Table of Contents

Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:43

Tabular Output Report in Format: HTML

Building: OfficeLarge

Environment: RUNPERIOD 1 ** Buffalo Niagara Intl AP NY USA TMY3 WMO#=725280

Simulation Timestamp: 2023-10-16 08:43:24


Table of Contents

Report: Annual Building Utility Performance Summary

For: Entire Facility

Timestamp: 2023-10-16 08:43:24

Values gathered over 8760.00 hours



Site and Source Energy

Total Energy [GJ] Energy Per Total Building Area [MJ/m2] Energy Per Conditioned Building Area [MJ/m2]
Total Site Energy 30784.56 664.60 664.60
Net Site Energy 30784.56 664.60 664.60
Total Source Energy 91361.48 1972.38 1972.38
Net Source Energy 91361.48 1972.38 1972.38


Site to Source Energy Conversion Factors

Site=>Source Conversion Factor
Electricity 3.167
Natural Gas 1.084
District Cooling 1.056
District Heating 3.613
Steam 1.200
Gasoline 1.050
Diesel 1.050
Coal 1.050
Fuel Oil No 1 1.050
Fuel Oil No 2 1.050
Propane 1.050
Other Fuel 1 1.000
Other Fuel 2 1.000


Building Area

Area [m2]
Total Building Area 46320.38
Net Conditioned Building Area 46320.38
Unconditioned Building Area 0.00


End Uses

Electricity [GJ] Natural Gas [GJ] Gasoline [GJ] Diesel [GJ] Coal [GJ] Fuel Oil No 1 [GJ] Fuel Oil No 2 [GJ] Propane [GJ] Other Fuel 1 [GJ] Other Fuel 2 [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating 0.00 2119.03 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 1733.72 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 3928.95 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 696.73 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 14676.40 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 1934.79 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 2402.24 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 374.21 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 596.57 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 3701.99
Humidification 1449.29 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 539.14
Heat Recovery 47.24 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 825.38 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 2280.17
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                           
Total End Uses 27840.15 2944.41 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 6521.30
Note: Natural gas appears to be the principal heating source based on energy usage.

End Uses By Subcategory

Subcategory Electricity [GJ] Natural Gas [GJ] Gasoline [GJ] Diesel [GJ] Coal [GJ] Fuel Oil No 1 [GJ] Fuel Oil No 2 [GJ] Propane [GJ] Other Fuel 1 [GJ] Other Fuel 2 [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Boiler 0.00 2119.03 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Boiler Parasitic 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling General 1733.72 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting LightsWired 3928.95 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting General 696.73 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment MiscPlug 5334.97 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  DataCenterPlugLoads 9341.42 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment Transformer 80.18 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  ElevatorLift 1848.78 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  ElevatorLightsFan 5.83 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans General 2402.24 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps General 374.21 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection General 596.57 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 3701.99
Humidification General 1449.29 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 539.14
Heat Recovery General 47.24 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  WaterUse 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 2280.17
  Water Heater 0.00 825.38 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


End Uses By Space Type

Space Type Electricity [GJ] Natural Gas [GJ] Gasoline [GJ] Diesel [GJ] Coal [GJ] Fuel Oil No 1 [GJ] Fuel Oil No 2 [GJ] Propane [GJ] Other Fuel 1 [GJ] Other Fuel 2 [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating Unassigned 0.00 2119.03 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling Unassigned 1733.72 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting GENERAL 3928.95 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting Unassigned 696.73 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment GENERAL 14676.40 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment Unassigned 1934.79 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans Unassigned 2402.24 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps Unassigned 374.21 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection Unassigned 596.57 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 3701.99
Humidification Unassigned 1449.29 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 539.14
Heat Recovery Unassigned 47.24 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems Unassigned 0.00 825.38 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 2280.17
Refrigeration Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Normalized Metrics

Utility Use Per Conditioned Floor Area

Electricity Intensity [MJ/m2] Natural Gas Intensity [MJ/m2] Gasoline Intensity [MJ/m2] Diesel Intensity [MJ/m2] Coal Intensity [MJ/m2] Fuel Oil No 1 Intensity [MJ/m2] Fuel Oil No 2 Intensity [MJ/m2] Propane Intensity [MJ/m2] Other Fuel 1 Intensity [MJ/m2] Other Fuel 2 Intensity [MJ/m2] District Cooling Intensity [MJ/m2] District Heating Intensity [MJ/m2] Water Intensity [m3/m2]
Lighting 99.86 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
HVAC 141.54 63.57 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.14
Other 359.63 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total 601.03 63.57 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.14


Utility Use Per Total Floor Area

Electricity Intensity [MJ/m2] Natural Gas Intensity [MJ/m2] Gasoline Intensity [MJ/m2] Diesel Intensity [MJ/m2] Coal Intensity [MJ/m2] Fuel Oil No 1 Intensity [MJ/m2] Fuel Oil No 2 Intensity [MJ/m2] Propane Intensity [MJ/m2] Other Fuel 1 Intensity [MJ/m2] Other Fuel 2 Intensity [MJ/m2] District Cooling Intensity [MJ/m2] District Heating Intensity [MJ/m2] Water Intensity [m3/m2]
Lighting 99.86 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
HVAC 141.54 63.57 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.14
Other 359.63 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total 601.03 63.57 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.14


Electric Loads Satisfied

Electricity [GJ] Percent Electricity [%]
Fuel-Fired Power Generation 0.000 0.00
High Temperature Geothermal* 0.000 0.00
Photovoltaic Power 0.000 0.00
Wind Power 0.000 0.00
Power Conversion 0.000 0.00
Net Decrease in On-Site Storage 0.000 0.00
Total On-Site Electric Sources 0.000 0.00
     
Electricity Coming From Utility 27840.147 100.00
Surplus Electricity Going To Utility 0.000 0.00
Net Electricity From Utility 27840.147 100.00
     
Total On-Site and Utility Electric Sources 27840.147 100.00
Total Electricity End Uses 27840.147 100.00


On-Site Thermal Sources

Heat [GJ] Percent Heat [%]
Water-Side Heat Recovery 0.00 0.00
Air to Air Heat Recovery for Cooling 176.36 4.95
Air to Air Heat Recovery for Heating 3383.80 95.05
High-Temperature Geothermal* 0.00 0.00
Solar Water Thermal 0.00 0.00
Solar Air Thermal 0.00 0.00
Total On-Site Thermal Sources 3560.16 100.00


Water Source Summary

Water [m3] Percent Water [%]
Rainwater Collection 0.00 0.00
Condensate Collection 0.00 0.00
Groundwater Well 0.00 0.00
Total On Site Water Sources 0.00 0.00
- - -
Initial Storage 0.00 0.00
Final Storage 0.00 0.00
Change in Storage 0.00 0.00
- - -
Water Supplied by Utility 6521.30 100.00
- - -
Total On Site, Change in Storage, and Utility Water Sources 6521.30 100.00
Total Water End Uses 6521.30 100.00


Setpoint Not Met Criteria

Degrees [deltaC]
Tolerance for Zone Heating Setpoint Not Met Time 0.56
Tolerance for Zone Cooling Setpoint Not Met Time 0.56


Comfort and Setpoint Not Met Summary

Facility [Hours]
Time Setpoint Not Met During Occupied Heating 111.50
Time Setpoint Not Met During Occupied Cooling 366.00
Time Not Comfortable Based on Simple ASHRAE 55-2004 5937.67


Note 1: An asterisk (*) indicates that the feature is not yet implemented.

Table of Contents

Top
Annual Building Utility Performance Summary
Input Verification and Results Summary
Demand End Use Components Summary
Source Energy End Use Components Summary
Component Sizing Summary
Surface Shadowing Summary
Adaptive Comfort Summary
Initialization Summary
Annual Heat Emissions Summary
Climatic Data Summary
Envelope Summary
Shading Summary
Lighting Summary
Equipment Summary
HVAC Sizing Summary
Coil Sizing Details
System Summary
Outdoor Air Summary
Outdoor Air Details
Object Count Summary
Energy Meters
Sensible Heat Gain Summary
Standard 62.1 Summary
LEED Summary
Annual Thermal Resilience Summary
Annual CO2 Resilience Summary
Annual Visual Resilience Summary

NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR

| Environment |

NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901

| Environment |

NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2013

| Environment |

NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND

| Environment |

NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICELARGE

| Environment |

NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL

| Environment |

NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL

| Environment |

NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 5A

| Environment |

NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_NY_BUFFALO

| Environment |

ZoneCoolingSummaryMonthly

| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |

ZoneHeatingSummaryMonthly

| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |

ZoneElectricSummaryMonthly

| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |

SpaceGainsMonthly

| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |

PeakSpaceGainsMonthly

| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |

SpaceGainComponentsAtCoolingPeakMonthly

| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |

EnergyConsumptionElectricityNaturalGasMonthly

| Meter |

EndUseEnergyConsumptionElectricityMonthly

| Meter |

EndUseEnergyConsumptionNaturalGasMonthly

| Meter |

PeakEnergyEndUseElectricityPart1Monthly

| Meter |

PeakEnergyEndUseElectricityPart2Monthly

| Meter |

ElectricComponentsOfPeakDemandMonthly

| Meter |

PeakEnergyEndUseNaturalGasMonthly

| Meter |

SetpointsNotMetWithTemperaturesMonthly

| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |

ComfortReportSimple55Monthly

| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |

OccupantComfortDataSummaryMonthly

| DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 | BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 |

ChillerReportMonthly

| COOLSYS1 CHILLER1 | COOLSYS1 CHILLER2 |

TowerReportMonthly

| CENTRAL TOWER | TOWERWATERSYS COOLTOWER 1 | TOWERWATERSYS COOLTOWER 2 |

BoilerReportMonthly

| HEATSYS1 BOILER | CENTRAL BOILER |

DXReportMonthly

| VAV_BOT WITH REHEAT COOLING COIL | VAV_MID WITH REHEAT COOLING COIL | VAV_TOP WITH REHEAT COOLING COIL | CAV_BAS COOLING COIL | AIRLOOP DATACENTER BASEMENT COOLING COIL | AIRLOOP DATACENTER BOT COOLING COIL | AIRLOOP DATACENTER MID COOLING COIL | AIRLOOP DATACENTER TOP COOLING COIL |

WindowReportMonthly

| PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW |

WindowEnergyReportMonthly

| PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW |

WindowZoneSummaryMonthly

| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |

WindowEnergyZoneSummaryMonthly

| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |

AverageOutdoorConditionsMonthly

| Environment |

OutdoorConditionsMaximumDryBulbMonthly

| Environment |

OutdoorConditionsMinimumDryBulbMonthly

| Environment |

OutdoorConditionsMaximumWetBulbMonthly

| Environment |

OutdoorConditionsMaximumDewPointMonthly

| Environment |

OutdoorGroundConditionsMonthly

| Environment |

WaterHeaterReportMonthly

| SWHSYS1 WATER HEATER |

DaylightingReportMonthly

| PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_4_DAYLCTRL |

CoilReportMonthly

| VAV_BOT WITH REHEAT HEATING COIL | CORE_BOTTOM VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | VAV_MID WITH REHEAT HEATING COIL | CORE_MID VAV BOX REHEAT COIL | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | VAV_TOP WITH REHEAT HEATING COIL | CORE_TOP VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | CAV_BAS HEATING COIL | AIRLOOP DATACENTER BASEMENT HEATING COIL | AIRLOOP DATACENTER BOT HEATING COIL | AIRLOOP DATACENTER MID HEATING COIL | AIRLOOP DATACENTER TOP HEATING COIL | AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | AIRLOOP DATACENTER BOT_SUPPHEATCOIL | AIRLOOP DATACENTER MID_SUPPHEATCOIL | AIRLOOP DATACENTER TOP_SUPPHEATCOIL | VAV_BOT WITH REHEAT COOLING COIL | VAV_MID WITH REHEAT COOLING COIL | VAV_TOP WITH REHEAT COOLING COIL | CAV_BAS COOLING COIL | AIRLOOP DATACENTER BASEMENT COOLING COIL | AIRLOOP DATACENTER BOT COOLING COIL | AIRLOOP DATACENTER MID COOLING COIL | AIRLOOP DATACENTER TOP COOLING COIL |

PlantLoopDemandReportMonthly

| HEATSYS1 | COOLSYS1_SUPPLY | COOLSYS1_DEMAND | SINGLE WATER PLANT LOOP | SWHSYS1 | TOWERWATERSYS |

FanReportMonthly

| CAV_BAS FAN | VAV_BOT WITH REHEAT FAN | VAV_MID WITH REHEAT FAN | VAV_TOP WITH REHEAT FAN | AIRLOOP DATACENTER BASEMENT SUPPLY FAN | AIRLOOP DATACENTER BOT SUPPLY FAN | AIRLOOP DATACENTER MID SUPPLY FAN | AIRLOOP DATACENTER TOP SUPPLY FAN |

PumpReportMonthly

| HEATSYS1 PUMP | COOLSYS1 PUMP SECONDARY | COOLSYS1 CHILLER1 PUMP | COOLSYS1 CHILLER2 PUMP | PLANT CIRC PUMP | SWHSYS1 PUMP | TOWERWATERSYS PUMP |

CondLoopDemandReportMonthly

| HEATSYS1 | COOLSYS1_SUPPLY | COOLSYS1_DEMAND | SINGLE WATER PLANT LOOP | SWHSYS1 | TOWERWATERSYS |

ZoneTemperatureOscillationReportMonthly

| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |

AirLoopSystemEnergyAndWaterUseMonthly

| VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | CAV_BAS | AIRLOOP DATACENTER BASEMENT | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |

AirLoopSystemComponentLoadsMonthly

| VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | CAV_BAS | AIRLOOP DATACENTER BASEMENT | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |

AirLoopSystemComponentEnergyUseMonthly

| VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | CAV_BAS | AIRLOOP DATACENTER BASEMENT | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |

MechanicalVentilationLoadsMonthly

| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |

HeatEmissionsReportMonthly

| Environment |

Table of Contents

Report: Input Verification and Results Summary

For: Entire Facility

Timestamp: 2023-10-16 08:43:24

General

Value
Program Version and Build EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:43
RunPeriod RUNPERIOD 1
Weather File Buffalo Niagara Intl AP NY USA TMY3 WMO#=725280
Latitude [deg] 42.93
Longitude [deg] -78.7
Elevation [m] 215.00
Time Zone -5.0
North Axis Angle [deg] 0.00
Rotation for Appendix G [deg] 0.00
Hours Simulated [hrs] 8760.00


ENVELOPE

Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [m2] 12183.89 3655.17 2436.78 3655.17 2436.78
Above Ground Wall Area [m2] 11589.54 3476.86 2317.91 3476.86 2317.91
Window Opening Area [m2] 4635.80 1390.74 927.16 1390.74 927.16
Gross Window-Wall Ratio [%] 38.05 38.05 38.05 38.05 38.05
Above Ground Window-Wall Ratio [%] 40.00 40.00 40.00 40.00 40.00


Conditioned Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [m2] 12183.89 3655.17 2436.78 3655.17 2436.78
Above Ground Wall Area [m2] 11589.54 3476.86 2317.91 3476.86 2317.91
Window Opening Area [m2] 4635.80 1390.74 927.16 1390.74 927.16
Gross Window-Wall Ratio [%] 38.05 38.05 38.05 38.05 38.05
Above Ground Window-Wall Ratio [%] 40.00 40.00 40.00 40.00 40.00


Skylight-Roof Ratio

Total
Gross Roof Area [m2] 3563.11
Skylight Area [m2] 0.00
Skylight-Roof Ratio [%] 0.00


PERFORMANCE

Zone Summary

Area [m2] Conditioned (Y/N) Part of Total Floor Area (Y/N) Volume [m3] Multipliers Above Ground Gross Wall Area [m2] Underground Gross Wall Area [m2] Window Glass Area [m2] Opening Area [m2] Lighting [W/m2] People [m2 per person] Plug and Process [W/m2]
BASEMENT 2779.43 Yes Yes 6779.02 1.00 0.00 397.05 0.00 0.00 10.2732 18.58 4.8418
CORE_BOTTOM 2496.12 Yes Yes 6849.35 1.00 0.00 0.00 0.00 0.00 10.2732 18.58 8.0697
CORE_MID 2496.12 Yes Yes 6849.35 10.00 0.00 0.00 0.00 0.00 10.2732 18.58 8.0696
CORE_TOP 2496.12 Yes Yes 6849.35 1.00 0.00 0.00 0.00 0.00 10.2732 18.58 8.0696
PERIMETER_BOT_ZN_3 313.41 Yes Yes 860.00 1.00 200.61 0.00 115.90 115.90 10.2732 18.58 8.0700
PERIMETER_BOT_ZN_2 201.98 Yes Yes 554.22 1.00 133.74 0.00 77.26 77.26 10.2732 18.58 8.0700
PERIMETER_BOT_ZN_1 313.42 Yes Yes 860.02 1.00 200.61 0.00 115.90 115.90 10.2732 18.58 8.0699
PERIMETER_BOT_ZN_4 201.98 Yes Yes 554.22 1.00 133.74 0.00 77.26 77.26 10.2732 18.58 8.0699
PERIMETER_MID_ZN_3 313.41 Yes Yes 860.00 10.00 200.61 0.00 115.90 115.90 10.2732 18.58 8.0700
PERIMETER_MID_ZN_2 201.98 Yes Yes 554.22 10.00 133.74 0.00 77.26 77.26 10.2732 18.58 8.0700
PERIMETER_MID_ZN_1 313.42 Yes Yes 860.02 10.00 200.61 0.00 115.90 115.90 10.2732 18.58 8.0699
PERIMETER_MID_ZN_4 201.98 Yes Yes 554.22 10.00 133.74 0.00 77.26 77.26 10.2732 18.58 8.0699
PERIMETER_TOP_ZN_3 313.41 Yes Yes 860.00 1.00 200.61 0.00 115.90 115.90 10.2732 18.58 8.0700
PERIMETER_TOP_ZN_2 201.98 Yes Yes 554.22 1.00 133.74 0.00 77.26 77.26 10.2732 18.58 8.0700
PERIMETER_TOP_ZN_1 313.42 Yes Yes 860.02 1.00 200.61 0.00 115.90 115.90 10.2732 18.58 8.0699
PERIMETER_TOP_ZN_4 201.98 Yes Yes 554.22 1.00 133.74 0.00 77.26 77.26 10.2732 18.58 8.0699
GROUNDFLOOR_PLENUM 3563.11 Yes No 4344.14 1.00 297.11 0.00 0.00 0.00 0.0000   0.0000
MIDFLOOR_PLENUM 3563.11 Yes No 4344.14 10.00 297.11 0.00 0.00 0.00 0.0000   0.0000
TOPFLOOR_PLENUM 3563.11 Yes No 4344.14 1.00 297.11 0.00 0.00 0.00 0.0000   0.0000
DATACENTER_BOT_ZN_6 36.20 Yes Yes 99.34 1.00 0.00 0.00 0.00 0.00 17.8735 18.58 215.2992
DATACENTER_MID_ZN_6 36.20 Yes Yes 99.34 10.00 0.00 0.00 0.00 0.00 17.8735 18.58 215.2992
DATACENTER_TOP_ZN_6 36.20 Yes Yes 99.34 1.00 0.00 0.00 0.00 0.00 17.8735 18.58 215.2992
DATACENTER_BASEMENT_ZN_6 783.68 Yes Yes 1911.37 1.00 0.00 197.31 0.00 0.00 10.2732 18.58 484.4232
Total 46320.38     126016.35   8024.24 594.36 4635.80 4635.80 10.3445 18.58 17.8789
Conditioned Total 46320.38     126016.35   8024.24 594.36 4635.80 4635.80 10.3445 18.58 17.8789
Unconditioned Total 0.00     0.00   0.00 0.00 0.00 0.00      
Not Part of Total 42757.27     52129.67   3565.29 0.00 0.00 0.00 0.0000   0.0000


Space Summary

Area [m2] Conditioned (Y/N) Part of Total Floor Area (Y/N) Multipliers Zone Name Space Type Radiant/Solar Enclosure Name Lighting [W/m2] People [m2 per person] Plug and Process [W/m2] Tags
BASEMENT 2779.43 Yes Yes 1.00 BASEMENT GENERAL BASEMENT 10.2732 18.58 4.8418  
CORE_BOTTOM 2496.12 Yes Yes 1.00 CORE_BOTTOM GENERAL CORE_BOTTOM 10.2732 18.58 8.0697  
CORE_MID 2496.12 Yes Yes 10.00 CORE_MID GENERAL CORE_MID 10.2732 18.58 8.0696  
CORE_TOP 2496.12 Yes Yes 1.00 CORE_TOP GENERAL CORE_TOP 10.2732 18.58 8.0696  
PERIMETER_BOT_ZN_3 313.41 Yes Yes 1.00 PERIMETER_BOT_ZN_3 GENERAL PERIMETER_BOT_ZN_3 10.2732 18.58 8.0700  
PERIMETER_BOT_ZN_2 201.98 Yes Yes 1.00 PERIMETER_BOT_ZN_2 GENERAL PERIMETER_BOT_ZN_2 10.2732 18.58 8.0700  
PERIMETER_BOT_ZN_1 313.42 Yes Yes 1.00 PERIMETER_BOT_ZN_1 GENERAL PERIMETER_BOT_ZN_1 10.2732 18.58 8.0699  
PERIMETER_BOT_ZN_4 201.98 Yes Yes 1.00 PERIMETER_BOT_ZN_4 GENERAL PERIMETER_BOT_ZN_4 10.2732 18.58 8.0699  
PERIMETER_MID_ZN_3 313.41 Yes Yes 10.00 PERIMETER_MID_ZN_3 GENERAL PERIMETER_MID_ZN_3 10.2732 18.58 8.0700  
PERIMETER_MID_ZN_2 201.98 Yes Yes 10.00 PERIMETER_MID_ZN_2 GENERAL PERIMETER_MID_ZN_2 10.2732 18.58 8.0700  
PERIMETER_MID_ZN_1 313.42 Yes Yes 10.00 PERIMETER_MID_ZN_1 GENERAL PERIMETER_MID_ZN_1 10.2732 18.58 8.0699  
PERIMETER_MID_ZN_4 201.98 Yes Yes 10.00 PERIMETER_MID_ZN_4 GENERAL PERIMETER_MID_ZN_4 10.2732 18.58 8.0699  
PERIMETER_TOP_ZN_3 313.41 Yes Yes 1.00 PERIMETER_TOP_ZN_3 GENERAL PERIMETER_TOP_ZN_3 10.2732 18.58 8.0700  
PERIMETER_TOP_ZN_2 201.98 Yes Yes 1.00 PERIMETER_TOP_ZN_2 GENERAL PERIMETER_TOP_ZN_2 10.2732 18.58 8.0700  
PERIMETER_TOP_ZN_1 313.42 Yes Yes 1.00 PERIMETER_TOP_ZN_1 GENERAL PERIMETER_TOP_ZN_1 10.2732 18.58 8.0699  
PERIMETER_TOP_ZN_4 201.98 Yes Yes 1.00 PERIMETER_TOP_ZN_4 GENERAL PERIMETER_TOP_ZN_4 10.2732 18.58 8.0699  
GROUNDFLOOR_PLENUM 3563.11 Yes No 1.00 GROUNDFLOOR_PLENUM GENERAL GROUNDFLOOR_PLENUM 0.0000 0.00 0.0000  
MIDFLOOR_PLENUM 3563.11 Yes No 10.00 MIDFLOOR_PLENUM GENERAL MIDFLOOR_PLENUM 0.0000 0.00 0.0000  
TOPFLOOR_PLENUM 3563.11 Yes No 1.00 TOPFLOOR_PLENUM GENERAL TOPFLOOR_PLENUM 0.0000 0.00 0.0000  
DATACENTER_BOT_ZN_6 36.20 Yes Yes 1.00 DATACENTER_BOT_ZN_6 GENERAL DATACENTER_BOT_ZN_6 17.8735 18.58 215.2992  
DATACENTER_MID_ZN_6 36.20 Yes Yes 10.00 DATACENTER_MID_ZN_6 GENERAL DATACENTER_MID_ZN_6 17.8735 18.58 215.2992  
DATACENTER_TOP_ZN_6 36.20 Yes Yes 1.00 DATACENTER_TOP_ZN_6 GENERAL DATACENTER_TOP_ZN_6 17.8735 18.58 215.2992  
DATACENTER_BASEMENT_ZN_6 783.68 Yes Yes 1.00 DATACENTER_BASEMENT_ZN_6 GENERAL DATACENTER_BASEMENT_ZN_6 10.2732 18.58 484.4232  
Total 46320.38             10.3445 9.29 17.8789  
Conditioned Total 46320.38             10.3445 9.29 17.8789  
Unconditioned Total 0.00             0.0000 0.00 0.0000  
Not Part of Total 42757.27             0.0000 0.00 0.0000  


Space Type Summary

Total Area [m2] Conditioned Area [m2] Unconditioned Area [m2] Not Part of Total Area [m2] Lighting [W/m2] People [m2 per person] Plug and Process [W/m2]
GENERAL 46320.38 46320.38 0.00 42757.27 3.1788 60.38 10.8345
Total 46320.38 46320.38 0.00 42757.27      



Table of Contents

Report: Demand End Use Components Summary

For: Entire Facility

Timestamp: 2023-10-16 08:43:24

End Uses

Electricity [W] Natural Gas [W] Gasoline [W] Diesel [W] Coal [W] Fuel Oil No 1 [W] Fuel Oil No 2 [W] Propane [W] Other Fuel 1 [W] Other Fuel 2 [W] District Cooling [W] Steam [W] Water [m3/s]
Time of Peak 15-AUG-14:39 26-DEC-07:10 - - - - - - - - - - 17-AUG-12:00
Heating 0.00 2175214.88 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 583018.50 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 332294.83 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 778371.69 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 39059.06 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 228540.74 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 58816.12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 90257.03 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 17458.89 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                           
Total End Uses 2110357.97 2192673.77 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


End Uses By Subcategory

Subcategory Electricity [W] Natural Gas [W] Gasoline [W] Diesel [W] Coal [W] Fuel Oil No 1 [W] Fuel Oil No 2 [W] Propane [W] Other Fuel 1 [W] Other Fuel 2 [W] District Cooling [W] Steam [W] Water [m3/s]
Heating General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Boiler 0.00 2175214.88 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Boiler Parasitic 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling General 583018.50 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting LightsWired 332294.83 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment MiscPlug 305206.10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  DataCenterPlugLoads 473165.59 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment Transformer 5015.67 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  ElevatorLift 33930.59 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  ElevatorLightsFan 112.80 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans General 228540.74 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps General 58816.12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection General 90257.03 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  WaterUse 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Water Heater 0.00 17458.89 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: Source Energy End Use Components Summary

For: Entire Facility

Timestamp: 2023-10-16 08:43:24

Values gathered over 8760.00 hours



Source Energy End Use Components Summary

Source Electricity [GJ] Source Natural Gas [GJ] Source Gasoline [GJ] Source Diesel [GJ] Source Coal [GJ] Source Fuel Oil No 1 [GJ] Source Fuel Oil No 2 [GJ] Source Propane [GJ] Source Other Fuel 1 [GJ] Source Other Fuel 2 [GJ] Source District Cooling [GJ] Source District Heating [GJ]
Heating 0.00 2297.03 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 5490.70 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 12442.98 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 2206.54 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 46480.15 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 6127.48 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 7607.91 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 1185.12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 1889.34 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 4589.92 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 149.62 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 894.71 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Total Source Energy End Use Components 88169.74 3191.74 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Normalized Metrics

Source Energy End Use Components Per Conditioned Floor Area

Source Electricity [MJ/m2] Source Natural Gas [MJ/m2] Source Gasoline [MJ/m2] Source Diesel [MJ/m2] Source Coal [MJ/m2] Source Fuel Oil No 1 [MJ/m2] Source Fuel Oil No 2 [MJ/m2] Source Propane [MJ/m2] Source Other Fuel 1 [MJ/m2] Source Other Fuel 2 [MJ/m2] Source District Cooling [MJ/m2] Source District Heating [MJ/m2]
Heating 0.00 49.59 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 118.54 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 268.63 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 47.64 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 1003.45 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 132.28 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 164.25 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 25.59 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 40.79 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 99.09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 3.23 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 19.32 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Total Source Energy End Use Components 1903.48 68.91 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Source Energy End Use Components Per Total Floor Area

Source Electricity [MJ/m2] Source Natural Gas [MJ/m2] Source Gasoline [MJ/m2] Source Diesel [MJ/m2] Source Coal [MJ/m2] Source Fuel Oil No 1 [MJ/m2] Source Fuel Oil No 2 [MJ/m2] Source Propane [MJ/m2] Source Other Fuel 1 [MJ/m2] Source Other Fuel 2 [MJ/m2] Source District Cooling [MJ/m2] Source District Heating [MJ/m2]
Heating 0.00 49.59 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 118.54 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 268.63 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 47.64 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 1003.45 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 132.28 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 164.25 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 25.59 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 40.79 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 99.09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 3.23 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 19.32 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Total Source Energy End Use Components 1903.48 68.91 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: Component Sizing Summary

For: Entire Facility

Timestamp: 2023-10-16 08:43:24

AirTerminal:SingleDuct:ConstantVolume:NoReheat

Design Size Maximum Air Flow Rate [m3/s]
BASEMENT DIRECT AIR 6.07
DATACENTER_BOT_ZN_6 DIRECT AIR 0.512428
DATACENTER_MID_ZN_6 DIRECT AIR 4.92
DATACENTER_TOP_ZN_6 DIRECT AIR 0.499615
DATACENTER_BASEMENT_ZN_6 DIRECT AIR 21.94
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

AirTerminal:SingleDuct:VAV:Reheat

Design Size Maximum Air Flow Rate [m3/s] Design Size Constant Minimum Air Flow Fraction User-Specified Constant Minimum Air Flow Fraction Design Size Minimum Air Flow Rate [m3/s] Design Size Maximum Flow Fraction during Reheat [] User-Specified Maximum Flow Fraction during Reheat [] Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] Design Size Maximum Reheat Water Flow Rate [m3/s] Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] Design Size Reheat Coil Sizing Inlet Air Temperature [C] Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir]
CORE_BOTTOM VAV BOX COMPONENT 6.30 0.301763 0.313000 1.97 0.804701 0.500000 0.001263 0.000213 1.97 12.80 0.008000
CORE_MID VAV BOX COMPONENT 59.39 0.320282 0.326000 19.36 0.854085 0.500000 0.001190 0.004459 19.36 12.80 0.008000
CORE_TOP VAV BOX COMPONENT 5.87 0.323802 0.338000 1.99 0.863471 0.500000 0.001177 0.000853 2.98 12.80 0.008000
PERIMETER_BOT_ZN_3 VAV BOX COMPONENT 1.05 0.226679 0.235000 0.247588 0.604477 0.500000 0.001681 0.000165 0.575697 12.80 0.008000
PERIMETER_BOT_ZN_2 VAV BOX COMPONENT 1.39 0.110534 0.200000 0.278476 0.300000 0.500000 0.003447 0.000111 0.389091 12.80 0.008000
PERIMETER_BOT_ZN_1 VAV BOX COMPONENT 1.61 0.148454 0.200000 0.321751 0.395877 0.500000 0.002566 0.000179 0.625594 12.80 0.008000
PERIMETER_BOT_ZN_4 VAV BOX COMPONENT 1.69 0.091137 0.200000 0.337744 0.300000 0.500000 0.004181 0.000093 0.337744 12.80 0.008000
PERIMETER_MID_ZN_3 VAV BOX COMPONENT 10.00 0.238846 0.243000 2.43 0.636922 0.500000 0.001595 0.002519 8.82 12.80 0.008000
PERIMETER_MID_ZN_2 VAV BOX COMPONENT 14.83 0.103759 0.200000 2.97 0.300000 0.500000 0.003672 0.001649 5.77 12.80 0.008000
PERIMETER_MID_ZN_1 VAV BOX COMPONENT 16.10 0.148335 0.200000 3.22 0.395559 0.500000 0.002569 0.002519 8.82 12.80 0.008000
PERIMETER_MID_ZN_4 VAV BOX COMPONENT 15.68 0.098171 0.200000 3.14 0.300000 0.500000 0.003881 0.001617 5.66 12.80 0.008000
PERIMETER_TOP_ZN_3 VAV BOX COMPONENT 1.12 0.212849 0.222000 0.249088 0.567598 0.500000 0.001790 0.000315 1.10 12.80 0.008000
PERIMETER_TOP_ZN_2 VAV BOX COMPONENT 1.49 0.103077 0.200000 0.298620 0.300000 0.500000 0.003696 0.000206 0.720283 12.80 0.008000
PERIMETER_TOP_ZN_1 VAV BOX COMPONENT 1.72 0.138569 0.200000 0.344702 0.369518 0.500000 0.002750 0.000315 1.10 12.80 0.008000
PERIMETER_TOP_ZN_4 VAV BOX COMPONENT 1.65 0.093465 0.200000 0.329332 0.300000 0.500000 0.004076 0.000204 0.715332 12.80 0.008000
User-Specified values were used. Design Size values were used if no User-Specified values were provided. Design Size values may be derived from alternate User-Specified values.

Coil:Heating:Water

Design Size Rated Capacity [W] Design Size Maximum Water Flow Rate [m3/s] Design Size U-Factor Times Area Value [W/K]
CORE_BOTTOM VAV BOX REHEAT COIL 24384.09 0.000213 504.43
CORE_MID VAV BOX REHEAT COIL 509693.53 0.004459 12357.36
CORE_TOP VAV BOX REHEAT COIL 97540.46 0.000853 2574.54
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL 18821.10 0.000165 496.42
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL 12719.09 0.000111 335.46
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL 20449.32 0.000179 539.33
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL 10619.50 0.000093 275.32
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL 287968.01 0.002519 7592.18
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL 188490.16 0.001649 4969.41
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL 287969.55 0.002519 7592.22
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL 184787.33 0.001617 4871.83
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL 36035.65 0.000315 949.94
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL 23518.56 0.000206 619.97
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL 36035.92 0.000315 949.94
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL 23356.95 0.000204 615.71
VAV_BOT WITH REHEAT HEATING COIL 81559.25 0.000714 1298.99
VAV_MID WITH REHEAT HEATING COIL 835544.76 0.007310 13168.53
VAV_TOP WITH REHEAT HEATING COIL 81603.30 0.000714 1303.00
CAV_BAS HEATING COIL 309371.51 0.002707 6738.85
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

AirLoopHVAC

Sum of Air Terminal Maximum Heating Flow Rates [m3/s] Sum of Air Terminal Minimum Heating Flow Rates [m3/s] Sum of Air Terminal Maximum Flow Rates [m3/s] Adjusted Heating Design Air Flow Rate [m3/s] Adjusted Cooling Design Air Flow Rate [m3/s] Adjusted Main Design Air Flow Rate [m3/s] User Heating Air Flow Ratio [] Calculated Heating Air Flow Ratio [] Design Supply Air Flow Rate [m3/s]
VAV_BOT WITH REHEAT 6.02 3.16 12.05 3.16 10.38 10.38 0.300000 0.304275 10.38
VAV_MID WITH REHEAT 58.00 31.11 116.00 42.92 96.93 96.93 0.300000 0.442762 96.93
VAV_TOP WITH REHEAT 5.93 3.21 11.86 6.62 10.63 10.63 0.300000 0.623181 10.63
CAV_BAS 6.07 6.07 6.07 6.07 6.07 6.07 1.00 1.00 6.07
AIRLOOP DATACENTER BASEMENT 21.94 21.94 21.94 21.94 21.94 21.94 1.00 0.999995 21.94
AIRLOOP DATACENTER BOT 0.512428 0.512428 0.512428 0.512428 0.512428 0.512428 1.00 1.00 0.512428
AIRLOOP DATACENTER MID 4.92 4.92 4.92 4.92 4.92 4.92 1.00 1.00 4.92
AIRLOOP DATACENTER TOP 0.499615 0.499615 0.499615 0.499615 0.499615 0.499615 1.00 1.00 0.499615
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Controller:OutdoorAir

Maximum Outdoor Air Flow Rate [m3/s] Minimum Outdoor Air Flow Rate [m3/s]
VAV_BOT WITH REHEAT_OA_CONTROLLER 10.38 2.54
VAV_MID WITH REHEAT_OA_CONTROLLER 96.93 25.38
VAV_TOP WITH REHEAT_OA_CONTROLLER 10.63 2.54
CAV_BAS_OA_CONTROLLER 6.07 1.20
AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER 21.94 0.338393
AIRLOOP DATACENTER BOT_OA_CONTROLLER 0.512428 0.015632
AIRLOOP DATACENTER MID_OA_CONTROLLER 4.92 0.156323
AIRLOOP DATACENTER TOP_OA_CONTROLLER 0.499615 0.015632
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

HeatExchanger:AirToAir:SensibleAndLatent

Design Size Nominal Supply Air Flow Rate [m3/s]
VAV_BOT WITH REHEAT OA HEAT RECOVERY 2.54
VAV_MID WITH REHEAT OA HEAT RECOVERY 25.38
VAV_TOP WITH REHEAT OA HEAT RECOVERY 2.54
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Coil:Cooling:Water

Design Size Design Inlet Air Temperature [C] Design Size Design Inlet Water Temperature [C] Design Size Design Outlet Air Temperature [C] Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] Design Size Design Coil Load [W] Design Size Design Water Flow Rate [m3/s] Design Size Design Air Flow Rate [m3/s]
VAV_BOT WITH REHEAT COOLING COIL 25.57 6.67 10.91 0.009989 0.008500 228603.16 0.009725 10.38
VAV_MID WITH REHEAT COOLING COIL 25.71 6.67 10.91 0.010160 0.008500 2200563.12 0.093617 96.93
VAV_TOP WITH REHEAT COOLING COIL 25.51 6.67 10.91 0.009991 0.008500 233234.66 0.009922 10.63
CAV_BAS COOLING COIL 24.89 6.67 11.39 0.009897 0.008500 123499.09 0.005254 6.07
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Fan:VariableVolume

Design Size Maximum Flow Rate [m3/s]
VAV_BOT WITH REHEAT FAN 10.38
VAV_MID WITH REHEAT FAN 96.93
VAV_TOP WITH REHEAT FAN 10.63
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Controller:WaterCoil

Maximum Actuated Flow [m3/s] Controller Convergence Tolerance
VAV_BOT WITH REHEAT_COOLC_CONTROLLER 0.009725 0.000049
VAV_BOT WITH REHEAT_HEATC_CONTROLLER 0.000714  
VAV_MID WITH REHEAT_COOLC_CONTROLLER 0.093617 0.000005
VAV_MID WITH REHEAT_HEATC_CONTROLLER 0.007310  
VAV_TOP WITH REHEAT_COOLC_CONTROLLER 0.009922 0.000048
VAV_TOP WITH REHEAT_HEATC_CONTROLLER 0.000714  
CAV_BAS_COOLC_CONTROLLER 0.005254 0.000091
CAV_BAS_HEATC_CONTROLLER 0.002707  
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Fan:ConstantVolume

Design Size Maximum Flow Rate [m3/s]
CAV_BAS FAN 6.07
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT

Design Size Rated Air Flow Rate [m3/s] Design Size Rated Total Cooling Capacity [W] Design Size Rated Sensible Cooling Capacity [W] Design Size Rated Water Flow Rate [m3/s]
AIRLOOP DATACENTER BASEMENT COOLING COIL 21.94 435227.10 306220.41 0.010659
AIRLOOP DATACENTER BOT COOLING COIL 0.512428 10034.39 7101.30 0.000246
AIRLOOP DATACENTER MID COOLING COIL 4.92 96406.42 68179.43 0.002361
AIRLOOP DATACENTER TOP COOLING COIL 0.499615 9793.48 6926.95 0.000240
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

AirLoopHVAC:UnitaryHeatPump:WaterToAir

Supply Air Flow Rate [m3/s] Supply Air Flow Rate During Heating Operation [m3/s] Supply Air Flow Rate During Cooling Operation [m3/s] Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] Nominal Heating Capacity [W] Nominal Cooling Capacity [W] Supplemental Heating Coil Nominal Capacity [W] Fraction of Supply Air Flow That Goes Through the Controlling Zone
AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP 21.94 21.94 21.94 21.94 435227.10 435227.10 22473.72 1.00
AIRLOOP DATACENTER BOT DXAC HEAT PUMP 0.512428 0.512428 0.512428 0.512428 10034.39 10034.39 1038.19 1.00
AIRLOOP DATACENTER MID DXAC HEAT PUMP 4.92 4.92 4.92 4.92 96406.42 96406.42 10381.93 1.00
AIRLOOP DATACENTER TOP DXAC HEAT PUMP 0.499615 0.499615 0.499615 0.499615 9793.48 9793.48 1038.19 1.00
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Fan:OnOff

Design Size Maximum Flow Rate [m3/s]
AIRLOOP DATACENTER BASEMENT SUPPLY FAN 21.94
AIRLOOP DATACENTER BOT SUPPLY FAN 0.512428
AIRLOOP DATACENTER MID SUPPLY FAN 4.92
AIRLOOP DATACENTER TOP SUPPLY FAN 0.499615
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT

Design Size Rated Air Flow Rate [m3/s] Design Size Rated Heating Capacity [W] Design Size Rated Water Flow Rate [m3/s]
AIRLOOP DATACENTER BASEMENT HEATING COIL 21.94 435227.10 0.010659
AIRLOOP DATACENTER BOT HEATING COIL 0.512428 10034.39 0.000246
AIRLOOP DATACENTER MID HEATING COIL 4.92 96406.42 0.002361
AIRLOOP DATACENTER TOP HEATING COIL 0.499615 9793.48 0.000240
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Coil:Heating:Electric

Design Size Nominal Capacity [W]
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL 22473.72
AIRLOOP DATACENTER BOT_SUPPHEATCOIL 1038.19
AIRLOOP DATACENTER MID_SUPPHEATCOIL 10381.93
AIRLOOP DATACENTER TOP_SUPPHEATCOIL 1038.19
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Humidifier:Steam:Electric

Design Size Nominal Capacity Volume [m3/s] User-Specified Nominal Capacity Volume [m3/s] Design Size Rated Power [W] User-Specified Rated Power [W]
DATACENTER_BASEMENT_ZN_6 HUMIDIFIER 0.000188 0.000037 96450.70 100000.00
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Pump:VariableSpeed

Design Flow Rate [m3/s] Design Power Consumption [W] Design Minimum Flow Rate [m3/s]
COOLSYS1 PUMP SECONDARY 0.118519 19350.47  
HEATSYS1 PUMP 0.026862 8089.59 0.000000
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

PlantLoop

Maximum Loop Flow Rate [m3/s] Plant Loop Volume [m3]
COOLSYS1_DEMAND 0.118519 14.22
HEATSYS1 0.026862 3.22
COOLSYS1_SUPPLY 0.118519 14.22
SINGLE WATER PLANT LOOP 0.013505 1.62
SWHSYS1 0.000440 0.052800
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

HeatExchanger:FluidToFluid

Loop Supply Side Design Fluid Flow Rate [m3/s] Loop Demand Side Design Fluid Flow Rate [m3/s] Heat Exchanger U-Factor Times Area Value [W/C] Loop-to-loop Temperature Difference Used to Size Heat Exchanger U-Factor Times Area Value [C]
BYPASS HEAT EXCHANGER 0.118519 0.118519 497482.15 5.60
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Boiler:HotWater

Design Size Nominal Capacity [W] User-Specified Nominal Capacity [W] Design Size Design Water Flow Rate [m3/s]
HEATSYS1 BOILER 3070468.04 3070468.04 0.026862
CENTRAL BOILER 556300.69 545478.78 0.013505
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Pump:ConstantSpeed

Design Flow Rate [m3/s] Design Power Consumption [W]
COOLSYS1 CHILLER1 PUMP 0.059259 6698.49
COOLSYS1 CHILLER2 PUMP 0.059259 6698.49
PLANT CIRC PUMP 0.013505 3444.52
SWHSYS1 PUMP 0.000440 56.21
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Chiller:Electric:ReformulatedEIR

Design Size Reference Chilled Water Flow Rate [m3/s] User-Specified Reference Chilled Water Flow Rate [m3/s] Design Size Reference Capacity [W] User-Specified Reference Capacity [W] Design Size Reference Condenser Water Flow Rate [m3/s]
COOLSYS1 CHILLER1 0.118519 0.059595 1404281.78 1410897.12 0.069820
COOLSYS1 CHILLER2 0.118519 0.059595 1404281.78 1410897.12 0.069820
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

FluidCooler:TwoSpeed

Design Water Flow Rate [m3/s] Air Flow Rate at High Fan Speed [m3/s] Fluid cooler UA value at high fan speed based on nominal capacity input [W/K] Air Flow Rate at Low Fan Speed [m3/s] Fan Power at Low Fan Speed [W] U-factor Times Area Value at Low Fan Speed [W/C]
CENTRAL TOWER 0.013505 139666.47 58456.61 69833.23 7879.72 21333.26
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

WaterHeater:Mixed

Use Side Design Flow Rate [m3/s]
SWHSYS1 WATER HEATER 0.000440
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

CondenserLoop

Maximum Loop Flow Rate [m3/s] Condenser Loop Volume [m3]
TOWERWATERSYS 0.139640 16.76
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

HeaderedPumps:VariableSpeed

Design Flow Rate [m3/s] Design Power Consumption [W]
TOWERWATERSYS PUMP 0.139640 34571.81
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

CoolingTower:VariableSpeed

Design Air Flow Rate [m3/s] Nominal Capacity [W] Air Flow Rate in free convection regime [m3/s] Tower capacity in free convection regime at design conditions [W]
TOWERWATERSYS COOLTOWER 1 55.36 1674019.00 11.07 209252.38
TOWERWATERSYS COOLTOWER 2 55.36 1674019.00 11.07 209252.38
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

PlantEquipmentOperation:ComponentSetPoint

Design Water Flow Rate [m3/s] Equipment # 47
WSHPPLANT OPERATION SCHEME 0.072520
User-Specified values were used. Design Size values were used if no User-Specified values were provided.


Table of Contents

Report: Surface Shadowing Summary

For: Entire Facility

Timestamp: 2023-10-16 08:43:24

Surfaces (Walls, Roofs, etc) that may be Shadowed by Other Surfaces

None


Subsurfaces (Windows and Doors) that may be Shadowed by Surfaces

Possible Shadow Receivers
PERIMETER_BOT_ZN_3_WALL_NORTH PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 |
PERIMETER_BOT_ZN_2_WALL_EAST PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 |
PERIMETER_BOT_ZN_1_WALL_SOUTH PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 |
PERIMETER_BOT_ZN_4_WALL_WEST PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 |
PERIMETER_MID_ZN_3_WALL_NORTH PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW |
PERIMETER_MID_ZN_2_WALL_EAST PERIMETER_MID_ZN_2_WALL_EAST_WINDOW |
PERIMETER_MID_ZN_1_WALL_SOUTH PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW |
PERIMETER_MID_ZN_4_WALL_WEST PERIMETER_MID_ZN_4_WALL_WEST_WINDOW |
PERIMETER_TOP_ZN_3_WALL_NORTH PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW |
PERIMETER_TOP_ZN_2_WALL_EAST PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW |
PERIMETER_TOP_ZN_1_WALL_SOUTH PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW |
PERIMETER_TOP_ZN_4_WALL_WEST PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW |



Table of Contents

Report: Adaptive Comfort Summary

For: Entire Facility

Timestamp: 2023-10-16 08:43:24

Time Not Meeting the Adaptive Comfort Models during Occupied Hours

ASHRAE55 90% Acceptability Limits [Hours] ASHRAE55 80% Acceptability Limits [Hours] CEN15251 Category I Acceptability Limits [Hours] CEN15251 Category II Acceptability Limits [Hours] CEN15251 Category III Acceptability Limits [Hours]



Table of Contents

Report: Initialization Summary

For: Entire Facility

Timestamp: 2023-10-16 08:43:24

Version

Version ID
1 22.1.0


Timesteps per Hour

#TimeSteps Minutes per TimeStep {minutes}
1 6 10


System Convergence Limits

Minimum System TimeStep {minutes} Max HVAC Iterations Minimum Plant Iterations Maximum Plant Iterations
1 1 20 2 8


Simulation Control

Do Zone Sizing Do System Sizing Do Plant Sizing Do Design Days Do Weather Simulation Do HVAC Sizing Simulation
1 Yes Yes Yes No Yes No


Performance Precision Tradeoffs

Use Coil Direct Simulation Zone Radiant Exchange Algorithm Override Mode Number of Timestep In Hour Force Euler Method Minimum Number of Warmup Days Force Suppress All Begin Environment Resets Minimum System Timestep MaxZoneTempDiff MaxAllowedDelTemp
1 No ScriptF Normal 6 No 1 No 1.0 0.300 2.0000E-003


Output Reporting Tolerances

Tolerance for Time Heating Setpoint Not Met Tolerance for Zone Cooling Setpoint Not Met Time
1 0.556 0.556


Site:GroundTemperature:BuildingSurface

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00


Site:GroundTemperature:FCfactorMethod

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 9.70 6.00 -2.20 -3.40 -4.20 2.70 7.50 13.70 18.60 22.00 20.70 16.50


Site:GroundTemperature:Shallow

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00


Site:GroundTemperature:Deep

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00


Site:GroundReflectance

Jan{dimensionless} Feb{dimensionless} Mar{dimensionless} Apr{dimensionless} May{dimensionless} Jun{dimensionless} Jul{dimensionless} Aug{dimensionless} Sep{dimensionless} Oct{dimensionless} Nov{dimensionless} Dec{dimensionless}
1 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20


Site:GroundReflectance:SnowModifier

Normal Daylighting {dimensionless}
1 1.000 1.000


Site:GroundReflectance:Snow

Jan{dimensionless} Feb{dimensionless} Mar{dimensionless} Apr{dimensionless} May{dimensionless} Jun{dimensionless} Jul{dimensionless} Aug{dimensionless} Sep{dimensionless} Oct{dimensionless} Nov{dimensionless} Dec{dimensionless}
1 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20


Site:GroundReflectance:Snow:Daylighting

Jan{dimensionless} Feb{dimensionless} Mar{dimensionless} Apr{dimensionless} May{dimensionless} Jun{dimensionless} Jul{dimensionless} Aug{dimensionless} Sep{dimensionless} Oct{dimensionless} Nov{dimensionless} Dec{dimensionless}
1 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20


Environment:Weather Station

Wind Sensor Height Above Ground {m} Wind Speed Profile Exponent {} Wind Speed Profile Boundary Layer Thickness {m} Air Temperature Sensor Height Above Ground {m} Wind Speed Modifier Coefficient-Internal Temperature Modifier Coefficient-Internal
1 10.000 0.140 270.000 1.500 1.586 9.750E-003


Site:Location

Location Name Latitude {N+/S- Deg} Longitude {E+/W- Deg} Time Zone Number {GMT+/-} Elevation {m} Standard Pressure at Elevation {Pa} Standard RhoAir at Elevation
1 Buffalo Niagara Intl AP NY USA TMY3 WMO#=725280 42.93 -78.73 -5.00 215.00 98769 1.1739


Site Water Mains Temperature Information

Calculation Method{} Water Mains Temperature Schedule Name{} Annual Average Outdoor Air Temperature{C} Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} Fixed Default Water Mains Temperature{C}
1 Correlation NA 8.97 26.20 NA


Building Information

Building Name North Axis {deg} Terrain Loads Convergence Tolerance Value Temperature Convergence Tolerance Value Solar Distribution Maximum Number of Warmup Days Minimum Number of Warmup Days
1 OfficeLarge 0.000 City 4.00000E-002 0.20000 FullInteriorAndExterior 25 6


Inside Convection Algorithm

Algorithm {Simple
TARP
CeilingDiffuser
AdaptiveConvectionAlgorithm}
1 TARP


Outside Convection Algorithm

Algorithm {SimpleCombined
TARP
MoWitt
DOE-2
AdaptiveConvectionAlgorithm}
1 TARP


Sky Radiance Distribution

Value {Anisotropic}
1 Anisotropic


Zone Air Solution Algorithm

Value {ThirdOrderBackwardDifference
AnalyticalSolution
EulerMethod}
1 ThirdOrderBackwardDifference


Zone Air Carbon Dioxide Balance Simulation

Simulation {Yes/No} Carbon Dioxide Concentration
1 No N/A


Zone Air Generic Contaminant Balance Simulation

Simulation {Yes/No} Generic Contaminant Concentration
1 No N/A


Zone Air Mass Flow Balance Simulation

Enforce Mass Balance



Adjust Zone Mixing and Return {AdjustMixingOnly
AdjustReturnOnly
AdjustMixingThenReturn
AdjustReturnThenMixing
None}
Adjust Zone Infiltration {AddInfiltration
AdjustInfiltration
None}

Infiltration Zones {MixingSourceZonesOnly
AllZones}


1 No N/A N/A N/A


HVACSystemRootFindingAlgorithm

Value {RegulaFalsi
Bisection
BisectionThenRegulaFalsi
RegulaFalsiThenBisection}
1 RegulaFalsi


Environment:Site Atmospheric Variation

Wind Speed Profile Exponent {} Wind Speed Profile Boundary Layer Thickness {m} Air Temperature Gradient Coefficient {K/m}
1 0.330 460.000 6.500000E-003


Surface Geometry

Starting Corner Vertex Input Direction Coordinate System Daylight Reference Point Coordinate System Rectangular (Simple) Surface Coordinate System
1 UpperLeftCorner Counterclockwise RelativeCoordinateSystem RelativeCoordinateSystem RelativeToZoneOrigin


Surface Heat Transfer Algorithm

Value {CTF - ConductionTransferFunction
EMPD - MoisturePenetrationDepthConductionTransferFunction
CondFD - ConductionFiniteDifference
HAMT - CombinedHeatAndMoistureFiniteElement} - Description
Inside Surface Max Temperature Limit{C}


Surface Convection Coefficient Lower Limit {W/m2-K}


Surface Convection Coefficient Upper Limit {W/m2-K}


1 CTF - ConductionTransferFunction 200 0.10 1000.0


Shading Summary

Number of Fixed Detached Shades Number of Building Detached Shades Number of Attached Shades
1 0 0 0


Zone Summary

Number of Zones Number of Zone Surfaces Number of SubSurfaces
1 23 221 36


Zone Information

Zone Name North Axis {deg} Origin X-Coordinate {m} Origin Y-Coordinate {m} Origin Z-Coordinate {m} Centroid X-Coordinate {m} Centroid Y-Coordinate {m} Centroid Z-Coordinate {m} Type Zone Multiplier Zone List Multiplier Minimum X {m} Maximum X {m} Minimum Y {m} Maximum Y {m} Minimum Z {m} Maximum Z {m} Ceiling Height {m} Volume {m3} Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} Floor Area {m2} Exterior Gross Wall Area {m2} Exterior Net Wall Area {m2} Exterior Window Area {m2} Number of Surfaces Number of SubSurfaces Number of Shading SubSurfaces Part of Total Building Area
1 BASEMENT 0.0 0.00 0.00 0.00 44.59 24.37 -1.22 1 1 1 16.08 73.11 0.00 48.74 -2.44 0.00 2.44 6779.02 TARP TARP 2779.43 0.00 0.00 0.00 9 0 0 Yes
2 CORE_BOTTOM 0.0 0.00 0.00 0.00 37.01 24.37 1.37 1 1 1 5.49 68.53 4.57 44.17 0.00 2.74 2.74 6849.35 TARP TARP 2496.12 0.00 0.00 0.00 7 0 0 Yes
3 CORE_MID 0.0 0.00 0.00 0.00 37.01 24.37 18.14 1 10 1 5.49 68.53 4.57 44.17 16.77 19.51 2.74 6849.35 TARP TARP 2496.12 0.00 0.00 0.00 6 0 0 Yes
4 CORE_TOP 0.0 0.00 0.00 0.00 37.01 24.37 34.91 1 1 1 5.49 68.53 4.57 44.17 33.54 36.28 2.74 6849.35 TARP TARP 2496.12 0.00 0.00 0.00 6 0 0 Yes
5 PERIMETER_BOT_ZN_3 0.0 0.00 0.00 0.00 36.55 46.54 1.37 1 1 1 0.00 73.11 44.17 48.74 0.00 2.74 2.74 860.00 TARP TARP 313.41 200.61 76.91 115.90 8 9 0 Yes
6 PERIMETER_BOT_ZN_2 0.0 0.00 0.00 0.00 70.95 24.37 1.37 1 1 1 68.53 73.11 0.00 48.74 0.00 2.74 2.74 554.22 TARP TARP 201.98 133.74 52.57 77.26 6 5 0 Yes
7 PERIMETER_BOT_ZN_1 0.0 0.00 0.00 0.00 36.55 2.20 1.37 1 1 1 0.00 73.11 0.00 4.57 0.00 2.74 2.74 860.02 TARP TARP 313.42 200.61 76.91 115.90 8 9 0 Yes
8 PERIMETER_BOT_ZN_4 0.0 0.00 0.00 0.00 2.16 24.37 1.37 1 1 1 0.00 4.57 0.00 48.74 0.00 2.74 2.74 554.22 TARP TARP 201.98 133.74 52.57 77.26 6 5 0 Yes
9 PERIMETER_MID_ZN_3 0.0 0.00 0.00 0.00 36.55 46.54 18.14 1 10 1 0.00 73.11 44.17 48.74 16.77 19.51 2.74 860.00 TARP TARP 313.41 200.61 84.71 115.90 7 1 0 Yes
10 PERIMETER_MID_ZN_2 0.0 0.00 0.00 0.00 70.95 24.37 18.14 1 10 1 68.53 73.11 0.00 48.74 16.77 19.51 2.74 554.22 TARP TARP 201.98 133.74 56.47 77.26 6 1 0 Yes
11 PERIMETER_MID_ZN_1 0.0 0.00 0.00 0.00 36.55 2.20 18.14 1 10 1 0.00 73.11 0.00 4.57 16.77 19.51 2.74 860.02 TARP TARP 313.42 200.61 84.71 115.90 7 1 0 Yes
12 PERIMETER_MID_ZN_4 0.0 0.00 0.00 0.00 2.16 24.37 18.14 1 10 1 0.00 4.57 0.00 48.74 16.77 19.51 2.74 554.22 TARP TARP 201.98 133.74 56.47 77.26 6 1 0 Yes
13 PERIMETER_TOP_ZN_3 0.0 0.00 0.00 0.00 36.55 46.54 34.91 1 1 1 0.00 73.11 44.17 48.74 33.54 36.28 2.74 860.00 TARP TARP 313.41 200.61 84.71 115.90 7 1 0 Yes
14 PERIMETER_TOP_ZN_2 0.0 0.00 0.00 0.00 70.95 24.37 34.91 1 1 1 68.53 73.11 0.00 48.74 33.54 36.28 2.74 554.22 TARP TARP 201.98 133.74 56.47 77.26 6 1 0 Yes
15 PERIMETER_TOP_ZN_1 0.0 0.00 0.00 0.00 36.55 2.20 34.91 1 1 1 0.00 73.11 0.00 4.57 33.54 36.28 2.74 860.02 TARP TARP 313.42 200.61 84.71 115.90 7 1 0 Yes
16 PERIMETER_TOP_ZN_4 0.0 0.00 0.00 0.00 2.16 24.37 34.91 1 1 1 0.00 4.57 0.00 48.74 33.54 36.28 2.74 554.22 TARP TARP 201.98 133.74 56.47 77.26 6 1 0 Yes
17 GROUNDFLOOR_PLENUM 0.0 0.00 0.00 0.00 36.55 24.37 3.35 1 1 1 0.00 73.11 0.00 48.74 2.74 3.96 1.22 4344.14 TARP TARP 3563.11 297.11 297.11 0.00 11 0 0 No
18 MIDFLOOR_PLENUM 0.0 0.00 0.00 0.00 36.55 24.37 20.12 1 10 1 0.00 73.11 0.00 48.74 19.51 20.73 1.22 4344.14 TARP TARP 3563.11 297.11 297.11 0.00 11 0 0 No
19 TOPFLOOR_PLENUM 0.0 0.00 0.00 0.00 36.55 24.37 36.89 1 1 1 0.00 73.11 0.00 48.74 36.28 37.50 1.22 4344.14 TARP TARP 3563.11 297.11 297.11 0.00 11 0 0 No
20 DATACENTER_BOT_ZN_6 0.0 5.49 44.17 0.00 5.03 24.37 1.37 1 1 1 4.57 5.49 4.57 44.17 0.00 2.74 2.74 99.34 TARP TARP 36.20 0.00 0.00 0.00 6 0 0 Yes
21 DATACENTER_MID_ZN_6 0.0 4.57 4.57 16.77 5.03 24.37 18.14 1 10 1 4.57 5.49 4.57 44.17 16.77 19.51 2.74 99.34 TARP TARP 36.20 0.00 0.00 0.00 6 0 0 Yes
22 DATACENTER_TOP_ZN_6 0.0 4.57 4.57 33.54 5.03 24.37 34.91 1 1 1 4.57 5.49 4.57 44.17 33.54 36.28 2.74 99.34 TARP TARP 36.20 0.00 0.00 0.00 6 0 0 Yes
23 DATACENTER_BASEMENT_ZN_6 0.0 16.08 0.00 -2.44 8.04 24.37 -1.22 1 1 1 0.00 16.08 0.00 48.74 -2.44 0.00 2.44 1911.37 TARP TARP 783.68 0.00 0.00 0.00 10 0 0 Yes


Zone Internal Gains Nominal

Zone Name Floor Area {m2} # Occupants Area per Occupant {m2/person} Occupant per Area {person/m2} Interior Lighting {W/m2} Electric Load {W/m2} Gas Load {W/m2} Other Load {W/m2} Hot Water Eq {W/m2} Steam Equipment {W/m2} Sum Loads per Area {W/m2} Outdoor Controlled Baseboard Heat
1 BASEMENT 2779.43 149.6 18.579 5.382E-002 10.273 4.842 0.000 0.000 0.000 0.000 15.115 No
2 CORE_BOTTOM 2496.12 134.4 18.579 5.382E-002 10.273 8.070 0.000 0.000 0.000 0.000 18.343 No
3 CORE_MID 2496.12 134.4 18.579 5.382E-002 10.273 8.070 0.000 0.000 0.000 0.000 18.343 No
4 CORE_TOP 2496.12 134.4 18.579 5.382E-002 10.273 8.070 0.000 0.000 0.000 0.000 18.343 No
5 PERIMETER_BOT_ZN_3 313.41 16.9 18.579 5.382E-002 10.273 8.070 0.000 0.000 0.000 0.000 18.343 No
6 PERIMETER_BOT_ZN_2 201.98 10.9 18.579 5.382E-002 10.273 8.070 0.000 0.000 0.000 0.000 18.343 No
7 PERIMETER_BOT_ZN_1 313.42 16.9 18.579 5.382E-002 10.273 8.070 0.000 0.000 0.000 0.000 18.343 No
8 PERIMETER_BOT_ZN_4 201.98 10.9 18.579 5.382E-002 10.273 8.070 0.000 0.000 0.000 0.000 18.343 No
9 PERIMETER_MID_ZN_3 313.41 16.9 18.579 5.382E-002 10.273 8.070 0.000 0.000 0.000 0.000 18.343 No
10 PERIMETER_MID_ZN_2 201.98 10.9 18.579 5.382E-002 10.273 8.070 0.000 0.000 0.000 0.000 18.343 No
11 PERIMETER_MID_ZN_1 313.42 16.9 18.579 5.382E-002 10.273 8.070 0.000 0.000 0.000 0.000 18.343 No
12 PERIMETER_MID_ZN_4 201.98 10.9 18.579 5.382E-002 10.273 8.070 0.000 0.000 0.000 0.000 18.343 No
13 PERIMETER_TOP_ZN_3 313.41 16.9 18.579 5.382E-002 10.273 8.070 0.000 0.000 0.000 0.000 18.343 No
14 PERIMETER_TOP_ZN_2 201.98 10.9 18.579 5.382E-002 10.273 8.070 0.000 0.000 0.000 0.000 18.343 No
15 PERIMETER_TOP_ZN_1 313.42 16.9 18.579 5.382E-002 10.273 8.070 0.000 0.000 0.000 0.000 18.343 No
16 PERIMETER_TOP_ZN_4 201.98 10.9 18.579 5.382E-002 10.273 8.070 0.000 0.000 0.000 0.000 18.343 No
17 GROUNDFLOOR_PLENUM 3563.11 0.0 N/A 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 No
18 MIDFLOOR_PLENUM 3563.11 0.0 N/A 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 No
19 TOPFLOOR_PLENUM 3563.11 0.0 N/A 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 No
20 DATACENTER_BOT_ZN_6 36.20 1.9 18.579 5.382E-002 17.873 215.299 0.000 0.000 0.000 0.000 233.173 No
21 DATACENTER_MID_ZN_6 36.20 1.9 18.579 5.382E-002 17.873 215.299 0.000 0.000 0.000 0.000 233.173 No
22 DATACENTER_TOP_ZN_6 36.20 1.9 18.579 5.382E-002 17.873 215.299 0.000 0.000 0.000 0.000 233.173 No
23 DATACENTER_BASEMENT_ZN_6 783.68 42.2 18.579 5.382E-002 10.273 484.423 0.000 0.000 0.000 0.000 494.696 No


People Internal Gains Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Number of People {} People/Floor Area {person/m2} Floor Area per person {m2/person} Fraction Radiant Fraction Convected Sensible Fraction Calculation Activity level ASHRAE 55 Warnings Carbon Dioxide Generation Rate Nominal Minimum Number of People Nominal Maximum Number of People MRT Calculation Type Work Efficiency Clothing Insulation Calculation Method Clothing Insulation Calculation Method Schedule Clothing Air Velocity Fanger Calculation Pierce Calculation KSU Calculation Cooling Effect Calculation Ankle Draft Calculation
1 DATACENTER_BOT_ZN_6 BLDG_OCC_SCH_WO_SB DATACENTER_BOT_ZN_6 36.20 1.9 1.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
2 DATACENTER_MID_ZN_6 BLDG_OCC_SCH_WO_SB DATACENTER_MID_ZN_6 36.20 1.9 1.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
3 DATACENTER_TOP_ZN_6 BLDG_OCC_SCH_WO_SB DATACENTER_TOP_ZN_6 36.20 1.9 1.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
4 DATACENTER_BASEMENT_ZN_6 BLDG_OCC_SCH_WO_SB DATACENTER_BASEMENT_ZN_6 783.68 42.2 42.2 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 42 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
5 BASEMENT BLDG_OCC_SCH_WO_SB BASEMENT 2779.43 149.6 149.6 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 150 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
6 CORE_BOTTOM BLDG_OCC_SCH_WO_SB CORE_BOTTOM 2496.12 134.4 134.4 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 134 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
7 CORE_MID BLDG_OCC_SCH_WO_SB CORE_MID 2496.12 134.4 134.4 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 134 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
8 CORE_TOP BLDG_OCC_SCH_WO_SB CORE_TOP 2496.12 134.4 134.4 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 134 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
9 PERIMETER_BOT_ZN_3 BLDG_OCC_SCH_WO_SB PERIMETER_BOT_ZN_3 313.41 16.9 16.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 17 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
10 PERIMETER_BOT_ZN_2 BLDG_OCC_SCH_WO_SB PERIMETER_BOT_ZN_2 201.98 10.9 10.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 11 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
11 PERIMETER_BOT_ZN_1 BLDG_OCC_SCH_WO_SB PERIMETER_BOT_ZN_1 313.42 16.9 16.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 17 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
12 PERIMETER_BOT_ZN_4 BLDG_OCC_SCH_WO_SB PERIMETER_BOT_ZN_4 201.98 10.9 10.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 11 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
13 PERIMETER_MID_ZN_3 BLDG_OCC_SCH_WO_SB PERIMETER_MID_ZN_3 313.41 16.9 16.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 17 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
14 PERIMETER_MID_ZN_2 BLDG_OCC_SCH_W_SB PERIMETER_MID_ZN_2 201.98 10.9 10.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 11 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
15 PERIMETER_MID_ZN_1 BLDG_OCC_SCH_WO_SB PERIMETER_MID_ZN_1 313.42 16.9 16.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 17 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
16 PERIMETER_MID_ZN_4 BLDG_OCC_SCH_WO_SB PERIMETER_MID_ZN_4 201.98 10.9 10.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 11 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
17 PERIMETER_TOP_ZN_3 BLDG_OCC_SCH_WO_SB PERIMETER_TOP_ZN_3 313.41 16.9 16.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 17 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
18 PERIMETER_TOP_ZN_2 BLDG_OCC_SCH_WO_SB PERIMETER_TOP_ZN_2 201.98 10.9 10.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 11 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
19 PERIMETER_TOP_ZN_1 BLDG_OCC_SCH_WO_SB PERIMETER_TOP_ZN_1 313.42 16.9 16.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 17 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
20 PERIMETER_TOP_ZN_4 BLDG_OCC_SCH_WO_SB PERIMETER_TOP_ZN_4 201.98 10.9 10.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 11 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No


Lights Internal Gains Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Lighting Level {W} Lights/Floor Area {W/m2} Lights per person {W/person} Fraction Return Air Fraction Radiant Fraction Short Wave Fraction Convected Fraction Replaceable End-Use Category Nominal Minimum Lighting Level {W} Nominal Maximum Lighting Level {W}
1 BASEMENT_LIGHTS LTG_SCH_OFFICE BASEMENT 2779.43 149.6 28553.717 10.273 190.864 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 28553.717
2 CORE_BOTTOM_LIGHTS LTG_SCH_OFFICE CORE_BOTTOM 2496.12 134.4 25643.245 10.273 190.864 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 25643.245
3 CORE_MID_LIGHTS LTG_SCH_OFFICE CORE_MID 2496.12 134.4 25643.245 10.273 190.864 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 25643.245
4 CORE_TOP_LIGHTS LTG_SCH_OFFICE CORE_TOP 2496.12 134.4 25643.245 10.273 190.864 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 25643.245
5 PERIMETER_BOT_ZN_3_LIGHTS LTG_SCH_OFFICE PERIMETER_BOT_ZN_3 313.41 16.9 3219.765 10.273 190.864 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 3219.765
6 PERIMETER_BOT_ZN_2_LIGHTS LTG_SCH_OFFICE PERIMETER_BOT_ZN_2 201.98 10.9 2074.939 10.273 190.864 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 2074.939
7 PERIMETER_BOT_ZN_1_LIGHTS LTG_SCH_OFFICE PERIMETER_BOT_ZN_1 313.42 16.9 3219.836 10.273 190.864 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 3219.836
8 PERIMETER_BOT_ZN_4_LIGHTS LTG_SCH_OFFICE PERIMETER_BOT_ZN_4 201.98 10.9 2074.939 10.273 190.864 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 2074.939
9 PERIMETER_MID_ZN_3_LIGHTS LTG_SCH_OFFICE PERIMETER_MID_ZN_3 313.41 16.9 3219.765 10.273 190.864 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 3219.765
10 PERIMETER_MID_ZN_2_LIGHTS LTG_SCH_OFFICE PERIMETER_MID_ZN_2 201.98 10.9 2074.939 10.273 190.864 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 2074.939
11 PERIMETER_MID_ZN_1_LIGHTS LTG_SCH_OFFICE PERIMETER_MID_ZN_1 313.42 16.9 3219.836 10.273 190.864 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 3219.836
12 PERIMETER_MID_ZN_4_LIGHTS LTG_SCH_OFFICE PERIMETER_MID_ZN_4 201.98 10.9 2074.939 10.273 190.864 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 2074.939
13 PERIMETER_TOP_ZN_3_LIGHTS LTG_SCH_OFFICE PERIMETER_TOP_ZN_3 313.41 16.9 3219.765 10.273 190.864 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 3219.765
14 PERIMETER_TOP_ZN_2_LIGHTS LTG_SCH_OFFICE PERIMETER_TOP_ZN_2 201.98 10.9 2074.939 10.273 190.864 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 2074.939
15 PERIMETER_TOP_ZN_1_LIGHTS LTG_SCH_OFFICE PERIMETER_TOP_ZN_1 313.42 16.9 3219.836 10.273 190.864 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 3219.836
16 PERIMETER_TOP_ZN_4_LIGHTS LTG_SCH_OFFICE PERIMETER_TOP_ZN_4 201.98 10.9 2074.939 10.273 190.864 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 2074.939
17 DATACENTER_BASEMENT_LIGHTS LTG_SCH_OFFICE DATACENTER_BASEMENT_ZN_6 783.68 42.2 8050.927 10.273 190.864 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 8050.927
18 DATACENTER_BOT_LIGHTS LTG_SCH_DATACENTER DATACENTER_BOT_ZN_6 36.20 1.9 647.068 17.873 332.067 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 647.068
19 DATACENTER_MID_LIGHTS LTG_SCH_DATACENTER DATACENTER_MID_ZN_6 36.20 1.9 647.068 17.873 332.067 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 647.068
20 DATACENTER_TOP_LIGHTS LTG_SCH_DATACENTER DATACENTER_TOP_ZN_6 36.20 1.9 647.068 17.873 332.067 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 647.068


ElectricEquipment Internal Gains Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Equipment Level {W} Equipment/Floor Area {W/m2} Equipment per person {W/person} Fraction Latent Fraction Radiant Fraction Lost Fraction Convected End-Use SubCategory Nominal Minimum Equipment Level {W} Nominal Maximum Equipment Level {W}
1 BASEMENT_MISCPLUG_EQUIP ALWAYS_ON BASEMENT 2779.43 149.6 13457.544 4.842 89.956 0.000 0.500 0.000 0.500 MiscPlug 13457.544 13457.544
2 CORE_BOTTOM_MISCPLUG_EQUIP BLDG_EQUIP_SCH CORE_BOTTOM 2496.12 134.4 20142.877 8.070 149.925 0.000 0.500 0.000 0.500 MiscPlug 0.000 20142.877
3 CORE_MID_MISCPLUG_EQUIP BLDG_EQUIP_SCH CORE_MID 2496.12 134.4 20142.800 8.070 149.924 0.000 0.500 0.000 0.500 MiscPlug 0.000 20142.800
4 CORE_TOP_MISCPLUG_EQUIP BLDG_EQUIP_SCH CORE_TOP 2496.12 134.4 20142.800 8.070 149.924 0.000 0.500 0.000 0.500 MiscPlug 0.000 20142.800
5 PERIMETER_BOT_ZN_3_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_BOT_ZN_3 313.41 16.9 2529.242 8.070 149.931 0.000 0.500 0.000 0.500 MiscPlug 0.000 2529.242
6 PERIMETER_BOT_ZN_2_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_BOT_ZN_2 201.98 10.9 1629.940 8.070 149.931 0.000 0.500 0.000 0.500 MiscPlug 0.000 1629.940
7 PERIMETER_BOT_ZN_1_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_BOT_ZN_1 313.42 16.9 2529.281 8.070 149.930 0.000 0.500 0.000 0.500 MiscPlug 0.000 2529.281
8 PERIMETER_BOT_ZN_4_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_BOT_ZN_4 201.98 10.9 1629.929 8.070 149.930 0.000 0.500 0.000 0.500 MiscPlug 0.000 1629.929
9 PERIMETER_MID_ZN_3_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_MID_ZN_3 313.41 16.9 2529.242 8.070 149.931 0.000 0.500 0.000 0.500 MiscPlug 0.000 2529.242
10 PERIMETER_MID_ZN_2_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_MID_ZN_2 201.98 10.9 1629.940 8.070 149.931 0.000 0.500 0.000 0.500 MiscPlug 0.000 1629.940
11 PERIMETER_MID_ZN_1_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_MID_ZN_1 313.42 16.9 2529.281 8.070 149.930 0.000 0.500 0.000 0.500 MiscPlug 0.000 2529.281
12 PERIMETER_MID_ZN_4_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_MID_ZN_4 201.98 10.9 1629.929 8.070 149.930 0.000 0.500 0.000 0.500 MiscPlug 0.000 1629.929
13 PERIMETER_TOP_ZN_3_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_TOP_ZN_3 313.41 16.9 2529.242 8.070 149.931 0.000 0.500 0.000 0.500 MiscPlug 0.000 2529.242
14 PERIMETER_TOP_ZN_2_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_TOP_ZN_2 201.98 10.9 1629.940 8.070 149.931 0.000 0.500 0.000 0.500 MiscPlug 0.000 1629.940
15 PERIMETER_TOP_ZN_1_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_TOP_ZN_1 313.42 16.9 2529.281 8.070 149.930 0.000 0.500 0.000 0.500 MiscPlug 0.000 2529.281
16 PERIMETER_TOP_ZN_4_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_TOP_ZN_4 201.98 10.9 1629.929 8.070 149.930 0.000 0.500 0.000 0.500 MiscPlug 0.000 1629.929
17 DATACENTER_BASEMENT_MISCPLUG_EQUIP DATACENTER_EQUIP_SCH DATACENTER_BASEMENT_ZN_6 783.68 42.2 379632.522 484.423 9000.000 0.000 0.100 0.000 0.900 DataCenterPlugLoads 94908.130 379632.522
18 DATACENTER_BOT_MISCPLUG_EQUIP DATACENTER_EQUIP_SCH DATACENTER_BOT_ZN_6 36.20 1.9 7794.422 215.299 4000.000 0.000 0.100 0.000 0.900 DataCenterPlugLoads 1948.606 7794.422
19 DATACENTER_MID_MISCPLUG_EQUIP DATACENTER_EQUIP_SCH DATACENTER_MID_ZN_6 36.20 1.9 7794.422 215.299 4000.000 0.000 0.100 0.000 0.900 DataCenterPlugLoads 1948.606 7794.422
20 DATACENTER_TOP_MISCPLUG_EQUIP DATACENTER_EQUIP_SCH DATACENTER_TOP_ZN_6 36.20 1.9 7794.422 215.299 4000.000 0.000 0.100 0.000 0.900 DataCenterPlugLoads 1948.606 7794.422


Construction CTF

Construction Name Index #Layers #CTFs Time Step {hours} ThermalConductance {w/m2-K} OuterThermalAbsorptance InnerThermalAbsorptance OuterSolarAbsorptance InnerSolarAbsorptance Roughness
1 SWINGING DOOR_CON 1 1 1 0.167 2.839 0.900 0.900 0.700 0.700 MediumRough
2 INTERIORFURNISHINGS 2 1 9 0.167 0.8000 0.900 0.900 0.700 0.700 MediumSmooth
3 DROPCEILING 4 1 3 0.167 4.488 0.900 0.900 0.700 0.700 MediumSmooth
4 INT_WALL 7 2 4 0.167 6.299 0.900 0.900 0.700 0.700 Smooth
5 EXT_SLAB_8IN_WITH_CARPET 8 2 7 0.167 3.285 0.900 0.900 0.700 0.700 MediumRough
6 INT_SLAB_FLOOR 12 2 7 0.167 3.839 0.900 0.900 0.700 0.700 MediumRough
7 INT_SLAB_CEILING 13 2 7 0.167 3.839 0.900 0.900 0.700 0.700 VeryRough
8 NONRES_ROOF 17 3 3 0.167 0.1864 0.900 0.900 0.700 0.700 Rough
9 NONRES_EXT_WALL_GRD 20 3 9 0.167 0.9689 0.900 0.900 0.700 0.700 MediumRough
10 NONRES_EXT_WALL_MID 21 3 9 0.167 0.9235 0.900 0.900 0.700 0.700 MediumRough
11 NONRES_EXT_WALL_TOP 22 3 9 0.167 1.155 0.900 0.900 0.700 0.700 MediumRough
12 BASEMENT_WALL_EAST_CFACTOR 39 2 7 0.167 0.4185 0.000 0.900 0.000 0.700 MediumRough
13 BASEMENT_WALL_SOUTH_CFACTOR 40 2 7 0.167 0.4185 0.000 0.900 0.000 0.700 MediumRough
14 BASEMENT_WALL_NORTH_CFACTOR 41 2 7 0.167 0.4185 0.000 0.900 0.000 0.700 MediumRough
15 DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR 42 2 7 0.167 0.4185 0.000 0.900 0.000 0.700 MediumRough
16 DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR 43 2 7 0.167 0.4185 0.000 0.900 0.000 0.700 MediumRough
17 DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR 44 2 7 0.167 0.4185 0.000 0.900 0.000 0.700 MediumRough


Material CTF Summary

Material Name Thickness {m} Conductivity {w/m-K} Density {kg/m3} Specific Heat {J/kg-K} ThermalResistance {m2-K/w}
1 OPAQUE DOOR PANEL_CON 0.0000 0.000 0.000 0.000 0.3522
2 STD WOOD 6INCH 0.1500 0.120 540.000 1210.000 1.250
3 AC02 ACOUSTIC CEILING 0.0127 0.057 288.000 1339.000 0.2228
4 G01 13MM GYPSUM BOARD 0.0127 0.160 800.000 1090.000 0.7937E-01
5 G01 13MM GYPSUM BOARD 0.0127 0.160 800.000 1090.000 0.7937E-01
6 200MM NORMALWEIGHT CONCRETE FLOOR 0.2032 2.310 2322.000 832.000 0.8797E-01
7 CP02 CARPET PAD 0.0000 0.000 0.000 0.000 0.2165
8 100MM NORMALWEIGHT CONCRETE FLOOR 0.1016 2.310 2322.000 832.000 0.4398E-01
9 CP02 CARPET PAD 0.0000 0.000 0.000 0.000 0.2165
10 CP02 CARPET PAD 0.0000 0.000 0.000 0.000 0.2165
11 100MM NORMALWEIGHT CONCRETE FLOOR 0.1016 2.310 2322.000 832.000 0.4398E-01
12 F13 BUILT-UP ROOFING 0.0095 0.160 1120.000 1460.000 0.5938E-01
13 NONRES_ROOF_INSULATION 0.0000 0.000 0.000 0.000 5.307
14 F08 METAL SURFACE 0.0008 45.280 7824.000 500.000 0.1767E-04
15 200MM NORMALWEIGHT CONCRETE WALL 0.2032 2.310 2322.000 832.000 0.8797E-01
16 NONRES_EXTERIOR_WALL_INSULATION_GRD 0.0000 0.000 0.000 0.000 0.8647
17 G01 13MM GYPSUM BOARD 0.0127 0.160 800.000 1090.000 0.7937E-01
18 200MM NORMALWEIGHT CONCRETE WALL 0.2032 2.310 2322.000 832.000 0.8797E-01
19 NONRES_EXTERIOR_WALL_INSULATION_MID 0.0000 0.000 0.000 0.000 0.9155
20 G01 13MM GYPSUM BOARD 0.0127 0.160 800.000 1090.000 0.7937E-01
21 200MM NORMALWEIGHT CONCRETE WALL 0.2032 2.310 2322.000 832.000 0.8797E-01
22 NONRES_EXTERIOR_WALL_INSULATION_TOP 0.0000 0.000 0.000 0.000 0.6987
23 G01 13MM GYPSUM BOARD 0.0127 0.160 800.000 1090.000 0.7937E-01
24 ~FC_Insulation_1 0.0000 0.000 0.000 0.000 2.312
25 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
26 ~FC_Insulation_2 0.0000 0.000 0.000 0.000 2.312
27 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
28 ~FC_Insulation_3 0.0000 0.000 0.000 0.000 2.312
29 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
30 ~FC_Insulation_4 0.0000 0.000 0.000 0.000 2.312
31 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
32 ~FC_Insulation_5 0.0000 0.000 0.000 0.000 2.312
33 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
34 ~FC_Insulation_6 0.0000 0.000 0.000 0.000 2.312
35 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01


CTF

Time Outside Cross Inside Flux (except final one)
1 1 0.0000000 0.0000000 -0.0000000 -0.0000000
2 0 2.8391315 2.8391315 2.8391315  
3 9 -0.27580628E-02 0.97439125E-12 -0.27580628E-02 0.28516790E-03
4 8 0.73590997E-01 0.21837543E-08 0.73590997E-01 -0.77836043E-02
5 7 -0.82599318 0.23162835E-06 -0.82599318 0.89703933E-01
6 6 5.1113916 0.48671053E-05 5.1113916 -0.57224845
7 5 -19.214933 0.30163627E-04 -19.214933 2.2266322
8 4 45.557404 0.63181060E-04 45.557404 -5.4853312
9 3 -68.275533 0.44785456E-04 -68.275533 8.5710568
10 2 62.555368 0.93952058E-05 62.555368 -8.2111738
11 1 -31.904423 0.39200004E-06 -31.904423 4.3886678
12 0 6.9260389 0.77047546E-09 6.9260389  
13 3 -0.21589802E-09 0.15643069E-09 -0.21589802E-09 0.12999471E-21
14 2 0.50772448E-02 0.30006816E-02 0.50772448E-02 -0.13693132E-08
15 1 -2.5944910 1.4597758 -2.5944910 0.76344767E-02
16 0 7.0433378 2.9911476 7.0433378  
17 4 0.68458728E-09 0.26079551E-09 0.68458728E-09 -0.34507121E-18
18 3 -0.72180374E-03 0.24295686E-03 -0.72180374E-03 0.69691454E-09
19 2 0.83054762 0.27682775 0.83054762 -0.35168967E-03
20 1 -12.650482 3.3590720 -12.650482 0.19281313
21 0 16.907513 1.4507143 16.907513  
22 7 -0.18651654E-16 -0.16428647E-15 -0.26578847E-08 -0.25364002E-17
23 6 0.67402962E-01 0.99142722E-07 0.38101547E-02 -0.76639482E-03
24 5 -1.8580732 0.49502125E-04 -0.10651409 0.21891119E-01
25 4 18.220105 0.12801333E-02 1.0775450 -0.22586539
26 3 -79.928293 0.66708484E-02 -4.9803755 1.0625663
27 2 166.43177 0.75131194E-02 11.128837 -2.4125483
28 1 -159.97298 0.18548900E-02 -11.587784 2.5494418
29 0 57.057412 0.52755123E-04 4.4818272  
30 7 0.43260499E-16 0.34524919E-16 0.52793240E-17 0.0000000
31 6 0.69434179E-09 0.98085174E-11 0.18162501E-10 -0.40870994E-12
32 5 -0.12888762E-04 0.28373718E-06 -0.16918523E-06 0.92361873E-08
33 4 0.25174112E-01 0.33697681E-03 0.22646198E-03 -0.31467795E-04
34 3 -3.7600775 0.27170599E-01 -0.48495626E-01 0.94171705E-02
35 2 51.553741 0.22121684 1.2284947 -0.25833933
36 1 -128.86110 0.21944682 -5.1479470 1.1228340
37 0 81.526494 0.16043334E-01 4.4519351  
38 7 0.52793240E-17 0.34524919E-16 0.43260499E-16 0.0000000
39 6 0.18162501E-10 0.98085174E-11 0.69434179E-09 -0.40870994E-12
40 5 -0.16918523E-06 0.28373718E-06 -0.12888762E-04 0.92361873E-08
41 4 0.22646198E-03 0.33697681E-03 0.25174112E-01 -0.31467795E-04
42 3 -0.48495626E-01 0.27170599E-01 -3.7600775 0.94171705E-02
43 2 1.2284947 0.22121684 51.553741 -0.25833933
44 1 -5.1479470 0.21944682 -128.86110 1.1228340
45 0 4.4519351 0.16043334E-01 81.526494  
46 3 -0.62854340E-06 0.84784826E-09 -0.38512804E-05 0.91756347E-17
47 2 0.78257096 0.11428808E-02 1.0614277 -0.73836085E-06
48 1 -21.991499 0.76199851E-01 -6.3161914 0.20349372
49 0 21.357363 0.71091016E-01 5.4032014  
50 9 -0.61082983E-15 0.35276446E-16 -0.14787207E-09 0.18036823E-17
51 8 0.21615122E-07 0.13022774E-12 0.37506347E-03 -0.24577139E-09
52 7 -0.12160115E-01 0.67804000E-08 -0.22968555E-01 0.13826493E-03
53 6 0.40313748 0.23652218E-05 0.47020644 -0.47216777E-02
54 5 -5.1689687 0.88520675E-04 -4.4267872 0.62916081E-01
55 4 32.907337 0.72566064E-03 21.383769 -0.42085466
56 3 -111.02301 0.15845227E-02 -55.512186 1.5122587
57 2 196.92983 0.89280554E-03 77.772262 -2.8975199
58 1 -171.09018 0.95459611E-04 -55.224854 2.7442846
59 0 57.057407 0.54436501E-06 15.563573  
60 9 -0.28033836E-14 0.31423843E-16 -0.15000593E-09 0.49342508E-16
61 8 0.21915022E-07 0.12441777E-12 0.37821899E-03 -0.24918134E-09
62 7 -0.12254290E-01 0.64567074E-08 -0.23104155E-01 0.13933574E-03
63 6 0.40569641 0.22493722E-05 0.47238617 -0.47518414E-02
64 5 -5.1939411 0.84090406E-04 -4.4435303 0.63225727E-01
65 4 33.017798 0.68864468E-03 21.449218 -0.42232128
66 3 -111.25804 0.15023393E-02 -55.641580 1.5156542
67 2 197.16277 0.84581883E-03 77.890928 -2.9012190
68 1 -171.17623 0.90368420E-04 -55.259345 2.7457926
69 0 57.057407 0.51494858E-06 15.557864  
70 9 0.16475985E-14 0.40698495E-16 -0.13909959E-09 -0.62647149E-17
71 8 0.20378875E-07 0.15355384E-12 0.36189576E-03 -0.23171482E-09
72 7 -0.11766586E-01 0.81065314E-08 -0.22401745E-01 0.13379037E-03
73 6 0.39244372 0.28436739E-05 0.46108386 -0.45956244E-02
74 5 -5.0645996 0.10693990E-03 -4.3566540 0.61621961E-01
75 4 32.445620 0.88045565E-03 21.109484 -0.41472443
76 3 -110.04047 0.19299305E-02 -54.969854 1.4980638
77 2 195.95581 0.10911488E-02 77.275137 -2.8820526
78 1 -170.73031 0.11703553E-03 -55.080813 2.7379774
79 0 57.057407 0.66971377E-06 15.587784  
80 7 -0.98583555E-09 -0.79843648E-16 0.12056005E-14 0.46388562E-17
81 6 0.11736010E-04 0.80964505E-08 0.31724491E-02 -0.26613162E-04
82 5 -0.85155955E-03 0.48044989E-05 -0.22273424 0.19474091E-02
83 4 0.19629464E-01 0.21887653E-03 4.8130477 -0.45106395E-01
84 3 -0.17247723 0.17421542E-02 -37.928201 0.39762344
85 2 0.61254091 0.29000861E-02 116.30250 -1.4155123
86 1 -0.88416489 0.88473762E-03 -143.80049 2.0472841
87 0 0.43108349 0.21254961E-04 60.838472  
88 7 -0.98583555E-09 -0.79843648E-16 0.12056005E-14 0.46388562E-17
89 6 0.11736010E-04 0.80964505E-08 0.31724491E-02 -0.26613162E-04
90 5 -0.85155955E-03 0.48044989E-05 -0.22273424 0.19474091E-02
91 4 0.19629464E-01 0.21887653E-03 4.8130477 -0.45106395E-01
92 3 -0.17247723 0.17421542E-02 -37.928201 0.39762344
93 2 0.61254091 0.29000861E-02 116.30250 -1.4155123
94 1 -0.88416489 0.88473762E-03 -143.80049 2.0472841
95 0 0.43108349 0.21254961E-04 60.838472  
96 7 -0.98583555E-09 -0.79843648E-16 0.12056005E-14 0.46388562E-17
97 6 0.11736010E-04 0.80964505E-08 0.31724491E-02 -0.26613162E-04
98 5 -0.85155955E-03 0.48044989E-05 -0.22273424 0.19474091E-02
99 4 0.19629464E-01 0.21887653E-03 4.8130477 -0.45106395E-01
100 3 -0.17247723 0.17421542E-02 -37.928201 0.39762344
101 2 0.61254091 0.29000861E-02 116.30250 -1.4155123
102 1 -0.88416489 0.88473762E-03 -143.80049 2.0472841
103 0 0.43108349 0.21254961E-04 60.838472  
104 7 -0.98583555E-09 -0.79843648E-16 0.12056005E-14 0.46388562E-17
105 6 0.11736010E-04 0.80964505E-08 0.31724491E-02 -0.26613162E-04
106 5 -0.85155955E-03 0.48044989E-05 -0.22273424 0.19474091E-02
107 4 0.19629464E-01 0.21887653E-03 4.8130477 -0.45106395E-01
108 3 -0.17247723 0.17421542E-02 -37.928201 0.39762344
109 2 0.61254091 0.29000861E-02 116.30250 -1.4155123
110 1 -0.88416489 0.88473762E-03 -143.80049 2.0472841
111 0 0.43108349 0.21254961E-04 60.838472  
112 7 -0.98583555E-09 -0.79843648E-16 0.12056005E-14 0.46388562E-17
113 6 0.11736010E-04 0.80964505E-08 0.31724491E-02 -0.26613162E-04
114 5 -0.85155955E-03 0.48044989E-05 -0.22273424 0.19474091E-02
115 4 0.19629464E-01 0.21887653E-03 4.8130477 -0.45106395E-01
116 3 -0.17247723 0.17421542E-02 -37.928201 0.39762344
117 2 0.61254091 0.29000861E-02 116.30250 -1.4155123
118 1 -0.88416489 0.88473762E-03 -143.80049 2.0472841
119 0 0.43108349 0.21254961E-04 60.838472  
120 7 -0.98583555E-09 -0.79843648E-16 0.12056005E-14 0.46388562E-17
121 6 0.11736010E-04 0.80964505E-08 0.31724491E-02 -0.26613162E-04
122 5 -0.85155955E-03 0.48044989E-05 -0.22273424 0.19474091E-02
123 4 0.19629464E-01 0.21887653E-03 4.8130477 -0.45106395E-01
124 3 -0.17247723 0.17421542E-02 -37.928201 0.39762344
125 2 0.61254091 0.29000861E-02 116.30250 -1.4155123
126 1 -0.88416489 0.88473762E-03 -143.80049 2.0472841
127 0 0.43108349 0.21254961E-04 60.838472  


WindowConstruction

Construction Name Index #Layers Roughness Conductance {W/m2-K} Conductance (Before Adjusted) {W/m2-K} Convection Coefficient Adjustment Ratio SHGC Solar Transmittance at Normal Incidence Visible Transmittance at Normal Incidence
1 WINDOW_U_0.419_SHGC_EAST_0.4 35 1 VerySmooth 2.381 2.381 1.000 0.401    
2 WINDOW_U_0.419_SHGC_SOUTH_0.4 36 1 VerySmooth 2.381 2.381 1.000 0.401    
3 WINDOW_U_0.419_SHGC_WEST_0.4 37 1 VerySmooth 2.381 2.381 1.000 0.401    
4 WINDOW_U_0.419_SHGC_NORTH_0.4 38 1 VerySmooth 2.381 2.381 1.000 0.401    


WindowMaterial:Glazing

Material Name Optical Data Type Spectral Data Set Name Thickness {m} Solar Transmittance Front Solar Reflectance Back Solar Reflectance Visible Transmittance Front Visible Reflectance Back Visible Reflectance Infrared Transmittance Front Thermal Emissivity Back Thermal Emissivity Conductivity {W/m-K} Dirt Factor Solar Diffusing
1 GLAZING LAYER EAST SpectralAverage   3.03930E-002 0.31435 0.47506 0.47506 0.44000 0.13397 0.17027 0.00000 0.84000 0.84000 0.12237 1.00000 No
2 GLAZING LAYER SOUTH SpectralAverage   3.03930E-002 0.31435 0.47506 0.47506 0.44000 0.13397 0.17027 0.00000 0.84000 0.84000 0.12237 1.00000 No
3 GLAZING LAYER WEST SpectralAverage   3.03930E-002 0.31435 0.47506 0.47506 0.44000 0.13397 0.17027 0.00000 0.84000 0.84000 0.12237 1.00000 No
4 GLAZING LAYER NORTH SpectralAverage   3.03930E-002 0.31435 0.47506 0.47506 0.44000 0.13397 0.17027 0.00000 0.84000 0.84000 0.12237 1.00000 No


Shadowing/Sun Position Calculations Annual Simulations

Shading Calculation Method Shading Calculation Update Frequency Method Shading Calculation Update Frequency {days} Maximum Figures in Shadow Overlap Calculations {} Polygon Clipping Algorithm Pixel Counting Resolution Sky Diffuse Modeling Algorithm Output External Shading Calculation Results Disable Self-Shading Within Shading Zone Groups Disable Self-Shading From Shading Zone Groups to Other Zones
1 PolygonClipping Periodic 30 15000 SutherlandHodgman 512 SimpleSkyDiffuseModeling No No No


Enclosure/Window Adjacency Daylighting Counts

Enclosure Name Number of Exterior Windows Number of Exterior Windows in Adjacent Enclosures
1 PERIMETER_BOT_ZN_3 5 0
2 PERIMETER_BOT_ZN_2 3 0
3 PERIMETER_BOT_ZN_1 5 0
4 PERIMETER_BOT_ZN_4 3 0
5 PERIMETER_MID_ZN_3 1 0
6 PERIMETER_MID_ZN_2 1 0
7 PERIMETER_MID_ZN_1 1 0
8 PERIMETER_MID_ZN_4 1 0
9 PERIMETER_TOP_ZN_3 1 0
10 PERIMETER_TOP_ZN_2 1 0
11 PERIMETER_TOP_ZN_1 1 0
12 PERIMETER_TOP_ZN_4 1 0


Enclosure/Window Adjacency Daylighting Matrix

Enclosure Name Number of Adjacent Enclosures with Windows Adjacent Enclosure Names - 1st 100 (max)
1 PERIMETER_BOT_ZN_3 0  
2 PERIMETER_BOT_ZN_2 0  
3 PERIMETER_BOT_ZN_1 0  
4 PERIMETER_BOT_ZN_4 0  
5 PERIMETER_MID_ZN_3 0  
6 PERIMETER_MID_ZN_2 0  
7 PERIMETER_MID_ZN_1 0  
8 PERIMETER_MID_ZN_4 0  
9 PERIMETER_TOP_ZN_3 0  
10 PERIMETER_TOP_ZN_2 0  
11 PERIMETER_TOP_ZN_1 0  
12 PERIMETER_TOP_ZN_4 0  


Water Heater Information

Type Name Volume {m3} Maximum Capacity {W} Standard Rated Recovery Efficiency Standard Rated Energy Factor
1 WaterHeater:Mixed SWHSYS1 WATER HEATER 1.1356 87921.3 0.481 5.5005E-002


Surface Convection Parameters

Surface Name Outside Model Assignment Outside Area [m2] Outside Perimeter [m] Outside Height [m] Inside Model Assignment Inside Height [m] Inside Perimeter Envelope [m] Inside Hydraulic Diameter [m] Window Wall Ratio Window Location Near Radiant {Yes/No} Has Active HVAC {Yes/No}
1 BASEMENT_WALL_EAST 0 0.00 0.00 0.00 0 2.44 0.00 52.56 -999.00 0 No No
2 BASEMENT_WALL_SOUTH 0 0.00 0.00 0.00 0 2.44 0.00 52.56 -999.00 0 No No
3 BASEMENT_WALL_NORTH 0 0.00 0.00 0.00 0 2.44 0.00 52.56 -999.00 0 No No
4 BASEMENT_WALL_WEST 0 0.00 0.00 0.00 0 2.44 0.00 52.56 -999.00 0 No No
5 BASEMENT_FLOOR 0 0.00 0.00 0.00 0 2.44 0.00 52.56 -999.00 0 No No
6 PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.44 0.00 52.56 -999.00 0 No No
7 PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.44 0.00 52.56 -999.00 0 No No
8 CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.44 0.00 52.56 -999.00 0 No No
9 PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.44 0.00 52.56 -999.00 0 No No
10 BASEMENT_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.44 0.00 52.56 -999.00 0 No No
11 CORE_BOT_ZN_5_WALL_SOUTH 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
12 CORE_BOT_ZN_5_WALL_WEST 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
13 CORE_BOT_ZN_5_WALL_NORTH 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
14 CORE_BOT_ZN_5_WALL_EAST 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
15 DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
16 CORE_BOT_ZN_5_FLOOR 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
17 CORE_BOT_ZN_5_CEILING 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
18 CORE_BOTTOM_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
19 CORE_MID_ZN_5_WALL_SOUTH 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
20 CORE_MID_ZN_5_WALL_WEST 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
21 CORE_MID_ZN_5_WALL_NORTH 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
22 CORE_MID_ZN_5_WALL_EAST 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
23 CORE_MID_ZN_5_FLOOR 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
24 CORE_MID_ZN_5_CEILING 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
25 CORE_MID_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
26 CORE_TOP_ZN_5_WALL_SOUTH 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
27 CORE_TOP_ZN_5_WALL_WEST 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
28 CORE_TOP_ZN_5_WALL_NORTH 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
29 CORE_TOP_ZN_5_WALL_EAST 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
30 CORE_TOP_ZN_5_FLOOR 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
31 CORE_TOP_ZN_5_CEILING 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
32 CORE_TOP_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
33 PERIMETER_BOT_ZN_3_WALL_NORTH 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.58 3 No No
34 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.58 5 No No
35 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.58 5 No No
36 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.58 5 No No
37 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.58 5 No No
38 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.58 5 No No
39 PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.58 0 No No
40 PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.58 0 No No
41 PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.58 0 No No
42 PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.58 0 No No
43 PERIMETER_BOT_ZN_3_WALL_WEST 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
44 CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
45 PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
46 DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
47 PERIMETER_BOT_ZN_3_FLOOR 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
48 DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
49 PERIMETER_BOT_ZN_3_CEILING 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
50 PERIMETER_BOT_ZN_3_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
51 PERIMETER_BOT_ZN_2_WALL_EAST 0 579.48 250.73 37.50 0 2.74 48.74 7.58 0.58 3 No No
52 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 0 579.48 250.73 37.50 0 2.74 48.74 7.58 0.58 5 No No
53 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 0 579.48 250.73 37.50 0 2.74 48.74 7.58 0.58 5 No No
54 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 0 579.48 250.73 37.50 0 2.74 48.74 7.58 0.58 5 No No
55 PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 0 579.48 250.73 37.50 0 2.74 48.74 7.58 0.58 0 No No
56 PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 0 579.48 250.73 37.50 0 2.74 48.74 7.58 0.58 0 No No
57 PERIMETER_BOT_ZN_2_WALL_NORTH 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
58 CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
59 PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
60 PERIMETER_BOT_ZN_2_FLOOR 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
61 PERIMETER_BOT_ZN_2_CEILING 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
62 PERIMETER_BOT_ZN_2_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
63 PERIMETER_BOT_ZN_1_WALL_SOUTH 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.58 3 No No
64 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.58 5 No No
65 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.58 5 No No
66 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.58 5 No No
67 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.58 5 No No
68 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.58 5 No No
69 PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.58 0 No No
70 PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.58 0 No No
71 PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.58 0 No No
72 PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.58 0 No No
73 PERIMETER_BOT_ZN_1_WALL_EAST 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
74 DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
75 PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
76 CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
77 DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
78 PERIMETER_BOT_ZN_1_FLOOR 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
79 PERIMETER_BOT_ZN_1_CEILING 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
80 PERIMETER_BOT_ZN_1_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
81 PERIMETER_BOT_ZN_4_WALL_WEST 0 579.48 172.48 37.50 0 2.74 48.74 7.58 0.58 3 No No
82 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 0 579.48 172.48 37.50 0 2.74 48.74 7.58 0.58 5 No No
83 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 0 579.48 172.48 37.50 0 2.74 48.74 7.58 0.58 5 No No
84 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 0 579.48 172.48 37.50 0 2.74 48.74 7.58 0.58 5 No No
85 PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 0 579.48 172.48 37.50 0 2.74 48.74 7.58 0.58 0 No No
86 PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 0 579.48 172.48 37.50 0 2.74 48.74 7.58 0.58 0 No No
87 PERIMETER_BOT_ZN_4_WALL_SOUTH 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
88 DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
89 PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
90 PERIMETER_BOT_ZN_4_FLOOR 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
91 PERIMETER_BOT_ZN_4_CEILING 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
92 PERIMETER_BOT_ZN_4_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
93 PERIMETER_MID_ZN_3_WALL_NORTH 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.58 3 No No
94 PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.58 5 No No
95 PERIMETER_MID_ZN_3_WALL_WEST 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
96 CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
97 PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
98 DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
99 PERIMETER_MID_ZN_3_FLOOR 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
100 PERIMETER_MID_ZN_3_CEILING 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
101 PERIMETER_MID_ZN_3_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
102 PERIMETER_MID_ZN_2_WALL_EAST 0 579.48 250.73 37.50 0 2.74 48.74 7.58 0.58 3 No No
103 PERIMETER_MID_ZN_2_WALL_EAST_WINDOW 0 579.48 250.73 37.50 0 2.74 48.74 7.58 0.58 5 No No
104 PERIMETER_MID_ZN_2_WALL_NORTH 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
105 CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
106 PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
107 PERIMETER_MID_ZN_2_FLOOR 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
108 PERIMETER_MID_ZN_2_CEILING 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
109 PERIMETER_MID_ZN_2_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
110 PERIMETER_MID_ZN_1_WALL_EAST 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
111 PERIMETER_MID_ZN_1_WALL_SOUTH 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.58 3 No No
112 PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.58 5 No No
113 DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
114 PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
115 CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
116 PERIMETER_MID_ZN_1_FLOOR 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
117 PERIMETER_MID_ZN_1_CEILING 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
118 PERIMETER_MID_ZN_1_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
119 PERIMETER_MID_ZN_4_WALL_WEST 0 579.48 172.48 37.50 0 2.74 48.74 7.58 0.58 3 No No
120 PERIMETER_MID_ZN_4_WALL_WEST_WINDOW 0 579.48 172.48 37.50 0 2.74 48.74 7.58 0.58 5 No No
121 PERIMETER_MID_ZN_4_WALL_SOUTH 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
122 DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
123 PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
124 PERIMETER_MID_ZN_4_FLOOR 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
125 PERIMETER_MID_ZN_4_CEILING 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
126 PERIMETER_MID_ZN_4_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
127 PERIMETER_TOP_ZN_3_WALL_NORTH 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.58 3 No No
128 PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.58 5 No No
129 PERIMETER_TOP_ZN_3_WALL_WEST 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
130 CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
131 PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
132 DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
133 PERIMETER_TOP_ZN_3_FLOOR 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
134 PERIMETER_TOP_ZN_3_CEILING 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
135 PERIMETER_TOP_ZN_3_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
136 PERIMETER_TOP_ZN_2_WALL_EAST 0 579.48 250.73 37.50 0 2.74 48.74 7.58 0.58 3 No No
137 PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW 0 579.48 250.73 37.50 0 2.74 48.74 7.58 0.58 5 No No
138 PERIMETER_TOP_ZN_2_WALL_NORTH 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
139 CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
140 INT-PER3S-NE-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
141 PERIMETER_TOP_ZN_2_FLOOR 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
142 PERIMETER_TOP_ZN_2_CEILING 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
143 PERIMETER_TOP_ZN_2_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
144 PERIMETER_TOP_ZN_1_WALL_SOUTH 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.58 3 No No
145 PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.58 5 No No
146 INT-PER3S-NE 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
147 DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
148 PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
149 CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
150 PERIMETER_TOP_ZN_1_FLOOR 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
151 PERIMETER_TOP_ZN_1_CEILING 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
152 PERIMETER_TOP_ZN_1_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
153 PERIMETER_TOP_ZN_4_WALL_WEST 0 579.48 172.48 37.50 0 2.74 48.74 7.58 0.58 3 No No
154 PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW 0 579.48 172.48 37.50 0 2.74 48.74 7.58 0.58 5 No No
155 PERIMETER_TOP_ZN_4_WALL_SOUTH 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
156 DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
157 PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
158 PERIMETER_TOP_ZN_4_FLOOR 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
159 PERIMETER_TOP_ZN_4_CEILING 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
160 PERIMETER_TOP_ZN_4_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
161 GROUNDFLOOR_PLENUM_WALL_NORTH 0 869.22 250.73 37.50 0 1.22 243.69 58.49 0.00 0 No No
162 GROUNDFLOOR_PLENUM_WEST 0 579.48 172.48 37.50 0 1.22 243.69 58.49 0.00 0 No No
163 GROUNDFLOOR_PLENUM_WALL_SOUTH 0 869.22 221.21 37.50 0 1.22 243.69 58.49 0.00 0 No No
164 GROUNDFLOOR_PLENUM_WALL_EAST 0 579.48 250.73 37.50 0 1.22 243.69 58.49 0.00 0 No No
165 iz-CORE_BOT_ZN_5_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
166 iz-PERIMETER_BOT_ZN_3_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
167 iz-PERIMETER_BOT_ZN_2_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
168 iz-PERIMETER_BOT_ZN_1_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
169 iz-PERIMETER_BOT_ZN_4_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
170 iz-DATACENTER_BOT_ZN_6_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
171 GROUNDFLOOR_PLENUM_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
172 MIDFLOOR_PLENUM_WALL_NORTH 0 869.22 250.73 37.50 0 1.22 243.69 58.49 0.00 0 No No
173 MIDFLOOR_PLENUM_WALL_WEST 0 579.48 172.48 37.50 0 1.22 243.69 58.49 0.00 0 No No
174 MIDFLOOR_PLENUM_WALL_SOUTH 0 869.22 221.21 37.50 0 1.22 243.69 58.49 0.00 0 No No
175 MIDFLOOR_PLENUM_WALL_EAST 0 579.48 250.73 37.50 0 1.22 243.69 58.49 0.00 0 No No
176 iz-CORE_MID_ZN_5_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
177 iz-PERIMETER_MID_ZN_3_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
178 iz-PERIMETER_MID_ZN_2_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
179 iz-PERIMETER_MID_ZN_1_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
180 iz-PERIMETER_MID_ZN_4_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
181 iz-DATACENTER_MID_ZN_6_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
182 MIDFLOOR_PLENUM_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
183 TOPFLOOR_PLENUM_WALL_NORTH 0 869.22 221.21 37.50 0 1.22 243.69 58.49 0.00 0 No No
184 TOPFLOOR_PLENUM_WALL_EAST 0 579.48 250.73 37.50 0 1.22 243.69 58.49 0.00 0 No No
185 TOPFLOOR_PLENUM_WALL_WEST 0 579.48 172.48 37.50 0 1.22 243.69 58.49 0.00 0 No No
186 TOPFLOOR_PLENUM_WALL_SOUTH 0 869.22 250.73 37.50 0 1.22 243.69 58.49 0.00 0 No No
187 iz-CORE_TOP_ZN_5_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
188 iz-PERIMETER_TOP_ZN_3_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
189 iz-PERIMETER_TOP_ZN_2_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
190 iz-PERIMETER_TOP_ZN_1_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
191 iz-PERIMETER_TOP_ZN_4_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
192 iz-DATACENTER_TOP_ZN_6_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
193 BUILDING_ROOF 0 3563.11 268.06 0.00 0 1.22 243.69 58.49 0.00 0 No No
194 DATACENTER_BOT_ZN_6_WALL_NORTH 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
195 DATACENTER_BOT_ZN_6_WALL_SOUTH 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
196 DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
197 DATACENTER_BOT_ZN_6_WALL_WEST 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
198 DATACENTER_BOT_ZN_6_FLOOR 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
199 DATACENTER_BOT_ZN_6_CEILING 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
200 DATACENTER_MID_ZN_6_WALL_WEST 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
201 DATACENTER_MID_ZN_6_WALL_SOUTH 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
202 DATACENTER_MID_ZN_6_WALL_EAST 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
203 DATACENTER_MID_ZN_6_WALL_NORTH 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
204 DATACENTER_MID_ZN_6_FLOOR 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
205 DATACENTER_MID_ZN_6_CEILING 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
206 DATACENTER_TOP_ZN_6_WALL_EAST 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
207 DATACENTER_TOP_ZN_6_WALL_WEST 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
208 DATACENTER_TOP_ZN_6_WALL_SOUTH 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
209 DATACENTER_TOP_ZN_6_WALL_NORTH 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
210 DATACENTER_TOP_ZN_6_FLOOR 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
211 DATACENTER_TOP_ZN_6_CEILING 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
212 DATACENTER_BASEMENT_ZN_6_WALL_NORTH 0 0.00 0.00 0.00 0 2.44 0.00 24.18 -999.00 0 No No
213 DATACENTER_BASEMENT_ZN_6_WALL_SOUTH 0 0.00 0.00 0.00 0 2.44 0.00 24.18 -999.00 0 No No
214 DATACENTER_BASEMENT_ZN_6_WALL_WEST 0 0.00 0.00 0.00 0 2.44 0.00 24.18 -999.00 0 No No
215 DATACENTER_BASEMENT_ZN_6_WALL_EAST 0 0.00 0.00 0.00 0 2.44 0.00 24.18 -999.00 0 No No
216 DATACENTER_BASEMENT_ZN_6_FLOOR 0 0.00 0.00 0.00 0 2.44 0.00 24.18 -999.00 0 No No
217 DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.44 0.00 24.18 -999.00 0 No No
218 DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 0 0.00 0.00 0.00 0 2.44 0.00 24.18 -999.00 0 No No
219 PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.44 0.00 24.18 -999.00 0 No No
220 DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 0 0.00 0.00 0.00 0 2.44 0.00 24.18 -999.00 0 No No
221 DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 0 0.00 0.00 0.00 0 2.44 0.00 24.18 -999.00 0 No No


ZoneInfiltration Airflow Stats Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Design Volume Flow Rate {m3/s} Volume Flow Rate/Floor Area {m3/s-m2} Volume Flow Rate/Exterior Surface Area {m3/s-m2} ACH - Air Changes per Hour Equation A - Constant Term Coefficient {} Equation B - Temperature Term Coefficient {1/C} Equation C - Velocity Term Coefficient {s/m} Equation D - Velocity Squared Term Coefficient {s2/m2}
1 PERIMETER_BOT_ZN_3_INFILTRATION INFIL_SCH_PNNL PERIMETER_BOT_ZN_3 313.41 16.9 0.114 3.646E-004 5.482E-004 0.478 0.000 0.000 0.224 0.000
2 PERIMETER_BOT_ZN_2_INFILTRATION INFIL_SCH_PNNL PERIMETER_BOT_ZN_2 201.98 10.9 7.617E-002 3.771E-004 5.534E-004 0.495 0.000 0.000 0.224 0.000
3 PERIMETER_BOT_ZN_1_INFILTRATION INFIL_SCH_PNNL PERIMETER_BOT_ZN_1 313.42 16.9 0.114 3.646E-004 5.482E-004 0.478 0.000 0.000 0.224 0.000
4 PERIMETER_BOT_ZN_4_INFILTRATION INFIL_SCH_PNNL PERIMETER_BOT_ZN_4 201.98 10.9 7.617E-002 3.771E-004 5.534E-004 0.495 0.000 0.000 0.224 0.000
5 PERIMETER_MID_ZN_3_INFILTRATION INFIL_SCH_PNNL PERIMETER_MID_ZN_3 313.41 16.9 0.114 3.646E-004 5.696E-004 0.478 0.000 0.000 0.224 0.000
6 PERIMETER_MID_ZN_2_INFILTRATION INFIL_SCH_PNNL PERIMETER_MID_ZN_2 201.98 10.9 7.617E-002 3.771E-004 5.696E-004 0.495 0.000 0.000 0.224 0.000
7 PERIMETER_MID_ZN_1_INFILTRATION INFIL_SCH_PNNL PERIMETER_MID_ZN_1 313.42 16.9 0.114 3.646E-004 5.696E-004 0.478 0.000 0.000 0.224 0.000
8 PERIMETER_MID_ZN_4_INFILTRATION INFIL_SCH_PNNL PERIMETER_MID_ZN_4 201.98 10.9 7.617E-002 3.771E-004 5.696E-004 0.495 0.000 0.000 0.224 0.000
9 PERIMETER_TOP_ZN_3_INFILTRATION INFIL_SCH_PNNL PERIMETER_TOP_ZN_3 313.41 16.9 0.114 3.646E-004 5.696E-004 0.478 0.000 0.000 0.224 0.000
10 PERIMETER_TOP_ZN_2_INFILTRATION INFIL_SCH_PNNL PERIMETER_TOP_ZN_2 201.98 10.9 7.617E-002 3.771E-004 5.696E-004 0.495 0.000 0.000 0.224 0.000
11 PERIMETER_TOP_ZN_1_INFILTRATION INFIL_SCH_PNNL PERIMETER_TOP_ZN_1 313.42 16.9 0.114 3.646E-004 5.696E-004 0.478 0.000 0.000 0.224 0.000
12 PERIMETER_TOP_ZN_4_INFILTRATION INFIL_SCH_PNNL PERIMETER_TOP_ZN_4 201.98 10.9 7.617E-002 3.771E-004 5.696E-004 0.495 0.000 0.000 0.224 0.000
13 GROUNDFLOOR_PLENUM_INFILTRATION INFIL_SCH_PNNL GROUNDFLOOR_PLENUM 3563.11 0.0 0.169 4.749E-005 5.696E-004 0.140 0.000 0.000 0.224 0.000
14 MIDFLOOR_PLENUM_INFILTRATION INFIL_SCH_PNNL MIDFLOOR_PLENUM 3563.11 0.0 0.169 4.749E-005 5.696E-004 0.140 0.000 0.000 0.224 0.000
15 TOPFLOOR_PLENUM_INFILTRATION INFIL_SCH_PNNL TOPFLOOR_PLENUM 3563.11 0.0 0.169 4.749E-005 4.384E-005 0.140 0.000 0.000 0.224 0.000


AirFlow Model

Simple
1 Simple


RoomAir Model

Zone Name Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined
1 BASEMENT Mixing/Well-Stirred
2 CORE_BOTTOM Mixing/Well-Stirred
3 CORE_MID Mixing/Well-Stirred
4 CORE_TOP Mixing/Well-Stirred
5 PERIMETER_BOT_ZN_3 Mixing/Well-Stirred
6 PERIMETER_BOT_ZN_2 Mixing/Well-Stirred
7 PERIMETER_BOT_ZN_1 Mixing/Well-Stirred
8 PERIMETER_BOT_ZN_4 Mixing/Well-Stirred
9 PERIMETER_MID_ZN_3 Mixing/Well-Stirred
10 PERIMETER_MID_ZN_2 Mixing/Well-Stirred
11 PERIMETER_MID_ZN_1 Mixing/Well-Stirred
12 PERIMETER_MID_ZN_4 Mixing/Well-Stirred
13 PERIMETER_TOP_ZN_3 Mixing/Well-Stirred
14 PERIMETER_TOP_ZN_2 Mixing/Well-Stirred
15 PERIMETER_TOP_ZN_1 Mixing/Well-Stirred
16 PERIMETER_TOP_ZN_4 Mixing/Well-Stirred
17 GROUNDFLOOR_PLENUM Mixing/Well-Stirred
18 MIDFLOOR_PLENUM Mixing/Well-Stirred
19 TOPFLOOR_PLENUM Mixing/Well-Stirred
20 DATACENTER_BOT_ZN_6 Mixing/Well-Stirred
21 DATACENTER_MID_ZN_6 Mixing/Well-Stirred
22 DATACENTER_TOP_ZN_6 Mixing/Well-Stirred
23 DATACENTER_BASEMENT_ZN_6 Mixing/Well-Stirred


AirflowNetwork Model:Control

No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation
1 NoMultizoneOrDistribution


Zone Volume Capacitance Multiplier

Sensible Heat Capacity Multiplier Moisture Capacity Multiplier Carbon Dioxide Capacity Multiplier Generic Contaminant Capacity Multiplier
1 1.000 1.000 1.000 1.000


Load Timesteps in Zone Design Calculation Averaging Window

Value
1 6


Heating Sizing Factor Information

Sizing Factor ID Value
1 Global 1.0000


Cooling Sizing Factor Information

Sizing Factor ID Value
1 Global 1.0000


Sky Daylight Factors

Sky Type MonthAndDay Daylighting Control Name Enclosure Name Window Name Reference Point Daylight Factor
1 Clear Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 PERIMETER_BOT_ZN_1_DAYLREFPT1 7.3739E-003
2 Clear Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 PERIMETER_BOT_ZN_1_DAYLREFPT2 7.3762E-003
3 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 PERIMETER_BOT_ZN_1_DAYLREFPT1 8.1480E-003
4 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 PERIMETER_BOT_ZN_1_DAYLREFPT2 8.1499E-003
5 Intermediate Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 PERIMETER_BOT_ZN_1_DAYLREFPT1 5.0354E-003
6 Intermediate Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 PERIMETER_BOT_ZN_1_DAYLREFPT2 5.0369E-003
7 Overcast Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 PERIMETER_BOT_ZN_1_DAYLREFPT1 2.7740E-003
8 Overcast Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 PERIMETER_BOT_ZN_1_DAYLREFPT2 2.7748E-003
9 Clear Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 PERIMETER_BOT_ZN_1_DAYLREFPT1 7.4268E-003
10 Clear Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 PERIMETER_BOT_ZN_1_DAYLREFPT2 7.5806E-003
11 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 PERIMETER_BOT_ZN_1_DAYLREFPT1 8.1923E-003
12 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 PERIMETER_BOT_ZN_1_DAYLREFPT2 8.3256E-003
13 Intermediate Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 PERIMETER_BOT_ZN_1_DAYLREFPT1 5.0729E-003
14 Intermediate Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 PERIMETER_BOT_ZN_1_DAYLREFPT2 5.1838E-003
15 Overcast Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 PERIMETER_BOT_ZN_1_DAYLREFPT1 2.7969E-003
16 Overcast Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 PERIMETER_BOT_ZN_1_DAYLREFPT2 2.8551E-003
17 Clear Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 PERIMETER_BOT_ZN_1_DAYLREFPT1 0.1789
18 Clear Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 PERIMETER_BOT_ZN_1_DAYLREFPT2 9.0286E-002
19 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 PERIMETER_BOT_ZN_1_DAYLREFPT1 0.2032
20 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 PERIMETER_BOT_ZN_1_DAYLREFPT2 0.1026
21 Intermediate Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 PERIMETER_BOT_ZN_1_DAYLREFPT1 0.1230
22 Intermediate Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 PERIMETER_BOT_ZN_1_DAYLREFPT2 4.9575E-002
23 Overcast Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 PERIMETER_BOT_ZN_1_DAYLREFPT1 5.0165E-002
24 Overcast Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 PERIMETER_BOT_ZN_1_DAYLREFPT2 1.7447E-002
25 Clear Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 PERIMETER_BOT_ZN_1_DAYLREFPT1 7.4355E-003
26 Clear Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 PERIMETER_BOT_ZN_1_DAYLREFPT2 7.6262E-003
27 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 PERIMETER_BOT_ZN_1_DAYLREFPT1 8.2018E-003
28 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 PERIMETER_BOT_ZN_1_DAYLREFPT2 8.3755E-003
29 Intermediate Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 PERIMETER_BOT_ZN_1_DAYLREFPT1 5.0806E-003
30 Intermediate Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 PERIMETER_BOT_ZN_1_DAYLREFPT2 5.2136E-003
31 Overcast Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 PERIMETER_BOT_ZN_1_DAYLREFPT1 2.7974E-003
32 Overcast Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 PERIMETER_BOT_ZN_1_DAYLREFPT2 2.8568E-003
33 Clear Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 PERIMETER_BOT_ZN_1_DAYLREFPT1 7.3737E-003
34 Clear Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 PERIMETER_BOT_ZN_1_DAYLREFPT2 7.3763E-003
35 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 PERIMETER_BOT_ZN_1_DAYLREFPT1 8.1477E-003
36 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 PERIMETER_BOT_ZN_1_DAYLREFPT2 8.1500E-003
37 Intermediate Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 PERIMETER_BOT_ZN_1_DAYLREFPT1 5.0353E-003
38 Intermediate Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 PERIMETER_BOT_ZN_1_DAYLREFPT2 5.0371E-003
39 Overcast Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 PERIMETER_BOT_ZN_1_DAYLREFPT1 2.7739E-003
40 Overcast Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 PERIMETER_BOT_ZN_1_DAYLREFPT2 2.7747E-003
41 Clear Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 PERIMETER_BOT_ZN_2_DAYLREFPT1 6.5146E-003
42 Clear Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 PERIMETER_BOT_ZN_2_DAYLREFPT2 6.9053E-003
43 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 PERIMETER_BOT_ZN_2_DAYLREFPT1 6.2963E-003
44 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 PERIMETER_BOT_ZN_2_DAYLREFPT2 6.7372E-003
45 Intermediate Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 PERIMETER_BOT_ZN_2_DAYLREFPT1 5.7884E-003
46 Intermediate Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 PERIMETER_BOT_ZN_2_DAYLREFPT2 5.9381E-003
47 Overcast Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 PERIMETER_BOT_ZN_2_DAYLREFPT1 4.7428E-003
48 Overcast Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 PERIMETER_BOT_ZN_2_DAYLREFPT2 4.7830E-003
49 Clear Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 PERIMETER_BOT_ZN_2_DAYLREFPT1 7.4104E-002
50 Clear Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 PERIMETER_BOT_ZN_2_DAYLREFPT2 3.5874E-002
51 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 PERIMETER_BOT_ZN_2_DAYLREFPT1 7.0696E-002
52 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 PERIMETER_BOT_ZN_2_DAYLREFPT2 3.3253E-002
53 Intermediate Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 PERIMETER_BOT_ZN_2_DAYLREFPT1 7.0524E-002
54 Intermediate Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 PERIMETER_BOT_ZN_2_DAYLREFPT2 2.9275E-002
55 Overcast Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 PERIMETER_BOT_ZN_2_DAYLREFPT1 5.2230E-002
56 Overcast Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 PERIMETER_BOT_ZN_2_DAYLREFPT2 1.9536E-002
57 Clear Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 PERIMETER_BOT_ZN_2_DAYLREFPT1 6.3958E-003
58 Clear Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 PERIMETER_BOT_ZN_2_DAYLREFPT2 6.5105E-003
59 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 PERIMETER_BOT_ZN_2_DAYLREFPT1 6.1415E-003
60 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 PERIMETER_BOT_ZN_2_DAYLREFPT2 6.2252E-003
61 Intermediate Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 PERIMETER_BOT_ZN_2_DAYLREFPT1 5.7418E-003
62 Intermediate Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 PERIMETER_BOT_ZN_2_DAYLREFPT2 5.7752E-003
63 Overcast Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 PERIMETER_BOT_ZN_2_DAYLREFPT1 4.7430E-003
64 Overcast Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 PERIMETER_BOT_ZN_2_DAYLREFPT2 4.7836E-003
65 Clear Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 PERIMETER_BOT_ZN_3_DAYLREFPT1 2.9423E-003
66 Clear Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 PERIMETER_BOT_ZN_3_DAYLREFPT2 2.9446E-003
67 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 PERIMETER_BOT_ZN_3_DAYLREFPT1 2.4978E-003
68 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 PERIMETER_BOT_ZN_3_DAYLREFPT2 2.4997E-003
69 Intermediate Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 PERIMETER_BOT_ZN_3_DAYLREFPT1 2.2010E-003
70 Intermediate Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 PERIMETER_BOT_ZN_3_DAYLREFPT2 2.2025E-003
71 Overcast Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 PERIMETER_BOT_ZN_3_DAYLREFPT1 2.7740E-003
72 Overcast Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 PERIMETER_BOT_ZN_3_DAYLREFPT2 2.7749E-003
73 Clear Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 PERIMETER_BOT_ZN_3_DAYLREFPT1 2.9948E-003
74 Clear Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 PERIMETER_BOT_ZN_3_DAYLREFPT2 3.1282E-003
75 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 PERIMETER_BOT_ZN_3_DAYLREFPT1 2.5411E-003
76 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 PERIMETER_BOT_ZN_3_DAYLREFPT2 2.6482E-003
77 Intermediate Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 PERIMETER_BOT_ZN_3_DAYLREFPT1 2.2369E-003
78 Intermediate Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 PERIMETER_BOT_ZN_3_DAYLREFPT2 2.3166E-003
79 Overcast Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 PERIMETER_BOT_ZN_3_DAYLREFPT1 2.7975E-003
80 Overcast Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 PERIMETER_BOT_ZN_3_DAYLREFPT2 2.8569E-003
81 Clear Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 PERIMETER_BOT_ZN_3_DAYLREFPT1 4.7643E-002
82 Clear Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 PERIMETER_BOT_ZN_3_DAYLREFPT2 2.5149E-002
83 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 PERIMETER_BOT_ZN_3_DAYLREFPT1 3.6564E-002
84 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 PERIMETER_BOT_ZN_3_DAYLREFPT2 1.9064E-002
85 Intermediate Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 PERIMETER_BOT_ZN_3_DAYLREFPT1 3.2853E-002
86 Intermediate Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 PERIMETER_BOT_ZN_3_DAYLREFPT2 1.2781E-002
87 Overcast Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 PERIMETER_BOT_ZN_3_DAYLREFPT1 5.0165E-002
88 Overcast Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 PERIMETER_BOT_ZN_3_DAYLREFPT2 1.7442E-002
89 Clear Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 PERIMETER_BOT_ZN_3_DAYLREFPT1 2.9923E-003
90 Clear Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 PERIMETER_BOT_ZN_3_DAYLREFPT2 3.1270E-003
91 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 PERIMETER_BOT_ZN_3_DAYLREFPT1 2.5377E-003
92 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 PERIMETER_BOT_ZN_3_DAYLREFPT2 2.6425E-003
93 Intermediate Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 PERIMETER_BOT_ZN_3_DAYLREFPT1 2.2309E-003
94 Intermediate Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 PERIMETER_BOT_ZN_3_DAYLREFPT2 2.2979E-003
95 Overcast Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 PERIMETER_BOT_ZN_3_DAYLREFPT1 2.7969E-003
96 Overcast Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 PERIMETER_BOT_ZN_3_DAYLREFPT2 2.8551E-003
97 Clear Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 PERIMETER_BOT_ZN_3_DAYLREFPT1 2.9422E-003
98 Clear Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 PERIMETER_BOT_ZN_3_DAYLREFPT2 2.9444E-003
99 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 PERIMETER_BOT_ZN_3_DAYLREFPT1 2.4976E-003
100 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 PERIMETER_BOT_ZN_3_DAYLREFPT2 2.4994E-003
101 Intermediate Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 PERIMETER_BOT_ZN_3_DAYLREFPT1 2.2009E-003
102 Intermediate Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 PERIMETER_BOT_ZN_3_DAYLREFPT2 2.2021E-003
103 Overcast Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 PERIMETER_BOT_ZN_3_DAYLREFPT1 2.7739E-003
104 Overcast Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 PERIMETER_BOT_ZN_3_DAYLREFPT2 2.7748E-003
105 Clear Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 PERIMETER_BOT_ZN_4_DAYLREFPT1 5.6796E-003
106 Clear Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 PERIMETER_BOT_ZN_4_DAYLREFPT2 5.7990E-003
107 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 PERIMETER_BOT_ZN_4_DAYLREFPT1 5.2369E-003
108 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 PERIMETER_BOT_ZN_4_DAYLREFPT2 5.3231E-003
109 Intermediate Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 PERIMETER_BOT_ZN_4_DAYLREFPT1 5.1952E-003
110 Intermediate Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 PERIMETER_BOT_ZN_4_DAYLREFPT2 5.2258E-003
111 Overcast Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 PERIMETER_BOT_ZN_4_DAYLREFPT1 4.7431E-003
112 Overcast Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 PERIMETER_BOT_ZN_4_DAYLREFPT2 4.7837E-003
113 Clear Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 PERIMETER_BOT_ZN_4_DAYLREFPT1 6.1599E-002
114 Clear Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 PERIMETER_BOT_ZN_4_DAYLREFPT2 3.0863E-002
115 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 PERIMETER_BOT_ZN_4_DAYLREFPT1 5.5006E-002
116 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 PERIMETER_BOT_ZN_4_DAYLREFPT2 2.6950E-002
117 Intermediate Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 PERIMETER_BOT_ZN_4_DAYLREFPT1 6.0419E-002
118 Intermediate Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 PERIMETER_BOT_ZN_4_DAYLREFPT2 2.5222E-002
119 Overcast Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 PERIMETER_BOT_ZN_4_DAYLREFPT1 5.2230E-002
120 Overcast Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 PERIMETER_BOT_ZN_4_DAYLREFPT2 1.9536E-002
121 Clear Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 PERIMETER_BOT_ZN_4_DAYLREFPT1 5.7714E-003
122 Clear Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 PERIMETER_BOT_ZN_4_DAYLREFPT2 6.0572E-003
123 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 PERIMETER_BOT_ZN_4_DAYLREFPT1 5.3573E-003
124 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 PERIMETER_BOT_ZN_4_DAYLREFPT2 5.6638E-003
125 Intermediate Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 PERIMETER_BOT_ZN_4_DAYLREFPT1 5.2386E-003
126 Intermediate Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 PERIMETER_BOT_ZN_4_DAYLREFPT2 5.3721E-003
127 Overcast Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 PERIMETER_BOT_ZN_4_DAYLREFPT1 4.7428E-003
128 Overcast Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 PERIMETER_BOT_ZN_4_DAYLREFPT2 4.7829E-003
129 Clear Sky 01/21 PERIMETER_MID_ZN_1_DAYLCTRL PERIMETER_MID_ZN_1 PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW PERIMETER_MID_ZN_1_DAYLREFPT1 0.1796
130 Clear Sky 01/21 PERIMETER_MID_ZN_1_DAYLCTRL PERIMETER_MID_ZN_1 PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW PERIMETER_MID_ZN_1_DAYLREFPT2 0.1245
131 Clear Turbid Sky 01/21 PERIMETER_MID_ZN_1_DAYLCTRL PERIMETER_MID_ZN_1 PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW PERIMETER_MID_ZN_1_DAYLREFPT1 0.1983
132 Clear Turbid Sky 01/21 PERIMETER_MID_ZN_1_DAYLCTRL PERIMETER_MID_ZN_1 PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW PERIMETER_MID_ZN_1_DAYLREFPT2 0.1401
133 Intermediate Sky 01/21 PERIMETER_MID_ZN_1_DAYLCTRL PERIMETER_MID_ZN_1 PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW PERIMETER_MID_ZN_1_DAYLREFPT1 0.1366
134 Intermediate Sky 01/21 PERIMETER_MID_ZN_1_DAYLCTRL PERIMETER_MID_ZN_1 PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW PERIMETER_MID_ZN_1_DAYLREFPT2 7.3226E-002
135 Overcast Sky 01/21 PERIMETER_MID_ZN_1_DAYLCTRL PERIMETER_MID_ZN_1 PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW PERIMETER_MID_ZN_1_DAYLREFPT1 6.1425E-002
136 Overcast Sky 01/21 PERIMETER_MID_ZN_1_DAYLCTRL PERIMETER_MID_ZN_1 PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW PERIMETER_MID_ZN_1_DAYLREFPT2 3.0380E-002
137 Clear Sky 01/21 PERIMETER_MID_ZN_2_DAYLCTRL PERIMETER_MID_ZN_2 PERIMETER_MID_ZN_2_WALL_EAST_WINDOW PERIMETER_MID_ZN_2_DAYLREFPT1 8.8010E-002
138 Clear Sky 01/21 PERIMETER_MID_ZN_2_DAYLCTRL PERIMETER_MID_ZN_2 PERIMETER_MID_ZN_2_WALL_EAST_WINDOW PERIMETER_MID_ZN_2_DAYLREFPT2 5.1534E-002
139 Clear Turbid Sky 01/21 PERIMETER_MID_ZN_2_DAYLCTRL PERIMETER_MID_ZN_2 PERIMETER_MID_ZN_2_WALL_EAST_WINDOW PERIMETER_MID_ZN_2_DAYLREFPT1 8.4229E-002
140 Clear Turbid Sky 01/21 PERIMETER_MID_ZN_2_DAYLCTRL PERIMETER_MID_ZN_2 PERIMETER_MID_ZN_2_WALL_EAST_WINDOW PERIMETER_MID_ZN_2_DAYLREFPT2 4.8446E-002
141 Intermediate Sky 01/21 PERIMETER_MID_ZN_2_DAYLCTRL PERIMETER_MID_ZN_2 PERIMETER_MID_ZN_2_WALL_EAST_WINDOW PERIMETER_MID_ZN_2_DAYLREFPT1 8.3421E-002
142 Intermediate Sky 01/21 PERIMETER_MID_ZN_2_DAYLCTRL PERIMETER_MID_ZN_2 PERIMETER_MID_ZN_2_WALL_EAST_WINDOW PERIMETER_MID_ZN_2_DAYLREFPT2 4.2988E-002
143 Overcast Sky 01/21 PERIMETER_MID_ZN_2_DAYLCTRL PERIMETER_MID_ZN_2 PERIMETER_MID_ZN_2_WALL_EAST_WINDOW PERIMETER_MID_ZN_2_DAYLREFPT1 6.2997E-002
144 Overcast Sky 01/21 PERIMETER_MID_ZN_2_DAYLCTRL PERIMETER_MID_ZN_2 PERIMETER_MID_ZN_2_WALL_EAST_WINDOW PERIMETER_MID_ZN_2_DAYLREFPT2 3.0728E-002
145 Clear Sky 01/21 PERIMETER_MID_ZN_3_DAYLCTRL PERIMETER_MID_ZN_3 PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW PERIMETER_MID_ZN_3_DAYLREFPT1 5.9052E-002
146 Clear Sky 01/21 PERIMETER_MID_ZN_3_DAYLCTRL PERIMETER_MID_ZN_3 PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW PERIMETER_MID_ZN_3_DAYLREFPT2 3.9326E-002
147 Clear Turbid Sky 01/21 PERIMETER_MID_ZN_3_DAYLCTRL PERIMETER_MID_ZN_3 PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW PERIMETER_MID_ZN_3_DAYLREFPT1 4.6512E-002
148 Clear Turbid Sky 01/21 PERIMETER_MID_ZN_3_DAYLCTRL PERIMETER_MID_ZN_3 PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW PERIMETER_MID_ZN_3_DAYLREFPT2 3.1020E-002
149 Intermediate Sky 01/21 PERIMETER_MID_ZN_3_DAYLCTRL PERIMETER_MID_ZN_3 PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW PERIMETER_MID_ZN_3_DAYLREFPT1 4.2452E-002
150 Intermediate Sky 01/21 PERIMETER_MID_ZN_3_DAYLCTRL PERIMETER_MID_ZN_3 PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW PERIMETER_MID_ZN_3_DAYLREFPT2 2.3150E-002
151 Overcast Sky 01/21 PERIMETER_MID_ZN_3_DAYLCTRL PERIMETER_MID_ZN_3 PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW PERIMETER_MID_ZN_3_DAYLREFPT1 6.1425E-002
152 Overcast Sky 01/21 PERIMETER_MID_ZN_3_DAYLCTRL PERIMETER_MID_ZN_3 PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW PERIMETER_MID_ZN_3_DAYLREFPT2 3.0375E-002
153 Clear Sky 01/21 PERIMETER_MID_ZN_4_DAYLCTRL PERIMETER_MID_ZN_4 PERIMETER_MID_ZN_4_WALL_WEST_WINDOW PERIMETER_MID_ZN_4_DAYLREFPT1 7.3869E-002
154 Clear Sky 01/21 PERIMETER_MID_ZN_4_DAYLCTRL PERIMETER_MID_ZN_4 PERIMETER_MID_ZN_4_WALL_WEST_WINDOW PERIMETER_MID_ZN_4_DAYLREFPT2 4.4627E-002
155 Clear Turbid Sky 01/21 PERIMETER_MID_ZN_4_DAYLCTRL PERIMETER_MID_ZN_4 PERIMETER_MID_ZN_4_WALL_WEST_WINDOW PERIMETER_MID_ZN_4_DAYLREFPT1 6.6473E-002
156 Clear Turbid Sky 01/21 PERIMETER_MID_ZN_4_DAYLCTRL PERIMETER_MID_ZN_4 PERIMETER_MID_ZN_4_WALL_WEST_WINDOW PERIMETER_MID_ZN_4_DAYLREFPT2 3.9742E-002
157 Intermediate Sky 01/21 PERIMETER_MID_ZN_4_DAYLCTRL PERIMETER_MID_ZN_4 PERIMETER_MID_ZN_4_WALL_WEST_WINDOW PERIMETER_MID_ZN_4_DAYLREFPT1 7.2102E-002
158 Intermediate Sky 01/21 PERIMETER_MID_ZN_4_DAYLCTRL PERIMETER_MID_ZN_4 PERIMETER_MID_ZN_4_WALL_WEST_WINDOW PERIMETER_MID_ZN_4_DAYLREFPT2 3.7612E-002
159 Overcast Sky 01/21 PERIMETER_MID_ZN_4_DAYLCTRL PERIMETER_MID_ZN_4 PERIMETER_MID_ZN_4_WALL_WEST_WINDOW PERIMETER_MID_ZN_4_DAYLREFPT1 6.2997E-002
160 Overcast Sky 01/21 PERIMETER_MID_ZN_4_DAYLCTRL PERIMETER_MID_ZN_4 PERIMETER_MID_ZN_4_WALL_WEST_WINDOW PERIMETER_MID_ZN_4_DAYLREFPT2 3.0728E-002
161 Clear Sky 01/21 PERIMETER_TOP_ZN_1_DAYLCTRL PERIMETER_TOP_ZN_1 PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW PERIMETER_TOP_ZN_1_DAYLREFPT1 0.1796
162 Clear Sky 01/21 PERIMETER_TOP_ZN_1_DAYLCTRL PERIMETER_TOP_ZN_1 PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW PERIMETER_TOP_ZN_1_DAYLREFPT2 0.1248
163 Clear Turbid Sky 01/21 PERIMETER_TOP_ZN_1_DAYLCTRL PERIMETER_TOP_ZN_1 PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW PERIMETER_TOP_ZN_1_DAYLREFPT1 0.1984
164 Clear Turbid Sky 01/21 PERIMETER_TOP_ZN_1_DAYLCTRL PERIMETER_TOP_ZN_1 PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW PERIMETER_TOP_ZN_1_DAYLREFPT2 0.1404
165 Intermediate Sky 01/21 PERIMETER_TOP_ZN_1_DAYLCTRL PERIMETER_TOP_ZN_1 PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW PERIMETER_TOP_ZN_1_DAYLREFPT1 0.1368
166 Intermediate Sky 01/21 PERIMETER_TOP_ZN_1_DAYLCTRL PERIMETER_TOP_ZN_1 PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW PERIMETER_TOP_ZN_1_DAYLREFPT2 7.3407E-002
167 Overcast Sky 01/21 PERIMETER_TOP_ZN_1_DAYLCTRL PERIMETER_TOP_ZN_1 PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW PERIMETER_TOP_ZN_1_DAYLREFPT1 6.1557E-002
168 Overcast Sky 01/21 PERIMETER_TOP_ZN_1_DAYLCTRL PERIMETER_TOP_ZN_1 PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW PERIMETER_TOP_ZN_1_DAYLREFPT2 3.0447E-002
169 Clear Sky 01/21 PERIMETER_TOP_ZN_2_DAYLCTRL PERIMETER_TOP_ZN_2 PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW PERIMETER_TOP_ZN_2_DAYLREFPT1 8.8074E-002
170 Clear Sky 01/21 PERIMETER_TOP_ZN_2_DAYLCTRL PERIMETER_TOP_ZN_2 PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW PERIMETER_TOP_ZN_2_DAYLREFPT2 5.1615E-002
171 Clear Turbid Sky 01/21 PERIMETER_TOP_ZN_2_DAYLCTRL PERIMETER_TOP_ZN_2 PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW PERIMETER_TOP_ZN_2_DAYLREFPT1 8.4302E-002
172 Clear Turbid Sky 01/21 PERIMETER_TOP_ZN_2_DAYLCTRL PERIMETER_TOP_ZN_2 PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW PERIMETER_TOP_ZN_2_DAYLREFPT2 4.8525E-002
173 Intermediate Sky 01/21 PERIMETER_TOP_ZN_2_DAYLCTRL PERIMETER_TOP_ZN_2 PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW PERIMETER_TOP_ZN_2_DAYLREFPT1 8.3550E-002
174 Intermediate Sky 01/21 PERIMETER_TOP_ZN_2_DAYLCTRL PERIMETER_TOP_ZN_2 PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW PERIMETER_TOP_ZN_2_DAYLREFPT2 4.3080E-002
175 Overcast Sky 01/21 PERIMETER_TOP_ZN_2_DAYLCTRL PERIMETER_TOP_ZN_2 PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW PERIMETER_TOP_ZN_2_DAYLREFPT1 6.3129E-002
176 Overcast Sky 01/21 PERIMETER_TOP_ZN_2_DAYLCTRL PERIMETER_TOP_ZN_2 PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW PERIMETER_TOP_ZN_2_DAYLREFPT2 3.0795E-002
177 Clear Sky 01/21 PERIMETER_TOP_ZN_3_DAYLCTRL PERIMETER_TOP_ZN_3 PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW PERIMETER_TOP_ZN_3_DAYLREFPT1 5.9056E-002
178 Clear Sky 01/21 PERIMETER_TOP_ZN_3_DAYLCTRL PERIMETER_TOP_ZN_3 PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW PERIMETER_TOP_ZN_3_DAYLREFPT2 3.9371E-002
179 Clear Turbid Sky 01/21 PERIMETER_TOP_ZN_3_DAYLCTRL PERIMETER_TOP_ZN_3 PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW PERIMETER_TOP_ZN_3_DAYLREFPT1 4.6520E-002
180 Clear Turbid Sky 01/21 PERIMETER_TOP_ZN_3_DAYLCTRL PERIMETER_TOP_ZN_3 PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW PERIMETER_TOP_ZN_3_DAYLREFPT2 3.1056E-002
181 Intermediate Sky 01/21 PERIMETER_TOP_ZN_3_DAYLCTRL PERIMETER_TOP_ZN_3 PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW PERIMETER_TOP_ZN_3_DAYLREFPT1 4.2519E-002
182 Intermediate Sky 01/21 PERIMETER_TOP_ZN_3_DAYLCTRL PERIMETER_TOP_ZN_3 PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW PERIMETER_TOP_ZN_3_DAYLREFPT2 2.3193E-002
183 Overcast Sky 01/21 PERIMETER_TOP_ZN_3_DAYLCTRL PERIMETER_TOP_ZN_3 PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW PERIMETER_TOP_ZN_3_DAYLREFPT1 6.1557E-002
184 Overcast Sky 01/21 PERIMETER_TOP_ZN_3_DAYLCTRL PERIMETER_TOP_ZN_3 PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW PERIMETER_TOP_ZN_3_DAYLREFPT2 3.0442E-002
185 Clear Sky 01/21 PERIMETER_TOP_ZN_4_DAYLCTRL PERIMETER_TOP_ZN_4 PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW PERIMETER_TOP_ZN_4_DAYLREFPT1 7.3911E-002
186 Clear Sky 01/21 PERIMETER_TOP_ZN_4_DAYLCTRL PERIMETER_TOP_ZN_4 PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW PERIMETER_TOP_ZN_4_DAYLREFPT2 4.4691E-002
187 Clear Turbid Sky 01/21 PERIMETER_TOP_ZN_4_DAYLCTRL PERIMETER_TOP_ZN_4 PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW PERIMETER_TOP_ZN_4_DAYLREFPT1 6.6519E-002
188 Clear Turbid Sky 01/21 PERIMETER_TOP_ZN_4_DAYLCTRL PERIMETER_TOP_ZN_4 PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW PERIMETER_TOP_ZN_4_DAYLREFPT2 3.9800E-002
189 Intermediate Sky 01/21 PERIMETER_TOP_ZN_4_DAYLCTRL PERIMETER_TOP_ZN_4 PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW PERIMETER_TOP_ZN_4_DAYLREFPT1 7.2212E-002
190 Intermediate Sky 01/21 PERIMETER_TOP_ZN_4_DAYLCTRL PERIMETER_TOP_ZN_4 PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW PERIMETER_TOP_ZN_4_DAYLREFPT2 3.7691E-002
191 Overcast Sky 01/21 PERIMETER_TOP_ZN_4_DAYLCTRL PERIMETER_TOP_ZN_4 PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW PERIMETER_TOP_ZN_4_DAYLREFPT1 6.3129E-002
192 Overcast Sky 01/21 PERIMETER_TOP_ZN_4_DAYLCTRL PERIMETER_TOP_ZN_4 PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW PERIMETER_TOP_ZN_4_DAYLREFPT2 3.0795E-002


Zone Sizing Information

Zone Name Load Type Calc Des Load {W} User Des Load {W} Calc Des Air Flow Rate {m3/s} User Des Air Flow Rate {m3/s} Design Day Name Date/Time of Peak Temperature at Peak {C} Humidity Ratio at Peak {kgWater/kgDryAir} Floor Area {m2} # Occupants Calc Outdoor Air Flow Rate {m3/s} Calc DOAS Heat Addition Rate {W}
1 BASEMENT Cooling 82134.63115 82134.63115 6.06748 6.06748 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 23.41800 1.33548E-002 2779.42662 149.60210 1.20016 0.00000
2 BASEMENT Heating 0.00000 0.00000 0.00000 1.20016 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 07:50:00 -16.30000 9.24091E-004 2779.42662 149.60210 1.20016 0.00000
3 CORE_BOTTOM Cooling 85333.38473 85333.38473 6.30311 6.30311 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 23.41800 1.33548E-002 2496.12046 134.35320 1.07782 0.00000
4 CORE_BOTTOM Heating 5020.01379 5020.01379 0.21865 1.07782 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -16.30000 9.24091E-004 2496.12046 134.35320 1.07782 0.00000
5 CORE_MID Cooling 804183.56428 804183.56428 59.38652 59.38652 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 23.41800 1.33548E-002 2496.12046 134.35320 10.77825 0.00000
6 CORE_MID Heating 319656.95957 319656.95957 13.85442 13.85442 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -16.30000 9.24091E-004 2496.12046 134.35320 10.77825 0.00000
7 CORE_TOP Cooling 79543.95055 79543.95055 5.87410 5.87410 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 23.41800 1.33548E-002 2496.12046 134.35320 1.07782 0.00000
8 CORE_TOP Heating 68299.40912 68299.40912 2.97894 2.97894 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -16.30000 9.24091E-004 2496.12046 134.35320 1.07782 0.00000
9 PERIMETER_BOT_ZN_3 Cooling 14136.02701 14136.02701 1.05356 1.05356 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:30:00 30.30000 1.33670E-002 313.41284 16.86939 0.13533 0.00000
10 PERIMETER_BOT_ZN_3 Heating 13176.23339 13176.23339 0.57570 0.57570 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -16.30000 9.24091E-004 313.41284 16.86939 0.13533 0.00000
11 PERIMETER_BOT_ZN_2 Cooling 18682.23359 18682.23359 1.39238 1.39238 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 09:00:00 25.18500 1.33579E-002 201.97515 10.87127 8.72129E-002 0.00000
12 PERIMETER_BOT_ZN_2 Heating 8903.75087 8903.75087 0.38909 0.38909 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -16.30000 9.24091E-004 201.97515 10.87127 8.72129E-002 0.00000
13 PERIMETER_BOT_ZN_1 Cooling 21585.34913 21585.34913 1.60876 1.60876 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 13:20:00 29.99000 1.33664E-002 313.41969 16.86975 0.13533 0.00000
14 PERIMETER_BOT_ZN_1 Heating 14314.36135 14314.36135 0.62559 0.62559 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -16.30000 9.24091E-004 313.41969 16.86975 0.13533 0.00000
15 PERIMETER_BOT_ZN_4 Cooling 22658.45444 22658.45444 1.68872 1.68872 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 17:10:00 28.84300 1.33644E-002 201.97515 10.87127 8.72129E-002 0.00000
16 PERIMETER_BOT_ZN_4 Heating 7309.23239 7309.23239 0.31916 0.31916 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -16.30000 9.24091E-004 201.97515 10.87127 8.72129E-002 0.00000
17 PERIMETER_MID_ZN_3 Cooling 134150.81852 134150.81852 9.99894 9.99894 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:40:00 30.30000 1.33670E-002 313.41284 16.86939 1.35332 0.00000
18 PERIMETER_MID_ZN_3 Heating 201556.35329 201556.35329 8.81648 8.81648 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -16.30000 9.24091E-004 313.41284 16.86939 1.35332 0.00000
19 PERIMETER_MID_ZN_2 Cooling 199008.45640 199008.45640 14.83295 14.83295 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 09:20:00 25.71200 1.33588E-002 201.97515 10.87127 0.87213 0.00000
20 PERIMETER_MID_ZN_2 Heating 131929.08466 131929.08466 5.77102 5.77102 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -16.30000 9.24091E-004 201.97515 10.87127 0.87213 0.00000
21 PERIMETER_MID_ZN_1 Cooling 216013.69875 216013.69875 16.10049 16.10049 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 13:30:00 30.06750 1.33665E-002 313.41969 16.86975 1.35335 0.00000
22 PERIMETER_MID_ZN_1 Heating 201557.43707 201557.43707 8.81653 8.81653 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -16.30000 9.24091E-004 313.41969 16.86975 1.35335 0.00000
23 PERIMETER_MID_ZN_4 Cooling 210335.53063 210335.53063 15.67719 15.67719 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 17:10:00 28.84300 1.33644E-002 201.97515 10.87127 0.87213 0.00000
24 PERIMETER_MID_ZN_4 Heating 129339.83267 129339.83267 5.65754 5.65754 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -16.30000 9.24091E-004 201.97515 10.87127 0.87213 0.00000
25 PERIMETER_TOP_ZN_3 Cooling 15053.21705 15053.21705 1.12202 1.12202 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 30.30000 1.33670E-002 313.41284 16.86939 0.13533 0.00000
26 PERIMETER_TOP_ZN_3 Heating 25219.65045 25219.65045 1.10361 1.10361 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -16.30000 9.24091E-004 313.41284 16.86939 0.13533 0.00000
27 PERIMETER_TOP_ZN_2 Cooling 20031.90909 20031.90909 1.49310 1.49310 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 09:30:00 25.97550 1.33593E-002 201.97515 10.87127 8.72129E-002 0.00000
28 PERIMETER_TOP_ZN_2 Heating 16459.60720 16459.60720 0.72028 0.72028 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -16.30000 9.24091E-004 201.97515 10.87127 8.72129E-002 0.00000
29 PERIMETER_TOP_ZN_1 Cooling 23123.11609 23123.11609 1.72351 1.72351 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 13:40:00 30.14500 1.33667E-002 313.41969 16.86975 0.13533 0.00000
30 PERIMETER_TOP_ZN_1 Heating 25219.83462 25219.83462 1.10362 1.10362 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -16.30000 9.24091E-004 313.41969 16.86975 0.13533 0.00000
31 PERIMETER_TOP_ZN_4 Cooling 22092.16924 22092.16924 1.64666 1.64666 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 17:10:00 28.84300 1.33644E-002 201.97515 10.87127 8.72129E-002 0.00000
32 PERIMETER_TOP_ZN_4 Heating 16346.56938 16346.56938 0.71533 0.71533 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -16.30000 9.24091E-004 201.97515 10.87127 8.72129E-002 0.00000
33 DATACENTER_BOT_ZN_6 Cooling 8717.42175 8717.42175 0.51243 0.51243 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 19:10:00 26.50250 1.33602E-002 36.20274 1.94861 1.56323E-002 0.00000
34 DATACENTER_BOT_ZN_6 Heating 0.00000 0.00000 0.00000 1.56323E-002 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 05:20:00 -16.30000 9.24091E-004 36.20274 1.94861 1.56323E-002 0.00000
35 DATACENTER_MID_ZN_6 Cooling 83648.65269 83648.65269 4.91706 4.91706 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 19:10:00 26.50250 1.33602E-002 36.20274 1.94861 0.15632 0.00000
36 DATACENTER_MID_ZN_6 Heating 0.00000 0.00000 0.00000 0.15632 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 05:40:00 -16.30000 9.24091E-004 36.20274 1.94861 0.15632 0.00000
37 DATACENTER_TOP_ZN_6 Cooling 8499.42936 8499.42936 0.49961 0.49961 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 19:10:00 26.50250 1.33602E-002 36.20274 1.94861 1.56323E-002 0.00000
38 DATACENTER_TOP_ZN_6 Heating 0.00000 0.00000 0.00000 1.56323E-002 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 05:40:00 -16.30000 9.24091E-004 36.20274 1.94861 1.56323E-002 0.00000
39 DATACENTER_BASEMENT_ZN_6 Cooling 373215.54267 373215.54267 21.93810 21.93810 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 07:00:00 21.83700 1.33520E-002 783.67941 42.18139 0.33839 0.00000
40 DATACENTER_BASEMENT_ZN_6 Heating 0.00000 0.00000 0.00000 0.33839 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 18:40:00 -16.30000 9.24091E-004 783.67941 42.18139 0.33839 0.00000


System Sizing Information

System Name Load Type Peak Load Kind User Design Capacity Calc Des Air Flow Rate [m3/s] User Des Air Flow Rate [m3/s] Design Day Name Date/Time of Peak
1 VAV_BOT WITH REHEAT Cooling Sensible 153041.93 10.38019 10.38019 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 00:00:00
2 VAV_BOT WITH REHEAT Heating Sensible 87048.39 2.98736 2.98736 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 22:00:00
3 VAV_MID WITH REHEAT Cooling Sensible 1420774.88 96.92789 96.92789 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 00:00:00
4 VAV_MID WITH REHEAT Heating Sensible 870600.92 42.91599 42.91599 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 22:20:00
5 VAV_TOP WITH REHEAT Cooling Sensible 159040.44 10.62577 10.62577 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 00:00:00
6 VAV_TOP WITH REHEAT Heating Sensible 87091.60 6.62178 6.62178 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 22:30:00
7 CAV_BAS Cooling Sensible 79846.18 6.06748 6.06748 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 05:00:00
8 CAV_BAS Heating Sensible 79706.12 1.20016 1.20016 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00
9 AIRLOOP DATACENTER BASEMENT Cooling Sensible 368329.03 21.93821 21.93821 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 05:00:00
10 AIRLOOP DATACENTER BASEMENT Heating Sensible 22473.72 0.33839 0.33839 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00
11 AIRLOOP DATACENTER BOT Cooling Sensible 8573.48 0.51243 0.51243 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 05:00:00
12 AIRLOOP DATACENTER BOT Heating Sensible 1038.19 1.56323E-002 1.56323E-002 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00
13 AIRLOOP DATACENTER MID Cooling Sensible 82263.72 4.91706 4.91706 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 05:00:00
14 AIRLOOP DATACENTER MID Heating Sensible 10381.93 0.15632 0.15632 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00
15 AIRLOOP DATACENTER TOP Cooling Sensible 8360.76 0.49961 0.49961 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 05:00:00
16 AIRLOOP DATACENTER TOP Heating Sensible 1038.19 1.56323E-002 1.56323E-002 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00


Component Sizing Information

Component Type Component Name Input Field Description Value
1 AirTerminal:SingleDuct:ConstantVolume:NoReheat BASEMENT DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 6.06748
2 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 6.30311
3 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.30176
4 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.31300
5 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 1.97287
6 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.80470
7 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
8 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.26258E-003
9 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 2.13323E-004
10 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 1.97287
11 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
12 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
13 Coil:Heating:Water CORE_BOTTOM VAV BOX REHEAT COIL Design Size Rated Capacity [W] 24384.08831
14 Coil:Heating:Water CORE_BOTTOM VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 2.13323E-004
15 Coil:Heating:Water CORE_BOTTOM VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 504.42954
16 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 59.38652
17 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.32028
18 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.32600
19 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 19.36001
20 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.85409
21 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
22 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.18958E-003
23 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 4.45902E-003
24 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 19.36001
25 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
26 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
27 Coil:Heating:Water CORE_MID VAV BOX REHEAT COIL Design Size Rated Capacity [W] 509693.53055
28 Coil:Heating:Water CORE_MID VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 4.45902E-003
29 Coil:Heating:Water CORE_MID VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 12357.35744
30 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 5.87410
31 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.32380
32 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.33800
33 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 1.98545
34 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.86347
35 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
36 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.17665E-003
37 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 8.53327E-004
38 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 2.97894
39 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
40 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
41 Coil:Heating:Water CORE_TOP VAV BOX REHEAT COIL Design Size Rated Capacity [W] 97540.46472
42 Coil:Heating:Water CORE_TOP VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 8.53327E-004
43 Coil:Heating:Water CORE_TOP VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 2574.53521
44 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 1.05356
45 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.22668
46 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.23500
47 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.24759
48 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.60448
49 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
50 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.68079E-003
51 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.64655E-004
52 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.57570
53 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
54 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
55 Coil:Heating:Water PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 18821.10136
56 Coil:Heating:Water PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.64655E-004
57 Coil:Heating:Water PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 496.42227
58 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 1.39238
59 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.11053
60 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.20000
61 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.27848
62 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.30000
63 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
64 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 3.44691E-003
65 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.11272E-004
66 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.38909
67 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
68 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
69 Coil:Heating:Water PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 12719.08773
70 Coil:Heating:Water PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.11272E-004
71 Coil:Heating:Water PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 335.46015
72 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 1.60876
73 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.14845
74 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.20000
75 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.32175
76 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.39588
77 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
78 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 2.56645E-003
79 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.78900E-004
80 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.62559
81 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
82 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
83 Coil:Heating:Water PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 20449.31676
84 Coil:Heating:Water PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.78900E-004
85 Coil:Heating:Water PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 539.33070
86 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 1.68872
87 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 9.11371E-002
88 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.20000
89 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.33774
90 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.30000
91 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
92 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 4.18051E-003
93 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 9.29040E-005
94 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.33774
95 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
96 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
97 Coil:Heating:Water PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 10619.49891
98 Coil:Heating:Water PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 9.29040E-005
99 Coil:Heating:Water PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 275.31898
100 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 9.99894
101 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.23885
102 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.24300
103 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 2.42974
104 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.63692
105 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
106 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.59517E-003
107 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 2.51927E-003
108 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 8.81648
109 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
110 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
111 Coil:Heating:Water PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 287968.00796
112 Coil:Heating:Water PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 2.51927E-003
113 Coil:Heating:Water PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 7592.17862
114 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_2 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 14.83295
115 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_2 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.10376
116 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_2 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.20000
117 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_2 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 2.96659
118 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_2 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.30000
119 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_2 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
120 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_2 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 3.67197E-003
121 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_2 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.64899E-003
122 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 5.77102
123 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
124 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
125 Coil:Heating:Water PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 188490.15961
126 Coil:Heating:Water PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.64899E-003
127 Coil:Heating:Water PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 4969.41267
128 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 16.10049
129 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.14833
130 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.20000
131 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 3.22010
132 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.39556
133 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
134 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 2.56852E-003
135 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 2.51928E-003
136 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 8.81653
137 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
138 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
139 Coil:Heating:Water PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 287969.55421
140 Coil:Heating:Water PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 2.51928E-003
141 Coil:Heating:Water PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 7592.21948
142 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 15.67719
143 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 9.81713E-002
144 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.20000
145 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 3.13544
146 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.30000
147 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
148 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 3.88097E-003
149 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.61660E-003
150 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 5.65754
151 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
152 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
153 Coil:Heating:Water PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 184787.32755
154 Coil:Heating:Water PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.61660E-003
155 Coil:Heating:Water PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 4871.83291
156 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 1.12202
157 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.21285
158 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.22200
159 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.24909
160 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.56760
161 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
162 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.79000E-003
163 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 3.15256E-004
164 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 1.10361
165 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
166 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
167 Coil:Heating:Water PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 36035.65214
168 Coil:Heating:Water PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 3.15256E-004
169 Coil:Heating:Water PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 949.93647
170 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 1.49310
171 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.10308
172 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.20000
173 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.29862
174 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.30000
175 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
176 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 3.69625E-003
177 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 2.05751E-004
178 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.72028
179 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
180 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
181 Coil:Heating:Water PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 23518.56019
182 Coil:Heating:Water PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 2.05751E-004
183 Coil:Heating:Water PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 619.96690
184 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 1.72351
185 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.13857
186 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.20000
187 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.34470
188 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.36952
189 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
190 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 2.74953E-003
191 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 3.15258E-004
192 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 1.10362
193 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
194 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
195 Coil:Heating:Water PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 36035.91519
196 Coil:Heating:Water PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 3.15258E-004
197 Coil:Heating:Water PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 949.94341
198 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 1.64666
199 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 9.34649E-002
200 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.20000
201 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.32933
202 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.30000
203 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
204 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 4.07639E-003
205 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 2.04337E-004
206 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.71533
207 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
208 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
209 Coil:Heating:Water PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 23356.94664
210 Coil:Heating:Water PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 2.04337E-004
211 Coil:Heating:Water PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 615.70689
212 AirTerminal:SingleDuct:ConstantVolume:NoReheat DATACENTER_BOT_ZN_6 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 0.51243
213 AirTerminal:SingleDuct:ConstantVolume:NoReheat DATACENTER_MID_ZN_6 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 4.91706
214 AirTerminal:SingleDuct:ConstantVolume:NoReheat DATACENTER_TOP_ZN_6 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 0.49961
215 AirTerminal:SingleDuct:ConstantVolume:NoReheat DATACENTER_BASEMENT_ZN_6 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 21.93810
216 AirLoopHVAC VAV_BOT WITH REHEAT Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 6.02326
217 AirLoopHVAC VAV_BOT WITH REHEAT Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 3.15843
218 AirLoopHVAC VAV_BOT WITH REHEAT Sum of Air Terminal Maximum Flow Rates [m3/s] 12.04653
219 AirLoopHVAC VAV_BOT WITH REHEAT Adjusted Heating Design Air Flow Rate [m3/s] 3.15843
220 AirLoopHVAC VAV_BOT WITH REHEAT Adjusted Cooling Design Air Flow Rate [m3/s] 10.38019
221 AirLoopHVAC VAV_BOT WITH REHEAT Adjusted Main Design Air Flow Rate [m3/s] 10.38019
222 AirLoopHVAC VAV_BOT WITH REHEAT User Heating Air Flow Ratio [] 0.30000
223 AirLoopHVAC VAV_BOT WITH REHEAT Calculated Heating Air Flow Ratio [] 0.30427
224 AirLoopHVAC VAV_MID WITH REHEAT Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 57.99805
225 AirLoopHVAC VAV_MID WITH REHEAT Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 31.11188
226 AirLoopHVAC VAV_MID WITH REHEAT Sum of Air Terminal Maximum Flow Rates [m3/s] 115.99610
227 AirLoopHVAC VAV_MID WITH REHEAT Adjusted Heating Design Air Flow Rate [m3/s] 42.91599
228 AirLoopHVAC VAV_MID WITH REHEAT Adjusted Cooling Design Air Flow Rate [m3/s] 96.92789
229 AirLoopHVAC VAV_MID WITH REHEAT Adjusted Main Design Air Flow Rate [m3/s] 96.92789
230 AirLoopHVAC VAV_MID WITH REHEAT User Heating Air Flow Ratio [] 0.30000
231 AirLoopHVAC VAV_MID WITH REHEAT Calculated Heating Air Flow Ratio [] 0.44276
232 AirLoopHVAC VAV_TOP WITH REHEAT Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 5.92970
233 AirLoopHVAC VAV_TOP WITH REHEAT Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 3.20719
234 AirLoopHVAC VAV_TOP WITH REHEAT Sum of Air Terminal Maximum Flow Rates [m3/s] 11.85939
235 AirLoopHVAC VAV_TOP WITH REHEAT Adjusted Heating Design Air Flow Rate [m3/s] 6.62178
236 AirLoopHVAC VAV_TOP WITH REHEAT Adjusted Cooling Design Air Flow Rate [m3/s] 10.62577
237 AirLoopHVAC VAV_TOP WITH REHEAT Adjusted Main Design Air Flow Rate [m3/s] 10.62577
238 AirLoopHVAC VAV_TOP WITH REHEAT User Heating Air Flow Ratio [] 0.30000
239 AirLoopHVAC VAV_TOP WITH REHEAT Calculated Heating Air Flow Ratio [] 0.62318
240 AirLoopHVAC CAV_BAS Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 6.06748
241 AirLoopHVAC CAV_BAS Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 6.06748
242 AirLoopHVAC CAV_BAS Sum of Air Terminal Maximum Flow Rates [m3/s] 6.06748
243 AirLoopHVAC CAV_BAS Adjusted Heating Design Air Flow Rate [m3/s] 6.06748
244 AirLoopHVAC CAV_BAS Adjusted Cooling Design Air Flow Rate [m3/s] 6.06748
245 AirLoopHVAC CAV_BAS Adjusted Main Design Air Flow Rate [m3/s] 6.06748
246 AirLoopHVAC CAV_BAS User Heating Air Flow Ratio [] 1.00000
247 AirLoopHVAC CAV_BAS Calculated Heating Air Flow Ratio [] 1.00000
248 AirLoopHVAC AIRLOOP DATACENTER BASEMENT Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 21.93810
249 AirLoopHVAC AIRLOOP DATACENTER BASEMENT Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 21.93810
250 AirLoopHVAC AIRLOOP DATACENTER BASEMENT Sum of Air Terminal Maximum Flow Rates [m3/s] 21.93810
251 AirLoopHVAC AIRLOOP DATACENTER BASEMENT Adjusted Heating Design Air Flow Rate [m3/s] 21.93810
252 AirLoopHVAC AIRLOOP DATACENTER BASEMENT Adjusted Cooling Design Air Flow Rate [m3/s] 21.93821
253 AirLoopHVAC AIRLOOP DATACENTER BASEMENT Adjusted Main Design Air Flow Rate [m3/s] 21.93821
254 AirLoopHVAC AIRLOOP DATACENTER BASEMENT User Heating Air Flow Ratio [] 1.00000
255 AirLoopHVAC AIRLOOP DATACENTER BASEMENT Calculated Heating Air Flow Ratio [] 1.00000
256 AirLoopHVAC AIRLOOP DATACENTER BOT Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 0.51243
257 AirLoopHVAC AIRLOOP DATACENTER BOT Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 0.51243
258 AirLoopHVAC AIRLOOP DATACENTER BOT Sum of Air Terminal Maximum Flow Rates [m3/s] 0.51243
259 AirLoopHVAC AIRLOOP DATACENTER BOT Adjusted Heating Design Air Flow Rate [m3/s] 0.51243
260 AirLoopHVAC AIRLOOP DATACENTER BOT Adjusted Cooling Design Air Flow Rate [m3/s] 0.51243
261 AirLoopHVAC AIRLOOP DATACENTER BOT Adjusted Main Design Air Flow Rate [m3/s] 0.51243
262 AirLoopHVAC AIRLOOP DATACENTER BOT User Heating Air Flow Ratio [] 1.00000
263 AirLoopHVAC AIRLOOP DATACENTER BOT Calculated Heating Air Flow Ratio [] 1.00000
264 AirLoopHVAC AIRLOOP DATACENTER MID Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 4.91706
265 AirLoopHVAC AIRLOOP DATACENTER MID Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 4.91706
266 AirLoopHVAC AIRLOOP DATACENTER MID Sum of Air Terminal Maximum Flow Rates [m3/s] 4.91706
267 AirLoopHVAC AIRLOOP DATACENTER MID Adjusted Heating Design Air Flow Rate [m3/s] 4.91706
268 AirLoopHVAC AIRLOOP DATACENTER MID Adjusted Cooling Design Air Flow Rate [m3/s] 4.91706
269 AirLoopHVAC AIRLOOP DATACENTER MID Adjusted Main Design Air Flow Rate [m3/s] 4.91706
270 AirLoopHVAC AIRLOOP DATACENTER MID User Heating Air Flow Ratio [] 1.00000
271 AirLoopHVAC AIRLOOP DATACENTER MID Calculated Heating Air Flow Ratio [] 1.00000
272 AirLoopHVAC AIRLOOP DATACENTER TOP Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 0.49961
273 AirLoopHVAC AIRLOOP DATACENTER TOP Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 0.49961
274 AirLoopHVAC AIRLOOP DATACENTER TOP Sum of Air Terminal Maximum Flow Rates [m3/s] 0.49961
275 AirLoopHVAC AIRLOOP DATACENTER TOP Adjusted Heating Design Air Flow Rate [m3/s] 0.49961
276 AirLoopHVAC AIRLOOP DATACENTER TOP Adjusted Cooling Design Air Flow Rate [m3/s] 0.49961
277 AirLoopHVAC AIRLOOP DATACENTER TOP Adjusted Main Design Air Flow Rate [m3/s] 0.49961
278 AirLoopHVAC AIRLOOP DATACENTER TOP User Heating Air Flow Ratio [] 1.00000
279 AirLoopHVAC AIRLOOP DATACENTER TOP Calculated Heating Air Flow Ratio [] 1.00000
280 AirLoopHVAC VAV_BOT WITH REHEAT Design Supply Air Flow Rate [m3/s] 10.38019
281 AirLoopHVAC VAV_MID WITH REHEAT Design Supply Air Flow Rate [m3/s] 96.92789
282 AirLoopHVAC VAV_TOP WITH REHEAT Design Supply Air Flow Rate [m3/s] 10.62577
283 AirLoopHVAC CAV_BAS Design Supply Air Flow Rate [m3/s] 6.06748
284 AirLoopHVAC AIRLOOP DATACENTER BASEMENT Design Supply Air Flow Rate [m3/s] 21.93821
285 AirLoopHVAC AIRLOOP DATACENTER BOT Design Supply Air Flow Rate [m3/s] 0.51243
286 AirLoopHVAC AIRLOOP DATACENTER MID Design Supply Air Flow Rate [m3/s] 4.91706
287 AirLoopHVAC AIRLOOP DATACENTER TOP Design Supply Air Flow Rate [m3/s] 0.49961
288 Controller:OutdoorAir VAV_BOT WITH REHEAT_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 10.38019
289 Controller:OutdoorAir VAV_BOT WITH REHEAT_OA_CONTROLLER Minimum Outdoor Air Flow Rate [m3/s] 2.53819
290 HeatExchanger:AirToAir:SensibleAndLatent VAV_BOT WITH REHEAT OA HEAT RECOVERY Design Size Nominal Supply Air Flow Rate [m3/s] 2.53819
291 Coil:Cooling:Water VAV_BOT WITH REHEAT COOLING COIL Design Size Design Inlet Air Temperature [C] 25.57327
292 Coil:Cooling:Water VAV_BOT WITH REHEAT COOLING COIL Design Size Design Inlet Water Temperature [C] 6.67000
293 Coil:Cooling:Water VAV_BOT WITH REHEAT COOLING COIL Design Size Design Outlet Air Temperature [C] 10.90922
294 Coil:Cooling:Water VAV_BOT WITH REHEAT COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 9.98850E-003
295 Coil:Cooling:Water VAV_BOT WITH REHEAT COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 8.50000E-003
296 Coil:Cooling:Water VAV_BOT WITH REHEAT COOLING COIL Design Size Design Coil Load [W] 228603.15808
297 Coil:Cooling:Water VAV_BOT WITH REHEAT COOLING COIL Design Size Design Water Flow Rate [m3/s] 9.72531E-003
298 Coil:Cooling:Water VAV_BOT WITH REHEAT COOLING COIL Design Size Design Air Flow Rate [m3/s] 10.38019
299 Coil:Heating:Water VAV_BOT WITH REHEAT HEATING COIL Design Size Rated Capacity [W] 81559.25069
300 Coil:Heating:Water VAV_BOT WITH REHEAT HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 7.13516E-004
301 Coil:Heating:Water VAV_BOT WITH REHEAT HEATING COIL Design Size U-Factor Times Area Value [W/K] 1298.98860
302 Fan:VariableVolume VAV_BOT WITH REHEAT FAN Design Size Maximum Flow Rate [m3/s] 10.38019
303 Controller:WaterCoil VAV_BOT WITH REHEAT_COOLC_CONTROLLER Maximum Actuated Flow [m3/s] 9.72531E-003
304 Controller:WaterCoil VAV_BOT WITH REHEAT_COOLC_CONTROLLER Controller Convergence Tolerance 4.89641E-005
305 Controller:WaterCoil VAV_BOT WITH REHEAT_HEATC_CONTROLLER Maximum Actuated Flow [m3/s] 7.13516E-004
306 Controller:OutdoorAir VAV_MID WITH REHEAT_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 96.92789
307 Controller:OutdoorAir VAV_MID WITH REHEAT_OA_CONTROLLER Minimum Outdoor Air Flow Rate [m3/s] 25.38195
308 HeatExchanger:AirToAir:SensibleAndLatent VAV_MID WITH REHEAT OA HEAT RECOVERY Design Size Nominal Supply Air Flow Rate [m3/s] 25.38195
309 Coil:Cooling:Water VAV_MID WITH REHEAT COOLING COIL Design Size Design Inlet Air Temperature [C] 25.71311
310 Coil:Cooling:Water VAV_MID WITH REHEAT COOLING COIL Design Size Design Inlet Water Temperature [C] 6.67000
311 Coil:Cooling:Water VAV_MID WITH REHEAT COOLING COIL Design Size Design Outlet Air Temperature [C] 10.90981
312 Coil:Cooling:Water VAV_MID WITH REHEAT COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 1.01599E-002
313 Coil:Cooling:Water VAV_MID WITH REHEAT COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 8.50000E-003
314 Coil:Cooling:Water VAV_MID WITH REHEAT COOLING COIL Design Size Design Coil Load [W] 2200563.11984
315 Coil:Cooling:Water VAV_MID WITH REHEAT COOLING COIL Design Size Design Water Flow Rate [m3/s] 9.36170E-002
316 Coil:Cooling:Water VAV_MID WITH REHEAT COOLING COIL Design Size Design Air Flow Rate [m3/s] 96.92789
317 Coil:Heating:Water VAV_MID WITH REHEAT HEATING COIL Design Size Rated Capacity [W] 835544.76141
318 Coil:Heating:Water VAV_MID WITH REHEAT HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 7.30971E-003
319 Coil:Heating:Water VAV_MID WITH REHEAT HEATING COIL Design Size U-Factor Times Area Value [W/K] 13168.53360
320 Fan:VariableVolume VAV_MID WITH REHEAT FAN Design Size Maximum Flow Rate [m3/s] 96.92789
321 Controller:WaterCoil VAV_MID WITH REHEAT_COOLC_CONTROLLER Maximum Actuated Flow [m3/s] 9.36170E-002
322 Controller:WaterCoil VAV_MID WITH REHEAT_COOLC_CONTROLLER Controller Convergence Tolerance 5.08658E-006
323 Controller:WaterCoil VAV_MID WITH REHEAT_HEATC_CONTROLLER Maximum Actuated Flow [m3/s] 7.30971E-003
324 Controller:OutdoorAir VAV_TOP WITH REHEAT_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 10.62577
325 Controller:OutdoorAir VAV_TOP WITH REHEAT_OA_CONTROLLER Minimum Outdoor Air Flow Rate [m3/s] 2.53819
326 HeatExchanger:AirToAir:SensibleAndLatent VAV_TOP WITH REHEAT OA HEAT RECOVERY Design Size Nominal Supply Air Flow Rate [m3/s] 2.53819
327 Coil:Cooling:Water VAV_TOP WITH REHEAT COOLING COIL Design Size Design Inlet Air Temperature [C] 25.50550
328 Coil:Cooling:Water VAV_TOP WITH REHEAT COOLING COIL Design Size Design Inlet Water Temperature [C] 6.67000
329 Coil:Cooling:Water VAV_TOP WITH REHEAT COOLING COIL Design Size Design Outlet Air Temperature [C] 10.90923
330 Coil:Cooling:Water VAV_TOP WITH REHEAT COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 9.99128E-003
331 Coil:Cooling:Water VAV_TOP WITH REHEAT COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 8.50000E-003
332 Coil:Cooling:Water VAV_TOP WITH REHEAT COOLING COIL Design Size Design Coil Load [W] 233234.65902
333 Coil:Cooling:Water VAV_TOP WITH REHEAT COOLING COIL Design Size Design Water Flow Rate [m3/s] 9.92234E-003
334 Coil:Cooling:Water VAV_TOP WITH REHEAT COOLING COIL Design Size Design Air Flow Rate [m3/s] 10.62577
335 Coil:Heating:Water VAV_TOP WITH REHEAT HEATING COIL Design Size Rated Capacity [W] 81603.29986
336 Coil:Heating:Water VAV_TOP WITH REHEAT HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 7.13901E-004
337 Coil:Heating:Water VAV_TOP WITH REHEAT HEATING COIL Design Size U-Factor Times Area Value [W/K] 1302.99633
338 Fan:VariableVolume VAV_TOP WITH REHEAT FAN Design Size Maximum Flow Rate [m3/s] 10.62577
339 Controller:WaterCoil VAV_TOP WITH REHEAT_COOLC_CONTROLLER Maximum Actuated Flow [m3/s] 9.92234E-003
340 Controller:WaterCoil VAV_TOP WITH REHEAT_COOLC_CONTROLLER Controller Convergence Tolerance 4.79917E-005
341 Controller:WaterCoil VAV_TOP WITH REHEAT_HEATC_CONTROLLER Maximum Actuated Flow [m3/s] 7.13901E-004
342 Controller:OutdoorAir CAV_BAS_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 6.06748
343 Controller:OutdoorAir CAV_BAS_OA_CONTROLLER Minimum Outdoor Air Flow Rate [m3/s] 1.20016
344 Coil:Cooling:Water CAV_BAS COOLING COIL Design Size Design Inlet Air Temperature [C] 24.89102
345 Coil:Cooling:Water CAV_BAS COOLING COIL Design Size Design Inlet Water Temperature [C] 6.67000
346 Coil:Cooling:Water CAV_BAS COOLING COIL Design Size Design Outlet Air Temperature [C] 11.38837
347 Coil:Cooling:Water CAV_BAS COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 9.89654E-003
348 Coil:Cooling:Water CAV_BAS COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 8.50000E-003
349 Coil:Cooling:Water CAV_BAS COOLING COIL Design Size Design Coil Load [W] 123499.09010
350 Coil:Cooling:Water CAV_BAS COOLING COIL Design Size Design Water Flow Rate [m3/s] 5.25394E-003
351 Coil:Cooling:Water CAV_BAS COOLING COIL Design Size Design Air Flow Rate [m3/s] 6.06748
352 Coil:Heating:Water CAV_BAS HEATING COIL Design Size Rated Capacity [W] 309371.51400
353 Coil:Heating:Water CAV_BAS HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 2.70652E-003
354 Coil:Heating:Water CAV_BAS HEATING COIL Design Size U-Factor Times Area Value [W/K] 6738.85199
355 Fan:ConstantVolume CAV_BAS FAN Design Size Maximum Flow Rate [m3/s] 6.06748
356 Controller:WaterCoil CAV_BAS_COOLC_CONTROLLER Maximum Actuated Flow [m3/s] 5.25394E-003
357 Controller:WaterCoil CAV_BAS_COOLC_CONTROLLER Controller Convergence Tolerance 9.06350E-005
358 Controller:WaterCoil CAV_BAS_HEATC_CONTROLLER Maximum Actuated Flow [m3/s] 2.70652E-003
359 Controller:OutdoorAir AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 21.93821
360 Controller:OutdoorAir AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER Minimum Outdoor Air Flow Rate [m3/s] 0.33839
361 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER BASEMENT COOLING COIL Design Size Rated Air Flow Rate [m3/s] 21.93821
362 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER BASEMENT COOLING COIL Design Size Rated Total Cooling Capacity [W] 435227.10248
363 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER BASEMENT COOLING COIL Design Size Rated Sensible Cooling Capacity [W] 306220.40523
364 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER BASEMENT COOLING COIL Design Size Rated Water Flow Rate [m3/s] 1.06587E-002
365 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP Supply Air Flow Rate [m3/s] 21.93821
366 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP Supply Air Flow Rate During Heating Operation [m3/s] 21.93821
367 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP Supply Air Flow Rate During Cooling Operation [m3/s] 21.93821
368 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] 21.93821
369 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP Nominal Heating Capacity [W] 435227.10248
370 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP Nominal Cooling Capacity [W] 435227.10248
371 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP Supplemental Heating Coil Nominal Capacity [W] 22473.71574
372 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
373 Fan:OnOff AIRLOOP DATACENTER BASEMENT SUPPLY FAN Design Size Maximum Flow Rate [m3/s] 21.93821
374 COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER BASEMENT HEATING COIL Design Size Rated Air Flow Rate [m3/s] 21.93821
375 COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER BASEMENT HEATING COIL Design Size Rated Heating Capacity [W] 435227.10248
376 COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER BASEMENT HEATING COIL Design Size Rated Water Flow Rate [m3/s] 1.06587E-002
377 Coil:Heating:Electric AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL Design Size Nominal Capacity [W] 22473.71574
378 Humidifier:Steam:Electric DATACENTER_BASEMENT_ZN_6 HUMIDIFIER Design Size Nominal Capacity Volume [m3/s] 1.87928E-004
379 Humidifier:Steam:Electric DATACENTER_BASEMENT_ZN_6 HUMIDIFIER User-Specified Nominal Capacity Volume [m3/s] 3.72000E-005
380 Humidifier:Steam:Electric DATACENTER_BASEMENT_ZN_6 HUMIDIFIER Design Size Rated Power [W] 96450.69782
381 Humidifier:Steam:Electric DATACENTER_BASEMENT_ZN_6 HUMIDIFIER User-Specified Rated Power [W] 100000.00000
382 Controller:OutdoorAir AIRLOOP DATACENTER BOT_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 0.51243
383 Controller:OutdoorAir AIRLOOP DATACENTER BOT_OA_CONTROLLER Minimum Outdoor Air Flow Rate [m3/s] 1.56323E-002
384 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER BOT COOLING COIL Design Size Rated Air Flow Rate [m3/s] 0.51243
385 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER BOT COOLING COIL Design Size Rated Total Cooling Capacity [W] 10034.39420
386 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER BOT COOLING COIL Design Size Rated Sensible Cooling Capacity [W] 7101.30031
387 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER BOT COOLING COIL Design Size Rated Water Flow Rate [m3/s] 2.45742E-004
388 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BOT DXAC HEAT PUMP Supply Air Flow Rate [m3/s] 0.51243
389 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BOT DXAC HEAT PUMP Supply Air Flow Rate During Heating Operation [m3/s] 0.51243
390 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BOT DXAC HEAT PUMP Supply Air Flow Rate During Cooling Operation [m3/s] 0.51243
391 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BOT DXAC HEAT PUMP Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] 0.51243
392 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BOT DXAC HEAT PUMP Nominal Heating Capacity [W] 10034.39420
393 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BOT DXAC HEAT PUMP Nominal Cooling Capacity [W] 10034.39420
394 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BOT DXAC HEAT PUMP Supplemental Heating Coil Nominal Capacity [W] 1038.19256
395 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BOT DXAC HEAT PUMP Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
396 Fan:OnOff AIRLOOP DATACENTER BOT SUPPLY FAN Design Size Maximum Flow Rate [m3/s] 0.51243
397 COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER BOT HEATING COIL Design Size Rated Air Flow Rate [m3/s] 0.51243
398 COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER BOT HEATING COIL Design Size Rated Heating Capacity [W] 10034.39420
399 COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER BOT HEATING COIL Design Size Rated Water Flow Rate [m3/s] 2.45742E-004
400 Coil:Heating:Electric AIRLOOP DATACENTER BOT_SUPPHEATCOIL Design Size Nominal Capacity [W] 1038.19256
401 Controller:OutdoorAir AIRLOOP DATACENTER MID_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 4.91706
402 Controller:OutdoorAir AIRLOOP DATACENTER MID_OA_CONTROLLER Minimum Outdoor Air Flow Rate [m3/s] 0.15632
403 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER MID COOLING COIL Design Size Rated Air Flow Rate [m3/s] 4.91706
404 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER MID COOLING COIL Design Size Rated Total Cooling Capacity [W] 96406.41861
405 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER MID COOLING COIL Design Size Rated Sensible Cooling Capacity [W] 68179.42634
406 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER MID COOLING COIL Design Size Rated Water Flow Rate [m3/s] 2.36099E-003
407 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER MID DXAC HEAT PUMP Supply Air Flow Rate [m3/s] 4.91706
408 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER MID DXAC HEAT PUMP Supply Air Flow Rate During Heating Operation [m3/s] 4.91706
409 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER MID DXAC HEAT PUMP Supply Air Flow Rate During Cooling Operation [m3/s] 4.91706
410 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER MID DXAC HEAT PUMP Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] 4.91706
411 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER MID DXAC HEAT PUMP Nominal Heating Capacity [W] 96406.41861
412 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER MID DXAC HEAT PUMP Nominal Cooling Capacity [W] 96406.41861
413 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER MID DXAC HEAT PUMP Supplemental Heating Coil Nominal Capacity [W] 10381.92564
414 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER MID DXAC HEAT PUMP Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
415 Fan:OnOff AIRLOOP DATACENTER MID SUPPLY FAN Design Size Maximum Flow Rate [m3/s] 4.91706
416 COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER MID HEATING COIL Design Size Rated Air Flow Rate [m3/s] 4.91706
417 COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER MID HEATING COIL Design Size Rated Heating Capacity [W] 96406.41861
418 COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER MID HEATING COIL Design Size Rated Water Flow Rate [m3/s] 2.36099E-003
419 Coil:Heating:Electric AIRLOOP DATACENTER MID_SUPPHEATCOIL Design Size Nominal Capacity [W] 10381.92564
420 Controller:OutdoorAir AIRLOOP DATACENTER TOP_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 0.49961
421 Controller:OutdoorAir AIRLOOP DATACENTER TOP_OA_CONTROLLER Minimum Outdoor Air Flow Rate [m3/s] 1.56323E-002
422 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER TOP COOLING COIL Design Size Rated Air Flow Rate [m3/s] 0.49961
423 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER TOP COOLING COIL Design Size Rated Total Cooling Capacity [W] 9793.48262
424 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER TOP COOLING COIL Design Size Rated Sensible Cooling Capacity [W] 6926.95391
425 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER TOP COOLING COIL Design Size Rated Water Flow Rate [m3/s] 2.39842E-004
426 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER TOP DXAC HEAT PUMP Supply Air Flow Rate [m3/s] 0.49961
427 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER TOP DXAC HEAT PUMP Supply Air Flow Rate During Heating Operation [m3/s] 0.49961
428 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER TOP DXAC HEAT PUMP Supply Air Flow Rate During Cooling Operation [m3/s] 0.49961
429 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER TOP DXAC HEAT PUMP Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] 0.49961
430 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER TOP DXAC HEAT PUMP Nominal Heating Capacity [W] 9793.48262
431 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER TOP DXAC HEAT PUMP Nominal Cooling Capacity [W] 9793.48262
432 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER TOP DXAC HEAT PUMP Supplemental Heating Coil Nominal Capacity [W] 1038.19256
433 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER TOP DXAC HEAT PUMP Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
434 Fan:OnOff AIRLOOP DATACENTER TOP SUPPLY FAN Design Size Maximum Flow Rate [m3/s] 0.49961
435 COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER TOP HEATING COIL Design Size Rated Air Flow Rate [m3/s] 0.49961
436 COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER TOP HEATING COIL Design Size Rated Heating Capacity [W] 9793.48262
437 COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER TOP HEATING COIL Design Size Rated Water Flow Rate [m3/s] 2.39842E-004
438 Coil:Heating:Electric AIRLOOP DATACENTER TOP_SUPPHEATCOIL Design Size Nominal Capacity [W] 1038.19256
439 Pump:VariableSpeed COOLSYS1 PUMP SECONDARY Design Flow Rate [m3/s] 0.11852
440 Pump:VariableSpeed COOLSYS1 PUMP SECONDARY Design Power Consumption [W] 19350.47031
441 PlantLoop COOLSYS1_DEMAND Maximum Loop Flow Rate [m3/s] 0.11852
442 PlantLoop COOLSYS1_DEMAND Plant Loop Volume [m3] 14.22224
443 HeatExchanger:FluidToFluid BYPASS HEAT EXCHANGER Loop Supply Side Design Fluid Flow Rate [m3/s] 0.11852
444 HeatExchanger:FluidToFluid BYPASS HEAT EXCHANGER Loop Demand Side Design Fluid Flow Rate [m3/s] 0.11852
445 HeatExchanger:FluidToFluid BYPASS HEAT EXCHANGER Heat Exchanger U-Factor Times Area Value [W/C] 497482.14769
446 HeatExchanger:FluidToFluid BYPASS HEAT EXCHANGER Loop-to-loop Temperature Difference Used to Size Heat Exchanger U-Factor Times Area Value [C] 5.60000
447 PlantLoop HEATSYS1 Maximum Loop Flow Rate [m3/s] 2.68618E-002
448 PlantLoop HEATSYS1 Plant Loop Volume [m3] 3.22342
449 Pump:VariableSpeed HEATSYS1 PUMP Design Flow Rate [m3/s] 2.68618E-002
450 Pump:VariableSpeed HEATSYS1 PUMP Design Power Consumption [W] 8089.59268
451 Pump:VariableSpeed HEATSYS1 PUMP Design Minimum Flow Rate [m3/s] 0.00000
452 Boiler:HotWater HEATSYS1 BOILER Design Size Nominal Capacity [W] 3070468.03778
453 Boiler:HotWater HEATSYS1 BOILER User-Specified Nominal Capacity [W] 3070468.04000
454 Boiler:HotWater HEATSYS1 BOILER Design Size Design Water Flow Rate [m3/s] 2.68618E-002
455 PlantLoop COOLSYS1_SUPPLY Maximum Loop Flow Rate [m3/s] 0.11852
456 PlantLoop COOLSYS1_SUPPLY Plant Loop Volume [m3] 14.22224
457 Pump:ConstantSpeed COOLSYS1 CHILLER1 PUMP Design Flow Rate [m3/s] 5.92593E-002
458 Pump:ConstantSpeed COOLSYS1 CHILLER1 PUMP Design Power Consumption [W] 6698.49158
459 Pump:ConstantSpeed COOLSYS1 CHILLER2 PUMP Design Flow Rate [m3/s] 5.92593E-002
460 Pump:ConstantSpeed COOLSYS1 CHILLER2 PUMP Design Power Consumption [W] 6698.49158
461 Chiller:Electric:ReformulatedEIR COOLSYS1 CHILLER1 Design Size Reference Chilled Water Flow Rate [m3/s] 0.11852
462 Chiller:Electric:ReformulatedEIR COOLSYS1 CHILLER1 User-Specified Reference Chilled Water Flow Rate [m3/s] 5.95950E-002
463 Chiller:Electric:ReformulatedEIR COOLSYS1 CHILLER1 Design Size Reference Capacity [W] 1404281.78136
464 Chiller:Electric:ReformulatedEIR COOLSYS1 CHILLER1 User-Specified Reference Capacity [W] 1410897.12500
465 Chiller:Electric:ReformulatedEIR COOLSYS1 CHILLER1 Design Size Reference Condenser Water Flow Rate [m3/s] 6.98201E-002
466 Chiller:Electric:ReformulatedEIR COOLSYS1 CHILLER2 Design Size Reference Chilled Water Flow Rate [m3/s] 0.11852
467 Chiller:Electric:ReformulatedEIR COOLSYS1 CHILLER2 User-Specified Reference Chilled Water Flow Rate [m3/s] 5.95950E-002
468 Chiller:Electric:ReformulatedEIR COOLSYS1 CHILLER2 Design Size Reference Capacity [W] 1404281.78136
469 Chiller:Electric:ReformulatedEIR COOLSYS1 CHILLER2 User-Specified Reference Capacity [W] 1410897.12500
470 Chiller:Electric:ReformulatedEIR COOLSYS1 CHILLER2 Design Size Reference Condenser Water Flow Rate [m3/s] 6.98201E-002
471 PlantLoop SINGLE WATER PLANT LOOP Maximum Loop Flow Rate [m3/s] 1.35053E-002
472 PlantLoop SINGLE WATER PLANT LOOP Plant Loop Volume [m3] 1.62063
473 Pump:ConstantSpeed PLANT CIRC PUMP Design Flow Rate [m3/s] 1.35053E-002
474 Pump:ConstantSpeed PLANT CIRC PUMP Design Power Consumption [W] 3444.51517
475 FluidCooler:TwoSpeed CENTRAL TOWER Design Water Flow Rate [m3/s] 1.35053E-002
476 FluidCooler:TwoSpeed CENTRAL TOWER Air Flow Rate at High Fan Speed [m3/s] 139666.46671
477 FluidCooler:TwoSpeed CENTRAL TOWER Fluid cooler UA value at high fan speed based on nominal capacity input [W/K] 58456.60917
478 FluidCooler:TwoSpeed CENTRAL TOWER Air Flow Rate at Low Fan Speed [m3/s] 69833.23335
479 FluidCooler:TwoSpeed CENTRAL TOWER Fan Power at Low Fan Speed [W] 7879.72339
480 FluidCooler:TwoSpeed CENTRAL TOWER U-factor Times Area Value at Low Fan Speed [W/C] 21333.26252
481 Boiler:HotWater CENTRAL BOILER Design Size Nominal Capacity [W] 556300.68943
482 Boiler:HotWater CENTRAL BOILER User-Specified Nominal Capacity [W] 545478.78000
483 Boiler:HotWater CENTRAL BOILER Design Size Design Water Flow Rate [m3/s] 1.35053E-002
484 PlantLoop SWHSYS1 Maximum Loop Flow Rate [m3/s] 4.40000E-004
485 PlantLoop SWHSYS1 Plant Loop Volume [m3] 5.28000E-002
486 Pump:ConstantSpeed SWHSYS1 PUMP Design Flow Rate [m3/s] 4.40000E-004
487 Pump:ConstantSpeed SWHSYS1 PUMP Design Power Consumption [W] 56.20530
488 WaterHeater:Mixed SWHSYS1 WATER HEATER Use Side Design Flow Rate [m3/s] 4.40000E-004
489 CondenserLoop TOWERWATERSYS Maximum Loop Flow Rate [m3/s] 0.13964
490 CondenserLoop TOWERWATERSYS Condenser Loop Volume [m3] 16.75682
491 HeaderedPumps:VariableSpeed TOWERWATERSYS PUMP Design Flow Rate [m3/s] 0.13964
492 HeaderedPumps:VariableSpeed TOWERWATERSYS PUMP Design Power Consumption [W] 34571.80893
493 CoolingTower:VariableSpeed TOWERWATERSYS COOLTOWER 1 Design Air Flow Rate [m3/s] 55.35545
494 CoolingTower:VariableSpeed TOWERWATERSYS COOLTOWER 1 Nominal Capacity [W] 1674019.00482
495 CoolingTower:VariableSpeed TOWERWATERSYS COOLTOWER 1 Air Flow Rate in free convection regime [m3/s] 11.07109
496 CoolingTower:VariableSpeed TOWERWATERSYS COOLTOWER 1 Tower capacity in free convection regime at design conditions [W] 209252.37560
497 CoolingTower:VariableSpeed TOWERWATERSYS COOLTOWER 2 Design Air Flow Rate [m3/s] 55.35545
498 CoolingTower:VariableSpeed TOWERWATERSYS COOLTOWER 2 Nominal Capacity [W] 1674019.00482
499 CoolingTower:VariableSpeed TOWERWATERSYS COOLTOWER 2 Air Flow Rate in free convection regime [m3/s] 11.07109
500 CoolingTower:VariableSpeed TOWERWATERSYS COOLTOWER 2 Tower capacity in free convection regime at design conditions [W] 209252.37560
501 PlantEquipmentOperation:ComponentSetPoint WSHPPLANT OPERATION SCHEME Design Water Flow Rate [m3/s] Equipment # 47 7.25200E-002
502 PlantEquipmentOperation:ComponentSetPoint WSHPPLANT OPERATION SCHEME Design Water Flow Rate [m3/s] Equipment # 47 7.25200E-002


Water Heating Coil Capacity Information

Component Type Name Nominal Total Capacity {W}
1 Coil:Heating:Water CORE_BOTTOM VAV BOX REHEAT COIL 23118.58
2 Coil:Heating:Water CORE_MID VAV BOX REHEAT COIL 482843.24
3 Coil:Heating:Water CORE_TOP VAV BOX REHEAT COIL 92431.34
4 Coil:Heating:Water PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL 17832.90
5 Coil:Heating:Water PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL 12051.16
6 Coil:Heating:Water PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL 19375.38
7 Coil:Heating:Water PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL 10056.74
8 Coil:Heating:Water PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL 272826.65
9 Coil:Heating:Water PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL 178578.90
10 Coil:Heating:Water PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL 272828.11
11 Coil:Heating:Water PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL 175071.06
12 Coil:Heating:Water PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL 34140.01
13 Coil:Heating:Water PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL 22281.34
14 Coil:Heating:Water PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL 34140.26
15 Coil:Heating:Water PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL 22128.23
16 Coil:Heating:Water VAV_BOT WITH REHEAT HEATING COIL 58594.07
17 Coil:Heating:Water VAV_MID WITH REHEAT HEATING COIL 586545.04
18 Coil:Heating:Water VAV_TOP WITH REHEAT HEATING COIL 58947.92
19 Coil:Heating:Water CAV_BAS HEATING COIL 238890.49


Water Cooling Coil Capacity Information

Component Type Name Nominal Total Capacity {W} Nominal Sensible Capacity {W} Nominal Latent Capacity {W} Nominal Sensible Heat Ratio Nominal Coil UA Value {W/C} Nominal Coil Surface Area {m2}
1 Coil:Cooling:Water VAV_BOT WITH REHEAT COOLING COIL 264703.75 180014.68 84689.07 0.68 28027.06 284.27
2 Coil:Cooling:Water VAV_MID WITH REHEAT COOLING COIL 2503609.88 1695570.92 808038.96 0.68 265231.62 2690.13
3 Coil:Cooling:Water VAV_TOP WITH REHEAT COOLING COIL 270649.96 184133.39 86516.57 0.68 28667.56 290.76
4 Coil:Cooling:Water CAV_BAS COOLING COIL 147434.44 101698.31 45736.12 0.69 15253.25 154.71


Chiller Standard Rating Information

Component Type Component Name IPLV in SI Units {W/W} IPLV in IP Units {Btu/W-h}
1 Chiller:Electric:ReformulatedEIR COOLSYS1 CHILLER1 6.84 23.33
2 Chiller:Electric:ReformulatedEIR COOLSYS1 CHILLER2 6.84 23.33


Zone Surfaces

Zone Name # Surfaces
1 BASEMENT 10
2 CORE_BOTTOM 8
3 CORE_MID 7
4 CORE_TOP 7
5 PERIMETER_BOT_ZN_3 18
6 PERIMETER_BOT_ZN_2 12
7 PERIMETER_BOT_ZN_1 18
8 PERIMETER_BOT_ZN_4 12
9 PERIMETER_MID_ZN_3 9
10 PERIMETER_MID_ZN_2 8
11 PERIMETER_MID_ZN_1 9
12 PERIMETER_MID_ZN_4 8
13 PERIMETER_TOP_ZN_3 9
14 PERIMETER_TOP_ZN_2 8
15 PERIMETER_TOP_ZN_1 9
16 PERIMETER_TOP_ZN_4 8
17 GROUNDFLOOR_PLENUM 11
18 MIDFLOOR_PLENUM 11
19 TOPFLOOR_PLENUM 11
20 DATACENTER_BOT_ZN_6 6
21 DATACENTER_MID_ZN_6 6
22 DATACENTER_TOP_ZN_6 6
23 DATACENTER_BASEMENT_ZN_6 10


HeatTransfer Surface

Surface Name Surface Class Base Surface Heat Transfer Algorithm Construction Nominal U (w/o film coefs) {W/m2-K} Nominal U (with film coefs) {W/m2-K} Solar Diffusing Area (Net) {m2} Area (Gross) {m2} Area (Sunlit Calc) {m2} Azimuth {deg} Tilt {deg} ~Width {m} ~Height {m} Reveal {m} ExtBoundCondition ExtConvCoeffCalc IntConvCoeffCalc SunExposure WindExposure ViewFactorToGround ViewFactorToSky ViewFactorToGround-IR ViewFactorToSky-IR #Sides
1 BASEMENT_WALL_EAST Wall   CTF - ConductionTransferFunction BASEMENT_WALL_EAST_CFACTOR 0.419 0.394   118.87 118.87 118.87 90.00 90.00 48.74 2.44 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
2 BASEMENT_WALL_SOUTH Wall   CTF - ConductionTransferFunction BASEMENT_WALL_SOUTH_CFACTOR 0.419 0.394   139.09 139.09 139.09 180.00 90.00 57.03 2.44 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
3 BASEMENT_WALL_NORTH Wall   CTF - ConductionTransferFunction BASEMENT_WALL_NORTH_CFACTOR 0.419 0.394   139.09 139.09 139.09 0.00 90.00 57.03 2.44 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
4 BASEMENT_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   118.87 118.87 118.87 270.00 90.00 48.74 2.44 0.00 DATACENTER_BASEMENT_ZN_6_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
5 BASEMENT_FLOOR Floor   CTF - ConductionTransferFunction EXT_SLAB_8IN_WITH_CARPET 3.285 1.827   2779.43 2779.43 2779.43 0.00 180.00 57.03 48.74 0.00 BASEMENT_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.00 1.00 0.00 4
6 PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   201.98 201.98 201.98 225.00 0.00 6.47 39.59 0.00 PERIMETER_BOT_ZN_2_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
7 PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   250.34 250.34 250.34 180.00 0.00 57.03 4.57 0.00 PERIMETER_BOT_ZN_1_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
8 CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   2076.77 2076.77 2076.77 180.00 0.00 52.45 39.59 0.00 CORE_BOT_ZN_5_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
9 PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   250.34 250.34 250.34 180.00 0.00 52.45 4.57 0.00 PERIMETER_BOT_ZN_3_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
10 BASEMENT_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   7126.21 7126.21 7126.21 0.00 90.00 7126.21 1.00 0.00 BASEMENT_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
11 CORE_BOT_ZN_5_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   173.00 173.00 173.00 180.00 90.00 63.05 2.74 0.00 CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
12 CORE_BOT_ZN_5_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 270.00 90.00 39.59 2.74 0.00 DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
13 CORE_BOT_ZN_5_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   173.00 173.00 173.00 0.00 90.00 63.05 2.74 0.00 CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
14 CORE_BOT_ZN_5_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 90.00 90.00 39.59 2.74 0.00 CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
15 DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   419.30 419.30 419.30 0.00 180.00 10.59 39.59 0.00 DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.00 1.00 0.00 4
16 CORE_BOT_ZN_5_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   2076.82 2076.82 2076.82 0.00 180.00 52.46 39.59 0.00 CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.00 1.00 0.00 4
17 CORE_BOT_ZN_5_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   2496.12 2496.12 2496.12 180.00 0.00 63.05 39.59 0.00 iz-CORE_BOT_ZN_5_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
18 CORE_BOTTOM_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   5064.65 5064.65 5064.65 0.00 90.00 5064.65 1.00 0.00 CORE_BOTTOM_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
19 CORE_MID_ZN_5_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   173.00 173.00 173.00 180.00 90.00 63.05 2.74 0.00 CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
20 CORE_MID_ZN_5_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 270.00 90.00 39.59 2.74 0.00 DATACENTER_MID_ZN_6_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
21 CORE_MID_ZN_5_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   173.00 173.00 173.00 0.00 90.00 63.05 2.74 0.00 CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
22 CORE_MID_ZN_5_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 90.00 90.00 39.59 2.74 0.00 CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
23 CORE_MID_ZN_5_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   2496.12 2496.12 2496.12 0.00 180.00 63.05 39.59 0.00 CORE_MID_ZN_5_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
24 CORE_MID_ZN_5_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   2496.12 2496.12 2496.12 180.00 0.00 63.05 39.59 0.00 iz-CORE_MID_ZN_5_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
25 CORE_MID_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   5064.65 5064.65 5064.65 0.00 90.00 5064.65 1.00 0.00 CORE_MID_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
26 CORE_TOP_ZN_5_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   173.00 173.00 173.00 180.00 90.00 63.05 2.74 0.00 CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
27 CORE_TOP_ZN_5_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 270.00 90.00 39.59 2.74 0.00 DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
28 CORE_TOP_ZN_5_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   173.00 173.00 173.00 0.00 90.00 63.05 2.74 0.00 CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
29 CORE_TOP_ZN_5_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 90.00 90.00 39.59 2.74 0.00 CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
30 CORE_TOP_ZN_5_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   2496.12 2496.12 2496.12 0.00 180.00 63.05 39.59 0.00 CORE_TOP_ZN_5_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
31 CORE_TOP_ZN_5_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   2496.12 2496.12 2496.12 180.00 0.00 63.05 39.59 0.00 iz-CORE_TOP_ZN_5_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
32 CORE_TOP_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   5064.65 5064.65 5064.65 0.00 90.00 5064.65 1.00 0.00 CORE_TOP_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
33 PERIMETER_BOT_ZN_3_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.969 0.846   76.91 200.61 76.91 0.00 90.00 73.11 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
34 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 Window PERIMETER_BOT_ZN_3_WALL_NORTH Window5 Detailed Fenestration WINDOW_U_0.419_SHGC_NORTH_0.4 N/A 2.381 No 23.18 23.18 23.18 0.00 90.00 13.65 1.70 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
35 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 Window PERIMETER_BOT_ZN_3_WALL_NORTH Window5 Detailed Fenestration WINDOW_U_0.419_SHGC_NORTH_0.4 N/A 2.381 No 23.18 23.18 23.18 0.00 90.00 13.65 1.70 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
36 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 Window PERIMETER_BOT_ZN_3_WALL_NORTH Window5 Detailed Fenestration WINDOW_U_0.419_SHGC_NORTH_0.4 N/A 2.381 No 23.18 23.18 23.18 0.00 90.00 13.65 1.70 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
37 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 Window PERIMETER_BOT_ZN_3_WALL_NORTH Window5 Detailed Fenestration WINDOW_U_0.419_SHGC_NORTH_0.4 N/A 2.381 No 23.18 23.18 23.18 0.00 90.00 13.65 1.70 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
38 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 Window PERIMETER_BOT_ZN_3_WALL_NORTH Window5 Detailed Fenestration WINDOW_U_0.419_SHGC_NORTH_0.4 N/A 2.381 No 23.18 23.18 23.18 0.00 90.00 13.65 1.70 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
39 PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 Door PERIMETER_BOT_ZN_3_WALL_NORTH CTF - ConductionTransferFunction SWINGING DOOR_CON 2.839 2.839   1.95 1.95 1.95 0.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
40 PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 Door PERIMETER_BOT_ZN_3_WALL_NORTH CTF - ConductionTransferFunction SWINGING DOOR_CON 2.839 2.839   1.95 1.95 1.95 0.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
41 PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 Door PERIMETER_BOT_ZN_3_WALL_NORTH CTF - ConductionTransferFunction SWINGING DOOR_CON 2.839 2.839   1.95 1.95 1.95 0.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
42 PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 Door PERIMETER_BOT_ZN_3_WALL_NORTH CTF - ConductionTransferFunction SWINGING DOOR_CON 2.839 2.839   1.95 1.95 1.95 0.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
43 PERIMETER_BOT_ZN_3_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 225.00 90.00 6.47 2.74 0.00 PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
44 CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   173.00 173.00 173.00 180.00 90.00 63.05 2.74 0.00 CORE_BOT_ZN_5_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
45 PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 135.00 90.00 6.47 2.74 0.00 PERIMETER_BOT_ZN_2_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
46 DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   2.51 2.51 2.51 180.00 90.00 0.91 2.74 0.00 DATACENTER_BOT_ZN_6_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
47 PERIMETER_BOT_ZN_3_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   250.34 250.34 250.34 0.00 180.00 52.46 6.47 0.00 PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
48 DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   63.07 63.07 63.07 0.00 180.00 11.51 4.57 0.00 DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.00 1.00 0.00 4
49 PERIMETER_BOT_ZN_3_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   313.41 313.41 313.41 180.00 0.00 63.96 6.47 0.00 iz-PERIMETER_BOT_ZN_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
50 PERIMETER_BOT_ZN_3_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   626.83 626.83 626.83 0.00 90.00 626.83 1.00 0.00 PERIMETER_BOT_ZN_3_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
51 PERIMETER_BOT_ZN_2_WALL_EAST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.969 0.846   52.57 133.74 52.57 90.00 90.00 48.74 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
52 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 Window PERIMETER_BOT_ZN_2_WALL_EAST Window5 Detailed Fenestration WINDOW_U_0.419_SHGC_EAST_0.4 N/A 2.381 No 25.75 25.75 25.75 90.00 90.00 15.43 1.67 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
53 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 Window PERIMETER_BOT_ZN_2_WALL_EAST Window5 Detailed Fenestration WINDOW_U_0.419_SHGC_EAST_0.4 N/A 2.381 No 25.75 25.75 25.75 90.00 90.00 15.43 1.67 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
54 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 Window PERIMETER_BOT_ZN_2_WALL_EAST Window5 Detailed Fenestration WINDOW_U_0.419_SHGC_EAST_0.4 N/A 2.381 No 25.75 25.75 25.75 90.00 90.00 15.43 1.67 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
55 PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 Door PERIMETER_BOT_ZN_2_WALL_EAST CTF - ConductionTransferFunction SWINGING DOOR_CON 2.839 2.839   1.95 1.95 1.95 90.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
56 PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 Door PERIMETER_BOT_ZN_2_WALL_EAST CTF - ConductionTransferFunction SWINGING DOOR_CON 2.839 2.839   1.95 1.95 1.95 90.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
57 PERIMETER_BOT_ZN_2_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 315.00 90.00 6.47 2.74 0.00 PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
58 CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 270.00 90.00 39.59 2.74 0.00 CORE_BOT_ZN_5_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
59 PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 225.00 90.00 6.47 2.74 0.00 PERIMETER_BOT_ZN_1_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
60 PERIMETER_BOT_ZN_2_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   201.98 201.98 201.98 45.00 180.00 6.47 48.74 0.00 PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
61 PERIMETER_BOT_ZN_2_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   201.98 201.98 201.98 225.00 0.00 6.47 39.59 0.00 iz-PERIMETER_BOT_ZN_2_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
62 PERIMETER_BOT_ZN_2_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   403.95 403.95 403.95 0.00 90.00 403.95 1.00 0.00 PERIMETER_BOT_ZN_2_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
63 PERIMETER_BOT_ZN_1_WALL_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.969 0.846   76.91 200.61 76.91 180.00 90.00 73.11 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
64 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 Window PERIMETER_BOT_ZN_1_WALL_SOUTH Window5 Detailed Fenestration WINDOW_U_0.419_SHGC_SOUTH_0.4 N/A 2.381 No 23.18 23.18 23.18 180.00 90.00 13.65 1.70 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
65 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 Window PERIMETER_BOT_ZN_1_WALL_SOUTH Window5 Detailed Fenestration WINDOW_U_0.419_SHGC_SOUTH_0.4 N/A 2.381 No 23.18 23.18 23.18 180.00 90.00 13.65 1.70 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
66 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 Window PERIMETER_BOT_ZN_1_WALL_SOUTH Window5 Detailed Fenestration WINDOW_U_0.419_SHGC_SOUTH_0.4 N/A 2.381 No 23.18 23.18 23.18 180.00 90.00 13.65 1.70 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
67 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 Window PERIMETER_BOT_ZN_1_WALL_SOUTH Window5 Detailed Fenestration WINDOW_U_0.419_SHGC_SOUTH_0.4 N/A 2.381 No 23.18 23.18 23.18 180.00 90.00 13.65 1.70 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
68 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 Window PERIMETER_BOT_ZN_1_WALL_SOUTH Window5 Detailed Fenestration WINDOW_U_0.419_SHGC_SOUTH_0.4 N/A 2.381 No 23.18 23.18 23.18 180.00 90.00 13.65 1.70 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
69 PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 Door PERIMETER_BOT_ZN_1_WALL_SOUTH CTF - ConductionTransferFunction SWINGING DOOR_CON 2.839 2.839   1.95 1.95 1.95 180.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
70 PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 Door PERIMETER_BOT_ZN_1_WALL_SOUTH CTF - ConductionTransferFunction SWINGING DOOR_CON 2.839 2.839   1.95 1.95 1.95 180.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
71 PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 Door PERIMETER_BOT_ZN_1_WALL_SOUTH CTF - ConductionTransferFunction SWINGING DOOR_CON 2.839 2.839   1.95 1.95 1.95 180.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
72 PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 Door PERIMETER_BOT_ZN_1_WALL_SOUTH CTF - ConductionTransferFunction SWINGING DOOR_CON 2.839 2.839   1.95 1.95 1.95 180.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
73 PERIMETER_BOT_ZN_1_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 45.00 90.00 6.47 2.74 0.00 PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
74 DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   2.51 2.51 2.51 0.00 90.00 0.91 2.74 0.00 DATACENTER_BOT_ZN_6_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
75 PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 315.00 90.00 6.47 2.74 0.00 PERIMETER_BOT_ZN_4_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
76 CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   173.00 173.00 173.00 0.00 90.00 63.05 2.74 0.00 CORE_BOT_ZN_5_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
77 DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   63.07 63.07 63.07 0.00 180.00 16.08 4.57 0.00 DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.00 1.00 0.00 4
78 PERIMETER_BOT_ZN_1_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   250.35 250.35 250.35 0.00 180.00 57.03 6.47 0.00 PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.00 1.00 0.00 4
79 PERIMETER_BOT_ZN_1_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   313.42 313.42 313.42 180.00 0.00 73.11 6.47 0.00 iz-PERIMETER_BOT_ZN_1_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
80 PERIMETER_BOT_ZN_1_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   626.84 626.84 626.84 0.00 90.00 626.84 1.00 0.00 PERIMETER_BOT_ZN_1_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
81 PERIMETER_BOT_ZN_4_WALL_WEST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.969 0.846   52.57 133.74 52.57 270.00 90.00 48.74 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
82 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 Window PERIMETER_BOT_ZN_4_WALL_WEST Window5 Detailed Fenestration WINDOW_U_0.419_SHGC_WEST_0.4 N/A 2.381 No 25.75 25.75 25.75 270.00 90.00 15.43 1.67 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
83 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 Window PERIMETER_BOT_ZN_4_WALL_WEST Window5 Detailed Fenestration WINDOW_U_0.419_SHGC_WEST_0.4 N/A 2.381 No 25.75 25.75 25.75 270.00 90.00 15.43 1.67 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
84 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 Window PERIMETER_BOT_ZN_4_WALL_WEST Window5 Detailed Fenestration WINDOW_U_0.419_SHGC_WEST_0.4 N/A 2.381 No 25.75 25.75 25.75 270.00 90.00 15.43 1.67 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
85 PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 Door PERIMETER_BOT_ZN_4_WALL_WEST CTF - ConductionTransferFunction SWINGING DOOR_CON 2.839 2.839   1.95 1.95 1.95 270.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
86 PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 Door PERIMETER_BOT_ZN_4_WALL_WEST CTF - ConductionTransferFunction SWINGING DOOR_CON 2.839 2.839   1.95 1.95 1.95 270.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
87 PERIMETER_BOT_ZN_4_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 135.00 90.00 6.47 2.74 0.00 PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
88 DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 90.00 90.00 39.59 2.74 0.00 DATACENTER_BOT_ZN_6_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
89 PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 45.00 90.00 6.47 2.74 0.00 PERIMETER_BOT_ZN_3_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
90 PERIMETER_BOT_ZN_4_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   201.98 201.98 201.98 315.00 180.00 6.47 39.59 0.00 PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.00 1.00 0.00 4
91 PERIMETER_BOT_ZN_4_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   201.98 201.98 201.98 135.00 0.00 6.47 48.74 0.00 iz-PERIMETER_BOT_ZN_4_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
92 PERIMETER_BOT_ZN_4_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   403.95 403.95 403.95 0.00 90.00 403.95 1.00 0.00 PERIMETER_BOT_ZN_4_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
93 PERIMETER_MID_ZN_3_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 0.924 0.811   84.71 200.61 84.71 0.00 90.00 73.11 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
94 PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW Window PERIMETER_MID_ZN_3_WALL_NORTH Window5 Detailed Fenestration WINDOW_U_0.419_SHGC_NORTH_0.4 N/A 2.381 No 115.90 115.90 115.90 0.00 90.00 73.11 1.59 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
95 PERIMETER_MID_ZN_3_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 225.00 90.00 6.47 2.74 0.00 PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
96 CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   173.00 173.00 173.00 180.00 90.00 63.05 2.74 0.00 CORE_MID_ZN_5_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
97 PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 135.00 90.00 6.47 2.74 0.00 PERIMETER_MID_ZN_2_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
98 DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   2.51 2.51 2.51 180.00 90.00 0.91 2.74 0.00 DATACENTER_MID_ZN_6_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
99 PERIMETER_MID_ZN_3_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   313.41 313.41 313.41 0.00 180.00 63.96 6.47 0.00 PERIMETER_MID_ZN_3_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
100 PERIMETER_MID_ZN_3_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   313.41 313.41 313.41 180.00 0.00 63.96 6.47 0.00 iz-PERIMETER_MID_ZN_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
101 PERIMETER_MID_ZN_3_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   626.83 626.83 626.83 0.00 90.00 626.83 1.00 0.00 PERIMETER_MID_ZN_3_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
102 PERIMETER_MID_ZN_2_WALL_EAST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 0.924 0.811   56.47 133.74 56.47 90.00 90.00 48.74 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
103 PERIMETER_MID_ZN_2_WALL_EAST_WINDOW Window PERIMETER_MID_ZN_2_WALL_EAST Window5 Detailed Fenestration WINDOW_U_0.419_SHGC_EAST_0.4 N/A 2.381 No 77.26 77.26 77.26 90.00 90.00 48.74 1.59 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
104 PERIMETER_MID_ZN_2_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 315.00 90.00 6.47 2.74 0.00 PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
105 CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 270.00 90.00 39.59 2.74 0.00 CORE_MID_ZN_5_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
106 PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 225.00 90.00 6.47 2.74 0.00 PERIMETER_MID_ZN_1_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
107 PERIMETER_MID_ZN_2_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   201.98 201.98 201.98 45.00 180.00 6.47 48.74 0.00 PERIMETER_MID_ZN_2_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
108 PERIMETER_MID_ZN_2_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   201.98 201.98 201.98 225.00 0.00 6.47 39.59 0.00 iz-PERIMETER_MID_ZN_2_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
109 PERIMETER_MID_ZN_2_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   403.95 403.95 403.95 0.00 90.00 403.95 1.00 0.00 PERIMETER_MID_ZN_2_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
110 PERIMETER_MID_ZN_1_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 45.00 90.00 6.47 2.74 0.00 PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
111 PERIMETER_MID_ZN_1_WALL_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 0.924 0.811   84.71 200.61 84.71 180.00 90.00 73.11 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
112 PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW Window PERIMETER_MID_ZN_1_WALL_SOUTH Window5 Detailed Fenestration WINDOW_U_0.419_SHGC_SOUTH_0.4 N/A 2.381 No 115.90 115.90 115.90 180.00 90.00 73.11 1.59 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
113 DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   2.51 2.51 2.51 0.00 90.00 0.91 2.74 0.00 DATACENTER_MID_ZN_6_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
114 PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 315.00 90.00 6.47 2.74 0.00 PERIMETER_MID_ZN_4_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
115 CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   173.00 173.00 173.00 0.00 90.00 63.05 2.74 0.00 CORE_MID_ZN_5_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
116 PERIMETER_MID_ZN_1_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   313.42 313.42 313.42 0.00 180.00 73.11 6.47 0.00 PERIMETER_MID_ZN_1_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
117 PERIMETER_MID_ZN_1_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   313.42 313.42 313.42 180.00 0.00 73.11 6.47 0.00 iz-PERIMETER_MID_ZN_1_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
118 PERIMETER_MID_ZN_1_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   626.84 626.84 626.84 0.00 90.00 626.84 1.00 0.00 PERIMETER_MID_ZN_1_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
119 PERIMETER_MID_ZN_4_WALL_WEST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 0.924 0.811   56.47 133.74 56.47 270.00 90.00 48.74 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
120 PERIMETER_MID_ZN_4_WALL_WEST_WINDOW Window PERIMETER_MID_ZN_4_WALL_WEST Window5 Detailed Fenestration WINDOW_U_0.419_SHGC_WEST_0.4 N/A 2.381 No 77.26 77.26 77.26 270.00 90.00 48.74 1.59 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
121 PERIMETER_MID_ZN_4_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 135.00 90.00 6.47 2.74 0.00 PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
122 DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 90.00 90.00 39.59 2.74 0.00 DATACENTER_MID_ZN_6_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
123 PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 45.00 90.00 6.47 2.74 0.00 PERIMETER_MID_ZN_3_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
124 PERIMETER_MID_ZN_4_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   201.98 201.98 201.98 315.00 180.00 6.47 39.59 0.00 PERIMETER_MID_ZN_4_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
125 PERIMETER_MID_ZN_4_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   201.98 201.98 201.98 135.00 0.00 6.47 48.74 0.00 iz-PERIMETER_MID_ZN_4_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
126 PERIMETER_MID_ZN_4_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   403.95 403.95 403.95 0.00 90.00 403.95 1.00 0.00 PERIMETER_MID_ZN_4_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
127 PERIMETER_TOP_ZN_3_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.155 0.985   84.71 200.61 84.71 0.00 90.00 73.11 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
128 PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW Window PERIMETER_TOP_ZN_3_WALL_NORTH Window5 Detailed Fenestration WINDOW_U_0.419_SHGC_NORTH_0.4 N/A 2.381 No 115.90 115.90 115.90 0.00 90.00 73.11 1.59 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
129 PERIMETER_TOP_ZN_3_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 225.00 90.00 6.47 2.74 0.00 PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
130 CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   173.00 173.00 173.00 180.00 90.00 63.05 2.74 0.00 CORE_TOP_ZN_5_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
131 PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 135.00 90.00 6.47 2.74 0.00 PERIMETER_TOP_ZN_2_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
132 DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   2.51 2.51 2.51 180.00 90.00 0.91 2.74 0.00 DATACENTER_TOP_ZN_6_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
133 PERIMETER_TOP_ZN_3_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   313.41 313.41 313.41 0.00 180.00 63.96 6.47 0.00 PERIMETER_TOP_ZN_3_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
134 PERIMETER_TOP_ZN_3_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   313.41 313.41 313.41 180.00 0.00 63.96 6.47 0.00 iz-PERIMETER_TOP_ZN_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
135 PERIMETER_TOP_ZN_3_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   626.83 626.83 626.83 0.00 90.00 626.83 1.00 0.00 PERIMETER_TOP_ZN_3_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
136 PERIMETER_TOP_ZN_2_WALL_EAST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.155 0.985   56.47 133.74 56.47 90.00 90.00 48.74 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
137 PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW Window PERIMETER_TOP_ZN_2_WALL_EAST Window5 Detailed Fenestration WINDOW_U_0.419_SHGC_EAST_0.4 N/A 2.381 No 77.26 77.26 77.26 90.00 90.00 48.74 1.59 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
138 PERIMETER_TOP_ZN_2_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 315.00 90.00 6.47 2.74 0.00 PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
139 CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 270.00 90.00 39.59 2.74 0.00 CORE_TOP_ZN_5_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
140 INT-PER3S-NE-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 225.00 90.00 6.47 2.74 0.00 INT-PER3S-NE Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
141 PERIMETER_TOP_ZN_2_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   201.98 201.98 201.98 45.00 180.00 6.47 48.74 0.00 PERIMETER_TOP_ZN_2_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
142 PERIMETER_TOP_ZN_2_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   201.98 201.98 201.98 225.00 0.00 6.47 39.59 0.00 iz-PERIMETER_TOP_ZN_2_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
143 PERIMETER_TOP_ZN_2_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   403.95 403.95 403.95 0.00 90.00 403.95 1.00 0.00 PERIMETER_TOP_ZN_2_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
144 PERIMETER_TOP_ZN_1_WALL_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.155 0.985   84.71 200.61 84.71 180.00 90.00 73.11 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
145 PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW Window PERIMETER_TOP_ZN_1_WALL_SOUTH Window5 Detailed Fenestration WINDOW_U_0.419_SHGC_SOUTH_0.4 N/A 2.381 No 115.90 115.90 115.90 180.00 90.00 73.11 1.59 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
146 INT-PER3S-NE Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 45.00 90.00 6.47 2.74 0.00 INT-PER3S-NE-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
147 DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   2.51 2.51 2.51 0.00 90.00 0.91 2.74 0.00 DATACENTER_TOP_ZN_6_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
148 PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 315.00 90.00 6.47 2.74 0.00 PERIMETER_TOP_ZN_4_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
149 CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   173.00 173.00 173.00 0.00 90.00 63.05 2.74 0.00 CORE_TOP_ZN_5_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
150 PERIMETER_TOP_ZN_1_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   313.42 313.42 313.42 0.00 180.00 73.11 6.47 0.00 PERIMETER_TOP_ZN_1_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
151 PERIMETER_TOP_ZN_1_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   313.42 313.42 313.42 180.00 0.00 73.11 6.47 0.00 iz-PERIMETER_TOP_ZN_1_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
152 PERIMETER_TOP_ZN_1_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   626.84 626.84 626.84 0.00 90.00 626.84 1.00 0.00 PERIMETER_TOP_ZN_1_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
153 PERIMETER_TOP_ZN_4_WALL_WEST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.155 0.985   56.47 133.74 56.47 270.00 90.00 48.74 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
154 PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW Window PERIMETER_TOP_ZN_4_WALL_WEST Window5 Detailed Fenestration WINDOW_U_0.419_SHGC_WEST_0.4 N/A 2.381 No 77.26 77.26 77.26 270.00 90.00 48.74 1.59 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
155 PERIMETER_TOP_ZN_4_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 135.00 90.00 6.47 2.74 0.00 PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
156 DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 90.00 90.00 39.59 2.74 0.00 DATACENTER_TOP_ZN_6_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
157 PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 45.00 90.00 6.47 2.74 0.00 PERIMETER_TOP_ZN_3_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
158 PERIMETER_TOP_ZN_4_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   201.98 201.98 201.98 315.00 180.00 6.47 39.59 0.00 PERIMETER_TOP_ZN_4_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
159 PERIMETER_TOP_ZN_4_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   201.98 201.98 201.98 135.00 0.00 6.47 48.74 0.00 iz-PERIMETER_TOP_ZN_4_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
160 PERIMETER_TOP_ZN_4_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   403.95 403.95 403.95 0.00 90.00 403.95 1.00 0.00 PERIMETER_TOP_ZN_4_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
161 GROUNDFLOOR_PLENUM_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.969 0.846   89.13 89.13 89.13 0.00 90.00 73.11 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
162 GROUNDFLOOR_PLENUM_WEST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.969 0.846   59.42 59.42 59.42 270.00 90.00 48.74 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
163 GROUNDFLOOR_PLENUM_WALL_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.969 0.846   89.13 89.13 89.13 180.00 90.00 73.11 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
164 GROUNDFLOOR_PLENUM_WALL_EAST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.969 0.846   59.42 59.42 59.42 90.00 90.00 48.74 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
165 iz-CORE_BOT_ZN_5_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   2496.12 2496.12 2496.12 0.00 180.00 63.05 39.59 0.00 CORE_BOT_ZN_5_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
166 iz-PERIMETER_BOT_ZN_3_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   313.41 313.41 313.41 0.00 180.00 63.96 6.47 0.00 PERIMETER_BOT_ZN_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
167 iz-PERIMETER_BOT_ZN_2_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   201.98 201.98 201.98 45.00 180.00 6.47 48.74 0.00 PERIMETER_BOT_ZN_2_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
168 iz-PERIMETER_BOT_ZN_1_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   313.42 313.42 313.42 0.00 180.00 73.11 6.47 0.00 PERIMETER_BOT_ZN_1_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
169 iz-PERIMETER_BOT_ZN_4_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   201.98 201.98 201.98 315.00 180.00 6.47 39.59 0.00 PERIMETER_BOT_ZN_4_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
170 iz-DATACENTER_BOT_ZN_6_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   36.20 36.20 36.20 0.00 180.00 0.91 39.59 0.00 DATACENTER_BOT_ZN_6_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
171 GROUNDFLOOR_PLENUM_CEILING Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   3563.11 3563.11 3563.11 180.00 0.00 73.11 48.74 0.00 GROUNDFLOOR_PLENUM_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
172 MIDFLOOR_PLENUM_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 0.924 0.811   89.13 89.13 89.13 0.00 90.00 73.11 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
173 MIDFLOOR_PLENUM_WALL_WEST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 0.924 0.811   59.42 59.42 59.42 270.00 90.00 48.74 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
174 MIDFLOOR_PLENUM_WALL_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 0.924 0.811   89.13 89.13 89.13 180.00 90.00 73.11 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
175 MIDFLOOR_PLENUM_WALL_EAST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 0.924 0.811   59.42 59.42 59.42 90.00 90.00 48.74 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
176 iz-CORE_MID_ZN_5_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   2496.12 2496.12 2496.12 0.00 180.00 63.05 39.59 0.00 CORE_MID_ZN_5_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
177 iz-PERIMETER_MID_ZN_3_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   313.41 313.41 313.41 0.00 180.00 63.96 6.47 0.00 PERIMETER_MID_ZN_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
178 iz-PERIMETER_MID_ZN_2_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   201.98 201.98 201.98 45.00 180.00 6.47 48.74 0.00 PERIMETER_MID_ZN_2_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
179 iz-PERIMETER_MID_ZN_1_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   313.42 313.42 313.42 0.00 180.00 73.11 6.47 0.00 PERIMETER_MID_ZN_1_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
180 iz-PERIMETER_MID_ZN_4_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   201.98 201.98 201.98 315.00 180.00 6.47 39.59 0.00 PERIMETER_MID_ZN_4_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
181 iz-DATACENTER_MID_ZN_6_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   36.20 36.20 36.20 0.00 180.00 0.91 39.59 0.00 DATACENTER_MID_ZN_6_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
182 MIDFLOOR_PLENUM_CEILING Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   3563.11 3563.11 3563.11 180.00 0.00 73.11 48.74 0.00 MIDFLOOR_PLENUM_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
183 TOPFLOOR_PLENUM_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.155 0.985   89.13 89.13 89.13 180.00 90.00 73.11 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
184 TOPFLOOR_PLENUM_WALL_EAST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.155 0.985   59.42 59.42 59.42 90.00 90.00 48.74 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
185 TOPFLOOR_PLENUM_WALL_WEST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.155 0.985   59.42 59.42 59.42 270.00 90.00 48.74 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
186 TOPFLOOR_PLENUM_WALL_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.155 0.985   89.13 89.13 89.13 0.00 90.00 73.11 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
187 iz-CORE_TOP_ZN_5_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   2496.12 2496.12 2496.12 0.00 180.00 63.05 39.59 0.00 CORE_TOP_ZN_5_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
188 iz-PERIMETER_TOP_ZN_3_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   313.41 313.41 313.41 0.00 180.00 63.96 6.47 0.00 PERIMETER_TOP_ZN_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
189 iz-PERIMETER_TOP_ZN_2_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   201.98 201.98 201.98 45.00 180.00 6.47 48.74 0.00 PERIMETER_TOP_ZN_2_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
190 iz-PERIMETER_TOP_ZN_1_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   313.42 313.42 313.42 0.00 180.00 73.11 6.47 0.00 PERIMETER_TOP_ZN_1_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
191 iz-PERIMETER_TOP_ZN_4_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   201.98 201.98 201.98 315.00 180.00 6.47 39.59 0.00 PERIMETER_TOP_ZN_4_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
192 iz-DATACENTER_TOP_ZN_6_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   36.20 36.20 36.20 0.00 180.00 0.91 39.59 0.00 DATACENTER_TOP_ZN_6_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
193 BUILDING_ROOF Roof   CTF - ConductionTransferFunction NONRES_ROOF 0.186 0.180   3563.11 3563.11 3563.11 180.00 0.00 73.11 48.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 4
194 DATACENTER_BOT_ZN_6_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   2.51 2.51 2.51 0.00 90.00 0.91 2.74 0.00 DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
195 DATACENTER_BOT_ZN_6_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   2.51 2.51 2.51 180.00 90.00 0.91 2.74 0.00 DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
196 DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 90.00 90.00 39.59 2.74 0.00 CORE_BOT_ZN_5_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
197 DATACENTER_BOT_ZN_6_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 270.00 90.00 39.59 2.74 0.00 DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
198 DATACENTER_BOT_ZN_6_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   36.20 36.20 36.20 0.00 180.00 0.91 39.59 0.00 DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.00 1.00 0.00 4
199 DATACENTER_BOT_ZN_6_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   36.20 36.20 36.20 180.00 0.00 0.91 39.59 0.00 iz-DATACENTER_BOT_ZN_6_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
200 DATACENTER_MID_ZN_6_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 270.00 90.00 39.59 2.74 0.00 DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
201 DATACENTER_MID_ZN_6_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   2.51 2.51 2.51 180.00 90.00 0.91 2.74 0.00 DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
202 DATACENTER_MID_ZN_6_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 90.00 90.00 39.59 2.74 0.00 CORE_MID_ZN_5_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
203 DATACENTER_MID_ZN_6_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   2.51 2.51 2.51 0.00 90.00 0.91 2.74 0.00 DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
204 DATACENTER_MID_ZN_6_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   36.20 36.20 36.20 0.00 180.00 0.91 39.59 0.00 DATACENTER_MID_ZN_6_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.00 1.00 0.00 4
205 DATACENTER_MID_ZN_6_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   36.20 36.20 36.20 180.00 0.00 0.91 39.59 0.00 iz-DATACENTER_MID_ZN_6_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
206 DATACENTER_TOP_ZN_6_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 90.00 90.00 39.59 2.74 0.00 CORE_TOP_ZN_5_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
207 DATACENTER_TOP_ZN_6_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 270.00 90.00 39.59 2.74 0.00 DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
208 DATACENTER_TOP_ZN_6_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   2.51 2.51 2.51 180.00 90.00 0.91 2.74 0.00 DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
209 DATACENTER_TOP_ZN_6_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   2.51 2.51 2.51 0.00 90.00 0.91 2.74 0.00 DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
210 DATACENTER_TOP_ZN_6_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   36.20 36.20 36.20 0.00 180.00 0.91 39.59 0.00 DATACENTER_TOP_ZN_6_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.00 1.00 0.00 4
211 DATACENTER_TOP_ZN_6_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   36.20 36.20 36.20 180.00 0.00 0.91 39.59 0.00 iz-DATACENTER_TOP_ZN_6_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
212 DATACENTER_BASEMENT_ZN_6_WALL_NORTH Wall   CTF - ConductionTransferFunction DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR 0.419 0.394   39.22 39.22 39.22 0.00 90.00 16.08 2.44 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
213 DATACENTER_BASEMENT_ZN_6_WALL_SOUTH Wall   CTF - ConductionTransferFunction DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR 0.419 0.394   39.22 39.22 39.22 180.00 90.00 16.08 2.44 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
214 DATACENTER_BASEMENT_ZN_6_WALL_WEST Wall   CTF - ConductionTransferFunction DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR 0.419 0.394   118.87 118.87 118.87 270.00 90.00 48.74 2.44 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
215 DATACENTER_BASEMENT_ZN_6_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   118.87 118.87 118.87 90.00 90.00 48.74 2.44 0.00 BASEMENT_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
216 DATACENTER_BASEMENT_ZN_6_FLOOR Floor   CTF - ConductionTransferFunction EXT_SLAB_8IN_WITH_CARPET 3.285 1.827   783.68 783.68 783.68 0.00 180.00 16.08 48.74 0.00 DATACENTER_BASEMENT_ZN_6_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.00 1.00 0.00 4
217 DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   36.20 36.20 36.20 180.00 0.00 0.91 39.59 0.00 DATACENTER_BOT_ZN_6_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
218 DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   419.35 419.35 419.35 180.00 0.00 10.59 39.59 0.00 DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
219 PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   201.98 201.98 201.98 135.00 0.00 6.47 48.74 0.00 PERIMETER_BOT_ZN_4_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
220 DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   63.08 63.08 63.08 180.00 0.00 16.08 6.47 0.00 DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
221 DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   63.07 63.07 63.07 180.00 0.00 11.51 6.47 0.00 DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4


Environment

Environment Name Environment Type Start Date End Date Start DayOfWeek Duration {#days} Source:Start DayOfWeek Use Daylight Saving Use Holidays Apply Weekend Holiday Rule Use Rain Values Use Snow Values Sky Temperature Model
1 RUNPERIOD 1 WeatherFileRunPeriod 01/01/2017 12/31/2017 Sunday 365 Use RunPeriod Specified Day No No No Yes Yes Clark and Allen


Environment:Special Days

Special Day Name Special Day Type Source Start Date Duration {#days}
1 NEW YEARS DAY Holiday InputFile 01/01 1Environment:Special Days


Environment:Daylight Saving

Daylight Saving Indicator Source Start Date End Date
1 Yes InputFile 03/12 11/05


Tabular Report

Style Unit Conversion
1 Commaandhtml commaandhtml


Warmup Convergence Information

Zone Name Environment Type/Name Average Warmup Temperature Difference {deltaC} Std Dev Warmup Temperature Difference {deltaC} Max Temperature Pass/Fail Convergence Min Temperature Pass/Fail Convergence Average Warmup Load Difference {W} Std Dev Warmup Load Difference {W} Heating Load Pass/Fail Convergence Cooling Load Pass/Fail Convergence
1 BASEMENT RunPeriod: RUNPERIOD 1 8.8197119478E-004 1.3622251042E-003 Pass Pass 0.0000000000 0.0000000000 Pass Pass
2 CORE_BOTTOM RunPeriod: RUNPERIOD 1 3.2637055953E-003 6.0388546469E-003 Pass Pass 0.0000000000 0.0000000000 Pass Pass
3 CORE_MID RunPeriod: RUNPERIOD 1 4.4000822093E-002 2.2593418275E-002 Pass Pass 0.4983660349 0.4988075775 Pass Pass
4 CORE_TOP RunPeriod: RUNPERIOD 1 3.0338503933E-002 3.6026141501E-002 Pass Pass 6.0129095840 21.9534546087 Pass Pass
5 PERIMETER_BOT_ZN_3 RunPeriod: RUNPERIOD 1 2.2262872073E-002 1.6372235360E-002 Pass Pass 0.0000000000 0.0000000000 Pass Pass
6 PERIMETER_BOT_ZN_2 RunPeriod: RUNPERIOD 1 2.2243940104E-002 1.6008266567E-002 Pass Pass 0.0000000000 0.0000000000 Pass Pass
7 PERIMETER_BOT_ZN_1 RunPeriod: RUNPERIOD 1 2.5322108386E-002 1.9431335342E-002 Pass Pass 0.0000000000 0.0000000000 Pass Pass
8 PERIMETER_BOT_ZN_4 RunPeriod: RUNPERIOD 1 2.3883239338E-002 1.8348102815E-002 Pass Pass 0.0000000000 0.0000000000 Pass Pass
9 PERIMETER_MID_ZN_3 RunPeriod: RUNPERIOD 1 0.3088522323 0.2912737737 Pass Pass 22.4672297207 136.4592426010 Pass Pass
10 PERIMETER_MID_ZN_2 RunPeriod: RUNPERIOD 1 0.3296292783 0.3181279079 Pass Pass 7.6732813399 31.9545786460 Pass Pass
11 PERIMETER_MID_ZN_1 RunPeriod: RUNPERIOD 1 0.2905727208 0.2921635166 Pass Pass 11.1282365965 45.2190287792 Pass Pass
12 PERIMETER_MID_ZN_4 RunPeriod: RUNPERIOD 1 0.2177049975 0.2299000972 Pass Pass 8.5993192998 31.8087891681 Pass Pass
13 PERIMETER_TOP_ZN_3 RunPeriod: RUNPERIOD 1 0.4601956769 0.4274095015 Pass Pass 22.8707542309 99.5694404694 Pass Pass
14 PERIMETER_TOP_ZN_2 RunPeriod: RUNPERIOD 1 0.4882274058 0.4706600285 Pass Pass 12.2243758192 50.9844402673 Pass Pass
15 PERIMETER_TOP_ZN_1 RunPeriod: RUNPERIOD 1 0.4436403355 0.4403555644 Pass Pass 19.7426474786 92.1882097508 Pass Pass
16 PERIMETER_TOP_ZN_4 RunPeriod: RUNPERIOD 1 0.3823242963 0.3827435055 Pass Pass 9.2859741888 32.5816145562 Pass Pass
17 GROUNDFLOOR_PLENUM RunPeriod: RUNPERIOD 1 6.8171619333E-003 5.1190637123E-003 Pass Pass 0.0000000000 0.0000000000 Pass Pass
18 MIDFLOOR_PLENUM RunPeriod: RUNPERIOD 1 5.1358146103E-002 2.7915403351E-002 Pass Pass 0.4974157831 0.4604313827 Pass Pass
19 TOPFLOOR_PLENUM RunPeriod: RUNPERIOD 1 0.1258742029 8.2571127484E-002 Pass Pass 0.4921644610 0.4752886126 Pass Pass
20 DATACENTER_BOT_ZN_6 RunPeriod: RUNPERIOD 1 3.5669644974E-007 6.1117558629E-007 Pass Pass 4.9732262352E-003 3.5959972228E-003 Pass Pass
21 DATACENTER_MID_ZN_6 RunPeriod: RUNPERIOD 1 6.1616029155E-003 4.2544221725E-003 Pass Pass 2.1174975649E-003 2.0704004788E-003 Pass Pass
22 DATACENTER_TOP_ZN_6 RunPeriod: RUNPERIOD 1 9.1010676820E-003 6.5827047050E-003 Pass Pass 3.3713096542E-003 3.1419608490E-003 Pass Pass
23 DATACENTER_BASEMENT_ZN_6 RunPeriod: RUNPERIOD 1 6.9288376501E-006 3.9957508092E-006 Pass Pass 4.4336168617E-005 1.0936075044E-004 Pass Pass



Table of Contents

Report: Annual Heat Emissions Summary

For: Entire Facility

Timestamp: 2023-10-16 08:43:24

Heat Emission by Components

Envelope Convection Zone Exfiltration Zone Exhaust Air HVAC Relief Air HVAC Reject Heat Total
Heat Emissions [GJ] 6735.40 307.22 0.00 28895.19 11576.07 47513.88



Table of Contents

Report: Climatic Data Summary

For: Entire Facility

Timestamp: 2023-10-16 08:43:24

SizingPeriod:DesignDay

Maximum Dry Bulb [C] Daily Temperature Range [deltaC] Humidity Value Humidity Type Wind Speed [m/s] Wind Direction
BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB -16.30 0.00 -16.30 Wetbulb [C] 5.10 270.00
BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 30.30 9.30 21.80 Wetbulb [C] 5.70 240.00


Monthly Precipitation Summary

Monthly Total Precipitation from .epw [mm] Monthly Total Hours of Rain from .epw Monthly Total Precipitation in Site:Precipitation [mm] Monthly Total Roof Irrigation Depth [mm] Monthly Total Rain Collection Volume [m3]
Jan 0.00 0      
Feb 0.00 0      
Mar 0.00 0      
Apr 0.00 0      
May 44.00 33      
Jun 0.00 0      
Jul 0.00 0      
Aug 0.00 0      
Sep 67.00 33      
Oct 0.00 0      
Nov 0.00 0      
Dec 0.00 0      


Weather Statistics File

Value
None  



Table of Contents

Report: Envelope Summary

For: Entire Facility

Timestamp: 2023-10-16 08:43:24

Opaque Exterior

Construction Reflectance U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Net Area [m2] Azimuth [deg] Tilt [deg] Cardinal Direction
BASEMENT_WALL_EAST BASEMENT_WALL_EAST_CFACTOR 1.00 0.399 0.419 118.87 118.87 90.00 90.00 E
BASEMENT_WALL_SOUTH BASEMENT_WALL_SOUTH_CFACTOR 1.00 0.399 0.419 139.09 139.09 180.00 90.00 S
BASEMENT_WALL_NORTH BASEMENT_WALL_NORTH_CFACTOR 1.00 0.399 0.419 139.09 139.09 0.00 90.00 N
PERIMETER_BOT_ZN_3_WALL_NORTH NONRES_EXT_WALL_GRD 0.30 0.846 0.969 200.61 76.91 0.00 90.00 N
PERIMETER_BOT_ZN_2_WALL_EAST NONRES_EXT_WALL_GRD 0.30 0.846 0.969 133.74 52.57 90.00 90.00 E
PERIMETER_BOT_ZN_1_WALL_SOUTH NONRES_EXT_WALL_GRD 0.30 0.846 0.969 200.61 76.91 180.00 90.00 S
PERIMETER_BOT_ZN_4_WALL_WEST NONRES_EXT_WALL_GRD 0.30 0.846 0.969 133.74 52.57 270.00 90.00 W
PERIMETER_MID_ZN_3_WALL_NORTH NONRES_EXT_WALL_MID 0.30 0.811 0.924 2006.06 847.11 0.00 90.00 N
PERIMETER_MID_ZN_2_WALL_EAST NONRES_EXT_WALL_MID 0.30 0.811 0.924 1337.37 564.74 90.00 90.00 E
PERIMETER_MID_ZN_1_WALL_SOUTH NONRES_EXT_WALL_MID 0.30 0.811 0.924 2006.06 847.11 180.00 90.00 S
PERIMETER_MID_ZN_4_WALL_WEST NONRES_EXT_WALL_MID 0.30 0.811 0.924 1337.37 564.74 270.00 90.00 W
PERIMETER_TOP_ZN_3_WALL_NORTH NONRES_EXT_WALL_TOP 0.30 0.985 1.155 200.61 84.71 0.00 90.00 N
PERIMETER_TOP_ZN_2_WALL_EAST NONRES_EXT_WALL_TOP 0.30 0.985 1.155 133.74 56.47 90.00 90.00 E
PERIMETER_TOP_ZN_1_WALL_SOUTH NONRES_EXT_WALL_TOP 0.30 0.985 1.155 200.61 84.71 180.00 90.00 S
PERIMETER_TOP_ZN_4_WALL_WEST NONRES_EXT_WALL_TOP 0.30 0.985 1.155 133.74 56.47 270.00 90.00 W
GROUNDFLOOR_PLENUM_WALL_NORTH NONRES_EXT_WALL_GRD 0.30 0.846 0.969 89.13 89.13 0.00 90.00 N
GROUNDFLOOR_PLENUM_WEST NONRES_EXT_WALL_GRD 0.30 0.846 0.969 59.42 59.42 270.00 90.00 W
GROUNDFLOOR_PLENUM_WALL_SOUTH NONRES_EXT_WALL_GRD 0.30 0.846 0.969 89.13 89.13 180.00 90.00 S
GROUNDFLOOR_PLENUM_WALL_EAST NONRES_EXT_WALL_GRD 0.30 0.846 0.969 59.42 59.42 90.00 90.00 E
MIDFLOOR_PLENUM_WALL_NORTH NONRES_EXT_WALL_MID 0.30 0.811 0.924 891.32 891.32 0.00 90.00 N
MIDFLOOR_PLENUM_WALL_WEST NONRES_EXT_WALL_MID 0.30 0.811 0.924 594.21 594.21 270.00 90.00 W
MIDFLOOR_PLENUM_WALL_SOUTH NONRES_EXT_WALL_MID 0.30 0.811 0.924 891.32 891.32 180.00 90.00 S
MIDFLOOR_PLENUM_WALL_EAST NONRES_EXT_WALL_MID 0.30 0.811 0.924 594.21 594.21 90.00 90.00 E
TOPFLOOR_PLENUM_WALL_NORTH NONRES_EXT_WALL_TOP 0.30 0.985 1.155 89.13 89.13 180.00 90.00 S
TOPFLOOR_PLENUM_WALL_EAST NONRES_EXT_WALL_TOP 0.30 0.985 1.155 59.42 59.42 90.00 90.00 E
TOPFLOOR_PLENUM_WALL_WEST NONRES_EXT_WALL_TOP 0.30 0.985 1.155 59.42 59.42 270.00 90.00 W
TOPFLOOR_PLENUM_WALL_SOUTH NONRES_EXT_WALL_TOP 0.30 0.985 1.155 89.13 89.13 0.00 90.00 N
BUILDING_ROOF NONRES_ROOF 0.30 0.182 0.186 3563.11 3563.11 180.00 0.00  
DATACENTER_BASEMENT_ZN_6_WALL_NORTH DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR 1.00 0.399 0.419 39.22 39.22 0.00 90.00 N
DATACENTER_BASEMENT_ZN_6_WALL_SOUTH DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR 1.00 0.399 0.419 39.22 39.22 180.00 90.00 S
DATACENTER_BASEMENT_ZN_6_WALL_WEST DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR 1.00 0.399 0.419 118.87 118.87 270.00 90.00 W


Opaque Interior

Construction Reflectance U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Net Area [m2] Azimuth [deg] Tilt [deg] Cardinal Direction
BASEMENT_WALL_WEST INT_WALL 0.30 2.511 6.299 118.87 118.87 270.00 90.00 W
BASEMENT_FLOOR EXT_SLAB_8IN_WITH_CARPET 0.30 1.591 3.285 2779.43 2779.43 0.00 180.00  
PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER INT_SLAB_CEILING 0.30 1.887 3.839 201.98 201.98 225.00 0.00  
PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER INT_SLAB_CEILING 0.30 1.887 3.839 250.34 250.34 180.00 0.00  
CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER INT_SLAB_CEILING 0.30 1.887 3.839 2076.77 2076.77 180.00 0.00  
PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER INT_SLAB_CEILING 0.30 1.887 3.839 250.34 250.34 180.00 0.00  
CORE_BOT_ZN_5_WALL_SOUTH INT_WALL 0.30 2.511 6.299 173.00 173.00 180.00 90.00 S
CORE_BOT_ZN_5_WALL_WEST INT_WALL 0.30 2.511 6.299 108.64 108.64 270.00 90.00 W
CORE_BOT_ZN_5_WALL_NORTH INT_WALL 0.30 2.511 6.299 173.00 173.00 0.00 90.00 N
CORE_BOT_ZN_5_WALL_EAST INT_WALL 0.30 2.511 6.299 108.64 108.64 90.00 90.00 E
DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER INT_SLAB_FLOOR 0.30 1.887 3.839 419.30 419.30 0.00 180.00  
CORE_BOT_ZN_5_FLOOR INT_SLAB_FLOOR 0.30 1.887 3.839 2076.82 2076.82 0.00 180.00  
CORE_BOT_ZN_5_CEILING DROPCEILING 0.30 2.031 4.488 2496.12 2496.12 180.00 0.00  
CORE_MID_ZN_5_WALL_SOUTH INT_WALL 0.30 2.511 6.299 1729.99 1729.99 180.00 90.00 S
CORE_MID_ZN_5_WALL_WEST INT_WALL 0.30 2.511 6.299 1086.40 1086.40 270.00 90.00 W
CORE_MID_ZN_5_WALL_NORTH INT_WALL 0.30 2.511 6.299 1729.99 1729.99 0.00 90.00 N
CORE_MID_ZN_5_WALL_EAST INT_WALL 0.30 2.511 6.299 1086.40 1086.40 90.00 90.00 E
CORE_MID_ZN_5_FLOOR INT_SLAB_FLOOR 0.30 1.711 3.839 24961.20 24961.20 0.00 180.00  
CORE_MID_ZN_5_CEILING DROPCEILING 0.30 2.031 4.488 24961.20 24961.20 180.00 0.00  
CORE_TOP_ZN_5_WALL_SOUTH INT_WALL 0.30 2.511 6.299 173.00 173.00 180.00 90.00 S
CORE_TOP_ZN_5_WALL_WEST INT_WALL 0.30 2.511 6.299 108.64 108.64 270.00 90.00 W
CORE_TOP_ZN_5_WALL_NORTH INT_WALL 0.30 2.511 6.299 173.00 173.00 0.00 90.00 N
CORE_TOP_ZN_5_WALL_EAST INT_WALL 0.30 2.511 6.299 108.64 108.64 90.00 90.00 E
CORE_TOP_ZN_5_FLOOR INT_SLAB_FLOOR 0.30 1.711 3.839 2496.12 2496.12 0.00 180.00  
CORE_TOP_ZN_5_CEILING DROPCEILING 0.30 2.031 4.488 2496.12 2496.12 180.00 0.00  
PERIMETER_BOT_ZN_3_WALL_WEST INT_WALL 0.30 2.511 6.299 17.75 17.75 225.00 90.00 W
CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 173.00 173.00 180.00 90.00 S
PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 17.75 17.75 135.00 90.00 S
DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 2.51 2.51 180.00 90.00 S
PERIMETER_BOT_ZN_3_FLOOR INT_SLAB_FLOOR 0.30 1.887 3.839 250.34 250.34 0.00 180.00  
DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER INT_SLAB_FLOOR 0.30 1.887 3.839 63.07 63.07 0.00 180.00  
PERIMETER_BOT_ZN_3_CEILING DROPCEILING 0.30 2.031 4.488 313.41 313.41 180.00 0.00  
PERIMETER_BOT_ZN_2_WALL_NORTH INT_WALL 0.30 2.511 6.299 17.75 17.75 315.00 90.00 N
CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 108.64 108.64 270.00 90.00 W
PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 17.75 17.75 225.00 90.00 W
PERIMETER_BOT_ZN_2_FLOOR INT_SLAB_FLOOR 0.30 1.887 3.839 201.98 201.98 45.00 180.00  
PERIMETER_BOT_ZN_2_CEILING DROPCEILING 0.30 2.031 4.488 201.98 201.98 225.00 0.00  
PERIMETER_BOT_ZN_1_WALL_EAST INT_WALL 0.30 2.511 6.299 17.75 17.75 45.00 90.00 E
DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 2.51 2.51 0.00 90.00 N
PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 17.75 17.75 315.00 90.00 N
CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 173.00 173.00 0.00 90.00 N
DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER INT_SLAB_FLOOR 0.30 1.887 3.839 63.07 63.07 0.00 180.00  
PERIMETER_BOT_ZN_1_FLOOR INT_SLAB_FLOOR 0.30 1.887 3.839 250.35 250.35 0.00 180.00  
PERIMETER_BOT_ZN_1_CEILING DROPCEILING 0.30 2.031 4.488 313.42 313.42 180.00 0.00  
PERIMETER_BOT_ZN_4_WALL_SOUTH INT_WALL 0.30 2.511 6.299 17.75 17.75 135.00 90.00 S
DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 108.64 108.64 90.00 90.00 E
PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 17.75 17.75 45.00 90.00 E
PERIMETER_BOT_ZN_4_FLOOR INT_SLAB_FLOOR 0.30 1.887 3.839 201.98 201.98 315.00 180.00  
PERIMETER_BOT_ZN_4_CEILING DROPCEILING 0.30 2.031 4.488 201.98 201.98 135.00 0.00  
PERIMETER_MID_ZN_3_WALL_WEST INT_WALL 0.30 2.511 6.299 177.47 177.47 225.00 90.00 W
CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 1729.99 1729.99 180.00 90.00 S
PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 177.47 177.47 135.00 90.00 S
DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 25.09 25.09 180.00 90.00 S
PERIMETER_MID_ZN_3_FLOOR INT_SLAB_FLOOR 0.30 1.711 3.839 3134.13 3134.13 0.00 180.00  
PERIMETER_MID_ZN_3_CEILING DROPCEILING 0.30 2.031 4.488 3134.13 3134.13 180.00 0.00  
PERIMETER_MID_ZN_2_WALL_NORTH INT_WALL 0.30 2.511 6.299 177.47 177.47 315.00 90.00 N
CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 1086.40 1086.40 270.00 90.00 W
PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 177.47 177.47 225.00 90.00 W
PERIMETER_MID_ZN_2_FLOOR INT_SLAB_FLOOR 0.30 1.711 3.839 2019.75 2019.75 45.00 180.00  
PERIMETER_MID_ZN_2_CEILING DROPCEILING 0.30 2.031 4.488 2019.75 2019.75 225.00 0.00  
PERIMETER_MID_ZN_1_WALL_EAST INT_WALL 0.30 2.511 6.299 177.47 177.47 45.00 90.00 E
DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 25.09 25.09 0.00 90.00 N
PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 177.47 177.47 315.00 90.00 N
CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 1729.99 1729.99 0.00 90.00 N
PERIMETER_MID_ZN_1_FLOOR INT_SLAB_FLOOR 0.30 1.711 3.839 3134.20 3134.20 0.00 180.00  
PERIMETER_MID_ZN_1_CEILING DROPCEILING 0.30 2.031 4.488 3134.20 3134.20 180.00 0.00  
PERIMETER_MID_ZN_4_WALL_SOUTH INT_WALL 0.30 2.511 6.299 177.47 177.47 135.00 90.00 S
DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 1086.40 1086.40 90.00 90.00 E
PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 177.47 177.47 45.00 90.00 E
PERIMETER_MID_ZN_4_FLOOR INT_SLAB_FLOOR 0.30 1.711 3.839 2019.75 2019.75 315.00 180.00  
PERIMETER_MID_ZN_4_CEILING DROPCEILING 0.30 2.031 4.488 2019.75 2019.75 135.00 0.00  
PERIMETER_TOP_ZN_3_WALL_WEST INT_WALL 0.30 2.511 6.299 17.75 17.75 225.00 90.00 W
CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 173.00 173.00 180.00 90.00 S
PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 17.75 17.75 135.00 90.00 S
DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 2.51 2.51 180.00 90.00 S
PERIMETER_TOP_ZN_3_FLOOR INT_SLAB_FLOOR 0.30 1.711 3.839 313.41 313.41 0.00 180.00  
PERIMETER_TOP_ZN_3_CEILING DROPCEILING 0.30 2.031 4.488 313.41 313.41 180.00 0.00  
PERIMETER_TOP_ZN_2_WALL_NORTH INT_WALL 0.30 2.511 6.299 17.75 17.75 315.00 90.00 N
CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 108.64 108.64 270.00 90.00 W
INT-PER3S-NE-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 17.75 17.75 225.00 90.00 W
PERIMETER_TOP_ZN_2_FLOOR INT_SLAB_FLOOR 0.30 1.711 3.839 201.98 201.98 45.00 180.00  
PERIMETER_TOP_ZN_2_CEILING DROPCEILING 0.30 2.031 4.488 201.98 201.98 225.00 0.00  
INT-PER3S-NE INT_WALL 0.30 2.511 6.299 17.75 17.75 45.00 90.00 E
DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 2.51 2.51 0.00 90.00 N
PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 17.75 17.75 315.00 90.00 N
CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 173.00 173.00 0.00 90.00 N
PERIMETER_TOP_ZN_1_FLOOR INT_SLAB_FLOOR 0.30 1.711 3.839 313.42 313.42 0.00 180.00  
PERIMETER_TOP_ZN_1_CEILING DROPCEILING 0.30 2.031 4.488 313.42 313.42 180.00 0.00  
PERIMETER_TOP_ZN_4_WALL_SOUTH INT_WALL 0.30 2.511 6.299 17.75 17.75 135.00 90.00 S
DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 108.64 108.64 90.00 90.00 E
PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 17.75 17.75 45.00 90.00 E
PERIMETER_TOP_ZN_4_FLOOR INT_SLAB_FLOOR 0.30 1.711 3.839 201.98 201.98 315.00 180.00  
PERIMETER_TOP_ZN_4_CEILING DROPCEILING 0.30 2.031 4.488 201.98 201.98 135.00 0.00  
iz-CORE_BOT_ZN_5_CEILING DROPCEILING 0.30 2.031 4.488 2496.12 2496.12 0.00 180.00  
iz-PERIMETER_BOT_ZN_3_CEILING DROPCEILING 0.30 2.031 4.488 313.41 313.41 0.00 180.00  
iz-PERIMETER_BOT_ZN_2_CEILING DROPCEILING 0.30 2.031 4.488 201.98 201.98 45.00 180.00  
iz-PERIMETER_BOT_ZN_1_CEILING DROPCEILING 0.30 2.031 4.488 313.42 313.42 0.00 180.00  
iz-PERIMETER_BOT_ZN_4_CEILING DROPCEILING 0.30 2.031 4.488 201.98 201.98 315.00 180.00  
iz-DATACENTER_BOT_ZN_6_CEILING DROPCEILING 0.30 2.031 4.488 36.20 36.20 0.00 180.00  
GROUNDFLOOR_PLENUM_CEILING INT_SLAB_CEILING 0.30 2.104 3.839 3563.11 3563.11 180.00 0.00  
iz-CORE_MID_ZN_5_CEILING DROPCEILING 0.30 2.031 4.488 24961.20 24961.20 0.00 180.00  
iz-PERIMETER_MID_ZN_3_CEILING DROPCEILING 0.30 2.031 4.488 3134.13 3134.13 0.00 180.00  
iz-PERIMETER_MID_ZN_2_CEILING DROPCEILING 0.30 2.031 4.488 2019.75 2019.75 45.00 180.00  
iz-PERIMETER_MID_ZN_1_CEILING DROPCEILING 0.30 2.031 4.488 3134.20 3134.20 0.00 180.00  
iz-PERIMETER_MID_ZN_4_CEILING DROPCEILING 0.30 2.031 4.488 2019.75 2019.75 315.00 180.00  
iz-DATACENTER_MID_ZN_6_CEILING DROPCEILING 0.30 2.031 4.488 362.03 362.03 0.00 180.00  
MIDFLOOR_PLENUM_CEILING INT_SLAB_CEILING 0.30 2.104 3.839 35631.06 35631.06 180.00 0.00  
iz-CORE_TOP_ZN_5_CEILING DROPCEILING 0.30 2.031 4.488 2496.12 2496.12 0.00 180.00  
iz-PERIMETER_TOP_ZN_3_CEILING DROPCEILING 0.30 2.031 4.488 313.41 313.41 0.00 180.00  
iz-PERIMETER_TOP_ZN_2_CEILING DROPCEILING 0.30 2.031 4.488 201.98 201.98 45.00 180.00  
iz-PERIMETER_TOP_ZN_1_CEILING DROPCEILING 0.30 2.031 4.488 313.42 313.42 0.00 180.00  
iz-PERIMETER_TOP_ZN_4_CEILING DROPCEILING 0.30 2.031 4.488 201.98 201.98 315.00 180.00  
iz-DATACENTER_TOP_ZN_6_CEILING DROPCEILING 0.30 2.031 4.488 36.20 36.20 0.00 180.00  
DATACENTER_BOT_ZN_6_WALL_NORTH INT_WALL 0.30 2.511 6.299 2.51 2.51 0.00 90.00 N
DATACENTER_BOT_ZN_6_WALL_SOUTH INT_WALL 0.30 2.511 6.299 2.51 2.51 180.00 90.00 S
DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 108.64 108.64 90.00 90.00 E
DATACENTER_BOT_ZN_6_WALL_WEST INT_WALL 0.30 2.511 6.299 108.64 108.64 270.00 90.00 W
DATACENTER_BOT_ZN_6_FLOOR INT_SLAB_FLOOR 0.30 1.887 3.839 36.20 36.20 0.00 180.00  
DATACENTER_BOT_ZN_6_CEILING DROPCEILING 0.30 2.031 4.488 36.20 36.20 180.00 0.00  
DATACENTER_MID_ZN_6_WALL_WEST INT_WALL 0.30 2.511 6.299 1086.40 1086.40 270.00 90.00 W
DATACENTER_MID_ZN_6_WALL_SOUTH INT_WALL 0.30 2.511 6.299 25.09 25.09 180.00 90.00 S
DATACENTER_MID_ZN_6_WALL_EAST INT_WALL 0.30 2.511 6.299 1086.40 1086.40 90.00 90.00 E
DATACENTER_MID_ZN_6_WALL_NORTH INT_WALL 0.30 2.511 6.299 25.09 25.09 0.00 90.00 N
DATACENTER_MID_ZN_6_FLOOR INT_SLAB_FLOOR 0.30 1.711 3.839 362.03 362.03 0.00 180.00  
DATACENTER_MID_ZN_6_CEILING DROPCEILING 0.30 2.031 4.488 362.03 362.03 180.00 0.00  
DATACENTER_TOP_ZN_6_WALL_EAST INT_WALL 0.30 2.511 6.299 108.64 108.64 90.00 90.00 E
DATACENTER_TOP_ZN_6_WALL_WEST INT_WALL 0.30 2.511 6.299 108.64 108.64 270.00 90.00 W
DATACENTER_TOP_ZN_6_WALL_SOUTH INT_WALL 0.30 2.511 6.299 2.51 2.51 180.00 90.00 S
DATACENTER_TOP_ZN_6_WALL_NORTH INT_WALL 0.30 2.511 6.299 2.51 2.51 0.00 90.00 N
DATACENTER_TOP_ZN_6_FLOOR INT_SLAB_FLOOR 0.30 1.711 3.839 36.20 36.20 0.00 180.00  
DATACENTER_TOP_ZN_6_CEILING DROPCEILING 0.30 2.031 4.488 36.20 36.20 180.00 0.00  
DATACENTER_BASEMENT_ZN_6_WALL_EAST INT_WALL 0.30 2.511 6.299 118.87 118.87 90.00 90.00 E
DATACENTER_BASEMENT_ZN_6_FLOOR EXT_SLAB_8IN_WITH_CARPET 0.30 1.591 3.285 783.68 783.68 0.00 180.00  
DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER INT_SLAB_CEILING 0.30 1.887 3.839 36.20 36.20 180.00 0.00  
DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 INT_SLAB_CEILING 0.30 1.887 3.839 419.35 419.35 180.00 0.00  
PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER INT_SLAB_CEILING 0.30 1.887 3.839 201.98 201.98 135.00 0.00  
DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 INT_SLAB_CEILING 0.30 1.887 3.839 63.08 63.08 180.00 0.00  
DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 INT_SLAB_CEILING 0.30 1.887 3.839 63.07 63.07 180.00 0.00  
BASEMENT_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 7126.21   0.00 90.00 N
CORE_BOTTOM_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 5064.65   0.00 90.00 N
CORE_MID_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 50646.53   0.00 90.00 N
CORE_TOP_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 5064.65   0.00 90.00 N
PERIMETER_BOT_ZN_3_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 626.83   0.00 90.00 N
PERIMETER_BOT_ZN_2_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 403.95   0.00 90.00 N
PERIMETER_BOT_ZN_1_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 626.84   0.00 90.00 N
PERIMETER_BOT_ZN_4_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 403.95   0.00 90.00 N
PERIMETER_MID_ZN_3_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 6268.26   0.00 90.00 N
PERIMETER_MID_ZN_2_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 4039.50   0.00 90.00 N
PERIMETER_MID_ZN_1_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 6268.35   0.00 90.00 N
PERIMETER_MID_ZN_4_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 4039.48   0.00 90.00 N
PERIMETER_TOP_ZN_3_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 626.83   0.00 90.00 N
PERIMETER_TOP_ZN_2_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 403.95   0.00 90.00 N
PERIMETER_TOP_ZN_1_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 626.84   0.00 90.00 N
PERIMETER_TOP_ZN_4_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 403.95   0.00 90.00 N


Exterior Fenestration

Construction Frame and Divider Glass Area [m2] Frame Area [m2] Divider Area [m2] Area of One Opening [m2] Area of Multiplied Openings [m2] Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance Frame Conductance [W/m2-K] Divider Conductance [W/m2-K] NFRC Product Type Assembly U-Factor [W/m2-K] Assembly SHGC Assembly Visible Transmittance Shade Control Parent Surface Azimuth [deg] Tilt [deg] Cardinal Direction
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 WINDOW_U_0.419_SHGC_NORTH_0.4   23.18 0.00 0.00 23.18 23.18 2.381 0.401 0.442             No PERIMETER_BOT_ZN_3_WALL_NORTH 0.00 90.00 N
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 WINDOW_U_0.419_SHGC_NORTH_0.4   23.18 0.00 0.00 23.18 23.18 2.381 0.401 0.442             No PERIMETER_BOT_ZN_3_WALL_NORTH 0.00 90.00 N
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 WINDOW_U_0.419_SHGC_NORTH_0.4   23.18 0.00 0.00 23.18 23.18 2.381 0.401 0.442             No PERIMETER_BOT_ZN_3_WALL_NORTH 0.00 90.00 N
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 WINDOW_U_0.419_SHGC_NORTH_0.4   23.18 0.00 0.00 23.18 23.18 2.381 0.401 0.442             No PERIMETER_BOT_ZN_3_WALL_NORTH 0.00 90.00 N
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 WINDOW_U_0.419_SHGC_NORTH_0.4   23.18 0.00 0.00 23.18 23.18 2.381 0.401 0.442             No PERIMETER_BOT_ZN_3_WALL_NORTH 0.00 90.00 N
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 WINDOW_U_0.419_SHGC_EAST_0.4   25.75 0.00 0.00 25.75 25.75 2.381 0.401 0.442             No PERIMETER_BOT_ZN_2_WALL_EAST 90.00 90.00 E
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 WINDOW_U_0.419_SHGC_EAST_0.4   25.75 0.00 0.00 25.75 25.75 2.381 0.401 0.442             No PERIMETER_BOT_ZN_2_WALL_EAST 90.00 90.00 E
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 WINDOW_U_0.419_SHGC_EAST_0.4   25.75 0.00 0.00 25.75 25.75 2.381 0.401 0.442             No PERIMETER_BOT_ZN_2_WALL_EAST 90.00 90.00 E
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 WINDOW_U_0.419_SHGC_SOUTH_0.4   23.18 0.00 0.00 23.18 23.18 2.381 0.401 0.442             No PERIMETER_BOT_ZN_1_WALL_SOUTH 180.00 90.00 S
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 WINDOW_U_0.419_SHGC_SOUTH_0.4   23.18 0.00 0.00 23.18 23.18 2.381 0.401 0.442             No PERIMETER_BOT_ZN_1_WALL_SOUTH 180.00 90.00 S
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 WINDOW_U_0.419_SHGC_SOUTH_0.4   23.18 0.00 0.00 23.18 23.18 2.381 0.401 0.442             No PERIMETER_BOT_ZN_1_WALL_SOUTH 180.00 90.00 S
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 WINDOW_U_0.419_SHGC_SOUTH_0.4   23.18 0.00 0.00 23.18 23.18 2.381 0.401 0.442             No PERIMETER_BOT_ZN_1_WALL_SOUTH 180.00 90.00 S
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 WINDOW_U_0.419_SHGC_SOUTH_0.4   23.18 0.00 0.00 23.18 23.18 2.381 0.401 0.442             No PERIMETER_BOT_ZN_1_WALL_SOUTH 180.00 90.00 S
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 WINDOW_U_0.419_SHGC_WEST_0.4   25.75 0.00 0.00 25.75 25.75 2.381 0.401 0.442             No PERIMETER_BOT_ZN_4_WALL_WEST 270.00 90.00 W
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 WINDOW_U_0.419_SHGC_WEST_0.4   25.75 0.00 0.00 25.75 25.75 2.381 0.401 0.442             No PERIMETER_BOT_ZN_4_WALL_WEST 270.00 90.00 W
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 WINDOW_U_0.419_SHGC_WEST_0.4   25.75 0.00 0.00 25.75 25.75 2.381 0.401 0.442             No PERIMETER_BOT_ZN_4_WALL_WEST 270.00 90.00 W
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW WINDOW_U_0.419_SHGC_NORTH_0.4   115.90 0.00 0.00 115.90 1158.95 2.381 0.401 0.442             No PERIMETER_MID_ZN_3_WALL_NORTH 0.00 90.00 N
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW WINDOW_U_0.419_SHGC_EAST_0.4   77.26 0.00 0.00 77.26 772.63 2.381 0.401 0.442             No PERIMETER_MID_ZN_2_WALL_EAST 90.00 90.00 E
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW WINDOW_U_0.419_SHGC_SOUTH_0.4   115.90 0.00 0.00 115.90 1158.95 2.381 0.401 0.442             No PERIMETER_MID_ZN_1_WALL_SOUTH 180.00 90.00 S
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW WINDOW_U_0.419_SHGC_WEST_0.4   77.26 0.00 0.00 77.26 772.63 2.381 0.401 0.442             No PERIMETER_MID_ZN_4_WALL_WEST 270.00 90.00 W
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW WINDOW_U_0.419_SHGC_NORTH_0.4   115.90 0.00 0.00 115.90 115.90 2.381 0.401 0.442             No PERIMETER_TOP_ZN_3_WALL_NORTH 0.00 90.00 N
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW WINDOW_U_0.419_SHGC_EAST_0.4   77.26 0.00 0.00 77.26 77.26 2.381 0.401 0.442             No PERIMETER_TOP_ZN_2_WALL_EAST 90.00 90.00 E
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW WINDOW_U_0.419_SHGC_SOUTH_0.4   115.90 0.00 0.00 115.90 115.90 2.381 0.401 0.442             No PERIMETER_TOP_ZN_1_WALL_SOUTH 180.00 90.00 S
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW WINDOW_U_0.419_SHGC_WEST_0.4   77.26 0.00 0.00 77.26 77.26 2.381 0.401 0.442             No PERIMETER_TOP_ZN_4_WALL_WEST 270.00 90.00 W
Total or Average             4635.80 2.381 0.401 0.442                      
North Total or Average             1390.74 2.381 0.401 0.442                      
Non-North Total or Average             3245.06 2.381 0.401 0.442                      


Exterior Fenestration Shaded State

Frame and Divider Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance NFRC Product Type Assembly U-Factor [W/m2-K] Assembly SHGC Assembly Visible Transmittance
None                


Interior Fenestration

Construction Area of One Opening [m2] Area of Openings [m2] Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance
Total or Average     0.00 - - -


Exterior Door

Construction U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Parent Surface
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 SWINGING DOOR_CON 1.992 2.839 1.95 PERIMETER_BOT_ZN_3_WALL_NORTH
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 SWINGING DOOR_CON 1.992 2.839 1.95 PERIMETER_BOT_ZN_3_WALL_NORTH
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 SWINGING DOOR_CON 1.992 2.839 1.95 PERIMETER_BOT_ZN_3_WALL_NORTH
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 SWINGING DOOR_CON 1.992 2.839 1.95 PERIMETER_BOT_ZN_3_WALL_NORTH
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 SWINGING DOOR_CON 1.992 2.839 1.95 PERIMETER_BOT_ZN_2_WALL_EAST
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 SWINGING DOOR_CON 1.992 2.839 1.95 PERIMETER_BOT_ZN_2_WALL_EAST
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 SWINGING DOOR_CON 1.992 2.839 1.95 PERIMETER_BOT_ZN_1_WALL_SOUTH
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 SWINGING DOOR_CON 1.992 2.839 1.95 PERIMETER_BOT_ZN_1_WALL_SOUTH
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 SWINGING DOOR_CON 1.992 2.839 1.95 PERIMETER_BOT_ZN_1_WALL_SOUTH
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 SWINGING DOOR_CON 1.992 2.839 1.95 PERIMETER_BOT_ZN_1_WALL_SOUTH
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 SWINGING DOOR_CON 1.992 2.839 1.95 PERIMETER_BOT_ZN_4_WALL_WEST
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 SWINGING DOOR_CON 1.992 2.839 1.95 PERIMETER_BOT_ZN_4_WALL_WEST


Interior Door

Construction U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Parent Surface
None          



Table of Contents

Report: Shading Summary

For: Entire Facility

Timestamp: 2023-10-16 08:43:24

Sunlit Fraction

March 21 9am March 21 noon March 21 3pm June 21 9am June 21 noon June 21 3pm December 21 9am December 21 noon December 21 3pm
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00


Window Control

Name Type Shaded Construction Control Glare Control
None          



Table of Contents

Report: Lighting Summary

For: Entire Facility

Timestamp: 2023-10-16 08:43:24

Interior Lighting

Zone Name Space Name Space Type Lighting Power Density [W/m2] Space Area [m2] Total Power [W] End Use Subcategory Schedule Name Scheduled Hours/Week [hr] Hours/Week > 1% [hr] Full Load Hours/Week [hr] Return Air Fraction Conditioned (Y/N) Consumption [GJ]
BASEMENT_LIGHTS BASEMENT BASEMENT GENERAL 10.2732 2779.43 28553.72 LightsWired LTG_SCH_OFFICE 50.34 168.00 49.04 0.0000 Y 262.84
CORE_BOTTOM_LIGHTS CORE_BOTTOM CORE_BOTTOM GENERAL 10.2732 2496.12 25643.24 LightsWired LTG_SCH_OFFICE 50.34 168.00 49.04 0.0000 Y 236.05
CORE_MID_LIGHTS CORE_MID CORE_MID GENERAL 10.2732 24961.20 256432.45 LightsWired LTG_SCH_OFFICE 50.34 168.00 49.04 0.0000 Y 2360.52
CORE_TOP_LIGHTS CORE_TOP CORE_TOP GENERAL 10.2732 2496.12 25643.24 LightsWired LTG_SCH_OFFICE 50.34 168.00 49.04 0.0000 Y 236.05
PERIMETER_BOT_ZN_3_LIGHTS PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3 GENERAL 10.2732 313.41 3219.77 LightsWired LTG_SCH_OFFICE 50.34 168.00 28.77 0.0000 Y 17.39
PERIMETER_BOT_ZN_2_LIGHTS PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2 GENERAL 10.2732 201.98 2074.94 LightsWired LTG_SCH_OFFICE 50.34 168.00 28.54 0.0000 Y 11.12
PERIMETER_BOT_ZN_1_LIGHTS PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1 GENERAL 10.2732 313.42 3219.84 LightsWired LTG_SCH_OFFICE 50.34 168.00 28.33 0.0000 Y 17.12
PERIMETER_BOT_ZN_4_LIGHTS PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4 GENERAL 10.2732 201.98 2074.94 LightsWired LTG_SCH_OFFICE 50.34 168.00 28.52 0.0000 Y 11.11
PERIMETER_MID_ZN_3_LIGHTS PERIMETER_MID_ZN_3 PERIMETER_MID_ZN_3 GENERAL 10.2732 3134.13 32197.65 LightsWired LTG_SCH_OFFICE 50.34 168.00 28.71 0.0000 Y 173.52
PERIMETER_MID_ZN_2_LIGHTS PERIMETER_MID_ZN_2 PERIMETER_MID_ZN_2 GENERAL 10.2732 2019.75 20749.39 LightsWired LTG_SCH_OFFICE 50.34 168.00 28.50 0.0000 Y 110.99
PERIMETER_MID_ZN_1_LIGHTS PERIMETER_MID_ZN_1 PERIMETER_MID_ZN_1 GENERAL 10.2732 3134.20 32198.36 LightsWired LTG_SCH_OFFICE 50.34 168.00 28.30 0.0000 Y 171.06
PERIMETER_MID_ZN_4_LIGHTS PERIMETER_MID_ZN_4 PERIMETER_MID_ZN_4 GENERAL 10.2732 2019.75 20749.39 LightsWired LTG_SCH_OFFICE 50.34 168.00 28.47 0.0000 Y 110.88
PERIMETER_TOP_ZN_3_LIGHTS PERIMETER_TOP_ZN_3 PERIMETER_TOP_ZN_3 GENERAL 10.2732 313.41 3219.77 LightsWired LTG_SCH_OFFICE 50.34 168.00 28.70 0.0000 Y 17.35
PERIMETER_TOP_ZN_2_LIGHTS PERIMETER_TOP_ZN_2 PERIMETER_TOP_ZN_2 GENERAL 10.2732 201.98 2074.94 LightsWired LTG_SCH_OFFICE 50.34 168.00 28.49 0.0000 Y 11.10
PERIMETER_TOP_ZN_1_LIGHTS PERIMETER_TOP_ZN_1 PERIMETER_TOP_ZN_1 GENERAL 10.2732 313.42 3219.84 LightsWired LTG_SCH_OFFICE 50.34 168.00 28.30 0.0000 Y 17.10
PERIMETER_TOP_ZN_4_LIGHTS PERIMETER_TOP_ZN_4 PERIMETER_TOP_ZN_4 GENERAL 10.2732 201.98 2074.94 LightsWired LTG_SCH_OFFICE 50.34 168.00 28.47 0.0000 Y 11.09
DATACENTER_BASEMENT_LIGHTS DATACENTER_BASEMENT_ZN_6 DATACENTER_BASEMENT_ZN_6 GENERAL 10.2732 783.68 8050.93 LightsWired LTG_SCH_OFFICE 50.34 168.00 49.04 0.0000 Y 74.11
DATACENTER_BOT_LIGHTS DATACENTER_BOT_ZN_6 DATACENTER_BOT_ZN_6 GENERAL 17.8735 36.20 647.07 LightsWired LTG_SCH_DATACENTER 56.02 168.00 54.57 0.0000 Y 6.63
DATACENTER_MID_LIGHTS DATACENTER_MID_ZN_6 DATACENTER_MID_ZN_6 GENERAL 17.8735 362.03 6470.68 LightsWired LTG_SCH_DATACENTER 56.02 168.00 54.57 0.0000 Y 66.28
DATACENTER_TOP_LIGHTS DATACENTER_TOP_ZN_6 DATACENTER_TOP_ZN_6 GENERAL 17.8735 36.20 647.07 LightsWired LTG_SCH_DATACENTER 56.02 168.00 54.57 0.0000 Y 6.63
Interior Lighting Total       10.3445 46320.38 479162.15               1235.01


Daylighting

Zone Control Name Daylighting Method Control Type Fraction Controlled Lighting Installed in Zone [W] Lighting Controlled [W]
PERIMETER_BOT_ZN_1_DAYLREFPT1 PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_DAYLCTRL SplitFlux Stepped 0.39 3219.84 1241.89
PERIMETER_BOT_ZN_1_DAYLREFPT2 PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_DAYLCTRL SplitFlux Stepped 0.14 3219.84 445.95
PERIMETER_BOT_ZN_2_DAYLREFPT1 PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_DAYLCTRL SplitFlux Stepped 0.39 2074.94 800.30
PERIMETER_BOT_ZN_2_DAYLREFPT2 PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_DAYLCTRL SplitFlux Stepped 0.14 2074.94 287.38
PERIMETER_BOT_ZN_3_DAYLREFPT1 PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_DAYLCTRL SplitFlux Stepped 0.39 3219.77 1241.86
PERIMETER_BOT_ZN_3_DAYLREFPT2 PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_DAYLCTRL SplitFlux Stepped 0.14 3219.77 445.94
PERIMETER_BOT_ZN_4_DAYLREFPT1 PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_DAYLCTRL SplitFlux Stepped 0.39 2074.94 800.30
PERIMETER_BOT_ZN_4_DAYLREFPT2 PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_DAYLCTRL SplitFlux Stepped 0.14 2074.94 287.38
PERIMETER_MID_ZN_1_DAYLREFPT1 PERIMETER_MID_ZN_1 PERIMETER_MID_ZN_1_DAYLCTRL SplitFlux Stepped 0.39 3219.84 1241.89
PERIMETER_MID_ZN_1_DAYLREFPT2 PERIMETER_MID_ZN_1 PERIMETER_MID_ZN_1_DAYLCTRL SplitFlux Stepped 0.14 3219.84 445.95
PERIMETER_MID_ZN_2_DAYLREFPT1 PERIMETER_MID_ZN_2 PERIMETER_MID_ZN_2_DAYLCTRL SplitFlux Stepped 0.39 2074.94 800.30
PERIMETER_MID_ZN_2_DAYLREFPT2 PERIMETER_MID_ZN_2 PERIMETER_MID_ZN_2_DAYLCTRL SplitFlux Stepped 0.14 2074.94 287.38
PERIMETER_MID_ZN_3_DAYLREFPT1 PERIMETER_MID_ZN_3 PERIMETER_MID_ZN_3_DAYLCTRL SplitFlux Stepped 0.39 3219.77 1241.86
PERIMETER_MID_ZN_3_DAYLREFPT2 PERIMETER_MID_ZN_3 PERIMETER_MID_ZN_3_DAYLCTRL SplitFlux Stepped 0.14 3219.77 445.94
PERIMETER_MID_ZN_4_DAYLREFPT1 PERIMETER_MID_ZN_4 PERIMETER_MID_ZN_4_DAYLCTRL SplitFlux Stepped 0.39 2074.94 800.30
PERIMETER_MID_ZN_4_DAYLREFPT2 PERIMETER_MID_ZN_4 PERIMETER_MID_ZN_4_DAYLCTRL SplitFlux Stepped 0.14 2074.94 287.38
PERIMETER_TOP_ZN_1_DAYLREFPT1 PERIMETER_TOP_ZN_1 PERIMETER_TOP_ZN_1_DAYLCTRL SplitFlux Stepped 0.39 3219.84 1241.89
PERIMETER_TOP_ZN_1_DAYLREFPT2 PERIMETER_TOP_ZN_1 PERIMETER_TOP_ZN_1_DAYLCTRL SplitFlux Stepped 0.14 3219.84 445.95
PERIMETER_TOP_ZN_2_DAYLREFPT1 PERIMETER_TOP_ZN_2 PERIMETER_TOP_ZN_2_DAYLCTRL SplitFlux Stepped 0.39 2074.94 800.30
PERIMETER_TOP_ZN_2_DAYLREFPT2 PERIMETER_TOP_ZN_2 PERIMETER_TOP_ZN_2_DAYLCTRL SplitFlux Stepped 0.14 2074.94 287.38
PERIMETER_TOP_ZN_3_DAYLREFPT1 PERIMETER_TOP_ZN_3 PERIMETER_TOP_ZN_3_DAYLCTRL SplitFlux Stepped 0.39 3219.77 1241.86
PERIMETER_TOP_ZN_3_DAYLREFPT2 PERIMETER_TOP_ZN_3 PERIMETER_TOP_ZN_3_DAYLCTRL SplitFlux Stepped 0.14 3219.77 445.94
PERIMETER_TOP_ZN_4_DAYLREFPT1 PERIMETER_TOP_ZN_4 PERIMETER_TOP_ZN_4_DAYLCTRL SplitFlux Stepped 0.39 2074.94 800.30
PERIMETER_TOP_ZN_4_DAYLREFPT2 PERIMETER_TOP_ZN_4 PERIMETER_TOP_ZN_4_DAYLCTRL SplitFlux Stepped 0.14 2074.94 287.38


Exterior Lighting

Total Watts Astronomical Clock/Schedule Schedule Name Scheduled Hours/Week [hr] Hours/Week > 1% [hr] Full Load Hours/Week [hr] Consumption [GJ]
EXTERIOR_LIGHTS_A 13279.00 AstronomicalClock -   42.04 42.04 104.80
EXTERIOR_LIGHTS_B 44301.60 AstronomicalClock -   83.67 71.18 591.93
Exterior Lighting Total 57580.60           696.73



Table of Contents

Report: Equipment Summary

For: Entire Facility

Timestamp: 2023-10-16 08:43:24

Central Plant

Type Reference Capacity [W] Reference Efficiency [W/W] Rated Capacity [W] Rated Efficiency [W/W] IPLV in SI Units [W/W] IPLV in IP Units [Btu/W-h]
BYPASS HEAT EXCHANGER HeatExchanger:FluidToFluid 2779493.28          
HEATSYS1 BOILER Boiler:HotWater 3070468.04 0.81        
COOLSYS1 CHILLER1 Chiller:Electric:ReformulatedEIR 1410897.12 6.28 1350421.09 5.98 6.84 23.33
COOLSYS1 CHILLER2 Chiller:Electric:ReformulatedEIR 1410897.12 6.28 1350421.09 5.98 6.84 23.33
CENTRAL TOWER FluidCooler:TwoSpeed 582060.00          
CENTRAL BOILER Boiler:HotWater 545478.78 0.80        
TOWERWATERSYS COOLTOWER 1 CoolingTower:VariableSpeed 1674019.00          
TOWERWATERSYS COOLTOWER 2 CoolingTower:VariableSpeed 1674019.00          


Cooling Coils

Type Design Coil Load [W] Nominal Total Capacity [W] Nominal Sensible Capacity [W] Nominal Latent Capacity [W] Nominal Sensible Heat Ratio Nominal Efficiency [W/W] Nominal Coil UA Value [W/C] Nominal Coil Surface Area [m2]
VAV_BOT WITH REHEAT COOLING COIL Coil:Cooling:Water 228603.16 264703.75 180014.68 84689.07 0.68 - 28027.06 284.27
VAV_MID WITH REHEAT COOLING COIL Coil:Cooling:Water 2200563.12 2503609.88 1695570.92 808038.96 0.68 - 265231.62 2690.13
VAV_TOP WITH REHEAT COOLING COIL Coil:Cooling:Water 233234.66 270649.96 184133.39 86516.57 0.68 - 28667.56 290.76
CAV_BAS COOLING COIL Coil:Cooling:Water 123499.09 147434.44 101698.31 45736.12 0.69 - 15253.25 154.71
AIRLOOP DATACENTER BASEMENT COOLING COIL Coil:Cooling:WaterToAirHeatPump:EquationFit   435227.10 306220.41 129006.70 0.70 0.00    
AIRLOOP DATACENTER BOT COOLING COIL Coil:Cooling:WaterToAirHeatPump:EquationFit   10034.39 7101.30 2933.09 0.71 0.00    
AIRLOOP DATACENTER MID COOLING COIL Coil:Cooling:WaterToAirHeatPump:EquationFit   96406.42 68179.43 28226.99 0.71 0.00    
AIRLOOP DATACENTER TOP COOLING COIL Coil:Cooling:WaterToAirHeatPump:EquationFit   9793.48 6926.95 2866.53 0.71 0.00    
Nominal values are gross at rated conditions, i.e., the supply air fan heat and electric power NOT accounted for.

DX Cooling Coils

DX Cooling Coil Type Standard Rated Net Cooling Capacity [W] Standard Rated Net COP [W/W] EER [Btu/W-h] SEER User [Btu/W-h] SEER Standard [Btu/W-h] IEER [Btu/W-h]
None              


DX Cooling Coil ASHRAE 127 Standard Ratings Report

DX Cooling Coil Type Rated Net Cooling Capacity Test A [W] Rated Electric Power Test A [W] Rated Net Cooling Capacity Test B [W] Rated Electric Power Test B [W] Rated Net Cooling Capacity Test C [W] Rated Electric Power Test C [W] Rated Net Cooling Capacity Test D [W] Rated Electric Power Test D [W]
None                  


DX Heating Coils

DX Heating Coil Type High Temperature Heating (net) Rating Capacity [W] Low Temperature Heating (net) Rating Capacity [W] HSPF [Btu/W-h] Region Number
None          


Heating Coils

Type Design Coil Load [W] Nominal Total Capacity [W] Nominal Efficiency [W/W]
CORE_BOTTOM VAV BOX REHEAT COIL Coil:Heating:Water 24384.09 23118.58 -
CORE_MID VAV BOX REHEAT COIL Coil:Heating:Water 509693.53 482843.24 -
CORE_TOP VAV BOX REHEAT COIL Coil:Heating:Water 97540.46 92431.34 -
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL Coil:Heating:Water 18821.10 17832.90 -
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL Coil:Heating:Water 12719.09 12051.16 -
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL Coil:Heating:Water 20449.32 19375.38 -
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL Coil:Heating:Water 10619.50 10056.74 -
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL Coil:Heating:Water 287968.01 272826.65 -
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL Coil:Heating:Water 188490.16 178578.90 -
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL Coil:Heating:Water 287969.55 272828.11 -
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL Coil:Heating:Water 184787.33 175071.06 -
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL Coil:Heating:Water 36035.65 34140.01 -
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL Coil:Heating:Water 23518.56 22281.34 -
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL Coil:Heating:Water 36035.92 34140.26 -
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL Coil:Heating:Water 23356.95 22128.23 -
VAV_BOT WITH REHEAT HEATING COIL Coil:Heating:Water 81559.25 58594.07 -
VAV_MID WITH REHEAT HEATING COIL Coil:Heating:Water 835544.76 586545.04 -
VAV_TOP WITH REHEAT HEATING COIL Coil:Heating:Water 81603.30 58947.92 -
CAV_BAS HEATING COIL Coil:Heating:Water 309371.51 238890.49 -
AIRLOOP DATACENTER BASEMENT HEATING COIL Coil:Heating:WaterToAirHeatPump:EquationFit   435227.10 0.00
AIRLOOP DATACENTER BOT HEATING COIL Coil:Heating:WaterToAirHeatPump:EquationFit   10034.39 0.00
AIRLOOP DATACENTER MID HEATING COIL Coil:Heating:WaterToAirHeatPump:EquationFit   96406.42 0.00
AIRLOOP DATACENTER TOP HEATING COIL Coil:Heating:WaterToAirHeatPump:EquationFit   9793.48 0.00
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL Coil:Heating:Electric   22473.72 1.00
AIRLOOP DATACENTER BOT_SUPPHEATCOIL Coil:Heating:Electric   1038.19 1.00
AIRLOOP DATACENTER MID_SUPPHEATCOIL Coil:Heating:Electric   10381.93 1.00
AIRLOOP DATACENTER TOP_SUPPHEATCOIL Coil:Heating:Electric   1038.19 1.00
Nominal values are gross at rated conditions, i.e., the supply air fan heat and electric power NOT accounted for.

Fans

Type Total Efficiency [W/W] Delta Pressure [pa] Max Air Flow Rate [m3/s] Rated Electricity Rate [W] Rated Power Per Max Air Flow Rate [W-s/m3] Motor Heat In Air Fraction Fan Energy Index End Use Subcategory Design Day Name for Fan Sizing Peak Date/Time for Fan Sizing Peak
VAV_BOT WITH REHEAT FAN Fan:VariableVolume 0.61 1389.42 10.38 23579.58 2271.59 1.00 1.12 General BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00
VAV_MID WITH REHEAT FAN Fan:VariableVolume 0.61 1389.42 96.93 220180.73 2271.59 1.00 1.08 General BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00
VAV_TOP WITH REHEAT FAN Fan:VariableVolume 0.61 1389.42 10.63 24137.43 2271.59 1.00 1.12 General BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:20:00
CAV_BAS FAN Fan:ConstantVolume 0.60 1018.41 6.07 10288.35 1695.65 1.00 1.15 General BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00
AIRLOOP DATACENTER BASEMENT SUPPLY FAN Fan:OnOff 0.62 1018.41 21.94 36181.53 1649.25 1.00 1.14 General BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 07:10:00
AIRLOOP DATACENTER BOT SUPPLY FAN Fan:OnOff 0.56 622.50 0.51 573.97 1120.11 1.00 1.59 General BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00
AIRLOOP DATACENTER MID SUPPLY FAN Fan:OnOff 0.56 622.50 4.92 5507.64 1120.11 1.00 1.16 General BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00
AIRLOOP DATACENTER TOP SUPPLY FAN Fan:OnOff 0.56 622.50 0.50 559.62 1120.11 1.00 1.61 General BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00


Pumps

Type Control Head [pa] Water Flow [m3/s] Electricity Rate [W] Power Per Water Flow Rate [W-s/m3] Motor Efficiency [W/W] End Use Subcategory
COOLSYS1 PUMP SECONDARY Pump:VariableSpeed Intermittent 105797.75 0.118519 19350.47 163269.45 0.90 General
HEATSYS1 PUMP Pump:VariableSpeed Intermittent 180705.70 0.026862 8089.59 301156.09 0.90 General
COOLSYS1 CHILLER1 PUMP Pump:ConstantSpeed Intermittent 73247.35 0.059259 6698.49 113036.94 0.90 General
COOLSYS1 CHILLER2 PUMP Pump:ConstantSpeed Intermittent 73247.35 0.059259 6698.49 113036.94 0.90 General
PLANT CIRC PUMP Pump:ConstantSpeed Intermittent 179045.11 0.013505 3444.52 255050.01 0.90 General
SWHSYS1 PUMP Pump:ConstantSpeed Intermittent 29891.00 0.000440 56.21 127739.32 0.30 General
TOWERWATERSYS PUMP HeaderedPumps:VariableSpeed Intermittent 148556.62 0.139640 34571.81 247577.87 0.90 General


Service Water Heating

Type Storage Volume [m3] Input [W] Thermal Efficiency [W/W] Recovery Efficiency [W/W] Energy Factor
SWHSYS1 WATER HEATER WaterHeater:Mixed 1.14 87921.32 0.80 0.48 0.06



Table of Contents

Report: HVAC Sizing Summary

For: Entire Facility

Timestamp: 2023-10-16 08:43:24

Zone Sensible Cooling

Calculated Design Load [W] User Design Load [W] User Design Load per Area [W/m2] Calculated Design Air Flow [m3/s] User Design Air Flow [m3/s] Design Day Name Date/Time Of Peak {TIMESTAMP} Thermostat Setpoint Temperature at Peak Load [C] Indoor Temperature at Peak Load [C] Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] Outdoor Temperature at Peak Load [C] Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] Minimum Outdoor Air Flow Rate [m3/s] Heat Gain Rate from DOAS [W]
BASEMENT 82134.63 82134.63 29.55 6.067 6.067 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 24.00 24.00 0.00892 23.42 0.01335 1.200 0.00
CORE_BOTTOM 85333.38 85333.38 34.19 6.303 6.303 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 24.00 24.00 0.00887 23.42 0.01335 1.078 0.00
CORE_MID 804183.56 804183.56 322.17 59.387 59.387 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 24.00 24.00 0.00889 23.42 0.01335 10.778 0.00
CORE_TOP 79543.95 79543.95 31.87 5.874 5.874 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 24.00 24.00 0.00889 23.42 0.01335 1.078 0.00
PERIMETER_BOT_ZN_3 14136.03 14136.03 45.10 1.054 1.054 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:30:00 24.00 24.00 0.00891 30.30 0.01337 0.135 0.00
PERIMETER_BOT_ZN_2 18682.23 18682.23 92.50 1.392 1.392 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 09:00:00 24.00 24.00 0.00870 25.18 0.01336 0.087 0.00
PERIMETER_BOT_ZN_1 21585.35 21585.35 68.87 1.609 1.609 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 13:20:00 24.00 24.00 0.00877 29.99 0.01337 0.135 0.00
PERIMETER_BOT_ZN_4 22658.45 22658.45 112.18 1.689 1.689 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 17:10:00 24.00 24.00 0.00867 28.84 0.01336 0.087 0.00
PERIMETER_MID_ZN_3 134150.82 134150.82 428.03 9.999 9.999 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:40:00 24.00 24.00 0.00911 30.30 0.01337 1.353 0.00
PERIMETER_MID_ZN_2 199008.46 199008.46 985.31 14.833 14.833 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 09:20:00 24.00 24.00 0.00878 25.71 0.01336 0.872 0.00
PERIMETER_MID_ZN_1 216013.70 216013.70 689.22 16.100 16.100 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 13:30:00 24.00 24.00 0.00889 30.07 0.01337 1.353 0.00
PERIMETER_MID_ZN_4 210335.53 210335.53 1041.39 15.677 15.677 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 17:10:00 24.00 24.00 0.00876 28.84 0.01336 0.872 0.00
PERIMETER_TOP_ZN_3 15053.22 15053.22 48.03 1.122 1.122 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 24.00 24.00 0.00911 30.30 0.01337 0.135 0.00
PERIMETER_TOP_ZN_2 20031.91 20031.91 99.18 1.493 1.493 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 09:30:00 24.00 24.00 0.00881 25.98 0.01336 0.087 0.00
PERIMETER_TOP_ZN_1 23123.12 23123.12 73.78 1.724 1.724 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 13:40:00 24.00 24.00 0.00891 30.14 0.01337 0.135 0.00
PERIMETER_TOP_ZN_4 22092.17 22092.17 109.38 1.647 1.647 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 17:10:00 24.00 24.00 0.00878 28.84 0.01336 0.087 0.00
DATACENTER_BOT_ZN_6 8717.42 8717.42 240.79 0.512 0.512 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 19:10:00 27.00 27.00 0.00858 26.50 0.01336 0.016 0.00
DATACENTER_MID_ZN_6 83648.65 83648.65 2310.56 4.917 4.917 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 19:10:00 27.00 27.00 0.00859 26.50 0.01336 0.156 0.00
DATACENTER_TOP_ZN_6 8499.43 8499.43 234.77 0.500 0.500 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 19:10:00 27.00 27.00 0.00859 26.50 0.01336 0.016 0.00
DATACENTER_BASEMENT_ZN_6 373215.54 373215.54 476.23 21.938 21.938 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 07:00:00 27.00 27.00 0.00854 21.84 0.01335 0.338 0.00
The Design Load is the zone sensible load only. It does not include any system effects or ventilation loads.

Zone Sensible Heating

Calculated Design Load [W] User Design Load [W] User Design Load per Area [W/m2] Calculated Design Air Flow [m3/s] User Design Air Flow [m3/s] Design Day Name Date/Time Of Peak {TIMESTAMP} Thermostat Setpoint Temperature at Peak Load [C] Indoor Temperature at Peak Load [C] Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] Outdoor Temperature at Peak Load [C] Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] Minimum Outdoor Air Flow Rate [m3/s] Heat Gain Rate from DOAS [W]
BASEMENT 0.00 0.00 0.00 0.000 1.200 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 07:50:00 21.00 22.93 0.00092 -16.30 0.00092 1.200 0.00
CORE_BOTTOM 5020.01 5020.01 2.01 0.219 1.078 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00796 -16.30 0.00092 1.078 0.00
CORE_MID 319656.96 319656.96 128.06 13.854 13.854 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00800 -16.30 0.00092 10.778 0.00
CORE_TOP 68299.41 68299.41 27.36 2.979 2.979 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00800 -16.30 0.00092 1.078 0.00
PERIMETER_BOT_ZN_3 13176.23 13176.23 42.04 0.576 0.576 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00753 -16.30 0.00092 0.135 0.00
PERIMETER_BOT_ZN_2 8903.75 8903.75 44.08 0.389 0.389 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00756 -16.30 0.00092 0.087 0.00
PERIMETER_BOT_ZN_1 14314.36 14314.36 45.67 0.626 0.626 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00759 -16.30 0.00092 0.135 0.00
PERIMETER_BOT_ZN_4 7309.23 7309.23 36.19 0.319 0.319 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00734 -16.30 0.00092 0.087 0.00
PERIMETER_MID_ZN_3 201556.35 201556.35 643.10 8.816 8.816 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00739 -16.30 0.00092 1.353 0.00
PERIMETER_MID_ZN_2 131929.08 131929.08 653.19 5.771 5.771 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00738 -16.30 0.00092 0.872 0.00
PERIMETER_MID_ZN_1 201557.44 201557.44 643.09 8.817 8.817 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00739 -16.30 0.00092 1.353 0.00
PERIMETER_MID_ZN_4 129339.83 129339.83 640.37 5.658 5.658 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00737 -16.30 0.00092 0.872 0.00
PERIMETER_TOP_ZN_3 25219.65 25219.65 80.47 1.104 1.104 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00740 -16.30 0.00092 0.135 0.00
PERIMETER_TOP_ZN_2 16459.61 16459.61 81.49 0.720 0.720 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00739 -16.30 0.00092 0.087 0.00
PERIMETER_TOP_ZN_1 25219.83 25219.83 80.47 1.104 1.104 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00740 -16.30 0.00092 0.135 0.00
PERIMETER_TOP_ZN_4 16346.57 16346.57 80.93 0.715 0.715 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00738 -16.30 0.00092 0.087 0.00
DATACENTER_BOT_ZN_6 0.00 0.00 0.00 0.000 0.016 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 05:20:00 18.00 24.59 0.00149 -16.30 0.00092 0.016 0.00
DATACENTER_MID_ZN_6 0.00 0.00 0.00 0.000 0.156 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 05:40:00 18.00 22.48 0.00149 -16.30 0.00092 0.156 0.00
DATACENTER_TOP_ZN_6 0.00 0.00 0.00 0.000 0.016 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 05:40:00 18.00 20.44 0.00149 -16.30 0.00092 0.016 0.00
DATACENTER_BASEMENT_ZN_6 0.00 0.00 0.00 0.000 0.338 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 18:40:00 18.00 27.00 0.00850 -16.30 0.00092 0.338 0.00
The Design Load is the zone sensible load only. It does not include any system effects or ventilation loads.

System Design Air Flow Rates

Calculated cooling [m3/s] User cooling [m3/s] Calculated heating [m3/s] User heating [m3/s] Adjusted cooling [m3/s] Adjusted heating [m3/s] Adjusted main [m3/s] Calculated Heating Air Flow Ratio [] User Heating Air Flow Ratio []
VAV_BOT WITH REHEAT 10.38 10.38 2.99 2.99 10.3802 3.1584 10.3802 0.3043 0.3000
VAV_MID WITH REHEAT 96.93 96.93 42.92 42.92 96.9279 42.9160 96.9279 0.4428 0.3000
VAV_TOP WITH REHEAT 10.63 10.63 6.62 6.62 10.6258 6.6218 10.6258 0.6232 0.3000
CAV_BAS 6.07 6.07 1.20 1.20 6.0675 6.0675 6.0675 1.0000 1.0000
AIRLOOP DATACENTER BASEMENT 21.94 21.94 0.34 0.34 21.9382 21.9381 21.9382 1.0000 1.0000
AIRLOOP DATACENTER BOT 0.51 0.51 0.02 0.02 0.5124 0.5124 0.5124 1.0000 1.0000
AIRLOOP DATACENTER MID 4.92 4.92 0.16 0.16 4.9171 4.9171 4.9171 1.0000 1.0000
AIRLOOP DATACENTER TOP 0.50 0.50 0.02 0.02 0.4996 0.4996 0.4996 1.0000 1.0000


Plant Loop Coincident Design Fluid Flow Rate Adjustments

Previous Design Volume Flow Rate [m3/s] Algorithm Volume Flow Rate [m3/s] Coincident Design Volume Flow Rate [m3/s] Coincident Size Adjusted Peak Sizing Period Name Peak Day into Period {TIMESTAMP}[day] Peak Hour Of Day {TIMESTAMP}[hr] Peak Step Start Minute {TIMESTAMP}[min]
None                


Coil Sizing Summary

Coil Type HVAC Type HVAC Name Coil Final Gross Total Capacity [W] Coil Final Gross Sensible Capacity [W] Coil Final Reference Air Volume Flow Rate [m3/s] Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] Coil U-value Times Area Value [W/K] Design Day Name at Sensible Ideal Loads Peak Date/Time at Sensible Ideal Loads Peak Design Day Name at Air Flow Ideal Loads Peak Date/Time at Air Flow Ideal Loads Peak Coil Total Capacity at Ideal Loads Peak [W] Coil Sensible Capacity at Ideal Loads Peak [W] Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] Coil Entering Air Drybulb at Ideal Loads Peak [C] Coil Entering Air Wetbulb at Ideal Loads Peak [C] Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Coil Leaving Air Drybulb at Ideal Loads Peak [C] Coil Leaving Air Wetbulb at Ideal Loads Peak [C] Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Outdoor Air Drybulb at Ideal Loads Peak [C] Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Outdoor Air Wetbulb at Ideal Loads Peak [C] Outdoor Air Flow Percentage at Ideal Loads Peak [%] Zone Air Drybulb at Ideal Loads Peak [C] Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Zone Air Relative Humidity at Ideal Loads Peak [%] Zone Sensible Heat Gain at Ideal Loads Peak [W] Zone Latent Heat Gain at Ideal Loads Peak [W] Coil Total Capacity at Rating Conditions [W] Coil Sensible Capacity at Rating Conditions [W]
CORE_BOTTOM VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT CORE_BOTTOM VAV BOX 24384.088 24384.088 1.972873 0.00021332 504.430 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 24384.09 24384.09 1.972873 12.80 11.37 0.00800000 40.00 20.89 0.00800000 -16.30 0.00092409 -16.30 0.0000 21.00 0.00795757 50.1545 5020.01 0.00 24472.83 24472.83
CORE_MID VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT CORE_MID VAV BOX 509693.531 509693.531 19.360007 0.00445902 12357.357 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 509693.53 509693.53 19.360007 12.80 11.37 0.00800000 40.00 20.89 0.00800000 -16.30 0.00092409 -16.30 0.0000 21.00 0.00800000 50.4185 319656.96 0.00 511339.54 511339.54
CORE_TOP VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT CORE_TOP VAV BOX 97540.465 97540.465 2.978937 0.00085333 2574.535 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 97540.46 97540.46 2.978937 12.80 11.37 0.00800000 40.00 20.89 0.00800000 -16.30 0.00092409 -16.30 0.0000 21.00 0.00800000 50.4185 68299.41 0.00 97875.85 97875.85
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_BOT_ZN_3 VAV BOX 18821.101 18821.101 0.575697 0.00016466 496.422 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 18821.10 18821.10 0.575697 12.80 11.37 0.00800000 40.00 20.89 0.00800000 -16.30 0.00092409 -16.30 0.0000 21.00 0.00753279 47.5148 13176.23 0.00 18883.28 18883.28
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_BOT_ZN_2 VAV BOX 12719.088 12719.088 0.389091 0.00011127 335.460 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 12719.09 12719.09 0.389091 12.80 11.37 0.00800000 40.00 20.89 0.00800000 -16.30 0.00092409 -16.30 0.0000 21.00 0.00755583 47.6583 8903.75 0.00 12760.99 12760.99
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_BOT_ZN_1 VAV BOX 20449.317 20449.317 0.625594 0.00017890 539.331 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 20449.32 20449.32 0.625594 12.80 11.37 0.00800000 40.00 20.89 0.00800000 -16.30 0.00092409 -16.30 0.0000 21.00 0.00759365 47.8935 14314.36 0.00 20516.61 20516.61
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_BOT_ZN_4 VAV BOX 10619.499 10619.499 0.337744 0.00009290 275.319 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 10619.50 10619.50 0.337744 12.80 11.37 0.00800000 40.00 20.89 0.00800000 -16.30 0.00092409 -16.30 0.0000 21.00 0.00734190 46.3266 7309.23 0.00 10652.04 10652.04
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_MID_ZN_3 VAV BOX 287968.008 287968.008 8.816485 0.00251927 7592.179 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 287968.01 287968.01 8.816485 12.80 11.37 0.00800000 40.00 20.89 0.00800000 -16.30 0.00092409 -16.30 0.0000 21.00 0.00739302 46.6475 201556.35 0.00 288896.23 288896.23
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_MID_ZN_2 VAV BOX 188490.160 188490.160 5.771020 0.00164899 4969.413 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 188490.16 188490.16 5.771020 12.80 11.37 0.00800000 40.00 20.89 0.00800000 -16.30 0.00092409 -16.30 0.0000 21.00 0.00738321 46.5866 131929.08 0.00 189097.25 189097.25
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_MID_ZN_1 VAV BOX 287969.554 287969.554 8.816532 0.00251928 7592.219 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 287969.55 287969.55 8.816532 12.80 11.37 0.00800000 40.00 20.89 0.00800000 -16.30 0.00092409 -16.30 0.0000 21.00 0.00739302 46.6475 201557.44 0.00 288897.78 288897.78
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_MID_ZN_4 VAV BOX 184787.328 184787.328 5.657541 0.00161660 4871.833 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 184787.33 184787.33 5.657541 12.80 11.37 0.00800000 40.00 20.89 0.00800000 -16.30 0.00092409 -16.30 0.0000 21.00 0.00737145 46.5133 129339.83 0.00 185382.80 185382.80
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_TOP_ZN_3 VAV BOX 36035.652 36035.652 1.103608 0.00031526 949.936 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 36035.65 36035.65 1.103608 12.80 11.37 0.00800000 40.00 20.89 0.00800000 -16.30 0.00092409 -16.30 0.0000 21.00 0.00739985 46.6917 25219.65 0.00 36150.86 36150.86
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_TOP_ZN_2 VAV BOX 23518.560 23518.560 0.720283 0.00020575 619.967 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 23518.56 23518.56 0.720283 12.80 11.37 0.00800000 40.00 20.89 0.00800000 -16.30 0.00092409 -16.30 0.0000 21.00 0.00738804 46.6184 16459.61 0.00 23593.70 23593.70
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_TOP_ZN_1 VAV BOX 36035.915 36035.915 1.103616 0.00031526 949.943 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 36035.92 36035.92 1.103616 12.80 11.37 0.00800000 40.00 20.89 0.00800000 -16.30 0.00092409 -16.30 0.0000 21.00 0.00739985 46.6918 25219.83 0.00 36151.12 36151.12
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_TOP_ZN_4 VAV BOX 23356.947 23356.947 0.715332 0.00020434 615.707 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 23356.95 23356.95 0.715332 12.80 11.37 0.00800000 40.00 20.89 0.00800000 -16.30 0.00092409 -16.30 0.0000 21.00 0.00738444 46.5960 16346.57 0.00 23431.58 23431.58
VAV_BOT WITH REHEAT COOLING COIL Coil:Cooling:Water AirLoopHVAC VAV_BOT WITH REHEAT 228603.158 -999.000 10.380194 0.00972531 -999.000 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 228603.16 181597.36 10.380194 25.57 17.89 0.00998850 10.91 10.91 0.00850000 30.30 0.01336696 21.83 24.4522 24.00 0.00886297 46.4892 136282.02 0.00 232708.06 175191.99
VAV_BOT WITH REHEAT HEATING COIL Coil:Heating:Water AirLoopHVAC VAV_BOT WITH REHEAT 81559.251 81559.251 3.114058 0.00071352 1298.989 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 22:00:00 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 81559.25 81559.25 3.114058 -9.40 -9.40 0.00217632 12.80 11.37 0.00800000 -16.30 0.00092409 -16.30 81.5075 21.00 0.00751165 47.3820 35282.10 0.00 70856.63 70856.63
VAV_MID WITH REHEAT COOLING COIL Coil:Cooling:Water AirLoopHVAC VAV_MID WITH REHEAT 2200563.120 -999.000 96.927885 0.09361704 -999.000 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 2200563.12 1711308.79 96.927885 25.71 18.08 0.01015989 10.91 10.91 0.00850000 30.30 0.01336696 21.83 26.1864 24.00 0.00896085 46.9963 1251442.35 0.00 2239466.54 1655037.24
VAV_MID WITH REHEAT HEATING COIL Coil:Heating:Water AirLoopHVAC VAV_MID WITH REHEAT 835544.761 835544.761 29.078366 0.00730971 13168.534 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 22:20:00 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 835544.76 835544.76 29.078366 -11.56 -11.56 0.00174431 12.80 11.37 0.00800000 -16.30 0.00092409 -16.30 87.2881 17.93 0.00719538 54.9621 448688.65 0.00 709125.86 709125.86
VAV_TOP WITH REHEAT COOLING COIL Coil:Cooling:Water AirLoopHVAC VAV_TOP WITH REHEAT 233234.659 -999.000 10.625771 0.00992234 -999.000 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:20:00 233234.66 185026.51 10.625771 25.51 17.87 0.00999128 10.91 10.91 0.00850000 30.30 0.01336696 21.83 23.8871 24.00 0.00892998 46.8369 142373.38 0.00 237430.85 178488.26
VAV_TOP WITH REHEAT HEATING COIL Coil:Heating:Water AirLoopHVAC VAV_TOP WITH REHEAT 81603.300 81603.300 3.187731 0.00071390 1302.996 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 22:30:00 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 81603.30 81603.30 3.187731 -8.90 -8.90 0.00221577 12.80 11.37 0.00800000 -16.30 0.00092409 -16.30 79.6237 17.04 0.00715479 57.8237 50969.50 0.00 71287.04 71287.04
CAV_BAS COOLING COIL Coil:Cooling:Water AirLoopHVAC CAV_BAS 123499.090 -999.000 6.067479 0.00525394 -999.000 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 11:00:00 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 123499.09 98418.03 6.067479 24.89 17.59 0.00989654 11.39 11.29 0.00850000 28.16 0.01336316 21.21 19.7801 24.00 0.00895054 46.9417 81025.01 0.00 125762.20 95446.65
CAV_BAS HEATING COIL Coil:Heating:Water AirLoopHVAC CAV_BAS 309371.514 309371.514 6.067479 0.00270652 6738.852 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 309371.51 309371.51 6.067479 -3.22 -6.76 0.00092409 40.00 20.89 0.00800000 -16.30 0.00092409 -16.30 19.7801 23.03 0.00092409 5.2051 0.00 0.00 252165.66 252165.66
AIRLOOP DATACENTER BASEMENT COOLING COIL COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoopHVAC AIRLOOP DATACENTER BASEMENT 435227.102 306220.405 21.938211 0.01065868 -999.000 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 07:10:00 404300.35 397580.40 -999.0 28.48 17.76 0.00861661 12.80 11.87 0.00850000 30.30 0.01336696 21.83 -999.0000 27.00 0.00854210 37.5154 372775.03 0.00 -999.00 -999.00
AIRLOOP DATACENTER BOT COOLING COIL COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoopHVAC AIRLOOP DATACENTER BOT 10034.394 7101.300 0.512428 0.00024574 -999.000 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 19:10:00 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 19:10:00 9300.07 8992.67 -999.0 27.95 17.67 0.00872877 12.80 11.87 0.00850000 26.50 0.01336023 20.72 -999.0000 27.00 0.00858303 37.6902 8717.42 0.00 -999.00 -999.00
AIRLOOP DATACENTER MID COOLING COIL COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoopHVAC AIRLOOP DATACENTER MID 96406.419 68179.426 4.917060 0.00236099 -999.000 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 19:10:00 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 19:10:00 89369.50 86296.99 -999.0 27.95 17.68 0.00873826 12.80 11.87 0.00850000 26.50 0.01336023 20.72 -999.0000 27.00 0.00858649 37.7053 83648.65 0.00 -999.00 -999.00
AIRLOOP DATACENTER TOP COOLING COIL COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoopHVAC AIRLOOP DATACENTER TOP 9793.483 6926.954 0.499615 0.00023984 -999.000 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 19:00:00 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 19:10:00 9078.34 8771.14 -999.0 27.96 17.68 0.00873445 12.80 11.87 0.00850000 26.67 0.01336053 20.77 -999.0000 27.00 0.00858501 37.6989 8498.17 0.00 -999.00 -999.00
AIRLOOP DATACENTER BASEMENT HEATING COIL COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoopHVAC AIRLOOP DATACENTER BASEMENT 435227.102 435227.102 21.938211 0.01065868 -999.000 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 435227.10 435227.10 21.938211 -16.30 -16.30 0.00092409 40.00 20.89 0.00800000 -16.30 0.00092409 -16.30 1.5425 27.00 0.00850000 37.3272 0.00 0.00 -999.00 -999.00
AIRLOOP DATACENTER BOT HEATING COIL COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoopHVAC AIRLOOP DATACENTER BOT 10034.394 10034.394 0.512428 0.00024574 -999.000 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 10034.39 10034.39 0.512428 -16.30 -16.30 0.00092409 40.00 20.89 0.00800000 -16.30 0.00092409 -16.30 3.0506 25.35 0.00148747 7.2799 0.00 0.00 -999.00 -999.00
AIRLOOP DATACENTER MID HEATING COIL COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoopHVAC AIRLOOP DATACENTER MID 96406.419 96406.419 4.917060 0.00236099 -999.000 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 96406.42 96406.42 4.917060 -16.30 -16.30 0.00092409 40.00 20.89 0.00800000 -16.30 0.00092409 -16.30 3.1792 23.67 0.00148748 8.0528 0.00 0.00 -999.00 -999.00
AIRLOOP DATACENTER TOP HEATING COIL COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoopHVAC AIRLOOP DATACENTER TOP 9793.483 9793.483 0.499615 0.00023984 -999.000 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 9793.48 9793.48 0.499615 -16.30 -16.30 0.00092409 40.00 20.89 0.00800000 -16.30 0.00092409 -16.30 3.1289 22.50 0.00148708 8.6411 0.00 0.00 -999.00 -999.00
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL Coil:Heating:Electric AirLoopHVAC AIRLOOP DATACENTER BASEMENT 22473.716 22473.716 -999.0 -999.0 -999.000 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 22473.72 22473.72 21.938211 -0.25 -0.25 0.00838314 40.00 20.89 0.00800000 -16.30 0.00092409 -16.30 1.5425 27.00 0.00850000 37.3272 0.00 0.00 -999.00 -999.00
AIRLOOP DATACENTER BOT_SUPPHEATCOIL Coil:Heating:Electric AirLoopHVAC AIRLOOP DATACENTER BOT 1038.193 1038.193 -999.0 -999.0 -999.000 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 1038.19 1038.19 0.512428 -0.50 -4.08 0.00147029 40.00 20.89 0.00800000 -16.30 0.00092409 -16.30 3.0506 25.35 0.00148747 7.2799 0.00 0.00 -999.00 -999.00
AIRLOOP DATACENTER MID_SUPPHEATCOIL Coil:Heating:Electric AirLoopHVAC AIRLOOP DATACENTER MID 10381.926 10381.926 -999.0 -999.0 -999.000 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 10381.93 10381.93 4.917060 -0.52 -4.10 0.00146957 40.00 20.89 0.00800000 -16.30 0.00092409 -16.30 3.1792 23.67 0.00148748 8.0528 0.00 0.00 -999.00 -999.00
AIRLOOP DATACENTER TOP_SUPPHEATCOIL Coil:Heating:Electric AirLoopHVAC AIRLOOP DATACENTER TOP 1038.193 1038.193 -999.0 -999.0 -999.000 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 1038.19 1038.19 0.499615 -0.51 -4.09 0.00146947 40.00 20.89 0.00800000 -16.30 0.00092409 -16.30 3.1289 22.50 0.00148708 8.6411 0.00 0.00 -999.00 -999.00



Table of Contents

Report: Coil Sizing Details

For: Entire Facility

Timestamp: 2023-10-16 08:43:24

Coils

Coil Type Coil Location HVAC Type HVAC Name Zone Name(s) System Sizing Method Concurrence System Sizing Method Capacity System Sizing Method Air Flow Autosized Coil Capacity? Autosized Coil Airflow? Autosized Coil Water Flow? OA Pretreated prior to coil inlet? Coil Final Gross Total Capacity [W] Coil Final Gross Sensible Capacity [W] Coil Final Reference Air Volume Flow Rate [m3/s] Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] Coil U-value Times Area Value [W/K] Terminal Unit Reheat Coil Multiplier DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio Moist Air Heat Capacity [J/kg-K] Dry Air Heat Capacity [J/kg-K] Standard Air Density Adjusted for Elevation [kg/m3] Supply Fan Name for Coil Supply Fan Type for Coil Supply Fan Maximum Air Volume Flow Rate [m3/s] Supply Fan Maximum Air Mass Flow Rate [kg/s] Plant Name for Coil Plant Fluid Specific Heat Capacity [J/kg-K] Plant Fluid Density [kg/m3] Plant Maximum Fluid Mass Flow Rate [kg/s] Plant Design Fluid Return Temperature [C] Plant Design Fluid Supply Temperature [C] Plant Design Fluid Temperature Difference [deltaC] Plant Design Capacity [W] Coil Capacity Percentage of Plant Design Capacity [%] Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] Design Day Name at Sensible Ideal Loads Peak Date/Time at Sensible Ideal Loads Peak Design Day Name at Total Ideal Loads Peak Date/Time at Total Ideal Loads Peak Design Day Name at Air Flow Ideal Loads Peak Date/Time at Air Flow Ideal Loads Peak Peak Load Type to Size On Coil Total Capacity at Ideal Loads Peak [W] Coil Sensible Capacity at Ideal Loads Peak [W] Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] Coil Entering Air Drybulb at Ideal Loads Peak [C] Coil Entering Air Wetbulb at Ideal Loads Peak [C] Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] Coil Leaving Air Drybulb at Ideal Loads Peak [C] Coil Leaving Air Wetbulb at Ideal Loads Peak [C] Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] Supply Fan Air Heat Gain at Ideal Loads Peak [W] Coil and Fan Net Total Capacity at Ideal Loads Peak [W] Outdoor Air Drybulb at Ideal Loads Peak [C] Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Outdoor Air Wetbulb at Ideal Loads Peak [C] Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] Outdoor Air Flow Percentage at Ideal Loads Peak [%] System Return Air Drybulb at Ideal Loads Peak [C] System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Zone Air Drybulb at Ideal Loads Peak [C] Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Zone Air Relative Humidity at Ideal Loads Peak [%] Zone Sensible Heat Gain at Ideal Loads Peak [W] Zone Latent Heat Gain at Ideal Loads Peak [W] Coil Total Capacity at Rating Conditions [W] Coil Sensible Capacity at Rating Conditions [W] Coil Air Mass Flow Rate at Rating Conditions [kg/s] Coil Entering Air Drybulb at Rating Conditions [C] Coil Entering Air Wetbulb at Rating Conditions [C] Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] Coil Leaving Air Drybulb at Rating Conditions [C] Coil Leaving Air Wetbulb at Rating Conditions [C] Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K]
CORE_BOTTOM VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT CORE_BOTTOM VAV BOX CORE_BOTTOM N/A N/A N/A Yes Yes Yes No 24384.088 24384.088 1.972873 0.00021332 504.430 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1739 unknown unknown -999.0 -999.0   4197.9300 999.8980 26.85905367 54.44 82.22 27.78 3132262.43 0.7785 0.794149 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 24384.09 24384.09 1.0000 2.31600517 1.972873 12.80 11.37 0.00800000 33059.8 40.00 20.89 0.00800000 60796.0 0.21330088 60.00 32.22 27.78 0.000 24384.09 -16.30 0.00092409 -16.30 0.00000000 0.0000 20.88 0.00795757 21.00 0.00795757 50.1545 5020.01 0.00 24472.83 24472.83 2.31600517 12.80 11.60 0.00800000 33059.8 23.16 15.65 0.00800000 43626.7
CORE_MID VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT CORE_MID VAV BOX CORE_MID N/A N/A N/A Yes Yes Yes No 509693.531 509693.531 19.360007 0.00445902 12357.357 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1739 unknown unknown -999.0 -999.0   4197.9300 999.8980 26.85905367 54.44 82.22 27.78 3132262.43 16.2724 16.599864 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 509693.53 509693.53 1.0000 22.72720207 19.360007 12.80 11.37 0.00800000 33059.8 40.00 20.89 0.00800000 60796.0 4.45856649 60.00 32.22 27.78 0.000 509693.53 -16.30 0.00092409 -16.30 0.00000000 0.0000 20.87 0.00800000 21.00 0.00800000 50.4185 319656.96 0.00 511339.54 511339.54 22.72720207 12.80 11.60 0.00800000 33059.8 34.86 19.61 0.00800000 55558.8
CORE_TOP VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT CORE_TOP VAV BOX CORE_TOP N/A N/A N/A Yes Yes Yes No 97540.465 97540.465 2.978937 0.00085333 2574.535 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1739 unknown unknown -999.0 -999.0   4197.9300 999.8980 26.85905367 54.44 82.22 27.78 3132262.43 3.1141 3.176730 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 97540.46 97540.46 1.0000 3.49704994 2.978937 12.80 11.37 0.00800000 33059.8 40.00 20.89 0.00800000 60796.0 0.85323949 60.00 32.22 27.78 0.000 97540.46 -16.30 0.00092409 -16.30 0.00000000 0.0000 20.91 0.00800000 21.00 0.00800000 50.4185 68299.41 0.00 97875.85 97875.85 3.49704994 12.80 11.60 0.00800000 33059.8 40.25 21.26 0.00800000 61047.9
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_BOT_ZN_3 VAV BOX PERIMETER_BOT_ZN_3 N/A N/A N/A Yes Yes Yes No 18821.101 18821.101 0.575697 0.00016466 496.422 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1739 unknown unknown -999.0 -999.0   4197.9300 999.8980 26.85905367 54.44 82.22 27.78 3132262.43 0.6009 0.612972 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 18821.10 18821.10 1.0000 0.67582474 0.575697 12.80 11.37 0.00800000 33059.8 40.00 20.89 0.00800000 60796.0 0.16463841 60.00 32.22 27.78 0.000 18821.10 -16.30 0.00092409 -16.30 0.00000000 0.0000 20.95 0.00753279 21.00 0.00753279 47.5148 13176.23 0.00 18883.28 18883.28 0.67582474 12.80 11.60 0.00800000 33059.8 40.20 21.24 0.00800000 61000.9
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_BOT_ZN_2 VAV BOX PERIMETER_BOT_ZN_2 N/A N/A N/A Yes Yes Yes No 12719.088 12719.088 0.389091 0.00011127 335.460 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1739 unknown unknown -999.0 -999.0   4197.9300 999.8980 26.85905367 54.44 82.22 27.78 3132262.43 0.4061 0.414239 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 12719.09 12719.09 1.0000 0.45676359 0.389091 12.80 11.37 0.00800000 33059.8 40.00 20.89 0.00800000 60796.0 0.11126078 60.00 32.22 27.78 0.000 12719.09 -16.30 0.00092409 -16.30 0.00000000 0.0000 20.95 0.00755583 21.00 0.00755583 47.6583 8903.75 0.00 12760.99 12760.99 0.45676359 12.80 11.60 0.00800000 33059.8 40.20 21.24 0.00800000 60997.7
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_BOT_ZN_1 VAV BOX PERIMETER_BOT_ZN_1 N/A N/A N/A Yes Yes Yes No 20449.317 20449.317 0.625594 0.00017890 539.331 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1739 unknown unknown -999.0 -999.0   4197.9300 999.8980 26.85905367 54.44 82.22 27.78 3132262.43 0.6529 0.666000 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 20449.32 20449.32 1.0000 0.73440087 0.625594 12.80 11.37 0.00800000 33059.8 40.00 20.89 0.00800000 60796.0 0.17888129 60.00 32.22 27.78 0.000 20449.32 -16.30 0.00092409 -16.30 0.00000000 0.0000 20.95 0.00759365 21.00 0.00759365 47.8935 14314.36 0.00 20516.61 20516.61 0.73440087 12.80 11.60 0.00800000 33059.8 40.20 21.24 0.00800000 60996.4
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_BOT_ZN_4 VAV BOX PERIMETER_BOT_ZN_4 N/A N/A N/A Yes Yes Yes No 10619.499 10619.499 0.337744 0.00009290 275.319 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1739 unknown unknown -999.0 -999.0   4197.9300 999.8980 26.85905367 54.44 82.22 27.78 3132262.43 0.3390 0.345859 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 10619.50 10619.50 1.0000 0.39648624 0.337744 12.80 11.37 0.00800000 33059.8 40.00 20.89 0.00800000 60796.0 0.09289453 60.00 32.22 27.78 0.000 10619.50 -16.30 0.00092409 -16.30 0.00000000 0.0000 20.95 0.00734190 21.00 0.00734190 46.3266 7309.23 0.00 10652.04 10652.04 0.39648624 12.80 11.60 0.00800000 33059.8 39.15 20.93 0.00800000 59925.9
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_MID_ZN_3 VAV BOX PERIMETER_MID_ZN_3 N/A N/A N/A Yes Yes Yes No 287968.008 287968.008 8.816485 0.00251927 7592.179 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1739 unknown unknown -999.0 -999.0   4197.9300 999.8980 26.85905367 54.44 82.22 27.78 3132262.43 9.1936 9.378636 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 287968.01 287968.01 1.0000 10.34989469 8.816485 12.80 11.37 0.00800000 33059.8 40.00 20.89 0.00800000 60796.0 2.51901276 60.00 32.22 27.78 0.000 287968.01 -16.30 0.00092409 -16.30 0.00000000 0.0000 20.95 0.00739302 21.00 0.00739302 46.6475 201556.35 0.00 288896.23 288896.23 10.34989469 12.80 11.60 0.00800000 33059.8 40.17 21.23 0.00800000 60972.8
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_MID_ZN_2 VAV BOX PERIMETER_MID_ZN_2 N/A N/A N/A Yes Yes Yes No 188490.160 188490.160 5.771020 0.00164899 4969.413 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1739 unknown unknown -999.0 -999.0   4197.9300 999.8980 26.85905367 54.44 82.22 27.78 3132262.43 6.0177 6.138809 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 188490.16 188490.16 1.0000 6.77474660 5.771020 12.80 11.37 0.00800000 33059.8 40.00 20.89 0.00800000 60796.0 1.64882593 60.00 32.22 27.78 0.000 188490.16 -16.30 0.00092409 -16.30 0.00000000 0.0000 20.95 0.00738321 21.00 0.00738321 46.5866 131929.08 0.00 189097.25 189097.25 6.77474660 12.80 11.60 0.00800000 33059.8 40.17 21.23 0.00800000 60971.9
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_MID_ZN_1 VAV BOX PERIMETER_MID_ZN_1 N/A N/A N/A Yes Yes Yes No 287969.554 287969.554 8.816532 0.00251928 7592.219 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1739 unknown unknown -999.0 -999.0   4197.9300 999.8980 26.85905367 54.44 82.22 27.78 3132262.43 9.1937 9.378686 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 287969.55 287969.55 1.0000 10.34994997 8.816532 12.80 11.37 0.00800000 33059.8 40.00 20.89 0.00800000 60796.0 2.51902629 60.00 32.22 27.78 0.000 287969.55 -16.30 0.00092409 -16.30 0.00000000 0.0000 20.95 0.00739302 21.00 0.00739302 46.6475 201557.44 0.00 288897.78 288897.78 10.34994997 12.80 11.60 0.00800000 33059.8 40.17 21.23 0.00800000 60972.8
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_MID_ZN_4 VAV BOX PERIMETER_MID_ZN_4 N/A N/A N/A Yes Yes Yes No 184787.328 184787.328 5.657541 0.00161660 4871.833 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1739 unknown unknown -999.0 -999.0   4197.9300 999.8980 26.85905367 54.44 82.22 27.78 3132262.43 5.8995 6.018214 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 184787.33 184787.33 1.0000 6.64153087 5.657541 12.80 11.37 0.00800000 33059.8 40.00 20.89 0.00800000 60796.0 1.61643524 60.00 32.22 27.78 0.000 184787.33 -16.30 0.00092409 -16.30 0.00000000 0.0000 20.95 0.00737145 21.00 0.00737145 46.5133 129339.83 0.00 185382.80 185382.80 6.64153087 12.80 11.60 0.00800000 33059.8 40.17 21.23 0.00800000 60972.5
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_TOP_ZN_3 VAV BOX PERIMETER_TOP_ZN_3 N/A N/A N/A Yes Yes Yes No 36035.652 36035.652 1.103608 0.00031526 949.936 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1739 unknown unknown -999.0 -999.0   4197.9300 999.8980 26.85905367 54.44 82.22 27.78 3132262.43 1.1505 1.173621 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 36035.65 36035.65 1.0000 1.29555383 1.103608 12.80 11.37 0.00800000 33059.8 40.00 20.89 0.00800000 60796.0 0.31522345 60.00 32.22 27.78 0.000 36035.65 -16.30 0.00092409 -16.30 0.00000000 0.0000 20.94 0.00739985 21.00 0.00739985 46.6917 25219.65 0.00 36150.86 36150.86 1.29555383 12.80 11.60 0.00800000 33059.8 40.16 21.23 0.00800000 60963.6
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_TOP_ZN_2 VAV BOX PERIMETER_TOP_ZN_2 N/A N/A N/A Yes Yes Yes No 23518.560 23518.560 0.720283 0.00020575 619.967 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1739 unknown unknown -999.0 -999.0   4197.9300 999.8980 26.85905367 54.44 82.22 27.78 3132262.43 0.7508 0.765960 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 23518.56 23518.56 1.0000 0.84555809 0.720283 12.80 11.37 0.00800000 33059.8 40.00 20.89 0.00800000 60796.0 0.20572964 60.00 32.22 27.78 0.000 23518.56 -16.30 0.00092409 -16.30 0.00000000 0.0000 20.94 0.00738804 21.00 0.00738804 46.6184 16459.61 0.00 23593.70 23593.70 0.84555809 12.80 11.60 0.00800000 33059.8 40.16 21.23 0.00800000 60962.9
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_TOP_ZN_1 VAV BOX PERIMETER_TOP_ZN_1 N/A N/A N/A Yes Yes Yes No 36035.915 36035.915 1.103616 0.00031526 949.943 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1739 unknown unknown -999.0 -999.0   4197.9300 999.8980 26.85905367 54.44 82.22 27.78 3132262.43 1.1505 1.173629 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 36035.92 36035.92 1.0000 1.29556327 1.103616 12.80 11.37 0.00800000 33059.8 40.00 20.89 0.00800000 60796.0 0.31522575 60.00 32.22 27.78 0.000 36035.92 -16.30 0.00092409 -16.30 0.00000000 0.0000 20.94 0.00739985 21.00 0.00739985 46.6918 25219.83 0.00 36151.12 36151.12 1.29556327 12.80 11.60 0.00800000 33059.8 40.16 21.23 0.00800000 60963.6
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_TOP_ZN_4 VAV BOX PERIMETER_TOP_ZN_4 N/A N/A N/A Yes Yes Yes No 23356.947 23356.947 0.715332 0.00020434 615.707 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1739 unknown unknown -999.0 -999.0   4197.9300 999.8980 26.85905367 54.44 82.22 27.78 3132262.43 0.7457 0.760697 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 23356.95 23356.95 1.0000 0.83974691 0.715332 12.80 11.37 0.00800000 33059.8 40.00 20.89 0.00800000 60796.0 0.20431591 60.00 32.22 27.78 0.000 23356.95 -16.30 0.00092409 -16.30 0.00000000 0.0000 20.94 0.00738444 21.00 0.00738444 46.5960 16346.57 0.00 23431.58 23431.58 0.83974691 12.80 11.60 0.00800000 33059.8 40.16 21.23 0.00800000 60963.0
VAV_BOT WITH REHEAT COOLING COIL Coil:Cooling:Water AirLoop AirLoopHVAC VAV_BOT WITH REHEAT CORE_BOTTOM; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_4; Coincident CoolingDesignCapacity N/A Yes Yes Yes No 228603.158 -999.000 10.380194 0.00972531 -999.000 -999.0000 1.00000 1.00000 1023.4081 1004.8586 1.1739 VAV_BOT WITH REHEAT FAN Fan:VariableVolume 10.380194 12.18557256   4197.9300 999.8980 118.50653719 12.27 6.67 5.60 2785900.03 8.2057 8.205720 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 Sensible 228603.16 181597.36 1.0000 12.18557256 10.380194 25.57 17.89 0.00998850 51152.5 10.91 10.91 0.00850000 32392.4 9.72431473 6.67 12.27 5.60 23579.579 205023.58 30.30 0.01336696 21.83 2.53819000 24.4522 24.00 0.00886297 24.00 0.00886297 46.4892 136282.02 0.00 232708.06 175191.99 12.18557256 25.57 18.17 0.00998850 51152.5 11.53 11.18 0.00811724 32055.5
VAV_BOT WITH REHEAT HEATING COIL Coil:Heating:Water AirLoop AirLoopHVAC VAV_BOT WITH REHEAT CORE_BOTTOM; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_4; Coincident HeatingDesignCapacity N/A Yes Yes Yes No 81559.251 81559.251 3.114058 0.00071352 1298.989 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1739 VAV_BOT WITH REHEAT FAN Fan:VariableVolume 10.380194 12.18557256   4197.9300 999.8980 26.85905367 54.44 82.22 27.78 3132262.43 2.6038 2.656248 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 22:00:00 unknown unknown BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 81559.25 81559.25 1.0000 3.65567177 3.114058 -9.40 -9.40 0.00217632 -4043.2 12.80 11.37 0.00800000 33059.8 0.71344312 60.00 32.22 27.78 0.000 81559.25 -16.30 0.00092409 -16.30 2.53819000 81.5075 21.00 0.00769562 21.00 0.00751165 47.3820 35282.10 0.00 70856.63 70856.63 3.65567177 2.80 -0.91 0.00217632 8267.7 22.01 9.39 0.00217632 27650.4
VAV_MID WITH REHEAT COOLING COIL Coil:Cooling:Water AirLoop AirLoopHVAC VAV_MID WITH REHEAT CORE_MID; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_4; Coincident CoolingDesignCapacity N/A Yes Yes Yes No 2200563.120 -999.000 96.927885 0.09361704 -999.000 -999.0000 1.00000 1.00000 1023.7267 1004.8586 1.1739 VAV_MID WITH REHEAT FAN Fan:VariableVolume 96.927885 113.78609815   4197.9300 999.8980 118.50653719 12.27 6.67 5.60 2785900.03 78.9893 78.989307 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 Sensible 2200563.12 1711308.79 1.0000 113.78609815 96.927885 25.71 18.08 0.01015989 51732.5 10.91 10.91 0.00850000 32393.0 93.60749226 6.67 12.27 5.60 220180.728 1980382.39 30.30 0.01336696 21.83 25.38195000 26.1864 24.00 0.00896085 24.00 0.00896085 46.9963 1251442.35 0.00 2239466.54 1655037.24 113.78609815 25.71 18.35 0.01015989 51732.5 11.51 11.17 0.00812359 32051.1
VAV_MID WITH REHEAT HEATING COIL Coil:Heating:Water AirLoop AirLoopHVAC VAV_MID WITH REHEAT CORE_MID; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_4; Coincident HeatingDesignCapacity N/A Yes Yes Yes No 835544.761 835544.761 29.078366 0.00730971 13168.534 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1739 VAV_MID WITH REHEAT FAN Fan:VariableVolume 96.927885 113.78609815   4197.9300 999.8980 26.85905367 54.44 82.22 27.78 3132262.43 26.6754 27.212293 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 22:20:00 unknown unknown BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 835544.76 835544.76 1.0000 34.13582945 29.078366 -11.56 -11.56 0.00174431 -7289.7 12.80 11.37 0.00800000 33059.8 7.30896440 60.00 32.22 27.78 0.000 835544.76 -16.30 0.00092409 -16.30 25.38195000 87.2881 21.00 0.00737647 17.93 0.00719538 54.9621 448688.65 0.00 709125.86 709125.86 34.13582945 2.80 -1.58 0.00174431 7185.0 23.41 9.53 0.00174431 27958.7
VAV_TOP WITH REHEAT COOLING COIL Coil:Cooling:Water AirLoop AirLoopHVAC VAV_TOP WITH REHEAT CORE_TOP; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_4; Coincident CoolingDesignCapacity N/A Yes Yes Yes No 233234.659 -999.000 10.625771 0.00992234 -999.000 -999.0000 1.00000 1.00000 1023.4133 1004.8586 1.1739 VAV_TOP WITH REHEAT FAN Fan:VariableVolume 10.625771 12.47386165   4197.9300 999.8980 118.50653719 12.27 6.67 5.60 2785900.03 8.3720 8.371968 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:20:00 Sensible 233234.66 185026.51 1.0000 12.47386165 10.625771 25.51 17.87 0.00999128 51090.3 10.91 10.91 0.00850000 32392.4 9.92132938 6.67 12.27 5.60 24137.430 209097.23 30.30 0.01336696 21.83 2.53819000 23.8871 24.00 0.00892998 24.00 0.00892998 46.8369 142373.38 0.00 237430.85 178488.26 12.47386165 25.51 18.15 0.00999128 51090.3 11.52 11.18 0.00811793 32056.0
VAV_TOP WITH REHEAT HEATING COIL Coil:Heating:Water AirLoop AirLoopHVAC VAV_TOP WITH REHEAT CORE_TOP; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_4; Coincident HeatingDesignCapacity N/A Yes Yes Yes No 81603.300 81603.300 3.187731 0.00071390 1302.996 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1739 VAV_TOP WITH REHEAT FAN Fan:VariableVolume 10.625771 12.47386165   4197.9300 999.8980 26.85905367 54.44 82.22 27.78 3132262.43 2.6053 2.657683 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 22:30:00 unknown unknown BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 81603.30 81603.30 1.0000 3.74215849 3.187731 -8.90 -8.90 0.00221577 -3439.3 12.80 11.37 0.00800000 33059.8 0.71382844 60.00 32.22 27.78 0.000 81603.30 -16.30 0.00092409 -16.30 2.53819000 79.6237 20.01 0.00726323 17.04 0.00715479 57.8237 50969.50 0.00 71287.04 71287.04 3.74215849 2.80 -0.85 0.00221577 8366.6 21.68 9.28 0.00221577 27416.3
CAV_BAS COOLING COIL Coil:Cooling:Water AirLoop AirLoopHVAC CAV_BAS BASEMENT Coincident CoolingDesignCapacity N/A Yes Yes Yes No 123499.090 -999.000 6.067479 0.00525394 -999.000 -999.0000 1.00000 1.00000 1023.2372 1004.8586 1.1739 CAV_BAS FAN Fan:ConstantVolume 6.067479 7.12276751   4197.9300 999.8980 118.50653719 12.27 6.67 5.60 2785900.03 4.4330 4.433005 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 11:00:00 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 08:20:00 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 Sensible 123499.09 98418.03 1.0000 7.12276751 6.067479 24.89 17.59 0.00989654 50220.1 11.39 11.29 0.00850000 32881.4 5.25340083 6.67 12.27 5.60 10288.348 113210.74 28.16 0.01336316 21.21 1.20015641 19.7801 24.00 0.00895054 24.00 0.00895054 46.9417 81025.01 0.00 125762.20 95446.65 7.12276751 24.89 17.86 0.00989654 50220.1 11.80 11.39 0.00820951 32563.7
CAV_BAS HEATING COIL Coil:Heating:Water AirLoop AirLoopHVAC CAV_BAS BASEMENT Coincident HeatingDesignCapacity N/A Yes Yes Yes No 309371.514 309371.514 6.067479 0.00270652 6738.852 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1739 CAV_BAS FAN Fan:ConstantVolume 6.067479 7.12276751   4197.9300 999.8980 26.85905367 54.44 82.22 27.78 3132262.43 9.8769 10.075712 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 unknown unknown BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 Sensible 309371.51 309371.51 1.0000 7.12276751 6.067479 -3.22 -6.76 0.00092409 -934.2 40.00 20.89 0.00800000 60796.0 2.70624087 60.00 32.22 27.78 0.000 309371.51 -16.30 0.00092409 -16.30 1.20015641 19.7801 0.00 0.00092409 23.03 0.00092409 5.2051 0.00 0.00 252165.66 252165.66 7.12276751 12.80 3.26 0.00092409 15195.0 47.97 18.22 0.00092409 50597.8
AIRLOOP DATACENTER BASEMENT COOLING COIL COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoop AirLoopHVAC AIRLOOP DATACENTER BASEMENT DATACENTER_BASEMENT_ZN_6 Coincident CoolingDesignCapacity N/A Yes No unknown No 435227.102 306220.405 21.938211 0.01065868 -999.000 -999.0000 -999.00000 -999.00000 1020.8578 1004.8586 1.1739 unknown unknown -999.0 -999.0   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 07:10:00 Sensible 404300.35 397580.40 0.9289 -999.0 -999.0 28.48 17.76 0.00861661 50620.8 12.80 11.87 0.00850000 34322.2 -999.0 -999.00 -999.00 -999.00 0.000 404300.35 30.30 0.01336696 21.83 0.33839277 -999.0000 27.00 0.00854210 27.00 0.00854210 37.5154 372775.03 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
AIRLOOP DATACENTER BOT COOLING COIL COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoop AirLoopHVAC AIRLOOP DATACENTER BOT DATACENTER_BOT_ZN_6 Coincident CoolingDesignCapacity N/A Yes No unknown No 10034.394 7101.300 0.512428 0.00024574 -999.000 -999.0000 -999.00000 -999.00000 1021.0663 1004.8586 1.1739 unknown unknown -999.0 -999.0   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 19:10:00 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 19:10:00 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 19:10:00 Sensible 9300.07 8992.67 0.9268 -999.0 -999.0 27.95 17.67 0.00872877 50372.5 12.80 11.87 0.00850000 34322.2 -999.0 -999.00 -999.00 -999.00 0.000 9300.07 26.50 0.01336023 20.72 0.01563234 -999.0000 27.00 0.00858303 27.00 0.00858303 37.6902 8717.42 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
AIRLOOP DATACENTER MID COOLING COIL COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoop AirLoopHVAC AIRLOOP DATACENTER MID DATACENTER_MID_ZN_6 Coincident CoolingDesignCapacity N/A Yes No unknown No 96406.419 68179.426 4.917060 0.00236099 -999.000 -999.0000 -999.00000 -999.00000 1021.0840 1004.8586 1.1739 unknown unknown -999.0 -999.0   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 19:10:00 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 19:10:00 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 19:10:00 Sensible 89369.50 86296.99 0.9270 -999.0 -999.0 27.95 17.68 0.00873826 50396.0 12.80 11.87 0.00850000 34322.2 -999.0 -999.00 -999.00 -999.00 0.000 89369.50 26.50 0.01336023 20.72 0.15632344 -999.0000 27.00 0.00858649 27.00 0.00858649 37.7053 83648.65 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
AIRLOOP DATACENTER TOP COOLING COIL COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoop AirLoopHVAC AIRLOOP DATACENTER TOP DATACENTER_TOP_ZN_6 Coincident CoolingDesignCapacity N/A Yes No unknown No 9793.483 6926.954 0.499615 0.00023984 -999.000 -999.0000 -999.00000 -999.00000 1021.0769 1004.8586 1.1739 unknown unknown -999.0 -999.0   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 19:00:00 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 19:00:00 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 19:10:00 Sensible 9078.34 8771.14 0.9270 -999.0 -999.0 27.96 17.68 0.00873445 50392.0 12.80 11.87 0.00850000 34322.2 -999.0 -999.00 -999.00 -999.00 0.000 9078.34 26.67 0.01336053 20.77 0.01563234 -999.0000 27.00 0.00858501 27.00 0.00858501 37.6989 8498.17 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
AIRLOOP DATACENTER BASEMENT HEATING COIL COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoop AirLoopHVAC AIRLOOP DATACENTER BASEMENT DATACENTER_BASEMENT_ZN_6 Coincident HeatingDesignCapacity N/A Yes No unknown No 435227.102 435227.102 21.938211 0.01065868 -999.000 -999.0000 -999.00000 -999.00000 1019.7116 1004.8586 1.1739 unknown unknown -999.0 -999.0   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 unknown unknown BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 Sensible 435227.10 435227.10 1.0000 25.75382141 21.938211 -16.30 -16.30 0.00092409 -14095.8 40.00 20.89 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 435227.10 -16.30 0.00092409 -16.30 0.33839277 1.5425 0.00 0.00850000 27.00 0.00850000 37.3272 0.00 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
AIRLOOP DATACENTER BOT HEATING COIL COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoop AirLoopHVAC AIRLOOP DATACENTER BOT DATACENTER_BOT_ZN_6 Coincident HeatingDesignCapacity N/A Yes No unknown No 10034.394 10034.394 0.512428 0.00024574 -999.000 -999.0000 -999.00000 -999.00000 1019.7116 1004.8586 1.1739 unknown unknown -999.0 -999.0   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 unknown unknown BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 Sensible 10034.39 10034.39 1.0000 0.60155198 0.512428 -16.30 -16.30 0.00092409 -14095.8 40.00 20.89 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 10034.39 -16.30 0.00092409 -16.30 0.01563234 3.0506 0.00 0.00148747 25.35 0.00148747 7.2799 0.00 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
AIRLOOP DATACENTER MID HEATING COIL COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoop AirLoopHVAC AIRLOOP DATACENTER MID DATACENTER_MID_ZN_6 Coincident HeatingDesignCapacity N/A Yes No unknown No 96406.419 96406.419 4.917060 0.00236099 -999.000 -999.0000 -999.00000 -999.00000 1019.7116 1004.8586 1.1739 unknown unknown -999.0 -999.0   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 unknown unknown BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 Sensible 96406.42 96406.42 1.0000 5.77226170 4.917060 -16.30 -16.30 0.00092409 -14095.8 40.00 20.89 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 96406.42 -16.30 0.00092409 -16.30 0.15632344 3.1792 0.00 0.00148748 23.67 0.00148748 8.0528 0.00 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
AIRLOOP DATACENTER TOP HEATING COIL COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoop AirLoopHVAC AIRLOOP DATACENTER TOP DATACENTER_TOP_ZN_6 Coincident HeatingDesignCapacity N/A Yes No unknown No 9793.483 9793.483 0.499615 0.00023984 -999.000 -999.0000 -999.00000 -999.00000 1019.7116 1004.8586 1.1739 unknown unknown -999.0 -999.0   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 unknown unknown BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 Sensible 9793.48 9793.48 1.0000 0.58651054 0.499615 -16.30 -16.30 0.00092409 -14095.8 40.00 20.89 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 9793.48 -16.30 0.00092409 -16.30 0.01563234 3.1289 0.00 0.00148708 22.50 0.00148708 8.6411 0.00 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL Coil:Heating:Electric AirLoop AirLoopHVAC AIRLOOP DATACENTER BASEMENT DATACENTER_BASEMENT_ZN_6 Coincident HeatingDesignCapacity N/A Yes No unknown No 22473.716 22473.716 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1739 AIRLOOP DATACENTER BASEMENT SUPPLY FAN Fan:OnOff 21.938211 25.75382141   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 unknown unknown BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 Sensible 22473.72 22473.72 1.0000 25.75382141 21.938211 -0.25 -0.25 0.00838314 20709.2 40.00 20.89 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 22473.72 -16.30 0.00092409 -16.30 0.33839277 1.5425 0.00 0.00850000 27.00 0.00850000 37.3272 0.00 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
AIRLOOP DATACENTER BOT_SUPPHEATCOIL Coil:Heating:Electric AirLoop AirLoopHVAC AIRLOOP DATACENTER BOT DATACENTER_BOT_ZN_6 Coincident HeatingDesignCapacity N/A Yes No unknown No 1038.193 1038.193 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1739 AIRLOOP DATACENTER BOT SUPPLY FAN Fan:OnOff 0.512428 0.60155198   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 unknown unknown BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 Sensible 1038.19 1038.19 1.0000 0.60155198 0.512428 -0.50 -4.08 0.00147029 3176.1 40.00 20.89 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 1038.19 -16.30 0.00092409 -16.30 0.01563234 3.0506 0.00 0.00148747 25.35 0.00148747 7.2799 0.00 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
AIRLOOP DATACENTER MID_SUPPHEATCOIL Coil:Heating:Electric AirLoop AirLoopHVAC AIRLOOP DATACENTER MID DATACENTER_MID_ZN_6 Coincident HeatingDesignCapacity N/A Yes No unknown No 10381.926 10381.926 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1739 AIRLOOP DATACENTER MID SUPPLY FAN Fan:OnOff 4.917060 5.77226170   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 unknown unknown BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 Sensible 10381.93 10381.93 1.0000 5.77226170 4.917060 -0.52 -4.10 0.00146957 3153.2 40.00 20.89 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 10381.93 -16.30 0.00092409 -16.30 0.15632344 3.1792 0.00 0.00148748 23.67 0.00148748 8.0528 0.00 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
AIRLOOP DATACENTER TOP_SUPPHEATCOIL Coil:Heating:Electric AirLoop AirLoopHVAC AIRLOOP DATACENTER TOP DATACENTER_TOP_ZN_6 Coincident HeatingDesignCapacity N/A Yes No unknown No 1038.193 1038.193 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1739 AIRLOOP DATACENTER TOP SUPPLY FAN Fan:OnOff 0.499615 0.58651054   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 unknown unknown BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 Sensible 1038.19 1038.19 1.0000 0.58651054 0.499615 -0.51 -4.09 0.00146947 3161.2 40.00 20.89 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 1038.19 -16.30 0.00092409 -16.30 0.01563234 3.1289 0.00 0.00148708 22.50 0.00148708 8.6411 0.00 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0



Table of Contents

Report: System Summary

For: Entire Facility

Timestamp: 2023-10-16 08:43:24

Economizer

High Limit Shutoff Control Minimum Outdoor Air [m3/s] Maximum Outdoor Air [m3/s] Return Air Temp Limit Return Air Enthalpy Limit Outdoor Air Temperature Limit [C] Outdoor Air Enthalpy Limit [C]
VAV_BOT WITH REHEAT_OA_CONTROLLER DifferentialDryBulb 2.54 10.38 -      
VAV_MID WITH REHEAT_OA_CONTROLLER DifferentialDryBulb 25.38 96.93 -      
VAV_TOP WITH REHEAT_OA_CONTROLLER DifferentialDryBulb 2.54 10.63 -      
CAV_BAS_OA_CONTROLLER DifferentialDryBulb 1.20 6.07 -      
AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER DifferentialDryBulb 0.34 21.94 -      


Demand Controlled Ventilation using Controller:MechanicalVentilation

Controller:MechanicalVentilation Name Outdoor Air Per Person [m3/s-person] Outdoor Air Per Area [m3/s-m2] Outdoor Air Per Zone [m3/s] Outdoor Air ACH [ach] Outdoor Air Method Outdoor Air Schedule Name Air Distribution Effectiveness in Cooling Mode Air Distribution Effectiveness in Heating Mode Air Distribution Effectiveness Schedule Name
CORE_BOTTOM VAV_BOT WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
CORE_MID VAV_MID WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
CORE_TOP VAV_TOP WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_BOT_ZN_3 VAV_BOT WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_BOT_ZN_2 VAV_BOT WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_BOT_ZN_1 VAV_BOT WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_BOT_ZN_4 VAV_BOT WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_MID_ZN_3 VAV_MID WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_MID_ZN_2 VAV_MID WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_MID_ZN_1 VAV_MID WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_MID_ZN_4 VAV_MID WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_TOP_ZN_3 VAV_TOP WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_TOP_ZN_2 VAV_TOP WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_TOP_ZN_1 VAV_TOP WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_TOP_ZN_4 VAV_TOP WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  


Time Not Comfortable Based on Simple ASHRAE 55-2004

Winter Clothes [hr] Summer Clothes [hr] Summer or Winter Clothes [hr]
BASEMENT 2580.00 1557.67 398.00
CORE_BOTTOM 2478.17 1390.33 12.50
CORE_MID 1931.33 3055.83 197.33
CORE_TOP 2517.67 3618.17 961.00
PERIMETER_BOT_ZN_3 2467.00 3331.83 737.50
PERIMETER_BOT_ZN_2 2678.50 3457.83 809.83
PERIMETER_BOT_ZN_1 2833.67 3065.33 776.00
PERIMETER_BOT_ZN_4 2884.33 2680.50 502.83
PERIMETER_MID_ZN_3 3344.50 4043.17 2008.33
PERIMETER_MID_ZN_2 2956.17 3393.33 1705.00
PERIMETER_MID_ZN_1 3247.67 3507.83 1469.67
PERIMETER_MID_ZN_4 3355.50 3959.50 1766.33
PERIMETER_TOP_ZN_3 3685.83 4248.50 2445.00
PERIMETER_TOP_ZN_2 3817.00 4005.33 2281.50
PERIMETER_TOP_ZN_1 3503.50 3795.33 1912.83
PERIMETER_TOP_ZN_4 3592.67 4151.50 2150.33
DATACENTER_BOT_ZN_6 5904.33 1045.83 1045.83
DATACENTER_MID_ZN_6 5136.17 390.67 277.50
DATACENTER_TOP_ZN_6 4719.17 801.00 432.33
DATACENTER_BASEMENT_ZN_6 5943.00 5607.83 5607.83
GROUNDFLOOR_PLENUM 0.00 0.00 0.00
MIDFLOOR_PLENUM 0.00 0.00 0.00
TOPFLOOR_PLENUM 0.00 0.00 0.00
Facility 5943.00 5943.00 5937.67
Aggregated over the RunPeriods for Weather

Time Setpoint Not Met

During Heating [hr] During Cooling [hr] During Occupied Heating [hr] During Occupied Cooling [hr]
BASEMENT 0.00 32.50 0.00 1.00
CORE_BOTTOM 0.00 0.00 0.00 0.00
CORE_MID 1.17 0.50 0.50 0.50
CORE_TOP 13.67 0.00 1.83 0.00
PERIMETER_BOT_ZN_3 3.67 3.50 0.00 3.00
PERIMETER_BOT_ZN_2 5.17 18.83 0.00 18.83
PERIMETER_BOT_ZN_1 7.00 29.83 0.00 29.17
PERIMETER_BOT_ZN_4 1.50 77.67 0.00 35.50
PERIMETER_MID_ZN_3 135.50 1.33 37.00 1.00
PERIMETER_MID_ZN_2 79.00 20.50 6.67 20.50
PERIMETER_MID_ZN_1 64.67 28.17 3.00 27.67
PERIMETER_MID_ZN_4 60.67 30.00 3.67 16.50
PERIMETER_TOP_ZN_3 313.83 4.50 102.67 3.67
PERIMETER_TOP_ZN_2 189.00 20.83 35.67 20.33
PERIMETER_TOP_ZN_1 163.83 23.33 27.50 22.00
PERIMETER_TOP_ZN_4 139.83 30.00 24.67 17.33
DATACENTER_BOT_ZN_6 0.00 0.00 0.00 0.00
DATACENTER_MID_ZN_6 0.00 0.00 0.00 0.00
DATACENTER_TOP_ZN_6 0.00 0.00 0.00 0.00
DATACENTER_BASEMENT_ZN_6 0.00 338.50 0.00 262.67
GROUNDFLOOR_PLENUM 0.00 0.00 0.00 0.00
MIDFLOOR_PLENUM 0.00 0.00 0.00 0.00
TOPFLOOR_PLENUM 0.00 0.00 0.00 0.00
Facility 358.67 513.00 111.50 366.00
Aggregated over the RunPeriods for Weather


Table of Contents

Report: Outdoor Air Summary

For: Entire Facility

Timestamp: 2023-10-16 08:43:24

Average Outdoor Air During Occupied Hours

Average Number of Occupants Nominal Number of Occupants Zone Volume [m3] Mechanical Ventilation [ach] Infiltration [ach] AFN Infiltration [ach] Simple Ventilation [ach]
BASEMENT 62.11 149.60 6779.02 1.352 0.000 0.000 0.000
CORE_BOTTOM 55.78 134.35 6849.35 1.081 0.000 0.000 0.000
CORE_MID 55.78 134.35 6849.35 0.875 0.000 0.000 0.000
CORE_TOP 55.78 134.35 6849.35 0.862 0.000 0.000 0.000
PERIMETER_BOT_ZN_3 7.00 16.87 860.00 1.021 0.059 0.000 0.000
PERIMETER_BOT_ZN_2 4.51 10.87 554.22 1.646 0.061 0.000 0.000
PERIMETER_BOT_ZN_1 7.00 16.87 860.02 1.509 0.059 0.000 0.000
PERIMETER_BOT_ZN_4 4.51 10.87 554.22 2.185 0.061 0.000 0.000
PERIMETER_MID_ZN_3 7.00 16.87 860.00 0.900 0.138 0.000 0.000
PERIMETER_MID_ZN_2 3.94 10.87 554.22 1.578 0.151 0.000 0.000
PERIMETER_MID_ZN_1 7.00 16.87 860.02 1.460 0.138 0.000 0.000
PERIMETER_MID_ZN_4 4.51 10.87 554.22 1.761 0.143 0.000 0.000
PERIMETER_TOP_ZN_3 7.00 16.87 860.00 0.934 0.171 0.000 0.000
PERIMETER_TOP_ZN_2 4.51 10.87 554.22 1.726 0.177 0.000 0.000
PERIMETER_TOP_ZN_1 7.00 16.87 860.02 1.493 0.171 0.000 0.000
PERIMETER_TOP_ZN_4 4.51 10.87 554.22 1.829 0.177 0.000 0.000
DATACENTER_BOT_ZN_6 0.81 1.95 99.34 0.427 0.000 0.000 0.000
DATACENTER_MID_ZN_6 0.81 1.95 99.34 0.427 0.000 0.000 0.000
DATACENTER_TOP_ZN_6 0.81 1.95 99.34 0.427 0.000 0.000 0.000
DATACENTER_BASEMENT_ZN_6 17.51 42.18 1911.37 25.947 0.000 0.000 0.000
Values shown for a single zone without multipliers

Minimum Outdoor Air During Occupied Hours

Average Number of Occupants Nominal Number of Occupants Zone Volume [m3] Mechanical Ventilation [ach] Infiltration [ach] AFN Infiltration [ach] Simple Ventilation [ach]
BASEMENT 62.11 149.60 6779.02 0.000 0.000 0.000 0.000
CORE_BOTTOM 55.78 134.35 6849.35 0.000 0.000 0.000 0.000
CORE_MID 55.78 134.35 6849.35 0.000 0.000 0.000 0.000
CORE_TOP 55.78 134.35 6849.35 0.000 0.000 0.000 0.000
PERIMETER_BOT_ZN_3 7.00 16.87 860.00 0.000 0.000 0.000 0.000
PERIMETER_BOT_ZN_2 4.51 10.87 554.22 0.000 0.000 0.000 0.000
PERIMETER_BOT_ZN_1 7.00 16.87 860.02 0.000 0.000 0.000 0.000
PERIMETER_BOT_ZN_4 4.51 10.87 554.22 0.000 0.000 0.000 0.000
PERIMETER_MID_ZN_3 7.00 16.87 860.00 0.000 0.000 0.000 0.000
PERIMETER_MID_ZN_2 3.94 10.87 554.22 0.000 0.000 0.000 0.000
PERIMETER_MID_ZN_1 7.00 16.87 860.02 0.000 0.000 0.000 0.000
PERIMETER_MID_ZN_4 4.51 10.87 554.22 0.000 0.000 0.000 0.000
PERIMETER_TOP_ZN_3 7.00 16.87 860.00 0.000 0.000 0.000 0.000
PERIMETER_TOP_ZN_2 4.51 10.87 554.22 0.000 0.000 0.000 0.000
PERIMETER_TOP_ZN_1 7.00 16.87 860.02 0.000 0.000 0.000 0.000
PERIMETER_TOP_ZN_4 4.51 10.87 554.22 0.000 0.000 0.000 0.000
DATACENTER_BOT_ZN_6 0.81 1.95 99.34 0.000 0.000 0.000 0.000
DATACENTER_MID_ZN_6 0.81 1.95 99.34 0.000 0.000 0.000 0.000
DATACENTER_TOP_ZN_6 0.81 1.95 99.34 0.000 0.000 0.000 0.000
DATACENTER_BASEMENT_ZN_6 17.51 42.18 1911.37 0.000 0.000 0.000 0.000
Values shown for a single zone without multipliers


Table of Contents

Report: Outdoor Air Details

For: Entire Facility

Timestamp: 2023-10-16 08:43:24

Mechanical Ventilation Parameters by Zone

AirLoop Name Average Number of Occupants Nominal Number of Occupants Zone Volume [m3] Zone Area [m2] Design Zone Outdoor Airflow - Voz [m3/s] Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s]
BASEMENT CAV_BAS 62.11 149.60 6779.02 2779.43 1.2002 1.200
CORE_BOTTOM VAV_BOT WITH REHEAT 55.78 134.35 6849.35 2496.12 0.0000 1.078
CORE_MID VAV_MID WITH REHEAT 55.78 134.35 6849.35 2496.12 0.0000 10.778
CORE_TOP VAV_TOP WITH REHEAT 55.78 134.35 6849.35 2496.12 0.0000 1.078
PERIMETER_BOT_ZN_3 VAV_BOT WITH REHEAT 7.00 16.87 860.00 313.41 0.0000 0.135
PERIMETER_BOT_ZN_2 VAV_BOT WITH REHEAT 4.51 10.87 554.22 201.98 0.0000 0.087
PERIMETER_BOT_ZN_1 VAV_BOT WITH REHEAT 7.00 16.87 860.02 313.42 0.0000 0.135
PERIMETER_BOT_ZN_4 VAV_BOT WITH REHEAT 4.51 10.87 554.22 201.98 0.0000 0.087
PERIMETER_MID_ZN_3 VAV_MID WITH REHEAT 7.00 16.87 860.00 313.41 0.0000 1.353
PERIMETER_MID_ZN_2 VAV_MID WITH REHEAT 3.94 10.87 554.22 201.98 0.0000 0.872
PERIMETER_MID_ZN_1 VAV_MID WITH REHEAT 7.00 16.87 860.02 313.42 0.0000 1.353
PERIMETER_MID_ZN_4 VAV_MID WITH REHEAT 4.51 10.87 554.22 201.98 0.0000 0.872
PERIMETER_TOP_ZN_3 VAV_TOP WITH REHEAT 7.00 16.87 860.00 313.41 0.0000 0.135
PERIMETER_TOP_ZN_2 VAV_TOP WITH REHEAT 4.51 10.87 554.22 201.98 0.0000 0.087
PERIMETER_TOP_ZN_1 VAV_TOP WITH REHEAT 7.00 16.87 860.02 313.42 0.0000 0.135
PERIMETER_TOP_ZN_4 VAV_TOP WITH REHEAT 4.51 10.87 554.22 201.98 0.0000 0.087
DATACENTER_BOT_ZN_6 AIRLOOP DATACENTER BOT 0.81 1.95 99.34 36.20 0.0156 0.016
DATACENTER_MID_ZN_6 AIRLOOP DATACENTER MID 0.81 1.95 99.34 36.20 0.1563 0.156
DATACENTER_TOP_ZN_6 AIRLOOP DATACENTER TOP 0.81 1.95 99.34 36.20 0.0156 0.016
DATACENTER_BASEMENT_ZN_6 AIRLOOP DATACENTER BASEMENT 17.51 42.18 1911.37 783.68 0.3384 0.338
Total Facility   1029.47 2493.19 126016.35 46320.38 1.7261 158.471


Total Outdoor Air by Zone

Mechanical Ventilation [m3] Natural Ventilation [m3] Total Ventilation [m3] Infiltration [m3] Total Ventilation and Infiltration [m3] Dynamic Target Ventilation - Voz-dyn [m3] Time Below Voz-dyn [hr] Time At Voz-dyn [hr] Time Above Voz-dyn [hr] Time Above Zero When Unoccupied [hr]
BASEMENT 55487713.01 0.00 55487713.01 0.00 55487713.01 37848132.68 3997.50 918.33 3844.17 284.46
CORE_BOTTOM 45689088.52 0.00 45689088.52 0.00 45689088.52 33990283.35 3676.08 9.78 5074.14 426.63
CORE_MID 0.36E+09 0.00 0.36E+09 0.00 0.36E+09 0.34E+09 4044.53 7.11 4708.36 409.76
CORE_TOP 35338038.16 0.00 35338038.16 0.00 35338038.16 33990283.35 4073.46 2.71 4683.83 475.49
PERIMETER_BOT_ZN_3 5422546.99 0.00 5422546.99 584665.50 6007212.49 4267819.30 4196.83 66.79 4496.38 426.63
PERIMETER_BOT_ZN_2 5670470.72 0.00 5670470.72 389776.73 6060247.45 2750345.05 3552.68 5.10 5202.22 426.63
PERIMETER_BOT_ZN_1 7965179.84 0.00 7965179.84 584665.50 8549845.33 4267912.63 3642.36 5.28 5112.36 426.63
PERIMETER_BOT_ZN_4 7520132.60 0.00 7520132.60 389776.73 7909909.33 2750345.05 3515.23 5.04 5239.73 426.63
PERIMETER_MID_ZN_3 46716919.11 0.00 46716919.11 1371204.53 48088123.65 42678193.03 4055.68 13.20 4691.12 409.76
PERIMETER_MID_ZN_2 57143379.79 0.00 57143379.79 914135.73 58057515.52 27503450.52 3888.04 6.12 4865.84 1318.76
PERIMETER_MID_ZN_1 75249086.55 0.00 75249086.55 1371204.53 76620291.08 42679126.28 3972.14 5.22 4782.64 409.76
PERIMETER_MID_ZN_4 59118565.25 0.00 59118565.25 914135.73 60032700.98 27503450.52 3876.12 4.85 4879.03 409.76
PERIMETER_TOP_ZN_3 4816110.64 0.00 4816110.64 1702496.76 6518607.40 4267819.30 4051.97 2.97 4705.05 475.49
PERIMETER_TOP_ZN_2 5726902.35 0.00 5726902.35 1134997.06 6861899.42 2750345.05 3968.42 4.17 4787.42 475.49
PERIMETER_TOP_ZN_1 7659722.55 0.00 7659722.55 1702496.76 9362219.30 4267912.63 4005.49 1.43 4753.08 475.49
PERIMETER_TOP_ZN_4 6105687.49 0.00 6105687.49 1134997.06 7240684.55 2750345.05 3954.14 4.56 4801.30 475.49
DATACENTER_BOT_ZN_6 244296.02 0.00 244296.02 0.00 244296.02 492981.60 4419.00 4341.00 0.00 0.00
DATACENTER_MID_ZN_6 2442960.18 0.00 2442960.18 0.00 2442960.18 4929815.99 4419.00 4341.00 0.00 0.00
DATACENTER_TOP_ZN_6 244296.02 0.00 244296.02 0.00 244296.02 492981.60 4419.00 4341.00 0.00 0.00
DATACENTER_BASEMENT_ZN_6 0.41E+09 0.00 0.41E+09 0.00 0.41E+09 10671554.30 11.97 76.83 8671.19 2816.00
Total Facility 0.66E+10 0.00 0.66E+10 53330677.35 0.67E+10 0.50E+10 4964.31 4395.38 8750.33 3725.25


Average Outdoor Air During Occupancy by Zone - Flow Rates

Mechanical Ventilation [m3/s] Natural Ventilation [m3/s] Total Ventilation [m3/s] Infiltration [m3/s] Total Ventilation and Infiltration [m3/s] Dynamic Target Ventilation - Voz-dyn [m3/s] Time Below Voz-dyn [hr] Time At Voz-dyn [hr] Time Above Voz-dyn [hr]
BASEMENT 2.4901 0.0000 2.4901 0.0000 2.4901 1.2002 1340.97 915.88 3686.15
CORE_BOTTOM 2.0119 0.0000 2.0119 0.0000 2.0119 1.0778 1198.23 7.08 4737.69
CORE_MID 16.3153 0.0000 16.3153 0.0000 16.3153 10.7782 1341.74 6.68 4594.58
CORE_TOP 1.6081 0.0000 1.6081 0.0000 1.6081 1.0778 1349.27 2.54 4591.18
PERIMETER_BOT_ZN_3 0.2389 0.0000 0.2389 0.0139 0.2528 0.1353 1716.39 63.70 4162.91
PERIMETER_BOT_ZN_2 0.2488 0.0000 0.2488 0.0092 0.2580 0.0872 1118.38 3.27 4821.35
PERIMETER_BOT_ZN_1 0.3534 0.0000 0.3534 0.0139 0.3673 0.1353 1187.34 3.88 4751.79
PERIMETER_BOT_ZN_4 0.3296 0.0000 0.3296 0.0092 0.3388 0.0872 1089.69 3.64 4849.67
PERIMETER_MID_ZN_3 2.1123 0.0000 2.1123 0.0325 2.1448 1.3533 1358.76 12.25 4571.99
PERIMETER_MID_ZN_2 2.3884 0.0000 2.3884 0.0230 2.4113 0.8721 1229.63 3.57 3800.81
PERIMETER_MID_ZN_1 3.4256 0.0000 3.4256 0.0325 3.4581 1.3533 1283.95 3.34 4655.71
PERIMETER_MID_ZN_4 2.6653 0.0000 2.6653 0.0217 2.6869 0.8721 1223.13 2.40 4717.47
PERIMETER_TOP_ZN_3 0.2193 0.0000 0.2193 0.0404 0.2596 0.1353 1332.48 2.43 4608.09
PERIMETER_TOP_ZN_2 0.2611 0.0000 0.2611 0.0269 0.2880 0.0872 1270.62 2.81 4669.57
PERIMETER_TOP_ZN_1 0.3503 0.0000 0.3503 0.0404 0.3906 0.1353 1296.08 0.77 4646.15
PERIMETER_TOP_ZN_4 0.2769 0.0000 0.2769 0.0269 0.3038 0.0872 1259.87 3.48 4679.64
DATACENTER_BOT_ZN_6 0.0114 0.0000 0.0114 0.0000 0.0114 0.0156 1602.00 4341.00 0.00
DATACENTER_MID_ZN_6 0.1142 0.0000 0.1142 0.0000 0.1142 0.1563 1602.00 4341.00 0.00
DATACENTER_TOP_ZN_6 0.0114 0.0000 0.0114 0.0000 0.0114 0.0156 1602.00 4341.00 0.00
DATACENTER_BASEMENT_ZN_6 13.3228 0.0000 13.3228 0.0000 13.3228 0.3384 10.97 76.83 5855.19
Total Facility 291.9432 0.0000 291.9432 1.2780 293.2213 158.4706 2147.31 4374.67 5934.08


Total Outdoor Air by AirLoop

Mechanical Ventilation [m3] Natural Ventilation [m3/s] Total Ventilation [m3/s] Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] Time Below Voz-sum-dyn [hr] Time At Voz-sum-dyn [hr] Time Above Voz-sum-dyn [hr] Time Above Zero When Unoccupied [hr]
VAV_BOT WITH REHEAT 99614114.73 0.00 99614114.73 48026705.38 3563.01 5.25 5191.74 426.63
VAV_MID WITH REHEAT 0.83E+09 0.00 0.83E+09 0.48E+09 3933.93 5.52 4820.55 409.76
VAV_TOP WITH REHEAT 82198767.30 0.00 82198767.30 48026705.38 3998.51 1.53 4759.96 475.27
CAV_BAS 76467652.91 0.00 76467652.91 37848132.68 3929.48 4.67 4825.85 284.44
AIRLOOP DATACENTER BASEMENT 0.57E+09 0.00 0.57E+09 10671554.30 11.97 0.00 8748.03 2816.00
AIRLOOP DATACENTER BOT 336664.50 0.00 336664.50 492981.60 4419.00 0.00 4341.00 0.00
AIRLOOP DATACENTER MID 3366645.00 0.00 3366645.00 4929815.99 4419.00 0.00 4341.00 0.00
AIRLOOP DATACENTER TOP 336664.50 0.00 336664.50 492981.60 4419.00 0.00 4341.00 0.00


Average Outdoor Air During Occupancy by AirLoop

Mechanical Ventilation [m3/s] Natural Ventilation [m3/s] Total Ventilation [m3/s] Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] Time Below Voz-sum-dyn [hr] Time At Voz-sum-dyn [hr] Time Above Voz-sum-dyn [hr]
VAV_BOT WITH REHEAT 4.3870 0.0000 4.3870 1.5229 1119.44 4.24 4819.31
VAV_MID WITH REHEAT 37.3569 0.0000 37.3569 15.2292 1254.40 3.68 4684.91
VAV_TOP WITH REHEAT 3.7423 0.0000 3.7423 1.5229 1289.56 0.79 4652.65
CAV_BAS 3.4316 0.0000 3.4316 1.2002 1308.17 1.95 4632.89
AIRLOOP DATACENTER BASEMENT 18.3602 0.0000 18.3602 0.3384 10.97 0.00 5932.03
AIRLOOP DATACENTER BOT 0.0157 0.0000 0.0157 0.0156 1602.00 0.00 4341.00
AIRLOOP DATACENTER MID 0.1574 0.0000 0.1574 0.1563 1602.00 0.00 4341.00
AIRLOOP DATACENTER TOP 0.0157 0.0000 0.0157 0.0156 1602.00 0.00 4341.00


Outdoor Air Controller Limiting Factors by AirLoop

No Limiting Factor [hr] Limits and Scheduled Limits [hr] Economizer [hr] Exhaust Flow [hr] Mixed Air Flow [hr] High Humidity [hr] Demand Controlled Ventilation [hr] Night Ventilation [hr] Demand Limiting [hr] Energy Management System [hr]
VAV_BOT WITH REHEAT 0.00 2039.97 3276.57 0.00 0.00 0.00 0.00 0.00 0.00 0.00
VAV_MID WITH REHEAT 0.00 2410.47 2839.76 0.00 0.00 0.00 0.00 0.00 0.00 0.00
VAV_TOP WITH REHEAT 0.00 2562.85 2813.33 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CAV_BAS 0.00 905.47 4042.17 0.00 0.00 0.00 0.00 0.00 0.00 0.00
AIRLOOP DATACENTER BASEMENT 0.00 76.83 8671.19 0.00 0.00 0.00 0.00 0.00 0.00 0.00
AIRLOOP DATACENTER BOT 0.00 4341.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
AIRLOOP DATACENTER MID 0.00 4341.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
AIRLOOP DATACENTER TOP 0.00 4341.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Average Outdoor Air for Limiting Factors During Occupancy

No Limiting Factor [m3/s] Limits and Scheduled Limits [m3/s] Economizer [m3/s] Exhaust Flow [m3/s] Mixed Air Flow [m3/s] High Humidity [m3/s] Demand Controlled Ventilation [m3/s] Night Ventilation [m3/s] Demand Limiting [m3/s] Energy Management System [m3/s]
VAV_BOT WITH REHEAT 0.0000 3.4999 6.6464 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
VAV_MID WITH REHEAT 0.0000 34.9857 56.6653 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
VAV_TOP WITH REHEAT 0.0000 3.4990 5.6784 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
CAV_BAS 0.0000 1.6548 5.0296 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
AIRLOOP DATACENTER BASEMENT 0.0000 0.4715 18.6300 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
AIRLOOP DATACENTER BOT 0.0000 0.0215 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
AIRLOOP DATACENTER MID 0.0000 0.2155 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
AIRLOOP DATACENTER TOP 0.0000 0.0215 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000



Table of Contents

Report: Object Count Summary

For: Entire Facility

Timestamp: 2023-10-16 08:43:24

Surfaces by Class

Total Outdoors
Wall 98 30
Floor 41 0
Roof 30 1
Internal Mass 16 0
Building Detached Shading 0 0
Fixed Detached Shading 0 0
Window 24 24
Door 12 12
Glass Door 0 0
Shading 0 0
Overhang 0 0
Fin 0 0
Tubular Daylighting Device Dome 0 0
Tubular Daylighting Device Diffuser 0 0


HVAC

Count
HVAC Air Loops 8
Conditioned Zones 23
Unconditioned Zones 0
Supply Plenums 0
Return Plenums 3


Input Fields

Count
IDF Objects 1401
Defaulted Fields 1182
Fields with Defaults 3927
Autosized Fields 338
Autosizable Fields 414
Autocalculated Fields 226
Autocalculatable Fields 473



Table of Contents

Report: Energy Meters

For: Entire Facility

Timestamp: 2023-10-16 08:43:24

Annual and Peak Values - Electricity

Electricity Annual Value [GJ] Electricity Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Electricity Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
Electricity:Facility 27840.15 329422.36 21-MAY-05:00 2110357.97 15-AUG-14:40
Electricity:Building 18605.35 225715.65 07-MAY-17:10 1164206.62 01-DEC-16:20
Electricity:Zone:BASEMENT 687.24 14732.47 01-JAN-00:10 36407.88 02-JAN-08:10
Electricity:SpaceType:GENERAL 18605.35 225715.65 07-MAY-17:10 1164206.62 01-DEC-16:20
InteriorLights:Electricity 3928.95 18459.50 01-JAN-11:00 385834.94 02-JAN-16:50
InteriorLights:Electricity:Zone:BASEMENT 262.84 1274.92 01-JAN-00:10 22950.34 02-JAN-08:10
InteriorLights:Electricity:SpaceType:GENERAL 3928.95 18459.50 01-JAN-11:00 385834.94 02-JAN-16:50
LightsWired:InteriorLights:Electricity 3928.95 18459.50 01-JAN-11:00 385834.94 02-JAN-16:50
LightsWired:InteriorLights:Electricity:Zone:BASEMENT 262.84 1274.92 01-JAN-00:10 22950.34 02-JAN-08:10
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL 3928.95 18459.50 01-JAN-11:00 385834.94 02-JAN-16:50
Electricity:Zone:CORE_BOTTOM 525.67 5598.20 01-JAN-00:10 37817.64 02-JAN-08:10
InteriorLights:Electricity:Zone:CORE_BOTTOM 236.05 1144.97 01-JAN-00:10 20611.01 02-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:CORE_BOTTOM 236.05 1144.97 01-JAN-00:10 20611.01 02-JAN-08:10
Electricity:Zone:CORE_MID 5256.66 55981.88 01-JAN-00:10 378175.77 02-JAN-08:10
InteriorLights:Electricity:Zone:CORE_MID 2360.53 11449.71 01-JAN-00:10 206110.14 02-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:CORE_MID 2360.53 11449.71 01-JAN-00:10 206110.14 02-JAN-08:10
Electricity:Zone:CORE_TOP 525.67 5598.19 01-JAN-00:10 37817.58 02-JAN-08:10
InteriorLights:Electricity:Zone:CORE_TOP 236.05 1144.97 01-JAN-00:10 20611.01 02-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:CORE_TOP 236.05 1144.97 01-JAN-00:10 20611.01 02-JAN-08:10
Electricity:Zone:PERIMETER_BOT_ZN_3 53.75 627.57 26-MAR-17:10 4748.47 02-JAN-16:40
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 17.39 68.40 01-JAN-11:00 2587.92 02-JAN-16:40
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 17.39 68.40 01-JAN-11:00 2587.92 02-JAN-16:40
Electricity:Zone:PERIMETER_BOT_ZN_2 34.55 404.43 26-MAR-17:10 3060.10 02-JAN-16:40
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 11.12 44.08 01-JAN-09:20 1667.75 02-JAN-16:40
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 11.12 44.08 01-JAN-09:20 1667.75 02-JAN-16:40
Electricity:Zone:PERIMETER_BOT_ZN_1 53.49 627.58 12-MAR-17:10 4748.56 02-JAN-16:50
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 17.12 68.40 01-JAN-09:20 2587.98 02-JAN-16:50
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 17.12 68.40 01-JAN-09:20 2587.98 02-JAN-16:50
Electricity:Zone:PERIMETER_BOT_ZN_4 34.54 404.43 12-MAR-17:10 3060.09 02-JAN-16:50
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 11.11 44.08 01-JAN-10:20 1667.75 02-JAN-16:50
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 11.11 44.08 01-JAN-10:20 1667.75 02-JAN-16:50
Electricity:Zone:PERIMETER_MID_ZN_3 537.18 6275.73 12-MAR-17:10 47484.70 02-JAN-16:40
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 173.52 684.02 01-JAN-10:40 25879.19 02-JAN-16:40
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 173.52 684.02 01-JAN-10:40 25879.19 02-JAN-16:40
Electricity:Zone:PERIMETER_MID_ZN_2 345.34 4044.32 26-MAR-17:10 30600.95 02-JAN-16:40
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 110.99 440.81 01-JAN-09:10 16677.53 02-JAN-16:40
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 110.99 440.81 01-JAN-09:10 16677.53 02-JAN-16:40
Electricity:Zone:PERIMETER_MID_ZN_1 534.72 6275.83 12-MAR-17:10 47485.60 02-JAN-16:50
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 171.06 684.04 01-JAN-09:10 25879.75 02-JAN-16:50
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 171.06 684.04 01-JAN-09:10 25879.75 02-JAN-16:50
Electricity:Zone:PERIMETER_MID_ZN_4 345.23 4044.30 12-MAR-17:10 30600.86 02-JAN-16:50
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 110.88 440.81 01-JAN-10:10 16677.53 02-JAN-16:50
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 110.88 440.81 01-JAN-10:10 16677.53 02-JAN-16:50
Electricity:Zone:PERIMETER_TOP_ZN_3 53.71 627.57 12-MAR-17:10 4748.47 02-JAN-16:40
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 17.35 68.40 01-JAN-10:40 2587.92 02-JAN-16:40
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 17.35 68.40 01-JAN-10:40 2587.92 02-JAN-16:40
Electricity:Zone:PERIMETER_TOP_ZN_2 34.53 404.43 26-MAR-17:10 3060.10 02-JAN-16:40
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 11.10 44.08 01-JAN-09:10 1667.75 02-JAN-16:40
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 11.10 44.08 01-JAN-09:10 1667.75 02-JAN-16:40
Electricity:Zone:PERIMETER_TOP_ZN_1 53.47 627.58 12-MAR-17:10 4748.56 02-JAN-16:50
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 17.10 68.40 01-JAN-09:10 2587.98 02-JAN-16:50
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 17.10 68.40 01-JAN-09:10 2587.98 02-JAN-16:50
Electricity:Zone:PERIMETER_TOP_ZN_4 34.52 404.43 12-MAR-17:10 3060.09 02-JAN-16:50
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 11.09 44.08 01-JAN-10:10 1667.75 02-JAN-16:50
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 11.09 44.08 01-JAN-10:10 1667.75 02-JAN-16:50
Electricity:Zone:DATACENTER_BASEMENT_ZN_6 7568.97 95267.60 01-JAN-00:10 386103.53 03-APR-07:10
InteriorLights:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 74.11 359.47 01-JAN-00:10 6471.01 02-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 74.11 359.47 01-JAN-00:10 6471.01 02-JAN-08:10
Electricity:Zone:DATACENTER_BOT_ZN_6 160.51 1980.76 01-JAN-00:10 8373.14 03-APR-07:10
InteriorLights:Electricity:Zone:DATACENTER_BOT_ZN_6 6.63 32.15 01-JAN-00:10 578.72 02-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_BOT_ZN_6 6.63 32.15 01-JAN-00:10 578.72 02-JAN-08:10
Electricity:Zone:DATACENTER_MID_ZN_6 1605.09 19807.58 01-JAN-00:10 83731.41 03-APR-07:10
InteriorLights:Electricity:Zone:DATACENTER_MID_ZN_6 66.28 321.53 01-JAN-00:10 5787.18 02-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_MID_ZN_6 66.28 321.53 01-JAN-00:10 5787.18 02-JAN-08:10
Electricity:Zone:DATACENTER_TOP_ZN_6 160.51 1980.76 01-JAN-00:10 8373.14 03-APR-07:10
InteriorLights:Electricity:Zone:DATACENTER_TOP_ZN_6 6.63 32.15 01-JAN-00:10 578.72 02-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_TOP_ZN_6 6.63 32.15 01-JAN-00:10 578.72 02-JAN-08:10
InteriorEquipment:Electricity 14676.40 207256.16 01-JAN-00:10 778371.69 03-APR-07:10
InteriorEquipment:Electricity:Zone:BASEMENT 424.40 13457.54 01-JAN-00:10 13457.54 01-JAN-00:10
InteriorEquipment:Electricity:SpaceType:GENERAL 14676.40 207256.16 01-JAN-00:10 778371.69 03-APR-07:10
MiscPlug:InteriorEquipment:Electricity 5334.97 88964.76 01-JAN-00:10 305206.10 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:BASEMENT 424.40 13457.54 01-JAN-00:10 13457.54 01-JAN-00:10
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL 5334.97 88964.76 01-JAN-00:10 305206.10 02-JAN-08:10
InteriorEquipment:Electricity:Zone:CORE_BOTTOM 289.61 4453.23 01-JAN-00:10 17206.63 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_BOTTOM 289.61 4453.23 01-JAN-00:10 17206.63 02-JAN-08:10
InteriorEquipment:Electricity:Zone:CORE_MID 2896.13 44532.17 01-JAN-00:10 172065.63 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_MID 2896.13 44532.17 01-JAN-00:10 172065.63 02-JAN-08:10
InteriorEquipment:Electricity:Zone:CORE_TOP 289.61 4453.22 01-JAN-00:10 17206.56 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_TOP 289.61 4453.22 01-JAN-00:10 17206.56 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 36.37 559.17 01-JAN-00:10 2160.55 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 36.37 559.17 01-JAN-00:10 2160.55 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 23.44 360.35 01-JAN-00:10 1392.34 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 23.44 360.35 01-JAN-00:10 1392.34 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 36.37 559.18 01-JAN-00:10 2160.58 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 36.37 559.18 01-JAN-00:10 2160.58 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 23.44 360.35 01-JAN-00:10 1392.33 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 23.44 360.35 01-JAN-00:10 1392.33 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 363.65 5591.71 01-JAN-00:10 21605.52 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 363.65 5591.71 01-JAN-00:10 21605.52 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 234.35 3603.51 01-JAN-00:10 13923.42 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 234.35 3603.51 01-JAN-00:10 13923.42 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 363.66 5591.79 01-JAN-00:10 21605.85 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 363.66 5591.79 01-JAN-00:10 21605.85 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 234.35 3603.49 01-JAN-00:10 13923.33 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 234.35 3603.49 01-JAN-00:10 13923.33 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 36.37 559.17 01-JAN-00:10 2160.55 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 36.37 559.17 01-JAN-00:10 2160.55 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 23.44 360.35 01-JAN-00:10 1392.34 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 23.44 360.35 01-JAN-00:10 1392.34 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 36.37 559.18 01-JAN-00:10 2160.58 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 36.37 559.18 01-JAN-00:10 2160.58 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 23.44 360.35 01-JAN-00:10 1392.33 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 23.44 360.35 01-JAN-00:10 1392.33 02-JAN-08:10
InteriorEquipment:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 7494.86 94908.13 01-JAN-00:10 379632.52 31-MAR-23:10
DataCenterPlugLoads:InteriorEquipment:Electricity 9341.42 118291.40 01-JAN-00:10 473165.59 31-MAR-23:10
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 7494.86 94908.13 01-JAN-00:10 379632.52 31-MAR-23:10
DataCenterPlugLoads:InteriorEquipment:Electricity:SpaceType:GENERAL 9341.42 118291.40 01-JAN-00:10 473165.59 31-MAR-23:10
InteriorEquipment:Electricity:Zone:DATACENTER_BOT_ZN_6 153.88 1948.61 01-JAN-00:10 7794.42 31-MAR-23:10
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_BOT_ZN_6 153.88 1948.61 01-JAN-00:10 7794.42 31-MAR-23:10
InteriorEquipment:Electricity:Zone:DATACENTER_MID_ZN_6 1538.81 19486.06 01-JAN-00:10 77944.22 31-MAR-23:10
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_MID_ZN_6 1538.81 19486.06 01-JAN-00:10 77944.22 31-MAR-23:10
InteriorEquipment:Electricity:Zone:DATACENTER_TOP_ZN_6 153.88 1948.61 01-JAN-00:10 7794.42 31-MAR-23:10
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_TOP_ZN_6 153.88 1948.61 01-JAN-00:10 7794.42 31-MAR-23:10
Electricity:Plant 1712.61 3561.33 31-JAN-01:50 575290.89 15-AUG-14:40
HeatRejection:Electricity 596.57 107.43 06-JAN-08:00 90257.03 10-MAY-13:40
General:HeatRejection:Electricity 596.57 107.43 06-JAN-08:00 90257.03 10-MAY-13:40
Electricity:HVAC 4970.85 49419.30 30-SEP-23:00 526090.66 17-AUG-15:00
ExteriorEquipment:Electricity 1934.79 28603.11 01-JAN-00:10 118535.44 01-NOV-07:20
Transformer:ExteriorEquipment:Electricity 80.18 1421.04 01-JAN-00:10 5057.48 01-DEC-16:30
ElectricityPurchased:Facility 27840.15 329422.36 21-MAY-05:00 2110357.97 15-AUG-14:40
ElectricityPurchased:Plant 27840.15 329422.36 21-MAY-05:00 2110357.97 15-AUG-14:40
Cogeneration:ElectricityPurchased 27840.15 329422.36 21-MAY-05:00 2110357.97 15-AUG-14:40
General:Cogeneration:ElectricityPurchased 27840.15 329422.36 21-MAY-05:00 2110357.97 15-AUG-14:40
ElectricitySurplusSold:Facility 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
ElectricitySurplusSold:Plant 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cogeneration:ElectricitySurplusSold 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Cogeneration:ElectricitySurplusSold 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
ElectricityNet:Facility 27840.15 329422.36 21-MAY-05:00 2110357.97 15-AUG-14:40
ElectricityNet:Plant 27840.15 329422.36 21-MAY-05:00 2110357.97 15-AUG-14:40
Cogeneration:ElectricityNet 27840.15 329422.36 21-MAY-05:00 2110357.97 15-AUG-14:40
General:Cogeneration:ElectricityNet 27840.15 329422.36 21-MAY-05:00 2110357.97 15-AUG-14:40
Fans:Electricity 2402.24 42822.76 02-JAN-04:40 292128.76 09-AUG-15:20
General:Fans:Electricity 2402.24 42822.76 02-JAN-04:40 292128.76 09-AUG-15:20
ExteriorLights:Electricity 696.73 0.00 01-JAN-08:00 57580.60 01-JAN-06:10
General:ExteriorLights:Electricity 696.73 0.00 01-JAN-08:00 57580.60 01-JAN-06:10
ElevatorLift:ExteriorEquipment:Electricity 1848.78 27144.47 01-JAN-00:10 113101.96 01-JAN-07:10
ElevatorLightsFan:ExteriorEquipment:Electricity 5.83 37.60 01-JAN-00:10 376.00 01-JAN-07:10
HeatRecovery:Electricity 47.24 0.00 01-JAN-00:10 5613.48 02-JAN-07:10
General:HeatRecovery:Electricity 47.24 0.00 01-JAN-00:10 5613.48 02-JAN-07:10
Cooling:Electricity 1733.72 1595.93 14-JAN-17:50 583018.50 15-AUG-14:40
General:Cooling:Electricity 1733.72 1595.93 14-JAN-17:50 583018.50 15-AUG-14:40
Heating:Electricity 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:Electricity 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Humidifier:Electricity 1449.29 0.00 11-JAN-13:10 100000.00 14-FEB-16:00
General:Humidifier:Electricity 1449.29 0.00 11-JAN-13:10 100000.00 14-FEB-16:00
Boiler Parasitic:Heating:Electricity 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Pumps:Electricity 374.21 3444.52 06-FEB-01:00 59285.61 15-AUG-14:30
General:Pumps:Electricity 374.21 3444.52 06-FEB-01:00 59285.61 15-AUG-14:30
WIRED_LTG_ELECTRICITY 110.40 0.00 01-JAN-00:10 10841.96 02-JAN-17:00
WIRED_INT_EQUIP 5334.97 88964.76 31-MAR-23:10 305206.10 03-APR-07:10


Annual and Peak Values - Natural Gas

Natural Gas Annual Value [GJ] Natural Gas Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Natural Gas Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
NaturalGas:Facility 2944.41 8146.58 06-FEB-01:00 2192673.77 26-DEC-07:10
NaturalGas:Plant 2944.41 8146.58 06-FEB-01:00 2192673.77 26-DEC-07:10
Heating:NaturalGas 2119.03 0.00 01-JAN-00:40 2175214.88 26-DEC-07:10
Boiler:Heating:NaturalGas 2119.03 0.00 01-JAN-00:40 2175214.88 26-DEC-07:10
WaterSystems:NaturalGas 825.38 8146.58 02-JAN-06:00 86742.10 06-FEB-12:50
Water Heater:WaterSystems:NaturalGas 825.38 8146.58 02-JAN-06:00 86742.10 06-FEB-12:50


Annual and Peak Values - Cooling

Cooling Annual Value [GJ] Cooling Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Cooling Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
PlantLoopCoolingDemand:Facility 9307.30 3991.87 14-JAN-17:50 3587731.97 15-AUG-14:30
PlantLoopCoolingDemand:HVAC 9307.30 3991.87 14-JAN-17:50 3587731.97 15-AUG-14:30
CoolingCoils:PlantLoopCoolingDemand 9307.30 3991.87 14-JAN-17:50 3587731.97 15-AUG-14:30


Annual and Peak Values - Water

Annual Value [m3] Minimum Value [m3/s] Timestamp of Minimum {TIMESTAMP} Maximum Value [m3/s] Timestamp of Maximum {TIMESTAMP}
Water:Facility 6521.30 0.00 11-MAR-01:00 0.00 17-AUG-13:00
Water:HVAC 539.14 0.00 11-JAN-13:10 0.00 22-FEB-05:20
Humidifier:Water 539.14 0.00 11-JAN-13:10 0.00 22-FEB-05:20
General:Humidifier:Water 539.14 0.00 11-JAN-13:10 0.00 22-FEB-05:20
MainsWater:Facility 6521.30 0.00 11-MAR-01:00 0.00 17-AUG-13:00
MainsWater:HVAC 539.14 0.00 11-JAN-13:10 0.00 22-FEB-05:20
Humidifier:MainsWater 539.14 0.00 11-JAN-13:10 0.00 22-FEB-05:20
General:Humidifier:MainsWater 539.14 0.00 11-JAN-13:10 0.00 22-FEB-05:20
Water:Plant 5982.16 0.00 01-JAN-00:10 0.00 17-AUG-13:00
WaterSystems:Water 2280.17 0.00 01-JAN-00:10 0.00 02-JAN-12:10
WaterUse:WaterSystems:Water 2280.17 0.00 01-JAN-00:10 0.00 02-JAN-12:10
MainsWater:Plant 5982.16 0.00 01-JAN-00:10 0.00 17-AUG-13:00
WaterSystems:MainsWater 2280.17 0.00 01-JAN-00:10 0.00 02-JAN-12:10
WaterUse:WaterSystems:MainsWater 2280.17 0.00 01-JAN-00:10 0.00 02-JAN-12:10
Water Heater:WaterSystems:Water 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Water Heater:WaterSystems:MainsWater 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
HeatRejection:Water 3701.99 0.00 01-JAN-00:10 0.00 04-AUG-13:10
General:HeatRejection:Water 3701.99 0.00 01-JAN-00:10 0.00 04-AUG-13:10
HeatRejection:MainsWater 3701.99 0.00 01-JAN-00:10 0.00 04-AUG-13:10
General:HeatRejection:MainsWater 3701.99 0.00 01-JAN-00:10 0.00 04-AUG-13:10


Annual and Peak Values - Other by Weight/Mass

Annual Value [kg] Minimum Value [kg/s] Timestamp of Minimum {TIMESTAMP} Maximum Value [kg/s] Timestamp of Maximum {TIMESTAMP}
Carbon Equivalent:Facility 0.00 0.000 01-JAN-00:10 0.000 01-JAN-00:10
CarbonEquivalentEmissions:Carbon Equivalent 0.00 0.000 01-JAN-00:10 0.000 01-JAN-00:10


Annual and Peak Values - Other Volumetric

Annual Value [m3] Minimum Value [m3/s] Timestamp of Minimum {TIMESTAMP} Maximum Value [m3/s] Timestamp of Maximum {TIMESTAMP}
None          


Annual and Peak Values - Other Liquid/Gas

Annual Value [L] Minimum Value [L] Timestamp of Minimum {TIMESTAMP} Maximum Value [L] Timestamp of Maximum {TIMESTAMP}
None          


Annual and Peak Values - Other

Annual Value [GJ] Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
EnergyTransfer:Facility 49787.57 94181.42 30-JAN-03:40 13907533.52 15-AUG-14:30
EnergyTransfer:Building 18952.76 88794.43 26-JAN-22:30 1747665.79 09-AUG-15:20
EnergyTransfer:Zone:BASEMENT 687.10 0.00 01-JAN-00:10 70987.93 05-SEP-05:10
Heating:EnergyTransfer 1058.75 0.00 01-FEB-00:20 1328052.95 02-JAN-05:10
Heating:EnergyTransfer:Zone:BASEMENT 2.22 0.00 01-JAN-00:10 13574.47 17-JUN-16:10
General:Heating:EnergyTransfer 1058.75 0.00 01-FEB-00:20 1328052.95 02-JAN-05:10
General:Heating:EnergyTransfer:Zone:BASEMENT 2.22 0.00 01-JAN-00:10 13574.47 17-JUN-16:10
Cooling:EnergyTransfer 17894.02 84947.11 30-JAN-06:00 1747665.79 09-AUG-15:20
Cooling:EnergyTransfer:Zone:BASEMENT 684.88 0.00 01-JAN-00:10 70987.93 05-SEP-05:10
General:Cooling:EnergyTransfer 17894.02 84947.11 30-JAN-06:00 1747665.79 09-AUG-15:20
General:Cooling:EnergyTransfer:Zone:BASEMENT 684.88 0.00 01-JAN-00:10 70987.93 05-SEP-05:10
EnergyTransfer:Zone:CORE_BOTTOM 615.97 0.00 01-JAN-00:10 56749.68 14-AUG-13:10
Heating:EnergyTransfer:Zone:CORE_BOTTOM 0.00 0.00 01-JAN-00:10 213.28 28-FEB-10:10
General:Heating:EnergyTransfer:Zone:CORE_BOTTOM 0.00 0.00 01-JAN-00:10 213.28 28-FEB-10:10
Cooling:EnergyTransfer:Zone:CORE_BOTTOM 615.97 0.00 01-JAN-00:10 56749.68 14-AUG-13:10
General:Cooling:EnergyTransfer:Zone:CORE_BOTTOM 615.97 0.00 01-JAN-00:10 56749.68 14-AUG-13:10
EnergyTransfer:Zone:CORE_MID 4374.71 0.00 01-JAN-00:40 484785.24 02-JAN-05:10
Heating:EnergyTransfer:Zone:CORE_MID 15.22 0.00 01-JAN-00:10 484785.24 02-JAN-05:10
General:Heating:EnergyTransfer:Zone:CORE_MID 15.22 0.00 01-JAN-00:10 484785.24 02-JAN-05:10
Cooling:EnergyTransfer:Zone:CORE_MID 4359.49 0.00 01-JAN-00:40 480076.32 24-MAR-11:40
General:Cooling:EnergyTransfer:Zone:CORE_MID 4359.49 0.00 01-JAN-00:40 480076.32 24-MAR-11:40
EnergyTransfer:Zone:CORE_TOP 405.98 0.00 01-JAN-00:40 74828.27 06-FEB-05:10
Heating:EnergyTransfer:Zone:CORE_TOP 17.77 0.00 01-JAN-00:40 74828.27 06-FEB-05:10
General:Heating:EnergyTransfer:Zone:CORE_TOP 17.77 0.00 01-JAN-00:40 74828.27 06-FEB-05:10
Cooling:EnergyTransfer:Zone:CORE_TOP 388.21 0.00 01-JAN-00:20 52480.84 21-JUL-14:00
General:Cooling:EnergyTransfer:Zone:CORE_TOP 388.21 0.00 01-JAN-00:20 52480.84 21-JUL-14:00
EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 66.48 0.00 01-JAN-00:10 11383.85 14-AUG-12:30
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 2.07 0.00 01-JAN-00:10 9841.69 06-FEB-05:10
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 2.07 0.00 01-JAN-00:10 9841.69 06-FEB-05:10
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 64.41 0.00 01-JAN-00:10 11383.85 14-AUG-12:30
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 64.41 0.00 01-JAN-00:10 11383.85 14-AUG-12:30
EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 65.38 0.00 01-JAN-00:10 15465.49 13-JUL-08:30
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 1.74 0.00 01-JAN-00:10 7180.65 07-FEB-06:10
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 1.74 0.00 01-JAN-00:10 7180.65 07-FEB-06:10
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 63.64 0.00 01-JAN-00:10 15465.49 13-JUL-08:30
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 63.64 0.00 01-JAN-00:10 15465.49 13-JUL-08:30
EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 101.06 0.00 01-JAN-00:10 22561.27 31-OCT-13:00
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 2.99 0.00 01-JAN-00:10 12385.03 06-FEB-05:10
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 2.99 0.00 01-JAN-00:10 12385.03 06-FEB-05:10
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 98.07 0.00 01-JAN-00:10 22561.27 31-OCT-13:00
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 98.07 0.00 01-JAN-00:10 22561.27 31-OCT-13:00
EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 95.73 0.00 01-JAN-00:10 19531.07 10-AUG-16:00
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 0.31 0.00 01-JAN-00:10 5432.83 06-FEB-05:10
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 0.31 0.00 01-JAN-00:10 5432.83 06-FEB-05:10
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 95.41 0.00 01-JAN-00:10 19531.07 10-AUG-16:00
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 95.41 0.00 01-JAN-00:10 19531.07 10-AUG-16:00
EnergyTransfer:Zone:PERIMETER_MID_ZN_3 656.16 0.00 01-JAN-00:40 144288.39 06-FEB-04:30
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 234.37 0.00 01-JAN-00:40 144288.39 06-FEB-04:30
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 234.37 0.00 01-JAN-00:40 144288.39 06-FEB-04:30
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 421.80 0.00 01-JAN-00:20 106373.01 21-JUL-13:30
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 421.80 0.00 01-JAN-00:20 106373.01 21-JUL-13:30
EnergyTransfer:Zone:PERIMETER_MID_ZN_2 651.25 0.00 01-JAN-00:40 167644.25 06-FEB-05:10
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 137.82 0.00 01-JAN-00:40 167644.25 06-FEB-05:10
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 137.82 0.00 01-JAN-00:40 167644.25 06-FEB-05:10
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 513.43 0.00 01-JAN-00:20 164309.09 13-JUL-08:30
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 513.43 0.00 01-JAN-00:20 164309.09 13-JUL-08:30
EnergyTransfer:Zone:PERIMETER_MID_ZN_1 963.21 0.00 01-JAN-00:40 234586.26 31-OCT-13:20
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 153.22 0.00 01-JAN-00:40 213961.52 06-FEB-05:10
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 153.22 0.00 01-JAN-00:40 213961.52 06-FEB-05:10
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 809.99 0.00 01-JAN-00:20 234586.26 31-OCT-13:20
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 809.99 0.00 01-JAN-00:20 234586.26 31-OCT-13:20
EnergyTransfer:Zone:PERIMETER_MID_ZN_4 668.10 0.00 01-JAN-00:40 171413.41 04-AUG-16:50
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 113.20 0.00 01-JAN-00:40 162784.64 06-FEB-05:10
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 113.20 0.00 01-JAN-00:40 162784.64 06-FEB-05:10
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 554.90 0.00 01-JAN-00:20 171413.41 04-AUG-16:50
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 554.90 0.00 01-JAN-00:20 171413.41 04-AUG-16:50
EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 84.70 0.00 01-JAN-00:40 17251.49 06-FEB-05:10
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 45.41 0.00 01-JAN-00:40 17251.49 06-FEB-05:10
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 45.41 0.00 01-JAN-00:40 17251.49 06-FEB-05:10
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 39.29 0.00 01-JAN-00:10 11630.59 21-JUL-13:30
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 39.29 0.00 01-JAN-00:10 11630.59 21-JUL-13:30
EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 75.14 0.00 01-JAN-00:40 19902.33 13-FEB-05:20
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 26.66 0.00 01-JAN-00:40 19902.33 13-FEB-05:20
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 26.66 0.00 01-JAN-00:40 19902.33 13-FEB-05:20
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 48.48 0.00 01-JAN-00:20 15947.91 13-JUL-08:30
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 48.48 0.00 01-JAN-00:20 15947.91 13-JUL-08:30
EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 107.91 0.00 01-JAN-00:40 24225.48 26-DEC-04:10
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 32.58 0.00 01-JAN-00:40 24225.48 26-DEC-04:10
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 32.58 0.00 01-JAN-00:40 24225.48 26-DEC-04:10
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 75.32 0.00 01-JAN-00:20 23876.85 31-OCT-13:30
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 75.32 0.00 01-JAN-00:20 23876.85 31-OCT-13:30
EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 74.87 0.00 01-JAN-00:40 20468.36 13-FEB-05:20
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 22.11 0.00 01-JAN-00:40 20468.36 13-FEB-05:20
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 22.11 0.00 01-JAN-00:40 20468.36 13-FEB-05:20
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 52.76 0.00 01-JAN-00:20 17942.04 02-JUL-17:00
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 52.76 0.00 01-JAN-00:20 17942.04 02-JUL-17:00
EnergyTransfer:Zone:GROUNDFLOOR_PLENUM 59.45 0.00 01-JAN-00:10 9755.68 14-AUG-14:40
Heating:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM 4.58 0.00 01-JAN-00:10 7766.96 28-FEB-10:10
General:Heating:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM 4.58 0.00 01-JAN-00:10 7766.96 28-FEB-10:10
Cooling:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM 54.88 0.00 01-JAN-00:10 9755.68 14-AUG-14:40
General:Cooling:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM 54.88 0.00 01-JAN-00:10 9755.68 14-AUG-14:40
EnergyTransfer:Zone:MIDFLOOR_PLENUM 527.17 0.00 01-JAN-00:40 174545.25 02-JAN-06:20
Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM 179.62 0.00 01-JAN-00:40 174545.25 02-JAN-06:20
General:Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM 179.62 0.00 01-JAN-00:40 174545.25 02-JAN-06:20
Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM 347.55 0.00 01-JAN-00:10 79761.45 21-JUL-12:10
General:Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM 347.55 0.00 01-JAN-00:10 79761.45 21-JUL-12:10
EnergyTransfer:Zone:TOPFLOOR_PLENUM 110.86 0.00 01-JAN-00:40 32455.96 06-FEB-05:20
Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM 59.54 0.00 01-JAN-00:40 32455.96 06-FEB-05:20
General:Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM 59.54 0.00 01-JAN-00:40 32455.96 06-FEB-05:20
Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM 51.32 0.00 01-JAN-00:10 19989.93 21-JUL-13:40
General:Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM 51.32 0.00 01-JAN-00:10 19989.93 21-JUL-13:40
EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 136.37 12.04 30-JAN-05:20 8409.16 02-AUG-18:40
Heating:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 136.37 12.04 30-JAN-05:20 8409.16 02-AUG-18:40
General:Cooling:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 136.37 12.04 30-JAN-05:20 8409.16 02-AUG-18:40
EnergyTransfer:Zone:DATACENTER_MID_ZN_6 1153.65 8.48 21-JAN-09:20 80774.48 02-AUG-18:40
Heating:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 6.36 0.00 02-JAN-17:00 5795.81 24-JAN-01:20
General:Heating:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 6.36 0.00 02-JAN-17:00 5795.81 24-JAN-01:20
Cooling:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 1147.30 0.00 01-JAN-00:10 80774.48 02-AUG-18:40
General:Cooling:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 1147.30 0.00 01-JAN-00:10 80774.48 02-AUG-18:40
EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 106.02 0.20 03-JAN-08:00 8129.31 02-AUG-18:40
Heating:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 0.95 0.00 02-JAN-14:40 614.45 09-JAN-23:30
General:Heating:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 0.95 0.00 02-JAN-14:40 614.45 09-JAN-23:30
Cooling:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 105.07 0.00 01-JAN-00:10 8129.31 02-AUG-18:40
General:Cooling:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 105.07 0.00 01-JAN-00:10 8129.31 02-AUG-18:40
EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 7165.49 84869.15 30-JAN-05:00 376317.10 15-AUG-18:00
Heating:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 7165.49 84869.15 30-JAN-05:00 376317.10 15-AUG-18:00
General:Cooling:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 7165.49 84869.15 30-JAN-05:00 376317.10 15-AUG-18:00
PlantLoopHeatingDemand:Facility 2015.31 0.00 01-JAN-00:40 1823350.43 26-DEC-07:10
PlantLoopHeatingDemand:Plant 444.85 0.00 01-JAN-00:10 55156.12 15-FEB-12:20
WaterSystems:PlantLoopHeatingDemand 444.85 0.00 01-JAN-00:10 55156.12 15-FEB-12:20
General:WaterSystems:PlantLoopHeatingDemand 444.85 0.00 01-JAN-00:10 55156.12 15-FEB-12:20
EnergyTransfer:HVAC 13446.03 3041.37 30-JAN-01:40 3429176.92 15-AUG-14:30
HeatingCoils:EnergyTransfer 1570.46 0.00 01-JAN-00:40 1805767.55 26-DEC-07:10
PlantLoopHeatingDemand:HVAC 1570.46 0.00 01-JAN-00:40 1805767.55 26-DEC-07:10
HeatingCoils:PlantLoopHeatingDemand 1570.46 0.00 01-JAN-00:40 1805767.55 26-DEC-07:10
CoolingCoils:EnergyTransfer 8315.41 2395.94 14-JAN-17:50 3429176.92 15-AUG-14:30
HeatRecoveryForHeating:EnergyTransfer 3383.80 0.00 01-JAN-00:10 1006668.30 11-DEC-20:00
HeatRecoveryForCooling:EnergyTransfer 176.36 0.00 01-JAN-00:10 485634.79 20-JUL-14:00
EnergyTransfer:Plant 17388.78 0.00 01-JAN-00:40 8870003.18 15-AUG-14:40
LoopToLoop:EnergyTransfer 4877.89 0.00 01-JAN-00:10 2885095.37 15-AUG-14:30
WaterSystems:EnergyTransfer 444.85 0.00 01-JAN-00:10 55156.12 15-FEB-12:20
WaterUse:WaterSystems:EnergyTransfer 444.85 0.00 01-JAN-00:10 55156.12 15-FEB-12:20
Boilers:EnergyTransfer 1555.98 0.00 01-JAN-00:40 1807509.12 26-DEC-07:10
Chillers:EnergyTransfer 4884.12 0.00 01-JAN-00:10 2821794.25 15-AUG-14:40
HeatRejection:EnergyTransfer 5625.94 0.00 01-JAN-00:10 3248011.99 15-AUG-14:40
General:HeatRejection:EnergyTransfer 5625.94 0.00 01-JAN-00:10 3248011.99 15-AUG-14:40
Water Heater:WaterSystems:PlantLoopHeatingDemand 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10



Table of Contents

Report: Sensible Heat Gain Summary

For: Entire Facility

Timestamp: 2023-10-16 08:43:24

Annual Building Sensible Heat Gain Components

HVAC Zone Eq & Other Sensible Air Heating [GJ] HVAC Zone Eq & Other Sensible Air Cooling [GJ] HVAC Terminal Unit Sensible Air Heating [GJ] HVAC Terminal Unit Sensible Air Cooling [GJ] HVAC Input Heated Surface Heating [GJ] HVAC Input Cooled Surface Cooling [GJ] People Sensible Heat Addition [GJ] Lights Sensible Heat Addition [GJ] Equipment Sensible Heat Addition [GJ] Window Heat Addition [GJ] Interzone Air Transfer Heat Addition [GJ] Infiltration Heat Addition [GJ] Opaque Surface Conduction and Other Heat Addition [GJ] Equipment Sensible Heat Removal [GJ] Window Heat Removal [GJ] Interzone Air Transfer Heat Removal [GJ] Infiltration Heat Removal [GJ] Opaque Surface Conduction and Other Heat Removal [GJ]
BASEMENT 0.000 0.000 2.224 -684.875 0.000 0.000 92.911 262.844 424.397 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 -97.502
CORE_BOTTOM 0.000 0.000 0.000 -615.966 0.000 0.000 83.534 236.053 289.614 0.000 0.000 0.000 6.766 0.000 0.000 0.000 0.000 -0.009
CORE_MID 0.000 0.000 15.216 -4359.473 0.000 0.000 858.658 2360.527 2896.128 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 -1771.056
CORE_TOP 0.000 0.000 17.772 -388.205 0.000 0.000 88.529 236.053 289.613 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 -243.762
PERIMETER_BOT_ZN_3 0.000 0.000 2.074 -64.406 0.000 0.000 11.020 17.389 36.365 28.710 0.000 0.050 59.136 0.000 -79.718 0.000 -10.621 0.000
PERIMETER_BOT_ZN_2 0.000 0.000 1.741 -63.640 0.000 0.000 7.174 11.117 23.435 55.889 0.000 0.037 19.810 0.000 -48.615 0.000 -6.948 0.000
PERIMETER_BOT_ZN_1 0.000 0.000 2.988 -98.074 0.000 0.000 10.952 17.123 36.366 103.982 0.000 0.049 9.292 0.000 -72.114 0.000 -10.563 0.000
PERIMETER_BOT_ZN_4 0.000 0.000 0.314 -95.411 0.000 0.000 6.999 11.107 23.435 54.868 0.000 0.031 62.128 0.000 -55.845 0.000 -7.625 0.000
PERIMETER_MID_ZN_3 0.000 0.000 234.368 -421.793 0.000 0.000 114.845 173.521 363.654 298.649 0.000 1.125 171.211 0.000 -715.729 0.000 -219.853 -0.004
PERIMETER_MID_ZN_2 0.000 0.000 137.818 -513.423 0.000 0.000 54.332 110.990 234.352 561.675 0.000 0.768 10.555 0.000 -448.933 0.000 -148.134 -0.016
PERIMETER_MID_ZN_1 0.000 0.000 153.216 -809.987 0.000 0.000 112.130 171.058 363.660 1039.106 0.000 1.054 0.016 0.000 -684.879 0.000 -230.490 -114.869
PERIMETER_MID_ZN_4 0.000 0.000 113.203 -554.891 0.000 0.000 74.251 110.883 234.351 562.906 0.000 0.735 92.054 0.000 -481.146 0.000 -152.346 -0.000
PERIMETER_TOP_ZN_3 0.000 0.000 45.414 -39.286 0.000 0.000 11.618 17.349 36.365 30.317 0.000 0.129 0.001 0.000 -68.208 0.000 -26.188 -7.511
PERIMETER_TOP_ZN_2 0.000 0.000 26.663 -48.478 0.000 0.000 7.427 11.098 23.435 56.477 0.000 0.088 0.000 0.000 -42.959 0.000 -17.714 -16.036
PERIMETER_TOP_ZN_1 0.000 0.000 32.584 -75.323 0.000 0.000 11.366 17.104 36.366 104.511 0.000 0.124 0.000 0.000 -65.161 0.000 -27.307 -34.264
PERIMETER_TOP_ZN_4 0.000 0.000 22.107 -52.762 0.000 0.000 7.501 11.088 23.435 56.448 0.000 0.086 0.000 0.000 -46.166 0.000 -18.204 -3.533
DATACENTER_BOT_ZN_6 0.000 0.000 0.000 -136.368 0.000 0.000 0.950 6.628 153.881 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 -25.091
DATACENTER_MID_ZN_6 0.000 0.000 6.358 -1147.296 0.000 0.000 9.519 66.280 1538.806 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 -473.667
DATACENTER_TOP_ZN_6 0.000 0.000 0.948 -105.067 0.000 0.000 0.955 6.628 153.881 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 -57.345
DATACENTER_BASEMENT_ZN_6 0.000 0.000 0.000 -7165.493 0.000 0.000 20.310 74.111 7494.857 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 -423.785
GROUNDFLOOR_PLENUM 4.580 -54.875 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.086 73.140 0.000 0.000 0.000 -22.930 0.000
MIDFLOOR_PLENUM 179.624 -347.550 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 1.619 546.579 0.000 0.000 0.000 -380.272 -0.019
TOPFLOOR_PLENUM 59.537 -51.318 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.105 32.225 0.000 0.000 0.000 -40.549 -0.000
Total Facility 243.740 -453.743 815.010 -17440.216 0.000 0.000 1584.981 3928.949 14676.396 2953.539 0.000 6.087 1082.913 0.000 -2809.474 0.000 -1319.743 -3268.470


Peak Cooling Sensible Heat Gain Components

Time of Peak {TIMESTAMP} HVAC Zone Eq & Other Sensible Air Heating [W] HVAC Zone Eq & Other Sensible Air Cooling [W] HVAC Terminal Unit Sensible Air Heating [W] HVAC Terminal Unit Sensible Air Cooling [W] HVAC Input Heated Surface Heating [W] HVAC Input Cooled Surface Cooling [W] People Sensible Heat Addition [W] Lights Sensible Heat Addition [W] Equipment Sensible Heat Addition [W] Window Heat Addition [W] Interzone Air Transfer Heat Addition [W] Infiltration Heat Addition [W] Opaque Surface Conduction and Other Heat Addition [W] Equipment Sensible Heat Removal [W] Window Heat Removal [W] Interzone Air Transfer Heat Removal [W] Infiltration Heat Removal [W] Opaque Surface Conduction and Other Heat Removal [W]
BASEMENT 03-JUL-04:11 0.00 0.00 0.00 -123195.54 0.00 0.00 0.00 2550.13 13457.54 0.00 0.00 0.00 107187.86 0.00 -0.00 0.00 0.00 0.00
CORE_BOTTOM 24-JUL-04:13 0.00 0.00 0.00 -100945.31 0.00 0.00 0.00 2290.20 5937.65 0.00 0.00 0.00 92717.47 0.00 -0.00 0.00 0.00 0.00
CORE_MID 18-SEP-04:12 0.00 0.00 0.00 -887047.08 0.00 0.00 0.00 22901.98 59376.23 0.00 0.00 0.00 804768.87 0.00 -0.00 0.00 0.00 0.00
CORE_TOP 19-JUN-04:12 0.00 0.00 0.00 -87965.72 0.00 0.00 0.00 2290.20 5937.62 0.00 0.00 0.00 79737.90 0.00 -0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_3 06-AUG-16:21 0.00 0.00 0.00 -17691.75 0.00 0.00 42.45 68.40 720.18 4342.32 0.00 23.76 12494.64 0.00 -0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_2 04-JUL-08:31 0.00 0.00 0.00 -27809.70 0.00 0.00 18.11 44.08 464.11 21935.62 0.00 0.00 5555.80 0.00 -0.00 0.00 -208.04 0.00
PERIMETER_BOT_ZN_1 10-SEP-12:42 0.00 0.00 0.00 -27775.59 0.00 0.00 32.42 68.40 720.19 27810.37 0.00 0.00 0.00 0.00 -0.00 0.00 -331.04 -524.76
PERIMETER_BOT_ZN_4 02-JUL-17:01 0.00 0.00 0.00 -35903.95 0.00 0.00 0.00 44.08 360.35 22315.29 0.00 0.00 13342.94 0.00 -0.00 0.00 -158.71 0.00
PERIMETER_MID_ZN_3 16-JUL-16:31 0.00 0.00 0.00 -167989.82 0.00 0.00 421.16 684.02 7201.84 46656.47 0.00 829.18 112197.14 0.00 -0.00 0.00 0.00 0.00
PERIMETER_MID_ZN_2 04-JUL-08:31 0.00 0.00 0.00 -299441.53 0.00 0.00 172.37 440.81 4641.14 217779.18 0.00 0.00 81454.96 0.00 -0.00 0.00 -5046.93 0.00
PERIMETER_MID_ZN_1 03-SEP-12:32 0.00 0.00 0.00 -294940.21 0.00 0.00 345.03 684.04 7201.95 237750.93 0.00 0.00 54834.78 0.00 -0.00 0.00 -5876.51 0.00
PERIMETER_MID_ZN_4 11-JUN-16:51 0.00 0.00 0.00 -318839.07 0.00 0.00 163.46 440.81 4641.11 194123.21 0.00 0.00 122674.54 0.00 -0.00 0.00 -3204.06 0.00
PERIMETER_TOP_ZN_3 16-JUL-16:31 0.00 0.00 0.00 -19488.94 0.00 0.00 39.96 68.40 720.18 4512.70 0.00 43.53 14104.17 0.00 -0.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_2 16-JUL-08:31 0.00 0.00 0.00 -28075.78 0.00 0.00 20.29 44.08 464.11 20103.65 0.00 0.00 7607.77 0.00 -0.00 0.00 -164.12 0.00
PERIMETER_TOP_ZN_1 30-JUL-11:52 0.00 0.00 0.00 -30986.43 0.00 0.00 35.23 68.40 720.19 21547.82 0.00 0.00 8959.86 0.00 -0.00 0.00 -345.07 0.00
PERIMETER_TOP_ZN_4 02-JUL-16:51 0.00 0.00 0.00 -34918.92 0.00 0.00 13.13 44.08 464.11 22311.82 0.00 0.00 12584.98 0.00 -0.00 0.00 -499.20 0.00
DATACENTER_BOT_ZN_6 02-AUG-18:40 0.00 0.00 0.00 -8408.99 0.00 0.00 10.62 192.90 7794.42 0.00 0.00 0.00 411.05 0.00 -0.00 0.00 0.00 0.00
DATACENTER_MID_ZN_6 02-AUG-18:40 0.00 0.00 0.00 -80772.81 0.00 0.00 106.16 1929.04 77944.22 0.00 0.00 0.00 793.39 0.00 -0.00 0.00 0.00 0.00
DATACENTER_TOP_ZN_6 02-AUG-18:40 0.00 0.00 0.00 -8129.14 0.00 0.00 10.62 192.90 7794.42 0.00 0.00 0.00 131.20 0.00 -0.00 0.00 0.00 0.00
DATACENTER_BASEMENT_ZN_6 15-AUG-18:00 0.00 0.00 0.00 -376246.44 0.00 0.00 215.52 2157.00 379632.52 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 0.00 -5758.60
GROUNDFLOOR_PLENUM 07-AUG-05:15 0.00 -12093.62 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 12157.82 0.00 -0.00 0.00 -64.20 0.00
MIDFLOOR_PLENUM 07-DEC-04:01 0.00 -108558.13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 157467.15 0.00 -0.00 0.00 -48909.02 0.00
TOPFLOOR_PLENUM 21-JUL-13:40 0.00 -19988.51 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 222.67 19765.84 0.00 -0.00 0.00 0.00 0.00
Total Facility 11-AUG-05:02 0.00 -24598.43 0.00 -2033524.14 0.00 0.00 16198.06 42872.09 616289.16 0.00 0.00 0.00 1469556.20 0.00 -81534.29 0.00 -5258.63 0.00


Peak Heating Sensible Heat Gain Components

Time of Peak {TIMESTAMP} HVAC Zone Eq & Other Sensible Air Heating [W] HVAC Zone Eq & Other Sensible Air Cooling [W] HVAC Terminal Unit Sensible Air Heating [W] HVAC Terminal Unit Sensible Air Cooling [W] HVAC Input Heated Surface Heating [W] HVAC Input Cooled Surface Cooling [W] People Sensible Heat Addition [W] Lights Sensible Heat Addition [W] Equipment Sensible Heat Addition [W] Window Heat Addition [W] Interzone Air Transfer Heat Addition [W] Infiltration Heat Addition [W] Opaque Surface Conduction and Other Heat Addition [W] Equipment Sensible Heat Removal [W] Window Heat Removal [W] Interzone Air Transfer Heat Removal [W] Infiltration Heat Removal [W] Opaque Surface Conduction and Other Heat Removal [W]
BASEMENT 17-JUN-16:02 0.00 0.00 14829.11 0.00 0.00 0.00 520.12 1274.92 13457.54 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 0.00 -30081.70
CORE_BOTTOM 28-FEB-10:05 0.00 0.00 426.58 0.00 0.00 0.00 9130.44 20611.01 17206.63 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 0.00 -47374.67
CORE_MID 02-JAN-04:01 0.00 0.00 562434.24 0.00 0.00 0.00 0.00 11449.71 59376.23 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 0.00 -633260.17
CORE_TOP 02-JAN-04:01 0.00 0.00 84144.53 0.00 0.00 0.00 0.00 1144.97 5937.62 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 0.00 -91227.13
PERIMETER_BOT_ZN_3 06-FEB-04:01 0.00 0.00 13983.10 0.00 0.00 0.00 0.00 143.76 745.56 0.00 0.00 0.00 0.00 0.00 -7889.36 0.00 -1911.49 -5071.57
PERIMETER_BOT_ZN_2 06-FEB-04:01 0.00 0.00 14558.98 0.00 0.00 0.00 0.00 92.65 480.47 0.00 0.00 0.00 0.00 0.00 -5069.08 0.00 -1278.70 -8784.31
PERIMETER_BOT_ZN_1 06-FEB-04:01 0.00 0.00 21537.01 0.00 0.00 0.00 0.00 143.77 745.57 0.00 0.00 0.00 0.00 0.00 -7566.19 0.00 -1855.93 -13004.23
PERIMETER_BOT_ZN_4 06-FEB-05:01 0.00 0.00 12512.22 0.00 0.00 0.00 0.00 185.31 480.46 0.00 0.00 0.00 0.00 0.00 -5411.33 0.00 -1374.29 -6392.38
PERIMETER_MID_ZN_3 06-FEB-04:21 0.00 0.00 153820.85 0.00 0.00 0.00 0.00 1437.63 7455.61 0.00 0.00 0.00 0.00 0.00 -72435.24 0.00 -40927.56 -49351.29
PERIMETER_MID_ZN_2 26-DEC-04:01 0.00 0.00 214212.73 0.00 0.00 0.00 0.00 926.46 4804.68 0.00 0.00 0.00 0.00 0.00 -41676.31 0.00 -31740.14 -146527.42
PERIMETER_MID_ZN_1 26-DEC-04:01 0.00 0.00 241876.58 0.00 0.00 0.00 0.00 1437.66 7455.72 0.00 0.00 0.00 0.00 0.00 -65157.57 0.00 -47322.88 -138289.51
PERIMETER_MID_ZN_4 06-FEB-04:21 0.00 0.00 216741.33 0.00 0.00 0.00 0.00 926.46 4804.65 0.00 0.00 0.00 0.00 0.00 -49253.02 0.00 -28228.36 -144991.05
PERIMETER_TOP_ZN_3 06-FEB-05:01 0.00 0.00 18561.37 0.00 0.00 0.00 0.00 287.56 745.56 0.00 0.00 0.00 0.00 0.00 -6782.06 0.00 -4882.06 -7930.37
PERIMETER_TOP_ZN_2 06-FEB-04:21 0.00 0.00 23456.87 0.00 0.00 0.00 0.00 92.65 480.47 0.00 0.00 0.00 0.00 0.00 -4500.30 0.00 -3339.39 -16190.29
PERIMETER_TOP_ZN_1 06-FEB-04:21 0.00 0.00 27325.15 0.00 0.00 0.00 0.00 143.77 745.57 0.00 0.00 0.00 0.00 0.00 -7032.09 0.00 -4974.58 -16207.83
PERIMETER_TOP_ZN_4 06-FEB-04:21 0.00 0.00 25403.20 0.00 0.00 0.00 0.00 92.65 480.46 0.00 0.00 0.00 0.00 0.00 -4755.59 0.00 -3396.16 -17824.55
DATACENTER_BOT_ZN_6 - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
DATACENTER_MID_ZN_6 24-JAN-01:20 0.00 0.00 5795.81 0.00 0.00 0.00 0.00 321.53 19486.06 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 0.00 -25603.39
DATACENTER_TOP_ZN_6 15-JAN-18:55 0.00 0.00 620.09 0.00 0.00 0.00 0.00 32.15 1948.61 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 0.00 -2600.85
DATACENTER_BASEMENT_ZN_6 - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
GROUNDFLOOR_PLENUM 15-FEB-06:02 14251.41 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 -851.23 -13400.18
MIDFLOOR_PLENUM 02-JAN-06:12 193300.63 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 -5284.93 -188015.71
TOPFLOOR_PLENUM 06-FEB-05:10 33734.40 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 -7902.41 -25831.98
Total Facility 02-JAN-06:01 -57742.74 210760.54 1452150.85 -210760.54 0.00 0.00 22492.86 42872.09 261414.96 0.00 0.00 0.00 0.00 0.00 -167706.11 0.00 -19315.04 -1534166.88



Table of Contents

Report: Standard 62.1 Summary

For: Entire Facility

Timestamp: 2023-10-16 08:43:24

System Ventilation Requirements for Cooling

Sum of Zone Primary Air Flow - Vpz-sum [m3/s] System Population - Ps Sum of Zone Population - Pz-sum Occupant Diversity - D Origin of D Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] System Primary Airflow - Vps [m3/s] Average Outdoor Air Fraction - Xs System Ventilation Efficiency - Ev Calculation Method for Ev Outdoor Air Intake Flow - Vot [m3/s] Percent Outdoor Air - %OA Environment Name of Peak System Population - Ps Date and Time of Last Peak System Population - Ps
VAV_BOT WITH REHEAT 12.0465 0.0000 0.0000 1.0000 Calculated from schedules 0.0000 10.3802 0.0000 1.0000 Not calculated 0.0000 0.0000    
VAV_MID WITH REHEAT 115.9961 0.0000 0.0000 1.0000 Calculated from schedules 0.0000 96.9279 0.0000 1.0000 Not calculated 0.0000 0.0000    
VAV_TOP WITH REHEAT 11.8594 0.0000 0.0000 1.0000 Calculated from schedules 0.0000 10.6258 0.0000 1.0000 Not calculated 0.0000 0.0000    
CAV_BAS 6.0675 0.0000 149.6021 1.0000 Calculated from schedules 1.2002 6.0675 0.1978 1.0000 Not calculated 1.2002 0.1978    
AIRLOOP DATACENTER BASEMENT 21.9381 0.0000 42.1814 1.0000 Calculated from schedules 0.3384 21.9382 0.0154 1.0000 Not calculated 0.3384 0.0154    
AIRLOOP DATACENTER BOT 0.5124 0.0000 1.9486 1.0000 Calculated from schedules 0.0156 0.5124 0.0305 1.0000 Not calculated 0.0156 0.0305    
AIRLOOP DATACENTER MID 4.9171 0.0000 19.4861 1.0000 Calculated from schedules 0.1563 4.9171 0.0318 1.0000 Not calculated 0.1563 0.0318    
AIRLOOP DATACENTER TOP 0.4996 0.0000 1.9486 1.0000 Calculated from schedules 0.0156 0.4996 0.0313 1.0000 Not calculated 0.0156 0.0313    


System Ventilation Requirements for Heating

Sum of Zone Primary Air Flow - Vpz-sum [m3/s] System Population - Ps Sum of Zone Population - Pz-sum Occupant Diversity - D Origin of D Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] System Primary Airflow - Vps [m3/s] Average Outdoor Air Fraction - Xs System Ventilation Efficiency - Ev Calculation Method for Ev Outdoor Air Intake Flow Vot [m3/s] Percent Outdoor Air - %OA Environment Name of Peak System Population - Ps Date and Time of Last Peak System Population - Ps
VAV_BOT WITH REHEAT 6.0233 0.0000 0.0000 1.0000 Calculated from schedules 0.0000 3.1584 0.0000 1.0000 Not calculated 0.0000 0.0000    
VAV_MID WITH REHEAT 57.9981 0.0000 0.0000 1.0000 Calculated from schedules 0.0000 31.1119 0.0000 1.0000 Not calculated 0.0000 0.0000    
VAV_TOP WITH REHEAT 5.9297 0.0000 0.0000 1.0000 Calculated from schedules 0.0000 3.2072 0.0000 1.0000 Not calculated 0.0000 0.0000    
CAV_BAS 6.0675 0.0000 149.6021 1.0000 Calculated from schedules 1.2002 6.0675 1.0000 1.0000 Not calculated 1.2002 0.1978    
AIRLOOP DATACENTER BASEMENT 21.9381 0.0000 42.1814 1.0000 Calculated from schedules 0.3384 21.9381 1.0000 1.0000 Not calculated 0.3384 0.0154    
AIRLOOP DATACENTER BOT 0.5124 0.0000 1.9486 1.0000 Calculated from schedules 0.0156 0.5124 1.0000 1.0000 Not calculated 0.0156 0.0305    
AIRLOOP DATACENTER MID 4.9171 0.0000 19.4861 1.0000 Calculated from schedules 0.1563 4.9171 1.0000 1.0000 Not calculated 0.1563 0.0318    
AIRLOOP DATACENTER TOP 0.4996 0.0000 1.9486 1.0000 Calculated from schedules 0.0156 0.4996 1.0000 1.0000 Not calculated 0.0156 0.0313    


Zone Ventilation Parameters

AirLoop Name People Outdoor Air Rate - Rp [m3/s-person] Zone Population - Pz Area Outdoor Air Rate - Ra [m3/s-m2] Zone Floor Area - Az [m2] Breathing Zone Outdoor Airflow - Vbz [m3/s] Cooling Zone Air Distribution Effectiveness - Ez-clg Cooling Zone Outdoor Airflow - Voz-clg [m3/s] Heating Zone Air Distribution Effectiveness - Ez-htg Heating Zone Outdoor Airflow - Voz-htg [m3/s]
BASEMENT CAV_BAS 0.000000 149.6021 0.000432 2779.43 1.2002 1.0000 1.2002 1.000 1.2002
CORE_BOTTOM VAV_BOT WITH REHEAT 0.000000 134.3532 0.000432 2496.12 0.0000 1.0000 0.0000 1.000 0.0000
CORE_MID VAV_MID WITH REHEAT 0.000000 1343.5320 0.000432 24961.20 0.0000 1.0000 0.0000 1.000 0.0000
CORE_TOP VAV_TOP WITH REHEAT 0.000000 134.3532 0.000432 2496.12 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_BOT_ZN_3 VAV_BOT WITH REHEAT 0.000000 16.8694 0.000432 313.41 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_BOT_ZN_2 VAV_BOT WITH REHEAT 0.000000 10.8713 0.000432 201.98 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_BOT_ZN_1 VAV_BOT WITH REHEAT 0.000000 16.8698 0.000432 313.42 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_BOT_ZN_4 VAV_BOT WITH REHEAT 0.000000 10.8713 0.000432 201.98 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_MID_ZN_3 VAV_MID WITH REHEAT 0.000000 168.6939 0.000432 3134.13 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_MID_ZN_2 VAV_MID WITH REHEAT 0.000000 108.7127 0.000432 2019.75 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_MID_ZN_1 VAV_MID WITH REHEAT 0.000000 168.6975 0.000432 3134.20 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_MID_ZN_4 VAV_MID WITH REHEAT 0.000000 108.7127 0.000432 2019.75 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_TOP_ZN_3 VAV_TOP WITH REHEAT 0.000000 16.8694 0.000432 313.41 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_TOP_ZN_2 VAV_TOP WITH REHEAT 0.000000 10.8713 0.000432 201.98 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_TOP_ZN_1 VAV_TOP WITH REHEAT 0.000000 16.8698 0.000432 313.42 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_TOP_ZN_4 VAV_TOP WITH REHEAT 0.000000 10.8713 0.000432 201.98 0.0000 1.0000 0.0000 1.000 0.0000
DATACENTER_BOT_ZN_6 AIRLOOP DATACENTER BOT 0.000000 1.9486 0.000432 36.20 0.0156 1.0000 0.0156 1.000 0.0156
DATACENTER_MID_ZN_6 AIRLOOP DATACENTER MID 0.000000 19.4861 0.000432 362.03 0.1563 1.0000 0.1563 1.000 0.1563
DATACENTER_TOP_ZN_6 AIRLOOP DATACENTER TOP 0.000000 1.9486 0.000432 36.20 0.0156 1.0000 0.0156 1.000 0.0156
DATACENTER_BASEMENT_ZN_6 AIRLOOP DATACENTER BASEMENT 0.000000 42.1814 0.000432 783.68 0.3384 1.0000 0.3384 1.000 0.3384


System Ventilation Parameters

People Outdoor Air Rate - Rp [m3/s-person] Sum of Zone Population - Pz-sum Area Outdoor Air Rate - Ra [m3/s-m2] Sum of Zone Floor Area - Az-sum [m2] Breathing Zone Outdoor Airflow - Vbz [m3/s] Cooling Zone Outdoor Airflow - Voz-clg [m3/s] Heating Zone Outdoor Airflow - Voz-htg [m3/s]
VAV_BOT WITH REHEAT   0.00 0.000432 3526.9033 0.0000 0.0000 0.0000
VAV_MID WITH REHEAT   0.00 0.000432 35269.0328 0.0000 0.0000 0.0000
VAV_TOP WITH REHEAT   0.00 0.000432 3526.9033 0.0000 0.0000 0.0000
CAV_BAS 0.000000 149.60 0.000432 2779.4266 1.2002 1.2002 1.2002
AIRLOOP DATACENTER BASEMENT 0.000000 42.18 0.000432 783.6794 0.3384 0.3384 0.3384
AIRLOOP DATACENTER BOT 0.000000 1.95 0.000432 36.2027 0.0156 0.0156 0.0156
AIRLOOP DATACENTER MID 0.000000 19.49 0.000432 362.0274 0.1563 0.1563 0.1563
AIRLOOP DATACENTER TOP 0.000000 1.95 0.000432 36.2027 0.0156 0.0156 0.0156


Zone Ventilation Calculations for Cooling Design

AirLoop Name Box Type Zone Primary Airflow - Vpz [m3/s] Zone Discharge Airflow - Vdz [m3/s] Minimum Zone Primary Airflow - Vpz-min [m3/s] Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? Zone Outdoor Airflow Cooling - Voz-clg [m3/s] Primary Outdoor Air Fraction - Zpz Primary Air Fraction - Ep Secondary Recirculation Fraction- Er Supply Air Fraction- Fa Mixed Air Fraction - Fb Outdoor Air Fraction - Fc Zone Ventilation Efficiency - Evz
BASEMENT CAV_BAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 6.0675 6.0675 6.0675 No 1.2002 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CORE_BOTTOM VAV_BOT WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 6.3031 6.3031 1.9729 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CORE_MID VAV_MID WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 59.3865 59.3865 19.3600 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CORE_TOP VAV_TOP WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 5.8741 5.8741 1.9854 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_BOT_ZN_3 VAV_BOT WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.0536 1.0536 0.2476 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_BOT_ZN_2 VAV_BOT WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.3924 1.3924 0.2785 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_BOT_ZN_1 VAV_BOT WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.6088 1.6088 0.3218 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_BOT_ZN_4 VAV_BOT WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.6887 1.6887 0.3377 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_MID_ZN_3 VAV_MID WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 9.9989 9.9989 2.4297 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_MID_ZN_2 VAV_MID WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 14.8330 14.8330 2.9666 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_MID_ZN_1 VAV_MID WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 16.1005 16.1005 3.2201 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_MID_ZN_4 VAV_MID WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 15.6772 15.6772 3.1354 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_TOP_ZN_3 VAV_TOP WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.1220 1.1220 0.2491 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_TOP_ZN_2 VAV_TOP WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.4931 1.4931 0.2986 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_TOP_ZN_1 VAV_TOP WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.7235 1.7235 0.3447 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_TOP_ZN_4 VAV_TOP WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.6467 1.6467 0.3293 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
DATACENTER_BOT_ZN_6 AIRLOOP DATACENTER BOT AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.5124 0.5124 0.5124 No 0.0156 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
DATACENTER_MID_ZN_6 AIRLOOP DATACENTER MID AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 4.9171 4.9171 4.9171 No 0.1563 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
DATACENTER_TOP_ZN_6 AIRLOOP DATACENTER TOP AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.4996 0.4996 0.4996 No 0.0156 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
DATACENTER_BASEMENT_ZN_6 AIRLOOP DATACENTER BASEMENT AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 21.9381 21.9381 21.9381 No 0.3384 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000


System Ventilation Calculations for Cooling Design

Sum of Zone Primary Airflow - Vpz-sum [m3/s] System Primary Airflow - Vps [m3/s] Sum of Zone Discharge Airflow - Vdz-sum [m3/s] Sum of Min Zone Primary Airflow - Vpz-min [m3/s] Zone Outdoor Airflow Cooling - Voz-clg [m3/s] Zone Ventilation Efficiency - Evz-min
VAV_BOT WITH REHEAT 12.0465 10.3802 12.0465 3.1584 0.0000 1.0000
VAV_MID WITH REHEAT 115.9961 96.9279 115.9961 31.1119 0.0000 1.0000
VAV_TOP WITH REHEAT 11.8594 10.6258 11.8594 3.2072 0.0000 1.0000
CAV_BAS 6.0675 6.0675 6.0675 6.0675 1.2002 1.0000
AIRLOOP DATACENTER BASEMENT 21.9381 21.9382 21.9381 21.9381 0.3384 1.0000
AIRLOOP DATACENTER BOT 0.5124 0.5124 0.5124 0.5124 0.0156 1.0000
AIRLOOP DATACENTER MID 4.9171 4.9171 4.9171 4.9171 0.1563 1.0000
AIRLOOP DATACENTER TOP 0.4996 0.4996 0.4996 0.4996 0.0156 1.0000


Zone Ventilation Calculations for Heating Design

AirLoop Name Box Type Zone Primary Airflow - Vpz [m3/s] Zone Discharge Airflow - Vdz [m3/s] Minimum Zone Primary Airflow - Vpz-min [m3/s] Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? Zone Outdoor Airflow Heating - Voz-htg [m3/s] Primary Outdoor Air Fraction - Zpz Primary Air Fraction - Ep Secondary Recirculation Fraction- Er Supply Air Fraction- Fa Mixed Air Fraction - Fb Outdoor Air Fraction - Fc Zone Ventilation Efficiency - Evz
BASEMENT CAV_BAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 6.0675 6.0675 6.0675 No 1.2002 1.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CORE_BOTTOM VAV_BOT WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 3.1516 3.1516 1.9729 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CORE_MID VAV_MID WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 29.6933 29.6933 19.3600 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CORE_TOP VAV_TOP WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 2.9371 2.9371 1.9854 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_BOT_ZN_3 VAV_BOT WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.5268 0.5268 0.2476 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_BOT_ZN_2 VAV_BOT WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.6962 0.6962 0.2785 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_BOT_ZN_1 VAV_BOT WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.8044 0.8044 0.3218 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_BOT_ZN_4 VAV_BOT WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.8444 0.8444 0.3377 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_MID_ZN_3 VAV_MID WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 4.9995 4.9995 2.4297 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_MID_ZN_2 VAV_MID WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 7.4165 7.4165 2.9666 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_MID_ZN_1 VAV_MID WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 8.0502 8.0502 3.2201 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_MID_ZN_4 VAV_MID WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 7.8386 7.8386 3.1354 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_TOP_ZN_3 VAV_TOP WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.5610 0.5610 0.2491 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_TOP_ZN_2 VAV_TOP WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.7466 0.7466 0.2986 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_TOP_ZN_1 VAV_TOP WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.8618 0.8618 0.3447 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_TOP_ZN_4 VAV_TOP WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.8233 0.8233 0.3293 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
DATACENTER_BOT_ZN_6 AIRLOOP DATACENTER BOT AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.5124 0.5124 0.5124 No 0.0156 1.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
DATACENTER_MID_ZN_6 AIRLOOP DATACENTER MID AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 4.9171 4.9171 4.9171 No 0.1563 1.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
DATACENTER_TOP_ZN_6 AIRLOOP DATACENTER TOP AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.4996 0.4996 0.4996 No 0.0156 1.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
DATACENTER_BASEMENT_ZN_6 AIRLOOP DATACENTER BASEMENT AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 21.9381 21.9381 21.9381 No 0.3384 1.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000


System Ventilation Calculations for Heating Design

Sum of Zone Primary Airflow - Vpz-sum [m3/s] System Primary Airflow - Vps [m3/s] Sum of Zone Discharge Airflow - Vdz-sum [m3/s] Sum of Min Zone Primary Airflow - Vpz-min [m3/s] Zone Outdoor Airflow Heating - Voz-htg [m3/s] Zone Ventilation Efficiency - Evz-min
VAV_BOT WITH REHEAT 6.0233 3.1584 3.1584 3.1584 0.0000 1.0000
VAV_MID WITH REHEAT 57.9981 31.1119 31.1119 31.1119 0.0000 1.0000
VAV_TOP WITH REHEAT 5.9297 3.2072 3.2072 3.2072 0.0000 1.0000
CAV_BAS 6.0675 6.0675 6.0675 6.0675 1.2002 1.0000
AIRLOOP DATACENTER BASEMENT 21.9381 21.9381 21.9381 21.9381 0.3384 1.0000
AIRLOOP DATACENTER BOT 0.5124 0.5124 0.5124 0.5124 0.0156 1.0000
AIRLOOP DATACENTER MID 4.9171 4.9171 4.9171 4.9171 0.1563 1.0000
AIRLOOP DATACENTER TOP 0.4996 0.4996 0.4996 0.4996 0.0156 1.0000



Table of Contents

Report: LEED Summary

For: Entire Facility

Timestamp: 2023-10-16 08:43:24

Sec1.1A-General Information

Data
Weather File RUNPERIOD 1 ** Buffalo Niagara Intl AP NY USA TMY3 WMO#=725280
Total gross floor area [m2] 46320.38
Principal Heating Source Natural Gas


EAp2-1. Space Usage Type

Space Area [m2] Regularly Occupied Area [m2] Unconditioned Area [m2] Typical Hours/Week in Operation [hr/wk]
BASEMENT 2779.43 2779.43 0.00 113.98
CORE_BOTTOM 2496.12 2496.12 0.00 113.98
CORE_MID 2496.12 2496.12 0.00 113.98
CORE_TOP 2496.12 2496.12 0.00 113.98
PERIMETER_BOT_ZN_3 313.41 313.41 0.00 113.98
PERIMETER_BOT_ZN_2 201.98 201.98 0.00 113.98
PERIMETER_BOT_ZN_1 313.42 313.42 0.00 113.98
PERIMETER_BOT_ZN_4 201.98 201.98 0.00 113.98
PERIMETER_MID_ZN_3 313.41 313.41 0.00 113.98
PERIMETER_MID_ZN_2 201.98 201.98 0.00 96.54
PERIMETER_MID_ZN_1 313.42 313.42 0.00 113.98
PERIMETER_MID_ZN_4 201.98 201.98 0.00 113.98
PERIMETER_TOP_ZN_3 313.41 313.41 0.00 113.98
PERIMETER_TOP_ZN_2 201.98 201.98 0.00 113.98
PERIMETER_TOP_ZN_1 313.42 313.42 0.00 113.98
PERIMETER_TOP_ZN_4 201.98 201.98 0.00 113.98
DATACENTER_BOT_ZN_6 36.20 36.20 0.00 113.98
DATACENTER_MID_ZN_6 36.20 36.20 0.00 113.98
DATACENTER_TOP_ZN_6 36.20 36.20 0.00 113.98
DATACENTER_BASEMENT_ZN_6 783.68 783.68 0.00 113.98
GROUNDFLOOR_PLENUM 3563.11 3563.11 0.00 0.00
MIDFLOOR_PLENUM 3563.11 3563.11 0.00 0.00
TOPFLOOR_PLENUM 3563.11 3563.11 0.00 0.00
Totals 46320.38 46320.38 0.00  


EAp2-2. Advisory Messages

Data
Number of hours heating loads not met 111.50
Number of hours cooling loads not met 366.00
Number of hours not met 477.50


EAp2-3. Energy Type Summary

Utility Rate Virtual Rate [$/unit energy] Units of Energy Units of Demand
None        


EAp2-4/5. Performance Rating Method Compliance

Electricity Energy Use [GJ] Electricity Demand [W] Natural Gas Energy Use [GJ] Natural Gas Demand [W] Gasoline Use [GJ] Gasoline Demand [W] Diesel Use [GJ] Diesel Demand [W] Coal Use [GJ] Coal Demand [W] Fuel Oil No 1 Use [GJ] Fuel Oil No 1 Demand [W] Fuel Oil No 2 Use [GJ] Fuel Oil No 2 Demand [W] Propane Use [GJ] Propane Demand [W] Other Fuel 1 Use [GJ] Other Fuel 1 Demand [W] Other Fuel 2 Use [GJ] Other Fuel 2 Demand [W] District Cooling Use [GJ] District Cooling Demand [W] District Heating Use [GJ] District Heating Demand [W]
Heating -- General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heating -- Boiler 0.00 0.00 2119.03 2175214.88 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heating -- Boiler Parasitic 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling -- General 1733.72 583018.50 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting -- LightsWired 3928.95 385834.94 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting -- General 696.73 57580.60 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- MiscPlug 5334.97 305206.10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- DataCenterPlugLoads 9341.42 473165.59 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment -- Transformer 80.18 5057.48 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment -- ElevatorLift 1848.78 113101.96 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment -- ElevatorLightsFan 5.83 376.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans -- General 2402.24 292128.76 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps -- General 374.21 59285.61 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection -- General 596.57 90257.03 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification -- General 1449.29 100000.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery -- General 47.24 5613.48 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems -- General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems -- WaterUse 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems -- Water Heater 0.00 0.00 825.38 86742.10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration -- Not Subdivided 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators -- General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


EAp2-6. Energy Use Summary

Process Subtotal [GJ] Total Energy Use [GJ]
Electricity 14676.40 27840.15
Natural Gas 0.00 2944.41
Additional 0.00 0.00
Total 14676.40 30784.56


EAp2-7. Energy Cost Summary

Process Subtotal [$] Total Energy Cost [$]
Electricity 0.00  
Natural Gas 0.00  
Additional 0.00  
Total 0.00  
Process energy cost based on ratio of process to total energy.

L-1. Renewable Energy Source Summary

Rated Capacity [kW] Annual Energy Generated [GJ]
Photovoltaic 0.00 0.00
Wind 0.00 0.00


EAp2-17a. Energy Use Intensity - Electricity

Electricty [MJ/m2]
Interior Lighting (All) 84.82
Space Heating 0.00
Space Cooling 37.43
Fans (All) 51.86
Service Water Heating 0.00
Receptacle Equipment 316.85
Miscellaneous (All) 601.03
Subtotal 601.03


EAp2-17b. Energy Use Intensity - Natural Gas

Natural Gas [MJ/m2]
Space Heating 45.75
Service Water Heating 17.82
Miscellaneous (All) 63.57
Subtotal 63.57


EAp2-17c. Energy Use Intensity - Additional

Additional [MJ/m2]
Subtotal 0.00
Miscellaneous 0.00


EAp2-18. End Use Percentage

Percent [%]
Interior Lighting (All) 12.76
Space Heating 6.88
Space Cooling 5.63
Fans (All) 7.80
Service Water Heating 2.68
Receptacle Equipment 47.67
Miscellaneous 16.56


Schedules-Equivalent Full Load Hours (Schedule Type=Fraction)

Equivalent Full Load Hours of Operation Per Year [hr] Hours > 1% [hr]
EXTERIOR_LIGHTING_SCHEDULE_A 6570. 6570.
EXTERIOR_LIGHTING_SCHEDULE_B 8103. 8760.
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 4472. 4472.
EXTERIOR_LIGHTING_SCHEDULE_B_2016 7665. 8760.
EXTERIOR_LIGHTING_SCHEDULE_C_2016 6752. 8760.
ALWAYS_ON 8760. 8760.
EXTERIOR_LGT_ALWAYS_ON 8760. 8760.
EXTERIOR_LGT_189_1 6828. 8760.
ALWAYS_OFF 0. 0.
LTG_SCH_OFFICE 2625. 8760.
LTG_SCH_DATACENTER 2921. 8760.
EXTERIOR_LIGHT_SCH 4380. 4380.
BLDG_EQUIP_SCH 4049. 8760.
DATACENTER_EQUIP_SCH 5478. 8760.
BLDG_OCC_SCH 2528. 5992.
BLDG_OCC_SCH_W_SB 1878. 5056.
BLDG_OCC_SCH_WO_SB 2557. 5992.
BLDG_ELEVATORS 2270. 8760.
ELEV_LIGHT_FAN_SCH_24_7 8760. 8760.
ELEV_LIGHT_FAN_SCH_ADD_DF 2154. 8760.
BLDG_SWH_SCH 1474. 6570.
WORK_EFF_SCH 0. 0.
INFIL_SCH 3976. 3976.
INFIL_SCH_PNNL 5172. 8760.
INFIL_HALF_ON_SCH 6368. 8760.
FAN_SCH 8760. 8760.
REHEATCOILAVAILSCHED 8760. 8760.
COOLINGCOILAVAILSCHED 8760. 8760.
MINOA_MOTORIZEDDAMPER_SCHED 4472. 4472.
MINOA_SCHED 8760. 8760.
CORE_BOTTOM SUB CAT LATENT FRACT SCHED 438. 8760.
CORE_BOTTOM SUB CAT SENSIBLE FRACT SCHED 1752. 8760.
CORE_MID SUB CAT LATENT FRACT SCHED 438. 8760.
CORE_MID SUB CAT SENSIBLE FRACT SCHED 1752. 8760.
CORE_TOP SUB CAT LATENT FRACT SCHED 438. 8760.
CORE_TOP SUB CAT SENSIBLE FRACT SCHED 1752. 8760.
SUPPLYFANSCH 8760. 8760.
PERIMETER_MID_ZN_2_MDP_SCH 1565. 7824.


Schedules-SetPoints (Schedule Type=Temperature)

First Object Used Month Assumed 11am First Wednesday [C] Days with Same 11am Value 11pm First Wednesday [C] Days with Same 11pm Value
HTGSETP_DC_SCH DATACENTER COOLING SETPOINTS DUAL SP CONTROL January 18.00 365 18.00 365
CLGSETP_DC_SCH DATACENTER COOLING SETPOINTS DUAL SP CONTROL July 27.00 365 27.00 365
HTGSETP_SCH_YES_OPTIMUM CORE_BOTTOM DUAL SP CONTROL January 21.00 365 15.60 365
CLGSETP_SCH_YES_OPTIMUM CORE_BOTTOM DUAL SP CONTROL July 24.00 365 26.70 365



Table of Contents

Report: Annual Thermal Resilience Summary

For: Entire Facility

Timestamp: 2023-10-16 08:43:24

Heat Index Hours

Safe (≤ 26.7°C) [hr] Caution (> 26.7, ≤ 32.2°C) [hr] Extreme Caution (> 32.2, ≤ 39.4°C) [hr] Danger (> 39.4, ≤ 51.7°C) [hr] Extreme Danger (> 51.7°C) [hr]
BASEMENT 8366.83 393.17 0.00 0.00 0.00
CORE_BOTTOM 8738.67 21.33 0.00 0.00 0.00
CORE_MID 8760.00 0.00 0.00 0.00 0.00
CORE_TOP 8759.17 0.83 0.00 0.00 0.00
PERIMETER_BOT_ZN_3 8741.83 18.17 0.00 0.00 0.00
PERIMETER_BOT_ZN_2 8721.50 38.50 0.00 0.00 0.00
PERIMETER_BOT_ZN_1 8698.50 61.50 0.00 0.00 0.00
PERIMETER_BOT_ZN_4 8377.83 382.17 0.00 0.00 0.00
PERIMETER_MID_ZN_3 8746.33 13.67 0.00 0.00 0.00
PERIMETER_MID_ZN_2 8703.17 56.83 0.00 0.00 0.00
PERIMETER_MID_ZN_1 8693.33 66.67 0.00 0.00 0.00
PERIMETER_MID_ZN_4 8594.33 165.67 0.00 0.00 0.00
PERIMETER_TOP_ZN_3 8730.83 29.17 0.00 0.00 0.00
PERIMETER_TOP_ZN_2 8702.50 57.50 0.00 0.00 0.00
PERIMETER_TOP_ZN_1 8684.67 75.33 0.00 0.00 0.00
PERIMETER_TOP_ZN_4 8595.67 164.33 0.00 0.00 0.00
DATACENTER_BOT_ZN_6 7706.17 1053.83 0.00 0.00 0.00
DATACENTER_MID_ZN_6 7689.00 1071.00 0.00 0.00 0.00
DATACENTER_TOP_ZN_6 7671.33 1088.67 0.00 0.00 0.00
DATACENTER_BASEMENT_ZN_6 6704.33 2036.00 19.67 0.00 0.00
GROUNDFLOOR_PLENUM 8760.00 0.00 0.00 0.00 0.00
MIDFLOOR_PLENUM 8760.00 0.00 0.00 0.00 0.00
TOPFLOOR_PLENUM 8685.50 74.50 0.00 0.00 0.00
Min 6704.33 0.00 0.00 0.00 0.00
Max 8760.00 2036.00 19.67 0.00 0.00
Average 8460.50 298.64 0.86 0.00 0.00
Sum 194591.50 6868.83 19.67 0.00 0.00


Heat Index OccupantHours

Safe (≤ 26.7°C) [hr] Caution (> 26.7, ≤ 32.2°C) [hr] Extreme Caution (> 32.2, ≤ 39.4°C) [hr] Danger (> 39.4, ≤ 51.7°C) [hr] Extreme Danger (> 51.7°C) [hr]
BASEMENT 367563.67 1052.33 0.00 0.00 0.00
CORE_BOTTOM 330813.00 0.00 0.00 0.00 0.00
CORE_MID 330813.00 0.00 0.00 0.00 0.00
CORE_TOP 330808.00 5.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_3 38925.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_2 24909.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_1 38925.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_4 24909.00 0.00 0.00 0.00 0.00
PERIMETER_MID_ZN_3 38925.00 0.00 0.00 0.00 0.00
PERIMETER_MID_ZN_2 18354.00 0.00 0.00 0.00 0.00
PERIMETER_MID_ZN_1 38925.00 0.00 0.00 0.00 0.00
PERIMETER_MID_ZN_4 24909.00 0.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_3 38925.00 0.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_2 24909.00 0.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_1 38925.00 0.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_4 24909.00 0.00 0.00 0.00 0.00
DATACENTER_BOT_ZN_6 1730.17 537.83 0.00 0.00 0.00
DATACENTER_MID_ZN_6 1713.83 554.17 0.00 0.00 0.00
DATACENTER_TOP_ZN_6 1702.67 565.33 0.00 0.00 0.00
DATACENTER_BASEMENT_ZN_6 78886.33 24196.00 312.67 0.00 0.00
GROUNDFLOOR_PLENUM 0.00 0.00 0.00 0.00 0.00
MIDFLOOR_PLENUM 0.00 0.00 0.00 0.00 0.00
TOPFLOOR_PLENUM 0.00 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00 0.00
Max 367563.67 24196.00 312.67 0.00 0.00
Average 79151.29 1170.03 13.59 0.00 0.00
Sum 1820479.67 26910.67 312.67 0.00 0.00


Humidex Hours

Little to no Discomfort (≤ 29) [hr] Some Discomfort (> 29, ≤ 40) [hr] Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] Dangerous (> 45, ≤ 50) [hr] Heat Stroke Quite Possible (> 50) [hr]
BASEMENT 7709.83 1050.17 0.00 0.00 0.00
CORE_BOTTOM 8236.00 524.00 0.00 0.00 0.00
CORE_MID 8268.50 491.50 0.00 0.00 0.00
CORE_TOP 8266.50 493.50 0.00 0.00 0.00
PERIMETER_BOT_ZN_3 8271.33 488.67 0.00 0.00 0.00
PERIMETER_BOT_ZN_2 8473.33 286.67 0.00 0.00 0.00
PERIMETER_BOT_ZN_1 8302.00 458.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_4 7966.33 793.67 0.00 0.00 0.00
PERIMETER_MID_ZN_3 8284.33 475.67 0.00 0.00 0.00
PERIMETER_MID_ZN_2 8279.83 480.17 0.00 0.00 0.00
PERIMETER_MID_ZN_1 8237.00 523.00 0.00 0.00 0.00
PERIMETER_MID_ZN_4 8156.17 603.83 0.00 0.00 0.00
PERIMETER_TOP_ZN_3 8291.67 468.33 0.00 0.00 0.00
PERIMETER_TOP_ZN_2 8296.00 464.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_1 8253.17 506.83 0.00 0.00 0.00
PERIMETER_TOP_ZN_4 8188.33 571.67 0.00 0.00 0.00
DATACENTER_BOT_ZN_6 8270.17 489.83 0.00 0.00 0.00
DATACENTER_MID_ZN_6 8254.00 506.00 0.00 0.00 0.00
DATACENTER_TOP_ZN_6 8249.17 510.83 0.00 0.00 0.00
DATACENTER_BASEMENT_ZN_6 6908.17 1851.83 0.00 0.00 0.00
GROUNDFLOOR_PLENUM 8134.33 625.67 0.00 0.00 0.00
MIDFLOOR_PLENUM 8230.00 530.00 0.00 0.00 0.00
TOPFLOOR_PLENUM 7969.83 790.17 0.00 0.00 0.00
Min 6908.17 286.67 0.00 0.00 0.00
Max 8473.33 1851.83 0.00 0.00 0.00
Average 8152.00 608.00 0.00 0.00 0.00
Sum 187496.00 13984.00 0.00 0.00 0.00


Humidex OccupantHours

Little to no Discomfort (≤ 29) [hr] Some Discomfort (> 29, ≤ 40) [hr] Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] Dangerous (> 45, ≤ 50) [hr] Heat Stroke Quite Possible (> 50) [hr]
BASEMENT 360057.67 8558.33 0.00 0.00 0.00
CORE_BOTTOM 329972.00 841.00 0.00 0.00 0.00
CORE_MID 330102.00 711.00 0.00 0.00 0.00
CORE_TOP 330079.00 734.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_3 38925.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_2 24909.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_1 38925.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_4 24909.00 0.00 0.00 0.00 0.00
PERIMETER_MID_ZN_3 38921.17 3.83 0.00 0.00 0.00
PERIMETER_MID_ZN_2 18353.67 0.33 0.00 0.00 0.00
PERIMETER_MID_ZN_1 38923.00 2.00 0.00 0.00 0.00
PERIMETER_MID_ZN_4 24908.67 0.33 0.00 0.00 0.00
PERIMETER_TOP_ZN_3 38920.33 4.67 0.00 0.00 0.00
PERIMETER_TOP_ZN_2 24908.17 0.83 0.00 0.00 0.00
PERIMETER_TOP_ZN_1 38922.67 2.33 0.00 0.00 0.00
PERIMETER_TOP_ZN_4 24908.50 0.50 0.00 0.00 0.00
DATACENTER_BOT_ZN_6 1959.17 308.83 0.00 0.00 0.00
DATACENTER_MID_ZN_6 1949.83 318.17 0.00 0.00 0.00
DATACENTER_TOP_ZN_6 1945.83 322.17 0.00 0.00 0.00
DATACENTER_BASEMENT_ZN_6 81405.50 21989.50 0.00 0.00 0.00
GROUNDFLOOR_PLENUM 0.00 0.00 0.00 0.00 0.00
MIDFLOOR_PLENUM 0.00 0.00 0.00 0.00 0.00
TOPFLOOR_PLENUM 0.00 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00 0.00
Max 360057.67 21989.50 0.00 0.00 0.00
Average 78865.44 1469.47 0.00 0.00 0.00
Sum 1813905.17 33797.83 0.00 0.00 0.00


Heating SET Hours

SET ≤ 12.2°C Hours (°C) SET ≤ 12.2°C OccupantHours (°C) Longest SET ≤ 12.2°C Duration [hr] Start Time of the Longest SET ≤ 12.2°C Duration
None        


Cooling SET Hours

SET > 30°C Hours (°C) SET > 30°C OccupantHours (°C) Longest SET > 30°C Duration [hr] Start Time of the Longest SET > 30°C Duration
None        



Table of Contents

Report: Annual CO2 Resilience Summary

For: Entire Facility

Timestamp: 2023-10-16 08:43:24

CO2 Level Hours

Safe (<= 1000 ppm) [hr] Caution (> 1000, <= 5000 ppm) [hr] Hazard (> 5000 ppm) [hr]
None      


CO2 Level OccupantHours

Safe (<= 1000 ppm) [hr] Caution (> 1000, <= 5000 ppm) [hr] Hazard (> 5000 ppm) [hr]
None      



Table of Contents

Report: Annual Visual Resilience Summary

For: Entire Facility

Timestamp: 2023-10-16 08:43:24

Illuminance Level Hours

A Bit Dark (<= 100 lux) [hr] Dim (> 100, <= 300 lux) [hr] Adequate (> 300, <= 500 lux) [hr] Bright (>500 lux) [hr]
BASEMENT 0.00 0.00 0.00 0.00
CORE_BOTTOM 0.00 0.00 0.00 0.00
CORE_MID 0.00 0.00 0.00 0.00
CORE_TOP 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_3 0.00 0.00 8760.00 0.00
PERIMETER_BOT_ZN_2 0.00 0.00 8760.00 0.00
PERIMETER_BOT_ZN_1 0.00 0.00 8760.00 0.00
PERIMETER_BOT_ZN_4 0.00 0.00 8760.00 0.00
PERIMETER_MID_ZN_3 0.00 0.00 8760.00 0.00
PERIMETER_MID_ZN_2 0.00 0.00 8760.00 0.00
PERIMETER_MID_ZN_1 0.00 0.00 8760.00 0.00
PERIMETER_MID_ZN_4 0.00 0.00 8760.00 0.00
PERIMETER_TOP_ZN_3 0.00 0.00 8760.00 0.00
PERIMETER_TOP_ZN_2 0.00 0.00 8760.00 0.00
PERIMETER_TOP_ZN_1 0.00 0.00 8760.00 0.00
PERIMETER_TOP_ZN_4 0.00 0.00 8760.00 0.00
DATACENTER_BOT_ZN_6 0.00 0.00 0.00 0.00
DATACENTER_MID_ZN_6 0.00 0.00 0.00 0.00
DATACENTER_TOP_ZN_6 0.00 0.00 0.00 0.00
DATACENTER_BASEMENT_ZN_6 0.00 0.00 0.00 0.00
GROUNDFLOOR_PLENUM 0.00 0.00 0.00 0.00
MIDFLOOR_PLENUM 0.00 0.00 0.00 0.00
TOPFLOOR_PLENUM 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00
Max 0.00 0.00 8760.00 0.00
Average 0.00 0.00 4570.43 0.00
Sum 0.00 0.00 105120.00 0.00


Illuminance Level OccupantHours

A Bit Dark (<= 100 lux) [hr] Dim (> 100, <= 300 lux) [hr] Adequate (> 300, <= 500 lux) [hr] Bright (>500 lux) [hr]
BASEMENT 0.00 0.00 0.00 0.00
CORE_BOTTOM 0.00 0.00 0.00 0.00
CORE_MID 0.00 0.00 0.00 0.00
CORE_TOP 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_3 0.00 0.00 38925.00 0.00
PERIMETER_BOT_ZN_2 0.00 0.00 24909.00 0.00
PERIMETER_BOT_ZN_1 0.00 0.00 38925.00 0.00
PERIMETER_BOT_ZN_4 0.00 0.00 24909.00 0.00
PERIMETER_MID_ZN_3 0.00 0.00 38925.00 0.00
PERIMETER_MID_ZN_2 0.00 0.00 18354.00 0.00
PERIMETER_MID_ZN_1 0.00 0.00 38925.00 0.00
PERIMETER_MID_ZN_4 0.00 0.00 24909.00 0.00
PERIMETER_TOP_ZN_3 0.00 0.00 38925.00 0.00
PERIMETER_TOP_ZN_2 0.00 0.00 24909.00 0.00
PERIMETER_TOP_ZN_1 0.00 0.00 38925.00 0.00
PERIMETER_TOP_ZN_4 0.00 0.00 24909.00 0.00
DATACENTER_BOT_ZN_6 0.00 0.00 0.00 0.00
DATACENTER_MID_ZN_6 0.00 0.00 0.00 0.00
DATACENTER_TOP_ZN_6 0.00 0.00 0.00 0.00
DATACENTER_BASEMENT_ZN_6 0.00 0.00 0.00 0.00
GROUNDFLOOR_PLENUM 0.00 0.00 0.00 0.00
MIDFLOOR_PLENUM 0.00 0.00 0.00 0.00
TOPFLOOR_PLENUM 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00
Max 0.00 0.00 38925.00 0.00
Average 0.00 0.00 16367.35 0.00
Sum 0.00 0.00 376449.00 0.00



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR

For: Environment

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January -3.40
February -4.23
March 2.667
April 7.472
May 13.731
June 18.627
July 22.029
August 20.690
September 16.545
October 9.725
November 6.035
December -2.18
   
Annual Sum or Average 9.049
Minimum of Months -4.23
Maximum of Months 22.029



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901

For: Environment

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January -3.40
February -4.23
March 2.667
April 7.472
May 13.731
June 18.627
July 22.029
August 20.690
September 16.545
October 9.725
November 6.035
December -2.18
   
Annual Sum or Average 9.049
Minimum of Months -4.23
Maximum of Months 22.029



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2013

For: Environment

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January -3.40
February -4.23
March 2.667
April 7.472
May 13.731
June 18.627
July 22.029
August 20.690
September 16.545
October 9.725
November 6.035
December -2.18
   
Annual Sum or Average 9.049
Minimum of Months -4.23
Maximum of Months 22.029



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND

For: Environment

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January -3.40
February -4.23
March 2.667
April 7.472
May 13.731
June 18.627
July 22.029
August 20.690
September 16.545
October 9.725
November 6.035
December -2.18
   
Annual Sum or Average 9.049
Minimum of Months -4.23
Maximum of Months 22.029



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICELARGE

For: Environment

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January -3.40
February -4.23
March 2.667
April 7.472
May 13.731
June 18.627
July 22.029
August 20.690
September 16.545
October 9.725
November 6.035
December -2.18
   
Annual Sum or Average 9.049
Minimum of Months -4.23
Maximum of Months 22.029



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL

For: Environment

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January -3.40
February -4.23
March 2.667
April 7.472
May 13.731
June 18.627
July 22.029
August 20.690
September 16.545
October 9.725
November 6.035
December -2.18
   
Annual Sum or Average 9.049
Minimum of Months -4.23
Maximum of Months 22.029



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL

For: Environment

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January -3.40
February -4.23
March 2.667
April 7.472
May 13.731
June 18.627
July 22.029
August 20.690
September 16.545
October 9.725
November 6.035
December -2.18
   
Annual Sum or Average 9.049
Minimum of Months -4.23
Maximum of Months 22.029



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 5A

For: Environment

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January -3.40
February -4.23
March 2.667
April 7.472
May 13.731
June 18.627
July 22.029
August 20.690
September 16.545
October 9.725
November 6.035
December -2.18
   
Annual Sum or Average 9.049
Minimum of Months -4.23
Maximum of Months 22.029



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_NY_BUFFALO

For: Environment

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January -3.40
February -4.23
March 2.667
April 7.472
May 13.731
June 18.627
July 22.029
August 20.690
September 16.545
October 9.725
November 6.035
December -2.18
   
Annual Sum or Average 9.049
Minimum of Months -4.23
Maximum of Months 22.029



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: BASEMENT

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.455789E+11 115408.75 02-JAN-04:01 -1.0 -1.9 0.557820E+10 7499.17 11-JAN-10:09 7.98 6.90
February 0.418127E+11 114069.02 21-FEB-04:01 -11.2 -12.4 0.504605E+10 7499.20 28-FEB-10:30 -3.0 -4.8
March 0.554048E+11 115195.23 13-MAR-04:11 10.37 10.02 0.612145E+10 7499.30 14-MAR-09:50 18.77 16.25
April 0.544780E+11 119345.66 10-APR-04:12 3.50 2.94 0.544720E+10 7499.28 19-APR-09:20 9.07 6.91
May 0.573564E+11 117955.39 30-MAY-04:12 12.20 11.68 0.589970E+10 7499.22 24-MAY-09:20 12.20 11.68
June 0.620234E+11 115054.10 13-JUN-04:12 9.63 9.05 0.588180E+10 7499.52 22-JUN-13:20 20.60 15.30
July 0.632541E+11 123217.92 03-JUL-04:11 11.70 11.07 0.547401E+10 7499.06 27-JUL-13:09 29.40 22.00
August 0.710156E+11 115964.00 01-AUG-04:12 12.23 11.69 0.613850E+10 7529.93 14-AUG-09:00 23.90 22.00
September 0.621737E+11 118950.68 18-SEP-04:12 10.20 9.28 0.545263E+10 7499.50 12-SEP-13:20 10.20 9.28
October 0.618174E+11 119181.64 16-OCT-03:01 0.68 0.41 0.566930E+10 7499.21 30-OCT-13:00 15.00 8.94
November 0.582137E+11 118547.96 20-NOV-05:11 5.00 4.72 0.561279E+10 7499.20 16-NOV-14:20 5.00 4.72
December 0.517478E+11 118832.76 26-DEC-04:01 -11.8 -12.8 0.545481E+10 7499.17 04-DEC-14:30 -11.8 -12.8
                     
Annual Sum or Average 0.684877E+12         0.677764E+11        
Minimum of Months 0.418127E+11 114069.02   -11.8 -12.8 0.504605E+10 7499.06   -11.8 -12.8
Maximum of Months 0.710156E+11 123217.92   12.23 11.69 0.613850E+10 7529.93   29.40 22.00



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: CORE_BOTTOM

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.330475E+11 82566.51 19-JAN-06:01 1.10 -0.1 0.501096E+10 6735.63 06-JAN-14:09 1.10 -0.1
February 0.315125E+11 85691.33 23-FEB-06:01 2.30 1.81 0.455958E+10 6891.12 28-FEB-10:50 -2.5 -4.4
March 0.486312E+11 97498.08 16-MAR-04:13 18.13 13.40 0.549630E+10 6978.91 07-MAR-10:50 18.13 13.40
April 0.528084E+11 98197.65 10-APR-04:12 3.50 2.94 0.488345E+10 6747.53 14-APR-09:20 2.80 2.15
May 0.531189E+11 99825.77 30-MAY-04:12 12.20 11.68 0.528666E+10 6734.89 10-MAY-09:09 12.20 11.68
June 0.620741E+11 98336.80 02-JUN-04:13 20.00 17.45 0.526925E+10 6735.14 22-JUN-13:09 20.60 15.40
July 0.688661E+11 100974.50 24-JUL-04:13 16.10 15.07 0.489453E+10 6734.83 12-JUL-09:00 16.10 15.07
August 0.758850E+11 97883.24 22-AUG-04:13 14.40 12.82 0.549584E+10 6735.27 02-AUG-13:09 14.40 12.82
September 0.535139E+11 100262.74 18-SEP-04:12 10.20 9.28 0.488270E+10 6735.16 12-SEP-13:09 10.20 9.28
October 0.499280E+11 96499.49 23-OCT-04:12 12.77 10.74 0.507864E+10 6776.50 24-OCT-09:20 2.97 0.67
November 0.463099E+11 97505.41 06-NOV-05:12 8.90 6.96 0.502941E+10 6771.80 24-NOV-10:00 1.10 -0.6
December 0.402725E+11 89232.79 15-DEC-05:11 2.60 2.09 0.488698E+10 6834.18 11-DEC-14:50 2.60 2.09
                     
Annual Sum or Average 0.615968E+12         0.607743E+11        
Minimum of Months 0.315125E+11 82566.51   1.10 -0.1 0.455958E+10 6734.83   -2.5 -4.4
Maximum of Months 0.758850E+11 100974.50   20.00 17.45 0.549630E+10 6978.91   20.60 15.40



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: CORE_MID

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.232517E+11 23590.05 20-JAN-17:15 -1.5 -4.2 0.435974E+10 6549.47 06-JAN-14:00 -1.5 -4.2
February 0.222195E+11 53399.58 24-FEB-16:15 -2.6 -4.4 0.400112E+10 6748.06 24-FEB-16:19 -2.6 -4.4
March 0.315012E+11 83131.35 17-MAR-05:02 10.50 9.94 0.527015E+10 6984.55 03-MAR-11:09 10.50 9.94
April 0.331687E+11 79775.53 21-APR-05:02 2.80 1.46 0.479743E+10 6784.45 11-APR-09:00 2.80 1.46
May 0.425281E+11 85187.76 30-MAY-04:12 12.20 11.68 0.526471E+10 6734.88 10-MAY-09:09 12.20 11.68
June 0.494537E+11 87644.23 30-JUN-04:12 16.50 15.77 0.526151E+10 6735.15 22-JUN-13:09 16.50 15.77
July 0.507633E+11 88472.70 18-JUL-04:11 17.60 17.00 0.489192E+10 6734.80 03-JUL-13:30 17.60 17.00
August 0.530706E+11 88254.89 09-AUG-04:11 16.47 13.64 0.549419E+10 6735.24 02-AUG-13:09 16.47 13.64
September 0.433689E+11 88732.75 18-SEP-04:12 10.20 9.28 0.486770E+10 6735.17 12-SEP-13:09 10.20 9.28
October 0.341928E+11 83650.27 13-OCT-05:02 10.50 10.16 0.501005E+10 6942.34 17-OCT-09:20 3.53 0.77
November 0.280153E+11 62572.44 01-NOV-05:03 5.68 3.03 0.487365E+10 6861.32 03-NOV-09:30 4.75 2.42
December 0.244156E+11 34908.43 04-DEC-14:08 0.00 -2.9 0.435046E+10 6734.54 01-DEC-10:00 0.00 -2.9
                     
Annual Sum or Average 0.435949E+12         0.584426E+11        
Minimum of Months 0.222195E+11 23590.05   -2.6 -4.4 0.400112E+10 6549.47   -2.6 -4.4
Maximum of Months 0.530706E+11 88732.75   17.60 17.00 0.549419E+10 6984.55   17.60 17.00



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: CORE_TOP

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.165106E+11 17914.88 11-JAN-17:00 11.10 9.84 0.399605E+10 6043.96 19-JAN-14:00 1.10 -0.2
February 0.162852E+11 18485.71 17-FEB-17:00 1.10 0.20 0.369934E+10 6237.75 17-FEB-14:00 1.10 0.20
March 0.260066E+11 80708.17 16-MAR-05:03 14.03 11.42 0.486116E+10 6734.90 16-MAR-13:00 18.90 15.16
April 0.279595E+11 41251.49 21-APR-16:00 13.30 8.77 0.456321E+10 6758.91 13-APR-13:20 13.30 8.77
May 0.388485E+11 80258.97 17-MAY-05:02 16.05 11.54 0.519450E+10 6735.34 11-MAY-09:09 16.05 11.54
June 0.498864E+11 87980.02 19-JUN-04:12 16.70 15.97 0.524788E+10 6735.14 22-JUN-13:09 20.60 15.40
July 0.530924E+11 87014.28 05-JUL-04:11 18.67 16.56 0.489115E+10 6734.79 12-JUL-09:00 20.60 14.64
August 0.533441E+11 86970.72 11-AUG-04:12 18.53 15.89 0.548688E+10 6735.23 02-AUG-13:09 18.53 15.89
September 0.396207E+11 84583.80 18-SEP-04:12 10.20 9.28 0.482093E+10 6735.14 12-SEP-13:09 10.20 9.28
October 0.275816E+11 69174.32 13-OCT-05:02 10.50 10.16 0.472412E+10 6734.68 12-OCT-13:00 10.50 10.16
November 0.213749E+11 28729.58 01-NOV-15:20 9.40 6.48 0.439460E+10 6734.79 16-NOV-14:09 17.20 13.27
December 0.176969E+11 18997.54 01-DEC-17:00 7.20 4.89 0.390011E+10 6369.16 01-DEC-14:00 7.20 4.89
                     
Annual Sum or Average 0.388207E+12         0.557799E+11        
Minimum of Months 0.162852E+11 17914.88   1.10 0.20 0.369934E+10 6043.96   1.10 -0.2
Maximum of Months 0.533441E+11 87980.02   18.67 16.56 0.548688E+10 6758.91   20.60 15.89



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.127401E+10 2246.69 17-JAN-16:40 7.80 6.69 0.489114E+09 758.09 17-JAN-14:00 7.80 6.69
February 0.139414E+10 2929.02 28-FEB-12:00 -1.1 -3.7 0.457724E+09 771.73 17-FEB-14:39 -1.1 -3.7
March 0.349806E+10 8943.28 16-MAR-04:11 18.13 13.40 0.624486E+09 845.65 16-MAR-13:00 18.90 15.16
April 0.455415E+10 7188.60 07-APR-13:30 20.00 10.05 0.594603E+09 845.64 21-APR-13:00 14.40 8.43
May 0.614451E+10 9016.56 24-MAY-05:03 18.80 15.75 0.658032E+09 845.64 10-MAY-09:09 18.80 15.75
June 0.944175E+10 17495.76 25-JUN-18:21 26.15 17.91 0.661531E+09 845.68 22-JUN-13:09 26.15 17.91
July 0.112800E+11 17476.46 02-JUL-18:21 23.35 16.56 0.615551E+09 846.01 20-JUL-13:20 30.00 23.48
August 0.112586E+11 17693.09 06-AUG-16:21 27.80 18.95 0.690186E+09 846.59 14-AUG-13:09 26.47 20.73
September 0.629908E+10 11925.49 15-SEP-05:02 18.30 16.87 0.608411E+09 845.68 12-SEP-13:09 18.30 16.87
October 0.417968E+10 6051.42 12-OCT-12:10 17.20 13.87 0.614843E+09 845.63 03-OCT-09:00 17.20 13.87
November 0.310134E+10 4577.05 27-NOV-12:00 15.00 10.52 0.584628E+09 845.64 16-NOV-14:09 15.00 10.52
December 0.198106E+10 2841.23 15-DEC-14:30 2.80 1.33 0.500191E+09 829.56 01-DEC-14:09 2.80 1.33
                     
Annual Sum or Average 0.644065E+11         0.709930E+10        
Minimum of Months 0.127401E+10 2246.69   -1.1 -3.7 0.457724E+09 758.09   -1.1 -3.7
Maximum of Months 0.112800E+11 17693.09   27.80 18.95 0.690186E+09 846.59   30.00 23.48



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.131717E+10 2455.94 06-JAN-10:25 -6.4 -8.0 0.311826E+09 496.78 06-JAN-10:30 -6.4 -8.0
February 0.144644E+10 11738.36 28-FEB-10:10 -3.6 -5.3 0.295071E+09 564.89 28-FEB-10:09 -3.6 -5.3
March 0.373951E+10 10377.25 21-MAR-08:50 1.52 -0.7 0.403007E+09 559.95 07-MAR-10:30 1.52 -0.7
April 0.527362E+10 23638.48 23-APR-09:22 12.75 5.29 0.376662E+09 545.71 17-APR-09:20 12.75 5.29
May 0.697431E+10 14426.93 31-MAY-08:20 17.40 13.11 0.420231E+09 545.44 31-MAY-09:09 17.88 13.30
June 0.906705E+10 23634.19 25-JUN-09:02 20.97 14.96 0.425304E+09 545.80 20-JUN-09:30 20.97 14.96
July 0.103939E+11 27822.87 04-JUL-08:31 21.10 17.36 0.396016E+09 545.96 13-JUL-09:30 20.55 15.92
August 0.100116E+11 23679.95 06-AUG-09:01 24.18 17.35 0.442821E+09 546.14 04-AUG-09:39 24.18 17.35
September 0.664333E+10 22188.73 04-SEP-08:52 16.70 13.10 0.388713E+09 544.99 12-SEP-13:09 21.10 16.55
October 0.430189E+10 11220.39 11-OCT-08:50 14.53 11.11 0.389048E+09 544.97 03-OCT-09:00 14.53 11.11
November 0.294917E+10 6455.52 03-NOV-08:55 3.90 1.83 0.350996E+09 544.95 03-NOV-09:39 5.03 2.61
December 0.152262E+10 3645.43 04-DEC-09:45 -1.8 -3.7 0.302996E+09 544.64 04-DEC-10:09 -1.6 -3.7
                     
Annual Sum or Average 0.636406E+11         0.450269E+10        
Minimum of Months 0.131717E+10 2455.94   -6.4 -8.0 0.295071E+09 496.78   -6.4 -8.0
Maximum of Months 0.103939E+11 27822.87   24.18 17.36 0.442821E+09 564.89   24.18 17.35



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.272346E+10 16586.05 15-JAN-13:23 4.70 2.09 0.523616E+09 853.41 12-JAN-14:30 4.70 2.09
February 0.308926E+10 23094.91 28-FEB-12:00 -1.1 -3.7 0.491150E+09 900.68 28-FEB-10:50 -1.1 -3.7
March 0.715037E+10 23270.02 07-MAR-13:50 -2.9 -5.9 0.646538E+09 900.59 06-MAR-14:30 -2.9 -5.9
April 0.763839E+10 26932.35 23-APR-12:43 16.93 8.62 0.586723E+09 846.74 24-APR-13:00 12.80 6.89
May 0.873842E+10 26022.82 14-MAY-13:02 24.08 17.77 0.651182E+09 845.67 10-MAY-13:09 24.08 17.77
June 0.113348E+11 27098.42 25-JUN-13:02 26.10 17.26 0.659552E+09 845.71 22-JUN-13:09 26.10 17.26
July 0.139450E+11 27682.12 04-JUL-13:12 25.93 17.51 0.615327E+09 846.95 31-JUL-13:00 25.00 19.43
August 0.154124E+11 27739.48 06-AUG-16:21 27.80 18.95 0.689798E+09 846.83 03-AUG-13:00 27.80 18.95
September 0.114155E+11 27777.75 10-SEP-12:42 17.12 10.59 0.607239E+09 847.34 22-SEP-13:00 23.90 15.30
October 0.842693E+10 27059.54 09-OCT-11:23 11.40 7.02 0.616016E+09 891.02 31-OCT-13:09 15.00 10.18
November 0.528461E+10 18957.35 03-NOV-12:20 8.17 4.43 0.573188E+09 846.41 15-NOV-14:20 11.30 6.41
December 0.291515E+10 16290.91 04-DEC-11:30 -0.6 -3.1 0.507873E+09 868.93 11-DEC-14:50 -8.2 -9.3
                     
Annual Sum or Average 0.980743E+11         0.716820E+10        
Minimum of Months 0.272346E+10 16290.91   -2.9 -5.9 0.491150E+09 845.67   -8.2 -9.3
Maximum of Months 0.154124E+11 27777.75   27.80 18.95 0.689798E+09 900.68   27.80 19.43



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.225766E+10 4192.03 12-JAN-15:30 -5.8 -8.2 0.321083E+09 531.68 12-JAN-14:00 -5.8 -8.2
February 0.287181E+10 9476.91 28-FEB-16:30 0.00 -2.6 0.310349E+09 544.95 28-FEB-14:50 0.00 -2.6
March 0.630957E+10 23923.56 16-MAR-04:11 18.13 13.40 0.424719E+09 546.53 06-MAR-14:30 18.13 13.40
April 0.849896E+10 28777.83 02-APR-16:12 7.77 5.85 0.392808E+09 545.90 14-APR-09:20 2.80 2.15
May 0.860911E+10 31840.60 07-MAY-17:11 14.63 5.67 0.423009E+09 544.96 10-MAY-09:09 18.68 14.82
June 0.126590E+11 32758.36 25-JUN-17:41 26.78 18.33 0.427183E+09 545.00 22-JUN-13:09 26.78 18.33
July 0.149601E+11 35902.43 02-JUL-17:01 24.82 16.94 0.397710E+09 544.99 03-JUL-13:30 25.00 16.74
August 0.162517E+11 34000.93 06-AUG-16:21 27.80 18.95 0.446087E+09 545.02 02-AUG-13:09 27.80 18.95
September 0.813028E+10 28834.60 04-SEP-16:52 18.30 12.88 0.391821E+09 545.00 12-SEP-13:09 21.10 16.55
October 0.614209E+10 14386.47 11-OCT-16:00 21.70 14.52 0.399517E+09 544.96 12-OCT-13:00 18.30 14.87
November 0.485138E+10 11673.30 27-NOV-05:12 17.97 12.28 0.389572E+09 544.97 16-NOV-14:09 17.97 12.28
December 0.386958E+10 7615.44 04-DEC-15:30 -0.3 -3.1 0.354064E+09 544.95 04-DEC-14:30 -0.3 -3.1
                     
Annual Sum or Average 0.954113E+11         0.467792E+10        
Minimum of Months 0.225766E+10 4192.03   -5.8 -8.2 0.310349E+09 531.68   -5.8 -8.2
Maximum of Months 0.162517E+11 35902.43   27.80 18.95 0.446087E+09 546.53   27.80 18.95



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 69295510.27 1706.87 21-JAN-17:25 -1.4 -3.1 0.463902E+09 625.89 23-JAN-10:09 -7.0 -8.8
February 0.104726E+09 2091.65 14-FEB-15:53 1.10 -3.0 0.420969E+09 630.64 17-FEB-14:50 3.22 1.00
March 0.158184E+10 6313.43 15-MAR-14:00 26.10 16.06 0.549447E+09 845.64 16-MAR-13:00 18.90 15.16
April 0.246123E+10 4526.18 07-APR-13:50 20.00 10.11 0.524635E+09 845.63 21-APR-13:00 14.40 8.43
May 0.454563E+10 7413.33 23-MAY-14:40 23.90 13.32 0.638466E+09 845.63 17-MAY-09:00 23.90 13.32
June 0.758741E+10 11385.95 18-JUN-15:01 25.55 20.06 0.658115E+09 845.68 22-JUN-13:09 20.60 15.40
July 0.883562E+10 16800.86 16-JUL-16:31 28.33 21.22 0.614969E+09 845.73 20-JUL-13:39 30.00 23.72
August 0.811031E+10 11613.27 07-AUG-04:11 20.00 18.50 0.687316E+09 845.69 02-AUG-13:09 20.00 18.50
September 0.485551E+10 7391.59 15-SEP-14:00 25.60 21.03 0.594098E+09 845.68 12-SEP-13:09 25.60 21.03
October 0.258182E+10 4227.11 05-OCT-14:30 18.90 12.54 0.549429E+09 845.62 12-OCT-13:00 18.30 14.87
November 0.127202E+10 3126.91 08-NOV-16:10 5.68 5.18 0.484933E+09 789.89 16-NOV-14:00 17.20 13.27
December 0.174262E+09 1843.80 01-DEC-13:30 11.10 9.57 0.448548E+09 676.64 01-DEC-14:09 8.12 6.69
                     
Annual Sum or Average 0.421797E+11         0.663483E+10        
Minimum of Months 69295510.27 1706.87   -1.4 -3.1 0.420969E+09 625.89   -7.0 -8.8
Maximum of Months 0.883562E+10 16800.86   28.33 21.22 0.687316E+09 845.73   30.00 23.72



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.126003E+09 2020.25 21-JAN-17:25 -1.4 -3.1 0.219201E+09 388.31 06-JAN-09:00 -1.4 -3.1
February 0.366102E+09 2954.32 28-FEB-10:00 -3.9 -5.5 0.200984E+09 519.58 28-FEB-09:00 -3.9 -5.5
March 0.231317E+10 6995.60 14-MAR-10:30 20.80 17.14 0.266343E+09 521.22 14-MAR-10:09 20.80 17.14
April 0.401319E+10 14043.16 24-APR-07:40 4.27 2.13 0.257026E+09 529.64 06-APR-08:00 4.27 2.13
May 0.639667E+10 25052.15 21-MAY-09:22 16.40 11.86 0.299637E+09 537.10 08-MAY-07:30 16.40 11.86
June 0.870282E+10 27497.53 11-JUN-08:51 23.30 16.13 0.310033E+09 521.42 20-JUN-08:09 19.37 15.57
July 0.969737E+10 29958.60 04-JUL-08:31 21.10 17.36 0.291795E+09 521.59 10-JUL-08:09 20.28 17.18
August 0.894673E+10 21035.82 20-AUG-09:22 20.00 14.29 0.323477E+09 522.25 02-AUG-08:00 20.00 14.29
September 0.613013E+10 20003.58 04-SEP-09:12 17.07 13.15 0.278805E+09 521.24 12-SEP-12:20 20.77 15.37
October 0.319064E+10 9738.38 17-OCT-08:50 2.23 -0.3 0.261679E+09 521.88 17-OCT-10:09 5.18 2.15
November 0.130855E+10 4009.01 03-NOV-09:05 4.18 2.03 0.227936E+09 521.20 03-NOV-10:30 6.15 3.28
December 0.151361E+09 2092.19 04-DEC-10:00 -1.7 -3.7 0.211628E+09 406.75 04-DEC-09:00 -1.7 -3.7
                     
Annual Sum or Average 0.513427E+11         0.314854E+10        
Minimum of Months 0.126003E+09 2020.25   -3.9 -5.5 0.200984E+09 388.31   -3.9 -5.5
Maximum of Months 0.969737E+10 29958.60   23.30 17.36 0.323477E+09 537.10   20.80 17.18



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.159484E+10 14072.27 12-JAN-13:40 -6.5 -9.0 0.499787E+09 845.65 12-JAN-14:50 -5.7 -8.2
February 0.202755E+10 18518.98 28-FEB-13:50 0.00 -3.0 0.460918E+09 878.20 14-FEB-15:50 0.00 -3.0
March 0.569593E+10 24424.88 01-MAR-15:45 1.02 -1.9 0.611939E+09 932.43 03-MAR-11:09 -2.7 -4.8
April 0.591175E+10 26980.37 23-APR-13:32 16.13 9.68 0.552716E+09 846.74 06-APR-09:00 16.13 9.68
May 0.779523E+10 27467.40 14-MAY-13:32 24.63 17.99 0.635943E+09 845.67 10-MAY-13:09 24.63 17.99
June 0.100027E+11 27377.08 18-JUN-13:02 26.02 20.50 0.654099E+09 845.71 22-JUN-13:09 20.60 15.40
July 0.118283E+11 28889.92 30-JUL-11:52 25.60 19.95 0.614002E+09 846.61 31-JUL-13:00 25.00 19.43
August 0.127839E+11 27247.09 13-AUG-13:42 30.00 22.88 0.686802E+09 846.53 03-AUG-13:00 30.00 22.88
September 0.109658E+11 29493.15 03-SEP-12:32 19.03 12.28 0.599564E+09 872.33 21-SEP-13:30 25.30 16.56
October 0.741205E+10 27902.86 09-OCT-12:32 12.03 8.05 0.593597E+09 927.49 31-OCT-13:30 15.00 10.33
November 0.373807E+10 19793.08 03-NOV-12:30 8.35 4.56 0.528616E+09 874.05 03-NOV-09:50 8.35 4.56
December 0.124329E+10 20662.69 04-DEC-14:16 0.00 -2.9 0.468734E+09 884.78 04-DEC-14:30 0.00 -2.9
                     
Annual Sum or Average 0.809994E+11         0.690672E+10        
Minimum of Months 0.124329E+10 14072.27   -6.5 -9.0 0.460918E+09 845.65   -5.7 -8.2
Maximum of Months 0.127839E+11 29493.15   30.00 22.88 0.686802E+09 932.43   30.00 22.88



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.276051E+09 2572.42 12-JAN-16:00 -6.1 -8.3 0.300426E+09 451.91 12-JAN-16:19 -6.3 -8.3
February 0.509959E+09 5964.01 28-FEB-16:30 0.00 -2.6 0.275808E+09 522.68 24-FEB-16:19 0.00 -2.6
March 0.269340E+10 9225.37 01-MAR-15:45 1.02 -1.9 0.360681E+09 557.02 02-MAR-16:49 2.98 0.70
April 0.419137E+10 18468.20 02-APR-16:41 6.97 5.34 0.336493E+09 544.96 21-APR-13:00 14.40 8.43
May 0.666525E+10 29769.69 07-MAY-17:01 14.82 5.77 0.398882E+09 544.96 05-MAY-13:09 14.82 5.77
June 0.959163E+10 31883.93 11-JUN-16:51 25.60 17.82 0.419441E+09 544.99 22-JUN-13:09 20.60 15.40
July 0.101027E+11 30736.65 16-JUL-16:31 28.33 21.22 0.395021E+09 544.98 03-JUL-13:30 28.33 21.22
August 0.963656E+10 27814.39 06-AUG-16:31 27.80 18.98 0.440207E+09 545.01 02-AUG-13:09 27.80 18.98
September 0.621939E+10 26968.58 03-SEP-16:32 18.70 12.33 0.373989E+09 544.99 12-SEP-13:09 21.10 16.55
October 0.351781E+10 12119.40 11-OCT-16:00 21.70 14.52 0.347114E+09 544.95 12-OCT-13:00 18.30 14.87
November 0.171183E+10 4870.95 15-NOV-15:20 11.70 6.66 0.313627E+09 544.93 15-NOV-14:00 11.70 6.66
December 0.373651E+09 4871.42 04-DEC-14:08 0.00 -2.9 0.290042E+09 471.56 04-DEC-15:00 -0.6 -3.3
                     
Annual Sum or Average 0.554896E+11         0.425173E+10        
Minimum of Months 0.276051E+09 2572.42   -6.1 -8.3 0.275808E+09 451.91   -6.3 -8.3
Maximum of Months 0.101027E+11 31883.93   28.33 21.22 0.440207E+09 557.02   28.33 21.22



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 20257653.05 1491.11 14-JAN-17:03 3.22 2.72 0.462475E+09 625.94 23-JAN-10:30 -6.7 -8.5
February 33194065.42 1495.12 18-FEB-17:03 0.82 -0.6 0.418674E+09 625.95 07-FEB-10:50 0.82 -0.6
March 0.117730E+10 6879.72 15-MAR-14:30 25.85 16.15 0.535436E+09 845.64 16-MAR-13:00 18.90 15.16
April 0.194284E+10 4371.29 20-APR-15:40 14.80 10.94 0.500895E+09 845.62 21-APR-13:00 14.40 8.43
May 0.415512E+10 7666.34 23-MAY-14:40 23.90 13.32 0.618824E+09 845.63 10-MAY-13:39 23.90 13.32
June 0.760815E+10 18502.86 18-JUN-15:01 25.55 20.06 0.653341E+09 845.68 22-JUN-13:09 20.60 15.40
July 0.913772E+10 19491.52 16-JUL-16:31 28.33 21.22 0.614328E+09 845.75 21-JUL-13:20 30.97 21.96
August 0.817051E+10 16679.26 06-AUG-16:31 27.80 18.98 0.683736E+09 845.70 02-AUG-13:09 27.80 18.98
September 0.449324E+10 7787.66 15-SEP-14:00 25.60 21.03 0.578721E+09 845.68 12-SEP-13:09 25.60 21.03
October 0.190997E+10 4050.52 12-OCT-15:30 18.30 15.05 0.521003E+09 845.62 12-OCT-13:00 18.30 15.05
November 0.573368E+09 2207.88 16-NOV-17:00 18.30 13.48 0.468277E+09 752.86 16-NOV-14:00 18.30 13.48
December 64466571.60 1654.31 01-DEC-13:20 12.03 10.45 0.445716E+09 625.95 28-DEC-10:00 -10.6 -11.7
                     
Annual Sum or Average 0.392861E+11         0.650143E+10        
Minimum of Months 20257653.05 1491.11   0.82 -0.6 0.418674E+09 625.94   -10.6 -11.7
Maximum of Months 0.913772E+10 19491.52   28.33 21.22 0.683736E+09 845.75   30.97 21.96



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 38363920.51 1757.95 14-JAN-17:03 3.22 2.72 0.298695E+09 403.39 23-JAN-10:50 -6.3 -8.2
February 0.258824E+09 2699.98 28-FEB-10:10 -3.6 -5.3 0.272873E+09 506.17 28-FEB-10:20 -3.3 -5.1
March 0.185792E+10 6270.43 14-MAR-10:40 21.27 17.29 0.356450E+09 544.97 15-MAR-13:30 25.55 15.84
April 0.337587E+10 10816.62 24-APR-09:20 6.47 3.13 0.344242E+09 544.96 21-APR-13:00 6.47 3.13
May 0.597536E+10 17969.71 21-MAY-09:43 16.20 11.92 0.404886E+09 544.97 26-MAY-09:00 18.90 12.57
June 0.875458E+10 24358.98 18-JUN-10:22 25.30 21.06 0.421821E+09 545.94 12-JUN-09:00 25.30 21.06
July 0.998593E+10 28079.99 16-JUL-08:31 25.53 21.91 0.395828E+09 545.87 03-JUL-09:00 25.53 21.91
August 0.907534E+10 20771.61 06-AUG-09:12 24.47 17.45 0.440075E+09 545.92 10-AUG-09:00 27.80 20.31
September 0.579600E+10 15723.58 04-SEP-09:52 17.80 13.22 0.376763E+09 544.99 12-SEP-13:09 21.10 16.55
October 0.255237E+10 8449.38 11-OCT-09:30 15.85 11.81 0.346493E+09 544.96 03-OCT-09:00 15.85 11.81
November 0.740671E+09 2792.87 03-NOV-09:55 5.60 2.99 0.304018E+09 518.37 03-NOV-09:00 5.60 2.99
December 67647646.29 1969.86 16-DEC-06:04 -0.7 -1.3 0.288046E+09 403.39 12-DEC-10:09 -0.7 -1.3
                     
Annual Sum or Average 0.484789E+11         0.425019E+10        
Minimum of Months 38363920.51 1757.95   -3.6 -5.3 0.272873E+09 403.39   -6.3 -8.2
Maximum of Months 0.998593E+10 28079.99   25.53 21.91 0.440075E+09 545.94   27.80 21.91



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.111898E+10 12061.67 12-JAN-13:40 -6.5 -9.0 0.491014E+09 845.65 12-JAN-14:50 -5.7 -8.2
February 0.156096E+10 17695.30 28-FEB-13:50 0.00 -3.0 0.451948E+09 845.64 10-FEB-14:50 0.00 -3.0
March 0.482571E+10 20243.56 15-MAR-13:30 25.55 15.84 0.592342E+09 846.69 14-MAR-13:00 25.55 15.84
April 0.509544E+10 20600.09 23-APR-14:31 15.20 9.59 0.532555E+09 886.75 05-APR-13:20 15.20 9.59
May 0.729591E+10 29272.18 14-MAY-14:02 25.18 18.10 0.618573E+09 845.68 10-MAY-13:39 25.18 18.10
June 0.100944E+11 29455.86 18-JUN-13:02 26.02 20.50 0.647640E+09 845.71 22-JUN-13:09 20.60 15.40
July 0.122198E+11 31002.17 30-JUL-11:52 25.60 19.95 0.611645E+09 846.78 31-JUL-13:00 25.00 19.43
August 0.129210E+11 29120.56 13-AUG-15:02 29.90 23.27 0.681875E+09 846.69 03-AUG-13:00 29.90 23.27
September 0.104489E+11 29923.71 10-SEP-13:22 17.20 10.61 0.587845E+09 852.23 21-SEP-13:30 25.30 16.56
October 0.627033E+10 23876.85 31-OCT-13:30 15.00 10.33 0.569521E+09 878.57 31-OCT-13:39 15.00 10.41
November 0.261866E+10 17801.91 03-NOV-12:40 8.53 4.68 0.508616E+09 845.64 01-NOV-13:39 8.53 4.68
December 0.854097E+09 10754.68 16-DEC-13:30 5.60 3.03 0.460269E+09 845.65 04-DEC-14:30 5.60 3.03
                     
Annual Sum or Average 0.753243E+11         0.675384E+10        
Minimum of Months 0.854097E+09 10754.68   -6.5 -9.0 0.451948E+09 845.64   -5.7 -8.2
Maximum of Months 0.129210E+11 31002.17   29.90 23.27 0.681875E+09 886.75   29.90 23.27



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.151133E+09 2493.80 12-JAN-16:00 -6.1 -8.3 0.299319E+09 428.16 12-JAN-15:00 -6.1 -8.3
February 0.366521E+09 5829.94 28-FEB-16:30 0.00 -2.6 0.274518E+09 521.19 28-FEB-16:49 -0.4 -2.9
March 0.226971E+10 8579.38 21-MAR-16:00 4.40 1.34 0.353016E+09 544.96 15-MAR-13:30 4.40 1.34
April 0.366091E+10 13026.82 19-APR-16:00 17.20 8.76 0.325469E+09 544.96 21-APR-13:00 14.40 8.43
May 0.638022E+10 27995.91 07-MAY-16:42 15.00 5.89 0.386371E+09 544.97 10-MAY-13:39 25.73 17.72
June 0.964490E+10 32104.07 18-JUN-17:01 23.22 18.52 0.414701E+09 544.99 22-JUN-13:09 20.60 15.40
July 0.103592E+11 34916.36 02-JUL-16:51 25.00 17.00 0.393066E+09 544.96 12-JUL-09:00 20.60 14.64
August 0.973447E+10 29145.90 06-AUG-16:31 27.80 18.98 0.436012E+09 545.01 02-AUG-13:09 27.80 18.98
September 0.598545E+10 27803.91 04-SEP-16:32 18.30 12.97 0.363609E+09 544.99 12-SEP-13:09 21.10 16.55
October 0.292422E+10 12238.90 11-OCT-16:00 21.70 14.52 0.334629E+09 544.95 12-OCT-13:00 18.30 14.87
November 0.108300E+10 4234.85 15-NOV-15:30 11.70 6.70 0.306800E+09 544.82 15-NOV-14:00 11.70 6.70
December 0.202441E+09 2653.52 04-DEC-15:50 -0.5 -3.2 0.288681E+09 445.69 04-DEC-15:00 -0.6 -3.3
                     
Annual Sum or Average 0.527622E+11         0.417619E+10        
Minimum of Months 0.151133E+09 2493.80   -6.1 -8.3 0.274518E+09 428.16   -6.1 -8.3
Maximum of Months 0.103592E+11 34916.36   27.80 18.98 0.436012E+09 545.01   27.80 18.98



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: GROUNDFLOOR_PLENUM

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.345504E+09 8147.05 24-JAN-05:01 -11.8 -13.0 0.00 0.00 01-JAN-00:10 -11.8 -13.0
February 0.328047E+09 8898.38 21-FEB-05:01 -12.0 -13.0 0.00 0.00 01-FEB-00:10 -12.0 -13.0
March 0.225199E+10 5828.88 16-MAR-05:15 13.67 11.27 0.00 0.00 01-MAR-00:10 13.67 11.27
April 0.399824E+10 6917.73 10-APR-05:08 3.98 3.28 0.00 0.00 01-APR-00:10 3.98 3.28
May 0.543723E+10 7918.92 30-MAY-05:15 12.20 11.93 0.00 0.00 01-MAY-00:10 12.20 11.93
June 0.842247E+10 9075.73 27-JUN-05:03 21.20 19.66 0.00 0.00 01-JUN-00:10 21.20 19.66
July 0.997363E+10 10669.62 05-JUL-05:15 19.23 16.66 0.00 0.00 01-JUL-00:10 19.23 16.66
August 0.103839E+11 12094.90 07-AUG-05:15 20.20 18.58 0.00 0.00 01-AUG-00:10 20.20 18.58
September 0.652156E+10 8620.40 18-SEP-05:15 9.60 8.73 0.00 0.00 01-SEP-00:10 9.60 8.73
October 0.400655E+10 6271.55 23-OCT-05:15 11.70 10.06 0.00 0.00 01-OCT-00:10 11.70 10.06
November 0.259859E+10 5417.22 06-NOV-06:15 8.90 6.78 0.00 0.00 01-NOV-00:10 8.90 6.78
December 0.607776E+09 7005.83 26-DEC-05:01 -12.2 -13.2 0.00 0.00 01-DEC-00:10 -12.2 -13.2
                     
Annual Sum or Average 0.548755E+11         0.00        
Minimum of Months 0.328047E+09 5417.22   -12.2 -13.2 0.00 0.00   -12.2 -13.2
Maximum of Months 0.103839E+11 12094.90   21.20 19.66 0.00 0.00   21.20 19.66



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: MIDFLOOR_PLENUM

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.374071E+09 9636.21 28-JAN-04:01 -6.3 -7.8 0.00 0.00 01-JAN-00:10 -6.3 -7.8
February 0.363717E+09 10167.11 25-FEB-04:01 -8.2 -9.1 0.00 0.00 01-FEB-00:10 -8.2 -9.1
March 0.897540E+09 10544.59 20-MAR-03:01 -2.3 -3.7 0.00 0.00 01-MAR-00:10 -2.3 -3.7
April 0.141002E+10 8515.84 17-APR-04:01 -3.4 -5.0 0.00 0.00 01-APR-00:10 -3.4 -5.0
May 0.330561E+10 5109.51 30-MAY-05:10 12.20 11.93 0.00 0.00 01-MAY-00:10 12.20 11.93
June 0.608809E+10 6940.07 29-JUN-15:30 26.15 19.78 0.00 0.00 01-JUN-00:10 26.15 19.78
July 0.751851E+10 7976.15 21-JUL-12:10 30.10 21.65 0.00 0.00 01-JUL-00:10 30.10 21.65
August 0.742872E+10 7824.48 09-AUG-15:20 29.40 18.24 0.00 0.00 01-AUG-00:10 29.40 18.24
September 0.462309E+10 6852.41 18-SEP-05:15 9.60 8.73 0.00 0.00 01-SEP-00:10 9.60 8.73
October 0.175484E+10 8797.02 30-OCT-04:01 -0.5 -1.2 0.00 0.00 01-OCT-00:10 -0.5 -1.2
November 0.634866E+09 9369.46 18-NOV-05:01 1.60 -0.5 0.00 0.00 01-NOV-00:10 1.60 -0.5
December 0.356207E+09 10855.82 07-DEC-04:01 -7.8 -8.1 0.00 0.00 01-DEC-00:10 -7.8 -8.1
                     
Annual Sum or Average 0.347553E+11         0.00        
Minimum of Months 0.356207E+09 5109.51   -8.2 -9.1 0.00 0.00   -8.2 -9.1
Maximum of Months 0.751851E+10 10855.82   30.10 21.65 0.00 0.00   30.10 21.65



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: TOPFLOOR_PLENUM

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:03 -1.0 -1.6 0.00 0.00 01-JAN-00:10 -1.0 -1.6
February 0.00 0.00 01-FEB-00:03 -3.3 -4.7 0.00 0.00 01-FEB-00:10 -3.3 -4.7
March 0.763817E+09 12412.37 15-MAR-14:10 26.02 16.09 0.00 0.00 01-MAR-00:10 26.02 16.09
April 0.215554E+10 10151.45 21-APR-14:20 14.60 8.38 0.00 0.00 01-APR-00:10 14.60 8.38
May 0.574088E+10 14715.39 31-MAY-14:20 21.70 14.12 0.00 0.00 01-MAY-00:10 21.70 14.12
June 0.107683E+11 19729.68 12-JUN-13:50 30.40 20.15 0.00 0.00 01-JUN-00:10 30.40 20.15
July 0.130625E+11 19989.93 21-JUL-13:40 31.33 21.85 0.00 0.00 01-JUL-00:10 31.33 21.85
August 0.115531E+11 19336.83 09-AUG-15:00 29.40 18.10 0.00 0.00 01-AUG-00:10 29.40 18.10
September 0.587823E+10 14945.49 21-SEP-15:40 26.10 17.00 0.00 0.00 01-SEP-00:10 26.10 17.00
October 0.130714E+10 8655.22 11-OCT-15:40 21.87 14.55 0.00 0.00 01-OCT-00:10 21.87 14.55
November 89602842.25 1740.93 16-NOV-13:10 18.62 13.01 0.00 0.00 01-NOV-00:10 18.62 13.01
December 0.00 0.00 01-DEC-00:10 4.95 3.07 0.00 0.00 01-DEC-00:10 4.95 3.07
                     
Annual Sum or Average 0.513192E+11         0.00        
Minimum of Months 0.00 0.00   -3.3 -4.7 0.00 0.00   -3.3 -4.7
Maximum of Months 0.130625E+11 19989.93   31.33 21.85 0.00 0.00   31.33 21.85



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.216183E+10 2078.95 12-JAN-16:40 -6.5 -8.3 95230014.83 126.82 12-JAN-10:09 -6.5 -8.3
February 0.686873E+10 4343.42 28-FEB-17:00 -0.6 -3.0 86396467.82 126.82 21-FEB-10:09 -0.6 -3.0
March 0.139338E+11 6988.66 31-MAR-24:00 4.20 3.93 0.103237E+09 126.83 14-MAR-09:00 4.20 3.93
April 0.188446E+11 8236.06 24-APR-18:00 11.70 8.10 91605125.07 126.82 28-APR-13:00 10.00 9.06
May 0.445620E+10 3500.12 31-MAY-24:00 17.10 14.03 99236276.24 126.85 17-MAY-13:00 17.10 14.03
June 0.955583E+10 5371.14 30-JUN-24:00 16.90 13.02 98966849.35 126.86 08-JUN-09:30 16.90 13.02
July 0.149778E+11 7271.88 31-JUL-23:47 19.37 17.14 91888435.12 126.84 05-JUL-13:00 19.37 17.14
August 0.200361E+11 8409.16 02-AUG-18:40 22.07 14.68 0.103238E+09 126.83 30-AUG-09:00 17.80 17.48
September 0.442637E+10 3200.52 30-SEP-24:00 14.40 12.09 91612319.54 126.86 13-SEP-13:00 14.40 12.09
October 0.918313E+10 5143.38 31-OCT-24:00 6.60 4.77 95232483.55 126.84 12-OCT-09:00 6.60 4.77
November 0.135508E+11 6017.13 24-NOV-16:20 3.87 1.42 94300307.22 126.82 06-NOV-10:30 3.87 1.42
December 0.183725E+11 7886.92 04-DEC-16:20 -1.1 -3.7 91880876.59 126.82 01-DEC-14:09 -1.1 -3.7
                     
Annual Sum or Average 0.136368E+12         0.114282E+10        
Minimum of Months 0.216183E+10 2078.95   -6.5 -8.3 86396467.82 126.82   -6.5 -8.3
Maximum of Months 0.200361E+11 8409.16   22.07 17.14 0.103238E+09 126.86   19.37 17.48



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: DATACENTER_MID_ZN_6

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.424657E+09 1626.97 12-JAN-16:50 -6.6 -8.3 93473700.84 126.82 12-JAN-10:00 -6.6 -8.3
February 0.407939E+10 3814.84 28-FEB-17:00 -0.6 -3.0 86396476.40 126.82 21-FEB-10:09 -0.6 -3.0
March 0.114659E+11 6109.13 31-MAR-23:40 4.40 4.06 0.103237E+09 126.83 14-MAR-13:00 4.40 4.06
April 0.167146E+11 7796.58 24-APR-18:00 11.70 8.10 91605156.61 126.82 28-APR-13:00 10.00 9.06
May 0.362860E+10 3285.38 31-MAY-24:00 17.10 14.03 99235935.76 126.85 17-MAY-13:39 17.10 14.03
June 0.883331E+10 5155.82 30-JUN-24:00 16.90 13.02 98967282.62 126.86 27-JUN-13:00 16.90 13.02
July 0.141660E+11 7019.53 31-JUL-23:57 19.10 16.93 91889611.67 126.85 05-JUL-13:00 19.10 16.93
August 0.189045E+11 8077.45 02-AUG-18:40 22.07 14.68 0.103239E+09 126.83 30-AUG-09:00 17.80 17.48
September 0.364900E+10 2621.98 30-SEP-24:00 14.40 12.09 91610333.36 126.85 26-SEP-13:00 14.40 12.09
October 0.737039E+10 4389.59 31-OCT-23:40 6.73 4.84 95232269.63 126.84 12-OCT-13:00 6.73 4.84
November 0.109671E+11 5508.60 15-NOV-16:20 10.93 6.40 94300324.02 126.82 06-NOV-10:30 10.93 6.40
December 0.145262E+11 7005.80 04-DEC-16:30 -1.4 -3.9 91880885.22 126.82 01-DEC-14:09 -1.4 -3.9
                     
Annual Sum or Average 0.114730E+12         0.114107E+10        
Minimum of Months 0.424657E+09 1626.97   -6.6 -8.3 86396476.40 126.82   -6.6 -8.3
Maximum of Months 0.189045E+11 8077.45   22.07 16.93 0.103239E+09 126.86   19.10 17.48



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.208986E+09 1455.11 12-JAN-16:40 -6.5 -8.3 90098540.73 127.38 18-JAN-10:20 2.40 1.12
February 0.284752E+10 3832.01 28-FEB-17:00 -0.6 -3.0 86395939.40 126.82 21-FEB-10:09 -0.6 -3.0
March 0.100237E+11 5766.17 21-MAR-17:40 3.50 0.63 0.103237E+09 126.83 14-MAR-13:00 3.50 0.63
April 0.157064E+11 7803.40 24-APR-18:00 11.70 8.10 91605161.51 126.82 28-APR-13:00 10.00 9.06
May 0.314561E+10 3188.68 31-MAY-23:30 17.20 13.94 99235935.04 126.85 17-MAY-13:30 17.20 13.94
June 0.870822E+10 5077.49 30-JUN-23:23 17.15 12.82 98967232.07 126.86 21-JUN-13:20 17.15 12.82
July 0.141765E+11 7004.62 31-JUL-23:57 19.10 16.93 91889453.78 126.85 19-JUL-09:39 19.10 16.93
August 0.188321E+11 8129.31 02-AUG-18:40 22.07 14.68 0.103239E+09 126.83 30-AUG-13:09 18.58 18.07
September 0.321051E+10 2454.42 04-SEP-17:42 16.97 12.18 91609898.81 126.85 08-SEP-13:00 22.80 18.10
October 0.606829E+10 4213.51 11-OCT-17:00 21.70 14.52 95232235.42 126.84 12-OCT-13:00 18.30 14.87
November 0.933813E+10 5429.25 15-NOV-16:30 10.55 6.20 94300323.05 126.82 06-NOV-10:30 10.55 6.20
December 0.128007E+11 6752.66 04-DEC-16:30 -1.4 -3.9 91880887.20 126.82 01-DEC-14:09 -1.4 -3.9
                     
Annual Sum or Average 0.105067E+12         0.113769E+10        
Minimum of Months 0.208986E+09 1455.11   -6.5 -8.3 86395939.40 126.82   -1.4 -3.9
Maximum of Months 0.188321E+11 8129.31   22.07 16.93 0.103239E+09 127.38   22.80 18.10



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.235123E+12 91319.39 12-JAN-16:55 -6.7 -8.2 0.206144E+10 2745.29 13-JAN-14:00 2.80 -2.4
February 0.432749E+12 183036.38 23-FEB-17:00 -0.6 -1.8 0.187025E+10 2745.32 01-FEB-10:09 -0.6 -1.8
March 0.727957E+12 358405.67 31-MAR-24:00 4.20 3.93 0.223489E+10 2748.33 14-MAR-09:50 4.20 3.93
April 0.942743E+12 368020.08 21-APR-16:00 13.30 8.77 0.198309E+10 2748.63 28-APR-09:09 10.00 8.84
May 0.240792E+12 176248.25 31-MAY-24:00 17.10 14.03 0.214807E+10 2745.62 10-MAY-13:09 17.10 14.03
June 0.471476E+12 268359.86 30-JUN-24:00 16.90 13.02 0.214249E+10 2748.92 20-JUN-09:00 16.90 13.02
July 0.732526E+12 360670.83 31-JUL-23:57 19.10 16.93 0.202770E+10 3297.18 21-JUL-09:09 19.10 16.93
August 0.976084E+12 376317.10 15-AUG-18:00 18.30 17.98 0.245362E+10 4201.32 15-AUG-13:09 18.30 17.98
September 0.236677E+12 175553.63 30-SEP-24:00 14.40 12.09 0.198300E+10 2746.46 21-SEP-13:09 14.40 12.09
October 0.487438E+12 268572.66 31-OCT-24:00 6.60 4.77 0.206145E+10 2746.29 05-OCT-13:30 6.60 4.77
November 0.708066E+12 276937.65 15-NOV-16:55 9.40 5.56 0.204142E+10 2748.08 16-NOV-14:00 17.20 13.27
December 0.973866E+12 367689.85 15-DEC-17:00 2.80 1.83 0.198902E+10 2749.26 01-DEC-10:00 2.80 1.83
                     
Annual Sum or Average 0.716549E+13         0.249965E+11        
Minimum of Months 0.235123E+12 91319.39   -6.7 -8.2 0.187025E+10 2745.29   -0.6 -2.4
Maximum of Months 0.976084E+12 376317.10   19.10 17.98 0.245362E+10 4201.32   19.10 17.98



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: BASEMENT

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 64602547.14 12202.30 31-JAN-06:04 -11.6
February 61026783.96 12282.40 01-FEB-06:05 7.02
March 89745298.26 12663.80 17-MAR-04:15 10.60
April 88576417.83 12759.35 03-APR-03:05 -1.8
May 0.149667E+09 13682.11 29-MAY-16:33 15.73
June 0.182114E+09 14828.63 17-JUN-16:02 28.40
July 0.357821E+09 14099.01 16-JUL-20:33 23.50
August 0.364177E+09 14374.63 27-AUG-17:01 22.20
September 0.373355E+09 13482.30 17-SEP-16:53 22.80
October 0.208886E+09 12783.52 24-OCT-03:15 0.40
November 0.197417E+09 12764.57 24-NOV-04:05 -3.2
December 87122953.09 14558.25 13-DEC-05:52 1.10
         
Annual Sum or Average 0.222451E+10      
Minimum of Months 61026783.96 12202.30   -11.6
Maximum of Months 0.373355E+09 14828.63   28.40



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: CORE_BOTTOM

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:03 -1.0
February 127966.31 426.55 28-FEB-10:05 -3.6
March 0.00 0.00 01-MAR-00:10 -4.9
April 0.00 0.00 01-APR-00:10 4.10
May 0.00 0.00 01-MAY-00:10 6.67
June 0.00 0.00 01-JUN-00:10 17.05
July 0.00 0.00 01-JUL-00:10 16.82
August 0.00 0.00 01-AUG-00:03 18.85
September 0.00 0.00 01-SEP-00:10 14.65
October 0.00 0.00 01-OCT-00:10 14.42
November 0.00 0.00 01-NOV-00:10 6.53
December 0.00 0.00 01-DEC-00:10 4.95
         
Annual Sum or Average 127966.31      
Minimum of Months 0.00 0.00   -4.9
Maximum of Months 127966.31 426.55   18.85



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: CORE_MID

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.870798E+09 56243.53 02-JAN-04:01 -1.0
February 0.344186E+09 47342.28 27-FEB-05:01 -2.2
March 42617268.93 43972.27 06-MAR-06:02 -11.1
April 0.00 0.00 01-APR-00:10 4.10
May 0.00 0.00 01-MAY-00:10 6.67
June 0.00 0.00 01-JUN-00:10 17.05
July 0.00 0.00 01-JUL-00:10 16.82
August 0.00 0.00 01-AUG-00:03 18.85
September 0.00 0.00 01-SEP-00:10 14.65
October 0.00 0.00 01-OCT-00:10 14.42
November 0.00 0.00 01-NOV-00:10 6.53
December 0.263979E+09 48606.87 11-DEC-05:11 -17.8
         
Annual Sum or Average 0.152158E+10      
Minimum of Months 0.00 0.00   -17.8
Maximum of Months 0.870798E+09 56243.53   18.85



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: CORE_TOP

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.551545E+10 84144.69 02-JAN-04:01 -1.0
February 0.462621E+10 83298.49 21-FEB-04:01 -11.2
March 0.172561E+10 80778.54 06-MAR-04:01 -11.1
April 0.361848E+09 75933.98 17-APR-04:01 -3.4
May 0.00 0.00 01-MAY-00:10 6.67
June 0.00 0.00 01-JUN-00:10 17.05
July 0.00 0.00 01-JUL-00:10 16.82
August 0.00 0.00 01-AUG-00:03 18.85
September 0.00 0.00 01-SEP-00:10 14.65
October 0.345791E+09 74712.69 30-OCT-04:01 -0.5
November 0.935277E+09 76885.66 20-NOV-05:11 5.00
December 0.426194E+10 84140.54 26-DEC-04:01 -11.8
         
Annual Sum or Average 0.177721E+11      
Minimum of Months 0.00 0.00   -11.8
Maximum of Months 0.551545E+10 84144.69   18.85



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.899440E+09 13586.37 30-JAN-05:01 -9.5
February 0.746120E+09 13982.95 06-FEB-04:01 -15.0
March 0.113272E+09 12834.91 06-MAR-05:01 -11.1
April 0.00 0.00 01-APR-00:10 4.10
May 0.00 0.00 01-MAY-00:10 6.67
June 0.00 0.00 01-JUN-00:10 17.05
July 0.00 0.00 01-JUL-00:10 16.82
August 0.00 0.00 01-AUG-00:03 18.85
September 0.00 0.00 01-SEP-00:10 14.65
October 0.00 0.00 01-OCT-00:10 14.42
November 48201.90 241.01 18-NOV-09:17 2.57
December 0.315342E+09 13204.03 11-DEC-05:01 -17.5
         
Annual Sum or Average 0.207422E+10      
Minimum of Months 0.00 0.00   -17.5
Maximum of Months 0.899440E+09 13982.95   18.85



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.650821E+09 13943.32 30-JAN-05:01 -9.5
February 0.587559E+09 14558.64 06-FEB-04:01 -15.0
March 83522602.22 13111.27 06-MAR-05:01 -11.1
April 741273.58 3590.19 17-APR-05:02 -4.0
May 0.00 0.00 01-MAY-00:10 6.67
June 0.00 0.00 01-JUN-00:10 17.05
July 0.00 0.00 01-JUL-00:10 16.82
August 0.00 0.00 01-AUG-00:03 18.85
September 0.00 0.00 01-SEP-00:10 14.65
October 85773.50 562.68 30-OCT-05:03 -0.1
November 5258476.48 9003.51 25-NOV-06:01 -1.7
December 0.412629E+09 13874.19 11-DEC-05:01 -17.5
         
Annual Sum or Average 0.174062E+10      
Minimum of Months 0.00 0.00   -17.5
Maximum of Months 0.650821E+09 14558.64   18.85



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.114262E+10 20679.12 30-JAN-04:01 -9.9
February 0.105372E+10 21536.66 06-FEB-04:01 -15.0
March 0.165414E+09 19293.80 06-MAR-05:01 -11.1
April 7810683.01 15855.92 17-APR-05:02 -4.0
May 0.00 0.00 01-MAY-00:10 6.67
June 0.00 0.00 01-JUN-00:10 17.05
July 0.00 0.00 01-JUL-00:10 16.82
August 0.00 0.00 01-AUG-00:03 18.85
September 0.00 0.00 01-SEP-00:10 14.65
October 5600437.41 10687.09 30-OCT-05:03 -0.1
November 23822726.81 16296.04 24-NOV-06:01 -3.8
December 0.588994E+09 20690.56 26-DEC-04:01 -11.8
         
Annual Sum or Average 0.298799E+10      
Minimum of Months 0.00 0.00   -15.0
Maximum of Months 0.114262E+10 21536.66   18.85



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.195534E+09 12239.04 30-JAN-05:01 -9.5
February 0.110075E+09 12512.39 06-FEB-05:01 -14.8
March 1451984.46 7300.77 07-MAR-06:01 -13.3
April 0.00 0.00 01-APR-00:10 4.10
May 0.00 0.00 01-MAY-00:10 6.67
June 0.00 0.00 01-JUN-00:10 17.05
July 0.00 0.00 01-JUL-00:10 16.82
August 0.00 0.00 01-AUG-00:03 18.85
September 0.00 0.00 01-SEP-00:10 14.65
October 0.00 0.00 01-OCT-00:10 14.42
November 11165.82 55.83 18-NOV-09:17 2.57
December 7173196.69 10402.22 11-DEC-06:01 -18.5
         
Annual Sum or Average 0.314246E+09      
Minimum of Months 0.00 0.00   -18.5
Maximum of Months 0.195534E+09 12512.39   18.85



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.738971E+10 15207.03 29-JAN-22:22 -9.2
February 0.639721E+10 15382.33 06-FEB-04:21 -15.0
March 0.222895E+10 14501.58 06-MAR-03:42 -11.0
April 0.323837E+09 13479.64 17-APR-03:02 -2.9
May 942945.28 5595.52 08-MAY-05:03 3.40
June 0.00 0.00 01-JUN-00:10 17.05
July 0.00 0.00 01-JUL-00:10 16.82
August 0.00 0.00 01-AUG-00:03 18.85
September 293173.47 1954.49 30-SEP-05:03 7.20
October 0.208374E+09 12940.73 30-OCT-04:01 -0.5
November 0.857853E+09 13210.88 24-NOV-04:03 -3.2
December 0.602963E+10 15192.29 26-DEC-04:01 -11.8
         
Annual Sum or Average 0.234368E+11      
Minimum of Months 0.00 0.00   -15.0
Maximum of Months 0.738971E+10 15382.33   18.85



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.431815E+10 21186.96 29-JAN-22:22 -9.2
February 0.377373E+10 21416.52 06-FEB-05:01 -14.8
March 0.978029E+09 19926.24 07-MAR-04:01 -12.9
April 0.162325E+09 17838.67 17-APR-04:01 -3.4
May 155960.59 593.64 01-MAY-05:03 1.70
June 0.00 0.00 01-JUN-00:10 17.05
July 0.00 0.00 01-JUL-00:10 16.82
August 0.00 0.00 01-AUG-00:03 18.85
September 1123354.31 3628.49 30-SEP-05:03 7.20
October 0.124394E+09 18260.19 30-OCT-04:01 -0.5
November 0.550749E+09 18467.08 25-NOV-05:01 -1.7
December 0.387321E+10 21421.06 26-DEC-04:01 -11.8
         
Annual Sum or Average 0.137819E+11      
Minimum of Months 0.00 0.00   -14.8
Maximum of Months 0.431815E+10 21421.06   18.85



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.482676E+10 23941.83 29-JAN-22:22 -9.2
February 0.442568E+10 24078.93 06-FEB-04:21 -15.0
March 0.996115E+09 22391.71 06-MAR-04:01 -11.1
April 0.239824E+09 20354.04 17-APR-04:01 -3.4
May 0.00 0.00 01-MAY-00:10 6.67
June 0.00 0.00 01-JUN-00:10 17.05
July 0.00 0.00 01-JUL-00:10 16.82
August 0.00 0.00 01-AUG-00:03 18.85
September 0.00 0.00 01-SEP-00:10 14.65
October 0.109579E+09 20151.41 30-OCT-04:01 -0.5
November 0.604437E+09 20526.17 29-NOV-05:01 1.70
December 0.411924E+10 24187.47 26-DEC-04:01 -11.8
         
Annual Sum or Average 0.153216E+11      
Minimum of Months 0.00 0.00   -15.0
Maximum of Months 0.482676E+10 24187.47   18.85



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.384756E+10 21384.07 29-JAN-22:22 -9.2
February 0.317464E+10 21674.65 06-FEB-04:21 -15.0
March 0.771853E+09 20008.64 06-MAR-04:01 -11.1
April 0.107359E+09 17812.11 17-APR-04:01 -3.4
May 2355.35 19.63 12-MAY-05:04 8.90
June 0.00 0.00 01-JUN-00:10 17.05
July 0.00 0.00 01-JUL-00:10 16.82
August 0.00 0.00 01-AUG-00:03 18.85
September 0.00 0.00 01-SEP-00:10 14.65
October 79634837.48 17606.72 30-OCT-04:01 -0.5
November 0.394747E+09 18059.12 29-NOV-05:01 1.70
December 0.294450E+10 21550.56 26-DEC-04:01 -11.8
         
Annual Sum or Average 0.113203E+11      
Minimum of Months 0.00 0.00   -15.0
Maximum of Months 0.384756E+10 21674.65   18.85



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.123694E+11 17760.03 29-JAN-22:22 -9.2
February 0.110021E+11 18561.79 06-FEB-05:01 -14.8
March 0.517385E+10 17335.02 06-MAR-01:52 -10.6
April 0.137773E+10 16396.45 16-APR-04:03 -2.2
May 63019601.74 13389.39 08-MAY-04:12 3.30
June 509796.27 3398.64 14-JUN-05:03 6.78
July 0.00 0.00 01-JUL-00:10 16.82
August 0.00 0.00 01-AUG-00:03 18.85
September 45736599.78 12893.07 29-SEP-05:03 10.50
October 0.107740E+10 16136.41 16-OCT-03:01 0.68
November 0.297848E+10 16420.76 24-NOV-04:11 -3.1
December 0.113259E+11 18186.61 26-DEC-06:01 -12.2
         
Annual Sum or Average 0.454142E+11      
Minimum of Months 0.00 0.00   -14.8
Maximum of Months 0.123694E+11 18561.79   18.85



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.734230E+10 22870.39 29-JAN-22:22 -9.2
February 0.659455E+10 23457.80 06-FEB-04:21 -15.0
March 0.245072E+10 22122.18 06-MAR-01:52 -10.6
April 0.664658E+09 21344.50 17-APR-03:11 -3.0
May 31372965.83 14307.45 12-MAY-05:02 8.90
June 0.00 0.00 01-JUN-00:10 17.05
July 0.00 0.00 01-JUL-00:10 16.82
August 0.00 0.00 01-AUG-00:03 18.85
September 27273645.96 10023.33 29-SEP-05:03 10.50
October 0.589338E+09 20676.86 16-OCT-03:01 0.68
November 0.175813E+10 21408.46 24-NOV-04:11 -3.1
December 0.720442E+10 22965.02 26-DEC-04:01 -11.8
         
Annual Sum or Average 0.266628E+11      
Minimum of Months 0.00 0.00   -15.0
Maximum of Months 0.734230E+10 23457.80   18.85



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.880634E+10 26572.98 29-JAN-22:22 -9.2
February 0.830152E+10 27325.96 06-FEB-04:21 -15.0
March 0.291862E+10 25445.06 06-MAR-01:52 -10.6
April 0.107219E+10 24725.68 17-APR-03:11 -3.0
May 63106536.85 19700.24 12-MAY-05:02 8.90
June 3400459.86 11680.66 14-JUN-05:03 6.78
July 0.00 0.00 01-JUL-00:10 16.82
August 0.00 0.00 01-AUG-00:03 18.85
September 31158362.43 14601.69 29-SEP-05:03 10.50
October 0.676798E+09 24008.96 30-OCT-03:01 -0.1
November 0.213066E+10 24911.82 24-NOV-04:11 -3.1
December 0.858003E+10 26746.78 26-DEC-04:01 -11.8
         
Annual Sum or Average 0.325838E+11      
Minimum of Months 0.00 0.00   -15.0
Maximum of Months 0.880634E+10 27325.96   18.85



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.674223E+10 24958.39 29-JAN-22:22 -9.2
February 0.559774E+10 25404.23 06-FEB-04:21 -15.0
March 0.196865E+10 23635.66 06-MAR-05:11 -11.1
April 0.485723E+09 22781.43 17-APR-03:11 -3.0
May 11481252.69 11885.51 12-MAY-05:02 8.90
June 289047.82 1926.99 14-JUN-05:03 6.78
July 0.00 0.00 01-JUL-00:10 16.82
August 0.00 0.00 01-AUG-00:03 18.85
September 16223578.59 9276.77 29-SEP-05:03 10.50
October 0.421656E+09 22458.74 30-OCT-03:01 -0.1
November 0.127314E+10 23126.48 24-NOV-04:11 -3.1
December 0.558978E+10 24907.02 26-DEC-04:01 -11.8
         
Annual Sum or Average 0.221069E+11      
Minimum of Months 0.00 0.00   -15.0
Maximum of Months 0.674223E+10 25404.23   18.85



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: GROUNDFLOOR_PLENUM

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.134965E+10 12007.08 11-JAN-06:02 5.68
February 0.145435E+10 14251.44 15-FEB-06:02 5.60
March 0.339358E+09 11857.08 13-MAR-04:11 10.37
April 0.127476E+09 11888.75 18-APR-04:11 4.07
May 80662456.78 8334.04 01-MAY-04:12 3.17
June 89302263.32 10454.97 25-JUN-16:21 27.50
July 0.131848E+09 10537.18 16-JUL-16:01 30.03
August 0.114093E+09 11904.95 13-AUG-15:21 29.70
September 72642315.98 9744.87 10-SEP-15:22 17.50
October 77057033.42 10773.18 10-OCT-04:11 10.00
November 78956622.86 12650.68 27-NOV-05:12 17.97
December 0.664055E+09 13480.01 18-DEC-05:01 1.70
         
Annual Sum or Average 0.457945E+10      
Minimum of Months 72642315.98 8334.04   1.70
Maximum of Months 0.145435E+10 14251.44   30.03



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: MIDFLOOR_PLENUM

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.549785E+10 19330.08 02-JAN-06:12 -1.1
February 0.457174E+10 13250.12 24-FEB-16:15 -2.6
March 0.203119E+10 15272.84 03-MAR-11:03 -2.7
April 0.542175E+09 8420.48 02-APR-16:41 6.97
May 62964749.97 9572.84 14-MAY-14:52 26.10
June 65286051.97 8951.39 18-JUN-15:01 25.55
July 74556408.97 11657.51 16-JUL-15:51 30.60
August 53558610.06 10158.43 13-AUG-15:02 29.90
September 60893405.84 10788.51 04-SEP-15:52 18.30
October 0.353006E+09 9248.56 09-OCT-12:32 12.03
November 0.814794E+09 5967.29 16-NOV-06:02 11.78
December 0.383400E+10 11888.37 26-DEC-06:11 -12.2
         
Annual Sum or Average 0.179620E+11      
Minimum of Months 53558610.06 5967.29   -12.2
Maximum of Months 0.549785E+10 19330.08   30.60



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: TOPFLOOR_PLENUM

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.150276E+11 30416.41 30-JAN-05:12 -9.6
February 0.131490E+11 33734.43 06-FEB-05:10 -14.8
March 0.654730E+10 29652.47 06-MAR-05:22 -11.1
April 0.243557E+10 22240.39 17-APR-05:02 -4.0
May 0.585511E+09 14629.44 31-MAY-05:03 13.98
June 0.155513E+09 14233.76 13-JUN-05:03 8.90
July 75119555.14 13933.06 13-JUL-05:03 11.88
August 97578330.01 14523.62 03-AUG-05:03 11.10
September 0.431585E+09 14983.42 19-SEP-05:03 10.60
October 0.215127E+10 19428.58 30-OCT-04:12 -0.4
November 0.499958E+10 21919.22 24-NOV-05:13 -3.2
December 0.138810E+11 32444.35 11-DEC-05:33 -18.3
         
Annual Sum or Average 0.595366E+11      
Minimum of Months 75119555.14 13933.06   -18.3
Maximum of Months 0.150276E+11 33734.43   13.98



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:03 -1.0
February 0.00 0.00 01-FEB-00:03 -3.3
March 0.00 0.00 01-MAR-00:10 -4.9
April 0.00 0.00 01-APR-00:10 4.10
May 0.00 0.00 01-MAY-00:10 6.67
June 0.00 0.00 01-JUN-00:10 17.05
July 0.00 0.00 01-JUL-00:10 16.82
August 0.00 0.00 01-AUG-00:03 18.85
September 0.00 0.00 01-SEP-00:10 14.65
October 0.00 0.00 01-OCT-00:10 14.42
November 0.00 0.00 01-NOV-00:10 6.53
December 0.00 0.00 01-DEC-00:10 4.95
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   -4.9
Maximum of Months 0.00 0.00   18.85



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: DATACENTER_MID_ZN_6

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.635795E+09 579.58 24-JAN-01:20 -11.1
February 0.00 0.00 01-FEB-00:03 -3.3
March 0.00 0.00 01-MAR-00:10 -4.9
April 0.00 0.00 01-APR-00:10 4.10
May 0.00 0.00 01-MAY-00:10 6.67
June 0.00 0.00 01-JUN-00:10 17.05
July 0.00 0.00 01-JUL-00:10 16.82
August 0.00 0.00 01-AUG-00:03 18.85
September 0.00 0.00 01-SEP-00:10 14.65
October 0.00 0.00 01-OCT-00:10 14.42
November 0.00 0.00 01-NOV-00:10 6.53
December 0.00 0.00 01-DEC-00:10 4.95
         
Annual Sum or Average 0.635795E+09      
Minimum of Months 0.00 0.00   -11.1
Maximum of Months 0.635795E+09 579.58   18.85



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.801025E+09 620.09 15-JAN-18:55 0.00
February 0.147034E+09 573.66 05-FEB-20:40 -11.5
March 0.00 0.00 01-MAR-00:10 -4.9
April 0.00 0.00 01-APR-00:10 4.10
May 276333.54 118.92 01-MAY-06:45 4.95
June 0.00 0.00 01-JUN-00:10 17.05
July 0.00 0.00 01-JUL-00:10 16.82
August 0.00 0.00 01-AUG-00:03 18.85
September 0.00 0.00 01-SEP-00:10 14.65
October 0.00 0.00 01-OCT-00:10 14.42
November 0.00 0.00 01-NOV-00:10 6.53
December 0.00 0.00 01-DEC-00:10 4.95
         
Annual Sum or Average 0.948335E+09      
Minimum of Months 0.00 0.00   -11.5
Maximum of Months 0.801025E+09 620.09   18.85



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:03 -1.0
February 0.00 0.00 01-FEB-00:03 -3.3
March 0.00 0.00 01-MAR-00:10 -4.9
April 0.00 0.00 01-APR-00:10 4.10
May 0.00 0.00 01-MAY-00:10 6.67
June 0.00 0.00 01-JUN-00:10 17.05
July 0.00 0.00 01-JUL-00:10 16.82
August 0.00 0.00 01-AUG-00:03 18.85
September 0.00 0.00 01-SEP-00:10 14.65
October 0.00 0.00 01-OCT-00:10 14.42
November 0.00 0.00 01-NOV-00:10 6.53
December 0.00 0.00 01-DEC-00:10 4.95
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   -4.9
Maximum of Months 0.00 0.00   18.85



Table of Contents

Report: ZoneElectricSummaryMonthly

For: BASEMENT

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.219312E+11 22950.34 02-JAN-08:09 0.360447E+11 13457.54 01-JAN-00:10
February 0.198933E+11 22950.34 01-FEB-08:09 0.325565E+11 13457.54 01-FEB-00:10
March 0.236388E+11 22950.34 01-MAR-08:09 0.360447E+11 13457.54 01-MAR-00:10
April 0.211142E+11 22950.34 03-APR-07:10 0.348820E+11 13457.54 01-APR-00:10
May 0.227850E+11 22950.34 01-MAY-07:10 0.360447E+11 13457.54 01-MAY-00:10
June 0.226748E+11 22950.34 01-JUN-07:10 0.348820E+11 13457.54 01-JUN-00:10
July 0.212244E+11 22950.34 03-JUL-07:10 0.360447E+11 13457.54 01-JUL-00:10
August 0.236388E+11 22950.34 01-AUG-07:10 0.360447E+11 13457.54 01-AUG-00:10
September 0.211142E+11 22950.34 01-SEP-07:10 0.348820E+11 13457.54 01-SEP-00:10
October 0.219312E+11 22950.34 02-OCT-07:10 0.360447E+11 13457.54 01-OCT-00:10
November 0.216742E+11 22950.34 01-NOV-07:10 0.348820E+11 13457.54 01-NOV-00:10
December 0.212244E+11 22950.34 01-DEC-08:09 0.360447E+11 13457.54 01-DEC-00:10
             
Annual Sum or Average 0.262844E+12     0.424397E+12    
Minimum of Months 0.198933E+11 22950.34   0.325565E+11 13457.54  
Maximum of Months 0.236388E+11 22950.34   0.360447E+11 13457.54  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: CORE_BOTTOM

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.196958E+11 20611.01 02-JAN-08:09 0.243681E+11 17206.63 02-JAN-08:09
February 0.178655E+11 20611.01 01-FEB-08:09 0.220609E+11 17206.63 01-FEB-08:09
March 0.212293E+11 20611.01 01-MAR-08:09 0.253549E+11 17206.63 01-MAR-08:09
April 0.189620E+11 20611.01 03-APR-07:10 0.235306E+11 17206.63 03-APR-07:10
May 0.204625E+11 20611.01 01-MAY-07:10 0.248615E+11 17206.63 01-MAY-07:10
June 0.203636E+11 20611.01 01-JUN-07:10 0.244160E+11 17206.63 01-JUN-07:10
July 0.190610E+11 20611.01 03-JUL-07:10 0.239708E+11 17206.63 03-JUL-07:10
August 0.212293E+11 20611.01 01-AUG-07:10 0.253549E+11 17206.63 01-AUG-07:10
September 0.189620E+11 20611.01 01-SEP-07:10 0.235199E+11 17206.63 01-SEP-07:10
October 0.196958E+11 20611.01 02-OCT-07:10 0.243735E+11 17206.63 02-OCT-07:10
November 0.194649E+11 20611.01 01-NOV-07:10 0.238373E+11 17206.63 01-NOV-07:10
December 0.190610E+11 20611.01 01-DEC-08:09 0.239654E+11 17206.63 01-DEC-08:09
             
Annual Sum or Average 0.236053E+12     0.289614E+12    
Minimum of Months 0.178655E+11 20611.01   0.220609E+11 17206.63  
Maximum of Months 0.212293E+11 20611.01   0.253549E+11 17206.63  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: CORE_MID

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.196958E+11 20611.01 02-JAN-08:09 0.243680E+11 17206.56 02-JAN-08:09
February 0.178655E+11 20611.01 01-FEB-08:09 0.220609E+11 17206.56 01-FEB-08:09
March 0.212293E+11 20611.01 01-MAR-08:09 0.253548E+11 17206.56 01-MAR-08:09
April 0.189620E+11 20611.01 03-APR-07:10 0.235305E+11 17206.56 03-APR-07:10
May 0.204625E+11 20611.01 01-MAY-07:10 0.248614E+11 17206.56 01-MAY-07:10
June 0.203636E+11 20611.01 01-JUN-07:10 0.244159E+11 17206.56 01-JUN-07:10
July 0.190610E+11 20611.01 03-JUL-07:10 0.239707E+11 17206.56 03-JUL-07:10
August 0.212293E+11 20611.01 01-AUG-07:10 0.253548E+11 17206.56 01-AUG-07:10
September 0.189620E+11 20611.01 01-SEP-07:10 0.235198E+11 17206.56 01-SEP-07:10
October 0.196958E+11 20611.01 02-OCT-07:10 0.243734E+11 17206.56 02-OCT-07:10
November 0.194649E+11 20611.01 01-NOV-07:10 0.238372E+11 17206.56 01-NOV-07:10
December 0.190610E+11 20611.01 01-DEC-08:09 0.239653E+11 17206.56 01-DEC-08:09
             
Annual Sum or Average 0.236053E+12     0.289613E+12    
Minimum of Months 0.178655E+11 20611.01   0.220609E+11 17206.56  
Maximum of Months 0.212293E+11 20611.01   0.253548E+11 17206.56  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: CORE_TOP

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.196958E+11 20611.01 02-JAN-08:09 0.243680E+11 17206.56 02-JAN-08:09
February 0.178655E+11 20611.01 01-FEB-08:09 0.220609E+11 17206.56 01-FEB-08:09
March 0.212293E+11 20611.01 01-MAR-08:09 0.253548E+11 17206.56 01-MAR-08:09
April 0.189620E+11 20611.01 03-APR-07:10 0.235305E+11 17206.56 03-APR-07:10
May 0.204625E+11 20611.01 01-MAY-07:10 0.248614E+11 17206.56 01-MAY-07:10
June 0.203636E+11 20611.01 01-JUN-07:10 0.244159E+11 17206.56 01-JUN-07:10
July 0.190610E+11 20611.01 03-JUL-07:10 0.239707E+11 17206.56 03-JUL-07:10
August 0.212293E+11 20611.01 01-AUG-07:10 0.253548E+11 17206.56 01-AUG-07:10
September 0.189620E+11 20611.01 01-SEP-07:10 0.235198E+11 17206.56 01-SEP-07:10
October 0.196958E+11 20611.01 02-OCT-07:10 0.243734E+11 17206.56 02-OCT-07:10
November 0.194649E+11 20611.01 01-NOV-07:10 0.238372E+11 17206.56 01-NOV-07:10
December 0.190610E+11 20611.01 01-DEC-08:09 0.239653E+11 17206.56 01-DEC-08:09
             
Annual Sum or Average 0.236053E+12     0.289613E+12    
Minimum of Months 0.178655E+11 20611.01   0.220609E+11 17206.56  
Maximum of Months 0.212293E+11 20611.01   0.253548E+11 17206.56  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.163420E+10 2587.92 02-JAN-16:40 0.305979E+10 2160.55 02-JAN-08:09
February 0.137979E+10 2587.92 01-FEB-08:09 0.277008E+10 2160.55 01-FEB-08:09
March 0.152637E+10 1803.00 13-MAR-07:10 0.318369E+10 2160.55 01-MAR-08:09
April 0.131178E+10 1803.00 12-APR-07:10 0.295462E+10 2160.55 03-APR-07:10
May 0.137447E+10 1350.81 10-MAY-07:10 0.312174E+10 2160.55 01-MAY-07:10
June 0.134476E+10 1231.33 01-JUN-07:10 0.306580E+10 2160.55 01-JUN-07:10
July 0.127049E+10 1350.81 11-JUL-07:10 0.300989E+10 2160.55 03-JUL-07:10
August 0.143362E+10 1350.81 21-AUG-07:10 0.318369E+10 2160.55 01-AUG-07:10
September 0.134736E+10 1803.00 26-SEP-07:10 0.295328E+10 2160.55 01-SEP-07:10
October 0.148600E+10 2587.92 30-OCT-07:10 0.306046E+10 2160.55 02-OCT-07:10
November 0.163804E+10 2587.92 01-NOV-07:10 0.299314E+10 2160.55 01-NOV-07:10
December 0.164221E+10 2587.92 01-DEC-16:19 0.300922E+10 2160.55 01-DEC-08:09
             
Annual Sum or Average 0.173891E+11     0.363654E+11    
Minimum of Months 0.127049E+10 1231.33   0.277008E+10 2160.55  
Maximum of Months 0.164221E+10 2587.92   0.318369E+10 2160.55  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.102806E+10 1667.75 02-JAN-16:40 0.197184E+10 1392.34 02-JAN-08:09
February 0.880886E+09 1667.75 01-FEB-16:00 0.178515E+10 1392.34 01-FEB-08:09
March 0.977868E+09 1161.92 17-MAR-07:10 0.205169E+10 1392.34 01-MAR-08:09
April 0.846170E+09 947.51 12-APR-07:10 0.190407E+10 1392.34 03-APR-07:10
May 0.891341E+09 870.51 11-MAY-07:10 0.201177E+10 1392.34 01-MAY-07:10
June 0.872128E+09 793.52 01-JUN-07:10 0.197572E+10 1392.34 01-JUN-07:10
July 0.823311E+09 870.51 17-JUL-15:39 0.193969E+10 1392.34 03-JUL-07:10
August 0.928581E+09 870.51 24-AUG-07:10 0.205169E+10 1392.34 01-AUG-07:10
September 0.864672E+09 947.51 22-SEP-15:30 0.190321E+10 1392.34 01-SEP-07:10
October 0.942463E+09 1453.34 23-OCT-07:10 0.197228E+10 1392.34 02-OCT-07:10
November 0.103205E+10 1667.75 01-NOV-07:10 0.192889E+10 1392.34 01-NOV-07:10
December 0.102971E+10 1667.75 01-DEC-16:19 0.193926E+10 1392.34 01-DEC-08:09
             
Annual Sum or Average 0.111172E+11     0.234352E+11    
Minimum of Months 0.823311E+09 793.52   0.178515E+10 1392.34  
Maximum of Months 0.103205E+10 1667.75   0.205169E+10 1392.34  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.155657E+10 2587.98 02-JAN-16:49 0.305983E+10 2160.58 02-JAN-08:09
February 0.134995E+10 2255.25 01-FEB-08:09 0.277013E+10 2160.58 01-FEB-08:09
March 0.151197E+10 1803.04 13-MAR-07:10 0.318374E+10 2160.58 01-MAR-08:09
April 0.131454E+10 1803.04 12-APR-07:10 0.295467E+10 2160.58 03-APR-07:10
May 0.138550E+10 1350.84 10-MAY-07:10 0.312179E+10 2160.58 01-MAY-07:10
June 0.135624E+10 1350.84 19-JUN-07:10 0.306585E+10 2160.58 01-JUN-07:10
July 0.128047E+10 1350.84 11-JUL-07:10 0.300994E+10 2160.58 03-JUL-07:10
August 0.144180E+10 1350.84 21-AUG-07:10 0.318374E+10 2160.58 01-AUG-07:10
September 0.134135E+10 1803.04 26-SEP-07:10 0.295333E+10 2160.58 01-SEP-07:10
October 0.145079E+10 2255.25 23-OCT-07:10 0.306051E+10 2160.58 02-OCT-07:10
November 0.156848E+10 2587.98 01-NOV-07:10 0.299318E+10 2160.58 01-NOV-07:10
December 0.156494E+10 2587.98 01-DEC-16:19 0.300927E+10 2160.58 01-DEC-08:09
             
Annual Sum or Average 0.171226E+11     0.363660E+11    
Minimum of Months 0.128047E+10 1350.84   0.277013E+10 2160.58  
Maximum of Months 0.156848E+10 2587.98   0.318374E+10 2160.58  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.102383E+10 1667.75 02-JAN-16:49 0.197183E+10 1392.33 02-JAN-08:09
February 0.876961E+09 1667.75 01-FEB-08:09 0.178514E+10 1392.33 01-FEB-08:09
March 0.978761E+09 1453.34 13-MAR-07:10 0.205168E+10 1392.33 01-MAR-08:09
April 0.846042E+09 1161.92 12-APR-07:10 0.190406E+10 1392.33 03-APR-07:10
May 0.888030E+09 947.51 11-MAY-07:10 0.201175E+10 1392.33 01-MAY-07:10
June 0.868841E+09 870.51 07-JUN-07:10 0.197570E+10 1392.33 01-JUN-07:10
July 0.821492E+09 947.51 11-JUL-07:10 0.193968E+10 1392.33 03-JUL-07:10
August 0.925005E+09 947.51 21-AUG-07:10 0.205168E+10 1392.33 01-AUG-07:10
September 0.867268E+09 1238.92 26-SEP-07:10 0.190319E+10 1392.33 01-SEP-07:10
October 0.950181E+09 1667.75 30-OCT-07:10 0.197226E+10 1392.33 02-OCT-07:10
November 0.102838E+10 1667.75 01-NOV-07:10 0.192888E+10 1392.33 01-NOV-07:10
December 0.103180E+10 1667.75 01-DEC-16:19 0.193924E+10 1392.33 01-DEC-08:09
             
Annual Sum or Average 0.111066E+11     0.234351E+11    
Minimum of Months 0.821492E+09 870.51   0.178514E+10 1392.33  
Maximum of Months 0.103180E+10 1667.75   0.205168E+10 1392.33  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.162864E+10 2587.92 02-JAN-16:40 0.305979E+10 2160.55 02-JAN-08:09
February 0.137619E+10 2587.92 01-FEB-08:09 0.277008E+10 2160.55 01-FEB-08:09
March 0.152372E+10 1803.00 13-MAR-07:10 0.318369E+10 2160.55 01-MAR-08:09
April 0.131034E+10 1803.00 12-APR-07:10 0.295462E+10 2160.55 03-APR-07:10
May 0.137342E+10 1350.81 10-MAY-07:10 0.312174E+10 2160.55 01-MAY-07:10
June 0.134387E+10 1231.33 01-JUN-07:10 0.306580E+10 2160.55 01-JUN-07:10
July 0.126989E+10 1350.81 11-JUL-07:10 0.300989E+10 2160.55 03-JUL-07:10
August 0.143276E+10 1350.81 21-AUG-07:10 0.318369E+10 2160.55 01-AUG-07:10
September 0.134511E+10 1803.00 26-SEP-07:10 0.295328E+10 2160.55 01-SEP-07:10
October 0.148192E+10 2587.92 30-OCT-07:10 0.306046E+10 2160.55 02-OCT-07:10
November 0.163109E+10 2587.92 01-NOV-07:10 0.299314E+10 2160.55 01-NOV-07:10
December 0.163516E+10 2587.92 01-DEC-16:19 0.300922E+10 2160.55 01-DEC-08:09
             
Annual Sum or Average 0.173521E+11     0.363654E+11    
Minimum of Months 0.126989E+10 1231.33   0.277008E+10 2160.55  
Maximum of Months 0.163516E+10 2587.92   0.318369E+10 2160.55  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.102523E+10 1667.75 02-JAN-16:40 0.197184E+10 1392.34 02-JAN-08:09
February 0.879549E+09 1667.75 01-FEB-16:00 0.178515E+10 1392.34 01-FEB-08:09
March 0.976711E+09 1161.92 17-MAR-07:10 0.205169E+10 1392.34 01-MAR-08:09
April 0.845141E+09 947.51 12-APR-07:10 0.190407E+10 1392.34 03-APR-07:10
May 0.890371E+09 870.51 11-MAY-07:10 0.201177E+10 1392.34 01-MAY-07:10
June 0.871526E+09 793.52 01-JUN-07:10 0.197572E+10 1392.34 01-JUN-07:10
July 0.822452E+09 793.52 03-JUL-07:10 0.193969E+10 1392.34 03-JUL-07:10
August 0.927739E+09 870.51 28-AUG-15:30 0.205169E+10 1392.34 01-AUG-07:10
September 0.863601E+09 947.51 26-SEP-07:10 0.190321E+10 1392.34 01-SEP-07:10
October 0.940992E+09 1453.34 23-OCT-07:10 0.197228E+10 1392.34 02-OCT-07:10
November 0.102882E+10 1667.75 01-NOV-07:10 0.192889E+10 1392.34 01-NOV-07:10
December 0.102689E+10 1667.75 01-DEC-16:19 0.193926E+10 1392.34 01-DEC-08:09
             
Annual Sum or Average 0.110990E+11     0.234352E+11    
Minimum of Months 0.822452E+09 793.52   0.178515E+10 1392.34  
Maximum of Months 0.102882E+10 1667.75   0.205169E+10 1392.34  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.155545E+10 2587.98 02-JAN-16:49 0.305983E+10 2160.58 02-JAN-08:09
February 0.134746E+10 2255.25 01-FEB-08:09 0.277013E+10 2160.58 01-FEB-08:09
March 0.151031E+10 1803.04 13-MAR-07:10 0.318374E+10 2160.58 01-MAR-08:09
April 0.131335E+10 1803.04 12-APR-07:10 0.295467E+10 2160.58 03-APR-07:10
May 0.138412E+10 1350.84 10-MAY-07:10 0.312179E+10 2160.58 01-MAY-07:10
June 0.135529E+10 1231.36 01-JUN-07:10 0.306585E+10 2160.58 01-JUN-07:10
July 0.127955E+10 1350.84 11-JUL-07:10 0.300994E+10 2160.58 03-JUL-07:10
August 0.144039E+10 1350.84 21-AUG-07:10 0.318374E+10 2160.58 01-AUG-07:10
September 0.133994E+10 1803.04 26-SEP-07:10 0.295333E+10 2160.58 01-SEP-07:10
October 0.144986E+10 2255.25 23-OCT-07:10 0.306051E+10 2160.58 02-OCT-07:10
November 0.156705E+10 2587.98 01-NOV-07:10 0.299318E+10 2160.58 01-NOV-07:10
December 0.156300E+10 2587.98 01-DEC-16:19 0.300927E+10 2160.58 01-DEC-08:09
             
Annual Sum or Average 0.171058E+11     0.363660E+11    
Minimum of Months 0.127955E+10 1231.36   0.277013E+10 2160.58  
Maximum of Months 0.156705E+10 2587.98   0.318374E+10 2160.58  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.102119E+10 1667.75 02-JAN-16:49 0.197183E+10 1392.33 02-JAN-08:09
February 0.875464E+09 1667.75 01-FEB-08:09 0.178514E+10 1392.33 01-FEB-08:09
March 0.977456E+09 1453.34 17-MAR-07:10 0.205168E+10 1392.33 01-MAR-08:09
April 0.845314E+09 1161.92 12-APR-07:10 0.190406E+10 1392.33 03-APR-07:10
May 0.887092E+09 947.51 11-MAY-07:10 0.201175E+10 1392.33 01-MAY-07:10
June 0.868081E+09 870.51 07-JUN-07:10 0.197570E+10 1392.33 01-JUN-07:10
July 0.820715E+09 870.51 11-JUL-07:10 0.193968E+10 1392.33 03-JUL-07:10
August 0.924238E+09 947.51 24-AUG-07:10 0.205168E+10 1392.33 01-AUG-07:10
September 0.866014E+09 1161.92 14-SEP-07:10 0.190319E+10 1392.33 01-SEP-07:10
October 0.948638E+09 1667.75 30-OCT-07:10 0.197226E+10 1392.33 02-OCT-07:10
November 0.102556E+10 1667.75 01-NOV-07:10 0.192888E+10 1392.33 01-NOV-07:10
December 0.102853E+10 1667.75 01-DEC-16:19 0.193924E+10 1392.33 01-DEC-08:09
             
Annual Sum or Average 0.110883E+11     0.234351E+11    
Minimum of Months 0.820715E+09 870.51   0.178514E+10 1392.33  
Maximum of Months 0.102853E+10 1667.75   0.205168E+10 1392.33  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.162801E+10 2587.92 02-JAN-16:40 0.305979E+10 2160.55 02-JAN-08:09
February 0.137559E+10 2587.92 01-FEB-16:00 0.277008E+10 2160.55 01-FEB-08:09
March 0.152366E+10 1803.00 13-MAR-07:10 0.318369E+10 2160.55 01-MAR-08:09
April 0.131028E+10 1803.00 12-APR-07:10 0.295462E+10 2160.55 03-APR-07:10
May 0.137330E+10 1350.81 10-MAY-07:10 0.312174E+10 2160.55 01-MAY-07:10
June 0.134387E+10 1231.33 01-JUN-07:10 0.306580E+10 2160.55 01-JUN-07:10
July 0.126989E+10 1350.81 11-JUL-07:10 0.300989E+10 2160.55 03-JUL-07:10
August 0.143271E+10 1350.81 21-AUG-07:10 0.318369E+10 2160.55 01-AUG-07:10
September 0.134489E+10 1803.00 26-SEP-07:10 0.295328E+10 2160.55 01-SEP-07:10
October 0.148156E+10 2587.92 30-OCT-07:10 0.306046E+10 2160.55 02-OCT-07:10
November 0.163050E+10 2587.92 01-NOV-07:10 0.299314E+10 2160.55 01-NOV-07:10
December 0.163449E+10 2587.92 01-DEC-16:19 0.300922E+10 2160.55 01-DEC-08:09
             
Annual Sum or Average 0.173487E+11     0.363654E+11    
Minimum of Months 0.126989E+10 1231.33   0.277008E+10 2160.55  
Maximum of Months 0.163449E+10 2587.92   0.318369E+10 2160.55  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.102495E+10 1667.75 02-JAN-16:40 0.197184E+10 1392.34 02-JAN-08:09
February 0.879405E+09 1667.75 01-FEB-16:00 0.178515E+10 1392.34 01-FEB-08:09
March 0.976706E+09 1161.92 17-MAR-07:10 0.205169E+10 1392.34 01-MAR-08:09
April 0.845075E+09 947.51 12-APR-07:10 0.190407E+10 1392.34 03-APR-07:10
May 0.890343E+09 870.51 11-MAY-07:10 0.201177E+10 1392.34 01-MAY-07:10
June 0.871494E+09 793.52 01-JUN-07:10 0.197572E+10 1392.34 01-JUN-07:10
July 0.822397E+09 793.52 03-JUL-07:10 0.193969E+10 1392.34 03-JUL-07:10
August 0.927668E+09 870.51 28-AUG-15:30 0.205169E+10 1392.34 01-AUG-07:10
September 0.863552E+09 947.51 26-SEP-07:10 0.190321E+10 1392.34 01-SEP-07:10
October 0.940817E+09 1453.34 23-OCT-07:10 0.197228E+10 1392.34 02-OCT-07:10
November 0.102859E+10 1667.75 01-NOV-07:10 0.192889E+10 1392.34 01-NOV-07:10
December 0.102678E+10 1667.75 01-DEC-16:19 0.193926E+10 1392.34 01-DEC-08:09
             
Annual Sum or Average 0.110978E+11     0.234352E+11    
Minimum of Months 0.822397E+09 793.52   0.178515E+10 1392.34  
Maximum of Months 0.102859E+10 1667.75   0.205169E+10 1392.34  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.155529E+10 2587.98 02-JAN-16:49 0.305983E+10 2160.58 02-JAN-08:09
February 0.134716E+10 2255.25 01-FEB-08:09 0.277013E+10 2160.58 01-FEB-08:09
March 0.151030E+10 1803.04 13-MAR-07:10 0.318374E+10 2160.58 01-MAR-08:09
April 0.131330E+10 1803.04 12-APR-07:10 0.295467E+10 2160.58 03-APR-07:10
May 0.138401E+10 1350.84 10-MAY-07:10 0.312179E+10 2160.58 01-MAY-07:10
June 0.135514E+10 1231.36 01-JUN-07:10 0.306585E+10 2160.58 01-JUN-07:10
July 0.127952E+10 1350.84 11-JUL-07:10 0.300994E+10 2160.58 03-JUL-07:10
August 0.144038E+10 1350.84 21-AUG-07:10 0.318374E+10 2160.58 01-AUG-07:10
September 0.133978E+10 1803.04 26-SEP-07:10 0.295333E+10 2160.58 01-SEP-07:10
October 0.144951E+10 2255.25 23-OCT-07:10 0.306051E+10 2160.58 02-OCT-07:10
November 0.156678E+10 2587.98 01-NOV-07:10 0.299318E+10 2160.58 01-NOV-07:10
December 0.156300E+10 2587.98 01-DEC-16:19 0.300927E+10 2160.58 01-DEC-08:09
             
Annual Sum or Average 0.171042E+11     0.363660E+11    
Minimum of Months 0.127952E+10 1231.36   0.277013E+10 2160.58  
Maximum of Months 0.156678E+10 2587.98   0.318374E+10 2160.58  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.102119E+10 1667.75 02-JAN-16:49 0.197183E+10 1392.33 02-JAN-08:09
February 0.875286E+09 1667.75 01-FEB-08:09 0.178514E+10 1392.33 01-FEB-08:09
March 0.977398E+09 1453.34 17-MAR-07:10 0.205168E+10 1392.33 01-MAR-08:09
April 0.845255E+09 1161.92 12-APR-07:10 0.190406E+10 1392.33 03-APR-07:10
May 0.887048E+09 947.51 11-MAY-07:10 0.201175E+10 1392.33 01-MAY-07:10
June 0.868055E+09 870.51 07-JUN-07:10 0.197570E+10 1392.33 01-JUN-07:10
July 0.820669E+09 870.51 11-JUL-07:10 0.193968E+10 1392.33 03-JUL-07:10
August 0.924213E+09 947.51 24-AUG-07:10 0.205168E+10 1392.33 01-AUG-07:10
September 0.866014E+09 1161.92 14-SEP-07:10 0.190319E+10 1392.33 01-SEP-07:10
October 0.948536E+09 1667.75 30-OCT-07:10 0.197226E+10 1392.33 02-OCT-07:10
November 0.102551E+10 1667.75 01-NOV-07:10 0.192888E+10 1392.33 01-NOV-07:10
December 0.102839E+10 1667.75 01-DEC-16:19 0.193924E+10 1392.33 01-DEC-08:09
             
Annual Sum or Average 0.110876E+11     0.234351E+11    
Minimum of Months 0.820669E+09 870.51   0.178514E+10 1392.33  
Maximum of Months 0.102839E+10 1667.75   0.205168E+10 1392.33  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.553024E+09 578.72 02-JAN-08:09 0.521915E+10 1948.61 01-JAN-00:10
February 0.501634E+09 578.72 01-FEB-08:09 0.942813E+10 3897.21 01-FEB-00:10
March 0.596080E+09 578.72 01-MAR-08:09 0.156645E+11 7794.42 31-MAR-23:10
April 0.532421E+09 578.72 03-APR-07:10 0.201821E+11 7794.42 01-APR-00:10
May 0.574552E+09 578.72 01-MAY-07:10 0.522616E+10 3897.21 31-MAY-23:10
June 0.571774E+09 578.72 01-JUN-07:10 0.101086E+11 5845.82 30-JUN-23:10
July 0.535199E+09 578.72 03-JUL-07:10 0.156645E+11 7794.42 31-JUL-23:10
August 0.596080E+09 578.72 01-AUG-07:10 0.208555E+11 7794.42 01-AUG-00:10
September 0.532421E+09 578.72 01-SEP-07:10 0.505780E+10 3897.21 30-SEP-23:10
October 0.553024E+09 578.72 02-OCT-07:10 0.104453E+11 5845.82 31-OCT-23:10
November 0.546542E+09 578.72 01-NOV-07:10 0.151524E+11 5845.82 01-NOV-00:10
December 0.535199E+09 578.72 01-DEC-08:09 0.208766E+11 7794.42 01-DEC-00:10
             
Annual Sum or Average 0.662795E+10     0.153881E+12    
Minimum of Months 0.501634E+09 578.72   0.505780E+10 1948.61  
Maximum of Months 0.596080E+09 578.72   0.208766E+11 7794.42  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: DATACENTER_MID_ZN_6

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.553024E+09 578.72 02-JAN-08:09 0.521915E+10 1948.61 01-JAN-00:10
February 0.501634E+09 578.72 01-FEB-08:09 0.942813E+10 3897.21 01-FEB-00:10
March 0.596080E+09 578.72 01-MAR-08:09 0.156645E+11 7794.42 31-MAR-23:10
April 0.532421E+09 578.72 03-APR-07:10 0.201821E+11 7794.42 01-APR-00:10
May 0.574552E+09 578.72 01-MAY-07:10 0.522616E+10 3897.21 31-MAY-23:10
June 0.571774E+09 578.72 01-JUN-07:10 0.101086E+11 5845.82 30-JUN-23:10
July 0.535199E+09 578.72 03-JUL-07:10 0.156645E+11 7794.42 31-JUL-23:10
August 0.596080E+09 578.72 01-AUG-07:10 0.208555E+11 7794.42 01-AUG-00:10
September 0.532421E+09 578.72 01-SEP-07:10 0.505780E+10 3897.21 30-SEP-23:10
October 0.553024E+09 578.72 02-OCT-07:10 0.104453E+11 5845.82 31-OCT-23:10
November 0.546542E+09 578.72 01-NOV-07:10 0.151524E+11 5845.82 01-NOV-00:10
December 0.535199E+09 578.72 01-DEC-08:09 0.208766E+11 7794.42 01-DEC-00:10
             
Annual Sum or Average 0.662795E+10     0.153881E+12    
Minimum of Months 0.501634E+09 578.72   0.505780E+10 1948.61  
Maximum of Months 0.596080E+09 578.72   0.208766E+11 7794.42  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.553024E+09 578.72 02-JAN-08:09 0.521915E+10 1948.61 01-JAN-00:10
February 0.501634E+09 578.72 01-FEB-08:09 0.942813E+10 3897.21 01-FEB-00:10
March 0.596080E+09 578.72 01-MAR-08:09 0.156645E+11 7794.42 31-MAR-23:10
April 0.532421E+09 578.72 03-APR-07:10 0.201821E+11 7794.42 01-APR-00:10
May 0.574552E+09 578.72 01-MAY-07:10 0.522616E+10 3897.21 31-MAY-23:10
June 0.571774E+09 578.72 01-JUN-07:10 0.101086E+11 5845.82 30-JUN-23:10
July 0.535199E+09 578.72 03-JUL-07:10 0.156645E+11 7794.42 31-JUL-23:10
August 0.596080E+09 578.72 01-AUG-07:10 0.208555E+11 7794.42 01-AUG-00:10
September 0.532421E+09 578.72 01-SEP-07:10 0.505780E+10 3897.21 30-SEP-23:10
October 0.553024E+09 578.72 02-OCT-07:10 0.104453E+11 5845.82 31-OCT-23:10
November 0.546542E+09 578.72 01-NOV-07:10 0.151524E+11 5845.82 01-NOV-00:10
December 0.535199E+09 578.72 01-DEC-08:09 0.208766E+11 7794.42 01-DEC-00:10
             
Annual Sum or Average 0.662795E+10     0.153881E+12    
Minimum of Months 0.501634E+09 578.72   0.505780E+10 1948.61  
Maximum of Months 0.596080E+09 578.72   0.208766E+11 7794.42  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.618367E+10 6471.01 02-JAN-08:09 0.254202E+12 94908.13 01-JAN-00:10
February 0.560905E+10 6471.01 01-FEB-08:09 0.459203E+12 189816.26 01-FEB-00:10
March 0.666512E+10 6471.01 01-MAR-08:09 0.762947E+12 379632.52 31-MAR-23:10
April 0.595330E+10 6471.01 03-APR-07:10 0.982982E+12 379632.52 01-APR-00:10
May 0.642439E+10 6471.01 01-MAY-07:10 0.254544E+12 189816.26 31-MAY-23:10
June 0.639333E+10 6471.01 01-JUN-07:10 0.492345E+12 284724.39 30-JUN-23:10
July 0.598436E+10 6471.01 03-JUL-07:10 0.762947E+12 379632.52 31-JUL-23:10
August 0.666512E+10 6471.01 01-AUG-07:10 0.101578E+13 379632.52 01-AUG-00:10
September 0.595330E+10 6471.01 01-SEP-07:10 0.246344E+12 189816.26 30-SEP-23:10
October 0.618367E+10 6471.01 02-OCT-07:10 0.508746E+12 284724.39 31-OCT-23:10
November 0.611120E+10 6471.01 01-NOV-07:10 0.738006E+12 284724.39 01-NOV-00:10
December 0.598436E+10 6471.01 01-DEC-08:09 0.101681E+13 379632.52 01-DEC-00:10
             
Annual Sum or Average 0.741109E+11     0.749486E+13    
Minimum of Months 0.560905E+10 6471.01   0.246344E+12 94908.13  
Maximum of Months 0.666512E+10 6471.01   0.101681E+13 379632.52  



Table of Contents

Report: SpaceGainsMonthly

For: BASEMENT

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.133902E+11 0.219312E+11 0.360447E+11 0.00 0.00 0.00 0.00 0.00 0.00
February 0.121482E+11 0.198933E+11 0.325565E+11 0.00 0.00 0.00 0.00 0.00 0.00
March 0.145160E+11 0.236388E+11 0.360447E+11 0.00 0.00 0.00 0.00 0.00 0.00
April 0.128805E+11 0.211142E+11 0.348820E+11 0.00 0.00 0.00 0.00 0.00 0.00
May 0.139531E+11 0.227850E+11 0.360447E+11 0.00 0.00 0.00 0.00 0.00 0.00
June 0.139143E+11 0.226748E+11 0.348820E+11 0.00 0.00 0.00 0.00 0.00 0.00
July 0.129193E+11 0.212244E+11 0.360447E+11 0.00 0.00 0.00 0.00 0.00 0.00
August 0.145160E+11 0.236388E+11 0.360447E+11 0.00 0.00 0.00 0.00 0.00 0.00
September 0.128805E+11 0.211142E+11 0.348820E+11 0.00 0.00 0.00 0.00 0.00 0.00
October 0.133902E+11 0.219312E+11 0.360447E+11 0.00 0.00 0.00 0.00 0.00 0.00
November 0.132595E+11 0.216742E+11 0.348820E+11 0.00 0.00 0.00 0.00 0.00 0.00
December 0.129193E+11 0.212244E+11 0.360447E+11 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.160687E+12 0.262844E+12 0.424397E+12 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.121482E+11 0.198933E+11 0.325565E+11 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.145160E+11 0.236388E+11 0.360447E+11 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: CORE_BOTTOM

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.120254E+11 0.196958E+11 0.243681E+11 0.00 0.00 0.00 0.00 0.00 0.00
February 0.109099E+11 0.178655E+11 0.220609E+11 0.00 0.00 0.00 0.00 0.00 0.00
March 0.130364E+11 0.212293E+11 0.253549E+11 0.00 0.00 0.00 0.00 0.00 0.00
April 0.115676E+11 0.189620E+11 0.235306E+11 0.00 0.00 0.00 0.00 0.00 0.00
May 0.125309E+11 0.204625E+11 0.248615E+11 0.00 0.00 0.00 0.00 0.00 0.00
June 0.124961E+11 0.203636E+11 0.244160E+11 0.00 0.00 0.00 0.00 0.00 0.00
July 0.116025E+11 0.190610E+11 0.239708E+11 0.00 0.00 0.00 0.00 0.00 0.00
August 0.130364E+11 0.212293E+11 0.253549E+11 0.00 0.00 0.00 0.00 0.00 0.00
September 0.115676E+11 0.189620E+11 0.235199E+11 0.00 0.00 0.00 0.00 0.00 0.00
October 0.120254E+11 0.196958E+11 0.243735E+11 0.00 0.00 0.00 0.00 0.00 0.00
November 0.119080E+11 0.194649E+11 0.238373E+11 0.00 0.00 0.00 0.00 0.00 0.00
December 0.116025E+11 0.190610E+11 0.239654E+11 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.144308E+12 0.236053E+12 0.289614E+12 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.109099E+11 0.178655E+11 0.220609E+11 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.130364E+11 0.212293E+11 0.253549E+11 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: CORE_MID

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.120254E+11 0.196958E+11 0.243680E+11 0.00 0.00 0.00 0.00 0.00 0.00
February 0.109099E+11 0.178655E+11 0.220609E+11 0.00 0.00 0.00 0.00 0.00 0.00
March 0.130364E+11 0.212293E+11 0.253548E+11 0.00 0.00 0.00 0.00 0.00 0.00
April 0.115676E+11 0.189620E+11 0.235305E+11 0.00 0.00 0.00 0.00 0.00 0.00
May 0.125309E+11 0.204625E+11 0.248614E+11 0.00 0.00 0.00 0.00 0.00 0.00
June 0.124961E+11 0.203636E+11 0.244159E+11 0.00 0.00 0.00 0.00 0.00 0.00
July 0.116025E+11 0.190610E+11 0.239707E+11 0.00 0.00 0.00 0.00 0.00 0.00
August 0.130364E+11 0.212293E+11 0.253548E+11 0.00 0.00 0.00 0.00 0.00 0.00
September 0.115676E+11 0.189620E+11 0.235198E+11 0.00 0.00 0.00 0.00 0.00 0.00
October 0.120254E+11 0.196958E+11 0.243734E+11 0.00 0.00 0.00 0.00 0.00 0.00
November 0.119080E+11 0.194649E+11 0.238372E+11 0.00 0.00 0.00 0.00 0.00 0.00
December 0.116025E+11 0.190610E+11 0.239653E+11 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.144308E+12 0.236053E+12 0.289613E+12 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.109099E+11 0.178655E+11 0.220609E+11 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.130364E+11 0.212293E+11 0.253548E+11 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: CORE_TOP

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.120254E+11 0.196958E+11 0.243680E+11 0.00 0.00 0.00 0.00 0.00 0.00
February 0.109099E+11 0.178655E+11 0.220609E+11 0.00 0.00 0.00 0.00 0.00 0.00
March 0.130364E+11 0.212293E+11 0.253548E+11 0.00 0.00 0.00 0.00 0.00 0.00
April 0.115676E+11 0.189620E+11 0.235305E+11 0.00 0.00 0.00 0.00 0.00 0.00
May 0.125309E+11 0.204625E+11 0.248614E+11 0.00 0.00 0.00 0.00 0.00 0.00
June 0.124961E+11 0.203636E+11 0.244159E+11 0.00 0.00 0.00 0.00 0.00 0.00
July 0.116025E+11 0.190610E+11 0.239707E+11 0.00 0.00 0.00 0.00 0.00 0.00
August 0.130364E+11 0.212293E+11 0.253548E+11 0.00 0.00 0.00 0.00 0.00 0.00
September 0.115676E+11 0.189620E+11 0.235198E+11 0.00 0.00 0.00 0.00 0.00 0.00
October 0.120254E+11 0.196958E+11 0.243734E+11 0.00 0.00 0.00 0.00 0.00 0.00
November 0.119080E+11 0.194649E+11 0.238372E+11 0.00 0.00 0.00 0.00 0.00 0.00
December 0.116025E+11 0.190610E+11 0.239653E+11 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.144308E+12 0.236053E+12 0.289613E+12 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.109099E+11 0.178655E+11 0.220609E+11 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.130364E+11 0.212293E+11 0.253548E+11 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.150991E+10 0.163420E+10 0.305979E+10 0.00 0.00 0.00 0.00 0.00 0.167987E+10
February 0.136985E+10 0.137979E+10 0.277008E+10 0.00 0.00 0.00 0.00 0.00 0.178230E+10
March 0.163685E+10 0.152637E+10 0.318369E+10 0.00 0.00 0.00 0.00 360194.08 0.113169E+10
April 0.145243E+10 0.131178E+10 0.295462E+10 0.00 0.00 0.00 0.00 0.00 0.934392E+09
May 0.157338E+10 0.137447E+10 0.312174E+10 0.00 0.00 0.00 0.00 198557.23 0.535194E+09
June 0.156900E+10 0.134476E+10 0.306580E+10 0.00 0.00 0.00 0.00 8555251.77 0.302475E+09
July 0.145680E+10 0.127049E+10 0.300989E+10 0.00 0.00 0.00 0.00 22694598.90 0.169372E+09
August 0.163685E+10 0.143362E+10 0.318369E+10 0.00 0.00 0.00 0.00 16636903.03 0.194727E+09
September 0.145243E+10 0.134736E+10 0.295328E+10 0.00 0.00 0.00 0.00 1259733.39 0.314093E+09
October 0.150991E+10 0.148600E+10 0.306046E+10 0.00 0.00 0.00 0.00 0.00 0.730792E+09
November 0.149516E+10 0.163804E+10 0.299314E+10 0.00 0.00 0.00 0.00 0.00 0.100859E+10
December 0.145680E+10 0.164221E+10 0.300922E+10 0.00 0.00 0.00 0.00 0.00 0.183703E+10
                   
Annual Sum or Average 0.181194E+11 0.173891E+11 0.363654E+11 0.00 0.00 0.00 0.00 49705238.41 0.106205E+11
Minimum of Months 0.136985E+10 0.127049E+10 0.277008E+10 0.00 0.00 0.00 0.00 0.00 0.169372E+09
Maximum of Months 0.163685E+10 0.164221E+10 0.318369E+10 0.00 0.00 0.00 0.00 22694598.90 0.183703E+10



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.973041E+09 0.102806E+10 0.197184E+10 0.00 0.00 0.00 0.00 0.00 0.111608E+10
February 0.882782E+09 0.880886E+09 0.178515E+10 0.00 0.00 0.00 0.00 0.00 0.117818E+10
March 0.105485E+10 0.977868E+09 0.205169E+10 0.00 0.00 0.00 0.00 240815.23 0.746328E+09
April 0.936002E+09 0.846170E+09 0.190407E+10 0.00 0.00 0.00 0.00 0.00 0.607119E+09
May 0.101394E+10 0.891341E+09 0.201177E+10 0.00 0.00 0.00 0.00 258121.10 0.356502E+09
June 0.101113E+10 0.872128E+09 0.197572E+10 0.00 0.00 0.00 0.00 6179843.44 0.195096E+09
July 0.938820E+09 0.823311E+09 0.193969E+10 0.00 0.00 0.00 0.00 17217695.22 0.100616E+09
August 0.105485E+10 0.928581E+09 0.205169E+10 0.00 0.00 0.00 0.00 12521505.19 0.114439E+09
September 0.936002E+09 0.864672E+09 0.190321E+10 0.00 0.00 0.00 0.00 951137.84 0.205991E+09
October 0.973041E+09 0.942463E+09 0.197228E+10 0.00 0.00 0.00 0.00 0.00 0.479541E+09
November 0.963541E+09 0.103205E+10 0.192889E+10 0.00 0.00 0.00 0.00 0.00 0.649979E+09
December 0.938820E+09 0.102971E+10 0.193926E+10 0.00 0.00 0.00 0.00 0.00 0.119820E+10
                   
Annual Sum or Average 0.116768E+11 0.111172E+11 0.234352E+11 0.00 0.00 0.00 0.00 37369118.02 0.694806E+10
Minimum of Months 0.882782E+09 0.823311E+09 0.178515E+10 0.00 0.00 0.00 0.00 0.00 0.100616E+09
Maximum of Months 0.105485E+10 0.103205E+10 0.205169E+10 0.00 0.00 0.00 0.00 17217695.22 0.119820E+10



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.150994E+10 0.155657E+10 0.305983E+10 0.00 0.00 0.00 0.00 0.00 0.167558E+10
February 0.136988E+10 0.134995E+10 0.277013E+10 0.00 0.00 0.00 0.00 0.00 0.176123E+10
March 0.163688E+10 0.151197E+10 0.318374E+10 0.00 0.00 0.00 0.00 358913.27 0.114599E+10
April 0.145246E+10 0.131454E+10 0.295467E+10 0.00 0.00 0.00 0.00 0.00 0.923948E+09
May 0.157341E+10 0.138550E+10 0.312179E+10 0.00 0.00 0.00 0.00 164036.50 0.535848E+09
June 0.156904E+10 0.135624E+10 0.306585E+10 0.00 0.00 0.00 0.00 8678787.98 0.298763E+09
July 0.145684E+10 0.128047E+10 0.300994E+10 0.00 0.00 0.00 0.00 22775426.39 0.167219E+09
August 0.163688E+10 0.144180E+10 0.318374E+10 0.00 0.00 0.00 0.00 15840502.91 0.195775E+09
September 0.145246E+10 0.134135E+10 0.295333E+10 0.00 0.00 0.00 0.00 1140172.40 0.323053E+09
October 0.150994E+10 0.145079E+10 0.306051E+10 0.00 0.00 0.00 0.00 0.00 0.736901E+09
November 0.149520E+10 0.156848E+10 0.299318E+10 0.00 0.00 0.00 0.00 0.00 0.986741E+09
December 0.145684E+10 0.156494E+10 0.300927E+10 0.00 0.00 0.00 0.00 0.00 0.181202E+10
                   
Annual Sum or Average 0.181198E+11 0.171226E+11 0.363660E+11 0.00 0.00 0.00 0.00 48957839.46 0.105631E+11
Minimum of Months 0.136988E+10 0.128047E+10 0.277013E+10 0.00 0.00 0.00 0.00 0.00 0.167219E+09
Maximum of Months 0.163688E+10 0.156848E+10 0.318374E+10 0.00 0.00 0.00 0.00 22775426.39 0.181202E+10



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.973041E+09 0.102383E+10 0.197183E+10 0.00 0.00 0.00 0.00 0.00 0.115300E+10
February 0.882782E+09 0.876961E+09 0.178514E+10 0.00 0.00 0.00 0.00 0.00 0.124376E+10
March 0.105485E+10 0.978761E+09 0.205168E+10 0.00 0.00 0.00 0.00 240122.79 0.823150E+09
April 0.936002E+09 0.846042E+09 0.190406E+10 0.00 0.00 0.00 0.00 0.00 0.690989E+09
May 0.101394E+10 0.888030E+09 0.201175E+10 0.00 0.00 0.00 0.00 109359.96 0.386979E+09
June 0.101113E+10 0.868841E+09 0.197570E+10 0.00 0.00 0.00 0.00 5476322.81 0.228853E+09
July 0.938820E+09 0.821492E+09 0.193968E+10 0.00 0.00 0.00 0.00 14221920.22 0.136547E+09
August 0.105485E+10 0.925005E+09 0.205168E+10 0.00 0.00 0.00 0.00 10271614.37 0.157314E+09
September 0.936002E+09 0.867268E+09 0.190319E+10 0.00 0.00 0.00 0.00 726843.53 0.228855E+09
October 0.973041E+09 0.950181E+09 0.197226E+10 0.00 0.00 0.00 0.00 0.00 0.526439E+09
November 0.963541E+09 0.102838E+10 0.192888E+10 0.00 0.00 0.00 0.00 0.00 0.727408E+09
December 0.938820E+09 0.103180E+10 0.193924E+10 0.00 0.00 0.00 0.00 0.00 0.132184E+10
                   
Annual Sum or Average 0.116768E+11 0.111066E+11 0.234351E+11 0.00 0.00 0.00 0.00 31046183.70 0.762514E+10
Minimum of Months 0.882782E+09 0.821492E+09 0.178514E+10 0.00 0.00 0.00 0.00 0.00 0.136547E+09
Maximum of Months 0.105485E+10 0.103180E+10 0.205168E+10 0.00 0.00 0.00 0.00 14221920.22 0.132184E+10



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.150991E+10 0.162864E+10 0.305979E+10 0.00 0.00 0.00 0.00 0.00 0.352257E+10
February 0.136985E+10 0.137619E+10 0.277008E+10 0.00 0.00 0.00 0.00 0.00 0.374239E+10
March 0.163685E+10 0.152372E+10 0.318369E+10 0.00 0.00 0.00 0.00 750007.66 0.233617E+10
April 0.145243E+10 0.131034E+10 0.295462E+10 0.00 0.00 0.00 0.00 0.00 0.189251E+10
May 0.157338E+10 0.137342E+10 0.312174E+10 0.00 0.00 0.00 0.00 693250.49 0.114355E+10
June 0.156900E+10 0.134387E+10 0.306580E+10 0.00 0.00 0.00 0.00 20240726.50 0.665924E+09
July 0.145680E+10 0.126989E+10 0.300989E+10 0.00 0.00 0.00 0.00 48726558.74 0.392984E+09
August 0.163685E+10 0.143276E+10 0.318369E+10 0.00 0.00 0.00 0.00 39250169.28 0.448800E+09
September 0.145243E+10 0.134511E+10 0.295328E+10 0.00 0.00 0.00 0.00 2866302.89 0.666533E+09
October 0.150991E+10 0.148192E+10 0.306046E+10 0.00 0.00 0.00 0.00 0.00 0.146060E+10
November 0.149516E+10 0.163109E+10 0.299314E+10 0.00 0.00 0.00 0.00 0.00 0.197647E+10
December 0.145680E+10 0.163516E+10 0.300922E+10 0.00 0.00 0.00 0.00 0.00 0.373678E+10
                   
Annual Sum or Average 0.181194E+11 0.173521E+11 0.363654E+11 0.00 0.00 0.00 0.00 0.112527E+09 0.219853E+11
Minimum of Months 0.136985E+10 0.126989E+10 0.277008E+10 0.00 0.00 0.00 0.00 0.00 0.392984E+09
Maximum of Months 0.163685E+10 0.163516E+10 0.318369E+10 0.00 0.00 0.00 0.00 48726558.74 0.374239E+10



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.715730E+09 0.102523E+10 0.197184E+10 0.00 0.00 0.00 0.00 0.00 0.236034E+10
February 0.649041E+09 0.879549E+09 0.178515E+10 0.00 0.00 0.00 0.00 0.00 0.250989E+10
March 0.773965E+09 0.976711E+09 0.205169E+10 0.00 0.00 0.00 0.00 506980.27 0.158279E+10
April 0.688021E+09 0.845141E+09 0.190407E+10 0.00 0.00 0.00 0.00 0.00 0.128636E+10
May 0.744847E+09 0.890371E+09 0.201177E+10 0.00 0.00 0.00 0.00 665918.02 0.785974E+09
June 0.742030E+09 0.871526E+09 0.197572E+10 0.00 0.00 0.00 0.00 13672732.15 0.448049E+09
July 0.690839E+09 0.822452E+09 0.193969E+10 0.00 0.00 0.00 0.00 33160024.37 0.262540E+09
August 0.773965E+09 0.927739E+09 0.205169E+10 0.00 0.00 0.00 0.00 26649385.68 0.302458E+09
September 0.688021E+09 0.863601E+09 0.190321E+10 0.00 0.00 0.00 0.00 2147219.26 0.450766E+09
October 0.715730E+09 0.940992E+09 0.197228E+10 0.00 0.00 0.00 0.00 0.00 0.998247E+09
November 0.708685E+09 0.102882E+10 0.192889E+10 0.00 0.00 0.00 0.00 0.00 0.132722E+10
December 0.690839E+09 0.102689E+10 0.193926E+10 0.00 0.00 0.00 0.00 0.00 0.249880E+10
                   
Annual Sum or Average 0.858171E+10 0.110990E+11 0.234352E+11 0.00 0.00 0.00 0.00 76802259.74 0.148134E+11
Minimum of Months 0.649041E+09 0.822452E+09 0.178515E+10 0.00 0.00 0.00 0.00 0.00 0.262540E+09
Maximum of Months 0.773965E+09 0.102882E+10 0.205169E+10 0.00 0.00 0.00 0.00 33160024.37 0.250989E+10



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.150994E+10 0.155545E+10 0.305983E+10 0.00 0.00 0.00 0.00 0.00 0.365062E+10
February 0.136988E+10 0.134746E+10 0.277013E+10 0.00 0.00 0.00 0.00 0.00 0.383796E+10
March 0.163688E+10 0.151031E+10 0.318374E+10 0.00 0.00 0.00 0.00 748294.13 0.251588E+10
April 0.145246E+10 0.131335E+10 0.295467E+10 0.00 0.00 0.00 0.00 0.00 0.198932E+10
May 0.157341E+10 0.138412E+10 0.312179E+10 0.00 0.00 0.00 0.00 351792.95 0.119229E+10
June 0.156904E+10 0.135529E+10 0.306585E+10 0.00 0.00 0.00 0.00 19393570.94 0.672530E+09
July 0.145684E+10 0.127955E+10 0.300994E+10 0.00 0.00 0.00 0.00 47398402.71 0.404930E+09
August 0.163688E+10 0.144039E+10 0.318374E+10 0.00 0.00 0.00 0.00 35127756.16 0.478909E+09
September 0.145246E+10 0.133994E+10 0.295333E+10 0.00 0.00 0.00 0.00 2426422.94 0.725715E+09
October 0.150994E+10 0.144986E+10 0.306051E+10 0.00 0.00 0.00 0.00 0.00 0.161183E+10
November 0.149520E+10 0.156705E+10 0.299318E+10 0.00 0.00 0.00 0.00 0.00 0.209954E+10
December 0.145684E+10 0.156300E+10 0.300927E+10 0.00 0.00 0.00 0.00 0.00 0.386943E+10
                   
Annual Sum or Average 0.181198E+11 0.171058E+11 0.363660E+11 0.00 0.00 0.00 0.00 0.105446E+09 0.230490E+11
Minimum of Months 0.136988E+10 0.127955E+10 0.277013E+10 0.00 0.00 0.00 0.00 0.00 0.404930E+09
Maximum of Months 0.163688E+10 0.156705E+10 0.318374E+10 0.00 0.00 0.00 0.00 47398402.71 0.386943E+10



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.973041E+09 0.102119E+10 0.197183E+10 0.00 0.00 0.00 0.00 0.00 0.238601E+10
February 0.882782E+09 0.875464E+09 0.178514E+10 0.00 0.00 0.00 0.00 0.00 0.254413E+10
March 0.105485E+10 0.977456E+09 0.205168E+10 0.00 0.00 0.00 0.00 560107.16 0.164570E+10
April 0.936002E+09 0.845314E+09 0.190406E+10 0.00 0.00 0.00 0.00 0.00 0.133876E+10
May 0.101394E+10 0.887092E+09 0.201175E+10 0.00 0.00 0.00 0.00 234539.58 0.822134E+09
June 0.101113E+10 0.868081E+09 0.197570E+10 0.00 0.00 0.00 0.00 13181398.10 0.484481E+09
July 0.938820E+09 0.820715E+09 0.193968E+10 0.00 0.00 0.00 0.00 32489523.75 0.297575E+09
August 0.105485E+10 0.924238E+09 0.205168E+10 0.00 0.00 0.00 0.00 25424476.14 0.339250E+09
September 0.936002E+09 0.866014E+09 0.190319E+10 0.00 0.00 0.00 0.00 1649271.29 0.470625E+09
October 0.973041E+09 0.948638E+09 0.197226E+10 0.00 0.00 0.00 0.00 0.00 0.101259E+10
November 0.963541E+09 0.102556E+10 0.192888E+10 0.00 0.00 0.00 0.00 0.00 0.135191E+10
December 0.938820E+09 0.102853E+10 0.193924E+10 0.00 0.00 0.00 0.00 0.00 0.254140E+10
                   
Annual Sum or Average 0.116768E+11 0.110883E+11 0.234351E+11 0.00 0.00 0.00 0.00 73539316.02 0.152346E+11
Minimum of Months 0.882782E+09 0.820715E+09 0.178514E+10 0.00 0.00 0.00 0.00 0.00 0.297575E+09
Maximum of Months 0.105485E+10 0.102853E+10 0.205168E+10 0.00 0.00 0.00 0.00 32489523.75 0.254413E+10



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.150991E+10 0.162801E+10 0.305979E+10 0.00 0.00 0.00 0.00 0.00 0.428425E+10
February 0.136985E+10 0.137559E+10 0.277008E+10 0.00 0.00 0.00 0.00 0.00 0.455986E+10
March 0.163685E+10 0.152366E+10 0.318369E+10 0.00 0.00 0.00 0.00 819974.37 0.276049E+10
April 0.145243E+10 0.131028E+10 0.295462E+10 0.00 0.00 0.00 0.00 0.00 0.220126E+10
May 0.157338E+10 0.137330E+10 0.312174E+10 0.00 0.00 0.00 0.00 554592.88 0.135118E+10
June 0.156900E+10 0.134387E+10 0.306580E+10 0.00 0.00 0.00 0.00 22726147.29 0.815492E+09
July 0.145680E+10 0.126989E+10 0.300989E+10 0.00 0.00 0.00 0.00 56691597.72 0.494653E+09
August 0.163685E+10 0.143271E+10 0.318369E+10 0.00 0.00 0.00 0.00 44750796.60 0.554578E+09
September 0.145243E+10 0.134489E+10 0.295328E+10 0.00 0.00 0.00 0.00 3192811.94 0.782987E+09
October 0.150991E+10 0.148156E+10 0.306046E+10 0.00 0.00 0.00 0.00 0.00 0.163159E+10
November 0.149516E+10 0.163050E+10 0.299314E+10 0.00 0.00 0.00 0.00 0.00 0.223845E+10
December 0.145680E+10 0.163449E+10 0.300922E+10 0.00 0.00 0.00 0.00 0.00 0.451332E+10
                   
Annual Sum or Average 0.181194E+11 0.173487E+11 0.363654E+11 0.00 0.00 0.00 0.00 0.128736E+09 0.261881E+11
Minimum of Months 0.136985E+10 0.126989E+10 0.277008E+10 0.00 0.00 0.00 0.00 0.00 0.494653E+09
Maximum of Months 0.163685E+10 0.163449E+10 0.318369E+10 0.00 0.00 0.00 0.00 56691597.72 0.455986E+10



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.973041E+09 0.102495E+10 0.197184E+10 0.00 0.00 0.00 0.00 0.00 0.287310E+10
February 0.882782E+09 0.879405E+09 0.178515E+10 0.00 0.00 0.00 0.00 0.00 0.306579E+10
March 0.105485E+10 0.976706E+09 0.205169E+10 0.00 0.00 0.00 0.00 549764.50 0.186188E+10
April 0.936002E+09 0.845075E+09 0.190407E+10 0.00 0.00 0.00 0.00 0.00 0.150837E+10
May 0.101394E+10 0.890343E+09 0.201177E+10 0.00 0.00 0.00 0.00 527454.92 0.942232E+09
June 0.101113E+10 0.871494E+09 0.197572E+10 0.00 0.00 0.00 0.00 15610295.19 0.553995E+09
July 0.938820E+09 0.822397E+09 0.193969E+10 0.00 0.00 0.00 0.00 38639102.00 0.332309E+09
August 0.105485E+10 0.927668E+09 0.205169E+10 0.00 0.00 0.00 0.00 30219285.99 0.376329E+09
September 0.936002E+09 0.863552E+09 0.190321E+10 0.00 0.00 0.00 0.00 2373982.76 0.538878E+09
October 0.973041E+09 0.940817E+09 0.197228E+10 0.00 0.00 0.00 0.00 0.00 0.113055E+10
November 0.963541E+09 0.102859E+10 0.192889E+10 0.00 0.00 0.00 0.00 0.00 0.150971E+10
December 0.938820E+09 0.102678E+10 0.193926E+10 0.00 0.00 0.00 0.00 0.00 0.302102E+10
                   
Annual Sum or Average 0.116768E+11 0.110978E+11 0.234352E+11 0.00 0.00 0.00 0.00 87919885.36 0.177142E+11
Minimum of Months 0.882782E+09 0.822397E+09 0.178515E+10 0.00 0.00 0.00 0.00 0.00 0.332309E+09
Maximum of Months 0.105485E+10 0.102859E+10 0.205169E+10 0.00 0.00 0.00 0.00 38639102.00 0.306579E+10



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.150994E+10 0.155529E+10 0.305983E+10 0.00 0.00 0.00 0.00 0.00 0.438961E+10
February 0.136988E+10 0.134716E+10 0.277013E+10 0.00 0.00 0.00 0.00 0.00 0.464605E+10
March 0.163688E+10 0.151030E+10 0.318374E+10 0.00 0.00 0.00 0.00 817083.69 0.293591E+10
April 0.145246E+10 0.131330E+10 0.295467E+10 0.00 0.00 0.00 0.00 0.00 0.232319E+10
May 0.157341E+10 0.138401E+10 0.312179E+10 0.00 0.00 0.00 0.00 398619.95 0.141520E+10
June 0.156904E+10 0.135514E+10 0.306585E+10 0.00 0.00 0.00 0.00 22607604.82 0.820282E+09
July 0.145684E+10 0.127952E+10 0.300994E+10 0.00 0.00 0.00 0.00 56039799.21 0.504305E+09
August 0.163688E+10 0.144038E+10 0.318374E+10 0.00 0.00 0.00 0.00 41375047.04 0.589905E+09
September 0.145246E+10 0.133978E+10 0.295333E+10 0.00 0.00 0.00 0.00 2850522.94 0.863892E+09
October 0.150994E+10 0.144951E+10 0.306051E+10 0.00 0.00 0.00 0.00 0.00 0.183076E+10
November 0.149520E+10 0.156678E+10 0.299318E+10 0.00 0.00 0.00 0.00 0.00 0.237793E+10
December 0.145684E+10 0.156300E+10 0.300927E+10 0.00 0.00 0.00 0.00 0.00 0.460948E+10
                   
Annual Sum or Average 0.181198E+11 0.171042E+11 0.363660E+11 0.00 0.00 0.00 0.00 0.124089E+09 0.273065E+11
Minimum of Months 0.136988E+10 0.127952E+10 0.277013E+10 0.00 0.00 0.00 0.00 0.00 0.504305E+09
Maximum of Months 0.163688E+10 0.156678E+10 0.318374E+10 0.00 0.00 0.00 0.00 56039799.21 0.464605E+10



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.973041E+09 0.102119E+10 0.197183E+10 0.00 0.00 0.00 0.00 0.00 0.289454E+10
February 0.882782E+09 0.875286E+09 0.178514E+10 0.00 0.00 0.00 0.00 0.00 0.309500E+10
March 0.105485E+10 0.977398E+09 0.205168E+10 0.00 0.00 0.00 0.00 626229.15 0.194101E+10
April 0.936002E+09 0.845255E+09 0.190406E+10 0.00 0.00 0.00 0.00 0.00 0.157723E+10
May 0.101394E+10 0.887048E+09 0.201175E+10 0.00 0.00 0.00 0.00 265759.61 0.983313E+09
June 0.101113E+10 0.868055E+09 0.197570E+10 0.00 0.00 0.00 0.00 15252332.27 0.592650E+09
July 0.938820E+09 0.820669E+09 0.193968E+10 0.00 0.00 0.00 0.00 38319494.42 0.369014E+09
August 0.105485E+10 0.924213E+09 0.205168E+10 0.00 0.00 0.00 0.00 29885647.58 0.417513E+09
September 0.936002E+09 0.866014E+09 0.190319E+10 0.00 0.00 0.00 0.00 1958668.03 0.560831E+09
October 0.973041E+09 0.948536E+09 0.197226E+10 0.00 0.00 0.00 0.00 0.00 0.116193E+10
November 0.963541E+09 0.102551E+10 0.192888E+10 0.00 0.00 0.00 0.00 0.00 0.155666E+10
December 0.938820E+09 0.102839E+10 0.193924E+10 0.00 0.00 0.00 0.00 0.00 0.305475E+10
                   
Annual Sum or Average 0.116768E+11 0.110876E+11 0.234351E+11 0.00 0.00 0.00 0.00 86308131.06 0.182044E+11
Minimum of Months 0.882782E+09 0.820669E+09 0.178514E+10 0.00 0.00 0.00 0.00 0.00 0.369014E+09
Maximum of Months 0.105485E+10 0.102839E+10 0.205168E+10 0.00 0.00 0.00 0.00 38319494.42 0.309500E+10



Table of Contents

Report: SpaceGainsMonthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.174411E+09 0.553024E+09 0.521915E+10 0.00 0.00 0.00 0.00 0.00 0.00
February 0.158233E+09 0.501634E+09 0.942813E+10 0.00 0.00 0.00 0.00 0.00 0.00
March 0.189074E+09 0.596080E+09 0.156645E+11 0.00 0.00 0.00 0.00 0.00 0.00
April 0.167772E+09 0.532421E+09 0.201821E+11 0.00 0.00 0.00 0.00 0.00 0.00
May 0.181743E+09 0.574552E+09 0.522616E+10 0.00 0.00 0.00 0.00 0.00 0.00
June 0.181238E+09 0.571774E+09 0.101086E+11 0.00 0.00 0.00 0.00 0.00 0.00
July 0.168277E+09 0.535199E+09 0.156645E+11 0.00 0.00 0.00 0.00 0.00 0.00
August 0.189074E+09 0.596080E+09 0.208555E+11 0.00 0.00 0.00 0.00 0.00 0.00
September 0.167772E+09 0.532421E+09 0.505780E+10 0.00 0.00 0.00 0.00 0.00 0.00
October 0.174411E+09 0.553024E+09 0.104453E+11 0.00 0.00 0.00 0.00 0.00 0.00
November 0.172708E+09 0.546542E+09 0.151524E+11 0.00 0.00 0.00 0.00 0.00 0.00
December 0.168277E+09 0.535199E+09 0.208766E+11 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.209299E+10 0.662795E+10 0.153881E+12 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.158233E+09 0.501634E+09 0.505780E+10 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.189074E+09 0.596080E+09 0.208766E+11 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: DATACENTER_MID_ZN_6

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.174411E+09 0.553024E+09 0.521915E+10 0.00 0.00 0.00 0.00 0.00 0.00
February 0.158233E+09 0.501634E+09 0.942813E+10 0.00 0.00 0.00 0.00 0.00 0.00
March 0.189074E+09 0.596080E+09 0.156645E+11 0.00 0.00 0.00 0.00 0.00 0.00
April 0.167772E+09 0.532421E+09 0.201821E+11 0.00 0.00 0.00 0.00 0.00 0.00
May 0.181743E+09 0.574552E+09 0.522616E+10 0.00 0.00 0.00 0.00 0.00 0.00
June 0.181238E+09 0.571774E+09 0.101086E+11 0.00 0.00 0.00 0.00 0.00 0.00
July 0.168277E+09 0.535199E+09 0.156645E+11 0.00 0.00 0.00 0.00 0.00 0.00
August 0.189074E+09 0.596080E+09 0.208555E+11 0.00 0.00 0.00 0.00 0.00 0.00
September 0.167772E+09 0.532421E+09 0.505780E+10 0.00 0.00 0.00 0.00 0.00 0.00
October 0.174411E+09 0.553024E+09 0.104453E+11 0.00 0.00 0.00 0.00 0.00 0.00
November 0.172708E+09 0.546542E+09 0.151524E+11 0.00 0.00 0.00 0.00 0.00 0.00
December 0.168277E+09 0.535199E+09 0.208766E+11 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.209299E+10 0.662795E+10 0.153881E+12 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.158233E+09 0.501634E+09 0.505780E+10 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.189074E+09 0.596080E+09 0.208766E+11 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.174411E+09 0.553024E+09 0.521915E+10 0.00 0.00 0.00 0.00 0.00 0.00
February 0.158233E+09 0.501634E+09 0.942813E+10 0.00 0.00 0.00 0.00 0.00 0.00
March 0.189074E+09 0.596080E+09 0.156645E+11 0.00 0.00 0.00 0.00 0.00 0.00
April 0.167772E+09 0.532421E+09 0.201821E+11 0.00 0.00 0.00 0.00 0.00 0.00
May 0.181743E+09 0.574552E+09 0.522616E+10 0.00 0.00 0.00 0.00 0.00 0.00
June 0.181238E+09 0.571774E+09 0.101086E+11 0.00 0.00 0.00 0.00 0.00 0.00
July 0.168277E+09 0.535199E+09 0.156645E+11 0.00 0.00 0.00 0.00 0.00 0.00
August 0.189074E+09 0.596080E+09 0.208555E+11 0.00 0.00 0.00 0.00 0.00 0.00
September 0.167772E+09 0.532421E+09 0.505780E+10 0.00 0.00 0.00 0.00 0.00 0.00
October 0.174411E+09 0.553024E+09 0.104453E+11 0.00 0.00 0.00 0.00 0.00 0.00
November 0.172708E+09 0.546542E+09 0.151524E+11 0.00 0.00 0.00 0.00 0.00 0.00
December 0.168277E+09 0.535199E+09 0.208766E+11 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.209299E+10 0.662795E+10 0.153881E+12 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.158233E+09 0.501634E+09 0.505780E+10 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.189074E+09 0.596080E+09 0.208766E+11 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.377547E+10 0.618367E+10 0.254202E+12 0.00 0.00 0.00 0.00 0.00 0.00
February 0.342526E+10 0.560905E+10 0.459203E+12 0.00 0.00 0.00 0.00 0.00 0.00
March 0.409289E+10 0.666512E+10 0.762947E+12 0.00 0.00 0.00 0.00 0.00 0.00
April 0.363176E+10 0.595330E+10 0.982982E+12 0.00 0.00 0.00 0.00 0.00 0.00
May 0.393418E+10 0.642439E+10 0.254544E+12 0.00 0.00 0.00 0.00 0.00 0.00
June 0.392325E+10 0.639333E+10 0.492345E+12 0.00 0.00 0.00 0.00 0.00 0.00
July 0.364269E+10 0.598436E+10 0.762947E+12 0.00 0.00 0.00 0.00 0.00 0.00
August 0.409289E+10 0.666512E+10 0.101578E+13 0.00 0.00 0.00 0.00 0.00 0.00
September 0.363176E+10 0.595330E+10 0.246344E+12 0.00 0.00 0.00 0.00 0.00 0.00
October 0.377547E+10 0.618367E+10 0.508746E+12 0.00 0.00 0.00 0.00 0.00 0.00
November 0.373861E+10 0.611120E+10 0.738006E+12 0.00 0.00 0.00 0.00 0.00 0.00
December 0.364269E+10 0.598436E+10 0.101681E+13 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.453069E+11 0.741109E+11 0.749486E+13 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.342526E+10 0.560905E+10 0.246344E+12 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.409289E+10 0.666512E+10 0.101681E+13 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: GROUNDFLOOR_PLENUM

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.366494E+10
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.386250E+10
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 367766.06 0.245203E+10
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.199330E+10
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 474303.74 0.112692E+10
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 14123899.12 0.635600E+09
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 37996869.10 0.359520E+09
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 31121599.16 0.427421E+09
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1641266.42 0.674657E+09
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.156821E+10
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.216880E+10
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.399641E+10
                   
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00 85725703.60 0.229303E+11
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.359520E+09
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 37996869.10 0.399641E+10



Table of Contents

Report: SpaceGainsMonthly

For: MIDFLOOR_PLENUM

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.599398E+10
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.633791E+10
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1099800.92 0.410325E+10
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.334093E+10
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1652789.12 0.193850E+10
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 30160215.88 0.110280E+10
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 67208183.29 0.632125E+09
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 58718327.75 0.755131E+09
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 3082205.87 0.116542E+10
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.262384E+10
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.355327E+10
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.648009E+10
                   
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.161922E+09 0.380272E+11
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.632125E+09
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 67208183.29 0.648009E+10



Table of Contents

Report: SpaceGainsMonthly

For: TOPFLOOR_PLENUM

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.637060E+10
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.677126E+10
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 79618.09 0.433143E+10
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.357010E+10
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 80186.89 0.220114E+10
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 16492240.05 0.130409E+10
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 48325841.52 0.785450E+09
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 37979996.57 0.889275E+09
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1582187.45 0.129141E+10
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.268229E+10
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.357985E+10
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.677161E+10
                   
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.104540E+09 0.405485E+11
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.785450E+09
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 48325841.52 0.677161E+10



Table of Contents

Report: PeakSpaceGainsMonthly

For: BASEMENT

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 17832.21 02-JAN-10:09 22950.34 02-JAN-08:09 13457.54 01-JAN-00:10 0.00 0.00 0.00 0.00 0.00 0.00
February 17832.21 01-FEB-10:09 22950.34 01-FEB-08:09 13457.54 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00 0.00
March 17832.21 01-MAR-10:09 22950.34 01-MAR-08:09 13457.54 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00 0.00
April 17832.21 03-APR-09:09 22950.34 03-APR-07:10 13457.54 01-APR-00:10 0.00 0.00 0.00 0.00 0.00 0.00
May 17832.21 01-MAY-09:09 22950.34 01-MAY-07:10 13457.54 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00 0.00
June 17832.21 01-JUN-09:09 22950.34 01-JUN-07:10 13457.54 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00 0.00
July 17832.21 03-JUL-09:09 22950.34 03-JUL-07:10 13457.54 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00 0.00
August 17832.21 01-AUG-09:09 22950.34 01-AUG-07:10 13457.54 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00 0.00
September 17832.21 01-SEP-09:09 22950.34 01-SEP-07:10 13457.54 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00 0.00
October 17832.21 02-OCT-09:09 22950.34 02-OCT-07:10 13457.54 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00 0.00
November 17832.21 01-NOV-09:09 22950.34 01-NOV-07:10 13457.54 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00 0.00
December 17832.21 01-DEC-10:09 22950.34 01-DEC-08:09 13457.54 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average             0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 17832.21   22950.34   13457.54   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 17832.21   22950.34   13457.54   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: CORE_BOTTOM

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 16014.58 02-JAN-10:09 20611.01 02-JAN-08:09 17206.63 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 0.00
February 16014.58 01-FEB-10:09 20611.01 01-FEB-08:09 17206.63 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 0.00
March 16014.58 01-MAR-10:09 20611.01 01-MAR-08:09 17206.63 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 0.00
April 16014.58 03-APR-09:09 20611.01 03-APR-07:10 17206.63 03-APR-07:10 0.00 0.00 0.00 0.00 0.00 0.00
May 16014.58 01-MAY-09:09 20611.01 01-MAY-07:10 17206.63 01-MAY-07:10 0.00 0.00 0.00 0.00 0.00 0.00
June 16014.58 01-JUN-09:09 20611.01 01-JUN-07:10 17206.63 01-JUN-07:10 0.00 0.00 0.00 0.00 0.00 0.00
July 16014.58 03-JUL-09:09 20611.01 03-JUL-07:10 17206.63 03-JUL-07:10 0.00 0.00 0.00 0.00 0.00 0.00
August 16014.58 01-AUG-09:09 20611.01 01-AUG-07:10 17206.63 01-AUG-07:10 0.00 0.00 0.00 0.00 0.00 0.00
September 16014.58 01-SEP-09:09 20611.01 01-SEP-07:10 17206.63 01-SEP-07:10 0.00 0.00 0.00 0.00 0.00 0.00
October 16014.58 02-OCT-09:09 20611.01 02-OCT-07:10 17206.63 02-OCT-07:10 0.00 0.00 0.00 0.00 0.00 0.00
November 16014.58 01-NOV-09:09 20611.01 01-NOV-07:10 17206.63 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 0.00
December 16014.58 01-DEC-10:09 20611.01 01-DEC-08:09 17206.63 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average             0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 16014.58   20611.01   17206.63   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 16014.58   20611.01   17206.63   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: CORE_MID

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 16014.58 02-JAN-10:09 20611.01 02-JAN-08:09 17206.56 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 0.00
February 16014.58 01-FEB-10:09 20611.01 01-FEB-08:09 17206.56 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 0.00
March 16014.58 01-MAR-10:09 20611.01 01-MAR-08:09 17206.56 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 0.00
April 16014.58 03-APR-09:09 20611.01 03-APR-07:10 17206.56 03-APR-07:10 0.00 0.00 0.00 0.00 0.00 0.00
May 16014.58 01-MAY-09:09 20611.01 01-MAY-07:10 17206.56 01-MAY-07:10 0.00 0.00 0.00 0.00 0.00 0.00
June 16014.58 01-JUN-09:09 20611.01 01-JUN-07:10 17206.56 01-JUN-07:10 0.00 0.00 0.00 0.00 0.00 0.00
July 16014.58 03-JUL-09:09 20611.01 03-JUL-07:10 17206.56 03-JUL-07:10 0.00 0.00 0.00 0.00 0.00 0.00
August 16014.58 01-AUG-09:09 20611.01 01-AUG-07:10 17206.56 01-AUG-07:10 0.00 0.00 0.00 0.00 0.00 0.00
September 16014.58 01-SEP-09:09 20611.01 01-SEP-07:10 17206.56 01-SEP-07:10 0.00 0.00 0.00 0.00 0.00 0.00
October 16014.58 02-OCT-09:09 20611.01 02-OCT-07:10 17206.56 02-OCT-07:10 0.00 0.00 0.00 0.00 0.00 0.00
November 16014.58 01-NOV-09:09 20611.01 01-NOV-07:10 17206.56 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 0.00
December 16014.58 01-DEC-10:09 20611.01 01-DEC-08:09 17206.56 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average             0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 16014.58   20611.01   17206.56   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 16014.58   20611.01   17206.56   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: CORE_TOP

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 16014.58 02-JAN-10:09 20611.01 02-JAN-08:09 17206.56 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 0.00
February 16014.58 01-FEB-10:09 20611.01 01-FEB-08:09 17206.56 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 0.00
March 16014.58 01-MAR-10:09 20611.01 01-MAR-08:09 17206.56 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 0.00
April 16014.58 03-APR-09:09 20611.01 03-APR-07:10 17206.56 03-APR-07:10 0.00 0.00 0.00 0.00 0.00 0.00
May 16014.58 01-MAY-09:09 20611.01 01-MAY-07:10 17206.56 01-MAY-07:10 0.00 0.00 0.00 0.00 0.00 0.00
June 16014.58 01-JUN-09:09 20611.01 01-JUN-07:10 17206.56 01-JUN-07:10 0.00 0.00 0.00 0.00 0.00 0.00
July 16014.58 03-JUL-09:09 20611.01 03-JUL-07:10 17206.56 03-JUL-07:10 0.00 0.00 0.00 0.00 0.00 0.00
August 16014.58 01-AUG-09:09 20611.01 01-AUG-07:10 17206.56 01-AUG-07:10 0.00 0.00 0.00 0.00 0.00 0.00
September 16014.58 01-SEP-09:09 20611.01 01-SEP-07:10 17206.56 01-SEP-07:10 0.00 0.00 0.00 0.00 0.00 0.00
October 16014.58 02-OCT-09:09 20611.01 02-OCT-07:10 17206.56 02-OCT-07:10 0.00 0.00 0.00 0.00 0.00 0.00
November 16014.58 01-NOV-09:09 20611.01 01-NOV-07:10 17206.56 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 0.00
December 16014.58 01-DEC-10:09 20611.01 01-DEC-08:09 17206.56 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average             0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 16014.58   20611.01   17206.56   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 16014.58   20611.01   17206.56   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 2010.79 02-JAN-10:09 2587.92 02-JAN-16:40 2160.55 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:03 3036.42 12-JAN-05:57
February 2010.79 01-FEB-10:09 2587.92 01-FEB-08:09 2160.55 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 01-FEB-00:03 3131.71 13-FEB-05:51
March 2010.79 01-MAR-10:09 1803.00 13-MAR-07:10 2160.55 01-MAR-08:09 0.00 0.00 0.00 0.00 24.33 15-MAR-14:00 1896.88 02-MAR-01:00
April 2010.79 03-APR-09:09 1803.00 12-APR-07:10 2160.55 03-APR-07:10 0.00 0.00 0.00 0.00 0.00 01-APR-00:10 1823.13 16-APR-01:55
May 2010.79 01-MAY-09:09 1350.81 10-MAY-07:10 2160.55 01-MAY-07:10 0.00 0.00 0.00 0.00 25.77 14-MAY-15:10 1064.13 29-MAY-14:00
June 2010.79 01-JUN-09:09 1231.33 01-JUN-07:10 2160.55 01-JUN-07:10 0.00 0.00 0.00 0.00 134.11 17-JUN-17:02 891.90 13-JUN-03:00
July 2010.79 03-JUL-09:09 1350.81 11-JUL-07:10 2160.55 03-JUL-07:10 0.00 0.00 0.00 0.00 230.88 21-JUL-02:30 666.09 06-JUL-02:00
August 2010.79 01-AUG-09:09 1350.81 21-AUG-07:10 2160.55 01-AUG-07:10 0.00 0.00 0.00 0.00 264.15 13-AUG-12:52 420.47 30-AUG-21:10
September 2010.79 01-SEP-09:09 1803.00 26-SEP-07:10 2160.55 01-SEP-07:10 0.00 0.00 0.00 0.00 52.24 16-SEP-17:02 775.85 29-SEP-04:00
October 2010.79 02-OCT-09:09 2587.92 30-OCT-07:10 2160.55 02-OCT-07:10 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 1025.54 08-OCT-09:00
November 2010.79 01-NOV-09:09 2587.92 01-NOV-07:10 2160.55 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 1793.16 17-NOV-02:00
December 2010.79 01-DEC-10:09 2587.92 01-DEC-16:19 2160.55 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 2944.20 09-DEC-18:03
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 2010.79   1231.33   2160.55   0.00 0.00 0.00 0.00 0.00   420.47  
Maximum of Months 2010.79   2587.92   2160.55   0.00 0.00 0.00 0.00 264.15   3131.71  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 1295.83 02-JAN-10:09 1667.75 02-JAN-16:40 1392.34 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:03 2024.30 12-JAN-05:55
February 1295.83 01-FEB-10:09 1667.75 01-FEB-16:00 1392.34 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 01-FEB-00:03 2084.91 13-FEB-05:51
March 1295.83 01-MAR-10:09 1161.92 17-MAR-07:10 1392.34 01-MAR-08:09 0.00 0.00 0.00 0.00 16.22 15-MAR-14:00 1278.83 26-MAR-10:00
April 1295.83 03-APR-09:09 947.51 12-APR-07:10 1392.34 03-APR-07:10 0.00 0.00 0.00 0.00 0.00 01-APR-00:10 1183.27 16-APR-07:00
May 1295.83 01-MAY-09:09 870.51 11-MAY-07:10 1392.34 01-MAY-07:10 0.00 0.00 0.00 0.00 59.54 14-MAY-15:10 745.25 29-MAY-14:00
June 1295.83 01-JUN-09:09 793.52 01-JUN-07:10 1392.34 01-JUN-07:10 0.00 0.00 0.00 0.00 114.17 17-JUN-17:02 590.74 13-JUN-03:00
July 1295.83 03-JUL-09:09 870.51 17-JUL-15:39 1392.34 03-JUL-07:10 0.00 0.00 0.00 0.00 209.35 21-JUL-02:10 426.03 06-JUL-02:00
August 1295.83 01-AUG-09:09 870.51 24-AUG-07:10 1392.34 01-AUG-07:10 0.00 0.00 0.00 0.00 201.82 13-AUG-12:50 260.45 30-AUG-21:10
September 1295.83 01-SEP-09:09 947.51 22-SEP-15:30 1392.34 01-SEP-07:10 0.00 0.00 0.00 0.00 52.45 16-SEP-17:02 502.41 29-SEP-04:00
October 1295.83 02-OCT-09:09 1453.34 23-OCT-07:10 1392.34 02-OCT-07:10 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 702.94 08-OCT-09:00
November 1295.83 01-NOV-09:09 1667.75 01-NOV-07:10 1392.34 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 1153.21 17-NOV-02:00
December 1295.83 01-DEC-10:09 1667.75 01-DEC-16:19 1392.34 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 1913.64 09-DEC-18:03
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 1295.83   793.52   1392.34   0.00 0.00 0.00 0.00 0.00   260.45  
Maximum of Months 1295.83   1667.75   1392.34   0.00 0.00 0.00 0.00 209.35   2084.91  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 2010.83 02-JAN-10:09 2587.98 02-JAN-16:49 2160.58 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:03 3036.43 12-JAN-05:55
February 2010.83 01-FEB-10:09 2255.25 01-FEB-08:09 2160.58 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 01-FEB-00:03 3118.89 13-FEB-05:51
March 2010.83 01-MAR-10:09 1803.04 13-MAR-07:10 2160.58 01-MAR-08:09 0.00 0.00 0.00 0.00 24.01 15-MAR-14:00 1963.33 02-MAR-01:00
April 2010.83 03-APR-09:09 1803.04 12-APR-07:10 2160.58 03-APR-07:10 0.00 0.00 0.00 0.00 0.00 01-APR-00:10 1728.40 16-APR-01:55
May 2010.83 01-MAY-09:09 1350.84 10-MAY-07:10 2160.58 01-MAY-07:10 0.00 0.00 0.00 0.00 18.67 10-MAY-14:00 1121.70 29-MAY-14:00
June 2010.83 01-JUN-09:09 1350.84 19-JUN-07:10 2160.58 01-JUN-07:10 0.00 0.00 0.00 0.00 148.36 17-JUN-17:02 892.14 13-JUN-03:00
July 2010.83 03-JUL-09:09 1350.84 11-JUL-07:10 2160.58 03-JUL-07:10 0.00 0.00 0.00 0.00 249.80 21-JUL-02:10 657.98 06-JUL-02:00
August 2010.83 01-AUG-09:09 1350.84 21-AUG-07:10 2160.58 01-AUG-07:10 0.00 0.00 0.00 0.00 266.38 13-AUG-13:26 413.07 30-AUG-21:10
September 2010.83 01-SEP-09:09 1803.04 26-SEP-07:10 2160.58 01-SEP-07:10 0.00 0.00 0.00 0.00 48.60 16-SEP-13:00 748.14 29-SEP-04:00
October 2010.83 02-OCT-09:09 2255.25 23-OCT-07:10 2160.58 02-OCT-07:10 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 1013.07 08-OCT-09:00
November 2010.83 01-NOV-09:09 2587.98 01-NOV-07:10 2160.58 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 1750.42 17-NOV-02:00
December 2010.83 01-DEC-10:09 2587.98 01-DEC-16:19 2160.58 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 2900.11 09-DEC-18:03
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 2010.83   1350.84   2160.58   0.00 0.00 0.00 0.00 0.00   413.07  
Maximum of Months 2010.83   2587.98   2160.58   0.00 0.00 0.00 0.00 266.38   3118.89  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 1295.83 02-JAN-10:09 1667.75 02-JAN-16:49 1392.33 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:03 2024.26 12-JAN-06:00
February 1295.83 01-FEB-10:09 1667.75 01-FEB-08:09 1392.33 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 01-FEB-00:03 2094.54 13-FEB-05:51
March 1295.83 01-MAR-10:09 1453.34 13-MAR-07:10 1392.33 01-MAR-08:09 0.00 0.00 0.00 0.00 16.22 15-MAR-14:00 1407.77 02-MAR-01:00
April 1295.83 03-APR-09:09 1161.92 12-APR-07:10 1392.33 03-APR-07:10 0.00 0.00 0.00 0.00 0.00 01-APR-00:10 1335.54 16-APR-01:55
May 1295.83 01-MAY-09:09 947.51 11-MAY-07:10 1392.33 01-MAY-07:10 0.00 0.00 0.00 0.00 12.45 10-MAY-14:00 806.41 29-MAY-15:20
June 1295.83 01-JUN-09:09 870.51 07-JUN-07:10 1392.33 01-JUN-07:10 0.00 0.00 0.00 0.00 72.48 12-JUN-13:00 656.16 13-JUN-03:00
July 1295.83 03-JUL-09:09 947.51 11-JUL-07:10 1392.33 03-JUL-07:10 0.00 0.00 0.00 0.00 147.97 21-JUL-02:10 524.97 06-JUL-02:00
August 1295.83 01-AUG-09:09 947.51 21-AUG-07:10 1392.33 01-AUG-07:10 0.00 0.00 0.00 0.00 186.01 13-AUG-12:48 373.53 27-AUG-16:50
September 1295.83 01-SEP-09:09 1238.92 26-SEP-07:10 1392.33 01-SEP-07:10 0.00 0.00 0.00 0.00 32.40 16-SEP-13:00 545.40 29-SEP-04:00
October 1295.83 02-OCT-09:09 1667.75 30-OCT-07:10 1392.33 02-OCT-07:10 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 739.44 08-OCT-09:00
November 1295.83 01-NOV-09:09 1667.75 01-NOV-07:10 1392.33 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 1306.53 17-NOV-02:00
December 1295.83 01-DEC-10:09 1667.75 01-DEC-16:19 1392.33 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 2066.70 09-DEC-18:10
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 1295.83   870.51   1392.33   0.00 0.00 0.00 0.00 0.00   373.53  
Maximum of Months 1295.83   1667.75   1392.33   0.00 0.00 0.00 0.00 186.01   2094.54  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 2010.79 02-JAN-10:09 2587.92 02-JAN-16:40 2160.55 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:03 6887.72 12-JAN-05:50
February 2010.79 01-FEB-10:09 2587.92 01-FEB-08:09 2160.55 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 01-FEB-00:03 6760.28 13-FEB-06:00
March 2010.79 01-MAR-10:09 1803.00 13-MAR-07:10 2160.55 01-MAR-08:09 0.00 0.00 0.00 0.00 54.11 15-MAR-14:00 4090.53 02-MAR-05:10
April 2010.79 03-APR-09:09 1803.00 12-APR-07:10 2160.55 03-APR-07:10 0.00 0.00 0.00 0.00 0.00 01-APR-00:10 3441.66 16-APR-01:55
May 2010.79 01-MAY-09:09 1350.81 10-MAY-07:10 2160.55 01-MAY-07:10 0.00 0.00 0.00 0.00 164.38 14-MAY-15:00 2165.86 29-MAY-13:55
June 2010.79 01-JUN-09:09 1231.33 01-JUN-07:10 2160.55 01-JUN-07:10 0.00 0.00 0.00 0.00 328.70 17-JUN-17:02 1898.80 13-JUN-03:00
July 2010.79 03-JUL-09:09 1350.81 11-JUL-07:10 2160.55 03-JUL-07:10 0.00 0.00 0.00 0.00 461.19 21-JUL-03:00 1377.55 06-JUL-02:00
August 2010.79 01-AUG-09:09 1350.81 21-AUG-07:10 2160.55 01-AUG-07:10 0.00 0.00 0.00 0.00 620.82 13-AUG-12:52 912.43 30-AUG-21:10
September 2010.79 01-SEP-09:09 1803.00 26-SEP-07:10 2160.55 01-SEP-07:10 0.00 0.00 0.00 0.00 135.08 16-SEP-17:02 1557.74 29-SEP-04:00
October 2010.79 02-OCT-09:09 2587.92 30-OCT-07:10 2160.55 02-OCT-07:10 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 1963.22 08-OCT-09:00
November 2010.79 01-NOV-09:09 2587.92 01-NOV-07:10 2160.55 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 3517.78 17-NOV-05:57
December 2010.79 01-DEC-10:09 2587.92 01-DEC-16:19 2160.55 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 6265.80 09-DEC-18:03
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 2010.79   1231.33   2160.55   0.00 0.00 0.00 0.00 0.00   912.43  
Maximum of Months 2010.79   2587.92   2160.55   0.00 0.00 0.00 0.00 620.82   6887.72  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 1239.33 02-JAN-08:09 1667.75 02-JAN-16:40 1392.34 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:03 4738.35 12-JAN-05:47
February 1239.33 01-FEB-08:09 1667.75 01-FEB-16:00 1392.34 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 01-FEB-00:03 4952.65 13-FEB-05:59
March 1239.33 01-MAR-08:09 1161.92 17-MAR-07:10 1392.34 01-MAR-08:09 0.00 0.00 0.00 0.00 36.06 15-MAR-14:00 2727.71 02-MAR-05:04
April 1239.33 03-APR-07:10 947.51 12-APR-07:10 1392.34 03-APR-07:10 0.00 0.00 0.00 0.00 0.00 01-APR-00:10 2315.08 16-APR-07:00
May 1239.33 01-MAY-07:10 870.51 11-MAY-07:10 1392.34 01-MAY-07:10 0.00 0.00 0.00 0.00 169.38 14-MAY-15:00 1665.19 29-MAY-13:55
June 1239.33 01-JUN-07:10 793.52 01-JUN-07:10 1392.34 01-JUN-07:10 0.00 0.00 0.00 0.00 269.58 17-JUN-17:02 1282.94 13-JUN-03:00
July 1239.33 03-JUL-07:10 793.52 03-JUL-07:10 1392.34 03-JUL-07:10 0.00 0.00 0.00 0.00 403.88 21-JUL-03:00 912.76 06-JUL-02:00
August 1239.33 01-AUG-07:10 870.51 28-AUG-15:30 1392.34 01-AUG-07:10 0.00 0.00 0.00 0.00 475.29 13-AUG-13:10 578.20 30-AUG-21:10
September 1239.33 01-SEP-07:10 947.51 26-SEP-07:10 1392.34 01-SEP-07:10 0.00 0.00 0.00 0.00 124.60 16-SEP-17:02 1011.58 29-SEP-04:00
October 1239.33 02-OCT-07:10 1453.34 23-OCT-07:10 1392.34 02-OCT-07:10 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 1384.16 08-OCT-09:00
November 1239.33 01-NOV-07:10 1667.75 01-NOV-07:10 1392.34 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 2345.20 17-NOV-06:00
December 1239.33 01-DEC-08:09 1667.75 01-DEC-16:19 1392.34 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 4145.71 09-DEC-18:03
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 1239.33   793.52   1392.34   0.00 0.00 0.00 0.00 0.00   578.20  
Maximum of Months 1239.33   1667.75   1392.34   0.00 0.00 0.00 0.00 475.29   4952.65  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 2010.83 02-JAN-10:09 2587.98 02-JAN-16:49 2160.58 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:03 7107.49 12-JAN-05:50
February 2010.83 01-FEB-10:09 2255.25 01-FEB-08:09 2160.58 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 01-FEB-00:03 7329.91 13-FEB-06:00
March 2010.83 01-MAR-10:09 1803.04 13-MAR-07:10 2160.58 01-MAR-08:09 0.00 0.00 0.00 0.00 53.64 15-MAR-14:00 4480.17 26-MAR-13:00
April 2010.83 03-APR-09:09 1803.04 12-APR-07:10 2160.58 03-APR-07:10 0.00 0.00 0.00 0.00 0.00 01-APR-00:10 3449.86 16-APR-01:55
May 2010.83 01-MAY-09:09 1350.84 10-MAY-07:10 2160.58 01-MAY-07:10 0.00 0.00 0.00 0.00 41.51 10-MAY-14:00 2444.98 29-MAY-14:00
June 2010.83 01-JUN-09:09 1231.36 01-JUN-07:10 2160.58 01-JUN-07:10 0.00 0.00 0.00 0.00 357.98 17-JUN-17:02 1926.43 13-JUN-03:00
July 2010.83 03-JUL-09:09 1350.84 11-JUL-07:10 2160.58 03-JUL-07:10 0.00 0.00 0.00 0.00 500.97 21-JUL-03:00 1387.07 06-JUL-02:00
August 2010.83 01-AUG-09:09 1350.84 21-AUG-07:10 2160.58 01-AUG-07:10 0.00 0.00 0.00 0.00 612.28 13-AUG-13:04 903.45 30-AUG-21:10
September 2010.83 01-SEP-09:09 1803.04 26-SEP-07:10 2160.58 01-SEP-07:10 0.00 0.00 0.00 0.00 110.11 16-SEP-13:00 1563.45 29-SEP-04:00
October 2010.83 02-OCT-09:09 2255.25 23-OCT-07:10 2160.58 02-OCT-07:10 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 2207.69 09-OCT-11:50
November 2010.83 01-NOV-09:09 2587.98 01-NOV-07:10 2160.58 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 3519.67 17-NOV-02:00
December 2010.83 01-DEC-10:09 2587.98 01-DEC-16:19 2160.58 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 6346.61 09-DEC-18:03
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 2010.83   1231.36   2160.58   0.00 0.00 0.00 0.00 0.00   903.45  
Maximum of Months 2010.83   2587.98   2160.58   0.00 0.00 0.00 0.00 612.28   7329.91  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 1295.83 02-JAN-10:09 1667.75 02-JAN-16:49 1392.33 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:03 4738.29 12-JAN-05:42
February 1295.83 01-FEB-10:09 1667.75 01-FEB-08:09 1392.33 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 01-FEB-00:03 4952.78 13-FEB-06:00
March 1295.83 01-MAR-10:09 1453.34 17-MAR-07:10 1392.33 01-MAR-08:09 0.00 0.00 0.00 0.00 36.07 15-MAR-14:00 2983.63 25-MAR-17:10
April 1295.83 03-APR-09:09 1161.92 12-APR-07:10 1392.33 03-APR-07:10 0.00 0.00 0.00 0.00 0.00 01-APR-00:10 2335.25 16-APR-01:55
May 1295.83 01-MAY-09:09 947.51 11-MAY-07:10 1392.33 01-MAY-07:10 0.00 0.00 0.00 0.00 27.68 10-MAY-14:00 1740.73 29-MAY-15:00
June 1295.83 01-JUN-09:09 870.51 07-JUN-07:10 1392.33 01-JUN-07:10 0.00 0.00 0.00 0.00 166.55 12-JUN-13:00 1317.27 13-JUN-03:00
July 1295.83 03-JUL-09:09 870.51 11-JUL-07:10 1392.33 03-JUL-07:10 0.00 0.00 0.00 0.00 388.15 21-JUL-03:00 972.33 06-JUL-02:00
August 1295.83 01-AUG-09:09 947.51 24-AUG-07:10 1392.33 01-AUG-07:10 0.00 0.00 0.00 0.00 494.55 13-AUG-13:10 803.40 27-AUG-16:30
September 1295.83 01-SEP-09:09 1161.92 14-SEP-07:10 1392.33 01-SEP-07:10 0.00 0.00 0.00 0.00 73.40 16-SEP-13:00 1025.05 29-SEP-04:00
October 1295.83 02-OCT-09:09 1667.75 30-OCT-07:10 1392.33 02-OCT-07:10 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 1354.49 08-OCT-09:00
November 1295.83 01-NOV-09:09 1667.75 01-NOV-07:10 1392.33 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 2345.05 17-NOV-05:55
December 1295.83 01-DEC-10:09 1667.75 01-DEC-16:19 1392.33 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 4233.75 09-DEC-18:03
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 1295.83   870.51   1392.33   0.00 0.00 0.00 0.00 0.00   803.40  
Maximum of Months 1295.83   1667.75   1392.33   0.00 0.00 0.00 0.00 494.55   4952.78  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 2010.79 02-JAN-10:09 2587.92 02-JAN-16:40 2160.55 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:03 8184.17 12-JAN-05:40
February 2010.79 01-FEB-10:09 2587.92 01-FEB-16:00 2160.55 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 01-FEB-00:03 7871.75 13-FEB-06:00
March 2010.79 01-MAR-10:09 1803.00 13-MAR-07:10 2160.55 01-MAR-08:09 0.00 0.00 0.00 0.00 63.50 15-MAR-14:00 4837.96 02-MAR-05:20
April 2010.79 03-APR-09:09 1803.00 12-APR-07:10 2160.55 03-APR-07:10 0.00 0.00 0.00 0.00 0.00 01-APR-00:10 4146.95 04-APR-21:03
May 2010.79 01-MAY-09:09 1350.81 10-MAY-07:10 2160.55 01-MAY-07:10 0.00 0.00 0.00 0.00 109.58 14-MAY-14:50 2546.69 29-MAY-13:55
June 2010.79 01-JUN-09:09 1231.33 01-JUN-07:10 2160.55 01-JUN-07:10 0.00 0.00 0.00 0.00 367.28 17-JUN-17:02 2286.93 13-JUN-03:00
July 2010.79 03-JUL-09:09 1350.81 11-JUL-07:10 2160.55 03-JUL-07:10 0.00 0.00 0.00 0.00 603.91 21-JUL-03:06 1629.37 06-JUL-02:00
August 2010.79 01-AUG-09:09 1350.81 21-AUG-07:10 2160.55 01-AUG-07:10 0.00 0.00 0.00 0.00 741.51 13-AUG-13:08 1100.83 30-AUG-21:10
September 2010.79 01-SEP-09:09 1803.00 26-SEP-07:10 2160.55 01-SEP-07:10 0.00 0.00 0.00 0.00 131.89 16-SEP-13:00 1728.99 29-SEP-04:17
October 2010.79 02-OCT-09:09 2587.92 30-OCT-07:10 2160.55 02-OCT-07:10 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 2348.07 30-OCT-05:00
November 2010.79 01-NOV-09:09 2587.92 01-NOV-07:10 2160.55 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 4399.14 17-NOV-05:57
December 2010.79 01-DEC-10:09 2587.92 01-DEC-16:19 2160.55 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 7496.65 09-DEC-18:03
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 2010.79   1231.33   2160.55   0.00 0.00 0.00 0.00 0.00   1100.83  
Maximum of Months 2010.79   2587.92   2160.55   0.00 0.00 0.00 0.00 741.51   8184.17  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 1295.83 02-JAN-10:09 1667.75 02-JAN-16:40 1392.34 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:03 5942.06 12-JAN-05:59
February 1295.83 01-FEB-10:09 1667.75 01-FEB-16:00 1392.34 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 01-FEB-00:03 6171.64 13-FEB-06:00
March 1295.83 01-MAR-10:09 1161.92 17-MAR-07:10 1392.34 01-MAR-08:09 0.00 0.00 0.00 0.00 42.33 15-MAR-14:00 3353.67 02-MAR-05:16
April 1295.83 03-APR-09:09 947.51 12-APR-07:10 1392.34 03-APR-07:10 0.00 0.00 0.00 0.00 0.00 01-APR-00:10 2762.74 04-APR-21:03
May 1295.83 01-MAY-09:09 870.51 11-MAY-07:10 1392.34 01-MAY-07:10 0.00 0.00 0.00 0.00 137.02 14-MAY-14:50 1972.05 29-MAY-13:55
June 1295.83 01-JUN-09:09 793.52 01-JUN-07:10 1392.34 01-JUN-07:10 0.00 0.00 0.00 0.00 306.36 17-JUN-17:02 1547.79 13-JUN-03:00
July 1295.83 03-JUL-09:09 793.52 03-JUL-07:10 1392.34 03-JUL-07:10 0.00 0.00 0.00 0.00 494.30 21-JUL-03:10 1079.85 06-JUL-02:00
August 1295.83 01-AUG-09:09 870.51 28-AUG-15:30 1392.34 01-AUG-07:10 0.00 0.00 0.00 0.00 584.79 13-AUG-13:10 698.57 30-AUG-21:10
September 1295.83 01-SEP-09:09 947.51 26-SEP-07:10 1392.34 01-SEP-07:10 0.00 0.00 0.00 0.00 124.82 16-SEP-17:02 1151.34 29-SEP-04:20
October 1295.83 02-OCT-09:09 1453.34 23-OCT-07:10 1392.34 02-OCT-07:10 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 1570.98 30-OCT-05:00
November 1295.83 01-NOV-09:09 1667.75 01-NOV-07:10 1392.34 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 2932.70 17-NOV-05:57
December 1295.83 01-DEC-10:09 1667.75 01-DEC-16:19 1392.34 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 4973.74 09-DEC-18:03
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 1295.83   793.52   1392.34   0.00 0.00 0.00 0.00 0.00   698.57  
Maximum of Months 1295.83   1667.75   1392.34   0.00 0.00 0.00 0.00 584.79   6171.64  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 2010.83 02-JAN-10:09 2587.98 02-JAN-16:49 2160.58 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:03 8838.54 12-JAN-06:00
February 2010.83 01-FEB-10:09 2255.25 01-FEB-08:09 2160.58 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 01-FEB-00:03 8690.01 13-FEB-06:00
March 2010.83 01-MAR-10:09 1803.04 13-MAR-07:10 2160.58 01-MAR-08:09 0.00 0.00 0.00 0.00 62.81 15-MAR-14:00 5030.46 02-MAR-05:16
April 2010.83 03-APR-09:09 1803.04 12-APR-07:10 2160.58 03-APR-07:10 0.00 0.00 0.00 0.00 0.00 01-APR-00:10 4146.71 04-APR-21:03
May 2010.83 01-MAY-09:09 1350.84 10-MAY-07:10 2160.58 01-MAY-07:10 0.00 0.00 0.00 0.00 48.71 10-MAY-14:00 2885.42 29-MAY-14:00
June 2010.83 01-JUN-09:09 1231.36 01-JUN-07:10 2160.58 01-JUN-07:10 0.00 0.00 0.00 0.00 412.55 17-JUN-17:02 2320.40 13-JUN-03:00
July 2010.83 03-JUL-09:09 1350.84 11-JUL-07:10 2160.58 03-JUL-07:10 0.00 0.00 0.00 0.00 685.93 21-JUL-03:08 1638.41 06-JUL-02:00
August 2010.83 01-AUG-09:09 1350.84 21-AUG-07:10 2160.58 01-AUG-07:10 0.00 0.00 0.00 0.00 758.57 13-AUG-13:04 1147.39 20-AUG-15:00
September 2010.83 01-SEP-09:09 1803.04 26-SEP-07:10 2160.58 01-SEP-07:10 0.00 0.00 0.00 0.00 131.89 16-SEP-13:00 1727.00 29-SEP-04:20
October 2010.83 02-OCT-09:09 2255.25 23-OCT-07:10 2160.58 02-OCT-07:10 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 2468.59 09-OCT-12:00
November 2010.83 01-NOV-09:09 2587.98 01-NOV-07:10 2160.58 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 4398.97 17-NOV-06:00
December 2010.83 01-DEC-10:09 2587.98 01-DEC-16:19 2160.58 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 7583.80 09-DEC-18:03
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 2010.83   1231.36   2160.58   0.00 0.00 0.00 0.00 0.00   1147.39  
Maximum of Months 2010.83   2587.98   2160.58   0.00 0.00 0.00 0.00 758.57   8838.54  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 1295.83 02-JAN-10:09 1667.75 02-JAN-16:49 1392.33 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:03 5942.06 12-JAN-05:59
February 1295.83 01-FEB-10:09 1667.75 01-FEB-08:09 1392.33 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 01-FEB-00:03 6172.50 13-FEB-05:59
March 1295.83 01-MAR-10:09 1453.34 17-MAR-07:10 1392.33 01-MAR-08:09 0.00 0.00 0.00 0.00 42.33 15-MAR-14:00 3580.52 25-MAR-17:10
April 1295.83 03-APR-09:09 1161.92 12-APR-07:10 1392.33 03-APR-07:10 0.00 0.00 0.00 0.00 0.00 01-APR-00:10 2767.27 04-APR-21:03
May 1295.83 01-MAY-09:09 947.51 11-MAY-07:10 1392.33 01-MAY-07:10 0.00 0.00 0.00 0.00 32.48 10-MAY-14:00 2116.76 29-MAY-15:10
June 1295.83 01-JUN-09:09 870.51 07-JUN-07:10 1392.33 01-JUN-07:10 0.00 0.00 0.00 0.00 202.53 12-JUN-13:00 1586.65 13-JUN-03:00
July 1295.83 03-JUL-09:09 870.51 11-JUL-07:10 1392.33 03-JUL-07:10 0.00 0.00 0.00 0.00 512.14 21-JUL-03:10 1152.75 06-JUL-02:00
August 1295.83 01-AUG-09:09 947.51 24-AUG-07:10 1392.33 01-AUG-07:10 0.00 0.00 0.00 0.00 590.69 13-AUG-13:10 1017.63 27-AUG-16:50
September 1295.83 01-SEP-09:09 1161.92 14-SEP-07:10 1392.33 01-SEP-07:10 0.00 0.00 0.00 0.00 87.93 16-SEP-13:00 1151.24 29-SEP-04:20
October 1295.83 02-OCT-09:09 1667.75 30-OCT-07:10 1392.33 02-OCT-07:10 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 1570.98 30-OCT-05:00
November 1295.83 01-NOV-09:09 1667.75 01-NOV-07:10 1392.33 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 2932.90 17-NOV-06:00
December 1295.83 01-DEC-10:09 1667.75 01-DEC-16:19 1392.33 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 5092.03 09-DEC-18:03
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 1295.83   870.51   1392.33   0.00 0.00 0.00 0.00 0.00   1017.63  
Maximum of Months 1295.83   1667.75   1392.33   0.00 0.00 0.00 0.00 590.69   6172.50  



Table of Contents

Report: PeakSpaceGainsMonthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 232.27 02-JAN-10:09 578.72 02-JAN-08:09 1948.61 01-JAN-00:10 0.00 0.00 0.00 0.00 0.00 0.00
February 232.27 01-FEB-10:09 578.72 01-FEB-08:09 3897.21 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00 0.00
March 232.27 01-MAR-10:09 578.72 01-MAR-08:09 7794.42 31-MAR-23:10 0.00 0.00 0.00 0.00 0.00 0.00
April 232.27 03-APR-09:09 578.72 03-APR-07:10 7794.42 01-APR-00:10 0.00 0.00 0.00 0.00 0.00 0.00
May 232.27 01-MAY-09:09 578.72 01-MAY-07:10 3897.21 31-MAY-23:10 0.00 0.00 0.00 0.00 0.00 0.00
June 232.27 01-JUN-09:09 578.72 01-JUN-07:10 5845.82 30-JUN-23:10 0.00 0.00 0.00 0.00 0.00 0.00
July 232.27 03-JUL-09:09 578.72 03-JUL-07:10 7794.42 31-JUL-23:10 0.00 0.00 0.00 0.00 0.00 0.00
August 232.27 01-AUG-09:09 578.72 01-AUG-07:10 7794.42 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00 0.00
September 232.27 01-SEP-09:09 578.72 01-SEP-07:10 3897.21 30-SEP-23:10 0.00 0.00 0.00 0.00 0.00 0.00
October 232.27 02-OCT-09:09 578.72 02-OCT-07:10 5845.82 31-OCT-23:10 0.00 0.00 0.00 0.00 0.00 0.00
November 232.27 01-NOV-09:09 578.72 01-NOV-07:10 5845.82 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00 0.00
December 232.27 01-DEC-10:09 578.72 01-DEC-08:09 7794.42 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average             0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 232.27   578.72   1948.61   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 232.27   578.72   7794.42   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: DATACENTER_MID_ZN_6

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 232.27 02-JAN-10:09 578.72 02-JAN-08:09 1948.61 01-JAN-00:10 0.00 0.00 0.00 0.00 0.00 0.00
February 232.27 01-FEB-10:09 578.72 01-FEB-08:09 3897.21 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00 0.00
March 232.27 01-MAR-10:09 578.72 01-MAR-08:09 7794.42 31-MAR-23:10 0.00 0.00 0.00 0.00 0.00 0.00
April 232.27 03-APR-09:09 578.72 03-APR-07:10 7794.42 01-APR-00:10 0.00 0.00 0.00 0.00 0.00 0.00
May 232.27 01-MAY-09:09 578.72 01-MAY-07:10 3897.21 31-MAY-23:10 0.00 0.00 0.00 0.00 0.00 0.00
June 232.27 01-JUN-09:09 578.72 01-JUN-07:10 5845.82 30-JUN-23:10 0.00 0.00 0.00 0.00 0.00 0.00
July 232.27 03-JUL-09:09 578.72 03-JUL-07:10 7794.42 31-JUL-23:10 0.00 0.00 0.00 0.00 0.00 0.00
August 232.27 01-AUG-09:09 578.72 01-AUG-07:10 7794.42 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00 0.00
September 232.27 01-SEP-09:09 578.72 01-SEP-07:10 3897.21 30-SEP-23:10 0.00 0.00 0.00 0.00 0.00 0.00
October 232.27 02-OCT-09:09 578.72 02-OCT-07:10 5845.82 31-OCT-23:10 0.00 0.00 0.00 0.00 0.00 0.00
November 232.27 01-NOV-09:09 578.72 01-NOV-07:10 5845.82 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00 0.00
December 232.27 01-DEC-10:09 578.72 01-DEC-08:09 7794.42 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average             0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 232.27   578.72   1948.61   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 232.27   578.72   7794.42   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 232.27 02-JAN-10:09 578.72 02-JAN-08:09 1948.61 01-JAN-00:10 0.00 0.00 0.00 0.00 0.00 0.00
February 232.27 01-FEB-10:09 578.72 01-FEB-08:09 3897.21 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00 0.00
March 232.27 01-MAR-10:09 578.72 01-MAR-08:09 7794.42 31-MAR-23:10 0.00 0.00 0.00 0.00 0.00 0.00
April 232.27 03-APR-09:09 578.72 03-APR-07:10 7794.42 01-APR-00:10 0.00 0.00 0.00 0.00 0.00 0.00
May 232.27 01-MAY-09:09 578.72 01-MAY-07:10 3897.21 31-MAY-23:10 0.00 0.00 0.00 0.00 0.00 0.00
June 232.27 01-JUN-09:09 578.72 01-JUN-07:10 5845.82 30-JUN-23:10 0.00 0.00 0.00 0.00 0.00 0.00
July 232.27 03-JUL-09:09 578.72 03-JUL-07:10 7794.42 31-JUL-23:10 0.00 0.00 0.00 0.00 0.00 0.00
August 232.27 01-AUG-09:09 578.72 01-AUG-07:10 7794.42 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00 0.00
September 232.27 01-SEP-09:09 578.72 01-SEP-07:10 3897.21 30-SEP-23:10 0.00 0.00 0.00 0.00 0.00 0.00
October 232.27 02-OCT-09:09 578.72 02-OCT-07:10 5845.82 31-OCT-23:10 0.00 0.00 0.00 0.00 0.00 0.00
November 232.27 01-NOV-09:09 578.72 01-NOV-07:10 5845.82 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00 0.00
December 232.27 01-DEC-10:09 578.72 01-DEC-08:09 7794.42 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average             0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 232.27   578.72   1948.61   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 232.27   578.72   7794.42   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 5027.92 02-JAN-10:09 6471.01 02-JAN-08:09 94908.13 01-JAN-00:10 0.00 0.00 0.00 0.00 0.00 0.00
February 5027.92 01-FEB-10:09 6471.01 01-FEB-08:09 189816.26 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00 0.00
March 5027.92 01-MAR-10:09 6471.01 01-MAR-08:09 379632.52 31-MAR-23:10 0.00 0.00 0.00 0.00 0.00 0.00
April 5027.92 03-APR-09:09 6471.01 03-APR-07:10 379632.52 01-APR-00:10 0.00 0.00 0.00 0.00 0.00 0.00
May 5027.92 01-MAY-09:09 6471.01 01-MAY-07:10 189816.26 31-MAY-23:10 0.00 0.00 0.00 0.00 0.00 0.00
June 5027.92 01-JUN-09:09 6471.01 01-JUN-07:10 284724.39 30-JUN-23:10 0.00 0.00 0.00 0.00 0.00 0.00
July 5027.92 03-JUL-09:09 6471.01 03-JUL-07:10 379632.52 31-JUL-23:10 0.00 0.00 0.00 0.00 0.00 0.00
August 5027.92 01-AUG-09:09 6471.01 01-AUG-07:10 379632.52 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00 0.00
September 5027.92 01-SEP-09:09 6471.01 01-SEP-07:10 189816.26 30-SEP-23:10 0.00 0.00 0.00 0.00 0.00 0.00
October 5027.92 02-OCT-09:09 6471.01 02-OCT-07:10 284724.39 31-OCT-23:10 0.00 0.00 0.00 0.00 0.00 0.00
November 5027.92 01-NOV-09:09 6471.01 01-NOV-07:10 284724.39 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00 0.00
December 5027.92 01-DEC-10:09 6471.01 01-DEC-08:09 379632.52 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average             0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 5027.92   6471.01   94908.13   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 5027.92   6471.01   379632.52   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: GROUNDFLOOR_PLENUM

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-JAN-00:03 6500.47 12-JAN-01:53
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-FEB-00:03 6531.83 13-FEB-05:51
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 35.14 15-MAR-14:00 4270.19 02-MAR-01:00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-APR-00:10 4012.96 16-APR-01:55
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 107.24 14-MAY-14:52 1944.16 29-MAY-14:08
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 301.24 17-JUN-17:02 1887.34 13-JUN-03:00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 425.60 21-JUL-02:30 1391.17 06-JUL-02:00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 629.52 13-AUG-13:00 871.64 30-AUG-21:10
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 80.77 16-SEP-17:02 1695.91 29-SEP-04:00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 2185.96 08-OCT-09:00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 3913.55 17-NOV-02:00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 6439.62 09-DEC-18:03
                       
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00        
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00   871.64  
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 629.52   6531.83  



Table of Contents

Report: PeakSpaceGainsMonthly

For: MIDFLOOR_PLENUM

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-JAN-00:03 10741.80 12-JAN-05:51
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-FEB-00:03 10640.48 13-FEB-06:00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 72.97 15-MAR-14:00 6956.78 02-MAR-01:00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-APR-00:10 6618.07 16-APR-01:55
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 312.59 14-MAY-15:00 3181.90 29-MAY-13:55
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 583.42 17-JUN-17:02 3276.24 13-JUN-03:00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 669.87 21-JUL-03:00 2395.47 06-JUL-02:00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1206.03 13-AUG-12:52 1541.59 30-AUG-21:10
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 173.82 16-SEP-17:02 2925.31 29-SEP-04:00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 3652.50 08-OCT-09:00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 6498.36 17-NOV-02:00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 10800.39 09-DEC-18:03
                       
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00        
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00   1541.59  
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1206.03   10800.39  



Table of Contents

Report: PeakSpaceGainsMonthly

For: TOPFLOOR_PLENUM

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-JAN-00:03 11688.16 12-JAN-06:00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-FEB-00:03 11602.42 13-FEB-06:00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 26.69 15-MAR-14:00 7005.27 02-MAR-01:00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-APR-00:10 6403.47 16-APR-03:53
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 18.88 10-MAY-15:00 4266.40 29-MAY-14:00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 492.92 17-JUN-17:02 3661.23 13-JUN-03:00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 707.01 21-JUL-02:20 2590.31 06-JUL-02:00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 899.49 13-AUG-12:52 1707.71 30-AUG-21:03
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 97.96 16-SEP-13:00 2855.47 29-SEP-04:20
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 3373.18 19-OCT-23:00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 6564.89 17-NOV-02:00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 12068.99 09-DEC-18:03
                       
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00        
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00   1707.71  
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 899.49   12068.99  



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: BASEMENT

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 115408.75 02-JAN-04:01 0.00 12749.23 134575.44 0.00 0.00 0.00 0.00 0.00 0.00
February 114069.02 21-FEB-04:01 0.00 10199.39 107660.35 0.00 0.00 0.00 0.00 0.00 0.00
March 115195.23 13-MAR-04:11 0.00 17850.93 94202.81 0.00 0.00 0.00 0.00 0.00 0.00
April 119345.66 10-APR-04:12 0.00 15300.79 80745.26 0.00 0.00 0.00 0.00 0.00 0.00
May 117955.39 30-MAY-04:12 0.00 15300.79 80745.26 0.00 0.00 0.00 0.00 0.00 0.00
June 115054.10 13-JUN-04:12 0.00 12750.66 67287.72 0.00 0.00 0.00 0.00 0.00 0.00
July 123217.92 03-JUL-04:11 0.00 20401.06 107660.35 0.00 0.00 0.00 0.00 0.00 0.00
August 115964.00 01-AUG-04:12 0.00 15300.79 80745.26 0.00 0.00 0.00 0.00 0.00 0.00
September 118950.68 18-SEP-04:12 0.00 15300.79 80745.26 0.00 0.00 0.00 0.00 0.00 0.00
October 119181.64 16-OCT-03:01 0.00 10199.39 107660.35 0.00 0.00 0.00 0.00 0.00 0.00
November 118547.96 20-NOV-05:11 0.00 25501.32 134575.44 0.00 0.00 0.00 0.00 0.00 0.00
December 118832.76 26-DEC-04:01 0.00 12749.23 134575.44 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 114069.02   0.00 10199.39 67287.72 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 123217.92   0.00 25501.32 134575.44 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: CORE_BOTTOM

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 82566.51 19-JAN-06:01 12897.91 18321.59 61179.12 0.00 0.00 0.00 0.00 0.00 0.00
February 85691.33 23-FEB-06:01 11285.67 16031.39 53531.73 0.00 0.00 0.00 0.00 0.00 0.00
March 97498.08 16-MAR-04:13 0.00 16031.39 41563.52 0.00 0.00 0.00 0.00 0.00 0.00
April 98197.65 10-APR-04:12 0.00 13741.19 35625.87 0.00 0.00 0.00 0.00 0.00 0.00
May 99825.77 30-MAY-04:12 0.00 13741.19 35625.87 0.00 0.00 0.00 0.00 0.00 0.00
June 98336.80 02-JUN-04:13 0.00 16031.39 41563.52 0.00 0.00 0.00 0.00 0.00 0.00
July 100974.50 24-JUL-04:13 0.00 16031.39 41563.52 0.00 0.00 0.00 0.00 0.00 0.00
August 97883.24 22-AUG-04:13 0.00 16031.39 41563.52 0.00 0.00 0.00 0.00 0.00 0.00
September 100262.74 18-SEP-04:12 0.00 13741.19 35625.87 0.00 0.00 0.00 0.00 0.00 0.00
October 96499.49 23-OCT-04:12 0.00 11450.99 29688.23 0.00 0.00 0.00 0.00 0.00 0.00
November 97505.41 06-NOV-05:12 0.00 13741.19 35625.87 0.00 0.00 0.00 0.00 0.00 0.00
December 89232.79 15-DEC-05:11 0.00 22901.98 59376.45 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 82566.51   0.00 11450.99 29688.23 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 100974.50   12897.91 22901.98 61179.12 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: CORE_MID

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 23590.05 20-JAN-17:15 9673.43 22900.96 19118.40 0.00 0.00 0.00 0.00 0.00 0.00
February 53399.58 24-FEB-16:15 30632.53 41222.03 34413.13 0.00 0.00 0.00 0.00 0.00 0.00
March 83131.35 17-MAR-05:02 8061.19 11450.99 38236.81 0.00 0.00 0.00 0.00 0.00 0.00
April 79775.53 21-APR-05:02 8061.19 11450.99 38236.81 0.00 0.00 0.00 0.00 0.00 0.00
May 85187.76 30-MAY-04:12 0.00 13741.19 35625.74 0.00 0.00 0.00 0.00 0.00 0.00
June 87644.23 30-JUN-04:12 0.00 13741.19 35625.74 0.00 0.00 0.00 0.00 0.00 0.00
July 88472.70 18-JUL-04:11 0.00 16031.39 41563.36 0.00 0.00 0.00 0.00 0.00 0.00
August 88254.89 09-AUG-04:11 0.00 16031.39 41563.36 0.00 0.00 0.00 0.00 0.00 0.00
September 88732.75 18-SEP-04:12 0.00 13741.19 35625.74 0.00 0.00 0.00 0.00 0.00 0.00
October 83650.27 13-OCT-05:02 8061.19 11450.99 38236.81 0.00 0.00 0.00 0.00 0.00 0.00
November 62572.44 01-NOV-05:03 6448.95 9160.79 30589.44 0.00 0.00 0.00 0.00 0.00 0.00
December 34908.43 04-DEC-14:08 64058.32 82444.06 68826.25 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 23590.05   0.00 9160.79 19118.40 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 88732.75   64058.32 82444.06 68826.25 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: CORE_TOP

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 17914.88 11-JAN-17:00 15316.26 20611.01 17206.56 0.00 0.00 0.00 0.00 0.00 0.00
February 18485.71 17-FEB-17:00 15316.26 20611.01 17206.56 0.00 0.00 0.00 0.00 0.00 0.00
March 80708.17 16-MAR-05:03 6448.95 9160.79 30589.44 0.00 0.00 0.00 0.00 0.00 0.00
April 41251.49 21-APR-16:00 15316.26 20611.01 17206.56 0.00 0.00 0.00 0.00 0.00 0.00
May 80258.97 17-MAY-05:02 8061.19 11450.99 38236.81 0.00 0.00 0.00 0.00 0.00 0.00
June 87980.02 19-JUN-04:12 0.00 13741.19 35625.74 0.00 0.00 0.00 0.00 0.00 0.00
July 87014.28 05-JUL-04:11 0.00 16031.39 41563.36 0.00 0.00 0.00 0.00 0.00 0.00
August 86970.72 11-AUG-04:12 0.00 11450.99 29688.11 0.00 0.00 0.00 0.00 0.00 0.00
September 84583.80 18-SEP-04:12 0.00 13741.19 35625.74 0.00 0.00 0.00 0.00 0.00 0.00
October 69174.32 13-OCT-05:02 8061.19 11450.99 38236.81 0.00 0.00 0.00 0.00 0.00 0.00
November 28729.58 01-NOV-15:20 15316.26 20611.01 17206.56 0.00 0.00 0.00 0.00 0.00 0.00
December 18997.54 01-DEC-17:00 15316.26 20611.01 17206.56 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 17914.88   0.00 9160.79 17206.56 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 87980.02   15316.26 20611.01 41563.36 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 2246.69 17-JAN-16:40 1923.11 2255.20 2160.55 0.00 0.00 0.00 0.00 0.00 190.56
February 2929.02 28-FEB-12:00 5769.33 3693.99 6481.66 0.00 0.00 0.00 0.00 0.00 273.76
March 8943.28 16-MAR-04:11 0.00 2012.90 5218.93 0.00 0.00 0.00 0.00 0.00 183.53
April 7188.60 07-APR-13:30 2010.79 1231.33 2160.55 0.00 0.00 0.00 0.00 0.00 54.69
May 9016.56 24-MAY-05:03 809.73 1002.35 3840.98 0.00 0.00 0.00 0.00 0.00 52.82
June 17495.76 25-JUN-18:21 0.00 547.22 4473.37 0.00 0.00 0.00 0.00 0.00 21.81
July 17476.46 02-JUL-18:21 0.00 684.02 5591.71 0.00 0.00 0.00 0.00 0.00 86.02
August 17693.09 06-AUG-16:21 1012.16 684.02 7201.84 0.00 0.00 0.00 0.00 23.76 0.00
September 11925.49 15-SEP-05:02 1012.16 1437.79 4801.23 0.00 0.00 0.00 0.00 0.00 24.72
October 6051.42 12-OCT-12:10 1923.11 1231.33 2160.55 0.00 0.00 0.00 0.00 0.00 102.87
November 4577.05 27-NOV-12:00 1923.11 1231.33 2160.55 0.00 0.00 0.00 0.00 0.00 172.12
December 2841.23 15-DEC-14:30 2010.79 1231.33 2160.55 0.00 0.00 0.00 0.00 0.00 186.72
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 2246.69   0.00 547.22 2160.55 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 17693.09   5769.33 3693.99 7201.84 0.00 0.00 0.00 0.00 23.76 273.76



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 2455.94 06-JAN-10:25 2591.66 1587.03 2784.68 0.00 0.00 0.00 0.00 0.00 68.84
February 11738.36 28-FEB-10:10 2591.66 1587.03 2784.68 0.00 0.00 0.00 0.00 0.00 134.77
March 10377.25 21-MAR-08:50 2478.65 1587.03 2784.68 0.00 0.00 0.00 0.00 0.00 101.48
April 23638.48 23-APR-09:22 326.14 220.40 2320.57 0.00 0.00 0.00 0.00 0.00 246.94
May 14426.93 31-MAY-08:20 1239.33 793.52 1392.34 0.00 0.00 0.00 0.00 0.00 67.46
June 23634.19 25-JUN-09:02 326.14 220.40 2320.57 0.00 0.00 0.00 0.00 0.00 114.23
July 27822.87 04-JUL-08:31 587.05 396.73 4177.03 0.00 0.00 0.00 0.00 0.00 208.04
August 23679.95 06-AUG-09:01 456.59 308.57 3248.80 0.00 0.00 0.00 0.00 0.00 99.10
September 22188.73 04-SEP-08:52 326.14 220.40 2320.57 0.00 0.00 0.00 0.00 0.00 178.53
October 11220.39 11-OCT-08:50 1239.33 793.52 1392.34 0.00 0.00 0.00 0.00 0.00 36.27
November 6455.52 03-NOV-08:55 2478.65 1587.03 2784.68 0.00 0.00 0.00 0.00 0.00 179.77
December 3645.43 04-DEC-09:45 2478.65 1587.03 2784.68 0.00 0.00 0.00 0.00 0.00 251.24
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 2455.94   326.14 220.40 1392.34 0.00 0.00 0.00 0.00 0.00 36.27
Maximum of Months 27822.87   2591.66 1587.03 4177.03 0.00 0.00 0.00 0.00 0.00 251.24



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 16586.05 15-JAN-13:23 303.66 205.21 2160.58 0.00 0.00 0.00 0.00 0.00 1030.62
February 23094.91 28-FEB-12:00 5769.46 3694.08 6481.75 0.00 0.00 0.00 0.00 0.00 299.05
March 23270.02 07-MAR-13:50 5769.46 3694.08 6481.75 0.00 0.00 0.00 0.00 0.00 271.17
April 26932.35 23-APR-12:43 404.87 273.61 2880.78 0.00 0.00 0.00 0.00 0.00 343.29
May 26022.82 14-MAY-13:02 404.87 273.61 2880.78 0.00 0.00 0.00 0.00 0.00 193.74
June 27098.42 25-JUN-13:02 506.09 342.02 3600.97 0.00 0.00 0.00 0.00 0.00 38.92
July 27682.12 04-JUL-13:12 506.09 342.02 3600.97 0.00 0.00 0.00 0.00 0.00 49.08
August 27739.48 06-AUG-16:21 1012.19 684.04 7201.95 0.00 0.00 0.00 0.00 7.11 0.00
September 27777.75 10-SEP-12:42 506.09 342.02 3600.97 0.00 0.00 0.00 0.00 0.00 331.04
October 27059.54 09-OCT-11:23 404.87 273.61 2880.78 0.00 0.00 0.00 0.00 0.00 823.86
November 18957.35 03-NOV-12:20 1923.15 1231.36 2160.58 0.00 0.00 0.00 0.00 0.00 160.75
December 16290.91 04-DEC-11:30 1923.15 1231.36 2160.58 0.00 0.00 0.00 0.00 0.00 380.41
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 16290.91   303.66 205.21 2160.58 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 27777.75   5769.46 3694.08 7201.95 0.00 0.00 0.00 0.00 7.11 1030.62



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 4192.03 12-JAN-15:30 2478.65 1587.03 2784.67 0.00 0.00 0.00 0.00 0.00 429.58
February 9476.91 28-FEB-16:30 1239.33 793.52 1392.33 0.00 0.00 0.00 0.00 0.00 179.95
March 23923.56 16-MAR-04:11 0.00 1297.19 3363.25 0.00 0.00 0.00 0.00 0.00 131.93
April 28777.83 02-APR-16:12 391.37 264.49 2784.67 0.00 0.00 0.00 0.00 0.00 702.69
May 31840.60 07-MAY-17:11 0.00 352.65 2882.79 0.00 0.00 0.00 0.00 0.00 340.62
June 32758.36 25-JUN-17:41 0.00 396.73 3243.14 0.00 0.00 0.00 0.00 0.00 55.02
July 35902.43 02-JUL-17:01 0.00 440.81 3603.49 0.00 0.00 0.00 0.00 0.00 158.71
August 34000.93 06-AUG-16:21 652.28 440.81 4641.11 0.00 0.00 0.00 0.00 0.00 66.49
September 28834.60 04-SEP-16:52 391.37 264.49 2784.67 0.00 0.00 0.00 0.00 0.00 195.64
October 14386.47 11-OCT-16:00 1239.33 793.52 1392.33 0.00 0.00 0.00 0.00 0.00 5.63
November 11673.30 27-NOV-05:12 0.00 926.56 2402.32 0.00 0.00 0.00 0.00 0.00 314.71
December 7615.44 04-DEC-15:30 1239.33 793.52 1392.33 0.00 0.00 0.00 0.00 0.00 190.08
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 4192.03   0.00 264.49 1392.33 0.00 0.00 0.00 0.00 0.00 5.63
Maximum of Months 35902.43   2478.65 1587.03 4641.11 0.00 0.00 0.00 0.00 0.00 702.69



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 1706.87 21-JAN-17:25 202.43 287.53 1440.37 0.00 0.00 0.00 0.00 0.00 564.03
February 2091.65 14-FEB-15:53 5769.33 3693.99 6481.66 0.00 0.00 0.00 0.00 0.00 132.77
March 6313.43 15-MAR-14:00 2010.79 1231.33 2160.55 0.00 0.00 0.00 0.00 54.11 0.00
April 4526.18 07-APR-13:50 2010.79 1231.33 2160.55 0.00 0.00 0.00 0.00 0.00 149.32
May 7413.33 23-MAY-14:40 1923.11 1231.33 2160.55 0.00 0.00 0.00 0.00 0.00 6.98
June 11385.95 18-JUN-15:01 708.51 478.82 5041.29 0.00 0.00 0.00 0.00 0.00 197.50
July 16800.86 16-JUL-16:31 1012.16 684.02 7201.84 0.00 0.00 0.00 0.00 82.92 0.00
August 11613.27 07-AUG-04:11 0.00 2012.90 5218.93 0.00 0.00 0.00 0.00 0.00 340.88
September 7391.59 15-SEP-14:00 2010.79 1231.33 2160.55 0.00 0.00 0.00 0.00 18.85 0.00
October 4227.11 05-OCT-14:30 1923.11 1231.33 2160.55 0.00 0.00 0.00 0.00 0.00 117.57
November 3126.91 08-NOV-16:10 1923.11 1803.00 2160.55 0.00 0.00 0.00 0.00 0.00 166.43
December 1843.80 01-DEC-13:30 1923.11 1231.33 2160.55 0.00 0.00 0.00 0.00 0.00 586.74
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 1706.87   0.00 287.53 1440.37 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 16800.86   5769.33 3693.99 7201.84 0.00 0.00 0.00 0.00 82.92 586.74



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 2020.25 21-JAN-17:25 130.46 185.29 928.23 0.00 0.00 0.00 0.00 0.00 372.68
February 2954.32 28-FEB-10:00 2478.65 1587.03 2784.68 0.00 0.00 0.00 0.00 0.00 304.26
March 6995.60 14-MAR-10:30 1239.33 793.52 1392.34 0.00 0.00 0.00 0.00 0.00 46.96
April 14043.16 24-APR-07:40 3717.98 2380.55 4177.03 0.00 0.00 0.00 0.00 0.00 169.17
May 25052.15 21-MAY-09:22 326.14 220.40 2320.57 0.00 0.00 0.00 0.00 0.00 1047.70
June 27497.53 11-JUN-08:51 456.59 308.57 3248.80 0.00 0.00 0.00 0.00 0.00 523.60
July 29958.60 04-JUL-08:31 587.05 396.73 4177.03 0.00 0.00 0.00 0.00 0.00 504.69
August 21035.82 20-AUG-09:22 326.14 220.40 2320.57 0.00 0.00 0.00 0.00 0.00 420.23
September 20003.58 04-SEP-09:12 326.14 220.40 2320.57 0.00 0.00 0.00 0.00 0.00 406.63
October 9738.38 17-OCT-08:50 2478.65 1587.03 2784.68 0.00 0.00 0.00 0.00 0.00 158.21
November 4009.01 03-NOV-09:05 0.00 1587.03 2784.68 0.00 0.00 0.00 0.00 0.00 408.05
December 2092.19 04-DEC-10:00 2478.65 1587.03 2784.68 0.00 0.00 0.00 0.00 0.00 534.11
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 2020.25   0.00 185.29 928.23 0.00 0.00 0.00 0.00 0.00 46.96
Maximum of Months 29958.60   3717.98 2380.55 4177.03 0.00 0.00 0.00 0.00 0.00 1047.70



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 14072.27 12-JAN-13:40 3846.30 2462.72 4321.17 0.00 0.00 0.00 0.00 0.00 1659.30
February 18518.98 28-FEB-13:50 1923.15 1231.36 2160.58 0.00 0.00 0.00 0.00 0.00 709.11
March 24424.88 01-MAR-15:45 3846.30 2462.72 4321.17 0.00 0.00 0.00 0.00 0.00 1163.47
April 26980.37 23-APR-13:32 404.87 273.61 2880.78 0.00 0.00 0.00 0.00 0.00 1026.48
May 27467.40 14-MAY-13:32 506.09 342.02 3600.97 0.00 0.00 0.00 0.00 0.00 396.81
June 27377.08 18-JUN-13:02 506.09 342.02 3600.97 0.00 0.00 0.00 0.00 0.00 201.44
July 28889.92 30-JUL-11:52 607.31 410.42 4321.17 0.00 0.00 0.00 0.00 0.00 262.94
August 27247.09 13-AUG-13:42 506.09 342.02 3600.97 0.00 0.00 0.00 0.00 446.25 0.00
September 29493.15 03-SEP-12:32 607.31 410.42 4321.17 0.00 0.00 0.00 0.00 0.00 587.65
October 27902.86 09-OCT-12:32 506.09 342.02 3600.97 0.00 0.00 0.00 0.00 0.00 1782.44
November 19793.08 03-NOV-12:30 1923.15 1231.36 2160.58 0.00 0.00 0.00 0.00 0.00 369.23
December 20662.69 04-DEC-14:16 10054.17 6156.79 10802.92 0.00 0.00 0.00 0.00 0.00 806.43
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 14072.27   404.87 273.61 2160.58 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 29493.15   10054.17 6156.79 10802.92 0.00 0.00 0.00 0.00 446.25 1782.44



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 2572.42 12-JAN-16:00 1239.33 793.52 1392.33 0.00 0.00 0.00 0.00 0.00 948.48
February 5964.01 28-FEB-16:30 1239.33 793.52 1392.33 0.00 0.00 0.00 0.00 0.00 423.96
March 9225.37 01-MAR-15:45 2478.65 1587.03 2784.67 0.00 0.00 0.00 0.00 0.00 787.99
April 18468.20 02-APR-16:41 521.82 352.65 3712.89 0.00 0.00 0.00 0.00 0.00 1583.70
May 29769.69 07-MAY-17:01 0.00 352.65 2882.79 0.00 0.00 0.00 0.00 0.00 816.36
June 31883.93 11-JUN-16:51 652.28 440.81 4641.11 0.00 0.00 0.00 0.00 0.00 320.41
July 30736.65 16-JUL-16:31 652.28 440.81 4641.11 0.00 0.00 0.00 0.00 0.00 94.54
August 27814.39 06-AUG-16:31 456.59 308.57 3248.78 0.00 0.00 0.00 0.00 0.00 8.36
September 26968.58 03-SEP-16:32 391.37 264.49 2784.67 0.00 0.00 0.00 0.00 0.00 340.46
October 12119.40 11-OCT-16:00 1239.33 793.52 1392.33 0.00 0.00 0.00 0.00 0.00 13.84
November 4870.95 15-NOV-15:20 1239.33 793.52 1392.33 0.00 0.00 0.00 0.00 0.00 195.95
December 4871.42 04-DEC-14:08 5183.32 3174.07 5569.33 0.00 0.00 0.00 0.00 0.00 476.41
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 2572.42   0.00 264.49 1392.33 0.00 0.00 0.00 0.00 0.00 8.36
Maximum of Months 31883.93   5183.32 3174.07 5569.33 0.00 0.00 0.00 0.00 0.00 1583.70



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 1491.11 14-JAN-17:03 404.87 575.05 2880.74 0.00 0.00 0.00 0.00 0.00 170.73
February 1495.12 18-FEB-17:03 404.87 400.64 2880.74 0.00 0.00 0.00 0.00 0.00 715.04
March 6879.72 15-MAR-14:30 1923.11 1231.33 2160.55 0.00 0.00 0.00 0.00 46.46 0.00
April 4371.29 20-APR-15:40 1923.11 1231.33 2160.55 0.00 0.00 0.00 0.00 0.00 226.31
May 7666.34 23-MAY-14:40 1923.11 1231.33 2160.55 0.00 0.00 0.00 0.00 0.00 13.21
June 18502.86 18-JUN-15:01 708.51 478.82 5041.29 0.00 0.00 0.00 0.00 0.00 326.59
July 19491.52 16-JUL-16:31 1012.16 684.02 7201.84 0.00 0.00 0.00 0.00 43.53 0.00
August 16679.26 06-AUG-16:31 708.51 478.82 5041.29 0.00 0.00 0.00 0.00 113.41 0.00
September 7787.66 15-SEP-14:00 2010.79 1231.33 2160.55 0.00 0.00 0.00 0.00 21.70 0.00
October 4050.52 12-OCT-15:30 1923.11 1231.33 2160.55 0.00 0.00 0.00 0.00 0.00 273.94
November 2207.88 16-NOV-17:00 1923.11 2587.92 2160.55 0.00 0.00 0.00 0.00 0.00 192.93
December 1654.31 01-DEC-13:20 1923.11 1231.33 2160.55 0.00 0.00 0.00 0.00 0.00 578.55
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 1491.11   404.87 400.64 2160.55 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 19491.52   2010.79 2587.92 7201.84 0.00 0.00 0.00 0.00 113.41 715.04



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 1757.95 14-JAN-17:03 260.91 370.58 1856.46 0.00 0.00 0.00 0.00 0.00 113.28
February 2699.98 28-FEB-10:10 2591.66 1587.03 2784.68 0.00 0.00 0.00 0.00 0.00 381.40
March 6270.43 14-MAR-10:40 1239.33 793.52 1392.34 0.00 0.00 0.00 0.00 0.00 55.44
April 10816.62 24-APR-09:20 2591.66 1587.03 2784.68 0.00 0.00 0.00 0.00 0.00 217.25
May 17969.71 21-MAY-09:43 260.91 176.32 1856.46 0.00 0.00 0.00 0.00 0.00 1325.33
June 24358.98 18-JUN-10:22 326.14 220.40 2320.57 0.00 0.00 0.00 0.00 0.00 293.09
July 28079.99 16-JUL-08:31 456.59 308.57 3248.80 0.00 0.00 0.00 0.00 0.00 164.12
August 20771.61 06-AUG-09:12 326.14 220.40 2320.57 0.00 0.00 0.00 0.00 0.00 272.86
September 15723.58 04-SEP-09:52 326.14 220.40 2320.57 0.00 0.00 0.00 0.00 0.00 467.34
October 8449.38 11-OCT-09:30 1295.83 793.52 1392.34 0.00 0.00 0.00 0.00 0.00 90.48
November 2792.87 03-NOV-09:55 2591.66 1587.03 2784.68 0.00 0.00 0.00 0.00 0.00 403.37
December 1969.86 16-DEC-06:04 913.19 1297.19 4331.73 0.00 0.00 0.00 0.00 0.00 278.78
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 1757.95   260.91 176.32 1392.34 0.00 0.00 0.00 0.00 0.00 55.44
Maximum of Months 28079.99   2591.66 1587.03 4331.73 0.00 0.00 0.00 0.00 0.00 1325.33



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 12061.67 12-JAN-13:40 3846.30 2462.72 4321.17 0.00 0.00 0.00 0.00 0.00 2067.58
February 17695.30 28-FEB-13:50 1923.15 1231.36 2160.58 0.00 0.00 0.00 0.00 0.00 884.37
March 20243.56 15-MAR-13:30 2010.83 1231.36 2160.58 0.00 0.00 0.00 0.00 48.37 0.00
April 20600.09 23-APR-14:31 708.53 478.83 5041.36 0.00 0.00 0.00 0.00 0.00 1086.47
May 29272.18 14-MAY-14:02 506.09 342.02 3600.97 0.00 0.00 0.00 0.00 0.00 398.17
June 29455.86 18-JUN-13:02 506.09 342.02 3600.97 0.00 0.00 0.00 0.00 0.00 312.10
July 31002.17 30-JUL-11:52 607.31 410.42 4321.17 0.00 0.00 0.00 0.00 0.00 345.07
August 29120.56 13-AUG-15:02 607.31 410.42 4321.17 0.00 0.00 0.00 0.00 517.01 0.00
September 29923.71 10-SEP-13:22 506.09 342.02 3600.97 0.00 0.00 0.00 0.00 0.00 1002.27
October 23876.85 31-OCT-13:30 2010.83 1231.36 2160.58 0.00 0.00 0.00 0.00 0.00 405.67
November 17801.91 03-NOV-12:40 1923.15 1231.36 2160.58 0.00 0.00 0.00 0.00 0.00 448.94
December 10754.68 16-DEC-13:30 202.44 205.23 840.23 0.00 0.00 0.00 0.00 0.00 362.93
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 10754.68   202.44 205.23 840.23 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 31002.17   3846.30 2462.72 5041.36 0.00 0.00 0.00 0.00 517.01 2067.58



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 2493.80 12-JAN-16:00 1239.33 793.52 1392.33 0.00 0.00 0.00 0.00 0.00 1160.45
February 5829.94 28-FEB-16:30 1239.33 793.52 1392.33 0.00 0.00 0.00 0.00 0.00 528.78
March 8579.38 21-MAR-16:00 1239.33 793.52 1392.33 0.00 0.00 0.00 0.00 0.00 483.24
April 13026.82 19-APR-16:00 1239.33 793.52 1392.33 0.00 0.00 0.00 0.00 0.00 175.07
May 27995.91 07-MAY-16:42 391.37 264.49 2784.67 0.00 0.00 0.00 0.00 0.00 886.91
June 32104.07 18-JUN-17:01 0.00 396.73 3243.14 0.00 0.00 0.00 0.00 0.00 607.35
July 34916.36 02-JUL-16:51 652.28 440.81 4641.11 0.00 0.00 0.00 0.00 0.00 499.20
August 29145.90 06-AUG-16:31 456.59 308.57 3248.78 0.00 0.00 0.00 0.00 0.00 29.42
September 27803.91 04-SEP-16:32 391.37 264.49 2784.67 0.00 0.00 0.00 0.00 0.00 599.66
October 12238.90 11-OCT-16:00 1239.33 793.52 1392.33 0.00 0.00 0.00 0.00 0.00 17.96
November 4234.85 15-NOV-15:30 1239.33 793.52 1392.33 0.00 0.00 0.00 0.00 0.00 241.74
December 2653.52 04-DEC-15:50 1239.33 793.52 1392.33 0.00 0.00 0.00 0.00 0.00 470.16
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 2493.80   0.00 264.49 1392.33 0.00 0.00 0.00 0.00 0.00 17.96
Maximum of Months 34916.36   1239.33 793.52 4641.11 0.00 0.00 0.00 0.00 0.00 1160.45



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: GROUNDFLOOR_PLENUM

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 8147.05 24-JAN-05:01 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 4774.15
February 8898.38 21-FEB-05:01 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 4492.42
March 5828.88 16-MAR-05:15 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 164.37
April 6917.73 10-APR-05:08 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 262.22
May 7918.92 30-MAY-05:15 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 181.55
June 9075.73 27-JUN-05:03 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 69.79
July 10669.62 05-JUL-05:15 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 86.70
August 12094.90 07-AUG-05:15 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 64.20
September 8620.40 18-SEP-05:15 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 97.51
October 6271.55 23-OCT-05:15 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 196.12
November 5417.22 06-NOV-06:15 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 334.88
December 7005.83 26-DEC-05:01 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 4996.57
                       
Annual Sum or Average     0.00 0.00 0.00 0.00 0.00 0.00 0.00    
Minimum of Months 5417.22   0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 64.20
Maximum of Months 12094.90   0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 4996.57



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: MIDFLOOR_PLENUM

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 9636.21 28-JAN-04:01 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 4552.64
February 10167.11 25-FEB-04:01 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 5202.00
March 10544.59 20-MAR-03:01 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 3765.38
April 8515.84 17-APR-04:01 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 5109.51 30-MAY-05:10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 321.64
June 6940.07 29-JUN-15:30 0.00 0.00 0.00 0.00 0.00 0.00 0.00 73.89 0.00
July 7976.15 21-JUL-12:10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 198.76 0.00
August 7824.48 09-AUG-15:20 0.00 0.00 0.00 0.00 0.00 0.00 0.00 146.72 0.00
September 6852.41 18-SEP-05:15 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 175.08
October 8797.02 30-OCT-04:01 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1886.65
November 9369.46 18-NOV-05:01 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 3391.01
December 10855.82 07-DEC-04:01 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 4890.90
                       
Annual Sum or Average     0.00 0.00 0.00 0.00 0.00 0.00 0.00    
Minimum of Months 5109.51   0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 10855.82   0.00 0.00 0.00 0.00 0.00 0.00 0.00 198.76 5202.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: TOPFLOOR_PLENUM

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 0.00 01-JAN-00:03 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 2163.97
February 0.00 01-FEB-00:03 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 3168.92
March 12412.37 15-MAR-14:10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 22.39 0.00
April 10151.45 21-APR-14:20 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 587.63
May 14715.39 31-MAY-14:20 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 270.09
June 19729.68 12-JUN-13:50 0.00 0.00 0.00 0.00 0.00 0.00 0.00 293.42 0.00
July 19989.93 21-JUL-13:40 0.00 0.00 0.00 0.00 0.00 0.00 0.00 222.67 0.00
August 19336.83 09-AUG-15:00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 138.96 0.00
September 14945.49 21-SEP-15:40 0.00 0.00 0.00 0.00 0.00 0.00 0.00 8.76 0.00
October 8655.22 11-OCT-15:40 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 67.55
November 1740.93 16-NOV-13:10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 281.31
December 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 2728.35
                       
Annual Sum or Average     0.00 0.00 0.00 0.00 0.00 0.00 0.00    
Minimum of Months 0.00   0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 19989.93   0.00 0.00 0.00 0.00 0.00 0.00 0.00 293.42 3168.92



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 2078.95 12-JAN-16:40 222.14 578.72 1948.61 0.00 0.00 0.00 0.00 0.00 0.00
February 4343.42 28-FEB-17:00 444.28 1157.44 7794.42 0.00 0.00 0.00 0.00 0.00 0.00
March 6988.66 31-MAR-24:00 0.00 32.15 7794.42 0.00 0.00 0.00 0.00 0.00 0.00
April 8236.06 24-APR-18:00 23.38 192.90 7794.42 0.00 0.00 0.00 0.00 0.00 0.00
May 3500.12 31-MAY-24:00 0.00 32.15 3897.21 0.00 0.00 0.00 0.00 0.00 0.00
June 5371.14 30-JUN-24:00 0.00 32.15 5845.82 0.00 0.00 0.00 0.00 0.00 0.00
July 7271.88 31-JUL-23:47 0.00 96.46 23383.27 0.00 0.00 0.00 0.00 0.00 0.00
August 8409.16 02-AUG-18:40 23.38 192.90 7794.42 0.00 0.00 0.00 0.00 0.00 0.00
September 3200.52 30-SEP-24:00 0.00 32.15 3897.21 0.00 0.00 0.00 0.00 0.00 0.00
October 5143.38 31-OCT-24:00 0.00 32.15 5845.82 0.00 0.00 0.00 0.00 0.00 0.00
November 6017.13 24-NOV-16:20 222.14 578.72 5845.82 0.00 0.00 0.00 0.00 0.00 0.00
December 7886.92 04-DEC-16:20 222.14 578.72 7794.42 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 2078.95   0.00 32.15 1948.61 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 8409.16   444.28 1157.44 23383.27 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: DATACENTER_MID_ZN_6

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 1626.97 12-JAN-16:50 222.14 578.72 1948.61 0.00 0.00 0.00 0.00 0.00 0.00
February 3814.84 28-FEB-17:00 444.28 1157.44 7794.42 0.00 0.00 0.00 0.00 0.00 0.00
March 6109.13 31-MAR-23:40 0.00 32.15 7794.42 0.00 0.00 0.00 0.00 0.00 0.00
April 7796.58 24-APR-18:00 23.38 192.90 7794.42 0.00 0.00 0.00 0.00 0.00 0.00
May 3285.38 31-MAY-24:00 0.00 32.15 3897.21 0.00 0.00 0.00 0.00 0.00 0.00
June 5155.82 30-JUN-24:00 0.00 32.15 5845.82 0.00 0.00 0.00 0.00 0.00 0.00
July 7019.53 31-JUL-23:57 0.00 96.46 23383.27 0.00 0.00 0.00 0.00 0.00 0.00
August 8077.45 02-AUG-18:40 23.38 192.90 7794.42 0.00 0.00 0.00 0.00 0.00 0.00
September 2621.98 30-SEP-24:00 0.00 32.15 3897.21 0.00 0.00 0.00 0.00 0.00 0.00
October 4389.59 31-OCT-23:40 0.00 32.15 5845.82 0.00 0.00 0.00 0.00 0.00 0.00
November 5508.60 15-NOV-16:20 222.14 578.72 5845.82 0.00 0.00 0.00 0.00 0.00 0.00
December 7005.80 04-DEC-16:30 222.14 578.72 7794.42 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 1626.97   0.00 32.15 1948.61 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 8077.45   444.28 1157.44 23383.27 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 1455.11 12-JAN-16:40 222.14 578.72 1948.61 0.00 0.00 0.00 0.00 0.00 0.00
February 3832.01 28-FEB-17:00 444.28 1157.44 7794.42 0.00 0.00 0.00 0.00 0.00 0.00
March 5766.17 21-MAR-17:40 23.38 192.90 5845.82 0.00 0.00 0.00 0.00 0.00 0.00
April 7803.40 24-APR-18:00 23.38 192.90 7794.42 0.00 0.00 0.00 0.00 0.00 0.00
May 3188.68 31-MAY-23:30 0.00 32.15 3897.21 0.00 0.00 0.00 0.00 0.00 0.00
June 5077.49 30-JUN-23:23 0.00 96.46 17537.45 0.00 0.00 0.00 0.00 0.00 0.00
July 7004.62 31-JUL-23:57 0.00 96.46 23383.27 0.00 0.00 0.00 0.00 0.00 0.00
August 8129.31 02-AUG-18:40 23.38 192.90 7794.42 0.00 0.00 0.00 0.00 0.00 0.00
September 2454.42 04-SEP-17:42 0.00 192.92 11691.63 0.00 0.00 0.00 0.00 0.00 0.00
October 4213.51 11-OCT-17:00 70.15 321.51 3897.21 0.00 0.00 0.00 0.00 0.00 0.00
November 5429.25 15-NOV-16:30 222.14 578.72 5845.82 0.00 0.00 0.00 0.00 0.00 0.00
December 6752.66 04-DEC-16:30 222.14 578.72 7794.42 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 1455.11   0.00 32.15 1948.61 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 8129.31   444.28 1157.44 23383.27 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 91319.39 12-JAN-16:55 9617.36 12942.03 189816.26 0.00 0.00 0.00 0.00 0.00 0.00
February 183036.38 23-FEB-17:00 4808.68 6471.01 189816.26 0.00 0.00 0.00 0.00 0.00 0.00
March 358405.67 31-MAR-24:00 0.00 359.47 379632.52 0.00 0.00 0.00 0.00 0.00 0.00
April 368020.08 21-APR-16:00 4808.68 6471.01 379632.52 0.00 0.00 0.00 0.00 0.00 0.00
May 176248.25 31-MAY-24:00 0.00 359.47 189816.26 0.00 0.00 0.00 0.00 0.00 0.00
June 268359.86 30-JUN-24:00 0.00 359.47 284724.39 0.00 0.00 0.00 0.00 0.00 0.00
July 360670.83 31-JUL-23:57 0.00 1078.42 1138897.57 0.00 0.00 0.00 0.00 0.00 0.00
August 376317.10 15-AUG-18:00 506.18 2157.00 379632.52 0.00 0.00 0.00 0.00 0.00 0.00
September 175553.63 30-SEP-24:00 0.00 359.47 189816.26 0.00 0.00 0.00 0.00 0.00 0.00
October 268572.66 31-OCT-24:00 0.00 359.47 284724.39 0.00 0.00 0.00 0.00 0.00 0.00
November 276937.65 15-NOV-16:55 9617.36 12942.03 569448.78 0.00 0.00 0.00 0.00 0.00 0.00
December 367689.85 15-DEC-17:00 4808.68 6471.01 379632.52 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 91319.39   0.00 359.47 189816.26 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 376317.10   9617.36 12942.03 1138897.57 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: EnergyConsumptionElectricityNaturalGasMonthly

For: Meter

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ELECTRICITY:FACILITY [J] ELECTRICITY:FACILITY {Maximum} [W] ELECTRICITY:FACILITY {TIMESTAMP} NATURALGAS:FACILITY [J] NATURALGAS:FACILITY {Maximum} [W] NATURALGAS:FACILITY {TIMESTAMP}
January 0.167659E+13 1116463.31 13-JAN-16:00 0.666019E+12 2042193.17 02-JAN-07:10
February 0.189180E+13 1202488.97 24-FEB-16:19 0.570243E+12 2174350.20 21-FEB-07:10
March 0.247418E+13 1602482.84 15-MAR-15:09 0.290282E+12 1818702.97 06-MAR-07:10
April 0.268259E+13 1640561.27 07-APR-13:00 0.141966E+12 1188757.45 17-APR-06:10
May 0.172437E+13 1364232.54 23-MAY-15:09 0.757772E+11 409209.54 03-MAY-06:10
June 0.226448E+13 1754050.45 27-JUN-15:09 0.675651E+11 222131.77 13-JUN-06:10
July 0.292079E+13 1999145.26 05-JUL-15:00 0.634386E+11 79424.37 06-JUL-11:30
August 0.329709E+13 2110357.97 15-AUG-14:39 0.664440E+11 78303.88 30-AUG-11:39
September 0.171400E+13 1486062.26 21-SEP-15:00 0.653738E+11 406944.99 30-SEP-06:10
October 0.201552E+13 1368542.26 11-OCT-15:00 0.120851E+12 1050288.67 17-OCT-06:10
November 0.238336E+13 1464817.12 16-NOV-16:00 0.237684E+12 1183426.06 24-NOV-07:10
December 0.279538E+13 1548026.75 04-DEC-16:40 0.578767E+12 2192673.77 26-DEC-07:10
             
Annual Sum or Average 0.278401E+14     0.294441E+13    
Minimum of Months 0.167659E+13 1116463.31   0.634386E+11 78303.88  
Maximum of Months 0.329709E+13 2110357.97   0.666019E+12 2192673.77  



Table of Contents

Report: EndUseEnergyConsumptionElectricityMonthly

For: Meter

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

INTERIORLIGHTS:ELECTRICITY [J] EXTERIORLIGHTS:ELECTRICITY [J] INTERIOREQUIPMENT:ELECTRICITY [J] EXTERIOREQUIPMENT:ELECTRICITY [J] FANS:ELECTRICITY [J] PUMPS:ELECTRICITY [J] HEATING:ELECTRICITY [J] COOLING:ELECTRICITY [J] HEATREJECTION:ELECTRICITY [J] HUMIDIFIER:ELECTRICITY [J] HEATRECOVERY:ELECTRICITY [J] WATERSYSTEMS:ELECTRICITY [] COGENERATION:ELECTRICITY []
January 0.333878E+12 0.771825E+11 0.766053E+12 0.164271E+12 0.175767E+12 0.143642E+11 0.00 0.701232E+10 0.684219E+09 0.130200E+12 0.717795E+10 0.00 0.00
February 0.299660E+12 0.631847E+11 0.978954E+12 0.148382E+12 0.159611E+12 0.137952E+11 0.00 0.209396E+11 0.206348E+10 0.198642E+12 0.656459E+10 0.00 0.00
March 0.352073E+12 0.609448E+11 0.141687E+13 0.164522E+12 0.183204E+12 0.174159E+11 0.00 0.592571E+11 0.137199E+11 0.200002E+12 0.616761E+10 0.00 0.00
April 0.312775E+12 0.498759E+11 0.165903E+13 0.158945E+12 0.180661E+12 0.166764E+11 0.00 0.726191E+11 0.225210E+11 0.205791E+12 0.370199E+10 0.00 0.00
May 0.336078E+12 0.439628E+11 0.774844E+12 0.164393E+12 0.206231E+12 0.289683E+11 0.00 0.583796E+11 0.320795E+11 0.782129E+11 0.121870E+10 0.00 0.00
June 0.333561E+12 0.392241E+11 0.106252E+13 0.159182E+12 0.239057E+12 0.518699E+11 0.00 0.233722E+12 0.104615E+12 0.395007E+11 0.122823E+10 0.00 0.00
July 0.312677E+12 0.415577E+11 0.139340E+13 0.164155E+12 0.260548E+12 0.705777E+11 0.00 0.510033E+12 0.162784E+12 0.218181E+10 0.286824E+10 0.00 0.00
August 0.348913E+12 0.479546E+11 0.173200E+13 0.164521E+12 0.261187E+12 0.667452E+11 0.00 0.513831E+12 0.152145E+12 0.760178E+10 0.219166E+10 0.00 0.00
September 0.313983E+12 0.550581E+11 0.740713E+12 0.158944E+12 0.210102E+12 0.403668E+11 0.00 0.115243E+12 0.687212E+11 0.100952E+11 0.771104E+09 0.00 0.00
October 0.328965E+12 0.662307E+11 0.108340E+13 0.164269E+12 0.183503E+12 0.209099E+11 0.00 0.444697E+11 0.177405E+11 0.102764E+12 0.326976E+10 0.00 0.00
November 0.330967E+12 0.721941E+11 0.135889E+13 0.159046E+12 0.168148E+12 0.165174E+11 0.00 0.458143E+11 0.134408E+11 0.213212E+12 0.513231E+10 0.00 0.00
December 0.325420E+12 0.793591E+11 0.170972E+13 0.164161E+12 0.174226E+12 0.160020E+11 0.00 0.524008E+11 0.605579E+10 0.261091E+12 0.694993E+10 0.00 0.00
                           
Annual Sum or Average 0.392895E+13 0.696729E+12 0.146764E+14 0.193479E+13 0.240224E+13 0.374209E+12 0.00 0.173372E+13 0.596570E+12 0.144929E+13 0.472421E+11 0.00 0.00
Minimum of Months 0.299660E+12 0.392241E+11 0.740713E+12 0.148382E+12 0.159611E+12 0.137952E+11 0.00 0.701232E+10 0.684219E+09 0.218181E+10 0.771104E+09 0.00 0.00
Maximum of Months 0.352073E+12 0.793591E+11 0.173200E+13 0.164522E+12 0.261187E+12 0.705777E+11 0.00 0.513831E+12 0.162784E+12 0.261091E+12 0.717795E+10 0.00 0.00



Table of Contents

Report: EndUseEnergyConsumptionNaturalGasMonthly

For: Meter

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

INTERIOREQUIPMENT:NATURALGAS [] EXTERIOREQUIPMENT:NATURALGAS [] HEATING:NATURALGAS [J] COOLING:NATURALGAS [] WATERSYSTEMS:NATURALGAS [J] COGENERATION:NATURALGAS [] HUMIDIFIER:NATURALGAS []
January 0.00 0.00 0.591776E+12 0.00 0.742425E+11 0.00 0.00
February 0.00 0.00 0.502236E+12 0.00 0.680072E+11 0.00 0.00
March 0.00 0.00 0.212481E+12 0.00 0.778006E+11 0.00 0.00
April 0.00 0.00 0.719862E+11 0.00 0.699794E+11 0.00 0.00
May 0.00 0.00 0.470482E+10 0.00 0.710724E+11 0.00 0.00
June 0.00 0.00 0.598325E+09 0.00 0.669668E+11 0.00 0.00
July 0.00 0.00 2969.76 0.00 0.634386E+11 0.00 0.00
August 0.00 0.00 10016001.90 0.00 0.664340E+11 0.00 0.00
September 0.00 0.00 0.299181E+10 0.00 0.623820E+11 0.00 0.00
October 0.00 0.00 0.543948E+11 0.00 0.664558E+11 0.00 0.00
November 0.00 0.00 0.170021E+12 0.00 0.676628E+11 0.00 0.00
December 0.00 0.00 0.507833E+12 0.00 0.709338E+11 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.211903E+13 0.00 0.825376E+12 0.00 0.00
Minimum of Months 0.00 0.00 2969.76 0.00 0.623820E+11 0.00 0.00
Maximum of Months 0.00 0.00 0.591776E+12 0.00 0.778006E+11 0.00 0.00



Table of Contents

Report: PeakEnergyEndUseElectricityPart1Monthly

For: Meter

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

INTERIORLIGHTS:ELECTRICITY {Maximum} [W] INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} EXTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] EXTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} FANS:ELECTRICITY {Maximum} [W] FANS:ELECTRICITY {TIMESTAMP} PUMPS:ELECTRICITY {Maximum} [W] PUMPS:ELECTRICITY {TIMESTAMP} HEATING:ELECTRICITY {Maximum} [W] HEATING:ELECTRICITY {TIMESTAMP}
January 385834.94 02-JAN-16:49 57580.60 01-JAN-06:10 423497.50 02-JAN-08:09 118533.43 11-JAN-08:20 107706.30 02-JAN-06:19 32627.96 02-JAN-07:19 0.00 01-JAN-00:10
February 379269.20 01-FEB-16:00 57580.60 01-FEB-06:10 541788.89 01-FEB-08:09 118530.04 01-FEB-08:20 116291.34 24-FEB-16:19 31509.17 08-FEB-06:10 0.00 01-FEB-00:10
March 358353.79 17-MAR-07:10 57580.60 01-MAR-06:10 660080.29 01-MAR-08:09 118513.95 17-MAR-07:19 198184.67 24-MAR-16:10 30564.13 24-MAR-10:39 0.00 01-MAR-00:10
April 352283.84 12-APR-07:10 57580.60 01-APR-05:10 778371.69 03-APR-07:10 118509.21 12-APR-07:19 173833.21 13-APR-11:39 29252.56 01-APR-06:30 0.00 01-APR-00:10
May 337934.08 11-MAY-07:10 57580.60 01-MAY-05:10 423497.50 01-MAY-07:10 118498.03 11-MAY-07:19 194922.98 23-MAY-14:30 35213.08 10-MAY-14:30 0.00 01-MAY-00:10
June 333338.24 19-JUN-07:10 57580.60 01-JUN-19:49 541788.89 01-JUN-07:10 118494.45 19-JUN-07:19 248469.22 12-JUN-15:20 54952.03 27-JUN-07:40 0.00 01-JUN-00:10
July 336163.20 11-JUL-07:10 57580.60 01-JUL-19:00 660080.29 03-JUL-07:10 118496.65 11-JUL-07:19 262575.52 19-JUL-14:00 57774.40 05-JUL-15:00 0.00 01-JUL-00:10
August 337087.14 24-AUG-07:10 57580.60 01-AUG-19:40 778371.69 01-AUG-07:10 118497.37 24-AUG-07:19 292128.76 09-AUG-15:20 59285.61 15-AUG-14:30 0.00 01-AUG-00:10
September 352360.83 26-SEP-07:10 57580.60 01-SEP-05:10 423497.50 01-SEP-07:10 118509.27 26-SEP-07:19 235541.72 21-SEP-15:00 56392.82 21-SEP-14:50 0.00 01-SEP-00:10
October 378345.27 30-OCT-07:10 57580.60 01-OCT-05:10 541788.89 02-OCT-07:10 118529.58 30-OCT-07:19 175270.15 11-OCT-15:00 29931.92 30-OCT-06:19 0.00 01-OCT-00:10
November 385834.94 01-NOV-07:10 57580.60 01-NOV-05:10 660080.29 01-NOV-07:10 118535.44 01-NOV-07:19 181047.04 03-NOV-09:20 29411.86 25-NOV-05:10 0.00 01-NOV-00:10
December 385834.94 01-DEC-16:19 57580.60 01-DEC-06:10 778371.69 01-DEC-08:09 118535.44 18-DEC-08:20 105614.38 26-DEC-06:10 32645.79 11-DEC-06:10 0.00 01-DEC-00:10
                             
Annual Sum or Average                            
Minimum of Months 333338.24   57580.60   423497.50   118494.45   105614.38   29252.56   0.00  
Maximum of Months 385834.94   57580.60   778371.69   118535.44   292128.76   59285.61   0.00  



Table of Contents

Report: PeakEnergyEndUseElectricityPart2Monthly

For: Meter

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

COOLING:ELECTRICITY {Maximum} [W] COOLING:ELECTRICITY {TIMESTAMP} HEATREJECTION:ELECTRICITY {Maximum} [W] HEATREJECTION:ELECTRICITY {TIMESTAMP} HUMIDIFIER:ELECTRICITY {Maximum} [W] HUMIDIFIER:ELECTRICITY {TIMESTAMP} HEATRECOVERY:ELECTRICITY {Maximum} [W] HEATRECOVERY:ELECTRICITY {TIMESTAMP} WATERSYSTEMS:ELECTRICITY [] COGENERATION:ELECTRICITY []
January 6804.13 12-JAN-16:40 1252.75 11-JAN-15:00 76099.33 13-JAN-17:00 5613.48 02-JAN-07:10 0.00 0.00
February 14140.47 14-FEB-16:00 3951.72 22-FEB-17:00 100000.00 14-FEB-15:00 5613.48 01-FEB-07:10 0.00 0.00
March 289279.73 15-MAR-13:00 69752.65 14-MAR-10:50 100000.00 01-MAR-04:40 5613.48 01-MAR-07:10 0.00 0.00
April 175606.07 07-APR-13:00 50250.29 08-APR-13:50 100000.00 01-APR-04:10 5613.48 01-APR-06:10 0.00 0.00
May 232753.84 10-MAY-14:20 90257.03 10-MAY-13:39 100000.00 07-MAY-13:50 5613.48 01-MAY-06:10 0.00 0.00
June 445737.96 27-JUN-07:40 90257.03 01-JUN-15:39 100000.00 03-JUN-16:10 5613.48 01-JUN-16:49 0.00 0.00
July 558683.70 05-JUL-15:00 90257.03 03-JUL-12:50 100000.00 06-JUL-13:00 5613.48 03-JUL-14:09 0.00 0.00
August 583018.50 15-AUG-14:39 90257.03 02-AUG-13:20 100000.00 04-AUG-12:39 5613.48 03-AUG-11:00 0.00 0.00
September 346824.52 15-SEP-14:00 90257.03 08-SEP-12:50 68413.88 19-SEP-13:00 5613.48 02-SEP-06:10 0.00 0.00
October 164639.89 11-OCT-14:00 53126.84 11-OCT-14:00 100000.00 08-OCT-09:00 5613.48 02-OCT-06:10 0.00 0.00
November 107700.42 16-NOV-12:00 49902.71 16-NOV-16:00 100000.00 01-NOV-04:19 5613.48 01-NOV-06:10 0.00 0.00
December 55663.60 01-DEC-10:00 40324.07 01-DEC-10:00 100000.00 02-DEC-05:19 5613.48 01-DEC-07:10 0.00 0.00
                     
Annual Sum or Average                 0.00 0.00
Minimum of Months 6804.13   1252.75   68413.88   5613.48   0.00 0.00
Maximum of Months 583018.50   90257.03   100000.00   5613.48   0.00 0.00



Table of Contents

Report: ElectricComponentsOfPeakDemandMonthly

For: Meter

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ELECTRICITY:FACILITY {Maximum} [W] ELECTRICITY:FACILITY {TIMESTAMP} INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] EXTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] FANS:ELECTRICITY {AT MAX/MIN} [W] PUMPS:ELECTRICITY {AT MAX/MIN} [W] HEATING:ELECTRICITY {AT MAX/MIN} [W] COOLING:ELECTRICITY {AT MAX/MIN} [W] HEATREJECTION:ELECTRICITY {AT MAX/MIN} [W]
January 1116463.31 13-JAN-16:00 385834.94 423497.50 57580.60 84486.91 79010.36 3665.50 0.00 5619.33 720.07
February 1202488.97 24-FEB-16:19 332294.83 541788.89 0.00 84450.25 116291.34 16518.47 0.00 12966.00 1217.53
March 1602482.84 15-MAR-15:09 332294.83 660080.29 0.00 84450.25 155261.72 28366.24 0.00 266663.39 69752.65
April 1640561.27 07-APR-13:00 332294.83 778371.69 0.00 39059.06 137943.16 27505.11 0.00 175606.07 49781.34
May 1364232.54 23-MAY-15:09 332294.83 423497.50 0.00 84450.25 180707.48 27903.19 0.00 170575.42 53397.40
June 1754050.45 27-JUN-15:09 332294.83 541788.89 0.00 84450.25 241538.23 53720.87 0.00 404386.88 90257.03
July 1999145.26 05-JUL-15:00 332294.83 660080.29 0.00 84450.25 215604.77 57774.40 0.00 558683.70 90257.03
August 2110357.97 15-AUG-14:39 332294.83 778371.69 0.00 39059.06 228540.74 58816.12 0.00 583018.50 90257.03
September 1486062.26 21-SEP-15:00 332294.83 423497.50 0.00 84450.25 235541.72 52719.24 0.00 261688.23 90257.03
October 1368542.26 11-OCT-15:00 332294.83 541788.89 0.00 84450.25 175270.15 28174.47 0.00 154025.06 52538.60
November 1464817.12 16-NOV-16:00 385834.94 660080.29 57580.60 84492.05 96017.67 27443.51 0.00 103465.36 49902.71
December 1548026.75 04-DEC-16:40 385834.94 778371.69 57580.60 84485.06 80714.94 29163.88 0.00 23900.17 2362.01
                       
Annual Sum or Average                      
Minimum of Months 1116463.31   332294.83 423497.50 0.00 39059.06 79010.36 3665.50 0.00 5619.33 720.07
Maximum of Months 2110357.97   385834.94 778371.69 57580.60 84492.05 241538.23 58816.12 0.00 583018.50 90257.03



Table of Contents

Report: PeakEnergyEndUseNaturalGasMonthly

For: Meter

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

INTERIOREQUIPMENT:NATURALGAS [] EXTERIOREQUIPMENT:NATURALGAS [] HEATING:NATURALGAS {Maximum} [W] HEATING:NATURALGAS {TIMESTAMP} COOLING:NATURALGAS [] WATERSYSTEMS:NATURALGAS {Maximum} [W] WATERSYSTEMS:NATURALGAS {TIMESTAMP} COGENERATION:NATURALGAS []
January 0.00 0.00 2009951.93 02-JAN-07:10 0.00 86665.09 31-JAN-12:00 0.00
February 0.00 0.00 2149147.05 21-FEB-07:10 0.00 86742.10 06-FEB-12:50 0.00
March 0.00 0.00 1786388.56 06-MAR-07:10 0.00 86658.89 01-MAR-12:50 0.00
April 0.00 0.00 1156712.94 17-APR-06:10 0.00 85695.18 03-APR-11:30 0.00
May 0.00 0.00 377320.78 03-MAY-06:10 0.00 84081.60 01-MAY-11:30 0.00
June 0.00 0.00 190654.75 13-JUN-06:10 0.00 81845.42 01-JUN-11:20 0.00
July 0.00 0.00 4.95 15-JUL-11:20 0.00 79424.37 06-JUL-11:30 0.00
August 0.00 0.00 5497.33 01-AUG-06:10 0.00 78303.88 30-AUG-11:39 0.00
September 0.00 0.00 398798.41 30-SEP-06:10 0.00 79569.63 29-SEP-11:39 0.00
October 0.00 0.00 1018818.57 17-OCT-06:10 0.00 81785.40 31-OCT-11:50 0.00
November 0.00 0.00 1151583.18 24-NOV-07:10 0.00 83968.80 30-NOV-12:30 0.00
December 0.00 0.00 2175214.88 26-DEC-07:10 0.00 85637.41 29-DEC-12:20 0.00
                 
Annual Sum or Average 0.00 0.00     0.00     0.00
Minimum of Months 0.00 0.00 4.95   0.00 78303.88   0.00
Maximum of Months 0.00 0.00 2175214.88   0.00 86742.10   0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: BASEMENT

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.17 25.73 0.00 25.73
February 0.00 0.00 0.00 0.00 0.17 25.78 0.00 25.78
March 0.00 0.00 0.00 0.00 0.17 25.57 0.00 25.57
April 0.00 0.00 0.00 0.00 1.00 25.72 0.00 25.72
May 0.00 0.00 0.00 0.00 1.83 26.21 0.00 26.21
June 0.00 0.00 0.00 0.00 1.17 25.98 0.00 25.98
July 0.00 0.00 0.00 0.00 4.17 26.63 0.00 26.63
August 0.00 0.00 0.00 0.00 6.83 26.64 0.17 26.59
September 0.00 0.00 0.00 0.00 7.17 27.11 0.00 27.11
October 0.00 0.00 0.00 0.00 4.50 26.59 0.17 26.62
November 0.00 0.00 0.00 0.00 4.17 26.68 0.67 26.77
December 0.00 0.00 0.00 0.00 1.17 25.74 0.00 25.74
                 
Annual Sum or Average 0.00   0.00   32.50 26.62 1.00 26.63
Minimum of Months 0.00 0.00 0.00 0.00 0.17 25.57 0.00 25.57
Maximum of Months 0.00 0.00 0.00 0.00 7.17 27.11 0.67 27.11



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: CORE_BOTTOM

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: CORE_MID

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 1.00 19.42 0.50 19.60 0.00 19.60 0.00 19.60
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.50 24.67 0.50 24.67
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.17 18.85 0.00 18.85 0.00 18.85 0.00 18.85
                 
Annual Sum or Average 1.17 19.34 0.50 19.52 0.50 20.71 0.50 21.45
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 1.00 19.42 0.50 19.60 0.50 24.67 0.50 24.67



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: CORE_TOP

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 4.50 18.62 0.67 18.82 0.00 18.82 0.00 18.82
February 4.00 18.52 0.50 18.72 0.00 18.72 0.00 18.72
March 1.33 18.86 0.00 18.86 0.00 18.86 0.00 18.86
April 0.17 19.20 0.00 19.20 0.00 19.20 0.00 19.20
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.50 19.23 0.00 19.23 0.00 19.23 0.00 19.23
December 3.17 18.81 0.67 18.98 0.00 18.98 0.00 18.98
                 
Annual Sum or Average 13.67 18.69 1.83 18.85 0.00 18.85 0.00 18.85
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 4.50 19.23 0.67 19.23 0.00 19.23 0.00 19.23



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 1.50 19.09 0.00 19.09 0.00 19.09 0.00 19.09
February 1.67 18.90 0.00 18.90 0.00 18.90 0.00 18.90
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 1.50 27.39 1.17 27.40
August 0.00 0.00 0.00 0.00 2.00 27.24 1.83 27.31
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.50 19.23 0.00 19.23 0.00 19.23 0.00 19.23
                 
Annual Sum or Average 3.67 19.02 0.00 19.02 3.50 23.07 3.00 24.35
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 1.67 19.23 0.00 19.23 2.00 27.39 1.83 27.40



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 1.83 19.09 0.00 19.09 0.00 19.09 0.00 19.09
February 2.17 18.92 0.00 18.92 0.17 19.34 0.17 19.70
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.83 27.97 0.83 27.97
May 0.00 0.00 0.00 0.00 2.33 27.78 2.33 27.78
June 0.00 0.00 0.00 0.00 4.67 27.88 4.67 27.88
July 0.00 0.00 0.00 0.00 6.00 28.04 6.00 28.04
August 0.00 0.00 0.00 0.00 1.67 27.89 1.67 27.89
September 0.00 0.00 0.00 0.00 2.67 28.11 2.67 28.11
October 0.00 0.00 0.00 0.00 0.50 27.45 0.50 27.45
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 1.17 19.17 0.00 19.17 0.00 19.17 0.00 19.17
                 
Annual Sum or Average 5.17 19.04 0.00 19.04 18.83 26.00 18.83 26.84
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 2.17 19.17 0.00 19.17 6.00 28.11 6.00 28.11



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 2.33 18.98 0.00 18.98 0.50 20.47 0.50 21.52
February 3.17 18.55 0.00 18.55 0.17 18.86 0.17 19.15
March 0.17 19.33 0.00 19.33 0.17 23.31 0.17 24.64
April 0.00 0.00 0.00 0.00 1.67 27.76 1.67 27.76
May 0.00 0.00 0.00 0.00 1.67 27.66 1.67 27.66
June 0.00 0.00 0.00 0.00 3.50 27.68 3.50 27.68
July 0.00 0.00 0.00 0.00 8.00 27.78 7.83 27.79
August 0.00 0.00 0.00 0.00 6.00 27.86 5.50 27.91
September 0.00 0.00 0.00 0.00 4.67 28.17 4.67 28.17
October 0.00 0.00 0.00 0.00 2.83 27.14 2.83 27.14
November 0.00 0.00 0.00 0.00 0.33 27.29 0.33 27.29
December 1.33 19.09 0.00 19.09 0.33 20.74 0.33 21.84
                 
Annual Sum or Average 7.00 18.81 0.00 18.81 29.83 26.04 29.17 26.80
Minimum of Months 0.00 0.00 0.00 0.00 0.17 18.86 0.17 19.15
Maximum of Months 3.17 19.33 0.00 19.33 8.00 28.17 7.83 28.17



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.50 19.10 0.00 19.10 0.00 19.10 0.00 19.10
February 1.00 19.22 0.00 19.22 0.00 19.22 0.00 19.22
March 0.00 0.00 0.00 0.00 1.50 27.76 1.33 27.75
April 0.00 0.00 0.00 0.00 5.50 28.27 3.67 28.33
May 0.00 0.00 0.00 0.00 5.00 28.17 3.33 28.18
June 0.00 0.00 0.00 0.00 11.00 28.18 4.83 28.34
July 0.00 0.00 0.00 0.00 25.00 27.73 9.67 27.90
August 0.00 0.00 0.00 0.00 24.33 27.54 8.50 27.73
September 0.00 0.00 0.00 0.00 4.50 28.29 3.33 28.29
October 0.00 0.00 0.00 0.00 0.67 27.31 0.67 27.31
November 0.00 0.00 0.00 0.00 0.17 27.30 0.17 27.30
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 1.50 19.18 0.00 19.18 77.67 27.66 35.50 27.87
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 1.00 19.22 0.00 19.22 25.00 28.29 9.67 28.34



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 43.33 17.16 11.83 17.35 0.00 17.35 0.00 17.35
February 42.33 17.22 12.67 17.60 0.00 17.60 0.00 17.60
March 10.67 18.16 1.67 18.44 0.00 18.44 0.00 18.44
April 0.67 19.03 0.00 19.03 0.00 19.03 0.00 19.03
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 1.33 27.37 1.00 27.39
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.50 19.31 0.00 19.31 0.00 19.31 0.00 19.31
November 2.17 19.17 0.00 19.17 0.00 19.17 0.00 19.17
December 35.83 17.15 10.83 17.38 0.00 17.38 0.00 17.38
                 
Annual Sum or Average 135.50 17.30 37.00 17.55 1.33 17.62 1.00 17.68
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 43.33 19.31 12.67 19.31 1.33 27.37 1.00 27.39



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 25.33 15.96 3.00 15.88 0.00 15.88 0.00 15.88
February 22.67 15.91 1.67 15.85 0.00 15.85 0.00 15.85
March 5.67 18.05 0.00 18.05 0.00 18.05 0.00 18.05
April 0.83 19.12 0.00 19.12 0.50 22.36 0.50 23.83
May 0.00 0.00 0.00 0.00 1.33 27.80 1.33 27.80
June 0.00 0.00 0.00 0.00 4.67 27.97 4.67 27.97
July 0.00 0.00 0.00 0.00 7.83 28.14 7.83 28.14
August 0.00 0.00 0.00 0.00 3.83 27.74 3.83 27.74
September 0.00 0.00 0.00 0.00 2.33 28.05 2.33 28.05
October 0.33 19.22 0.00 19.22 0.00 19.22 0.00 19.22
November 2.17 19.12 0.00 19.12 0.00 19.12 0.00 19.12
December 22.00 16.17 2.00 16.09 0.00 16.09 0.00 16.09
                 
Annual Sum or Average 79.00 16.29 6.67 16.20 20.50 18.48 20.50 20.02
Minimum of Months 0.00 0.00 0.00 0.00 0.00 15.85 0.00 15.85
Maximum of Months 25.33 19.22 3.00 19.22 7.83 28.14 7.83 28.14



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 21.00 16.45 1.50 16.43 0.00 16.43 0.00 16.43
February 20.17 16.41 0.67 16.40 0.33 16.53 0.33 16.66
March 4.50 18.54 0.00 18.54 0.17 18.77 0.17 18.99
April 0.50 19.12 0.00 19.12 1.00 24.86 1.00 26.00
May 0.00 0.00 0.00 0.00 1.33 27.62 1.33 27.62
June 0.00 0.00 0.00 0.00 3.17 27.64 3.17 27.64
July 0.00 0.00 0.00 0.00 7.50 27.78 7.17 27.79
August 0.00 0.00 0.00 0.00 5.33 27.95 5.17 27.96
September 0.00 0.00 0.00 0.00 4.83 28.26 4.83 28.26
October 0.17 19.23 0.00 19.23 4.50 25.67 4.50 25.79
November 1.50 19.16 0.00 19.16 0.00 19.16 0.00 19.16
December 16.83 16.79 0.83 16.79 0.00 16.79 0.00 16.79
                 
Annual Sum or Average 64.67 16.76 3.00 16.74 28.17 19.91 27.67 21.61
Minimum of Months 0.00 0.00 0.00 0.00 0.00 16.43 0.00 16.43
Maximum of Months 21.00 19.23 1.50 19.23 7.50 28.26 7.17 28.26



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 21.33 16.29 2.17 16.21 0.00 16.21 0.00 16.21
February 17.33 16.38 0.17 16.37 0.00 16.37 0.00 16.37
March 4.17 18.57 0.00 18.57 0.00 18.57 0.00 18.57
April 0.33 19.24 0.00 19.24 1.17 25.77 0.83 26.44
May 0.00 0.00 0.00 0.00 3.83 28.06 2.50 28.08
June 0.00 0.00 0.00 0.00 7.50 28.48 3.67 28.50
July 0.00 0.00 0.00 0.00 9.17 28.50 4.67 28.48
August 0.00 0.00 0.00 0.00 5.00 28.42 2.83 28.49
September 0.00 0.00 0.00 0.00 3.33 28.26 2.00 28.31
October 0.17 19.32 0.00 19.32 0.00 19.32 0.00 19.32
November 1.83 19.25 0.00 19.25 0.00 19.25 0.00 19.25
December 15.50 16.56 1.33 16.48 0.00 16.48 0.00 16.48
                 
Annual Sum or Average 60.67 16.66 3.67 16.59 30.00 20.33 16.50 21.53
Minimum of Months 0.00 0.00 0.00 0.00 0.00 16.21 0.00 16.21
Maximum of Months 21.33 19.32 2.17 19.32 9.17 28.50 4.67 28.50



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 89.83 16.43 30.50 16.69 0.00 16.69 0.00 16.69
February 89.33 16.23 31.67 16.55 0.00 16.55 0.00 16.55
March 35.50 16.80 10.33 17.00 0.00 17.00 0.00 17.00
April 7.17 16.98 1.33 16.85 0.00 16.85 0.00 16.85
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.50 27.31 0.50 27.31
July 0.00 0.00 0.00 0.00 2.17 27.60 1.50 27.61
August 0.00 0.00 0.00 0.00 1.83 27.41 1.67 27.42
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 3.00 18.58 0.33 18.76 0.00 18.76 0.00 18.76
November 9.33 18.15 0.83 18.24 0.00 18.24 0.00 18.24
December 79.67 16.33 27.67 16.55 0.00 16.55 0.00 16.55
                 
Annual Sum or Average 313.83 16.47 102.67 16.70 4.50 16.82 3.67 16.91
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 89.83 18.58 31.67 18.76 2.17 27.60 1.67 27.61



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 54.17 15.12 11.83 15.05 0.00 15.05 0.00 15.05
February 50.83 15.11 10.83 15.07 0.00 15.07 0.00 15.07
March 18.17 15.97 0.67 15.93 0.00 15.93 0.00 15.93
April 4.83 16.55 0.50 16.40 0.00 16.40 0.00 16.40
May 0.00 0.00 0.00 0.00 0.83 27.68 0.83 27.68
June 0.00 0.00 0.00 0.00 5.67 27.80 5.67 27.80
July 0.00 0.00 0.00 0.00 8.67 28.16 8.33 28.17
August 0.00 0.00 0.00 0.00 4.00 27.87 3.83 27.88
September 0.00 0.00 0.00 0.00 1.67 27.78 1.67 27.78
October 2.50 17.78 0.00 17.78 0.00 17.78 0.00 17.78
November 7.67 17.47 0.17 17.42 0.00 17.42 0.00 17.42
December 50.83 15.15 11.67 15.08 0.00 15.08 0.00 15.08
                 
Annual Sum or Average 189.00 15.37 35.67 15.28 20.83 16.36 20.33 17.24
Minimum of Months 0.00 0.00 0.00 0.00 0.00 15.05 0.00 15.05
Maximum of Months 54.17 17.78 11.83 17.78 8.67 28.16 8.33 28.17



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 46.33 15.57 9.00 15.50 0.00 15.50 0.00 15.50
February 48.83 15.60 9.50 15.67 0.00 15.67 0.00 15.67
March 14.67 16.60 0.83 16.62 0.00 16.62 0.00 16.62
April 4.50 16.89 1.00 16.52 0.50 17.45 0.50 18.23
May 0.00 0.00 0.00 0.00 0.83 27.83 0.83 27.83
June 0.00 0.00 0.00 0.00 3.50 27.74 3.50 27.74
July 0.00 0.00 0.00 0.00 8.33 27.88 7.50 27.90
August 0.00 0.00 0.00 0.00 5.33 28.06 4.83 28.08
September 0.00 0.00 0.00 0.00 4.17 28.18 4.17 28.18
October 1.83 18.22 0.00 18.22 0.67 20.69 0.67 22.11
November 5.67 18.17 0.00 18.17 0.00 18.17 0.00 18.17
December 42.00 15.63 7.17 15.62 0.00 15.62 0.00 15.62
                 
Annual Sum or Average 163.83 15.84 27.50 15.81 23.33 17.13 22.00 18.13
Minimum of Months 0.00 0.00 0.00 0.00 0.00 15.50 0.00 15.50
Maximum of Months 48.83 18.22 9.50 18.22 8.33 28.18 7.50 28.18



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 44.00 15.18 10.33 15.09 0.00 15.09 0.00 15.09
February 38.83 15.30 7.00 15.25 0.00 15.25 0.00 15.25
March 12.83 16.45 1.00 16.34 0.00 16.34 0.00 16.34
April 2.50 17.86 0.33 17.52 0.17 18.06 0.17 18.55
May 0.00 0.00 0.00 0.00 3.50 28.07 2.50 28.05
June 0.00 0.00 0.00 0.00 7.33 28.62 3.83 28.64
July 0.00 0.00 0.00 0.00 10.33 28.50 5.33 28.50
August 0.00 0.00 0.00 0.00 5.67 28.40 3.33 28.47
September 0.00 0.00 0.00 0.00 3.00 28.22 2.17 28.20
October 1.83 18.32 0.00 18.32 0.00 18.32 0.00 18.32
November 4.50 18.33 0.00 18.33 0.00 18.33 0.00 18.33
December 35.33 15.41 6.00 15.34 0.00 15.34 0.00 15.34
                 
Annual Sum or Average 139.83 15.58 24.67 15.47 30.00 17.47 17.33 18.36
Minimum of Months 0.00 0.00 0.00 0.00 0.00 15.09 0.00 15.09
Maximum of Months 44.00 18.33 10.33 18.33 10.33 28.62 5.33 28.64



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: GROUNDFLOOR_PLENUM

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: MIDFLOOR_PLENUM

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: TOPFLOOR_PLENUM

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: DATACENTER_MID_ZN_6

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 84.17 28.71 61.00 28.62
August 0.00 0.00 0.00 0.00 254.33 29.45 201.67 29.46
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   338.50 29.27 262.67 29.26
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 254.33 29.45 201.67 29.46



Table of Contents

Report: ComfortReportSimple55Monthly

For: BASEMENT

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 354.17 23.87 34.17 24.05 12.00 24.11
February 327.83 23.75 19.17 23.88 0.00 23.88
March 202.50 23.94 98.17 24.29 0.00 24.29
April 28.00 24.01 97.17 25.68 0.00 25.68
May 18.17 24.00 191.00 25.09 0.00 25.09
June 89.50 24.69 354.33 24.64 89.50 24.65
July 178.50 25.07 486.33 24.74 178.50 24.81
August 72.67 24.94 483.00 24.57 72.67 24.62
September 45.33 25.11 386.33 24.74 45.33 24.77
October 0.50 24.00 225.67 25.23 0.00 25.23
November 38.33 24.00 131.67 25.52 0.00 25.52
December 202.17 23.91 73.00 24.49 0.00 24.49
             
Annual Sum or Average 1557.67 24.14 2580.00 24.63 398.00 24.66
Minimum of Months 0.50 23.75 19.17 23.88 0.00 23.88
Maximum of Months 354.17 25.11 486.33 25.68 178.50 25.68



Table of Contents

Report: ComfortReportSimple55Monthly

For: CORE_BOTTOM

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 442.33 23.75 12.50 23.77 12.50 23.78
February 366.50 23.78 0.00 23.78 0.00 23.78
March 191.00 23.95 99.17 24.19 0.00 24.19
April 25.50 23.97 98.17 25.11 0.00 25.11
May 32.83 23.96 183.67 24.61 0.00 24.61
June 0.00 0.00 368.83 24.32 0.00 24.32
July 0.00 0.00 488.83 24.27 0.00 24.27
August 0.00 0.00 497.17 24.23 0.00 24.23
September 0.50 23.62 375.67 24.40 0.00 24.40
October 20.33 23.91 216.83 24.73 0.00 24.73
November 60.17 23.95 99.17 24.95 0.00 24.95
December 251.17 23.90 38.17 24.09 0.00 24.09
             
Annual Sum or Average 1390.33 23.83 2478.17 24.26 12.50 24.26
Minimum of Months 0.00 0.00 0.00 23.77 0.00 23.78
Maximum of Months 442.33 23.97 497.17 25.11 12.50 25.11



Table of Contents

Report: ComfortReportSimple55Monthly

For: CORE_MID

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 502.00 21.87 86.33 21.60 86.33 21.40
February 454.00 22.10 60.50 21.94 60.50 21.81
March 421.83 23.13 37.00 23.18 4.17 23.16
April 302.83 23.46 7.17 23.49 0.00 23.49
May 143.33 23.67 129.50 24.08 0.00 24.08
June 30.17 23.75 303.17 24.19 0.00 24.19
July 0.00 0.00 480.33 24.23 0.00 24.23
August 0.00 0.00 447.50 24.23 0.00 24.23
September 43.67 23.53 276.33 24.22 0.00 24.22
October 256.17 23.53 55.00 23.67 0.00 23.67
November 411.83 23.35 2.17 23.35 0.00 23.35
December 490.00 22.25 46.33 22.10 46.33 21.98
             
Annual Sum or Average 3055.83 22.76 1931.33 23.19 197.33 23.09
Minimum of Months 0.00 0.00 2.17 21.60 0.00 21.40
Maximum of Months 502.00 23.75 480.33 24.23 86.33 24.23



Table of Contents

Report: ComfortReportSimple55Monthly

For: CORE_TOP

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 502.00 20.80 272.83 20.51 272.83 20.37
February 454.00 21.01 220.00 20.68 220.00 20.51
March 458.17 21.93 136.17 21.72 110.50 21.49
April 400.33 22.68 20.00 22.54 20.00 22.42
May 230.00 23.37 88.00 23.60 0.00 23.60
June 64.17 23.55 296.67 24.08 0.00 24.08
July 0.67 23.58 469.17 24.26 0.00 24.26
August 7.50 23.45 438.50 24.21 0.00 24.21
September 135.83 23.17 219.33 23.83 1.33 23.84
October 386.67 22.46 53.83 22.37 33.17 22.23
November 481.83 22.02 72.50 21.78 72.50 21.60
December 497.00 20.93 230.67 20.62 230.67 20.45
             
Annual Sum or Average 3618.17 21.84 2517.67 22.16 961.00 21.88
Minimum of Months 0.67 20.80 20.00 20.51 0.00 20.37
Maximum of Months 502.00 23.58 469.17 24.26 272.83 24.26



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 502.00 20.98 287.67 20.85 287.67 20.79
February 454.00 21.21 212.00 21.03 212.00 20.94
March 436.00 22.25 98.33 22.18 66.83 22.02
April 322.00 23.15 17.50 23.25 0.00 23.25
May 185.50 23.53 112.17 23.90 0.00 23.90
June 27.00 24.84 354.67 24.38 11.00 24.43
July 14.33 26.68 486.17 24.47 14.33 24.53
August 13.00 25.95 466.50 24.33 9.67 24.37
September 93.33 23.52 251.00 24.09 6.83 24.13
October 344.33 23.07 43.33 23.22 0.00 23.22
November 445.50 22.71 8.50 22.75 0.00 22.75
December 494.83 21.49 129.17 21.31 129.17 21.20
             
Annual Sum or Average 3331.83 22.20 2467.00 22.67 737.50 22.48
Minimum of Months 13.00 20.98 8.50 20.85 0.00 20.79
Maximum of Months 502.00 26.68 486.17 24.47 287.67 24.53



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 502.00 20.95 261.83 20.82 261.83 20.76
February 451.17 21.15 208.83 20.98 208.83 20.89
March 431.00 22.05 83.00 22.06 49.83 21.95
April 312.33 22.62 70.17 22.94 3.17 22.96
May 188.00 23.21 200.50 23.86 9.33 23.94
June 62.67 24.47 377.17 24.36 21.33 24.47
July 35.00 26.67 478.00 24.49 34.00 24.63
August 49.50 24.00 422.83 24.18 13.17 24.25
September 134.83 23.31 292.83 24.03 15.67 24.12
October 345.17 22.59 80.33 22.95 0.50 22.95
November 449.17 22.03 17.50 22.09 6.67 22.07
December 497.00 21.07 185.50 20.94 185.50 20.87
             
Annual Sum or Average 3457.83 21.96 2678.50 22.57 809.83 22.42
Minimum of Months 35.00 20.95 17.50 20.82 0.50 20.76
Maximum of Months 502.00 26.67 478.00 24.49 261.83 24.63



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 470.17 21.17 241.50 20.96 235.67 20.83
February 416.50 21.34 184.33 21.10 178.83 20.95
March 350.50 22.24 120.17 22.43 49.33 22.27
April 285.00 22.79 94.83 23.15 10.33 23.14
May 192.17 23.23 176.67 23.83 5.67 23.88
June 66.50 24.31 365.00 24.33 20.33 24.43
July 40.83 26.48 475.67 24.58 36.67 24.73
August 34.50 25.76 458.17 24.42 23.17 24.53
September 109.83 23.97 332.33 24.33 26.50 24.47
October 254.17 22.76 140.17 23.36 8.67 23.40
November 380.50 22.24 68.83 22.49 15.83 22.44
December 464.67 21.37 176.00 21.23 165.00 21.09
             
Annual Sum or Average 3065.33 22.18 2833.67 22.82 776.00 22.67
Minimum of Months 34.50 21.17 68.83 20.96 5.67 20.83
Maximum of Months 470.17 26.48 475.67 24.58 235.67 24.73



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 499.67 21.26 163.17 21.13 162.67 21.05
February 436.83 21.77 70.67 21.66 68.33 21.56
March 287.33 22.90 115.83 23.33 8.33 23.34
April 100.83 23.87 208.50 24.51 13.50 24.62
May 122.50 23.72 251.83 24.33 18.83 24.46
June 41.33 26.36 453.33 24.66 37.33 24.80
July 83.50 26.32 497.00 24.84 83.50 25.03
August 68.50 26.04 514.00 24.67 68.50 24.81
September 76.17 24.32 362.67 24.44 25.33 24.58
October 200.33 23.12 170.83 23.76 1.67 23.77
November 302.83 23.09 58.33 23.38 0.17 23.39
December 460.67 22.54 18.17 22.51 14.67 22.46
             
Annual Sum or Average 2680.50 22.74 2884.33 23.51 502.83 23.52
Minimum of Months 41.33 21.26 18.17 21.13 0.17 21.05
Maximum of Months 499.67 26.36 514.00 24.84 162.67 25.03



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_MID_ZN_3

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 502.00 19.94 475.33 19.91 475.33 19.90
February 454.00 20.01 427.00 19.98 427.00 19.97
March 484.33 20.91 278.83 20.74 261.83 20.60
April 465.00 21.85 68.17 21.62 68.17 21.44
May 309.00 22.97 63.00 23.17 1.00 23.17
June 80.17 23.74 284.33 24.14 11.50 24.19
July 30.33 25.39 464.50 24.43 28.00 24.49
August 48.83 23.68 399.67 24.18 8.17 24.22
September 220.33 23.00 162.50 23.51 12.17 23.57
October 463.17 21.78 81.33 21.60 75.33 21.44
November 489.00 20.91 203.00 20.70 203.00 20.59
December 497.00 20.00 436.83 19.93 436.83 19.90
             
Annual Sum or Average 4043.17 21.18 3344.50 21.45 2008.33 21.17
Minimum of Months 30.33 19.94 63.00 19.91 1.00 19.90
Maximum of Months 502.00 25.39 475.33 24.43 475.33 24.49



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_MID_ZN_2

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 427.00 19.84 407.83 19.82 407.83 19.81
February 385.00 19.97 343.67 19.90 343.67 19.87
March 407.17 21.02 191.33 20.84 177.17 20.69
April 320.33 21.56 80.33 21.63 47.83 21.46
May 226.67 22.62 120.00 23.29 7.00 23.36
June 96.33 23.88 278.17 24.29 24.67 24.44
July 61.33 26.11 394.67 24.71 54.33 24.90
August 79.67 23.89 327.33 24.27 23.17 24.40
September 186.33 22.84 190.17 23.65 19.17 23.78
October 365.83 21.62 70.67 21.62 48.17 21.49
November 415.67 20.89 168.00 20.69 168.00 20.58
December 422.00 19.88 384.00 19.83 384.00 19.81
             
Annual Sum or Average 3393.33 21.16 2956.17 21.56 1705.00 21.32
Minimum of Months 61.33 19.84 70.67 19.82 7.00 19.81
Maximum of Months 427.00 26.11 407.83 24.71 407.83 24.90



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_MID_ZN_1

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 477.33 20.42 364.50 20.25 359.17 20.15
February 425.33 20.46 299.50 20.24 295.00 20.13
March 390.50 21.49 180.33 21.50 126.33 21.28
April 345.67 21.90 113.83 22.12 49.17 21.96
May 251.00 22.77 141.33 23.37 5.17 23.41
June 108.50 23.64 317.83 24.13 20.83 24.23
July 72.67 25.47 458.50 24.57 54.17 24.73
August 68.33 24.34 423.67 24.34 23.33 24.45
September 155.33 23.49 296.50 24.11 30.67 24.28
October 321.33 22.13 143.50 22.60 36.83 22.52
November 412.00 21.32 158.50 21.31 124.00 21.13
December 479.83 20.43 349.67 20.28 345.00 20.19
             
Annual Sum or Average 3507.83 21.54 3247.67 22.06 1469.67 21.81
Minimum of Months 68.33 20.42 113.83 20.24 5.17 20.13
Maximum of Months 479.83 25.47 458.50 24.57 359.17 24.73



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_MID_ZN_4

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 502.00 20.09 449.17 20.04 449.17 20.02
February 452.00 20.25 363.33 20.14 363.33 20.10
March 459.67 21.19 196.17 21.09 171.50 20.94
April 388.67 21.76 91.50 21.93 41.83 21.81
May 277.00 22.76 151.83 23.38 15.00 23.50
June 105.33 23.74 355.50 24.22 26.50 24.35
July 69.00 25.43 464.00 24.58 53.83 24.72
August 74.33 23.97 429.17 24.30 23.00 24.39
September 219.33 22.93 219.17 23.65 23.17 23.80
October 433.83 21.70 81.00 21.76 44.33 21.65
November 481.33 21.04 155.50 20.86 155.50 20.75
December 497.00 20.18 399.17 20.08 399.17 20.04
             
Annual Sum or Average 3959.50 21.31 3355.50 21.77 1766.33 21.53
Minimum of Months 69.00 20.09 81.00 20.04 15.00 20.02
Maximum of Months 502.00 25.43 464.00 24.58 449.17 24.72



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 502.00 19.74 493.33 19.73 493.33 19.73
February 454.00 19.79 439.00 19.77 439.00 19.77
March 488.83 20.52 341.83 20.37 326.50 20.25
April 474.33 21.35 150.67 21.02 150.67 20.82
May 350.83 22.58 62.50 22.71 12.50 22.65
June 109.67 23.40 276.83 24.01 15.17 24.08
July 52.67 25.13 453.00 24.45 40.50 24.54
August 82.67 23.44 378.17 24.09 13.67 24.14
September 269.17 22.57 148.67 23.11 16.33 23.17
October 478.33 21.10 151.50 20.77 147.00 20.54
November 489.00 20.34 317.33 20.16 317.33 20.08
December 497.00 19.75 473.00 19.72 473.00 19.71
             
Annual Sum or Average 4248.50 20.89 3685.83 21.12 2445.00 20.86
Minimum of Months 52.67 19.74 62.50 19.72 12.50 19.71
Maximum of Months 502.00 25.13 493.33 24.45 493.33 24.54



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 502.00 19.82 494.00 19.81 494.00 19.81
February 454.00 19.91 411.17 19.85 411.17 19.82
March 482.00 20.69 275.00 20.49 254.17 20.32
April 378.33 21.27 128.17 21.16 97.50 20.92
May 264.00 22.39 159.33 23.10 8.67 23.11
June 113.50 23.78 345.67 24.20 30.83 24.35
July 76.17 25.83 464.33 24.63 63.83 24.81
August 92.33 23.66 399.83 24.17 24.33 24.28
September 211.50 22.45 241.33 23.41 18.67 23.50
October 445.50 21.22 129.67 21.02 109.83 20.80
November 489.00 20.46 295.83 20.26 295.83 20.17
December 497.00 19.81 472.67 19.78 472.67 19.77
             
Annual Sum or Average 4005.33 20.93 3817.00 21.35 2281.50 21.09
Minimum of Months 76.17 19.81 128.17 19.78 8.67 19.77
Maximum of Months 502.00 25.83 494.00 24.63 494.00 24.81



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 485.67 20.13 406.83 19.96 404.83 19.89
February 432.67 20.13 341.00 19.93 337.00 19.84
March 419.17 21.03 228.50 20.87 191.50 20.66
April 365.00 21.38 160.33 21.44 105.00 21.21
May 284.00 22.38 135.17 22.92 17.50 22.90
June 137.33 23.29 303.33 23.98 24.00 24.10
July 89.33 25.07 440.83 24.53 59.17 24.70
August 97.17 23.78 398.00 24.22 25.00 24.34
September 193.83 22.94 268.17 23.78 31.33 23.94
October 367.33 21.51 176.00 21.69 89.67 21.43
November 437.67 20.80 232.83 20.60 216.17 20.43
December 486.17 20.06 412.50 19.94 411.67 19.89
             
Annual Sum or Average 3795.33 21.19 3503.50 21.61 1912.83 21.33
Minimum of Months 89.33 20.06 135.17 19.93 17.50 19.84
Maximum of Months 486.17 25.07 440.83 24.53 411.67 24.70



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 502.00 19.88 471.83 19.85 471.83 19.83
February 452.00 20.01 392.83 19.92 392.83 19.89
March 466.33 20.82 255.67 20.66 234.83 20.50
April 398.00 21.32 144.67 21.39 95.67 21.20
May 314.50 22.44 138.33 23.02 19.50 23.11
June 129.17 23.41 331.67 24.09 30.33 24.23
July 89.00 24.97 447.00 24.54 61.17 24.69
August 103.33 23.55 398.33 24.18 27.50 24.29
September 261.50 22.56 191.50 23.32 25.67 23.47
October 454.33 21.23 132.33 21.11 102.50 20.90
November 484.33 20.59 248.67 20.37 248.67 20.26
December 497.00 19.90 439.83 19.83 439.83 19.80
             
Annual Sum or Average 4151.50 21.04 3592.67 21.43 2150.33 21.19
Minimum of Months 89.00 19.88 132.33 19.83 19.50 19.80
Maximum of Months 502.00 24.97 471.83 24.54 471.83 24.69



Table of Contents

Report: ComfortReportSimple55Monthly

For: GROUNDFLOOR_PLENUM

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00
             
Annual Sum or Average 0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: ComfortReportSimple55Monthly

For: MIDFLOOR_PLENUM

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00
             
Annual Sum or Average 0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: ComfortReportSimple55Monthly

For: TOPFLOOR_PLENUM

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00
             
Annual Sum or Average 0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: ComfortReportSimple55Monthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 466.33 27.00 0.00 27.00
February 0.00 0.00 451.00 27.00 0.00 27.00
March 21.33 27.00 514.00 27.00 21.33 27.00
April 75.00 27.00 485.00 27.00 75.00 27.00
May 19.50 27.00 508.00 27.00 19.50 27.00
June 153.00 27.00 496.00 27.00 153.00 27.00
July 301.33 27.00 497.00 27.00 301.33 27.00
August 415.50 27.00 514.00 27.00 415.50 27.00
September 38.33 27.00 485.00 27.00 38.33 27.00
October 16.33 27.00 502.00 27.00 16.33 27.00
November 4.83 27.00 489.00 27.00 4.83 27.00
December 0.67 27.00 497.00 27.00 0.67 27.00
             
Annual Sum or Average 1045.83 27.00 5904.33 27.00 1045.83 27.00
Minimum of Months 0.00 0.00 451.00 27.00 0.00 27.00
Maximum of Months 415.50 27.00 514.00 27.00 415.50 27.00



Table of Contents

Report: ComfortReportSimple55Monthly

For: DATACENTER_MID_ZN_6

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 99.50 25.39 171.00 26.41 0.00 26.41
February 13.67 27.00 220.00 27.00 0.00 27.00
March 0.00 0.00 445.00 27.00 0.00 27.00
April 3.83 27.00 485.00 27.00 3.83 27.00
May 7.50 27.00 508.00 27.00 7.50 27.00
June 46.50 27.00 496.00 27.00 46.50 27.00
July 97.17 27.00 497.00 27.00 97.17 27.00
August 107.67 27.00 514.00 27.00 107.67 27.00
September 12.50 27.00 485.00 27.00 12.50 27.00
October 2.33 27.00 502.00 27.00 2.33 27.00
November 0.00 0.00 481.67 27.00 0.00 27.00
December 0.00 0.00 331.50 27.00 0.00 27.00
             
Annual Sum or Average 390.67 26.59 5136.17 26.97 277.50 26.97
Minimum of Months 0.00 0.00 171.00 26.41 0.00 26.41
Maximum of Months 107.67 27.00 514.00 27.00 107.67 27.00



Table of Contents

Report: ComfortReportSimple55Monthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 236.17 24.79 130.00 25.18 32.83 24.97
February 77.50 27.00 154.83 27.00 0.00 27.00
March 21.17 27.00 366.33 27.00 0.00 27.00
April 5.83 27.00 461.17 27.00 5.83 27.00
May 10.33 27.00 508.00 27.00 10.33 27.00
June 79.17 27.00 496.00 27.00 79.17 27.00
July 143.67 27.00 497.00 27.00 143.67 27.00
August 139.83 27.00 514.00 27.00 139.83 27.00
September 18.50 27.00 485.00 27.00 18.50 27.00
October 2.17 27.00 462.83 27.00 2.17 27.00
November 4.00 27.00 409.50 27.00 0.00 27.00
December 62.67 27.00 234.50 27.00 0.00 27.00
             
Annual Sum or Average 801.00 26.35 4719.17 26.88 432.33 26.86
Minimum of Months 2.17 24.79 130.00 25.18 0.00 24.97
Maximum of Months 236.17 27.00 514.00 27.00 143.67 27.00



Table of Contents

Report: ComfortReportSimple55Monthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 177.83 27.00 502.00 27.00 177.83 27.00
February 454.00 27.00 454.00 27.00 454.00 27.00
March 514.00 27.00 514.00 27.00 514.00 27.00
April 485.00 27.00 485.00 27.00 485.00 27.00
May 497.00 27.00 508.00 27.00 497.00 27.00
June 496.00 27.00 496.00 27.00 496.00 27.00
July 497.00 27.22 497.00 27.22 497.00 27.22
August 514.00 27.99 514.00 27.99 514.00 27.99
September 485.00 27.00 485.00 27.00 485.00 27.00
October 502.00 27.00 502.00 27.00 502.00 27.00
November 489.00 27.00 489.00 27.00 489.00 27.00
December 497.00 27.00 497.00 27.00 497.00 27.00
             
Annual Sum or Average 5607.83 27.11 5943.00 27.11 5607.83 27.11
Minimum of Months 177.83 27.00 454.00 27.00 177.83 27.00
Maximum of Months 514.00 27.99 514.00 27.99 514.00 27.99



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 27.00000 16.93532 0.65059 14.02181
February 454.00000 27.00000 16.13725 0.69452 15.26482
March 514.00000 27.00006 21.79407 0.84618 20.35039
April 485.00000 27.00001 26.65408 0.95241 24.24746
May 508.00000 27.00024 30.39372 0.23811 6.34702
June 496.00000 27.00083 34.90003 0.36410 7.88114
July 497.00000 27.00075 37.35378 0.43726 9.07398
August 514.00000 27.00020 36.59879 0.47193 9.74652
September 485.00000 27.00064 35.88199 0.29378 6.92534
October 502.00000 27.00018 30.25331 0.90744 22.48816
November 489.00000 27.00000 26.10024 0.87971 21.44167
December 497.00000 27.00000 19.09173 0.79982 18.61443
           
Annual Sum or Average 5943.00000 27.00024 27.75127 0.62694 14.67715
Minimum of Months 454.00000 27.00000 16.13725 0.23811 6.34702
Maximum of Months 514.00000 27.00083 37.35378 0.95241 24.24746



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: DATACENTER_MID_ZN_6

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 26.62181 17.11735 0.44098 9.97752
February 454.00000 27.00000 16.12216 0.53602 11.20612
March 514.00000 27.00007 21.78277 0.69396 15.50292
April 485.00000 27.00001 26.63063 0.79650 18.56787
May 508.00000 27.00022 30.40444 0.15007 5.72021
June 496.00000 27.00086 34.91270 0.27322 6.75206
July 497.00000 27.00083 37.37060 0.33522 7.46666
August 514.00000 27.00026 36.59257 0.34088 7.57155
September 485.00000 27.00050 35.99558 0.20708 6.10133
October 502.00000 27.00016 30.23834 0.78956 18.31392
November 489.00000 27.00001 26.06537 0.71390 15.87857
December 497.00000 27.00000 19.06576 0.58781 12.45176
           
Annual Sum or Average 5943.00000 26.96830 27.76841 0.48786 11.27944
Minimum of Months 454.00000 26.62181 16.12216 0.15007 5.72021
Maximum of Months 514.00000 27.00086 37.37060 0.79650 18.56787



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 25.88616 17.46961 0.24947 8.79121
February 454.00000 27.00021 16.12375 0.48269 10.18166
March 514.00000 27.00007 21.79139 0.63688 14.09289
April 485.00000 27.00001 26.63997 0.74967 17.17870
May 508.00000 27.00024 30.43222 0.12042 5.72862
June 496.00000 27.00085 34.92232 0.27154 6.86542
July 497.00000 27.00082 37.37671 0.34386 7.67251
August 514.00000 27.00027 36.60475 0.33905 7.64373
September 485.00000 27.00047 36.05487 0.17769 6.03224
October 502.00000 27.00016 30.26148 0.73216 16.61837
November 489.00000 27.00001 26.08012 0.64157 13.90126
December 497.00000 27.00000 19.07582 0.52243 11.00860
           
Annual Sum or Average 5943.00000 26.90617 27.81338 0.43807 10.46704
Minimum of Months 454.00000 25.88616 16.12375 0.12042 5.72862
Maximum of Months 514.00000 27.00085 37.37671 0.74967 17.17870



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 26.99997 30.03017 1.00739 26.45182
February 454.00000 27.00034 29.87066 1.17273 33.93981
March 514.00000 27.00074 27.55993 1.32969 41.83185
April 485.00000 27.00110 27.22837 1.47513 49.55735
May 508.00000 26.99998 32.44019 0.50316 10.36669
June 496.00000 27.00191 39.67500 0.81200 19.06361
July 497.00000 27.21797 43.10300 1.11547 31.55376
August 514.00000 27.99242 36.26848 1.48488 49.04007
September 485.00000 27.00021 39.47788 0.62224 13.31557
October 502.00000 27.00025 31.39903 1.26253 38.37522
November 489.00000 27.00080 28.84817 1.37187 44.02715
December 497.00000 27.00034 24.44065 1.43755 47.53056
           
Annual Sum or Average 5943.00000 27.10453 32.54138 1.13308 33.77240
Minimum of Months 454.00000 26.99997 24.44065 0.50316 10.36669
Maximum of Months 514.00000 27.99242 43.10300 1.48488 49.55735



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: BASEMENT

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 24.16099 17.82632 0.23363 6.83235
February 454.00000 24.11721 16.43379 0.21424 6.37577
March 514.00000 24.30861 22.87781 0.32254 7.56734
April 485.00000 24.46798 26.36789 0.38997 8.62660
May 508.00000 24.46748 32.21702 -0.4231 9.65621
June 496.00000 24.45628 46.12623 -0.3079 7.97848
July 497.00000 24.61171 57.15787 -0.1756 7.06995
August 514.00000 24.48661 51.02417 -0.2455 7.35190
September 485.00000 24.55147 45.33241 -0.2784 7.84588
October 502.00000 24.56606 31.95159 0.46351 10.09247
November 489.00000 24.55867 25.14181 0.40777 9.05328
December 497.00000 24.42265 18.92740 0.31596 7.53301
           
Annual Sum or Average 5943.00000 24.43285 32.73823 0.07446 8.00873
Minimum of Months 454.00000 24.11721 16.43379 -0.4231 6.37577
Maximum of Months 514.00000 24.61171 57.15787 0.46351 10.09247



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: CORE_BOTTOM

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 23.80591 21.99117 0.16105 6.03822
February 454.00000 23.91762 19.54592 0.17484 5.92357
March 514.00000 24.21628 24.43985 0.31713 7.45697
April 485.00000 24.32678 27.60759 0.38589 8.38858
May 508.00000 24.28137 33.60269 -0.4500 9.79472
June 496.00000 24.24795 45.07541 -0.3487 7.96152
July 497.00000 24.26343 53.48323 -0.2723 6.82102
August 514.00000 24.22283 50.11516 -0.2987 7.10527
September 485.00000 24.31710 45.41105 -0.3420 8.02919
October 502.00000 24.36403 33.78325 0.42799 9.15219
November 489.00000 24.39194 27.30621 0.37936 8.35107
December 497.00000 24.22048 21.35693 0.27581 6.84264
           
Annual Sum or Average 5943.00000 24.21605 33.75127 0.03223 7.66644
Minimum of Months 454.00000 23.80591 19.54592 -0.4500 5.92357
Maximum of Months 514.00000 24.39194 53.48323 0.42799 9.79472



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: CORE_MID

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 21.87129 21.99738 -0.3422 9.34077
February 454.00000 22.09815 21.76791 -0.2863 7.89101
March 514.00000 23.29437 26.98968 0.06393 6.28409
April 485.00000 23.72170 29.86544 0.20352 6.32330
May 508.00000 24.08119 34.32330 -0.5510 11.91467
June 496.00000 24.13135 45.73069 -0.4241 9.16813
July 497.00000 24.21833 54.16685 -0.3300 7.58025
August 514.00000 24.19655 50.89870 -0.3583 7.95710
September 485.00000 24.13714 46.27013 -0.4357 9.53947
October 502.00000 23.82169 35.83048 0.26859 6.90784
November 489.00000 23.45860 30.30152 0.12126 5.87901
December 497.00000 22.27761 24.80722 -0.2192 7.40441
           
Annual Sum or Average 5943.00000 23.45187 35.34559 -0.1909 8.02204
Minimum of Months 454.00000 21.87129 21.76791 -0.5510 5.87901
Maximum of Months 514.00000 24.21833 54.16685 0.26859 11.91467



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: CORE_TOP

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 20.80232 22.99342 -0.6247 16.14340
February 454.00000 21.01389 22.63787 -0.5700 14.79676
March 514.00000 22.16368 28.64241 -0.2198 9.44731
April 485.00000 22.91435 31.55976 0.00041 6.88413
May 508.00000 23.80217 35.11297 -0.6536 15.08913
June 496.00000 24.07027 45.98521 -0.4372 9.64565
July 497.00000 24.23904 54.00717 -0.3115 7.39218
August 514.00000 24.16707 50.91712 -0.3644 8.08152
September 485.00000 23.86448 47.29084 -0.5356 12.30985
October 502.00000 22.81290 38.51421 0.01566 7.09460
November 489.00000 22.04700 33.12722 -0.2315 8.09528
December 497.00000 20.93138 26.20738 -0.5662 14.51421
           
Annual Sum or Average 5943.00000 22.74910 36.51396 -0.3740 10.76858
Minimum of Months 454.00000 20.80232 22.63787 -0.6536 6.88413
Maximum of Months 514.00000 24.23904 54.00717 0.01566 16.14340



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 20.98428 21.02071 -0.5570 12.43026
February 454.00000 21.20919 20.69470 -0.4973 11.17278
March 514.00000 22.52279 25.79624 -0.1185 7.76588
April 485.00000 23.49340 28.27906 0.14794 6.40122
May 508.00000 23.95813 33.88072 -0.5828 13.24791
June 496.00000 24.25531 44.53850 -0.3332 8.15880
July 497.00000 24.39443 52.69437 -0.1977 6.68588
August 514.00000 24.25193 49.49620 -0.2831 7.36937
September 485.00000 24.04114 45.61016 -0.4649 10.61315
October 502.00000 23.40192 34.78608 0.15988 6.54656
November 489.00000 22.84274 28.74508 -0.0305 6.11559
December 497.00000 21.49723 22.99435 -0.4012 9.51872
           
Annual Sum or Average 5943.00000 23.08378 34.14490 -0.2624 8.82571
Minimum of Months 454.00000 20.98428 20.69470 -0.5828 6.11559
Maximum of Months 514.00000 24.39443 52.69437 0.15988 13.24791



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 20.94732 20.33074 -0.5575 12.30789
February 454.00000 21.17000 20.02156 -0.4956 11.32554
March 514.00000 22.37020 25.50893 -0.1193 7.65997
April 485.00000 23.16404 28.27903 0.12967 7.14441
May 508.00000 23.84102 33.65468 -0.5245 13.54953
June 496.00000 24.18310 44.44617 -0.2683 8.43097
July 497.00000 24.30587 52.69291 -0.1423 7.15464
August 514.00000 24.06503 49.86701 -0.2703 8.05478
September 485.00000 23.91671 45.57961 -0.4180 11.23538
October 502.00000 23.09724 34.81107 0.12892 7.10372
November 489.00000 22.21775 28.95793 -0.1514 6.90943
December 497.00000 21.06581 22.85794 -0.5004 10.97955
           
Annual Sum or Average 5943.00000 22.87459 34.02099 -0.2647 9.31084
Minimum of Months 454.00000 20.94732 20.02156 -0.5575 6.90943
Maximum of Months 514.00000 24.30587 52.69291 0.12967 13.54953



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 21.37543 20.24016 -0.4517 12.23637
February 454.00000 21.56135 19.81519 -0.3967 11.18872
March 514.00000 22.87155 24.88958 0.00887 8.17363
April 485.00000 23.36613 28.00257 0.16447 7.65526
May 508.00000 23.85402 33.78474 -0.5622 14.14045
June 496.00000 24.18769 44.55546 -0.3188 8.73661
July 497.00000 24.38673 52.51430 -0.1527 7.01046
August 514.00000 24.25628 49.25914 -0.2073 7.38783
September 485.00000 24.14366 44.95416 -0.3237 9.94270
October 502.00000 23.47350 34.00460 0.23602 8.53610
November 489.00000 22.72217 28.32637 -0.0287 7.45031
December 497.00000 21.57899 22.62904 -0.3766 10.35562
           
Annual Sum or Average 5943.00000 23.16002 33.68390 -0.2000 9.39457
Minimum of Months 454.00000 21.37543 19.81519 -0.5622 7.01046
Maximum of Months 514.00000 24.38673 52.51430 0.23602 14.14045



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 21.27464 19.74005 -0.4510 10.17304
February 454.00000 21.86199 19.00684 -0.2931 8.14176
March 514.00000 23.49086 23.59272 0.18634 7.82980
April 485.00000 24.26517 26.17706 0.44194 10.31273
May 508.00000 24.14045 32.98007 -0.3848 10.73021
June 496.00000 24.44695 43.64005 -0.0910 7.22824
July 497.00000 24.59186 51.63660 0.05825 7.19989
August 514.00000 24.48617 48.39097 0.01385 6.90119
September 485.00000 24.21452 44.65768 -0.2808 8.93870
October 502.00000 23.82198 33.08505 0.32946 8.46871
November 489.00000 23.59117 26.53672 0.20018 6.94495
December 497.00000 22.66228 20.66911 -0.0795 6.39828
           
Annual Sum or Average 5943.00000 23.58188 32.61206 -0.0280 8.27086
Minimum of Months 454.00000 21.27464 19.00684 -0.4510 6.39828
Maximum of Months 514.00000 24.59186 51.63660 0.44194 10.73021



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 19.94313 21.69246 -0.9082 24.75081
February 454.00000 20.01017 21.69138 -0.8736 23.41630
March 514.00000 21.08795 28.19959 -0.5008 14.05520
April 485.00000 21.94071 31.20035 -0.2364 8.44581
May 508.00000 23.40395 35.47299 -0.7873 20.06334
June 496.00000 24.06428 45.60091 -0.4245 9.92434
July 497.00000 24.33683 53.97557 -0.2471 7.10618
August 514.00000 24.11994 50.65232 -0.3683 8.70129
September 485.00000 23.55213 47.39021 -0.6494 16.05053
October 502.00000 21.94845 37.85355 -0.1954 7.99123
November 489.00000 20.91290 31.87238 -0.5135 11.95233
December 497.00000 19.99944 25.05107 -0.8512 22.81193
           
Annual Sum or Average 5943.00000 22.12716 35.98964 -0.5442 14.55051
Minimum of Months 454.00000 19.94313 21.69138 -0.9082 7.10618
Maximum of Months 514.00000 24.33683 53.97557 -0.1954 24.75081



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 427.00000 19.84285 20.69797 -0.9164 25.10922
February 385.00000 19.97162 20.69951 -0.8612 23.18084
March 433.00000 21.19384 27.12101 -0.4400 12.28238
April 410.00000 22.14918 29.85979 -0.1362 8.79343
May 430.00000 23.38139 34.58805 -0.6990 19.62396
June 418.00000 24.06639 45.10849 -0.3273 10.32088
July 422.00000 24.42780 53.29980 -0.1239 7.84034
August 433.00000 24.08274 50.25809 -0.2938 9.24721
September 410.00000 23.53036 46.87994 -0.5714 16.10746
October 427.00000 21.97988 36.66843 -0.1577 8.05761
November 417.00000 20.90307 30.55524 -0.5094 11.92918
December 422.00000 19.88159 24.05547 -0.8747 23.56601
           
Annual Sum or Average 5034.00000 22.13143 35.07089 -0.4905 14.62037
Minimum of Months 385.00000 19.84285 20.69797 -0.9164 7.84034
Maximum of Months 433.00000 24.42780 53.29980 -0.1239 25.10922



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 20.62024 20.62059 -0.6809 19.23897
February 454.00000 20.68444 20.57253 -0.6424 18.21347
March 514.00000 22.13808 26.42740 -0.1785 10.29689
April 485.00000 22.56986 29.49947 -0.0354 8.65176
May 508.00000 23.48910 34.74724 -0.6895 18.58838
June 496.00000 23.99975 45.47207 -0.3963 10.60221
July 497.00000 24.35115 53.58979 -0.1849 7.59390
August 514.00000 24.18354 50.06671 -0.2572 8.37983
September 485.00000 23.92215 45.79230 -0.3993 12.36076
October 502.00000 22.87910 35.26494 0.09185 8.97162
November 489.00000 21.79965 29.91883 -0.2632 9.98672
December 497.00000 20.56906 24.08456 -0.6684 17.91116
           
Annual Sum or Average 5943.00000 22.61603 34.77522 -0.3570 12.53284
Minimum of Months 454.00000 20.56906 20.57253 -0.6895 7.59390
Maximum of Months 514.00000 24.35115 53.58979 0.09185 19.23897



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 20.09439 20.78733 -0.8431 22.30725
February 454.00000 20.27012 20.70136 -0.7737 20.11567
March 514.00000 21.50267 26.97713 -0.3495 11.20959
April 485.00000 22.25312 29.80715 -0.0986 8.62626
May 508.00000 23.38136 34.82679 -0.6778 19.30110
June 496.00000 24.05109 45.16301 -0.2938 10.04710
July 497.00000 24.37291 53.39176 -0.1153 7.62011
August 514.00000 24.14784 50.14945 -0.2340 8.57979
September 485.00000 23.51753 46.94102 -0.5582 15.67999
October 502.00000 22.01120 36.82894 -0.1347 7.82407
November 489.00000 21.08710 30.77000 -0.4460 10.62850
December 497.00000 20.17814 24.16206 -0.7794 19.93957
           
Annual Sum or Average 5943.00000 22.25531 35.14578 -0.4397 13.44465
Minimum of Months 454.00000 20.09439 20.70136 -0.8431 7.62011
Maximum of Months 514.00000 24.37291 53.39176 -0.0986 22.30725



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 19.74287 21.94227 -1.0050 28.92663
February 454.00000 19.79389 21.92344 -0.9740 27.76729
March 514.00000 20.68911 29.00459 -0.6327 18.15633
April 485.00000 21.40872 32.40077 -0.3823 11.13955
May 508.00000 23.03050 36.35091 -0.9167 25.63463
June 496.00000 23.94829 45.98573 -0.4569 11.40884
July 497.00000 24.31118 54.10539 -0.2448 7.42994
August 514.00000 24.03092 50.90036 -0.3936 9.65821
September 485.00000 23.20076 48.49549 -0.7714 21.09056
October 502.00000 21.23815 39.60708 -0.3852 11.89128
November 489.00000 20.33860 33.63801 -0.6923 17.61264
December 497.00000 19.75483 25.57786 -0.9656 27.57716
           
Annual Sum or Average 5943.00000 21.80798 36.76318 -0.6494 18.12511
Minimum of Months 454.00000 19.74287 21.92344 -1.0050 7.42994
Maximum of Months 514.00000 24.31118 54.10539 -0.2448 28.92663



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 19.81895 21.35733 -0.9656 27.33535
February 454.00000 19.91343 21.34481 -0.9142 25.63827
March 514.00000 20.89182 28.21061 -0.5328 15.76699
April 485.00000 21.89579 30.92722 -0.2081 10.42324
May 508.00000 23.24466 35.15932 -0.7376 21.20504
June 496.00000 24.00110 45.33174 -0.3219 10.42575
July 497.00000 24.35404 53.36962 -0.1116 7.71805
August 514.00000 24.01433 50.45239 -0.2862 9.35976
September 485.00000 23.35862 47.45027 -0.6190 17.89925
October 502.00000 21.53025 38.25442 -0.2799 10.49562
November 489.00000 20.45840 32.76318 -0.6488 16.33571
December 497.00000 19.81281 25.09803 -0.9428 26.58222
           
Annual Sum or Average 5943.00000 21.95794 35.91227 -0.5448 16.53394
Minimum of Months 454.00000 19.81281 21.34481 -0.9656 7.71805
Maximum of Months 514.00000 24.35404 53.36962 -0.1116 27.33535



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 20.26191 21.10493 -0.8081 23.47296
February 454.00000 20.31334 21.06005 -0.7709 22.98178
March 514.00000 21.57776 27.42977 -0.3399 13.49840
April 485.00000 22.07938 30.67327 -0.1722 10.50446
May 508.00000 23.16067 35.53218 -0.8059 23.44659
June 496.00000 23.85410 45.94366 -0.4365 12.40135
July 497.00000 24.28331 53.84501 -0.1943 8.21747
August 514.00000 24.07224 50.36184 -0.2882 9.46981
September 485.00000 23.63292 46.71514 -0.5026 15.96241
October 502.00000 22.23113 36.83168 -0.0842 10.67307
November 489.00000 21.13922 31.76699 -0.4565 13.87229
December 497.00000 20.14606 24.86619 -0.8165 22.92134
           
Annual Sum or Average 5943.00000 22.24534 35.61428 -0.4711 15.57103
Minimum of Months 454.00000 20.14606 21.06005 -0.8165 8.21747
Maximum of Months 514.00000 24.28331 53.84501 -0.0842 23.47296



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 19.88490 21.20248 -0.9376 26.26055
February 454.00000 20.03241 21.10708 -0.8672 24.03446
March 514.00000 21.11307 27.78458 -0.4700 14.33521
April 485.00000 21.84424 30.85028 -0.2137 10.29099
May 508.00000 23.06029 35.56095 -0.7885 23.92374
June 496.00000 23.91116 45.60883 -0.3318 11.68246
July 497.00000 24.30113 53.66362 -0.1265 8.24861
August 514.00000 24.02904 50.46482 -0.2668 9.66987
September 485.00000 23.20139 47.89593 -0.6661 19.86906
October 502.00000 21.48993 38.18600 -0.2790 10.27255
November 489.00000 20.62264 32.38323 -0.5908 14.76380
December 497.00000 19.89592 24.90025 -0.8888 24.53819
           
Annual Sum or Average 5943.00000 21.96534 35.90381 -0.5332 16.43611
Minimum of Months 454.00000 19.88490 21.10708 -0.9376 8.24861
Maximum of Months 514.00000 24.30113 53.66362 -0.1265 26.26055



Table of Contents

Report: ChillerReportMonthly

For: COOLSYS1 CHILLER1

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

CHILLER ELECTRICITY ENERGY [J] CHILLER ELECTRICITY RATE {Maximum} [W] CHILLER ELECTRICITY RATE {TIMESTAMP} CHILLER ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] CHILLER EVAPORATOR COOLING ENERGY [J] CHILLER EVAPORATOR COOLING RATE [] CHILLER CONDENSER HEAT TRANSFER ENERGY [J] CHILLER COP [W/W] CHILLER COP {Maximum} [W/W] CHILLER COP {TIMESTAMP} CHILLER PART LOAD RATIO [] CHILLER PART LOAD RATIO []
January 0.176463E+09 1450.49 20-JAN-13:10 34.81 0.755364E+09 0.00 0.931827E+09 0.20 4.29 03-JAN-07:20 0.00 0.00
February 0.212974E+09 1669.50 28-FEB-14:10 41.75 0.911612E+09 0.00 0.112459E+10 0.27 4.29 05-FEB-02:00 0.00 0.00
March 0.961243E+10 170466.72 15-MAR-14:10 85.17 0.621028E+11 0.00 0.717152E+11 0.56 7.49 15-MAR-12:50 0.00 0.00
April 0.506808E+10 78113.06 07-APR-14:00 86.34 0.240036E+11 0.00 0.290716E+11 0.53 6.50 07-APR-14:00 0.00 0.00
May 0.383986E+11 183815.59 10-MAY-14:20 226.77 0.217446E+12 0.00 0.255845E+12 1.52 7.57 23-MAY-14:50 0.00 0.00
June 0.121199E+12 192012.04 01-JUN-15:00 432.75 0.788224E+12 0.00 0.909423E+12 3.54 7.57 30-JUN-16:10 0.00 0.00
July 0.182873E+12 206368.48 20-JUL-05:04 567.16 0.123586E+13 0.00 0.141873E+13 4.69 7.57 18-JUL-04:13 0.00 0.00
August 0.161191E+12 213492.84 15-AUG-14:40 559.06 0.108634E+13 0.00 0.124753E+13 4.50 7.56 23-AUG-13:20 0.00 0.00
September 0.814864E+11 191229.00 15-SEP-14:00 331.61 0.518908E+12 0.00 0.600394E+12 2.59 7.56 20-SEP-12:50 0.00 0.00
October 0.142244E+11 118361.43 11-OCT-14:40 132.29 0.736846E+11 0.00 0.879089E+11 0.82 7.38 11-OCT-14:40 0.00 0.00
November 0.260021E+10 57956.18 16-NOV-13:10 80.99 0.110937E+11 0.00 0.136939E+11 0.48 4.41 16-NOV-13:10 0.00 0.00
December 0.295159E+09 7017.30 01-DEC-06:02 56.88 0.126341E+10 0.00 0.155857E+10 0.33 4.29 04-DEC-07:20 0.00 0.00
                         
Annual Sum or Average 0.617338E+12     2635.60 0.402059E+13 0.00 0.463792E+13 1.68     0.00 0.00
Minimum of Months 0.176463E+09 1450.49   34.81 0.755364E+09 0.00 0.931827E+09 0.20 4.29   0.00 0.00
Maximum of Months 0.182873E+12 213492.84   567.16 0.123586E+13 0.00 0.141873E+13 4.69 7.57   0.00 0.00



Table of Contents

Report: ChillerReportMonthly

For: COOLSYS1 CHILLER2

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

CHILLER ELECTRICITY ENERGY [J] CHILLER ELECTRICITY RATE {Maximum} [W] CHILLER ELECTRICITY RATE {TIMESTAMP} CHILLER ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] CHILLER EVAPORATOR COOLING ENERGY [J] CHILLER EVAPORATOR COOLING RATE [] CHILLER CONDENSER HEAT TRANSFER ENERGY [J] CHILLER COP [W/W] CHILLER COP {Maximum} [W/W] CHILLER COP {TIMESTAMP} CHILLER PART LOAD RATIO [] CHILLER PART LOAD RATIO []
January 0.00 0.00 01-JAN-00:03 0.00 0.00 0.00 0.00 0.00 0.00 01-JAN-00:03 0.00 0.00
February 0.00 0.00 01-FEB-00:03 0.00 0.00 0.00 0.00 0.00 0.00 01-FEB-00:03 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00 0.00 01-APR-00:10 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00 0.00 01-MAY-00:10 0.00 0.00
June 0.220392E+11 168651.43 27-JUN-07:40 54.25 0.153165E+12 0.00 0.175204E+12 0.52 7.23 30-JUN-15:30 0.00 0.00
July 0.540922E+11 206368.48 20-JUL-05:04 123.06 0.373803E+12 0.00 0.427895E+12 1.14 7.26 27-JUL-05:05 0.00 0.00
August 0.382948E+11 213492.84 15-AUG-14:40 90.63 0.266188E+12 0.00 0.304482E+12 0.84 7.39 04-AUG-11:00 0.00 0.00
September 0.100641E+11 152244.61 15-SEP-15:00 25.33 0.703757E+11 0.00 0.804398E+11 0.24 7.28 21-SEP-14:30 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 0.00 0.00
                         
Annual Sum or Average 0.124490E+12     293.27 0.863531E+12 0.00 0.988021E+12 0.23     0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00 0.00   0.00 0.00
Maximum of Months 0.540922E+11 213492.84   123.06 0.373803E+12 0.00 0.427895E+12 1.14 7.39   0.00 0.00



Table of Contents

Report: TowerReportMonthly

For: CENTRAL TOWER

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

COOLING TOWER FAN ELECTRICITY ENERGY [J] COOLING TOWER FAN ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] COOLING TOWER FAN ELECTRICITY RATE {Maximum} [W] COOLING TOWER FAN ELECTRICITY RATE {TIMESTAMP} COOLING TOWER HEAT TRANSFER RATE {Maximum} [W] COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} COOLING TOWER INLET TEMPERATURE [C] COOLING TOWER OUTLET TEMPERATURE [C] COOLING TOWER MASS FLOW RATE [kg/s]
January 0.684219E+09 744.00 1252.75 11-JAN-16:00 31447.16 12-JAN-16:40 18.56 18.33 14.39
February 0.206348E+10 672.00 3951.72 22-FEB-18:00 68928.76 28-FEB-17:00 19.13 18.33 14.39
March 0.128984E+11 744.00 49248.27 12-MAR-13:00 515564.58 14-MAR-13:10 20.43 18.61 14.39
April 0.224974E+11 720.00 49248.27 07-APR-09:40 448765.16 08-APR-14:00 21.11 18.43 14.39
May 0.311462E+11 744.00 49248.27 09-MAY-11:50 209588.40 10-MAY-15:00 19.46 18.76 14.39
June 0.866286E+11 720.00 49248.27 01-JUN-09:40 629708.01 27-JUN-14:30 24.82 21.66 14.39
July 0.122599E+12 744.00 49248.27 01-JUL-06:40 725236.04 21-JUL-03:02 35.66 26.54 14.39
August 0.123285E+12 744.00 49248.27 01-AUG-00:03 746099.07 13-AUG-16:02 36.55 25.96 14.39
September 0.587160E+11 720.00 49248.27 01-SEP-12:50 271434.00 15-SEP-12:10 20.45 19.62 14.39
October 0.175560E+11 744.00 49248.27 03-OCT-13:00 204666.71 11-OCT-15:00 19.58 18.45 14.39
November 0.134215E+11 720.00 49248.27 04-NOV-13:20 254179.61 05-NOV-14:00 20.08 18.39 14.39
December 0.605579E+10 744.00 40324.07 01-DEC-11:00 266383.97 01-DEC-11:00 20.30 18.33 14.39
                   
Annual Sum or Average 0.497552E+12 8760.00         23.06 20.14 14.39
Minimum of Months 0.684219E+09 672.00 1252.75   31447.16   18.56 18.33 14.39
Maximum of Months 0.123285E+12 744.00 49248.27   746099.07   36.55 26.54 14.39



Table of Contents

Report: TowerReportMonthly

For: TOWERWATERSYS COOLTOWER 1

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

COOLING TOWER FAN ELECTRICITY ENERGY [J] COOLING TOWER FAN ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] COOLING TOWER FAN ELECTRICITY RATE {Maximum} [W] COOLING TOWER FAN ELECTRICITY RATE {TIMESTAMP} COOLING TOWER HEAT TRANSFER RATE {Maximum} [W] COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} COOLING TOWER INLET TEMPERATURE [C] COOLING TOWER OUTLET TEMPERATURE [C] COOLING TOWER MASS FLOW RATE [kg/s]
January 0.00 0.00 0.00 01-JAN-00:03 246847.21 23-JAN-07:20 20.96 20.96 0.37
February 0.00 0.00 0.00 01-FEB-00:03 246515.83 23-FEB-13:30 20.99 20.98 0.36
March 0.821539E+09 27.95 20504.38 14-MAR-10:50 1423392.97 15-MAR-14:20 21.11 21.01 3.48
April 23595268.98 19.00 1002.02 08-APR-13:50 600853.36 07-APR-14:00 21.02 20.97 3.80
May 0.920913E+09 156.54 20504.38 10-MAY-12:00 1365961.02 23-MAY-14:50 21.55 21.20 19.19
June 0.133426E+11 388.23 20504.38 01-JUN-13:00 1473466.47 30-JUN-14:30 22.96 21.74 39.91
July 0.281050E+11 529.69 20504.38 01-JUL-14:00 1576467.98 05-JUL-16:00 24.43 22.58 50.18
August 0.215655E+11 486.66 20504.38 01-AUG-11:50 1637048.88 15-AUG-14:40 23.55 21.91 49.06
September 0.787035E+10 281.43 20504.38 08-SEP-10:50 1495105.71 20-SEP-15:30 22.41 21.59 30.45
October 0.184537E+09 66.83 3878.57 11-OCT-15:00 1005383.23 11-OCT-15:00 21.16 21.04 8.69
November 19351031.40 13.99 654.44 16-NOV-17:00 328546.76 16-NOV-13:10 21.00 20.98 2.37
December 0.00 0.00 0.00 01-DEC-00:10 246387.18 06-DEC-05:21 20.93 20.92 0.45
                   
Annual Sum or Average 0.728533E+11 1970.32         21.85 21.33 17.48
Minimum of Months 0.00 0.00 0.00   246387.18   20.93 20.92 0.36
Maximum of Months 0.281050E+11 529.69 20504.38   1637048.88   24.43 22.58 50.18



Table of Contents

Report: TowerReportMonthly

For: TOWERWATERSYS COOLTOWER 2

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

COOLING TOWER FAN ELECTRICITY ENERGY [J] COOLING TOWER FAN ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] COOLING TOWER FAN ELECTRICITY RATE {Maximum} [W] COOLING TOWER FAN ELECTRICITY RATE {TIMESTAMP} COOLING TOWER HEAT TRANSFER RATE {Maximum} [W] COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} COOLING TOWER INLET TEMPERATURE [C] COOLING TOWER OUTLET TEMPERATURE [C] COOLING TOWER MASS FLOW RATE [kg/s]
January 0.00 0.00 0.00 01-JAN-00:03 0.00 01-JAN-00:03 20.96 20.96 0.00
February 0.00 0.00 0.00 01-FEB-00:03 0.00 01-FEB-00:03 20.99 20.99 0.00
March 0.00 0.00 0.00 01-MAR-00:10 0.00 01-MAR-00:10 21.11 21.11 0.00
April 0.00 0.00 0.00 01-APR-00:10 0.00 01-APR-00:10 21.02 21.02 0.00
May 12302627.09 0.17 20504.38 10-MAY-13:40 885755.07 10-MAY-13:40 21.55 21.55 0.01
June 0.464393E+10 63.49 20504.38 01-JUN-15:40 1309602.09 27-JUN-07:40 22.96 22.66 5.64
July 0.120805E+11 163.66 20504.38 03-JUL-12:50 1576467.98 05-JUL-16:00 24.43 23.62 13.37
August 0.729395E+10 99.18 20504.38 02-AUG-13:20 1637048.88 15-AUG-14:40 23.55 23.06 8.57
September 0.213481E+10 29.07 20504.38 08-SEP-12:50 1243656.55 20-SEP-14:30 22.41 22.27 2.60
October 0.00 0.00 0.00 01-OCT-00:10 0.00 01-OCT-00:10 21.16 21.16 0.00
November 0.00 0.00 0.00 01-NOV-00:10 0.00 01-NOV-00:10 21.00 21.00 0.00
December 0.00 0.00 0.00 01-DEC-00:10 0.00 01-DEC-00:10 20.93 20.93 0.00
                   
Annual Sum or Average 0.261655E+11 355.56         21.85 21.70 2.54
Minimum of Months 0.00 0.00 0.00   0.00   20.93 20.93 0.00
Maximum of Months 0.120805E+11 163.66 20504.38   1637048.88   24.43 23.62 13.37



Table of Contents

Report: BoilerReportMonthly

For: HEATSYS1 BOILER

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

BOILER HEATING ENERGY [J] BOILER GAS CONSUMPTION [] BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] BOILER HEATING RATE {Maximum} [W] BOILER HEATING RATE {TIMESTAMP} BOILER GAS CONSUMPTION RATE [] BOILER INLET TEMPERATURE [C] BOILER OUTLET TEMPERATURE [C] BOILER MASS FLOW RATE [kg/s] BOILER ANCILLARY ELECTRICITY RATE [W] BOILER PART LOAD RATIO [] BOILER PART LOAD RATIO {Maximum} [] BOILER PART LOAD RATIO {TIMESTAMP}
January 0.442715E+12 0.00 592.52 2176872.57 02-JAN-04:01 0.00 32.45 71.52 0.90 0.00 0.05 0.71 02-JAN-04:01
February 0.376235E+12 0.00 535.39 1938265.26 27-FEB-05:01 0.00 32.31 71.26 0.87 0.00 0.05 0.63 27-FEB-05:01
March 0.151668E+12 0.00 446.87 1743053.54 06-MAR-06:02 0.00 28.95 59.32 0.31 0.00 0.02 0.57 06-MAR-06:02
April 0.497038E+11 0.00 282.94 1580320.80 11-APR-04:11 0.00 26.98 48.07 0.09 0.00 0.01 0.51 11-APR-04:11
May 0.310459E+10 0.00 88.69 281524.33 03-MAY-06:10 0.00 27.38 33.93 0.00 0.00 0.00 0.09 03-MAY-06:10
June 0.388426E+09 0.00 13.37 123771.03 13-JUN-06:10 0.00 26.17 27.21 0.00 0.00 0.00 0.04 13-JUN-06:10
July 2412.93 0.00 0.17 4.02 15-JUL-11:20 0.00 25.97 25.99 0.00 0.00 0.00 0.00 15-JUL-11:20
August 6502281.84 0.00 2.96 6141.96 03-AUG-06:10 0.00 26.20 26.43 0.00 0.00 0.00 0.00 03-AUG-06:10
September 0.198659E+10 0.00 45.38 301044.60 30-SEP-06:10 0.00 37.97 41.07 0.00 0.00 0.00 0.10 30-SEP-06:10
October 0.374007E+11 0.00 249.51 1659501.42 30-OCT-04:01 0.00 26.63 44.85 0.07 0.00 0.00 0.54 30-OCT-04:01
November 0.117706E+12 0.00 391.99 1719316.19 20-NOV-05:11 0.00 25.78 55.08 0.22 0.00 0.01 0.56 20-NOV-05:11
December 0.375069E+12 0.00 576.08 1833400.48 11-DEC-06:01 0.00 32.32 69.98 0.77 0.00 0.05 0.60 11-DEC-06:01
                           
Annual Sum or Average 0.155598E+13 0.00 3225.88     0.00 29.06 47.75 0.27 0.00 0.02    
Minimum of Months 2412.93 0.00 0.17 4.02   0.00 25.78 25.99 0.00 0.00 0.00 0.00  
Maximum of Months 0.442715E+12 0.00 592.52 2176872.57   0.00 37.97 71.52 0.90 0.00 0.05 0.71  



Table of Contents

Report: BoilerReportMonthly

For: CENTRAL BOILER

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

BOILER HEATING ENERGY [J] BOILER GAS CONSUMPTION [] BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] BOILER HEATING RATE {Maximum} [W] BOILER HEATING RATE {TIMESTAMP} BOILER GAS CONSUMPTION RATE [] BOILER INLET TEMPERATURE [C] BOILER OUTLET TEMPERATURE [C] BOILER MASS FLOW RATE [kg/s] BOILER ANCILLARY ELECTRICITY RATE [W] BOILER PART LOAD RATIO [] BOILER PART LOAD RATIO []
January 0.00 0.00 0.00 0.00 01-JAN-00:03 0.00 18.56 18.56 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 01-FEB-00:03 0.00 19.13 19.13 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 01-MAR-00:10 0.00 20.43 20.43 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 01-APR-00:10 0.00 21.11 21.11 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 01-MAY-00:10 0.00 19.46 19.46 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 01-JUN-00:10 0.00 24.82 24.82 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 01-JUL-00:10 0.00 35.66 35.66 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 01-AUG-00:03 0.00 36.55 36.55 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 01-SEP-00:10 0.00 20.45 20.45 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 01-OCT-00:10 0.00 19.58 19.58 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 01-NOV-00:10 0.00 20.08 20.08 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 01-DEC-00:10 0.00 20.30 20.30 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.00 0.00 0.00     0.00 23.06 23.06 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00   0.00 18.56 18.56 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00   0.00 36.55 36.55 0.00 0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: VAV_BOT WITH REHEAT COOLING COIL

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 15133938.07 0.00 14.42 15133938.07 0.00 0.00 0.00 0.00 4338.63 18-JAN-13:10 4338.63 18-JAN-13:10 0.00 0.00 0.00
February 30370707.14 0.00 18.08 30370707.14 0.00 0.00 0.00 0.00 13132.71 14-FEB-15:05 13132.71 14-FEB-15:05 0.00 0.00 0.00
March 0.636447E+10 0.00 50.75 0.617335E+10 0.00 0.00 0.00 0.00 113138.33 14-MAR-13:10 109468.79 15-MAR-14:10 0.00 0.00 0.00
April 0.263950E+10 0.00 53.20 0.263950E+10 0.00 0.00 0.00 0.00 55809.84 07-APR-14:00 55809.84 07-APR-14:00 0.00 0.00 0.00
May 0.198913E+11 0.00 215.58 0.196449E+11 0.00 0.00 0.00 0.00 107783.30 24-MAY-05:03 96814.95 23-MAY-14:30 0.00 0.00 0.00
June 0.873465E+11 0.00 416.93 0.691969E+11 0.00 0.00 0.00 0.00 233622.86 27-JUN-07:50 128798.47 12-JUN-04:12 0.00 0.00 0.00
July 0.155884E+12 0.00 542.43 0.112842E+12 0.00 0.00 0.00 0.00 313195.47 20-JUL-05:02 139907.62 21-JUL-05:03 0.00 0.00 0.00
August 0.137201E+12 0.00 542.51 0.107087E+12 0.00 0.00 0.00 0.00 308028.85 14-AUG-05:03 141449.26 14-AUG-15:10 0.00 0.00 0.00
September 0.531998E+11 0.00 319.01 0.423298E+11 0.00 0.00 0.00 0.00 204540.98 16-SEP-05:02 116090.47 21-SEP-15:30 0.00 0.00 0.00
October 0.736889E+10 0.00 99.39 0.736317E+10 0.00 0.00 0.00 0.00 84349.94 11-OCT-15:00 84349.94 11-OCT-15:00 0.00 0.00 0.00
November 0.119546E+10 0.00 36.32 0.119546E+10 0.00 0.00 0.00 0.00 55937.35 27-NOV-05:12 55937.35 27-NOV-05:12 0.00 0.00 0.00
December 23996758.26 0.00 20.38 23996758.26 0.00 0.00 0.00 0.00 4685.28 19-DEC-13:10 4685.28 19-DEC-13:10 0.00 0.00 0.00
                               
Annual Sum or Average 0.471160E+12 0.00 2328.99 0.368541E+12 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 15133938.07 0.00 14.42 15133938.07 0.00 0.00 0.00 0.00 4338.63   4338.63   0.00 0.00 0.00
Maximum of Months 0.155884E+12 0.00 542.51 0.112842E+12 0.00 0.00 0.00 0.00 313195.47   141449.26   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: VAV_MID WITH REHEAT COOLING COIL

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 74783.10 0.00 27.44 74783.10 0.00 0.00 0.00 0.00 138.77 06-JAN-17:15 138.77 06-JAN-17:15 0.00 0.00 0.00
February 6151402.80 0.00 33.20 6151402.80 0.00 0.00 0.00 0.00 8316.78 28-FEB-14:50 8316.78 28-FEB-14:50 0.00 0.00 0.00
March 0.439210E+11 0.00 63.87 0.428562E+11 0.00 0.00 0.00 0.00 844458.96 15-MAR-14:20 844458.96 15-MAR-14:20 0.00 0.00 0.00
April 0.172933E+11 0.00 63.24 0.172933E+11 0.00 0.00 0.00 0.00 383718.89 07-APR-14:00 383718.89 07-APR-14:00 0.00 0.00 0.00
May 0.168731E+12 0.00 210.83 0.166816E+12 0.00 0.00 0.00 0.00 938097.25 10-MAY-14:40 871685.01 23-MAY-14:30 0.00 0.00 0.00
June 0.719590E+12 0.00 392.15 0.577213E+12 0.00 0.00 0.00 0.00 1971307.61 27-JUN-05:03 1124754.13 12-JUN-15:20 0.00 0.00 0.00
July 0.121862E+13 0.00 449.99 0.899969E+12 0.00 0.00 0.00 0.00 2940046.35 20-JUL-05:02 1255865.60 16-JUL-16:31 0.00 0.00 0.00
August 0.100915E+13 0.00 433.71 0.815634E+12 0.00 0.00 0.00 0.00 2613186.77 14-AUG-04:12 1242246.95 09-AUG-15:20 0.00 0.00 0.00
September 0.450278E+12 0.00 313.04 0.362418E+12 0.00 0.00 0.00 0.00 1750087.72 16-SEP-05:02 1081132.70 21-SEP-15:50 0.00 0.00 0.00
October 0.557712E+11 0.00 106.91 0.557484E+11 0.00 0.00 0.00 0.00 678165.67 11-OCT-15:00 678165.67 11-OCT-15:00 0.00 0.00 0.00
November 0.700992E+10 0.00 48.06 0.700992E+10 0.00 0.00 0.00 0.00 194113.19 16-NOV-13:10 194113.19 16-NOV-13:10 0.00 0.00 0.00
December 647703.50 0.00 53.57 647703.50 0.00 0.00 0.00 0.00 120.37 14-DEC-12:10 120.37 14-DEC-12:10 0.00 0.00 0.00
                               
Annual Sum or Average 0.369036E+13 0.00 2196.01 0.294496E+13 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 74783.10 0.00 27.44 74783.10 0.00 0.00 0.00 0.00 120.37   120.37   0.00 0.00 0.00
Maximum of Months 0.121862E+13 0.00 449.99 0.899969E+12 0.00 0.00 0.00 0.00 2940046.35   1255865.60   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: VAV_TOP WITH REHEAT COOLING COIL

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 1891717.87 0.00 14.39 1891717.87 0.00 0.00 0.00 0.00 777.89 07-JAN-23:12 777.89 07-JAN-23:12 0.00 0.00 0.00
February 2999215.84 0.00 17.91 2999215.84 0.00 0.00 0.00 0.00 875.54 28-FEB-13:10 875.54 28-FEB-13:10 0.00 0.00 0.00
March 0.461181E+10 0.00 68.72 0.460139E+10 0.00 0.00 0.00 0.00 103313.64 15-MAR-14:10 103313.64 15-MAR-14:10 0.00 0.00 0.00
April 0.165045E+10 0.00 70.61 0.165045E+10 0.00 0.00 0.00 0.00 37829.97 07-APR-14:00 37829.97 07-APR-14:00 0.00 0.00 0.00
May 0.168839E+11 0.00 206.26 0.167360E+11 0.00 0.00 0.00 0.00 109840.20 10-MAY-14:40 101882.32 10-MAY-14:30 0.00 0.00 0.00
June 0.776562E+11 0.00 387.94 0.620073E+11 0.00 0.00 0.00 0.00 317802.08 27-JUN-15:00 139709.89 12-JUN-14:00 0.00 0.00 0.00
July 0.133148E+12 0.00 447.57 0.983701E+11 0.00 0.00 0.00 0.00 298283.71 20-JUL-05:02 153164.29 21-JUL-05:03 0.00 0.00 0.00
August 0.108163E+12 0.00 428.80 0.869952E+11 0.00 0.00 0.00 0.00 282148.92 14-AUG-04:12 145531.49 09-AUG-15:10 0.00 0.00 0.00
September 0.445474E+11 0.00 306.37 0.357347E+11 0.00 0.00 0.00 0.00 192984.29 15-SEP-12:40 124872.79 21-SEP-15:50 0.00 0.00 0.00
October 0.485472E+10 0.00 113.39 0.485472E+10 0.00 0.00 0.00 0.00 67295.36 11-OCT-15:00 67295.36 11-OCT-15:00 0.00 0.00 0.00
November 0.655271E+09 0.00 65.28 0.655271E+09 0.00 0.00 0.00 0.00 15780.51 16-NOV-13:00 15780.51 16-NOV-13:00 0.00 0.00 0.00
December 3384188.89 0.00 24.91 3384188.89 0.00 0.00 0.00 0.00 877.06 11-DEC-05:40 877.06 11-DEC-05:40 0.00 0.00 0.00
                               
Annual Sum or Average 0.392178E+12 0.00 2152.14 0.311613E+12 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 1891717.87 0.00 14.39 1891717.87 0.00 0.00 0.00 0.00 777.89   777.89   0.00 0.00 0.00
Maximum of Months 0.133148E+12 0.00 447.57 0.983701E+11 0.00 0.00 0.00 0.00 317802.08   153164.29   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: CAV_BAS COOLING COIL

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 84197.20 0.00 0.69 84197.20 0.00 0.00 0.00 0.00 60.53 06-JAN-17:15 60.53 06-JAN-17:15 0.00 0.00 0.00
February 196614.84 0.00 0.92 196614.84 0.00 0.00 0.00 0.00 292.94 09-FEB-11:00 292.94 09-FEB-11:00 0.00 0.00 0.00
March 0.351920E+10 0.00 28.80 0.350257E+10 0.00 0.00 0.00 0.00 71189.91 16-MAR-04:11 61718.94 16-MAR-04:11 0.00 0.00 0.00
April 0.607669E+09 0.00 15.19 0.607669E+09 0.00 0.00 0.00 0.00 27932.90 08-APR-04:12 27932.90 08-APR-04:12 0.00 0.00 0.00
May 0.831938E+10 0.00 117.05 0.827302E+10 0.00 0.00 0.00 0.00 98076.02 24-MAY-05:03 59106.24 24-MAY-05:03 0.00 0.00 0.00
June 0.420856E+11 0.00 293.67 0.355007E+11 0.00 0.00 0.00 0.00 144283.93 27-JUN-04:53 77739.98 12-JUN-04:12 0.00 0.00 0.00
July 0.802959E+11 0.00 368.96 0.608901E+11 0.00 0.00 0.00 0.00 180591.72 20-JUL-04:33 109939.97 04-JUL-15:48 0.00 0.00 0.00
August 0.705731E+11 0.00 378.19 0.579471E+11 0.00 0.00 0.00 0.00 185702.80 13-AUG-17:20 112263.09 06-AUG-15:39 0.00 0.00 0.00
September 0.300396E+11 0.00 236.69 0.252107E+11 0.00 0.00 0.00 0.00 126332.32 16-SEP-04:12 68497.91 25-SEP-13:10 0.00 0.00 0.00
October 0.290239E+10 0.00 56.97 0.287536E+10 0.00 0.00 0.00 0.00 80204.75 26-OCT-05:02 49111.20 11-OCT-13:20 0.00 0.00 0.00
November 0.561211E+09 0.00 12.35 0.560898E+09 0.00 0.00 0.00 0.00 62248.49 27-NOV-06:03 62248.49 27-NOV-06:03 0.00 0.00 0.00
December 1701705.22 0.00 0.96 1701705.22 0.00 0.00 0.00 0.00 11028.29 01-DEC-06:02 11028.29 01-DEC-06:02 0.00 0.00 0.00
                               
Annual Sum or Average 0.238906E+12 0.00 1510.45 0.195370E+12 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 84197.20 0.00 0.69 84197.20 0.00 0.00 0.00 0.00 60.53   60.53   0.00 0.00 0.00
Maximum of Months 0.802959E+11 0.00 378.19 0.608901E+11 0.00 0.00 0.00 0.00 185702.80   112263.09   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: AIRLOOP DATACENTER BASEMENT COOLING COIL

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [J] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [J] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION {Maximum} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL RUNTIME FRACTION {MINIMUM} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE {Maximum} [W] COOLING COIL LATENT COOLING RATE {TIMESTAMP} COOLING COIL ELECTRICITY RATE {Maximum} [W] COOLING COIL ELECTRICITY RATE {TIMESTAMP} COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.635088E+10 0.423777E+10 740.00 0.635073E+10 158009.31 0.00 0.02 13-JAN-18:00 0.01 11-JAN-18:10 3716.70 13-JAN-18:00 3716.70 13-JAN-18:00 23.48 11-JAN-18:40 1959.07 13-JAN-18:00 0.00
February 0.101905E+11 0.517208E+10 672.00 0.101661E+11 24404242.36 0.00 0.03 22-FEB-18:00 0.01 01-FEB-05:11 5131.11 14-FEB-17:05 5131.11 14-FEB-17:05 117.65 01-FEB-11:00 2450.15 22-FEB-18:30 0.00
March 0.353730E+11 0.132212E+11 685.32 0.314121E+11 0.396094E+10 0.00 0.80 14-MAR-13:00 0.01 12-MAR-10:10 317408.35 14-MAR-13:00 288313.19 15-MAR-14:00 93410.48 14-MAR-10:50 98176.98 14-MAR-13:00 0.00
April 0.566671E+11 0.192647E+11 700.80 0.517223E+11 0.494474E+10 0.00 0.70 08-APR-14:00 0.01 09-APR-01:10 254030.20 08-APR-14:00 245333.36 08-APR-13:00 45156.72 08-APR-18:00 76945.49 08-APR-13:10 0.00
May 0.776230E+10 0.499537E+10 531.39 0.725883E+10 0.503473E+09 0.00 0.34 10-MAY-15:00 0.01 28-MAY-08:50 123932.84 10-MAY-15:00 104750.48 10-MAY-15:00 20107.41 14-MAY-13:52 40110.66 10-MAY-15:00 0.00
June 0.187737E+12 0.582620E+11 570.60 0.132033E+12 0.557043E+11 0.00 0.94 27-JUN-14:10 0.01 01-JUN-00:10 424052.81 27-JUN-14:10 222261.51 12-JUN-14:00 224870.45 27-JUN-15:00 122021.41 27-JUN-14:10 0.00
July 0.753583E+12 0.218422E+12 715.48 0.462198E+12 0.291385E+12 0.00 1.00 05-JUL-09:50 0.01 06-JUL-06:05 471962.62 20-JUL-22:12 344121.86 19-JUL-12:13 309333.13 20-JUL-22:00 141719.06 15-JUL-13:57 0.00
August 0.853980E+12 0.247080E+12 737.71 0.570323E+12 0.283657E+12 0.00 1.00 03-AUG-12:30 0.01 01-AUG-05:03 457474.72 14-AUG-00:55 400078.15 10-AUG-15:20 284345.17 25-AUG-19:00 141885.54 13-AUG-15:00 0.00
September 0.177885E+11 0.815941E+10 371.30 0.130695E+11 0.471899E+10 0.00 0.44 15-SEP-12:00 0.01 04-SEP-19:40 176371.84 15-SEP-12:00 126374.32 16-SEP-13:00 70886.79 15-SEP-12:00 52634.05 15-SEP-12:00 0.00
October 0.994863E+10 0.553191E+10 579.86 0.947695E+10 0.471680E+09 0.00 0.30 11-OCT-15:00 0.00 10-OCT-23:50 103151.78 11-OCT-15:00 95905.29 11-OCT-15:00 11099.89 22-OCT-12:53 32651.93 11-OCT-15:00 0.00
November 0.229845E+11 0.911021E+10 708.04 0.205032E+11 0.248127E+10 0.00 0.38 05-NOV-14:00 0.01 05-NOV-19:10 132905.11 05-NOV-14:00 109085.35 05-NOV-14:00 28254.89 05-NOV-15:00 38832.50 05-NOV-14:00 0.00
December 0.164990E+11 0.780505E+10 743.08 0.156680E+11 0.830970E+09 0.00 0.37 01-DEC-11:00 0.01 01-DEC-08:65 128272.42 01-DEC-11:00 85920.95 01-DEC-11:00 42351.46 01-DEC-11:00 34578.99 01-DEC-11:00 0.00
                                       
Annual Sum or Average 0.197887E+13 0.601261E+12 7755.59 0.133018E+13 0.648683E+12 0.00                         0.00
Minimum of Months 0.635088E+10 0.423777E+10 371.30 0.635073E+10 158009.31 0.00 0.02   0.00   3716.70   3716.70   23.48   1959.07   0.00
Maximum of Months 0.853980E+12 0.247080E+12 743.08 0.570323E+12 0.291385E+12 0.00 1.00   0.01   471962.62   400078.15   309333.13   141885.54   0.00



Table of Contents

Report: DXReportMonthly

For: AIRLOOP DATACENTER BOT COOLING COIL

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [J] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [J] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION {Maximum} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL RUNTIME FRACTION {MINIMUM} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE {Maximum} [W] COOLING COIL LATENT COOLING RATE {TIMESTAMP} COOLING COIL ELECTRICITY RATE {Maximum} [W] COOLING COIL ELECTRICITY RATE {TIMESTAMP} COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.296986E+10 0.831406E+09 744.00 0.296986E+10 -0.0 0.00 0.27 15-JAN-16:35 0.02 30-JAN-07:05 2119.87 15-JAN-16:35 2119.87 15-JAN-16:35 0.00 18-JAN-19:40 549.45 15-JAN-16:35 0.00
February 0.758374E+10 0.196145E+10 672.00 0.758374E+10 0.00 0.00 0.53 28-FEB-16:55 0.27 06-FEB-07:05 4405.92 28-FEB-16:55 4405.92 28-FEB-16:55 0.00 20-FEB-09:50 1091.78 28-FEB-16:55 0.00
March 0.148969E+11 0.357535E+10 744.00 0.148750E+11 21954336.76 0.00 0.81 25-MAR-17:55 0.55 01-MAR-07:10 7562.63 31-MAR-24:00 7562.63 31-MAR-24:00 281.26 16-MAR-15:50 2011.11 15-MAR-14:10 0.00
April 0.199022E+11 0.445211E+10 720.00 0.198994E+11 2734954.87 0.00 0.93 02-APR-17:57 0.29 30-APR-24:00 8801.88 02-APR-18:00 8801.88 02-APR-18:00 97.63 12-APR-16:10 2134.37 07-APR-14:00 0.00
May 0.572982E+10 0.145238E+10 744.00 0.569400E+10 35818947.87 0.00 0.45 31-MAY-24:00 0.18 12-MAY-06:10 4074.10 31-MAY-24:00 4074.10 31-MAY-24:00 223.90 17-MAY-15:20 940.40 31-MAY-24:00 0.00
June 0.110525E+11 0.286154E+10 720.00 0.108671E+11 0.185376E+09 0.00 0.65 30-JUN-23:10 0.41 10-JUN-06:40 5945.11 30-JUN-24:00 5945.11 30-JUN-24:00 475.05 27-JUN-14:00 1731.56 27-JUN-13:00 0.00
July 0.167493E+11 0.477235E+10 744.00 0.164402E+11 0.309098E+09 0.00 0.85 31-JUL-23:23 0.62 07-JUL-06:40 7871.50 31-JUL-23:43 7845.92 31-JUL-23:47 476.92 20-JUL-15:00 2496.94 21-JUL-14:00 0.00
August 0.216839E+11 0.588954E+10 744.00 0.214534E+11 0.230473E+09 0.00 1.00 14-AUG-16:00 0.29 31-AUG-24:00 9030.16 14-AUG-16:00 8972.34 04-AUG-18:40 471.64 15-AUG-14:10 3077.83 18-AUG-15:00 0.00
September 0.584012E+10 0.148502E+10 720.00 0.570450E+10 0.135619E+09 0.00 0.43 30-SEP-24:00 0.17 30-SEP-07:00 3774.50 30-SEP-24:00 3774.50 30-SEP-24:00 347.24 15-SEP-15:20 921.52 21-SEP-17:00 0.00
October 0.103654E+11 0.246607E+10 744.00 0.103344E+11 30969443.97 0.00 0.62 31-OCT-24:00 0.36 30-OCT-06:10 5717.36 31-OCT-24:00 5717.36 31-OCT-24:00 185.05 12-OCT-15:30 1331.58 11-OCT-17:00 0.00
November 0.145591E+11 0.339024E+10 720.00 0.145574E+11 1705602.09 0.00 0.70 26-NOV-14:00 0.57 21-NOV-07:10 6264.58 15-NOV-16:20 6264.58 15-NOV-16:20 133.76 16-NOV-16:20 1552.79 26-NOV-14:00 0.00
December 0.192257E+11 0.447960E+10 744.00 0.192253E+11 399441.90 0.00 0.88 04-DEC-16:20 0.72 11-DEC-07:05 7939.48 04-DEC-16:10 7939.48 04-DEC-16:10 78.39 01-DEC-13:40 1818.34 04-DEC-16:20 0.00
                                       
Annual Sum or Average 0.150559E+12 0.376171E+11 8760.00 0.149604E+12 0.954148E+09 0.00                         0.00
Minimum of Months 0.296986E+10 0.831406E+09 672.00 0.296986E+10 -0.0 0.00 0.27   0.02   2119.87   2119.87   0.00   549.45   0.00
Maximum of Months 0.216839E+11 0.588954E+10 744.00 0.214534E+11 0.309098E+09 0.00 1.00   0.72   9030.16   8972.34   476.92   3077.83   0.00



Table of Contents

Report: DXReportMonthly

For: AIRLOOP DATACENTER MID COOLING COIL

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [J] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [J] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION {Maximum} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL RUNTIME FRACTION {MINIMUM} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE {Maximum} [W] COOLING COIL LATENT COOLING RATE {TIMESTAMP} COOLING COIL ELECTRICITY RATE {Maximum} [W] COOLING COIL ELECTRICITY RATE {TIMESTAMP} COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.539046E+10 0.170479E+10 393.41 0.539046E+10 -0.0 0.00 0.21 12-JAN-16:50 0.00 01-JAN-00:03 15564.16 12-JAN-16:50 15564.16 12-JAN-16:50 0.00 19-JAN-20:20 4244.88 12-JAN-16:50 0.00
February 0.473833E+11 0.126728E+11 672.00 0.473833E+11 -0.0 0.00 0.49 28-FEB-16:55 0.10 06-FEB-07:05 38541.64 28-FEB-16:55 38541.64 28-FEB-16:55 0.00 21-FEB-05:13 9643.46 28-FEB-16:55 0.00
March 0.123668E+12 0.301477E+11 744.00 0.123450E+12 0.218090E+09 0.00 0.77 25-MAR-17:55 0.39 06-MAR-07:10 66598.92 31-MAR-23:40 66598.92 31-MAR-23:40 2764.67 16-MAR-15:50 18956.12 15-MAR-14:10 0.00
April 0.177122E+12 0.400223E+11 720.00 0.177093E+12 28845694.40 0.00 0.90 22-APR-18:12 0.21 30-APR-24:00 80622.42 24-APR-18:00 80622.42 24-APR-18:00 976.89 12-APR-16:10 20093.15 07-APR-14:00 0.00
May 0.483950E+11 0.124006E+11 744.00 0.480425E+11 0.352499E+09 0.00 0.44 31-MAY-24:00 0.11 01-MAY-06:05 38361.42 31-MAY-24:00 38361.42 31-MAY-24:00 2204.18 17-MAY-15:20 8873.28 31-MAY-24:00 0.00
June 0.102685E+12 0.267045E+11 720.00 0.100844E+12 0.184095E+10 0.00 0.65 30-JUN-23:23 0.36 14-JUN-06:05 57065.85 30-JUN-24:00 57065.85 30-JUN-24:00 4705.96 27-JUN-14:00 16508.16 27-JUN-13:00 0.00
July 0.158741E+12 0.453194E+11 744.00 0.155663E+12 0.307859E+10 0.00 0.85 31-JUL-23:15 0.59 06-JUL-06:40 75976.12 31-JUL-23:53 75703.64 31-JUL-23:57 4755.82 20-JUL-15:00 23692.65 19-JUL-15:00 0.00
August 0.204895E+12 0.557897E+11 744.00 0.202597E+12 0.229871E+10 0.00 0.99 04-AUG-18:40 0.22 31-AUG-24:00 85735.26 04-AUG-18:40 85735.26 04-AUG-18:40 4693.51 14-AUG-10:00 29202.32 18-AUG-15:00 0.00
September 0.499986E+11 0.128566E+11 720.00 0.486693E+11 0.132923E+10 0.00 0.38 30-SEP-24:00 0.11 30-SEP-07:00 31727.41 30-SEP-24:00 31727.41 30-SEP-24:00 3432.02 15-SEP-15:20 8819.49 21-SEP-17:00 0.00
October 0.849039E+11 0.204855E+11 744.00 0.845954E+11 0.308526E+09 0.00 0.56 31-OCT-23:40 0.25 30-OCT-06:10 49403.58 31-OCT-23:40 49403.58 31-OCT-23:40 1840.79 12-OCT-15:30 12506.25 11-OCT-17:00 0.00
November 0.119155E+12 0.282348E+11 720.00 0.119137E+12 18774838.14 0.00 0.66 15-NOV-16:20 0.44 24-NOV-07:10 57601.04 15-NOV-16:20 57601.04 15-NOV-16:20 1335.50 16-NOV-16:20 13419.10 16-NOV-13:00 0.00
December 0.153174E+12 0.365277E+11 744.00 0.153169E+12 4778383.17 0.00 0.82 04-DEC-16:20 0.54 11-DEC-07:05 70332.35 04-DEC-16:20 70332.35 04-DEC-16:20 834.87 01-DEC-13:30 16297.53 04-DEC-16:20 0.00
                                       
Annual Sum or Average 0.127551E+13 0.322867E+12 8409.41 0.126603E+13 0.947899E+10 0.00                         0.00
Minimum of Months 0.539046E+10 0.170479E+10 393.41 0.539046E+10 -0.0 0.00 0.21   0.00   15564.16   15564.16   0.00   4244.88   0.00
Maximum of Months 0.204895E+12 0.557897E+11 744.00 0.202597E+12 0.307859E+10 0.00 0.99   0.59   85735.26   85735.26   4755.82   29202.32   0.00



Table of Contents

Report: DXReportMonthly

For: AIRLOOP DATACENTER TOP COOLING COIL

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [J] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [J] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION {Maximum} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL RUNTIME FRACTION {MINIMUM} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE {Maximum} [W] COOLING COIL LATENT COOLING RATE {TIMESTAMP} COOLING COIL ELECTRICITY RATE {Maximum} [W] COOLING COIL ELECTRICITY RATE {TIMESTAMP} COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.194364E+09 61895420.68 149.26 0.194364E+09 -0.0 0.00 0.19 12-JAN-16:40 0.00 01-JAN-00:03 1395.34 12-JAN-16:40 1395.34 12-JAN-16:40 0.00 15-JAN-16:40 384.82 12-JAN-16:40 0.00
February 0.338111E+10 0.920289E+09 635.75 0.338111E+10 -0.0 0.00 0.48 28-FEB-16:55 0.00 05-FEB-00:05 3880.20 28-FEB-16:55 3880.20 28-FEB-16:55 0.00 03-FEB-15:30 971.67 28-FEB-16:55 0.00
March 0.109483E+11 0.270047E+10 744.00 0.109266E+11 21707855.83 0.00 0.72 25-MAR-17:42 0.24 06-MAR-04:01 6284.70 31-MAR-23:20 6284.70 31-MAR-23:20 276.67 16-MAR-15:50 1919.72 15-MAR-14:10 0.00
April 0.167270E+11 0.381180E+10 720.00 0.167241E+11 2822239.23 0.00 0.89 24-APR-18:00 0.14 30-APR-24:00 8077.92 24-APR-18:00 8077.92 24-APR-18:00 96.88 12-APR-16:10 2020.52 07-APR-14:00 0.00
May 0.437961E+10 0.113262E+10 743.87 0.434472E+10 34887983.83 0.00 0.43 31-MAY-23:30 0.00 01-MAY-06:35 3748.30 31-MAY-23:30 3748.30 31-MAY-23:30 219.66 17-MAY-15:20 870.17 31-MAY-23:30 0.00
June 0.101664E+11 0.265552E+10 720.00 0.998230E+10 0.184105E+09 0.00 0.64 30-JUN-23:13 0.31 14-JUN-06:05 5637.11 30-JUN-23:30 5637.11 30-JUN-23:30 473.73 27-JUN-14:00 1680.14 27-JUN-13:00 0.00
July 0.159082E+11 0.455423E+10 744.00 0.156005E+11 0.307684E+09 0.00 0.84 31-JUL-23:15 0.56 06-JUL-06:40 7591.69 31-JUL-23:53 7564.32 31-JUL-23:57 475.65 20-JUL-15:00 2410.26 19-JUL-15:00 0.00
August 0.204406E+11 0.558569E+10 744.00 0.202110E+11 0.229536E+09 0.00 0.99 04-AUG-18:30 0.19 31-AUG-24:00 8652.87 04-AUG-18:40 8652.87 04-AUG-18:40 469.39 14-AUG-10:00 2961.28 18-AUG-15:00 0.00
September 0.458363E+10 0.119140E+10 720.00 0.445144E+10 0.132193E+09 0.00 0.36 21-SEP-17:30 0.04 30-SEP-06:10 3014.05 04-SEP-17:45 3014.05 04-SEP-17:45 344.49 15-SEP-15:10 905.30 21-SEP-17:00 0.00
October 0.721174E+10 0.176185E+10 744.00 0.718120E+10 30543200.35 0.00 0.55 11-OCT-17:00 0.10 30-OCT-03:20 4742.07 11-OCT-17:00 4674.12 11-OCT-17:00 184.38 12-OCT-15:30 1265.76 11-OCT-17:00 0.00
November 0.103094E+11 0.247878E+10 720.00 0.103077E+11 1767133.96 0.00 0.64 15-NOV-16:20 0.29 24-NOV-04:23 5686.46 15-NOV-16:20 5686.46 15-NOV-16:20 130.27 16-NOV-16:20 1322.73 16-NOV-17:00 0.00
December 0.136157E+11 0.329330E+10 744.00 0.136153E+11 446735.68 0.00 0.79 04-DEC-16:20 0.40 26-DEC-03:50 6790.13 04-DEC-16:20 6790.13 04-DEC-16:20 79.03 01-DEC-13:40 1583.73 04-DEC-16:20 0.00
                                       
Annual Sum or Average 0.117866E+12 0.301478E+11 8128.89 0.116920E+12 0.945693E+09 0.00                         0.00
Minimum of Months 0.194364E+09 61895420.68 149.26 0.194364E+09 -0.0 0.00 0.19   0.00   1395.34   1395.34   0.00   384.82   0.00
Maximum of Months 0.204406E+11 0.558569E+10 744.00 0.202110E+11 0.307684E+09 0.00 0.99   0.56   8652.87   8652.87   475.65   2961.28   0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 138.01 0.00 138.01 0.01 953.32 0.00 0.00 0.00
February 210.28 0.00 210.28 3.54 896.08 0.00 0.00 0.00
March 255.01 0.00 255.01 59.51 664.66 0.00 0.00 0.00
April 324.93 1.30 323.64 137.74 477.90 0.00 0.00 0.00
May 377.56 16.01 361.55 267.28 287.94 0.00 0.00 0.00
June 454.12 38.66 415.47 464.14 182.36 0.00 0.00 0.00
July 421.26 27.19 394.07 504.89 125.30 0.00 0.00 0.00
August 364.51 5.55 358.96 409.35 168.37 0.00 0.00 0.00
September 277.40 0.06 277.34 232.52 283.35 0.00 0.00 0.00
October 207.37 0.00 207.37 76.32 475.17 0.00 0.00 0.00
November 139.34 0.00 139.34 15.89 639.34 0.00 0.00 0.00
December 129.18 0.00 129.18 0.44 936.71 0.00 0.00 0.00
                 
Annual Sum or Average 275.18 7.43 267.75 182.08 505.57 0.00 0.00 0.00
Minimum of Months 129.18 0.00 129.18 0.01 125.30 0.00 0.00 0.00
Maximum of Months 454.12 38.66 415.47 504.89 953.32 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 138.01 0.00 138.01 0.01 953.32 0.00 0.00 0.00
February 210.28 0.00 210.28 3.54 896.08 0.00 0.00 0.00
March 255.01 0.00 255.01 59.51 664.66 0.00 0.00 0.00
April 324.93 1.30 323.64 137.74 477.90 0.00 0.00 0.00
May 377.56 16.01 361.55 267.28 287.94 0.00 0.00 0.00
June 454.12 38.66 415.47 464.14 182.36 0.00 0.00 0.00
July 421.26 27.19 394.07 504.89 125.30 0.00 0.00 0.00
August 364.51 5.55 358.96 409.35 168.37 0.00 0.00 0.00
September 277.40 0.06 277.34 232.52 283.35 0.00 0.00 0.00
October 207.37 0.00 207.37 76.32 475.17 0.00 0.00 0.00
November 139.34 0.00 139.34 15.89 639.34 0.00 0.00 0.00
December 129.18 0.00 129.18 0.44 936.71 0.00 0.00 0.00
                 
Annual Sum or Average 275.18 7.43 267.75 182.08 505.57 0.00 0.00 0.00
Minimum of Months 129.18 0.00 129.18 0.01 125.30 0.00 0.00 0.00
Maximum of Months 454.12 38.66 415.47 504.89 953.32 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 138.01 0.00 138.01 0.01 953.32 0.00 0.00 0.00
February 210.28 0.00 210.28 3.54 896.08 0.00 0.00 0.00
March 255.01 0.00 255.01 59.51 664.66 0.00 0.00 0.00
April 324.93 1.30 323.64 137.74 477.90 0.00 0.00 0.00
May 377.56 16.01 361.55 267.28 287.94 0.00 0.00 0.00
June 454.12 38.66 415.47 464.14 182.36 0.00 0.00 0.00
July 421.26 27.19 394.07 504.89 125.30 0.00 0.00 0.00
August 364.51 5.55 358.96 409.35 168.37 0.00 0.00 0.00
September 277.40 0.06 277.34 232.52 283.35 0.00 0.00 0.00
October 207.37 0.00 207.37 76.32 475.17 0.00 0.00 0.00
November 139.34 0.00 139.34 15.89 639.34 0.00 0.00 0.00
December 129.18 0.00 129.18 0.44 936.71 0.00 0.00 0.00
                 
Annual Sum or Average 275.18 7.43 267.75 182.08 505.57 0.00 0.00 0.00
Minimum of Months 129.18 0.00 129.18 0.01 125.30 0.00 0.00 0.00
Maximum of Months 454.12 38.66 415.47 504.89 953.32 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 138.01 0.00 138.01 0.01 953.32 0.00 0.00 0.00
February 210.28 0.00 210.28 3.54 896.08 0.00 0.00 0.00
March 255.01 0.00 255.01 59.51 664.66 0.00 0.00 0.00
April 324.93 1.30 323.64 137.74 477.90 0.00 0.00 0.00
May 377.56 16.01 361.55 267.28 287.94 0.00 0.00 0.00
June 454.12 38.66 415.47 464.14 182.36 0.00 0.00 0.00
July 421.26 27.19 394.07 504.89 125.30 0.00 0.00 0.00
August 364.51 5.55 358.96 409.35 168.37 0.00 0.00 0.00
September 277.40 0.06 277.34 232.52 283.35 0.00 0.00 0.00
October 207.37 0.00 207.37 76.32 475.17 0.00 0.00 0.00
November 139.34 0.00 139.34 15.89 639.34 0.00 0.00 0.00
December 129.18 0.00 129.18 0.44 936.71 0.00 0.00 0.00
                 
Annual Sum or Average 275.18 7.43 267.75 182.08 505.57 0.00 0.00 0.00
Minimum of Months 129.18 0.00 129.18 0.01 125.30 0.00 0.00 0.00
Maximum of Months 454.12 38.66 415.47 504.89 953.32 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 138.01 0.00 138.01 0.01 953.29 0.00 0.00 0.00
February 210.27 0.00 210.27 3.54 896.04 0.00 0.00 0.00
March 255.00 0.00 255.00 59.51 664.63 0.00 0.00 0.00
April 324.92 1.30 323.62 137.74 477.88 0.00 0.00 0.00
May 377.54 16.01 361.53 267.27 287.93 0.00 0.00 0.00
June 454.10 38.66 415.45 464.12 182.35 0.00 0.00 0.00
July 421.24 27.19 394.05 504.87 125.29 0.00 0.00 0.00
August 364.49 5.54 358.95 409.33 168.37 0.00 0.00 0.00
September 277.39 0.06 277.33 232.51 283.34 0.00 0.00 0.00
October 207.36 0.00 207.36 76.32 475.15 0.00 0.00 0.00
November 139.34 0.00 139.34 15.89 639.31 0.00 0.00 0.00
December 129.17 0.00 129.17 0.44 936.67 0.00 0.00 0.00
                 
Annual Sum or Average 275.17 7.43 267.74 182.07 505.55 0.00 0.00 0.00
Minimum of Months 129.17 0.00 129.17 0.01 125.29 0.00 0.00 0.00
Maximum of Months 454.10 38.66 415.45 504.87 953.29 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 280.62 90.49 190.13 93.11 956.51 0.00 0.00 0.00
February 411.76 123.56 288.20 166.76 900.04 0.00 0.00 0.00
March 590.86 247.45 343.41 421.91 659.99 0.00 0.00 0.00
April 782.05 345.55 436.50 686.41 479.22 0.00 0.00 0.00
May 876.17 387.58 488.59 911.80 316.83 0.00 0.00 0.00
June 978.54 432.46 546.07 1154.01 200.05 0.00 0.00 0.00
July 939.65 413.72 525.94 1199.48 131.35 0.00 0.00 0.00
August 848.61 356.20 492.41 1057.95 172.01 0.00 0.00 0.00
September 706.19 313.24 392.95 785.37 293.29 0.00 0.00 0.00
October 479.21 198.21 280.99 394.42 480.33 0.00 0.00 0.00
November 271.82 87.20 184.62 144.42 647.88 0.00 0.00 0.00
December 218.83 45.21 173.61 45.41 952.12 0.00 0.00 0.00
                 
Annual Sum or Average 616.27 254.02 362.25 590.74 513.86 0.00 0.00 0.00
Minimum of Months 218.83 45.21 173.61 45.41 131.35 0.00 0.00 0.00
Maximum of Months 978.54 432.46 546.07 1199.48 956.51 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 280.62 90.49 190.13 93.11 956.51 0.00 0.00 0.00
February 411.76 123.56 288.20 166.76 900.04 0.00 0.00 0.00
March 590.86 247.45 343.41 421.91 659.99 0.00 0.00 0.00
April 782.05 345.55 436.50 686.41 479.22 0.00 0.00 0.00
May 876.17 387.58 488.59 911.80 316.83 0.00 0.00 0.00
June 978.54 432.46 546.07 1154.01 200.05 0.00 0.00 0.00
July 939.65 413.72 525.94 1199.48 131.35 0.00 0.00 0.00
August 848.61 356.20 492.41 1057.95 172.01 0.00 0.00 0.00
September 706.19 313.24 392.95 785.37 293.29 0.00 0.00 0.00
October 479.21 198.21 280.99 394.42 480.33 0.00 0.00 0.00
November 271.82 87.20 184.62 144.42 647.88 0.00 0.00 0.00
December 218.83 45.21 173.61 45.41 952.12 0.00 0.00 0.00
                 
Annual Sum or Average 616.27 254.02 362.25 590.74 513.86 0.00 0.00 0.00
Minimum of Months 218.83 45.21 173.61 45.41 131.35 0.00 0.00 0.00
Maximum of Months 978.54 432.46 546.07 1199.48 956.51 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 280.62 90.49 190.13 93.11 956.50 0.00 0.00 0.00
February 411.75 123.56 288.20 166.76 900.02 0.00 0.00 0.00
March 590.85 247.45 343.41 421.90 659.97 0.00 0.00 0.00
April 782.03 345.54 436.49 686.40 479.21 0.00 0.00 0.00
May 876.16 387.57 488.58 911.79 316.83 0.00 0.00 0.00
June 978.52 432.46 546.06 1153.98 200.05 0.00 0.00 0.00
July 939.63 413.71 525.93 1199.45 131.35 0.00 0.00 0.00
August 848.59 356.19 492.40 1057.93 172.00 0.00 0.00 0.00
September 706.18 313.23 392.94 785.35 293.28 0.00 0.00 0.00
October 479.20 198.21 280.99 394.42 480.32 0.00 0.00 0.00
November 271.81 87.19 184.62 144.42 647.87 0.00 0.00 0.00
December 218.82 45.21 173.61 45.41 952.10 0.00 0.00 0.00
                 
Annual Sum or Average 616.26 254.02 362.24 590.73 513.85 0.00 0.00 0.00
Minimum of Months 218.82 45.21 173.61 45.41 131.35 0.00 0.00 0.00
Maximum of Months 978.52 432.46 546.06 1199.45 956.50 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 593.46 346.42 247.04 447.25 787.46 0.00 0.00 0.00
February 677.58 326.72 350.86 499.24 770.88 0.00 0.00 0.00
March 827.03 464.70 362.33 764.36 586.01 0.00 0.00 0.00
April 684.91 273.69 411.22 660.09 469.05 0.00 0.00 0.00
May 599.36 174.08 425.28 637.53 310.36 0.00 0.00 0.00
June 582.38 123.41 458.97 698.20 199.53 0.00 0.00 0.00
July 594.52 144.25 450.27 794.15 135.49 0.00 0.00 0.00
August 667.44 216.40 451.04 876.56 176.48 0.00 0.00 0.00
September 776.04 377.99 398.05 938.43 283.39 0.00 0.00 0.00
October 742.55 424.16 318.39 765.32 435.19 0.00 0.00 0.00
November 531.80 300.22 231.58 471.67 564.49 0.00 0.00 0.00
December 496.25 256.83 239.42 349.35 790.11 0.00 0.00 0.00
                 
Annual Sum or Average 647.58 285.59 361.99 659.45 457.35 0.00 0.00 0.00
Minimum of Months 496.25 123.41 231.58 349.35 135.49 0.00 0.00 0.00
Maximum of Months 827.03 464.70 458.97 938.43 790.11 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 593.46 346.42 247.04 447.25 787.46 0.00 0.00 0.00
February 677.58 326.72 350.86 499.24 770.88 0.00 0.00 0.00
March 827.03 464.70 362.33 764.36 586.01 0.00 0.00 0.00
April 684.91 273.69 411.22 660.09 469.05 0.00 0.00 0.00
May 599.36 174.08 425.28 637.53 310.36 0.00 0.00 0.00
June 582.38 123.41 458.97 698.20 199.53 0.00 0.00 0.00
July 594.52 144.25 450.27 794.15 135.49 0.00 0.00 0.00
August 667.44 216.40 451.04 876.56 176.48 0.00 0.00 0.00
September 776.04 377.99 398.05 938.43 283.39 0.00 0.00 0.00
October 742.55 424.16 318.39 765.32 435.19 0.00 0.00 0.00
November 531.80 300.22 231.58 471.67 564.49 0.00 0.00 0.00
December 496.25 256.83 239.42 349.35 790.11 0.00 0.00 0.00
                 
Annual Sum or Average 647.57 285.59 361.99 659.45 457.35 0.00 0.00 0.00
Minimum of Months 496.25 123.41 231.58 349.35 135.49 0.00 0.00 0.00
Maximum of Months 827.03 464.70 458.97 938.43 790.11 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 593.46 346.42 247.04 447.25 787.46 0.00 0.00 0.00
February 677.58 326.72 350.86 499.24 770.88 0.00 0.00 0.00
March 827.03 464.70 362.33 764.36 586.01 0.00 0.00 0.00
April 684.91 273.69 411.22 660.09 469.05 0.00 0.00 0.00
May 599.36 174.08 425.28 637.53 310.36 0.00 0.00 0.00
June 582.38 123.41 458.97 698.20 199.53 0.00 0.00 0.00
July 594.52 144.25 450.27 794.15 135.49 0.00 0.00 0.00
August 667.44 216.40 451.04 876.56 176.48 0.00 0.00 0.00
September 776.04 377.99 398.05 938.43 283.39 0.00 0.00 0.00
October 742.55 424.16 318.39 765.32 435.19 0.00 0.00 0.00
November 531.80 300.22 231.58 471.67 564.49 0.00 0.00 0.00
December 496.25 256.83 239.42 349.35 790.11 0.00 0.00 0.00
                 
Annual Sum or Average 647.58 285.59 361.99 659.45 457.35 0.00 0.00 0.00
Minimum of Months 496.25 123.41 231.58 349.35 135.49 0.00 0.00 0.00
Maximum of Months 827.03 464.70 458.97 938.43 790.11 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 593.46 346.42 247.04 447.25 787.46 0.00 0.00 0.00
February 677.58 326.72 350.86 499.24 770.88 0.00 0.00 0.00
March 827.03 464.70 362.33 764.36 586.01 0.00 0.00 0.00
April 684.91 273.69 411.22 660.09 469.05 0.00 0.00 0.00
May 599.36 174.08 425.28 637.53 310.36 0.00 0.00 0.00
June 582.38 123.41 458.97 698.20 199.53 0.00 0.00 0.00
July 594.52 144.25 450.27 794.15 135.49 0.00 0.00 0.00
August 667.44 216.40 451.04 876.56 176.48 0.00 0.00 0.00
September 776.04 377.99 398.05 938.43 283.39 0.00 0.00 0.00
October 742.55 424.16 318.39 765.32 435.19 0.00 0.00 0.00
November 531.80 300.22 231.58 471.67 564.49 0.00 0.00 0.00
December 496.25 256.83 239.42 349.35 790.11 0.00 0.00 0.00
                 
Annual Sum or Average 647.57 285.59 361.99 659.45 457.35 0.00 0.00 0.00
Minimum of Months 496.25 123.41 231.58 349.35 135.49 0.00 0.00 0.00
Maximum of Months 827.03 464.70 458.97 938.43 790.11 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 593.43 346.40 247.03 447.23 787.43 0.00 0.00 0.00
February 677.55 326.71 350.84 499.22 770.85 0.00 0.00 0.00
March 827.00 464.68 362.31 764.33 585.98 0.00 0.00 0.00
April 684.88 273.68 411.20 660.07 469.03 0.00 0.00 0.00
May 599.33 174.07 425.26 637.50 310.35 0.00 0.00 0.00
June 582.36 123.40 458.95 698.17 199.52 0.00 0.00 0.00
July 594.49 144.24 450.25 794.12 135.48 0.00 0.00 0.00
August 667.42 216.39 451.02 876.53 176.48 0.00 0.00 0.00
September 776.01 377.97 398.03 938.39 283.38 0.00 0.00 0.00
October 742.52 424.14 318.38 765.29 435.17 0.00 0.00 0.00
November 531.78 300.21 231.57 471.65 564.46 0.00 0.00 0.00
December 496.23 256.82 239.41 349.34 790.08 0.00 0.00 0.00
                 
Annual Sum or Average 647.55 285.58 361.97 659.43 457.33 0.00 0.00 0.00
Minimum of Months 496.23 123.40 231.57 349.34 135.48 0.00 0.00 0.00
Maximum of Months 827.00 464.68 458.95 938.39 790.08 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 240.77 56.52 184.25 54.76 1033.44 0.00 0.00 0.00
February 390.22 100.29 289.93 135.10 990.50 0.00 0.00 0.00
March 611.60 261.87 349.73 430.15 749.95 0.00 0.00 0.00
April 748.82 307.05 441.78 629.59 580.41 0.00 0.00 0.00
May 883.36 399.22 484.14 915.85 364.90 0.00 0.00 0.00
June 1065.80 501.31 564.49 1256.49 250.41 0.00 0.00 0.00
July 952.86 417.77 535.10 1197.36 181.29 0.00 0.00 0.00
August 861.81 366.45 495.36 1058.56 234.10 0.00 0.00 0.00
September 676.79 292.28 384.51 744.20 339.01 0.00 0.00 0.00
October 438.73 154.54 284.18 338.16 552.97 0.00 0.00 0.00
November 259.99 74.92 185.07 122.81 749.36 0.00 0.00 0.00
December 225.39 49.11 176.28 47.34 1081.56 0.00 0.00 0.00
                 
Annual Sum or Average 614.02 249.16 364.86 579.95 590.29 0.00 0.00 0.00
Minimum of Months 225.39 49.11 176.28 47.34 181.29 0.00 0.00 0.00
Maximum of Months 1065.80 501.31 564.49 1256.49 1081.56 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 240.77 56.52 184.25 54.76 1033.44 0.00 0.00 0.00
February 390.22 100.29 289.93 135.10 990.50 0.00 0.00 0.00
March 611.60 261.87 349.73 430.15 749.95 0.00 0.00 0.00
April 748.82 307.05 441.78 629.59 580.41 0.00 0.00 0.00
May 883.36 399.22 484.14 915.85 364.90 0.00 0.00 0.00
June 1065.80 501.31 564.49 1256.49 250.41 0.00 0.00 0.00
July 952.86 417.77 535.10 1197.36 181.29 0.00 0.00 0.00
August 861.81 366.45 495.36 1058.56 234.10 0.00 0.00 0.00
September 676.79 292.28 384.51 744.20 339.01 0.00 0.00 0.00
October 438.73 154.54 284.18 338.16 552.97 0.00 0.00 0.00
November 259.99 74.92 185.07 122.81 749.36 0.00 0.00 0.00
December 225.39 49.11 176.28 47.34 1081.56 0.00 0.00 0.00
                 
Annual Sum or Average 614.02 249.16 364.86 579.95 590.29 0.00 0.00 0.00
Minimum of Months 225.39 49.11 176.28 47.34 181.29 0.00 0.00 0.00
Maximum of Months 1065.80 501.31 564.49 1256.49 1081.56 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 240.77 56.52 184.24 54.76 1033.42 0.00 0.00 0.00
February 390.21 100.29 289.93 135.10 990.48 0.00 0.00 0.00
March 611.59 261.87 349.72 430.15 749.94 0.00 0.00 0.00
April 748.81 307.04 441.77 629.58 580.40 0.00 0.00 0.00
May 883.34 399.21 484.13 915.83 364.89 0.00 0.00 0.00
June 1065.78 501.30 564.48 1256.46 250.41 0.00 0.00 0.00
July 952.85 417.76 535.09 1197.34 181.29 0.00 0.00 0.00
August 861.79 366.44 495.35 1058.54 234.10 0.00 0.00 0.00
September 676.78 292.27 384.51 744.18 339.01 0.00 0.00 0.00
October 438.72 154.54 284.18 338.15 552.96 0.00 0.00 0.00
November 259.99 74.92 185.07 122.81 749.35 0.00 0.00 0.00
December 225.38 49.11 176.28 47.34 1081.54 0.00 0.00 0.00
                 
Annual Sum or Average 614.01 249.16 364.85 579.94 590.27 0.00 0.00 0.00
Minimum of Months 225.38 49.11 176.28 47.34 181.29 0.00 0.00 0.00
Maximum of Months 1065.78 501.30 564.48 1256.46 1081.54 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 690.06 0.00 690.06 5.23 4338.53 0.00 0.00 0.00
February 1051.38 0.00 1051.38 43.24 4067.93 0.00 0.00 0.00
March 1275.03 0.00 1275.03 354.79 2963.08 0.00 0.00 0.00
April 1624.65 6.48 1618.17 791.12 2094.01 0.00 0.00 0.00
May 1887.77 80.05 1807.71 1380.28 1340.20 0.00 0.00 0.00
June 2270.59 193.28 2077.30 2338.29 868.04 0.00 0.00 0.00
July 2106.27 135.96 1970.31 2538.14 607.45 0.00 0.00 0.00
August 1822.51 27.73 1794.78 2069.80 805.65 0.00 0.00 0.00
September 1386.97 0.29 1386.68 1192.88 1308.84 0.00 0.00 0.00
October 1036.82 0.00 1036.82 453.64 2082.74 0.00 0.00 0.00
November 696.72 0.00 696.72 123.82 2727.67 0.00 0.00 0.00
December 645.87 0.00 645.87 6.68 4137.55 0.00 0.00 0.00
                 
Annual Sum or Average 1375.89 37.14 1338.75 947.01 2269.56 0.00 0.00 0.00
Minimum of Months 645.87 0.00 645.87 5.23 607.45 0.00 0.00 0.00
Maximum of Months 2270.59 193.28 2077.30 2538.14 4338.53 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 841.86 271.46 570.40 297.99 2628.41 0.00 0.00 0.00
February 1235.27 370.67 864.59 533.62 2493.30 0.00 0.00 0.00
March 1772.57 742.34 1030.23 1296.18 1819.10 0.00 0.00 0.00
April 2346.11 1036.64 1309.47 2086.45 1321.14 0.00 0.00 0.00
May 2628.49 1162.72 1465.77 2731.13 899.89 0.00 0.00 0.00
June 2935.58 1297.38 1638.20 3440.84 583.91 0.00 0.00 0.00
July 2818.93 1241.13 1577.79 3569.00 406.35 0.00 0.00 0.00
August 2545.80 1068.59 1477.21 3148.70 530.71 0.00 0.00 0.00
September 2118.55 939.71 1178.84 2352.77 829.86 0.00 0.00 0.00
October 1437.61 594.63 842.98 1215.03 1305.91 0.00 0.00 0.00
November 815.44 261.58 553.85 467.21 1733.10 0.00 0.00 0.00
December 656.47 135.64 520.83 152.53 2594.99 0.00 0.00 0.00
                 
Annual Sum or Average 1848.80 762.06 1086.74 1781.06 1423.56 0.00 0.00 0.00
Minimum of Months 656.47 135.64 520.83 152.53 406.35 0.00 0.00 0.00
Maximum of Months 2935.58 1297.38 1638.20 3569.00 2628.41 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 2967.25 1732.07 1235.18 2249.83 3740.56 0.00 0.00 0.00
February 3387.85 1633.59 1754.26 2513.11 3676.03 0.00 0.00 0.00
March 4135.10 2323.48 1811.61 3816.06 2786.26 0.00 0.00 0.00
April 3424.51 1368.44 2056.07 3313.53 2200.33 0.00 0.00 0.00
May 2996.75 870.38 2126.37 3172.83 1493.22 0.00 0.00 0.00
June 2911.88 617.04 2294.84 3476.53 959.97 0.00 0.00 0.00
July 2972.55 721.24 2251.31 3952.89 668.44 0.00 0.00 0.00
August 3337.18 1082.00 2255.18 4364.56 869.58 0.00 0.00 0.00
September 3880.15 1889.92 1990.23 4662.37 1374.07 0.00 0.00 0.00
October 3712.73 2120.78 1591.95 3815.41 2066.90 0.00 0.00 0.00
November 2658.98 1501.08 1157.90 2374.37 2634.04 0.00 0.00 0.00
December 2481.21 1284.14 1197.07 1773.51 3688.01 0.00 0.00 0.00
                 
Annual Sum or Average 3237.84 1427.92 1809.91 3294.98 2171.74 0.00 0.00 0.00
Minimum of Months 2481.21 617.04 1157.90 1773.51 668.44 0.00 0.00 0.00
Maximum of Months 4135.10 2323.48 2294.84 4662.37 3740.56 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 722.30 169.57 552.73 178.20 2785.34 0.00 0.00 0.00
February 1170.65 300.87 869.79 446.13 2630.34 0.00 0.00 0.00
March 1834.79 785.61 1049.18 1364.42 1921.51 0.00 0.00 0.00
April 2246.45 921.14 1325.32 1991.31 1440.91 0.00 0.00 0.00
May 2650.05 1197.65 1452.40 2775.96 999.59 0.00 0.00 0.00
June 3197.36 1503.91 1693.46 3787.90 679.34 0.00 0.00 0.00
July 2858.56 1253.29 1605.27 3623.69 487.26 0.00 0.00 0.00
August 2585.40 1099.34 1486.06 3223.01 608.63 0.00 0.00 0.00
September 2030.34 876.82 1153.53 2260.98 911.53 0.00 0.00 0.00
October 1316.17 463.63 852.54 1087.77 1395.90 0.00 0.00 0.00
November 779.96 224.76 555.21 424.50 1816.45 0.00 0.00 0.00
December 676.16 147.33 528.83 168.87 2698.10 0.00 0.00 0.00
                 
Annual Sum or Average 1842.05 747.48 1094.57 1784.96 1525.71 0.00 0.00 0.00
Minimum of Months 676.16 147.33 528.83 168.87 487.26 0.00 0.00 0.00
Maximum of Months 3197.36 1503.91 1693.46 3787.90 2785.34 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 690.06 0.00 690.06 9.80 4212.09 0.00 0.00 0.00
February 1051.38 0.00 1051.38 53.96 3941.87 0.00 0.00 0.00
March 1275.03 0.00 1275.03 379.37 2807.82 0.00 0.00 0.00
April 1624.65 6.48 1618.17 836.20 1959.00 0.00 0.00 0.00
May 1887.77 80.05 1807.71 1408.12 1274.26 0.00 0.00 0.00
June 2270.59 193.28 2077.30 2330.37 851.83 0.00 0.00 0.00
July 2106.27 135.96 1970.31 2515.49 607.44 0.00 0.00 0.00
August 1822.51 27.73 1794.78 2058.95 793.09 0.00 0.00 0.00
September 1386.97 0.29 1386.68 1211.07 1238.33 0.00 0.00 0.00
October 1036.82 0.00 1036.82 504.23 1895.40 0.00 0.00 0.00
November 696.72 0.00 696.72 152.89 2500.75 0.00 0.00 0.00
December 645.87 0.00 645.87 10.11 3976.89 0.00 0.00 0.00
                 
Annual Sum or Average 1375.89 37.14 1338.75 961.36 2162.87 0.00 0.00 0.00
Minimum of Months 645.87 0.00 645.87 9.80 607.44 0.00 0.00 0.00
Maximum of Months 2270.59 193.28 2077.30 2515.49 4212.09 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 841.86 271.46 570.40 307.06 2551.39 0.00 0.00 0.00
February 1235.27 370.67 864.59 548.64 2420.07 0.00 0.00 0.00
March 1772.57 742.34 1030.23 1322.27 1723.35 0.00 0.00 0.00
April 2346.11 1036.64 1309.47 2113.48 1248.22 0.00 0.00 0.00
May 2628.49 1162.72 1465.77 2737.28 865.77 0.00 0.00 0.00
June 2935.58 1297.38 1638.20 3428.88 576.77 0.00 0.00 0.00
July 2818.93 1241.13 1577.79 3550.80 408.50 0.00 0.00 0.00
August 2545.80 1068.59 1477.21 3136.73 525.80 0.00 0.00 0.00
September 2118.55 939.71 1178.84 2358.78 795.64 0.00 0.00 0.00
October 1437.61 594.63 842.98 1251.42 1200.96 0.00 0.00 0.00
November 815.44 261.58 553.85 494.66 1595.81 0.00 0.00 0.00
December 656.47 135.64 520.83 160.03 2497.06 0.00 0.00 0.00
                 
Annual Sum or Average 1848.80 762.06 1086.74 1790.87 1362.23 0.00 0.00 0.00
Minimum of Months 656.47 135.64 520.83 160.03 408.50 0.00 0.00 0.00
Maximum of Months 2935.58 1297.38 1638.20 3550.80 2551.39 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 2967.25 1732.07 1235.18 2276.41 3605.06 0.00 0.00 0.00
February 3387.85 1633.59 1754.26 2540.66 3549.82 0.00 0.00 0.00
March 4135.10 2323.48 1811.61 3858.86 2623.39 0.00 0.00 0.00
April 3424.51 1368.44 2056.07 3349.90 2069.58 0.00 0.00 0.00
May 2996.75 870.38 2126.37 3184.66 1424.62 0.00 0.00 0.00
June 2911.88 617.04 2294.84 3462.73 938.65 0.00 0.00 0.00
July 2972.55 721.24 2251.31 3928.21 665.87 0.00 0.00 0.00
August 3337.18 1082.00 2255.18 4347.70 855.45 0.00 0.00 0.00
September 3880.15 1889.92 1990.23 4668.27 1311.46 0.00 0.00 0.00
October 3712.73 2120.78 1591.95 3866.87 1899.01 0.00 0.00 0.00
November 2658.98 1501.08 1157.90 2425.07 2418.82 0.00 0.00 0.00
December 2481.21 1284.14 1197.07 1805.05 3527.36 0.00 0.00 0.00
                 
Annual Sum or Average 3237.84 1427.92 1809.91 3314.02 2066.23 0.00 0.00 0.00
Minimum of Months 2481.21 617.04 1157.90 1805.05 665.87 0.00 0.00 0.00
Maximum of Months 4135.10 2323.48 2294.84 4668.27 3605.06 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 722.30 169.57 552.73 183.59 2704.03 0.00 0.00 0.00
February 1170.65 300.87 869.79 452.78 2558.97 0.00 0.00 0.00
March 1834.79 785.61 1049.18 1378.70 1827.41 0.00 0.00 0.00
April 2246.45 921.14 1325.32 2008.89 1364.33 0.00 0.00 0.00
May 2650.05 1197.65 1452.40 2781.39 959.00 0.00 0.00 0.00
June 3197.36 1503.91 1693.46 3774.62 666.06 0.00 0.00 0.00
July 2858.56 1253.29 1605.27 3605.83 484.27 0.00 0.00 0.00
August 2585.40 1099.34 1486.06 3212.15 599.30 0.00 0.00 0.00
September 2030.34 876.82 1153.53 2266.96 872.71 0.00 0.00 0.00
October 1316.17 463.63 852.54 1111.56 1297.25 0.00 0.00 0.00
November 779.96 224.76 555.21 441.96 1693.81 0.00 0.00 0.00
December 676.16 147.33 528.83 174.74 2605.16 0.00 0.00 0.00
                 
Annual Sum or Average 1842.05 747.48 1094.57 1789.97 1463.91 0.00 0.00 0.00
Minimum of Months 676.16 147.33 528.83 174.74 484.27 0.00 0.00 0.00
Maximum of Months 3197.36 1503.91 1693.46 3774.62 2704.03 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.369653E+09 0.00 0.369653E+09 15304.68 0.255338E+10
February 0.508708E+09 0.00 0.508708E+09 8557778.71 0.216780E+10
March 0.683018E+09 0.00 0.683018E+09 0.159396E+09 0.178021E+10
April 0.842230E+09 3360833.16 0.838870E+09 0.357029E+09 0.123873E+10
May 0.101125E+10 42882803.87 0.968368E+09 0.715879E+09 0.771212E+09
June 0.117709E+10 0.100200E+09 0.107689E+10 0.120305E+10 0.472680E+09
July 0.112830E+10 72834337.51 0.105547E+10 0.135229E+10 0.335599E+09
August 0.976293E+09 14852187.10 0.961441E+09 0.109641E+10 0.450974E+09
September 0.719013E+09 149379.83 0.718864E+09 0.602680E+09 0.734452E+09
October 0.555410E+09 0.00 0.555410E+09 0.204413E+09 0.127270E+10
November 0.361182E+09 0.00 0.361182E+09 41194193.24 0.165716E+10
December 0.345984E+09 0.00 0.345984E+09 1191398.91 0.250889E+10
           
Annual Sum or Average 0.867813E+10 0.234279E+09 0.844385E+10 0.574210E+10 0.159438E+11
Minimum of Months 0.345984E+09 0.00 0.345984E+09 15304.68 0.335599E+09
Maximum of Months 0.117709E+10 0.100200E+09 0.107689E+10 0.135229E+10 0.255338E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.369653E+09 0.00 0.369653E+09 15303.70 0.255338E+10
February 0.508708E+09 0.00 0.508708E+09 8557695.72 0.216780E+10
March 0.683017E+09 0.00 0.683017E+09 0.159395E+09 0.178021E+10
April 0.842230E+09 3360829.13 0.838869E+09 0.357029E+09 0.123873E+10
May 0.101125E+10 42882752.42 0.968368E+09 0.715878E+09 0.771212E+09
June 0.117709E+10 0.100199E+09 0.107689E+10 0.120305E+10 0.472680E+09
July 0.112830E+10 72834250.12 0.105547E+10 0.135229E+10 0.335598E+09
August 0.976293E+09 14852169.28 0.961441E+09 0.109641E+10 0.450974E+09
September 0.719013E+09 149379.65 0.718863E+09 0.602679E+09 0.734452E+09
October 0.555409E+09 0.00 0.555409E+09 0.204413E+09 0.127270E+10
November 0.361182E+09 0.00 0.361182E+09 41194082.54 0.165716E+10
December 0.345984E+09 0.00 0.345984E+09 1191389.89 0.250889E+10
           
Annual Sum or Average 0.867812E+10 0.234279E+09 0.844384E+10 0.574209E+10 0.159438E+11
Minimum of Months 0.345984E+09 0.00 0.345984E+09 15303.70 0.335598E+09
Maximum of Months 0.117709E+10 0.100199E+09 0.107689E+10 0.135229E+10 0.255338E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.369653E+09 0.00 0.369653E+09 15304.68 0.255338E+10
February 0.508708E+09 0.00 0.508708E+09 8557778.71 0.216780E+10
March 0.683018E+09 0.00 0.683018E+09 0.159396E+09 0.178021E+10
April 0.842230E+09 3360833.16 0.838870E+09 0.357029E+09 0.123873E+10
May 0.101125E+10 42882803.87 0.968368E+09 0.715879E+09 0.771212E+09
June 0.117709E+10 0.100200E+09 0.107689E+10 0.120305E+10 0.472680E+09
July 0.112830E+10 72834337.51 0.105547E+10 0.135229E+10 0.335599E+09
August 0.976293E+09 14852187.10 0.961441E+09 0.109641E+10 0.450974E+09
September 0.719013E+09 149379.83 0.718864E+09 0.602680E+09 0.734452E+09
October 0.555410E+09 0.00 0.555410E+09 0.204413E+09 0.127270E+10
November 0.361182E+09 0.00 0.361182E+09 41194193.24 0.165716E+10
December 0.345984E+09 0.00 0.345984E+09 1191398.91 0.250889E+10
           
Annual Sum or Average 0.867813E+10 0.234279E+09 0.844385E+10 0.574210E+10 0.159438E+11
Minimum of Months 0.345984E+09 0.00 0.345984E+09 15304.68 0.335599E+09
Maximum of Months 0.117709E+10 0.100200E+09 0.107689E+10 0.135229E+10 0.255338E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.369653E+09 0.00 0.369653E+09 15303.70 0.255338E+10
February 0.508708E+09 0.00 0.508708E+09 8557695.72 0.216780E+10
March 0.683017E+09 0.00 0.683017E+09 0.159395E+09 0.178021E+10
April 0.842230E+09 3360829.13 0.838869E+09 0.357029E+09 0.123873E+10
May 0.101125E+10 42882752.42 0.968368E+09 0.715878E+09 0.771212E+09
June 0.117709E+10 0.100199E+09 0.107689E+10 0.120305E+10 0.472680E+09
July 0.112830E+10 72834250.12 0.105547E+10 0.135229E+10 0.335598E+09
August 0.976293E+09 14852169.28 0.961441E+09 0.109641E+10 0.450974E+09
September 0.719013E+09 149379.65 0.718863E+09 0.602679E+09 0.734452E+09
October 0.555409E+09 0.00 0.555409E+09 0.204413E+09 0.127270E+10
November 0.361182E+09 0.00 0.361182E+09 41194082.54 0.165716E+10
December 0.345984E+09 0.00 0.345984E+09 1191389.89 0.250889E+10
           
Annual Sum or Average 0.867812E+10 0.234279E+09 0.844384E+10 0.574209E+10 0.159438E+11
Minimum of Months 0.345984E+09 0.00 0.345984E+09 15303.70 0.335598E+09
Maximum of Months 0.117709E+10 0.100199E+09 0.107689E+10 0.135229E+10 0.255338E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.369638E+09 0.00 0.369638E+09 15304.06 0.255328E+10
February 0.508688E+09 0.00 0.508688E+09 8557433.80 0.216771E+10
March 0.682990E+09 0.00 0.682990E+09 0.159389E+09 0.178014E+10
April 0.842196E+09 3360697.70 0.838836E+09 0.357015E+09 0.123868E+10
May 0.101121E+10 42881075.51 0.968329E+09 0.715850E+09 0.771181E+09
June 0.117704E+10 0.100196E+09 0.107684E+10 0.120300E+10 0.472661E+09
July 0.112826E+10 72831401.97 0.105542E+10 0.135223E+10 0.335585E+09
August 0.976254E+09 14851588.49 0.961403E+09 0.109636E+10 0.450956E+09
September 0.718984E+09 149373.81 0.718835E+09 0.602655E+09 0.734422E+09
October 0.555387E+09 0.00 0.555387E+09 0.204405E+09 0.127265E+10
November 0.361168E+09 0.00 0.361168E+09 41192532.93 0.165710E+10
December 0.345970E+09 0.00 0.345970E+09 1191350.89 0.250878E+10
           
Annual Sum or Average 0.867778E+10 0.234270E+09 0.844351E+10 0.574186E+10 0.159431E+11
Minimum of Months 0.345970E+09 0.00 0.345970E+09 15304.06 0.335585E+09
Maximum of Months 0.117704E+10 0.100196E+09 0.107684E+10 0.135223E+10 0.255328E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.751622E+09 0.242365E+09 0.509257E+09 0.249378E+09 0.256193E+10
February 0.996129E+09 0.298914E+09 0.697216E+09 0.403427E+09 0.217738E+10
March 0.158257E+10 0.662771E+09 0.919800E+09 0.113005E+10 0.176771E+10
April 0.202706E+10 0.895665E+09 0.113140E+10 0.177917E+10 0.124213E+10
May 0.234674E+10 0.103809E+10 0.130865E+10 0.244217E+10 0.848601E+09
June 0.253637E+10 0.112095E+10 0.141542E+10 0.299118E+10 0.518538E+09
July 0.251676E+10 0.110810E+10 0.140867E+10 0.321268E+10 0.351806E+09
August 0.227291E+10 0.954045E+09 0.131887E+10 0.283362E+10 0.460701E+09
September 0.183044E+10 0.811914E+09 0.101853E+10 0.203567E+10 0.760205E+09
October 0.128351E+10 0.530895E+09 0.752616E+09 0.105642E+10 0.128651E+10
November 0.704546E+09 0.226010E+09 0.478535E+09 0.374331E+09 0.167930E+10
December 0.586102E+09 0.121101E+09 0.465000E+09 0.121623E+09 0.255016E+10
           
Annual Sum or Average 0.194348E+11 0.801081E+10 0.114240E+11 0.186297E+11 0.162050E+11
Minimum of Months 0.586102E+09 0.121101E+09 0.465000E+09 0.121623E+09 0.351806E+09
Maximum of Months 0.253637E+10 0.112095E+10 0.141542E+10 0.321268E+10 0.256193E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.751622E+09 0.242365E+09 0.509257E+09 0.249378E+09 0.256193E+10
February 0.996129E+09 0.298914E+09 0.697216E+09 0.403427E+09 0.217738E+10
March 0.158257E+10 0.662771E+09 0.919800E+09 0.113005E+10 0.176771E+10
April 0.202706E+10 0.895665E+09 0.113140E+10 0.177917E+10 0.124213E+10
May 0.234674E+10 0.103809E+10 0.130865E+10 0.244217E+10 0.848601E+09
June 0.253637E+10 0.112095E+10 0.141542E+10 0.299118E+10 0.518538E+09
July 0.251676E+10 0.110810E+10 0.140867E+10 0.321268E+10 0.351806E+09
August 0.227291E+10 0.954045E+09 0.131887E+10 0.283362E+10 0.460701E+09
September 0.183044E+10 0.811914E+09 0.101853E+10 0.203567E+10 0.760205E+09
October 0.128351E+10 0.530895E+09 0.752616E+09 0.105642E+10 0.128651E+10
November 0.704546E+09 0.226010E+09 0.478535E+09 0.374331E+09 0.167930E+10
December 0.586102E+09 0.121101E+09 0.465000E+09 0.121623E+09 0.255016E+10
           
Annual Sum or Average 0.194348E+11 0.801081E+10 0.114240E+11 0.186297E+11 0.162050E+11
Minimum of Months 0.586102E+09 0.121101E+09 0.465000E+09 0.121623E+09 0.351806E+09
Maximum of Months 0.253637E+10 0.112095E+10 0.141542E+10 0.321268E+10 0.256193E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.751608E+09 0.242360E+09 0.509247E+09 0.249373E+09 0.256188E+10
February 0.996111E+09 0.298908E+09 0.697203E+09 0.403420E+09 0.217734E+10
March 0.158254E+10 0.662759E+09 0.919783E+09 0.113003E+10 0.176768E+10
April 0.202703E+10 0.895649E+09 0.113138E+10 0.177914E+10 0.124211E+10
May 0.234669E+10 0.103807E+10 0.130863E+10 0.244213E+10 0.848585E+09
June 0.253632E+10 0.112093E+10 0.141539E+10 0.299113E+10 0.518528E+09
July 0.251672E+10 0.110808E+10 0.140864E+10 0.321262E+10 0.351799E+09
August 0.227287E+10 0.954027E+09 0.131884E+10 0.283357E+10 0.460692E+09
September 0.183041E+10 0.811900E+09 0.101851E+10 0.203563E+10 0.760191E+09
October 0.128349E+10 0.530885E+09 0.752603E+09 0.105640E+10 0.128649E+10
November 0.704533E+09 0.226006E+09 0.478527E+09 0.374324E+09 0.167927E+10
December 0.586091E+09 0.121099E+09 0.464992E+09 0.121621E+09 0.255011E+10
           
Annual Sum or Average 0.194344E+11 0.801067E+10 0.114237E+11 0.186294E+11 0.162047E+11
Minimum of Months 0.586091E+09 0.121099E+09 0.464992E+09 0.121621E+09 0.351799E+09
Maximum of Months 0.253632E+10 0.112093E+10 0.141539E+10 0.321262E+10 0.256188E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.158951E+10 0.927846E+09 0.661667E+09 0.119791E+10 0.210915E+10
February 0.163920E+10 0.790407E+09 0.848791E+09 0.120777E+10 0.186492E+10
March 0.221512E+10 0.124466E+10 0.970456E+09 0.204727E+10 0.156956E+10
April 0.177529E+10 0.709410E+09 0.106588E+10 0.171096E+10 0.121577E+10
May 0.160532E+10 0.466252E+09 0.113907E+10 0.170756E+10 0.831263E+09
June 0.150953E+10 0.319878E+09 0.118966E+10 0.180973E+10 0.517185E+09
July 0.159236E+10 0.386358E+09 0.120600E+10 0.212705E+10 0.362886E+09
August 0.178768E+10 0.579612E+09 0.120807E+10 0.234779E+10 0.472694E+09
September 0.201149E+10 0.979747E+09 0.103175E+10 0.243241E+10 0.734543E+09
October 0.198886E+10 0.113607E+10 0.852784E+09 0.204982E+10 0.116561E+10
November 0.137843E+10 0.778171E+09 0.600260E+09 0.122258E+10 0.146315E+10
December 0.132915E+10 0.687895E+09 0.641254E+09 0.935706E+09 0.211624E+10
           
Annual Sum or Average 0.204219E+11 0.900631E+10 0.114156E+11 0.207966E+11 0.144230E+11
Minimum of Months 0.132915E+10 0.319878E+09 0.600260E+09 0.935706E+09 0.362886E+09
Maximum of Months 0.221512E+10 0.124466E+10 0.120807E+10 0.243241E+10 0.211624E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.158951E+10 0.927845E+09 0.661667E+09 0.119791E+10 0.210915E+10
February 0.163920E+10 0.790406E+09 0.848790E+09 0.120777E+10 0.186492E+10
March 0.221511E+10 0.124466E+10 0.970455E+09 0.204727E+10 0.156956E+10
April 0.177529E+10 0.709410E+09 0.106588E+10 0.171096E+10 0.121577E+10
May 0.160532E+10 0.466252E+09 0.113907E+10 0.170756E+10 0.831262E+09
June 0.150953E+10 0.319878E+09 0.118966E+10 0.180972E+10 0.517185E+09
July 0.159236E+10 0.386357E+09 0.120600E+10 0.212705E+10 0.362886E+09
August 0.178768E+10 0.579611E+09 0.120807E+10 0.234779E+10 0.472694E+09
September 0.201149E+10 0.979745E+09 0.103175E+10 0.243241E+10 0.734542E+09
October 0.198886E+10 0.113607E+10 0.852783E+09 0.204982E+10 0.116561E+10
November 0.137843E+10 0.778170E+09 0.600260E+09 0.122257E+10 0.146315E+10
December 0.132915E+10 0.687894E+09 0.641253E+09 0.935704E+09 0.211624E+10
           
Annual Sum or Average 0.204219E+11 0.900630E+10 0.114156E+11 0.207965E+11 0.144230E+11
Minimum of Months 0.132915E+10 0.319878E+09 0.600260E+09 0.935704E+09 0.362886E+09
Maximum of Months 0.221511E+10 0.124466E+10 0.120807E+10 0.243241E+10 0.211624E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.158951E+10 0.927846E+09 0.661667E+09 0.119791E+10 0.210915E+10
February 0.163920E+10 0.790407E+09 0.848791E+09 0.120777E+10 0.186492E+10
March 0.221512E+10 0.124466E+10 0.970456E+09 0.204727E+10 0.156956E+10
April 0.177529E+10 0.709410E+09 0.106588E+10 0.171096E+10 0.121577E+10
May 0.160532E+10 0.466252E+09 0.113907E+10 0.170756E+10 0.831263E+09
June 0.150953E+10 0.319878E+09 0.118966E+10 0.180973E+10 0.517185E+09
July 0.159236E+10 0.386358E+09 0.120600E+10 0.212705E+10 0.362886E+09
August 0.178768E+10 0.579612E+09 0.120807E+10 0.234779E+10 0.472694E+09
September 0.201149E+10 0.979747E+09 0.103175E+10 0.243241E+10 0.734543E+09
October 0.198886E+10 0.113607E+10 0.852784E+09 0.204982E+10 0.116561E+10
November 0.137843E+10 0.778171E+09 0.600260E+09 0.122258E+10 0.146315E+10
December 0.132915E+10 0.687895E+09 0.641254E+09 0.935706E+09 0.211624E+10
           
Annual Sum or Average 0.204219E+11 0.900631E+10 0.114156E+11 0.207966E+11 0.144230E+11
Minimum of Months 0.132915E+10 0.319878E+09 0.600260E+09 0.935706E+09 0.362886E+09
Maximum of Months 0.221512E+10 0.124466E+10 0.120807E+10 0.243241E+10 0.211624E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.158951E+10 0.927845E+09 0.661667E+09 0.119791E+10 0.210915E+10
February 0.163920E+10 0.790406E+09 0.848790E+09 0.120777E+10 0.186492E+10
March 0.221511E+10 0.124466E+10 0.970455E+09 0.204727E+10 0.156956E+10
April 0.177529E+10 0.709410E+09 0.106588E+10 0.171096E+10 0.121577E+10
May 0.160532E+10 0.466252E+09 0.113907E+10 0.170756E+10 0.831262E+09
June 0.150953E+10 0.319878E+09 0.118966E+10 0.180972E+10 0.517185E+09
July 0.159236E+10 0.386357E+09 0.120600E+10 0.212705E+10 0.362886E+09
August 0.178768E+10 0.579611E+09 0.120807E+10 0.234779E+10 0.472694E+09
September 0.201149E+10 0.979745E+09 0.103175E+10 0.243241E+10 0.734542E+09
October 0.198886E+10 0.113607E+10 0.852783E+09 0.204982E+10 0.116561E+10
November 0.137843E+10 0.778170E+09 0.600260E+09 0.122257E+10 0.146315E+10
December 0.132915E+10 0.687894E+09 0.641253E+09 0.935704E+09 0.211624E+10
           
Annual Sum or Average 0.204219E+11 0.900630E+10 0.114156E+11 0.207965E+11 0.144230E+11
Minimum of Months 0.132915E+10 0.319878E+09 0.600260E+09 0.935704E+09 0.362886E+09
Maximum of Months 0.221511E+10 0.124466E+10 0.120807E+10 0.243241E+10 0.211624E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.158945E+10 0.927809E+09 0.661641E+09 0.119786E+10 0.210906E+10
February 0.163913E+10 0.790375E+09 0.848756E+09 0.120772E+10 0.186484E+10
March 0.221503E+10 0.124461E+10 0.970417E+09 0.204719E+10 0.156949E+10
April 0.177522E+10 0.709382E+09 0.106583E+10 0.171089E+10 0.121572E+10
May 0.160525E+10 0.466233E+09 0.113902E+10 0.170749E+10 0.831229E+09
June 0.150947E+10 0.319865E+09 0.118961E+10 0.180965E+10 0.517164E+09
July 0.159229E+10 0.386342E+09 0.120595E+10 0.212697E+10 0.362872E+09
August 0.178761E+10 0.579588E+09 0.120802E+10 0.234770E+10 0.472675E+09
September 0.201141E+10 0.979707E+09 0.103170E+10 0.243232E+10 0.734513E+09
October 0.198878E+10 0.113603E+10 0.852749E+09 0.204974E+10 0.116557E+10
November 0.137838E+10 0.778139E+09 0.600236E+09 0.122253E+10 0.146309E+10
December 0.132910E+10 0.687867E+09 0.641228E+09 0.935668E+09 0.211616E+10
           
Annual Sum or Average 0.204211E+11 0.900594E+10 0.114152E+11 0.207957E+11 0.144224E+11
Minimum of Months 0.132910E+10 0.319865E+09 0.600236E+09 0.935668E+09 0.362872E+09
Maximum of Months 0.221503E+10 0.124461E+10 0.120802E+10 0.243232E+10 0.211616E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.644878E+09 0.151392E+09 0.493486E+09 0.146673E+09 0.276796E+10
February 0.944024E+09 0.242621E+09 0.701403E+09 0.326844E+09 0.239621E+10
March 0.163812E+10 0.701403E+09 0.936713E+09 0.115213E+10 0.200867E+10
April 0.194095E+10 0.795869E+09 0.114508E+10 0.163191E+10 0.150441E+10
May 0.236599E+10 0.106927E+10 0.129671E+10 0.245300E+10 0.977335E+09
June 0.276255E+10 0.129939E+10 0.146316E+10 0.325682E+10 0.649075E+09
July 0.255215E+10 0.111895E+10 0.143320E+10 0.320700E+10 0.485572E+09
August 0.230827E+10 0.981499E+09 0.132677E+10 0.283524E+10 0.627019E+09
September 0.175423E+10 0.757577E+09 0.996657E+09 0.192896E+10 0.878726E+09
October 0.117508E+10 0.413932E+09 0.761152E+09 0.905716E+09 0.148106E+10
November 0.673896E+09 0.194193E+09 0.479703E+09 0.318320E+09 0.194234E+10
December 0.603681E+09 0.131535E+09 0.472146E+09 0.126799E+09 0.289686E+10
           
Annual Sum or Average 0.193638E+11 0.785764E+10 0.115062E+11 0.182894E+11 0.186152E+11
Minimum of Months 0.603681E+09 0.131535E+09 0.472146E+09 0.126799E+09 0.485572E+09
Maximum of Months 0.276255E+10 0.129939E+10 0.146316E+10 0.325682E+10 0.289686E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.644878E+09 0.151392E+09 0.493486E+09 0.146673E+09 0.276796E+10
February 0.944024E+09 0.242621E+09 0.701403E+09 0.326844E+09 0.239621E+10
March 0.163812E+10 0.701403E+09 0.936713E+09 0.115213E+10 0.200867E+10
April 0.194095E+10 0.795869E+09 0.114508E+10 0.163191E+10 0.150441E+10
May 0.236599E+10 0.106927E+10 0.129671E+10 0.245300E+10 0.977335E+09
June 0.276255E+10 0.129939E+10 0.146316E+10 0.325682E+10 0.649075E+09
July 0.255215E+10 0.111895E+10 0.143320E+10 0.320700E+10 0.485572E+09
August 0.230827E+10 0.981499E+09 0.132677E+10 0.283524E+10 0.627019E+09
September 0.175423E+10 0.757577E+09 0.996657E+09 0.192896E+10 0.878726E+09
October 0.117508E+10 0.413932E+09 0.761152E+09 0.905716E+09 0.148106E+10
November 0.673896E+09 0.194193E+09 0.479703E+09 0.318320E+09 0.194234E+10
December 0.603681E+09 0.131535E+09 0.472146E+09 0.126799E+09 0.289686E+10
           
Annual Sum or Average 0.193638E+11 0.785764E+10 0.115062E+11 0.182894E+11 0.186152E+11
Minimum of Months 0.603681E+09 0.131535E+09 0.472146E+09 0.126799E+09 0.485572E+09
Maximum of Months 0.276255E+10 0.129939E+10 0.146316E+10 0.325682E+10 0.289686E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.644866E+09 0.151389E+09 0.493477E+09 0.146670E+09 0.276790E+10
February 0.944007E+09 0.242617E+09 0.701390E+09 0.326838E+09 0.239617E+10
March 0.163809E+10 0.701391E+09 0.936696E+09 0.115210E+10 0.200863E+10
April 0.194092E+10 0.795855E+09 0.114506E+10 0.163188E+10 0.150438E+10
May 0.236594E+10 0.106925E+10 0.129669E+10 0.245296E+10 0.977317E+09
June 0.276250E+10 0.129937E+10 0.146313E+10 0.325676E+10 0.649063E+09
July 0.255210E+10 0.111893E+10 0.143317E+10 0.320694E+10 0.485563E+09
August 0.230823E+10 0.981481E+09 0.132675E+10 0.283519E+10 0.627008E+09
September 0.175420E+10 0.757563E+09 0.996638E+09 0.192892E+10 0.878710E+09
October 0.117506E+10 0.413924E+09 0.761138E+09 0.905700E+09 0.148104E+10
November 0.673884E+09 0.194189E+09 0.479695E+09 0.318314E+09 0.194230E+10
December 0.603670E+09 0.131533E+09 0.472137E+09 0.126797E+09 0.289680E+10
           
Annual Sum or Average 0.193635E+11 0.785749E+10 0.115060E+11 0.182891E+11 0.186149E+11
Minimum of Months 0.603670E+09 0.131533E+09 0.472137E+09 0.126797E+09 0.485563E+09
Maximum of Months 0.276250E+10 0.129937E+10 0.146313E+10 0.325676E+10 0.289680E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.184824E+10 0.00 0.184824E+10 13997624.62 0.116203E+11
February 0.254351E+10 0.00 0.254351E+10 0.104600E+09 0.984115E+10
March 0.341505E+10 0.00 0.341505E+10 0.950273E+09 0.793631E+10
April 0.421110E+10 16803962.60 0.419430E+10 0.205058E+10 0.542768E+10
May 0.505620E+10 0.214411E+09 0.484178E+10 0.369694E+10 0.358958E+10
June 0.588536E+10 0.500992E+09 0.538437E+10 0.606085E+10 0.224997E+10
July 0.564143E+10 0.364167E+09 0.527727E+10 0.679815E+10 0.162699E+10
August 0.488141E+10 74260037.56 0.480715E+10 0.554376E+10 0.215785E+10
September 0.359502E+10 746890.12 0.359428E+10 0.309195E+10 0.339252E+10
October 0.277701E+10 0.00 0.277701E+10 0.121503E+10 0.557841E+10
November 0.180589E+10 0.00 0.180589E+10 0.320937E+09 0.707012E+10
December 0.172990E+10 0.00 0.172990E+10 17882656.37 0.110820E+11
           
Annual Sum or Average 0.433901E+11 0.117138E+10 0.422187E+11 0.298649E+11 0.715729E+11
Minimum of Months 0.172990E+10 0.00 0.172990E+10 13997624.62 0.162699E+10
Maximum of Months 0.588536E+10 0.500992E+09 0.538437E+10 0.679815E+10 0.116203E+11



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.225484E+10 0.727087E+09 0.152775E+10 0.798126E+09 0.703993E+10
February 0.298836E+10 0.896733E+09 0.209163E+10 0.129095E+10 0.603178E+10
March 0.474766E+10 0.198829E+10 0.275937E+10 0.347169E+10 0.487228E+10
April 0.608113E+10 0.268697E+10 0.339416E+10 0.540809E+10 0.342440E+10
May 0.704014E+10 0.311423E+10 0.392591E+10 0.731505E+10 0.241026E+10
June 0.760902E+10 0.336281E+10 0.424621E+10 0.891866E+10 0.151349E+10
July 0.755021E+10 0.332425E+10 0.422596E+10 0.955920E+10 0.108836E+10
August 0.681867E+10 0.286211E+10 0.395656E+10 0.843347E+10 0.142146E+10
September 0.549127E+10 0.243572E+10 0.305556E+10 0.609838E+10 0.215100E+10
October 0.385049E+10 0.159267E+10 0.225783E+10 0.325434E+10 0.349775E+10
November 0.211362E+10 0.678023E+09 0.143559E+10 0.121100E+10 0.449219E+10
December 0.175829E+10 0.363300E+09 0.139499E+10 0.408546E+09 0.695041E+10
           
Annual Sum or Average 0.583037E+11 0.240322E+11 0.342715E+11 0.561675E+11 0.448933E+11
Minimum of Months 0.175829E+10 0.363300E+09 0.139499E+10 0.408546E+09 0.108836E+10
Maximum of Months 0.760902E+10 0.336281E+10 0.424621E+10 0.955920E+10 0.703993E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.794747E+10 0.463917E+10 0.330830E+10 0.602594E+10 0.100187E+11
February 0.819589E+10 0.395199E+10 0.424390E+10 0.607970E+10 0.889304E+10
March 0.110754E+11 0.622322E+10 0.485222E+10 0.102209E+11 0.746271E+10
April 0.887633E+10 0.354701E+10 0.532932E+10 0.858866E+10 0.570325E+10
May 0.802650E+10 0.233123E+10 0.569526E+10 0.849810E+10 0.399945E+10
June 0.754758E+10 0.159937E+10 0.594821E+10 0.901116E+10 0.248824E+10
July 0.796169E+10 0.193177E+10 0.602992E+10 0.105874E+11 0.179035E+10
August 0.893830E+10 0.289802E+10 0.604028E+10 0.116900E+11 0.232909E+10
September 0.100573E+11 0.489867E+10 0.515867E+10 0.120849E+11 0.356160E+10
October 0.994417E+10 0.568030E+10 0.426387E+10 0.102192E+11 0.553599E+10
November 0.689207E+10 0.389081E+10 0.300127E+10 0.615437E+10 0.682743E+10
December 0.664566E+10 0.343943E+10 0.320623E+10 0.475017E+10 0.987797E+10
           
Annual Sum or Average 0.102108E+12 0.450310E+11 0.570775E+11 0.103911E+12 0.684879E+11
Minimum of Months 0.664566E+10 0.159937E+10 0.300127E+10 0.475017E+10 0.179035E+10
Maximum of Months 0.110754E+11 0.622322E+10 0.604028E+10 0.120849E+11 0.100187E+11



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.193461E+10 0.454172E+09 0.148044E+10 0.477288E+09 0.746025E+10
February 0.283204E+10 0.727856E+09 0.210419E+10 0.107929E+10 0.636332E+10
March 0.491430E+10 0.210419E+10 0.281011E+10 0.365446E+10 0.514658E+10
April 0.582280E+10 0.238758E+10 0.343522E+10 0.516148E+10 0.373484E+10
May 0.709789E+10 0.320779E+10 0.389010E+10 0.743512E+10 0.267730E+10
June 0.828757E+10 0.389813E+10 0.438944E+10 0.981824E+10 0.176084E+10
July 0.765638E+10 0.335682E+10 0.429956E+10 0.970570E+10 0.130509E+10
August 0.692474E+10 0.294447E+10 0.398027E+10 0.863250E+10 0.163015E+10
September 0.526265E+10 0.227271E+10 0.298994E+10 0.586047E+10 0.236267E+10
October 0.352522E+10 0.124178E+10 0.228343E+10 0.291349E+10 0.373879E+10
November 0.202167E+10 0.582573E+09 0.143910E+10 0.110030E+10 0.470823E+10
December 0.181103E+10 0.394602E+09 0.141642E+10 0.452297E+09 0.722658E+10
           
Annual Sum or Average 0.580909E+11 0.235727E+11 0.345182E+11 0.562906E+11 0.481146E+11
Minimum of Months 0.181103E+10 0.394602E+09 0.141642E+10 0.452297E+09 0.130509E+10
Maximum of Months 0.828757E+10 0.389813E+10 0.438944E+10 0.981824E+10 0.746025E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.184824E+10 0.00 0.184824E+10 26238579.10 0.112817E+11
February 0.254351E+10 0.00 0.254351E+10 0.130546E+09 0.953617E+10
March 0.341505E+10 0.00 0.341505E+10 0.101610E+10 0.752046E+10
April 0.421110E+10 16803962.60 0.419430E+10 0.216743E+10 0.507774E+10
May 0.505620E+10 0.214411E+09 0.484178E+10 0.377152E+10 0.341298E+10
June 0.588536E+10 0.500992E+09 0.538437E+10 0.604031E+10 0.220795E+10
July 0.564143E+10 0.364167E+09 0.527727E+10 0.673750E+10 0.162696E+10
August 0.488141E+10 74260037.56 0.480715E+10 0.551470E+10 0.212421E+10
September 0.359502E+10 746890.12 0.359428E+10 0.313910E+10 0.320975E+10
October 0.277701E+10 0.00 0.277701E+10 0.135052E+10 0.507664E+10
November 0.180589E+10 0.00 0.180589E+10 0.396288E+09 0.648194E+10
December 0.172990E+10 0.00 0.172990E+10 27072859.48 0.106517E+11
           
Annual Sum or Average 0.433901E+11 0.117138E+10 0.422187E+11 0.303173E+11 0.682082E+11
Minimum of Months 0.172990E+10 0.00 0.172990E+10 26238579.10 0.162696E+10
Maximum of Months 0.588536E+10 0.500992E+09 0.538437E+10 0.673750E+10 0.112817E+11



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.225484E+10 0.727087E+09 0.152775E+10 0.822441E+09 0.683365E+10
February 0.298836E+10 0.896733E+09 0.209163E+10 0.132727E+10 0.585464E+10
March 0.474766E+10 0.198829E+10 0.275937E+10 0.354157E+10 0.461581E+10
April 0.608113E+10 0.268697E+10 0.339416E+10 0.547815E+10 0.323538E+10
May 0.704014E+10 0.311423E+10 0.392591E+10 0.733154E+10 0.231888E+10
June 0.760902E+10 0.336281E+10 0.424621E+10 0.888765E+10 0.149498E+10
July 0.755021E+10 0.332425E+10 0.422596E+10 0.951045E+10 0.109413E+10
August 0.681867E+10 0.286211E+10 0.395656E+10 0.840141E+10 0.140829E+10
September 0.549127E+10 0.243572E+10 0.305556E+10 0.611397E+10 0.206230E+10
October 0.385049E+10 0.159267E+10 0.225783E+10 0.335179E+10 0.321664E+10
November 0.211362E+10 0.678023E+09 0.143559E+10 0.128216E+10 0.413634E+10
December 0.175829E+10 0.363300E+09 0.139499E+10 0.428613E+09 0.668812E+10
           
Annual Sum or Average 0.583037E+11 0.240322E+11 0.342715E+11 0.564770E+11 0.429592E+11
Minimum of Months 0.175829E+10 0.363300E+09 0.139499E+10 0.428613E+09 0.109413E+10
Maximum of Months 0.760902E+10 0.336281E+10 0.424621E+10 0.951045E+10 0.683365E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.794747E+10 0.463917E+10 0.330830E+10 0.609714E+10 0.965580E+10
February 0.819589E+10 0.395199E+10 0.424390E+10 0.614636E+10 0.858772E+10
March 0.110754E+11 0.622322E+10 0.485222E+10 0.103356E+11 0.702649E+10
April 0.887633E+10 0.354701E+10 0.532932E+10 0.868294E+10 0.536434E+10
May 0.802650E+10 0.233123E+10 0.569526E+10 0.852980E+10 0.381570E+10
June 0.754758E+10 0.159937E+10 0.594821E+10 0.897539E+10 0.243299E+10
July 0.796169E+10 0.193177E+10 0.602992E+10 0.105213E+11 0.178347E+10
August 0.893830E+10 0.289802E+10 0.604028E+10 0.116449E+11 0.229123E+10
September 0.100573E+11 0.489867E+10 0.515867E+10 0.121001E+11 0.339931E+10
October 0.994417E+10 0.568030E+10 0.426387E+10 0.103570E+11 0.508630E+10
November 0.689207E+10 0.389081E+10 0.300127E+10 0.628577E+10 0.626959E+10
December 0.664566E+10 0.343943E+10 0.320623E+10 0.483464E+10 0.944769E+10
           
Annual Sum or Average 0.102108E+12 0.450310E+11 0.570775E+11 0.104511E+12 0.651606E+11
Minimum of Months 0.664566E+10 0.159937E+10 0.300127E+10 0.483464E+10 0.178347E+10
Maximum of Months 0.110754E+11 0.622322E+10 0.604028E+10 0.121001E+11 0.965580E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.193461E+10 0.454172E+09 0.148044E+10 0.491734E+09 0.724247E+10
February 0.283204E+10 0.727856E+09 0.210419E+10 0.109535E+10 0.619065E+10
March 0.491430E+10 0.210419E+10 0.281011E+10 0.369270E+10 0.489455E+10
April 0.582280E+10 0.238758E+10 0.343522E+10 0.520705E+10 0.353633E+10
May 0.709789E+10 0.320779E+10 0.389010E+10 0.744969E+10 0.256859E+10
June 0.828757E+10 0.389813E+10 0.438944E+10 0.978381E+10 0.172642E+10
July 0.765638E+10 0.335682E+10 0.429956E+10 0.965785E+10 0.129708E+10
August 0.692474E+10 0.294447E+10 0.398027E+10 0.860343E+10 0.160517E+10
September 0.526265E+10 0.227271E+10 0.298994E+10 0.587595E+10 0.226208E+10
October 0.352522E+10 0.124178E+10 0.228343E+10 0.297721E+10 0.347454E+10
November 0.202167E+10 0.582573E+09 0.143910E+10 0.114556E+10 0.439036E+10
December 0.181103E+10 0.394602E+09 0.141642E+10 0.468035E+09 0.697765E+10
           
Annual Sum or Average 0.580909E+11 0.235727E+11 0.345182E+11 0.564484E+11 0.461659E+11
Minimum of Months 0.181103E+10 0.394602E+09 0.141642E+10 0.468035E+09 0.129708E+10
Maximum of Months 0.828757E+10 0.389813E+10 0.438944E+10 0.978381E+10 0.724247E+10



Table of Contents

Report: WindowZoneSummaryMonthly

For: BASEMENT

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: CORE_BOTTOM

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: CORE_MID

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: CORE_TOP

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.03 4766.58 690.06 0.00 690.06 0.00 0.00
February 17.69 4480.37 1051.39 0.00 1051.39 0.00 0.00
March 297.55 3323.25 1275.04 0.00 1275.04 0.00 0.00
April 688.71 2389.50 1624.66 6.48 1618.18 0.00 0.00
May 1336.38 1439.68 1887.77 80.05 1807.72 0.00 0.00
June 2320.67 911.80 2270.59 193.28 2077.31 0.00 0.00
July 2524.41 626.49 2106.28 135.96 1970.31 0.00 0.00
August 2046.74 841.87 1822.52 27.73 1794.79 0.00 0.00
September 1162.57 1416.76 1386.97 0.29 1386.69 0.00 0.00
October 381.59 2375.84 1036.82 0.00 1036.82 0.00 0.00
November 79.46 3196.66 696.72 0.00 696.72 0.00 0.00
December 2.22 4683.52 645.87 0.00 645.87 0.00 0.00
               
Annual Sum or Average 910.40 2527.85 1375.90 37.14 1338.75 0.00 0.00
Minimum of Months 0.03 626.49 645.87 0.00 645.87 0.00 0.00
Maximum of Months 2524.41 4766.58 2270.59 193.28 2077.31 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 279.32 2869.53 841.86 271.46 570.40 0.00 0.00
February 500.28 2700.10 1235.27 370.67 864.60 0.00 0.00
March 1265.73 1979.95 1772.58 742.35 1030.24 0.00 0.00
April 2059.21 1437.64 2346.12 1036.64 1309.48 0.00 0.00
May 2735.39 950.49 2628.50 1162.73 1465.77 0.00 0.00
June 3462.00 600.16 2935.59 1297.39 1638.20 0.00 0.00
July 3598.41 394.05 2818.94 1241.14 1577.80 0.00 0.00
August 3173.84 516.01 2545.81 1068.59 1477.22 0.00 0.00
September 2356.09 879.86 2118.56 939.71 1178.85 0.00 0.00
October 1183.26 1440.98 1437.62 594.64 842.98 0.00 0.00
November 433.25 1943.63 815.44 261.58 553.86 0.00 0.00
December 136.23 2856.35 656.47 135.64 520.83 0.00 0.00
               
Annual Sum or Average 1772.22 1541.56 1848.81 762.06 1086.75 0.00 0.00
Minimum of Months 136.23 394.05 656.47 135.64 520.83 0.00 0.00
Maximum of Months 3598.41 2869.53 2935.59 1297.39 1638.20 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 2236.23 3937.29 2967.26 1732.08 1235.18 0.00 0.00
February 2496.20 3854.38 3387.86 1633.60 1754.26 0.00 0.00
March 3821.78 2930.01 4135.11 2323.49 1811.62 0.00 0.00
April 3300.44 2345.22 3424.52 1368.45 2056.07 0.00 0.00
May 3187.62 1551.78 2996.76 870.39 2126.38 0.00 0.00
June 3490.96 997.65 2911.89 617.04 2294.84 0.00 0.00
July 3970.72 677.43 2972.56 721.24 2251.32 0.00 0.00
August 4382.79 882.41 3337.19 1082.00 2255.19 0.00 0.00
September 4692.12 1416.93 3880.16 1889.93 1990.23 0.00 0.00
October 3826.55 2175.93 3712.74 2120.79 1591.95 0.00 0.00
November 2358.35 2822.41 2658.99 1501.09 1157.90 0.00 0.00
December 1746.75 3950.54 2481.22 1284.14 1197.07 0.00 0.00
               
Annual Sum or Average 3297.25 2286.73 3237.85 1427.93 1809.92 0.00 0.00
Minimum of Months 1746.75 677.43 2481.22 617.04 1157.90 0.00 0.00
Maximum of Months 4692.12 3950.54 4135.11 2323.49 2294.84 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 164.28 3100.29 722.30 169.57 552.74 0.00 0.00
February 405.31 2971.47 1170.66 300.87 869.79 0.00 0.00
March 1290.45 2249.84 1834.80 785.62 1049.18 0.00 0.00
April 1888.77 1741.21 2246.46 921.14 1325.32 0.00 0.00
May 2747.52 1094.68 2650.06 1197.66 1452.40 0.00 0.00
June 3769.44 751.24 3197.38 1503.91 1693.46 0.00 0.00
July 3592.05 543.87 2858.58 1253.30 1605.28 0.00 0.00
August 3175.66 702.30 2585.41 1099.34 1486.07 0.00 0.00
September 2232.57 1017.04 2030.35 876.82 1153.53 0.00 0.00
October 1014.46 1658.89 1316.17 463.63 852.54 0.00 0.00
November 368.42 2248.06 779.97 224.76 555.21 0.00 0.00
December 142.02 3244.67 676.16 147.33 528.83 0.00 0.00
               
Annual Sum or Average 1739.85 1770.84 1842.06 747.49 1094.57 0.00 0.00
Minimum of Months 142.02 543.87 676.16 147.33 528.83 0.00 0.00
Maximum of Months 3769.44 3244.67 3197.38 1503.91 1693.46 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 5.23 4338.53 690.06 0.00 690.06 0.00 0.00
February 43.24 4067.93 1051.38 0.00 1051.38 0.00 0.00
March 354.79 2963.08 1275.03 0.00 1275.03 0.00 0.00
April 791.12 2094.01 1624.65 6.48 1618.17 0.00 0.00
May 1380.28 1340.20 1887.77 80.05 1807.71 0.00 0.00
June 2338.29 868.04 2270.59 193.28 2077.30 0.00 0.00
July 2538.14 607.45 2106.27 135.96 1970.31 0.00 0.00
August 2069.80 805.65 1822.51 27.73 1794.78 0.00 0.00
September 1192.88 1308.84 1386.97 0.29 1386.68 0.00 0.00
October 453.64 2082.74 1036.82 0.00 1036.82 0.00 0.00
November 123.82 2727.67 696.72 0.00 696.72 0.00 0.00
December 6.68 4137.55 645.87 0.00 645.87 0.00 0.00
               
Annual Sum or Average 947.01 2269.56 1375.89 37.14 1338.75 0.00 0.00
Minimum of Months 5.23 607.45 645.87 0.00 645.87 0.00 0.00
Maximum of Months 2538.14 4338.53 2270.59 193.28 2077.30 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 297.99 2628.41 841.86 271.46 570.40 0.00 0.00
February 533.62 2493.30 1235.27 370.67 864.59 0.00 0.00
March 1296.18 1819.10 1772.57 742.34 1030.23 0.00 0.00
April 2086.45 1321.14 2346.11 1036.64 1309.47 0.00 0.00
May 2731.13 899.89 2628.49 1162.72 1465.77 0.00 0.00
June 3440.84 583.91 2935.58 1297.38 1638.20 0.00 0.00
July 3569.00 406.35 2818.93 1241.13 1577.79 0.00 0.00
August 3148.70 530.71 2545.80 1068.59 1477.21 0.00 0.00
September 2352.77 829.86 2118.55 939.71 1178.84 0.00 0.00
October 1215.03 1305.91 1437.61 594.63 842.98 0.00 0.00
November 467.21 1733.10 815.44 261.58 553.85 0.00 0.00
December 152.53 2594.99 656.47 135.64 520.83 0.00 0.00
               
Annual Sum or Average 1781.06 1423.56 1848.80 762.06 1086.74 0.00 0.00
Minimum of Months 152.53 406.35 656.47 135.64 520.83 0.00 0.00
Maximum of Months 3569.00 2628.41 2935.58 1297.38 1638.20 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 2249.83 3740.56 2967.25 1732.07 1235.18 0.00 0.00
February 2513.11 3676.03 3387.85 1633.59 1754.26 0.00 0.00
March 3816.06 2786.26 4135.10 2323.48 1811.61 0.00 0.00
April 3313.53 2200.33 3424.51 1368.44 2056.07 0.00 0.00
May 3172.83 1493.22 2996.75 870.38 2126.37 0.00 0.00
June 3476.53 959.97 2911.88 617.04 2294.84 0.00 0.00
July 3952.89 668.44 2972.55 721.24 2251.31 0.00 0.00
August 4364.56 869.58 3337.18 1082.00 2255.18 0.00 0.00
September 4662.37 1374.07 3880.15 1889.92 1990.23 0.00 0.00
October 3815.41 2066.90 3712.73 2120.78 1591.95 0.00 0.00
November 2374.37 2634.04 2658.98 1501.08 1157.90 0.00 0.00
December 1773.51 3688.01 2481.21 1284.14 1197.07 0.00 0.00
               
Annual Sum or Average 3294.98 2171.74 3237.84 1427.92 1809.91 0.00 0.00
Minimum of Months 1773.51 668.44 2481.21 617.04 1157.90 0.00 0.00
Maximum of Months 4662.37 3740.56 4135.10 2323.48 2294.84 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 178.20 2785.34 722.30 169.57 552.73 0.00 0.00
February 446.13 2630.34 1170.65 300.87 869.79 0.00 0.00
March 1364.42 1921.51 1834.79 785.61 1049.18 0.00 0.00
April 1991.31 1440.91 2246.45 921.14 1325.32 0.00 0.00
May 2775.96 999.59 2650.05 1197.65 1452.40 0.00 0.00
June 3787.90 679.34 3197.36 1503.91 1693.46 0.00 0.00
July 3623.69 487.26 2858.56 1253.29 1605.27 0.00 0.00
August 3223.01 608.63 2585.40 1099.34 1486.06 0.00 0.00
September 2260.98 911.53 2030.34 876.82 1153.53 0.00 0.00
October 1087.77 1395.90 1316.17 463.63 852.54 0.00 0.00
November 424.50 1816.45 779.96 224.76 555.21 0.00 0.00
December 168.87 2698.10 676.16 147.33 528.83 0.00 0.00
               
Annual Sum or Average 1784.96 1525.71 1842.05 747.48 1094.57 0.00 0.00
Minimum of Months 168.87 487.26 676.16 147.33 528.83 0.00 0.00
Maximum of Months 3787.90 2785.34 3197.36 1503.91 1693.46 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 9.80 4212.09 690.06 0.00 690.06 0.00 0.00
February 53.96 3941.87 1051.38 0.00 1051.38 0.00 0.00
March 379.37 2807.82 1275.03 0.00 1275.03 0.00 0.00
April 836.20 1959.00 1624.65 6.48 1618.17 0.00 0.00
May 1408.12 1274.26 1887.77 80.05 1807.71 0.00 0.00
June 2330.37 851.83 2270.59 193.28 2077.30 0.00 0.00
July 2515.49 607.44 2106.27 135.96 1970.31 0.00 0.00
August 2058.95 793.09 1822.51 27.73 1794.78 0.00 0.00
September 1211.07 1238.33 1386.97 0.29 1386.68 0.00 0.00
October 504.23 1895.40 1036.82 0.00 1036.82 0.00 0.00
November 152.89 2500.75 696.72 0.00 696.72 0.00 0.00
December 10.11 3976.89 645.87 0.00 645.87 0.00 0.00
               
Annual Sum or Average 961.36 2162.87 1375.89 37.14 1338.75 0.00 0.00
Minimum of Months 9.80 607.44 645.87 0.00 645.87 0.00 0.00
Maximum of Months 2515.49 4212.09 2270.59 193.28 2077.30 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 307.06 2551.39 841.86 271.46 570.40 0.00 0.00
February 548.64 2420.07 1235.27 370.67 864.59 0.00 0.00
March 1322.27 1723.35 1772.57 742.34 1030.23 0.00 0.00
April 2113.48 1248.22 2346.11 1036.64 1309.47 0.00 0.00
May 2737.28 865.77 2628.49 1162.72 1465.77 0.00 0.00
June 3428.88 576.77 2935.58 1297.38 1638.20 0.00 0.00
July 3550.80 408.50 2818.93 1241.13 1577.79 0.00 0.00
August 3136.73 525.80 2545.80 1068.59 1477.21 0.00 0.00
September 2358.78 795.64 2118.55 939.71 1178.84 0.00 0.00
October 1251.42 1200.96 1437.61 594.63 842.98 0.00 0.00
November 494.66 1595.81 815.44 261.58 553.85 0.00 0.00
December 160.03 2497.06 656.47 135.64 520.83 0.00 0.00
               
Annual Sum or Average 1790.87 1362.23 1848.80 762.06 1086.74 0.00 0.00
Minimum of Months 160.03 408.50 656.47 135.64 520.83 0.00 0.00
Maximum of Months 3550.80 2551.39 2935.58 1297.38 1638.20 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 2276.41 3605.06 2967.25 1732.07 1235.18 0.00 0.00
February 2540.66 3549.82 3387.85 1633.59 1754.26 0.00 0.00
March 3858.86 2623.39 4135.10 2323.48 1811.61 0.00 0.00
April 3349.90 2069.58 3424.51 1368.44 2056.07 0.00 0.00
May 3184.66 1424.62 2996.75 870.38 2126.37 0.00 0.00
June 3462.73 938.65 2911.88 617.04 2294.84 0.00 0.00
July 3928.21 665.87 2972.55 721.24 2251.31 0.00 0.00
August 4347.70 855.45 3337.18 1082.00 2255.18 0.00 0.00
September 4668.27 1311.46 3880.15 1889.92 1990.23 0.00 0.00
October 3866.87 1899.01 3712.73 2120.78 1591.95 0.00 0.00
November 2425.07 2418.82 2658.98 1501.08 1157.90 0.00 0.00
December 1805.05 3527.36 2481.21 1284.14 1197.07 0.00 0.00
               
Annual Sum or Average 3314.02 2066.23 3237.84 1427.92 1809.91 0.00 0.00
Minimum of Months 1805.05 665.87 2481.21 617.04 1157.90 0.00 0.00
Maximum of Months 4668.27 3605.06 4135.10 2323.48 2294.84 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 183.59 2704.03 722.30 169.57 552.73 0.00 0.00
February 452.78 2558.97 1170.65 300.87 869.79 0.00 0.00
March 1378.70 1827.41 1834.79 785.61 1049.18 0.00 0.00
April 2008.89 1364.33 2246.45 921.14 1325.32 0.00 0.00
May 2781.39 959.00 2650.05 1197.65 1452.40 0.00 0.00
June 3774.62 666.06 3197.36 1503.91 1693.46 0.00 0.00
July 3605.83 484.27 2858.56 1253.29 1605.27 0.00 0.00
August 3212.15 599.30 2585.40 1099.34 1486.06 0.00 0.00
September 2266.96 872.71 2030.34 876.82 1153.53 0.00 0.00
October 1111.56 1297.25 1316.17 463.63 852.54 0.00 0.00
November 441.96 1693.81 779.96 224.76 555.21 0.00 0.00
December 174.74 2605.16 676.16 147.33 528.83 0.00 0.00
               
Annual Sum or Average 1789.97 1463.91 1842.05 747.48 1094.57 0.00 0.00
Minimum of Months 174.74 484.27 676.16 147.33 528.83 0.00 0.00
Maximum of Months 3774.62 2704.03 3197.36 1503.91 1693.46 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: GROUNDFLOOR_PLENUM

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: MIDFLOOR_PLENUM

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: TOPFLOOR_PLENUM

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: DATACENTER_MID_ZN_6

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: BASEMENT

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: CORE_BOTTOM

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: CORE_MID

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: CORE_TOP

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 76520.82 0.127668E+11 0.184825E+10 0.00 0.184825E+10 0.00 0.00
February 42788382.67 0.108389E+11 0.254352E+10 0.00 0.254352E+10 0.00 0.00
March 0.796971E+09 0.890099E+10 0.341506E+10 0.00 0.341506E+10 0.00 0.00
April 0.178513E+10 0.619358E+10 0.421112E+10 16804022.27 0.419431E+10 0.00 0.00
May 0.357936E+10 0.385603E+10 0.505621E+10 0.214412E+09 0.484180E+10 0.00 0.00
June 0.601518E+10 0.236338E+10 0.588538E+10 0.500994E+09 0.538439E+10 0.00 0.00
July 0.676138E+10 0.167798E+10 0.564146E+10 0.364169E+09 0.527729E+10 0.00 0.00
August 0.548199E+10 0.225485E+10 0.488143E+10 74260301.26 0.480717E+10 0.00 0.00
September 0.301337E+10 0.367223E+10 0.359504E+10 746892.77 0.359429E+10 0.00 0.00
October 0.102206E+10 0.636344E+10 0.277702E+10 0.00 0.277702E+10 0.00 0.00
November 0.205969E+09 0.828575E+10 0.180590E+10 0.00 0.180590E+10 0.00 0.00
December 5956928.49 0.125443E+11 0.172991E+10 0.00 0.172991E+10 0.00 0.00
               
Annual Sum or Average 0.287102E+11 0.797183E+11 0.433903E+11 0.117139E+10 0.422189E+11 0.00 0.00
Minimum of Months 76520.82 0.167798E+10 0.172991E+10 0.00 0.172991E+10 0.00 0.00
Maximum of Months 0.676138E+10 0.127668E+11 0.588538E+10 0.500994E+09 0.538439E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.748129E+09 0.768574E+10 0.225485E+10 0.727090E+09 0.152776E+10 0.00 0.00
February 0.121027E+10 0.653209E+10 0.298837E+10 0.896736E+09 0.209163E+10 0.00 0.00
March 0.339012E+10 0.530309E+10 0.474768E+10 0.198830E+10 0.275938E+10 0.00 0.00
April 0.533748E+10 0.372637E+10 0.608115E+10 0.268698E+10 0.339417E+10 0.00 0.00
May 0.732646E+10 0.254579E+10 0.704017E+10 0.311424E+10 0.392593E+10 0.00 0.00
June 0.897349E+10 0.155560E+10 0.760905E+10 0.336283E+10 0.424622E+10 0.00 0.00
July 0.963797E+10 0.105541E+10 0.755024E+10 0.332427E+10 0.422597E+10 0.00 0.00
August 0.850080E+10 0.138209E+10 0.681870E+10 0.286212E+10 0.395658E+10 0.00 0.00
September 0.610698E+10 0.228060E+10 0.549130E+10 0.243573E+10 0.305557E+10 0.00 0.00
October 0.316924E+10 0.385951E+10 0.385051E+10 0.159267E+10 0.225784E+10 0.00 0.00
November 0.112299E+10 0.503788E+10 0.211362E+10 0.678026E+09 0.143560E+10 0.00 0.00
December 0.364867E+09 0.765043E+10 0.175829E+10 0.363301E+09 0.139499E+10 0.00 0.00
               
Annual Sum or Average 0.558888E+11 0.486146E+11 0.583039E+11 0.240323E+11 0.342716E+11 0.00 0.00
Minimum of Months 0.364867E+09 0.105541E+10 0.175829E+10 0.363301E+09 0.139499E+10 0.00 0.00
Maximum of Months 0.963797E+10 0.768574E+10 0.760905E+10 0.336283E+10 0.424622E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.598951E+10 0.105456E+11 0.794750E+10 0.463919E+10 0.330831E+10 0.00 0.00
February 0.603881E+10 0.932451E+10 0.819592E+10 0.395200E+10 0.424392E+10 0.00 0.00
March 0.102363E+11 0.784773E+10 0.110755E+11 0.622324E+10 0.485224E+10 0.00 0.00
April 0.855474E+10 0.607881E+10 0.887636E+10 0.354702E+10 0.532934E+10 0.00 0.00
May 0.853773E+10 0.415628E+10 0.802653E+10 0.233124E+10 0.569529E+10 0.00 0.00
June 0.904856E+10 0.258590E+10 0.754761E+10 0.159938E+10 0.594823E+10 0.00 0.00
July 0.106352E+11 0.181442E+10 0.796172E+10 0.193177E+10 0.602994E+10 0.00 0.00
August 0.117389E+11 0.236345E+10 0.893834E+10 0.289803E+10 0.604030E+10 0.00 0.00
September 0.121620E+11 0.367268E+10 0.100574E+11 0.489869E+10 0.515869E+10 0.00 0.00
October 0.102490E+11 0.582802E+10 0.994420E+10 0.568032E+10 0.426388E+10 0.00 0.00
November 0.611283E+10 0.731569E+10 0.689210E+10 0.389082E+10 0.300128E+10 0.00 0.00
December 0.467849E+10 0.105811E+11 0.664569E+10 0.343944E+10 0.320624E+10 0.00 0.00
               
Annual Sum or Average 0.103982E+12 0.721143E+11 0.102109E+12 0.450312E+11 0.570777E+11 0.00 0.00
Minimum of Months 0.467849E+10 0.181442E+10 0.664569E+10 0.159938E+10 0.300128E+10 0.00 0.00
Maximum of Months 0.121620E+11 0.105811E+11 0.110755E+11 0.622324E+10 0.604030E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.440017E+09 0.830381E+10 0.193462E+10 0.454173E+09 0.148045E+10 0.00 0.00
February 0.980526E+09 0.718859E+10 0.283206E+10 0.727859E+09 0.210420E+10 0.00 0.00
March 0.345635E+10 0.602598E+10 0.491432E+10 0.210420E+10 0.281012E+10 0.00 0.00
April 0.489569E+10 0.451321E+10 0.582283E+10 0.238759E+10 0.343523E+10 0.00 0.00
May 0.735896E+10 0.293199E+10 0.709792E+10 0.320780E+10 0.389012E+10 0.00 0.00
June 0.977039E+10 0.194721E+10 0.828760E+10 0.389814E+10 0.438945E+10 0.00 0.00
July 0.962095E+10 0.145671E+10 0.765641E+10 0.335683E+10 0.429958E+10 0.00 0.00
August 0.850568E+10 0.188105E+10 0.692477E+10 0.294448E+10 0.398029E+10 0.00 0.00
September 0.578683E+10 0.263616E+10 0.526267E+10 0.227272E+10 0.298995E+10 0.00 0.00
October 0.271713E+10 0.444316E+10 0.352523E+10 0.124179E+10 0.228344E+10 0.00 0.00
November 0.954953E+09 0.582698E+10 0.202168E+10 0.582575E+09 0.143910E+10 0.00 0.00
December 0.380395E+09 0.869052E+10 0.181103E+10 0.394604E+09 0.141643E+10 0.00 0.00
               
Annual Sum or Average 0.548679E+11 0.558454E+11 0.580911E+11 0.235728E+11 0.345184E+11 0.00 0.00
Minimum of Months 0.380395E+09 0.145671E+10 0.181103E+10 0.394604E+09 0.141643E+10 0.00 0.00
Maximum of Months 0.977039E+10 0.869052E+10 0.828760E+10 0.389814E+10 0.438945E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 13997624.62 0.116203E+11 0.184824E+10 0.00 0.184824E+10 0.00 0.00
February 0.104600E+09 0.984115E+10 0.254351E+10 0.00 0.254351E+10 0.00 0.00
March 0.950273E+09 0.793631E+10 0.341505E+10 0.00 0.341505E+10 0.00 0.00
April 0.205058E+10 0.542768E+10 0.421110E+10 16803962.60 0.419430E+10 0.00 0.00
May 0.369694E+10 0.358958E+10 0.505620E+10 0.214411E+09 0.484178E+10 0.00 0.00
June 0.606085E+10 0.224997E+10 0.588536E+10 0.500992E+09 0.538437E+10 0.00 0.00
July 0.679815E+10 0.162699E+10 0.564143E+10 0.364167E+09 0.527727E+10 0.00 0.00
August 0.554376E+10 0.215785E+10 0.488141E+10 74260037.56 0.480715E+10 0.00 0.00
September 0.309195E+10 0.339252E+10 0.359502E+10 746890.12 0.359428E+10 0.00 0.00
October 0.121503E+10 0.557841E+10 0.277701E+10 0.00 0.277701E+10 0.00 0.00
November 0.320937E+09 0.707012E+10 0.180589E+10 0.00 0.180589E+10 0.00 0.00
December 17882656.37 0.110820E+11 0.172990E+10 0.00 0.172990E+10 0.00 0.00
               
Annual Sum or Average 0.298649E+11 0.715729E+11 0.433901E+11 0.117138E+10 0.422187E+11 0.00 0.00
Minimum of Months 13997624.62 0.162699E+10 0.172990E+10 0.00 0.172990E+10 0.00 0.00
Maximum of Months 0.679815E+10 0.116203E+11 0.588536E+10 0.500992E+09 0.538437E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.798126E+09 0.703993E+10 0.225484E+10 0.727087E+09 0.152775E+10 0.00 0.00
February 0.129095E+10 0.603178E+10 0.298836E+10 0.896733E+09 0.209163E+10 0.00 0.00
March 0.347169E+10 0.487228E+10 0.474766E+10 0.198829E+10 0.275937E+10 0.00 0.00
April 0.540809E+10 0.342440E+10 0.608113E+10 0.268697E+10 0.339416E+10 0.00 0.00
May 0.731505E+10 0.241026E+10 0.704014E+10 0.311423E+10 0.392591E+10 0.00 0.00
June 0.891866E+10 0.151349E+10 0.760902E+10 0.336281E+10 0.424621E+10 0.00 0.00
July 0.955920E+10 0.108836E+10 0.755021E+10 0.332425E+10 0.422596E+10 0.00 0.00
August 0.843347E+10 0.142146E+10 0.681867E+10 0.286211E+10 0.395656E+10 0.00 0.00
September 0.609838E+10 0.215100E+10 0.549127E+10 0.243572E+10 0.305556E+10 0.00 0.00
October 0.325434E+10 0.349775E+10 0.385049E+10 0.159267E+10 0.225783E+10 0.00 0.00
November 0.121100E+10 0.449219E+10 0.211362E+10 0.678023E+09 0.143559E+10 0.00 0.00
December 0.408546E+09 0.695041E+10 0.175829E+10 0.363300E+09 0.139499E+10 0.00 0.00
               
Annual Sum or Average 0.561675E+11 0.448933E+11 0.583037E+11 0.240322E+11 0.342715E+11 0.00 0.00
Minimum of Months 0.408546E+09 0.108836E+10 0.175829E+10 0.363300E+09 0.139499E+10 0.00 0.00
Maximum of Months 0.955920E+10 0.703993E+10 0.760902E+10 0.336281E+10 0.424621E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.602594E+10 0.100187E+11 0.794747E+10 0.463917E+10 0.330830E+10 0.00 0.00
February 0.607970E+10 0.889304E+10 0.819589E+10 0.395199E+10 0.424390E+10 0.00 0.00
March 0.102209E+11 0.746271E+10 0.110754E+11 0.622322E+10 0.485222E+10 0.00 0.00
April 0.858866E+10 0.570325E+10 0.887633E+10 0.354701E+10 0.532932E+10 0.00 0.00
May 0.849810E+10 0.399945E+10 0.802650E+10 0.233123E+10 0.569526E+10 0.00 0.00
June 0.901116E+10 0.248824E+10 0.754758E+10 0.159937E+10 0.594821E+10 0.00 0.00
July 0.105874E+11 0.179035E+10 0.796169E+10 0.193177E+10 0.602992E+10 0.00 0.00
August 0.116900E+11 0.232909E+10 0.893830E+10 0.289802E+10 0.604028E+10 0.00 0.00
September 0.120849E+11 0.356160E+10 0.100573E+11 0.489867E+10 0.515867E+10 0.00 0.00
October 0.102192E+11 0.553599E+10 0.994417E+10 0.568030E+10 0.426387E+10 0.00 0.00
November 0.615437E+10 0.682743E+10 0.689207E+10 0.389081E+10 0.300127E+10 0.00 0.00
December 0.475017E+10 0.987797E+10 0.664566E+10 0.343943E+10 0.320623E+10 0.00 0.00
               
Annual Sum or Average 0.103911E+12 0.684879E+11 0.102108E+12 0.450310E+11 0.570775E+11 0.00 0.00
Minimum of Months 0.475017E+10 0.179035E+10 0.664566E+10 0.159937E+10 0.300127E+10 0.00 0.00
Maximum of Months 0.120849E+11 0.100187E+11 0.110754E+11 0.622322E+10 0.604028E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.477288E+09 0.746025E+10 0.193461E+10 0.454172E+09 0.148044E+10 0.00 0.00
February 0.107929E+10 0.636332E+10 0.283204E+10 0.727856E+09 0.210419E+10 0.00 0.00
March 0.365446E+10 0.514658E+10 0.491430E+10 0.210419E+10 0.281011E+10 0.00 0.00
April 0.516148E+10 0.373484E+10 0.582280E+10 0.238758E+10 0.343522E+10 0.00 0.00
May 0.743512E+10 0.267730E+10 0.709789E+10 0.320779E+10 0.389010E+10 0.00 0.00
June 0.981824E+10 0.176084E+10 0.828757E+10 0.389813E+10 0.438944E+10 0.00 0.00
July 0.970570E+10 0.130509E+10 0.765638E+10 0.335682E+10 0.429956E+10 0.00 0.00
August 0.863250E+10 0.163015E+10 0.692474E+10 0.294447E+10 0.398027E+10 0.00 0.00
September 0.586047E+10 0.236267E+10 0.526265E+10 0.227271E+10 0.298994E+10 0.00 0.00
October 0.291349E+10 0.373879E+10 0.352522E+10 0.124178E+10 0.228343E+10 0.00 0.00
November 0.110030E+10 0.470823E+10 0.202167E+10 0.582573E+09 0.143910E+10 0.00 0.00
December 0.452297E+09 0.722658E+10 0.181103E+10 0.394602E+09 0.141642E+10 0.00 0.00
               
Annual Sum or Average 0.562906E+11 0.481146E+11 0.580909E+11 0.235727E+11 0.345182E+11 0.00 0.00
Minimum of Months 0.452297E+09 0.130509E+10 0.181103E+10 0.394602E+09 0.141642E+10 0.00 0.00
Maximum of Months 0.981824E+10 0.746025E+10 0.828757E+10 0.389813E+10 0.438944E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 26238579.10 0.112817E+11 0.184824E+10 0.00 0.184824E+10 0.00 0.00
February 0.130546E+09 0.953617E+10 0.254351E+10 0.00 0.254351E+10 0.00 0.00
March 0.101610E+10 0.752046E+10 0.341505E+10 0.00 0.341505E+10 0.00 0.00
April 0.216743E+10 0.507774E+10 0.421110E+10 16803962.60 0.419430E+10 0.00 0.00
May 0.377152E+10 0.341298E+10 0.505620E+10 0.214411E+09 0.484178E+10 0.00 0.00
June 0.604031E+10 0.220795E+10 0.588536E+10 0.500992E+09 0.538437E+10 0.00 0.00
July 0.673750E+10 0.162696E+10 0.564143E+10 0.364167E+09 0.527727E+10 0.00 0.00
August 0.551470E+10 0.212421E+10 0.488141E+10 74260037.56 0.480715E+10 0.00 0.00
September 0.313910E+10 0.320975E+10 0.359502E+10 746890.12 0.359428E+10 0.00 0.00
October 0.135052E+10 0.507664E+10 0.277701E+10 0.00 0.277701E+10 0.00 0.00
November 0.396288E+09 0.648194E+10 0.180589E+10 0.00 0.180589E+10 0.00 0.00
December 27072859.48 0.106517E+11 0.172990E+10 0.00 0.172990E+10 0.00 0.00
               
Annual Sum or Average 0.303173E+11 0.682082E+11 0.433901E+11 0.117138E+10 0.422187E+11 0.00 0.00
Minimum of Months 26238579.10 0.162696E+10 0.172990E+10 0.00 0.172990E+10 0.00 0.00
Maximum of Months 0.673750E+10 0.112817E+11 0.588536E+10 0.500992E+09 0.538437E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.822441E+09 0.683365E+10 0.225484E+10 0.727087E+09 0.152775E+10 0.00 0.00
February 0.132727E+10 0.585464E+10 0.298836E+10 0.896733E+09 0.209163E+10 0.00 0.00
March 0.354157E+10 0.461581E+10 0.474766E+10 0.198829E+10 0.275937E+10 0.00 0.00
April 0.547815E+10 0.323538E+10 0.608113E+10 0.268697E+10 0.339416E+10 0.00 0.00
May 0.733154E+10 0.231888E+10 0.704014E+10 0.311423E+10 0.392591E+10 0.00 0.00
June 0.888765E+10 0.149498E+10 0.760902E+10 0.336281E+10 0.424621E+10 0.00 0.00
July 0.951045E+10 0.109413E+10 0.755021E+10 0.332425E+10 0.422596E+10 0.00 0.00
August 0.840141E+10 0.140829E+10 0.681867E+10 0.286211E+10 0.395656E+10 0.00 0.00
September 0.611397E+10 0.206230E+10 0.549127E+10 0.243572E+10 0.305556E+10 0.00 0.00
October 0.335179E+10 0.321664E+10 0.385049E+10 0.159267E+10 0.225783E+10 0.00 0.00
November 0.128216E+10 0.413634E+10 0.211362E+10 0.678023E+09 0.143559E+10 0.00 0.00
December 0.428613E+09 0.668812E+10 0.175829E+10 0.363300E+09 0.139499E+10 0.00 0.00
               
Annual Sum or Average 0.564770E+11 0.429592E+11 0.583037E+11 0.240322E+11 0.342715E+11 0.00 0.00
Minimum of Months 0.428613E+09 0.109413E+10 0.175829E+10 0.363300E+09 0.139499E+10 0.00 0.00
Maximum of Months 0.951045E+10 0.683365E+10 0.760902E+10 0.336281E+10 0.424621E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.609714E+10 0.965580E+10 0.794747E+10 0.463917E+10 0.330830E+10 0.00 0.00
February 0.614636E+10 0.858772E+10 0.819589E+10 0.395199E+10 0.424390E+10 0.00 0.00
March 0.103356E+11 0.702649E+10 0.110754E+11 0.622322E+10 0.485222E+10 0.00 0.00
April 0.868294E+10 0.536434E+10 0.887633E+10 0.354701E+10 0.532932E+10 0.00 0.00
May 0.852980E+10 0.381570E+10 0.802650E+10 0.233123E+10 0.569526E+10 0.00 0.00
June 0.897539E+10 0.243299E+10 0.754758E+10 0.159937E+10 0.594821E+10 0.00 0.00
July 0.105213E+11 0.178347E+10 0.796169E+10 0.193177E+10 0.602992E+10 0.00 0.00
August 0.116449E+11 0.229123E+10 0.893830E+10 0.289802E+10 0.604028E+10 0.00 0.00
September 0.121001E+11 0.339931E+10 0.100573E+11 0.489867E+10 0.515867E+10 0.00 0.00
October 0.103570E+11 0.508630E+10 0.994417E+10 0.568030E+10 0.426387E+10 0.00 0.00
November 0.628577E+10 0.626959E+10 0.689207E+10 0.389081E+10 0.300127E+10 0.00 0.00
December 0.483464E+10 0.944769E+10 0.664566E+10 0.343943E+10 0.320623E+10 0.00 0.00
               
Annual Sum or Average 0.104511E+12 0.651606E+11 0.102108E+12 0.450310E+11 0.570775E+11 0.00 0.00
Minimum of Months 0.483464E+10 0.178347E+10 0.664566E+10 0.159937E+10 0.300127E+10 0.00 0.00
Maximum of Months 0.121001E+11 0.965580E+10 0.110754E+11 0.622322E+10 0.604028E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.491734E+09 0.724247E+10 0.193461E+10 0.454172E+09 0.148044E+10 0.00 0.00
February 0.109535E+10 0.619065E+10 0.283204E+10 0.727856E+09 0.210419E+10 0.00 0.00
March 0.369270E+10 0.489455E+10 0.491430E+10 0.210419E+10 0.281011E+10 0.00 0.00
April 0.520705E+10 0.353633E+10 0.582280E+10 0.238758E+10 0.343522E+10 0.00 0.00
May 0.744969E+10 0.256859E+10 0.709789E+10 0.320779E+10 0.389010E+10 0.00 0.00
June 0.978381E+10 0.172642E+10 0.828757E+10 0.389813E+10 0.438944E+10 0.00 0.00
July 0.965785E+10 0.129708E+10 0.765638E+10 0.335682E+10 0.429956E+10 0.00 0.00
August 0.860343E+10 0.160517E+10 0.692474E+10 0.294447E+10 0.398027E+10 0.00 0.00
September 0.587595E+10 0.226208E+10 0.526265E+10 0.227271E+10 0.298994E+10 0.00 0.00
October 0.297721E+10 0.347454E+10 0.352522E+10 0.124178E+10 0.228343E+10 0.00 0.00
November 0.114556E+10 0.439036E+10 0.202167E+10 0.582573E+09 0.143910E+10 0.00 0.00
December 0.468035E+09 0.697765E+10 0.181103E+10 0.394602E+09 0.141642E+10 0.00 0.00
               
Annual Sum or Average 0.564484E+11 0.461659E+11 0.580909E+11 0.235727E+11 0.345182E+11 0.00 0.00
Minimum of Months 0.468035E+09 0.129708E+10 0.181103E+10 0.394602E+09 0.141642E+10 0.00 0.00
Maximum of Months 0.978381E+10 0.724247E+10 0.828757E+10 0.389813E+10 0.438944E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: GROUNDFLOOR_PLENUM

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: MIDFLOOR_PLENUM

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: TOPFLOOR_PLENUM

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: DATACENTER_MID_ZN_6

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AverageOutdoorConditionsMonthly

For: Environment

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] SITE OUTDOOR AIR WETBULB TEMPERATURE [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] SITE WIND SPEED [m/s] SITE SKY TEMPERATURE [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] SITE RAIN STATUS []
January -3.4 -4.9 -8.7 5.96 -14.4 41.15 62.17 0.00
February -4.2 -5.4 -8.1 6.66 -15.1 65.72 71.39 0.00
March 2.67 0.66 -2.8 5.20 -8.9 69.76 141.76 0.00
April 7.47 4.95 1.92 5.29 -2.7 89.32 159.79 0.00
May 13.73 9.66 5.81 4.79 3.34 93.75 203.34 0.03
June 18.63 14.47 11.49 5.10 8.69 105.42 236.95 0.00
July 22.03 18.19 16.11 4.43 13.39 102.98 214.28 0.00
August 20.69 16.39 13.72 4.23 11.88 99.24 178.64 0.00
September 16.55 13.42 11.22 4.10 7.08 75.66 154.97 0.03
October 9.73 7.36 4.97 4.79 0.13 58.70 104.01 0.00
November 6.03 3.70 0.77 5.87 -3.2 41.19 58.47 0.00
December -2.2 -3.2 -5.3 6.59 -12.0 40.52 44.30 0.00
                 
Annual Sum or Average 9.05 6.33 3.49 5.24 -0.9 73.64 136.19 0.01
Minimum of Months -4.2 -5.4 -8.7 4.10 -15.1 40.52 44.30 0.00
Maximum of Months 22.03 18.19 16.11 6.66 13.39 105.42 236.95 0.03



Table of Contents

Report: OutdoorConditionsMaximumDryBulbMonthly

For: Environment

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] SITE WIND SPEED {AT MAX/MIN} [m/s] SITE SKY TEMPERATURE {AT MAX/MIN} [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2]
January 11.70 11-JAN-15:00 10.14 8.90 13.40 7.15 65.50 1.00
February 12.80 22-FEB-17:00 6.18 -2.2 14.90 3.48 0.00 0.00
March 26.10 15-MAR-13:00 16.06 9.40 6.70 14.65 249.50 400.00
April 21.10 08-APR-12:00 13.43 7.80 8.20 11.46 330.00 283.50
May 26.10 10-MAY-13:00 17.84 13.30 5.20 13.35 258.50 457.00
June 30.60 12-JUN-13:00 20.23 15.00 8.20 17.93 252.00 572.00
July 31.70 21-JUL-13:00 21.73 17.20 5.20 22.47 330.00 231.00
August 30.60 10-AUG-13:00 20.24 15.00 5.70 19.70 220.50 635.00
September 27.20 16-SEP-13:09 19.53 15.68 8.80 17.30 207.00 564.67
October 22.20 11-OCT-12:00 14.14 8.30 6.20 6.95 121.00 665.00
November 19.40 05-NOV-13:00 13.85 10.00 12.40 14.84 133.00 3.50
December 15.00 01-DEC-10:00 12.41 10.60 12.90 10.69 56.50 11.50
                 
Annual Sum or Average                
Minimum of Months 11.70   6.18 -2.2 5.20 3.48 0.00 0.00
Maximum of Months 31.70   21.73 17.20 14.90 22.47 330.00 665.00



Table of Contents

Report: OutdoorConditionsMinimumDryBulbMonthly

For: Environment

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] SITE WIND SPEED {AT MAX/MIN} [m/s] SITE SKY TEMPERATURE {AT MAX/MIN} [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2]
January -13.9 31-JAN-01:00 -14.5 -17.2 1.50 -25.9 0.00 0.00
February -16.7 07-FEB-06:00 -17.3 -20.6 6.20 -35.1 0.00 0.00
March -13.3 07-MAR-05:19 -13.9 -16.7 2.43 -32.2 0.00 0.00
April -4.4 17-APR-05:00 -5.4 -7.8 2.10 -20.5 35.00 151.50
May 1.70 01-MAY-04:00 0.96 0.00 0.00 -14.2 0.00 0.00
June 6.70 04-JUN-04:00 5.40 3.90 2.10 -7.3 20.00 104.00
July 11.70 03-JUL-03:00 11.07 10.60 2.10 -1.2 0.00 0.00
August 11.10 01-AUG-04:00 10.75 10.60 2.10 -0.8 0.00 0.00
September 6.10 05-SEP-05:00 5.59 5.00 2.10 -6.2 24.50 41.00
October -2.8 17-OCT-04:10 -3.2 -4.0 2.18 -19.4 0.00 0.00
November -3.9 24-NOV-05:00 -4.5 -5.6 2.10 -18.1 0.00 0.00
December -18.9 11-DEC-05:00 -19.4 -23.3 2.10 -35.1 0.00 0.00
                 
Annual Sum or Average                
Minimum of Months -18.9   -19.4 -23.3 0.00 -35.1 0.00 0.00
Maximum of Months 11.70   11.07 10.60 6.20 -0.8 35.00 151.50



Table of Contents

Report: OutdoorConditionsMaximumWetBulbMonthly

For: Environment

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

SITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] SITE WIND SPEED {AT MAX/MIN} [m/s] SITE SKY TEMPERATURE {AT MAX/MIN} [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2]
January 10.21 11-JAN-17:00 11.10 9.40 10.30 6.55 0.00 0.00
February 6.89 01-FEB-03:00 7.20 6.70 3.60 2.22 0.00 0.00
March 17.83 14-MAR-12:00 25.00 13.90 6.20 14.10 197.00 562.50
April 13.78 08-APR-13:00 20.60 8.90 10.30 9.72 268.50 325.50
May 18.19 10-MAY-14:00 26.10 13.90 5.20 16.85 273.00 238.00
June 23.75 27-JUN-12:00 30.60 21.10 9.30 21.09 304.00 606.00
July 24.79 21-JUL-01:00 28.90 23.30 8.80 27.46 0.00 0.00
August 23.42 13-AUG-15:00 29.40 21.10 9.80 19.87 212.00 276.00
September 21.17 15-SEP-11:00 26.10 18.90 3.60 16.30 204.00 464.50
October 15.23 12-OCT-14:00 18.30 13.30 10.30 9.13 148.00 367.50
November 13.96 05-NOV-14:00 18.30 11.10 11.30 14.10 72.00 6.00
December 12.41 01-DEC-10:00 15.00 10.60 12.90 10.69 56.50 11.50
                 
Annual Sum or Average                
Minimum of Months 6.89   7.20 6.70 3.60 2.22 0.00 0.00
Maximum of Months 24.79   30.60 23.30 12.90 27.46 304.00 606.00



Table of Contents

Report: OutdoorConditionsMaximumDewPointMonthly

For: Environment

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

SITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] SITE WIND SPEED {AT MAX/MIN} [m/s] SITE SKY TEMPERATURE {AT MAX/MIN} [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2]
January 9.40 11-JAN-13:00 10.00 9.66 12.90 5.54 95.50 2.00
February 6.70 01-FEB-04:10 7.20 6.89 3.52 2.22 0.00 0.00
March 15.00 14-MAR-10:20 20.33 16.97 4.80 10.50 159.17 592.83
April 11.10 08-APR-21:00 13.90 12.23 12.90 9.72 0.00 0.00
May 15.60 17-MAY-12:00 16.70 15.97 6.70 13.54 184.00 0.00
June 21.70 27-JUN-14:00 25.60 22.78 8.20 16.85 255.50 530.00
July 23.30 20-JUL-20:00 25.60 24.03 4.60 24.16 0.00 0.00
August 21.70 14-AUG-03:20 23.70 22.19 5.00 21.90 0.00 0.00
September 20.00 15-SEP-18:00 21.70 20.51 0.00 19.52 0.00 0.00
October 14.40 01-OCT-07:19 14.60 14.50 3.77 10.56 67.50 30.17
November 11.70 05-NOV-15:00 12.80 12.14 7.20 8.74 28.00 4.50
December 11.10 01-DEC-12:00 13.90 12.22 10.30 6.35 158.00 84.50
                 
Annual Sum or Average                
Minimum of Months 6.70   7.20 6.89 0.00 2.22 0.00 0.00
Maximum of Months 23.30   25.60 24.03 12.90 24.16 255.50 592.83



Table of Contents

Report: OutdoorGroundConditionsMonthly

For: Environment

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

SITE GROUND TEMPERATURE [C] SITE SURFACE GROUND TEMPERATURE [C] SITE DEEP GROUND TEMPERATURE [C] SITE MAINS WATER TEMPERATURE [C] SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] SITE SNOW ON GROUND STATUS []
January 18.00 13.00 16.00 7.32 12.49 0.00
February 18.00 13.00 16.00 6.57 19.26 0.00
March 18.00 13.00 16.00 7.29 28.63 0.00
April 18.00 13.00 16.00 9.34 37.44 0.00
May 18.00 13.00 16.00 12.19 46.60 0.00
June 18.00 13.00 16.00 15.07 54.01 0.00
July 18.00 13.00 16.00 17.20 50.29 0.00
August 18.00 13.00 16.00 18.01 43.20 0.00
September 18.00 13.00 16.00 17.27 32.93 0.00
October 18.00 13.00 16.00 15.18 21.28 0.00
November 18.00 13.00 16.00 12.32 12.54 0.00
December 18.00 13.00 16.00 9.45 10.96 0.00
             
Annual Sum or Average 18.00 13.00 16.00 12.30 30.86 0.00
Minimum of Months 18.00 13.00 16.00 6.57 10.96 0.00
Maximum of Months 18.00 13.00 16.00 18.01 54.01 0.00



Table of Contents

Report: WaterHeaterReportMonthly

For: SWHSYS1 WATER HEATER

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] WATER HEATER BURNER HEATING ENERGY [] WATER HEATER GAS CONSUMPTION [] WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] WATER HEATER LOSS DEMAND ENERGY [] WATER HEATER HEAT LOSS ENERGY [J] WATER HEATER TANK TEMPERATURE [C] WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] WATER HEATER SOURCE ENERGY []
January 0.421451E+11 -0.411088E+11 0.00 0.00 744.00 0.00 -0.103631E+10 58.97 0.00 0.00
February 0.388341E+11 -0.378965E+11 0.00 0.00 672.00 0.00 -937636926.2 58.99 0.00 0.00
March 0.450012E+11 -0.439703E+11 0.00 0.00 744.00 0.00 -0.103088E+10 58.98 0.00 0.00
April 0.392850E+11 -0.382940E+11 0.00 0.00 720.00 0.00 -990963571.5 58.98 0.00 0.00
May 0.395995E+11 -0.385752E+11 0.00 0.00 744.00 0.00 -0.102427E+10 58.97 0.00 0.00
June 0.368575E+11 -0.358672E+11 0.00 0.00 720.00 0.00 -990281769.5 58.98 0.00 0.00
July 0.334563E+11 -0.324385E+11 0.00 0.00 744.00 0.00 -0.101777E+10 58.98 0.00 0.00
August 0.358697E+11 -0.348481E+11 0.00 0.00 744.00 0.00 -0.102161E+10 58.98 0.00 0.00
September 0.331732E+11 -0.321865E+11 0.00 0.00 720.00 0.00 -986673766.5 58.97 0.00 0.00
October 0.358864E+11 -0.348666E+11 0.00 0.00 744.00 0.00 -0.101979E+10 58.97 0.00 0.00
November 0.374150E+11 -0.364271E+11 0.00 0.00 720.00 0.00 -987924620.5 58.98 0.00 0.00
December 0.394869E+11 -0.384605E+11 0.00 0.00 744.00 0.00 -0.102638E+10 58.97 0.00 0.00
                     
Annual Sum or Average 0.457010E+12 -0.444939E+12 0.00 0.00 8760.00 0.00 -0.120705E+11 58.98 0.00 0.00
Minimum of Months 0.331732E+11 -0.439703E+11 0.00 0.00 672.00 0.00 -0.103631E+10 58.97 0.00 0.00
Maximum of Months 0.450012E+11 -0.321865E+11 0.00 0.00 744.00 0.00 -937636926.2 58.99 0.00 0.00



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_BOT_ZN_1_DAYLCTRL

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 255.17 0.50 0.48 01-JAN-09:20 4678.29 33.10 240.17 253.17 3728.53 34.06 244.17 226.50
February 262.50 0.50 0.48 01-FEB-09:50 5881.90 33.26 252.67 258.00 1891.16 26.42 229.83 235.50
March 339.33 0.50 0.48 01-MAR-07:40 8389.80 30.63 272.00 329.00 1554.75 22.79 241.33 296.50
April 371.17 0.51 0.48 01-APR-07:10 2230.51 20.63 165.00 349.17 1232.05 22.01 260.00 316.83
May 332.17 0.51 0.48 01-MAY-06:40 2040.14 20.66 136.67 389.50 1186.18 22.10 264.67 343.50
June 430.67 0.51 0.48 01-JUN-06:19 1844.73 20.44 162.67 397.17 1050.06 21.85 297.67 359.33
July 439.00 0.51 0.48 01-JUL-06:30 1929.83 20.49 180.00 405.67 1082.35 21.90 292.17 361.67
August 406.00 0.51 0.48 01-AUG-06:19 2274.62 20.98 219.33 380.67 1245.08 22.38 300.67 342.17
September 289.17 0.50 0.48 01-SEP-07:40 3214.42 22.42 186.00 327.83 1620.93 23.02 262.50 295.33
October 314.33 0.50 0.48 01-OCT-07:19 6790.00 32.80 284.17 300.33 1648.47 23.49 238.00 279.67
November 258.33 0.51 0.48 01-NOV-07:49 4410.79 32.94 244.00 243.50 1765.83 28.61 234.50 220.33
December 230.67 0.50 0.48 01-DEC-08:09 3958.09 32.19 220.33 241.17 3058.34 33.42 228.33 211.17
                         
Annual Sum or Average 3928.50 0.51     3760.13 25.74 2563.00 3875.17 1631.18 24.47 3093.83 3488.50
Minimum of Months 230.67 0.50 0.48   1844.73 20.44 136.67 241.17 1050.06 21.85 228.33 211.17
Maximum of Months 439.00 0.51 0.48   8389.80 33.26 284.17 405.67 3728.53 34.06 300.67 361.67



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_BOT_ZN_2_DAYLCTRL

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 255.17 0.51 0.48 01-JAN-09:20 1635.61 23.24 101.50 240.83 808.32 23.25 142.83 197.33
February 262.50 0.51 0.48 01-FEB-09:50 2257.31 24.23 134.50 251.33 1159.03 24.43 181.50 221.83
March 339.33 0.50 0.48 01-MAR-07:19 3061.78 24.87 152.67 324.00 1324.00 24.19 203.83 291.67
April 371.17 0.51 0.48 01-APR-06:30 3311.38 24.31 146.67 353.83 1851.13 24.81 228.50 322.50
May 332.17 0.50 0.48 01-MAY-05:30 4393.18 25.01 111.67 397.83 1856.94 24.30 222.50 354.83
June 430.67 0.50 0.48 01-JUN-05:00 3999.69 24.26 146.33 406.67 1752.30 24.03 243.50 378.17
July 439.00 0.50 0.48 01-JUL-05:10 3788.21 24.46 151.33 414.00 1658.52 24.03 260.17 378.50
August 406.00 0.50 0.48 01-AUG-05:49 3521.50 24.73 161.50 383.83 1546.34 24.25 266.00 351.50
September 289.17 0.50 0.48 01-SEP-07:40 3557.08 25.25 131.83 329.50 1938.29 25.49 215.83 294.67
October 314.33 0.51 0.48 01-OCT-07:10 2284.71 24.14 132.50 293.50 1206.60 24.31 193.67 260.83
November 258.33 0.53 0.48 01-NOV-07:40 1645.10 23.49 109.50 234.50 892.50 23.66 143.17 187.17
December 230.67 0.51 0.48 01-DEC-07:00 1417.68 23.07 94.00 230.50 705.38 23.27 133.50 181.67
                         
Annual Sum or Average 3928.50 0.51     3067.64 24.33 1574.00 3860.33 1452.78 24.20 2435.00 3420.67
Minimum of Months 230.67 0.50 0.48   1417.68 23.07 94.00 230.50 705.38 23.25 133.50 181.67
Maximum of Months 439.00 0.53 0.48   4393.18 25.25 161.50 414.00 1938.29 25.49 266.00 378.50



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_BOT_ZN_3_DAYLCTRL

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 255.17 0.53 0.48 01-JAN-10:00 715.21 17.89 0.00 226.00 398.05 19.30 5.00 152.50
February 262.50 0.52 0.48 01-FEB-12:39 939.35 18.85 0.00 245.00 520.41 20.20 73.00 201.00
March 339.33 0.51 0.48 01-MAR-08:20 1000.19 19.34 0.00 319.33 583.72 20.77 112.00 272.67
April 371.17 0.51 0.48 01-APR-07:10 1158.61 19.82 15.67 353.67 676.09 21.15 192.83 321.00
May 332.17 0.49 0.48 01-MAY-06:10 1390.69 21.86 104.17 404.83 835.74 23.05 269.50 367.50
June 430.67 0.50 0.48 01-JUN-06:10 1547.12 23.17 185.83 416.67 870.46 22.34 322.00 388.00
July 439.00 0.50 0.48 01-JUL-05:30 1472.37 22.86 179.50 421.17 855.47 23.15 329.00 391.33
August 406.00 0.50 0.48 01-AUG-05:00 1306.23 20.52 70.00 391.17 771.46 21.86 284.00 357.33
September 289.17 0.51 0.48 01-SEP-07:40 1098.51 20.04 3.33 325.33 675.51 21.47 167.17 279.33
October 314.33 0.52 0.48 01-OCT-07:00 875.66 18.62 0.00 285.00 501.82 20.05 53.33 234.50
November 258.33 0.55 0.48 01-NOV-08:30 693.49 17.33 0.00 222.50 384.23 18.67 4.00 139.50
December 230.67 0.54 0.48 01-DEC-12:09 718.36 17.81 0.00 214.83 390.97 19.15 7.00 131.50
                         
Annual Sum or Average 3928.50 0.51     1130.51 20.18 558.50 3825.50 654.44 21.18 1818.83 3236.17
Minimum of Months 230.67 0.49 0.48   693.49 17.33 0.00 214.83 384.23 18.67 4.00 131.50
Maximum of Months 439.00 0.55 0.48   1547.12 23.17 185.83 421.17 870.46 23.15 329.00 391.33



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_BOT_ZN_4_DAYLCTRL

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 255.17 0.51 0.48 01-JAN-10:20 1534.79 23.51 110.17 241.00 827.09 23.84 150.50 196.67
February 262.50 0.51 0.48 01-FEB-10:30 2109.93 24.06 132.83 251.00 1106.83 24.41 184.33 222.33
March 339.33 0.50 0.48 01-MAR-08:20 3008.13 24.70 149.00 326.17 1691.18 25.12 211.17 294.33
April 371.17 0.51 0.48 01-APR-07:30 3521.47 23.44 137.33 351.00 1484.27 22.99 206.00 319.17
May 332.17 0.50 0.48 01-MAY-06:49 3786.44 21.37 54.83 396.50 2072.42 21.43 192.67 359.67
June 430.67 0.50 0.48 01-JUN-06:40 3986.40 21.17 68.83 405.83 1707.94 21.41 229.17 374.17
July 439.00 0.50 0.48 01-JUL-06:30 3563.12 21.20 82.00 411.00 1610.43 21.54 235.67 377.67
August 406.00 0.50 0.48 01-AUG-06:40 3340.04 22.74 127.00 386.50 1796.42 23.37 249.50 354.17
September 289.17 0.50 0.48 01-SEP-07:00 3687.78 24.99 123.33 327.00 1596.43 24.17 209.83 295.17
October 314.33 0.51 0.48 01-OCT-08:09 2144.69 23.94 132.00 291.83 1125.61 24.21 191.17 260.83
November 258.33 0.53 0.48 01-NOV-08:30 1573.83 23.07 107.17 232.50 829.91 23.23 140.83 191.00
December 230.67 0.52 0.48 01-DEC-11:50 1478.03 23.03 96.83 226.67 774.11 23.42 136.00 180.00
                         
Annual Sum or Average 3928.50 0.51     2967.07 22.95 1321.33 3847.00 1449.67 23.12 2336.83 3425.17
Minimum of Months 230.67 0.50 0.48   1478.03 21.17 54.83 226.67 774.11 21.41 136.00 180.00
Maximum of Months 439.00 0.53 0.48   3986.40 24.99 149.00 411.00 2072.42 25.12 249.50 377.67



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_MID_ZN_1_DAYLCTRL

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 255.17 0.50 0.48 01-JAN-09:09 4693.60 32.28 233.83 253.17 3821.17 33.28 232.67 228.33
February 262.50 0.50 0.48 01-FEB-09:50 5902.56 32.55 242.67 258.00 2047.07 24.44 107.00 240.50
March 339.33 0.50 0.48 01-MAR-07:30 8438.43 28.77 231.50 329.33 1676.51 18.26 13.33 300.33
April 371.17 0.51 0.48 01-APR-06:00 2266.04 14.29 0.00 349.50 1317.06 17.73 3.83 320.33
May 332.17 0.51 0.48 01-MAY-06:40 2081.07 14.61 0.00 389.83 1269.27 18.14 0.00 349.33
June 430.67 0.51 0.48 01-JUN-06:19 1875.89 14.48 0.00 397.33 1120.74 17.94 0.00 362.33
July 439.00 0.51 0.48 01-JUL-06:19 1960.76 14.43 0.00 405.67 1154.91 17.89 1.33 365.17
August 406.00 0.51 0.48 01-AUG-06:19 2307.18 14.81 0.00 380.83 1328.53 18.26 1.83 346.50
September 289.17 0.50 0.48 01-SEP-07:40 3262.58 16.45 17.00 327.83 1735.58 18.78 11.00 299.83
October 314.33 0.50 0.48 01-OCT-07:19 6824.08 31.77 270.67 300.50 1846.63 19.00 26.33 281.67
November 258.33 0.51 0.48 01-NOV-07:49 4422.23 32.24 238.50 243.33 2147.97 27.67 161.33 222.67
December 230.67 0.50 0.48 01-DEC-08:09 3955.83 30.86 204.50 241.17 3143.45 32.75 216.67 214.67
                         
Annual Sum or Average 3928.50 0.50     3790.65 21.76 1438.67 3876.50 1752.10 21.08 775.33 3531.67
Minimum of Months 230.67 0.50 0.48   1875.89 14.29 0.00 241.17 1120.74 17.73 0.00 214.67
Maximum of Months 439.00 0.51 0.48   8438.43 32.55 270.67 405.67 3821.17 33.28 232.67 365.17



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_MID_ZN_2_DAYLCTRL

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 255.17 0.51 0.48 01-JAN-09:09 1662.86 20.42 70.67 242.00 847.66 21.11 70.50 201.67
February 262.50 0.51 0.48 01-FEB-09:50 2296.35 21.56 83.17 252.00 1210.69 22.36 74.33 224.83
March 339.33 0.50 0.48 01-MAR-07:19 3115.68 22.21 115.83 324.17 1388.63 21.86 61.67 294.83
April 371.17 0.51 0.48 01-APR-06:30 3346.09 20.58 104.17 354.17 1926.44 22.53 87.83 326.83
May 332.17 0.50 0.48 01-MAY-05:30 4450.03 22.07 103.50 398.67 1947.84 21.69 56.17 358.83
June 430.67 0.50 0.48 01-JUN-05:00 4050.73 21.32 133.17 407.67 1836.16 21.45 76.00 380.50
July 439.00 0.50 0.48 01-JUL-04:00 3838.23 21.55 136.00 414.67 1741.17 21.47 75.67 382.17
August 406.00 0.50 0.48 01-AUG-05:49 3576.84 21.80 123.00 384.17 1624.98 21.70 67.67 354.67
September 289.17 0.50 0.48 01-SEP-07:40 3622.56 22.42 86.50 330.17 2018.80 23.24 64.50 297.33
October 314.33 0.51 0.48 01-OCT-06:00 2328.11 21.37 92.33 294.33 1261.74 22.16 66.83 264.50
November 258.33 0.52 0.48 01-NOV-07:40 1671.27 20.81 87.33 235.00 929.82 21.71 77.83 192.83
December 230.67 0.51 0.48 01-DEC-07:00 1437.25 19.70 60.00 231.17 739.93 21.23 62.50 186.50
                         
Annual Sum or Average 3928.50 0.51     3112.83 21.38 1195.67 3868.17 1520.55 21.87 841.50 3465.50
Minimum of Months 230.67 0.50 0.48   1437.25 19.70 60.00 231.17 739.93 21.11 56.17 186.50
Maximum of Months 439.00 0.52 0.48   4450.03 22.42 136.00 414.67 2018.80 23.24 87.83 382.17



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_MID_ZN_3_DAYLCTRL

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 255.17 0.53 0.48 01-JAN-10:39 723.22 11.71 0.00 226.50 422.48 15.22 0.00 160.67
February 262.50 0.52 0.48 01-FEB-10:30 951.89 13.01 0.00 245.00 552.68 16.37 0.00 208.00
March 339.33 0.51 0.48 01-MAR-08:20 1015.51 13.70 0.00 320.00 621.06 17.15 0.00 277.83
April 371.17 0.51 0.48 01-APR-06:00 1177.95 14.24 0.00 354.17 719.57 17.65 0.17 327.33
May 332.17 0.49 0.48 01-MAY-05:00 1419.39 16.74 26.17 404.83 894.41 20.03 32.17 371.00
June 430.67 0.49 0.48 01-JUN-06:10 1576.11 18.50 74.50 416.83 958.85 20.13 47.50 394.50
July 439.00 0.50 0.48 01-JUL-05:30 1498.88 18.13 71.17 421.67 910.44 19.88 49.67 394.33
August 406.00 0.50 0.48 01-AUG-05:00 1328.87 14.96 0.00 391.33 820.92 18.42 8.50 359.33
September 289.17 0.50 0.48 01-SEP-07:40 1118.30 14.90 0.00 325.67 719.71 18.35 0.00 285.33
October 314.33 0.52 0.48 01-OCT-07:49 887.73 12.81 0.00 285.33 533.39 16.25 0.00 241.50
November 258.33 0.55 0.48 01-NOV-08:20 701.29 11.22 0.00 222.67 407.87 14.60 0.00 149.67
December 230.67 0.53 0.48 01-DEC-11:00 726.32 11.58 0.00 215.33 414.81 15.03 0.00 144.67
                         
Annual Sum or Average 3928.50 0.51     1149.33 14.71 171.83 3829.33 700.15 17.75 138.00 3314.17
Minimum of Months 230.67 0.49 0.48   701.29 11.22 0.00 215.33 407.87 14.60 0.00 144.67
Maximum of Months 439.00 0.55 0.48   1576.11 18.50 74.50 421.67 958.85 20.13 49.67 394.50



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_MID_ZN_4_DAYLCTRL

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 255.17 0.51 0.48 01-JAN-10:09 1559.10 21.06 86.17 241.67 861.99 21.98 79.17 201.33
February 262.50 0.51 0.48 01-FEB-10:20 2147.41 21.38 81.67 251.83 1156.67 22.35 74.67 224.67
March 339.33 0.50 0.48 01-MAR-08:20 3038.51 21.20 102.17 326.50 1758.33 23.00 86.33 297.50
April 371.17 0.51 0.48 01-APR-07:19 3576.49 20.37 104.33 351.17 1556.16 20.29 49.67 321.83
May 332.17 0.50 0.48 01-MAY-06:40 3827.73 17.43 43.00 396.50 2163.47 18.06 0.00 363.00
June 430.67 0.50 0.48 01-JUN-06:30 4038.39 17.19 52.50 406.50 1796.49 18.03 0.00 378.17
July 439.00 0.50 0.48 01-JUL-06:19 3613.53 17.27 54.67 411.83 1692.29 18.25 3.67 381.17
August 406.00 0.50 0.48 01-AUG-06:40 3391.28 19.35 85.50 387.00 1874.75 20.68 53.83 357.00
September 289.17 0.50 0.48 01-SEP-07:00 3713.56 22.10 84.67 327.00 1676.21 21.63 42.00 297.83
October 314.33 0.51 0.48 01-OCT-08:09 2184.04 21.11 90.33 292.50 1177.59 22.03 65.00 263.33
November 258.33 0.53 0.48 01-NOV-08:30 1598.92 20.54 87.33 233.50 865.57 21.27 73.17 194.67
December 230.67 0.51 0.48 01-DEC-11:50 1502.35 20.37 64.67 228.00 808.96 21.43 67.50 184.33
                         
Annual Sum or Average 3928.50 0.51     3007.22 19.70 937.00 3854.00 1516.94 20.52 595.00 3464.83
Minimum of Months 230.67 0.50 0.48   1502.35 17.19 43.00 228.00 808.96 18.03 0.00 184.33
Maximum of Months 439.00 0.53 0.48   4038.39 22.10 104.33 411.83 2163.47 23.00 86.33 381.17



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_TOP_ZN_1_DAYLCTRL

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 255.17 0.50 0.48 01-JAN-09:09 4695.47 32.27 233.83 253.17 3823.52 33.28 232.67 228.83
February 262.50 0.50 0.48 01-FEB-09:50 5905.75 32.55 242.67 258.17 2050.14 24.43 107.00 240.67
March 339.33 0.50 0.48 01-MAR-07:30 8441.99 28.76 231.33 329.50 1678.97 18.24 13.33 300.33
April 371.17 0.51 0.48 01-APR-06:00 2269.42 14.26 0.00 349.50 1319.12 17.72 3.67 320.50
May 332.17 0.51 0.48 01-MAY-06:40 2083.78 14.58 0.00 389.83 1271.00 18.13 0.00 349.33
June 430.67 0.51 0.48 01-JUN-06:19 1878.42 14.46 0.00 397.50 1122.35 17.93 0.00 362.33
July 439.00 0.51 0.48 01-JUL-06:19 1963.53 14.40 0.00 405.67 1156.63 17.87 1.00 365.50
August 406.00 0.51 0.48 01-AUG-06:19 2310.65 14.78 0.00 380.83 1330.64 18.24 1.67 346.50
September 289.17 0.50 0.48 01-SEP-07:40 3266.52 16.43 17.00 327.83 1738.18 18.76 10.50 300.17
October 314.33 0.50 0.48 01-OCT-07:19 6827.05 31.76 270.50 300.67 1947.79 19.26 30.17 281.67
November 258.33 0.51 0.48 01-NOV-07:49 4424.29 32.23 238.33 243.50 2432.26 29.38 187.17 222.83
December 230.67 0.50 0.48 01-DEC-08:09 3957.66 30.85 204.50 241.17 3145.80 32.75 216.67 214.67
                         
Annual Sum or Average 3928.50 0.50     3793.56 21.74 1438.17 3877.33 1780.71 21.20 803.83 3533.33
Minimum of Months 230.67 0.50 0.48   1878.42 14.26 0.00 241.17 1122.35 17.72 0.00 214.67
Maximum of Months 439.00 0.51 0.48   8441.99 32.55 270.50 405.67 3823.52 33.28 232.67 365.50



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_TOP_ZN_2_DAYLCTRL

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 255.17 0.51 0.48 01-JAN-09:09 1664.25 20.39 70.67 242.00 848.87 21.10 70.00 202.17
February 262.50 0.51 0.48 01-FEB-09:50 2298.35 21.54 83.17 252.00 1212.33 22.35 74.00 225.33
March 339.33 0.50 0.48 01-MAR-07:19 3085.88 21.20 103.83 324.00 1390.21 21.84 61.67 295.17
April 371.17 0.51 0.48 01-APR-06:30 3348.20 20.55 104.17 354.17 1928.19 22.52 87.83 327.00
May 332.17 0.50 0.48 01-MAY-05:30 4452.13 22.04 103.50 398.67 1949.69 21.68 56.17 359.00
June 430.67 0.50 0.48 01-JUN-05:00 4052.97 21.30 133.17 407.83 1838.02 21.44 76.00 380.67
July 439.00 0.50 0.48 01-JUL-04:00 3840.43 21.52 136.00 415.00 1743.00 21.46 75.67 382.33
August 406.00 0.50 0.48 01-AUG-05:49 3579.13 21.78 123.00 384.33 1626.90 21.68 67.67 354.83
September 289.17 0.50 0.48 01-SEP-07:40 3624.45 22.39 86.50 330.17 2020.70 23.23 64.33 297.50
October 314.33 0.51 0.48 01-OCT-06:00 2329.76 21.34 92.33 294.33 1263.17 22.15 66.83 264.67
November 258.33 0.52 0.48 01-NOV-07:40 1672.65 20.78 87.33 235.00 930.97 21.70 77.33 193.33
December 230.67 0.51 0.48 01-DEC-07:00 1438.72 19.68 60.00 231.17 741.12 21.22 62.50 187.00
                         
Annual Sum or Average 3928.50 0.51     3112.03 21.27 1183.67 3868.67 1522.21 21.85 840.00 3469.00
Minimum of Months 230.67 0.50 0.48   1438.72 19.68 60.00 231.17 741.12 21.10 56.17 187.00
Maximum of Months 439.00 0.52 0.48   4452.13 22.39 136.00 415.00 2020.70 23.23 87.83 382.33



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_TOP_ZN_3_DAYLCTRL

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 255.17 0.53 0.48 01-JAN-10:39 724.13 11.68 0.00 226.83 423.16 15.21 0.00 161.00
February 262.50 0.52 0.48 01-FEB-10:30 953.13 12.98 0.00 245.17 553.58 16.35 0.00 208.33
March 339.33 0.51 0.48 01-MAR-08:20 1016.63 13.67 0.00 320.00 621.94 17.14 0.00 278.33
April 371.17 0.51 0.48 01-APR-06:00 1179.29 14.21 0.00 354.17 720.58 17.63 0.17 327.50
May 332.17 0.49 0.48 01-MAY-05:00 1420.57 16.71 26.17 404.83 895.47 20.02 31.83 371.33
June 430.67 0.49 0.48 01-JUN-06:10 1577.63 18.47 74.50 416.83 960.09 20.11 46.50 394.50
July 439.00 0.50 0.48 01-JUL-05:30 1500.39 18.10 71.17 421.67 911.65 19.87 49.33 394.33
August 406.00 0.50 0.48 01-AUG-05:00 1330.28 14.93 0.00 391.33 822.04 18.41 7.50 359.33
September 289.17 0.50 0.48 01-SEP-07:40 1119.21 14.87 0.00 325.67 720.60 18.33 0.00 285.50
October 314.33 0.52 0.48 01-OCT-07:49 888.76 12.78 0.00 285.33 534.18 16.24 0.00 241.67
November 258.33 0.55 0.48 01-NOV-08:20 702.20 11.20 0.00 222.83 408.53 14.59 0.00 150.50
December 230.67 0.53 0.48 01-DEC-11:00 727.30 11.55 0.00 215.50 415.50 15.01 0.00 145.00
                         
Annual Sum or Average 3928.50 0.51     1150.54 14.69 171.83 3830.17 701.12 17.74 135.33 3317.33
Minimum of Months 230.67 0.49 0.48   702.20 11.20 0.00 215.50 408.53 14.59 0.00 145.00
Maximum of Months 439.00 0.55 0.48   1577.63 18.47 74.50 421.67 960.09 20.11 49.33 394.50



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_TOP_ZN_4_DAYLCTRL

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 255.17 0.51 0.48 01-JAN-10:09 1560.49 21.03 86.17 241.67 863.15 21.97 78.83 201.50
February 262.50 0.51 0.48 01-FEB-10:20 2149.39 21.35 81.67 252.00 1158.31 22.34 74.50 224.83
March 339.33 0.50 0.48 01-MAR-08:20 3040.36 21.17 102.17 326.67 1759.94 22.98 86.17 297.50
April 371.17 0.51 0.48 01-APR-07:19 3578.64 20.35 104.33 351.33 1557.92 20.27 49.67 322.00
May 332.17 0.50 0.48 01-MAY-06:40 3829.73 17.40 43.00 396.50 2165.28 18.05 0.00 363.33
June 430.67 0.50 0.48 01-JUN-06:30 4040.61 17.15 52.50 406.50 1798.44 18.02 0.00 378.33
July 439.00 0.50 0.48 01-JUL-06:19 3615.84 17.24 54.67 412.00 1694.19 18.23 3.67 381.33
August 406.00 0.50 0.48 01-AUG-06:40 3393.67 19.32 85.50 387.17 1876.72 20.67 53.83 357.00
September 289.17 0.50 0.48 01-SEP-07:00 3715.40 22.08 84.67 327.00 1677.98 21.62 42.00 297.83
October 314.33 0.51 0.48 01-OCT-08:09 2185.75 21.09 90.33 292.50 1179.05 22.02 65.00 264.00
November 258.33 0.53 0.48 01-NOV-08:30 1600.30 20.51 87.33 233.50 866.71 21.26 72.83 194.83
December 230.67 0.51 0.48 01-DEC-11:50 1503.82 20.35 64.67 228.00 810.16 21.42 67.50 184.67
                         
Annual Sum or Average 3928.50 0.51     3009.17 19.67 937.00 3854.83 1518.60 20.50 594.00 3467.17
Minimum of Months 230.67 0.50 0.48   1503.82 17.15 43.00 228.00 810.16 18.02 0.00 184.67
Maximum of Months 439.00 0.53 0.48   4040.61 22.08 104.33 412.00 2165.28 22.98 86.17 381.33



Table of Contents

Report: CoilReportMonthly

For: VAV_BOT WITH REHEAT HEATING COIL

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.150698E+10 63056.68 13-JAN-07:10 0.00 0.00 0.00 0.00 0.00
February 0.223077E+10 77905.93 21-FEB-07:10 0.00 0.00 0.00 0.00 0.00
March 0.281895E+10 72052.18 06-MAR-07:10 0.00 0.00 0.00 0.00 0.00
April 0.571655E+09 49880.17 17-APR-06:10 0.00 0.00 0.00 0.00 0.00
May 0.132846E+09 20882.42 01-MAY-06:40 0.00 0.00 0.00 0.00 0.00
June 1029605.95 890.69 10-JUN-06:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 32193965.40 16905.70 30-SEP-06:10 0.00 0.00 0.00 0.00 0.00
October 0.461959E+09 47055.23 17-OCT-06:10 0.00 0.00 0.00 0.00 0.00
November 0.114651E+10 47011.56 24-NOV-07:10 0.00 0.00 0.00 0.00 0.00
December 0.380994E+10 76081.61 28-DEC-07:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.127128E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.380994E+10 77905.93   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: CORE_BOTTOM VAV BOX REHEAT COIL

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:03 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:03 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.199923E+10 15304.18 12-JAN-06:02 0.00 0.00 0.00 0.00 0.00
February 0.157189E+10 16152.93 16-FEB-06:01 0.00 0.00 0.00 0.00 0.00
March 0.319470E+09 16602.99 27-MAR-05:01 0.00 0.00 0.00 0.00 0.00
April 684737.33 840.41 17-APR-05:08 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 140361.59 144.67 17-OCT-06:00 0.00 0.00 0.00 0.00 0.00
November 8624163.97 2174.32 24-NOV-06:03 0.00 0.00 0.00 0.00 0.00
December 0.821107E+09 16526.32 05-DEC-06:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.472114E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.199923E+10 16602.99   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.196432E+10 16228.30 09-JAN-05:02 0.00 0.00 0.00 0.00 0.00
February 0.164785E+10 16659.74 02-FEB-06:01 0.00 0.00 0.00 0.00 0.00
March 0.367159E+09 16722.56 25-MAR-05:01 0.00 0.00 0.00 0.00 0.00
April 18260682.60 6141.87 17-APR-05:02 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 24300191.59 3164.43 30-OCT-05:03 0.00 0.00 0.00 0.00 0.00
November 0.154857E+09 12693.67 25-NOV-06:01 0.00 0.00 0.00 0.00 0.00
December 0.147350E+10 16702.44 20-DEC-06:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.565024E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.196432E+10 16722.56   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.236964E+10 23135.32 18-JAN-06:02 0.00 0.00 0.00 0.00 0.00
February 0.200456E+10 23128.72 18-FEB-06:01 0.00 0.00 0.00 0.00 0.00
March 0.409636E+09 23174.54 28-MAR-05:02 0.00 0.00 0.00 0.00 0.00
April 42737991.01 23161.18 17-APR-05:02 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 39294025.79 15089.76 30-OCT-05:03 0.00 0.00 0.00 0.00 0.00
November 0.155431E+09 23161.85 24-NOV-06:01 0.00 0.00 0.00 0.00 0.00
December 0.149561E+10 23119.09 20-DEC-06:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.651691E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.236964E+10 23174.54   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.122795E+10 15250.12 30-JAN-05:02 0.00 0.00 0.00 0.00 0.00
February 0.594512E+09 15251.59 13-FEB-05:02 0.00 0.00 0.00 0.00 0.00
March 27583011.64 9429.37 07-MAR-06:01 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 84916120.51 15652.80 26-DEC-06:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.193496E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.122795E+10 15652.80   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: VAV_MID WITH REHEAT HEATING COIL

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.441126E+11 637370.28 13-JAN-07:10 0.00 0.00 0.00 0.00 0.00
February 0.387843E+11 801082.75 21-FEB-07:10 0.00 0.00 0.00 0.00 0.00
March 0.284942E+11 853243.56 03-MAR-16:20 0.00 0.00 0.00 0.00 0.00
April 0.173072E+11 536487.89 17-APR-06:10 0.00 0.00 0.00 0.00 0.00
May 0.144425E+10 204498.73 03-MAY-06:10 0.00 0.00 0.00 0.00 0.00
June 0.353283E+09 110849.15 13-JUN-06:10 0.00 0.00 0.00 0.00 0.00
July 2898.86 4.83 15-JUL-11:20 0.00 0.00 0.00 0.00 0.00
August 385356.70 1074.84 31-AUG-06:55 0.00 0.00 0.00 0.00 0.00
September 0.763879E+09 201495.64 05-SEP-06:10 0.00 0.00 0.00 0.00 0.00
October 0.115694E+11 486112.08 17-OCT-06:10 0.00 0.00 0.00 0.00 0.00
November 0.276792E+11 505344.99 24-NOV-07:10 0.00 0.00 0.00 0.00 0.00
December 0.350910E+11 761780.81 28-DEC-07:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.205600E+12     0.00 0.00 0.00 0.00 0.00
Minimum of Months 2898.86 4.83   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.441126E+11 853243.56   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: CORE_MID VAV BOX REHEAT COIL

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.228180E+11 602861.91 02-JAN-04:03 0.00 0.00 0.00 0.00 0.00
February 0.118834E+11 602331.67 13-FEB-06:04 0.00 0.00 0.00 0.00 0.00
March 0.877207E+09 602860.54 06-MAR-06:04 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.851086E+10 602203.61 27-DEC-06:03 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.440895E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.228180E+11 602861.91   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.983133E+11 145981.24 31-JAN-06:04 0.00 0.00 0.00 0.00 0.00
February 0.858585E+11 145978.20 27-FEB-06:05 0.00 0.00 0.00 0.00 0.00
March 0.352080E+11 146013.94 13-MAR-05:02 0.00 0.00 0.00 0.00 0.00
April 0.707842E+10 145459.49 17-APR-05:03 0.00 0.00 0.00 0.00 0.00
May 52279871.55 70077.51 08-MAY-05:03 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.105102E+09 41736.60 30-SEP-05:03 0.00 0.00 0.00 0.00 0.00
October 0.495974E+10 155528.72 24-OCT-05:02 0.00 0.00 0.00 0.00 0.00
November 0.189238E+11 145870.34 02-NOV-05:03 0.00 0.00 0.00 0.00 0.00
December 0.827896E+11 145963.29 12-DEC-06:05 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.333289E+12     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.983133E+11 155528.72   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.702688E+11 207506.42 23-JAN-05:03 0.00 0.00 0.00 0.00 0.00
February 0.603633E+11 207428.75 28-FEB-06:02 0.00 0.00 0.00 0.00 0.00
March 0.218440E+11 207032.29 27-MAR-05:02 0.00 0.00 0.00 0.00 0.00
April 0.577016E+10 206810.30 15-APR-04:11 0.00 0.00 0.00 0.00 0.00
May 0.217208E+09 23617.08 01-MAY-05:03 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.258761E+09 63331.02 30-SEP-05:03 0.00 0.00 0.00 0.00 0.00
October 0.550225E+10 210646.65 24-OCT-05:02 0.00 0.00 0.00 0.00 0.00
November 0.202760E+11 207187.94 25-NOV-05:02 0.00 0.00 0.00 0.00 0.00
December 0.651129E+11 207418.75 26-DEC-05:04 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.249613E+12     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.702688E+11 210646.65   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.709704E+11 235318.69 23-JAN-06:03 0.00 0.00 0.00 0.00 0.00
February 0.625667E+11 234503.07 23-FEB-05:03 0.00 0.00 0.00 0.00 0.00
March 0.180986E+11 233919.28 20-MAR-05:03 0.00 0.00 0.00 0.00 0.00
April 0.616580E+10 233928.88 05-APR-04:12 0.00 0.00 0.00 0.00 0.00
May 0.177111E+09 18341.97 01-MAY-05:20 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.124762E+09 18351.67 30-SEP-05:05 0.00 0.00 0.00 0.00 0.00
October 0.330028E+10 250298.33 24-OCT-05:02 0.00 0.00 0.00 0.00 0.00
November 0.149925E+11 234451.26 20-NOV-05:12 0.00 0.00 0.00 0.00 0.00
December 0.644720E+11 235070.82 14-DEC-05:12 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.240868E+12     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.709704E+11 250298.33   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.655882E+11 210875.47 04-JAN-06:02 0.00 0.00 0.00 0.00 0.00
February 0.545623E+11 210922.60 28-FEB-06:02 0.00 0.00 0.00 0.00 0.00
March 0.194690E+11 210500.13 20-MAR-05:02 0.00 0.00 0.00 0.00 0.00
April 0.508982E+10 210171.51 05-APR-04:11 0.00 0.00 0.00 0.00 0.00
May 0.161342E+09 22529.45 12-MAY-05:04 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.214233E+09 25693.91 29-SEP-05:03 0.00 0.00 0.00 0.00 0.00
October 0.466189E+10 210211.18 16-OCT-05:01 0.00 0.00 0.00 0.00 0.00
November 0.168072E+11 210218.66 21-NOV-05:11 0.00 0.00 0.00 0.00 0.00
December 0.551779E+11 210844.44 28-DEC-06:02 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.221732E+12     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.655882E+11 210922.60   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: VAV_TOP WITH REHEAT HEATING COIL

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.698613E+10 64314.62 13-JAN-07:10 0.00 0.00 0.00 0.00 0.00
February 0.633509E+10 80993.32 21-FEB-07:10 0.00 0.00 0.00 0.00 0.00
March 0.214540E+10 74184.46 06-MAR-07:10 0.00 0.00 0.00 0.00 0.00
April 0.531667E+09 54145.39 17-APR-06:10 0.00 0.00 0.00 0.00 0.00
May 0.127733E+09 21355.93 03-MAY-06:10 0.00 0.00 0.00 0.00 0.00
June 18945559.68 12180.35 13-JUN-06:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 2687031.62 3832.93 01-AUG-06:10 0.00 0.00 0.00 0.00 0.00
September 71037130.00 21316.45 05-SEP-06:10 0.00 0.00 0.00 0.00 0.00
October 0.407684E+09 50275.81 17-OCT-06:10 0.00 0.00 0.00 0.00 0.00
November 0.507836E+09 50580.33 24-NOV-07:10 0.00 0.00 0.00 0.00 0.00
December 0.589077E+10 77389.94 28-DEC-07:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.230250E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.698613E+10 80993.32   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: CORE_TOP VAV BOX REHEAT COIL

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.118589E+11 85515.11 17-JAN-06:05 0.00 0.00 0.00 0.00 0.00
February 0.995770E+10 85490.71 03-FEB-06:03 0.00 0.00 0.00 0.00 0.00
March 0.395856E+10 85520.62 21-MAR-05:03 0.00 0.00 0.00 0.00 0.00
April 0.721492E+09 85477.80 17-APR-05:03 0.00 0.00 0.00 0.00 0.00
May 589756.12 577.84 01-MAY-05:55 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.801419E+09 85500.57 30-OCT-04:03 0.00 0.00 0.00 0.00 0.00
November 0.247647E+10 85532.52 20-NOV-05:14 0.00 0.00 0.00 0.00 0.00
December 0.983370E+10 85523.55 13-DEC-06:03 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.396088E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.118589E+11 85532.52   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.151621E+11 16401.07 18-JAN-06:04 0.00 0.00 0.00 0.00 0.00
February 0.134905E+11 16397.44 01-FEB-06:05 0.00 0.00 0.00 0.00 0.00
March 0.700495E+10 16428.73 13-MAR-04:13 0.00 0.00 0.00 0.00 0.00
April 0.219269E+10 16396.67 03-APR-05:03 0.00 0.00 0.00 0.00 0.00
May 0.175466E+09 16318.79 01-MAY-05:03 0.00 0.00 0.00 0.00 0.00
June 792698.94 4996.16 14-JUN-05:03 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.120390E+09 16363.84 29-SEP-05:03 0.00 0.00 0.00 0.00 0.00
October 0.189253E+10 16400.35 16-OCT-05:04 0.00 0.00 0.00 0.00 0.00
November 0.477125E+10 16444.63 20-NOV-05:43 0.00 0.00 0.00 0.00 0.00
December 0.139642E+11 16443.12 14-DEC-06:04 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.587749E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.151621E+11 16444.63   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.102209E+11 21710.85 21-JAN-05:03 0.00 0.00 0.00 0.00 0.00
February 0.903850E+10 21792.42 01-FEB-05:12 0.00 0.00 0.00 0.00 0.00
March 0.406767E+10 21775.01 13-MAR-04:11 0.00 0.00 0.00 0.00 0.00
April 0.139941E+10 21710.28 17-APR-03:12 0.00 0.00 0.00 0.00 0.00
May 0.158117E+09 18238.96 12-MAY-05:02 0.00 0.00 0.00 0.00 0.00
June 151576.82 1010.51 14-JUN-05:03 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 1314358.73 984.66 31-AUG-05:10 0.00 0.00 0.00 0.00 0.00
September 0.126510E+09 12816.61 29-SEP-05:03 0.00 0.00 0.00 0.00 0.00
October 0.140014E+10 21704.25 16-OCT-05:02 0.00 0.00 0.00 0.00 0.00
November 0.377102E+10 21800.07 29-NOV-06:02 0.00 0.00 0.00 0.00 0.00
December 0.100050E+11 21810.80 19-DEC-05:02 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.401888E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.102209E+11 21810.80   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.116750E+11 25151.82 23-JAN-05:45 0.00 0.00 0.00 0.00 0.00
February 0.107165E+11 25234.17 23-FEB-06:03 0.00 0.00 0.00 0.00 0.00
March 0.435778E+10 25153.38 20-MAR-05:14 0.00 0.00 0.00 0.00 0.00
April 0.193256E+10 25237.55 03-APR-05:03 0.00 0.00 0.00 0.00 0.00
May 0.265800E+09 25033.97 12-MAY-05:02 0.00 0.00 0.00 0.00 0.00
June 22293862.88 14976.41 14-JUN-05:03 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 95753440.63 18673.42 29-SEP-05:03 0.00 0.00 0.00 0.00 0.00
October 0.137913E+10 25161.23 17-OCT-05:03 0.00 0.00 0.00 0.00 0.00
November 0.384539E+10 25159.29 24-NOV-05:33 0.00 0.00 0.00 0.00 0.00
December 0.115081E+11 25239.02 21-DEC-06:03 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.457982E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.116750E+11 25239.02   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.974826E+10 23921.88 12-JAN-05:12 0.00 0.00 0.00 0.00 0.00
February 0.819051E+10 24003.33 01-FEB-05:12 0.00 0.00 0.00 0.00 0.00
March 0.366186E+10 23918.35 20-MAR-03:02 0.00 0.00 0.00 0.00 0.00
April 0.134148E+10 23896.33 11-APR-04:12 0.00 0.00 0.00 0.00 0.00
May 0.178208E+09 15171.15 12-MAY-05:02 0.00 0.00 0.00 0.00 0.00
June 9607624.68 4038.43 14-JUN-05:03 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 866148.96 247.97 31-AUG-05:50 0.00 0.00 0.00 0.00 0.00
September 0.112550E+09 11863.40 29-SEP-05:03 0.00 0.00 0.00 0.00 0.00
October 0.133580E+10 23900.14 30-OCT-04:02 0.00 0.00 0.00 0.00 0.00
November 0.326314E+10 23900.82 21-NOV-05:12 0.00 0.00 0.00 0.00 0.00
December 0.849865E+10 24009.53 13-DEC-05:12 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.363409E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.974826E+10 24009.53   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: CAV_BAS HEATING COIL

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:03 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:03 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: AIRLOOP DATACENTER BASEMENT HEATING COIL

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:03 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:03 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: AIRLOOP DATACENTER BOT HEATING COIL

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:03 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:03 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: AIRLOOP DATACENTER MID HEATING COIL

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:03 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:03 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: AIRLOOP DATACENTER TOP HEATING COIL

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:03 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:03 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:03 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:03 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: AIRLOOP DATACENTER BOT_SUPPHEATCOIL

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:03 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:03 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: AIRLOOP DATACENTER MID_SUPPHEATCOIL

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:03 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:03 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: AIRLOOP DATACENTER TOP_SUPPHEATCOIL

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:03 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:03 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: VAV_BOT WITH REHEAT COOLING COIL

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 15133938.07 15133938.07 4338.63 18-JAN-13:10 4338.63 0.00
February 0.00 0.00 30370707.14 30370707.14 13132.71 14-FEB-15:05 13132.71 0.00
March 0.00 0.00 0.636447E+10 0.617335E+10 113138.33 14-MAR-13:10 98323.32 0.04
April 0.00 0.00 0.263950E+10 0.263950E+10 55809.84 07-APR-14:00 55809.84 0.02
May 0.00 0.00 0.198913E+11 0.196449E+11 107783.30 24-MAY-05:03 71134.97 0.14
June 0.00 0.00 0.873465E+11 0.691969E+11 233622.86 27-JUN-07:50 100722.19 0.49
July 0.00 0.00 0.155884E+12 0.112842E+12 313195.47 20-JUL-05:02 125408.10 0.72
August 0.00 0.00 0.137201E+12 0.107087E+12 308028.85 14-AUG-05:03 117157.25 0.72
September 0.00 0.00 0.531998E+11 0.423298E+11 204540.98 16-SEP-05:02 93463.55 0.40
October 0.00 0.00 0.736889E+10 0.736317E+10 84349.94 11-OCT-15:00 84349.94 0.10
November 0.00 0.00 0.119546E+10 0.119546E+10 55937.35 27-NOV-05:12 55937.35 0.03
December 0.00 0.00 23996758.26 23996758.26 4685.28 19-DEC-13:10 4685.28 0.00
                 
Annual Sum or Average 0.00 0.00 0.471160E+12 0.368541E+12       0.22
Minimum of Months 0.00 0.00 15133938.07 15133938.07 4338.63   4338.63 0.00
Maximum of Months 0.00 0.00 0.155884E+12 0.112842E+12 313195.47   125408.10 0.72



Table of Contents

Report: CoilReportMonthly

For: VAV_MID WITH REHEAT COOLING COIL

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 74783.10 74783.10 138.77 06-JAN-17:15 138.77 0.00
February 0.00 0.00 6151402.80 6151402.80 8316.78 28-FEB-14:50 8316.78 0.00
March 0.00 0.00 0.439210E+11 0.428562E+11 844458.96 15-MAR-14:20 844458.96 0.04
April 0.00 0.00 0.172933E+11 0.172933E+11 383718.89 07-APR-14:00 383718.89 0.02
May 0.00 0.00 0.168731E+12 0.166816E+12 938097.25 10-MAY-14:40 851457.78 0.13
June 0.00 0.00 0.719590E+12 0.577213E+12 1971307.61 27-JUN-05:03 839163.35 0.45
July 0.00 0.00 0.121862E+13 0.899969E+12 2940046.35 20-JUL-05:02 1176697.49 0.59
August 0.00 0.00 0.100915E+13 0.815634E+12 2613186.77 14-AUG-04:12 980561.44 0.57
September 0.00 0.00 0.450278E+12 0.362418E+12 1750087.72 16-SEP-05:02 792134.66 0.39
October 0.00 0.00 0.557712E+11 0.557484E+11 678165.67 11-OCT-15:00 678165.67 0.10
November 0.00 0.00 0.700992E+10 0.700992E+10 194113.19 16-NOV-13:10 194113.19 0.03
December 0.00 0.00 647703.50 647703.50 120.37 14-DEC-12:10 120.37 0.00
                 
Annual Sum or Average 0.00 0.00 0.369036E+13 0.294496E+13       0.20
Minimum of Months 0.00 0.00 74783.10 74783.10 120.37   120.37 0.00
Maximum of Months 0.00 0.00 0.121862E+13 0.899969E+12 2940046.35   1176697.49 0.59



Table of Contents

Report: CoilReportMonthly

For: VAV_TOP WITH REHEAT COOLING COIL

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 1891717.87 1891717.87 777.89 07-JAN-23:12 777.89 0.00
February 0.00 0.00 2999215.84 2999215.84 875.54 28-FEB-13:10 875.54 0.00
March 0.00 0.00 0.461181E+10 0.460139E+10 103313.64 15-MAR-14:10 103313.64 0.05
April 0.00 0.00 0.165045E+10 0.165045E+10 37829.97 07-APR-14:00 37829.97 0.02
May 0.00 0.00 0.168839E+11 0.167360E+11 109840.20 10-MAY-14:40 101663.43 0.13
June 0.00 0.00 0.776562E+11 0.620073E+11 317802.08 27-JUN-15:00 132967.21 0.45
July 0.00 0.00 0.133148E+12 0.983701E+11 298283.71 20-JUL-05:02 119324.24 0.59
August 0.00 0.00 0.108163E+12 0.869952E+11 282148.92 14-AUG-04:12 105874.56 0.57
September 0.00 0.00 0.445474E+11 0.357347E+11 192984.29 15-SEP-12:40 104930.70 0.39
October 0.00 0.00 0.485472E+10 0.485472E+10 67295.36 11-OCT-15:00 67295.36 0.10
November 0.00 0.00 0.655271E+09 0.655271E+09 15780.51 16-NOV-13:00 15780.51 0.03
December 0.00 0.00 3384188.89 3384188.89 877.06 11-DEC-05:40 877.06 0.00
                 
Annual Sum or Average 0.00 0.00 0.392178E+12 0.311613E+12       0.20
Minimum of Months 0.00 0.00 1891717.87 1891717.87 777.89   777.89 0.00
Maximum of Months 0.00 0.00 0.133148E+12 0.983701E+11 317802.08   132967.21 0.59



Table of Contents

Report: CoilReportMonthly

For: CAV_BAS COOLING COIL

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 84197.20 84197.20 60.53 06-JAN-17:15 60.53 0.00
February 0.00 0.00 196614.84 196614.84 292.94 09-FEB-11:00 292.94 0.00
March 0.00 0.00 0.351920E+10 0.350257E+10 71189.91 16-MAR-04:11 61718.94 0.04
April 0.00 0.00 0.607669E+09 0.607669E+09 27932.90 08-APR-04:12 27932.90 0.01
May 0.00 0.00 0.831938E+10 0.827302E+10 98076.02 24-MAY-05:03 59106.24 0.09
June 0.00 0.00 0.420856E+11 0.355007E+11 144283.93 27-JUN-04:53 61148.49 0.36
July 0.00 0.00 0.802959E+11 0.608901E+11 180591.72 20-JUL-04:33 72766.43 0.49
August 0.00 0.00 0.705731E+11 0.579471E+11 185702.80 13-AUG-17:20 91840.68 0.50
September 0.00 0.00 0.300396E+11 0.252107E+11 126332.32 16-SEP-04:12 54187.06 0.31
October 0.00 0.00 0.290239E+10 0.287536E+10 80204.75 26-OCT-05:02 40660.83 0.06
November 0.00 0.00 0.561211E+09 0.560898E+09 62248.49 27-NOV-06:03 62248.49 0.02
December 0.00 0.00 1701705.22 1701705.22 11028.29 01-DEC-06:02 11028.29 0.00
                 
Annual Sum or Average 0.00 0.00 0.238906E+12 0.195370E+12       0.16
Minimum of Months 0.00 0.00 84197.20 84197.20 60.53   60.53 0.00
Maximum of Months 0.00 0.00 0.802959E+11 0.608901E+11 185702.80   91840.68 0.50



Table of Contents

Report: CoilReportMonthly

For: AIRLOOP DATACENTER BASEMENT COOLING COIL

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.635088E+10 0.635073E+10 3716.70 13-JAN-18:00 3716.70 0.00
February 0.00 0.00 0.101905E+11 0.101661E+11 5131.11 14-FEB-17:05 5131.11 0.00
March 0.00 0.00 0.353730E+11 0.314121E+11 317408.35 14-MAR-13:00 258730.58 0.00
April 0.00 0.00 0.566671E+11 0.517223E+11 254030.20 08-APR-14:00 231567.28 0.00
May 0.00 0.00 0.776230E+10 0.725883E+10 123932.84 10-MAY-15:00 104750.48 0.00
June 0.00 0.00 0.187737E+12 0.132033E+12 424052.81 27-JUN-14:10 221417.32 0.00
July 0.00 0.00 0.753583E+12 0.462198E+12 471962.62 20-JUL-22:12 165311.48 0.00
August 0.00 0.00 0.853980E+12 0.570323E+12 457474.72 14-AUG-00:55 181707.52 0.00
September 0.00 0.00 0.177885E+11 0.130695E+11 176371.84 15-SEP-12:00 105485.05 0.00
October 0.00 0.00 0.994863E+10 0.947695E+10 103151.78 11-OCT-15:00 95905.29 0.00
November 0.00 0.00 0.229845E+11 0.205032E+11 132905.11 05-NOV-14:00 109085.35 0.00
December 0.00 0.00 0.164990E+11 0.156680E+11 128272.42 01-DEC-11:00 85920.95 0.00
                 
Annual Sum or Average 0.00 0.00 0.197887E+13 0.133018E+13       0.00
Minimum of Months 0.00 0.00 0.635088E+10 0.635073E+10 3716.70   3716.70 0.00
Maximum of Months 0.00 0.00 0.853980E+12 0.570323E+12 471962.62   258730.58 0.00



Table of Contents

Report: CoilReportMonthly

For: AIRLOOP DATACENTER BOT COOLING COIL

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.296986E+10 0.296986E+10 2119.87 15-JAN-16:35 2119.87 0.00
February 0.00 0.00 0.758374E+10 0.758374E+10 4405.92 28-FEB-16:55 4405.92 0.00
March 0.00 0.00 0.148969E+11 0.148750E+11 7562.63 31-MAR-24:00 7562.63 0.00
April 0.00 0.00 0.199022E+11 0.198994E+11 8801.88 02-APR-18:00 8801.88 0.00
May 0.00 0.00 0.572982E+10 0.569400E+10 4074.10 31-MAY-24:00 4074.10 0.00
June 0.00 0.00 0.110525E+11 0.108671E+11 5945.11 30-JUN-24:00 5945.11 0.00
July 0.00 0.00 0.167493E+11 0.164402E+11 7871.50 31-JUL-23:43 7845.79 0.00
August 0.00 0.00 0.216839E+11 0.214534E+11 9030.16 14-AUG-16:00 8694.80 0.00
September 0.00 0.00 0.584012E+10 0.570450E+10 3774.50 30-SEP-24:00 3774.50 0.00
October 0.00 0.00 0.103654E+11 0.103344E+11 5717.36 31-OCT-24:00 5717.36 0.00
November 0.00 0.00 0.145591E+11 0.145574E+11 6264.58 15-NOV-16:20 6264.58 0.00
December 0.00 0.00 0.192257E+11 0.192253E+11 7939.48 04-DEC-16:10 7939.48 0.00
                 
Annual Sum or Average 0.00 0.00 0.150559E+12 0.149604E+12       0.00
Minimum of Months 0.00 0.00 0.296986E+10 0.296986E+10 2119.87   2119.87 0.00
Maximum of Months 0.00 0.00 0.216839E+11 0.214534E+11 9030.16   8801.88 0.00



Table of Contents

Report: CoilReportMonthly

For: AIRLOOP DATACENTER MID COOLING COIL

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.539046E+10 0.539046E+10 15564.16 12-JAN-16:50 15564.16 0.00
February 0.00 0.00 0.473833E+11 0.473833E+11 38541.64 28-FEB-16:55 38541.64 0.00
March 0.00 0.00 0.123668E+12 0.123450E+12 66598.92 31-MAR-23:40 66598.92 0.00
April 0.00 0.00 0.177122E+12 0.177093E+12 80622.42 24-APR-18:00 80622.42 0.00
May 0.00 0.00 0.483950E+11 0.480425E+11 38361.42 31-MAY-24:00 38361.42 0.00
June 0.00 0.00 0.102685E+12 0.100844E+12 57065.85 30-JUN-24:00 57065.85 0.00
July 0.00 0.00 0.158741E+12 0.155663E+12 75976.12 31-JUL-23:53 75702.02 0.00
August 0.00 0.00 0.204895E+12 0.202597E+12 85735.26 04-AUG-18:40 85735.26 0.00
September 0.00 0.00 0.499986E+11 0.486693E+11 31727.41 30-SEP-24:00 31727.41 0.00
October 0.00 0.00 0.849039E+11 0.845954E+11 49403.58 31-OCT-23:40 49403.58 0.00
November 0.00 0.00 0.119155E+12 0.119137E+12 57601.04 15-NOV-16:20 57601.04 0.00
December 0.00 0.00 0.153174E+12 0.153169E+12 70332.35 04-DEC-16:20 70332.35 0.00
                 
Annual Sum or Average 0.00 0.00 0.127551E+13 0.126603E+13       0.00
Minimum of Months 0.00 0.00 0.539046E+10 0.539046E+10 15564.16   15564.16 0.00
Maximum of Months 0.00 0.00 0.204895E+12 0.202597E+12 85735.26   85735.26 0.00



Table of Contents

Report: CoilReportMonthly

For: AIRLOOP DATACENTER TOP COOLING COIL

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.194364E+09 0.194364E+09 1395.34 12-JAN-16:40 1395.34 0.00
February 0.00 0.00 0.338111E+10 0.338111E+10 3880.20 28-FEB-16:55 3880.20 0.00
March 0.00 0.00 0.109483E+11 0.109266E+11 6284.70 31-MAR-23:20 6284.70 0.00
April 0.00 0.00 0.167270E+11 0.167241E+11 8077.92 24-APR-18:00 8077.92 0.00
May 0.00 0.00 0.437961E+10 0.434472E+10 3748.30 31-MAY-23:30 3748.30 0.00
June 0.00 0.00 0.101664E+11 0.998230E+10 5637.11 30-JUN-23:30 5637.11 0.00
July 0.00 0.00 0.159082E+11 0.156005E+11 7591.69 31-JUL-23:53 7564.16 0.00
August 0.00 0.00 0.204406E+11 0.202110E+11 8652.87 04-AUG-18:40 8652.87 0.00
September 0.00 0.00 0.458363E+10 0.445144E+10 3014.05 04-SEP-17:45 3014.05 0.00
October 0.00 0.00 0.721174E+10 0.718120E+10 4742.07 11-OCT-17:00 4674.12 0.00
November 0.00 0.00 0.103094E+11 0.103077E+11 5686.46 15-NOV-16:20 5686.46 0.00
December 0.00 0.00 0.136157E+11 0.136153E+11 6790.13 04-DEC-16:20 6790.13 0.00
                 
Annual Sum or Average 0.00 0.00 0.117866E+12 0.116920E+12       0.00
Minimum of Months 0.00 0.00 0.194364E+09 0.194364E+09 1395.34   1395.34 0.00
Maximum of Months 0.00 0.00 0.204406E+11 0.202110E+11 8652.87   8652.87 0.00



Table of Contents

Report: PlantLoopDemandReportMonthly

For: HEATSYS1

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 0.00 0.00 01-JAN-00:03 165290.77 2176872.57 02-JAN-04:01
February 0.00 0.00 01-FEB-00:03 155520.54 1938265.26 27-FEB-05:01
March 0.00 0.00 01-MAR-00:10 56626.49 1743053.54 06-MAR-06:02
April 0.00 0.00 01-APR-00:10 19175.84 1580320.80 11-APR-04:11
May 0.00 0.00 01-MAY-00:10 1159.12 281524.33 03-MAY-06:10
June 0.00 0.00 01-JUN-00:10 149.86 123771.03 13-JUN-06:10
July 0.00 0.00 01-JUL-00:10 0.00 4.02 15-JUL-11:20
August 0.00 0.00 01-AUG-00:03 2.43 6141.96 03-AUG-06:10
September 0.00 0.00 01-SEP-00:10 766.43 301044.60 30-SEP-06:10
October 0.00 0.00 01-OCT-00:10 13963.82 1659501.42 30-OCT-04:01
November 0.00 0.00 01-NOV-00:10 45411.31 1719316.19 20-NOV-05:11
December 0.00 0.00 01-DEC-00:10 140034.59 1833400.48 11-DEC-06:01
             
Annual Sum or Average 0.00     49339.92    
Minimum of Months 0.00 0.00   0.00 4.02  
Maximum of Months 0.00 0.00   165290.77 2176872.57  



Table of Contents

Report: PlantLoopDemandReportMonthly

For: COOLSYS1_SUPPLY

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 282.02 6203.87 20-JAN-13:10 0.00 0.00 01-JAN-00:03
February 376.82 7142.87 28-FEB-14:10 0.00 0.00 01-FEB-00:03
March 23186.53 1253692.26 15-MAR-13:50 0.00 0.00 01-MAR-00:10
April 9260.63 508065.45 07-APR-14:00 0.00 0.00 01-APR-00:10
May 82208.32 1404184.79 10-MAY-15:40 0.00 0.00 01-MAY-00:10
June 370726.47 2284820.95 27-JUN-07:40 0.00 0.00 01-JUN-00:10
July 613723.89 3371563.00 20-JUL-05:02 0.00 0.00 01-JUL-00:10
August 513181.23 2990534.13 15-AUG-14:30 0.00 0.00 01-AUG-00:03
September 231059.45 2132797.84 15-SEP-15:00 0.00 0.00 01-SEP-00:10
October 27511.12 873744.12 11-OCT-14:40 0.00 0.00 01-OCT-00:10
November 4281.86 255839.37 16-NOV-13:10 0.00 0.00 01-NOV-00:10
December 471.70 30042.66 01-DEC-06:02 0.00 0.00 01-DEC-00:10
             
Annual Sum or Average 157665.51     0.00    
Minimum of Months 282.02 6203.87   0.00 0.00  
Maximum of Months 613723.89 3371563.00   0.00 0.00  



Table of Contents

Report: PlantLoopDemandReportMonthly

For: COOLSYS1_DEMAND

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 0.21 217.02 20-JAN-13:10 0.00 0.00 01-JAN-00:03
February 2.26 1741.54 28-FEB-14:50 0.00 0.00 01-FEB-00:03
March 22519.55 1250309.12 15-MAR-13:50 0.00 0.00 01-MAR-00:10
April 8540.64 502934.28 07-APR-14:00 0.00 0.00 01-APR-00:10
May 80279.44 1374495.30 24-MAY-05:03 0.00 0.00 01-MAY-00:10
June 365972.52 4171850.52 27-JUN-05:03 0.00 0.00 01-JUN-00:10
July 608011.56 4742134.59 17-JUL-04:12 0.00 0.00 01-JUL-00:10
August 508242.62 4528576.84 14-AUG-04:12 0.00 0.00 01-AUG-00:03
September 228556.26 4039103.53 16-SEP-05:02 0.00 0.00 01-SEP-00:10
October 26451.68 880523.90 26-OCT-05:02 0.00 0.00 01-OCT-00:10
November 3601.88 271544.16 16-NOV-11:25 0.00 0.00 01-NOV-00:10
December 10.80 45301.29 01-DEC-06:02 0.00 0.00 01-DEC-00:10
             
Annual Sum or Average 155647.11     0.00    
Minimum of Months 0.21 217.02   0.00 0.00  
Maximum of Months 608011.56 4742134.59   0.00 0.00  



Table of Contents

Report: PlantLoopDemandReportMonthly

For: SINGLE WATER PLANT LOOP

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 11211.54 31447.16 12-JAN-16:40 0.00 0.00 01-JAN-00:03
February 40028.01 68928.76 28-FEB-17:00 0.00 0.00 01-FEB-00:03
March 105045.52 1105325.10 15-MAR-14:00 0.00 0.00 01-MAR-00:10
April 139154.81 784688.92 08-APR-13:10 0.00 0.00 01-APR-00:10
May 56563.36 697805.94 10-MAY-15:00 0.00 0.00 01-MAY-00:10
June 327627.20 1349295.65 27-JUN-14:20 0.00 0.00 01-JUN-00:10
July 880678.64 1631258.97 15-JUL-13:53 0.00 0.00 01-JUL-00:10
August 926575.10 1677546.28 13-AUG-15:00 0.00 0.00 01-AUG-00:03
September 106341.45 802985.14 16-SEP-14:30 0.00 0.00 01-SEP-00:10
October 62184.27 492427.62 11-OCT-15:00 0.00 0.00 01-OCT-00:10
November 87207.97 423342.34 05-NOV-14:00 0.00 0.00 01-NOV-00:10
December 98348.65 266383.97 01-DEC-11:00 0.00 0.00 01-DEC-00:10
             
Annual Sum or Average 239149.44     0.00    
Minimum of Months 11211.54 31447.16   0.00 0.00  
Maximum of Months 926575.10 1677546.28   0.00 0.00  



Table of Contents

Report: PlantLoopDemandReportMonthly

For: SWHSYS1

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 0.00 0.00 01-JAN-00:03 16749.86 56724.50 31-JAN-12:20
February 0.00 0.00 01-FEB-00:03 17065.26 56958.23 17-FEB-12:10
March 0.00 0.00 01-MAR-00:10 17816.20 56766.04 01-MAR-12:10
April 0.00 0.00 01-APR-00:10 16180.23 55002.56 03-APR-11:30
May 0.00 0.00 01-MAY-00:10 15808.99 52525.96 01-MAY-11:20
June 0.00 0.00 01-JUN-00:10 15244.22 49319.85 01-JUN-12:00
July 0.00 0.00 01-JUL-00:10 13521.26 46491.09 03-JUL-12:00
August 0.00 0.00 01-AUG-00:03 14418.57 45017.64 01-AUG-11:20
September 0.00 0.00 01-SEP-00:10 13833.22 46431.87 29-SEP-12:00
October 0.00 0.00 01-OCT-00:10 14433.94 49237.05 31-OCT-11:20
November 0.00 0.00 01-NOV-00:10 15466.14 52362.90 30-NOV-12:15
December 0.00 0.00 01-DEC-00:10 15767.00 54971.65 29-DEC-12:40
             
Annual Sum or Average 0.00     15516.53    
Minimum of Months 0.00 0.00   13521.26 45017.64  
Maximum of Months 0.00 0.00   17816.20 56958.23  



Table of Contents

Report: PlantLoopDemandReportMonthly

For: TOWERWATERSYS

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 23.12 16999.20 23-JAN-07:20 1903.47 159629.52 24-JAN-04:11
February 19.27 11541.60 02-FEB-04:33 2709.51 154752.04 05-FEB-01:03
March 30920.94 2092358.79 14-MAR-13:00 2933.76 145197.11 23-MAR-09:30
April 9303.84 600853.36 07-APR-14:00 2182.49 137848.61 17-APR-15:50
May 97328.91 2097179.67 10-MAY-13:40 678.78 116031.59 01-MAY-08:70
June 634016.81 5936905.14 27-JUN-07:40 422.63 97995.97 03-JUN-06:20
July 1257562.38 6682912.17 05-JUL-16:00 135.97 70260.31 06-JUL-05:40
August 912779.54 6908633.30 15-AUG-14:40 418.56 49046.25 24-AUG-07:00
September 364041.22 4823453.06 15-SEP-11:00 324.92 58001.44 06-SEP-19:50
October 32161.51 1005383.23 11-OCT-15:00 1864.77 135397.24 17-OCT-12:50
November 4478.72 328546.76 16-NOV-13:10 3347.36 145981.34 26-NOV-11:02
December 25.07 8465.79 15-DEC-06:40 3154.85 163356.92 23-DEC-05:01
             
Annual Sum or Average 281124.94     1665.71    
Minimum of Months 19.27 8465.79   135.97 49046.25  
Maximum of Months 1257562.38 6908633.30   3347.36 163356.92  



Table of Contents

Report: FanReportMonthly

For: CAV_BAS FAN

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.146107E+11 0.76 10288.35 02-JAN-04:01 1.42
February 0.133678E+11 0.77 10288.35 01-FEB-06:03 1.42
March 0.161749E+11 0.84 10288.35 01-MAR-05:01 1.43
April 0.147732E+11 0.79 10288.35 01-APR-04:02 1.43
May 0.158317E+11 0.82 10288.35 01-MAY-04:12 1.42
June 0.155556E+11 0.82 10288.35 01-JUN-04:12 1.42
July 0.156803E+11 0.80 10288.35 01-JUL-04:12 1.42
August 0.170960E+11 0.88 10288.35 01-AUG-04:12 1.42
September 0.159944E+11 0.85 10288.35 01-SEP-04:12 1.42
October 0.156836E+11 0.81 10288.35 01-OCT-23:50 1.42
November 0.151578E+11 0.81 10288.35 01-NOV-04:12 1.43
December 0.149483E+11 0.77 10288.35 01-DEC-05:11 1.42
           
Annual Sum or Average 0.184874E+12 0.81      
Minimum of Months 0.133678E+11 0.76 10288.35   1.42
Maximum of Months 0.170960E+11 0.88 10288.35   1.43



Table of Contents

Report: FanReportMonthly

For: VAV_BOT WITH REHEAT FAN

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.366844E+10 0.31 18493.99 12-JAN-15:50 1.64
February 0.371524E+10 0.33 22011.32 28-FEB-16:40 1.83
March 0.692461E+10 0.42 22011.32 06-MAR-14:20 1.83
April 0.789285E+10 0.45 20622.28 01-APR-09:40 1.75
May 0.825741E+10 0.46 16336.81 01-MAY-06:15 1.51
June 0.120273E+11 0.59 23570.15 19-JUN-04:12 1.89
July 0.143085E+11 0.67 23570.15 05-JUL-04:11 1.89
August 0.155038E+11 0.71 23570.15 14-AUG-14:30 1.89
September 0.890107E+10 0.48 19807.40 14-SEP-05:03 1.69
October 0.673504E+10 0.40 15614.02 17-OCT-08:35 1.47
November 0.555776E+10 0.37 20622.28 18-NOV-09:17 1.76
December 0.471089E+10 0.34 19121.56 11-DEC-15:10 1.68
           
Annual Sum or Average 0.982029E+11 0.46      
Minimum of Months 0.366844E+10 0.31 15614.02   1.47
Maximum of Months 0.155038E+11 0.71 23570.15   1.89



Table of Contents

Report: FanReportMonthly

For: VAV_MID WITH REHEAT FAN

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.381633E+11 0.37 59345.35 02-JAN-04:01 0.86
February 0.346858E+11 0.37 80877.78 24-FEB-16:15 1.03
March 0.411189E+11 0.35 217787.16 02-MAR-16:00 1.90
April 0.431285E+11 0.35 213593.64 13-APR-11:07 1.87
May 0.620076E+11 0.41 144294.62 08-MAY-07:20 1.47
June 0.915413E+11 0.52 187102.00 27-JUN-05:03 1.70
July 0.105195E+12 0.54 220092.66 22-JUL-05:03 1.89
August 0.103828E+12 0.54 220092.66 07-AUG-04:11 1.89
September 0.682522E+11 0.43 151452.90 21-SEP-16:00 1.49
October 0.427206E+11 0.33 213593.64 17-OCT-09:57 1.87
November 0.331545E+11 0.31 213593.64 03-NOV-09:00 1.87
December 0.353746E+11 0.35 59345.35 11-DEC-05:11 0.87
           
Annual Sum or Average 0.699171E+12 0.41      
Minimum of Months 0.331545E+11 0.31 59345.35   0.86
Maximum of Months 0.105195E+12 0.54 220092.66   1.90



Table of Contents

Report: FanReportMonthly

For: VAV_TOP WITH REHEAT FAN

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.462767E+10 0.43 5580.77 02-JAN-04:01 0.79
February 0.424507E+10 0.43 5580.77 01-FEB-05:11 0.79
March 0.428901E+10 0.38 10819.73 15-MAR-14:10 1.15
April 0.387024E+10 0.34 13115.66 05-APR-13:10 1.30
May 0.543736E+10 0.37 12482.05 31-MAY-16:00 1.26
June 0.893575E+10 0.48 18882.16 12-JUN-15:20 1.62
July 0.106676E+11 0.51 24127.77 17-JUL-04:12 1.89
August 0.100621E+11 0.50 24127.77 07-AUG-04:11 1.89
September 0.595804E+10 0.39 16523.05 21-SEP-15:50 1.49
October 0.366740E+10 0.31 9303.96 11-OCT-15:50 1.05
November 0.328096E+10 0.32 5580.77 13-NOV-05:11 0.79
December 0.449574E+10 0.42 5580.77 04-DEC-04:01 0.79
           
Annual Sum or Average 0.695369E+11 0.41      
Minimum of Months 0.328096E+10 0.31 5580.77   0.79
Maximum of Months 0.106676E+11 0.51 24127.77   1.89



Table of Contents

Report: FanReportMonthly

For: AIRLOOP DATACENTER BASEMENT SUPPLY FAN

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.969086E+11 1.38 36181.53 01-JAN-00:03 1.38
February 0.875304E+11 1.38 36181.53 01-FEB-00:03 1.38
March 0.969086E+11 1.38 36181.53 01-MAR-00:20 1.39
April 0.937825E+11 1.39 36181.53 01-APR-00:20 1.38
May 0.969086E+11 1.38 36181.53 01-MAY-00:10 1.38
June 0.937825E+11 1.37 36181.53 01-JUN-00:10 1.38
July 0.969086E+11 1.37 36181.53 01-JUL-00:10 1.38
August 0.969086E+11 1.37 36181.53 01-AUG-00:03 1.37
September 0.937825E+11 1.38 36181.53 01-SEP-00:10 1.38
October 0.969086E+11 1.38 36181.53 01-OCT-00:10 1.38
November 0.937825E+11 1.38 36181.53 01-NOV-00:10 1.38
December 0.969086E+11 1.39 36181.53 01-DEC-00:10 1.39
           
Annual Sum or Average 0.114102E+13 1.38      
Minimum of Months 0.875304E+11 1.37 36181.53   1.37
Maximum of Months 0.969086E+11 1.39 36181.53   1.39



Table of Contents

Report: FanReportMonthly

For: AIRLOOP DATACENTER BOT SUPPLY FAN

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.153733E+10 0.94 573.97 01-JAN-00:03 0.94
February 0.138856E+10 0.94 573.97 01-FEB-00:03 0.95
March 0.153733E+10 0.94 573.97 01-MAR-00:10 0.94
April 0.148774E+10 0.94 573.97 01-APR-00:10 0.94
May 0.153733E+10 0.94 573.97 01-MAY-00:10 0.94
June 0.148774E+10 0.94 573.97 01-JUN-00:10 0.94
July 0.153733E+10 0.94 573.97 01-JUL-00:10 0.94
August 0.153733E+10 0.94 573.97 01-AUG-00:03 0.94
September 0.148774E+10 0.94 573.97 01-SEP-00:10 0.94
October 0.153733E+10 0.94 573.97 01-OCT-00:10 0.94
November 0.148774E+10 0.94 573.97 01-NOV-00:10 0.94
December 0.153733E+10 0.94 573.97 01-DEC-00:10 0.94
           
Annual Sum or Average 0.181009E+11 0.94      
Minimum of Months 0.138856E+10 0.94 573.97   0.94
Maximum of Months 0.153733E+10 0.94 573.97   0.95



Table of Contents

Report: FanReportMonthly

For: AIRLOOP DATACENTER MID SUPPLY FAN

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.147517E+11 0.94 5507.64 01-JAN-00:03 0.94
February 0.133241E+11 0.94 5507.64 01-FEB-00:03 0.95
March 0.147517E+11 0.94 5507.64 01-MAR-00:10 0.94
April 0.142758E+11 0.94 5507.64 01-APR-00:10 0.94
May 0.147517E+11 0.94 5507.64 01-MAY-00:10 0.94
June 0.142758E+11 0.94 5507.64 01-JUN-00:20 0.94
July 0.147517E+11 0.94 5507.64 01-JUL-00:10 0.94
August 0.147517E+11 0.94 5507.64 01-AUG-00:03 0.94
September 0.142758E+11 0.94 5507.64 01-SEP-00:10 0.94
October 0.147517E+11 0.94 5507.64 01-OCT-00:10 0.94
November 0.142758E+11 0.94 5507.64 01-NOV-00:10 0.94
December 0.147517E+11 0.94 5507.64 01-DEC-00:10 0.94
           
Annual Sum or Average 0.173689E+12 0.94      
Minimum of Months 0.133241E+11 0.94 5507.64   0.94
Maximum of Months 0.147517E+11 0.94 5507.64   0.95



Table of Contents

Report: FanReportMonthly

For: AIRLOOP DATACENTER TOP SUPPLY FAN

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.149889E+10 0.94 559.62 01-JAN-00:03 0.94
February 0.135384E+10 0.94 559.62 01-FEB-00:03 0.95
March 0.149889E+10 0.94 559.62 01-MAR-00:10 0.94
April 0.145054E+10 0.94 559.62 01-APR-00:10 0.94
May 0.149889E+10 0.94 559.62 01-MAY-00:10 0.94
June 0.145054E+10 0.94 559.62 01-JUN-00:10 0.94
July 0.149889E+10 0.94 559.62 01-JUL-00:10 0.94
August 0.149889E+10 0.94 559.62 01-AUG-00:03 0.94
September 0.145054E+10 0.94 559.62 01-SEP-00:10 0.94
October 0.149889E+10 0.94 559.62 01-OCT-00:10 0.94
November 0.145054E+10 0.94 559.62 01-NOV-00:10 0.94
December 0.149889E+10 0.94 559.62 01-DEC-00:10 0.94
           
Annual Sum or Average 0.176483E+11 0.94      
Minimum of Months 0.135384E+10 0.94 559.62   0.94
Maximum of Months 0.149889E+10 0.94 559.62   0.95



Table of Contents

Report: PumpReportMonthly

For: HEATSYS1 PUMP

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

PUMP ELECTRICITY ENERGY [J] PUMP FLUID HEAT GAIN ENERGY [J] PUMP ELECTRICITY RATE {Maximum} [W] PUMP ELECTRICITY RATE {TIMESTAMP} PUMP SHAFT POWER {AT MAX/MIN} [W] PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s]
January 0.203595E+10 0.183235E+10 5982.14 30-JAN-05:02 5383.93 5383.93 47.29 12.38
February 0.177459E+10 0.159713E+10 6041.08 21-FEB-07:10 5436.97 5436.97 48.61 12.80
March 0.727936E+09 0.655143E+09 5963.84 06-MAR-06:02 5367.45 5367.45 47.97 12.25
April 0.222767E+09 0.200490E+09 4836.59 17-APR-05:02 4352.93 4352.93 42.01 7.56
May 12810456.06 11529410.45 1089.78 03-MAY-06:10 980.80 980.80 25.17 1.19
June 1624019.73 1461617.76 503.02 13-JUN-06:10 452.72 452.72 25.86 0.53
July 10.11 9.10 0.02 15-JUL-11:20 0.02 0.02 25.97 0.00
August 27292.19 24562.97 25.76 03-AUG-06:10 23.19 23.19 26.09 0.03
September 9011905.28 8110714.75 1148.92 30-SEP-06:10 1034.03 1034.03 24.59 1.25
October 0.161354E+09 0.145218E+09 4781.62 16-OCT-05:01 4303.46 4303.46 35.57 7.43
November 0.526371E+09 0.473734E+09 4868.11 24-NOV-06:01 4381.30 4381.30 42.59 7.65
December 0.177852E+10 0.160067E+10 6002.08 26-DEC-07:10 5401.87 5401.87 47.46 12.52
                 
Annual Sum or Average 0.725096E+10 0.652586E+10            
Minimum of Months 10.11 9.10 0.02   0.02 0.02 24.59 0.00
Maximum of Months 0.203595E+10 0.183235E+10 6041.08   5436.97 5436.97 48.61 12.80



Table of Contents

Report: PumpReportMonthly

For: COOLSYS1 PUMP SECONDARY

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

PUMP ELECTRICITY ENERGY [J] PUMP FLUID HEAT GAIN ENERGY [J] PUMP ELECTRICITY RATE {Maximum} [W] PUMP ELECTRICITY RATE {TIMESTAMP} PUMP SHAFT POWER {AT MAX/MIN} [W] PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s]
January 1605.55 1445.00 0.39 18-JAN-13:10 0.36 0.36 6.70 0.12
February 3820.88 3438.79 1.15 14-FEB-15:05 1.04 1.04 6.70 0.33
March 35929939.37 32336945.43 1604.05 15-MAR-13:30 1443.65 1443.65 6.71 41.66
April 5162872.86 4646585.57 172.80 08-APR-13:00 155.52 155.52 6.70 13.86
May 89193205.66 80273885.09 1886.21 24-MAY-05:03 1697.59 1697.59 6.70 44.80
June 0.656876E+09 0.591188E+09 19464.64 27-JUN-05:03 17518.17 17518.17 9.40 118.51
July 0.134234E+10 0.120811E+10 19464.64 15-JUL-05:03 17518.17 17518.17 9.41 118.51
August 0.122066E+10 0.109860E+10 19464.64 07-AUG-05:02 17518.17 17518.17 9.07 118.51
September 0.468386E+09 0.421548E+09 19464.64 14-SEP-05:03 17518.17 17518.17 9.27 118.51
October 43767810.28 39391029.25 1654.93 11-OCT-12:10 1489.44 1489.44 6.71 42.25
November 2551403.26 2296262.93 152.76 27-NOV-06:03 137.48 137.48 6.70 12.95
December 4100.65 3690.58 7.84 01-DEC-06:02 7.06 7.06 6.70 1.79
                 
Annual Sum or Average 0.386488E+10 0.347839E+10            
Minimum of Months 1605.55 1445.00 0.39   0.36 0.36 6.70 0.12
Maximum of Months 0.134234E+10 0.120811E+10 19464.64   17518.17 17518.17 9.41 118.51



Table of Contents

Report: PumpReportMonthly

For: COOLSYS1 CHILLER1 PUMP

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

PUMP ELECTRICITY ENERGY [J] PUMP FLUID HEAT GAIN ENERGY [J] PUMP ELECTRICITY RATE {Maximum} [W] PUMP ELECTRICITY RATE {TIMESTAMP} PUMP SHAFT POWER {AT MAX/MIN} [W] PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s]
January 0.839474E+09 0.755527E+09 6698.49 02-JAN-07:20 6028.64 6028.64 6.72 59.25
February 0.100684E+10 0.906157E+09 6698.49 01-FEB-11:50 6028.64 6028.64 6.72 59.25
March 0.205395E+10 0.184856E+10 6698.49 01-MAR-12:50 6028.64 6028.64 6.72 59.25
April 0.208209E+10 0.187388E+10 6698.49 01-APR-06:30 6028.64 6028.64 6.72 59.25
May 0.546852E+10 0.492167E+10 6698.49 01-MAY-04:30 6028.64 6028.64 6.73 59.25
June 0.104357E+11 0.939209E+10 6698.49 01-JUN-04:12 6028.64 6028.64 7.99 59.25
July 0.136769E+11 0.123092E+11 6698.49 01-JUL-04:12 6028.64 6028.64 7.98 59.25
August 0.134816E+11 0.121334E+11 6698.49 01-AUG-00:03 6028.64 6028.64 6.81 59.25
September 0.799666E+10 0.719699E+10 6698.49 01-SEP-04:12 6028.64 6028.64 7.35 59.25
October 0.319134E+10 0.287220E+10 6698.49 02-OCT-06:30 6028.64 6028.64 6.74 59.25
November 0.195841E+10 0.176257E+10 6698.49 01-NOV-06:20 6028.64 6028.64 6.74 59.25
December 0.137164E+10 0.123448E+10 6698.49 01-DEC-05:11 6028.64 6028.64 6.75 59.25
                 
Annual Sum or Average 0.635631E+11 0.572068E+11            
Minimum of Months 0.839474E+09 0.755527E+09 6698.49   6028.64 6028.64 6.72 59.25
Maximum of Months 0.136769E+11 0.123092E+11 6698.49   6028.64 6028.64 7.99 59.25



Table of Contents

Report: PumpReportMonthly

For: COOLSYS1 CHILLER2 PUMP

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

PUMP ELECTRICITY ENERGY [J] PUMP FLUID HEAT GAIN ENERGY [J] PUMP ELECTRICITY RATE {Maximum} [W] PUMP ELECTRICITY RATE {TIMESTAMP} PUMP SHAFT POWER {AT MAX/MIN} [W] PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s]
January 0.00 0.00 0.00 01-JAN-00:03 0.00 0.00 6.70 0.00
February 0.00 0.00 0.00 01-FEB-00:03 0.00 0.00 6.72 0.00
March 0.00 0.00 0.00 01-MAR-00:10 0.00 0.00 6.72 0.00
April 0.00 0.00 0.00 01-APR-00:10 0.00 0.00 6.72 0.00
May 40190949.50 36171854.55 6698.49 10-MAY-14:30 6028.64 6028.64 12.17 29.63
June 0.155338E+10 0.139804E+10 6698.49 01-JUN-15:10 6028.64 6028.64 12.69 29.63
July 0.341770E+10 0.307593E+10 6698.49 03-JUL-12:50 6028.64 6028.64 12.41 29.63
August 0.243061E+10 0.218755E+10 6698.49 02-AUG-13:30 6028.64 6028.64 12.74 29.63
September 0.724241E+09 0.651817E+09 6698.49 08-SEP-13:10 6028.64 6028.64 12.37 29.63
October 0.00 0.00 0.00 01-OCT-00:10 0.00 0.00 6.82 0.00
November 0.00 0.00 0.00 01-NOV-00:10 0.00 0.00 6.79 0.00
December 0.00 0.00 0.00 01-DEC-00:10 0.00 0.00 6.72 0.00
                 
Annual Sum or Average 0.816613E+10 0.734952E+10            
Minimum of Months 0.00 0.00 0.00   0.00 0.00 6.70 0.00
Maximum of Months 0.341770E+10 0.307593E+10 6698.49   6028.64 6028.64 12.74 29.63



Table of Contents

Report: PumpReportMonthly

For: PLANT CIRC PUMP

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

PUMP ELECTRICITY ENERGY [J] PUMP FLUID HEAT GAIN ENERGY [J] PUMP ELECTRICITY RATE {Maximum} [W] PUMP ELECTRICITY RATE {TIMESTAMP} PUMP SHAFT POWER {AT MAX/MIN} [W] PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s]
January 0.922579E+10 0.830321E+10 3444.52 01-JAN-00:03 3100.06 3100.06 18.49 14.39
February 0.833297E+10 0.749967E+10 3444.52 01-FEB-00:03 3100.06 3100.06 18.90 14.39
March 0.922579E+10 0.830321E+10 3444.52 01-MAR-00:10 3100.06 3100.06 19.77 14.39
April 0.892818E+10 0.803536E+10 3444.52 01-APR-00:10 3100.06 3100.06 20.53 14.39
May 0.922579E+10 0.830321E+10 3444.52 01-MAY-00:10 3100.06 3100.06 18.93 14.39
June 0.892818E+10 0.803536E+10 3444.52 01-JUN-00:10 3100.06 3100.06 19.53 14.39
July 0.922579E+10 0.830321E+10 3444.52 01-JUL-00:10 3100.06 3100.06 21.49 14.39
August 0.922579E+10 0.830321E+10 3444.52 01-AUG-00:03 3100.06 3100.06 35.50 14.39
September 0.892818E+10 0.803536E+10 3444.52 01-SEP-00:10 3100.06 3100.06 18.95 14.39
October 0.922579E+10 0.830321E+10 3444.52 01-OCT-00:10 3100.06 3100.06 19.34 14.39
November 0.892818E+10 0.803536E+10 3444.52 01-NOV-00:10 3100.06 3100.06 20.01 14.39
December 0.922579E+10 0.830321E+10 3444.52 01-DEC-00:10 3100.06 3100.06 20.38 14.39
                 
Annual Sum or Average 0.108626E+12 0.977636E+11            
Minimum of Months 0.833297E+10 0.749967E+10 3444.52   3100.06 3100.06 18.49 14.39
Maximum of Months 0.922579E+10 0.830321E+10 3444.52   3100.06 3100.06 35.50 14.39



Table of Contents

Report: PumpReportMonthly

For: SWHSYS1 PUMP

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

PUMP ELECTRICITY ENERGY [J] PUMP FLUID HEAT GAIN ENERGY [J] PUMP ELECTRICITY RATE {Maximum} [W] PUMP ELECTRICITY RATE {TIMESTAMP} PUMP SHAFT POWER {AT MAX/MIN} [W] PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s]
January 0.112905E+09 33871561.48 56.21 01-JAN-06:03 16.86 16.86 55.67 0.44
February 0.101979E+09 30593668.43 56.21 01-FEB-06:03 16.86 16.86 55.51 0.44
March 0.112905E+09 33871561.48 56.21 01-MAR-06:01 16.86 16.86 56.00 0.44
April 0.109263E+09 32778930.46 56.21 01-APR-05:03 16.86 16.86 56.06 0.44
May 0.112905E+09 33871561.48 56.21 01-MAY-05:03 16.86 16.86 56.54 0.44
June 0.109263E+09 32778930.46 56.21 01-JUN-05:03 16.86 16.86 55.81 0.44
July 0.112905E+09 33871561.48 56.21 01-JUL-05:03 16.86 16.86 56.58 0.44
August 0.112905E+09 33871561.48 56.21 01-AUG-05:03 16.86 16.86 57.10 0.44
September 0.109263E+09 32778930.46 56.21 01-SEP-05:03 16.86 16.86 56.56 0.44
October 0.112905E+09 33871561.48 56.21 01-OCT-05:10 16.86 16.86 56.32 0.44
November 0.109263E+09 32778930.46 56.21 01-NOV-05:03 16.86 16.86 56.11 0.44
December 0.112905E+09 33871561.48 56.21 01-DEC-06:02 16.86 16.86 56.46 0.44
                 
Annual Sum or Average 0.132937E+10 0.398810E+09            
Minimum of Months 0.101979E+09 30593668.43 56.21   16.86 16.86 55.51 0.44
Maximum of Months 0.112905E+09 33871561.48 56.21   16.86 16.86 57.10 0.44



Table of Contents

Report: PumpReportMonthly

For: TOWERWATERSYS PUMP

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

PUMP ELECTRICITY ENERGY [J] PUMP FLUID HEAT GAIN ENERGY [J] PUMP ELECTRICITY RATE {Maximum} [W] PUMP ELECTRICITY RATE {TIMESTAMP} PUMP SHAFT POWER {AT MAX/MIN} [W] PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s]
January 0.215012E+10 0.193511E+10 17159.11 23-JAN-07:20 15443.20 15443.20 21.16 69.54
February 0.257878E+10 0.232090E+10 17158.88 02-FEB-04:33 15442.99 15442.99 21.14 69.54
March 0.525940E+10 0.473346E+10 17254.33 14-MAR-13:00 15528.90 15528.90 28.30 69.54
April 0.532898E+10 0.479608E+10 17183.92 07-APR-14:00 15465.53 15465.53 23.17 69.54
May 0.140188E+11 0.126170E+11 17254.57 10-MAY-13:40 15529.12 15529.12 28.32 69.54
June 0.301850E+11 0.271665E+11 34523.41 27-JUN-07:05 31071.07 31071.07 28.98 139.07
July 0.428021E+11 0.385219E+11 34523.41 05-JUL-09:40 31071.07 31071.07 28.93 139.07
August 0.402736E+11 0.362462E+11 34523.41 07-AUG-11:30 31071.07 31071.07 28.86 139.07
September 0.221311E+11 0.199180E+11 34523.41 15-SEP-10:30 31071.07 31071.07 28.86 139.07
October 0.817472E+10 0.735725E+10 17201.14 11-OCT-15:00 15481.02 15481.02 24.56 69.54
November 0.499263E+10 0.449337E+10 17172.34 16-NOV-13:10 15455.11 15455.11 22.23 69.54
December 0.351314E+10 0.316183E+10 17158.75 15-DEC-06:40 15442.88 15442.88 21.13 69.54
                 
Annual Sum or Average 0.181408E+12 0.163267E+12            
Minimum of Months 0.215012E+10 0.193511E+10 17158.75   15442.88 15442.88 21.13 69.54
Maximum of Months 0.428021E+11 0.385219E+11 34523.41   31071.07 31071.07 28.98 139.07



Table of Contents

Report: CondLoopDemandReportMonthly

For: HEATSYS1

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 0.00 0.00 01-JAN-00:03 35.03 35.03 165290.77 2176872.57 02-JAN-04:01
February 0.00 0.00 01-FEB-00:03 36.09 36.09 155520.54 1938265.26 27-FEB-05:01
March 0.00 0.00 01-MAR-00:10 27.89 27.89 56626.49 1743053.54 06-MAR-06:02
April 0.00 0.00 01-APR-00:10 22.62 22.62 19175.84 1580320.80 11-APR-04:11
May 0.00 0.00 01-MAY-00:10 21.96 21.96 1159.12 281524.33 03-MAY-06:10
June 0.00 0.00 01-JUN-00:10 28.07 28.07 149.86 123771.03 13-JUN-06:10
July 0.00 0.00 01-JUL-00:10 25.97 25.97 0.00 4.02 15-JUL-11:20
August 0.00 0.00 01-AUG-00:03 25.97 25.97 2.43 6141.96 03-AUG-06:10
September 0.00 0.00 01-SEP-00:10 26.17 26.17 766.43 301044.60 30-SEP-06:10
October 0.00 0.00 01-OCT-00:10 23.19 23.19 13963.82 1659501.42 30-OCT-04:01
November 0.00 0.00 01-NOV-00:10 23.71 23.71 45411.31 1719316.19 20-NOV-05:11
December 0.00 0.00 01-DEC-00:10 24.62 24.62 140034.59 1833400.48 11-DEC-06:01
                 
Annual Sum or Average 0.00         49339.92    
Minimum of Months 0.00 0.00   21.96 21.96 0.00 4.02  
Maximum of Months 0.00 0.00   36.09 36.09 165290.77 2176872.57  



Table of Contents

Report: CondLoopDemandReportMonthly

For: COOLSYS1_SUPPLY

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 282.02 6203.87 20-JAN-13:10 6.72 6.70 0.00 0.00 01-JAN-00:03
February 376.82 7142.87 28-FEB-14:10 6.73 6.70 0.00 0.00 01-FEB-00:03
March 23186.53 1253692.26 15-MAR-13:50 11.75 6.70 0.00 0.00 01-MAR-00:10
April 9260.63 508065.45 07-APR-14:00 8.75 6.70 0.00 0.00 01-APR-00:10
May 82208.32 1404184.79 10-MAY-15:40 12.36 8.68 0.00 0.00 01-MAY-00:10
June 370726.47 2284820.95 27-JUN-07:40 11.30 6.70 0.00 0.00 01-JUN-00:10
July 613723.89 3371563.00 20-JUL-05:02 13.50 7.81 0.00 0.00 01-JUL-00:10
August 513181.23 2990534.13 15-AUG-14:30 12.73 7.04 0.00 0.00 01-AUG-00:03
September 231059.45 2132797.84 15-SEP-15:00 11.00 6.70 0.00 0.00 01-SEP-00:10
October 27511.12 873744.12 11-OCT-14:40 10.22 6.70 0.00 0.00 01-OCT-00:10
November 4281.86 255839.37 16-NOV-13:10 7.73 6.70 0.00 0.00 01-NOV-00:10
December 471.70 30042.66 01-DEC-06:02 6.82 6.70 0.00 0.00 01-DEC-00:10
                 
Annual Sum or Average 157665.51         0.00    
Minimum of Months 282.02 6203.87   6.72 6.70 0.00 0.00  
Maximum of Months 613723.89 3371563.00   13.50 8.68 0.00 0.00  



Table of Contents

Report: CondLoopDemandReportMonthly

For: COOLSYS1_DEMAND

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 0.21 217.02 20-JAN-13:10 7.15 6.70 0.00 0.00 01-JAN-00:03
February 2.26 1741.54 28-FEB-14:50 8.36 6.70 0.00 0.00 01-FEB-00:03
March 22519.55 1250309.12 15-MAR-13:50 14.08 6.70 0.00 0.00 01-MAR-00:10
April 8540.64 502934.28 07-APR-14:00 17.22 6.70 0.00 0.00 01-APR-00:10
May 80279.44 1374495.30 24-MAY-05:03 14.03 6.70 0.00 0.00 01-MAY-00:10
June 365972.52 4171850.52 27-JUN-05:03 15.11 10.90 0.00 0.00 01-JUN-00:10
July 608011.56 4742134.59 17-JUL-04:12 16.26 11.47 0.00 0.00 01-JUL-00:10
August 508242.62 4528576.84 14-AUG-04:12 16.39 11.24 0.00 0.00 01-AUG-00:03
September 228556.26 4039103.53 16-SEP-05:02 14.84 10.76 0.00 0.00 01-SEP-00:10
October 26451.68 880523.90 26-OCT-05:02 15.03 6.70 0.00 0.00 01-OCT-00:10
November 3601.88 271544.16 16-NOV-11:25 14.72 6.70 0.00 0.00 01-NOV-00:10
December 10.80 45301.29 01-DEC-06:02 12.74 6.70 0.00 0.00 01-DEC-00:10
                 
Annual Sum or Average 155647.11         0.00    
Minimum of Months 0.21 217.02   7.15 6.70 0.00 0.00  
Maximum of Months 608011.56 4742134.59   17.22 11.47 0.00 0.00  



Table of Contents

Report: CondLoopDemandReportMonthly

For: SINGLE WATER PLANT LOOP

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 11211.54 31447.16 12-JAN-16:40 18.96 18.33 0.00 0.00 01-JAN-00:03
February 40028.01 68928.76 28-FEB-17:00 19.71 18.33 0.00 0.00 01-FEB-00:03
March 105045.52 1105325.10 15-MAR-14:00 40.06 30.52 0.00 0.00 01-MAR-00:10
April 139154.81 784688.92 08-APR-13:10 33.85 25.06 0.00 0.00 01-APR-00:10
May 56563.36 697805.94 10-MAY-15:00 32.15 28.00 0.00 0.00 01-MAY-00:10
June 327627.20 1349295.65 27-JUN-14:20 44.74 32.42 0.00 0.00 01-JUN-00:10
July 880678.64 1631258.97 15-JUL-13:53 50.10 36.85 0.00 0.00 01-JUL-00:10
August 926575.10 1677546.28 13-AUG-15:00 50.98 36.73 0.00 0.00 01-AUG-00:03
September 106341.45 802985.14 16-SEP-14:30 34.21 29.24 0.00 0.00 01-SEP-00:10
October 62184.27 492427.62 11-OCT-15:00 28.12 24.05 0.00 0.00 01-OCT-00:10
November 87207.97 423342.34 05-NOV-14:00 26.76 21.70 0.00 0.00 01-NOV-00:10
December 98348.65 266383.97 01-DEC-11:00 23.65 18.33 0.00 0.00 01-DEC-00:10
                 
Annual Sum or Average 239149.44         0.00    
Minimum of Months 11211.54 31447.16   18.96 18.33 0.00 0.00  
Maximum of Months 926575.10 1677546.28   50.98 36.85 0.00 0.00  



Table of Contents

Report: CondLoopDemandReportMonthly

For: SWHSYS1

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 0.00 0.00 01-JAN-00:03 57.30 57.30 16749.86 56724.50 31-JAN-12:20
February 0.00 0.00 01-FEB-00:03 56.09 56.09 17065.26 56958.23 17-FEB-12:10
March 0.00 0.00 01-MAR-00:10 56.45 56.45 17816.20 56766.04 01-MAR-12:10
April 0.00 0.00 01-APR-00:10 56.31 56.31 16180.23 55002.56 03-APR-11:30
May 0.00 0.00 01-MAY-00:10 57.44 57.44 15808.99 52525.96 01-MAY-11:20
June 0.00 0.00 01-JUN-00:10 56.43 56.43 15244.22 49319.85 01-JUN-12:00
July 0.00 0.00 01-JUL-00:10 57.11 57.11 13521.26 46491.09 03-JUL-12:00
August 0.00 0.00 01-AUG-00:03 57.60 57.60 14418.57 45017.64 01-AUG-11:20
September 0.00 0.00 01-SEP-00:10 57.13 57.13 13833.22 46431.87 29-SEP-12:00
October 0.00 0.00 01-OCT-00:10 57.29 57.29 14433.94 49237.05 31-OCT-11:20
November 0.00 0.00 01-NOV-00:10 56.74 56.74 15466.14 52362.90 30-NOV-12:15
December 0.00 0.00 01-DEC-00:10 56.85 56.85 15767.00 54971.65 29-DEC-12:40
                 
Annual Sum or Average 0.00         15516.53    
Minimum of Months 0.00 0.00   56.09 56.09 13521.26 45017.64  
Maximum of Months 0.00 0.00   57.60 57.60 17816.20 56958.23  



Table of Contents

Report: CondLoopDemandReportMonthly

For: TOWERWATERSYS

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 23.12 16999.20 23-JAN-07:20 21.16 20.31 1903.47 159629.52 24-JAN-04:11
February 19.27 11541.60 02-FEB-04:33 21.14 20.30 2709.51 154752.04 05-FEB-01:03
March 30920.94 2092358.79 14-MAR-13:00 28.30 23.83 2933.76 145197.11 23-MAR-09:30
April 9303.84 600853.36 07-APR-14:00 23.17 21.10 2182.49 137848.61 17-APR-15:50
May 97328.91 2097179.67 10-MAY-13:40 28.32 22.22 678.78 116031.59 01-MAY-08:70
June 634016.81 5936905.14 27-JUN-07:40 31.31 26.81 422.63 97995.97 03-JUN-06:20
July 1257562.38 6682912.17 05-JUL-16:00 32.60 27.17 135.97 70260.31 06-JUL-05:40
August 912779.54 6908633.30 15-AUG-14:40 32.98 27.35 418.56 49046.25 24-AUG-07:00
September 364041.22 4823453.06 15-SEP-11:00 29.40 25.20 324.92 58001.44 06-SEP-19:50
October 32161.51 1005383.23 11-OCT-15:00 24.56 21.10 1864.77 135397.24 17-OCT-12:50
November 4478.72 328546.76 16-NOV-13:10 22.23 21.10 3347.36 145981.34 26-NOV-11:02
December 25.07 8465.79 15-DEC-06:40 21.13 20.36 3154.85 163356.92 23-DEC-05:01
                 
Annual Sum or Average 281124.94         1665.71    
Minimum of Months 19.27 8465.79   21.13 20.30 135.97 49046.25  
Maximum of Months 1257562.38 6908633.30   32.98 27.35 3347.36 163356.92  



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: BASEMENT

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: CORE_BOTTOM

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: CORE_MID

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: CORE_TOP

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: GROUNDFLOOR_PLENUM

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00 0.00
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: MIDFLOOR_PLENUM

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00 0.00
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: TOPFLOOR_PLENUM

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00 0.00
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: DATACENTER_MID_ZN_6

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: VAV_BOT WITH REHEAT

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.906812E+10 0.00 15133938.07 0.366844E+10 0.00 0.00
February 0.804957E+10 0.00 30370707.14 0.371524E+10 0.00 0.00
March 0.394280E+10 0.00 0.636447E+10 0.692461E+10 0.00 0.00
April 0.633339E+09 0.00 0.263950E+10 0.789285E+10 0.00 0.00
May 0.132846E+09 0.00 0.198913E+11 0.825741E+10 0.00 0.00
June 1029605.95 0.00 0.873465E+11 0.120273E+11 0.00 0.00
July 0.00 0.00 0.155884E+12 0.143085E+11 0.00 0.00
August 0.00 0.00 0.137201E+12 0.155038E+11 0.00 0.00
September 32193965.40 0.00 0.531998E+11 0.890107E+10 0.00 0.00
October 0.525694E+09 0.00 0.736889E+10 0.673504E+10 0.00 0.00
November 0.146542E+10 0.00 0.119546E+10 0.555776E+10 0.00 0.00
December 0.768507E+10 0.00 23996758.26 0.471089E+10 0.00 0.00
             
Annual Sum or Average 0.315361E+11 0.00 0.471160E+12 0.982029E+11 0.00 0.00
Minimum of Months 0.00 0.00 15133938.07 0.366844E+10 0.00 0.00
Maximum of Months 0.906812E+10 0.00 0.155884E+12 0.155038E+11 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: VAV_MID WITH REHEAT

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.372071E+12 0.00 74783.10 0.381633E+11 0.00 0.00
February 0.314018E+12 0.00 6151402.80 0.346858E+11 0.00 0.00
March 0.123991E+12 0.00 0.439210E+11 0.411189E+11 0.00 0.00
April 0.414114E+11 0.00 0.172933E+11 0.431285E+11 0.00 0.00
May 0.205219E+10 0.00 0.168731E+12 0.620076E+11 0.00 0.00
June 0.353283E+09 0.00 0.719590E+12 0.915413E+11 0.00 0.00
July 2898.86 0.00 0.121862E+13 0.105195E+12 0.00 0.00
August 385356.70 0.00 0.100915E+13 0.103828E+12 0.00 0.00
September 0.146674E+10 0.00 0.450278E+12 0.682522E+11 0.00 0.00
October 0.299935E+11 0.00 0.557712E+11 0.427206E+11 0.00 0.00
November 0.986786E+11 0.00 0.700992E+10 0.331545E+11 0.00 0.00
December 0.311154E+12 0.00 647703.50 0.353746E+11 0.00 0.00
             
Annual Sum or Average 0.129519E+13 0.00 0.369036E+13 0.699171E+12 0.00 0.00
Minimum of Months 2898.86 0.00 74783.10 0.331545E+11 0.00 0.00
Maximum of Months 0.372071E+12 0.00 0.121862E+13 0.105195E+12 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: VAV_TOP WITH REHEAT

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.656512E+11 0.00 1891717.87 0.462767E+10 0.00 0.00
February 0.577288E+11 0.00 2999215.84 0.424507E+10 0.00 0.00
March 0.251962E+11 0.00 0.461181E+10 0.428901E+10 0.00 0.00
April 0.811930E+10 0.00 0.165045E+10 0.387024E+10 0.00 0.00
May 0.905914E+09 0.00 0.168839E+11 0.543736E+10 0.00 0.00
June 51791322.99 0.00 0.776562E+11 0.893575E+10 0.00 0.00
July 0.00 0.00 0.133148E+12 0.106676E+11 0.00 0.00
August 4867539.30 0.00 0.108163E+12 0.100621E+11 0.00 0.00
September 0.526240E+09 0.00 0.445474E+11 0.595804E+10 0.00 0.00
October 0.721670E+10 0.00 0.485472E+10 0.366740E+10 0.00 0.00
November 0.186351E+11 0.00 0.655271E+09 0.328096E+10 0.00 0.00
December 0.597004E+11 0.00 3384188.89 0.449574E+10 0.00 0.00
             
Annual Sum or Average 0.243737E+12 0.00 0.392178E+12 0.695369E+11 0.00 0.00
Minimum of Months 0.00 0.00 1891717.87 0.328096E+10 0.00 0.00
Maximum of Months 0.656512E+11 0.00 0.133148E+12 0.106676E+11 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: CAV_BAS

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.00 0.00 84197.20 0.146107E+11 0.00 0.00
February 0.00 0.00 196614.84 0.133678E+11 0.00 0.00
March 0.00 0.00 0.351920E+10 0.161749E+11 0.00 0.00
April 0.00 0.00 0.607669E+09 0.147732E+11 0.00 0.00
May 0.00 0.00 0.831938E+10 0.158317E+11 0.00 0.00
June 0.00 0.00 0.420856E+11 0.155556E+11 0.00 0.00
July 0.00 0.00 0.802959E+11 0.156803E+11 0.00 0.00
August 0.00 0.00 0.705731E+11 0.170960E+11 0.00 0.00
September 0.00 0.00 0.300396E+11 0.159944E+11 0.00 0.00
October 0.00 0.00 0.290239E+10 0.156836E+11 0.00 0.00
November 0.00 0.00 0.561211E+09 0.151578E+11 0.00 0.00
December 0.00 0.00 1701705.22 0.149483E+11 0.00 0.00
             
Annual Sum or Average 0.00 0.00 0.238906E+12 0.184874E+12 0.00 0.00
Minimum of Months 0.00 0.00 84197.20 0.133678E+11 0.00 0.00
Maximum of Months 0.00 0.00 0.802959E+11 0.170960E+11 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: AIRLOOP DATACENTER BASEMENT

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.00 0.00 0.105887E+11 0.231346E+12 0.00 48.43
February 0.00 0.00 0.153626E+11 0.291344E+12 0.00 73.89
March 0.00 0.00 0.485942E+11 0.310132E+12 0.00 74.40
April 0.00 0.00 0.759318E+11 0.318839E+12 0.00 76.55
May 0.00 0.00 0.127577E+11 0.180117E+12 0.00 29.10
June 0.00 0.00 0.245999E+12 0.191545E+12 0.00 14.69
July 0.00 0.00 0.972006E+12 0.317513E+12 0.00 0.81
August 0.00 0.00 0.110106E+13 0.351590E+12 0.00 2.83
September 0.00 0.00 0.259479E+11 0.112037E+12 0.00 3.76
October 0.00 0.00 0.154805E+11 0.205205E+12 0.00 38.23
November 0.00 0.00 0.320947E+11 0.316105E+12 0.00 79.31
December 0.00 0.00 0.243040E+11 0.365805E+12 0.00 97.13
             
Annual Sum or Average 0.00 0.00 0.258013E+13 0.319158E+13 0.00 539.14
Minimum of Months 0.00 0.00 0.105887E+11 0.112037E+12 0.00 0.81
Maximum of Months 0.00 0.00 0.110106E+13 0.365805E+12 0.00 97.13



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: AIRLOOP DATACENTER BOT

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.00 0.00 0.380127E+10 0.236874E+10 0.00 0.00
February 0.00 0.00 0.954519E+10 0.335001E+10 0.00 0.00
March 0.00 0.00 0.184723E+11 0.511268E+10 0.00 0.00
April 0.00 0.00 0.243543E+11 0.593985E+10 0.00 0.00
May 0.00 0.00 0.718220E+10 0.298971E+10 0.00 0.00
June 0.00 0.00 0.139140E+11 0.434928E+10 0.00 0.00
July 0.00 0.00 0.215217E+11 0.630968E+10 0.00 0.00
August 0.00 0.00 0.275734E+11 0.742688E+10 0.00 0.00
September 0.00 0.00 0.732514E+10 0.297276E+10 0.00 0.00
October 0.00 0.00 0.128314E+11 0.400340E+10 0.00 0.00
November 0.00 0.00 0.179493E+11 0.487798E+10 0.00 0.00
December 0.00 0.00 0.237053E+11 0.601693E+10 0.00 0.00
             
Annual Sum or Average 0.00 0.00 0.188176E+12 0.557179E+11 0.00 0.00
Minimum of Months 0.00 0.00 0.380127E+10 0.236874E+10 0.00 0.00
Maximum of Months 0.00 0.00 0.275734E+11 0.742688E+10 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: AIRLOOP DATACENTER MID

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.00 0.00 0.709524E+10 0.164564E+11 0.00 0.00
February 0.00 0.00 0.600561E+11 0.259969E+11 0.00 0.00
March 0.00 0.00 0.153815E+12 0.448993E+11 0.00 0.00
April 0.00 0.00 0.217144E+12 0.542981E+11 0.00 0.00
May 0.00 0.00 0.607956E+11 0.271523E+11 0.00 0.00
June 0.00 0.00 0.129390E+12 0.409803E+11 0.00 0.00
July 0.00 0.00 0.204061E+12 0.600711E+11 0.00 0.00
August 0.00 0.00 0.260685E+12 0.705414E+11 0.00 0.00
September 0.00 0.00 0.628552E+11 0.271324E+11 0.00 0.00
October 0.00 0.00 0.105389E+12 0.352372E+11 0.00 0.00
November 0.00 0.00 0.147390E+12 0.425106E+11 0.00 0.00
December 0.00 0.00 0.189701E+12 0.512794E+11 0.00 0.00
             
Annual Sum or Average 0.00 0.00 0.159838E+13 0.496555E+12 0.00 0.00
Minimum of Months 0.00 0.00 0.709524E+10 0.164564E+11 0.00 0.00
Maximum of Months 0.00 0.00 0.260685E+12 0.705414E+11 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: AIRLOOP DATACENTER TOP

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.00 0.00 0.256260E+09 0.156079E+10 0.00 0.00
February 0.00 0.00 0.430140E+10 0.227413E+10 0.00 0.00
March 0.00 0.00 0.136487E+11 0.419936E+10 0.00 0.00
April 0.00 0.00 0.205388E+11 0.526234E+10 0.00 0.00
May 0.00 0.00 0.551223E+10 0.263151E+10 0.00 0.00
June 0.00 0.00 0.128219E+11 0.410606E+10 0.00 0.00
July 0.00 0.00 0.204624E+11 0.605312E+10 0.00 0.00
August 0.00 0.00 0.260263E+11 0.708458E+10 0.00 0.00
September 0.00 0.00 0.577503E+10 0.264194E+10 0.00 0.00
October 0.00 0.00 0.897359E+10 0.326074E+10 0.00 0.00
November 0.00 0.00 0.127882E+11 0.392932E+10 0.00 0.00
December 0.00 0.00 0.169090E+11 0.479219E+10 0.00 0.00
             
Annual Sum or Average 0.00 0.00 0.148014E+12 0.477961E+11 0.00 0.00
Minimum of Months 0.00 0.00 0.256260E+09 0.156079E+10 0.00 0.00
Maximum of Months 0.00 0.00 0.260263E+11 0.708458E+10 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: VAV_BOT WITH REHEAT

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.366844E+10 15133938.07 0.906812E+10 0.643486E+11 0.00 0.00 0.00 0.00
February 0.371524E+10 30370707.14 0.804957E+10 0.561444E+11 0.00 0.00 0.00 0.00
March 0.692461E+10 0.636447E+10 0.394280E+10 0.238208E+11 3729723.55 0.00 0.00 0.00
April 0.789285E+10 0.263950E+10 0.633339E+09 0.591436E+10 0.00 0.00 0.00 0.00
May 0.825741E+10 0.198913E+11 0.132846E+09 0.758149E+09 2542438.39 0.00 0.00 0.00
June 0.120273E+11 0.873465E+11 1029605.95 0.188627E+09 0.288273E+10 0.00 0.00 0.00
July 0.143085E+11 0.155884E+12 0.00 0.164848E+09 0.851849E+10 0.00 0.00 0.00
August 0.155038E+11 0.137201E+12 0.00 0.710962E+09 0.343233E+10 0.00 0.00 0.00
September 0.890107E+10 0.531998E+11 32193965.40 0.238683E+09 0.420978E+09 0.00 0.00 0.00
October 0.673504E+10 0.736889E+10 0.525694E+09 0.468891E+10 0.00 0.00 0.00 0.00
November 0.555776E+10 0.119546E+10 0.146542E+10 0.115862E+11 0.00 0.00 0.00 0.00
December 0.471089E+10 23996758.26 0.768507E+10 0.446339E+11 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.982029E+11 0.471160E+12 0.315361E+11 0.213198E+12 0.152608E+11 0.00 0.00 0.00
Minimum of Months 0.366844E+10 15133938.07 0.00 0.164848E+09 0.00 0.00 0.00 0.00
Maximum of Months 0.155038E+11 0.155884E+12 0.906812E+10 0.643486E+11 0.851849E+10 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: VAV_MID WITH REHEAT

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.381633E+11 74783.10 0.372071E+12 0.698550E+12 0.00 0.00 0.00 0.00
February 0.346858E+11 6151402.80 0.314018E+12 0.642468E+12 0.00 0.00 0.00 0.00
March 0.411189E+11 0.439210E+11 0.123991E+12 0.395699E+12 64807.12 0.00 0.00 0.00
April 0.431285E+11 0.172933E+11 0.414114E+11 0.138644E+12 0.00 0.00 0.00 0.00
May 0.620076E+11 0.168731E+12 0.205219E+10 0.165913E+11 21402971.27 0.00 0.00 0.00
June 0.915413E+11 0.719590E+12 0.353283E+09 0.390163E+10 0.285988E+11 0.00 0.00 0.00
July 0.105195E+12 0.121862E+13 2898.86 0.202102E+10 0.828846E+11 0.00 0.00 0.00
August 0.103828E+12 0.100915E+13 385356.70 0.753421E+10 0.330101E+11 0.00 0.00 0.00
September 0.682522E+11 0.450278E+12 0.146674E+10 0.591964E+10 0.444798E+10 0.00 0.00 0.00
October 0.427206E+11 0.557712E+11 0.299935E+11 0.920796E+11 0.00 0.00 0.00 0.00
November 0.331545E+11 0.700992E+10 0.986786E+11 0.239508E+12 0.00 0.00 0.00 0.00
December 0.353746E+11 647703.50 0.311154E+12 0.623879E+12 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.699171E+12 0.369036E+13 0.129519E+13 0.286680E+13 0.148963E+12 0.00 0.00 0.00
Minimum of Months 0.331545E+11 74783.10 2898.86 0.202102E+10 0.00 0.00 0.00 0.00
Maximum of Months 0.105195E+12 0.121862E+13 0.372071E+12 0.698550E+12 0.828846E+11 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: VAV_TOP WITH REHEAT

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.462767E+10 1891717.87 0.656512E+11 0.689482E+11 0.00 0.00 0.00 0.00
February 0.424507E+10 2999215.84 0.577288E+11 0.630632E+11 0.00 0.00 0.00 0.00
March 0.428901E+10 0.461181E+10 0.251962E+11 0.427895E+11 0.00 0.00 0.00 0.00
April 0.387024E+10 0.165045E+10 0.811930E+10 0.184650E+11 0.00 0.00 0.00 0.00
May 0.543736E+10 0.168839E+11 0.905914E+09 0.246982E+10 0.00 0.00 0.00 0.00
June 0.893575E+10 0.776562E+11 51791322.99 0.498475E+09 0.234570E+10 0.00 0.00 0.00
July 0.106676E+11 0.133148E+12 0.00 0.157591E+09 0.700386E+10 0.00 0.00 0.00
August 0.100621E+11 0.108163E+12 4867539.30 0.733812E+09 0.252253E+10 0.00 0.00 0.00
September 0.595804E+10 0.445474E+11 0.526240E+09 0.926337E+09 0.267050E+09 0.00 0.00 0.00
October 0.366740E+10 0.485472E+10 0.721670E+10 0.130672E+11 0.00 0.00 0.00 0.00
November 0.328096E+10 0.655271E+09 0.186351E+11 0.308157E+11 0.00 0.00 0.00 0.00
December 0.449574E+10 3384188.89 0.597004E+11 0.618659E+11 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.695369E+11 0.392178E+12 0.243737E+12 0.303801E+12 0.121391E+11 0.00 0.00 0.00
Minimum of Months 0.328096E+10 1891717.87 0.00 0.157591E+09 0.00 0.00 0.00 0.00
Maximum of Months 0.106676E+11 0.133148E+12 0.656512E+11 0.689482E+11 0.700386E+10 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: CAV_BAS

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.146107E+11 84197.20 0.00 0.00 0.00 0.00 0.00 0.00
February 0.133678E+11 196614.84 0.00 0.00 0.00 0.00 0.00 0.00
March 0.161749E+11 0.351920E+10 0.00 0.00 0.00 0.00 0.00 0.00
April 0.147732E+11 0.607669E+09 0.00 0.00 0.00 0.00 0.00 0.00
May 0.158317E+11 0.831938E+10 0.00 0.00 0.00 0.00 0.00 0.00
June 0.155556E+11 0.420856E+11 0.00 0.00 0.00 0.00 0.00 0.00
July 0.156803E+11 0.802959E+11 0.00 0.00 0.00 0.00 0.00 0.00
August 0.170960E+11 0.705731E+11 0.00 0.00 0.00 0.00 0.00 0.00
September 0.159944E+11 0.300396E+11 0.00 0.00 0.00 0.00 0.00 0.00
October 0.156836E+11 0.290239E+10 0.00 0.00 0.00 0.00 0.00 0.00
November 0.151578E+11 0.561211E+09 0.00 0.00 0.00 0.00 0.00 0.00
December 0.149483E+11 1701705.22 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.184874E+12 0.238906E+12 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.133678E+11 84197.20 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.170960E+11 0.802959E+11 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: AIRLOOP DATACENTER BASEMENT

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.969086E+11 0.635088E+10 0.00 0.00 0.00 0.129616E+12 0.00 0.00
February 0.875304E+11 0.101905E+11 0.00 0.00 0.00 0.197752E+12 0.00 0.00
March 0.969086E+11 0.353730E+11 0.00 0.00 0.00 0.199106E+12 0.00 0.00
April 0.937825E+11 0.566671E+11 0.00 0.00 0.00 0.204869E+12 0.00 0.00
May 0.969086E+11 0.776230E+10 0.00 0.00 0.00 0.778624E+11 0.00 0.00
June 0.937825E+11 0.187737E+12 0.00 0.00 0.00 0.393237E+11 0.00 0.00
July 0.969086E+11 0.753583E+12 0.00 0.00 0.00 0.217203E+10 0.00 0.00
August 0.969086E+11 0.853980E+12 0.00 0.00 0.00 0.756771E+10 0.00 0.00
September 0.937825E+11 0.177885E+11 0.00 0.00 0.00 0.100499E+11 0.00 0.00
October 0.969086E+11 0.994863E+10 0.00 0.00 0.00 0.102304E+12 0.00 0.00
November 0.937825E+11 0.229845E+11 0.00 0.00 0.00 0.212257E+12 0.00 0.00
December 0.969086E+11 0.164990E+11 0.00 0.00 0.00 0.259921E+12 0.00 0.00
                 
Annual Sum or Average 0.114102E+13 0.197887E+13 0.00 0.00 0.00 0.144280E+13 0.00 0.00
Minimum of Months 0.875304E+11 0.635088E+10 0.00 0.00 0.00 0.217203E+10 0.00 0.00
Maximum of Months 0.969086E+11 0.853980E+12 0.00 0.00 0.00 0.259921E+12 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: AIRLOOP DATACENTER BOT

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.153733E+10 0.296986E+10 0.00 0.00 0.00 0.00 0.00 0.00
February 0.138856E+10 0.758374E+10 0.00 0.00 0.00 0.00 0.00 0.00
March 0.153733E+10 0.148969E+11 0.00 0.00 0.00 0.00 0.00 0.00
April 0.148774E+10 0.199022E+11 0.00 0.00 0.00 0.00 0.00 0.00
May 0.153733E+10 0.572982E+10 0.00 0.00 0.00 0.00 0.00 0.00
June 0.148774E+10 0.110525E+11 0.00 0.00 0.00 0.00 0.00 0.00
July 0.153733E+10 0.167493E+11 0.00 0.00 0.00 0.00 0.00 0.00
August 0.153733E+10 0.216839E+11 0.00 0.00 0.00 0.00 0.00 0.00
September 0.148774E+10 0.584012E+10 0.00 0.00 0.00 0.00 0.00 0.00
October 0.153733E+10 0.103654E+11 0.00 0.00 0.00 0.00 0.00 0.00
November 0.148774E+10 0.145591E+11 0.00 0.00 0.00 0.00 0.00 0.00
December 0.153733E+10 0.192257E+11 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.181009E+11 0.150559E+12 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.138856E+10 0.296986E+10 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.153733E+10 0.216839E+11 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: AIRLOOP DATACENTER MID

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.147517E+11 0.539046E+10 0.00 0.00 0.00 0.00 0.00 0.00
February 0.133241E+11 0.473833E+11 0.00 0.00 0.00 0.00 0.00 0.00
March 0.147517E+11 0.123668E+12 0.00 0.00 0.00 0.00 0.00 0.00
April 0.142758E+11 0.177122E+12 0.00 0.00 0.00 0.00 0.00 0.00
May 0.147517E+11 0.483950E+11 0.00 0.00 0.00 0.00 0.00 0.00
June 0.142758E+11 0.102685E+12 0.00 0.00 0.00 0.00 0.00 0.00
July 0.147517E+11 0.158741E+12 0.00 0.00 0.00 0.00 0.00 0.00
August 0.147517E+11 0.204895E+12 0.00 0.00 0.00 0.00 0.00 0.00
September 0.142758E+11 0.499986E+11 0.00 0.00 0.00 0.00 0.00 0.00
October 0.147517E+11 0.849039E+11 0.00 0.00 0.00 0.00 0.00 0.00
November 0.142758E+11 0.119155E+12 0.00 0.00 0.00 0.00 0.00 0.00
December 0.147517E+11 0.153174E+12 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.173689E+12 0.127551E+13 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.133241E+11 0.539046E+10 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.147517E+11 0.204895E+12 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: AIRLOOP DATACENTER TOP

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.149889E+10 0.194364E+09 0.00 0.00 0.00 0.00 0.00 0.00
February 0.135384E+10 0.338111E+10 0.00 0.00 0.00 0.00 0.00 0.00
March 0.149889E+10 0.109483E+11 0.00 0.00 0.00 0.00 0.00 0.00
April 0.145054E+10 0.167270E+11 0.00 0.00 0.00 0.00 0.00 0.00
May 0.149889E+10 0.437961E+10 0.00 0.00 0.00 0.00 0.00 0.00
June 0.145054E+10 0.101664E+11 0.00 0.00 0.00 0.00 0.00 0.00
July 0.149889E+10 0.159082E+11 0.00 0.00 0.00 0.00 0.00 0.00
August 0.149889E+10 0.204406E+11 0.00 0.00 0.00 0.00 0.00 0.00
September 0.145054E+10 0.458363E+10 0.00 0.00 0.00 0.00 0.00 0.00
October 0.149889E+10 0.721174E+10 0.00 0.00 0.00 0.00 0.00 0.00
November 0.145054E+10 0.103094E+11 0.00 0.00 0.00 0.00 0.00 0.00
December 0.149889E+10 0.136157E+11 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.176483E+11 0.117866E+12 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.135384E+10 0.194364E+09 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.149889E+10 0.204406E+11 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: VAV_BOT WITH REHEAT

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.366844E+10 0.906812E+10 15133938.07 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.371524E+10 0.804957E+10 30370707.14 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.692461E+10 0.394280E+10 0.636447E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.789285E+10 0.633339E+09 0.263950E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.825741E+10 0.132846E+09 0.198913E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.120273E+11 1029605.95 0.873465E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.143085E+11 0.00 0.155884E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.155038E+11 0.00 0.137201E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.890107E+10 32193965.40 0.531998E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.673504E+10 0.525694E+09 0.736889E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.555776E+10 0.146542E+10 0.119546E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.471089E+10 0.768507E+10 23996758.26 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.982029E+11 0.315361E+11 0.471160E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.366844E+10 0.00 15133938.07 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.155038E+11 0.906812E+10 0.155884E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: VAV_MID WITH REHEAT

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.381633E+11 0.372071E+12 74783.10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.346858E+11 0.314018E+12 6151402.80 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.411189E+11 0.123991E+12 0.439210E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.431285E+11 0.414114E+11 0.172933E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.620076E+11 0.205219E+10 0.168731E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.915413E+11 0.353283E+09 0.719590E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.105195E+12 2898.86 0.121862E+13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.103828E+12 385356.70 0.100915E+13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.682522E+11 0.146674E+10 0.450278E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.427206E+11 0.299935E+11 0.557712E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.331545E+11 0.986786E+11 0.700992E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.353746E+11 0.311154E+12 647703.50 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.699171E+12 0.129519E+13 0.369036E+13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.331545E+11 2898.86 74783.10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.105195E+12 0.372071E+12 0.121862E+13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: VAV_TOP WITH REHEAT

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.462767E+10 0.656512E+11 1891717.87 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.424507E+10 0.577288E+11 2999215.84 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.428901E+10 0.251962E+11 0.461181E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.387024E+10 0.811930E+10 0.165045E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.543736E+10 0.905914E+09 0.168839E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.893575E+10 51791322.99 0.776562E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.106676E+11 0.00 0.133148E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.100621E+11 4867539.30 0.108163E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.595804E+10 0.526240E+09 0.445474E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.366740E+10 0.721670E+10 0.485472E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.328096E+10 0.186351E+11 0.655271E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.449574E+10 0.597004E+11 3384188.89 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.695369E+11 0.243737E+12 0.392178E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.328096E+10 0.00 1891717.87 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.106676E+11 0.656512E+11 0.133148E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: CAV_BAS

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.146107E+11 0.00 84197.20 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.133678E+11 0.00 196614.84 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.161749E+11 0.00 0.351920E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.147732E+11 0.00 0.607669E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.158317E+11 0.00 0.831938E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.155556E+11 0.00 0.420856E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.156803E+11 0.00 0.802959E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.170960E+11 0.00 0.705731E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.159944E+11 0.00 0.300396E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.156836E+11 0.00 0.290239E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.151578E+11 0.00 0.561211E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.149483E+11 0.00 1701705.22 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.184874E+12 0.00 0.238906E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.133678E+11 0.00 84197.20 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.170960E+11 0.00 0.802959E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: AIRLOOP DATACENTER BASEMENT

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.969086E+11 0.00 0.105887E+11 0.00 0.423777E+10 0.00 0.00 0.00 0.130200E+12 0.00 0.00 0.00
February 0.875304E+11 0.00 0.153626E+11 0.00 0.517208E+10 0.00 0.00 0.00 0.198642E+12 0.00 0.00 0.00
March 0.969086E+11 0.00 0.485942E+11 0.00 0.132212E+11 0.00 0.00 0.00 0.200002E+12 0.00 0.00 0.00
April 0.937825E+11 0.00 0.759318E+11 0.00 0.192647E+11 0.00 0.00 0.00 0.205791E+12 0.00 0.00 0.00
May 0.969086E+11 0.00 0.127577E+11 0.00 0.499537E+10 0.00 0.00 0.00 0.782129E+11 0.00 0.00 0.00
June 0.937825E+11 0.00 0.245999E+12 0.00 0.582620E+11 0.00 0.00 0.00 0.395007E+11 0.00 0.00 0.00
July 0.969086E+11 0.00 0.972006E+12 0.00 0.218422E+12 0.00 0.00 0.00 0.218181E+10 0.00 0.00 0.00
August 0.969086E+11 0.00 0.110106E+13 0.00 0.247080E+12 0.00 0.00 0.00 0.760178E+10 0.00 0.00 0.00
September 0.937825E+11 0.00 0.259479E+11 0.00 0.815941E+10 0.00 0.00 0.00 0.100952E+11 0.00 0.00 0.00
October 0.969086E+11 0.00 0.154805E+11 0.00 0.553191E+10 0.00 0.00 0.00 0.102764E+12 0.00 0.00 0.00
November 0.937825E+11 0.00 0.320947E+11 0.00 0.911021E+10 0.00 0.00 0.00 0.213212E+12 0.00 0.00 0.00
December 0.969086E+11 0.00 0.243040E+11 0.00 0.780505E+10 0.00 0.00 0.00 0.261091E+12 0.00 0.00 0.00
                         
Annual Sum or Average 0.114102E+13 0.00 0.258013E+13 0.00 0.601261E+12 0.00 0.00 0.00 0.144929E+13 0.00 0.00 0.00
Minimum of Months 0.875304E+11 0.00 0.105887E+11 0.00 0.423777E+10 0.00 0.00 0.00 0.218181E+10 0.00 0.00 0.00
Maximum of Months 0.969086E+11 0.00 0.110106E+13 0.00 0.247080E+12 0.00 0.00 0.00 0.261091E+12 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: AIRLOOP DATACENTER BOT

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.153733E+10 0.00 0.380127E+10 0.00 0.831406E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.138856E+10 0.00 0.954519E+10 0.00 0.196145E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.153733E+10 0.00 0.184723E+11 0.00 0.357535E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.148774E+10 0.00 0.243543E+11 0.00 0.445211E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.153733E+10 0.00 0.718220E+10 0.00 0.145238E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.148774E+10 0.00 0.139140E+11 0.00 0.286154E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.153733E+10 0.00 0.215217E+11 0.00 0.477235E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.153733E+10 0.00 0.275734E+11 0.00 0.588954E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.148774E+10 0.00 0.732514E+10 0.00 0.148502E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.153733E+10 0.00 0.128314E+11 0.00 0.246607E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.148774E+10 0.00 0.179493E+11 0.00 0.339024E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.153733E+10 0.00 0.237053E+11 0.00 0.447960E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.181009E+11 0.00 0.188176E+12 0.00 0.376171E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.138856E+10 0.00 0.380127E+10 0.00 0.831406E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.153733E+10 0.00 0.275734E+11 0.00 0.588954E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: AIRLOOP DATACENTER MID

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.147517E+11 0.00 0.709524E+10 0.00 0.170479E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.133241E+11 0.00 0.600561E+11 0.00 0.126728E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.147517E+11 0.00 0.153815E+12 0.00 0.301477E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.142758E+11 0.00 0.217144E+12 0.00 0.400223E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.147517E+11 0.00 0.607956E+11 0.00 0.124006E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.142758E+11 0.00 0.129390E+12 0.00 0.267045E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.147517E+11 0.00 0.204061E+12 0.00 0.453194E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.147517E+11 0.00 0.260685E+12 0.00 0.557897E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.142758E+11 0.00 0.628552E+11 0.00 0.128566E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.147517E+11 0.00 0.105389E+12 0.00 0.204855E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.142758E+11 0.00 0.147390E+12 0.00 0.282348E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.147517E+11 0.00 0.189701E+12 0.00 0.365277E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.173689E+12 0.00 0.159838E+13 0.00 0.322867E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.133241E+11 0.00 0.709524E+10 0.00 0.170479E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.147517E+11 0.00 0.260685E+12 0.00 0.557897E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: AIRLOOP DATACENTER TOP

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.149889E+10 0.00 0.256260E+09 0.00 61895420.68 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.135384E+10 0.00 0.430140E+10 0.00 0.920289E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.149889E+10 0.00 0.136487E+11 0.00 0.270047E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.145054E+10 0.00 0.205388E+11 0.00 0.381180E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.149889E+10 0.00 0.551223E+10 0.00 0.113262E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.145054E+10 0.00 0.128219E+11 0.00 0.265552E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.149889E+10 0.00 0.204624E+11 0.00 0.455423E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.149889E+10 0.00 0.260263E+11 0.00 0.558569E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.145054E+10 0.00 0.577503E+10 0.00 0.119140E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.149889E+10 0.00 0.897359E+10 0.00 0.176185E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.145054E+10 0.00 0.127882E+11 0.00 0.247878E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.149889E+10 0.00 0.169090E+11 0.00 0.329330E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.176483E+11 0.00 0.148014E+12 0.00 0.301478E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.135384E+10 0.00 0.256260E+09 0.00 61895420.68 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.149889E+10 0.00 0.260263E+11 0.00 0.558569E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: BASEMENT

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.641128E+10 0.00 0.00 76497603.53 0.00 0.00 0.598019E+11 0.00 0.39
February 0.815931E+10 0.00 0.00 72984562.49 0.00 0.00 0.520096E+11 0.00 0.39
March 0.652650E+09 0.00 0.00 0.132875E+09 0.00 0.00 0.733161E+11 0.00 0.66
April 0.381446E+09 0.00 0.00 0.121731E+09 0.00 0.00 0.735718E+11 0.00 0.86
May 0.217408E+09 5008595.40 0.00 0.116109E+09 268562.79 0.00 0.704102E+11 0.00 1.31
June 94794231.17 0.310507E+10 0.00 0.102233E+09 33437226.40 0.00 0.442162E+11 0.00 1.44
July 0.138094E+09 0.133628E+11 0.00 70249471.97 58890597.35 0.00 0.166531E+11 0.00 1.16
August 60891714.01 0.787254E+10 0.00 0.108251E+09 19757273.55 0.00 0.311561E+11 0.00 1.40
September 0.406205E+09 0.199133E+10 0.00 0.120146E+09 3603214.30 0.00 0.548611E+11 0.00 1.52
October 0.403732E+09 0.00 0.00 0.135793E+09 0.00 0.00 0.797969E+11 0.00 1.06
November 0.337914E+09 0.00 0.00 0.133977E+09 0.00 0.00 0.779658E+11 0.00 0.78
December 0.729791E+09 0.00 0.00 0.119402E+09 0.00 0.00 0.713394E+11 0.00 0.46
                   
Annual Sum or Average 0.179935E+11 0.263368E+11 0.00 0.131025E+10 0.115957E+09 0.00 0.705098E+12 0.00 0.96
Minimum of Months 60891714.01 0.00 0.00 70249471.97 0.00 0.00 0.166531E+11 0.00 0.39
Maximum of Months 0.815931E+10 0.133628E+11 0.00 0.135793E+09 58890597.35 0.00 0.797969E+11 0.00 1.52



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: CORE_BOTTOM

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.115515E+11 0.00 0.00 39037227.06 0.00 0.00 0.266269E+11 0.00 0.45
February 0.822738E+10 0.00 0.00 45387095.94 0.00 0.00 0.286211E+11 0.00 0.46
March 0.255164E+10 394259.02 0.00 0.106234E+09 0.00 0.00 0.544146E+11 0.00 0.60
April 0.395612E+10 0.00 0.00 0.106276E+09 0.00 0.00 0.600908E+11 0.00 0.75
May 0.348938E+10 6881699.57 0.00 93989967.82 16760330.66 0.00 0.523591E+11 0.00 0.93
June 0.222856E+10 0.337830E+10 0.00 83281855.23 0.609892E+09 0.00 0.316768E+11 0.00 1.10
July 0.319848E+10 0.122319E+11 0.00 48589560.99 0.261135E+10 0.00 0.109977E+11 0.00 1.01
August 0.568027E+10 0.781118E+10 0.00 81539144.92 0.160532E+10 0.00 0.221970E+11 0.00 1.20
September 0.306347E+10 0.277118E+10 0.00 83698569.88 68093114.46 0.00 0.366218E+11 0.00 1.01
October 0.209791E+10 0.00 0.00 98655722.47 0.00 0.00 0.560363E+11 0.00 0.75
November 0.137522E+10 0.00 0.00 94880561.42 0.00 0.00 0.548966E+11 0.00 0.60
December 0.298718E+10 0.00 0.00 71772441.92 0.00 0.00 0.457402E+11 0.00 0.48
                   
Annual Sum or Average 0.504071E+11 0.261998E+11 0.00 0.953341E+09 0.491141E+10 0.00 0.480279E+12 0.00 0.78
Minimum of Months 0.137522E+10 0.00 0.00 39037227.06 0.00 0.00 0.109977E+11 0.00 0.45
Maximum of Months 0.115515E+11 0.122319E+11 0.00 0.106276E+09 0.261135E+10 0.00 0.600908E+11 0.00 1.20



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: CORE_MID

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.258950E+12 0.00 0.00 10482567.23 0.00 0.743644E+10 0.175848E+11 0.00 0.43
February 0.237064E+12 0.00 0.00 14281889.93 0.00 0.499925E+10 0.215648E+11 0.00 0.43
March 0.169615E+12 0.00 0.00 0.290916E+09 0.00 0.120550E+09 0.185297E+12 0.00 0.48
April 0.109973E+12 0.00 0.00 0.401159E+09 0.00 0.00 0.286212E+12 0.00 0.54
May 0.415181E+11 21512704.76 0.00 0.643194E+09 0.190857E+09 0.00 0.395331E+12 0.00 0.76
June 0.175019E+11 0.259933E+11 0.00 0.619186E+09 0.253333E+10 0.00 0.248455E+12 0.00 0.87
July 0.119777E+11 0.966078E+11 0.00 0.372754E+09 0.931871E+10 0.00 0.839176E+11 0.00 0.74
August 0.125985E+11 0.526091E+11 0.00 0.648450E+09 0.411917E+10 0.00 0.173987E+12 0.00 0.83
September 0.385059E+11 0.220718E+11 0.00 0.589760E+09 0.267929E+09 0.00 0.273117E+12 0.00 0.83
October 0.874455E+11 0.00 0.00 0.451676E+09 0.00 0.00 0.302929E+12 0.00 0.55
November 0.135523E+12 0.00 0.00 0.263930E+09 32786807.01 0.00 0.201148E+12 0.00 0.46
December 0.242116E+12 0.00 0.00 35668900.36 0.00 0.280880E+10 0.416379E+11 0.00 0.43
                   
Annual Sum or Average 0.136279E+13 0.197304E+12 0.00 0.434146E+10 0.164628E+11 0.153650E+11 0.223118E+13 0.00 0.61
Minimum of Months 0.119777E+11 0.00 0.00 10482567.23 0.00 0.00 0.175848E+11 0.00 0.43
Maximum of Months 0.258950E+12 0.966078E+11 0.00 0.648450E+09 0.931871E+10 0.743644E+10 0.395331E+12 0.00 0.87



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: CORE_TOP

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.201049E+11 0.00 0.00 0.00 0.00 0.279566E+10 0.00 0.00 0.41
February 0.191324E+11 0.00 0.00 0.00 0.00 0.250762E+10 0.00 0.00 0.41
March 0.199035E+11 0.00 0.00 11504912.15 0.00 0.996494E+09 0.806657E+10 0.00 0.47
April 0.156372E+11 0.00 0.00 19854400.94 0.00 0.177430E+09 0.169459E+11 0.00 0.50
May 0.862001E+10 2770052.68 0.00 47472838.03 6729249.80 0.00 0.316783E+11 0.00 0.72
June 0.277492E+10 0.281511E+10 0.00 56450852.43 0.372339E+09 0.00 0.235536E+11 0.00 0.91
July 0.141768E+10 0.104833E+11 0.00 33802240.22 0.105317E+10 0.00 0.817243E+10 0.00 0.79
August 0.167938E+10 0.593553E+10 0.00 59539761.51 0.439216E+09 0.00 0.157096E+11 0.00 0.86
September 0.729328E+10 0.211743E+10 0.00 42841571.88 39900737.64 0.00 0.200361E+11 0.00 0.78
October 0.147590E+11 0.00 0.00 19913108.20 0.00 0.259040E+09 0.157881E+11 0.00 0.50
November 0.195793E+11 0.00 0.00 4040377.58 22708731.02 0.461824E+09 0.438220E+10 0.00 0.43
December 0.201088E+11 0.00 0.00 38218.45 0.00 0.242911E+10 0.232708E+09 0.00 0.41
                   
Annual Sum or Average 0.151010E+12 0.213541E+11 0.00 0.295458E+09 0.193406E+10 0.962718E+10 0.144566E+12 0.00 0.60
Minimum of Months 0.141768E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.41
Maximum of Months 0.201088E+11 0.104833E+11 0.00 59539761.51 0.105317E+10 0.279566E+10 0.316783E+11 0.00 0.91



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.262561E+10 0.00 0.00 0.00 0.00 0.132799E+10 0.00 0.00 0.38
February 0.266985E+10 0.00 0.00 0.00 0.00 0.970340E+09 0.00 0.00 0.37
March 0.325651E+10 58332.36 0.00 2220619.12 0.00 0.214268E+09 0.139331E+10 0.00 0.44
April 0.229550E+10 0.00 0.00 4808510.84 0.00 0.00 0.348686E+10 0.00 0.57
May 0.128994E+10 178201.07 0.00 8220654.77 2508283.73 0.00 0.497440E+10 0.00 0.89
June 0.426187E+09 0.631951E+09 0.00 10201214.57 73360934.32 0.00 0.402414E+10 0.00 1.30
July 0.458067E+09 0.217188E+10 0.00 6420160.57 0.320262E+09 0.00 0.147799E+10 0.00 1.25
August 0.834310E+09 0.130131E+10 0.00 10269696.26 0.200798E+09 0.00 0.260896E+10 0.00 1.37
September 0.108321E+10 0.403432E+09 0.00 6703731.67 8808936.33 0.00 0.314464E+10 0.00 0.96
October 0.228286E+10 0.00 0.00 3880351.52 0.00 0.00 0.282602E+10 0.00 0.55
November 0.321368E+10 0.00 0.00 1203208.35 0.00 0.00 0.110408E+10 0.00 0.38
December 0.351332E+10 0.00 0.00 34104.81 0.00 0.548043E+09 61922503.46 0.00 0.34
                   
Annual Sum or Average 0.239490E+11 0.450881E+10 0.00 53962252.47 0.605738E+09 0.306064E+10 0.251023E+11 0.00 0.73
Minimum of Months 0.426187E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.34
Maximum of Months 0.351332E+10 0.217188E+10 0.00 10269696.26 0.320262E+09 0.132799E+10 0.497440E+10 0.00 1.37



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.297587E+10 0.00 0.00 0.00 0.00 0.146664E+10 0.00 0.00 0.65
February 0.275476E+10 0.00 0.00 414482.87 0.00 0.119130E+10 0.185082E+09 0.00 0.65
March 0.360701E+10 41679.55 0.00 3307503.90 0.00 0.263435E+09 0.172529E+10 0.00 0.76
April 0.280346E+10 0.00 0.00 6788711.56 0.00 5581991.78 0.418811E+10 0.00 1.02
May 0.170480E+10 67918.16 0.00 9866873.98 2897055.40 0.00 0.579428E+10 0.00 1.57
June 0.657060E+09 0.547168E+09 0.00 9906018.26 58660788.95 0.00 0.446497E+10 0.00 1.97
July 0.531987E+09 0.167077E+10 0.00 8188683.49 0.385102E+09 0.00 0.190058E+10 0.00 1.91
August 0.121937E+10 0.849726E+09 0.00 9190101.42 0.237586E+09 0.00 0.249319E+10 0.00 1.98
September 0.149651E+10 0.317452E+09 0.00 8179260.96 15572552.48 0.00 0.358380E+10 0.00 1.59
October 0.282430E+10 0.00 0.00 4101563.07 0.00 1084314.26 0.273752E+10 0.00 0.90
November 0.407159E+10 0.00 0.00 818768.69 0.00 36089824.26 0.696858E+09 0.00 0.65
December 0.351027E+10 0.00 0.00 36412.87 0.00 0.110591E+10 25203481.23 0.00 0.59
                   
Annual Sum or Average 0.281570E+11 0.338522E+10 0.00 60798381.06 0.699818E+09 0.407003E+10 0.277949E+11 0.00 1.19
Minimum of Months 0.531987E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.59
Maximum of Months 0.407159E+10 0.167077E+10 0.00 9906018.26 0.385102E+09 0.146664E+10 0.579428E+10 0.00 1.98



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.289695E+10 0.00 0.00 2478354.29 0.00 0.155593E+10 0.145602E+10 0.00 0.54
February 0.267366E+10 0.00 0.00 3687884.12 0.00 0.121799E+10 0.197470E+10 0.00 0.57
March 0.309809E+10 160230.29 0.00 11495141.68 0.00 0.327960E+09 0.567588E+10 0.00 0.77
April 0.286616E+10 0.00 0.00 10491400.27 0.00 28335977.66 0.685597E+10 0.00 0.98
May 0.204403E+10 3374014.64 0.00 11489166.37 1416163.22 0.00 0.677202E+10 0.00 1.29
June 0.902262E+09 0.702738E+09 0.00 11180322.52 88329761.59 0.00 0.439171E+10 0.00 1.55
July 0.664091E+09 0.245765E+10 0.00 7955889.63 0.411730E+09 0.00 0.150928E+10 0.00 1.48
August 0.118515E+10 0.152275E+10 0.00 14073200.20 0.257975E+09 0.00 0.315216E+10 0.00 1.79
September 0.137542E+10 0.574939E+09 0.00 17013171.08 11300517.24 0.00 0.605077E+10 0.00 1.71
October 0.236354E+10 0.00 0.00 12424676.98 0.00 29829009.12 0.726707E+10 0.00 1.10
November 0.377359E+10 0.00 0.00 5397928.26 0.00 85415867.10 0.359403E+10 0.00 0.65
December 0.363212E+10 0.00 0.00 2049764.63 0.00 0.110402E+10 0.134927E+10 0.00 0.49
                   
Annual Sum or Average 0.274751E+11 0.526161E+10 0.00 0.109737E+09 0.770752E+09 0.434948E+10 0.500489E+11 0.00 1.08
Minimum of Months 0.664091E+09 0.00 0.00 2049764.63 0.00 0.00 0.134927E+10 0.00 0.49
Maximum of Months 0.377359E+10 0.245765E+10 0.00 17013171.08 0.411730E+09 0.155593E+10 0.726707E+10 0.00 1.79



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.456984E+10 0.00 0.00 88227.75 0.00 0.722965E+09 93760350.91 0.00 0.79
February 0.418864E+10 0.00 0.00 819131.38 0.00 0.320477E+09 0.600059E+09 0.00 0.80
March 0.256726E+10 67227.08 0.00 8618321.24 0.00 921323.32 0.520020E+10 0.00 1.04
April 0.971388E+09 0.00 0.00 15059070.00 0.00 0.00 0.922908E+10 0.00 1.57
May 0.132171E+10 1723726.43 0.00 13556548.72 2249928.30 0.00 0.731621E+10 0.00 1.93
June 0.374023E+09 0.752406E+09 0.00 17390454.64 79532841.98 0.00 0.556196E+10 0.00 2.67
July 0.450299E+09 0.273118E+10 0.00 13378778.81 0.278945E+09 0.00 0.193500E+10 0.00 2.48
August 0.783873E+09 0.181893E+10 0.00 18631005.96 71146143.09 0.00 0.396442E+10 0.00 2.92
September 0.109134E+10 0.414840E+09 0.00 11448999.28 8041991.00 0.00 0.443499E+10 0.00 1.90
October 0.199850E+10 0.00 0.00 7247140.66 0.00 0.00 0.523852E+10 0.00 1.23
November 0.250687E+10 0.00 0.00 4329171.37 0.00 0.00 0.382210E+10 0.00 0.87
December 0.419156E+10 0.00 0.00 1280998.65 0.00 16875858.55 0.150319E+10 0.00 0.73
                   
Annual Sum or Average 0.250153E+11 0.571915E+10 0.00 0.111848E+09 0.439915E+09 0.106124E+10 0.488995E+11 0.00 1.58
Minimum of Months 0.374023E+09 0.00 0.00 88227.75 0.00 0.00 93760350.91 0.00 0.73
Maximum of Months 0.456984E+10 0.273118E+10 0.00 18631005.96 0.278945E+09 0.722965E+09 0.922908E+10 0.00 2.92



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.338760E+10 0.00 0.00 0.00 0.00 0.357666E+11 0.00 0.00 0.46
February 0.472548E+10 0.00 0.00 0.00 0.00 0.321448E+11 0.00 0.00 0.46
March 0.222315E+11 0.00 0.00 6191398.10 0.00 0.169585E+11 0.250445E+10 0.00 0.45
April 0.313271E+11 0.00 0.00 6343915.26 0.00 0.420198E+10 0.565778E+10 0.00 0.45
May 0.196579E+11 230530.26 0.00 46252139.12 24842919.63 12942241.94 0.270137E+11 0.00 0.69
June 0.628558E+10 0.517775E+10 0.00 72418282.78 0.318811E+09 0.00 0.273308E+11 0.00 1.04
July 0.226464E+10 0.179959E+11 0.00 47941681.37 0.114960E+10 0.00 0.106960E+11 0.00 0.96
August 0.573214E+10 0.928656E+10 0.00 72771237.85 0.480258E+09 0.00 0.168770E+11 0.00 0.97
September 0.165804E+11 0.314487E+10 0.00 38459022.00 77731484.43 5018882.37 0.161209E+11 0.00 0.76
October 0.310496E+11 0.00 0.00 7386063.62 0.00 0.303190E+10 0.552821E+10 0.00 0.46
November 0.262074E+11 0.00 362578.82 0.00 3751077.94 0.118421E+11 0.00 1193.82 0.41
December 0.534614E+10 0.00 0.00 0.00 0.00 0.334736E+11 0.00 0.00 0.45
                   
Annual Sum or Average 0.174795E+12 0.356053E+11 362578.82 0.297764E+09 0.205500E+10 0.137437E+12 0.111729E+12 1193.82 0.63
Minimum of Months 0.226464E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.41
Maximum of Months 0.313271E+11 0.179959E+11 362578.82 72771237.85 0.114960E+10 0.357666E+11 0.273308E+11 1193.82 1.04



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.630868E+10 0.00 0.00 0.00 0.00 0.377974E+11 0.00 0.00 0.81
February 0.103812E+11 0.00 0.00 273302.66 0.00 0.306203E+11 0.113465E+09 0.00 0.82
March 0.310310E+11 0.00 0.00 13351312.18 0.00 0.130659E+11 0.603847E+10 0.00 0.85
April 0.298459E+11 0.00 0.00 45263932.37 0.00 0.330607E+10 0.268705E+11 0.00 1.00
May 0.221584E+11 281465.47 0.00 80314374.42 30331913.23 28726727.90 0.465849E+11 0.00 1.50
June 0.816373E+10 0.500525E+10 0.00 90848765.42 0.235036E+09 0.00 0.406383E+11 0.00 1.89
July 0.250002E+10 0.160166E+11 0.00 86079333.13 0.167414E+10 0.00 0.190396E+11 0.00 1.75
August 0.696835E+10 0.738408E+10 0.00 90240174.47 0.803625E+09 0.00 0.237891E+11 0.00 1.73
September 0.186178E+11 0.262546E+10 0.00 68225324.21 0.340323E+09 0.151046E+09 0.283361E+11 0.00 1.52
October 0.349555E+11 0.00 0.00 17665691.65 0.00 0.296815E+10 0.115927E+11 0.00 0.88
November 0.324069E+11 0.00 383398.29 948359.73 4640337.15 0.131576E+11 0.805394E+09 283.16 0.78
December 0.630848E+10 0.00 0.00 0.00 0.00 0.380153E+11 0.00 0.00 0.81
                   
Annual Sum or Average 0.209646E+12 0.310316E+11 383398.29 0.493211E+09 0.308810E+10 0.139110E+12 0.203808E+12 283.16 1.20
Minimum of Months 0.250002E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.78
Maximum of Months 0.349555E+11 0.160166E+11 383398.29 90848765.42 0.167414E+10 0.380153E+11 0.465849E+11 283.16 1.89



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.145392E+11 0.00 0.00 16818549.94 0.00 0.302308E+11 0.809606E+10 0.00 0.62
February 0.160066E+11 0.00 0.00 26530416.06 0.00 0.248823E+11 0.112289E+11 0.00 0.66
March 0.277410E+11 0.00 0.00 89257680.11 0.00 0.977333E+10 0.388843E+11 0.00 0.82
April 0.301072E+11 0.00 0.00 74524998.90 0.00 0.413002E+10 0.460544E+11 0.00 0.90
May 0.250660E+11 30301663.42 0.00 94436112.30 14911343.42 0.00 0.526715E+11 0.00 1.18
June 0.108003E+11 0.594963E+10 0.00 92029121.05 0.432334E+09 0.00 0.349958E+11 0.00 1.37
July 0.479649E+10 0.214506E+11 0.00 67830631.20 0.157037E+10 0.00 0.115983E+11 0.00 1.22
August 0.796315E+10 0.119384E+11 0.00 0.122467E+09 0.614291E+09 0.00 0.245943E+11 0.00 1.45
September 0.159324E+11 0.508934E+10 0.00 0.165493E+09 0.136359E+09 0.00 0.529395E+11 0.00 1.64
October 0.260927E+11 0.00 0.00 0.103561E+09 0.00 0.219922E+10 0.558997E+11 0.00 1.05
November 0.300249E+11 0.00 0.00 37531999.36 5453341.31 0.102091E+11 0.244738E+11 0.00 0.68
December 0.153793E+11 0.00 0.00 10226222.82 0.00 0.310896E+11 0.513781E+10 0.00 0.60
                   
Annual Sum or Average 0.224449E+12 0.444582E+11 0.00 0.900706E+09 0.277372E+10 0.112514E+12 0.366574E+12 0.00 1.02
Minimum of Months 0.479649E+10 0.00 0.00 10226222.82 0.00 0.00 0.513781E+10 0.00 0.60
Maximum of Months 0.301072E+11 0.214506E+11 0.00 0.165493E+09 0.157037E+10 0.310896E+11 0.558997E+11 0.00 1.64



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.962170E+10 0.00 0.00 0.00 0.00 0.367640E+11 0.00 0.00 0.86
February 0.133886E+11 0.00 0.00 1052690.03 0.00 0.291671E+11 0.751687E+09 0.00 0.86
March 0.346498E+11 0.00 0.00 16326688.36 0.00 0.116355E+11 0.827211E+10 0.00 0.91
April 0.355408E+11 0.00 0.00 35043117.22 0.00 0.331892E+10 0.239099E+11 0.00 1.08
May 0.255200E+11 297485.48 0.00 86369154.02 32058298.11 4382365.87 0.432232E+11 0.00 1.58
June 0.100375E+11 0.550026E+10 0.00 0.112610E+09 0.368041E+09 0.00 0.339641E+11 0.00 2.02
July 0.414020E+10 0.178738E+11 0.00 79776234.65 0.109359E+10 0.00 0.984756E+10 0.00 1.65
August 0.782936E+10 0.894791E+10 0.00 91799980.17 0.499543E+09 0.00 0.173120E+11 0.00 1.71
September 0.208679E+11 0.278783E+10 0.00 70094772.68 0.306560E+09 0.00 0.231013E+11 0.00 1.53
October 0.390311E+11 0.00 0.00 16999084.54 0.00 0.229667E+10 0.117030E+11 0.00 0.97
November 0.366933E+11 0.00 0.00 2160597.03 5309967.93 0.104897E+11 0.193653E+10 0.00 0.83
December 0.125349E+11 0.00 0.00 0.00 0.00 0.340420E+11 0.00 0.00 0.85
                   
Annual Sum or Average 0.249855E+12 0.351101E+11 0.00 0.512232E+09 0.230510E+10 0.127718E+12 0.174021E+12 0.00 1.24
Minimum of Months 0.414020E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.83
Maximum of Months 0.390311E+11 0.178738E+11 0.00 0.112610E+09 0.109359E+10 0.367640E+11 0.432232E+11 0.00 2.02



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 59912678.40 0.00 0.00 0.00 0.00 0.338374E+10 0.00 0.00 0.48
February 0.141089E+09 0.00 0.00 0.00 0.00 0.311387E+10 0.00 0.00 0.48
March 0.145437E+10 0.00 0.00 564529.03 0.00 0.209045E+10 0.195175E+09 0.00 0.49
April 0.257578E+10 0.00 0.00 486864.32 0.00 0.784021E+09 0.436671E+09 0.00 0.46
May 0.207810E+10 0.00 0.00 3829933.30 1013151.84 81725128.01 0.236854E+10 0.00 0.67
June 0.687404E+09 0.562271E+09 0.00 7209683.00 40466578.80 259851.21 0.268901E+10 0.00 1.07
July 0.284710E+09 0.193379E+10 0.00 4678501.14 0.129622E+09 0.00 0.105334E+10 0.00 1.02
August 0.604500E+09 0.102656E+10 0.00 7434707.86 56891135.52 0.00 0.162855E+10 0.00 1.01
September 0.164592E+10 0.291204E+09 0.00 3269983.14 17824446.20 63727919.20 0.137179E+10 0.00 0.75
October 0.250572E+10 0.00 0.00 451466.55 0.00 0.702630E+09 0.349708E+09 0.00 0.46
November 0.126723E+10 0.00 2645183.56 0.00 354742.11 0.186127E+10 0.00 52532.69 0.44
December 0.195049E+09 0.00 0.00 0.00 0.00 0.316877E+10 0.00 0.00 0.47
                   
Annual Sum or Average 0.134998E+11 0.381382E+10 2645183.56 27925668.35 0.246172E+09 0.152505E+11 0.100928E+11 52532.69 0.65
Minimum of Months 59912678.40 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.44
Maximum of Months 0.257578E+10 0.193379E+10 2645183.56 7434707.86 0.129622E+09 0.338374E+10 0.268901E+10 52532.69 1.07



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.150299E+09 0.00 0.00 0.00 0.00 0.336006E+10 0.00 0.00 0.76
February 0.634572E+09 0.00 0.00 0.00 0.00 0.269043E+10 0.00 0.00 0.77
March 0.234520E+10 0.00 0.00 904621.50 0.00 0.147793E+10 0.414000E+09 0.00 0.86
April 0.236420E+10 0.00 0.00 3578404.93 0.00 0.579936E+09 0.225986E+10 0.00 0.98
May 0.205665E+10 0.00 0.00 7240550.30 1214621.24 56594497.64 0.444118E+10 0.00 1.45
June 0.748806E+09 0.539233E+09 0.00 9165782.00 32330453.46 0.00 0.410529E+10 0.00 1.96
July 0.260281E+09 0.175720E+10 0.00 8373430.11 0.182410E+09 0.00 0.194764E+10 0.00 1.86
August 0.636602E+09 0.813763E+09 0.00 9662296.37 92655165.35 0.00 0.238480E+10 0.00 1.81
September 0.166580E+10 0.251416E+09 0.00 6024323.82 40682246.50 39797897.12 0.266937E+10 0.00 1.49
October 0.286258E+10 0.00 0.00 1156579.40 0.00 0.636343E+09 0.783314E+09 0.00 0.87
November 0.181686E+10 0.00 3013641.78 3205.56 425284.03 0.183501E+10 8695349.66 28349.93 0.80
December 0.282034E+09 0.00 0.00 0.00 0.00 0.320760E+10 0.00 0.00 0.77
                   
Annual Sum or Average 0.158239E+11 0.336161E+10 3013641.78 46109194.00 0.349718E+09 0.138837E+11 0.190141E+11 28349.93 1.20
Minimum of Months 0.150299E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.76
Maximum of Months 0.286258E+10 0.175720E+10 3013641.78 9662296.37 0.182410E+09 0.336006E+10 0.444118E+10 28349.93 1.96



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.854618E+09 0.00 0.00 1092902.86 0.00 0.301619E+10 0.520567E+09 0.00 0.61
February 0.115982E+10 0.00 0.00 2042249.52 0.00 0.238688E+10 0.915552E+09 0.00 0.64
March 0.222571E+10 0.00 0.00 7126979.36 0.00 0.125131E+10 0.312596E+10 0.00 0.84
April 0.247938E+10 0.00 0.00 6147512.68 0.00 0.768028E+09 0.430912E+10 0.00 0.90
May 0.248616E+10 484874.11 0.00 8751867.15 1169266.72 0.132034E+09 0.523132E+10 0.00 1.17
June 0.118063E+10 0.658737E+09 0.00 9450799.90 53274885.15 8051578.26 0.363538E+10 0.00 1.44
July 0.510765E+09 0.235520E+10 0.00 7528843.12 0.197674E+09 0.00 0.131790E+10 0.00 1.34
August 0.869392E+09 0.132091E+10 0.00 13501481.29 81168698.93 0.00 0.255136E+10 0.00 1.53
September 0.159186E+10 0.477291E+09 0.00 14949259.51 22214350.88 47040594.65 0.518045E+10 0.00 1.63
October 0.249136E+10 0.00 0.00 7830232.92 0.00 0.535358E+09 0.457112E+10 0.00 1.02
November 0.196916E+10 0.00 1896229.46 2582735.93 2055355.22 0.152174E+10 0.166735E+10 14479.89 0.69
December 0.837442E+09 0.00 0.00 678296.68 0.00 0.312755E+10 0.309664E+09 0.00 0.60
                   
Annual Sum or Average 0.186563E+11 0.481262E+10 1896229.46 81683160.91 0.357557E+09 0.127942E+11 0.333357E+11 14479.89 1.04
Minimum of Months 0.510765E+09 0.00 0.00 678296.68 0.00 0.00 0.309664E+09 0.00 0.60
Maximum of Months 0.249136E+10 0.235520E+10 1896229.46 14949259.51 0.197674E+09 0.312755E+10 0.523132E+10 14479.89 1.63



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.512236E+09 0.00 0.00 0.00 0.00 0.331638E+10 0.00 0.00 0.83
February 0.910680E+09 0.00 0.00 82965.11 0.00 0.266791E+10 54726736.65 0.00 0.84
March 0.273864E+10 0.00 0.00 1419142.95 0.00 0.135966E+10 0.712965E+09 0.00 0.96
April 0.302592E+10 0.00 0.00 2962666.46 0.00 0.571244E+09 0.234086E+10 0.00 1.11
May 0.273241E+10 57433.36 0.00 8102666.98 1282106.82 45274803.61 0.424713E+10 0.00 1.60
June 0.106242E+10 0.589508E+09 0.00 12490452.38 60147883.96 343562.66 0.356573E+10 0.00 2.13
July 0.469715E+09 0.191701E+10 0.00 8891173.33 0.153772E+09 0.00 0.104811E+10 0.00 1.78
August 0.869230E+09 0.996575E+09 0.00 10131644.22 66133170.52 0.00 0.169739E+10 0.00 1.81
September 0.209664E+10 0.250856E+09 0.00 6328116.34 45784861.15 47469529.87 0.220839E+10 0.00 1.54
October 0.335703E+10 0.00 0.00 1393828.97 0.00 0.534512E+09 0.100371E+10 0.00 1.00
November 0.233427E+10 0.00 994387.88 125646.92 2766545.24 0.156483E+10 0.137050E+09 5834.42 0.88
December 0.689797E+09 0.00 0.00 0.00 0.00 0.311069E+10 0.00 0.00 0.84
                   
Annual Sum or Average 0.207990E+11 0.375400E+10 994387.88 51928303.64 0.329887E+09 0.132183E+11 0.170161E+11 5834.42 1.28
Minimum of Months 0.469715E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.83
Maximum of Months 0.335703E+10 0.191701E+10 994387.88 12490452.38 0.153772E+09 0.331638E+10 0.424713E+10 5834.42 2.13



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.00 0.00 0.00 2500813.18 0.00 0.00 0.829148E+09 0.00 0.28
February 0.00 0.00 0.00 7320290.78 0.00 0.00 0.752380E+09 0.00 0.28
March 0.00 296055.22 0.00 15981252.44 0.00 0.00 0.661577E+09 0.00 0.30
April 0.00 0.00 0.00 18439041.14 0.00 0.00 0.503221E+09 0.00 0.29
May 0.00 198883.00 0.00 4184785.66 0.00 0.00 0.361399E+09 0.00 0.29
June 0.00 57105667.54 0.00 5710488.33 0.00 0.00 0.160073E+09 0.00 0.30
July 0.00 0.159476E+09 0.00 3154326.88 0.00 0.00 28474143.49 0.00 0.28
August 0.00 81651978.96 0.00 10425686.05 0.00 0.00 75418148.59 0.00 0.31
September 0.00 23328633.01 0.00 3281192.06 0.00 0.00 0.196466E+09 0.00 0.29
October 0.00 0.00 0.00 8643156.42 0.00 0.00 0.444391E+09 0.00 0.28
November 0.00 0.00 0.00 12746712.99 0.00 0.00 0.564453E+09 0.00 0.28
December 0.00 0.00 0.00 17127591.40 0.00 0.00 0.761462E+09 0.00 0.28
                   
Annual Sum or Average 0.00 0.322058E+09 0.00 0.109515E+09 0.00 0.00 0.533846E+10 0.00 0.29
Minimum of Months 0.00 0.00 0.00 2500813.18 0.00 0.00 28474143.49 0.00 0.28
Maximum of Months 0.00 0.159476E+09 0.00 18439041.14 0.00 0.00 0.829148E+09 0.00 0.31



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: DATACENTER_MID_ZN_6

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.276024E+10 0.00 0.00 7067093.53 0.00 0.00 0.547102E+10 0.00 0.28
February 0.00 0.00 0.00 52474393.34 0.00 0.00 0.754431E+10 0.00 0.28
March 0.00 2819567.87 0.00 0.137199E+09 0.00 0.00 0.663841E+10 0.00 0.30
April 0.00 0.00 0.00 0.166695E+09 0.00 0.00 0.504822E+10 0.00 0.29
May 0.00 1822426.50 0.00 35401120.69 0.00 0.00 0.362489E+10 0.00 0.29
June 0.00 0.566174E+09 0.00 53189740.77 0.00 0.00 0.160395E+10 0.00 0.30
July 0.00 0.158989E+10 0.00 29834440.01 0.00 0.00 0.286188E+09 0.00 0.28
August 0.00 0.814467E+09 0.00 98777507.08 0.00 0.00 0.757903E+09 0.00 0.31
September 0.00 0.224675E+09 0.00 27806983.60 0.00 0.00 0.198086E+10 0.00 0.29
October 0.00 0.00 0.00 73001780.94 0.00 0.00 0.445727E+10 0.00 0.28
November 0.00 0.00 0.00 0.108185E+09 0.00 0.00 0.566090E+10 0.00 0.28
December 0.00 0.00 0.00 0.143856E+09 0.00 0.00 0.764014E+10 0.00 0.28
                   
Annual Sum or Average 0.276024E+10 0.319985E+10 0.00 0.933488E+09 0.00 0.00 0.507141E+11 0.00 0.29
Minimum of Months 0.00 0.00 0.00 7067093.53 0.00 0.00 0.286188E+09 0.00 0.28
Maximum of Months 0.276024E+10 0.158989E+10 0.00 0.166695E+09 0.00 0.00 0.764014E+10 0.00 0.31



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.515075E+09 0.00 0.00 314138.02 0.00 0.00 0.293744E+09 0.00 0.28
February 253428.32 0.00 0.00 4556980.71 0.00 0.00 0.754813E+09 0.00 0.28
March 0.00 277607.47 0.00 12769966.09 0.00 0.00 0.664861E+09 0.00 0.30
April 0.00 0.00 0.00 16025024.90 0.00 0.00 0.505537E+09 0.00 0.29
May 1137492.86 188780.34 0.00 3236118.34 0.00 0.00 0.362062E+09 0.00 0.29
June 0.00 56663413.93 0.00 5261113.19 0.00 0.00 0.160587E+09 0.00 0.30
July 0.00 0.158959E+09 0.00 2969984.54 0.00 0.00 28676161.82 0.00 0.28
August 0.00 81370163.43 0.00 9843149.66 0.00 0.00 75947984.02 0.00 0.31
September 0.00 22419401.84 0.00 2516274.27 0.00 0.00 0.199181E+09 0.00 0.29
October 0.00 0.00 0.00 6537893.11 0.00 0.00 0.446808E+09 0.00 0.28
November 0.00 0.00 0.00 9844493.08 0.00 0.00 0.567199E+09 0.00 0.28
December 0.00 0.00 0.00 13484286.46 0.00 0.00 0.764990E+09 0.00 0.28
                   
Annual Sum or Average 0.516466E+09 0.319878E+09 0.00 87359422.37 0.00 0.00 0.482441E+10 0.00 0.29
Minimum of Months 0.00 0.00 0.00 314138.02 0.00 0.00 28676161.82 0.00 0.28
Maximum of Months 0.515075E+09 0.158959E+09 0.00 16025024.90 0.00 0.00 0.764990E+09 0.00 0.31



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.00 0.00 0.00 0.732051E+09 0.00 0.00 0.456618E+12 0.00 6.89
February 0.00 0.00 0.00 0.143294E+10 0.00 0.00 0.708272E+12 0.00 11.69
March 0.00 2330482.49 0.00 0.190464E+10 0.00 0.00 0.988931E+12 0.00 22.39
April 0.00 0.00 0.00 0.222681E+10 0.00 0.00 0.118445E+13 0.00 33.69
May 0.00 0.00 0.00 0.541754E+09 0.00 0.00 0.409282E+12 0.00 17.69
June 0.00 0.168039E+11 0.00 0.105917E+10 0.00 0.00 0.435128E+12 0.00 35.41
July 0.00 0.102313E+12 0.00 0.126804E+10 0.00 0.00 0.181561E+12 0.00 39.32
August 0.00 0.315235E+11 0.00 0.184689E+10 0.00 0.00 0.258751E+12 0.00 42.19
September 0.00 0.749696E+09 0.00 0.558766E+09 0.00 0.00 0.324920E+12 0.00 23.10
October 0.00 0.00 0.00 0.104071E+10 0.00 0.00 0.677818E+12 0.00 22.46
November 0.00 0.00 0.00 0.155627E+10 0.00 0.00 0.991676E+12 0.00 25.34
December 0.00 0.00 0.00 0.298331E+10 0.00 0.00 0.131323E+13 0.00 23.30
                   
Annual Sum or Average 0.00 0.151393E+12 0.00 0.171513E+11 0.00 0.00 0.793064E+13 0.00 25.35
Minimum of Months 0.00 0.00 0.00 0.541754E+09 0.00 0.00 0.181561E+12 0.00 6.89
Maximum of Months 0.00 0.102313E+12 0.00 0.298331E+10 0.00 0.00 0.131323E+13 0.00 42.19



Table of Contents

Report: HeatEmissionsReportMonthly

For: Environment

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

SITE TOTAL SURFACE HEAT EMISSION TO AIR [J] SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J]
January 0.256526E+12 0.514005E+11 0.00 0.250656E+13 0.183179E+12
February 0.393256E+12 0.541640E+11 0.00 0.260926E+13 0.227930E+12
March 0.586377E+12 0.342615E+11 0.00 0.319185E+13 0.393147E+12
April 0.707108E+12 0.277452E+11 0.00 0.343344E+13 0.425655E+12
May 0.870815E+12 0.159276E+11 0.00 0.254771E+13 0.396729E+12
June 0.936452E+12 0.686875E+10 0.00 0.164157E+13 0.161915E+13
July 0.868929E+12 -499442210.3 0.00 0.302378E+12 0.328104E+13
August 0.741636E+12 0.300163E+10 0.00 0.111613E+13 0.318282E+13
September 0.561921E+12 0.912444E+10 0.00 0.205992E+13 0.878259E+12
October 0.376882E+12 0.213806E+11 0.00 0.295717E+13 0.280168E+12
November 0.203999E+12 0.292453E+11 0.00 0.311652E+13 0.301624E+12
December 0.231501E+12 0.545995E+11 0.00 0.341264E+13 0.406358E+12
           
Annual Sum or Average 0.673540E+13 0.307220E+12 0.00 0.288952E+14 0.115761E+14
Minimum of Months 0.203999E+12 -499442210.3 0.00 0.302378E+12 0.183179E+12
Maximum of Months 0.936452E+12 0.545995E+11 0.00 0.343344E+13 0.328104E+13