Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:43
Tabular Output Report in Format: HTML
Building: OfficeLarge
Environment: RUNPERIOD 1 ** International Falls Intl Ap MN USA TMY3 WMO#=727470
Simulation Timestamp: 2023-10-16 08:43:41
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 08:43:41
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 33166.21 | 716.02 | 716.02 |
Net Site Energy | 33166.21 | 716.02 | 716.02 |
Total Source Energy | 94043.70 | 2030.29 | 2030.29 |
Net Source Energy | 94043.70 | 2030.29 | 2030.29 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 46320.38 |
Net Conditioned Building Area | 46320.38 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 4384.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 1497.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 3932.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 698.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 14676.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 1934.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 2526.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 381.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 477.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3105.63 |
Humidification | 1706.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 634.93 |
Heat Recovery | 56.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 892.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2280.17 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 27888.40 | 5277.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6020.73 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler | 0.00 | 4384.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 1497.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 3932.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 698.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 5334.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DataCenterPlugLoads | 9341.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 80.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 1848.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 5.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | General | 2526.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 381.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 477.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3105.63 |
Humidification | General | 1706.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 634.93 |
Heat Recovery | General | 56.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2280.17 | |
Water Heater | 0.00 | 892.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 4384.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 1497.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 3932.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 698.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 14676.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 1934.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 2526.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 381.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 477.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3105.63 |
Humidification | Unassigned | 1706.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 634.93 |
Heat Recovery | Unassigned | 56.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 0.00 | 892.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2280.17 |
Refrigeration | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 99.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 142.27 | 113.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.13 |
Other | 359.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 602.08 | 113.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.13 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 99.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 142.27 | 113.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.13 |
Other | 359.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 602.08 | 113.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.13 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 27888.395 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 27888.395 | 100.00 |
Total On-Site and Utility Electric Sources | 27888.395 | 100.00 |
Total Electricity End Uses | 27888.395 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | 0.00 |
Air to Air Heat Recovery for Cooling | 191.62 | 3.81 |
Air to Air Heat Recovery for Heating | 4833.40 | 96.19 |
High-Temperature Geothermal* | 0.00 | 0.00 |
Solar Water Thermal | 0.00 | 0.00 |
Solar Air Thermal | 0.00 | 0.00 |
Total On-Site Thermal Sources | 5025.02 | 100.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 6020.73 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 6020.73 | 100.00 |
Total Water End Uses | 6020.73 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 237.33 |
Time Setpoint Not Met During Occupied Cooling | 314.67 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 5941.83 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2013
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICELARGE
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 7
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_MN_INTERNATIONALFALLS
| Environment |ZoneCoolingSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |ZoneHeatingSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |ZoneElectricSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |SpaceGainsMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |PeakSpaceGainsMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |SpaceGainComponentsAtCoolingPeakMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |ComfortReportSimple55Monthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |OccupantComfortDataSummaryMonthly
| DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 | BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 |ChillerReportMonthly
| COOLSYS1 CHILLER1 | COOLSYS1 CHILLER2 |TowerReportMonthly
| CENTRAL TOWER | TOWERWATERSYS COOLTOWER 1 | TOWERWATERSYS COOLTOWER 2 |BoilerReportMonthly
| HEATSYS1 BOILER | CENTRAL BOILER |DXReportMonthly
| VAV_BOT WITH REHEAT COOLING COIL | VAV_MID WITH REHEAT COOLING COIL | VAV_TOP WITH REHEAT COOLING COIL | CAV_BAS COOLING COIL | AIRLOOP DATACENTER BASEMENT COOLING COIL | AIRLOOP DATACENTER BOT COOLING COIL | AIRLOOP DATACENTER MID COOLING COIL | AIRLOOP DATACENTER TOP COOLING COIL |WindowReportMonthly
| PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW |WindowEnergyReportMonthly
| PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW |WindowZoneSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |WindowEnergyZoneSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWHSYS1 WATER HEATER |DaylightingReportMonthly
| PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_4_DAYLCTRL |CoilReportMonthly
| VAV_BOT WITH REHEAT HEATING COIL | CORE_BOTTOM VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | VAV_MID WITH REHEAT HEATING COIL | CORE_MID VAV BOX REHEAT COIL | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | VAV_TOP WITH REHEAT HEATING COIL | CORE_TOP VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | CAV_BAS HEATING COIL | AIRLOOP DATACENTER BASEMENT HEATING COIL | AIRLOOP DATACENTER BOT HEATING COIL | AIRLOOP DATACENTER MID HEATING COIL | AIRLOOP DATACENTER TOP HEATING COIL | AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | AIRLOOP DATACENTER BOT_SUPPHEATCOIL | AIRLOOP DATACENTER MID_SUPPHEATCOIL | AIRLOOP DATACENTER TOP_SUPPHEATCOIL | VAV_BOT WITH REHEAT COOLING COIL | VAV_MID WITH REHEAT COOLING COIL | VAV_TOP WITH REHEAT COOLING COIL | CAV_BAS COOLING COIL | AIRLOOP DATACENTER BASEMENT COOLING COIL | AIRLOOP DATACENTER BOT COOLING COIL | AIRLOOP DATACENTER MID COOLING COIL | AIRLOOP DATACENTER TOP COOLING COIL |PlantLoopDemandReportMonthly
| HEATSYS1 | COOLSYS1_SUPPLY | COOLSYS1_DEMAND | SINGLE WATER PLANT LOOP | SWHSYS1 | TOWERWATERSYS |FanReportMonthly
| CAV_BAS FAN | VAV_BOT WITH REHEAT FAN | VAV_MID WITH REHEAT FAN | VAV_TOP WITH REHEAT FAN | AIRLOOP DATACENTER BASEMENT SUPPLY FAN | AIRLOOP DATACENTER BOT SUPPLY FAN | AIRLOOP DATACENTER MID SUPPLY FAN | AIRLOOP DATACENTER TOP SUPPLY FAN |PumpReportMonthly
| HEATSYS1 PUMP | COOLSYS1 PUMP SECONDARY | COOLSYS1 CHILLER1 PUMP | COOLSYS1 CHILLER2 PUMP | PLANT CIRC PUMP | SWHSYS1 PUMP | TOWERWATERSYS PUMP |CondLoopDemandReportMonthly
| HEATSYS1 | COOLSYS1_SUPPLY | COOLSYS1_DEMAND | SINGLE WATER PLANT LOOP | SWHSYS1 | TOWERWATERSYS |ZoneTemperatureOscillationReportMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |AirLoopSystemEnergyAndWaterUseMonthly
| VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | CAV_BAS | AIRLOOP DATACENTER BASEMENT | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |AirLoopSystemComponentLoadsMonthly
| VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | CAV_BAS | AIRLOOP DATACENTER BASEMENT | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |AirLoopSystemComponentEnergyUseMonthly
| VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | CAV_BAS | AIRLOOP DATACENTER BASEMENT | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |MechanicalVentilationLoadsMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 08:43:41
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:43 |
RunPeriod | RUNPERIOD 1 |
Weather File | International Falls Intl Ap MN USA TMY3 WMO#=727470 |
Latitude [deg] | 48.57 |
Longitude [deg] | -93.4 |
Elevation [m] | 359.00 |
Time Zone | -6.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 12183.89 | 3655.17 | 2436.78 | 3655.17 | 2436.78 |
Above Ground Wall Area [m2] | 11589.54 | 3476.86 | 2317.91 | 3476.86 | 2317.91 |
Window Opening Area [m2] | 4635.80 | 1390.74 | 927.16 | 1390.74 | 927.16 |
Gross Window-Wall Ratio [%] | 38.05 | 38.05 | 38.05 | 38.05 | 38.05 |
Above Ground Window-Wall Ratio [%] | 40.00 | 40.00 | 40.00 | 40.00 | 40.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 12183.89 | 3655.17 | 2436.78 | 3655.17 | 2436.78 |
Above Ground Wall Area [m2] | 11589.54 | 3476.86 | 2317.91 | 3476.86 | 2317.91 |
Window Opening Area [m2] | 4635.80 | 1390.74 | 927.16 | 1390.74 | 927.16 |
Gross Window-Wall Ratio [%] | 38.05 | 38.05 | 38.05 | 38.05 | 38.05 |
Above Ground Window-Wall Ratio [%] | 40.00 | 40.00 | 40.00 | 40.00 | 40.00 |
Total | |
Gross Roof Area [m2] | 3563.11 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
BASEMENT | 2779.43 | Yes | Yes | 6779.02 | 1.00 | 0.00 | 397.05 | 0.00 | 0.00 | 10.2732 | 18.58 | 4.8418 |
CORE_BOTTOM | 2496.12 | Yes | Yes | 6849.35 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.2732 | 18.58 | 8.0697 |
CORE_MID | 2496.12 | Yes | Yes | 6849.35 | 10.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.2732 | 18.58 | 8.0696 |
CORE_TOP | 2496.12 | Yes | Yes | 6849.35 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.2732 | 18.58 | 8.0696 |
PERIMETER_BOT_ZN_3 | 313.41 | Yes | Yes | 860.00 | 1.00 | 200.61 | 0.00 | 115.90 | 115.90 | 10.2732 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_2 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 77.26 | 77.26 | 10.2732 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_1 | 313.42 | Yes | Yes | 860.02 | 1.00 | 200.61 | 0.00 | 115.90 | 115.90 | 10.2732 | 18.58 | 8.0699 |
PERIMETER_BOT_ZN_4 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 77.26 | 77.26 | 10.2732 | 18.58 | 8.0699 |
PERIMETER_MID_ZN_3 | 313.41 | Yes | Yes | 860.00 | 10.00 | 200.61 | 0.00 | 115.90 | 115.90 | 10.2732 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_2 | 201.98 | Yes | Yes | 554.22 | 10.00 | 133.74 | 0.00 | 77.26 | 77.26 | 10.2732 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_1 | 313.42 | Yes | Yes | 860.02 | 10.00 | 200.61 | 0.00 | 115.90 | 115.90 | 10.2732 | 18.58 | 8.0699 |
PERIMETER_MID_ZN_4 | 201.98 | Yes | Yes | 554.22 | 10.00 | 133.74 | 0.00 | 77.26 | 77.26 | 10.2732 | 18.58 | 8.0699 |
PERIMETER_TOP_ZN_3 | 313.41 | Yes | Yes | 860.00 | 1.00 | 200.61 | 0.00 | 115.90 | 115.90 | 10.2732 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_2 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 77.26 | 77.26 | 10.2732 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_1 | 313.42 | Yes | Yes | 860.02 | 1.00 | 200.61 | 0.00 | 115.90 | 115.90 | 10.2732 | 18.58 | 8.0699 |
PERIMETER_TOP_ZN_4 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 77.26 | 77.26 | 10.2732 | 18.58 | 8.0699 |
GROUNDFLOOR_PLENUM | 3563.11 | Yes | No | 4344.14 | 1.00 | 297.11 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
MIDFLOOR_PLENUM | 3563.11 | Yes | No | 4344.14 | 10.00 | 297.11 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
TOPFLOOR_PLENUM | 3563.11 | Yes | No | 4344.14 | 1.00 | 297.11 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
DATACENTER_BOT_ZN_6 | 36.20 | Yes | Yes | 99.34 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.8735 | 18.58 | 215.2992 |
DATACENTER_MID_ZN_6 | 36.20 | Yes | Yes | 99.34 | 10.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.8735 | 18.58 | 215.2992 |
DATACENTER_TOP_ZN_6 | 36.20 | Yes | Yes | 99.34 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.8735 | 18.58 | 215.2992 |
DATACENTER_BASEMENT_ZN_6 | 783.68 | Yes | Yes | 1911.37 | 1.00 | 0.00 | 197.31 | 0.00 | 0.00 | 10.2732 | 18.58 | 484.4232 |
Total | 46320.38 | 126016.35 | 8024.24 | 594.36 | 4635.80 | 4635.80 | 10.3445 | 18.58 | 17.8789 | |||
Conditioned Total | 46320.38 | 126016.35 | 8024.24 | 594.36 | 4635.80 | 4635.80 | 10.3445 | 18.58 | 17.8789 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 42757.27 | 52129.67 | 3565.29 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
BASEMENT | 2779.43 | Yes | Yes | 1.00 | BASEMENT | GENERAL | BASEMENT | 10.2732 | 18.58 | 4.8418 | |
CORE_BOTTOM | 2496.12 | Yes | Yes | 1.00 | CORE_BOTTOM | GENERAL | CORE_BOTTOM | 10.2732 | 18.58 | 8.0697 | |
CORE_MID | 2496.12 | Yes | Yes | 10.00 | CORE_MID | GENERAL | CORE_MID | 10.2732 | 18.58 | 8.0696 | |
CORE_TOP | 2496.12 | Yes | Yes | 1.00 | CORE_TOP | GENERAL | CORE_TOP | 10.2732 | 18.58 | 8.0696 | |
PERIMETER_BOT_ZN_3 | 313.41 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_3 | GENERAL | PERIMETER_BOT_ZN_3 | 10.2732 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_2 | 201.98 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_2 | GENERAL | PERIMETER_BOT_ZN_2 | 10.2732 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_1 | 313.42 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_1 | GENERAL | PERIMETER_BOT_ZN_1 | 10.2732 | 18.58 | 8.0699 | |
PERIMETER_BOT_ZN_4 | 201.98 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_4 | GENERAL | PERIMETER_BOT_ZN_4 | 10.2732 | 18.58 | 8.0699 | |
PERIMETER_MID_ZN_3 | 313.41 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_3 | GENERAL | PERIMETER_MID_ZN_3 | 10.2732 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_2 | 201.98 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_2 | GENERAL | PERIMETER_MID_ZN_2 | 10.2732 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_1 | 313.42 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_1 | GENERAL | PERIMETER_MID_ZN_1 | 10.2732 | 18.58 | 8.0699 | |
PERIMETER_MID_ZN_4 | 201.98 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_4 | GENERAL | PERIMETER_MID_ZN_4 | 10.2732 | 18.58 | 8.0699 | |
PERIMETER_TOP_ZN_3 | 313.41 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_3 | GENERAL | PERIMETER_TOP_ZN_3 | 10.2732 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_2 | 201.98 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_2 | GENERAL | PERIMETER_TOP_ZN_2 | 10.2732 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_1 | 313.42 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_1 | GENERAL | PERIMETER_TOP_ZN_1 | 10.2732 | 18.58 | 8.0699 | |
PERIMETER_TOP_ZN_4 | 201.98 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_4 | GENERAL | PERIMETER_TOP_ZN_4 | 10.2732 | 18.58 | 8.0699 | |
GROUNDFLOOR_PLENUM | 3563.11 | Yes | No | 1.00 | GROUNDFLOOR_PLENUM | GENERAL | GROUNDFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
MIDFLOOR_PLENUM | 3563.11 | Yes | No | 10.00 | MIDFLOOR_PLENUM | GENERAL | MIDFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
TOPFLOOR_PLENUM | 3563.11 | Yes | No | 1.00 | TOPFLOOR_PLENUM | GENERAL | TOPFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
DATACENTER_BOT_ZN_6 | 36.20 | Yes | Yes | 1.00 | DATACENTER_BOT_ZN_6 | GENERAL | DATACENTER_BOT_ZN_6 | 17.8735 | 18.58 | 215.2992 | |
DATACENTER_MID_ZN_6 | 36.20 | Yes | Yes | 10.00 | DATACENTER_MID_ZN_6 | GENERAL | DATACENTER_MID_ZN_6 | 17.8735 | 18.58 | 215.2992 | |
DATACENTER_TOP_ZN_6 | 36.20 | Yes | Yes | 1.00 | DATACENTER_TOP_ZN_6 | GENERAL | DATACENTER_TOP_ZN_6 | 17.8735 | 18.58 | 215.2992 | |
DATACENTER_BASEMENT_ZN_6 | 783.68 | Yes | Yes | 1.00 | DATACENTER_BASEMENT_ZN_6 | GENERAL | DATACENTER_BASEMENT_ZN_6 | 10.2732 | 18.58 | 484.4232 | |
Total | 46320.38 | 10.3445 | 9.29 | 17.8789 | |||||||
Conditioned Total | 46320.38 | 10.3445 | 9.29 | 17.8789 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 42757.27 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 46320.38 | 46320.38 | 0.00 | 42757.27 | 3.1788 | 60.38 | 10.8345 |
Total | 46320.38 | 46320.38 | 0.00 | 42757.27 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:43:41
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 08-AUG-15:20 | 09-JAN-07:10 | - | - | - | - | - | - | - | - | - | - | 18-MAY-15:00 |
Heating | 0.00 | 3461431.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 464056.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 332294.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 778371.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 84450.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 305999.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 53121.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 89285.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 6524.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 33307.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 2114105.39 | 3494739.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler | 0.00 | 3461431.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 464056.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 332294.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 305206.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DataCenterPlugLoads | 473165.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 5015.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 79171.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 263.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | General | 305999.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 53121.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 89285.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 6524.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Water Heater | 0.00 | 33307.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:43:41
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 4753.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 4742.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 12453.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 2211.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 46480.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 6127.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 8002.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 1208.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 1511.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 5405.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 178.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 967.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 88322.55 | 5721.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 102.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 102.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 268.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 47.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1003.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 132.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 172.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 26.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 32.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 116.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 3.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 20.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1906.78 | 123.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 102.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 102.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 268.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 47.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1003.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 132.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 172.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 26.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 32.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 116.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 3.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 20.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1906.78 | 123.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:43:41
AirTerminal:SingleDuct:ConstantVolume:NoReheatDesign Size Maximum Air Flow Rate [m3/s] | |
BASEMENT DIRECT AIR | 6.25 |
DATACENTER_BOT_ZN_6 DIRECT AIR | 0.539345 |
DATACENTER_MID_ZN_6 DIRECT AIR | 5.19 |
DATACENTER_TOP_ZN_6 DIRECT AIR | 0.526377 |
DATACENTER_BASEMENT_ZN_6 DIRECT AIR | 22.35 |
Design Size Maximum Air Flow Rate [m3/s] | Design Size Constant Minimum Air Flow Fraction | User-Specified Constant Minimum Air Flow Fraction | Design Size Minimum Air Flow Rate [m3/s] | Design Size Maximum Flow Fraction during Reheat [] | User-Specified Maximum Flow Fraction during Reheat [] | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | Design Size Maximum Reheat Water Flow Rate [m3/s] | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | |
CORE_BOTTOM VAV BOX COMPONENT | 6.44 | 0.295257 | 0.309000 | 1.99 | 0.787351 | 0.500000 | 0.001290 | 0.000243 | 1.99 | 12.80 | 0.008000 |
CORE_MID VAV BOX COMPONENT | 60.59 | 0.313895 | 0.322000 | 19.51 | 0.837054 | 0.500000 | 0.001214 | 0.004705 | 19.51 | 12.80 | 0.008000 |
CORE_TOP VAV BOX COMPONENT | 5.96 | 0.319355 | 0.336000 | 2.00 | 0.851613 | 0.500000 | 0.001193 | 0.000980 | 3.48 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | 1.07 | 0.223050 | 0.233000 | 0.249474 | 0.594801 | 0.500000 | 0.001708 | 0.000196 | 0.697535 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | 1.56 | 0.098396 | 0.200000 | 0.312828 | 0.300000 | 0.500000 | 0.003872 | 0.000134 | 0.476691 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | 1.91 | 0.125142 | 0.200000 | 0.381689 | 0.333711 | 0.500000 | 0.003045 | 0.000214 | 0.761200 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | 1.87 | 0.082244 | 0.200000 | 0.374262 | 0.300000 | 0.500000 | 0.004633 | 0.000114 | 0.407207 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_3 VAV BOX COMPONENT | 10.10 | 0.236510 | 0.243000 | 2.45 | 0.630694 | 0.500000 | 0.001611 | 0.002751 | 9.79 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_2 VAV BOX COMPONENT | 16.71 | 0.092092 | 0.200000 | 3.34 | 0.300000 | 0.500000 | 0.004137 | 0.001826 | 6.50 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_1 VAV BOX COMPONENT | 19.63 | 0.121668 | 0.200000 | 3.93 | 0.324449 | 0.500000 | 0.003131 | 0.002790 | 9.93 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_4 VAV BOX COMPONENT | 17.74 | 0.086743 | 0.200000 | 3.55 | 0.300000 | 0.500000 | 0.004392 | 0.001802 | 6.42 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | 1.23 | 0.193826 | 0.226000 | 0.278463 | 0.516870 | 0.500000 | 0.001966 | 0.000346 | 1.23 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | 1.67 | 0.092223 | 0.200000 | 0.333766 | 0.300000 | 0.500000 | 0.004131 | 0.000228 | 0.813610 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | 2.06 | 0.115972 | 0.200000 | 0.411868 | 0.309259 | 0.500000 | 0.003285 | 0.000350 | 1.25 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | 1.84 | 0.083536 | 0.200000 | 0.368475 | 0.300000 | 0.500000 | 0.004561 | 0.000229 | 0.813878 | 12.80 | 0.008000 |
Design Size Rated Capacity [W] | Design Size Maximum Water Flow Rate [m3/s] | Design Size U-Factor Times Area Value [W/K] | |
CORE_BOTTOM VAV BOX REHEAT COIL | 27788.12 | 0.000243 | 586.02 |
CORE_MID VAV BOX REHEAT COIL | 537834.02 | 0.004705 | 13326.87 |
CORE_TOP VAV BOX REHEAT COIL | 112058.31 | 0.000980 | 2957.10 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | 22409.42 | 0.000196 | 590.99 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | 15312.74 | 0.000134 | 403.81 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | 24451.15 | 0.000214 | 644.79 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | 13084.87 | 0.000114 | 345.11 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | 314442.50 | 0.002751 | 8290.21 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | 208689.56 | 0.001826 | 5501.95 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | 318931.68 | 0.002790 | 8408.50 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | 206019.99 | 0.001802 | 5431.60 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | 39548.70 | 0.000346 | 1042.56 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | 26114.19 | 0.000228 | 688.40 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | 40047.71 | 0.000350 | 1055.71 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | 26122.68 | 0.000229 | 688.62 |
VAV_BOT WITH REHEAT HEATING COIL | 128608.27 | 0.001125 | 1885.03 |
VAV_MID WITH REHEAT HEATING COIL | 1308944.79 | 0.011451 | 18738.58 |
VAV_TOP WITH REHEAT HEATING COIL | 129416.38 | 0.001132 | 1907.21 |
CAV_BAS HEATING COIL | 335252.24 | 0.002933 | 7091.33 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT | 6.43 | 3.31 | 12.86 | 3.42 | 10.72 | 10.72 | 0.300000 | 0.319150 | 10.72 |
VAV_MID WITH REHEAT | 62.39 | 32.78 | 124.78 | 48.08 | 100.09 | 100.09 | 0.300000 | 0.480360 | 100.09 |
VAV_TOP WITH REHEAT | 6.38 | 3.39 | 12.76 | 7.59 | 11.00 | 11.00 | 0.300000 | 0.689990 | 11.00 |
CAV_BAS | 6.25 | 6.25 | 6.25 | 6.25 | 6.25 | 6.25 | 1.00 | 1.00 | 6.25 |
AIRLOOP DATACENTER BASEMENT | 22.35 | 22.35 | 22.35 | 22.35 | 22.35 | 22.35 | 1.00 | 0.999916 | 22.35 |
AIRLOOP DATACENTER BOT | 0.539345 | 0.539345 | 0.539345 | 0.539345 | 0.539345 | 0.539345 | 1.00 | 1.00 | 0.539345 |
AIRLOOP DATACENTER MID | 5.19 | 5.19 | 5.19 | 5.19 | 5.19 | 5.19 | 1.00 | 1.00 | 5.19 |
AIRLOOP DATACENTER TOP | 0.526377 | 0.526377 | 0.526377 | 0.526377 | 0.526377 | 0.526377 | 1.00 | 1.00 | 0.526377 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT_OA_CONTROLLER | 10.72 | 2.54 |
VAV_MID WITH REHEAT_OA_CONTROLLER | 100.09 | 25.38 |
VAV_TOP WITH REHEAT_OA_CONTROLLER | 11.00 | 2.54 |
CAV_BAS_OA_CONTROLLER | 6.25 | 1.20 |
AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER | 22.35 | 0.338393 |
AIRLOOP DATACENTER BOT_OA_CONTROLLER | 0.539345 | 0.015632 |
AIRLOOP DATACENTER MID_OA_CONTROLLER | 5.19 | 0.156323 |
AIRLOOP DATACENTER TOP_OA_CONTROLLER | 0.526377 | 0.015632 |
Design Size Nominal Supply Air Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT OA HEAT RECOVERY | 2.54 |
VAV_MID WITH REHEAT OA HEAT RECOVERY | 25.38 |
VAV_TOP WITH REHEAT OA HEAT RECOVERY | 2.54 |
CAV_BAS OA HEAT RECOVERY | 1.20 |
Design Size Design Inlet Air Temperature [C] | Design Size Design Inlet Water Temperature [C] | Design Size Design Outlet Air Temperature [C] | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | Design Size Design Coil Load [W] | Design Size Design Water Flow Rate [m3/s] | Design Size Design Air Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT COOLING COIL | 25.45 | 6.67 | 10.88 | 0.009762 | 0.008500 | 223699.74 | 0.009517 | 10.72 |
VAV_MID WITH REHEAT COOLING COIL | 25.57 | 6.67 | 10.88 | 0.009890 | 0.008500 | 2140844.70 | 0.091076 | 100.09 |
VAV_TOP WITH REHEAT COOLING COIL | 25.41 | 6.67 | 10.88 | 0.009773 | 0.008500 | 229452.62 | 0.009761 | 11.00 |
CAV_BAS COOLING COIL | 25.18 | 6.67 | 11.36 | 0.009773 | 0.008500 | 125039.64 | 0.005319 | 6.25 |
Design Size Maximum Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT FAN | 10.72 |
VAV_MID WITH REHEAT FAN | 100.09 |
VAV_TOP WITH REHEAT FAN | 11.00 |
Maximum Actuated Flow [m3/s] | Controller Convergence Tolerance | |
VAV_BOT WITH REHEAT_COOLC_CONTROLLER | 0.009517 | 0.000050 |
VAV_BOT WITH REHEAT_HEATC_CONTROLLER | 0.001125 | |
VAV_MID WITH REHEAT_COOLC_CONTROLLER | 0.091076 | 0.000005 |
VAV_MID WITH REHEAT_HEATC_CONTROLLER | 0.011451 | |
VAV_TOP WITH REHEAT_COOLC_CONTROLLER | 0.009761 | 0.000049 |
VAV_TOP WITH REHEAT_HEATC_CONTROLLER | 0.001132 | |
CAV_BAS_COOLC_CONTROLLER | 0.005319 | 0.000090 |
CAV_BAS_HEATC_CONTROLLER | 0.002933 |
Design Size Maximum Flow Rate [m3/s] | |
CAV_BAS FAN | 6.25 |
Design Size Rated Air Flow Rate [m3/s] | Design Size Rated Total Cooling Capacity [W] | Design Size Rated Sensible Cooling Capacity [W] | Design Size Rated Water Flow Rate [m3/s] | |
AIRLOOP DATACENTER BASEMENT COOLING COIL | 22.35 | 437947.87 | 302632.26 | 0.010725 |
AIRLOOP DATACENTER BOT COOLING COIL | 0.539345 | 10376.83 | 7230.01 | 0.000254 |
AIRLOOP DATACENTER MID COOLING COIL | 5.19 | 100031.98 | 69661.32 | 0.002450 |
AIRLOOP DATACENTER TOP COOLING COIL | 0.526377 | 10133.26 | 7057.96 | 0.000248 |
Supply Air Flow Rate [m3/s] | Supply Air Flow Rate During Heating Operation [m3/s] | Supply Air Flow Rate During Cooling Operation [m3/s] | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | Nominal Heating Capacity [W] | Nominal Cooling Capacity [W] | Supplemental Heating Coil Nominal Capacity [W] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | 22.35 | 22.35 | 22.35 | 22.35 | 437947.87 | 437947.87 | 28525.81 | 1.00 |
AIRLOOP DATACENTER BOT DXAC HEAT PUMP | 0.539345 | 0.539345 | 0.539345 | 0.539345 | 10376.83 | 10376.83 | 1317.77 | 1.00 |
AIRLOOP DATACENTER MID DXAC HEAT PUMP | 5.19 | 5.19 | 5.19 | 5.19 | 100031.98 | 100031.98 | 13177.74 | 1.00 |
AIRLOOP DATACENTER TOP DXAC HEAT PUMP | 0.526377 | 0.526377 | 0.526377 | 0.526377 | 10133.26 | 10133.26 | 1317.77 | 1.00 |
Design Size Maximum Flow Rate [m3/s] | |
AIRLOOP DATACENTER BASEMENT SUPPLY FAN | 22.35 |
AIRLOOP DATACENTER BOT SUPPLY FAN | 0.539345 |
AIRLOOP DATACENTER MID SUPPLY FAN | 5.19 |
AIRLOOP DATACENTER TOP SUPPLY FAN | 0.526377 |
Design Size Rated Air Flow Rate [m3/s] | Design Size Rated Heating Capacity [W] | Design Size Rated Water Flow Rate [m3/s] | |
AIRLOOP DATACENTER BASEMENT HEATING COIL | 22.35 | 437947.87 | 0.010725 |
AIRLOOP DATACENTER BOT HEATING COIL | 0.539345 | 10376.83 | 0.000254 |
AIRLOOP DATACENTER MID HEATING COIL | 5.19 | 100031.98 | 0.002450 |
AIRLOOP DATACENTER TOP HEATING COIL | 0.526377 | 10133.26 | 0.000248 |
Design Size Nominal Capacity [W] | |
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | 28525.81 |
AIRLOOP DATACENTER BOT_SUPPHEATCOIL | 1317.77 |
AIRLOOP DATACENTER MID_SUPPHEATCOIL | 13177.74 |
AIRLOOP DATACENTER TOP_SUPPHEATCOIL | 1317.77 |
Design Size Nominal Capacity Volume [m3/s] | User-Specified Nominal Capacity Volume [m3/s] | Design Size Rated Power [W] | User-Specified Rated Power [W] | |
DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | 0.000207 | 0.000037 | 96450.70 | 100000.00 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | Design Minimum Flow Rate [m3/s] | |
COOLSYS1 PUMP SECONDARY | 0.115674 | 18886.05 | |
HEATSYS1 PUMP | 0.033551 | 10104.07 | 0.000000 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
COOLSYS1_DEMAND | 0.115674 | 13.88 |
HEATSYS1 | 0.033551 | 4.03 |
COOLSYS1_SUPPLY | 0.115674 | 13.88 |
SINGLE WATER PLANT LOOP | 0.013677 | 1.64 |
SWHSYS1 | 0.000440 | 0.052800 |
Loop Supply Side Design Fluid Flow Rate [m3/s] | Loop Demand Side Design Fluid Flow Rate [m3/s] | Heat Exchanger U-Factor Times Area Value [W/C] | Loop-to-loop Temperature Difference Used to Size Heat Exchanger U-Factor Times Area Value [C] | |
BYPASS HEAT EXCHANGER | 0.115674 | 0.115674 | 485542.27 | 5.60 |
Design Size Nominal Capacity [W] | User-Specified Nominal Capacity [W] | Design Size Design Water Flow Rate [m3/s] | |
HEATSYS1 BOILER | 3835077.31 | 3835077.31 | 0.033551 |
CENTRAL BOILER | 563390.91 | 552306.81 | 0.013677 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
COOLSYS1 CHILLER1 PUMP | 0.057837 | 6537.72 |
COOLSYS1 CHILLER2 PUMP | 0.057837 | 6537.72 |
PLANT CIRC PUMP | 0.013677 | 3488.42 |
SWHSYS1 PUMP | 0.000440 | 56.21 |
Design Size Reference Chilled Water Flow Rate [m3/s] | User-Specified Reference Chilled Water Flow Rate [m3/s] | Design Size Reference Capacity [W] | User-Specified Reference Capacity [W] | Design Size Reference Condenser Water Flow Rate [m3/s] | |
COOLSYS1 CHILLER1 | 0.115674 | 0.058180 | 1370939.07 | 1377480.50 | 0.068166 |
COOLSYS1 CHILLER2 | 0.115674 | 0.058180 | 1370939.07 | 1377480.50 | 0.068166 |
Design Water Flow Rate [m3/s] | Air Flow Rate at High Fan Speed [m3/s] | Fluid cooler UA value at high fan speed based on nominal capacity input [W/K] | Air Flow Rate at Low Fan Speed [m3/s] | Fan Power at Low Fan Speed [W] | U-factor Times Area Value at Low Fan Speed [W/C] | |
CENTRAL TOWER | 0.013677 | 139666.47 | 57830.63 | 69833.23 | 7879.72 | 21269.23 |
Use Side Design Flow Rate [m3/s] | |
SWHSYS1 WATER HEATER | 0.000440 |
Maximum Loop Flow Rate [m3/s] | Condenser Loop Volume [m3] | |
TOWERWATERSYS | 0.136333 | 16.36 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
TOWERWATERSYS PUMP | 0.136333 | 33752.99 |
Design Air Flow Rate [m3/s] | Nominal Capacity [W] | Air Flow Rate in free convection regime [m3/s] | Tower capacity in free convection regime at design conditions [W] | |
TOWERWATERSYS COOLTOWER 1 | 54.98 | 1634899.15 | 11.00 | 204362.39 |
TOWERWATERSYS COOLTOWER 2 | 54.98 | 1634899.15 | 11.00 | 204362.39 |
Design Water Flow Rate [m3/s] Equipment # 47 | |
WSHPPLANT OPERATION SCHEME | 0.070803 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:43:41
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
PERIMETER_BOT_ZN_3_WALL_NORTH | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | |
PERIMETER_BOT_ZN_2_WALL_EAST | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | |
PERIMETER_BOT_ZN_1_WALL_SOUTH | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | |
PERIMETER_BOT_ZN_4_WALL_WEST | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | |
PERIMETER_MID_ZN_3_WALL_NORTH | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_MID_ZN_2_WALL_EAST | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_MID_ZN_1_WALL_SOUTH | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_MID_ZN_4_WALL_WEST | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | |
PERIMETER_TOP_ZN_3_WALL_NORTH | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_TOP_ZN_2_WALL_EAST | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_TOP_ZN_1_WALL_SOUTH | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_TOP_ZN_4_WALL_WEST | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 08:43:41
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 08:43:41
VersionVersion ID | |
1 | 22.1.0 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 5.40 | -2.00 | -14.60 | -16.90 | -11.50 | -6.20 | 4.00 | 13.40 | 18.00 | 19.70 | 17.90 | 12.30 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | International Falls Intl Ap MN USA TMY3 WMO#=727470 | 48.57 | -93.40 | -6.00 | 359.00 | 97086 | 1.1539 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 3.29 | 36.60 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | OfficeLarge | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 23 | 221 | 36 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | BASEMENT | 0.0 | 0.00 | 0.00 | 0.00 | 44.59 | 24.37 | -1.22 | 1 | 1 | 1 | 16.08 | 73.11 | 0.00 | 48.74 | -2.44 | 0.00 | 2.44 | 6779.02 | TARP | TARP | 2779.43 | 0.00 | 0.00 | 0.00 | 9 | 0 | 0 | Yes |
2 | CORE_BOTTOM | 0.0 | 0.00 | 0.00 | 0.00 | 37.01 | 24.37 | 1.37 | 1 | 1 | 1 | 5.49 | 68.53 | 4.57 | 44.17 | 0.00 | 2.74 | 2.74 | 6849.35 | TARP | TARP | 2496.12 | 0.00 | 0.00 | 0.00 | 7 | 0 | 0 | Yes |
3 | CORE_MID | 0.0 | 0.00 | 0.00 | 0.00 | 37.01 | 24.37 | 18.14 | 1 | 10 | 1 | 5.49 | 68.53 | 4.57 | 44.17 | 16.77 | 19.51 | 2.74 | 6849.35 | TARP | TARP | 2496.12 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
4 | CORE_TOP | 0.0 | 0.00 | 0.00 | 0.00 | 37.01 | 24.37 | 34.91 | 1 | 1 | 1 | 5.49 | 68.53 | 4.57 | 44.17 | 33.54 | 36.28 | 2.74 | 6849.35 | TARP | TARP | 2496.12 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
5 | PERIMETER_BOT_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 46.54 | 1.37 | 1 | 1 | 1 | 0.00 | 73.11 | 44.17 | 48.74 | 0.00 | 2.74 | 2.74 | 860.00 | TARP | TARP | 313.41 | 200.61 | 76.91 | 115.90 | 8 | 9 | 0 | Yes |
6 | PERIMETER_BOT_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 70.95 | 24.37 | 1.37 | 1 | 1 | 1 | 68.53 | 73.11 | 0.00 | 48.74 | 0.00 | 2.74 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 52.57 | 77.26 | 6 | 5 | 0 | Yes |
7 | PERIMETER_BOT_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 2.20 | 1.37 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 4.57 | 0.00 | 2.74 | 2.74 | 860.02 | TARP | TARP | 313.42 | 200.61 | 76.91 | 115.90 | 8 | 9 | 0 | Yes |
8 | PERIMETER_BOT_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.16 | 24.37 | 1.37 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 48.74 | 0.00 | 2.74 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 52.57 | 77.26 | 6 | 5 | 0 | Yes |
9 | PERIMETER_MID_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 46.54 | 18.14 | 1 | 10 | 1 | 0.00 | 73.11 | 44.17 | 48.74 | 16.77 | 19.51 | 2.74 | 860.00 | TARP | TARP | 313.41 | 200.61 | 84.71 | 115.90 | 7 | 1 | 0 | Yes |
10 | PERIMETER_MID_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 70.95 | 24.37 | 18.14 | 1 | 10 | 1 | 68.53 | 73.11 | 0.00 | 48.74 | 16.77 | 19.51 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 56.47 | 77.26 | 6 | 1 | 0 | Yes |
11 | PERIMETER_MID_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 2.20 | 18.14 | 1 | 10 | 1 | 0.00 | 73.11 | 0.00 | 4.57 | 16.77 | 19.51 | 2.74 | 860.02 | TARP | TARP | 313.42 | 200.61 | 84.71 | 115.90 | 7 | 1 | 0 | Yes |
12 | PERIMETER_MID_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.16 | 24.37 | 18.14 | 1 | 10 | 1 | 0.00 | 4.57 | 0.00 | 48.74 | 16.77 | 19.51 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 56.47 | 77.26 | 6 | 1 | 0 | Yes |
13 | PERIMETER_TOP_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 46.54 | 34.91 | 1 | 1 | 1 | 0.00 | 73.11 | 44.17 | 48.74 | 33.54 | 36.28 | 2.74 | 860.00 | TARP | TARP | 313.41 | 200.61 | 84.71 | 115.90 | 7 | 1 | 0 | Yes |
14 | PERIMETER_TOP_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 70.95 | 24.37 | 34.91 | 1 | 1 | 1 | 68.53 | 73.11 | 0.00 | 48.74 | 33.54 | 36.28 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 56.47 | 77.26 | 6 | 1 | 0 | Yes |
15 | PERIMETER_TOP_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 2.20 | 34.91 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 4.57 | 33.54 | 36.28 | 2.74 | 860.02 | TARP | TARP | 313.42 | 200.61 | 84.71 | 115.90 | 7 | 1 | 0 | Yes |
16 | PERIMETER_TOP_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.16 | 24.37 | 34.91 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 48.74 | 33.54 | 36.28 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 56.47 | 77.26 | 6 | 1 | 0 | Yes |
17 | GROUNDFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 24.37 | 3.35 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 48.74 | 2.74 | 3.96 | 1.22 | 4344.14 | TARP | TARP | 3563.11 | 297.11 | 297.11 | 0.00 | 11 | 0 | 0 | No |
18 | MIDFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 24.37 | 20.12 | 1 | 10 | 1 | 0.00 | 73.11 | 0.00 | 48.74 | 19.51 | 20.73 | 1.22 | 4344.14 | TARP | TARP | 3563.11 | 297.11 | 297.11 | 0.00 | 11 | 0 | 0 | No |
19 | TOPFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 24.37 | 36.89 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 48.74 | 36.28 | 37.50 | 1.22 | 4344.14 | TARP | TARP | 3563.11 | 297.11 | 297.11 | 0.00 | 11 | 0 | 0 | No |
20 | DATACENTER_BOT_ZN_6 | 0.0 | 5.49 | 44.17 | 0.00 | 5.03 | 24.37 | 1.37 | 1 | 1 | 1 | 4.57 | 5.49 | 4.57 | 44.17 | 0.00 | 2.74 | 2.74 | 99.34 | TARP | TARP | 36.20 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
21 | DATACENTER_MID_ZN_6 | 0.0 | 4.57 | 4.57 | 16.77 | 5.03 | 24.37 | 18.14 | 1 | 10 | 1 | 4.57 | 5.49 | 4.57 | 44.17 | 16.77 | 19.51 | 2.74 | 99.34 | TARP | TARP | 36.20 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
22 | DATACENTER_TOP_ZN_6 | 0.0 | 4.57 | 4.57 | 33.54 | 5.03 | 24.37 | 34.91 | 1 | 1 | 1 | 4.57 | 5.49 | 4.57 | 44.17 | 33.54 | 36.28 | 2.74 | 99.34 | TARP | TARP | 36.20 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
23 | DATACENTER_BASEMENT_ZN_6 | 0.0 | 16.08 | 0.00 | -2.44 | 8.04 | 24.37 | -1.22 | 1 | 1 | 1 | 0.00 | 16.08 | 0.00 | 48.74 | -2.44 | 0.00 | 2.44 | 1911.37 | TARP | TARP | 783.68 | 0.00 | 0.00 | 0.00 | 10 | 0 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | BASEMENT | 2779.43 | 149.6 | 18.579 | 5.382E-002 | 10.273 | 4.842 | 0.000 | 0.000 | 0.000 | 0.000 | 15.115 | No |
2 | CORE_BOTTOM | 2496.12 | 134.4 | 18.579 | 5.382E-002 | 10.273 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 18.343 | No |
3 | CORE_MID | 2496.12 | 134.4 | 18.579 | 5.382E-002 | 10.273 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 18.343 | No |
4 | CORE_TOP | 2496.12 | 134.4 | 18.579 | 5.382E-002 | 10.273 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 18.343 | No |
5 | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 18.579 | 5.382E-002 | 10.273 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 18.343 | No |
6 | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 10.273 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 18.343 | No |
7 | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 18.579 | 5.382E-002 | 10.273 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 18.343 | No |
8 | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 10.273 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 18.343 | No |
9 | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 18.579 | 5.382E-002 | 10.273 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 18.343 | No |
10 | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 10.273 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 18.343 | No |
11 | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 18.579 | 5.382E-002 | 10.273 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 18.343 | No |
12 | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 10.273 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 18.343 | No |
13 | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 18.579 | 5.382E-002 | 10.273 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 18.343 | No |
14 | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 10.273 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 18.343 | No |
15 | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 18.579 | 5.382E-002 | 10.273 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 18.343 | No |
16 | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 10.273 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 18.343 | No |
17 | GROUNDFLOOR_PLENUM | 3563.11 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
18 | MIDFLOOR_PLENUM | 3563.11 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
19 | TOPFLOOR_PLENUM | 3563.11 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
20 | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 18.579 | 5.382E-002 | 17.873 | 215.299 | 0.000 | 0.000 | 0.000 | 0.000 | 233.173 | No |
21 | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 18.579 | 5.382E-002 | 17.873 | 215.299 | 0.000 | 0.000 | 0.000 | 0.000 | 233.173 | No |
22 | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 18.579 | 5.382E-002 | 17.873 | 215.299 | 0.000 | 0.000 | 0.000 | 0.000 | 233.173 | No |
23 | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 18.579 | 5.382E-002 | 10.273 | 484.423 | 0.000 | 0.000 | 0.000 | 0.000 | 494.696 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | DATACENTER_BOT_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 1.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | DATACENTER_MID_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 1.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
3 | DATACENTER_TOP_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 1.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
4 | DATACENTER_BASEMENT_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 42.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 42 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
5 | BASEMENT | BLDG_OCC_SCH_WO_SB | BASEMENT | 2779.43 | 149.6 | 149.6 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 150 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
6 | CORE_BOTTOM | BLDG_OCC_SCH_WO_SB | CORE_BOTTOM | 2496.12 | 134.4 | 134.4 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 134 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
7 | CORE_MID | BLDG_OCC_SCH_WO_SB | CORE_MID | 2496.12 | 134.4 | 134.4 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 134 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
8 | CORE_TOP | BLDG_OCC_SCH_WO_SB | CORE_TOP | 2496.12 | 134.4 | 134.4 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 134 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
9 | PERIMETER_BOT_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
10 | PERIMETER_BOT_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
11 | PERIMETER_BOT_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
12 | PERIMETER_BOT_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
13 | PERIMETER_MID_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
14 | PERIMETER_MID_ZN_2 | BLDG_OCC_SCH_W_SB | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
15 | PERIMETER_MID_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
16 | PERIMETER_MID_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
17 | PERIMETER_TOP_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
18 | PERIMETER_TOP_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
19 | PERIMETER_TOP_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
20 | PERIMETER_TOP_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | BASEMENT_LIGHTS | LTG_SCH_OFFICE | BASEMENT | 2779.43 | 149.6 | 28553.717 | 10.273 | 190.864 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 28553.717 |
2 | CORE_BOTTOM_LIGHTS | LTG_SCH_OFFICE | CORE_BOTTOM | 2496.12 | 134.4 | 25643.245 | 10.273 | 190.864 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 25643.245 |
3 | CORE_MID_LIGHTS | LTG_SCH_OFFICE | CORE_MID | 2496.12 | 134.4 | 25643.245 | 10.273 | 190.864 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 25643.245 |
4 | CORE_TOP_LIGHTS | LTG_SCH_OFFICE | CORE_TOP | 2496.12 | 134.4 | 25643.245 | 10.273 | 190.864 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 25643.245 |
5 | PERIMETER_BOT_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 3219.765 | 10.273 | 190.864 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3219.765 |
6 | PERIMETER_BOT_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 2074.939 | 10.273 | 190.864 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2074.939 |
7 | PERIMETER_BOT_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 3219.836 | 10.273 | 190.864 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3219.836 |
8 | PERIMETER_BOT_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 2074.939 | 10.273 | 190.864 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2074.939 |
9 | PERIMETER_MID_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 3219.765 | 10.273 | 190.864 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3219.765 |
10 | PERIMETER_MID_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 2074.939 | 10.273 | 190.864 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2074.939 |
11 | PERIMETER_MID_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 3219.836 | 10.273 | 190.864 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3219.836 |
12 | PERIMETER_MID_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 2074.939 | 10.273 | 190.864 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2074.939 |
13 | PERIMETER_TOP_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 3219.765 | 10.273 | 190.864 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3219.765 |
14 | PERIMETER_TOP_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 2074.939 | 10.273 | 190.864 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2074.939 |
15 | PERIMETER_TOP_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 3219.836 | 10.273 | 190.864 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3219.836 |
16 | PERIMETER_TOP_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 2074.939 | 10.273 | 190.864 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2074.939 |
17 | DATACENTER_BASEMENT_LIGHTS | LTG_SCH_OFFICE | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 8050.927 | 10.273 | 190.864 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 8050.927 |
18 | DATACENTER_BOT_LIGHTS | LTG_SCH_DATACENTER | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 647.068 | 17.873 | 332.067 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 647.068 |
19 | DATACENTER_MID_LIGHTS | LTG_SCH_DATACENTER | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 647.068 | 17.873 | 332.067 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 647.068 |
20 | DATACENTER_TOP_LIGHTS | LTG_SCH_DATACENTER | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 647.068 | 17.873 | 332.067 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 647.068 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | BASEMENT_MISCPLUG_EQUIP | ALWAYS_ON | BASEMENT | 2779.43 | 149.6 | 13457.544 | 4.842 | 89.956 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 13457.544 | 13457.544 |
2 | CORE_BOTTOM_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_BOTTOM | 2496.12 | 134.4 | 20142.877 | 8.070 | 149.925 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 20142.877 |
3 | CORE_MID_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_MID | 2496.12 | 134.4 | 20142.800 | 8.070 | 149.924 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 20142.800 |
4 | CORE_TOP_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_TOP | 2496.12 | 134.4 | 20142.800 | 8.070 | 149.924 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 20142.800 |
5 | PERIMETER_BOT_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 2529.242 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.242 |
6 | PERIMETER_BOT_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 1629.940 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.940 |
7 | PERIMETER_BOT_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 2529.281 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.281 |
8 | PERIMETER_BOT_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 1629.929 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.929 |
9 | PERIMETER_MID_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 2529.242 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.242 |
10 | PERIMETER_MID_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 1629.940 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.940 |
11 | PERIMETER_MID_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 2529.281 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.281 |
12 | PERIMETER_MID_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 1629.929 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.929 |
13 | PERIMETER_TOP_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 2529.242 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.242 |
14 | PERIMETER_TOP_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 1629.940 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.940 |
15 | PERIMETER_TOP_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 2529.281 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.281 |
16 | PERIMETER_TOP_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 1629.929 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.929 |
17 | DATACENTER_BASEMENT_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 379632.522 | 484.423 | 9000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 94908.130 | 379632.522 |
18 | DATACENTER_BOT_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 7794.422 | 215.299 | 4000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 1948.606 | 7794.422 |
19 | DATACENTER_MID_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 7794.422 | 215.299 | 4000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 1948.606 | 7794.422 |
20 | DATACENTER_TOP_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 7794.422 | 215.299 | 4000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 1948.606 | 7794.422 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 2.839 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | INTERIORFURNISHINGS | 2 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
3 | DROPCEILING | 4 | 1 | 3 | 0.167 | 4.488 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
4 | INT_WALL | 7 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | EXT_SLAB_8IN_WITH_CARPET | 8 | 2 | 7 | 0.167 | 3.285 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
6 | INT_SLAB_FLOOR | 12 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
7 | INT_SLAB_CEILING | 13 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | VeryRough |
8 | NONRES_ROOF | 17 | 3 | 3 | 0.167 | 0.1625 | 0.900 | 0.900 | 0.700 | 0.700 | Rough |
9 | NONRES_EXT_WALL_GRD | 20 | 3 | 9 | 0.167 | 0.8300 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
10 | NONRES_EXT_WALL_MID | 21 | 3 | 9 | 0.167 | 0.7863 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
11 | NONRES_EXT_WALL_TOP | 22 | 3 | 9 | 0.167 | 1.009 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
12 | BASEMENT_WALL_EAST_CFACTOR | 39 | 2 | 7 | 0.167 | 0.2699 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | BASEMENT_WALL_SOUTH_CFACTOR | 40 | 2 | 7 | 0.167 | 0.2699 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | BASEMENT_WALL_NORTH_CFACTOR | 41 | 2 | 7 | 0.167 | 0.2699 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR | 42 | 2 | 7 | 0.167 | 0.2699 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
16 | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR | 43 | 2 | 7 | 0.167 | 0.2699 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
17 | DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR | 44 | 2 | 7 | 0.167 | 0.2699 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.3522 |
2 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
3 | AC02 ACOUSTIC CEILING | 0.0127 | 0.057 | 288.000 | 1339.000 | 0.2228 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | 200MM NORMALWEIGHT CONCRETE FLOOR | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
7 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
8 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
9 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
10 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
11 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
12 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
13 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 6.093 |
14 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
15 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
16 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 1.037 |
17 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
18 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
19 | NONRES_EXTERIOR_WALL_INSULATION_MID | 0.0000 | 0.000 | 0.000 | 0.000 | 1.105 |
20 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
21 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
22 | NONRES_EXTERIOR_WALL_INSULATION_TOP | 0.0000 | 0.000 | 0.000 | 0.000 | 0.8237 |
23 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
24 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 3.628 |
25 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
26 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 3.628 |
27 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
28 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 3.628 |
29 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
30 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 3.628 |
31 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
32 | ~FC_Insulation_5 | 0.0000 | 0.000 | 0.000 | 0.000 | 3.628 |
33 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
34 | ~FC_Insulation_6 | 0.0000 | 0.000 | 0.000 | 0.000 | 3.628 |
35 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 2.8391315 | 2.8391315 | 2.8391315 | |
3 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
4 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
5 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
6 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
7 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
8 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
9 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
10 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
11 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
12 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
13 | 3 | -0.21589802E-09 | 0.15643069E-09 | -0.21589802E-09 | 0.12999471E-21 |
14 | 2 | 0.50772448E-02 | 0.30006816E-02 | 0.50772448E-02 | -0.13693132E-08 |
15 | 1 | -2.5944910 | 1.4597758 | -2.5944910 | 0.76344767E-02 |
16 | 0 | 7.0433378 | 2.9911476 | 7.0433378 | |
17 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
18 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
19 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
20 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
21 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
22 | 7 | -0.18651654E-16 | -0.16428647E-15 | -0.26578847E-08 | -0.25364002E-17 |
23 | 6 | 0.67402962E-01 | 0.99142722E-07 | 0.38101547E-02 | -0.76639482E-03 |
24 | 5 | -1.8580732 | 0.49502125E-04 | -0.10651409 | 0.21891119E-01 |
25 | 4 | 18.220105 | 0.12801333E-02 | 1.0775450 | -0.22586539 |
26 | 3 | -79.928293 | 0.66708484E-02 | -4.9803755 | 1.0625663 |
27 | 2 | 166.43177 | 0.75131194E-02 | 11.128837 | -2.4125483 |
28 | 1 | -159.97298 | 0.18548900E-02 | -11.587784 | 2.5494418 |
29 | 0 | 57.057412 | 0.52755123E-04 | 4.4818272 | |
30 | 7 | 0.43260499E-16 | 0.34524919E-16 | 0.52793240E-17 | 0.0000000 |
31 | 6 | 0.69434179E-09 | 0.98085174E-11 | 0.18162501E-10 | -0.40870994E-12 |
32 | 5 | -0.12888762E-04 | 0.28373718E-06 | -0.16918523E-06 | 0.92361873E-08 |
33 | 4 | 0.25174112E-01 | 0.33697681E-03 | 0.22646198E-03 | -0.31467795E-04 |
34 | 3 | -3.7600775 | 0.27170599E-01 | -0.48495626E-01 | 0.94171705E-02 |
35 | 2 | 51.553741 | 0.22121684 | 1.2284947 | -0.25833933 |
36 | 1 | -128.86110 | 0.21944682 | -5.1479470 | 1.1228340 |
37 | 0 | 81.526494 | 0.16043334E-01 | 4.4519351 | |
38 | 7 | 0.52793240E-17 | 0.34524919E-16 | 0.43260499E-16 | 0.0000000 |
39 | 6 | 0.18162501E-10 | 0.98085174E-11 | 0.69434179E-09 | -0.40870994E-12 |
40 | 5 | -0.16918523E-06 | 0.28373718E-06 | -0.12888762E-04 | 0.92361873E-08 |
41 | 4 | 0.22646198E-03 | 0.33697681E-03 | 0.25174112E-01 | -0.31467795E-04 |
42 | 3 | -0.48495626E-01 | 0.27170599E-01 | -3.7600775 | 0.94171705E-02 |
43 | 2 | 1.2284947 | 0.22121684 | 51.553741 | -0.25833933 |
44 | 1 | -5.1479470 | 0.21944682 | -128.86110 | 1.1228340 |
45 | 0 | 4.4519351 | 0.16043334E-01 | 81.526494 | |
46 | 3 | -0.63083111E-06 | 0.74112372E-09 | -0.38647046E-05 | 0.15329585E-16 |
47 | 2 | 0.78415922 | 0.99752939E-03 | 1.0633801 | -0.74093433E-06 |
48 | 1 | -22.010056 | 0.66447931E-01 | -6.3131541 | 0.20386814 |
49 | 0 | 21.355302 | 0.61958938E-01 | 5.3791822 | |
50 | 9 | -0.18184691E-14 | 0.28097163E-16 | -0.15437903E-09 | 0.42281572E-16 |
51 | 8 | 0.22529355E-07 | 0.11232537E-12 | 0.38463784E-03 | -0.25616649E-09 |
52 | 7 | -0.12445705E-01 | 0.57914341E-08 | -0.23379721E-01 | 0.14151220E-03 |
53 | 6 | 0.41089736 | 0.20123329E-05 | 0.47681267 | -0.48131481E-02 |
54 | 5 | -5.2446941 | 0.75059793E-04 | -4.4775149 | 0.63855043E-01 |
55 | 4 | 33.242279 | 0.61344040E-03 | 21.582026 | -0.42530178 |
56 | 3 | -111.73561 | 0.13358480E-02 | -55.904128 | 1.5225540 |
57 | 2 | 197.63606 | 0.75086744E-03 | 78.131773 | -2.9087348 |
58 | 1 | -171.35103 | 0.80103876E-04 | -55.329475 | 2.7488562 |
59 | 0 | 57.057407 | 0.45563487E-06 | 15.546359 | |
60 | 9 | -0.45719712E-14 | 0.27682002E-16 | -0.15643277E-09 | 0.85453293E-16 |
61 | 8 | 0.22815700E-07 | 0.10660981E-12 | 0.38760953E-03 | -0.25942234E-09 |
62 | 7 | -0.12534255E-01 | 0.54803652E-08 | -0.23507179E-01 | 0.14251905E-03 |
63 | 6 | 0.41330326 | 0.19019750E-05 | 0.47885866 | -0.48415080E-02 |
64 | 5 | -5.2681707 | 0.70870595E-04 | -4.4932156 | 0.64146145E-01 |
65 | 4 | 33.346110 | 0.57866488E-03 | 21.643366 | -0.42668038 |
66 | 3 | -111.95648 | 0.12590731E-02 | -56.025383 | 1.5257451 |
67 | 2 | 197.85492 | 0.70718823E-03 | 78.243035 | -2.9122105 |
68 | 1 | -171.43186 | 0.75392391E-04 | -55.361928 | 2.7502728 |
69 | 0 | 57.057407 | 0.42848903E-06 | 15.541080 | |
70 | 9 | -0.33808012E-15 | 0.34972917E-16 | -0.14598079E-09 | 0.47841714E-18 |
71 | 8 | 0.21349114E-07 | 0.13533401E-12 | 0.37225214E-03 | -0.24274679E-09 |
72 | 7 | -0.12076170E-01 | 0.70668839E-08 | -0.22847671E-01 | 0.13731045E-03 |
73 | 6 | 0.40085647 | 0.24680520E-05 | 0.46826241 | -0.46947901E-02 |
74 | 5 | -5.1467077 | 0.92462493E-04 | -4.4118499 | 0.62640056E-01 |
75 | 4 | 32.808865 | 0.75866459E-03 | 21.325369 | -0.41954723 |
76 | 3 | -110.81348 | 0.16579313E-02 | -55.396723 | 1.5092316 |
77 | 2 | 196.72215 | 0.93484174E-03 | 77.666390 | -2.8942219 |
78 | 1 | -171.01346 | 0.10002080E-03 | -55.194115 | 2.7429399 |
79 | 0 | 57.057407 | 0.57079447E-06 | 15.568689 | |
80 | 7 | -0.15524988E-08 | -0.27599222E-15 | 0.12191615E-13 | -0.17961055E-15 |
81 | 6 | 0.75408527E-05 | 0.51820635E-08 | 0.31843202E-02 | -0.26712746E-04 |
82 | 5 | -0.54428247E-03 | 0.30714476E-05 | -0.22340912 | 0.19533659E-02 |
83 | 4 | 0.12532102E-01 | 0.13984121E-03 | 4.8242913 | -0.45214473E-01 |
84 | 3 | -0.11008570 | 0.11123587E-02 | -37.991733 | 0.39832565 |
85 | 2 | 0.39093855 | 0.18508074E-02 | 116.42617 | -1.4171665 |
86 | 1 | -0.56428968 | 0.56416853E-03 | -143.87330 | 2.0484809 |
87 | 0 | 0.27512533 | 0.13606908E-04 | 60.838472 | |
88 | 7 | -0.15524988E-08 | -0.27599222E-15 | 0.12191615E-13 | -0.17961055E-15 |
89 | 6 | 0.75408527E-05 | 0.51820635E-08 | 0.31843202E-02 | -0.26712746E-04 |
90 | 5 | -0.54428247E-03 | 0.30714476E-05 | -0.22340912 | 0.19533659E-02 |
91 | 4 | 0.12532102E-01 | 0.13984121E-03 | 4.8242913 | -0.45214473E-01 |
92 | 3 | -0.11008570 | 0.11123587E-02 | -37.991733 | 0.39832565 |
93 | 2 | 0.39093855 | 0.18508074E-02 | 116.42617 | -1.4171665 |
94 | 1 | -0.56428968 | 0.56416853E-03 | -143.87330 | 2.0484809 |
95 | 0 | 0.27512533 | 0.13606908E-04 | 60.838472 | |
96 | 7 | -0.15524988E-08 | -0.27599222E-15 | 0.12191615E-13 | -0.17961055E-15 |
97 | 6 | 0.75408527E-05 | 0.51820635E-08 | 0.31843202E-02 | -0.26712746E-04 |
98 | 5 | -0.54428247E-03 | 0.30714476E-05 | -0.22340912 | 0.19533659E-02 |
99 | 4 | 0.12532102E-01 | 0.13984121E-03 | 4.8242913 | -0.45214473E-01 |
100 | 3 | -0.11008570 | 0.11123587E-02 | -37.991733 | 0.39832565 |
101 | 2 | 0.39093855 | 0.18508074E-02 | 116.42617 | -1.4171665 |
102 | 1 | -0.56428968 | 0.56416853E-03 | -143.87330 | 2.0484809 |
103 | 0 | 0.27512533 | 0.13606908E-04 | 60.838472 | |
104 | 7 | -0.15524988E-08 | -0.27599222E-15 | 0.12191615E-13 | -0.17961055E-15 |
105 | 6 | 0.75408527E-05 | 0.51820635E-08 | 0.31843202E-02 | -0.26712746E-04 |
106 | 5 | -0.54428247E-03 | 0.30714476E-05 | -0.22340912 | 0.19533659E-02 |
107 | 4 | 0.12532102E-01 | 0.13984121E-03 | 4.8242913 | -0.45214473E-01 |
108 | 3 | -0.11008570 | 0.11123587E-02 | -37.991733 | 0.39832565 |
109 | 2 | 0.39093855 | 0.18508074E-02 | 116.42617 | -1.4171665 |
110 | 1 | -0.56428968 | 0.56416853E-03 | -143.87330 | 2.0484809 |
111 | 0 | 0.27512533 | 0.13606908E-04 | 60.838472 | |
112 | 7 | -0.15524988E-08 | -0.27599222E-15 | 0.12191615E-13 | -0.17961055E-15 |
113 | 6 | 0.75408527E-05 | 0.51820635E-08 | 0.31843202E-02 | -0.26712746E-04 |
114 | 5 | -0.54428247E-03 | 0.30714476E-05 | -0.22340912 | 0.19533659E-02 |
115 | 4 | 0.12532102E-01 | 0.13984121E-03 | 4.8242913 | -0.45214473E-01 |
116 | 3 | -0.11008570 | 0.11123587E-02 | -37.991733 | 0.39832565 |
117 | 2 | 0.39093855 | 0.18508074E-02 | 116.42617 | -1.4171665 |
118 | 1 | -0.56428968 | 0.56416853E-03 | -143.87330 | 2.0484809 |
119 | 0 | 0.27512533 | 0.13606908E-04 | 60.838472 | |
120 | 7 | -0.15524988E-08 | -0.27599222E-15 | 0.12191615E-13 | -0.17961055E-15 |
121 | 6 | 0.75408527E-05 | 0.51820635E-08 | 0.31843202E-02 | -0.26712746E-04 |
122 | 5 | -0.54428247E-03 | 0.30714476E-05 | -0.22340912 | 0.19533659E-02 |
123 | 4 | 0.12532102E-01 | 0.13984121E-03 | 4.8242913 | -0.45214473E-01 |
124 | 3 | -0.11008570 | 0.11123587E-02 | -37.991733 | 0.39832565 |
125 | 2 | 0.39093855 | 0.18508074E-02 | 116.42617 | -1.4171665 |
126 | 1 | -0.56428968 | 0.56416853E-03 | -143.87330 | 2.0484809 |
127 | 0 | 0.27512533 | 0.13606908E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | WINDOW_U_0.379_SHGC_EAST_0.45 | 35 | 1 | VerySmooth | 2.153 | 2.153 | 1.000 | 0.451 | ||
2 | WINDOW_U_0.379_SHGC_SOUTH_0.45 | 36 | 1 | VerySmooth | 2.153 | 2.153 | 1.000 | 0.451 | ||
3 | WINDOW_U_0.379_SHGC_WEST_0.45 | 37 | 1 | VerySmooth | 2.153 | 2.153 | 1.000 | 0.451 | ||
4 | WINDOW_U_0.379_SHGC_NORTH_0.45 | 38 | 1 | VerySmooth | 2.153 | 2.153 | 1.000 | 0.451 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | GLAZING LAYER EAST | SpectralAverage | 3.46913E-002 | 0.36619 | 0.43199 | 0.43199 | 0.49500 | 0.13079 | 0.16089 | 0.00000 | 0.84000 | 0.84000 | 0.11879 | 1.00000 | No | |
2 | GLAZING LAYER SOUTH | SpectralAverage | 3.46913E-002 | 0.36619 | 0.43199 | 0.43199 | 0.49500 | 0.13079 | 0.16089 | 0.00000 | 0.84000 | 0.84000 | 0.11879 | 1.00000 | No | |
3 | GLAZING LAYER WEST | SpectralAverage | 3.46913E-002 | 0.36619 | 0.43199 | 0.43199 | 0.49500 | 0.13079 | 0.16089 | 0.00000 | 0.84000 | 0.84000 | 0.11879 | 1.00000 | No | |
4 | GLAZING LAYER NORTH | SpectralAverage | 3.46913E-002 | 0.36619 | 0.43199 | 0.43199 | 0.49500 | 0.13079 | 0.16089 | 0.00000 | 0.84000 | 0.84000 | 0.11879 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 30 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Enclosure Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Enclosures | |
1 | PERIMETER_BOT_ZN_3 | 5 | 0 |
2 | PERIMETER_BOT_ZN_2 | 3 | 0 |
3 | PERIMETER_BOT_ZN_1 | 5 | 0 |
4 | PERIMETER_BOT_ZN_4 | 3 | 0 |
5 | PERIMETER_MID_ZN_3 | 1 | 0 |
6 | PERIMETER_MID_ZN_2 | 1 | 0 |
7 | PERIMETER_MID_ZN_1 | 1 | 0 |
8 | PERIMETER_MID_ZN_4 | 1 | 0 |
9 | PERIMETER_TOP_ZN_3 | 1 | 0 |
10 | PERIMETER_TOP_ZN_2 | 1 | 0 |
11 | PERIMETER_TOP_ZN_1 | 1 | 0 |
12 | PERIMETER_TOP_ZN_4 | 1 | 0 |
Enclosure Name | Number of Adjacent Enclosures with Windows | Adjacent Enclosure Names - 1st 100 (max) | |
1 | PERIMETER_BOT_ZN_3 | 0 | |
2 | PERIMETER_BOT_ZN_2 | 0 | |
3 | PERIMETER_BOT_ZN_1 | 0 | |
4 | PERIMETER_BOT_ZN_4 | 0 | |
5 | PERIMETER_MID_ZN_3 | 0 | |
6 | PERIMETER_MID_ZN_2 | 0 | |
7 | PERIMETER_MID_ZN_1 | 0 | |
8 | PERIMETER_MID_ZN_4 | 0 | |
9 | PERIMETER_TOP_ZN_3 | 0 | |
10 | PERIMETER_TOP_ZN_2 | 0 | |
11 | PERIMETER_TOP_ZN_1 | 0 | |
12 | PERIMETER_TOP_ZN_4 | 0 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 1.1356 | 87921.3 | 0.481 | 5.5005E-002 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | BASEMENT_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
2 | BASEMENT_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
3 | BASEMENT_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
4 | BASEMENT_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
5 | BASEMENT_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
6 | PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
7 | PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
8 | CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
9 | PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
10 | BASEMENT_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
11 | CORE_BOT_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
12 | CORE_BOT_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
13 | CORE_BOT_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
14 | CORE_BOT_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
15 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
16 | CORE_BOT_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
17 | CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
18 | CORE_BOTTOM_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
19 | CORE_MID_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
20 | CORE_MID_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
21 | CORE_MID_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
22 | CORE_MID_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
23 | CORE_MID_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
24 | CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
25 | CORE_MID_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
26 | CORE_TOP_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
27 | CORE_TOP_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
28 | CORE_TOP_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
29 | CORE_TOP_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
30 | CORE_TOP_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
31 | CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
32 | CORE_TOP_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
33 | PERIMETER_BOT_ZN_3_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
34 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
35 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
36 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
37 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
38 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
39 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
40 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
41 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
42 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
43 | PERIMETER_BOT_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
44 | CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
45 | PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
46 | DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
47 | PERIMETER_BOT_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
48 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
49 | PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
50 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
51 | PERIMETER_BOT_ZN_2_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
52 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
53 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
54 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
55 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
56 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
57 | PERIMETER_BOT_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
58 | CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
59 | PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
60 | PERIMETER_BOT_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
61 | PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
62 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
63 | PERIMETER_BOT_ZN_1_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
64 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
65 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
66 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
67 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
68 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
69 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
70 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
71 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
72 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
73 | PERIMETER_BOT_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
74 | DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
75 | PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
76 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
77 | DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
78 | PERIMETER_BOT_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
79 | PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
80 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
81 | PERIMETER_BOT_ZN_4_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
82 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
83 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
84 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
85 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
86 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
87 | PERIMETER_BOT_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
88 | DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
89 | PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
90 | PERIMETER_BOT_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
91 | PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
92 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
93 | PERIMETER_MID_ZN_3_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
94 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
95 | PERIMETER_MID_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
96 | CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
97 | PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
98 | DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
99 | PERIMETER_MID_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
100 | PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
101 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
102 | PERIMETER_MID_ZN_2_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
103 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
104 | PERIMETER_MID_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
105 | CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
106 | PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
107 | PERIMETER_MID_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
108 | PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
109 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
110 | PERIMETER_MID_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
111 | PERIMETER_MID_ZN_1_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
112 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
113 | DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
114 | PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
115 | CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
116 | PERIMETER_MID_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
117 | PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
118 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
119 | PERIMETER_MID_ZN_4_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
120 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
121 | PERIMETER_MID_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
122 | DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
123 | PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
124 | PERIMETER_MID_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
125 | PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
126 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
127 | PERIMETER_TOP_ZN_3_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
128 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
129 | PERIMETER_TOP_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
130 | CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
131 | PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
132 | DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
133 | PERIMETER_TOP_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
134 | PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
135 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
136 | PERIMETER_TOP_ZN_2_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
137 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
138 | PERIMETER_TOP_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
139 | CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
140 | INT-PER3S-NE-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
141 | PERIMETER_TOP_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
142 | PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
143 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
144 | PERIMETER_TOP_ZN_1_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
145 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
146 | INT-PER3S-NE | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
147 | DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
148 | PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
149 | CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
150 | PERIMETER_TOP_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
151 | PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
152 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
153 | PERIMETER_TOP_ZN_4_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
154 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
155 | PERIMETER_TOP_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
156 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
157 | PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
158 | PERIMETER_TOP_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
159 | PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
160 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
161 | GROUNDFLOOR_PLENUM_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
162 | GROUNDFLOOR_PLENUM_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
163 | GROUNDFLOOR_PLENUM_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
164 | GROUNDFLOOR_PLENUM_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
165 | iz-CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
166 | iz-PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
167 | iz-PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
168 | iz-PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
169 | iz-PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
170 | iz-DATACENTER_BOT_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
171 | GROUNDFLOOR_PLENUM_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
172 | MIDFLOOR_PLENUM_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
173 | MIDFLOOR_PLENUM_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
174 | MIDFLOOR_PLENUM_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
175 | MIDFLOOR_PLENUM_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
176 | iz-CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
177 | iz-PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
178 | iz-PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
179 | iz-PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
180 | iz-PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
181 | iz-DATACENTER_MID_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
182 | MIDFLOOR_PLENUM_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
183 | TOPFLOOR_PLENUM_WALL_NORTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
184 | TOPFLOOR_PLENUM_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
185 | TOPFLOOR_PLENUM_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
186 | TOPFLOOR_PLENUM_WALL_SOUTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
187 | iz-CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
188 | iz-PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
189 | iz-PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
190 | iz-PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
191 | iz-PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
192 | iz-DATACENTER_TOP_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
193 | BUILDING_ROOF | 0 | 3563.11 | 268.06 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
194 | DATACENTER_BOT_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
195 | DATACENTER_BOT_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
196 | DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
197 | DATACENTER_BOT_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
198 | DATACENTER_BOT_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
199 | DATACENTER_BOT_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
200 | DATACENTER_MID_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
201 | DATACENTER_MID_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
202 | DATACENTER_MID_ZN_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
203 | DATACENTER_MID_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
204 | DATACENTER_MID_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
205 | DATACENTER_MID_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
206 | DATACENTER_TOP_ZN_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
207 | DATACENTER_TOP_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
208 | DATACENTER_TOP_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
209 | DATACENTER_TOP_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
210 | DATACENTER_TOP_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
211 | DATACENTER_TOP_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
212 | DATACENTER_BASEMENT_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
213 | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
214 | DATACENTER_BASEMENT_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
215 | DATACENTER_BASEMENT_ZN_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
216 | DATACENTER_BASEMENT_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
217 | DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
218 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
219 | PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
220 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
221 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | PERIMETER_BOT_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 0.114 | 3.646E-004 | 5.482E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | PERIMETER_BOT_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 7.617E-002 | 3.771E-004 | 5.534E-004 | 0.495 | 0.000 | 0.000 | 0.224 | 0.000 |
3 | PERIMETER_BOT_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 0.114 | 3.646E-004 | 5.482E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | PERIMETER_BOT_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 7.617E-002 | 3.771E-004 | 5.534E-004 | 0.495 | 0.000 | 0.000 | 0.224 | 0.000 |
5 | PERIMETER_MID_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 0.114 | 3.646E-004 | 5.696E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
6 | PERIMETER_MID_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 7.617E-002 | 3.771E-004 | 5.696E-004 | 0.495 | 0.000 | 0.000 | 0.224 | 0.000 |
7 | PERIMETER_MID_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 0.114 | 3.646E-004 | 5.696E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
8 | PERIMETER_MID_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 7.617E-002 | 3.771E-004 | 5.696E-004 | 0.495 | 0.000 | 0.000 | 0.224 | 0.000 |
9 | PERIMETER_TOP_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 0.114 | 3.646E-004 | 5.696E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
10 | PERIMETER_TOP_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 7.617E-002 | 3.771E-004 | 5.696E-004 | 0.495 | 0.000 | 0.000 | 0.224 | 0.000 |
11 | PERIMETER_TOP_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 0.114 | 3.646E-004 | 5.696E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
12 | PERIMETER_TOP_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 7.617E-002 | 3.771E-004 | 5.696E-004 | 0.495 | 0.000 | 0.000 | 0.224 | 0.000 |
13 | GROUNDFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | GROUNDFLOOR_PLENUM | 3563.11 | 0.0 | 0.169 | 4.749E-005 | 5.696E-004 | 0.140 | 0.000 | 0.000 | 0.224 | 0.000 |
14 | MIDFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | MIDFLOOR_PLENUM | 3563.11 | 0.0 | 0.169 | 4.749E-005 | 5.696E-004 | 0.140 | 0.000 | 0.000 | 0.224 | 0.000 |
15 | TOPFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | TOPFLOOR_PLENUM | 3563.11 | 0.0 | 0.169 | 4.749E-005 | 4.384E-005 | 0.140 | 0.000 | 0.000 | 0.224 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | BASEMENT | Mixing/Well-Stirred |
2 | CORE_BOTTOM | Mixing/Well-Stirred |
3 | CORE_MID | Mixing/Well-Stirred |
4 | CORE_TOP | Mixing/Well-Stirred |
5 | PERIMETER_BOT_ZN_3 | Mixing/Well-Stirred |
6 | PERIMETER_BOT_ZN_2 | Mixing/Well-Stirred |
7 | PERIMETER_BOT_ZN_1 | Mixing/Well-Stirred |
8 | PERIMETER_BOT_ZN_4 | Mixing/Well-Stirred |
9 | PERIMETER_MID_ZN_3 | Mixing/Well-Stirred |
10 | PERIMETER_MID_ZN_2 | Mixing/Well-Stirred |
11 | PERIMETER_MID_ZN_1 | Mixing/Well-Stirred |
12 | PERIMETER_MID_ZN_4 | Mixing/Well-Stirred |
13 | PERIMETER_TOP_ZN_3 | Mixing/Well-Stirred |
14 | PERIMETER_TOP_ZN_2 | Mixing/Well-Stirred |
15 | PERIMETER_TOP_ZN_1 | Mixing/Well-Stirred |
16 | PERIMETER_TOP_ZN_4 | Mixing/Well-Stirred |
17 | GROUNDFLOOR_PLENUM | Mixing/Well-Stirred |
18 | MIDFLOOR_PLENUM | Mixing/Well-Stirred |
19 | TOPFLOOR_PLENUM | Mixing/Well-Stirred |
20 | DATACENTER_BOT_ZN_6 | Mixing/Well-Stirred |
21 | DATACENTER_MID_ZN_6 | Mixing/Well-Stirred |
22 | DATACENTER_TOP_ZN_6 | Mixing/Well-Stirred |
23 | DATACENTER_BASEMENT_ZN_6 | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sky Type | MonthAndDay | Daylighting Control Name | Enclosure Name | Window Name | Reference Point | Daylight Factor | |
1 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 8.7821E-003 |
2 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 8.7848E-003 |
3 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 9.8565E-003 |
4 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 9.8588E-003 |
5 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 5.5890E-003 |
6 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 5.5907E-003 |
7 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 3.1188E-003 |
8 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 3.1198E-003 |
9 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 8.8443E-003 |
10 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 9.0267E-003 |
11 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 9.9094E-003 |
12 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.0070E-002 |
13 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 5.6333E-003 |
14 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 5.7637E-003 |
15 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 3.1446E-003 |
16 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 3.2101E-003 |
17 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 0.2061 |
18 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 0.1141 |
19 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 0.2366 |
20 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 0.1328 |
21 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 0.1344 |
22 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 5.5825E-002 |
23 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 5.6434E-002 |
24 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.9626E-002 |
25 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 8.8541E-003 |
26 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 9.0783E-003 |
27 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 9.9202E-003 |
28 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.0127E-002 |
29 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 5.6412E-003 |
30 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 5.7943E-003 |
31 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 3.1452E-003 |
32 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 3.2120E-003 |
33 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 8.7818E-003 |
34 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 8.7849E-003 |
35 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 9.8562E-003 |
36 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 9.8589E-003 |
37 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 5.5889E-003 |
38 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 5.5909E-003 |
39 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 3.1187E-003 |
40 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 3.1197E-003 |
41 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 7.5541E-003 |
42 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 8.0923E-003 |
43 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 7.3616E-003 |
44 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 7.9904E-003 |
45 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 6.5641E-003 |
46 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 6.7378E-003 |
47 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 5.3324E-003 |
48 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 5.3776E-003 |
49 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 8.6065E-002 |
50 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 4.2182E-002 |
51 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 8.2822E-002 |
52 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.9564E-002 |
53 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 8.0263E-002 |
54 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.3589E-002 |
55 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 5.8755E-002 |
56 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 2.1975E-002 |
57 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 7.3697E-003 |
58 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 7.5083E-003 |
59 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 7.1170E-003 |
60 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 7.2188E-003 |
61 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 6.5096E-003 |
62 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 6.5493E-003 |
63 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 5.3325E-003 |
64 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 5.3783E-003 |
65 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.4484E-003 |
66 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 3.4511E-003 |
67 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.9198E-003 |
68 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.9221E-003 |
69 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.5472E-003 |
70 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.5489E-003 |
71 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.1189E-003 |
72 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 3.1198E-003 |
73 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.5097E-003 |
74 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 3.6668E-003 |
75 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.9710E-003 |
76 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 3.0981E-003 |
77 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.5892E-003 |
78 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.6830E-003 |
79 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.1452E-003 |
80 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 3.2120E-003 |
81 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 5.7292E-002 |
82 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 3.0285E-002 |
83 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 4.4061E-002 |
84 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.3020E-002 |
85 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.9148E-002 |
86 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.5168E-002 |
87 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 5.6434E-002 |
88 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.9620E-002 |
89 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.5072E-003 |
90 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 3.6664E-003 |
91 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.9674E-003 |
92 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 3.0925E-003 |
93 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.5829E-003 |
94 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.6632E-003 |
95 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.1446E-003 |
96 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 3.2101E-003 |
97 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.4482E-003 |
98 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 3.4509E-003 |
99 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.9196E-003 |
100 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.9218E-003 |
101 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.5471E-003 |
102 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.5485E-003 |
103 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.1187E-003 |
104 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 3.1197E-003 |
105 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 6.5922E-003 |
106 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 6.7364E-003 |
107 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 6.1136E-003 |
108 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 6.2183E-003 |
109 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 5.9732E-003 |
110 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 6.0096E-003 |
111 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 5.3326E-003 |
112 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 5.3784E-003 |
113 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 7.2503E-002 |
114 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.6547E-002 |
115 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 6.5419E-002 |
116 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.2308E-002 |
117 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 7.0348E-002 |
118 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.9515E-002 |
119 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 5.8755E-002 |
120 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.1975E-002 |
121 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 6.7284E-003 |
122 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 7.1051E-003 |
123 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 6.2954E-003 |
124 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 6.7128E-003 |
125 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 6.0237E-003 |
126 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 6.1786E-003 |
127 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 5.3323E-003 |
128 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 5.3775E-003 |
129 | Clear Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 0.2069 |
130 | Clear Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 0.1543 |
131 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 0.2307 |
132 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 0.1773 |
133 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 0.1505 |
134 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 8.2100E-002 |
135 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 6.9092E-002 |
136 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 3.4167E-002 |
137 | Clear Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 0.1021 |
138 | Clear Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 6.0423E-002 |
139 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 9.8531E-002 |
140 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 5.7431E-002 |
141 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 9.4858E-002 |
142 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 4.9142E-002 |
143 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 7.0861E-002 |
144 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 3.4558E-002 |
145 | Clear Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 7.0553E-002 |
146 | Clear Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 4.6922E-002 |
147 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 5.5604E-002 |
148 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 3.7023E-002 |
149 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 5.0259E-002 |
150 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 2.7187E-002 |
151 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 6.9093E-002 |
152 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 3.4161E-002 |
153 | Clear Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 8.6753E-002 |
154 | Clear Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 5.2634E-002 |
155 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 7.8821E-002 |
156 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 4.7385E-002 |
157 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 8.3758E-002 |
158 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 4.3765E-002 |
159 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 7.0861E-002 |
160 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 3.4558E-002 |
161 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 0.2069 |
162 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 0.1545 |
163 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 0.2308 |
164 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 0.1776 |
165 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 0.1507 |
166 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 8.2294E-002 |
167 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 6.9240E-002 |
168 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 3.4243E-002 |
169 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 0.1022 |
170 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 6.0517E-002 |
171 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 9.8604E-002 |
172 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 5.7523E-002 |
173 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 9.5000E-002 |
174 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 4.9247E-002 |
175 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 7.1009E-002 |
176 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 3.4634E-002 |
177 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 7.0557E-002 |
178 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 4.6977E-002 |
179 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 5.5613E-002 |
180 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 3.7066E-002 |
181 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 5.0339E-002 |
182 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 2.7238E-002 |
183 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 6.9241E-002 |
184 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 3.4237E-002 |
185 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 8.6797E-002 |
186 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 5.2710E-002 |
187 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 7.8870E-002 |
188 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 4.7455E-002 |
189 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 8.3884E-002 |
190 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 4.3856E-002 |
191 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 7.1009E-002 |
192 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 3.4634E-002 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | BASEMENT | Cooling | 83116.38730 | 83116.38730 | 6.24706 | 6.24706 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 20.92400 | 1.27099E-002 | 2779.42662 | 149.60210 | 1.20016 | 0.00000 |
2 | BASEMENT | Heating | 0.00000 | 0.00000 | 0.00000 | 1.20016 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -32.70000 | 1.83376E-004 | 2779.42662 | 149.60210 | 1.20016 | 0.00000 |
3 | CORE_BOTTOM | Cooling | 85722.04421 | 85722.04421 | 6.44200 | 6.44200 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 20.92400 | 1.27099E-002 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 |
4 | CORE_BOTTOM | Heating | 8581.63982 | 8581.63982 | 0.37871 | 1.07782 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -32.70000 | 1.83376E-004 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 |
5 | CORE_MID | Cooling | 806511.82990 | 806511.82990 | 60.59484 | 60.59484 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 20.92400 | 1.27099E-002 | 2496.12046 | 134.35320 | 10.77825 | 0.00000 |
6 | CORE_MID | Heating | 349573.07757 | 349573.07757 | 15.43329 | 15.43329 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -32.70000 | 1.83376E-004 | 2496.12046 | 134.35320 | 10.77825 | 0.00000 |
7 | CORE_TOP | Cooling | 79273.98709 | 79273.98709 | 5.95589 | 5.95589 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 20.92400 | 1.27099E-002 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 |
8 | CORE_TOP | Heating | 78449.37546 | 78449.37546 | 3.48326 | 3.48326 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -32.70000 | 1.83376E-004 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 |
9 | PERIMETER_BOT_ZN_3 | Cooling | 14121.41289 | 14121.41289 | 1.07070 | 1.07070 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | 30.10000 | 1.27259E-002 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
10 | PERIMETER_BOT_ZN_3 | Heating | 15682.35117 | 15682.35117 | 0.69753 | 0.69753 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -32.70000 | 1.83376E-004 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
11 | PERIMETER_BOT_ZN_2 | Cooling | 20629.71735 | 20629.71735 | 1.56414 | 1.56414 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 08:30:00 | 22.10200 | 1.27119E-002 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
12 | PERIMETER_BOT_ZN_2 | Heating | 10715.43745 | 10715.43745 | 0.47669 | 0.47669 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -32.70000 | 1.83376E-004 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
13 | PERIMETER_BOT_ZN_1 | Cooling | 25170.56826 | 25170.56826 | 1.90845 | 1.90845 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:20:00 | 29.68667 | 1.27251E-002 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
14 | PERIMETER_BOT_ZN_1 | Heating | 17109.76351 | 17109.76351 | 0.76120 | 0.76120 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -32.70000 | 1.83376E-004 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
15 | PERIMETER_BOT_ZN_4 | Cooling | 24680.95117 | 24680.95117 | 1.87131 | 1.87131 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 | 28.15733 | 1.27224E-002 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
16 | PERIMETER_BOT_ZN_4 | Heating | 9158.08432 | 9158.08432 | 0.40721 | 0.40721 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -32.70000 | 1.83376E-004 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
17 | PERIMETER_MID_ZN_3 | Cooling | 133171.49046 | 133171.49046 | 10.09768 | 10.09768 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 | 30.10000 | 1.27259E-002 | 313.41284 | 16.86939 | 1.35332 | 0.00000 |
18 | PERIMETER_MID_ZN_3 | Heating | 220021.47723 | 220021.47723 | 9.79378 | 9.79378 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -32.70000 | 1.83376E-004 | 313.41284 | 16.86939 | 1.35332 | 0.00000 |
19 | PERIMETER_MID_ZN_2 | Cooling | 220408.64831 | 220408.64831 | 16.71217 | 16.71217 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 09:10:00 | 23.63133 | 1.27146E-002 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
20 | PERIMETER_MID_ZN_2 | Heating | 146021.97449 | 146021.97449 | 6.50022 | 6.50022 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -32.70000 | 1.83376E-004 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
21 | PERIMETER_MID_ZN_1 | Cooling | 258879.38217 | 258879.38217 | 19.62923 | 19.62923 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 29.79000 | 1.27253E-002 | 313.41969 | 16.86975 | 1.35335 | 0.00000 |
22 | PERIMETER_MID_ZN_1 | Heating | 223160.12343 | 223160.12343 | 9.93378 | 9.93378 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -32.70000 | 1.83376E-004 | 313.41969 | 16.86975 | 1.35335 | 0.00000 |
23 | PERIMETER_MID_ZN_4 | Cooling | 233999.88852 | 233999.88852 | 17.74270 | 17.74270 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:20:00 | 27.95067 | 1.27221E-002 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
24 | PERIMETER_MID_ZN_4 | Heating | 144155.25303 | 144155.25303 | 6.41700 | 6.41700 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -32.70000 | 1.83376E-004 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
25 | PERIMETER_TOP_ZN_3 | Cooling | 14667.25151 | 14667.25151 | 1.11216 | 1.11216 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | 30.10000 | 1.27259E-002 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
26 | PERIMETER_TOP_ZN_3 | Heating | 27670.14986 | 27670.14986 | 1.23214 | 1.23214 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -32.70000 | 1.83376E-004 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
27 | PERIMETER_TOP_ZN_2 | Cooling | 22008.97929 | 22008.97929 | 1.66883 | 1.66883 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 09:10:00 | 23.63133 | 1.27146E-002 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
28 | PERIMETER_TOP_ZN_2 | Heating | 18270.60233 | 18270.60233 | 0.81361 | 0.81361 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -32.70000 | 1.83376E-004 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
29 | PERIMETER_TOP_ZN_1 | Cooling | 27159.08765 | 27159.08765 | 2.05934 | 2.05934 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 29.89333 | 1.27255E-002 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
30 | PERIMETER_TOP_ZN_1 | Heating | 28019.05018 | 28019.05018 | 1.24770 | 1.24770 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -32.70000 | 1.83376E-004 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
31 | PERIMETER_TOP_ZN_4 | Cooling | 24297.79082 | 24297.79082 | 1.84238 | 1.84238 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:20:00 | 27.95067 | 1.27221E-002 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
32 | PERIMETER_TOP_ZN_4 | Heating | 18276.50279 | 18276.50279 | 0.81388 | 0.81388 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -32.70000 | 1.83376E-004 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
33 | DATACENTER_BOT_ZN_6 | Cooling | 9019.03132 | 9019.03132 | 0.53935 | 0.53935 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 19:20:00 | 24.80933 | 1.27166E-002 | 36.20274 | 1.94861 | 1.56323E-002 | 0.00000 |
34 | DATACENTER_BOT_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 1.56323E-002 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 05:30:00 | -32.70000 | 1.83376E-004 | 36.20274 | 1.94861 | 1.56323E-002 | 0.00000 |
35 | DATACENTER_MID_ZN_6 | Cooling | 86864.64270 | 86864.64270 | 5.19459 | 5.19459 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 19:20:00 | 24.80933 | 1.27166E-002 | 36.20274 | 1.94861 | 0.15632 | 0.00000 |
36 | DATACENTER_MID_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 0.15632 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 05:40:00 | -32.70000 | 1.83376E-004 | 36.20274 | 1.94861 | 0.15632 | 0.00000 |
37 | DATACENTER_TOP_ZN_6 | Cooling | 8802.15773 | 8802.15773 | 0.52638 | 0.52638 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 19:20:00 | 24.80933 | 1.27166E-002 | 36.20274 | 1.94861 | 1.56323E-002 | 0.00000 |
38 | DATACENTER_TOP_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 1.56323E-002 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 05:30:00 | -32.70000 | 1.83376E-004 | 36.20274 | 1.94861 | 1.56323E-002 | 0.00000 |
39 | DATACENTER_BASEMENT_ZN_6 | Cooling | 373774.80562 | 373774.80562 | 22.35181 | 22.35181 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 07:00:00 | 18.81600 | 1.27063E-002 | 783.67941 | 42.18139 | 0.33839 | 0.00000 |
40 | DATACENTER_BASEMENT_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 0.33839 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 06:10:00 | -32.70000 | 1.83376E-004 | 783.67941 | 42.18139 | 0.33839 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | VAV_BOT WITH REHEAT | Cooling | Sensible | 156659.12 | 10.71741 | 10.71741 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
2 | VAV_BOT WITH REHEAT | Heating | Sensible | 133870.62 | 3.42046 | 3.42046 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 06:30:00 |
3 | VAV_MID WITH REHEAT | Cooling | Sensible | 1462386.73 | 100.08750 | 100.08750 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
4 | VAV_MID WITH REHEAT | Heating | Sensible | 1337955.74 | 48.07806 | 48.07806 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 05:30:00 |
5 | VAV_TOP WITH REHEAT | Cooling | Sensible | 160663.58 | 11.00101 | 11.00101 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
6 | VAV_TOP WITH REHEAT | Heating | Sensible | 133883.25 | 7.59059 | 7.59059 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 02:20:00 |
7 | CAV_BAS | Cooling | Sensible | 79881.47 | 6.24706 | 6.24706 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
8 | CAV_BAS | Heating | Sensible | 101170.70 | 1.20016 | 1.20016 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
9 | AIRLOOP DATACENTER BASEMENT | Cooling | Sensible | 368813.28 | 22.35367 | 22.35367 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
10 | AIRLOOP DATACENTER BASEMENT | Heating | Sensible | 28525.81 | 0.33839 | 0.33839 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
11 | AIRLOOP DATACENTER BOT | Cooling | Sensible | 8839.89 | 0.53935 | 0.53935 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
12 | AIRLOOP DATACENTER BOT | Heating | Sensible | 1317.77 | 1.56323E-002 | 1.56323E-002 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
13 | AIRLOOP DATACENTER MID | Cooling | Sensible | 85124.62 | 5.19459 | 5.19459 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
14 | AIRLOOP DATACENTER MID | Heating | Sensible | 13177.74 | 0.15632 | 0.15632 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
15 | AIRLOOP DATACENTER TOP | Cooling | Sensible | 8626.37 | 0.52638 | 0.52638 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
16 | AIRLOOP DATACENTER TOP | Heating | Sensible | 1317.77 | 1.56323E-002 | 1.56323E-002 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | BASEMENT DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 6.24706 |
2 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 6.44200 |
3 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.29526 |
4 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30900 |
5 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.99058 |
6 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.78735 |
7 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
8 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.29040E-003 |
9 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.43103E-004 |
10 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.99058 |
11 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
12 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
13 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 27788.11619 |
14 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.43103E-004 |
15 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 586.02085 |
16 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 60.59484 |
17 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.31390 |
18 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.32200 |
19 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 19.51154 |
20 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.83705 |
21 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
22 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.21378E-003 |
23 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 4.70521E-003 |
24 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 19.51154 |
25 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
26 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
27 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 537834.02335 |
28 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 4.70521E-003 |
29 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 13326.87191 |
30 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 5.95589 |
31 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.31936 |
32 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.33600 |
33 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.00118 |
34 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.85161 |
35 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
36 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.19303E-003 |
37 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 9.80335E-004 |
38 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 3.48326 |
39 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
40 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
41 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 112058.31441 |
42 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 9.80335E-004 |
43 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 2957.09502 |
44 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.07070 |
45 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.22305 |
46 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.23300 |
47 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.24947 |
48 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.59480 |
49 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
50 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.70813E-003 |
51 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.96047E-004 |
52 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.69753 |
53 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
54 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
55 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 22409.41814 |
56 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.96047E-004 |
57 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 590.99005 |
58 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.56414 |
59 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 9.83960E-002 |
60 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
61 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.31283 |
62 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
63 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
64 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.87211E-003 |
65 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.33962E-004 |
66 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.47669 |
67 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
68 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
69 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 15312.73566 |
70 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.33962E-004 |
71 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 403.81294 |
72 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.90845 |
73 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.12514 |
74 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
75 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.38169 |
76 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.33371 |
77 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
78 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.04455E-003 |
79 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.13909E-004 |
80 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.76120 |
81 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
82 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
83 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 24451.14519 |
84 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.13909E-004 |
85 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 644.79153 |
86 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.87131 |
87 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 8.22445E-002 |
88 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
89 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.37426 |
90 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
91 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
92 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 4.63253E-003 |
93 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.14472E-004 |
94 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.40721 |
95 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
96 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
97 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 13084.87242 |
98 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.14472E-004 |
99 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 345.11198 |
100 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 10.09768 |
101 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.23651 |
102 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.24300 |
103 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.45374 |
104 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.63069 |
105 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
106 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.61092E-003 |
107 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.75088E-003 |
108 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 9.79378 |
109 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
110 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
111 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 314442.50446 |
112 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.75088E-003 |
113 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 8290.21413 |
114 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 16.71217 |
115 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 9.20916E-002 |
116 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
117 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 3.34243 |
118 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
119 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
120 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 4.13719E-003 |
121 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.82571E-003 |
122 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 6.50022 |
123 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
124 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
125 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 208689.56197 |
126 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.82571E-003 |
127 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 5501.95499 |
128 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 19.62923 |
129 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.12167 |
130 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
131 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 3.92585 |
132 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.32445 |
133 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
134 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.13146E-003 |
135 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.79015E-003 |
136 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 9.93378 |
137 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
138 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
139 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 318931.67955 |
140 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.79015E-003 |
141 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 8408.50183 |
142 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 17.74270 |
143 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 8.67428E-002 |
144 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
145 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 3.54854 |
146 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
147 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
148 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 4.39230E-003 |
149 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.80235E-003 |
150 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 6.41700 |
151 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
152 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
153 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 206019.98809 |
154 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.80235E-003 |
155 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 5431.59961 |
156 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.23214 |
157 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.19383 |
158 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.22600 |
159 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.27846 |
160 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.51687 |
161 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
162 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.96568E-003 |
163 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 3.45989E-004 |
164 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.23214 |
165 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
166 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
167 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 39548.70169 |
168 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.45989E-004 |
169 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 1042.56401 |
170 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.66883 |
171 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 9.22233E-002 |
172 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
173 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.33377 |
174 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
175 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
176 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 4.13128E-003 |
177 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.28458E-004 |
178 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.81361 |
179 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
180 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
181 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 26114.18984 |
182 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.28458E-004 |
183 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 688.40099 |
184 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.05934 |
185 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.11597 |
186 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
187 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.41187 |
188 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30926 |
189 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
190 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.28527E-003 |
191 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 3.50355E-004 |
192 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.24770 |
193 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
194 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
195 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 40047.71048 |
196 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.50355E-004 |
197 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 1055.71283 |
198 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.84238 |
199 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 8.35362E-002 |
200 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
201 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.36848 |
202 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
203 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
204 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 4.56090E-003 |
205 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.28533E-004 |
206 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.81388 |
207 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
208 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
209 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 26122.67671 |
210 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.28533E-004 |
211 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 688.62307 |
212 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DATACENTER_BOT_ZN_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.53935 |
213 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DATACENTER_MID_ZN_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 5.19459 |
214 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DATACENTER_TOP_ZN_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.52638 |
215 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DATACENTER_BASEMENT_ZN_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 22.35181 |
216 | AirLoopHVAC | VAV_BOT WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 6.42830 |
217 | AirLoopHVAC | VAV_BOT WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 3.30883 |
218 | AirLoopHVAC | VAV_BOT WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 12.85660 |
219 | AirLoopHVAC | VAV_BOT WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 3.42046 |
220 | AirLoopHVAC | VAV_BOT WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 10.71741 |
221 | AirLoopHVAC | VAV_BOT WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 10.71741 |
222 | AirLoopHVAC | VAV_BOT WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
223 | AirLoopHVAC | VAV_BOT WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.31915 |
224 | AirLoopHVAC | VAV_MID WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 62.38831 |
225 | AirLoopHVAC | VAV_MID WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 32.78209 |
226 | AirLoopHVAC | VAV_MID WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 124.77662 |
227 | AirLoopHVAC | VAV_MID WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 48.07806 |
228 | AirLoopHVAC | VAV_MID WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 100.08750 |
229 | AirLoopHVAC | VAV_MID WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 100.08750 |
230 | AirLoopHVAC | VAV_MID WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
231 | AirLoopHVAC | VAV_MID WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.48036 |
232 | AirLoopHVAC | VAV_TOP WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 6.37929 |
233 | AirLoopHVAC | VAV_TOP WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 3.39375 |
234 | AirLoopHVAC | VAV_TOP WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 12.75858 |
235 | AirLoopHVAC | VAV_TOP WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 7.59059 |
236 | AirLoopHVAC | VAV_TOP WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 11.00101 |
237 | AirLoopHVAC | VAV_TOP WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 11.00101 |
238 | AirLoopHVAC | VAV_TOP WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
239 | AirLoopHVAC | VAV_TOP WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.68999 |
240 | AirLoopHVAC | CAV_BAS | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 6.24706 |
241 | AirLoopHVAC | CAV_BAS | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 6.24706 |
242 | AirLoopHVAC | CAV_BAS | Sum of Air Terminal Maximum Flow Rates [m3/s] | 6.24706 |
243 | AirLoopHVAC | CAV_BAS | Adjusted Heating Design Air Flow Rate [m3/s] | 6.24706 |
244 | AirLoopHVAC | CAV_BAS | Adjusted Cooling Design Air Flow Rate [m3/s] | 6.24706 |
245 | AirLoopHVAC | CAV_BAS | Adjusted Main Design Air Flow Rate [m3/s] | 6.24706 |
246 | AirLoopHVAC | CAV_BAS | User Heating Air Flow Ratio [] | 1.00000 |
247 | AirLoopHVAC | CAV_BAS | Calculated Heating Air Flow Ratio [] | 1.00000 |
248 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 22.35181 |
249 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 22.35181 |
250 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 22.35181 |
251 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Adjusted Heating Design Air Flow Rate [m3/s] | 22.35181 |
252 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Adjusted Cooling Design Air Flow Rate [m3/s] | 22.35367 |
253 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Adjusted Main Design Air Flow Rate [m3/s] | 22.35367 |
254 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | User Heating Air Flow Ratio [] | 1.00000 |
255 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Calculated Heating Air Flow Ratio [] | 0.99992 |
256 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.53935 |
257 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.53935 |
258 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.53935 |
259 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Adjusted Heating Design Air Flow Rate [m3/s] | 0.53935 |
260 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.53935 |
261 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Adjusted Main Design Air Flow Rate [m3/s] | 0.53935 |
262 | AirLoopHVAC | AIRLOOP DATACENTER BOT | User Heating Air Flow Ratio [] | 1.00000 |
263 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Calculated Heating Air Flow Ratio [] | 1.00000 |
264 | AirLoopHVAC | AIRLOOP DATACENTER MID | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 5.19459 |
265 | AirLoopHVAC | AIRLOOP DATACENTER MID | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 5.19459 |
266 | AirLoopHVAC | AIRLOOP DATACENTER MID | Sum of Air Terminal Maximum Flow Rates [m3/s] | 5.19459 |
267 | AirLoopHVAC | AIRLOOP DATACENTER MID | Adjusted Heating Design Air Flow Rate [m3/s] | 5.19459 |
268 | AirLoopHVAC | AIRLOOP DATACENTER MID | Adjusted Cooling Design Air Flow Rate [m3/s] | 5.19459 |
269 | AirLoopHVAC | AIRLOOP DATACENTER MID | Adjusted Main Design Air Flow Rate [m3/s] | 5.19459 |
270 | AirLoopHVAC | AIRLOOP DATACENTER MID | User Heating Air Flow Ratio [] | 1.00000 |
271 | AirLoopHVAC | AIRLOOP DATACENTER MID | Calculated Heating Air Flow Ratio [] | 1.00000 |
272 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.52638 |
273 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.52638 |
274 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.52638 |
275 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Adjusted Heating Design Air Flow Rate [m3/s] | 0.52638 |
276 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.52638 |
277 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Adjusted Main Design Air Flow Rate [m3/s] | 0.52638 |
278 | AirLoopHVAC | AIRLOOP DATACENTER TOP | User Heating Air Flow Ratio [] | 1.00000 |
279 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Calculated Heating Air Flow Ratio [] | 1.00000 |
280 | AirLoopHVAC | VAV_BOT WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 10.71741 |
281 | AirLoopHVAC | VAV_MID WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 100.08750 |
282 | AirLoopHVAC | VAV_TOP WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 11.00101 |
283 | AirLoopHVAC | CAV_BAS | Design Supply Air Flow Rate [m3/s] | 6.24706 |
284 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Design Supply Air Flow Rate [m3/s] | 22.35367 |
285 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Design Supply Air Flow Rate [m3/s] | 0.53935 |
286 | AirLoopHVAC | AIRLOOP DATACENTER MID | Design Supply Air Flow Rate [m3/s] | 5.19459 |
287 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Design Supply Air Flow Rate [m3/s] | 0.52638 |
288 | Controller:OutdoorAir | VAV_BOT WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 10.71741 |
289 | Controller:OutdoorAir | VAV_BOT WITH REHEAT_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 2.53819 |
290 | HeatExchanger:AirToAir:SensibleAndLatent | VAV_BOT WITH REHEAT OA HEAT RECOVERY | Design Size Nominal Supply Air Flow Rate [m3/s] | 2.53819 |
291 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Inlet Air Temperature [C] | 25.44845 |
292 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
293 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Outlet Air Temperature [C] | 10.87565 |
294 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 9.76154E-003 |
295 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
296 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Coil Load [W] | 223699.74310 |
297 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 9.51670E-003 |
298 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 10.71741 |
299 | Coil:Heating:Water | VAV_BOT WITH REHEAT HEATING COIL | Design Size Rated Capacity [W] | 128608.27012 |
300 | Coil:Heating:Water | VAV_BOT WITH REHEAT HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.12512E-003 |
301 | Coil:Heating:Water | VAV_BOT WITH REHEAT HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 1885.02983 |
302 | Fan:VariableVolume | VAV_BOT WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 10.71741 |
303 | Controller:WaterCoil | VAV_BOT WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 9.51670E-003 |
304 | Controller:WaterCoil | VAV_BOT WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 5.00373E-005 |
305 | Controller:WaterCoil | VAV_BOT WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 1.12512E-003 |
306 | Controller:OutdoorAir | VAV_MID WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 100.08750 |
307 | Controller:OutdoorAir | VAV_MID WITH REHEAT_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 25.38195 |
308 | HeatExchanger:AirToAir:SensibleAndLatent | VAV_MID WITH REHEAT OA HEAT RECOVERY | Design Size Nominal Supply Air Flow Rate [m3/s] | 25.38195 |
309 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Inlet Air Temperature [C] | 25.56600 |
310 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
311 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Outlet Air Temperature [C] | 10.87610 |
312 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 9.89040E-003 |
313 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
314 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Coil Load [W] | 2140844.69582 |
315 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 9.10765E-002 |
316 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 100.08750 |
317 | Coil:Heating:Water | VAV_MID WITH REHEAT HEATING COIL | Design Size Rated Capacity [W] | 1308944.78709 |
318 | Coil:Heating:Water | VAV_MID WITH REHEAT HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.14512E-002 |
319 | Coil:Heating:Water | VAV_MID WITH REHEAT HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 18738.58325 |
320 | Fan:VariableVolume | VAV_MID WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 100.08750 |
321 | Controller:WaterCoil | VAV_MID WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 9.10765E-002 |
322 | Controller:WaterCoil | VAV_MID WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 5.22847E-006 |
323 | Controller:WaterCoil | VAV_MID WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 1.14512E-002 |
324 | Controller:OutdoorAir | VAV_TOP WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 11.00101 |
325 | Controller:OutdoorAir | VAV_TOP WITH REHEAT_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 2.53819 |
326 | HeatExchanger:AirToAir:SensibleAndLatent | VAV_TOP WITH REHEAT OA HEAT RECOVERY | Design Size Nominal Supply Air Flow Rate [m3/s] | 2.53819 |
327 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Inlet Air Temperature [C] | 25.40748 |
328 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
329 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Outlet Air Temperature [C] | 10.87569 |
330 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 9.77286E-003 |
331 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
332 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Coil Load [W] | 229452.62260 |
333 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 9.76144E-003 |
334 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 11.00101 |
335 | Coil:Heating:Water | VAV_TOP WITH REHEAT HEATING COIL | Design Size Rated Capacity [W] | 129416.37590 |
336 | Coil:Heating:Water | VAV_TOP WITH REHEAT HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.13219E-003 |
337 | Coil:Heating:Water | VAV_TOP WITH REHEAT HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 1907.21150 |
338 | Fan:VariableVolume | VAV_TOP WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 11.00101 |
339 | Controller:WaterCoil | VAV_TOP WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 9.76144E-003 |
340 | Controller:WaterCoil | VAV_TOP WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 4.87828E-005 |
341 | Controller:WaterCoil | VAV_TOP WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 1.13219E-003 |
342 | Controller:OutdoorAir | CAV_BAS_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 6.24706 |
343 | Controller:OutdoorAir | CAV_BAS_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.20016 |
344 | HeatExchanger:AirToAir:SensibleAndLatent | CAV_BAS OA HEAT RECOVERY | Design Size Nominal Supply Air Flow Rate [m3/s] | 1.20016 |
345 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Inlet Air Temperature [C] | 25.18093 |
346 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
347 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Outlet Air Temperature [C] | 11.36358 |
348 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 9.77299E-003 |
349 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
350 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Coil Load [W] | 125039.63573 |
351 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 5.31948E-003 |
352 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 6.24706 |
353 | Coil:Heating:Water | CAV_BAS HEATING COIL | Design Size Rated Capacity [W] | 335252.23891 |
354 | Coil:Heating:Water | CAV_BAS HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.93293E-003 |
355 | Coil:Heating:Water | CAV_BAS HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 7091.32754 |
356 | Fan:ConstantVolume | CAV_BAS FAN | Design Size Maximum Flow Rate [m3/s] | 6.24706 |
357 | Controller:WaterCoil | CAV_BAS_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 5.31948E-003 |
358 | Controller:WaterCoil | CAV_BAS_COOLC_CONTROLLER | Controller Convergence Tolerance | 8.95183E-005 |
359 | Controller:WaterCoil | CAV_BAS_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 2.93293E-003 |
360 | Controller:OutdoorAir | AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 22.35367 |
361 | Controller:OutdoorAir | AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.33839 |
362 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 22.35367 |
363 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Rated Total Cooling Capacity [W] | 437947.86849 |
364 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Rated Sensible Cooling Capacity [W] | 302632.25703 |
365 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Rated Water Flow Rate [m3/s] | 1.07253E-002 |
366 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 22.35367 |
367 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 22.35367 |
368 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 22.35367 |
369 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 22.35367 |
370 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Nominal Heating Capacity [W] | 437947.86849 |
371 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 437947.86849 |
372 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 28525.80837 |
373 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
374 | Fan:OnOff | AIRLOOP DATACENTER BASEMENT SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 22.35367 |
375 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 22.35367 |
376 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT HEATING COIL | Design Size Rated Heating Capacity [W] | 437947.86849 |
377 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT HEATING COIL | Design Size Rated Water Flow Rate [m3/s] | 1.07253E-002 |
378 | Coil:Heating:Electric | AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 28525.80837 |
379 | Humidifier:Steam:Electric | DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | Design Size Nominal Capacity Volume [m3/s] | 2.06633E-004 |
380 | Humidifier:Steam:Electric | DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | User-Specified Nominal Capacity Volume [m3/s] | 3.72000E-005 |
381 | Humidifier:Steam:Electric | DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | Design Size Rated Power [W] | 96450.69782 |
382 | Humidifier:Steam:Electric | DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | User-Specified Rated Power [W] | 100000.00000 |
383 | Controller:OutdoorAir | AIRLOOP DATACENTER BOT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.53935 |
384 | Controller:OutdoorAir | AIRLOOP DATACENTER BOT_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.56323E-002 |
385 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.53935 |
386 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT COOLING COIL | Design Size Rated Total Cooling Capacity [W] | 10376.82941 |
387 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT COOLING COIL | Design Size Rated Sensible Cooling Capacity [W] | 7230.01023 |
388 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT COOLING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.54128E-004 |
389 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 0.53935 |
390 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 0.53935 |
391 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 0.53935 |
392 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 0.53935 |
393 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Nominal Heating Capacity [W] | 10376.82941 |
394 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 10376.82941 |
395 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 1317.77417 |
396 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
397 | Fan:OnOff | AIRLOOP DATACENTER BOT SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.53935 |
398 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.53935 |
399 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT HEATING COIL | Design Size Rated Heating Capacity [W] | 10376.82941 |
400 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT HEATING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.54128E-004 |
401 | Coil:Heating:Electric | AIRLOOP DATACENTER BOT_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 1317.77417 |
402 | Controller:OutdoorAir | AIRLOOP DATACENTER MID_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 5.19459 |
403 | Controller:OutdoorAir | AIRLOOP DATACENTER MID_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.15632 |
404 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 5.19459 |
405 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID COOLING COIL | Design Size Rated Total Cooling Capacity [W] | 100031.98315 |
406 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID COOLING COIL | Design Size Rated Sensible Cooling Capacity [W] | 69661.31930 |
407 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID COOLING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.44978E-003 |
408 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 5.19459 |
409 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 5.19459 |
410 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 5.19459 |
411 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 5.19459 |
412 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Nominal Heating Capacity [W] | 100031.98315 |
413 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 100031.98315 |
414 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 13177.74171 |
415 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
416 | Fan:OnOff | AIRLOOP DATACENTER MID SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 5.19459 |
417 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 5.19459 |
418 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID HEATING COIL | Design Size Rated Heating Capacity [W] | 100031.98315 |
419 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID HEATING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.44978E-003 |
420 | Coil:Heating:Electric | AIRLOOP DATACENTER MID_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 13177.74171 |
421 | Controller:OutdoorAir | AIRLOOP DATACENTER TOP_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.52638 |
422 | Controller:OutdoorAir | AIRLOOP DATACENTER TOP_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.56323E-002 |
423 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.52638 |
424 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP COOLING COIL | Design Size Rated Total Cooling Capacity [W] | 10133.26105 |
425 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP COOLING COIL | Design Size Rated Sensible Cooling Capacity [W] | 7057.95677 |
426 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP COOLING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.48163E-004 |
427 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 0.52638 |
428 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 0.52638 |
429 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 0.52638 |
430 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 0.52638 |
431 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Nominal Heating Capacity [W] | 10133.26105 |
432 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 10133.26105 |
433 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 1317.77417 |
434 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
435 | Fan:OnOff | AIRLOOP DATACENTER TOP SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.52638 |
436 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.52638 |
437 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP HEATING COIL | Design Size Rated Heating Capacity [W] | 10133.26105 |
438 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP HEATING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.48163E-004 |
439 | Coil:Heating:Electric | AIRLOOP DATACENTER TOP_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 1317.77417 |
440 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Flow Rate [m3/s] | 0.11567 |
441 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Power Consumption [W] | 18886.04701 |
442 | PlantLoop | COOLSYS1_DEMAND | Maximum Loop Flow Rate [m3/s] | 0.11567 |
443 | PlantLoop | COOLSYS1_DEMAND | Plant Loop Volume [m3] | 13.88089 |
444 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Loop Supply Side Design Fluid Flow Rate [m3/s] | 0.11567 |
445 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Loop Demand Side Design Fluid Flow Rate [m3/s] | 0.11567 |
446 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Heat Exchanger U-Factor Times Area Value [W/C] | 485542.26737 |
447 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Loop-to-loop Temperature Difference Used to Size Heat Exchanger U-Factor Times Area Value [C] | 5.60000 |
448 | PlantLoop | HEATSYS1 | Maximum Loop Flow Rate [m3/s] | 3.35509E-002 |
449 | PlantLoop | HEATSYS1 | Plant Loop Volume [m3] | 4.02611 |
450 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Flow Rate [m3/s] | 3.35509E-002 |
451 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Power Consumption [W] | 10104.06653 |
452 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Minimum Flow Rate [m3/s] | 0.00000 |
453 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Nominal Capacity [W] | 3835077.31016 |
454 | Boiler:HotWater | HEATSYS1 BOILER | User-Specified Nominal Capacity [W] | 3835077.31000 |
455 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Design Water Flow Rate [m3/s] | 3.35509E-002 |
456 | PlantLoop | COOLSYS1_SUPPLY | Maximum Loop Flow Rate [m3/s] | 0.11567 |
457 | PlantLoop | COOLSYS1_SUPPLY | Plant Loop Volume [m3] | 13.88089 |
458 | Pump:ConstantSpeed | COOLSYS1 CHILLER1 PUMP | Design Flow Rate [m3/s] | 5.78371E-002 |
459 | Pump:ConstantSpeed | COOLSYS1 CHILLER1 PUMP | Design Power Consumption [W] | 6537.72363 |
460 | Pump:ConstantSpeed | COOLSYS1 CHILLER2 PUMP | Design Flow Rate [m3/s] | 5.78371E-002 |
461 | Pump:ConstantSpeed | COOLSYS1 CHILLER2 PUMP | Design Power Consumption [W] | 6537.72363 |
462 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | Design Size Reference Chilled Water Flow Rate [m3/s] | 0.11567 |
463 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | User-Specified Reference Chilled Water Flow Rate [m3/s] | 5.81800E-002 |
464 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | Design Size Reference Capacity [W] | 1370939.07274 |
465 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | User-Specified Reference Capacity [W] | 1377480.50500 |
466 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | Design Size Reference Condenser Water Flow Rate [m3/s] | 6.81664E-002 |
467 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | Design Size Reference Chilled Water Flow Rate [m3/s] | 0.11567 |
468 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | User-Specified Reference Chilled Water Flow Rate [m3/s] | 5.81800E-002 |
469 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | Design Size Reference Capacity [W] | 1370939.07274 |
470 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | User-Specified Reference Capacity [W] | 1377480.50500 |
471 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | Design Size Reference Condenser Water Flow Rate [m3/s] | 6.81664E-002 |
472 | PlantLoop | SINGLE WATER PLANT LOOP | Maximum Loop Flow Rate [m3/s] | 1.36774E-002 |
473 | PlantLoop | SINGLE WATER PLANT LOOP | Plant Loop Volume [m3] | 1.64129 |
474 | Pump:ConstantSpeed | PLANT CIRC PUMP | Design Flow Rate [m3/s] | 1.36774E-002 |
475 | Pump:ConstantSpeed | PLANT CIRC PUMP | Design Power Consumption [W] | 3488.41657 |
476 | FluidCooler:TwoSpeed | CENTRAL TOWER | Design Water Flow Rate [m3/s] | 1.36774E-002 |
477 | FluidCooler:TwoSpeed | CENTRAL TOWER | Air Flow Rate at High Fan Speed [m3/s] | 139666.46671 |
478 | FluidCooler:TwoSpeed | CENTRAL TOWER | Fluid cooler UA value at high fan speed based on nominal capacity input [W/K] | 57830.62582 |
479 | FluidCooler:TwoSpeed | CENTRAL TOWER | Air Flow Rate at Low Fan Speed [m3/s] | 69833.23335 |
480 | FluidCooler:TwoSpeed | CENTRAL TOWER | Fan Power at Low Fan Speed [W] | 7879.72339 |
481 | FluidCooler:TwoSpeed | CENTRAL TOWER | U-factor Times Area Value at Low Fan Speed [W/C] | 21269.22881 |
482 | Boiler:HotWater | CENTRAL BOILER | Design Size Nominal Capacity [W] | 563390.91188 |
483 | Boiler:HotWater | CENTRAL BOILER | User-Specified Nominal Capacity [W] | 552306.81000 |
484 | Boiler:HotWater | CENTRAL BOILER | Design Size Design Water Flow Rate [m3/s] | 1.36774E-002 |
485 | PlantLoop | SWHSYS1 | Maximum Loop Flow Rate [m3/s] | 4.40000E-004 |
486 | PlantLoop | SWHSYS1 | Plant Loop Volume [m3] | 5.28000E-002 |
487 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Flow Rate [m3/s] | 4.40000E-004 |
488 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Power Consumption [W] | 56.20530 |
489 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | Use Side Design Flow Rate [m3/s] | 4.40000E-004 |
490 | CondenserLoop | TOWERWATERSYS | Maximum Loop Flow Rate [m3/s] | 0.13633 |
491 | CondenserLoop | TOWERWATERSYS | Condenser Loop Volume [m3] | 16.35994 |
492 | HeaderedPumps:VariableSpeed | TOWERWATERSYS PUMP | Design Flow Rate [m3/s] | 0.13633 |
493 | HeaderedPumps:VariableSpeed | TOWERWATERSYS PUMP | Design Power Consumption [W] | 33752.98736 |
494 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Design Air Flow Rate [m3/s] | 54.98119 |
495 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Nominal Capacity [W] | 1634899.14991 |
496 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Air Flow Rate in free convection regime [m3/s] | 10.99624 |
497 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Tower capacity in free convection regime at design conditions [W] | 204362.39374 |
498 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Design Air Flow Rate [m3/s] | 54.98119 |
499 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Nominal Capacity [W] | 1634899.14991 |
500 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Air Flow Rate in free convection regime [m3/s] | 10.99624 |
501 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Tower capacity in free convection regime at design conditions [W] | 204362.39374 |
502 | PlantEquipmentOperation:ComponentSetPoint | WSHPPLANT OPERATION SCHEME | Design Water Flow Rate [m3/s] Equipment # 47 | 7.08025E-002 |
503 | PlantEquipmentOperation:ComponentSetPoint | WSHPPLANT OPERATION SCHEME | Design Water Flow Rate [m3/s] Equipment # 47 | 7.08025E-002 |
Component Type | Name | Nominal Total Capacity {W} | |
1 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | 26344.34 |
2 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | 509445.96 |
3 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | 106188.08 |
4 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | 21233.01 |
5 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | 14508.74 |
6 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | 23167.26 |
7 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | 12398.18 |
8 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | 297919.37 |
9 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | 197722.77 |
10 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | 302172.19 |
11 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | 195193.66 |
12 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | 37469.65 |
13 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | 24741.32 |
14 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | 37942.38 |
15 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | 24749.35 |
16 | Coil:Heating:Water | VAV_BOT WITH REHEAT HEATING COIL | 81526.27 |
17 | Coil:Heating:Water | VAV_MID WITH REHEAT HEATING COIL | 805821.31 |
18 | Coil:Heating:Water | VAV_TOP WITH REHEAT HEATING COIL | 82581.54 |
19 | Coil:Heating:Water | CAV_BAS HEATING COIL | 250042.76 |
Component Type | Name | Nominal Total Capacity {W} | Nominal Sensible Capacity {W} | Nominal Latent Capacity {W} | Nominal Sensible Heat Ratio | Nominal Coil UA Value {W/C} | Nominal Coil Surface Area {m2} | |
1 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | 269462.33 | 182027.18 | 87435.15 | 0.68 | 28981.35 | 293.94 |
2 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | 2542744.99 | 1711723.88 | 831021.11 | 0.67 | 273411.05 | 2773.09 |
3 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | 276557.07 | 186831.78 | 89725.30 | 0.68 | 29754.25 | 301.78 |
4 | Coil:Cooling:Water | CAV_BAS COOLING COIL | 151880.67 | 103572.77 | 48307.90 | 0.68 | 15924.27 | 161.51 |
Component Type | Component Name | IPLV in SI Units {W/W} | IPLV in IP Units {Btu/W-h} | |
1 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | 6.84 | 23.33 |
2 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | 6.84 | 23.33 |
Zone Name | # Surfaces | |
1 | BASEMENT | 10 |
2 | CORE_BOTTOM | 8 |
3 | CORE_MID | 7 |
4 | CORE_TOP | 7 |
5 | PERIMETER_BOT_ZN_3 | 18 |
6 | PERIMETER_BOT_ZN_2 | 12 |
7 | PERIMETER_BOT_ZN_1 | 18 |
8 | PERIMETER_BOT_ZN_4 | 12 |
9 | PERIMETER_MID_ZN_3 | 9 |
10 | PERIMETER_MID_ZN_2 | 8 |
11 | PERIMETER_MID_ZN_1 | 9 |
12 | PERIMETER_MID_ZN_4 | 8 |
13 | PERIMETER_TOP_ZN_3 | 9 |
14 | PERIMETER_TOP_ZN_2 | 8 |
15 | PERIMETER_TOP_ZN_1 | 9 |
16 | PERIMETER_TOP_ZN_4 | 8 |
17 | GROUNDFLOOR_PLENUM | 11 |
18 | MIDFLOOR_PLENUM | 11 |
19 | TOPFLOOR_PLENUM | 11 |
20 | DATACENTER_BOT_ZN_6 | 6 |
21 | DATACENTER_MID_ZN_6 | 6 |
22 | DATACENTER_TOP_ZN_6 | 6 |
23 | DATACENTER_BASEMENT_ZN_6 | 10 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | BASEMENT_WALL_EAST | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_EAST_CFACTOR | 0.270 | 0.259 | 118.87 | 118.87 | 118.87 | 90.00 | 90.00 | 48.74 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | BASEMENT_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_SOUTH_CFACTOR | 0.270 | 0.259 | 139.09 | 139.09 | 139.09 | 180.00 | 90.00 | 57.03 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
3 | BASEMENT_WALL_NORTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_NORTH_CFACTOR | 0.270 | 0.259 | 139.09 | 139.09 | 139.09 | 0.00 | 90.00 | 57.03 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | BASEMENT_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.87 | 118.87 | 118.87 | 270.00 | 90.00 | 48.74 | 2.44 | 0.00 | DATACENTER_BASEMENT_ZN_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
5 | BASEMENT_FLOOR | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 2779.43 | 2779.43 | 2779.43 | 0.00 | 180.00 | 57.03 | 48.74 | 0.00 | BASEMENT_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
6 | PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | PERIMETER_BOT_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
7 | PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 250.34 | 250.34 | 250.34 | 180.00 | 0.00 | 57.03 | 4.57 | 0.00 | PERIMETER_BOT_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
8 | CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 2076.77 | 2076.77 | 2076.77 | 180.00 | 0.00 | 52.45 | 39.59 | 0.00 | CORE_BOT_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
9 | PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 250.34 | 250.34 | 250.34 | 180.00 | 0.00 | 52.45 | 4.57 | 0.00 | PERIMETER_BOT_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
10 | BASEMENT_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 7126.21 | 7126.21 | 7126.21 | 0.00 | 90.00 | 7126.21 | 1.00 | 0.00 | BASEMENT_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
11 | CORE_BOT_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
12 | CORE_BOT_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
13 | CORE_BOT_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
14 | CORE_BOT_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
15 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 419.30 | 419.30 | 419.30 | 0.00 | 180.00 | 10.59 | 39.59 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
16 | CORE_BOT_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 2076.82 | 2076.82 | 2076.82 | 0.00 | 180.00 | 52.46 | 39.59 | 0.00 | CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
17 | CORE_BOT_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 2496.12 | 2496.12 | 2496.12 | 180.00 | 0.00 | 63.05 | 39.59 | 0.00 | iz-CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
18 | CORE_BOTTOM_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 5064.65 | 5064.65 | 5064.65 | 0.00 | 90.00 | 5064.65 | 1.00 | 0.00 | CORE_BOTTOM_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
19 | CORE_MID_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
20 | CORE_MID_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
21 | CORE_MID_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
22 | CORE_MID_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
23 | CORE_MID_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_MID_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
24 | CORE_MID_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 2496.12 | 2496.12 | 2496.12 | 180.00 | 0.00 | 63.05 | 39.59 | 0.00 | iz-CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
25 | CORE_MID_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 5064.65 | 5064.65 | 5064.65 | 0.00 | 90.00 | 5064.65 | 1.00 | 0.00 | CORE_MID_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
26 | CORE_TOP_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
27 | CORE_TOP_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
28 | CORE_TOP_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
29 | CORE_TOP_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
30 | CORE_TOP_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_TOP_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
31 | CORE_TOP_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 2496.12 | 2496.12 | 2496.12 | 180.00 | 0.00 | 63.05 | 39.59 | 0.00 | iz-CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
32 | CORE_TOP_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 5064.65 | 5064.65 | 5064.65 | 0.00 | 90.00 | 5064.65 | 1.00 | 0.00 | CORE_TOP_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
33 | PERIMETER_BOT_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.830 | 0.738 | 76.91 | 200.61 | 76.91 | 0.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
34 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.379_SHGC_NORTH_0.45 | N/A | 2.153 | No | 23.18 | 23.18 | 23.18 | 0.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
35 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.379_SHGC_NORTH_0.45 | N/A | 2.153 | No | 23.18 | 23.18 | 23.18 | 0.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
36 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.379_SHGC_NORTH_0.45 | N/A | 2.153 | No | 23.18 | 23.18 | 23.18 | 0.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
37 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.379_SHGC_NORTH_0.45 | N/A | 2.153 | No | 23.18 | 23.18 | 23.18 | 0.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
38 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.379_SHGC_NORTH_0.45 | N/A | 2.153 | No | 23.18 | 23.18 | 23.18 | 0.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
39 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.839 | 2.839 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
40 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.839 | 2.839 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
41 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.839 | 2.839 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
42 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.839 | 2.839 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
43 | PERIMETER_BOT_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
44 | CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
45 | PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
46 | DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
47 | PERIMETER_BOT_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 250.34 | 250.34 | 250.34 | 0.00 | 180.00 | 52.46 | 6.47 | 0.00 | PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
48 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 63.07 | 63.07 | 63.07 | 0.00 | 180.00 | 11.51 | 4.57 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
49 | PERIMETER_BOT_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.41 | 313.41 | 313.41 | 180.00 | 0.00 | 63.96 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
50 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.83 | 626.83 | 626.83 | 0.00 | 90.00 | 626.83 | 1.00 | 0.00 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
51 | PERIMETER_BOT_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.830 | 0.738 | 52.57 | 133.74 | 52.57 | 90.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
52 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.379_SHGC_EAST_0.45 | N/A | 2.153 | No | 25.75 | 25.75 | 25.75 | 90.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
53 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.379_SHGC_EAST_0.45 | N/A | 2.153 | No | 25.75 | 25.75 | 25.75 | 90.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
54 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.379_SHGC_EAST_0.45 | N/A | 2.153 | No | 25.75 | 25.75 | 25.75 | 90.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
55 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | Door | PERIMETER_BOT_ZN_2_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.839 | 2.839 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
56 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | Door | PERIMETER_BOT_ZN_2_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.839 | 2.839 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
57 | PERIMETER_BOT_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
58 | CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
59 | PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
60 | PERIMETER_BOT_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
61 | PERIMETER_BOT_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | iz-PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
62 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
63 | PERIMETER_BOT_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.830 | 0.738 | 76.91 | 200.61 | 76.91 | 180.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
64 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.379_SHGC_SOUTH_0.45 | N/A | 2.153 | No | 23.18 | 23.18 | 23.18 | 180.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
65 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.379_SHGC_SOUTH_0.45 | N/A | 2.153 | No | 23.18 | 23.18 | 23.18 | 180.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
66 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.379_SHGC_SOUTH_0.45 | N/A | 2.153 | No | 23.18 | 23.18 | 23.18 | 180.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
67 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.379_SHGC_SOUTH_0.45 | N/A | 2.153 | No | 23.18 | 23.18 | 23.18 | 180.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
68 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.379_SHGC_SOUTH_0.45 | N/A | 2.153 | No | 23.18 | 23.18 | 23.18 | 180.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
69 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.839 | 2.839 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
70 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.839 | 2.839 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
71 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.839 | 2.839 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
72 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.839 | 2.839 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
73 | PERIMETER_BOT_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
74 | DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
75 | PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
76 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
77 | DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 63.07 | 63.07 | 63.07 | 0.00 | 180.00 | 16.08 | 4.57 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
78 | PERIMETER_BOT_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 250.35 | 250.35 | 250.35 | 0.00 | 180.00 | 57.03 | 6.47 | 0.00 | PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
79 | PERIMETER_BOT_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.42 | 313.42 | 313.42 | 180.00 | 0.00 | 73.11 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
80 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.84 | 626.84 | 626.84 | 0.00 | 90.00 | 626.84 | 1.00 | 0.00 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
81 | PERIMETER_BOT_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.830 | 0.738 | 52.57 | 133.74 | 52.57 | 270.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
82 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.379_SHGC_WEST_0.45 | N/A | 2.153 | No | 25.75 | 25.75 | 25.75 | 270.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
83 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.379_SHGC_WEST_0.45 | N/A | 2.153 | No | 25.75 | 25.75 | 25.75 | 270.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
84 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.379_SHGC_WEST_0.45 | N/A | 2.153 | No | 25.75 | 25.75 | 25.75 | 270.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
85 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | Door | PERIMETER_BOT_ZN_4_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.839 | 2.839 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
86 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | Door | PERIMETER_BOT_ZN_4_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.839 | 2.839 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
87 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
88 | DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
89 | PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
90 | PERIMETER_BOT_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
91 | PERIMETER_BOT_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | iz-PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
92 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
93 | PERIMETER_MID_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.786 | 0.703 | 84.71 | 200.61 | 84.71 | 0.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
94 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_MID_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.379_SHGC_NORTH_0.45 | N/A | 2.153 | No | 115.90 | 115.90 | 115.90 | 0.00 | 90.00 | 73.11 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
95 | PERIMETER_MID_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
96 | CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
97 | PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
98 | DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
99 | PERIMETER_MID_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
100 | PERIMETER_MID_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.41 | 313.41 | 313.41 | 180.00 | 0.00 | 63.96 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
101 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.83 | 626.83 | 626.83 | 0.00 | 90.00 | 626.83 | 1.00 | 0.00 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
102 | PERIMETER_MID_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.786 | 0.703 | 56.47 | 133.74 | 56.47 | 90.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
103 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_MID_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.379_SHGC_EAST_0.45 | N/A | 2.153 | No | 77.26 | 77.26 | 77.26 | 90.00 | 90.00 | 48.74 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
104 | PERIMETER_MID_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
105 | CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
106 | PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
107 | PERIMETER_MID_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_MID_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
108 | PERIMETER_MID_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | iz-PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
109 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
110 | PERIMETER_MID_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
111 | PERIMETER_MID_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.786 | 0.703 | 84.71 | 200.61 | 84.71 | 180.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
112 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_MID_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.379_SHGC_SOUTH_0.45 | N/A | 2.153 | No | 115.90 | 115.90 | 115.90 | 180.00 | 90.00 | 73.11 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
113 | DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
114 | PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
115 | CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
116 | PERIMETER_MID_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
117 | PERIMETER_MID_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.42 | 313.42 | 313.42 | 180.00 | 0.00 | 73.11 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
118 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.84 | 626.84 | 626.84 | 0.00 | 90.00 | 626.84 | 1.00 | 0.00 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
119 | PERIMETER_MID_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.786 | 0.703 | 56.47 | 133.74 | 56.47 | 270.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
120 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_MID_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.379_SHGC_WEST_0.45 | N/A | 2.153 | No | 77.26 | 77.26 | 77.26 | 270.00 | 90.00 | 48.74 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
121 | PERIMETER_MID_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
122 | DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
123 | PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
124 | PERIMETER_MID_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_MID_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
125 | PERIMETER_MID_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | iz-PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
126 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
127 | PERIMETER_TOP_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.009 | 0.877 | 84.71 | 200.61 | 84.71 | 0.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
128 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_TOP_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.379_SHGC_NORTH_0.45 | N/A | 2.153 | No | 115.90 | 115.90 | 115.90 | 0.00 | 90.00 | 73.11 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
129 | PERIMETER_TOP_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
130 | CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
131 | PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
132 | DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
133 | PERIMETER_TOP_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_TOP_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
134 | PERIMETER_TOP_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.41 | 313.41 | 313.41 | 180.00 | 0.00 | 63.96 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
135 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.83 | 626.83 | 626.83 | 0.00 | 90.00 | 626.83 | 1.00 | 0.00 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
136 | PERIMETER_TOP_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.009 | 0.877 | 56.47 | 133.74 | 56.47 | 90.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
137 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_TOP_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.379_SHGC_EAST_0.45 | N/A | 2.153 | No | 77.26 | 77.26 | 77.26 | 90.00 | 90.00 | 48.74 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
138 | PERIMETER_TOP_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
139 | CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
140 | INT-PER3S-NE-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | INT-PER3S-NE | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
141 | PERIMETER_TOP_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_TOP_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
142 | PERIMETER_TOP_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | iz-PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
143 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
144 | PERIMETER_TOP_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.009 | 0.877 | 84.71 | 200.61 | 84.71 | 180.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
145 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_TOP_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.379_SHGC_SOUTH_0.45 | N/A | 2.153 | No | 115.90 | 115.90 | 115.90 | 180.00 | 90.00 | 73.11 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
146 | INT-PER3S-NE | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | INT-PER3S-NE-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
147 | DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
148 | PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
149 | CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
150 | PERIMETER_TOP_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_TOP_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
151 | PERIMETER_TOP_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.42 | 313.42 | 313.42 | 180.00 | 0.00 | 73.11 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
152 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.84 | 626.84 | 626.84 | 0.00 | 90.00 | 626.84 | 1.00 | 0.00 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
153 | PERIMETER_TOP_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.009 | 0.877 | 56.47 | 133.74 | 56.47 | 270.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
154 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_TOP_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.379_SHGC_WEST_0.45 | N/A | 2.153 | No | 77.26 | 77.26 | 77.26 | 270.00 | 90.00 | 48.74 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
155 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
156 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
157 | PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
158 | PERIMETER_TOP_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_TOP_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
159 | PERIMETER_TOP_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | iz-PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
160 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
161 | GROUNDFLOOR_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.830 | 0.738 | 89.13 | 89.13 | 89.13 | 0.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
162 | GROUNDFLOOR_PLENUM_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.830 | 0.738 | 59.42 | 59.42 | 59.42 | 270.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
163 | GROUNDFLOOR_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.830 | 0.738 | 89.13 | 89.13 | 89.13 | 180.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
164 | GROUNDFLOOR_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.830 | 0.738 | 59.42 | 59.42 | 59.42 | 90.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
165 | iz-CORE_BOT_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
166 | iz-PERIMETER_BOT_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
167 | iz-PERIMETER_BOT_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
168 | iz-PERIMETER_BOT_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
169 | iz-PERIMETER_BOT_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
170 | iz-DATACENTER_BOT_ZN_6_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_BOT_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
171 | GROUNDFLOOR_PLENUM_CEILING | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 3563.11 | 3563.11 | 3563.11 | 180.00 | 0.00 | 73.11 | 48.74 | 0.00 | GROUNDFLOOR_PLENUM_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
172 | MIDFLOOR_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.786 | 0.703 | 89.13 | 89.13 | 89.13 | 0.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
173 | MIDFLOOR_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.786 | 0.703 | 59.42 | 59.42 | 59.42 | 270.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
174 | MIDFLOOR_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.786 | 0.703 | 89.13 | 89.13 | 89.13 | 180.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
175 | MIDFLOOR_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.786 | 0.703 | 59.42 | 59.42 | 59.42 | 90.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
176 | iz-CORE_MID_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
177 | iz-PERIMETER_MID_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
178 | iz-PERIMETER_MID_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
179 | iz-PERIMETER_MID_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
180 | iz-PERIMETER_MID_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
181 | iz-DATACENTER_MID_ZN_6_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_MID_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
182 | MIDFLOOR_PLENUM_CEILING | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 3563.11 | 3563.11 | 3563.11 | 180.00 | 0.00 | 73.11 | 48.74 | 0.00 | MIDFLOOR_PLENUM_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
183 | TOPFLOOR_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.009 | 0.877 | 89.13 | 89.13 | 89.13 | 180.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
184 | TOPFLOOR_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.009 | 0.877 | 59.42 | 59.42 | 59.42 | 90.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
185 | TOPFLOOR_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.009 | 0.877 | 59.42 | 59.42 | 59.42 | 270.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
186 | TOPFLOOR_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.009 | 0.877 | 89.13 | 89.13 | 89.13 | 0.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
187 | iz-CORE_TOP_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
188 | iz-PERIMETER_TOP_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
189 | iz-PERIMETER_TOP_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
190 | iz-PERIMETER_TOP_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
191 | iz-PERIMETER_TOP_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
192 | iz-DATACENTER_TOP_ZN_6_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_TOP_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
193 | BUILDING_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.163 | 0.158 | 3563.11 | 3563.11 | 3563.11 | 180.00 | 0.00 | 73.11 | 48.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
194 | DATACENTER_BOT_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
195 | DATACENTER_BOT_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
196 | DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
197 | DATACENTER_BOT_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
198 | DATACENTER_BOT_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
199 | DATACENTER_BOT_ZN_6_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | iz-DATACENTER_BOT_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
200 | DATACENTER_MID_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
201 | DATACENTER_MID_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
202 | DATACENTER_MID_ZN_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
203 | DATACENTER_MID_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
204 | DATACENTER_MID_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_MID_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
205 | DATACENTER_MID_ZN_6_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | iz-DATACENTER_MID_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
206 | DATACENTER_TOP_ZN_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
207 | DATACENTER_TOP_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
208 | DATACENTER_TOP_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
209 | DATACENTER_TOP_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
210 | DATACENTER_TOP_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_TOP_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
211 | DATACENTER_TOP_ZN_6_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | iz-DATACENTER_TOP_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
212 | DATACENTER_BASEMENT_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR | 0.270 | 0.259 | 39.22 | 39.22 | 39.22 | 0.00 | 90.00 | 16.08 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
213 | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR | 0.270 | 0.259 | 39.22 | 39.22 | 39.22 | 180.00 | 90.00 | 16.08 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
214 | DATACENTER_BASEMENT_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR | 0.270 | 0.259 | 118.87 | 118.87 | 118.87 | 270.00 | 90.00 | 48.74 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
215 | DATACENTER_BASEMENT_ZN_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.87 | 118.87 | 118.87 | 90.00 | 90.00 | 48.74 | 2.44 | 0.00 | BASEMENT_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
216 | DATACENTER_BASEMENT_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 783.68 | 783.68 | 783.68 | 0.00 | 180.00 | 16.08 | 48.74 | 0.00 | DATACENTER_BASEMENT_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
217 | DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | DATACENTER_BOT_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
218 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 419.35 | 419.35 | 419.35 | 180.00 | 0.00 | 10.59 | 39.59 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
219 | PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | PERIMETER_BOT_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
220 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 63.08 | 63.08 | 63.08 | 180.00 | 0.00 | 16.08 | 6.47 | 0.00 | DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
221 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 63.07 | 63.07 | 63.07 | 180.00 | 0.00 | 11.51 | 6.47 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | BASEMENT | RunPeriod: RUNPERIOD 1 | 2.3300054694E-003 | 1.4900141601E-003 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
2 | CORE_BOTTOM | RunPeriod: RUNPERIOD 1 | 0.1206112116 | 8.5163417542E-002 | Pass | Pass | 0.4868565974 | 0.4974273159 | Pass | Pass |
3 | CORE_MID | RunPeriod: RUNPERIOD 1 | 1.5230370930E-002 | 1.2302778942E-002 | Pass | Pass | 0.4881464142 | 0.4931656645 | Pass | Pass |
4 | CORE_TOP | RunPeriod: RUNPERIOD 1 | 0.1522481814 | 0.1677613400 | Pass | Pass | 0.5792512772 | 0.5309792981 | Pass | Pass |
5 | PERIMETER_BOT_ZN_3 | RunPeriod: RUNPERIOD 1 | 0.2979868685 | 0.3041985944 | Pass | Pass | 0.5395708275 | 0.4903096040 | Pass | Pass |
6 | PERIMETER_BOT_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.2755116580 | 0.3183024369 | Pass | Pass | 0.5825411612 | 0.5866607458 | Pass | Pass |
7 | PERIMETER_BOT_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.2838762951 | 0.2952157798 | Pass | Pass | 0.7988427472 | 3.3244507738 | Pass | Pass |
8 | PERIMETER_BOT_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.1045017120 | 0.1260576833 | Pass | Pass | 0.5525747635 | 0.6383354054 | Pass | Pass |
9 | PERIMETER_MID_ZN_3 | RunPeriod: RUNPERIOD 1 | 1.0110869363 | 0.8055566341 | Pass | Pass | 0.5539360393 | 0.5115760806 | Pass | Pass |
10 | PERIMETER_MID_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.8800247110 | 0.9188215263 | Pass | Pass | 0.5319410662 | 0.4895410279 | Pass | Pass |
11 | PERIMETER_MID_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.5912500464 | 0.6945869583 | Pass | Pass | 0.5687764326 | 0.6505864021 | Pass | Pass |
12 | PERIMETER_MID_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.8380139703 | 0.8868754075 | Pass | Pass | 0.5400562829 | 0.5065412004 | Pass | Pass |
13 | PERIMETER_TOP_ZN_3 | RunPeriod: RUNPERIOD 1 | 1.2481755563 | 0.9992295140 | Pass | Pass | 0.5375139232 | 0.5038505600 | Pass | Pass |
14 | PERIMETER_TOP_ZN_2 | RunPeriod: RUNPERIOD 1 | 1.1262642142 | 1.1343390887 | Pass | Pass | 0.5313884518 | 0.4801886171 | Pass | Pass |
15 | PERIMETER_TOP_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.7682514520 | 0.9104149694 | Pass | Pass | 0.5894609898 | 0.6730999864 | Pass | Pass |
16 | PERIMETER_TOP_ZN_4 | RunPeriod: RUNPERIOD 1 | 1.0904535129 | 1.1155835242 | Pass | Pass | 0.5337690125 | 0.4834982292 | Pass | Pass |
17 | GROUNDFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 4.6232420610E-002 | 4.5475031673E-002 | Pass | Pass | 0.4974127947 | 0.4742730106 | Pass | Pass |
18 | MIDFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 0.1137828245 | 7.4407686937E-002 | Pass | Pass | 0.4886275496 | 0.4910221689 | Pass | Pass |
19 | TOPFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 0.2586225862 | 0.2039796131 | Pass | Pass | 0.4933490554 | 0.4876715776 | Pass | Pass |
20 | DATACENTER_BOT_ZN_6 | RunPeriod: RUNPERIOD 1 | 2.1529344116E-002 | 2.5697326946E-002 | Pass | Pass | 0.1649548801 | 1.2523002112 | Pass | Pass |
21 | DATACENTER_MID_ZN_6 | RunPeriod: RUNPERIOD 1 | 3.5616153997E-002 | 4.6596834533E-002 | Pass | Pass | 1.0801190016E-002 | 1.8936547484E-002 | Pass | Pass |
22 | DATACENTER_TOP_ZN_6 | RunPeriod: RUNPERIOD 1 | 4.0151165241E-002 | 4.7298294880E-002 | Pass | Pass | 1.2234575396E-002 | 1.9450229143E-002 | Pass | Pass |
23 | DATACENTER_BASEMENT_ZN_6 | RunPeriod: RUNPERIOD 1 | 8.5910016040E-006 | 6.1810507609E-006 | Pass | Pass | 1.5351422098E-004 | 1.2997348844E-004 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 08:43:41
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 6301.49 | 308.52 | 0.00 | 33327.84 | 10554.63 | 50492.49 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 08:43:41
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | -32.70 | 0.00 | -32.70 | Wetbulb [C] | 2.40 | 210.00 |
INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 30.10 | 12.40 | 21.10 | Wetbulb [C] | 4.70 | 200.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 0.00 | 0 | |||
Feb | 0.00 | 0 | |||
Mar | 12.00 | 13 | |||
Apr | 16.00 | 23 | |||
May | 0.00 | 0 | |||
Jun | 190.00 | 53 | |||
Jul | 136.00 | 41 | |||
Aug | 87.00 | 42 | |||
Sep | 0.00 | 0 | |||
Oct | 0.00 | 0 | |||
Nov | 0.00 | 0 | |||
Dec | 0.00 | 0 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 08:43:41
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BASEMENT_WALL_EAST | BASEMENT_WALL_EAST_CFACTOR | 1.00 | 0.261 | 0.270 | 118.87 | 118.87 | 90.00 | 90.00 | E |
BASEMENT_WALL_SOUTH | BASEMENT_WALL_SOUTH_CFACTOR | 1.00 | 0.261 | 0.270 | 139.09 | 139.09 | 180.00 | 90.00 | S |
BASEMENT_WALL_NORTH | BASEMENT_WALL_NORTH_CFACTOR | 1.00 | 0.261 | 0.270 | 139.09 | 139.09 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_3_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.738 | 0.830 | 200.61 | 76.91 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_2_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.738 | 0.830 | 133.74 | 52.57 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.738 | 0.830 | 200.61 | 76.91 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_4_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.738 | 0.830 | 133.74 | 52.57 | 270.00 | 90.00 | W |
PERIMETER_MID_ZN_3_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.703 | 0.786 | 2006.06 | 847.11 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_2_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 0.703 | 0.786 | 1337.37 | 564.74 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.703 | 0.786 | 2006.06 | 847.11 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_4_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 0.703 | 0.786 | 1337.37 | 564.74 | 270.00 | 90.00 | W |
PERIMETER_TOP_ZN_3_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 0.877 | 1.009 | 200.61 | 84.71 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_2_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 0.877 | 1.009 | 133.74 | 56.47 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 0.877 | 1.009 | 200.61 | 84.71 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_4_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 0.877 | 1.009 | 133.74 | 56.47 | 270.00 | 90.00 | W |
GROUNDFLOOR_PLENUM_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.738 | 0.830 | 89.13 | 89.13 | 0.00 | 90.00 | N |
GROUNDFLOOR_PLENUM_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.738 | 0.830 | 59.42 | 59.42 | 270.00 | 90.00 | W |
GROUNDFLOOR_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.738 | 0.830 | 89.13 | 89.13 | 180.00 | 90.00 | S |
GROUNDFLOOR_PLENUM_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.738 | 0.830 | 59.42 | 59.42 | 90.00 | 90.00 | E |
MIDFLOOR_PLENUM_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.703 | 0.786 | 891.32 | 891.32 | 0.00 | 90.00 | N |
MIDFLOOR_PLENUM_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 0.703 | 0.786 | 594.21 | 594.21 | 270.00 | 90.00 | W |
MIDFLOOR_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.703 | 0.786 | 891.32 | 891.32 | 180.00 | 90.00 | S |
MIDFLOOR_PLENUM_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 0.703 | 0.786 | 594.21 | 594.21 | 90.00 | 90.00 | E |
TOPFLOOR_PLENUM_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 0.877 | 1.009 | 89.13 | 89.13 | 180.00 | 90.00 | S |
TOPFLOOR_PLENUM_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 0.877 | 1.009 | 59.42 | 59.42 | 90.00 | 90.00 | E |
TOPFLOOR_PLENUM_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 0.877 | 1.009 | 59.42 | 59.42 | 270.00 | 90.00 | W |
TOPFLOOR_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 0.877 | 1.009 | 89.13 | 89.13 | 0.00 | 90.00 | N |
BUILDING_ROOF | NONRES_ROOF | 0.30 | 0.159 | 0.163 | 3563.11 | 3563.11 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_WALL_NORTH | DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR | 1.00 | 0.261 | 0.270 | 39.22 | 39.22 | 0.00 | 90.00 | N |
DATACENTER_BASEMENT_ZN_6_WALL_SOUTH | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR | 1.00 | 0.261 | 0.270 | 39.22 | 39.22 | 180.00 | 90.00 | S |
DATACENTER_BASEMENT_ZN_6_WALL_WEST | DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR | 1.00 | 0.261 | 0.270 | 118.87 | 118.87 | 270.00 | 90.00 | W |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BASEMENT_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 118.87 | 118.87 | 270.00 | 90.00 | W |
BASEMENT_FLOOR | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 2779.43 | 2779.43 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 225.00 | 0.00 | |
PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 250.34 | 250.34 | 180.00 | 0.00 | |
CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 2076.77 | 2076.77 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 250.34 | 250.34 | 180.00 | 0.00 | |
CORE_BOT_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
CORE_BOT_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
CORE_BOT_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 419.30 | 419.30 | 0.00 | 180.00 | |
CORE_BOT_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 2076.82 | 2076.82 | 0.00 | 180.00 | |
CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 180.00 | 0.00 | |
CORE_MID_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 180.00 | 90.00 | S |
CORE_MID_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 270.00 | 90.00 | W |
CORE_MID_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 0.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 90.00 | 90.00 | E |
CORE_MID_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 24961.20 | 24961.20 | 0.00 | 180.00 | |
CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 24961.20 | 24961.20 | 180.00 | 0.00 | |
CORE_TOP_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
CORE_TOP_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
CORE_TOP_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
CORE_TOP_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 2496.12 | 2496.12 | 0.00 | 180.00 | |
CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 250.34 | 250.34 | 0.00 | 180.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 63.07 | 63.07 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
PERIMETER_BOT_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 45.00 | 180.00 | |
PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 225.00 | 0.00 | |
PERIMETER_BOT_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 63.07 | 63.07 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 250.35 | 250.35 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
PERIMETER_BOT_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 315.00 | 180.00 | |
PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 135.00 | 0.00 | |
PERIMETER_MID_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 225.00 | 90.00 | W |
CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 135.00 | 90.00 | S |
DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 3134.13 | 3134.13 | 0.00 | 180.00 | |
PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.13 | 3134.13 | 180.00 | 0.00 | |
PERIMETER_MID_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 315.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 270.00 | 90.00 | W |
PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 225.00 | 90.00 | W |
PERIMETER_MID_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 2019.75 | 2019.75 | 45.00 | 180.00 | |
PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 225.00 | 0.00 | |
PERIMETER_MID_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 45.00 | 90.00 | E |
DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 315.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 3134.20 | 3134.20 | 0.00 | 180.00 | |
PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.20 | 3134.20 | 180.00 | 0.00 | |
PERIMETER_MID_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 135.00 | 90.00 | S |
DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 45.00 | 90.00 | E |
PERIMETER_MID_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 2019.75 | 2019.75 | 315.00 | 180.00 | |
PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 135.00 | 0.00 | |
PERIMETER_TOP_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 313.41 | 313.41 | 0.00 | 180.00 | |
PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 180.00 | 0.00 | |
PERIMETER_TOP_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
INT-PER3S-NE-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
PERIMETER_TOP_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 201.98 | 201.98 | 45.00 | 180.00 | |
PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 225.00 | 0.00 | |
INT-PER3S-NE | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 313.42 | 313.42 | 0.00 | 180.00 | |
PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 180.00 | 0.00 | |
PERIMETER_TOP_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
PERIMETER_TOP_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 201.98 | 201.98 | 315.00 | 180.00 | |
PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 135.00 | 0.00 | |
iz-CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 45.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 315.00 | 180.00 | |
iz-DATACENTER_BOT_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 0.00 | 180.00 | |
GROUNDFLOOR_PLENUM_CEILING | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 3563.11 | 3563.11 | 180.00 | 0.00 | |
iz-CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 24961.20 | 24961.20 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.13 | 3134.13 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 45.00 | 180.00 | |
iz-PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.20 | 3134.20 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 315.00 | 180.00 | |
iz-DATACENTER_MID_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 362.03 | 362.03 | 0.00 | 180.00 | |
MIDFLOOR_PLENUM_CEILING | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 35631.06 | 35631.06 | 180.00 | 0.00 | |
iz-CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 45.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 315.00 | 180.00 | |
iz-DATACENTER_TOP_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 0.00 | 180.00 | |
DATACENTER_BOT_ZN_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
DATACENTER_BOT_ZN_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
DATACENTER_BOT_ZN_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
DATACENTER_BOT_ZN_6_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 36.20 | 36.20 | 0.00 | 180.00 | |
DATACENTER_BOT_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 180.00 | 0.00 | |
DATACENTER_MID_ZN_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 270.00 | 90.00 | W |
DATACENTER_MID_ZN_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 180.00 | 90.00 | S |
DATACENTER_MID_ZN_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 90.00 | 90.00 | E |
DATACENTER_MID_ZN_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 0.00 | 90.00 | N |
DATACENTER_MID_ZN_6_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 362.03 | 362.03 | 0.00 | 180.00 | |
DATACENTER_MID_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 362.03 | 362.03 | 180.00 | 0.00 | |
DATACENTER_TOP_ZN_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
DATACENTER_TOP_ZN_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
DATACENTER_TOP_ZN_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
DATACENTER_TOP_ZN_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
DATACENTER_TOP_ZN_6_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 36.20 | 36.20 | 0.00 | 180.00 | |
DATACENTER_TOP_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 118.87 | 118.87 | 90.00 | 90.00 | E |
DATACENTER_BASEMENT_ZN_6_FLOOR | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 783.68 | 783.68 | 0.00 | 180.00 | |
DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 36.20 | 36.20 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 419.35 | 419.35 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 135.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 63.08 | 63.08 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 63.07 | 63.07 | 180.00 | 0.00 | |
BASEMENT_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 7126.21 | 0.00 | 90.00 | N | ||
CORE_BOTTOM_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 5064.65 | 0.00 | 90.00 | N | ||
CORE_MID_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 50646.53 | 0.00 | 90.00 | N | ||
CORE_TOP_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 5064.65 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.83 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.84 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 6268.26 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 4039.50 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 6268.35 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 4039.48 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.83 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.84 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | WINDOW_U_0.379_SHGC_NORTH_0.45 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.153 | 0.451 | 0.497 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | WINDOW_U_0.379_SHGC_NORTH_0.45 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.153 | 0.451 | 0.497 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | WINDOW_U_0.379_SHGC_NORTH_0.45 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.153 | 0.451 | 0.497 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | WINDOW_U_0.379_SHGC_NORTH_0.45 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.153 | 0.451 | 0.497 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | WINDOW_U_0.379_SHGC_NORTH_0.45 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.153 | 0.451 | 0.497 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | WINDOW_U_0.379_SHGC_EAST_0.45 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 2.153 | 0.451 | 0.497 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | WINDOW_U_0.379_SHGC_EAST_0.45 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 2.153 | 0.451 | 0.497 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | WINDOW_U_0.379_SHGC_EAST_0.45 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 2.153 | 0.451 | 0.497 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | WINDOW_U_0.379_SHGC_SOUTH_0.45 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.153 | 0.451 | 0.497 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | WINDOW_U_0.379_SHGC_SOUTH_0.45 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.153 | 0.451 | 0.497 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | WINDOW_U_0.379_SHGC_SOUTH_0.45 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.153 | 0.451 | 0.497 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | WINDOW_U_0.379_SHGC_SOUTH_0.45 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.153 | 0.451 | 0.497 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | WINDOW_U_0.379_SHGC_SOUTH_0.45 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.153 | 0.451 | 0.497 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | WINDOW_U_0.379_SHGC_WEST_0.45 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 2.153 | 0.451 | 0.497 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | WINDOW_U_0.379_SHGC_WEST_0.45 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 2.153 | 0.451 | 0.497 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | WINDOW_U_0.379_SHGC_WEST_0.45 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 2.153 | 0.451 | 0.497 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.379_SHGC_NORTH_0.45 | 115.90 | 0.00 | 0.00 | 115.90 | 1158.95 | 2.153 | 0.451 | 0.497 | No | PERIMETER_MID_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.379_SHGC_EAST_0.45 | 77.26 | 0.00 | 0.00 | 77.26 | 772.63 | 2.153 | 0.451 | 0.497 | No | PERIMETER_MID_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.379_SHGC_SOUTH_0.45 | 115.90 | 0.00 | 0.00 | 115.90 | 1158.95 | 2.153 | 0.451 | 0.497 | No | PERIMETER_MID_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.379_SHGC_WEST_0.45 | 77.26 | 0.00 | 0.00 | 77.26 | 772.63 | 2.153 | 0.451 | 0.497 | No | PERIMETER_MID_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.379_SHGC_NORTH_0.45 | 115.90 | 0.00 | 0.00 | 115.90 | 115.90 | 2.153 | 0.451 | 0.497 | No | PERIMETER_TOP_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.379_SHGC_EAST_0.45 | 77.26 | 0.00 | 0.00 | 77.26 | 77.26 | 2.153 | 0.451 | 0.497 | No | PERIMETER_TOP_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.379_SHGC_SOUTH_0.45 | 115.90 | 0.00 | 0.00 | 115.90 | 115.90 | 2.153 | 0.451 | 0.497 | No | PERIMETER_TOP_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.379_SHGC_WEST_0.45 | 77.26 | 0.00 | 0.00 | 77.26 | 77.26 | 2.153 | 0.451 | 0.497 | No | PERIMETER_TOP_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
Total or Average | 4635.80 | 2.153 | 0.451 | 0.497 | |||||||||||||||||
North Total or Average | 1390.74 | 2.153 | 0.451 | 0.497 | |||||||||||||||||
Non-North Total or Average | 3245.06 | 2.153 | 0.451 | 0.497 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | SWINGING DOOR_CON | 1.992 | 2.839 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | SWINGING DOOR_CON | 1.992 | 2.839 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | SWINGING DOOR_CON | 1.992 | 2.839 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | SWINGING DOOR_CON | 1.992 | 2.839 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | SWINGING DOOR_CON | 1.992 | 2.839 | 1.95 | PERIMETER_BOT_ZN_2_WALL_EAST |
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | SWINGING DOOR_CON | 1.992 | 2.839 | 1.95 | PERIMETER_BOT_ZN_2_WALL_EAST |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | SWINGING DOOR_CON | 1.992 | 2.839 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | SWINGING DOOR_CON | 1.992 | 2.839 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | SWINGING DOOR_CON | 1.992 | 2.839 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | SWINGING DOOR_CON | 1.992 | 2.839 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | SWINGING DOOR_CON | 1.992 | 2.839 | 1.95 | PERIMETER_BOT_ZN_4_WALL_WEST |
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | SWINGING DOOR_CON | 1.992 | 2.839 | 1.95 | PERIMETER_BOT_ZN_4_WALL_WEST |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 08:43:41
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 08:43:41
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
BASEMENT_LIGHTS | BASEMENT | BASEMENT | GENERAL | 10.2732 | 2779.43 | 28553.72 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 49.04 | 0.0000 | Y | 262.84 |
CORE_BOTTOM_LIGHTS | CORE_BOTTOM | CORE_BOTTOM | GENERAL | 10.2732 | 2496.12 | 25643.24 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 49.04 | 0.0000 | Y | 236.05 |
CORE_MID_LIGHTS | CORE_MID | CORE_MID | GENERAL | 10.2732 | 24961.20 | 256432.45 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 49.04 | 0.0000 | Y | 2360.52 |
CORE_TOP_LIGHTS | CORE_TOP | CORE_TOP | GENERAL | 10.2732 | 2496.12 | 25643.24 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 49.04 | 0.0000 | Y | 236.05 |
PERIMETER_BOT_ZN_3_LIGHTS | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3 | GENERAL | 10.2732 | 313.41 | 3219.77 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 28.95 | 0.0000 | Y | 17.50 |
PERIMETER_BOT_ZN_2_LIGHTS | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2 | GENERAL | 10.2732 | 201.98 | 2074.94 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 28.69 | 0.0000 | Y | 11.17 |
PERIMETER_BOT_ZN_1_LIGHTS | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1 | GENERAL | 10.2732 | 313.42 | 3219.84 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 28.43 | 0.0000 | Y | 17.18 |
PERIMETER_BOT_ZN_4_LIGHTS | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4 | GENERAL | 10.2732 | 201.98 | 2074.94 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 28.62 | 0.0000 | Y | 11.15 |
PERIMETER_MID_ZN_3_LIGHTS | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3 | GENERAL | 10.2732 | 3134.13 | 32197.65 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 28.89 | 0.0000 | Y | 174.62 |
PERIMETER_MID_ZN_2_LIGHTS | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2 | GENERAL | 10.2732 | 2019.75 | 20749.39 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 28.65 | 0.0000 | Y | 111.60 |
PERIMETER_MID_ZN_1_LIGHTS | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1 | GENERAL | 10.2732 | 3134.20 | 32198.36 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 28.40 | 0.0000 | Y | 171.68 |
PERIMETER_MID_ZN_4_LIGHTS | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4 | GENERAL | 10.2732 | 2019.75 | 20749.39 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 28.58 | 0.0000 | Y | 111.33 |
PERIMETER_TOP_ZN_3_LIGHTS | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3 | GENERAL | 10.2732 | 313.41 | 3219.77 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 28.89 | 0.0000 | Y | 17.46 |
PERIMETER_TOP_ZN_2_LIGHTS | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2 | GENERAL | 10.2732 | 201.98 | 2074.94 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 28.65 | 0.0000 | Y | 11.16 |
PERIMETER_TOP_ZN_1_LIGHTS | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1 | GENERAL | 10.2732 | 313.42 | 3219.84 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 28.40 | 0.0000 | Y | 17.17 |
PERIMETER_TOP_ZN_4_LIGHTS | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4 | GENERAL | 10.2732 | 201.98 | 2074.94 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 28.58 | 0.0000 | Y | 11.13 |
DATACENTER_BASEMENT_LIGHTS | DATACENTER_BASEMENT_ZN_6 | DATACENTER_BASEMENT_ZN_6 | GENERAL | 10.2732 | 783.68 | 8050.93 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 49.04 | 0.0000 | Y | 74.11 |
DATACENTER_BOT_LIGHTS | DATACENTER_BOT_ZN_6 | DATACENTER_BOT_ZN_6 | GENERAL | 17.8735 | 36.20 | 647.07 | LightsWired | LTG_SCH_DATACENTER | 56.02 | 168.00 | 54.57 | 0.0000 | Y | 6.63 |
DATACENTER_MID_LIGHTS | DATACENTER_MID_ZN_6 | DATACENTER_MID_ZN_6 | GENERAL | 17.8735 | 362.03 | 6470.68 | LightsWired | LTG_SCH_DATACENTER | 56.02 | 168.00 | 54.57 | 0.0000 | Y | 66.28 |
DATACENTER_TOP_LIGHTS | DATACENTER_TOP_ZN_6 | DATACENTER_TOP_ZN_6 | GENERAL | 17.8735 | 36.20 | 647.07 | LightsWired | LTG_SCH_DATACENTER | 56.02 | 168.00 | 54.57 | 0.0000 | Y | 6.63 |
Interior Lighting Total | 10.3445 | 46320.38 | 479162.15 | 1235.84 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
PERIMETER_BOT_ZN_1_DAYLREFPT1 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_DAYLCTRL | SplitFlux | Stepped | 0.39 | 3219.84 | 1241.89 |
PERIMETER_BOT_ZN_1_DAYLREFPT2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_DAYLCTRL | SplitFlux | Stepped | 0.14 | 3219.84 | 445.95 |
PERIMETER_BOT_ZN_2_DAYLREFPT1 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_DAYLCTRL | SplitFlux | Stepped | 0.39 | 2074.94 | 800.30 |
PERIMETER_BOT_ZN_2_DAYLREFPT2 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_DAYLCTRL | SplitFlux | Stepped | 0.14 | 2074.94 | 287.38 |
PERIMETER_BOT_ZN_3_DAYLREFPT1 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_DAYLCTRL | SplitFlux | Stepped | 0.39 | 3219.77 | 1241.86 |
PERIMETER_BOT_ZN_3_DAYLREFPT2 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_DAYLCTRL | SplitFlux | Stepped | 0.14 | 3219.77 | 445.94 |
PERIMETER_BOT_ZN_4_DAYLREFPT1 | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_DAYLCTRL | SplitFlux | Stepped | 0.39 | 2074.94 | 800.30 |
PERIMETER_BOT_ZN_4_DAYLREFPT2 | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_DAYLCTRL | SplitFlux | Stepped | 0.14 | 2074.94 | 287.38 |
PERIMETER_MID_ZN_1_DAYLREFPT1 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_DAYLCTRL | SplitFlux | Stepped | 0.39 | 3219.84 | 1241.89 |
PERIMETER_MID_ZN_1_DAYLREFPT2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_DAYLCTRL | SplitFlux | Stepped | 0.14 | 3219.84 | 445.95 |
PERIMETER_MID_ZN_2_DAYLREFPT1 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_DAYLCTRL | SplitFlux | Stepped | 0.39 | 2074.94 | 800.30 |
PERIMETER_MID_ZN_2_DAYLREFPT2 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_DAYLCTRL | SplitFlux | Stepped | 0.14 | 2074.94 | 287.38 |
PERIMETER_MID_ZN_3_DAYLREFPT1 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_DAYLCTRL | SplitFlux | Stepped | 0.39 | 3219.77 | 1241.86 |
PERIMETER_MID_ZN_3_DAYLREFPT2 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_DAYLCTRL | SplitFlux | Stepped | 0.14 | 3219.77 | 445.94 |
PERIMETER_MID_ZN_4_DAYLREFPT1 | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_DAYLCTRL | SplitFlux | Stepped | 0.39 | 2074.94 | 800.30 |
PERIMETER_MID_ZN_4_DAYLREFPT2 | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_DAYLCTRL | SplitFlux | Stepped | 0.14 | 2074.94 | 287.38 |
PERIMETER_TOP_ZN_1_DAYLREFPT1 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_DAYLCTRL | SplitFlux | Stepped | 0.39 | 3219.84 | 1241.89 |
PERIMETER_TOP_ZN_1_DAYLREFPT2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_DAYLCTRL | SplitFlux | Stepped | 0.14 | 3219.84 | 445.95 |
PERIMETER_TOP_ZN_2_DAYLREFPT1 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_DAYLCTRL | SplitFlux | Stepped | 0.39 | 2074.94 | 800.30 |
PERIMETER_TOP_ZN_2_DAYLREFPT2 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_DAYLCTRL | SplitFlux | Stepped | 0.14 | 2074.94 | 287.38 |
PERIMETER_TOP_ZN_3_DAYLREFPT1 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_DAYLCTRL | SplitFlux | Stepped | 0.39 | 3219.77 | 1241.86 |
PERIMETER_TOP_ZN_3_DAYLREFPT2 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_DAYLCTRL | SplitFlux | Stepped | 0.14 | 3219.77 | 445.94 |
PERIMETER_TOP_ZN_4_DAYLREFPT1 | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_DAYLCTRL | SplitFlux | Stepped | 0.39 | 2074.94 | 800.30 |
PERIMETER_TOP_ZN_4_DAYLREFPT2 | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_DAYLCTRL | SplitFlux | Stepped | 0.14 | 2074.94 | 287.38 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS_A | 13279.00 | AstronomicalClock | - | 42.55 | 42.55 | 106.07 | |
EXTERIOR_LIGHTS_B | 44301.60 | AstronomicalClock | - | 83.52 | 71.23 | 592.34 | |
Exterior Lighting Total | 57580.60 | 698.41 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 08:43:41
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
BYPASS HEAT EXCHANGER | HeatExchanger:FluidToFluid | 2712783.72 | |||||
HEATSYS1 BOILER | Boiler:HotWater | 3835077.31 | 0.81 | ||||
COOLSYS1 CHILLER1 | Chiller:Electric:ReformulatedEIR | 1377480.50 | 6.28 | 1318422.77 | 5.98 | 6.84 | 23.33 |
COOLSYS1 CHILLER2 | Chiller:Electric:ReformulatedEIR | 1377480.50 | 6.28 | 1318422.77 | 5.98 | 6.84 | 23.33 |
CENTRAL TOWER | FluidCooler:TwoSpeed | 582060.00 | |||||
CENTRAL BOILER | Boiler:HotWater | 552306.81 | 0.80 | ||||
TOWERWATERSYS COOLTOWER 1 | CoolingTower:VariableSpeed | 1634899.15 | |||||
TOWERWATERSYS COOLTOWER 2 | CoolingTower:VariableSpeed | 1634899.15 |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
VAV_BOT WITH REHEAT COOLING COIL | Coil:Cooling:Water | 223699.74 | 269462.33 | 182027.18 | 87435.15 | 0.68 | - | 28981.35 | 293.94 |
VAV_MID WITH REHEAT COOLING COIL | Coil:Cooling:Water | 2140844.70 | 2542744.99 | 1711723.88 | 831021.11 | 0.67 | - | 273411.05 | 2773.09 |
VAV_TOP WITH REHEAT COOLING COIL | Coil:Cooling:Water | 229452.62 | 276557.07 | 186831.78 | 89725.30 | 0.68 | - | 29754.25 | 301.78 |
CAV_BAS COOLING COIL | Coil:Cooling:Water | 125039.64 | 151880.67 | 103572.77 | 48307.90 | 0.68 | - | 15924.27 | 161.51 |
AIRLOOP DATACENTER BASEMENT COOLING COIL | Coil:Cooling:WaterToAirHeatPump:EquationFit | 437947.87 | 302632.26 | 135315.61 | 0.69 | 0.00 | |||
AIRLOOP DATACENTER BOT COOLING COIL | Coil:Cooling:WaterToAirHeatPump:EquationFit | 10376.83 | 7230.01 | 3146.82 | 0.70 | 0.00 | |||
AIRLOOP DATACENTER MID COOLING COIL | Coil:Cooling:WaterToAirHeatPump:EquationFit | 100031.98 | 69661.32 | 30370.66 | 0.70 | 0.00 | |||
AIRLOOP DATACENTER TOP COOLING COIL | Coil:Cooling:WaterToAirHeatPump:EquationFit | 10133.26 | 7057.96 | 3075.30 | 0.70 | 0.00 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
None |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
None |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Water | 27788.12 | 26344.34 | - |
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Water | 537834.02 | 509445.96 | - |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Water | 112058.31 | 106188.08 | - |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 22409.42 | 21233.01 | - |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 15312.74 | 14508.74 | - |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 24451.15 | 23167.26 | - |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 13084.87 | 12398.18 | - |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 314442.50 | 297919.37 | - |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 208689.56 | 197722.77 | - |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 318931.68 | 302172.19 | - |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 206019.99 | 195193.66 | - |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 39548.70 | 37469.65 | - |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 26114.19 | 24741.32 | - |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 40047.71 | 37942.38 | - |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 26122.68 | 24749.35 | - |
VAV_BOT WITH REHEAT HEATING COIL | Coil:Heating:Water | 128608.27 | 81526.27 | - |
VAV_MID WITH REHEAT HEATING COIL | Coil:Heating:Water | 1308944.79 | 805821.31 | - |
VAV_TOP WITH REHEAT HEATING COIL | Coil:Heating:Water | 129416.38 | 82581.54 | - |
CAV_BAS HEATING COIL | Coil:Heating:Water | 335252.24 | 250042.76 | - |
AIRLOOP DATACENTER BASEMENT HEATING COIL | Coil:Heating:WaterToAirHeatPump:EquationFit | 437947.87 | 0.00 | |
AIRLOOP DATACENTER BOT HEATING COIL | Coil:Heating:WaterToAirHeatPump:EquationFit | 10376.83 | 0.00 | |
AIRLOOP DATACENTER MID HEATING COIL | Coil:Heating:WaterToAirHeatPump:EquationFit | 100031.98 | 0.00 | |
AIRLOOP DATACENTER TOP HEATING COIL | Coil:Heating:WaterToAirHeatPump:EquationFit | 10133.26 | 0.00 | |
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | Coil:Heating:Electric | 28525.81 | 1.00 | |
AIRLOOP DATACENTER BOT_SUPPHEATCOIL | Coil:Heating:Electric | 1317.77 | 1.00 | |
AIRLOOP DATACENTER MID_SUPPHEATCOIL | Coil:Heating:Electric | 13177.74 | 1.00 | |
AIRLOOP DATACENTER TOP_SUPPHEATCOIL | Coil:Heating:Electric | 1317.77 | 1.00 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
VAV_BOT WITH REHEAT FAN | Fan:VariableVolume | 0.61 | 1389.42 | 10.72 | 24345.60 | 2271.59 | 1.00 | 1.12 | General | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 |
VAV_MID WITH REHEAT FAN | Fan:VariableVolume | 0.61 | 1389.42 | 100.09 | 227358.09 | 2271.59 | 1.00 | 1.08 | General | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 |
VAV_TOP WITH REHEAT FAN | Fan:VariableVolume | 0.61 | 1389.42 | 11.00 | 24989.82 | 2271.59 | 1.00 | 1.12 | General | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 |
CAV_BAS FAN | Fan:ConstantVolume | 0.60 | 1018.41 | 6.25 | 10592.85 | 1695.65 | 1.00 | 1.15 | General | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
AIRLOOP DATACENTER BASEMENT SUPPLY FAN | Fan:OnOff | 0.62 | 1018.41 | 22.35 | 36866.73 | 1649.25 | 1.00 | 1.14 | General | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 |
AIRLOOP DATACENTER BOT SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.54 | 604.12 | 1120.11 | 1.00 | 1.57 | General | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
AIRLOOP DATACENTER MID SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 5.19 | 5818.50 | 1120.11 | 1.00 | 1.15 | General | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
AIRLOOP DATACENTER TOP SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.53 | 589.60 | 1120.11 | 1.00 | 1.58 | General | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
COOLSYS1 PUMP SECONDARY | Pump:VariableSpeed | Intermittent | 105797.75 | 0.115674 | 18886.05 | 163269.45 | 0.90 | General |
HEATSYS1 PUMP | Pump:VariableSpeed | Intermittent | 180705.70 | 0.033551 | 10104.07 | 301156.09 | 0.90 | General |
COOLSYS1 CHILLER1 PUMP | Pump:ConstantSpeed | Intermittent | 73247.35 | 0.057837 | 6537.72 | 113036.94 | 0.90 | General |
COOLSYS1 CHILLER2 PUMP | Pump:ConstantSpeed | Intermittent | 73247.35 | 0.057837 | 6537.72 | 113036.94 | 0.90 | General |
PLANT CIRC PUMP | Pump:ConstantSpeed | Intermittent | 179045.11 | 0.013677 | 3488.42 | 255050.01 | 0.90 | General |
SWHSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 29891.00 | 0.000440 | 56.21 | 127739.32 | 0.30 | General |
TOWERWATERSYS PUMP | HeaderedPumps:VariableSpeed | Intermittent | 148556.62 | 0.136333 | 33752.99 | 247577.87 | 0.90 | General |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 1.14 | 87921.32 | 0.80 | 0.48 | 0.06 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:43:41
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 83116.39 | 83116.39 | 29.90 | 6.247 | 6.247 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 24.00 | 24.00 | 0.00892 | 20.92 | 0.01271 | 1.200 | 0.00 |
CORE_BOTTOM | 85722.04 | 85722.04 | 34.34 | 6.442 | 6.442 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 24.00 | 24.00 | 0.00886 | 20.92 | 0.01271 | 1.078 | 0.00 |
CORE_MID | 806511.83 | 806511.83 | 323.11 | 60.595 | 60.595 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 24.00 | 24.00 | 0.00889 | 20.92 | 0.01271 | 10.778 | 0.00 |
CORE_TOP | 79273.99 | 79273.99 | 31.76 | 5.956 | 5.956 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 24.00 | 24.00 | 0.00889 | 20.92 | 0.01271 | 1.078 | 0.00 |
PERIMETER_BOT_ZN_3 | 14121.41 | 14121.41 | 45.06 | 1.071 | 1.071 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | 24.00 | 24.00 | 0.00887 | 30.10 | 0.01273 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_2 | 20629.72 | 20629.72 | 102.14 | 1.564 | 1.564 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 08:30:00 | 24.00 | 24.00 | 0.00867 | 22.10 | 0.01271 | 0.087 | 0.00 |
PERIMETER_BOT_ZN_1 | 25170.57 | 25170.57 | 80.31 | 1.908 | 1.908 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:20:00 | 24.00 | 24.00 | 0.00871 | 29.69 | 0.01273 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_4 | 24680.95 | 24680.95 | 122.20 | 1.871 | 1.871 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 | 24.00 | 24.00 | 0.00864 | 28.16 | 0.01272 | 0.087 | 0.00 |
PERIMETER_MID_ZN_3 | 133171.49 | 133171.49 | 424.91 | 10.098 | 10.098 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 | 24.00 | 24.00 | 0.00902 | 30.10 | 0.01273 | 1.353 | 0.00 |
PERIMETER_MID_ZN_2 | 220408.65 | 220408.65 | 1091.27 | 16.712 | 16.712 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 09:10:00 | 24.00 | 24.00 | 0.00871 | 23.63 | 0.01271 | 0.872 | 0.00 |
PERIMETER_MID_ZN_1 | 258879.38 | 258879.38 | 825.98 | 19.629 | 19.629 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 24.00 | 24.00 | 0.00877 | 29.79 | 0.01273 | 1.353 | 0.00 |
PERIMETER_MID_ZN_4 | 233999.89 | 233999.89 | 1158.56 | 17.743 | 17.743 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:20:00 | 24.00 | 24.00 | 0.00870 | 27.95 | 0.01272 | 0.872 | 0.00 |
PERIMETER_TOP_ZN_3 | 14667.25 | 14667.25 | 46.80 | 1.112 | 1.112 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | 24.00 | 24.00 | 0.00902 | 30.10 | 0.01273 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_2 | 22008.98 | 22008.98 | 108.97 | 1.669 | 1.669 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 09:10:00 | 24.00 | 24.00 | 0.00874 | 23.63 | 0.01271 | 0.087 | 0.00 |
PERIMETER_TOP_ZN_1 | 27159.09 | 27159.09 | 86.65 | 2.059 | 2.059 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 24.00 | 24.00 | 0.00879 | 29.89 | 0.01273 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_4 | 24297.79 | 24297.79 | 120.30 | 1.842 | 1.842 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:20:00 | 24.00 | 24.00 | 0.00871 | 27.95 | 0.01272 | 0.087 | 0.00 |
DATACENTER_BOT_ZN_6 | 9019.03 | 9019.03 | 249.13 | 0.539 | 0.539 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 19:20:00 | 27.00 | 27.00 | 0.00858 | 24.81 | 0.01272 | 0.016 | 0.00 |
DATACENTER_MID_ZN_6 | 86864.64 | 86864.64 | 2399.39 | 5.195 | 5.195 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 19:20:00 | 27.00 | 27.00 | 0.00858 | 24.81 | 0.01272 | 0.156 | 0.00 |
DATACENTER_TOP_ZN_6 | 8802.16 | 8802.16 | 243.14 | 0.526 | 0.526 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 19:20:00 | 27.00 | 27.00 | 0.00858 | 24.81 | 0.01272 | 0.016 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 373774.81 | 373774.81 | 476.95 | 22.352 | 22.352 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 07:00:00 | 27.00 | 27.00 | 0.00854 | 18.82 | 0.01271 | 0.338 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.000 | 1.200 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 22.74 | 0.00018 | -32.70 | 0.00018 | 1.200 | 0.00 |
CORE_BOTTOM | 8581.64 | 8581.64 | 3.44 | 0.379 | 1.078 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00800 | -32.70 | 0.00018 | 1.078 | 0.00 |
CORE_MID | 349573.08 | 349573.08 | 140.05 | 15.433 | 15.433 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00800 | -32.70 | 0.00018 | 10.778 | 0.00 |
CORE_TOP | 78449.38 | 78449.38 | 31.43 | 3.483 | 3.483 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00800 | -32.70 | 0.00018 | 1.078 | 0.00 |
PERIMETER_BOT_ZN_3 | 15682.35 | 15682.35 | 50.04 | 0.698 | 0.698 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00780 | -32.70 | 0.00018 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_2 | 10715.44 | 10715.44 | 53.05 | 0.477 | 0.477 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00781 | -32.70 | 0.00018 | 0.087 | 0.00 |
PERIMETER_BOT_ZN_1 | 17109.76 | 17109.76 | 54.59 | 0.761 | 0.761 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00782 | -32.70 | 0.00018 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_4 | 9158.08 | 9158.08 | 45.34 | 0.407 | 0.407 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00776 | -32.70 | 0.00018 | 0.087 | 0.00 |
PERIMETER_MID_ZN_3 | 220021.48 | 220021.48 | 702.02 | 9.794 | 9.794 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00768 | -32.70 | 0.00018 | 1.353 | 0.00 |
PERIMETER_MID_ZN_2 | 146021.97 | 146021.97 | 722.97 | 6.500 | 6.500 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00768 | -32.70 | 0.00018 | 0.872 | 0.00 |
PERIMETER_MID_ZN_1 | 223160.12 | 223160.12 | 712.02 | 9.934 | 9.934 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00769 | -32.70 | 0.00018 | 1.353 | 0.00 |
PERIMETER_MID_ZN_4 | 144155.25 | 144155.25 | 713.73 | 6.417 | 6.417 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00768 | -32.70 | 0.00018 | 0.872 | 0.00 |
PERIMETER_TOP_ZN_3 | 27670.15 | 27670.15 | 88.29 | 1.232 | 1.232 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00769 | -32.70 | 0.00018 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_2 | 18270.60 | 18270.60 | 90.46 | 0.814 | 0.814 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00768 | -32.70 | 0.00018 | 0.087 | 0.00 |
PERIMETER_TOP_ZN_1 | 28019.05 | 28019.05 | 89.40 | 1.248 | 1.248 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00769 | -32.70 | 0.00018 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_4 | 18276.50 | 18276.50 | 90.49 | 0.814 | 0.814 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00768 | -32.70 | 0.00018 | 0.087 | 0.00 |
DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.016 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 05:30:00 | 18.00 | 24.12 | 0.00083 | -32.70 | 0.00018 | 0.016 | 0.00 |
DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.156 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 05:40:00 | 18.00 | 22.10 | 0.00083 | -32.70 | 0.00018 | 0.156 | 0.00 |
DATACENTER_TOP_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.016 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 05:30:00 | 18.00 | 19.68 | 0.00083 | -32.70 | 0.00018 | 0.016 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.338 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 06:10:00 | 18.00 | 27.00 | 0.00850 | -32.70 | 0.00018 | 0.338 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
VAV_BOT WITH REHEAT | 10.72 | 10.72 | 3.42 | 3.42 | 10.7174 | 3.4205 | 10.7174 | 0.3191 | 0.3000 |
VAV_MID WITH REHEAT | 100.09 | 100.09 | 48.08 | 48.08 | 100.0875 | 48.0781 | 100.0875 | 0.4804 | 0.3000 |
VAV_TOP WITH REHEAT | 11.00 | 11.00 | 7.59 | 7.59 | 11.0010 | 7.5906 | 11.0010 | 0.6900 | 0.3000 |
CAV_BAS | 6.25 | 6.25 | 1.20 | 1.20 | 6.2471 | 6.2471 | 6.2471 | 1.0000 | 1.0000 |
AIRLOOP DATACENTER BASEMENT | 22.35 | 22.35 | 0.34 | 0.34 | 22.3537 | 22.3518 | 22.3537 | 0.9999 | 1.0000 |
AIRLOOP DATACENTER BOT | 0.54 | 0.54 | 0.02 | 0.02 | 0.5393 | 0.5393 | 0.5393 | 1.0000 | 1.0000 |
AIRLOOP DATACENTER MID | 5.19 | 5.19 | 0.16 | 0.16 | 5.1946 | 5.1946 | 5.1946 | 1.0000 | 1.0000 |
AIRLOOP DATACENTER TOP | 0.53 | 0.53 | 0.02 | 0.02 | 0.5264 | 0.5264 | 0.5264 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | 27788.116 | 27788.116 | 1.990577 | 0.00024310 | 586.021 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 27788.12 | 27788.12 | 1.990577 | 12.80 | 11.22 | 0.00800000 | 40.00 | 20.69 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 0.0000 | 21.00 | 0.00799981 | 49.5584 | 8581.64 | 0.00 | 27888.44 | 27888.44 |
CORE_MID VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | 537834.023 | 537834.023 | 19.511538 | 0.00470521 | 13326.872 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 537834.02 | 537834.02 | 19.511538 | 12.80 | 11.22 | 0.00800000 | 40.00 | 20.69 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 0.0000 | 21.00 | 0.00800000 | 49.5595 | 349573.08 | 0.00 | 539519.12 | 539519.12 |
CORE_TOP VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | 112058.314 | 112058.314 | 3.483261 | 0.00098034 | 2957.095 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 112058.31 | 112058.31 | 3.483261 | 12.80 | 11.22 | 0.00800000 | 40.00 | 20.69 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 0.0000 | 21.00 | 0.00800000 | 49.5595 | 78449.38 | 0.00 | 112439.07 | 112439.07 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | 22409.418 | 22409.418 | 0.697535 | 0.00019605 | 590.990 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 22409.42 | 22409.42 | 0.697535 | 12.80 | 11.22 | 0.00800000 | 40.00 | 20.69 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 0.0000 | 21.00 | 0.00779818 | 48.3275 | 15682.35 | 0.00 | 22482.90 | 22482.90 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | 15312.736 | 15312.736 | 0.476691 | 0.00013396 | 403.813 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 15312.74 | 15312.74 | 0.476691 | 12.80 | 11.22 | 0.00800000 | 40.00 | 20.69 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 0.0000 | 21.00 | 0.00780581 | 48.3742 | 10715.44 | 0.00 | 15362.80 | 15362.80 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | 24451.145 | 24451.145 | 0.761200 | 0.00021391 | 644.792 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 24451.15 | 24451.15 | 0.761200 | 12.80 | 11.22 | 0.00800000 | 40.00 | 20.69 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 0.0000 | 21.00 | 0.00781876 | 48.4533 | 17109.76 | 0.00 | 24531.01 | 24531.01 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | 13084.872 | 13084.872 | 0.407207 | 0.00011447 | 345.112 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 13084.87 | 13084.87 | 0.407207 | 12.80 | 11.22 | 0.00800000 | 40.00 | 20.69 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 0.0000 | 21.00 | 0.00775908 | 48.0886 | 9158.08 | 0.00 | 13128.01 | 13128.01 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | 314442.504 | 314442.504 | 9.793779 | 0.00275088 | 8290.214 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 314442.50 | 314442.50 | 9.793779 | 12.80 | 11.22 | 0.00800000 | 40.00 | 20.69 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 0.0000 | 21.00 | 0.00768222 | 47.6204 | 220021.48 | 0.00 | 315456.38 | 315456.38 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | 208689.562 | 208689.562 | 6.500215 | 0.00182571 | 5501.955 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 208689.56 | 208689.56 | 6.500215 | 12.80 | 11.22 | 0.00800000 | 40.00 | 20.69 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 0.0000 | 21.00 | 0.00768107 | 47.6134 | 146021.97 | 0.00 | 209361.70 | 209361.70 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | 318931.680 | 318931.680 | 9.933779 | 0.00279015 | 8408.502 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 318931.68 | 318931.68 | 9.933779 | 12.80 | 11.22 | 0.00800000 | 40.00 | 20.69 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 0.0000 | 21.00 | 0.00768663 | 47.6474 | 223160.12 | 0.00 | 319959.53 | 319959.53 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | 206019.988 | 206019.988 | 6.416997 | 0.00180235 | 5431.600 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 206019.99 | 206019.99 | 6.416997 | 12.80 | 11.22 | 0.00800000 | 40.00 | 20.69 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 0.0000 | 21.00 | 0.00767706 | 47.5890 | 144155.25 | 0.00 | 206683.72 | 206683.72 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | 39548.702 | 39548.702 | 1.232139 | 0.00034599 | 1042.564 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 39548.70 | 39435.14 | 1.232139 | 12.80 | 11.22 | 0.00800000 | 40.00 | 20.69 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 0.0000 | 21.00 | 0.00768645 | 47.6473 | 27670.15 | 0.00 | 39675.28 | 39675.28 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | 26114.190 | 26114.190 | 0.813610 | 0.00022846 | 688.401 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 26114.19 | 26114.19 | 0.813610 | 12.80 | 11.22 | 0.00800000 | 40.00 | 20.69 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 0.0000 | 21.00 | 0.00768349 | 47.6293 | 18270.60 | 0.00 | 26197.71 | 26197.71 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | 40047.710 | 40047.710 | 1.247700 | 0.00035035 | 1055.713 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 40047.71 | 40047.71 | 1.247700 | 12.80 | 11.22 | 0.00800000 | 40.00 | 20.69 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 0.0000 | 21.00 | 0.00769020 | 47.6702 | 28019.05 | 0.00 | 40175.85 | 40175.85 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | 26122.677 | 26122.677 | 0.813878 | 0.00022853 | 688.623 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 26122.68 | 26122.68 | 0.813878 | 12.80 | 11.22 | 0.00800000 | 40.00 | 20.69 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 0.0000 | 21.00 | 0.00768376 | 47.6310 | 18276.50 | 0.00 | 26206.21 | 26206.21 |
VAV_BOT WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | VAV_BOT WITH REHEAT | 223699.743 | -999.000 | 10.717412 | 0.00951670 | -999.000 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 223699.74 | 183762.35 | 10.717412 | 25.45 | 17.49 | 0.00976154 | 10.88 | 10.88 | 0.00850000 | 30.10 | 0.01272586 | 21.13 | 23.6829 | 24.00 | 0.00883760 | 45.5680 | 140880.59 | 0.00 | 230482.17 | 177582.89 |
VAV_BOT WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoopHVAC | VAV_BOT WITH REHEAT | 128608.270 | 128608.270 | 3.215224 | 0.00112512 | 1885.030 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 06:30:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 128608.27 | 128608.27 | 3.215224 | -21.70 | -21.70 | 0.00178368 | 12.80 | 11.22 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 78.9429 | 19.80 | 0.00774352 | 51.6958 | 36834.47 | 0.00 | 98584.61 | 98584.61 |
VAV_MID WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | VAV_MID WITH REHEAT | 2140844.696 | -999.000 | 100.087500 | 0.09107648 | -999.000 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 2140844.70 | 1729801.13 | 100.087500 | 25.57 | 17.63 | 0.00989040 | 10.88 | 10.88 | 0.00850000 | 30.10 | 0.01272586 | 21.13 | 25.3598 | 24.00 | 0.00891004 | 45.9369 | 1302956.32 | 0.00 | 2204829.62 | 1674496.18 |
VAV_MID WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoopHVAC | VAV_MID WITH REHEAT | 1308944.787 | 1308944.787 | 30.026250 | 0.01145122 | 18738.583 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 05:30:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 1308944.79 | 1308944.79 | 30.026250 | -24.80 | -24.80 | 0.00133050 | 12.80 | 11.22 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 84.5325 | 17.84 | 0.00758071 | 57.2042 | 405989.29 | 0.00 | 974183.13 | 974183.13 |
VAV_TOP WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | VAV_TOP WITH REHEAT | 229452.623 | -999.000 | 11.001012 | 0.00976144 | -999.000 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | 229452.62 | 188091.88 | 11.001012 | 25.41 | 17.48 | 0.00977286 | 10.88 | 10.88 | 0.00850000 | 30.10 | 0.01272586 | 21.13 | 23.0723 | 24.00 | 0.00888605 | 45.8152 | 144946.93 | 0.00 | 236413.24 | 181778.45 |
VAV_TOP WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoopHVAC | VAV_TOP WITH REHEAT | 129416.376 | 129416.376 | 3.300304 | 0.00113219 | 1907.211 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 02:20:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 129416.38 | 129416.38 | 3.300304 | -21.02 | -21.02 | 0.00187875 | 12.80 | 11.22 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 76.9078 | 15.87 | 0.00759523 | 64.9634 | 42071.77 | 0.00 | 99865.83 | 99865.83 |
CAV_BAS COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | CAV_BAS | 125039.636 | -999.000 | 6.247056 | 0.00531948 | -999.000 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:00:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 125039.64 | 102207.91 | 6.247056 | 25.18 | 17.41 | 0.00977299 | 11.36 | 11.13 | 0.00850000 | 29.48 | 0.01272477 | 20.95 | 19.2116 | 24.00 | 0.00896124 | 46.1963 | 73388.37 | 0.00 | 128898.46 | 99575.71 |
CAV_BAS HEATING COIL | Coil:Heating:Water | AirLoopHVAC | CAV_BAS | 335252.239 | 335252.239 | 6.247056 | 0.00293293 | 7091.328 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 335252.24 | 335252.24 | 6.247056 | -6.28 | -10.33 | 0.00018338 | 40.00 | 20.69 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 19.2116 | 22.85 | 0.00018338 | 1.0276 | 0.00 | 0.00 | 263780.99 | 263780.99 |
AIRLOOP DATACENTER BASEMENT COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | 437947.868 | 302632.257 | 22.353674 | 0.01072531 | -999.000 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 404768.44 | 398770.92 | -999.0 | 28.50 | 17.57 | 0.00860544 | 12.80 | 11.72 | 0.00850000 | 30.10 | 0.01272586 | 21.13 | -999.0000 | 27.00 | 0.00854203 | 36.8760 | 373369.40 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BOT COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER BOT | 10376.829 | 7230.010 | 0.539345 | 0.00025413 | -999.000 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 19:20:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 19:20:00 | 9560.48 | 9286.60 | -999.0 | 27.92 | 17.46 | 0.00870005 | 12.80 | 11.72 | 0.00850000 | 24.81 | 0.01271660 | 19.55 | -999.0000 | 27.00 | 0.00858015 | 37.0358 | 9019.03 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER MID COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER MID | 100031.983 | 69661.319 | 5.194593 | 0.00244978 | -999.000 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 19:20:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 19:20:00 | 92175.69 | 89438.43 | -999.0 | 27.92 | 17.46 | 0.00870757 | 12.80 | 11.72 | 0.00850000 | 24.81 | 0.01271660 | 19.55 | -999.0000 | 27.00 | 0.00858318 | 37.0487 | 86864.64 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER TOP COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER TOP | 10133.261 | 7057.957 | 0.526377 | 0.00024816 | -999.000 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 19:20:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 19:20:00 | 9336.95 | 9063.09 | -999.0 | 27.92 | 17.46 | 0.00870495 | 12.80 | 11.72 | 0.00850000 | 24.81 | 0.01271660 | 19.55 | -999.0000 | 27.00 | 0.00858216 | 37.0444 | 8802.16 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BASEMENT HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | 437947.868 | 437947.868 | 22.353674 | 0.01072531 | -999.000 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 437947.87 | 437947.87 | 22.353674 | -32.70 | -32.70 | 0.00018338 | 40.00 | 20.69 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 1.5138 | 27.00 | 0.00850000 | 36.6913 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BOT HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER BOT | 10376.829 | 10376.829 | 0.539345 | 0.00025413 | -999.000 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 10376.83 | 10376.83 | 0.539345 | -32.70 | -32.70 | 0.00018338 | 40.00 | 20.69 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 2.8984 | 24.87 | 0.00082584 | 4.0926 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER MID HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER MID | 100031.983 | 100031.983 | 5.194593 | 0.00244978 | -999.000 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 100031.98 | 100031.98 | 5.194593 | -32.70 | -32.70 | 0.00018338 | 40.00 | 20.69 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 3.0093 | 23.37 | 0.00082586 | 4.4795 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER TOP HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER TOP | 10133.261 | 10133.261 | 0.526377 | 0.00024816 | -999.000 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 10133.26 | 10133.26 | 0.526377 | -32.70 | -32.70 | 0.00018338 | 40.00 | 20.69 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 2.9698 | 21.93 | 0.00082519 | 4.8836 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | 28525.808 | 28525.808 | -999.0 | -999.0 | -999.000 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 28525.81 | 28525.81 | 22.353674 | -0.50 | -0.50 | 0.00837410 | 40.00 | 20.69 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 1.5138 | 27.00 | 0.00850000 | 36.6913 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BOT_SUPPHEATCOIL | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER BOT | 1317.774 | 1317.774 | -999.0 | -999.0 | -999.000 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 1317.77 | 1317.77 | 0.539345 | -0.95 | -5.59 | 0.00080722 | 40.00 | 20.69 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 2.8984 | 24.87 | 0.00082584 | 4.0926 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER MID_SUPPHEATCOIL | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER MID | 13177.742 | 13177.742 | -999.0 | -999.0 | -999.000 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 13177.74 | 13177.74 | 5.194593 | -0.98 | -5.61 | 0.00080653 | 40.00 | 20.69 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 3.0093 | 23.37 | 0.00082586 | 4.4795 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER TOP_SUPPHEATCOIL | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER TOP | 1317.774 | 1317.774 | -999.0 | -999.0 | -999.000 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 1317.77 | 1317.77 | 0.526377 | -0.97 | -5.60 | 0.00080613 | 40.00 | 20.69 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 2.9698 | 21.93 | 0.00082519 | 4.8836 | 0.00 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 08:43:41
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
CORE_BOTTOM VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | CORE_BOTTOM | N/A | N/A | N/A | Yes | Yes | Yes | No | 27788.116 | 27788.116 | 1.990577 | 0.00024310 | 586.021 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 33.54750678 | 54.44 | 82.22 | 27.78 | 3912259.76 | 0.7103 | 0.724578 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 27788.12 | 27788.12 | 1.0000 | 2.29697686 | 1.990577 | 12.80 | 11.22 | 0.00800000 | 33059.8 | 40.00 | 20.69 | 0.00800000 | 60796.0 | 0.24307776 | 60.00 | 32.22 | 27.78 | 0.000 | 27788.12 | -32.70 | 0.00018338 | -32.70 | 0.00000000 | 0.0000 | 20.79 | 0.00799981 | 21.00 | 0.00799981 | 49.5584 | 8581.64 | 0.00 | 27888.44 | 27888.44 | 2.29697686 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 24.71 | 16.21 | 0.00800000 | 45201.2 | |
CORE_MID VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | CORE_MID | N/A | N/A | N/A | Yes | Yes | Yes | No | 537834.023 | 537834.023 | 19.511538 | 0.00470521 | 13326.872 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 33.54750678 | 54.44 | 82.22 | 27.78 | 3912259.76 | 13.7474 | 14.024073 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 537834.02 | 537834.02 | 1.0000 | 22.51484824 | 19.511538 | 12.80 | 11.22 | 0.00800000 | 33059.8 | 40.00 | 20.69 | 0.00800000 | 60796.0 | 4.70472668 | 60.00 | 32.22 | 27.78 | 0.000 | 537834.02 | -32.70 | 0.00018338 | -32.70 | 0.00000000 | 0.0000 | 20.87 | 0.00800000 | 21.00 | 0.00800000 | 49.5595 | 349573.08 | 0.00 | 539519.12 | 539519.12 | 22.51484824 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 36.30 | 20.06 | 0.00800000 | 57022.6 | |
CORE_TOP VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | CORE_TOP | N/A | N/A | N/A | Yes | Yes | Yes | No | 112058.314 | 112058.314 | 3.483261 | 0.00098034 | 2957.095 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 33.54750678 | 54.44 | 82.22 | 27.78 | 3912259.76 | 2.8643 | 2.921931 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 112058.31 | 112058.31 | 1.0000 | 4.01942186 | 3.483261 | 12.80 | 11.22 | 0.00800000 | 33059.8 | 40.00 | 20.69 | 0.00800000 | 60796.0 | 0.98023501 | 60.00 | 32.22 | 27.78 | 0.000 | 112058.31 | -32.70 | 0.00018338 | -32.70 | 0.00000000 | 0.0000 | 20.91 | 0.00800000 | 21.00 | 0.00800000 | 49.5595 | 78449.38 | 0.00 | 112439.07 | 112439.07 | 4.01942186 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.23 | 21.25 | 0.00800000 | 61033.8 | |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | PERIMETER_BOT_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 22409.418 | 22409.418 | 0.697535 | 0.00019605 | 590.990 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 33.54750678 | 54.44 | 82.22 | 27.78 | 3912259.76 | 0.5728 | 0.584328 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 22409.42 | 22409.42 | 1.0000 | 0.80490285 | 0.697535 | 12.80 | 11.22 | 0.00800000 | 33059.8 | 40.00 | 20.69 | 0.00800000 | 60796.0 | 0.19602737 | 60.00 | 32.22 | 27.78 | 0.000 | 22409.42 | -32.70 | 0.00018338 | -32.70 | 0.00000000 | 0.0000 | 20.95 | 0.00779818 | 21.00 | 0.00779818 | 48.3275 | 15682.35 | 0.00 | 22482.90 | 22482.90 | 0.80490285 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.19 | 21.24 | 0.00800000 | 60992.3 | |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | PERIMETER_BOT_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 15312.736 | 15312.736 | 0.476691 | 0.00013396 | 403.813 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 33.54750678 | 54.44 | 82.22 | 27.78 | 3912259.76 | 0.3914 | 0.399281 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 15312.74 | 15312.74 | 1.0000 | 0.55006511 | 0.476691 | 12.80 | 11.22 | 0.00800000 | 33059.8 | 40.00 | 20.69 | 0.00800000 | 60796.0 | 0.13394883 | 60.00 | 32.22 | 27.78 | 0.000 | 15312.74 | -32.70 | 0.00018338 | -32.70 | 0.00000000 | 0.0000 | 20.95 | 0.00780581 | 21.00 | 0.00780581 | 48.3742 | 10715.44 | 0.00 | 15362.80 | 15362.80 | 0.55006511 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.19 | 21.24 | 0.00800000 | 60988.9 | |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | PERIMETER_BOT_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 24451.145 | 24451.145 | 0.761200 | 0.00021391 | 644.792 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 33.54750678 | 54.44 | 82.22 | 27.78 | 3912259.76 | 0.6250 | 0.637566 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 24451.15 | 24451.15 | 1.0000 | 0.87836809 | 0.761200 | 12.80 | 11.22 | 0.00800000 | 33059.8 | 40.00 | 20.69 | 0.00800000 | 60796.0 | 0.21388746 | 60.00 | 32.22 | 27.78 | 0.000 | 24451.15 | -32.70 | 0.00018338 | -32.70 | 0.00000000 | 0.0000 | 20.95 | 0.00781876 | 21.00 | 0.00781876 | 48.4533 | 17109.76 | 0.00 | 24531.01 | 24531.01 | 0.87836809 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.19 | 21.24 | 0.00800000 | 60987.8 | |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | PERIMETER_BOT_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 13084.872 | 13084.872 | 0.407207 | 0.00011447 | 345.112 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 33.54750678 | 54.44 | 82.22 | 27.78 | 3912259.76 | 0.3345 | 0.341189 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 13084.87 | 13084.87 | 1.0000 | 0.46988635 | 0.407207 | 12.80 | 11.22 | 0.00800000 | 33059.8 | 40.00 | 20.69 | 0.00800000 | 60796.0 | 0.11446049 | 60.00 | 32.22 | 27.78 | 0.000 | 13084.87 | -32.70 | 0.00018338 | -32.70 | 0.00000000 | 0.0000 | 20.95 | 0.00775908 | 21.00 | 0.00775908 | 48.0886 | 9158.08 | 0.00 | 13128.01 | 13128.01 | 0.46988635 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.20 | 21.24 | 0.00800000 | 60998.5 | |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | PERIMETER_MID_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 314442.504 | 314442.504 | 9.793779 | 0.00275088 | 8290.214 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 33.54750678 | 54.44 | 82.22 | 27.78 | 3912259.76 | 8.0374 | 8.199118 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 314442.50 | 314442.50 | 1.0000 | 11.30128536 | 9.793779 | 12.80 | 11.22 | 0.00800000 | 33059.8 | 40.00 | 20.69 | 0.00800000 | 60796.0 | 2.75059958 | 60.00 | 32.22 | 27.78 | 0.000 | 314442.50 | -32.70 | 0.00018338 | -32.70 | 0.00000000 | 0.0000 | 20.95 | 0.00768222 | 21.00 | 0.00768222 | 47.6204 | 220021.48 | 0.00 | 315456.38 | 315456.38 | 11.30128536 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.17 | 21.23 | 0.00800000 | 60973.1 | |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | PERIMETER_MID_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 208689.562 | 208689.562 | 6.500215 | 0.00182571 | 5501.955 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 33.54750678 | 54.44 | 82.22 | 27.78 | 3912259.76 | 5.3342 | 5.441600 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 208689.56 | 208689.56 | 1.0000 | 7.50075993 | 6.500215 | 12.80 | 11.22 | 0.00800000 | 33059.8 | 40.00 | 20.69 | 0.00800000 | 60796.0 | 1.82552109 | 60.00 | 32.22 | 27.78 | 0.000 | 208689.56 | -32.70 | 0.00018338 | -32.70 | 0.00000000 | 0.0000 | 20.95 | 0.00768107 | 21.00 | 0.00768107 | 47.6134 | 146021.97 | 0.00 | 209361.70 | 209361.70 | 7.50075993 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.17 | 21.23 | 0.00800000 | 60971.9 | |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | PERIMETER_MID_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 318931.680 | 318931.680 | 9.933779 | 0.00279015 | 8408.502 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 33.54750678 | 54.44 | 82.22 | 27.78 | 3912259.76 | 8.1521 | 8.316173 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 318931.68 | 318931.68 | 1.0000 | 11.46283397 | 9.933779 | 12.80 | 11.22 | 0.00800000 | 33059.8 | 40.00 | 20.69 | 0.00800000 | 60796.0 | 2.78986884 | 60.00 | 32.22 | 27.78 | 0.000 | 318931.68 | -32.70 | 0.00018338 | -32.70 | 0.00000000 | 0.0000 | 20.95 | 0.00768663 | 21.00 | 0.00768663 | 47.6474 | 223160.12 | 0.00 | 319959.53 | 319959.53 | 11.46283397 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.17 | 21.23 | 0.00800000 | 60972.6 | |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | PERIMETER_MID_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 206019.988 | 206019.988 | 6.416997 | 0.00180235 | 5431.600 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 33.54750678 | 54.44 | 82.22 | 27.78 | 3912259.76 | 5.2660 | 5.371990 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 206019.99 | 206019.99 | 1.0000 | 7.40473178 | 6.416997 | 12.80 | 11.22 | 0.00800000 | 33059.8 | 40.00 | 20.69 | 0.00800000 | 60796.0 | 1.80216887 | 60.00 | 32.22 | 27.78 | 0.000 | 206019.99 | -32.70 | 0.00018338 | -32.70 | 0.00000000 | 0.0000 | 20.95 | 0.00767706 | 21.00 | 0.00767706 | 47.5890 | 144155.25 | 0.00 | 206683.72 | 206683.72 | 7.40473178 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.17 | 21.23 | 0.00800000 | 60972.2 | |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | PERIMETER_TOP_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 39548.702 | 39548.702 | 1.232139 | 0.00034599 | 1042.564 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 33.54750678 | 54.44 | 82.22 | 27.78 | 3912259.76 | 1.0109 | 1.031236 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 39548.70 | 39435.14 | 1.0000 | 1.42179532 | 1.232139 | 12.80 | 11.22 | 0.00800000 | 33059.8 | 40.00 | 20.69 | 0.00800000 | 60796.0 | 0.34595400 | 60.00 | 32.22 | 27.78 | 0.000 | 39548.70 | -32.70 | 0.00018338 | -32.70 | 0.00000000 | 0.0000 | 20.95 | 0.00768645 | 21.00 | 0.00768645 | 47.6473 | 27670.15 | 0.00 | 39675.28 | 39675.28 | 1.42179532 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.17 | 21.23 | 0.00800000 | 60964.9 | |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | PERIMETER_TOP_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 26114.190 | 26114.190 | 0.813610 | 0.00022846 | 688.401 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 33.54750678 | 54.44 | 82.22 | 27.78 | 3912259.76 | 0.6675 | 0.680930 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 26114.19 | 26114.19 | 1.0000 | 0.93884436 | 0.813610 | 12.80 | 11.22 | 0.00800000 | 33059.8 | 40.00 | 20.69 | 0.00800000 | 60796.0 | 0.22843502 | 60.00 | 32.22 | 27.78 | 0.000 | 26114.19 | -32.70 | 0.00018338 | -32.70 | 0.00000000 | 0.0000 | 20.95 | 0.00768349 | 21.00 | 0.00768349 | 47.6293 | 18270.60 | 0.00 | 26197.71 | 26197.71 | 0.93884436 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.16 | 21.23 | 0.00800000 | 60964.0 | |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | PERIMETER_TOP_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 40047.710 | 40047.710 | 1.247700 | 0.00035035 | 1055.713 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 33.54750678 | 54.44 | 82.22 | 27.78 | 3912259.76 | 1.0236 | 1.044248 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 40047.71 | 40047.71 | 1.0000 | 1.43975229 | 1.247700 | 12.80 | 11.22 | 0.00800000 | 33059.8 | 40.00 | 20.69 | 0.00800000 | 60796.0 | 0.35031910 | 60.00 | 32.22 | 27.78 | 0.000 | 40047.71 | -32.70 | 0.00018338 | -32.70 | 0.00000000 | 0.0000 | 20.95 | 0.00769020 | 21.00 | 0.00769020 | 47.6702 | 28019.05 | 0.00 | 40175.85 | 40175.85 | 1.43975229 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.17 | 21.23 | 0.00800000 | 60964.5 | |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | PERIMETER_TOP_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 26122.677 | 26122.677 | 0.813878 | 0.00022853 | 688.623 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 33.54750678 | 54.44 | 82.22 | 27.78 | 3912259.76 | 0.6677 | 0.681151 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 26122.68 | 26122.68 | 1.0000 | 0.93915437 | 0.813878 | 12.80 | 11.22 | 0.00800000 | 33059.8 | 40.00 | 20.69 | 0.00800000 | 60796.0 | 0.22850926 | 60.00 | 32.22 | 27.78 | 0.000 | 26122.68 | -32.70 | 0.00018338 | -32.70 | 0.00000000 | 0.0000 | 20.95 | 0.00768376 | 21.00 | 0.00768376 | 47.6310 | 18276.50 | 0.00 | 26206.21 | 26206.21 | 0.93915437 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.16 | 21.23 | 0.00800000 | 60963.9 | |
VAV_BOT WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV_BOT WITH REHEAT | CORE_BOTTOM; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 223699.743 | -999.000 | 10.717412 | 0.00951670 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1022.9862 | 1004.8586 | 1.1539 | VAV_BOT WITH REHEAT FAN | Fan:VariableVolume | 10.717412 | 12.36708776 | 4197.9300 | 999.8980 | 115.66230675 | 12.27 | 6.67 | 5.60 | 2719036.70 | 8.2272 | 8.227169 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | Sensible | 223699.74 | 183762.35 | 1.0000 | 12.36708776 | 10.717412 | 25.45 | 17.49 | 0.00976154 | 50446.4 | 10.88 | 10.88 | 0.00850000 | 32358.1 | 9.51573340 | 6.67 | 12.27 | 5.60 | 24345.600 | 199354.14 | 30.10 | 0.01272586 | 21.13 | 2.53819000 | 23.6829 | 24.00 | 0.00883760 | 24.00 | 0.00883760 | 45.5680 | 140880.59 | 0.00 | 230482.17 | 177582.89 | 12.36708776 | 25.45 | 17.94 | 0.00976154 | 50446.4 | 11.41 | 11.07 | 0.00806560 | 31809.7 | |
VAV_BOT WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV_BOT WITH REHEAT | CORE_BOTTOM; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 128608.270 | 128608.270 | 3.215224 | 0.00112512 | 1885.030 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | VAV_BOT WITH REHEAT FAN | Fan:VariableVolume | 10.717412 | 12.36708776 | 4197.9300 | 999.8980 | 33.54750678 | 54.44 | 82.22 | 27.78 | 3912259.76 | 3.2873 | 3.353473 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 06:30:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 128608.27 | 128608.27 | 1.0000 | 3.71012633 | 3.215224 | -21.70 | -21.70 | 0.00178368 | -17412.6 | 12.80 | 11.22 | 0.00800000 | 33059.8 | 1.12500648 | 60.00 | 32.22 | 27.78 | 0.000 | 128608.27 | -32.70 | 0.00018338 | -32.70 | 2.53819000 | 78.9429 | 19.56 | 0.00778319 | 19.80 | 0.00774352 | 51.6958 | 36834.47 | 0.00 | 98584.61 | 98584.61 | 3.71012633 | 2.80 | -1.52 | 0.00178368 | 7283.7 | 29.16 | 12.06 | 0.00178368 | 33855.5 | |
VAV_MID WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV_MID WITH REHEAT | CORE_MID; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 2140844.696 | -999.000 | 100.087500 | 0.09107648 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1023.2258 | 1004.8586 | 1.1539 | VAV_MID WITH REHEAT FAN | Fan:VariableVolume | 100.087500 | 115.49345412 | 4197.9300 | 999.8980 | 115.66230675 | 12.27 | 6.67 | 5.60 | 2719036.70 | 78.7354 | 78.735410 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | Sensible | 2140844.70 | 1729801.13 | 1.0000 | 115.49345412 | 100.087500 | 25.57 | 17.63 | 0.00989040 | 50895.1 | 10.88 | 10.88 | 0.00850000 | 32358.6 | 91.06719161 | 6.67 | 12.27 | 5.60 | 227358.088 | 1913486.61 | 30.10 | 0.01272586 | 21.13 | 25.38195000 | 25.3598 | 24.00 | 0.00891004 | 24.00 | 0.00891004 | 45.9369 | 1302956.32 | 0.00 | 2204829.62 | 1674496.18 | 115.49345412 | 25.57 | 18.09 | 0.00989040 | 50895.1 | 11.40 | 11.07 | 0.00806976 | 31804.6 | |
VAV_MID WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV_MID WITH REHEAT | CORE_MID; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 1308944.787 | 1308944.787 | 30.026250 | 0.01145122 | 18738.583 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | VAV_MID WITH REHEAT FAN | Fan:VariableVolume | 100.087500 | 115.49345412 | 4197.9300 | 999.8980 | 33.54750678 | 54.44 | 82.22 | 27.78 | 3912259.76 | 33.4575 | 34.130858 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 05:30:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 1308944.79 | 1308944.79 | 1.0000 | 34.64803624 | 30.026250 | -24.80 | -24.80 | 0.00133050 | -21649.5 | 12.80 | 11.22 | 0.00800000 | 33059.8 | 11.45005187 | 60.00 | 32.22 | 27.78 | 0.000 | 1308944.79 | -32.70 | 0.00018338 | -32.70 | 25.38195000 | 84.5325 | 18.40 | 0.00759978 | 17.84 | 0.00758071 | 57.2042 | 405989.29 | 0.00 | 974183.13 | 974183.13 | 34.64803624 | 2.80 | -2.25 | 0.00133050 | 6148.0 | 30.71 | 12.23 | 0.00133050 | 34264.5 | |
VAV_TOP WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV_TOP WITH REHEAT | CORE_TOP; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 229452.623 | -999.000 | 11.001012 | 0.00976144 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1023.0073 | 1004.8586 | 1.1539 | VAV_TOP WITH REHEAT FAN | Fan:VariableVolume | 11.001012 | 12.69434089 | 4197.9300 | 999.8980 | 115.66230675 | 12.27 | 6.67 | 5.60 | 2719036.70 | 8.4387 | 8.438747 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | Sensible | 229452.62 | 188091.88 | 1.0000 | 12.69434089 | 11.001012 | 25.41 | 17.48 | 0.00977286 | 50433.4 | 10.88 | 10.88 | 0.00850000 | 32358.2 | 9.76044922 | 6.67 | 12.27 | 5.60 | 24989.824 | 204462.80 | 30.10 | 0.01272586 | 21.13 | 2.53819000 | 23.0723 | 24.00 | 0.00888605 | 24.00 | 0.00888605 | 45.8152 | 144946.93 | 0.00 | 236413.24 | 181778.45 | 12.69434089 | 25.41 | 17.94 | 0.00977286 | 50433.4 | 11.41 | 11.07 | 0.00806643 | 31809.8 | |
VAV_TOP WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV_TOP WITH REHEAT | CORE_TOP; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 129416.376 | 129416.376 | 3.300304 | 0.00113219 | 1907.211 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | VAV_TOP WITH REHEAT FAN | Fan:VariableVolume | 11.001012 | 12.69434089 | 4197.9300 | 999.8980 | 33.54750678 | 54.44 | 82.22 | 27.78 | 3912259.76 | 3.3080 | 3.374544 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 02:20:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 129416.38 | 129416.38 | 1.0000 | 3.80830227 | 3.300304 | -21.02 | -21.02 | 0.00187875 | -16494.9 | 12.80 | 11.22 | 0.00800000 | 33059.8 | 1.13207542 | 60.00 | 32.22 | 27.78 | 0.000 | 129416.38 | -32.70 | 0.00018338 | -32.70 | 2.53819000 | 76.9078 | 17.89 | 0.00752515 | 15.87 | 0.00759523 | 64.9634 | 42071.77 | 0.00 | 99865.83 | 99865.83 | 3.80830227 | 2.80 | -1.37 | 0.00187875 | 7522.0 | 28.81 | 12.01 | 0.00187875 | 33745.2 | |
CAV_BAS COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | CAV_BAS | BASEMENT | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 125039.636 | -999.000 | 6.247056 | 0.00531948 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1023.0075 | 1004.8586 | 1.1539 | CAV_BAS FAN | Fan:ConstantVolume | 6.247056 | 7.20863370 | 4197.9300 | 999.8980 | 115.66230675 | 12.27 | 6.67 | 5.60 | 2719036.70 | 4.5987 | 4.598674 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:00:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:00:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | Sensible | 125039.64 | 102207.91 | 1.0000 | 7.20863370 | 6.247056 | 25.18 | 17.41 | 0.00977299 | 50201.9 | 11.36 | 11.13 | 0.00850000 | 32856.1 | 5.31893252 | 6.67 | 12.27 | 5.60 | 10592.848 | 114446.79 | 29.48 | 0.01272477 | 20.95 | 1.20015641 | 19.2116 | 24.00 | 0.00896124 | 24.00 | 0.00896124 | 46.1963 | 73388.37 | 0.00 | 128898.46 | 99575.71 | 7.20863370 | 25.18 | 17.86 | 0.00977299 | 50201.9 | 11.68 | 11.29 | 0.00816051 | 32320.8 | |
CAV_BAS HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | CAV_BAS | BASEMENT | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 335252.239 | 335252.239 | 6.247056 | 0.00293293 | 7091.328 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | CAV_BAS FAN | Fan:ConstantVolume | 6.247056 | 7.20863370 | 4197.9300 | 999.8980 | 33.54750678 | 54.44 | 82.22 | 27.78 | 3912259.76 | 8.5693 | 8.741734 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 335252.24 | 335252.24 | 1.0000 | 7.20863370 | 6.247056 | -6.28 | -10.33 | 0.00018338 | -5856.1 | 40.00 | 20.69 | 0.00800000 | 60796.0 | 2.93263365 | 60.00 | 32.22 | 27.78 | 0.000 | 335252.24 | -32.70 | 0.00018338 | -32.70 | 1.20015641 | 19.2116 | 0.00 | 0.00018338 | 22.85 | 0.00018338 | 1.0276 | 0.00 | 0.00 | 263780.99 | 263780.99 | 7.20863370 | 12.80 | 2.24 | 0.00018338 | 13324.9 | 49.20 | 18.01 | 0.00018338 | 49917.3 | |
AIRLOOP DATACENTER BASEMENT COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | DATACENTER_BASEMENT_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 437947.868 | 302632.257 | 22.353674 | 0.01072531 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1020.8371 | 1004.8586 | 1.1539 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | Sensible | 404768.44 | 398770.92 | 0.9242 | -999.0 | -999.0 | 28.50 | 17.57 | 0.00860544 | 50613.4 | 12.80 | 11.72 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 404768.44 | 30.10 | 0.01272586 | 21.13 | 0.33839277 | -999.0000 | 27.00 | 0.00854203 | 27.00 | 0.00854203 | 36.8760 | 373369.40 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BOT COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BOT | DATACENTER_BOT_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 10376.829 | 7230.010 | 0.539345 | 0.00025413 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1021.0129 | 1004.8586 | 1.1539 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 19:20:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 19:20:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 19:20:00 | Sensible | 9560.48 | 9286.60 | 0.9213 | -999.0 | -999.0 | 27.92 | 17.46 | 0.00870005 | 50266.9 | 12.80 | 11.72 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9560.48 | 24.81 | 0.01271660 | 19.55 | 0.01563234 | -999.0000 | 27.00 | 0.00858015 | 27.00 | 0.00858015 | 37.0358 | 9019.03 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER MID COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER MID | DATACENTER_MID_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 100031.983 | 69661.319 | 5.194593 | 0.00244978 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1021.0269 | 1004.8586 | 1.1539 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 19:20:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 19:20:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 19:20:00 | Sensible | 92175.69 | 89438.43 | 0.9215 | -999.0 | -999.0 | 27.92 | 17.46 | 0.00870757 | 50283.5 | 12.80 | 11.72 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 92175.69 | 24.81 | 0.01271660 | 19.55 | 0.15632344 | -999.0000 | 27.00 | 0.00858318 | 27.00 | 0.00858318 | 37.0487 | 86864.64 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER TOP COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER TOP | DATACENTER_TOP_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 10133.261 | 7057.957 | 0.526377 | 0.00024816 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1021.0221 | 1004.8586 | 1.1539 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 19:20:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 19:20:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 19:20:00 | Sensible | 9336.95 | 9063.09 | 0.9214 | -999.0 | -999.0 | 27.92 | 17.46 | 0.00870495 | 50277.8 | 12.80 | 11.72 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9336.95 | 24.81 | 0.01271660 | 19.55 | 0.01563234 | -999.0000 | 27.00 | 0.00858216 | 27.00 | 0.00858216 | 37.0444 | 8802.16 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BASEMENT HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | DATACENTER_BASEMENT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 437947.868 | 437947.868 | 22.353674 | 0.01072531 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 1.1539 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 437947.87 | 437947.87 | 1.0000 | 25.79445953 | 22.353674 | -32.70 | -32.70 | 0.00018338 | -32410.8 | 40.00 | 20.69 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 437947.87 | -32.70 | 0.00018338 | -32.70 | 0.33839277 | 1.5138 | 0.00 | 0.00850000 | 27.00 | 0.00850000 | 36.6913 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BOT HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BOT | DATACENTER_BOT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 10376.829 | 10376.829 | 0.539345 | 0.00025413 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 1.1539 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 10376.83 | 10376.83 | 1.0000 | 0.62236374 | 0.539345 | -32.70 | -32.70 | 0.00018338 | -32410.8 | 40.00 | 20.69 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 10376.83 | -32.70 | 0.00018338 | -32.70 | 0.01563234 | 2.8984 | 0.00 | 0.00082584 | 24.87 | 0.00082584 | 4.0926 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER MID HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER MID | DATACENTER_MID_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 100031.983 | 100031.983 | 5.194593 | 0.00244978 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 1.1539 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 100031.98 | 100031.98 | 1.0000 | 5.99416997 | 5.194593 | -32.70 | -32.70 | 0.00018338 | -32410.8 | 40.00 | 20.69 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 100031.98 | -32.70 | 0.00018338 | -32.70 | 0.15632344 | 3.0093 | 0.00 | 0.00082586 | 23.37 | 0.00082586 | 4.4795 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER TOP HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER TOP | DATACENTER_TOP_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 10133.261 | 10133.261 | 0.526377 | 0.00024816 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 1.1539 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 10133.26 | 10133.26 | 1.0000 | 0.60739948 | 0.526377 | -32.70 | -32.70 | 0.00018338 | -32410.8 | 40.00 | 20.69 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 10133.26 | -32.70 | 0.00018338 | -32.70 | 0.01563234 | 2.9698 | 0.00 | 0.00082519 | 21.93 | 0.00082519 | 4.8836 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | DATACENTER_BASEMENT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 28525.808 | 28525.808 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | AIRLOOP DATACENTER BASEMENT SUPPLY FAN | Fan:OnOff | 22.353674 | 25.79445953 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 28525.81 | 28525.81 | 1.0000 | 25.79445953 | 22.353674 | -0.50 | -0.50 | 0.00837410 | 20438.0 | 40.00 | 20.69 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 28525.81 | -32.70 | 0.00018338 | -32.70 | 0.33839277 | 1.5138 | 0.00 | 0.00850000 | 27.00 | 0.00850000 | 36.6913 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BOT_SUPPHEATCOIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BOT | DATACENTER_BOT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 1317.774 | 1317.774 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | AIRLOOP DATACENTER BOT SUPPLY FAN | Fan:OnOff | 0.539345 | 0.62236374 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 1317.77 | 1317.77 | 1.0000 | 0.62236374 | 0.539345 | -0.95 | -5.59 | 0.00080722 | 1065.0 | 40.00 | 20.69 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 1317.77 | -32.70 | 0.00018338 | -32.70 | 0.01563234 | 2.8984 | 0.00 | 0.00082584 | 24.87 | 0.00082584 | 4.0926 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER MID_SUPPHEATCOIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER MID | DATACENTER_MID_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 13177.742 | 13177.742 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | AIRLOOP DATACENTER MID SUPPLY FAN | Fan:OnOff | 5.194593 | 5.99416997 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 13177.74 | 13177.74 | 1.0000 | 5.99416997 | 5.194593 | -0.98 | -5.61 | 0.00080653 | 1026.8 | 40.00 | 20.69 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 13177.74 | -32.70 | 0.00018338 | -32.70 | 0.15632344 | 3.0093 | 0.00 | 0.00082586 | 23.37 | 0.00082586 | 4.4795 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER TOP_SUPPHEATCOIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER TOP | DATACENTER_TOP_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 1317.774 | 1317.774 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | AIRLOOP DATACENTER TOP SUPPLY FAN | Fan:OnOff | 0.526377 | 0.60739948 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 1317.77 | 1317.77 | 1.0000 | 0.60739948 | 0.526377 | -0.97 | -5.60 | 0.00080613 | 1038.8 | 40.00 | 20.69 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 1317.77 | -32.70 | 0.00018338 | -32.70 | 0.01563234 | 2.9698 | 0.00 | 0.00082519 | 21.93 | 0.00082519 | 4.8836 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 08:43:41
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
VAV_BOT WITH REHEAT_OA_CONTROLLER | DifferentialDryBulb | 2.54 | 10.72 | - | |||
VAV_MID WITH REHEAT_OA_CONTROLLER | DifferentialDryBulb | 25.38 | 100.09 | - | |||
VAV_TOP WITH REHEAT_OA_CONTROLLER | DifferentialDryBulb | 2.54 | 11.00 | - | |||
CAV_BAS_OA_CONTROLLER | DifferentialDryBulb | 1.20 | 6.25 | - | |||
AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER | DifferentialDryBulb | 0.34 | 22.35 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
CORE_BOTTOM | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_MID | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_TOP | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
BASEMENT | 2183.00 | 2294.17 | 387.00 |
CORE_BOTTOM | 2021.00 | 2159.67 | 22.17 |
CORE_MID | 2054.50 | 3517.17 | 553.00 |
CORE_TOP | 2827.67 | 3978.33 | 1506.50 |
PERIMETER_BOT_ZN_3 | 3070.17 | 3694.50 | 1436.50 |
PERIMETER_BOT_ZN_2 | 3210.50 | 3734.83 | 1533.50 |
PERIMETER_BOT_ZN_1 | 3158.00 | 3320.50 | 1261.83 |
PERIMETER_BOT_ZN_4 | 2988.33 | 3198.83 | 984.17 |
PERIMETER_MID_ZN_3 | 3859.00 | 4213.67 | 2590.33 |
PERIMETER_MID_ZN_2 | 3272.50 | 3539.00 | 2116.17 |
PERIMETER_MID_ZN_1 | 3513.33 | 3727.17 | 1868.83 |
PERIMETER_MID_ZN_4 | 3716.50 | 4178.17 | 2309.50 |
PERIMETER_TOP_ZN_3 | 4050.83 | 4464.83 | 2924.67 |
PERIMETER_TOP_ZN_2 | 4031.17 | 4216.33 | 2683.83 |
PERIMETER_TOP_ZN_1 | 3710.83 | 3975.00 | 2237.83 |
PERIMETER_TOP_ZN_4 | 3880.33 | 4383.00 | 2621.83 |
DATACENTER_BOT_ZN_6 | 5654.83 | 1021.17 | 1007.33 |
DATACENTER_MID_ZN_6 | 4556.50 | 684.00 | 330.33 |
DATACENTER_TOP_ZN_6 | 4121.17 | 1083.50 | 465.33 |
DATACENTER_BASEMENT_ZN_6 | 5943.00 | 5525.83 | 5525.83 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
Facility | 5943.00 | 5943.00 | 5941.83 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
BASEMENT | 0.00 | 35.33 | 0.00 | 2.17 |
CORE_BOTTOM | 0.00 | 3.67 | 0.00 | 2.67 |
CORE_MID | 3.17 | 1.00 | 1.00 | 1.00 |
CORE_TOP | 24.67 | 0.83 | 3.83 | 0.83 |
PERIMETER_BOT_ZN_3 | 23.00 | 5.83 | 4.17 | 5.83 |
PERIMETER_BOT_ZN_2 | 22.17 | 21.83 | 1.00 | 21.83 |
PERIMETER_BOT_ZN_1 | 22.50 | 40.17 | 1.17 | 40.00 |
PERIMETER_BOT_ZN_4 | 7.33 | 63.67 | 0.00 | 29.67 |
PERIMETER_MID_ZN_3 | 309.67 | 5.17 | 115.33 | 5.17 |
PERIMETER_MID_ZN_2 | 166.50 | 19.83 | 28.83 | 19.83 |
PERIMETER_MID_ZN_1 | 124.67 | 37.83 | 15.17 | 37.17 |
PERIMETER_MID_ZN_4 | 126.50 | 29.00 | 22.00 | 14.33 |
PERIMETER_TOP_ZN_3 | 535.00 | 2.67 | 211.00 | 2.00 |
PERIMETER_TOP_ZN_2 | 300.00 | 17.00 | 65.67 | 16.67 |
PERIMETER_TOP_ZN_1 | 255.50 | 29.67 | 47.67 | 28.67 |
PERIMETER_TOP_ZN_4 | 237.67 | 26.50 | 50.50 | 13.17 |
DATACENTER_BOT_ZN_6 | 0.00 | 4.83 | 0.00 | 2.00 |
DATACENTER_MID_ZN_6 | 0.00 | 3.33 | 0.00 | 0.67 |
DATACENTER_TOP_ZN_6 | 0.00 | 2.83 | 0.00 | 0.33 |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 201.83 | 0.00 | 187.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 645.83 | 404.17 | 237.33 | 314.67 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 08:43:41
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 62.01 | 149.60 | 6779.02 | 1.247 | 0.000 | 0.000 | 0.000 |
CORE_BOTTOM | 55.69 | 134.35 | 6849.35 | 1.026 | 0.000 | 0.000 | 0.000 |
CORE_MID | 55.69 | 134.35 | 6849.35 | 0.837 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 55.69 | 134.35 | 6849.35 | 0.808 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 6.99 | 16.87 | 860.00 | 0.996 | 0.045 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 4.51 | 10.87 | 554.22 | 1.749 | 0.046 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 6.99 | 16.87 | 860.02 | 1.668 | 0.045 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 4.51 | 10.87 | 554.22 | 2.256 | 0.046 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 6.99 | 16.87 | 860.00 | 0.913 | 0.104 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 3.94 | 10.87 | 554.22 | 1.726 | 0.114 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 6.99 | 16.87 | 860.02 | 1.693 | 0.104 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 4.51 | 10.87 | 554.22 | 1.906 | 0.108 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 6.99 | 16.87 | 860.00 | 0.984 | 0.129 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 4.51 | 10.87 | 554.22 | 1.840 | 0.133 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 6.99 | 16.87 | 860.02 | 1.693 | 0.129 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 4.51 | 10.87 | 554.22 | 1.938 | 0.133 | 0.000 | 0.000 |
DATACENTER_BOT_ZN_6 | 0.81 | 1.95 | 99.34 | 0.427 | 0.000 | 0.000 | 0.000 |
DATACENTER_MID_ZN_6 | 0.81 | 1.95 | 99.34 | 0.427 | 0.000 | 0.000 | 0.000 |
DATACENTER_TOP_ZN_6 | 0.81 | 1.95 | 99.34 | 0.426 | 0.000 | 0.000 | 0.000 |
DATACENTER_BASEMENT_ZN_6 | 17.48 | 42.18 | 1911.37 | 23.059 | 0.000 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 62.01 | 149.60 | 6779.02 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_BOTTOM | 55.69 | 134.35 | 6849.35 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_MID | 55.69 | 134.35 | 6849.35 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 55.69 | 134.35 | 6849.35 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 6.99 | 16.87 | 860.00 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 4.51 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 6.99 | 16.87 | 860.02 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 4.51 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 6.99 | 16.87 | 860.00 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 3.94 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 6.99 | 16.87 | 860.02 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 4.51 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 6.99 | 16.87 | 860.00 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 4.51 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 6.99 | 16.87 | 860.02 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 4.51 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
DATACENTER_BOT_ZN_6 | 0.81 | 1.95 | 99.34 | 0.000 | 0.000 | 0.000 | 0.000 |
DATACENTER_MID_ZN_6 | 0.81 | 1.95 | 99.34 | 0.000 | 0.000 | 0.000 | 0.000 |
DATACENTER_TOP_ZN_6 | 0.81 | 1.95 | 99.34 | 0.000 | 0.000 | 0.000 | 0.000 |
DATACENTER_BASEMENT_ZN_6 | 17.48 | 42.18 | 1911.37 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 08:43:41
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
BASEMENT | CAV_BAS | 62.01 | 149.60 | 6779.02 | 2779.43 | 1.2002 | 1.200 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | 55.69 | 134.35 | 6849.35 | 2496.12 | 0.0000 | 1.078 |
CORE_MID | VAV_MID WITH REHEAT | 55.69 | 134.35 | 6849.35 | 2496.12 | 0.0000 | 10.778 |
CORE_TOP | VAV_TOP WITH REHEAT | 55.69 | 134.35 | 6849.35 | 2496.12 | 0.0000 | 1.078 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | 6.99 | 16.87 | 860.00 | 313.41 | 0.0000 | 0.135 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | 4.51 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | 6.99 | 16.87 | 860.02 | 313.42 | 0.0000 | 0.135 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | 4.51 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | 6.99 | 16.87 | 860.00 | 313.41 | 0.0000 | 1.353 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | 3.94 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.872 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | 6.99 | 16.87 | 860.02 | 313.42 | 0.0000 | 1.353 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | 4.51 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.872 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | 6.99 | 16.87 | 860.00 | 313.41 | 0.0000 | 0.135 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | 4.51 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | 6.99 | 16.87 | 860.02 | 313.42 | 0.0000 | 0.135 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | 4.51 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | 0.81 | 1.95 | 99.34 | 36.20 | 0.0156 | 0.016 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | 0.81 | 1.95 | 99.34 | 36.20 | 0.1563 | 0.156 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | 0.81 | 1.95 | 99.34 | 36.20 | 0.0156 | 0.016 |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | 17.48 | 42.18 | 1911.37 | 783.68 | 0.3384 | 0.338 |
Total Facility | 1027.73 | 2493.19 | 126016.35 | 46320.38 | 1.7261 | 158.471 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
BASEMENT | 50901961.64 | 0.00 | 50901961.64 | 0.00 | 50901961.64 | 37848132.68 | 4046.76 | 1375.74 | 3337.49 | 296.52 |
CORE_BOTTOM | 43118342.99 | 0.00 | 43118342.99 | 0.00 | 43118342.99 | 33990283.35 | 3776.76 | 9.80 | 4973.45 | 442.39 |
CORE_MID | 0.35E+09 | 0.00 | 0.35E+09 | 0.00 | 0.35E+09 | 0.34E+09 | 4128.10 | 23.87 | 4608.02 | 616.40 |
CORE_TOP | 33013079.52 | 0.00 | 33013079.52 | 0.00 | 33013079.52 | 33990283.35 | 4150.31 | 12.63 | 4597.07 | 492.82 |
PERIMETER_BOT_ZN_3 | 5253707.10 | 0.00 | 5253707.10 | 431999.69 | 5685706.79 | 4267819.30 | 4489.86 | 59.77 | 4210.37 | 442.39 |
PERIMETER_BOT_ZN_2 | 5987060.97 | 0.00 | 5987060.97 | 287999.59 | 6275060.57 | 2750345.05 | 3631.98 | 4.07 | 5123.95 | 442.39 |
PERIMETER_BOT_ZN_1 | 8772851.93 | 0.00 | 8772851.93 | 431999.69 | 9204851.61 | 4267912.63 | 3692.86 | 7.12 | 5060.02 | 442.39 |
PERIMETER_BOT_ZN_4 | 7728913.73 | 0.00 | 7728913.73 | 287999.59 | 8016913.32 | 2750345.05 | 3581.26 | 2.45 | 5176.29 | 442.39 |
PERIMETER_MID_ZN_3 | 47406764.19 | 0.00 | 47406764.19 | 1013169.02 | 48419933.21 | 42678193.03 | 4172.87 | 28.47 | 4558.66 | 616.40 |
PERIMETER_MID_ZN_2 | 62158070.93 | 0.00 | 62158070.93 | 675445.55 | 62833516.48 | 27503450.52 | 3905.41 | 4.62 | 4849.97 | 1525.40 |
PERIMETER_MID_ZN_1 | 87312636.24 | 0.00 | 87312636.24 | 1013169.02 | 88325805.26 | 42679126.28 | 3967.01 | 4.76 | 4788.23 | 616.40 |
PERIMETER_MID_ZN_4 | 64056360.67 | 0.00 | 64056360.67 | 675445.55 | 64731806.23 | 27503450.52 | 3894.37 | 4.97 | 4860.67 | 616.40 |
PERIMETER_TOP_ZN_3 | 5053525.35 | 0.00 | 5053525.35 | 1257968.18 | 6311493.53 | 4267819.30 | 4090.34 | 3.60 | 4666.07 | 492.78 |
PERIMETER_TOP_ZN_2 | 6079412.34 | 0.00 | 6079412.34 | 838644.88 | 6918057.22 | 2750345.05 | 4014.84 | 2.29 | 4742.88 | 492.78 |
PERIMETER_TOP_ZN_1 | 8649179.38 | 0.00 | 8649179.38 | 1257968.18 | 9907147.56 | 4267912.63 | 4032.20 | 1.07 | 4726.73 | 492.78 |
PERIMETER_TOP_ZN_4 | 6437368.96 | 0.00 | 6437368.96 | 838644.88 | 7276013.84 | 2750345.05 | 4005.08 | 2.97 | 4751.95 | 492.78 |
DATACENTER_BOT_ZN_6 | 244296.02 | 0.00 | 244296.02 | 0.00 | 244296.02 | 492981.60 | 4419.00 | 4341.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 2442960.18 | 0.00 | 2442960.18 | 0.00 | 2442960.18 | 4929815.99 | 4419.00 | 4341.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 244296.02 | 0.00 | 244296.02 | 0.00 | 244296.02 | 492981.60 | 4419.00 | 4341.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.36E+09 | 0.00 | 0.36E+09 | 0.00 | 0.36E+09 | 10671554.30 | 12.67 | 92.17 | 8655.17 | 2813.67 |
Total Facility | 0.66E+10 | 0.00 | 0.66E+10 | 39405516.14 | 0.67E+10 | 0.50E+10 | 5202.33 | 4389.62 | 8747.61 | 3722.67 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
BASEMENT | 2.2931 | 0.0000 | 2.2931 | 0.0000 | 2.2931 | 1.2002 | 1374.35 | 1373.83 | 3194.81 |
CORE_BOTTOM | 1.9084 | 0.0000 | 1.9084 | 0.0000 | 1.9084 | 1.0778 | 1244.84 | 8.14 | 4690.02 |
CORE_MID | 15.5972 | 0.0000 | 15.5972 | 0.0000 | 15.5972 | 10.7782 | 1413.80 | 22.59 | 4506.60 |
CORE_TOP | 1.5080 | 0.0000 | 1.5080 | 0.0000 | 1.5080 | 1.0778 | 1407.22 | 12.53 | 4523.25 |
PERIMETER_BOT_ZN_3 | 0.2329 | 0.0000 | 0.2329 | 0.0105 | 0.2434 | 0.1353 | 1953.65 | 58.17 | 3931.19 |
PERIMETER_BOT_ZN_2 | 0.2641 | 0.0000 | 0.2641 | 0.0070 | 0.2711 | 0.0872 | 1150.83 | 3.25 | 4788.92 |
PERIMETER_BOT_ZN_1 | 0.3908 | 0.0000 | 0.3908 | 0.0105 | 0.4013 | 0.1353 | 1197.33 | 4.26 | 4741.42 |
PERIMETER_BOT_ZN_4 | 0.3403 | 0.0000 | 0.3403 | 0.0070 | 0.3473 | 0.0872 | 1106.57 | 1.57 | 4834.86 |
PERIMETER_MID_ZN_3 | 2.1428 | 0.0000 | 2.1428 | 0.0246 | 2.1674 | 1.3533 | 1460.56 | 27.22 | 4455.22 |
PERIMETER_MID_ZN_2 | 2.6113 | 0.0000 | 2.6113 | 0.0173 | 2.6286 | 0.8721 | 1233.50 | 1.99 | 3798.51 |
PERIMETER_MID_ZN_1 | 3.9704 | 0.0000 | 3.9704 | 0.0246 | 3.9950 | 1.3533 | 1269.33 | 3.61 | 4670.06 |
PERIMETER_MID_ZN_4 | 2.8833 | 0.0000 | 2.8833 | 0.0164 | 2.8997 | 0.8721 | 1226.18 | 3.08 | 4713.74 |
PERIMETER_TOP_ZN_3 | 0.2311 | 0.0000 | 0.2311 | 0.0305 | 0.2617 | 0.1353 | 1351.01 | 3.23 | 4588.75 |
PERIMETER_TOP_ZN_2 | 0.2783 | 0.0000 | 0.2783 | 0.0204 | 0.2987 | 0.0872 | 1290.99 | 1.92 | 4650.09 |
PERIMETER_TOP_ZN_1 | 0.3970 | 0.0000 | 0.3970 | 0.0305 | 0.4276 | 0.1353 | 1303.07 | 0.78 | 4639.15 |
PERIMETER_TOP_ZN_4 | 0.2933 | 0.0000 | 0.2933 | 0.0204 | 0.3137 | 0.0872 | 1284.67 | 2.08 | 4656.24 |
DATACENTER_BOT_ZN_6 | 0.0114 | 0.0000 | 0.0114 | 0.0000 | 0.0114 | 0.0156 | 1602.00 | 4341.00 | 0.00 |
DATACENTER_MID_ZN_6 | 0.1142 | 0.0000 | 0.1142 | 0.0000 | 0.1142 | 0.1563 | 1602.00 | 4341.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 0.0114 | 0.0000 | 0.0114 | 0.0000 | 0.0114 | 0.0156 | 1602.00 | 4341.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 11.8305 | 0.0000 | 11.8305 | 0.0000 | 11.8305 | 0.3384 | 9.33 | 92.17 | 5841.50 |
Total Facility | 293.1830 | 0.0000 | 293.1830 | 0.9658 | 294.1488 | 158.4706 | 2385.33 | 4372.48 | 5933.94 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
VAV_BOT WITH REHEAT | 94351789.51 | 0.00 | 94351789.51 | 48026705.38 | 3651.08 | 5.93 | 5103.00 | 442.39 |
VAV_MID WITH REHEAT | 0.81E+09 | 0.00 | 0.81E+09 | 0.48E+09 | 3973.47 | 2.48 | 4784.05 | 616.40 |
VAV_TOP WITH REHEAT | 78870716.41 | 0.00 | 78870716.41 | 48026705.38 | 4037.10 | 1.18 | 4721.72 | 492.37 |
CAV_BAS | 67778129.04 | 0.00 | 67778129.04 | 37848132.68 | 3987.38 | 4.10 | 4768.52 | 296.48 |
AIRLOOP DATACENTER BASEMENT | 0.48E+09 | 0.00 | 0.48E+09 | 10671554.30 | 12.67 | 0.00 | 8747.33 | 2813.67 |
AIRLOOP DATACENTER BOT | 325290.55 | 0.00 | 325290.55 | 492981.60 | 4419.00 | 0.00 | 4341.00 | 0.00 |
AIRLOOP DATACENTER MID | 3252905.49 | 0.00 | 3252905.49 | 4929815.99 | 4419.00 | 0.00 | 4341.00 | 0.00 |
AIRLOOP DATACENTER TOP | 325290.55 | 0.00 | 325290.55 | 492981.60 | 4419.00 | 0.00 | 4341.00 | 0.00 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
VAV_BOT WITH REHEAT | 4.1762 | 0.0000 | 4.1762 | 1.5229 | 1156.04 | 3.73 | 4783.23 |
VAV_MID WITH REHEAT | 36.4893 | 0.0000 | 36.4893 | 15.2292 | 1271.68 | 1.72 | 4669.61 |
VAV_TOP WITH REHEAT | 3.6056 | 0.0000 | 3.6056 | 1.5229 | 1306.04 | 0.87 | 4636.08 |
CAV_BAS | 3.0534 | 0.0000 | 3.0534 | 1.2002 | 1346.44 | 1.62 | 4594.94 |
AIRLOOP DATACENTER BASEMENT | 15.7528 | 0.0000 | 15.7528 | 0.3384 | 9.33 | 0.00 | 5933.67 |
AIRLOOP DATACENTER BOT | 0.0152 | 0.0000 | 0.0152 | 0.0156 | 1602.00 | 0.00 | 4341.00 |
AIRLOOP DATACENTER MID | 0.1520 | 0.0000 | 0.1520 | 0.1563 | 1602.00 | 0.00 | 4341.00 |
AIRLOOP DATACENTER TOP | 0.0152 | 0.0000 | 0.0152 | 0.0156 | 1602.00 | 0.00 | 4341.00 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
VAV_BOT WITH REHEAT | 0.00 | 2340.34 | 3027.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
VAV_MID WITH REHEAT | 0.00 | 2621.71 | 2940.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
VAV_TOP WITH REHEAT | 0.00 | 2765.94 | 2666.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CAV_BAS | 0.00 | 1354.03 | 3608.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER BASEMENT | 0.00 | 92.17 | 8655.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER BOT | 0.00 | 4341.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER MID | 0.00 | 4341.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER TOP | 0.00 | 4341.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
VAV_BOT WITH REHEAT | 0.0000 | 3.3829 | 6.5414 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
VAV_MID WITH REHEAT | 0.0000 | 33.8285 | 55.1836 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
VAV_TOP WITH REHEAT | 0.0000 | 3.3836 | 5.5555 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
CAV_BAS | 0.0000 | 1.5981 | 4.8256 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
AIRLOOP DATACENTER BASEMENT | 0.0000 | 0.4514 | 16.0208 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
AIRLOOP DATACENTER BOT | 0.0000 | 0.0208 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
AIRLOOP DATACENTER MID | 0.0000 | 0.2082 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
AIRLOOP DATACENTER TOP | 0.0000 | 0.0208 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 08:43:41
Surfaces by ClassTotal | Outdoors | |
Wall | 98 | 30 |
Floor | 41 | 0 |
Roof | 30 | 1 |
Internal Mass | 16 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 24 | 24 |
Door | 12 | 12 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 8 |
Conditioned Zones | 23 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 3 |
Count | |
IDF Objects | 1403 |
Defaulted Fields | 1182 |
Fields with Defaults | 3947 |
Autosized Fields | 339 |
Autosizable Fields | 415 |
Autocalculated Fields | 226 |
Autocalculatable Fields | 473 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 08:43:41
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 27888.40 | 329755.57 | 28-MAY-05:00 | 2114105.39 | 08-AUG-15:20 |
Electricity:Building | 18608.66 | 225715.65 | 07-MAY-17:10 | 1164206.62 | 01-DEC-16:20 |
Electricity:Zone:BASEMENT | 687.24 | 14732.47 | 01-JAN-00:10 | 36407.88 | 02-JAN-08:10 |
Electricity:SpaceType:GENERAL | 18608.66 | 225715.65 | 07-MAY-17:10 | 1164206.62 | 01-DEC-16:20 |
InteriorLights:Electricity | 3932.27 | 18459.50 | 01-JAN-10:20 | 385834.94 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:BASEMENT | 262.84 | 1274.92 | 01-JAN-00:10 | 22950.34 | 02-JAN-08:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 3932.27 | 18459.50 | 01-JAN-10:20 | 385834.94 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity | 3932.27 | 18459.50 | 01-JAN-10:20 | 385834.94 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:BASEMENT | 262.84 | 1274.92 | 01-JAN-00:10 | 22950.34 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 3932.27 | 18459.50 | 01-JAN-10:20 | 385834.94 | 02-JAN-08:10 |
Electricity:Zone:CORE_BOTTOM | 525.67 | 5598.20 | 01-JAN-00:10 | 37817.64 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_BOTTOM | 236.05 | 1144.97 | 01-JAN-00:10 | 20611.01 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_BOTTOM | 236.05 | 1144.97 | 01-JAN-00:10 | 20611.01 | 02-JAN-08:10 |
Electricity:Zone:CORE_MID | 5256.66 | 55981.88 | 01-JAN-00:10 | 378175.77 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_MID | 2360.53 | 11449.71 | 01-JAN-00:10 | 206110.14 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_MID | 2360.53 | 11449.71 | 01-JAN-00:10 | 206110.14 | 02-JAN-08:10 |
Electricity:Zone:CORE_TOP | 525.67 | 5598.19 | 01-JAN-00:10 | 37817.58 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_TOP | 236.05 | 1144.97 | 01-JAN-00:10 | 20611.01 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_TOP | 236.05 | 1144.97 | 01-JAN-00:10 | 20611.01 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_3 | 53.86 | 627.57 | 02-APR-17:10 | 4748.47 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 17.50 | 68.40 | 01-JAN-10:20 | 2587.92 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 17.50 | 68.40 | 01-JAN-10:20 | 2587.92 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_2 | 34.61 | 404.43 | 16-APR-17:10 | 3060.10 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 11.17 | 44.08 | 01-JAN-08:40 | 1667.75 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 11.17 | 44.08 | 01-JAN-08:40 | 1667.75 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_1 | 53.55 | 627.58 | 12-MAR-17:10 | 4748.56 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 17.18 | 68.40 | 01-JAN-08:40 | 2587.98 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 17.18 | 68.40 | 01-JAN-08:40 | 2587.98 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_4 | 34.58 | 404.43 | 12-MAR-17:10 | 3060.09 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 11.15 | 44.08 | 01-JAN-10:20 | 1667.75 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 11.15 | 44.08 | 01-JAN-10:20 | 1667.75 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_MID_ZN_3 | 538.27 | 6275.73 | 02-APR-17:10 | 47484.70 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 174.62 | 684.02 | 01-JAN-10:10 | 25879.19 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 174.62 | 684.02 | 01-JAN-10:10 | 25879.19 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_MID_ZN_2 | 345.95 | 4044.32 | 16-APR-17:10 | 30600.95 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 111.60 | 440.81 | 01-JAN-08:40 | 16677.53 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 111.60 | 440.81 | 01-JAN-08:40 | 16677.53 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_MID_ZN_1 | 535.34 | 6275.83 | 12-MAR-17:10 | 47485.60 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 171.68 | 684.04 | 01-JAN-08:40 | 25879.75 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 171.68 | 684.04 | 01-JAN-08:40 | 25879.75 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_MID_ZN_4 | 345.68 | 4044.30 | 12-MAR-17:10 | 30600.86 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 111.33 | 440.81 | 01-JAN-10:10 | 16677.53 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 111.33 | 440.81 | 01-JAN-10:10 | 16677.53 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_3 | 53.83 | 627.57 | 26-MAR-17:10 | 4748.47 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 17.46 | 68.40 | 01-JAN-10:10 | 2587.92 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 17.46 | 68.40 | 01-JAN-10:10 | 2587.92 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_2 | 34.59 | 404.43 | 16-APR-17:10 | 3060.10 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 11.16 | 44.08 | 01-JAN-08:40 | 1667.75 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 11.16 | 44.08 | 01-JAN-08:40 | 1667.75 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_1 | 53.53 | 627.58 | 12-MAR-17:10 | 4748.56 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 17.17 | 68.40 | 01-JAN-08:40 | 2587.98 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 17.17 | 68.40 | 01-JAN-08:40 | 2587.98 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_4 | 34.57 | 404.43 | 12-MAR-17:10 | 3060.09 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 11.13 | 44.08 | 01-JAN-10:10 | 1667.75 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 11.13 | 44.08 | 01-JAN-10:10 | 1667.75 | 02-JAN-08:10 |
Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 7568.97 | 95267.60 | 01-JAN-00:10 | 386103.53 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 74.11 | 359.47 | 01-JAN-00:10 | 6471.01 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 74.11 | 359.47 | 01-JAN-00:10 | 6471.01 | 02-JAN-08:10 |
Electricity:Zone:DATACENTER_BOT_ZN_6 | 160.51 | 1980.76 | 01-JAN-00:10 | 8373.14 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_BOT_ZN_6 | 6.63 | 32.15 | 01-JAN-00:10 | 578.72 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_BOT_ZN_6 | 6.63 | 32.15 | 01-JAN-00:10 | 578.72 | 02-JAN-08:10 |
Electricity:Zone:DATACENTER_MID_ZN_6 | 1605.09 | 19807.58 | 01-JAN-00:10 | 83731.41 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_MID_ZN_6 | 66.28 | 321.53 | 01-JAN-00:10 | 5787.18 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_MID_ZN_6 | 66.28 | 321.53 | 01-JAN-00:10 | 5787.18 | 02-JAN-08:10 |
Electricity:Zone:DATACENTER_TOP_ZN_6 | 160.51 | 1980.76 | 01-JAN-00:10 | 8373.14 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_TOP_ZN_6 | 6.63 | 32.15 | 01-JAN-00:10 | 578.72 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_TOP_ZN_6 | 6.63 | 32.15 | 01-JAN-00:10 | 578.72 | 02-JAN-08:10 |
InteriorEquipment:Electricity | 14676.40 | 207256.16 | 01-JAN-00:10 | 778371.69 | 03-APR-07:10 |
InteriorEquipment:Electricity:Zone:BASEMENT | 424.40 | 13457.54 | 01-JAN-00:10 | 13457.54 | 01-JAN-00:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 14676.40 | 207256.16 | 01-JAN-00:10 | 778371.69 | 03-APR-07:10 |
MiscPlug:InteriorEquipment:Electricity | 5334.97 | 88964.76 | 01-JAN-00:10 | 305206.10 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:BASEMENT | 424.40 | 13457.54 | 01-JAN-00:10 | 13457.54 | 01-JAN-00:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 5334.97 | 88964.76 | 01-JAN-00:10 | 305206.10 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 289.61 | 4453.23 | 01-JAN-00:10 | 17206.63 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 289.61 | 4453.23 | 01-JAN-00:10 | 17206.63 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_MID | 2896.13 | 44532.17 | 01-JAN-00:10 | 172065.63 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_MID | 2896.13 | 44532.17 | 01-JAN-00:10 | 172065.63 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_TOP | 289.61 | 4453.22 | 01-JAN-00:10 | 17206.56 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_TOP | 289.61 | 4453.22 | 01-JAN-00:10 | 17206.56 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 36.37 | 559.17 | 01-JAN-00:10 | 2160.55 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 36.37 | 559.17 | 01-JAN-00:10 | 2160.55 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.34 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.34 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 36.37 | 559.18 | 01-JAN-00:10 | 2160.58 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 36.37 | 559.18 | 01-JAN-00:10 | 2160.58 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.33 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.33 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 363.65 | 5591.71 | 01-JAN-00:10 | 21605.52 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 363.65 | 5591.71 | 01-JAN-00:10 | 21605.52 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 234.35 | 3603.51 | 01-JAN-00:10 | 13923.42 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 234.35 | 3603.51 | 01-JAN-00:10 | 13923.42 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 363.66 | 5591.79 | 01-JAN-00:10 | 21605.85 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 363.66 | 5591.79 | 01-JAN-00:10 | 21605.85 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 234.35 | 3603.49 | 01-JAN-00:10 | 13923.33 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 234.35 | 3603.49 | 01-JAN-00:10 | 13923.33 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 36.37 | 559.17 | 01-JAN-00:10 | 2160.55 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 36.37 | 559.17 | 01-JAN-00:10 | 2160.55 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.34 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.34 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 36.37 | 559.18 | 01-JAN-00:10 | 2160.58 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 36.37 | 559.18 | 01-JAN-00:10 | 2160.58 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.33 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.33 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 7494.86 | 94908.13 | 01-JAN-00:10 | 379632.52 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity | 9341.42 | 118291.40 | 01-JAN-00:10 | 473165.59 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 7494.86 | 94908.13 | 01-JAN-00:10 | 379632.52 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:SpaceType:GENERAL | 9341.42 | 118291.40 | 01-JAN-00:10 | 473165.59 | 31-MAR-23:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_BOT_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_BOT_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_MID_ZN_6 | 1538.81 | 19486.06 | 01-JAN-00:10 | 77944.22 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_MID_ZN_6 | 1538.81 | 19486.06 | 01-JAN-00:10 | 77944.22 | 31-MAR-23:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_TOP_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_TOP_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
Electricity:Plant | 1489.83 | 3550.48 | 05-JAN-03:30 | 556052.68 | 05-JUL-10:20 |
HeatRejection:Electricity | 477.25 | 51.34 | 06-JAN-09:00 | 89285.81 | 16-MAY-12:40 |
General:HeatRejection:Electricity | 477.25 | 51.34 | 06-JAN-09:00 | 89285.81 | 16-MAY-12:40 |
Electricity:HVAC | 5236.89 | 50524.37 | 17-SEP-05:00 | 500011.51 | 08-AUG-15:20 |
ExteriorEquipment:Electricity | 1934.79 | 28603.11 | 01-JAN-00:10 | 118535.44 | 02-JAN-08:20 |
Transformer:ExteriorEquipment:Electricity | 80.18 | 1421.04 | 01-JAN-00:10 | 5057.48 | 01-DEC-16:30 |
ElectricityPurchased:Facility | 27888.40 | 329755.57 | 28-MAY-05:00 | 2114105.39 | 08-AUG-15:20 |
ElectricityPurchased:Plant | 27888.40 | 329755.57 | 28-MAY-05:00 | 2114105.39 | 08-AUG-15:20 |
Cogeneration:ElectricityPurchased | 27888.40 | 329755.57 | 28-MAY-05:00 | 2114105.39 | 08-AUG-15:20 |
General:Cogeneration:ElectricityPurchased | 27888.40 | 329755.57 | 28-MAY-05:00 | 2114105.39 | 08-AUG-15:20 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 27888.40 | 329755.57 | 28-MAY-05:00 | 2114105.39 | 08-AUG-15:20 |
ElectricityNet:Plant | 27888.40 | 329755.57 | 28-MAY-05:00 | 2114105.39 | 08-AUG-15:20 |
Cogeneration:ElectricityNet | 27888.40 | 329755.57 | 28-MAY-05:00 | 2114105.39 | 08-AUG-15:20 |
General:Cogeneration:ElectricityNet | 27888.40 | 329755.57 | 28-MAY-05:00 | 2114105.39 | 08-AUG-15:20 |
Fans:Electricity | 2526.83 | 43878.96 | 04-FEB-18:40 | 331054.64 | 05-JUL-11:30 |
General:Fans:Electricity | 2526.83 | 43878.96 | 04-FEB-18:40 | 331054.64 | 05-JUL-11:30 |
ExteriorLights:Electricity | 698.41 | 0.00 | 01-JAN-08:20 | 57580.60 | 01-JAN-06:10 |
General:ExteriorLights:Electricity | 698.41 | 0.00 | 01-JAN-08:20 | 57580.60 | 01-JAN-06:10 |
ElevatorLift:ExteriorEquipment:Electricity | 1848.78 | 27144.47 | 01-JAN-00:10 | 113101.96 | 01-JAN-07:10 |
ElevatorLightsFan:ExteriorEquipment:Electricity | 5.83 | 37.60 | 01-JAN-00:10 | 376.00 | 01-JAN-07:10 |
HeatRecovery:Electricity | 56.49 | 0.00 | 01-JAN-00:10 | 6524.59 | 02-JAN-07:10 |
General:HeatRecovery:Electricity | 56.49 | 0.00 | 01-JAN-00:10 | 6524.59 | 02-JAN-07:10 |
Cooling:Electricity | 1497.42 | 1372.62 | 06-JAN-09:00 | 556452.58 | 05-JUL-10:20 |
General:Cooling:Electricity | 1497.42 | 1372.62 | 06-JAN-09:00 | 556452.58 | 05-JUL-10:20 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Humidifier:Electricity | 1706.80 | 0.00 | 23-APR-10:50 | 100000.00 | 06-FEB-17:10 |
General:Humidifier:Electricity | 1706.80 | 0.00 | 23-APR-10:50 | 100000.00 | 06-FEB-17:10 |
Boiler Parasitic:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Pumps:Electricity | 381.74 | 3488.42 | 01-JAN-00:40 | 69323.28 | 05-JUL-10:40 |
General:Pumps:Electricity | 381.74 | 3488.42 | 01-JAN-00:40 | 69323.28 | 05-JUL-10:40 |
WIRED_LTG_ELECTRICITY | 110.50 | 0.00 | 01-JAN-00:10 | 10841.96 | 02-JAN-08:20 |
WIRED_INT_EQUIP | 5334.97 | 88964.76 | 31-MAR-23:10 | 305206.10 | 03-APR-07:10 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 5277.81 | 8146.58 | 01-JAN-01:20 | 3494739.04 | 09-JAN-07:10 |
NaturalGas:Plant | 5277.81 | 8146.58 | 01-JAN-01:20 | 3494739.04 | 09-JAN-07:10 |
Heating:NaturalGas | 4384.93 | 0.00 | 01-JAN-00:40 | 3461431.52 | 09-JAN-07:10 |
Boiler:Heating:NaturalGas | 4384.93 | 0.00 | 01-JAN-00:40 | 3461431.52 | 09-JAN-07:10 |
WaterSystems:NaturalGas | 892.88 | 8146.58 | 01-JAN-01:20 | 90000.01 | 23-FEB-12:50 |
Water Heater:WaterSystems:NaturalGas | 892.88 | 8146.58 | 01-JAN-01:20 | 90000.01 | 23-FEB-12:50 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
PlantLoopCoolingDemand:Facility | 8059.35 | 2970.83 | 06-JAN-09:00 | 3827336.61 | 05-JUL-10:30 |
PlantLoopCoolingDemand:HVAC | 8059.35 | 2970.83 | 06-JAN-09:00 | 3827336.61 | 05-JUL-10:30 |
CoolingCoils:PlantLoopCoolingDemand | 8059.35 | 2970.83 | 06-JAN-09:00 | 3827336.61 | 05-JUL-10:30 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 6020.73 | 0.00 | 18-MAY-23:10 | 0.00 | 18-MAY-16:00 |
Water:HVAC | 634.93 | 0.00 | 23-APR-10:50 | 0.00 | 01-MAR-05:10 |
Humidifier:Water | 634.93 | 0.00 | 23-APR-10:50 | 0.00 | 01-MAR-05:10 |
General:Humidifier:Water | 634.93 | 0.00 | 23-APR-10:50 | 0.00 | 01-MAR-05:10 |
MainsWater:Facility | 6020.73 | 0.00 | 18-MAY-23:10 | 0.00 | 18-MAY-16:00 |
MainsWater:HVAC | 634.93 | 0.00 | 23-APR-10:50 | 0.00 | 01-MAR-05:10 |
Humidifier:MainsWater | 634.93 | 0.00 | 23-APR-10:50 | 0.00 | 01-MAR-05:10 |
General:Humidifier:MainsWater | 634.93 | 0.00 | 23-APR-10:50 | 0.00 | 01-MAR-05:10 |
Water:Plant | 5385.80 | 0.00 | 01-JAN-00:10 | 0.00 | 18-MAY-16:00 |
WaterSystems:Water | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterUse:WaterSystems:Water | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
MainsWater:Plant | 5385.80 | 0.00 | 01-JAN-00:10 | 0.00 | 18-MAY-16:00 |
WaterSystems:MainsWater | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterUse:WaterSystems:MainsWater | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water Heater:WaterSystems:Water | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:MainsWater | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
HeatRejection:Water | 3105.63 | 0.00 | 01-JAN-00:10 | 0.00 | 18-MAY-16:00 |
General:HeatRejection:Water | 3105.63 | 0.00 | 01-JAN-00:10 | 0.00 | 18-MAY-16:00 |
HeatRejection:MainsWater | 3105.63 | 0.00 | 01-JAN-00:10 | 0.00 | 18-MAY-16:00 |
General:HeatRejection:MainsWater | 3105.63 | 0.00 | 01-JAN-00:10 | 0.00 | 18-MAY-16:00 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 52336.69 | 90009.74 | 01-JAN-06:00 | 14014426.10 | 05-JUL-10:30 |
EnergyTransfer:Building | 19727.37 | 87978.69 | 01-JAN-16:00 | 1937113.40 | 26-DEC-06:10 |
EnergyTransfer:Zone:BASEMENT | 671.72 | 0.00 | 01-JAN-00:10 | 72363.21 | 05-SEP-05:10 |
Heating:EnergyTransfer | 1879.47 | 0.00 | 01-FEB-22:10 | 1654009.45 | 02-JAN-05:10 |
Heating:EnergyTransfer:Zone:BASEMENT | 2.67 | 0.00 | 01-JAN-00:10 | 16728.53 | 29-JUL-16:10 |
General:Heating:EnergyTransfer | 1879.47 | 0.00 | 01-FEB-22:10 | 1654009.45 | 02-JAN-05:10 |
General:Heating:EnergyTransfer:Zone:BASEMENT | 2.67 | 0.00 | 01-JAN-00:10 | 16728.53 | 29-JUL-16:10 |
Cooling:EnergyTransfer | 17847.90 | 81059.71 | 01-JAN-09:20 | 1753660.26 | 08-AUG-15:20 |
Cooling:EnergyTransfer:Zone:BASEMENT | 669.05 | 0.00 | 01-JAN-00:10 | 72363.21 | 05-SEP-05:10 |
General:Cooling:EnergyTransfer | 17847.90 | 81059.71 | 01-JAN-09:20 | 1753660.26 | 08-AUG-15:20 |
General:Cooling:EnergyTransfer:Zone:BASEMENT | 669.05 | 0.00 | 01-JAN-00:10 | 72363.21 | 05-SEP-05:10 |
EnergyTransfer:Zone:CORE_BOTTOM | 597.26 | 0.00 | 01-JAN-00:40 | 56618.72 | 05-JUL-15:50 |
Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.02 | 0.00 | 01-JAN-00:10 | 10362.56 | 02-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.02 | 0.00 | 01-JAN-00:10 | 10362.56 | 02-JAN-06:10 |
Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 597.25 | 0.00 | 01-JAN-00:40 | 56618.72 | 05-JUL-15:50 |
General:Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 597.25 | 0.00 | 01-JAN-00:40 | 56618.72 | 05-JUL-15:50 |
EnergyTransfer:Zone:CORE_MID | 4298.58 | 0.00 | 01-JAN-00:40 | 532073.27 | 02-JAN-05:30 |
Heating:EnergyTransfer:Zone:CORE_MID | 33.73 | 0.00 | 01-JAN-00:20 | 532073.27 | 02-JAN-05:30 |
General:Heating:EnergyTransfer:Zone:CORE_MID | 33.73 | 0.00 | 01-JAN-00:20 | 532073.27 | 02-JAN-05:30 |
Cooling:EnergyTransfer:Zone:CORE_MID | 4264.85 | 0.00 | 01-JAN-00:40 | 483619.51 | 05-JUL-15:30 |
General:Cooling:EnergyTransfer:Zone:CORE_MID | 4264.85 | 0.00 | 01-JAN-00:40 | 483619.51 | 05-JUL-15:30 |
EnergyTransfer:Zone:CORE_TOP | 392.25 | 0.00 | 01-JAN-00:40 | 74769.10 | 23-JAN-05:20 |
Heating:EnergyTransfer:Zone:CORE_TOP | 32.76 | 0.00 | 01-JAN-00:40 | 74769.10 | 23-JAN-05:20 |
General:Heating:EnergyTransfer:Zone:CORE_TOP | 32.76 | 0.00 | 01-JAN-00:40 | 74769.10 | 23-JAN-05:20 |
Cooling:EnergyTransfer:Zone:CORE_TOP | 359.49 | 0.00 | 01-JAN-00:10 | 54008.79 | 05-JUL-15:30 |
General:Cooling:EnergyTransfer:Zone:CORE_TOP | 359.49 | 0.00 | 01-JAN-00:10 | 54008.79 | 05-JUL-15:30 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 67.74 | 0.00 | 01-JAN-00:40 | 13549.68 | 09-JAN-05:10 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 8.84 | 0.00 | 01-JAN-00:40 | 13549.68 | 09-JAN-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 8.84 | 0.00 | 01-JAN-00:40 | 13549.68 | 09-JAN-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 58.91 | 0.00 | 01-JAN-00:20 | 11356.33 | 29-JUN-14:50 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 58.91 | 0.00 | 01-JAN-00:20 | 11356.33 | 29-JUN-14:50 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 69.54 | 0.00 | 01-JAN-00:40 | 17359.78 | 31-JUL-08:10 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 5.93 | 0.00 | 01-JAN-00:40 | 12030.30 | 09-JAN-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 5.93 | 0.00 | 01-JAN-00:40 | 12030.30 | 09-JAN-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 63.62 | 0.00 | 01-JAN-00:20 | 17359.78 | 31-JUL-08:10 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 63.62 | 0.00 | 01-JAN-00:20 | 17359.78 | 31-JUL-08:10 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 114.65 | 0.00 | 01-JAN-00:40 | 25771.73 | 01-SEP-13:10 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 7.66 | 0.00 | 01-JAN-00:40 | 18718.92 | 09-JAN-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 7.66 | 0.00 | 01-JAN-00:40 | 18718.92 | 09-JAN-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 106.99 | 0.00 | 01-JAN-00:20 | 25771.73 | 01-SEP-13:10 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 106.99 | 0.00 | 01-JAN-00:20 | 25771.73 | 01-SEP-13:10 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 96.82 | 0.00 | 01-JAN-00:40 | 20706.96 | 24-JUL-17:00 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 1.87 | 0.00 | 01-JAN-00:20 | 9965.81 | 09-JAN-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 1.87 | 0.00 | 01-JAN-00:20 | 9965.81 | 09-JAN-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 94.95 | 0.00 | 01-JAN-00:40 | 20706.96 | 24-JUL-17:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 94.95 | 0.00 | 01-JAN-00:40 | 20706.96 | 24-JUL-17:00 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 841.42 | 0.00 | 01-JAN-00:40 | 147716.03 | 01-JAN-08:10 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 445.03 | 0.00 | 01-JAN-00:40 | 147716.03 | 01-JAN-08:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 445.03 | 0.00 | 01-JAN-00:40 | 147716.03 | 01-JAN-08:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 396.39 | 0.00 | 01-JAN-00:10 | 110866.49 | 29-JUN-15:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 396.39 | 0.00 | 01-JAN-00:10 | 110866.49 | 29-JUN-15:00 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 791.78 | 0.00 | 01-JAN-00:40 | 185199.90 | 24-JUL-08:40 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 259.56 | 0.00 | 01-JAN-00:40 | 180384.39 | 09-JAN-05:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 259.56 | 0.00 | 01-JAN-00:40 | 180384.39 | 09-JAN-05:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 532.21 | 0.00 | 01-JAN-00:10 | 185199.90 | 24-JUL-08:40 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 532.21 | 0.00 | 01-JAN-00:10 | 185199.90 | 24-JUL-08:40 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 1205.80 | 0.00 | 01-JAN-00:40 | 273866.08 | 01-SEP-13:20 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 267.81 | 0.00 | 01-JAN-00:40 | 253325.73 | 09-JAN-05:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 267.81 | 0.00 | 01-JAN-00:40 | 253325.73 | 09-JAN-05:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 937.98 | 0.00 | 01-JAN-00:20 | 273866.08 | 01-SEP-13:20 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 937.98 | 0.00 | 01-JAN-00:20 | 273866.08 | 01-SEP-13:20 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 793.21 | 0.00 | 01-JAN-00:40 | 203157.27 | 30-JUN-17:00 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 217.44 | 0.00 | 01-JAN-00:40 | 178473.69 | 09-JAN-05:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 217.44 | 0.00 | 01-JAN-00:40 | 178473.69 | 09-JAN-05:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 575.76 | 0.00 | 01-JAN-00:20 | 203157.27 | 30-JUN-17:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 575.76 | 0.00 | 01-JAN-00:20 | 203157.27 | 30-JUN-17:00 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 112.14 | 0.00 | 01-JAN-00:40 | 18847.07 | 13-FEB-04:20 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 75.23 | 0.00 | 01-JAN-00:40 | 18847.07 | 13-FEB-04:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 75.23 | 0.00 | 01-JAN-00:40 | 18847.07 | 13-FEB-04:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 36.91 | 0.00 | 01-JAN-00:10 | 11909.05 | 29-JUN-15:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 36.91 | 0.00 | 01-JAN-00:10 | 11909.05 | 29-JUN-15:00 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 93.27 | 0.00 | 01-JAN-00:40 | 20915.62 | 04-JAN-05:10 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 43.99 | 0.00 | 01-JAN-00:40 | 20915.62 | 04-JAN-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 43.99 | 0.00 | 01-JAN-00:40 | 20915.62 | 04-JAN-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 49.29 | 0.00 | 01-JAN-00:10 | 18617.66 | 24-JUL-08:50 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 49.29 | 0.00 | 01-JAN-00:10 | 18617.66 | 24-JUL-08:50 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 136.61 | 0.00 | 01-JAN-00:40 | 28333.48 | 01-SEP-13:20 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 50.84 | 0.00 | 01-JAN-00:40 | 28270.66 | 13-FEB-04:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 50.84 | 0.00 | 01-JAN-00:40 | 28270.66 | 13-FEB-04:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 85.78 | 0.00 | 01-JAN-00:10 | 28333.48 | 01-SEP-13:20 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 85.78 | 0.00 | 01-JAN-00:10 | 28333.48 | 01-SEP-13:20 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 91.59 | 0.00 | 01-JAN-00:40 | 22208.58 | 09-JAN-05:10 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 37.54 | 0.00 | 01-JAN-00:40 | 22208.58 | 09-JAN-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 37.54 | 0.00 | 01-JAN-00:40 | 22208.58 | 09-JAN-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 54.04 | 0.00 | 01-JAN-00:10 | 20941.39 | 30-JUN-17:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 54.04 | 0.00 | 01-JAN-00:10 | 20941.39 | 30-JUN-17:00 |
EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 61.11 | 0.00 | 01-JAN-00:40 | 12472.43 | 26-DEC-14:50 |
Heating:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 9.29 | 0.00 | 01-JAN-00:40 | 12472.43 | 26-DEC-14:50 |
General:Heating:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 9.29 | 0.00 | 01-JAN-00:40 | 12472.43 | 26-DEC-14:50 |
Cooling:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 51.82 | 0.00 | 01-JAN-00:20 | 10179.23 | 24-JUL-14:50 |
General:Cooling:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 51.82 | 0.00 | 01-JAN-00:20 | 10179.23 | 24-JUL-14:50 |
EnergyTransfer:Zone:MIDFLOOR_PLENUM | 631.77 | 0.00 | 01-JAN-00:40 | 227543.75 | 02-JAN-06:20 |
Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 276.44 | 0.00 | 01-JAN-00:40 | 227543.75 | 02-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 276.44 | 0.00 | 01-JAN-00:40 | 227543.75 | 02-JAN-06:20 |
Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 355.33 | 0.00 | 01-JAN-00:10 | 84976.22 | 24-JUL-15:20 |
General:Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 355.33 | 0.00 | 01-JAN-00:10 | 84976.22 | 24-JUL-15:20 |
EnergyTransfer:Zone:TOPFLOOR_PLENUM | 137.39 | 0.00 | 01-JAN-00:40 | 37531.09 | 09-JAN-05:10 |
Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 93.89 | 0.00 | 01-JAN-00:40 | 37531.09 | 09-JAN-05:10 |
General:Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 93.89 | 0.00 | 01-JAN-00:40 | 37531.09 | 09-JAN-05:10 |
Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 43.50 | 0.00 | 01-JAN-00:10 | 20928.82 | 30-JUN-14:50 |
General:Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 43.50 | 0.00 | 01-JAN-00:10 | 20928.82 | 30-JUN-14:50 |
EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 133.98 | 4.44 | 07-JAN-18:20 | 8806.15 | 21-APR-18:20 |
Heating:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 0.15 | 0.00 | 01-JAN-16:00 | 637.62 | 01-JAN-17:50 |
General:Heating:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 0.15 | 0.00 | 01-JAN-16:00 | 637.62 | 01-JAN-17:50 |
Cooling:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 133.83 | 0.00 | 01-JAN-00:10 | 8806.15 | 21-APR-18:20 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 133.83 | 0.00 | 01-JAN-00:10 | 8806.15 | 21-APR-18:20 |
EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 1121.89 | 0.04 | 17-JAN-12:30 | 84396.41 | 21-APR-18:20 |
Heating:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 7.78 | 0.00 | 02-JAN-07:20 | 6341.96 | 01-JAN-17:10 |
General:Heating:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 7.78 | 0.00 | 02-JAN-07:20 | 6341.96 | 01-JAN-17:10 |
Cooling:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 1114.12 | 0.00 | 01-JAN-00:10 | 84396.41 | 21-APR-18:20 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 1114.12 | 0.00 | 01-JAN-00:10 | 84396.41 | 21-APR-18:20 |
EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 101.45 | 1.01 | 17-JAN-12:40 | 8429.19 | 21-APR-18:20 |
Heating:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 1.02 | 0.00 | 02-JAN-07:20 | 645.36 | 01-JAN-17:10 |
General:Heating:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 1.02 | 0.00 | 02-JAN-07:20 | 645.36 | 01-JAN-17:10 |
Cooling:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 100.43 | 0.00 | 01-JAN-00:10 | 8429.19 | 21-APR-18:20 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 100.43 | 0.00 | 01-JAN-00:10 | 8429.19 | 21-APR-18:20 |
EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 7165.39 | 81058.30 | 01-JAN-09:30 | 374006.04 | 09-AUG-23:10 |
Heating:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 7165.39 | 81058.30 | 01-JAN-09:30 | 374006.04 | 09-AUG-23:10 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 7165.39 | 81058.30 | 01-JAN-09:30 | 374006.04 | 09-AUG-23:10 |
PlantLoopHeatingDemand:Facility | 3871.90 | 0.00 | 01-JAN-00:40 | 2849844.21 | 09-JAN-07:10 |
PlantLoopHeatingDemand:Plant | 499.04 | 0.00 | 01-JAN-00:10 | 61546.93 | 27-FEB-12:40 |
WaterSystems:PlantLoopHeatingDemand | 499.04 | 0.00 | 01-JAN-00:10 | 61546.93 | 27-FEB-12:40 |
General:WaterSystems:PlantLoopHeatingDemand | 499.04 | 0.00 | 01-JAN-00:10 | 61546.93 | 27-FEB-12:40 |
EnergyTransfer:HVAC | 15590.64 | 1859.29 | 01-JAN-06:40 | 3677978.03 | 05-JUL-10:30 |
HeatingCoils:EnergyTransfer | 3372.86 | 0.00 | 01-JAN-00:40 | 2830054.69 | 09-JAN-07:10 |
PlantLoopHeatingDemand:HVAC | 3372.86 | 0.00 | 01-JAN-00:40 | 2830054.69 | 09-JAN-07:10 |
HeatingCoils:PlantLoopHeatingDemand | 3372.86 | 0.00 | 01-JAN-00:40 | 2830054.69 | 09-JAN-07:10 |
CoolingCoils:EnergyTransfer | 7192.76 | 1598.21 | 06-JAN-09:00 | 3677978.03 | 05-JUL-10:30 |
HeatRecoveryForHeating:EnergyTransfer | 4833.40 | 0.00 | 01-JAN-00:10 | 1259555.07 | 13-JAN-17:10 |
HeatRecoveryForCooling:EnergyTransfer | 191.62 | 0.00 | 01-JAN-00:10 | 649342.98 | 15-JUL-14:00 |
EnergyTransfer:Plant | 17018.69 | 0.00 | 01-JAN-00:40 | 8950065.10 | 05-JUL-10:30 |
LoopToLoop:EnergyTransfer | 4175.18 | 0.00 | 01-JAN-00:10 | 3022572.91 | 05-JUL-10:30 |
WaterSystems:EnergyTransfer | 499.04 | 0.00 | 01-JAN-00:10 | 61546.93 | 27-FEB-12:40 |
WaterUse:WaterSystems:EnergyTransfer | 499.04 | 0.00 | 01-JAN-00:10 | 61546.93 | 27-FEB-12:40 |
Boilers:EnergyTransfer | 3342.62 | 0.00 | 01-JAN-00:40 | 2848476.43 | 09-JAN-07:10 |
Chillers:EnergyTransfer | 4185.51 | 0.00 | 01-JAN-00:10 | 2754961.01 | 05-JUL-10:20 |
HeatRejection:EnergyTransfer | 4816.34 | 0.00 | 01-JAN-00:10 | 3163151.20 | 05-JUL-10:20 |
General:HeatRejection:EnergyTransfer | 4816.34 | 0.00 | 01-JAN-00:10 | 3163151.20 | 05-JUL-10:20 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 08:43:41
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
BASEMENT | 0.000 | 0.000 | 2.668 | -669.050 | 0.000 | 0.000 | 93.107 | 262.844 | 424.397 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -113.966 |
CORE_BOTTOM | 0.000 | 0.000 | 0.018 | -597.247 | 0.000 | 0.000 | 83.727 | 236.053 | 289.614 | 0.000 | 0.000 | 0.000 | 0.007 | 0.000 | 0.000 | 0.000 | 0.000 | -12.165 |
CORE_MID | 0.000 | 0.000 | 33.730 | -4264.841 | 0.000 | 0.000 | 866.702 | 2360.527 | 2896.128 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -1892.247 |
CORE_TOP | 0.000 | 0.000 | 32.758 | -359.487 | 0.000 | 0.000 | 89.586 | 236.053 | 289.613 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -288.522 |
PERIMETER_BOT_ZN_3 | 0.000 | 0.000 | 8.836 | -58.905 | 0.000 | 0.000 | 11.191 | 17.496 | 36.365 | 29.982 | 0.000 | 0.031 | 67.986 | 0.000 | -102.735 | 0.000 | -10.246 | 0.000 |
PERIMETER_BOT_ZN_2 | 0.000 | 0.000 | 5.925 | -63.618 | 0.000 | 0.000 | 7.269 | 11.175 | 23.435 | 62.938 | 0.000 | 0.023 | 21.855 | 0.000 | -62.253 | 0.000 | -6.750 | 0.000 |
PERIMETER_BOT_ZN_1 | 0.000 | 0.000 | 7.661 | -106.991 | 0.000 | 0.000 | 11.043 | 17.183 | 36.366 | 134.539 | 0.000 | 0.031 | 0.001 | 0.000 | -89.188 | 0.000 | -10.275 | -0.370 |
PERIMETER_BOT_ZN_4 | 0.000 | 0.000 | 1.874 | -94.950 | 0.000 | 0.000 | 7.104 | 11.149 | 23.435 | 62.937 | 0.000 | 0.020 | 65.011 | 0.000 | -69.336 | 0.000 | -7.245 | 0.000 |
PERIMETER_MID_ZN_3 | 0.000 | 0.000 | 445.026 | -396.389 | 0.000 | 0.000 | 115.953 | 174.617 | 363.654 | 310.401 | 0.000 | 0.735 | 161.170 | 0.000 | -955.202 | 0.000 | -219.964 | -0.013 |
PERIMETER_MID_ZN_2 | 0.000 | 0.000 | 259.562 | -532.213 | 0.000 | 0.000 | 54.864 | 111.597 | 234.352 | 631.803 | 0.000 | 0.512 | 0.035 | 0.000 | -589.706 | 0.000 | -148.209 | -22.563 |
PERIMETER_MID_ZN_1 | 0.000 | 0.000 | 267.810 | -937.980 | 0.000 | 0.000 | 112.680 | 171.678 | 363.660 | 1344.518 | 0.000 | 0.687 | 0.003 | 0.000 | -861.867 | 0.000 | -229.148 | -232.037 |
PERIMETER_MID_ZN_4 | 0.000 | 0.000 | 217.444 | -575.759 | 0.000 | 0.000 | 74.923 | 111.332 | 234.351 | 643.400 | 0.000 | 0.466 | 69.581 | 0.000 | -624.778 | 0.000 | -150.959 | -0.011 |
PERIMETER_TOP_ZN_3 | 0.000 | 0.000 | 75.226 | -36.914 | 0.000 | 0.000 | 11.741 | 17.460 | 36.365 | 31.660 | 0.000 | 0.089 | 0.000 | 0.000 | -92.320 | 0.000 | -26.505 | -16.803 |
PERIMETER_TOP_ZN_2 | 0.000 | 0.000 | 43.989 | -49.285 | 0.000 | 0.000 | 7.495 | 11.159 | 23.435 | 63.534 | 0.000 | 0.060 | 0.000 | 0.000 | -57.170 | 0.000 | -17.945 | -25.274 |
PERIMETER_TOP_ZN_1 | 0.000 | 0.000 | 50.839 | -85.775 | 0.000 | 0.000 | 11.417 | 17.167 | 36.366 | 135.161 | 0.000 | 0.081 | 0.001 | 0.000 | -83.094 | 0.000 | -27.542 | -54.621 |
PERIMETER_TOP_ZN_4 | 0.000 | 0.000 | 37.545 | -54.041 | 0.000 | 0.000 | 7.562 | 11.132 | 23.435 | 64.577 | 0.000 | 0.055 | 0.000 | 0.000 | -60.694 | 0.000 | -18.266 | -11.305 |
DATACENTER_BOT_ZN_6 | 0.000 | 0.000 | 0.147 | -133.832 | 0.000 | 0.000 | 0.950 | 6.628 | 153.881 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -27.774 |
DATACENTER_MID_ZN_6 | 0.000 | 0.000 | 7.775 | -1114.115 | 0.000 | 0.000 | 9.556 | 66.280 | 1538.806 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -508.302 |
DATACENTER_TOP_ZN_6 | 0.000 | 0.000 | 1.016 | -100.432 | 0.000 | 0.000 | 0.960 | 6.628 | 153.881 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -62.053 |
DATACENTER_BASEMENT_ZN_6 | 0.000 | 0.000 | 0.000 | -7165.393 | 0.000 | 0.000 | 20.370 | 74.111 | 7494.857 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -423.945 |
GROUNDFLOOR_PLENUM | 9.288 | -51.824 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.053 | 64.429 | 0.000 | 0.000 | 0.000 | -21.946 | -0.001 |
MIDFLOOR_PLENUM | 276.442 | -355.329 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.995 | 447.754 | 0.000 | 0.000 | 0.000 | -369.861 | -0.003 |
TOPFLOOR_PLENUM | 93.887 | -43.503 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.078 | 0.002 | 0.000 | 0.000 | 0.000 | -40.298 | -10.164 |
Total Facility | 379.617 | -450.656 | 1499.850 | -17397.216 | 0.000 | 0.000 | 1598.202 | 3932.267 | 14676.396 | 3515.450 | 0.000 | 3.918 | 897.835 | 0.000 | -3648.343 | 0.000 | -1305.161 | -3702.138 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | 30-MAY-04:11 | 0.00 | 0.00 | 0.00 | -120950.13 | 0.00 | 0.00 | 0.00 | 2550.13 | 13457.54 | 0.00 | 0.00 | 0.00 | 104942.45 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 30-MAY-04:11 | 0.00 | 0.00 | 0.00 | -103322.06 | 0.00 | 0.00 | 0.00 | 2290.20 | 5937.65 | 0.00 | 0.00 | 0.00 | 95094.22 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 30-MAY-04:11 | 0.00 | 0.00 | 0.00 | -923766.78 | 0.00 | 0.00 | 0.00 | 22901.98 | 59376.23 | 0.00 | 0.00 | 0.00 | 841488.57 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 05-JUL-04:12 | 0.00 | 0.00 | 0.00 | -87263.80 | 0.00 | 0.00 | 0.00 | 2290.20 | 5937.62 | 0.00 | 0.00 | 0.00 | 79035.97 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 23-JUL-16:11 | 0.00 | 0.00 | 0.00 | -17251.97 | 0.00 | 0.00 | 41.58 | 68.40 | 720.18 | 5681.22 | 0.00 | 87.32 | 10653.27 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 13-AUG-09:31 | 0.00 | 0.00 | 0.00 | -29023.49 | 0.00 | 0.00 | 19.44 | 44.08 | 464.11 | 19672.21 | 0.00 | 0.00 | 9031.07 | 0.00 | -0.00 | 0.00 | -207.43 | 0.00 |
PERIMETER_BOT_ZN_1 | 13-AUG-12:51 | 0.00 | 0.00 | 0.00 | -35989.91 | 0.00 | 0.00 | 30.09 | 68.40 | 720.19 | 28147.80 | 0.00 | 0.00 | 7248.07 | 0.00 | -0.00 | 0.00 | -224.65 | 0.00 |
PERIMETER_BOT_ZN_4 | 16-JUL-16:21 | 0.00 | 0.00 | 0.00 | -38370.60 | 0.00 | 0.00 | 13.11 | 44.08 | 464.11 | 24110.92 | 0.00 | 0.00 | 14042.45 | 0.00 | -0.00 | 0.00 | -304.08 | 0.00 |
PERIMETER_MID_ZN_3 | 23-JUL-15:21 | 0.00 | 0.00 | 0.00 | -166952.27 | 0.00 | 0.00 | 417.34 | 684.02 | 7201.84 | 62938.67 | 0.00 | 2568.42 | 93141.98 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 18-JUN-08:31 | 0.00 | 0.00 | 0.00 | -326203.17 | 0.00 | 0.00 | 170.90 | 440.81 | 4641.14 | 223417.70 | 0.00 | 0.00 | 104249.86 | 0.00 | -0.00 | 0.00 | -6717.24 | 0.00 |
PERIMETER_MID_ZN_1 | 04-SEP-11:51 | 0.00 | 0.00 | 0.00 | -386845.50 | 0.00 | 0.00 | 276.74 | 684.04 | 7201.95 | 337083.16 | 0.00 | 0.00 | 58518.59 | 0.00 | -0.00 | 0.00 | -16918.97 | 0.00 |
PERIMETER_MID_ZN_4 | 23-APR-16:31 | 0.00 | 0.00 | 0.00 | -363499.05 | 0.00 | 0.00 | 135.97 | 440.81 | 4641.11 | 265215.99 | 0.00 | 0.00 | 97169.44 | 0.00 | -0.00 | 0.00 | -4104.27 | 0.00 |
PERIMETER_TOP_ZN_3 | 23-JUL-15:21 | 0.00 | 0.00 | 0.00 | -20844.69 | 0.00 | 0.00 | 39.96 | 68.40 | 720.18 | 6176.89 | 0.00 | 271.66 | 13567.58 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 18-JUN-08:41 | 0.00 | 0.00 | 0.00 | -32248.55 | 0.00 | 0.00 | 17.75 | 44.08 | 464.11 | 21930.31 | 0.00 | 0.00 | 10608.24 | 0.00 | -0.00 | 0.00 | -815.94 | 0.00 |
PERIMETER_TOP_ZN_1 | 04-SEP-13:41 | 0.00 | 0.00 | 0.00 | -39794.67 | 0.00 | 0.00 | 28.60 | 68.40 | 720.19 | 25425.86 | 0.00 | 0.00 | 15500.37 | 0.00 | -0.00 | 0.00 | -1948.76 | 0.00 |
PERIMETER_TOP_ZN_4 | 23-APR-16:41 | 0.00 | 0.00 | 0.00 | -37378.12 | 0.00 | 0.00 | 14.04 | 44.08 | 464.11 | 25808.27 | 0.00 | 0.00 | 11530.88 | 0.00 | -0.00 | 0.00 | -483.25 | 0.00 |
DATACENTER_BOT_ZN_6 | 21-APR-18:20 | 0.00 | 0.00 | 0.00 | -8805.52 | 0.00 | 0.00 | 10.62 | 192.90 | 7794.42 | 0.00 | 0.00 | 0.00 | 807.58 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 21-APR-18:20 | 0.00 | 0.00 | 0.00 | -84390.29 | 0.00 | 0.00 | 106.16 | 1929.04 | 77944.22 | 0.00 | 0.00 | 0.00 | 4410.87 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 21-APR-18:20 | 0.00 | 0.00 | 0.00 | -8428.58 | 0.00 | 0.00 | 10.62 | 192.90 | 7794.42 | 0.00 | 0.00 | 0.00 | 430.64 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 09-AUG-23:03 | 0.00 | 0.00 | 0.00 | -378392.21 | 0.00 | 0.00 | 0.00 | 359.47 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -1599.78 |
GROUNDFLOOR_PLENUM | 24-JUL-05:02 | 0.00 | -11106.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11214.72 | 0.00 | -0.00 | 0.00 | -108.03 | 0.00 |
MIDFLOOR_PLENUM | 10-FEB-04:01 | 0.00 | -159320.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 205680.87 | 0.00 | -0.00 | 0.00 | -46360.09 | 0.00 |
TOPFLOOR_PLENUM | 30-JUN-14:50 | 0.00 | -20930.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 357.43 | 20572.86 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 24-JUL-04:11 | 0.00 | 52461.74 | 0.00 | -2022934.61 | 0.00 | 0.00 | 0.00 | 42872.09 | 469008.02 | 0.00 | 0.00 | 0.00 | 1557928.48 | 0.00 | -76409.46 | 0.00 | -22926.26 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | 29-JUL-16:01 | 0.00 | 0.00 | 18148.10 | 0.00 | 0.00 | 0.00 | 520.12 | 1274.92 | 13457.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -33400.69 |
CORE_BOTTOM | 02-JAN-05:01 | 0.00 | 0.00 | 17768.49 | 0.00 | 0.00 | 0.00 | 0.00 | 2290.20 | 5937.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -25996.34 |
CORE_MID | 02-JAN-04:01 | 0.00 | 0.00 | 622926.62 | 0.00 | 0.00 | 0.00 | 0.00 | 11449.71 | 59376.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -693752.55 |
CORE_TOP | 09-JAN-04:11 | 0.00 | 0.00 | 84540.99 | 0.00 | 0.00 | 0.00 | 0.00 | 1144.97 | 5937.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -91623.58 |
PERIMETER_BOT_ZN_3 | 01-JAN-08:61 | 0.00 | 0.00 | 15347.44 | 0.00 | 0.00 | 0.00 | 88.57 | 143.76 | 720.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -8684.01 | 0.00 | -1368.80 | -6247.13 |
PERIMETER_BOT_ZN_2 | 02-JAN-04:01 | 0.00 | 0.00 | 18660.48 | 0.00 | 0.00 | 0.00 | 0.00 | 92.65 | 480.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -4805.70 | 0.00 | -739.22 | -13688.67 |
PERIMETER_BOT_ZN_1 | 09-JAN-04:21 | 0.00 | 0.00 | 26598.82 | 0.00 | 0.00 | 0.00 | 0.00 | 143.77 | 745.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -10185.50 | 0.00 | -1069.33 | -16233.32 |
PERIMETER_BOT_ZN_4 | 09-JAN-04:01 | 0.00 | 0.00 | 17489.80 | 0.00 | 0.00 | 0.00 | 0.00 | 92.65 | 480.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -6853.32 | 0.00 | -627.45 | -10582.14 |
PERIMETER_MID_ZN_3 | 24-DEC-07:02 | 0.00 | 0.00 | 157845.07 | 0.00 | 0.00 | 0.00 | 920.07 | 1437.63 | 7201.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -97478.28 | 0.00 | -34844.26 | -35082.07 |
PERIMETER_MID_ZN_2 | 24-DEC-07:02 | 0.00 | 0.00 | 244591.31 | 0.00 | 0.00 | 0.00 | 593.30 | 926.46 | 4641.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -62881.21 | 0.00 | -23746.50 | -164124.51 |
PERIMETER_MID_ZN_1 | 24-DEC-07:02 | 0.00 | 0.00 | 297455.76 | 0.00 | 0.00 | 0.00 | 917.69 | 1437.66 | 7201.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -94708.55 | 0.00 | -35460.70 | -176843.82 |
PERIMETER_MID_ZN_4 | 24-DEC-07:02 | 0.00 | 0.00 | 247465.81 | 0.00 | 0.00 | 0.00 | 590.01 | 926.46 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -65590.04 | 0.00 | -23915.38 | -164117.97 |
PERIMETER_TOP_ZN_3 | 13-FEB-04:11 | 0.00 | 0.00 | 20362.08 | 0.00 | 0.00 | 0.00 | 0.00 | 143.76 | 745.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -7944.82 | 0.00 | -5896.68 | -7409.90 |
PERIMETER_TOP_ZN_2 | 13-FEB-04:11 | 0.00 | 0.00 | 27010.17 | 0.00 | 0.00 | 0.00 | 0.00 | 92.65 | 480.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -5112.16 | 0.00 | -4003.36 | -18467.77 |
PERIMETER_TOP_ZN_1 | 13-FEB-04:11 | 0.00 | 0.00 | 33360.54 | 0.00 | 0.00 | 0.00 | 0.00 | 143.77 | 745.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -7707.18 | 0.00 | -5996.58 | -20546.12 |
PERIMETER_TOP_ZN_4 | 13-FEB-04:11 | 0.00 | 0.00 | 29272.65 | 0.00 | 0.00 | 0.00 | 0.00 | 92.65 | 480.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -5390.88 | 0.00 | -4062.69 | -20392.19 |
DATACENTER_BOT_ZN_6 | 01-JAN-17:50 | 0.00 | 0.00 | 637.62 | 0.00 | 0.00 | 0.00 | 5.36 | 32.15 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -2623.75 |
DATACENTER_MID_ZN_6 | 01-JAN-17:10 | 0.00 | 0.00 | 6341.98 | 0.00 | 0.00 | 0.00 | 68.82 | 321.53 | 19486.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -26218.38 |
DATACENTER_TOP_ZN_6 | 24-JAN-23:35 | 0.00 | 0.00 | 649.24 | 0.00 | 0.00 | 0.00 | 5.90 | 32.15 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -2635.90 |
DATACENTER_BASEMENT_ZN_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 26-MAR-15:22 | 17766.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -922.11 | -16844.47 |
MIDFLOOR_PLENUM | 02-JAN-06:12 | 239671.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -5860.62 | -233810.83 |
TOPFLOOR_PLENUM | 09-JAN-05:42 | 39090.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -3893.83 | -35196.36 |
Total Facility | 02-JAN-06:01 | 119327.97 | 81496.20 | 1707007.12 | -81496.20 | 0.00 | 0.00 | 23498.52 | 42872.09 | 261414.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -278313.39 | 0.00 | -22263.71 | -1853543.54 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 08:43:41
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
VAV_BOT WITH REHEAT | 12.8566 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 10.7174 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_MID WITH REHEAT | 124.7766 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 100.0875 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_TOP WITH REHEAT | 12.7586 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 11.0010 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
CAV_BAS | 6.2471 | 0.0000 | 149.6021 | 1.0000 | Calculated from schedules | 1.2002 | 6.2471 | 0.1921 | 1.0000 | Not calculated | 1.2002 | 0.1921 | ||
AIRLOOP DATACENTER BASEMENT | 22.3518 | 0.0000 | 42.1814 | 1.0000 | Calculated from schedules | 0.3384 | 22.3537 | 0.0151 | 1.0000 | Not calculated | 0.3384 | 0.0151 | ||
AIRLOOP DATACENTER BOT | 0.5393 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.5393 | 0.0290 | 1.0000 | Not calculated | 0.0156 | 0.0290 | ||
AIRLOOP DATACENTER MID | 5.1946 | 0.0000 | 19.4861 | 1.0000 | Calculated from schedules | 0.1563 | 5.1946 | 0.0301 | 1.0000 | Not calculated | 0.1563 | 0.0301 | ||
AIRLOOP DATACENTER TOP | 0.5264 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.5264 | 0.0297 | 1.0000 | Not calculated | 0.0156 | 0.0297 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
VAV_BOT WITH REHEAT | 6.4283 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 3.3088 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_MID WITH REHEAT | 62.3883 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 32.7821 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_TOP WITH REHEAT | 6.3793 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 3.3938 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
CAV_BAS | 6.2471 | 0.0000 | 149.6021 | 1.0000 | Calculated from schedules | 1.2002 | 6.2471 | 1.0000 | 1.0000 | Not calculated | 1.2002 | 0.1921 | ||
AIRLOOP DATACENTER BASEMENT | 22.3518 | 0.0000 | 42.1814 | 1.0000 | Calculated from schedules | 0.3384 | 22.3518 | 1.0000 | 1.0000 | Not calculated | 0.3384 | 0.0151 | ||
AIRLOOP DATACENTER BOT | 0.5393 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.5393 | 1.0000 | 1.0000 | Not calculated | 0.0156 | 0.0290 | ||
AIRLOOP DATACENTER MID | 5.1946 | 0.0000 | 19.4861 | 1.0000 | Calculated from schedules | 0.1563 | 5.1946 | 1.0000 | 1.0000 | Not calculated | 0.1563 | 0.0301 | ||
AIRLOOP DATACENTER TOP | 0.5264 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.5264 | 1.0000 | 1.0000 | Not calculated | 0.0156 | 0.0297 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
BASEMENT | CAV_BAS | 0.000000 | 149.6021 | 0.000432 | 2779.43 | 1.2002 | 1.0000 | 1.2002 | 1.000 | 1.2002 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | 0.000000 | 134.3532 | 0.000432 | 2496.12 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_MID | VAV_MID WITH REHEAT | 0.000000 | 1343.5320 | 0.000432 | 24961.20 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_TOP | VAV_TOP WITH REHEAT | 0.000000 | 134.3532 | 0.000432 | 2496.12 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | 0.000000 | 16.8694 | 0.000432 | 313.41 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | 0.000000 | 16.8698 | 0.000432 | 313.42 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | 0.000000 | 168.6939 | 0.000432 | 3134.13 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | 0.000000 | 108.7127 | 0.000432 | 2019.75 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | 0.000000 | 168.6975 | 0.000432 | 3134.20 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | 0.000000 | 108.7127 | 0.000432 | 2019.75 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | 0.000000 | 16.8694 | 0.000432 | 313.41 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | 0.000000 | 16.8698 | 0.000432 | 313.42 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | 0.000000 | 1.9486 | 0.000432 | 36.20 | 0.0156 | 1.0000 | 0.0156 | 1.000 | 0.0156 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | 0.000000 | 19.4861 | 0.000432 | 362.03 | 0.1563 | 1.0000 | 0.1563 | 1.000 | 0.1563 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | 0.000000 | 1.9486 | 0.000432 | 36.20 | 0.0156 | 1.0000 | 0.0156 | 1.000 | 0.0156 |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | 0.000000 | 42.1814 | 0.000432 | 783.68 | 0.3384 | 1.0000 | 0.3384 | 1.000 | 0.3384 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
VAV_BOT WITH REHEAT | 0.00 | 0.000432 | 3526.9033 | 0.0000 | 0.0000 | 0.0000 | |
VAV_MID WITH REHEAT | 0.00 | 0.000432 | 35269.0328 | 0.0000 | 0.0000 | 0.0000 | |
VAV_TOP WITH REHEAT | 0.00 | 0.000432 | 3526.9033 | 0.0000 | 0.0000 | 0.0000 | |
CAV_BAS | 0.000000 | 149.60 | 0.000432 | 2779.4266 | 1.2002 | 1.2002 | 1.2002 |
AIRLOOP DATACENTER BASEMENT | 0.000000 | 42.18 | 0.000432 | 783.6794 | 0.3384 | 0.3384 | 0.3384 |
AIRLOOP DATACENTER BOT | 0.000000 | 1.95 | 0.000432 | 36.2027 | 0.0156 | 0.0156 | 0.0156 |
AIRLOOP DATACENTER MID | 0.000000 | 19.49 | 0.000432 | 362.0274 | 0.1563 | 0.1563 | 0.1563 |
AIRLOOP DATACENTER TOP | 0.000000 | 1.95 | 0.000432 | 36.2027 | 0.0156 | 0.0156 | 0.0156 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | CAV_BAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 6.2471 | 6.2471 | 6.2471 | No | 1.2002 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 6.4420 | 6.4420 | 1.9906 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 60.5948 | 60.5948 | 19.5115 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 5.9559 | 5.9559 | 2.0012 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.0707 | 1.0707 | 0.2495 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.5641 | 1.5641 | 0.3128 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.9084 | 1.9084 | 0.3817 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.8713 | 1.8713 | 0.3743 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 10.0977 | 10.0977 | 2.4537 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 16.7122 | 16.7122 | 3.3424 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 19.6292 | 19.6292 | 3.9258 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 17.7427 | 17.7427 | 3.5485 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.2321 | 1.2321 | 0.2785 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.6688 | 1.6688 | 0.3338 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.0593 | 2.0593 | 0.4119 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.8424 | 1.8424 | 0.3685 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.5393 | 0.5393 | 0.5393 | No | 0.0156 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 5.1946 | 5.1946 | 5.1946 | No | 0.1563 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.5264 | 0.5264 | 0.5264 | No | 0.0156 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 22.3518 | 22.3518 | 22.3518 | No | 0.3384 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
VAV_BOT WITH REHEAT | 12.8566 | 10.7174 | 12.8566 | 3.3088 | 0.0000 | 1.0000 |
VAV_MID WITH REHEAT | 124.7766 | 100.0875 | 124.7766 | 32.7821 | 0.0000 | 1.0000 |
VAV_TOP WITH REHEAT | 12.7586 | 11.0010 | 12.7586 | 3.3938 | 0.0000 | 1.0000 |
CAV_BAS | 6.2471 | 6.2471 | 6.2471 | 6.2471 | 1.2002 | 1.0000 |
AIRLOOP DATACENTER BASEMENT | 22.3518 | 22.3537 | 22.3518 | 22.3518 | 0.3384 | 1.0000 |
AIRLOOP DATACENTER BOT | 0.5393 | 0.5393 | 0.5393 | 0.5393 | 0.0156 | 1.0000 |
AIRLOOP DATACENTER MID | 5.1946 | 5.1946 | 5.1946 | 5.1946 | 0.1563 | 1.0000 |
AIRLOOP DATACENTER TOP | 0.5264 | 0.5264 | 0.5264 | 0.5264 | 0.0156 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | CAV_BAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 6.2471 | 6.2471 | 6.2471 | No | 1.2002 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 3.2210 | 3.2210 | 1.9906 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 30.2974 | 30.2974 | 19.5115 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.9779 | 2.9779 | 2.0012 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5354 | 0.5354 | 0.2495 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7821 | 0.7821 | 0.3128 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.9542 | 0.9542 | 0.3817 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.9357 | 0.9357 | 0.3743 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 5.0488 | 5.0488 | 2.4537 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 8.3561 | 8.3561 | 3.3424 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 9.8146 | 9.8146 | 3.9258 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 8.8713 | 8.8713 | 3.5485 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6161 | 0.6161 | 0.2785 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8344 | 0.8344 | 0.3338 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.0297 | 1.0297 | 0.4119 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.9212 | 0.9212 | 0.3685 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.5393 | 0.5393 | 0.5393 | No | 0.0156 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 5.1946 | 5.1946 | 5.1946 | No | 0.1563 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.5264 | 0.5264 | 0.5264 | No | 0.0156 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 22.3518 | 22.3518 | 22.3518 | No | 0.3384 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
VAV_BOT WITH REHEAT | 6.4283 | 3.3088 | 3.3088 | 3.3088 | 0.0000 | 1.0000 |
VAV_MID WITH REHEAT | 62.3883 | 32.7821 | 32.7821 | 32.7821 | 0.0000 | 1.0000 |
VAV_TOP WITH REHEAT | 6.3793 | 3.3938 | 3.3938 | 3.3938 | 0.0000 | 1.0000 |
CAV_BAS | 6.2471 | 6.2471 | 6.2471 | 6.2471 | 1.2002 | 1.0000 |
AIRLOOP DATACENTER BASEMENT | 22.3518 | 22.3518 | 22.3518 | 22.3518 | 0.3384 | 1.0000 |
AIRLOOP DATACENTER BOT | 0.5393 | 0.5393 | 0.5393 | 0.5393 | 0.0156 | 1.0000 |
AIRLOOP DATACENTER MID | 5.1946 | 5.1946 | 5.1946 | 5.1946 | 0.1563 | 1.0000 |
AIRLOOP DATACENTER TOP | 0.5264 | 0.5264 | 0.5264 | 0.5264 | 0.0156 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 08:43:41
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** International Falls Intl Ap MN USA TMY3 WMO#=727470 |
Total gross floor area [m2] | 46320.38 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
BASEMENT | 2779.43 | 2779.43 | 0.00 | 113.98 |
CORE_BOTTOM | 2496.12 | 2496.12 | 0.00 | 113.98 |
CORE_MID | 2496.12 | 2496.12 | 0.00 | 113.98 |
CORE_TOP | 2496.12 | 2496.12 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_3 | 313.41 | 313.41 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_2 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_1 | 313.42 | 313.42 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_4 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_MID_ZN_3 | 313.41 | 313.41 | 0.00 | 113.98 |
PERIMETER_MID_ZN_2 | 201.98 | 201.98 | 0.00 | 96.54 |
PERIMETER_MID_ZN_1 | 313.42 | 313.42 | 0.00 | 113.98 |
PERIMETER_MID_ZN_4 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_3 | 313.41 | 313.41 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_2 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_1 | 313.42 | 313.42 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_4 | 201.98 | 201.98 | 0.00 | 113.98 |
DATACENTER_BOT_ZN_6 | 36.20 | 36.20 | 0.00 | 113.98 |
DATACENTER_MID_ZN_6 | 36.20 | 36.20 | 0.00 | 113.98 |
DATACENTER_TOP_ZN_6 | 36.20 | 36.20 | 0.00 | 113.98 |
DATACENTER_BASEMENT_ZN_6 | 783.68 | 783.68 | 0.00 | 113.98 |
GROUNDFLOOR_PLENUM | 3563.11 | 3563.11 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 3563.11 | 3563.11 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 3563.11 | 3563.11 | 0.00 | 0.00 |
Totals | 46320.38 | 46320.38 | 0.00 |
Data | |
Number of hours heating loads not met | 237.33 |
Number of hours cooling loads not met | 314.67 |
Number of hours not met | 551.67 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler | 0.00 | 0.00 | 4384.93 | 3461431.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 1497.42 | 556452.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 3932.27 | 385834.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 698.41 | 57580.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 5334.97 | 305206.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- DataCenterPlugLoads | 9341.42 | 473165.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Transformer | 80.18 | 5057.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLift | 1848.78 | 113101.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLightsFan | 5.83 | 376.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 2526.83 | 331054.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 381.74 | 69323.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- General | 477.25 | 89285.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- General | 1706.80 | 100000.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- General | 56.49 | 6524.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 0.00 | 0.00 | 892.88 | 90000.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 14676.40 | 27888.40 |
Natural Gas | 0.00 | 5277.81 |
Additional | 0.00 | 0.00 |
Total | 14676.40 | 33166.21 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 84.89 |
Space Heating | 0.00 |
Space Cooling | 32.33 |
Fans (All) | 54.55 |
Service Water Heating | 0.00 |
Receptacle Equipment | 316.85 |
Miscellaneous (All) | 602.08 |
Subtotal | 602.08 |
Natural Gas [MJ/m2] | |
Space Heating | 94.67 |
Service Water Heating | 19.28 |
Miscellaneous (All) | 113.94 |
Subtotal | 113.94 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 11.86 |
Space Heating | 13.22 |
Space Cooling | 4.51 |
Fans (All) | 7.62 |
Service Water Heating | 2.69 |
Receptacle Equipment | 44.25 |
Miscellaneous | 15.85 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 4472. | 4472. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 6752. | 8760. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 6828. | 8760. |
ALWAYS_OFF | 0. | 0. |
LTG_SCH_OFFICE | 2625. | 8760. |
LTG_SCH_DATACENTER | 2921. | 8760. |
EXTERIOR_LIGHT_SCH | 4380. | 4380. |
BLDG_EQUIP_SCH | 4049. | 8760. |
DATACENTER_EQUIP_SCH | 5478. | 8760. |
BLDG_OCC_SCH | 2528. | 5992. |
BLDG_OCC_SCH_W_SB | 1878. | 5056. |
BLDG_OCC_SCH_WO_SB | 2557. | 5992. |
BLDG_ELEVATORS | 2270. | 8760. |
ELEV_LIGHT_FAN_SCH_24_7 | 8760. | 8760. |
ELEV_LIGHT_FAN_SCH_ADD_DF | 2154. | 8760. |
BLDG_SWH_SCH | 1474. | 6570. |
WORK_EFF_SCH | 0. | 0. |
INFIL_SCH | 3976. | 3976. |
INFIL_SCH_PNNL | 5172. | 8760. |
INFIL_HALF_ON_SCH | 6368. | 8760. |
FAN_SCH | 8760. | 8760. |
REHEATCOILAVAILSCHED | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
MINOA_MOTORIZEDDAMPER_SCHED | 4472. | 4472. |
MINOA_SCHED | 8760. | 8760. |
CORE_BOTTOM SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_BOTTOM SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_MID SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_MID SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_TOP SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_TOP SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
SUPPLYFANSCH | 8760. | 8760. |
PERIMETER_MID_ZN_2_MDP_SCH | 1565. | 7824. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
HTGSETP_DC_SCH | DATACENTER COOLING SETPOINTS DUAL SP CONTROL | January | 18.00 | 365 | 18.00 | 365 |
CLGSETP_DC_SCH | DATACENTER COOLING SETPOINTS DUAL SP CONTROL | July | 27.00 | 365 | 27.00 | 365 |
HTGSETP_SCH_YES_OPTIMUM | CORE_BOTTOM DUAL SP CONTROL | January | 21.00 | 365 | 15.60 | 365 |
CLGSETP_SCH_YES_OPTIMUM | CORE_BOTTOM DUAL SP CONTROL | July | 24.00 | 365 | 26.70 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:43:41
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
BASEMENT | 8373.83 | 386.17 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 8746.17 | 13.83 | 0.00 | 0.00 | 0.00 |
CORE_MID | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 8749.83 | 10.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 8726.83 | 33.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 8713.33 | 46.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 8408.00 | 352.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 8752.50 | 7.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 8713.00 | 47.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 8706.67 | 53.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 8649.17 | 110.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 8750.67 | 9.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 8712.83 | 47.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 8710.50 | 49.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 8661.83 | 98.17 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 8132.50 | 627.50 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 8117.33 | 642.67 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 8107.33 | 652.67 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 7035.83 | 1713.00 | 11.17 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 8735.00 | 25.00 | 0.00 | 0.00 | 0.00 |
Min | 7035.83 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 1713.00 | 11.17 | 0.00 | 0.00 |
Average | 8545.36 | 214.16 | 0.49 | 0.00 | 0.00 |
Sum | 196543.17 | 4925.67 | 11.17 | 0.00 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
BASEMENT | 367589.33 | 1026.67 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 330794.00 | 19.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 330813.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 330813.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 18354.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 1908.17 | 359.83 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 1899.83 | 368.17 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 1897.00 | 371.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 82327.67 | 20824.00 | 243.33 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 367589.33 | 20824.00 | 243.33 | 0.00 | 0.00 |
Average | 79325.70 | 998.64 | 10.58 | 0.00 | 0.00 |
Sum | 1824491.00 | 22968.67 | 243.33 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
BASEMENT | 7833.17 | 926.83 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 8288.00 | 472.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 8303.33 | 456.67 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 8353.33 | 406.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 8438.50 | 321.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 8603.17 | 156.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 8478.33 | 281.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 8142.50 | 617.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 8461.17 | 298.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 8479.33 | 280.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 8392.33 | 367.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 8329.50 | 430.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 8488.83 | 271.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 8492.00 | 268.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 8425.50 | 334.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 8365.83 | 394.17 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 8464.50 | 295.50 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 8449.67 | 310.33 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 8446.33 | 313.67 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 7229.67 | 1529.33 | 1.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 8276.83 | 483.17 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 8357.00 | 403.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 8358.67 | 401.33 | 0.00 | 0.00 | 0.00 |
Min | 7229.67 | 156.83 | 0.00 | 0.00 | 0.00 |
Max | 8603.17 | 1529.33 | 1.00 | 0.00 | 0.00 |
Average | 8324.24 | 435.72 | 0.04 | 0.00 | 0.00 |
Sum | 191457.50 | 10021.50 | 1.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
BASEMENT | 361500.67 | 7115.33 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 329677.67 | 1135.33 | 0.00 | 0.00 | 0.00 |
CORE_MID | 329818.17 | 994.83 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 329899.00 | 914.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 38874.33 | 50.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 24892.33 | 16.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 38879.67 | 45.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 24892.33 | 16.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 38879.50 | 45.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 18345.67 | 8.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 38885.00 | 40.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 24894.00 | 15.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 38889.83 | 35.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 24894.00 | 15.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 38887.50 | 37.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 24895.67 | 13.33 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 2078.00 | 190.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 2068.33 | 199.67 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 2066.50 | 201.50 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 84466.33 | 18924.67 | 4.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 361500.67 | 18924.67 | 4.00 | 0.00 | 0.00 |
Average | 79029.76 | 1304.98 | 0.17 | 0.00 | 0.00 |
Sum | 1817684.50 | 30014.50 | 4.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:43:41
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:43:41
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 0.00 | 8760.00 | 0.00 |
Average | 0.00 | 0.00 | 4570.43 | 0.00 |
Sum | 0.00 | 0.00 | 105120.00 | 0.00 |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 18354.00 | 0.00 |
PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 24909.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 0.00 | 38925.00 | 0.00 |
Average | 0.00 | 0.00 | 16367.35 | 0.00 |
Sum | 0.00 | 0.00 | 376449.00 | 0.00 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -16.89 |
February | -11.56 |
March | -6.15 |
April | 3.968 |
May | 13.433 |
June | 18.029 |
July | 19.667 |
August | 17.942 |
September | 12.293 |
October | 5.424 |
November | -2.00 |
December | -14.64 |
Annual Sum or Average | 3.363 |
Minimum of Months | -16.89 |
Maximum of Months | 19.667 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Environment
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -16.89 |
February | -11.56 |
March | -6.15 |
April | 3.968 |
May | 13.433 |
June | 18.029 |
July | 19.667 |
August | 17.942 |
September | 12.293 |
October | 5.424 |
November | -2.00 |
December | -14.64 |
Annual Sum or Average | 3.363 |
Minimum of Months | -16.89 |
Maximum of Months | 19.667 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2013
For: Environment
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -16.89 |
February | -11.56 |
March | -6.15 |
April | 3.968 |
May | 13.433 |
June | 18.029 |
July | 19.667 |
August | 17.942 |
September | 12.293 |
October | 5.424 |
November | -2.00 |
December | -14.64 |
Annual Sum or Average | 3.363 |
Minimum of Months | -16.89 |
Maximum of Months | 19.667 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -16.89 |
February | -11.56 |
March | -6.15 |
April | 3.968 |
May | 13.433 |
June | 18.029 |
July | 19.667 |
August | 17.942 |
September | 12.293 |
October | 5.424 |
November | -2.00 |
December | -14.64 |
Annual Sum or Average | 3.363 |
Minimum of Months | -16.89 |
Maximum of Months | 19.667 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICELARGE
For: Environment
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -16.89 |
February | -11.56 |
March | -6.15 |
April | 3.968 |
May | 13.433 |
June | 18.029 |
July | 19.667 |
August | 17.942 |
September | 12.293 |
October | 5.424 |
November | -2.00 |
December | -14.64 |
Annual Sum or Average | 3.363 |
Minimum of Months | -16.89 |
Maximum of Months | 19.667 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -16.89 |
February | -11.56 |
March | -6.15 |
April | 3.968 |
May | 13.433 |
June | 18.029 |
July | 19.667 |
August | 17.942 |
September | 12.293 |
October | 5.424 |
November | -2.00 |
December | -14.64 |
Annual Sum or Average | 3.363 |
Minimum of Months | -16.89 |
Maximum of Months | 19.667 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -16.89 |
February | -11.56 |
March | -6.15 |
April | 3.968 |
May | 13.433 |
June | 18.029 |
July | 19.667 |
August | 17.942 |
September | 12.293 |
October | 5.424 |
November | -2.00 |
December | -14.64 |
Annual Sum or Average | 3.363 |
Minimum of Months | -16.89 |
Maximum of Months | 19.667 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 7
For: Environment
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -16.89 |
February | -11.56 |
March | -6.15 |
April | 3.968 |
May | 13.433 |
June | 18.029 |
July | 19.667 |
August | 17.942 |
September | 12.293 |
October | 5.424 |
November | -2.00 |
December | -14.64 |
Annual Sum or Average | 3.363 |
Minimum of Months | -16.89 |
Maximum of Months | 19.667 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_MN_INTERNATIONALFALLS
For: Environment
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -16.89 |
February | -11.56 |
March | -6.15 |
April | 3.968 |
May | 13.433 |
June | 18.029 |
July | 19.667 |
August | 17.942 |
September | 12.293 |
October | 5.424 |
November | -2.00 |
December | -14.64 |
Annual Sum or Average | 3.363 |
Minimum of Months | -16.89 |
Maximum of Months | 19.667 |
Report: ZoneCoolingSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.391876E+11 | 110760.34 | 20-JAN-05:01 | -6.2 | -6.8 | 0.539427E+10 | 7507.78 | 11-JAN-10:20 | -6.2 | -6.8 |
February | 0.411824E+11 | 112601.41 | 06-FEB-05:01 | -20.1 | -20.4 | 0.508793E+10 | 7803.19 | 01-FEB-10:09 | -20.1 | -20.4 |
March | 0.523341E+11 | 115512.76 | 20-MAR-03:01 | -7.4 | -7.7 | 0.612706E+10 | 7501.06 | 15-MAR-13:09 | -7.4 | -7.7 |
April | 0.542637E+11 | 117458.25 | 17-APR-03:02 | -0.7 | -2.4 | 0.544752E+10 | 7499.16 | 07-APR-09:09 | -0.7 | -2.4 |
May | 0.603712E+11 | 120951.70 | 30-MAY-04:11 | 10.60 | 8.25 | 0.590116E+10 | 7499.15 | 24-MAY-09:20 | 10.60 | 8.25 |
June | 0.630804E+11 | 119723.61 | 12-JUN-04:12 | 12.03 | 11.73 | 0.588216E+10 | 7499.26 | 06-JUN-13:30 | 12.03 | 11.73 |
July | 0.649060E+11 | 118125.38 | 10-JUL-04:12 | 8.33 | 7.93 | 0.547892E+10 | 7830.37 | 05-JUL-13:09 | 8.33 | 7.93 |
August | 0.720007E+11 | 116914.87 | 02-AUG-04:12 | 10.40 | 9.44 | 0.613858E+10 | 7499.27 | 10-AUG-13:00 | 19.40 | 16.96 |
September | 0.612814E+11 | 117745.01 | 05-SEP-04:12 | 6.33 | 5.88 | 0.545256E+10 | 7499.08 | 14-SEP-09:09 | 13.27 | 10.50 |
October | 0.597945E+11 | 120880.71 | 10-OCT-04:11 | 2.57 | 0.01 | 0.566934E+10 | 7499.26 | 25-OCT-09:39 | 2.20 | 2.03 |
November | 0.534767E+11 | 119997.58 | 13-NOV-04:01 | -8.2 | -8.9 | 0.561012E+10 | 7499.20 | 29-NOV-10:09 | -10.3 | -11.0 |
December | 0.471707E+11 | 113893.82 | 18-DEC-05:01 | -15.2 | -16.2 | 0.539050E+10 | 7567.24 | 18-DEC-16:00 | -23.5 | -24.0 |
Annual Sum or Average | 0.669049E+12 | 0.675801E+11 | ||||||||
Minimum of Months | 0.391876E+11 | 110760.34 | -20.1 | -20.4 | 0.508793E+10 | 7499.08 | -23.5 | -24.0 | ||
Maximum of Months | 0.720007E+11 | 120951.70 | 12.03 | 11.73 | 0.613858E+10 | 7830.37 | 19.40 | 16.96 |
Report: ZoneCoolingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.303929E+11 | 52893.89 | 20-JAN-15:30 | -5.3 | -7.0 | 0.485879E+10 | 6755.47 | 31-JAN-10:00 | -15.6 | -16.0 |
February | 0.328558E+11 | 87411.71 | 09-FEB-06:01 | -3.2 | -4.5 | 0.456057E+10 | 6905.69 | 10-FEB-10:30 | -17.8 | -18.4 |
March | 0.457720E+11 | 90915.16 | 28-MAR-04:11 | 2.03 | 0.68 | 0.548746E+10 | 6955.70 | 23-MAR-09:30 | 2.03 | 0.68 |
April | 0.522400E+11 | 96091.29 | 24-APR-04:12 | 4.40 | 3.41 | 0.488360E+10 | 6886.58 | 05-APR-09:00 | 4.40 | 3.41 |
May | 0.557824E+11 | 103336.81 | 30-MAY-04:11 | 10.60 | 8.25 | 0.528630E+10 | 6734.88 | 24-MAY-09:09 | 10.60 | 8.25 |
June | 0.615916E+11 | 100740.23 | 26-JUN-04:13 | 16.87 | 15.70 | 0.526939E+10 | 6734.90 | 13-JUN-09:00 | 16.87 | 15.70 |
July | 0.675618E+11 | 98252.34 | 17-JUL-04:12 | 10.97 | 10.53 | 0.490183E+10 | 7146.78 | 05-JUL-13:09 | 10.97 | 10.53 |
August | 0.735137E+11 | 96090.66 | 17-AUG-04:12 | 15.00 | 14.30 | 0.549719E+10 | 6734.81 | 10-AUG-13:30 | 15.00 | 14.30 |
September | 0.515159E+11 | 100880.99 | 05-SEP-04:12 | 6.33 | 5.88 | 0.488149E+10 | 6734.81 | 14-SEP-09:09 | 13.27 | 10.50 |
October | 0.479956E+11 | 96391.62 | 23-OCT-04:12 | 5.60 | 4.25 | 0.507440E+10 | 6820.58 | 30-OCT-09:30 | -1.9 | -3.3 |
November | 0.416627E+11 | 90311.77 | 21-NOV-05:11 | 9.60 | 9.49 | 0.501911E+10 | 6886.92 | 10-NOV-10:20 | 9.60 | 9.49 |
December | 0.363624E+11 | 88082.06 | 06-DEC-06:01 | -0.8 | -0.8 | 0.486094E+10 | 6894.09 | 01-DEC-10:00 | -0.8 | -0.8 |
Annual Sum or Average | 0.597247E+12 | 0.605811E+11 | ||||||||
Minimum of Months | 0.303929E+11 | 52893.89 | -5.3 | -7.0 | 0.456057E+10 | 6734.81 | -17.8 | -18.4 | ||
Maximum of Months | 0.735137E+11 | 103336.81 | 16.87 | 15.70 | 0.549719E+10 | 7146.78 | 16.87 | 15.70 |
Report: ZoneCoolingSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.227263E+11 | 20501.88 | 06-JAN-09:00 | -35.6 | -35.7 | 0.418533E+10 | 6557.67 | 27-JAN-14:00 | -14.4 | -15.6 |
February | 0.235855E+11 | 26874.10 | 10-FEB-16:37 | -12.2 | -13.6 | 0.402589E+10 | 6734.75 | 10-FEB-14:39 | -12.2 | -13.6 |
March | 0.298063E+11 | 41142.56 | 31-MAR-09:30 | 0.85 | -1.4 | 0.514032E+10 | 6810.34 | 31-MAR-09:30 | 0.85 | -1.4 |
April | 0.329908E+11 | 81195.10 | 14-APR-05:03 | 2.12 | 1.45 | 0.477770E+10 | 7137.44 | 27-APR-09:20 | -1.5 | -3.1 |
May | 0.450006E+11 | 92391.94 | 30-MAY-04:11 | 10.60 | 8.25 | 0.527018E+10 | 6740.73 | 08-MAY-09:30 | 10.60 | 8.25 |
June | 0.490378E+11 | 88047.82 | 28-JUN-04:12 | 15.20 | 14.63 | 0.526104E+10 | 6734.85 | 13-JUN-09:00 | 15.20 | 14.63 |
July | 0.498466E+11 | 88518.67 | 25-JUL-04:11 | 15.93 | 14.90 | 0.489623E+10 | 6965.70 | 05-JUL-13:09 | 15.93 | 14.90 |
August | 0.510522E+11 | 87301.79 | 01-AUG-04:12 | 18.13 | 17.48 | 0.548918E+10 | 6734.86 | 10-AUG-13:39 | 19.03 | 16.37 |
September | 0.403971E+11 | 86463.11 | 01-SEP-04:12 | 15.93 | 15.93 | 0.485562E+10 | 6748.71 | 27-SEP-09:20 | 6.70 | 5.08 |
October | 0.323280E+11 | 79302.90 | 20-OCT-05:03 | 7.52 | 7.52 | 0.495692E+10 | 6793.82 | 25-OCT-09:50 | 2.75 | 2.54 |
November | 0.256147E+11 | 81849.23 | 10-NOV-17:20 | -4.8 | -6.8 | 0.465129E+10 | 6968.93 | 07-NOV-16:49 | -4.8 | -6.8 |
December | 0.240996E+11 | 21414.14 | 05-DEC-17:15 | -0.1 | -0.1 | 0.412853E+10 | 6691.31 | 01-DEC-14:00 | -0.1 | -0.1 |
Annual Sum or Average | 0.426485E+12 | 0.576382E+11 | ||||||||
Minimum of Months | 0.227263E+11 | 20501.88 | -35.6 | -35.7 | 0.402589E+10 | 6557.67 | -14.4 | -15.6 | ||
Maximum of Months | 0.510522E+11 | 92391.94 | 18.13 | 17.48 | 0.548918E+10 | 7137.44 | 19.03 | 16.37 |
Report: ZoneCoolingSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.135206E+11 | 17355.46 | 20-JAN-16:50 | -6.9 | -8.2 | 0.388204E+10 | 5930.13 | 20-JAN-14:00 | -6.9 | -8.2 |
February | 0.156829E+11 | 19451.26 | 28-FEB-14:05 | 4.27 | 0.38 | 0.365385E+10 | 6407.78 | 08-FEB-14:00 | 4.27 | 0.38 |
March | 0.222650E+11 | 28644.58 | 29-MAR-16:00 | 5.00 | 1.34 | 0.462257E+10 | 6734.48 | 29-MAR-13:00 | 5.00 | 1.34 |
April | 0.269868E+11 | 40829.47 | 13-APR-16:00 | 20.00 | 8.11 | 0.447731E+10 | 6734.66 | 13-APR-09:30 | 20.00 | 8.11 |
May | 0.414384E+11 | 85020.59 | 26-MAY-04:12 | 19.40 | 15.71 | 0.519773E+10 | 6743.64 | 08-MAY-13:39 | 19.40 | 15.71 |
June | 0.482366E+11 | 84961.13 | 19-JUN-04:12 | 17.40 | 16.54 | 0.523799E+10 | 6734.82 | 13-JUN-09:00 | 17.40 | 16.54 |
July | 0.497729E+11 | 87278.56 | 05-JUL-04:12 | 19.80 | 18.77 | 0.488508E+10 | 7006.50 | 05-JUL-13:09 | 23.30 | 21.28 |
August | 0.488405E+11 | 86207.79 | 09-AUG-04:12 | 18.70 | 17.59 | 0.546929E+10 | 6734.89 | 10-AUG-13:39 | 19.03 | 16.37 |
September | 0.342955E+11 | 83534.33 | 01-SEP-04:12 | 15.93 | 15.93 | 0.476708E+10 | 6749.64 | 26-SEP-09:00 | 10.60 | 9.09 |
October | 0.249397E+11 | 38986.00 | 20-OCT-16:00 | 18.30 | 9.93 | 0.456535E+10 | 6734.62 | 25-OCT-13:00 | 11.10 | 7.08 |
November | 0.192791E+11 | 22206.11 | 17-NOV-17:00 | 6.70 | 1.30 | 0.418692E+10 | 6713.16 | 17-NOV-14:00 | 6.70 | 1.30 |
December | 0.142311E+11 | 17482.01 | 28-DEC-17:00 | -2.4 | -4.0 | 0.377693E+10 | 6041.87 | 28-DEC-14:00 | -2.4 | -4.0 |
Annual Sum or Average | 0.359489E+12 | 0.547221E+11 | ||||||||
Minimum of Months | 0.135206E+11 | 17355.46 | -6.9 | -8.2 | 0.365385E+10 | 5930.13 | -6.9 | -8.2 | ||
Maximum of Months | 0.497729E+11 | 87278.56 | 20.00 | 18.77 | 0.546929E+10 | 7006.50 | 23.30 | 21.28 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.334201E+09 | 2142.74 | 20-JAN-16:10 | -5.9 | -7.4 | 0.470371E+09 | 710.43 | 19-JAN-14:20 | -5.9 | -7.4 |
February | 0.104082E+10 | 2971.28 | 22-FEB-11:18 | -2.8 | -5.1 | 0.448823E+09 | 810.12 | 21-FEB-14:00 | -2.8 | -5.1 |
March | 0.245388E+10 | 4416.43 | 27-MAR-13:30 | 6.15 | 2.33 | 0.584322E+09 | 845.61 | 28-MAR-13:00 | 6.10 | 2.91 |
April | 0.422002E+10 | 7155.67 | 18-APR-14:00 | 17.80 | 10.49 | 0.583549E+09 | 845.62 | 27-APR-13:09 | 1.28 | -2.0 |
May | 0.747532E+10 | 13217.28 | 24-MAY-05:03 | 13.13 | 10.07 | 0.659901E+09 | 845.64 | 24-MAY-09:09 | 22.38 | 16.32 |
June | 0.998788E+10 | 14238.75 | 26-JUN-04:12 | 16.87 | 15.70 | 0.661503E+09 | 846.44 | 28-JUN-13:20 | 30.00 | 21.52 |
July | 0.110511E+11 | 17255.49 | 23-JUL-16:11 | 29.43 | 22.47 | 0.616637E+09 | 932.61 | 05-JUL-13:09 | 29.43 | 22.47 |
August | 0.101312E+11 | 12168.12 | 14-AUG-05:02 | 15.92 | 13.40 | 0.689722E+09 | 845.65 | 10-AUG-13:30 | 15.92 | 13.40 |
September | 0.543932E+10 | 8248.32 | 01-SEP-15:00 | 26.10 | 17.82 | 0.603904E+09 | 845.63 | 11-SEP-13:09 | 18.90 | 14.33 |
October | 0.361777E+10 | 5593.54 | 02-OCT-13:10 | 10.92 | 9.77 | 0.602317E+09 | 845.62 | 11-OCT-13:50 | 6.70 | 4.36 |
November | 0.237370E+10 | 4370.82 | 01-NOV-13:30 | 17.80 | 13.07 | 0.544068E+09 | 845.61 | 01-NOV-13:00 | 17.80 | 13.26 |
December | 0.780365E+09 | 2521.10 | 07-DEC-06:03 | -7.8 | -8.0 | 0.463271E+09 | 741.87 | 05-DEC-14:20 | -7.8 | -8.0 |
Annual Sum or Average | 0.589055E+11 | 0.692839E+10 | ||||||||
Minimum of Months | 0.334201E+09 | 2142.74 | -7.8 | -8.0 | 0.448823E+09 | 710.43 | -7.8 | -8.0 | ||
Maximum of Months | 0.110511E+11 | 17255.49 | 29.43 | 22.47 | 0.689722E+09 | 932.61 | 30.00 | 22.47 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.585385E+09 | 2884.67 | 31-JAN-11:00 | -15.6 | -16.0 | 0.303106E+09 | 490.97 | 25-JAN-10:30 | -15.6 | -16.0 |
February | 0.149084E+10 | 7287.13 | 28-FEB-10:10 | -5.5 | -7.3 | 0.295523E+09 | 545.86 | 28-FEB-10:20 | -5.0 | -6.8 |
March | 0.327284E+10 | 14346.37 | 20-MAR-08:48 | -3.5 | -4.6 | 0.380365E+09 | 580.13 | 23-MAR-09:30 | -7.5 | -8.3 |
April | 0.600780E+10 | 18909.61 | 30-APR-08:42 | 7.43 | 3.93 | 0.373867E+09 | 563.78 | 05-APR-09:00 | 7.43 | 3.93 |
May | 0.815255E+10 | 26110.73 | 21-MAY-08:52 | 12.20 | 7.39 | 0.423927E+09 | 545.88 | 17-MAY-09:09 | 12.20 | 7.39 |
June | 0.102347E+11 | 27649.19 | 25-JUN-08:61 | 24.08 | 20.82 | 0.424511E+09 | 546.13 | 27-JUN-09:20 | 25.37 | 19.29 |
July | 0.112708E+11 | 26731.21 | 23-JUL-09:32 | 26.13 | 22.79 | 0.395310E+09 | 553.05 | 05-JUL-13:09 | 26.13 | 22.79 |
August | 0.948184E+10 | 29020.54 | 13-AUG-09:31 | 20.03 | 15.18 | 0.439533E+09 | 545.17 | 22-AUG-09:09 | 20.18 | 14.51 |
September | 0.617844E+10 | 19145.94 | 10-SEP-09:02 | 13.68 | 10.14 | 0.380846E+09 | 544.97 | 14-SEP-09:09 | 13.27 | 10.50 |
October | 0.398853E+10 | 16657.86 | 09-OCT-09:32 | 2.20 | -1.2 | 0.364755E+09 | 544.96 | 19-OCT-09:00 | 13.90 | 10.03 |
November | 0.231510E+10 | 5317.33 | 16-NOV-09:35 | 0.93 | -1.0 | 0.332351E+09 | 544.95 | 09-NOV-10:39 | 0.93 | -1.0 |
December | 0.638799E+09 | 3059.46 | 01-DEC-10:20 | -20.5 | -20.8 | 0.293738E+09 | 518.13 | 01-DEC-10:30 | -20.3 | -20.6 |
Annual Sum or Average | 0.636176E+11 | 0.440783E+10 | ||||||||
Minimum of Months | 0.585385E+09 | 2884.67 | -20.5 | -20.8 | 0.293738E+09 | 490.97 | -20.3 | -20.6 | ||
Maximum of Months | 0.112708E+11 | 29020.54 | 26.13 | 22.79 | 0.439533E+09 | 580.13 | 26.13 | 22.79 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.308702E+10 | 19638.91 | 27-JAN-11:50 | -17.4 | -18.1 | 0.526815E+09 | 854.42 | 27-JAN-11:50 | -17.4 | -18.1 |
February | 0.533740E+10 | 28470.49 | 20-FEB-13:23 | 4.45 | 0.09 | 0.508160E+09 | 911.70 | 27-FEB-14:39 | -8.2 | -10.4 |
March | 0.723907E+10 | 31919.46 | 26-MAR-13:22 | 8.60 | 4.34 | 0.616204E+09 | 916.40 | 06-MAR-14:00 | 8.60 | 4.34 |
April | 0.973751E+10 | 33108.45 | 23-APR-12:52 | 22.80 | 15.30 | 0.578258E+09 | 847.08 | 20-APR-13:39 | 22.80 | 15.30 |
May | 0.113899E+11 | 26311.89 | 14-MAY-12:02 | 16.88 | 6.57 | 0.653619E+09 | 847.22 | 24-MAY-13:50 | 26.97 | 17.65 |
June | 0.126924E+11 | 31512.30 | 25-JUN-11:22 | 27.25 | 21.76 | 0.658267E+09 | 846.73 | 30-JUN-13:00 | 31.10 | 23.76 |
July | 0.150878E+11 | 33765.86 | 16-JUL-12:22 | 23.60 | 18.48 | 0.614982E+09 | 943.97 | 05-JUL-13:09 | 23.60 | 18.48 |
August | 0.155768E+11 | 35984.63 | 13-AUG-12:51 | 22.80 | 14.20 | 0.687984E+09 | 848.18 | 01-AUG-13:50 | 22.80 | 14.20 |
September | 0.110620E+11 | 34105.39 | 10-SEP-11:42 | 17.20 | 10.70 | 0.597507E+09 | 867.49 | 01-SEP-13:20 | 17.20 | 10.70 |
October | 0.799188E+10 | 34942.20 | 22-OCT-12:31 | 17.77 | 12.92 | 0.585831E+09 | 846.38 | 25-OCT-13:50 | 11.02 | 7.00 |
November | 0.514401E+10 | 22170.31 | 29-NOV-11:35 | -4.2 | -6.1 | 0.555347E+09 | 876.98 | 10-NOV-10:20 | -4.2 | -6.1 |
December | 0.264565E+10 | 14423.73 | 20-DEC-13:05 | -21.3 | -21.8 | 0.493363E+09 | 869.76 | 20-DEC-14:50 | -19.1 | -19.9 |
Annual Sum or Average | 0.106991E+12 | 0.707634E+10 | ||||||||
Minimum of Months | 0.264565E+10 | 14423.73 | -21.3 | -21.8 | 0.493363E+09 | 846.38 | -19.1 | -19.9 | ||
Maximum of Months | 0.155768E+11 | 35984.63 | 27.25 | 21.76 | 0.687984E+09 | 943.97 | 31.10 | 23.76 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.125144E+10 | 4874.80 | 27-JAN-15:35 | -14.4 | -15.6 | 0.312643E+09 | 535.89 | 27-JAN-14:00 | -14.4 | -15.6 |
February | 0.299054E+10 | 12650.86 | 27-FEB-15:40 | -7.8 | -10.1 | 0.309193E+09 | 544.95 | 27-FEB-14:00 | -7.8 | -10.1 |
March | 0.607247E+10 | 31149.22 | 26-MAR-16:42 | 10.18 | 5.01 | 0.401526E+09 | 563.53 | 06-MAR-14:00 | 10.18 | 5.01 |
April | 0.922076E+10 | 35196.45 | 23-APR-16:11 | 26.50 | 16.86 | 0.388682E+09 | 547.46 | 26-APR-13:00 | 0.00 | -0.5 |
May | 0.106199E+11 | 33196.63 | 14-MAY-16:41 | 20.00 | 8.40 | 0.424244E+09 | 544.97 | 16-MAY-13:20 | 24.67 | 15.35 |
June | 0.126876E+11 | 32781.31 | 17-JUN-17:41 | 23.90 | 13.28 | 0.426709E+09 | 544.97 | 13-JUN-09:00 | 23.90 | 13.28 |
July | 0.154267E+11 | 38366.11 | 16-JUL-16:21 | 21.95 | 16.03 | 0.397899E+09 | 558.92 | 05-JUL-13:00 | 21.95 | 16.03 |
August | 0.154654E+11 | 33831.94 | 13-AUG-14:11 | 23.13 | 14.51 | 0.445962E+09 | 544.98 | 10-AUG-13:30 | 23.13 | 14.51 |
September | 0.780718E+10 | 33189.16 | 03-SEP-17:01 | 21.52 | 16.01 | 0.385898E+09 | 544.96 | 11-SEP-13:09 | 18.90 | 14.33 |
October | 0.602114E+10 | 23297.77 | 22-OCT-15:12 | 19.23 | 12.63 | 0.388705E+09 | 544.95 | 11-OCT-13:50 | 19.23 | 12.63 |
November | 0.436256E+10 | 9039.91 | 09-NOV-15:30 | 1.65 | -3.5 | 0.369103E+09 | 544.96 | 28-NOV-14:00 | -7.2 | -8.5 |
December | 0.302429E+10 | 4723.76 | 20-DEC-15:30 | -19.5 | -20.3 | 0.322056E+09 | 544.95 | 28-DEC-14:50 | -1.7 | -3.7 |
Annual Sum or Average | 0.949500E+11 | 0.457262E+10 | ||||||||
Minimum of Months | 0.125144E+10 | 4723.76 | -19.5 | -20.3 | 0.309193E+09 | 535.89 | -14.4 | -15.6 | ||
Maximum of Months | 0.154654E+11 | 38366.11 | 26.50 | 16.86 | 0.445962E+09 | 563.53 | 24.67 | 16.03 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 11622012.70 | 1448.56 | 28-JAN-17:01 | -7.8 | -9.1 | 0.459277E+09 | 625.95 | 02-JAN-14:50 | -7.8 | -9.1 |
February | 99667116.69 | 1982.96 | 08-FEB-13:17 | 4.60 | -0.7 | 0.420538E+09 | 653.15 | 08-FEB-14:00 | 5.00 | -0.5 |
March | 0.742608E+09 | 2667.45 | 27-MAR-14:00 | 6.70 | 2.41 | 0.517721E+09 | 756.84 | 28-MAR-13:00 | 6.10 | 2.91 |
April | 0.220638E+10 | 4558.37 | 18-APR-14:00 | 17.80 | 10.49 | 0.512504E+09 | 845.60 | 18-APR-13:00 | 17.80 | 10.49 |
May | 0.592255E+10 | 10300.42 | 26-MAY-05:03 | 19.40 | 15.69 | 0.645004E+09 | 845.64 | 24-MAY-09:09 | 19.40 | 15.69 |
June | 0.823256E+10 | 13132.64 | 30-JUN-05:02 | 26.20 | 22.42 | 0.658786E+09 | 846.05 | 28-JUN-13:39 | 26.20 | 22.42 |
July | 0.869626E+10 | 16696.70 | 23-JUL-15:21 | 30.00 | 22.65 | 0.615210E+09 | 916.19 | 05-JUL-13:09 | 30.00 | 22.65 |
August | 0.706768E+10 | 9150.58 | 09-AUG-14:00 | 27.20 | 21.48 | 0.683988E+09 | 845.65 | 10-AUG-13:39 | 19.03 | 16.37 |
September | 0.393834E+10 | 7465.22 | 01-SEP-15:20 | 26.10 | 17.76 | 0.578208E+09 | 845.63 | 11-SEP-13:09 | 18.90 | 14.33 |
October | 0.209438E+10 | 3734.81 | 12-OCT-12:33 | 1.70 | -0.5 | 0.518942E+09 | 845.60 | 02-OCT-13:00 | 1.70 | -0.5 |
November | 0.613617E+09 | 2673.54 | 16-NOV-16:55 | 3.90 | -0.3 | 0.469207E+09 | 784.91 | 01-NOV-13:00 | 3.90 | -0.3 |
December | 13414067.11 | 1452.27 | 30-DEC-17:02 | -3.3 | -3.3 | 0.444699E+09 | 625.97 | 21-DEC-10:09 | -3.3 | -3.3 |
Annual Sum or Average | 0.396391E+11 | 0.652408E+10 | ||||||||
Minimum of Months | 11622012.70 | 1448.56 | -7.8 | -9.1 | 0.420538E+09 | 625.95 | -7.8 | -9.1 | ||
Maximum of Months | 0.869626E+10 | 16696.70 | 30.00 | 22.65 | 0.683988E+09 | 916.19 | 30.00 | 22.65 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 59988142.68 | 2158.39 | 20-JAN-06:04 | -6.8 | -7.3 | 0.218465E+09 | 385.82 | 04-JAN-09:20 | -6.8 | -7.3 |
February | 0.476832E+09 | 3318.54 | 08-FEB-10:50 | 0.03 | -3.0 | 0.200749E+09 | 490.19 | 28-FEB-09:00 | -6.1 | -7.7 |
March | 0.187578E+10 | 12026.12 | 31-MAR-09:40 | 1.13 | -1.2 | 0.257105E+09 | 532.88 | 29-MAR-10:30 | 1.13 | -1.2 |
April | 0.468980E+10 | 14233.08 | 18-APR-09:00 | 17.80 | 10.61 | 0.260529E+09 | 542.34 | 21-APR-07:30 | 2.20 | -1.6 |
May | 0.774008E+10 | 29729.60 | 14-MAY-08:31 | 9.53 | 3.36 | 0.305077E+09 | 550.07 | 01-MAY-07:49 | 9.53 | 3.36 |
June | 0.100725E+11 | 32632.08 | 18-JUN-08:31 | 20.93 | 13.90 | 0.309748E+09 | 522.46 | 07-JUN-08:50 | 20.93 | 13.90 |
July | 0.107366E+11 | 31219.58 | 23-JUL-07:21 | 22.75 | 21.08 | 0.290965E+09 | 531.93 | 05-JUL-10:00 | 22.75 | 21.08 |
August | 0.847307E+10 | 32526.74 | 20-AUG-09:01 | 20.97 | 15.56 | 0.316760E+09 | 521.26 | 21-AUG-07:10 | 15.97 | 15.14 |
September | 0.558017E+10 | 28464.75 | 10-SEP-09:32 | 14.83 | 10.42 | 0.264735E+09 | 521.22 | 13-SEP-10:30 | 15.80 | 11.43 |
October | 0.263961E+10 | 10755.55 | 18-OCT-09:00 | 6.70 | 4.93 | 0.239051E+09 | 522.47 | 19-OCT-07:00 | 8.90 | 6.71 |
November | 0.820539E+09 | 3513.24 | 16-NOV-10:25 | 3.05 | 0.21 | 0.221346E+09 | 505.03 | 16-NOV-09:00 | 3.05 | 0.21 |
December | 56350559.92 | 2226.78 | 05-DEC-06:04 | -1.1 | -1.1 | 0.210779E+09 | 385.83 | 21-DEC-09:09 | -28.4 | -28.7 |
Annual Sum or Average | 0.532213E+11 | 0.309531E+10 | ||||||||
Minimum of Months | 56350559.92 | 2158.39 | -6.8 | -7.3 | 0.200749E+09 | 385.82 | -28.4 | -28.7 | ||
Maximum of Months | 0.107366E+11 | 32632.08 | 22.75 | 21.08 | 0.316760E+09 | 550.07 | 22.75 | 21.08 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.249008E+10 | 18851.75 | 27-JAN-13:40 | -14.8 | -15.9 | 0.510888E+09 | 845.65 | 06-JAN-14:09 | -14.8 | -15.9 |
February | 0.462339E+10 | 24615.78 | 28-FEB-13:30 | 3.05 | -0.7 | 0.488629E+09 | 861.98 | 08-FEB-14:00 | 3.05 | -0.7 |
March | 0.615900E+10 | 36270.06 | 26-MAR-13:11 | 8.50 | 4.25 | 0.589545E+09 | 913.02 | 17-MAR-13:09 | 8.50 | 4.25 |
April | 0.828781E+10 | 37348.91 | 23-APR-14:31 | 25.20 | 16.35 | 0.552960E+09 | 881.31 | 04-APR-14:00 | 25.20 | 16.35 |
May | 0.107624E+11 | 33836.01 | 14-MAY-13:52 | 18.90 | 7.72 | 0.642929E+09 | 847.39 | 24-MAY-13:00 | 27.10 | 17.69 |
June | 0.117101E+11 | 34634.60 | 18-JUN-12:32 | 26.10 | 17.75 | 0.652132E+09 | 846.54 | 30-JUN-13:00 | 31.10 | 23.76 |
July | 0.133511E+11 | 35999.26 | 23-JUL-14:01 | 30.00 | 22.46 | 0.612186E+09 | 923.46 | 05-JUL-13:09 | 30.00 | 22.46 |
August | 0.134058E+11 | 37594.02 | 20-AUG-13:01 | 25.00 | 15.55 | 0.678736E+09 | 847.47 | 01-AUG-13:50 | 25.00 | 15.55 |
September | 0.107321E+11 | 38677.33 | 04-SEP-11:51 | 15.60 | 9.21 | 0.581326E+09 | 897.32 | 01-SEP-13:39 | 15.60 | 9.21 |
October | 0.714673E+10 | 37060.08 | 22-OCT-13:11 | 18.67 | 12.99 | 0.549089E+09 | 869.53 | 18-OCT-13:30 | 18.67 | 12.99 |
November | 0.366841E+10 | 25919.73 | 07-NOV-12:28 | -2.2 | -5.3 | 0.517846E+09 | 858.74 | 16-NOV-10:39 | 3.50 | 0.38 |
December | 0.146157E+10 | 13655.11 | 02-DEC-13:20 | -18.8 | -19.5 | 0.475500E+09 | 845.65 | 19-DEC-14:09 | -22.5 | -23.1 |
Annual Sum or Average | 0.937985E+11 | 0.685177E+10 | ||||||||
Minimum of Months | 0.146157E+10 | 13655.11 | -18.8 | -19.5 | 0.475500E+09 | 845.65 | -22.5 | -23.1 | ||
Maximum of Months | 0.134058E+11 | 38677.33 | 30.00 | 22.46 | 0.678736E+09 | 923.46 | 31.10 | 23.76 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.256514E+09 | 3193.61 | 27-JAN-16:00 | -14.4 | -15.6 | 0.301418E+09 | 488.34 | 27-JAN-16:10 | -14.8 | -15.9 |
February | 0.872765E+09 | 6698.69 | 08-FEB-16:30 | 3.85 | -1.1 | 0.281251E+09 | 543.39 | 08-FEB-14:00 | 3.85 | -1.1 |
March | 0.233666E+10 | 28290.23 | 26-MAR-17:11 | 9.63 | 4.75 | 0.344650E+09 | 548.04 | 10-MAR-16:10 | 9.63 | 4.75 |
April | 0.494092E+10 | 36347.22 | 23-APR-16:31 | 26.30 | 16.77 | 0.331024E+09 | 554.85 | 04-APR-14:00 | 26.30 | 16.77 |
May | 0.871822E+10 | 35795.19 | 14-MAY-17:11 | 20.00 | 8.46 | 0.406293E+09 | 544.96 | 16-MAY-13:09 | 24.58 | 15.35 |
June | 0.979593E+10 | 31433.43 | 17-JUN-17:41 | 23.90 | 13.28 | 0.417619E+09 | 544.96 | 13-JUN-09:00 | 23.90 | 13.28 |
July | 0.108445E+11 | 35284.70 | 23-JUL-16:01 | 29.72 | 22.65 | 0.393806E+09 | 555.96 | 05-JUL-13:00 | 29.72 | 22.65 |
August | 0.933170E+10 | 32411.66 | 27-AUG-17:51 | 22.80 | 19.07 | 0.432072E+09 | 544.97 | 10-AUG-13:39 | 22.80 | 19.07 |
September | 0.591542E+10 | 31620.00 | 03-SEP-17:01 | 21.52 | 16.01 | 0.354127E+09 | 544.96 | 11-SEP-13:30 | 18.90 | 14.50 |
October | 0.331258E+10 | 12051.60 | 22-OCT-15:52 | 18.90 | 12.36 | 0.328105E+09 | 544.86 | 19-OCT-13:00 | 18.90 | 12.36 |
November | 0.108619E+10 | 7000.20 | 10-NOV-17:20 | -4.8 | -6.8 | 0.305734E+09 | 527.94 | 17-NOV-14:00 | 10.60 | 3.43 |
December | 0.164749E+09 | 2521.52 | 20-DEC-15:40 | -19.8 | -20.5 | 0.288443E+09 | 416.29 | 08-DEC-14:00 | -19.8 | -20.5 |
Annual Sum or Average | 0.575761E+11 | 0.418454E+10 | ||||||||
Minimum of Months | 0.164749E+09 | 2521.52 | -19.8 | -20.5 | 0.281251E+09 | 416.29 | -19.8 | -20.5 | ||
Maximum of Months | 0.108445E+11 | 36347.22 | 29.72 | 22.65 | 0.432072E+09 | 555.96 | 29.72 | 22.65 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 8677951.23 | 1608.74 | 28-JAN-17:01 | -7.8 | -9.1 | 0.457027E+09 | 626.08 | 04-JAN-14:00 | -7.8 | -9.1 |
February | 64059386.23 | 1759.86 | 08-FEB-14:40 | 5.00 | -0.5 | 0.418297E+09 | 626.82 | 08-FEB-14:50 | 5.00 | -0.5 |
March | 0.411785E+09 | 2442.72 | 28-MAR-15:00 | 6.70 | 3.01 | 0.508517E+09 | 715.07 | 28-MAR-13:00 | 6.70 | 3.01 |
April | 0.170894E+10 | 4415.95 | 18-APR-14:00 | 17.80 | 10.49 | 0.488569E+09 | 845.60 | 18-APR-13:00 | 17.80 | 10.49 |
May | 0.563728E+10 | 9598.32 | 24-MAY-14:30 | 27.45 | 17.67 | 0.626331E+09 | 846.42 | 08-MAY-13:39 | 27.45 | 17.67 |
June | 0.817417E+10 | 12744.23 | 29-JUN-05:03 | 22.30 | 19.61 | 0.653424E+09 | 845.65 | 26-JUN-13:20 | 22.30 | 19.61 |
July | 0.875013E+10 | 20847.63 | 23-JUL-15:21 | 30.00 | 22.65 | 0.612244E+09 | 871.33 | 05-JUL-13:09 | 30.00 | 22.65 |
August | 0.693010E+10 | 9735.00 | 09-AUG-15:30 | 27.25 | 21.19 | 0.673792E+09 | 845.65 | 10-AUG-13:39 | 19.03 | 16.37 |
September | 0.352123E+10 | 8009.28 | 01-SEP-15:20 | 26.10 | 17.76 | 0.547911E+09 | 845.63 | 11-SEP-13:09 | 18.90 | 14.33 |
October | 0.138915E+10 | 3238.73 | 19-OCT-13:40 | 21.33 | 13.69 | 0.488444E+09 | 809.58 | 20-OCT-13:00 | 18.90 | 10.07 |
November | 0.306890E+09 | 2321.37 | 01-NOV-16:00 | 17.80 | 13.26 | 0.461243E+09 | 727.95 | 01-NOV-13:00 | 17.80 | 13.26 |
December | 11733942.63 | 1616.34 | 30-DEC-17:02 | -3.3 | -3.3 | 0.442815E+09 | 626.01 | 18-DEC-10:00 | -3.3 | -3.3 |
Annual Sum or Average | 0.369142E+11 | 0.637861E+10 | ||||||||
Minimum of Months | 8677951.23 | 1608.74 | -7.8 | -9.1 | 0.418297E+09 | 626.01 | -7.8 | -9.1 | ||
Maximum of Months | 0.875013E+10 | 20847.63 | 30.00 | 22.65 | 0.673792E+09 | 871.33 | 30.00 | 22.65 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 18703167.11 | 1911.09 | 21-JAN-17:02 | -5.0 | -7.1 | 0.298283E+09 | 403.42 | 04-JAN-10:30 | -5.0 | -7.1 |
February | 0.308788E+09 | 2851.67 | 28-FEB-10:33 | -3.9 | -5.9 | 0.272757E+09 | 493.17 | 28-FEB-10:39 | -3.9 | -5.9 |
March | 0.134594E+10 | 6354.54 | 31-MAR-10:00 | 1.70 | -0.9 | 0.346757E+09 | 544.95 | 17-MAR-09:00 | 1.70 | -0.9 |
April | 0.389941E+10 | 13518.86 | 18-APR-09:30 | 18.05 | 10.95 | 0.349879E+09 | 544.96 | 18-APR-09:00 | 18.30 | 11.28 |
May | 0.734003E+10 | 27784.77 | 21-MAY-09:21 | 13.15 | 7.90 | 0.410597E+09 | 545.87 | 18-MAY-09:39 | 13.15 | 7.90 |
June | 0.998198E+10 | 32261.38 | 18-JUN-08:41 | 21.32 | 14.26 | 0.420588E+09 | 546.19 | 27-JUN-09:50 | 25.92 | 19.10 |
July | 0.107948E+11 | 31056.05 | 23-JUL-07:21 | 22.75 | 21.08 | 0.394349E+09 | 547.04 | 05-JUL-13:00 | 22.75 | 21.08 |
August | 0.830028E+10 | 28458.60 | 20-AUG-09:22 | 21.70 | 15.75 | 0.428755E+09 | 544.97 | 10-AUG-13:39 | 21.70 | 15.75 |
September | 0.495831E+10 | 15535.43 | 01-SEP-09:10 | 20.28 | 17.76 | 0.353857E+09 | 544.97 | 14-SEP-09:09 | 13.27 | 10.50 |
October | 0.180853E+10 | 8290.15 | 19-OCT-09:30 | 12.50 | 9.01 | 0.319428E+09 | 544.96 | 19-OCT-09:00 | 13.90 | 10.03 |
November | 0.499823E+09 | 2775.65 | 16-NOV-10:25 | 3.05 | 0.21 | 0.298449E+09 | 484.85 | 16-NOV-10:20 | 3.05 | 0.21 |
December | 28449031.03 | 2281.72 | 28-DEC-06:04 | -2.3 | -2.8 | 0.287629E+09 | 403.42 | 11-DEC-10:50 | -2.3 | -2.8 |
Annual Sum or Average | 0.492851E+11 | 0.418133E+10 | ||||||||
Minimum of Months | 18703167.11 | 1911.09 | -5.0 | -7.1 | 0.272757E+09 | 403.42 | -5.0 | -7.1 | ||
Maximum of Months | 0.107948E+11 | 32261.38 | 22.75 | 21.08 | 0.428755E+09 | 547.04 | 25.92 | 21.08 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.197719E+10 | 16560.65 | 27-JAN-13:40 | -14.8 | -15.9 | 0.502087E+09 | 845.65 | 06-JAN-14:09 | -14.8 | -15.9 |
February | 0.382937E+10 | 23737.73 | 28-FEB-13:45 | 3.62 | -0.3 | 0.478094E+09 | 846.28 | 22-FEB-14:09 | 3.62 | -0.3 |
March | 0.492520E+10 | 32749.55 | 19-MAR-13:51 | 3.90 | 0.85 | 0.575980E+09 | 847.29 | 17-MAR-13:39 | 3.90 | 0.85 |
April | 0.712192E+10 | 38908.95 | 23-APR-14:01 | 24.60 | 16.15 | 0.539050E+09 | 846.47 | 13-APR-13:00 | 24.60 | 16.15 |
May | 0.101939E+11 | 34349.63 | 14-MAY-13:52 | 18.90 | 7.72 | 0.629195E+09 | 847.52 | 24-MAY-13:00 | 27.10 | 17.69 |
June | 0.116409E+11 | 36394.54 | 18-JUN-12:42 | 26.10 | 17.78 | 0.644567E+09 | 846.59 | 30-JUN-13:00 | 31.10 | 23.76 |
July | 0.134246E+11 | 38497.78 | 23-JUL-14:01 | 30.00 | 22.46 | 0.607591E+09 | 899.11 | 05-JUL-13:09 | 30.00 | 22.46 |
August | 0.131523E+11 | 36388.50 | 27-AUG-15:01 | 23.40 | 18.62 | 0.668776E+09 | 847.54 | 01-AUG-13:50 | 23.40 | 18.62 |
September | 0.979997E+10 | 39793.64 | 04-SEP-13:41 | 16.10 | 9.63 | 0.561202E+09 | 884.18 | 01-SEP-13:39 | 16.10 | 9.63 |
October | 0.578128E+10 | 38006.14 | 22-OCT-13:31 | 19.03 | 12.89 | 0.524786E+09 | 846.10 | 20-OCT-13:00 | 19.03 | 12.89 |
November | 0.288737E+10 | 19696.71 | 17-NOV-13:10 | 10.10 | 3.25 | 0.502900E+09 | 845.64 | 28-NOV-14:00 | -7.2 | -8.5 |
December | 0.104137E+10 | 10937.26 | 02-DEC-13:30 | -18.6 | -19.3 | 0.468785E+09 | 845.64 | 20-DEC-14:39 | -19.3 | -20.1 |
Annual Sum or Average | 0.857754E+11 | 0.670301E+10 | ||||||||
Minimum of Months | 0.104137E+10 | 10937.26 | -18.6 | -19.3 | 0.468785E+09 | 845.64 | -19.3 | -20.1 | ||
Maximum of Months | 0.134246E+11 | 39793.64 | 30.00 | 22.46 | 0.668776E+09 | 899.11 | 31.10 | 23.76 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.200116E+09 | 3074.31 | 27-JAN-16:00 | -14.4 | -15.6 | 0.299914E+09 | 462.47 | 27-JAN-16:10 | -14.8 | -15.9 |
February | 0.719293E+09 | 6434.87 | 08-FEB-16:30 | 3.85 | -1.1 | 0.279017E+09 | 527.76 | 08-FEB-14:00 | 3.85 | -1.1 |
March | 0.185803E+10 | 11317.77 | 28-MAR-17:00 | 7.20 | 3.52 | 0.340412E+09 | 522.45 | 29-MAR-15:09 | 4.50 | 1.36 |
April | 0.429165E+10 | 37376.01 | 23-APR-16:41 | 26.20 | 16.72 | 0.322004E+09 | 544.94 | 18-APR-13:00 | 26.20 | 16.72 |
May | 0.842220E+10 | 36620.97 | 14-MAY-17:11 | 20.00 | 8.46 | 0.396164E+09 | 544.97 | 23-MAY-13:50 | 25.63 | 17.00 |
June | 0.975946E+10 | 32608.47 | 17-JUN-17:41 | 23.90 | 13.28 | 0.412151E+09 | 544.97 | 26-JUN-13:20 | 25.97 | 17.06 |
July | 0.108814E+11 | 37286.59 | 23-JUL-16:01 | 29.72 | 22.65 | 0.390551E+09 | 547.91 | 05-JUL-13:00 | 29.72 | 22.65 |
August | 0.918909E+10 | 34073.64 | 27-AUG-17:41 | 22.80 | 19.07 | 0.424676E+09 | 544.97 | 10-AUG-13:39 | 22.80 | 19.07 |
September | 0.538257E+10 | 31355.11 | 03-SEP-17:12 | 21.33 | 15.90 | 0.341215E+09 | 544.95 | 07-SEP-13:00 | 23.90 | 14.48 |
October | 0.250693E+10 | 11365.60 | 19-OCT-16:00 | 21.70 | 13.55 | 0.319410E+09 | 544.77 | 20-OCT-13:00 | 18.90 | 10.07 |
November | 0.732690E+09 | 3581.33 | 17-NOV-15:50 | 10.10 | 3.24 | 0.301849E+09 | 517.90 | 17-NOV-15:00 | 10.00 | 3.20 |
December | 97631342.09 | 2478.17 | 05-DEC-06:04 | -1.1 | -1.1 | 0.287809E+09 | 403.42 | 11-DEC-10:50 | -21.4 | -21.9 |
Annual Sum or Average | 0.540411E+11 | 0.411517E+10 | ||||||||
Minimum of Months | 97631342.09 | 2478.17 | -14.4 | -15.6 | 0.279017E+09 | 403.42 | -21.4 | -21.9 | ||
Maximum of Months | 0.108814E+11 | 37376.01 | 29.72 | 22.65 | 0.424676E+09 | 547.91 | 29.72 | 22.65 |
Report: ZoneCoolingSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.179073E+09 | 10814.36 | 28-JAN-05:01 | -26.7 | -26.9 | 0.00 | 0.00 | 01-JAN-00:10 | -26.7 | -26.9 |
February | 0.399959E+09 | 10731.36 | 17-FEB-05:01 | -30.3 | -30.5 | 0.00 | 0.00 | 01-FEB-00:10 | -30.3 | -30.5 |
March | 0.149081E+10 | 8999.69 | 06-MAR-05:01 | -18.4 | -18.8 | 0.00 | 0.00 | 01-MAR-00:10 | -18.4 | -18.8 |
April | 0.402054E+10 | 7016.52 | 24-APR-05:15 | 4.40 | 3.41 | 0.00 | 0.00 | 01-APR-00:10 | 4.40 | 3.41 |
May | 0.668319E+10 | 9773.43 | 30-MAY-05:15 | 10.60 | 8.25 | 0.00 | 0.00 | 01-MAY-00:10 | 10.60 | 8.25 |
June | 0.871588E+10 | 9336.61 | 27-JUN-05:02 | 15.68 | 14.97 | 0.00 | 0.00 | 01-JUN-00:10 | 15.68 | 14.97 |
July | 0.993169E+10 | 11107.19 | 24-JUL-05:02 | 17.88 | 16.12 | 0.00 | 0.00 | 01-JUL-00:10 | 17.88 | 16.12 |
August | 0.953676E+10 | 9457.90 | 14-AUG-05:15 | 15.73 | 13.37 | 0.00 | 0.00 | 01-AUG-00:10 | 15.73 | 13.37 |
September | 0.563392E+10 | 9586.60 | 05-SEP-05:15 | 5.60 | 5.31 | 0.00 | 0.00 | 01-SEP-00:10 | 5.60 | 5.31 |
October | 0.352356E+10 | 7505.57 | 30-OCT-05:01 | -9.9 | -10.6 | 0.00 | 0.00 | 01-OCT-00:10 | -9.9 | -10.6 |
November | 0.144120E+10 | 6906.87 | 25-NOV-05:01 | -19.0 | -19.3 | 0.00 | 0.00 | 01-NOV-00:10 | -19.0 | -19.3 |
December | 0.267329E+09 | 9327.68 | 21-DEC-05:01 | -26.9 | -27.1 | 0.00 | 0.00 | 01-DEC-00:10 | -26.9 | -27.1 |
Annual Sum or Average | 0.518239E+11 | 0.00 | ||||||||
Minimum of Months | 0.179073E+09 | 6906.87 | -30.3 | -30.5 | 0.00 | 0.00 | -30.3 | -30.5 | ||
Maximum of Months | 0.993169E+10 | 11107.19 | 17.88 | 16.12 | 0.00 | 0.00 | 17.88 | 16.12 |
Report: ZoneCoolingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.713183E+09 | 14369.19 | 28-JAN-04:01 | -26.7 | -26.9 | 0.00 | 0.00 | 01-JAN-00:10 | -26.7 | -26.9 |
February | 0.682994E+09 | 15932.31 | 10-FEB-04:01 | -20.5 | -20.8 | 0.00 | 0.00 | 01-FEB-00:10 | -20.5 | -20.8 |
March | 0.730483E+09 | 12370.23 | 15-MAR-03:01 | -21.7 | -22.0 | 0.00 | 0.00 | 01-MAR-00:10 | -21.7 | -22.0 |
April | 0.166534E+10 | 11386.15 | 27-APR-04:01 | -3.1 | -4.2 | 0.00 | 0.00 | 01-APR-00:10 | -3.1 | -4.2 |
May | 0.456307E+10 | 7429.31 | 19-MAY-05:13 | 14.27 | 9.81 | 0.00 | 0.00 | 01-MAY-00:10 | 14.27 | 9.81 |
June | 0.646599E+10 | 8478.98 | 30-JUN-15:50 | 31.78 | 24.63 | 0.00 | 0.00 | 01-JUN-00:10 | 31.78 | 24.63 |
July | 0.749377E+10 | 8497.62 | 24-JUL-15:20 | 29.23 | 19.07 | 0.00 | 0.00 | 01-JUL-00:10 | 29.23 | 19.07 |
August | 0.644596E+10 | 7802.01 | 25-AUG-05:13 | 7.97 | 7.76 | 0.00 | 0.00 | 01-AUG-00:10 | 7.97 | 7.76 |
September | 0.376217E+10 | 6945.44 | 01-SEP-16:00 | 26.10 | 17.64 | 0.00 | 0.00 | 01-SEP-00:10 | 26.10 | 17.64 |
October | 0.161027E+10 | 10221.64 | 30-OCT-04:01 | -10.0 | -10.7 | 0.00 | 0.00 | 01-OCT-00:10 | -10.0 | -10.7 |
November | 0.668220E+09 | 12207.30 | 25-NOV-04:11 | -18.2 | -18.5 | 0.00 | 0.00 | 01-NOV-00:10 | -18.2 | -18.5 |
December | 0.731599E+09 | 15093.25 | 02-DEC-04:01 | -26.8 | -27.0 | 0.00 | 0.00 | 01-DEC-00:10 | -26.8 | -27.0 |
Annual Sum or Average | 0.355331E+11 | 0.00 | ||||||||
Minimum of Months | 0.668220E+09 | 6945.44 | -26.8 | -27.0 | 0.00 | 0.00 | -26.8 | -27.0 | ||
Maximum of Months | 0.749377E+10 | 15932.31 | 31.78 | 24.63 | 0.00 | 0.00 | 31.78 | 24.63 |
Report: ZoneCoolingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:01 | -21.9 | -22.1 | 0.00 | 0.00 | 01-JAN-00:10 | -21.9 | -22.1 |
February | 0.00 | 0.00 | 01-FEB-00:03 | -23.1 | -23.5 | 0.00 | 0.00 | 01-FEB-00:10 | -23.1 | -23.5 |
March | 0.154143E+09 | 3336.62 | 31-MAR-15:00 | 8.30 | 2.63 | 0.00 | 0.00 | 01-MAR-00:10 | 8.30 | 2.63 |
April | 0.195107E+10 | 10449.92 | 13-APR-14:40 | 19.63 | 7.88 | 0.00 | 0.00 | 01-APR-00:10 | 19.63 | 7.88 |
May | 0.690096E+10 | 18430.45 | 18-MAY-14:30 | 28.70 | 16.68 | 0.00 | 0.00 | 01-MAY-00:10 | 28.70 | 16.68 |
June | 0.100295E+11 | 20928.82 | 30-JUN-14:50 | 32.02 | 24.38 | 0.00 | 0.00 | 01-JUN-00:10 | 32.02 | 24.38 |
July | 0.114847E+11 | 19476.01 | 24-JUL-14:30 | 29.40 | 19.57 | 0.00 | 0.00 | 01-JUL-00:10 | 29.40 | 19.57 |
August | 0.858391E+10 | 17826.46 | 08-AUG-15:10 | 30.60 | 23.30 | 0.00 | 0.00 | 01-AUG-00:10 | 30.60 | 23.30 |
September | 0.362512E+10 | 15163.51 | 01-SEP-16:00 | 26.10 | 17.64 | 0.00 | 0.00 | 01-SEP-00:10 | 26.10 | 17.64 |
October | 0.750941E+09 | 7027.47 | 20-OCT-14:50 | 18.90 | 10.07 | 0.00 | 0.00 | 01-OCT-00:10 | 18.90 | 10.07 |
November | 22971849.93 | 1923.93 | 01-NOV-16:30 | 17.25 | 13.03 | 0.00 | 0.00 | 01-NOV-00:10 | 17.25 | 13.03 |
December | 0.00 | 0.00 | 01-DEC-00:10 | -8.8 | -9.9 | 0.00 | 0.00 | 01-DEC-00:10 | -8.8 | -9.9 |
Annual Sum or Average | 0.435033E+11 | 0.00 | ||||||||
Minimum of Months | 0.00 | 0.00 | -23.1 | -23.5 | 0.00 | 0.00 | -23.1 | -23.5 | ||
Maximum of Months | 0.114847E+11 | 20928.82 | 32.02 | 24.38 | 0.00 | 0.00 | 32.02 | 24.38 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.142022E+10 | 2289.88 | 25-JAN-16:30 | -18.4 | -19.1 | 94922348.11 | 126.82 | 11-JAN-14:09 | -18.4 | -19.1 |
February | 0.684833E+10 | 4765.77 | 27-FEB-17:00 | -7.8 | -10.2 | 86396439.77 | 126.82 | 13-FEB-14:09 | -7.8 | -10.2 |
March | 0.135834E+11 | 7052.75 | 31-MAR-24:00 | 3.60 | 0.45 | 0.103236E+09 | 126.82 | 28-MAR-13:09 | 3.60 | 0.45 |
April | 0.188124E+11 | 8806.15 | 21-APR-18:20 | 10.53 | 2.25 | 91609583.44 | 126.82 | 19-APR-09:20 | 10.53 | 2.25 |
May | 0.465290E+10 | 3292.46 | 31-MAY-24:00 | 11.20 | 9.10 | 99236465.36 | 126.86 | 26-MAY-13:30 | 11.20 | 9.10 |
June | 0.953729E+10 | 5405.43 | 30-JUN-23:45 | 16.35 | 13.47 | 98967158.23 | 126.86 | 23-JUN-09:20 | 16.35 | 13.47 |
July | 0.150291E+11 | 7274.45 | 31-JUL-23:52 | 17.00 | 15.17 | 91888126.87 | 126.84 | 05-JUL-09:00 | 17.00 | 15.17 |
August | 0.199966E+11 | 8653.47 | 13-AUG-18:31 | 21.13 | 14.84 | 0.103240E+09 | 126.83 | 15-AUG-09:09 | 15.10 | 14.70 |
September | 0.430202E+10 | 3308.34 | 30-SEP-24:00 | 7.80 | 6.76 | 91608871.23 | 126.86 | 01-SEP-09:50 | 7.80 | 6.76 |
October | 0.900628E+10 | 4824.78 | 31-OCT-24:00 | 3.30 | -0.4 | 95230352.88 | 126.83 | 02-OCT-13:00 | 3.30 | -0.4 |
November | 0.130282E+11 | 6254.08 | 09-NOV-16:10 | 0.82 | -3.8 | 94300559.12 | 126.84 | 21-NOV-14:09 | 13.77 | 12.33 |
December | 0.176153E+11 | 7861.64 | 20-DEC-16:00 | -20.2 | -20.8 | 91880832.27 | 126.82 | 01-DEC-10:09 | -20.2 | -20.8 |
Annual Sum or Average | 0.133832E+12 | 0.114252E+10 | ||||||||
Minimum of Months | 0.142022E+10 | 2289.88 | -20.2 | -20.8 | 86396439.77 | 126.82 | -20.2 | -20.8 | ||
Maximum of Months | 0.199966E+11 | 8806.15 | 21.13 | 15.17 | 0.103240E+09 | 126.86 | 17.00 | 15.17 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.456964E+09 | 1822.28 | 27-JAN-16:30 | -15.6 | -16.5 | 89793643.47 | 126.82 | 20-JAN-14:09 | -15.6 | -16.5 |
February | 0.406769E+10 | 4077.12 | 27-FEB-17:00 | -7.8 | -10.2 | 86396460.24 | 126.82 | 13-FEB-14:09 | -7.8 | -10.2 |
March | 0.108626E+11 | 6317.83 | 31-MAR-23:20 | 3.93 | 0.64 | 0.103236E+09 | 126.82 | 28-MAR-13:09 | 3.93 | 0.64 |
April | 0.165888E+11 | 8439.64 | 21-APR-18:20 | 10.53 | 2.25 | 91606498.01 | 126.82 | 19-APR-09:20 | 10.53 | 2.25 |
May | 0.393075E+10 | 2937.55 | 14-MAY-18:43 | 18.17 | 8.43 | 99236167.27 | 126.85 | 26-MAY-09:00 | 22.60 | 18.32 |
June | 0.875452E+10 | 5271.04 | 30-JUN-23:55 | 16.10 | 13.43 | 98967549.69 | 126.86 | 30-JUN-09:39 | 16.10 | 13.43 |
July | 0.141763E+11 | 6918.77 | 31-JUL-23:52 | 17.00 | 15.17 | 91889349.37 | 126.85 | 05-JUL-09:00 | 17.00 | 15.17 |
August | 0.187668E+11 | 8283.56 | 02-AUG-18:40 | 18.53 | 13.51 | 0.103241E+09 | 126.83 | 10-AUG-09:30 | 18.30 | 16.86 |
September | 0.334478E+10 | 3021.55 | 05-SEP-17:50 | 15.78 | 9.39 | 91607326.91 | 126.85 | 01-SEP-13:00 | 15.78 | 9.39 |
October | 0.697501E+10 | 4265.79 | 18-OCT-16:50 | 15.28 | 10.42 | 95230317.95 | 126.83 | 02-OCT-13:00 | 15.28 | 10.42 |
November | 0.992614E+10 | 5680.00 | 09-NOV-16:20 | 0.53 | -4.0 | 94300526.45 | 126.83 | 21-NOV-14:09 | 13.77 | 12.33 |
December | 0.135612E+11 | 6939.60 | 20-DEC-16:05 | -20.4 | -21.0 | 91880844.66 | 126.82 | 01-DEC-10:09 | -20.4 | -21.0 |
Annual Sum or Average | 0.111412E+12 | 0.113739E+10 | ||||||||
Minimum of Months | 0.456964E+09 | 1822.28 | -20.4 | -21.0 | 86396460.24 | 126.82 | -20.4 | -21.0 | ||
Maximum of Months | 0.187668E+11 | 8439.64 | 18.53 | 15.17 | 0.103241E+09 | 126.86 | 22.60 | 18.32 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.351596E+09 | 1550.11 | 25-JAN-16:30 | -18.4 | -19.1 | 84960812.67 | 126.82 | 20-JAN-14:09 | -18.4 | -19.1 |
February | 0.275745E+10 | 4021.52 | 27-FEB-17:00 | -7.8 | -10.2 | 86385068.09 | 126.82 | 13-FEB-14:09 | -7.8 | -10.2 |
March | 0.923939E+10 | 6239.50 | 28-MAR-17:50 | 7.20 | 2.87 | 0.103236E+09 | 126.82 | 28-MAR-13:09 | 7.20 | 2.87 |
April | 0.153326E+11 | 8429.19 | 21-APR-18:20 | 10.53 | 2.25 | 91605712.74 | 126.82 | 19-APR-09:20 | 10.53 | 2.25 |
May | 0.345876E+10 | 2844.21 | 14-MAY-18:47 | 18.17 | 8.43 | 99230872.45 | 126.85 | 26-MAY-09:00 | 22.60 | 18.32 |
June | 0.850878E+10 | 5250.42 | 30-JUN-23:34 | 16.60 | 13.50 | 98967399.58 | 126.86 | 30-JUN-09:39 | 16.60 | 13.50 |
July | 0.140401E+11 | 6826.75 | 31-JUL-23:52 | 17.00 | 15.17 | 91889206.27 | 126.85 | 05-JUL-09:00 | 17.00 | 15.17 |
August | 0.185597E+11 | 8316.20 | 02-AUG-18:40 | 18.53 | 13.51 | 0.103241E+09 | 126.83 | 28-AUG-13:09 | 20.60 | 18.71 |
September | 0.268241E+10 | 3018.24 | 05-SEP-17:50 | 15.78 | 9.39 | 91607218.62 | 126.85 | 01-SEP-13:39 | 15.78 | 9.39 |
October | 0.545137E+10 | 4267.62 | 18-OCT-16:50 | 15.28 | 10.42 | 95230312.87 | 126.83 | 02-OCT-13:00 | 15.28 | 10.42 |
November | 0.812821E+10 | 5535.14 | 09-NOV-16:20 | 0.53 | -4.0 | 94300528.71 | 126.83 | 21-NOV-14:09 | 13.77 | 12.33 |
December | 0.119219E+11 | 6717.25 | 20-DEC-16:05 | -20.4 | -21.0 | 91880847.87 | 126.82 | 01-DEC-10:09 | -20.4 | -21.0 |
Annual Sum or Average | 0.100432E+12 | 0.113254E+10 | ||||||||
Minimum of Months | 0.351596E+09 | 1550.11 | -20.4 | -21.0 | 84960812.67 | 126.82 | -20.4 | -21.0 | ||
Maximum of Months | 0.185597E+11 | 8429.19 | 18.53 | 15.17 | 0.103241E+09 | 126.86 | 22.60 | 18.71 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.232603E+12 | 91311.54 | 20-JAN-17:00 | -7.2 | -8.4 | 0.206144E+10 | 2745.29 | 24-JAN-14:00 | -13.3 | -13.9 |
February | 0.433310E+12 | 183678.30 | 22-FEB-17:00 | -1.1 | -3.9 | 0.187025E+10 | 2745.50 | 13-FEB-10:20 | -1.1 | -3.9 |
March | 0.727273E+12 | 359138.72 | 31-MAR-24:00 | 3.60 | 0.45 | 0.223477E+10 | 2745.44 | 08-MAR-10:00 | 3.60 | 0.45 |
April | 0.943179E+12 | 368544.38 | 19-APR-16:00 | 7.20 | 1.06 | 0.198300E+10 | 2746.29 | 14-APR-09:09 | 7.20 | 1.06 |
May | 0.242344E+12 | 175937.47 | 31-MAY-24:00 | 11.20 | 9.10 | 0.214815E+10 | 2747.04 | 23-MAY-13:39 | 11.20 | 9.10 |
June | 0.471997E+12 | 268899.54 | 30-JUN-23:55 | 16.10 | 13.43 | 0.214249E+10 | 2748.56 | 21-JUN-09:00 | 16.10 | 13.43 |
July | 0.734015E+12 | 361158.07 | 31-JUL-23:52 | 17.00 | 15.17 | 0.202326E+10 | 3382.62 | 21-JUL-13:00 | 17.00 | 15.17 |
August | 0.978630E+12 | 378473.15 | 09-AUG-23:03 | 18.95 | 17.54 | 0.239907E+10 | 4296.24 | 08-AUG-13:00 | 18.95 | 17.54 |
September | 0.236898E+12 | 176206.65 | 30-SEP-24:00 | 7.80 | 6.76 | 0.198296E+10 | 2745.95 | 12-SEP-09:30 | 7.80 | 6.76 |
October | 0.487027E+12 | 267457.12 | 31-OCT-24:00 | 3.30 | -0.4 | 0.206147E+10 | 2746.89 | 19-OCT-13:00 | 3.30 | -0.4 |
November | 0.706384E+12 | 276848.10 | 17-NOV-17:00 | 6.70 | 1.30 | 0.204136E+10 | 2748.12 | 01-NOV-13:00 | 6.70 | 1.30 |
December | 0.971733E+12 | 367479.70 | 06-DEC-17:00 | -7.0 | -7.2 | 0.198896E+10 | 2745.42 | 14-DEC-10:00 | -20.7 | -21.2 |
Annual Sum or Average | 0.716539E+13 | 0.249372E+11 | ||||||||
Minimum of Months | 0.232603E+12 | 91311.54 | -7.2 | -8.4 | 0.187025E+10 | 2745.29 | -20.7 | -21.2 | ||
Maximum of Months | 0.978630E+12 | 378473.15 | 18.95 | 17.54 | 0.239907E+10 | 4296.24 | 18.95 | 17.54 |
Report: ZoneHeatingSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.120632E+09 | 12751.10 | 17-JAN-06:05 | -5.9 |
February | 78435953.07 | 12421.60 | 08-FEB-05:03 | -4.4 |
March | 0.126395E+09 | 12529.41 | 27-MAR-03:03 | -3.3 |
April | 0.140397E+09 | 13007.33 | 15-APR-04:15 | 5.60 |
May | 0.251877E+09 | 13132.56 | 01-MAY-03:05 | -2.1 |
June | 0.269159E+09 | 16330.04 | 24-JUN-16:01 | 28.98 |
July | 0.418351E+09 | 18148.18 | 29-JUL-16:01 | 30.50 |
August | 0.348178E+09 | 15028.84 | 27-AUG-13:42 | 22.02 |
September | 0.357478E+09 | 13082.67 | 06-SEP-03:05 | 1.60 |
October | 0.318242E+09 | 13006.40 | 07-OCT-04:15 | 9.07 |
November | 0.157825E+09 | 12590.00 | 06-NOV-06:04 | -3.9 |
December | 80858956.55 | 12574.14 | 08-DEC-05:03 | -20.3 |
Annual Sum or Average | 0.266783E+10 | |||
Minimum of Months | 78435953.07 | 12421.60 | -20.3 | |
Maximum of Months | 0.418351E+09 | 18148.18 | 30.50 |
Report: ZoneHeatingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 17564381.46 | 17768.50 | 02-JAN-05:01 | -18.2 |
February | 0.00 | 0.00 | 01-FEB-00:03 | -23.1 |
March | 0.00 | 0.00 | 01-MAR-00:10 | -1.3 |
April | 0.00 | 0.00 | 01-APR-00:10 | 3.52 |
May | 0.00 | 0.00 | 01-MAY-00:10 | -0.0 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 11.35 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 15.83 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 17.07 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 19.75 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 7.52 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 3.60 |
December | 0.00 | 0.00 | 01-DEC-00:10 | -8.8 |
Annual Sum or Average | 17564381.46 | |||
Minimum of Months | 0.00 | 0.00 | -23.1 | |
Maximum of Months | 17564381.46 | 17768.50 | 19.75 |
Report: ZoneHeatingSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.180898E+10 | 62292.69 | 02-JAN-04:01 | -18.8 |
February | 0.356106E+09 | 53099.44 | 21-FEB-05:21 | 2.50 |
March | 68010504.17 | 51272.35 | 06-MAR-05:01 | -18.4 |
April | 1173811.64 | 4569.13 | 04-APR-12:20 | -4.2 |
May | 528413.33 | 1625.97 | 01-MAY-06:55 | -1.3 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 11.35 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 15.83 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 17.07 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 19.75 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 7.52 |
November | 0.201560E+09 | 53341.78 | 27-NOV-05:11 | -7.2 |
December | 0.936654E+09 | 57926.52 | 26-DEC-04:01 | -25.0 |
Annual Sum or Average | 0.337301E+10 | |||
Minimum of Months | 0.00 | 0.00 | -25.0 | |
Maximum of Months | 0.180898E+10 | 62292.69 | 19.75 |
Report: ZoneHeatingSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.109071E+11 | 84541.08 | 09-JAN-04:11 | -32.6 |
February | 0.554468E+10 | 83465.91 | 13-FEB-04:11 | -23.0 |
March | 0.269727E+10 | 82548.69 | 06-MAR-04:01 | -17.4 |
April | 0.703928E+09 | 76004.45 | 03-APR-04:01 | -5.4 |
May | 8124239.20 | 66232.64 | 01-MAY-05:02 | -3.4 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 11.35 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 15.83 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 17.07 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 19.75 |
October | 0.789593E+09 | 78424.32 | 30-OCT-03:01 | -9.5 |
November | 0.354650E+10 | 82210.46 | 27-NOV-04:01 | -7.2 |
December | 0.856035E+10 | 84412.34 | 26-DEC-04:01 | -25.0 |
Annual Sum or Average | 0.327575E+11 | |||
Minimum of Months | 0.00 | 0.00 | -32.6 | |
Maximum of Months | 0.109071E+11 | 84541.08 | 19.75 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.482493E+10 | 15347.43 | 01-JAN-08:61 | -26.7 |
February | 0.151946E+10 | 14001.60 | 13-FEB-04:01 | -22.9 |
March | 0.392788E+09 | 13528.58 | 06-MAR-05:01 | -18.4 |
April | 3286960.14 | 11855.51 | 05-APR-05:01 | -13.4 |
May | 0.00 | 0.00 | 01-MAY-00:10 | -0.0 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 11.35 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 15.83 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 17.07 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 19.75 |
October | 2678455.86 | 12069.02 | 30-OCT-05:01 | -9.9 |
November | 0.179908E+09 | 13005.11 | 25-NOV-05:01 | -19.0 |
December | 0.191279E+10 | 14332.19 | 26-DEC-04:01 | -25.0 |
Annual Sum or Average | 0.883584E+10 | |||
Minimum of Months | 0.00 | 0.00 | -26.7 | |
Maximum of Months | 0.482493E+10 | 15347.43 | 19.75 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.288990E+10 | 18660.47 | 02-JAN-04:01 | -18.8 |
February | 0.957441E+09 | 17134.44 | 13-FEB-04:01 | -22.9 |
March | 0.296169E+09 | 16212.21 | 06-MAR-05:01 | -18.4 |
April | 9299946.53 | 12626.01 | 05-APR-05:01 | -13.4 |
May | 0.00 | 0.00 | 01-MAY-00:10 | -0.0 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 11.35 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 15.83 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 17.07 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 19.75 |
October | 6300941.77 | 14165.01 | 30-OCT-05:01 | -9.9 |
November | 0.202409E+09 | 15766.97 | 25-NOV-05:01 | -19.0 |
December | 0.156383E+10 | 17782.66 | 26-DEC-04:01 | -25.0 |
Annual Sum or Average | 0.592534E+10 | |||
Minimum of Months | 0.00 | 0.00 | -25.0 | |
Maximum of Months | 0.288990E+10 | 18660.47 | 19.75 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.348373E+10 | 26598.85 | 09-JAN-04:21 | -32.8 |
February | 0.133437E+10 | 25555.42 | 13-FEB-04:01 | -22.9 |
March | 0.475911E+09 | 23419.63 | 06-MAR-05:01 | -18.4 |
April | 31274993.92 | 19246.84 | 04-APR-05:01 | -9.0 |
May | 8120.44 | 39.89 | 10-MAY-06:17 | 5.83 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 11.35 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 15.83 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 17.07 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 19.75 |
October | 31159087.19 | 20934.41 | 30-OCT-05:01 | -9.9 |
November | 0.368365E+09 | 23483.86 | 25-NOV-05:01 | -19.0 |
December | 0.193639E+10 | 26151.12 | 26-DEC-04:01 | -25.0 |
Annual Sum or Average | 0.766120E+10 | |||
Minimum of Months | 0.00 | 0.00 | -32.8 | |
Maximum of Months | 0.348373E+10 | 26598.85 | 19.75 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.147558E+10 | 17489.81 | 09-JAN-04:01 | -32.4 |
February | 0.251858E+09 | 15018.52 | 13-FEB-05:01 | -23.4 |
March | 15609751.40 | 13809.25 | 06-MAR-05:01 | -18.4 |
April | 0.00 | 0.00 | 01-APR-00:10 | 3.52 |
May | 0.00 | 0.00 | 01-MAY-00:10 | -0.0 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 11.35 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 15.83 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 17.07 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 19.75 |
October | 297661.57 | 4464.92 | 30-OCT-05:01 | -9.9 |
November | 8506974.14 | 12697.82 | 24-NOV-06:01 | -10.5 |
December | 0.122367E+09 | 14831.00 | 26-DEC-05:01 | -25.9 |
Annual Sum or Average | 0.187422E+10 | |||
Minimum of Months | 0.00 | 0.00 | -32.4 | |
Maximum of Months | 0.147558E+10 | 17489.81 | 19.75 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.144243E+11 | 15759.00 | 09-JAN-05:11 | -32.8 |
February | 0.826639E+10 | 15292.36 | 12-FEB-22:41 | -16.8 |
March | 0.429880E+10 | 14825.40 | 06-MAR-04:11 | -17.6 |
April | 0.702566E+09 | 13605.11 | 03-APR-03:01 | -7.4 |
May | 6629973.04 | 11652.59 | 01-MAY-05:02 | -3.4 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 11.35 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 15.83 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 17.07 |
September | 426258.66 | 1544.34 | 23-SEP-05:03 | 4.90 |
October | 0.440755E+09 | 13196.95 | 30-OCT-03:01 | -9.5 |
November | 0.358288E+10 | 14778.68 | 27-NOV-01:52 | -6.7 |
December | 0.127799E+11 | 15784.65 | 24-DEC-07:02 | -31.1 |
Annual Sum or Average | 0.445027E+11 | |||
Minimum of Months | 0.00 | 0.00 | -32.8 | |
Maximum of Months | 0.144243E+11 | 15784.65 | 17.07 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.867397E+10 | 24346.44 | 08-JAN-21:52 | -28.9 |
February | 0.434388E+10 | 24027.34 | 12-FEB-22:41 | -16.8 |
March | 0.213847E+10 | 23162.58 | 06-MAR-04:11 | -17.6 |
April | 0.329872E+09 | 19995.27 | 03-APR-04:01 | -5.4 |
May | 1521692.27 | 9237.00 | 01-MAY-05:02 | -3.4 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 11.35 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 15.83 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 17.07 |
September | 2242759.88 | 3766.18 | 23-SEP-05:03 | 4.90 |
October | 0.293185E+09 | 19701.03 | 30-OCT-04:01 | -10.0 |
November | 0.224077E+10 | 22618.60 | 25-NOV-04:11 | -18.2 |
December | 0.793250E+10 | 24459.26 | 24-DEC-07:02 | -31.1 |
Annual Sum or Average | 0.259564E+11 | |||
Minimum of Months | 0.00 | 0.00 | -31.1 | |
Maximum of Months | 0.867397E+10 | 24459.26 | 17.07 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.878269E+10 | 29569.17 | 09-JAN-02:32 | -32.2 |
February | 0.431188E+10 | 29032.27 | 13-FEB-04:01 | -22.9 |
March | 0.229530E+10 | 28102.85 | 06-MAR-04:11 | -17.6 |
April | 0.432725E+09 | 24448.41 | 03-APR-04:01 | -5.4 |
May | 3775170.84 | 10093.12 | 01-MAY-05:02 | -3.4 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 11.35 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 15.83 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 17.07 |
September | 182189.56 | 610.54 | 20-SEP-05:03 | 5.60 |
October | 0.304960E+09 | 24292.94 | 30-OCT-04:01 | -10.0 |
November | 0.239052E+10 | 27567.80 | 25-NOV-04:11 | -18.2 |
December | 0.825916E+10 | 29745.81 | 24-DEC-07:02 | -31.1 |
Annual Sum or Average | 0.267812E+11 | |||
Minimum of Months | 0.00 | 0.00 | -32.2 | |
Maximum of Months | 0.878269E+10 | 29745.81 | 17.07 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.774599E+10 | 24718.00 | 09-JAN-02:32 | -32.2 |
February | 0.374163E+10 | 24205.98 | 13-FEB-04:01 | -22.9 |
March | 0.168800E+10 | 23461.58 | 06-MAR-04:11 | -17.6 |
April | 0.239117E+09 | 20277.98 | 03-APR-04:01 | -5.4 |
May | 1411138.89 | 3132.31 | 01-MAY-05:02 | -3.4 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 11.35 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 15.83 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 17.07 |
September | 410744.97 | 1461.86 | 20-SEP-05:03 | 5.60 |
October | 0.194527E+09 | 19965.26 | 30-OCT-04:01 | -10.0 |
November | 0.163862E+10 | 22881.08 | 25-NOV-04:11 | -18.2 |
December | 0.649479E+10 | 24746.65 | 24-DEC-07:02 | -31.1 |
Annual Sum or Average | 0.217445E+11 | |||
Minimum of Months | 0.00 | 0.00 | -32.2 | |
Maximum of Months | 0.774599E+10 | 24746.65 | 17.07 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.207200E+11 | 20130.53 | 09-JAN-05:31 | -32.2 |
February | 0.137967E+11 | 20362.88 | 13-FEB-04:11 | -23.0 |
March | 0.858339E+10 | 19112.23 | 06-MAR-05:01 | -18.4 |
April | 0.235440E+10 | 18026.75 | 02-APR-05:03 | -5.7 |
May | 0.118147E+09 | 15489.72 | 01-MAY-04:01 | -2.9 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 11.35 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 15.83 |
August | 1453458.94 | 3827.66 | 19-AUG-05:03 | 4.60 |
September | 0.124549E+09 | 14012.55 | 13-SEP-05:02 | 3.98 |
October | 0.196761E+10 | 17666.59 | 30-OCT-03:01 | -9.5 |
November | 0.802307E+10 | 18662.51 | 23-NOV-22:42 | -11.0 |
December | 0.195368E+11 | 19478.51 | 24-DEC-09:21 | -30.5 |
Annual Sum or Average | 0.752261E+11 | |||
Minimum of Months | 0.00 | 0.00 | -32.2 | |
Maximum of Months | 0.207200E+11 | 20362.88 | 15.83 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.126259E+11 | 25597.58 | 14-JAN-04:11 | -25.2 |
February | 0.759879E+10 | 27012.71 | 13-FEB-04:11 | -23.0 |
March | 0.430914E+10 | 24881.26 | 06-MAR-05:01 | -18.4 |
April | 0.109905E+10 | 23226.66 | 10-APR-03:01 | -1.9 |
May | 45263139.11 | 20333.36 | 01-MAY-04:01 | -2.9 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 11.35 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 15.83 |
August | 1443346.20 | 4098.91 | 19-AUG-05:03 | 4.60 |
September | 77278474.31 | 14852.94 | 13-SEP-05:02 | 3.98 |
October | 0.114757E+10 | 23368.87 | 30-OCT-03:01 | -9.5 |
November | 0.482519E+10 | 24253.35 | 27-NOV-01:52 | -6.7 |
December | 0.122598E+11 | 25381.37 | 25-DEC-06:01 | -29.3 |
Annual Sum or Average | 0.439894E+11 | |||
Minimum of Months | 0.00 | 0.00 | -29.3 | |
Maximum of Months | 0.126259E+11 | 27012.71 | 15.83 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.141473E+11 | 31550.75 | 04-JAN-04:21 | -28.1 |
February | 0.838625E+10 | 33363.13 | 13-FEB-04:11 | -23.0 |
March | 0.519538E+10 | 30992.05 | 05-MAR-07:02 | -28.5 |
April | 0.162237E+10 | 28831.20 | 10-APR-03:01 | -1.9 |
May | 99036942.45 | 25248.09 | 01-MAY-04:01 | -2.9 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 11.35 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 15.83 |
August | 1963100.69 | 3497.49 | 19-AUG-05:03 | 4.60 |
September | 89207767.66 | 17337.57 | 13-SEP-05:02 | 3.98 |
October | 0.138426E+10 | 29053.93 | 30-OCT-03:01 | -9.5 |
November | 0.569913E+10 | 30309.07 | 23-NOV-18:42 | -9.4 |
December | 0.142146E+11 | 31440.45 | 24-DEC-08:61 | -31.1 |
Annual Sum or Average | 0.508395E+11 | |||
Minimum of Months | 0.00 | 0.00 | -31.1 | |
Maximum of Months | 0.142146E+11 | 33363.13 | 15.83 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.117341E+11 | 27997.51 | 04-JAN-04:21 | -28.1 |
February | 0.658133E+10 | 29275.42 | 13-FEB-04:11 | -23.0 |
March | 0.354839E+10 | 26967.01 | 06-MAR-05:01 | -18.4 |
April | 0.848034E+09 | 25053.25 | 10-APR-03:01 | -1.9 |
May | 40447883.84 | 21670.49 | 01-MAY-04:01 | -2.9 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 11.35 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 15.83 |
August | 51036.65 | 275.31 | 19-AUG-05:03 | 4.60 |
September | 39153644.13 | 8723.09 | 20-SEP-05:03 | 5.60 |
October | 0.780483E+09 | 25327.95 | 30-OCT-03:01 | -9.5 |
November | 0.366418E+10 | 25968.65 | 24-NOV-04:01 | -11.0 |
December | 0.103085E+11 | 27630.12 | 24-DEC-09:21 | -30.5 |
Annual Sum or Average | 0.375447E+11 | |||
Minimum of Months | 0.00 | 0.00 | -30.5 | |
Maximum of Months | 0.117341E+11 | 29275.42 | 15.83 |
Report: ZoneHeatingSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.392126E+10 | 14494.92 | 02-JAN-06:12 | -17.8 |
February | 0.155505E+10 | 14240.57 | 20-FEB-13:23 | 4.45 |
March | 0.731802E+09 | 17766.55 | 26-MAR-15:22 | 10.85 |
April | 0.149971E+09 | 15513.98 | 23-APR-15:31 | 26.33 |
May | 92860695.28 | 10727.62 | 21-MAY-14:52 | 22.80 |
June | 86075216.68 | 10313.22 | 25-JUN-10:42 | 27.62 |
July | 0.124525E+09 | 13982.09 | 23-JUL-15:31 | 30.00 |
August | 0.148128E+09 | 13629.74 | 20-AUG-15:11 | 25.20 |
September | 83656022.89 | 12627.39 | 03-SEP-15:41 | 21.70 |
October | 86983142.96 | 11047.39 | 22-OCT-15:12 | 19.23 |
November | 0.344606E+09 | 12835.76 | 14-NOV-05:11 | 3.13 |
December | 0.196296E+10 | 13407.31 | 06-DEC-06:01 | -0.8 |
Annual Sum or Average | 0.928788E+10 | |||
Minimum of Months | 83656022.89 | 10313.22 | -17.8 | |
Maximum of Months | 0.392126E+10 | 17766.55 | 30.00 |
Report: ZoneHeatingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.865257E+10 | 23967.14 | 02-JAN-06:12 | -17.8 |
February | 0.492506E+10 | 12411.53 | 27-FEB-06:12 | -18.7 |
March | 0.309004E+10 | 22369.35 | 26-MAR-16:31 | 10.37 |
April | 0.861397E+09 | 17437.35 | 23-APR-15:51 | 26.70 |
May | 0.112215E+09 | 14141.78 | 14-MAY-15:11 | 20.00 |
June | 64361405.42 | 11143.37 | 18-JUN-13:52 | 26.70 |
July | 76441208.46 | 15933.46 | 23-JUL-16:01 | 29.72 |
August | 77609094.30 | 14787.61 | 20-AUG-15:01 | 25.40 |
September | 71180160.89 | 13878.24 | 03-SEP-15:41 | 21.70 |
October | 0.473274E+09 | 12637.88 | 09-OCT-13:21 | 5.85 |
November | 0.268329E+10 | 11856.74 | 07-NOV-16:45 | -3.4 |
December | 0.655627E+10 | 18169.78 | 26-DEC-06:11 | -26.6 |
Annual Sum or Average | 0.276437E+11 | |||
Minimum of Months | 64361405.42 | 11143.37 | -26.6 | |
Maximum of Months | 0.865257E+10 | 23967.14 | 29.72 |
Report: ZoneHeatingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.243773E+11 | 39090.22 | 09-JAN-05:42 | -32.0 |
February | 0.163259E+11 | 36356.66 | 13-FEB-05:08 | -23.4 |
March | 0.109770E+11 | 33457.06 | 06-MAR-05:21 | -18.6 |
April | 0.368463E+10 | 25546.31 | 03-APR-04:12 | -5.2 |
May | 0.600465E+09 | 15814.98 | 16-MAY-05:02 | 8.98 |
June | 0.129375E+09 | 15759.87 | 17-JUN-05:03 | 5.55 |
July | 99215174.37 | 15122.51 | 18-JUL-05:03 | 8.27 |
August | 0.144130E+09 | 14059.01 | 25-AUG-05:03 | 7.88 |
September | 0.703391E+09 | 12947.86 | 08-SEP-05:03 | 10.10 |
October | 0.366423E+10 | 27803.70 | 30-OCT-05:12 | -9.8 |
November | 0.107227E+11 | 29651.76 | 25-NOV-05:21 | -19.1 |
December | 0.224586E+11 | 35642.08 | 26-DEC-05:31 | -26.4 |
Annual Sum or Average | 0.938870E+11 | |||
Minimum of Months | 99215174.37 | 12947.86 | -32.0 | |
Maximum of Months | 0.243773E+11 | 39090.22 | 10.10 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.146586E+09 | 637.62 | 01-JAN-17:50 | -19.8 |
February | 0.00 | 0.00 | 01-FEB-00:03 | -23.1 |
March | 0.00 | 0.00 | 01-MAR-00:10 | -1.3 |
April | 0.00 | 0.00 | 01-APR-00:10 | 3.52 |
May | 0.00 | 0.00 | 01-MAY-00:10 | -0.0 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 11.35 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 15.83 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 17.07 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 19.75 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 7.52 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 3.60 |
December | 0.00 | 0.00 | 01-DEC-00:10 | -8.8 |
Annual Sum or Average | 0.146586E+09 | |||
Minimum of Months | 0.00 | 0.00 | -23.1 | |
Maximum of Months | 0.146586E+09 | 637.62 | 19.75 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.777524E+09 | 634.20 | 01-JAN-17:10 | -19.1 |
February | 0.00 | 0.00 | 01-FEB-00:03 | -23.1 |
March | 0.00 | 0.00 | 01-MAR-00:10 | -1.3 |
April | 0.00 | 0.00 | 01-APR-00:10 | 3.52 |
May | 0.00 | 0.00 | 01-MAY-00:10 | -0.0 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 11.35 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 15.83 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 17.07 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 19.75 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 7.52 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 3.60 |
December | 0.00 | 0.00 | 01-DEC-00:10 | -8.8 |
Annual Sum or Average | 0.777524E+09 | |||
Minimum of Months | 0.00 | 0.00 | -23.1 | |
Maximum of Months | 0.777524E+09 | 634.20 | 19.75 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.824937E+09 | 649.24 | 24-JAN-23:35 | -18.7 |
February | 0.175652E+09 | 603.75 | 12-FEB-23:04 | -17.4 |
March | 0.00 | 0.00 | 01-MAR-00:10 | -1.3 |
April | 0.00 | 0.00 | 01-APR-00:10 | 3.52 |
May | 7669121.18 | 545.75 | 01-MAY-04:55 | -3.3 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 11.35 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 15.83 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 17.07 |
September | 436945.33 | 424.38 | 24-SEP-07:53 | 8.30 |
October | 7341042.33 | 396.31 | 30-OCT-03:15 | -9.6 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 3.60 |
December | 0.00 | 0.00 | 01-DEC-00:10 | -8.8 |
Annual Sum or Average | 0.101604E+10 | |||
Minimum of Months | 0.00 | 0.00 | -18.7 | |
Maximum of Months | 0.824937E+09 | 649.24 | 17.07 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:01 | -21.9 |
February | 0.00 | 0.00 | 01-FEB-00:03 | -23.1 |
March | 0.00 | 0.00 | 01-MAR-00:10 | -1.3 |
April | 0.00 | 0.00 | 01-APR-00:10 | 3.52 |
May | 0.00 | 0.00 | 01-MAY-00:10 | -0.0 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 11.35 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 15.83 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 17.07 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 19.75 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 7.52 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 3.60 |
December | 0.00 | 0.00 | 01-DEC-00:10 | -8.8 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | -23.1 | |
Maximum of Months | 0.00 | 0.00 | 19.75 |
Report: ZoneElectricSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.219312E+11 | 22950.34 | 02-JAN-08:09 | 0.360447E+11 | 13457.54 | 01-JAN-00:10 |
February | 0.198933E+11 | 22950.34 | 01-FEB-08:09 | 0.325565E+11 | 13457.54 | 01-FEB-00:10 |
March | 0.236388E+11 | 22950.34 | 01-MAR-08:09 | 0.360447E+11 | 13457.54 | 01-MAR-00:10 |
April | 0.211142E+11 | 22950.34 | 03-APR-07:10 | 0.348820E+11 | 13457.54 | 01-APR-00:10 |
May | 0.227850E+11 | 22950.34 | 01-MAY-07:10 | 0.360447E+11 | 13457.54 | 01-MAY-00:10 |
June | 0.226748E+11 | 22950.34 | 01-JUN-07:10 | 0.348820E+11 | 13457.54 | 01-JUN-00:10 |
July | 0.212244E+11 | 22950.34 | 03-JUL-07:10 | 0.360447E+11 | 13457.54 | 01-JUL-00:10 |
August | 0.236388E+11 | 22950.34 | 01-AUG-07:10 | 0.360447E+11 | 13457.54 | 01-AUG-00:10 |
September | 0.211142E+11 | 22950.34 | 01-SEP-07:10 | 0.348820E+11 | 13457.54 | 01-SEP-00:10 |
October | 0.219312E+11 | 22950.34 | 02-OCT-07:10 | 0.360447E+11 | 13457.54 | 01-OCT-00:10 |
November | 0.216742E+11 | 22950.34 | 01-NOV-07:10 | 0.348820E+11 | 13457.54 | 01-NOV-00:10 |
December | 0.212244E+11 | 22950.34 | 01-DEC-08:09 | 0.360447E+11 | 13457.54 | 01-DEC-00:10 |
Annual Sum or Average | 0.262844E+12 | 0.424397E+12 | ||||
Minimum of Months | 0.198933E+11 | 22950.34 | 0.325565E+11 | 13457.54 | ||
Maximum of Months | 0.236388E+11 | 22950.34 | 0.360447E+11 | 13457.54 |
Report: ZoneElectricSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.196958E+11 | 20611.01 | 02-JAN-08:09 | 0.243681E+11 | 17206.63 | 02-JAN-08:09 |
February | 0.178655E+11 | 20611.01 | 01-FEB-08:09 | 0.220609E+11 | 17206.63 | 01-FEB-08:09 |
March | 0.212293E+11 | 20611.01 | 01-MAR-08:09 | 0.253549E+11 | 17206.63 | 01-MAR-08:09 |
April | 0.189620E+11 | 20611.01 | 03-APR-07:10 | 0.235306E+11 | 17206.63 | 03-APR-07:10 |
May | 0.204625E+11 | 20611.01 | 01-MAY-07:10 | 0.248615E+11 | 17206.63 | 01-MAY-07:10 |
June | 0.203636E+11 | 20611.01 | 01-JUN-07:10 | 0.244160E+11 | 17206.63 | 01-JUN-07:10 |
July | 0.190610E+11 | 20611.01 | 03-JUL-07:10 | 0.239708E+11 | 17206.63 | 03-JUL-07:10 |
August | 0.212293E+11 | 20611.01 | 01-AUG-07:10 | 0.253549E+11 | 17206.63 | 01-AUG-07:10 |
September | 0.189620E+11 | 20611.01 | 01-SEP-07:10 | 0.235199E+11 | 17206.63 | 01-SEP-07:10 |
October | 0.196958E+11 | 20611.01 | 02-OCT-07:10 | 0.243735E+11 | 17206.63 | 02-OCT-07:10 |
November | 0.194649E+11 | 20611.01 | 01-NOV-07:10 | 0.238373E+11 | 17206.63 | 01-NOV-07:10 |
December | 0.190610E+11 | 20611.01 | 01-DEC-08:09 | 0.239654E+11 | 17206.63 | 01-DEC-08:09 |
Annual Sum or Average | 0.236053E+12 | 0.289614E+12 | ||||
Minimum of Months | 0.178655E+11 | 20611.01 | 0.220609E+11 | 17206.63 | ||
Maximum of Months | 0.212293E+11 | 20611.01 | 0.253549E+11 | 17206.63 |
Report: ZoneElectricSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.196958E+11 | 20611.01 | 02-JAN-08:09 | 0.243680E+11 | 17206.56 | 02-JAN-08:09 |
February | 0.178655E+11 | 20611.01 | 01-FEB-08:09 | 0.220609E+11 | 17206.56 | 01-FEB-08:09 |
March | 0.212293E+11 | 20611.01 | 01-MAR-08:09 | 0.253548E+11 | 17206.56 | 01-MAR-08:09 |
April | 0.189620E+11 | 20611.01 | 03-APR-07:10 | 0.235305E+11 | 17206.56 | 03-APR-07:10 |
May | 0.204625E+11 | 20611.01 | 01-MAY-07:10 | 0.248614E+11 | 17206.56 | 01-MAY-07:10 |
June | 0.203636E+11 | 20611.01 | 01-JUN-07:10 | 0.244159E+11 | 17206.56 | 01-JUN-07:10 |
July | 0.190610E+11 | 20611.01 | 03-JUL-07:10 | 0.239707E+11 | 17206.56 | 03-JUL-07:10 |
August | 0.212293E+11 | 20611.01 | 01-AUG-07:10 | 0.253548E+11 | 17206.56 | 01-AUG-07:10 |
September | 0.189620E+11 | 20611.01 | 01-SEP-07:10 | 0.235198E+11 | 17206.56 | 01-SEP-07:10 |
October | 0.196958E+11 | 20611.01 | 02-OCT-07:10 | 0.243734E+11 | 17206.56 | 02-OCT-07:10 |
November | 0.194649E+11 | 20611.01 | 01-NOV-07:10 | 0.238372E+11 | 17206.56 | 01-NOV-07:10 |
December | 0.190610E+11 | 20611.01 | 01-DEC-08:09 | 0.239653E+11 | 17206.56 | 01-DEC-08:09 |
Annual Sum or Average | 0.236053E+12 | 0.289613E+12 | ||||
Minimum of Months | 0.178655E+11 | 20611.01 | 0.220609E+11 | 17206.56 | ||
Maximum of Months | 0.212293E+11 | 20611.01 | 0.253548E+11 | 17206.56 |
Report: ZoneElectricSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.196958E+11 | 20611.01 | 02-JAN-08:09 | 0.243680E+11 | 17206.56 | 02-JAN-08:09 |
February | 0.178655E+11 | 20611.01 | 01-FEB-08:09 | 0.220609E+11 | 17206.56 | 01-FEB-08:09 |
March | 0.212293E+11 | 20611.01 | 01-MAR-08:09 | 0.253548E+11 | 17206.56 | 01-MAR-08:09 |
April | 0.189620E+11 | 20611.01 | 03-APR-07:10 | 0.235305E+11 | 17206.56 | 03-APR-07:10 |
May | 0.204625E+11 | 20611.01 | 01-MAY-07:10 | 0.248614E+11 | 17206.56 | 01-MAY-07:10 |
June | 0.203636E+11 | 20611.01 | 01-JUN-07:10 | 0.244159E+11 | 17206.56 | 01-JUN-07:10 |
July | 0.190610E+11 | 20611.01 | 03-JUL-07:10 | 0.239707E+11 | 17206.56 | 03-JUL-07:10 |
August | 0.212293E+11 | 20611.01 | 01-AUG-07:10 | 0.253548E+11 | 17206.56 | 01-AUG-07:10 |
September | 0.189620E+11 | 20611.01 | 01-SEP-07:10 | 0.235198E+11 | 17206.56 | 01-SEP-07:10 |
October | 0.196958E+11 | 20611.01 | 02-OCT-07:10 | 0.243734E+11 | 17206.56 | 02-OCT-07:10 |
November | 0.194649E+11 | 20611.01 | 01-NOV-07:10 | 0.238372E+11 | 17206.56 | 01-NOV-07:10 |
December | 0.190610E+11 | 20611.01 | 01-DEC-08:09 | 0.239653E+11 | 17206.56 | 01-DEC-08:09 |
Annual Sum or Average | 0.236053E+12 | 0.289613E+12 | ||||
Minimum of Months | 0.178655E+11 | 20611.01 | 0.220609E+11 | 17206.56 | ||
Maximum of Months | 0.212293E+11 | 20611.01 | 0.253548E+11 | 17206.56 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.170446E+10 | 2587.92 | 02-JAN-08:09 | 0.305979E+10 | 2160.55 | 02-JAN-08:09 |
February | 0.138330E+10 | 2255.20 | 01-FEB-08:09 | 0.277008E+10 | 2160.55 | 01-FEB-08:09 |
March | 0.154201E+10 | 2255.20 | 03-MAR-16:49 | 0.318369E+10 | 2160.55 | 01-MAR-08:09 |
April | 0.130619E+10 | 1470.28 | 03-APR-07:10 | 0.295462E+10 | 2160.55 | 03-APR-07:10 |
May | 0.135053E+10 | 1231.33 | 01-MAY-07:10 | 0.312174E+10 | 2160.55 | 01-MAY-07:10 |
June | 0.132866E+10 | 1470.28 | 30-JUN-07:10 | 0.306580E+10 | 2160.55 | 01-JUN-07:10 |
July | 0.125481E+10 | 1231.33 | 03-JUL-07:10 | 0.300989E+10 | 2160.55 | 03-JUL-07:10 |
August | 0.144311E+10 | 1803.00 | 31-AUG-07:10 | 0.318369E+10 | 2160.55 | 01-AUG-07:10 |
September | 0.133798E+10 | 1803.00 | 19-SEP-07:10 | 0.295328E+10 | 2160.55 | 01-SEP-07:10 |
October | 0.149888E+10 | 2587.92 | 26-OCT-07:10 | 0.306046E+10 | 2160.55 | 02-OCT-07:10 |
November | 0.164710E+10 | 2587.92 | 01-NOV-07:10 | 0.299314E+10 | 2160.55 | 01-NOV-07:10 |
December | 0.169848E+10 | 2587.92 | 01-DEC-08:09 | 0.300922E+10 | 2160.55 | 01-DEC-08:09 |
Annual Sum or Average | 0.174955E+11 | 0.363654E+11 | ||||
Minimum of Months | 0.125481E+10 | 1231.33 | 0.277008E+10 | 2160.55 | ||
Maximum of Months | 0.170446E+10 | 2587.92 | 0.318369E+10 | 2160.55 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.106624E+10 | 1667.75 | 02-JAN-08:09 | 0.197184E+10 | 1392.34 | 02-JAN-08:09 |
February | 0.880432E+09 | 1667.75 | 02-FEB-16:00 | 0.178515E+10 | 1392.34 | 01-FEB-08:09 |
March | 0.985553E+09 | 1453.34 | 03-MAR-16:49 | 0.205169E+10 | 1392.34 | 01-MAR-08:09 |
April | 0.841959E+09 | 870.51 | 03-APR-07:10 | 0.190407E+10 | 1392.34 | 03-APR-07:10 |
May | 0.876502E+09 | 793.52 | 01-MAY-07:10 | 0.201177E+10 | 1392.34 | 01-MAY-07:10 |
June | 0.863337E+09 | 870.51 | 09-JUN-07:10 | 0.197572E+10 | 1392.34 | 01-JUN-07:10 |
July | 0.814954E+09 | 793.52 | 03-JUL-07:10 | 0.193969E+10 | 1392.34 | 03-JUL-07:10 |
August | 0.931491E+09 | 1161.92 | 31-AUG-07:10 | 0.205169E+10 | 1392.34 | 01-AUG-07:10 |
September | 0.859975E+09 | 1161.92 | 19-SEP-07:10 | 0.190321E+10 | 1392.34 | 01-SEP-07:10 |
October | 0.949453E+09 | 1667.75 | 26-OCT-07:10 | 0.197228E+10 | 1392.34 | 02-OCT-07:10 |
November | 0.104020E+10 | 1667.75 | 01-NOV-07:10 | 0.192889E+10 | 1392.34 | 01-NOV-07:10 |
December | 0.106477E+10 | 1667.75 | 01-DEC-16:19 | 0.193926E+10 | 1392.34 | 01-DEC-08:09 |
Annual Sum or Average | 0.111749E+11 | 0.234352E+11 | ||||
Minimum of Months | 0.814954E+09 | 793.52 | 0.178515E+10 | 1392.34 | ||
Maximum of Months | 0.106624E+10 | 1667.75 | 0.205169E+10 | 1392.34 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.160916E+10 | 2587.98 | 02-JAN-08:09 | 0.305983E+10 | 2160.58 | 02-JAN-08:09 |
February | 0.134265E+10 | 2255.25 | 02-FEB-16:49 | 0.277013E+10 | 2160.58 | 01-FEB-08:09 |
March | 0.152370E+10 | 2255.25 | 03-MAR-16:00 | 0.318374E+10 | 2160.58 | 01-MAR-08:09 |
April | 0.130846E+10 | 1470.31 | 03-APR-07:10 | 0.295467E+10 | 2160.58 | 03-APR-07:10 |
May | 0.136224E+10 | 1231.36 | 01-MAY-07:10 | 0.312179E+10 | 2160.58 | 01-MAY-07:10 |
June | 0.134232E+10 | 1470.31 | 30-JUN-07:10 | 0.306585E+10 | 2160.58 | 01-JUN-07:10 |
July | 0.126639E+10 | 1231.36 | 03-JUL-07:10 | 0.300994E+10 | 2160.58 | 03-JUL-07:10 |
August | 0.144790E+10 | 1803.04 | 31-AUG-07:10 | 0.318374E+10 | 2160.58 | 01-AUG-07:10 |
September | 0.133407E+10 | 1803.04 | 19-SEP-07:10 | 0.295333E+10 | 2160.58 | 01-SEP-07:10 |
October | 0.145983E+10 | 2587.98 | 26-OCT-07:10 | 0.306051E+10 | 2160.58 | 02-OCT-07:10 |
November | 0.157656E+10 | 2587.98 | 01-NOV-07:10 | 0.299318E+10 | 2160.58 | 01-NOV-07:10 |
December | 0.160990E+10 | 2587.98 | 01-DEC-16:19 | 0.300927E+10 | 2160.58 | 01-DEC-08:09 |
Annual Sum or Average | 0.171832E+11 | 0.363660E+11 | ||||
Minimum of Months | 0.126639E+10 | 1231.36 | 0.277013E+10 | 2160.58 | ||
Maximum of Months | 0.160990E+10 | 2587.98 | 0.318374E+10 | 2160.58 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.106564E+10 | 1667.75 | 02-JAN-08:09 | 0.197183E+10 | 1392.33 | 02-JAN-08:09 |
February | 0.874156E+09 | 1453.34 | 01-FEB-08:09 | 0.178514E+10 | 1392.33 | 01-FEB-08:09 |
March | 0.986835E+09 | 1453.34 | 13-MAR-07:10 | 0.205168E+10 | 1392.33 | 01-MAR-08:09 |
April | 0.840656E+09 | 947.51 | 03-APR-07:10 | 0.190406E+10 | 1392.33 | 03-APR-07:10 |
May | 0.871851E+09 | 870.51 | 12-MAY-07:10 | 0.201175E+10 | 1392.33 | 01-MAY-07:10 |
June | 0.857736E+09 | 947.51 | 09-JUN-07:10 | 0.197570E+10 | 1392.33 | 01-JUN-07:10 |
July | 0.809486E+09 | 870.51 | 03-JUL-07:10 | 0.193968E+10 | 1392.33 | 03-JUL-07:10 |
August | 0.930662E+09 | 1161.92 | 28-AUG-07:10 | 0.205168E+10 | 1392.33 | 01-AUG-07:10 |
September | 0.861601E+09 | 1161.92 | 12-SEP-07:10 | 0.190319E+10 | 1392.33 | 01-SEP-07:10 |
October | 0.955909E+09 | 1667.75 | 26-OCT-07:10 | 0.197226E+10 | 1392.33 | 02-OCT-07:10 |
November | 0.103325E+10 | 1667.75 | 01-NOV-07:10 | 0.192888E+10 | 1392.33 | 01-NOV-07:10 |
December | 0.106146E+10 | 1667.75 | 01-DEC-08:09 | 0.193924E+10 | 1392.33 | 01-DEC-08:09 |
Annual Sum or Average | 0.111492E+11 | 0.234351E+11 | ||||
Minimum of Months | 0.809486E+09 | 870.51 | 0.178514E+10 | 1392.33 | ||
Maximum of Months | 0.106564E+10 | 1667.75 | 0.205168E+10 | 1392.33 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.169906E+10 | 2587.92 | 02-JAN-08:09 | 0.305979E+10 | 2160.55 | 02-JAN-08:09 |
February | 0.137980E+10 | 2255.20 | 01-FEB-08:09 | 0.277008E+10 | 2160.55 | 01-FEB-08:09 |
March | 0.153867E+10 | 2255.20 | 03-MAR-16:49 | 0.318369E+10 | 2160.55 | 01-MAR-08:09 |
April | 0.130502E+10 | 1470.28 | 03-APR-07:10 | 0.295462E+10 | 2160.55 | 03-APR-07:10 |
May | 0.134995E+10 | 1231.33 | 01-MAY-07:10 | 0.312174E+10 | 2160.55 | 01-MAY-07:10 |
June | 0.132739E+10 | 1350.81 | 09-JUN-07:10 | 0.306580E+10 | 2160.55 | 01-JUN-07:10 |
July | 0.125444E+10 | 1231.33 | 03-JUL-07:10 | 0.300989E+10 | 2160.55 | 03-JUL-07:10 |
August | 0.144185E+10 | 1803.00 | 31-AUG-07:10 | 0.318369E+10 | 2160.55 | 01-AUG-07:10 |
September | 0.133628E+10 | 1803.00 | 19-SEP-07:10 | 0.295328E+10 | 2160.55 | 01-SEP-07:10 |
October | 0.149390E+10 | 2587.92 | 26-OCT-07:10 | 0.306046E+10 | 2160.55 | 02-OCT-07:10 |
November | 0.164276E+10 | 2587.92 | 01-NOV-07:10 | 0.299314E+10 | 2160.55 | 01-NOV-07:10 |
December | 0.169256E+10 | 2587.92 | 01-DEC-08:09 | 0.300922E+10 | 2160.55 | 01-DEC-08:09 |
Annual Sum or Average | 0.174617E+11 | 0.363654E+11 | ||||
Minimum of Months | 0.125444E+10 | 1231.33 | 0.277008E+10 | 2160.55 | ||
Maximum of Months | 0.169906E+10 | 2587.92 | 0.318369E+10 | 2160.55 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.106403E+10 | 1667.75 | 02-JAN-08:09 | 0.197184E+10 | 1392.34 | 02-JAN-08:09 |
February | 0.879560E+09 | 1667.75 | 02-FEB-16:00 | 0.178515E+10 | 1392.34 | 01-FEB-08:09 |
March | 0.984104E+09 | 1453.34 | 03-MAR-16:49 | 0.205169E+10 | 1392.34 | 01-MAR-08:09 |
April | 0.841459E+09 | 870.51 | 03-APR-07:10 | 0.190407E+10 | 1392.34 | 03-APR-07:10 |
May | 0.875985E+09 | 793.52 | 01-MAY-07:10 | 0.201177E+10 | 1392.34 | 01-MAY-07:10 |
June | 0.862514E+09 | 870.51 | 09-JUN-07:10 | 0.197572E+10 | 1392.34 | 01-JUN-07:10 |
July | 0.814390E+09 | 793.52 | 03-JUL-07:10 | 0.193969E+10 | 1392.34 | 03-JUL-07:10 |
August | 0.930262E+09 | 1161.92 | 31-AUG-07:10 | 0.205169E+10 | 1392.34 | 01-AUG-07:10 |
September | 0.859095E+09 | 1161.92 | 19-SEP-07:10 | 0.190321E+10 | 1392.34 | 01-SEP-07:10 |
October | 0.947768E+09 | 1667.75 | 30-OCT-07:10 | 0.197228E+10 | 1392.34 | 02-OCT-07:10 |
November | 0.103814E+10 | 1667.75 | 01-NOV-07:10 | 0.192889E+10 | 1392.34 | 01-NOV-07:10 |
December | 0.106238E+10 | 1667.75 | 01-DEC-16:19 | 0.193926E+10 | 1392.34 | 01-DEC-08:09 |
Annual Sum or Average | 0.111597E+11 | 0.234352E+11 | ||||
Minimum of Months | 0.814390E+09 | 793.52 | 0.178515E+10 | 1392.34 | ||
Maximum of Months | 0.106403E+10 | 1667.75 | 0.205169E+10 | 1392.34 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.160874E+10 | 2587.98 | 02-JAN-08:09 | 0.305983E+10 | 2160.58 | 02-JAN-08:09 |
February | 0.134070E+10 | 2255.25 | 02-FEB-16:49 | 0.277013E+10 | 2160.58 | 01-FEB-08:09 |
March | 0.152220E+10 | 2255.25 | 03-MAR-16:00 | 0.318374E+10 | 2160.58 | 01-MAR-08:09 |
April | 0.130754E+10 | 1350.84 | 03-APR-07:10 | 0.295467E+10 | 2160.58 | 03-APR-07:10 |
May | 0.136129E+10 | 1231.36 | 01-MAY-07:10 | 0.312179E+10 | 2160.58 | 01-MAY-07:10 |
June | 0.134120E+10 | 1350.84 | 09-JUN-07:10 | 0.306585E+10 | 2160.58 | 01-JUN-07:10 |
July | 0.126566E+10 | 1231.36 | 03-JUL-07:10 | 0.300994E+10 | 2160.58 | 03-JUL-07:10 |
August | 0.144629E+10 | 1803.04 | 31-AUG-07:10 | 0.318374E+10 | 2160.58 | 01-AUG-07:10 |
September | 0.133245E+10 | 1803.04 | 19-SEP-07:10 | 0.295333E+10 | 2160.58 | 01-SEP-07:10 |
October | 0.145834E+10 | 2587.98 | 26-OCT-07:10 | 0.306051E+10 | 2160.58 | 02-OCT-07:10 |
November | 0.157485E+10 | 2587.98 | 01-NOV-07:10 | 0.299318E+10 | 2160.58 | 01-NOV-07:10 |
December | 0.160854E+10 | 2587.98 | 01-DEC-16:19 | 0.300927E+10 | 2160.58 | 01-DEC-08:09 |
Annual Sum or Average | 0.171678E+11 | 0.363660E+11 | ||||
Minimum of Months | 0.126566E+10 | 1231.36 | 0.277013E+10 | 2160.58 | ||
Maximum of Months | 0.160874E+10 | 2587.98 | 0.318374E+10 | 2160.58 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.106324E+10 | 1667.75 | 02-JAN-08:09 | 0.197183E+10 | 1392.33 | 02-JAN-08:09 |
February | 0.873044E+09 | 1453.34 | 01-FEB-08:09 | 0.178514E+10 | 1392.33 | 01-FEB-08:09 |
March | 0.985236E+09 | 1453.34 | 13-MAR-07:10 | 0.205168E+10 | 1392.33 | 01-MAR-08:09 |
April | 0.839823E+09 | 947.51 | 03-APR-07:10 | 0.190406E+10 | 1392.33 | 03-APR-07:10 |
May | 0.871402E+09 | 870.51 | 12-MAY-07:10 | 0.201175E+10 | 1392.33 | 01-MAY-07:10 |
June | 0.857143E+09 | 947.51 | 30-JUN-07:10 | 0.197570E+10 | 1392.33 | 01-JUN-07:10 |
July | 0.808952E+09 | 870.51 | 03-JUL-07:10 | 0.193968E+10 | 1392.33 | 03-JUL-07:10 |
August | 0.929266E+09 | 1161.92 | 28-AUG-07:10 | 0.205168E+10 | 1392.33 | 01-AUG-07:10 |
September | 0.860767E+09 | 1161.92 | 12-SEP-07:10 | 0.190319E+10 | 1392.33 | 01-SEP-07:10 |
October | 0.953878E+09 | 1667.75 | 26-OCT-07:10 | 0.197226E+10 | 1392.33 | 02-OCT-07:10 |
November | 0.103122E+10 | 1667.75 | 01-NOV-07:10 | 0.192888E+10 | 1392.33 | 01-NOV-07:10 |
December | 0.105920E+10 | 1667.75 | 01-DEC-08:09 | 0.193924E+10 | 1392.33 | 01-DEC-08:09 |
Annual Sum or Average | 0.111332E+11 | 0.234351E+11 | ||||
Minimum of Months | 0.808952E+09 | 870.51 | 0.178514E+10 | 1392.33 | ||
Maximum of Months | 0.106324E+10 | 1667.75 | 0.205168E+10 | 1392.33 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.169892E+10 | 2587.92 | 02-JAN-08:09 | 0.305979E+10 | 2160.55 | 02-JAN-08:09 |
February | 0.137980E+10 | 2255.20 | 01-FEB-08:09 | 0.277008E+10 | 2160.55 | 01-FEB-08:09 |
March | 0.153847E+10 | 2255.20 | 03-MAR-16:49 | 0.318369E+10 | 2160.55 | 01-MAR-08:09 |
April | 0.130497E+10 | 1470.28 | 03-APR-07:10 | 0.295462E+10 | 2160.55 | 03-APR-07:10 |
May | 0.134990E+10 | 1231.33 | 01-MAY-07:10 | 0.312174E+10 | 2160.55 | 01-MAY-07:10 |
June | 0.132739E+10 | 1350.81 | 09-JUN-07:10 | 0.306580E+10 | 2160.55 | 01-JUN-07:10 |
July | 0.125439E+10 | 1231.33 | 03-JUL-07:10 | 0.300989E+10 | 2160.55 | 03-JUL-07:10 |
August | 0.144183E+10 | 1803.00 | 31-AUG-07:10 | 0.318369E+10 | 2160.55 | 01-AUG-07:10 |
September | 0.133623E+10 | 1803.00 | 19-SEP-07:10 | 0.295328E+10 | 2160.55 | 01-SEP-07:10 |
October | 0.149341E+10 | 2587.92 | 26-OCT-07:10 | 0.306046E+10 | 2160.55 | 02-OCT-07:10 |
November | 0.164214E+10 | 2587.92 | 01-NOV-07:10 | 0.299314E+10 | 2160.55 | 01-NOV-07:10 |
December | 0.169241E+10 | 2587.92 | 01-DEC-08:09 | 0.300922E+10 | 2160.55 | 01-DEC-08:09 |
Annual Sum or Average | 0.174599E+11 | 0.363654E+11 | ||||
Minimum of Months | 0.125439E+10 | 1231.33 | 0.277008E+10 | 2160.55 | ||
Maximum of Months | 0.169892E+10 | 2587.92 | 0.318369E+10 | 2160.55 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.106398E+10 | 1667.75 | 02-JAN-08:09 | 0.197184E+10 | 1392.34 | 02-JAN-08:09 |
February | 0.879577E+09 | 1667.75 | 02-FEB-16:00 | 0.178515E+10 | 1392.34 | 01-FEB-08:09 |
March | 0.983743E+09 | 1453.34 | 03-MAR-16:49 | 0.205169E+10 | 1392.34 | 01-MAR-08:09 |
April | 0.841487E+09 | 870.51 | 03-APR-07:10 | 0.190407E+10 | 1392.34 | 03-APR-07:10 |
May | 0.875952E+09 | 793.52 | 01-MAY-07:10 | 0.201177E+10 | 1392.34 | 01-MAY-07:10 |
June | 0.862514E+09 | 870.51 | 09-JUN-07:10 | 0.197572E+10 | 1392.34 | 01-JUN-07:10 |
July | 0.814373E+09 | 793.52 | 03-JUL-07:10 | 0.193969E+10 | 1392.34 | 03-JUL-07:10 |
August | 0.930262E+09 | 1161.92 | 31-AUG-07:10 | 0.205169E+10 | 1392.34 | 01-AUG-07:10 |
September | 0.859065E+09 | 1161.92 | 19-SEP-07:10 | 0.190321E+10 | 1392.34 | 01-SEP-07:10 |
October | 0.947633E+09 | 1667.75 | 30-OCT-07:10 | 0.197228E+10 | 1392.34 | 02-OCT-07:10 |
November | 0.103812E+10 | 1667.75 | 01-NOV-07:10 | 0.192889E+10 | 1392.34 | 01-NOV-07:10 |
December | 0.106238E+10 | 1667.75 | 01-DEC-16:19 | 0.193926E+10 | 1392.34 | 01-DEC-08:09 |
Annual Sum or Average | 0.111591E+11 | 0.234352E+11 | ||||
Minimum of Months | 0.814373E+09 | 793.52 | 0.178515E+10 | 1392.34 | ||
Maximum of Months | 0.106398E+10 | 1667.75 | 0.205169E+10 | 1392.34 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.160874E+10 | 2587.98 | 02-JAN-08:09 | 0.305983E+10 | 2160.58 | 02-JAN-08:09 |
February | 0.134070E+10 | 2255.25 | 02-FEB-16:49 | 0.277013E+10 | 2160.58 | 01-FEB-08:09 |
March | 0.152215E+10 | 2255.25 | 03-MAR-16:00 | 0.318374E+10 | 2160.58 | 01-MAR-08:09 |
April | 0.130744E+10 | 1350.84 | 03-APR-07:10 | 0.295467E+10 | 2160.58 | 03-APR-07:10 |
May | 0.136124E+10 | 1231.36 | 01-MAY-07:10 | 0.312179E+10 | 2160.58 | 01-MAY-07:10 |
June | 0.134117E+10 | 1350.84 | 09-JUN-07:10 | 0.306585E+10 | 2160.58 | 01-JUN-07:10 |
July | 0.126556E+10 | 1231.36 | 03-JUL-07:10 | 0.300994E+10 | 2160.58 | 03-JUL-07:10 |
August | 0.144620E+10 | 1803.04 | 31-AUG-07:10 | 0.318374E+10 | 2160.58 | 01-AUG-07:10 |
September | 0.133230E+10 | 1803.04 | 19-SEP-07:10 | 0.295333E+10 | 2160.58 | 01-SEP-07:10 |
October | 0.145823E+10 | 2587.98 | 26-OCT-07:10 | 0.306051E+10 | 2160.58 | 02-OCT-07:10 |
November | 0.157478E+10 | 2587.98 | 01-NOV-07:10 | 0.299318E+10 | 2160.58 | 01-NOV-07:10 |
December | 0.160814E+10 | 2587.98 | 01-DEC-16:19 | 0.300927E+10 | 2160.58 | 01-DEC-08:09 |
Annual Sum or Average | 0.171667E+11 | 0.363660E+11 | ||||
Minimum of Months | 0.126556E+10 | 1231.36 | 0.277013E+10 | 2160.58 | ||
Maximum of Months | 0.160874E+10 | 2587.98 | 0.318374E+10 | 2160.58 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.106317E+10 | 1667.75 | 02-JAN-08:09 | 0.197183E+10 | 1392.33 | 02-JAN-08:09 |
February | 0.872867E+09 | 1453.34 | 01-FEB-08:09 | 0.178514E+10 | 1392.33 | 01-FEB-08:09 |
March | 0.985190E+09 | 1453.34 | 13-MAR-07:10 | 0.205168E+10 | 1392.33 | 01-MAR-08:09 |
April | 0.839775E+09 | 947.51 | 03-APR-07:10 | 0.190406E+10 | 1392.33 | 03-APR-07:10 |
May | 0.871402E+09 | 870.51 | 12-MAY-07:10 | 0.201175E+10 | 1392.33 | 01-MAY-07:10 |
June | 0.857171E+09 | 947.51 | 30-JUN-07:10 | 0.197570E+10 | 1392.33 | 01-JUN-07:10 |
July | 0.808947E+09 | 870.51 | 03-JUL-07:10 | 0.193968E+10 | 1392.33 | 03-JUL-07:10 |
August | 0.929258E+09 | 1161.92 | 28-AUG-07:10 | 0.205168E+10 | 1392.33 | 01-AUG-07:10 |
September | 0.860589E+09 | 1161.92 | 12-SEP-07:10 | 0.190319E+10 | 1392.33 | 01-SEP-07:10 |
October | 0.953863E+09 | 1667.75 | 26-OCT-07:10 | 0.197226E+10 | 1392.33 | 02-OCT-07:10 |
November | 0.103117E+10 | 1667.75 | 01-NOV-07:10 | 0.192888E+10 | 1392.33 | 01-NOV-07:10 |
December | 0.105905E+10 | 1667.75 | 01-DEC-08:09 | 0.193924E+10 | 1392.33 | 01-DEC-08:09 |
Annual Sum or Average | 0.111325E+11 | 0.234351E+11 | ||||
Minimum of Months | 0.808947E+09 | 870.51 | 0.178514E+10 | 1392.33 | ||
Maximum of Months | 0.106317E+10 | 1667.75 | 0.205168E+10 | 1392.33 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.553024E+09 | 578.72 | 02-JAN-08:09 | 0.521915E+10 | 1948.61 | 01-JAN-00:10 |
February | 0.501634E+09 | 578.72 | 01-FEB-08:09 | 0.942813E+10 | 3897.21 | 01-FEB-00:10 |
March | 0.596080E+09 | 578.72 | 01-MAR-08:09 | 0.156645E+11 | 7794.42 | 31-MAR-23:10 |
April | 0.532421E+09 | 578.72 | 03-APR-07:10 | 0.201821E+11 | 7794.42 | 01-APR-00:10 |
May | 0.574552E+09 | 578.72 | 01-MAY-07:10 | 0.522616E+10 | 3897.21 | 31-MAY-23:10 |
June | 0.571774E+09 | 578.72 | 01-JUN-07:10 | 0.101086E+11 | 5845.82 | 30-JUN-23:10 |
July | 0.535199E+09 | 578.72 | 03-JUL-07:10 | 0.156645E+11 | 7794.42 | 31-JUL-23:10 |
August | 0.596080E+09 | 578.72 | 01-AUG-07:10 | 0.208555E+11 | 7794.42 | 01-AUG-00:10 |
September | 0.532421E+09 | 578.72 | 01-SEP-07:10 | 0.505780E+10 | 3897.21 | 30-SEP-23:10 |
October | 0.553024E+09 | 578.72 | 02-OCT-07:10 | 0.104453E+11 | 5845.82 | 31-OCT-23:10 |
November | 0.546542E+09 | 578.72 | 01-NOV-07:10 | 0.151524E+11 | 5845.82 | 01-NOV-00:10 |
December | 0.535199E+09 | 578.72 | 01-DEC-08:09 | 0.208766E+11 | 7794.42 | 01-DEC-00:10 |
Annual Sum or Average | 0.662795E+10 | 0.153881E+12 | ||||
Minimum of Months | 0.501634E+09 | 578.72 | 0.505780E+10 | 1948.61 | ||
Maximum of Months | 0.596080E+09 | 578.72 | 0.208766E+11 | 7794.42 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.553024E+09 | 578.72 | 02-JAN-08:09 | 0.521915E+10 | 1948.61 | 01-JAN-00:10 |
February | 0.501634E+09 | 578.72 | 01-FEB-08:09 | 0.942813E+10 | 3897.21 | 01-FEB-00:10 |
March | 0.596080E+09 | 578.72 | 01-MAR-08:09 | 0.156645E+11 | 7794.42 | 31-MAR-23:10 |
April | 0.532421E+09 | 578.72 | 03-APR-07:10 | 0.201821E+11 | 7794.42 | 01-APR-00:10 |
May | 0.574552E+09 | 578.72 | 01-MAY-07:10 | 0.522616E+10 | 3897.21 | 31-MAY-23:10 |
June | 0.571774E+09 | 578.72 | 01-JUN-07:10 | 0.101086E+11 | 5845.82 | 30-JUN-23:10 |
July | 0.535199E+09 | 578.72 | 03-JUL-07:10 | 0.156645E+11 | 7794.42 | 31-JUL-23:10 |
August | 0.596080E+09 | 578.72 | 01-AUG-07:10 | 0.208555E+11 | 7794.42 | 01-AUG-00:10 |
September | 0.532421E+09 | 578.72 | 01-SEP-07:10 | 0.505780E+10 | 3897.21 | 30-SEP-23:10 |
October | 0.553024E+09 | 578.72 | 02-OCT-07:10 | 0.104453E+11 | 5845.82 | 31-OCT-23:10 |
November | 0.546542E+09 | 578.72 | 01-NOV-07:10 | 0.151524E+11 | 5845.82 | 01-NOV-00:10 |
December | 0.535199E+09 | 578.72 | 01-DEC-08:09 | 0.208766E+11 | 7794.42 | 01-DEC-00:10 |
Annual Sum or Average | 0.662795E+10 | 0.153881E+12 | ||||
Minimum of Months | 0.501634E+09 | 578.72 | 0.505780E+10 | 1948.61 | ||
Maximum of Months | 0.596080E+09 | 578.72 | 0.208766E+11 | 7794.42 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.553024E+09 | 578.72 | 02-JAN-08:09 | 0.521915E+10 | 1948.61 | 01-JAN-00:10 |
February | 0.501634E+09 | 578.72 | 01-FEB-08:09 | 0.942813E+10 | 3897.21 | 01-FEB-00:10 |
March | 0.596080E+09 | 578.72 | 01-MAR-08:09 | 0.156645E+11 | 7794.42 | 31-MAR-23:10 |
April | 0.532421E+09 | 578.72 | 03-APR-07:10 | 0.201821E+11 | 7794.42 | 01-APR-00:10 |
May | 0.574552E+09 | 578.72 | 01-MAY-07:10 | 0.522616E+10 | 3897.21 | 31-MAY-23:10 |
June | 0.571774E+09 | 578.72 | 01-JUN-07:10 | 0.101086E+11 | 5845.82 | 30-JUN-23:10 |
July | 0.535199E+09 | 578.72 | 03-JUL-07:10 | 0.156645E+11 | 7794.42 | 31-JUL-23:10 |
August | 0.596080E+09 | 578.72 | 01-AUG-07:10 | 0.208555E+11 | 7794.42 | 01-AUG-00:10 |
September | 0.532421E+09 | 578.72 | 01-SEP-07:10 | 0.505780E+10 | 3897.21 | 30-SEP-23:10 |
October | 0.553024E+09 | 578.72 | 02-OCT-07:10 | 0.104453E+11 | 5845.82 | 31-OCT-23:10 |
November | 0.546542E+09 | 578.72 | 01-NOV-07:10 | 0.151524E+11 | 5845.82 | 01-NOV-00:10 |
December | 0.535199E+09 | 578.72 | 01-DEC-08:09 | 0.208766E+11 | 7794.42 | 01-DEC-00:10 |
Annual Sum or Average | 0.662795E+10 | 0.153881E+12 | ||||
Minimum of Months | 0.501634E+09 | 578.72 | 0.505780E+10 | 1948.61 | ||
Maximum of Months | 0.596080E+09 | 578.72 | 0.208766E+11 | 7794.42 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.618367E+10 | 6471.01 | 02-JAN-08:09 | 0.254202E+12 | 94908.13 | 01-JAN-00:10 |
February | 0.560905E+10 | 6471.01 | 01-FEB-08:09 | 0.459203E+12 | 189816.26 | 01-FEB-00:10 |
March | 0.666512E+10 | 6471.01 | 01-MAR-08:09 | 0.762947E+12 | 379632.52 | 31-MAR-23:10 |
April | 0.595330E+10 | 6471.01 | 03-APR-07:10 | 0.982982E+12 | 379632.52 | 01-APR-00:10 |
May | 0.642439E+10 | 6471.01 | 01-MAY-07:10 | 0.254544E+12 | 189816.26 | 31-MAY-23:10 |
June | 0.639333E+10 | 6471.01 | 01-JUN-07:10 | 0.492345E+12 | 284724.39 | 30-JUN-23:10 |
July | 0.598436E+10 | 6471.01 | 03-JUL-07:10 | 0.762947E+12 | 379632.52 | 31-JUL-23:10 |
August | 0.666512E+10 | 6471.01 | 01-AUG-07:10 | 0.101578E+13 | 379632.52 | 01-AUG-00:10 |
September | 0.595330E+10 | 6471.01 | 01-SEP-07:10 | 0.246344E+12 | 189816.26 | 30-SEP-23:10 |
October | 0.618367E+10 | 6471.01 | 02-OCT-07:10 | 0.508746E+12 | 284724.39 | 31-OCT-23:10 |
November | 0.611120E+10 | 6471.01 | 01-NOV-07:10 | 0.738006E+12 | 284724.39 | 01-NOV-00:10 |
December | 0.598436E+10 | 6471.01 | 01-DEC-08:09 | 0.101681E+13 | 379632.52 | 01-DEC-00:10 |
Annual Sum or Average | 0.741109E+11 | 0.749486E+13 | ||||
Minimum of Months | 0.560905E+10 | 6471.01 | 0.246344E+12 | 94908.13 | ||
Maximum of Months | 0.666512E+10 | 6471.01 | 0.101681E+13 | 379632.52 |
Report: SpaceGainsMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.133902E+11 | 0.219312E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.121482E+11 | 0.198933E+11 | 0.325565E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.145160E+11 | 0.236388E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.128805E+11 | 0.211142E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.139531E+11 | 0.227850E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.139143E+11 | 0.226748E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.129193E+11 | 0.212244E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.145160E+11 | 0.236388E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.128805E+11 | 0.211142E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.133902E+11 | 0.219312E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.132595E+11 | 0.216742E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.129193E+11 | 0.212244E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.160687E+12 | 0.262844E+12 | 0.424397E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.121482E+11 | 0.198933E+11 | 0.325565E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.145160E+11 | 0.236388E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.120254E+11 | 0.196958E+11 | 0.243681E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.109099E+11 | 0.178655E+11 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.130364E+11 | 0.212293E+11 | 0.253549E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.115676E+11 | 0.189620E+11 | 0.235306E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.125309E+11 | 0.204625E+11 | 0.248615E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.124961E+11 | 0.203636E+11 | 0.244160E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.116025E+11 | 0.190610E+11 | 0.239708E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.130364E+11 | 0.212293E+11 | 0.253549E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.115676E+11 | 0.189620E+11 | 0.235199E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.120254E+11 | 0.196958E+11 | 0.243735E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.119080E+11 | 0.194649E+11 | 0.238373E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.116025E+11 | 0.190610E+11 | 0.239654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.144308E+12 | 0.236053E+12 | 0.289614E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.109099E+11 | 0.178655E+11 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.130364E+11 | 0.212293E+11 | 0.253549E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.120254E+11 | 0.196958E+11 | 0.243680E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.109099E+11 | 0.178655E+11 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.130364E+11 | 0.212293E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.115676E+11 | 0.189620E+11 | 0.235305E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.125309E+11 | 0.204625E+11 | 0.248614E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.124961E+11 | 0.203636E+11 | 0.244159E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.116025E+11 | 0.190610E+11 | 0.239707E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.130364E+11 | 0.212293E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.115676E+11 | 0.189620E+11 | 0.235198E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.120254E+11 | 0.196958E+11 | 0.243734E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.119080E+11 | 0.194649E+11 | 0.238372E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.116025E+11 | 0.190610E+11 | 0.239653E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.144308E+12 | 0.236053E+12 | 0.289613E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.109099E+11 | 0.178655E+11 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.130364E+11 | 0.212293E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.120254E+11 | 0.196958E+11 | 0.243680E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.109099E+11 | 0.178655E+11 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.130364E+11 | 0.212293E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.115676E+11 | 0.189620E+11 | 0.235305E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.125309E+11 | 0.204625E+11 | 0.248614E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.124961E+11 | 0.203636E+11 | 0.244159E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.116025E+11 | 0.190610E+11 | 0.239707E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.130364E+11 | 0.212293E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.115676E+11 | 0.189620E+11 | 0.235198E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.120254E+11 | 0.196958E+11 | 0.243734E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.119080E+11 | 0.194649E+11 | 0.238372E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.116025E+11 | 0.190610E+11 | 0.239653E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.144308E+12 | 0.236053E+12 | 0.289613E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.109099E+11 | 0.178655E+11 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.130364E+11 | 0.212293E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150991E+10 | 0.170446E+10 | 0.305979E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.163263E+10 |
February | 0.136985E+10 | 0.138330E+10 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.144736E+10 |
March | 0.163685E+10 | 0.154201E+10 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.100233E+10 |
April | 0.145243E+10 | 0.130619E+10 | 0.295462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 414580.79 | 0.966040E+09 |
May | 0.157338E+10 | 0.135053E+10 | 0.312174E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2792396.76 | 0.455175E+09 |
June | 0.156900E+10 | 0.132866E+10 | 0.306580E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10939972.21 | 0.248875E+09 |
July | 0.145680E+10 | 0.125481E+10 | 0.300989E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12782102.91 | 0.174953E+09 |
August | 0.163685E+10 | 0.144311E+10 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4274497.53 | 0.248438E+09 |
September | 0.145243E+10 | 0.133798E+10 | 0.295328E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 140598.34 | 0.435427E+09 |
October | 0.150991E+10 | 0.149888E+10 | 0.306046E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.678450E+09 |
November | 0.149516E+10 | 0.164710E+10 | 0.299314E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.118882E+10 |
December | 0.145680E+10 | 0.169848E+10 | 0.300922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.176797E+10 |
Annual Sum or Average | 0.181194E+11 | 0.174955E+11 | 0.363654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 31344148.55 | 0.102465E+11 |
Minimum of Months | 0.136985E+10 | 0.125481E+10 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.174953E+09 |
Maximum of Months | 0.163685E+10 | 0.170446E+10 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12782102.91 | 0.176797E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.106624E+10 | 0.197184E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.108558E+10 |
February | 0.882782E+09 | 0.880432E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.965330E+09 |
March | 0.105485E+10 | 0.985553E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.666641E+09 |
April | 0.936002E+09 | 0.841959E+09 | 0.190407E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 881253.78 | 0.633728E+09 |
May | 0.101394E+10 | 0.876502E+09 | 0.201177E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1865492.33 | 0.302618E+09 |
June | 0.101113E+10 | 0.863337E+09 | 0.197572E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8311495.76 | 0.161037E+09 |
July | 0.938820E+09 | 0.814954E+09 | 0.193969E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9268931.82 | 0.105384E+09 |
August | 0.105485E+10 | 0.931491E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2911072.61 | 0.155142E+09 |
September | 0.936002E+09 | 0.859975E+09 | 0.190321E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 93729.57 | 0.286060E+09 |
October | 0.973041E+09 | 0.949453E+09 | 0.197228E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.442579E+09 |
November | 0.963541E+09 | 0.104020E+10 | 0.192889E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.777874E+09 |
December | 0.938820E+09 | 0.106477E+10 | 0.193926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.116816E+10 |
Annual Sum or Average | 0.116768E+11 | 0.111749E+11 | 0.234352E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 23331975.87 | 0.675013E+10 |
Minimum of Months | 0.882782E+09 | 0.814954E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.105384E+09 |
Maximum of Months | 0.105485E+10 | 0.106624E+10 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9268931.82 | 0.116816E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150994E+10 | 0.160916E+10 | 0.305983E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.164036E+10 |
February | 0.136988E+10 | 0.134265E+10 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.147336E+10 |
March | 0.163688E+10 | 0.152370E+10 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.101685E+10 |
April | 0.145246E+10 | 0.130846E+10 | 0.295467E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12226.31 | 0.964463E+09 |
May | 0.157341E+10 | 0.136224E+10 | 0.312179E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2790705.32 | 0.452771E+09 |
June | 0.156904E+10 | 0.134232E+10 | 0.306585E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11434036.50 | 0.242042E+09 |
July | 0.145684E+10 | 0.126639E+10 | 0.300994E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12654364.71 | 0.168825E+09 |
August | 0.163688E+10 | 0.144790E+10 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4246740.74 | 0.249377E+09 |
September | 0.145246E+10 | 0.133407E+10 | 0.295333E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 132687.05 | 0.443808E+09 |
October | 0.150994E+10 | 0.145983E+10 | 0.306051E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.674807E+09 |
November | 0.149520E+10 | 0.157656E+10 | 0.299318E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.117568E+10 |
December | 0.145684E+10 | 0.160990E+10 | 0.300927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.177311E+10 |
Annual Sum or Average | 0.181198E+11 | 0.171832E+11 | 0.363660E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 31270760.62 | 0.102754E+11 |
Minimum of Months | 0.136988E+10 | 0.126639E+10 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.168825E+09 |
Maximum of Months | 0.163688E+10 | 0.160990E+10 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12654364.71 | 0.177311E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.106564E+10 | 0.197183E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.111400E+10 |
February | 0.882782E+09 | 0.874156E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.101162E+10 |
March | 0.105485E+10 | 0.986835E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.711823E+09 |
April | 0.936002E+09 | 0.840656E+09 | 0.190406E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 24.65 | 0.706613E+09 |
May | 0.101394E+10 | 0.871851E+09 | 0.201175E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1861568.26 | 0.323529E+09 |
June | 0.101113E+10 | 0.857736E+09 | 0.197570E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7021740.22 | 0.182222E+09 |
July | 0.938820E+09 | 0.809486E+09 | 0.193968E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8095949.52 | 0.131651E+09 |
August | 0.105485E+10 | 0.930662E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2820020.25 | 0.189105E+09 |
September | 0.936002E+09 | 0.861601E+09 | 0.190319E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 93647.46 | 0.308238E+09 |
October | 0.973041E+09 | 0.955909E+09 | 0.197226E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.480679E+09 |
November | 0.963541E+09 | 0.103325E+10 | 0.192888E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.841124E+09 |
December | 0.938820E+09 | 0.106146E+10 | 0.193924E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.124447E+10 |
Annual Sum or Average | 0.116768E+11 | 0.111492E+11 | 0.234351E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 19892950.36 | 0.724507E+10 |
Minimum of Months | 0.882782E+09 | 0.809486E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.131651E+09 |
Maximum of Months | 0.105485E+10 | 0.106564E+10 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8095949.52 | 0.124447E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150991E+10 | 0.169906E+10 | 0.305979E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.363628E+10 |
February | 0.136985E+10 | 0.137980E+10 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.311227E+10 |
March | 0.163685E+10 | 0.153867E+10 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.215157E+10 |
April | 0.145243E+10 | 0.130502E+10 | 0.295462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3727563.50 | 0.197947E+10 |
May | 0.157338E+10 | 0.134995E+10 | 0.312174E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6205313.05 | 0.996676E+09 |
June | 0.156900E+10 | 0.132739E+10 | 0.306580E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 24591611.68 | 0.548024E+09 |
July | 0.145680E+10 | 0.125444E+10 | 0.300989E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 28811367.15 | 0.400810E+09 |
August | 0.163685E+10 | 0.144185E+10 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9889207.07 | 0.542294E+09 |
September | 0.145243E+10 | 0.133628E+10 | 0.295328E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 300627.99 | 0.925593E+09 |
October | 0.150991E+10 | 0.149390E+10 | 0.306046E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.138061E+10 |
November | 0.149516E+10 | 0.164276E+10 | 0.299314E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.245431E+10 |
December | 0.145680E+10 | 0.169256E+10 | 0.300922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.386845E+10 |
Annual Sum or Average | 0.181194E+11 | 0.174617E+11 | 0.363654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 73525690.43 | 0.219964E+11 |
Minimum of Months | 0.136985E+10 | 0.125444E+10 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.400810E+09 |
Maximum of Months | 0.163685E+10 | 0.169906E+10 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 28811367.15 | 0.386845E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.715730E+09 | 0.106403E+10 | 0.197184E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.243549E+10 |
February | 0.649041E+09 | 0.879560E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.209253E+10 |
March | 0.773965E+09 | 0.984104E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.146264E+10 |
April | 0.688021E+09 | 0.841459E+09 | 0.190407E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2888576.93 | 0.136567E+10 |
May | 0.744847E+09 | 0.875985E+09 | 0.201177E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4162966.41 | 0.680158E+09 |
June | 0.742030E+09 | 0.862514E+09 | 0.197572E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17708473.66 | 0.366802E+09 |
July | 0.690839E+09 | 0.814390E+09 | 0.193969E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19721778.29 | 0.261680E+09 |
August | 0.773965E+09 | 0.930262E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6555244.19 | 0.370238E+09 |
September | 0.688021E+09 | 0.859095E+09 | 0.190321E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 200384.17 | 0.622171E+09 |
October | 0.715730E+09 | 0.947768E+09 | 0.197228E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.931101E+09 |
November | 0.708685E+09 | 0.103814E+10 | 0.192889E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.164516E+10 |
December | 0.690839E+09 | 0.106238E+10 | 0.193926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.258728E+10 |
Annual Sum or Average | 0.858171E+10 | 0.111597E+11 | 0.234352E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 51237423.65 | 0.148209E+11 |
Minimum of Months | 0.649041E+09 | 0.814390E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.261680E+09 |
Maximum of Months | 0.773965E+09 | 0.106403E+10 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19721778.29 | 0.258728E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150994E+10 | 0.160874E+10 | 0.305983E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.370246E+10 |
February | 0.136988E+10 | 0.134070E+10 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.327367E+10 |
March | 0.163688E+10 | 0.152220E+10 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.228339E+10 |
April | 0.145246E+10 | 0.130754E+10 | 0.295467E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7261.63 | 0.211994E+10 |
May | 0.157341E+10 | 0.136129E+10 | 0.312179E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6199931.59 | 0.102530E+10 |
June | 0.156904E+10 | 0.134120E+10 | 0.306585E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 24942679.42 | 0.544805E+09 |
July | 0.145684E+10 | 0.126566E+10 | 0.300994E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 27769110.32 | 0.403542E+09 |
August | 0.163688E+10 | 0.144629E+10 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9489270.43 | 0.580506E+09 |
September | 0.145246E+10 | 0.133245E+10 | 0.295333E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 256825.47 | 0.999284E+09 |
October | 0.150994E+10 | 0.145834E+10 | 0.306051E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.148248E+10 |
November | 0.149520E+10 | 0.157485E+10 | 0.299318E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.255916E+10 |
December | 0.145684E+10 | 0.160854E+10 | 0.300927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.394027E+10 |
Annual Sum or Average | 0.181198E+11 | 0.171678E+11 | 0.363660E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 68665078.86 | 0.229148E+11 |
Minimum of Months | 0.136988E+10 | 0.126566E+10 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.403542E+09 |
Maximum of Months | 0.163688E+10 | 0.160874E+10 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 27769110.32 | 0.394027E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.106324E+10 | 0.197183E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.244547E+10 |
February | 0.882782E+09 | 0.873044E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.212483E+10 |
March | 0.105485E+10 | 0.985236E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.149276E+10 |
April | 0.936002E+09 | 0.839823E+09 | 0.190406E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.139659E+10 |
May | 0.101394E+10 | 0.871402E+09 | 0.201175E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4136862.19 | 0.703806E+09 |
June | 0.101113E+10 | 0.857143E+09 | 0.197570E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16895636.81 | 0.379579E+09 |
July | 0.938820E+09 | 0.808952E+09 | 0.193968E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18855761.35 | 0.290619E+09 |
August | 0.105485E+10 | 0.929266E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6558349.81 | 0.392846E+09 |
September | 0.936002E+09 | 0.860767E+09 | 0.190319E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 200810.09 | 0.641795E+09 |
October | 0.973041E+09 | 0.953878E+09 | 0.197226E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.954898E+09 |
November | 0.963541E+09 | 0.103122E+10 | 0.192888E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.166797E+10 |
December | 0.938820E+09 | 0.105920E+10 | 0.193924E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.260477E+10 |
Annual Sum or Average | 0.116768E+11 | 0.111332E+11 | 0.234351E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 46647420.26 | 0.150959E+11 |
Minimum of Months | 0.882782E+09 | 0.808952E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.290619E+09 |
Maximum of Months | 0.105485E+10 | 0.106324E+10 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18855761.35 | 0.260477E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150991E+10 | 0.169892E+10 | 0.305979E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.449124E+10 |
February | 0.136985E+10 | 0.137980E+10 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.382652E+10 |
March | 0.163685E+10 | 0.153847E+10 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.259401E+10 |
April | 0.145243E+10 | 0.130497E+10 | 0.295462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5985609.35 | 0.228762E+10 |
May | 0.157338E+10 | 0.134990E+10 | 0.312174E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7290675.04 | 0.117198E+10 |
June | 0.156900E+10 | 0.132739E+10 | 0.306580E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 29332388.36 | 0.652354E+09 |
July | 0.145680E+10 | 0.125439E+10 | 0.300989E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 33986498.80 | 0.483258E+09 |
August | 0.163685E+10 | 0.144183E+10 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11956316.07 | 0.647962E+09 |
September | 0.145243E+10 | 0.133623E+10 | 0.295328E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 339658.65 | 0.106648E+10 |
October | 0.150991E+10 | 0.149341E+10 | 0.306046E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.156906E+10 |
November | 0.149516E+10 | 0.164214E+10 | 0.299314E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.294696E+10 |
December | 0.145680E+10 | 0.169241E+10 | 0.300922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.476718E+10 |
Annual Sum or Average | 0.181194E+11 | 0.174599E+11 | 0.363654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 88891146.26 | 0.265046E+11 |
Minimum of Months | 0.136985E+10 | 0.125439E+10 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.483258E+09 |
Maximum of Months | 0.163685E+10 | 0.169892E+10 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 33986498.80 | 0.476718E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.106398E+10 | 0.197184E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.301471E+10 |
February | 0.882782E+09 | 0.879577E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.256830E+10 |
March | 0.105485E+10 | 0.983743E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.176063E+10 |
April | 0.936002E+09 | 0.841487E+09 | 0.190407E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3821758.77 | 0.159591E+10 |
May | 0.101394E+10 | 0.875952E+09 | 0.201177E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4875408.21 | 0.814000E+09 |
June | 0.101113E+10 | 0.862514E+09 | 0.197572E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20832859.24 | 0.444558E+09 |
July | 0.938820E+09 | 0.814373E+09 | 0.193969E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22934027.42 | 0.320224E+09 |
August | 0.105485E+10 | 0.930262E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7692366.13 | 0.453009E+09 |
September | 0.936002E+09 | 0.859065E+09 | 0.190321E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 226424.81 | 0.734595E+09 |
October | 0.973041E+09 | 0.947633E+09 | 0.197228E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.107045E+10 |
November | 0.963541E+09 | 0.103812E+10 | 0.192889E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.197189E+10 |
December | 0.938820E+09 | 0.106238E+10 | 0.193926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.319721E+10 |
Annual Sum or Average | 0.116768E+11 | 0.111591E+11 | 0.234352E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 60382844.58 | 0.179455E+11 |
Minimum of Months | 0.882782E+09 | 0.814373E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.320224E+09 |
Maximum of Months | 0.105485E+10 | 0.106398E+10 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22934027.42 | 0.319721E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150994E+10 | 0.160874E+10 | 0.305983E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.455651E+10 |
February | 0.136988E+10 | 0.134070E+10 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.396767E+10 |
March | 0.163688E+10 | 0.152215E+10 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.274021E+10 |
April | 0.145246E+10 | 0.130744E+10 | 0.295467E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4921.07 | 0.247024E+10 |
May | 0.157341E+10 | 0.136124E+10 | 0.312179E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7285345.55 | 0.121980E+10 |
June | 0.156904E+10 | 0.134117E+10 | 0.306585E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 29658282.01 | 0.651768E+09 |
July | 0.145684E+10 | 0.126556E+10 | 0.300994E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 32726203.41 | 0.488322E+09 |
August | 0.163688E+10 | 0.144620E+10 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11201690.37 | 0.701578E+09 |
September | 0.145246E+10 | 0.133230E+10 | 0.295333E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 303693.47 | 0.117917E+10 |
October | 0.150994E+10 | 0.145823E+10 | 0.306051E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.170336E+10 |
November | 0.149520E+10 | 0.157478E+10 | 0.299318E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.302993E+10 |
December | 0.145684E+10 | 0.160814E+10 | 0.300927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.483304E+10 |
Annual Sum or Average | 0.181198E+11 | 0.171667E+11 | 0.363660E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 81180135.88 | 0.275416E+11 |
Minimum of Months | 0.136988E+10 | 0.126556E+10 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.488322E+09 |
Maximum of Months | 0.163688E+10 | 0.160874E+10 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 32726203.41 | 0.483304E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.106317E+10 | 0.197183E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.302205E+10 |
February | 0.882782E+09 | 0.872867E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.259780E+10 |
March | 0.105485E+10 | 0.985190E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.179985E+10 |
April | 0.936002E+09 | 0.839775E+09 | 0.190406E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.163936E+10 |
May | 0.101394E+10 | 0.871402E+09 | 0.201175E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4860458.81 | 0.843248E+09 |
June | 0.101113E+10 | 0.857171E+09 | 0.197570E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20111851.38 | 0.457642E+09 |
July | 0.938820E+09 | 0.808947E+09 | 0.193968E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22328074.99 | 0.353849E+09 |
August | 0.105485E+10 | 0.929258E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7813709.66 | 0.476180E+09 |
September | 0.936002E+09 | 0.860589E+09 | 0.190319E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 226337.17 | 0.758933E+09 |
October | 0.973041E+09 | 0.953863E+09 | 0.197226E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.110988E+10 |
November | 0.963541E+09 | 0.103117E+10 | 0.192888E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.199705E+10 |
December | 0.938820E+09 | 0.105905E+10 | 0.193924E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.321040E+10 |
Annual Sum or Average | 0.116768E+11 | 0.111325E+11 | 0.234351E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 55340432.01 | 0.182662E+11 |
Minimum of Months | 0.882782E+09 | 0.808947E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.353849E+09 |
Maximum of Months | 0.105485E+10 | 0.106317E+10 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22328074.99 | 0.321040E+10 |
Report: SpaceGainsMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.174411E+09 | 0.553024E+09 | 0.521915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.158233E+09 | 0.501634E+09 | 0.942813E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.189074E+09 | 0.596080E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.167772E+09 | 0.532421E+09 | 0.201821E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.181743E+09 | 0.574552E+09 | 0.522616E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.181238E+09 | 0.571774E+09 | 0.101086E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.168277E+09 | 0.535199E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.189074E+09 | 0.596080E+09 | 0.208555E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.167772E+09 | 0.532421E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.174411E+09 | 0.553024E+09 | 0.104453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.172708E+09 | 0.546542E+09 | 0.151524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.168277E+09 | 0.535199E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.209299E+10 | 0.662795E+10 | 0.153881E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.158233E+09 | 0.501634E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.189074E+09 | 0.596080E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.174411E+09 | 0.553024E+09 | 0.521915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.158233E+09 | 0.501634E+09 | 0.942813E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.189074E+09 | 0.596080E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.167772E+09 | 0.532421E+09 | 0.201821E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.181743E+09 | 0.574552E+09 | 0.522616E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.181238E+09 | 0.571774E+09 | 0.101086E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.168277E+09 | 0.535199E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.189074E+09 | 0.596080E+09 | 0.208555E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.167772E+09 | 0.532421E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.174411E+09 | 0.553024E+09 | 0.104453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.172708E+09 | 0.546542E+09 | 0.151524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.168277E+09 | 0.535199E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.209299E+10 | 0.662795E+10 | 0.153881E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.158233E+09 | 0.501634E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.189074E+09 | 0.596080E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.174411E+09 | 0.553024E+09 | 0.521915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.158233E+09 | 0.501634E+09 | 0.942813E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.189074E+09 | 0.596080E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.167772E+09 | 0.532421E+09 | 0.201821E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.181743E+09 | 0.574552E+09 | 0.522616E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.181238E+09 | 0.571774E+09 | 0.101086E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.168277E+09 | 0.535199E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.189074E+09 | 0.596080E+09 | 0.208555E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.167772E+09 | 0.532421E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.174411E+09 | 0.553024E+09 | 0.104453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.172708E+09 | 0.546542E+09 | 0.151524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.168277E+09 | 0.535199E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.209299E+10 | 0.662795E+10 | 0.153881E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.158233E+09 | 0.501634E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.189074E+09 | 0.596080E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.377547E+10 | 0.618367E+10 | 0.254202E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.342526E+10 | 0.560905E+10 | 0.459203E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.409289E+10 | 0.666512E+10 | 0.762947E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.363176E+10 | 0.595330E+10 | 0.982982E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.393418E+10 | 0.642439E+10 | 0.254544E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.392325E+10 | 0.639333E+10 | 0.492345E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.364269E+10 | 0.598436E+10 | 0.762947E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.409289E+10 | 0.666512E+10 | 0.101578E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.363176E+10 | 0.595330E+10 | 0.246344E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.377547E+10 | 0.618367E+10 | 0.508746E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.373861E+10 | 0.611120E+10 | 0.738006E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.364269E+10 | 0.598436E+10 | 0.101681E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.453069E+11 | 0.741109E+11 | 0.749486E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.342526E+10 | 0.560905E+10 | 0.246344E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.409289E+10 | 0.666512E+10 | 0.101681E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.347201E+10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.312607E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.215598E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 648087.57 | 0.206180E+10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3893515.97 | 0.955111E+09 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19614504.01 | 0.518362E+09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22689722.85 | 0.367584E+09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6029336.29 | 0.529998E+09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 140852.37 | 0.928122E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.144944E+10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.256755E+10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.381419E+10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 53016019.06 | 0.219462E+11 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.367584E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22689722.85 | 0.381419E+10 |
Report: SpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.586871E+10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.520817E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.365084E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3565869.09 | 0.348278E+10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7047667.69 | 0.166910E+10 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36354035.69 | 0.899935E+09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41378619.08 | 0.649681E+09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10928571.85 | 0.917871E+09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 233593.31 | 0.160472E+10 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.243595E+10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.425760E+10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.634078E+10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 99508356.71 | 0.369861E+11 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.649681E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41378619.08 | 0.634078E+10 |
Report: SpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.653358E+10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.567375E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.397856E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 883804.21 | 0.369033E+10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4966367.60 | 0.186856E+10 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32531613.26 | 0.102589E+10 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30726977.03 | 0.755880E+09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8352727.32 | 0.105505E+10 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 63740.69 | 0.175256E+10 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.252109E+10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.448079E+10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.696245E+10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 77525230.11 | 0.402985E+11 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.755880E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32531613.26 | 0.696245E+10 |
Report: PeakSpaceGainsMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 17832.21 | 02-JAN-10:09 | 22950.34 | 02-JAN-08:09 | 13457.54 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 17832.21 | 01-FEB-10:09 | 22950.34 | 01-FEB-08:09 | 13457.54 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 17832.21 | 01-MAR-10:09 | 22950.34 | 01-MAR-08:09 | 13457.54 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 17832.21 | 03-APR-09:09 | 22950.34 | 03-APR-07:10 | 13457.54 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 17832.21 | 01-MAY-09:09 | 22950.34 | 01-MAY-07:10 | 13457.54 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 17832.21 | 01-JUN-09:09 | 22950.34 | 01-JUN-07:10 | 13457.54 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 17832.21 | 03-JUL-09:09 | 22950.34 | 03-JUL-07:10 | 13457.54 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 17832.21 | 01-AUG-09:09 | 22950.34 | 01-AUG-07:10 | 13457.54 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 17832.21 | 01-SEP-09:09 | 22950.34 | 01-SEP-07:10 | 13457.54 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 17832.21 | 02-OCT-09:09 | 22950.34 | 02-OCT-07:10 | 13457.54 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 17832.21 | 01-NOV-09:09 | 22950.34 | 01-NOV-07:10 | 13457.54 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 17832.21 | 01-DEC-10:09 | 22950.34 | 01-DEC-08:09 | 13457.54 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 17832.21 | 22950.34 | 13457.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 17832.21 | 22950.34 | 13457.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 16014.58 | 02-JAN-10:09 | 20611.01 | 02-JAN-08:09 | 17206.63 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 16014.58 | 01-FEB-10:09 | 20611.01 | 01-FEB-08:09 | 17206.63 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 16014.58 | 01-MAR-10:09 | 20611.01 | 01-MAR-08:09 | 17206.63 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 16014.58 | 03-APR-09:09 | 20611.01 | 03-APR-07:10 | 17206.63 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 16014.58 | 01-MAY-09:09 | 20611.01 | 01-MAY-07:10 | 17206.63 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 16014.58 | 01-JUN-09:09 | 20611.01 | 01-JUN-07:10 | 17206.63 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 16014.58 | 03-JUL-09:09 | 20611.01 | 03-JUL-07:10 | 17206.63 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 16014.58 | 01-AUG-09:09 | 20611.01 | 01-AUG-07:10 | 17206.63 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 16014.58 | 01-SEP-09:09 | 20611.01 | 01-SEP-07:10 | 17206.63 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 16014.58 | 02-OCT-09:09 | 20611.01 | 02-OCT-07:10 | 17206.63 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 16014.58 | 01-NOV-09:09 | 20611.01 | 01-NOV-07:10 | 17206.63 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 16014.58 | 01-DEC-10:09 | 20611.01 | 01-DEC-08:09 | 17206.63 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 16014.58 | 20611.01 | 17206.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 16014.58 | 20611.01 | 17206.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 16014.58 | 02-JAN-10:09 | 20611.01 | 02-JAN-08:09 | 17206.56 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 16014.58 | 01-FEB-10:09 | 20611.01 | 01-FEB-08:09 | 17206.56 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 16014.58 | 01-MAR-10:09 | 20611.01 | 01-MAR-08:09 | 17206.56 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 16014.58 | 03-APR-09:09 | 20611.01 | 03-APR-07:10 | 17206.56 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 16014.58 | 01-MAY-09:09 | 20611.01 | 01-MAY-07:10 | 17206.56 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 16014.58 | 01-JUN-09:09 | 20611.01 | 01-JUN-07:10 | 17206.56 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 16014.58 | 03-JUL-09:09 | 20611.01 | 03-JUL-07:10 | 17206.56 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 16014.58 | 01-AUG-09:09 | 20611.01 | 01-AUG-07:10 | 17206.56 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 16014.58 | 01-SEP-09:09 | 20611.01 | 01-SEP-07:10 | 17206.56 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 16014.58 | 02-OCT-09:09 | 20611.01 | 02-OCT-07:10 | 17206.56 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 16014.58 | 01-NOV-09:09 | 20611.01 | 01-NOV-07:10 | 17206.56 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 16014.58 | 01-DEC-10:09 | 20611.01 | 01-DEC-08:09 | 17206.56 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 16014.58 | 20611.01 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 16014.58 | 20611.01 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 16014.58 | 02-JAN-10:09 | 20611.01 | 02-JAN-08:09 | 17206.56 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 16014.58 | 01-FEB-10:09 | 20611.01 | 01-FEB-08:09 | 17206.56 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 16014.58 | 01-MAR-10:09 | 20611.01 | 01-MAR-08:09 | 17206.56 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 16014.58 | 03-APR-09:09 | 20611.01 | 03-APR-07:10 | 17206.56 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 16014.58 | 01-MAY-09:09 | 20611.01 | 01-MAY-07:10 | 17206.56 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 16014.58 | 01-JUN-09:09 | 20611.01 | 01-JUN-07:10 | 17206.56 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 16014.58 | 03-JUL-09:09 | 20611.01 | 03-JUL-07:10 | 17206.56 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 16014.58 | 01-AUG-09:09 | 20611.01 | 01-AUG-07:10 | 17206.56 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 16014.58 | 01-SEP-09:09 | 20611.01 | 01-SEP-07:10 | 17206.56 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 16014.58 | 02-OCT-09:09 | 20611.01 | 02-OCT-07:10 | 17206.56 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 16014.58 | 01-NOV-09:09 | 20611.01 | 01-NOV-07:10 | 17206.56 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 16014.58 | 01-DEC-10:09 | 20611.01 | 01-DEC-08:09 | 17206.56 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 16014.58 | 20611.01 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 16014.58 | 20611.01 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.79 | 02-JAN-10:09 | 2587.92 | 02-JAN-08:09 | 2160.55 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 2912.13 | 04-JAN-05:51 |
February | 2010.79 | 01-FEB-10:09 | 2255.20 | 01-FEB-08:09 | 2160.55 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 3542.21 | 12-FEB-22:51 |
March | 2010.79 | 01-MAR-10:09 | 2255.20 | 03-MAR-16:49 | 2160.55 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1786.12 | 15-MAR-04:57 |
April | 2010.79 | 03-APR-09:09 | 1470.28 | 03-APR-07:10 | 2160.55 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 90.60 | 23-APR-16:00 | 1541.40 | 01-APR-19:00 |
May | 2010.79 | 01-MAY-09:09 | 1231.33 | 01-MAY-07:10 | 2160.55 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 36.46 | 24-MAY-15:00 | 766.91 | 08-MAY-24:00 |
June | 2010.79 | 01-JUN-09:09 | 1470.28 | 30-JUN-07:10 | 2160.55 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 125.97 | 29-JUN-21:02 | 533.91 | 20-JUN-04:00 |
July | 2010.79 | 03-JUL-09:09 | 1231.33 | 03-JUL-07:10 | 2160.55 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 203.91 | 23-JUL-14:55 | 514.46 | 09-JUL-10:00 |
August | 2010.79 | 01-AUG-09:09 | 1803.00 | 31-AUG-07:10 | 2160.55 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 80.02 | 08-AUG-16:00 | 693.79 | 27-AUG-06:00 |
September | 2010.79 | 01-SEP-09:09 | 1803.00 | 19-SEP-07:10 | 2160.55 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12.80 | 01-SEP-15:00 | 912.19 | 20-SEP-01:00 |
October | 2010.79 | 02-OCT-09:09 | 2587.92 | 26-OCT-07:10 | 2160.55 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 1171.58 | 31-OCT-21:10 |
November | 2010.79 | 01-NOV-09:09 | 2587.92 | 01-NOV-07:10 | 2160.55 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 2166.83 | 22-NOV-02:00 |
December | 2010.79 | 01-DEC-10:09 | 2587.92 | 01-DEC-08:09 | 2160.55 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 2896.49 | 16-DEC-05:59 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.79 | 1231.33 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 514.46 | |||||
Maximum of Months | 2010.79 | 2587.92 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 203.91 | 3542.21 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 1667.75 | 02-JAN-08:09 | 1392.34 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 1941.72 | 04-JAN-05:51 |
February | 1295.83 | 01-FEB-10:09 | 1667.75 | 02-FEB-16:00 | 1392.34 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 2337.19 | 12-FEB-22:51 |
March | 1295.83 | 01-MAR-10:09 | 1453.34 | 03-MAR-16:49 | 1392.34 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1190.75 | 15-MAR-04:52 |
April | 1295.83 | 03-APR-09:09 | 870.51 | 03-APR-07:10 | 1392.34 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 114.69 | 23-APR-16:20 | 995.57 | 01-APR-19:00 |
May | 1295.83 | 01-MAY-09:09 | 793.52 | 01-MAY-07:10 | 1392.34 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 24.31 | 24-MAY-15:00 | 562.94 | 14-MAY-08:00 |
June | 1295.83 | 01-JUN-09:09 | 870.51 | 09-JUN-07:10 | 1392.34 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 102.64 | 24-JUN-17:10 | 342.91 | 20-JUN-04:00 |
July | 1295.83 | 03-JUL-09:09 | 793.52 | 03-JUL-07:10 | 1392.34 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 152.54 | 23-JUL-15:00 | 333.80 | 09-JUL-10:00 |
August | 1295.83 | 01-AUG-09:09 | 1161.92 | 31-AUG-07:10 | 1392.34 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 53.35 | 08-AUG-16:00 | 443.86 | 27-AUG-06:00 |
September | 1295.83 | 01-SEP-09:09 | 1161.92 | 19-SEP-07:10 | 1392.34 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8.54 | 01-SEP-15:00 | 595.01 | 20-SEP-01:00 |
October | 1295.83 | 02-OCT-09:09 | 1667.75 | 26-OCT-07:10 | 1392.34 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 765.81 | 31-OCT-21:10 |
November | 1295.83 | 01-NOV-09:09 | 1667.75 | 01-NOV-07:10 | 1392.34 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1397.37 | 22-NOV-02:00 |
December | 1295.83 | 01-DEC-10:09 | 1667.75 | 01-DEC-16:19 | 1392.34 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1930.99 | 16-DEC-05:57 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 793.52 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 333.80 | |||||
Maximum of Months | 1295.83 | 1667.75 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 152.54 | 2337.19 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.83 | 02-JAN-10:09 | 2587.98 | 02-JAN-08:09 | 2160.58 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 2912.38 | 04-JAN-05:51 |
February | 2010.83 | 01-FEB-10:09 | 2255.25 | 02-FEB-16:49 | 2160.58 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 3434.28 | 12-FEB-22:51 |
March | 2010.83 | 01-MAR-10:09 | 2255.25 | 03-MAR-16:00 | 2160.58 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1786.13 | 15-MAR-04:55 |
April | 2010.83 | 03-APR-09:09 | 1470.31 | 03-APR-07:10 | 2160.58 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 33.17 | 23-APR-16:14 | 1677.39 | 16-APR-12:20 |
May | 2010.83 | 01-MAY-09:09 | 1231.36 | 01-MAY-07:10 | 2160.58 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 36.46 | 24-MAY-15:00 | 752.51 | 08-MAY-24:00 |
June | 2010.83 | 01-JUN-09:09 | 1470.31 | 30-JUN-07:10 | 2160.58 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 126.82 | 24-JUN-17:10 | 522.45 | 20-JUN-04:00 |
July | 2010.83 | 03-JUL-09:09 | 1231.36 | 03-JUL-07:10 | 2160.58 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 205.25 | 23-JUL-14:55 | 481.73 | 09-JUL-10:00 |
August | 2010.83 | 01-AUG-09:09 | 1803.04 | 31-AUG-07:10 | 2160.58 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 80.02 | 08-AUG-16:00 | 696.81 | 27-AUG-06:00 |
September | 2010.83 | 01-SEP-09:09 | 1803.04 | 19-SEP-07:10 | 2160.58 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12.71 | 01-SEP-15:00 | 894.07 | 20-SEP-01:00 |
October | 2010.83 | 02-OCT-09:09 | 2587.98 | 26-OCT-07:10 | 2160.58 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 1148.46 | 31-OCT-21:10 |
November | 2010.83 | 01-NOV-09:09 | 2587.98 | 01-NOV-07:10 | 2160.58 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 2075.72 | 22-NOV-02:00 |
December | 2010.83 | 01-DEC-10:09 | 2587.98 | 01-DEC-16:19 | 2160.58 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 2896.48 | 16-DEC-05:52 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.83 | 1231.36 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 481.73 | |||||
Maximum of Months | 2010.83 | 2587.98 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 205.25 | 3434.28 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 1667.75 | 02-JAN-08:09 | 1392.33 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 1944.53 | 04-JAN-05:51 |
February | 1295.83 | 01-FEB-10:09 | 1453.34 | 01-FEB-08:09 | 1392.33 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 2464.36 | 12-FEB-22:51 |
March | 1295.83 | 01-MAR-10:09 | 1453.34 | 13-MAR-07:10 | 1392.33 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1209.13 | 17-MAR-04:00 |
April | 1295.83 | 03-APR-09:09 | 947.51 | 03-APR-07:10 | 1392.33 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.04 | 23-APR-15:54 | 1130.64 | 09-APR-13:00 |
May | 1295.83 | 01-MAY-09:09 | 870.51 | 12-MAY-07:10 | 1392.33 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 24.31 | 24-MAY-15:00 | 531.04 | 08-MAY-24:00 |
June | 1295.83 | 01-JUN-09:09 | 947.51 | 09-JUN-07:10 | 1392.33 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 80.74 | 29-JUN-16:00 | 399.84 | 10-JUN-22:00 |
July | 1295.83 | 03-JUL-09:09 | 870.51 | 03-JUL-07:10 | 1392.33 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 132.23 | 23-JUL-14:53 | 408.48 | 16-JUL-17:00 |
August | 1295.83 | 01-AUG-09:09 | 1161.92 | 28-AUG-07:10 | 1392.33 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 53.35 | 08-AUG-16:00 | 550.68 | 27-AUG-06:00 |
September | 1295.83 | 01-SEP-09:09 | 1161.92 | 12-SEP-07:10 | 1392.33 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8.54 | 01-SEP-15:00 | 635.29 | 20-SEP-01:00 |
October | 1295.83 | 02-OCT-09:09 | 1667.75 | 26-OCT-07:10 | 1392.33 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 805.71 | 31-OCT-21:10 |
November | 1295.83 | 01-NOV-09:09 | 1667.75 | 01-NOV-07:10 | 1392.33 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1536.09 | 22-NOV-02:00 |
December | 1295.83 | 01-DEC-10:09 | 1667.75 | 01-DEC-08:09 | 1392.33 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1930.99 | 16-DEC-05:57 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 870.51 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 399.84 | |||||
Maximum of Months | 1295.83 | 1667.75 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 132.23 | 2464.36 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.79 | 02-JAN-10:09 | 2587.92 | 02-JAN-08:09 | 2160.55 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 6374.41 | 04-JAN-05:51 |
February | 2010.79 | 01-FEB-10:09 | 2255.20 | 01-FEB-08:09 | 2160.55 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 7840.61 | 12-FEB-22:59 |
March | 2010.79 | 01-MAR-10:09 | 2255.20 | 03-MAR-16:49 | 2160.55 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 4068.05 | 15-MAR-05:00 |
April | 2010.79 | 03-APR-09:09 | 1470.28 | 03-APR-07:10 | 2160.55 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 407.63 | 23-APR-16:00 | 3112.35 | 01-APR-19:00 |
May | 2010.79 | 01-MAY-09:09 | 1231.33 | 01-MAY-07:10 | 2160.55 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 83.06 | 24-MAY-15:00 | 1674.78 | 29-MAY-18:00 |
June | 2010.79 | 01-JUN-09:09 | 1350.81 | 09-JUN-07:10 | 2160.55 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 287.23 | 29-JUN-21:02 | 1122.14 | 20-JUN-04:00 |
July | 2010.79 | 03-JUL-09:09 | 1231.33 | 03-JUL-07:10 | 2160.55 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 416.62 | 23-JUL-14:44 | 1123.50 | 06-JUL-21:53 |
August | 2010.79 | 01-AUG-09:09 | 1803.00 | 31-AUG-07:10 | 2160.55 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 184.57 | 08-AUG-16:00 | 1461.69 | 27-AUG-06:00 |
September | 2010.79 | 01-SEP-09:09 | 1803.00 | 19-SEP-07:10 | 2160.55 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 28.47 | 01-SEP-15:00 | 1918.86 | 20-SEP-01:00 |
October | 2010.79 | 02-OCT-09:09 | 2587.92 | 26-OCT-07:10 | 2160.55 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 2673.39 | 31-OCT-21:02 |
November | 2010.79 | 01-NOV-09:09 | 2587.92 | 01-NOV-07:10 | 2160.55 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 4219.23 | 22-NOV-02:00 |
December | 2010.79 | 01-DEC-10:09 | 2587.92 | 01-DEC-08:09 | 2160.55 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 6431.25 | 16-DEC-05:51 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.79 | 1231.33 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1122.14 | |||||
Maximum of Months | 2010.79 | 2587.92 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 416.62 | 7840.61 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1239.33 | 02-JAN-08:09 | 1667.75 | 02-JAN-08:09 | 1392.34 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 4536.04 | 04-JAN-05:51 |
February | 1239.33 | 01-FEB-08:09 | 1667.75 | 02-FEB-16:00 | 1392.34 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 5227.03 | 12-FEB-23:00 |
March | 1239.33 | 01-MAR-08:09 | 1453.34 | 03-MAR-16:49 | 1392.34 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 2800.02 | 15-MAR-05:00 |
April | 1239.33 | 03-APR-07:10 | 870.51 | 03-APR-07:10 | 1392.34 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 333.79 | 23-APR-16:00 | 2354.41 | 16-APR-11:53 |
May | 1239.33 | 01-MAY-07:10 | 793.52 | 01-MAY-07:10 | 1392.34 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 55.37 | 24-MAY-15:00 | 1292.28 | 14-MAY-08:30 |
June | 1239.33 | 01-JUN-07:10 | 870.51 | 09-JUN-07:10 | 1392.34 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 241.06 | 24-JUN-17:01 | 805.47 | 18-JUN-07:10 |
July | 1239.33 | 03-JUL-07:10 | 793.52 | 03-JUL-07:10 | 1392.34 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 325.95 | 23-JUL-14:43 | 727.77 | 06-JUL-22:00 |
August | 1239.33 | 01-AUG-07:10 | 1161.92 | 31-AUG-07:10 | 1392.34 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 123.05 | 08-AUG-16:00 | 992.13 | 27-AUG-06:00 |
September | 1239.33 | 01-SEP-07:10 | 1161.92 | 19-SEP-07:10 | 1392.34 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 18.98 | 01-SEP-15:00 | 1246.58 | 20-SEP-01:00 |
October | 1239.33 | 02-OCT-07:10 | 1667.75 | 30-OCT-07:10 | 1392.34 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 1781.70 | 31-OCT-21:02 |
November | 1239.33 | 01-NOV-07:10 | 1667.75 | 01-NOV-07:10 | 1392.34 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 2784.34 | 21-NOV-22:02 |
December | 1239.33 | 01-DEC-08:09 | 1667.75 | 01-DEC-16:19 | 1392.34 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 4474.67 | 16-DEC-05:51 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1239.33 | 793.52 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 727.77 | |||||
Maximum of Months | 1239.33 | 1667.75 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 333.79 | 5227.03 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.83 | 02-JAN-10:09 | 2587.98 | 02-JAN-08:09 | 2160.58 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 6807.07 | 04-JAN-05:51 |
February | 2010.83 | 01-FEB-10:09 | 2255.25 | 02-FEB-16:49 | 2160.58 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 7840.57 | 12-FEB-23:00 |
March | 2010.83 | 01-MAR-10:09 | 2255.25 | 03-MAR-16:00 | 2160.58 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 4199.94 | 15-MAR-04:57 |
April | 2010.83 | 03-APR-09:09 | 1350.84 | 03-APR-07:10 | 2160.58 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 54.37 | 23-APR-15:54 | 3907.12 | 16-APR-12:00 |
May | 2010.83 | 01-MAY-09:09 | 1231.36 | 01-MAY-07:10 | 2160.58 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 83.06 | 24-MAY-15:00 | 1711.23 | 29-MAY-18:00 |
June | 2010.83 | 01-JUN-09:09 | 1350.84 | 09-JUN-07:10 | 2160.58 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 295.80 | 24-JUN-17:01 | 1114.66 | 20-JUN-04:00 |
July | 2010.83 | 03-JUL-09:09 | 1231.36 | 03-JUL-07:10 | 2160.58 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 418.56 | 23-JUL-14:43 | 1136.91 | 06-JUL-21:53 |
August | 2010.83 | 01-AUG-09:09 | 1803.04 | 31-AUG-07:10 | 2160.58 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 184.57 | 08-AUG-16:00 | 1524.24 | 27-AUG-06:00 |
September | 2010.83 | 01-SEP-09:09 | 1803.04 | 19-SEP-07:10 | 2160.58 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 28.25 | 01-SEP-15:00 | 1915.20 | 20-SEP-01:00 |
October | 2010.83 | 02-OCT-09:09 | 2587.98 | 26-OCT-07:10 | 2160.58 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 2675.55 | 31-OCT-21:02 |
November | 2010.83 | 01-NOV-09:09 | 2587.98 | 01-NOV-07:10 | 2160.58 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 4210.70 | 22-NOV-02:00 |
December | 2010.83 | 01-DEC-10:09 | 2587.98 | 01-DEC-16:19 | 2160.58 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 6719.08 | 16-DEC-05:51 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.83 | 1231.36 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1114.66 | |||||
Maximum of Months | 2010.83 | 2587.98 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 418.56 | 7840.57 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 1667.75 | 02-JAN-08:09 | 1392.33 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 4537.79 | 04-JAN-05:51 |
February | 1295.83 | 01-FEB-10:09 | 1453.34 | 01-FEB-08:09 | 1392.33 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 5227.04 | 12-FEB-22:52 |
March | 1295.83 | 01-MAR-10:09 | 1453.34 | 13-MAR-07:10 | 1392.33 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 2799.92 | 15-MAR-04:57 |
April | 1295.83 | 03-APR-09:09 | 947.51 | 03-APR-07:10 | 1392.33 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 2137.38 | 01-APR-19:00 |
May | 1295.83 | 01-MAY-09:09 | 870.51 | 12-MAY-07:10 | 1392.33 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 55.37 | 24-MAY-15:00 | 1159.56 | 29-MAY-18:00 |
June | 1295.83 | 01-JUN-09:09 | 947.51 | 30-JUN-07:10 | 1392.33 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 187.47 | 29-JUN-16:00 | 762.89 | 20-JUN-04:00 |
July | 1295.83 | 03-JUL-09:09 | 870.51 | 03-JUL-07:10 | 1392.33 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 277.33 | 23-JUL-14:43 | 929.83 | 16-JUL-17:10 |
August | 1295.83 | 01-AUG-09:09 | 1161.92 | 28-AUG-07:10 | 1392.33 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 123.04 | 08-AUG-16:00 | 1062.00 | 27-AUG-06:00 |
September | 1295.83 | 01-SEP-09:09 | 1161.92 | 12-SEP-07:10 | 1392.33 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 18.98 | 01-SEP-15:00 | 1264.66 | 20-SEP-01:00 |
October | 1295.83 | 02-OCT-09:09 | 1667.75 | 26-OCT-07:10 | 1392.33 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 1783.39 | 31-OCT-21:02 |
November | 1295.83 | 01-NOV-09:09 | 1667.75 | 01-NOV-07:10 | 1392.33 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 2825.22 | 22-NOV-02:00 |
December | 1295.83 | 01-DEC-10:09 | 1667.75 | 01-DEC-08:09 | 1392.33 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 4480.60 | 16-DEC-05:51 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 870.51 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 762.89 | |||||
Maximum of Months | 1295.83 | 1667.75 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 277.33 | 5227.04 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.79 | 02-JAN-10:09 | 2587.92 | 02-JAN-08:09 | 2160.55 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 7828.64 | 04-JAN-06:00 |
February | 2010.79 | 01-FEB-10:09 | 2255.20 | 01-FEB-08:09 | 2160.55 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 9538.90 | 12-FEB-23:00 |
March | 2010.79 | 01-MAR-10:09 | 2255.20 | 03-MAR-16:49 | 2160.55 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 4987.92 | 15-MAR-05:00 |
April | 2010.79 | 03-APR-09:09 | 1470.28 | 03-APR-07:10 | 2160.55 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 588.37 | 23-APR-15:51 | 3592.24 | 01-APR-18:00 |
May | 2010.79 | 01-MAY-09:09 | 1231.33 | 01-MAY-07:10 | 2160.55 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 100.08 | 24-MAY-15:00 | 2033.11 | 29-MAY-18:00 |
June | 2010.79 | 01-JUN-09:09 | 1350.81 | 09-JUN-07:10 | 2160.55 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 345.65 | 29-JUN-16:00 | 1324.95 | 20-JUN-04:00 |
July | 2010.79 | 03-JUL-09:09 | 1231.33 | 03-JUL-07:10 | 2160.55 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 498.01 | 23-JUL-14:44 | 1373.12 | 06-JUL-21:53 |
August | 2010.79 | 01-AUG-09:09 | 1803.00 | 31-AUG-07:10 | 2160.55 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 225.31 | 08-AUG-16:00 | 1730.96 | 27-AUG-06:00 |
September | 2010.79 | 01-SEP-09:09 | 1803.00 | 19-SEP-07:10 | 2160.55 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 33.42 | 01-SEP-15:00 | 2214.39 | 20-SEP-01:00 |
October | 2010.79 | 02-OCT-09:09 | 2587.92 | 26-OCT-07:10 | 2160.55 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 3316.40 | 31-OCT-21:02 |
November | 2010.79 | 01-NOV-09:09 | 2587.92 | 01-NOV-07:10 | 2160.55 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 5188.80 | 21-NOV-22:02 |
December | 2010.79 | 01-DEC-10:09 | 2587.92 | 01-DEC-08:09 | 2160.55 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 7897.72 | 16-DEC-06:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.79 | 1231.33 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1324.95 | |||||
Maximum of Months | 2010.79 | 2587.92 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 588.37 | 9538.90 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 1667.75 | 02-JAN-08:09 | 1392.34 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 5718.29 | 04-JAN-06:00 |
February | 1295.83 | 01-FEB-10:09 | 1667.75 | 02-FEB-16:00 | 1392.34 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 6511.68 | 12-FEB-23:00 |
March | 1295.83 | 01-MAR-10:09 | 1453.34 | 03-MAR-16:49 | 1392.34 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 3485.69 | 15-MAR-04:57 |
April | 1295.83 | 03-APR-09:09 | 870.51 | 03-APR-07:10 | 1392.34 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 415.35 | 23-APR-16:10 | 2543.37 | 16-APR-11:53 |
May | 1295.83 | 01-MAY-09:09 | 793.52 | 01-MAY-07:10 | 1392.34 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 66.72 | 24-MAY-15:00 | 1518.56 | 14-MAY-08:20 |
June | 1295.83 | 01-JUN-09:09 | 870.51 | 09-JUN-07:10 | 1392.34 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 282.00 | 24-JUN-17:10 | 979.13 | 18-JUN-07:20 |
July | 1295.83 | 03-JUL-09:09 | 793.52 | 03-JUL-07:10 | 1392.34 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 400.57 | 23-JUL-14:43 | 893.03 | 06-JUL-21:53 |
August | 1295.83 | 01-AUG-09:09 | 1161.92 | 31-AUG-07:10 | 1392.34 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 150.21 | 08-AUG-16:00 | 1178.94 | 27-AUG-06:00 |
September | 1295.83 | 01-SEP-09:09 | 1161.92 | 19-SEP-07:10 | 1392.34 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 22.28 | 01-SEP-15:00 | 1445.99 | 20-SEP-04:15 |
October | 1295.83 | 02-OCT-09:09 | 1667.75 | 30-OCT-07:10 | 1392.34 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 2210.43 | 31-OCT-21:02 |
November | 1295.83 | 01-NOV-09:09 | 1667.75 | 01-NOV-07:10 | 1392.34 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 3456.45 | 21-NOV-22:02 |
December | 1295.83 | 01-DEC-10:09 | 1667.75 | 01-DEC-16:19 | 1392.34 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 5657.76 | 16-DEC-05:52 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 793.52 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 893.03 | |||||
Maximum of Months | 1295.83 | 1667.75 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 415.35 | 6511.68 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.83 | 02-JAN-10:09 | 2587.98 | 02-JAN-08:09 | 2160.58 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 8413.81 | 04-JAN-06:00 |
February | 2010.83 | 01-FEB-10:09 | 2255.25 | 02-FEB-16:49 | 2160.58 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 9767.45 | 12-FEB-22:59 |
March | 2010.83 | 01-MAR-10:09 | 2255.25 | 03-MAR-16:00 | 2160.58 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 5228.47 | 15-MAR-04:58 |
April | 2010.83 | 03-APR-09:09 | 1350.84 | 03-APR-07:10 | 2160.58 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 41.14 | 23-APR-16:04 | 4231.04 | 16-APR-12:00 |
May | 2010.83 | 01-MAY-09:09 | 1231.36 | 01-MAY-07:10 | 2160.58 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 100.08 | 24-MAY-15:00 | 2079.69 | 29-MAY-18:00 |
June | 2010.83 | 01-JUN-09:09 | 1350.84 | 09-JUN-07:10 | 2160.58 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 348.70 | 24-JUN-17:10 | 1314.39 | 20-JUN-04:00 |
July | 2010.83 | 03-JUL-09:09 | 1231.36 | 03-JUL-07:10 | 2160.58 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 514.41 | 23-JUL-14:43 | 1389.48 | 06-JUL-21:53 |
August | 2010.83 | 01-AUG-09:09 | 1803.04 | 31-AUG-07:10 | 2160.58 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 225.30 | 08-AUG-16:00 | 1812.68 | 27-AUG-06:00 |
September | 2010.83 | 01-SEP-09:09 | 1803.04 | 19-SEP-07:10 | 2160.58 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 33.15 | 01-SEP-15:00 | 2212.30 | 20-SEP-01:00 |
October | 2010.83 | 02-OCT-09:09 | 2587.98 | 26-OCT-07:10 | 2160.58 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 3319.85 | 31-OCT-21:02 |
November | 2010.83 | 01-NOV-09:09 | 2587.98 | 01-NOV-07:10 | 2160.58 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 5188.75 | 21-NOV-22:02 |
December | 2010.83 | 01-DEC-10:09 | 2587.98 | 01-DEC-16:19 | 2160.58 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 8486.74 | 16-DEC-05:56 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.83 | 1231.36 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1314.39 | |||||
Maximum of Months | 2010.83 | 2587.98 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 514.41 | 9767.45 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 1667.75 | 02-JAN-08:09 | 1392.33 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 5718.29 | 04-JAN-05:58 |
February | 1295.83 | 01-FEB-10:09 | 1453.34 | 01-FEB-08:09 | 1392.33 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 6511.73 | 12-FEB-22:59 |
March | 1295.83 | 01-MAR-10:09 | 1453.34 | 13-MAR-07:10 | 1392.33 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 3485.66 | 15-MAR-04:57 |
April | 1295.83 | 03-APR-09:09 | 947.51 | 03-APR-07:10 | 1392.33 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 2495.88 | 01-APR-18:00 |
May | 1295.83 | 01-MAY-09:09 | 870.51 | 12-MAY-07:10 | 1392.33 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 66.72 | 24-MAY-15:00 | 1408.79 | 29-MAY-18:00 |
June | 1295.83 | 01-JUN-09:09 | 947.51 | 30-JUN-07:10 | 1392.33 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 230.44 | 29-JUN-16:00 | 902.62 | 20-JUN-04:00 |
July | 1295.83 | 03-JUL-09:09 | 870.51 | 03-JUL-07:10 | 1392.33 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 334.88 | 23-JUL-14:43 | 1180.49 | 16-JUL-17:10 |
August | 1295.83 | 01-AUG-09:09 | 1161.92 | 28-AUG-07:10 | 1392.33 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 150.20 | 08-AUG-16:00 | 1264.71 | 27-AUG-06:00 |
September | 1295.83 | 01-SEP-09:09 | 1161.92 | 12-SEP-07:10 | 1392.33 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 22.28 | 01-SEP-15:00 | 1468.82 | 20-SEP-01:00 |
October | 1295.83 | 02-OCT-09:09 | 1667.75 | 26-OCT-07:10 | 1392.33 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 2214.01 | 31-OCT-21:02 |
November | 1295.83 | 01-NOV-09:09 | 1667.75 | 01-NOV-07:10 | 1392.33 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 3461.97 | 21-NOV-22:02 |
December | 1295.83 | 01-DEC-10:09 | 1667.75 | 01-DEC-08:09 | 1392.33 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 5657.62 | 16-DEC-05:52 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 870.51 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 902.62 | |||||
Maximum of Months | 1295.83 | 1667.75 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 334.88 | 6511.73 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 232.27 | 02-JAN-10:09 | 578.72 | 02-JAN-08:09 | 1948.61 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 232.27 | 01-FEB-10:09 | 578.72 | 01-FEB-08:09 | 3897.21 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 232.27 | 01-MAR-10:09 | 578.72 | 01-MAR-08:09 | 7794.42 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 232.27 | 03-APR-09:09 | 578.72 | 03-APR-07:10 | 7794.42 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 232.27 | 01-MAY-09:09 | 578.72 | 01-MAY-07:10 | 3897.21 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 232.27 | 01-JUN-09:09 | 578.72 | 01-JUN-07:10 | 5845.82 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 232.27 | 03-JUL-09:09 | 578.72 | 03-JUL-07:10 | 7794.42 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 232.27 | 01-AUG-09:09 | 578.72 | 01-AUG-07:10 | 7794.42 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 232.27 | 01-SEP-09:09 | 578.72 | 01-SEP-07:10 | 3897.21 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 232.27 | 02-OCT-09:09 | 578.72 | 02-OCT-07:10 | 5845.82 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 232.27 | 01-NOV-09:09 | 578.72 | 01-NOV-07:10 | 5845.82 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 232.27 | 01-DEC-10:09 | 578.72 | 01-DEC-08:09 | 7794.42 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 232.27 | 578.72 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 232.27 | 578.72 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 232.27 | 02-JAN-10:09 | 578.72 | 02-JAN-08:09 | 1948.61 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 232.27 | 01-FEB-10:09 | 578.72 | 01-FEB-08:09 | 3897.21 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 232.27 | 01-MAR-10:09 | 578.72 | 01-MAR-08:09 | 7794.42 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 232.27 | 03-APR-09:09 | 578.72 | 03-APR-07:10 | 7794.42 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 232.27 | 01-MAY-09:09 | 578.72 | 01-MAY-07:10 | 3897.21 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 232.27 | 01-JUN-09:09 | 578.72 | 01-JUN-07:10 | 5845.82 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 232.27 | 03-JUL-09:09 | 578.72 | 03-JUL-07:10 | 7794.42 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 232.27 | 01-AUG-09:09 | 578.72 | 01-AUG-07:10 | 7794.42 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 232.27 | 01-SEP-09:09 | 578.72 | 01-SEP-07:10 | 3897.21 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 232.27 | 02-OCT-09:09 | 578.72 | 02-OCT-07:10 | 5845.82 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 232.27 | 01-NOV-09:09 | 578.72 | 01-NOV-07:10 | 5845.82 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 232.27 | 01-DEC-10:09 | 578.72 | 01-DEC-08:09 | 7794.42 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 232.27 | 578.72 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 232.27 | 578.72 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 232.27 | 02-JAN-10:09 | 578.72 | 02-JAN-08:09 | 1948.61 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 232.27 | 01-FEB-10:09 | 578.72 | 01-FEB-08:09 | 3897.21 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 232.27 | 01-MAR-10:09 | 578.72 | 01-MAR-08:09 | 7794.42 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 232.27 | 03-APR-09:09 | 578.72 | 03-APR-07:10 | 7794.42 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 232.27 | 01-MAY-09:09 | 578.72 | 01-MAY-07:10 | 3897.21 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 232.27 | 01-JUN-09:09 | 578.72 | 01-JUN-07:10 | 5845.82 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 232.27 | 03-JUL-09:09 | 578.72 | 03-JUL-07:10 | 7794.42 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 232.27 | 01-AUG-09:09 | 578.72 | 01-AUG-07:10 | 7794.42 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 232.27 | 01-SEP-09:09 | 578.72 | 01-SEP-07:10 | 3897.21 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 232.27 | 02-OCT-09:09 | 578.72 | 02-OCT-07:10 | 5845.82 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 232.27 | 01-NOV-09:09 | 578.72 | 01-NOV-07:10 | 5845.82 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 232.27 | 01-DEC-10:09 | 578.72 | 01-DEC-08:09 | 7794.42 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 232.27 | 578.72 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 232.27 | 578.72 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 5027.92 | 02-JAN-10:09 | 6471.01 | 02-JAN-08:09 | 94908.13 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 5027.92 | 01-FEB-10:09 | 6471.01 | 01-FEB-08:09 | 189816.26 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 5027.92 | 01-MAR-10:09 | 6471.01 | 01-MAR-08:09 | 379632.52 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 5027.92 | 03-APR-09:09 | 6471.01 | 03-APR-07:10 | 379632.52 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 5027.92 | 01-MAY-09:09 | 6471.01 | 01-MAY-07:10 | 189816.26 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5027.92 | 01-JUN-09:09 | 6471.01 | 01-JUN-07:10 | 284724.39 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 5027.92 | 03-JUL-09:09 | 6471.01 | 03-JUL-07:10 | 379632.52 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 5027.92 | 01-AUG-09:09 | 6471.01 | 01-AUG-07:10 | 379632.52 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 5027.92 | 01-SEP-09:09 | 6471.01 | 01-SEP-07:10 | 189816.26 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 5027.92 | 02-OCT-09:09 | 6471.01 | 02-OCT-07:10 | 284724.39 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5027.92 | 01-NOV-09:09 | 6471.01 | 01-NOV-07:10 | 284724.39 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 5027.92 | 01-DEC-10:09 | 6471.01 | 01-DEC-08:09 | 379632.52 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 5027.92 | 6471.01 | 94908.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 5027.92 | 6471.01 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 5842.95 | 04-JAN-05:51 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 7828.30 | 12-FEB-22:51 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 3758.83 | 15-MAR-04:52 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 157.22 | 23-APR-16:00 | 3331.28 | 01-APR-19:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59.76 | 24-MAY-15:00 | 1644.91 | 08-MAY-24:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 267.71 | 24-JUN-17:01 | 1116.85 | 20-JUN-04:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 422.78 | 23-JUL-15:00 | 1031.01 | 06-JUL-21:53 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 141.13 | 08-AUG-16:00 | 1466.15 | 27-AUG-06:00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.56 | 01-SEP-15:00 | 1965.00 | 20-SEP-01:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 2517.93 | 31-OCT-21:10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 4734.24 | 22-NOV-02:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 6063.71 | 16-DEC-05:51 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1031.01 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 422.78 | 7828.30 |
Report: PeakSpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 10118.59 | 04-JAN-05:51 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 12886.01 | 12-FEB-23:00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 6437.75 | 15-MAR-05:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 475.80 | 23-APR-15:51 | 5638.13 | 01-APR-19:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 107.58 | 24-MAY-15:00 | 2867.49 | 08-MAY-24:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 506.65 | 24-JUN-17:01 | 1925.13 | 20-JUN-04:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 794.71 | 23-JUL-15:00 | 1827.75 | 06-JUL-22:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 255.75 | 08-AUG-16:00 | 2566.46 | 27-AUG-06:00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.25 | 01-SEP-15:00 | 3406.81 | 20-SEP-01:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 4327.07 | 31-OCT-21:02 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 7836.55 | 22-NOV-02:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 10251.46 | 16-DEC-05:51 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1827.75 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 794.71 | 12886.01 |
Report: PeakSpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 11545.77 | 04-JAN-06:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 13463.03 | 12-FEB-23:00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 7147.67 | 15-MAR-05:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 296.55 | 23-APR-15:51 | 5785.27 | 01-APR-18:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 91.83 | 24-MAY-15:00 | 3190.49 | 29-MAY-18:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 444.49 | 29-JUN-16:00 | 2071.69 | 20-JUN-04:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 594.82 | 15-JUL-17:03 | 1998.90 | 06-JUL-21:53 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 266.36 | 08-AUG-16:00 | 2810.93 | 27-AUG-06:00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.09 | 01-SEP-16:00 | 3583.71 | 20-SEP-01:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 4845.45 | 31-OCT-21:02 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 7924.13 | 22-NOV-02:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 11351.20 | 16-DEC-06:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1998.90 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 594.82 | 13463.03 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 110760.34 | 20-JAN-05:01 | 0.00 | 25501.32 | 134575.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 112601.41 | 06-FEB-05:01 | 0.00 | 25501.32 | 134575.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 115512.76 | 20-MAR-03:01 | 0.00 | 10199.39 | 107660.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 117458.25 | 17-APR-03:02 | 0.00 | 7649.54 | 80745.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 120951.70 | 30-MAY-04:11 | 0.00 | 17850.93 | 94202.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 119723.61 | 12-JUN-04:12 | 0.00 | 12750.66 | 67287.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 118125.38 | 10-JUL-04:12 | 0.00 | 15300.79 | 80745.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 116914.87 | 02-AUG-04:12 | 0.00 | 15300.79 | 80745.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 117745.01 | 05-SEP-04:12 | 0.00 | 15300.79 | 80745.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 120880.71 | 10-OCT-04:11 | 0.00 | 25501.32 | 134575.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 119997.58 | 13-NOV-04:01 | 0.00 | 8924.46 | 94202.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 113893.82 | 18-DEC-05:01 | 0.00 | 25501.32 | 134575.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 110760.34 | 0.00 | 7649.54 | 67287.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 120951.70 | 0.00 | 25501.32 | 134575.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 52893.89 | 20-JAN-15:30 | 30632.53 | 41222.03 | 34413.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 87411.71 | 09-FEB-06:01 | 11285.67 | 16031.39 | 53531.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 90915.16 | 28-MAR-04:11 | 0.00 | 20611.78 | 53438.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 96091.29 | 24-APR-04:12 | 0.00 | 11450.99 | 29688.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 103336.81 | 30-MAY-04:11 | 0.00 | 16031.39 | 41563.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 100740.23 | 26-JUN-04:13 | 0.00 | 13741.19 | 35625.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 98252.34 | 17-JUL-04:12 | 0.00 | 13741.19 | 35625.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 96090.66 | 17-AUG-04:12 | 0.00 | 13741.19 | 35625.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 100880.99 | 05-SEP-04:12 | 0.00 | 13741.19 | 35625.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 96391.62 | 23-OCT-04:12 | 0.00 | 11450.99 | 29688.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 90311.77 | 21-NOV-05:11 | 0.00 | 18321.59 | 47501.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 88082.06 | 06-DEC-06:01 | 11285.67 | 16031.39 | 53531.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 52893.89 | 0.00 | 11450.99 | 29688.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 103336.81 | 30632.53 | 41222.03 | 53531.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 20501.88 | 06-JAN-09:00 | 15316.26 | 20611.01 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 26874.10 | 10-FEB-16:37 | 45948.79 | 61833.04 | 51619.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 41142.56 | 31-MAR-09:30 | 32029.16 | 41222.03 | 34413.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 81195.10 | 14-APR-05:03 | 6448.95 | 9160.79 | 30589.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 92391.94 | 30-MAY-04:11 | 0.00 | 16031.39 | 41563.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 88047.82 | 28-JUN-04:12 | 0.00 | 13741.19 | 35625.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 88518.67 | 25-JUL-04:11 | 0.00 | 16031.39 | 41563.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 87301.79 | 01-AUG-04:12 | 0.00 | 13741.19 | 35625.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 86463.11 | 01-SEP-04:12 | 0.00 | 13741.19 | 35625.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 79302.90 | 20-OCT-05:03 | 6448.95 | 9160.79 | 30589.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 81849.23 | 10-NOV-17:20 | 9673.43 | 22900.96 | 19118.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 21414.14 | 05-DEC-17:15 | 9673.43 | 22900.96 | 19118.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 20501.88 | 0.00 | 9160.79 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 92391.94 | 45948.79 | 61833.04 | 51619.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 17355.46 | 20-JAN-16:50 | 45948.79 | 61833.04 | 51619.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 19451.26 | 28-FEB-14:05 | 32029.16 | 41222.03 | 34413.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 28644.58 | 29-MAR-16:00 | 15316.26 | 20611.01 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 40829.47 | 13-APR-16:00 | 15316.26 | 20611.01 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 85020.59 | 26-MAY-04:12 | 0.00 | 13741.19 | 35625.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 84961.13 | 19-JUN-04:12 | 0.00 | 13741.19 | 35625.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 87278.56 | 05-JUL-04:12 | 0.00 | 13741.19 | 35625.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 86207.79 | 09-AUG-04:12 | 0.00 | 13741.19 | 35625.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 83534.33 | 01-SEP-04:12 | 0.00 | 13741.19 | 35625.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 38986.00 | 20-OCT-16:00 | 15316.26 | 20611.01 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 22206.11 | 17-NOV-17:00 | 15316.26 | 20611.01 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 17482.01 | 28-DEC-17:00 | 15316.26 | 20611.01 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 17355.46 | 0.00 | 13741.19 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 87278.56 | 45948.79 | 61833.04 | 51619.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2142.74 | 20-JAN-16:10 | 1923.11 | 2135.72 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 279.21 |
February | 2971.28 | 22-FEB-11:18 | 7692.44 | 4925.33 | 8642.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 138.65 |
March | 4416.43 | 27-MAR-13:30 | 2010.79 | 1231.33 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 230.91 |
April | 7155.67 | 18-APR-14:00 | 2010.79 | 1231.33 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 110.13 |
May | 13217.28 | 24-MAY-05:03 | 809.73 | 547.28 | 3840.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.94 |
June | 14238.75 | 26-JUN-04:12 | 0.00 | 1725.34 | 4473.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 220.47 |
July | 17255.49 | 23-JUL-16:11 | 809.73 | 547.22 | 5761.47 | 0.00 | 0.00 | 0.00 | 0.00 | 87.32 | 0.00 |
August | 12168.12 | 14-AUG-05:02 | 1012.16 | 1437.79 | 4801.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 55.54 |
September | 8248.32 | 01-SEP-15:00 | 1923.11 | 1231.33 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 12.80 | 0.00 |
October | 5593.54 | 02-OCT-13:10 | 2010.79 | 1231.33 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 56.73 |
November | 4370.82 | 01-NOV-13:30 | 2010.79 | 1231.33 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 58.07 |
December | 2521.10 | 07-DEC-06:03 | 1417.03 | 2012.90 | 6721.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 198.10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2142.74 | 0.00 | 547.22 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 17255.49 | 7692.44 | 4925.33 | 8642.21 | 0.00 | 0.00 | 0.00 | 0.00 | 87.32 | 279.21 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2884.67 | 31-JAN-11:00 | 2591.66 | 1587.03 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 205.93 |
February | 7287.13 | 28-FEB-10:10 | 3887.49 | 2380.55 | 4177.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 133.12 |
March | 14346.37 | 20-MAR-08:48 | 4957.30 | 3174.07 | 5569.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 60.27 |
April | 18909.61 | 30-APR-08:42 | 326.14 | 220.40 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 255.05 |
May | 26110.73 | 21-MAY-08:52 | 391.37 | 264.49 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 150.06 |
June | 27649.19 | 25-JUN-08:61 | 456.59 | 308.57 | 3248.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 85.83 |
July | 26731.21 | 23-JUL-09:32 | 391.37 | 264.49 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.02 |
August | 29020.54 | 13-AUG-09:31 | 521.82 | 352.65 | 3712.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 207.43 |
September | 19145.94 | 10-SEP-09:02 | 326.14 | 220.40 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 205.65 |
October | 16657.86 | 09-OCT-09:32 | 260.91 | 176.32 | 1856.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 172.54 |
November | 5317.33 | 16-NOV-09:35 | 2478.65 | 1587.03 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 108.09 |
December | 3059.46 | 01-DEC-10:20 | 2591.66 | 1587.03 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 292.29 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2884.67 | 260.91 | 176.32 | 1856.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.02 | |
Maximum of Months | 29020.54 | 4957.30 | 3174.07 | 5569.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 292.29 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 19638.91 | 27-JAN-11:50 | 3846.30 | 2462.72 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36.08 |
February | 28470.49 | 20-FEB-13:23 | 404.87 | 273.61 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1347.18 |
March | 31919.46 | 26-MAR-13:22 | 506.09 | 342.02 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 712.57 |
April | 33108.45 | 23-APR-12:52 | 607.31 | 410.42 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 332.36 |
May | 26311.89 | 14-MAY-12:02 | 404.87 | 273.61 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 424.02 |
June | 31512.30 | 25-JUN-11:22 | 607.31 | 410.42 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 7.47 | 0.00 |
July | 33765.86 | 16-JUL-12:22 | 607.31 | 410.42 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 177.65 |
August | 35984.63 | 13-AUG-12:51 | 809.75 | 547.23 | 5761.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 224.65 |
September | 34105.39 | 10-SEP-11:42 | 607.31 | 410.42 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 270.71 |
October | 34942.20 | 22-OCT-12:31 | 708.53 | 478.83 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 315.92 |
November | 22170.31 | 29-NOV-11:35 | 3846.30 | 2462.72 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 287.54 |
December | 14423.73 | 20-DEC-13:05 | 3846.30 | 2462.72 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 309.73 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 14423.73 | 404.87 | 273.61 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 35984.63 | 3846.30 | 2462.72 | 5761.56 | 0.00 | 0.00 | 0.00 | 0.00 | 7.47 | 1347.18 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4874.80 | 27-JAN-15:35 | 2478.65 | 1587.03 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 12650.86 | 27-FEB-15:40 | 3717.98 | 2380.55 | 4177.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 314.09 |
March | 31149.22 | 26-MAR-16:42 | 391.37 | 264.49 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 375.50 |
April | 35196.45 | 23-APR-16:11 | 521.82 | 352.65 | 3712.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 112.95 |
May | 33196.63 | 14-MAY-16:41 | 456.59 | 308.57 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 206.22 |
June | 32781.31 | 17-JUN-17:41 | 456.59 | 308.57 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 56.67 |
July | 38366.11 | 16-JUL-16:21 | 652.28 | 440.81 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 304.08 |
August | 33831.94 | 13-AUG-14:11 | 521.82 | 352.65 | 3712.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 125.45 |
September | 33189.16 | 03-SEP-17:01 | 0.00 | 396.73 | 3243.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 157.96 |
October | 23297.77 | 22-OCT-15:12 | 391.37 | 264.49 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 171.99 |
November | 9039.91 | 09-NOV-15:30 | 1239.33 | 793.52 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 203.35 |
December | 4723.76 | 20-DEC-15:30 | 1239.33 | 793.52 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 192.91 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 4723.76 | 0.00 | 264.49 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 38366.11 | 3717.98 | 2380.55 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 375.50 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1448.56 | 28-JAN-17:01 | 708.51 | 1006.34 | 5041.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 773.70 |
February | 1982.96 | 08-FEB-13:17 | 5769.33 | 3693.99 | 6481.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 263.41 |
March | 2667.45 | 27-MAR-14:00 | 2010.79 | 1231.33 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 510.47 |
April | 4558.37 | 18-APR-14:00 | 2010.79 | 1231.33 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 262.82 |
May | 10300.42 | 26-MAY-05:03 | 809.73 | 801.36 | 3840.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59.79 |
June | 13132.64 | 30-JUN-05:02 | 1012.16 | 1252.93 | 4801.23 | 0.00 | 0.00 | 0.00 | 0.00 | 34.99 | 0.00 |
July | 16696.70 | 23-JUL-15:21 | 1012.16 | 684.02 | 7201.84 | 0.00 | 0.00 | 0.00 | 0.00 | 256.84 | 0.00 |
August | 9150.58 | 09-AUG-14:00 | 2010.79 | 1231.33 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 44.31 | 0.00 |
September | 7465.22 | 01-SEP-15:20 | 1923.11 | 1231.33 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 27.15 | 0.00 |
October | 3734.81 | 12-OCT-12:33 | 5769.33 | 3693.99 | 6481.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 478.20 |
November | 2673.54 | 16-NOV-16:55 | 3846.22 | 5175.84 | 4321.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 160.56 |
December | 1452.27 | 30-DEC-17:02 | 506.08 | 718.81 | 3600.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 79.15 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1448.56 | 506.08 | 684.02 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 16696.70 | 5769.33 | 5175.84 | 7201.84 | 0.00 | 0.00 | 0.00 | 0.00 | 256.84 | 773.70 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2158.39 | 20-JAN-06:04 | 1043.64 | 1482.50 | 4950.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 597.22 |
February | 3318.54 | 08-FEB-10:50 | 0.00 | 1587.03 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 133.01 |
March | 12026.12 | 31-MAR-09:40 | 0.00 | 1587.03 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 424.04 |
April | 14233.08 | 18-APR-09:00 | 1239.33 | 793.52 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 130.32 |
May | 29729.60 | 14-MAY-08:31 | 456.59 | 308.57 | 3248.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1168.07 |
June | 32632.08 | 18-JUN-08:31 | 587.05 | 396.73 | 4177.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 671.72 |
July | 31219.58 | 23-JUL-07:21 | 521.82 | 352.65 | 3712.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 183.56 |
August | 32526.74 | 20-AUG-09:01 | 587.05 | 396.73 | 4177.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 670.37 |
September | 28464.75 | 10-SEP-09:32 | 391.37 | 264.49 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 529.62 |
October | 10755.55 | 18-OCT-09:00 | 3717.98 | 2380.55 | 4177.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 260.30 |
November | 3513.24 | 16-NOV-10:25 | 0.00 | 1587.03 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 227.17 |
December | 2226.78 | 05-DEC-06:04 | 1043.64 | 1482.50 | 4950.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 328.86 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2158.39 | 0.00 | 264.49 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 130.32 | |
Maximum of Months | 32632.08 | 3717.98 | 2380.55 | 4950.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1168.07 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 18851.75 | 27-JAN-13:40 | 1923.15 | 1231.36 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 24615.78 | 28-FEB-13:30 | 1923.15 | 1231.36 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 449.77 |
March | 36270.06 | 26-MAR-13:11 | 708.53 | 478.83 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1916.36 |
April | 37348.91 | 23-APR-14:31 | 809.75 | 547.23 | 5761.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 675.11 |
May | 33836.01 | 14-MAY-13:52 | 607.31 | 410.42 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 655.11 |
June | 34634.60 | 18-JUN-12:32 | 607.31 | 410.42 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 277.71 |
July | 35999.26 | 23-JUL-14:01 | 809.75 | 547.23 | 5761.56 | 0.00 | 0.00 | 0.00 | 0.00 | 83.89 | 0.00 |
August | 37594.02 | 20-AUG-13:01 | 809.75 | 547.23 | 5761.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 485.98 |
September | 38677.33 | 04-SEP-11:51 | 910.97 | 615.63 | 6481.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1691.90 |
October | 37060.08 | 22-OCT-13:11 | 708.53 | 478.83 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 660.69 |
November | 25919.73 | 07-NOV-12:28 | 4233.34 | 4925.43 | 7682.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 480.35 |
December | 13655.11 | 02-DEC-13:20 | 202.44 | 205.23 | 840.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 169.94 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 13655.11 | 202.44 | 205.23 | 840.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 38677.33 | 4233.34 | 4925.43 | 7682.08 | 0.00 | 0.00 | 0.00 | 0.00 | 83.89 | 1916.36 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3193.61 | 27-JAN-16:00 | 1239.33 | 793.52 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6698.69 | 08-FEB-16:30 | 1239.33 | 793.52 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 220.06 |
March | 28290.23 | 26-MAR-17:11 | 0.00 | 396.73 | 3243.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 921.88 |
April | 36347.22 | 23-APR-16:31 | 652.28 | 440.81 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 410.43 |
May | 35795.19 | 14-MAY-17:11 | 0.00 | 440.81 | 3603.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 673.00 |
June | 31433.43 | 17-JUN-17:41 | 456.59 | 308.57 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 142.37 |
July | 35284.70 | 23-JUL-16:01 | 652.28 | 440.81 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36.72 |
August | 32411.66 | 27-AUG-17:51 | 0.00 | 352.65 | 2882.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 252.56 |
September | 31620.00 | 03-SEP-17:01 | 0.00 | 396.73 | 3243.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 385.49 |
October | 12051.60 | 22-OCT-15:52 | 326.14 | 220.40 | 2320.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 269.43 |
November | 7000.20 | 10-NOV-17:20 | 782.73 | 1853.05 | 1547.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 200.02 |
December | 2521.52 | 20-DEC-15:40 | 1239.33 | 793.52 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 416.77 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2521.52 | 0.00 | 220.40 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 36347.22 | 1239.33 | 1853.05 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 921.88 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1608.74 | 28-JAN-17:01 | 708.51 | 1006.34 | 5041.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 960.67 |
February | 1759.86 | 08-FEB-14:40 | 4021.58 | 2462.66 | 4321.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 354.09 |
March | 2442.72 | 28-MAR-15:00 | 1923.11 | 1231.33 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 597.55 |
April | 4415.95 | 18-APR-14:00 | 2010.79 | 1231.33 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 331.95 |
May | 9598.32 | 24-MAY-14:30 | 1923.11 | 1231.33 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 86.45 | 0.00 |
June | 12744.23 | 29-JUN-05:03 | 809.73 | 547.28 | 3840.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41.70 |
July | 20847.63 | 23-JUL-15:21 | 1012.16 | 684.02 | 7201.84 | 0.00 | 0.00 | 0.00 | 0.00 | 271.66 | 0.00 |
August | 9735.00 | 09-AUG-15:30 | 1923.11 | 1231.33 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 46.45 | 0.00 |
September | 8009.28 | 01-SEP-15:20 | 1923.11 | 1231.33 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 31.87 | 0.00 |
October | 3238.73 | 19-OCT-13:40 | 4021.58 | 2462.66 | 4321.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 53.08 |
November | 2321.37 | 01-NOV-16:00 | 1923.11 | 1470.28 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 66.23 |
December | 1616.34 | 30-DEC-17:02 | 506.08 | 718.81 | 3600.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 98.32 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1608.74 | 506.08 | 547.28 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 20847.63 | 4021.58 | 2462.66 | 7201.84 | 0.00 | 0.00 | 0.00 | 0.00 | 271.66 | 960.67 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1911.09 | 21-JAN-17:02 | 391.37 | 555.88 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 772.38 |
February | 2851.67 | 28-FEB-10:33 | 3887.49 | 2380.55 | 4177.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 327.47 |
March | 6354.54 | 31-MAR-10:00 | 1295.83 | 793.52 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 502.26 |
April | 13518.86 | 18-APR-09:30 | 1295.83 | 793.52 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 174.57 |
May | 27784.77 | 21-MAY-09:21 | 521.82 | 352.65 | 3712.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 432.79 |
June | 32261.38 | 18-JUN-08:41 | 587.05 | 396.73 | 4177.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 815.94 |
July | 31056.05 | 23-JUL-07:21 | 521.82 | 352.65 | 3712.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 228.96 |
August | 28458.60 | 20-AUG-09:22 | 391.37 | 264.49 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 581.95 |
September | 15535.43 | 01-SEP-09:10 | 1295.83 | 793.52 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 56.49 |
October | 8290.15 | 19-OCT-09:30 | 1295.83 | 793.52 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 189.81 |
November | 2775.65 | 16-NOV-10:25 | 2591.66 | 1587.03 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 275.38 |
December | 2281.72 | 28-DEC-06:04 | 1043.64 | 1482.50 | 4950.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 231.79 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1911.09 | 391.37 | 264.49 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 56.49 | |
Maximum of Months | 32261.38 | 3887.49 | 2380.55 | 4950.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 815.94 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 16560.65 | 27-JAN-13:40 | 1923.15 | 1231.36 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 23737.73 | 28-FEB-13:45 | 3846.30 | 2462.72 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 641.37 |
March | 32749.55 | 19-MAR-13:51 | 708.53 | 478.83 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 737.83 |
April | 38908.95 | 23-APR-14:01 | 809.75 | 547.23 | 5761.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 951.70 |
May | 34349.63 | 14-MAY-13:52 | 607.31 | 410.42 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 779.18 |
June | 36394.54 | 18-JUN-12:42 | 607.31 | 410.42 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 361.30 |
July | 38497.78 | 23-JUL-14:01 | 809.75 | 547.23 | 5761.56 | 0.00 | 0.00 | 0.00 | 0.00 | 64.75 | 0.00 |
August | 36388.50 | 27-AUG-15:01 | 708.53 | 478.83 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 389.79 |
September | 39793.64 | 04-SEP-13:41 | 910.97 | 615.63 | 6481.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1948.76 |
October | 38006.14 | 22-OCT-13:31 | 708.53 | 478.83 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 739.06 |
November | 19696.71 | 17-NOV-13:10 | 1923.15 | 1231.36 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 537.14 |
December | 10937.26 | 02-DEC-13:30 | 202.44 | 205.23 | 840.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 189.52 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 10937.26 | 202.44 | 205.23 | 840.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 39793.64 | 3846.30 | 2462.72 | 6481.75 | 0.00 | 0.00 | 0.00 | 0.00 | 64.75 | 1948.76 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3074.31 | 27-JAN-16:00 | 1239.33 | 793.52 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6434.87 | 08-FEB-16:30 | 1239.33 | 793.52 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 274.70 |
March | 11317.77 | 28-MAR-17:00 | 391.37 | 440.84 | 773.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 124.26 |
April | 37376.01 | 23-APR-16:41 | 652.28 | 440.81 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 483.25 |
May | 36620.97 | 14-MAY-17:11 | 0.00 | 440.81 | 3603.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 823.32 |
June | 32608.47 | 17-JUN-17:41 | 456.59 | 308.57 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 180.33 |
July | 37286.59 | 23-JUL-16:01 | 652.28 | 440.81 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67.48 |
August | 34073.64 | 27-AUG-17:41 | 0.00 | 352.65 | 2882.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 330.79 |
September | 31355.11 | 03-SEP-17:12 | 0.00 | 264.49 | 2162.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 448.31 |
October | 11365.60 | 19-OCT-16:00 | 1239.33 | 793.52 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44.02 |
November | 3581.33 | 17-NOV-15:50 | 1239.33 | 793.52 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 315.01 |
December | 2478.17 | 05-DEC-06:04 | 1043.64 | 1482.50 | 4950.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 409.23 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2478.17 | 0.00 | 264.49 | 773.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 37376.01 | 1239.33 | 1482.50 | 4950.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 823.32 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 10814.36 | 28-JAN-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2084.17 |
February | 10731.36 | 17-FEB-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1095.40 |
March | 8999.69 | 06-MAR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2932.21 |
April | 7016.52 | 24-APR-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 289.16 |
May | 9773.43 | 30-MAY-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 226.46 |
June | 9336.61 | 27-JUN-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59.36 |
July | 11107.19 | 24-JUL-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 108.03 |
August | 9457.90 | 14-AUG-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 122.23 |
September | 9586.60 | 05-SEP-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 207.61 |
October | 7505.57 | 30-OCT-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 216.06 |
November | 6906.87 | 25-NOV-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2682.39 |
December | 9327.68 | 21-DEC-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1150.51 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 6906.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59.36 | |
Maximum of Months | 11107.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2932.21 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 14369.19 | 28-JAN-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3646.62 |
February | 15932.31 | 10-FEB-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4636.01 |
March | 12370.23 | 15-MAR-03:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4490.40 |
April | 11386.15 | 27-APR-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3405.19 |
May | 7429.31 | 19-MAY-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.91 |
June | 8478.98 | 30-JUN-15:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 251.79 | 0.00 |
July | 8497.62 | 24-JUL-15:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 121.27 | 0.00 |
August | 7802.01 | 25-AUG-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 6945.44 | 01-SEP-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.42 | 0.00 |
October | 10221.64 | 30-OCT-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1307.42 |
November | 12207.30 | 25-NOV-04:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4378.34 |
December | 15093.25 | 02-DEC-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3851.76 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 6945.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 15932.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 251.79 | 4636.01 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3858.46 |
February | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6708.79 |
March | 3336.62 | 31-MAR-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 592.96 |
April | 10449.92 | 13-APR-14:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 195.66 |
May | 18430.45 | 18-MAY-14:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 70.97 | 0.00 |
June | 20928.82 | 30-JUN-14:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 357.43 | 0.00 |
July | 19476.01 | 24-JUL-14:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 116.09 | 0.00 |
August | 17826.46 | 08-AUG-15:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 246.69 | 0.00 |
September | 15163.51 | 01-SEP-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.09 | 0.00 |
October | 7027.47 | 20-OCT-14:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 201.86 |
November | 1923.93 | 01-NOV-16:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 111.81 |
December | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4202.19 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 20928.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 357.43 | 6708.79 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 2289.88 | 25-JAN-16:30 | 222.14 | 578.72 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 4765.77 | 27-FEB-17:00 | 222.14 | 578.72 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 7052.75 | 31-MAR-24:00 | 0.00 | 32.15 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 8806.15 | 21-APR-18:20 | 23.38 | 192.90 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 3292.46 | 31-MAY-24:00 | 0.00 | 32.15 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5405.43 | 30-JUN-23:45 | 0.00 | 128.61 | 23383.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 7274.45 | 31-JUL-23:52 | 0.00 | 160.76 | 38972.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 8653.47 | 13-AUG-18:31 | 0.00 | 225.07 | 54560.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 3308.34 | 30-SEP-24:00 | 0.00 | 32.15 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 4824.78 | 31-OCT-24:00 | 0.00 | 32.15 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6254.08 | 09-NOV-16:10 | 222.14 | 578.72 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 7861.64 | 20-DEC-16:00 | 444.28 | 1157.44 | 15588.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 2289.88 | 0.00 | 32.15 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 8806.15 | 444.28 | 1157.44 | 54560.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 1822.28 | 27-JAN-16:30 | 222.14 | 578.72 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 4077.12 | 27-FEB-17:00 | 222.14 | 578.72 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6317.83 | 31-MAR-23:20 | 0.00 | 32.15 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 8439.64 | 21-APR-18:20 | 23.38 | 192.90 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 2937.55 | 14-MAY-18:43 | 0.00 | 192.92 | 11691.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5271.04 | 30-JUN-23:55 | 0.00 | 64.31 | 11691.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6918.77 | 31-JUL-23:52 | 0.00 | 160.76 | 38972.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 8283.56 | 02-AUG-18:40 | 23.38 | 192.90 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 3021.55 | 05-SEP-17:50 | 23.38 | 192.90 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 4265.79 | 18-OCT-16:50 | 70.15 | 321.51 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5680.00 | 09-NOV-16:20 | 222.14 | 578.72 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6939.60 | 20-DEC-16:05 | 444.28 | 1157.44 | 15588.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 1822.28 | 0.00 | 32.15 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 8439.64 | 444.28 | 1157.44 | 38972.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 1550.11 | 25-JAN-16:30 | 222.14 | 578.72 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 4021.52 | 27-FEB-17:00 | 222.14 | 578.72 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6239.50 | 28-MAR-17:50 | 23.38 | 192.90 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 8429.19 | 21-APR-18:20 | 23.38 | 192.90 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 2844.21 | 14-MAY-18:47 | 0.00 | 192.92 | 11691.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5250.42 | 30-JUN-23:34 | 0.00 | 160.76 | 29229.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6826.75 | 31-JUL-23:52 | 0.00 | 160.76 | 38972.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 8316.20 | 02-AUG-18:40 | 23.38 | 192.90 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 3018.24 | 05-SEP-17:50 | 23.38 | 192.90 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 4267.62 | 18-OCT-16:50 | 70.15 | 321.51 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5535.14 | 09-NOV-16:20 | 222.14 | 578.72 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6717.25 | 20-DEC-16:05 | 444.28 | 1157.44 | 15588.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 1550.11 | 0.00 | 160.76 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 8429.19 | 444.28 | 1157.44 | 38972.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 91311.54 | 20-JAN-17:00 | 9617.36 | 12942.03 | 189816.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 183678.30 | 22-FEB-17:00 | 4808.68 | 6471.01 | 189816.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 359138.72 | 31-MAR-24:00 | 0.00 | 359.47 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 368544.38 | 19-APR-16:00 | 4808.68 | 6471.01 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 175937.47 | 31-MAY-24:00 | 0.00 | 359.47 | 189816.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 268899.54 | 30-JUN-23:55 | 0.00 | 718.95 | 569448.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 361158.07 | 31-JUL-23:52 | 0.00 | 1797.37 | 1898162.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 378473.15 | 09-AUG-23:03 | 0.00 | 1437.90 | 1518530.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 176206.65 | 30-SEP-24:00 | 0.00 | 359.47 | 189816.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 267457.12 | 31-OCT-24:00 | 0.00 | 359.47 | 284724.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 276848.10 | 17-NOV-17:00 | 4808.68 | 6471.01 | 284724.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 367479.70 | 06-DEC-17:00 | 4808.68 | 6471.01 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 91311.54 | 0.00 | 359.47 | 189816.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 378473.15 | 9617.36 | 12942.03 | 1898162.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.170015E+13 | 1129360.98 | 02-JAN-08:09 | 0.155314E+13 | 3494739.04 | 09-JAN-07:10 |
February | 0.192310E+13 | 1286803.10 | 10-FEB-16:30 | 0.809619E+12 | 2948109.30 | 14-FEB-07:10 |
March | 0.253186E+13 | 1381130.31 | 17-MAR-15:00 | 0.478989E+12 | 2239371.12 | 15-MAR-06:00 |
April | 0.274862E+13 | 1779319.07 | 13-APR-15:20 | 0.191907E+12 | 1560055.73 | 05-APR-06:10 |
May | 0.182991E+13 | 1554108.57 | 25-MAY-15:20 | 0.876071E+11 | 597256.95 | 02-MAY-06:10 |
June | 0.227853E+13 | 1826468.27 | 30-JUN-15:09 | 0.738553E+11 | 176180.32 | 03-JUN-06:10 |
July | 0.279252E+13 | 2074464.89 | 05-JUL-15:09 | 0.691926E+11 | 84425.42 | 03-JUL-11:30 |
August | 0.314582E+13 | 2114105.39 | 08-AUG-15:20 | 0.724890E+11 | 213065.30 | 19-AUG-06:19 |
September | 0.162426E+13 | 1546178.34 | 01-SEP-15:00 | 0.796720E+11 | 541892.67 | 23-SEP-06:10 |
October | 0.206785E+13 | 1406908.50 | 20-OCT-15:09 | 0.192645E+12 | 1458499.73 | 30-OCT-06:10 |
November | 0.241414E+13 | 1471711.17 | 07-NOV-16:49 | 0.444281E+12 | 1832710.91 | 27-NOV-07:10 |
December | 0.283163E+13 | 1566698.33 | 27-DEC-08:09 | 0.122442E+13 | 3204596.65 | 26-DEC-07:10 |
Annual Sum or Average | 0.278884E+14 | 0.527781E+13 | ||||
Minimum of Months | 0.162426E+13 | 1129360.98 | 0.691926E+11 | 84425.42 | ||
Maximum of Months | 0.314582E+13 | 2114105.39 | 0.155314E+13 | 3494739.04 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [J] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [J] | HUMIDIFIER:ELECTRICITY [J] | HEATRECOVERY:ELECTRICITY [J] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 0.336332E+12 | 0.812592E+11 | 0.766053E+12 | 0.164273E+12 | 0.191811E+12 | 0.262276E+11 | 0.00 | 0.609882E+10 | 0.337799E+09 | 0.119444E+12 | 0.831840E+10 | 0.00 | 0.00 |
February | 0.299593E+12 | 0.652922E+11 | 0.978954E+12 | 0.148382E+12 | 0.170850E+12 | 0.235473E+11 | 0.00 | 0.218911E+11 | 0.167410E+10 | 0.205725E+12 | 0.719429E+10 | 0.00 | 0.00 |
March | 0.352578E+12 | 0.612903E+11 | 0.141687E+13 | 0.164522E+12 | 0.191006E+12 | 0.228448E+11 | 0.00 | 0.433267E+11 | 0.407780E+10 | 0.267589E+12 | 0.775471E+10 | 0.00 | 0.00 |
April | 0.312530E+12 | 0.482521E+11 | 0.165903E+13 | 0.158945E+12 | 0.194789E+12 | 0.188206E+11 | 0.00 | 0.805697E+11 | 0.192843E+11 | 0.252133E+12 | 0.426831E+10 | 0.00 | 0.00 |
May | 0.335160E+12 | 0.411642E+11 | 0.774844E+12 | 0.164393E+12 | 0.234104E+12 | 0.328218E+11 | 0.00 | 0.986676E+11 | 0.467429E+11 | 0.997726E+11 | 0.224447E+10 | 0.00 | 0.00 |
June | 0.332955E+12 | 0.355351E+11 | 0.106252E+13 | 0.159182E+12 | 0.255819E+12 | 0.488904E+11 | 0.00 | 0.242195E+12 | 0.961624E+11 | 0.436938E+11 | 0.157640E+10 | 0.00 | 0.00 |
July | 0.312086E+12 | 0.383631E+11 | 0.139340E+13 | 0.164155E+12 | 0.275867E+12 | 0.616913E+11 | 0.00 | 0.410274E+12 | 0.133270E+12 | 0.768856E+09 | 0.263854E+10 | 0.00 | 0.00 |
August | 0.349185E+12 | 0.454937E+11 | 0.173200E+13 | 0.164521E+12 | 0.255877E+12 | 0.568891E+11 | 0.00 | 0.408167E+12 | 0.130591E+12 | 0.159915E+10 | 0.149704E+10 | 0.00 | 0.00 |
September | 0.313669E+12 | 0.544708E+11 | 0.740713E+12 | 0.158944E+12 | 0.204936E+12 | 0.264409E+11 | 0.00 | 0.563345E+11 | 0.267672E+11 | 0.401234E+11 | 0.186561E+10 | 0.00 | 0.00 |
October | 0.329357E+12 | 0.677508E+11 | 0.108340E+13 | 0.164269E+12 | 0.186953E+12 | 0.183974E+11 | 0.00 | 0.370444E+11 | 0.923446E+10 | 0.166564E+12 | 0.487841E+10 | 0.00 | 0.00 |
November | 0.331376E+12 | 0.756144E+11 | 0.135889E+13 | 0.159046E+12 | 0.176016E+12 | 0.186677E+11 | 0.00 | 0.411421E+11 | 0.563975E+10 | 0.241546E+12 | 0.619896E+10 | 0.00 | 0.00 |
December | 0.327446E+12 | 0.839194E+11 | 0.170972E+13 | 0.164162E+12 | 0.188803E+12 | 0.265032E+11 | 0.00 | 0.517107E+11 | 0.347056E+10 | 0.267840E+12 | 0.805083E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.393227E+13 | 0.698405E+12 | 0.146764E+14 | 0.193479E+13 | 0.252683E+13 | 0.381742E+12 | 0.00 | 0.149742E+13 | 0.477252E+12 | 0.170680E+13 | 0.564860E+11 | 0.00 | 0.00 |
Minimum of Months | 0.299593E+12 | 0.355351E+11 | 0.740713E+12 | 0.148382E+12 | 0.170850E+12 | 0.183974E+11 | 0.00 | 0.609882E+10 | 0.337799E+09 | 0.768856E+09 | 0.149704E+10 | 0.00 | 0.00 |
Maximum of Months | 0.352578E+12 | 0.839194E+11 | 0.173200E+13 | 0.164522E+12 | 0.275867E+12 | 0.616913E+11 | 0.00 | 0.410274E+12 | 0.133270E+12 | 0.267840E+12 | 0.831840E+10 | 0.00 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [J] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.00 | 0.00 | 0.147349E+13 | 0.00 | 0.796463E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.736217E+12 | 0.00 | 0.734022E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.394333E+12 | 0.00 | 0.846568E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.115424E+12 | 0.00 | 0.764823E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.961029E+10 | 0.00 | 0.779968E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.318626E+09 | 0.00 | 0.735367E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 9895079.62 | 0.00 | 0.691827E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.382459E+09 | 0.00 | 0.721066E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.126264E+11 | 0.00 | 0.670457E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.121645E+12 | 0.00 | 0.710001E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.372149E+12 | 0.00 | 0.721321E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.114872E+13 | 0.00 | 0.756917E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.438493E+13 | 0.00 | 0.892880E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 9895079.62 | 0.00 | 0.670457E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.147349E+13 | 0.00 | 0.846568E+11 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | EXTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum} [W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 385834.94 | 02-JAN-08:09 | 57580.60 | 01-JAN-06:10 | 423497.50 | 02-JAN-08:09 | 118535.44 | 02-JAN-08:20 | 122767.00 | 02-JAN-06:19 | 31889.95 | 25-JAN-06:10 | 0.00 | 01-JAN-00:10 |
February | 375276.56 | 02-FEB-16:00 | 57580.60 | 01-FEB-06:10 | 541788.89 | 01-FEB-08:09 | 118518.19 | 15-FEB-08:20 | 211016.36 | 10-FEB-16:30 | 32560.21 | 13-FEB-06:10 | 0.00 | 01-FEB-00:10 |
March | 369206.61 | 03-MAR-16:00 | 57580.60 | 01-MAR-06:10 | 660080.29 | 01-MAR-08:09 | 118522.43 | 13-MAR-07:19 | 206973.21 | 31-MAR-09:30 | 31014.91 | 06-MAR-07:10 | 0.00 | 01-MAR-00:10 |
April | 339487.26 | 03-APR-07:10 | 57580.60 | 01-APR-05:10 | 778371.69 | 03-APR-07:10 | 118499.24 | 03-APR-07:19 | 215925.41 | 28-APR-10:00 | 31214.65 | 04-APR-11:30 | 0.00 | 01-APR-00:10 |
May | 333218.76 | 12-MAY-07:10 | 57580.60 | 01-MAY-19:30 | 423497.50 | 01-MAY-07:10 | 118494.36 | 12-MAY-07:19 | 284222.75 | 18-MAY-14:39 | 53802.67 | 16-MAY-12:00 | 0.00 | 01-MAY-00:10 |
June | 338173.03 | 30-JUN-07:10 | 57580.60 | 01-JUN-19:00 | 541788.89 | 01-JUN-07:10 | 118498.21 | 30-JUN-07:19 | 292299.10 | 28-JUN-14:30 | 54557.36 | 19-JUN-15:20 | 0.00 | 01-JUN-00:10 |
July | 333218.76 | 03-JUL-07:10 | 57580.60 | 01-JUL-20:19 | 660080.29 | 03-JUL-07:10 | 118494.36 | 03-JUL-07:19 | 331054.64 | 05-JUL-11:30 | 69323.28 | 05-JUL-10:39 | 0.00 | 01-JUL-00:10 |
August | 354856.85 | 31-AUG-07:10 | 57580.60 | 01-AUG-19:49 | 778371.69 | 01-AUG-07:10 | 118511.22 | 31-AUG-07:19 | 305999.95 | 08-AUG-15:20 | 54972.56 | 31-AUG-12:50 | 0.00 | 01-AUG-00:10 |
September | 354856.85 | 19-SEP-07:10 | 57580.60 | 01-SEP-05:10 | 423497.50 | 01-SEP-07:10 | 118511.22 | 19-SEP-07:19 | 287922.88 | 01-SEP-15:00 | 54854.02 | 01-SEP-13:09 | 0.00 | 01-SEP-00:10 |
October | 385834.94 | 30-OCT-07:10 | 57580.60 | 01-OCT-05:10 | 541788.89 | 02-OCT-07:10 | 118535.44 | 30-OCT-07:19 | 180037.33 | 20-OCT-15:09 | 28959.26 | 30-OCT-06:19 | 0.00 | 01-OCT-00:10 |
November | 385834.94 | 01-NOV-07:10 | 57580.60 | 01-NOV-05:10 | 660080.29 | 01-NOV-07:10 | 118535.44 | 01-NOV-07:19 | 149834.91 | 17-NOV-10:20 | 30756.68 | 27-NOV-07:40 | 0.00 | 01-NOV-00:10 |
December | 385834.94 | 01-DEC-16:19 | 57580.60 | 01-DEC-06:10 | 778371.69 | 01-DEC-08:09 | 118535.44 | 04-DEC-08:20 | 119449.44 | 26-DEC-06:10 | 32636.74 | 11-DEC-07:49 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 333218.76 | 57580.60 | 423497.50 | 118494.36 | 119449.44 | 28959.26 | 0.00 | |||||||
Maximum of Months | 385834.94 | 57580.60 | 778371.69 | 118535.44 | 331054.64 | 69323.28 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY {Maximum} [W] | HEATREJECTION:ELECTRICITY {TIMESTAMP} | HUMIDIFIER:ELECTRICITY {Maximum} [W] | HUMIDIFIER:ELECTRICITY {TIMESTAMP} | HEATRECOVERY:ELECTRICITY {Maximum} [W] | HEATRECOVERY:ELECTRICITY {TIMESTAMP} | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 8541.76 | 27-JAN-16:19 | 645.37 | 20-JAN-15:09 | 57676.62 | 21-JAN-15:00 | 6524.59 | 02-JAN-07:10 | 0.00 | 0.00 |
February | 16733.84 | 08-FEB-15:30 | 3818.26 | 08-FEB-15:50 | 100000.00 | 06-FEB-17:10 | 6524.59 | 01-FEB-07:10 | 0.00 | 0.00 |
March | 27824.59 | 29-MAR-11:30 | 4857.49 | 31-MAR-18:19 | 100000.00 | 01-MAR-04:10 | 6524.59 | 01-MAR-18:40 | 0.00 | 0.00 |
April | 252310.73 | 23-APR-16:19 | 52832.64 | 23-APR-16:19 | 100000.00 | 01-APR-04:19 | 6524.59 | 01-APR-16:10 | 0.00 | 0.00 |
May | 300724.18 | 25-MAY-15:00 | 89285.81 | 16-MAY-12:39 | 100000.00 | 06-MAY-16:19 | 6524.59 | 10-MAY-14:00 | 0.00 | 0.00 |
June | 469806.95 | 19-JUN-15:20 | 89285.81 | 06-JUN-12:20 | 100000.00 | 03-JUN-16:10 | 6524.59 | 06-JUN-11:00 | 0.00 | 0.00 |
July | 556452.58 | 05-JUL-10:20 | 89285.81 | 03-JUL-12:20 | 42481.65 | 07-JUL-17:00 | 6524.59 | 03-JUL-13:50 | 0.00 | 0.00 |
August | 523271.75 | 31-AUG-12:50 | 89285.81 | 04-AUG-13:39 | 80300.79 | 19-AUG-04:00 | 6524.59 | 08-AUG-10:30 | 0.00 | 0.00 |
September | 288776.29 | 01-SEP-13:09 | 89285.81 | 01-SEP-09:20 | 100000.00 | 08-SEP-14:39 | 6524.59 | 01-SEP-14:09 | 0.00 | 0.00 |
October | 164016.03 | 19-OCT-14:00 | 52183.34 | 19-OCT-14:00 | 100000.00 | 09-OCT-09:09 | 6524.59 | 07-OCT-16:19 | 0.00 | 0.00 |
November | 96070.96 | 01-NOV-14:00 | 49688.58 | 01-NOV-12:09 | 100000.00 | 02-NOV-21:10 | 6524.59 | 04-NOV-14:39 | 0.00 | 0.00 |
December | 24121.51 | 18-DEC-16:30 | 2954.82 | 28-DEC-15:50 | 100000.00 | 01-DEC-02:49 | 6524.59 | 01-DEC-07:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | ||||||||
Minimum of Months | 8541.76 | 645.37 | 42481.65 | 6524.59 | 0.00 | 0.00 | ||||
Maximum of Months | 556452.58 | 89285.81 | 100000.00 | 6524.59 | 0.00 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY {AT MAX/MIN} [W] | |
January | 1129360.98 | 02-JAN-08:09 | 385834.94 | 423497.50 | 57580.60 | 118337.19 | 85739.39 | 9089.28 | 0.00 | 1484.01 | 79.36 |
February | 1286803.10 | 10-FEB-16:30 | 334729.47 | 541788.89 | 0.00 | 84452.08 | 211016.36 | 3882.73 | 0.00 | 13034.44 | 889.33 |
March | 1381130.31 | 17-MAR-15:00 | 332294.83 | 660080.29 | 0.00 | 84450.25 | 176234.13 | 3813.50 | 0.00 | 18605.83 | 1909.16 |
April | 1779319.07 | 13-APR-15:20 | 332294.83 | 778371.69 | 0.00 | 84450.25 | 206583.88 | 27097.28 | 0.00 | 200848.59 | 49672.56 |
May | 1554108.57 | 25-MAY-15:20 | 332294.83 | 423497.50 | 0.00 | 84450.25 | 268590.14 | 52223.94 | 0.00 | 297241.51 | 89285.81 |
June | 1826468.27 | 30-JUN-15:09 | 332294.83 | 541788.89 | 0.00 | 84450.25 | 283712.88 | 54225.04 | 0.00 | 434185.97 | 89285.81 |
July | 2074464.89 | 05-JUL-15:09 | 332294.83 | 660080.29 | 0.00 | 84450.25 | 331054.64 | 68774.18 | 0.00 | 507613.78 | 89285.81 |
August | 2114105.39 | 08-AUG-15:20 | 332294.83 | 778371.69 | 0.00 | 84450.25 | 305999.95 | 53121.85 | 0.00 | 464056.42 | 89285.81 |
September | 1546178.34 | 01-SEP-15:00 | 332294.83 | 423497.50 | 0.00 | 84450.25 | 287922.88 | 52199.22 | 0.00 | 270003.26 | 89285.81 |
October | 1406908.50 | 20-OCT-15:09 | 332294.83 | 541788.89 | 0.00 | 84450.25 | 180037.33 | 26983.42 | 0.00 | 91766.18 | 49587.60 |
November | 1471711.17 | 07-NOV-16:49 | 385834.94 | 660080.29 | 57580.60 | 84492.05 | 141927.72 | 16348.92 | 0.00 | 18167.49 | 1665.68 |
December | 1566698.33 | 27-DEC-08:09 | 385834.94 | 778371.69 | 57580.60 | 118337.19 | 81846.37 | 17621.63 | 0.00 | 19213.80 | 1367.53 |
Annual Sum or Average | |||||||||||
Minimum of Months | 1129360.98 | 332294.83 | 423497.50 | 0.00 | 84450.25 | 81846.37 | 3813.50 | 0.00 | 1484.01 | 79.36 | |
Maximum of Months | 2114105.39 | 385834.94 | 778371.69 | 57580.60 | 118337.19 | 331054.64 | 68774.18 | 0.00 | 507613.78 | 89285.81 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS {Maximum} [W] | WATERSYSTEMS:NATURALGAS {TIMESTAMP} | COGENERATION:NATURALGAS [] | |
January | 0.00 | 0.00 | 3461431.52 | 09-JAN-07:10 | 0.00 | 89698.03 | 31-JAN-12:20 | 0.00 |
February | 0.00 | 0.00 | 2915469.06 | 14-FEB-07:10 | 0.00 | 90000.01 | 23-FEB-12:50 | 0.00 |
March | 0.00 | 0.00 | 2205749.74 | 15-MAR-06:00 | 0.00 | 89955.71 | 01-MAR-12:50 | 0.00 |
April | 0.00 | 0.00 | 1527076.07 | 05-APR-06:10 | 0.00 | 89387.03 | 03-APR-11:50 | 0.00 |
May | 0.00 | 0.00 | 568102.43 | 02-MAY-06:10 | 0.00 | 88232.67 | 01-MAY-11:50 | 0.00 |
June | 0.00 | 0.00 | 145975.27 | 03-JUN-06:10 | 0.00 | 86384.51 | 01-JUN-11:50 | 0.00 |
July | 0.00 | 0.00 | 10522.85 | 08-JUL-06:10 | 0.00 | 84425.42 | 03-JUL-11:30 | 0.00 |
August | 0.00 | 0.00 | 183037.25 | 19-AUG-06:19 | 0.00 | 83045.12 | 01-AUG-11:39 | 0.00 |
September | 0.00 | 0.00 | 511902.59 | 23-SEP-06:10 | 0.00 | 83288.01 | 29-SEP-11:20 | 0.00 |
October | 0.00 | 0.00 | 1426458.35 | 30-OCT-06:10 | 0.00 | 85073.78 | 31-OCT-11:39 | 0.00 |
November | 0.00 | 0.00 | 1800349.12 | 27-NOV-07:10 | 0.00 | 86977.83 | 30-NOV-12:39 | 0.00 |
December | 0.00 | 0.00 | 3172369.83 | 26-DEC-07:10 | 0.00 | 88548.12 | 29-DEC-12:30 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 10522.85 | 0.00 | 83045.12 | 0.00 | ||
Maximum of Months | 0.00 | 0.00 | 3461431.52 | 0.00 | 90000.01 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 25.74 | 0.00 | 25.74 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 25.99 | 0.00 | 25.99 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 26.02 | 0.00 | 26.02 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 26.61 | 0.50 | 26.74 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 26.69 | 0.00 | 26.69 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 5.83 | 26.12 | 1.00 | 25.92 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 5.50 | 26.11 | 0.00 | 26.11 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 5.33 | 26.91 | 0.00 | 26.91 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 5.67 | 26.78 | 0.00 | 26.78 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 26.25 | 0.00 | 26.25 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 25.11 | 0.67 | 24.92 |
Annual Sum or Average | 0.00 | 0.00 | 35.33 | 26.38 | 2.17 | 26.32 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 5.83 | 26.91 | 1.00 | 26.91 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 25.59 | 0.00 | 25.59 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 25.62 | 0.00 | 25.62 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 24.87 | 2.67 | 24.83 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 25.73 | 0.00 | 25.73 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 25.59 | 0.00 | 25.59 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 3.67 | 25.05 | 2.67 | 24.94 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 25.73 | 2.67 | 25.73 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 2.50 | 19.06 | 1.00 | 19.29 | 0.00 | 19.29 | 0.00 | 19.29 |
February | 0.17 | 18.70 | 0.00 | 18.70 | 0.00 | 18.70 | 0.00 | 18.70 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 24.70 | 1.00 | 24.70 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.17 | 18.62 | 0.00 | 18.62 | 0.00 | 18.62 | 0.00 | 18.62 |
December | 0.33 | 19.27 | 0.00 | 19.27 | 0.00 | 19.27 | 0.00 | 19.27 |
Annual Sum or Average | 3.17 | 19.04 | 1.00 | 19.24 | 1.00 | 20.29 | 1.00 | 21.01 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2.50 | 19.27 | 1.00 | 19.29 | 1.00 | 24.70 | 1.00 | 24.70 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 8.50 | 18.62 | 1.67 | 18.84 | 0.00 | 18.84 | 0.00 | 18.84 |
February | 3.67 | 18.27 | 0.17 | 18.36 | 0.00 | 18.36 | 0.00 | 18.36 |
March | 1.83 | 18.42 | 0.00 | 18.42 | 0.00 | 18.42 | 0.00 | 18.42 |
April | 0.33 | 19.15 | 0.00 | 19.15 | 0.00 | 19.15 | 0.00 | 19.15 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 24.70 | 0.83 | 24.70 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.50 | 19.17 | 0.00 | 19.17 | 0.00 | 19.17 | 0.00 | 19.17 |
November | 3.33 | 18.67 | 0.33 | 18.81 | 0.00 | 18.81 | 0.00 | 18.81 |
December | 6.50 | 18.70 | 1.67 | 18.94 | 0.00 | 18.94 | 0.00 | 18.94 |
Annual Sum or Average | 24.67 | 18.60 | 3.83 | 18.78 | 0.83 | 18.95 | 0.83 | 19.11 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 8.50 | 19.17 | 1.67 | 19.17 | 0.83 | 24.70 | 0.83 | 24.70 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 14.50 | 17.76 | 3.17 | 17.88 | 0.00 | 17.88 | 0.00 | 17.88 |
February | 3.83 | 19.07 | 0.50 | 19.20 | 0.00 | 19.20 | 0.00 | 19.20 |
March | 0.83 | 19.17 | 0.00 | 19.17 | 0.00 | 19.17 | 0.00 | 19.17 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 5.83 | 25.44 | 5.83 | 25.44 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.17 | 19.33 | 0.00 | 19.33 | 0.00 | 19.33 | 0.00 | 19.33 |
December | 3.67 | 18.94 | 0.50 | 19.09 | 0.00 | 19.09 | 0.00 | 19.09 |
Annual Sum or Average | 23.00 | 18.23 | 4.17 | 18.33 | 5.83 | 19.58 | 5.83 | 20.46 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 14.50 | 19.33 | 3.17 | 19.33 | 5.83 | 25.44 | 5.83 | 25.44 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 12.00 | 17.04 | 0.83 | 17.04 | 0.00 | 17.04 | 0.00 | 17.04 |
February | 3.83 | 18.76 | 0.00 | 18.76 | 0.00 | 18.76 | 0.00 | 18.76 |
March | 1.17 | 19.16 | 0.00 | 19.16 | 0.00 | 19.16 | 0.00 | 19.16 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 27.93 | 1.33 | 27.93 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 28.17 | 3.50 | 28.17 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 5.33 | 28.50 | 5.33 | 28.50 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 4.50 | 28.05 | 4.50 | 28.05 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.83 | 28.64 | 3.83 | 28.64 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 28.09 | 2.17 | 28.09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 27.81 | 1.17 | 27.81 |
November | 0.33 | 19.20 | 0.00 | 19.20 | 0.00 | 19.20 | 0.00 | 19.20 |
December | 4.83 | 18.68 | 0.17 | 18.74 | 0.00 | 18.74 | 0.00 | 18.74 |
Annual Sum or Average | 22.17 | 17.84 | 1.00 | 17.83 | 21.83 | 22.89 | 21.83 | 24.65 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.04 | 0.00 | 17.04 |
Maximum of Months | 12.00 | 19.20 | 0.83 | 19.20 | 5.33 | 28.64 | 5.33 | 28.64 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 11.67 | 17.31 | 0.83 | 17.28 | 0.17 | 17.38 | 0.17 | 17.47 |
February | 4.00 | 18.74 | 0.17 | 18.81 | 1.50 | 20.90 | 1.50 | 22.12 |
March | 1.17 | 19.09 | 0.00 | 19.09 | 4.17 | 25.90 | 4.17 | 26.74 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 28.34 | 2.33 | 28.34 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 27.99 | 2.17 | 27.99 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 28.02 | 3.00 | 28.02 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 9.33 | 26.74 | 9.17 | 26.73 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 7.00 | 28.24 | 7.00 | 28.24 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 6.00 | 28.28 | 6.00 | 28.28 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 4.33 | 28.51 | 4.33 | 28.51 |
November | 0.67 | 19.16 | 0.00 | 19.16 | 0.17 | 20.78 | 0.17 | 21.86 |
December | 5.00 | 18.57 | 0.17 | 18.63 | 0.00 | 18.63 | 0.00 | 18.63 |
Annual Sum or Average | 22.50 | 17.99 | 1.17 | 17.99 | 40.17 | 24.15 | 40.00 | 25.55 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.38 | 0.00 | 17.47 |
Maximum of Months | 11.67 | 19.16 | 0.83 | 19.16 | 9.33 | 28.51 | 9.17 | 28.51 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 5.50 | 18.50 | 0.00 | 18.50 | 0.00 | 18.50 | 0.00 | 18.50 |
February | 1.33 | 19.14 | 0.00 | 19.14 | 0.00 | 19.14 | 0.00 | 19.14 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 28.37 | 1.83 | 28.30 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 4.50 | 28.83 | 2.67 | 28.88 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 5.33 | 28.74 | 2.67 | 28.75 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 8.50 | 27.85 | 3.17 | 27.93 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 20.50 | 27.92 | 9.33 | 28.06 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 17.33 | 27.77 | 6.67 | 28.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 3.67 | 28.19 | 2.17 | 28.31 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 27.94 | 1.17 | 27.98 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.50 | 19.34 | 0.00 | 19.34 | 0.00 | 19.34 | 0.00 | 19.34 |
Annual Sum or Average | 7.33 | 18.67 | 0.00 | 18.67 | 63.67 | 27.07 | 29.67 | 27.48 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 5.50 | 19.34 | 0.00 | 19.34 | 20.50 | 28.83 | 9.33 | 28.88 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 113.67 | 16.84 | 50.50 | 17.23 | 0.00 | 17.23 | 0.00 | 17.23 |
February | 59.83 | 17.01 | 19.17 | 17.38 | 0.00 | 17.38 | 0.00 | 17.38 |
March | 22.33 | 17.86 | 5.83 | 18.20 | 0.00 | 18.20 | 0.00 | 18.20 |
April | 2.17 | 18.72 | 0.00 | 18.72 | 0.00 | 18.72 | 0.00 | 18.72 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 25.25 | 5.17 | 25.25 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.83 | 19.09 | 0.00 | 19.09 | 0.00 | 19.09 | 0.00 | 19.09 |
November | 18.50 | 17.18 | 3.67 | 17.23 | 0.00 | 17.23 | 0.00 | 17.23 |
December | 92.33 | 16.50 | 36.17 | 16.78 | 0.00 | 16.78 | 0.00 | 16.78 |
Annual Sum or Average | 309.67 | 16.89 | 115.33 | 17.20 | 5.17 | 17.29 | 5.17 | 17.39 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 113.67 | 19.09 | 50.50 | 19.09 | 5.17 | 25.25 | 5.17 | 25.25 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 54.50 | 15.14 | 12.17 | 15.07 | 0.00 | 15.07 | 0.00 | 15.07 |
February | 30.17 | 15.71 | 1.83 | 15.73 | 0.00 | 15.73 | 0.00 | 15.73 |
March | 11.67 | 17.07 | 0.50 | 17.05 | 0.00 | 17.05 | 0.00 | 17.05 |
April | 2.17 | 18.80 | 0.00 | 18.80 | 0.17 | 19.43 | 0.17 | 19.98 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 27.94 | 3.17 | 27.94 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 5.50 | 28.69 | 5.50 | 28.69 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 4.67 | 28.31 | 4.67 | 28.31 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 4.50 | 28.55 | 4.50 | 28.55 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 27.94 | 1.67 | 27.94 |
October | 0.83 | 19.08 | 0.00 | 19.08 | 0.17 | 20.46 | 0.17 | 21.44 |
November | 13.33 | 16.33 | 1.33 | 16.20 | 0.00 | 16.20 | 0.00 | 16.20 |
December | 53.83 | 15.07 | 13.00 | 14.97 | 0.00 | 14.97 | 0.00 | 14.97 |
Annual Sum or Average | 166.50 | 15.52 | 28.83 | 15.41 | 19.83 | 16.60 | 19.83 | 17.60 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.97 | 0.00 | 14.97 |
Maximum of Months | 54.50 | 19.08 | 13.00 | 19.08 | 5.50 | 28.69 | 5.50 | 28.69 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 41.33 | 15.54 | 5.33 | 15.52 | 0.00 | 15.52 | 0.00 | 15.52 |
February | 20.33 | 16.36 | 1.83 | 16.39 | 0.33 | 16.55 | 0.33 | 16.71 |
March | 9.33 | 17.29 | 0.67 | 17.22 | 3.67 | 20.21 | 3.67 | 21.94 |
April | 1.67 | 19.00 | 0.00 | 19.00 | 2.17 | 24.27 | 2.00 | 25.69 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 28.03 | 2.50 | 28.03 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 28.02 | 3.00 | 28.02 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 8.00 | 27.08 | 7.67 | 27.07 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 6.33 | 28.35 | 6.17 | 28.37 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 7.33 | 27.84 | 7.33 | 27.84 |
October | 0.33 | 18.80 | 0.00 | 18.80 | 4.50 | 28.01 | 4.50 | 28.34 |
November | 10.00 | 16.67 | 0.67 | 16.56 | 0.00 | 16.56 | 0.00 | 16.56 |
December | 41.67 | 15.50 | 6.67 | 15.44 | 0.00 | 15.44 | 0.00 | 15.44 |
Annual Sum or Average | 124.67 | 15.94 | 15.17 | 15.88 | 37.83 | 18.46 | 37.17 | 20.10 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.44 | 0.00 | 15.44 |
Maximum of Months | 41.67 | 19.00 | 6.67 | 19.00 | 8.00 | 28.35 | 7.67 | 28.37 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 44.33 | 15.32 | 9.33 | 15.22 | 0.00 | 15.22 | 0.00 | 15.22 |
February | 22.17 | 16.09 | 2.83 | 16.02 | 0.00 | 16.02 | 0.00 | 16.02 |
March | 8.67 | 17.36 | 0.33 | 17.27 | 1.17 | 18.44 | 0.67 | 18.97 |
April | 1.67 | 19.09 | 0.00 | 19.09 | 2.17 | 24.61 | 1.00 | 25.52 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 4.33 | 28.96 | 1.83 | 28.99 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 3.67 | 28.40 | 1.50 | 28.38 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 9.17 | 28.69 | 4.33 | 28.77 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 6.50 | 28.50 | 3.50 | 28.55 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 28.79 | 1.17 | 28.80 |
October | 0.33 | 18.88 | 0.00 | 18.88 | 0.33 | 23.33 | 0.33 | 24.81 |
November | 6.17 | 17.67 | 0.00 | 17.67 | 0.00 | 17.67 | 0.00 | 17.67 |
December | 43.17 | 15.34 | 9.50 | 15.19 | 0.00 | 15.19 | 0.00 | 15.19 |
Annual Sum or Average | 126.50 | 15.77 | 22.00 | 15.62 | 29.00 | 17.75 | 14.33 | 18.56 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.19 | 0.00 | 15.19 |
Maximum of Months | 44.33 | 19.09 | 9.50 | 19.09 | 9.17 | 28.96 | 4.33 | 28.99 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 160.17 | 16.23 | 71.17 | 16.63 | 0.00 | 16.63 | 0.00 | 16.63 |
February | 104.67 | 16.32 | 39.50 | 16.74 | 0.00 | 16.74 | 0.00 | 16.74 |
March | 52.83 | 16.83 | 18.33 | 17.10 | 0.00 | 17.10 | 0.00 | 17.10 |
April | 11.67 | 17.02 | 1.67 | 17.01 | 0.00 | 17.01 | 0.00 | 17.01 |
May | 0.33 | 18.81 | 0.00 | 18.81 | 0.00 | 18.81 | 0.00 | 18.81 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 26.63 | 2.00 | 26.53 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 8.00 | 17.36 | 1.17 | 17.43 | 0.00 | 17.43 | 0.00 | 17.43 |
November | 54.33 | 16.19 | 18.33 | 16.31 | 0.00 | 16.31 | 0.00 | 16.31 |
December | 143.00 | 15.94 | 60.83 | 16.23 | 0.00 | 16.23 | 0.00 | 16.23 |
Annual Sum or Average | 535.00 | 16.26 | 211.00 | 16.57 | 2.67 | 16.61 | 2.00 | 16.64 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 160.17 | 18.81 | 71.17 | 18.81 | 2.67 | 26.63 | 2.00 | 26.53 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 82.33 | 14.61 | 21.83 | 14.56 | 0.00 | 14.56 | 0.00 | 14.56 |
February | 56.33 | 14.96 | 10.00 | 14.96 | 0.00 | 14.96 | 0.00 | 14.96 |
March | 28.33 | 15.79 | 3.00 | 15.69 | 0.00 | 15.69 | 0.00 | 15.69 |
April | 9.33 | 16.57 | 0.83 | 16.41 | 0.00 | 16.41 | 0.00 | 16.41 |
May | 0.33 | 19.07 | 0.00 | 19.07 | 1.67 | 26.57 | 1.67 | 27.25 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 5.67 | 28.56 | 5.67 | 28.56 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 4.67 | 28.36 | 4.33 | 28.39 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 4.17 | 28.43 | 4.17 | 28.43 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.61 | 0.83 | 27.61 |
October | 6.33 | 17.11 | 0.17 | 17.06 | 0.00 | 17.06 | 0.00 | 17.06 |
November | 40.33 | 15.29 | 9.33 | 15.17 | 0.00 | 15.17 | 0.00 | 15.17 |
December | 76.67 | 14.52 | 20.50 | 14.46 | 0.00 | 14.46 | 0.00 | 14.46 |
Annual Sum or Average | 300.00 | 14.97 | 65.67 | 14.88 | 17.00 | 15.48 | 16.67 | 16.02 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.46 | 0.00 | 14.46 |
Maximum of Months | 82.33 | 19.07 | 21.83 | 19.07 | 5.67 | 28.56 | 5.67 | 28.56 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 75.67 | 15.07 | 17.00 | 15.06 | 0.00 | 15.06 | 0.00 | 15.06 |
February | 45.00 | 15.37 | 5.17 | 15.38 | 0.00 | 15.38 | 0.00 | 15.38 |
March | 21.33 | 16.35 | 2.00 | 16.24 | 1.83 | 17.09 | 1.83 | 17.83 |
April | 7.17 | 17.03 | 0.83 | 16.79 | 1.50 | 18.63 | 1.33 | 19.85 |
May | 0.33 | 19.17 | 0.00 | 19.17 | 1.83 | 26.56 | 1.83 | 27.18 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 28.02 | 2.83 | 28.02 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 6.83 | 27.59 | 6.17 | 27.59 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 6.00 | 28.38 | 6.00 | 28.38 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 28.23 | 5.00 | 28.25 |
October | 4.00 | 17.59 | 0.00 | 17.59 | 3.67 | 22.77 | 3.67 | 24.60 |
November | 32.67 | 15.56 | 8.17 | 15.40 | 0.00 | 15.40 | 0.00 | 15.40 |
December | 69.33 | 14.98 | 14.50 | 14.96 | 0.00 | 14.96 | 0.00 | 14.96 |
Annual Sum or Average | 255.50 | 15.37 | 47.67 | 15.30 | 29.67 | 16.44 | 28.67 | 17.37 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.96 | 0.00 | 14.96 |
Maximum of Months | 75.67 | 19.17 | 17.00 | 19.17 | 6.83 | 28.38 | 6.17 | 28.38 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 75.17 | 14.70 | 19.50 | 14.64 | 0.00 | 14.64 | 0.00 | 14.64 |
February | 44.17 | 15.15 | 6.50 | 15.13 | 0.00 | 15.13 | 0.00 | 15.13 |
March | 19.33 | 16.29 | 2.00 | 16.13 | 0.17 | 16.22 | 0.00 | 16.22 |
April | 5.67 | 17.51 | 0.67 | 17.24 | 1.67 | 19.72 | 0.83 | 20.63 |
May | 0.17 | 19.37 | 0.00 | 19.37 | 4.00 | 28.57 | 1.67 | 28.69 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 28.47 | 1.50 | 28.43 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 9.00 | 28.77 | 4.33 | 28.87 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 6.50 | 28.51 | 3.83 | 28.56 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 28.79 | 0.83 | 28.81 |
October | 2.67 | 18.48 | 0.00 | 18.48 | 0.17 | 19.00 | 0.17 | 19.46 |
November | 28.00 | 15.64 | 7.33 | 15.48 | 0.00 | 15.48 | 0.00 | 15.48 |
December | 62.50 | 14.65 | 14.50 | 14.58 | 0.00 | 14.58 | 0.00 | 14.58 |
Annual Sum or Average | 237.67 | 15.12 | 50.50 | 15.02 | 26.50 | 16.17 | 13.17 | 16.68 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.58 | 0.00 | 14.58 |
Maximum of Months | 75.17 | 19.37 | 19.50 | 19.37 | 9.00 | 28.79 | 4.33 | 28.87 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 4.83 | 28.75 | 2.00 | 28.58 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 4.83 | 28.75 | 2.00 | 28.58 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 4.83 | 28.75 | 2.00 | 28.58 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 28.64 | 0.67 | 28.51 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 3.33 | 28.64 | 0.67 | 28.51 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 28.64 | 0.67 | 28.51 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 28.53 | 0.33 | 28.44 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 2.83 | 28.53 | 0.33 | 28.44 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 28.53 | 0.33 | 28.44 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 60.50 | 28.98 | 51.83 | 29.03 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 141.33 | 29.38 | 135.17 | 29.41 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 201.83 | 29.26 | 187.00 | 29.30 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 141.33 | 29.38 | 135.17 | 29.41 |
Report: ComfortReportSimple55Monthly
For: BASEMENT
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 454.17 | 23.61 | 0.00 | 23.61 | 0.00 | 23.61 |
February | 342.17 | 23.92 | 2.00 | 23.93 | 0.00 | 23.93 |
March | 312.33 | 24.00 | 17.83 | 24.12 | 0.00 | 24.12 |
April | 204.17 | 24.00 | 74.33 | 24.61 | 0.00 | 24.61 |
May | 43.17 | 24.00 | 231.33 | 24.86 | 11.33 | 24.83 |
June | 136.50 | 24.73 | 373.17 | 24.64 | 132.83 | 24.66 |
July | 154.67 | 25.24 | 491.17 | 24.78 | 154.67 | 24.87 |
August | 77.67 | 24.72 | 501.50 | 24.53 | 77.67 | 24.56 |
September | 10.50 | 24.00 | 254.83 | 25.00 | 10.50 | 24.96 |
October | 26.33 | 24.00 | 133.17 | 25.71 | 0.00 | 25.71 |
November | 181.33 | 24.00 | 91.00 | 24.64 | 0.00 | 24.64 |
December | 351.17 | 23.86 | 12.67 | 23.93 | 0.00 | 23.93 |
Annual Sum or Average | 2294.17 | 24.04 | 2183.00 | 24.46 | 387.00 | 24.50 |
Minimum of Months | 10.50 | 23.61 | 0.00 | 23.61 | 0.00 | 23.61 |
Maximum of Months | 454.17 | 25.24 | 501.50 | 25.71 | 154.67 | 25.71 |
Report: ComfortReportSimple55Monthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 500.83 | 23.23 | 16.67 | 23.13 | 16.67 | 23.04 |
February | 412.00 | 23.83 | 0.00 | 23.83 | 0.00 | 23.83 |
March | 334.33 | 23.95 | 5.50 | 23.98 | 0.00 | 23.98 |
April | 153.67 | 23.99 | 54.33 | 24.47 | 0.00 | 24.47 |
May | 51.83 | 24.00 | 202.33 | 24.47 | 0.00 | 24.47 |
June | 6.50 | 24.86 | 375.17 | 24.32 | 2.50 | 24.33 |
July | 3.00 | 24.77 | 493.17 | 24.30 | 3.00 | 24.30 |
August | 0.00 | 0.00 | 502.83 | 24.25 | 0.00 | 24.25 |
September | 3.17 | 23.83 | 243.33 | 24.57 | 0.00 | 24.57 |
October | 53.83 | 23.91 | 95.50 | 24.79 | 0.00 | 24.79 |
November | 213.33 | 23.94 | 32.17 | 24.05 | 0.00 | 24.05 |
December | 427.17 | 23.88 | 0.00 | 23.88 | 0.00 | 23.88 |
Annual Sum or Average | 2159.67 | 23.75 | 2021.00 | 24.07 | 22.17 | 24.06 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 23.13 | 0.00 | 23.04 |
Maximum of Months | 500.83 | 24.86 | 502.83 | 24.79 | 16.67 | 24.79 |
Report: ComfortReportSimple55Monthly
For: CORE_MID
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 21.34 | 218.83 | 21.01 | 218.83 | 20.84 |
February | 454.00 | 22.04 | 95.00 | 21.77 | 95.00 | 21.58 |
March | 510.33 | 22.88 | 27.67 | 22.78 | 27.67 | 22.69 |
April | 423.83 | 23.54 | 0.00 | 23.54 | 0.00 | 23.54 |
May | 142.50 | 23.73 | 153.83 | 24.13 | 0.00 | 24.13 |
June | 38.17 | 24.02 | 322.00 | 24.21 | 8.00 | 24.23 |
July | 3.33 | 24.34 | 470.50 | 24.27 | 3.00 | 24.27 |
August | 12.33 | 23.46 | 430.00 | 24.17 | 0.00 | 24.17 |
September | 104.83 | 23.54 | 132.33 | 24.04 | 2.83 | 24.04 |
October | 359.00 | 23.37 | 4.67 | 23.38 | 0.00 | 23.38 |
November | 469.83 | 22.76 | 40.83 | 22.59 | 38.83 | 22.45 |
December | 497.00 | 21.61 | 158.83 | 21.31 | 158.83 | 21.13 |
Annual Sum or Average | 3517.17 | 22.56 | 2054.50 | 22.82 | 553.00 | 22.61 |
Minimum of Months | 3.33 | 21.34 | 0.00 | 21.01 | 0.00 | 20.84 |
Maximum of Months | 510.33 | 24.34 | 470.50 | 24.27 | 218.83 | 24.27 |
Report: ComfortReportSimple55Monthly
For: CORE_TOP
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.46 | 379.17 | 20.27 | 379.17 | 20.19 |
February | 454.00 | 20.89 | 271.50 | 20.60 | 271.50 | 20.47 |
March | 514.00 | 21.62 | 182.83 | 21.27 | 182.83 | 21.07 |
April | 461.33 | 22.55 | 60.67 | 22.29 | 60.67 | 22.08 |
May | 199.67 | 23.19 | 143.00 | 23.69 | 2.00 | 23.68 |
June | 81.50 | 23.18 | 299.00 | 23.96 | 7.83 | 23.96 |
July | 32.00 | 23.34 | 436.17 | 24.18 | 3.00 | 24.19 |
August | 44.83 | 23.25 | 394.17 | 24.05 | 1.83 | 24.05 |
September | 242.83 | 23.13 | 74.50 | 23.37 | 11.00 | 23.40 |
October | 461.50 | 22.21 | 48.67 | 21.98 | 48.67 | 21.79 |
November | 487.67 | 21.32 | 191.33 | 20.91 | 191.33 | 20.68 |
December | 497.00 | 20.54 | 346.67 | 20.32 | 346.67 | 20.23 |
Annual Sum or Average | 3978.33 | 21.63 | 2827.67 | 21.80 | 1506.50 | 21.49 |
Minimum of Months | 32.00 | 20.46 | 48.67 | 20.27 | 1.83 | 20.19 |
Maximum of Months | 514.00 | 23.34 | 436.17 | 24.18 | 379.17 | 24.19 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.37 | 456.33 | 20.31 | 456.33 | 20.30 |
February | 454.00 | 20.99 | 306.33 | 20.83 | 306.33 | 20.76 |
March | 512.00 | 21.78 | 158.00 | 21.53 | 158.00 | 21.38 |
April | 430.33 | 23.09 | 19.67 | 23.06 | 13.33 | 23.00 |
May | 159.50 | 23.63 | 181.00 | 24.06 | 0.00 | 24.06 |
June | 13.83 | 24.73 | 382.00 | 24.33 | 4.50 | 24.36 |
July | 17.50 | 26.06 | 485.33 | 24.45 | 15.33 | 24.51 |
August | 10.00 | 23.62 | 464.33 | 24.23 | 0.33 | 24.23 |
September | 182.83 | 23.30 | 128.33 | 23.77 | 0.00 | 23.77 |
October | 440.67 | 22.94 | 5.00 | 22.94 | 2.00 | 22.93 |
November | 474.83 | 21.85 | 107.67 | 21.65 | 104.17 | 21.49 |
December | 497.00 | 20.61 | 376.17 | 20.49 | 376.17 | 20.44 |
Annual Sum or Average | 3694.50 | 21.82 | 3070.17 | 22.15 | 1436.50 | 21.86 |
Minimum of Months | 10.00 | 20.37 | 5.00 | 20.31 | 0.00 | 20.30 |
Maximum of Months | 512.00 | 26.06 | 485.33 | 24.45 | 456.33 | 24.51 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.37 | 440.83 | 20.31 | 440.83 | 20.28 |
February | 450.33 | 21.11 | 270.17 | 20.92 | 270.17 | 20.83 |
March | 462.50 | 21.59 | 165.83 | 21.47 | 151.00 | 21.33 |
April | 335.33 | 22.45 | 80.17 | 22.73 | 17.50 | 22.71 |
May | 145.83 | 23.37 | 247.67 | 24.10 | 10.33 | 24.18 |
June | 68.33 | 24.35 | 388.83 | 24.33 | 23.67 | 24.46 |
July | 42.50 | 24.91 | 454.83 | 24.33 | 26.00 | 24.43 |
August | 81.83 | 23.72 | 389.00 | 24.13 | 17.00 | 24.23 |
September | 231.00 | 22.89 | 174.00 | 23.56 | 7.83 | 23.63 |
October | 436.33 | 22.25 | 36.83 | 22.43 | 6.83 | 22.45 |
November | 481.83 | 21.40 | 142.17 | 21.22 | 142.17 | 21.10 |
December | 497.00 | 20.50 | 420.17 | 20.43 | 420.17 | 20.41 |
Annual Sum or Average | 3734.83 | 21.64 | 3210.50 | 22.08 | 1533.50 | 21.85 |
Minimum of Months | 42.50 | 20.37 | 36.83 | 20.31 | 6.83 | 20.28 |
Maximum of Months | 502.00 | 24.91 | 454.83 | 24.33 | 440.83 | 24.46 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 463.00 | 20.75 | 345.83 | 20.53 | 338.00 | 20.42 |
February | 359.83 | 21.35 | 228.83 | 21.30 | 191.83 | 21.11 |
March | 397.33 | 21.83 | 188.50 | 21.90 | 137.33 | 21.75 |
April | 315.17 | 22.61 | 105.50 | 22.93 | 29.00 | 22.90 |
May | 154.50 | 23.18 | 236.00 | 23.96 | 5.00 | 24.00 |
June | 79.17 | 23.81 | 357.50 | 24.22 | 13.17 | 24.29 |
July | 43.67 | 25.40 | 451.67 | 24.46 | 27.67 | 24.58 |
August | 58.83 | 24.90 | 437.33 | 24.37 | 26.83 | 24.51 |
September | 195.00 | 23.34 | 228.50 | 24.00 | 24.83 | 24.16 |
October | 376.67 | 22.54 | 98.33 | 22.92 | 27.17 | 23.00 |
November | 420.00 | 21.61 | 163.33 | 21.53 | 127.33 | 21.33 |
December | 457.33 | 20.81 | 316.67 | 20.64 | 313.67 | 20.55 |
Annual Sum or Average | 3320.50 | 21.91 | 3158.00 | 22.43 | 1261.83 | 22.21 |
Minimum of Months | 43.67 | 20.75 | 98.33 | 20.53 | 5.00 | 20.42 |
Maximum of Months | 463.00 | 25.40 | 451.67 | 24.46 | 338.00 | 24.58 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 500.17 | 20.75 | 373.33 | 20.62 | 373.33 | 20.57 |
February | 419.33 | 21.60 | 158.17 | 21.44 | 149.17 | 21.31 |
March | 409.67 | 22.42 | 65.33 | 22.53 | 30.33 | 22.50 |
April | 176.50 | 23.52 | 126.67 | 24.13 | 10.17 | 24.23 |
May | 118.00 | 23.70 | 296.83 | 24.31 | 24.67 | 24.39 |
June | 44.83 | 25.48 | 451.17 | 24.53 | 41.00 | 24.61 |
July | 95.00 | 25.84 | 497.00 | 24.79 | 95.00 | 24.93 |
August | 67.83 | 25.84 | 510.50 | 24.63 | 67.83 | 24.76 |
September | 142.17 | 23.28 | 242.33 | 24.08 | 14.17 | 24.17 |
October | 311.50 | 22.97 | 75.83 | 23.30 | 3.67 | 23.33 |
November | 418.67 | 22.48 | 33.33 | 22.49 | 17.00 | 22.44 |
December | 495.17 | 21.56 | 157.83 | 21.32 | 157.83 | 21.18 |
Annual Sum or Average | 3198.83 | 22.34 | 2988.33 | 22.94 | 984.17 | 22.81 |
Minimum of Months | 44.83 | 20.75 | 33.33 | 20.62 | 3.67 | 20.57 |
Maximum of Months | 500.17 | 25.84 | 510.50 | 24.79 | 373.33 | 24.93 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.65 | 502.00 | 19.65 | 502.00 | 19.65 |
February | 454.00 | 19.93 | 445.00 | 19.92 | 445.00 | 19.91 |
March | 514.00 | 20.52 | 409.50 | 20.40 | 409.50 | 20.35 |
April | 476.33 | 21.58 | 159.17 | 21.25 | 158.17 | 21.05 |
May | 234.67 | 22.96 | 147.83 | 23.46 | 4.00 | 23.43 |
June | 78.33 | 23.68 | 303.50 | 24.13 | 10.00 | 24.17 |
July | 62.33 | 25.07 | 453.83 | 24.44 | 45.17 | 24.54 |
August | 79.33 | 23.07 | 361.67 | 23.94 | 1.17 | 23.94 |
September | 328.67 | 22.68 | 65.83 | 22.92 | 4.67 | 22.92 |
October | 498.00 | 21.39 | 125.83 | 21.13 | 125.83 | 20.97 |
November | 489.00 | 20.23 | 387.83 | 20.09 | 387.83 | 20.04 |
December | 497.00 | 19.71 | 497.00 | 19.71 | 497.00 | 19.71 |
Annual Sum or Average | 4213.67 | 20.92 | 3859.00 | 21.15 | 2590.33 | 20.88 |
Minimum of Months | 62.33 | 19.65 | 65.83 | 19.65 | 1.17 | 19.65 |
Maximum of Months | 514.00 | 25.07 | 502.00 | 24.44 | 502.00 | 24.54 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 427.00 | 19.57 | 427.00 | 19.57 | 427.00 | 19.57 |
February | 385.00 | 19.93 | 356.17 | 19.88 | 356.17 | 19.86 |
March | 419.50 | 20.79 | 285.33 | 20.60 | 284.00 | 20.52 |
April | 321.00 | 21.48 | 136.50 | 21.50 | 93.67 | 21.27 |
May | 185.17 | 22.83 | 181.83 | 23.74 | 9.67 | 23.82 |
June | 99.00 | 23.92 | 291.67 | 24.29 | 30.50 | 24.45 |
July | 71.00 | 25.00 | 368.33 | 24.53 | 49.67 | 24.68 |
August | 130.17 | 23.22 | 273.50 | 23.99 | 20.17 | 24.14 |
September | 265.00 | 22.20 | 96.00 | 22.81 | 6.00 | 22.88 |
October | 397.17 | 21.13 | 121.67 | 21.07 | 104.83 | 20.93 |
November | 417.00 | 20.15 | 314.17 | 19.99 | 314.17 | 19.93 |
December | 422.00 | 19.58 | 420.33 | 19.58 | 420.33 | 19.58 |
Annual Sum or Average | 3539.00 | 20.90 | 3272.50 | 21.25 | 2116.17 | 21.00 |
Minimum of Months | 71.00 | 19.57 | 96.00 | 19.57 | 6.00 | 19.57 |
Maximum of Months | 427.00 | 25.00 | 427.00 | 24.53 | 427.00 | 24.68 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 470.67 | 20.17 | 395.00 | 19.98 | 387.83 | 19.89 |
February | 377.67 | 20.70 | 291.83 | 20.59 | 260.83 | 20.41 |
March | 412.50 | 21.27 | 280.17 | 21.27 | 236.83 | 21.12 |
April | 344.33 | 21.81 | 170.33 | 21.96 | 99.83 | 21.76 |
May | 192.67 | 22.76 | 219.33 | 23.61 | 10.67 | 23.64 |
June | 131.83 | 23.27 | 318.17 | 23.99 | 16.83 | 24.07 |
July | 97.67 | 24.56 | 424.33 | 24.44 | 51.00 | 24.58 |
August | 119.83 | 23.70 | 375.83 | 24.18 | 25.83 | 24.32 |
September | 254.50 | 22.90 | 196.00 | 23.64 | 27.33 | 23.83 |
October | 408.00 | 21.79 | 155.33 | 22.02 | 93.17 | 21.94 |
November | 438.17 | 20.71 | 272.50 | 20.57 | 244.17 | 20.39 |
December | 479.33 | 20.19 | 414.50 | 20.03 | 414.50 | 19.97 |
Annual Sum or Average | 3727.17 | 21.40 | 3513.33 | 21.81 | 1868.83 | 21.55 |
Minimum of Months | 97.67 | 20.17 | 155.33 | 19.98 | 10.67 | 19.89 |
Maximum of Months | 479.33 | 24.56 | 424.33 | 24.44 | 414.50 | 24.58 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.88 | 478.33 | 19.83 | 478.33 | 19.82 |
February | 445.33 | 20.31 | 369.50 | 20.18 | 369.50 | 20.14 |
March | 476.33 | 20.83 | 316.00 | 20.72 | 299.67 | 20.62 |
April | 402.67 | 21.60 | 152.33 | 21.61 | 106.00 | 21.44 |
May | 228.33 | 22.78 | 222.50 | 23.60 | 23.50 | 23.68 |
June | 129.83 | 23.13 | 330.50 | 23.98 | 26.50 | 24.06 |
July | 103.33 | 24.65 | 441.17 | 24.48 | 67.00 | 24.61 |
August | 129.67 | 23.36 | 356.17 | 24.05 | 31.33 | 24.16 |
September | 314.17 | 22.33 | 123.50 | 22.91 | 9.67 | 22.99 |
October | 462.00 | 21.30 | 121.67 | 21.29 | 93.17 | 21.16 |
November | 487.50 | 20.43 | 322.83 | 20.25 | 322.83 | 20.17 |
December | 497.00 | 19.89 | 482.00 | 19.87 | 482.00 | 19.86 |
Annual Sum or Average | 4178.17 | 21.09 | 3716.50 | 21.45 | 2309.50 | 21.21 |
Minimum of Months | 103.33 | 19.88 | 121.67 | 19.83 | 9.67 | 19.82 |
Maximum of Months | 502.00 | 24.65 | 482.00 | 24.48 | 482.00 | 24.61 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.50 | 502.00 | 19.50 | 502.00 | 19.50 |
February | 454.00 | 19.73 | 449.83 | 19.73 | 449.83 | 19.72 |
March | 514.00 | 20.21 | 456.67 | 20.14 | 456.67 | 20.12 |
April | 479.17 | 20.98 | 246.00 | 20.64 | 246.00 | 20.47 |
May | 279.00 | 22.43 | 160.33 | 22.85 | 29.50 | 22.70 |
June | 127.50 | 23.12 | 283.83 | 23.88 | 12.67 | 23.93 |
July | 86.33 | 24.28 | 420.50 | 24.31 | 47.33 | 24.43 |
August | 146.00 | 22.77 | 314.17 | 23.68 | 3.67 | 23.68 |
September | 388.83 | 22.14 | 61.33 | 22.27 | 20.83 | 22.22 |
October | 502.00 | 20.67 | 231.33 | 20.38 | 231.33 | 20.23 |
November | 489.00 | 19.88 | 427.83 | 19.80 | 427.83 | 19.76 |
December | 497.00 | 19.55 | 497.00 | 19.55 | 497.00 | 19.55 |
Annual Sum or Average | 4464.83 | 20.66 | 4050.83 | 20.85 | 2924.67 | 20.60 |
Minimum of Months | 86.33 | 19.50 | 61.33 | 19.50 | 3.67 | 19.50 |
Maximum of Months | 514.00 | 24.28 | 502.00 | 24.31 | 502.00 | 24.43 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.69 | 502.00 | 19.69 | 502.00 | 19.69 |
February | 454.00 | 19.88 | 417.83 | 19.83 | 417.83 | 19.81 |
March | 500.50 | 20.58 | 374.83 | 20.39 | 374.83 | 20.32 |
April | 383.33 | 21.22 | 183.33 | 21.02 | 150.17 | 20.77 |
May | 215.50 | 22.45 | 218.00 | 23.42 | 12.33 | 23.41 |
June | 127.17 | 23.55 | 350.50 | 24.10 | 32.67 | 24.25 |
July | 97.33 | 24.43 | 424.83 | 24.38 | 57.67 | 24.53 |
August | 160.67 | 22.93 | 329.83 | 23.84 | 20.33 | 23.96 |
September | 318.83 | 21.90 | 117.50 | 22.44 | 15.67 | 22.42 |
October | 471.00 | 20.74 | 212.83 | 20.55 | 200.67 | 20.38 |
November | 489.00 | 19.94 | 402.67 | 19.82 | 402.67 | 19.78 |
December | 497.00 | 19.69 | 497.00 | 19.69 | 497.00 | 19.69 |
Annual Sum or Average | 4216.33 | 20.76 | 4031.17 | 21.10 | 2683.83 | 20.85 |
Minimum of Months | 97.33 | 19.69 | 117.50 | 19.69 | 12.33 | 19.69 |
Maximum of Months | 502.00 | 24.43 | 502.00 | 24.38 | 502.00 | 24.53 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 478.67 | 19.97 | 412.83 | 19.79 | 410.33 | 19.71 |
February | 398.33 | 20.41 | 315.50 | 20.21 | 295.33 | 20.05 |
March | 425.33 | 20.85 | 329.83 | 20.82 | 291.50 | 20.66 |
April | 361.67 | 21.31 | 220.50 | 21.30 | 161.33 | 21.07 |
May | 221.67 | 22.33 | 216.50 | 23.14 | 26.17 | 23.05 |
June | 154.67 | 22.78 | 298.00 | 23.75 | 19.67 | 23.82 |
July | 119.83 | 24.01 | 396.83 | 24.30 | 54.50 | 24.47 |
August | 160.00 | 23.20 | 340.17 | 23.97 | 25.50 | 24.12 |
September | 292.00 | 22.37 | 182.00 | 23.15 | 30.83 | 23.28 |
October | 424.33 | 21.11 | 228.00 | 21.21 | 169.33 | 21.03 |
November | 452.17 | 20.23 | 328.33 | 20.07 | 311.00 | 19.94 |
December | 486.33 | 19.95 | 442.33 | 19.82 | 442.33 | 19.77 |
Annual Sum or Average | 3975.00 | 21.05 | 3710.83 | 21.40 | 2237.83 | 21.13 |
Minimum of Months | 119.83 | 19.95 | 182.00 | 19.79 | 19.67 | 19.71 |
Maximum of Months | 486.33 | 24.01 | 442.33 | 24.30 | 442.33 | 24.47 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.75 | 484.17 | 19.72 | 484.17 | 19.71 |
February | 445.67 | 20.05 | 386.17 | 19.94 | 386.17 | 19.90 |
March | 482.17 | 20.56 | 366.50 | 20.45 | 352.17 | 20.37 |
April | 411.50 | 21.16 | 215.83 | 21.09 | 172.50 | 20.89 |
May | 254.67 | 22.40 | 217.50 | 23.22 | 36.67 | 23.24 |
June | 165.50 | 22.82 | 310.33 | 23.79 | 31.83 | 23.88 |
July | 133.33 | 24.20 | 412.67 | 24.38 | 74.83 | 24.53 |
August | 182.17 | 23.02 | 319.50 | 23.84 | 34.33 | 23.96 |
September | 356.67 | 22.02 | 107.17 | 22.52 | 13.67 | 22.57 |
October | 463.33 | 20.80 | 192.50 | 20.69 | 167.50 | 20.51 |
November | 489.00 | 20.08 | 375.67 | 19.92 | 375.67 | 19.85 |
December | 497.00 | 19.75 | 492.33 | 19.74 | 492.33 | 19.74 |
Annual Sum or Average | 4383.00 | 20.88 | 3880.33 | 21.17 | 2621.83 | 20.94 |
Minimum of Months | 133.33 | 19.75 | 107.17 | 19.72 | 13.67 | 19.71 |
Maximum of Months | 502.00 | 24.20 | 492.33 | 24.38 | 492.33 | 24.53 |
Report: ComfortReportSimple55Monthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 13.83 | 25.81 | 261.33 | 26.94 | 0.00 | 26.94 |
February | 1.83 | 27.00 | 417.50 | 27.00 | 1.83 | 27.00 |
March | 13.00 | 27.00 | 514.00 | 27.00 | 13.00 | 27.00 |
April | 38.17 | 27.06 | 485.00 | 27.01 | 38.17 | 27.01 |
May | 40.00 | 27.00 | 508.00 | 27.00 | 40.00 | 27.00 |
June | 153.33 | 27.00 | 496.00 | 27.00 | 153.33 | 27.00 |
July | 320.67 | 27.00 | 497.00 | 27.00 | 320.67 | 27.00 |
August | 389.67 | 27.00 | 514.00 | 27.00 | 389.67 | 27.00 |
September | 32.83 | 27.00 | 485.00 | 27.00 | 32.83 | 27.00 |
October | 17.00 | 27.00 | 502.00 | 27.00 | 17.00 | 27.00 |
November | 0.83 | 27.00 | 489.00 | 27.00 | 0.83 | 27.00 |
December | 0.00 | 0.00 | 486.00 | 27.00 | 0.00 | 27.00 |
Annual Sum or Average | 1021.17 | 26.99 | 5654.83 | 27.00 | 1007.33 | 27.00 |
Minimum of Months | 0.00 | 0.00 | 261.33 | 26.94 | 0.00 | 26.94 |
Maximum of Months | 389.67 | 27.06 | 514.00 | 27.01 | 389.67 | 27.01 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 260.50 | 25.30 | 71.00 | 25.52 | 9.50 | 25.42 |
February | 37.50 | 27.00 | 161.33 | 27.00 | 0.00 | 27.00 |
March | 6.50 | 27.00 | 358.00 | 27.00 | 3.00 | 27.00 |
April | 9.33 | 27.05 | 472.83 | 27.00 | 9.33 | 27.00 |
May | 29.17 | 27.00 | 508.00 | 27.00 | 29.17 | 27.00 |
June | 57.83 | 27.00 | 496.00 | 27.00 | 57.83 | 27.00 |
July | 110.50 | 27.00 | 497.00 | 27.00 | 110.50 | 27.00 |
August | 90.67 | 27.00 | 514.00 | 27.00 | 90.67 | 27.00 |
September | 16.00 | 27.00 | 485.00 | 27.00 | 16.00 | 27.00 |
October | 4.33 | 27.00 | 496.83 | 27.00 | 4.33 | 27.00 |
November | 13.00 | 27.00 | 345.00 | 27.00 | 0.00 | 27.00 |
December | 48.67 | 27.00 | 151.50 | 27.00 | 0.00 | 27.00 |
Annual Sum or Average | 684.00 | 26.35 | 4556.50 | 26.91 | 330.33 | 26.90 |
Minimum of Months | 4.33 | 25.30 | 71.00 | 25.52 | 0.00 | 25.42 |
Maximum of Months | 260.50 | 27.05 | 514.00 | 27.00 | 110.50 | 27.00 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 373.00 | 24.53 | 109.33 | 24.35 | 74.83 | 24.07 |
February | 97.17 | 26.95 | 101.67 | 26.97 | 0.00 | 26.97 |
March | 46.83 | 27.00 | 253.50 | 27.00 | 2.00 | 27.00 |
April | 15.17 | 27.02 | 397.67 | 27.00 | 9.83 | 27.00 |
May | 35.00 | 27.00 | 500.83 | 27.00 | 35.00 | 27.00 |
June | 79.67 | 27.00 | 496.00 | 27.00 | 79.67 | 27.00 |
July | 135.67 | 27.00 | 497.00 | 27.00 | 135.67 | 27.00 |
August | 108.33 | 27.00 | 514.00 | 27.00 | 108.33 | 27.00 |
September | 15.83 | 27.00 | 485.00 | 27.00 | 15.83 | 27.00 |
October | 4.17 | 27.00 | 445.00 | 27.00 | 4.17 | 27.00 |
November | 66.83 | 27.00 | 234.17 | 27.00 | 0.00 | 27.00 |
December | 105.83 | 27.00 | 87.00 | 27.00 | 0.00 | 27.00 |
Annual Sum or Average | 1083.50 | 26.14 | 4121.17 | 26.75 | 465.33 | 26.71 |
Minimum of Months | 4.17 | 24.53 | 87.00 | 24.35 | 0.00 | 24.07 |
Maximum of Months | 373.00 | 27.02 | 514.00 | 27.00 | 135.67 | 27.00 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 91.83 | 27.00 | 502.00 | 27.00 | 91.83 | 27.00 |
February | 454.00 | 27.00 | 454.00 | 27.00 | 454.00 | 27.00 |
March | 514.00 | 27.00 | 514.00 | 27.00 | 514.00 | 27.00 |
April | 485.00 | 27.00 | 485.00 | 27.00 | 485.00 | 27.00 |
May | 501.00 | 27.00 | 508.00 | 27.00 | 501.00 | 27.00 |
June | 496.00 | 27.00 | 496.00 | 27.00 | 496.00 | 27.00 |
July | 497.00 | 27.24 | 497.00 | 27.24 | 497.00 | 27.24 |
August | 514.00 | 27.66 | 514.00 | 27.66 | 514.00 | 27.66 |
September | 485.00 | 27.00 | 485.00 | 27.00 | 485.00 | 27.00 |
October | 502.00 | 27.00 | 502.00 | 27.00 | 502.00 | 27.00 |
November | 489.00 | 27.00 | 489.00 | 27.00 | 489.00 | 27.00 |
December | 497.00 | 27.00 | 497.00 | 27.00 | 497.00 | 27.00 |
Annual Sum or Average | 5525.83 | 27.08 | 5943.00 | 27.08 | 5525.83 | 27.08 |
Minimum of Months | 91.83 | 27.00 | 454.00 | 27.00 | 91.83 | 27.00 |
Maximum of Months | 514.00 | 27.66 | 514.00 | 27.66 | 514.00 | 27.66 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 26.94985 | 10.66739 | 0.54926 | 11.55972 |
February | 454.00000 | 27.00000 | 11.54407 | 0.66124 | 14.37928 |
March | 514.00000 | 27.00000 | 15.00966 | 0.76584 | 17.55015 |
April | 485.00000 | 27.00527 | 18.11787 | 0.88037 | 21.48929 |
May | 508.00000 | 27.00027 | 29.09713 | 0.25132 | 6.58291 |
June | 496.00000 | 27.00089 | 34.63409 | 0.36265 | 7.89940 |
July | 497.00000 | 27.00070 | 36.40488 | 0.43695 | 9.09340 |
August | 514.00000 | 27.00036 | 35.73491 | 0.45875 | 9.50564 |
September | 485.00000 | 27.00035 | 32.69510 | 0.25404 | 6.54023 |
October | 502.00000 | 27.00003 | 27.22737 | 0.86910 | 21.06870 |
November | 489.00000 | 27.00002 | 17.97918 | 0.78002 | 18.00152 |
December | 497.00000 | 27.00000 | 11.55039 | 0.69529 | 15.30132 |
Annual Sum or Average | 5943.00000 | 26.99641 | 23.48589 | 0.57943 | 13.22527 |
Minimum of Months | 454.00000 | 26.94985 | 10.66739 | 0.25132 | 6.54023 |
Maximum of Months | 514.00000 | 27.00527 | 36.40488 | 0.88037 | 21.48929 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 26.05126 | 10.62821 | 0.25567 | 8.02655 |
February | 454.00000 | 27.00000 | 11.53159 | 0.50468 | 10.60014 |
March | 514.00000 | 27.00000 | 14.99519 | 0.60817 | 13.07210 |
April | 485.00000 | 27.00184 | 18.10685 | 0.72416 | 16.29693 |
May | 508.00000 | 27.00025 | 29.10420 | 0.17194 | 6.03774 |
June | 496.00000 | 27.00092 | 34.66673 | 0.26818 | 6.77232 |
July | 497.00000 | 27.00078 | 36.42444 | 0.33242 | 7.48189 |
August | 514.00000 | 27.00040 | 35.74470 | 0.31392 | 7.26311 |
September | 485.00000 | 27.00024 | 32.75730 | 0.15086 | 5.76319 |
October | 502.00000 | 27.00003 | 27.21366 | 0.74203 | 16.79594 |
November | 489.00000 | 27.00002 | 17.95231 | 0.60042 | 12.85888 |
December | 497.00000 | 27.00000 | 11.53331 | 0.48708 | 10.18218 |
Annual Sum or Average | 5943.00000 | 26.92023 | 23.48556 | 0.42900 | 10.08213 |
Minimum of Months | 454.00000 | 26.05126 | 10.62821 | 0.15086 | 5.76319 |
Maximum of Months | 514.00000 | 27.00184 | 36.42444 | 0.74203 | 16.79594 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 25.11608 | 10.67951 | 0.03070 | 8.39036 |
February | 454.00000 | 26.98830 | 11.53580 | 0.44266 | 9.52631 |
March | 514.00000 | 27.00000 | 15.00031 | 0.54348 | 11.62853 |
April | 485.00000 | 27.00093 | 18.11205 | 0.66752 | 14.81830 |
May | 508.00000 | 26.99941 | 29.11078 | 0.14153 | 6.11180 |
June | 496.00000 | 27.00091 | 34.68707 | 0.25623 | 6.82076 |
July | 497.00000 | 27.00077 | 36.43722 | 0.32643 | 7.53114 |
August | 514.00000 | 27.00042 | 35.76233 | 0.29815 | 7.18397 |
September | 485.00000 | 27.00036 | 32.81595 | 0.10263 | 5.67930 |
October | 502.00000 | 27.00003 | 27.22829 | 0.67533 | 14.93055 |
November | 489.00000 | 27.00002 | 17.96544 | 0.52943 | 11.30143 |
December | 497.00000 | 27.00000 | 11.53931 | 0.42836 | 9.15944 |
Annual Sum or Average | 5943.00000 | 26.84021 | 23.50354 | 0.36926 | 9.41486 |
Minimum of Months | 454.00000 | 25.11608 | 10.67951 | 0.03070 | 5.67930 |
Maximum of Months | 514.00000 | 27.00093 | 36.43722 | 0.67533 | 14.93055 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 26.99997 | 30.00034 | 0.97616 | 25.18054 |
February | 454.00000 | 27.00036 | 29.75749 | 1.17760 | 34.17704 |
March | 514.00000 | 27.00014 | 25.55138 | 1.30532 | 40.55384 |
April | 485.00000 | 27.00020 | 21.27550 | 1.42868 | 47.05400 |
May | 508.00000 | 27.00022 | 31.73179 | 0.52447 | 10.84916 |
June | 496.00000 | 27.00184 | 39.23939 | 0.81597 | 19.19682 |
July | 497.00000 | 27.23769 | 41.66387 | 1.11816 | 31.72684 |
August | 514.00000 | 27.66315 | 36.82926 | 1.39608 | 44.92075 |
September | 485.00000 | 26.99998 | 33.77335 | 0.57520 | 12.10490 |
October | 502.00000 | 27.00029 | 30.06060 | 1.24652 | 37.56127 |
November | 489.00000 | 27.00029 | 25.82048 | 1.33152 | 41.91391 |
December | 497.00000 | 27.00017 | 22.31571 | 1.40175 | 45.61266 |
Annual Sum or Average | 5943.00000 | 27.07752 | 30.69651 | 1.10811 | 32.57705 |
Minimum of Months | 454.00000 | 26.99997 | 21.27550 | 0.52447 | 10.84916 |
Maximum of Months | 514.00000 | 27.66315 | 41.66387 | 1.42868 | 47.05400 |
Report: OccupantComfortDataSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.76965 | 12.81587 | 0.08508 | 6.02357 |
February | 454.00000 | 24.27563 | 11.89847 | 0.21648 | 6.26380 |
March | 514.00000 | 24.33599 | 14.50132 | 0.26194 | 6.63380 |
April | 485.00000 | 24.47124 | 16.41914 | 0.31896 | 7.55382 |
May | 508.00000 | 24.48870 | 31.73958 | -0.4102 | 9.50538 |
June | 496.00000 | 24.46119 | 46.78689 | -0.2981 | 7.93112 |
July | 497.00000 | 24.63084 | 54.76131 | -0.1818 | 7.22075 |
August | 514.00000 | 24.49054 | 52.52813 | -0.2315 | 7.10362 |
September | 485.00000 | 24.54816 | 36.76986 | -0.3434 | 8.71564 |
October | 502.00000 | 24.56605 | 26.81257 | 0.42258 | 9.42702 |
November | 489.00000 | 24.51699 | 17.15355 | 0.32937 | 7.70041 |
December | 497.00000 | 24.27447 | 11.98251 | 0.22088 | 6.41290 |
Annual Sum or Average | 5943.00000 | 24.40260 | 28.00521 | 0.03050 | 7.54765 |
Minimum of Months | 454.00000 | 23.76965 | 11.89847 | -0.4102 | 6.02357 |
Maximum of Months | 514.00000 | 24.63084 | 54.76131 | 0.42258 | 9.50538 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.22927 | 13.04570 | -0.0505 | 6.18055 |
February | 454.00000 | 23.88757 | 13.69619 | 0.13186 | 5.62948 |
March | 514.00000 | 24.10650 | 16.20006 | 0.22516 | 6.22616 |
April | 485.00000 | 24.30698 | 17.73660 | 0.30865 | 7.23366 |
May | 508.00000 | 24.27545 | 32.23102 | -0.4516 | 9.90187 |
June | 496.00000 | 24.24958 | 45.24740 | -0.3459 | 7.94062 |
July | 497.00000 | 24.29649 | 51.75802 | -0.2741 | 6.92026 |
August | 514.00000 | 24.24843 | 51.05847 | -0.2885 | 7.02900 |
September | 485.00000 | 24.29641 | 38.19297 | -0.4082 | 9.08259 |
October | 502.00000 | 24.30014 | 28.63593 | 0.37149 | 8.15078 |
November | 489.00000 | 24.25723 | 19.38348 | 0.27723 | 6.87070 |
December | 497.00000 | 23.97779 | 13.84027 | 0.15175 | 5.74508 |
Annual Sum or Average | 5943.00000 | 24.12008 | 28.56064 | -0.0313 | 7.25219 |
Minimum of Months | 454.00000 | 23.22927 | 13.04570 | -0.4516 | 5.62948 |
Maximum of Months | 514.00000 | 24.30698 | 51.75802 | 0.37149 | 9.90187 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.34353 | 13.92771 | -0.5251 | 13.08623 |
February | 454.00000 | 22.04288 | 15.65217 | -0.3347 | 8.96426 |
March | 514.00000 | 22.88789 | 18.65228 | -0.0974 | 6.44516 |
April | 485.00000 | 23.64459 | 19.72713 | 0.11308 | 5.72935 |
May | 508.00000 | 24.12282 | 32.93147 | -0.5365 | 11.89923 |
June | 496.00000 | 24.13040 | 46.02357 | -0.4229 | 9.16248 |
July | 497.00000 | 24.24527 | 52.55105 | -0.3351 | 7.71098 |
August | 514.00000 | 24.13430 | 52.28543 | -0.3770 | 8.31659 |
September | 485.00000 | 24.03630 | 39.29679 | -0.5299 | 11.42102 |
October | 502.00000 | 23.58934 | 31.12505 | 0.17295 | 6.12562 |
November | 489.00000 | 22.80829 | 22.29895 | -0.1018 | 6.81485 |
December | 497.00000 | 21.61287 | 15.81333 | -0.4416 | 10.96389 |
Annual Sum or Average | 5943.00000 | 23.22501 | 30.16142 | -0.2849 | 8.88825 |
Minimum of Months | 454.00000 | 21.34353 | 13.92771 | -0.5365 | 5.72935 |
Maximum of Months | 514.00000 | 24.24527 | 52.55105 | 0.17295 | 13.08623 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.45599 | 14.40147 | -0.7750 | 20.73096 |
February | 454.00000 | 20.88716 | 16.26685 | -0.6423 | 16.67542 |
March | 514.00000 | 21.62003 | 20.07724 | -0.4226 | 11.44611 |
April | 485.00000 | 22.62349 | 21.23912 | -0.1444 | 7.69234 |
May | 508.00000 | 23.82090 | 33.50133 | -0.6473 | 15.90350 |
June | 496.00000 | 23.97227 | 46.66357 | -0.4723 | 10.57690 |
July | 497.00000 | 24.16323 | 52.93040 | -0.3585 | 8.28901 |
August | 514.00000 | 24.01838 | 52.97038 | -0.4184 | 9.20219 |
September | 485.00000 | 23.59232 | 40.83273 | -0.6974 | 16.54549 |
October | 502.00000 | 22.35580 | 33.79040 | -0.1384 | 7.69686 |
November | 489.00000 | 21.32793 | 23.88928 | -0.4749 | 13.37792 |
December | 497.00000 | 20.54239 | 16.35553 | -0.7354 | 19.53800 |
Annual Sum or Average | 5943.00000 | 22.46111 | 31.21480 | -0.4930 | 13.10902 |
Minimum of Months | 454.00000 | 20.45599 | 14.40147 | -0.7750 | 7.69234 |
Maximum of Months | 514.00000 | 24.16323 | 52.97038 | -0.1384 | 20.73096 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.36533 | 13.33353 | -0.8157 | 20.73261 |
February | 454.00000 | 20.99022 | 14.59665 | -0.6038 | 13.96389 |
March | 514.00000 | 21.79115 | 17.53575 | -0.3654 | 9.47167 |
April | 485.00000 | 23.21914 | 18.31831 | 0.01064 | 6.17318 |
May | 508.00000 | 24.06143 | 31.75084 | -0.5321 | 12.37363 |
June | 496.00000 | 24.25227 | 44.42801 | -0.3215 | 7.91028 |
July | 497.00000 | 24.38596 | 50.93750 | -0.2145 | 6.82256 |
August | 514.00000 | 24.21027 | 50.59722 | -0.3117 | 7.57339 |
September | 485.00000 | 23.84632 | 38.55861 | -0.6010 | 13.91179 |
October | 502.00000 | 23.07312 | 29.34975 | 0.03412 | 5.97605 |
November | 489.00000 | 21.90816 | 20.77997 | -0.3134 | 8.80015 |
December | 497.00000 | 20.61060 | 14.92448 | -0.6988 | 17.09930 |
Annual Sum or Average | 5943.00000 | 22.73866 | 28.89451 | -0.3934 | 10.87859 |
Minimum of Months | 454.00000 | 20.36533 | 13.33353 | -0.8157 | 5.97605 |
Maximum of Months | 514.00000 | 24.38596 | 50.93750 | 0.03412 | 20.73261 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.36630 | 12.40996 | -0.8026 | 20.27744 |
February | 454.00000 | 21.12923 | 13.62270 | -0.5510 | 13.01622 |
March | 514.00000 | 21.86311 | 16.54237 | -0.3134 | 9.62954 |
April | 485.00000 | 22.99672 | 17.84748 | 0.03681 | 7.63829 |
May | 508.00000 | 24.00998 | 31.53870 | -0.4457 | 12.06910 |
June | 496.00000 | 24.14597 | 44.53369 | -0.2449 | 8.66876 |
July | 497.00000 | 24.19521 | 51.18152 | -0.1633 | 7.39789 |
August | 514.00000 | 23.95367 | 51.21001 | -0.3135 | 9.53924 |
September | 485.00000 | 23.55641 | 38.78256 | -0.6044 | 16.09325 |
October | 502.00000 | 22.52179 | 29.35500 | -0.0538 | 6.98314 |
November | 489.00000 | 21.44460 | 20.43827 | -0.4045 | 9.94061 |
December | 497.00000 | 20.50207 | 14.16450 | -0.7304 | 17.73896 |
Annual Sum or Average | 5943.00000 | 22.56857 | 28.60889 | -0.3815 | 11.56680 |
Minimum of Months | 454.00000 | 20.36630 | 12.40996 | -0.8026 | 6.98314 |
Maximum of Months | 514.00000 | 24.19521 | 51.21001 | 0.03681 | 20.27744 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.00478 | 12.24551 | -0.6060 | 17.31664 |
February | 454.00000 | 21.96581 | 13.04039 | -0.3101 | 12.15827 |
March | 514.00000 | 22.38742 | 16.10737 | -0.1678 | 10.19154 |
April | 485.00000 | 23.17188 | 17.62694 | 0.07806 | 8.32969 |
May | 508.00000 | 23.94058 | 31.61966 | -0.4933 | 13.22385 |
June | 496.00000 | 24.09991 | 44.66736 | -0.3214 | 9.00635 |
July | 497.00000 | 24.29373 | 50.94074 | -0.1740 | 7.41387 |
August | 514.00000 | 24.18065 | 50.45320 | -0.2244 | 8.30055 |
September | 485.00000 | 23.85313 | 38.08303 | -0.4803 | 14.39585 |
October | 502.00000 | 22.95663 | 28.64902 | 0.06665 | 8.62482 |
November | 489.00000 | 21.98648 | 19.96134 | -0.2610 | 10.11000 |
December | 497.00000 | 21.09818 | 14.06386 | -0.5620 | 15.27631 |
Annual Sum or Average | 5943.00000 | 22.91953 | 28.26300 | -0.2880 | 11.18542 |
Minimum of Months | 454.00000 | 21.00478 | 12.24551 | -0.6060 | 7.41387 |
Maximum of Months | 514.00000 | 24.29373 | 50.94074 | 0.07806 | 17.31664 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.75930 | 11.95434 | -0.6682 | 16.20414 |
February | 454.00000 | 21.80680 | 12.83823 | -0.3447 | 9.80665 |
March | 514.00000 | 22.78029 | 15.42925 | -0.0449 | 7.54340 |
April | 485.00000 | 24.05570 | 16.53363 | 0.33476 | 8.90278 |
May | 508.00000 | 24.18399 | 31.03009 | -0.3283 | 10.25647 |
June | 496.00000 | 24.37860 | 43.78225 | -0.1110 | 7.06153 |
July | 497.00000 | 24.58440 | 49.93643 | 0.05845 | 7.37335 |
August | 514.00000 | 24.46859 | 49.39649 | -0.0052 | 7.03877 |
September | 485.00000 | 23.95808 | 37.67464 | -0.4289 | 11.86824 |
October | 502.00000 | 23.44977 | 27.58172 | 0.19813 | 7.22295 |
November | 489.00000 | 22.72453 | 18.82741 | -0.0657 | 6.67953 |
December | 497.00000 | 21.56627 | 13.18548 | -0.4046 | 10.10562 |
Annual Sum or Average | 5943.00000 | 23.23612 | 27.48521 | -0.1497 | 9.16169 |
Minimum of Months | 454.00000 | 20.75930 | 11.95434 | -0.6682 | 6.67953 |
Maximum of Months | 514.00000 | 24.58440 | 49.93643 | 0.33476 | 16.20414 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.64848 | 13.02735 | -1.0962 | 32.42080 |
February | 454.00000 | 19.92778 | 15.26002 | -0.9568 | 26.59945 |
March | 514.00000 | 20.51864 | 19.02476 | -0.7374 | 18.59627 |
April | 485.00000 | 21.62735 | 20.42451 | -0.3864 | 10.66676 |
May | 508.00000 | 23.62491 | 32.57602 | -0.7003 | 18.26181 |
June | 496.00000 | 24.07237 | 45.18499 | -0.4111 | 9.60224 |
July | 497.00000 | 24.29023 | 52.06912 | -0.2775 | 7.64184 |
August | 514.00000 | 23.92454 | 52.18282 | -0.4473 | 10.10680 |
September | 485.00000 | 23.11420 | 40.61065 | -0.8641 | 23.08086 |
October | 502.00000 | 21.40698 | 32.05976 | -0.3756 | 9.78398 |
November | 489.00000 | 20.22798 | 22.83100 | -0.7750 | 20.56503 |
December | 497.00000 | 19.70901 | 15.17475 | -1.0504 | 30.58076 |
Annual Sum or Average | 5943.00000 | 21.85781 | 30.17154 | -0.6709 | 18.08457 |
Minimum of Months | 454.00000 | 19.64848 | 13.02735 | -1.0962 | 7.64184 |
Maximum of Months | 514.00000 | 24.29023 | 52.18282 | -0.2775 | 32.42080 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 427.00000 | 19.56808 | 12.16981 | -1.0914 | 32.41911 |
February | 385.00000 | 19.93312 | 14.16848 | -0.9164 | 25.21791 |
March | 433.00000 | 20.89613 | 17.36897 | -0.6093 | 15.76983 |
April | 410.00000 | 22.10705 | 18.71553 | -0.2066 | 10.30468 |
May | 430.00000 | 23.70495 | 31.69017 | -0.5702 | 16.79046 |
June | 418.00000 | 24.05365 | 44.92027 | -0.2943 | 10.56133 |
July | 422.00000 | 24.27959 | 51.62509 | -0.1580 | 8.33029 |
August | 433.00000 | 23.78917 | 52.05819 | -0.3906 | 12.16821 |
September | 410.00000 | 22.88557 | 40.29654 | -0.8479 | 25.07623 |
October | 427.00000 | 21.36972 | 30.62516 | -0.3628 | 10.47472 |
November | 417.00000 | 20.14970 | 21.46584 | -0.7832 | 20.76875 |
December | 422.00000 | 19.58369 | 14.22766 | -1.0639 | 31.30024 |
Annual Sum or Average | 5034.00000 | 21.87340 | 29.22721 | -0.6058 | 18.20562 |
Minimum of Months | 385.00000 | 19.56808 | 12.16981 | -1.0914 | 8.33029 |
Maximum of Months | 433.00000 | 24.27959 | 52.05819 | -0.1580 | 32.41911 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.40506 | 12.20629 | -0.7948 | 24.24412 |
February | 454.00000 | 21.28837 | 13.60413 | -0.5012 | 17.41410 |
March | 514.00000 | 21.85592 | 17.03802 | -0.3217 | 13.51897 |
April | 485.00000 | 22.51119 | 18.57119 | -0.0882 | 10.36129 |
May | 508.00000 | 23.68119 | 32.06530 | -0.5835 | 16.65998 |
June | 496.00000 | 23.89901 | 45.36945 | -0.3997 | 11.19591 |
July | 497.00000 | 24.22085 | 51.87684 | -0.2124 | 8.46696 |
August | 514.00000 | 23.97692 | 51.61494 | -0.3083 | 10.43871 |
September | 485.00000 | 23.49476 | 39.00604 | -0.5968 | 19.11995 |
October | 502.00000 | 22.24524 | 29.70044 | -0.1076 | 10.57983 |
November | 489.00000 | 21.07951 | 21.29194 | -0.5075 | 15.83424 |
December | 497.00000 | 20.32386 | 14.41309 | -0.8171 | 23.63661 |
Annual Sum or Average | 5943.00000 | 22.42586 | 29.03858 | -0.4360 | 15.09593 |
Minimum of Months | 454.00000 | 20.32386 | 12.20629 | -0.8171 | 8.46696 |
Maximum of Months | 514.00000 | 24.22085 | 51.87684 | -0.0882 | 24.24412 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.87796 | 12.24309 | -0.9986 | 28.64580 |
February | 454.00000 | 20.37915 | 14.07946 | -0.7907 | 21.34401 |
March | 514.00000 | 21.07261 | 17.54961 | -0.5426 | 15.01383 |
April | 485.00000 | 22.02781 | 19.03552 | -0.2094 | 10.29713 |
May | 508.00000 | 23.59090 | 32.08501 | -0.5687 | 17.42627 |
June | 496.00000 | 23.88741 | 45.38130 | -0.3429 | 10.96160 |
July | 497.00000 | 24.28103 | 51.66457 | -0.1374 | 8.50390 |
August | 514.00000 | 23.85504 | 51.93734 | -0.3324 | 10.99566 |
September | 485.00000 | 22.94116 | 40.19594 | -0.8066 | 23.70118 |
October | 502.00000 | 21.52998 | 30.74703 | -0.2984 | 9.45622 |
November | 489.00000 | 20.44248 | 21.76379 | -0.6914 | 17.76699 |
December | 497.00000 | 19.88951 | 14.33624 | -0.9662 | 27.10374 |
Annual Sum or Average | 5943.00000 | 21.99615 | 29.39086 | -0.5550 | 16.71714 |
Minimum of Months | 454.00000 | 19.87796 | 12.24309 | -0.9986 | 8.50390 |
Maximum of Months | 514.00000 | 24.28103 | 51.93734 | -0.1374 | 28.64580 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.50104 | 12.79074 | -1.1857 | 36.32638 |
February | 454.00000 | 19.73201 | 15.12539 | -1.0605 | 31.12001 |
March | 514.00000 | 20.21320 | 19.51343 | -0.8625 | 23.17437 |
April | 485.00000 | 21.01279 | 21.37675 | -0.5584 | 15.18712 |
May | 508.00000 | 23.21440 | 33.10878 | -0.8413 | 24.37152 |
June | 496.00000 | 23.85475 | 45.88772 | -0.4795 | 12.04321 |
July | 497.00000 | 24.15006 | 52.63146 | -0.3191 | 8.84892 |
August | 514.00000 | 23.68641 | 53.09438 | -0.5247 | 12.60442 |
September | 485.00000 | 22.49978 | 42.12052 | -1.0781 | 32.31335 |
October | 502.00000 | 20.66728 | 33.97157 | -0.5825 | 15.10018 |
November | 489.00000 | 19.88069 | 23.59562 | -0.9138 | 25.95602 |
December | 497.00000 | 19.54980 | 14.96223 | -1.1475 | 34.61850 |
Annual Sum or Average | 5943.00000 | 21.51375 | 30.82115 | -0.7937 | 22.55134 |
Minimum of Months | 454.00000 | 19.50104 | 12.79074 | -1.1857 | 8.84892 |
Maximum of Months | 514.00000 | 24.15006 | 53.09438 | -0.3191 | 36.32638 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.69071 | 12.38138 | -1.1149 | 33.27735 |
February | 454.00000 | 19.88441 | 14.57850 | -0.9729 | 27.82358 |
March | 514.00000 | 20.67077 | 18.44939 | -0.6971 | 18.78548 |
April | 485.00000 | 21.81652 | 19.79827 | -0.2921 | 12.46393 |
May | 508.00000 | 23.50777 | 32.30170 | -0.6276 | 18.67809 |
June | 496.00000 | 23.91953 | 45.37556 | -0.3169 | 11.21778 |
July | 497.00000 | 24.15672 | 52.00159 | -0.1683 | 8.86982 |
August | 514.00000 | 23.67929 | 52.71693 | -0.4096 | 12.86289 |
September | 485.00000 | 22.64219 | 41.19768 | -0.9370 | 28.66787 |
October | 502.00000 | 20.95668 | 32.64986 | -0.4900 | 13.89372 |
November | 489.00000 | 19.93998 | 22.97204 | -0.8789 | 24.71631 |
December | 497.00000 | 19.69037 | 14.52751 | -1.0984 | 32.55995 |
Annual Sum or Average | 5943.00000 | 21.72970 | 30.05227 | -0.6642 | 20.23512 |
Minimum of Months | 454.00000 | 19.69037 | 12.38138 | -1.1149 | 8.86982 |
Maximum of Months | 514.00000 | 24.15672 | 52.71693 | -0.1683 | 33.27735 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.15562 | 12.26986 | -0.9043 | 28.06483 |
February | 454.00000 | 20.85340 | 13.90427 | -0.6485 | 21.75902 |
March | 514.00000 | 21.45054 | 17.78581 | -0.4647 | 16.60058 |
April | 485.00000 | 22.03242 | 19.56417 | -0.2317 | 13.01737 |
May | 508.00000 | 23.39521 | 32.47551 | -0.6895 | 20.91043 |
June | 496.00000 | 23.68185 | 46.08283 | -0.4673 | 13.90742 |
July | 497.00000 | 24.07155 | 52.49787 | -0.2559 | 9.98993 |
August | 514.00000 | 23.78458 | 52.39352 | -0.3721 | 12.53102 |
September | 485.00000 | 23.08729 | 40.14459 | -0.7517 | 25.06175 |
October | 502.00000 | 21.60736 | 31.52861 | -0.2922 | 13.94777 |
November | 489.00000 | 20.51390 | 22.42386 | -0.6854 | 20.90413 |
December | 497.00000 | 20.04119 | 14.51459 | -0.9387 | 28.03450 |
Annual Sum or Average | 5943.00000 | 22.06843 | 29.77543 | -0.5575 | 18.68615 |
Minimum of Months | 454.00000 | 20.04119 | 12.26986 | -0.9387 | 9.98993 |
Maximum of Months | 514.00000 | 24.07155 | 52.49787 | -0.2317 | 28.06483 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.74996 | 12.25544 | -1.0821 | 32.11394 |
February | 454.00000 | 20.11775 | 14.27778 | -0.8950 | 25.57018 |
March | 514.00000 | 20.78146 | 18.23494 | -0.6537 | 18.45653 |
April | 485.00000 | 21.60581 | 19.94940 | -0.3350 | 13.20765 |
May | 508.00000 | 23.30791 | 32.48611 | -0.6697 | 21.67354 |
June | 496.00000 | 23.69058 | 46.02080 | -0.4033 | 13.34698 |
July | 497.00000 | 24.14838 | 52.22084 | -0.1757 | 9.73080 |
August | 514.00000 | 23.65972 | 52.71508 | -0.3961 | 13.06776 |
September | 485.00000 | 22.55866 | 41.25093 | -0.9502 | 29.74871 |
October | 502.00000 | 21.05845 | 32.40857 | -0.4411 | 12.91892 |
November | 489.00000 | 20.07936 | 22.72688 | -0.8195 | 22.68953 |
December | 497.00000 | 19.74675 | 14.40679 | -1.0510 | 30.68064 |
Annual Sum or Average | 5943.00000 | 21.72429 | 30.05394 | -0.6536 | 20.20236 |
Minimum of Months | 454.00000 | 19.74675 | 12.25544 | -1.0821 | 9.73080 |
Maximum of Months | 514.00000 | 24.14838 | 52.71508 | -0.1757 | 32.11394 |
Report: ChillerReportMonthly
For: COOLSYS1 CHILLER1
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportCHILLER ELECTRICITY ENERGY [J] | CHILLER ELECTRICITY RATE {Maximum} [W] | CHILLER ELECTRICITY RATE {TIMESTAMP} | CHILLER ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | CHILLER EVAPORATOR COOLING ENERGY [J] | CHILLER EVAPORATOR COOLING RATE [] | CHILLER CONDENSER HEAT TRANSFER ENERGY [J] | CHILLER COP [W/W] | CHILLER COP {Maximum} [W/W] | CHILLER COP {TIMESTAMP} | CHILLER PART LOAD RATIO [] | CHILLER PART LOAD RATIO [] | |
January | 0.687105E+09 | 1564.39 | 31-JAN-19:00 | 138.69 | 0.294138E+10 | 0.00 | 0.362848E+10 | 0.80 | 4.29 | 13-JAN-01:00 | 0.00 | 0.00 |
February | 0.754279E+09 | 2678.92 | 11-FEB-13:30 | 149.05 | 0.322891E+10 | 0.00 | 0.398318E+10 | 0.95 | 4.29 | 17-FEB-17:50 | 0.00 | 0.00 |
March | 0.785056E+09 | 8741.40 | 29-MAR-11:30 | 144.09 | 0.336077E+10 | 0.00 | 0.414583E+10 | 0.83 | 4.29 | 16-MAR-18:40 | 0.00 | 0.00 |
April | 0.943524E+10 | 104573.75 | 23-APR-15:13 | 110.80 | 0.502174E+11 | 0.00 | 0.596527E+11 | 0.71 | 7.24 | 23-APR-15:13 | 0.00 | 0.00 |
May | 0.612525E+11 | 186303.26 | 17-MAY-11:40 | 247.03 | 0.397123E+12 | 0.00 | 0.458376E+12 | 1.90 | 7.57 | 10-MAY-15:30 | 0.00 | 0.00 |
June | 0.124437E+12 | 193375.84 | 29-JUN-17:10 | 395.29 | 0.835619E+12 | 0.00 | 0.960056E+12 | 3.39 | 7.57 | 08-JUN-11:50 | 0.00 | 0.00 |
July | 0.154122E+12 | 205631.96 | 05-JUL-10:15 | 500.73 | 0.104386E+13 | 0.00 | 0.119798E+13 | 4.11 | 7.75 | 05-JUL-14:50 | 0.00 | 0.00 |
August | 0.121960E+12 | 193556.94 | 08-AUG-16:40 | 481.03 | 0.800769E+12 | 0.00 | 0.922729E+12 | 3.74 | 7.56 | 04-AUG-14:10 | 0.00 | 0.00 |
September | 0.352208E+11 | 184532.91 | 07-SEP-15:00 | 196.02 | 0.207747E+12 | 0.00 | 0.242968E+12 | 1.40 | 7.56 | 07-SEP-13:30 | 0.00 | 0.00 |
October | 0.737925E+10 | 118505.20 | 19-OCT-15:00 | 101.85 | 0.417374E+11 | 0.00 | 0.491167E+11 | 0.63 | 7.41 | 19-OCT-15:00 | 0.00 | 0.00 |
November | 0.129963E+10 | 49272.59 | 01-NOV-15:00 | 98.83 | 0.554402E+10 | 0.00 | 0.684365E+10 | 0.59 | 4.29 | 28-NOV-18:10 | 0.00 | 0.00 |
December | 0.783209E+09 | 4435.88 | 18-DEC-16:30 | 156.02 | 0.335300E+10 | 0.00 | 0.413621E+10 | 0.90 | 4.29 | 16-DEC-08:50 | 0.00 | 0.00 |
Annual Sum or Average | 0.518116E+12 | 2719.42 | 0.339550E+13 | 0.00 | 0.391362E+13 | 1.67 | 0.00 | 0.00 | ||||
Minimum of Months | 0.687105E+09 | 1564.39 | 98.83 | 0.294138E+10 | 0.00 | 0.362848E+10 | 0.59 | 4.29 | 0.00 | 0.00 | ||
Maximum of Months | 0.154122E+12 | 205631.96 | 500.73 | 0.104386E+13 | 0.00 | 0.119798E+13 | 4.11 | 7.75 | 0.00 | 0.00 |
Report: ChillerReportMonthly
For: COOLSYS1 CHILLER2
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportCHILLER ELECTRICITY ENERGY [J] | CHILLER ELECTRICITY RATE {Maximum} [W] | CHILLER ELECTRICITY RATE {TIMESTAMP} | CHILLER ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | CHILLER EVAPORATOR COOLING ENERGY [J] | CHILLER EVAPORATOR COOLING RATE [] | CHILLER CONDENSER HEAT TRANSFER ENERGY [J] | CHILLER COP [W/W] | CHILLER COP {Maximum} [W/W] | CHILLER COP {TIMESTAMP} | CHILLER PART LOAD RATIO [] | CHILLER PART LOAD RATIO [] | |
January | 0.00 | 0.00 | 01-JAN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 |
May | 0.872826E+10 | 119667.44 | 25-MAY-16:00 | 23.67 | 0.619142E+11 | 0.00 | 0.706425E+11 | 0.22 | 7.31 | 17-MAY-13:30 | 0.00 | 0.00 |
June | 0.279928E+11 | 180048.61 | 19-JUN-15:20 | 63.40 | 0.192670E+12 | 0.00 | 0.220663E+12 | 0.60 | 7.33 | 29-JUN-04:15 | 0.00 | 0.00 |
July | 0.436069E+11 | 205631.96 | 05-JUL-10:15 | 99.51 | 0.307599E+12 | 0.00 | 0.351206E+12 | 0.94 | 7.75 | 05-JUL-14:50 | 0.00 | 0.00 |
August | 0.296595E+11 | 185213.82 | 31-AUG-12:50 | 70.33 | 0.208203E+12 | 0.00 | 0.237862E+12 | 0.66 | 7.28 | 22-AUG-14:10 | 0.00 | 0.00 |
September | 0.272982E+10 | 124420.69 | 01-SEP-13:10 | 6.83 | 0.196213E+11 | 0.00 | 0.223511E+11 | 0.07 | 7.26 | 01-SEP-13:10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.112717E+12 | 263.75 | 0.790007E+12 | 0.00 | 0.902725E+12 | 0.21 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.436069E+11 | 205631.96 | 99.51 | 0.307599E+12 | 0.00 | 0.351206E+12 | 0.94 | 7.75 | 0.00 | 0.00 |
Report: TowerReportMonthly
For: CENTRAL TOWER
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportCOOLING TOWER FAN ELECTRICITY ENERGY [J] | COOLING TOWER FAN ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | COOLING TOWER FAN ELECTRICITY RATE {Maximum} [W] | COOLING TOWER FAN ELECTRICITY RATE {TIMESTAMP} | COOLING TOWER HEAT TRANSFER RATE {Maximum} [W] | COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} | COOLING TOWER INLET TEMPERATURE [C] | COOLING TOWER OUTLET TEMPERATURE [C] | COOLING TOWER MASS FLOW RATE [kg/s] | |
January | 0.337799E+09 | 744.00 | 817.45 | 20-JAN-15:10 | 43744.20 | 20-JAN-15:10 | 18.51 | 18.33 | 14.51 |
February | 0.167410E+10 | 672.00 | 4088.38 | 08-FEB-11:05 | 189387.86 | 08-FEB-11:05 | 19.18 | 18.33 | 14.39 |
March | 0.407780E+10 | 744.00 | 5720.47 | 27-MAR-14:15 | 243459.25 | 22-MAR-14:47 | 20.00 | 18.33 | 14.26 |
April | 0.192118E+11 | 720.00 | 49248.27 | 11-APR-13:25 | 666460.08 | 23-APR-16:01 | 21.46 | 18.59 | 14.19 |
May | 0.410146E+11 | 744.00 | 49248.27 | 02-MAY-14:40 | 254073.54 | 25-MAY-13:10 | 20.49 | 19.52 | 14.44 |
June | 0.779255E+11 | 720.00 | 49248.27 | 01-JUN-07:50 | 683968.33 | 30-JUN-02:62 | 24.74 | 21.71 | 14.55 |
July | 0.103821E+12 | 744.00 | 49248.27 | 01-JUL-07:50 | 735878.36 | 15-JUL-14:10 | 31.30 | 24.22 | 14.57 |
August | 0.111500E+12 | 744.00 | 49248.27 | 01-AUG-00:03 | 746911.09 | 08-AUG-15:10 | 32.13 | 23.25 | 14.56 |
September | 0.248866E+11 | 720.00 | 49248.27 | 01-SEP-00:03 | 222324.10 | 01-SEP-15:10 | 19.34 | 18.66 | 14.47 |
October | 0.917075E+10 | 744.00 | 49248.27 | 19-OCT-11:50 | 196484.20 | 19-OCT-15:10 | 19.59 | 18.38 | 14.25 |
November | 0.563363E+10 | 720.00 | 49248.27 | 01-NOV-11:50 | 277064.62 | 10-NOV-12:22 | 19.98 | 18.34 | 14.24 |
December | 0.347056E+10 | 744.00 | 3102.41 | 28-DEC-11:30 | 191016.77 | 20-DEC-11:50 | 20.19 | 18.33 | 14.52 |
Annual Sum or Average | 0.402724E+12 | 8760.00 | 22.28 | 19.68 | 14.41 | ||||
Minimum of Months | 0.337799E+09 | 672.00 | 817.45 | 43744.20 | 18.51 | 18.33 | 14.19 | ||
Maximum of Months | 0.111500E+12 | 744.00 | 49248.27 | 746911.09 | 32.13 | 24.22 | 14.57 |
Report: TowerReportMonthly
For: TOWERWATERSYS COOLTOWER 1
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportCOOLING TOWER FAN ELECTRICITY ENERGY [J] | COOLING TOWER FAN ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | COOLING TOWER FAN ELECTRICITY RATE {Maximum} [W] | COOLING TOWER FAN ELECTRICITY RATE {TIMESTAMP} | COOLING TOWER HEAT TRANSFER RATE {Maximum} [W] | COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} | COOLING TOWER INLET TEMPERATURE [C] | COOLING TOWER OUTLET TEMPERATURE [C] | COOLING TOWER MASS FLOW RATE [kg/s] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 248328.38 | 23-JAN-11:20 | 20.93 | 20.92 | 0.96 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 248636.22 | 08-FEB-11:00 | 20.95 | 20.94 | 1.31 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 248335.22 | 06-MAR-13:07 | 20.92 | 20.91 | 1.08 |
April | 72521207.81 | 24.31 | 3635.75 | 23-APR-16:15 | 792834.03 | 13-APR-15:20 | 21.03 | 20.94 | 5.13 |
May | 0.434440E+10 | 194.72 | 20018.77 | 16-MAY-12:10 | 1497179.67 | 17-MAY-11:30 | 21.87 | 21.24 | 20.30 |
June | 0.127230E+11 | 361.18 | 20018.77 | 06-JUN-09:40 | 1740107.76 | 20-JUN-04:12 | 23.27 | 21.93 | 35.40 |
July | 0.201006E+11 | 453.98 | 20018.77 | 03-JUL-07:20 | 1598853.45 | 05-JUL-16:00 | 23.72 | 22.12 | 42.86 |
August | 0.132655E+11 | 389.02 | 20018.77 | 01-AUG-05:04 | 1496019.14 | 04-AUG-13:30 | 22.86 | 21.61 | 40.25 |
September | 0.140011E+10 | 143.85 | 20018.77 | 01-SEP-08:20 | 1520371.52 | 07-SEP-15:10 | 21.44 | 21.10 | 16.46 |
October | 63708622.23 | 27.62 | 2935.07 | 19-OCT-15:00 | 1010305.85 | 19-OCT-15:00 | 21.07 | 21.00 | 3.97 |
November | 6118142.71 | 5.33 | 440.31 | 01-NOV-12:10 | 272122.10 | 01-NOV-15:00 | 20.97 | 20.96 | 1.34 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 248293.64 | 12-DEC-21:20 | 20.98 | 20.96 | 1.21 |
Annual Sum or Average | 0.519760E+11 | 1600.02 | 21.67 | 21.22 | 14.29 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 248293.64 | 20.92 | 20.91 | 0.96 | ||
Maximum of Months | 0.201006E+11 | 453.98 | 20018.77 | 1740107.76 | 23.72 | 22.12 | 42.86 |
Report: TowerReportMonthly
For: TOWERWATERSYS COOLTOWER 2
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportCOOLING TOWER FAN ELECTRICITY ENERGY [J] | COOLING TOWER FAN ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | COOLING TOWER FAN ELECTRICITY RATE {Maximum} [W] | COOLING TOWER FAN ELECTRICITY RATE {TIMESTAMP} | COOLING TOWER HEAT TRANSFER RATE {Maximum} [W] | COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} | COOLING TOWER INLET TEMPERATURE [C] | COOLING TOWER OUTLET TEMPERATURE [C] | COOLING TOWER MASS FLOW RATE [kg/s] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 20.93 | 20.93 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 20.95 | 20.95 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 20.92 | 20.92 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 21.03 | 21.03 | 0.00 |
May | 0.138392E+10 | 19.50 | 20018.77 | 16-MAY-12:40 | 1204818.77 | 16-MAY-16:00 | 21.87 | 21.77 | 1.75 |
June | 0.551395E+10 | 77.97 | 20018.77 | 06-JUN-12:20 | 1415831.03 | 19-JUN-15:20 | 23.27 | 22.86 | 6.55 |
July | 0.934847E+10 | 130.01 | 20018.77 | 03-JUL-12:20 | 1598853.45 | 05-JUL-16:00 | 23.72 | 23.06 | 10.41 |
August | 0.582546E+10 | 80.83 | 20018.77 | 04-AUG-13:40 | 1421701.27 | 31-AUG-12:50 | 22.86 | 22.46 | 6.92 |
September | 0.480450E+09 | 6.67 | 20018.77 | 01-SEP-09:20 | 1040821.25 | 01-SEP-13:10 | 21.44 | 21.41 | 0.63 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 21.07 | 21.07 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 20.97 | 20.97 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 20.98 | 20.98 | 0.00 |
Annual Sum or Average | 0.225522E+11 | 314.98 | 21.67 | 21.54 | 2.21 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 20.92 | 20.92 | 0.00 | ||
Maximum of Months | 0.934847E+10 | 130.01 | 20018.77 | 1598853.45 | 23.72 | 23.06 | 10.41 |
Report: BoilerReportMonthly
For: HEATSYS1 BOILER
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportBOILER HEATING ENERGY [J] | BOILER GAS CONSUMPTION [] | BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] | BOILER HEATING RATE {Maximum} [W] | BOILER HEATING RATE {TIMESTAMP} | BOILER GAS CONSUMPTION RATE [] | BOILER INLET TEMPERATURE [C] | BOILER OUTLET TEMPERATURE [C] | BOILER MASS FLOW RATE [kg/s] | BOILER ANCILLARY ELECTRICITY RATE [W] | BOILER PART LOAD RATIO [] | BOILER PART LOAD RATIO {Maximum} [] | BOILER PART LOAD RATIO {TIMESTAMP} | |
January | 0.116921E+13 | 0.00 | 671.73 | 2964503.23 | 09-JAN-07:02 | 0.00 | 36.86 | 77.50 | 2.89 | 0.00 | 0.11 | 0.77 | 09-JAN-07:02 |
February | 0.559699E+12 | 0.00 | 571.26 | 2629765.84 | 14-FEB-07:03 | 0.00 | 32.84 | 74.19 | 1.38 | 0.00 | 0.06 | 0.69 | 14-FEB-07:03 |
March | 0.282164E+12 | 0.00 | 539.69 | 2024309.83 | 06-MAR-05:01 | 0.00 | 29.93 | 66.72 | 0.55 | 0.00 | 0.03 | 0.53 | 06-MAR-05:01 |
April | 0.794728E+11 | 0.00 | 316.76 | 1740089.43 | 10-APR-04:01 | 0.00 | 26.90 | 50.28 | 0.15 | 0.00 | 0.01 | 0.45 | 10-APR-04:01 |
May | 0.649624E+10 | 0.00 | 85.60 | 955228.26 | 01-MAY-05:02 | 0.00 | 31.75 | 37.60 | 0.01 | 0.00 | 0.00 | 0.25 | 01-MAY-05:02 |
June | 0.206992E+09 | 0.00 | 16.42 | 94765.59 | 03-JUN-06:10 | 0.00 | 30.20 | 31.37 | 0.00 | 0.00 | 0.00 | 0.02 | 03-JUN-06:10 |
July | 6423780.38 | 0.00 | 1.00 | 6831.32 | 08-JUL-06:10 | 0.00 | 29.40 | 29.47 | 0.00 | 0.00 | 0.00 | 0.00 | 08-JUL-06:10 |
August | 0.248288E+09 | 0.00 | 13.88 | 121133.34 | 19-AUG-06:15 | 0.00 | 29.43 | 30.42 | 0.00 | 0.00 | 0.00 | 0.03 | 19-AUG-06:15 |
September | 0.834020E+10 | 0.00 | 137.57 | 388548.85 | 23-SEP-06:10 | 0.00 | 28.10 | 38.62 | 0.01 | 0.00 | 0.00 | 0.10 | 23-SEP-06:10 |
October | 0.824696E+11 | 0.00 | 351.63 | 1916873.07 | 16-OCT-04:11 | 0.00 | 26.21 | 51.72 | 0.15 | 0.00 | 0.01 | 0.50 | 16-OCT-04:11 |
November | 0.266409E+12 | 0.00 | 526.39 | 2185366.93 | 27-NOV-05:11 | 0.00 | 29.38 | 66.87 | 0.53 | 0.00 | 0.03 | 0.57 | 27-NOV-05:11 |
December | 0.887893E+12 | 0.00 | 653.36 | 2628294.04 | 26-DEC-07:03 | 0.00 | 34.87 | 75.95 | 2.01 | 0.00 | 0.09 | 0.69 | 26-DEC-07:03 |
Annual Sum or Average | 0.334262E+13 | 0.00 | 3885.26 | 0.00 | 30.49 | 52.45 | 0.64 | 0.00 | 0.03 | ||||
Minimum of Months | 6423780.38 | 0.00 | 1.00 | 6831.32 | 0.00 | 26.21 | 29.47 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.116921E+13 | 0.00 | 671.73 | 2964503.23 | 0.00 | 36.86 | 77.50 | 2.89 | 0.00 | 0.11 | 0.77 |
Report: BoilerReportMonthly
For: CENTRAL BOILER
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportBOILER HEATING ENERGY [J] | BOILER GAS CONSUMPTION [] | BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] | BOILER HEATING RATE {Maximum} [W] | BOILER HEATING RATE {TIMESTAMP} | BOILER GAS CONSUMPTION RATE [] | BOILER INLET TEMPERATURE [C] | BOILER OUTLET TEMPERATURE [C] | BOILER MASS FLOW RATE [kg/s] | BOILER ANCILLARY ELECTRICITY RATE [W] | BOILER PART LOAD RATIO [] | BOILER PART LOAD RATIO [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 0.00 | 18.51 | 18.51 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 19.18 | 19.18 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 20.00 | 20.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 21.46 | 21.46 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 20.49 | 20.49 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 24.74 | 24.74 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 31.30 | 31.30 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 32.13 | 32.13 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 19.34 | 19.34 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 19.59 | 19.59 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 19.98 | 19.98 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 20.19 | 20.19 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 22.28 | 22.28 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.51 | 18.51 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.13 | 32.13 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: VAV_BOT WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 18529901.46 | 0.00 | 11.53 | 18529901.46 | 0.00 | 0.00 | 0.00 | 0.00 | 5966.72 | 27-JAN-15:20 | 5966.72 | 27-JAN-15:20 | 0.00 | 0.00 | 0.00 |
February | 70658977.20 | 0.00 | 16.94 | 70658977.20 | 0.00 | 0.00 | 0.00 | 0.00 | 28730.33 | 10-FEB-10:25 | 28730.33 | 10-FEB-10:25 | 0.00 | 0.00 | 0.00 |
March | 91912802.74 | 0.00 | 47.79 | 91912802.74 | 0.00 | 0.00 | 0.00 | 0.00 | 15261.81 | 23-MAR-10:05 | 15261.81 | 23-MAR-10:05 | 0.00 | 0.00 | 0.00 |
April | 0.517077E+10 | 0.00 | 69.80 | 0.517077E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 100546.26 | 23-APR-16:11 | 100546.26 | 23-APR-16:11 | 0.00 | 0.00 | 0.00 |
May | 0.398890E+11 | 0.00 | 230.50 | 0.389586E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 143308.86 | 26-MAY-11:00 | 125685.76 | 18-MAY-14:50 | 0.00 | 0.00 | 0.00 |
June | 0.932611E+11 | 0.00 | 384.32 | 0.745529E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 229762.53 | 19-JUN-15:30 | 159154.66 | 30-JUN-05:02 | 0.00 | 0.00 | 0.00 |
July | 0.128694E+12 | 0.00 | 482.06 | 0.966485E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 293042.67 | 05-JUL-10:25 | 143918.81 | 24-JUL-14:50 | 0.00 | 0.00 | 0.00 |
August | 0.100130E+12 | 0.00 | 464.37 | 0.753437E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 250088.88 | 31-AUG-12:50 | 145982.75 | 08-AUG-15:00 | 0.00 | 0.00 | 0.00 |
September | 0.203591E+11 | 0.00 | 175.52 | 0.181659E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 156749.99 | 01-SEP-13:10 | 131742.32 | 01-SEP-15:40 | 0.00 | 0.00 | 0.00 |
October | 0.358375E+10 | 0.00 | 56.06 | 0.358375E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 82763.18 | 19-OCT-15:00 | 82763.18 | 19-OCT-15:00 | 0.00 | 0.00 | 0.00 |
November | 0.443864E+09 | 0.00 | 30.72 | 0.443864E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 24638.94 | 01-NOV-15:00 | 24638.94 | 01-NOV-15:00 | 0.00 | 0.00 | 0.00 |
December | 21125539.57 | 0.00 | 23.08 | 21125539.57 | 0.00 | 0.00 | 0.00 | 0.00 | 7386.82 | 14-DEC-12:30 | 7386.82 | 14-DEC-12:30 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.391734E+12 | 0.00 | 1992.70 | 0.313070E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 18529901.46 | 0.00 | 11.53 | 18529901.46 | 0.00 | 0.00 | 0.00 | 0.00 | 5966.72 | 5966.72 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.128694E+12 | 0.00 | 482.06 | 0.966485E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 293042.67 | 159154.66 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: VAV_MID WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 943638.22 | 0.00 | 35.19 | 943638.22 | 0.00 | 0.00 | 0.00 | 0.00 | 476.75 | 27-JAN-15:00 | 476.75 | 27-JAN-15:00 | 0.00 | 0.00 | 0.00 |
February | 51940257.94 | 0.00 | 37.00 | 51940257.94 | 0.00 | 0.00 | 0.00 | 0.00 | 10222.14 | 11-FEB-13:20 | 10222.14 | 11-FEB-13:20 | 0.00 | 0.00 | 0.00 |
March | 0.178942E+09 | 0.00 | 40.69 | 0.178942E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 63436.99 | 29-MAR-11:30 | 63436.99 | 29-MAR-11:30 | 0.00 | 0.00 | 0.00 |
April | 0.383648E+11 | 0.00 | 72.50 | 0.383648E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 953717.49 | 23-APR-15:52 | 953717.49 | 23-APR-15:52 | 0.00 | 0.00 | 0.00 |
May | 0.356931E+12 | 0.00 | 230.47 | 0.348152E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1340507.47 | 26-MAY-11:00 | 1220875.54 | 18-MAY-15:00 | 0.00 | 0.00 | 0.00 |
June | 0.796711E+12 | 0.00 | 365.56 | 0.642269E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 2115328.93 | 29-JUN-04:12 | 1315137.91 | 29-JUN-15:50 | 0.00 | 0.00 | 0.00 |
July | 0.103109E+13 | 0.00 | 411.96 | 0.796710E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 2593460.28 | 05-JUL-10:30 | 1371401.89 | 23-JUL-16:01 | 0.00 | 0.00 | 0.00 |
August | 0.768851E+12 | 0.00 | 398.71 | 0.592028E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1987205.69 | 31-AUG-12:50 | 1277712.03 | 08-AUG-15:20 | 0.00 | 0.00 | 0.00 |
September | 0.177513E+12 | 0.00 | 174.89 | 0.160919E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1423241.84 | 01-SEP-13:10 | 1229690.53 | 01-SEP-16:00 | 0.00 | 0.00 | 0.00 |
October | 0.320185E+11 | 0.00 | 68.66 | 0.320185E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 681318.18 | 19-OCT-15:00 | 681318.18 | 19-OCT-15:00 | 0.00 | 0.00 | 0.00 |
November | 0.256935E+10 | 0.00 | 53.19 | 0.256935E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 155239.05 | 01-NOV-15:00 | 155239.05 | 01-NOV-15:00 | 0.00 | 0.00 | 0.00 |
December | 512583.72 | 0.00 | 25.36 | 512583.72 | 0.00 | 0.00 | 0.00 | 0.00 | 42.90 | 30-DEC-10:50 | 42.90 | 30-DEC-10:50 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.320428E+13 | 0.00 | 1914.18 | 0.261326E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 512583.72 | 0.00 | 25.36 | 512583.72 | 0.00 | 0.00 | 0.00 | 0.00 | 42.90 | 42.90 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.103109E+13 | 0.00 | 411.96 | 0.796710E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 2593460.28 | 1371401.89 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: VAV_TOP WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 744322.17 | 0.00 | 0.98 | 744322.17 | 0.00 | 0.00 | 0.00 | 0.00 | 1011.25 | 13-JAN-06:04 | 1011.25 | 13-JAN-06:04 | 0.00 | 0.00 | 0.00 |
February | 11637184.48 | 0.00 | 14.03 | 11637184.48 | 0.00 | 0.00 | 0.00 | 0.00 | 2136.35 | 08-FEB-10:50 | 2136.35 | 08-FEB-10:50 | 0.00 | 0.00 | 0.00 |
March | 46726950.28 | 0.00 | 38.64 | 46726950.28 | 0.00 | 0.00 | 0.00 | 0.00 | 2368.34 | 31-MAR-12:10 | 2368.34 | 31-MAR-12:10 | 0.00 | 0.00 | 0.00 |
April | 0.364001E+10 | 0.00 | 90.03 | 0.364001E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 104389.50 | 23-APR-16:01 | 104389.50 | 23-APR-16:01 | 0.00 | 0.00 | 0.00 |
May | 0.377033E+11 | 0.00 | 226.46 | 0.367897E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 150865.10 | 25-MAY-16:00 | 143270.07 | 18-MAY-14:30 | 0.00 | 0.00 | 0.00 |
June | 0.834621E+11 | 0.00 | 359.90 | 0.675133E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 303679.83 | 30-JUN-03:02 | 159798.66 | 30-JUN-14:50 | 0.00 | 0.00 | 0.00 |
July | 0.108927E+12 | 0.00 | 408.17 | 0.841428E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 262665.60 | 05-JUL-10:35 | 166629.34 | 23-JUL-14:01 | 0.00 | 0.00 | 0.00 |
August | 0.789273E+11 | 0.00 | 392.76 | 0.607464E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 224497.74 | 29-AUG-15:40 | 147663.60 | 08-AUG-15:20 | 0.00 | 0.00 | 0.00 |
September | 0.168080E+11 | 0.00 | 170.21 | 0.152758E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 165830.77 | 01-SEP-14:00 | 138825.20 | 01-SEP-16:00 | 0.00 | 0.00 | 0.00 |
October | 0.288334E+10 | 0.00 | 89.53 | 0.288334E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 67397.32 | 19-OCT-15:00 | 67397.32 | 19-OCT-15:00 | 0.00 | 0.00 | 0.00 |
November | 0.245820E+09 | 0.00 | 45.07 | 0.245820E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13002.50 | 01-NOV-15:00 | 13002.50 | 01-NOV-15:00 | 0.00 | 0.00 | 0.00 |
December | 589398.11 | 0.00 | 0.46 | 589398.11 | 0.00 | 0.00 | 0.00 | 0.00 | 985.81 | 09-DEC-19:22 | 985.81 | 09-DEC-19:22 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.332657E+12 | 0.00 | 1836.24 | 0.271297E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 589398.11 | 0.00 | 0.46 | 589398.11 | 0.00 | 0.00 | 0.00 | 0.00 | 985.81 | 985.81 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.108927E+12 | 0.00 | 408.17 | 0.841428E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 303679.83 | 166629.34 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: CAV_BAS COOLING COIL
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 33776607.20 | 0.00 | 108.89 | 33776607.20 | 0.00 | 0.00 | 0.00 | 0.00 | 8398.14 | 31-JAN-19:00 | 8398.14 | 31-JAN-19:00 | 0.00 | 0.00 | 0.00 |
February | 40624363.97 | 0.00 | 108.38 | 40624363.97 | 0.00 | 0.00 | 0.00 | 0.00 | 10701.12 | 01-FEB-18:00 | 10701.12 | 01-FEB-18:00 | 0.00 | 0.00 | 0.00 |
March | 23579530.63 | 0.00 | 92.32 | 23579530.63 | 0.00 | 0.00 | 0.00 | 0.00 | 8087.90 | 15-MAR-06:40 | 8087.90 | 15-MAR-06:40 | 0.00 | 0.00 | 0.00 |
April | 0.814743E+09 | 0.00 | 22.09 | 0.814743E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 27919.32 | 13-APR-16:00 | 27919.32 | 13-APR-16:00 | 0.00 | 0.00 | 0.00 |
May | 0.200178E+11 | 0.00 | 163.91 | 0.198513E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 100992.08 | 26-MAY-04:12 | 64599.77 | 26-MAY-04:12 | 0.00 | 0.00 | 0.00 |
June | 0.452142E+11 | 0.00 | 289.38 | 0.383284E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 200599.81 | 30-JUN-03:02 | 91123.52 | 30-JUN-04:03 | 0.00 | 0.00 | 0.00 |
July | 0.595295E+11 | 0.00 | 332.49 | 0.488739E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 180883.02 | 23-JUL-15:57 | 100834.83 | 23-JUL-18:47 | 0.00 | 0.00 | 0.00 |
August | 0.477552E+11 | 0.00 | 311.55 | 0.384284E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 143928.01 | 27-AUG-16:31 | 103890.21 | 20-AUG-14:20 | 0.00 | 0.00 | 0.00 |
September | 0.855878E+10 | 0.00 | 102.32 | 0.803949E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 106719.85 | 03-SEP-16:51 | 80195.29 | 03-SEP-15:36 | 0.00 | 0.00 | 0.00 |
October | 0.116867E+10 | 0.00 | 18.52 | 0.116867E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 46173.01 | 19-OCT-15:00 | 46173.01 | 19-OCT-15:00 | 0.00 | 0.00 | 0.00 |
November | 0.154435E+09 | 0.00 | 33.80 | 0.152724E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 20545.46 | 21-NOV-06:02 | 15085.85 | 01-NOV-04:11 | 0.00 | 0.00 | 0.00 |
December | 60024891.36 | 0.00 | 135.67 | 60024891.36 | 0.00 | 0.00 | 0.00 | 0.00 | 28616.80 | 18-DEC-16:30 | 28616.80 | 18-DEC-16:30 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.183371E+12 | 0.00 | 1719.31 | 0.155816E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 23579530.63 | 0.00 | 18.52 | 23579530.63 | 0.00 | 0.00 | 0.00 | 0.00 | 8087.90 | 8087.90 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.595295E+11 | 0.00 | 332.49 | 0.488739E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 200599.81 | 103890.21 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: AIRLOOP DATACENTER BASEMENT COOLING COIL
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.582103E+10 | 0.410696E+10 | 744.00 | 0.582103E+10 | 87.44 | 0.00 | 0.02 | 21-JAN-16:00 | 0.01 | 06-JAN-09:00 | 2813.12 | 21-JAN-16:00 | 2813.12 | 21-JAN-16:00 | 0.15 | 06-JAN-09:00 | 2028.77 | 27-JAN-14:25 | 0.00 |
February | 0.106108E+11 | 0.532970E+10 | 672.00 | 0.105412E+11 | 69564682.40 | 0.00 | 0.03 | 08-FEB-14:40 | 0.02 | 14-FEB-08:65 | 5155.73 | 22-FEB-17:33 | 5155.73 | 22-FEB-17:33 | 126.59 | 14-FEB-07:10 | 3190.14 | 08-FEB-14:40 | 0.00 |
March | 0.144095E+11 | 0.700143E+10 | 744.00 | 0.143464E+11 | 63088661.75 | 0.00 | 0.03 | 23-MAR-15:20 | 0.03 | 20-MAR-23:00 | 5692.27 | 05-MAR-03:42 | 5629.47 | 31-MAR-23:10 | 368.39 | 20-MAR-18:00 | 3447.58 | 23-MAR-15:20 | 0.00 |
April | 0.567057E+11 | 0.205553E+11 | 720.00 | 0.552791E+11 | 0.142666E+10 | 0.00 | 1.00 | 23-APR-15:51 | 0.02 | 30-APR-24:00 | 394062.08 | 23-APR-15:51 | 393286.24 | 23-APR-15:51 | 43859.80 | 23-APR-11:22 | 131581.61 | 23-APR-16:00 | 0.00 |
May | 0.276953E+11 | 0.118053E+11 | 600.14 | 0.262400E+11 | 0.145530E+10 | 0.00 | 0.41 | 25-MAY-13:10 | 0.01 | 29-MAY-09:32 | 158281.29 | 25-MAY-13:10 | 131269.81 | 25-MAY-16:00 | 47752.54 | 26-MAY-12:00 | 50945.04 | 25-MAY-13:10 | 0.00 |
June | 0.176663E+12 | 0.570657E+11 | 468.38 | 0.130179E+12 | 0.464842E+11 | 0.00 | 1.00 | 29-JUN-21:44 | 0.00 | 16-JUN-01:50 | 469473.19 | 29-JUN-21:42 | 225560.25 | 29-JUN-16:00 | 277988.63 | 29-JUN-23:00 | 133579.59 | 29-JUN-21:50 | 0.00 |
July | 0.551045E+12 | 0.160856E+12 | 618.37 | 0.338956E+12 | 0.212089E+12 | 0.00 | 1.00 | 03-JUL-13:00 | 0.01 | 27-JUL-02:70 | 474516.92 | 15-JUL-14:00 | 344761.15 | 21-JUL-15:13 | 311056.22 | 04-JUL-01:00 | 146748.00 | 15-JUL-14:10 | 0.00 |
August | 0.695164E+12 | 0.194096E+12 | 716.82 | 0.418159E+12 | 0.277006E+12 | 0.00 | 1.00 | 03-AUG-14:00 | 0.01 | 19-AUG-07:10 | 453123.46 | 31-AUG-12:55 | 376276.94 | 25-AUG-14:00 | 262925.83 | 28-AUG-20:00 | 145164.41 | 08-AUG-15:10 | 0.00 |
September | 0.541516E+10 | 0.426428E+10 | 416.67 | 0.481566E+10 | 0.599494E+09 | 0.00 | 0.36 | 01-SEP-15:00 | 0.01 | 30-SEP-22:30 | 130603.86 | 01-SEP-15:00 | 112903.84 | 01-SEP-15:00 | 24037.23 | 01-SEP-13:40 | 42635.65 | 01-SEP-15:00 | 0.00 |
October | 0.106052E+11 | 0.564937E+10 | 704.97 | 0.103268E+11 | 0.278360E+09 | 0.00 | 0.29 | 19-OCT-15:00 | 0.00 | 07-OCT-03:10 | 97535.16 | 19-OCT-15:00 | 97535.16 | 19-OCT-15:00 | 5779.69 | 19-OCT-13:00 | 31737.93 | 19-OCT-15:00 | 0.00 |
November | 0.149034E+11 | 0.701903E+10 | 696.18 | 0.143641E+11 | 0.539207E+09 | 0.00 | 0.31 | 01-NOV-15:00 | 0.01 | 01-NOV-04:57 | 106830.25 | 01-NOV-15:00 | 82681.63 | 01-NOV-15:00 | 24148.63 | 01-NOV-15:00 | 30754.15 | 01-NOV-15:00 | 0.00 |
December | 0.150538E+11 | 0.752547E+10 | 744.00 | 0.150089E+11 | 44896629.59 | 0.00 | 0.03 | 29-DEC-13:30 | 0.03 | 17-DEC-12:33 | 6076.59 | 06-DEC-03:00 | 5637.23 | 17-DEC-05:23 | 468.23 | 06-DEC-03:00 | 3634.80 | 29-DEC-13:30 | 0.00 |
Annual Sum or Average | 0.158409E+13 | 0.485275E+12 | 7845.54 | 0.104404E+13 | 0.540055E+12 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.541516E+10 | 0.410696E+10 | 416.67 | 0.481566E+10 | 87.44 | 0.00 | 0.02 | 0.00 | 2813.12 | 2813.12 | 0.15 | 2028.77 | 0.00 | ||||||
Maximum of Months | 0.695164E+12 | 0.194096E+12 | 744.00 | 0.418159E+12 | 0.277006E+12 | 0.00 | 1.00 | 0.03 | 474516.92 | 393286.24 | 311056.22 | 146748.00 | 0.00 |
Report: DXReportMonthly
For: AIRLOOP DATACENTER BOT COOLING COIL
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.185608E+10 | 0.561227E+09 | 669.76 | 0.185608E+10 | -0.0 | 0.00 | 0.27 | 20-JAN-16:25 | 0.00 | 01-JAN-00:01 | 2180.32 | 20-JAN-16:25 | 2180.32 | 20-JAN-16:25 | 0.00 | 01-JAN-16:49 | 583.08 | 20-JAN-16:25 | 0.00 |
February | 0.749899E+10 | 0.200186E+10 | 672.00 | 0.749899E+10 | -0.0 | 0.00 | 0.57 | 27-FEB-17:00 | 0.25 | 14-FEB-07:03 | 4737.72 | 27-FEB-17:00 | 4737.72 | 27-FEB-17:00 | 0.00 | 07-FEB-16:30 | 1206.11 | 27-FEB-17:00 | 0.00 |
March | 0.143998E+11 | 0.357084E+10 | 744.00 | 0.143998E+11 | -0.0 | 0.00 | 0.85 | 19-MAR-17:33 | 0.50 | 06-MAR-07:05 | 7656.88 | 31-MAR-24:00 | 7656.88 | 31-MAR-24:00 | 0.00 | 08-MAR-17:20 | 1803.34 | 19-MAR-17:35 | 0.00 |
April | 0.198874E+11 | 0.468275E+10 | 720.00 | 0.198874E+11 | 0.00 | 0.00 | 1.00 | 22-APR-17:55 | 0.30 | 30-APR-24:00 | 9110.17 | 21-APR-18:20 | 9110.17 | 21-APR-18:20 | 0.00 | 04-APR-11:34 | 2977.41 | 23-APR-16:00 | 0.00 |
May | 0.604336E+10 | 0.159021E+10 | 744.00 | 0.599972E+10 | 43641799.58 | 0.00 | 0.43 | 14-MAY-18:42 | 0.17 | 13-MAY-06:20 | 3896.58 | 31-MAY-24:00 | 3896.58 | 31-MAY-24:00 | 258.59 | 26-MAY-13:20 | 1182.21 | 25-MAY-18:40 | 0.00 |
June | 0.111463E+11 | 0.291490E+10 | 720.00 | 0.109455E+11 | 0.200829E+09 | 0.00 | 0.63 | 29-JUN-16:00 | 0.41 | 10-JUN-06:20 | 6055.05 | 30-JUN-23:32 | 6009.67 | 30-JUN-23:45 | 485.43 | 30-JUN-16:00 | 2112.40 | 29-JUN-16:00 | 0.00 |
July | 0.168157E+11 | 0.452252E+10 | 744.00 | 0.165368E+11 | 0.278846E+09 | 0.00 | 0.80 | 20-JUL-19:00 | 0.60 | 08-JUL-07:00 | 7878.58 | 31-JUL-23:52 | 7878.58 | 31-JUL-23:52 | 505.80 | 05-JUL-11:00 | 2537.19 | 21-JUL-15:13 | 0.00 |
August | 0.217185E+11 | 0.548738E+10 | 744.00 | 0.214316E+11 | 0.286903E+09 | 0.00 | 1.00 | 08-AUG-15:40 | 0.30 | 31-AUG-24:00 | 9257.59 | 13-AUG-18:31 | 9257.59 | 13-AUG-18:31 | 411.97 | 31-AUG-16:00 | 3275.31 | 08-AUG-15:40 | 0.00 |
September | 0.560885E+10 | 0.140722E+10 | 720.00 | 0.555339E+10 | 55463376.35 | 0.00 | 0.43 | 30-SEP-24:00 | 0.16 | 23-SEP-06:55 | 3912.47 | 30-SEP-24:00 | 3912.47 | 30-SEP-24:00 | 254.92 | 18-SEP-16:00 | 993.20 | 01-SEP-16:00 | 0.00 |
October | 0.101532E+11 | 0.245648E+10 | 744.00 | 0.101476E+11 | 5573974.11 | 0.00 | 0.61 | 31-OCT-24:00 | 0.32 | 30-OCT-06:10 | 5428.90 | 31-OCT-24:00 | 5428.90 | 31-OCT-24:00 | 93.19 | 02-OCT-10:50 | 1312.32 | 31-OCT-24:00 | 0.00 |
November | 0.139825E+11 | 0.341900E+10 | 720.00 | 0.139774E+11 | 5158854.03 | 0.00 | 0.72 | 12-NOV-16:03 | 0.51 | 25-NOV-07:05 | 6428.03 | 12-NOV-16:08 | 6428.03 | 12-NOV-16:08 | 184.92 | 21-NOV-12:10 | 1545.43 | 12-NOV-16:03 | 0.00 |
December | 0.182879E+11 | 0.448707E+10 | 744.00 | 0.182879E+11 | 0.00 | 0.00 | 0.91 | 10-DEC-15:51 | 0.67 | 26-DEC-07:03 | 7892.81 | 10-DEC-15:53 | 7892.81 | 10-DEC-15:53 | 0.00 | 04-DEC-19:50 | 1934.60 | 10-DEC-15:51 | 0.00 |
Annual Sum or Average | 0.147399E+12 | 0.371015E+11 | 8685.76 | 0.146522E+12 | 0.876415E+09 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.185608E+10 | 0.561227E+09 | 669.76 | 0.185608E+10 | -0.0 | 0.00 | 0.27 | 0.00 | 2180.32 | 2180.32 | 0.00 | 583.08 | 0.00 | ||||||
Maximum of Months | 0.217185E+11 | 0.548738E+10 | 744.00 | 0.214316E+11 | 0.286903E+09 | 0.00 | 1.00 | 0.67 | 9257.59 | 9257.59 | 505.80 | 3275.31 | 0.00 |
Report: DXReportMonthly
For: AIRLOOP DATACENTER MID COOLING COIL
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.216834E+10 | 0.711751E+09 | 160.76 | 0.216834E+10 | -0.0 | 0.00 | 0.22 | 27-JAN-16:30 | 0.00 | 01-JAN-00:01 | 16710.89 | 20-JAN-16:25 | 16710.89 | 20-JAN-16:25 | 0.00 | 19-JAN-16:30 | 4599.78 | 27-JAN-16:30 | 0.00 |
February | 0.466453E+11 | 0.129073E+11 | 672.00 | 0.466453E+11 | -0.0 | 0.00 | 0.51 | 08-FEB-17:00 | 0.08 | 13-FEB-07:03 | 42006.48 | 08-FEB-17:00 | 42006.48 | 08-FEB-17:00 | 0.00 | 08-FEB-14:20 | 10938.77 | 22-FEB-17:15 | 0.00 |
March | 0.116194E+12 | 0.294056E+11 | 744.00 | 0.116194E+12 | 0.00 | 0.00 | 0.79 | 31-MAR-23:20 | 0.34 | 06-MAR-07:05 | 68996.85 | 31-MAR-23:20 | 68996.85 | 31-MAR-23:20 | 0.00 | 09-MAR-18:30 | 16189.43 | 31-MAR-23:20 | 0.00 |
April | 0.176061E+12 | 0.419553E+11 | 720.00 | 0.176061E+12 | -0.0 | 0.00 | 1.00 | 23-APR-15:21 | 0.19 | 30-APR-24:00 | 87214.04 | 21-APR-18:20 | 87214.04 | 21-APR-18:20 | 0.00 | 11-APR-08:10 | 28679.34 | 23-APR-16:00 | 0.00 |
May | 0.526109E+11 | 0.140031E+11 | 744.00 | 0.521792E+11 | 0.431732E+09 | 0.00 | 0.43 | 14-MAY-18:42 | 0.08 | 01-MAY-06:05 | 35194.01 | 14-MAY-18:43 | 35194.01 | 14-MAY-18:43 | 2555.18 | 26-MAY-13:20 | 11634.83 | 25-MAY-18:40 | 0.00 |
June | 0.103041E+12 | 0.271161E+11 | 720.00 | 0.101050E+12 | 0.199163E+10 | 0.00 | 0.63 | 30-JUN-23:20 | 0.36 | 10-JUN-07:00 | 59020.81 | 30-JUN-23:32 | 58529.34 | 30-JUN-23:55 | 4843.28 | 30-JUN-16:00 | 20242.70 | 29-JUN-16:00 | 0.00 |
July | 0.159015E+12 | 0.428903E+11 | 744.00 | 0.156244E+12 | 0.277158E+10 | 0.00 | 0.80 | 28-JUL-18:50 | 0.56 | 08-JUL-17:00 | 75006.16 | 31-JUL-23:52 | 75006.16 | 31-JUL-23:52 | 5035.77 | 05-JUL-11:00 | 24143.91 | 21-JUL-15:13 | 0.00 |
August | 0.204278E+12 | 0.518092E+11 | 744.00 | 0.201422E+12 | 0.285557E+10 | 0.00 | 0.99 | 08-AUG-16:00 | 0.25 | 31-AUG-24:00 | 87942.29 | 02-AUG-18:40 | 87714.47 | 05-AUG-18:35 | 4108.70 | 31-AUG-16:00 | 31129.97 | 08-AUG-16:00 | 0.00 |
September | 0.459257E+11 | 0.116954E+11 | 720.00 | 0.453842E+11 | 0.541448E+09 | 0.00 | 0.41 | 09-SEP-17:55 | 0.11 | 23-SEP-06:55 | 35718.02 | 03-SEP-17:53 | 35612.53 | 03-SEP-17:53 | 2502.90 | 18-SEP-16:00 | 9291.42 | 01-SEP-17:30 | 0.00 |
October | 0.806228E+11 | 0.199222E+11 | 744.00 | 0.805676E+11 | 55247670.95 | 0.00 | 0.53 | 19-OCT-16:40 | 0.20 | 30-OCT-06:10 | 47219.35 | 19-OCT-16:50 | 46639.62 | 19-OCT-16:50 | 1097.00 | 02-OCT-13:10 | 12208.64 | 19-OCT-16:00 | 0.00 |
November | 0.108229E+12 | 0.271103E+11 | 720.00 | 0.108177E+12 | 51837132.31 | 0.00 | 0.69 | 17-NOV-16:00 | 0.35 | 27-NOV-04:01 | 58333.22 | 17-NOV-16:10 | 58333.22 | 17-NOV-16:10 | 1806.37 | 21-NOV-12:10 | 14642.29 | 17-NOV-16:00 | 0.00 |
December | 0.141743E+12 | 0.357101E+11 | 744.00 | 0.141743E+12 | -0.0 | 0.00 | 0.80 | 20-DEC-15:55 | 0.49 | 26-DEC-07:03 | 67216.07 | 08-DEC-15:55 | 67216.07 | 08-DEC-15:55 | 0.00 | 18-DEC-22:25 | 16420.98 | 20-DEC-15:55 | 0.00 |
Annual Sum or Average | 0.123653E+13 | 0.315237E+12 | 8176.76 | 0.122784E+13 | 0.869904E+10 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.216834E+10 | 0.711751E+09 | 160.76 | 0.216834E+10 | -0.0 | 0.00 | 0.22 | 0.00 | 16710.89 | 16710.89 | 0.00 | 4599.78 | 0.00 | ||||||
Maximum of Months | 0.204278E+12 | 0.518092E+11 | 744.00 | 0.201422E+12 | 0.285557E+10 | 0.00 | 1.00 | 0.56 | 87942.29 | 87714.47 | 5035.77 | 31129.97 | 0.00 |
Report: DXReportMonthly
For: AIRLOOP DATACENTER TOP COOLING COIL
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 99812034.80 | 31773263.70 | 62.00 | 99812034.80 | -0.0 | 0.00 | 0.20 | 20-JAN-16:25 | 0.00 | 01-JAN-00:01 | 1496.72 | 20-JAN-16:25 | 1496.72 | 20-JAN-16:25 | 0.00 | 18-JAN-14:30 | 412.58 | 20-JAN-16:25 | 0.00 |
February | 0.319744E+10 | 0.898037E+09 | 626.87 | 0.319744E+10 | 0.00 | 0.00 | 0.50 | 08-FEB-17:00 | 0.00 | 01-FEB-00:03 | 4177.83 | 08-FEB-17:00 | 4177.83 | 08-FEB-17:00 | 0.00 | 05-FEB-23:55 | 1045.11 | 08-FEB-17:00 | 0.00 |
March | 0.100171E+11 | 0.256371E+10 | 744.00 | 0.100171E+11 | -0.0 | 0.00 | 0.74 | 31-MAR-23:10 | 0.20 | 06-MAR-04:01 | 6485.16 | 31-MAR-23:10 | 6485.16 | 31-MAR-23:10 | 0.00 | 21-MAR-09:00 | 1536.13 | 31-MAR-23:10 | 0.00 |
April | 0.163700E+11 | 0.394114E+10 | 720.00 | 0.163700E+11 | 0.00 | 0.00 | 1.00 | 23-APR-15:42 | 0.09 | 30-APR-24:00 | 8718.71 | 21-APR-18:20 | 8718.71 | 21-APR-18:20 | 0.00 | 15-APR-23:10 | 2904.28 | 23-APR-16:00 | 0.00 |
May | 0.480231E+10 | 0.128825E+10 | 742.61 | 0.475913E+10 | 43183055.64 | 0.00 | 0.43 | 25-MAY-18:40 | 0.00 | 01-MAY-00:15 | 3586.07 | 25-MAY-18:50 | 3439.48 | 25-MAY-18:50 | 256.92 | 26-MAY-13:20 | 1190.68 | 25-MAY-18:40 | 0.00 |
June | 0.100781E+11 | 0.266762E+10 | 720.00 | 0.987932E+10 | 0.198824E+09 | 0.00 | 0.63 | 29-JUN-16:00 | 0.31 | 11-JUN-05:30 | 5890.38 | 30-JUN-23:32 | 5840.18 | 30-JUN-23:34 | 485.42 | 30-JUN-16:00 | 2064.63 | 29-JUN-16:00 | 0.00 |
July | 0.157857E+11 | 0.427596E+10 | 744.00 | 0.155089E+11 | 0.276814E+09 | 0.00 | 0.80 | 28-JUL-18:50 | 0.51 | 09-JUL-05:00 | 7416.35 | 31-JUL-23:52 | 7416.35 | 31-JUL-23:52 | 503.20 | 05-JUL-11:00 | 2450.18 | 21-JUL-15:13 | 0.00 |
August | 0.202409E+11 | 0.515445E+10 | 744.00 | 0.199558E+11 | 0.285029E+09 | 0.00 | 0.99 | 08-AUG-16:00 | 0.24 | 31-AUG-24:00 | 8861.69 | 05-AUG-18:35 | 8861.69 | 05-AUG-18:35 | 410.87 | 31-AUG-16:00 | 3152.61 | 08-AUG-16:00 | 0.00 |
September | 0.394908E+10 | 0.101700E+10 | 719.86 | 0.389575E+10 | 53331088.37 | 0.00 | 0.40 | 09-SEP-17:55 | 0.00 | 24-SEP-05:45 | 3547.01 | 03-SEP-17:42 | 3536.90 | 03-SEP-17:44 | 252.11 | 18-SEP-16:00 | 949.69 | 01-SEP-17:30 | 0.00 |
October | 0.655203E+10 | 0.163710E+10 | 744.00 | 0.654658E+10 | 5454238.43 | 0.00 | 0.53 | 19-OCT-16:40 | 0.03 | 30-OCT-03:15 | 4764.84 | 19-OCT-16:50 | 4706.60 | 19-OCT-16:50 | 92.63 | 02-OCT-14:10 | 1231.70 | 19-OCT-16:00 | 0.00 |
November | 0.904495E+10 | 0.229420E+10 | 720.00 | 0.903987E+10 | 5082936.96 | 0.00 | 0.66 | 17-NOV-16:10 | 0.22 | 27-NOV-04:03 | 5737.81 | 17-NOV-16:10 | 5737.81 | 17-NOV-16:10 | 176.92 | 21-NOV-12:10 | 1374.46 | 17-NOV-16:10 | 0.00 |
December | 0.125558E+11 | 0.320488E+10 | 744.00 | 0.125558E+11 | 0.00 | 0.00 | 0.77 | 20-DEC-15:55 | 0.37 | 25-DEC-07:40 | 6449.79 | 20-DEC-15:55 | 6449.79 | 20-DEC-15:55 | 0.00 | 29-DEC-05:52 | 1599.17 | 20-DEC-15:55 | 0.00 |
Annual Sum or Average | 0.112693E+12 | 0.289741E+11 | 8031.34 | 0.111826E+12 | 0.867719E+09 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 99812034.80 | 31773263.70 | 62.00 | 99812034.80 | -0.0 | 0.00 | 0.20 | 0.00 | 1496.72 | 1496.72 | 0.00 | 412.58 | 0.00 | ||||||
Maximum of Months | 0.202409E+11 | 0.515445E+10 | 744.00 | 0.199558E+11 | 0.285029E+09 | 0.00 | 1.00 | 0.51 | 8861.69 | 8861.69 | 503.20 | 3152.61 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 137.28 | 0.00 | 137.28 | 0.26 | 1357.17 | 0.00 | 0.00 | 0.00 |
February | 210.87 | 0.00 | 210.87 | 7.58 | 1109.80 | 0.00 | 0.00 | 0.00 |
March | 259.44 | 0.00 | 259.44 | 23.06 | 885.36 | 0.00 | 0.00 | 0.00 |
April | 340.10 | 2.65 | 337.45 | 120.53 | 548.17 | 0.00 | 0.00 | 0.00 |
May | 478.34 | 25.76 | 452.59 | 387.66 | 272.99 | 0.00 | 0.00 | 0.00 |
June | 533.84 | 58.68 | 475.16 | 547.27 | 188.86 | 0.00 | 0.00 | 0.00 |
July | 509.90 | 43.76 | 466.14 | 552.78 | 172.59 | 0.00 | 0.00 | 0.00 |
August | 387.28 | 6.65 | 380.63 | 371.56 | 209.24 | 0.00 | 0.00 | 0.00 |
September | 301.80 | 0.07 | 301.73 | 200.72 | 347.48 | 0.00 | 0.00 | 0.00 |
October | 209.55 | 0.00 | 209.55 | 50.83 | 560.84 | 0.00 | 0.00 | 0.00 |
November | 138.75 | 0.00 | 138.75 | 5.54 | 862.89 | 0.00 | 0.00 | 0.00 |
December | 116.31 | 0.00 | 116.31 | 0.00 | 1326.30 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 302.41 | 11.52 | 290.90 | 190.15 | 651.55 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 116.31 | 0.00 | 116.31 | 0.00 | 172.59 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 533.84 | 58.68 | 475.16 | 552.78 | 1357.17 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 137.28 | 0.00 | 137.28 | 0.26 | 1357.17 | 0.00 | 0.00 | 0.00 |
February | 210.87 | 0.00 | 210.87 | 7.58 | 1109.80 | 0.00 | 0.00 | 0.00 |
March | 259.44 | 0.00 | 259.44 | 23.06 | 885.36 | 0.00 | 0.00 | 0.00 |
April | 340.10 | 2.65 | 337.45 | 120.53 | 548.17 | 0.00 | 0.00 | 0.00 |
May | 478.34 | 25.76 | 452.58 | 387.66 | 272.99 | 0.00 | 0.00 | 0.00 |
June | 533.84 | 58.68 | 475.16 | 547.27 | 188.86 | 0.00 | 0.00 | 0.00 |
July | 509.90 | 43.76 | 466.14 | 552.78 | 172.59 | 0.00 | 0.00 | 0.00 |
August | 387.28 | 6.65 | 380.63 | 371.56 | 209.24 | 0.00 | 0.00 | 0.00 |
September | 301.80 | 0.07 | 301.73 | 200.72 | 347.48 | 0.00 | 0.00 | 0.00 |
October | 209.55 | 0.00 | 209.55 | 50.83 | 560.84 | 0.00 | 0.00 | 0.00 |
November | 138.75 | 0.00 | 138.75 | 5.54 | 862.89 | 0.00 | 0.00 | 0.00 |
December | 116.31 | 0.00 | 116.31 | 0.00 | 1326.30 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 302.41 | 11.52 | 290.90 | 190.15 | 651.55 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 116.31 | 0.00 | 116.31 | 0.00 | 172.59 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 533.84 | 58.68 | 475.16 | 552.78 | 1357.17 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 137.28 | 0.00 | 137.28 | 0.26 | 1357.17 | 0.00 | 0.00 | 0.00 |
February | 210.87 | 0.00 | 210.87 | 7.58 | 1109.80 | 0.00 | 0.00 | 0.00 |
March | 259.44 | 0.00 | 259.44 | 23.06 | 885.36 | 0.00 | 0.00 | 0.00 |
April | 340.10 | 2.65 | 337.45 | 120.53 | 548.17 | 0.00 | 0.00 | 0.00 |
May | 478.34 | 25.76 | 452.59 | 387.66 | 272.99 | 0.00 | 0.00 | 0.00 |
June | 533.84 | 58.68 | 475.16 | 547.27 | 188.86 | 0.00 | 0.00 | 0.00 |
July | 509.90 | 43.76 | 466.14 | 552.78 | 172.59 | 0.00 | 0.00 | 0.00 |
August | 387.28 | 6.65 | 380.63 | 371.56 | 209.24 | 0.00 | 0.00 | 0.00 |
September | 301.80 | 0.07 | 301.73 | 200.72 | 347.48 | 0.00 | 0.00 | 0.00 |
October | 209.55 | 0.00 | 209.55 | 50.83 | 560.84 | 0.00 | 0.00 | 0.00 |
November | 138.75 | 0.00 | 138.75 | 5.54 | 862.89 | 0.00 | 0.00 | 0.00 |
December | 116.31 | 0.00 | 116.31 | 0.00 | 1326.30 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 302.41 | 11.52 | 290.90 | 190.15 | 651.55 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 116.31 | 0.00 | 116.31 | 0.00 | 172.59 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 533.84 | 58.68 | 475.16 | 552.78 | 1357.17 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 137.28 | 0.00 | 137.28 | 0.26 | 1357.17 | 0.00 | 0.00 | 0.00 |
February | 210.87 | 0.00 | 210.87 | 7.58 | 1109.80 | 0.00 | 0.00 | 0.00 |
March | 259.44 | 0.00 | 259.44 | 23.06 | 885.36 | 0.00 | 0.00 | 0.00 |
April | 340.10 | 2.65 | 337.45 | 120.53 | 548.17 | 0.00 | 0.00 | 0.00 |
May | 478.34 | 25.76 | 452.58 | 387.66 | 272.99 | 0.00 | 0.00 | 0.00 |
June | 533.84 | 58.68 | 475.16 | 547.27 | 188.86 | 0.00 | 0.00 | 0.00 |
July | 509.90 | 43.76 | 466.14 | 552.78 | 172.59 | 0.00 | 0.00 | 0.00 |
August | 387.28 | 6.65 | 380.63 | 371.56 | 209.24 | 0.00 | 0.00 | 0.00 |
September | 301.80 | 0.07 | 301.73 | 200.72 | 347.48 | 0.00 | 0.00 | 0.00 |
October | 209.55 | 0.00 | 209.55 | 50.83 | 560.84 | 0.00 | 0.00 | 0.00 |
November | 138.75 | 0.00 | 138.75 | 5.54 | 862.89 | 0.00 | 0.00 | 0.00 |
December | 116.31 | 0.00 | 116.31 | 0.00 | 1326.30 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 302.41 | 11.52 | 290.90 | 190.15 | 651.55 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 116.31 | 0.00 | 116.31 | 0.00 | 172.59 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 533.84 | 58.68 | 475.16 | 552.78 | 1357.17 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 137.27 | 0.00 | 137.27 | 0.26 | 1357.12 | 0.00 | 0.00 | 0.00 |
February | 210.86 | 0.00 | 210.86 | 7.58 | 1109.75 | 0.00 | 0.00 | 0.00 |
March | 259.43 | 0.00 | 259.43 | 23.06 | 885.32 | 0.00 | 0.00 | 0.00 |
April | 340.09 | 2.65 | 337.44 | 120.53 | 548.14 | 0.00 | 0.00 | 0.00 |
May | 478.32 | 25.76 | 452.57 | 387.65 | 272.98 | 0.00 | 0.00 | 0.00 |
June | 533.82 | 58.68 | 475.14 | 547.25 | 188.85 | 0.00 | 0.00 | 0.00 |
July | 509.88 | 43.76 | 466.12 | 552.75 | 172.58 | 0.00 | 0.00 | 0.00 |
August | 387.27 | 6.65 | 380.62 | 371.55 | 209.23 | 0.00 | 0.00 | 0.00 |
September | 301.79 | 0.07 | 301.71 | 200.71 | 347.47 | 0.00 | 0.00 | 0.00 |
October | 209.55 | 0.00 | 209.55 | 50.82 | 560.82 | 0.00 | 0.00 | 0.00 |
November | 138.75 | 0.00 | 138.75 | 5.54 | 862.86 | 0.00 | 0.00 | 0.00 |
December | 116.31 | 0.00 | 116.31 | 0.00 | 1326.24 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 302.40 | 11.52 | 290.88 | 190.14 | 651.52 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 116.31 | 0.00 | 116.31 | 0.00 | 172.58 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 533.82 | 58.68 | 475.14 | 552.75 | 1357.12 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 334.41 | 139.59 | 194.81 | 106.80 | 1354.35 | 0.00 | 0.00 | 0.00 |
February | 525.49 | 224.15 | 301.34 | 269.27 | 1094.76 | 0.00 | 0.00 | 0.00 |
March | 716.01 | 359.16 | 356.85 | 490.27 | 880.59 | 0.00 | 0.00 | 0.00 |
April | 992.60 | 535.39 | 457.21 | 887.05 | 548.70 | 0.00 | 0.00 | 0.00 |
May | 1074.29 | 472.27 | 602.02 | 1122.12 | 300.50 | 0.00 | 0.00 | 0.00 |
June | 1216.17 | 581.76 | 634.41 | 1406.72 | 209.75 | 0.00 | 0.00 | 0.00 |
July | 1191.40 | 559.40 | 631.99 | 1422.38 | 185.49 | 0.00 | 0.00 | 0.00 |
August | 918.57 | 401.48 | 517.09 | 1046.33 | 217.45 | 0.00 | 0.00 | 0.00 |
September | 735.62 | 329.26 | 406.36 | 726.82 | 358.66 | 0.00 | 0.00 | 0.00 |
October | 445.43 | 168.91 | 276.52 | 303.69 | 568.19 | 0.00 | 0.00 | 0.00 |
November | 283.56 | 94.80 | 188.76 | 113.80 | 863.92 | 0.00 | 0.00 | 0.00 |
December | 258.75 | 95.64 | 163.11 | 64.78 | 1335.12 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 725.09 | 330.42 | 394.67 | 665.26 | 658.02 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 258.75 | 94.80 | 163.11 | 64.78 | 185.49 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1216.17 | 581.76 | 634.41 | 1422.38 | 1354.35 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 334.41 | 139.59 | 194.81 | 106.80 | 1354.35 | 0.00 | 0.00 | 0.00 |
February | 525.49 | 224.15 | 301.34 | 269.27 | 1094.76 | 0.00 | 0.00 | 0.00 |
March | 716.01 | 359.16 | 356.85 | 490.27 | 880.59 | 0.00 | 0.00 | 0.00 |
April | 992.60 | 535.39 | 457.21 | 887.05 | 548.70 | 0.00 | 0.00 | 0.00 |
May | 1074.29 | 472.27 | 602.02 | 1122.12 | 300.50 | 0.00 | 0.00 | 0.00 |
June | 1216.17 | 581.76 | 634.41 | 1406.72 | 209.75 | 0.00 | 0.00 | 0.00 |
July | 1191.40 | 559.40 | 631.99 | 1422.38 | 185.49 | 0.00 | 0.00 | 0.00 |
August | 918.57 | 401.48 | 517.09 | 1046.33 | 217.45 | 0.00 | 0.00 | 0.00 |
September | 735.62 | 329.26 | 406.36 | 726.82 | 358.66 | 0.00 | 0.00 | 0.00 |
October | 445.43 | 168.91 | 276.52 | 303.69 | 568.19 | 0.00 | 0.00 | 0.00 |
November | 283.56 | 94.80 | 188.76 | 113.80 | 863.92 | 0.00 | 0.00 | 0.00 |
December | 258.75 | 95.64 | 163.11 | 64.78 | 1335.12 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 725.09 | 330.42 | 394.67 | 665.26 | 658.02 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 258.75 | 94.80 | 163.11 | 64.78 | 185.49 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1216.17 | 581.76 | 634.41 | 1422.38 | 1354.35 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 334.40 | 139.59 | 194.81 | 106.79 | 1354.32 | 0.00 | 0.00 | 0.00 |
February | 525.48 | 224.15 | 301.33 | 269.27 | 1094.74 | 0.00 | 0.00 | 0.00 |
March | 716.00 | 359.16 | 356.84 | 490.26 | 880.58 | 0.00 | 0.00 | 0.00 |
April | 992.58 | 535.38 | 457.20 | 887.04 | 548.69 | 0.00 | 0.00 | 0.00 |
May | 1074.27 | 472.26 | 602.01 | 1122.10 | 300.49 | 0.00 | 0.00 | 0.00 |
June | 1216.15 | 581.75 | 634.40 | 1406.70 | 209.75 | 0.00 | 0.00 | 0.00 |
July | 1191.37 | 559.39 | 631.98 | 1422.36 | 185.49 | 0.00 | 0.00 | 0.00 |
August | 918.55 | 401.47 | 517.08 | 1046.31 | 217.44 | 0.00 | 0.00 | 0.00 |
September | 735.61 | 329.25 | 406.35 | 726.80 | 358.65 | 0.00 | 0.00 | 0.00 |
October | 445.42 | 168.90 | 276.52 | 303.68 | 568.18 | 0.00 | 0.00 | 0.00 |
November | 283.56 | 94.80 | 188.76 | 113.80 | 863.91 | 0.00 | 0.00 | 0.00 |
December | 258.75 | 95.64 | 163.11 | 64.77 | 1335.09 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 725.07 | 330.41 | 394.66 | 665.24 | 658.01 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 258.75 | 94.80 | 163.11 | 64.77 | 185.49 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1216.15 | 581.75 | 634.40 | 1422.36 | 1354.32 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 945.29 | 657.62 | 287.67 | 733.68 | 1066.71 | 0.00 | 0.00 | 0.00 |
February | 1196.97 | 808.47 | 388.49 | 1061.56 | 913.18 | 0.00 | 0.00 | 0.00 |
March | 1054.67 | 667.46 | 387.21 | 960.04 | 773.68 | 0.00 | 0.00 | 0.00 |
April | 955.50 | 518.62 | 436.88 | 957.09 | 528.41 | 0.00 | 0.00 | 0.00 |
May | 803.33 | 274.64 | 528.69 | 884.46 | 297.04 | 0.00 | 0.00 | 0.00 |
June | 720.81 | 192.13 | 528.68 | 852.52 | 204.76 | 0.00 | 0.00 | 0.00 |
July | 788.08 | 249.66 | 538.42 | 979.14 | 184.64 | 0.00 | 0.00 | 0.00 |
August | 841.62 | 352.04 | 489.58 | 1011.79 | 217.64 | 0.00 | 0.00 | 0.00 |
September | 901.50 | 480.12 | 421.38 | 996.39 | 342.05 | 0.00 | 0.00 | 0.00 |
October | 769.82 | 452.77 | 317.05 | 736.21 | 506.67 | 0.00 | 0.00 | 0.00 |
November | 685.74 | 430.37 | 255.37 | 570.20 | 717.52 | 0.00 | 0.00 | 0.00 |
December | 729.88 | 478.59 | 251.29 | 514.90 | 1053.72 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 863.93 | 461.34 | 402.59 | 853.25 | 565.63 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 685.74 | 192.13 | 251.29 | 514.90 | 184.64 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1196.97 | 808.47 | 538.42 | 1061.56 | 1066.71 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 945.29 | 657.62 | 287.67 | 733.68 | 1066.71 | 0.00 | 0.00 | 0.00 |
February | 1196.97 | 808.47 | 388.49 | 1061.56 | 913.18 | 0.00 | 0.00 | 0.00 |
March | 1054.67 | 667.46 | 387.21 | 960.04 | 773.68 | 0.00 | 0.00 | 0.00 |
April | 955.50 | 518.62 | 436.88 | 957.09 | 528.41 | 0.00 | 0.00 | 0.00 |
May | 803.33 | 274.64 | 528.69 | 884.46 | 297.04 | 0.00 | 0.00 | 0.00 |
June | 720.81 | 192.13 | 528.68 | 852.52 | 204.76 | 0.00 | 0.00 | 0.00 |
July | 788.08 | 249.66 | 538.42 | 979.14 | 184.64 | 0.00 | 0.00 | 0.00 |
August | 841.62 | 352.04 | 489.58 | 1011.79 | 217.64 | 0.00 | 0.00 | 0.00 |
September | 901.50 | 480.12 | 421.38 | 996.39 | 342.05 | 0.00 | 0.00 | 0.00 |
October | 769.82 | 452.77 | 317.05 | 736.21 | 506.67 | 0.00 | 0.00 | 0.00 |
November | 685.74 | 430.37 | 255.37 | 570.20 | 717.52 | 0.00 | 0.00 | 0.00 |
December | 729.88 | 478.59 | 251.29 | 514.89 | 1053.72 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 863.93 | 461.34 | 402.59 | 853.25 | 565.63 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 685.74 | 192.13 | 251.29 | 514.89 | 184.64 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1196.97 | 808.47 | 538.42 | 1061.56 | 1066.71 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 945.29 | 657.62 | 287.67 | 733.68 | 1066.71 | 0.00 | 0.00 | 0.00 |
February | 1196.97 | 808.47 | 388.49 | 1061.56 | 913.18 | 0.00 | 0.00 | 0.00 |
March | 1054.67 | 667.46 | 387.21 | 960.04 | 773.68 | 0.00 | 0.00 | 0.00 |
April | 955.50 | 518.62 | 436.88 | 957.09 | 528.41 | 0.00 | 0.00 | 0.00 |
May | 803.33 | 274.64 | 528.69 | 884.46 | 297.04 | 0.00 | 0.00 | 0.00 |
June | 720.81 | 192.13 | 528.68 | 852.52 | 204.76 | 0.00 | 0.00 | 0.00 |
July | 788.08 | 249.66 | 538.42 | 979.14 | 184.64 | 0.00 | 0.00 | 0.00 |
August | 841.62 | 352.04 | 489.58 | 1011.79 | 217.64 | 0.00 | 0.00 | 0.00 |
September | 901.50 | 480.12 | 421.38 | 996.39 | 342.05 | 0.00 | 0.00 | 0.00 |
October | 769.82 | 452.77 | 317.05 | 736.21 | 506.67 | 0.00 | 0.00 | 0.00 |
November | 685.74 | 430.37 | 255.37 | 570.20 | 717.52 | 0.00 | 0.00 | 0.00 |
December | 729.88 | 478.59 | 251.29 | 514.90 | 1053.72 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 863.93 | 461.34 | 402.59 | 853.25 | 565.63 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 685.74 | 192.13 | 251.29 | 514.90 | 184.64 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1196.97 | 808.47 | 538.42 | 1061.56 | 1066.71 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 945.29 | 657.62 | 287.67 | 733.68 | 1066.71 | 0.00 | 0.00 | 0.00 |
February | 1196.97 | 808.47 | 388.49 | 1061.56 | 913.18 | 0.00 | 0.00 | 0.00 |
March | 1054.67 | 667.46 | 387.21 | 960.04 | 773.68 | 0.00 | 0.00 | 0.00 |
April | 955.50 | 518.62 | 436.88 | 957.09 | 528.41 | 0.00 | 0.00 | 0.00 |
May | 803.33 | 274.64 | 528.69 | 884.46 | 297.04 | 0.00 | 0.00 | 0.00 |
June | 720.81 | 192.13 | 528.68 | 852.52 | 204.76 | 0.00 | 0.00 | 0.00 |
July | 788.08 | 249.66 | 538.42 | 979.14 | 184.64 | 0.00 | 0.00 | 0.00 |
August | 841.62 | 352.04 | 489.58 | 1011.79 | 217.64 | 0.00 | 0.00 | 0.00 |
September | 901.50 | 480.12 | 421.38 | 996.39 | 342.05 | 0.00 | 0.00 | 0.00 |
October | 769.82 | 452.77 | 317.05 | 736.21 | 506.67 | 0.00 | 0.00 | 0.00 |
November | 685.74 | 430.37 | 255.37 | 570.20 | 717.52 | 0.00 | 0.00 | 0.00 |
December | 729.88 | 478.59 | 251.29 | 514.89 | 1053.72 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 863.93 | 461.34 | 402.59 | 853.25 | 565.63 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 685.74 | 192.13 | 251.29 | 514.89 | 184.64 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1196.97 | 808.47 | 538.42 | 1061.56 | 1066.71 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 945.26 | 657.59 | 287.66 | 733.65 | 1066.67 | 0.00 | 0.00 | 0.00 |
February | 1196.92 | 808.44 | 388.48 | 1061.52 | 913.15 | 0.00 | 0.00 | 0.00 |
March | 1054.63 | 667.44 | 387.20 | 960.00 | 773.65 | 0.00 | 0.00 | 0.00 |
April | 955.46 | 518.60 | 436.86 | 957.06 | 528.39 | 0.00 | 0.00 | 0.00 |
May | 803.29 | 274.63 | 528.67 | 884.43 | 297.03 | 0.00 | 0.00 | 0.00 |
June | 720.78 | 192.12 | 528.66 | 852.49 | 204.75 | 0.00 | 0.00 | 0.00 |
July | 788.05 | 249.65 | 538.40 | 979.10 | 184.63 | 0.00 | 0.00 | 0.00 |
August | 841.59 | 352.03 | 489.56 | 1011.75 | 217.63 | 0.00 | 0.00 | 0.00 |
September | 901.47 | 480.10 | 421.37 | 996.35 | 342.04 | 0.00 | 0.00 | 0.00 |
October | 769.79 | 452.75 | 317.04 | 736.18 | 506.65 | 0.00 | 0.00 | 0.00 |
November | 685.71 | 430.35 | 255.36 | 570.18 | 717.49 | 0.00 | 0.00 | 0.00 |
December | 729.85 | 478.57 | 251.28 | 514.87 | 1053.68 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 863.90 | 461.33 | 402.57 | 853.22 | 565.61 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 685.71 | 192.12 | 251.28 | 514.87 | 184.63 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1196.92 | 808.44 | 538.40 | 1061.52 | 1066.67 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 337.99 | 141.53 | 196.46 | 118.82 | 1421.90 | 0.00 | 0.00 | 0.00 |
February | 550.68 | 251.51 | 299.17 | 314.98 | 1189.39 | 0.00 | 0.00 | 0.00 |
March | 724.65 | 370.80 | 353.85 | 513.72 | 981.45 | 0.00 | 0.00 | 0.00 |
April | 925.70 | 468.86 | 456.84 | 801.70 | 654.63 | 0.00 | 0.00 | 0.00 |
May | 1137.39 | 542.54 | 594.85 | 1217.18 | 347.48 | 0.00 | 0.00 | 0.00 |
June | 1097.55 | 474.57 | 622.98 | 1248.74 | 250.76 | 0.00 | 0.00 | 0.00 |
July | 1171.75 | 544.74 | 627.01 | 1382.00 | 234.93 | 0.00 | 0.00 | 0.00 |
August | 964.27 | 438.16 | 526.11 | 1091.40 | 279.72 | 0.00 | 0.00 | 0.00 |
September | 753.61 | 338.59 | 415.03 | 749.29 | 404.79 | 0.00 | 0.00 | 0.00 |
October | 476.06 | 191.11 | 284.95 | 342.47 | 639.41 | 0.00 | 0.00 | 0.00 |
November | 289.14 | 97.49 | 191.65 | 116.29 | 961.79 | 0.00 | 0.00 | 0.00 |
December | 257.75 | 90.21 | 167.54 | 60.65 | 1451.19 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 724.83 | 329.64 | 395.19 | 665.24 | 732.88 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 257.75 | 90.21 | 167.54 | 60.65 | 234.93 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1171.75 | 544.74 | 627.01 | 1382.00 | 1451.19 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 337.99 | 141.53 | 196.46 | 118.82 | 1421.90 | 0.00 | 0.00 | 0.00 |
February | 550.68 | 251.51 | 299.17 | 314.98 | 1189.39 | 0.00 | 0.00 | 0.00 |
March | 724.65 | 370.80 | 353.85 | 513.72 | 981.45 | 0.00 | 0.00 | 0.00 |
April | 925.70 | 468.86 | 456.84 | 801.70 | 654.63 | 0.00 | 0.00 | 0.00 |
May | 1137.39 | 542.54 | 594.85 | 1217.18 | 347.48 | 0.00 | 0.00 | 0.00 |
June | 1097.55 | 474.57 | 622.98 | 1248.74 | 250.76 | 0.00 | 0.00 | 0.00 |
July | 1171.75 | 544.74 | 627.01 | 1382.00 | 234.93 | 0.00 | 0.00 | 0.00 |
August | 964.27 | 438.16 | 526.11 | 1091.40 | 279.72 | 0.00 | 0.00 | 0.00 |
September | 753.61 | 338.59 | 415.03 | 749.29 | 404.79 | 0.00 | 0.00 | 0.00 |
October | 476.06 | 191.11 | 284.95 | 342.47 | 639.41 | 0.00 | 0.00 | 0.00 |
November | 289.14 | 97.49 | 191.65 | 116.29 | 961.79 | 0.00 | 0.00 | 0.00 |
December | 257.75 | 90.21 | 167.54 | 60.65 | 1451.19 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 724.83 | 329.64 | 395.19 | 665.24 | 732.88 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 257.75 | 90.21 | 167.54 | 60.65 | 234.93 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1171.75 | 544.74 | 627.01 | 1382.00 | 1451.19 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 337.98 | 141.53 | 196.45 | 118.82 | 1421.88 | 0.00 | 0.00 | 0.00 |
February | 550.67 | 251.51 | 299.16 | 314.98 | 1189.37 | 0.00 | 0.00 | 0.00 |
March | 724.64 | 370.79 | 353.84 | 513.71 | 981.43 | 0.00 | 0.00 | 0.00 |
April | 925.68 | 468.85 | 456.83 | 801.68 | 654.62 | 0.00 | 0.00 | 0.00 |
May | 1137.37 | 542.53 | 594.84 | 1217.16 | 347.47 | 0.00 | 0.00 | 0.00 |
June | 1097.53 | 474.57 | 622.97 | 1248.72 | 250.76 | 0.00 | 0.00 | 0.00 |
July | 1171.72 | 544.73 | 626.99 | 1381.97 | 234.92 | 0.00 | 0.00 | 0.00 |
August | 964.25 | 438.15 | 526.10 | 1091.38 | 279.72 | 0.00 | 0.00 | 0.00 |
September | 753.60 | 338.58 | 415.02 | 749.27 | 404.78 | 0.00 | 0.00 | 0.00 |
October | 476.05 | 191.11 | 284.94 | 342.46 | 639.39 | 0.00 | 0.00 | 0.00 |
November | 289.13 | 97.48 | 191.65 | 116.29 | 961.77 | 0.00 | 0.00 | 0.00 |
December | 257.74 | 90.21 | 167.53 | 60.65 | 1451.16 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 724.82 | 329.64 | 395.18 | 665.23 | 732.86 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 257.74 | 90.21 | 167.53 | 60.65 | 234.92 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1171.72 | 544.73 | 626.99 | 1381.97 | 1451.16 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 686.37 | 0.00 | 686.37 | 5.52 | 6514.93 | 0.00 | 0.00 | 0.00 |
February | 1054.32 | 0.00 | 1054.32 | 68.16 | 5202.72 | 0.00 | 0.00 | 0.00 |
March | 1297.16 | 0.00 | 1297.16 | 156.81 | 4082.91 | 0.00 | 0.00 | 0.00 |
April | 1700.50 | 13.27 | 1687.23 | 696.10 | 2449.95 | 0.00 | 0.00 | 0.00 |
May | 2391.69 | 128.79 | 2262.90 | 1970.44 | 1296.73 | 0.00 | 0.00 | 0.00 |
June | 2669.16 | 293.41 | 2375.75 | 2758.37 | 900.96 | 0.00 | 0.00 | 0.00 |
July | 2549.47 | 218.79 | 2330.68 | 2782.72 | 838.58 | 0.00 | 0.00 | 0.00 |
August | 1936.40 | 33.25 | 1903.15 | 1893.77 | 985.36 | 0.00 | 0.00 | 0.00 |
September | 1508.98 | 0.37 | 1508.61 | 1046.26 | 1612.66 | 0.00 | 0.00 | 0.00 |
October | 1047.76 | 0.00 | 1047.76 | 321.57 | 2486.13 | 0.00 | 0.00 | 0.00 |
November | 693.75 | 0.00 | 693.75 | 42.25 | 3836.88 | 0.00 | 0.00 | 0.00 |
December | 581.55 | 0.00 | 581.55 | 0.18 | 6242.75 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1512.04 | 57.58 | 1454.46 | 984.27 | 3028.93 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 581.55 | 0.00 | 581.55 | 0.18 | 838.58 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2669.16 | 293.41 | 2375.75 | 2782.72 | 6514.93 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1003.21 | 418.77 | 584.44 | 331.33 | 3920.64 | 0.00 | 0.00 | 0.00 |
February | 1576.45 | 672.44 | 904.01 | 843.14 | 3106.71 | 0.00 | 0.00 | 0.00 |
March | 2148.02 | 1077.48 | 1070.54 | 1491.78 | 2492.36 | 0.00 | 0.00 | 0.00 |
April | 2977.78 | 1606.15 | 1371.62 | 2676.61 | 1536.44 | 0.00 | 0.00 | 0.00 |
May | 3222.83 | 1416.79 | 1806.04 | 3354.19 | 869.15 | 0.00 | 0.00 | 0.00 |
June | 3648.47 | 1745.26 | 1903.20 | 4200.38 | 611.85 | 0.00 | 0.00 | 0.00 |
July | 3574.15 | 1678.20 | 1895.96 | 4243.32 | 563.51 | 0.00 | 0.00 | 0.00 |
August | 2755.68 | 1204.42 | 1551.25 | 3128.03 | 648.24 | 0.00 | 0.00 | 0.00 |
September | 2206.84 | 987.77 | 1219.07 | 2192.08 | 1015.47 | 0.00 | 0.00 | 0.00 |
October | 1336.28 | 506.71 | 829.56 | 947.12 | 1559.45 | 0.00 | 0.00 | 0.00 |
November | 850.69 | 284.40 | 566.28 | 362.18 | 2361.74 | 0.00 | 0.00 | 0.00 |
December | 776.24 | 286.91 | 489.33 | 204.47 | 3810.42 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 2175.24 | 991.24 | 1183.99 | 2003.43 | 1869.94 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 776.24 | 284.40 | 489.33 | 204.47 | 563.51 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 3648.47 | 1745.26 | 1903.20 | 4243.32 | 3920.64 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 4726.41 | 3288.06 | 1438.35 | 3672.91 | 5224.16 | 0.00 | 0.00 | 0.00 |
February | 5984.77 | 4042.32 | 1942.45 | 5300.59 | 4425.60 | 0.00 | 0.00 | 0.00 |
March | 5273.31 | 3337.27 | 1936.04 | 4790.89 | 3746.24 | 0.00 | 0.00 | 0.00 |
April | 4777.45 | 2593.07 | 2184.38 | 4784.20 | 2517.54 | 0.00 | 0.00 | 0.00 |
May | 4016.58 | 1373.17 | 2643.41 | 4404.27 | 1447.63 | 0.00 | 0.00 | 0.00 |
June | 3604.00 | 960.62 | 2643.37 | 4257.80 | 989.35 | 0.00 | 0.00 | 0.00 |
July | 3940.34 | 1248.28 | 2692.06 | 4881.84 | 914.15 | 0.00 | 0.00 | 0.00 |
August | 4208.06 | 1760.20 | 2447.86 | 5044.34 | 1063.50 | 0.00 | 0.00 | 0.00 |
September | 4507.46 | 2400.56 | 2106.90 | 4958.10 | 1664.76 | 0.00 | 0.00 | 0.00 |
October | 3849.05 | 2263.82 | 1585.23 | 3689.75 | 2420.85 | 0.00 | 0.00 | 0.00 |
November | 3428.65 | 2151.83 | 1276.83 | 2872.59 | 3392.78 | 0.00 | 0.00 | 0.00 |
December | 3649.36 | 2392.93 | 1256.43 | 2598.49 | 5076.42 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 4319.61 | 2306.69 | 2012.91 | 4263.44 | 2732.96 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 3428.65 | 960.62 | 1256.43 | 2598.49 | 914.15 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 5984.77 | 4042.32 | 2692.06 | 5300.59 | 5224.16 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1013.95 | 424.58 | 589.37 | 372.62 | 4050.26 | 0.00 | 0.00 | 0.00 |
February | 1652.02 | 754.53 | 897.49 | 986.49 | 3280.22 | 0.00 | 0.00 | 0.00 |
March | 2173.93 | 1112.39 | 1061.54 | 1596.57 | 2639.52 | 0.00 | 0.00 | 0.00 |
April | 2777.07 | 1406.56 | 1370.51 | 2495.49 | 1677.88 | 0.00 | 0.00 | 0.00 |
May | 3412.13 | 1627.60 | 1784.53 | 3678.36 | 974.17 | 0.00 | 0.00 | 0.00 |
June | 3292.63 | 1423.71 | 1868.92 | 3788.48 | 677.45 | 0.00 | 0.00 | 0.00 |
July | 3515.20 | 1634.20 | 1881.00 | 4182.44 | 646.38 | 0.00 | 0.00 | 0.00 |
August | 2892.78 | 1314.46 | 1578.32 | 3329.67 | 731.64 | 0.00 | 0.00 | 0.00 |
September | 2260.81 | 1015.75 | 1245.06 | 2290.80 | 1103.06 | 0.00 | 0.00 | 0.00 |
October | 1428.17 | 573.33 | 854.84 | 1094.26 | 1655.32 | 0.00 | 0.00 | 0.00 |
November | 867.40 | 292.45 | 574.95 | 390.38 | 2467.02 | 0.00 | 0.00 | 0.00 |
December | 773.24 | 270.64 | 502.60 | 200.89 | 3932.22 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 2174.48 | 988.92 | 1185.56 | 2040.21 | 1981.16 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 773.24 | 270.64 | 502.60 | 200.89 | 646.38 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 3515.20 | 1634.20 | 1881.00 | 4182.44 | 4050.26 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 686.37 | 0.00 | 686.37 | 7.34 | 6425.51 | 0.00 | 0.00 | 0.00 |
February | 1054.32 | 0.00 | 1054.32 | 75.27 | 5089.89 | 0.00 | 0.00 | 0.00 |
March | 1297.16 | 0.00 | 1297.16 | 175.55 | 3939.57 | 0.00 | 0.00 | 0.00 |
April | 1700.50 | 13.27 | 1687.23 | 746.54 | 2296.59 | 0.00 | 0.00 | 0.00 |
May | 2391.69 | 128.79 | 2262.90 | 2005.21 | 1238.50 | 0.00 | 0.00 | 0.00 |
June | 2669.16 | 293.41 | 2375.75 | 2771.51 | 871.20 | 0.00 | 0.00 | 0.00 |
July | 2549.47 | 218.79 | 2330.68 | 2785.64 | 821.67 | 0.00 | 0.00 | 0.00 |
August | 1936.40 | 33.25 | 1903.15 | 1903.18 | 952.90 | 0.00 | 0.00 | 0.00 |
September | 1508.98 | 0.37 | 1508.61 | 1088.49 | 1511.67 | 0.00 | 0.00 | 0.00 |
October | 1047.76 | 0.00 | 1047.76 | 367.97 | 2286.84 | 0.00 | 0.00 | 0.00 |
November | 693.75 | 0.00 | 693.75 | 50.82 | 3658.63 | 0.00 | 0.00 | 0.00 |
December | 581.55 | 0.00 | 581.55 | 0.39 | 6136.75 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1512.04 | 57.58 | 1454.46 | 1003.92 | 2927.43 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 581.55 | 0.00 | 581.55 | 0.39 | 821.67 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2669.16 | 293.41 | 2375.75 | 2785.64 | 6425.51 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1003.21 | 418.77 | 584.44 | 335.60 | 3869.70 | 0.00 | 0.00 | 0.00 |
February | 1576.45 | 672.44 | 904.01 | 856.85 | 3039.18 | 0.00 | 0.00 | 0.00 |
March | 2148.02 | 1077.48 | 1070.54 | 1515.71 | 2403.14 | 0.00 | 0.00 | 0.00 |
April | 2977.78 | 1606.15 | 1371.62 | 2706.63 | 1453.09 | 0.00 | 0.00 | 0.00 |
May | 3222.83 | 1416.79 | 1806.04 | 3364.27 | 840.06 | 0.00 | 0.00 | 0.00 |
June | 3648.47 | 1745.26 | 1903.20 | 4197.47 | 596.61 | 0.00 | 0.00 | 0.00 |
July | 3574.15 | 1678.20 | 1895.96 | 4237.62 | 555.74 | 0.00 | 0.00 | 0.00 |
August | 2755.68 | 1204.42 | 1551.25 | 3124.93 | 634.29 | 0.00 | 0.00 | 0.00 |
September | 2206.84 | 987.77 | 1219.07 | 2209.13 | 968.48 | 0.00 | 0.00 | 0.00 |
October | 1336.28 | 506.71 | 829.56 | 977.98 | 1450.53 | 0.00 | 0.00 | 0.00 |
November | 850.69 | 284.40 | 566.28 | 375.87 | 2249.83 | 0.00 | 0.00 | 0.00 |
December | 776.24 | 286.91 | 489.33 | 207.92 | 3748.05 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 2175.24 | 991.24 | 1183.99 | 2014.66 | 1812.83 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 776.24 | 284.40 | 489.33 | 207.92 | 555.74 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 3648.47 | 1745.26 | 1903.20 | 4237.62 | 3869.70 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 4726.41 | 3288.06 | 1438.35 | 3690.92 | 5134.81 | 0.00 | 0.00 | 0.00 |
February | 5984.77 | 4042.32 | 1942.45 | 5331.09 | 4299.67 | 0.00 | 0.00 | 0.00 |
March | 5273.31 | 3337.27 | 1936.04 | 4825.49 | 3597.54 | 0.00 | 0.00 | 0.00 |
April | 4777.45 | 2593.07 | 2184.38 | 4821.32 | 2374.68 | 0.00 | 0.00 | 0.00 |
May | 4016.58 | 1373.17 | 2643.41 | 4417.36 | 1390.68 | 0.00 | 0.00 | 0.00 |
June | 3604.00 | 960.62 | 2643.37 | 4262.40 | 957.15 | 0.00 | 0.00 | 0.00 |
July | 3940.34 | 1248.28 | 2692.06 | 4877.42 | 895.41 | 0.00 | 0.00 | 0.00 |
August | 4208.06 | 1760.20 | 2447.86 | 5041.62 | 1034.78 | 0.00 | 0.00 | 0.00 |
September | 4507.46 | 2400.56 | 2106.90 | 4980.18 | 1582.66 | 0.00 | 0.00 | 0.00 |
October | 3849.05 | 2263.82 | 1585.23 | 3741.81 | 2247.93 | 0.00 | 0.00 | 0.00 |
November | 3428.65 | 2151.83 | 1276.83 | 2916.18 | 3212.53 | 0.00 | 0.00 | 0.00 |
December | 3649.36 | 2392.93 | 1256.43 | 2621.22 | 4974.19 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 4319.61 | 2306.69 | 2012.91 | 4285.93 | 2634.90 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 3428.65 | 960.62 | 1256.43 | 2621.22 | 895.41 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 5984.77 | 4042.32 | 2692.06 | 5331.09 | 5134.81 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1013.95 | 424.58 | 589.37 | 375.33 | 3996.60 | 0.00 | 0.00 | 0.00 |
February | 1652.02 | 754.53 | 897.49 | 992.36 | 3211.27 | 0.00 | 0.00 | 0.00 |
March | 2173.93 | 1112.39 | 1061.54 | 1608.07 | 2552.93 | 0.00 | 0.00 | 0.00 |
April | 2777.07 | 1406.56 | 1370.51 | 2515.47 | 1594.05 | 0.00 | 0.00 | 0.00 |
May | 3412.13 | 1627.60 | 1784.53 | 3685.60 | 941.32 | 0.00 | 0.00 | 0.00 |
June | 3292.63 | 1423.71 | 1868.92 | 3789.07 | 659.42 | 0.00 | 0.00 | 0.00 |
July | 3515.20 | 1634.20 | 1881.00 | 4177.02 | 635.35 | 0.00 | 0.00 | 0.00 |
August | 2892.78 | 1314.46 | 1578.32 | 3328.77 | 714.06 | 0.00 | 0.00 | 0.00 |
September | 2260.81 | 1015.75 | 1245.06 | 2305.28 | 1054.92 | 0.00 | 0.00 | 0.00 |
October | 1428.17 | 573.33 | 854.84 | 1115.80 | 1554.90 | 0.00 | 0.00 | 0.00 |
November | 867.40 | 292.45 | 574.95 | 401.48 | 2363.77 | 0.00 | 0.00 | 0.00 |
December | 773.24 | 270.64 | 502.60 | 202.87 | 3875.75 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 2174.48 | 988.92 | 1185.56 | 2047.73 | 1924.60 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 773.24 | 270.64 | 502.60 | 202.87 | 635.35 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 3515.20 | 1634.20 | 1881.00 | 4177.02 | 3996.60 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.367681E+09 | 0.00 | 0.367681E+09 | 694538.71 | 0.363505E+10 |
February | 0.510130E+09 | 0.00 | 0.510130E+09 | 18341653.02 | 0.268482E+10 |
March | 0.694872E+09 | 0.00 | 0.694872E+09 | 61753351.75 | 0.237134E+10 |
April | 0.881549E+09 | 6880384.05 | 0.874669E+09 | 0.312417E+09 | 0.142085E+10 |
May | 0.128119E+10 | 68990411.35 | 0.121220E+10 | 0.103832E+10 | 0.731170E+09 |
June | 0.138371E+10 | 0.152107E+09 | 0.123160E+10 | 0.141852E+10 | 0.489516E+09 |
July | 0.136572E+10 | 0.117204E+09 | 0.124851E+10 | 0.148055E+10 | 0.462263E+09 |
August | 0.103730E+10 | 17813684.08 | 0.101949E+10 | 0.995191E+09 | 0.560433E+09 |
September | 0.782265E+09 | 191758.42 | 0.782073E+09 | 0.520267E+09 | 0.900666E+09 |
October | 0.561271E+09 | 0.00 | 0.561271E+09 | 0.136133E+09 | 0.150216E+10 |
November | 0.359644E+09 | 0.00 | 0.359644E+09 | 14356729.36 | 0.223661E+10 |
December | 0.311529E+09 | 0.00 | 0.311529E+09 | 0.00 | 0.355235E+10 |
Annual Sum or Average | 0.953687E+10 | 0.363187E+09 | 0.917368E+10 | 0.599655E+10 | 0.205472E+11 |
Minimum of Months | 0.311529E+09 | 0.00 | 0.311529E+09 | 0.00 | 0.462263E+09 |
Maximum of Months | 0.138371E+10 | 0.152107E+09 | 0.124851E+10 | 0.148055E+10 | 0.363505E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.367681E+09 | 0.00 | 0.367681E+09 | 694533.47 | 0.363505E+10 |
February | 0.510130E+09 | 0.00 | 0.510130E+09 | 18341576.26 | 0.268482E+10 |
March | 0.694871E+09 | 0.00 | 0.694871E+09 | 61753152.55 | 0.237134E+10 |
April | 0.881548E+09 | 6880375.79 | 0.874668E+09 | 0.312416E+09 | 0.142085E+10 |
May | 0.128119E+10 | 68990328.57 | 0.121220E+10 | 0.103832E+10 | 0.731170E+09 |
June | 0.138371E+10 | 0.152106E+09 | 0.123160E+10 | 0.141852E+10 | 0.489516E+09 |
July | 0.136571E+10 | 0.117204E+09 | 0.124851E+10 | 0.148055E+10 | 0.462263E+09 |
August | 0.103730E+10 | 17813662.71 | 0.101949E+10 | 0.995190E+09 | 0.560433E+09 |
September | 0.782265E+09 | 191758.19 | 0.782073E+09 | 0.520267E+09 | 0.900666E+09 |
October | 0.561270E+09 | 0.00 | 0.561270E+09 | 0.136133E+09 | 0.150216E+10 |
November | 0.359644E+09 | 0.00 | 0.359644E+09 | 14356686.53 | 0.223661E+10 |
December | 0.311529E+09 | 0.00 | 0.311529E+09 | 0.00 | 0.355235E+10 |
Annual Sum or Average | 0.953686E+10 | 0.363187E+09 | 0.917367E+10 | 0.599654E+10 | 0.205472E+11 |
Minimum of Months | 0.311529E+09 | 0.00 | 0.311529E+09 | 0.00 | 0.462263E+09 |
Maximum of Months | 0.138371E+10 | 0.152106E+09 | 0.124851E+10 | 0.148055E+10 | 0.363505E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.367681E+09 | 0.00 | 0.367681E+09 | 694538.71 | 0.363505E+10 |
February | 0.510130E+09 | 0.00 | 0.510130E+09 | 18341653.02 | 0.268482E+10 |
March | 0.694872E+09 | 0.00 | 0.694872E+09 | 61753351.75 | 0.237134E+10 |
April | 0.881549E+09 | 6880384.05 | 0.874669E+09 | 0.312417E+09 | 0.142085E+10 |
May | 0.128119E+10 | 68990411.35 | 0.121220E+10 | 0.103832E+10 | 0.731170E+09 |
June | 0.138371E+10 | 0.152107E+09 | 0.123160E+10 | 0.141852E+10 | 0.489516E+09 |
July | 0.136572E+10 | 0.117204E+09 | 0.124851E+10 | 0.148055E+10 | 0.462263E+09 |
August | 0.103730E+10 | 17813684.08 | 0.101949E+10 | 0.995191E+09 | 0.560433E+09 |
September | 0.782265E+09 | 191758.42 | 0.782073E+09 | 0.520267E+09 | 0.900666E+09 |
October | 0.561271E+09 | 0.00 | 0.561271E+09 | 0.136133E+09 | 0.150216E+10 |
November | 0.359644E+09 | 0.00 | 0.359644E+09 | 14356729.36 | 0.223661E+10 |
December | 0.311529E+09 | 0.00 | 0.311529E+09 | 0.00 | 0.355235E+10 |
Annual Sum or Average | 0.953687E+10 | 0.363187E+09 | 0.917368E+10 | 0.599655E+10 | 0.205472E+11 |
Minimum of Months | 0.311529E+09 | 0.00 | 0.311529E+09 | 0.00 | 0.462263E+09 |
Maximum of Months | 0.138371E+10 | 0.152107E+09 | 0.124851E+10 | 0.148055E+10 | 0.363505E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.367681E+09 | 0.00 | 0.367681E+09 | 694533.47 | 0.363505E+10 |
February | 0.510130E+09 | 0.00 | 0.510130E+09 | 18341576.26 | 0.268482E+10 |
March | 0.694871E+09 | 0.00 | 0.694871E+09 | 61753152.55 | 0.237134E+10 |
April | 0.881548E+09 | 6880375.79 | 0.874668E+09 | 0.312416E+09 | 0.142085E+10 |
May | 0.128119E+10 | 68990328.57 | 0.121220E+10 | 0.103832E+10 | 0.731170E+09 |
June | 0.138371E+10 | 0.152106E+09 | 0.123160E+10 | 0.141852E+10 | 0.489516E+09 |
July | 0.136571E+10 | 0.117204E+09 | 0.124851E+10 | 0.148055E+10 | 0.462263E+09 |
August | 0.103730E+10 | 17813662.71 | 0.101949E+10 | 0.995190E+09 | 0.560433E+09 |
September | 0.782265E+09 | 191758.19 | 0.782073E+09 | 0.520267E+09 | 0.900666E+09 |
October | 0.561270E+09 | 0.00 | 0.561270E+09 | 0.136133E+09 | 0.150216E+10 |
November | 0.359644E+09 | 0.00 | 0.359644E+09 | 14356686.53 | 0.223661E+10 |
December | 0.311529E+09 | 0.00 | 0.311529E+09 | 0.00 | 0.355235E+10 |
Annual Sum or Average | 0.953686E+10 | 0.363187E+09 | 0.917367E+10 | 0.599654E+10 | 0.205472E+11 |
Minimum of Months | 0.311529E+09 | 0.00 | 0.311529E+09 | 0.00 | 0.462263E+09 |
Maximum of Months | 0.138371E+10 | 0.152106E+09 | 0.124851E+10 | 0.148055E+10 | 0.363505E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.367667E+09 | 0.00 | 0.367667E+09 | 694510.71 | 0.363490E+10 |
February | 0.510110E+09 | 0.00 | 0.510110E+09 | 18340913.77 | 0.268471E+10 |
March | 0.694844E+09 | 0.00 | 0.694844E+09 | 61750862.82 | 0.237124E+10 |
April | 0.881513E+09 | 6880106.74 | 0.874633E+09 | 0.312404E+09 | 0.142079E+10 |
May | 0.128114E+10 | 68987630.74 | 0.121216E+10 | 0.103828E+10 | 0.731140E+09 |
June | 0.138365E+10 | 0.152101E+09 | 0.123155E+10 | 0.141846E+10 | 0.489496E+09 |
July | 0.136566E+10 | 0.117200E+09 | 0.124846E+10 | 0.148049E+10 | 0.462245E+09 |
August | 0.103726E+10 | 17812966.11 | 0.101945E+10 | 0.995151E+09 | 0.560411E+09 |
September | 0.782234E+09 | 191750.69 | 0.782042E+09 | 0.520247E+09 | 0.900630E+09 |
October | 0.561248E+09 | 0.00 | 0.561248E+09 | 0.136128E+09 | 0.150210E+10 |
November | 0.359630E+09 | 0.00 | 0.359630E+09 | 14356150.72 | 0.223652E+10 |
December | 0.311517E+09 | 0.00 | 0.311517E+09 | 0.00 | 0.355221E+10 |
Annual Sum or Average | 0.953648E+10 | 0.363173E+09 | 0.917331E+10 | 0.599630E+10 | 0.205464E+11 |
Minimum of Months | 0.311517E+09 | 0.00 | 0.311517E+09 | 0.00 | 0.462245E+09 |
Maximum of Months | 0.138365E+10 | 0.152101E+09 | 0.124846E+10 | 0.148049E+10 | 0.363490E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.895674E+09 | 0.373882E+09 | 0.521792E+09 | 0.286043E+09 | 0.362748E+10 |
February | 0.127126E+10 | 0.542265E+09 | 0.729000E+09 | 0.651423E+09 | 0.264846E+10 |
March | 0.191777E+10 | 0.961982E+09 | 0.955788E+09 | 0.131315E+10 | 0.235858E+10 |
April | 0.257282E+10 | 0.138773E+10 | 0.118509E+10 | 0.229924E+10 | 0.142223E+10 |
May | 0.287737E+10 | 0.126492E+10 | 0.161245E+10 | 0.300549E+10 | 0.804851E+09 |
June | 0.315231E+10 | 0.150792E+10 | 0.164438E+10 | 0.364623E+10 | 0.543678E+09 |
July | 0.319104E+10 | 0.149831E+10 | 0.169273E+10 | 0.380971E+10 | 0.496826E+09 |
August | 0.246029E+10 | 0.107532E+10 | 0.138497E+10 | 0.280249E+10 | 0.582407E+09 |
September | 0.190673E+10 | 0.853441E+09 | 0.105329E+10 | 0.188391E+10 | 0.929648E+09 |
October | 0.119304E+10 | 0.452399E+09 | 0.740643E+09 | 0.813400E+09 | 0.152184E+10 |
November | 0.735000E+09 | 0.245727E+09 | 0.489272E+09 | 0.294969E+09 | 0.223929E+10 |
December | 0.693036E+09 | 0.256157E+09 | 0.436879E+09 | 0.173496E+09 | 0.357598E+10 |
Annual Sum or Average | 0.228663E+11 | 0.104201E+11 | 0.124463E+11 | 0.209795E+11 | 0.207513E+11 |
Minimum of Months | 0.693036E+09 | 0.245727E+09 | 0.436879E+09 | 0.173496E+09 | 0.496826E+09 |
Maximum of Months | 0.319104E+10 | 0.150792E+10 | 0.169273E+10 | 0.380971E+10 | 0.362748E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.895674E+09 | 0.373882E+09 | 0.521792E+09 | 0.286043E+09 | 0.362748E+10 |
February | 0.127126E+10 | 0.542265E+09 | 0.729000E+09 | 0.651423E+09 | 0.264846E+10 |
March | 0.191777E+10 | 0.961982E+09 | 0.955788E+09 | 0.131315E+10 | 0.235858E+10 |
April | 0.257282E+10 | 0.138773E+10 | 0.118509E+10 | 0.229924E+10 | 0.142223E+10 |
May | 0.287737E+10 | 0.126492E+10 | 0.161245E+10 | 0.300549E+10 | 0.804851E+09 |
June | 0.315231E+10 | 0.150792E+10 | 0.164438E+10 | 0.364623E+10 | 0.543678E+09 |
July | 0.319104E+10 | 0.149831E+10 | 0.169273E+10 | 0.380971E+10 | 0.496826E+09 |
August | 0.246029E+10 | 0.107532E+10 | 0.138497E+10 | 0.280249E+10 | 0.582407E+09 |
September | 0.190673E+10 | 0.853441E+09 | 0.105329E+10 | 0.188391E+10 | 0.929648E+09 |
October | 0.119304E+10 | 0.452399E+09 | 0.740643E+09 | 0.813400E+09 | 0.152184E+10 |
November | 0.735000E+09 | 0.245727E+09 | 0.489272E+09 | 0.294969E+09 | 0.223929E+10 |
December | 0.693036E+09 | 0.256157E+09 | 0.436879E+09 | 0.173496E+09 | 0.357598E+10 |
Annual Sum or Average | 0.228663E+11 | 0.104201E+11 | 0.124463E+11 | 0.209795E+11 | 0.207513E+11 |
Minimum of Months | 0.693036E+09 | 0.245727E+09 | 0.436879E+09 | 0.173496E+09 | 0.496826E+09 |
Maximum of Months | 0.319104E+10 | 0.150792E+10 | 0.169273E+10 | 0.380971E+10 | 0.362748E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.895658E+09 | 0.373875E+09 | 0.521782E+09 | 0.286038E+09 | 0.362742E+10 |
February | 0.127124E+10 | 0.542255E+09 | 0.728987E+09 | 0.651411E+09 | 0.264841E+10 |
March | 0.191774E+10 | 0.961965E+09 | 0.955771E+09 | 0.131312E+10 | 0.235854E+10 |
April | 0.257278E+10 | 0.138771E+10 | 0.118507E+10 | 0.229920E+10 | 0.142220E+10 |
May | 0.287732E+10 | 0.126490E+10 | 0.161242E+10 | 0.300544E+10 | 0.804837E+09 |
June | 0.315225E+10 | 0.150790E+10 | 0.164435E+10 | 0.364616E+10 | 0.543668E+09 |
July | 0.319098E+10 | 0.149828E+10 | 0.169270E+10 | 0.380964E+10 | 0.496817E+09 |
August | 0.246025E+10 | 0.107530E+10 | 0.138495E+10 | 0.280244E+10 | 0.582396E+09 |
September | 0.190669E+10 | 0.853425E+09 | 0.105327E+10 | 0.188387E+10 | 0.929631E+09 |
October | 0.119302E+10 | 0.452391E+09 | 0.740629E+09 | 0.813385E+09 | 0.152181E+10 |
November | 0.734986E+09 | 0.245723E+09 | 0.489263E+09 | 0.294964E+09 | 0.223925E+10 |
December | 0.693024E+09 | 0.256153E+09 | 0.436871E+09 | 0.173493E+09 | 0.357591E+10 |
Annual Sum or Average | 0.228659E+11 | 0.104199E+11 | 0.124461E+11 | 0.209792E+11 | 0.207509E+11 |
Minimum of Months | 0.693024E+09 | 0.245723E+09 | 0.436871E+09 | 0.173493E+09 | 0.496817E+09 |
Maximum of Months | 0.319098E+10 | 0.150790E+10 | 0.169270E+10 | 0.380964E+10 | 0.362742E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.253188E+10 | 0.176137E+10 | 0.770506E+09 | 0.196508E+10 | 0.285708E+10 |
February | 0.289571E+10 | 0.195586E+10 | 0.939845E+09 | 0.256814E+10 | 0.220917E+10 |
March | 0.282484E+10 | 0.178773E+10 | 0.103711E+10 | 0.257137E+10 | 0.207223E+10 |
April | 0.247666E+10 | 0.134426E+10 | 0.113240E+10 | 0.248079E+10 | 0.136964E+10 |
May | 0.215163E+10 | 0.735590E+09 | 0.141604E+10 | 0.236895E+10 | 0.795585E+09 |
June | 0.186833E+10 | 0.497993E+09 | 0.137034E+10 | 0.220974E+10 | 0.530727E+09 |
July | 0.211079E+10 | 0.668687E+09 | 0.144210E+10 | 0.262252E+10 | 0.494527E+09 |
August | 0.225420E+10 | 0.942914E+09 | 0.131128E+10 | 0.270997E+10 | 0.582925E+09 |
September | 0.233669E+10 | 0.124446E+10 | 0.109223E+10 | 0.258265E+10 | 0.886591E+09 |
October | 0.206188E+10 | 0.121270E+10 | 0.849187E+09 | 0.197187E+10 | 0.135707E+10 |
November | 0.177744E+10 | 0.111552E+10 | 0.661915E+09 | 0.147796E+10 | 0.185981E+10 |
December | 0.195491E+10 | 0.128186E+10 | 0.673052E+09 | 0.137910E+10 | 0.282229E+10 |
Annual Sum or Average | 0.272450E+11 | 0.145489E+11 | 0.126960E+11 | 0.269081E+11 | 0.178376E+11 |
Minimum of Months | 0.177744E+10 | 0.497993E+09 | 0.661915E+09 | 0.137910E+10 | 0.494527E+09 |
Maximum of Months | 0.289571E+10 | 0.195586E+10 | 0.144210E+10 | 0.270997E+10 | 0.285708E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.253187E+10 | 0.176137E+10 | 0.770505E+09 | 0.196508E+10 | 0.285708E+10 |
February | 0.289570E+10 | 0.195586E+10 | 0.939844E+09 | 0.256813E+10 | 0.220917E+10 |
March | 0.282484E+10 | 0.178773E+10 | 0.103711E+10 | 0.257136E+10 | 0.207223E+10 |
April | 0.247666E+10 | 0.134426E+10 | 0.113240E+10 | 0.248079E+10 | 0.136964E+10 |
May | 0.215163E+10 | 0.735590E+09 | 0.141604E+10 | 0.236894E+10 | 0.795585E+09 |
June | 0.186833E+10 | 0.497993E+09 | 0.137034E+10 | 0.220974E+10 | 0.530727E+09 |
July | 0.211078E+10 | 0.668686E+09 | 0.144210E+10 | 0.262252E+10 | 0.494527E+09 |
August | 0.225420E+10 | 0.942913E+09 | 0.131128E+10 | 0.270997E+10 | 0.582925E+09 |
September | 0.233669E+10 | 0.124446E+10 | 0.109223E+10 | 0.258264E+10 | 0.886591E+09 |
October | 0.206188E+10 | 0.121270E+10 | 0.849186E+09 | 0.197186E+10 | 0.135707E+10 |
November | 0.177743E+10 | 0.111552E+10 | 0.661914E+09 | 0.147796E+10 | 0.185981E+10 |
December | 0.195491E+10 | 0.128186E+10 | 0.673052E+09 | 0.137909E+10 | 0.282229E+10 |
Annual Sum or Average | 0.272449E+11 | 0.145489E+11 | 0.126960E+11 | 0.269081E+11 | 0.178376E+11 |
Minimum of Months | 0.177743E+10 | 0.497993E+09 | 0.661914E+09 | 0.137909E+10 | 0.494527E+09 |
Maximum of Months | 0.289570E+10 | 0.195586E+10 | 0.144210E+10 | 0.270997E+10 | 0.285708E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.253188E+10 | 0.176137E+10 | 0.770506E+09 | 0.196508E+10 | 0.285708E+10 |
February | 0.289571E+10 | 0.195586E+10 | 0.939845E+09 | 0.256814E+10 | 0.220917E+10 |
March | 0.282484E+10 | 0.178773E+10 | 0.103711E+10 | 0.257137E+10 | 0.207223E+10 |
April | 0.247666E+10 | 0.134426E+10 | 0.113240E+10 | 0.248079E+10 | 0.136964E+10 |
May | 0.215163E+10 | 0.735590E+09 | 0.141604E+10 | 0.236895E+10 | 0.795585E+09 |
June | 0.186833E+10 | 0.497993E+09 | 0.137034E+10 | 0.220974E+10 | 0.530727E+09 |
July | 0.211079E+10 | 0.668687E+09 | 0.144210E+10 | 0.262252E+10 | 0.494527E+09 |
August | 0.225420E+10 | 0.942914E+09 | 0.131128E+10 | 0.270997E+10 | 0.582925E+09 |
September | 0.233669E+10 | 0.124446E+10 | 0.109223E+10 | 0.258265E+10 | 0.886591E+09 |
October | 0.206188E+10 | 0.121270E+10 | 0.849187E+09 | 0.197187E+10 | 0.135707E+10 |
November | 0.177744E+10 | 0.111552E+10 | 0.661915E+09 | 0.147796E+10 | 0.185981E+10 |
December | 0.195491E+10 | 0.128186E+10 | 0.673052E+09 | 0.137910E+10 | 0.282229E+10 |
Annual Sum or Average | 0.272450E+11 | 0.145489E+11 | 0.126960E+11 | 0.269081E+11 | 0.178376E+11 |
Minimum of Months | 0.177744E+10 | 0.497993E+09 | 0.661915E+09 | 0.137910E+10 | 0.494527E+09 |
Maximum of Months | 0.289571E+10 | 0.195586E+10 | 0.144210E+10 | 0.270997E+10 | 0.285708E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.253187E+10 | 0.176137E+10 | 0.770505E+09 | 0.196508E+10 | 0.285708E+10 |
February | 0.289570E+10 | 0.195586E+10 | 0.939844E+09 | 0.256813E+10 | 0.220917E+10 |
March | 0.282484E+10 | 0.178773E+10 | 0.103711E+10 | 0.257136E+10 | 0.207223E+10 |
April | 0.247666E+10 | 0.134426E+10 | 0.113240E+10 | 0.248079E+10 | 0.136964E+10 |
May | 0.215163E+10 | 0.735590E+09 | 0.141604E+10 | 0.236894E+10 | 0.795585E+09 |
June | 0.186833E+10 | 0.497993E+09 | 0.137034E+10 | 0.220974E+10 | 0.530727E+09 |
July | 0.211078E+10 | 0.668686E+09 | 0.144210E+10 | 0.262252E+10 | 0.494527E+09 |
August | 0.225420E+10 | 0.942913E+09 | 0.131128E+10 | 0.270997E+10 | 0.582925E+09 |
September | 0.233669E+10 | 0.124446E+10 | 0.109223E+10 | 0.258264E+10 | 0.886591E+09 |
October | 0.206188E+10 | 0.121270E+10 | 0.849186E+09 | 0.197186E+10 | 0.135707E+10 |
November | 0.177743E+10 | 0.111552E+10 | 0.661914E+09 | 0.147796E+10 | 0.185981E+10 |
December | 0.195491E+10 | 0.128186E+10 | 0.673052E+09 | 0.137909E+10 | 0.282229E+10 |
Annual Sum or Average | 0.272449E+11 | 0.145489E+11 | 0.126960E+11 | 0.269081E+11 | 0.178376E+11 |
Minimum of Months | 0.177743E+10 | 0.497993E+09 | 0.661914E+09 | 0.137909E+10 | 0.494527E+09 |
Maximum of Months | 0.289570E+10 | 0.195586E+10 | 0.144210E+10 | 0.270997E+10 | 0.285708E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.253177E+10 | 0.176130E+10 | 0.770475E+09 | 0.196500E+10 | 0.285697E+10 |
February | 0.289559E+10 | 0.195578E+10 | 0.939807E+09 | 0.256803E+10 | 0.220908E+10 |
March | 0.282473E+10 | 0.178766E+10 | 0.103707E+10 | 0.257126E+10 | 0.207215E+10 |
April | 0.247656E+10 | 0.134421E+10 | 0.113235E+10 | 0.248069E+10 | 0.136958E+10 |
May | 0.215154E+10 | 0.735561E+09 | 0.141598E+10 | 0.236885E+10 | 0.795553E+09 |
June | 0.186826E+10 | 0.497973E+09 | 0.137029E+10 | 0.220965E+10 | 0.530706E+09 |
July | 0.211070E+10 | 0.668660E+09 | 0.144204E+10 | 0.262242E+10 | 0.494507E+09 |
August | 0.225411E+10 | 0.942876E+09 | 0.131123E+10 | 0.270986E+10 | 0.582902E+09 |
September | 0.233660E+10 | 0.124441E+10 | 0.109219E+10 | 0.258254E+10 | 0.886556E+09 |
October | 0.206180E+10 | 0.121265E+10 | 0.849153E+09 | 0.197179E+10 | 0.135702E+10 |
November | 0.177736E+10 | 0.111548E+10 | 0.661888E+09 | 0.147790E+10 | 0.185974E+10 |
December | 0.195483E+10 | 0.128181E+10 | 0.673025E+09 | 0.137904E+10 | 0.282217E+10 |
Annual Sum or Average | 0.272439E+11 | 0.145484E+11 | 0.126955E+11 | 0.269070E+11 | 0.178369E+11 |
Minimum of Months | 0.177736E+10 | 0.497973E+09 | 0.661888E+09 | 0.137904E+10 | 0.494507E+09 |
Maximum of Months | 0.289559E+10 | 0.195578E+10 | 0.144204E+10 | 0.270986E+10 | 0.285697E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.905261E+09 | 0.379070E+09 | 0.526191E+09 | 0.318251E+09 | 0.380842E+10 |
February | 0.133220E+10 | 0.608461E+09 | 0.723740E+09 | 0.762003E+09 | 0.287737E+10 |
March | 0.194090E+10 | 0.993147E+09 | 0.947756E+09 | 0.137594E+10 | 0.262872E+10 |
April | 0.239942E+10 | 0.121528E+10 | 0.118414E+10 | 0.207800E+10 | 0.169680E+10 |
May | 0.304638E+10 | 0.145314E+10 | 0.159324E+10 | 0.326009E+10 | 0.930688E+09 |
June | 0.284486E+10 | 0.123010E+10 | 0.161477E+10 | 0.323674E+10 | 0.649972E+09 |
July | 0.313840E+10 | 0.145903E+10 | 0.167937E+10 | 0.370155E+10 | 0.629232E+09 |
August | 0.258270E+10 | 0.117356E+10 | 0.140913E+10 | 0.292321E+10 | 0.749204E+09 |
September | 0.195336E+10 | 0.877617E+09 | 0.107575E+10 | 0.194215E+10 | 0.104922E+10 |
October | 0.127509E+10 | 0.511875E+09 | 0.763210E+09 | 0.917259E+09 | 0.171259E+10 |
November | 0.749443E+09 | 0.252684E+09 | 0.496759E+09 | 0.301428E+09 | 0.249295E+10 |
December | 0.690356E+09 | 0.241629E+09 | 0.448726E+09 | 0.162439E+09 | 0.388686E+10 |
Annual Sum or Average | 0.228584E+11 | 0.103956E+11 | 0.124628E+11 | 0.209791E+11 | 0.231120E+11 |
Minimum of Months | 0.690356E+09 | 0.241629E+09 | 0.448726E+09 | 0.162439E+09 | 0.629232E+09 |
Maximum of Months | 0.313840E+10 | 0.145903E+10 | 0.167937E+10 | 0.370155E+10 | 0.388686E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.905261E+09 | 0.379070E+09 | 0.526191E+09 | 0.318251E+09 | 0.380842E+10 |
February | 0.133220E+10 | 0.608461E+09 | 0.723740E+09 | 0.762003E+09 | 0.287737E+10 |
March | 0.194090E+10 | 0.993147E+09 | 0.947756E+09 | 0.137594E+10 | 0.262872E+10 |
April | 0.239942E+10 | 0.121528E+10 | 0.118414E+10 | 0.207800E+10 | 0.169680E+10 |
May | 0.304638E+10 | 0.145314E+10 | 0.159324E+10 | 0.326009E+10 | 0.930688E+09 |
June | 0.284486E+10 | 0.123010E+10 | 0.161477E+10 | 0.323674E+10 | 0.649972E+09 |
July | 0.313840E+10 | 0.145903E+10 | 0.167937E+10 | 0.370155E+10 | 0.629232E+09 |
August | 0.258270E+10 | 0.117356E+10 | 0.140913E+10 | 0.292321E+10 | 0.749204E+09 |
September | 0.195336E+10 | 0.877617E+09 | 0.107575E+10 | 0.194215E+10 | 0.104922E+10 |
October | 0.127509E+10 | 0.511875E+09 | 0.763210E+09 | 0.917259E+09 | 0.171259E+10 |
November | 0.749443E+09 | 0.252684E+09 | 0.496759E+09 | 0.301428E+09 | 0.249295E+10 |
December | 0.690356E+09 | 0.241629E+09 | 0.448726E+09 | 0.162439E+09 | 0.388686E+10 |
Annual Sum or Average | 0.228584E+11 | 0.103956E+11 | 0.124628E+11 | 0.209791E+11 | 0.231120E+11 |
Minimum of Months | 0.690356E+09 | 0.241629E+09 | 0.448726E+09 | 0.162439E+09 | 0.629232E+09 |
Maximum of Months | 0.313840E+10 | 0.145903E+10 | 0.167937E+10 | 0.370155E+10 | 0.388686E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.905245E+09 | 0.379063E+09 | 0.526182E+09 | 0.318245E+09 | 0.380835E+10 |
February | 0.133218E+10 | 0.608450E+09 | 0.723727E+09 | 0.761989E+09 | 0.287732E+10 |
March | 0.194087E+10 | 0.993129E+09 | 0.947738E+09 | 0.137591E+10 | 0.262867E+10 |
April | 0.239937E+10 | 0.121526E+10 | 0.118411E+10 | 0.207796E+10 | 0.169677E+10 |
May | 0.304632E+10 | 0.145311E+10 | 0.159321E+10 | 0.326003E+10 | 0.930671E+09 |
June | 0.284481E+10 | 0.123007E+10 | 0.161474E+10 | 0.323669E+10 | 0.649960E+09 |
July | 0.313835E+10 | 0.145901E+10 | 0.167934E+10 | 0.370148E+10 | 0.629220E+09 |
August | 0.258265E+10 | 0.117354E+10 | 0.140911E+10 | 0.292316E+10 | 0.749190E+09 |
September | 0.195333E+10 | 0.877601E+09 | 0.107573E+10 | 0.194212E+10 | 0.104920E+10 |
October | 0.127506E+10 | 0.511866E+09 | 0.763196E+09 | 0.917242E+09 | 0.171255E+10 |
November | 0.749429E+09 | 0.252679E+09 | 0.496750E+09 | 0.301423E+09 | 0.249290E+10 |
December | 0.690343E+09 | 0.241625E+09 | 0.448718E+09 | 0.162436E+09 | 0.388679E+10 |
Annual Sum or Average | 0.228580E+11 | 0.103954E+11 | 0.124625E+11 | 0.209787E+11 | 0.231116E+11 |
Minimum of Months | 0.690343E+09 | 0.241625E+09 | 0.448718E+09 | 0.162436E+09 | 0.629220E+09 |
Maximum of Months | 0.313835E+10 | 0.145901E+10 | 0.167934E+10 | 0.370148E+10 | 0.388679E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.183838E+10 | 0.00 | 0.183838E+10 | 14793643.08 | 0.174496E+11 |
February | 0.255062E+10 | 0.00 | 0.255062E+10 | 0.164905E+09 | 0.125864E+11 |
March | 0.347432E+10 | 0.00 | 0.347432E+10 | 0.420013E+09 | 0.109357E+11 |
April | 0.440769E+10 | 34401504.24 | 0.437329E+10 | 0.180430E+10 | 0.635027E+10 |
May | 0.640589E+10 | 0.344948E+09 | 0.606095E+10 | 0.527763E+10 | 0.347316E+10 |
June | 0.691846E+10 | 0.760524E+09 | 0.615794E+10 | 0.714970E+10 | 0.233530E+10 |
July | 0.682850E+10 | 0.586014E+09 | 0.624248E+10 | 0.745325E+10 | 0.224606E+10 |
August | 0.518646E+10 | 89067343.42 | 0.509739E+10 | 0.507227E+10 | 0.263920E+10 |
September | 0.391128E+10 | 958780.49 | 0.391032E+10 | 0.271191E+10 | 0.418001E+10 |
October | 0.280632E+10 | 0.00 | 0.280632E+10 | 0.861306E+09 | 0.665884E+10 |
November | 0.179820E+10 | 0.00 | 0.179820E+10 | 0.109520E+09 | 0.994518E+10 |
December | 0.155763E+10 | 0.00 | 0.155763E+10 | 474412.07 | 0.167206E+11 |
Annual Sum or Average | 0.476837E+11 | 0.181591E+10 | 0.458678E+11 | 0.310401E+11 | 0.955202E+11 |
Minimum of Months | 0.155763E+10 | 0.00 | 0.155763E+10 | 474412.07 | 0.224606E+10 |
Maximum of Months | 0.691846E+10 | 0.760524E+09 | 0.624248E+10 | 0.745325E+10 | 0.174496E+11 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.268699E+10 | 0.112164E+10 | 0.156536E+10 | 0.887421E+09 | 0.105010E+11 |
February | 0.381376E+10 | 0.162678E+10 | 0.218698E+10 | 0.203974E+10 | 0.751574E+10 |
March | 0.575325E+10 | 0.288592E+10 | 0.286733E+10 | 0.399559E+10 | 0.667554E+10 |
April | 0.771840E+10 | 0.416315E+10 | 0.355525E+10 | 0.693776E+10 | 0.398246E+10 |
May | 0.863202E+10 | 0.379474E+10 | 0.483729E+10 | 0.898387E+10 | 0.232794E+10 |
June | 0.945682E+10 | 0.452372E+10 | 0.493310E+10 | 0.108874E+11 | 0.158592E+10 |
July | 0.957301E+10 | 0.449488E+10 | 0.507813E+10 | 0.113653E+11 | 0.150931E+10 |
August | 0.738081E+10 | 0.322593E+10 | 0.415488E+10 | 0.837811E+10 | 0.173624E+10 |
September | 0.572012E+10 | 0.256030E+10 | 0.315982E+10 | 0.568187E+10 | 0.263209E+10 |
October | 0.357909E+10 | 0.135718E+10 | 0.222190E+10 | 0.253677E+10 | 0.417683E+10 |
November | 0.220498E+10 | 0.737174E+09 | 0.146780E+10 | 0.938780E+09 | 0.612162E+10 |
December | 0.207909E+10 | 0.768464E+09 | 0.131062E+10 | 0.547645E+09 | 0.102058E+11 |
Annual Sum or Average | 0.685983E+11 | 0.312599E+11 | 0.373385E+11 | 0.631803E+11 | 0.589706E+11 |
Minimum of Months | 0.207909E+10 | 0.737174E+09 | 0.131062E+10 | 0.547645E+09 | 0.150931E+10 |
Maximum of Months | 0.957301E+10 | 0.452372E+10 | 0.507813E+10 | 0.113653E+11 | 0.105010E+11 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.126592E+11 | 0.880674E+10 | 0.385248E+10 | 0.983752E+10 | 0.139924E+11 |
February | 0.144784E+11 | 0.977919E+10 | 0.469917E+10 | 0.128232E+11 | 0.107064E+11 |
March | 0.141240E+11 | 0.893855E+10 | 0.518548E+10 | 0.128319E+11 | 0.100339E+11 |
April | 0.123832E+11 | 0.672123E+10 | 0.566192E+10 | 0.124007E+11 | 0.652547E+10 |
May | 0.107580E+11 | 0.367791E+10 | 0.708010E+10 | 0.117964E+11 | 0.387732E+10 |
June | 0.934156E+10 | 0.248994E+10 | 0.685162E+10 | 0.110362E+11 | 0.256440E+10 |
July | 0.105538E+11 | 0.334339E+10 | 0.721041E+10 | 0.130755E+11 | 0.244846E+10 |
August | 0.112709E+11 | 0.471451E+10 | 0.655634E+10 | 0.135108E+11 | 0.284849E+10 |
September | 0.116833E+11 | 0.622225E+10 | 0.546108E+10 | 0.128514E+11 | 0.431505E+10 |
October | 0.103093E+11 | 0.606341E+10 | 0.424588E+10 | 0.988262E+10 | 0.648400E+10 |
November | 0.888707E+10 | 0.557754E+10 | 0.330953E+10 | 0.744575E+10 | 0.879409E+10 |
December | 0.977444E+10 | 0.640922E+10 | 0.336522E+10 | 0.695981E+10 | 0.135967E+11 |
Annual Sum or Average | 0.136223E+12 | 0.727439E+11 | 0.634792E+11 | 0.134452E+12 | 0.861867E+11 |
Minimum of Months | 0.888707E+10 | 0.248994E+10 | 0.330953E+10 | 0.695981E+10 | 0.244846E+10 |
Maximum of Months | 0.144784E+11 | 0.977919E+10 | 0.721041E+10 | 0.135108E+11 | 0.139924E+11 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.271576E+10 | 0.113720E+10 | 0.157856E+10 | 0.998023E+09 | 0.108482E+11 |
February | 0.399656E+10 | 0.182536E+10 | 0.217120E+10 | 0.238652E+10 | 0.793552E+10 |
March | 0.582265E+10 | 0.297941E+10 | 0.284324E+10 | 0.427627E+10 | 0.706969E+10 |
April | 0.719818E+10 | 0.364581E+10 | 0.355237E+10 | 0.646832E+10 | 0.434907E+10 |
May | 0.913905E+10 | 0.435937E+10 | 0.477968E+10 | 0.985212E+10 | 0.260922E+10 |
June | 0.853450E+10 | 0.369025E+10 | 0.484425E+10 | 0.981975E+10 | 0.175594E+10 |
July | 0.941511E+10 | 0.437705E+10 | 0.503806E+10 | 0.112022E+11 | 0.173126E+10 |
August | 0.774801E+10 | 0.352065E+10 | 0.422736E+10 | 0.891819E+10 | 0.195962E+10 |
September | 0.586003E+10 | 0.263283E+10 | 0.322721E+10 | 0.593774E+10 | 0.285912E+10 |
October | 0.382522E+10 | 0.153561E+10 | 0.228961E+10 | 0.293088E+10 | 0.443362E+10 |
November | 0.224831E+10 | 0.758043E+09 | 0.149026E+10 | 0.101186E+10 | 0.639452E+10 |
December | 0.207105E+10 | 0.724881E+09 | 0.134617E+10 | 0.538059E+09 | 0.105321E+11 |
Annual Sum or Average | 0.685744E+11 | 0.311865E+11 | 0.373879E+11 | 0.643400E+11 | 0.624778E+11 |
Minimum of Months | 0.207105E+10 | 0.724881E+09 | 0.134617E+10 | 0.538059E+09 | 0.173126E+10 |
Maximum of Months | 0.941511E+10 | 0.437705E+10 | 0.503806E+10 | 0.112022E+11 | 0.108482E+11 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.183838E+10 | 0.00 | 0.183838E+10 | 19663990.89 | 0.172101E+11 |
February | 0.255062E+10 | 0.00 | 0.255062E+10 | 0.182082E+09 | 0.123135E+11 |
March | 0.347432E+10 | 0.00 | 0.347432E+10 | 0.470187E+09 | 0.105517E+11 |
April | 0.440769E+10 | 34401504.24 | 0.437329E+10 | 0.193503E+10 | 0.595276E+10 |
May | 0.640589E+10 | 0.344948E+09 | 0.606095E+10 | 0.537074E+10 | 0.331721E+10 |
June | 0.691846E+10 | 0.760524E+09 | 0.615794E+10 | 0.718374E+10 | 0.225814E+10 |
July | 0.682850E+10 | 0.586014E+09 | 0.624248E+10 | 0.746106E+10 | 0.220076E+10 |
August | 0.518646E+10 | 89067343.42 | 0.509739E+10 | 0.509749E+10 | 0.255225E+10 |
September | 0.391128E+10 | 958780.49 | 0.391032E+10 | 0.282137E+10 | 0.391826E+10 |
October | 0.280632E+10 | 0.00 | 0.280632E+10 | 0.985559E+09 | 0.612509E+10 |
November | 0.179820E+10 | 0.00 | 0.179820E+10 | 0.131715E+09 | 0.948316E+10 |
December | 0.155763E+10 | 0.00 | 0.155763E+10 | 1036690.57 | 0.164367E+11 |
Annual Sum or Average | 0.476837E+11 | 0.181591E+10 | 0.458678E+11 | 0.316597E+11 | 0.923196E+11 |
Minimum of Months | 0.155763E+10 | 0.00 | 0.155763E+10 | 1036690.57 | 0.220076E+10 |
Maximum of Months | 0.691846E+10 | 0.760524E+09 | 0.624248E+10 | 0.746106E+10 | 0.172101E+11 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.268699E+10 | 0.112164E+10 | 0.156536E+10 | 0.898867E+09 | 0.103646E+11 |
February | 0.381376E+10 | 0.162678E+10 | 0.218698E+10 | 0.207289E+10 | 0.735239E+10 |
March | 0.575325E+10 | 0.288592E+10 | 0.286733E+10 | 0.405968E+10 | 0.643656E+10 |
April | 0.771840E+10 | 0.416315E+10 | 0.355525E+10 | 0.701560E+10 | 0.376641E+10 |
May | 0.863202E+10 | 0.379474E+10 | 0.483729E+10 | 0.901086E+10 | 0.225003E+10 |
June | 0.945682E+10 | 0.452372E+10 | 0.493310E+10 | 0.108798E+11 | 0.154641E+10 |
July | 0.957301E+10 | 0.449488E+10 | 0.507813E+10 | 0.113501E+11 | 0.148850E+10 |
August | 0.738081E+10 | 0.322593E+10 | 0.415488E+10 | 0.836982E+10 | 0.169888E+10 |
September | 0.572012E+10 | 0.256030E+10 | 0.315982E+10 | 0.572607E+10 | 0.251030E+10 |
October | 0.357909E+10 | 0.135718E+10 | 0.222190E+10 | 0.261942E+10 | 0.388509E+10 |
November | 0.220498E+10 | 0.737174E+09 | 0.146780E+10 | 0.974257E+09 | 0.583157E+10 |
December | 0.207909E+10 | 0.768464E+09 | 0.131062E+10 | 0.556884E+09 | 0.100388E+11 |
Annual Sum or Average | 0.685983E+11 | 0.312599E+11 | 0.373385E+11 | 0.635343E+11 | 0.571695E+11 |
Minimum of Months | 0.207909E+10 | 0.737174E+09 | 0.131062E+10 | 0.556884E+09 | 0.148850E+10 |
Maximum of Months | 0.957301E+10 | 0.452372E+10 | 0.507813E+10 | 0.113501E+11 | 0.103646E+11 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.126592E+11 | 0.880674E+10 | 0.385248E+10 | 0.988577E+10 | 0.137531E+11 |
February | 0.144784E+11 | 0.977919E+10 | 0.469917E+10 | 0.128970E+11 | 0.104018E+11 |
March | 0.141240E+11 | 0.893855E+10 | 0.518548E+10 | 0.129246E+11 | 0.963565E+10 |
April | 0.123832E+11 | 0.672123E+10 | 0.566192E+10 | 0.124969E+11 | 0.615516E+10 |
May | 0.107580E+11 | 0.367791E+10 | 0.708010E+10 | 0.118315E+11 | 0.372480E+10 |
June | 0.934156E+10 | 0.248994E+10 | 0.685162E+10 | 0.110481E+11 | 0.248093E+10 |
July | 0.105538E+11 | 0.334339E+10 | 0.721041E+10 | 0.130637E+11 | 0.239826E+10 |
August | 0.112709E+11 | 0.471451E+10 | 0.655634E+10 | 0.135035E+11 | 0.277155E+10 |
September | 0.116833E+11 | 0.622225E+10 | 0.546108E+10 | 0.129086E+11 | 0.410227E+10 |
October | 0.103093E+11 | 0.606341E+10 | 0.424588E+10 | 0.100221E+11 | 0.602085E+10 |
November | 0.888707E+10 | 0.557754E+10 | 0.330953E+10 | 0.755875E+10 | 0.832688E+10 |
December | 0.977444E+10 | 0.640922E+10 | 0.336522E+10 | 0.702067E+10 | 0.133229E+11 |
Annual Sum or Average | 0.136223E+12 | 0.727439E+11 | 0.634792E+11 | 0.135161E+12 | 0.830941E+11 |
Minimum of Months | 0.888707E+10 | 0.248994E+10 | 0.330953E+10 | 0.702067E+10 | 0.239826E+10 |
Maximum of Months | 0.144784E+11 | 0.977919E+10 | 0.721041E+10 | 0.135035E+11 | 0.137531E+11 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.271576E+10 | 0.113720E+10 | 0.157856E+10 | 0.100527E+10 | 0.107045E+11 |
February | 0.399656E+10 | 0.182536E+10 | 0.217120E+10 | 0.240071E+10 | 0.776869E+10 |
March | 0.582265E+10 | 0.297941E+10 | 0.284324E+10 | 0.430706E+10 | 0.683777E+10 |
April | 0.719818E+10 | 0.364581E+10 | 0.355237E+10 | 0.652010E+10 | 0.413178E+10 |
May | 0.913905E+10 | 0.435937E+10 | 0.477968E+10 | 0.987151E+10 | 0.252122E+10 |
June | 0.853450E+10 | 0.369025E+10 | 0.484425E+10 | 0.982128E+10 | 0.170921E+10 |
July | 0.941511E+10 | 0.437705E+10 | 0.503806E+10 | 0.111877E+11 | 0.170172E+10 |
August | 0.774801E+10 | 0.352065E+10 | 0.422736E+10 | 0.891577E+10 | 0.191253E+10 |
September | 0.586003E+10 | 0.263283E+10 | 0.322721E+10 | 0.597529E+10 | 0.273436E+10 |
October | 0.382522E+10 | 0.153561E+10 | 0.228961E+10 | 0.298856E+10 | 0.416464E+10 |
November | 0.224831E+10 | 0.758043E+09 | 0.149026E+10 | 0.104063E+10 | 0.612689E+10 |
December | 0.207105E+10 | 0.724881E+09 | 0.134617E+10 | 0.543378E+09 | 0.103808E+11 |
Annual Sum or Average | 0.685744E+11 | 0.311865E+11 | 0.373879E+11 | 0.645773E+11 | 0.606941E+11 |
Minimum of Months | 0.207105E+10 | 0.724881E+09 | 0.134617E+10 | 0.543378E+09 | 0.170172E+10 |
Maximum of Months | 0.941511E+10 | 0.437705E+10 | 0.503806E+10 | 0.111877E+11 | 0.107045E+11 |
Report: WindowZoneSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1.30 | 6785.80 | 686.38 | 0.00 | 686.38 | 0.00 | 0.00 |
February | 37.91 | 5548.94 | 1054.33 | 0.00 | 1054.33 | 0.00 | 0.00 |
March | 115.28 | 4426.75 | 1297.17 | 0.00 | 1297.17 | 0.00 | 0.00 |
April | 602.65 | 2740.81 | 1700.50 | 13.27 | 1687.23 | 0.00 | 0.00 |
May | 1938.30 | 1364.93 | 2391.70 | 128.79 | 2262.91 | 0.00 | 0.00 |
June | 2736.32 | 944.27 | 2669.17 | 293.41 | 2375.76 | 0.00 | 0.00 |
July | 2763.85 | 862.94 | 2549.48 | 218.79 | 2330.68 | 0.00 | 0.00 |
August | 1857.79 | 1046.20 | 1936.41 | 33.25 | 1903.15 | 0.00 | 0.00 |
September | 1003.59 | 1737.38 | 1508.99 | 0.37 | 1508.62 | 0.00 | 0.00 |
October | 254.13 | 2804.18 | 1047.76 | 0.00 | 1047.76 | 0.00 | 0.00 |
November | 27.69 | 4314.42 | 693.75 | 0.00 | 693.75 | 0.00 | 0.00 |
December | 0.00 | 6631.43 | 581.55 | 0.00 | 581.55 | 0.00 | 0.00 |
Annual Sum or Average | 950.74 | 3257.71 | 1512.05 | 57.58 | 1454.46 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 862.94 | 581.55 | 0.00 | 581.55 | 0.00 | 0.00 |
Maximum of Months | 2763.85 | 6785.80 | 2669.17 | 293.41 | 2375.76 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 320.39 | 4063.02 | 1003.21 | 418.77 | 584.44 | 0.00 | 0.00 |
February | 807.81 | 3284.27 | 1576.46 | 672.45 | 904.01 | 0.00 | 0.00 |
March | 1470.81 | 2641.76 | 2148.03 | 1077.48 | 1070.54 | 0.00 | 0.00 |
April | 2661.14 | 1646.09 | 2977.79 | 1606.16 | 1371.63 | 0.00 | 0.00 |
May | 3366.34 | 901.49 | 3222.84 | 1416.80 | 1806.04 | 0.00 | 0.00 |
June | 4220.14 | 629.25 | 3648.48 | 1745.27 | 1903.21 | 0.00 | 0.00 |
July | 4267.12 | 556.48 | 3574.17 | 1678.20 | 1895.96 | 0.00 | 0.00 |
August | 3138.97 | 652.33 | 2755.69 | 1204.43 | 1551.26 | 0.00 | 0.00 |
September | 2180.43 | 1075.97 | 2206.85 | 987.77 | 1219.07 | 0.00 | 0.00 |
October | 911.06 | 1704.56 | 1336.28 | 506.72 | 829.57 | 0.00 | 0.00 |
November | 341.40 | 2591.76 | 850.69 | 284.40 | 566.28 | 0.00 | 0.00 |
December | 194.33 | 4005.33 | 776.25 | 286.91 | 489.33 | 0.00 | 0.00 |
Annual Sum or Average | 1995.76 | 1974.04 | 2175.25 | 991.25 | 1184.00 | 0.00 | 0.00 |
Minimum of Months | 194.33 | 556.48 | 776.25 | 284.40 | 489.33 | 0.00 | 0.00 |
Maximum of Months | 4267.12 | 4063.02 | 3648.48 | 1745.27 | 1903.21 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 3668.36 | 5333.52 | 4726.43 | 3288.07 | 1438.36 | 0.00 | 0.00 |
February | 5307.78 | 4565.87 | 5984.79 | 4042.34 | 1942.45 | 0.00 | 0.00 |
March | 4800.15 | 3868.38 | 5273.33 | 3337.28 | 1936.04 | 0.00 | 0.00 |
April | 4785.43 | 2642.02 | 4777.47 | 2593.08 | 2184.39 | 0.00 | 0.00 |
May | 4422.28 | 1485.18 | 4016.60 | 1373.18 | 2643.42 | 0.00 | 0.00 |
June | 4262.59 | 1023.77 | 3604.01 | 960.63 | 2643.38 | 0.00 | 0.00 |
July | 4895.64 | 923.17 | 3940.35 | 1248.28 | 2692.07 | 0.00 | 0.00 |
August | 5058.89 | 1088.19 | 4208.07 | 1760.20 | 2447.87 | 0.00 | 0.00 |
September | 4981.91 | 1710.23 | 4507.47 | 2400.57 | 2106.91 | 0.00 | 0.00 |
October | 3681.02 | 2533.35 | 3849.06 | 2263.83 | 1585.24 | 0.00 | 0.00 |
November | 2850.98 | 3587.58 | 3428.67 | 2151.84 | 1276.83 | 0.00 | 0.00 |
December | 2574.46 | 5268.56 | 3649.37 | 2392.94 | 1256.43 | 0.00 | 0.00 |
Annual Sum or Average | 4266.22 | 2828.12 | 4319.62 | 2306.70 | 2012.92 | 0.00 | 0.00 |
Minimum of Months | 2574.46 | 923.17 | 3428.67 | 960.63 | 1256.43 | 0.00 | 0.00 |
Maximum of Months | 5307.78 | 5333.52 | 5984.79 | 4042.34 | 2692.07 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 356.46 | 4265.68 | 1013.95 | 424.58 | 589.37 | 0.00 | 0.00 |
February | 944.94 | 3568.15 | 1652.02 | 754.54 | 897.49 | 0.00 | 0.00 |
March | 1541.14 | 2944.34 | 2173.94 | 1112.39 | 1061.55 | 0.00 | 0.00 |
April | 2405.07 | 1963.88 | 2777.09 | 1406.57 | 1370.52 | 0.00 | 0.00 |
May | 3651.51 | 1042.43 | 3412.14 | 1627.61 | 1784.53 | 0.00 | 0.00 |
June | 3746.21 | 752.28 | 3292.64 | 1423.71 | 1868.93 | 0.00 | 0.00 |
July | 4145.97 | 704.78 | 3515.21 | 1634.21 | 1881.00 | 0.00 | 0.00 |
August | 3274.18 | 839.16 | 2892.79 | 1314.47 | 1578.32 | 0.00 | 0.00 |
September | 2247.85 | 1214.36 | 2260.82 | 1015.75 | 1245.07 | 0.00 | 0.00 |
October | 1027.39 | 1918.21 | 1428.18 | 573.33 | 854.84 | 0.00 | 0.00 |
November | 348.87 | 2885.34 | 867.41 | 292.46 | 574.95 | 0.00 | 0.00 |
December | 181.94 | 4353.53 | 773.24 | 270.64 | 502.60 | 0.00 | 0.00 |
Annual Sum or Average | 1995.71 | 2198.62 | 2174.49 | 988.92 | 1185.57 | 0.00 | 0.00 |
Minimum of Months | 181.94 | 704.78 | 773.24 | 270.64 | 502.60 | 0.00 | 0.00 |
Maximum of Months | 4145.97 | 4353.53 | 3515.21 | 1634.21 | 1881.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 5.52 | 6514.93 | 686.37 | 0.00 | 686.37 | 0.00 | 0.00 |
February | 68.16 | 5202.72 | 1054.32 | 0.00 | 1054.32 | 0.00 | 0.00 |
March | 156.81 | 4082.91 | 1297.16 | 0.00 | 1297.16 | 0.00 | 0.00 |
April | 696.10 | 2449.95 | 1700.50 | 13.27 | 1687.23 | 0.00 | 0.00 |
May | 1970.44 | 1296.73 | 2391.69 | 128.79 | 2262.90 | 0.00 | 0.00 |
June | 2758.37 | 900.96 | 2669.16 | 293.41 | 2375.75 | 0.00 | 0.00 |
July | 2782.72 | 838.58 | 2549.47 | 218.79 | 2330.68 | 0.00 | 0.00 |
August | 1893.77 | 985.36 | 1936.40 | 33.25 | 1903.15 | 0.00 | 0.00 |
September | 1046.26 | 1612.66 | 1508.98 | 0.37 | 1508.61 | 0.00 | 0.00 |
October | 321.57 | 2486.13 | 1047.76 | 0.00 | 1047.76 | 0.00 | 0.00 |
November | 42.25 | 3836.88 | 693.75 | 0.00 | 693.75 | 0.00 | 0.00 |
December | 0.18 | 6242.75 | 581.55 | 0.00 | 581.55 | 0.00 | 0.00 |
Annual Sum or Average | 984.27 | 3028.93 | 1512.04 | 57.58 | 1454.46 | 0.00 | 0.00 |
Minimum of Months | 0.18 | 838.58 | 581.55 | 0.00 | 581.55 | 0.00 | 0.00 |
Maximum of Months | 2782.72 | 6514.93 | 2669.16 | 293.41 | 2375.75 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 331.33 | 3920.64 | 1003.21 | 418.77 | 584.44 | 0.00 | 0.00 |
February | 843.14 | 3106.71 | 1576.45 | 672.44 | 904.01 | 0.00 | 0.00 |
March | 1491.78 | 2492.36 | 2148.02 | 1077.48 | 1070.54 | 0.00 | 0.00 |
April | 2676.61 | 1536.44 | 2977.78 | 1606.15 | 1371.62 | 0.00 | 0.00 |
May | 3354.19 | 869.15 | 3222.83 | 1416.79 | 1806.04 | 0.00 | 0.00 |
June | 4200.38 | 611.85 | 3648.47 | 1745.26 | 1903.20 | 0.00 | 0.00 |
July | 4243.32 | 563.51 | 3574.15 | 1678.20 | 1895.96 | 0.00 | 0.00 |
August | 3128.03 | 648.24 | 2755.68 | 1204.42 | 1551.25 | 0.00 | 0.00 |
September | 2192.08 | 1015.47 | 2206.84 | 987.77 | 1219.07 | 0.00 | 0.00 |
October | 947.12 | 1559.45 | 1336.28 | 506.71 | 829.56 | 0.00 | 0.00 |
November | 362.18 | 2361.74 | 850.69 | 284.40 | 566.28 | 0.00 | 0.00 |
December | 204.47 | 3810.42 | 776.24 | 286.91 | 489.33 | 0.00 | 0.00 |
Annual Sum or Average | 2003.43 | 1869.94 | 2175.24 | 991.24 | 1183.99 | 0.00 | 0.00 |
Minimum of Months | 204.47 | 563.51 | 776.24 | 284.40 | 489.33 | 0.00 | 0.00 |
Maximum of Months | 4243.32 | 3920.64 | 3648.47 | 1745.26 | 1903.20 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 3672.91 | 5224.16 | 4726.41 | 3288.06 | 1438.35 | 0.00 | 0.00 |
February | 5300.59 | 4425.60 | 5984.77 | 4042.32 | 1942.45 | 0.00 | 0.00 |
March | 4790.89 | 3746.24 | 5273.31 | 3337.27 | 1936.04 | 0.00 | 0.00 |
April | 4784.20 | 2517.54 | 4777.45 | 2593.07 | 2184.38 | 0.00 | 0.00 |
May | 4404.27 | 1447.63 | 4016.58 | 1373.17 | 2643.41 | 0.00 | 0.00 |
June | 4257.80 | 989.35 | 3604.00 | 960.62 | 2643.37 | 0.00 | 0.00 |
July | 4881.84 | 914.15 | 3940.34 | 1248.28 | 2692.06 | 0.00 | 0.00 |
August | 5044.34 | 1063.50 | 4208.06 | 1760.20 | 2447.86 | 0.00 | 0.00 |
September | 4958.10 | 1664.76 | 4507.46 | 2400.56 | 2106.90 | 0.00 | 0.00 |
October | 3689.75 | 2420.85 | 3849.05 | 2263.82 | 1585.23 | 0.00 | 0.00 |
November | 2872.59 | 3392.78 | 3428.65 | 2151.83 | 1276.83 | 0.00 | 0.00 |
December | 2598.49 | 5076.42 | 3649.36 | 2392.93 | 1256.43 | 0.00 | 0.00 |
Annual Sum or Average | 4263.44 | 2732.96 | 4319.61 | 2306.69 | 2012.91 | 0.00 | 0.00 |
Minimum of Months | 2598.49 | 914.15 | 3428.65 | 960.62 | 1256.43 | 0.00 | 0.00 |
Maximum of Months | 5300.59 | 5224.16 | 5984.77 | 4042.32 | 2692.06 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 372.62 | 4050.26 | 1013.95 | 424.58 | 589.37 | 0.00 | 0.00 |
February | 986.49 | 3280.22 | 1652.02 | 754.53 | 897.49 | 0.00 | 0.00 |
March | 1596.57 | 2639.52 | 2173.93 | 1112.39 | 1061.54 | 0.00 | 0.00 |
April | 2495.49 | 1677.88 | 2777.07 | 1406.56 | 1370.51 | 0.00 | 0.00 |
May | 3678.36 | 974.17 | 3412.13 | 1627.60 | 1784.53 | 0.00 | 0.00 |
June | 3788.48 | 677.45 | 3292.63 | 1423.71 | 1868.92 | 0.00 | 0.00 |
July | 4182.44 | 646.38 | 3515.20 | 1634.20 | 1881.00 | 0.00 | 0.00 |
August | 3329.67 | 731.64 | 2892.78 | 1314.46 | 1578.32 | 0.00 | 0.00 |
September | 2290.80 | 1103.06 | 2260.81 | 1015.75 | 1245.06 | 0.00 | 0.00 |
October | 1094.26 | 1655.32 | 1428.17 | 573.33 | 854.84 | 0.00 | 0.00 |
November | 390.38 | 2467.02 | 867.40 | 292.45 | 574.95 | 0.00 | 0.00 |
December | 200.89 | 3932.22 | 773.24 | 270.64 | 502.60 | 0.00 | 0.00 |
Annual Sum or Average | 2040.21 | 1981.16 | 2174.48 | 988.92 | 1185.56 | 0.00 | 0.00 |
Minimum of Months | 200.89 | 646.38 | 773.24 | 270.64 | 502.60 | 0.00 | 0.00 |
Maximum of Months | 4182.44 | 4050.26 | 3515.20 | 1634.20 | 1881.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 7.34 | 6425.51 | 686.37 | 0.00 | 686.37 | 0.00 | 0.00 |
February | 75.27 | 5089.89 | 1054.32 | 0.00 | 1054.32 | 0.00 | 0.00 |
March | 175.55 | 3939.57 | 1297.16 | 0.00 | 1297.16 | 0.00 | 0.00 |
April | 746.54 | 2296.59 | 1700.50 | 13.27 | 1687.23 | 0.00 | 0.00 |
May | 2005.21 | 1238.50 | 2391.69 | 128.79 | 2262.90 | 0.00 | 0.00 |
June | 2771.51 | 871.20 | 2669.16 | 293.41 | 2375.75 | 0.00 | 0.00 |
July | 2785.64 | 821.67 | 2549.47 | 218.79 | 2330.68 | 0.00 | 0.00 |
August | 1903.18 | 952.90 | 1936.40 | 33.25 | 1903.15 | 0.00 | 0.00 |
September | 1088.49 | 1511.67 | 1508.98 | 0.37 | 1508.61 | 0.00 | 0.00 |
October | 367.97 | 2286.84 | 1047.76 | 0.00 | 1047.76 | 0.00 | 0.00 |
November | 50.82 | 3658.63 | 693.75 | 0.00 | 693.75 | 0.00 | 0.00 |
December | 0.39 | 6136.75 | 581.55 | 0.00 | 581.55 | 0.00 | 0.00 |
Annual Sum or Average | 1003.92 | 2927.43 | 1512.04 | 57.58 | 1454.46 | 0.00 | 0.00 |
Minimum of Months | 0.39 | 821.67 | 581.55 | 0.00 | 581.55 | 0.00 | 0.00 |
Maximum of Months | 2785.64 | 6425.51 | 2669.16 | 293.41 | 2375.75 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 335.60 | 3869.70 | 1003.21 | 418.77 | 584.44 | 0.00 | 0.00 |
February | 856.85 | 3039.18 | 1576.45 | 672.44 | 904.01 | 0.00 | 0.00 |
March | 1515.71 | 2403.14 | 2148.02 | 1077.48 | 1070.54 | 0.00 | 0.00 |
April | 2706.63 | 1453.09 | 2977.78 | 1606.15 | 1371.62 | 0.00 | 0.00 |
May | 3364.27 | 840.06 | 3222.83 | 1416.79 | 1806.04 | 0.00 | 0.00 |
June | 4197.47 | 596.61 | 3648.47 | 1745.26 | 1903.20 | 0.00 | 0.00 |
July | 4237.62 | 555.74 | 3574.15 | 1678.20 | 1895.96 | 0.00 | 0.00 |
August | 3124.93 | 634.29 | 2755.68 | 1204.42 | 1551.25 | 0.00 | 0.00 |
September | 2209.13 | 968.48 | 2206.84 | 987.77 | 1219.07 | 0.00 | 0.00 |
October | 977.98 | 1450.53 | 1336.28 | 506.71 | 829.56 | 0.00 | 0.00 |
November | 375.87 | 2249.83 | 850.69 | 284.40 | 566.28 | 0.00 | 0.00 |
December | 207.92 | 3748.05 | 776.24 | 286.91 | 489.33 | 0.00 | 0.00 |
Annual Sum or Average | 2014.66 | 1812.83 | 2175.24 | 991.24 | 1183.99 | 0.00 | 0.00 |
Minimum of Months | 207.92 | 555.74 | 776.24 | 284.40 | 489.33 | 0.00 | 0.00 |
Maximum of Months | 4237.62 | 3869.70 | 3648.47 | 1745.26 | 1903.20 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 3690.92 | 5134.81 | 4726.41 | 3288.06 | 1438.35 | 0.00 | 0.00 |
February | 5331.09 | 4299.67 | 5984.77 | 4042.32 | 1942.45 | 0.00 | 0.00 |
March | 4825.49 | 3597.54 | 5273.31 | 3337.27 | 1936.04 | 0.00 | 0.00 |
April | 4821.32 | 2374.68 | 4777.45 | 2593.07 | 2184.38 | 0.00 | 0.00 |
May | 4417.36 | 1390.68 | 4016.58 | 1373.17 | 2643.41 | 0.00 | 0.00 |
June | 4262.40 | 957.15 | 3604.00 | 960.62 | 2643.37 | 0.00 | 0.00 |
July | 4877.42 | 895.41 | 3940.34 | 1248.28 | 2692.06 | 0.00 | 0.00 |
August | 5041.62 | 1034.78 | 4208.06 | 1760.20 | 2447.86 | 0.00 | 0.00 |
September | 4980.18 | 1582.66 | 4507.46 | 2400.56 | 2106.90 | 0.00 | 0.00 |
October | 3741.81 | 2247.93 | 3849.05 | 2263.82 | 1585.23 | 0.00 | 0.00 |
November | 2916.18 | 3212.53 | 3428.65 | 2151.83 | 1276.83 | 0.00 | 0.00 |
December | 2621.22 | 4974.19 | 3649.36 | 2392.93 | 1256.43 | 0.00 | 0.00 |
Annual Sum or Average | 4285.93 | 2634.90 | 4319.61 | 2306.69 | 2012.91 | 0.00 | 0.00 |
Minimum of Months | 2621.22 | 895.41 | 3428.65 | 960.62 | 1256.43 | 0.00 | 0.00 |
Maximum of Months | 5331.09 | 5134.81 | 5984.77 | 4042.32 | 2692.06 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 375.33 | 3996.60 | 1013.95 | 424.58 | 589.37 | 0.00 | 0.00 |
February | 992.36 | 3211.27 | 1652.02 | 754.53 | 897.49 | 0.00 | 0.00 |
March | 1608.07 | 2552.93 | 2173.93 | 1112.39 | 1061.54 | 0.00 | 0.00 |
April | 2515.47 | 1594.05 | 2777.07 | 1406.56 | 1370.51 | 0.00 | 0.00 |
May | 3685.60 | 941.32 | 3412.13 | 1627.60 | 1784.53 | 0.00 | 0.00 |
June | 3789.07 | 659.42 | 3292.63 | 1423.71 | 1868.92 | 0.00 | 0.00 |
July | 4177.02 | 635.35 | 3515.20 | 1634.20 | 1881.00 | 0.00 | 0.00 |
August | 3328.77 | 714.06 | 2892.78 | 1314.46 | 1578.32 | 0.00 | 0.00 |
September | 2305.28 | 1054.92 | 2260.81 | 1015.75 | 1245.06 | 0.00 | 0.00 |
October | 1115.80 | 1554.90 | 1428.17 | 573.33 | 854.84 | 0.00 | 0.00 |
November | 401.48 | 2363.77 | 867.40 | 292.45 | 574.95 | 0.00 | 0.00 |
December | 202.87 | 3875.75 | 773.24 | 270.64 | 502.60 | 0.00 | 0.00 |
Annual Sum or Average | 2047.73 | 1924.60 | 2174.48 | 988.92 | 1185.56 | 0.00 | 0.00 |
Minimum of Months | 202.87 | 635.35 | 773.24 | 270.64 | 502.60 | 0.00 | 0.00 |
Maximum of Months | 4177.02 | 3996.60 | 3515.20 | 1634.20 | 1881.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 3472655.07 | 0.181751E+11 | 0.183839E+10 | 0.00 | 0.183839E+10 | 0.00 | 0.00 |
February | 91707372.33 | 0.134240E+11 | 0.255063E+10 | 0.00 | 0.255063E+10 | 0.00 | 0.00 |
March | 0.308764E+09 | 0.118566E+11 | 0.347433E+10 | 0.00 | 0.347433E+10 | 0.00 | 0.00 |
April | 0.156207E+10 | 0.710418E+10 | 0.440771E+10 | 34401626.41 | 0.437331E+10 | 0.00 | 0.00 |
May | 0.519154E+10 | 0.365582E+10 | 0.640592E+10 | 0.344949E+09 | 0.606097E+10 | 0.00 | 0.00 |
June | 0.709253E+10 | 0.244756E+10 | 0.691849E+10 | 0.760527E+09 | 0.615796E+10 | 0.00 | 0.00 |
July | 0.740271E+10 | 0.231130E+10 | 0.682852E+10 | 0.586017E+09 | 0.624250E+10 | 0.00 | 0.00 |
August | 0.497591E+10 | 0.280214E+10 | 0.518648E+10 | 89067659.70 | 0.509741E+10 | 0.00 | 0.00 |
September | 0.260132E+10 | 0.450329E+10 | 0.391129E+10 | 958783.89 | 0.391033E+10 | 0.00 | 0.00 |
October | 0.680660E+09 | 0.751072E+10 | 0.280633E+10 | 0.00 | 0.280633E+10 | 0.00 | 0.00 |
November | 71782982.51 | 0.111830E+11 | 0.179821E+10 | 0.00 | 0.179821E+10 | 0.00 | 0.00 |
December | 0.00 | 0.177616E+11 | 0.155763E+10 | 0.00 | 0.155763E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.299825E+11 | 0.102735E+12 | 0.476839E+11 | 0.181592E+10 | 0.458680E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.231130E+10 | 0.155763E+10 | 0.00 | 0.155763E+10 | 0.00 | 0.00 |
Maximum of Months | 0.740271E+10 | 0.181751E+11 | 0.691849E+10 | 0.760527E+09 | 0.624250E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.858124E+09 | 0.108824E+11 | 0.268701E+10 | 0.112164E+10 | 0.156537E+10 | 0.00 | 0.00 |
February | 0.195426E+10 | 0.794532E+10 | 0.381377E+10 | 0.162678E+10 | 0.218699E+10 | 0.00 | 0.00 |
March | 0.393942E+10 | 0.707569E+10 | 0.575328E+10 | 0.288593E+10 | 0.286735E+10 | 0.00 | 0.00 |
April | 0.689768E+10 | 0.426666E+10 | 0.771843E+10 | 0.416317E+10 | 0.355526E+10 | 0.00 | 0.00 |
May | 0.901642E+10 | 0.241454E+10 | 0.863206E+10 | 0.379475E+10 | 0.483731E+10 | 0.00 | 0.00 |
June | 0.109386E+11 | 0.163102E+10 | 0.945686E+10 | 0.452374E+10 | 0.493312E+10 | 0.00 | 0.00 |
July | 0.114291E+11 | 0.149047E+10 | 0.957305E+10 | 0.449490E+10 | 0.507815E+10 | 0.00 | 0.00 |
August | 0.840742E+10 | 0.174721E+10 | 0.738084E+10 | 0.322594E+10 | 0.415489E+10 | 0.00 | 0.00 |
September | 0.565169E+10 | 0.278893E+10 | 0.572014E+10 | 0.256031E+10 | 0.315984E+10 | 0.00 | 0.00 |
October | 0.244018E+10 | 0.456548E+10 | 0.357910E+10 | 0.135719E+10 | 0.222191E+10 | 0.00 | 0.00 |
November | 0.884902E+09 | 0.671783E+10 | 0.220499E+10 | 0.737177E+09 | 0.146781E+10 | 0.00 | 0.00 |
December | 0.520485E+09 | 0.107279E+11 | 0.207910E+10 | 0.768467E+09 | 0.131063E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.629382E+11 | 0.622534E+11 | 0.685986E+11 | 0.312600E+11 | 0.373386E+11 | 0.00 | 0.00 |
Minimum of Months | 0.520485E+09 | 0.149047E+10 | 0.207910E+10 | 0.737177E+09 | 0.131063E+10 | 0.00 | 0.00 |
Maximum of Months | 0.114291E+11 | 0.108824E+11 | 0.957305E+10 | 0.452374E+10 | 0.507815E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.982533E+10 | 0.142853E+11 | 0.126593E+11 | 0.880677E+10 | 0.385250E+10 | 0.00 | 0.00 |
February | 0.128406E+11 | 0.110458E+11 | 0.144784E+11 | 0.977922E+10 | 0.469919E+10 | 0.00 | 0.00 |
March | 0.128567E+11 | 0.103611E+11 | 0.141241E+11 | 0.893858E+10 | 0.518550E+10 | 0.00 | 0.00 |
April | 0.124038E+11 | 0.684812E+10 | 0.123832E+11 | 0.672125E+10 | 0.566194E+10 | 0.00 | 0.00 |
May | 0.118446E+11 | 0.397789E+10 | 0.107580E+11 | 0.367792E+10 | 0.708013E+10 | 0.00 | 0.00 |
June | 0.110486E+11 | 0.265362E+10 | 0.934159E+10 | 0.248994E+10 | 0.685165E+10 | 0.00 | 0.00 |
July | 0.131125E+11 | 0.247262E+10 | 0.105538E+11 | 0.334341E+10 | 0.721043E+10 | 0.00 | 0.00 |
August | 0.135497E+11 | 0.291460E+10 | 0.112709E+11 | 0.471453E+10 | 0.655637E+10 | 0.00 | 0.00 |
September | 0.129131E+11 | 0.443292E+10 | 0.116834E+11 | 0.622227E+10 | 0.546110E+10 | 0.00 | 0.00 |
October | 0.985924E+10 | 0.678532E+10 | 0.103093E+11 | 0.606343E+10 | 0.424590E+10 | 0.00 | 0.00 |
November | 0.738973E+10 | 0.929900E+10 | 0.888711E+10 | 0.557756E+10 | 0.330955E+10 | 0.00 | 0.00 |
December | 0.689542E+10 | 0.141113E+11 | 0.977447E+10 | 0.640924E+10 | 0.336523E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.134539E+12 | 0.891875E+11 | 0.136224E+12 | 0.727441E+11 | 0.634795E+11 | 0.00 | 0.00 |
Minimum of Months | 0.689542E+10 | 0.247262E+10 | 0.888711E+10 | 0.248994E+10 | 0.330955E+10 | 0.00 | 0.00 |
Maximum of Months | 0.135497E+11 | 0.142853E+11 | 0.144784E+11 | 0.977922E+10 | 0.721043E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.954746E+09 | 0.114252E+11 | 0.271577E+10 | 0.113720E+10 | 0.157856E+10 | 0.00 | 0.00 |
February | 0.228599E+10 | 0.863206E+10 | 0.399658E+10 | 0.182537E+10 | 0.217121E+10 | 0.00 | 0.00 |
March | 0.412779E+10 | 0.788612E+10 | 0.582267E+10 | 0.297942E+10 | 0.284325E+10 | 0.00 | 0.00 |
April | 0.623395E+10 | 0.509037E+10 | 0.719821E+10 | 0.364582E+10 | 0.355238E+10 | 0.00 | 0.00 |
May | 0.978022E+10 | 0.279205E+10 | 0.913909E+10 | 0.435939E+10 | 0.477970E+10 | 0.00 | 0.00 |
June | 0.971018E+10 | 0.194990E+10 | 0.853453E+10 | 0.369026E+10 | 0.484427E+10 | 0.00 | 0.00 |
July | 0.111046E+11 | 0.188768E+10 | 0.941515E+10 | 0.437707E+10 | 0.503808E+10 | 0.00 | 0.00 |
August | 0.876958E+10 | 0.224760E+10 | 0.774804E+10 | 0.352066E+10 | 0.422738E+10 | 0.00 | 0.00 |
September | 0.582643E+10 | 0.314763E+10 | 0.586006E+10 | 0.263284E+10 | 0.322722E+10 | 0.00 | 0.00 |
October | 0.275176E+10 | 0.513773E+10 | 0.382523E+10 | 0.153562E+10 | 0.228962E+10 | 0.00 | 0.00 |
November | 0.904279E+09 | 0.747880E+10 | 0.224831E+10 | 0.758046E+09 | 0.149027E+10 | 0.00 | 0.00 |
December | 0.487313E+09 | 0.116605E+11 | 0.207105E+10 | 0.724884E+09 | 0.134617E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.629368E+11 | 0.693356E+11 | 0.685747E+11 | 0.311866E+11 | 0.373881E+11 | 0.00 | 0.00 |
Minimum of Months | 0.487313E+09 | 0.188768E+10 | 0.207105E+10 | 0.724884E+09 | 0.134617E+10 | 0.00 | 0.00 |
Maximum of Months | 0.111046E+11 | 0.116605E+11 | 0.941515E+10 | 0.437707E+10 | 0.503808E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 14793643.08 | 0.174496E+11 | 0.183838E+10 | 0.00 | 0.183838E+10 | 0.00 | 0.00 |
February | 0.164905E+09 | 0.125864E+11 | 0.255062E+10 | 0.00 | 0.255062E+10 | 0.00 | 0.00 |
March | 0.420013E+09 | 0.109357E+11 | 0.347432E+10 | 0.00 | 0.347432E+10 | 0.00 | 0.00 |
April | 0.180430E+10 | 0.635027E+10 | 0.440769E+10 | 34401504.24 | 0.437329E+10 | 0.00 | 0.00 |
May | 0.527763E+10 | 0.347316E+10 | 0.640589E+10 | 0.344948E+09 | 0.606095E+10 | 0.00 | 0.00 |
June | 0.714970E+10 | 0.233530E+10 | 0.691846E+10 | 0.760524E+09 | 0.615794E+10 | 0.00 | 0.00 |
July | 0.745325E+10 | 0.224606E+10 | 0.682850E+10 | 0.586014E+09 | 0.624248E+10 | 0.00 | 0.00 |
August | 0.507227E+10 | 0.263920E+10 | 0.518646E+10 | 89067343.42 | 0.509739E+10 | 0.00 | 0.00 |
September | 0.271191E+10 | 0.418001E+10 | 0.391128E+10 | 958780.49 | 0.391032E+10 | 0.00 | 0.00 |
October | 0.861306E+09 | 0.665884E+10 | 0.280632E+10 | 0.00 | 0.280632E+10 | 0.00 | 0.00 |
November | 0.109520E+09 | 0.994518E+10 | 0.179820E+10 | 0.00 | 0.179820E+10 | 0.00 | 0.00 |
December | 474412.07 | 0.167206E+11 | 0.155763E+10 | 0.00 | 0.155763E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.310401E+11 | 0.955202E+11 | 0.476837E+11 | 0.181591E+10 | 0.458678E+11 | 0.00 | 0.00 |
Minimum of Months | 474412.07 | 0.224606E+10 | 0.155763E+10 | 0.00 | 0.155763E+10 | 0.00 | 0.00 |
Maximum of Months | 0.745325E+10 | 0.174496E+11 | 0.691846E+10 | 0.760524E+09 | 0.624248E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.887421E+09 | 0.105010E+11 | 0.268699E+10 | 0.112164E+10 | 0.156536E+10 | 0.00 | 0.00 |
February | 0.203974E+10 | 0.751574E+10 | 0.381376E+10 | 0.162678E+10 | 0.218698E+10 | 0.00 | 0.00 |
March | 0.399559E+10 | 0.667554E+10 | 0.575325E+10 | 0.288592E+10 | 0.286733E+10 | 0.00 | 0.00 |
April | 0.693776E+10 | 0.398246E+10 | 0.771840E+10 | 0.416315E+10 | 0.355525E+10 | 0.00 | 0.00 |
May | 0.898387E+10 | 0.232794E+10 | 0.863202E+10 | 0.379474E+10 | 0.483729E+10 | 0.00 | 0.00 |
June | 0.108874E+11 | 0.158592E+10 | 0.945682E+10 | 0.452372E+10 | 0.493310E+10 | 0.00 | 0.00 |
July | 0.113653E+11 | 0.150931E+10 | 0.957301E+10 | 0.449488E+10 | 0.507813E+10 | 0.00 | 0.00 |
August | 0.837811E+10 | 0.173624E+10 | 0.738081E+10 | 0.322593E+10 | 0.415488E+10 | 0.00 | 0.00 |
September | 0.568187E+10 | 0.263209E+10 | 0.572012E+10 | 0.256030E+10 | 0.315982E+10 | 0.00 | 0.00 |
October | 0.253677E+10 | 0.417683E+10 | 0.357909E+10 | 0.135718E+10 | 0.222190E+10 | 0.00 | 0.00 |
November | 0.938780E+09 | 0.612162E+10 | 0.220498E+10 | 0.737174E+09 | 0.146780E+10 | 0.00 | 0.00 |
December | 0.547645E+09 | 0.102058E+11 | 0.207909E+10 | 0.768464E+09 | 0.131062E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.631803E+11 | 0.589706E+11 | 0.685983E+11 | 0.312599E+11 | 0.373385E+11 | 0.00 | 0.00 |
Minimum of Months | 0.547645E+09 | 0.150931E+10 | 0.207909E+10 | 0.737174E+09 | 0.131062E+10 | 0.00 | 0.00 |
Maximum of Months | 0.113653E+11 | 0.105010E+11 | 0.957301E+10 | 0.452372E+10 | 0.507813E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.983752E+10 | 0.139924E+11 | 0.126592E+11 | 0.880674E+10 | 0.385248E+10 | 0.00 | 0.00 |
February | 0.128232E+11 | 0.107064E+11 | 0.144784E+11 | 0.977919E+10 | 0.469917E+10 | 0.00 | 0.00 |
March | 0.128319E+11 | 0.100339E+11 | 0.141240E+11 | 0.893855E+10 | 0.518548E+10 | 0.00 | 0.00 |
April | 0.124007E+11 | 0.652547E+10 | 0.123832E+11 | 0.672123E+10 | 0.566192E+10 | 0.00 | 0.00 |
May | 0.117964E+11 | 0.387732E+10 | 0.107580E+11 | 0.367791E+10 | 0.708010E+10 | 0.00 | 0.00 |
June | 0.110362E+11 | 0.256440E+10 | 0.934156E+10 | 0.248994E+10 | 0.685162E+10 | 0.00 | 0.00 |
July | 0.130755E+11 | 0.244846E+10 | 0.105538E+11 | 0.334339E+10 | 0.721041E+10 | 0.00 | 0.00 |
August | 0.135108E+11 | 0.284849E+10 | 0.112709E+11 | 0.471451E+10 | 0.655634E+10 | 0.00 | 0.00 |
September | 0.128514E+11 | 0.431505E+10 | 0.116833E+11 | 0.622225E+10 | 0.546108E+10 | 0.00 | 0.00 |
October | 0.988262E+10 | 0.648400E+10 | 0.103093E+11 | 0.606341E+10 | 0.424588E+10 | 0.00 | 0.00 |
November | 0.744575E+10 | 0.879409E+10 | 0.888707E+10 | 0.557754E+10 | 0.330953E+10 | 0.00 | 0.00 |
December | 0.695981E+10 | 0.135967E+11 | 0.977444E+10 | 0.640922E+10 | 0.336522E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.134452E+12 | 0.861867E+11 | 0.136223E+12 | 0.727439E+11 | 0.634792E+11 | 0.00 | 0.00 |
Minimum of Months | 0.695981E+10 | 0.244846E+10 | 0.888707E+10 | 0.248994E+10 | 0.330953E+10 | 0.00 | 0.00 |
Maximum of Months | 0.135108E+11 | 0.139924E+11 | 0.144784E+11 | 0.977919E+10 | 0.721041E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.998023E+09 | 0.108482E+11 | 0.271576E+10 | 0.113720E+10 | 0.157856E+10 | 0.00 | 0.00 |
February | 0.238652E+10 | 0.793552E+10 | 0.399656E+10 | 0.182536E+10 | 0.217120E+10 | 0.00 | 0.00 |
March | 0.427627E+10 | 0.706969E+10 | 0.582265E+10 | 0.297941E+10 | 0.284324E+10 | 0.00 | 0.00 |
April | 0.646832E+10 | 0.434907E+10 | 0.719818E+10 | 0.364581E+10 | 0.355237E+10 | 0.00 | 0.00 |
May | 0.985212E+10 | 0.260922E+10 | 0.913905E+10 | 0.435937E+10 | 0.477968E+10 | 0.00 | 0.00 |
June | 0.981975E+10 | 0.175594E+10 | 0.853450E+10 | 0.369025E+10 | 0.484425E+10 | 0.00 | 0.00 |
July | 0.112022E+11 | 0.173126E+10 | 0.941511E+10 | 0.437705E+10 | 0.503806E+10 | 0.00 | 0.00 |
August | 0.891819E+10 | 0.195962E+10 | 0.774801E+10 | 0.352065E+10 | 0.422736E+10 | 0.00 | 0.00 |
September | 0.593774E+10 | 0.285912E+10 | 0.586003E+10 | 0.263283E+10 | 0.322721E+10 | 0.00 | 0.00 |
October | 0.293088E+10 | 0.443362E+10 | 0.382522E+10 | 0.153561E+10 | 0.228961E+10 | 0.00 | 0.00 |
November | 0.101186E+10 | 0.639452E+10 | 0.224831E+10 | 0.758043E+09 | 0.149026E+10 | 0.00 | 0.00 |
December | 0.538059E+09 | 0.105321E+11 | 0.207105E+10 | 0.724881E+09 | 0.134617E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.643400E+11 | 0.624778E+11 | 0.685744E+11 | 0.311865E+11 | 0.373879E+11 | 0.00 | 0.00 |
Minimum of Months | 0.538059E+09 | 0.173126E+10 | 0.207105E+10 | 0.724881E+09 | 0.134617E+10 | 0.00 | 0.00 |
Maximum of Months | 0.112022E+11 | 0.108482E+11 | 0.941511E+10 | 0.437705E+10 | 0.503806E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 19663990.89 | 0.172101E+11 | 0.183838E+10 | 0.00 | 0.183838E+10 | 0.00 | 0.00 |
February | 0.182082E+09 | 0.123135E+11 | 0.255062E+10 | 0.00 | 0.255062E+10 | 0.00 | 0.00 |
March | 0.470187E+09 | 0.105517E+11 | 0.347432E+10 | 0.00 | 0.347432E+10 | 0.00 | 0.00 |
April | 0.193503E+10 | 0.595276E+10 | 0.440769E+10 | 34401504.24 | 0.437329E+10 | 0.00 | 0.00 |
May | 0.537074E+10 | 0.331721E+10 | 0.640589E+10 | 0.344948E+09 | 0.606095E+10 | 0.00 | 0.00 |
June | 0.718374E+10 | 0.225814E+10 | 0.691846E+10 | 0.760524E+09 | 0.615794E+10 | 0.00 | 0.00 |
July | 0.746106E+10 | 0.220076E+10 | 0.682850E+10 | 0.586014E+09 | 0.624248E+10 | 0.00 | 0.00 |
August | 0.509749E+10 | 0.255225E+10 | 0.518646E+10 | 89067343.42 | 0.509739E+10 | 0.00 | 0.00 |
September | 0.282137E+10 | 0.391826E+10 | 0.391128E+10 | 958780.49 | 0.391032E+10 | 0.00 | 0.00 |
October | 0.985559E+09 | 0.612509E+10 | 0.280632E+10 | 0.00 | 0.280632E+10 | 0.00 | 0.00 |
November | 0.131715E+09 | 0.948316E+10 | 0.179820E+10 | 0.00 | 0.179820E+10 | 0.00 | 0.00 |
December | 1036690.57 | 0.164367E+11 | 0.155763E+10 | 0.00 | 0.155763E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.316597E+11 | 0.923196E+11 | 0.476837E+11 | 0.181591E+10 | 0.458678E+11 | 0.00 | 0.00 |
Minimum of Months | 1036690.57 | 0.220076E+10 | 0.155763E+10 | 0.00 | 0.155763E+10 | 0.00 | 0.00 |
Maximum of Months | 0.746106E+10 | 0.172101E+11 | 0.691846E+10 | 0.760524E+09 | 0.624248E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.898867E+09 | 0.103646E+11 | 0.268699E+10 | 0.112164E+10 | 0.156536E+10 | 0.00 | 0.00 |
February | 0.207289E+10 | 0.735239E+10 | 0.381376E+10 | 0.162678E+10 | 0.218698E+10 | 0.00 | 0.00 |
March | 0.405968E+10 | 0.643656E+10 | 0.575325E+10 | 0.288592E+10 | 0.286733E+10 | 0.00 | 0.00 |
April | 0.701560E+10 | 0.376641E+10 | 0.771840E+10 | 0.416315E+10 | 0.355525E+10 | 0.00 | 0.00 |
May | 0.901086E+10 | 0.225003E+10 | 0.863202E+10 | 0.379474E+10 | 0.483729E+10 | 0.00 | 0.00 |
June | 0.108798E+11 | 0.154641E+10 | 0.945682E+10 | 0.452372E+10 | 0.493310E+10 | 0.00 | 0.00 |
July | 0.113501E+11 | 0.148850E+10 | 0.957301E+10 | 0.449488E+10 | 0.507813E+10 | 0.00 | 0.00 |
August | 0.836982E+10 | 0.169888E+10 | 0.738081E+10 | 0.322593E+10 | 0.415488E+10 | 0.00 | 0.00 |
September | 0.572607E+10 | 0.251030E+10 | 0.572012E+10 | 0.256030E+10 | 0.315982E+10 | 0.00 | 0.00 |
October | 0.261942E+10 | 0.388509E+10 | 0.357909E+10 | 0.135718E+10 | 0.222190E+10 | 0.00 | 0.00 |
November | 0.974257E+09 | 0.583157E+10 | 0.220498E+10 | 0.737174E+09 | 0.146780E+10 | 0.00 | 0.00 |
December | 0.556884E+09 | 0.100388E+11 | 0.207909E+10 | 0.768464E+09 | 0.131062E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.635343E+11 | 0.571695E+11 | 0.685983E+11 | 0.312599E+11 | 0.373385E+11 | 0.00 | 0.00 |
Minimum of Months | 0.556884E+09 | 0.148850E+10 | 0.207909E+10 | 0.737174E+09 | 0.131062E+10 | 0.00 | 0.00 |
Maximum of Months | 0.113501E+11 | 0.103646E+11 | 0.957301E+10 | 0.452372E+10 | 0.507813E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.988577E+10 | 0.137531E+11 | 0.126592E+11 | 0.880674E+10 | 0.385248E+10 | 0.00 | 0.00 |
February | 0.128970E+11 | 0.104018E+11 | 0.144784E+11 | 0.977919E+10 | 0.469917E+10 | 0.00 | 0.00 |
March | 0.129246E+11 | 0.963565E+10 | 0.141240E+11 | 0.893855E+10 | 0.518548E+10 | 0.00 | 0.00 |
April | 0.124969E+11 | 0.615516E+10 | 0.123832E+11 | 0.672123E+10 | 0.566192E+10 | 0.00 | 0.00 |
May | 0.118315E+11 | 0.372480E+10 | 0.107580E+11 | 0.367791E+10 | 0.708010E+10 | 0.00 | 0.00 |
June | 0.110481E+11 | 0.248093E+10 | 0.934156E+10 | 0.248994E+10 | 0.685162E+10 | 0.00 | 0.00 |
July | 0.130637E+11 | 0.239826E+10 | 0.105538E+11 | 0.334339E+10 | 0.721041E+10 | 0.00 | 0.00 |
August | 0.135035E+11 | 0.277155E+10 | 0.112709E+11 | 0.471451E+10 | 0.655634E+10 | 0.00 | 0.00 |
September | 0.129086E+11 | 0.410227E+10 | 0.116833E+11 | 0.622225E+10 | 0.546108E+10 | 0.00 | 0.00 |
October | 0.100221E+11 | 0.602085E+10 | 0.103093E+11 | 0.606341E+10 | 0.424588E+10 | 0.00 | 0.00 |
November | 0.755875E+10 | 0.832688E+10 | 0.888707E+10 | 0.557754E+10 | 0.330953E+10 | 0.00 | 0.00 |
December | 0.702067E+10 | 0.133229E+11 | 0.977444E+10 | 0.640922E+10 | 0.336522E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.135161E+12 | 0.830941E+11 | 0.136223E+12 | 0.727439E+11 | 0.634792E+11 | 0.00 | 0.00 |
Minimum of Months | 0.702067E+10 | 0.239826E+10 | 0.888707E+10 | 0.248994E+10 | 0.330953E+10 | 0.00 | 0.00 |
Maximum of Months | 0.135035E+11 | 0.137531E+11 | 0.144784E+11 | 0.977919E+10 | 0.721041E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.100527E+10 | 0.107045E+11 | 0.271576E+10 | 0.113720E+10 | 0.157856E+10 | 0.00 | 0.00 |
February | 0.240071E+10 | 0.776869E+10 | 0.399656E+10 | 0.182536E+10 | 0.217120E+10 | 0.00 | 0.00 |
March | 0.430706E+10 | 0.683777E+10 | 0.582265E+10 | 0.297941E+10 | 0.284324E+10 | 0.00 | 0.00 |
April | 0.652010E+10 | 0.413178E+10 | 0.719818E+10 | 0.364581E+10 | 0.355237E+10 | 0.00 | 0.00 |
May | 0.987151E+10 | 0.252122E+10 | 0.913905E+10 | 0.435937E+10 | 0.477968E+10 | 0.00 | 0.00 |
June | 0.982128E+10 | 0.170921E+10 | 0.853450E+10 | 0.369025E+10 | 0.484425E+10 | 0.00 | 0.00 |
July | 0.111877E+11 | 0.170172E+10 | 0.941511E+10 | 0.437705E+10 | 0.503806E+10 | 0.00 | 0.00 |
August | 0.891577E+10 | 0.191253E+10 | 0.774801E+10 | 0.352065E+10 | 0.422736E+10 | 0.00 | 0.00 |
September | 0.597529E+10 | 0.273436E+10 | 0.586003E+10 | 0.263283E+10 | 0.322721E+10 | 0.00 | 0.00 |
October | 0.298856E+10 | 0.416464E+10 | 0.382522E+10 | 0.153561E+10 | 0.228961E+10 | 0.00 | 0.00 |
November | 0.104063E+10 | 0.612689E+10 | 0.224831E+10 | 0.758043E+09 | 0.149026E+10 | 0.00 | 0.00 |
December | 0.543378E+09 | 0.103808E+11 | 0.207105E+10 | 0.724881E+09 | 0.134617E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.645773E+11 | 0.606941E+11 | 0.685744E+11 | 0.311865E+11 | 0.373879E+11 | 0.00 | 0.00 |
Minimum of Months | 0.543378E+09 | 0.170172E+10 | 0.207105E+10 | 0.724881E+09 | 0.134617E+10 | 0.00 | 0.00 |
Maximum of Months | 0.111877E+11 | 0.107045E+11 | 0.941511E+10 | 0.437705E+10 | 0.503806E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | -16.9 | -17.4 | -20.0 | 3.73 | -31.9 | 33.25 | 98.18 | 0.00 |
February | -11.6 | -12.7 | -16.7 | 4.33 | -26.7 | 48.91 | 138.70 | 0.00 |
March | -6.2 | -7.6 | -10.8 | 3.55 | -19.4 | 56.69 | 163.76 | 0.01 |
April | 3.97 | 0.41 | -4.8 | 4.72 | -9.1 | 70.41 | 207.70 | 0.01 |
May | 13.43 | 8.45 | 3.53 | 3.60 | 2.20 | 102.27 | 202.62 | 0.00 |
June | 18.03 | 14.19 | 11.55 | 3.74 | 7.84 | 104.36 | 210.60 | 0.06 |
July | 19.67 | 16.51 | 14.78 | 3.14 | 8.97 | 101.67 | 223.82 | 0.04 |
August | 17.94 | 15.20 | 13.59 | 3.45 | 8.99 | 87.39 | 175.79 | 0.04 |
September | 12.29 | 9.87 | 7.80 | 3.78 | 3.34 | 70.27 | 143.96 | 0.00 |
October | 5.42 | 3.47 | 1.07 | 3.53 | -4.7 | 51.74 | 90.11 | 0.00 |
November | -2.0 | -3.6 | -6.9 | 4.42 | -13.7 | 34.68 | 65.95 | 0.00 |
December | -14.6 | -15.1 | -18.1 | 3.91 | -28.3 | 29.58 | 68.99 | 0.00 |
Annual Sum or Average | 3.36 | 1.04 | -2.0 | 3.82 | -8.4 | 66.03 | 149.18 | 0.01 |
Minimum of Months | -16.9 | -17.4 | -20.0 | 3.14 | -31.9 | 29.58 | 65.95 | 0.00 |
Maximum of Months | 19.67 | 16.51 | 14.78 | 4.72 | 8.99 | 104.36 | 223.82 | 0.06 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 1.10 | 29-JAN-14:00 | -1.0 | -4.4 | 2.60 | -11.4 | 145.00 | 110.00 |
February | 8.90 | 20-FEB-15:00 | 2.87 | -6.7 | 8.80 | -9.0 | 49.00 | 646.00 |
March | 11.10 | 26-MAR-15:00 | 5.48 | -1.1 | 5.20 | -5.7 | 53.00 | 842.00 |
April | 26.70 | 23-APR-15:00 | 16.95 | 11.10 | 11.30 | 12.03 | 75.50 | 811.00 |
May | 29.40 | 25-MAY-17:00 | 19.26 | 13.90 | 1.50 | 16.49 | 47.50 | 582.00 |
June | 35.00 | 29-JUN-15:00 | 24.72 | 21.10 | 6.70 | 24.66 | 132.00 | 705.00 |
July | 31.10 | 15-JUL-14:20 | 25.35 | 23.33 | 8.07 | 19.93 | 299.67 | 518.33 |
August | 30.60 | 08-AUG-14:00 | 23.36 | 20.60 | 6.70 | 17.93 | 163.50 | 672.50 |
September | 26.10 | 01-SEP-14:00 | 17.82 | 13.30 | 3.60 | 14.28 | 112.00 | 751.50 |
October | 22.20 | 19-OCT-14:00 | 13.62 | 7.20 | 6.70 | 8.15 | 35.50 | 701.50 |
November | 18.30 | 01-NOV-14:00 | 13.44 | 10.00 | 3.10 | 11.84 | 105.00 | 30.50 |
December | 1.10 | 28-DEC-02:00 | 0.43 | -0.6 | 4.60 | -5.5 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 1.10 | -1.0 | -6.7 | 1.50 | -11.4 | 0.00 | 0.00 | |
Maximum of Months | 35.00 | 25.35 | 23.33 | 11.30 | 24.66 | 299.67 | 842.00 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -35.6 | 06-JAN-08:00 | -35.7 | -37.8 | 0.00 | -57.8 | 27.00 | 381.00 |
February | -33.3 | 14-FEB-06:00 | -33.4 | -36.7 | 0.00 | -55.6 | 0.00 | 0.00 |
March | -28.9 | 05-MAR-06:00 | -29.1 | -32.2 | 1.50 | -50.6 | 27.00 | 41.50 |
April | -13.9 | 05-APR-05:00 | -14.4 | -16.1 | 0.00 | -32.5 | 14.50 | 199.00 |
May | -3.9 | 01-MAY-05:00 | -6.2 | -12.2 | 0.00 | -22.4 | 35.00 | 415.00 |
June | 1.10 | 04-JUN-04:00 | 0.62 | 0.00 | 0.00 | -14.9 | 37.00 | 169.50 |
July | 6.10 | 02-JUL-04:00 | 6.10 | 6.10 | 0.00 | -8.8 | 33.50 | 204.50 |
August | 4.40 | 19-AUG-03:00 | 4.40 | 4.40 | 0.00 | -10.7 | 0.00 | 0.00 |
September | 1.10 | 06-SEP-03:00 | 1.10 | 1.10 | 0.00 | -14.7 | 0.00 | 0.00 |
October | -10.0 | 30-OCT-03:00 | -10.7 | -12.8 | 1.50 | -28.2 | 0.00 | 0.00 |
November | -20.6 | 29-NOV-05:00 | -20.8 | -22.2 | 2.10 | -37.8 | 0.00 | 0.00 |
December | -31.1 | 24-DEC-06:19 | -31.3 | -35.1 | 3.33 | -53.1 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -35.6 | -35.7 | -37.8 | 0.00 | -57.8 | 0.00 | 0.00 | |
Maximum of Months | 6.10 | 6.10 | 6.10 | 3.33 | -8.8 | 37.00 | 415.00 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -0.5 | 16-JAN-12:00 | 0.00 | -1.1 | 5.70 | -6.6 | 172.50 | 3.00 |
February | 3.34 | 21-FEB-12:00 | 6.70 | -1.1 | 7.70 | -6.0 | 270.00 | 303.00 |
March | 5.48 | 26-MAR-15:00 | 11.10 | -1.1 | 5.20 | -5.7 | 53.00 | 842.00 |
April | 16.95 | 23-APR-15:00 | 26.70 | 11.10 | 11.30 | 12.03 | 75.50 | 811.00 |
May | 19.91 | 26-MAY-11:00 | 25.60 | 17.20 | 6.20 | 22.64 | 300.50 | 6.00 |
June | 24.72 | 29-JUN-15:00 | 35.00 | 21.10 | 6.70 | 24.66 | 132.00 | 705.00 |
July | 25.76 | 15-JUL-13:00 | 31.10 | 23.90 | 7.70 | 18.99 | 333.00 | 421.00 |
August | 23.36 | 08-AUG-14:00 | 30.60 | 20.60 | 6.70 | 17.93 | 163.50 | 672.50 |
September | 18.67 | 01-SEP-00:00 | 19.00 | 17.50 | 2.80 | 16.30 | 0.00 | 0.00 |
October | 13.72 | 19-OCT-13:00 | 21.70 | 7.80 | 5.70 | 7.75 | 54.50 | 739.00 |
November | 14.29 | 21-NOV-12:00 | 15.00 | 13.90 | 5.20 | 11.46 | 134.50 | 25.50 |
December | 0.43 | 28-DEC-02:00 | 1.10 | -0.6 | 4.60 | -5.5 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -0.5 | 0.00 | -1.1 | 2.80 | -6.6 | 0.00 | 0.00 | |
Maximum of Months | 25.76 | 35.00 | 23.90 | 11.30 | 24.66 | 333.00 | 842.00 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -1.1 | 16-JAN-11:00 | -0.6 | -0.8 | 5.70 | -7.3 | 164.50 | 5.00 |
February | -0.6 | 21-FEB-08:00 | 4.40 | 2.25 | 8.80 | -6.6 | 123.00 | 89.50 |
March | 0.00 | 29-MAR-20:00 | 1.70 | 0.95 | 1.50 | -4.8 | 0.00 | 0.00 |
April | 11.10 | 23-APR-13:00 | 24.40 | 16.08 | 10.80 | 9.72 | 98.50 | 903.50 |
May | 17.20 | 26-MAY-11:00 | 25.60 | 19.91 | 6.20 | 22.64 | 300.50 | 6.00 |
June | 22.80 | 29-JUN-23:19 | 26.30 | 23.71 | 5.20 | 14.28 | 0.00 | 0.00 |
July | 23.90 | 15-JUL-13:00 | 31.10 | 25.76 | 7.70 | 18.99 | 333.00 | 421.00 |
August | 20.60 | 08-AUG-14:00 | 30.60 | 23.36 | 6.70 | 17.93 | 163.50 | 672.50 |
September | 17.92 | 01-SEP-00:10 | 19.75 | 18.15 | 3.22 | 13.23 | 0.00 | 0.00 |
October | 12.20 | 07-OCT-12:20 | 14.47 | 13.17 | 3.43 | 9.20 | 163.17 | 18.50 |
November | 13.90 | 21-NOV-12:00 | 15.00 | 14.29 | 5.20 | 11.46 | 134.50 | 25.50 |
December | -0.0 | 05-DEC-17:00 | 0.00 | -0.0 | 1.50 | -6.4 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -1.1 | -0.6 | -0.8 | 1.50 | -7.3 | 0.00 | 0.00 | |
Maximum of Months | 23.90 | 31.10 | 25.76 | 10.80 | 22.64 | 333.00 | 903.50 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 1.89 | 11.66 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 0.58 | 19.92 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 0.81 | 26.63 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 2.58 | 37.52 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 5.43 | 45.25 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 8.61 | 47.76 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 11.25 | 48.86 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 12.66 | 38.94 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 12.41 | 29.23 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 10.60 | 17.37 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 7.72 | 10.89 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 4.55 | 9.11 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 6.63 | 28.63 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 0.58 | 9.11 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 12.66 | 48.86 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.464892E+11 | -0.454374E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.105180E+10 | 58.98 | 0.00 | 0.00 |
February | 0.431660E+11 | -0.422325E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -933445242.1 | 58.98 | 0.00 | 0.00 |
March | 0.505210E+11 | -0.494897E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.103128E+10 | 58.99 | 0.00 | 0.00 |
April | 0.445088E+11 | -0.435173E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -991416506.7 | 58.98 | 0.00 | 0.00 |
May | 0.451687E+11 | -0.441458E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.102297E+10 | 58.98 | 0.00 | 0.00 |
June | 0.421376E+11 | -0.411475E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -990105413.1 | 58.98 | 0.00 | 0.00 |
July | 0.380765E+11 | -0.370595E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.101704E+10 | 58.98 | 0.00 | 0.00 |
August | 0.404328E+11 | -0.394114E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.102145E+10 | 58.98 | 0.00 | 0.00 |
September | 0.369204E+11 | -0.359332E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -987143596.9 | 58.98 | 0.00 | 0.00 |
October | 0.395386E+11 | -0.385183E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.102034E+10 | 58.97 | 0.00 | 0.00 |
November | 0.410152E+11 | -0.400245E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -990723665.8 | 58.98 | 0.00 | 0.00 |
December | 0.433069E+11 | -0.422745E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.103236E+10 | 58.98 | 0.00 | 0.00 |
Annual Sum or Average | 0.511282E+12 | -0.499192E+12 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.120901E+11 | 58.98 | 0.00 | 0.00 |
Minimum of Months | 0.369204E+11 | -0.494897E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -0.105180E+10 | 58.97 | 0.00 | 0.00 |
Maximum of Months | 0.505210E+11 | -0.359332E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -933445242.1 | 58.99 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_1_DAYLCTRL
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 243.33 | 0.49 | 0.48 | 01-JAN-08:39 | 5711.58 | 36.01 | 239.83 | 239.17 | 4738.56 | 36.96 | 241.83 | 227.83 |
February | 265.33 | 0.49 | 0.48 | 01-FEB-08:39 | 8829.80 | 36.52 | 261.83 | 258.83 | 3735.18 | 30.65 | 232.50 | 241.83 |
March | 254.17 | 0.50 | 0.48 | 02-MAR-10:39 | 12441.99 | 35.71 | 242.33 | 324.17 | 2027.11 | 22.86 | 232.17 | 291.17 |
April | 296.33 | 0.52 | 0.48 | 01-APR-07:00 | 2631.77 | 20.43 | 135.67 | 352.33 | 1601.52 | 21.86 | 238.67 | 321.17 |
May | 437.50 | 0.51 | 0.48 | 01-MAY-06:19 | 2317.56 | 20.92 | 206.83 | 414.83 | 1284.43 | 22.34 | 307.50 | 374.17 |
June | 401.83 | 0.51 | 0.48 | 01-JUN-05:30 | 2212.70 | 20.98 | 202.17 | 415.00 | 1242.18 | 22.41 | 302.33 | 376.33 |
July | 409.17 | 0.50 | 0.48 | 01-JUL-05:30 | 2396.08 | 21.26 | 217.50 | 421.83 | 1354.93 | 22.69 | 321.50 | 384.67 |
August | 352.83 | 0.50 | 0.48 | 01-AUG-07:40 | 3020.85 | 21.88 | 203.67 | 380.67 | 1566.21 | 22.94 | 291.17 | 342.17 |
September | 344.17 | 0.50 | 0.48 | 01-SEP-06:49 | 5858.11 | 25.67 | 236.33 | 334.17 | 1613.06 | 22.97 | 253.33 | 302.00 |
October | 299.00 | 0.49 | 0.48 | 01-OCT-06:49 | 6244.62 | 32.37 | 277.50 | 298.83 | 1732.96 | 26.46 | 256.67 | 275.17 |
November | 255.50 | 0.51 | 0.48 | 01-NOV-08:09 | 4521.60 | 34.56 | 246.00 | 241.33 | 3706.50 | 35.75 | 248.50 | 220.83 |
December | 226.33 | 0.50 | 0.48 | 01-DEC-08:20 | 4253.41 | 34.12 | 215.33 | 225.00 | 3498.54 | 35.37 | 218.33 | 205.33 |
Annual Sum or Average | 3785.50 | 0.50 | 4656.05 | 27.12 | 2685.00 | 3906.17 | 2143.49 | 26.03 | 3144.50 | 3562.67 | ||
Minimum of Months | 226.33 | 0.49 | 0.48 | 2212.70 | 20.43 | 135.67 | 225.00 | 1242.18 | 21.86 | 218.33 | 205.33 | |
Maximum of Months | 437.50 | 0.52 | 0.48 | 12441.99 | 36.52 | 277.50 | 421.83 | 4738.56 | 36.96 | 321.50 | 384.67 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_2_DAYLCTRL
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 243.33 | 0.52 | 0.48 | 01-JAN-08:39 | 1911.24 | 25.04 | 118.50 | 225.17 | 1111.59 | 25.14 | 157.00 | 195.33 |
February | 265.33 | 0.51 | 0.48 | 01-FEB-08:39 | 2531.35 | 25.10 | 140.83 | 249.50 | 1348.16 | 25.18 | 185.83 | 225.17 |
March | 254.17 | 0.50 | 0.48 | 02-MAR-10:39 | 4274.53 | 26.83 | 124.33 | 320.50 | 2579.51 | 26.98 | 190.00 | 285.50 |
April | 296.33 | 0.51 | 0.48 | 01-APR-06:00 | 4571.60 | 25.72 | 124.00 | 358.33 | 2674.87 | 25.98 | 199.17 | 328.33 |
May | 437.50 | 0.50 | 0.48 | 01-MAY-05:10 | 4150.62 | 25.10 | 187.67 | 424.50 | 1849.82 | 24.84 | 282.67 | 390.33 |
June | 401.83 | 0.50 | 0.48 | 01-JUN-04:49 | 5040.49 | 25.96 | 158.50 | 422.50 | 2348.32 | 25.59 | 270.67 | 390.50 |
July | 409.17 | 0.50 | 0.48 | 01-JUL-04:49 | 4820.18 | 26.02 | 171.00 | 428.33 | 2221.63 | 25.58 | 286.67 | 396.50 |
August | 352.83 | 0.50 | 0.48 | 01-AUG-07:40 | 4041.44 | 25.13 | 142.67 | 384.33 | 1799.99 | 24.72 | 246.83 | 351.00 |
September | 344.17 | 0.50 | 0.48 | 01-SEP-06:19 | 3155.86 | 24.00 | 155.67 | 334.17 | 1673.76 | 24.42 | 224.17 | 301.17 |
October | 299.00 | 0.50 | 0.48 | 01-OCT-06:40 | 2360.86 | 24.38 | 139.50 | 290.67 | 1038.70 | 23.83 | 189.67 | 252.67 |
November | 255.50 | 0.52 | 0.48 | 01-NOV-07:00 | 1568.24 | 23.90 | 103.00 | 228.50 | 853.23 | 24.14 | 153.00 | 191.00 |
December | 226.33 | 0.52 | 0.48 | 01-DEC-08:20 | 1390.81 | 23.36 | 84.50 | 207.83 | 918.06 | 24.77 | 130.67 | 175.33 |
Annual Sum or Average | 3785.50 | 0.51 | 3519.99 | 25.11 | 1650.17 | 3874.33 | 1766.20 | 25.09 | 2516.33 | 3482.83 | ||
Minimum of Months | 226.33 | 0.50 | 0.48 | 1390.81 | 23.36 | 84.50 | 207.83 | 853.23 | 23.83 | 130.67 | 175.33 | |
Maximum of Months | 437.50 | 0.52 | 0.48 | 5040.49 | 26.83 | 187.67 | 428.33 | 2674.87 | 26.98 | 286.67 | 396.50 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_3_DAYLCTRL
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 243.33 | 0.54 | 0.48 | 01-JAN-10:20 | 712.91 | 17.67 | 0.00 | 210.83 | 409.06 | 19.31 | 10.50 | 156.17 |
February | 265.33 | 0.52 | 0.48 | 01-FEB-09:30 | 906.20 | 18.84 | 0.00 | 240.17 | 537.98 | 20.45 | 77.50 | 200.67 |
March | 254.17 | 0.51 | 0.48 | 02-MAR-10:39 | 990.99 | 19.37 | 1.50 | 313.67 | 626.85 | 20.95 | 102.50 | 261.83 |
April | 296.33 | 0.51 | 0.48 | 01-APR-08:09 | 1127.42 | 19.69 | 25.17 | 356.50 | 709.83 | 21.12 | 148.33 | 322.83 |
May | 437.50 | 0.49 | 0.48 | 01-MAY-05:30 | 1521.42 | 22.71 | 163.50 | 432.17 | 867.94 | 23.21 | 345.50 | 411.00 |
June | 401.83 | 0.49 | 0.48 | 01-JUN-04:49 | 1799.01 | 23.97 | 214.50 | 440.50 | 990.19 | 24.14 | 348.00 | 409.33 |
July | 409.17 | 0.49 | 0.48 | 01-JUL-04:49 | 1722.52 | 23.53 | 218.67 | 440.83 | 1011.20 | 24.81 | 362.83 | 417.50 |
August | 352.83 | 0.49 | 0.48 | 01-AUG-07:40 | 1428.86 | 20.96 | 101.67 | 388.17 | 853.78 | 22.33 | 262.00 | 353.83 |
September | 344.17 | 0.50 | 0.48 | 01-SEP-06:49 | 1096.26 | 19.82 | 1.17 | 332.00 | 641.64 | 21.22 | 176.83 | 288.83 |
October | 299.00 | 0.52 | 0.48 | 01-OCT-07:19 | 893.98 | 18.80 | 0.00 | 280.50 | 499.90 | 20.21 | 54.33 | 224.83 |
November | 255.50 | 0.55 | 0.48 | 01-NOV-08:50 | 690.39 | 17.48 | 0.00 | 215.17 | 382.95 | 18.88 | 1.33 | 149.33 |
December | 226.33 | 0.55 | 0.48 | 01-DEC-09:30 | 658.69 | 17.40 | 0.00 | 194.50 | 365.78 | 18.92 | 1.83 | 128.83 |
Annual Sum or Average | 3785.50 | 0.51 | 1206.56 | 20.47 | 726.17 | 3845.00 | 701.49 | 21.67 | 1891.50 | 3325.00 | ||
Minimum of Months | 226.33 | 0.49 | 0.48 | 658.69 | 17.40 | 0.00 | 194.50 | 365.78 | 18.88 | 1.33 | 128.83 | |
Maximum of Months | 437.50 | 0.55 | 0.48 | 1799.01 | 23.97 | 218.67 | 440.83 | 1011.20 | 24.81 | 362.83 | 417.50 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_4_DAYLCTRL
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 243.33 | 0.52 | 0.48 | 01-JAN-10:20 | 1859.50 | 24.95 | 113.50 | 226.50 | 1050.56 | 24.96 | 156.50 | 197.33 |
February | 265.33 | 0.51 | 0.48 | 01-FEB-09:30 | 2543.52 | 25.33 | 145.00 | 251.67 | 1365.37 | 25.38 | 189.17 | 227.33 |
March | 254.17 | 0.50 | 0.48 | 02-MAR-10:39 | 3919.54 | 25.54 | 117.33 | 320.17 | 2267.93 | 25.74 | 188.50 | 284.17 |
April | 296.33 | 0.51 | 0.48 | 01-APR-08:20 | 4667.97 | 24.22 | 111.83 | 355.50 | 2030.53 | 23.39 | 174.83 | 325.67 |
May | 437.50 | 0.50 | 0.48 | 01-MAY-06:30 | 3810.78 | 22.49 | 133.83 | 423.17 | 2183.38 | 23.38 | 254.17 | 396.00 |
June | 401.83 | 0.49 | 0.48 | 01-JUN-05:30 | 4086.04 | 21.60 | 84.17 | 433.33 | 1798.26 | 22.07 | 256.50 | 401.17 |
July | 409.17 | 0.49 | 0.48 | 01-JUL-05:40 | 4401.96 | 22.02 | 95.33 | 436.00 | 1956.30 | 22.28 | 254.17 | 405.67 |
August | 352.83 | 0.49 | 0.48 | 01-AUG-07:49 | 3999.62 | 23.74 | 135.33 | 386.50 | 2234.73 | 24.30 | 235.67 | 351.50 |
September | 344.17 | 0.50 | 0.48 | 01-SEP-07:10 | 3395.05 | 24.41 | 155.50 | 334.67 | 1928.98 | 24.89 | 224.83 | 303.83 |
October | 299.00 | 0.50 | 0.48 | 01-OCT-07:30 | 2543.52 | 25.08 | 141.50 | 291.33 | 1085.74 | 24.21 | 184.83 | 254.00 |
November | 255.50 | 0.53 | 0.48 | 01-NOV-08:50 | 1549.06 | 23.76 | 103.50 | 229.33 | 812.62 | 23.84 | 149.33 | 193.17 |
December | 226.33 | 0.52 | 0.48 | 01-DEC-09:30 | 1420.29 | 22.91 | 84.50 | 213.83 | 738.84 | 23.10 | 126.17 | 176.83 |
Annual Sum or Average | 3785.50 | 0.50 | 3348.18 | 23.65 | 1421.33 | 3902.00 | 1697.58 | 23.83 | 2394.67 | 3516.67 | ||
Minimum of Months | 226.33 | 0.49 | 0.48 | 1420.29 | 21.60 | 84.17 | 213.83 | 738.84 | 22.07 | 126.17 | 176.83 | |
Maximum of Months | 437.50 | 0.53 | 0.48 | 4667.97 | 25.54 | 155.50 | 436.00 | 2267.93 | 25.74 | 256.50 | 405.67 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_1_DAYLCTRL
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 243.33 | 0.49 | 0.48 | 01-JAN-08:39 | 5752.13 | 35.44 | 233.33 | 239.17 | 4880.29 | 36.50 | 234.17 | 228.50 |
February | 265.33 | 0.49 | 0.48 | 01-FEB-08:39 | 8890.07 | 35.98 | 256.50 | 258.83 | 4826.55 | 32.01 | 200.33 | 246.33 |
March | 254.17 | 0.50 | 0.48 | 02-MAR-10:39 | 12525.61 | 34.67 | 215.00 | 324.33 | 2184.39 | 18.16 | 11.67 | 293.33 |
April | 296.33 | 0.52 | 0.48 | 01-APR-07:49 | 2698.82 | 14.12 | 0.00 | 352.33 | 1725.18 | 17.70 | 12.33 | 324.50 |
May | 437.50 | 0.50 | 0.48 | 01-MAY-06:19 | 2353.06 | 14.78 | 0.00 | 415.33 | 1371.96 | 18.24 | 1.67 | 380.67 |
June | 401.83 | 0.51 | 0.48 | 01-JUN-05:19 | 2248.21 | 15.08 | 0.00 | 415.17 | 1326.18 | 18.53 | 0.17 | 380.83 |
July | 409.17 | 0.50 | 0.48 | 01-JUL-05:30 | 2436.80 | 15.35 | 0.00 | 422.00 | 1447.84 | 18.82 | 8.00 | 387.00 |
August | 352.83 | 0.50 | 0.48 | 01-AUG-07:40 | 3064.64 | 15.90 | 10.00 | 380.83 | 1674.79 | 18.79 | 23.00 | 346.33 |
September | 344.17 | 0.50 | 0.48 | 01-SEP-06:40 | 5899.60 | 21.52 | 115.00 | 334.83 | 1725.19 | 18.49 | 19.00 | 306.00 |
October | 299.00 | 0.49 | 0.48 | 01-OCT-06:49 | 6276.22 | 31.37 | 264.17 | 299.00 | 1834.08 | 22.86 | 106.67 | 277.50 |
November | 255.50 | 0.50 | 0.48 | 01-NOV-08:09 | 4548.06 | 34.02 | 243.67 | 241.33 | 3802.53 | 35.31 | 245.67 | 223.50 |
December | 226.33 | 0.50 | 0.48 | 01-DEC-08:20 | 4276.70 | 33.32 | 207.50 | 225.17 | 3598.88 | 34.71 | 211.17 | 207.00 |
Annual Sum or Average | 3785.50 | 0.50 | 4699.54 | 23.41 | 1545.17 | 3908.33 | 2319.20 | 23.00 | 1073.83 | 3601.50 | ||
Minimum of Months | 226.33 | 0.49 | 0.48 | 2248.21 | 14.12 | 0.00 | 225.17 | 1326.18 | 17.70 | 0.17 | 207.00 | |
Maximum of Months | 437.50 | 0.52 | 0.48 | 12525.61 | 35.98 | 264.17 | 422.00 | 4880.29 | 36.50 | 245.67 | 387.00 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_2_DAYLCTRL
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 243.33 | 0.52 | 0.48 | 01-JAN-08:39 | 1941.12 | 22.89 | 99.17 | 225.67 | 1154.17 | 23.54 | 88.67 | 198.67 |
February | 265.33 | 0.51 | 0.48 | 01-FEB-08:39 | 2577.93 | 22.60 | 86.67 | 249.67 | 1410.43 | 23.29 | 98.17 | 227.00 |
March | 254.17 | 0.50 | 0.48 | 02-MAR-10:39 | 4280.02 | 22.77 | 80.83 | 320.83 | 2668.11 | 25.08 | 87.67 | 288.50 |
April | 296.33 | 0.51 | 0.48 | 01-APR-06:00 | 4592.69 | 21.62 | 84.33 | 359.00 | 2777.08 | 23.80 | 75.83 | 332.17 |
May | 437.50 | 0.50 | 0.48 | 01-MAY-05:10 | 4204.47 | 21.66 | 135.17 | 424.67 | 1936.49 | 22.34 | 86.50 | 393.50 |
June | 401.83 | 0.50 | 0.48 | 01-JUN-04:49 | 5107.15 | 23.14 | 133.00 | 423.33 | 2449.08 | 23.16 | 83.17 | 394.33 |
July | 409.17 | 0.50 | 0.48 | 01-JUL-04:40 | 4870.10 | 22.53 | 126.00 | 429.17 | 2323.24 | 23.14 | 81.67 | 400.33 |
August | 352.83 | 0.50 | 0.48 | 01-AUG-07:40 | 4105.07 | 22.18 | 99.83 | 384.83 | 1889.17 | 22.19 | 60.83 | 355.67 |
September | 344.17 | 0.50 | 0.48 | 01-SEP-06:19 | 3215.12 | 21.03 | 96.83 | 334.33 | 1746.13 | 22.11 | 72.83 | 304.83 |
October | 299.00 | 0.50 | 0.48 | 01-OCT-06:40 | 2379.27 | 21.15 | 99.50 | 290.83 | 1089.87 | 21.64 | 62.17 | 257.33 |
November | 255.50 | 0.52 | 0.48 | 01-NOV-07:00 | 1594.91 | 21.46 | 90.33 | 228.83 | 890.10 | 22.30 | 71.67 | 194.83 |
December | 226.33 | 0.52 | 0.48 | 01-DEC-08:20 | 1416.00 | 20.79 | 67.33 | 208.67 | 952.98 | 23.13 | 78.67 | 179.33 |
Annual Sum or Average | 3785.50 | 0.50 | 3561.97 | 22.01 | 1199.00 | 3879.83 | 1842.45 | 22.91 | 947.83 | 3526.50 | ||
Minimum of Months | 226.33 | 0.50 | 0.48 | 1416.00 | 20.79 | 67.33 | 208.67 | 890.10 | 21.64 | 60.83 | 179.33 | |
Maximum of Months | 437.50 | 0.52 | 0.48 | 5107.15 | 23.14 | 135.17 | 429.17 | 2777.08 | 25.08 | 98.17 | 400.33 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_3_DAYLCTRL
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 243.33 | 0.54 | 0.48 | 01-JAN-10:09 | 720.98 | 11.76 | 0.00 | 211.33 | 434.20 | 15.38 | 0.00 | 165.33 |
February | 265.33 | 0.52 | 0.48 | 01-FEB-09:30 | 918.29 | 13.18 | 0.00 | 240.33 | 571.80 | 16.74 | 0.00 | 206.00 |
March | 254.17 | 0.51 | 0.48 | 02-MAR-10:39 | 1009.19 | 14.07 | 0.00 | 314.17 | 668.05 | 17.64 | 0.00 | 269.00 |
April | 296.33 | 0.51 | 0.48 | 01-APR-07:00 | 1151.70 | 14.51 | 0.00 | 356.67 | 757.79 | 18.03 | 4.00 | 327.00 |
May | 437.50 | 0.49 | 0.48 | 01-MAY-05:19 | 1547.60 | 17.79 | 53.67 | 432.33 | 930.72 | 20.92 | 69.17 | 415.67 |
June | 401.83 | 0.49 | 0.48 | 01-JUN-04:49 | 1830.45 | 19.35 | 76.83 | 440.50 | 1094.57 | 22.39 | 113.83 | 417.67 |
July | 409.17 | 0.49 | 0.48 | 01-JUL-04:49 | 1756.79 | 18.85 | 65.17 | 441.00 | 1075.52 | 21.98 | 110.33 | 419.33 |
August | 352.83 | 0.49 | 0.48 | 01-AUG-07:40 | 1471.84 | 15.54 | 0.00 | 388.67 | 909.11 | 19.01 | 31.00 | 356.67 |
September | 344.17 | 0.50 | 0.48 | 01-SEP-06:49 | 1113.55 | 14.32 | 0.00 | 332.17 | 682.85 | 17.74 | 0.00 | 294.17 |
October | 299.00 | 0.51 | 0.48 | 01-OCT-07:19 | 905.47 | 12.96 | 0.00 | 281.17 | 531.06 | 16.40 | 0.00 | 232.83 |
November | 255.50 | 0.55 | 0.48 | 01-NOV-08:50 | 698.13 | 11.38 | 0.00 | 215.33 | 406.41 | 14.85 | 0.00 | 156.50 |
December | 226.33 | 0.54 | 0.48 | 01-DEC-09:20 | 665.67 | 11.28 | 0.00 | 194.67 | 388.03 | 14.85 | 0.00 | 140.17 |
Annual Sum or Average | 3785.50 | 0.51 | 1228.54 | 15.12 | 195.67 | 3848.33 | 751.56 | 18.50 | 328.33 | 3400.33 | ||
Minimum of Months | 226.33 | 0.49 | 0.48 | 665.67 | 11.28 | 0.00 | 194.67 | 388.03 | 14.85 | 0.00 | 140.17 | |
Maximum of Months | 437.50 | 0.55 | 0.48 | 1830.45 | 19.35 | 76.83 | 441.00 | 1094.57 | 22.39 | 113.83 | 419.33 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_4_DAYLCTRL
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 243.33 | 0.52 | 0.48 | 01-JAN-10:09 | 1889.09 | 22.70 | 92.67 | 227.67 | 1094.10 | 23.32 | 83.00 | 200.67 |
February | 265.33 | 0.50 | 0.48 | 01-FEB-09:30 | 2539.98 | 21.43 | 75.33 | 251.50 | 1428.89 | 23.48 | 95.67 | 229.33 |
March | 254.17 | 0.50 | 0.48 | 02-MAR-10:39 | 3989.72 | 22.80 | 78.83 | 321.17 | 2352.86 | 23.63 | 72.50 | 287.67 |
April | 296.33 | 0.51 | 0.48 | 01-APR-08:09 | 4742.17 | 21.18 | 84.50 | 355.67 | 2125.42 | 20.69 | 40.67 | 329.67 |
May | 437.50 | 0.50 | 0.48 | 01-MAY-06:30 | 3873.97 | 18.89 | 81.00 | 424.00 | 2272.84 | 20.56 | 51.83 | 398.50 |
June | 401.83 | 0.49 | 0.48 | 01-JUN-05:30 | 4143.94 | 17.71 | 46.83 | 433.83 | 1888.66 | 18.80 | 0.00 | 404.17 |
July | 409.17 | 0.49 | 0.48 | 01-JUL-05:30 | 4465.21 | 18.18 | 53.67 | 436.83 | 2055.01 | 19.03 | 2.17 | 408.50 |
August | 352.83 | 0.49 | 0.48 | 01-AUG-07:49 | 4045.99 | 20.40 | 79.17 | 388.00 | 2330.65 | 21.64 | 58.50 | 355.33 |
September | 344.17 | 0.50 | 0.48 | 01-SEP-06:00 | 3410.48 | 21.35 | 99.83 | 334.83 | 2004.82 | 22.61 | 78.17 | 306.83 |
October | 299.00 | 0.50 | 0.48 | 01-OCT-07:19 | 2561.03 | 21.64 | 102.67 | 291.50 | 1139.23 | 21.99 | 65.17 | 258.67 |
November | 255.50 | 0.52 | 0.48 | 01-NOV-08:50 | 1575.20 | 21.26 | 86.67 | 230.33 | 849.51 | 21.92 | 72.67 | 196.83 |
December | 226.33 | 0.52 | 0.48 | 01-DEC-09:20 | 1444.26 | 20.35 | 65.67 | 214.83 | 773.03 | 21.16 | 58.00 | 181.50 |
Annual Sum or Average | 3785.50 | 0.50 | 3390.94 | 20.38 | 946.83 | 3910.17 | 1773.16 | 21.33 | 678.33 | 3557.67 | ||
Minimum of Months | 226.33 | 0.49 | 0.48 | 1444.26 | 17.71 | 46.83 | 214.83 | 773.03 | 18.80 | 0.00 | 181.50 | |
Maximum of Months | 437.50 | 0.52 | 0.48 | 4742.17 | 22.80 | 102.67 | 436.83 | 2352.86 | 23.63 | 95.67 | 408.50 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_1_DAYLCTRL
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 243.33 | 0.49 | 0.48 | 01-JAN-08:39 | 5753.53 | 35.43 | 233.33 | 239.17 | 4882.46 | 36.49 | 234.17 | 228.50 |
February | 265.33 | 0.49 | 0.48 | 01-FEB-08:39 | 8892.29 | 35.98 | 256.50 | 258.83 | 4829.67 | 32.01 | 200.33 | 246.33 |
March | 254.17 | 0.50 | 0.48 | 02-MAR-10:39 | 12528.62 | 34.66 | 215.00 | 324.33 | 2187.22 | 18.14 | 11.33 | 293.50 |
April | 296.33 | 0.52 | 0.48 | 01-APR-07:49 | 2702.03 | 14.09 | 0.00 | 352.33 | 1727.32 | 17.69 | 12.17 | 324.67 |
May | 437.50 | 0.50 | 0.48 | 01-MAY-06:19 | 2356.55 | 14.75 | 0.00 | 415.33 | 1374.08 | 18.22 | 1.50 | 381.00 |
June | 401.83 | 0.51 | 0.48 | 01-JUN-05:19 | 2251.36 | 15.05 | 0.00 | 415.17 | 1328.15 | 18.52 | 0.00 | 381.00 |
July | 409.17 | 0.50 | 0.48 | 01-JUL-05:30 | 2440.16 | 15.32 | 0.00 | 422.17 | 1449.96 | 18.80 | 7.33 | 387.00 |
August | 352.83 | 0.50 | 0.48 | 01-AUG-07:40 | 3068.69 | 15.87 | 10.00 | 381.00 | 1677.35 | 18.78 | 22.17 | 346.50 |
September | 344.17 | 0.50 | 0.48 | 01-SEP-06:40 | 5903.35 | 21.50 | 115.00 | 334.83 | 1727.85 | 18.47 | 18.83 | 306.00 |
October | 299.00 | 0.49 | 0.48 | 01-OCT-06:49 | 6278.90 | 31.36 | 264.17 | 299.17 | 1836.65 | 22.85 | 106.67 | 277.50 |
November | 255.50 | 0.50 | 0.48 | 01-NOV-08:09 | 4549.61 | 34.01 | 243.67 | 241.33 | 3804.69 | 35.30 | 245.67 | 223.50 |
December | 226.33 | 0.50 | 0.48 | 01-DEC-08:20 | 4278.15 | 33.31 | 207.50 | 225.33 | 3600.74 | 34.71 | 211.00 | 207.00 |
Annual Sum or Average | 3785.50 | 0.50 | 4702.47 | 23.39 | 1545.17 | 3909.00 | 2321.53 | 22.99 | 1071.17 | 3602.50 | ||
Minimum of Months | 226.33 | 0.49 | 0.48 | 2251.36 | 14.09 | 0.00 | 225.33 | 1328.15 | 17.69 | 0.00 | 207.00 | |
Maximum of Months | 437.50 | 0.52 | 0.48 | 12528.62 | 35.98 | 264.17 | 422.17 | 4882.46 | 36.49 | 245.67 | 387.00 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_2_DAYLCTRL
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 243.33 | 0.52 | 0.48 | 01-JAN-08:39 | 1942.31 | 22.86 | 99.00 | 225.67 | 1155.32 | 23.53 | 88.67 | 199.00 |
February | 265.33 | 0.51 | 0.48 | 01-FEB-08:39 | 2516.84 | 21.10 | 73.83 | 249.67 | 1411.92 | 23.27 | 97.83 | 227.17 |
March | 254.17 | 0.50 | 0.48 | 02-MAR-10:39 | 4281.45 | 22.74 | 80.83 | 321.17 | 2669.71 | 25.07 | 87.50 | 288.67 |
April | 296.33 | 0.51 | 0.48 | 01-APR-06:00 | 4594.16 | 21.59 | 84.33 | 359.00 | 2778.74 | 23.78 | 75.83 | 332.17 |
May | 437.50 | 0.50 | 0.48 | 01-MAY-05:10 | 4207.11 | 21.63 | 135.17 | 424.83 | 1938.56 | 22.33 | 86.50 | 393.50 |
June | 401.83 | 0.50 | 0.48 | 01-JUN-04:49 | 5109.68 | 23.11 | 133.00 | 423.33 | 2451.31 | 23.14 | 83.17 | 394.33 |
July | 409.17 | 0.50 | 0.48 | 01-JUL-04:40 | 4872.57 | 22.50 | 126.00 | 429.17 | 2325.51 | 23.13 | 81.67 | 400.33 |
August | 352.83 | 0.50 | 0.48 | 01-AUG-07:40 | 4107.36 | 22.15 | 99.83 | 384.83 | 1891.29 | 22.18 | 60.67 | 355.67 |
September | 344.17 | 0.50 | 0.48 | 01-SEP-06:19 | 3217.01 | 21.00 | 96.83 | 334.50 | 1747.87 | 22.10 | 72.50 | 305.00 |
October | 299.00 | 0.50 | 0.48 | 01-OCT-06:40 | 2380.96 | 21.12 | 99.50 | 290.83 | 1091.29 | 21.63 | 62.00 | 257.50 |
November | 255.50 | 0.52 | 0.48 | 01-NOV-07:00 | 1596.19 | 21.43 | 90.33 | 228.83 | 891.21 | 22.29 | 71.50 | 194.83 |
December | 226.33 | 0.52 | 0.48 | 01-DEC-08:20 | 1417.18 | 20.76 | 67.33 | 208.67 | 954.02 | 23.12 | 78.50 | 179.50 |
Annual Sum or Average | 3785.50 | 0.50 | 3559.50 | 21.88 | 1186.00 | 3880.50 | 1844.19 | 22.90 | 946.33 | 3527.67 | ||
Minimum of Months | 226.33 | 0.50 | 0.48 | 1417.18 | 20.76 | 67.33 | 208.67 | 891.21 | 21.63 | 60.67 | 179.50 | |
Maximum of Months | 437.50 | 0.52 | 0.48 | 5109.68 | 23.11 | 135.17 | 429.17 | 2778.74 | 25.07 | 97.83 | 400.33 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_3_DAYLCTRL
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 243.33 | 0.54 | 0.48 | 01-JAN-10:09 | 721.75 | 11.73 | 0.00 | 211.33 | 434.84 | 15.37 | 0.00 | 165.50 |
February | 265.33 | 0.52 | 0.48 | 01-FEB-09:30 | 919.16 | 13.15 | 0.00 | 240.33 | 572.58 | 16.73 | 0.00 | 206.00 |
March | 254.17 | 0.51 | 0.48 | 02-MAR-10:39 | 1009.89 | 14.04 | 0.00 | 314.17 | 668.82 | 17.63 | 0.00 | 269.67 |
April | 296.33 | 0.51 | 0.48 | 01-APR-07:00 | 1152.52 | 14.48 | 0.00 | 356.67 | 758.63 | 18.01 | 3.83 | 327.00 |
May | 437.50 | 0.49 | 0.48 | 01-MAY-05:19 | 1549.28 | 17.76 | 53.67 | 432.33 | 932.00 | 20.90 | 69.00 | 415.67 |
June | 401.83 | 0.49 | 0.48 | 01-JUN-04:49 | 1832.12 | 19.32 | 76.83 | 440.50 | 1095.97 | 22.38 | 113.33 | 417.67 |
July | 409.17 | 0.49 | 0.48 | 01-JUL-04:49 | 1758.34 | 18.82 | 65.17 | 441.00 | 1076.88 | 21.97 | 110.17 | 419.50 |
August | 352.83 | 0.49 | 0.48 | 01-AUG-07:40 | 1473.27 | 15.51 | 0.00 | 388.67 | 910.32 | 19.00 | 29.67 | 356.67 |
September | 344.17 | 0.50 | 0.48 | 01-SEP-06:49 | 1114.76 | 14.29 | 0.00 | 332.17 | 683.81 | 17.73 | 0.00 | 294.33 |
October | 299.00 | 0.51 | 0.48 | 01-OCT-07:19 | 906.63 | 12.93 | 0.00 | 281.17 | 531.89 | 16.39 | 0.00 | 233.67 |
November | 255.50 | 0.55 | 0.48 | 01-NOV-08:50 | 699.01 | 11.35 | 0.00 | 215.50 | 407.06 | 14.84 | 0.00 | 157.17 |
December | 226.33 | 0.54 | 0.48 | 01-DEC-09:20 | 666.49 | 11.25 | 0.00 | 194.67 | 388.65 | 14.83 | 0.00 | 140.67 |
Annual Sum or Average | 3785.50 | 0.51 | 1229.74 | 15.09 | 195.67 | 3848.50 | 752.57 | 18.48 | 326.00 | 3403.50 | ||
Minimum of Months | 226.33 | 0.49 | 0.48 | 666.49 | 11.25 | 0.00 | 194.67 | 388.65 | 14.83 | 0.00 | 140.67 | |
Maximum of Months | 437.50 | 0.55 | 0.48 | 1832.12 | 19.32 | 76.83 | 441.00 | 1095.97 | 22.38 | 113.33 | 419.50 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_4_DAYLCTRL
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 243.33 | 0.52 | 0.48 | 01-JAN-10:09 | 1890.28 | 22.68 | 92.67 | 227.67 | 1095.24 | 23.31 | 83.00 | 200.83 |
February | 265.33 | 0.50 | 0.48 | 01-FEB-09:30 | 2541.39 | 21.40 | 75.33 | 251.67 | 1430.36 | 23.47 | 94.83 | 229.50 |
March | 254.17 | 0.50 | 0.48 | 02-MAR-10:39 | 3991.07 | 22.77 | 78.83 | 321.17 | 2354.46 | 23.61 | 71.83 | 287.67 |
April | 296.33 | 0.51 | 0.48 | 01-APR-08:09 | 4743.71 | 21.16 | 84.50 | 355.67 | 2127.07 | 20.67 | 40.67 | 329.83 |
May | 437.50 | 0.50 | 0.48 | 01-MAY-06:30 | 3876.39 | 18.86 | 81.00 | 424.00 | 2274.83 | 20.54 | 51.83 | 398.50 |
June | 401.83 | 0.49 | 0.48 | 01-JUN-05:30 | 4146.40 | 17.68 | 46.83 | 433.83 | 1890.80 | 18.79 | 0.00 | 404.17 |
July | 409.17 | 0.49 | 0.48 | 01-JUL-05:30 | 4467.68 | 18.15 | 53.67 | 436.83 | 2057.23 | 19.01 | 2.17 | 408.50 |
August | 352.83 | 0.49 | 0.48 | 01-AUG-07:49 | 4048.47 | 20.37 | 79.17 | 388.00 | 2332.91 | 21.62 | 58.50 | 355.33 |
September | 344.17 | 0.50 | 0.48 | 01-SEP-06:00 | 3412.52 | 21.33 | 99.83 | 335.00 | 2006.61 | 22.59 | 77.67 | 307.00 |
October | 299.00 | 0.50 | 0.48 | 01-OCT-07:19 | 2562.77 | 21.62 | 102.50 | 291.50 | 1140.73 | 21.97 | 64.83 | 258.67 |
November | 255.50 | 0.52 | 0.48 | 01-NOV-08:50 | 1576.48 | 21.23 | 86.67 | 230.33 | 850.63 | 21.91 | 72.33 | 197.00 |
December | 226.33 | 0.52 | 0.48 | 01-DEC-09:20 | 1445.45 | 20.33 | 65.67 | 214.83 | 774.09 | 21.15 | 57.83 | 182.00 |
Annual Sum or Average | 3785.50 | 0.50 | 3392.85 | 20.36 | 946.67 | 3910.50 | 1774.91 | 21.32 | 675.50 | 3559.00 | ||
Minimum of Months | 226.33 | 0.49 | 0.48 | 1445.45 | 17.68 | 46.83 | 214.83 | 774.09 | 18.79 | 0.00 | 182.00 | |
Maximum of Months | 437.50 | 0.52 | 0.48 | 4743.71 | 22.77 | 102.50 | 436.83 | 2354.46 | 23.61 | 94.83 | 408.50 |
Report: CoilReportMonthly
For: VAV_BOT WITH REHEAT HEATING COIL
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.366628E+11 | 125772.97 | 09-JAN-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.138838E+11 | 122332.67 | 14-FEB-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.539866E+10 | 107796.50 | 15-MAR-06:55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.163951E+10 | 76739.38 | 05-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.178546E+09 | 29620.47 | 01-MAY-07:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 2367970.25 | 2899.43 | 02-JUN-20:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 5.14 | 0.01 | 26-JUL-20:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 3105444.49 | 4338.58 | 19-AUG-06:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.172997E+09 | 23529.87 | 23-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.108243E+10 | 64407.98 | 30-OCT-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.245511E+10 | 66748.93 | 24-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.192735E+11 | 120590.77 | 20-DEC-08:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.807527E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 5.14 | 0.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.366628E+11 | 125772.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_BOTTOM VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.123472E+09 | 32873.20 | 02-JAN-06:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.123472E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.123472E+09 | 32873.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.697281E+10 | 16087.30 | 09-JAN-07:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.267418E+10 | 16438.30 | 07-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.888649E+09 | 16554.44 | 23-MAR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 23303615.16 | 16491.67 | 05-APR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 13858244.73 | 15201.63 | 30-OCT-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.454661E+09 | 16494.56 | 10-NOV-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.341374E+10 | 15685.27 | 07-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.144412E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.697281E+10 | 16554.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.525823E+10 | 18863.11 | 02-JAN-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.228571E+10 | 19326.75 | 07-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.115191E+10 | 19375.81 | 23-MAR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.104092E+09 | 19348.05 | 05-APR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.104030E+09 | 18815.52 | 30-OCT-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.931146E+09 | 19385.07 | 08-NOV-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.371001E+10 | 19373.66 | 07-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.135451E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.525823E+10 | 19385.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.564755E+10 | 26560.31 | 02-JAN-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.246548E+10 | 27278.68 | 22-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.128306E+10 | 27276.55 | 23-MAR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.164780E+09 | 27373.14 | 10-APR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 290847.05 | 302.48 | 01-MAY-05:25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.148552E+09 | 26674.85 | 30-OCT-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.101852E+10 | 27348.30 | 04-NOV-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.379021E+10 | 27274.06 | 07-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.145185E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.564755E+10 | 27373.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.388137E+10 | 18379.58 | 02-JAN-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.115071E+10 | 18338.04 | 13-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.158432E+09 | 18309.00 | 06-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 6753168.89 | 6789.81 | 30-OCT-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.110907E+09 | 18304.47 | 24-NOV-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.832281E+09 | 18335.34 | 26-DEC-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.614046E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.388137E+10 | 18379.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV_MID WITH REHEAT HEATING COIL
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.413683E+12 | 1327167.90 | 09-JAN-07:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.156757E+12 | 1287080.76 | 14-FEB-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.458159E+11 | 1081923.78 | 15-MAR-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.214374E+11 | 784353.74 | 05-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.380798E+10 | 381140.12 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.182535E+09 | 94189.57 | 03-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 5324533.71 | 6790.69 | 08-JUL-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 94076103.51 | 111572.33 | 19-AUG-06:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.361389E+10 | 251332.61 | 06-SEP-07:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.235122E+11 | 658850.03 | 30-OCT-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.361401E+11 | 674366.00 | 24-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.245759E+12 | 1246723.18 | 20-DEC-09:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.950808E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 5324533.71 | 6790.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.413683E+12 | 1327167.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_MID VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.482237E+11 | 641626.54 | 17-JAN-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.112181E+11 | 641891.15 | 21-FEB-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.273742E+10 | 641236.37 | 06-MAR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.685418E+10 | 641707.98 | 27-NOV-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.264548E+11 | 641313.66 | 04-DEC-05:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.954883E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.482237E+11 | 641891.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.173808E+12 | 163410.98 | 06-JAN-09:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.105478E+12 | 150897.98 | 14-FEB-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.623216E+11 | 144621.45 | 06-MAR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.128244E+11 | 145098.62 | 21-APR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.252503E+09 | 143440.48 | 01-MAY-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.204468E+09 | 37433.28 | 23-SEP-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.101536E+11 | 155762.04 | 05-OCT-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.531176E+11 | 145591.54 | 28-NOV-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.154813E+12 | 145554.88 | 28-DEC-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.572973E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.173808E+12 | 163410.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.118243E+12 | 229665.24 | 03-JAN-05:22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.680151E+11 | 229730.47 | 28-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.419302E+11 | 229421.55 | 13-MAR-03:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.101275E+11 | 228897.08 | 28-APR-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.195908E+09 | 118263.31 | 01-MAY-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 14090061.63 | 17403.53 | 19-AUG-05:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.117969E+10 | 67547.53 | 23-SEP-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.136018E+11 | 229078.92 | 31-OCT-04:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.446853E+11 | 229529.60 | 20-NOV-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.109830E+12 | 229816.39 | 27-DEC-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.407823E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.118243E+12 | 229816.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.116112E+12 | 282535.05 | 30-JAN-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.613597E+11 | 281199.77 | 02-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.407237E+11 | 281177.37 | 06-MAR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.110444E+11 | 280942.05 | 10-APR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.453358E+09 | 129317.58 | 01-MAY-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 3929920.20 | 5260.66 | 19-AUG-06:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.641244E+09 | 41866.43 | 20-SEP-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.990195E+10 | 279672.75 | 30-OCT-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.413875E+11 | 281978.90 | 27-NOV-05:52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.112981E+12 | 282707.76 | 28-DEC-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.394609E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.116112E+12 | 282707.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.108788E+12 | 234890.14 | 03-JAN-05:22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.612327E+11 | 234856.03 | 27-FEB-05:22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.380622E+11 | 234329.66 | 08-MAR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.966681E+10 | 233977.04 | 10-APR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.367032E+09 | 53480.89 | 01-MAY-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 26536600.87 | 15061.08 | 19-AUG-05:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.872978E+09 | 46916.10 | 20-SEP-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.108466E+11 | 234140.49 | 10-OCT-04:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.381770E+11 | 234374.30 | 28-NOV-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.960257E+11 | 234860.97 | 04-DEC-05:22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.364065E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.108788E+12 | 234890.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV_TOP WITH REHEAT HEATING COIL
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.480154E+11 | 134819.34 | 09-JAN-08:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.200776E+11 | 131449.75 | 14-FEB-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.605299E+10 | 110568.11 | 15-MAR-06:55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.853121E+09 | 80399.22 | 05-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.197038E+09 | 35698.37 | 02-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 23131953.18 | 12074.36 | 03-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 2449964.03 | 1906.68 | 18-JUL-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 6460154.41 | 4758.50 | 18-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.201035E+09 | 25858.04 | 23-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.649943E+09 | 67072.71 | 30-OCT-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.377226E+10 | 68815.28 | 24-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.324280E+11 | 125934.85 | 20-DEC-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.112279E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 2449964.03 | 1906.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.480154E+11 | 134819.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_TOP VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.201304E+11 | 85392.63 | 20-JAN-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.114529E+11 | 85409.62 | 07-FEB-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.647273E+10 | 85451.31 | 27-MAR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.155407E+10 | 85398.21 | 10-APR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 63760030.78 | 83837.75 | 01-MAY-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.165677E+10 | 85377.39 | 30-OCT-04:24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.752874E+10 | 85412.28 | 20-NOV-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.168475E+11 | 85376.98 | 07-DEC-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.657069E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.201304E+11 | 85451.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.243268E+11 | 20403.07 | 06-JAN-09:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.166208E+11 | 18618.22 | 14-FEB-08:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.113031E+11 | 17787.95 | 21-MAR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.362778E+10 | 17733.74 | 17-APR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.252923E+09 | 17686.15 | 01-MAY-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 161174.50 | 187.47 | 10-JUN-05:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 13386036.09 | 5588.12 | 19-AUG-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.374266E+09 | 17592.62 | 29-SEP-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.338761E+10 | 17735.76 | 10-OCT-04:33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.104462E+11 | 17772.98 | 21-NOV-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.228420E+11 | 18084.38 | 20-DEC-09:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.931950E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.243268E+11 | 20403.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.159917E+11 | 23901.97 | 31-JAN-05:14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.102722E+11 | 23891.52 | 11-FEB-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.671699E+10 | 23839.88 | 03-MAR-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.212413E+10 | 23774.57 | 03-APR-04:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.161172E+09 | 23623.97 | 01-MAY-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 16572507.23 | 1683.70 | 10-JUN-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 19496925.52 | 6205.01 | 19-AUG-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.423505E+09 | 18958.13 | 13-SEP-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.283962E+10 | 23956.10 | 16-OCT-04:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.736797E+10 | 23902.31 | 04-NOV-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.154571E+11 | 23896.47 | 30-DEC-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.613905E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.159917E+11 | 23956.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.175272E+11 | 29569.24 | 19-JAN-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.107339E+11 | 29563.90 | 07-FEB-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.762320E+10 | 29570.75 | 04-MAR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.292758E+10 | 29566.53 | 27-APR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.330322E+09 | 29122.23 | 01-MAY-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 9543447.73 | 1993.03 | 03-JUN-05:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 31527700.89 | 6102.09 | 19-AUG-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.397915E+09 | 22175.04 | 13-SEP-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.290234E+10 | 29562.09 | 30-OCT-03:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.810651E+10 | 29544.78 | 20-NOV-05:24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.177692E+11 | 29579.02 | 28-DEC-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.683592E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.177692E+11 | 29579.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.151809E+11 | 26363.41 | 20-JAN-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.924331E+10 | 26269.42 | 04-FEB-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.614872E+10 | 26270.96 | 03-MAR-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.212128E+10 | 26133.84 | 03-APR-04:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.217875E+09 | 26009.58 | 01-MAY-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 8763030.99 | 2046.08 | 10-JUN-05:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 30376407.67 | 2611.73 | 19-AUG-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.403568E+09 | 11169.40 | 20-SEP-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.239187E+10 | 26243.35 | 16-OCT-04:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.629960E+10 | 26266.87 | 25-NOV-05:52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.136648E+11 | 26362.70 | 07-DEC-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.557111E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.151809E+11 | 26363.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CAV_BAS HEATING COIL
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.932215E+09 | 30530.37 | 06-JAN-07:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.932215E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.932215E+09 | 30530.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BASEMENT HEATING COIL
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BOT HEATING COIL
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER MID HEATING COIL
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER TOP HEATING COIL
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BOT_SUPPHEATCOIL
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER MID_SUPPHEATCOIL
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER TOP_SUPPHEATCOIL
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV_BOT WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 18529901.46 | 18529901.46 | 5966.72 | 27-JAN-15:20 | 5966.72 | 0.00 |
February | 0.00 | 0.00 | 70658977.20 | 70658977.20 | 28730.33 | 10-FEB-10:25 | 28730.33 | 0.00 |
March | 0.00 | 0.00 | 91912802.74 | 91912802.74 | 15261.81 | 23-MAR-10:05 | 15261.81 | 0.00 |
April | 0.00 | 0.00 | 0.517077E+10 | 0.517077E+10 | 100546.26 | 23-APR-16:11 | 100546.26 | 0.01 |
May | 0.00 | 0.00 | 0.398890E+11 | 0.389586E+11 | 143308.86 | 26-MAY-11:00 | 93571.14 | 0.21 |
June | 0.00 | 0.00 | 0.932611E+11 | 0.745529E+11 | 229762.53 | 19-JUN-15:30 | 104048.14 | 0.44 |
July | 0.00 | 0.00 | 0.128694E+12 | 0.966485E+11 | 293042.67 | 05-JUL-10:25 | 105378.27 | 0.65 |
August | 0.00 | 0.00 | 0.100130E+12 | 0.753437E+11 | 250088.88 | 31-AUG-12:50 | 112473.55 | 0.62 |
September | 0.00 | 0.00 | 0.203591E+11 | 0.181659E+11 | 156749.99 | 01-SEP-13:10 | 113377.78 | 0.16 |
October | 0.00 | 0.00 | 0.358375E+10 | 0.358375E+10 | 82763.18 | 19-OCT-15:00 | 82763.18 | 0.02 |
November | 0.00 | 0.00 | 0.443864E+09 | 0.443864E+09 | 24638.94 | 01-NOV-15:00 | 24638.94 | 0.01 |
December | 0.00 | 0.00 | 21125539.57 | 21125539.57 | 7386.82 | 14-DEC-12:30 | 7386.82 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.391734E+12 | 0.313070E+12 | 0.18 | |||
Minimum of Months | 0.00 | 0.00 | 18529901.46 | 18529901.46 | 5966.72 | 5966.72 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.128694E+12 | 0.966485E+11 | 293042.67 | 113377.78 | 0.65 |
Report: CoilReportMonthly
For: VAV_MID WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 943638.22 | 943638.22 | 476.75 | 27-JAN-15:00 | 476.75 | 0.00 |
February | 0.00 | 0.00 | 51940257.94 | 51940257.94 | 10222.14 | 11-FEB-13:20 | 10222.14 | 0.00 |
March | 0.00 | 0.00 | 0.178942E+09 | 0.178942E+09 | 63436.99 | 29-MAR-11:30 | 63436.99 | 0.00 |
April | 0.00 | 0.00 | 0.383648E+11 | 0.383648E+11 | 953717.49 | 23-APR-15:52 | 953717.49 | 0.01 |
May | 0.00 | 0.00 | 0.356931E+12 | 0.348152E+12 | 1340507.47 | 26-MAY-11:00 | 875999.98 | 0.21 |
June | 0.00 | 0.00 | 0.796711E+12 | 0.642269E+12 | 2115328.93 | 29-JUN-04:12 | 1014400.80 | 0.42 |
July | 0.00 | 0.00 | 0.103109E+13 | 0.796710E+12 | 2593460.28 | 05-JUL-10:30 | 932829.94 | 0.55 |
August | 0.00 | 0.00 | 0.768851E+12 | 0.592028E+12 | 1987205.69 | 31-AUG-12:50 | 899248.18 | 0.54 |
September | 0.00 | 0.00 | 0.177513E+12 | 0.160919E+12 | 1423241.84 | 01-SEP-13:10 | 1032503.99 | 0.16 |
October | 0.00 | 0.00 | 0.320185E+11 | 0.320185E+11 | 681318.18 | 19-OCT-15:00 | 681318.18 | 0.02 |
November | 0.00 | 0.00 | 0.256935E+10 | 0.256935E+10 | 155239.05 | 01-NOV-15:00 | 155239.05 | 0.01 |
December | 0.00 | 0.00 | 512583.72 | 512583.72 | 42.90 | 30-DEC-10:50 | 42.90 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.320428E+13 | 0.261326E+13 | 0.16 | |||
Minimum of Months | 0.00 | 0.00 | 512583.72 | 512583.72 | 42.90 | 42.90 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.103109E+13 | 0.796710E+12 | 2593460.28 | 1032503.99 | 0.55 |
Report: CoilReportMonthly
For: VAV_TOP WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 744322.17 | 744322.17 | 1011.25 | 13-JAN-06:04 | 1011.25 | 0.00 |
February | 0.00 | 0.00 | 11637184.48 | 11637184.48 | 2136.35 | 08-FEB-10:50 | 2136.35 | 0.00 |
March | 0.00 | 0.00 | 46726950.28 | 46726950.28 | 2368.34 | 31-MAR-12:10 | 2368.34 | 0.00 |
April | 0.00 | 0.00 | 0.364001E+10 | 0.364001E+10 | 104389.50 | 23-APR-16:01 | 104389.50 | 0.01 |
May | 0.00 | 0.00 | 0.377033E+11 | 0.367897E+11 | 150865.10 | 25-MAY-16:00 | 132743.19 | 0.20 |
June | 0.00 | 0.00 | 0.834621E+11 | 0.675133E+11 | 303679.83 | 30-JUN-03:02 | 121011.61 | 0.41 |
July | 0.00 | 0.00 | 0.108927E+12 | 0.841428E+11 | 262665.60 | 05-JUL-10:35 | 93462.37 | 0.55 |
August | 0.00 | 0.00 | 0.789273E+11 | 0.607464E+11 | 224497.74 | 29-AUG-15:40 | 129712.17 | 0.53 |
September | 0.00 | 0.00 | 0.168080E+11 | 0.152758E+11 | 165830.77 | 01-SEP-14:00 | 125735.25 | 0.15 |
October | 0.00 | 0.00 | 0.288334E+10 | 0.288334E+10 | 67397.32 | 19-OCT-15:00 | 67397.32 | 0.02 |
November | 0.00 | 0.00 | 0.245820E+09 | 0.245820E+09 | 13002.50 | 01-NOV-15:00 | 13002.50 | 0.01 |
December | 0.00 | 0.00 | 589398.11 | 589398.11 | 985.81 | 09-DEC-19:22 | 985.81 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.332657E+12 | 0.271297E+12 | 0.16 | |||
Minimum of Months | 0.00 | 0.00 | 589398.11 | 589398.11 | 985.81 | 985.81 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.108927E+12 | 0.841428E+11 | 303679.83 | 132743.19 | 0.55 |
Report: CoilReportMonthly
For: CAV_BAS COOLING COIL
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 33776607.20 | 33776607.20 | 8398.14 | 31-JAN-19:00 | 8398.14 | 0.00 |
February | 0.00 | 0.00 | 40624363.97 | 40624363.97 | 10701.12 | 01-FEB-18:00 | 10701.12 | 0.00 |
March | 0.00 | 0.00 | 23579530.63 | 23579530.63 | 8087.90 | 15-MAR-06:40 | 8087.90 | 0.00 |
April | 0.00 | 0.00 | 0.814743E+09 | 0.814743E+09 | 27919.32 | 13-APR-16:00 | 27919.32 | 0.00 |
May | 0.00 | 0.00 | 0.200178E+11 | 0.198513E+11 | 100992.08 | 26-MAY-04:12 | 64599.77 | 0.17 |
June | 0.00 | 0.00 | 0.452142E+11 | 0.383284E+11 | 200599.81 | 30-JUN-03:02 | 79820.68 | 0.33 |
July | 0.00 | 0.00 | 0.595295E+11 | 0.488739E+11 | 180883.02 | 23-JUL-15:57 | 98326.71 | 0.45 |
August | 0.00 | 0.00 | 0.477552E+11 | 0.384284E+11 | 143928.01 | 27-AUG-16:31 | 79712.80 | 0.42 |
September | 0.00 | 0.00 | 0.855878E+10 | 0.803949E+10 | 106719.85 | 03-SEP-16:51 | 79871.50 | 0.10 |
October | 0.00 | 0.00 | 0.116867E+10 | 0.116867E+10 | 46173.01 | 19-OCT-15:00 | 46173.01 | 0.01 |
November | 0.00 | 0.00 | 0.154435E+09 | 0.152724E+09 | 20545.46 | 21-NOV-06:02 | 11337.95 | 0.01 |
December | 0.00 | 0.00 | 60024891.36 | 60024891.36 | 28616.80 | 18-DEC-16:30 | 28616.80 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.183371E+12 | 0.155816E+12 | 0.13 | |||
Minimum of Months | 0.00 | 0.00 | 23579530.63 | 23579530.63 | 8087.90 | 8087.90 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.595295E+11 | 0.488739E+11 | 200599.81 | 98326.71 | 0.45 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BASEMENT COOLING COIL
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.582103E+10 | 0.582103E+10 | 2813.12 | 21-JAN-16:00 | 2813.12 | 0.00 |
February | 0.00 | 0.00 | 0.106108E+11 | 0.105412E+11 | 5155.73 | 22-FEB-17:33 | 5155.73 | 0.00 |
March | 0.00 | 0.00 | 0.144095E+11 | 0.143464E+11 | 5692.27 | 05-MAR-03:42 | 5369.49 | 0.00 |
April | 0.00 | 0.00 | 0.567057E+11 | 0.552791E+11 | 394062.08 | 23-APR-15:51 | 393286.24 | 0.00 |
May | 0.00 | 0.00 | 0.276953E+11 | 0.262400E+11 | 158281.29 | 25-MAY-13:10 | 127077.67 | 0.00 |
June | 0.00 | 0.00 | 0.176663E+12 | 0.130179E+12 | 469473.19 | 29-JUN-21:42 | 218795.04 | 0.00 |
July | 0.00 | 0.00 | 0.551045E+12 | 0.338956E+12 | 474516.92 | 15-JUL-14:00 | 245979.35 | 0.00 |
August | 0.00 | 0.00 | 0.695164E+12 | 0.418159E+12 | 453123.46 | 31-AUG-12:55 | 214373.73 | 0.00 |
September | 0.00 | 0.00 | 0.541516E+10 | 0.481566E+10 | 130603.86 | 01-SEP-15:00 | 112903.84 | 0.00 |
October | 0.00 | 0.00 | 0.106052E+11 | 0.103268E+11 | 97535.16 | 19-OCT-15:00 | 97535.16 | 0.00 |
November | 0.00 | 0.00 | 0.149034E+11 | 0.143641E+11 | 106830.25 | 01-NOV-15:00 | 82681.63 | 0.00 |
December | 0.00 | 0.00 | 0.150538E+11 | 0.150089E+11 | 6076.59 | 06-DEC-03:00 | 5608.36 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.158409E+13 | 0.104404E+13 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.541516E+10 | 0.481566E+10 | 2813.12 | 2813.12 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.695164E+12 | 0.418159E+12 | 474516.92 | 393286.24 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BOT COOLING COIL
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.185608E+10 | 0.185608E+10 | 2180.32 | 20-JAN-16:25 | 2180.32 | 0.00 |
February | 0.00 | 0.00 | 0.749899E+10 | 0.749899E+10 | 4737.72 | 27-FEB-17:00 | 4737.72 | 0.00 |
March | 0.00 | 0.00 | 0.143998E+11 | 0.143998E+11 | 7656.88 | 31-MAR-24:00 | 7656.88 | 0.00 |
April | 0.00 | 0.00 | 0.198874E+11 | 0.198874E+11 | 9110.17 | 21-APR-18:20 | 9110.17 | 0.00 |
May | 0.00 | 0.00 | 0.604336E+10 | 0.599972E+10 | 3896.58 | 31-MAY-24:00 | 3896.58 | 0.00 |
June | 0.00 | 0.00 | 0.111463E+11 | 0.109455E+11 | 6055.05 | 30-JUN-23:32 | 6004.54 | 0.00 |
July | 0.00 | 0.00 | 0.168157E+11 | 0.165368E+11 | 7878.58 | 31-JUL-23:52 | 7878.58 | 0.00 |
August | 0.00 | 0.00 | 0.217185E+11 | 0.214316E+11 | 9257.59 | 13-AUG-18:31 | 9257.59 | 0.00 |
September | 0.00 | 0.00 | 0.560885E+10 | 0.555339E+10 | 3912.47 | 30-SEP-24:00 | 3912.47 | 0.00 |
October | 0.00 | 0.00 | 0.101532E+11 | 0.101476E+11 | 5428.90 | 31-OCT-24:00 | 5428.90 | 0.00 |
November | 0.00 | 0.00 | 0.139825E+11 | 0.139774E+11 | 6428.03 | 12-NOV-16:08 | 6428.03 | 0.00 |
December | 0.00 | 0.00 | 0.182879E+11 | 0.182879E+11 | 7892.81 | 10-DEC-15:53 | 7892.81 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.147399E+12 | 0.146522E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.185608E+10 | 0.185608E+10 | 2180.32 | 2180.32 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.217185E+11 | 0.214316E+11 | 9257.59 | 9257.59 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER MID COOLING COIL
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.216834E+10 | 0.216834E+10 | 16710.89 | 20-JAN-16:25 | 16710.89 | 0.00 |
February | 0.00 | 0.00 | 0.466453E+11 | 0.466453E+11 | 42006.48 | 08-FEB-17:00 | 42006.48 | 0.00 |
March | 0.00 | 0.00 | 0.116194E+12 | 0.116194E+12 | 68996.85 | 31-MAR-23:20 | 68996.85 | 0.00 |
April | 0.00 | 0.00 | 0.176061E+12 | 0.176061E+12 | 87214.04 | 21-APR-18:20 | 87214.04 | 0.00 |
May | 0.00 | 0.00 | 0.526109E+11 | 0.521792E+11 | 35194.01 | 14-MAY-18:43 | 35194.01 | 0.00 |
June | 0.00 | 0.00 | 0.103041E+12 | 0.101050E+12 | 59020.81 | 30-JUN-23:32 | 58518.98 | 0.00 |
July | 0.00 | 0.00 | 0.159015E+12 | 0.156244E+12 | 75006.16 | 31-JUL-23:52 | 75006.16 | 0.00 |
August | 0.00 | 0.00 | 0.204278E+12 | 0.201422E+12 | 87942.29 | 02-AUG-18:40 | 87096.82 | 0.00 |
September | 0.00 | 0.00 | 0.459257E+11 | 0.453842E+11 | 35718.02 | 03-SEP-17:53 | 35612.53 | 0.00 |
October | 0.00 | 0.00 | 0.806228E+11 | 0.805676E+11 | 47219.35 | 19-OCT-16:50 | 46639.62 | 0.00 |
November | 0.00 | 0.00 | 0.108229E+12 | 0.108177E+12 | 58333.22 | 17-NOV-16:10 | 58333.22 | 0.00 |
December | 0.00 | 0.00 | 0.141743E+12 | 0.141743E+12 | 67216.07 | 08-DEC-15:55 | 67216.07 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.123653E+13 | 0.122784E+13 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.216834E+10 | 0.216834E+10 | 16710.89 | 16710.89 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.204278E+12 | 0.201422E+12 | 87942.29 | 87214.04 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER TOP COOLING COIL
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 99812034.80 | 99812034.80 | 1496.72 | 20-JAN-16:25 | 1496.72 | 0.00 |
February | 0.00 | 0.00 | 0.319744E+10 | 0.319744E+10 | 4177.83 | 08-FEB-17:00 | 4177.83 | 0.00 |
March | 0.00 | 0.00 | 0.100171E+11 | 0.100171E+11 | 6485.16 | 31-MAR-23:10 | 6485.16 | 0.00 |
April | 0.00 | 0.00 | 0.163700E+11 | 0.163700E+11 | 8718.71 | 21-APR-18:20 | 8718.71 | 0.00 |
May | 0.00 | 0.00 | 0.480231E+10 | 0.475913E+10 | 3586.07 | 25-MAY-18:50 | 3439.48 | 0.00 |
June | 0.00 | 0.00 | 0.100781E+11 | 0.987932E+10 | 5890.38 | 30-JUN-23:32 | 5840.08 | 0.00 |
July | 0.00 | 0.00 | 0.157857E+11 | 0.155089E+11 | 7416.35 | 31-JUL-23:52 | 7416.35 | 0.00 |
August | 0.00 | 0.00 | 0.202409E+11 | 0.199558E+11 | 8861.69 | 05-AUG-18:35 | 8861.69 | 0.00 |
September | 0.00 | 0.00 | 0.394908E+10 | 0.389575E+10 | 3547.01 | 03-SEP-17:42 | 3536.90 | 0.00 |
October | 0.00 | 0.00 | 0.655203E+10 | 0.654658E+10 | 4764.84 | 19-OCT-16:50 | 4706.60 | 0.00 |
November | 0.00 | 0.00 | 0.904495E+10 | 0.903987E+10 | 5737.81 | 17-NOV-16:10 | 5737.81 | 0.00 |
December | 0.00 | 0.00 | 0.125558E+11 | 0.125558E+11 | 6449.79 | 20-DEC-15:55 | 6449.79 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.112693E+12 | 0.111826E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 99812034.80 | 99812034.80 | 1496.72 | 1496.72 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.202409E+11 | 0.199558E+11 | 8861.69 | 8861.69 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:01 | 436534.11 | 2964503.23 | 09-JAN-07:02 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 231356.90 | 2629765.84 | 14-FEB-07:03 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 105348.04 | 2024309.83 | 06-MAR-05:01 |
April | 0.00 | 0.00 | 01-APR-00:10 | 30660.81 | 1740089.43 | 10-APR-04:01 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 2425.42 | 955228.26 | 01-MAY-05:02 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 79.86 | 94765.59 | 03-JUN-06:10 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 2.40 | 6831.32 | 08-JUL-06:10 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 92.70 | 121133.34 | 19-AUG-06:15 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 3217.67 | 388548.85 | 23-SEP-06:10 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 30790.62 | 1916873.07 | 16-OCT-04:11 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 102781.11 | 2185366.93 | 27-NOV-05:11 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 331501.41 | 2628294.04 | 26-DEC-07:03 |
Annual Sum or Average | 0.00 | 105993.73 | ||||
Minimum of Months | 0.00 | 0.00 | 2.40 | 6831.32 | ||
Maximum of Months | 0.00 | 0.00 | 436534.11 | 2964503.23 |
Report: PlantLoopDemandReportMonthly
For: COOLSYS1_SUPPLY
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 1098.19 | 6712.60 | 31-JAN-19:00 | 0.00 | 0.00 | 01-JAN-00:01 |
February | 1334.70 | 11458.35 | 11-FEB-13:30 | 0.00 | 0.00 | 01-FEB-00:03 |
March | 1255.60 | 37392.22 | 29-MAR-11:30 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 19377.22 | 757126.36 | 23-APR-15:13 | 0.00 | 0.00 | 01-APR-00:10 |
May | 177533.63 | 1697466.61 | 25-MAY-16:00 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 405668.67 | 2431315.66 | 19-JUN-15:20 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 527330.21 | 5920463.32 | 05-JUL-11:00 | 0.00 | 0.00 | 01-JUL-00:03 |
August | 384414.30 | 2504448.75 | 31-AUG-12:50 | 0.00 | 0.00 | 01-AUG-00:03 |
September | 88453.04 | 1807698.35 | 01-SEP-13:10 | 0.00 | 0.00 | 01-SEP-00:03 |
October | 15582.98 | 878274.66 | 19-OCT-15:00 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 2138.89 | 209358.89 | 01-NOV-15:00 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 1251.87 | 19031.41 | 18-DEC-16:30 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 136627.33 | 0.00 | ||||
Minimum of Months | 1098.19 | 6712.60 | 0.00 | 0.00 | ||
Maximum of Months | 527330.21 | 5920463.32 | 0.00 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: COOLSYS1_DEMAND
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 1.62 | 1032.15 | 31-JAN-19:00 | 0.00 | 0.00 | 01-JAN-00:01 |
February | 29.63 | 8451.36 | 10-FEB-10:25 | 0.00 | 0.00 | 01-FEB-00:03 |
March | 115.37 | 39197.42 | 29-MAR-11:30 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 18477.79 | 1269778.65 | 23-APR-14:31 | 0.00 | 0.00 | 01-APR-00:10 |
May | 174495.71 | 1832933.85 | 26-MAY-05:03 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 400431.98 | 4415765.01 | 29-JUN-04:12 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 522659.51 | 5925362.86 | 05-JUL-11:00 | 0.00 | 0.00 | 01-JUL-00:03 |
August | 379298.85 | 3115501.28 | 09-AUG-05:03 | 0.00 | 0.00 | 01-AUG-00:03 |
September | 86959.54 | 1800884.51 | 01-SEP-13:10 | 0.00 | 0.00 | 01-SEP-00:03 |
October | 14780.84 | 874525.67 | 19-OCT-15:00 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 1331.56 | 204799.10 | 01-NOV-15:00 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 17.95 | 16369.63 | 18-DEC-16:30 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 134381.70 | 0.00 | ||||
Minimum of Months | 1.62 | 1032.15 | 0.00 | 0.00 | ||
Maximum of Months | 522659.51 | 5925362.86 | 0.00 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SINGLE WATER PLANT LOOP
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 8872.37 | 43744.20 | 20-JAN-15:10 | 0.00 | 0.00 | 01-JAN-00:01 |
February | 39966.46 | 189387.86 | 08-FEB-11:05 | 0.00 | 0.00 | 01-FEB-00:03 |
March | 76957.42 | 243459.25 | 22-MAR-14:47 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 148223.58 | 1420080.64 | 23-APR-16:00 | 0.00 | 0.00 | 01-APR-00:10 |
May | 108327.18 | 919709.74 | 25-MAY-18:00 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 327841.19 | 1495861.23 | 29-JUN-16:00 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 666961.07 | 1762986.71 | 15-JUL-14:10 | 0.00 | 0.00 | 01-JUL-00:03 |
August | 708662.80 | 1753189.70 | 08-AUG-15:10 | 0.00 | 0.00 | 01-AUG-00:03 |
September | 49855.45 | 725652.29 | 01-SEP-15:10 | 0.00 | 0.00 | 01-SEP-00:03 |
October | 57199.26 | 486434.31 | 19-OCT-15:00 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 75374.87 | 328726.74 | 01-NOV-15:00 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 92367.76 | 191016.77 | 20-DEC-11:50 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 198514.24 | 0.00 | ||||
Minimum of Months | 8872.37 | 43744.20 | 0.00 | 0.00 | ||
Maximum of Months | 708662.80 | 1762986.71 | 0.00 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:01 | 18359.19 | 62795.00 | 31-JAN-12:45 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 18850.20 | 63325.26 | 28-FEB-12:15 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 19868.19 | 63330.10 | 02-MAR-12:35 |
April | 0.00 | 0.00 | 01-APR-00:10 | 18187.89 | 62114.39 | 04-APR-11:40 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 17881.68 | 59634.56 | 01-MAY-11:50 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 17273.80 | 56292.94 | 01-JUN-11:40 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 15239.56 | 52952.96 | 03-JUL-11:30 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 16116.39 | 50926.39 | 01-AUG-12:00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 15273.24 | 51339.04 | 29-SEP-11:40 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 15790.02 | 53980.11 | 31-OCT-11:40 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 16844.85 | 57251.03 | 30-NOV-12:40 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 17181.31 | 60309.58 | 29-DEC-12:20 |
Annual Sum or Average | 0.00 | 17229.38 | ||||
Minimum of Months | 0.00 | 0.00 | 15239.56 | 50926.39 | ||
Maximum of Months | 0.00 | 0.00 | 19868.19 | 63330.10 |
Report: PlantLoopDemandReportMonthly
For: TOWERWATERSYS
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 76.71 | 10276.71 | 23-JAN-11:20 | 9101.89 | 160653.31 | 23-JAN-01:41 |
February | 91.91 | 16614.56 | 08-FEB-11:00 | 10111.02 | 158092.75 | 27-FEB-01:22 |
March | 73.48 | 14607.38 | 28-MAR-12:40 | 8841.80 | 157867.10 | 20-MAR-11:40 |
April | 21213.49 | 792834.03 | 13-APR-15:20 | 3635.59 | 157054.37 | 27-APR-12:20 |
May | 234590.02 | 3514222.44 | 25-MAY-16:00 | 1084.62 | 131543.95 | 05-MAY-05:50 |
June | 739174.28 | 6665014.56 | 30-JUN-16:00 | 338.90 | 91228.17 | 02-JUN-16:50 |
July | 962620.86 | 7328702.72 | 05-JUL-11:00 | 195.31 | 57109.39 | 17-JUL-07:20 |
August | 656848.85 | 6008573.40 | 31-AUG-12:50 | 649.68 | 71112.28 | 02-AUG-08:50 |
September | 111933.10 | 3025213.52 | 01-SEP-13:10 | 782.54 | 130788.57 | 14-SEP-06:00 |
October | 17450.29 | 1010305.85 | 19-OCT-15:00 | 3041.11 | 153827.72 | 13-OCT-15:50 |
November | 1705.31 | 272122.10 | 01-NOV-15:00 | 5735.06 | 161725.65 | 23-NOV-20:32 |
December | 93.99 | 9561.33 | 12-DEC-21:20 | 9670.34 | 148496.45 | 18-DEC-13:00 |
Annual Sum or Average | 230815.72 | 4405.48 | ||||
Minimum of Months | 73.48 | 9561.33 | 195.31 | 57109.39 | ||
Maximum of Months | 962620.86 | 7328702.72 | 10111.02 | 161725.65 |
Report: FanReportMonthly
For: CAV_BAS FAN
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.147474E+11 | 0.76 | 10592.85 | 02-JAN-06:01 | 1.44 |
February | 0.139169E+11 | 0.79 | 10592.85 | 01-FEB-06:01 | 1.46 |
March | 0.167521E+11 | 0.86 | 10592.85 | 01-MAR-05:01 | 1.46 |
April | 0.154454E+11 | 0.82 | 10592.85 | 01-APR-04:01 | 1.45 |
May | 0.165600E+11 | 0.84 | 10592.85 | 01-MAY-03:02 | 1.46 |
June | 0.161965E+11 | 0.85 | 10592.85 | 01-JUN-04:12 | 1.44 |
July | 0.163982E+11 | 0.83 | 10592.85 | 01-JUL-04:12 | 1.44 |
August | 0.178045E+11 | 0.90 | 10592.85 | 01-AUG-04:12 | 1.44 |
September | 0.164227E+11 | 0.86 | 10592.85 | 01-SEP-04:12 | 1.44 |
October | 0.162313E+11 | 0.83 | 10592.85 | 01-OCT-23:10 | 1.44 |
November | 0.153326E+11 | 0.81 | 10592.85 | 01-NOV-04:11 | 1.44 |
December | 0.151002E+11 | 0.78 | 10592.85 | 01-DEC-05:01 | 1.46 |
Annual Sum or Average | 0.190908E+12 | 0.83 | |||
Minimum of Months | 0.139169E+11 | 0.76 | 10592.85 | 1.44 | |
Maximum of Months | 0.178045E+11 | 0.90 | 10592.85 | 1.46 |
Report: FanReportMonthly
For: VAV_BOT WITH REHEAT FAN
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.408998E+10 | 0.35 | 24249.15 | 20-JAN-16:00 | 1.94 |
February | 0.462882E+10 | 0.36 | 24335.86 | 22-FEB-17:15 | 1.95 |
March | 0.694070E+10 | 0.43 | 24335.86 | 02-MAR-15:00 | 1.95 |
April | 0.890931E+10 | 0.48 | 24335.86 | 29-APR-10:40 | 1.95 |
May | 0.102794E+11 | 0.52 | 19832.01 | 26-MAY-04:12 | 1.69 |
June | 0.131499E+11 | 0.62 | 24335.86 | 26-JUN-04:12 | 1.93 |
July | 0.153649E+11 | 0.68 | 24335.86 | 05-JUL-10:25 | 1.92 |
August | 0.147521E+11 | 0.68 | 24335.86 | 08-AUG-15:00 | 1.92 |
September | 0.811369E+10 | 0.46 | 20311.35 | 01-SEP-15:40 | 1.71 |
October | 0.635692E+10 | 0.39 | 16325.69 | 17-OCT-17:30 | 1.51 |
November | 0.534403E+10 | 0.36 | 21907.33 | 09-NOV-09:07 | 1.82 |
December | 0.452863E+10 | 0.34 | 20954.03 | 20-DEC-15:30 | 1.77 |
Annual Sum or Average | 0.102458E+12 | 0.47 | |||
Minimum of Months | 0.408998E+10 | 0.34 | 16325.69 | 1.51 | |
Maximum of Months | 0.153649E+11 | 0.68 | 24335.86 | 1.95 |
Report: FanReportMonthly
For: VAV_MID WITH REHEAT FAN
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.497949E+11 | 0.46 | 67273.08 | 02-JAN-04:01 | 0.93 |
February | 0.413208E+11 | 0.42 | 161424.09 | 10-FEB-16:15 | 1.57 |
March | 0.450207E+11 | 0.39 | 227267.14 | 10-MAR-15:27 | 1.94 |
April | 0.520985E+11 | 0.38 | 227267.14 | 04-APR-15:55 | 1.95 |
May | 0.824135E+11 | 0.47 | 190677.88 | 18-MAY-14:40 | 1.72 |
June | 0.103001E+12 | 0.54 | 227267.14 | 29-JUN-04:12 | 1.92 |
July | 0.115665E+12 | 0.56 | 227267.14 | 05-JUL-10:30 | 1.92 |
August | 0.970260E+11 | 0.52 | 206847.03 | 08-AUG-15:20 | 1.81 |
September | 0.615698E+11 | 0.41 | 193084.34 | 01-SEP-16:00 | 1.73 |
October | 0.429194E+11 | 0.34 | 227267.14 | 18-OCT-08:57 | 1.94 |
November | 0.371537E+11 | 0.35 | 101258.37 | 07-NOV-16:45 | 1.18 |
December | 0.462448E+11 | 0.43 | 67273.08 | 04-DEC-05:01 | 0.93 |
Annual Sum or Average | 0.774228E+12 | 0.44 | |||
Minimum of Months | 0.371537E+11 | 0.34 | 67273.08 | 0.93 | |
Maximum of Months | 0.115665E+12 | 0.56 | 227267.14 | 1.95 |
Report: FanReportMonthly
For: VAV_TOP WITH REHEAT FAN
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.565314E+10 | 0.49 | 6280.71 | 18-JAN-05:01 | 0.85 |
February | 0.483130E+10 | 0.47 | 6280.71 | 01-FEB-05:01 | 0.85 |
March | 0.476671E+10 | 0.42 | 6280.71 | 01-MAR-06:01 | 0.84 |
April | 0.460154E+10 | 0.37 | 21791.56 | 06-APR-14:57 | 1.79 |
May | 0.732535E+10 | 0.42 | 20683.84 | 18-MAY-14:30 | 1.71 |
June | 0.973738E+10 | 0.50 | 24939.87 | 30-JUN-14:50 | 1.92 |
July | 0.109133E+11 | 0.51 | 24979.83 | 05-JUL-10:40 | 1.91 |
August | 0.876917E+10 | 0.47 | 21814.52 | 08-AUG-15:20 | 1.76 |
September | 0.509588E+10 | 0.36 | 20647.01 | 01-SEP-16:00 | 1.70 |
October | 0.392007E+10 | 0.34 | 9186.62 | 20-OCT-15:00 | 1.05 |
November | 0.445128E+10 | 0.42 | 6280.71 | 04-NOV-05:01 | 0.84 |
December | 0.540392E+10 | 0.47 | 6280.71 | 28-DEC-05:01 | 0.84 |
Annual Sum or Average | 0.754691E+11 | 0.44 | |||
Minimum of Months | 0.392007E+10 | 0.34 | 6280.71 | 0.84 | |
Maximum of Months | 0.109133E+11 | 0.51 | 24979.83 | 1.92 |
Report: FanReportMonthly
For: AIRLOOP DATACENTER BASEMENT SUPPLY FAN
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.987438E+11 | 1.41 | 36866.73 | 01-JAN-00:01 | 1.41 |
February | 0.891880E+11 | 1.41 | 36866.73 | 01-FEB-00:03 | 1.41 |
March | 0.987438E+11 | 1.41 | 36866.73 | 01-MAR-00:10 | 1.41 |
April | 0.955586E+11 | 1.41 | 36866.73 | 01-APR-00:10 | 1.41 |
May | 0.987438E+11 | 1.40 | 36866.73 | 01-MAY-00:10 | 1.41 |
June | 0.955586E+11 | 1.40 | 36866.73 | 01-JUN-00:10 | 1.41 |
July | 0.987438E+11 | 1.39 | 36866.73 | 01-JUL-00:03 | 1.40 |
August | 0.987438E+11 | 1.40 | 36866.73 | 01-AUG-00:03 | 1.39 |
September | 0.955586E+11 | 1.40 | 36866.73 | 01-SEP-00:03 | 1.39 |
October | 0.987438E+11 | 1.41 | 36866.73 | 01-OCT-00:10 | 1.41 |
November | 0.955586E+11 | 1.41 | 36866.73 | 01-NOV-00:10 | 1.41 |
December | 0.987438E+11 | 1.41 | 36866.73 | 01-DEC-00:10 | 1.41 |
Annual Sum or Average | 0.116263E+13 | 1.41 | |||
Minimum of Months | 0.891880E+11 | 1.39 | 36866.73 | 1.39 | |
Maximum of Months | 0.987438E+11 | 1.41 | 36866.73 | 1.41 |
Report: FanReportMonthly
For: AIRLOOP DATACENTER BOT SUPPLY FAN
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.161809E+10 | 0.96 | 604.12 | 01-JAN-00:01 | 0.96 |
February | 0.146150E+10 | 0.96 | 604.12 | 01-FEB-00:03 | 0.96 |
March | 0.161809E+10 | 0.96 | 604.12 | 01-MAR-00:10 | 0.96 |
April | 0.156589E+10 | 0.96 | 604.12 | 01-APR-00:10 | 0.96 |
May | 0.161809E+10 | 0.95 | 604.12 | 01-MAY-00:10 | 0.96 |
June | 0.156589E+10 | 0.95 | 604.12 | 01-JUN-00:10 | 0.95 |
July | 0.161809E+10 | 0.95 | 604.12 | 01-JUL-00:03 | 0.95 |
August | 0.161809E+10 | 0.95 | 604.12 | 01-AUG-00:03 | 0.95 |
September | 0.156589E+10 | 0.95 | 604.12 | 01-SEP-00:03 | 0.95 |
October | 0.161809E+10 | 0.96 | 604.12 | 01-OCT-00:10 | 0.95 |
November | 0.156589E+10 | 0.96 | 604.12 | 01-NOV-00:10 | 0.96 |
December | 0.161809E+10 | 0.96 | 604.12 | 01-DEC-00:10 | 0.96 |
Annual Sum or Average | 0.190517E+11 | 0.96 | |||
Minimum of Months | 0.146150E+10 | 0.95 | 604.12 | 0.95 | |
Maximum of Months | 0.161809E+10 | 0.96 | 604.12 | 0.96 |
Report: FanReportMonthly
For: AIRLOOP DATACENTER MID SUPPLY FAN
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.155843E+11 | 0.96 | 5818.50 | 01-JAN-00:01 | 0.96 |
February | 0.140761E+11 | 0.96 | 5818.50 | 01-FEB-00:03 | 0.96 |
March | 0.155843E+11 | 0.96 | 5818.50 | 01-MAR-00:10 | 0.96 |
April | 0.150816E+11 | 0.96 | 5818.50 | 01-APR-00:10 | 0.96 |
May | 0.155843E+11 | 0.95 | 5818.50 | 01-MAY-00:10 | 0.96 |
June | 0.150816E+11 | 0.95 | 5818.50 | 01-JUN-00:10 | 0.95 |
July | 0.155843E+11 | 0.95 | 5818.50 | 01-JUL-00:03 | 0.95 |
August | 0.155843E+11 | 0.95 | 5818.50 | 01-AUG-00:03 | 0.95 |
September | 0.150816E+11 | 0.95 | 5818.50 | 01-SEP-00:05 | 0.95 |
October | 0.155843E+11 | 0.96 | 5818.50 | 01-OCT-00:10 | 0.95 |
November | 0.150816E+11 | 0.96 | 5818.50 | 01-NOV-00:20 | 0.96 |
December | 0.155843E+11 | 0.96 | 5818.50 | 01-DEC-00:10 | 0.96 |
Annual Sum or Average | 0.183492E+12 | 0.96 | |||
Minimum of Months | 0.140761E+11 | 0.95 | 5818.50 | 0.95 | |
Maximum of Months | 0.155843E+11 | 0.96 | 5818.50 | 0.96 |
Report: FanReportMonthly
For: AIRLOOP DATACENTER TOP SUPPLY FAN
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.157918E+10 | 0.96 | 589.60 | 01-JAN-00:01 | 0.96 |
February | 0.142636E+10 | 0.96 | 589.60 | 01-FEB-00:03 | 0.96 |
March | 0.157918E+10 | 0.96 | 589.60 | 01-MAR-00:10 | 0.96 |
April | 0.152824E+10 | 0.96 | 589.60 | 01-APR-00:10 | 0.96 |
May | 0.157918E+10 | 0.95 | 589.60 | 01-MAY-00:10 | 0.96 |
June | 0.152824E+10 | 0.95 | 589.60 | 01-JUN-00:10 | 0.95 |
July | 0.157918E+10 | 0.95 | 589.60 | 01-JUL-00:03 | 0.95 |
August | 0.157918E+10 | 0.95 | 589.60 | 01-AUG-00:03 | 0.95 |
September | 0.152824E+10 | 0.95 | 589.60 | 01-SEP-00:03 | 0.95 |
October | 0.157918E+10 | 0.96 | 589.60 | 01-OCT-00:10 | 0.95 |
November | 0.152824E+10 | 0.96 | 589.60 | 01-NOV-00:10 | 0.96 |
December | 0.157918E+10 | 0.96 | 589.60 | 01-DEC-00:10 | 0.96 |
Annual Sum or Average | 0.185936E+11 | 0.96 | |||
Minimum of Months | 0.142636E+10 | 0.95 | 589.60 | 0.95 | |
Maximum of Months | 0.157918E+10 | 0.96 | 589.60 | 0.96 |
Report: PumpReportMonthly
For: HEATSYS1 PUMP
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.514375E+10 | 0.462937E+10 | 8134.85 | 09-JAN-07:03 | 7321.37 | 7321.37 | 50.77 | 21.93 |
February | 0.251076E+10 | 0.225968E+10 | 7864.97 | 14-FEB-07:10 | 7078.47 | 7078.47 | 52.61 | 18.84 |
March | 0.132144E+10 | 0.118930E+10 | 7123.49 | 06-MAR-05:01 | 6411.14 | 6411.14 | 45.93 | 13.42 |
April | 0.360183E+09 | 0.324165E+09 | 5712.80 | 05-APR-05:01 | 5141.52 | 5141.52 | 39.19 | 8.58 |
May | 31333222.42 | 28199900.18 | 3459.57 | 01-MAY-05:02 | 3113.61 | 3113.61 | 28.38 | 4.26 |
June | 953674.75 | 858307.27 | 431.65 | 03-JUN-06:10 | 388.49 | 388.49 | 31.37 | 0.45 |
July | 28695.77 | 25826.20 | 30.52 | 08-JUL-06:10 | 27.47 | 27.47 | 29.46 | 0.03 |
August | 1086218.31 | 977596.48 | 523.10 | 19-AUG-06:15 | 470.79 | 470.79 | 28.86 | 0.55 |
September | 34381124.54 | 30943012.09 | 1461.43 | 23-SEP-06:10 | 1315.29 | 1315.29 | 23.84 | 1.60 |
October | 0.373663E+09 | 0.336297E+09 | 5743.92 | 30-OCT-05:01 | 5169.53 | 5169.53 | 41.80 | 8.65 |
November | 0.123024E+10 | 0.110721E+10 | 7114.55 | 28-NOV-06:01 | 6403.09 | 6403.09 | 46.09 | 13.38 |
December | 0.396659E+10 | 0.356993E+10 | 7919.16 | 26-DEC-07:03 | 7127.25 | 7127.25 | 49.70 | 19.46 |
Annual Sum or Average | 0.149744E+11 | 0.134770E+11 | ||||||
Minimum of Months | 28695.77 | 25826.20 | 30.52 | 27.47 | 27.47 | 23.84 | 0.03 | |
Maximum of Months | 0.514375E+10 | 0.462937E+10 | 8134.85 | 7321.37 | 7321.37 | 52.61 | 21.93 |
Report: PumpReportMonthly
For: COOLSYS1 PUMP SECONDARY
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 4010.33 | 3609.30 | 0.59 | 27-JAN-15:30 | 0.53 | 0.53 | 6.70 | 0.17 |
February | 16655.23 | 14989.71 | 2.53 | 10-FEB-10:25 | 2.28 | 2.28 | 6.70 | 0.68 |
March | 42582.38 | 38324.14 | 6.87 | 29-MAR-11:30 | 6.18 | 6.18 | 6.70 | 1.60 |
April | 14058631.34 | 12652768.21 | 1888.62 | 23-APR-15:52 | 1699.76 | 1699.76 | 6.71 | 44.23 |
May | 0.358621E+09 | 0.322759E+09 | 3587.62 | 16-MAY-13:00 | 3228.86 | 3228.86 | 8.16 | 58.53 |
June | 0.852579E+09 | 0.767321E+09 | 18997.47 | 29-JUN-04:12 | 17097.73 | 17097.73 | 9.05 | 115.66 |
July | 0.146857E+10 | 0.132171E+10 | 18997.47 | 05-JUL-05:03 | 17097.73 | 17097.73 | 9.24 | 115.66 |
August | 0.811850E+09 | 0.730665E+09 | 13215.07 | 09-AUG-05:03 | 11893.56 | 11893.56 | 8.61 | 100.19 |
September | 0.204192E+09 | 0.183773E+09 | 4902.12 | 07-SEP-12:10 | 4411.91 | 4411.91 | 7.20 | 66.81 |
October | 31788728.14 | 28609855.33 | 1894.59 | 19-OCT-14:30 | 1705.13 | 1705.13 | 6.71 | 44.29 |
November | 865577.94 | 779020.15 | 59.33 | 01-NOV-15:00 | 53.40 | 53.40 | 6.70 | 7.40 |
December | 6311.73 | 5680.56 | 2.26 | 18-DEC-16:30 | 2.04 | 2.04 | 6.70 | 0.61 |
Annual Sum or Average | 0.374259E+10 | 0.336833E+10 | ||||||
Minimum of Months | 4010.33 | 3609.30 | 0.59 | 0.53 | 0.53 | 6.70 | 0.17 | |
Maximum of Months | 0.146857E+10 | 0.132171E+10 | 18997.47 | 17097.73 | 17097.73 | 9.24 | 115.66 |
Report: PumpReportMonthly
For: COOLSYS1 CHILLER1 PUMP
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.326428E+10 | 0.293786E+10 | 6537.72 | 03-JAN-18:50 | 5883.95 | 5883.95 | 6.72 | 57.83 |
February | 0.350790E+10 | 0.315711E+10 | 6537.72 | 01-FEB-07:03 | 5883.95 | 5883.95 | 6.73 | 57.83 |
March | 0.339354E+10 | 0.305418E+10 | 6537.72 | 01-MAR-13:50 | 5883.95 | 5883.95 | 6.73 | 57.83 |
April | 0.261646E+10 | 0.235481E+10 | 6537.72 | 03-APR-03:10 | 5883.95 | 5883.95 | 6.73 | 57.83 |
May | 0.581454E+10 | 0.523308E+10 | 6537.72 | 01-MAY-06:10 | 5883.95 | 5883.95 | 6.73 | 57.83 |
June | 0.930354E+10 | 0.837318E+10 | 6537.72 | 01-JUN-04:12 | 5883.95 | 5883.95 | 7.05 | 57.83 |
July | 0.117851E+11 | 0.106066E+11 | 6537.72 | 01-JUL-04:12 | 5883.95 | 5883.95 | 6.83 | 57.83 |
August | 0.113214E+11 | 0.101893E+11 | 6537.72 | 01-AUG-00:03 | 5883.95 | 5883.95 | 6.75 | 57.83 |
September | 0.461476E+10 | 0.415328E+10 | 6537.72 | 01-SEP-00:40 | 5883.95 | 5883.95 | 6.87 | 57.83 |
October | 0.239703E+10 | 0.215733E+10 | 6537.72 | 01-OCT-08:43 | 5883.95 | 5883.95 | 7.04 | 57.83 |
November | 0.232594E+10 | 0.209335E+10 | 6537.72 | 01-NOV-04:11 | 5883.95 | 5883.95 | 6.78 | 57.83 |
December | 0.367213E+10 | 0.330492E+10 | 6537.72 | 01-DEC-07:05 | 5883.95 | 5883.95 | 6.72 | 57.83 |
Annual Sum or Average | 0.640166E+11 | 0.576150E+11 | ||||||
Minimum of Months | 0.232594E+10 | 0.209335E+10 | 6537.72 | 5883.95 | 5883.95 | 6.72 | 57.83 | |
Maximum of Months | 0.117851E+11 | 0.106066E+11 | 6537.72 | 5883.95 | 5883.95 | 7.05 | 57.83 |
Report: PumpReportMonthly
For: COOLSYS1 CHILLER2 PUMP
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 0.00 | 0.00 | 6.70 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 6.73 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 6.72 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 6.73 | 0.00 |
May | 0.768836E+09 | 0.691953E+09 | 6537.72 | 10-MAY-16:00 | 5883.95 | 5883.95 | 12.32 | 28.92 |
June | 0.177854E+10 | 0.160069E+10 | 6537.72 | 06-JUN-12:10 | 5883.95 | 5883.95 | 12.55 | 28.92 |
July | 0.260103E+10 | 0.234093E+10 | 6537.72 | 03-JUL-12:10 | 5883.95 | 5883.95 | 12.36 | 28.92 |
August | 0.192013E+10 | 0.172812E+10 | 6537.72 | 04-AUG-13:50 | 5883.95 | 5883.95 | 12.69 | 28.92 |
September | 0.180441E+09 | 0.162397E+09 | 6537.72 | 01-SEP-09:10 | 5883.95 | 5883.95 | 12.83 | 28.92 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 7.28 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 6.72 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 6.72 | 0.00 |
Annual Sum or Average | 0.724898E+10 | 0.652408E+10 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.70 | 0.00 | |
Maximum of Months | 0.260103E+10 | 0.234093E+10 | 6537.72 | 5883.95 | 5883.95 | 12.83 | 28.92 |
Report: PumpReportMonthly
For: PLANT CIRC PUMP
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.934337E+10 | 0.840904E+10 | 3488.42 | 01-JAN-00:01 | 3139.57 | 3139.57 | 18.46 | 14.57 |
February | 0.843918E+10 | 0.759526E+10 | 3488.42 | 01-FEB-00:03 | 3139.57 | 3139.57 | 18.80 | 14.57 |
March | 0.934337E+10 | 0.840904E+10 | 3488.42 | 01-MAR-00:10 | 3139.57 | 3139.57 | 19.79 | 14.57 |
April | 0.904198E+10 | 0.813778E+10 | 3488.42 | 01-APR-00:10 | 3139.57 | 3139.57 | 20.59 | 14.57 |
May | 0.934337E+10 | 0.840904E+10 | 3488.42 | 01-MAY-00:10 | 3139.57 | 3139.57 | 18.91 | 14.57 |
June | 0.904198E+10 | 0.813778E+10 | 3488.42 | 01-JUN-00:10 | 3139.57 | 3139.57 | 19.46 | 14.57 |
July | 0.934337E+10 | 0.840904E+10 | 3488.42 | 01-JUL-00:03 | 3139.57 | 3139.57 | 20.68 | 14.57 |
August | 0.934337E+10 | 0.840904E+10 | 3488.42 | 01-AUG-00:03 | 3139.57 | 3139.57 | 29.60 | 14.57 |
September | 0.904198E+10 | 0.813778E+10 | 3488.42 | 01-SEP-00:03 | 3139.57 | 3139.57 | 20.90 | 14.57 |
October | 0.934337E+10 | 0.840904E+10 | 3488.42 | 01-OCT-00:10 | 3139.57 | 3139.57 | 19.46 | 14.57 |
November | 0.904198E+10 | 0.813778E+10 | 3488.42 | 01-NOV-00:10 | 3139.57 | 3139.57 | 19.86 | 14.57 |
December | 0.934337E+10 | 0.840904E+10 | 3488.42 | 01-DEC-00:10 | 3139.57 | 3139.57 | 20.29 | 14.57 |
Annual Sum or Average | 0.110011E+12 | 0.990096E+11 | ||||||
Minimum of Months | 0.843918E+10 | 0.759526E+10 | 3488.42 | 3139.57 | 3139.57 | 18.46 | 14.57 | |
Maximum of Months | 0.934337E+10 | 0.840904E+10 | 3488.42 | 3139.57 | 3139.57 | 29.60 | 14.57 |
Report: PumpReportMonthly
For: SWHSYS1 PUMP
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.112905E+09 | 33871561.48 | 56.21 | 01-JAN-06:01 | 16.86 | 16.86 | 56.02 | 0.44 |
February | 0.101979E+09 | 30593668.43 | 56.21 | 01-FEB-06:01 | 16.86 | 16.86 | 55.72 | 0.44 |
March | 0.112905E+09 | 33871561.48 | 56.21 | 01-MAR-06:01 | 16.86 | 16.86 | 54.95 | 0.44 |
April | 0.109263E+09 | 32778930.46 | 56.21 | 01-APR-05:02 | 16.86 | 16.86 | 55.96 | 0.44 |
May | 0.112905E+09 | 33871561.48 | 56.21 | 01-MAY-05:02 | 16.86 | 16.86 | 56.14 | 0.44 |
June | 0.109263E+09 | 32778930.46 | 56.21 | 01-JUN-05:03 | 16.86 | 16.86 | 55.44 | 0.44 |
July | 0.112905E+09 | 33871561.48 | 56.21 | 01-JUL-05:03 | 16.86 | 16.86 | 56.60 | 0.44 |
August | 0.112905E+09 | 33871561.48 | 56.21 | 01-AUG-05:02 | 16.86 | 16.86 | 56.79 | 0.44 |
September | 0.109263E+09 | 32778930.46 | 56.21 | 01-SEP-05:03 | 16.86 | 16.86 | 55.61 | 0.44 |
October | 0.112905E+09 | 33871561.48 | 56.21 | 01-OCT-05:10 | 16.86 | 16.86 | 55.90 | 0.44 |
November | 0.109263E+09 | 32778930.46 | 56.21 | 01-NOV-05:02 | 16.86 | 16.86 | 56.09 | 0.44 |
December | 0.112905E+09 | 33871561.48 | 56.21 | 01-DEC-06:01 | 16.86 | 16.86 | 55.51 | 0.44 |
Annual Sum or Average | 0.132937E+10 | 0.398810E+09 | ||||||
Minimum of Months | 0.101979E+09 | 30593668.43 | 56.21 | 16.86 | 16.86 | 54.95 | 0.44 | |
Maximum of Months | 0.112905E+09 | 33871561.48 | 56.21 | 16.86 | 16.86 | 56.79 | 0.44 |
Report: PumpReportMonthly
For: TOWERWATERSYS PUMP
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.836324E+10 | 0.752692E+10 | 16752.44 | 23-JAN-11:20 | 15077.19 | 15077.19 | 21.14 | 67.89 |
February | 0.898748E+10 | 0.808874E+10 | 16752.71 | 08-FEB-11:00 | 15077.44 | 15077.44 | 21.16 | 67.89 |
March | 0.867352E+10 | 0.780617E+10 | 16752.62 | 28-MAR-12:40 | 15077.36 | 15077.36 | 21.15 | 67.89 |
April | 0.667867E+10 | 0.601080E+10 | 16785.70 | 13-APR-15:20 | 15107.13 | 15107.13 | 23.89 | 67.89 |
May | 0.163922E+11 | 0.147530E+11 | 33662.88 | 25-MAY-16:00 | 30296.59 | 30296.59 | 27.29 | 135.78 |
June | 0.278036E+11 | 0.250232E+11 | 33705.73 | 19-JUN-13:50 | 30335.16 | 30335.16 | 28.90 | 135.78 |
July | 0.363803E+11 | 0.327423E+11 | 33705.73 | 03-JUL-12:50 | 30335.16 | 30335.16 | 29.52 | 135.78 |
August | 0.333783E+11 | 0.300405E+11 | 33705.73 | 07-AUG-15:30 | 30335.16 | 30335.16 | 29.07 | 135.78 |
September | 0.122558E+11 | 0.110303E+11 | 33638.56 | 01-SEP-13:10 | 30274.70 | 30274.70 | 26.43 | 135.78 |
October | 0.613868E+10 | 0.552481E+10 | 16794.96 | 19-OCT-15:00 | 15115.46 | 15115.46 | 24.66 | 67.89 |
November | 0.595945E+10 | 0.536351E+10 | 16763.55 | 01-NOV-15:00 | 15087.20 | 15087.20 | 22.06 | 67.89 |
December | 0.940823E+10 | 0.846740E+10 | 16752.41 | 12-DEC-21:20 | 15077.17 | 15077.17 | 21.13 | 67.89 |
Annual Sum or Average | 0.180420E+12 | 0.162378E+12 | ||||||
Minimum of Months | 0.595945E+10 | 0.536351E+10 | 16752.41 | 15077.17 | 15077.17 | 21.13 | 67.89 | |
Maximum of Months | 0.363803E+11 | 0.327423E+11 | 33705.73 | 30335.16 | 30335.16 | 29.52 | 135.78 |
Report: CondLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:01 | 41.33 | 41.33 | 436534.11 | 2964503.23 | 09-JAN-07:02 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 45.22 | 82.00 | 231356.90 | 2629765.84 | 14-FEB-07:03 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 25.87 | 25.87 | 105348.04 | 2024309.83 | 06-MAR-05:01 |
April | 0.00 | 0.00 | 01-APR-00:10 | 26.22 | 26.22 | 30660.81 | 1740089.43 | 10-APR-04:01 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 24.14 | 24.14 | 2425.42 | 955228.26 | 01-MAY-05:02 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 33.55 | 33.55 | 79.86 | 94765.59 | 03-JUN-06:10 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 29.51 | 29.51 | 2.40 | 6831.32 | 08-JUL-06:10 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 29.36 | 29.36 | 92.70 | 121133.34 | 19-AUG-06:15 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 30.25 | 30.25 | 3217.67 | 388548.85 | 23-SEP-06:10 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 21.88 | 21.88 | 30790.62 | 1916873.07 | 16-OCT-04:11 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 25.53 | 25.53 | 102781.11 | 2185366.93 | 27-NOV-05:11 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 30.12 | 30.12 | 331501.41 | 2628294.04 | 26-DEC-07:03 |
Annual Sum or Average | 0.00 | 105993.73 | ||||||
Minimum of Months | 0.00 | 0.00 | 21.88 | 21.88 | 2.40 | 6831.32 | ||
Maximum of Months | 0.00 | 0.00 | 45.22 | 82.00 | 436534.11 | 2964503.23 |
Report: CondLoopDemandReportMonthly
For: COOLSYS1_SUPPLY
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 1098.19 | 6712.60 | 31-JAN-19:00 | 6.73 | 6.70 | 0.00 | 0.00 | 01-JAN-00:01 |
February | 1334.70 | 11458.35 | 11-FEB-13:30 | 6.75 | 6.70 | 0.00 | 0.00 | 01-FEB-00:03 |
March | 1255.60 | 37392.22 | 29-MAR-11:30 | 6.85 | 6.70 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 19377.22 | 757126.36 | 23-APR-15:13 | 9.82 | 6.70 | 0.00 | 0.00 | 01-APR-00:10 |
May | 177533.63 | 1697466.61 | 25-MAY-16:00 | 10.20 | 6.70 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 405668.67 | 2431315.66 | 19-JUN-15:20 | 11.72 | 6.70 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 527330.21 | 5920463.32 | 05-JUL-11:00 | 18.94 | 13.24 | 0.00 | 0.00 | 01-JUL-00:03 |
August | 384414.30 | 2504448.75 | 31-AUG-12:50 | 11.87 | 6.70 | 0.00 | 0.00 | 01-AUG-00:03 |
September | 88453.04 | 1807698.35 | 01-SEP-13:10 | 10.43 | 6.70 | 0.00 | 0.00 | 01-SEP-00:03 |
October | 15582.98 | 878274.66 | 19-OCT-15:00 | 10.32 | 6.70 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 2138.89 | 209358.89 | 01-NOV-15:00 | 7.56 | 6.70 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 1251.87 | 19031.41 | 18-DEC-16:30 | 6.78 | 6.70 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 136627.33 | 0.00 | ||||||
Minimum of Months | 1098.19 | 6712.60 | 6.73 | 6.70 | 0.00 | 0.00 | ||
Maximum of Months | 527330.21 | 5920463.32 | 18.94 | 13.24 | 0.00 | 0.00 |
Report: CondLoopDemandReportMonthly
For: COOLSYS1_DEMAND
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 1.62 | 1032.15 | 31-JAN-19:00 | 8.33 | 6.70 | 0.00 | 0.00 | 01-JAN-00:01 |
February | 29.63 | 8451.36 | 10-FEB-10:25 | 9.68 | 6.70 | 0.00 | 0.00 | 01-FEB-00:03 |
March | 115.37 | 39197.42 | 29-MAR-11:30 | 12.55 | 6.70 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 18477.79 | 1269778.65 | 23-APR-14:31 | 13.64 | 6.70 | 0.00 | 0.00 | 01-APR-00:10 |
May | 174495.71 | 1832933.85 | 26-MAY-05:03 | 14.19 | 6.76 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 400431.98 | 4415765.01 | 29-JUN-04:12 | 15.82 | 11.25 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 522659.51 | 5925362.86 | 05-JUL-11:00 | 18.95 | 13.21 | 0.00 | 0.00 | 01-JUL-00:03 |
August | 379298.85 | 3115501.28 | 09-AUG-05:03 | 14.13 | 9.83 | 0.00 | 0.00 | 01-AUG-00:03 |
September | 86959.54 | 1800884.51 | 01-SEP-13:10 | 13.32 | 6.70 | 0.00 | 0.00 | 01-SEP-00:03 |
October | 14780.84 | 874525.67 | 19-OCT-15:00 | 11.52 | 6.70 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 1331.56 | 204799.10 | 01-NOV-15:00 | 13.31 | 6.70 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 17.95 | 16369.63 | 18-DEC-16:30 | 13.10 | 6.70 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 134381.70 | 0.00 | ||||||
Minimum of Months | 1.62 | 1032.15 | 8.33 | 6.70 | 0.00 | 0.00 | ||
Maximum of Months | 522659.51 | 5925362.86 | 18.95 | 13.21 | 0.00 | 0.00 |
Report: CondLoopDemandReportMonthly
For: SINGLE WATER PLANT LOOP
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 8872.37 | 43744.20 | 20-JAN-15:10 | 19.20 | 18.33 | 0.00 | 0.00 | 01-JAN-00:01 |
February | 39966.46 | 189387.86 | 08-FEB-11:05 | 22.07 | 18.33 | 0.00 | 0.00 | 01-FEB-00:03 |
March | 76957.42 | 243459.25 | 22-MAR-14:47 | 23.13 | 18.33 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 148223.58 | 1420080.64 | 23-APR-16:00 | 45.75 | 32.94 | 0.00 | 0.00 | 01-APR-00:10 |
May | 108327.18 | 919709.74 | 25-MAY-18:00 | 36.25 | 31.62 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 327841.19 | 1495861.23 | 29-JUN-16:00 | 47.18 | 38.99 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 666961.07 | 1762986.71 | 15-JUL-14:10 | 52.17 | 38.04 | 0.00 | 0.00 | 01-JUL-00:03 |
August | 708662.80 | 1753189.70 | 08-AUG-15:10 | 51.99 | 37.65 | 0.00 | 0.00 | 01-AUG-00:03 |
September | 49855.45 | 725652.29 | 01-SEP-15:10 | 32.52 | 28.17 | 0.00 | 0.00 | 01-SEP-00:03 |
October | 57199.26 | 486434.31 | 19-OCT-15:00 | 27.88 | 24.03 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 75374.87 | 328726.74 | 01-NOV-15:00 | 24.81 | 20.38 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 92367.76 | 191016.77 | 20-DEC-11:50 | 22.10 | 18.33 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 198514.24 | 0.00 | ||||||
Minimum of Months | 8872.37 | 43744.20 | 19.20 | 18.33 | 0.00 | 0.00 | ||
Maximum of Months | 708662.80 | 1762986.71 | 52.17 | 38.99 | 0.00 | 0.00 |
Report: CondLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:01 | 56.94 | 56.94 | 18359.19 | 62795.00 | 31-JAN-12:45 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 56.14 | 56.14 | 18850.20 | 63325.26 | 28-FEB-12:15 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 55.55 | 55.55 | 19868.19 | 63330.10 | 02-MAR-12:35 |
April | 0.00 | 0.00 | 01-APR-00:10 | 56.60 | 56.60 | 18187.89 | 62114.39 | 04-APR-11:40 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 56.73 | 56.73 | 17881.68 | 59634.56 | 01-MAY-11:50 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 56.17 | 56.17 | 17273.80 | 56292.94 | 01-JUN-11:40 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 57.21 | 57.21 | 15239.56 | 52952.96 | 03-JUL-11:30 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 57.31 | 57.31 | 16116.39 | 50926.39 | 01-AUG-12:00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 56.18 | 56.18 | 15273.24 | 51339.04 | 29-SEP-11:40 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 57.00 | 57.00 | 15790.02 | 53980.11 | 31-OCT-11:40 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 56.70 | 56.70 | 16844.85 | 57251.03 | 30-NOV-12:40 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 55.97 | 55.97 | 17181.31 | 60309.58 | 29-DEC-12:20 |
Annual Sum or Average | 0.00 | 17229.38 | ||||||
Minimum of Months | 0.00 | 0.00 | 55.55 | 55.55 | 15239.56 | 50926.39 | ||
Maximum of Months | 0.00 | 0.00 | 57.31 | 57.31 | 19868.19 | 63330.10 |
Report: CondLoopDemandReportMonthly
For: TOWERWATERSYS
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 76.71 | 10276.71 | 23-JAN-11:20 | 21.14 | 20.26 | 9101.89 | 160653.31 | 23-JAN-01:41 |
February | 91.91 | 16614.56 | 08-FEB-11:00 | 21.16 | 20.28 | 10111.02 | 158092.75 | 27-FEB-01:22 |
March | 73.48 | 14607.38 | 28-MAR-12:40 | 21.15 | 20.39 | 8841.80 | 157867.10 | 20-MAR-11:40 |
April | 21213.49 | 792834.03 | 13-APR-15:20 | 23.89 | 21.10 | 3635.59 | 157054.37 | 27-APR-12:20 |
May | 234590.02 | 3514222.44 | 25-MAY-16:00 | 27.29 | 23.83 | 1084.62 | 131543.95 | 05-MAY-05:50 |
June | 739174.28 | 6665014.56 | 30-JUN-16:00 | 32.84 | 28.54 | 338.90 | 91228.17 | 02-JUN-16:50 |
July | 962620.86 | 7328702.72 | 05-JUL-11:00 | 34.01 | 28.46 | 195.31 | 57109.39 | 17-JUL-07:20 |
August | 656848.85 | 6008573.40 | 31-AUG-12:50 | 31.69 | 26.68 | 649.68 | 71112.28 | 02-AUG-08:50 |
September | 111933.10 | 3025213.52 | 01-SEP-13:10 | 26.43 | 22.76 | 782.54 | 130788.57 | 14-SEP-06:00 |
October | 17450.29 | 1010305.85 | 19-OCT-15:00 | 24.66 | 21.10 | 3041.11 | 153827.72 | 13-OCT-15:50 |
November | 1705.31 | 272122.10 | 01-NOV-15:00 | 22.06 | 21.10 | 5735.06 | 161725.65 | 23-NOV-20:32 |
December | 93.99 | 9561.33 | 12-DEC-21:20 | 21.13 | 20.26 | 9670.34 | 148496.45 | 18-DEC-13:00 |
Annual Sum or Average | 230815.72 | 4405.48 | ||||||
Minimum of Months | 73.48 | 9561.33 | 21.13 | 20.26 | 195.31 | 57109.39 | ||
Maximum of Months | 962620.86 | 7328702.72 | 34.01 | 28.54 | 10111.02 | 161725.65 |
Report: ZoneTemperatureOscillationReportMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV_BOT WITH REHEAT
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.585462E+11 | 0.00 | 18529901.46 | 0.408998E+10 | 0.00 | 0.00 |
February | 0.224598E+11 | 0.00 | 70658977.20 | 0.462882E+10 | 0.00 | 0.00 |
March | 0.888071E+10 | 0.00 | 91912802.74 | 0.694070E+10 | 0.00 | 0.00 |
April | 0.193169E+10 | 0.00 | 0.517077E+10 | 0.890931E+10 | 0.00 | 0.00 |
May | 0.178837E+09 | 0.00 | 0.398890E+11 | 0.102794E+11 | 0.00 | 0.00 |
June | 2367970.25 | 0.00 | 0.932611E+11 | 0.131499E+11 | 0.00 | 0.00 |
July | 5.14 | 0.00 | 0.128694E+12 | 0.153649E+11 | 0.00 | 0.00 |
August | 3105444.49 | 0.00 | 0.100130E+12 | 0.147521E+11 | 0.00 | 0.00 |
September | 0.172997E+09 | 0.00 | 0.203591E+11 | 0.811369E+10 | 0.00 | 0.00 |
October | 0.135563E+10 | 0.00 | 0.358375E+10 | 0.635692E+10 | 0.00 | 0.00 |
November | 0.497034E+10 | 0.00 | 0.443864E+09 | 0.534403E+10 | 0.00 | 0.00 |
December | 0.310197E+11 | 0.00 | 21125539.57 | 0.452863E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.129521E+12 | 0.00 | 0.391734E+12 | 0.102458E+12 | 0.00 | 0.00 |
Minimum of Months | 5.14 | 0.00 | 18529901.46 | 0.408998E+10 | 0.00 | 0.00 |
Maximum of Months | 0.585462E+11 | 0.00 | 0.128694E+12 | 0.153649E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV_MID WITH REHEAT
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.978857E+12 | 0.00 | 943638.22 | 0.497949E+11 | 0.00 | 0.00 |
February | 0.464061E+12 | 0.00 | 51940257.94 | 0.413208E+11 | 0.00 | 0.00 |
March | 0.231591E+12 | 0.00 | 0.178942E+09 | 0.450207E+11 | 0.00 | 0.00 |
April | 0.651004E+11 | 0.00 | 0.383648E+11 | 0.520985E+11 | 0.00 | 0.00 |
May | 0.507678E+10 | 0.00 | 0.356931E+12 | 0.824135E+11 | 0.00 | 0.00 |
June | 0.182535E+09 | 0.00 | 0.796711E+12 | 0.103001E+12 | 0.00 | 0.00 |
July | 5324533.71 | 0.00 | 0.103109E+13 | 0.115665E+12 | 0.00 | 0.00 |
August | 0.138633E+09 | 0.00 | 0.768851E+12 | 0.970260E+11 | 0.00 | 0.00 |
September | 0.651227E+10 | 0.00 | 0.177513E+12 | 0.615698E+11 | 0.00 | 0.00 |
October | 0.680162E+11 | 0.00 | 0.320185E+11 | 0.429194E+11 | 0.00 | 0.00 |
November | 0.220362E+12 | 0.00 | 0.256935E+10 | 0.371537E+11 | 0.00 | 0.00 |
December | 0.745864E+12 | 0.00 | 512583.72 | 0.462448E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.278577E+13 | 0.00 | 0.320428E+13 | 0.774228E+12 | 0.00 | 0.00 |
Minimum of Months | 5324533.71 | 0.00 | 512583.72 | 0.371537E+11 | 0.00 | 0.00 |
Maximum of Months | 0.978857E+12 | 0.00 | 0.103109E+13 | 0.115665E+12 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV_TOP WITH REHEAT
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.141172E+12 | 0.00 | 744322.17 | 0.565314E+10 | 0.00 | 0.00 |
February | 0.784007E+11 | 0.00 | 11637184.48 | 0.483130E+10 | 0.00 | 0.00 |
March | 0.443178E+11 | 0.00 | 46726950.28 | 0.476671E+10 | 0.00 | 0.00 |
April | 0.132080E+11 | 0.00 | 0.364001E+10 | 0.460154E+10 | 0.00 | 0.00 |
May | 0.122309E+10 | 0.00 | 0.377033E+11 | 0.732535E+10 | 0.00 | 0.00 |
June | 58172113.63 | 0.00 | 0.834621E+11 | 0.973738E+10 | 0.00 | 0.00 |
July | 2449964.03 | 0.00 | 0.108927E+12 | 0.109133E+11 | 0.00 | 0.00 |
August | 0.101247E+09 | 0.00 | 0.789273E+11 | 0.876917E+10 | 0.00 | 0.00 |
September | 0.180029E+10 | 0.00 | 0.168080E+11 | 0.509588E+10 | 0.00 | 0.00 |
October | 0.138282E+11 | 0.00 | 0.288334E+10 | 0.392007E+10 | 0.00 | 0.00 |
November | 0.435212E+11 | 0.00 | 0.245820E+09 | 0.445128E+10 | 0.00 | 0.00 |
December | 0.119009E+12 | 0.00 | 589398.11 | 0.540392E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.456642E+12 | 0.00 | 0.332657E+12 | 0.754691E+11 | 0.00 | 0.00 |
Minimum of Months | 2449964.03 | 0.00 | 589398.11 | 0.392007E+10 | 0.00 | 0.00 |
Maximum of Months | 0.141172E+12 | 0.00 | 0.108927E+12 | 0.109133E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: CAV_BAS
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.932215E+09 | 0.00 | 33776607.20 | 0.147474E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 40624363.97 | 0.139169E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 23579530.63 | 0.167521E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.814743E+09 | 0.154454E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.200178E+11 | 0.165600E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.452142E+11 | 0.161965E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.595295E+11 | 0.163982E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.477552E+11 | 0.178045E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.855878E+10 | 0.164227E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.116867E+10 | 0.162313E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.154435E+09 | 0.153326E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 60024891.36 | 0.151002E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.932215E+09 | 0.00 | 0.183371E+12 | 0.190908E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 23579530.63 | 0.139169E+11 | 0.00 | 0.00 |
Maximum of Months | 0.932215E+09 | 0.00 | 0.595295E+11 | 0.178045E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER BASEMENT
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.992799E+10 | 0.222295E+12 | 0.00 | 44.43 |
February | 0.00 | 0.00 | 0.159405E+11 | 0.300243E+12 | 0.00 | 76.53 |
March | 0.00 | 0.00 | 0.214109E+11 | 0.373335E+12 | 0.00 | 99.54 |
April | 0.00 | 0.00 | 0.772610E+11 | 0.368246E+12 | 0.00 | 93.79 |
May | 0.00 | 0.00 | 0.395006E+11 | 0.210322E+12 | 0.00 | 37.12 |
June | 0.00 | 0.00 | 0.233729E+12 | 0.196318E+12 | 0.00 | 16.25 |
July | 0.00 | 0.00 | 0.711901E+12 | 0.260369E+12 | 0.00 | 0.29 |
August | 0.00 | 0.00 | 0.889261E+12 | 0.294439E+12 | 0.00 | 0.59 |
September | 0.00 | 0.00 | 0.967944E+10 | 0.139946E+12 | 0.00 | 14.93 |
October | 0.00 | 0.00 | 0.162546E+11 | 0.270958E+12 | 0.00 | 61.96 |
November | 0.00 | 0.00 | 0.219224E+11 | 0.344124E+12 | 0.00 | 89.86 |
December | 0.00 | 0.00 | 0.225792E+11 | 0.374109E+12 | 0.00 | 99.64 |
Annual Sum or Average | 0.00 | 0.00 | 0.206937E+13 | 0.335470E+13 | 0.00 | 634.93 |
Minimum of Months | 0.00 | 0.00 | 0.967944E+10 | 0.139946E+12 | 0.00 | 0.29 |
Maximum of Months | 0.00 | 0.00 | 0.889261E+12 | 0.374109E+12 | 0.00 | 99.64 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER BOT
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.241731E+10 | 0.217931E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.950085E+10 | 0.346336E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.179707E+11 | 0.518893E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.245702E+11 | 0.624865E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.763357E+10 | 0.320829E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.140612E+11 | 0.448080E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.213382E+11 | 0.614061E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.272059E+11 | 0.710547E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.701607E+10 | 0.297312E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.126097E+11 | 0.407457E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.174015E+11 | 0.498489E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.227750E+11 | 0.610516E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.184500E+12 | 0.561531E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.241731E+10 | 0.217931E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.272059E+11 | 0.710547E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER MID
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.288009E+10 | 0.162960E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.595526E+11 | 0.269834E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.145600E+12 | 0.449899E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.218017E+12 | 0.570368E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.666140E+11 | 0.295874E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.130157E+12 | 0.421977E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.201906E+12 | 0.584746E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.256087E+12 | 0.673935E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.576211E+11 | 0.267770E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.100545E+12 | 0.355065E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.135339E+12 | 0.421918E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.177453E+12 | 0.512943E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.155177E+13 | 0.498729E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.288009E+10 | 0.162960E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.256087E+12 | 0.673935E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER TOP
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.131585E+09 | 0.161096E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.409548E+10 | 0.232439E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.125808E+11 | 0.414289E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.203111E+11 | 0.546938E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.609056E+10 | 0.286743E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.127458E+11 | 0.419586E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.200617E+11 | 0.585514E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.253953E+11 | 0.673364E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.496608E+10 | 0.254524E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.818913E+10 | 0.321628E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.113392E+11 | 0.382244E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.157607E+11 | 0.478406E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.141667E+12 | 0.475677E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.131585E+09 | 0.161096E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.253953E+11 | 0.673364E+10 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV_BOT WITH REHEAT
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.408998E+10 | 18529901.46 | 0.585462E+11 | 0.807605E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.462882E+10 | 70658977.20 | 0.224598E+11 | 0.626690E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.694070E+10 | 91912802.74 | 0.888071E+10 | 0.498597E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.890931E+10 | 0.517077E+10 | 0.193169E+10 | 0.110299E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.102794E+11 | 0.398890E+11 | 0.178837E+09 | 0.162384E+10 | 0.279407E+09 | 0.00 | 0.00 | 0.00 |
June | 0.131499E+11 | 0.932611E+11 | 2367970.25 | 54230762.81 | 0.541270E+10 | 0.00 | 0.00 | 0.00 |
July | 0.153649E+11 | 0.128694E+12 | 5.14 | 69379244.83 | 0.662205E+10 | 0.00 | 0.00 | 0.00 |
August | 0.147521E+11 | 0.100130E+12 | 3105444.49 | 16893305.41 | 0.345335E+10 | 0.00 | 0.00 | 0.00 |
September | 0.811369E+10 | 0.203591E+11 | 0.172997E+09 | 0.150677E+10 | 61067691.38 | 0.00 | 0.00 | 0.00 |
October | 0.635692E+10 | 0.358375E+10 | 0.135563E+10 | 0.106606E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.534403E+10 | 0.443864E+09 | 0.497034E+10 | 0.330716E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.452863E+10 | 21125539.57 | 0.310197E+11 | 0.775226E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.102458E+12 | 0.391734E+12 | 0.129521E+12 | 0.328845E+12 | 0.158286E+11 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.408998E+10 | 18529901.46 | 5.14 | 16893305.41 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.153649E+11 | 0.128694E+12 | 0.585462E+11 | 0.807605E+11 | 0.662205E+10 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV_MID WITH REHEAT
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.497949E+11 | 943638.22 | 0.978857E+12 | 0.809788E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.413208E+11 | 51940257.94 | 0.464061E+12 | 0.720985E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.450207E+11 | 0.178942E+09 | 0.231591E+12 | 0.696133E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.520985E+11 | 0.383652E+11 | 0.651004E+11 | 0.217801E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.824135E+11 | 0.356931E+12 | 0.507678E+10 | 0.289178E+11 | 0.306383E+10 | 0.00 | 0.00 | 0.00 |
June | 0.103001E+12 | 0.796711E+12 | 0.182535E+09 | 0.106143E+10 | 0.543558E+11 | 0.00 | 0.00 | 0.00 |
July | 0.115665E+12 | 0.103109E+13 | 5324533.71 | 0.948549E+09 | 0.649707E+11 | 0.00 | 0.00 | 0.00 |
August | 0.970260E+11 | 0.768851E+12 | 0.138633E+09 | 0.118166E+10 | 0.332719E+11 | 0.00 | 0.00 | 0.00 |
September | 0.615698E+11 | 0.177513E+12 | 0.651227E+10 | 0.297487E+11 | 0.752616E+09 | 0.00 | 0.00 | 0.00 |
October | 0.429194E+11 | 0.320185E+11 | 0.680162E+11 | 0.199071E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.371537E+11 | 0.258794E+10 | 0.220362E+12 | 0.478166E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.462448E+11 | 512583.72 | 0.745864E+12 | 0.848185E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.774228E+12 | 0.320430E+13 | 0.278577E+13 | 0.403199E+13 | 0.156415E+12 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.371537E+11 | 512583.72 | 5324533.71 | 0.948549E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.115665E+12 | 0.103109E+13 | 0.978857E+12 | 0.848185E+12 | 0.649707E+11 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV_TOP WITH REHEAT
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.565314E+10 | 744322.17 | 0.141172E+12 | 0.785307E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.483130E+10 | 11637184.48 | 0.784007E+11 | 0.701052E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.476671E+10 | 46726950.28 | 0.443178E+11 | 0.717974E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.460154E+10 | 0.364001E+10 | 0.132080E+11 | 0.272445E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.732535E+10 | 0.377033E+11 | 0.122309E+10 | 0.433043E+10 | 0.230601E+09 | 0.00 | 0.00 | 0.00 |
June | 0.973738E+10 | 0.834621E+11 | 58172113.63 | 0.121045E+09 | 0.499240E+10 | 0.00 | 0.00 | 0.00 |
July | 0.109133E+11 | 0.108927E+12 | 2449964.03 | 47002139.83 | 0.561109E+10 | 0.00 | 0.00 | 0.00 |
August | 0.876917E+10 | 0.789273E+11 | 0.101247E+09 | 0.182672E+09 | 0.262911E+10 | 0.00 | 0.00 | 0.00 |
September | 0.509588E+10 | 0.168080E+11 | 0.180029E+10 | 0.498113E+10 | 32077026.48 | 0.00 | 0.00 | 0.00 |
October | 0.392007E+10 | 0.288334E+10 | 0.138282E+11 | 0.267998E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.445128E+10 | 0.245820E+09 | 0.435212E+11 | 0.511382E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.540392E+10 | 589398.11 | 0.119009E+12 | 0.812847E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.754691E+11 | 0.332657E+12 | 0.456642E+12 | 0.416563E+12 | 0.134953E+11 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.392007E+10 | 589398.11 | 2449964.03 | 47002139.83 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.109133E+11 | 0.108927E+12 | 0.141172E+12 | 0.812847E+11 | 0.561109E+10 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: CAV_BAS
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.147474E+11 | 33776607.20 | 0.932215E+09 | 0.236767E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.139169E+11 | 40624363.97 | 0.00 | 0.117538E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.167521E+11 | 23579530.63 | 0.00 | 0.443248E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.154454E+11 | 0.814743E+09 | 0.00 | 0.429417E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.165600E+11 | 0.200178E+11 | 0.00 | 0.512425E+09 | 65588513.47 | 0.00 | 0.00 | 0.00 |
June | 0.161965E+11 | 0.452142E+11 | 0.00 | 0.133210E+09 | 0.212660E+10 | 0.00 | 0.00 | 0.00 |
July | 0.163982E+11 | 0.595295E+11 | 0.00 | 0.181734E+09 | 0.237527E+10 | 0.00 | 0.00 | 0.00 |
August | 0.178045E+11 | 0.477552E+11 | 0.00 | 0.106185E+09 | 0.131424E+10 | 0.00 | 0.00 | 0.00 |
September | 0.164227E+11 | 0.855878E+10 | 0.00 | 0.177500E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.162313E+11 | 0.116867E+10 | 0.00 | 0.230926E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.153326E+11 | 0.154435E+09 | 0.00 | 0.145223E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.151002E+11 | 60024891.36 | 0.00 | 0.129139E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.190908E+12 | 0.183371E+12 | 0.932215E+09 | 0.560005E+11 | 0.588170E+10 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.139169E+11 | 23579530.63 | 0.00 | 0.106185E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.178045E+11 | 0.595295E+11 | 0.932215E+09 | 0.236767E+11 | 0.237527E+10 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER BASEMENT
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.987438E+11 | 0.582103E+10 | 0.00 | 0.00 | 0.00 | 0.118909E+12 | 0.00 | 0.00 |
February | 0.891880E+11 | 0.106108E+11 | 0.00 | 0.00 | 0.00 | 0.204803E+12 | 0.00 | 0.00 |
March | 0.987438E+11 | 0.144095E+11 | 0.00 | 0.00 | 0.00 | 0.266390E+12 | 0.00 | 0.00 |
April | 0.955586E+11 | 0.567057E+11 | 0.00 | 0.00 | 0.00 | 0.251003E+12 | 0.00 | 0.00 |
May | 0.987438E+11 | 0.276953E+11 | 0.00 | 0.00 | 0.00 | 0.993255E+11 | 0.00 | 0.00 |
June | 0.955586E+11 | 0.176663E+12 | 0.00 | 0.00 | 0.00 | 0.434980E+11 | 0.00 | 0.00 |
July | 0.987438E+11 | 0.551045E+12 | 0.00 | 0.00 | 0.00 | 0.765411E+09 | 0.00 | 0.00 |
August | 0.987438E+11 | 0.695164E+12 | 0.00 | 0.00 | 0.00 | 0.159198E+10 | 0.00 | 0.00 |
September | 0.955586E+11 | 0.541516E+10 | 0.00 | 0.00 | 0.00 | 0.399436E+11 | 0.00 | 0.00 |
October | 0.987438E+11 | 0.106052E+11 | 0.00 | 0.00 | 0.00 | 0.165818E+12 | 0.00 | 0.00 |
November | 0.955586E+11 | 0.149034E+11 | 0.00 | 0.00 | 0.00 | 0.240464E+12 | 0.00 | 0.00 |
December | 0.987438E+11 | 0.150538E+11 | 0.00 | 0.00 | 0.00 | 0.266640E+12 | 0.00 | 0.00 |
Annual Sum or Average | 0.116263E+13 | 0.158409E+13 | 0.00 | 0.00 | 0.00 | 0.169915E+13 | 0.00 | 0.00 |
Minimum of Months | 0.891880E+11 | 0.541516E+10 | 0.00 | 0.00 | 0.00 | 0.765411E+09 | 0.00 | 0.00 |
Maximum of Months | 0.987438E+11 | 0.695164E+12 | 0.00 | 0.00 | 0.00 | 0.266640E+12 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER BOT
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.161809E+10 | 0.185608E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.146150E+10 | 0.749899E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.161809E+10 | 0.143998E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.156589E+10 | 0.198874E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.161809E+10 | 0.604336E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.156589E+10 | 0.111463E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.161809E+10 | 0.168157E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.161809E+10 | 0.217185E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.156589E+10 | 0.560885E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.161809E+10 | 0.101532E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.156589E+10 | 0.139825E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.161809E+10 | 0.182879E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.190517E+11 | 0.147399E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.146150E+10 | 0.185608E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.161809E+10 | 0.217185E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER MID
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.155843E+11 | 0.216834E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.140761E+11 | 0.466453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.155843E+11 | 0.116194E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.150816E+11 | 0.176061E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.155843E+11 | 0.526109E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.150816E+11 | 0.103041E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.155843E+11 | 0.159015E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.155843E+11 | 0.204278E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.150816E+11 | 0.459257E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.155843E+11 | 0.806228E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.150816E+11 | 0.108229E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.155843E+11 | 0.141743E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.183492E+12 | 0.123653E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.140761E+11 | 0.216834E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.155843E+11 | 0.204278E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER TOP
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.157918E+10 | 99812034.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.142636E+10 | 0.319744E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.157918E+10 | 0.100171E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.152824E+10 | 0.163700E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.157918E+10 | 0.480231E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.152824E+10 | 0.100781E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.157918E+10 | 0.157857E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.157918E+10 | 0.202409E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.152824E+10 | 0.394908E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.157918E+10 | 0.655203E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.152824E+10 | 0.904495E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.157918E+10 | 0.125558E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.185936E+11 | 0.112693E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.142636E+10 | 99812034.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.157918E+10 | 0.202409E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV_BOT WITH REHEAT
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.408998E+10 | 0.585462E+11 | 18529901.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.462882E+10 | 0.224598E+11 | 70658977.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.694070E+10 | 0.888071E+10 | 91912802.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.890931E+10 | 0.193169E+10 | 0.517077E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.102794E+11 | 0.178837E+09 | 0.398890E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.131499E+11 | 2367970.25 | 0.932611E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.153649E+11 | 5.14 | 0.128694E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.147521E+11 | 3105444.49 | 0.100130E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.811369E+10 | 0.172997E+09 | 0.203591E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.635692E+10 | 0.135563E+10 | 0.358375E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.534403E+10 | 0.497034E+10 | 0.443864E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.452863E+10 | 0.310197E+11 | 21125539.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.102458E+12 | 0.129521E+12 | 0.391734E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.408998E+10 | 5.14 | 18529901.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.153649E+11 | 0.585462E+11 | 0.128694E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV_MID WITH REHEAT
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.497949E+11 | 0.978857E+12 | 943638.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.413208E+11 | 0.464061E+12 | 51940257.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.450207E+11 | 0.231591E+12 | 0.178942E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.520985E+11 | 0.651004E+11 | 0.383648E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.824135E+11 | 0.507678E+10 | 0.356931E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.103001E+12 | 0.182535E+09 | 0.796711E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.115665E+12 | 5324533.71 | 0.103109E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.970260E+11 | 0.138633E+09 | 0.768851E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.615698E+11 | 0.651227E+10 | 0.177513E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.429194E+11 | 0.680162E+11 | 0.320185E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.371537E+11 | 0.220362E+12 | 0.256935E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.462448E+11 | 0.745864E+12 | 512583.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.774228E+12 | 0.278577E+13 | 0.320428E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.371537E+11 | 5324533.71 | 512583.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.115665E+12 | 0.978857E+12 | 0.103109E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV_TOP WITH REHEAT
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.565314E+10 | 0.141172E+12 | 744322.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.483130E+10 | 0.784007E+11 | 11637184.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.476671E+10 | 0.443178E+11 | 46726950.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.460154E+10 | 0.132080E+11 | 0.364001E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.732535E+10 | 0.122309E+10 | 0.377033E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.973738E+10 | 58172113.63 | 0.834621E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.109133E+11 | 2449964.03 | 0.108927E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.876917E+10 | 0.101247E+09 | 0.789273E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.509588E+10 | 0.180029E+10 | 0.168080E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.392007E+10 | 0.138282E+11 | 0.288334E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.445128E+10 | 0.435212E+11 | 0.245820E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.540392E+10 | 0.119009E+12 | 589398.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.754691E+11 | 0.456642E+12 | 0.332657E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.392007E+10 | 2449964.03 | 589398.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.109133E+11 | 0.141172E+12 | 0.108927E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: CAV_BAS
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.147474E+11 | 0.932215E+09 | 33776607.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.139169E+11 | 0.00 | 40624363.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.167521E+11 | 0.00 | 23579530.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.154454E+11 | 0.00 | 0.814743E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.165600E+11 | 0.00 | 0.200178E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.161965E+11 | 0.00 | 0.452142E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.163982E+11 | 0.00 | 0.595295E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.178045E+11 | 0.00 | 0.477552E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.164227E+11 | 0.00 | 0.855878E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.162313E+11 | 0.00 | 0.116867E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.153326E+11 | 0.00 | 0.154435E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.151002E+11 | 0.00 | 60024891.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.190908E+12 | 0.932215E+09 | 0.183371E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.139169E+11 | 0.00 | 23579530.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.178045E+11 | 0.932215E+09 | 0.595295E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER BASEMENT
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.987438E+11 | 0.00 | 0.992799E+10 | 0.00 | 0.410696E+10 | 0.00 | 0.00 | 0.00 | 0.119444E+12 | 0.00 | 0.00 | 0.00 |
February | 0.891880E+11 | 0.00 | 0.159405E+11 | 0.00 | 0.532970E+10 | 0.00 | 0.00 | 0.00 | 0.205725E+12 | 0.00 | 0.00 | 0.00 |
March | 0.987438E+11 | 0.00 | 0.214109E+11 | 0.00 | 0.700143E+10 | 0.00 | 0.00 | 0.00 | 0.267589E+12 | 0.00 | 0.00 | 0.00 |
April | 0.955586E+11 | 0.00 | 0.772610E+11 | 0.00 | 0.205553E+11 | 0.00 | 0.00 | 0.00 | 0.252133E+12 | 0.00 | 0.00 | 0.00 |
May | 0.987438E+11 | 0.00 | 0.395006E+11 | 0.00 | 0.118053E+11 | 0.00 | 0.00 | 0.00 | 0.997726E+11 | 0.00 | 0.00 | 0.00 |
June | 0.955586E+11 | 0.00 | 0.233729E+12 | 0.00 | 0.570657E+11 | 0.00 | 0.00 | 0.00 | 0.436938E+11 | 0.00 | 0.00 | 0.00 |
July | 0.987438E+11 | 0.00 | 0.711901E+12 | 0.00 | 0.160856E+12 | 0.00 | 0.00 | 0.00 | 0.768856E+09 | 0.00 | 0.00 | 0.00 |
August | 0.987438E+11 | 0.00 | 0.889261E+12 | 0.00 | 0.194096E+12 | 0.00 | 0.00 | 0.00 | 0.159915E+10 | 0.00 | 0.00 | 0.00 |
September | 0.955586E+11 | 0.00 | 0.967944E+10 | 0.00 | 0.426428E+10 | 0.00 | 0.00 | 0.00 | 0.401234E+11 | 0.00 | 0.00 | 0.00 |
October | 0.987438E+11 | 0.00 | 0.162546E+11 | 0.00 | 0.564937E+10 | 0.00 | 0.00 | 0.00 | 0.166564E+12 | 0.00 | 0.00 | 0.00 |
November | 0.955586E+11 | 0.00 | 0.219224E+11 | 0.00 | 0.701903E+10 | 0.00 | 0.00 | 0.00 | 0.241546E+12 | 0.00 | 0.00 | 0.00 |
December | 0.987438E+11 | 0.00 | 0.225792E+11 | 0.00 | 0.752547E+10 | 0.00 | 0.00 | 0.00 | 0.267840E+12 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.116263E+13 | 0.00 | 0.206937E+13 | 0.00 | 0.485275E+12 | 0.00 | 0.00 | 0.00 | 0.170680E+13 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.891880E+11 | 0.00 | 0.967944E+10 | 0.00 | 0.410696E+10 | 0.00 | 0.00 | 0.00 | 0.768856E+09 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.987438E+11 | 0.00 | 0.889261E+12 | 0.00 | 0.194096E+12 | 0.00 | 0.00 | 0.00 | 0.267840E+12 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER BOT
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.161809E+10 | 0.00 | 0.241731E+10 | 0.00 | 0.561227E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.146150E+10 | 0.00 | 0.950085E+10 | 0.00 | 0.200186E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.161809E+10 | 0.00 | 0.179707E+11 | 0.00 | 0.357084E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.156589E+10 | 0.00 | 0.245702E+11 | 0.00 | 0.468275E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.161809E+10 | 0.00 | 0.763357E+10 | 0.00 | 0.159021E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.156589E+10 | 0.00 | 0.140612E+11 | 0.00 | 0.291490E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.161809E+10 | 0.00 | 0.213382E+11 | 0.00 | 0.452252E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.161809E+10 | 0.00 | 0.272059E+11 | 0.00 | 0.548738E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.156589E+10 | 0.00 | 0.701607E+10 | 0.00 | 0.140722E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.161809E+10 | 0.00 | 0.126097E+11 | 0.00 | 0.245648E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.156589E+10 | 0.00 | 0.174015E+11 | 0.00 | 0.341900E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.161809E+10 | 0.00 | 0.227750E+11 | 0.00 | 0.448707E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.190517E+11 | 0.00 | 0.184500E+12 | 0.00 | 0.371015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.146150E+10 | 0.00 | 0.241731E+10 | 0.00 | 0.561227E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.161809E+10 | 0.00 | 0.272059E+11 | 0.00 | 0.548738E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER MID
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.155843E+11 | 0.00 | 0.288009E+10 | 0.00 | 0.711751E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.140761E+11 | 0.00 | 0.595526E+11 | 0.00 | 0.129073E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.155843E+11 | 0.00 | 0.145600E+12 | 0.00 | 0.294056E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.150816E+11 | 0.00 | 0.218017E+12 | 0.00 | 0.419553E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.155843E+11 | 0.00 | 0.666140E+11 | 0.00 | 0.140031E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.150816E+11 | 0.00 | 0.130157E+12 | 0.00 | 0.271161E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.155843E+11 | 0.00 | 0.201906E+12 | 0.00 | 0.428903E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.155843E+11 | 0.00 | 0.256087E+12 | 0.00 | 0.518092E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.150816E+11 | 0.00 | 0.576211E+11 | 0.00 | 0.116954E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.155843E+11 | 0.00 | 0.100545E+12 | 0.00 | 0.199222E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.150816E+11 | 0.00 | 0.135339E+12 | 0.00 | 0.271103E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.155843E+11 | 0.00 | 0.177453E+12 | 0.00 | 0.357101E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.183492E+12 | 0.00 | 0.155177E+13 | 0.00 | 0.315237E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.140761E+11 | 0.00 | 0.288009E+10 | 0.00 | 0.711751E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.155843E+11 | 0.00 | 0.256087E+12 | 0.00 | 0.518092E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER TOP
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.157918E+10 | 0.00 | 0.131585E+09 | 0.00 | 31773263.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.142636E+10 | 0.00 | 0.409548E+10 | 0.00 | 0.898037E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.157918E+10 | 0.00 | 0.125808E+11 | 0.00 | 0.256371E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.152824E+10 | 0.00 | 0.203111E+11 | 0.00 | 0.394114E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.157918E+10 | 0.00 | 0.609056E+10 | 0.00 | 0.128825E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.152824E+10 | 0.00 | 0.127458E+11 | 0.00 | 0.266762E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.157918E+10 | 0.00 | 0.200617E+11 | 0.00 | 0.427596E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.157918E+10 | 0.00 | 0.253953E+11 | 0.00 | 0.515445E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.152824E+10 | 0.00 | 0.496608E+10 | 0.00 | 0.101700E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.157918E+10 | 0.00 | 0.818913E+10 | 0.00 | 0.163710E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.152824E+10 | 0.00 | 0.113392E+11 | 0.00 | 0.229420E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.157918E+10 | 0.00 | 0.157607E+11 | 0.00 | 0.320488E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.185936E+11 | 0.00 | 0.141667E+12 | 0.00 | 0.289741E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.142636E+10 | 0.00 | 0.131585E+09 | 0.00 | 31773263.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.157918E+10 | 0.00 | 0.253953E+11 | 0.00 | 0.515445E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.206411E+11 | 0.00 | 0.00 | 58023107.94 | 0.00 | 0.00 | 0.396449E+11 | 0.00 | 0.33 |
February | 0.514735E+10 | 0.00 | 0.00 | 99532640.31 | 0.00 | 0.00 | 0.548678E+11 | 0.00 | 0.38 |
March | 0.270790E+09 | 0.00 | 0.00 | 0.142193E+09 | 0.00 | 0.00 | 0.746789E+11 | 0.00 | 0.46 |
April | 0.181061E+09 | 0.00 | 0.00 | 0.134525E+09 | 0.00 | 0.00 | 0.739391E+11 | 0.00 | 0.78 |
May | 0.129506E+09 | 10935665.65 | 0.00 | 0.122543E+09 | 0.00 | 0.00 | 0.624174E+11 | 0.00 | 1.19 |
June | 85413515.58 | 0.323644E+10 | 0.00 | 0.101796E+09 | 27660684.09 | 0.00 | 0.427310E+11 | 0.00 | 1.46 |
July | 0.157062E+09 | 0.500656E+10 | 0.00 | 99599761.74 | 79445160.34 | 0.00 | 0.319982E+11 | 0.00 | 1.29 |
August | 68523329.82 | 0.319895E+10 | 0.00 | 0.126062E+09 | 1434254.30 | 0.00 | 0.509122E+11 | 0.00 | 1.61 |
September | 0.198702E+09 | 0.00 | 0.00 | 0.131018E+09 | 0.00 | 0.00 | 0.743322E+11 | 0.00 | 1.28 |
October | 0.255807E+09 | 0.00 | 0.00 | 0.134782E+09 | 0.00 | 0.00 | 0.801509E+11 | 0.00 | 0.81 |
November | 0.191042E+09 | 0.00 | 0.00 | 0.130376E+09 | 0.00 | 0.00 | 0.738629E+11 | 0.00 | 0.58 |
December | 0.877431E+10 | 0.00 | 0.00 | 0.100473E+09 | 0.00 | 0.00 | 0.587050E+11 | 0.00 | 0.34 |
Annual Sum or Average | 0.361007E+11 | 0.114529E+11 | 0.00 | 0.138092E+10 | 0.108540E+09 | 0.00 | 0.718240E+12 | 0.00 | 0.88 |
Minimum of Months | 68523329.82 | 0.00 | 0.00 | 58023107.94 | 0.00 | 0.00 | 0.319982E+11 | 0.00 | 0.33 |
Maximum of Months | 0.206411E+11 | 0.500656E+10 | 0.00 | 0.142193E+09 | 79445160.34 | 0.00 | 0.801509E+11 | 0.00 | 1.61 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.313234E+11 | 0.00 | 0.00 | 26780111.87 | 0.00 | 34149220.94 | 0.225707E+11 | 0.00 | 0.41 |
February | 0.113323E+11 | 0.00 | 0.00 | 55061548.08 | 0.00 | 0.00 | 0.341945E+11 | 0.00 | 0.44 |
March | 0.417984E+10 | 0.00 | 0.00 | 0.100763E+09 | 0.00 | 0.00 | 0.531892E+11 | 0.00 | 0.50 |
April | 0.382528E+10 | 0.00 | 0.00 | 0.114847E+09 | 27001376.37 | 0.00 | 0.588599E+11 | 0.00 | 0.69 |
May | 0.415865E+10 | 0.147217E+09 | 0.00 | 97824323.53 | 0.00 | 0.00 | 0.453761E+11 | 0.00 | 0.88 |
June | 0.263097E+10 | 0.483621E+10 | 0.00 | 83044202.07 | 0.533905E+09 | 0.00 | 0.306852E+11 | 0.00 | 1.09 |
July | 0.530910E+10 | 0.724475E+10 | 0.00 | 66512522.90 | 0.220883E+10 | 0.00 | 0.209013E+11 | 0.00 | 1.08 |
August | 0.854656E+10 | 0.491779E+10 | 0.00 | 86998201.95 | 93426769.11 | 0.00 | 0.339247E+11 | 0.00 | 1.28 |
September | 0.360686E+10 | 0.125690E+09 | 0.00 | 91388554.98 | 464413.21 | 0.00 | 0.503895E+11 | 0.00 | 0.88 |
October | 0.316440E+10 | 0.00 | 0.00 | 92823632.72 | 0.00 | 0.00 | 0.545390E+11 | 0.00 | 0.61 |
November | 0.243951E+10 | 0.00 | 0.00 | 82435968.63 | 0.00 | 0.00 | 0.479778E+11 | 0.00 | 0.51 |
December | 0.993547E+10 | 0.00 | 0.00 | 54471571.84 | 0.00 | 0.00 | 0.417529E+11 | 0.00 | 0.43 |
Annual Sum or Average | 0.904523E+11 | 0.172717E+11 | 0.00 | 0.952950E+09 | 0.286362E+10 | 34149220.94 | 0.494361E+12 | 0.00 | 0.73 |
Minimum of Months | 0.243951E+10 | 0.00 | 0.00 | 26780111.87 | 0.00 | 0.00 | 0.209013E+11 | 0.00 | 0.41 |
Maximum of Months | 0.313234E+11 | 0.724475E+10 | 0.00 | 0.114847E+09 | 0.220883E+10 | 34149220.94 | 0.588599E+11 | 0.00 | 1.28 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.456339E+12 | 0.00 | 0.00 | 3497220.84 | 0.00 | 0.198630E+11 | 0.498582E+10 | 0.00 | 0.40 |
February | 0.312979E+12 | 0.00 | 0.00 | 26725571.12 | 0.00 | 0.559527E+10 | 0.246008E+11 | 0.00 | 0.40 |
March | 0.228128E+12 | 0.00 | 0.00 | 0.187391E+09 | 0.00 | 0.121791E+10 | 0.130776E+12 | 0.00 | 0.44 |
April | 0.109100E+12 | 0.00 | 0.00 | 0.427371E+09 | 0.791918E+09 | 0.00 | 0.276744E+12 | 0.00 | 0.50 |
May | 0.451742E+11 | 0.143550E+10 | 0.00 | 0.691501E+09 | 0.00 | 0.00 | 0.339680E+12 | 0.00 | 0.73 |
June | 0.189753E+11 | 0.400000E+11 | 0.00 | 0.613775E+09 | 0.384246E+10 | 0.00 | 0.234061E+12 | 0.00 | 0.87 |
July | 0.208783E+11 | 0.587550E+11 | 0.00 | 0.512008E+09 | 0.844482E+10 | 0.00 | 0.161206E+12 | 0.00 | 0.80 |
August | 0.262366E+11 | 0.347183E+11 | 0.00 | 0.611126E+09 | 0.488688E+09 | 0.00 | 0.247887E+12 | 0.00 | 0.90 |
September | 0.535221E+11 | 0.119727E+10 | 0.00 | 0.587985E+09 | 0.00 | 0.00 | 0.358737E+12 | 0.00 | 0.71 |
October | 0.122214E+12 | 0.00 | 0.00 | 0.363787E+09 | 0.00 | 0.00 | 0.259575E+12 | 0.00 | 0.48 |
November | 0.191735E+12 | 0.00 | 0.00 | 0.139769E+09 | 0.00 | 0.140344E+10 | 0.112823E+12 | 0.00 | 0.42 |
December | 0.373448E+12 | 0.00 | 0.00 | 8243957.92 | 0.00 | 0.123114E+11 | 0.948924E+10 | 0.00 | 0.40 |
Annual Sum or Average | 0.195873E+13 | 0.136106E+12 | 0.00 | 0.417318E+10 | 0.135679E+11 | 0.403910E+11 | 0.216057E+13 | 0.00 | 0.59 |
Minimum of Months | 0.189753E+11 | 0.00 | 0.00 | 3497220.84 | 0.00 | 0.00 | 0.498582E+10 | 0.00 | 0.40 |
Maximum of Months | 0.456339E+12 | 0.587550E+11 | 0.00 | 0.691501E+09 | 0.844482E+10 | 0.198630E+11 | 0.358737E+12 | 0.00 | 0.90 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.303292E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.100252E+11 | 0.00 | 0.00 | 0.36 |
February | 0.223920E+11 | 0.00 | 0.00 | 153723.63 | 0.00 | 0.517148E+10 | 0.326418E+09 | 0.00 | 0.38 |
March | 0.240193E+11 | 0.00 | 0.00 | 2635277.36 | 0.00 | 0.186428E+10 | 0.264229E+10 | 0.00 | 0.42 |
April | 0.153049E+11 | 0.00 | 0.00 | 18155412.18 | 87790130.81 | 0.395548E+09 | 0.149438E+11 | 0.00 | 0.47 |
May | 0.816866E+10 | 0.142841E+09 | 0.00 | 52887166.61 | 0.00 | 5564460.95 | 0.255883E+11 | 0.00 | 0.70 |
June | 0.349106E+10 | 0.403343E+10 | 0.00 | 51824469.38 | 0.549282E+09 | 0.00 | 0.204825E+11 | 0.00 | 0.87 |
July | 0.296815E+10 | 0.611075E+10 | 0.00 | 43300507.86 | 0.100306E+10 | 0.00 | 0.140618E+11 | 0.00 | 0.80 |
August | 0.394207E+10 | 0.364660E+10 | 0.00 | 49079495.80 | 33130314.52 | 0.00 | 0.206089E+11 | 0.00 | 0.88 |
September | 0.101439E+11 | 97847875.90 | 0.00 | 35809007.30 | 0.00 | 0.00 | 0.237779E+11 | 0.00 | 0.64 |
October | 0.186730E+11 | 0.00 | 0.00 | 10625856.01 | 0.00 | 0.347899E+09 | 0.902586E+10 | 0.00 | 0.44 |
November | 0.193641E+11 | 0.00 | 0.00 | 1729072.56 | 99382.75 | 0.194992E+10 | 0.210894E+10 | 0.00 | 0.40 |
December | 0.228917E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.938643E+10 | 0.00 | 0.00 | 0.37 |
Annual Sum or Average | 0.181688E+12 | 0.140315E+11 | 0.00 | 0.266200E+09 | 0.167336E+10 | 0.291463E+11 | 0.133567E+12 | 0.00 | 0.56 |
Minimum of Months | 0.296815E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.36 |
Maximum of Months | 0.303292E+11 | 0.611075E+10 | 0.00 | 52887166.61 | 0.100306E+10 | 0.100252E+11 | 0.255883E+11 | 0.00 | 0.88 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.876089E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.588145E+10 | 0.00 | 0.00 | 0.39 |
February | 0.207485E+10 | 0.00 | 0.00 | 670.80 | 0.00 | 0.241000E+10 | 17938380.61 | 0.00 | 0.34 |
March | 0.369104E+10 | 0.00 | 0.00 | 581688.08 | 0.00 | 0.627133E+09 | 0.502203E+09 | 0.00 | 0.35 |
April | 0.257226E+10 | 0.00 | 0.00 | 3981832.92 | 3384008.61 | 9738769.04 | 0.284240E+10 | 0.00 | 0.51 |
May | 0.111480E+10 | 28462639.81 | 0.00 | 10436615.36 | 0.00 | 0.00 | 0.485111E+10 | 0.00 | 0.95 |
June | 0.462814E+09 | 0.946048E+09 | 0.00 | 11283578.59 | 63474666.79 | 0.00 | 0.428132E+10 | 0.00 | 1.37 |
July | 0.772454E+09 | 0.132083E+10 | 0.00 | 8954218.86 | 0.274887E+09 | 0.00 | 0.294779E+10 | 0.00 | 1.35 |
August | 0.124741E+10 | 0.813719E+09 | 0.00 | 9455832.30 | 11622221.41 | 0.00 | 0.382442E+10 | 0.00 | 1.38 |
September | 0.162536E+10 | 19803360.07 | 0.00 | 6295843.89 | 58203.64 | 0.00 | 0.396548E+10 | 0.00 | 0.78 |
October | 0.287126E+10 | 0.00 | 0.00 | 2409874.99 | 0.00 | 24127368.70 | 0.190381E+10 | 0.00 | 0.42 |
November | 0.329779E+10 | 0.00 | 0.00 | 390263.25 | 0.00 | 0.325802E+09 | 0.435052E+09 | 0.00 | 0.34 |
December | 0.176402E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.332541E+10 | 0.00 | 0.00 | 0.34 |
Annual Sum or Average | 0.223701E+11 | 0.312886E+10 | 0.00 | 53790419.03 | 0.353426E+09 | 0.126037E+11 | 0.255715E+11 | 0.00 | 0.71 |
Minimum of Months | 0.462814E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.34 |
Maximum of Months | 0.369104E+10 | 0.132083E+10 | 0.00 | 11283578.59 | 0.274887E+09 | 0.588145E+10 | 0.485111E+10 | 0.00 | 1.38 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.219623E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.577553E+10 | 0.00 | 0.00 | 0.73 |
February | 0.315666E+10 | 0.00 | 0.00 | 529656.65 | 0.00 | 0.222786E+10 | 0.271641E+09 | 0.00 | 0.67 |
March | 0.407297E+10 | 0.00 | 0.00 | 3738704.29 | 0.00 | 0.789056E+09 | 0.176736E+10 | 0.00 | 0.74 |
April | 0.313664E+10 | 0.00 | 0.00 | 9165265.17 | 4243384.49 | 29965044.32 | 0.490693E+10 | 0.00 | 1.11 |
May | 0.156277E+10 | 20770217.80 | 0.00 | 12696086.26 | 0.00 | 0.00 | 0.557220E+10 | 0.00 | 1.63 |
June | 0.781277E+09 | 0.782314E+09 | 0.00 | 13015332.71 | 53667601.89 | 0.00 | 0.498651E+10 | 0.00 | 2.23 |
July | 0.115154E+10 | 0.125320E+10 | 0.00 | 9445156.87 | 0.309040E+09 | 0.00 | 0.335111E+10 | 0.00 | 2.29 |
August | 0.211026E+10 | 0.626903E+09 | 0.00 | 10921700.35 | 25144600.77 | 0.00 | 0.337796E+10 | 0.00 | 2.13 |
September | 0.244337E+10 | 17904807.91 | 0.00 | 7810612.87 | 72984.57 | 0.00 | 0.431128E+10 | 0.00 | 1.41 |
October | 0.444242E+10 | 0.00 | 0.00 | 2153678.79 | 0.00 | 32110026.93 | 0.143216E+10 | 0.00 | 0.80 |
November | 0.423021E+10 | 0.00 | 0.00 | 437545.72 | 0.00 | 0.588508E+09 | 0.270061E+09 | 0.00 | 0.66 |
December | 0.228570E+10 | 0.00 | 0.00 | 177.51 | 0.00 | 0.403490E+10 | 1547505.79 | 0.00 | 0.65 |
Annual Sum or Average | 0.315700E+11 | 0.270109E+10 | 0.00 | 69913917.18 | 0.392168E+09 | 0.134779E+11 | 0.302488E+11 | 0.00 | 1.26 |
Minimum of Months | 0.781277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.65 |
Maximum of Months | 0.444242E+10 | 0.125320E+10 | 0.00 | 13015332.71 | 0.309040E+09 | 0.577553E+10 | 0.557220E+10 | 0.00 | 2.29 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.288642E+10 | 0.00 | 0.00 | 4339758.98 | 0.00 | 0.533327E+10 | 0.336228E+10 | 0.00 | 0.68 |
February | 0.253868E+10 | 0.00 | 0.00 | 10408966.58 | 0.00 | 0.238431E+10 | 0.506848E+10 | 0.00 | 0.74 |
March | 0.390024E+10 | 0.00 | 0.00 | 14974758.15 | 0.00 | 0.821400E+09 | 0.667279E+10 | 0.00 | 0.77 |
April | 0.336777E+10 | 13465764.68 | 0.00 | 14575506.52 | 145591.09 | 0.135341E+09 | 0.879930E+10 | 0.00 | 1.21 |
May | 0.208543E+10 | 38238047.29 | 0.00 | 15929929.34 | 0.00 | 0.00 | 0.686274E+10 | 0.00 | 1.44 |
June | 0.123430E+10 | 0.111206E+10 | 0.00 | 12498638.13 | 91860243.24 | 0.00 | 0.440304E+10 | 0.00 | 1.71 |
July | 0.142260E+10 | 0.173526E+10 | 0.00 | 11373499.80 | 0.416817E+09 | 0.00 | 0.327241E+10 | 0.00 | 1.78 |
August | 0.229697E+10 | 0.123805E+10 | 0.00 | 18460118.35 | 15306432.81 | 0.00 | 0.476973E+10 | 0.00 | 2.06 |
September | 0.252409E+10 | 62062755.81 | 0.00 | 18703530.17 | 89050.28 | 0.00 | 0.811147E+10 | 0.00 | 1.61 |
October | 0.420556E+10 | 0.00 | 0.00 | 13727066.05 | 0.00 | 65258876.14 | 0.575393E+10 | 0.00 | 0.98 |
November | 0.401304E+10 | 0.00 | 0.00 | 6242735.36 | 0.00 | 0.689280E+09 | 0.368832E+10 | 0.00 | 0.65 |
December | 0.316313E+10 | 0.00 | 0.00 | 3389314.47 | 0.00 | 0.369840E+10 | 0.191559E+10 | 0.00 | 0.58 |
Annual Sum or Average | 0.336382E+11 | 0.419913E+10 | 0.00 | 0.144624E+09 | 0.524218E+09 | 0.131272E+11 | 0.626801E+11 | 0.00 | 1.19 |
Minimum of Months | 0.123430E+10 | 0.00 | 0.00 | 3389314.47 | 0.00 | 0.00 | 0.191559E+10 | 0.00 | 0.58 |
Maximum of Months | 0.420556E+10 | 0.173526E+10 | 0.00 | 18703530.17 | 0.416817E+09 | 0.533327E+10 | 0.879930E+10 | 0.00 | 2.06 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.333786E+10 | 0.00 | 0.00 | 275818.90 | 0.00 | 0.593975E+10 | 0.263256E+09 | 0.00 | 0.88 |
February | 0.430333E+10 | 0.00 | 0.00 | 1918425.22 | 0.00 | 0.145067E+10 | 0.134615E+10 | 0.00 | 0.84 |
March | 0.447569E+10 | 0.00 | 0.00 | 7836145.97 | 0.00 | 78805761.52 | 0.425196E+10 | 0.00 | 0.98 |
April | 0.158685E+10 | 5602127.37 | 0.00 | 15455599.59 | 1948922.27 | 0.00 | 0.924709E+10 | 0.00 | 1.63 |
May | 0.130512E+10 | 33694860.51 | 0.00 | 17891532.45 | 0.00 | 0.00 | 0.688472E+10 | 0.00 | 2.05 |
June | 0.520500E+09 | 0.110128E+10 | 0.00 | 15629718.54 | 67786487.54 | 0.00 | 0.514092E+10 | 0.00 | 2.65 |
July | 0.819915E+09 | 0.186682E+10 | 0.00 | 17810201.88 | 0.293187E+09 | 0.00 | 0.406185E+10 | 0.00 | 2.83 |
August | 0.130185E+10 | 0.112018E+10 | 0.00 | 22479912.91 | 8440589.64 | 0.00 | 0.610567E+10 | 0.00 | 3.15 |
September | 0.202643E+10 | 23869022.50 | 0.00 | 10554624.66 | 87317.56 | 0.00 | 0.577128E+10 | 0.00 | 1.74 |
October | 0.327638E+10 | 0.00 | 0.00 | 5865408.52 | 0.00 | 295620.43 | 0.440445E+10 | 0.00 | 1.09 |
November | 0.391713E+10 | 0.00 | 0.00 | 2396314.39 | 0.00 | 36841157.25 | 0.238024E+10 | 0.00 | 0.82 |
December | 0.617155E+10 | 0.00 | 0.00 | 315224.28 | 0.00 | 0.952008E+09 | 0.444760E+09 | 0.00 | 0.78 |
Annual Sum or Average | 0.330426E+11 | 0.415145E+10 | 0.00 | 0.118429E+09 | 0.371451E+09 | 0.845837E+10 | 0.503023E+11 | 0.00 | 1.63 |
Minimum of Months | 0.520500E+09 | 0.00 | 0.00 | 275818.90 | 0.00 | 0.00 | 0.263256E+09 | 0.00 | 0.78 |
Maximum of Months | 0.617155E+10 | 0.186682E+10 | 0.00 | 22479912.91 | 0.293187E+09 | 0.593975E+10 | 0.924709E+10 | 0.00 | 3.15 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.731137E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.878234E+11 | 0.00 | 0.00 | 0.52 |
February | 0.345086E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.501246E+11 | 0.00 | 0.00 | 0.45 |
March | 0.165103E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.290818E+11 | 0.00 | 0.00 | 0.43 |
April | 0.286760E+11 | 0.00 | 0.00 | 6108603.48 | 99590144.09 | 0.687477E+10 | 0.483085E+10 | 0.00 | 0.43 |
May | 0.159624E+11 | 0.289419E+09 | 0.00 | 70369224.64 | 0.00 | 0.120793E+09 | 0.294072E+11 | 0.00 | 0.77 |
June | 0.521404E+10 | 0.835810E+10 | 0.00 | 83121485.48 | 0.482110E+09 | 0.00 | 0.305675E+11 | 0.00 | 1.12 |
July | 0.472669E+10 | 0.114179E+11 | 0.00 | 66624683.34 | 0.104787E+10 | 0.00 | 0.216910E+11 | 0.00 | 1.05 |
August | 0.977466E+10 | 0.593863E+10 | 0.00 | 54942739.96 | 68764542.73 | 0.00 | 0.219679E+11 | 0.00 | 0.96 |
September | 0.234782E+11 | 0.189215E+09 | 0.00 | 29601968.47 | 0.00 | 11395814.62 | 0.182169E+11 | 0.00 | 0.60 |
October | 0.338761E+11 | 0.00 | 0.00 | 1284133.02 | 0.00 | 0.586547E+10 | 0.102594E+10 | 0.00 | 0.42 |
November | 0.142093E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.243766E+11 | 0.00 | 0.00 | 0.42 |
December | 0.586504E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.673035E+11 | 0.00 | 0.00 | 0.49 |
Annual Sum or Average | 0.157196E+12 | 0.261932E+11 | 0.00 | 0.312053E+09 | 0.169833E+10 | 0.271582E+12 | 0.127707E+12 | 0.00 | 0.64 |
Minimum of Months | 0.586504E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.42 |
Maximum of Months | 0.338761E+11 | 0.114179E+11 | 0.00 | 83121485.48 | 0.104787E+10 | 0.878234E+11 | 0.305675E+11 | 0.00 | 1.12 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.485530E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.796325E+11 | 0.00 | 0.00 | 0.85 |
February | 0.139079E+11 | 0.00 | 0.00 | 16180.38 | 0.00 | 0.455600E+11 | 43798035.46 | 0.00 | 0.85 |
March | 0.270938E+11 | 0.00 | 0.00 | 16560920.07 | 0.00 | 0.273344E+11 | 0.684758E+10 | 0.00 | 0.92 |
April | 0.285987E+11 | 0.00 | 0.00 | 66566054.14 | 0.135660E+09 | 0.612263E+10 | 0.353901E+11 | 0.00 | 1.14 |
May | 0.201636E+11 | 0.225454E+09 | 0.00 | 0.111937E+09 | 0.00 | 25370692.84 | 0.458627E+11 | 0.00 | 1.61 |
June | 0.773755E+10 | 0.771554E+10 | 0.00 | 0.126989E+09 | 0.477815E+09 | 0.00 | 0.470537E+11 | 0.00 | 2.20 |
July | 0.696054E+10 | 0.123839E+11 | 0.00 | 95961004.82 | 0.118375E+10 | 0.00 | 0.333545E+11 | 0.00 | 2.15 |
August | 0.171292E+11 | 0.551005E+10 | 0.00 | 0.103874E+09 | 0.399900E+09 | 0.00 | 0.275086E+11 | 0.00 | 1.91 |
September | 0.340663E+11 | 0.208511E+09 | 0.00 | 58399274.26 | 0.00 | 0.201784E+09 | 0.291242E+11 | 0.00 | 1.38 |
October | 0.434626E+11 | 0.00 | 0.00 | 9359226.07 | 0.00 | 0.788073E+10 | 0.568465E+10 | 0.00 | 0.90 |
November | 0.226066E+11 | 0.00 | 0.00 | 120385.80 | 0.00 | 0.276063E+11 | 0.224448E+09 | 0.00 | 0.85 |
December | 0.326903E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.660442E+11 | 0.00 | 0.00 | 0.85 |
Annual Sum or Average | 0.229851E+12 | 0.260434E+11 | 0.00 | 0.589782E+09 | 0.219712E+10 | 0.260408E+12 | 0.231094E+12 | 0.00 | 1.30 |
Minimum of Months | 0.326903E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.85 |
Maximum of Months | 0.434626E+11 | 0.123839E+11 | 0.00 | 0.126989E+09 | 0.118375E+10 | 0.796325E+11 | 0.470537E+11 | 0.00 | 2.20 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.223783E+11 | 0.00 | 0.00 | 35573403.76 | 0.00 | 0.677104E+11 | 0.249098E+11 | 0.00 | 0.75 |
February | 0.198676E+11 | 0.00 | 0.00 | 84289098.46 | 0.00 | 0.381704E+11 | 0.345271E+11 | 0.00 | 0.88 |
March | 0.256035E+11 | 0.00 | 0.00 | 0.138667E+09 | 0.00 | 0.241806E+11 | 0.523709E+11 | 0.00 | 0.93 |
April | 0.298200E+11 | 0.384477E+09 | 0.00 | 0.122509E+09 | 0.00 | 0.677933E+10 | 0.722543E+11 | 0.00 | 1.20 |
May | 0.239826E+11 | 0.415122E+09 | 0.00 | 0.148332E+09 | 0.00 | 0.187706E+09 | 0.570010E+11 | 0.00 | 1.39 |
June | 0.148054E+11 | 0.105107E+11 | 0.00 | 0.108548E+09 | 0.699274E+09 | 0.00 | 0.350268E+11 | 0.00 | 1.59 |
July | 0.113564E+11 | 0.164338E+11 | 0.00 | 0.102443E+09 | 0.163199E+10 | 0.00 | 0.267151E+11 | 0.00 | 1.54 |
August | 0.174595E+11 | 0.106822E+11 | 0.00 | 0.151769E+09 | 84564851.77 | 0.00 | 0.361382E+11 | 0.00 | 1.76 |
September | 0.294676E+11 | 0.695656E+09 | 0.00 | 0.184641E+09 | 0.00 | 17835767.42 | 0.700212E+11 | 0.00 | 1.59 |
October | 0.401089E+11 | 0.00 | 0.00 | 0.138671E+09 | 0.00 | 0.693293E+10 | 0.467368E+11 | 0.00 | 1.05 |
November | 0.276617E+11 | 0.00 | 0.00 | 47750535.62 | 0.00 | 0.229207E+11 | 0.255087E+11 | 0.00 | 0.79 |
December | 0.145991E+11 | 0.00 | 0.00 | 20650578.70 | 0.00 | 0.629510E+11 | 0.102528E+11 | 0.00 | 0.70 |
Annual Sum or Average | 0.277111E+12 | 0.391220E+11 | 0.00 | 0.128384E+10 | 0.241583E+10 | 0.229851E+12 | 0.491463E+12 | 0.00 | 1.18 |
Minimum of Months | 0.113564E+11 | 0.00 | 0.00 | 20650578.70 | 0.00 | 0.00 | 0.102528E+11 | 0.00 | 0.70 |
Maximum of Months | 0.401089E+11 | 0.164338E+11 | 0.00 | 0.184641E+09 | 0.163199E+10 | 0.677104E+11 | 0.722543E+11 | 0.00 | 1.76 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.767099E+10 | 0.00 | 0.00 | 23083.69 | 0.00 | 0.810638E+11 | 67163380.36 | 0.00 | 0.89 |
February | 0.152574E+11 | 0.00 | 0.00 | 3733659.87 | 0.00 | 0.458787E+11 | 0.222596E+10 | 0.00 | 0.91 |
March | 0.296590E+11 | 0.00 | 0.00 | 24506529.36 | 0.00 | 0.262744E+11 | 0.121283E+11 | 0.00 | 1.01 |
April | 0.362640E+11 | 0.00 | 0.00 | 51681618.07 | 0.144025E+09 | 0.562809E+10 | 0.318589E+11 | 0.00 | 1.25 |
May | 0.230157E+11 | 0.348120E+09 | 0.00 | 0.137881E+09 | 0.00 | 48891871.52 | 0.429183E+11 | 0.00 | 1.75 |
June | 0.127658E+11 | 0.856876E+10 | 0.00 | 98710252.50 | 0.594201E+09 | 0.00 | 0.291408E+11 | 0.00 | 2.08 |
July | 0.824648E+10 | 0.136396E+11 | 0.00 | 0.107206E+09 | 0.115984E+10 | 0.00 | 0.230970E+11 | 0.00 | 1.98 |
August | 0.168709E+11 | 0.707652E+10 | 0.00 | 93682824.73 | 36616676.96 | 0.00 | 0.245763E+11 | 0.00 | 1.94 |
September | 0.368293E+11 | 0.229446E+09 | 0.00 | 56237819.78 | 0.00 | 20175853.95 | 0.269871E+11 | 0.00 | 1.46 |
October | 0.461957E+11 | 0.00 | 0.00 | 14932274.76 | 0.00 | 0.650318E+10 | 0.962124E+10 | 0.00 | 1.01 |
November | 0.271116E+11 | 0.00 | 0.00 | 1073943.19 | 0.00 | 0.251186E+11 | 0.123690E+10 | 0.00 | 0.91 |
December | 0.700105E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.657341E+11 | 0.00 | 0.00 | 0.90 |
Annual Sum or Average | 0.266888E+12 | 0.298625E+11 | 0.00 | 0.589669E+09 | 0.193468E+10 | 0.256270E+12 | 0.203858E+12 | 0.00 | 1.34 |
Minimum of Months | 0.700105E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.89 |
Maximum of Months | 0.461957E+11 | 0.136396E+11 | 0.00 | 0.137881E+09 | 0.115984E+10 | 0.810638E+11 | 0.429183E+11 | 0.00 | 2.08 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 33913415.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.919029E+10 | 0.00 | 0.00 | 0.59 |
February | 0.248421E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.510219E+10 | 0.00 | 0.00 | 0.51 |
March | 0.100898E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.335104E+10 | 0.00 | 0.00 | 0.49 |
April | 0.236560E+10 | 0.00 | 0.00 | 398627.73 | 12215961.78 | 0.124897E+10 | 0.342543E+09 | 0.00 | 0.48 |
May | 0.193688E+10 | 28047683.35 | 0.00 | 6116443.50 | 0.00 | 0.104647E+09 | 0.237302E+10 | 0.00 | 0.79 |
June | 0.733775E+09 | 0.829924E+09 | 0.00 | 7522475.27 | 69008576.27 | 0.00 | 0.280193E+10 | 0.00 | 1.13 |
July | 0.560401E+09 | 0.120684E+10 | 0.00 | 6070538.32 | 0.135846E+09 | 0.00 | 0.202683E+10 | 0.00 | 1.08 |
August | 0.127486E+10 | 0.617008E+09 | 0.00 | 4689117.84 | 6768117.21 | 5456036.05 | 0.183347E+10 | 0.00 | 0.98 |
September | 0.269609E+10 | 15262886.85 | 0.00 | 1781470.02 | 0.00 | 0.233618E+09 | 0.115692E+10 | 0.00 | 0.62 |
October | 0.240980E+10 | 0.00 | 0.00 | 38349.35 | 0.00 | 0.136228E+10 | 35364518.67 | 0.00 | 0.48 |
November | 0.745863E+09 | 0.00 | 0.00 | 0.00 | 846.97 | 0.278331E+10 | 0.00 | 28314.41 | 0.47 |
December | 47032102.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.677561E+10 | 0.00 | 0.00 | 0.55 |
Annual Sum or Average | 0.140616E+11 | 0.269708E+10 | 0.00 | 26617022.04 | 0.223839E+09 | 0.301574E+11 | 0.105701E+11 | 28314.41 | 0.68 |
Minimum of Months | 33913415.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.47 |
Maximum of Months | 0.269609E+10 | 0.120684E+10 | 0.00 | 7522475.27 | 0.135846E+09 | 0.919029E+10 | 0.280193E+10 | 28314.41 | 1.13 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.132067E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.692613E+10 | 0.00 | 0.00 | 0.77 |
February | 0.785132E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.399229E+10 | 0.00 | 0.00 | 0.78 |
March | 0.188196E+10 | 0.00 | 0.00 | 840135.54 | 0.00 | 0.261794E+10 | 0.337732E+09 | 0.00 | 0.87 |
April | 0.214374E+10 | 0.00 | 0.00 | 5279353.03 | 14642053.30 | 0.881255E+09 | 0.279818E+10 | 0.00 | 1.10 |
May | 0.200278E+10 | 21933359.37 | 0.00 | 9831437.61 | 0.00 | 61108596.41 | 0.399909E+10 | 0.00 | 1.60 |
June | 0.693178E+09 | 0.783787E+09 | 0.00 | 11955167.18 | 65177455.21 | 0.00 | 0.459283E+10 | 0.00 | 2.21 |
July | 0.601862E+09 | 0.127260E+10 | 0.00 | 9473965.92 | 0.155562E+09 | 0.00 | 0.330620E+10 | 0.00 | 2.20 |
August | 0.155449E+10 | 0.560923E+09 | 0.00 | 9766127.82 | 39221333.39 | 4853864.48 | 0.265573E+10 | 0.00 | 1.91 |
September | 0.298343E+10 | 15260666.98 | 0.00 | 4765016.95 | 0.00 | 0.206379E+09 | 0.250836E+10 | 0.00 | 1.33 |
October | 0.286248E+10 | 0.00 | 0.00 | 696926.72 | 0.00 | 0.134115E+10 | 0.414821E+09 | 0.00 | 0.90 |
November | 0.136181E+10 | 0.00 | 0.00 | 0.00 | 3240.08 | 0.257557E+10 | 0.00 | 23751.69 | 0.82 |
December | 0.128062E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.547886E+10 | 0.00 | 0.00 | 0.77 |
Annual Sum or Average | 0.171310E+11 | 0.265451E+10 | 0.00 | 52608130.76 | 0.274606E+09 | 0.240855E+11 | 0.206129E+11 | 23751.69 | 1.27 |
Minimum of Months | 0.128062E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.77 |
Maximum of Months | 0.298343E+10 | 0.127260E+10 | 0.00 | 11955167.18 | 0.155562E+09 | 0.692613E+10 | 0.459283E+10 | 23751.69 | 2.21 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.180628E+10 | 0.00 | 0.00 | 2512380.54 | 0.00 | 0.626393E+10 | 0.165809E+10 | 0.00 | 0.69 |
February | 0.139983E+10 | 0.00 | 0.00 | 6630130.85 | 0.00 | 0.355309E+10 | 0.279550E+10 | 0.00 | 0.80 |
March | 0.177790E+10 | 0.00 | 0.00 | 9259681.13 | 0.00 | 0.257106E+10 | 0.396724E+10 | 0.00 | 0.88 |
April | 0.214245E+10 | 37159931.69 | 0.00 | 10279446.30 | 919332.74 | 0.106073E+10 | 0.666157E+10 | 0.00 | 1.19 |
May | 0.236130E+10 | 38160912.27 | 0.00 | 13493268.51 | 0.00 | 0.141402E+09 | 0.533483E+10 | 0.00 | 1.40 |
June | 0.147927E+10 | 0.103739E+10 | 0.00 | 10371798.48 | 0.100692E+09 | 0.00 | 0.363870E+10 | 0.00 | 1.61 |
July | 0.107172E+10 | 0.166166E+10 | 0.00 | 10066828.68 | 0.228723E+09 | 0.00 | 0.281920E+10 | 0.00 | 1.60 |
August | 0.189735E+10 | 0.110721E+10 | 0.00 | 16165929.99 | 10335117.88 | 15307080.63 | 0.346415E+10 | 0.00 | 1.81 |
September | 0.294232E+10 | 54489203.63 | 0.00 | 15819504.11 | 0.00 | 0.233218E+09 | 0.625665E+10 | 0.00 | 1.55 |
October | 0.299531E+10 | 0.00 | 0.00 | 10983647.79 | 0.00 | 0.122520E+10 | 0.389434E+10 | 0.00 | 1.05 |
November | 0.186275E+10 | 0.00 | 0.00 | 3741898.29 | 5250.99 | 0.234493E+10 | 0.186629E+10 | 33169.19 | 0.77 |
December | 0.956735E+09 | 0.00 | 0.00 | 1189975.49 | 0.00 | 0.580417E+10 | 0.605306E+09 | 0.00 | 0.65 |
Annual Sum or Average | 0.226932E+11 | 0.393607E+10 | 0.00 | 0.110514E+09 | 0.340675E+09 | 0.232130E+11 | 0.429619E+11 | 33169.19 | 1.17 |
Minimum of Months | 0.956735E+09 | 0.00 | 0.00 | 1189975.49 | 0.00 | 0.00 | 0.605306E+09 | 0.00 | 0.65 |
Maximum of Months | 0.299531E+10 | 0.166166E+10 | 0.00 | 16165929.99 | 0.228723E+09 | 0.626393E+10 | 0.666157E+10 | 33169.19 | 1.81 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.457824E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.719686E+10 | 0.00 | 0.00 | 0.84 |
February | 0.102698E+10 | 0.00 | 0.00 | 327292.71 | 0.00 | 0.403169E+10 | 0.205913E+09 | 0.00 | 0.87 |
March | 0.193312E+10 | 0.00 | 0.00 | 1750372.85 | 0.00 | 0.271885E+10 | 0.102844E+10 | 0.00 | 1.00 |
April | 0.278962E+10 | 1978169.02 | 0.00 | 4775738.60 | 14942240.71 | 0.875019E+09 | 0.308556E+10 | 0.00 | 1.27 |
May | 0.232991E+10 | 31312452.07 | 0.00 | 13123166.60 | 0.00 | 85908507.50 | 0.405133E+10 | 0.00 | 1.77 |
June | 0.125046E+10 | 0.845404E+09 | 0.00 | 9582665.13 | 79490480.16 | 0.00 | 0.301387E+10 | 0.00 | 2.12 |
July | 0.836383E+09 | 0.139123E+10 | 0.00 | 10291685.68 | 0.152873E+09 | 0.00 | 0.229987E+10 | 0.00 | 2.03 |
August | 0.180150E+10 | 0.749821E+09 | 0.00 | 9554878.73 | 15467376.35 | 2777873.09 | 0.230360E+10 | 0.00 | 2.00 |
September | 0.363519E+10 | 19300596.02 | 0.00 | 4997763.25 | 0.00 | 0.166022E+09 | 0.229516E+10 | 0.00 | 1.47 |
October | 0.341501E+10 | 0.00 | 0.00 | 1265258.71 | 0.00 | 0.107077E+10 | 0.817245E+09 | 0.00 | 1.04 |
November | 0.170056E+10 | 0.00 | 0.00 | 43796.42 | 9651.11 | 0.253719E+10 | 81540151.15 | 19459.71 | 0.90 |
December | 0.334593E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.569707E+10 | 0.00 | 0.00 | 0.84 |
Annual Sum or Average | 0.215111E+11 | 0.303905E+10 | 0.00 | 55712618.70 | 0.262782E+09 | 0.243822E+11 | 0.191825E+11 | 19459.71 | 1.35 |
Minimum of Months | 0.334593E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.84 |
Maximum of Months | 0.363519E+10 | 0.139123E+10 | 0.00 | 13123166.60 | 0.152873E+09 | 0.719686E+10 | 0.405133E+10 | 19459.71 | 2.12 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 53999452.22 | 0.00 | 0.00 | 2206410.27 | 0.00 | 0.00 | 0.107838E+10 | 0.00 | 0.28 |
February | 0.00 | 0.00 | 0.00 | 8318159.14 | 0.00 | 0.00 | 0.889304E+09 | 0.00 | 0.28 |
March | 0.00 | 0.00 | 0.00 | 17028685.08 | 0.00 | 0.00 | 0.888682E+09 | 0.00 | 0.30 |
April | 0.00 | 0.00 | 0.00 | 20311257.90 | 0.00 | 0.00 | 0.564678E+09 | 0.00 | 0.29 |
May | 0.00 | 4271443.96 | 0.00 | 4135372.97 | 0.00 | 0.00 | 0.328812E+09 | 0.00 | 0.29 |
June | 0.00 | 82541490.96 | 0.00 | 5567696.32 | 0.00 | 0.00 | 0.148145E+09 | 0.00 | 0.31 |
July | 0.00 | 0.115168E+09 | 0.00 | 5385895.20 | 0.00 | 0.00 | 57973056.80 | 0.00 | 0.28 |
August | 0.00 | 75553292.98 | 0.00 | 10148799.86 | 0.00 | 0.00 | 84472271.17 | 0.00 | 0.31 |
September | 0.00 | 1117538.14 | 0.00 | 3919148.28 | 0.00 | 0.00 | 0.351889E+09 | 0.00 | 0.29 |
October | 0.00 | 0.00 | 0.00 | 8635489.22 | 0.00 | 0.00 | 0.563718E+09 | 0.00 | 0.28 |
November | 0.00 | 0.00 | 0.00 | 12767499.64 | 0.00 | 0.00 | 0.695104E+09 | 0.00 | 0.28 |
December | 0.00 | 0.00 | 0.00 | 17575035.37 | 0.00 | 0.00 | 0.102159E+10 | 0.00 | 0.28 |
Annual Sum or Average | 53999452.22 | 0.278652E+09 | 0.00 | 0.115999E+09 | 0.00 | 0.00 | 0.667275E+10 | 0.00 | 0.29 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 2206410.27 | 0.00 | 0.00 | 57973056.80 | 0.00 | 0.28 |
Maximum of Months | 53999452.22 | 0.115168E+09 | 0.00 | 20311257.90 | 0.00 | 0.00 | 0.107838E+10 | 0.00 | 0.31 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.676891E+10 | 0.00 | 0.00 | 5983835.89 | 0.00 | 0.00 | 0.434430E+10 | 0.00 | 0.28 |
February | 0.00 | 0.00 | 0.00 | 60678103.45 | 0.00 | 0.00 | 0.891515E+10 | 0.00 | 0.28 |
March | 0.00 | 0.00 | 0.00 | 0.143820E+09 | 0.00 | 0.00 | 0.891285E+10 | 0.00 | 0.30 |
April | 0.00 | 0.00 | 0.00 | 0.182948E+09 | 0.00 | 0.00 | 0.566608E+10 | 0.00 | 0.29 |
May | 0.00 | 41769281.87 | 0.00 | 35694896.86 | 0.00 | 0.00 | 0.329633E+10 | 0.00 | 0.29 |
June | 0.00 | 0.819101E+09 | 0.00 | 51848093.79 | 0.00 | 0.00 | 0.148630E+10 | 0.00 | 0.31 |
July | 0.00 | 0.114732E+10 | 0.00 | 50834756.89 | 0.00 | 0.00 | 0.583062E+09 | 0.00 | 0.28 |
August | 0.00 | 0.752822E+09 | 0.00 | 95545535.32 | 0.00 | 0.00 | 0.850836E+09 | 0.00 | 0.31 |
September | 0.00 | 9540689.21 | 0.00 | 31688594.18 | 0.00 | 0.00 | 0.353649E+10 | 0.00 | 0.29 |
October | 0.00 | 0.00 | 0.00 | 71039084.45 | 0.00 | 0.00 | 0.565186E+10 | 0.00 | 0.28 |
November | 0.00 | 0.00 | 0.00 | 0.105101E+09 | 0.00 | 0.00 | 0.697232E+10 | 0.00 | 0.28 |
December | 0.00 | 0.00 | 0.00 | 0.146327E+09 | 0.00 | 0.00 | 0.102445E+11 | 0.00 | 0.28 |
Annual Sum or Average | 0.676891E+10 | 0.277055E+10 | 0.00 | 0.981509E+09 | 0.00 | 0.00 | 0.604601E+11 | 0.00 | 0.29 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 5983835.89 | 0.00 | 0.00 | 0.583062E+09 | 0.00 | 0.28 |
Maximum of Months | 0.676891E+10 | 0.114732E+10 | 0.00 | 0.182948E+09 | 0.00 | 0.00 | 0.102445E+11 | 0.00 | 0.31 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.880421E+09 | 0.00 | 0.00 | 321537.92 | 0.00 | 0.00 | 0.209818E+09 | 0.00 | 0.28 |
February | 404024.49 | 0.00 | 0.00 | 5111040.76 | 0.00 | 0.00 | 0.892005E+09 | 0.00 | 0.28 |
March | 0.00 | 0.00 | 0.00 | 13149087.24 | 0.00 | 0.00 | 0.892534E+09 | 0.00 | 0.30 |
April | 0.00 | 0.00 | 0.00 | 17434041.57 | 0.00 | 0.00 | 0.567496E+09 | 0.00 | 0.29 |
May | 3166147.19 | 4206161.67 | 0.00 | 3275897.91 | 0.00 | 0.00 | 0.326768E+09 | 0.00 | 0.29 |
June | 0.00 | 81823822.23 | 0.00 | 5111162.16 | 0.00 | 0.00 | 0.148902E+09 | 0.00 | 0.31 |
July | 0.00 | 0.114672E+09 | 0.00 | 5032527.70 | 0.00 | 0.00 | 58478449.52 | 0.00 | 0.28 |
August | 0.00 | 75171069.38 | 0.00 | 9444399.73 | 0.00 | 0.00 | 85379946.61 | 0.00 | 0.31 |
September | 0.00 | 950371.18 | 0.00 | 2715052.66 | 0.00 | 0.00 | 0.354929E+09 | 0.00 | 0.29 |
October | 0.00 | 0.00 | 0.00 | 6190742.48 | 0.00 | 0.00 | 0.566191E+09 | 0.00 | 0.28 |
November | 0.00 | 0.00 | 0.00 | 9572681.17 | 0.00 | 0.00 | 0.698280E+09 | 0.00 | 0.28 |
December | 0.00 | 0.00 | 0.00 | 13727760.97 | 0.00 | 0.00 | 0.102538E+10 | 0.00 | 0.28 |
Annual Sum or Average | 0.883991E+09 | 0.276823E+09 | 0.00 | 91085932.28 | 0.00 | 0.00 | 0.582616E+10 | 0.00 | 0.29 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 321537.92 | 0.00 | 0.00 | 58478449.52 | 0.00 | 0.28 |
Maximum of Months | 0.880421E+09 | 0.114672E+09 | 0.00 | 17434041.57 | 0.00 | 0.00 | 0.102538E+10 | 0.00 | 0.31 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.100068E+10 | 0.00 | 0.00 | 0.445491E+12 | 0.00 | 4.93 |
February | 0.00 | 0.00 | 0.00 | 0.164504E+10 | 0.00 | 0.00 | 0.716923E+12 | 0.00 | 9.95 |
March | 0.00 | 0.00 | 0.00 | 0.227813E+10 | 0.00 | 0.00 | 0.107798E+13 | 0.00 | 16.33 |
April | 0.00 | 0.00 | 0.00 | 0.254057E+10 | 0.00 | 0.00 | 0.123226E+13 | 0.00 | 29.94 |
May | 0.00 | 0.172007E+09 | 0.00 | 0.586388E+09 | 0.00 | 0.00 | 0.414509E+12 | 0.00 | 18.65 |
June | 0.00 | 0.187272E+11 | 0.00 | 0.103110E+10 | 0.00 | 0.00 | 0.454545E+12 | 0.00 | 32.97 |
July | 0.00 | 0.688844E+11 | 0.00 | 0.163196E+10 | 0.00 | 0.00 | 0.351991E+12 | 0.00 | 39.70 |
August | 0.00 | 0.177479E+11 | 0.00 | 0.270118E+10 | 0.00 | 0.00 | 0.401153E+12 | 0.00 | 43.21 |
September | 0.00 | 0.00 | 0.00 | 0.573695E+09 | 0.00 | 0.00 | 0.368680E+12 | 0.00 | 16.55 |
October | 0.00 | 0.00 | 0.00 | 0.114290E+10 | 0.00 | 0.00 | 0.741943E+12 | 0.00 | 18.05 |
November | 0.00 | 0.00 | 0.00 | 0.199298E+10 | 0.00 | 0.00 | 0.102758E+13 | 0.00 | 18.95 |
December | 0.00 | 0.00 | 0.00 | 0.424690E+10 | 0.00 | 0.00 | 0.131985E+13 | 0.00 | 16.61 |
Annual Sum or Average | 0.00 | 0.105532E+12 | 0.00 | 0.213715E+11 | 0.00 | 0.00 | 0.855290E+13 | 0.00 | 22.23 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.573695E+09 | 0.00 | 0.00 | 0.351991E+12 | 0.00 | 4.93 |
Maximum of Months | 0.00 | 0.688844E+11 | 0.00 | 0.424690E+10 | 0.00 | 0.00 | 0.131985E+13 | 0.00 | 43.21 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 08:43:41
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.292042E+12 | 0.506143E+11 | 0.00 | 0.284466E+13 | 0.337787E+12 |
February | 0.400578E+12 | 0.445106E+11 | 0.00 | 0.286225E+13 | 0.286382E+12 |
March | 0.566029E+12 | 0.314957E+11 | 0.00 | 0.356071E+13 | 0.332837E+12 |
April | 0.696762E+12 | 0.286275E+11 | 0.00 | 0.351571E+13 | 0.469286E+12 |
May | 0.798748E+12 | 0.143187E+11 | 0.00 | 0.268283E+13 | 0.718369E+12 |
June | 0.810906E+12 | 0.549849E+10 | 0.00 | 0.188424E+13 | 0.170298E+13 |
July | 0.834184E+12 | 0.265747E+10 | 0.00 | 0.136506E+13 | 0.268095E+13 |
August | 0.696998E+12 | 0.690420E+10 | 0.00 | 0.200114E+13 | 0.254337E+13 |
September | 0.510982E+12 | 0.133659E+11 | 0.00 | 0.264472E+13 | 0.393268E+12 |
October | 0.305700E+12 | 0.204794E+11 | 0.00 | 0.314205E+13 | 0.249259E+12 |
November | 0.169747E+12 | 0.354906E+11 | 0.00 | 0.315146E+13 | 0.316583E+12 |
December | 0.218814E+12 | 0.545613E+11 | 0.00 | 0.367298E+13 | 0.523560E+12 |
Annual Sum or Average | 0.630149E+13 | 0.308524E+12 | 0.00 | 0.333278E+14 | 0.105546E+14 |
Minimum of Months | 0.169747E+12 | 0.265747E+10 | 0.00 | 0.136506E+13 | 0.249259E+12 |
Maximum of Months | 0.834184E+12 | 0.545613E+11 | 0.00 | 0.367298E+13 | 0.268095E+13 |