 1822720.57 | 30-MAY-11:00 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 421457.85 | 4865442.14 | 26-JUN-04:12 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 569461.62 | 4702643.78 | 26-JUL-05:03 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 547957.89 | 5126131.37 | 04-AUG-04:12 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 214513.51 | 2935828.81 | 11-SEP-05:03 | 0.00 | 0.00 | 01-SEP-00:03 |
October | 15471.89 | 947308.54 | 20-OCT-14:50 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 1701.41 | 300252.43 | 09-NOV-06:03 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 7.86 | 7803.26 | 15-DEC-13:10 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 165028.52 | 0.00 | ||||
Minimum of Months | 1.51 | 2144.04 | 0.00 | 0.00 | ||
Maximum of Months | 569461.62 | 5126131.37 | 0.00 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SINGLE WATER PLANT LOOP
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 9153.05 | 34805.27 | 12-JAN-16:40 | 0.00 | 0.00 | 01-JAN-00:02 |
February | 39424.50 | 71357.53 | 24-FEB-17:00 | 0.00 | 0.00 | 01-FEB-00:03 |
March | 79729.04 | 389714.02 | 19-MAR-16:00 | 0.00 | 0.00 | 01-MAR-00:05 |
April | 232376.22 | 1642880.19 | 15-APR-15:00 | 0.00 | 0.00 | 01-APR-00:10 |
May | 83898.71 | 953126.12 | 31-MAY-15:00 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 413909.89 | 1466087.97 | 13-JUN-12:10 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 804590.56 | 1737078.24 | 26-JUL-15:10 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 936865.33 | 2000638.08 | 04-AUG-16:00 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 161228.64 | 1086374.59 | 06-SEP-15:00 | 0.00 | 0.00 | 01-SEP-00:03 |
October | 58830.16 | 609662.95 | 20-OCT-15:00 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 73866.88 | 134285.08 | 03-NOV-14:30 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 94757.32 | 119923.49 | 01-DEC-16:10 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 251090.09 | 0.00 | ||||
Minimum of Months | 9153.05 | 34805.27 | 0.00 | 0.00 | ||
Maximum of Months | 936865.33 | 2000638.08 | 0.00 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:02 | 17647.13 | 60110.28 | 31-JAN-12:50 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 18074.50 | 60544.73 | 16-FEB-12:35 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 18941.08 | 60409.07 | 01-MAR-12:50 |
April | 0.00 | 0.00 | 01-APR-00:10 | 17203.45 | 58721.77 | 03-APR-11:40 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 16771.73 | 55979.72 | 01-MAY-11:40 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 16079.94 | 52372.81 | 01-JUN-11:50 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 14149.35 | 48970.71 | 03-JUL-11:30 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 14988.08 | 47056.08 | 01-AUG-11:20 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 14315.07 | 48150.96 | 29-SEP-12:00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 14948.73 | 51196.84 | 31-OCT-11:40 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 16084.27 | 54727.82 | 30-NOV-12:50 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 16496.82 | 57851.55 | 29-DEC-12:30 |
Annual Sum or Average | 0.00 | 16298.08 | ||||
Minimum of Months | 0.00 | 0.00 | 14149.35 | 47056.08 | ||
Maximum of Months | 0.00 | 0.00 | 18941.08 | 60544.73 |
Report: PlantLoopDemandReportMonthly
For: TOWERWATERSYS
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 31.09 | 15676.30 | 12-JAN-14:00 | 4217.93 | 198870.42 | 22-JAN-15:52 |
February | 21.68 | 10861.74 | 24-FEB-18:05 | 3317.91 | 181889.61 | 11-FEB-04:09 |
March | 2393.23 | 280596.39 | 25-MAR-15:00 | 4847.58 | 190187.75 | 23-MAR-04:16 |
April | 92621.07 | 4120151.45 | 18-APR-09:45 | 4321.00 | 183125.41 | 04-APR-15:10 |
May | 195039.25 | 3518446.03 | 30-MAY-13:10 | 955.53 | 155775.03 | 02-MAY-05:40 |
June | 807080.54 | 6479930.78 | 26-JUN-07:50 | 422.01 | 118157.67 | 02-JUN-06:00 |
July | 1107724.47 | 7161383.85 | 26-JUL-15:00 | 228.78 | 56567.06 | 22-JUL-07:20 |
August | 1068495.71 | 8323552.29 | 04-AUG-07:20 | 462.02 | 91937.80 | 07-AUG-07:40 |
September | 309914.82 | 4266163.84 | 11-SEP-09:40 | 710.68 | 126992.25 | 27-SEP-10:40 |
October | 18092.48 | 1097104.99 | 20-OCT-15:00 | 2994.70 | 169536.85 | 16-OCT-06:20 |
November | 1733.63 | 359616.98 | 03-NOV-13:20 | 3330.45 | 176364.70 | 25-NOV-21:22 |
December | 15.65 | 17390.54 | 26-DEC-07:20 | 2101.82 | 187181.40 | 12-DEC-01:32 |
Annual Sum or Average | 302703.17 | 2319.14 | ||||
Minimum of Months | 15.65 | 10861.74 | 228.78 | 56567.06 | ||
Maximum of Months | 1107724.47 | 8323552.29 | 4847.58 | 198870.42 |
Report: FanReportMonthly
For: CAV_BAS FAN
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.146947E+11 | 0.76 | 10579.36 | 02-JAN-05:01 | 1.45 |
February | 0.137966E+11 | 0.79 | 10579.36 | 01-FEB-06:01 | 1.47 |
March | 0.165447E+11 | 0.85 | 10579.36 | 01-MAR-06:02 | 1.46 |
April | 0.152070E+11 | 0.81 | 10579.36 | 01-APR-04:01 | 1.46 |
May | 0.162335E+11 | 0.83 | 10579.36 | 01-MAY-04:12 | 1.46 |
June | 0.162552E+11 | 0.85 | 10579.36 | 01-JUN-04:12 | 1.45 |
July | 0.162850E+11 | 0.83 | 10579.36 | 01-JUL-04:12 | 1.45 |
August | 0.176937E+11 | 0.90 | 10579.36 | 01-AUG-04:12 | 1.45 |
September | 0.166865E+11 | 0.88 | 10579.36 | 01-SEP-04:12 | 1.45 |
October | 0.159526E+11 | 0.82 | 10579.36 | 02-OCT-04:12 | 1.45 |
November | 0.152183E+11 | 0.81 | 10579.36 | 01-NOV-04:11 | 1.46 |
December | 0.151286E+11 | 0.78 | 10579.36 | 01-DEC-05:01 | 1.46 |
Annual Sum or Average | 0.189696E+12 | 0.83 | |||
Minimum of Months | 0.137966E+11 | 0.76 | 10579.36 | 1.45 | |
Maximum of Months | 0.176937E+11 | 0.90 | 10579.36 | 1.47 |
Report: FanReportMonthly
For: VAV_BOT WITH REHEAT FAN
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.373875E+10 | 0.34 | 15352.93 | 03-JAN-10:50 | 1.46 |
February | 0.421642E+10 | 0.36 | 22841.30 | 13-FEB-15:30 | 1.88 |
March | 0.640124E+10 | 0.41 | 22841.30 | 07-MAR-13:57 | 1.88 |
April | 0.817993E+10 | 0.47 | 22841.30 | 03-APR-14:00 | 1.88 |
May | 0.862269E+10 | 0.48 | 18265.37 | 30-MAY-15:20 | 1.61 |
June | 0.124190E+11 | 0.60 | 24311.10 | 27-JUN-04:12 | 1.93 |
July | 0.141217E+11 | 0.66 | 22236.55 | 03-JUL-15:10 | 1.82 |
August | 0.160972E+11 | 0.72 | 23270.34 | 22-AUG-15:00 | 1.88 |
September | 0.878200E+10 | 0.48 | 24311.10 | 11-SEP-04:12 | 1.94 |
October | 0.666766E+10 | 0.40 | 21408.83 | 14-OCT-09:27 | 1.80 |
November | 0.527347E+10 | 0.37 | 21408.83 | 04-NOV-08:20 | 1.80 |
December | 0.509061E+10 | 0.36 | 21731.72 | 15-DEC-15:30 | 1.82 |
Annual Sum or Average | 0.996107E+11 | 0.47 | |||
Minimum of Months | 0.373875E+10 | 0.34 | 15352.93 | 1.46 | |
Maximum of Months | 0.160972E+11 | 0.72 | 24311.10 | 1.94 |
Report: FanReportMonthly
For: VAV_MID WITH REHEAT FAN
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.501013E+11 | 0.47 | 63138.47 | 02-JAN-04:01 | 0.90 |
February | 0.381731E+11 | 0.40 | 63138.47 | 01-FEB-05:01 | 0.90 |
March | 0.425280E+11 | 0.38 | 227263.16 | 10-MAR-15:25 | 1.95 |
April | 0.489672E+11 | 0.38 | 223435.34 | 25-APR-10:27 | 1.93 |
May | 0.652793E+11 | 0.43 | 156511.10 | 31-MAY-15:20 | 1.52 |
June | 0.972312E+11 | 0.53 | 227263.16 | 27-JUN-05:03 | 1.93 |
July | 0.101444E+12 | 0.53 | 198355.04 | 26-JUL-05:03 | 1.77 |
August | 0.103560E+12 | 0.54 | 227263.16 | 04-AUG-04:12 | 1.93 |
September | 0.680236E+11 | 0.43 | 180350.40 | 08-SEP-16:00 | 1.67 |
October | 0.421497E+11 | 0.34 | 223435.34 | 23-OCT-09:20 | 1.93 |
November | 0.383439E+11 | 0.36 | 122092.58 | 04-NOV-05:02 | 1.32 |
December | 0.426632E+11 | 0.41 | 124821.15 | 01-DEC-17:00 | 1.34 |
Annual Sum or Average | 0.738465E+12 | 0.43 | |||
Minimum of Months | 0.381731E+11 | 0.34 | 63138.47 | 0.90 | |
Maximum of Months | 0.103560E+12 | 0.54 | 227263.16 | 1.95 |
Report: FanReportMonthly
For: VAV_TOP WITH REHEAT FAN
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.560207E+10 | 0.49 | 6089.00 | 02-JAN-04:01 | 0.83 |
February | 0.464699E+10 | 0.46 | 6089.00 | 01-FEB-05:01 | 0.84 |
March | 0.432426E+10 | 0.39 | 6089.00 | 01-MAR-05:11 | 0.84 |
April | 0.468678E+10 | 0.38 | 17655.93 | 18-APR-15:00 | 1.55 |
May | 0.599873E+10 | 0.40 | 17821.42 | 31-MAY-15:00 | 1.56 |
June | 0.956889E+10 | 0.50 | 24993.40 | 30-JUN-05:03 | 1.93 |
July | 0.996303E+10 | 0.50 | 19678.56 | 05-JUL-15:20 | 1.66 |
August | 0.992678E+10 | 0.50 | 24335.18 | 04-AUG-15:20 | 1.90 |
September | 0.602633E+10 | 0.40 | 20347.20 | 08-SEP-16:00 | 1.70 |
October | 0.373195E+10 | 0.33 | 8080.70 | 20-OCT-15:40 | 0.97 |
November | 0.439244E+10 | 0.41 | 6570.89 | 03-NOV-15:00 | 0.87 |
December | 0.524547E+10 | 0.47 | 6089.00 | 01-DEC-05:01 | 0.83 |
Annual Sum or Average | 0.741137E+11 | 0.43 | |||
Minimum of Months | 0.373195E+10 | 0.33 | 6089.00 | 0.83 | |
Maximum of Months | 0.996303E+10 | 0.50 | 24993.40 | 1.93 |
Report: FanReportMonthly
For: AIRLOOP DATACENTER BASEMENT SUPPLY FAN
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.991204E+11 | 1.41 | 37007.31 | 01-JAN-00:02 | 1.41 |
February | 0.895281E+11 | 1.41 | 37007.31 | 01-FEB-00:03 | 1.41 |
March | 0.991204E+11 | 1.42 | 37007.31 | 01-MAR-00:05 | 1.42 |
April | 0.959229E+11 | 1.41 | 37007.31 | 01-APR-00:10 | 1.42 |
May | 0.991204E+11 | 1.41 | 37007.31 | 01-MAY-00:10 | 1.41 |
June | 0.959229E+11 | 1.40 | 37007.31 | 01-JUN-00:10 | 1.41 |
July | 0.991204E+11 | 1.40 | 37007.31 | 01-JUL-00:10 | 1.40 |
August | 0.991204E+11 | 1.40 | 37007.31 | 01-AUG-00:10 | 1.39 |
September | 0.959229E+11 | 1.41 | 37007.31 | 01-SEP-00:03 | 1.40 |
October | 0.991204E+11 | 1.41 | 37007.31 | 01-OCT-00:10 | 1.41 |
November | 0.959229E+11 | 1.42 | 37007.31 | 01-NOV-00:10 | 1.42 |
December | 0.991204E+11 | 1.42 | 37007.31 | 01-DEC-00:10 | 1.42 |
Annual Sum or Average | 0.116706E+13 | 1.41 | |||
Minimum of Months | 0.895281E+11 | 1.40 | 37007.31 | 1.39 | |
Maximum of Months | 0.991204E+11 | 1.42 | 37007.31 | 1.42 |
Report: FanReportMonthly
For: AIRLOOP DATACENTER BOT SUPPLY FAN
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.159788E+10 | 0.97 | 596.58 | 01-JAN-00:02 | 0.96 |
February | 0.144324E+10 | 0.96 | 596.58 | 01-FEB-00:03 | 0.97 |
March | 0.159788E+10 | 0.96 | 596.58 | 01-MAR-00:05 | 0.97 |
April | 0.154633E+10 | 0.96 | 596.58 | 01-APR-00:10 | 0.96 |
May | 0.159788E+10 | 0.96 | 596.58 | 01-MAY-00:10 | 0.96 |
June | 0.154633E+10 | 0.96 | 596.58 | 01-JUN-00:10 | 0.96 |
July | 0.159788E+10 | 0.96 | 596.58 | 01-JUL-00:10 | 0.96 |
August | 0.159788E+10 | 0.96 | 596.58 | 01-AUG-00:10 | 0.96 |
September | 0.154633E+10 | 0.96 | 596.58 | 01-SEP-00:03 | 0.96 |
October | 0.159788E+10 | 0.96 | 596.58 | 01-OCT-00:10 | 0.96 |
November | 0.154633E+10 | 0.96 | 596.58 | 01-NOV-00:10 | 0.96 |
December | 0.159788E+10 | 0.96 | 596.58 | 01-DEC-00:10 | 0.96 |
Annual Sum or Average | 0.188137E+11 | 0.96 | |||
Minimum of Months | 0.144324E+10 | 0.96 | 596.58 | 0.96 | |
Maximum of Months | 0.159788E+10 | 0.97 | 596.58 | 0.97 |
Report: FanReportMonthly
For: AIRLOOP DATACENTER MID SUPPLY FAN
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.153522E+11 | 0.97 | 5731.84 | 01-JAN-00:02 | 0.96 |
February | 0.138665E+11 | 0.96 | 5731.84 | 01-FEB-00:03 | 0.97 |
March | 0.153522E+11 | 0.96 | 5731.84 | 01-MAR-00:05 | 0.97 |
April | 0.148569E+11 | 0.96 | 5731.84 | 01-APR-00:10 | 0.96 |
May | 0.153522E+11 | 0.96 | 5731.84 | 01-MAY-00:30 | 0.96 |
June | 0.148569E+11 | 0.96 | 5731.84 | 01-JUN-00:10 | 0.96 |
July | 0.153522E+11 | 0.96 | 5731.84 | 01-JUL-00:10 | 0.96 |
August | 0.153522E+11 | 0.96 | 5731.84 | 01-AUG-00:10 | 0.96 |
September | 0.148569E+11 | 0.96 | 5731.84 | 01-SEP-00:03 | 0.96 |
October | 0.153522E+11 | 0.96 | 5731.84 | 01-OCT-00:10 | 0.96 |
November | 0.148569E+11 | 0.96 | 5731.84 | 01-NOV-00:10 | 0.96 |
December | 0.153522E+11 | 0.96 | 5731.84 | 01-DEC-00:10 | 0.96 |
Annual Sum or Average | 0.180759E+12 | 0.96 | |||
Minimum of Months | 0.138665E+11 | 0.96 | 5731.84 | 0.96 | |
Maximum of Months | 0.153522E+11 | 0.97 | 5731.84 | 0.97 |
Report: FanReportMonthly
For: AIRLOOP DATACENTER TOP SUPPLY FAN
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.156048E+10 | 0.97 | 582.62 | 01-JAN-00:02 | 0.96 |
February | 0.140946E+10 | 0.96 | 582.62 | 01-FEB-00:03 | 0.97 |
March | 0.156048E+10 | 0.96 | 582.62 | 01-MAR-00:05 | 0.97 |
April | 0.151014E+10 | 0.96 | 582.62 | 01-APR-00:10 | 0.96 |
May | 0.156048E+10 | 0.96 | 582.62 | 01-MAY-00:10 | 0.96 |
June | 0.151014E+10 | 0.96 | 582.62 | 01-JUN-00:10 | 0.96 |
July | 0.156048E+10 | 0.96 | 582.62 | 01-JUL-00:10 | 0.96 |
August | 0.156048E+10 | 0.96 | 582.62 | 01-AUG-00:10 | 0.96 |
September | 0.151014E+10 | 0.96 | 582.62 | 01-SEP-00:03 | 0.96 |
October | 0.156048E+10 | 0.96 | 582.62 | 01-OCT-00:10 | 0.96 |
November | 0.151014E+10 | 0.96 | 582.62 | 01-NOV-00:10 | 0.96 |
December | 0.156048E+10 | 0.96 | 582.62 | 01-DEC-00:10 | 0.96 |
Annual Sum or Average | 0.183734E+11 | 0.96 | |||
Minimum of Months | 0.140946E+10 | 0.96 | 582.62 | 0.96 | |
Maximum of Months | 0.156048E+10 | 0.97 | 582.62 | 0.97 |
Report: PumpReportMonthly
For: HEATSYS1 PUMP
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.449719E+10 | 0.404747E+10 | 7916.90 | 30-JAN-07:04 | 7125.21 | 7125.21 | 50.06 | 20.72 |
February | 0.306604E+10 | 0.275944E+10 | 7887.11 | 02-FEB-07:10 | 7098.40 | 7098.40 | 50.69 | 20.37 |
March | 0.116075E+10 | 0.104468E+10 | 7039.60 | 06-MAR-05:01 | 6335.64 | 6335.64 | 45.87 | 13.41 |
April | 0.405721E+09 | 0.365149E+09 | 7013.10 | 03-APR-05:01 | 6311.79 | 6311.79 | 47.24 | 13.26 |
May | 20984171.38 | 18885754.24 | 4775.96 | 02-MAY-04:11 | 4298.37 | 4298.37 | 25.38 | 6.59 |
June | 5043886.13 | 4539497.52 | 962.50 | 02-JUN-05:03 | 866.25 | 866.25 | 26.36 | 1.03 |
July | 86.00 | 77.40 | 0.15 | 24-JUL-06:10 | 0.14 | 0.14 | 25.33 | 0.00 |
August | 163896.90 | 147507.21 | 107.80 | 16-AUG-06:15 | 97.02 | 97.02 | 25.18 | 0.11 |
September | 51916927.27 | 46725234.55 | 4986.82 | 30-SEP-04:01 | 4488.14 | 4488.14 | 29.58 | 7.02 |
October | 0.264022E+09 | 0.237620E+09 | 5366.31 | 16-OCT-04:11 | 4829.67 | 4829.67 | 25.03 | 7.87 |
November | 0.141250E+10 | 0.127125E+10 | 7044.73 | 27-NOV-06:02 | 6340.26 | 6340.26 | 48.02 | 13.42 |
December | 0.272906E+10 | 0.245615E+10 | 7050.77 | 12-DEC-05:02 | 6345.69 | 6345.69 | 48.10 | 13.45 |
Annual Sum or Average | 0.136134E+11 | 0.122521E+11 | ||||||
Minimum of Months | 86.00 | 77.40 | 0.15 | 0.14 | 0.14 | 25.03 | 0.00 | |
Maximum of Months | 0.449719E+10 | 0.404747E+10 | 7916.90 | 7125.21 | 7125.21 | 50.69 | 20.72 |
Report: PumpReportMonthly
For: COOLSYS1 PUMP SECONDARY
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 5129.71 | 4616.74 | 5.55 | 12-JAN-14:40 | 5.00 | 5.00 | 6.70 | 1.37 |
February | 7676.51 | 6908.86 | 3.25 | 17-FEB-16:30 | 2.92 | 2.92 | 6.70 | 0.86 |
March | 947806.19 | 853025.57 | 39.50 | 19-MAR-13:53 | 35.55 | 35.55 | 6.70 | 5.96 |
April | 81507833.60 | 73357050.24 | 2620.83 | 18-APR-12:40 | 2358.75 | 2358.75 | 6.71 | 54.45 |
May | 0.183251E+09 | 0.164926E+09 | 1895.24 | 30-MAY-11:00 | 1705.71 | 1705.71 | 6.71 | 47.15 |
June | 0.790553E+09 | 0.711497E+09 | 21268.55 | 27-JUN-04:12 | 19141.69 | 19141.69 | 8.98 | 129.49 |
July | 0.107107E+10 | 0.963966E+09 | 21268.55 | 26-JUL-05:03 | 19141.69 | 19141.69 | 9.49 | 129.49 |
August | 0.113252E+10 | 0.101926E+10 | 21268.55 | 03-AUG-05:03 | 19141.69 | 19141.69 | 6.81 | 129.49 |
September | 0.487781E+09 | 0.439003E+09 | 9300.82 | 11-SEP-05:03 | 8370.74 | 8370.74 | 7.96 | 93.03 |
October | 13701985.16 | 12331786.65 | 521.90 | 20-OCT-14:40 | 469.71 | 469.71 | 6.70 | 25.68 |
November | 1737812.97 | 1564031.68 | 273.61 | 03-NOV-13:20 | 246.25 | 246.25 | 6.70 | 18.47 |
December | 3124.27 | 2811.85 | 1.17 | 07-DEC-13:30 | 1.05 | 1.05 | 6.70 | 0.33 |
Annual Sum or Average | 0.376309E+10 | 0.338678E+10 | ||||||
Minimum of Months | 3124.27 | 2811.85 | 1.17 | 1.05 | 1.05 | 6.70 | 0.33 | |
Maximum of Months | 0.113252E+10 | 0.101926E+10 | 21268.55 | 19141.69 | 19141.69 | 9.49 | 129.49 |
Report: PumpReportMonthly
For: COOLSYS1 CHILLER1 PUMP
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.182502E+10 | 0.164252E+10 | 7319.28 | 02-JAN-07:20 | 6587.36 | 6587.36 | 6.72 | 64.74 |
February | 0.120142E+10 | 0.108128E+10 | 7319.28 | 01-FEB-02:08 | 6587.36 | 6587.36 | 6.72 | 64.74 |
March | 0.222633E+10 | 0.200369E+10 | 7319.28 | 01-MAR-00:05 | 6587.36 | 6587.36 | 6.72 | 64.74 |
April | 0.425652E+10 | 0.383087E+10 | 7319.28 | 01-APR-06:20 | 6587.36 | 6587.36 | 6.72 | 64.74 |
May | 0.714575E+10 | 0.643117E+10 | 7319.28 | 02-MAY-04:19 | 6587.36 | 6587.36 | 6.73 | 64.74 |
June | 0.106665E+11 | 0.959987E+10 | 7319.28 | 01-JUN-05:00 | 6587.36 | 6587.36 | 7.40 | 64.74 |
July | 0.146241E+11 | 0.131617E+11 | 7319.28 | 01-JUL-00:12 | 6587.36 | 6587.36 | 6.79 | 64.74 |
August | 0.143357E+11 | 0.129021E+11 | 7319.28 | 01-AUG-01:42 | 6587.36 | 6587.36 | 6.82 | 64.74 |
September | 0.712817E+10 | 0.641535E+10 | 7319.28 | 01-SEP-04:12 | 6587.36 | 6587.36 | 7.26 | 64.74 |
October | 0.265757E+10 | 0.239181E+10 | 7319.28 | 01-OCT-10:05 | 6587.36 | 6587.36 | 6.73 | 64.74 |
November | 0.154201E+10 | 0.138781E+10 | 7319.28 | 03-NOV-04:12 | 6587.36 | 6587.36 | 6.91 | 64.74 |
December | 0.781375E+09 | 0.703238E+09 | 7319.28 | 01-DEC-04:08 | 6587.36 | 6587.36 | 6.72 | 64.74 |
Annual Sum or Average | 0.683905E+11 | 0.615514E+11 | ||||||
Minimum of Months | 0.781375E+09 | 0.703238E+09 | 7319.28 | 6587.36 | 6587.36 | 6.72 | 64.74 | |
Maximum of Months | 0.146241E+11 | 0.131617E+11 | 7319.28 | 6587.36 | 6587.36 | 7.40 | 64.74 |
Report: PumpReportMonthly
For: COOLSYS1 CHILLER2 PUMP
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 0.00 | 0.00 | 6.70 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 6.72 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 6.72 | 0.00 |
April | 0.177859E+09 | 0.160073E+09 | 7319.28 | 18-APR-09:00 | 6587.36 | 6587.36 | 12.18 | 32.37 |
May | 0.469898E+09 | 0.422908E+09 | 7319.28 | 05-MAY-13:10 | 6587.36 | 6587.36 | 12.14 | 32.37 |
June | 0.190331E+10 | 0.171298E+10 | 7319.28 | 09-JUN-09:40 | 6587.36 | 6587.36 | 12.19 | 32.37 |
July | 0.291381E+10 | 0.262243E+10 | 7319.28 | 03-JUL-07:30 | 6587.36 | 6587.36 | 11.94 | 32.37 |
August | 0.291490E+10 | 0.262341E+10 | 7319.28 | 01-AUG-07:25 | 6587.36 | 6587.36 | 12.32 | 32.37 |
September | 0.755350E+09 | 0.679815E+09 | 7319.28 | 05-SEP-13:50 | 6587.36 | 6587.36 | 12.62 | 32.37 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 6.72 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 6.72 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 6.72 | 0.00 |
Annual Sum or Average | 0.913512E+10 | 0.822161E+10 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.70 | 0.00 | |
Maximum of Months | 0.291490E+10 | 0.262341E+10 | 7319.28 | 6587.36 | 6587.36 | 12.62 | 32.37 |
Report: PumpReportMonthly
For: PLANT CIRC PUMP
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.938818E+10 | 0.844937E+10 | 3505.15 | 01-JAN-00:02 | 3154.63 | 3154.63 | 18.49 | 14.64 |
February | 0.847965E+10 | 0.763169E+10 | 3505.15 | 01-FEB-00:03 | 3154.63 | 3154.63 | 18.61 | 14.64 |
March | 0.938818E+10 | 0.844937E+10 | 3505.15 | 01-MAR-00:05 | 3154.63 | 3154.63 | 19.53 | 14.64 |
April | 0.908534E+10 | 0.817681E+10 | 3505.15 | 01-APR-00:10 | 3154.63 | 3154.63 | 20.49 | 14.64 |
May | 0.938818E+10 | 0.844937E+10 | 3505.15 | 01-MAY-00:10 | 3154.63 | 3154.63 | 18.92 | 14.64 |
June | 0.908534E+10 | 0.817681E+10 | 3505.15 | 01-JUN-00:10 | 3154.63 | 3154.63 | 19.59 | 14.64 |
July | 0.938818E+10 | 0.844937E+10 | 3505.15 | 01-JUL-00:10 | 3154.63 | 3154.63 | 27.59 | 14.64 |
August | 0.938818E+10 | 0.844937E+10 | 3505.15 | 01-AUG-00:10 | 3154.63 | 3154.63 | 36.79 | 14.64 |
September | 0.908534E+10 | 0.817681E+10 | 3505.15 | 01-SEP-00:03 | 3154.63 | 3154.63 | 18.99 | 14.64 |
October | 0.938818E+10 | 0.844937E+10 | 3505.15 | 01-OCT-00:10 | 3154.63 | 3154.63 | 19.39 | 14.64 |
November | 0.908534E+10 | 0.817681E+10 | 3505.15 | 01-NOV-00:10 | 3154.63 | 3154.63 | 19.96 | 14.64 |
December | 0.938818E+10 | 0.844937E+10 | 3505.15 | 01-DEC-00:10 | 3154.63 | 3154.63 | 20.24 | 14.64 |
Annual Sum or Average | 0.110538E+12 | 0.994845E+11 | ||||||
Minimum of Months | 0.847965E+10 | 0.763169E+10 | 3505.15 | 3154.63 | 3154.63 | 18.49 | 14.64 | |
Maximum of Months | 0.938818E+10 | 0.844937E+10 | 3505.15 | 3154.63 | 3154.63 | 36.79 | 14.64 |
Report: PumpReportMonthly
For: SWHSYS1 PUMP
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.112905E+09 | 33871561.48 | 56.21 | 01-JAN-06:03 | 16.86 | 16.86 | 55.53 | 0.44 |
February | 0.101979E+09 | 30593668.43 | 56.21 | 01-FEB-06:01 | 16.86 | 16.86 | 55.68 | 0.44 |
March | 0.112905E+09 | 33871561.48 | 56.21 | 01-MAR-06:02 | 16.86 | 16.86 | 55.01 | 0.44 |
April | 0.109263E+09 | 32778930.46 | 56.21 | 01-APR-05:01 | 16.86 | 16.86 | 56.19 | 0.44 |
May | 0.112905E+09 | 33871561.48 | 56.21 | 01-MAY-05:02 | 16.86 | 16.86 | 55.49 | 0.44 |
June | 0.109263E+09 | 32778930.46 | 56.21 | 01-JUN-05:03 | 16.86 | 16.86 | 56.40 | 0.44 |
July | 0.112905E+09 | 33871561.48 | 56.21 | 01-JUL-05:03 | 16.86 | 16.86 | 55.90 | 0.44 |
August | 0.112905E+09 | 33871561.48 | 56.21 | 01-AUG-05:02 | 16.86 | 16.86 | 56.87 | 0.44 |
September | 0.109263E+09 | 32778930.46 | 56.21 | 01-SEP-05:03 | 16.86 | 16.86 | 55.76 | 0.44 |
October | 0.112905E+09 | 33871561.48 | 56.21 | 01-OCT-05:10 | 16.86 | 16.86 | 56.38 | 0.44 |
November | 0.109263E+09 | 32778930.46 | 56.21 | 01-NOV-05:03 | 16.86 | 16.86 | 55.38 | 0.44 |
December | 0.112905E+09 | 33871561.48 | 56.21 | 01-DEC-06:01 | 16.86 | 16.86 | 56.37 | 0.44 |
Annual Sum or Average | 0.132937E+10 | 0.398810E+09 | ||||||
Minimum of Months | 0.101979E+09 | 30593668.43 | 56.21 | 16.86 | 16.86 | 55.01 | 0.44 | |
Maximum of Months | 0.112905E+09 | 33871561.48 | 56.21 | 16.86 | 16.86 | 56.87 | 0.44 |
Report: PumpReportMonthly
For: TOWERWATERSYS PUMP
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.467289E+10 | 0.420560E+10 | 18743.28 | 12-JAN-14:00 | 16868.95 | 16868.95 | 21.15 | 75.96 |
February | 0.307053E+10 | 0.276348E+10 | 18743.07 | 24-FEB-18:05 | 16868.76 | 16868.76 | 21.13 | 75.96 |
March | 0.567822E+10 | 0.511040E+10 | 18754.52 | 25-MAR-15:00 | 16879.07 | 16879.07 | 21.98 | 75.96 |
April | 0.112968E+11 | 0.101671E+11 | 37672.35 | 18-APR-09:45 | 33905.12 | 33905.12 | 27.59 | 151.91 |
May | 0.191643E+11 | 0.172478E+11 | 37642.41 | 30-MAY-13:10 | 33878.17 | 33878.17 | 26.64 | 151.91 |
June | 0.317968E+11 | 0.286171E+11 | 37710.92 | 12-JUN-12:50 | 33939.83 | 33939.83 | 28.98 | 151.91 |
July | 0.441667E+11 | 0.397500E+11 | 37710.92 | 03-JUL-08:30 | 33939.83 | 33939.83 | 28.97 | 151.91 |
August | 0.434381E+11 | 0.390942E+11 | 37710.92 | 01-AUG-08:20 | 33939.83 | 33939.83 | 29.18 | 151.91 |
September | 0.201098E+11 | 0.180988E+11 | 37679.63 | 11-SEP-09:40 | 33911.66 | 33911.66 | 27.82 | 151.91 |
October | 0.680138E+10 | 0.612124E+10 | 18789.26 | 20-OCT-15:00 | 16910.33 | 16910.33 | 24.56 | 75.96 |
November | 0.394849E+10 | 0.355364E+10 | 18757.88 | 03-NOV-13:20 | 16882.09 | 16882.09 | 22.23 | 75.96 |
December | 0.200064E+10 | 0.180058E+10 | 18743.35 | 26-DEC-07:20 | 16869.01 | 16869.01 | 21.15 | 75.96 |
Annual Sum or Average | 0.196145E+12 | 0.176530E+12 | ||||||
Minimum of Months | 0.200064E+10 | 0.180058E+10 | 18743.07 | 16868.76 | 16868.76 | 21.13 | 75.96 | |
Maximum of Months | 0.441667E+11 | 0.397500E+11 | 37710.92 | 33939.83 | 33939.83 | 29.18 | 151.91 |
Report: CondLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:02 | 35.02 | 35.02 | 373611.28 | 2863880.51 | 30-JAN-07:02 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 34.95 | 82.00 | 290516.59 | 2858859.26 | 02-FEB-07:02 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 35.75 | 82.00 | 91355.26 | 2089523.17 | 07-MAR-06:01 |
April | 0.00 | 0.00 | 01-APR-00:10 | 26.63 | 26.63 | 34402.36 | 1927689.98 | 03-APR-05:01 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 23.61 | 23.61 | 1895.27 | 1559900.23 | 02-MAY-04:11 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 24.51 | 24.51 | 477.26 | 238739.65 | 02-JUN-05:03 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 25.33 | 25.33 | 0.01 | 37.07 | 24-JUL-06:10 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.33 | 25.33 | 14.77 | 26212.05 | 16-AUG-06:15 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 25.73 | 25.73 | 4844.17 | 1537769.58 | 30-SEP-04:01 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 22.73 | 22.73 | 23362.75 | 1874152.86 | 16-OCT-04:11 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 24.55 | 24.55 | 115762.19 | 2026568.60 | 13-NOV-06:01 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 28.82 | 28.82 | 217745.66 | 2280148.89 | 18-DEC-05:01 |
Annual Sum or Average | 0.00 | 95196.11 | ||||||
Minimum of Months | 0.00 | 0.00 | 22.73 | 22.73 | 0.01 | 37.07 | ||
Maximum of Months | 0.00 | 0.00 | 35.75 | 82.00 | 373611.28 | 2863880.51 |
Report: CondLoopDemandReportMonthly
For: COOLSYS1_SUPPLY
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 614.46 | 7946.17 | 12-JAN-14:40 | 6.73 | 6.70 | 0.00 | 0.00 | 01-JAN-00:02 |
February | 453.70 | 12263.64 | 17-FEB-16:30 | 6.75 | 6.70 | 0.00 | 0.00 | 01-FEB-00:03 |
March | 3090.36 | 216788.82 | 25-MAR-15:00 | 7.50 | 6.70 | 0.00 | 0.00 | 01-MAR-00:05 |
April | 58147.33 | 2054305.85 | 18-APR-09:05 | 10.49 | 6.70 | 0.00 | 0.00 | 01-APR-00:10 |
May | 138735.35 | 1832607.15 | 30-MAY-11:00 | 10.08 | 6.70 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 425932.97 | 2691029.02 | 26-JUN-07:50 | 11.66 | 6.70 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 575588.73 | 2557779.33 | 07-JUL-11:00 | 11.42 | 6.70 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 554621.25 | 3815992.82 | 04-AUG-07:20 | 13.74 | 8.05 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 216907.44 | 2102867.85 | 11-SEP-09:40 | 10.58 | 6.70 | 0.00 | 0.00 | 01-SEP-00:03 |
October | 16357.09 | 951674.01 | 20-OCT-15:00 | 10.21 | 6.70 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 2236.44 | 281291.88 | 03-NOV-13:20 | 7.74 | 6.70 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 270.42 | 12849.72 | 15-DEC-13:10 | 6.75 | 6.70 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 167334.34 | 0.00 | ||||||
Minimum of Months | 270.42 | 7946.17 | 6.73 | 6.70 | 0.00 | 0.00 | ||
Maximum of Months | 575588.73 | 3815992.82 | 13.74 | 8.05 | 0.00 | 0.00 |
Report: CondLoopDemandReportMonthly
For: COOLSYS1_DEMAND
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 1.51 | 2144.04 | 12-JAN-14:40 | 7.07 | 6.70 | 0.00 | 0.00 | 01-JAN-00:02 |
February | 6.74 | 7409.20 | 17-FEB-16:30 | 8.76 | 6.70 | 0.00 | 0.00 | 01-FEB-00:03 |
March | 2342.67 | 213455.35 | 25-MAR-15:00 | 16.93 | 6.70 | 0.00 | 0.00 | 01-MAR-00:05 |
April | 56594.02 | 1848835.45 | 16-APR-15:22 | 16.33 | 6.70 | 0.00 | 0.00 | 01-APR-00:10 |
May | 135957.11 | 1822720.57 | 30-MAY-11:00 | 15.94 | 6.70 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 421457.85 | 4865442.14 | 26-JUN-04:12 | 16.00 | 11.17 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 569461.62 | 4702643.78 | 26-JUL-05:03 | 15.38 | 11.03 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 547957.89 | 5126131.37 | 04-AUG-04:12 | 16.70 | 11.40 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 214513.51 | 2935828.81 | 11-SEP-05:03 | 14.24 | 8.98 | 0.00 | 0.00 | 01-SEP-00:03 |
October | 15471.89 | 947308.54 | 20-OCT-14:50 | 15.56 | 6.70 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 1701.41 | 300252.43 | 09-NOV-06:03 | 11.57 | 6.70 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 7.86 | 7803.26 | 15-DEC-13:10 | 12.38 | 6.70 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 165028.52 | 0.00 | ||||||
Minimum of Months | 1.51 | 2144.04 | 7.07 | 6.70 | 0.00 | 0.00 | ||
Maximum of Months | 569461.62 | 5126131.37 | 16.93 | 11.40 | 0.00 | 0.00 |
Report: CondLoopDemandReportMonthly
For: SINGLE WATER PLANT LOOP
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 9153.05 | 34805.27 | 12-JAN-16:40 | 19.02 | 18.33 | 0.00 | 0.00 | 01-JAN-00:02 |
February | 39424.50 | 71357.53 | 24-FEB-17:00 | 19.74 | 18.33 | 0.00 | 0.00 | 01-FEB-00:03 |
March | 79729.04 | 389714.02 | 19-MAR-16:00 | 25.96 | 21.19 | 0.00 | 0.00 | 01-MAR-00:05 |
April | 232376.22 | 1642880.19 | 15-APR-15:00 | 49.78 | 36.57 | 0.00 | 0.00 | 01-APR-00:10 |
May | 83898.71 | 953126.12 | 31-MAY-15:00 | 36.81 | 32.23 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 413909.89 | 1466087.97 | 13-JUN-12:10 | 46.49 | 33.37 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 804590.56 | 1737078.24 | 26-JUL-15:10 | 51.53 | 37.16 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 936865.33 | 2000638.08 | 04-AUG-16:00 | 56.40 | 41.42 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 161228.64 | 1086374.59 | 06-SEP-15:00 | 39.34 | 34.54 | 0.00 | 0.00 | 01-SEP-00:03 |
October | 58830.16 | 609662.95 | 20-OCT-15:00 | 30.22 | 25.55 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 73866.88 | 134285.08 | 03-NOV-14:30 | 20.97 | 18.33 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 94757.32 | 119923.49 | 01-DEC-16:10 | 20.69 | 18.33 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 251090.09 | 0.00 | ||||||
Minimum of Months | 9153.05 | 34805.27 | 19.02 | 18.33 | 0.00 | 0.00 | ||
Maximum of Months | 936865.33 | 2000638.08 | 56.40 | 41.42 | 0.00 | 0.00 |
Report: CondLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:02 | 56.82 | 56.82 | 17647.13 | 60110.28 | 31-JAN-12:50 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 56.11 | 56.11 | 18074.50 | 60544.73 | 16-FEB-12:35 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 55.59 | 55.59 | 18941.08 | 60409.07 | 01-MAR-12:50 |
April | 0.00 | 0.00 | 01-APR-00:10 | 56.69 | 56.69 | 17203.45 | 58721.77 | 03-APR-11:40 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 56.47 | 56.47 | 16771.73 | 55979.72 | 01-MAY-11:40 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 56.99 | 56.99 | 16079.94 | 52372.81 | 01-JUN-11:50 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 56.45 | 56.45 | 14149.35 | 48970.71 | 03-JUL-11:30 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 57.35 | 57.35 | 14988.08 | 47056.08 | 01-AUG-11:20 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 56.41 | 56.41 | 14315.07 | 48150.96 | 29-SEP-12:00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 57.05 | 57.05 | 14948.73 | 51196.84 | 31-OCT-11:40 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 56.04 | 56.04 | 16084.27 | 54727.82 | 30-NOV-12:50 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 56.84 | 56.84 | 16496.82 | 57851.55 | 29-DEC-12:30 |
Annual Sum or Average | 0.00 | 16298.08 | ||||||
Minimum of Months | 0.00 | 0.00 | 55.59 | 55.59 | 14149.35 | 47056.08 | ||
Maximum of Months | 0.00 | 0.00 | 57.35 | 57.35 | 18941.08 | 60544.73 |
Report: CondLoopDemandReportMonthly
For: TOWERWATERSYS
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 31.09 | 15676.30 | 12-JAN-14:00 | 21.15 | 20.28 | 4217.93 | 198870.42 | 22-JAN-15:52 |
February | 21.68 | 10861.74 | 24-FEB-18:05 | 21.13 | 20.34 | 3317.91 | 181889.61 | 11-FEB-04:09 |
March | 2393.23 | 280596.39 | 25-MAR-15:00 | 21.98 | 21.10 | 4847.58 | 190187.75 | 23-MAR-04:16 |
April | 92621.07 | 4120151.45 | 18-APR-09:45 | 27.59 | 24.02 | 4321.00 | 183125.41 | 04-APR-15:10 |
May | 195039.25 | 3518446.03 | 30-MAY-13:10 | 26.64 | 23.41 | 955.53 | 155775.03 | 02-MAY-05:40 |
June | 807080.54 | 6479930.78 | 26-JUN-07:50 | 31.30 | 26.43 | 422.01 | 118157.67 | 02-JUN-06:00 |
July | 1107724.47 | 7161383.85 | 26-JUL-15:00 | 32.38 | 28.66 | 228.78 | 56567.06 | 22-JUL-07:20 |
August | 1068495.71 | 8323552.29 | 04-AUG-07:20 | 34.21 | 28.64 | 462.02 | 91937.80 | 07-AUG-07:40 |
September | 309914.82 | 4266163.84 | 11-SEP-09:40 | 27.82 | 24.02 | 710.68 | 126992.25 | 27-SEP-10:40 |
October | 18092.48 | 1097104.99 | 20-OCT-15:00 | 24.56 | 21.10 | 2994.70 | 169536.85 | 16-OCT-06:20 |
November | 1733.63 | 359616.98 | 03-NOV-13:20 | 22.23 | 21.10 | 3330.45 | 176364.70 | 25-NOV-21:22 |
December | 15.65 | 17390.54 | 26-DEC-07:20 | 21.15 | 20.23 | 2101.82 | 187181.40 | 12-DEC-01:32 |
Annual Sum or Average | 302703.17 | 2319.14 | ||||||
Minimum of Months | 15.65 | 10861.74 | 21.13 | 20.23 | 228.78 | 56567.06 | ||
Maximum of Months | 1107724.47 | 8323552.29 | 34.21 | 28.66 | 4847.58 | 198870.42 |
Report: ZoneTemperatureOscillationReportMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV_BOT WITH REHEAT
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.410899E+11 | 0.00 | 9072185.77 | 0.373875E+10 | 0.00 | 0.00 |
February | 0.338060E+11 | 0.00 | 30375945.91 | 0.421642E+10 | 0.00 | 0.00 |
March | 0.544467E+10 | 0.00 | 0.756454E+09 | 0.640124E+10 | 0.00 | 0.00 |
April | 0.142013E+10 | 0.00 | 0.151676E+11 | 0.817993E+10 | 0.00 | 0.00 |
May | 0.104991E+09 | 0.00 | 0.328973E+11 | 0.862269E+10 | 0.00 | 0.00 |
June | 25271107.16 | 0.00 | 0.992520E+11 | 0.124190E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.147030E+12 | 0.141217E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.149682E+12 | 0.160972E+11 | 0.00 | 0.00 |
September | 0.215581E+09 | 0.00 | 0.487271E+11 | 0.878200E+10 | 0.00 | 0.00 |
October | 0.879943E+09 | 0.00 | 0.425736E+10 | 0.666766E+10 | 0.00 | 0.00 |
November | 0.591617E+10 | 0.00 | 0.433232E+09 | 0.527347E+10 | 0.00 | 0.00 |
December | 0.150643E+11 | 0.00 | 21023358.35 | 0.509061E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.103967E+12 | 0.00 | 0.498263E+12 | 0.996107E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 9072185.77 | 0.373875E+10 | 0.00 | 0.00 |
Maximum of Months | 0.410899E+11 | 0.00 | 0.149682E+12 | 0.160972E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV_MID WITH REHEAT
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.840149E+12 | 0.00 | 29315269.17 | 0.501013E+11 | 0.00 | 0.00 |
February | 0.583478E+12 | 0.00 | 27029005.22 | 0.381731E+11 | 0.00 | 0.00 |
March | 0.204998E+12 | 0.00 | 0.522420E+10 | 0.425280E+11 | 0.00 | 0.00 |
April | 0.742277E+11 | 0.00 | 0.112402E+12 | 0.489672E+11 | 0.00 | 0.00 |
May | 0.385320E+10 | 0.00 | 0.279891E+12 | 0.652793E+11 | 0.00 | 0.00 |
June | 0.782493E+09 | 0.00 | 0.833663E+12 | 0.972312E+11 | 0.00 | 0.00 |
July | 22712.32 | 0.00 | 0.114616E+13 | 0.101444E+12 | 0.00 | 0.00 |
August | 32106182.68 | 0.00 | 0.109160E+13 | 0.103560E+12 | 0.00 | 0.00 |
September | 0.970690E+10 | 0.00 | 0.425327E+12 | 0.680236E+11 | 0.00 | 0.00 |
October | 0.507309E+11 | 0.00 | 0.325785E+11 | 0.421497E+11 | 0.00 | 0.00 |
November | 0.250175E+12 | 0.00 | 0.360259E+10 | 0.383439E+11 | 0.00 | 0.00 |
December | 0.486103E+12 | 0.00 | 8640854.02 | 0.426632E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.250424E+13 | 0.00 | 0.393051E+13 | 0.738465E+12 | 0.00 | 0.00 |
Minimum of Months | 22712.32 | 0.00 | 8640854.02 | 0.381731E+11 | 0.00 | 0.00 |
Maximum of Months | 0.840149E+12 | 0.00 | 0.114616E+13 | 0.103560E+12 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV_TOP WITH REHEAT
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.127478E+12 | 0.00 | 3479025.07 | 0.560207E+10 | 0.00 | 0.00 |
February | 0.882250E+11 | 0.00 | 4713850.52 | 0.464699E+10 | 0.00 | 0.00 |
March | 0.366134E+11 | 0.00 | 0.452687E+09 | 0.432426E+10 | 0.00 | 0.00 |
April | 0.143730E+11 | 0.00 | 0.121570E+11 | 0.468678E+10 | 0.00 | 0.00 |
May | 0.115600E+10 | 0.00 | 0.297247E+11 | 0.599873E+10 | 0.00 | 0.00 |
June | 0.433575E+09 | 0.00 | 0.912012E+11 | 0.956889E+10 | 0.00 | 0.00 |
July | 1902.11 | 0.00 | 0.124036E+12 | 0.996303E+10 | 0.00 | 0.00 |
August | 4514506.20 | 0.00 | 0.114658E+12 | 0.992678E+10 | 0.00 | 0.00 |
September | 0.277045E+10 | 0.00 | 0.440558E+11 | 0.602633E+10 | 0.00 | 0.00 |
October | 0.115127E+11 | 0.00 | 0.279138E+10 | 0.373195E+10 | 0.00 | 0.00 |
November | 0.467410E+11 | 0.00 | 0.197745E+09 | 0.439244E+10 | 0.00 | 0.00 |
December | 0.874582E+11 | 0.00 | 2632868.35 | 0.524547E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.416765E+12 | 0.00 | 0.419285E+12 | 0.741137E+11 | 0.00 | 0.00 |
Minimum of Months | 1902.11 | 0.00 | 2632868.35 | 0.373195E+10 | 0.00 | 0.00 |
Maximum of Months | 0.127478E+12 | 0.00 | 0.124036E+12 | 0.996303E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: CAV_BAS
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.998648E+09 | 0.00 | 83777.90 | 0.146947E+11 | 0.00 | 0.00 |
February | 0.347387E+10 | 0.00 | 367811.27 | 0.137966E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 26256360.24 | 0.165447E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.574840E+10 | 0.152070E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.145144E+11 | 0.162335E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.501647E+11 | 0.162552E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.731938E+11 | 0.162850E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.777734E+11 | 0.176937E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.277808E+11 | 0.166865E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.188053E+10 | 0.159526E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 61208898.32 | 0.152183E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 126762.73 | 0.151286E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.447252E+10 | 0.00 | 0.251144E+12 | 0.189696E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 83777.90 | 0.137966E+11 | 0.00 | 0.00 |
Maximum of Months | 0.347387E+10 | 0.00 | 0.777734E+11 | 0.176937E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER BASEMENT
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.101081E+11 | 0.225354E+12 | 0.00 | 45.41 |
February | 0.00 | 0.00 | 0.152400E+11 | 0.288415E+12 | 0.00 | 72.06 |
March | 0.00 | 0.00 | 0.245981E+11 | 0.351009E+12 | 0.00 | 90.84 |
April | 0.00 | 0.00 | 0.183605E+12 | 0.330532E+12 | 0.00 | 71.00 |
May | 0.00 | 0.00 | 0.263636E+11 | 0.147561E+12 | 0.00 | 14.91 |
June | 0.00 | 0.00 | 0.308452E+12 | 0.173650E+12 | 0.00 | 1.07 |
July | 0.00 | 0.00 | 0.899576E+12 | 0.299573E+12 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.113021E+13 | 0.352381E+12 | 0.00 | 1.56 |
September | 0.00 | 0.00 | 0.655526E+11 | 0.159634E+12 | 0.00 | 16.76 |
October | 0.00 | 0.00 | 0.175999E+11 | 0.282814E+12 | 0.00 | 66.11 |
November | 0.00 | 0.00 | 0.179195E+11 | 0.312316E+12 | 0.00 | 78.24 |
December | 0.00 | 0.00 | 0.225638E+11 | 0.374498E+12 | 0.00 | 99.64 |
Annual Sum or Average | 0.00 | 0.00 | 0.272179E+13 | 0.329774E+13 | 0.00 | 557.61 |
Minimum of Months | 0.00 | 0.00 | 0.101081E+11 | 0.147561E+12 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.113021E+13 | 0.374498E+12 | 0.00 | 99.64 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER BOT
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.251045E+10 | 0.217117E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.916809E+10 | 0.334267E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.181283E+11 | 0.512605E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.245827E+11 | 0.622284E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.739241E+10 | 0.310324E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.141831E+11 | 0.455793E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.215798E+11 | 0.630663E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.279222E+11 | 0.757974E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.729996E+10 | 0.308817E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.127322E+11 | 0.409855E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.173571E+11 | 0.490985E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.231379E+11 | 0.609067E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.185994E+12 | 0.565975E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.251045E+10 | 0.217117E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.279222E+11 | 0.757974E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER MID
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.327576E+10 | 0.161410E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.590752E+11 | 0.263984E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.146850E+12 | 0.443351E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.217996E+12 | 0.567305E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.625103E+11 | 0.282018E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.131332E+12 | 0.428851E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.204002E+12 | 0.599593E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.262757E+12 | 0.717951E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.613600E+11 | 0.279799E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.101850E+12 | 0.356185E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.136433E+12 | 0.416883E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.182925E+12 | 0.515807E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.157037E+13 | 0.503314E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.327576E+10 | 0.161410E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.262757E+12 | 0.717951E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER TOP
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.168288E+09 | 0.160013E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.419143E+10 | 0.230858E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.130701E+11 | 0.416325E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.206019E+11 | 0.549839E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.572603E+10 | 0.274658E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.129335E+11 | 0.428548E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.203591E+11 | 0.602532E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.261595E+11 | 0.719789E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.546739E+10 | 0.269481E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.840078E+10 | 0.325100E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.116634E+11 | 0.382676E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.162713E+11 | 0.481903E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.145013E+12 | 0.484172E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.168288E+09 | 0.160013E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.261595E+11 | 0.719789E+10 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV_BOT WITH REHEAT
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.373875E+10 | 9072185.77 | 0.410899E+11 | 0.843876E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.421642E+10 | 30375945.91 | 0.338060E+11 | 0.430349E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.640124E+10 | 0.756454E+09 | 0.544467E+10 | 0.334813E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.817993E+10 | 0.151676E+11 | 0.142013E+10 | 0.114855E+11 | 0.778460E+09 | 0.00 | 0.00 | 0.00 |
May | 0.862269E+10 | 0.328973E+11 | 0.104991E+09 | 0.101438E+10 | 0.639756E+09 | 0.00 | 0.00 | 0.00 |
June | 0.124190E+11 | 0.992520E+11 | 25271107.16 | 0.151975E+09 | 0.594344E+10 | 0.00 | 0.00 | 0.00 |
July | 0.141217E+11 | 0.147030E+12 | 0.00 | 46518735.98 | 0.875717E+10 | 0.00 | 0.00 | 0.00 |
August | 0.160972E+11 | 0.149682E+12 | 0.00 | 0.236833E+09 | 0.880021E+10 | 0.00 | 0.00 | 0.00 |
September | 0.878200E+10 | 0.487271E+11 | 0.215581E+09 | 0.202478E+10 | 0.192614E+10 | 0.00 | 0.00 | 0.00 |
October | 0.666766E+10 | 0.425736E+10 | 0.879943E+09 | 0.834920E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.527347E+10 | 0.433232E+09 | 0.591617E+10 | 0.319183E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.509061E+10 | 21023358.35 | 0.150643E+11 | 0.639393E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.996107E+11 | 0.498263E+12 | 0.103967E+12 | 0.280071E+12 | 0.268452E+11 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.373875E+10 | 9072185.77 | 0.00 | 46518735.98 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.160972E+11 | 0.149682E+12 | 0.410899E+11 | 0.843876E+11 | 0.880021E+10 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV_MID WITH REHEAT
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.501013E+11 | 29315269.17 | 0.840149E+12 | 0.823725E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.381731E+11 | 27029005.22 | 0.583478E+12 | 0.509838E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.425280E+11 | 0.522536E+10 | 0.204998E+12 | 0.489493E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.489672E+11 | 0.112402E+12 | 0.742277E+11 | 0.208240E+12 | 0.760545E+10 | 0.00 | 0.00 | 0.00 |
May | 0.652793E+11 | 0.279891E+12 | 0.385320E+10 | 0.211590E+11 | 0.646582E+10 | 0.00 | 0.00 | 0.00 |
June | 0.972312E+11 | 0.833663E+12 | 0.782493E+09 | 0.469640E+10 | 0.592789E+11 | 0.00 | 0.00 | 0.00 |
July | 0.101444E+12 | 0.114616E+13 | 22712.32 | 0.568279E+09 | 0.859934E+11 | 0.00 | 0.00 | 0.00 |
August | 0.103560E+12 | 0.109160E+13 | 32106182.68 | 0.291014E+10 | 0.842306E+11 | 0.00 | 0.00 | 0.00 |
September | 0.680236E+11 | 0.425327E+12 | 0.970690E+10 | 0.325649E+11 | 0.199209E+11 | 0.00 | 0.00 | 0.00 |
October | 0.421497E+11 | 0.325785E+11 | 0.507309E+11 | 0.145422E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.383439E+11 | 0.360284E+10 | 0.250175E+12 | 0.419797E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.426632E+11 | 8640854.02 | 0.486103E+12 | 0.790500E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.738465E+12 | 0.393051E+13 | 0.250424E+13 | 0.344891E+13 | 0.263495E+12 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.381731E+11 | 8640854.02 | 22712.32 | 0.568279E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.103560E+12 | 0.114616E+13 | 0.840149E+12 | 0.823725E+12 | 0.859934E+11 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV_TOP WITH REHEAT
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.560207E+10 | 3479025.07 | 0.127478E+12 | 0.801056E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.464699E+10 | 4713850.52 | 0.882250E+11 | 0.504594E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.432426E+10 | 0.452687E+09 | 0.366134E+11 | 0.522634E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.468678E+10 | 0.121570E+11 | 0.143730E+11 | 0.250972E+11 | 0.577500E+09 | 0.00 | 0.00 | 0.00 |
May | 0.599873E+10 | 0.297247E+11 | 0.115600E+10 | 0.261094E+10 | 0.492255E+09 | 0.00 | 0.00 | 0.00 |
June | 0.956889E+10 | 0.912012E+11 | 0.433575E+09 | 0.817258E+09 | 0.521723E+10 | 0.00 | 0.00 | 0.00 |
July | 0.996303E+10 | 0.124036E+12 | 1902.11 | 10500012.62 | 0.727376E+10 | 0.00 | 0.00 | 0.00 |
August | 0.992678E+10 | 0.114658E+12 | 4514506.20 | 0.269704E+09 | 0.757125E+10 | 0.00 | 0.00 | 0.00 |
September | 0.602633E+10 | 0.440558E+11 | 0.277045E+10 | 0.436721E+10 | 0.160127E+10 | 0.00 | 0.00 | 0.00 |
October | 0.373195E+10 | 0.279138E+10 | 0.115127E+11 | 0.186560E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.439244E+10 | 0.197745E+09 | 0.467410E+11 | 0.443200E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.524547E+10 | 2632868.35 | 0.874582E+11 | 0.759740E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.741137E+11 | 0.419285E+12 | 0.416765E+12 | 0.354951E+12 | 0.227333E+11 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.373195E+10 | 2632868.35 | 1902.11 | 10500012.62 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.996303E+10 | 0.124036E+12 | 0.127478E+12 | 0.801056E+11 | 0.757125E+10 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: CAV_BAS
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.146947E+11 | 83777.90 | 0.998648E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.137966E+11 | 367811.27 | 0.347387E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.165447E+11 | 26256360.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.152070E+11 | 0.574840E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.162335E+11 | 0.145144E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.162552E+11 | 0.501647E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.162850E+11 | 0.731938E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.176937E+11 | 0.777734E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.166865E+11 | 0.277808E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.159526E+11 | 0.188053E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.152183E+11 | 61208898.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.151286E+11 | 126762.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.189696E+12 | 0.251144E+12 | 0.447252E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.137966E+11 | 83777.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.176937E+11 | 0.777734E+11 | 0.347387E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER BASEMENT
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.991204E+11 | 0.595031E+10 | 0.00 | 0.00 | 0.00 | 0.121528E+12 | 0.00 | 0.00 |
February | 0.895281E+11 | 0.100733E+11 | 0.00 | 0.00 | 0.00 | 0.192852E+12 | 0.00 | 0.00 |
March | 0.991204E+11 | 0.169035E+11 | 0.00 | 0.00 | 0.00 | 0.243099E+12 | 0.00 | 0.00 |
April | 0.959229E+11 | 0.139867E+12 | 0.00 | 0.00 | 0.00 | 0.190016E+12 | 0.00 | 0.00 |
May | 0.991204E+11 | 0.180099E+11 | 0.00 | 0.00 | 0.00 | 0.399077E+11 | 0.00 | 0.00 |
June | 0.959229E+11 | 0.233604E+12 | 0.00 | 0.00 | 0.00 | 0.286529E+10 | 0.00 | 0.00 |
July | 0.991204E+11 | 0.699123E+12 | 0.00 | 0.00 | 0.00 | 413349.74 | 0.00 | 0.00 |
August | 0.991204E+11 | 0.881150E+12 | 0.00 | 0.00 | 0.00 | 0.418352E+10 | 0.00 | 0.00 |
September | 0.959229E+11 | 0.468914E+11 | 0.00 | 0.00 | 0.00 | 0.448480E+11 | 0.00 | 0.00 |
October | 0.991204E+11 | 0.116167E+11 | 0.00 | 0.00 | 0.00 | 0.176914E+12 | 0.00 | 0.00 |
November | 0.959229E+11 | 0.118511E+11 | 0.00 | 0.00 | 0.00 | 0.209383E+12 | 0.00 | 0.00 |
December | 0.991204E+11 | 0.150260E+11 | 0.00 | 0.00 | 0.00 | 0.266640E+12 | 0.00 | 0.00 |
Annual Sum or Average | 0.116706E+13 | 0.209007E+13 | 0.00 | 0.00 | 0.00 | 0.149224E+13 | 0.00 | 0.00 |
Minimum of Months | 0.895281E+11 | 0.595031E+10 | 0.00 | 0.00 | 0.00 | 413349.74 | 0.00 | 0.00 |
Maximum of Months | 0.991204E+11 | 0.881150E+12 | 0.00 | 0.00 | 0.00 | 0.266640E+12 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER BOT
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.159788E+10 | 0.193716E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.144324E+10 | 0.726866E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.159788E+10 | 0.146001E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.154633E+10 | 0.199062E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.159788E+10 | 0.588705E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.154633E+10 | 0.111715E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.159788E+10 | 0.168711E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.159788E+10 | 0.219404E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.154633E+10 | 0.575813E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.159788E+10 | 0.102315E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.154633E+10 | 0.139936E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.159788E+10 | 0.186451E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.188137E+11 | 0.148211E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.144324E+10 | 0.193716E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.159788E+10 | 0.219404E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER MID
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.153522E+11 | 0.248695E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.138665E+11 | 0.465433E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.153522E+11 | 0.117867E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.148569E+11 | 0.176123E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.153522E+11 | 0.496606E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.148569E+11 | 0.103303E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.153522E+11 | 0.159395E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.153522E+11 | 0.206314E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.148569E+11 | 0.482370E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.153522E+11 | 0.815834E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.148569E+11 | 0.109602E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.153522E+11 | 0.146696E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.180759E+12 | 0.124781E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.138665E+11 | 0.248695E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.153522E+11 | 0.206314E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER TOP
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.156048E+10 | 0.128632E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.140946E+10 | 0.329231E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.156048E+10 | 0.104674E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.151014E+10 | 0.166136E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.156048E+10 | 0.453993E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.151014E+10 | 0.101582E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.156048E+10 | 0.158942E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.156048E+10 | 0.205221E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.151014E+10 | 0.428272E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.156048E+10 | 0.671026E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.151014E+10 | 0.934680E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.156048E+10 | 0.130127E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.183734E+11 | 0.114969E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.140946E+10 | 0.128632E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.156048E+10 | 0.205221E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV_BOT WITH REHEAT
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.373875E+10 | 0.410899E+11 | 9072185.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.421642E+10 | 0.338060E+11 | 30375945.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.640124E+10 | 0.544467E+10 | 0.756454E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.817993E+10 | 0.142013E+10 | 0.151676E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.862269E+10 | 0.104991E+09 | 0.328973E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.124190E+11 | 25271107.16 | 0.992520E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.141217E+11 | 0.00 | 0.147030E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.160972E+11 | 0.00 | 0.149682E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.878200E+10 | 0.215581E+09 | 0.487271E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.666766E+10 | 0.879943E+09 | 0.425736E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.527347E+10 | 0.591617E+10 | 0.433232E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.509061E+10 | 0.150643E+11 | 21023358.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.996107E+11 | 0.103967E+12 | 0.498263E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.373875E+10 | 0.00 | 9072185.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.160972E+11 | 0.410899E+11 | 0.149682E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV_MID WITH REHEAT
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.501013E+11 | 0.840149E+12 | 29315269.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.381731E+11 | 0.583478E+12 | 27029005.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.425280E+11 | 0.204998E+12 | 0.522420E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.489672E+11 | 0.742277E+11 | 0.112402E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.652793E+11 | 0.385320E+10 | 0.279891E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.972312E+11 | 0.782493E+09 | 0.833663E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.101444E+12 | 22712.32 | 0.114616E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.103560E+12 | 32106182.68 | 0.109160E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.680236E+11 | 0.970690E+10 | 0.425327E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.421497E+11 | 0.507309E+11 | 0.325785E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.383439E+11 | 0.250175E+12 | 0.360259E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.426632E+11 | 0.486103E+12 | 8640854.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.738465E+12 | 0.250424E+13 | 0.393051E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.381731E+11 | 22712.32 | 8640854.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.103560E+12 | 0.840149E+12 | 0.114616E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV_TOP WITH REHEAT
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.560207E+10 | 0.127478E+12 | 3479025.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.464699E+10 | 0.882250E+11 | 4713850.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.432426E+10 | 0.366134E+11 | 0.452687E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.468678E+10 | 0.143730E+11 | 0.121570E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.599873E+10 | 0.115600E+10 | 0.297247E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.956889E+10 | 0.433575E+09 | 0.912012E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.996303E+10 | 1902.11 | 0.124036E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.992678E+10 | 4514506.20 | 0.114658E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.602633E+10 | 0.277045E+10 | 0.440558E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.373195E+10 | 0.115127E+11 | 0.279138E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.439244E+10 | 0.467410E+11 | 0.197745E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.524547E+10 | 0.874582E+11 | 2632868.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.741137E+11 | 0.416765E+12 | 0.419285E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.373195E+10 | 1902.11 | 2632868.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.996303E+10 | 0.127478E+12 | 0.124036E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: CAV_BAS
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.146947E+11 | 0.998648E+09 | 83777.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.137966E+11 | 0.347387E+10 | 367811.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.165447E+11 | 0.00 | 26256360.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.152070E+11 | 0.00 | 0.574840E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.162335E+11 | 0.00 | 0.145144E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.162552E+11 | 0.00 | 0.501647E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.162850E+11 | 0.00 | 0.731938E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.176937E+11 | 0.00 | 0.777734E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.166865E+11 | 0.00 | 0.277808E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.159526E+11 | 0.00 | 0.188053E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.152183E+11 | 0.00 | 61208898.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.151286E+11 | 0.00 | 126762.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.189696E+12 | 0.447252E+10 | 0.251144E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.137966E+11 | 0.00 | 83777.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.176937E+11 | 0.347387E+10 | 0.777734E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER BASEMENT
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.991204E+11 | 0.00 | 0.101081E+11 | 0.00 | 0.415777E+10 | 0.00 | 0.00 | 0.00 | 0.122075E+12 | 0.00 | 0.00 | 0.00 |
February | 0.895281E+11 | 0.00 | 0.152400E+11 | 0.00 | 0.516669E+10 | 0.00 | 0.00 | 0.00 | 0.193720E+12 | 0.00 | 0.00 | 0.00 |
March | 0.991204E+11 | 0.00 | 0.245981E+11 | 0.00 | 0.769461E+10 | 0.00 | 0.00 | 0.00 | 0.244194E+12 | 0.00 | 0.00 | 0.00 |
April | 0.959229E+11 | 0.00 | 0.183605E+12 | 0.00 | 0.437382E+11 | 0.00 | 0.00 | 0.00 | 0.190871E+12 | 0.00 | 0.00 | 0.00 |
May | 0.991204E+11 | 0.00 | 0.263636E+11 | 0.00 | 0.835365E+10 | 0.00 | 0.00 | 0.00 | 0.400873E+11 | 0.00 | 0.00 | 0.00 |
June | 0.959229E+11 | 0.00 | 0.308452E+12 | 0.00 | 0.748487E+11 | 0.00 | 0.00 | 0.00 | 0.287819E+10 | 0.00 | 0.00 | 0.00 |
July | 0.991204E+11 | 0.00 | 0.899576E+12 | 0.00 | 0.200453E+12 | 0.00 | 0.00 | 0.00 | 415210.40 | 0.00 | 0.00 | 0.00 |
August | 0.991204E+11 | 0.00 | 0.113021E+13 | 0.00 | 0.249058E+12 | 0.00 | 0.00 | 0.00 | 0.420235E+10 | 0.00 | 0.00 | 0.00 |
September | 0.959229E+11 | 0.00 | 0.655526E+11 | 0.00 | 0.186612E+11 | 0.00 | 0.00 | 0.00 | 0.450499E+11 | 0.00 | 0.00 | 0.00 |
October | 0.991204E+11 | 0.00 | 0.175999E+11 | 0.00 | 0.598312E+10 | 0.00 | 0.00 | 0.00 | 0.177710E+12 | 0.00 | 0.00 | 0.00 |
November | 0.959229E+11 | 0.00 | 0.179195E+11 | 0.00 | 0.606837E+10 | 0.00 | 0.00 | 0.00 | 0.210325E+12 | 0.00 | 0.00 | 0.00 |
December | 0.991204E+11 | 0.00 | 0.225638E+11 | 0.00 | 0.753774E+10 | 0.00 | 0.00 | 0.00 | 0.267840E+12 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.116706E+13 | 0.00 | 0.272179E+13 | 0.00 | 0.631721E+12 | 0.00 | 0.00 | 0.00 | 0.149895E+13 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.895281E+11 | 0.00 | 0.101081E+11 | 0.00 | 0.415777E+10 | 0.00 | 0.00 | 0.00 | 415210.40 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.991204E+11 | 0.00 | 0.113021E+13 | 0.00 | 0.249058E+12 | 0.00 | 0.00 | 0.00 | 0.267840E+12 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER BOT
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.159788E+10 | 0.00 | 0.251045E+10 | 0.00 | 0.573297E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.144324E+10 | 0.00 | 0.916809E+10 | 0.00 | 0.189943E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.159788E+10 | 0.00 | 0.181283E+11 | 0.00 | 0.352818E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.154633E+10 | 0.00 | 0.245827E+11 | 0.00 | 0.467651E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.159788E+10 | 0.00 | 0.739241E+10 | 0.00 | 0.150536E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.154633E+10 | 0.00 | 0.141831E+11 | 0.00 | 0.301160E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.159788E+10 | 0.00 | 0.215798E+11 | 0.00 | 0.470876E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.159788E+10 | 0.00 | 0.279222E+11 | 0.00 | 0.598186E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.154633E+10 | 0.00 | 0.729996E+10 | 0.00 | 0.154183E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.159788E+10 | 0.00 | 0.127322E+11 | 0.00 | 0.250067E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.154633E+10 | 0.00 | 0.173571E+11 | 0.00 | 0.336352E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.159788E+10 | 0.00 | 0.231379E+11 | 0.00 | 0.449279E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.188137E+11 | 0.00 | 0.185994E+12 | 0.00 | 0.377838E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.144324E+10 | 0.00 | 0.251045E+10 | 0.00 | 0.573297E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.159788E+10 | 0.00 | 0.279222E+11 | 0.00 | 0.598186E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER MID
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.153522E+11 | 0.00 | 0.327576E+10 | 0.00 | 0.788806E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.138665E+11 | 0.00 | 0.590752E+11 | 0.00 | 0.125319E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.153522E+11 | 0.00 | 0.146850E+12 | 0.00 | 0.289829E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.148569E+11 | 0.00 | 0.217996E+12 | 0.00 | 0.418736E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.153522E+11 | 0.00 | 0.625103E+11 | 0.00 | 0.128497E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.148569E+11 | 0.00 | 0.131332E+12 | 0.00 | 0.280282E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.153522E+11 | 0.00 | 0.204002E+12 | 0.00 | 0.446071E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.153522E+11 | 0.00 | 0.262757E+12 | 0.00 | 0.564429E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.148569E+11 | 0.00 | 0.613600E+11 | 0.00 | 0.131230E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.153522E+11 | 0.00 | 0.101850E+12 | 0.00 | 0.202663E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.148569E+11 | 0.00 | 0.136433E+12 | 0.00 | 0.268314E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.153522E+11 | 0.00 | 0.182925E+12 | 0.00 | 0.362285E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.180759E+12 | 0.00 | 0.157037E+13 | 0.00 | 0.322554E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.138665E+11 | 0.00 | 0.327576E+10 | 0.00 | 0.788806E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.153522E+11 | 0.00 | 0.262757E+12 | 0.00 | 0.564429E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER TOP
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.156048E+10 | 0.00 | 0.168288E+09 | 0.00 | 39656275.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.140946E+10 | 0.00 | 0.419143E+10 | 0.00 | 0.899114E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.156048E+10 | 0.00 | 0.130701E+11 | 0.00 | 0.260278E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.151014E+10 | 0.00 | 0.206019E+11 | 0.00 | 0.398825E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.156048E+10 | 0.00 | 0.572603E+10 | 0.00 | 0.118611E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.151014E+10 | 0.00 | 0.129335E+11 | 0.00 | 0.277534E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.156048E+10 | 0.00 | 0.203591E+11 | 0.00 | 0.446484E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.156048E+10 | 0.00 | 0.261595E+11 | 0.00 | 0.563742E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.151014E+10 | 0.00 | 0.546739E+10 | 0.00 | 0.118467E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.156048E+10 | 0.00 | 0.840078E+10 | 0.00 | 0.169052E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.151014E+10 | 0.00 | 0.116634E+11 | 0.00 | 0.231662E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.156048E+10 | 0.00 | 0.162713E+11 | 0.00 | 0.325856E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.183734E+11 | 0.00 | 0.145013E+12 | 0.00 | 0.300439E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.140946E+10 | 0.00 | 0.168288E+09 | 0.00 | 39656275.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.156048E+10 | 0.00 | 0.261595E+11 | 0.00 | 0.563742E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.517615E+11 | 0.00 | 0.00 | 24469838.28 | 0.00 | 0.00 | 0.202739E+11 | 0.00 | 0.33 |
February | 0.221424E+11 | 0.00 | 0.00 | 63439513.93 | 0.00 | 0.00 | 0.418977E+11 | 0.00 | 0.39 |
March | 0.713257E+09 | 0.00 | 0.00 | 0.126808E+09 | 0.00 | 0.00 | 0.746748E+11 | 0.00 | 0.58 |
April | 0.409735E+09 | 0.333801E+09 | 0.00 | 0.117492E+09 | 1403838.29 | 0.00 | 0.669386E+11 | 0.00 | 0.80 |
May | 0.218100E+09 | 0.522153E+09 | 0.00 | 0.109462E+09 | 565983.52 | 0.00 | 0.654408E+11 | 0.00 | 1.30 |
June | 0.103229E+09 | 0.618517E+10 | 0.00 | 92476816.25 | 7028275.31 | 0.00 | 0.403743E+11 | 0.00 | 1.33 |
July | 0.137918E+09 | 0.112013E+11 | 0.00 | 80413422.00 | 19065667.65 | 0.00 | 0.230877E+11 | 0.00 | 1.28 |
August | 0.125657E+09 | 0.137855E+11 | 0.00 | 0.105674E+09 | 34662711.45 | 0.00 | 0.315558E+11 | 0.00 | 1.45 |
September | 0.240002E+09 | 0.120540E+10 | 0.00 | 0.120602E+09 | 25349037.65 | 0.00 | 0.574242E+11 | 0.00 | 1.22 |
October | 0.386449E+09 | 0.00 | 0.00 | 0.135430E+09 | 0.00 | 0.00 | 0.794614E+11 | 0.00 | 0.94 |
November | 0.329210E+10 | 0.00 | 0.00 | 0.122264E+09 | 0.00 | 0.00 | 0.722737E+11 | 0.00 | 0.68 |
December | 0.124572E+11 | 0.00 | 0.00 | 99258914.05 | 0.00 | 0.00 | 0.591462E+11 | 0.00 | 0.38 |
Annual Sum or Average | 0.919875E+11 | 0.332333E+11 | 0.00 | 0.119779E+10 | 88075513.88 | 0.00 | 0.632549E+12 | 0.00 | 0.89 |
Minimum of Months | 0.103229E+09 | 0.00 | 0.00 | 24469838.28 | 0.00 | 0.00 | 0.202739E+11 | 0.00 | 0.33 |
Maximum of Months | 0.517615E+11 | 0.137855E+11 | 0.00 | 0.135430E+09 | 34662711.45 | 0.00 | 0.794614E+11 | 0.00 | 1.45 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.267022E+11 | 0.00 | 0.00 | 23335583.14 | 0.00 | 1025857.15 | 0.167622E+11 | 0.00 | 0.42 |
February | 0.240076E+11 | 0.00 | 0.00 | 42387439.17 | 0.00 | 3295945.98 | 0.253686E+11 | 0.00 | 0.45 |
March | 0.340613E+10 | 0.00 | 0.00 | 98011760.19 | 0.00 | 0.00 | 0.527486E+11 | 0.00 | 0.57 |
April | 0.407168E+10 | 0.274484E+09 | 0.00 | 0.101451E+09 | 50747050.77 | 0.00 | 0.533296E+11 | 0.00 | 0.72 |
May | 0.352308E+10 | 0.510118E+09 | 0.00 | 87407698.28 | 56375971.24 | 0.00 | 0.467203E+11 | 0.00 | 0.94 |
June | 0.140451E+10 | 0.554893E+10 | 0.00 | 72172285.84 | 0.807951E+09 | 0.00 | 0.292812E+11 | 0.00 | 1.00 |
July | 0.362627E+10 | 0.110427E+11 | 0.00 | 51732471.53 | 0.223952E+10 | 0.00 | 0.133866E+11 | 0.00 | 1.08 |
August | 0.591421E+10 | 0.118946E+11 | 0.00 | 72523283.65 | 0.226653E+10 | 0.00 | 0.193492E+11 | 0.00 | 1.20 |
September | 0.276925E+10 | 0.625769E+09 | 0.00 | 85975765.94 | 46174868.09 | 0.00 | 0.390307E+11 | 0.00 | 0.85 |
October | 0.251587E+10 | 0.00 | 0.00 | 95767237.50 | 0.00 | 0.00 | 0.549747E+11 | 0.00 | 0.69 |
November | 0.390399E+10 | 0.00 | 0.00 | 80161122.53 | 0.00 | 0.00 | 0.480795E+11 | 0.00 | 0.58 |
December | 0.702052E+10 | 0.00 | 0.00 | 64488187.47 | 0.00 | 0.00 | 0.385228E+11 | 0.00 | 0.45 |
Annual Sum or Average | 0.888653E+11 | 0.298966E+11 | 0.00 | 0.875414E+09 | 0.546729E+10 | 4321803.13 | 0.437554E+12 | 0.00 | 0.75 |
Minimum of Months | 0.140451E+10 | 0.00 | 0.00 | 23335583.14 | 0.00 | 0.00 | 0.133866E+11 | 0.00 | 0.42 |
Maximum of Months | 0.267022E+11 | 0.118946E+11 | 0.00 | 0.101451E+09 | 0.226653E+10 | 3295945.98 | 0.549747E+11 | 0.00 | 1.20 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.368339E+12 | 0.00 | 0.00 | 7629658.90 | 0.00 | 0.155137E+11 | 0.686612E+10 | 0.00 | 0.41 |
February | 0.350513E+12 | 0.00 | 0.00 | 21135573.50 | 0.00 | 0.629898E+10 | 0.255971E+11 | 0.00 | 0.42 |
March | 0.204124E+12 | 0.00 | 0.00 | 0.213366E+09 | 0.00 | 0.120320E+10 | 0.145005E+12 | 0.00 | 0.48 |
April | 0.121184E+12 | 0.188217E+10 | 0.00 | 0.364654E+09 | 0.689541E+09 | 44512164.08 | 0.233247E+12 | 0.00 | 0.53 |
May | 0.440864E+11 | 0.379987E+10 | 0.00 | 0.577935E+09 | 0.666906E+09 | 0.00 | 0.341610E+12 | 0.00 | 0.77 |
June | 0.136258E+11 | 0.445118E+11 | 0.00 | 0.533586E+09 | 0.293340E+10 | 0.00 | 0.218896E+12 | 0.00 | 0.79 |
July | 0.146087E+11 | 0.855637E+11 | 0.00 | 0.385447E+09 | 0.849016E+10 | 0.00 | 0.101415E+12 | 0.00 | 0.79 |
August | 0.165360E+11 | 0.873023E+11 | 0.00 | 0.528220E+09 | 0.415022E+10 | 0.00 | 0.140060E+12 | 0.00 | 0.82 |
September | 0.447508E+11 | 0.515142E+10 | 0.00 | 0.567109E+09 | 0.501619E+09 | 0.00 | 0.274099E+12 | 0.00 | 0.69 |
October | 0.117054E+12 | 0.00 | 0.00 | 0.364166E+09 | 0.00 | 0.00 | 0.251048E+12 | 0.00 | 0.50 |
November | 0.189608E+12 | 0.00 | 0.00 | 0.175074E+09 | 0.00 | 0.208376E+10 | 0.136000E+12 | 0.00 | 0.46 |
December | 0.259875E+12 | 0.00 | 0.00 | 30889075.07 | 0.00 | 0.504504E+10 | 0.247440E+11 | 0.00 | 0.41 |
Annual Sum or Average | 0.174430E+13 | 0.228211E+12 | 0.00 | 0.376921E+10 | 0.174318E+11 | 0.301892E+11 | 0.189859E+13 | 0.00 | 0.59 |
Minimum of Months | 0.136258E+11 | 0.00 | 0.00 | 7629658.90 | 0.00 | 0.00 | 0.686612E+10 | 0.00 | 0.41 |
Maximum of Months | 0.368339E+12 | 0.873023E+11 | 0.00 | 0.577935E+09 | 0.849016E+10 | 0.155137E+11 | 0.341610E+12 | 0.00 | 0.82 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.220802E+11 | 0.00 | 0.00 | 28190.35 | 0.00 | 0.888635E+10 | 0.130534E+09 | 0.00 | 0.37 |
February | 0.239477E+11 | 0.00 | 0.00 | 426426.78 | 0.00 | 0.745780E+10 | 0.549201E+09 | 0.00 | 0.39 |
March | 0.209411E+11 | 0.00 | 0.00 | 5407996.25 | 265100.21 | 0.143644E+10 | 0.505285E+10 | 0.00 | 0.45 |
April | 0.145350E+11 | 0.238748E+09 | 0.00 | 18782210.78 | 77133501.16 | 0.324023E+09 | 0.140824E+11 | 0.00 | 0.50 |
May | 0.839899E+10 | 0.350396E+09 | 0.00 | 42863658.04 | 32727611.94 | 0.00 | 0.270682E+11 | 0.00 | 0.74 |
June | 0.277496E+10 | 0.468031E+10 | 0.00 | 44317032.65 | 0.436410E+09 | 0.00 | 0.187273E+11 | 0.00 | 0.80 |
July | 0.173209E+10 | 0.972048E+10 | 0.00 | 32784855.02 | 0.103847E+10 | 0.00 | 0.938699E+10 | 0.00 | 0.83 |
August | 0.205667E+10 | 0.865042E+10 | 0.00 | 45715746.74 | 0.479176E+09 | 0.00 | 0.121444E+11 | 0.00 | 0.82 |
September | 0.771056E+10 | 0.487119E+09 | 0.00 | 35317870.64 | 42945390.61 | 0.00 | 0.178830E+11 | 0.00 | 0.63 |
October | 0.171112E+11 | 0.00 | 0.00 | 11599586.74 | 7433042.62 | 0.332297E+09 | 0.105280E+11 | 0.00 | 0.45 |
November | 0.176168E+11 | 0.00 | 0.00 | 4954874.49 | 0.00 | 0.212385E+10 | 0.493456E+10 | 0.00 | 0.42 |
December | 0.183825E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.456228E+10 | 0.00 | 0.00 | 0.38 |
Annual Sum or Average | 0.157288E+12 | 0.241275E+11 | 0.00 | 0.242198E+09 | 0.211456E+10 | 0.251230E+11 | 0.120487E+12 | 0.00 | 0.57 |
Minimum of Months | 0.173209E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.37 |
Maximum of Months | 0.239477E+11 | 0.972048E+10 | 0.00 | 45715746.74 | 0.103847E+10 | 0.888635E+10 | 0.270682E+11 | 0.00 | 0.83 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.870500E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.475123E+10 | 0.00 | 0.00 | 0.41 |
February | 0.217845E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.379011E+10 | 0.00 | 0.00 | 0.39 |
March | 0.335892E+10 | 0.00 | 0.00 | 1141903.65 | 0.00 | 0.419406E+09 | 0.931669E+09 | 0.00 | 0.40 |
April | 0.256823E+10 | 49267044.65 | 0.00 | 3636055.18 | 6175335.58 | 32510165.75 | 0.242055E+10 | 0.00 | 0.57 |
May | 0.119343E+10 | 89442037.70 | 0.00 | 7841617.20 | 5510031.35 | 0.00 | 0.455676E+10 | 0.00 | 0.94 |
June | 0.460507E+09 | 0.102510E+10 | 0.00 | 8579686.99 | 0.101506E+09 | 0.00 | 0.344306E+10 | 0.00 | 1.21 |
July | 0.530572E+09 | 0.188476E+10 | 0.00 | 6403699.99 | 0.272903E+09 | 0.00 | 0.171283E+10 | 0.00 | 1.30 |
August | 0.863104E+09 | 0.198011E+10 | 0.00 | 7854188.05 | 0.283650E+09 | 0.00 | 0.209197E+10 | 0.00 | 1.34 |
September | 0.141905E+10 | 0.107225E+09 | 0.00 | 5829738.73 | 5782246.44 | 0.00 | 0.269096E+10 | 0.00 | 0.77 |
October | 0.268902E+10 | 0.00 | 0.00 | 2734161.99 | 0.00 | 0.00 | 0.213034E+10 | 0.00 | 0.48 |
November | 0.279885E+10 | 0.00 | 0.00 | 1244814.08 | 0.00 | 0.561142E+09 | 0.103003E+10 | 0.00 | 0.41 |
December | 0.237477E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.177300E+10 | 0.00 | 0.00 | 0.34 |
Annual Sum or Average | 0.213054E+11 | 0.513590E+10 | 0.00 | 45265865.85 | 0.675527E+09 | 0.113274E+11 | 0.210082E+11 | 0.00 | 0.71 |
Minimum of Months | 0.460507E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.34 |
Maximum of Months | 0.335892E+10 | 0.198011E+10 | 0.00 | 8579686.99 | 0.283650E+09 | 0.475123E+10 | 0.455676E+10 | 0.00 | 1.34 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.176643E+10 | 0.00 | 0.00 | 1199.86 | 0.00 | 0.437261E+10 | 1240497.85 | 0.00 | 0.72 |
February | 0.277247E+10 | 0.00 | 0.00 | 373468.58 | 0.00 | 0.334800E+10 | 0.205332E+09 | 0.00 | 0.69 |
March | 0.369598E+10 | 0.00 | 0.00 | 2803166.72 | 0.00 | 0.600270E+09 | 0.159715E+10 | 0.00 | 0.76 |
April | 0.331423E+10 | 53658942.17 | 0.00 | 5130142.50 | 6670604.40 | 67194867.18 | 0.272650E+10 | 0.00 | 1.01 |
May | 0.162268E+10 | 91373523.15 | 0.00 | 10237047.13 | 6276823.56 | 0.00 | 0.493434E+10 | 0.00 | 1.59 |
June | 0.790997E+09 | 0.931820E+09 | 0.00 | 8087776.69 | 0.108289E+09 | 0.00 | 0.345163E+10 | 0.00 | 1.88 |
July | 0.731503E+09 | 0.161194E+10 | 0.00 | 7002377.71 | 0.315855E+09 | 0.00 | 0.186154E+10 | 0.00 | 2.09 |
August | 0.131610E+10 | 0.146842E+10 | 0.00 | 7364006.23 | 0.365536E+09 | 0.00 | 0.207280E+10 | 0.00 | 1.98 |
September | 0.188553E+10 | 0.106503E+09 | 0.00 | 8726559.90 | 5651572.10 | 406262.16 | 0.312515E+10 | 0.00 | 1.40 |
October | 0.332075E+10 | 0.00 | 0.00 | 2992451.05 | 0.00 | 3389685.32 | 0.221259E+10 | 0.00 | 0.83 |
November | 0.354157E+10 | 0.00 | 0.00 | 370053.28 | 0.00 | 0.830132E+09 | 0.580290E+09 | 0.00 | 0.70 |
December | 0.233583E+10 | 0.00 | 0.00 | 54306.26 | 0.00 | 0.251137E+10 | 43616159.67 | 0.00 | 0.63 |
Annual Sum or Average | 0.270940E+11 | 0.426372E+10 | 0.00 | 53142555.91 | 0.808279E+09 | 0.117334E+11 | 0.228122E+11 | 0.00 | 1.19 |
Minimum of Months | 0.731503E+09 | 0.00 | 0.00 | 1199.86 | 0.00 | 0.00 | 1240497.85 | 0.00 | 0.63 |
Maximum of Months | 0.369598E+10 | 0.161194E+10 | 0.00 | 10237047.13 | 0.365536E+09 | 0.437261E+10 | 0.493434E+10 | 0.00 | 2.09 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.201216E+10 | 0.00 | 0.00 | 3792883.48 | 0.00 | 0.386839E+10 | 0.265522E+10 | 0.00 | 0.63 |
February | 0.301703E+10 | 0.00 | 0.00 | 5992769.93 | 0.00 | 0.246928E+10 | 0.348046E+10 | 0.00 | 0.64 |
March | 0.316477E+10 | 0.00 | 0.00 | 10196517.19 | 0.00 | 0.701499E+09 | 0.541793E+10 | 0.00 | 0.78 |
April | 0.327762E+10 | 0.112712E+09 | 0.00 | 9846517.46 | 3357025.69 | 83953680.48 | 0.557270E+10 | 0.00 | 1.00 |
May | 0.194458E+10 | 0.138775E+09 | 0.00 | 10354827.05 | 1359945.40 | 0.00 | 0.567206E+10 | 0.00 | 1.27 |
June | 0.987810E+09 | 0.115795E+10 | 0.00 | 8596007.56 | 0.137928E+09 | 0.00 | 0.339085E+10 | 0.00 | 1.40 |
July | 0.826129E+09 | 0.221205E+10 | 0.00 | 7042450.81 | 0.360463E+09 | 0.00 | 0.174484E+10 | 0.00 | 1.57 |
August | 0.134955E+10 | 0.237961E+10 | 0.00 | 11086965.86 | 0.372765E+09 | 0.00 | 0.260788E+10 | 0.00 | 1.79 |
September | 0.179093E+10 | 0.204669E+09 | 0.00 | 15139932.90 | 5023248.65 | 1952160.53 | 0.506250E+10 | 0.00 | 1.39 |
October | 0.269356E+10 | 0.00 | 0.00 | 14139709.95 | 0.00 | 38993505.22 | 0.780245E+10 | 0.00 | 1.08 |
November | 0.301386E+10 | 0.00 | 0.00 | 6358736.15 | 0.00 | 0.728230E+09 | 0.359420E+10 | 0.00 | 0.68 |
December | 0.222974E+10 | 0.00 | 0.00 | 6753562.82 | 0.00 | 0.220418E+10 | 0.318220E+10 | 0.00 | 0.57 |
Annual Sum or Average | 0.263077E+11 | 0.620576E+10 | 0.00 | 0.109301E+09 | 0.880897E+09 | 0.100965E+11 | 0.501833E+11 | 0.00 | 1.07 |
Minimum of Months | 0.826129E+09 | 0.00 | 0.00 | 3792883.48 | 0.00 | 0.00 | 0.174484E+10 | 0.00 | 0.57 |
Maximum of Months | 0.327762E+10 | 0.237961E+10 | 0.00 | 15139932.90 | 0.372765E+09 | 0.386839E+10 | 0.780245E+10 | 0.00 | 1.79 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.306615E+10 | 0.00 | 0.00 | 213867.76 | 0.00 | 0.413157E+10 | 0.171460E+09 | 0.00 | 0.87 |
February | 0.441351E+10 | 0.00 | 0.00 | 1498431.14 | 0.00 | 0.248031E+10 | 0.931168E+09 | 0.00 | 0.86 |
March | 0.358247E+10 | 0.00 | 0.00 | 6104345.56 | 0.00 | 37557709.23 | 0.411268E+10 | 0.00 | 1.02 |
April | 0.145898E+10 | 74482532.84 | 0.00 | 15305188.64 | 3693917.23 | 236147.50 | 0.804956E+10 | 0.00 | 1.62 |
May | 0.126342E+10 | 0.103015E+09 | 0.00 | 12518403.94 | 8839003.87 | 0.00 | 0.605787E+10 | 0.00 | 1.86 |
June | 0.460458E+09 | 0.110111E+10 | 0.00 | 11360274.05 | 0.112228E+09 | 0.00 | 0.438317E+10 | 0.00 | 2.33 |
July | 0.549457E+09 | 0.251328E+10 | 0.00 | 13274219.17 | 0.245481E+09 | 0.00 | 0.246301E+10 | 0.00 | 2.70 |
August | 0.846553E+09 | 0.285633E+10 | 0.00 | 17165519.81 | 0.164875E+09 | 0.00 | 0.373579E+10 | 0.00 | 3.05 |
September | 0.165186E+10 | 0.130721E+09 | 0.00 | 9755421.36 | 5933247.61 | 0.00 | 0.380509E+10 | 0.00 | 1.62 |
October | 0.261613E+10 | 0.00 | 0.00 | 6852222.05 | 0.00 | 0.00 | 0.505341E+10 | 0.00 | 1.20 |
November | 0.332554E+10 | 0.00 | 0.00 | 3773182.12 | 0.00 | 0.158996E+09 | 0.299092E+10 | 0.00 | 0.93 |
December | 0.472344E+10 | 0.00 | 0.00 | 1264413.66 | 0.00 | 0.414219E+09 | 0.976887E+09 | 0.00 | 0.78 |
Annual Sum or Average | 0.279580E+11 | 0.677894E+10 | 0.00 | 99085489.25 | 0.541051E+09 | 0.722290E+10 | 0.427310E+11 | 0.00 | 1.58 |
Minimum of Months | 0.460458E+09 | 0.00 | 0.00 | 213867.76 | 0.00 | 0.00 | 0.171460E+09 | 0.00 | 0.78 |
Maximum of Months | 0.472344E+10 | 0.285633E+10 | 0.00 | 17165519.81 | 0.245481E+09 | 0.413157E+10 | 0.804956E+10 | 0.00 | 3.05 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.179401E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.736899E+11 | 0.00 | 0.00 | 0.57 |
February | 0.365972E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.687810E+11 | 0.00 | 0.00 | 0.53 |
March | 0.198555E+11 | 0.00 | 0.00 | 27301.56 | 0.00 | 0.255241E+11 | 0.137135E+09 | 0.00 | 0.49 |
April | 0.272502E+11 | 0.371217E+09 | 0.00 | 7514333.31 | 53220373.72 | 0.864936E+10 | 0.498287E+10 | 0.00 | 0.50 |
May | 0.203713E+11 | 0.687155E+09 | 0.00 | 42684484.23 | 90141161.10 | 0.446445E+09 | 0.238389E+11 | 0.00 | 0.77 |
June | 0.751248E+10 | 0.874578E+10 | 0.00 | 58440569.56 | 0.414200E+09 | 5931279.06 | 0.221003E+11 | 0.00 | 0.98 |
July | 0.399717E+10 | 0.153899E+11 | 0.00 | 43200933.52 | 0.114414E+10 | 0.00 | 0.115109E+11 | 0.00 | 0.99 |
August | 0.718849E+10 | 0.147824E+11 | 0.00 | 48633290.87 | 0.680566E+09 | 0.00 | 0.116761E+11 | 0.00 | 0.94 |
September | 0.213475E+11 | 0.925675E+09 | 0.00 | 28886207.08 | 54308214.77 | 0.126767E+10 | 0.114795E+11 | 0.00 | 0.64 |
October | 0.328056E+11 | 0.00 | 0.00 | 1552260.73 | 0.00 | 0.717735E+10 | 0.188109E+10 | 0.00 | 0.46 |
November | 0.183748E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.248034E+11 | 0.00 | 0.00 | 0.48 |
December | 0.740394E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.455724E+11 | 0.00 | 0.00 | 0.50 |
Annual Sum or Average | 0.164897E+12 | 0.409022E+11 | 0.00 | 0.230939E+09 | 0.243658E+10 | 0.255918E+12 | 0.876068E+11 | 0.00 | 0.65 |
Minimum of Months | 0.740394E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.46 |
Maximum of Months | 0.328056E+11 | 0.153899E+11 | 0.00 | 58440569.56 | 0.114414E+10 | 0.736899E+11 | 0.238389E+11 | 0.00 | 0.99 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.386880E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.618077E+11 | 0.00 | 0.00 | 0.83 |
February | 0.100143E+11 | 0.00 | 0.00 | 656808.95 | 0.00 | 0.531517E+11 | 0.378619E+09 | 0.00 | 0.84 |
March | 0.258735E+11 | 0.00 | 0.00 | 10050950.01 | 0.00 | 0.217276E+11 | 0.624857E+10 | 0.00 | 0.91 |
April | 0.297599E+11 | 0.542582E+09 | 0.00 | 30936320.92 | 40766789.97 | 0.824095E+10 | 0.160712E+11 | 0.00 | 1.03 |
May | 0.205722E+11 | 0.810035E+09 | 0.00 | 82415179.40 | 76619540.87 | 0.185904E+09 | 0.381922E+11 | 0.00 | 1.52 |
June | 0.109697E+11 | 0.892242E+10 | 0.00 | 73250592.58 | 0.357796E+09 | 7070167.62 | 0.289918E+11 | 0.00 | 1.82 |
July | 0.473232E+10 | 0.153918E+11 | 0.00 | 71251499.28 | 0.137567E+10 | 0.00 | 0.176142E+11 | 0.00 | 1.93 |
August | 0.835825E+10 | 0.140646E+11 | 0.00 | 69175573.25 | 0.862082E+09 | 0.00 | 0.182452E+11 | 0.00 | 1.72 |
September | 0.211061E+11 | 0.101560E+10 | 0.00 | 71290523.82 | 54278594.29 | 0.119085E+10 | 0.224314E+11 | 0.00 | 1.33 |
October | 0.397515E+11 | 0.00 | 0.00 | 6903944.97 | 0.00 | 0.645460E+10 | 0.434162E+10 | 0.00 | 0.86 |
November | 0.217358E+11 | 0.00 | 0.00 | 556909.85 | 0.00 | 0.263699E+11 | 0.429482E+09 | 0.00 | 0.85 |
December | 0.417596E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.435684E+11 | 0.00 | 0.00 | 0.82 |
Annual Sum or Average | 0.200918E+12 | 0.407470E+11 | 0.00 | 0.416488E+09 | 0.276721E+10 | 0.222705E+12 | 0.152944E+12 | 0.00 | 1.21 |
Minimum of Months | 0.386880E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.82 |
Maximum of Months | 0.397515E+11 | 0.153918E+11 | 0.00 | 82415179.40 | 0.137567E+10 | 0.618077E+11 | 0.381922E+11 | 0.00 | 1.93 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.155518E+11 | 0.00 | 0.00 | 29515080.24 | 0.00 | 0.497473E+11 | 0.192629E+11 | 0.00 | 0.69 |
February | 0.188120E+11 | 0.00 | 0.00 | 46868971.54 | 0.00 | 0.381716E+11 | 0.266207E+11 | 0.00 | 0.71 |
March | 0.241518E+11 | 0.00 | 0.00 | 77468114.93 | 0.00 | 0.190930E+11 | 0.371154E+11 | 0.00 | 0.85 |
April | 0.268669E+11 | 0.109376E+10 | 0.00 | 72237300.05 | 31045757.27 | 0.805993E+10 | 0.399551E+11 | 0.00 | 0.95 |
May | 0.228823E+11 | 0.121499E+10 | 0.00 | 82616795.84 | 37563092.65 | 0.393653E+09 | 0.424051E+11 | 0.00 | 1.16 |
June | 0.125192E+11 | 0.103643E+11 | 0.00 | 68698252.24 | 0.537859E+09 | 7606716.93 | 0.249655E+11 | 0.00 | 1.24 |
July | 0.682562E+10 | 0.192753E+11 | 0.00 | 57416238.25 | 0.135291E+10 | 0.00 | 0.129364E+11 | 0.00 | 1.31 |
August | 0.834530E+10 | 0.197072E+11 | 0.00 | 95453793.14 | 0.817473E+09 | 0.00 | 0.207424E+11 | 0.00 | 1.45 |
September | 0.200271E+11 | 0.209703E+10 | 0.00 | 0.139519E+09 | 38459157.99 | 0.106040E+10 | 0.405363E+11 | 0.00 | 1.35 |
October | 0.263560E+11 | 0.00 | 0.00 | 0.126235E+09 | 0.00 | 0.481752E+10 | 0.622336E+11 | 0.00 | 1.06 |
November | 0.251420E+11 | 0.00 | 0.00 | 40317365.91 | 0.00 | 0.187594E+11 | 0.200456E+11 | 0.00 | 0.73 |
December | 0.969837E+10 | 0.00 | 0.00 | 44885143.60 | 0.00 | 0.370528E+11 | 0.171901E+11 | 0.00 | 0.69 |
Annual Sum or Average | 0.217178E+12 | 0.537526E+11 | 0.00 | 0.881231E+09 | 0.281531E+10 | 0.177163E+12 | 0.364009E+12 | 0.00 | 1.02 |
Minimum of Months | 0.682562E+10 | 0.00 | 0.00 | 29515080.24 | 0.00 | 0.00 | 0.129364E+11 | 0.00 | 0.69 |
Maximum of Months | 0.268669E+11 | 0.197072E+11 | 0.00 | 0.139519E+09 | 0.135291E+10 | 0.497473E+11 | 0.622336E+11 | 0.00 | 1.45 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.786976E+10 | 0.00 | 0.00 | 58319.33 | 0.00 | 0.610935E+11 | 0.146778E+09 | 0.00 | 0.88 |
February | 0.169233E+11 | 0.00 | 0.00 | 2900600.13 | 0.00 | 0.486423E+11 | 0.185897E+10 | 0.00 | 0.89 |
March | 0.297744E+11 | 0.00 | 0.00 | 11801542.61 | 0.00 | 0.213398E+11 | 0.737792E+10 | 0.00 | 0.98 |
April | 0.313112E+11 | 0.457883E+09 | 0.00 | 47154815.23 | 62659784.06 | 0.640479E+10 | 0.242899E+11 | 0.00 | 1.19 |
May | 0.258011E+11 | 0.821436E+09 | 0.00 | 79092384.37 | 0.114282E+09 | 0.330375E+09 | 0.309284E+11 | 0.00 | 1.53 |
June | 0.125777E+11 | 0.818099E+10 | 0.00 | 64950642.81 | 0.419286E+09 | 7527003.48 | 0.229834E+11 | 0.00 | 1.77 |
July | 0.613123E+10 | 0.174328E+11 | 0.00 | 76960205.04 | 0.762443E+09 | 0.00 | 0.122707E+11 | 0.00 | 1.81 |
August | 0.812126E+10 | 0.150983E+11 | 0.00 | 79135675.62 | 0.731697E+09 | 0.00 | 0.165211E+11 | 0.00 | 1.81 |
September | 0.271461E+11 | 0.118376E+10 | 0.00 | 55138780.08 | 48434865.74 | 0.119200E+10 | 0.152312E+11 | 0.00 | 1.35 |
October | 0.389588E+11 | 0.00 | 0.00 | 18365139.29 | 0.00 | 0.572916E+10 | 0.124345E+11 | 0.00 | 0.99 |
November | 0.282193E+11 | 0.00 | 0.00 | 1838044.05 | 0.00 | 0.223669E+11 | 0.132076E+10 | 0.00 | 0.91 |
December | 0.815420E+10 | 0.00 | 0.00 | 61404.47 | 0.00 | 0.419773E+11 | 0.152501E+09 | 0.00 | 0.87 |
Annual Sum or Average | 0.240988E+12 | 0.431752E+11 | 0.00 | 0.437458E+09 | 0.213880E+10 | 0.209084E+12 | 0.145516E+12 | 0.00 | 1.25 |
Minimum of Months | 0.613123E+10 | 0.00 | 0.00 | 58319.33 | 0.00 | 0.00 | 0.146778E+09 | 0.00 | 0.87 |
Maximum of Months | 0.389588E+11 | 0.174328E+11 | 0.00 | 79135675.62 | 0.762443E+09 | 0.610935E+11 | 0.309284E+11 | 0.00 | 1.81 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 80000959.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.725251E+10 | 0.00 | 0.00 | 0.62 |
February | 0.241938E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.704487E+10 | 0.00 | 0.00 | 0.58 |
March | 0.145487E+10 | 0.00 | 0.00 | 0.00 | 39754.39 | 0.281777E+10 | 0.00 | 0.00 | 0.55 |
April | 0.224780E+10 | 39162057.44 | 0.00 | 590115.28 | 11523149.79 | 0.134883E+10 | 0.406738E+09 | 0.00 | 0.56 |
May | 0.252623E+10 | 62359268.80 | 0.00 | 3357513.18 | 4907828.25 | 0.119214E+09 | 0.194680E+10 | 0.00 | 0.79 |
June | 0.935400E+09 | 0.889813E+09 | 0.00 | 5276067.64 | 70037815.42 | 61758019.04 | 0.202034E+10 | 0.00 | 1.02 |
July | 0.510918E+09 | 0.170877E+10 | 0.00 | 4008265.23 | 0.159995E+09 | 0.00 | 0.108316E+10 | 0.00 | 1.06 |
August | 0.796465E+09 | 0.142160E+10 | 0.00 | 4810665.52 | 94671060.59 | 0.00 | 0.109961E+10 | 0.00 | 0.97 |
September | 0.213924E+10 | 84261836.63 | 0.00 | 2354280.90 | 5073235.19 | 0.348046E+09 | 0.869866E+09 | 0.00 | 0.68 |
October | 0.265844E+10 | 0.00 | 0.00 | 12862.29 | 1114658.06 | 0.138771E+10 | 39150143.83 | 0.00 | 0.52 |
November | 0.129818E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.266418E+10 | 0.00 | 0.00 | 0.53 |
December | 41814435.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.423412E+10 | 0.00 | 0.00 | 0.54 |
Annual Sum or Average | 0.149313E+11 | 0.420597E+10 | 0.00 | 20409770.04 | 0.347363E+09 | 0.272790E+11 | 0.746566E+10 | 0.00 | 0.70 |
Minimum of Months | 41814435.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.52 |
Maximum of Months | 0.265844E+10 | 0.170877E+10 | 0.00 | 5276067.64 | 0.159995E+09 | 0.725251E+10 | 0.202034E+10 | 0.00 | 1.06 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.218161E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.504894E+10 | 0.00 | 0.00 | 0.75 |
February | 0.585683E+09 | 0.00 | 0.00 | 17166.16 | 0.00 | 0.479192E+10 | 17773341.16 | 0.00 | 0.78 |
March | 0.199147E+10 | 0.00 | 0.00 | 474268.80 | 41927.21 | 0.202488E+10 | 0.320044E+09 | 0.00 | 0.87 |
April | 0.216598E+10 | 56240891.36 | 0.00 | 2530449.74 | 10383639.38 | 0.111172E+10 | 0.133256E+10 | 0.00 | 1.02 |
May | 0.208409E+10 | 72260249.95 | 0.00 | 7377395.95 | 1460767.77 | 49670852.49 | 0.344590E+10 | 0.00 | 1.48 |
June | 0.981127E+09 | 0.922236E+09 | 0.00 | 7228033.30 | 54559082.52 | 48442490.28 | 0.290542E+10 | 0.00 | 1.87 |
July | 0.423270E+09 | 0.168013E+10 | 0.00 | 7150856.47 | 0.153319E+09 | 0.00 | 0.178353E+10 | 0.00 | 2.02 |
August | 0.714915E+09 | 0.140505E+10 | 0.00 | 7072840.04 | 0.103065E+09 | 0.00 | 0.179240E+10 | 0.00 | 1.76 |
September | 0.183581E+10 | 96250847.90 | 0.00 | 6031247.00 | 3771399.59 | 0.229718E+09 | 0.182099E+10 | 0.00 | 1.30 |
October | 0.321605E+10 | 0.00 | 0.00 | 251518.78 | 1175580.80 | 0.913708E+09 | 0.158266E+09 | 0.00 | 0.85 |
November | 0.148992E+10 | 0.00 | 0.00 | 1919.98 | 0.00 | 0.236836E+10 | 7137139.01 | 0.00 | 0.82 |
December | 0.188190E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.359954E+10 | 0.00 | 0.00 | 0.77 |
Annual Sum or Average | 0.158947E+11 | 0.423217E+10 | 0.00 | 38135696.22 | 0.327776E+09 | 0.201869E+11 | 0.135840E+11 | 0.00 | 1.19 |
Minimum of Months | 0.188190E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.75 |
Maximum of Months | 0.321605E+10 | 0.168013E+10 | 0.00 | 7377395.95 | 0.153319E+09 | 0.504894E+10 | 0.344590E+10 | 0.00 | 2.02 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.119748E+10 | 0.00 | 0.00 | 2197802.82 | 0.00 | 0.451586E+10 | 0.134192E+10 | 0.00 | 0.64 |
February | 0.156844E+10 | 0.00 | 0.00 | 3522128.01 | 0.00 | 0.376840E+10 | 0.193551E+10 | 0.00 | 0.68 |
March | 0.180590E+10 | 877.62 | 0.00 | 5695696.24 | 47511.43 | 0.194801E+10 | 0.299994E+10 | 0.00 | 0.82 |
April | 0.209307E+10 | 0.111378E+09 | 0.00 | 6005965.51 | 8083760.94 | 0.108690E+10 | 0.376023E+10 | 0.00 | 0.96 |
May | 0.247156E+10 | 0.103663E+09 | 0.00 | 7219403.31 | 924549.68 | 0.130305E+09 | 0.398307E+10 | 0.00 | 1.17 |
June | 0.126556E+10 | 0.106739E+10 | 0.00 | 6479499.28 | 85924987.73 | 73295402.46 | 0.252760E+10 | 0.00 | 1.30 |
July | 0.680475E+09 | 0.217313E+10 | 0.00 | 5861345.90 | 0.173930E+09 | 0.00 | 0.141195E+10 | 0.00 | 1.41 |
August | 0.803094E+09 | 0.190818E+10 | 0.00 | 10333804.13 | 0.107071E+09 | 0.00 | 0.219700E+10 | 0.00 | 1.51 |
September | 0.191114E+10 | 0.185289E+09 | 0.00 | 13062490.43 | 2660562.81 | 0.264451E+09 | 0.354550E+10 | 0.00 | 1.34 |
October | 0.235231E+10 | 1335159.89 | 0.00 | 9130846.18 | 356891.18 | 0.732416E+09 | 0.498350E+10 | 0.00 | 1.01 |
November | 0.187000E+10 | 0.00 | 0.00 | 2453510.66 | 0.00 | 0.202666E+10 | 0.143177E+10 | 0.00 | 0.72 |
December | 0.691256E+09 | 0.00 | 0.00 | 3218704.71 | 0.00 | 0.336515E+10 | 0.119914E+10 | 0.00 | 0.66 |
Annual Sum or Average | 0.187103E+11 | 0.555037E+10 | 0.00 | 75181197.17 | 0.379000E+09 | 0.179114E+11 | 0.313172E+11 | 0.00 | 1.02 |
Minimum of Months | 0.680475E+09 | 0.00 | 0.00 | 2197802.82 | 0.00 | 0.00 | 0.119914E+10 | 0.00 | 0.64 |
Maximum of Months | 0.247156E+10 | 0.217313E+10 | 0.00 | 13062490.43 | 0.173930E+09 | 0.451586E+10 | 0.498350E+10 | 0.00 | 1.51 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.565312E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.521345E+10 | 0.00 | 0.00 | 0.82 |
February | 0.112699E+10 | 0.00 | 0.00 | 232272.58 | 0.00 | 0.460823E+10 | 0.156642E+09 | 0.00 | 0.87 |
March | 0.212498E+10 | 0.00 | 0.00 | 978622.09 | 46585.95 | 0.217233E+10 | 0.650686E+09 | 0.00 | 0.98 |
April | 0.244690E+10 | 53026375.94 | 0.00 | 4060335.86 | 11265721.98 | 0.851889E+09 | 0.235675E+10 | 0.00 | 1.21 |
May | 0.279129E+10 | 73447246.25 | 0.00 | 7131951.80 | 5751209.32 | 94044830.97 | 0.292350E+10 | 0.00 | 1.56 |
June | 0.123346E+10 | 0.822415E+09 | 0.00 | 6256083.02 | 70658955.48 | 47283612.53 | 0.235920E+10 | 0.00 | 1.84 |
July | 0.591155E+09 | 0.195731E+10 | 0.00 | 8229230.94 | 0.111313E+09 | 0.00 | 0.133998E+10 | 0.00 | 1.95 |
August | 0.771194E+09 | 0.146774E+10 | 0.00 | 8354165.52 | 0.103031E+09 | 0.00 | 0.168217E+10 | 0.00 | 1.89 |
September | 0.249240E+10 | 0.103421E+09 | 0.00 | 5259914.31 | 4119185.90 | 0.288248E+09 | 0.135561E+10 | 0.00 | 1.38 |
October | 0.310026E+10 | 0.00 | 0.00 | 1550977.83 | 1306205.42 | 0.846459E+09 | 0.113325E+10 | 0.00 | 1.01 |
November | 0.194643E+10 | 0.00 | 0.00 | 163432.61 | 0.00 | 0.223476E+10 | 0.127071E+09 | 0.00 | 0.91 |
December | 0.535716E+09 | 0.00 | 0.00 | 333.11 | 0.00 | 0.355282E+10 | 4630684.80 | 0.00 | 0.83 |
Annual Sum or Average | 0.197261E+11 | 0.447736E+10 | 0.00 | 42217319.66 | 0.307492E+09 | 0.199095E+11 | 0.140895E+11 | 0.00 | 1.27 |
Minimum of Months | 0.535716E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.82 |
Maximum of Months | 0.310026E+10 | 0.195731E+10 | 0.00 | 8354165.52 | 0.111313E+09 | 0.521345E+10 | 0.292350E+10 | 0.00 | 1.95 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 46108742.21 | 0.00 | 0.00 | 2136625.62 | 0.00 | 0.00 | 0.989444E+09 | 0.00 | 0.28 |
February | 0.00 | 0.00 | 0.00 | 7545261.45 | 0.00 | 0.00 | 0.819393E+09 | 0.00 | 0.29 |
March | 0.00 | 0.00 | 0.00 | 15834640.47 | 0.00 | 0.00 | 0.743938E+09 | 0.00 | 0.31 |
April | 0.00 | 10188425.61 | 0.00 | 18276988.92 | 0.00 | 0.00 | 0.498244E+09 | 0.00 | 0.29 |
May | 0.00 | 11701013.39 | 0.00 | 3662335.86 | 0.00 | 0.00 | 0.262978E+09 | 0.00 | 0.29 |
June | 0.00 | 97845450.08 | 0.00 | 4819222.18 | 0.00 | 0.00 | 0.113483E+09 | 0.00 | 0.30 |
July | 0.00 | 0.166295E+09 | 0.00 | 2781278.35 | 0.00 | 0.00 | 15559091.95 | 0.00 | 0.28 |
August | 0.00 | 0.163310E+09 | 0.00 | 6883339.15 | 0.00 | 0.00 | 35932825.13 | 0.00 | 0.31 |
September | 0.00 | 19039498.07 | 0.00 | 3337464.86 | 0.00 | 0.00 | 0.268027E+09 | 0.00 | 0.29 |
October | 0.00 | 0.00 | 0.00 | 8689418.03 | 0.00 | 0.00 | 0.505812E+09 | 0.00 | 0.28 |
November | 0.00 | 0.00 | 0.00 | 12824742.91 | 0.00 | 0.00 | 0.642670E+09 | 0.00 | 0.28 |
December | 0.00 | 0.00 | 0.00 | 18410876.36 | 0.00 | 0.00 | 0.868505E+09 | 0.00 | 0.28 |
Annual Sum or Average | 46108742.21 | 0.468380E+09 | 0.00 | 0.105202E+09 | 0.00 | 0.00 | 0.576399E+10 | 0.00 | 0.29 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 2136625.62 | 0.00 | 0.00 | 15559091.95 | 0.00 | 0.28 |
Maximum of Months | 46108742.21 | 0.166295E+09 | 0.00 | 18410876.36 | 0.00 | 0.00 | 0.989444E+09 | 0.00 | 0.31 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.612510E+10 | 0.00 | 0.00 | 5288513.10 | 0.00 | 0.00 | 0.404097E+10 | 0.00 | 0.28 |
February | 0.00 | 0.00 | 0.00 | 55679829.78 | 0.00 | 0.00 | 0.821255E+10 | 0.00 | 0.29 |
March | 0.00 | 0.00 | 0.00 | 0.133339E+09 | 0.00 | 0.00 | 0.746417E+10 | 0.00 | 0.31 |
April | 0.00 | 0.101706E+09 | 0.00 | 0.164174E+09 | 0.00 | 0.00 | 0.499929E+10 | 0.00 | 0.29 |
May | 0.00 | 0.113879E+09 | 0.00 | 30548873.68 | 0.00 | 0.00 | 0.265042E+10 | 0.00 | 0.29 |
June | 0.00 | 0.972961E+09 | 0.00 | 44358574.37 | 0.00 | 0.00 | 0.114081E+10 | 0.00 | 0.30 |
July | 0.00 | 0.165804E+10 | 0.00 | 26282960.10 | 0.00 | 0.00 | 0.157319E+09 | 0.00 | 0.28 |
August | 0.00 | 0.163258E+10 | 0.00 | 65012006.00 | 0.00 | 0.00 | 0.362310E+09 | 0.00 | 0.31 |
September | 0.00 | 0.187353E+09 | 0.00 | 26749304.58 | 0.00 | 0.00 | 0.269150E+10 | 0.00 | 0.29 |
October | 0.00 | 0.00 | 0.00 | 72124906.35 | 0.00 | 0.00 | 0.507172E+10 | 0.00 | 0.28 |
November | 0.00 | 0.00 | 0.00 | 0.106137E+09 | 0.00 | 0.00 | 0.644754E+10 | 0.00 | 0.28 |
December | 0.00 | 0.00 | 0.00 | 0.154753E+09 | 0.00 | 0.00 | 0.871371E+10 | 0.00 | 0.28 |
Annual Sum or Average | 0.612510E+10 | 0.466652E+10 | 0.00 | 0.884448E+09 | 0.00 | 0.00 | 0.519523E+11 | 0.00 | 0.29 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 5288513.10 | 0.00 | 0.00 | 0.157319E+09 | 0.00 | 0.28 |
Maximum of Months | 0.612510E+10 | 0.165804E+10 | 0.00 | 0.164174E+09 | 0.00 | 0.00 | 0.871371E+10 | 0.00 | 0.31 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.805211E+09 | 0.00 | 0.00 | 296353.96 | 0.00 | 0.00 | 0.191853E+09 | 0.00 | 0.28 |
February | 3983437.27 | 0.00 | 0.00 | 4781591.99 | 0.00 | 0.00 | 0.817923E+09 | 0.00 | 0.29 |
March | 0.00 | 0.00 | 0.00 | 12394807.43 | 0.00 | 0.00 | 0.747377E+09 | 0.00 | 0.31 |
April | 0.00 | 10155643.12 | 0.00 | 15764996.47 | 0.00 | 0.00 | 0.500712E+09 | 0.00 | 0.29 |
May | 2277585.04 | 11453491.86 | 0.00 | 2782491.94 | 0.00 | 0.00 | 0.263809E+09 | 0.00 | 0.29 |
June | 0.00 | 97296859.26 | 0.00 | 4322453.76 | 0.00 | 0.00 | 0.114513E+09 | 0.00 | 0.30 |
July | 0.00 | 0.165646E+09 | 0.00 | 2608741.93 | 0.00 | 0.00 | 15866769.67 | 0.00 | 0.28 |
August | 0.00 | 0.163042E+09 | 0.00 | 6454287.58 | 0.00 | 0.00 | 36437297.29 | 0.00 | 0.31 |
September | 15110243.85 | 18739462.20 | 0.00 | 2231519.36 | 0.00 | 0.00 | 0.255034E+09 | 0.00 | 0.29 |
October | 0.00 | 0.00 | 0.00 | 6342337.87 | 0.00 | 0.00 | 0.508245E+09 | 0.00 | 0.28 |
November | 0.00 | 0.00 | 0.00 | 9748295.33 | 0.00 | 0.00 | 0.645834E+09 | 0.00 | 0.28 |
December | 0.00 | 0.00 | 0.00 | 14508063.68 | 0.00 | 0.00 | 0.872367E+09 | 0.00 | 0.28 |
Annual Sum or Average | 0.826582E+09 | 0.466334E+09 | 0.00 | 82235941.30 | 0.00 | 0.00 | 0.496997E+10 | 0.00 | 0.29 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 296353.96 | 0.00 | 0.00 | 15866769.67 | 0.00 | 0.28 |
Maximum of Months | 0.805211E+09 | 0.165646E+09 | 0.00 | 15764996.47 | 0.00 | 0.00 | 0.872367E+09 | 0.00 | 0.31 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.102716E+10 | 0.00 | 0.00 | 0.448127E+12 | 0.00 | 5.53 |
February | 0.00 | 0.00 | 0.00 | 0.159524E+10 | 0.00 | 0.00 | 0.704066E+12 | 0.00 | 11.30 |
March | 0.00 | 0.00 | 0.00 | 0.203463E+10 | 0.00 | 0.00 | 0.105259E+13 | 0.00 | 21.09 |
April | 0.00 | 0.366121E+10 | 0.00 | 0.236959E+10 | 0.00 | 0.00 | 0.109077E+13 | 0.00 | 32.91 |
May | 0.00 | 0.753480E+09 | 0.00 | 0.570986E+09 | 0.00 | 0.00 | 0.364472E+12 | 0.00 | 18.75 |
June | 0.00 | 0.204850E+11 | 0.00 | 0.843568E+09 | 0.00 | 0.00 | 0.358885E+12 | 0.00 | 31.96 |
July | 0.00 | 0.106603E+12 | 0.00 | 0.136017E+10 | 0.00 | 0.00 | 0.240214E+12 | 0.00 | 42.22 |
August | 0.00 | 0.498787E+11 | 0.00 | 0.169826E+10 | 0.00 | 0.00 | 0.247216E+12 | 0.00 | 43.74 |
September | 0.00 | 0.107076E+10 | 0.00 | 0.550730E+09 | 0.00 | 0.00 | 0.333883E+12 | 0.00 | 19.82 |
October | 0.00 | 0.00 | 0.00 | 0.110385E+10 | 0.00 | 0.00 | 0.752414E+12 | 0.00 | 20.18 |
November | 0.00 | 0.00 | 0.00 | 0.218034E+10 | 0.00 | 0.00 | 0.999591E+12 | 0.00 | 21.67 |
December | 0.00 | 0.00 | 0.00 | 0.367042E+10 | 0.00 | 0.00 | 0.132121E+13 | 0.00 | 19.87 |
Annual Sum or Average | 0.00 | 0.182453E+12 | 0.00 | 0.190049E+11 | 0.00 | 0.00 | 0.791344E+13 | 0.00 | 24.16 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.550730E+09 | 0.00 | 0.00 | 0.240214E+12 | 0.00 | 5.53 |
Maximum of Months | 0.00 | 0.106603E+12 | 0.00 | 0.367042E+10 | 0.00 | 0.00 | 0.132121E+13 | 0.00 | 43.74 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 08:43:43
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.390011E+12 | 0.738651E+11 | 0.00 | 0.260919E+13 | 0.304319E+12 |
February | 0.417981E+12 | 0.552980E+11 | 0.00 | 0.267976E+13 | 0.298807E+12 |
March | 0.614907E+12 | 0.491581E+11 | 0.00 | 0.327555E+13 | 0.332153E+12 |
April | 0.729991E+12 | 0.300472E+11 | 0.00 | 0.316116E+13 | 0.714266E+12 |
May | 0.828303E+12 | 0.170292E+11 | 0.00 | 0.249556E+13 | 0.591444E+12 |
June | 0.866292E+12 | 0.510048E+10 | 0.00 | 0.149632E+13 | 0.186604E+13 |
July | 0.868635E+12 | 0.231320E+10 | 0.00 | 0.677295E+12 | 0.309563E+13 |
August | 0.749907E+12 | 0.577277E+10 | 0.00 | 0.105440E+13 | 0.333740E+13 |
September | 0.532027E+12 | 0.150767E+11 | 0.00 | 0.212546E+13 | 0.869871E+12 |
October | 0.408566E+12 | 0.290239E+11 | 0.00 | 0.296443E+13 | 0.248494E+12 |
November | 0.267802E+12 | 0.476572E+11 | 0.00 | 0.304413E+13 | 0.318187E+12 |
December | 0.218964E+12 | 0.634565E+11 | 0.00 | 0.346339E+13 | 0.452955E+12 |
Annual Sum or Average | 0.689339E+13 | 0.393798E+12 | 0.00 | 0.290466E+14 | 0.124296E+14 |
Minimum of Months | 0.218964E+12 | 0.231320E+10 | 0.00 | 0.677295E+12 | 0.248494E+12 |
Maximum of Months | 0.868635E+12 | 0.738651E+11 | 0.00 | 0.346339E+13 | 0.333740E+13 |