Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:43
Tabular Output Report in Format: HTML
Building: OfficeLarge
Environment: RUNPERIOD 1 ** Albuquerque Intl Sunport NM USA TMY3 WMO#=723650
Simulation Timestamp: 2023-10-16 08:43:29
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 08:43:29
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 31767.76 | 685.83 | 685.83 |
Net Site Energy | 31767.76 | 685.83 | 685.83 |
Total Source Energy | 97538.12 | 2105.73 | 2105.73 |
Net Source Energy | 97538.12 | 2105.73 | 2105.73 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 46320.38 |
Net Conditioned Building Area | 46320.38 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 704.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 2625.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 3917.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 695.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 14676.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 1934.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 3038.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 465.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 771.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7337.79 |
Humidification | 2169.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 807.03 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 769.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2280.17 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 30293.75 | 1474.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10424.99 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler | 0.00 | 704.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 2625.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 3917.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 695.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 5334.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DataCenterPlugLoads | 9341.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 80.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 1848.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 5.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | General | 3038.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 465.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 771.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7337.79 |
Humidification | General | 2169.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 807.03 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2280.17 | |
Water Heater | 0.00 | 769.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 704.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 2625.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 3917.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 695.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 14676.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 1934.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 3038.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 465.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 771.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7337.79 |
Humidification | Unassigned | 2169.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 807.03 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 0.00 | 769.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2280.17 |
Refrigeration | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 99.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 195.79 | 31.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.23 |
Other | 358.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 654.00 | 31.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.23 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 99.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 195.79 | 31.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.23 |
Other | 358.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 654.00 | 31.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.23 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 30293.746 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 30293.746 | 100.00 |
Total On-Site and Utility Electric Sources | 30293.746 | 100.00 |
Total Electricity End Uses | 30293.746 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 10424.99 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 10424.99 | 100.00 |
Total Water End Uses | 10424.99 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 7.33 |
Time Setpoint Not Met During Occupied Cooling | 877.67 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 5927.00 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2013
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICELARGE
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 4B
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_NM_ALBUQUERQUE
| Environment |ZoneCoolingSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |ZoneHeatingSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |ZoneElectricSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |SpaceGainsMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |PeakSpaceGainsMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |SpaceGainComponentsAtCoolingPeakMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |ComfortReportSimple55Monthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |OccupantComfortDataSummaryMonthly
| DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 | BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 |ChillerReportMonthly
| COOLSYS1 CHILLER1 | COOLSYS1 CHILLER2 |TowerReportMonthly
| CENTRAL TOWER | TOWERWATERSYS COOLTOWER 1 | TOWERWATERSYS COOLTOWER 2 |BoilerReportMonthly
| HEATSYS1 BOILER | CENTRAL BOILER |DXReportMonthly
| VAV_BOT WITH REHEAT COOLING COIL | VAV_MID WITH REHEAT COOLING COIL | VAV_TOP WITH REHEAT COOLING COIL | CAV_BAS COOLING COIL | AIRLOOP DATACENTER BASEMENT COOLING COIL | AIRLOOP DATACENTER BOT COOLING COIL | AIRLOOP DATACENTER MID COOLING COIL | AIRLOOP DATACENTER TOP COOLING COIL |WindowReportMonthly
| PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW |WindowEnergyReportMonthly
| PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW |WindowZoneSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |WindowEnergyZoneSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWHSYS1 WATER HEATER |DaylightingReportMonthly
| PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_4_DAYLCTRL |CoilReportMonthly
| VAV_BOT WITH REHEAT HEATING COIL | CORE_BOTTOM VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | VAV_MID WITH REHEAT HEATING COIL | CORE_MID VAV BOX REHEAT COIL | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | VAV_TOP WITH REHEAT HEATING COIL | CORE_TOP VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | CAV_BAS HEATING COIL | AIRLOOP DATACENTER BASEMENT HEATING COIL | AIRLOOP DATACENTER BOT HEATING COIL | AIRLOOP DATACENTER MID HEATING COIL | AIRLOOP DATACENTER TOP HEATING COIL | AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | AIRLOOP DATACENTER BOT_SUPPHEATCOIL | AIRLOOP DATACENTER MID_SUPPHEATCOIL | AIRLOOP DATACENTER TOP_SUPPHEATCOIL | VAV_BOT WITH REHEAT COOLING COIL | VAV_MID WITH REHEAT COOLING COIL | VAV_TOP WITH REHEAT COOLING COIL | CAV_BAS COOLING COIL | AIRLOOP DATACENTER BASEMENT COOLING COIL | AIRLOOP DATACENTER BOT COOLING COIL | AIRLOOP DATACENTER MID COOLING COIL | AIRLOOP DATACENTER TOP COOLING COIL |PlantLoopDemandReportMonthly
| HEATSYS1 | COOLSYS1_SUPPLY | COOLSYS1_DEMAND | SINGLE WATER PLANT LOOP | SWHSYS1 | TOWERWATERSYS |FanReportMonthly
| CAV_BAS FAN | VAV_BOT WITH REHEAT FAN | VAV_MID WITH REHEAT FAN | VAV_TOP WITH REHEAT FAN | AIRLOOP DATACENTER BASEMENT SUPPLY FAN | AIRLOOP DATACENTER BOT SUPPLY FAN | AIRLOOP DATACENTER MID SUPPLY FAN | AIRLOOP DATACENTER TOP SUPPLY FAN |PumpReportMonthly
| HEATSYS1 PUMP | COOLSYS1 PUMP SECONDARY | COOLSYS1 CHILLER1 PUMP | COOLSYS1 CHILLER2 PUMP | PLANT CIRC PUMP | SWHSYS1 PUMP | TOWERWATERSYS PUMP |CondLoopDemandReportMonthly
| HEATSYS1 | COOLSYS1_SUPPLY | COOLSYS1_DEMAND | SINGLE WATER PLANT LOOP | SWHSYS1 | TOWERWATERSYS |ZoneTemperatureOscillationReportMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |AirLoopSystemEnergyAndWaterUseMonthly
| VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | CAV_BAS | AIRLOOP DATACENTER BASEMENT | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |AirLoopSystemComponentLoadsMonthly
| VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | CAV_BAS | AIRLOOP DATACENTER BASEMENT | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |AirLoopSystemComponentEnergyUseMonthly
| VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | CAV_BAS | AIRLOOP DATACENTER BASEMENT | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |MechanicalVentilationLoadsMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 08:43:29
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:43 |
RunPeriod | RUNPERIOD 1 |
Weather File | Albuquerque Intl Sunport NM USA TMY3 WMO#=723650 |
Latitude [deg] | 35.04 |
Longitude [deg] | -106.6 |
Elevation [m] | 1619.00 |
Time Zone | -7.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 12183.89 | 3655.17 | 2436.78 | 3655.17 | 2436.78 |
Above Ground Wall Area [m2] | 11589.54 | 3476.86 | 2317.91 | 3476.86 | 2317.91 |
Window Opening Area [m2] | 4635.80 | 1390.74 | 927.16 | 1390.74 | 927.16 |
Gross Window-Wall Ratio [%] | 38.05 | 38.05 | 38.05 | 38.05 | 38.05 |
Above Ground Window-Wall Ratio [%] | 40.00 | 40.00 | 40.00 | 40.00 | 40.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 12183.89 | 3655.17 | 2436.78 | 3655.17 | 2436.78 |
Above Ground Wall Area [m2] | 11589.54 | 3476.86 | 2317.91 | 3476.86 | 2317.91 |
Window Opening Area [m2] | 4635.80 | 1390.74 | 927.16 | 1390.74 | 927.16 |
Gross Window-Wall Ratio [%] | 38.05 | 38.05 | 38.05 | 38.05 | 38.05 |
Above Ground Window-Wall Ratio [%] | 40.00 | 40.00 | 40.00 | 40.00 | 40.00 |
Total | |
Gross Roof Area [m2] | 3563.11 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
BASEMENT | 2779.43 | Yes | Yes | 6779.02 | 1.00 | 0.00 | 397.05 | 0.00 | 0.00 | 10.2732 | 18.58 | 4.8418 |
CORE_BOTTOM | 2496.12 | Yes | Yes | 6849.35 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.2732 | 18.58 | 8.0697 |
CORE_MID | 2496.12 | Yes | Yes | 6849.35 | 10.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.2732 | 18.58 | 8.0696 |
CORE_TOP | 2496.12 | Yes | Yes | 6849.35 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.2732 | 18.58 | 8.0696 |
PERIMETER_BOT_ZN_3 | 313.41 | Yes | Yes | 860.00 | 1.00 | 200.61 | 0.00 | 115.90 | 115.90 | 10.2732 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_2 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 77.26 | 77.26 | 10.2732 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_1 | 313.42 | Yes | Yes | 860.02 | 1.00 | 200.61 | 0.00 | 115.90 | 115.90 | 10.2732 | 18.58 | 8.0699 |
PERIMETER_BOT_ZN_4 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 77.26 | 77.26 | 10.2732 | 18.58 | 8.0699 |
PERIMETER_MID_ZN_3 | 313.41 | Yes | Yes | 860.00 | 10.00 | 200.61 | 0.00 | 115.90 | 115.90 | 10.2732 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_2 | 201.98 | Yes | Yes | 554.22 | 10.00 | 133.74 | 0.00 | 77.26 | 77.26 | 10.2732 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_1 | 313.42 | Yes | Yes | 860.02 | 10.00 | 200.61 | 0.00 | 115.90 | 115.90 | 10.2732 | 18.58 | 8.0699 |
PERIMETER_MID_ZN_4 | 201.98 | Yes | Yes | 554.22 | 10.00 | 133.74 | 0.00 | 77.26 | 77.26 | 10.2732 | 18.58 | 8.0699 |
PERIMETER_TOP_ZN_3 | 313.41 | Yes | Yes | 860.00 | 1.00 | 200.61 | 0.00 | 115.90 | 115.90 | 10.2732 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_2 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 77.26 | 77.26 | 10.2732 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_1 | 313.42 | Yes | Yes | 860.02 | 1.00 | 200.61 | 0.00 | 115.90 | 115.90 | 10.2732 | 18.58 | 8.0699 |
PERIMETER_TOP_ZN_4 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 77.26 | 77.26 | 10.2732 | 18.58 | 8.0699 |
GROUNDFLOOR_PLENUM | 3563.11 | Yes | No | 4344.14 | 1.00 | 297.11 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
MIDFLOOR_PLENUM | 3563.11 | Yes | No | 4344.14 | 10.00 | 297.11 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
TOPFLOOR_PLENUM | 3563.11 | Yes | No | 4344.14 | 1.00 | 297.11 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
DATACENTER_BOT_ZN_6 | 36.20 | Yes | Yes | 99.34 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.8735 | 18.58 | 215.2992 |
DATACENTER_MID_ZN_6 | 36.20 | Yes | Yes | 99.34 | 10.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.8735 | 18.58 | 215.2992 |
DATACENTER_TOP_ZN_6 | 36.20 | Yes | Yes | 99.34 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.8735 | 18.58 | 215.2992 |
DATACENTER_BASEMENT_ZN_6 | 783.68 | Yes | Yes | 1911.37 | 1.00 | 0.00 | 197.31 | 0.00 | 0.00 | 10.2732 | 18.58 | 484.4232 |
Total | 46320.38 | 126016.35 | 8024.24 | 594.36 | 4635.80 | 4635.80 | 10.3445 | 18.58 | 17.8789 | |||
Conditioned Total | 46320.38 | 126016.35 | 8024.24 | 594.36 | 4635.80 | 4635.80 | 10.3445 | 18.58 | 17.8789 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 42757.27 | 52129.67 | 3565.29 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
BASEMENT | 2779.43 | Yes | Yes | 1.00 | BASEMENT | GENERAL | BASEMENT | 10.2732 | 18.58 | 4.8418 | |
CORE_BOTTOM | 2496.12 | Yes | Yes | 1.00 | CORE_BOTTOM | GENERAL | CORE_BOTTOM | 10.2732 | 18.58 | 8.0697 | |
CORE_MID | 2496.12 | Yes | Yes | 10.00 | CORE_MID | GENERAL | CORE_MID | 10.2732 | 18.58 | 8.0696 | |
CORE_TOP | 2496.12 | Yes | Yes | 1.00 | CORE_TOP | GENERAL | CORE_TOP | 10.2732 | 18.58 | 8.0696 | |
PERIMETER_BOT_ZN_3 | 313.41 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_3 | GENERAL | PERIMETER_BOT_ZN_3 | 10.2732 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_2 | 201.98 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_2 | GENERAL | PERIMETER_BOT_ZN_2 | 10.2732 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_1 | 313.42 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_1 | GENERAL | PERIMETER_BOT_ZN_1 | 10.2732 | 18.58 | 8.0699 | |
PERIMETER_BOT_ZN_4 | 201.98 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_4 | GENERAL | PERIMETER_BOT_ZN_4 | 10.2732 | 18.58 | 8.0699 | |
PERIMETER_MID_ZN_3 | 313.41 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_3 | GENERAL | PERIMETER_MID_ZN_3 | 10.2732 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_2 | 201.98 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_2 | GENERAL | PERIMETER_MID_ZN_2 | 10.2732 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_1 | 313.42 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_1 | GENERAL | PERIMETER_MID_ZN_1 | 10.2732 | 18.58 | 8.0699 | |
PERIMETER_MID_ZN_4 | 201.98 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_4 | GENERAL | PERIMETER_MID_ZN_4 | 10.2732 | 18.58 | 8.0699 | |
PERIMETER_TOP_ZN_3 | 313.41 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_3 | GENERAL | PERIMETER_TOP_ZN_3 | 10.2732 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_2 | 201.98 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_2 | GENERAL | PERIMETER_TOP_ZN_2 | 10.2732 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_1 | 313.42 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_1 | GENERAL | PERIMETER_TOP_ZN_1 | 10.2732 | 18.58 | 8.0699 | |
PERIMETER_TOP_ZN_4 | 201.98 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_4 | GENERAL | PERIMETER_TOP_ZN_4 | 10.2732 | 18.58 | 8.0699 | |
GROUNDFLOOR_PLENUM | 3563.11 | Yes | No | 1.00 | GROUNDFLOOR_PLENUM | GENERAL | GROUNDFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
MIDFLOOR_PLENUM | 3563.11 | Yes | No | 10.00 | MIDFLOOR_PLENUM | GENERAL | MIDFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
TOPFLOOR_PLENUM | 3563.11 | Yes | No | 1.00 | TOPFLOOR_PLENUM | GENERAL | TOPFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
DATACENTER_BOT_ZN_6 | 36.20 | Yes | Yes | 1.00 | DATACENTER_BOT_ZN_6 | GENERAL | DATACENTER_BOT_ZN_6 | 17.8735 | 18.58 | 215.2992 | |
DATACENTER_MID_ZN_6 | 36.20 | Yes | Yes | 10.00 | DATACENTER_MID_ZN_6 | GENERAL | DATACENTER_MID_ZN_6 | 17.8735 | 18.58 | 215.2992 | |
DATACENTER_TOP_ZN_6 | 36.20 | Yes | Yes | 1.00 | DATACENTER_TOP_ZN_6 | GENERAL | DATACENTER_TOP_ZN_6 | 17.8735 | 18.58 | 215.2992 | |
DATACENTER_BASEMENT_ZN_6 | 783.68 | Yes | Yes | 1.00 | DATACENTER_BASEMENT_ZN_6 | GENERAL | DATACENTER_BASEMENT_ZN_6 | 10.2732 | 18.58 | 484.4232 | |
Total | 46320.38 | 10.3445 | 9.29 | 17.8789 | |||||||
Conditioned Total | 46320.38 | 10.3445 | 9.29 | 17.8789 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 42757.27 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 46320.38 | 46320.38 | 0.00 | 42757.27 | 3.1788 | 60.38 | 10.8345 |
Total | 46320.38 | 46320.38 | 0.00 | 42757.27 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:43:29
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 21-AUG-15:09 | 06-FEB-07:10 | - | - | - | - | - | - | - | - | - | - | 21-JUL-16:30 |
Heating | 0.00 | 776482.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 445678.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 332294.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 778371.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 84450.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 308360.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 48514.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 84672.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 100000.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 21190.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 2182343.09 | 797672.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler | 0.00 | 776482.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 445678.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 332294.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 305206.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DataCenterPlugLoads | 473165.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 5015.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 79171.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 263.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | General | 308360.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 48514.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 84672.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 100000.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Water Heater | 0.00 | 21190.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:43:29
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 763.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 8313.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 12406.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 2203.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 46480.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 6127.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 9621.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 1473.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 2443.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 6870.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 834.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 95940.29 | 1597.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 16.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 179.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 267.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 47.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1003.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 132.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 207.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 31.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 52.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 148.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 18.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 2071.23 | 34.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 16.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 179.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 267.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 47.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1003.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 132.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 207.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 31.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 52.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 148.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 18.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 2071.23 | 34.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:43:29
AirTerminal:SingleDuct:ConstantVolume:NoReheatDesign Size Maximum Air Flow Rate [m3/s] | |
BASEMENT DIRECT AIR | 7.31 |
DATACENTER_BOT_ZN_6 DIRECT AIR | 0.608508 |
DATACENTER_MID_ZN_6 DIRECT AIR | 5.84 |
DATACENTER_TOP_ZN_6 DIRECT AIR | 0.595610 |
DATACENTER_BASEMENT_ZN_6 DIRECT AIR | 26.11 |
Design Size Maximum Air Flow Rate [m3/s] | Design Size Constant Minimum Air Flow Fraction | User-Specified Constant Minimum Air Flow Fraction | Design Size Minimum Air Flow Rate [m3/s] | Design Size Maximum Flow Fraction during Reheat [] | User-Specified Maximum Flow Fraction during Reheat [] | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | Design Size Maximum Reheat Water Flow Rate [m3/s] | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | |
CORE_BOTTOM VAV BOX COMPONENT | 7.54 | 0.252150 | 0.274000 | 2.07 | 0.672399 | 0.500000 | 0.001511 | 0.000150 | 2.07 | 12.80 | 0.008000 |
CORE_MID VAV BOX COMPONENT | 71.14 | 0.267373 | 0.286000 | 20.35 | 0.712994 | 0.500000 | 0.001425 | 0.003638 | 20.35 | 12.80 | 0.008000 |
CORE_TOP VAV BOX COMPONENT | 7.01 | 0.271440 | 0.298000 | 2.09 | 0.723840 | 0.500000 | 0.001404 | 0.000702 | 2.91 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | 1.35 | 0.176901 | 0.200000 | 0.270005 | 0.471735 | 0.500000 | 0.002154 | 0.000099 | 0.411323 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | 1.69 | 0.091070 | 0.200000 | 0.337994 | 0.300000 | 0.500000 | 0.004184 | 0.000074 | 0.337994 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | 1.70 | 0.140648 | 0.200000 | 0.339608 | 0.375061 | 0.500000 | 0.002709 | 0.000118 | 0.487100 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | 2.09 | 0.073743 | 0.200000 | 0.417410 | 0.300000 | 0.500000 | 0.005167 | 0.000066 | 0.417410 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_3 VAV BOX COMPONENT | 12.96 | 0.184286 | 0.200000 | 2.59 | 0.491429 | 0.500000 | 0.002067 | 0.001862 | 7.72 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_2 VAV BOX COMPONENT | 18.05 | 0.085259 | 0.200000 | 3.61 | 0.300000 | 0.500000 | 0.004469 | 0.001236 | 5.13 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_1 VAV BOX COMPONENT | 16.65 | 0.143422 | 0.200000 | 3.33 | 0.382459 | 0.500000 | 0.002656 | 0.001842 | 7.64 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_4 VAV BOX COMPONENT | 19.50 | 0.078926 | 0.200000 | 3.90 | 0.300000 | 0.500000 | 0.004827 | 0.001173 | 4.86 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | 1.47 | 0.162905 | 0.200000 | 0.293202 | 0.434413 | 0.500000 | 0.002339 | 0.000236 | 0.978271 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | 1.82 | 0.084459 | 0.200000 | 0.364450 | 0.300000 | 0.500000 | 0.004511 | 0.000156 | 0.645750 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | 1.82 | 0.131130 | 0.200000 | 0.364259 | 0.349679 | 0.500000 | 0.002906 | 0.000234 | 0.969017 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | 2.06 | 0.074636 | 0.200000 | 0.412418 | 0.300000 | 0.500000 | 0.005105 | 0.000151 | 0.624984 | 12.80 | 0.008000 |
Design Size Rated Capacity [W] | Design Size Maximum Water Flow Rate [m3/s] | Design Size U-Factor Times Area Value [W/K] | |
CORE_BOTTOM VAV BOX REHEAT COIL | 17116.65 | 0.000150 | 345.06 |
CORE_MID VAV BOX REHEAT COIL | 415860.09 | 0.003638 | 9823.56 |
CORE_TOP VAV BOX REHEAT COIL | 80297.93 | 0.000702 | 2119.50 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | 11355.25 | 0.000099 | 299.63 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | 8410.04 | 0.000074 | 212.38 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | 13442.38 | 0.000118 | 354.64 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | 7498.38 | 0.000066 | 171.06 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | 212844.56 | 0.001862 | 5612.55 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | 141301.07 | 0.001236 | 3725.91 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | 210517.74 | 0.001842 | 5551.24 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | 134078.30 | 0.001173 | 3535.58 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | 26958.17 | 0.000236 | 710.75 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | 17794.28 | 0.000156 | 469.14 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | 26703.49 | 0.000234 | 704.04 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | 17222.62 | 0.000151 | 454.07 |
VAV_BOT WITH REHEAT HEATING COIL | 53488.05 | 0.000468 | 889.54 |
VAV_MID WITH REHEAT HEATING COIL | 442531.84 | 0.003871 | 7433.87 |
VAV_TOP WITH REHEAT HEATING COIL | 41023.75 | 0.000359 | 698.32 |
CAV_BAS HEATING COIL | 300438.84 | 0.002628 | 6666.88 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT | 7.18 | 3.43 | 14.37 | 3.43 | 12.53 | 12.53 | 0.300000 | 0.273868 | 12.53 |
VAV_MID WITH REHEAT | 69.15 | 33.78 | 138.30 | 38.04 | 117.44 | 117.44 | 0.300000 | 0.323918 | 117.44 |
VAV_TOP WITH REHEAT | 7.09 | 3.52 | 14.18 | 6.12 | 13.06 | 13.06 | 0.300000 | 0.468854 | 13.06 |
CAV_BAS | 7.31 | 7.31 | 7.31 | 7.31 | 7.31 | 7.31 | 1.00 | 1.00 | 7.31 |
AIRLOOP DATACENTER BASEMENT | 26.11 | 26.11 | 26.11 | 26.11 | 26.11 | 26.11 | 1.00 | 0.999992 | 26.11 |
AIRLOOP DATACENTER BOT | 0.608508 | 0.608508 | 0.608508 | 0.608508 | 0.608508 | 0.608508 | 1.00 | 1.00 | 0.608508 |
AIRLOOP DATACENTER MID | 5.84 | 5.84 | 5.84 | 5.84 | 5.84 | 5.84 | 1.00 | 1.00 | 5.84 |
AIRLOOP DATACENTER TOP | 0.595610 | 0.595610 | 0.595610 | 0.595610 | 0.595610 | 0.595610 | 1.00 | 1.00 | 0.595610 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT_OA_CONTROLLER | 12.53 | |
VAV_MID WITH REHEAT_OA_CONTROLLER | 117.44 | |
VAV_TOP WITH REHEAT_OA_CONTROLLER | 13.06 | |
CAV_BAS_OA_CONTROLLER | 7.31 | 1.20 |
AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER | 26.11 | 0.338393 |
AIRLOOP DATACENTER BOT_OA_CONTROLLER | 0.608508 | 0.015632 |
AIRLOOP DATACENTER MID_OA_CONTROLLER | 5.84 | 0.156323 |
AIRLOOP DATACENTER TOP_OA_CONTROLLER | 0.595610 | 0.015632 |
Design Size Design Inlet Air Temperature [C] | Design Size Design Inlet Water Temperature [C] | Design Size Design Outlet Air Temperature [C] | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | Design Size Design Coil Load [W] | Design Size Design Water Flow Rate [m3/s] | Design Size Design Air Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT COOLING COIL | 26.30 | 6.67 | 10.67 | 0.006968 | 0.006968 | 197464.45 | 0.008401 | 12.53 |
VAV_MID WITH REHEAT COOLING COIL | 26.50 | 6.67 | 10.67 | 0.006948 | 0.006948 | 1874643.09 | 0.079752 | 117.44 |
VAV_TOP WITH REHEAT COOLING COIL | 26.16 | 6.67 | 10.67 | 0.006960 | 0.006960 | 204050.78 | 0.008681 | 13.06 |
CAV_BAS COOLING COIL | 25.69 | 6.67 | 11.13 | 0.007134 | 0.007134 | 107353.46 | 0.004567 | 7.31 |
Design Size Maximum Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT FAN | 12.53 |
VAV_MID WITH REHEAT FAN | 117.44 |
VAV_TOP WITH REHEAT FAN | 13.06 |
Maximum Actuated Flow [m3/s] | Controller Convergence Tolerance | |
VAV_BOT WITH REHEAT_COOLC_CONTROLLER | 0.008401 | 0.000057 |
VAV_BOT WITH REHEAT_HEATC_CONTROLLER | 0.000468 | |
VAV_MID WITH REHEAT_COOLC_CONTROLLER | 0.079752 | 0.000006 |
VAV_MID WITH REHEAT_HEATC_CONTROLLER | 0.003871 | |
VAV_TOP WITH REHEAT_COOLC_CONTROLLER | 0.008681 | 0.000055 |
VAV_TOP WITH REHEAT_HEATC_CONTROLLER | 0.000359 | |
CAV_BAS_COOLC_CONTROLLER | 0.004567 | 0.000104 |
CAV_BAS_HEATC_CONTROLLER | 0.002628 |
Design Size Maximum Flow Rate [m3/s] | |
CAV_BAS FAN | 7.31 |
Design Size Rated Air Flow Rate [m3/s] | Design Size Rated Total Cooling Capacity [W] | Design Size Rated Sensible Cooling Capacity [W] | Design Size Rated Water Flow Rate [m3/s] | |
AIRLOOP DATACENTER BASEMENT COOLING COIL | 26.11 | 477837.93 | 253468.45 | 0.011702 |
AIRLOOP DATACENTER BOT COOLING COIL | 0.608508 | 10848.53 | 5808.33 | 0.000266 |
AIRLOOP DATACENTER MID COOLING COIL | 5.84 | 104123.97 | 55735.08 | 0.002550 |
AIRLOOP DATACENTER TOP COOLING COIL | 0.595610 | 10621.04 | 5685.83 | 0.000260 |
Supply Air Flow Rate [m3/s] | Supply Air Flow Rate During Heating Operation [m3/s] | Supply Air Flow Rate During Cooling Operation [m3/s] | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | Nominal Heating Capacity [W] | Nominal Cooling Capacity [W] | Supplemental Heating Coil Nominal Capacity [W] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | 26.11 | 26.11 | 26.11 | 26.11 | 477837.93 | 477837.93 | 16131.55 | 1.00 |
AIRLOOP DATACENTER BOT DXAC HEAT PUMP | 0.608508 | 0.608508 | 0.608508 | 0.608508 | 10848.53 | 10848.53 | 745.21 | 1.00 |
AIRLOOP DATACENTER MID DXAC HEAT PUMP | 5.84 | 5.84 | 5.84 | 5.84 | 104123.97 | 104123.97 | 7452.11 | 1.00 |
AIRLOOP DATACENTER TOP DXAC HEAT PUMP | 0.595610 | 0.595610 | 0.595610 | 0.595610 | 10621.04 | 10621.04 | 745.21 | 1.00 |
Design Size Maximum Flow Rate [m3/s] | |
AIRLOOP DATACENTER BASEMENT SUPPLY FAN | 26.11 |
AIRLOOP DATACENTER BOT SUPPLY FAN | 0.608508 |
AIRLOOP DATACENTER MID SUPPLY FAN | 5.84 |
AIRLOOP DATACENTER TOP SUPPLY FAN | 0.595610 |
Design Size Rated Air Flow Rate [m3/s] | Design Size Rated Heating Capacity [W] | Design Size Rated Water Flow Rate [m3/s] | |
AIRLOOP DATACENTER BASEMENT HEATING COIL | 26.11 | 477837.93 | 0.011702 |
AIRLOOP DATACENTER BOT HEATING COIL | 0.608508 | 10848.53 | 0.000266 |
AIRLOOP DATACENTER MID HEATING COIL | 5.84 | 104123.97 | 0.002550 |
AIRLOOP DATACENTER TOP HEATING COIL | 0.595610 | 10621.04 | 0.000260 |
Design Size Nominal Capacity [W] | |
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | 16131.55 |
AIRLOOP DATACENTER BOT_SUPPHEATCOIL | 745.21 |
AIRLOOP DATACENTER MID_SUPPHEATCOIL | 7452.11 |
AIRLOOP DATACENTER TOP_SUPPHEATCOIL | 745.21 |
Design Size Nominal Capacity Volume [m3/s] | User-Specified Nominal Capacity Volume [m3/s] | Design Size Rated Power [W] | User-Specified Rated Power [W] | |
DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | 0.000141 | 0.000037 | 96450.70 | 100000.00 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | Design Minimum Flow Rate [m3/s] | |
COOLSYS1 PUMP SECONDARY | 0.101400 | 16555.54 | |
HEATSYS1 PUMP | 0.019062 | 5740.58 | 0.000000 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
COOLSYS1_DEMAND | 0.101400 | 12.17 |
HEATSYS1 | 0.019062 | 2.29 |
COOLSYS1_SUPPLY | 0.101400 | 12.17 |
SINGLE WATER PLANT LOOP | 0.014778 | 1.77 |
SWHSYS1 | 0.000440 | 0.052800 |
Loop Supply Side Design Fluid Flow Rate [m3/s] | Loop Demand Side Design Fluid Flow Rate [m3/s] | Heat Exchanger U-Factor Times Area Value [W/C] | Loop-to-loop Temperature Difference Used to Size Heat Exchanger U-Factor Times Area Value [C] | |
BYPASS HEAT EXCHANGER | 0.101400 | 0.101400 | 425627.11 | 5.60 |
Design Size Nominal Capacity [W] | User-Specified Nominal Capacity [W] | Design Size Design Water Flow Rate [m3/s] | |
HEATSYS1 BOILER | 2178883.43 | 2178883.43 | 0.019062 |
CENTRAL BOILER | 608726.82 | 595089.06 | 0.014778 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
COOLSYS1 CHILLER1 PUMP | 0.050700 | 5730.98 |
COOLSYS1 CHILLER2 PUMP | 0.050700 | 5730.98 |
PLANT CIRC PUMP | 0.014778 | 3769.13 |
SWHSYS1 PUMP | 0.000440 | 56.21 |
Design Size Reference Chilled Water Flow Rate [m3/s] | User-Specified Reference Chilled Water Flow Rate [m3/s] | Design Size Reference Capacity [W] | User-Specified Reference Capacity [W] | Design Size Reference Condenser Water Flow Rate [m3/s] | |
COOLSYS1 CHILLER1 | 0.101400 | 0.051480 | 1213061.94 | 1218781.75 | 0.060313 |
COOLSYS1 CHILLER2 | 0.101400 | 0.051480 | 1213061.94 | 1218781.75 | 0.060313 |
Design Water Flow Rate [m3/s] | Air Flow Rate at High Fan Speed [m3/s] | Fluid cooler UA value at high fan speed based on nominal capacity input [W/K] | Air Flow Rate at Low Fan Speed [m3/s] | Fan Power at Low Fan Speed [W] | U-factor Times Area Value at Low Fan Speed [W/C] | |
CENTRAL TOWER | 0.014778 | 139666.47 | 54543.25 | 69833.23 | 7879.72 | 20907.78 |
Use Side Design Flow Rate [m3/s] | |
SWHSYS1 WATER HEATER | 0.000440 |
Maximum Loop Flow Rate [m3/s] | Condenser Loop Volume [m3] | |
TOWERWATERSYS | 0.120626 | 14.48 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
TOWERWATERSYS PUMP | 0.120626 | 29864.32 |
Design Air Flow Rate [m3/s] | Nominal Capacity [W] | Air Flow Rate in free convection regime [m3/s] | Tower capacity in free convection regime at design conditions [W] | |
TOWERWATERSYS COOLTOWER 1 | 56.68 | 1447837.94 | 11.34 | 180979.74 |
TOWERWATERSYS COOLTOWER 2 | 56.68 | 1447837.94 | 11.34 | 180979.74 |
Design Water Flow Rate [m3/s] Equipment # 47 | |
WSHPPLANT OPERATION SCHEME | 0.062645 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:43:29
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
PERIMETER_BOT_ZN_3_WALL_NORTH | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | |
PERIMETER_BOT_ZN_2_WALL_EAST | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | |
PERIMETER_BOT_ZN_1_WALL_SOUTH | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | |
PERIMETER_BOT_ZN_4_WALL_WEST | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | |
PERIMETER_MID_ZN_3_WALL_NORTH | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_MID_ZN_2_WALL_EAST | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_MID_ZN_1_WALL_SOUTH | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_MID_ZN_4_WALL_WEST | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | |
PERIMETER_TOP_ZN_3_WALL_NORTH | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_TOP_ZN_2_WALL_EAST | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_TOP_ZN_1_WALL_SOUTH | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_TOP_ZN_4_WALL_WEST | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 08:43:29
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 08:43:29
VersionVersion ID | |
1 | 22.1.0 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.70 | 7.00 | 2.10 | 2.60 | 4.30 | 8.80 | 13.90 | 17.80 | 23.20 | 25.60 | 24.10 | 20.50 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Albuquerque Intl Sunport NM USA TMY3 WMO#=723650 | 35.04 | -106.62 | -7.00 | 1619.00 | 83328 | 0.9904 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 13.63 | 23.50 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | OfficeLarge | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 23 | 221 | 36 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | BASEMENT | 0.0 | 0.00 | 0.00 | 0.00 | 44.59 | 24.37 | -1.22 | 1 | 1 | 1 | 16.08 | 73.11 | 0.00 | 48.74 | -2.44 | 0.00 | 2.44 | 6779.02 | TARP | TARP | 2779.43 | 0.00 | 0.00 | 0.00 | 9 | 0 | 0 | Yes |
2 | CORE_BOTTOM | 0.0 | 0.00 | 0.00 | 0.00 | 37.01 | 24.37 | 1.37 | 1 | 1 | 1 | 5.49 | 68.53 | 4.57 | 44.17 | 0.00 | 2.74 | 2.74 | 6849.35 | TARP | TARP | 2496.12 | 0.00 | 0.00 | 0.00 | 7 | 0 | 0 | Yes |
3 | CORE_MID | 0.0 | 0.00 | 0.00 | 0.00 | 37.01 | 24.37 | 18.14 | 1 | 10 | 1 | 5.49 | 68.53 | 4.57 | 44.17 | 16.77 | 19.51 | 2.74 | 6849.35 | TARP | TARP | 2496.12 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
4 | CORE_TOP | 0.0 | 0.00 | 0.00 | 0.00 | 37.01 | 24.37 | 34.91 | 1 | 1 | 1 | 5.49 | 68.53 | 4.57 | 44.17 | 33.54 | 36.28 | 2.74 | 6849.35 | TARP | TARP | 2496.12 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
5 | PERIMETER_BOT_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 46.54 | 1.37 | 1 | 1 | 1 | 0.00 | 73.11 | 44.17 | 48.74 | 0.00 | 2.74 | 2.74 | 860.00 | TARP | TARP | 313.41 | 200.61 | 76.91 | 115.90 | 8 | 9 | 0 | Yes |
6 | PERIMETER_BOT_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 70.95 | 24.37 | 1.37 | 1 | 1 | 1 | 68.53 | 73.11 | 0.00 | 48.74 | 0.00 | 2.74 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 52.57 | 77.26 | 6 | 5 | 0 | Yes |
7 | PERIMETER_BOT_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 2.20 | 1.37 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 4.57 | 0.00 | 2.74 | 2.74 | 860.02 | TARP | TARP | 313.42 | 200.61 | 76.91 | 115.90 | 8 | 9 | 0 | Yes |
8 | PERIMETER_BOT_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.16 | 24.37 | 1.37 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 48.74 | 0.00 | 2.74 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 52.57 | 77.26 | 6 | 5 | 0 | Yes |
9 | PERIMETER_MID_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 46.54 | 18.14 | 1 | 10 | 1 | 0.00 | 73.11 | 44.17 | 48.74 | 16.77 | 19.51 | 2.74 | 860.00 | TARP | TARP | 313.41 | 200.61 | 84.71 | 115.90 | 7 | 1 | 0 | Yes |
10 | PERIMETER_MID_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 70.95 | 24.37 | 18.14 | 1 | 10 | 1 | 68.53 | 73.11 | 0.00 | 48.74 | 16.77 | 19.51 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 56.47 | 77.26 | 6 | 1 | 0 | Yes |
11 | PERIMETER_MID_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 2.20 | 18.14 | 1 | 10 | 1 | 0.00 | 73.11 | 0.00 | 4.57 | 16.77 | 19.51 | 2.74 | 860.02 | TARP | TARP | 313.42 | 200.61 | 84.71 | 115.90 | 7 | 1 | 0 | Yes |
12 | PERIMETER_MID_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.16 | 24.37 | 18.14 | 1 | 10 | 1 | 0.00 | 4.57 | 0.00 | 48.74 | 16.77 | 19.51 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 56.47 | 77.26 | 6 | 1 | 0 | Yes |
13 | PERIMETER_TOP_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 46.54 | 34.91 | 1 | 1 | 1 | 0.00 | 73.11 | 44.17 | 48.74 | 33.54 | 36.28 | 2.74 | 860.00 | TARP | TARP | 313.41 | 200.61 | 84.71 | 115.90 | 7 | 1 | 0 | Yes |
14 | PERIMETER_TOP_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 70.95 | 24.37 | 34.91 | 1 | 1 | 1 | 68.53 | 73.11 | 0.00 | 48.74 | 33.54 | 36.28 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 56.47 | 77.26 | 6 | 1 | 0 | Yes |
15 | PERIMETER_TOP_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 2.20 | 34.91 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 4.57 | 33.54 | 36.28 | 2.74 | 860.02 | TARP | TARP | 313.42 | 200.61 | 84.71 | 115.90 | 7 | 1 | 0 | Yes |
16 | PERIMETER_TOP_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.16 | 24.37 | 34.91 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 48.74 | 33.54 | 36.28 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 56.47 | 77.26 | 6 | 1 | 0 | Yes |
17 | GROUNDFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 24.37 | 3.35 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 48.74 | 2.74 | 3.96 | 1.22 | 4344.14 | TARP | TARP | 3563.11 | 297.11 | 297.11 | 0.00 | 11 | 0 | 0 | No |
18 | MIDFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 24.37 | 20.12 | 1 | 10 | 1 | 0.00 | 73.11 | 0.00 | 48.74 | 19.51 | 20.73 | 1.22 | 4344.14 | TARP | TARP | 3563.11 | 297.11 | 297.11 | 0.00 | 11 | 0 | 0 | No |
19 | TOPFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 24.37 | 36.89 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 48.74 | 36.28 | 37.50 | 1.22 | 4344.14 | TARP | TARP | 3563.11 | 297.11 | 297.11 | 0.00 | 11 | 0 | 0 | No |
20 | DATACENTER_BOT_ZN_6 | 0.0 | 5.49 | 44.17 | 0.00 | 5.03 | 24.37 | 1.37 | 1 | 1 | 1 | 4.57 | 5.49 | 4.57 | 44.17 | 0.00 | 2.74 | 2.74 | 99.34 | TARP | TARP | 36.20 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
21 | DATACENTER_MID_ZN_6 | 0.0 | 4.57 | 4.57 | 16.77 | 5.03 | 24.37 | 18.14 | 1 | 10 | 1 | 4.57 | 5.49 | 4.57 | 44.17 | 16.77 | 19.51 | 2.74 | 99.34 | TARP | TARP | 36.20 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
22 | DATACENTER_TOP_ZN_6 | 0.0 | 4.57 | 4.57 | 33.54 | 5.03 | 24.37 | 34.91 | 1 | 1 | 1 | 4.57 | 5.49 | 4.57 | 44.17 | 33.54 | 36.28 | 2.74 | 99.34 | TARP | TARP | 36.20 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
23 | DATACENTER_BASEMENT_ZN_6 | 0.0 | 16.08 | 0.00 | -2.44 | 8.04 | 24.37 | -1.22 | 1 | 1 | 1 | 0.00 | 16.08 | 0.00 | 48.74 | -2.44 | 0.00 | 2.44 | 1911.37 | TARP | TARP | 783.68 | 0.00 | 0.00 | 0.00 | 10 | 0 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | BASEMENT | 2779.43 | 149.6 | 18.579 | 5.382E-002 | 10.273 | 4.842 | 0.000 | 0.000 | 0.000 | 0.000 | 15.115 | No |
2 | CORE_BOTTOM | 2496.12 | 134.4 | 18.579 | 5.382E-002 | 10.273 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 18.343 | No |
3 | CORE_MID | 2496.12 | 134.4 | 18.579 | 5.382E-002 | 10.273 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 18.343 | No |
4 | CORE_TOP | 2496.12 | 134.4 | 18.579 | 5.382E-002 | 10.273 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 18.343 | No |
5 | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 18.579 | 5.382E-002 | 10.273 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 18.343 | No |
6 | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 10.273 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 18.343 | No |
7 | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 18.579 | 5.382E-002 | 10.273 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 18.343 | No |
8 | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 10.273 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 18.343 | No |
9 | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 18.579 | 5.382E-002 | 10.273 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 18.343 | No |
10 | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 10.273 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 18.343 | No |
11 | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 18.579 | 5.382E-002 | 10.273 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 18.343 | No |
12 | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 10.273 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 18.343 | No |
13 | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 18.579 | 5.382E-002 | 10.273 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 18.343 | No |
14 | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 10.273 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 18.343 | No |
15 | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 18.579 | 5.382E-002 | 10.273 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 18.343 | No |
16 | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 10.273 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 18.343 | No |
17 | GROUNDFLOOR_PLENUM | 3563.11 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
18 | MIDFLOOR_PLENUM | 3563.11 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
19 | TOPFLOOR_PLENUM | 3563.11 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
20 | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 18.579 | 5.382E-002 | 17.873 | 215.299 | 0.000 | 0.000 | 0.000 | 0.000 | 233.173 | No |
21 | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 18.579 | 5.382E-002 | 17.873 | 215.299 | 0.000 | 0.000 | 0.000 | 0.000 | 233.173 | No |
22 | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 18.579 | 5.382E-002 | 17.873 | 215.299 | 0.000 | 0.000 | 0.000 | 0.000 | 233.173 | No |
23 | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 18.579 | 5.382E-002 | 10.273 | 484.423 | 0.000 | 0.000 | 0.000 | 0.000 | 494.696 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | DATACENTER_BOT_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 1.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | DATACENTER_MID_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 1.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
3 | DATACENTER_TOP_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 1.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
4 | DATACENTER_BASEMENT_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 42.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 42 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
5 | BASEMENT | BLDG_OCC_SCH_WO_SB | BASEMENT | 2779.43 | 149.6 | 149.6 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 150 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
6 | CORE_BOTTOM | BLDG_OCC_SCH_WO_SB | CORE_BOTTOM | 2496.12 | 134.4 | 134.4 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 134 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
7 | CORE_MID | BLDG_OCC_SCH_WO_SB | CORE_MID | 2496.12 | 134.4 | 134.4 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 134 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
8 | CORE_TOP | BLDG_OCC_SCH_WO_SB | CORE_TOP | 2496.12 | 134.4 | 134.4 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 134 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
9 | PERIMETER_BOT_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
10 | PERIMETER_BOT_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
11 | PERIMETER_BOT_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
12 | PERIMETER_BOT_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
13 | PERIMETER_MID_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
14 | PERIMETER_MID_ZN_2 | BLDG_OCC_SCH_W_SB | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
15 | PERIMETER_MID_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
16 | PERIMETER_MID_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
17 | PERIMETER_TOP_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
18 | PERIMETER_TOP_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
19 | PERIMETER_TOP_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
20 | PERIMETER_TOP_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | BASEMENT_LIGHTS | LTG_SCH_OFFICE | BASEMENT | 2779.43 | 149.6 | 28553.717 | 10.273 | 190.864 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 28553.717 |
2 | CORE_BOTTOM_LIGHTS | LTG_SCH_OFFICE | CORE_BOTTOM | 2496.12 | 134.4 | 25643.245 | 10.273 | 190.864 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 25643.245 |
3 | CORE_MID_LIGHTS | LTG_SCH_OFFICE | CORE_MID | 2496.12 | 134.4 | 25643.245 | 10.273 | 190.864 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 25643.245 |
4 | CORE_TOP_LIGHTS | LTG_SCH_OFFICE | CORE_TOP | 2496.12 | 134.4 | 25643.245 | 10.273 | 190.864 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 25643.245 |
5 | PERIMETER_BOT_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 3219.765 | 10.273 | 190.864 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3219.765 |
6 | PERIMETER_BOT_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 2074.939 | 10.273 | 190.864 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2074.939 |
7 | PERIMETER_BOT_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 3219.836 | 10.273 | 190.864 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3219.836 |
8 | PERIMETER_BOT_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 2074.939 | 10.273 | 190.864 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2074.939 |
9 | PERIMETER_MID_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 3219.765 | 10.273 | 190.864 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3219.765 |
10 | PERIMETER_MID_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 2074.939 | 10.273 | 190.864 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2074.939 |
11 | PERIMETER_MID_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 3219.836 | 10.273 | 190.864 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3219.836 |
12 | PERIMETER_MID_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 2074.939 | 10.273 | 190.864 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2074.939 |
13 | PERIMETER_TOP_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 3219.765 | 10.273 | 190.864 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3219.765 |
14 | PERIMETER_TOP_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 2074.939 | 10.273 | 190.864 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2074.939 |
15 | PERIMETER_TOP_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 3219.836 | 10.273 | 190.864 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3219.836 |
16 | PERIMETER_TOP_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 2074.939 | 10.273 | 190.864 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2074.939 |
17 | DATACENTER_BASEMENT_LIGHTS | LTG_SCH_OFFICE | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 8050.927 | 10.273 | 190.864 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 8050.927 |
18 | DATACENTER_BOT_LIGHTS | LTG_SCH_DATACENTER | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 647.068 | 17.873 | 332.067 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 647.068 |
19 | DATACENTER_MID_LIGHTS | LTG_SCH_DATACENTER | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 647.068 | 17.873 | 332.067 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 647.068 |
20 | DATACENTER_TOP_LIGHTS | LTG_SCH_DATACENTER | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 647.068 | 17.873 | 332.067 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 647.068 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | BASEMENT_MISCPLUG_EQUIP | ALWAYS_ON | BASEMENT | 2779.43 | 149.6 | 13457.544 | 4.842 | 89.956 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 13457.544 | 13457.544 |
2 | CORE_BOTTOM_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_BOTTOM | 2496.12 | 134.4 | 20142.877 | 8.070 | 149.925 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 20142.877 |
3 | CORE_MID_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_MID | 2496.12 | 134.4 | 20142.800 | 8.070 | 149.924 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 20142.800 |
4 | CORE_TOP_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_TOP | 2496.12 | 134.4 | 20142.800 | 8.070 | 149.924 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 20142.800 |
5 | PERIMETER_BOT_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 2529.242 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.242 |
6 | PERIMETER_BOT_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 1629.940 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.940 |
7 | PERIMETER_BOT_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 2529.281 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.281 |
8 | PERIMETER_BOT_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 1629.929 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.929 |
9 | PERIMETER_MID_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 2529.242 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.242 |
10 | PERIMETER_MID_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 1629.940 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.940 |
11 | PERIMETER_MID_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 2529.281 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.281 |
12 | PERIMETER_MID_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 1629.929 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.929 |
13 | PERIMETER_TOP_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 2529.242 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.242 |
14 | PERIMETER_TOP_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 1629.940 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.940 |
15 | PERIMETER_TOP_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 2529.281 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.281 |
16 | PERIMETER_TOP_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 1629.929 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.929 |
17 | DATACENTER_BASEMENT_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 379632.522 | 484.423 | 9000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 94908.130 | 379632.522 |
18 | DATACENTER_BOT_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 7794.422 | 215.299 | 4000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 1948.606 | 7794.422 |
19 | DATACENTER_MID_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 7794.422 | 215.299 | 4000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 1948.606 | 7794.422 |
20 | DATACENTER_TOP_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 7794.422 | 215.299 | 4000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 1948.606 | 7794.422 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 2.839 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | INTERIORFURNISHINGS | 2 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
3 | DROPCEILING | 4 | 1 | 3 | 0.167 | 4.488 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
4 | INT_WALL | 7 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | EXT_SLAB_8IN_WITH_CARPET | 8 | 2 | 7 | 0.167 | 3.285 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
6 | INT_SLAB_FLOOR | 12 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
7 | INT_SLAB_CEILING | 13 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | VeryRough |
8 | NONRES_ROOF | 17 | 3 | 3 | 0.167 | 0.1864 | 0.900 | 0.900 | 0.700 | 0.700 | Rough |
9 | NONRES_EXT_WALL_GRD | 20 | 3 | 9 | 0.167 | 1.075 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
10 | NONRES_EXT_WALL_MID | 21 | 3 | 9 | 0.167 | 1.028 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
11 | NONRES_EXT_WALL_TOP | 22 | 3 | 9 | 0.167 | 1.266 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
12 | BASEMENT_WALL_EAST_CFACTOR | 39 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | BASEMENT_WALL_SOUTH_CFACTOR | 40 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | BASEMENT_WALL_NORTH_CFACTOR | 41 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR | 42 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
16 | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR | 43 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
17 | DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR | 44 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.3522 |
2 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
3 | AC02 ACOUSTIC CEILING | 0.0127 | 0.057 | 288.000 | 1339.000 | 0.2228 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | 200MM NORMALWEIGHT CONCRETE FLOOR | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
7 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
8 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
9 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
10 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
11 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
12 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
13 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 5.307 |
14 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
15 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
16 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.7632 |
17 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
18 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
19 | NONRES_EXTERIOR_WALL_INSULATION_MID | 0.0000 | 0.000 | 0.000 | 0.000 | 0.8055 |
20 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
21 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
22 | NONRES_EXTERIOR_WALL_INSULATION_TOP | 0.0000 | 0.000 | 0.000 | 0.000 | 0.6228 |
23 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
24 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
25 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
26 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
27 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
28 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
29 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
30 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
31 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
32 | ~FC_Insulation_5 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
33 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
34 | ~FC_Insulation_6 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
35 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 2.8391315 | 2.8391315 | 2.8391315 | |
3 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
4 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
5 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
6 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
7 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
8 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
9 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
10 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
11 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
12 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
13 | 3 | -0.21589802E-09 | 0.15643069E-09 | -0.21589802E-09 | 0.12999471E-21 |
14 | 2 | 0.50772448E-02 | 0.30006816E-02 | 0.50772448E-02 | -0.13693132E-08 |
15 | 1 | -2.5944910 | 1.4597758 | -2.5944910 | 0.76344767E-02 |
16 | 0 | 7.0433378 | 2.9911476 | 7.0433378 | |
17 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
18 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
19 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
20 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
21 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
22 | 7 | -0.18651654E-16 | -0.16428647E-15 | -0.26578847E-08 | -0.25364002E-17 |
23 | 6 | 0.67402962E-01 | 0.99142722E-07 | 0.38101547E-02 | -0.76639482E-03 |
24 | 5 | -1.8580732 | 0.49502125E-04 | -0.10651409 | 0.21891119E-01 |
25 | 4 | 18.220105 | 0.12801333E-02 | 1.0775450 | -0.22586539 |
26 | 3 | -79.928293 | 0.66708484E-02 | -4.9803755 | 1.0625663 |
27 | 2 | 166.43177 | 0.75131194E-02 | 11.128837 | -2.4125483 |
28 | 1 | -159.97298 | 0.18548900E-02 | -11.587784 | 2.5494418 |
29 | 0 | 57.057412 | 0.52755123E-04 | 4.4818272 | |
30 | 7 | 0.43260499E-16 | 0.34524919E-16 | 0.52793240E-17 | 0.0000000 |
31 | 6 | 0.69434179E-09 | 0.98085174E-11 | 0.18162501E-10 | -0.40870994E-12 |
32 | 5 | -0.12888762E-04 | 0.28373718E-06 | -0.16918523E-06 | 0.92361873E-08 |
33 | 4 | 0.25174112E-01 | 0.33697681E-03 | 0.22646198E-03 | -0.31467795E-04 |
34 | 3 | -3.7600775 | 0.27170599E-01 | -0.48495626E-01 | 0.94171705E-02 |
35 | 2 | 51.553741 | 0.22121684 | 1.2284947 | -0.25833933 |
36 | 1 | -128.86110 | 0.21944682 | -5.1479470 | 1.1228340 |
37 | 0 | 81.526494 | 0.16043334E-01 | 4.4519351 | |
38 | 7 | 0.52793240E-17 | 0.34524919E-16 | 0.43260499E-16 | 0.0000000 |
39 | 6 | 0.18162501E-10 | 0.98085174E-11 | 0.69434179E-09 | -0.40870994E-12 |
40 | 5 | -0.16918523E-06 | 0.28373718E-06 | -0.12888762E-04 | 0.92361873E-08 |
41 | 4 | 0.22646198E-03 | 0.33697681E-03 | 0.25174112E-01 | -0.31467795E-04 |
42 | 3 | -0.48495626E-01 | 0.27170599E-01 | -3.7600775 | 0.94171705E-02 |
43 | 2 | 1.2284947 | 0.22121684 | 51.553741 | -0.25833933 |
44 | 1 | -5.1479470 | 0.21944682 | -128.86110 | 1.1228340 |
45 | 0 | 4.4519351 | 0.16043334E-01 | 81.526494 | |
46 | 3 | -0.62854340E-06 | 0.84784826E-09 | -0.38512804E-05 | 0.91756347E-17 |
47 | 2 | 0.78257096 | 0.11428808E-02 | 1.0614277 | -0.73836085E-06 |
48 | 1 | -21.991499 | 0.76199851E-01 | -6.3161914 | 0.20349372 |
49 | 0 | 21.357363 | 0.71091016E-01 | 5.4032014 | |
50 | 9 | -0.34463022E-15 | 0.36894385E-16 | -0.14288780E-09 | 0.12757077E-17 |
51 | 8 | 0.20913840E-07 | 0.14359092E-12 | 0.36762620E-03 | -0.23779757E-09 |
52 | 7 | -0.11937955E-01 | 0.75343451E-08 | -0.22648608E-01 | 0.13573889E-03 |
53 | 6 | 0.39710065 | 0.26364580E-05 | 0.46505929 | -0.46505182E-02 |
54 | 5 | -5.1100523 | 0.98937734E-04 | -4.3872286 | 0.62185548E-01 |
55 | 4 | 32.646709 | 0.81302423E-03 | 21.229086 | -0.41739428 |
56 | 3 | -110.46842 | 0.17791168E-02 | -55.206350 | 1.5042464 |
57 | 2 | 196.38009 | 0.10043743E-02 | 77.491871 | -2.8887901 |
58 | 1 | -170.88709 | 0.10757908E-03 | -55.143519 | 2.7407251 |
59 | 0 | 57.057407 | 0.61468164E-06 | 15.577169 | |
60 | 9 | -0.22955380E-15 | 0.37743381E-16 | -0.14509256E-09 | 0.32676096E-18 |
61 | 8 | 0.21224167E-07 | 0.13772622E-12 | 0.37092755E-03 | -0.24132609E-09 |
62 | 7 | -0.12036605E-01 | 0.72012381E-08 | -0.22790691E-01 | 0.13686058E-03 |
63 | 6 | 0.39978134 | 0.25163753E-05 | 0.46734577 | -0.46821170E-02 |
64 | 5 | -5.1362151 | 0.94318005E-04 | -4.4048053 | 0.62509952E-01 |
65 | 4 | 32.762449 | 0.77422319E-03 | 21.297824 | -0.41893096 |
66 | 3 | -110.71472 | 0.16925811E-02 | -55.342260 | 1.5078047 |
67 | 2 | 196.62425 | 0.95470525E-03 | 77.616458 | -2.8926672 |
68 | 1 | -170.97729 | 0.10217823E-03 | -55.179630 | 2.7423060 |
69 | 0 | 57.057407 | 0.58332056E-06 | 15.571109 | |
70 | 9 | 0.11276195E-14 | 0.47405760E-16 | -0.13382366E-09 | -0.64614724E-17 |
71 | 8 | 0.19634610E-07 | 0.16705312E-12 | 0.35383761E-03 | -0.22325229E-09 |
72 | 7 | -0.11525316E-01 | 0.88979655E-08 | -0.22054087E-01 | 0.13104703E-03 |
73 | 6 | 0.38588679 | 0.31323747E-05 | 0.45547913 | -0.45183345E-02 |
74 | 5 | -5.0005974 | 0.11815564E-03 | -4.3135163 | 0.60828376E-01 |
75 | 4 | 32.162433 | 0.97545471E-03 | 20.940665 | -0.41096462 |
76 | 3 | -109.43770 | 0.21433374E-02 | -54.636007 | 1.4893559 |
77 | 2 | 195.35810 | 0.12144036E-02 | 76.969321 | -2.8725616 |
78 | 1 | -170.50942 | 0.13051365E-03 | -54.992579 | 2.7341060 |
79 | 0 | 57.057407 | 0.74839837E-06 | 15.602923 | |
80 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
81 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
82 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
83 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
84 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
85 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
86 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
87 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 | |
88 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
89 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
90 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
91 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
92 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
93 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
94 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
95 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 | |
96 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
97 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
98 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
99 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
100 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
101 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
102 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
103 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 | |
104 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
105 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
106 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
107 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
108 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
109 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
110 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
111 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 | |
112 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
113 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
114 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
115 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
116 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
117 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
118 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
119 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 | |
120 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
121 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
122 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
123 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
124 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
125 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
126 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
127 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | WINDOW_U_0.42_SHGC_EAST_0.4 | 35 | 1 | VerySmooth | 2.387 | 2.387 | 1.000 | 0.401 | ||
2 | WINDOW_U_0.42_SHGC_SOUTH_0.4 | 36 | 1 | VerySmooth | 2.387 | 2.387 | 1.000 | 0.401 | ||
3 | WINDOW_U_0.42_SHGC_WEST_0.4 | 37 | 1 | VerySmooth | 2.387 | 2.387 | 1.000 | 0.401 | ||
4 | WINDOW_U_0.42_SHGC_NORTH_0.4 | 38 | 1 | VerySmooth | 2.387 | 2.387 | 1.000 | 0.401 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | GLAZING LAYER EAST | SpectralAverage | 3.02786E-002 | 0.31435 | 0.47495 | 0.47495 | 0.44000 | 0.13397 | 0.17027 | 0.00000 | 0.84000 | 0.84000 | 0.12239 | 1.00000 | No | |
2 | GLAZING LAYER SOUTH | SpectralAverage | 3.02786E-002 | 0.31435 | 0.47495 | 0.47495 | 0.44000 | 0.13397 | 0.17027 | 0.00000 | 0.84000 | 0.84000 | 0.12239 | 1.00000 | No | |
3 | GLAZING LAYER WEST | SpectralAverage | 3.02786E-002 | 0.31435 | 0.47495 | 0.47495 | 0.44000 | 0.13397 | 0.17027 | 0.00000 | 0.84000 | 0.84000 | 0.12239 | 1.00000 | No | |
4 | GLAZING LAYER NORTH | SpectralAverage | 3.02786E-002 | 0.31435 | 0.47495 | 0.47495 | 0.44000 | 0.13397 | 0.17027 | 0.00000 | 0.84000 | 0.84000 | 0.12239 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 30 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Enclosure Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Enclosures | |
1 | PERIMETER_BOT_ZN_3 | 5 | 0 |
2 | PERIMETER_BOT_ZN_2 | 3 | 0 |
3 | PERIMETER_BOT_ZN_1 | 5 | 0 |
4 | PERIMETER_BOT_ZN_4 | 3 | 0 |
5 | PERIMETER_MID_ZN_3 | 1 | 0 |
6 | PERIMETER_MID_ZN_2 | 1 | 0 |
7 | PERIMETER_MID_ZN_1 | 1 | 0 |
8 | PERIMETER_MID_ZN_4 | 1 | 0 |
9 | PERIMETER_TOP_ZN_3 | 1 | 0 |
10 | PERIMETER_TOP_ZN_2 | 1 | 0 |
11 | PERIMETER_TOP_ZN_1 | 1 | 0 |
12 | PERIMETER_TOP_ZN_4 | 1 | 0 |
Enclosure Name | Number of Adjacent Enclosures with Windows | Adjacent Enclosure Names - 1st 100 (max) | |
1 | PERIMETER_BOT_ZN_3 | 0 | |
2 | PERIMETER_BOT_ZN_2 | 0 | |
3 | PERIMETER_BOT_ZN_1 | 0 | |
4 | PERIMETER_BOT_ZN_4 | 0 | |
5 | PERIMETER_MID_ZN_3 | 0 | |
6 | PERIMETER_MID_ZN_2 | 0 | |
7 | PERIMETER_MID_ZN_1 | 0 | |
8 | PERIMETER_MID_ZN_4 | 0 | |
9 | PERIMETER_TOP_ZN_3 | 0 | |
10 | PERIMETER_TOP_ZN_2 | 0 | |
11 | PERIMETER_TOP_ZN_1 | 0 | |
12 | PERIMETER_TOP_ZN_4 | 0 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 1.1356 | 87921.3 | 0.481 | 5.5005E-002 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | BASEMENT_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
2 | BASEMENT_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
3 | BASEMENT_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
4 | BASEMENT_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
5 | BASEMENT_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
6 | PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
7 | PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
8 | CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
9 | PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
10 | BASEMENT_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
11 | CORE_BOT_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
12 | CORE_BOT_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
13 | CORE_BOT_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
14 | CORE_BOT_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
15 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
16 | CORE_BOT_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
17 | CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
18 | CORE_BOTTOM_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
19 | CORE_MID_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
20 | CORE_MID_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
21 | CORE_MID_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
22 | CORE_MID_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
23 | CORE_MID_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
24 | CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
25 | CORE_MID_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
26 | CORE_TOP_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
27 | CORE_TOP_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
28 | CORE_TOP_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
29 | CORE_TOP_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
30 | CORE_TOP_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
31 | CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
32 | CORE_TOP_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
33 | PERIMETER_BOT_ZN_3_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
34 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
35 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
36 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
37 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
38 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
39 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
40 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
41 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
42 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
43 | PERIMETER_BOT_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
44 | CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
45 | PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
46 | DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
47 | PERIMETER_BOT_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
48 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
49 | PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
50 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
51 | PERIMETER_BOT_ZN_2_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
52 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
53 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
54 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
55 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
56 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
57 | PERIMETER_BOT_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
58 | CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
59 | PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
60 | PERIMETER_BOT_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
61 | PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
62 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
63 | PERIMETER_BOT_ZN_1_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
64 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
65 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
66 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
67 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
68 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
69 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
70 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
71 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
72 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
73 | PERIMETER_BOT_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
74 | DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
75 | PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
76 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
77 | DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
78 | PERIMETER_BOT_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
79 | PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
80 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
81 | PERIMETER_BOT_ZN_4_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
82 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
83 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
84 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
85 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
86 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
87 | PERIMETER_BOT_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
88 | DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
89 | PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
90 | PERIMETER_BOT_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
91 | PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
92 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
93 | PERIMETER_MID_ZN_3_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
94 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
95 | PERIMETER_MID_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
96 | CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
97 | PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
98 | DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
99 | PERIMETER_MID_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
100 | PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
101 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
102 | PERIMETER_MID_ZN_2_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
103 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
104 | PERIMETER_MID_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
105 | CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
106 | PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
107 | PERIMETER_MID_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
108 | PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
109 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
110 | PERIMETER_MID_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
111 | PERIMETER_MID_ZN_1_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
112 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
113 | DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
114 | PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
115 | CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
116 | PERIMETER_MID_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
117 | PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
118 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
119 | PERIMETER_MID_ZN_4_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
120 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
121 | PERIMETER_MID_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
122 | DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
123 | PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
124 | PERIMETER_MID_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
125 | PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
126 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
127 | PERIMETER_TOP_ZN_3_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
128 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
129 | PERIMETER_TOP_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
130 | CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
131 | PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
132 | DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
133 | PERIMETER_TOP_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
134 | PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
135 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
136 | PERIMETER_TOP_ZN_2_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
137 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
138 | PERIMETER_TOP_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
139 | CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
140 | INT-PER3S-NE-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
141 | PERIMETER_TOP_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
142 | PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
143 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
144 | PERIMETER_TOP_ZN_1_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
145 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
146 | INT-PER3S-NE | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
147 | DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
148 | PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
149 | CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
150 | PERIMETER_TOP_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
151 | PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
152 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
153 | PERIMETER_TOP_ZN_4_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
154 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
155 | PERIMETER_TOP_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
156 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
157 | PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
158 | PERIMETER_TOP_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
159 | PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
160 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
161 | GROUNDFLOOR_PLENUM_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
162 | GROUNDFLOOR_PLENUM_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
163 | GROUNDFLOOR_PLENUM_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
164 | GROUNDFLOOR_PLENUM_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
165 | iz-CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
166 | iz-PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
167 | iz-PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
168 | iz-PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
169 | iz-PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
170 | iz-DATACENTER_BOT_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
171 | GROUNDFLOOR_PLENUM_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
172 | MIDFLOOR_PLENUM_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
173 | MIDFLOOR_PLENUM_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
174 | MIDFLOOR_PLENUM_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
175 | MIDFLOOR_PLENUM_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
176 | iz-CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
177 | iz-PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
178 | iz-PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
179 | iz-PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
180 | iz-PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
181 | iz-DATACENTER_MID_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
182 | MIDFLOOR_PLENUM_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
183 | TOPFLOOR_PLENUM_WALL_NORTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
184 | TOPFLOOR_PLENUM_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
185 | TOPFLOOR_PLENUM_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
186 | TOPFLOOR_PLENUM_WALL_SOUTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
187 | iz-CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
188 | iz-PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
189 | iz-PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
190 | iz-PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
191 | iz-PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
192 | iz-DATACENTER_TOP_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
193 | BUILDING_ROOF | 0 | 3563.11 | 268.06 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
194 | DATACENTER_BOT_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
195 | DATACENTER_BOT_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
196 | DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
197 | DATACENTER_BOT_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
198 | DATACENTER_BOT_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
199 | DATACENTER_BOT_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
200 | DATACENTER_MID_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
201 | DATACENTER_MID_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
202 | DATACENTER_MID_ZN_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
203 | DATACENTER_MID_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
204 | DATACENTER_MID_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
205 | DATACENTER_MID_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
206 | DATACENTER_TOP_ZN_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
207 | DATACENTER_TOP_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
208 | DATACENTER_TOP_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
209 | DATACENTER_TOP_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
210 | DATACENTER_TOP_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
211 | DATACENTER_TOP_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
212 | DATACENTER_BASEMENT_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
213 | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
214 | DATACENTER_BASEMENT_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
215 | DATACENTER_BASEMENT_ZN_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
216 | DATACENTER_BASEMENT_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
217 | DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
218 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
219 | PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
220 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
221 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | PERIMETER_BOT_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 0.114 | 3.646E-004 | 5.482E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | PERIMETER_BOT_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 7.617E-002 | 3.771E-004 | 5.534E-004 | 0.495 | 0.000 | 0.000 | 0.224 | 0.000 |
3 | PERIMETER_BOT_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 0.114 | 3.646E-004 | 5.482E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | PERIMETER_BOT_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 7.617E-002 | 3.771E-004 | 5.534E-004 | 0.495 | 0.000 | 0.000 | 0.224 | 0.000 |
5 | PERIMETER_MID_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 0.114 | 3.646E-004 | 5.696E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
6 | PERIMETER_MID_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 7.617E-002 | 3.771E-004 | 5.696E-004 | 0.495 | 0.000 | 0.000 | 0.224 | 0.000 |
7 | PERIMETER_MID_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 0.114 | 3.646E-004 | 5.696E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
8 | PERIMETER_MID_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 7.617E-002 | 3.771E-004 | 5.696E-004 | 0.495 | 0.000 | 0.000 | 0.224 | 0.000 |
9 | PERIMETER_TOP_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 0.114 | 3.646E-004 | 5.696E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
10 | PERIMETER_TOP_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 7.617E-002 | 3.771E-004 | 5.696E-004 | 0.495 | 0.000 | 0.000 | 0.224 | 0.000 |
11 | PERIMETER_TOP_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 0.114 | 3.646E-004 | 5.696E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
12 | PERIMETER_TOP_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 7.617E-002 | 3.771E-004 | 5.696E-004 | 0.495 | 0.000 | 0.000 | 0.224 | 0.000 |
13 | GROUNDFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | GROUNDFLOOR_PLENUM | 3563.11 | 0.0 | 0.169 | 4.749E-005 | 5.696E-004 | 0.140 | 0.000 | 0.000 | 0.224 | 0.000 |
14 | MIDFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | MIDFLOOR_PLENUM | 3563.11 | 0.0 | 0.169 | 4.749E-005 | 5.696E-004 | 0.140 | 0.000 | 0.000 | 0.224 | 0.000 |
15 | TOPFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | TOPFLOOR_PLENUM | 3563.11 | 0.0 | 0.169 | 4.749E-005 | 4.384E-005 | 0.140 | 0.000 | 0.000 | 0.224 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | BASEMENT | Mixing/Well-Stirred |
2 | CORE_BOTTOM | Mixing/Well-Stirred |
3 | CORE_MID | Mixing/Well-Stirred |
4 | CORE_TOP | Mixing/Well-Stirred |
5 | PERIMETER_BOT_ZN_3 | Mixing/Well-Stirred |
6 | PERIMETER_BOT_ZN_2 | Mixing/Well-Stirred |
7 | PERIMETER_BOT_ZN_1 | Mixing/Well-Stirred |
8 | PERIMETER_BOT_ZN_4 | Mixing/Well-Stirred |
9 | PERIMETER_MID_ZN_3 | Mixing/Well-Stirred |
10 | PERIMETER_MID_ZN_2 | Mixing/Well-Stirred |
11 | PERIMETER_MID_ZN_1 | Mixing/Well-Stirred |
12 | PERIMETER_MID_ZN_4 | Mixing/Well-Stirred |
13 | PERIMETER_TOP_ZN_3 | Mixing/Well-Stirred |
14 | PERIMETER_TOP_ZN_2 | Mixing/Well-Stirred |
15 | PERIMETER_TOP_ZN_1 | Mixing/Well-Stirred |
16 | PERIMETER_TOP_ZN_4 | Mixing/Well-Stirred |
17 | GROUNDFLOOR_PLENUM | Mixing/Well-Stirred |
18 | MIDFLOOR_PLENUM | Mixing/Well-Stirred |
19 | TOPFLOOR_PLENUM | Mixing/Well-Stirred |
20 | DATACENTER_BOT_ZN_6 | Mixing/Well-Stirred |
21 | DATACENTER_MID_ZN_6 | Mixing/Well-Stirred |
22 | DATACENTER_TOP_ZN_6 | Mixing/Well-Stirred |
23 | DATACENTER_BASEMENT_ZN_6 | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sky Type | MonthAndDay | Daylighting Control Name | Enclosure Name | Window Name | Reference Point | Daylight Factor | |
1 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 6.8541E-003 |
2 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 6.8564E-003 |
3 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 7.4446E-003 |
4 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 7.4465E-003 |
5 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 5.0195E-003 |
6 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 5.0210E-003 |
7 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.7740E-003 |
8 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.7748E-003 |
9 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 6.9074E-003 |
10 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 7.0659E-003 |
11 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 7.4896E-003 |
12 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 7.6279E-003 |
13 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 5.0578E-003 |
14 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 5.1718E-003 |
15 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.7969E-003 |
16 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.8551E-003 |
17 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 0.1724 |
18 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 7.9625E-002 |
19 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 0.1939 |
20 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 8.8377E-002 |
21 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 0.1243 |
22 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.8418E-002 |
23 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 5.0165E-002 |
24 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.7447E-002 |
25 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 6.9097E-003 |
26 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 7.0761E-003 |
27 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 7.4918E-003 |
28 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 7.6382E-003 |
29 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 5.0598E-003 |
30 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 5.1791E-003 |
31 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.7974E-003 |
32 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.8568E-003 |
33 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 6.8538E-003 |
34 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 6.8562E-003 |
35 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 7.4443E-003 |
36 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 7.4463E-003 |
37 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 5.0193E-003 |
38 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 5.0208E-003 |
39 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.7739E-003 |
40 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.7747E-003 |
41 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 5.9727E-003 |
42 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 6.2664E-003 |
43 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 5.6318E-003 |
44 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 5.9472E-003 |
45 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 5.4442E-003 |
46 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 5.5810E-003 |
47 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 4.7428E-003 |
48 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 4.7830E-003 |
49 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 6.5460E-002 |
50 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.1931E-002 |
51 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 6.0112E-002 |
52 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 2.8515E-002 |
53 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 6.4180E-002 |
54 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 2.6527E-002 |
55 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 5.2230E-002 |
56 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 1.9536E-002 |
57 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 5.8873E-003 |
58 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 5.9973E-003 |
59 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 5.5220E-003 |
60 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 5.6015E-003 |
61 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 5.4008E-003 |
62 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 5.4313E-003 |
63 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 4.7430E-003 |
64 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 4.7836E-003 |
65 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.8455E-003 |
66 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.8477E-003 |
67 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.4219E-003 |
68 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.4237E-003 |
69 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.1442E-003 |
70 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.1455E-003 |
71 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.7740E-003 |
72 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.7749E-003 |
73 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.8952E-003 |
74 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 3.0242E-003 |
75 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.4621E-003 |
76 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.5635E-003 |
77 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.1761E-003 |
78 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.2469E-003 |
79 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.7975E-003 |
80 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.8569E-003 |
81 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 4.5113E-002 |
82 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.3763E-002 |
83 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.4583E-002 |
84 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.7985E-002 |
85 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.1113E-002 |
86 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.2133E-002 |
87 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 5.0165E-002 |
88 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.7442E-002 |
89 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.8939E-003 |
90 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 3.0210E-003 |
91 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.4608E-003 |
92 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.5603E-003 |
93 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.1746E-003 |
94 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.2424E-003 |
95 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.7969E-003 |
96 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.8551E-003 |
97 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.8454E-003 |
98 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.8476E-003 |
99 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.4218E-003 |
100 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.4236E-003 |
101 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.1441E-003 |
102 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.1453E-003 |
103 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.7739E-003 |
104 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.7748E-003 |
105 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 5.7832E-003 |
106 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 5.8938E-003 |
107 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 5.3928E-003 |
108 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 5.4726E-003 |
109 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 5.3137E-003 |
110 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 5.3438E-003 |
111 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 4.7431E-003 |
112 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 4.7837E-003 |
113 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 6.3643E-002 |
114 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.1223E-002 |
115 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 5.7876E-002 |
116 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.7643E-002 |
117 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 6.2572E-002 |
118 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.5896E-002 |
119 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 5.2230E-002 |
120 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 1.9536E-002 |
121 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 5.8654E-003 |
122 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 6.1473E-003 |
123 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 5.4988E-003 |
124 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 5.7993E-003 |
125 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 5.3565E-003 |
126 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 5.4910E-003 |
127 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 4.7428E-003 |
128 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 4.7829E-003 |
129 | Clear Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 0.1679 |
130 | Clear Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 0.1105 |
131 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 0.1824 |
132 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 0.1214 |
133 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 0.1360 |
134 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 7.1813E-002 |
135 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 6.1425E-002 |
136 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 3.0380E-002 |
137 | Clear Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 7.8232E-002 |
138 | Clear Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 4.6196E-002 |
139 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 7.2249E-002 |
140 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 4.1990E-002 |
141 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 7.6336E-002 |
142 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 3.9411E-002 |
143 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 6.2997E-002 |
144 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 3.0728E-002 |
145 | Clear Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 5.6218E-002 |
146 | Clear Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 3.7454E-002 |
147 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 4.4282E-002 |
148 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 2.9558E-002 |
149 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 4.0458E-002 |
150 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 2.2217E-002 |
151 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 6.1425E-002 |
152 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 3.0375E-002 |
153 | Clear Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 7.6177E-002 |
154 | Clear Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 4.5219E-002 |
155 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 6.9717E-002 |
156 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 4.0783E-002 |
157 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 7.4533E-002 |
158 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 3.8569E-002 |
159 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 6.2997E-002 |
160 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 3.0728E-002 |
161 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 0.1680 |
162 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 0.1108 |
163 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 0.1826 |
164 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 0.1217 |
165 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 0.1362 |
166 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 7.1993E-002 |
167 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 6.1557E-002 |
168 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 3.0447E-002 |
169 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 7.8288E-002 |
170 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 4.6266E-002 |
171 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 7.2312E-002 |
172 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 4.2056E-002 |
173 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 7.6456E-002 |
174 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 3.9494E-002 |
175 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 6.3129E-002 |
176 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 3.0795E-002 |
177 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 5.6222E-002 |
178 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 3.7497E-002 |
179 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 4.4291E-002 |
180 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 2.9592E-002 |
181 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 4.0522E-002 |
182 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 2.2258E-002 |
183 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 6.1557E-002 |
184 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 3.0442E-002 |
185 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 7.6229E-002 |
186 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 4.5286E-002 |
187 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 6.9776E-002 |
188 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 4.0846E-002 |
189 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 7.4650E-002 |
190 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 3.8650E-002 |
191 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 6.3129E-002 |
192 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 3.0795E-002 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | BASEMENT | Cooling | 83206.96487 | 83206.96487 | 7.31001 | 7.31001 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 25.11000 | 5.68410E-003 | 2779.42662 | 149.60210 | 1.20016 | 0.00000 |
2 | BASEMENT | Heating | 0.00000 | 0.00000 | 0.00000 | 1.20016 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -7.90000 | 2.34317E-003 | 2779.42662 | 149.60210 | 1.20016 | 0.00000 |
3 | CORE_BOTTOM | Cooling | 85875.41138 | 85875.41138 | 7.54332 | 7.54332 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 25.11000 | 5.68410E-003 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 |
4 | CORE_BOTTOM | Heating | 0.00000 | 0.00000 | 0.00000 | 1.07782 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 06:20:00 | -7.90000 | 2.34317E-003 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 |
5 | CORE_MID | Cooling | 810018.20921 | 810018.20921 | 71.13830 | 71.13830 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 25.11000 | 5.68410E-003 | 2496.12046 | 134.35320 | 10.77825 | 0.00000 |
6 | CORE_MID | Heating | 247369.64472 | 247369.64472 | 12.69220 | 12.69220 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -7.90000 | 2.34317E-003 | 2496.12046 | 134.35320 | 10.77825 | 0.00000 |
7 | CORE_TOP | Cooling | 79787.37333 | 79787.37333 | 7.00724 | 7.00724 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 25.11000 | 5.68410E-003 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 |
8 | CORE_TOP | Heating | 56227.70700 | 56227.70700 | 2.90653 | 2.90653 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -7.90000 | 2.34317E-003 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 |
9 | PERIMETER_BOT_ZN_3 | Cooling | 15241.16290 | 15241.16290 | 1.35003 | 1.35003 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 35.10000 | 5.69938E-003 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
10 | PERIMETER_BOT_ZN_3 | Heating | 7952.36655 | 7952.36655 | 0.41132 | 0.41132 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -7.90000 | 2.34317E-003 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
11 | PERIMETER_BOT_ZN_2 | Cooling | 19079.17301 | 19079.17301 | 1.68997 | 1.68997 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | 27.67500 | 5.68796E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
12 | PERIMETER_BOT_ZN_2 | Heating | 5613.41885 | 5613.41885 | 0.29045 | 0.29045 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -7.90000 | 2.34317E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
13 | PERIMETER_BOT_ZN_1 | Cooling | 19170.12859 | 19170.12859 | 1.69804 | 1.69804 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:10:00 | 34.53750 | 5.69851E-003 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
14 | PERIMETER_BOT_ZN_1 | Heating | 9411.41667 | 9411.41667 | 0.48710 | 0.48710 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -7.90000 | 2.34317E-003 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
15 | PERIMETER_BOT_ZN_4 | Cooling | 23562.10372 | 23562.10372 | 2.08705 | 2.08705 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 | 33.39000 | 5.69673E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
16 | PERIMETER_BOT_ZN_4 | Heating | 4047.32454 | 4047.32454 | 0.20906 | 0.20906 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -7.90000 | 2.34317E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
17 | PERIMETER_MID_ZN_3 | Cooling | 146306.10582 | 146306.10582 | 12.95925 | 12.95925 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | 35.10000 | 5.69938E-003 | 313.41284 | 16.86939 | 1.35332 | 0.00000 |
18 | PERIMETER_MID_ZN_3 | Heating | 148955.92704 | 148955.92704 | 7.72103 | 7.72103 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -7.90000 | 2.34317E-003 | 313.41284 | 16.86939 | 1.35332 | 0.00000 |
19 | PERIMETER_MID_ZN_2 | Cooling | 203797.75175 | 203797.75175 | 18.05148 | 18.05148 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:20:00 | 28.44000 | 5.68912E-003 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
20 | PERIMETER_MID_ZN_2 | Heating | 98885.26065 | 98885.26065 | 5.12603 | 5.12603 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -7.90000 | 2.34317E-003 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
21 | PERIMETER_MID_ZN_1 | Cooling | 187995.79900 | 187995.79900 | 16.65193 | 16.65193 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 34.76250 | 5.69886E-003 | 313.41969 | 16.86975 | 1.35335 | 0.00000 |
22 | PERIMETER_MID_ZN_1 | Heating | 147329.20692 | 147329.20692 | 7.63648 | 7.63648 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -7.90000 | 2.34317E-003 | 313.41969 | 16.86975 | 1.35335 | 0.00000 |
23 | PERIMETER_MID_ZN_4 | Cooling | 220149.75916 | 220149.75916 | 19.49987 | 19.49987 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 33.21000 | 5.69645E-003 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
24 | PERIMETER_MID_ZN_4 | Heating | 93835.40309 | 93835.40309 | 4.86363 | 4.86363 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -7.90000 | 2.34317E-003 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
25 | PERIMETER_TOP_ZN_3 | Cooling | 16550.96788 | 16550.96788 | 1.46601 | 1.46601 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | 35.10000 | 5.69938E-003 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
26 | PERIMETER_TOP_ZN_3 | Heating | 18863.42467 | 18863.42467 | 0.97827 | 0.97827 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -7.90000 | 2.34317E-003 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
27 | PERIMETER_TOP_ZN_2 | Cooling | 20572.95765 | 20572.95765 | 1.82225 | 1.82225 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:30:00 | 28.82250 | 5.68971E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
28 | PERIMETER_TOP_ZN_2 | Heating | 12451.05375 | 12451.05375 | 0.64575 | 0.64575 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -7.90000 | 2.34317E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
29 | PERIMETER_TOP_ZN_1 | Cooling | 20562.05425 | 20562.05425 | 1.82129 | 1.82129 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 34.87500 | 5.69904E-003 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
30 | PERIMETER_TOP_ZN_1 | Heating | 18685.36101 | 18685.36101 | 0.96902 | 0.96902 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -7.90000 | 2.34317E-003 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
31 | PERIMETER_TOP_ZN_4 | Cooling | 23280.72667 | 23280.72667 | 2.06209 | 2.06209 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 33.21000 | 5.69645E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
32 | PERIMETER_TOP_ZN_4 | Heating | 12051.33160 | 12051.33160 | 0.62498 | 0.62498 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -7.90000 | 2.34317E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
33 | DATACENTER_BOT_ZN_6 | Cooling | 8709.72991 | 8709.72991 | 0.60851 | 0.60851 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:50:00 | 30.17250 | 5.69177E-003 | 36.20274 | 1.94861 | 1.56323E-002 | 0.00000 |
34 | DATACENTER_BOT_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 1.56323E-002 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 06:20:00 | -7.90000 | 2.34317E-003 | 36.20274 | 1.94861 | 1.56323E-002 | 0.00000 |
35 | DATACENTER_MID_ZN_6 | Cooling | 83558.40103 | 83558.40103 | 5.83787 | 5.83787 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:50:00 | 30.17250 | 5.69177E-003 | 36.20274 | 1.94861 | 0.15632 | 0.00000 |
36 | DATACENTER_MID_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 0.15632 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 05:40:00 | -7.90000 | 2.34317E-003 | 36.20274 | 1.94861 | 0.15632 | 0.00000 |
37 | DATACENTER_TOP_ZN_6 | Cooling | 8525.09756 | 8525.09756 | 0.59561 | 0.59561 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | 30.51000 | 5.69229E-003 | 36.20274 | 1.94861 | 1.56323E-002 | 0.00000 |
38 | DATACENTER_TOP_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 1.56323E-002 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 05:40:00 | -7.90000 | 2.34317E-003 | 36.20274 | 1.94861 | 1.56323E-002 | 0.00000 |
39 | DATACENTER_BASEMENT_ZN_6 | Cooling | 373654.68189 | 373654.68189 | 26.10521 | 26.10521 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 07:00:00 | 22.81500 | 5.68069E-003 | 783.67941 | 42.18139 | 0.33839 | 0.00000 |
40 | DATACENTER_BASEMENT_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 0.33839 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 02:10:00 | -7.90000 | 2.34317E-003 | 783.67941 | 42.18139 | 0.33839 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | VAV_BOT WITH REHEAT | Cooling | Sensible | 164510.55 | 12.53117 | 12.53117 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
2 | VAV_BOT WITH REHEAT | Heating | Sensible | 51003.28 | 2.47576 | 2.47576 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 |
3 | VAV_MID WITH REHEAT | Cooling | Sensible | 1533911.18 | 117.43529 | 117.43529 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
4 | VAV_MID WITH REHEAT | Heating | Sensible | 521147.42 | 38.03937 | 38.03937 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 22:10:00 |
5 | VAV_TOP WITH REHEAT | Cooling | Sensible | 173077.28 | 13.06281 | 13.06281 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
6 | VAV_TOP WITH REHEAT | Heating | Sensible | 52220.27 | 6.12455 | 6.12455 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 22:20:00 |
7 | CAV_BAS | Cooling | Sensible | 84917.35 | 7.31001 | 7.31001 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
8 | CAV_BAS | Heating | Sensible | 57212.75 | 1.20016 | 1.20016 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
9 | AIRLOOP DATACENTER BASEMENT | Cooling | Sensible | 371181.63 | 26.10542 | 26.10542 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
10 | AIRLOOP DATACENTER BASEMENT | Heating | Sensible | 16131.55 | 0.33839 | 0.33839 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
11 | AIRLOOP DATACENTER BOT | Cooling | Sensible | 8650.93 | 0.60851 | 0.60851 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
12 | AIRLOOP DATACENTER BOT | Heating | Sensible | 745.21 | 1.56323E-002 | 1.56323E-002 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
13 | AIRLOOP DATACENTER MID | Cooling | Sensible | 82993.97 | 5.83787 | 5.83787 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
14 | AIRLOOP DATACENTER MID | Heating | Sensible | 7452.11 | 0.15632 | 0.15632 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
15 | AIRLOOP DATACENTER TOP | Cooling | Sensible | 8470.90 | 0.59561 | 0.59561 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
16 | AIRLOOP DATACENTER TOP | Heating | Sensible | 745.21 | 1.56323E-002 | 1.56323E-002 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | BASEMENT DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 7.31001 |
2 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 7.54332 |
3 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.25215 |
4 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.27400 |
5 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.06687 |
6 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.67240 |
7 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
8 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.51101E-003 |
9 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.49744E-004 |
10 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 2.06687 |
11 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
12 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
13 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 17116.64579 |
14 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.49744E-004 |
15 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 345.05814 |
16 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 71.13830 |
17 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.26737 |
18 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.28600 |
19 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 20.34555 |
20 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.71299 |
21 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
22 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.42498E-003 |
23 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 3.63813E-003 |
24 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 20.34555 |
25 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
26 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
27 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 415860.08646 |
28 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.63813E-003 |
29 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 9823.56045 |
30 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 7.00724 |
31 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.27144 |
32 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.29800 |
33 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.08816 |
34 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.72384 |
35 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
36 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.40363E-003 |
37 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 7.02481E-004 |
38 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 2.90653 |
39 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
40 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
41 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 80297.93378 |
42 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 7.02481E-004 |
43 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 2119.49917 |
44 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.35003 |
45 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.17690 |
46 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
47 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.27001 |
48 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.47174 |
49 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
50 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.15375E-003 |
51 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 9.93407E-005 |
52 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.41132 |
53 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
54 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
55 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 11355.25426 |
56 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 9.93407E-005 |
57 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 299.62704 |
58 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.68997 |
59 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 9.10696E-002 |
60 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
61 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.33799 |
62 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
63 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
64 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 4.18361E-003 |
65 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 7.35747E-005 |
66 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.33799 |
67 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
68 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
69 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 8410.03827 |
70 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 7.35747E-005 |
71 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 212.38345 |
72 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.69804 |
73 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.14065 |
74 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
75 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.33961 |
76 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.37506 |
77 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
78 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.70889E-003 |
79 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.17600E-004 |
80 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.48710 |
81 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
82 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
83 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 13442.38398 |
84 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.17600E-004 |
85 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 354.64099 |
86 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.08705 |
87 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 7.37428E-002 |
88 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
89 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.41741 |
90 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
91 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
92 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 5.16660E-003 |
93 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 6.55991E-005 |
94 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.41741 |
95 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
96 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
97 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 7498.37633 |
98 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 6.55991E-005 |
99 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 171.06048 |
100 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 12.95925 |
101 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.18429 |
102 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
103 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.59185 |
104 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.49143 |
105 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
106 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.06744E-003 |
107 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.86206E-003 |
108 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 7.72103 |
109 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
110 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
111 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 212844.56024 |
112 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.86206E-003 |
113 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 5612.54517 |
114 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 18.05148 |
115 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 8.52590E-002 |
116 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
117 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 3.61030 |
118 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
119 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
120 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 4.46874E-003 |
121 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.23616E-003 |
122 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 5.12603 |
123 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
124 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
125 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 141301.06873 |
126 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.23616E-003 |
127 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 3725.90887 |
128 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 16.65193 |
129 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.14342 |
130 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
131 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 3.33039 |
132 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.38246 |
133 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
134 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.65649E-003 |
135 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.84170E-003 |
136 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 7.63648 |
137 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
138 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
139 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 210517.74133 |
140 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.84170E-003 |
141 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 5551.23581 |
142 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 19.49987 |
143 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 7.89262E-002 |
144 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
145 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 3.89997 |
146 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
147 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
148 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 4.82730E-003 |
149 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.17298E-003 |
150 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 4.86363 |
151 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
152 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
153 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 134078.30127 |
154 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.17298E-003 |
155 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 3535.58129 |
156 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.46601 |
157 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.16290 |
158 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
159 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.29320 |
160 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.43441 |
161 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
162 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.33879E-003 |
163 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.35842E-004 |
164 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.97827 |
165 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
166 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
167 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 26958.16661 |
168 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.35842E-004 |
169 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 710.74918 |
170 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.82225 |
171 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 8.44589E-002 |
172 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
173 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.36445 |
174 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
175 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
176 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 4.51107E-003 |
177 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.55672E-004 |
178 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.64575 |
179 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
180 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
181 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 17794.28201 |
182 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.55672E-004 |
183 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 469.13677 |
184 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.82129 |
185 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.13113 |
186 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
187 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.36426 |
188 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.34968 |
189 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
190 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.90552E-003 |
191 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.33614E-004 |
192 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.96902 |
193 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
194 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
195 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 26703.48556 |
196 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.33614E-004 |
197 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 704.03848 |
198 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.06209 |
199 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 7.46355E-002 |
200 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
201 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.41242 |
202 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
203 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
204 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 5.10481E-003 |
205 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.50671E-004 |
206 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.62498 |
207 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
208 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
209 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 17222.61951 |
210 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.50671E-004 |
211 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 454.07209 |
212 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DATACENTER_BOT_ZN_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.60851 |
213 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DATACENTER_MID_ZN_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 5.83787 |
214 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DATACENTER_TOP_ZN_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.59561 |
215 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DATACENTER_BASEMENT_ZN_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 26.10521 |
216 | AirLoopHVAC | VAV_BOT WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 7.18420 |
217 | AirLoopHVAC | VAV_BOT WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 3.43189 |
218 | AirLoopHVAC | VAV_BOT WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 14.36841 |
219 | AirLoopHVAC | VAV_BOT WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 3.43189 |
220 | AirLoopHVAC | VAV_BOT WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 12.53117 |
221 | AirLoopHVAC | VAV_BOT WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 12.53117 |
222 | AirLoopHVAC | VAV_BOT WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
223 | AirLoopHVAC | VAV_BOT WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.27387 |
224 | AirLoopHVAC | VAV_MID WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 69.15042 |
225 | AirLoopHVAC | VAV_MID WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 33.77806 |
226 | AirLoopHVAC | VAV_MID WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 138.30083 |
227 | AirLoopHVAC | VAV_MID WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 38.03937 |
228 | AirLoopHVAC | VAV_MID WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 117.43529 |
229 | AirLoopHVAC | VAV_MID WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 117.43529 |
230 | AirLoopHVAC | VAV_MID WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
231 | AirLoopHVAC | VAV_MID WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.32392 |
232 | AirLoopHVAC | VAV_TOP WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 7.08944 |
233 | AirLoopHVAC | VAV_TOP WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 3.52249 |
234 | AirLoopHVAC | VAV_TOP WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 14.17888 |
235 | AirLoopHVAC | VAV_TOP WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 6.12455 |
236 | AirLoopHVAC | VAV_TOP WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 13.06281 |
237 | AirLoopHVAC | VAV_TOP WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 13.06281 |
238 | AirLoopHVAC | VAV_TOP WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
239 | AirLoopHVAC | VAV_TOP WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.46885 |
240 | AirLoopHVAC | CAV_BAS | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 7.31001 |
241 | AirLoopHVAC | CAV_BAS | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 7.31001 |
242 | AirLoopHVAC | CAV_BAS | Sum of Air Terminal Maximum Flow Rates [m3/s] | 7.31001 |
243 | AirLoopHVAC | CAV_BAS | Adjusted Heating Design Air Flow Rate [m3/s] | 7.31001 |
244 | AirLoopHVAC | CAV_BAS | Adjusted Cooling Design Air Flow Rate [m3/s] | 7.31001 |
245 | AirLoopHVAC | CAV_BAS | Adjusted Main Design Air Flow Rate [m3/s] | 7.31001 |
246 | AirLoopHVAC | CAV_BAS | User Heating Air Flow Ratio [] | 1.00000 |
247 | AirLoopHVAC | CAV_BAS | Calculated Heating Air Flow Ratio [] | 1.00000 |
248 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 26.10521 |
249 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 26.10521 |
250 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 26.10521 |
251 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Adjusted Heating Design Air Flow Rate [m3/s] | 26.10521 |
252 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Adjusted Cooling Design Air Flow Rate [m3/s] | 26.10542 |
253 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Adjusted Main Design Air Flow Rate [m3/s] | 26.10542 |
254 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | User Heating Air Flow Ratio [] | 1.00000 |
255 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Calculated Heating Air Flow Ratio [] | 0.99999 |
256 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.60851 |
257 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.60851 |
258 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.60851 |
259 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Adjusted Heating Design Air Flow Rate [m3/s] | 0.60851 |
260 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.60851 |
261 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Adjusted Main Design Air Flow Rate [m3/s] | 0.60851 |
262 | AirLoopHVAC | AIRLOOP DATACENTER BOT | User Heating Air Flow Ratio [] | 1.00000 |
263 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Calculated Heating Air Flow Ratio [] | 1.00000 |
264 | AirLoopHVAC | AIRLOOP DATACENTER MID | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 5.83787 |
265 | AirLoopHVAC | AIRLOOP DATACENTER MID | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 5.83787 |
266 | AirLoopHVAC | AIRLOOP DATACENTER MID | Sum of Air Terminal Maximum Flow Rates [m3/s] | 5.83787 |
267 | AirLoopHVAC | AIRLOOP DATACENTER MID | Adjusted Heating Design Air Flow Rate [m3/s] | 5.83787 |
268 | AirLoopHVAC | AIRLOOP DATACENTER MID | Adjusted Cooling Design Air Flow Rate [m3/s] | 5.83787 |
269 | AirLoopHVAC | AIRLOOP DATACENTER MID | Adjusted Main Design Air Flow Rate [m3/s] | 5.83787 |
270 | AirLoopHVAC | AIRLOOP DATACENTER MID | User Heating Air Flow Ratio [] | 1.00000 |
271 | AirLoopHVAC | AIRLOOP DATACENTER MID | Calculated Heating Air Flow Ratio [] | 1.00000 |
272 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.59561 |
273 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.59561 |
274 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.59561 |
275 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Adjusted Heating Design Air Flow Rate [m3/s] | 0.59561 |
276 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.59561 |
277 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Adjusted Main Design Air Flow Rate [m3/s] | 0.59561 |
278 | AirLoopHVAC | AIRLOOP DATACENTER TOP | User Heating Air Flow Ratio [] | 1.00000 |
279 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Calculated Heating Air Flow Ratio [] | 1.00000 |
280 | AirLoopHVAC | VAV_BOT WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 12.53117 |
281 | AirLoopHVAC | VAV_MID WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 117.43529 |
282 | AirLoopHVAC | VAV_TOP WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 13.06281 |
283 | AirLoopHVAC | CAV_BAS | Design Supply Air Flow Rate [m3/s] | 7.31001 |
284 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Design Supply Air Flow Rate [m3/s] | 26.10542 |
285 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Design Supply Air Flow Rate [m3/s] | 0.60851 |
286 | AirLoopHVAC | AIRLOOP DATACENTER MID | Design Supply Air Flow Rate [m3/s] | 5.83787 |
287 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Design Supply Air Flow Rate [m3/s] | 0.59561 |
288 | Controller:OutdoorAir | VAV_BOT WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 12.53117 |
289 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Inlet Air Temperature [C] | 26.29996 |
290 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
291 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Outlet Air Temperature [C] | 10.66766 |
292 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 6.96823E-003 |
293 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 6.96823E-003 |
294 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Coil Load [W] | 197464.45302 |
295 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 8.40059E-003 |
296 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 12.53117 |
297 | Coil:Heating:Water | VAV_BOT WITH REHEAT HEATING COIL | Design Size Rated Capacity [W] | 53488.04830 |
298 | Coil:Heating:Water | VAV_BOT WITH REHEAT HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 4.67937E-004 |
299 | Coil:Heating:Water | VAV_BOT WITH REHEAT HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 889.54215 |
300 | Fan:VariableVolume | VAV_BOT WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 12.53117 |
301 | Controller:WaterCoil | VAV_BOT WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 8.40059E-003 |
302 | Controller:WaterCoil | VAV_BOT WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 5.66853E-005 |
303 | Controller:WaterCoil | VAV_BOT WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 4.67937E-004 |
304 | Controller:OutdoorAir | VAV_MID WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 117.43529 |
305 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Inlet Air Temperature [C] | 26.50417 |
306 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
307 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Outlet Air Temperature [C] | 10.66758 |
308 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 6.94831E-003 |
309 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 6.94831E-003 |
310 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Coil Load [W] | 1874643.08823 |
311 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 7.97516E-002 |
312 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 117.43529 |
313 | Coil:Heating:Water | VAV_MID WITH REHEAT HEATING COIL | Design Size Rated Capacity [W] | 442531.84381 |
314 | Coil:Heating:Water | VAV_MID WITH REHEAT HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.87146E-003 |
315 | Coil:Heating:Water | VAV_MID WITH REHEAT HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 7433.86976 |
316 | Fan:VariableVolume | VAV_MID WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 117.43529 |
317 | Controller:WaterCoil | VAV_MID WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 7.97516E-002 |
318 | Controller:WaterCoil | VAV_MID WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 5.97092E-006 |
319 | Controller:WaterCoil | VAV_MID WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 3.87146E-003 |
320 | Controller:OutdoorAir | VAV_TOP WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 13.06281 |
321 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Inlet Air Temperature [C] | 26.16415 |
322 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
323 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Outlet Air Temperature [C] | 10.66763 |
324 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 6.95989E-003 |
325 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 6.95989E-003 |
326 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Coil Load [W] | 204050.78352 |
327 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 8.68079E-003 |
328 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 13.06281 |
329 | Coil:Heating:Water | VAV_TOP WITH REHEAT HEATING COIL | Design Size Rated Capacity [W] | 41023.75156 |
330 | Coil:Heating:Water | VAV_TOP WITH REHEAT HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.58894E-004 |
331 | Coil:Heating:Water | VAV_TOP WITH REHEAT HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 698.31942 |
332 | Fan:VariableVolume | VAV_TOP WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 13.06281 |
333 | Controller:WaterCoil | VAV_TOP WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 8.68079E-003 |
334 | Controller:WaterCoil | VAV_TOP WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 5.48556E-005 |
335 | Controller:WaterCoil | VAV_TOP WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 3.58894E-004 |
336 | Controller:OutdoorAir | CAV_BAS_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 7.31001 |
337 | Controller:OutdoorAir | CAV_BAS_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.20016 |
338 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Inlet Air Temperature [C] | 25.69361 |
339 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
340 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Outlet Air Temperature [C] | 11.12921 |
341 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 7.13385E-003 |
342 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 7.13385E-003 |
343 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Coil Load [W] | 107353.46362 |
344 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 4.56706E-003 |
345 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 7.31001 |
346 | Coil:Heating:Water | CAV_BAS HEATING COIL | Design Size Rated Capacity [W] | 300438.84012 |
347 | Coil:Heating:Water | CAV_BAS HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.62837E-003 |
348 | Coil:Heating:Water | CAV_BAS HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 6666.88498 |
349 | Fan:ConstantVolume | CAV_BAS FAN | Design Size Maximum Flow Rate [m3/s] | 7.31001 |
350 | Controller:WaterCoil | CAV_BAS_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 4.56706E-003 |
351 | Controller:WaterCoil | CAV_BAS_COOLC_CONTROLLER | Controller Convergence Tolerance | 1.04266E-004 |
352 | Controller:WaterCoil | CAV_BAS_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 2.62837E-003 |
353 | Controller:OutdoorAir | AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 26.10542 |
354 | Controller:OutdoorAir | AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.33839 |
355 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 26.10542 |
356 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Rated Total Cooling Capacity [W] | 477837.93078 |
357 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Rated Sensible Cooling Capacity [W] | 253468.45474 |
358 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Rated Water Flow Rate [m3/s] | 1.17022E-002 |
359 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 26.10542 |
360 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 26.10542 |
361 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 26.10542 |
362 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 26.10542 |
363 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Nominal Heating Capacity [W] | 477837.93078 |
364 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 477837.93078 |
365 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 16131.54879 |
366 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
367 | Fan:OnOff | AIRLOOP DATACENTER BASEMENT SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 26.10542 |
368 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 26.10542 |
369 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT HEATING COIL | Design Size Rated Heating Capacity [W] | 477837.93078 |
370 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT HEATING COIL | Design Size Rated Water Flow Rate [m3/s] | 1.17022E-002 |
371 | Coil:Heating:Electric | AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 16131.54879 |
372 | Humidifier:Steam:Electric | DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | Design Size Nominal Capacity Volume [m3/s] | 1.41188E-004 |
373 | Humidifier:Steam:Electric | DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | User-Specified Nominal Capacity Volume [m3/s] | 3.72000E-005 |
374 | Humidifier:Steam:Electric | DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | Design Size Rated Power [W] | 96450.69782 |
375 | Humidifier:Steam:Electric | DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | User-Specified Rated Power [W] | 100000.00000 |
376 | Controller:OutdoorAir | AIRLOOP DATACENTER BOT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.60851 |
377 | Controller:OutdoorAir | AIRLOOP DATACENTER BOT_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.56323E-002 |
378 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.60851 |
379 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT COOLING COIL | Design Size Rated Total Cooling Capacity [W] | 10848.52722 |
380 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT COOLING COIL | Design Size Rated Sensible Cooling Capacity [W] | 5808.32968 |
381 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT COOLING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.65680E-004 |
382 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 0.60851 |
383 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 0.60851 |
384 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 0.60851 |
385 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 0.60851 |
386 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Nominal Heating Capacity [W] | 10848.52722 |
387 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 10848.52722 |
388 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 745.21073 |
389 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
390 | Fan:OnOff | AIRLOOP DATACENTER BOT SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.60851 |
391 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.60851 |
392 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT HEATING COIL | Design Size Rated Heating Capacity [W] | 10848.52722 |
393 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT HEATING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.65680E-004 |
394 | Coil:Heating:Electric | AIRLOOP DATACENTER BOT_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 745.21073 |
395 | Controller:OutdoorAir | AIRLOOP DATACENTER MID_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 5.83787 |
396 | Controller:OutdoorAir | AIRLOOP DATACENTER MID_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.15632 |
397 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 5.83787 |
398 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID COOLING COIL | Design Size Rated Total Cooling Capacity [W] | 104123.97359 |
399 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID COOLING COIL | Design Size Rated Sensible Cooling Capacity [W] | 55735.07935 |
400 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID COOLING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.54999E-003 |
401 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 5.83787 |
402 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 5.83787 |
403 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 5.83787 |
404 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 5.83787 |
405 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Nominal Heating Capacity [W] | 104123.97359 |
406 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 104123.97359 |
407 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 7452.10725 |
408 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
409 | Fan:OnOff | AIRLOOP DATACENTER MID SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 5.83787 |
410 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 5.83787 |
411 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID HEATING COIL | Design Size Rated Heating Capacity [W] | 104123.97359 |
412 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID HEATING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.54999E-003 |
413 | Coil:Heating:Electric | AIRLOOP DATACENTER MID_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 7452.10725 |
414 | Controller:OutdoorAir | AIRLOOP DATACENTER TOP_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.59561 |
415 | Controller:OutdoorAir | AIRLOOP DATACENTER TOP_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.56323E-002 |
416 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.59561 |
417 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP COOLING COIL | Design Size Rated Total Cooling Capacity [W] | 10621.04176 |
418 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP COOLING COIL | Design Size Rated Sensible Cooling Capacity [W] | 5685.82672 |
419 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP COOLING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.60109E-004 |
420 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 0.59561 |
421 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 0.59561 |
422 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 0.59561 |
423 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 0.59561 |
424 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Nominal Heating Capacity [W] | 10621.04176 |
425 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 10621.04176 |
426 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 745.21073 |
427 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
428 | Fan:OnOff | AIRLOOP DATACENTER TOP SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.59561 |
429 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.59561 |
430 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP HEATING COIL | Design Size Rated Heating Capacity [W] | 10621.04176 |
431 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP HEATING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.60109E-004 |
432 | Coil:Heating:Electric | AIRLOOP DATACENTER TOP_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 745.21073 |
433 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Flow Rate [m3/s] | 0.10140 |
434 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Power Consumption [W] | 16555.53812 |
435 | PlantLoop | COOLSYS1_DEMAND | Maximum Loop Flow Rate [m3/s] | 0.10140 |
436 | PlantLoop | COOLSYS1_DEMAND | Plant Loop Volume [m3] | 12.16801 |
437 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Loop Supply Side Design Fluid Flow Rate [m3/s] | 0.10140 |
438 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Loop Demand Side Design Fluid Flow Rate [m3/s] | 0.10140 |
439 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Heat Exchanger U-Factor Times Area Value [W/C] | 425627.10507 |
440 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Loop-to-loop Temperature Difference Used to Size Heat Exchanger U-Factor Times Area Value [C] | 5.60000 |
441 | PlantLoop | HEATSYS1 | Maximum Loop Flow Rate [m3/s] | 1.90618E-002 |
442 | PlantLoop | HEATSYS1 | Plant Loop Volume [m3] | 2.28742 |
443 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Flow Rate [m3/s] | 1.90618E-002 |
444 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Power Consumption [W] | 5740.58391 |
445 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Minimum Flow Rate [m3/s] | 0.00000 |
446 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Nominal Capacity [W] | 2178883.42791 |
447 | Boiler:HotWater | HEATSYS1 BOILER | User-Specified Nominal Capacity [W] | 2178883.43000 |
448 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Design Water Flow Rate [m3/s] | 1.90618E-002 |
449 | PlantLoop | COOLSYS1_SUPPLY | Maximum Loop Flow Rate [m3/s] | 0.10140 |
450 | PlantLoop | COOLSYS1_SUPPLY | Plant Loop Volume [m3] | 12.16801 |
451 | Pump:ConstantSpeed | COOLSYS1 CHILLER1 PUMP | Design Flow Rate [m3/s] | 5.07001E-002 |
452 | Pump:ConstantSpeed | COOLSYS1 CHILLER1 PUMP | Design Power Consumption [W] | 5730.97868 |
453 | Pump:ConstantSpeed | COOLSYS1 CHILLER2 PUMP | Design Flow Rate [m3/s] | 5.07001E-002 |
454 | Pump:ConstantSpeed | COOLSYS1 CHILLER2 PUMP | Design Power Consumption [W] | 5730.97868 |
455 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | Design Size Reference Chilled Water Flow Rate [m3/s] | 0.10140 |
456 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | User-Specified Reference Chilled Water Flow Rate [m3/s] | 5.14800E-002 |
457 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | Design Size Reference Capacity [W] | 1213061.93648 |
458 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | User-Specified Reference Capacity [W] | 1218781.74500 |
459 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | Design Size Reference Condenser Water Flow Rate [m3/s] | 6.03130E-002 |
460 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | Design Size Reference Chilled Water Flow Rate [m3/s] | 0.10140 |
461 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | User-Specified Reference Chilled Water Flow Rate [m3/s] | 5.14800E-002 |
462 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | Design Size Reference Capacity [W] | 1213061.93648 |
463 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | User-Specified Reference Capacity [W] | 1218781.74500 |
464 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | Design Size Reference Condenser Water Flow Rate [m3/s] | 6.03130E-002 |
465 | PlantLoop | SINGLE WATER PLANT LOOP | Maximum Loop Flow Rate [m3/s] | 1.47780E-002 |
466 | PlantLoop | SINGLE WATER PLANT LOOP | Plant Loop Volume [m3] | 1.77336 |
467 | Pump:ConstantSpeed | PLANT CIRC PUMP | Design Flow Rate [m3/s] | 1.47780E-002 |
468 | Pump:ConstantSpeed | PLANT CIRC PUMP | Design Power Consumption [W] | 3769.12849 |
469 | FluidCooler:TwoSpeed | CENTRAL TOWER | Design Water Flow Rate [m3/s] | 1.47780E-002 |
470 | FluidCooler:TwoSpeed | CENTRAL TOWER | Air Flow Rate at High Fan Speed [m3/s] | 139666.46671 |
471 | FluidCooler:TwoSpeed | CENTRAL TOWER | Fluid cooler UA value at high fan speed based on nominal capacity input [W/K] | 54543.25446 |
472 | FluidCooler:TwoSpeed | CENTRAL TOWER | Air Flow Rate at Low Fan Speed [m3/s] | 69833.23335 |
473 | FluidCooler:TwoSpeed | CENTRAL TOWER | Fan Power at Low Fan Speed [W] | 7879.72339 |
474 | FluidCooler:TwoSpeed | CENTRAL TOWER | U-factor Times Area Value at Low Fan Speed [W/C] | 20907.77685 |
475 | Boiler:HotWater | CENTRAL BOILER | Design Size Nominal Capacity [W] | 608726.82280 |
476 | Boiler:HotWater | CENTRAL BOILER | User-Specified Nominal Capacity [W] | 595089.06000 |
477 | Boiler:HotWater | CENTRAL BOILER | Design Size Design Water Flow Rate [m3/s] | 1.47780E-002 |
478 | PlantLoop | SWHSYS1 | Maximum Loop Flow Rate [m3/s] | 4.40000E-004 |
479 | PlantLoop | SWHSYS1 | Plant Loop Volume [m3] | 5.28000E-002 |
480 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Flow Rate [m3/s] | 4.40000E-004 |
481 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Power Consumption [W] | 56.20530 |
482 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | Use Side Design Flow Rate [m3/s] | 4.40000E-004 |
483 | CondenserLoop | TOWERWATERSYS | Maximum Loop Flow Rate [m3/s] | 0.12063 |
484 | CondenserLoop | TOWERWATERSYS | Condenser Loop Volume [m3] | 14.47512 |
485 | HeaderedPumps:VariableSpeed | TOWERWATERSYS PUMP | Design Flow Rate [m3/s] | 0.12063 |
486 | HeaderedPumps:VariableSpeed | TOWERWATERSYS PUMP | Design Power Consumption [W] | 29864.32453 |
487 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Design Air Flow Rate [m3/s] | 56.67805 |
488 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Nominal Capacity [W] | 1447837.93760 |
489 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Air Flow Rate in free convection regime [m3/s] | 11.33561 |
490 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Tower capacity in free convection regime at design conditions [W] | 180979.74220 |
491 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Design Air Flow Rate [m3/s] | 56.67805 |
492 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Nominal Capacity [W] | 1447837.93760 |
493 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Air Flow Rate in free convection regime [m3/s] | 11.33561 |
494 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Tower capacity in free convection regime at design conditions [W] | 180979.74220 |
495 | PlantEquipmentOperation:ComponentSetPoint | WSHPPLANT OPERATION SCHEME | Design Water Flow Rate [m3/s] Equipment # 47 | 6.26450E-002 |
496 | PlantEquipmentOperation:ComponentSetPoint | WSHPPLANT OPERATION SCHEME | Design Water Flow Rate [m3/s] Equipment # 47 | 6.26450E-002 |
Component Type | Name | Nominal Total Capacity {W} | |
1 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | 16232.58 |
2 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | 394144.85 |
3 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | 76119.74 |
4 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | 10763.72 |
5 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | 7968.97 |
6 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | 12741.73 |
7 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | 7108.04 |
8 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | 201731.76 |
9 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | 133923.00 |
10 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | 199526.74 |
11 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | 127078.23 |
12 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | 25549.87 |
13 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | 16864.65 |
14 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | 25308.52 |
15 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | 16322.90 |
16 | Coil:Heating:Water | VAV_BOT WITH REHEAT HEATING COIL | 42062.96 |
17 | Coil:Heating:Water | VAV_MID WITH REHEAT HEATING COIL | 355087.08 |
18 | Coil:Heating:Water | VAV_TOP WITH REHEAT HEATING COIL | 33783.37 |
19 | Coil:Heating:Water | CAV_BAS HEATING COIL | 237311.59 |
Component Type | Name | Nominal Total Capacity {W} | Nominal Sensible Capacity {W} | Nominal Latent Capacity {W} | Nominal Sensible Heat Ratio | Nominal Coil UA Value {W/C} | Nominal Coil Surface Area {m2} | |
1 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | 267784.48 | 170492.61 | 97291.87 | 0.64 | 27465.93 | 278.57 |
2 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | 2524033.75 | 1603413.18 | 920620.58 | 0.64 | 258320.56 | 2620.03 |
3 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | 278164.21 | 177355.77 | 100808.43 | 0.64 | 28592.77 | 290.00 |
4 | Coil:Cooling:Water | CAV_BAS COOLING COIL | 147725.53 | 95633.87 | 52091.66 | 0.65 | 14601.45 | 148.10 |
Component Type | Component Name | IPLV in SI Units {W/W} | IPLV in IP Units {Btu/W-h} | |
1 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | 6.84 | 23.33 |
2 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | 6.84 | 23.33 |
Zone Name | # Surfaces | |
1 | BASEMENT | 10 |
2 | CORE_BOTTOM | 8 |
3 | CORE_MID | 7 |
4 | CORE_TOP | 7 |
5 | PERIMETER_BOT_ZN_3 | 18 |
6 | PERIMETER_BOT_ZN_2 | 12 |
7 | PERIMETER_BOT_ZN_1 | 18 |
8 | PERIMETER_BOT_ZN_4 | 12 |
9 | PERIMETER_MID_ZN_3 | 9 |
10 | PERIMETER_MID_ZN_2 | 8 |
11 | PERIMETER_MID_ZN_1 | 9 |
12 | PERIMETER_MID_ZN_4 | 8 |
13 | PERIMETER_TOP_ZN_3 | 9 |
14 | PERIMETER_TOP_ZN_2 | 8 |
15 | PERIMETER_TOP_ZN_1 | 9 |
16 | PERIMETER_TOP_ZN_4 | 8 |
17 | GROUNDFLOOR_PLENUM | 11 |
18 | MIDFLOOR_PLENUM | 11 |
19 | TOPFLOOR_PLENUM | 11 |
20 | DATACENTER_BOT_ZN_6 | 6 |
21 | DATACENTER_MID_ZN_6 | 6 |
22 | DATACENTER_TOP_ZN_6 | 6 |
23 | DATACENTER_BASEMENT_ZN_6 | 10 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | BASEMENT_WALL_EAST | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_EAST_CFACTOR | 0.419 | 0.394 | 118.87 | 118.87 | 118.87 | 90.00 | 90.00 | 48.74 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | BASEMENT_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_SOUTH_CFACTOR | 0.419 | 0.394 | 139.09 | 139.09 | 139.09 | 180.00 | 90.00 | 57.03 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
3 | BASEMENT_WALL_NORTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_NORTH_CFACTOR | 0.419 | 0.394 | 139.09 | 139.09 | 139.09 | 0.00 | 90.00 | 57.03 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | BASEMENT_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.87 | 118.87 | 118.87 | 270.00 | 90.00 | 48.74 | 2.44 | 0.00 | DATACENTER_BASEMENT_ZN_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
5 | BASEMENT_FLOOR | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 2779.43 | 2779.43 | 2779.43 | 0.00 | 180.00 | 57.03 | 48.74 | 0.00 | BASEMENT_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
6 | PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | PERIMETER_BOT_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
7 | PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 250.34 | 250.34 | 250.34 | 180.00 | 0.00 | 57.03 | 4.57 | 0.00 | PERIMETER_BOT_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
8 | CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 2076.77 | 2076.77 | 2076.77 | 180.00 | 0.00 | 52.45 | 39.59 | 0.00 | CORE_BOT_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
9 | PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 250.34 | 250.34 | 250.34 | 180.00 | 0.00 | 52.45 | 4.57 | 0.00 | PERIMETER_BOT_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
10 | BASEMENT_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 7126.21 | 7126.21 | 7126.21 | 0.00 | 90.00 | 7126.21 | 1.00 | 0.00 | BASEMENT_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
11 | CORE_BOT_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
12 | CORE_BOT_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
13 | CORE_BOT_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
14 | CORE_BOT_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
15 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 419.30 | 419.30 | 419.30 | 0.00 | 180.00 | 10.59 | 39.59 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
16 | CORE_BOT_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 2076.82 | 2076.82 | 2076.82 | 0.00 | 180.00 | 52.46 | 39.59 | 0.00 | CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
17 | CORE_BOT_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 2496.12 | 2496.12 | 2496.12 | 180.00 | 0.00 | 63.05 | 39.59 | 0.00 | iz-CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
18 | CORE_BOTTOM_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 5064.65 | 5064.65 | 5064.65 | 0.00 | 90.00 | 5064.65 | 1.00 | 0.00 | CORE_BOTTOM_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
19 | CORE_MID_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
20 | CORE_MID_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
21 | CORE_MID_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
22 | CORE_MID_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
23 | CORE_MID_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_MID_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
24 | CORE_MID_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 2496.12 | 2496.12 | 2496.12 | 180.00 | 0.00 | 63.05 | 39.59 | 0.00 | iz-CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
25 | CORE_MID_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 5064.65 | 5064.65 | 5064.65 | 0.00 | 90.00 | 5064.65 | 1.00 | 0.00 | CORE_MID_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
26 | CORE_TOP_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
27 | CORE_TOP_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
28 | CORE_TOP_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
29 | CORE_TOP_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
30 | CORE_TOP_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_TOP_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
31 | CORE_TOP_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 2496.12 | 2496.12 | 2496.12 | 180.00 | 0.00 | 63.05 | 39.59 | 0.00 | iz-CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
32 | CORE_TOP_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 5064.65 | 5064.65 | 5064.65 | 0.00 | 90.00 | 5064.65 | 1.00 | 0.00 | CORE_TOP_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
33 | PERIMETER_BOT_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.075 | 0.926 | 76.91 | 200.61 | 76.91 | 0.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
34 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.42_SHGC_NORTH_0.4 | N/A | 2.387 | No | 23.18 | 23.18 | 23.18 | 0.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
35 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.42_SHGC_NORTH_0.4 | N/A | 2.387 | No | 23.18 | 23.18 | 23.18 | 0.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
36 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.42_SHGC_NORTH_0.4 | N/A | 2.387 | No | 23.18 | 23.18 | 23.18 | 0.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
37 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.42_SHGC_NORTH_0.4 | N/A | 2.387 | No | 23.18 | 23.18 | 23.18 | 0.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
38 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.42_SHGC_NORTH_0.4 | N/A | 2.387 | No | 23.18 | 23.18 | 23.18 | 0.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
39 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.839 | 2.839 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
40 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.839 | 2.839 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
41 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.839 | 2.839 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
42 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.839 | 2.839 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
43 | PERIMETER_BOT_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
44 | CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
45 | PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
46 | DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
47 | PERIMETER_BOT_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 250.34 | 250.34 | 250.34 | 0.00 | 180.00 | 52.46 | 6.47 | 0.00 | PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
48 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 63.07 | 63.07 | 63.07 | 0.00 | 180.00 | 11.51 | 4.57 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
49 | PERIMETER_BOT_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.41 | 313.41 | 313.41 | 180.00 | 0.00 | 63.96 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
50 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.83 | 626.83 | 626.83 | 0.00 | 90.00 | 626.83 | 1.00 | 0.00 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
51 | PERIMETER_BOT_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.075 | 0.926 | 52.57 | 133.74 | 52.57 | 90.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
52 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.42_SHGC_EAST_0.4 | N/A | 2.387 | No | 25.75 | 25.75 | 25.75 | 90.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
53 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.42_SHGC_EAST_0.4 | N/A | 2.387 | No | 25.75 | 25.75 | 25.75 | 90.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
54 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.42_SHGC_EAST_0.4 | N/A | 2.387 | No | 25.75 | 25.75 | 25.75 | 90.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
55 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | Door | PERIMETER_BOT_ZN_2_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.839 | 2.839 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
56 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | Door | PERIMETER_BOT_ZN_2_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.839 | 2.839 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
57 | PERIMETER_BOT_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
58 | CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
59 | PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
60 | PERIMETER_BOT_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
61 | PERIMETER_BOT_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | iz-PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
62 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
63 | PERIMETER_BOT_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.075 | 0.926 | 76.91 | 200.61 | 76.91 | 180.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
64 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.42_SHGC_SOUTH_0.4 | N/A | 2.387 | No | 23.18 | 23.18 | 23.18 | 180.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
65 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.42_SHGC_SOUTH_0.4 | N/A | 2.387 | No | 23.18 | 23.18 | 23.18 | 180.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
66 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.42_SHGC_SOUTH_0.4 | N/A | 2.387 | No | 23.18 | 23.18 | 23.18 | 180.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
67 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.42_SHGC_SOUTH_0.4 | N/A | 2.387 | No | 23.18 | 23.18 | 23.18 | 180.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
68 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.42_SHGC_SOUTH_0.4 | N/A | 2.387 | No | 23.18 | 23.18 | 23.18 | 180.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
69 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.839 | 2.839 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
70 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.839 | 2.839 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
71 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.839 | 2.839 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
72 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.839 | 2.839 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
73 | PERIMETER_BOT_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
74 | DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
75 | PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
76 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
77 | DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 63.07 | 63.07 | 63.07 | 0.00 | 180.00 | 16.08 | 4.57 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
78 | PERIMETER_BOT_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 250.35 | 250.35 | 250.35 | 0.00 | 180.00 | 57.03 | 6.47 | 0.00 | PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
79 | PERIMETER_BOT_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.42 | 313.42 | 313.42 | 180.00 | 0.00 | 73.11 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
80 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.84 | 626.84 | 626.84 | 0.00 | 90.00 | 626.84 | 1.00 | 0.00 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
81 | PERIMETER_BOT_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.075 | 0.926 | 52.57 | 133.74 | 52.57 | 270.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
82 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.42_SHGC_WEST_0.4 | N/A | 2.387 | No | 25.75 | 25.75 | 25.75 | 270.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
83 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.42_SHGC_WEST_0.4 | N/A | 2.387 | No | 25.75 | 25.75 | 25.75 | 270.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
84 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.42_SHGC_WEST_0.4 | N/A | 2.387 | No | 25.75 | 25.75 | 25.75 | 270.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
85 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | Door | PERIMETER_BOT_ZN_4_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.839 | 2.839 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
86 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | Door | PERIMETER_BOT_ZN_4_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.839 | 2.839 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
87 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
88 | DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
89 | PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
90 | PERIMETER_BOT_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
91 | PERIMETER_BOT_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | iz-PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
92 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
93 | PERIMETER_MID_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.028 | 0.891 | 84.71 | 200.61 | 84.71 | 0.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
94 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_MID_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.42_SHGC_NORTH_0.4 | N/A | 2.387 | No | 115.90 | 115.90 | 115.90 | 0.00 | 90.00 | 73.11 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
95 | PERIMETER_MID_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
96 | CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
97 | PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
98 | DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
99 | PERIMETER_MID_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
100 | PERIMETER_MID_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.41 | 313.41 | 313.41 | 180.00 | 0.00 | 63.96 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
101 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.83 | 626.83 | 626.83 | 0.00 | 90.00 | 626.83 | 1.00 | 0.00 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
102 | PERIMETER_MID_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.028 | 0.891 | 56.47 | 133.74 | 56.47 | 90.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
103 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_MID_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.42_SHGC_EAST_0.4 | N/A | 2.387 | No | 77.26 | 77.26 | 77.26 | 90.00 | 90.00 | 48.74 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
104 | PERIMETER_MID_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
105 | CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
106 | PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
107 | PERIMETER_MID_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_MID_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
108 | PERIMETER_MID_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | iz-PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
109 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
110 | PERIMETER_MID_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
111 | PERIMETER_MID_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.028 | 0.891 | 84.71 | 200.61 | 84.71 | 180.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
112 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_MID_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.42_SHGC_SOUTH_0.4 | N/A | 2.387 | No | 115.90 | 115.90 | 115.90 | 180.00 | 90.00 | 73.11 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
113 | DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
114 | PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
115 | CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
116 | PERIMETER_MID_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
117 | PERIMETER_MID_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.42 | 313.42 | 313.42 | 180.00 | 0.00 | 73.11 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
118 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.84 | 626.84 | 626.84 | 0.00 | 90.00 | 626.84 | 1.00 | 0.00 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
119 | PERIMETER_MID_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.028 | 0.891 | 56.47 | 133.74 | 56.47 | 270.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
120 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_MID_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.42_SHGC_WEST_0.4 | N/A | 2.387 | No | 77.26 | 77.26 | 77.26 | 270.00 | 90.00 | 48.74 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
121 | PERIMETER_MID_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
122 | DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
123 | PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
124 | PERIMETER_MID_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_MID_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
125 | PERIMETER_MID_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | iz-PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
126 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
127 | PERIMETER_TOP_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.266 | 1.064 | 84.71 | 200.61 | 84.71 | 0.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
128 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_TOP_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.42_SHGC_NORTH_0.4 | N/A | 2.387 | No | 115.90 | 115.90 | 115.90 | 0.00 | 90.00 | 73.11 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
129 | PERIMETER_TOP_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
130 | CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
131 | PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
132 | DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
133 | PERIMETER_TOP_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_TOP_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
134 | PERIMETER_TOP_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.41 | 313.41 | 313.41 | 180.00 | 0.00 | 63.96 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
135 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.83 | 626.83 | 626.83 | 0.00 | 90.00 | 626.83 | 1.00 | 0.00 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
136 | PERIMETER_TOP_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.266 | 1.064 | 56.47 | 133.74 | 56.47 | 90.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
137 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_TOP_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.42_SHGC_EAST_0.4 | N/A | 2.387 | No | 77.26 | 77.26 | 77.26 | 90.00 | 90.00 | 48.74 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
138 | PERIMETER_TOP_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
139 | CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
140 | INT-PER3S-NE-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | INT-PER3S-NE | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
141 | PERIMETER_TOP_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_TOP_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
142 | PERIMETER_TOP_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | iz-PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
143 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
144 | PERIMETER_TOP_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.266 | 1.064 | 84.71 | 200.61 | 84.71 | 180.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
145 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_TOP_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.42_SHGC_SOUTH_0.4 | N/A | 2.387 | No | 115.90 | 115.90 | 115.90 | 180.00 | 90.00 | 73.11 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
146 | INT-PER3S-NE | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | INT-PER3S-NE-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
147 | DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
148 | PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
149 | CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
150 | PERIMETER_TOP_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_TOP_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
151 | PERIMETER_TOP_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.42 | 313.42 | 313.42 | 180.00 | 0.00 | 73.11 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
152 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.84 | 626.84 | 626.84 | 0.00 | 90.00 | 626.84 | 1.00 | 0.00 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
153 | PERIMETER_TOP_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.266 | 1.064 | 56.47 | 133.74 | 56.47 | 270.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
154 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_TOP_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.42_SHGC_WEST_0.4 | N/A | 2.387 | No | 77.26 | 77.26 | 77.26 | 270.00 | 90.00 | 48.74 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
155 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
156 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
157 | PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
158 | PERIMETER_TOP_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_TOP_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
159 | PERIMETER_TOP_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | iz-PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
160 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
161 | GROUNDFLOOR_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.075 | 0.926 | 89.13 | 89.13 | 89.13 | 0.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
162 | GROUNDFLOOR_PLENUM_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.075 | 0.926 | 59.42 | 59.42 | 59.42 | 270.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
163 | GROUNDFLOOR_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.075 | 0.926 | 89.13 | 89.13 | 89.13 | 180.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
164 | GROUNDFLOOR_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.075 | 0.926 | 59.42 | 59.42 | 59.42 | 90.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
165 | iz-CORE_BOT_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
166 | iz-PERIMETER_BOT_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
167 | iz-PERIMETER_BOT_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
168 | iz-PERIMETER_BOT_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
169 | iz-PERIMETER_BOT_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
170 | iz-DATACENTER_BOT_ZN_6_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_BOT_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
171 | GROUNDFLOOR_PLENUM_CEILING | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 3563.11 | 3563.11 | 3563.11 | 180.00 | 0.00 | 73.11 | 48.74 | 0.00 | GROUNDFLOOR_PLENUM_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
172 | MIDFLOOR_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.028 | 0.891 | 89.13 | 89.13 | 89.13 | 0.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
173 | MIDFLOOR_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.028 | 0.891 | 59.42 | 59.42 | 59.42 | 270.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
174 | MIDFLOOR_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.028 | 0.891 | 89.13 | 89.13 | 89.13 | 180.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
175 | MIDFLOOR_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.028 | 0.891 | 59.42 | 59.42 | 59.42 | 90.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
176 | iz-CORE_MID_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
177 | iz-PERIMETER_MID_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
178 | iz-PERIMETER_MID_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
179 | iz-PERIMETER_MID_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
180 | iz-PERIMETER_MID_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
181 | iz-DATACENTER_MID_ZN_6_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_MID_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
182 | MIDFLOOR_PLENUM_CEILING | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 3563.11 | 3563.11 | 3563.11 | 180.00 | 0.00 | 73.11 | 48.74 | 0.00 | MIDFLOOR_PLENUM_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
183 | TOPFLOOR_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.266 | 1.064 | 89.13 | 89.13 | 89.13 | 180.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
184 | TOPFLOOR_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.266 | 1.064 | 59.42 | 59.42 | 59.42 | 90.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
185 | TOPFLOOR_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.266 | 1.064 | 59.42 | 59.42 | 59.42 | 270.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
186 | TOPFLOOR_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.266 | 1.064 | 89.13 | 89.13 | 89.13 | 0.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
187 | iz-CORE_TOP_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
188 | iz-PERIMETER_TOP_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
189 | iz-PERIMETER_TOP_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
190 | iz-PERIMETER_TOP_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
191 | iz-PERIMETER_TOP_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
192 | iz-DATACENTER_TOP_ZN_6_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_TOP_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
193 | BUILDING_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 3563.11 | 3563.11 | 3563.11 | 180.00 | 0.00 | 73.11 | 48.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
194 | DATACENTER_BOT_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
195 | DATACENTER_BOT_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
196 | DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
197 | DATACENTER_BOT_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
198 | DATACENTER_BOT_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
199 | DATACENTER_BOT_ZN_6_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | iz-DATACENTER_BOT_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
200 | DATACENTER_MID_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
201 | DATACENTER_MID_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
202 | DATACENTER_MID_ZN_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
203 | DATACENTER_MID_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
204 | DATACENTER_MID_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_MID_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
205 | DATACENTER_MID_ZN_6_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | iz-DATACENTER_MID_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
206 | DATACENTER_TOP_ZN_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
207 | DATACENTER_TOP_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
208 | DATACENTER_TOP_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
209 | DATACENTER_TOP_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
210 | DATACENTER_TOP_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_TOP_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
211 | DATACENTER_TOP_ZN_6_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | iz-DATACENTER_TOP_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
212 | DATACENTER_BASEMENT_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR | 0.419 | 0.394 | 39.22 | 39.22 | 39.22 | 0.00 | 90.00 | 16.08 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
213 | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR | 0.419 | 0.394 | 39.22 | 39.22 | 39.22 | 180.00 | 90.00 | 16.08 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
214 | DATACENTER_BASEMENT_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR | 0.419 | 0.394 | 118.87 | 118.87 | 118.87 | 270.00 | 90.00 | 48.74 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
215 | DATACENTER_BASEMENT_ZN_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.87 | 118.87 | 118.87 | 90.00 | 90.00 | 48.74 | 2.44 | 0.00 | BASEMENT_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
216 | DATACENTER_BASEMENT_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 783.68 | 783.68 | 783.68 | 0.00 | 180.00 | 16.08 | 48.74 | 0.00 | DATACENTER_BASEMENT_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
217 | DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | DATACENTER_BOT_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
218 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 419.35 | 419.35 | 419.35 | 180.00 | 0.00 | 10.59 | 39.59 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
219 | PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | PERIMETER_BOT_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
220 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 63.08 | 63.08 | 63.08 | 180.00 | 0.00 | 16.08 | 6.47 | 0.00 | DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
221 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 63.07 | 63.07 | 63.07 | 180.00 | 0.00 | 11.51 | 6.47 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | BASEMENT | RunPeriod: RUNPERIOD 1 | 0.2641050645 | 0.2331974300 | Pass | Pass | 2.0267689830 | 4.8635486424 | Pass | Pass |
2 | CORE_BOTTOM | RunPeriod: RUNPERIOD 1 | 0.1155802427 | 0.1986360467 | Pass | Pass | 0.1754804434 | 0.3788184228 | Pass | Pass |
3 | CORE_MID | RunPeriod: RUNPERIOD 1 | 7.1311186234E-002 | 0.1317650729 | Pass | Pass | 0.1472543418 | 0.3528279445 | Pass | Pass |
4 | CORE_TOP | RunPeriod: RUNPERIOD 1 | 7.8194712930E-002 | 7.2681657095E-002 | Pass | Pass | 0.2948842236 | 0.4511583561 | Pass | Pass |
5 | PERIMETER_BOT_ZN_3 | RunPeriod: RUNPERIOD 1 | 9.0528135391E-002 | 0.1418708327 | Pass | Pass | 0.1747697094 | 0.3765778055 | Pass | Pass |
6 | PERIMETER_BOT_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.2343432981 | 0.3488225348 | Pass | Pass | 0.1775622768 | 0.3816599483 | Pass | Pass |
7 | PERIMETER_BOT_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.4042531187 | 0.7433477045 | Pass | Pass | 0.1953063143 | 0.4066039062 | Pass | Pass |
8 | PERIMETER_BOT_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.2430887597 | 0.4194602753 | Pass | Pass | 0.1757301349 | 0.3734298032 | Pass | Pass |
9 | PERIMETER_MID_ZN_3 | RunPeriod: RUNPERIOD 1 | 6.3676507495E-002 | 6.7357915401E-002 | Pass | Pass | 0.1465405770 | 0.3461750857 | Pass | Pass |
10 | PERIMETER_MID_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.2031004960 | 0.2665920240 | Pass | Pass | 0.1516017600 | 0.3606259040 | Pass | Pass |
11 | PERIMETER_MID_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.4485974653 | 0.7904273740 | Pass | Pass | 0.1863811184 | 0.4328979777 | Pass | Pass |
12 | PERIMETER_MID_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.1745638835 | 0.2595944122 | Pass | Pass | 0.1449748771 | 0.3416061508 | Pass | Pass |
13 | PERIMETER_TOP_ZN_3 | RunPeriod: RUNPERIOD 1 | 0.1442641281 | 0.1981359982 | Pass | Pass | 430.4155242131 | 5060.8821000008 | Pass | Pass |
14 | PERIMETER_TOP_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.1887940415 | 0.2058145566 | Pass | Pass | 2.6999162443 | 15.7336279695 | Pass | Pass |
15 | PERIMETER_TOP_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.3753418917 | 0.5628576017 | Pass | Pass | 0.3019727175 | 0.4563567961 | Pass | Pass |
16 | PERIMETER_TOP_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.1661613461 | 0.2123553250 | Pass | Pass | 1.9047968796 | 18.1745228502 | Pass | Pass |
17 | GROUNDFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 2.5822841500E-002 | 3.4237446320E-002 | Pass | Pass | 1.7105081443 | 9.5384252255 | Pass | Pass |
18 | MIDFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 4.1559449884E-002 | 6.0937862726E-002 | Pass | Pass | 0.2624894100 | 0.7392738377 | Pass | Pass |
19 | TOPFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 0.1039112971 | 8.1399530300E-002 | Pass | Pass | 0.5993694602 | 3.1065746271 | Pass | Pass |
20 | DATACENTER_BOT_ZN_6 | RunPeriod: RUNPERIOD 1 | 5.7732718570E-006 | 7.0145662318E-006 | Pass | Pass | 9.2583106698E-003 | 1.2242935953E-002 | Pass | Pass |
21 | DATACENTER_MID_ZN_6 | RunPeriod: RUNPERIOD 1 | 5.1324918840E-006 | 7.2125722435E-006 | Pass | Pass | 0.1970336574 | 0.6179398712 | Pass | Pass |
22 | DATACENTER_TOP_ZN_6 | RunPeriod: RUNPERIOD 1 | 3.7895396716E-002 | 3.2773548693E-002 | Pass | Pass | 0.1107626519 | 0.3570550597 | Pass | Pass |
23 | DATACENTER_BASEMENT_ZN_6 | RunPeriod: RUNPERIOD 1 | 6.7629273413E-005 | 7.9638331236E-005 | Pass | Pass | 9.6186280295E-005 | 1.1286417669E-004 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 08:43:29
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 8580.21 | 142.53 | 0.00 | 27626.59 | 16845.32 | 53194.64 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 08:43:29
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | -7.90 | 0.00 | -7.90 | Wetbulb [C] | 3.20 | 0.00 |
ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 35.10 | 13.50 | 15.70 | Wetbulb [C] | 4.40 | 220.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 0.00 | 0 | |||
Feb | 0.00 | 0 | |||
Mar | 0.00 | 0 | |||
Apr | 0.00 | 0 | |||
May | 9.00 | 6 | |||
Jun | 0.00 | 0 | |||
Jul | 0.00 | 0 | |||
Aug | 0.00 | 0 | |||
Sep | 0.00 | 0 | |||
Oct | 5.00 | 4 | |||
Nov | 9.00 | 7 | |||
Dec | 0.00 | 0 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 08:43:29
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BASEMENT_WALL_EAST | BASEMENT_WALL_EAST_CFACTOR | 1.00 | 0.399 | 0.419 | 118.87 | 118.87 | 90.00 | 90.00 | E |
BASEMENT_WALL_SOUTH | BASEMENT_WALL_SOUTH_CFACTOR | 1.00 | 0.399 | 0.419 | 139.09 | 139.09 | 180.00 | 90.00 | S |
BASEMENT_WALL_NORTH | BASEMENT_WALL_NORTH_CFACTOR | 1.00 | 0.399 | 0.419 | 139.09 | 139.09 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_3_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.926 | 1.075 | 200.61 | 76.91 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_2_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.926 | 1.075 | 133.74 | 52.57 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.926 | 1.075 | 200.61 | 76.91 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_4_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.926 | 1.075 | 133.74 | 52.57 | 270.00 | 90.00 | W |
PERIMETER_MID_ZN_3_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.891 | 1.028 | 2006.06 | 847.11 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_2_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 0.891 | 1.028 | 1337.37 | 564.74 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.891 | 1.028 | 2006.06 | 847.11 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_4_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 0.891 | 1.028 | 1337.37 | 564.74 | 270.00 | 90.00 | W |
PERIMETER_TOP_ZN_3_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 1.064 | 1.266 | 200.61 | 84.71 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_2_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 1.064 | 1.266 | 133.74 | 56.47 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 1.064 | 1.266 | 200.61 | 84.71 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_4_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 1.064 | 1.266 | 133.74 | 56.47 | 270.00 | 90.00 | W |
GROUNDFLOOR_PLENUM_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.926 | 1.075 | 89.13 | 89.13 | 0.00 | 90.00 | N |
GROUNDFLOOR_PLENUM_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.926 | 1.075 | 59.42 | 59.42 | 270.00 | 90.00 | W |
GROUNDFLOOR_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.926 | 1.075 | 89.13 | 89.13 | 180.00 | 90.00 | S |
GROUNDFLOOR_PLENUM_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.926 | 1.075 | 59.42 | 59.42 | 90.00 | 90.00 | E |
MIDFLOOR_PLENUM_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.891 | 1.028 | 891.32 | 891.32 | 0.00 | 90.00 | N |
MIDFLOOR_PLENUM_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 0.891 | 1.028 | 594.21 | 594.21 | 270.00 | 90.00 | W |
MIDFLOOR_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.891 | 1.028 | 891.32 | 891.32 | 180.00 | 90.00 | S |
MIDFLOOR_PLENUM_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 0.891 | 1.028 | 594.21 | 594.21 | 90.00 | 90.00 | E |
TOPFLOOR_PLENUM_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 1.064 | 1.266 | 89.13 | 89.13 | 180.00 | 90.00 | S |
TOPFLOOR_PLENUM_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 1.064 | 1.266 | 59.42 | 59.42 | 90.00 | 90.00 | E |
TOPFLOOR_PLENUM_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 1.064 | 1.266 | 59.42 | 59.42 | 270.00 | 90.00 | W |
TOPFLOOR_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 1.064 | 1.266 | 89.13 | 89.13 | 0.00 | 90.00 | N |
BUILDING_ROOF | NONRES_ROOF | 0.30 | 0.182 | 0.186 | 3563.11 | 3563.11 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_WALL_NORTH | DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR | 1.00 | 0.399 | 0.419 | 39.22 | 39.22 | 0.00 | 90.00 | N |
DATACENTER_BASEMENT_ZN_6_WALL_SOUTH | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR | 1.00 | 0.399 | 0.419 | 39.22 | 39.22 | 180.00 | 90.00 | S |
DATACENTER_BASEMENT_ZN_6_WALL_WEST | DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR | 1.00 | 0.399 | 0.419 | 118.87 | 118.87 | 270.00 | 90.00 | W |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BASEMENT_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 118.87 | 118.87 | 270.00 | 90.00 | W |
BASEMENT_FLOOR | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 2779.43 | 2779.43 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 225.00 | 0.00 | |
PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 250.34 | 250.34 | 180.00 | 0.00 | |
CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 2076.77 | 2076.77 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 250.34 | 250.34 | 180.00 | 0.00 | |
CORE_BOT_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
CORE_BOT_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
CORE_BOT_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 419.30 | 419.30 | 0.00 | 180.00 | |
CORE_BOT_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 2076.82 | 2076.82 | 0.00 | 180.00 | |
CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 180.00 | 0.00 | |
CORE_MID_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 180.00 | 90.00 | S |
CORE_MID_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 270.00 | 90.00 | W |
CORE_MID_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 0.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 90.00 | 90.00 | E |
CORE_MID_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 24961.20 | 24961.20 | 0.00 | 180.00 | |
CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 24961.20 | 24961.20 | 180.00 | 0.00 | |
CORE_TOP_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
CORE_TOP_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
CORE_TOP_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
CORE_TOP_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 2496.12 | 2496.12 | 0.00 | 180.00 | |
CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 250.34 | 250.34 | 0.00 | 180.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 63.07 | 63.07 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
PERIMETER_BOT_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 45.00 | 180.00 | |
PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 225.00 | 0.00 | |
PERIMETER_BOT_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 63.07 | 63.07 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 250.35 | 250.35 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
PERIMETER_BOT_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 315.00 | 180.00 | |
PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 135.00 | 0.00 | |
PERIMETER_MID_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 225.00 | 90.00 | W |
CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 135.00 | 90.00 | S |
DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 3134.13 | 3134.13 | 0.00 | 180.00 | |
PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.13 | 3134.13 | 180.00 | 0.00 | |
PERIMETER_MID_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 315.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 270.00 | 90.00 | W |
PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 225.00 | 90.00 | W |
PERIMETER_MID_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 2019.75 | 2019.75 | 45.00 | 180.00 | |
PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 225.00 | 0.00 | |
PERIMETER_MID_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 45.00 | 90.00 | E |
DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 315.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 3134.20 | 3134.20 | 0.00 | 180.00 | |
PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.20 | 3134.20 | 180.00 | 0.00 | |
PERIMETER_MID_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 135.00 | 90.00 | S |
DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 45.00 | 90.00 | E |
PERIMETER_MID_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 2019.75 | 2019.75 | 315.00 | 180.00 | |
PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 135.00 | 0.00 | |
PERIMETER_TOP_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 313.41 | 313.41 | 0.00 | 180.00 | |
PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 180.00 | 0.00 | |
PERIMETER_TOP_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
INT-PER3S-NE-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
PERIMETER_TOP_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 201.98 | 201.98 | 45.00 | 180.00 | |
PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 225.00 | 0.00 | |
INT-PER3S-NE | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 313.42 | 313.42 | 0.00 | 180.00 | |
PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 180.00 | 0.00 | |
PERIMETER_TOP_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
PERIMETER_TOP_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 201.98 | 201.98 | 315.00 | 180.00 | |
PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 135.00 | 0.00 | |
iz-CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 45.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 315.00 | 180.00 | |
iz-DATACENTER_BOT_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 0.00 | 180.00 | |
GROUNDFLOOR_PLENUM_CEILING | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 3563.11 | 3563.11 | 180.00 | 0.00 | |
iz-CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 24961.20 | 24961.20 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.13 | 3134.13 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 45.00 | 180.00 | |
iz-PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.20 | 3134.20 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 315.00 | 180.00 | |
iz-DATACENTER_MID_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 362.03 | 362.03 | 0.00 | 180.00 | |
MIDFLOOR_PLENUM_CEILING | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 35631.06 | 35631.06 | 180.00 | 0.00 | |
iz-CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 45.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 315.00 | 180.00 | |
iz-DATACENTER_TOP_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 0.00 | 180.00 | |
DATACENTER_BOT_ZN_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
DATACENTER_BOT_ZN_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
DATACENTER_BOT_ZN_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
DATACENTER_BOT_ZN_6_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 36.20 | 36.20 | 0.00 | 180.00 | |
DATACENTER_BOT_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 180.00 | 0.00 | |
DATACENTER_MID_ZN_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 270.00 | 90.00 | W |
DATACENTER_MID_ZN_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 180.00 | 90.00 | S |
DATACENTER_MID_ZN_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 90.00 | 90.00 | E |
DATACENTER_MID_ZN_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 0.00 | 90.00 | N |
DATACENTER_MID_ZN_6_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 362.03 | 362.03 | 0.00 | 180.00 | |
DATACENTER_MID_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 362.03 | 362.03 | 180.00 | 0.00 | |
DATACENTER_TOP_ZN_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
DATACENTER_TOP_ZN_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
DATACENTER_TOP_ZN_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
DATACENTER_TOP_ZN_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
DATACENTER_TOP_ZN_6_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 36.20 | 36.20 | 0.00 | 180.00 | |
DATACENTER_TOP_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 118.87 | 118.87 | 90.00 | 90.00 | E |
DATACENTER_BASEMENT_ZN_6_FLOOR | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 783.68 | 783.68 | 0.00 | 180.00 | |
DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 36.20 | 36.20 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 419.35 | 419.35 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 135.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 63.08 | 63.08 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 63.07 | 63.07 | 180.00 | 0.00 | |
BASEMENT_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 7126.21 | 0.00 | 90.00 | N | ||
CORE_BOTTOM_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 5064.65 | 0.00 | 90.00 | N | ||
CORE_MID_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 50646.53 | 0.00 | 90.00 | N | ||
CORE_TOP_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 5064.65 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.83 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.84 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 6268.26 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 4039.50 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 6268.35 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 4039.48 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.83 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.84 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | WINDOW_U_0.42_SHGC_NORTH_0.4 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.387 | 0.401 | 0.442 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | WINDOW_U_0.42_SHGC_NORTH_0.4 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.387 | 0.401 | 0.442 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | WINDOW_U_0.42_SHGC_NORTH_0.4 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.387 | 0.401 | 0.442 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | WINDOW_U_0.42_SHGC_NORTH_0.4 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.387 | 0.401 | 0.442 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | WINDOW_U_0.42_SHGC_NORTH_0.4 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.387 | 0.401 | 0.442 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | WINDOW_U_0.42_SHGC_EAST_0.4 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 2.387 | 0.401 | 0.442 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | WINDOW_U_0.42_SHGC_EAST_0.4 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 2.387 | 0.401 | 0.442 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | WINDOW_U_0.42_SHGC_EAST_0.4 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 2.387 | 0.401 | 0.442 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | WINDOW_U_0.42_SHGC_SOUTH_0.4 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.387 | 0.401 | 0.442 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | WINDOW_U_0.42_SHGC_SOUTH_0.4 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.387 | 0.401 | 0.442 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | WINDOW_U_0.42_SHGC_SOUTH_0.4 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.387 | 0.401 | 0.442 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | WINDOW_U_0.42_SHGC_SOUTH_0.4 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.387 | 0.401 | 0.442 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | WINDOW_U_0.42_SHGC_SOUTH_0.4 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.387 | 0.401 | 0.442 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | WINDOW_U_0.42_SHGC_WEST_0.4 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 2.387 | 0.401 | 0.442 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | WINDOW_U_0.42_SHGC_WEST_0.4 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 2.387 | 0.401 | 0.442 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | WINDOW_U_0.42_SHGC_WEST_0.4 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 2.387 | 0.401 | 0.442 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.42_SHGC_NORTH_0.4 | 115.90 | 0.00 | 0.00 | 115.90 | 1158.95 | 2.387 | 0.401 | 0.442 | No | PERIMETER_MID_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.42_SHGC_EAST_0.4 | 77.26 | 0.00 | 0.00 | 77.26 | 772.63 | 2.387 | 0.401 | 0.442 | No | PERIMETER_MID_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.42_SHGC_SOUTH_0.4 | 115.90 | 0.00 | 0.00 | 115.90 | 1158.95 | 2.387 | 0.401 | 0.442 | No | PERIMETER_MID_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.42_SHGC_WEST_0.4 | 77.26 | 0.00 | 0.00 | 77.26 | 772.63 | 2.387 | 0.401 | 0.442 | No | PERIMETER_MID_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.42_SHGC_NORTH_0.4 | 115.90 | 0.00 | 0.00 | 115.90 | 115.90 | 2.387 | 0.401 | 0.442 | No | PERIMETER_TOP_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.42_SHGC_EAST_0.4 | 77.26 | 0.00 | 0.00 | 77.26 | 77.26 | 2.387 | 0.401 | 0.442 | No | PERIMETER_TOP_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.42_SHGC_SOUTH_0.4 | 115.90 | 0.00 | 0.00 | 115.90 | 115.90 | 2.387 | 0.401 | 0.442 | No | PERIMETER_TOP_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.42_SHGC_WEST_0.4 | 77.26 | 0.00 | 0.00 | 77.26 | 77.26 | 2.387 | 0.401 | 0.442 | No | PERIMETER_TOP_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
Total or Average | 4635.80 | 2.387 | 0.401 | 0.442 | |||||||||||||||||
North Total or Average | 1390.74 | 2.387 | 0.401 | 0.442 | |||||||||||||||||
Non-North Total or Average | 3245.06 | 2.387 | 0.401 | 0.442 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | SWINGING DOOR_CON | 1.992 | 2.839 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | SWINGING DOOR_CON | 1.992 | 2.839 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | SWINGING DOOR_CON | 1.992 | 2.839 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | SWINGING DOOR_CON | 1.992 | 2.839 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | SWINGING DOOR_CON | 1.992 | 2.839 | 1.95 | PERIMETER_BOT_ZN_2_WALL_EAST |
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | SWINGING DOOR_CON | 1.992 | 2.839 | 1.95 | PERIMETER_BOT_ZN_2_WALL_EAST |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | SWINGING DOOR_CON | 1.992 | 2.839 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | SWINGING DOOR_CON | 1.992 | 2.839 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | SWINGING DOOR_CON | 1.992 | 2.839 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | SWINGING DOOR_CON | 1.992 | 2.839 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | SWINGING DOOR_CON | 1.992 | 2.839 | 1.95 | PERIMETER_BOT_ZN_4_WALL_WEST |
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | SWINGING DOOR_CON | 1.992 | 2.839 | 1.95 | PERIMETER_BOT_ZN_4_WALL_WEST |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 08:43:29
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 08:43:29
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
BASEMENT_LIGHTS | BASEMENT | BASEMENT | GENERAL | 10.2732 | 2779.43 | 28553.72 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 49.04 | 0.0000 | Y | 262.84 |
CORE_BOTTOM_LIGHTS | CORE_BOTTOM | CORE_BOTTOM | GENERAL | 10.2732 | 2496.12 | 25643.24 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 49.04 | 0.0000 | Y | 236.05 |
CORE_MID_LIGHTS | CORE_MID | CORE_MID | GENERAL | 10.2732 | 24961.20 | 256432.45 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 49.04 | 0.0000 | Y | 2360.52 |
CORE_TOP_LIGHTS | CORE_TOP | CORE_TOP | GENERAL | 10.2732 | 2496.12 | 25643.24 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 49.04 | 0.0000 | Y | 236.05 |
PERIMETER_BOT_ZN_3_LIGHTS | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3 | GENERAL | 10.2732 | 313.41 | 3219.77 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 28.25 | 0.0000 | Y | 17.08 |
PERIMETER_BOT_ZN_2_LIGHTS | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2 | GENERAL | 10.2732 | 201.98 | 2074.94 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 28.15 | 0.0000 | Y | 10.96 |
PERIMETER_BOT_ZN_1_LIGHTS | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1 | GENERAL | 10.2732 | 313.42 | 3219.84 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 27.89 | 0.0000 | Y | 16.85 |
PERIMETER_BOT_ZN_4_LIGHTS | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4 | GENERAL | 10.2732 | 201.98 | 2074.94 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 27.89 | 0.0000 | Y | 10.86 |
PERIMETER_MID_ZN_3_LIGHTS | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3 | GENERAL | 10.2732 | 3134.13 | 32197.65 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 28.21 | 0.0000 | Y | 170.47 |
PERIMETER_MID_ZN_2_LIGHTS | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2 | GENERAL | 10.2732 | 2019.75 | 20749.39 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 28.11 | 0.0000 | Y | 109.50 |
PERIMETER_MID_ZN_1_LIGHTS | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1 | GENERAL | 10.2732 | 3134.20 | 32198.36 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 27.86 | 0.0000 | Y | 168.40 |
PERIMETER_MID_ZN_4_LIGHTS | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4 | GENERAL | 10.2732 | 2019.75 | 20749.39 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 27.87 | 0.0000 | Y | 108.54 |
PERIMETER_TOP_ZN_3_LIGHTS | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3 | GENERAL | 10.2732 | 313.41 | 3219.77 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 28.20 | 0.0000 | Y | 17.05 |
PERIMETER_TOP_ZN_2_LIGHTS | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2 | GENERAL | 10.2732 | 201.98 | 2074.94 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 28.11 | 0.0000 | Y | 10.95 |
PERIMETER_TOP_ZN_1_LIGHTS | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1 | GENERAL | 10.2732 | 313.42 | 3219.84 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 27.86 | 0.0000 | Y | 16.84 |
PERIMETER_TOP_ZN_4_LIGHTS | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4 | GENERAL | 10.2732 | 201.98 | 2074.94 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 27.87 | 0.0000 | Y | 10.85 |
DATACENTER_BASEMENT_LIGHTS | DATACENTER_BASEMENT_ZN_6 | DATACENTER_BASEMENT_ZN_6 | GENERAL | 10.2732 | 783.68 | 8050.93 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 49.04 | 0.0000 | Y | 74.11 |
DATACENTER_BOT_LIGHTS | DATACENTER_BOT_ZN_6 | DATACENTER_BOT_ZN_6 | GENERAL | 17.8735 | 36.20 | 647.07 | LightsWired | LTG_SCH_DATACENTER | 56.02 | 168.00 | 54.57 | 0.0000 | Y | 6.63 |
DATACENTER_MID_LIGHTS | DATACENTER_MID_ZN_6 | DATACENTER_MID_ZN_6 | GENERAL | 17.8735 | 362.03 | 6470.68 | LightsWired | LTG_SCH_DATACENTER | 56.02 | 168.00 | 54.57 | 0.0000 | Y | 66.28 |
DATACENTER_TOP_LIGHTS | DATACENTER_TOP_ZN_6 | DATACENTER_TOP_ZN_6 | GENERAL | 17.8735 | 36.20 | 647.07 | LightsWired | LTG_SCH_DATACENTER | 56.02 | 168.00 | 54.57 | 0.0000 | Y | 6.63 |
Interior Lighting Total | 10.3445 | 46320.38 | 479162.15 | 1232.13 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
PERIMETER_BOT_ZN_1_DAYLREFPT1 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_DAYLCTRL | SplitFlux | Stepped | 0.39 | 3219.84 | 1241.89 |
PERIMETER_BOT_ZN_1_DAYLREFPT2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_DAYLCTRL | SplitFlux | Stepped | 0.14 | 3219.84 | 445.95 |
PERIMETER_BOT_ZN_2_DAYLREFPT1 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_DAYLCTRL | SplitFlux | Stepped | 0.39 | 2074.94 | 800.30 |
PERIMETER_BOT_ZN_2_DAYLREFPT2 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_DAYLCTRL | SplitFlux | Stepped | 0.14 | 2074.94 | 287.38 |
PERIMETER_BOT_ZN_3_DAYLREFPT1 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_DAYLCTRL | SplitFlux | Stepped | 0.39 | 3219.77 | 1241.86 |
PERIMETER_BOT_ZN_3_DAYLREFPT2 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_DAYLCTRL | SplitFlux | Stepped | 0.14 | 3219.77 | 445.94 |
PERIMETER_BOT_ZN_4_DAYLREFPT1 | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_DAYLCTRL | SplitFlux | Stepped | 0.39 | 2074.94 | 800.30 |
PERIMETER_BOT_ZN_4_DAYLREFPT2 | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_DAYLCTRL | SplitFlux | Stepped | 0.14 | 2074.94 | 287.38 |
PERIMETER_MID_ZN_1_DAYLREFPT1 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_DAYLCTRL | SplitFlux | Stepped | 0.39 | 3219.84 | 1241.89 |
PERIMETER_MID_ZN_1_DAYLREFPT2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_DAYLCTRL | SplitFlux | Stepped | 0.14 | 3219.84 | 445.95 |
PERIMETER_MID_ZN_2_DAYLREFPT1 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_DAYLCTRL | SplitFlux | Stepped | 0.39 | 2074.94 | 800.30 |
PERIMETER_MID_ZN_2_DAYLREFPT2 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_DAYLCTRL | SplitFlux | Stepped | 0.14 | 2074.94 | 287.38 |
PERIMETER_MID_ZN_3_DAYLREFPT1 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_DAYLCTRL | SplitFlux | Stepped | 0.39 | 3219.77 | 1241.86 |
PERIMETER_MID_ZN_3_DAYLREFPT2 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_DAYLCTRL | SplitFlux | Stepped | 0.14 | 3219.77 | 445.94 |
PERIMETER_MID_ZN_4_DAYLREFPT1 | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_DAYLCTRL | SplitFlux | Stepped | 0.39 | 2074.94 | 800.30 |
PERIMETER_MID_ZN_4_DAYLREFPT2 | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_DAYLCTRL | SplitFlux | Stepped | 0.14 | 2074.94 | 287.38 |
PERIMETER_TOP_ZN_1_DAYLREFPT1 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_DAYLCTRL | SplitFlux | Stepped | 0.39 | 3219.84 | 1241.89 |
PERIMETER_TOP_ZN_1_DAYLREFPT2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_DAYLCTRL | SplitFlux | Stepped | 0.14 | 3219.84 | 445.95 |
PERIMETER_TOP_ZN_2_DAYLREFPT1 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_DAYLCTRL | SplitFlux | Stepped | 0.39 | 2074.94 | 800.30 |
PERIMETER_TOP_ZN_2_DAYLREFPT2 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_DAYLCTRL | SplitFlux | Stepped | 0.14 | 2074.94 | 287.38 |
PERIMETER_TOP_ZN_3_DAYLREFPT1 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_DAYLCTRL | SplitFlux | Stepped | 0.39 | 3219.77 | 1241.86 |
PERIMETER_TOP_ZN_3_DAYLREFPT2 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_DAYLCTRL | SplitFlux | Stepped | 0.14 | 3219.77 | 445.94 |
PERIMETER_TOP_ZN_4_DAYLREFPT1 | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_DAYLCTRL | SplitFlux | Stepped | 0.39 | 2074.94 | 800.30 |
PERIMETER_TOP_ZN_4_DAYLREFPT2 | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_DAYLCTRL | SplitFlux | Stepped | 0.14 | 2074.94 | 287.38 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS_A | 13279.00 | AstronomicalClock | - | 41.81 | 41.81 | 104.23 | |
EXTERIOR_LIGHTS_B | 44301.60 | AstronomicalClock | - | 83.71 | 71.14 | 591.59 | |
Exterior Lighting Total | 57580.60 | 695.82 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 08:43:29
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
BYPASS HEAT EXCHANGER | HeatExchanger:FluidToFluid | 2378030.41 | |||||
HEATSYS1 BOILER | Boiler:HotWater | 2178883.43 | 0.81 | ||||
COOLSYS1 CHILLER1 | Chiller:Electric:ReformulatedEIR | 1218781.75 | 6.28 | 1166539.56 | 5.98 | 6.84 | 23.33 |
COOLSYS1 CHILLER2 | Chiller:Electric:ReformulatedEIR | 1218781.75 | 6.28 | 1166539.56 | 5.98 | 6.84 | 23.33 |
CENTRAL TOWER | FluidCooler:TwoSpeed | 582060.00 | |||||
CENTRAL BOILER | Boiler:HotWater | 595089.06 | 0.80 | ||||
TOWERWATERSYS COOLTOWER 1 | CoolingTower:VariableSpeed | 1447837.94 | |||||
TOWERWATERSYS COOLTOWER 2 | CoolingTower:VariableSpeed | 1447837.94 |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
VAV_BOT WITH REHEAT COOLING COIL | Coil:Cooling:Water | 197464.45 | 267784.48 | 170492.61 | 97291.87 | 0.64 | - | 27465.93 | 278.57 |
VAV_MID WITH REHEAT COOLING COIL | Coil:Cooling:Water | 1874643.09 | 2524033.75 | 1603413.18 | 920620.58 | 0.64 | - | 258320.56 | 2620.03 |
VAV_TOP WITH REHEAT COOLING COIL | Coil:Cooling:Water | 204050.78 | 278164.21 | 177355.77 | 100808.43 | 0.64 | - | 28592.77 | 290.00 |
CAV_BAS COOLING COIL | Coil:Cooling:Water | 107353.46 | 147725.53 | 95633.87 | 52091.66 | 0.65 | - | 14601.45 | 148.10 |
AIRLOOP DATACENTER BASEMENT COOLING COIL | Coil:Cooling:WaterToAirHeatPump:EquationFit | 477837.93 | 253468.45 | 224369.48 | 0.53 | 0.00 | |||
AIRLOOP DATACENTER BOT COOLING COIL | Coil:Cooling:WaterToAirHeatPump:EquationFit | 10848.53 | 5808.33 | 5040.20 | 0.54 | 0.00 | |||
AIRLOOP DATACENTER MID COOLING COIL | Coil:Cooling:WaterToAirHeatPump:EquationFit | 104123.97 | 55735.08 | 48388.89 | 0.54 | 0.00 | |||
AIRLOOP DATACENTER TOP COOLING COIL | Coil:Cooling:WaterToAirHeatPump:EquationFit | 10621.04 | 5685.83 | 4935.22 | 0.54 | 0.00 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
None |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
None |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Water | 17116.65 | 16232.58 | - |
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Water | 415860.09 | 394144.85 | - |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Water | 80297.93 | 76119.74 | - |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 11355.25 | 10763.72 | - |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 8410.04 | 7968.97 | - |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 13442.38 | 12741.73 | - |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 7498.38 | 7108.04 | - |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 212844.56 | 201731.76 | - |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 141301.07 | 133923.00 | - |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 210517.74 | 199526.74 | - |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 134078.30 | 127078.23 | - |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 26958.17 | 25549.87 | - |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 17794.28 | 16864.65 | - |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 26703.49 | 25308.52 | - |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 17222.62 | 16322.90 | - |
VAV_BOT WITH REHEAT HEATING COIL | Coil:Heating:Water | 53488.05 | 42062.96 | - |
VAV_MID WITH REHEAT HEATING COIL | Coil:Heating:Water | 442531.84 | 355087.08 | - |
VAV_TOP WITH REHEAT HEATING COIL | Coil:Heating:Water | 41023.75 | 33783.37 | - |
CAV_BAS HEATING COIL | Coil:Heating:Water | 300438.84 | 237311.59 | - |
AIRLOOP DATACENTER BASEMENT HEATING COIL | Coil:Heating:WaterToAirHeatPump:EquationFit | 477837.93 | 0.00 | |
AIRLOOP DATACENTER BOT HEATING COIL | Coil:Heating:WaterToAirHeatPump:EquationFit | 10848.53 | 0.00 | |
AIRLOOP DATACENTER MID HEATING COIL | Coil:Heating:WaterToAirHeatPump:EquationFit | 104123.97 | 0.00 | |
AIRLOOP DATACENTER TOP HEATING COIL | Coil:Heating:WaterToAirHeatPump:EquationFit | 10621.04 | 0.00 | |
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | Coil:Heating:Electric | 16131.55 | 1.00 | |
AIRLOOP DATACENTER BOT_SUPPHEATCOIL | Coil:Heating:Electric | 745.21 | 1.00 | |
AIRLOOP DATACENTER MID_SUPPHEATCOIL | Coil:Heating:Electric | 7452.11 | 1.00 | |
AIRLOOP DATACENTER TOP_SUPPHEATCOIL | Coil:Heating:Electric | 745.21 | 1.00 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
VAV_BOT WITH REHEAT FAN | Fan:VariableVolume | 0.61 | 1314.72 | 12.53 | 26935.32 | 2149.46 | 1.00 | 1.12 | General | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 |
VAV_MID WITH REHEAT FAN | Fan:VariableVolume | 0.61 | 1314.72 | 117.44 | 252423.00 | 2149.46 | 1.00 | 1.08 | General | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 |
VAV_TOP WITH REHEAT FAN | Fan:VariableVolume | 0.61 | 1314.72 | 13.06 | 28078.04 | 2149.46 | 1.00 | 1.12 | General | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:40:00 |
CAV_BAS FAN | Fan:ConstantVolume | 0.60 | 1018.41 | 7.31 | 12315.28 | 1684.71 | 1.00 | 1.15 | General | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
AIRLOOP DATACENTER BASEMENT SUPPLY FAN | Fan:OnOff | 0.62 | 1018.41 | 26.11 | 42873.76 | 1642.33 | 1.00 | 1.14 | General | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 07:10:00 |
AIRLOOP DATACENTER BOT SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.61 | 681.59 | 1120.11 | 1.00 | 1.53 | General | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
AIRLOOP DATACENTER MID SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 5.84 | 6539.04 | 1120.11 | 1.00 | 1.14 | General | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
AIRLOOP DATACENTER TOP SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.60 | 667.15 | 1120.11 | 1.00 | 1.53 | General | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
COOLSYS1 PUMP SECONDARY | Pump:VariableSpeed | Intermittent | 105797.75 | 0.101400 | 16555.54 | 163269.45 | 0.90 | General |
HEATSYS1 PUMP | Pump:VariableSpeed | Intermittent | 180705.70 | 0.019062 | 5740.58 | 301156.09 | 0.90 | General |
COOLSYS1 CHILLER1 PUMP | Pump:ConstantSpeed | Intermittent | 73247.35 | 0.050700 | 5730.98 | 113036.94 | 0.90 | General |
COOLSYS1 CHILLER2 PUMP | Pump:ConstantSpeed | Intermittent | 73247.35 | 0.050700 | 5730.98 | 113036.94 | 0.90 | General |
PLANT CIRC PUMP | Pump:ConstantSpeed | Intermittent | 179045.11 | 0.014778 | 3769.13 | 255050.01 | 0.90 | General |
SWHSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 29891.00 | 0.000440 | 56.21 | 127739.32 | 0.30 | General |
TOWERWATERSYS PUMP | HeaderedPumps:VariableSpeed | Intermittent | 148556.62 | 0.120626 | 29864.32 | 247577.87 | 0.90 | General |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 1.14 | 87921.32 | 0.80 | 0.48 | 0.06 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:43:29
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 83206.96 | 83206.96 | 29.94 | 7.310 | 7.310 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 24.00 | 24.00 | 0.00741 | 25.11 | 0.00568 | 1.200 | 0.00 |
CORE_BOTTOM | 85875.41 | 85875.41 | 34.40 | 7.543 | 7.543 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 24.00 | 24.00 | 0.00736 | 25.11 | 0.00568 | 1.078 | 0.00 |
CORE_MID | 810018.21 | 810018.21 | 324.51 | 71.138 | 71.138 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 24.00 | 24.00 | 0.00738 | 25.11 | 0.00568 | 10.778 | 0.00 |
CORE_TOP | 79787.37 | 79787.37 | 31.96 | 7.007 | 7.007 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 24.00 | 24.00 | 0.00739 | 25.11 | 0.00568 | 1.078 | 0.00 |
PERIMETER_BOT_ZN_3 | 15241.16 | 15241.16 | 48.63 | 1.350 | 1.350 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 24.00 | 24.00 | 0.00722 | 35.10 | 0.00570 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_2 | 19079.17 | 19079.17 | 94.46 | 1.690 | 1.690 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | 24.00 | 24.00 | 0.00711 | 27.68 | 0.00569 | 0.087 | 0.00 |
PERIMETER_BOT_ZN_1 | 19170.13 | 19170.13 | 61.16 | 1.698 | 1.698 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:10:00 | 24.00 | 24.00 | 0.00718 | 34.54 | 0.00570 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_4 | 23562.10 | 23562.10 | 116.66 | 2.087 | 2.087 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 | 24.00 | 24.00 | 0.00709 | 33.39 | 0.00570 | 0.087 | 0.00 |
PERIMETER_MID_ZN_3 | 146306.11 | 146306.11 | 466.82 | 12.959 | 12.959 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | 24.00 | 24.00 | 0.00719 | 35.10 | 0.00570 | 1.353 | 0.00 |
PERIMETER_MID_ZN_2 | 203797.75 | 203797.75 | 1009.02 | 18.051 | 18.051 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:20:00 | 24.00 | 24.00 | 0.00709 | 28.44 | 0.00569 | 0.872 | 0.00 |
PERIMETER_MID_ZN_1 | 187995.80 | 187995.80 | 599.82 | 16.652 | 16.652 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 24.00 | 24.00 | 0.00715 | 34.76 | 0.00570 | 1.353 | 0.00 |
PERIMETER_MID_ZN_4 | 220149.76 | 220149.76 | 1089.98 | 19.500 | 19.500 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 24.00 | 24.00 | 0.00708 | 33.21 | 0.00570 | 0.872 | 0.00 |
PERIMETER_TOP_ZN_3 | 16550.97 | 16550.97 | 52.81 | 1.466 | 1.466 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | 24.00 | 24.00 | 0.00716 | 35.10 | 0.00570 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_2 | 20572.96 | 20572.96 | 101.86 | 1.822 | 1.822 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:30:00 | 24.00 | 24.00 | 0.00708 | 28.82 | 0.00569 | 0.087 | 0.00 |
PERIMETER_TOP_ZN_1 | 20562.05 | 20562.05 | 65.61 | 1.821 | 1.821 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 24.00 | 24.00 | 0.00713 | 34.88 | 0.00570 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_4 | 23280.73 | 23280.73 | 115.27 | 2.062 | 2.062 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 24.00 | 24.00 | 0.00707 | 33.21 | 0.00570 | 0.087 | 0.00 |
DATACENTER_BOT_ZN_6 | 8709.73 | 8709.73 | 240.58 | 0.609 | 0.609 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:50:00 | 27.00 | 27.00 | 0.00708 | 30.17 | 0.00569 | 0.016 | 0.00 |
DATACENTER_MID_ZN_6 | 83558.40 | 83558.40 | 2308.07 | 5.838 | 5.838 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:50:00 | 27.00 | 27.00 | 0.00709 | 30.17 | 0.00569 | 0.156 | 0.00 |
DATACENTER_TOP_ZN_6 | 8525.10 | 8525.10 | 235.48 | 0.596 | 0.596 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | 27.00 | 27.00 | 0.00708 | 30.51 | 0.00569 | 0.016 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 373654.68 | 373654.68 | 476.80 | 26.105 | 26.105 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 07:00:00 | 27.00 | 27.00 | 0.00704 | 22.82 | 0.00568 | 0.338 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.000 | 1.200 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 24.27 | 0.00234 | -7.90 | 0.00234 | 1.200 | 0.00 |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.000 | 1.078 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 06:20:00 | 19.60 | 21.74 | 0.00234 | -7.90 | 0.00234 | 1.078 | 0.00 |
CORE_MID | 247369.64 | 247369.64 | 99.10 | 12.692 | 12.692 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00800 | -7.90 | 0.00234 | 10.778 | 0.00 |
CORE_TOP | 56227.71 | 56227.71 | 22.53 | 2.907 | 2.907 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00800 | -7.90 | 0.00234 | 1.078 | 0.00 |
PERIMETER_BOT_ZN_3 | 7952.37 | 7952.37 | 25.37 | 0.411 | 0.411 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00754 | -7.90 | 0.00234 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_2 | 5613.42 | 5613.42 | 27.79 | 0.290 | 0.290 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00760 | -7.90 | 0.00234 | 0.087 | 0.00 |
PERIMETER_BOT_ZN_1 | 9411.42 | 9411.42 | 30.03 | 0.487 | 0.487 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00768 | -7.90 | 0.00234 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_4 | 4047.32 | 4047.32 | 20.04 | 0.209 | 0.209 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00722 | -7.90 | 0.00234 | 0.087 | 0.00 |
PERIMETER_MID_ZN_3 | 148955.93 | 148955.93 | 475.27 | 7.721 | 7.721 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00765 | -7.90 | 0.00234 | 1.353 | 0.00 |
PERIMETER_MID_ZN_2 | 98885.26 | 98885.26 | 489.59 | 5.126 | 5.126 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00765 | -7.90 | 0.00234 | 0.872 | 0.00 |
PERIMETER_MID_ZN_1 | 147329.21 | 147329.21 | 470.07 | 7.636 | 7.636 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00765 | -7.90 | 0.00234 | 1.353 | 0.00 |
PERIMETER_MID_ZN_4 | 93835.40 | 93835.40 | 464.59 | 4.864 | 4.864 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00763 | -7.90 | 0.00234 | 0.872 | 0.00 |
PERIMETER_TOP_ZN_3 | 18863.42 | 18863.42 | 60.19 | 0.978 | 0.978 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00766 | -7.90 | 0.00234 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_2 | 12451.05 | 12451.05 | 61.65 | 0.646 | 0.646 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00766 | -7.90 | 0.00234 | 0.087 | 0.00 |
PERIMETER_TOP_ZN_1 | 18685.36 | 18685.36 | 59.62 | 0.969 | 0.969 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00766 | -7.90 | 0.00234 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_4 | 12051.33 | 12051.33 | 59.67 | 0.625 | 0.625 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00765 | -7.90 | 0.00234 | 0.087 | 0.00 |
DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.016 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 06:20:00 | 18.00 | 26.02 | 0.00698 | -7.90 | 0.00234 | 0.016 | 0.00 |
DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.156 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 05:40:00 | 18.00 | 23.03 | 0.00335 | -7.90 | 0.00234 | 0.156 | 0.00 |
DATACENTER_TOP_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.016 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 05:40:00 | 18.00 | 21.27 | 0.00284 | -7.90 | 0.00234 | 0.016 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.338 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 02:10:00 | 18.00 | 27.00 | 0.00700 | -7.90 | 0.00234 | 0.338 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
VAV_BOT WITH REHEAT | 12.53 | 12.53 | 2.48 | 2.48 | 12.5312 | 3.4319 | 12.5312 | 0.2739 | 0.3000 |
VAV_MID WITH REHEAT | 117.44 | 117.44 | 38.04 | 38.04 | 117.4353 | 38.0394 | 117.4353 | 0.3239 | 0.3000 |
VAV_TOP WITH REHEAT | 13.06 | 13.06 | 6.12 | 6.12 | 13.0628 | 6.1245 | 13.0628 | 0.4689 | 0.3000 |
CAV_BAS | 7.31 | 7.31 | 1.20 | 1.20 | 7.3100 | 7.3100 | 7.3100 | 1.0000 | 1.0000 |
AIRLOOP DATACENTER BASEMENT | 26.11 | 26.11 | 0.34 | 0.34 | 26.1054 | 26.1052 | 26.1054 | 1.0000 | 1.0000 |
AIRLOOP DATACENTER BOT | 0.61 | 0.61 | 0.02 | 0.02 | 0.6085 | 0.6085 | 0.6085 | 1.0000 | 1.0000 |
AIRLOOP DATACENTER MID | 5.84 | 5.84 | 0.16 | 0.16 | 5.8379 | 5.8379 | 5.8379 | 1.0000 | 1.0000 |
AIRLOOP DATACENTER TOP | 0.60 | 0.60 | 0.02 | 0.02 | 0.5956 | 0.5956 | 0.5956 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | 17116.646 | 17116.646 | 2.066869 | 0.00014974 | 345.058 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 06:20:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 06:20:00 | 17116.65 | 17116.65 | 2.066869 | 12.80 | 9.86 | 0.00800000 | 40.00 | 18.92 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 0.0000 | 21.00 | 0.00800000 | 42.5367 | 0.00 | 0.00 | 17179.76 | 17179.76 |
CORE_MID VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | 415860.086 | 415860.086 | 20.345554 | 0.00363813 | 9823.560 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 415860.09 | 415860.09 | 20.345554 | 12.80 | 9.86 | 0.00800000 | 40.00 | 18.92 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 0.0000 | 21.00 | 0.00800000 | 42.5367 | 247369.64 | 0.00 | 417219.33 | 417219.33 |
CORE_TOP VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | 80297.934 | 80297.934 | 2.906528 | 0.00070248 | 2119.499 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 80297.93 | 80297.93 | 2.906528 | 12.80 | 9.86 | 0.00800000 | 40.00 | 18.92 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 0.0000 | 21.00 | 0.00800000 | 42.5367 | 56227.71 | 0.00 | 80574.55 | 80574.55 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | 11355.254 | 11355.254 | 0.411323 | 0.00009934 | 299.627 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 11355.25 | 11355.25 | 0.411323 | 12.80 | 9.86 | 0.00800000 | 40.00 | 18.92 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 0.0000 | 21.00 | 0.00753808 | 40.1136 | 7952.37 | 0.00 | 11393.65 | 11393.65 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | 8410.038 | 8410.038 | 0.337994 | 0.00007357 | 212.383 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 8410.04 | 8410.04 | 0.337994 | 12.80 | 9.86 | 0.00800000 | 40.00 | 18.92 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 0.0000 | 21.00 | 0.00760470 | 40.4635 | 5613.42 | 0.00 | 8436.11 | 8436.11 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | 13442.384 | 13442.384 | 0.487100 | 0.00011760 | 354.641 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 13442.38 | 13442.38 | 0.487100 | 12.80 | 9.86 | 0.00800000 | 40.00 | 18.92 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 0.0000 | 21.00 | 0.00767661 | 40.8410 | 9411.42 | 0.00 | 13487.42 | 13487.42 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | 7498.376 | 7498.376 | 0.417410 | 0.00006560 | 171.060 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 7498.38 | 7498.38 | 0.417410 | 12.80 | 9.86 | 0.00800000 | 40.00 | 18.92 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 0.0000 | 21.00 | 0.00722236 | 38.4539 | 4047.32 | 0.00 | 7523.87 | 7523.87 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | 212844.560 | 212844.560 | 7.721031 | 0.00186206 | 5612.545 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 212844.56 | 212844.56 | 7.721031 | 12.80 | 9.86 | 0.00800000 | 40.00 | 18.92 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 0.0000 | 21.00 | 0.00765251 | 40.7154 | 148955.93 | 0.00 | 213537.63 | 213537.63 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | 141301.069 | 141301.069 | 5.126031 | 0.00123616 | 3725.909 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 141301.07 | 141301.07 | 5.126031 | 12.80 | 9.86 | 0.00800000 | 40.00 | 18.92 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 0.0000 | 21.00 | 0.00765220 | 40.7139 | 98885.26 | 0.00 | 141760.53 | 141760.53 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | 210517.741 | 210517.741 | 7.636483 | 0.00184170 | 5551.236 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 210517.74 | 210517.74 | 7.636483 | 12.80 | 9.86 | 0.00800000 | 40.00 | 18.92 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 0.0000 | 21.00 | 0.00764847 | 40.6942 | 147329.21 | 0.00 | 211203.58 | 211203.58 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | 134078.301 | 134078.301 | 4.863627 | 0.00117298 | 3535.581 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 134078.30 | 134078.30 | 4.863627 | 12.80 | 9.86 | 0.00800000 | 40.00 | 18.92 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 0.0000 | 21.00 | 0.00763239 | 40.6098 | 93835.40 | 0.00 | 134515.19 | 134515.19 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | 26958.167 | 26958.167 | 0.978271 | 0.00023584 | 710.749 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 26958.17 | 26958.17 | 0.978271 | 12.80 | 9.86 | 0.00800000 | 40.00 | 18.92 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 0.0000 | 21.00 | 0.00766309 | 40.7717 | 18863.42 | 0.00 | 27045.11 | 27045.11 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | 17794.282 | 17794.282 | 0.645750 | 0.00015567 | 469.137 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 17794.28 | 17794.28 | 0.645750 | 12.80 | 9.86 | 0.00800000 | 40.00 | 18.92 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 0.0000 | 21.00 | 0.00765998 | 40.7554 | 12451.05 | 0.00 | 17851.61 | 17851.61 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | 26703.486 | 26703.486 | 0.969017 | 0.00023361 | 704.038 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 26703.49 | 26703.49 | 0.969017 | 12.80 | 9.86 | 0.00800000 | 40.00 | 18.92 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 0.0000 | 21.00 | 0.00766004 | 40.7556 | 18685.36 | 0.00 | 26789.63 | 26789.63 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | 17222.620 | 17222.620 | 0.624984 | 0.00015067 | 454.072 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 17222.62 | 17222.62 | 0.624984 | 12.80 | 9.86 | 0.00800000 | 40.00 | 18.92 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 0.0000 | 21.00 | 0.00764936 | 40.6997 | 12051.33 | 0.00 | 17278.16 | 17278.16 |
VAV_BOT WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | VAV_BOT WITH REHEAT | 197464.453 | -999.000 | 12.531175 | 0.00840059 | -999.000 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 197464.45 | 197464.45 | 12.531175 | 26.30 | 13.90 | 0.00696823 | 10.67 | 7.95 | 0.00696823 | 35.10 | 0.00569938 | 15.77 | 20.2550 | 24.00 | 0.00730003 | 32.3850 | 138232.88 | 0.00 | 177309.01 | 177309.01 |
VAV_BOT WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoopHVAC | VAV_BOT WITH REHEAT | 53488.048 | 53488.048 | 3.759352 | 0.00046794 | 889.542 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 53488.05 | 53488.05 | 3.759352 | -1.50 | -2.61 | 0.00329874 | 12.80 | 9.86 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 67.5167 | 21.26 | 0.00583735 | 30.6494 | 27024.53 | 0.00 | 50885.45 | 50885.45 |
VAV_MID WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | VAV_MID WITH REHEAT | 1874643.088 | -999.000 | 117.435292 | 0.07975165 | -999.000 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 1874643.09 | 1874643.07 | 117.435292 | 26.50 | 13.95 | 0.00694831 | 10.67 | 7.93 | 0.00694831 | 35.10 | 0.00569938 | 15.77 | 21.6136 | 24.00 | 0.00731233 | 32.4387 | 1269697.76 | 0.00 | 1681868.91 | 1681868.91 |
VAV_MID WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoopHVAC | VAV_MID WITH REHEAT | 442531.844 | 442531.844 | 35.230587 | 0.00387146 | 7433.870 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 22:10:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 442531.84 | 442531.84 | 35.230587 | 0.18 | -0.96 | 0.00383608 | 12.80 | 9.86 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 72.0452 | 19.70 | 0.00760492 | 43.8327 | 393365.38 | 0.00 | 429642.22 | 429642.22 |
VAV_TOP WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | VAV_TOP WITH REHEAT | 204050.784 | -999.000 | 13.062809 | 0.00868079 | -999.000 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:40:00 | 204050.78 | 204050.78 | 13.062809 | 26.16 | 13.85 | 0.00695989 | 10.67 | 7.94 | 0.00695989 | 35.10 | 0.00569938 | 15.77 | 19.4307 | 24.00 | 0.00726532 | 32.2325 | 146910.66 | 0.00 | 183004.39 | 183004.39 |
VAV_TOP WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoopHVAC | VAV_TOP WITH REHEAT | 41023.752 | 41023.752 | 3.918843 | 0.00035889 | 698.319 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 22:20:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 41023.75 | 41023.75 | 3.918843 | 2.28 | 0.68 | 0.00418036 | 12.80 | 9.86 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 64.7689 | 17.92 | 0.00753225 | 48.5303 | 46196.38 | 0.00 | 40882.53 | 40882.53 |
CAV_BAS COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | CAV_BAS | 107353.464 | -999.000 | 7.310008 | 0.00456706 | -999.000 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 12:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 107353.46 | 107353.46 | 7.310008 | 25.69 | 13.83 | 0.00713385 | 11.13 | 8.31 | 0.00713385 | 33.34 | 0.00569665 | 15.21 | 16.4180 | 24.00 | 0.00745223 | 33.0526 | 74707.51 | 0.00 | 96886.06 | 96886.06 |
CAV_BAS HEATING COIL | Coil:Heating:Water | AirLoopHVAC | CAV_BAS | 300438.840 | 300438.840 | 7.310008 | 0.00262837 | 6666.885 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 300438.84 | 300438.84 | 7.310008 | -1.30 | -3.96 | 0.00234317 | 40.00 | 18.92 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 16.4180 | 24.34 | 0.00234317 | 10.2661 | 0.00 | 0.00 | 250561.46 | 250561.46 |
AIRLOOP DATACENTER BASEMENT COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | 477837.931 | 253468.455 | 26.105415 | 0.01170222 | -999.000 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 07:10:00 | 407820.58 | 406728.49 | -999.0 | 28.79 | 14.78 | 0.00702451 | 12.80 | 8.87 | 0.00700000 | 35.10 | 0.00569938 | 15.77 | -999.0000 | 27.00 | 0.00704193 | 26.1548 | 373217.32 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BOT COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER BOT | 10848.527 | 5808.330 | 0.608508 | 0.00026568 | -999.000 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:50:00 | 9213.73 | 9165.42 | -999.0 | 28.24 | 14.62 | 0.00704698 | 12.80 | 8.87 | 0.00700000 | 30.51 | 0.00569229 | 14.27 | -999.0000 | 27.00 | 0.00708271 | 26.3026 | 8707.45 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER MID COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER MID | 104123.974 | 55735.079 | 5.837867 | 0.00254999 | -999.000 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:50:00 | 88440.51 | 87958.81 | -999.0 | 28.24 | 14.62 | 0.00704882 | 12.80 | 8.87 | 0.00700000 | 30.51 | 0.00569229 | 14.27 | -999.0000 | 27.00 | 0.00708617 | 26.3154 | 83513.78 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER TOP COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER TOP | 10621.042 | 5685.827 | 0.595610 | 0.00026011 | -999.000 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | 9020.91 | 8972.63 | -999.0 | 28.24 | 14.62 | 0.00704797 | 12.80 | 8.87 | 0.00700000 | 30.51 | 0.00569229 | 14.27 | -999.0000 | 27.00 | 0.00708451 | 26.3093 | 8525.10 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BASEMENT HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | 477837.931 | 477837.931 | 26.105415 | 0.01170222 | -999.000 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 477837.93 | 477837.93 | 26.105415 | -7.90 | -7.90 | 0.00234317 | 40.00 | 18.92 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 1.2963 | 27.00 | 0.00700000 | 25.9964 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BOT HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER BOT | 10848.527 | 10848.527 | 0.608508 | 0.00026568 | -999.000 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 10848.53 | 10848.53 | 0.608508 | -7.90 | -7.90 | 0.00234317 | 40.00 | 18.92 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 2.5690 | 26.48 | 0.00698102 | 26.7386 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER MID HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER MID | 104123.974 | 104123.974 | 5.837867 | 0.00254999 | -999.000 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 104123.97 | 104123.97 | 5.837867 | -7.90 | -7.90 | 0.00234317 | 40.00 | 18.92 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 2.6777 | 24.17 | 0.00334894 | 14.8005 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER TOP HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER TOP | 10621.042 | 10621.042 | 0.595610 | 0.00026011 | -999.000 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 10621.04 | 10621.04 | 0.595610 | -7.90 | -7.90 | 0.00234317 | 40.00 | 18.92 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 2.6246 | 23.09 | 0.00283521 | 13.3790 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | 16131.549 | 16131.549 | -999.0 | -999.0 | -999.000 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 16131.55 | 16131.55 | 26.105415 | -0.10 | -0.10 | 0.00693964 | 40.00 | 18.92 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 1.2963 | 27.00 | 0.00700000 | 25.9964 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BOT_SUPPHEATCOIL | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER BOT | 745.211 | 745.211 | -999.0 | -999.0 | -999.000 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 745.21 | 745.21 | 0.608508 | -0.20 | -0.20 | 0.00686188 | 40.00 | 18.92 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 2.5690 | 26.48 | 0.00698102 | 26.7386 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER MID_SUPPHEATCOIL | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER MID | 7452.107 | 7452.107 | -999.0 | -999.0 | -999.000 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 7452.11 | 7452.11 | 5.837867 | -0.21 | -1.89 | 0.00332201 | 40.00 | 18.92 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 2.6777 | 24.17 | 0.00334894 | 14.8005 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER TOP_SUPPHEATCOIL | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER TOP | 745.211 | 745.211 | -999.0 | -999.0 | -999.000 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 745.21 | 745.21 | 0.595610 | -0.21 | -2.63 | 0.00282230 | 40.00 | 18.92 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 2.6246 | 23.09 | 0.00283521 | 13.3790 | 0.00 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 08:43:29
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
CORE_BOTTOM VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | CORE_BOTTOM | N/A | N/A | N/A | Yes | Yes | Yes | No | 17116.646 | 17116.646 | 2.066869 | 0.00014974 | 345.058 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 19.05987824 | 54.44 | 82.22 | 27.78 | 2222734.32 | 0.7701 | 0.785570 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 06:20:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 06:20:00 | Sensible | 17116.65 | 17116.65 | 1.0000 | 2.04704529 | 2.066869 | 12.80 | 9.86 | 0.00800000 | 33059.8 | 40.00 | 18.92 | 0.00800000 | 60796.0 | 0.14972861 | 60.00 | 32.22 | 27.78 | 0.000 | 17116.65 | -7.90 | 0.00234317 | -7.90 | 0.00000000 | 0.0000 | 21.00 | 0.00800000 | 21.00 | 0.00800000 | 42.5367 | 0.00 | 0.00 | 17179.76 | 17179.76 | 2.04704529 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 21.03 | 14.86 | 0.00800000 | 41452.3 | |
CORE_MID VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | CORE_MID | N/A | N/A | N/A | Yes | Yes | Yes | No | 415860.086 | 415860.086 | 20.345554 | 0.00363813 | 9823.560 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 19.05987824 | 54.44 | 82.22 | 27.78 | 2222734.32 | 18.7094 | 19.085926 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 415860.09 | 415860.09 | 1.0000 | 20.15041787 | 20.345554 | 12.80 | 9.86 | 0.00800000 | 33059.8 | 40.00 | 18.92 | 0.00800000 | 60796.0 | 3.63775432 | 60.00 | 32.22 | 27.78 | 0.000 | 415860.09 | -7.90 | 0.00234317 | -7.90 | 0.00000000 | 0.0000 | 20.87 | 0.00800000 | 21.00 | 0.00800000 | 42.5367 | 247369.64 | 0.00 | 417219.33 | 417219.33 | 20.15041787 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 33.11 | 19.05 | 0.00800000 | 53765.1 | |
CORE_TOP VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | CORE_TOP | N/A | N/A | N/A | Yes | Yes | Yes | No | 80297.934 | 80297.934 | 2.906528 | 0.00070248 | 2119.499 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 19.05987824 | 54.44 | 82.22 | 27.78 | 2222734.32 | 3.6126 | 3.685279 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 80297.93 | 80297.93 | 1.0000 | 2.87865070 | 2.906528 | 12.80 | 9.86 | 0.00800000 | 33059.8 | 40.00 | 18.92 | 0.00800000 | 60796.0 | 0.70240969 | 60.00 | 32.22 | 27.78 | 0.000 | 80297.93 | -7.90 | 0.00234317 | -7.90 | 0.00000000 | 0.0000 | 20.91 | 0.00800000 | 21.00 | 0.00800000 | 42.5367 | 56227.71 | 0.00 | 80574.55 | 80574.55 | 2.87865070 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.25 | 21.26 | 0.00800000 | 61050.2 | |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | PERIMETER_BOT_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 11355.254 | 11355.254 | 0.411323 | 0.00009934 | 299.627 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 19.05987824 | 54.44 | 82.22 | 27.78 | 2222734.32 | 0.5109 | 0.521150 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 11355.25 | 11355.25 | 1.0000 | 0.40737768 | 0.411323 | 12.80 | 9.86 | 0.00800000 | 33059.8 | 40.00 | 18.92 | 0.00800000 | 60796.0 | 0.09933058 | 60.00 | 32.22 | 27.78 | 0.000 | 11355.25 | -7.90 | 0.00234317 | -7.90 | 0.00000000 | 0.0000 | 20.91 | 0.00753808 | 21.00 | 0.00753808 | 40.1136 | 7952.37 | 0.00 | 11393.65 | 11393.65 | 0.40737768 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.23 | 21.25 | 0.00800000 | 61028.1 | |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | PERIMETER_BOT_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 8410.038 | 8410.038 | 0.337994 | 0.00007357 | 212.383 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 19.05987824 | 54.44 | 82.22 | 27.78 | 2222734.32 | 0.3784 | 0.385979 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 8410.04 | 8410.04 | 1.0000 | 0.33475257 | 0.337994 | 12.80 | 9.86 | 0.00800000 | 33059.8 | 40.00 | 18.92 | 0.00800000 | 60796.0 | 0.07356718 | 60.00 | 32.22 | 27.78 | 0.000 | 8410.04 | -7.90 | 0.00234317 | -7.90 | 0.00000000 | 0.0000 | 20.91 | 0.00760470 | 21.00 | 0.00760470 | 40.4635 | 5613.42 | 0.00 | 8436.11 | 8436.11 | 0.33475257 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 37.51 | 20.44 | 0.00800000 | 58260.9 | |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | PERIMETER_BOT_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 13442.384 | 13442.384 | 0.487100 | 0.00011760 | 354.641 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 19.05987824 | 54.44 | 82.22 | 27.78 | 2222734.32 | 0.6048 | 0.616939 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 13442.38 | 13442.38 | 1.0000 | 0.48242834 | 0.487100 | 12.80 | 9.86 | 0.00800000 | 33059.8 | 40.00 | 18.92 | 0.00800000 | 60796.0 | 0.11758784 | 60.00 | 32.22 | 27.78 | 0.000 | 13442.38 | -7.90 | 0.00234317 | -7.90 | 0.00000000 | 0.0000 | 20.95 | 0.00767661 | 21.00 | 0.00767661 | 40.8410 | 9411.42 | 0.00 | 13487.42 | 13487.42 | 0.48242834 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.22 | 21.25 | 0.00800000 | 61017.2 | |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | PERIMETER_BOT_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 7498.376 | 7498.376 | 0.417410 | 0.00006560 | 171.060 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 19.05987824 | 54.44 | 82.22 | 27.78 | 2222734.32 | 0.3373 | 0.344138 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 7498.38 | 7498.38 | 1.0000 | 0.41340678 | 0.417410 | 12.80 | 9.86 | 0.00800000 | 33059.8 | 40.00 | 18.92 | 0.00800000 | 60796.0 | 0.06559238 | 60.00 | 32.22 | 27.78 | 0.000 | 7498.38 | -7.90 | 0.00234317 | -7.90 | 0.00000000 | 0.0000 | 20.91 | 0.00722236 | 21.00 | 0.00722236 | 38.4539 | 4047.32 | 0.00 | 7523.87 | 7523.87 | 0.41340678 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 30.65 | 18.25 | 0.00800000 | 51259.5 | |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | PERIMETER_MID_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 212844.560 | 212844.560 | 7.721031 | 0.00186206 | 5612.545 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 19.05987824 | 54.44 | 82.22 | 27.78 | 2222734.32 | 9.5758 | 9.768515 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 212844.56 | 212844.56 | 1.0000 | 7.64697788 | 7.721031 | 12.80 | 9.86 | 0.00800000 | 33059.8 | 40.00 | 18.92 | 0.00800000 | 60796.0 | 1.86186711 | 60.00 | 32.22 | 27.78 | 0.000 | 212844.56 | -7.90 | 0.00234317 | -7.90 | 0.00000000 | 0.0000 | 20.95 | 0.00765251 | 21.00 | 0.00765251 | 40.7154 | 148955.93 | 0.00 | 213537.63 | 213537.63 | 7.64697788 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.18 | 21.24 | 0.00800000 | 60984.3 | |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | PERIMETER_MID_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 141301.069 | 141301.069 | 5.126031 | 0.00123616 | 3725.909 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 19.05987824 | 54.44 | 82.22 | 27.78 | 2222734.32 | 6.3571 | 6.485022 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 141301.07 | 141301.07 | 1.0000 | 5.07686630 | 5.126031 | 12.80 | 9.86 | 0.00800000 | 33059.8 | 40.00 | 18.92 | 0.00800000 | 60796.0 | 1.23603729 | 60.00 | 32.22 | 27.78 | 0.000 | 141301.07 | -7.90 | 0.00234317 | -7.90 | 0.00000000 | 0.0000 | 20.95 | 0.00765220 | 21.00 | 0.00765220 | 40.7139 | 98885.26 | 0.00 | 141760.53 | 141760.53 | 5.07686630 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.18 | 21.24 | 0.00800000 | 60982.7 | |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | PERIMETER_MID_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 210517.741 | 210517.741 | 7.636483 | 0.00184170 | 5551.236 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 19.05987824 | 54.44 | 82.22 | 27.78 | 2222734.32 | 9.4711 | 9.661726 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 210517.74 | 210517.74 | 1.0000 | 7.56324082 | 7.636483 | 12.80 | 9.86 | 0.00800000 | 33059.8 | 40.00 | 18.92 | 0.00800000 | 60796.0 | 1.84151316 | 60.00 | 32.22 | 27.78 | 0.000 | 210517.74 | -7.90 | 0.00234317 | -7.90 | 0.00000000 | 0.0000 | 20.95 | 0.00764847 | 21.00 | 0.00764847 | 40.6942 | 147329.21 | 0.00 | 211203.58 | 211203.58 | 7.56324082 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.19 | 21.24 | 0.00800000 | 60984.8 | |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | PERIMETER_MID_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 134078.301 | 134078.301 | 4.863627 | 0.00117298 | 3535.581 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 19.05987824 | 54.44 | 82.22 | 27.78 | 2222734.32 | 6.0321 | 6.153533 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 134078.30 | 134078.30 | 1.0000 | 4.81697914 | 4.863627 | 12.80 | 9.86 | 0.00800000 | 33059.8 | 40.00 | 18.92 | 0.00800000 | 60796.0 | 1.17285581 | 60.00 | 32.22 | 27.78 | 0.000 | 134078.30 | -7.90 | 0.00234317 | -7.90 | 0.00000000 | 0.0000 | 20.95 | 0.00763239 | 21.00 | 0.00763239 | 40.6098 | 93835.40 | 0.00 | 134515.19 | 134515.19 | 4.81697914 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.19 | 21.24 | 0.00800000 | 60985.0 | |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | PERIMETER_TOP_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 26958.167 | 26958.167 | 0.978271 | 0.00023584 | 710.749 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 19.05987824 | 54.44 | 82.22 | 27.78 | 2222734.32 | 1.2128 | 1.237247 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 26958.17 | 26958.17 | 1.0000 | 0.96888814 | 0.978271 | 12.80 | 9.86 | 0.00800000 | 33059.8 | 40.00 | 18.92 | 0.00800000 | 60796.0 | 0.23581774 | 60.00 | 32.22 | 27.78 | 0.000 | 26958.17 | -7.90 | 0.00234317 | -7.90 | 0.00000000 | 0.0000 | 20.95 | 0.00766309 | 21.00 | 0.00766309 | 40.7717 | 18863.42 | 0.00 | 27045.11 | 27045.11 | 0.96888814 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.17 | 21.23 | 0.00800000 | 60973.4 | |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | PERIMETER_TOP_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 17794.282 | 17794.282 | 0.645750 | 0.00015567 | 469.137 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 19.05987824 | 54.44 | 82.22 | 27.78 | 2222734.32 | 0.8006 | 0.816670 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 17794.28 | 17794.28 | 1.0000 | 0.63955675 | 0.645750 | 12.80 | 9.86 | 0.00800000 | 33059.8 | 40.00 | 18.92 | 0.00800000 | 60796.0 | 0.15565626 | 60.00 | 32.22 | 27.78 | 0.000 | 17794.28 | -7.90 | 0.00234317 | -7.90 | 0.00000000 | 0.0000 | 20.95 | 0.00765998 | 21.00 | 0.00765998 | 40.7554 | 12451.05 | 0.00 | 17851.61 | 17851.61 | 0.63955675 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.17 | 21.23 | 0.00800000 | 60972.3 | |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | PERIMETER_TOP_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 26703.486 | 26703.486 | 0.969017 | 0.00023361 | 704.038 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 19.05987824 | 54.44 | 82.22 | 27.78 | 2222734.32 | 1.2014 | 1.225558 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 26703.49 | 26703.49 | 1.0000 | 0.95972302 | 0.969017 | 12.80 | 9.86 | 0.00800000 | 33059.8 | 40.00 | 18.92 | 0.00800000 | 60796.0 | 0.23358991 | 60.00 | 32.22 | 27.78 | 0.000 | 26703.49 | -7.90 | 0.00234317 | -7.90 | 0.00000000 | 0.0000 | 20.95 | 0.00766004 | 21.00 | 0.00766004 | 40.7556 | 18685.36 | 0.00 | 26789.63 | 26789.63 | 0.95972302 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.17 | 21.23 | 0.00800000 | 60973.8 | |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | PERIMETER_TOP_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 17222.620 | 17222.620 | 0.624984 | 0.00015067 | 454.072 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 19.05987824 | 54.44 | 82.22 | 27.78 | 2222734.32 | 0.7748 | 0.790433 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 17222.62 | 17222.62 | 1.0000 | 0.61898965 | 0.624984 | 12.80 | 9.86 | 0.00800000 | 33059.8 | 40.00 | 18.92 | 0.00800000 | 60796.0 | 0.15065562 | 60.00 | 32.22 | 27.78 | 0.000 | 17222.62 | -7.90 | 0.00234317 | -7.90 | 0.00000000 | 0.0000 | 20.95 | 0.00764936 | 21.00 | 0.00764936 | 40.6997 | 12051.33 | 0.00 | 17278.16 | 17278.16 | 0.61898965 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.17 | 21.23 | 0.00800000 | 60973.3 | |
VAV_BOT WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV_BOT WITH REHEAT | CORE_BOTTOM; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 197464.453 | -999.000 | 12.531175 | 0.00840059 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1017.7936 | 1004.8586 | 0.9904 | VAV_BOT WITH REHEAT FAN | Fan:VariableVolume | 12.531175 | 12.41098698 | 4197.9300 | 999.8980 | 101.38975759 | 12.27 | 6.67 | 5.60 | 2383511.79 | 8.2846 | 8.284601 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | Sensible | 197464.45 | 197464.45 | 1.0000 | 12.41098698 | 12.531175 | 26.30 | 13.90 | 0.00696823 | 44195.1 | 10.67 | 7.95 | 0.00696823 | 28284.6 | 8.39973736 | 6.67 | 12.27 | 5.60 | 26935.316 | 170529.14 | 35.10 | 0.00569938 | 15.77 | 2.53819000 | 20.2550 | 24.00 | 0.00730003 | 24.00 | 0.00730003 | 32.3850 | 138232.88 | 0.00 | 177309.01 | 177309.01 | 12.41098698 | 26.30 | 15.88 | 0.00696823 | 44195.1 | 12.26 | 10.29 | 0.00696823 | 29908.6 | |
VAV_BOT WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV_BOT WITH REHEAT | CORE_BOTTOM; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 53488.048 | 53488.048 | 3.759352 | 0.00046794 | 889.542 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | VAV_BOT WITH REHEAT FAN | Fan:VariableVolume | 12.531175 | 12.41098698 | 4197.9300 | 999.8980 | 19.05987824 | 54.44 | 82.22 | 27.78 | 2222734.32 | 2.4064 | 2.454838 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 53488.05 | 53488.05 | 1.0000 | 3.72329610 | 3.759352 | -1.50 | -2.61 | 0.00329874 | 6737.2 | 12.80 | 9.86 | 0.00800000 | 33059.8 | 0.46788905 | 60.00 | 32.22 | 27.78 | 0.000 | 53488.05 | -7.90 | 0.00234317 | -7.90 | 2.53819000 | 67.5167 | 11.81 | 0.00528488 | 21.26 | 0.00583735 | 30.6494 | 27024.53 | 0.00 | 50885.45 | 50885.45 | 3.72329610 | 2.80 | 0.95 | 0.00329874 | 11080.7 | 16.32 | 8.04 | 0.00329874 | 24747.4 | |
VAV_MID WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV_MID WITH REHEAT | CORE_MID; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 1874643.088 | -999.000 | 117.435292 | 0.07975165 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1017.7566 | 1004.8586 | 0.9904 | VAV_MID WITH REHEAT FAN | Fan:VariableVolume | 117.435292 | 116.30895719 | 4197.9300 | 999.8980 | 101.38975759 | 12.27 | 6.67 | 5.60 | 2383511.79 | 78.6505 | 78.650464 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | Sensible | 1874643.09 | 1874643.07 | 1.0000 | 116.30895719 | 117.435292 | 26.50 | 13.95 | 0.00694831 | 44352.1 | 10.67 | 7.93 | 0.00694831 | 28234.3 | 79.74351510 | 6.67 | 12.27 | 5.60 | 252422.998 | 1622220.09 | 35.10 | 0.00569938 | 15.77 | 25.38195000 | 21.6136 | 24.00 | 0.00731233 | 24.00 | 0.00731233 | 32.4387 | 1269697.76 | 0.00 | 1681868.91 | 1681868.91 | 116.30895719 | 26.50 | 15.94 | 0.00694831 | 44352.1 | 12.30 | 10.28 | 0.00694831 | 29891.8 | |
VAV_MID WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV_MID WITH REHEAT | CORE_MID; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 442531.844 | 442531.844 | 35.230587 | 0.00387146 | 7433.870 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | VAV_MID WITH REHEAT FAN | Fan:VariableVolume | 117.435292 | 116.30895719 | 4197.9300 | 999.8980 | 19.05987824 | 54.44 | 82.22 | 27.78 | 2222734.32 | 19.9093 | 20.310028 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 22:10:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 442531.84 | 442531.84 | 1.0000 | 34.89268716 | 35.230587 | 0.18 | -0.96 | 0.00383608 | 9774.6 | 12.80 | 9.86 | 0.00800000 | 33059.8 | 3.87106669 | 60.00 | 32.22 | 27.78 | 0.000 | 442531.84 | -7.90 | 0.00234317 | -7.90 | 25.38195000 | 72.0452 | 21.00 | 0.00768360 | 19.70 | 0.00760492 | 43.8327 | 393365.38 | 0.00 | 429642.22 | 429642.22 | 34.89268716 | 2.80 | 1.72 | 0.00383608 | 12427.3 | 14.97 | 8.03 | 0.00383608 | 24740.6 | |
VAV_TOP WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV_TOP WITH REHEAT | CORE_TOP; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 204050.784 | -999.000 | 13.062809 | 0.00868079 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1017.7781 | 1004.8586 | 0.9904 | VAV_TOP WITH REHEAT FAN | Fan:VariableVolume | 13.062809 | 12.93752179 | 4197.9300 | 999.8980 | 101.38975759 | 12.27 | 6.67 | 5.60 | 2383511.79 | 8.5609 | 8.560930 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:40:00 | Sensible | 204050.78 | 204050.78 | 1.0000 | 12.93752179 | 13.062809 | 26.16 | 13.85 | 0.00695989 | 44035.6 | 10.67 | 7.94 | 0.00695989 | 28263.5 | 8.67990651 | 6.67 | 12.27 | 5.60 | 28078.044 | 175972.74 | 35.10 | 0.00569938 | 15.77 | 2.53819000 | 19.4307 | 24.00 | 0.00726532 | 24.00 | 0.00726532 | 32.2325 | 146910.66 | 0.00 | 183004.39 | 183004.39 | 12.93752179 | 26.16 | 15.82 | 0.00695989 | 44035.6 | 12.27 | 10.28 | 0.00695989 | 29890.3 | |
VAV_TOP WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV_TOP WITH REHEAT | CORE_TOP; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 41023.752 | 41023.752 | 3.918843 | 0.00035889 | 698.319 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | VAV_TOP WITH REHEAT FAN | Fan:VariableVolume | 13.062809 | 12.93752179 | 4197.9300 | 999.8980 | 19.05987824 | 54.44 | 82.22 | 27.78 | 2222734.32 | 1.8456 | 1.882788 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 22:20:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 41023.75 | 41023.75 | 1.0000 | 3.88125654 | 3.918843 | 2.28 | 0.68 | 0.00418036 | 12765.0 | 12.80 | 9.86 | 0.00800000 | 33059.8 | 0.35885706 | 60.00 | 32.22 | 27.78 | 0.000 | 41023.75 | -7.90 | 0.00234317 | -7.90 | 2.53819000 | 64.7689 | 21.00 | 0.00755784 | 17.92 | 0.00753225 | 48.5303 | 46196.38 | 0.00 | 40882.53 | 40882.53 | 3.88125654 | 2.80 | 2.20 | 0.00418036 | 13290.1 | 13.20 | 7.59 | 0.00418036 | 23823.5 | |
CAV_BAS COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | CAV_BAS | BASEMENT | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 107353.464 | -999.000 | 7.310008 | 0.00456706 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1018.1015 | 1004.8586 | 0.9904 | CAV_BAS FAN | Fan:ConstantVolume | 7.310008 | 7.23989722 | 4197.9300 | 999.8980 | 101.38975759 | 12.27 | 6.67 | 5.60 | 2383511.79 | 4.5040 | 4.504004 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 12:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 12:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | Sensible | 107353.46 | 107353.46 | 1.0000 | 7.23989722 | 7.310008 | 25.69 | 13.83 | 0.00713385 | 44000.0 | 11.13 | 8.31 | 0.00713385 | 29172.0 | 4.56659862 | 6.67 | 12.27 | 5.60 | 12315.278 | 95038.19 | 33.34 | 0.00569665 | 15.21 | 1.20015641 | 16.4180 | 24.00 | 0.00745223 | 24.00 | 0.00745223 | 33.0526 | 74707.51 | 0.00 | 96886.06 | 96886.06 | 7.23989722 | 25.69 | 15.81 | 0.00713385 | 44000.0 | 12.55 | 10.59 | 0.00713385 | 30617.8 | |
CAV_BAS HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | CAV_BAS | BASEMENT | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 300438.840 | 300438.840 | 7.310008 | 0.00262837 | 6666.885 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | CAV_BAS FAN | Fan:ConstantVolume | 7.310008 | 7.23989722 | 4197.9300 | 999.8980 | 19.05987824 | 54.44 | 82.22 | 27.78 | 2222734.32 | 13.5166 | 13.788661 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 300438.84 | 300438.84 | 1.0000 | 7.23989722 | 7.310008 | -1.30 | -3.96 | 0.00234317 | 4551.2 | 40.00 | 18.92 | 0.00800000 | 60796.0 | 2.62810192 | 60.00 | 32.22 | 27.78 | 0.000 | 300438.84 | -7.90 | 0.00234317 | -7.90 | 1.20015641 | 16.4180 | 0.00 | 0.00234317 | 24.34 | 0.00234317 | 10.2661 | 0.00 | 0.00 | 250561.46 | 250561.46 | 7.23989722 | 12.80 | 5.14 | 0.00234317 | 18777.8 | 47.09 | 19.08 | 0.00234317 | 53386.3 | |
AIRLOOP DATACENTER BASEMENT COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | DATACENTER_BASEMENT_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 477837.931 | 253468.455 | 26.105415 | 0.01170222 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1017.8982 | 1004.8586 | 0.9904 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 07:10:00 | Sensible | 407820.58 | 406728.49 | 0.8535 | -999.0 | -999.0 | 28.79 | 14.78 | 0.00702451 | 46872.8 | 12.80 | 8.87 | 0.00700000 | 30535.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 407820.58 | 35.10 | 0.00569938 | 15.77 | 0.33839277 | -999.0000 | 27.00 | 0.00704193 | 27.00 | 0.00704193 | 26.1548 | 373217.32 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BOT COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BOT | DATACENTER_BOT_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 10848.527 | 5808.330 | 0.608508 | 0.00026568 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1017.9400 | 1004.8586 | 0.9904 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:50:00 | Sensible | 9213.73 | 9165.42 | 0.8493 | -999.0 | -999.0 | 28.24 | 14.62 | 0.00704698 | 46370.1 | 12.80 | 8.87 | 0.00700000 | 30535.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9213.73 | 30.51 | 0.00569229 | 14.27 | 0.01563234 | -999.0000 | 27.00 | 0.00708271 | 27.00 | 0.00708271 | 26.3026 | 8707.45 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER MID COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER MID | DATACENTER_MID_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 104123.974 | 55735.079 | 5.837867 | 0.00254999 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1017.9434 | 1004.8586 | 0.9904 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:50:00 | Sensible | 88440.51 | 87958.81 | 0.8494 | -999.0 | -999.0 | 28.24 | 14.62 | 0.00704882 | 46378.6 | 12.80 | 8.87 | 0.00700000 | 30535.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 88440.51 | 30.51 | 0.00569229 | 14.27 | 0.15632344 | -999.0000 | 27.00 | 0.00708617 | 27.00 | 0.00708617 | 26.3154 | 83513.78 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER TOP COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER TOP | DATACENTER_TOP_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 10621.042 | 5685.827 | 0.595610 | 0.00026011 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1017.9418 | 1004.8586 | 0.9904 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | Sensible | 9020.91 | 8972.63 | 0.8493 | -999.0 | -999.0 | 28.24 | 14.62 | 0.00704797 | 46374.5 | 12.80 | 8.87 | 0.00700000 | 30535.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9020.91 | 30.51 | 0.00569229 | 14.27 | 0.01563234 | -999.0000 | 27.00 | 0.00708451 | 27.00 | 0.00708451 | 26.3093 | 8525.10 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BASEMENT HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | DATACENTER_BASEMENT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 477837.931 | 477837.931 | 26.105415 | 0.01170222 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 0.9904 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 477837.93 | 477837.93 | 1.0000 | 25.85503566 | 26.105415 | -7.90 | -7.90 | 0.00234317 | -2112.5 | 40.00 | 18.92 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 477837.93 | -7.90 | 0.00234317 | -7.90 | 0.33839277 | 1.2963 | 0.00 | 0.00700000 | 27.00 | 0.00700000 | 25.9964 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BOT HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BOT | DATACENTER_BOT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 10848.527 | 10848.527 | 0.608508 | 0.00026568 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 0.9904 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 10848.53 | 10848.53 | 1.0000 | 0.60267202 | 0.608508 | -7.90 | -7.90 | 0.00234317 | -2112.5 | 40.00 | 18.92 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 10848.53 | -7.90 | 0.00234317 | -7.90 | 0.01563234 | 2.5690 | 0.00 | 0.00698102 | 26.48 | 0.00698102 | 26.7386 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER MID HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER MID | DATACENTER_MID_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 104123.974 | 104123.974 | 5.837867 | 0.00254999 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 0.9904 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 104123.97 | 104123.97 | 1.0000 | 5.78187494 | 5.837867 | -7.90 | -7.90 | 0.00234317 | -2112.5 | 40.00 | 18.92 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 104123.97 | -7.90 | 0.00234317 | -7.90 | 0.15632344 | 2.6777 | 0.00 | 0.00334894 | 24.17 | 0.00334894 | 14.8005 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER TOP HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER TOP | DATACENTER_TOP_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 10621.042 | 10621.042 | 0.595610 | 0.00026011 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 0.9904 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 10621.04 | 10621.04 | 1.0000 | 0.58989791 | 0.595610 | -7.90 | -7.90 | 0.00234317 | -2112.5 | 40.00 | 18.92 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 10621.04 | -7.90 | 0.00234317 | -7.90 | 0.01563234 | 2.6246 | 0.00 | 0.00283521 | 23.09 | 0.00283521 | 13.3790 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | DATACENTER_BASEMENT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 16131.549 | 16131.549 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | AIRLOOP DATACENTER BASEMENT SUPPLY FAN | Fan:OnOff | 26.105415 | 25.85503566 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 16131.55 | 16131.55 | 1.0000 | 25.85503566 | 26.105415 | -0.10 | -0.10 | 0.00693964 | 17251.4 | 40.00 | 18.92 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 16131.55 | -7.90 | 0.00234317 | -7.90 | 0.33839277 | 1.2963 | 0.00 | 0.00700000 | 27.00 | 0.00700000 | 25.9964 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BOT_SUPPHEATCOIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BOT | DATACENTER_BOT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 745.211 | 745.211 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | AIRLOOP DATACENTER BOT SUPPLY FAN | Fan:OnOff | 0.608508 | 0.60267202 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 745.21 | 745.21 | 1.0000 | 0.60267202 | 0.608508 | -0.20 | -0.20 | 0.00686188 | 16954.6 | 40.00 | 18.92 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 745.21 | -7.90 | 0.00234317 | -7.90 | 0.01563234 | 2.5690 | 0.00 | 0.00698102 | 26.48 | 0.00698102 | 26.7386 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER MID_SUPPHEATCOIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER MID | DATACENTER_MID_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 7452.107 | 7452.107 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | AIRLOOP DATACENTER MID SUPPLY FAN | Fan:OnOff | 5.837867 | 5.78187494 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 7452.11 | 7452.11 | 1.0000 | 5.78187494 | 5.837867 | -0.21 | -1.89 | 0.00332201 | 8094.3 | 40.00 | 18.92 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 7452.11 | -7.90 | 0.00234317 | -7.90 | 0.15632344 | 2.6777 | 0.00 | 0.00334894 | 24.17 | 0.00334894 | 14.8005 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER TOP_SUPPHEATCOIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER TOP | DATACENTER_TOP_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 745.211 | 745.211 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | AIRLOOP DATACENTER TOP SUPPLY FAN | Fan:OnOff | 0.595610 | 0.58989791 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 745.21 | 745.21 | 1.0000 | 0.58989791 | 0.595610 | -0.21 | -2.63 | 0.00282230 | 6849.0 | 40.00 | 18.92 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 745.21 | -7.90 | 0.00234317 | -7.90 | 0.01563234 | 2.6246 | 0.00 | 0.00283521 | 23.09 | 0.00283521 | 13.3790 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 08:43:29
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
VAV_BOT WITH REHEAT_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 12.53 | - | |||
VAV_MID WITH REHEAT_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 117.44 | - | |||
VAV_TOP WITH REHEAT_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 13.06 | - | |||
CAV_BAS_OA_CONTROLLER | DifferentialDryBulb | 1.20 | 7.31 | - | |||
AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER | DifferentialDryBulb | 0.34 | 26.11 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
CORE_BOTTOM | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_MID | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_TOP | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
BASEMENT | 2573.33 | 1067.00 | 225.00 |
CORE_BOTTOM | 2280.50 | 1204.67 | 213.33 |
CORE_MID | 1770.33 | 2983.00 | 250.00 |
CORE_TOP | 2108.83 | 3446.67 | 612.00 |
PERIMETER_BOT_ZN_3 | 2054.00 | 3219.00 | 279.50 |
PERIMETER_BOT_ZN_2 | 2551.33 | 2816.67 | 445.17 |
PERIMETER_BOT_ZN_1 | 3104.00 | 2153.50 | 503.50 |
PERIMETER_BOT_ZN_4 | 3083.17 | 2089.00 | 490.83 |
PERIMETER_MID_ZN_3 | 2853.83 | 3736.67 | 1296.83 |
PERIMETER_MID_ZN_2 | 2500.17 | 2871.00 | 955.17 |
PERIMETER_MID_ZN_1 | 3127.50 | 2516.50 | 774.67 |
PERIMETER_MID_ZN_4 | 2842.17 | 3305.83 | 955.17 |
PERIMETER_TOP_ZN_3 | 3413.17 | 3899.67 | 1945.67 |
PERIMETER_TOP_ZN_2 | 3297.50 | 3387.00 | 1447.50 |
PERIMETER_TOP_ZN_1 | 3294.50 | 2722.17 | 1026.33 |
PERIMETER_TOP_ZN_4 | 3225.33 | 3545.50 | 1474.17 |
DATACENTER_BOT_ZN_6 | 5943.00 | 982.83 | 982.83 |
DATACENTER_MID_ZN_6 | 5842.17 | 329.00 | 329.00 |
DATACENTER_TOP_ZN_6 | 5383.00 | 585.33 | 481.33 |
DATACENTER_BASEMENT_ZN_6 | 5943.00 | 5914.50 | 5914.50 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
Facility | 5943.00 | 5941.83 | 5927.00 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
BASEMENT | 0.00 | 70.67 | 0.00 | 2.33 |
CORE_BOTTOM | 0.00 | 5.33 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 1.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 20.83 | 0.00 | 15.83 |
PERIMETER_BOT_ZN_2 | 0.00 | 63.50 | 0.00 | 63.00 |
PERIMETER_BOT_ZN_1 | 0.00 | 237.83 | 0.00 | 233.67 |
PERIMETER_BOT_ZN_4 | 0.00 | 113.50 | 0.00 | 57.00 |
PERIMETER_MID_ZN_3 | 10.00 | 12.50 | 0.33 | 9.00 |
PERIMETER_MID_ZN_2 | 9.00 | 63.83 | 0.00 | 61.50 |
PERIMETER_MID_ZN_1 | 2.67 | 357.33 | 0.00 | 353.17 |
PERIMETER_MID_ZN_4 | 5.67 | 53.50 | 0.00 | 32.50 |
PERIMETER_TOP_ZN_3 | 61.50 | 21.17 | 7.33 | 15.33 |
PERIMETER_TOP_ZN_2 | 46.50 | 65.50 | 1.83 | 60.83 |
PERIMETER_TOP_ZN_1 | 28.83 | 187.33 | 0.17 | 180.83 |
PERIMETER_TOP_ZN_4 | 29.50 | 54.67 | 0.00 | 32.83 |
DATACENTER_BOT_ZN_6 | 0.00 | 36.33 | 0.00 | 27.50 |
DATACENTER_MID_ZN_6 | 0.00 | 16.50 | 0.00 | 10.17 |
DATACENTER_TOP_ZN_6 | 0.00 | 14.67 | 0.00 | 7.33 |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 388.33 | 0.00 | 345.50 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 69.00 | 1047.33 | 7.33 | 877.67 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 08:43:29
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 62.01 | 149.60 | 6779.02 | 1.661 | 0.000 | 0.000 | 0.000 |
CORE_BOTTOM | 55.69 | 134.35 | 6849.35 | 1.182 | 0.000 | 0.000 | 0.000 |
CORE_MID | 55.69 | 134.35 | 6849.35 | 0.897 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 55.69 | 134.35 | 6849.35 | 0.851 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 6.99 | 16.87 | 860.00 | 1.099 | 0.043 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 4.51 | 10.87 | 554.22 | 2.158 | 0.044 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 6.99 | 16.87 | 860.02 | 2.077 | 0.043 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 4.51 | 10.87 | 554.22 | 2.601 | 0.045 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 6.99 | 16.87 | 860.00 | 0.889 | 0.100 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 3.94 | 10.87 | 554.22 | 1.998 | 0.112 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 6.99 | 16.87 | 860.02 | 1.949 | 0.101 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 4.51 | 10.87 | 554.22 | 1.960 | 0.104 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 6.99 | 16.87 | 860.00 | 0.939 | 0.125 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 4.51 | 10.87 | 554.22 | 2.149 | 0.129 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 6.99 | 16.87 | 860.02 | 1.955 | 0.125 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 4.51 | 10.87 | 554.22 | 2.031 | 0.129 | 0.000 | 0.000 |
DATACENTER_BOT_ZN_6 | 0.81 | 1.95 | 99.34 | 0.424 | 0.000 | 0.000 | 0.000 |
DATACENTER_MID_ZN_6 | 0.81 | 1.95 | 99.34 | 0.424 | 0.000 | 0.000 | 0.000 |
DATACENTER_TOP_ZN_6 | 0.81 | 1.95 | 99.34 | 0.424 | 0.000 | 0.000 | 0.000 |
DATACENTER_BASEMENT_ZN_6 | 17.48 | 42.18 | 1911.37 | 31.944 | 0.000 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 62.01 | 149.60 | 6779.02 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_BOTTOM | 55.69 | 134.35 | 6849.35 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_MID | 55.69 | 134.35 | 6849.35 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 55.69 | 134.35 | 6849.35 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 6.99 | 16.87 | 860.00 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 4.51 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 6.99 | 16.87 | 860.02 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 4.51 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 6.99 | 16.87 | 860.00 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 3.94 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 6.99 | 16.87 | 860.02 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 4.51 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 6.99 | 16.87 | 860.00 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 4.51 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 6.99 | 16.87 | 860.02 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 4.51 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
DATACENTER_BOT_ZN_6 | 0.81 | 1.95 | 99.34 | 0.000 | 0.000 | 0.000 | 0.000 |
DATACENTER_MID_ZN_6 | 0.81 | 1.95 | 99.34 | 0.000 | 0.000 | 0.000 | 0.000 |
DATACENTER_TOP_ZN_6 | 0.81 | 1.95 | 99.34 | 0.000 | 0.000 | 0.000 | 0.000 |
DATACENTER_BASEMENT_ZN_6 | 17.48 | 42.18 | 1911.37 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 08:43:29
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
BASEMENT | CAV_BAS | 62.01 | 149.60 | 6779.02 | 2779.43 | 1.2002 | 1.200 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | 55.69 | 134.35 | 6849.35 | 2496.12 | 0.0000 | 1.078 |
CORE_MID | VAV_MID WITH REHEAT | 55.69 | 134.35 | 6849.35 | 2496.12 | 0.0000 | 10.778 |
CORE_TOP | VAV_TOP WITH REHEAT | 55.69 | 134.35 | 6849.35 | 2496.12 | 0.0000 | 1.078 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | 6.99 | 16.87 | 860.00 | 313.41 | 0.0000 | 0.135 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | 4.51 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | 6.99 | 16.87 | 860.02 | 313.42 | 0.0000 | 0.135 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | 4.51 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | 6.99 | 16.87 | 860.00 | 313.41 | 0.0000 | 1.353 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | 3.94 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.872 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | 6.99 | 16.87 | 860.02 | 313.42 | 0.0000 | 1.353 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | 4.51 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.872 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | 6.99 | 16.87 | 860.00 | 313.41 | 0.0000 | 0.135 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | 4.51 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | 6.99 | 16.87 | 860.02 | 313.42 | 0.0000 | 0.135 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | 4.51 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | 0.81 | 1.95 | 99.34 | 36.20 | 0.0156 | 0.016 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | 0.81 | 1.95 | 99.34 | 36.20 | 0.1563 | 0.156 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | 0.81 | 1.95 | 99.34 | 36.20 | 0.0156 | 0.016 |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | 17.48 | 42.18 | 1911.37 | 783.68 | 0.3384 | 0.338 |
Total Facility | 1027.73 | 2493.19 | 126016.35 | 46320.38 | 1.7261 | 158.471 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
BASEMENT | 70446337.61 | 0.00 | 70446337.61 | 0.00 | 70446337.61 | 37848132.68 | 3772.22 | 1149.09 | 3838.69 | 461.30 |
CORE_BOTTOM | 51132672.19 | 0.00 | 51132672.19 | 0.00 | 51132672.19 | 33990283.35 | 4476.80 | 31.13 | 4252.07 | 531.56 |
CORE_MID | 0.37E+09 | 0.00 | 0.37E+09 | 0.00 | 0.37E+09 | 0.34E+09 | 5491.61 | 34.84 | 3233.54 | 209.10 |
CORE_TOP | 35284626.07 | 0.00 | 35284626.07 | 0.00 | 35284626.07 | 33990283.35 | 5798.99 | 36.32 | 2924.69 | 313.58 |
PERIMETER_BOT_ZN_3 | 5991886.36 | 0.00 | 5991886.36 | 435989.32 | 6427875.67 | 4267819.30 | 4172.49 | 64.12 | 4523.40 | 531.56 |
PERIMETER_BOT_ZN_2 | 7577008.43 | 0.00 | 7577008.43 | 290659.35 | 7867667.77 | 2750345.05 | 3197.03 | 5.00 | 5557.97 | 531.56 |
PERIMETER_BOT_ZN_1 | 11041675.17 | 0.00 | 11041675.17 | 435989.32 | 11477664.49 | 4267912.63 | 3380.38 | 24.85 | 5354.78 | 531.56 |
PERIMETER_BOT_ZN_4 | 9186977.88 | 0.00 | 9186977.88 | 290659.35 | 9477637.23 | 2750345.05 | 3192.86 | 0.00 | 5567.14 | 531.56 |
PERIMETER_MID_ZN_3 | 46325666.23 | 0.00 | 46325666.23 | 1022509.09 | 47348175.31 | 42678193.03 | 4796.42 | 61.20 | 3902.38 | 209.10 |
PERIMETER_MID_ZN_2 | 71810920.27 | 0.00 | 71810920.27 | 681672.26 | 72492592.53 | 27503450.52 | 3624.23 | 2.86 | 5132.91 | 1118.10 |
PERIMETER_MID_ZN_1 | 0.10E+09 | 0.00 | 0.10E+09 | 1022509.09 | 0.10E+09 | 42679126.28 | 3808.57 | 11.85 | 4939.58 | 209.10 |
PERIMETER_MID_ZN_4 | 66076464.31 | 0.00 | 66076464.31 | 681672.26 | 66758136.57 | 27503450.52 | 3620.70 | 2.36 | 5136.93 | 209.10 |
PERIMETER_TOP_ZN_3 | 4898809.76 | 0.00 | 4898809.76 | 1269544.06 | 6168353.82 | 4267819.30 | 4101.29 | 47.89 | 4610.82 | 313.58 |
PERIMETER_TOP_ZN_2 | 7171938.60 | 0.00 | 7171938.60 | 846362.13 | 8018300.73 | 2750345.05 | 3771.38 | 3.59 | 4985.03 | 313.58 |
PERIMETER_TOP_ZN_1 | 10045661.63 | 0.00 | 10045661.63 | 1269544.06 | 11315205.69 | 4267912.63 | 3857.27 | 6.23 | 4896.50 | 313.58 |
PERIMETER_TOP_ZN_4 | 6841145.83 | 0.00 | 6841145.83 | 846362.13 | 7687507.95 | 2750345.05 | 3749.86 | 2.88 | 5007.26 | 313.58 |
DATACENTER_BOT_ZN_6 | 244296.02 | 0.00 | 244296.02 | 0.00 | 244296.02 | 492981.60 | 4419.00 | 4341.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 2442960.18 | 0.00 | 2442960.18 | 0.00 | 2442960.18 | 4929815.99 | 4419.00 | 4341.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 244296.02 | 0.00 | 244296.02 | 0.00 | 244296.02 | 492981.60 | 4419.00 | 4341.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.52E+09 | 0.00 | 0.52E+09 | 0.00 | 0.52E+09 | 10671554.30 | 138.04 | 581.82 | 8040.14 | 2781.79 |
Total Facility | 0.73E+10 | 0.00 | 0.73E+10 | 39768736.56 | 0.74E+10 | 0.50E+10 | 6427.78 | 4399.05 | 8626.76 | 3690.86 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
BASEMENT | 3.0794 | 0.0000 | 3.0794 | 0.0000 | 3.0794 | 1.2002 | 1263.72 | 1145.74 | 3533.54 |
CORE_BOTTOM | 2.2143 | 0.0000 | 2.2143 | 0.0000 | 2.2143 | 1.0778 | 2124.63 | 29.61 | 3788.76 |
CORE_MID | 16.8076 | 0.0000 | 16.8076 | 0.0000 | 16.8076 | 10.7782 | 2815.27 | 34.49 | 3093.24 |
CORE_TOP | 1.5959 | 0.0000 | 1.5959 | 0.0000 | 1.5959 | 1.0778 | 3096.61 | 36.12 | 2810.27 |
PERIMETER_BOT_ZN_3 | 0.2586 | 0.0000 | 0.2586 | 0.0101 | 0.2687 | 0.1353 | 1816.05 | 62.92 | 4064.03 |
PERIMETER_BOT_ZN_2 | 0.3275 | 0.0000 | 0.3275 | 0.0067 | 0.3342 | 0.0872 | 911.59 | 5.00 | 5026.41 |
PERIMETER_BOT_ZN_1 | 0.4891 | 0.0000 | 0.4891 | 0.0101 | 0.4992 | 0.1353 | 1056.97 | 20.71 | 4865.32 |
PERIMETER_BOT_ZN_4 | 0.3945 | 0.0000 | 0.3945 | 0.0067 | 0.4013 | 0.0872 | 907.42 | 0.00 | 5035.58 |
PERIMETER_MID_ZN_3 | 2.0957 | 0.0000 | 2.0957 | 0.0237 | 2.1194 | 1.3533 | 2127.46 | 60.06 | 3755.48 |
PERIMETER_MID_ZN_2 | 3.0341 | 0.0000 | 3.0341 | 0.0170 | 3.0511 | 0.8721 | 1013.53 | 1.80 | 4018.67 |
PERIMETER_MID_ZN_1 | 4.5889 | 0.0000 | 4.5889 | 0.0237 | 4.6126 | 1.3533 | 1135.27 | 11.78 | 4795.95 |
PERIMETER_MID_ZN_4 | 2.9787 | 0.0000 | 2.9787 | 0.0158 | 2.9946 | 0.8721 | 1012.78 | 1.83 | 4928.39 |
PERIMETER_TOP_ZN_3 | 0.2215 | 0.0000 | 0.2215 | 0.0295 | 0.2510 | 0.1353 | 1403.97 | 47.64 | 4491.39 |
PERIMETER_TOP_ZN_2 | 0.3263 | 0.0000 | 0.3263 | 0.0197 | 0.3460 | 0.0872 | 1101.05 | 2.32 | 4839.64 |
PERIMETER_TOP_ZN_1 | 0.4605 | 0.0000 | 0.4605 | 0.0295 | 0.4900 | 0.1353 | 1159.26 | 5.78 | 4777.96 |
PERIMETER_TOP_ZN_4 | 0.3088 | 0.0000 | 0.3088 | 0.0197 | 0.3285 | 0.0872 | 1089.28 | 1.36 | 4852.36 |
DATACENTER_BOT_ZN_6 | 0.0114 | 0.0000 | 0.0114 | 0.0000 | 0.0114 | 0.0156 | 1602.00 | 4341.00 | 0.00 |
DATACENTER_MID_ZN_6 | 0.1142 | 0.0000 | 0.1142 | 0.0000 | 0.1142 | 0.1563 | 1602.00 | 4341.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 0.0114 | 0.0000 | 0.0114 | 0.0000 | 0.0114 | 0.0156 | 1602.00 | 4341.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 16.5121 | 0.0000 | 16.5121 | 0.0000 | 16.5121 | 0.3384 | 102.83 | 581.82 | 5258.35 |
Total Facility | 322.4031 | 0.0000 | 322.4031 | 0.9354 | 323.3385 | 158.4706 | 3610.78 | 4382.83 | 5844.89 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
VAV_BOT WITH REHEAT | 83308899.84 | 0.00 | 83308899.84 | 48026705.38 | 3326.12 | 12.82 | 5421.06 | 531.56 |
VAV_MID WITH REHEAT | 0.64E+09 | 0.00 | 0.64E+09 | 0.48E+09 | 3810.91 | 8.41 | 4940.67 | 209.10 |
VAV_TOP WITH REHEAT | 63015788.70 | 0.00 | 63015788.70 | 48026705.38 | 3873.76 | 9.76 | 4876.48 | 313.50 |
CAV_BAS | 69101501.33 | 0.00 | 69101501.33 | 37848132.68 | 4921.25 | 5.75 | 3833.01 | 461.30 |
AIRLOOP DATACENTER BASEMENT | 0.51E+09 | 0.00 | 0.51E+09 | 10671554.30 | 719.86 | 0.00 | 8040.14 | 2781.79 |
AIRLOOP DATACENTER BOT | 239632.35 | 0.00 | 239632.35 | 492981.60 | 8760.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER MID | 2396323.53 | 0.00 | 2396323.53 | 4929815.99 | 8760.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER TOP | 239632.35 | 0.00 | 239632.35 | 492981.60 | 8760.00 | 0.00 | 0.00 | 0.00 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
VAV_BOT WITH REHEAT | 3.6136 | 0.0000 | 3.6136 | 1.5229 | 986.35 | 11.39 | 4945.26 |
VAV_MID WITH REHEAT | 29.1653 | 0.0000 | 29.1653 | 15.2292 | 1136.29 | 8.38 | 4798.33 |
VAV_TOP WITH REHEAT | 2.8574 | 0.0000 | 2.8574 | 1.5229 | 1171.98 | 9.41 | 4761.60 |
CAV_BAS | 3.0206 | 0.0000 | 3.0206 | 1.2002 | 2409.44 | 1.25 | 3532.31 |
AIRLOOP DATACENTER BASEMENT | 16.1969 | 0.0000 | 16.1969 | 0.3384 | 684.65 | 0.00 | 5258.35 |
AIRLOOP DATACENTER BOT | 0.0112 | 0.0000 | 0.0112 | 0.0156 | 5943.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER MID | 0.1120 | 0.0000 | 0.1120 | 0.1563 | 5943.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER TOP | 0.0112 | 0.0000 | 0.0112 | 0.0156 | 5943.00 | 0.00 | 0.00 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
VAV_BOT WITH REHEAT | 0.00 | 0.00 | 4364.21 | 0.00 | 0.00 | 0.00 | 1202.93 | 0.00 | 0.00 | 0.00 |
VAV_MID WITH REHEAT | 0.00 | 0.05 | 3691.47 | 0.00 | 0.00 | 0.00 | 1448.47 | 0.00 | 0.00 | 0.00 |
VAV_TOP WITH REHEAT | 0.00 | 0.02 | 3553.35 | 0.00 | 0.00 | 0.00 | 1717.77 | 0.00 | 0.00 | 0.00 |
CAV_BAS | 0.00 | 1144.42 | 4016.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER BASEMENT | 0.00 | 581.82 | 8040.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER BOT | 0.00 | 4341.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER MID | 0.00 | 4341.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER TOP | 0.00 | 4341.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
VAV_BOT WITH REHEAT | 0.0000 | 0.0000 | 5.0954 | 0.0000 | 0.0000 | 0.0000 | 1.6224 | 0.0000 | 0.0000 | 0.0000 |
VAV_MID WITH REHEAT | 0.0000 | 0.0000 | 42.8828 | 0.0000 | 0.0000 | 0.0000 | 16.5828 | 0.0000 | 0.0000 | 0.0000 |
VAV_TOP WITH REHEAT | 0.0000 | 0.0000 | 4.3739 | 0.0000 | 0.0000 | 0.0000 | 1.6392 | 0.0000 | 0.0000 | 0.0000 |
CAV_BAS | 0.0000 | 1.1777 | 4.6720 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
AIRLOOP DATACENTER BASEMENT | 0.0000 | 0.3324 | 18.2702 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
AIRLOOP DATACENTER BOT | 0.0000 | 0.0153 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
AIRLOOP DATACENTER MID | 0.0000 | 0.1534 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
AIRLOOP DATACENTER TOP | 0.0000 | 0.0153 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 08:43:29
Surfaces by ClassTotal | Outdoors | |
Wall | 98 | 30 |
Floor | 41 | 0 |
Roof | 30 | 1 |
Internal Mass | 16 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 24 | 24 |
Door | 12 | 12 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 8 |
Conditioned Zones | 23 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 3 |
Count | |
IDF Objects | 1395 |
Defaulted Fields | 1182 |
Fields with Defaults | 3867 |
Autosized Fields | 332 |
Autosizable Fields | 411 |
Autocalculated Fields | 226 |
Autocalculatable Fields | 473 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 08:43:29
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 30293.75 | 339408.13 | 29-MAY-05:00 | 2182343.09 | 21-AUG-15:10 |
Electricity:Building | 18593.88 | 225715.65 | 14-MAY-17:10 | 1164206.62 | 01-DEC-16:50 |
Electricity:Zone:BASEMENT | 687.24 | 14732.47 | 01-JAN-00:10 | 36407.88 | 02-JAN-08:10 |
Electricity:SpaceType:GENERAL | 18593.88 | 225715.65 | 14-MAY-17:10 | 1164206.62 | 01-DEC-16:50 |
InteriorLights:Electricity | 3917.48 | 18459.50 | 01-JAN-09:10 | 385834.94 | 09-NOV-16:50 |
InteriorLights:Electricity:Zone:BASEMENT | 262.84 | 1274.92 | 01-JAN-00:10 | 22950.34 | 02-JAN-08:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 3917.48 | 18459.50 | 01-JAN-09:10 | 385834.94 | 09-NOV-16:50 |
LightsWired:InteriorLights:Electricity | 3917.48 | 18459.50 | 01-JAN-09:10 | 385834.94 | 09-NOV-16:50 |
LightsWired:InteriorLights:Electricity:Zone:BASEMENT | 262.84 | 1274.92 | 01-JAN-00:10 | 22950.34 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 3917.48 | 18459.50 | 01-JAN-09:10 | 385834.94 | 09-NOV-16:50 |
Electricity:Zone:CORE_BOTTOM | 525.67 | 5598.20 | 01-JAN-00:10 | 37817.64 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_BOTTOM | 236.05 | 1144.97 | 01-JAN-00:10 | 20611.01 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_BOTTOM | 236.05 | 1144.97 | 01-JAN-00:10 | 20611.01 | 02-JAN-08:10 |
Electricity:Zone:CORE_MID | 5256.66 | 55981.88 | 01-JAN-00:10 | 378175.77 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_MID | 2360.53 | 11449.71 | 01-JAN-00:10 | 206110.14 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_MID | 2360.53 | 11449.71 | 01-JAN-00:10 | 206110.14 | 02-JAN-08:10 |
Electricity:Zone:CORE_TOP | 525.67 | 5598.19 | 01-JAN-00:10 | 37817.58 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_TOP | 236.05 | 1144.97 | 01-JAN-00:10 | 20611.01 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_TOP | 236.05 | 1144.97 | 01-JAN-00:10 | 20611.01 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_3 | 53.44 | 627.57 | 26-MAR-17:10 | 4748.47 | 04-JAN-17:00 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 17.08 | 68.40 | 01-JAN-09:10 | 2587.92 | 04-JAN-17:00 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 17.08 | 68.40 | 01-JAN-09:10 | 2587.92 | 04-JAN-17:00 |
Electricity:Zone:PERIMETER_BOT_ZN_2 | 34.40 | 404.43 | 09-APR-17:10 | 3060.10 | 04-JAN-17:00 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 10.96 | 44.08 | 01-JAN-07:40 | 1667.75 | 04-JAN-17:00 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 10.96 | 44.08 | 01-JAN-07:40 | 1667.75 | 04-JAN-17:00 |
Electricity:Zone:PERIMETER_BOT_ZN_1 | 53.22 | 627.58 | 12-MAR-17:10 | 4748.56 | 09-NOV-16:50 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 16.85 | 68.40 | 01-JAN-07:40 | 2587.98 | 09-NOV-16:50 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 16.85 | 68.40 | 01-JAN-07:40 | 2587.98 | 09-NOV-16:50 |
Electricity:Zone:PERIMETER_BOT_ZN_4 | 34.30 | 404.43 | 12-MAR-17:10 | 3060.09 | 09-NOV-16:50 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 10.86 | 44.08 | 01-JAN-09:10 | 1667.75 | 09-NOV-16:50 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 10.86 | 44.08 | 01-JAN-09:10 | 1667.75 | 09-NOV-16:50 |
Electricity:Zone:PERIMETER_MID_ZN_3 | 534.13 | 6275.73 | 26-MAR-17:10 | 47484.70 | 04-JAN-17:00 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 170.48 | 684.02 | 01-JAN-09:00 | 25879.19 | 04-JAN-17:00 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 170.48 | 684.02 | 01-JAN-09:00 | 25879.19 | 04-JAN-17:00 |
Electricity:Zone:PERIMETER_MID_ZN_2 | 343.85 | 4044.32 | 09-APR-17:10 | 30600.95 | 04-JAN-17:00 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 109.50 | 440.81 | 01-JAN-07:40 | 16677.53 | 04-JAN-17:00 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 109.50 | 440.81 | 01-JAN-07:40 | 16677.53 | 04-JAN-17:00 |
Electricity:Zone:PERIMETER_MID_ZN_1 | 532.06 | 6275.83 | 12-MAR-17:10 | 47485.60 | 09-NOV-16:50 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 168.40 | 684.04 | 01-JAN-07:40 | 25879.75 | 09-NOV-16:50 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 168.40 | 684.04 | 01-JAN-07:40 | 25879.75 | 09-NOV-16:50 |
Electricity:Zone:PERIMETER_MID_ZN_4 | 342.89 | 4044.30 | 12-MAR-17:10 | 30600.86 | 09-NOV-16:50 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 108.54 | 440.81 | 01-JAN-09:00 | 16677.53 | 09-NOV-16:50 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 108.54 | 440.81 | 01-JAN-09:00 | 16677.53 | 09-NOV-16:50 |
Electricity:Zone:PERIMETER_TOP_ZN_3 | 53.41 | 627.57 | 26-MAR-17:10 | 4748.47 | 04-JAN-17:00 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 17.05 | 68.40 | 01-JAN-09:00 | 2587.92 | 04-JAN-17:00 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 17.05 | 68.40 | 01-JAN-09:00 | 2587.92 | 04-JAN-17:00 |
Electricity:Zone:PERIMETER_TOP_ZN_2 | 34.38 | 404.43 | 09-APR-17:10 | 3060.10 | 04-JAN-17:00 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 10.95 | 44.08 | 01-JAN-07:40 | 1667.75 | 04-JAN-17:00 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 10.95 | 44.08 | 01-JAN-07:40 | 1667.75 | 04-JAN-17:00 |
Electricity:Zone:PERIMETER_TOP_ZN_1 | 53.21 | 627.58 | 12-MAR-17:10 | 4748.56 | 09-NOV-16:50 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 16.84 | 68.40 | 01-JAN-07:40 | 2587.98 | 09-NOV-16:50 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 16.84 | 68.40 | 01-JAN-07:40 | 2587.98 | 09-NOV-16:50 |
Electricity:Zone:PERIMETER_TOP_ZN_4 | 34.29 | 404.43 | 12-MAR-17:10 | 3060.09 | 09-NOV-16:50 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 10.85 | 44.08 | 01-JAN-09:00 | 1667.75 | 09-NOV-16:50 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 10.85 | 44.08 | 01-JAN-09:00 | 1667.75 | 09-NOV-16:50 |
Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 7568.97 | 95267.60 | 01-JAN-00:10 | 386103.53 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 74.11 | 359.47 | 01-JAN-00:10 | 6471.01 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 74.11 | 359.47 | 01-JAN-00:10 | 6471.01 | 02-JAN-08:10 |
Electricity:Zone:DATACENTER_BOT_ZN_6 | 160.51 | 1980.76 | 01-JAN-00:10 | 8373.14 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_BOT_ZN_6 | 6.63 | 32.15 | 01-JAN-00:10 | 578.72 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_BOT_ZN_6 | 6.63 | 32.15 | 01-JAN-00:10 | 578.72 | 02-JAN-08:10 |
Electricity:Zone:DATACENTER_MID_ZN_6 | 1605.09 | 19807.58 | 01-JAN-00:10 | 83731.41 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_MID_ZN_6 | 66.28 | 321.53 | 01-JAN-00:10 | 5787.18 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_MID_ZN_6 | 66.28 | 321.53 | 01-JAN-00:10 | 5787.18 | 02-JAN-08:10 |
Electricity:Zone:DATACENTER_TOP_ZN_6 | 160.51 | 1980.76 | 01-JAN-00:10 | 8373.14 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_TOP_ZN_6 | 6.63 | 32.15 | 01-JAN-00:10 | 578.72 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_TOP_ZN_6 | 6.63 | 32.15 | 01-JAN-00:10 | 578.72 | 02-JAN-08:10 |
InteriorEquipment:Electricity | 14676.40 | 207256.16 | 01-JAN-00:10 | 778371.69 | 03-APR-07:10 |
InteriorEquipment:Electricity:Zone:BASEMENT | 424.40 | 13457.54 | 01-JAN-00:10 | 13457.54 | 01-JAN-00:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 14676.40 | 207256.16 | 01-JAN-00:10 | 778371.69 | 03-APR-07:10 |
MiscPlug:InteriorEquipment:Electricity | 5334.97 | 88964.76 | 01-JAN-00:10 | 305206.10 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:BASEMENT | 424.40 | 13457.54 | 01-JAN-00:10 | 13457.54 | 01-JAN-00:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 5334.97 | 88964.76 | 01-JAN-00:10 | 305206.10 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 289.61 | 4453.23 | 01-JAN-00:10 | 17206.63 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 289.61 | 4453.23 | 01-JAN-00:10 | 17206.63 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_MID | 2896.13 | 44532.17 | 01-JAN-00:10 | 172065.63 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_MID | 2896.13 | 44532.17 | 01-JAN-00:10 | 172065.63 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_TOP | 289.61 | 4453.22 | 01-JAN-00:10 | 17206.56 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_TOP | 289.61 | 4453.22 | 01-JAN-00:10 | 17206.56 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 36.37 | 559.17 | 01-JAN-00:10 | 2160.55 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 36.37 | 559.17 | 01-JAN-00:10 | 2160.55 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.34 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.34 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 36.37 | 559.18 | 01-JAN-00:10 | 2160.58 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 36.37 | 559.18 | 01-JAN-00:10 | 2160.58 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.33 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.33 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 363.65 | 5591.71 | 01-JAN-00:10 | 21605.52 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 363.65 | 5591.71 | 01-JAN-00:10 | 21605.52 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 234.35 | 3603.51 | 01-JAN-00:10 | 13923.42 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 234.35 | 3603.51 | 01-JAN-00:10 | 13923.42 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 363.66 | 5591.79 | 01-JAN-00:10 | 21605.85 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 363.66 | 5591.79 | 01-JAN-00:10 | 21605.85 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 234.35 | 3603.49 | 01-JAN-00:10 | 13923.33 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 234.35 | 3603.49 | 01-JAN-00:10 | 13923.33 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 36.37 | 559.17 | 01-JAN-00:10 | 2160.55 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 36.37 | 559.17 | 01-JAN-00:10 | 2160.55 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.34 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.34 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 36.37 | 559.18 | 01-JAN-00:10 | 2160.58 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 36.37 | 559.18 | 01-JAN-00:10 | 2160.58 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.33 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.33 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 7494.86 | 94908.13 | 01-JAN-00:10 | 379632.52 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity | 9341.42 | 118291.40 | 01-JAN-00:10 | 473165.59 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 7494.86 | 94908.13 | 01-JAN-00:10 | 379632.52 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:SpaceType:GENERAL | 9341.42 | 118291.40 | 01-JAN-00:10 | 473165.59 | 31-MAR-23:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_BOT_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_BOT_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_MID_ZN_6 | 1538.81 | 19486.06 | 01-JAN-00:10 | 77944.22 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_MID_ZN_6 | 1538.81 | 19486.06 | 01-JAN-00:10 | 77944.22 | 31-MAR-23:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_TOP_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_TOP_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
Electricity:Plant | 2338.44 | 4039.08 | 17-JAN-03:40 | 425283.37 | 05-SEP-13:10 |
HeatRejection:Electricity | 771.48 | 213.78 | 17-JAN-07:50 | 84672.89 | 06-JUN-12:20 |
General:HeatRejection:Electricity | 771.48 | 213.78 | 17-JAN-07:50 | 84672.89 | 06-JUN-12:20 |
Electricity:HVAC | 6810.99 | 57832.04 | 25-MAY-04:50 | 625918.77 | 17-AUG-15:10 |
ExteriorEquipment:Electricity | 1934.78 | 28603.11 | 01-JAN-00:10 | 118525.16 | 16-FEB-08:20 |
Transformer:ExteriorEquipment:Electricity | 80.17 | 1421.04 | 01-JAN-00:10 | 5057.48 | 01-DEC-17:00 |
ElectricityPurchased:Facility | 30293.75 | 339408.13 | 29-MAY-05:00 | 2182343.09 | 21-AUG-15:10 |
ElectricityPurchased:Plant | 30293.75 | 339408.13 | 29-MAY-05:00 | 2182343.09 | 21-AUG-15:10 |
Cogeneration:ElectricityPurchased | 30293.75 | 339408.13 | 29-MAY-05:00 | 2182343.09 | 21-AUG-15:10 |
General:Cogeneration:ElectricityPurchased | 30293.75 | 339408.13 | 29-MAY-05:00 | 2182343.09 | 21-AUG-15:10 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 30293.75 | 339408.13 | 29-MAY-05:00 | 2182343.09 | 21-AUG-15:10 |
ElectricityNet:Plant | 30293.75 | 339408.13 | 29-MAY-05:00 | 2182343.09 | 21-AUG-15:10 |
Cogeneration:ElectricityNet | 30293.75 | 339408.13 | 29-MAY-05:00 | 2182343.09 | 21-AUG-15:10 |
General:Cogeneration:ElectricityNet | 30293.75 | 339408.13 | 29-MAY-05:00 | 2182343.09 | 21-AUG-15:10 |
Fans:Electricity | 3038.09 | 50761.54 | 02-JAN-05:40 | 337697.87 | 07-AUG-15:30 |
General:Fans:Electricity | 3038.09 | 50761.54 | 02-JAN-05:40 | 337697.87 | 07-AUG-15:30 |
ExteriorLights:Electricity | 695.82 | 0.00 | 01-JAN-07:20 | 57580.60 | 01-JAN-06:10 |
General:ExteriorLights:Electricity | 695.82 | 0.00 | 01-JAN-07:20 | 57580.60 | 01-JAN-06:10 |
ElevatorLift:ExteriorEquipment:Electricity | 1848.78 | 27144.47 | 01-JAN-00:10 | 113101.96 | 01-JAN-07:10 |
ElevatorLightsFan:ExteriorEquipment:Electricity | 5.83 | 37.60 | 01-JAN-00:10 | 376.00 | 01-JAN-07:10 |
Cooling:Electricity | 2625.05 | 2376.03 | 17-JAN-07:50 | 453863.97 | 01-AUG-15:10 |
General:Cooling:Electricity | 2625.05 | 2376.03 | 17-JAN-07:50 | 453863.97 | 01-AUG-15:10 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Humidifier:Electricity | 2169.44 | 0.00 | 21-MAY-01:30 | 100000.00 | 01-JAN-11:20 |
General:Humidifier:Electricity | 2169.44 | 0.00 | 21-MAY-01:30 | 100000.00 | 01-JAN-11:20 |
Boiler Parasitic:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Pumps:Electricity | 465.21 | 3769.13 | 01-JAN-00:10 | 61655.43 | 02-OCT-11:00 |
General:Pumps:Electricity | 465.21 | 3769.13 | 01-JAN-00:10 | 61655.43 | 02-OCT-11:00 |
WIRED_LTG_ELECTRICITY | 110.08 | 0.00 | 01-JAN-00:10 | 10841.96 | 09-NOV-17:00 |
WIRED_INT_EQUIP | 5334.97 | 88964.76 | 31-MAR-23:10 | 305206.10 | 03-APR-07:10 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 1474.01 | 8146.58 | 01-JAN-12:30 | 797672.86 | 06-FEB-07:10 |
NaturalGas:Plant | 1474.01 | 8146.58 | 01-JAN-12:30 | 797672.86 | 06-FEB-07:10 |
Heating:NaturalGas | 704.20 | 0.00 | 01-JAN-00:10 | 776734.29 | 17-JAN-07:10 |
Boiler:Heating:NaturalGas | 704.20 | 0.00 | 01-JAN-00:10 | 776734.29 | 17-JAN-07:10 |
WaterSystems:NaturalGas | 769.81 | 8146.58 | 01-JAN-12:30 | 84068.58 | 10-FEB-12:40 |
Water Heater:WaterSystems:NaturalGas | 769.81 | 8146.58 | 01-JAN-12:30 | 84068.58 | 10-FEB-12:40 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
PlantLoopCoolingDemand:Facility | 13593.32 | 7113.79 | 18-JAN-07:10 | 2580068.21 | 23-AUG-16:00 |
PlantLoopCoolingDemand:HVAC | 13593.32 | 7113.79 | 18-JAN-07:10 | 2580068.21 | 23-AUG-16:00 |
CoolingCoils:PlantLoopCoolingDemand | 13593.32 | 7113.79 | 18-JAN-07:10 | 2580068.21 | 23-AUG-16:00 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 10424.99 | 0.00 | 21-MAY-01:30 | 0.00 | 21-JUL-16:30 |
Water:HVAC | 807.03 | 0.00 | 21-MAY-01:30 | 0.00 | 01-JAN-13:00 |
Humidifier:Water | 807.03 | 0.00 | 21-MAY-01:30 | 0.00 | 01-JAN-13:00 |
General:Humidifier:Water | 807.03 | 0.00 | 21-MAY-01:30 | 0.00 | 01-JAN-13:00 |
MainsWater:Facility | 10424.99 | 0.00 | 21-MAY-01:30 | 0.00 | 21-JUL-16:30 |
MainsWater:HVAC | 807.03 | 0.00 | 21-MAY-01:30 | 0.00 | 01-JAN-13:00 |
Humidifier:MainsWater | 807.03 | 0.00 | 21-MAY-01:30 | 0.00 | 01-JAN-13:00 |
General:Humidifier:MainsWater | 807.03 | 0.00 | 21-MAY-01:30 | 0.00 | 01-JAN-13:00 |
Water:Plant | 9617.96 | 0.00 | 01-JAN-00:10 | 0.00 | 21-JUL-16:30 |
WaterSystems:Water | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterUse:WaterSystems:Water | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
MainsWater:Plant | 9617.96 | 0.00 | 01-JAN-00:10 | 0.00 | 21-JUL-16:30 |
WaterSystems:MainsWater | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterUse:WaterSystems:MainsWater | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water Heater:WaterSystems:Water | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:MainsWater | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
HeatRejection:Water | 7337.79 | 0.00 | 01-JAN-00:10 | 0.00 | 21-JUL-16:30 |
General:HeatRejection:Water | 7337.79 | 0.00 | 01-JAN-00:10 | 0.00 | 21-JUL-16:30 |
HeatRejection:MainsWater | 7337.79 | 0.00 | 01-JAN-00:10 | 0.00 | 21-JUL-16:30 |
General:HeatRejection:MainsWater | 7337.79 | 0.00 | 01-JAN-00:10 | 0.00 | 21-JUL-16:30 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 58816.54 | 100759.21 | 19-JAN-04:40 | 10118257.16 | 05-SEP-13:10 |
EnergyTransfer:Building | 21372.34 | 89178.23 | 29-JAN-05:50 | 1800091.30 | 14-AUG-15:20 |
EnergyTransfer:Zone:BASEMENT | 759.34 | 0.00 | 01-JAN-00:10 | 72377.21 | 02-OCT-05:10 |
Heating:EnergyTransfer | 198.51 | 0.00 | 01-JAN-17:30 | 503117.23 | 17-JAN-06:10 |
Heating:EnergyTransfer:Zone:BASEMENT | 3.64 | 0.00 | 01-JAN-00:10 | 23462.95 | 22-JUL-16:10 |
General:Heating:EnergyTransfer | 198.51 | 0.00 | 01-JAN-17:30 | 503117.23 | 17-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:BASEMENT | 3.64 | 0.00 | 01-JAN-00:10 | 23462.95 | 22-JUL-16:10 |
Cooling:EnergyTransfer | 21173.83 | 88215.85 | 22-JAN-08:10 | 1800091.30 | 14-AUG-15:20 |
Cooling:EnergyTransfer:Zone:BASEMENT | 755.70 | 0.00 | 01-JAN-00:10 | 72377.21 | 02-OCT-05:10 |
General:Cooling:EnergyTransfer | 21173.83 | 88215.85 | 22-JAN-08:10 | 1800091.30 | 14-AUG-15:20 |
General:Cooling:EnergyTransfer:Zone:BASEMENT | 755.70 | 0.00 | 01-JAN-00:10 | 72377.21 | 02-OCT-05:10 |
EnergyTransfer:Zone:CORE_BOTTOM | 697.46 | 0.00 | 01-JAN-00:10 | 57960.02 | 21-AUG-13:10 |
Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 697.46 | 0.00 | 01-JAN-00:10 | 57960.02 | 21-AUG-13:10 |
General:Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 697.46 | 0.00 | 01-JAN-00:10 | 57960.02 | 21-AUG-13:10 |
EnergyTransfer:Zone:CORE_MID | 5092.58 | 0.00 | 01-JAN-00:10 | 467081.96 | 05-SEP-13:10 |
Heating:EnergyTransfer:Zone:CORE_MID | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:CORE_MID | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:CORE_MID | 5092.58 | 0.00 | 01-JAN-00:10 | 467081.96 | 05-SEP-13:10 |
General:Cooling:EnergyTransfer:Zone:CORE_MID | 5092.58 | 0.00 | 01-JAN-00:10 | 467081.96 | 05-SEP-13:10 |
EnergyTransfer:Zone:CORE_TOP | 475.45 | 0.00 | 01-JAN-00:10 | 55830.80 | 28-JUN-14:00 |
Heating:EnergyTransfer:Zone:CORE_TOP | 3.17 | 0.00 | 01-JAN-00:10 | 54766.07 | 17-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:CORE_TOP | 3.17 | 0.00 | 01-JAN-00:10 | 54766.07 | 17-JAN-06:10 |
Cooling:EnergyTransfer:Zone:CORE_TOP | 472.27 | 0.00 | 01-JAN-00:10 | 55830.80 | 28-JUN-14:00 |
General:Cooling:EnergyTransfer:Zone:CORE_TOP | 472.27 | 0.00 | 01-JAN-00:10 | 55830.80 | 28-JUN-14:00 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 84.64 | 0.00 | 01-JAN-00:10 | 12521.38 | 31-JUL-12:30 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 0.03 | 0.00 | 01-JAN-00:10 | 2772.16 | 06-FEB-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 0.03 | 0.00 | 01-JAN-00:10 | 2772.16 | 06-FEB-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 84.61 | 0.00 | 01-JAN-00:10 | 12521.38 | 31-JUL-12:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 84.61 | 0.00 | 01-JAN-00:10 | 12521.38 | 31-JUL-12:30 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 98.82 | 0.00 | 01-JAN-00:10 | 17530.23 | 05-JUL-08:20 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 0.06 | 0.00 | 01-JAN-00:10 | 1947.03 | 06-FEB-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 0.06 | 0.00 | 01-JAN-00:10 | 1947.03 | 06-FEB-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 98.77 | 0.00 | 01-JAN-00:10 | 17530.23 | 05-JUL-08:20 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 98.77 | 0.00 | 01-JAN-00:10 | 17530.23 | 05-JUL-08:20 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 156.51 | 0.00 | 01-JAN-00:10 | 21972.47 | 31-OCT-13:10 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 0.10 | 0.00 | 01-JAN-00:10 | 4162.81 | 18-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 0.10 | 0.00 | 01-JAN-00:10 | 4162.81 | 18-JAN-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 156.41 | 0.00 | 01-JAN-00:10 | 21972.47 | 31-OCT-13:10 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 156.41 | 0.00 | 01-JAN-00:10 | 21972.47 | 31-OCT-13:10 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 132.35 | 0.00 | 01-JAN-00:10 | 22124.62 | 21-AUG-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 01-JAN-00:10 | 804.18 | 17-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 01-JAN-00:10 | 804.18 | 17-JAN-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 132.35 | 0.00 | 01-JAN-00:10 | 22124.62 | 21-AUG-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 132.35 | 0.00 | 01-JAN-00:10 | 22124.62 | 21-AUG-16:00 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 663.11 | 0.00 | 01-JAN-00:10 | 118475.39 | 29-JUN-15:00 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 40.90 | 0.00 | 01-JAN-00:10 | 113802.43 | 06-FEB-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 40.90 | 0.00 | 01-JAN-00:10 | 113802.43 | 06-FEB-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 622.21 | 0.00 | 01-JAN-00:10 | 118475.39 | 29-JUN-15:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 622.21 | 0.00 | 01-JAN-00:10 | 118475.39 | 29-JUN-15:00 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 926.57 | 0.00 | 01-JAN-00:10 | 187488.76 | 05-JUL-08:40 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 19.07 | 0.00 | 01-JAN-00:10 | 75676.35 | 17-JAN-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 19.07 | 0.00 | 01-JAN-00:10 | 75676.35 | 17-JAN-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 907.50 | 0.00 | 01-JAN-00:10 | 187488.76 | 05-JUL-08:40 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 907.50 | 0.00 | 01-JAN-00:10 | 187488.76 | 05-JUL-08:40 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 1458.26 | 0.00 | 01-JAN-00:10 | 236271.31 | 01-OCT-12:20 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 12.92 | 0.00 | 01-JAN-00:10 | 99162.14 | 17-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 12.92 | 0.00 | 01-JAN-00:10 | 99162.14 | 17-JAN-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 1445.35 | 0.00 | 01-JAN-00:10 | 236271.31 | 01-OCT-12:20 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 1445.35 | 0.00 | 01-JAN-00:10 | 236271.31 | 01-OCT-12:20 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 914.29 | 0.00 | 01-JAN-00:10 | 216172.75 | 04-JUL-17:00 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 13.69 | 0.00 | 01-JAN-00:10 | 66972.69 | 06-FEB-05:30 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 13.69 | 0.00 | 01-JAN-00:10 | 66972.69 | 06-FEB-05:30 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 900.60 | 0.00 | 01-JAN-00:10 | 216172.75 | 04-JUL-17:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 900.60 | 0.00 | 01-JAN-00:10 | 216172.75 | 04-JUL-17:00 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 75.45 | 0.00 | 01-JAN-00:10 | 16097.04 | 17-JAN-05:10 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 14.31 | 0.00 | 01-JAN-00:10 | 16097.04 | 17-JAN-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 14.31 | 0.00 | 01-JAN-00:10 | 16097.04 | 17-JAN-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 61.14 | 0.00 | 01-JAN-00:10 | 13109.47 | 29-JUN-15:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 61.14 | 0.00 | 01-JAN-00:10 | 13109.47 | 29-JUN-15:00 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 93.82 | 0.00 | 01-JAN-00:10 | 19007.04 | 05-JUL-08:40 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 6.38 | 0.00 | 01-JAN-00:10 | 13831.49 | 17-JAN-05:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 6.38 | 0.00 | 01-JAN-00:10 | 13831.49 | 17-JAN-05:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 87.43 | 0.00 | 01-JAN-00:10 | 19007.04 | 05-JUL-08:40 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 87.43 | 0.00 | 01-JAN-00:10 | 19007.04 | 05-JUL-08:40 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 144.55 | 0.00 | 01-JAN-00:10 | 24195.22 | 28-SEP-13:30 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 6.27 | 0.00 | 01-JAN-00:10 | 18641.96 | 17-JAN-05:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 6.27 | 0.00 | 01-JAN-00:10 | 18641.96 | 17-JAN-05:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 138.29 | 0.00 | 01-JAN-00:10 | 24195.22 | 28-SEP-13:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 138.29 | 0.00 | 01-JAN-00:10 | 24195.22 | 28-SEP-13:30 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 92.61 | 0.00 | 01-JAN-00:10 | 22854.94 | 04-JUL-17:00 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 5.07 | 0.00 | 01-JAN-00:10 | 12406.40 | 17-JAN-05:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 5.07 | 0.00 | 01-JAN-00:10 | 12406.40 | 17-JAN-05:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 87.54 | 0.00 | 01-JAN-00:10 | 22854.94 | 04-JUL-17:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 87.54 | 0.00 | 01-JAN-00:10 | 22854.94 | 04-JUL-17:00 |
EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 82.67 | 0.00 | 01-JAN-00:10 | 11361.72 | 21-AUG-07:10 |
Heating:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 1.48 | 0.00 | 01-JAN-00:10 | 3754.73 | 24-DEC-09:30 |
General:Heating:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 1.48 | 0.00 | 01-JAN-00:10 | 3754.73 | 24-DEC-09:30 |
Cooling:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 81.20 | 0.00 | 01-JAN-00:10 | 11361.72 | 21-AUG-07:10 |
General:Cooling:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 81.20 | 0.00 | 01-JAN-00:10 | 11361.72 | 21-AUG-07:10 |
EnergyTransfer:Zone:MIDFLOOR_PLENUM | 580.58 | 0.00 | 01-JAN-00:10 | 94060.63 | 05-JUL-15:00 |
Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 46.98 | 0.00 | 01-JAN-00:10 | 51181.06 | 23-JAN-14:30 |
General:Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 46.98 | 0.00 | 01-JAN-00:10 | 51181.06 | 23-JAN-14:30 |
Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 533.60 | 0.00 | 01-JAN-00:10 | 94060.63 | 05-JUL-15:00 |
General:Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 533.60 | 0.00 | 01-JAN-00:10 | 94060.63 | 05-JUL-15:00 |
EnergyTransfer:Zone:TOPFLOOR_PLENUM | 115.78 | 0.00 | 01-JAN-00:10 | 25568.18 | 28-JUN-13:40 |
Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 23.43 | 0.00 | 01-JAN-00:10 | 21055.86 | 17-JAN-05:20 |
General:Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 23.43 | 0.00 | 01-JAN-00:10 | 21055.86 | 17-JAN-05:20 |
Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 92.35 | 0.00 | 01-JAN-00:10 | 25568.18 | 28-JUN-13:40 |
General:Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 92.35 | 0.00 | 01-JAN-00:10 | 25568.18 | 28-JUN-13:40 |
EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 142.59 | 782.90 | 22-JAN-07:20 | 8627.72 | 16-APR-18:20 |
Heating:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 142.59 | 782.90 | 22-JAN-07:20 | 8627.72 | 16-APR-18:20 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 142.59 | 782.90 | 22-JAN-07:20 | 8627.72 | 16-APR-18:20 |
EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 1268.84 | 8.82 | 08-JAN-07:10 | 82294.35 | 16-APR-18:00 |
Heating:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 0.35 | 0.00 | 01-JAN-00:10 | 5694.53 | 17-JAN-04:20 |
General:Heating:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 0.35 | 0.00 | 01-JAN-00:10 | 5694.53 | 17-JAN-04:20 |
Cooling:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 1268.49 | 0.00 | 01-JAN-03:10 | 82294.35 | 16-APR-18:00 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 1268.49 | 0.00 | 01-JAN-03:10 | 82294.35 | 16-APR-18:00 |
EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 119.80 | 0.54 | 21-JAN-12:30 | 8219.79 | 16-APR-18:00 |
Heating:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 0.67 | 0.00 | 01-JAN-15:40 | 712.05 | 16-JAN-18:10 |
General:Heating:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 0.67 | 0.00 | 01-JAN-15:40 | 712.05 | 16-JAN-18:10 |
Cooling:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 119.13 | 0.00 | 01-JAN-00:10 | 8219.79 | 16-APR-18:00 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 119.13 | 0.00 | 01-JAN-00:10 | 8219.79 | 16-APR-18:00 |
EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 7196.27 | 87387.37 | 22-JAN-09:10 | 375360.06 | 18-AUG-21:20 |
Heating:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 7196.27 | 87387.37 | 22-JAN-09:10 | 375360.06 | 18-AUG-21:20 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 7196.27 | 87387.37 | 22-JAN-09:10 | 375360.06 | 18-AUG-21:20 |
PlantLoopHeatingDemand:Facility | 916.71 | 0.00 | 01-JAN-00:10 | 690420.67 | 17-JAN-07:10 |
PlantLoopHeatingDemand:Plant | 400.28 | 0.00 | 01-JAN-00:10 | 50680.16 | 10-FEB-12:50 |
WaterSystems:PlantLoopHeatingDemand | 400.28 | 0.00 | 01-JAN-00:10 | 50680.16 | 10-FEB-12:50 |
General:WaterSystems:PlantLoopHeatingDemand | 400.28 | 0.00 | 01-JAN-00:10 | 50680.16 | 10-FEB-12:50 |
EnergyTransfer:HVAC | 12586.46 | 6536.34 | 17-JAN-03:40 | 2406600.99 | 23-AUG-16:00 |
HeatingCoils:EnergyTransfer | 516.44 | 0.00 | 01-JAN-00:10 | 673730.46 | 17-JAN-07:10 |
PlantLoopHeatingDemand:HVAC | 516.44 | 0.00 | 01-JAN-00:10 | 673730.46 | 17-JAN-07:10 |
HeatingCoils:PlantLoopHeatingDemand | 516.44 | 0.00 | 01-JAN-00:10 | 673730.46 | 17-JAN-07:10 |
CoolingCoils:EnergyTransfer | 12070.02 | 4591.44 | 18-JAN-07:10 | 2406600.99 | 23-AUG-16:00 |
EnergyTransfer:Plant | 24857.74 | 0.00 | 01-JAN-00:10 | 6555435.41 | 05-SEP-13:10 |
LoopToLoop:EnergyTransfer | 7615.65 | 0.00 | 01-JAN-00:10 | 2077607.06 | 05-SEP-13:10 |
WaterSystems:EnergyTransfer | 400.28 | 0.00 | 01-JAN-00:10 | 50680.16 | 10-FEB-12:50 |
WaterUse:WaterSystems:EnergyTransfer | 400.28 | 0.00 | 01-JAN-00:10 | 50680.16 | 10-FEB-12:50 |
Boilers:EnergyTransfer | 511.79 | 0.00 | 01-JAN-00:10 | 647269.03 | 17-JAN-07:10 |
Chillers:EnergyTransfer | 7614.13 | 0.00 | 01-JAN-00:10 | 2084113.53 | 05-SEP-13:10 |
HeatRejection:EnergyTransfer | 8715.89 | 0.00 | 01-JAN-00:10 | 2370814.63 | 05-SEP-13:10 |
General:HeatRejection:EnergyTransfer | 8715.89 | 0.00 | 01-JAN-00:10 | 2370814.63 | 05-SEP-13:10 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 08:43:29
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
BASEMENT | 0.000 | 0.000 | 3.638 | -755.694 | 0.000 | 0.000 | 92.677 | 262.844 | 424.397 | 0.000 | 0.000 | 0.000 | 0.003 | 0.000 | 0.000 | 0.000 | 0.000 | -27.862 |
CORE_BOTTOM | 0.000 | 0.000 | 0.000 | -697.458 | 0.000 | 0.000 | 83.422 | 236.053 | 289.614 | 0.000 | 0.000 | 0.000 | 88.369 | 0.000 | 0.000 | 0.000 | 0.000 | -0.005 |
CORE_MID | 0.000 | 0.000 | 0.000 | -5092.540 | 0.000 | 0.000 | 838.525 | 2360.527 | 2896.128 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -1002.640 |
CORE_TOP | 0.000 | 0.000 | 3.175 | -472.267 | 0.000 | 0.000 | 85.715 | 236.053 | 289.613 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -142.289 |
PERIMETER_BOT_ZN_3 | 0.000 | 0.000 | 0.028 | -84.607 | 0.000 | 0.000 | 10.705 | 17.077 | 36.365 | 42.246 | 0.000 | 0.184 | 47.316 | 0.000 | -64.498 | 0.000 | -4.817 | 0.000 |
PERIMETER_BOT_ZN_2 | 0.000 | 0.000 | 0.058 | -98.765 | 0.000 | 0.000 | 6.902 | 10.963 | 23.435 | 102.226 | 0.000 | 0.132 | 0.001 | 0.000 | -39.257 | 0.000 | -3.175 | -2.519 |
PERIMETER_BOT_ZN_1 | 0.000 | 0.000 | 0.095 | -156.410 | 0.000 | 0.000 | 10.526 | 16.854 | 36.366 | 182.677 | 0.000 | 0.185 | 0.003 | 0.000 | -60.601 | 0.000 | -4.975 | -24.719 |
PERIMETER_BOT_ZN_4 | 0.000 | 0.000 | 0.001 | -132.347 | 0.000 | 0.000 | 6.847 | 10.864 | 23.435 | 93.135 | 0.000 | 0.116 | 47.832 | 0.000 | -46.343 | 0.000 | -3.540 | 0.000 |
PERIMETER_MID_ZN_3 | 0.000 | 0.000 | 40.901 | -622.197 | 0.000 | 0.000 | 111.300 | 170.475 | 363.654 | 437.405 | 0.000 | 4.236 | 182.691 | 0.000 | -587.441 | 0.000 | -101.024 | 0.000 |
PERIMETER_MID_ZN_2 | 0.000 | 0.000 | 19.068 | -907.494 | 0.000 | 0.000 | 51.906 | 109.499 | 234.352 | 1021.317 | 0.000 | 2.892 | 0.002 | 0.000 | -372.092 | 0.000 | -69.952 | -89.496 |
PERIMETER_MID_ZN_1 | 0.000 | 0.000 | 12.916 | -1445.318 | 0.000 | 0.000 | 105.656 | 168.398 | 363.660 | 1818.159 | 0.000 | 4.156 | 0.023 | 0.000 | -590.566 | 0.000 | -112.397 | -324.662 |
PERIMETER_MID_ZN_4 | 0.000 | 0.000 | 13.689 | -900.571 | 0.000 | 0.000 | 71.647 | 108.540 | 234.351 | 946.367 | 0.000 | 2.733 | 6.025 | 0.000 | -410.272 | 0.000 | -72.509 | -0.009 |
PERIMETER_TOP_ZN_3 | 0.000 | 0.000 | 14.312 | -61.138 | 0.000 | 0.000 | 11.307 | 17.046 | 36.365 | 44.276 | 0.000 | 0.504 | 4.454 | 0.000 | -55.373 | 0.000 | -11.753 | -0.001 |
PERIMETER_TOP_ZN_2 | 0.000 | 0.000 | 6.383 | -87.433 | 0.000 | 0.000 | 7.112 | 10.949 | 23.435 | 102.459 | 0.000 | 0.341 | 0.003 | 0.000 | -35.437 | 0.000 | -8.230 | -19.579 |
PERIMETER_TOP_ZN_1 | 0.000 | 0.000 | 6.266 | -138.283 | 0.000 | 0.000 | 10.737 | 16.839 | 36.366 | 182.351 | 0.000 | 0.497 | 0.002 | 0.000 | -56.102 | 0.000 | -13.183 | -45.488 |
PERIMETER_TOP_ZN_4 | 0.000 | 0.000 | 5.070 | -87.540 | 0.000 | 0.000 | 7.241 | 10.854 | 23.435 | 94.719 | 0.000 | 0.329 | 0.001 | 0.000 | -39.177 | 0.000 | -8.552 | -6.379 |
DATACENTER_BOT_ZN_6 | 0.000 | 0.000 | 0.000 | -142.589 | 0.000 | 0.000 | 0.950 | 6.628 | 153.881 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -18.869 |
DATACENTER_MID_ZN_6 | 0.000 | 0.000 | 0.348 | -1268.488 | 0.000 | 0.000 | 9.499 | 66.280 | 1538.806 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -346.444 |
DATACENTER_TOP_ZN_6 | 0.000 | 0.000 | 0.675 | -119.128 | 0.000 | 0.000 | 0.951 | 6.628 | 153.881 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -43.005 |
DATACENTER_BASEMENT_ZN_6 | 0.000 | 0.000 | 0.000 | -7196.275 | 0.000 | 0.000 | 20.118 | 74.111 | 7494.857 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -392.811 |
GROUNDFLOOR_PLENUM | 1.476 | -81.198 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.340 | 89.864 | 0.000 | 0.000 | 0.000 | -10.483 | 0.000 |
MIDFLOOR_PLENUM | 46.981 | -533.599 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 6.229 | 660.065 | 0.000 | 0.000 | 0.000 | -179.675 | -0.002 |
TOPFLOOR_PLENUM | 23.429 | -92.346 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.533 | 87.412 | 0.000 | 0.000 | 0.000 | -19.028 | -0.004 |
Total Facility | 71.886 | -707.143 | 126.623 | -20466.543 | 0.000 | 0.000 | 1543.743 | 3917.482 | 14676.396 | 5067.335 | 0.000 | 23.407 | 1214.066 | 0.000 | -2357.159 | 0.000 | -623.293 | -2486.783 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | 21-FEB-05:11 | 0.00 | 0.00 | 0.00 | -122127.92 | 0.00 | 0.00 | 0.00 | 2550.13 | 13457.54 | 0.00 | 0.00 | 0.00 | 106120.25 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 02-OCT-04:13 | 0.00 | 0.00 | 0.00 | -101520.80 | 0.00 | 0.00 | 0.00 | 2290.20 | 5937.65 | 0.00 | 0.00 | 0.00 | 93292.95 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 05-SEP-04:12 | 0.00 | 0.00 | 0.00 | -889083.04 | 0.00 | 0.00 | 0.00 | 22901.98 | 59376.23 | 0.00 | 0.00 | 0.00 | 806804.83 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 05-JUL-04:13 | 0.00 | 0.00 | 0.00 | -96049.95 | 0.00 | 0.00 | 0.00 | 2290.20 | 5937.62 | 0.00 | 0.00 | 0.00 | 87822.13 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 18-JUN-18:11 | 0.00 | 0.00 | 0.00 | -19721.75 | 0.00 | 0.00 | 0.00 | 68.40 | 559.17 | 8609.61 | 0.00 | 104.76 | 10379.81 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 18-JUN-08:11 | 0.00 | 0.00 | 0.00 | -29237.27 | 0.00 | 0.00 | 15.59 | 44.08 | 464.11 | 23929.23 | 0.00 | 0.00 | 4851.80 | 0.00 | -0.00 | 0.00 | -67.53 | 0.00 |
PERIMETER_BOT_ZN_1 | 01-OCT-12:01 | 0.00 | 0.00 | 0.00 | -30094.17 | 0.00 | 0.00 | 24.95 | 68.40 | 720.19 | 32516.71 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -40.21 | -3195.88 |
PERIMETER_BOT_ZN_4 | 25-JUN-16:21 | 0.00 | 0.00 | 0.00 | -37369.10 | 0.00 | 0.00 | 10.80 | 44.08 | 464.11 | 25368.34 | 0.00 | 67.17 | 11414.60 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 04-JUL-18:12 | 0.00 | 0.00 | 0.00 | -193018.95 | 0.00 | 0.00 | 0.00 | 684.02 | 5591.71 | 81643.02 | 0.00 | 5261.66 | 99838.54 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 04-JUL-08:51 | 0.00 | 0.00 | 0.00 | -327545.73 | 0.00 | 0.00 | 128.17 | 440.81 | 4641.14 | 220328.05 | 0.00 | 0.00 | 102986.91 | 0.00 | -0.00 | 0.00 | -979.35 | 0.00 |
PERIMETER_MID_ZN_1 | 01-OCT-12:51 | 0.00 | 0.00 | 0.00 | -305743.75 | 0.00 | 0.00 | 213.68 | 684.04 | 7201.95 | 301137.97 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -826.43 | -2667.46 |
PERIMETER_MID_ZN_4 | 04-JUL-16:51 | 0.00 | 0.00 | 0.00 | -363134.20 | 0.00 | 0.00 | 85.11 | 440.81 | 4641.11 | 253070.96 | 0.00 | 3313.02 | 101583.19 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 04-JUL-16:51 | 0.00 | 0.00 | 0.00 | -22415.88 | 0.00 | 0.00 | 36.12 | 68.40 | 720.18 | 6457.81 | 0.00 | 1087.15 | 14046.21 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 04-JUL-08:51 | 0.00 | 0.00 | 0.00 | -33173.89 | 0.00 | 0.00 | 12.66 | 44.08 | 464.11 | 21984.21 | 0.00 | 0.00 | 10794.43 | 0.00 | -0.00 | 0.00 | -125.61 | 0.00 |
PERIMETER_TOP_ZN_1 | 09-OCT-13:21 | 0.00 | 0.00 | 0.00 | -32061.16 | 0.00 | 0.00 | 25.10 | 68.40 | 720.19 | 28600.71 | 0.00 | 0.00 | 2940.50 | 0.00 | -0.00 | 0.00 | -293.75 | 0.00 |
PERIMETER_TOP_ZN_4 | 04-JUL-16:51 | 0.00 | 0.00 | 0.00 | -39124.18 | 0.00 | 0.00 | 6.98 | 44.08 | 464.11 | 25174.81 | 0.00 | 373.75 | 13060.45 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 16-APR-18:20 | 0.00 | 0.00 | 0.00 | -8637.07 | 0.00 | 0.00 | 0.00 | 32.15 | 7794.42 | 0.00 | 0.00 | 0.00 | 810.50 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 16-APR-18:00 | 0.00 | 0.00 | 0.00 | -82326.60 | 0.00 | 0.00 | 0.00 | 321.53 | 77944.22 | 0.00 | 0.00 | 0.00 | 4060.85 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 16-APR-17:53 | 0.00 | 0.00 | 0.00 | -8219.79 | 0.00 | 0.00 | 0.00 | 32.15 | 7794.42 | 0.00 | 0.00 | 0.00 | 393.21 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 04-AUG-20:03 | 0.00 | 0.00 | 0.00 | -379463.39 | 0.00 | 0.00 | 174.03 | 1437.98 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -1781.13 |
GROUNDFLOOR_PLENUM | 21-AUG-05:10 | 0.00 | -12326.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12426.40 | 0.00 | -0.00 | 0.00 | -99.95 | 0.00 |
MIDFLOOR_PLENUM | 17-JAN-04:01 | 0.00 | -117150.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 165764.30 | 0.00 | -0.00 | 0.00 | -48614.14 | 0.00 |
TOPFLOOR_PLENUM | 28-JUN-13:40 | 0.00 | -25562.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 208.36 | 25354.31 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 21-AUG-04:12 | 0.00 | 44138.11 | 0.00 | -2179039.53 | 0.00 | 0.00 | 0.00 | 42872.09 | 587299.42 | 0.00 | 0.00 | 0.00 | 1594110.29 | 0.00 | -60320.84 | 0.00 | -29059.53 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | 22-JUL-16:01 | 0.00 | 0.00 | 24883.63 | 0.00 | 0.00 | 0.00 | 520.13 | 1274.92 | 13457.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -40136.23 |
CORE_BOTTOM | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 26-DEC-04:11 | 0.00 | 0.00 | 79482.62 | 0.00 | 0.00 | 0.00 | 0.00 | 1144.97 | 5937.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -86565.21 |
PERIMETER_BOT_ZN_3 | 17-JAN-06:01 | 0.00 | 0.00 | 10837.08 | 0.00 | 0.00 | 0.00 | 146.09 | 287.56 | 960.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -5766.60 | 0.00 | -298.52 | -6165.85 |
PERIMETER_BOT_ZN_2 | 17-JAN-06:01 | 0.00 | 0.00 | 8076.93 | 0.00 | 0.00 | 0.00 | 94.15 | 185.31 | 618.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3836.45 | 0.00 | -199.43 | -4939.34 |
PERIMETER_BOT_ZN_1 | 06-FEB-05:01 | 0.00 | 0.00 | 13434.03 | 0.00 | 0.00 | 0.00 | 0.00 | 287.56 | 745.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -5847.67 | 0.00 | -1090.06 | -7529.43 |
PERIMETER_BOT_ZN_4 | 17-JAN-06:01 | 0.00 | 0.00 | 5641.54 | 0.00 | 0.00 | 0.00 | 94.15 | 185.31 | 618.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3784.03 | 0.00 | -199.16 | -2556.62 |
PERIMETER_MID_ZN_3 | 17-JAN-04:01 | 0.00 | 0.00 | 155841.62 | 0.00 | 0.00 | 0.00 | 0.00 | 1437.63 | 7455.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -47682.05 | 0.00 | -25582.94 | -91469.87 |
PERIMETER_MID_ZN_2 | 17-JAN-04:01 | 0.00 | 0.00 | 172063.15 | 0.00 | 0.00 | 0.00 | 0.00 | 926.46 | 4804.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -31947.58 | 0.00 | -17508.63 | -128338.07 |
PERIMETER_MID_ZN_1 | 17-JAN-04:01 | 0.00 | 0.00 | 190431.68 | 0.00 | 0.00 | 0.00 | 0.00 | 1437.66 | 7455.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -48462.86 | 0.00 | -27163.67 | -123698.52 |
PERIMETER_MID_ZN_4 | 17-JAN-04:01 | 0.00 | 0.00 | 164358.46 | 0.00 | 0.00 | 0.00 | 0.00 | 926.46 | 4804.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -31943.52 | 0.00 | -18141.74 | -120004.30 |
PERIMETER_TOP_ZN_3 | 17-JAN-03:42 | 0.00 | 0.00 | 18794.23 | 0.00 | 0.00 | 0.00 | 0.00 | 143.76 | 745.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -4277.89 | 0.00 | -2991.73 | -12413.93 |
PERIMETER_TOP_ZN_2 | 17-JAN-03:42 | 0.00 | 0.00 | 20892.24 | 0.00 | 0.00 | 0.00 | 0.00 | 92.65 | 480.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2856.88 | 0.00 | -2087.38 | -16521.09 |
PERIMETER_TOP_ZN_1 | 17-JAN-03:02 | 0.00 | 0.00 | 22881.73 | 0.00 | 0.00 | 0.00 | 0.00 | 143.77 | 745.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -4202.11 | 0.00 | -3080.47 | -16488.49 |
PERIMETER_TOP_ZN_4 | 06-FEB-04:01 | 0.00 | 0.00 | 21189.96 | 0.00 | 0.00 | 0.00 | 0.00 | 92.65 | 480.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3308.60 | 0.00 | -1627.87 | -16826.61 |
DATACENTER_BOT_ZN_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 17-JAN-04:13 | 0.00 | 0.00 | 5694.53 | 0.00 | 0.00 | 0.00 | 0.00 | 321.53 | 19486.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -25502.11 |
DATACENTER_TOP_ZN_6 | 16-JAN-18:10 | 0.00 | 0.00 | 712.05 | 0.00 | 0.00 | 0.00 | 0.00 | 32.15 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -2692.81 |
DATACENTER_BASEMENT_ZN_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 20-AUG-15:31 | 15788.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 265.93 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -16054.14 |
MIDFLOOR_PLENUM | 05-MAR-16:01 | 161587.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -8921.80 | -152665.91 |
TOPFLOOR_PLENUM | 06-FEB-06:12 | 26804.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -849.09 | -25955.16 |
Total Facility | 17-JAN-04:01 | -452650.00 | 348541.54 | 847577.21 | -348541.54 | 0.00 | 0.00 | 0.00 | 21433.72 | 232425.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -193637.41 | 0.00 | -159703.60 | -295445.15 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 08:43:29
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
VAV_BOT WITH REHEAT | 14.3684 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 12.5312 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_MID WITH REHEAT | 138.3008 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 117.4353 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_TOP WITH REHEAT | 14.1789 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 13.0628 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
CAV_BAS | 7.3100 | 0.0000 | 149.6021 | 1.0000 | Calculated from schedules | 1.2002 | 7.3100 | 0.1642 | 1.0000 | Not calculated | 1.2002 | 0.1642 | ||
AIRLOOP DATACENTER BASEMENT | 26.1052 | 0.0000 | 42.1814 | 1.0000 | Calculated from schedules | 0.3384 | 26.1054 | 0.0130 | 1.0000 | Not calculated | 0.3384 | 0.0130 | ||
AIRLOOP DATACENTER BOT | 0.6085 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.6085 | 0.0257 | 1.0000 | Not calculated | 0.0156 | 0.0257 | ||
AIRLOOP DATACENTER MID | 5.8379 | 0.0000 | 19.4861 | 1.0000 | Calculated from schedules | 0.1563 | 5.8379 | 0.0268 | 1.0000 | Not calculated | 0.1563 | 0.0268 | ||
AIRLOOP DATACENTER TOP | 0.5956 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.5956 | 0.0262 | 1.0000 | Not calculated | 0.0156 | 0.0262 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
VAV_BOT WITH REHEAT | 7.1842 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 3.4319 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_MID WITH REHEAT | 69.1504 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 33.7781 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_TOP WITH REHEAT | 7.0894 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 3.5225 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
CAV_BAS | 7.3100 | 0.0000 | 149.6021 | 1.0000 | Calculated from schedules | 1.2002 | 7.3100 | 1.0000 | 1.0000 | Not calculated | 1.2002 | 0.1642 | ||
AIRLOOP DATACENTER BASEMENT | 26.1052 | 0.0000 | 42.1814 | 1.0000 | Calculated from schedules | 0.3384 | 26.1052 | 1.0000 | 1.0000 | Not calculated | 0.3384 | 0.0130 | ||
AIRLOOP DATACENTER BOT | 0.6085 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.6085 | 1.0000 | 1.0000 | Not calculated | 0.0156 | 0.0257 | ||
AIRLOOP DATACENTER MID | 5.8379 | 0.0000 | 19.4861 | 1.0000 | Calculated from schedules | 0.1563 | 5.8379 | 1.0000 | 1.0000 | Not calculated | 0.1563 | 0.0268 | ||
AIRLOOP DATACENTER TOP | 0.5956 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.5956 | 1.0000 | 1.0000 | Not calculated | 0.0156 | 0.0262 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
BASEMENT | CAV_BAS | 0.000000 | 149.6021 | 0.000432 | 2779.43 | 1.2002 | 1.0000 | 1.2002 | 1.000 | 1.2002 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | 0.000000 | 134.3532 | 0.000432 | 2496.12 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_MID | VAV_MID WITH REHEAT | 0.000000 | 1343.5320 | 0.000432 | 24961.20 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_TOP | VAV_TOP WITH REHEAT | 0.000000 | 134.3532 | 0.000432 | 2496.12 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | 0.000000 | 16.8694 | 0.000432 | 313.41 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | 0.000000 | 16.8698 | 0.000432 | 313.42 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | 0.000000 | 168.6939 | 0.000432 | 3134.13 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | 0.000000 | 108.7127 | 0.000432 | 2019.75 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | 0.000000 | 168.6975 | 0.000432 | 3134.20 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | 0.000000 | 108.7127 | 0.000432 | 2019.75 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | 0.000000 | 16.8694 | 0.000432 | 313.41 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | 0.000000 | 16.8698 | 0.000432 | 313.42 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | 0.000000 | 1.9486 | 0.000432 | 36.20 | 0.0156 | 1.0000 | 0.0156 | 1.000 | 0.0156 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | 0.000000 | 19.4861 | 0.000432 | 362.03 | 0.1563 | 1.0000 | 0.1563 | 1.000 | 0.1563 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | 0.000000 | 1.9486 | 0.000432 | 36.20 | 0.0156 | 1.0000 | 0.0156 | 1.000 | 0.0156 |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | 0.000000 | 42.1814 | 0.000432 | 783.68 | 0.3384 | 1.0000 | 0.3384 | 1.000 | 0.3384 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
VAV_BOT WITH REHEAT | 0.00 | 0.000432 | 3526.9033 | 0.0000 | 0.0000 | 0.0000 | |
VAV_MID WITH REHEAT | 0.00 | 0.000432 | 35269.0328 | 0.0000 | 0.0000 | 0.0000 | |
VAV_TOP WITH REHEAT | 0.00 | 0.000432 | 3526.9033 | 0.0000 | 0.0000 | 0.0000 | |
CAV_BAS | 0.000000 | 149.60 | 0.000432 | 2779.4266 | 1.2002 | 1.2002 | 1.2002 |
AIRLOOP DATACENTER BASEMENT | 0.000000 | 42.18 | 0.000432 | 783.6794 | 0.3384 | 0.3384 | 0.3384 |
AIRLOOP DATACENTER BOT | 0.000000 | 1.95 | 0.000432 | 36.2027 | 0.0156 | 0.0156 | 0.0156 |
AIRLOOP DATACENTER MID | 0.000000 | 19.49 | 0.000432 | 362.0274 | 0.1563 | 0.1563 | 0.1563 |
AIRLOOP DATACENTER TOP | 0.000000 | 1.95 | 0.000432 | 36.2027 | 0.0156 | 0.0156 | 0.0156 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | CAV_BAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 7.3100 | 7.3100 | 7.3100 | No | 1.2002 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 7.5433 | 7.5433 | 2.0669 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 71.1383 | 71.1383 | 20.3456 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 7.0072 | 7.0072 | 2.0882 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.3500 | 1.3500 | 0.2700 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.6900 | 1.6900 | 0.3380 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.6980 | 1.6980 | 0.3396 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.0871 | 2.0871 | 0.4174 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 12.9593 | 12.9593 | 2.5919 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 18.0515 | 18.0515 | 3.6103 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 16.6519 | 16.6519 | 3.3304 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 19.4999 | 19.4999 | 3.9000 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.4660 | 1.4660 | 0.2932 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.8222 | 1.8222 | 0.3644 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.8213 | 1.8213 | 0.3643 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.0621 | 2.0621 | 0.4124 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.6085 | 0.6085 | 0.6085 | No | 0.0156 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 5.8379 | 5.8379 | 5.8379 | No | 0.1563 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.5956 | 0.5956 | 0.5956 | No | 0.0156 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 26.1052 | 26.1052 | 26.1052 | No | 0.3384 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
VAV_BOT WITH REHEAT | 14.3684 | 12.5312 | 14.3684 | 3.4319 | 0.0000 | 1.0000 |
VAV_MID WITH REHEAT | 138.3008 | 117.4353 | 138.3008 | 33.7781 | 0.0000 | 1.0000 |
VAV_TOP WITH REHEAT | 14.1789 | 13.0628 | 14.1789 | 3.5225 | 0.0000 | 1.0000 |
CAV_BAS | 7.3100 | 7.3100 | 7.3100 | 7.3100 | 1.2002 | 1.0000 |
AIRLOOP DATACENTER BASEMENT | 26.1052 | 26.1054 | 26.1052 | 26.1052 | 0.3384 | 1.0000 |
AIRLOOP DATACENTER BOT | 0.6085 | 0.6085 | 0.6085 | 0.6085 | 0.0156 | 1.0000 |
AIRLOOP DATACENTER MID | 5.8379 | 5.8379 | 5.8379 | 5.8379 | 0.1563 | 1.0000 |
AIRLOOP DATACENTER TOP | 0.5956 | 0.5956 | 0.5956 | 0.5956 | 0.0156 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | CAV_BAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 7.3100 | 7.3100 | 7.3100 | No | 1.2002 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 3.7717 | 3.7717 | 2.0669 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 35.5692 | 35.5692 | 20.3456 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 3.5036 | 3.5036 | 2.0882 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6750 | 0.6750 | 0.2700 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8450 | 0.8450 | 0.3380 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8490 | 0.8490 | 0.3396 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.0435 | 1.0435 | 0.4174 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 6.4796 | 6.4796 | 2.5919 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 9.0257 | 9.0257 | 3.6103 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 8.3260 | 8.3260 | 3.3304 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 9.7499 | 9.7499 | 3.9000 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7330 | 0.7330 | 0.2932 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.9111 | 0.9111 | 0.3644 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.9106 | 0.9106 | 0.3643 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.0310 | 1.0310 | 0.4124 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.6085 | 0.6085 | 0.6085 | No | 0.0156 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 5.8379 | 5.8379 | 5.8379 | No | 0.1563 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.5956 | 0.5956 | 0.5956 | No | 0.0156 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 26.1052 | 26.1052 | 26.1052 | No | 0.3384 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
VAV_BOT WITH REHEAT | 7.1842 | 3.4319 | 3.4319 | 3.4319 | 0.0000 | 1.0000 |
VAV_MID WITH REHEAT | 69.1504 | 33.7781 | 33.7781 | 33.7781 | 0.0000 | 1.0000 |
VAV_TOP WITH REHEAT | 7.0894 | 3.5225 | 3.5225 | 3.5225 | 0.0000 | 1.0000 |
CAV_BAS | 7.3100 | 7.3100 | 7.3100 | 7.3100 | 1.2002 | 1.0000 |
AIRLOOP DATACENTER BASEMENT | 26.1052 | 26.1052 | 26.1052 | 26.1052 | 0.3384 | 1.0000 |
AIRLOOP DATACENTER BOT | 0.6085 | 0.6085 | 0.6085 | 0.6085 | 0.0156 | 1.0000 |
AIRLOOP DATACENTER MID | 5.8379 | 5.8379 | 5.8379 | 5.8379 | 0.1563 | 1.0000 |
AIRLOOP DATACENTER TOP | 0.5956 | 0.5956 | 0.5956 | 0.5956 | 0.0156 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 08:43:29
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Albuquerque Intl Sunport NM USA TMY3 WMO#=723650 |
Total gross floor area [m2] | 46320.38 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
BASEMENT | 2779.43 | 2779.43 | 0.00 | 113.98 |
CORE_BOTTOM | 2496.12 | 2496.12 | 0.00 | 113.98 |
CORE_MID | 2496.12 | 2496.12 | 0.00 | 113.98 |
CORE_TOP | 2496.12 | 2496.12 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_3 | 313.41 | 313.41 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_2 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_1 | 313.42 | 313.42 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_4 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_MID_ZN_3 | 313.41 | 313.41 | 0.00 | 113.98 |
PERIMETER_MID_ZN_2 | 201.98 | 201.98 | 0.00 | 96.54 |
PERIMETER_MID_ZN_1 | 313.42 | 313.42 | 0.00 | 113.98 |
PERIMETER_MID_ZN_4 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_3 | 313.41 | 313.41 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_2 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_1 | 313.42 | 313.42 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_4 | 201.98 | 201.98 | 0.00 | 113.98 |
DATACENTER_BOT_ZN_6 | 36.20 | 36.20 | 0.00 | 113.98 |
DATACENTER_MID_ZN_6 | 36.20 | 36.20 | 0.00 | 113.98 |
DATACENTER_TOP_ZN_6 | 36.20 | 36.20 | 0.00 | 113.98 |
DATACENTER_BASEMENT_ZN_6 | 783.68 | 783.68 | 0.00 | 113.98 |
GROUNDFLOOR_PLENUM | 3563.11 | 3563.11 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 3563.11 | 3563.11 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 3563.11 | 3563.11 | 0.00 | 0.00 |
Totals | 46320.38 | 46320.38 | 0.00 |
Data | |
Number of hours heating loads not met | 7.33 |
Number of hours cooling loads not met | 877.67 |
Number of hours not met | 885.00 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler | 0.00 | 0.00 | 704.20 | 776734.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 2625.05 | 453863.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 3917.48 | 385834.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 695.82 | 57580.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 5334.97 | 305206.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- DataCenterPlugLoads | 9341.42 | 473165.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Transformer | 80.17 | 5057.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLift | 1848.78 | 113101.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLightsFan | 5.83 | 376.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 3038.09 | 337697.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 465.21 | 61655.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- General | 771.48 | 84672.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- General | 2169.44 | 100000.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 0.00 | 0.00 | 769.81 | 84068.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 14676.40 | 30293.75 |
Natural Gas | 0.00 | 1474.01 |
Additional | 0.00 | 0.00 |
Total | 14676.40 | 31767.76 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 84.57 |
Space Heating | 0.00 |
Space Cooling | 56.67 |
Fans (All) | 65.59 |
Service Water Heating | 0.00 |
Receptacle Equipment | 316.85 |
Miscellaneous (All) | 654.00 |
Subtotal | 654.00 |
Natural Gas [MJ/m2] | |
Space Heating | 15.20 |
Service Water Heating | 16.62 |
Miscellaneous (All) | 31.82 |
Subtotal | 31.82 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 12.33 |
Space Heating | 2.22 |
Space Cooling | 8.26 |
Fans (All) | 9.56 |
Service Water Heating | 2.42 |
Receptacle Equipment | 46.20 |
Miscellaneous | 19.00 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 4472. | 4472. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 6752. | 8760. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 6828. | 8760. |
ALWAYS_OFF | 0. | 0. |
LTG_SCH_OFFICE | 2625. | 8760. |
LTG_SCH_DATACENTER | 2921. | 8760. |
EXTERIOR_LIGHT_SCH | 4380. | 4380. |
BLDG_EQUIP_SCH | 4049. | 8760. |
DATACENTER_EQUIP_SCH | 5478. | 8760. |
BLDG_OCC_SCH | 2528. | 5992. |
BLDG_OCC_SCH_W_SB | 1878. | 5056. |
BLDG_OCC_SCH_WO_SB | 2557. | 5992. |
BLDG_ELEVATORS | 2270. | 8760. |
ELEV_LIGHT_FAN_SCH_24_7 | 8760. | 8760. |
ELEV_LIGHT_FAN_SCH_ADD_DF | 2154. | 8760. |
BLDG_SWH_SCH | 1474. | 6570. |
WORK_EFF_SCH | 0. | 0. |
INFIL_SCH | 3976. | 3976. |
INFIL_SCH_PNNL | 5172. | 8760. |
INFIL_HALF_ON_SCH | 6368. | 8760. |
FAN_SCH | 8760. | 8760. |
REHEATCOILAVAILSCHED | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
MINOA_MOTORIZEDDAMPER_SCHED | 4472. | 4472. |
MINOA_SCHED | 8760. | 8760. |
CORE_BOTTOM SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_BOTTOM SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_MID SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_MID SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_TOP SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_TOP SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
SUPPLYFANSCH | 8760. | 8760. |
PERIMETER_MID_ZN_2_MDP_SCH | 1565. | 7824. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
HTGSETP_DC_SCH | DATACENTER COOLING SETPOINTS DUAL SP CONTROL | January | 18.00 | 365 | 18.00 | 365 |
CLGSETP_DC_SCH | DATACENTER COOLING SETPOINTS DUAL SP CONTROL | July | 27.00 | 365 | 27.00 | 365 |
HTGSETP_SCH_YES_OPTIMUM | CORE_BOTTOM DUAL SP CONTROL | January | 21.00 | 365 | 15.60 | 365 |
CLGSETP_SCH_YES_OPTIMUM | CORE_BOTTOM DUAL SP CONTROL | July | 24.00 | 365 | 26.70 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:43:29
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
BASEMENT | 8569.50 | 190.50 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 8752.33 | 7.67 | 0.00 | 0.00 | 0.00 |
CORE_MID | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 8731.83 | 28.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 8681.67 | 78.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 8681.83 | 78.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 8561.33 | 198.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 8741.00 | 19.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 8673.00 | 87.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 8683.00 | 77.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 8672.17 | 87.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 8734.67 | 25.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 8667.83 | 92.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 8690.67 | 69.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 8675.50 | 84.50 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 8721.17 | 38.83 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 8742.67 | 17.33 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 8747.33 | 12.67 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 7978.00 | 779.00 | 3.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 8641.83 | 118.17 | 0.00 | 0.00 | 0.00 |
Min | 7978.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 779.00 | 3.00 | 0.00 | 0.00 |
Average | 8669.01 | 90.86 | 0.13 | 0.00 | 0.00 |
Sum | 199387.33 | 2089.67 | 3.00 | 0.00 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
BASEMENT | 367994.17 | 621.83 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 330802.00 | 11.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 330813.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 330813.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 18354.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 2255.83 | 12.17 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 2264.50 | 3.50 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 2266.17 | 1.83 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 92722.00 | 10669.33 | 3.67 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 367994.17 | 10669.33 | 3.67 | 0.00 | 0.00 |
Average | 79842.59 | 492.16 | 0.16 | 0.00 | 0.00 |
Sum | 1836379.67 | 11319.67 | 3.67 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
BASEMENT | 8463.50 | 296.50 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 8651.00 | 109.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 8648.33 | 111.67 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 8669.83 | 90.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 8640.17 | 119.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 8657.17 | 102.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 8633.67 | 126.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 8497.00 | 263.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 8659.83 | 100.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 8608.17 | 151.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 8638.00 | 122.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 8590.17 | 169.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 8669.50 | 90.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 8612.33 | 147.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 8645.17 | 114.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 8595.17 | 164.83 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 8759.17 | 0.83 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 8759.67 | 0.33 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 8759.00 | 1.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 8145.67 | 614.33 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 8616.00 | 144.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 8679.00 | 81.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 8557.00 | 203.00 | 0.00 | 0.00 | 0.00 |
Min | 8145.67 | 0.33 | 0.00 | 0.00 | 0.00 |
Max | 8759.67 | 614.33 | 0.00 | 0.00 | 0.00 |
Average | 8615.41 | 144.59 | 0.00 | 0.00 | 0.00 |
Sum | 198154.50 | 3325.50 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
BASEMENT | 367739.00 | 877.00 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 330619.00 | 194.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 330688.00 | 125.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 330726.00 | 87.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 18354.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 2268.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 2268.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 2268.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 94559.33 | 8835.67 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 367739.00 | 8835.67 | 0.00 | 0.00 | 0.00 |
Average | 79894.97 | 439.94 | 0.00 | 0.00 | 0.00 |
Sum | 1837584.33 | 10118.67 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:43:29
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:43:29
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 0.00 | 8760.00 | 0.00 |
Average | 0.00 | 0.00 | 4570.43 | 0.00 |
Sum | 0.00 | 0.00 | 105120.00 | 0.00 |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 18354.00 | 0.00 |
PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 24909.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 0.00 | 38925.00 | 0.00 |
Average | 0.00 | 0.00 | 16367.35 | 0.00 |
Sum | 0.00 | 0.00 | 376449.00 | 0.00 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 2.601 |
February | 4.285 |
March | 8.765 |
April | 13.905 |
May | 17.822 |
June | 23.208 |
July | 25.626 |
August | 24.075 |
September | 20.490 |
October | 13.707 |
November | 6.961 |
December | 2.072 |
Annual Sum or Average | 13.676 |
Minimum of Months | 2.072 |
Maximum of Months | 25.626 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Environment
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 2.601 |
February | 4.285 |
March | 8.765 |
April | 13.905 |
May | 17.822 |
June | 23.208 |
July | 25.626 |
August | 24.075 |
September | 20.490 |
October | 13.707 |
November | 6.961 |
December | 2.072 |
Annual Sum or Average | 13.676 |
Minimum of Months | 2.072 |
Maximum of Months | 25.626 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2013
For: Environment
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 2.601 |
February | 4.285 |
March | 8.765 |
April | 13.905 |
May | 17.822 |
June | 23.208 |
July | 25.626 |
August | 24.075 |
September | 20.490 |
October | 13.707 |
November | 6.961 |
December | 2.072 |
Annual Sum or Average | 13.676 |
Minimum of Months | 2.072 |
Maximum of Months | 25.626 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 2.601 |
February | 4.285 |
March | 8.765 |
April | 13.905 |
May | 17.822 |
June | 23.208 |
July | 25.626 |
August | 24.075 |
September | 20.490 |
October | 13.707 |
November | 6.961 |
December | 2.072 |
Annual Sum or Average | 13.676 |
Minimum of Months | 2.072 |
Maximum of Months | 25.626 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICELARGE
For: Environment
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 2.601 |
February | 4.285 |
March | 8.765 |
April | 13.905 |
May | 17.822 |
June | 23.208 |
July | 25.626 |
August | 24.075 |
September | 20.490 |
October | 13.707 |
November | 6.961 |
December | 2.072 |
Annual Sum or Average | 13.676 |
Minimum of Months | 2.072 |
Maximum of Months | 25.626 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 2.601 |
February | 4.285 |
March | 8.765 |
April | 13.905 |
May | 17.822 |
June | 23.208 |
July | 25.626 |
August | 24.075 |
September | 20.490 |
October | 13.707 |
November | 6.961 |
December | 2.072 |
Annual Sum or Average | 13.676 |
Minimum of Months | 2.072 |
Maximum of Months | 25.626 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 2.601 |
February | 4.285 |
March | 8.765 |
April | 13.905 |
May | 17.822 |
June | 23.208 |
July | 25.626 |
August | 24.075 |
September | 20.490 |
October | 13.707 |
November | 6.961 |
December | 2.072 |
Annual Sum or Average | 13.676 |
Minimum of Months | 2.072 |
Maximum of Months | 25.626 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 4B
For: Environment
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 2.601 |
February | 4.285 |
March | 8.765 |
April | 13.905 |
May | 17.822 |
June | 23.208 |
July | 25.626 |
August | 24.075 |
September | 20.490 |
October | 13.707 |
November | 6.961 |
December | 2.072 |
Annual Sum or Average | 13.676 |
Minimum of Months | 2.072 |
Maximum of Months | 25.626 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_NM_ALBUQUERQUE
For: Environment
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 2.601 |
February | 4.285 |
March | 8.765 |
April | 13.905 |
May | 17.822 |
June | 23.208 |
July | 25.626 |
August | 24.075 |
September | 20.490 |
October | 13.707 |
November | 6.961 |
December | 2.072 |
Annual Sum or Average | 13.676 |
Minimum of Months | 2.072 |
Maximum of Months | 25.626 |
Report: ZoneCoolingSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.556773E+11 | 119847.91 | 17-JAN-04:01 | -3.3 | -5.0 | 0.566611E+10 | 7499.07 | 06-JAN-10:00 | -3.3 | -5.0 |
February | 0.508531E+11 | 122126.53 | 21-FEB-05:11 | 2.57 | 0.44 | 0.513946E+10 | 7499.09 | 22-FEB-10:39 | 2.03 | 0.93 |
March | 0.619780E+11 | 117553.86 | 20-MAR-04:12 | 9.03 | 4.70 | 0.613393E+10 | 7498.99 | 02-MAR-14:09 | 9.03 | 4.70 |
April | 0.599084E+11 | 118821.27 | 17-APR-04:12 | 10.00 | 2.17 | 0.545182E+10 | 7499.01 | 28-APR-13:09 | 24.40 | 9.92 |
May | 0.626648E+11 | 120056.09 | 01-MAY-04:12 | 11.10 | 7.33 | 0.590282E+10 | 7499.28 | 11-MAY-09:20 | 12.93 | 6.34 |
June | 0.651104E+11 | 116964.53 | 12-JUN-04:12 | 14.23 | 8.98 | 0.588419E+10 | 7499.12 | 30-JUN-13:00 | 26.70 | 17.72 |
July | 0.664539E+11 | 106086.51 | 19-JUL-04:12 | 18.87 | 11.61 | 0.547570E+10 | 7499.02 | 28-JUL-09:09 | 24.68 | 16.51 |
August | 0.740424E+11 | 109661.70 | 31-AUG-04:12 | 15.03 | 11.51 | 0.613909E+10 | 7500.37 | 28-AUG-13:39 | 15.03 | 11.51 |
September | 0.661477E+11 | 116571.74 | 19-SEP-04:12 | 13.33 | 9.47 | 0.545520E+10 | 7511.90 | 18-SEP-13:20 | 13.33 | 9.47 |
October | 0.682766E+11 | 119401.40 | 23-OCT-04:12 | 7.43 | 6.45 | 0.567381E+10 | 7499.27 | 03-OCT-13:09 | 7.43 | 6.45 |
November | 0.639720E+11 | 120030.42 | 27-NOV-04:01 | -3.9 | -6.4 | 0.561633E+10 | 7498.99 | 08-NOV-10:20 | -3.9 | -6.4 |
December | 0.606150E+11 | 121553.65 | 11-DEC-05:01 | 1.70 | -2.3 | 0.547225E+10 | 7499.06 | 27-DEC-10:09 | 1.97 | -0.8 |
Annual Sum or Average | 0.755700E+12 | 0.680107E+11 | ||||||||
Minimum of Months | 0.508531E+11 | 106086.51 | -3.9 | -6.4 | 0.513946E+10 | 7498.99 | -3.9 | -6.4 | ||
Maximum of Months | 0.740424E+11 | 122126.53 | 18.87 | 11.61 | 0.613909E+10 | 7511.90 | 26.70 | 17.72 |
Report: ZoneCoolingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.430943E+11 | 92999.86 | 02-JAN-04:01 | -1.8 | -3.6 | 0.506687E+10 | 6734.74 | 06-JAN-10:00 | 2.20 | -1.4 |
February | 0.426696E+11 | 96040.11 | 21-FEB-05:11 | 2.57 | 0.44 | 0.460208E+10 | 6734.76 | 22-FEB-10:39 | 2.03 | 0.93 |
March | 0.574410E+11 | 95083.10 | 27-MAR-04:12 | 5.20 | 0.41 | 0.549852E+10 | 6734.70 | 28-MAR-13:09 | 16.42 | 7.54 |
April | 0.611743E+11 | 98397.39 | 24-APR-04:12 | 6.10 | 2.66 | 0.488240E+10 | 6734.78 | 17-APR-13:00 | 6.10 | 2.66 |
May | 0.580657E+11 | 99158.90 | 22-MAY-04:13 | 17.43 | 11.95 | 0.528604E+10 | 6735.01 | 11-MAY-09:09 | 17.43 | 11.95 |
June | 0.652107E+11 | 98908.42 | 05-JUN-04:13 | 15.00 | 13.05 | 0.526925E+10 | 6734.83 | 08-JUN-13:09 | 16.52 | 13.78 |
July | 0.704934E+11 | 94556.25 | 08-JUL-04:12 | 16.30 | 14.75 | 0.489552E+10 | 6734.77 | 18-JUL-09:39 | 25.37 | 17.15 |
August | 0.792002E+11 | 91560.33 | 25-AUG-04:12 | 16.13 | 13.78 | 0.549572E+10 | 6735.34 | 28-AUG-13:39 | 23.30 | 16.88 |
September | 0.576874E+11 | 101012.80 | 05-SEP-04:13 | 17.23 | 15.17 | 0.488427E+10 | 6734.82 | 27-SEP-09:09 | 18.77 | 10.94 |
October | 0.580246E+11 | 101496.62 | 02-OCT-04:13 | 17.60 | 12.86 | 0.507811E+10 | 6734.84 | 24-OCT-13:39 | 10.53 | 5.31 |
November | 0.539274E+11 | 97473.74 | 24-NOV-05:11 | 2.40 | -2.3 | 0.502690E+10 | 6734.71 | 08-NOV-10:20 | 2.40 | -2.3 |
December | 0.504741E+11 | 94122.27 | 04-DEC-04:01 | -0.1 | -1.9 | 0.490037E+10 | 6734.71 | 21-DEC-10:20 | -2.8 | -4.8 |
Annual Sum or Average | 0.697463E+12 | 0.608860E+11 | ||||||||
Minimum of Months | 0.426696E+11 | 91560.33 | -1.8 | -3.6 | 0.460208E+10 | 6734.70 | -2.8 | -4.8 | ||
Maximum of Months | 0.792002E+11 | 101496.62 | 17.60 | 15.17 | 0.549852E+10 | 6735.34 | 25.37 | 17.15 |
Report: ZoneCoolingSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.303289E+11 | 35126.98 | 26-JAN-17:00 | 10.00 | 1.21 | 0.495082E+10 | 6734.75 | 06-JAN-10:00 | 10.00 | 1.21 |
February | 0.295726E+11 | 80166.06 | 15-FEB-06:02 | 6.93 | 2.40 | 0.452897E+10 | 6734.75 | 22-FEB-10:39 | 2.03 | 0.93 |
March | 0.395577E+11 | 79814.56 | 17-MAR-05:03 | 7.02 | 1.62 | 0.546517E+10 | 6734.70 | 13-MAR-09:09 | 7.02 | 1.62 |
April | 0.420571E+11 | 84734.96 | 28-APR-04:12 | 11.87 | 4.07 | 0.486863E+10 | 6734.70 | 17-APR-13:00 | 11.87 | 4.07 |
May | 0.480622E+11 | 86694.29 | 22-MAY-04:12 | 17.43 | 11.95 | 0.527754E+10 | 6734.97 | 11-MAY-09:09 | 17.43 | 11.95 |
June | 0.524838E+11 | 88214.88 | 30-JUN-04:12 | 17.07 | 12.23 | 0.526540E+10 | 6734.84 | 08-JUN-13:09 | 17.07 | 12.23 |
July | 0.531590E+11 | 88202.57 | 13-JUL-04:12 | 17.60 | 13.52 | 0.489286E+10 | 6734.77 | 18-JUL-09:39 | 25.37 | 17.15 |
August | 0.563266E+11 | 87879.22 | 04-AUG-04:12 | 19.03 | 13.93 | 0.549525E+10 | 6735.33 | 28-AUG-13:50 | 23.30 | 17.44 |
September | 0.481690E+11 | 88910.63 | 05-SEP-04:12 | 17.23 | 15.17 | 0.487784E+10 | 6734.80 | 27-SEP-09:09 | 18.77 | 10.94 |
October | 0.438015E+11 | 87679.61 | 03-OCT-04:12 | 14.63 | 11.58 | 0.505800E+10 | 6734.77 | 24-OCT-13:39 | 10.53 | 5.31 |
November | 0.353690E+11 | 82915.85 | 02-NOV-05:02 | 7.12 | 4.64 | 0.498384E+10 | 6734.71 | 08-NOV-10:20 | 13.50 | 6.09 |
December | 0.303703E+11 | 70907.72 | 01-DEC-06:03 | 3.90 | -0.5 | 0.479166E+10 | 6734.73 | 27-DEC-10:09 | 1.97 | -0.8 |
Annual Sum or Average | 0.509258E+12 | 0.604560E+11 | ||||||||
Minimum of Months | 0.295726E+11 | 35126.98 | 3.90 | -0.5 | 0.452897E+10 | 6734.70 | 1.97 | -0.8 | ||
Maximum of Months | 0.563266E+11 | 88910.63 | 19.03 | 15.17 | 0.549525E+10 | 6735.33 | 25.37 | 17.44 |
Report: ZoneCoolingSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.227782E+11 | 29400.72 | 05-JAN-17:00 | 13.30 | 5.53 | 0.447110E+10 | 6734.49 | 05-JAN-14:39 | 13.30 | 5.53 |
February | 0.225354E+11 | 39859.42 | 15-FEB-16:20 | 17.03 | 6.28 | 0.422412E+10 | 6734.62 | 15-FEB-10:09 | 17.03 | 6.28 |
March | 0.325752E+11 | 40992.28 | 08-MAR-16:30 | 22.50 | 8.65 | 0.529581E+10 | 6734.68 | 16-MAR-09:30 | 8.30 | 4.38 |
April | 0.385962E+11 | 78303.96 | 27-APR-05:03 | 9.40 | 3.12 | 0.481508E+10 | 6734.73 | 17-APR-13:00 | 9.40 | 3.12 |
May | 0.472105E+11 | 85687.08 | 22-MAY-04:12 | 17.43 | 11.95 | 0.525743E+10 | 6734.91 | 11-MAY-09:09 | 17.43 | 11.95 |
June | 0.553874E+11 | 86086.51 | 30-JUN-04:12 | 17.07 | 12.23 | 0.526168E+10 | 6772.06 | 28-JUN-13:00 | 17.07 | 12.23 |
July | 0.582659E+11 | 96063.81 | 05-JUL-04:13 | 22.20 | 13.87 | 0.489592E+10 | 6734.74 | 18-JUL-09:50 | 25.73 | 17.29 |
August | 0.601652E+11 | 89075.09 | 14-AUG-04:13 | 18.90 | 16.62 | 0.549691E+10 | 6735.34 | 28-AUG-13:50 | 23.30 | 17.44 |
September | 0.477501E+11 | 89143.30 | 05-SEP-04:12 | 17.23 | 15.17 | 0.486977E+10 | 6734.76 | 27-SEP-09:09 | 18.77 | 10.94 |
October | 0.378850E+11 | 83983.28 | 02-OCT-04:12 | 17.60 | 12.86 | 0.496226E+10 | 6734.72 | 24-OCT-13:39 | 10.53 | 5.31 |
November | 0.269542E+11 | 42422.07 | 01-NOV-15:20 | 12.07 | 7.11 | 0.472347E+10 | 6734.66 | 02-NOV-09:00 | 9.40 | 6.72 |
December | 0.221692E+11 | 29704.18 | 01-DEC-17:00 | 12.20 | 4.22 | 0.431980E+10 | 6734.59 | 28-DEC-14:50 | 7.80 | 2.68 |
Annual Sum or Average | 0.472273E+12 | 0.585934E+11 | ||||||||
Minimum of Months | 0.221692E+11 | 29400.72 | 9.40 | 3.12 | 0.422412E+10 | 6734.49 | 7.80 | 2.68 | ||
Maximum of Months | 0.601652E+11 | 96063.81 | 22.50 | 16.62 | 0.549691E+10 | 6772.06 | 25.73 | 17.44 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.280347E+10 | 3140.38 | 24-JAN-14:40 | 15.37 | 4.72 | 0.566743E+09 | 845.59 | 04-JAN-14:00 | 15.37 | 4.72 |
February | 0.298283E+10 | 4891.03 | 15-FEB-13:20 | 15.77 | 6.33 | 0.535521E+09 | 845.61 | 15-FEB-10:09 | 15.77 | 6.33 |
March | 0.500369E+10 | 7431.42 | 27-MAR-14:30 | 18.05 | 6.97 | 0.672914E+09 | 845.63 | 28-MAR-13:09 | 16.42 | 7.54 |
April | 0.709183E+10 | 9462.48 | 14-APR-14:00 | 23.30 | 10.26 | 0.608835E+09 | 845.64 | 17-APR-13:00 | 24.40 | 9.80 |
May | 0.805969E+10 | 13828.15 | 14-MAY-16:11 | 28.30 | 10.92 | 0.662236E+09 | 845.65 | 11-MAY-09:09 | 28.30 | 10.92 |
June | 0.117119E+11 | 19722.98 | 18-JUN-18:11 | 29.43 | 10.52 | 0.662285E+09 | 845.65 | 30-JUN-13:00 | 26.70 | 17.72 |
July | 0.129414E+11 | 19674.40 | 02-JUL-18:01 | 31.42 | 16.51 | 0.616198E+09 | 846.33 | 31-JUL-13:30 | 30.00 | 18.38 |
August | 0.132035E+11 | 19362.04 | 06-AUG-16:31 | 30.20 | 16.21 | 0.690778E+09 | 845.71 | 28-AUG-13:30 | 23.30 | 16.30 |
September | 0.803488E+10 | 16892.03 | 03-SEP-14:11 | 32.07 | 16.57 | 0.612467E+09 | 845.63 | 27-SEP-09:09 | 18.77 | 10.94 |
October | 0.578420E+10 | 12675.07 | 02-OCT-04:12 | 17.60 | 12.86 | 0.625220E+09 | 845.64 | 24-OCT-13:39 | 10.53 | 5.31 |
November | 0.393189E+10 | 5389.85 | 08-NOV-13:40 | 15.73 | 6.89 | 0.606902E+09 | 845.61 | 08-NOV-10:09 | 15.73 | 6.89 |
December | 0.305863E+10 | 4006.36 | 01-DEC-13:30 | 11.70 | 4.38 | 0.554079E+09 | 845.62 | 01-DEC-10:20 | 11.70 | 4.38 |
Annual Sum or Average | 0.846080E+11 | 0.741418E+10 | ||||||||
Minimum of Months | 0.280347E+10 | 3140.38 | 11.70 | 4.38 | 0.535521E+09 | 845.59 | 10.53 | 4.38 | ||
Maximum of Months | 0.132035E+11 | 19722.98 | 32.07 | 16.57 | 0.690778E+09 | 846.33 | 30.00 | 18.38 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.374970E+10 | 8252.53 | 02-JAN-09:25 | 2.75 | -0.6 | 0.367396E+09 | 544.95 | 24-JAN-10:09 | 8.07 | 2.63 |
February | 0.407618E+10 | 20367.45 | 19-FEB-09:32 | 8.13 | 3.75 | 0.347347E+09 | 544.96 | 15-FEB-10:09 | 8.13 | 3.75 |
March | 0.656902E+10 | 24118.68 | 26-MAR-08:32 | 9.67 | 3.27 | 0.433095E+09 | 544.95 | 28-MAR-13:09 | 16.42 | 7.54 |
April | 0.937899E+10 | 28603.02 | 30-APR-08:61 | 15.10 | 5.14 | 0.392799E+09 | 546.95 | 28-APR-09:00 | 15.10 | 5.14 |
May | 0.100875E+11 | 27933.46 | 14-MAY-07:31 | 18.17 | 8.24 | 0.426669E+09 | 546.30 | 15-MAY-09:50 | 20.92 | 9.24 |
June | 0.126481E+11 | 29233.71 | 18-JUN-08:11 | 23.73 | 11.69 | 0.426564E+09 | 546.63 | 19-JUN-09:00 | 21.10 | 8.29 |
July | 0.132511E+11 | 28837.76 | 02-JUL-08:41 | 23.03 | 17.20 | 0.397037E+09 | 546.93 | 06-JUL-09:20 | 27.93 | 15.97 |
August | 0.133899E+11 | 26256.61 | 20-AUG-08:11 | 24.97 | 14.91 | 0.444631E+09 | 546.85 | 15-AUG-09:00 | 24.97 | 14.91 |
September | 0.943616E+10 | 28898.02 | 03-SEP-08:11 | 24.07 | 14.28 | 0.393978E+09 | 546.49 | 01-SEP-09:20 | 24.07 | 14.28 |
October | 0.733519E+10 | 27161.97 | 01-OCT-08:41 | 17.43 | 11.07 | 0.401885E+09 | 545.03 | 10-OCT-09:09 | 20.18 | 13.84 |
November | 0.501296E+10 | 15603.01 | 12-NOV-09:13 | 3.17 | 0.48 | 0.387428E+09 | 544.94 | 21-NOV-14:09 | 15.18 | 5.79 |
December | 0.383018E+10 | 8056.50 | 29-DEC-09:20 | 1.67 | -0.9 | 0.356383E+09 | 544.95 | 01-DEC-10:20 | 1.67 | -0.9 |
Annual Sum or Average | 0.987651E+11 | 0.477521E+10 | ||||||||
Minimum of Months | 0.374970E+10 | 8056.50 | 1.67 | -0.9 | 0.347347E+09 | 544.94 | 1.67 | -0.9 | ||
Maximum of Months | 0.133899E+11 | 29233.71 | 24.97 | 17.20 | 0.444631E+09 | 546.95 | 27.93 | 15.97 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.108955E+11 | 26425.60 | 01-JAN-13:51 | 15.60 | 5.65 | 0.613685E+09 | 940.03 | 23-JAN-14:09 | 14.60 | 4.35 |
February | 0.109638E+11 | 26755.53 | 19-FEB-13:31 | 15.73 | 6.54 | 0.565651E+09 | 953.87 | 14-FEB-14:09 | 15.73 | 6.54 |
March | 0.116730E+11 | 24761.34 | 12-MAR-13:22 | 17.25 | 5.71 | 0.677228E+09 | 874.51 | 13-MAR-13:20 | 19.47 | 6.71 |
April | 0.116946E+11 | 25544.94 | 30-APR-12:42 | 20.40 | 7.05 | 0.607755E+09 | 847.99 | 17-APR-13:00 | 20.40 | 7.05 |
May | 0.980507E+10 | 24035.41 | 28-MAY-13:32 | 24.80 | 13.74 | 0.659739E+09 | 845.68 | 09-MAY-13:30 | 24.80 | 13.74 |
June | 0.119243E+11 | 24130.61 | 25-JUN-14:21 | 34.15 | 16.76 | 0.661125E+09 | 845.67 | 30-JUN-13:00 | 26.70 | 17.72 |
July | 0.144300E+11 | 24195.41 | 02-JUL-15:21 | 31.95 | 17.31 | 0.615963E+09 | 846.40 | 25-JUL-13:20 | 33.67 | 17.52 |
August | 0.175770E+11 | 25817.62 | 06-AUG-13:11 | 31.47 | 16.37 | 0.691247E+09 | 861.41 | 31-AUG-13:09 | 29.50 | 15.73 |
September | 0.152899E+11 | 27930.91 | 10-SEP-12:41 | 25.82 | 14.93 | 0.617181E+09 | 965.93 | 28-SEP-13:30 | 29.45 | 15.27 |
October | 0.158250E+11 | 30092.86 | 01-OCT-12:01 | 25.87 | 14.46 | 0.644661E+09 | 985.92 | 31-OCT-13:20 | 20.93 | 8.54 |
November | 0.134870E+11 | 28624.81 | 19-NOV-13:01 | 11.47 | 2.76 | 0.634201E+09 | 981.35 | 01-NOV-13:09 | 11.47 | 2.76 |
December | 0.128474E+11 | 29904.73 | 31-DEC-13:21 | 9.15 | 1.31 | 0.604895E+09 | 944.25 | 29-DEC-14:09 | 9.15 | 1.31 |
Annual Sum or Average | 0.156413E+12 | 0.759333E+10 | ||||||||
Minimum of Months | 0.980507E+10 | 24035.41 | 9.15 | 1.31 | 0.565651E+09 | 845.67 | 9.15 | 1.31 | ||
Maximum of Months | 0.175770E+11 | 30092.86 | 34.15 | 17.31 | 0.691247E+09 | 985.92 | 33.67 | 17.72 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.544880E+10 | 14023.78 | 01-JAN-15:52 | 15.60 | 5.80 | 0.366700E+09 | 544.94 | 19-JAN-14:00 | 5.00 | 1.80 |
February | 0.646263E+10 | 18294.73 | 12-FEB-16:12 | 17.93 | 6.17 | 0.350645E+09 | 544.96 | 15-FEB-10:09 | 11.38 | 5.33 |
March | 0.953333E+10 | 31083.39 | 12-MAR-16:01 | 19.60 | 6.14 | 0.439481E+09 | 544.96 | 28-MAR-13:09 | 16.42 | 7.54 |
April | 0.130032E+11 | 33375.49 | 16-APR-16:31 | 20.20 | 8.02 | 0.395641E+09 | 544.98 | 17-APR-13:00 | 24.40 | 9.80 |
May | 0.110807E+11 | 34943.70 | 14-MAY-16:11 | 28.30 | 10.92 | 0.425923E+09 | 544.98 | 11-MAY-09:09 | 28.30 | 10.92 |
June | 0.148066E+11 | 37369.91 | 25-JUN-16:21 | 34.45 | 14.68 | 0.427199E+09 | 544.97 | 30-JUN-13:00 | 26.70 | 17.72 |
July | 0.167903E+11 | 36625.25 | 02-JUL-16:41 | 31.28 | 16.81 | 0.397628E+09 | 544.97 | 18-JUL-09:39 | 25.37 | 17.15 |
August | 0.192464E+11 | 35081.63 | 06-AUG-17:11 | 30.20 | 16.04 | 0.446077E+09 | 545.03 | 28-AUG-13:30 | 23.30 | 16.30 |
September | 0.110609E+11 | 35037.47 | 24-SEP-16:01 | 25.50 | 15.65 | 0.395046E+09 | 544.97 | 19-SEP-13:09 | 25.50 | 15.65 |
October | 0.100400E+11 | 32348.81 | 01-OCT-14:01 | 28.30 | 13.52 | 0.404753E+09 | 544.97 | 03-OCT-13:39 | 25.20 | 14.40 |
November | 0.784232E+10 | 30879.66 | 19-NOV-15:01 | 14.90 | 3.99 | 0.399155E+09 | 544.95 | 21-NOV-14:09 | 15.18 | 5.79 |
December | 0.703460E+10 | 30753.43 | 31-DEC-16:01 | 9.82 | 1.41 | 0.381234E+09 | 544.95 | 01-DEC-10:20 | 9.82 | 1.41 |
Annual Sum or Average | 0.132350E+12 | 0.482948E+10 | ||||||||
Minimum of Months | 0.544880E+10 | 14023.78 | 9.82 | 1.41 | 0.350645E+09 | 544.94 | 5.00 | 1.41 | ||
Maximum of Months | 0.192464E+11 | 37369.91 | 34.45 | 16.81 | 0.446077E+09 | 545.03 | 28.30 | 17.72 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.139094E+10 | 2580.27 | 05-JAN-16:00 | 16.10 | 6.84 | 0.491828E+09 | 760.24 | 04-JAN-14:00 | 16.10 | 6.84 |
February | 0.165161E+10 | 2908.56 | 15-FEB-15:10 | 17.20 | 6.64 | 0.465425E+09 | 843.68 | 15-FEB-14:00 | 17.20 | 6.64 |
March | 0.291652E+10 | 4896.80 | 27-MAR-14:40 | 18.13 | 6.99 | 0.620564E+09 | 845.62 | 28-MAR-13:09 | 16.42 | 7.54 |
April | 0.454096E+10 | 8181.66 | 14-APR-14:00 | 23.30 | 10.26 | 0.590108E+09 | 845.63 | 17-APR-13:00 | 24.40 | 9.80 |
May | 0.657226E+10 | 9000.90 | 31-MAY-15:30 | 27.75 | 11.03 | 0.656072E+09 | 845.64 | 11-MAY-09:09 | 27.75 | 11.03 |
June | 0.100702E+11 | 18986.63 | 25-JUN-17:42 | 32.88 | 15.68 | 0.661427E+09 | 845.84 | 29-JUN-13:00 | 36.70 | 15.89 |
July | 0.107866E+11 | 19300.05 | 04-JUL-18:12 | 33.33 | 13.61 | 0.616100E+09 | 846.14 | 31-JUL-13:30 | 30.00 | 18.38 |
August | 0.100507E+11 | 18518.09 | 20-AUG-16:01 | 34.90 | 15.92 | 0.690341E+09 | 845.70 | 28-AUG-13:30 | 23.30 | 16.30 |
September | 0.663596E+10 | 17873.64 | 04-SEP-16:11 | 26.70 | 16.39 | 0.608903E+09 | 845.62 | 27-SEP-09:09 | 18.77 | 10.94 |
October | 0.409189E+10 | 8103.46 | 02-OCT-13:40 | 26.33 | 15.37 | 0.592026E+09 | 845.63 | 24-OCT-13:39 | 10.53 | 5.31 |
November | 0.231274E+10 | 3133.33 | 03-NOV-14:00 | 12.20 | 2.42 | 0.532609E+09 | 845.60 | 09-NOV-14:00 | 18.30 | 9.49 |
December | 0.120030E+10 | 2428.01 | 29-DEC-16:10 | 11.42 | 3.74 | 0.463953E+09 | 799.53 | 01-DEC-14:00 | 11.42 | 3.74 |
Annual Sum or Average | 0.622208E+11 | 0.698936E+10 | ||||||||
Minimum of Months | 0.120030E+10 | 2428.01 | 11.42 | 2.42 | 0.463953E+09 | 760.24 | 10.53 | 3.74 | ||
Maximum of Months | 0.107866E+11 | 19300.05 | 34.90 | 16.39 | 0.690341E+09 | 846.14 | 36.70 | 18.38 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.254600E+10 | 6225.43 | 27-JAN-09:40 | 2.07 | -2.9 | 0.246100E+09 | 521.19 | 27-JAN-09:09 | 2.07 | -2.9 |
February | 0.310448E+10 | 10124.44 | 14-FEB-09:30 | 8.35 | 2.46 | 0.234382E+09 | 521.20 | 07-FEB-11:09 | 8.35 | 2.46 |
March | 0.555590E+10 | 25986.83 | 12-MAR-09:52 | 11.10 | 2.35 | 0.303713E+09 | 521.22 | 17-MAR-15:30 | 12.20 | 5.76 |
April | 0.864457E+10 | 27880.41 | 30-APR-08:51 | 15.60 | 4.83 | 0.286783E+09 | 522.45 | 28-APR-10:09 | 15.60 | 4.83 |
May | 0.100036E+11 | 31233.56 | 29-MAY-09:11 | 19.07 | 13.00 | 0.311863E+09 | 521.57 | 17-MAY-07:49 | 19.07 | 13.00 |
June | 0.127323E+11 | 31905.08 | 18-JUN-08:11 | 23.73 | 11.69 | 0.312983E+09 | 529.46 | 29-JUN-07:19 | 27.93 | 17.35 |
July | 0.130263E+11 | 32746.82 | 04-JUL-08:51 | 26.70 | 18.67 | 0.293215E+09 | 528.47 | 21-JUL-07:19 | 27.43 | 15.33 |
August | 0.126895E+11 | 32582.82 | 20-AUG-08:41 | 25.82 | 15.35 | 0.326962E+09 | 523.39 | 02-AUG-10:30 | 25.82 | 15.35 |
September | 0.933010E+10 | 27849.80 | 03-SEP-09:01 | 25.97 | 15.10 | 0.288202E+09 | 521.60 | 26-SEP-08:39 | 19.27 | 10.46 |
October | 0.669418E+10 | 28772.50 | 01-OCT-08:51 | 17.80 | 11.25 | 0.287000E+09 | 521.23 | 02-OCT-12:09 | 25.10 | 14.89 |
November | 0.391816E+10 | 10659.04 | 01-NOV-09:00 | 10.00 | 6.46 | 0.264638E+09 | 521.20 | 01-NOV-07:30 | 10.00 | 6.46 |
December | 0.250468E+10 | 5911.22 | 29-DEC-09:30 | 1.95 | -0.8 | 0.235279E+09 | 521.19 | 29-DEC-09:09 | 1.95 | -0.8 |
Annual Sum or Average | 0.907498E+11 | 0.339112E+10 | ||||||||
Minimum of Months | 0.250468E+10 | 5911.22 | 1.95 | -2.9 | 0.234382E+09 | 521.19 | 1.95 | -2.9 | ||
Maximum of Months | 0.130263E+11 | 32746.82 | 26.70 | 18.67 | 0.326962E+09 | 529.46 | 27.93 | 17.35 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.108721E+11 | 27595.80 | 15-JAN-12:01 | 8.17 | 1.87 | 0.609136E+09 | 1023.05 | 23-JAN-14:09 | 14.60 | 4.35 |
February | 0.107086E+11 | 26644.47 | 19-FEB-13:41 | 15.92 | 6.62 | 0.560029E+09 | 1026.61 | 14-FEB-14:09 | 15.92 | 6.62 |
March | 0.105904E+11 | 27208.08 | 12-MAR-14:31 | 19.27 | 6.21 | 0.662783E+09 | 901.92 | 24-MAR-13:39 | 17.93 | 6.31 |
April | 0.992765E+10 | 25093.98 | 30-APR-13:32 | 21.33 | 7.45 | 0.597895E+09 | 847.06 | 17-APR-13:00 | 21.33 | 7.45 |
May | 0.881000E+10 | 23530.43 | 21-MAY-13:02 | 26.88 | 12.21 | 0.653675E+09 | 845.68 | 09-MAY-13:20 | 26.88 | 12.21 |
June | 0.104442E+11 | 23606.21 | 25-JUN-14:21 | 34.15 | 16.76 | 0.659026E+09 | 845.67 | 30-JUN-13:39 | 29.47 | 17.83 |
July | 0.123047E+11 | 25274.12 | 30-JUL-15:11 | 33.50 | 17.79 | 0.615913E+09 | 846.22 | 25-JUL-13:39 | 33.50 | 17.79 |
August | 0.148511E+11 | 25983.37 | 20-AUG-14:41 | 34.90 | 15.87 | 0.691285E+09 | 883.39 | 31-AUG-13:09 | 29.50 | 15.73 |
September | 0.151235E+11 | 28148.49 | 10-SEP-13:31 | 26.83 | 14.74 | 0.620784E+09 | 1037.70 | 28-SEP-13:39 | 29.63 | 15.09 |
October | 0.157098E+11 | 30574.16 | 01-OCT-12:51 | 27.20 | 14.12 | 0.648887E+09 | 1059.00 | 31-OCT-13:39 | 21.87 | 8.72 |
November | 0.130331E+11 | 28712.08 | 19-NOV-11:31 | 8.87 | 1.47 | 0.634444E+09 | 1046.98 | 01-NOV-13:20 | 8.87 | 1.47 |
December | 0.121596E+11 | 27382.17 | 31-DEC-14:11 | 10.37 | 1.81 | 0.600352E+09 | 1006.68 | 29-DEC-14:09 | 10.37 | 1.81 |
Annual Sum or Average | 0.144535E+12 | 0.755421E+10 | ||||||||
Minimum of Months | 0.881000E+10 | 23530.43 | 8.17 | 1.47 | 0.560029E+09 | 845.67 | 8.87 | 1.47 | ||
Maximum of Months | 0.157098E+11 | 30574.16 | 34.90 | 17.79 | 0.691285E+09 | 1059.00 | 33.50 | 17.83 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.305029E+10 | 10045.68 | 26-JAN-16:30 | 10.30 | 1.40 | 0.332864E+09 | 544.93 | 06-JAN-14:00 | 10.30 | 1.40 |
February | 0.386627E+10 | 14618.71 | 15-FEB-16:30 | 16.95 | 6.18 | 0.310215E+09 | 544.93 | 23-FEB-14:50 | 8.72 | 1.88 |
March | 0.577076E+10 | 29026.30 | 12-MAR-16:31 | 20.20 | 6.28 | 0.389208E+09 | 544.94 | 17-MAR-13:00 | 16.10 | 5.42 |
April | 0.807901E+10 | 33651.74 | 16-APR-17:01 | 20.40 | 8.05 | 0.372710E+09 | 544.97 | 17-APR-13:00 | 24.40 | 9.80 |
May | 0.921904E+10 | 33188.60 | 29-MAY-16:31 | 26.47 | 13.23 | 0.413844E+09 | 544.98 | 16-MAY-13:00 | 26.47 | 13.23 |
June | 0.117663E+11 | 35442.54 | 25-JUN-17:01 | 33.22 | 14.65 | 0.422608E+09 | 544.97 | 30-JUN-13:00 | 26.70 | 17.72 |
July | 0.121353E+11 | 36322.44 | 04-JUL-16:51 | 36.10 | 14.82 | 0.396197E+09 | 544.96 | 18-JUL-09:39 | 25.37 | 17.15 |
August | 0.121905E+11 | 35055.98 | 20-AUG-16:01 | 34.90 | 15.92 | 0.443917E+09 | 545.01 | 28-AUG-13:30 | 23.30 | 16.30 |
September | 0.923294E+10 | 31858.94 | 04-SEP-16:51 | 26.70 | 16.12 | 0.387792E+09 | 544.95 | 19-SEP-13:09 | 25.18 | 14.10 |
October | 0.728902E+10 | 31535.05 | 01-OCT-15:31 | 28.70 | 13.14 | 0.373194E+09 | 544.96 | 04-OCT-13:50 | 25.32 | 13.57 |
November | 0.447757E+10 | 18537.14 | 12-NOV-15:41 | 9.40 | 2.60 | 0.348048E+09 | 544.94 | 14-NOV-14:00 | 12.20 | 4.12 |
December | 0.298276E+10 | 8478.84 | 29-DEC-16:00 | 11.70 | 3.88 | 0.321508E+09 | 544.94 | 20-DEC-14:50 | 11.70 | 3.88 |
Annual Sum or Average | 0.900597E+11 | 0.451210E+10 | ||||||||
Minimum of Months | 0.298276E+10 | 8478.84 | 9.40 | 1.40 | 0.310215E+09 | 544.93 | 8.72 | 1.40 | ||
Maximum of Months | 0.121905E+11 | 36322.44 | 36.10 | 16.12 | 0.443917E+09 | 545.01 | 26.70 | 17.72 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.834025E+09 | 2749.94 | 05-JAN-15:30 | 16.10 | 6.84 | 0.474335E+09 | 720.95 | 24-JAN-14:00 | 16.10 | 4.97 |
February | 0.118354E+10 | 3191.28 | 15-FEB-16:00 | 17.20 | 6.50 | 0.443906E+09 | 813.63 | 15-FEB-14:00 | 17.20 | 6.50 |
March | 0.257286E+10 | 4149.66 | 16-MAR-14:50 | 20.10 | 8.53 | 0.587233E+09 | 845.62 | 28-MAR-13:50 | 15.28 | 7.39 |
April | 0.434336E+10 | 8509.85 | 14-APR-14:30 | 23.60 | 10.45 | 0.571694E+09 | 845.63 | 17-APR-13:00 | 24.40 | 9.80 |
May | 0.660002E+10 | 16884.36 | 29-MAY-16:41 | 26.28 | 13.29 | 0.646760E+09 | 845.64 | 31-MAY-13:20 | 26.50 | 11.57 |
June | 0.105414E+11 | 20921.82 | 11-JUN-18:41 | 25.47 | 12.13 | 0.659489E+09 | 857.19 | 28-JUN-13:00 | 37.80 | 14.11 |
July | 0.115989E+11 | 22421.48 | 04-JUL-16:51 | 36.10 | 14.82 | 0.615924E+09 | 845.64 | 18-JUL-09:50 | 25.73 | 17.29 |
August | 0.106454E+11 | 21765.84 | 20-AUG-16:01 | 34.90 | 15.92 | 0.689490E+09 | 845.71 | 28-AUG-13:30 | 23.30 | 16.30 |
September | 0.675660E+10 | 20454.92 | 04-SEP-16:11 | 26.70 | 16.39 | 0.602908E+09 | 845.65 | 13-SEP-13:30 | 26.40 | 14.44 |
October | 0.376673E+10 | 8565.60 | 02-OCT-13:40 | 26.33 | 15.37 | 0.567778E+09 | 845.63 | 02-OCT-13:30 | 26.33 | 15.37 |
November | 0.171563E+10 | 3147.10 | 02-NOV-15:30 | 16.95 | 9.55 | 0.500565E+09 | 831.11 | 03-NOV-13:00 | 12.20 | 2.42 |
December | 0.580727E+09 | 2570.65 | 29-DEC-15:40 | 11.50 | 3.90 | 0.451995E+09 | 743.27 | 01-DEC-14:00 | 11.50 | 3.90 |
Annual Sum or Average | 0.611392E+11 | 0.681208E+10 | ||||||||
Minimum of Months | 0.580727E+09 | 2570.65 | 11.50 | 3.90 | 0.443906E+09 | 720.95 | 11.50 | 2.42 | ||
Maximum of Months | 0.115989E+11 | 22421.48 | 36.10 | 16.39 | 0.689490E+09 | 857.19 | 37.80 | 17.29 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.185002E+10 | 4108.44 | 27-JAN-10:00 | 2.80 | -2.5 | 0.323857E+09 | 544.95 | 27-JAN-10:09 | 3.35 | -2.2 |
February | 0.243485E+10 | 8231.33 | 14-FEB-09:50 | 9.45 | 2.98 | 0.311947E+09 | 544.95 | 09-FEB-10:09 | 9.45 | 2.98 |
March | 0.481447E+10 | 17460.82 | 12-MAR-09:52 | 11.10 | 2.35 | 0.410208E+09 | 544.95 | 13-MAR-09:09 | 9.37 | 2.32 |
April | 0.818157E+10 | 27073.41 | 30-APR-09:01 | 15.78 | 4.89 | 0.389490E+09 | 546.06 | 28-APR-09:00 | 15.78 | 4.89 |
May | 0.992187E+10 | 31199.12 | 29-MAY-08:41 | 17.93 | 12.73 | 0.423835E+09 | 546.14 | 19-MAY-09:00 | 17.93 | 12.73 |
June | 0.130384E+11 | 28841.04 | 18-JUN-08:21 | 24.20 | 11.76 | 0.425681E+09 | 547.91 | 28-JUN-13:00 | 37.80 | 14.11 |
July | 0.136436E+11 | 33200.22 | 04-JUL-08:51 | 26.70 | 18.67 | 0.397486E+09 | 546.56 | 06-JUL-09:39 | 28.67 | 16.27 |
August | 0.132018E+11 | 32897.57 | 20-AUG-08:41 | 25.82 | 15.35 | 0.444927E+09 | 546.13 | 15-AUG-09:00 | 25.82 | 15.35 |
September | 0.939342E+10 | 28093.27 | 03-SEP-09:01 | 25.97 | 15.10 | 0.391192E+09 | 546.20 | 13-SEP-09:50 | 23.62 | 14.11 |
October | 0.610489E+10 | 25784.21 | 01-OCT-09:02 | 18.35 | 11.47 | 0.387890E+09 | 544.97 | 05-OCT-13:39 | 26.33 | 12.76 |
November | 0.306281E+10 | 9673.49 | 01-NOV-09:10 | 10.47 | 6.68 | 0.351373E+09 | 544.95 | 01-NOV-09:09 | 10.47 | 6.68 |
December | 0.178624E+10 | 3873.58 | 29-DEC-09:40 | 2.23 | -0.6 | 0.306642E+09 | 544.94 | 29-DEC-10:30 | 4.20 | 0.70 |
Annual Sum or Average | 0.874340E+11 | 0.456453E+10 | ||||||||
Minimum of Months | 0.178624E+10 | 3873.58 | 2.23 | -2.5 | 0.306642E+09 | 544.94 | 3.35 | -2.2 | ||
Maximum of Months | 0.136436E+11 | 33200.22 | 26.70 | 18.67 | 0.444927E+09 | 547.91 | 37.80 | 16.27 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.931371E+10 | 29657.09 | 08-JAN-14:01 | 12.80 | 4.25 | 0.584260E+09 | 945.22 | 26-JAN-14:20 | 10.20 | 1.54 |
February | 0.940880E+10 | 27723.14 | 12-FEB-14:12 | 17.57 | 5.95 | 0.540061E+09 | 973.94 | 14-FEB-14:20 | 20.97 | 7.09 |
March | 0.951187E+10 | 28988.70 | 12-MAR-14:31 | 19.27 | 6.21 | 0.642199E+09 | 865.37 | 08-MAR-14:09 | 19.27 | 6.21 |
April | 0.945197E+10 | 22938.18 | 30-APR-13:42 | 21.52 | 7.52 | 0.585937E+09 | 847.29 | 17-APR-13:00 | 21.52 | 7.52 |
May | 0.881768E+10 | 25204.34 | 29-MAY-16:01 | 27.02 | 13.03 | 0.644646E+09 | 845.68 | 08-MAY-13:30 | 27.02 | 13.03 |
June | 0.109459E+11 | 25149.33 | 25-JUN-16:31 | 34.07 | 14.58 | 0.655829E+09 | 851.43 | 28-JUN-13:00 | 37.80 | 14.11 |
July | 0.131400E+11 | 28035.42 | 04-JUL-14:51 | 35.60 | 14.20 | 0.615383E+09 | 845.66 | 18-JUL-09:50 | 25.73 | 17.29 |
August | 0.155205E+11 | 29236.96 | 20-AUG-14:41 | 34.90 | 15.87 | 0.689769E+09 | 864.43 | 31-AUG-13:09 | 29.50 | 15.73 |
September | 0.152778E+11 | 29213.79 | 03-SEP-13:01 | 31.38 | 16.74 | 0.613165E+09 | 1005.51 | 28-SEP-13:39 | 29.63 | 15.09 |
October | 0.149972E+11 | 32067.29 | 09-OCT-13:21 | 21.15 | 10.57 | 0.627905E+09 | 1005.78 | 31-OCT-13:00 | 22.80 | 8.86 |
November | 0.114167E+11 | 28372.91 | 12-NOV-13:31 | 8.53 | 2.42 | 0.609965E+09 | 993.90 | 01-NOV-13:20 | 8.53 | 2.42 |
December | 0.104842E+11 | 31964.83 | 31-DEC-13:51 | 10.00 | 1.60 | 0.573809E+09 | 938.98 | 29-DEC-14:09 | 10.00 | 1.60 |
Annual Sum or Average | 0.138286E+12 | 0.738293E+10 | ||||||||
Minimum of Months | 0.881768E+10 | 22938.18 | 8.53 | 1.60 | 0.540061E+09 | 845.66 | 8.53 | 1.54 | ||
Maximum of Months | 0.155205E+11 | 32067.29 | 35.60 | 16.74 | 0.689769E+09 | 1005.78 | 37.80 | 17.29 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.236182E+10 | 9517.32 | 26-JAN-16:30 | 10.30 | 1.40 | 0.327101E+09 | 544.84 | 26-JAN-14:00 | 10.30 | 1.40 |
February | 0.324510E+10 | 14552.80 | 15-FEB-16:30 | 16.95 | 6.18 | 0.304857E+09 | 544.92 | 15-FEB-14:00 | 16.95 | 6.18 |
March | 0.522545E+10 | 30142.20 | 12-MAR-16:31 | 20.20 | 6.28 | 0.376829E+09 | 544.93 | 09-MAR-14:39 | 20.20 | 6.28 |
April | 0.778098E+10 | 35186.21 | 16-APR-17:01 | 20.40 | 8.05 | 0.362972E+09 | 544.97 | 17-APR-13:00 | 24.40 | 9.80 |
May | 0.925642E+10 | 34314.12 | 07-MAY-15:51 | 24.40 | 8.93 | 0.406043E+09 | 544.97 | 08-MAY-13:30 | 25.85 | 9.73 |
June | 0.121149E+11 | 37525.43 | 11-JUN-16:41 | 28.22 | 13.16 | 0.419745E+09 | 551.16 | 27-JUN-15:00 | 37.80 | 15.32 |
July | 0.126930E+11 | 39134.94 | 04-JUL-16:51 | 36.10 | 14.82 | 0.395501E+09 | 544.96 | 18-JUL-09:50 | 25.73 | 17.29 |
August | 0.126425E+11 | 37899.08 | 20-AUG-16:01 | 34.90 | 15.92 | 0.442185E+09 | 545.01 | 28-AUG-13:30 | 23.30 | 16.30 |
September | 0.933813E+10 | 34888.81 | 24-SEP-16:11 | 25.40 | 15.61 | 0.382420E+09 | 544.99 | 13-SEP-13:30 | 25.40 | 15.61 |
October | 0.685855E+10 | 32643.76 | 15-OCT-16:01 | 20.60 | 7.82 | 0.363354E+09 | 544.97 | 05-OCT-13:39 | 20.60 | 7.82 |
November | 0.377265E+10 | 12148.62 | 02-NOV-15:50 | 16.78 | 9.71 | 0.338315E+09 | 544.94 | 14-NOV-14:00 | 12.20 | 4.12 |
December | 0.225315E+10 | 8091.53 | 29-DEC-16:00 | 11.70 | 3.88 | 0.316248E+09 | 544.87 | 20-DEC-14:00 | 11.70 | 3.88 |
Annual Sum or Average | 0.875427E+11 | 0.443557E+10 | ||||||||
Minimum of Months | 0.225315E+10 | 8091.53 | 10.30 | 1.40 | 0.304857E+09 | 544.84 | 10.30 | 1.40 | ||
Maximum of Months | 0.126930E+11 | 39134.94 | 36.10 | 15.92 | 0.442185E+09 | 551.16 | 37.80 | 17.29 |
Report: ZoneCoolingSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.214039E+10 | 5276.29 | 03-JAN-06:07 | -1.7 | -3.0 | 0.00 | 0.00 | 01-JAN-00:10 | -1.7 | -3.0 |
February | 0.257343E+10 | 7197.87 | 06-FEB-06:01 | -4.6 | -7.0 | 0.00 | 0.00 | 01-FEB-00:10 | -4.6 | -7.0 |
March | 0.489603E+10 | 6193.01 | 27-MAR-05:15 | 5.40 | 0.66 | 0.00 | 0.00 | 01-MAR-00:10 | 5.40 | 0.66 |
April | 0.715141E+10 | 7976.54 | 28-APR-14:50 | 24.90 | 10.40 | 0.00 | 0.00 | 01-APR-00:10 | 24.90 | 10.40 |
May | 0.761800E+10 | 9991.16 | 30-MAY-05:03 | 14.72 | 10.93 | 0.00 | 0.00 | 01-MAY-00:10 | 14.72 | 10.93 |
June | 0.102262E+11 | 10805.25 | 26-JUN-05:02 | 15.73 | 10.17 | 0.00 | 0.00 | 01-JUN-00:10 | 15.73 | 10.17 |
July | 0.114981E+11 | 11199.51 | 05-JUL-14:50 | 33.22 | 17.14 | 0.00 | 0.00 | 01-JUL-00:10 | 33.22 | 17.14 |
August | 0.123644E+11 | 12326.43 | 21-AUG-05:10 | 21.60 | 15.49 | 0.00 | 0.00 | 01-AUG-00:10 | 21.60 | 15.49 |
September | 0.861278E+10 | 10345.18 | 05-SEP-10:30 | 20.25 | 16.29 | 0.00 | 0.00 | 01-SEP-00:10 | 20.25 | 16.29 |
October | 0.677277E+10 | 10359.43 | 02-OCT-05:15 | 17.03 | 12.72 | 0.00 | 0.00 | 01-OCT-00:10 | 17.03 | 12.72 |
November | 0.443681E+10 | 6133.09 | 01-NOV-16:00 | 10.60 | 6.24 | 0.00 | 0.00 | 01-NOV-00:10 | 10.60 | 6.24 |
December | 0.290829E+10 | 4383.73 | 28-DEC-06:06 | -2.6 | -3.9 | 0.00 | 0.00 | 01-DEC-00:10 | -2.6 | -3.9 |
Annual Sum or Average | 0.811986E+11 | 0.00 | ||||||||
Minimum of Months | 0.214039E+10 | 4383.73 | -4.6 | -7.0 | 0.00 | 0.00 | -4.6 | -7.0 | ||
Maximum of Months | 0.123644E+11 | 12326.43 | 33.22 | 17.14 | 0.00 | 0.00 | 33.22 | 17.14 |
Report: ZoneCoolingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.742333E+09 | 11714.41 | 17-JAN-04:01 | -3.3 | -5.0 | 0.00 | 0.00 | 01-JAN-00:10 | -3.3 | -5.0 |
February | 0.952188E+09 | 11258.90 | 06-FEB-04:01 | -4.4 | -7.0 | 0.00 | 0.00 | 01-FEB-00:10 | -4.4 | -7.0 |
March | 0.197704E+10 | 9878.83 | 04-MAR-05:01 | -1.2 | -4.0 | 0.00 | 0.00 | 01-MAR-00:10 | -1.2 | -4.0 |
April | 0.392237E+10 | 6089.27 | 28-APR-15:00 | 25.00 | 10.42 | 0.00 | 0.00 | 01-APR-00:10 | 25.00 | 10.42 |
May | 0.555751E+10 | 6630.02 | 16-MAY-05:13 | 12.20 | 3.40 | 0.00 | 0.00 | 01-MAY-00:10 | 12.20 | 3.40 |
June | 0.813708E+10 | 8866.22 | 29-JUN-14:50 | 37.62 | 15.74 | 0.00 | 0.00 | 01-JUN-00:10 | 37.62 | 15.74 |
July | 0.929385E+10 | 11565.64 | 05-JUL-05:02 | 22.20 | 13.64 | 0.00 | 0.00 | 01-JUL-00:10 | 22.20 | 13.64 |
August | 0.945276E+10 | 9340.06 | 14-AUG-05:02 | 18.90 | 16.68 | 0.00 | 0.00 | 01-AUG-00:10 | 18.90 | 16.68 |
September | 0.669042E+10 | 8059.73 | 05-SEP-15:00 | 24.40 | 17.62 | 0.00 | 0.00 | 01-SEP-00:10 | 24.40 | 17.62 |
October | 0.417065E+10 | 7339.74 | 02-OCT-16:00 | 23.90 | 14.76 | 0.00 | 0.00 | 01-OCT-00:10 | 23.90 | 14.76 |
November | 0.171478E+10 | 9856.57 | 27-NOV-05:01 | -4.0 | -6.5 | 0.00 | 0.00 | 01-NOV-00:10 | -4.0 | -6.5 |
December | 0.749325E+09 | 10249.12 | 23-DEC-05:01 | -5.1 | -7.6 | 0.00 | 0.00 | 01-DEC-00:10 | -5.1 | -7.6 |
Annual Sum or Average | 0.533603E+11 | 0.00 | ||||||||
Minimum of Months | 0.742333E+09 | 6089.27 | -5.1 | -7.6 | 0.00 | 0.00 | -5.1 | -7.6 | ||
Maximum of Months | 0.945276E+10 | 11714.41 | 37.62 | 17.62 | 0.00 | 0.00 | 37.62 | 17.62 |
Report: ZoneCoolingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.490225E+09 | 3946.02 | 05-JAN-15:50 | 16.10 | 6.84 | 0.00 | 0.00 | 01-JAN-00:10 | 16.10 | 6.84 |
February | 0.128853E+10 | 8223.74 | 15-FEB-15:30 | 17.20 | 6.59 | 0.00 | 0.00 | 01-FEB-00:10 | 17.20 | 6.59 |
March | 0.352627E+10 | 11374.57 | 08-MAR-15:00 | 22.20 | 9.10 | 0.00 | 0.00 | 01-MAR-00:10 | 22.20 | 9.10 |
April | 0.762065E+10 | 17622.94 | 28-APR-14:40 | 24.80 | 10.38 | 0.00 | 0.00 | 01-APR-00:10 | 24.80 | 10.38 |
May | 0.104403E+11 | 20228.61 | 30-MAY-14:30 | 27.20 | 12.25 | 0.00 | 0.00 | 01-MAY-00:10 | 27.20 | 12.25 |
June | 0.156747E+11 | 25568.18 | 28-JUN-13:40 | 37.60 | 14.03 | 0.00 | 0.00 | 01-JUN-00:10 | 37.60 | 14.03 |
July | 0.177760E+11 | 24415.54 | 21-JUL-14:00 | 37.80 | 15.31 | 0.00 | 0.00 | 01-JUL-00:10 | 37.80 | 15.31 |
August | 0.170662E+11 | 23335.38 | 07-AUG-14:20 | 33.13 | 15.81 | 0.00 | 0.00 | 01-AUG-00:10 | 33.13 | 15.81 |
September | 0.110580E+11 | 18556.65 | 01-SEP-15:00 | 28.90 | 16.64 | 0.00 | 0.00 | 01-SEP-00:10 | 28.90 | 16.64 |
October | 0.568467E+10 | 14540.13 | 05-OCT-14:40 | 26.70 | 12.37 | 0.00 | 0.00 | 01-OCT-00:10 | 26.70 | 12.37 |
November | 0.145582E+10 | 7145.24 | 02-NOV-15:00 | 17.20 | 9.31 | 0.00 | 0.00 | 01-NOV-00:10 | 17.20 | 9.31 |
December | 0.267065E+09 | 3220.99 | 31-DEC-14:34 | 10.73 | 2.01 | 0.00 | 0.00 | 01-DEC-00:10 | 10.73 | 2.01 |
Annual Sum or Average | 0.923484E+11 | 0.00 | ||||||||
Minimum of Months | 0.267065E+09 | 3220.99 | 10.73 | 2.01 | 0.00 | 0.00 | 10.73 | 2.01 | ||
Maximum of Months | 0.177760E+11 | 25568.18 | 37.80 | 16.64 | 0.00 | 0.00 | 37.80 | 16.64 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.348151E+10 | 2805.44 | 26-JAN-17:00 | 10.00 | 1.21 | 95230022.01 | 126.82 | 31-JAN-14:09 | 5.40 | -1.5 |
February | 0.811843E+10 | 4772.59 | 15-FEB-17:00 | 16.70 | 5.85 | 86396696.77 | 126.83 | 17-FEB-10:00 | 7.20 | 4.72 |
March | 0.145206E+11 | 7127.52 | 31-MAR-24:00 | 6.90 | 3.36 | 0.103236E+09 | 126.83 | 29-MAR-09:50 | 6.90 | 3.36 |
April | 0.192433E+11 | 8637.07 | 16-APR-18:20 | 19.03 | 7.42 | 91622634.93 | 126.82 | 20-APR-09:00 | 12.20 | 5.87 |
May | 0.472418E+10 | 3533.09 | 31-MAY-24:00 | 18.60 | 7.93 | 99235852.40 | 126.86 | 24-MAY-13:00 | 18.60 | 7.93 |
June | 0.966964E+10 | 5378.03 | 30-JUN-23:23 | 22.60 | 14.29 | 98961881.21 | 126.86 | 08-JUN-13:09 | 22.60 | 14.29 |
July | 0.150325E+11 | 7280.08 | 31-JUL-23:55 | 21.00 | 17.53 | 91885568.52 | 126.84 | 17-JUL-09:09 | 21.00 | 17.53 |
August | 0.201607E+11 | 8197.77 | 30-AUG-17:40 | 28.50 | 14.73 | 0.103837E+09 | 130.98 | 17-AUG-13:00 | 28.50 | 14.73 |
September | 0.471029E+10 | 3520.26 | 30-SEP-24:00 | 17.40 | 10.77 | 91613921.36 | 126.86 | 07-SEP-09:30 | 17.40 | 10.77 |
October | 0.970564E+10 | 5329.20 | 31-OCT-24:00 | 13.00 | 4.55 | 95233103.66 | 126.85 | 03-OCT-09:09 | 13.00 | 4.55 |
November | 0.139820E+11 | 6691.69 | 06-NOV-16:50 | 14.40 | 4.28 | 94300827.05 | 126.83 | 02-NOV-09:50 | 14.40 | 4.28 |
December | 0.192406E+11 | 8415.24 | 29-DEC-16:40 | 10.57 | 3.30 | 91880712.09 | 126.82 | 08-DEC-14:09 | 10.57 | 3.30 |
Annual Sum or Average | 0.142589E+12 | 0.114343E+10 | ||||||||
Minimum of Months | 0.348151E+10 | 2805.44 | 6.90 | 1.21 | 86396696.77 | 126.82 | 5.40 | -1.5 | ||
Maximum of Months | 0.201607E+11 | 8637.07 | 28.50 | 17.53 | 0.103837E+09 | 130.98 | 28.50 | 17.53 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.176214E+10 | 2608.58 | 26-JAN-17:00 | 10.00 | 1.21 | 95229447.44 | 126.82 | 20-JAN-14:00 | 10.00 | 1.21 |
February | 0.646999E+10 | 4531.00 | 15-FEB-17:00 | 16.70 | 5.85 | 86396703.12 | 126.83 | 17-FEB-10:00 | 7.20 | 4.72 |
March | 0.128669E+11 | 6552.52 | 31-MAR-23:30 | 6.60 | 3.23 | 0.103236E+09 | 126.83 | 15-MAR-09:00 | 6.60 | 3.23 |
April | 0.178534E+11 | 8232.66 | 16-APR-18:00 | 19.40 | 7.60 | 91617135.39 | 126.82 | 20-APR-09:00 | 12.20 | 5.87 |
May | 0.409940E+10 | 3340.12 | 31-MAY-24:00 | 18.60 | 7.93 | 99235218.86 | 126.85 | 24-MAY-09:00 | 18.60 | 7.93 |
June | 0.905503E+10 | 5194.36 | 30-JUN-23:57 | 22.10 | 13.89 | 98962004.97 | 126.85 | 08-JUN-13:09 | 22.10 | 13.89 |
July | 0.143039E+11 | 7005.84 | 31-JUL-23:55 | 21.00 | 17.53 | 91886379.67 | 126.84 | 17-JUL-09:09 | 21.00 | 17.53 |
August | 0.190965E+11 | 7859.95 | 30-AUG-17:40 | 28.50 | 14.73 | 0.103538E+09 | 128.74 | 17-AUG-13:00 | 28.50 | 14.73 |
September | 0.416011E+10 | 3291.75 | 30-SEP-24:00 | 17.40 | 10.77 | 91612571.23 | 126.85 | 06-SEP-13:50 | 17.40 | 10.77 |
October | 0.853541E+10 | 4854.76 | 31-OCT-24:00 | 13.00 | 4.55 | 95233046.48 | 126.85 | 03-OCT-09:30 | 13.00 | 4.55 |
November | 0.120819E+11 | 6244.15 | 02-NOV-16:50 | 16.20 | 9.61 | 94300836.24 | 126.83 | 02-NOV-09:50 | 16.20 | 9.61 |
December | 0.165641E+11 | 7853.14 | 29-DEC-16:50 | 10.28 | 3.14 | 91880766.09 | 126.82 | 08-DEC-14:09 | 10.28 | 3.14 |
Annual Sum or Average | 0.126849E+12 | 0.114313E+10 | ||||||||
Minimum of Months | 0.176214E+10 | 2608.58 | 6.60 | 1.21 | 86396703.12 | 126.82 | 6.60 | 1.21 | ||
Maximum of Months | 0.190965E+11 | 8232.66 | 28.50 | 17.53 | 0.103538E+09 | 128.74 | 28.50 | 17.53 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.911529E+09 | 2534.09 | 26-JAN-17:00 | 10.00 | 1.21 | 94448201.33 | 126.82 | 04-JAN-10:09 | 10.00 | 1.21 |
February | 0.514978E+10 | 4563.30 | 15-FEB-17:00 | 16.70 | 5.85 | 86396703.61 | 126.83 | 17-FEB-10:00 | 7.20 | 4.72 |
March | 0.119005E+11 | 6379.37 | 24-MAR-17:50 | 16.47 | 5.22 | 0.103236E+09 | 126.83 | 29-MAR-09:39 | 9.27 | 4.61 |
April | 0.173912E+11 | 8219.79 | 16-APR-17:53 | 19.40 | 7.60 | 91612551.53 | 126.82 | 20-APR-09:00 | 12.20 | 5.87 |
May | 0.387104E+10 | 3274.42 | 31-MAY-23:40 | 18.93 | 8.15 | 99235065.76 | 126.84 | 23-MAY-13:50 | 18.93 | 8.15 |
June | 0.903184E+10 | 5184.35 | 30-JUN-23:57 | 22.10 | 13.89 | 98961950.77 | 126.86 | 08-JUN-13:09 | 22.10 | 13.89 |
July | 0.144042E+11 | 7178.00 | 04-JUL-18:40 | 32.77 | 13.53 | 91886260.25 | 126.84 | 17-JUL-09:09 | 22.77 | 17.51 |
August | 0.191500E+11 | 7994.15 | 30-AUG-17:40 | 28.50 | 14.73 | 0.103480E+09 | 128.21 | 17-AUG-13:00 | 28.50 | 14.73 |
September | 0.401528E+10 | 3237.19 | 30-SEP-23:40 | 17.50 | 10.08 | 91612280.94 | 126.85 | 06-SEP-13:39 | 17.50 | 10.08 |
October | 0.785078E+10 | 4675.98 | 04-OCT-17:00 | 26.10 | 12.23 | 95233001.26 | 126.85 | 03-OCT-09:30 | 26.10 | 12.23 |
November | 0.107349E+11 | 6236.40 | 02-NOV-16:50 | 16.20 | 9.61 | 94300850.39 | 126.83 | 02-NOV-09:50 | 16.20 | 9.61 |
December | 0.147174E+11 | 7794.01 | 29-DEC-16:50 | 10.28 | 3.14 | 91880788.11 | 126.82 | 08-DEC-14:09 | 10.28 | 3.14 |
Annual Sum or Average | 0.119129E+12 | 0.114228E+10 | ||||||||
Minimum of Months | 0.911529E+09 | 2534.09 | 10.00 | 1.21 | 86396703.61 | 126.82 | 7.20 | 1.21 | ||
Maximum of Months | 0.191500E+11 | 8219.79 | 32.77 | 14.73 | 0.103480E+09 | 128.21 | 28.50 | 17.51 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.239704E+12 | 93184.59 | 03-JAN-17:00 | 12.20 | 4.64 | 0.206154E+10 | 2745.50 | 10-JAN-14:20 | 9.23 | 2.60 |
February | 0.437335E+12 | 185081.98 | 15-FEB-17:00 | 16.70 | 5.85 | 0.187031E+10 | 2745.82 | 22-FEB-14:09 | 8.90 | 2.93 |
March | 0.731093E+12 | 359531.90 | 31-MAR-24:00 | 6.90 | 3.36 | 0.223482E+10 | 2745.71 | 15-MAR-13:00 | 6.90 | 3.36 |
April | 0.945432E+12 | 369665.39 | 29-APR-17:31 | 24.27 | 9.18 | 0.198861E+10 | 2924.00 | 26-APR-13:00 | 24.27 | 9.18 |
May | 0.242916E+12 | 176788.74 | 31-MAY-24:00 | 18.60 | 7.93 | 0.214825E+10 | 2747.47 | 22-MAY-13:09 | 18.60 | 7.93 |
June | 0.472830E+12 | 268544.76 | 30-JUN-23:57 | 22.10 | 13.89 | 0.214307E+10 | 2749.89 | 02-JUN-13:00 | 22.10 | 13.89 |
July | 0.734756E+12 | 357729.06 | 31-JUL-23:08 | 21.17 | 17.10 | 0.199166E+10 | 2840.41 | 10-JUL-13:20 | 21.17 | 17.10 |
August | 0.974723E+12 | 379081.92 | 04-AUG-20:03 | 27.28 | 14.39 | 0.267542E+10 | 4154.62 | 15-AUG-15:00 | 32.80 | 14.68 |
September | 0.238552E+12 | 177000.36 | 30-SEP-24:00 | 17.40 | 10.77 | 0.198345E+10 | 2747.61 | 11-SEP-13:00 | 17.40 | 10.77 |
October | 0.490191E+12 | 269460.55 | 31-OCT-24:00 | 13.00 | 4.55 | 0.206177E+10 | 2749.61 | 10-OCT-13:30 | 13.00 | 4.55 |
November | 0.710518E+12 | 277949.39 | 24-NOV-17:00 | 13.90 | 4.33 | 0.204141E+10 | 2746.84 | 09-NOV-10:00 | 13.90 | 4.33 |
December | 0.978221E+12 | 369329.29 | 29-DEC-17:00 | 10.00 | 2.99 | 0.198897E+10 | 2745.97 | 26-DEC-14:00 | 10.00 | 2.99 |
Annual Sum or Average | 0.719627E+13 | 0.251893E+11 | ||||||||
Minimum of Months | 0.238552E+12 | 93184.59 | 6.90 | 2.99 | 0.187031E+10 | 2745.50 | 6.90 | 2.60 | ||
Maximum of Months | 0.978221E+12 | 379081.92 | 27.28 | 17.10 | 0.267542E+10 | 4154.62 | 32.80 | 17.10 |
Report: ZoneHeatingSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.234333E+09 | 16127.22 | 01-JAN-07:53 | -1.7 |
February | 0.134621E+09 | 14668.12 | 15-FEB-05:15 | 7.60 |
March | 0.144159E+09 | 15198.97 | 27-MAR-04:45 | 5.50 |
April | 0.238766E+09 | 15169.22 | 10-APR-04:45 | 7.88 |
May | 0.334601E+09 | 15872.03 | 29-MAY-09:11 | 19.07 |
June | 0.338505E+09 | 21805.00 | 17-JUN-16:01 | 33.43 |
July | 0.527361E+09 | 24883.70 | 22-JUL-16:01 | 36.05 |
August | 0.415084E+09 | 19568.93 | 05-AUG-16:01 | 31.52 |
September | 0.396490E+09 | 18909.53 | 02-SEP-16:01 | 31.10 |
October | 0.344569E+09 | 15719.75 | 08-OCT-18:13 | 16.67 |
November | 0.297908E+09 | 16630.75 | 12-NOV-11:01 | 5.87 |
December | 0.231906E+09 | 15317.72 | 11-DEC-05:45 | 1.70 |
Annual Sum or Average | 0.363830E+10 | |||
Minimum of Months | 0.134621E+09 | 14668.12 | -1.7 | |
Maximum of Months | 0.527361E+09 | 24883.70 | 36.05 |
Report: ZoneHeatingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 2.30 |
February | 0.00 | 0.00 | 01-FEB-00:10 | -3.2 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 2.47 |
April | 0.00 | 0.00 | 01-APR-00:10 | 7.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 14.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.42 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 21.95 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 20.95 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 21.88 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 17.33 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 12.83 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 5.13 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | -3.2 | |
Maximum of Months | 0.00 | 0.00 | 21.95 |
Report: ZoneHeatingSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 2.30 |
February | 0.00 | 0.00 | 01-FEB-00:10 | -3.2 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 2.47 |
April | 0.00 | 0.00 | 01-APR-00:10 | 7.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 14.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.42 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 21.95 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 20.95 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 21.88 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 17.33 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 12.83 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 5.13 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | -3.2 | |
Maximum of Months | 0.00 | 0.00 | 21.95 |
Report: ZoneHeatingSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.134496E+10 | 79406.81 | 17-JAN-04:01 | -3.3 |
February | 0.474433E+09 | 78335.78 | 06-FEB-04:01 | -4.4 |
March | 27588265.89 | 68183.65 | 06-MAR-06:01 | -2.9 |
April | 0.00 | 0.00 | 01-APR-00:10 | 7.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 14.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.42 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 21.95 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 20.95 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 21.88 |
October | 1169366.58 | 7795.78 | 26-OCT-05:03 | -2.5 |
November | 0.272402E+09 | 74221.10 | 27-NOV-05:01 | -4.0 |
December | 0.105426E+10 | 79482.66 | 26-DEC-04:11 | 0.03 |
Annual Sum or Average | 0.317481E+10 | |||
Minimum of Months | 0.00 | 0.00 | -4.4 | |
Maximum of Months | 0.134496E+10 | 79482.66 | 21.95 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 15662693.32 | 10836.89 | 17-JAN-06:01 | -3.4 |
February | 11026559.35 | 10751.44 | 06-FEB-06:01 | -4.6 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 2.47 |
April | 0.00 | 0.00 | 01-APR-00:10 | 7.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 14.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.42 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 21.95 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 20.95 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 21.88 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 17.33 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 12.83 |
December | 1780029.58 | 5846.59 | 23-DEC-06:01 | -5.5 |
Annual Sum or Average | 28469282.25 | |||
Minimum of Months | 0.00 | 0.00 | -5.5 | |
Maximum of Months | 15662693.32 | 10836.89 | 21.95 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 20479898.98 | 8076.73 | 17-JAN-06:01 | -3.4 |
February | 12208003.60 | 7950.07 | 06-FEB-06:01 | -4.6 |
March | 328222.27 | 3931.75 | 04-MAR-06:01 | -1.7 |
April | 0.00 | 0.00 | 01-APR-00:10 | 7.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 14.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.42 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 21.95 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 20.95 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 21.88 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 17.33 |
November | 1254097.54 | 6003.18 | 28-NOV-06:01 | -2.1 |
December | 23792109.29 | 6347.74 | 13-DEC-06:01 | -6.9 |
Annual Sum or Average | 58062331.68 | |||
Minimum of Months | 0.00 | 0.00 | -6.9 | |
Maximum of Months | 23792109.29 | 8076.73 | 21.95 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 51256566.14 | 13029.15 | 17-JAN-06:01 | -3.4 |
February | 25697788.21 | 13433.93 | 06-FEB-05:01 | -4.4 |
March | 463528.47 | 5609.14 | 04-MAR-06:01 | -1.7 |
April | 0.00 | 0.00 | 01-APR-00:10 | 7.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 14.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.42 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 21.95 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 20.95 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 21.88 |
October | 153574.99 | 1023.83 | 26-OCT-05:03 | -2.5 |
November | 453456.39 | 3023.04 | 27-NOV-06:03 | -4.4 |
December | 17435857.13 | 11466.25 | 04-DEC-06:01 | -0.6 |
Annual Sum or Average | 95460771.33 | |||
Minimum of Months | 0.00 | 0.00 | -4.4 | |
Maximum of Months | 51256566.14 | 13433.93 | 21.95 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 615745.27 | 5641.38 | 17-JAN-06:01 | -3.4 |
February | 302376.61 | 5039.61 | 06-FEB-06:01 | -4.6 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 2.47 |
April | 0.00 | 0.00 | 01-APR-00:10 | 7.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 14.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.42 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 21.95 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 20.95 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 21.88 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 17.33 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 12.83 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 5.13 |
Annual Sum or Average | 918121.89 | |||
Minimum of Months | 0.00 | 0.00 | -4.6 | |
Maximum of Months | 615745.27 | 5641.38 | 21.95 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.135817E+10 | 15584.06 | 17-JAN-04:01 | -3.3 |
February | 0.831597E+09 | 15578.47 | 06-FEB-04:01 | -4.4 |
March | 0.174287E+09 | 13574.79 | 06-MAR-05:01 | -0.5 |
April | 6435267.41 | 12418.24 | 08-APR-05:03 | 2.62 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 14.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.42 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 21.95 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 20.95 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 21.88 |
October | 53125094.09 | 12653.76 | 27-OCT-05:02 | 0.50 |
November | 0.319361E+09 | 14347.14 | 27-NOV-05:01 | -4.0 |
December | 0.134711E+10 | 14416.87 | 14-DEC-04:01 | -1.4 |
Annual Sum or Average | 0.409008E+10 | |||
Minimum of Months | 0.00 | 0.00 | -4.4 | |
Maximum of Months | 0.135817E+10 | 15584.06 | 21.95 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.686043E+09 | 17206.07 | 17-JAN-04:01 | -3.3 |
February | 0.370168E+09 | 16981.73 | 06-FEB-04:01 | -4.4 |
March | 62476826.82 | 14453.02 | 04-MAR-05:01 | -1.2 |
April | 3053639.48 | 8179.73 | 08-APR-05:03 | 2.62 |
May | 20059.74 | 167.16 | 06-MAY-05:04 | 6.02 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.42 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 21.95 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 20.95 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 21.88 |
October | 31084132.96 | 11728.64 | 25-OCT-05:02 | -1.1 |
November | 0.119815E+09 | 15365.37 | 27-NOV-05:01 | -4.0 |
December | 0.634117E+09 | 15503.71 | 23-DEC-05:01 | -5.1 |
Annual Sum or Average | 0.190678E+10 | |||
Minimum of Months | 0.00 | 0.00 | -5.1 | |
Maximum of Months | 0.686043E+09 | 17206.07 | 21.95 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.487413E+09 | 19043.01 | 17-JAN-04:01 | -3.3 |
February | 0.280472E+09 | 18620.34 | 06-FEB-04:01 | -4.4 |
March | 38694281.63 | 16875.07 | 04-MAR-05:01 | -1.2 |
April | 2950070.18 | 8724.35 | 08-APR-05:03 | 2.62 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 14.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.42 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 21.95 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 20.95 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 21.88 |
October | 24479185.16 | 12067.31 | 26-OCT-05:03 | -2.5 |
November | 35164822.35 | 16218.68 | 27-NOV-05:01 | -4.0 |
December | 0.422402E+09 | 17851.45 | 26-DEC-05:01 | -1.0 |
Annual Sum or Average | 0.129158E+10 | |||
Minimum of Months | 0.00 | 0.00 | -4.4 | |
Maximum of Months | 0.487413E+09 | 19043.01 | 21.95 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.511298E+09 | 16435.60 | 17-JAN-04:01 | -3.3 |
February | 0.290699E+09 | 16244.31 | 06-FEB-04:01 | -4.4 |
March | 36058495.62 | 13811.11 | 04-MAR-05:01 | -1.2 |
April | 210995.68 | 931.78 | 08-APR-05:03 | 2.62 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 14.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.42 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 21.95 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 20.95 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 21.88 |
October | 19610312.71 | 8831.78 | 25-OCT-05:02 | -1.1 |
November | 65106821.52 | 14355.00 | 27-NOV-05:01 | -4.0 |
December | 0.445934E+09 | 14645.42 | 14-DEC-05:01 | -2.9 |
Annual Sum or Average | 0.136892E+10 | |||
Minimum of Months | 0.00 | 0.00 | -4.4 | |
Maximum of Months | 0.511298E+09 | 16435.60 | 21.95 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.424350E+10 | 18794.57 | 17-JAN-03:42 | -3.3 |
February | 0.268462E+10 | 18447.03 | 06-FEB-04:01 | -4.4 |
March | 0.102124E+10 | 16906.25 | 06-MAR-04:02 | 0.50 |
April | 0.155506E+09 | 15465.98 | 08-APR-04:12 | 2.80 |
May | 16086024.25 | 14254.63 | 05-MAY-05:02 | 5.68 |
June | 92028.02 | 613.52 | 09-JUN-05:03 | 7.98 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 21.95 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 20.95 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 21.88 |
October | 0.396077E+09 | 16117.09 | 26-OCT-04:11 | -2.8 |
November | 0.155006E+10 | 17356.93 | 27-NOV-04:01 | -3.9 |
December | 0.424431E+10 | 18015.30 | 26-DEC-04:11 | 0.03 |
Annual Sum or Average | 0.143115E+11 | |||
Minimum of Months | 0.00 | 0.00 | -4.4 | |
Maximum of Months | 0.424431E+10 | 18794.57 | 21.95 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.199462E+10 | 20892.28 | 17-JAN-03:42 | -3.3 |
February | 0.119093E+10 | 20814.80 | 06-FEB-04:01 | -4.4 |
March | 0.423207E+09 | 17407.21 | 04-MAR-05:01 | -1.2 |
April | 52420118.31 | 16763.36 | 08-APR-04:12 | 2.80 |
May | 7931037.88 | 10560.47 | 05-MAY-05:02 | 5.68 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.42 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 21.95 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 20.95 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 21.88 |
October | 0.186870E+09 | 17874.46 | 26-OCT-04:11 | -2.8 |
November | 0.609113E+09 | 19271.95 | 27-NOV-04:01 | -3.9 |
December | 0.191838E+10 | 20250.11 | 26-DEC-04:11 | 0.03 |
Annual Sum or Average | 0.638347E+10 | |||
Minimum of Months | 0.00 | 0.00 | -4.4 | |
Maximum of Months | 0.199462E+10 | 20892.28 | 21.95 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.193305E+10 | 22881.88 | 17-JAN-03:02 | -3.3 |
February | 0.122836E+10 | 22481.66 | 06-FEB-04:01 | -4.4 |
March | 0.531163E+09 | 19440.81 | 04-MAR-05:01 | -1.2 |
April | 98286839.15 | 18621.80 | 08-APR-04:12 | 2.80 |
May | 21831937.25 | 17457.80 | 05-MAY-05:02 | 5.68 |
June | 477216.50 | 3181.44 | 09-JUN-05:03 | 7.98 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 21.95 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 20.95 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 21.88 |
October | 0.193202E+09 | 19752.16 | 26-OCT-04:11 | -2.8 |
November | 0.478809E+09 | 20878.00 | 27-NOV-04:01 | -3.9 |
December | 0.178057E+10 | 22107.92 | 26-DEC-04:11 | 0.03 |
Annual Sum or Average | 0.626574E+10 | |||
Minimum of Months | 0.00 | 0.00 | -4.4 | |
Maximum of Months | 0.193305E+10 | 22881.88 | 21.95 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.161425E+10 | 20276.98 | 17-JAN-04:01 | -3.3 |
February | 0.991031E+09 | 21189.83 | 06-FEB-04:01 | -4.4 |
March | 0.346932E+09 | 17746.71 | 04-MAR-05:01 | -1.2 |
April | 29461330.63 | 8257.07 | 08-APR-05:03 | 2.62 |
May | 6775557.38 | 11155.13 | 05-MAY-05:02 | 5.68 |
June | 311095.02 | 1978.94 | 09-JUN-05:03 | 7.98 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 21.95 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 20.95 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 21.88 |
October | 0.135100E+09 | 17990.40 | 26-OCT-04:11 | -2.8 |
November | 0.481105E+09 | 19655.06 | 27-NOV-04:01 | -3.9 |
December | 0.146493E+10 | 20435.34 | 26-DEC-04:11 | 0.03 |
Annual Sum or Average | 0.506989E+10 | |||
Minimum of Months | 0.00 | 0.00 | -4.4 | |
Maximum of Months | 0.161425E+10 | 21189.83 | 21.95 |
Report: ZoneHeatingSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.177905E+09 | 10001.02 | 17-JAN-05:01 | -3.3 |
February | 0.113703E+09 | 10975.35 | 21-FEB-05:11 | 2.57 |
March | 0.113895E+09 | 13454.13 | 12-MAR-15:21 | 19.70 |
April | 0.124613E+09 | 11560.82 | 09-APR-14:51 | 18.90 |
May | 81985271.44 | 11795.77 | 14-MAY-15:31 | 28.30 |
June | 99430063.99 | 13651.92 | 25-JUN-15:41 | 35.32 |
July | 0.126647E+09 | 13738.49 | 30-JUL-16:01 | 33.62 |
August | 0.105779E+09 | 15788.21 | 20-AUG-15:31 | 35.00 |
September | 77253142.90 | 13294.60 | 03-SEP-13:31 | 32.23 |
October | 0.108239E+09 | 12882.25 | 15-OCT-15:02 | 21.02 |
November | 0.165075E+09 | 13530.24 | 19-NOV-15:01 | 14.90 |
December | 0.181566E+09 | 14065.81 | 31-DEC-14:41 | 10.92 |
Annual Sum or Average | 0.147609E+10 | |||
Minimum of Months | 77253142.90 | 10001.02 | -3.3 | |
Maximum of Months | 0.181566E+09 | 15788.21 | 35.32 |
Report: ZoneHeatingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.149598E+10 | 10732.71 | 01-JAN-14:31 | 15.93 |
February | 0.868879E+09 | 9068.90 | 12-FEB-16:32 | 17.57 |
March | 0.153098E+09 | 16159.09 | 05-MAR-16:01 | 14.40 |
April | 67495420.37 | 12252.63 | 09-APR-15:21 | 18.90 |
May | 74600607.21 | 12154.08 | 29-MAY-16:31 | 26.47 |
June | 82137833.28 | 14329.66 | 25-JUN-16:21 | 34.45 |
July | 99837146.63 | 14786.49 | 30-JUL-15:51 | 33.90 |
August | 74850244.29 | 14561.58 | 20-AUG-15:21 | 35.00 |
September | 70778856.75 | 11326.76 | 03-SEP-13:41 | 32.52 |
October | 0.110371E+09 | 13818.34 | 15-OCT-15:31 | 20.77 |
November | 0.383067E+09 | 11170.05 | 12-NOV-15:41 | 9.40 |
December | 0.121693E+10 | 9677.27 | 24-DEC-14:01 | 12.38 |
Annual Sum or Average | 0.469802E+10 | |||
Minimum of Months | 67495420.37 | 9068.90 | 9.40 | |
Maximum of Months | 0.149598E+10 | 16159.09 | 35.00 |
Report: ZoneHeatingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.603593E+10 | 26534.81 | 17-JAN-05:12 | -3.3 |
February | 0.379681E+10 | 26804.24 | 06-FEB-06:12 | -4.8 |
March | 0.217451E+10 | 11846.39 | 06-MAR-06:01 | -2.9 |
April | 0.793947E+09 | 14680.41 | 28-APR-05:03 | 11.93 |
May | 0.360350E+09 | 15745.94 | 12-MAY-05:03 | 9.60 |
June | 0.133258E+09 | 14462.24 | 20-JUN-05:03 | 12.77 |
July | 69806301.26 | 10897.97 | 05-JUL-04:11 | 22.20 |
August | 69938392.24 | 11493.56 | 30-AUG-05:02 | 15.50 |
September | 0.157219E+09 | 14166.57 | 27-SEP-05:03 | 11.60 |
October | 0.124739E+10 | 13999.47 | 04-OCT-05:03 | 12.80 |
November | 0.265516E+10 | 19550.95 | 27-NOV-06:03 | -4.4 |
December | 0.593467E+10 | 21162.29 | 26-DEC-05:13 | -0.9 |
Annual Sum or Average | 0.234290E+11 | |||
Minimum of Months | 69806301.26 | 10897.97 | -4.8 | |
Maximum of Months | 0.603593E+10 | 26804.24 | 22.20 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 2.30 |
February | 0.00 | 0.00 | 01-FEB-00:10 | -3.2 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 2.47 |
April | 0.00 | 0.00 | 01-APR-00:10 | 7.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 14.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.42 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 21.95 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 20.95 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 21.88 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 17.33 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 12.83 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 5.13 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | -3.2 | |
Maximum of Months | 0.00 | 0.00 | 21.95 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 34789780.90 | 569.45 | 17-JAN-04:13 | -3.3 |
February | 0.00 | 0.00 | 01-FEB-00:10 | -3.2 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 2.47 |
April | 0.00 | 0.00 | 01-APR-00:10 | 7.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 14.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.42 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 21.95 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 20.95 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 21.88 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 17.33 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 12.83 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 5.13 |
Annual Sum or Average | 34789780.90 | |||
Minimum of Months | 0.00 | 0.00 | -3.3 | |
Maximum of Months | 34789780.90 | 569.45 | 21.95 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.669669E+09 | 712.05 | 16-JAN-18:10 | -1.6 |
February | 4920681.05 | 358.48 | 06-FEB-04:13 | -4.4 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 2.47 |
April | 0.00 | 0.00 | 01-APR-00:10 | 7.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 14.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.42 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 21.95 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 20.95 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 21.88 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 17.33 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 12.83 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 5.13 |
Annual Sum or Average | 0.674590E+09 | |||
Minimum of Months | 0.00 | 0.00 | -4.4 | |
Maximum of Months | 0.669669E+09 | 712.05 | 21.95 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 2.30 |
February | 0.00 | 0.00 | 01-FEB-00:10 | -3.2 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 2.47 |
April | 0.00 | 0.00 | 01-APR-00:10 | 7.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 14.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.42 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 21.95 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 20.95 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 21.88 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 17.33 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 12.83 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 5.13 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | -3.2 | |
Maximum of Months | 0.00 | 0.00 | 21.95 |
Report: ZoneElectricSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.219312E+11 | 22950.34 | 02-JAN-08:09 | 0.360447E+11 | 13457.54 | 01-JAN-00:10 |
February | 0.198933E+11 | 22950.34 | 01-FEB-08:09 | 0.325565E+11 | 13457.54 | 01-FEB-00:10 |
March | 0.236388E+11 | 22950.34 | 01-MAR-08:09 | 0.360447E+11 | 13457.54 | 01-MAR-00:10 |
April | 0.211142E+11 | 22950.34 | 03-APR-07:10 | 0.348820E+11 | 13457.54 | 01-APR-00:10 |
May | 0.227850E+11 | 22950.34 | 01-MAY-07:10 | 0.360447E+11 | 13457.54 | 01-MAY-00:10 |
June | 0.226748E+11 | 22950.34 | 01-JUN-07:10 | 0.348820E+11 | 13457.54 | 01-JUN-00:10 |
July | 0.212244E+11 | 22950.34 | 03-JUL-07:10 | 0.360447E+11 | 13457.54 | 01-JUL-00:10 |
August | 0.236388E+11 | 22950.34 | 01-AUG-07:10 | 0.360447E+11 | 13457.54 | 01-AUG-00:10 |
September | 0.211142E+11 | 22950.34 | 01-SEP-07:10 | 0.348820E+11 | 13457.54 | 01-SEP-00:10 |
October | 0.219312E+11 | 22950.34 | 02-OCT-07:10 | 0.360447E+11 | 13457.54 | 01-OCT-00:10 |
November | 0.216742E+11 | 22950.34 | 01-NOV-07:10 | 0.348820E+11 | 13457.54 | 01-NOV-00:10 |
December | 0.212244E+11 | 22950.34 | 01-DEC-08:09 | 0.360447E+11 | 13457.54 | 01-DEC-00:10 |
Annual Sum or Average | 0.262844E+12 | 0.424397E+12 | ||||
Minimum of Months | 0.198933E+11 | 22950.34 | 0.325565E+11 | 13457.54 | ||
Maximum of Months | 0.236388E+11 | 22950.34 | 0.360447E+11 | 13457.54 |
Report: ZoneElectricSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.196958E+11 | 20611.01 | 02-JAN-08:09 | 0.243681E+11 | 17206.63 | 02-JAN-08:09 |
February | 0.178655E+11 | 20611.01 | 01-FEB-08:09 | 0.220609E+11 | 17206.63 | 01-FEB-08:09 |
March | 0.212293E+11 | 20611.01 | 01-MAR-08:09 | 0.253549E+11 | 17206.63 | 01-MAR-08:09 |
April | 0.189620E+11 | 20611.01 | 03-APR-07:10 | 0.235306E+11 | 17206.63 | 03-APR-07:10 |
May | 0.204625E+11 | 20611.01 | 01-MAY-07:10 | 0.248615E+11 | 17206.63 | 01-MAY-07:10 |
June | 0.203636E+11 | 20611.01 | 01-JUN-07:10 | 0.244160E+11 | 17206.63 | 01-JUN-07:10 |
July | 0.190610E+11 | 20611.01 | 03-JUL-07:10 | 0.239708E+11 | 17206.63 | 03-JUL-07:10 |
August | 0.212293E+11 | 20611.01 | 01-AUG-07:10 | 0.253549E+11 | 17206.63 | 01-AUG-07:10 |
September | 0.189620E+11 | 20611.01 | 01-SEP-07:10 | 0.235199E+11 | 17206.63 | 01-SEP-07:10 |
October | 0.196958E+11 | 20611.01 | 02-OCT-07:10 | 0.243735E+11 | 17206.63 | 02-OCT-07:10 |
November | 0.194649E+11 | 20611.01 | 01-NOV-07:10 | 0.238373E+11 | 17206.63 | 01-NOV-07:10 |
December | 0.190610E+11 | 20611.01 | 01-DEC-08:09 | 0.239654E+11 | 17206.63 | 01-DEC-08:09 |
Annual Sum or Average | 0.236053E+12 | 0.289614E+12 | ||||
Minimum of Months | 0.178655E+11 | 20611.01 | 0.220609E+11 | 17206.63 | ||
Maximum of Months | 0.212293E+11 | 20611.01 | 0.253549E+11 | 17206.63 |
Report: ZoneElectricSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.196958E+11 | 20611.01 | 02-JAN-08:09 | 0.243680E+11 | 17206.56 | 02-JAN-08:09 |
February | 0.178655E+11 | 20611.01 | 01-FEB-08:09 | 0.220609E+11 | 17206.56 | 01-FEB-08:09 |
March | 0.212293E+11 | 20611.01 | 01-MAR-08:09 | 0.253548E+11 | 17206.56 | 01-MAR-08:09 |
April | 0.189620E+11 | 20611.01 | 03-APR-07:10 | 0.235305E+11 | 17206.56 | 03-APR-07:10 |
May | 0.204625E+11 | 20611.01 | 01-MAY-07:10 | 0.248614E+11 | 17206.56 | 01-MAY-07:10 |
June | 0.203636E+11 | 20611.01 | 01-JUN-07:10 | 0.244159E+11 | 17206.56 | 01-JUN-07:10 |
July | 0.190610E+11 | 20611.01 | 03-JUL-07:10 | 0.239707E+11 | 17206.56 | 03-JUL-07:10 |
August | 0.212293E+11 | 20611.01 | 01-AUG-07:10 | 0.253548E+11 | 17206.56 | 01-AUG-07:10 |
September | 0.189620E+11 | 20611.01 | 01-SEP-07:10 | 0.235198E+11 | 17206.56 | 01-SEP-07:10 |
October | 0.196958E+11 | 20611.01 | 02-OCT-07:10 | 0.243734E+11 | 17206.56 | 02-OCT-07:10 |
November | 0.194649E+11 | 20611.01 | 01-NOV-07:10 | 0.238372E+11 | 17206.56 | 01-NOV-07:10 |
December | 0.190610E+11 | 20611.01 | 01-DEC-08:09 | 0.239653E+11 | 17206.56 | 01-DEC-08:09 |
Annual Sum or Average | 0.236053E+12 | 0.289613E+12 | ||||
Minimum of Months | 0.178655E+11 | 20611.01 | 0.220609E+11 | 17206.56 | ||
Maximum of Months | 0.212293E+11 | 20611.01 | 0.253548E+11 | 17206.56 |
Report: ZoneElectricSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.196958E+11 | 20611.01 | 02-JAN-08:09 | 0.243680E+11 | 17206.56 | 02-JAN-08:09 |
February | 0.178655E+11 | 20611.01 | 01-FEB-08:09 | 0.220609E+11 | 17206.56 | 01-FEB-08:09 |
March | 0.212293E+11 | 20611.01 | 01-MAR-08:09 | 0.253548E+11 | 17206.56 | 01-MAR-08:09 |
April | 0.189620E+11 | 20611.01 | 03-APR-07:10 | 0.235305E+11 | 17206.56 | 03-APR-07:10 |
May | 0.204625E+11 | 20611.01 | 01-MAY-07:10 | 0.248614E+11 | 17206.56 | 01-MAY-07:10 |
June | 0.203636E+11 | 20611.01 | 01-JUN-07:10 | 0.244159E+11 | 17206.56 | 01-JUN-07:10 |
July | 0.190610E+11 | 20611.01 | 03-JUL-07:10 | 0.239707E+11 | 17206.56 | 03-JUL-07:10 |
August | 0.212293E+11 | 20611.01 | 01-AUG-07:10 | 0.253548E+11 | 17206.56 | 01-AUG-07:10 |
September | 0.189620E+11 | 20611.01 | 01-SEP-07:10 | 0.235198E+11 | 17206.56 | 01-SEP-07:10 |
October | 0.196958E+11 | 20611.01 | 02-OCT-07:10 | 0.243734E+11 | 17206.56 | 02-OCT-07:10 |
November | 0.194649E+11 | 20611.01 | 01-NOV-07:10 | 0.238372E+11 | 17206.56 | 01-NOV-07:10 |
December | 0.190610E+11 | 20611.01 | 01-DEC-08:09 | 0.239653E+11 | 17206.56 | 01-DEC-08:09 |
Annual Sum or Average | 0.236053E+12 | 0.289613E+12 | ||||
Minimum of Months | 0.178655E+11 | 20611.01 | 0.220609E+11 | 17206.56 | ||
Maximum of Months | 0.212293E+11 | 20611.01 | 0.253548E+11 | 17206.56 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.154276E+10 | 2587.92 | 04-JAN-16:00 | 0.305979E+10 | 2160.55 | 02-JAN-08:09 |
February | 0.134714E+10 | 2255.20 | 16-FEB-08:09 | 0.277008E+10 | 2160.55 | 01-FEB-08:09 |
March | 0.151809E+10 | 1803.00 | 20-MAR-07:10 | 0.318369E+10 | 2160.55 | 01-MAR-08:09 |
April | 0.130339E+10 | 1231.33 | 03-APR-07:10 | 0.295462E+10 | 2160.55 | 03-APR-07:10 |
May | 0.138962E+10 | 1470.28 | 22-MAY-07:10 | 0.312174E+10 | 2160.55 | 01-MAY-07:10 |
June | 0.136006E+10 | 1470.28 | 01-JUN-15:00 | 0.306580E+10 | 2160.55 | 01-JUN-07:10 |
July | 0.129020E+10 | 1470.28 | 07-JUL-15:39 | 0.300989E+10 | 2160.55 | 03-JUL-07:10 |
August | 0.144281E+10 | 1231.33 | 01-AUG-07:10 | 0.318369E+10 | 2160.55 | 01-AUG-07:10 |
September | 0.133567E+10 | 2255.20 | 08-SEP-07:10 | 0.295328E+10 | 2160.55 | 01-SEP-07:10 |
October | 0.145450E+10 | 2255.20 | 25-OCT-07:10 | 0.306046E+10 | 2160.55 | 02-OCT-07:10 |
November | 0.152644E+10 | 2587.92 | 08-NOV-16:00 | 0.299314E+10 | 2160.55 | 01-NOV-07:10 |
December | 0.156637E+10 | 2587.92 | 01-DEC-16:30 | 0.300922E+10 | 2160.55 | 01-DEC-08:09 |
Annual Sum or Average | 0.170771E+11 | 0.363654E+11 | ||||
Minimum of Months | 0.129020E+10 | 1231.33 | 0.277008E+10 | 2160.55 | ||
Maximum of Months | 0.156637E+10 | 2587.92 | 0.318369E+10 | 2160.55 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.978317E+09 | 1667.75 | 04-JAN-16:00 | 0.197184E+10 | 1392.34 | 02-JAN-08:09 |
February | 0.860917E+09 | 1453.34 | 16-FEB-08:09 | 0.178515E+10 | 1392.34 | 01-FEB-08:09 |
March | 0.973789E+09 | 1161.92 | 14-MAR-15:00 | 0.205169E+10 | 1392.34 | 01-MAR-08:09 |
April | 0.842955E+09 | 793.52 | 03-APR-07:10 | 0.190407E+10 | 1392.34 | 03-APR-07:10 |
May | 0.902549E+09 | 870.51 | 03-MAY-15:30 | 0.201177E+10 | 1392.34 | 01-MAY-07:10 |
June | 0.883903E+09 | 947.51 | 01-JUN-15:00 | 0.197572E+10 | 1392.34 | 01-JUN-07:10 |
July | 0.836305E+09 | 947.51 | 07-JUL-15:39 | 0.193969E+10 | 1392.34 | 03-JUL-07:10 |
August | 0.932957E+09 | 793.52 | 01-AUG-07:10 | 0.205169E+10 | 1392.34 | 01-AUG-07:10 |
September | 0.858568E+09 | 1453.34 | 08-SEP-07:10 | 0.190321E+10 | 1392.34 | 01-SEP-07:10 |
October | 0.922055E+09 | 1161.92 | 25-OCT-07:10 | 0.197228E+10 | 1392.34 | 02-OCT-07:10 |
November | 0.977420E+09 | 1667.75 | 08-NOV-16:49 | 0.192889E+10 | 1392.34 | 01-NOV-07:10 |
December | 0.993343E+09 | 1667.75 | 01-DEC-16:30 | 0.193926E+10 | 1392.34 | 01-DEC-08:09 |
Annual Sum or Average | 0.109631E+11 | 0.234352E+11 | ||||
Minimum of Months | 0.836305E+09 | 793.52 | 0.178515E+10 | 1392.34 | ||
Maximum of Months | 0.993343E+09 | 1667.75 | 0.205169E+10 | 1392.34 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.148094E+10 | 2255.25 | 04-JAN-16:49 | 0.305983E+10 | 2160.58 | 02-JAN-08:09 |
February | 0.131576E+10 | 2255.25 | 16-FEB-08:09 | 0.277013E+10 | 2160.58 | 01-FEB-08:09 |
March | 0.150759E+10 | 1803.04 | 20-MAR-07:10 | 0.318374E+10 | 2160.58 | 01-MAR-08:09 |
April | 0.130790E+10 | 1231.36 | 03-APR-07:10 | 0.295467E+10 | 2160.58 | 03-APR-07:10 |
May | 0.140107E+10 | 1470.31 | 22-MAY-07:10 | 0.312179E+10 | 2160.58 | 01-MAY-07:10 |
June | 0.137621E+10 | 1470.31 | 01-JUN-15:00 | 0.306585E+10 | 2160.58 | 01-JUN-07:10 |
July | 0.130130E+10 | 1470.31 | 07-JUL-15:50 | 0.300994E+10 | 2160.58 | 03-JUL-07:10 |
August | 0.144934E+10 | 1231.36 | 01-AUG-07:10 | 0.318374E+10 | 2160.58 | 01-AUG-07:10 |
September | 0.133278E+10 | 2255.25 | 08-SEP-07:10 | 0.295333E+10 | 2160.58 | 01-SEP-07:10 |
October | 0.142029E+10 | 2255.25 | 25-OCT-07:10 | 0.306051E+10 | 2160.58 | 02-OCT-07:10 |
November | 0.147543E+10 | 2587.98 | 09-NOV-16:49 | 0.299318E+10 | 2160.58 | 01-NOV-07:10 |
December | 0.148582E+10 | 2587.98 | 01-DEC-16:40 | 0.300927E+10 | 2160.58 | 01-DEC-08:09 |
Annual Sum or Average | 0.168544E+11 | 0.363660E+11 | ||||
Minimum of Months | 0.130130E+10 | 1231.36 | 0.277013E+10 | 2160.58 | ||
Maximum of Months | 0.150759E+10 | 2587.98 | 0.318374E+10 | 2160.58 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.965380E+09 | 1453.34 | 04-JAN-16:49 | 0.197183E+10 | 1392.33 | 02-JAN-08:09 |
February | 0.852179E+09 | 1453.34 | 16-FEB-08:09 | 0.178514E+10 | 1392.33 | 01-FEB-08:09 |
March | 0.971637E+09 | 1161.92 | 17-MAR-07:10 | 0.205168E+10 | 1392.33 | 01-MAR-08:09 |
April | 0.836810E+09 | 793.52 | 03-APR-07:10 | 0.190406E+10 | 1392.33 | 03-APR-07:10 |
May | 0.893359E+09 | 947.51 | 22-MAY-07:10 | 0.201175E+10 | 1392.33 | 01-MAY-07:10 |
June | 0.879354E+09 | 1161.92 | 08-JUN-07:10 | 0.197570E+10 | 1392.33 | 01-JUN-07:10 |
July | 0.833132E+09 | 947.51 | 07-JUL-15:50 | 0.193968E+10 | 1392.33 | 03-JUL-07:10 |
August | 0.929361E+09 | 870.51 | 28-AUG-07:10 | 0.205168E+10 | 1392.33 | 01-AUG-07:10 |
September | 0.856482E+09 | 1453.34 | 08-SEP-07:10 | 0.190319E+10 | 1392.33 | 01-SEP-07:10 |
October | 0.923980E+09 | 1453.34 | 25-OCT-07:10 | 0.197226E+10 | 1392.33 | 02-OCT-07:10 |
November | 0.952105E+09 | 1667.75 | 09-NOV-16:49 | 0.192888E+10 | 1392.33 | 01-NOV-07:10 |
December | 0.970226E+09 | 1667.75 | 01-DEC-16:49 | 0.193924E+10 | 1392.33 | 01-DEC-08:09 |
Annual Sum or Average | 0.108640E+11 | 0.234351E+11 | ||||
Minimum of Months | 0.833132E+09 | 793.52 | 0.178514E+10 | 1392.33 | ||
Maximum of Months | 0.971637E+09 | 1667.75 | 0.205168E+10 | 1392.33 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.153750E+10 | 2587.92 | 04-JAN-16:00 | 0.305979E+10 | 2160.55 | 02-JAN-08:09 |
February | 0.134347E+10 | 2255.20 | 16-FEB-08:09 | 0.277008E+10 | 2160.55 | 01-FEB-08:09 |
March | 0.151582E+10 | 1803.00 | 20-MAR-07:10 | 0.318369E+10 | 2160.55 | 01-MAR-08:09 |
April | 0.130296E+10 | 1231.33 | 03-APR-07:10 | 0.295462E+10 | 2160.55 | 03-APR-07:10 |
May | 0.138900E+10 | 1350.81 | 22-MAY-07:10 | 0.312174E+10 | 2160.55 | 01-MAY-07:10 |
June | 0.135953E+10 | 1470.28 | 08-JUN-15:20 | 0.306580E+10 | 2160.55 | 01-JUN-07:10 |
July | 0.128920E+10 | 1470.28 | 07-JUL-15:50 | 0.300989E+10 | 2160.55 | 03-JUL-07:10 |
August | 0.144228E+10 | 1231.33 | 01-AUG-07:10 | 0.318369E+10 | 2160.55 | 01-AUG-07:10 |
September | 0.133384E+10 | 2255.20 | 08-SEP-07:10 | 0.295328E+10 | 2160.55 | 01-SEP-07:10 |
October | 0.145082E+10 | 2255.20 | 25-OCT-07:10 | 0.306046E+10 | 2160.55 | 02-OCT-07:10 |
November | 0.152276E+10 | 2587.92 | 08-NOV-16:00 | 0.299314E+10 | 2160.55 | 01-NOV-07:10 |
December | 0.156033E+10 | 2587.92 | 01-DEC-16:30 | 0.300922E+10 | 2160.55 | 01-DEC-08:09 |
Annual Sum or Average | 0.170475E+11 | 0.363654E+11 | ||||
Minimum of Months | 0.128920E+10 | 1231.33 | 0.277008E+10 | 2160.55 | ||
Maximum of Months | 0.156033E+10 | 2587.92 | 0.318369E+10 | 2160.55 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.976446E+09 | 1667.75 | 04-JAN-16:00 | 0.197184E+10 | 1392.34 | 02-JAN-08:09 |
February | 0.859414E+09 | 1453.34 | 16-FEB-08:09 | 0.178515E+10 | 1392.34 | 01-FEB-08:09 |
March | 0.972352E+09 | 947.51 | 02-MAR-16:49 | 0.205169E+10 | 1392.34 | 01-MAR-08:09 |
April | 0.842663E+09 | 793.52 | 03-APR-07:10 | 0.190407E+10 | 1392.34 | 03-APR-07:10 |
May | 0.901762E+09 | 870.51 | 22-MAY-07:10 | 0.201177E+10 | 1392.34 | 01-MAY-07:10 |
June | 0.883062E+09 | 947.51 | 08-JUN-15:20 | 0.197572E+10 | 1392.34 | 01-JUN-07:10 |
July | 0.835708E+09 | 947.51 | 07-JUL-15:50 | 0.193969E+10 | 1392.34 | 03-JUL-07:10 |
August | 0.932562E+09 | 793.52 | 01-AUG-07:10 | 0.205169E+10 | 1392.34 | 01-AUG-07:10 |
September | 0.857864E+09 | 1453.34 | 08-SEP-07:10 | 0.190321E+10 | 1392.34 | 01-SEP-07:10 |
October | 0.921129E+09 | 1161.92 | 25-OCT-07:10 | 0.197228E+10 | 1392.34 | 02-OCT-07:10 |
November | 0.975587E+09 | 1667.75 | 08-NOV-16:49 | 0.192889E+10 | 1392.34 | 01-NOV-07:10 |
December | 0.991317E+09 | 1667.75 | 01-DEC-16:30 | 0.193926E+10 | 1392.34 | 01-DEC-08:09 |
Annual Sum or Average | 0.109499E+11 | 0.234352E+11 | ||||
Minimum of Months | 0.835708E+09 | 793.52 | 0.178515E+10 | 1392.34 | ||
Maximum of Months | 0.991317E+09 | 1667.75 | 0.205169E+10 | 1392.34 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.148008E+10 | 2255.25 | 04-JAN-16:49 | 0.305983E+10 | 2160.58 | 02-JAN-08:09 |
February | 0.131428E+10 | 2255.25 | 16-FEB-08:09 | 0.277013E+10 | 2160.58 | 01-FEB-08:09 |
March | 0.150632E+10 | 1803.04 | 20-MAR-07:10 | 0.318374E+10 | 2160.58 | 01-MAR-08:09 |
April | 0.130719E+10 | 1231.36 | 03-APR-07:10 | 0.295467E+10 | 2160.58 | 03-APR-07:10 |
May | 0.139986E+10 | 1470.31 | 22-MAY-07:10 | 0.312179E+10 | 2160.58 | 01-MAY-07:10 |
June | 0.137469E+10 | 1470.31 | 08-JUN-07:10 | 0.306585E+10 | 2160.58 | 01-JUN-07:10 |
July | 0.130028E+10 | 1470.31 | 07-JUL-15:50 | 0.300994E+10 | 2160.58 | 03-JUL-07:10 |
August | 0.144860E+10 | 1231.36 | 01-AUG-07:10 | 0.318374E+10 | 2160.58 | 01-AUG-07:10 |
September | 0.133147E+10 | 2255.25 | 08-SEP-07:10 | 0.295333E+10 | 2160.58 | 01-SEP-07:10 |
October | 0.141735E+10 | 2255.25 | 25-OCT-07:10 | 0.306051E+10 | 2160.58 | 02-OCT-07:10 |
November | 0.147447E+10 | 2587.98 | 09-NOV-16:49 | 0.299318E+10 | 2160.58 | 01-NOV-07:10 |
December | 0.148522E+10 | 2587.98 | 01-DEC-16:40 | 0.300927E+10 | 2160.58 | 01-DEC-08:09 |
Annual Sum or Average | 0.168398E+11 | 0.363660E+11 | ||||
Minimum of Months | 0.130028E+10 | 1231.36 | 0.277013E+10 | 2160.58 | ||
Maximum of Months | 0.150632E+10 | 2587.98 | 0.318374E+10 | 2160.58 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.964281E+09 | 1453.34 | 04-JAN-16:49 | 0.197183E+10 | 1392.33 | 02-JAN-08:09 |
February | 0.851082E+09 | 1453.34 | 16-FEB-08:09 | 0.178514E+10 | 1392.33 | 01-FEB-08:09 |
March | 0.970554E+09 | 1161.92 | 17-MAR-07:10 | 0.205168E+10 | 1392.33 | 01-MAR-08:09 |
April | 0.836551E+09 | 793.52 | 03-APR-07:10 | 0.190406E+10 | 1392.33 | 03-APR-07:10 |
May | 0.892753E+09 | 947.51 | 22-MAY-07:10 | 0.201175E+10 | 1392.33 | 01-MAY-07:10 |
June | 0.878726E+09 | 947.51 | 08-JUN-07:10 | 0.197570E+10 | 1392.33 | 01-JUN-07:10 |
July | 0.832597E+09 | 947.51 | 07-JUL-15:00 | 0.193968E+10 | 1392.33 | 03-JUL-07:10 |
August | 0.928974E+09 | 870.51 | 28-AUG-07:10 | 0.205168E+10 | 1392.33 | 01-AUG-07:10 |
September | 0.855750E+09 | 1453.34 | 08-SEP-07:10 | 0.190319E+10 | 1392.33 | 01-SEP-07:10 |
October | 0.922558E+09 | 1453.34 | 25-OCT-07:10 | 0.197226E+10 | 1392.33 | 02-OCT-07:10 |
November | 0.951053E+09 | 1667.75 | 09-NOV-16:49 | 0.192888E+10 | 1392.33 | 01-NOV-07:10 |
December | 0.969119E+09 | 1667.75 | 01-DEC-16:49 | 0.193924E+10 | 1392.33 | 01-DEC-08:09 |
Annual Sum or Average | 0.108540E+11 | 0.234351E+11 | ||||
Minimum of Months | 0.832597E+09 | 793.52 | 0.178514E+10 | 1392.33 | ||
Maximum of Months | 0.970554E+09 | 1667.75 | 0.205168E+10 | 1392.33 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.153723E+10 | 2587.92 | 04-JAN-16:00 | 0.305979E+10 | 2160.55 | 02-JAN-08:09 |
February | 0.134324E+10 | 2255.20 | 16-FEB-08:09 | 0.277008E+10 | 2160.55 | 01-FEB-08:09 |
March | 0.151544E+10 | 1803.00 | 20-MAR-07:10 | 0.318369E+10 | 2160.55 | 01-MAR-08:09 |
April | 0.130296E+10 | 1231.33 | 03-APR-07:10 | 0.295462E+10 | 2160.55 | 03-APR-07:10 |
May | 0.138896E+10 | 1350.81 | 22-MAY-07:10 | 0.312174E+10 | 2160.55 | 01-MAY-07:10 |
June | 0.135953E+10 | 1470.28 | 08-JUN-15:20 | 0.306580E+10 | 2160.55 | 01-JUN-07:10 |
July | 0.128918E+10 | 1470.28 | 07-JUL-15:50 | 0.300989E+10 | 2160.55 | 03-JUL-07:10 |
August | 0.144227E+10 | 1231.33 | 01-AUG-07:10 | 0.318369E+10 | 2160.55 | 01-AUG-07:10 |
September | 0.133377E+10 | 2255.20 | 08-SEP-07:10 | 0.295328E+10 | 2160.55 | 01-SEP-07:10 |
October | 0.145076E+10 | 2255.20 | 25-OCT-07:10 | 0.306046E+10 | 2160.55 | 02-OCT-07:10 |
November | 0.152268E+10 | 2587.92 | 08-NOV-16:00 | 0.299314E+10 | 2160.55 | 01-NOV-07:10 |
December | 0.156010E+10 | 2587.92 | 01-DEC-16:30 | 0.300922E+10 | 2160.55 | 01-DEC-08:09 |
Annual Sum or Average | 0.170461E+11 | 0.363654E+11 | ||||
Minimum of Months | 0.128918E+10 | 1231.33 | 0.277008E+10 | 2160.55 | ||
Maximum of Months | 0.156010E+10 | 2587.92 | 0.318369E+10 | 2160.55 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.976446E+09 | 1667.75 | 04-JAN-16:00 | 0.197184E+10 | 1392.34 | 02-JAN-08:09 |
February | 0.859286E+09 | 1453.34 | 16-FEB-08:09 | 0.178515E+10 | 1392.34 | 01-FEB-08:09 |
March | 0.972345E+09 | 947.51 | 02-MAR-16:49 | 0.205169E+10 | 1392.34 | 01-MAR-08:09 |
April | 0.842592E+09 | 793.52 | 03-APR-07:10 | 0.190407E+10 | 1392.34 | 03-APR-07:10 |
May | 0.901756E+09 | 870.51 | 22-MAY-07:10 | 0.201177E+10 | 1392.34 | 01-MAY-07:10 |
June | 0.883062E+09 | 947.51 | 08-JUN-15:20 | 0.197572E+10 | 1392.34 | 01-JUN-07:10 |
July | 0.835708E+09 | 947.51 | 07-JUL-15:50 | 0.193969E+10 | 1392.34 | 03-JUL-07:10 |
August | 0.932519E+09 | 793.52 | 01-AUG-07:10 | 0.205169E+10 | 1392.34 | 01-AUG-07:10 |
September | 0.857864E+09 | 1453.34 | 08-SEP-07:10 | 0.190321E+10 | 1392.34 | 01-SEP-07:10 |
October | 0.921129E+09 | 1161.92 | 25-OCT-07:10 | 0.197228E+10 | 1392.34 | 02-OCT-07:10 |
November | 0.975482E+09 | 1667.75 | 08-NOV-16:49 | 0.192889E+10 | 1392.34 | 01-NOV-07:10 |
December | 0.991209E+09 | 1667.75 | 01-DEC-16:30 | 0.193926E+10 | 1392.34 | 01-DEC-08:09 |
Annual Sum or Average | 0.109494E+11 | 0.234352E+11 | ||||
Minimum of Months | 0.835708E+09 | 793.52 | 0.178515E+10 | 1392.34 | ||
Maximum of Months | 0.991209E+09 | 1667.75 | 0.205169E+10 | 1392.34 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.148008E+10 | 2255.25 | 04-JAN-16:49 | 0.305983E+10 | 2160.58 | 02-JAN-08:09 |
February | 0.131428E+10 | 2255.25 | 16-FEB-08:09 | 0.277013E+10 | 2160.58 | 01-FEB-08:09 |
March | 0.150627E+10 | 1803.04 | 20-MAR-07:10 | 0.318374E+10 | 2160.58 | 01-MAR-08:09 |
April | 0.130714E+10 | 1231.36 | 03-APR-07:10 | 0.295467E+10 | 2160.58 | 03-APR-07:10 |
May | 0.139986E+10 | 1470.31 | 22-MAY-07:10 | 0.312179E+10 | 2160.58 | 01-MAY-07:10 |
June | 0.137463E+10 | 1470.31 | 08-JUN-07:10 | 0.306585E+10 | 2160.58 | 01-JUN-07:10 |
July | 0.130015E+10 | 1470.31 | 07-JUL-15:50 | 0.300994E+10 | 2160.58 | 03-JUL-07:10 |
August | 0.144859E+10 | 1231.36 | 01-AUG-07:10 | 0.318374E+10 | 2160.58 | 01-AUG-07:10 |
September | 0.133139E+10 | 2255.25 | 08-SEP-07:10 | 0.295333E+10 | 2160.58 | 01-SEP-07:10 |
October | 0.141732E+10 | 2255.25 | 25-OCT-07:10 | 0.306051E+10 | 2160.58 | 02-OCT-07:10 |
November | 0.147427E+10 | 2587.98 | 09-NOV-16:49 | 0.299318E+10 | 2160.58 | 01-NOV-07:10 |
December | 0.148522E+10 | 2587.98 | 01-DEC-16:40 | 0.300927E+10 | 2160.58 | 01-DEC-08:09 |
Annual Sum or Average | 0.168392E+11 | 0.363660E+11 | ||||
Minimum of Months | 0.130015E+10 | 1231.36 | 0.277013E+10 | 2160.58 | ||
Maximum of Months | 0.150627E+10 | 2587.98 | 0.318374E+10 | 2160.58 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.964235E+09 | 1453.34 | 04-JAN-16:49 | 0.197183E+10 | 1392.33 | 02-JAN-08:09 |
February | 0.851006E+09 | 1453.34 | 16-FEB-08:09 | 0.178514E+10 | 1392.33 | 01-FEB-08:09 |
March | 0.970534E+09 | 1161.92 | 17-MAR-07:10 | 0.205168E+10 | 1392.33 | 01-MAR-08:09 |
April | 0.836551E+09 | 793.52 | 03-APR-07:10 | 0.190406E+10 | 1392.33 | 03-APR-07:10 |
May | 0.892691E+09 | 947.51 | 22-MAY-07:10 | 0.201175E+10 | 1392.33 | 01-MAY-07:10 |
June | 0.878712E+09 | 947.51 | 08-JUN-07:10 | 0.197570E+10 | 1392.33 | 01-JUN-07:10 |
July | 0.832566E+09 | 947.51 | 07-JUL-15:00 | 0.193968E+10 | 1392.33 | 03-JUL-07:10 |
August | 0.928969E+09 | 870.51 | 28-AUG-07:10 | 0.205168E+10 | 1392.33 | 01-AUG-07:10 |
September | 0.855743E+09 | 1453.34 | 08-SEP-07:10 | 0.190319E+10 | 1392.33 | 01-SEP-07:10 |
October | 0.922511E+09 | 1453.34 | 25-OCT-07:10 | 0.197226E+10 | 1392.33 | 02-OCT-07:10 |
November | 0.951053E+09 | 1667.75 | 09-NOV-16:49 | 0.192888E+10 | 1392.33 | 01-NOV-07:10 |
December | 0.969119E+09 | 1667.75 | 01-DEC-16:49 | 0.193924E+10 | 1392.33 | 01-DEC-08:09 |
Annual Sum or Average | 0.108537E+11 | 0.234351E+11 | ||||
Minimum of Months | 0.832566E+09 | 793.52 | 0.178514E+10 | 1392.33 | ||
Maximum of Months | 0.970534E+09 | 1667.75 | 0.205168E+10 | 1392.33 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.553024E+09 | 578.72 | 02-JAN-08:09 | 0.521915E+10 | 1948.61 | 01-JAN-00:10 |
February | 0.501634E+09 | 578.72 | 01-FEB-08:09 | 0.942813E+10 | 3897.21 | 01-FEB-00:10 |
March | 0.596080E+09 | 578.72 | 01-MAR-08:09 | 0.156645E+11 | 7794.42 | 31-MAR-23:10 |
April | 0.532421E+09 | 578.72 | 03-APR-07:10 | 0.201821E+11 | 7794.42 | 01-APR-00:10 |
May | 0.574552E+09 | 578.72 | 01-MAY-07:10 | 0.522616E+10 | 3897.21 | 31-MAY-23:10 |
June | 0.571774E+09 | 578.72 | 01-JUN-07:10 | 0.101086E+11 | 5845.82 | 30-JUN-23:10 |
July | 0.535199E+09 | 578.72 | 03-JUL-07:10 | 0.156645E+11 | 7794.42 | 31-JUL-23:10 |
August | 0.596080E+09 | 578.72 | 01-AUG-07:10 | 0.208555E+11 | 7794.42 | 01-AUG-00:10 |
September | 0.532421E+09 | 578.72 | 01-SEP-07:10 | 0.505780E+10 | 3897.21 | 30-SEP-23:10 |
October | 0.553024E+09 | 578.72 | 02-OCT-07:10 | 0.104453E+11 | 5845.82 | 31-OCT-23:10 |
November | 0.546542E+09 | 578.72 | 01-NOV-07:10 | 0.151524E+11 | 5845.82 | 01-NOV-00:10 |
December | 0.535199E+09 | 578.72 | 01-DEC-08:09 | 0.208766E+11 | 7794.42 | 01-DEC-00:10 |
Annual Sum or Average | 0.662795E+10 | 0.153881E+12 | ||||
Minimum of Months | 0.501634E+09 | 578.72 | 0.505780E+10 | 1948.61 | ||
Maximum of Months | 0.596080E+09 | 578.72 | 0.208766E+11 | 7794.42 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.553024E+09 | 578.72 | 02-JAN-08:09 | 0.521915E+10 | 1948.61 | 01-JAN-00:10 |
February | 0.501634E+09 | 578.72 | 01-FEB-08:09 | 0.942813E+10 | 3897.21 | 01-FEB-00:10 |
March | 0.596080E+09 | 578.72 | 01-MAR-08:09 | 0.156645E+11 | 7794.42 | 31-MAR-23:10 |
April | 0.532421E+09 | 578.72 | 03-APR-07:10 | 0.201821E+11 | 7794.42 | 01-APR-00:10 |
May | 0.574552E+09 | 578.72 | 01-MAY-07:10 | 0.522616E+10 | 3897.21 | 31-MAY-23:10 |
June | 0.571774E+09 | 578.72 | 01-JUN-07:10 | 0.101086E+11 | 5845.82 | 30-JUN-23:10 |
July | 0.535199E+09 | 578.72 | 03-JUL-07:10 | 0.156645E+11 | 7794.42 | 31-JUL-23:10 |
August | 0.596080E+09 | 578.72 | 01-AUG-07:10 | 0.208555E+11 | 7794.42 | 01-AUG-00:10 |
September | 0.532421E+09 | 578.72 | 01-SEP-07:10 | 0.505780E+10 | 3897.21 | 30-SEP-23:10 |
October | 0.553024E+09 | 578.72 | 02-OCT-07:10 | 0.104453E+11 | 5845.82 | 31-OCT-23:10 |
November | 0.546542E+09 | 578.72 | 01-NOV-07:10 | 0.151524E+11 | 5845.82 | 01-NOV-00:10 |
December | 0.535199E+09 | 578.72 | 01-DEC-08:09 | 0.208766E+11 | 7794.42 | 01-DEC-00:10 |
Annual Sum or Average | 0.662795E+10 | 0.153881E+12 | ||||
Minimum of Months | 0.501634E+09 | 578.72 | 0.505780E+10 | 1948.61 | ||
Maximum of Months | 0.596080E+09 | 578.72 | 0.208766E+11 | 7794.42 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.553024E+09 | 578.72 | 02-JAN-08:09 | 0.521915E+10 | 1948.61 | 01-JAN-00:10 |
February | 0.501634E+09 | 578.72 | 01-FEB-08:09 | 0.942813E+10 | 3897.21 | 01-FEB-00:10 |
March | 0.596080E+09 | 578.72 | 01-MAR-08:09 | 0.156645E+11 | 7794.42 | 31-MAR-23:10 |
April | 0.532421E+09 | 578.72 | 03-APR-07:10 | 0.201821E+11 | 7794.42 | 01-APR-00:10 |
May | 0.574552E+09 | 578.72 | 01-MAY-07:10 | 0.522616E+10 | 3897.21 | 31-MAY-23:10 |
June | 0.571774E+09 | 578.72 | 01-JUN-07:10 | 0.101086E+11 | 5845.82 | 30-JUN-23:10 |
July | 0.535199E+09 | 578.72 | 03-JUL-07:10 | 0.156645E+11 | 7794.42 | 31-JUL-23:10 |
August | 0.596080E+09 | 578.72 | 01-AUG-07:10 | 0.208555E+11 | 7794.42 | 01-AUG-00:10 |
September | 0.532421E+09 | 578.72 | 01-SEP-07:10 | 0.505780E+10 | 3897.21 | 30-SEP-23:10 |
October | 0.553024E+09 | 578.72 | 02-OCT-07:10 | 0.104453E+11 | 5845.82 | 31-OCT-23:10 |
November | 0.546542E+09 | 578.72 | 01-NOV-07:10 | 0.151524E+11 | 5845.82 | 01-NOV-00:10 |
December | 0.535199E+09 | 578.72 | 01-DEC-08:09 | 0.208766E+11 | 7794.42 | 01-DEC-00:10 |
Annual Sum or Average | 0.662795E+10 | 0.153881E+12 | ||||
Minimum of Months | 0.501634E+09 | 578.72 | 0.505780E+10 | 1948.61 | ||
Maximum of Months | 0.596080E+09 | 578.72 | 0.208766E+11 | 7794.42 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.618367E+10 | 6471.01 | 02-JAN-08:09 | 0.254202E+12 | 94908.13 | 01-JAN-00:10 |
February | 0.560905E+10 | 6471.01 | 01-FEB-08:09 | 0.459203E+12 | 189816.26 | 01-FEB-00:10 |
March | 0.666512E+10 | 6471.01 | 01-MAR-08:09 | 0.762947E+12 | 379632.52 | 31-MAR-23:10 |
April | 0.595330E+10 | 6471.01 | 03-APR-07:10 | 0.982982E+12 | 379632.52 | 01-APR-00:10 |
May | 0.642439E+10 | 6471.01 | 01-MAY-07:10 | 0.254544E+12 | 189816.26 | 31-MAY-23:10 |
June | 0.639333E+10 | 6471.01 | 01-JUN-07:10 | 0.492345E+12 | 284724.39 | 30-JUN-23:10 |
July | 0.598436E+10 | 6471.01 | 03-JUL-07:10 | 0.762947E+12 | 379632.52 | 31-JUL-23:10 |
August | 0.666512E+10 | 6471.01 | 01-AUG-07:10 | 0.101578E+13 | 379632.52 | 01-AUG-00:10 |
September | 0.595330E+10 | 6471.01 | 01-SEP-07:10 | 0.246344E+12 | 189816.26 | 30-SEP-23:10 |
October | 0.618367E+10 | 6471.01 | 02-OCT-07:10 | 0.508746E+12 | 284724.39 | 31-OCT-23:10 |
November | 0.611120E+10 | 6471.01 | 01-NOV-07:10 | 0.738006E+12 | 284724.39 | 01-NOV-00:10 |
December | 0.598436E+10 | 6471.01 | 01-DEC-08:09 | 0.101681E+13 | 379632.52 | 01-DEC-00:10 |
Annual Sum or Average | 0.741109E+11 | 0.749486E+13 | ||||
Minimum of Months | 0.560905E+10 | 6471.01 | 0.246344E+12 | 94908.13 | ||
Maximum of Months | 0.666512E+10 | 6471.01 | 0.101681E+13 | 379632.52 |
Report: SpaceGainsMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.133902E+11 | 0.219312E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.121482E+11 | 0.198933E+11 | 0.325565E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.145160E+11 | 0.236388E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.128805E+11 | 0.211142E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.139531E+11 | 0.227850E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.139143E+11 | 0.226748E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.129193E+11 | 0.212244E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.145160E+11 | 0.236388E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.128805E+11 | 0.211142E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.133902E+11 | 0.219312E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.132595E+11 | 0.216742E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.129193E+11 | 0.212244E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.160687E+12 | 0.262844E+12 | 0.424397E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.121482E+11 | 0.198933E+11 | 0.325565E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.145160E+11 | 0.236388E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.120254E+11 | 0.196958E+11 | 0.243681E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.109099E+11 | 0.178655E+11 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.130364E+11 | 0.212293E+11 | 0.253549E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.115676E+11 | 0.189620E+11 | 0.235306E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.125309E+11 | 0.204625E+11 | 0.248615E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.124961E+11 | 0.203636E+11 | 0.244160E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.116025E+11 | 0.190610E+11 | 0.239708E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.130364E+11 | 0.212293E+11 | 0.253549E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.115676E+11 | 0.189620E+11 | 0.235199E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.120254E+11 | 0.196958E+11 | 0.243735E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.119080E+11 | 0.194649E+11 | 0.238373E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.116025E+11 | 0.190610E+11 | 0.239654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.144308E+12 | 0.236053E+12 | 0.289614E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.109099E+11 | 0.178655E+11 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.130364E+11 | 0.212293E+11 | 0.253549E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.120254E+11 | 0.196958E+11 | 0.243680E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.109099E+11 | 0.178655E+11 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.130364E+11 | 0.212293E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.115676E+11 | 0.189620E+11 | 0.235305E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.125309E+11 | 0.204625E+11 | 0.248614E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.124961E+11 | 0.203636E+11 | 0.244159E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.116025E+11 | 0.190610E+11 | 0.239707E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.130364E+11 | 0.212293E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.115676E+11 | 0.189620E+11 | 0.235198E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.120254E+11 | 0.196958E+11 | 0.243734E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.119080E+11 | 0.194649E+11 | 0.238372E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.116025E+11 | 0.190610E+11 | 0.239653E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.144308E+12 | 0.236053E+12 | 0.289613E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.109099E+11 | 0.178655E+11 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.130364E+11 | 0.212293E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.120254E+11 | 0.196958E+11 | 0.243680E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.109099E+11 | 0.178655E+11 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.130364E+11 | 0.212293E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.115676E+11 | 0.189620E+11 | 0.235305E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.125309E+11 | 0.204625E+11 | 0.248614E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.124961E+11 | 0.203636E+11 | 0.244159E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.116025E+11 | 0.190610E+11 | 0.239707E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.130364E+11 | 0.212293E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.115676E+11 | 0.189620E+11 | 0.235198E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.120254E+11 | 0.196958E+11 | 0.243734E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.119080E+11 | 0.194649E+11 | 0.238372E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.116025E+11 | 0.190610E+11 | 0.239653E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.144308E+12 | 0.236053E+12 | 0.289613E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.109099E+11 | 0.178655E+11 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.130364E+11 | 0.212293E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150991E+10 | 0.154276E+10 | 0.305979E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.691358E+09 |
February | 0.136985E+10 | 0.134714E+10 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.642555E+09 |
March | 0.163685E+10 | 0.151809E+10 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.632920E+09 |
April | 0.145243E+10 | 0.130339E+10 | 0.295462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1070393.82 | 0.453996E+09 |
May | 0.157338E+10 | 0.138962E+10 | 0.312174E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9977183.91 | 0.306990E+09 |
June | 0.156900E+10 | 0.136006E+10 | 0.306580E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 49891322.35 | 0.161532E+09 |
July | 0.145680E+10 | 0.129020E+10 | 0.300989E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 71899734.85 | 83587866.68 |
August | 0.163685E+10 | 0.144281E+10 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 36419864.18 | 0.110111E+09 |
September | 0.145243E+10 | 0.133567E+10 | 0.295328E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12229560.99 | 0.184150E+09 |
October | 0.150991E+10 | 0.145450E+10 | 0.306046E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2936998.52 | 0.343411E+09 |
November | 0.149516E+10 | 0.152644E+10 | 0.299314E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.560148E+09 |
December | 0.145680E+10 | 0.156637E+10 | 0.300922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.646374E+09 |
Annual Sum or Average | 0.181194E+11 | 0.170771E+11 | 0.363654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.184425E+09 | 0.481713E+10 |
Minimum of Months | 0.136985E+10 | 0.129020E+10 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 83587866.68 |
Maximum of Months | 0.163685E+10 | 0.156637E+10 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 71899734.85 | 0.691358E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.978317E+09 | 0.197184E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.464872E+09 |
February | 0.882782E+09 | 0.860917E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.427815E+09 |
March | 0.105485E+10 | 0.973789E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.417673E+09 |
April | 0.936002E+09 | 0.842955E+09 | 0.190407E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 773641.20 | 0.300087E+09 |
May | 0.101394E+10 | 0.902549E+09 | 0.201177E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7101637.00 | 0.206241E+09 |
June | 0.101113E+10 | 0.883903E+09 | 0.197572E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 35790318.10 | 0.102264E+09 |
July | 0.938820E+09 | 0.836305E+09 | 0.193969E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 51829025.50 | 47968774.97 |
August | 0.105485E+10 | 0.932957E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 26556420.57 | 61029170.15 |
September | 0.936002E+09 | 0.858568E+09 | 0.190321E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8414230.92 | 0.121530E+09 |
October | 0.973041E+09 | 0.922055E+09 | 0.197228E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2003084.19 | 0.228860E+09 |
November | 0.963541E+09 | 0.977420E+09 | 0.192889E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.371400E+09 |
December | 0.938820E+09 | 0.993343E+09 | 0.193926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.425657E+09 |
Annual Sum or Average | 0.116768E+11 | 0.109631E+11 | 0.234352E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.132468E+09 | 0.317540E+10 |
Minimum of Months | 0.882782E+09 | 0.836305E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47968774.97 |
Maximum of Months | 0.105485E+10 | 0.993343E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 51829025.50 | 0.464872E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150994E+10 | 0.148094E+10 | 0.305983E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.722578E+09 |
February | 0.136988E+10 | 0.131576E+10 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.669316E+09 |
March | 0.163688E+10 | 0.150759E+10 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.645706E+09 |
April | 0.145246E+10 | 0.130790E+10 | 0.295467E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1057025.79 | 0.460771E+09 |
May | 0.157341E+10 | 0.140107E+10 | 0.312179E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9711245.21 | 0.305269E+09 |
June | 0.156904E+10 | 0.137621E+10 | 0.306585E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 51810359.22 | 0.155523E+09 |
July | 0.145684E+10 | 0.130130E+10 | 0.300994E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 72809520.45 | 79932890.58 |
August | 0.163688E+10 | 0.144934E+10 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 35937310.99 | 0.109855E+09 |
September | 0.145246E+10 | 0.133278E+10 | 0.295333E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11050644.40 | 0.194872E+09 |
October | 0.150994E+10 | 0.142029E+10 | 0.306051E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2356607.47 | 0.364576E+09 |
November | 0.149520E+10 | 0.147543E+10 | 0.299318E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.592830E+09 |
December | 0.145684E+10 | 0.148582E+10 | 0.300927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.673569E+09 |
Annual Sum or Average | 0.181198E+11 | 0.168544E+11 | 0.363660E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.184733E+09 | 0.497480E+10 |
Minimum of Months | 0.136988E+10 | 0.130130E+10 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 79932890.58 |
Maximum of Months | 0.163688E+10 | 0.150759E+10 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 72809520.45 | 0.722578E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.965380E+09 | 0.197183E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.485076E+09 |
February | 0.882782E+09 | 0.852179E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.460309E+09 |
March | 0.105485E+10 | 0.971637E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.463666E+09 |
April | 0.936002E+09 | 0.836810E+09 | 0.190406E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 702631.54 | 0.345898E+09 |
May | 0.101394E+10 | 0.893359E+09 | 0.201175E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6078651.55 | 0.224703E+09 |
June | 0.101113E+10 | 0.879354E+09 | 0.197570E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 31514108.24 | 0.122389E+09 |
July | 0.938820E+09 | 0.833132E+09 | 0.193968E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 45117335.14 | 65884684.08 |
August | 0.105485E+10 | 0.929361E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22802838.12 | 89594561.86 |
September | 0.936002E+09 | 0.856482E+09 | 0.190319E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7813465.55 | 0.138626E+09 |
October | 0.973041E+09 | 0.923980E+09 | 0.197226E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1825420.89 | 0.253600E+09 |
November | 0.963541E+09 | 0.952105E+09 | 0.192888E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.411564E+09 |
December | 0.938820E+09 | 0.970226E+09 | 0.193924E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.478787E+09 |
Annual Sum or Average | 0.116768E+11 | 0.108640E+11 | 0.234351E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.115854E+09 | 0.354010E+10 |
Minimum of Months | 0.882782E+09 | 0.833132E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 65884684.08 |
Maximum of Months | 0.105485E+10 | 0.971637E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 45117335.14 | 0.485076E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150991E+10 | 0.153750E+10 | 0.305979E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.141816E+10 |
February | 0.136985E+10 | 0.134347E+10 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.133039E+10 |
March | 0.163685E+10 | 0.151582E+10 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.132102E+10 |
April | 0.145243E+10 | 0.130296E+10 | 0.295462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2419395.76 | 0.957584E+09 |
May | 0.157338E+10 | 0.138900E+10 | 0.312174E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23944181.63 | 0.670004E+09 |
June | 0.156900E+10 | 0.135953E+10 | 0.306580E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.113886E+09 | 0.366794E+09 |
July | 0.145680E+10 | 0.128920E+10 | 0.300989E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.163495E+09 | 0.211752E+09 |
August | 0.163685E+10 | 0.144228E+10 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 84450726.43 | 0.274367E+09 |
September | 0.145243E+10 | 0.133384E+10 | 0.295328E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 28616144.74 | 0.399690E+09 |
October | 0.150991E+10 | 0.145082E+10 | 0.306046E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6834835.58 | 0.717439E+09 |
November | 0.149516E+10 | 0.152276E+10 | 0.299314E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.113686E+10 |
December | 0.145680E+10 | 0.156033E+10 | 0.300922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.129833E+10 |
Annual Sum or Average | 0.181194E+11 | 0.170475E+11 | 0.363654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.423646E+09 | 0.101024E+11 |
Minimum of Months | 0.136985E+10 | 0.128920E+10 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.211752E+09 |
Maximum of Months | 0.163685E+10 | 0.156033E+10 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.163495E+09 | 0.141816E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.715730E+09 | 0.976446E+09 | 0.197184E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.980015E+09 |
February | 0.649041E+09 | 0.859414E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.915669E+09 |
March | 0.773965E+09 | 0.972352E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.910106E+09 |
April | 0.688021E+09 | 0.842663E+09 | 0.190407E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1643694.29 | 0.681407E+09 |
May | 0.744847E+09 | 0.901762E+09 | 0.201177E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15596379.75 | 0.465164E+09 |
June | 0.742030E+09 | 0.883062E+09 | 0.197572E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 79088823.77 | 0.244693E+09 |
July | 0.690839E+09 | 0.835708E+09 | 0.193969E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.112021E+09 | 0.148387E+09 |
August | 0.773965E+09 | 0.932562E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 57482935.02 | 0.191861E+09 |
September | 0.688021E+09 | 0.857864E+09 | 0.190321E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18958676.53 | 0.274113E+09 |
October | 0.715730E+09 | 0.921129E+09 | 0.197228E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4424976.93 | 0.501959E+09 |
November | 0.708685E+09 | 0.975587E+09 | 0.192889E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.789781E+09 |
December | 0.690839E+09 | 0.991317E+09 | 0.193926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.892051E+09 |
Annual Sum or Average | 0.858171E+10 | 0.109499E+11 | 0.234352E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.289216E+09 | 0.699521E+10 |
Minimum of Months | 0.649041E+09 | 0.835708E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.148387E+09 |
Maximum of Months | 0.773965E+09 | 0.991317E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.112021E+09 | 0.980015E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150994E+10 | 0.148008E+10 | 0.305983E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.162546E+10 |
February | 0.136988E+10 | 0.131428E+10 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.150681E+10 |
March | 0.163688E+10 | 0.150632E+10 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.143999E+10 |
April | 0.145246E+10 | 0.130719E+10 | 0.295467E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2177556.29 | 0.102630E+10 |
May | 0.157341E+10 | 0.139986E+10 | 0.312179E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21358896.14 | 0.682019E+09 |
June | 0.156904E+10 | 0.137469E+10 | 0.306585E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.117929E+09 | 0.356452E+09 |
July | 0.145684E+10 | 0.130028E+10 | 0.300994E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.164291E+09 | 0.210595E+09 |
August | 0.163688E+10 | 0.144860E+10 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 81693435.57 | 0.290227E+09 |
September | 0.145246E+10 | 0.133147E+10 | 0.295333E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23622728.67 | 0.445682E+09 |
October | 0.150994E+10 | 0.141735E+10 | 0.306051E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4501555.24 | 0.830692E+09 |
November | 0.149520E+10 | 0.147447E+10 | 0.299318E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.132976E+10 |
December | 0.145684E+10 | 0.148522E+10 | 0.300927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.149575E+10 |
Annual Sum or Average | 0.181198E+11 | 0.168398E+11 | 0.363660E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.415575E+09 | 0.112397E+11 |
Minimum of Months | 0.136988E+10 | 0.130028E+10 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.210595E+09 |
Maximum of Months | 0.163688E+10 | 0.150632E+10 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.164291E+09 | 0.162546E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.964281E+09 | 0.197183E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.100453E+10 |
February | 0.882782E+09 | 0.851082E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.944585E+09 |
March | 0.105485E+10 | 0.970554E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.937383E+09 |
April | 0.936002E+09 | 0.836551E+09 | 0.190406E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1448659.02 | 0.702511E+09 |
May | 0.101394E+10 | 0.892753E+09 | 0.201175E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14048856.97 | 0.479455E+09 |
June | 0.101113E+10 | 0.878726E+09 | 0.197570E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 73481846.27 | 0.265249E+09 |
July | 0.938820E+09 | 0.832597E+09 | 0.193968E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.107527E+09 | 0.158218E+09 |
August | 0.105485E+10 | 0.928974E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 54424976.02 | 0.208991E+09 |
September | 0.936002E+09 | 0.855750E+09 | 0.190319E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18144969.61 | 0.294020E+09 |
October | 0.973041E+09 | 0.922558E+09 | 0.197226E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4180111.84 | 0.518561E+09 |
November | 0.963541E+09 | 0.951053E+09 | 0.192888E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.812619E+09 |
December | 0.938820E+09 | 0.969119E+09 | 0.193924E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.924771E+09 |
Annual Sum or Average | 0.116768E+11 | 0.108540E+11 | 0.234351E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.273256E+09 | 0.725089E+10 |
Minimum of Months | 0.882782E+09 | 0.832597E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.158218E+09 |
Maximum of Months | 0.105485E+10 | 0.970554E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.107527E+09 | 0.100453E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150991E+10 | 0.153723E+10 | 0.305979E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.163021E+10 |
February | 0.136985E+10 | 0.134324E+10 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.154394E+10 |
March | 0.163685E+10 | 0.151544E+10 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.152468E+10 |
April | 0.145243E+10 | 0.130296E+10 | 0.295462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2695721.88 | 0.112522E+10 |
May | 0.157338E+10 | 0.138896E+10 | 0.312174E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 26578973.42 | 0.803797E+09 |
June | 0.156900E+10 | 0.135953E+10 | 0.306580E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.137402E+09 | 0.447384E+09 |
July | 0.145680E+10 | 0.128918E+10 | 0.300989E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.195686E+09 | 0.267927E+09 |
August | 0.163685E+10 | 0.144227E+10 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.100091E+09 | 0.340356E+09 |
September | 0.145243E+10 | 0.133377E+10 | 0.295328E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 33392337.44 | 0.482439E+09 |
October | 0.150991E+10 | 0.145076E+10 | 0.306046E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8022202.69 | 0.827006E+09 |
November | 0.149516E+10 | 0.152268E+10 | 0.299314E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.128321E+10 |
December | 0.145680E+10 | 0.156010E+10 | 0.300922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.147703E+10 |
Annual Sum or Average | 0.181194E+11 | 0.170461E+11 | 0.363654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.503868E+09 | 0.117532E+11 |
Minimum of Months | 0.136985E+10 | 0.128918E+10 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.267927E+09 |
Maximum of Months | 0.163685E+10 | 0.156010E+10 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.195686E+09 | 0.163021E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.976446E+09 | 0.197184E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.112517E+10 |
February | 0.882782E+09 | 0.859286E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.106758E+10 |
March | 0.105485E+10 | 0.972345E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.106893E+10 |
April | 0.936002E+09 | 0.842592E+09 | 0.190407E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1702387.42 | 0.821562E+09 |
May | 0.101394E+10 | 0.901756E+09 | 0.201177E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17240966.93 | 0.568467E+09 |
June | 0.101113E+10 | 0.883062E+09 | 0.197572E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 93998012.90 | 0.302222E+09 |
July | 0.938820E+09 | 0.835708E+09 | 0.193969E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.132911E+09 | 0.189307E+09 |
August | 0.105485E+10 | 0.932519E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 67759248.75 | 0.239632E+09 |
September | 0.936002E+09 | 0.857864E+09 | 0.190321E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21908946.38 | 0.335622E+09 |
October | 0.973041E+09 | 0.921129E+09 | 0.197228E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5018028.39 | 0.592513E+09 |
November | 0.963541E+09 | 0.975482E+09 | 0.192889E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.903679E+09 |
December | 0.938820E+09 | 0.991209E+09 | 0.193926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.101549E+10 |
Annual Sum or Average | 0.116768E+11 | 0.109494E+11 | 0.234352E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.340539E+09 | 0.823018E+10 |
Minimum of Months | 0.882782E+09 | 0.835708E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.189307E+09 |
Maximum of Months | 0.105485E+10 | 0.991209E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.132911E+09 | 0.112517E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150994E+10 | 0.148008E+10 | 0.305983E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.186600E+10 |
February | 0.136988E+10 | 0.131428E+10 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.175672E+10 |
March | 0.163688E+10 | 0.150627E+10 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.168742E+10 |
April | 0.145246E+10 | 0.130714E+10 | 0.295467E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2348443.49 | 0.122016E+10 |
May | 0.157341E+10 | 0.139986E+10 | 0.312179E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 24414852.03 | 0.821301E+09 |
June | 0.156904E+10 | 0.137463E+10 | 0.306585E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.141707E+09 | 0.434370E+09 |
July | 0.145684E+10 | 0.130015E+10 | 0.300994E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.196423E+09 | 0.266423E+09 |
August | 0.163688E+10 | 0.144859E+10 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 97505286.94 | 0.360149E+09 |
September | 0.145246E+10 | 0.133139E+10 | 0.295333E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 28748670.87 | 0.542112E+09 |
October | 0.150994E+10 | 0.141732E+10 | 0.306051E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5871138.18 | 0.980014E+09 |
November | 0.149520E+10 | 0.147427E+10 | 0.299318E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.153609E+10 |
December | 0.145684E+10 | 0.148522E+10 | 0.300927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.171179E+10 |
Annual Sum or Average | 0.181198E+11 | 0.168392E+11 | 0.363660E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.497018E+09 | 0.131825E+11 |
Minimum of Months | 0.136988E+10 | 0.130015E+10 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.266423E+09 |
Maximum of Months | 0.163688E+10 | 0.150627E+10 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.196423E+09 | 0.186600E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.964235E+09 | 0.197183E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.116047E+10 |
February | 0.882782E+09 | 0.851006E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.110977E+10 |
March | 0.105485E+10 | 0.970534E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.110462E+10 |
April | 0.936002E+09 | 0.836551E+09 | 0.190406E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1564366.73 | 0.842392E+09 |
May | 0.101394E+10 | 0.892691E+09 | 0.201175E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16336175.92 | 0.579648E+09 |
June | 0.101113E+10 | 0.878712E+09 | 0.197570E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 89797011.25 | 0.324699E+09 |
July | 0.938820E+09 | 0.832566E+09 | 0.193968E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.129236E+09 | 0.198696E+09 |
August | 0.105485E+10 | 0.928969E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 65315080.69 | 0.257853E+09 |
September | 0.936002E+09 | 0.855743E+09 | 0.190319E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21504226.73 | 0.357471E+09 |
October | 0.973041E+09 | 0.922511E+09 | 0.197226E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4947888.41 | 0.613115E+09 |
November | 0.963541E+09 | 0.951053E+09 | 0.192888E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.938837E+09 |
December | 0.938820E+09 | 0.969119E+09 | 0.193924E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.106403E+10 |
Annual Sum or Average | 0.116768E+11 | 0.108537E+11 | 0.234351E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.328700E+09 | 0.855161E+10 |
Minimum of Months | 0.882782E+09 | 0.832566E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.198696E+09 |
Maximum of Months | 0.105485E+10 | 0.970534E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.129236E+09 | 0.116047E+10 |
Report: SpaceGainsMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.174411E+09 | 0.553024E+09 | 0.521915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.158233E+09 | 0.501634E+09 | 0.942813E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.189074E+09 | 0.596080E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.167772E+09 | 0.532421E+09 | 0.201821E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.181743E+09 | 0.574552E+09 | 0.522616E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.181238E+09 | 0.571774E+09 | 0.101086E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.168277E+09 | 0.535199E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.189074E+09 | 0.596080E+09 | 0.208555E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.167772E+09 | 0.532421E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.174411E+09 | 0.553024E+09 | 0.104453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.172708E+09 | 0.546542E+09 | 0.151524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.168277E+09 | 0.535199E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.209299E+10 | 0.662795E+10 | 0.153881E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.158233E+09 | 0.501634E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.189074E+09 | 0.596080E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.174411E+09 | 0.553024E+09 | 0.521915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.158233E+09 | 0.501634E+09 | 0.942813E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.189074E+09 | 0.596080E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.167772E+09 | 0.532421E+09 | 0.201821E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.181743E+09 | 0.574552E+09 | 0.522616E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.181238E+09 | 0.571774E+09 | 0.101086E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.168277E+09 | 0.535199E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.189074E+09 | 0.596080E+09 | 0.208555E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.167772E+09 | 0.532421E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.174411E+09 | 0.553024E+09 | 0.104453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.172708E+09 | 0.546542E+09 | 0.151524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.168277E+09 | 0.535199E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.209299E+10 | 0.662795E+10 | 0.153881E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.158233E+09 | 0.501634E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.189074E+09 | 0.596080E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.174411E+09 | 0.553024E+09 | 0.521915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.158233E+09 | 0.501634E+09 | 0.942813E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.189074E+09 | 0.596080E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.167772E+09 | 0.532421E+09 | 0.201821E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.181743E+09 | 0.574552E+09 | 0.522616E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.181238E+09 | 0.571774E+09 | 0.101086E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.168277E+09 | 0.535199E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.189074E+09 | 0.596080E+09 | 0.208555E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.167772E+09 | 0.532421E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.174411E+09 | 0.553024E+09 | 0.104453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.172708E+09 | 0.546542E+09 | 0.151524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.168277E+09 | 0.535199E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.209299E+10 | 0.662795E+10 | 0.153881E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.158233E+09 | 0.501634E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.189074E+09 | 0.596080E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.377547E+10 | 0.618367E+10 | 0.254202E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.342526E+10 | 0.560905E+10 | 0.459203E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.409289E+10 | 0.666512E+10 | 0.762947E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.363176E+10 | 0.595330E+10 | 0.982982E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.393418E+10 | 0.642439E+10 | 0.254544E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.392325E+10 | 0.639333E+10 | 0.492345E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.364269E+10 | 0.598436E+10 | 0.762947E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.409289E+10 | 0.666512E+10 | 0.101578E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.363176E+10 | 0.595330E+10 | 0.246344E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.377547E+10 | 0.618367E+10 | 0.508746E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.373861E+10 | 0.611120E+10 | 0.738006E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.364269E+10 | 0.598436E+10 | 0.101681E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.453069E+11 | 0.741109E+11 | 0.749486E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.342526E+10 | 0.560905E+10 | 0.246344E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.409289E+10 | 0.666512E+10 | 0.101681E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.152184E+10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.140321E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.136651E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 742492.71 | 0.973266E+09 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17376743.99 | 0.653299E+09 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 94223282.12 | 0.343090E+09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.138542E+09 | 0.183599E+09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 65866070.51 | 0.250329E+09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19825667.51 | 0.394772E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3602915.75 | 0.749506E+09 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.122757E+10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.141551E+10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.340180E+09 | 0.104825E+11 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.183599E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.138542E+09 | 0.152184E+10 |
Report: SpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.257506E+10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.239577E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.234567E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1504044.65 | 0.167088E+10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34116755.08 | 0.113977E+10 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.171638E+09 | 0.603163E+09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.251707E+09 | 0.332534E+09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.120537E+09 | 0.455206E+09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36570142.33 | 0.687339E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6803786.92 | 0.129357E+10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.209182E+10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.237672E+10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.622876E+09 | 0.179675E+11 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.332534E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.251707E+09 | 0.257506E+10 |
Report: SpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.260285E+10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.249563E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.250132E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 63492.57 | 0.185990E+10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18205370.89 | 0.128539E+10 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.157489E+09 | 0.679547E+09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.224201E+09 | 0.393782E+09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.104409E+09 | 0.527898E+09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25268592.38 | 0.777048E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3421105.95 | 0.137501E+10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.214403E+10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.238593E+10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.533057E+09 | 0.190283E+11 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.393782E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.224201E+09 | 0.260285E+10 |
Report: PeakSpaceGainsMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 17832.21 | 02-JAN-10:09 | 22950.34 | 02-JAN-08:09 | 13457.54 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 17832.21 | 01-FEB-10:09 | 22950.34 | 01-FEB-08:09 | 13457.54 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 17832.21 | 01-MAR-10:09 | 22950.34 | 01-MAR-08:09 | 13457.54 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 17832.21 | 03-APR-09:09 | 22950.34 | 03-APR-07:10 | 13457.54 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 17832.21 | 01-MAY-09:09 | 22950.34 | 01-MAY-07:10 | 13457.54 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 17832.21 | 01-JUN-09:09 | 22950.34 | 01-JUN-07:10 | 13457.54 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 17832.21 | 03-JUL-09:09 | 22950.34 | 03-JUL-07:10 | 13457.54 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 17832.21 | 01-AUG-09:09 | 22950.34 | 01-AUG-07:10 | 13457.54 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 17832.21 | 01-SEP-09:09 | 22950.34 | 01-SEP-07:10 | 13457.54 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 17832.21 | 02-OCT-09:09 | 22950.34 | 02-OCT-07:10 | 13457.54 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 17832.21 | 01-NOV-09:09 | 22950.34 | 01-NOV-07:10 | 13457.54 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 17832.21 | 01-DEC-10:09 | 22950.34 | 01-DEC-08:09 | 13457.54 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 17832.21 | 22950.34 | 13457.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 17832.21 | 22950.34 | 13457.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 16014.58 | 02-JAN-10:09 | 20611.01 | 02-JAN-08:09 | 17206.63 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 16014.58 | 01-FEB-10:09 | 20611.01 | 01-FEB-08:09 | 17206.63 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 16014.58 | 01-MAR-10:09 | 20611.01 | 01-MAR-08:09 | 17206.63 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 16014.58 | 03-APR-09:09 | 20611.01 | 03-APR-07:10 | 17206.63 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 16014.58 | 01-MAY-09:09 | 20611.01 | 01-MAY-07:10 | 17206.63 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 16014.58 | 01-JUN-09:09 | 20611.01 | 01-JUN-07:10 | 17206.63 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 16014.58 | 03-JUL-09:09 | 20611.01 | 03-JUL-07:10 | 17206.63 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 16014.58 | 01-AUG-09:09 | 20611.01 | 01-AUG-07:10 | 17206.63 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 16014.58 | 01-SEP-09:09 | 20611.01 | 01-SEP-07:10 | 17206.63 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 16014.58 | 02-OCT-09:09 | 20611.01 | 02-OCT-07:10 | 17206.63 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 16014.58 | 01-NOV-09:09 | 20611.01 | 01-NOV-07:10 | 17206.63 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 16014.58 | 01-DEC-10:09 | 20611.01 | 01-DEC-08:09 | 17206.63 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 16014.58 | 20611.01 | 17206.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 16014.58 | 20611.01 | 17206.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 16014.58 | 02-JAN-10:09 | 20611.01 | 02-JAN-08:09 | 17206.56 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 16014.58 | 01-FEB-10:09 | 20611.01 | 01-FEB-08:09 | 17206.56 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 16014.58 | 01-MAR-10:09 | 20611.01 | 01-MAR-08:09 | 17206.56 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 16014.58 | 03-APR-09:09 | 20611.01 | 03-APR-07:10 | 17206.56 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 16014.58 | 01-MAY-09:09 | 20611.01 | 01-MAY-07:10 | 17206.56 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 16014.58 | 01-JUN-09:09 | 20611.01 | 01-JUN-07:10 | 17206.56 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 16014.58 | 03-JUL-09:09 | 20611.01 | 03-JUL-07:10 | 17206.56 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 16014.58 | 01-AUG-09:09 | 20611.01 | 01-AUG-07:10 | 17206.56 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 16014.58 | 01-SEP-09:09 | 20611.01 | 01-SEP-07:10 | 17206.56 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 16014.58 | 02-OCT-09:09 | 20611.01 | 02-OCT-07:10 | 17206.56 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 16014.58 | 01-NOV-09:09 | 20611.01 | 01-NOV-07:10 | 17206.56 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 16014.58 | 01-DEC-10:09 | 20611.01 | 01-DEC-08:09 | 17206.56 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 16014.58 | 20611.01 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 16014.58 | 20611.01 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 16014.58 | 02-JAN-10:09 | 20611.01 | 02-JAN-08:09 | 17206.56 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 16014.58 | 01-FEB-10:09 | 20611.01 | 01-FEB-08:09 | 17206.56 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 16014.58 | 01-MAR-10:09 | 20611.01 | 01-MAR-08:09 | 17206.56 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 16014.58 | 03-APR-09:09 | 20611.01 | 03-APR-07:10 | 17206.56 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 16014.58 | 01-MAY-09:09 | 20611.01 | 01-MAY-07:10 | 17206.56 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 16014.58 | 01-JUN-09:09 | 20611.01 | 01-JUN-07:10 | 17206.56 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 16014.58 | 03-JUL-09:09 | 20611.01 | 03-JUL-07:10 | 17206.56 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 16014.58 | 01-AUG-09:09 | 20611.01 | 01-AUG-07:10 | 17206.56 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 16014.58 | 01-SEP-09:09 | 20611.01 | 01-SEP-07:10 | 17206.56 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 16014.58 | 02-OCT-09:09 | 20611.01 | 02-OCT-07:10 | 17206.56 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 16014.58 | 01-NOV-09:09 | 20611.01 | 01-NOV-07:10 | 17206.56 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 16014.58 | 01-DEC-10:09 | 20611.01 | 01-DEC-08:09 | 17206.56 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 16014.58 | 20611.01 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 16014.58 | 20611.01 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.79 | 02-JAN-10:09 | 2587.92 | 04-JAN-16:00 | 2160.55 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 1983.71 | 16-JAN-18:00 |
February | 2010.79 | 01-FEB-10:09 | 2255.20 | 16-FEB-08:09 | 2160.55 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1488.47 | 05-FEB-01:00 |
March | 2010.79 | 01-MAR-10:09 | 1803.00 | 20-MAR-07:10 | 2160.55 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1332.71 | 14-MAR-03:00 |
April | 2010.79 | 03-APR-09:09 | 1231.33 | 03-APR-07:10 | 2160.55 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 26.39 | 29-APR-16:00 | 1462.89 | 07-APR-22:00 |
May | 2010.79 | 01-MAY-09:09 | 1470.28 | 22-MAY-07:10 | 2160.55 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 137.75 | 14-MAY-17:00 | 908.29 | 03-MAY-22:00 |
June | 2010.79 | 01-JUN-09:09 | 1470.28 | 01-JUN-15:00 | 2160.55 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 359.13 | 18-JUN-16:14 | 693.60 | 10-JUN-01:00 |
July | 2010.79 | 03-JUL-09:09 | 1470.28 | 07-JUL-15:39 | 2160.55 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 485.64 | 04-JUL-14:51 | 350.49 | 15-JUL-18:52 |
August | 2010.79 | 01-AUG-09:09 | 1231.33 | 01-AUG-07:10 | 2160.55 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 261.55 | 20-AUG-16:53 | 357.59 | 10-AUG-21:30 |
September | 2010.79 | 01-SEP-09:09 | 2255.20 | 08-SEP-07:10 | 2160.55 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 172.14 | 03-SEP-15:00 | 516.97 | 18-SEP-00:55 |
October | 2010.79 | 02-OCT-09:09 | 2255.20 | 25-OCT-07:10 | 2160.55 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 74.99 | 01-OCT-16:10 | 833.10 | 11-OCT-23:00 |
November | 2010.79 | 01-NOV-09:09 | 2587.92 | 08-NOV-16:00 | 2160.55 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1496.87 | 26-NOV-05:55 |
December | 2010.79 | 01-DEC-10:09 | 2587.92 | 01-DEC-16:30 | 2160.55 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 2099.96 | 14-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.79 | 1231.33 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 350.49 | |||||
Maximum of Months | 2010.79 | 2587.92 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 485.64 | 2099.96 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 1667.75 | 04-JAN-16:00 | 1392.34 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 1328.22 | 16-JAN-18:00 |
February | 1295.83 | 01-FEB-10:09 | 1453.34 | 16-FEB-08:09 | 1392.34 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 994.48 | 05-FEB-01:00 |
March | 1295.83 | 01-MAR-10:09 | 1161.92 | 14-MAR-15:00 | 1392.34 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 878.37 | 14-MAR-03:00 |
April | 1295.83 | 03-APR-09:09 | 793.52 | 03-APR-07:10 | 1392.34 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 17.59 | 29-APR-16:00 | 1013.58 | 23-APR-09:00 |
May | 1295.83 | 01-MAY-09:09 | 870.51 | 03-MAY-15:30 | 1392.34 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 117.50 | 14-MAY-17:00 | 592.08 | 03-MAY-22:00 |
June | 1295.83 | 01-JUN-09:09 | 947.51 | 01-JUN-15:00 | 1392.34 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 279.22 | 18-JUN-16:14 | 451.70 | 10-JUN-01:00 |
July | 1295.83 | 03-JUL-09:09 | 947.51 | 07-JUL-15:39 | 1392.34 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 341.11 | 04-JUL-15:04 | 222.67 | 15-JUL-18:52 |
August | 1295.83 | 01-AUG-09:09 | 793.52 | 01-AUG-07:10 | 1392.34 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 191.30 | 05-AUG-17:10 | 322.63 | 27-AUG-07:40 |
September | 1295.83 | 01-SEP-09:09 | 1453.34 | 08-SEP-07:10 | 1392.34 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 122.79 | 03-SEP-15:00 | 351.56 | 18-SEP-00:55 |
October | 1295.83 | 02-OCT-09:09 | 1161.92 | 25-OCT-07:10 | 1392.34 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 61.70 | 01-OCT-16:10 | 547.97 | 11-OCT-23:00 |
November | 1295.83 | 01-NOV-09:09 | 1667.75 | 08-NOV-16:49 | 1392.34 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 978.71 | 26-NOV-05:55 |
December | 1295.83 | 01-DEC-10:09 | 1667.75 | 01-DEC-16:30 | 1392.34 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1372.31 | 14-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 793.52 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 222.67 | |||||
Maximum of Months | 1295.83 | 1667.75 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 341.11 | 1372.31 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.83 | 02-JAN-10:09 | 2255.25 | 04-JAN-16:49 | 2160.58 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 1977.95 | 16-JAN-18:00 |
February | 2010.83 | 01-FEB-10:09 | 2255.25 | 16-FEB-08:09 | 2160.58 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1544.85 | 05-FEB-01:00 |
March | 2010.83 | 01-MAR-10:09 | 1803.04 | 20-MAR-07:10 | 2160.58 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1347.46 | 14-MAR-03:00 |
April | 2010.83 | 03-APR-09:09 | 1231.36 | 03-APR-07:10 | 2160.58 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 26.39 | 29-APR-16:00 | 1473.27 | 07-APR-22:00 |
May | 2010.83 | 01-MAY-09:09 | 1470.31 | 22-MAY-07:10 | 2160.58 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 143.31 | 14-MAY-17:00 | 891.30 | 03-MAY-22:00 |
June | 2010.83 | 01-JUN-09:09 | 1470.31 | 01-JUN-15:00 | 2160.58 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 384.46 | 18-JUN-16:20 | 676.02 | 10-JUN-01:00 |
July | 2010.83 | 03-JUL-09:09 | 1470.31 | 07-JUL-15:50 | 2160.58 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 488.98 | 04-JUL-15:04 | 352.63 | 15-JUL-18:52 |
August | 2010.83 | 01-AUG-09:09 | 1231.36 | 01-AUG-07:10 | 2160.58 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 261.60 | 20-AUG-16:53 | 368.35 | 22-AUG-21:30 |
September | 2010.83 | 01-SEP-09:09 | 2255.25 | 08-SEP-07:10 | 2160.58 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 160.32 | 03-SEP-14:54 | 550.25 | 18-SEP-00:55 |
October | 2010.83 | 02-OCT-09:09 | 2255.25 | 25-OCT-07:10 | 2160.58 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 62.59 | 11-OCT-14:30 | 858.30 | 11-OCT-23:00 |
November | 2010.83 | 01-NOV-09:09 | 2587.98 | 09-NOV-16:49 | 2160.58 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1509.43 | 03-NOV-24:00 |
December | 2010.83 | 01-DEC-10:09 | 2587.98 | 01-DEC-16:40 | 2160.58 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 2134.68 | 14-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.83 | 1231.36 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 352.63 | |||||
Maximum of Months | 2010.83 | 2587.98 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 488.98 | 2134.68 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 1453.34 | 04-JAN-16:49 | 1392.33 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 1392.37 | 16-JAN-18:00 |
February | 1295.83 | 01-FEB-10:09 | 1453.34 | 16-FEB-08:09 | 1392.33 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1088.68 | 05-FEB-01:00 |
March | 1295.83 | 01-MAR-10:09 | 1161.92 | 17-MAR-07:10 | 1392.33 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 992.06 | 14-MAR-03:00 |
April | 1295.83 | 03-APR-09:09 | 793.52 | 03-APR-07:10 | 1392.33 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 17.59 | 29-APR-16:00 | 1106.04 | 07-APR-22:00 |
May | 1295.83 | 01-MAY-09:09 | 947.51 | 22-MAY-07:10 | 1392.33 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 81.59 | 14-MAY-16:53 | 652.71 | 18-MAY-02:00 |
June | 1295.83 | 01-JUN-09:09 | 1161.92 | 08-JUN-07:10 | 1392.33 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 235.38 | 18-JUN-16:00 | 547.56 | 10-JUN-01:00 |
July | 1295.83 | 03-JUL-09:09 | 947.51 | 07-JUL-15:50 | 1392.33 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 312.48 | 04-JUL-15:10 | 276.41 | 15-JUL-18:52 |
August | 1295.83 | 01-AUG-09:09 | 870.51 | 28-AUG-07:10 | 1392.33 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 167.85 | 20-AUG-16:53 | 326.34 | 22-AUG-21:30 |
September | 1295.83 | 01-SEP-09:09 | 1453.34 | 08-SEP-07:10 | 1392.33 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 131.70 | 03-SEP-14:56 | 394.43 | 18-SEP-00:55 |
October | 1295.83 | 02-OCT-09:09 | 1453.34 | 25-OCT-07:10 | 1392.33 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 44.12 | 11-OCT-13:00 | 612.02 | 11-OCT-23:00 |
November | 1295.83 | 01-NOV-09:09 | 1667.75 | 09-NOV-16:49 | 1392.33 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1100.43 | 03-NOV-24:00 |
December | 1295.83 | 01-DEC-10:09 | 1667.75 | 01-DEC-16:49 | 1392.33 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1550.72 | 14-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 793.52 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 276.41 | |||||
Maximum of Months | 1295.83 | 1667.75 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 312.48 | 1550.72 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.79 | 02-JAN-10:09 | 2587.92 | 04-JAN-16:00 | 2160.55 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 3769.58 | 16-JAN-18:00 |
February | 2010.79 | 01-FEB-10:09 | 2255.20 | 16-FEB-08:09 | 2160.55 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 2957.47 | 05-FEB-01:00 |
March | 2010.79 | 01-MAR-10:09 | 1803.00 | 20-MAR-07:10 | 2160.55 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 2627.61 | 14-MAR-03:00 |
April | 2010.79 | 03-APR-09:09 | 1231.33 | 03-APR-07:10 | 2160.55 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 59.56 | 01-APR-17:10 | 3072.48 | 07-APR-22:00 |
May | 2010.79 | 01-MAY-09:09 | 1350.81 | 22-MAY-07:10 | 2160.55 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 306.04 | 14-MAY-17:10 | 1960.57 | 03-MAY-22:00 |
June | 2010.79 | 01-JUN-09:09 | 1470.28 | 08-JUN-15:20 | 2160.55 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 829.74 | 18-JUN-16:14 | 1474.98 | 04-JUN-16:53 |
July | 2010.79 | 03-JUL-09:09 | 1470.28 | 07-JUL-15:50 | 2160.55 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1186.29 | 04-JUL-14:54 | 819.42 | 15-JUL-18:52 |
August | 2010.79 | 01-AUG-09:09 | 1231.33 | 01-AUG-07:10 | 2160.55 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 580.44 | 20-AUG-16:51 | 775.89 | 22-AUG-22:00 |
September | 2010.79 | 01-SEP-09:09 | 2255.20 | 08-SEP-07:10 | 2160.55 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 363.02 | 03-SEP-14:27 | 1088.11 | 07-SEP-22:00 |
October | 2010.79 | 02-OCT-09:09 | 2255.20 | 25-OCT-07:10 | 2160.55 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 190.73 | 01-OCT-16:00 | 1806.30 | 11-OCT-23:00 |
November | 2010.79 | 01-NOV-09:09 | 2587.92 | 08-NOV-16:00 | 2160.55 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 3100.81 | 03-NOV-21:03 |
December | 2010.79 | 01-DEC-10:09 | 2587.92 | 01-DEC-16:30 | 2160.55 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 4095.23 | 14-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.79 | 1231.33 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 775.89 | |||||
Maximum of Months | 2010.79 | 2587.92 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 1186.29 | 4095.23 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1239.33 | 02-JAN-08:09 | 1667.75 | 04-JAN-16:00 | 1392.34 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 2578.26 | 16-JAN-18:00 |
February | 1239.33 | 01-FEB-08:09 | 1453.34 | 16-FEB-08:09 | 1392.34 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 2023.52 | 05-FEB-01:00 |
March | 1239.33 | 01-MAR-08:09 | 947.51 | 02-MAR-16:49 | 1392.34 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1799.48 | 14-MAR-03:00 |
April | 1239.33 | 03-APR-07:10 | 793.52 | 03-APR-07:10 | 1392.34 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 49.21 | 01-APR-17:50 | 2333.28 | 23-APR-09:00 |
May | 1239.33 | 01-MAY-07:10 | 870.51 | 22-MAY-07:10 | 1392.34 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 235.30 | 14-MAY-17:10 | 1279.49 | 03-MAY-22:00 |
June | 1239.33 | 01-JUN-07:10 | 947.51 | 08-JUN-15:20 | 1392.34 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 633.31 | 18-JUN-16:14 | 1017.02 | 04-JUN-16:53 |
July | 1239.33 | 03-JUL-07:10 | 947.51 | 07-JUL-15:50 | 1392.34 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 808.35 | 04-JUL-14:54 | 571.72 | 15-JUL-18:52 |
August | 1239.33 | 01-AUG-07:10 | 793.52 | 01-AUG-07:10 | 1392.34 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 421.79 | 05-AUG-17:10 | 805.18 | 27-AUG-08:00 |
September | 1239.33 | 01-SEP-07:10 | 1453.34 | 08-SEP-07:10 | 1392.34 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 262.80 | 03-SEP-14:25 | 744.57 | 18-SEP-00:55 |
October | 1239.33 | 02-OCT-07:10 | 1161.92 | 25-OCT-07:10 | 1392.34 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 128.92 | 01-OCT-16:20 | 1202.61 | 11-OCT-23:00 |
November | 1239.33 | 01-NOV-07:10 | 1667.75 | 08-NOV-16:49 | 1392.34 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 2072.81 | 26-NOV-09:53 |
December | 1239.33 | 01-DEC-08:09 | 1667.75 | 01-DEC-16:30 | 1392.34 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 2761.01 | 14-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1239.33 | 793.52 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 571.72 | |||||
Maximum of Months | 1239.33 | 1667.75 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 808.35 | 2761.01 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.83 | 02-JAN-10:09 | 2255.25 | 04-JAN-16:49 | 2160.58 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 4262.81 | 16-JAN-18:00 |
February | 2010.83 | 01-FEB-10:09 | 2255.25 | 16-FEB-08:09 | 2160.58 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 3339.03 | 05-FEB-01:00 |
March | 2010.83 | 01-MAR-10:09 | 1803.04 | 20-MAR-07:10 | 2160.58 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 2824.38 | 14-MAR-03:00 |
April | 2010.83 | 03-APR-09:09 | 1231.36 | 03-APR-07:10 | 2160.58 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 57.68 | 29-APR-16:00 | 3174.76 | 07-APR-22:00 |
May | 2010.83 | 01-MAY-09:09 | 1470.31 | 22-MAY-07:10 | 2160.58 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 275.74 | 14-MAY-17:10 | 1931.66 | 03-MAY-22:00 |
June | 2010.83 | 01-JUN-09:09 | 1470.31 | 08-JUN-07:10 | 2160.58 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 845.52 | 18-JUN-16:14 | 1473.58 | 04-JUN-16:53 |
July | 2010.83 | 03-JUL-09:09 | 1470.31 | 07-JUL-15:50 | 2160.58 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1214.57 | 04-JUL-14:54 | 837.18 | 15-JUL-18:52 |
August | 2010.83 | 01-AUG-09:09 | 1231.36 | 01-AUG-07:10 | 2160.58 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 580.60 | 20-AUG-16:44 | 820.00 | 22-AUG-22:00 |
September | 2010.83 | 01-SEP-09:09 | 2255.25 | 08-SEP-07:10 | 2160.58 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 346.91 | 03-SEP-14:47 | 1270.36 | 17-SEP-19:53 |
October | 2010.83 | 02-OCT-09:09 | 2255.25 | 25-OCT-07:10 | 2160.58 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 121.17 | 11-OCT-15:00 | 1901.83 | 11-OCT-23:00 |
November | 2010.83 | 01-NOV-09:09 | 2587.98 | 09-NOV-16:49 | 2160.58 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 3443.03 | 26-NOV-10:00 |
December | 2010.83 | 01-DEC-10:09 | 2587.98 | 01-DEC-16:40 | 2160.58 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 4465.25 | 14-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.83 | 1231.36 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 820.00 | |||||
Maximum of Months | 2010.83 | 2587.98 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 1214.57 | 4465.25 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 1453.34 | 04-JAN-16:49 | 1392.33 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 2701.59 | 16-JAN-18:00 |
February | 1295.83 | 01-FEB-10:09 | 1453.34 | 16-FEB-08:09 | 1392.33 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 2151.31 | 05-FEB-01:00 |
March | 1295.83 | 01-MAR-10:09 | 1161.92 | 17-MAR-07:10 | 1392.33 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1833.42 | 14-MAR-03:00 |
April | 1295.83 | 03-APR-09:09 | 793.52 | 03-APR-07:10 | 1392.33 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 38.45 | 29-APR-16:00 | 2370.49 | 15-APR-17:02 |
May | 1295.83 | 01-MAY-09:09 | 947.51 | 22-MAY-07:10 | 1392.33 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 167.71 | 21-MAY-16:50 | 1334.86 | 18-MAY-02:00 |
June | 1295.83 | 01-JUN-09:09 | 947.51 | 08-JUN-07:10 | 1392.33 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 541.06 | 18-JUN-16:00 | 1080.45 | 10-JUN-01:00 |
July | 1295.83 | 03-JUL-09:09 | 947.51 | 07-JUL-15:00 | 1392.33 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 764.30 | 04-JUL-15:00 | 617.01 | 15-JUL-18:52 |
August | 1295.83 | 01-AUG-09:09 | 870.51 | 28-AUG-07:10 | 1392.33 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 386.03 | 20-AUG-17:00 | 604.81 | 08-AUG-01:00 |
September | 1295.83 | 01-SEP-09:09 | 1453.34 | 08-SEP-07:10 | 1392.33 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 259.01 | 03-SEP-14:25 | 874.91 | 17-SEP-19:53 |
October | 1295.83 | 02-OCT-09:09 | 1453.34 | 25-OCT-07:10 | 1392.33 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 99.31 | 11-OCT-13:00 | 1261.50 | 11-OCT-23:00 |
November | 1295.83 | 01-NOV-09:09 | 1667.75 | 09-NOV-16:49 | 1392.33 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 2143.54 | 03-NOV-21:10 |
December | 1295.83 | 01-DEC-10:09 | 1667.75 | 01-DEC-16:49 | 1392.33 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 2851.59 | 14-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 793.52 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 604.81 | |||||
Maximum of Months | 1295.83 | 1667.75 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 764.30 | 2851.59 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.79 | 02-JAN-10:09 | 2587.92 | 04-JAN-16:00 | 2160.55 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 4431.29 | 16-JAN-18:00 |
February | 2010.79 | 01-FEB-10:09 | 2255.20 | 16-FEB-08:09 | 2160.55 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 3506.30 | 05-FEB-01:17 |
March | 2010.79 | 01-MAR-10:09 | 1803.00 | 20-MAR-07:10 | 2160.55 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 3216.27 | 14-MAR-05:00 |
April | 2010.79 | 03-APR-09:09 | 1231.33 | 03-APR-07:10 | 2160.55 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 83.98 | 01-APR-17:10 | 3607.23 | 07-APR-22:00 |
May | 2010.79 | 01-MAY-09:09 | 1350.81 | 22-MAY-07:10 | 2160.55 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 326.08 | 14-MAY-17:10 | 2303.12 | 03-MAY-22:00 |
June | 2010.79 | 01-JUN-09:09 | 1470.28 | 08-JUN-15:20 | 2160.55 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1052.55 | 18-JUN-15:44 | 1857.07 | 04-JUN-16:53 |
July | 2010.79 | 03-JUL-09:09 | 1470.28 | 07-JUL-15:50 | 2160.55 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1421.16 | 04-JUL-14:54 | 1065.82 | 15-JUL-18:52 |
August | 2010.79 | 01-AUG-09:09 | 1231.33 | 01-AUG-07:10 | 2160.55 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 708.72 | 20-AUG-16:51 | 958.71 | 10-AUG-21:10 |
September | 2010.79 | 01-SEP-09:09 | 2255.20 | 08-SEP-07:10 | 2160.55 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 452.89 | 03-SEP-14:25 | 1288.27 | 07-SEP-22:00 |
October | 2010.79 | 02-OCT-09:09 | 2255.20 | 25-OCT-07:10 | 2160.55 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 212.95 | 01-OCT-16:00 | 2165.79 | 11-OCT-23:00 |
November | 2010.79 | 01-NOV-09:09 | 2587.92 | 08-NOV-16:00 | 2160.55 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 3754.72 | 03-NOV-21:03 |
December | 2010.79 | 01-DEC-10:09 | 2587.92 | 01-DEC-16:30 | 2160.55 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 4974.69 | 14-DEC-04:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.79 | 1231.33 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 958.71 | |||||
Maximum of Months | 2010.79 | 2587.92 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 1421.16 | 4974.69 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 1667.75 | 04-JAN-16:00 | 1392.34 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 2954.39 | 16-JAN-18:00 |
February | 1295.83 | 01-FEB-10:09 | 1453.34 | 16-FEB-08:09 | 1392.34 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 2327.73 | 05-FEB-01:17 |
March | 1295.83 | 01-MAR-10:09 | 947.51 | 02-MAR-16:49 | 1392.34 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 2144.24 | 14-MAR-05:00 |
April | 1295.83 | 03-APR-09:09 | 793.52 | 03-APR-07:10 | 1392.34 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 45.75 | 01-APR-17:50 | 2782.76 | 23-APR-09:00 |
May | 1295.83 | 01-MAY-09:09 | 870.51 | 22-MAY-07:10 | 1392.34 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 269.40 | 14-MAY-17:10 | 1512.12 | 03-MAY-22:00 |
June | 1295.83 | 01-JUN-09:09 | 947.51 | 08-JUN-15:20 | 1392.34 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 788.45 | 18-JUN-16:30 | 1278.47 | 04-JUN-16:53 |
July | 1295.83 | 03-JUL-09:09 | 947.51 | 07-JUL-15:50 | 1392.34 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1013.35 | 04-JUL-14:54 | 750.46 | 15-JUL-18:52 |
August | 1295.83 | 01-AUG-09:09 | 793.52 | 01-AUG-07:10 | 1392.34 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 484.55 | 20-AUG-16:50 | 944.63 | 27-AUG-08:10 |
September | 1295.83 | 01-SEP-09:09 | 1453.34 | 08-SEP-07:10 | 1392.34 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 329.59 | 03-SEP-14:25 | 894.43 | 17-SEP-20:00 |
October | 1295.83 | 02-OCT-09:09 | 1161.92 | 25-OCT-07:10 | 1392.34 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 133.21 | 01-OCT-15:50 | 1446.75 | 11-OCT-23:00 |
November | 1295.83 | 01-NOV-09:09 | 1667.75 | 08-NOV-16:49 | 1392.34 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 2511.11 | 03-NOV-21:03 |
December | 1295.83 | 01-DEC-10:09 | 1667.75 | 01-DEC-16:30 | 1392.34 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 3348.92 | 14-DEC-04:03 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 793.52 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 750.46 | |||||
Maximum of Months | 1295.83 | 1667.75 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 1013.35 | 3348.92 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.83 | 02-JAN-10:09 | 2255.25 | 04-JAN-16:49 | 2160.58 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 4431.78 | 16-JAN-18:00 |
February | 2010.83 | 01-FEB-10:09 | 2255.25 | 16-FEB-08:09 | 2160.58 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 3691.66 | 05-FEB-01:00 |
March | 2010.83 | 01-MAR-10:09 | 1803.04 | 20-MAR-07:10 | 2160.58 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 3225.01 | 14-MAR-03:00 |
April | 2010.83 | 03-APR-09:09 | 1231.36 | 03-APR-07:10 | 2160.58 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 66.38 | 29-APR-16:00 | 3757.35 | 07-APR-22:00 |
May | 2010.83 | 01-MAY-09:09 | 1470.31 | 22-MAY-07:10 | 2160.58 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 343.72 | 14-MAY-17:10 | 2267.62 | 03-MAY-22:00 |
June | 2010.83 | 01-JUN-09:09 | 1470.31 | 08-JUN-07:10 | 2160.58 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1089.65 | 18-JUN-15:44 | 1851.24 | 04-JUN-16:53 |
July | 2010.83 | 03-JUL-09:09 | 1470.31 | 07-JUL-15:50 | 2160.58 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1461.42 | 04-JUL-14:54 | 1090.13 | 15-JUL-18:52 |
August | 2010.83 | 01-AUG-09:09 | 1231.36 | 01-AUG-07:10 | 2160.58 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 711.36 | 20-AUG-16:44 | 1007.58 | 22-AUG-22:00 |
September | 2010.83 | 01-SEP-09:09 | 2255.25 | 08-SEP-07:10 | 2160.58 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 419.42 | 03-SEP-14:47 | 1521.87 | 17-SEP-20:00 |
October | 2010.83 | 02-OCT-09:09 | 2255.25 | 25-OCT-07:10 | 2160.58 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 162.60 | 11-OCT-14:50 | 2287.67 | 11-OCT-23:00 |
November | 2010.83 | 01-NOV-09:09 | 2587.98 | 09-NOV-16:49 | 2160.58 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 3987.89 | 03-NOV-21:03 |
December | 2010.83 | 01-DEC-10:09 | 2587.98 | 01-DEC-16:40 | 2160.58 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 4974.64 | 14-DEC-04:06 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.83 | 1231.36 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1007.58 | |||||
Maximum of Months | 2010.83 | 2587.98 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 1461.42 | 4974.64 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 1453.34 | 04-JAN-16:49 | 1392.33 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 2954.17 | 16-JAN-18:00 |
February | 1295.83 | 01-FEB-10:09 | 1453.34 | 16-FEB-08:09 | 1392.33 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 2400.45 | 05-FEB-01:00 |
March | 1295.83 | 01-MAR-10:09 | 1161.92 | 17-MAR-07:10 | 1392.33 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 2144.13 | 14-MAR-04:57 |
April | 1295.83 | 03-APR-09:09 | 793.52 | 03-APR-07:10 | 1392.33 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 44.25 | 29-APR-16:00 | 2931.75 | 15-APR-17:02 |
May | 1295.83 | 01-MAY-09:09 | 947.51 | 22-MAY-07:10 | 1392.33 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 218.01 | 21-MAY-16:40 | 1581.13 | 18-MAY-02:00 |
June | 1295.83 | 01-JUN-09:09 | 947.51 | 08-JUN-07:10 | 1392.33 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 656.68 | 18-JUN-16:00 | 1276.15 | 10-JUN-01:00 |
July | 1295.83 | 03-JUL-09:09 | 947.51 | 07-JUL-15:00 | 1392.33 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 937.15 | 04-JUL-15:00 | 799.31 | 15-JUL-18:52 |
August | 1295.83 | 01-AUG-09:09 | 870.51 | 28-AUG-07:10 | 1392.33 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 472.40 | 20-AUG-17:00 | 746.40 | 08-AUG-01:00 |
September | 1295.83 | 01-SEP-09:09 | 1453.34 | 08-SEP-07:10 | 1392.33 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 323.45 | 03-SEP-14:25 | 1040.87 | 17-SEP-20:00 |
October | 1295.83 | 02-OCT-09:09 | 1453.34 | 25-OCT-07:10 | 1392.33 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 118.11 | 11-OCT-13:00 | 1518.78 | 11-OCT-23:00 |
November | 1295.83 | 01-NOV-09:09 | 1667.75 | 09-NOV-16:49 | 1392.33 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 2547.69 | 03-NOV-21:03 |
December | 1295.83 | 01-DEC-10:09 | 1667.75 | 01-DEC-16:49 | 1392.33 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 3316.37 | 14-DEC-04:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 793.52 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 746.40 | |||||
Maximum of Months | 1295.83 | 1667.75 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 937.15 | 3316.37 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 232.27 | 02-JAN-10:09 | 578.72 | 02-JAN-08:09 | 1948.61 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 232.27 | 01-FEB-10:09 | 578.72 | 01-FEB-08:09 | 3897.21 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 232.27 | 01-MAR-10:09 | 578.72 | 01-MAR-08:09 | 7794.42 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 232.27 | 03-APR-09:09 | 578.72 | 03-APR-07:10 | 7794.42 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 232.27 | 01-MAY-09:09 | 578.72 | 01-MAY-07:10 | 3897.21 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 232.27 | 01-JUN-09:09 | 578.72 | 01-JUN-07:10 | 5845.82 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 232.27 | 03-JUL-09:09 | 578.72 | 03-JUL-07:10 | 7794.42 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 232.27 | 01-AUG-09:09 | 578.72 | 01-AUG-07:10 | 7794.42 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 232.27 | 01-SEP-09:09 | 578.72 | 01-SEP-07:10 | 3897.21 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 232.27 | 02-OCT-09:09 | 578.72 | 02-OCT-07:10 | 5845.82 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 232.27 | 01-NOV-09:09 | 578.72 | 01-NOV-07:10 | 5845.82 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 232.27 | 01-DEC-10:09 | 578.72 | 01-DEC-08:09 | 7794.42 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 232.27 | 578.72 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 232.27 | 578.72 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 232.27 | 02-JAN-10:09 | 578.72 | 02-JAN-08:09 | 1948.61 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 232.27 | 01-FEB-10:09 | 578.72 | 01-FEB-08:09 | 3897.21 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 232.27 | 01-MAR-10:09 | 578.72 | 01-MAR-08:09 | 7794.42 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 232.27 | 03-APR-09:09 | 578.72 | 03-APR-07:10 | 7794.42 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 232.27 | 01-MAY-09:09 | 578.72 | 01-MAY-07:10 | 3897.21 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 232.27 | 01-JUN-09:09 | 578.72 | 01-JUN-07:10 | 5845.82 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 232.27 | 03-JUL-09:09 | 578.72 | 03-JUL-07:10 | 7794.42 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 232.27 | 01-AUG-09:09 | 578.72 | 01-AUG-07:10 | 7794.42 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 232.27 | 01-SEP-09:09 | 578.72 | 01-SEP-07:10 | 3897.21 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 232.27 | 02-OCT-09:09 | 578.72 | 02-OCT-07:10 | 5845.82 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 232.27 | 01-NOV-09:09 | 578.72 | 01-NOV-07:10 | 5845.82 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 232.27 | 01-DEC-10:09 | 578.72 | 01-DEC-08:09 | 7794.42 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 232.27 | 578.72 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 232.27 | 578.72 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 232.27 | 02-JAN-10:09 | 578.72 | 02-JAN-08:09 | 1948.61 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 232.27 | 01-FEB-10:09 | 578.72 | 01-FEB-08:09 | 3897.21 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 232.27 | 01-MAR-10:09 | 578.72 | 01-MAR-08:09 | 7794.42 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 232.27 | 03-APR-09:09 | 578.72 | 03-APR-07:10 | 7794.42 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 232.27 | 01-MAY-09:09 | 578.72 | 01-MAY-07:10 | 3897.21 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 232.27 | 01-JUN-09:09 | 578.72 | 01-JUN-07:10 | 5845.82 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 232.27 | 03-JUL-09:09 | 578.72 | 03-JUL-07:10 | 7794.42 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 232.27 | 01-AUG-09:09 | 578.72 | 01-AUG-07:10 | 7794.42 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 232.27 | 01-SEP-09:09 | 578.72 | 01-SEP-07:10 | 3897.21 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 232.27 | 02-OCT-09:09 | 578.72 | 02-OCT-07:10 | 5845.82 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 232.27 | 01-NOV-09:09 | 578.72 | 01-NOV-07:10 | 5845.82 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 232.27 | 01-DEC-10:09 | 578.72 | 01-DEC-08:09 | 7794.42 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 232.27 | 578.72 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 232.27 | 578.72 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 5027.92 | 02-JAN-10:09 | 6471.01 | 02-JAN-08:09 | 94908.13 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 5027.92 | 01-FEB-10:09 | 6471.01 | 01-FEB-08:09 | 189816.26 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 5027.92 | 01-MAR-10:09 | 6471.01 | 01-MAR-08:09 | 379632.52 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 5027.92 | 03-APR-09:09 | 6471.01 | 03-APR-07:10 | 379632.52 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 5027.92 | 01-MAY-09:09 | 6471.01 | 01-MAY-07:10 | 189816.26 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5027.92 | 01-JUN-09:09 | 6471.01 | 01-JUN-07:10 | 284724.39 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 5027.92 | 03-JUL-09:09 | 6471.01 | 03-JUL-07:10 | 379632.52 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 5027.92 | 01-AUG-09:09 | 6471.01 | 01-AUG-07:10 | 379632.52 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 5027.92 | 01-SEP-09:09 | 6471.01 | 01-SEP-07:10 | 189816.26 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 5027.92 | 02-OCT-09:09 | 6471.01 | 02-OCT-07:10 | 284724.39 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5027.92 | 01-NOV-09:09 | 6471.01 | 01-NOV-07:10 | 284724.39 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 5027.92 | 01-DEC-10:09 | 6471.01 | 01-DEC-08:09 | 379632.52 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 5027.92 | 6471.01 | 94908.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 5027.92 | 6471.01 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 4343.09 | 16-JAN-18:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 3370.28 | 05-FEB-01:00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 2922.00 | 14-MAR-03:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.84 | 26-APR-15:00 | 3140.96 | 07-APR-22:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 269.77 | 14-MAY-17:00 | 1923.24 | 03-MAY-22:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 763.15 | 18-JUN-16:00 | 1488.60 | 10-JUN-03:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1022.63 | 04-JUL-14:51 | 701.95 | 15-JUL-18:54 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 525.56 | 05-AUG-17:01 | 727.40 | 22-AUG-22:20 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 344.08 | 03-SEP-15:00 | 1093.76 | 18-SEP-00:55 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 132.72 | 01-OCT-15:51 | 1766.98 | 11-OCT-23:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 3362.62 | 26-NOV-05:55 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 4693.38 | 14-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 701.95 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1022.63 | 4693.38 |
Report: PeakSpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 7175.36 | 16-JAN-18:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 5735.10 | 05-FEB-01:00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 4926.05 | 14-MAR-03:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 56.61 | 17-APR-15:00 | 5460.68 | 07-APR-22:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 560.16 | 14-MAY-16:51 | 3371.67 | 03-MAY-22:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1416.94 | 18-JUN-16:00 | 2578.64 | 10-JUN-03:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1834.93 | 04-JUL-15:00 | 1246.43 | 15-JUL-18:52 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 973.12 | 05-AUG-17:01 | 1293.14 | 22-AUG-22:00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 644.42 | 03-SEP-14:50 | 1859.75 | 18-SEP-00:55 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 260.14 | 01-OCT-16:00 | 3084.51 | 11-OCT-23:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 5644.77 | 26-NOV-05:55 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 7939.96 | 14-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1246.43 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1834.93 | 7939.96 |
Report: PeakSpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 6804.47 | 16-JAN-18:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 5680.49 | 05-FEB-01:00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 5006.92 | 14-MAR-03:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.04 | 13-APR-17:00 | 5872.77 | 07-APR-22:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 241.76 | 19-MAY-15:00 | 3597.47 | 03-MAY-22:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1128.53 | 18-JUN-16:10 | 2801.98 | 04-JUN-16:53 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1585.76 | 04-JUL-17:00 | 1671.34 | 15-JUL-18:52 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 827.57 | 20-AUG-17:00 | 1455.89 | 08-AUG-01:00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 433.80 | 03-SEP-14:50 | 2029.91 | 17-SEP-19:53 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 163.77 | 01-OCT-16:00 | 3406.47 | 11-OCT-23:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 6099.52 | 03-NOV-21:03 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 7783.88 | 14-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1455.89 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1585.76 | 7783.88 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 119847.91 | 17-JAN-04:01 | 0.00 | 10199.39 | 107660.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 122126.53 | 21-FEB-05:11 | 0.00 | 25501.32 | 134575.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 117553.86 | 20-MAR-04:12 | 0.00 | 12750.66 | 67287.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 118821.27 | 17-APR-04:12 | 0.00 | 15300.79 | 80745.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 120056.09 | 01-MAY-04:12 | 0.00 | 15300.79 | 80745.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 116964.53 | 12-JUN-04:12 | 0.00 | 15300.79 | 80745.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 106086.51 | 19-JUL-04:12 | 0.00 | 12750.66 | 67287.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 109661.70 | 31-AUG-04:12 | 0.00 | 12750.66 | 67287.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 116571.74 | 19-SEP-04:12 | 0.00 | 12750.66 | 67287.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 119401.40 | 23-OCT-04:12 | 0.00 | 15300.79 | 80745.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 120030.42 | 27-NOV-04:01 | 0.00 | 8924.46 | 94202.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 121553.65 | 11-DEC-05:01 | 0.00 | 25501.32 | 134575.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 106086.51 | 0.00 | 8924.46 | 67287.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 122126.53 | 0.00 | 25501.32 | 134575.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 92999.86 | 02-JAN-04:01 | 0.00 | 8014.80 | 41563.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 96040.11 | 21-FEB-05:11 | 0.00 | 22901.98 | 59376.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 95083.10 | 27-MAR-04:12 | 0.00 | 11450.99 | 29688.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 98397.39 | 24-APR-04:12 | 0.00 | 13741.19 | 35625.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 99158.90 | 22-MAY-04:13 | 0.00 | 13741.19 | 35625.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 98908.42 | 05-JUN-04:13 | 0.00 | 13741.19 | 35625.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 94556.25 | 08-JUL-04:12 | 0.00 | 6869.83 | 26719.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 91560.33 | 25-AUG-04:12 | 0.00 | 13741.19 | 35625.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 101012.80 | 05-SEP-04:13 | 0.00 | 13741.19 | 35625.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 101496.62 | 02-OCT-04:13 | 0.00 | 13741.19 | 35625.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 97473.74 | 24-NOV-05:11 | 0.00 | 18321.59 | 47501.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 94122.27 | 04-DEC-04:01 | 0.00 | 10304.74 | 53438.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 91560.33 | 0.00 | 6869.83 | 26719.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 101496.62 | 0.00 | 22901.98 | 59376.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 35126.98 | 26-JAN-17:00 | 15316.26 | 20611.01 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 80166.06 | 15-FEB-06:02 | 8061.19 | 11450.99 | 38236.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 79814.56 | 17-MAR-05:03 | 6448.95 | 9160.79 | 30589.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 84734.96 | 28-APR-04:12 | 0.00 | 13741.19 | 35625.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 86694.29 | 22-MAY-04:12 | 0.00 | 13741.19 | 35625.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 88214.88 | 30-JUN-04:12 | 0.00 | 13741.19 | 35625.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 88202.57 | 13-JUL-04:12 | 0.00 | 13741.19 | 35625.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 87879.22 | 04-AUG-04:12 | 0.00 | 13741.19 | 35625.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 88910.63 | 05-SEP-04:12 | 0.00 | 13741.19 | 35625.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 87679.61 | 03-OCT-04:12 | 0.00 | 13741.19 | 35625.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 82915.85 | 02-NOV-05:02 | 8061.19 | 11450.99 | 38236.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 70907.72 | 01-DEC-06:03 | 6448.95 | 9160.79 | 30589.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 35126.98 | 0.00 | 9160.79 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 88910.63 | 15316.26 | 20611.01 | 38236.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 29400.72 | 05-JAN-17:00 | 15316.26 | 20611.01 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 39859.42 | 15-FEB-16:20 | 15316.26 | 20611.01 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 40992.28 | 08-MAR-16:30 | 15316.26 | 20611.01 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 78303.96 | 27-APR-05:03 | 6448.95 | 9160.79 | 30589.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 85687.08 | 22-MAY-04:12 | 0.00 | 13741.19 | 35625.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 86086.51 | 30-JUN-04:12 | 0.00 | 13741.19 | 35625.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 96063.81 | 05-JUL-04:13 | 0.00 | 16031.39 | 41563.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 89075.09 | 14-AUG-04:13 | 0.00 | 16031.39 | 41563.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 89143.30 | 05-SEP-04:12 | 0.00 | 13741.19 | 35625.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 83983.28 | 02-OCT-04:12 | 0.00 | 13741.19 | 35625.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 42422.07 | 01-NOV-15:20 | 15316.26 | 20611.01 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 29704.18 | 01-DEC-17:00 | 15316.26 | 20611.01 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 29400.72 | 0.00 | 9160.79 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 96063.81 | 15316.26 | 20611.01 | 41563.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3140.38 | 24-JAN-14:40 | 2010.79 | 1231.33 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 89.77 |
February | 4891.03 | 15-FEB-13:20 | 3846.22 | 2462.66 | 4321.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36.52 |
March | 7431.42 | 27-MAR-14:30 | 1923.11 | 1231.33 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43.65 |
April | 9462.48 | 14-APR-14:00 | 2010.79 | 1231.33 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.76 |
May | 13828.15 | 14-MAY-16:11 | 1012.16 | 684.02 | 7201.84 | 0.00 | 0.00 | 0.00 | 0.00 | 80.65 | 0.00 |
June | 19722.98 | 18-JUN-18:11 | 0.00 | 684.02 | 5591.71 | 0.00 | 0.00 | 0.00 | 0.00 | 104.76 | 0.00 |
July | 19674.40 | 02-JUL-18:01 | 0.00 | 684.02 | 5591.71 | 0.00 | 0.00 | 0.00 | 0.00 | 120.65 | 0.00 |
August | 19362.04 | 06-AUG-16:31 | 1012.16 | 684.02 | 7201.84 | 0.00 | 0.00 | 0.00 | 0.00 | 109.03 | 0.00 |
September | 16892.03 | 03-SEP-14:11 | 910.95 | 615.62 | 6481.66 | 0.00 | 0.00 | 0.00 | 0.00 | 141.64 | 0.00 |
October | 12675.07 | 02-OCT-04:12 | 0.00 | 1725.34 | 4473.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 94.89 |
November | 5389.85 | 08-NOV-13:40 | 1923.11 | 1231.33 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45.01 |
December | 4006.36 | 01-DEC-13:30 | 1923.11 | 1231.33 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 112.44 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3140.38 | 0.00 | 615.62 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 19722.98 | 3846.22 | 2462.66 | 7201.84 | 0.00 | 0.00 | 0.00 | 0.00 | 141.64 | 112.44 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 8252.53 | 02-JAN-09:25 | 2478.65 | 1587.03 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 53.22 |
February | 20367.45 | 19-FEB-09:32 | 326.14 | 220.40 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 132.62 |
March | 24118.68 | 26-MAR-08:32 | 391.37 | 264.49 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 222.35 |
April | 28603.02 | 30-APR-08:61 | 652.28 | 440.81 | 4641.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 400.50 |
May | 27933.46 | 14-MAY-07:31 | 587.05 | 396.73 | 4177.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 137.97 |
June | 29233.71 | 18-JUN-08:11 | 652.28 | 440.81 | 4641.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67.53 |
July | 28837.76 | 02-JUL-08:41 | 652.28 | 440.81 | 4641.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 78.64 |
August | 26256.61 | 20-AUG-08:11 | 456.59 | 308.57 | 3248.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.02 |
September | 28898.02 | 03-SEP-08:11 | 652.28 | 440.81 | 4641.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.63 |
October | 27161.97 | 01-OCT-08:41 | 521.82 | 352.65 | 3712.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 139.42 |
November | 15603.01 | 12-NOV-09:13 | 260.91 | 176.32 | 1856.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 101.54 |
December | 8056.50 | 29-DEC-09:20 | 1239.33 | 793.52 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.85 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 8056.50 | 260.91 | 176.32 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.02 | |
Maximum of Months | 29233.71 | 2478.65 | 1587.03 | 4641.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 400.50 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 26425.60 | 01-JAN-13:51 | 708.53 | 478.83 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 241.21 |
February | 26755.53 | 19-FEB-13:31 | 1012.19 | 684.04 | 7201.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 466.04 |
March | 24761.34 | 12-MAR-13:22 | 506.09 | 342.02 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 155.94 |
April | 25544.94 | 30-APR-12:42 | 607.31 | 410.42 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 320.48 |
May | 24035.41 | 28-MAY-13:32 | 607.31 | 410.42 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.13 |
June | 24130.61 | 25-JUN-14:21 | 910.97 | 615.63 | 6481.75 | 0.00 | 0.00 | 0.00 | 0.00 | 79.36 | 0.00 |
July | 24195.41 | 02-JUL-15:21 | 1012.19 | 684.04 | 7201.95 | 0.00 | 0.00 | 0.00 | 0.00 | 122.72 | 0.00 |
August | 25817.62 | 06-AUG-13:11 | 708.53 | 478.83 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 64.25 | 0.00 |
September | 27930.91 | 10-SEP-12:41 | 809.75 | 547.23 | 5761.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41.51 |
October | 30092.86 | 01-OCT-12:01 | 1012.19 | 684.04 | 7201.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40.21 |
November | 28624.81 | 19-NOV-13:01 | 910.97 | 615.63 | 6481.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 350.63 |
December | 29904.73 | 31-DEC-13:21 | 1012.19 | 684.04 | 7201.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 99.05 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 24035.41 | 506.09 | 342.02 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 30092.86 | 1012.19 | 684.04 | 7201.95 | 0.00 | 0.00 | 0.00 | 0.00 | 122.72 | 466.04 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 14023.78 | 01-JAN-15:52 | 326.14 | 220.40 | 2320.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 260.79 |
February | 18294.73 | 12-FEB-16:12 | 326.14 | 220.40 | 2320.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.08 |
March | 31083.39 | 12-MAR-16:01 | 456.59 | 308.57 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 88.84 |
April | 33375.49 | 16-APR-16:31 | 521.82 | 352.65 | 3712.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.31 |
May | 34943.70 | 14-MAY-16:11 | 652.28 | 440.81 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 54.98 |
June | 37369.91 | 25-JUN-16:21 | 652.28 | 440.81 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 67.17 | 0.00 |
July | 36625.25 | 02-JUL-16:41 | 652.28 | 440.81 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 16.71 | 0.00 |
August | 35081.63 | 06-AUG-17:11 | 0.00 | 440.81 | 3603.49 | 0.00 | 0.00 | 0.00 | 0.00 | 5.58 | 0.00 |
September | 35037.47 | 24-SEP-16:01 | 652.28 | 440.81 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 64.93 |
October | 32348.81 | 01-OCT-14:01 | 652.28 | 440.81 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.86 |
November | 30879.66 | 19-NOV-15:01 | 456.59 | 308.57 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 357.58 |
December | 30753.43 | 31-DEC-16:01 | 456.59 | 308.57 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.13 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 14023.78 | 0.00 | 220.40 | 2320.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 37369.91 | 652.28 | 440.81 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 67.17 | 357.58 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2580.27 | 05-JAN-16:00 | 1923.11 | 1350.81 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 85.47 |
February | 2908.56 | 15-FEB-15:10 | 1923.11 | 1231.33 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 55.19 |
March | 4896.80 | 27-MAR-14:40 | 1923.11 | 1231.33 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 108.35 |
April | 8181.66 | 14-APR-14:00 | 2010.79 | 1231.33 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.91 |
May | 9000.90 | 31-MAY-15:30 | 1923.11 | 1231.33 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 109.03 | 0.00 |
June | 18986.63 | 25-JUN-17:42 | 0.00 | 684.02 | 5591.71 | 0.00 | 0.00 | 0.00 | 0.00 | 452.68 | 0.00 |
July | 19300.05 | 04-JUL-18:12 | 0.00 | 684.02 | 5591.71 | 0.00 | 0.00 | 0.00 | 0.00 | 526.17 | 0.00 |
August | 18518.09 | 20-AUG-16:01 | 1012.16 | 684.02 | 7201.84 | 0.00 | 0.00 | 0.00 | 0.00 | 344.98 | 0.00 |
September | 17873.64 | 04-SEP-16:11 | 910.95 | 615.62 | 6481.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.17 |
October | 8103.46 | 02-OCT-13:40 | 2010.79 | 1231.33 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 18.56 | 0.00 |
November | 3133.33 | 03-NOV-14:00 | 2010.79 | 1231.33 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 176.07 |
December | 2428.01 | 29-DEC-16:10 | 1923.11 | 2135.72 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.93 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2428.01 | 0.00 | 615.62 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 19300.05 | 2010.79 | 2135.72 | 7201.84 | 0.00 | 0.00 | 0.00 | 0.00 | 526.17 | 176.07 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 6225.43 | 27-JAN-09:40 | 1239.33 | 793.52 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 10124.44 | 14-FEB-09:30 | 1239.33 | 793.52 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57.35 |
March | 25986.83 | 12-MAR-09:52 | 391.37 | 264.49 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 487.21 |
April | 27880.41 | 30-APR-08:51 | 587.05 | 396.73 | 4177.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 869.61 |
May | 31233.56 | 29-MAY-09:11 | 652.28 | 440.81 | 4641.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 210.16 |
June | 31905.08 | 18-JUN-08:11 | 652.28 | 440.81 | 4641.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 170.70 |
July | 32746.82 | 04-JUL-08:51 | 652.28 | 440.81 | 4641.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 97.93 |
August | 32582.82 | 20-AUG-08:41 | 652.28 | 440.81 | 4641.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 99.38 |
September | 27849.80 | 03-SEP-09:01 | 456.59 | 308.57 | 3248.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.31 |
October | 28772.50 | 01-OCT-08:51 | 521.82 | 352.65 | 3712.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 325.11 |
November | 10659.04 | 01-NOV-09:00 | 1239.33 | 793.52 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 106.07 |
December | 5911.22 | 29-DEC-09:30 | 1239.33 | 793.52 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41.34 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 5911.22 | 391.37 | 264.49 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 32746.82 | 1239.33 | 793.52 | 4641.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 869.61 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 27595.80 | 15-JAN-12:01 | 809.75 | 547.23 | 5761.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1094.18 |
February | 26644.47 | 19-FEB-13:41 | 809.75 | 547.23 | 5761.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1075.94 |
March | 27208.08 | 12-MAR-14:31 | 809.75 | 547.23 | 5761.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 361.28 |
April | 25093.98 | 30-APR-13:32 | 607.31 | 410.42 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 756.45 |
May | 23530.43 | 21-MAY-13:02 | 506.09 | 342.02 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.86 |
June | 23606.21 | 25-JUN-14:21 | 910.97 | 615.63 | 6481.75 | 0.00 | 0.00 | 0.00 | 0.00 | 182.03 | 0.00 |
July | 25274.12 | 30-JUL-15:11 | 1012.19 | 684.04 | 7201.95 | 0.00 | 0.00 | 0.00 | 0.00 | 244.05 | 0.00 |
August | 25983.37 | 20-AUG-14:41 | 1012.19 | 684.04 | 7201.95 | 0.00 | 0.00 | 0.00 | 0.00 | 168.73 | 0.00 |
September | 28148.49 | 10-SEP-13:31 | 910.97 | 615.63 | 6481.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 109.07 |
October | 30574.16 | 01-OCT-12:51 | 1012.19 | 684.04 | 7201.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 82.64 |
November | 28712.08 | 19-NOV-11:31 | 910.97 | 615.63 | 6481.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 470.26 |
December | 27382.17 | 31-DEC-14:11 | 708.53 | 478.83 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 23530.43 | 506.09 | 342.02 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 30574.16 | 1012.19 | 684.04 | 7201.95 | 0.00 | 0.00 | 0.00 | 0.00 | 244.05 | 1094.18 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 10045.68 | 26-JAN-16:30 | 1239.33 | 793.52 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 102.55 |
February | 14618.71 | 15-FEB-16:30 | 1239.33 | 793.52 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 60.59 |
March | 29026.30 | 12-MAR-16:31 | 652.28 | 440.81 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 326.76 |
April | 33651.74 | 16-APR-17:01 | 0.00 | 440.81 | 3603.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 145.81 |
May | 33188.60 | 29-MAY-16:31 | 652.28 | 440.81 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 184.99 |
June | 35442.54 | 25-JUN-17:01 | 0.00 | 440.81 | 3603.49 | 0.00 | 0.00 | 0.00 | 0.00 | 114.74 | 0.00 |
July | 36322.44 | 04-JUL-16:51 | 652.28 | 440.81 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 331.30 | 0.00 |
August | 35055.98 | 20-AUG-16:01 | 652.28 | 440.81 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 115.29 | 0.00 |
September | 31858.94 | 04-SEP-16:51 | 652.28 | 440.81 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 101.61 |
October | 31535.05 | 01-OCT-15:31 | 587.05 | 396.73 | 4177.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.83 |
November | 18537.14 | 12-NOV-15:41 | 456.59 | 308.57 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 343.00 |
December | 8478.84 | 29-DEC-16:00 | 1239.33 | 793.52 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 8478.84 | 0.00 | 308.57 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 36322.44 | 1239.33 | 793.52 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 331.30 | 343.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2749.94 | 05-JAN-15:30 | 1923.11 | 1231.33 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 127.75 |
February | 3191.28 | 15-FEB-16:00 | 1923.11 | 1231.33 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 90.54 |
March | 4149.66 | 16-MAR-14:50 | 1923.11 | 1231.33 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 201.64 |
April | 8509.85 | 14-APR-14:30 | 1923.11 | 1231.33 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.34 |
May | 16884.36 | 29-MAY-16:41 | 1012.16 | 684.02 | 7201.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 63.87 |
June | 20921.82 | 11-JUN-18:41 | 0.00 | 684.02 | 5591.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 98.18 |
July | 22421.48 | 04-JUL-16:51 | 1012.16 | 684.02 | 7201.84 | 0.00 | 0.00 | 0.00 | 0.00 | 1087.15 | 0.00 |
August | 21765.84 | 20-AUG-16:01 | 1012.16 | 684.02 | 7201.84 | 0.00 | 0.00 | 0.00 | 0.00 | 394.39 | 0.00 |
September | 20454.92 | 04-SEP-16:11 | 910.95 | 615.62 | 6481.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36.82 |
October | 8565.60 | 02-OCT-13:40 | 2010.79 | 1231.33 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 21.91 | 0.00 |
November | 3147.10 | 02-NOV-15:30 | 1923.11 | 1231.33 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 128.61 |
December | 2570.65 | 29-DEC-15:40 | 1923.11 | 1350.81 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.86 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2570.65 | 0.00 | 615.62 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 22421.48 | 2010.79 | 1350.81 | 7201.84 | 0.00 | 0.00 | 0.00 | 0.00 | 1087.15 | 201.64 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4108.44 | 27-JAN-10:00 | 1239.33 | 793.52 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 8231.33 | 14-FEB-09:50 | 1239.33 | 793.52 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 66.47 |
March | 17460.82 | 12-MAR-09:52 | 391.37 | 264.49 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 591.31 |
April | 27073.41 | 30-APR-09:01 | 456.59 | 308.57 | 3248.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 975.17 |
May | 31199.12 | 29-MAY-08:41 | 652.28 | 440.81 | 4641.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 249.23 |
June | 28841.04 | 18-JUN-08:21 | 521.82 | 352.65 | 3712.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 214.30 |
July | 33200.22 | 04-JUL-08:51 | 652.28 | 440.81 | 4641.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 125.61 |
August | 32897.57 | 20-AUG-08:41 | 652.28 | 440.81 | 4641.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 125.90 |
September | 28093.27 | 03-SEP-09:01 | 456.59 | 308.57 | 3248.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.91 |
October | 25784.21 | 01-OCT-09:02 | 391.37 | 264.49 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 306.54 |
November | 9673.49 | 01-NOV-09:10 | 1295.83 | 793.52 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 156.43 |
December | 3873.58 | 29-DEC-09:40 | 1239.33 | 793.52 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67.84 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3873.58 | 391.37 | 264.49 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 33200.22 | 1295.83 | 793.52 | 4641.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 975.17 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 29657.09 | 08-JAN-14:01 | 809.75 | 547.23 | 5761.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 494.23 |
February | 27723.14 | 12-FEB-14:12 | 607.31 | 410.42 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 426.71 |
March | 28988.70 | 12-MAR-14:31 | 809.75 | 547.23 | 5761.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 432.88 |
April | 22938.18 | 30-APR-13:42 | 506.09 | 342.02 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 813.31 |
May | 25204.34 | 29-MAY-16:01 | 1012.19 | 684.04 | 7201.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.89 |
June | 25149.33 | 25-JUN-16:31 | 910.97 | 615.63 | 6481.75 | 0.00 | 0.00 | 0.00 | 0.00 | 693.10 | 0.00 |
July | 28035.42 | 04-JUL-14:51 | 1012.19 | 684.04 | 7201.95 | 0.00 | 0.00 | 0.00 | 0.00 | 1117.27 | 0.00 |
August | 29236.96 | 20-AUG-14:41 | 1012.19 | 684.04 | 7201.95 | 0.00 | 0.00 | 0.00 | 0.00 | 192.80 | 0.00 |
September | 29213.79 | 03-SEP-13:01 | 708.53 | 478.83 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 144.64 | 0.00 |
October | 32067.29 | 09-OCT-13:21 | 1012.19 | 684.04 | 7201.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 293.75 |
November | 28372.91 | 12-NOV-13:31 | 1012.19 | 684.04 | 7201.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 944.37 |
December | 31964.83 | 31-DEC-13:51 | 1012.19 | 684.04 | 7201.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 22938.18 | 506.09 | 342.02 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 32067.29 | 1012.19 | 684.04 | 7201.95 | 0.00 | 0.00 | 0.00 | 0.00 | 1117.27 | 944.37 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 9517.32 | 26-JAN-16:30 | 1239.33 | 793.52 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 128.34 |
February | 14552.80 | 15-FEB-16:30 | 1239.33 | 793.52 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 76.37 |
March | 30142.20 | 12-MAR-16:31 | 652.28 | 440.81 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 396.71 |
April | 35186.21 | 16-APR-17:01 | 0.00 | 440.81 | 3603.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 179.33 |
May | 34314.12 | 07-MAY-15:51 | 652.28 | 440.81 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 315.55 |
June | 37525.43 | 11-JUN-16:41 | 652.28 | 440.81 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 112.58 |
July | 39134.94 | 04-JUL-16:51 | 652.28 | 440.81 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 373.75 | 0.00 |
August | 37899.08 | 20-AUG-16:01 | 652.28 | 440.81 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 126.56 | 0.00 |
September | 34888.81 | 24-SEP-16:11 | 652.28 | 440.81 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 182.75 |
October | 32643.76 | 15-OCT-16:01 | 587.05 | 396.73 | 4177.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 122.24 |
November | 12148.62 | 02-NOV-15:50 | 1239.33 | 793.52 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 98.52 |
December | 8091.53 | 29-DEC-16:00 | 1239.33 | 793.52 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 8091.53 | 0.00 | 396.73 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 39134.94 | 1239.33 | 793.52 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 373.75 | 396.71 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 5276.29 | 03-JAN-06:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 50.34 |
February | 7197.87 | 06-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 496.97 |
March | 6193.01 | 27-MAR-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 126.78 |
April | 7976.54 | 28-APR-14:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.03 | 0.00 |
May | 9991.16 | 30-MAY-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 55.50 |
June | 10805.25 | 26-JUN-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 70.58 |
July | 11199.51 | 05-JUL-14:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 85.06 | 0.00 |
August | 12326.43 | 21-AUG-05:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 99.95 |
September | 10345.18 | 05-SEP-10:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.06 |
October | 10359.43 | 02-OCT-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 60.46 |
November | 6133.09 | 01-NOV-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 508.27 |
December | 4383.73 | 28-DEC-06:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 188.69 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 4383.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 12326.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 85.06 | 508.27 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 11714.41 | 17-JAN-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4861.41 |
February | 11258.90 | 06-FEB-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3733.72 |
March | 9878.83 | 04-MAR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3168.94 |
April | 6089.27 | 28-APR-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.44 | 0.00 |
May | 6630.02 | 16-MAY-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 8866.22 | 29-JUN-14:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 419.50 | 0.00 |
July | 11565.64 | 05-JUL-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 120.40 |
August | 9340.06 | 14-AUG-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 77.52 |
September | 8059.73 | 05-SEP-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.84 |
October | 7339.74 | 02-OCT-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43.88 |
November | 9856.57 | 27-NOV-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1338.54 |
December | 10249.12 | 23-DEC-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3317.54 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 6089.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 11714.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 419.50 | 4861.41 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3946.02 | 05-JAN-15:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 224.51 |
February | 8223.74 | 15-FEB-15:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 142.60 |
March | 11374.57 | 08-MAR-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 128.42 |
April | 17622.94 | 28-APR-14:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45.48 |
May | 20228.61 | 30-MAY-14:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.24 | 0.00 |
June | 25568.18 | 28-JUN-13:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 208.36 | 0.00 |
July | 24415.54 | 21-JUL-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 373.59 | 0.00 |
August | 23335.38 | 07-AUG-14:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.57 | 0.00 |
September | 18556.65 | 01-SEP-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 63.85 | 0.00 |
October | 14540.13 | 05-OCT-14:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.71 | 0.00 |
November | 7145.24 | 02-NOV-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 220.73 |
December | 3220.99 | 31-DEC-14:34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 3220.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 25568.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 373.59 | 224.51 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 2805.44 | 26-JAN-17:00 | 222.14 | 578.72 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 4772.59 | 15-FEB-17:00 | 222.14 | 578.72 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 7127.52 | 31-MAR-24:00 | 0.00 | 32.15 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 8637.07 | 16-APR-18:20 | 0.00 | 192.92 | 46766.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 3533.09 | 31-MAY-24:00 | 0.00 | 32.15 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5378.03 | 30-JUN-23:23 | 0.00 | 128.61 | 23383.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 7280.08 | 31-JUL-23:55 | 0.00 | 128.61 | 31177.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 8197.77 | 30-AUG-17:40 | 23.38 | 192.90 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 3520.26 | 30-SEP-24:00 | 0.00 | 32.15 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 5329.20 | 31-OCT-24:00 | 0.00 | 32.15 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6691.69 | 06-NOV-16:50 | 222.14 | 578.72 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 8415.24 | 29-DEC-16:40 | 222.14 | 578.72 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 2805.44 | 0.00 | 32.15 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 8637.07 | 222.14 | 578.72 | 46766.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 2608.58 | 26-JAN-17:00 | 222.14 | 578.72 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 4531.00 | 15-FEB-17:00 | 222.14 | 578.72 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6552.52 | 31-MAR-23:30 | 0.00 | 32.15 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 8232.66 | 16-APR-18:00 | 0.00 | 225.07 | 54560.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 3340.12 | 31-MAY-24:00 | 0.00 | 32.15 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5194.36 | 30-JUN-23:57 | 0.00 | 96.46 | 17537.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 7005.84 | 31-JUL-23:55 | 0.00 | 128.61 | 31177.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 7859.95 | 30-AUG-17:40 | 23.38 | 192.90 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 3291.75 | 30-SEP-24:00 | 0.00 | 32.15 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 4854.76 | 31-OCT-24:00 | 0.00 | 32.15 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6244.15 | 02-NOV-16:50 | 70.15 | 321.51 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 7853.14 | 29-DEC-16:50 | 222.14 | 578.72 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 2608.58 | 0.00 | 32.15 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 8232.66 | 222.14 | 578.72 | 54560.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 2534.09 | 26-JAN-17:00 | 222.14 | 578.72 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 4563.30 | 15-FEB-17:00 | 222.14 | 578.72 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6379.37 | 24-MAR-17:50 | 23.38 | 192.90 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 8219.79 | 16-APR-17:53 | 0.00 | 225.07 | 54560.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 3274.42 | 31-MAY-23:40 | 0.00 | 32.15 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5184.35 | 30-JUN-23:57 | 0.00 | 96.46 | 17537.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 7178.00 | 04-JUL-18:40 | 0.00 | 64.31 | 11691.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 7994.15 | 30-AUG-17:40 | 23.38 | 192.90 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 3237.19 | 30-SEP-23:40 | 0.00 | 32.15 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 4675.98 | 04-OCT-17:00 | 70.15 | 321.51 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6236.40 | 02-NOV-16:50 | 70.15 | 321.51 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 7794.01 | 29-DEC-16:50 | 222.14 | 578.72 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 2534.09 | 0.00 | 32.15 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 8219.79 | 222.14 | 578.72 | 54560.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 93184.59 | 03-JAN-17:00 | 4808.68 | 6471.01 | 94908.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 185081.98 | 15-FEB-17:00 | 4808.68 | 6471.01 | 189816.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 359531.90 | 31-MAR-24:00 | 0.00 | 359.47 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 369665.39 | 29-APR-17:31 | 2530.88 | 3594.74 | 3796325.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 176788.74 | 31-MAY-24:00 | 0.00 | 359.47 | 189816.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 268544.76 | 30-JUN-23:57 | 0.00 | 1078.42 | 854173.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 357729.06 | 31-JUL-23:08 | 0.00 | 1437.90 | 1518530.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 379081.92 | 04-AUG-20:03 | 1518.53 | 4313.93 | 1138897.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 177000.36 | 30-SEP-24:00 | 0.00 | 359.47 | 189816.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 269460.55 | 31-OCT-24:00 | 0.00 | 359.47 | 284724.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 277949.39 | 24-NOV-17:00 | 4808.68 | 6471.01 | 284724.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 369329.29 | 29-DEC-17:00 | 4808.68 | 6471.01 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 93184.59 | 0.00 | 359.47 | 94908.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 379081.92 | 4808.68 | 6471.01 | 3796325.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.178839E+13 | 1165191.02 | 05-JAN-16:10 | 0.299528E+12 | 793341.82 | 17-JAN-07:19 |
February | 0.198226E+13 | 1464007.52 | 14-FEB-16:10 | 0.198778E+12 | 797672.86 | 06-FEB-07:10 |
March | 0.262430E+13 | 1690280.11 | 08-MAR-16:19 | 0.113455E+12 | 442268.88 | 04-MAR-05:10 |
April | 0.302159E+13 | 2024014.16 | 26-APR-15:09 | 0.702553E+11 | 337404.34 | 08-APR-05:10 |
May | 0.205147E+13 | 1532767.54 | 09-MAY-15:20 | 0.661209E+11 | 94055.27 | 05-MAY-05:10 |
June | 0.254740E+13 | 1757314.56 | 26-JUN-15:20 | 0.613147E+11 | 76879.61 | 01-JUN-11:39 |
July | 0.309391E+13 | 1977110.57 | 31-JUL-15:09 | 0.582106E+11 | 73724.49 | 07-JUL-11:50 |
August | 0.359756E+13 | 2182343.09 | 21-AUG-15:09 | 0.611419E+11 | 73205.46 | 31-AUG-11:00 |
September | 0.195706E+13 | 1543923.59 | 12-SEP-15:00 | 0.580583E+11 | 75147.97 | 27-SEP-11:00 |
October | 0.232517E+13 | 1666375.75 | 11-OCT-15:00 | 0.827004E+11 | 449814.87 | 26-OCT-06:10 |
November | 0.246869E+13 | 1510157.00 | 02-NOV-15:00 | 0.120993E+12 | 570763.99 | 27-NOV-07:10 |
December | 0.283594E+13 | 1584069.26 | 20-DEC-16:00 | 0.283455E+12 | 718006.22 | 15-DEC-07:10 |
Annual Sum or Average | 0.302937E+14 | 0.147401E+13 | ||||
Minimum of Months | 0.178839E+13 | 1165191.02 | 0.580583E+11 | 73205.46 | ||
Maximum of Months | 0.359756E+13 | 2182343.09 | 0.299528E+12 | 797672.86 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [J] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [J] | HUMIDIFIER:ELECTRICITY [J] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 0.330609E+12 | 0.723803E+11 | 0.766053E+12 | 0.164269E+12 | 0.208832E+12 | 0.172382E+11 | 0.00 | 0.200012E+11 | 0.272250E+10 | 0.206287E+12 | 0.00 | 0.00 | 0.00 |
February | 0.298335E+12 | 0.607318E+11 | 0.978954E+12 | 0.148381E+12 | 0.193540E+12 | 0.177703E+11 | 0.00 | 0.389422E+11 | 0.815922E+10 | 0.237446E+12 | 0.00 | 0.00 | 0.00 |
March | 0.351794E+12 | 0.605302E+11 | 0.141687E+13 | 0.164522E+12 | 0.230111E+12 | 0.222901E+11 | 0.00 | 0.843930E+11 | 0.271781E+11 | 0.266613E+12 | 0.00 | 0.00 | 0.00 |
April | 0.312475E+12 | 0.517070E+11 | 0.165903E+13 | 0.158945E+12 | 0.250625E+12 | 0.331916E+11 | 0.00 | 0.227840E+12 | 0.687159E+11 | 0.259061E+12 | 0.00 | 0.00 | 0.00 |
May | 0.336658E+12 | 0.476383E+11 | 0.774844E+12 | 0.164394E+12 | 0.270973E+12 | 0.417670E+11 | 0.00 | 0.155893E+12 | 0.720610E+11 | 0.187242E+12 | 0.00 | 0.00 | 0.00 |
June | 0.334248E+12 | 0.434099E+11 | 0.106252E+13 | 0.159182E+12 | 0.303383E+12 | 0.615131E+11 | 0.00 | 0.364815E+12 | 0.111758E+12 | 0.106577E+12 | 0.00 | 0.00 | 0.00 |
July | 0.313459E+12 | 0.459853E+11 | 0.139340E+13 | 0.164155E+12 | 0.322655E+12 | 0.724824E+11 | 0.00 | 0.597854E+12 | 0.158402E+12 | 0.255158E+11 | 0.00 | 0.00 | 0.00 |
August | 0.349239E+12 | 0.507876E+11 | 0.173200E+13 | 0.164521E+12 | 0.327289E+12 | 0.750487E+11 | 0.00 | 0.667837E+12 | 0.151991E+12 | 0.788508E+11 | 0.00 | 0.00 | 0.00 |
September | 0.313553E+12 | 0.556800E+11 | 0.740713E+12 | 0.158944E+12 | 0.264085E+12 | 0.528273E+11 | 0.00 | 0.212078E+12 | 0.968616E+11 | 0.623129E+11 | 0.00 | 0.00 | 0.00 |
October | 0.327652E+12 | 0.645033E+11 | 0.108340E+13 | 0.164268E+12 | 0.242687E+12 | 0.362306E+11 | 0.00 | 0.138393E+12 | 0.533978E+11 | 0.214634E+12 | 0.00 | 0.00 | 0.00 |
November | 0.327017E+12 | 0.684284E+11 | 0.135889E+13 | 0.159043E+12 | 0.213822E+12 | 0.171397E+11 | 0.00 | 0.551696E+11 | 0.121188E+11 | 0.257061E+12 | 0.00 | 0.00 | 0.00 |
December | 0.322444E+12 | 0.740386E+11 | 0.170972E+13 | 0.164159E+12 | 0.210086E+12 | 0.177079E+11 | 0.00 | 0.618376E+11 | 0.811094E+10 | 0.267840E+12 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.391748E+13 | 0.695821E+12 | 0.146764E+14 | 0.193478E+13 | 0.303809E+13 | 0.465207E+12 | 0.00 | 0.262505E+13 | 0.771476E+12 | 0.216944E+13 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.298335E+12 | 0.434099E+11 | 0.740713E+12 | 0.148381E+12 | 0.193540E+12 | 0.171397E+11 | 0.00 | 0.200012E+11 | 0.272250E+10 | 0.255158E+11 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.351794E+12 | 0.740386E+11 | 0.173200E+13 | 0.164522E+12 | 0.327289E+12 | 0.750487E+11 | 0.00 | 0.667837E+12 | 0.158402E+12 | 0.267840E+12 | 0.00 | 0.00 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [J] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.00 | 0.00 | 0.229220E+12 | 0.00 | 0.703076E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.134681E+12 | 0.00 | 0.640970E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.407697E+11 | 0.00 | 0.726856E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.532210E+10 | 0.00 | 0.649332E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.717567E+09 | 0.00 | 0.654034E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 42022391.76 | 0.00 | 0.612727E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.582106E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.611419E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 2293195.06 | 0.00 | 0.580560E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.202812E+11 | 0.00 | 0.624192E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.570225E+11 | 0.00 | 0.639700E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.216145E+12 | 0.00 | 0.673097E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.704204E+12 | 0.00 | 0.769807E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.580560E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.229220E+12 | 0.00 | 0.726856E+11 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | EXTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum} [W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 379269.20 | 04-JAN-16:00 | 57580.60 | 01-JAN-06:10 | 423497.50 | 02-JAN-08:09 | 118502.51 | 31-JAN-08:20 | 149316.16 | 05-JAN-16:40 | 27257.83 | 17-JAN-06:10 | 0.00 | 01-JAN-00:10 |
February | 372703.55 | 16-FEB-08:09 | 57580.60 | 01-FEB-06:10 | 541788.89 | 01-FEB-08:09 | 118525.16 | 16-FEB-08:20 | 187502.92 | 15-FEB-16:00 | 27151.65 | 06-FEB-06:19 | 0.00 | 01-FEB-00:10 |
March | 352283.84 | 20-MAR-07:10 | 57580.60 | 01-MAR-06:10 | 660080.29 | 01-MAR-08:09 | 118509.21 | 20-MAR-07:19 | 202781.44 | 08-MAR-16:19 | 25383.26 | 08-MAR-14:30 | 0.00 | 01-MAR-00:10 |
April | 332294.83 | 03-APR-07:10 | 57580.60 | 01-APR-05:10 | 778371.69 | 03-APR-07:10 | 118493.64 | 03-APR-07:19 | 268246.22 | 28-APR-14:00 | 46327.34 | 13-APR-15:00 | 0.00 | 01-APR-00:10 |
May | 339487.29 | 22-MAY-07:10 | 57580.60 | 01-MAY-05:10 | 423497.50 | 01-MAY-07:10 | 118499.24 | 22-MAY-07:19 | 273680.57 | 19-MAY-15:09 | 48710.39 | 23-MAY-13:09 | 0.00 | 01-MAY-00:10 |
June | 341725.46 | 08-JUN-15:30 | 57580.60 | 01-JUN-19:10 | 541788.89 | 01-JUN-07:10 | 118498.59 | 08-JUN-07:19 | 320013.72 | 28-JUN-14:50 | 60488.20 | 27-JUN-15:00 | 0.00 | 01-JUN-00:10 |
July | 341725.46 | 07-JUL-15:00 | 57580.60 | 01-JUL-19:19 | 660080.29 | 03-JUL-07:10 | 118494.36 | 24-JUL-07:19 | 326580.18 | 31-JUL-15:20 | 60256.32 | 21-JUL-15:00 | 0.00 | 01-JUL-00:10 |
August | 333218.76 | 28-AUG-07:10 | 57580.60 | 01-AUG-05:10 | 778371.69 | 01-AUG-07:10 | 118494.36 | 28-AUG-07:19 | 337697.87 | 07-AUG-15:30 | 52315.55 | 07-AUG-13:39 | 0.00 | 01-AUG-00:10 |
September | 372703.55 | 08-SEP-07:10 | 57580.60 | 01-SEP-05:10 | 423497.50 | 01-SEP-07:10 | 118525.16 | 08-SEP-07:19 | 274349.78 | 15-SEP-15:00 | 61015.54 | 21-SEP-14:09 | 0.00 | 01-SEP-00:10 |
October | 369206.61 | 25-OCT-07:10 | 57580.60 | 01-OCT-05:10 | 541788.89 | 02-OCT-07:10 | 118522.43 | 25-OCT-07:19 | 227000.41 | 02-OCT-15:00 | 61655.43 | 02-OCT-10:00 | 0.00 | 01-OCT-00:10 |
November | 385834.94 | 09-NOV-16:49 | 57580.60 | 01-NOV-05:10 | 660080.29 | 01-NOV-07:10 | 118525.16 | 02-NOV-07:19 | 185337.03 | 03-NOV-15:00 | 25701.17 | 28-NOV-06:10 | 0.00 | 01-NOV-00:10 |
December | 385834.94 | 01-DEC-16:49 | 57580.60 | 01-DEC-06:10 | 778371.69 | 01-DEC-08:09 | 118511.28 | 08-DEC-08:20 | 151943.59 | 29-DEC-16:49 | 26140.67 | 23-DEC-05:10 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 332294.83 | 57580.60 | 423497.50 | 118493.64 | 149316.16 | 25383.26 | 0.00 | |||||||
Maximum of Months | 385834.94 | 57580.60 | 778371.69 | 118525.16 | 337697.87 | 61655.43 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY {Maximum} [W] | HEATREJECTION:ELECTRICITY {TIMESTAMP} | HUMIDIFIER:ELECTRICITY {Maximum} [W] | HUMIDIFIER:ELECTRICITY {TIMESTAMP} | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 62961.24 | 05-JAN-15:30 | 6942.24 | 05-JAN-15:00 | 100000.00 | 01-JAN-11:20 | 0.00 | 0.00 | 0.00 |
February | 191990.34 | 14-FEB-15:00 | 50126.08 | 14-FEB-15:00 | 100000.00 | 01-FEB-04:40 | 0.00 | 0.00 | 0.00 |
March | 238410.20 | 08-MAR-15:00 | 50473.63 | 08-MAR-14:09 | 100000.00 | 01-MAR-05:40 | 0.00 | 0.00 | 0.00 |
April | 367133.26 | 26-APR-15:09 | 52359.19 | 27-APR-13:50 | 100000.00 | 01-APR-04:19 | 0.00 | 0.00 | 0.00 |
May | 277389.04 | 19-MAY-15:09 | 66960.58 | 22-MAY-10:39 | 100000.00 | 01-MAY-00:30 | 0.00 | 0.00 | 0.00 |
June | 387987.26 | 28-JUN-14:50 | 84672.89 | 06-JUN-12:20 | 100000.00 | 03-JUN-17:40 | 0.00 | 0.00 | 0.00 |
July | 441417.47 | 21-JUL-14:50 | 84672.89 | 03-JUL-08:00 | 100000.00 | 03-JUL-21:19 | 0.00 | 0.00 | 0.00 |
August | 453863.97 | 01-AUG-15:09 | 84672.89 | 01-AUG-08:20 | 100000.00 | 02-AUG-18:10 | 0.00 | 0.00 | 0.00 |
September | 329828.27 | 05-SEP-13:39 | 84672.89 | 01-SEP-09:39 | 100000.00 | 30-SEP-17:10 | 0.00 | 0.00 | 0.00 |
October | 314250.43 | 02-OCT-14:00 | 84672.89 | 02-OCT-13:50 | 100000.00 | 04-OCT-21:10 | 0.00 | 0.00 | 0.00 |
November | 121955.74 | 09-NOV-13:00 | 49514.40 | 02-NOV-15:20 | 100000.00 | 01-NOV-21:10 | 0.00 | 0.00 | 0.00 |
December | 40405.72 | 24-DEC-14:00 | 18195.30 | 24-DEC-14:00 | 100000.00 | 01-DEC-05:19 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 40405.72 | 6942.24 | 100000.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 453863.97 | 84672.89 | 100000.00 | 0.00 | 0.00 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY {AT MAX/MIN} [W] | |
January | 1165191.02 | 05-JAN-16:10 | 334652.47 | 423497.50 | 0.00 | 84452.08 | 131663.20 | 24441.30 | 0.00 | 60340.34 | 6144.14 |
February | 1464007.52 | 14-FEB-16:10 | 332294.83 | 541788.89 | 0.00 | 84450.25 | 141123.40 | 25413.86 | 0.00 | 188845.08 | 50091.21 |
March | 1690280.11 | 08-MAR-16:19 | 332294.83 | 660080.29 | 0.00 | 84450.25 | 202781.44 | 24963.25 | 0.00 | 235404.46 | 50305.60 |
April | 2024014.16 | 26-APR-15:09 | 332294.83 | 778371.69 | 0.00 | 84450.25 | 265765.65 | 46183.42 | 0.00 | 367133.26 | 49815.07 |
May | 1532767.54 | 09-MAY-15:20 | 332294.83 | 423497.50 | 0.00 | 84450.25 | 243462.46 | 46008.32 | 0.00 | 253239.11 | 49815.07 |
June | 1757314.56 | 26-JUN-15:20 | 332294.83 | 541788.89 | 0.00 | 84450.25 | 312865.20 | 53575.98 | 0.00 | 375875.44 | 52938.19 |
July | 1977110.57 | 31-JUL-15:09 | 332294.83 | 660080.29 | 0.00 | 84450.25 | 326110.70 | 48760.60 | 0.00 | 435633.76 | 84672.89 |
August | 2182343.09 | 21-AUG-15:09 | 332294.83 | 778371.69 | 0.00 | 84450.25 | 308360.19 | 48514.66 | 0.00 | 445678.58 | 84672.89 |
September | 1543923.59 | 12-SEP-15:00 | 332294.83 | 423497.50 | 0.00 | 84450.25 | 271251.24 | 48501.73 | 0.00 | 251212.61 | 51793.62 |
October | 1666375.75 | 11-OCT-15:00 | 332294.83 | 541788.89 | 0.00 | 84450.25 | 217340.66 | 48178.65 | 0.00 | 285840.46 | 56482.01 |
November | 1510157.00 | 02-NOV-15:00 | 334652.47 | 660080.29 | 0.00 | 84452.08 | 152471.74 | 24567.20 | 0.00 | 104435.04 | 49498.17 |
December | 1584069.26 | 20-DEC-16:00 | 385834.94 | 778371.69 | 57580.60 | 84492.05 | 122420.64 | 24373.88 | 0.00 | 27428.32 | 3567.14 |
Annual Sum or Average | |||||||||||
Minimum of Months | 1165191.02 | 332294.83 | 423497.50 | 0.00 | 84450.25 | 122420.64 | 24373.88 | 0.00 | 27428.32 | 3567.14 | |
Maximum of Months | 2182343.09 | 385834.94 | 778371.69 | 57580.60 | 84492.05 | 326110.70 | 53575.98 | 0.00 | 445678.58 | 84672.89 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS {Maximum} [W] | WATERSYSTEMS:NATURALGAS {TIMESTAMP} | COGENERATION:NATURALGAS [] | |
January | 0.00 | 0.00 | 776734.29 | 17-JAN-07:10 | 0.00 | 84025.90 | 31-JAN-12:30 | 0.00 |
February | 0.00 | 0.00 | 776482.32 | 06-FEB-07:10 | 0.00 | 84068.58 | 10-FEB-12:39 | 0.00 |
March | 0.00 | 0.00 | 434122.30 | 04-MAR-05:10 | 0.00 | 83730.13 | 02-MAR-12:50 | 0.00 |
April | 0.00 | 0.00 | 308220.58 | 08-APR-05:10 | 0.00 | 82136.74 | 03-APR-11:50 | 0.00 |
May | 0.00 | 0.00 | 85908.69 | 05-MAY-05:10 | 0.00 | 79896.55 | 01-MAY-11:20 | 0.00 |
June | 0.00 | 0.00 | 12755.92 | 09-JUN-05:10 | 0.00 | 76879.61 | 01-JUN-11:39 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 73724.49 | 07-JUL-11:50 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 73205.46 | 31-AUG-11:00 | 0.00 |
September | 0.00 | 0.00 | 968.35 | 09-SEP-05:49 | 0.00 | 75147.97 | 27-SEP-11:00 | 0.00 |
October | 0.00 | 0.00 | 427973.95 | 26-OCT-06:19 | 0.00 | 78166.55 | 30-OCT-11:20 | 0.00 |
November | 0.00 | 0.00 | 562617.41 | 27-NOV-07:10 | 0.00 | 81093.45 | 29-NOV-12:20 | 0.00 |
December | 0.00 | 0.00 | 686363.94 | 15-DEC-07:10 | 0.00 | 83100.21 | 29-DEC-12:20 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 73205.46 | 0.00 | ||
Maximum of Months | 0.00 | 0.00 | 776734.29 | 0.00 | 84068.58 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 5.83 | 26.58 | 0.50 | 26.65 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 25.96 | 0.17 | 26.05 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 25.81 | 0.00 | 25.81 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 4.67 | 26.31 | 0.00 | 26.31 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 4.00 | 26.73 | 0.00 | 26.73 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 4.50 | 25.97 | 0.00 | 25.97 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 26.09 | 0.00 | 26.09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 6.67 | 26.29 | 0.00 | 26.29 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 7.50 | 26.45 | 0.17 | 26.48 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 9.17 | 26.60 | 0.83 | 26.67 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 11.17 | 26.63 | 0.00 | 26.63 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 7.67 | 26.12 | 0.67 | 26.21 |
Annual Sum or Average | 0.00 | 0.00 | 70.67 | 26.37 | 2.33 | 26.41 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 25.81 | 0.00 | 25.81 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 11.17 | 26.73 | 0.83 | 26.73 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 26.28 | 0.00 | 26.28 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 25.62 | 0.00 | 25.62 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 25.61 | 0.00 | 25.61 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 25.61 | 0.00 | 25.61 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 25.66 | 0.00 | 25.66 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 25.71 | 0.00 | 25.71 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 25.61 | 0.00 | 25.61 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 25.64 | 0.00 | 25.64 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 5.33 | 25.67 | 0.00 | 25.67 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 26.28 | 0.00 | 26.28 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.33 | 19.16 | 0.00 | 19.16 | 0.00 | 19.16 | 0.00 | 19.16 |
February | 0.33 | 18.94 | 0.00 | 18.94 | 0.00 | 18.94 | 0.00 | 18.94 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.67 | 18.60 | 0.00 | 18.60 | 0.00 | 18.60 | 0.00 | 18.60 |
Annual Sum or Average | 1.33 | 18.82 | 0.00 | 18.82 | 0.00 | 18.82 | 0.00 | 18.82 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.67 | 19.16 | 0.00 | 19.16 | 0.00 | 19.16 | 0.00 | 19.16 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 4.83 | 27.48 | 3.33 | 27.47 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 8.67 | 27.41 | 6.67 | 27.44 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 5.67 | 27.39 | 4.17 | 27.44 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 27.37 | 1.67 | 27.37 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 20.83 | 27.42 | 15.83 | 27.44 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 8.67 | 27.48 | 6.67 | 27.47 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.47 | 0.33 | 27.47 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.70 | 0.83 | 27.70 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 28.34 | 2.33 | 28.34 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 4.67 | 28.48 | 4.67 | 28.48 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 8.17 | 28.59 | 8.17 | 28.59 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 9.17 | 28.39 | 9.17 | 28.39 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 16.00 | 28.47 | 15.83 | 28.48 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 10.00 | 28.37 | 9.67 | 28.38 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 28.34 | 5.00 | 28.34 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 28.21 | 5.17 | 28.21 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 27.73 | 1.83 | 27.73 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 63.50 | 28.39 | 63.00 | 28.39 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 16.00 | 28.59 | 15.83 | 28.59 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 30.00 | 25.85 | 30.00 | 25.85 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 21.50 | 25.75 | 21.50 | 25.75 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 4.50 | 28.30 | 4.50 | 28.30 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 4.33 | 27.82 | 4.33 | 27.82 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 4.33 | 27.60 | 4.33 | 27.60 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 4.17 | 27.55 | 4.00 | 27.55 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 11.33 | 27.73 | 9.67 | 27.78 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 9.17 | 27.99 | 7.33 | 28.07 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 17.17 | 26.84 | 17.00 | 26.84 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 51.67 | 25.80 | 51.33 | 25.79 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 46.67 | 25.67 | 46.67 | 25.67 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 33.00 | 25.65 | 33.00 | 25.65 |
Annual Sum or Average | 0.00 | 0.00 | 237.83 | 26.15 | 233.67 | 26.15 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 4.17 | 25.65 | 4.00 | 25.65 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 51.67 | 28.30 | 51.33 | 28.30 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 27.87 | 1.17 | 27.87 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 28.15 | 1.67 | 28.15 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 4.00 | 28.85 | 3.00 | 28.94 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 12.17 | 28.16 | 5.67 | 28.37 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 6.33 | 28.61 | 4.50 | 28.72 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 17.33 | 28.03 | 6.67 | 28.26 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 26.00 | 27.93 | 9.50 | 28.19 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 24.83 | 27.97 | 8.83 | 28.17 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 7.67 | 28.45 | 5.17 | 28.58 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 6.17 | 28.57 | 4.67 | 28.75 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 3.67 | 28.34 | 3.67 | 28.34 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 28.22 | 2.50 | 28.22 |
Annual Sum or Average | 0.00 | 0.00 | 113.50 | 28.14 | 57.00 | 28.35 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 27.87 | 1.17 | 27.87 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 26.00 | 28.85 | 9.50 | 28.94 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 3.67 | 18.85 | 0.17 | 18.91 | 0.00 | 18.91 | 0.00 | 18.91 |
February | 2.17 | 18.87 | 0.17 | 18.98 | 0.00 | 18.98 | 0.00 | 18.98 |
March | 0.33 | 19.26 | 0.00 | 19.26 | 0.00 | 19.26 | 0.00 | 19.26 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 3.67 | 27.49 | 2.50 | 27.47 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 6.00 | 27.58 | 4.50 | 27.57 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 27.48 | 2.00 | 27.48 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.50 | 19.08 | 0.00 | 19.08 | 0.00 | 19.08 | 0.00 | 19.08 |
December | 3.33 | 19.13 | 0.00 | 19.13 | 0.00 | 19.13 | 0.00 | 19.13 |
Annual Sum or Average | 10.00 | 18.97 | 0.33 | 19.02 | 12.50 | 23.68 | 9.00 | 24.76 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 3.67 | 19.26 | 0.17 | 19.26 | 6.00 | 27.58 | 4.50 | 27.57 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 3.33 | 18.80 | 0.00 | 18.80 | 0.00 | 18.80 | 0.00 | 18.80 |
February | 1.83 | 18.75 | 0.00 | 18.75 | 0.00 | 18.75 | 0.00 | 18.75 |
March | 0.17 | 19.18 | 0.00 | 19.18 | 1.83 | 27.46 | 1.83 | 27.82 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 4.33 | 28.39 | 4.33 | 28.39 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 10.00 | 28.49 | 10.00 | 28.49 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 9.83 | 28.58 | 9.50 | 28.60 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 18.17 | 28.70 | 16.83 | 28.75 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 11.17 | 28.66 | 10.50 | 28.69 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 4.50 | 28.61 | 4.50 | 28.61 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 4.00 | 28.20 | 4.00 | 28.20 |
November | 0.50 | 19.16 | 0.00 | 19.16 | 0.00 | 19.16 | 0.00 | 19.16 |
December | 3.17 | 19.14 | 0.00 | 19.14 | 0.00 | 19.14 | 0.00 | 19.14 |
Annual Sum or Average | 9.00 | 18.94 | 0.00 | 18.94 | 63.83 | 27.38 | 61.50 | 27.94 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.75 | 0.00 | 18.75 |
Maximum of Months | 3.33 | 19.18 | 0.00 | 19.18 | 18.17 | 28.70 | 16.83 | 28.75 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 1.00 | 18.43 | 0.00 | 18.43 | 51.67 | 25.72 | 51.67 | 25.79 |
February | 0.67 | 18.86 | 0.00 | 18.86 | 37.00 | 25.58 | 37.00 | 25.64 |
March | 0.17 | 19.36 | 0.00 | 19.36 | 8.67 | 26.42 | 8.50 | 26.48 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 27.78 | 3.33 | 27.78 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 27.60 | 3.33 | 27.60 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 3.67 | 27.56 | 3.50 | 27.56 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 10.17 | 27.82 | 8.67 | 27.85 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 8.00 | 28.11 | 6.83 | 28.15 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 31.33 | 26.07 | 30.83 | 26.06 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 81.00 | 25.81 | 80.33 | 25.80 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 64.50 | 25.79 | 64.50 | 25.79 |
December | 0.83 | 19.20 | 0.00 | 19.20 | 54.67 | 25.45 | 54.67 | 25.50 |
Annual Sum or Average | 2.67 | 18.84 | 0.00 | 18.84 | 357.33 | 25.91 | 353.17 | 25.93 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 25.45 | 3.33 | 25.50 |
Maximum of Months | 1.00 | 19.36 | 0.00 | 19.36 | 81.00 | 28.11 | 80.33 | 28.15 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 2.33 | 18.88 | 0.00 | 18.88 | 0.00 | 18.88 | 0.00 | 18.88 |
February | 1.33 | 18.75 | 0.00 | 18.75 | 0.17 | 19.76 | 0.17 | 20.57 |
March | 0.17 | 19.31 | 0.00 | 19.31 | 2.67 | 27.83 | 2.33 | 28.04 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 4.83 | 28.74 | 3.00 | 28.83 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 5.83 | 28.56 | 3.67 | 28.67 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 10.33 | 28.81 | 5.00 | 28.84 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 11.33 | 28.80 | 6.17 | 28.90 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 8.50 | 28.67 | 4.83 | 28.71 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 6.00 | 28.64 | 4.17 | 28.73 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 3.67 | 28.79 | 3.00 | 28.87 |
November | 0.17 | 19.32 | 0.00 | 19.32 | 0.17 | 23.33 | 0.17 | 24.67 |
December | 1.67 | 19.25 | 0.00 | 19.25 | 0.00 | 19.25 | 0.00 | 19.25 |
Annual Sum or Average | 5.67 | 18.99 | 0.00 | 18.99 | 53.50 | 27.77 | 32.50 | 28.16 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.88 | 0.00 | 18.88 |
Maximum of Months | 2.33 | 19.32 | 0.00 | 19.32 | 11.33 | 28.81 | 6.17 | 28.90 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 20.00 | 16.92 | 3.17 | 16.87 | 0.00 | 16.87 | 0.00 | 16.87 |
February | 14.00 | 17.04 | 2.00 | 17.08 | 0.00 | 17.08 | 0.00 | 17.08 |
March | 3.00 | 18.75 | 0.00 | 18.75 | 0.00 | 18.75 | 0.00 | 18.75 |
April | 0.17 | 19.10 | 0.00 | 19.10 | 0.00 | 19.10 | 0.00 | 19.10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 4.83 | 27.65 | 3.00 | 27.63 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 10.17 | 27.71 | 7.67 | 27.71 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 27.66 | 3.50 | 27.68 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 27.41 | 1.17 | 27.41 |
October | 1.00 | 18.88 | 0.00 | 18.88 | 0.00 | 18.88 | 0.00 | 18.88 |
November | 5.50 | 17.86 | 0.33 | 17.70 | 0.00 | 17.70 | 0.00 | 17.70 |
December | 17.83 | 16.98 | 1.83 | 16.98 | 0.00 | 16.98 | 0.00 | 16.98 |
Annual Sum or Average | 61.50 | 17.18 | 7.33 | 17.14 | 21.17 | 19.61 | 15.33 | 20.78 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 20.00 | 19.10 | 3.17 | 19.10 | 10.17 | 27.71 | 7.67 | 27.71 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 13.33 | 16.92 | 0.67 | 16.82 | 0.00 | 16.82 | 0.00 | 16.82 |
February | 11.00 | 16.87 | 0.67 | 16.76 | 0.00 | 16.76 | 0.00 | 16.76 |
March | 2.67 | 18.78 | 0.00 | 18.78 | 1.00 | 21.23 | 1.00 | 22.63 |
April | 0.17 | 19.14 | 0.00 | 19.14 | 3.00 | 27.71 | 3.00 | 27.94 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 10.83 | 28.43 | 10.83 | 28.43 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 10.67 | 28.59 | 9.83 | 28.62 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 19.33 | 28.80 | 17.00 | 28.87 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 12.33 | 28.71 | 10.83 | 28.78 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 28.45 | 5.17 | 28.45 |
October | 1.00 | 18.49 | 0.00 | 18.49 | 3.17 | 25.67 | 3.17 | 26.65 |
November | 4.17 | 18.31 | 0.17 | 18.18 | 0.00 | 18.18 | 0.00 | 18.18 |
December | 14.17 | 17.01 | 0.33 | 16.96 | 0.00 | 16.96 | 0.00 | 16.96 |
Annual Sum or Average | 46.50 | 17.21 | 1.83 | 17.12 | 65.50 | 23.71 | 60.83 | 25.43 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.76 | 0.00 | 16.76 |
Maximum of Months | 14.17 | 19.14 | 0.67 | 19.14 | 19.33 | 28.80 | 17.00 | 28.87 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 9.50 | 17.61 | 0.00 | 17.61 | 22.17 | 23.38 | 22.17 | 24.40 |
February | 6.83 | 18.02 | 0.17 | 18.08 | 18.50 | 23.53 | 18.50 | 24.40 |
March | 1.33 | 18.97 | 0.00 | 18.97 | 3.50 | 25.71 | 3.50 | 26.79 |
April | 0.17 | 19.24 | 0.00 | 19.24 | 2.17 | 27.20 | 2.17 | 27.49 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 4.50 | 27.67 | 4.50 | 27.67 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 4.33 | 27.71 | 3.50 | 27.73 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 11.50 | 28.03 | 9.33 | 28.07 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 9.17 | 28.24 | 7.00 | 28.31 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 17.33 | 27.04 | 16.67 | 27.03 |
October | 0.50 | 18.50 | 0.00 | 18.50 | 49.33 | 25.82 | 48.67 | 25.85 |
November | 1.33 | 18.36 | 0.00 | 18.36 | 31.83 | 25.42 | 31.83 | 25.57 |
December | 9.17 | 17.73 | 0.00 | 17.73 | 13.00 | 22.69 | 13.00 | 23.99 |
Annual Sum or Average | 28.83 | 17.87 | 0.17 | 17.88 | 187.33 | 25.22 | 180.83 | 25.71 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 22.69 | 2.17 | 23.99 |
Maximum of Months | 9.50 | 19.24 | 0.17 | 19.24 | 49.33 | 28.24 | 48.67 | 28.31 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 10.83 | 17.53 | 0.00 | 17.53 | 0.00 | 17.53 | 0.00 | 17.53 |
February | 7.00 | 17.97 | 0.00 | 17.97 | 0.00 | 17.97 | 0.00 | 17.97 |
March | 1.17 | 18.99 | 0.00 | 18.99 | 2.00 | 24.90 | 1.67 | 26.07 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 4.67 | 28.74 | 3.00 | 28.82 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 6.17 | 28.63 | 4.00 | 28.72 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 9.50 | 29.05 | 4.50 | 29.07 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 12.83 | 28.86 | 6.83 | 28.98 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 9.00 | 28.83 | 4.83 | 28.92 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 6.83 | 28.59 | 5.00 | 28.64 |
October | 0.50 | 18.60 | 0.00 | 18.60 | 3.67 | 27.49 | 3.00 | 28.06 |
November | 2.17 | 18.68 | 0.00 | 18.68 | 0.00 | 18.68 | 0.00 | 18.68 |
December | 7.83 | 18.20 | 0.00 | 18.20 | 0.00 | 18.20 | 0.00 | 18.20 |
Annual Sum or Average | 29.50 | 17.97 | 0.00 | 17.97 | 54.67 | 25.00 | 32.83 | 26.11 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.53 | 0.00 | 17.53 |
Maximum of Months | 10.83 | 18.99 | 0.00 | 18.99 | 12.83 | 29.05 | 6.83 | 29.07 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 4.50 | 28.01 | 2.67 | 27.98 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 31.83 | 27.93 | 24.83 | 27.88 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 36.33 | 27.94 | 27.50 | 27.89 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 31.83 | 28.01 | 24.83 | 27.98 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 28.01 | 2.00 | 27.98 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 13.00 | 28.02 | 8.17 | 27.95 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 16.50 | 28.02 | 10.17 | 27.95 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 13.00 | 28.02 | 8.17 | 27.98 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 27.92 | 1.17 | 27.92 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 12.17 | 28.23 | 6.17 | 28.16 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 14.67 | 28.18 | 7.33 | 28.12 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 12.17 | 28.23 | 6.17 | 28.16 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 10.50 | 27.86 | 10.50 | 27.86 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 27.95 | 0.33 | 27.89 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 376.50 | 29.82 | 334.67 | 29.88 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 388.33 | 29.76 | 345.50 | 29.82 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 376.50 | 29.82 | 334.67 | 29.88 |
Report: ComfortReportSimple55Monthly
For: BASEMENT
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 172.50 | 24.00 | 81.17 | 24.76 | 0.00 | 24.76 |
February | 128.67 | 24.00 | 76.83 | 24.88 | 0.00 | 24.88 |
March | 114.17 | 24.00 | 75.00 | 24.93 | 0.00 | 24.93 |
April | 120.00 | 24.00 | 87.67 | 25.08 | 0.00 | 25.08 |
May | 72.67 | 24.00 | 161.67 | 25.01 | 0.67 | 25.01 |
June | 2.17 | 24.00 | 307.83 | 24.77 | 0.00 | 24.77 |
July | 123.17 | 24.45 | 477.00 | 24.62 | 123.17 | 24.59 |
August | 85.33 | 24.28 | 502.50 | 24.48 | 85.33 | 24.45 |
September | 15.83 | 24.73 | 394.00 | 24.71 | 15.83 | 24.71 |
October | 35.33 | 24.00 | 204.67 | 25.26 | 0.00 | 25.26 |
November | 42.83 | 24.00 | 109.67 | 25.85 | 0.00 | 25.85 |
December | 154.33 | 24.00 | 95.33 | 24.99 | 0.00 | 24.99 |
Annual Sum or Average | 1067.00 | 24.09 | 2573.33 | 24.83 | 225.00 | 24.81 |
Minimum of Months | 2.17 | 24.00 | 75.00 | 24.48 | 0.00 | 24.45 |
Maximum of Months | 172.50 | 24.73 | 502.50 | 25.85 | 123.17 | 25.85 |
Report: ComfortReportSimple55Monthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 244.17 | 23.95 | 11.67 | 24.04 | 0.00 | 24.04 |
February | 157.17 | 23.98 | 24.50 | 24.23 | 0.00 | 24.23 |
March | 121.17 | 24.01 | 44.33 | 24.55 | 0.00 | 24.55 |
April | 80.00 | 24.01 | 42.33 | 24.71 | 0.00 | 24.71 |
May | 77.00 | 24.02 | 141.50 | 24.51 | 1.00 | 24.50 |
June | 0.67 | 24.00 | 329.00 | 24.35 | 0.00 | 24.35 |
July | 137.33 | 24.45 | 481.50 | 24.32 | 137.33 | 24.34 |
August | 60.33 | 24.29 | 512.67 | 24.22 | 60.33 | 24.23 |
September | 14.67 | 24.11 | 397.17 | 24.41 | 14.67 | 24.40 |
October | 56.83 | 23.99 | 187.00 | 24.61 | 0.00 | 24.61 |
November | 80.67 | 24.00 | 61.17 | 24.76 | 0.00 | 24.76 |
December | 174.67 | 24.00 | 47.67 | 24.46 | 0.00 | 24.46 |
Annual Sum or Average | 1204.67 | 24.06 | 2280.50 | 24.38 | 213.33 | 24.38 |
Minimum of Months | 0.67 | 23.95 | 11.67 | 24.04 | 0.00 | 24.04 |
Maximum of Months | 244.17 | 24.45 | 512.67 | 24.76 | 137.33 | 24.76 |
Report: ComfortReportSimple55Monthly
For: CORE_MID
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 490.83 | 23.46 | 0.00 | 23.46 | 0.00 | 23.46 |
February | 405.17 | 23.61 | 0.00 | 23.61 | 0.00 | 23.61 |
March | 334.17 | 23.80 | 1.17 | 23.80 | 0.00 | 23.80 |
April | 284.67 | 23.93 | 4.83 | 23.95 | 0.00 | 23.95 |
May | 149.83 | 23.93 | 83.50 | 24.13 | 1.17 | 24.13 |
June | 20.33 | 23.90 | 269.33 | 24.26 | 0.00 | 24.26 |
July | 148.17 | 24.18 | 469.33 | 24.23 | 148.17 | 24.22 |
August | 83.00 | 24.19 | 489.33 | 24.22 | 83.00 | 24.22 |
September | 18.67 | 24.30 | 343.83 | 24.32 | 17.67 | 24.32 |
October | 191.33 | 23.82 | 106.50 | 24.04 | 0.00 | 24.04 |
November | 372.00 | 23.75 | 2.50 | 23.76 | 0.00 | 23.76 |
December | 484.83 | 23.52 | 0.00 | 23.52 | 0.00 | 23.52 |
Annual Sum or Average | 2983.00 | 23.72 | 1770.33 | 23.93 | 250.00 | 23.94 |
Minimum of Months | 18.67 | 23.46 | 0.00 | 23.46 | 0.00 | 23.46 |
Maximum of Months | 490.83 | 24.30 | 489.33 | 24.32 | 148.17 | 24.32 |
Report: ComfortReportSimple55Monthly
For: CORE_TOP
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 21.99 | 124.83 | 21.61 | 124.83 | 21.35 |
February | 448.33 | 22.53 | 55.50 | 22.31 | 55.50 | 22.13 |
March | 455.17 | 23.21 | 9.33 | 23.16 | 9.33 | 23.11 |
April | 336.50 | 23.64 | 1.50 | 23.65 | 0.00 | 23.65 |
May | 170.83 | 23.70 | 81.83 | 23.92 | 1.17 | 23.92 |
June | 30.00 | 23.73 | 278.00 | 24.23 | 0.00 | 24.23 |
July | 137.83 | 24.21 | 478.33 | 24.27 | 137.83 | 24.26 |
August | 85.67 | 24.18 | 495.67 | 24.24 | 85.67 | 24.23 |
September | 42.33 | 23.88 | 321.67 | 24.24 | 20.33 | 24.23 |
October | 286.33 | 23.28 | 86.50 | 23.50 | 1.67 | 23.50 |
November | 454.67 | 22.78 | 45.17 | 22.59 | 45.17 | 22.43 |
December | 497.00 | 22.01 | 130.50 | 21.65 | 130.50 | 21.41 |
Annual Sum or Average | 3446.67 | 22.86 | 2108.83 | 23.14 | 612.00 | 23.01 |
Minimum of Months | 30.00 | 21.99 | 1.50 | 21.61 | 0.00 | 21.35 |
Maximum of Months | 502.00 | 24.21 | 495.67 | 24.27 | 137.83 | 24.26 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 22.24 | 42.67 | 22.14 | 42.67 | 22.05 |
February | 445.17 | 22.71 | 15.17 | 22.65 | 15.17 | 22.59 |
March | 427.00 | 23.34 | 0.00 | 23.34 | 0.00 | 23.34 |
April | 247.50 | 23.79 | 13.33 | 23.88 | 0.00 | 23.88 |
May | 132.00 | 23.79 | 138.00 | 24.23 | 0.83 | 24.23 |
June | 11.17 | 26.01 | 367.50 | 24.49 | 8.17 | 24.54 |
July | 110.67 | 25.32 | 490.83 | 24.63 | 110.67 | 24.74 |
August | 62.67 | 25.01 | 508.00 | 24.39 | 62.67 | 24.45 |
September | 45.00 | 24.27 | 347.67 | 24.39 | 18.17 | 24.42 |
October | 279.83 | 23.44 | 109.67 | 23.70 | 0.00 | 23.70 |
November | 459.00 | 23.15 | 1.00 | 23.15 | 1.00 | 23.14 |
December | 497.00 | 22.48 | 20.17 | 22.43 | 20.17 | 22.37 |
Annual Sum or Average | 3219.00 | 23.11 | 2054.00 | 23.57 | 279.50 | 23.59 |
Minimum of Months | 11.17 | 22.24 | 0.00 | 22.14 | 0.00 | 22.05 |
Maximum of Months | 502.00 | 26.01 | 508.00 | 24.63 | 110.67 | 24.74 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 444.17 | 22.09 | 52.00 | 22.09 | 39.33 | 22.00 |
February | 367.67 | 22.40 | 35.00 | 22.52 | 11.00 | 22.49 |
March | 301.33 | 22.86 | 70.83 | 23.18 | 7.17 | 23.25 |
April | 170.33 | 23.66 | 141.83 | 24.14 | 14.33 | 24.28 |
May | 135.50 | 24.25 | 237.33 | 24.52 | 32.00 | 24.72 |
June | 46.50 | 25.72 | 397.33 | 24.55 | 31.67 | 24.71 |
July | 130.50 | 25.53 | 481.33 | 24.70 | 130.00 | 24.85 |
August | 92.83 | 25.19 | 484.17 | 24.43 | 85.00 | 24.55 |
September | 77.00 | 24.50 | 384.67 | 24.43 | 35.83 | 24.55 |
October | 227.67 | 23.21 | 184.67 | 23.85 | 15.33 | 23.97 |
November | 380.67 | 22.71 | 37.00 | 22.90 | 4.83 | 22.91 |
December | 442.50 | 22.10 | 45.17 | 22.06 | 38.67 | 21.98 |
Annual Sum or Average | 2816.67 | 22.98 | 2551.33 | 23.64 | 445.17 | 23.74 |
Minimum of Months | 46.50 | 22.09 | 35.00 | 22.06 | 4.83 | 21.98 |
Maximum of Months | 444.17 | 25.72 | 484.17 | 24.70 | 130.00 | 24.85 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 314.00 | 22.80 | 174.00 | 23.30 | 60.33 | 23.32 |
February | 246.17 | 22.97 | 155.50 | 23.56 | 24.67 | 23.62 |
March | 260.00 | 23.31 | 122.67 | 23.71 | 12.50 | 23.80 |
April | 175.00 | 23.63 | 118.17 | 24.06 | 5.00 | 24.12 |
May | 151.00 | 23.76 | 158.33 | 24.22 | 11.67 | 24.32 |
June | 40.17 | 24.37 | 337.33 | 24.38 | 10.00 | 24.45 |
July | 116.00 | 25.30 | 487.17 | 24.61 | 116.00 | 24.72 |
August | 69.83 | 25.42 | 508.67 | 24.47 | 69.83 | 24.57 |
September | 75.00 | 25.49 | 399.50 | 24.73 | 54.17 | 24.89 |
October | 168.83 | 24.21 | 277.83 | 24.63 | 56.00 | 24.82 |
November | 248.00 | 23.70 | 177.83 | 24.26 | 35.17 | 24.44 |
December | 289.50 | 23.00 | 187.00 | 23.50 | 48.17 | 23.52 |
Annual Sum or Average | 2153.50 | 23.60 | 3104.00 | 24.14 | 503.50 | 24.25 |
Minimum of Months | 40.17 | 22.80 | 118.17 | 23.30 | 5.00 | 23.32 |
Maximum of Months | 314.00 | 25.49 | 508.67 | 24.73 | 116.00 | 24.89 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 410.67 | 22.28 | 39.83 | 22.50 | 1.17 | 22.51 |
February | 299.83 | 22.91 | 79.17 | 23.27 | 4.33 | 23.31 |
March | 167.00 | 23.56 | 125.83 | 24.11 | 14.17 | 24.26 |
April | 45.67 | 25.33 | 236.67 | 25.04 | 21.83 | 25.20 |
May | 87.50 | 24.19 | 284.17 | 24.54 | 19.50 | 24.66 |
June | 43.33 | 25.88 | 457.67 | 24.61 | 41.17 | 24.72 |
July | 168.67 | 25.19 | 497.00 | 24.72 | 168.67 | 24.82 |
August | 141.67 | 25.12 | 514.00 | 24.61 | 141.67 | 24.70 |
September | 52.00 | 25.38 | 423.17 | 24.64 | 42.50 | 24.74 |
October | 138.00 | 23.74 | 248.00 | 24.35 | 19.67 | 24.48 |
November | 223.17 | 23.51 | 105.33 | 23.91 | 10.17 | 24.01 |
December | 311.50 | 23.30 | 72.33 | 23.59 | 6.00 | 23.65 |
Annual Sum or Average | 2089.00 | 23.58 | 3083.17 | 24.20 | 490.83 | 24.33 |
Minimum of Months | 43.33 | 22.28 | 39.83 | 22.50 | 1.17 | 22.51 |
Maximum of Months | 410.67 | 25.88 | 514.00 | 25.04 | 168.67 | 25.20 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.79 | 311.00 | 20.59 | 311.00 | 20.51 |
February | 454.00 | 21.24 | 183.50 | 21.00 | 183.50 | 20.87 |
March | 511.00 | 22.32 | 67.83 | 22.13 | 67.83 | 21.97 |
April | 395.17 | 23.17 | 11.67 | 23.11 | 11.67 | 23.05 |
May | 209.33 | 23.47 | 91.33 | 23.79 | 1.67 | 23.78 |
June | 29.33 | 24.08 | 336.67 | 24.39 | 5.33 | 24.43 |
July | 111.50 | 25.10 | 488.83 | 24.59 | 111.50 | 24.67 |
August | 67.17 | 24.58 | 488.83 | 24.35 | 64.00 | 24.38 |
September | 89.83 | 23.54 | 284.33 | 24.11 | 14.67 | 24.12 |
October | 381.33 | 22.57 | 92.83 | 22.68 | 28.67 | 22.58 |
November | 489.00 | 21.62 | 143.50 | 21.35 | 143.50 | 21.19 |
December | 497.00 | 20.68 | 353.50 | 20.55 | 353.50 | 20.49 |
Annual Sum or Average | 3736.67 | 22.02 | 2853.83 | 22.38 | 1296.83 | 22.16 |
Minimum of Months | 29.33 | 20.68 | 11.67 | 20.55 | 1.67 | 20.49 |
Maximum of Months | 511.00 | 25.10 | 488.83 | 24.59 | 353.50 | 24.67 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 412.33 | 21.19 | 190.50 | 20.97 | 190.50 | 20.85 |
February | 351.50 | 21.46 | 112.00 | 21.30 | 102.50 | 21.15 |
March | 330.33 | 22.21 | 69.33 | 22.41 | 29.00 | 22.36 |
April | 190.33 | 23.18 | 113.17 | 23.78 | 16.83 | 23.88 |
May | 164.00 | 23.87 | 177.50 | 24.39 | 34.50 | 24.63 |
June | 69.00 | 25.05 | 317.83 | 24.67 | 37.33 | 24.86 |
July | 129.17 | 25.67 | 408.83 | 24.92 | 128.50 | 25.07 |
August | 92.50 | 25.32 | 406.33 | 24.65 | 85.50 | 24.78 |
September | 102.83 | 23.90 | 277.83 | 24.34 | 32.17 | 24.47 |
October | 247.00 | 22.60 | 142.67 | 23.22 | 29.17 | 23.24 |
November | 367.67 | 21.75 | 66.67 | 21.73 | 51.83 | 21.60 |
December | 414.33 | 21.07 | 217.50 | 20.84 | 217.33 | 20.73 |
Annual Sum or Average | 2871.00 | 22.33 | 2500.17 | 22.94 | 955.17 | 22.87 |
Minimum of Months | 69.00 | 21.07 | 66.67 | 20.84 | 16.83 | 20.73 |
Maximum of Months | 414.33 | 25.67 | 408.83 | 24.92 | 217.33 | 25.07 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 345.17 | 22.57 | 227.17 | 22.96 | 130.83 | 22.91 |
February | 269.50 | 22.56 | 190.50 | 23.10 | 72.17 | 23.06 |
March | 297.50 | 22.73 | 129.17 | 23.17 | 27.83 | 23.19 |
April | 229.17 | 23.12 | 100.50 | 23.58 | 7.17 | 23.60 |
May | 199.83 | 23.41 | 127.67 | 23.89 | 10.50 | 23.96 |
June | 69.33 | 23.68 | 299.67 | 24.27 | 8.00 | 24.33 |
July | 113.83 | 25.19 | 479.17 | 24.60 | 113.83 | 24.70 |
August | 77.00 | 25.15 | 494.17 | 24.48 | 73.83 | 24.57 |
September | 100.67 | 25.01 | 373.67 | 24.70 | 61.83 | 24.86 |
October | 217.83 | 24.02 | 273.33 | 24.55 | 83.00 | 24.75 |
November | 286.33 | 23.28 | 188.67 | 23.91 | 69.50 | 24.06 |
December | 310.33 | 22.43 | 243.83 | 22.87 | 116.17 | 22.74 |
Annual Sum or Average | 2516.50 | 23.22 | 3127.50 | 23.84 | 774.67 | 23.89 |
Minimum of Months | 69.33 | 22.43 | 100.50 | 22.87 | 7.17 | 22.74 |
Maximum of Months | 345.17 | 25.19 | 494.17 | 24.70 | 130.83 | 24.86 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 449.83 | 21.11 | 198.17 | 20.94 | 193.00 | 20.83 |
February | 379.83 | 21.43 | 135.33 | 21.44 | 102.50 | 21.30 |
March | 408.67 | 22.13 | 82.17 | 22.36 | 31.33 | 22.35 |
April | 280.17 | 23.00 | 103.50 | 23.45 | 17.00 | 23.61 |
May | 188.83 | 23.19 | 186.83 | 23.86 | 16.67 | 24.00 |
June | 86.00 | 24.01 | 366.50 | 24.39 | 28.67 | 24.50 |
July | 141.17 | 24.71 | 493.17 | 24.48 | 141.17 | 24.52 |
August | 96.83 | 24.60 | 489.00 | 24.40 | 91.50 | 24.44 |
September | 113.50 | 23.72 | 331.67 | 24.25 | 36.50 | 24.36 |
October | 302.00 | 22.46 | 150.50 | 23.06 | 23.67 | 23.13 |
November | 411.00 | 21.67 | 94.33 | 21.68 | 65.00 | 21.55 |
December | 448.00 | 21.13 | 211.00 | 20.96 | 208.17 | 20.85 |
Annual Sum or Average | 3305.83 | 22.17 | 2842.17 | 22.84 | 955.17 | 22.76 |
Minimum of Months | 86.00 | 21.11 | 82.17 | 20.94 | 16.67 | 20.83 |
Maximum of Months | 449.83 | 24.71 | 493.17 | 24.48 | 208.17 | 24.52 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.22 | 399.33 | 20.08 | 399.33 | 20.03 |
February | 454.00 | 20.65 | 291.00 | 20.44 | 291.00 | 20.34 |
March | 513.00 | 21.72 | 161.67 | 21.40 | 161.67 | 21.20 |
April | 401.83 | 22.70 | 54.00 | 22.45 | 54.00 | 22.26 |
May | 243.67 | 23.11 | 94.17 | 23.43 | 8.83 | 23.37 |
June | 54.83 | 23.68 | 326.00 | 24.30 | 7.67 | 24.35 |
July | 120.17 | 25.09 | 485.00 | 24.59 | 120.17 | 24.67 |
August | 80.00 | 24.55 | 478.67 | 24.34 | 72.17 | 24.38 |
September | 140.33 | 23.33 | 259.00 | 23.93 | 21.33 | 23.97 |
October | 403.83 | 22.03 | 141.83 | 22.00 | 87.00 | 21.80 |
November | 489.00 | 20.88 | 275.33 | 20.59 | 275.33 | 20.45 |
December | 497.00 | 20.13 | 447.17 | 20.07 | 447.17 | 20.05 |
Annual Sum or Average | 3899.67 | 21.56 | 3413.17 | 21.86 | 1945.67 | 21.61 |
Minimum of Months | 54.83 | 20.13 | 54.00 | 20.07 | 7.67 | 20.03 |
Maximum of Months | 513.00 | 25.09 | 485.00 | 24.59 | 447.17 | 24.67 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 501.00 | 20.79 | 291.67 | 20.53 | 291.67 | 20.41 |
February | 430.67 | 21.19 | 171.50 | 20.88 | 170.00 | 20.70 |
March | 376.83 | 21.93 | 114.33 | 21.90 | 78.50 | 21.73 |
April | 193.67 | 22.80 | 147.50 | 23.45 | 20.83 | 23.40 |
May | 179.17 | 23.72 | 230.17 | 24.24 | 38.33 | 24.46 |
June | 78.33 | 24.83 | 397.00 | 24.54 | 44.17 | 24.70 |
July | 157.17 | 25.37 | 481.83 | 24.78 | 155.50 | 24.90 |
August | 115.67 | 25.03 | 486.00 | 24.53 | 105.17 | 24.64 |
September | 126.67 | 23.76 | 345.67 | 24.21 | 40.50 | 24.34 |
October | 278.50 | 22.27 | 171.50 | 22.77 | 47.17 | 22.65 |
November | 453.67 | 21.46 | 153.83 | 21.19 | 149.17 | 21.01 |
December | 495.67 | 20.58 | 306.50 | 20.34 | 306.50 | 20.23 |
Annual Sum or Average | 3387.00 | 21.98 | 3297.50 | 22.54 | 1447.50 | 22.38 |
Minimum of Months | 78.33 | 20.58 | 114.33 | 20.34 | 20.83 | 20.23 |
Maximum of Months | 501.00 | 25.37 | 486.00 | 24.78 | 306.50 | 24.90 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 346.50 | 21.61 | 271.67 | 21.88 | 171.83 | 21.65 |
February | 282.33 | 21.77 | 225.33 | 22.15 | 116.67 | 21.92 |
March | 326.83 | 22.22 | 178.67 | 22.42 | 89.00 | 22.25 |
April | 251.00 | 22.66 | 128.50 | 22.99 | 36.00 | 22.84 |
May | 236.00 | 23.12 | 135.50 | 23.60 | 19.83 | 23.63 |
June | 90.17 | 23.35 | 298.83 | 24.15 | 9.83 | 24.22 |
July | 121.67 | 25.07 | 473.00 | 24.58 | 119.83 | 24.66 |
August | 85.83 | 24.91 | 479.33 | 24.45 | 76.67 | 24.54 |
September | 128.67 | 24.37 | 352.33 | 24.50 | 59.67 | 24.67 |
October | 234.50 | 23.29 | 276.50 | 23.91 | 83.67 | 23.98 |
November | 293.83 | 22.37 | 205.00 | 22.85 | 86.50 | 22.74 |
December | 324.83 | 21.48 | 269.83 | 21.76 | 156.83 | 21.48 |
Annual Sum or Average | 2722.17 | 22.58 | 3294.50 | 23.23 | 1026.33 | 23.12 |
Minimum of Months | 85.83 | 21.48 | 128.50 | 21.76 | 9.83 | 21.48 |
Maximum of Months | 346.50 | 25.07 | 479.33 | 24.58 | 171.83 | 24.67 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 464.83 | 20.70 | 287.50 | 20.46 | 286.33 | 20.34 |
February | 388.00 | 21.05 | 202.17 | 20.95 | 174.67 | 20.78 |
March | 417.67 | 21.70 | 161.00 | 21.79 | 110.50 | 21.65 |
April | 295.50 | 22.59 | 128.67 | 22.99 | 41.83 | 23.02 |
May | 228.33 | 22.92 | 185.33 | 23.60 | 22.83 | 23.72 |
June | 115.83 | 23.63 | 350.50 | 24.26 | 35.50 | 24.37 |
July | 155.67 | 24.63 | 480.50 | 24.46 | 154.17 | 24.50 |
August | 119.67 | 24.33 | 477.50 | 24.34 | 103.33 | 24.37 |
September | 147.83 | 23.34 | 309.33 | 24.05 | 40.00 | 24.17 |
October | 328.67 | 22.10 | 175.67 | 22.58 | 59.50 | 22.53 |
November | 425.00 | 21.21 | 165.50 | 21.07 | 143.83 | 20.89 |
December | 458.50 | 20.68 | 301.67 | 20.46 | 301.67 | 20.37 |
Annual Sum or Average | 3545.50 | 21.85 | 3225.33 | 22.40 | 1474.17 | 22.24 |
Minimum of Months | 115.83 | 20.68 | 128.67 | 20.46 | 22.83 | 20.34 |
Maximum of Months | 464.83 | 24.63 | 480.50 | 24.46 | 301.67 | 24.50 |
Report: ComfortReportSimple55Monthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 3.33 | 27.00 | 502.00 | 27.00 | 3.33 | 27.00 |
February | 16.67 | 27.00 | 454.00 | 27.00 | 16.67 | 27.00 |
March | 31.00 | 27.00 | 514.00 | 27.00 | 31.00 | 27.00 |
April | 78.17 | 27.07 | 485.00 | 27.02 | 78.17 | 27.02 |
May | 13.50 | 27.00 | 508.00 | 27.00 | 13.50 | 27.00 |
June | 86.83 | 27.00 | 496.00 | 27.00 | 86.83 | 27.00 |
July | 224.50 | 27.00 | 497.00 | 27.00 | 224.50 | 27.00 |
August | 348.67 | 27.11 | 514.00 | 27.09 | 348.67 | 27.10 |
September | 52.00 | 27.00 | 485.00 | 27.00 | 52.00 | 27.00 |
October | 57.50 | 27.00 | 502.00 | 27.00 | 57.50 | 27.00 |
November | 36.50 | 27.00 | 489.00 | 27.00 | 36.50 | 27.00 |
December | 34.17 | 27.00 | 497.00 | 27.00 | 34.17 | 27.00 |
Annual Sum or Average | 982.83 | 27.05 | 5943.00 | 27.01 | 982.83 | 27.02 |
Minimum of Months | 3.33 | 27.00 | 454.00 | 27.00 | 3.33 | 27.00 |
Maximum of Months | 348.67 | 27.11 | 514.00 | 27.09 | 348.67 | 27.10 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 455.67 | 27.00 | 0.00 | 27.00 |
February | 6.00 | 27.00 | 438.50 | 27.00 | 6.00 | 27.00 |
March | 12.50 | 27.00 | 512.67 | 27.00 | 12.50 | 27.00 |
April | 17.00 | 27.23 | 485.00 | 27.02 | 17.00 | 27.02 |
May | 7.83 | 27.00 | 508.00 | 27.00 | 7.83 | 27.00 |
June | 30.83 | 27.00 | 496.00 | 27.00 | 30.83 | 27.00 |
July | 84.17 | 27.00 | 497.00 | 27.00 | 84.17 | 27.00 |
August | 113.33 | 27.19 | 514.00 | 27.07 | 113.33 | 27.09 |
September | 23.17 | 27.00 | 485.00 | 27.00 | 23.17 | 27.00 |
October | 25.17 | 27.00 | 502.00 | 27.00 | 25.17 | 27.00 |
November | 7.50 | 27.00 | 489.00 | 27.00 | 7.50 | 27.00 |
December | 1.50 | 27.00 | 459.33 | 27.00 | 1.50 | 27.00 |
Annual Sum or Average | 329.00 | 27.08 | 5842.17 | 27.01 | 329.00 | 27.01 |
Minimum of Months | 0.00 | 0.00 | 438.50 | 27.00 | 0.00 | 27.00 |
Maximum of Months | 113.33 | 27.23 | 514.00 | 27.07 | 113.33 | 27.09 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 73.50 | 25.43 | 310.67 | 26.70 | 0.00 | 26.70 |
February | 14.00 | 27.00 | 351.17 | 27.00 | 5.33 | 27.00 |
March | 13.67 | 27.00 | 476.33 | 27.00 | 13.67 | 27.00 |
April | 21.33 | 27.12 | 483.33 | 27.01 | 21.33 | 27.02 |
May | 13.50 | 27.00 | 503.00 | 27.00 | 13.50 | 27.00 |
June | 63.67 | 27.00 | 496.00 | 27.00 | 63.67 | 27.00 |
July | 128.17 | 27.00 | 497.00 | 27.00 | 128.17 | 27.00 |
August | 157.50 | 27.12 | 514.00 | 27.06 | 157.50 | 27.07 |
September | 42.33 | 27.00 | 485.00 | 27.00 | 42.33 | 27.00 |
October | 30.67 | 27.00 | 487.00 | 27.00 | 30.67 | 27.00 |
November | 4.33 | 27.00 | 433.17 | 27.00 | 4.33 | 27.00 |
December | 22.67 | 27.00 | 346.33 | 27.00 | 0.83 | 27.00 |
Annual Sum or Average | 585.33 | 26.84 | 5383.00 | 26.99 | 481.33 | 26.99 |
Minimum of Months | 4.33 | 25.43 | 310.67 | 26.70 | 0.00 | 26.70 |
Maximum of Months | 157.50 | 27.12 | 514.00 | 27.06 | 157.50 | 27.07 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 497.83 | 27.00 | 502.00 | 27.00 | 497.83 | 27.00 |
February | 454.00 | 27.00 | 454.00 | 27.00 | 454.00 | 27.00 |
March | 514.00 | 27.00 | 514.00 | 27.00 | 514.00 | 27.00 |
April | 485.00 | 27.03 | 485.00 | 27.03 | 485.00 | 27.03 |
May | 483.67 | 27.00 | 508.00 | 27.00 | 483.67 | 27.00 |
June | 496.00 | 27.00 | 496.00 | 27.00 | 496.00 | 27.00 |
July | 497.00 | 27.01 | 497.00 | 27.01 | 497.00 | 27.01 |
August | 514.00 | 28.94 | 514.00 | 28.94 | 514.00 | 28.94 |
September | 485.00 | 27.00 | 485.00 | 27.00 | 485.00 | 27.00 |
October | 502.00 | 27.00 | 502.00 | 27.00 | 502.00 | 27.00 |
November | 489.00 | 27.00 | 489.00 | 27.00 | 489.00 | 27.00 |
December | 497.00 | 27.00 | 497.00 | 27.00 | 497.00 | 27.00 |
Annual Sum or Average | 5914.50 | 27.17 | 5943.00 | 27.17 | 5914.50 | 27.17 |
Minimum of Months | 454.00 | 27.00 | 454.00 | 27.00 | 454.00 | 27.00 |
Maximum of Months | 514.00 | 28.94 | 514.00 | 28.94 | 514.00 | 28.94 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 27.00000 | 17.01447 | 0.73378 | 16.47465 |
February | 454.00000 | 27.00002 | 17.46638 | 0.79538 | 18.48339 |
March | 514.00000 | 27.00001 | 18.15794 | 0.85904 | 20.68749 |
April | 485.00000 | 27.01098 | 16.87157 | 0.91037 | 22.59649 |
May | 508.00000 | 27.00022 | 20.19328 | 0.18617 | 5.89182 |
June | 496.00000 | 27.00039 | 24.44656 | 0.29244 | 6.91145 |
July | 497.00000 | 27.00047 | 27.14210 | 0.36228 | 7.84267 |
August | 514.00000 | 27.07650 | 26.97780 | 0.43260 | 9.17217 |
September | 485.00000 | 27.00082 | 25.54707 | 0.24682 | 6.41460 |
October | 502.00000 | 27.00025 | 21.05040 | 0.87401 | 21.27251 |
November | 489.00000 | 27.00004 | 18.30971 | 0.85561 | 20.56845 |
December | 497.00000 | 26.99999 | 14.86210 | 0.83301 | 19.76740 |
Annual Sum or Average | 5943.00000 | 27.00770 | 20.70071 | 0.61340 | 14.63235 |
Minimum of Months | 454.00000 | 26.99999 | 14.86210 | 0.18617 | 5.89182 |
Maximum of Months | 514.00000 | 27.07650 | 27.14210 | 0.91037 | 22.59649 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 26.99987 | 16.99618 | 0.63498 | 13.66642 |
February | 454.00000 | 27.00002 | 17.44936 | 0.68190 | 15.01592 |
March | 514.00000 | 27.00001 | 18.13347 | 0.74219 | 16.79153 |
April | 485.00000 | 27.00866 | 16.84939 | 0.79641 | 18.55481 |
May | 508.00000 | 27.00017 | 20.20590 | 0.11433 | 5.52345 |
June | 496.00000 | 27.00040 | 24.45945 | 0.21194 | 6.13726 |
July | 497.00000 | 27.00052 | 27.16354 | 0.27011 | 6.66944 |
August | 514.00000 | 27.04218 | 27.02375 | 0.30196 | 7.14373 |
September | 485.00000 | 27.00070 | 25.64697 | 0.17894 | 5.87527 |
October | 502.00000 | 27.00024 | 21.05135 | 0.78709 | 18.29113 |
November | 489.00000 | 27.00004 | 18.29386 | 0.72414 | 16.23540 |
December | 497.00000 | 26.99999 | 14.83928 | 0.66296 | 14.46574 |
Annual Sum or Average | 5943.00000 | 27.00452 | 20.70688 | 0.50719 | 11.99807 |
Minimum of Months | 454.00000 | 26.99987 | 14.83928 | 0.11433 | 5.52345 |
Maximum of Months | 514.00000 | 27.04218 | 27.16354 | 0.79641 | 18.55481 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 26.74879 | 17.21560 | 0.51343 | 11.51879 |
February | 454.00000 | 27.00002 | 17.46245 | 0.62121 | 13.52261 |
March | 514.00000 | 27.00001 | 18.14808 | 0.69872 | 15.61702 |
April | 485.00000 | 27.00572 | 16.86366 | 0.77533 | 17.97876 |
May | 508.00000 | 27.00016 | 20.22538 | 0.10615 | 5.65421 |
June | 496.00000 | 27.00040 | 24.46843 | 0.22091 | 6.34212 |
July | 497.00000 | 27.00052 | 27.16551 | 0.28885 | 6.97263 |
August | 514.00000 | 27.03712 | 27.03050 | 0.31290 | 7.38055 |
September | 485.00000 | 27.00068 | 25.66906 | 0.17491 | 5.98141 |
October | 502.00000 | 27.00024 | 21.07018 | 0.75551 | 17.41031 |
November | 489.00000 | 27.00004 | 18.30610 | 0.66217 | 14.56743 |
December | 497.00000 | 26.99999 | 14.85040 | 0.58337 | 12.54097 |
Annual Sum or Average | 5943.00000 | 26.98263 | 20.73734 | 0.47462 | 11.26416 |
Minimum of Months | 454.00000 | 26.74879 | 14.85040 | 0.10615 | 5.65421 |
Maximum of Months | 514.00000 | 27.03712 | 27.16551 | 0.77533 | 17.97876 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 27.00051 | 28.91607 | 1.05820 | 28.64802 |
February | 454.00000 | 27.00042 | 24.57500 | 1.18019 | 34.30346 |
March | 514.00000 | 27.00026 | 19.64747 | 1.29067 | 39.80729 |
April | 485.00000 | 27.02826 | 16.41718 | 1.41307 | 46.22122 |
May | 508.00000 | 27.00076 | 25.07761 | 0.47873 | 9.88804 |
June | 496.00000 | 27.00449 | 29.59921 | 0.74673 | 16.78093 |
July | 497.00000 | 27.01257 | 32.58416 | 0.98073 | 25.33653 |
August | 514.00000 | 28.94339 | 30.10762 | 1.69720 | 59.75068 |
September | 485.00000 | 27.00225 | 32.36738 | 0.59255 | 12.43650 |
October | 502.00000 | 27.00160 | 25.10159 | 1.23544 | 37.03406 |
November | 489.00000 | 27.00038 | 20.41763 | 1.32391 | 41.51776 |
December | 497.00000 | 27.00007 | 17.03538 | 1.41136 | 46.12503 |
Annual Sum or Average | 5943.00000 | 27.17233 | 25.16815 | 1.11821 | 33.20428 |
Minimum of Months | 454.00000 | 27.00007 | 16.41718 | 0.47873 | 9.88804 |
Maximum of Months | 514.00000 | 28.94339 | 32.58416 | 1.69720 | 59.75068 |
Report: OccupantComfortDataSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.51504 | 14.16008 | 0.31076 | 7.47563 |
February | 454.00000 | 24.50117 | 15.27552 | 0.31735 | 7.54023 |
March | 514.00000 | 24.42583 | 15.23059 | 0.30951 | 7.32039 |
April | 485.00000 | 24.53827 | 13.65615 | 0.32771 | 7.74764 |
May | 508.00000 | 24.51212 | 21.18531 | -0.4707 | 10.73142 |
June | 496.00000 | 24.48808 | 31.89669 | -0.3909 | 9.14139 |
July | 497.00000 | 24.63595 | 45.75328 | -0.2428 | 7.47954 |
August | 514.00000 | 24.49725 | 45.38351 | -0.2743 | 7.54836 |
September | 485.00000 | 24.57898 | 37.44065 | -0.3135 | 8.38159 |
October | 502.00000 | 24.62598 | 22.58067 | 0.42270 | 9.52436 |
November | 489.00000 | 24.60733 | 15.75757 | 0.36444 | 8.40411 |
December | 497.00000 | 24.57938 | 12.11153 | 0.32236 | 7.73474 |
Annual Sum or Average | 5943.00000 | 24.54180 | 24.29139 | 0.05418 | 8.25833 |
Minimum of Months | 454.00000 | 24.42583 | 12.11153 | -0.4707 | 7.32039 |
Maximum of Months | 514.00000 | 24.63595 | 45.75328 | 0.42270 | 10.73142 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.19196 | 15.83677 | 0.24467 | 6.40471 |
February | 454.00000 | 24.26990 | 16.64455 | 0.27858 | 6.79066 |
March | 514.00000 | 24.27132 | 16.19119 | 0.29719 | 7.02249 |
April | 485.00000 | 24.31299 | 14.15636 | 0.30921 | 7.19508 |
May | 508.00000 | 24.27626 | 22.41116 | -0.5111 | 10.97046 |
June | 496.00000 | 24.24565 | 33.41216 | -0.4214 | 9.03714 |
July | 497.00000 | 24.27429 | 47.69734 | -0.3023 | 7.23854 |
August | 514.00000 | 24.21632 | 46.15372 | -0.3180 | 7.32639 |
September | 485.00000 | 24.34471 | 38.56229 | -0.3657 | 8.37940 |
October | 502.00000 | 24.35684 | 23.52847 | 0.37680 | 8.36082 |
November | 489.00000 | 24.33399 | 16.61475 | 0.31470 | 7.28464 |
December | 497.00000 | 24.36204 | 13.45090 | 0.28510 | 6.95584 |
Annual Sum or Average | 5943.00000 | 24.28764 | 25.47609 | 0.01297 | 7.75642 |
Minimum of Months | 454.00000 | 24.19196 | 13.45090 | -0.5111 | 6.40471 |
Maximum of Months | 514.00000 | 24.36204 | 47.69734 | 0.37680 | 10.97046 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.47219 | 17.41771 | 0.04441 | 5.60817 |
February | 454.00000 | 23.67660 | 18.14807 | 0.10638 | 5.65085 |
March | 514.00000 | 23.95812 | 17.25323 | 0.18685 | 5.96626 |
April | 485.00000 | 24.11317 | 14.91599 | 0.22269 | 6.18833 |
May | 508.00000 | 24.14017 | 22.88793 | -0.5871 | 12.62072 |
June | 496.00000 | 24.17684 | 33.53888 | -0.4816 | 10.13214 |
July | 497.00000 | 24.23061 | 47.57182 | -0.3600 | 7.95611 |
August | 514.00000 | 24.21510 | 46.47449 | -0.3704 | 8.10959 |
September | 485.00000 | 24.22992 | 38.98739 | -0.4348 | 9.32100 |
October | 502.00000 | 24.10369 | 24.29681 | 0.28701 | 7.09910 |
November | 489.00000 | 23.89466 | 18.11972 | 0.17162 | 5.91448 |
December | 497.00000 | 23.53508 | 15.45366 | 0.04875 | 5.54076 |
Annual Sum or Average | 5943.00000 | 23.98093 | 26.33782 | -0.0994 | 7.52794 |
Minimum of Months | 454.00000 | 23.47219 | 14.91599 | -0.5871 | 5.54076 |
Maximum of Months | 514.00000 | 24.23061 | 47.57182 | 0.28701 | 12.62072 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.98588 | 19.05288 | -0.3297 | 9.91788 |
February | 454.00000 | 22.54789 | 19.76454 | -0.1806 | 7.70687 |
March | 514.00000 | 23.29883 | 18.34981 | 0.01440 | 6.18244 |
April | 485.00000 | 23.81889 | 15.14204 | 0.14583 | 5.99166 |
May | 508.00000 | 24.03813 | 22.73005 | -0.6217 | 13.83474 |
June | 496.00000 | 24.16039 | 33.56337 | -0.4708 | 9.98565 |
July | 497.00000 | 24.28232 | 47.49340 | -0.3197 | 7.49672 |
August | 514.00000 | 24.24359 | 46.42212 | -0.3441 | 7.77620 |
September | 485.00000 | 24.18095 | 38.75160 | -0.4518 | 9.68175 |
October | 502.00000 | 23.65392 | 24.96582 | 0.16700 | 6.69732 |
November | 489.00000 | 22.86851 | 19.79011 | -0.0921 | 6.94684 |
December | 497.00000 | 22.00617 | 17.23095 | -0.3354 | 9.66483 |
Annual Sum or Average | 5943.00000 | 23.43053 | 27.01352 | -0.2358 | 8.50132 |
Minimum of Months | 454.00000 | 21.98588 | 15.14204 | -0.6217 | 5.99166 |
Maximum of Months | 514.00000 | 24.28232 | 47.49340 | 0.16700 | 13.83474 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.24207 | 17.31528 | -0.2554 | 7.36949 |
February | 454.00000 | 22.73458 | 17.94522 | -0.1273 | 6.49913 |
March | 514.00000 | 23.46666 | 16.73295 | 0.06184 | 5.82229 |
April | 485.00000 | 24.01233 | 13.97046 | 0.21121 | 6.32615 |
May | 508.00000 | 24.18751 | 22.01983 | -0.5456 | 12.30767 |
June | 496.00000 | 24.33839 | 32.49278 | -0.3429 | 8.26142 |
July | 497.00000 | 24.46970 | 46.37172 | -0.1818 | 6.81657 |
August | 514.00000 | 24.30875 | 45.20032 | -0.2540 | 7.08641 |
September | 485.00000 | 24.29372 | 37.93181 | -0.3920 | 9.15450 |
October | 502.00000 | 23.78984 | 23.77153 | 0.20221 | 6.89629 |
November | 489.00000 | 23.20210 | 17.60217 | -0.0091 | 5.72686 |
December | 497.00000 | 22.48406 | 14.87021 | -0.2108 | 6.74313 |
Annual Sum or Average | 5943.00000 | 23.63376 | 25.59754 | -0.1544 | 7.42803 |
Minimum of Months | 454.00000 | 22.24207 | 13.97046 | -0.5456 | 5.72686 |
Maximum of Months | 514.00000 | 24.46970 | 46.37172 | 0.21121 | 12.30767 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.36920 | 16.18769 | -0.1810 | 7.65475 |
February | 454.00000 | 22.76159 | 17.00671 | -0.0640 | 7.18206 |
March | 514.00000 | 23.39578 | 16.22019 | 0.12366 | 7.18466 |
April | 485.00000 | 24.02098 | 13.52047 | 0.32370 | 8.76854 |
May | 508.00000 | 24.22278 | 21.55193 | -0.3850 | 11.62176 |
June | 496.00000 | 24.30915 | 32.38828 | -0.2084 | 8.24795 |
July | 497.00000 | 24.45460 | 46.27211 | -0.0534 | 8.14102 |
August | 514.00000 | 24.23300 | 45.20775 | -0.1503 | 7.85020 |
September | 485.00000 | 24.25639 | 37.71832 | -0.2690 | 8.86911 |
October | 502.00000 | 23.79151 | 23.22268 | 0.28610 | 9.14582 |
November | 489.00000 | 23.06718 | 16.93552 | 0.02178 | 6.79684 |
December | 497.00000 | 22.33912 | 13.99257 | -0.1996 | 7.57191 |
Annual Sum or Average | 5943.00000 | 23.60777 | 25.10109 | -0.0635 | 8.26259 |
Minimum of Months | 454.00000 | 22.33912 | 13.52047 | -0.3850 | 6.79684 |
Maximum of Months | 514.00000 | 24.45460 | 46.27211 | 0.32370 | 11.62176 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.39582 | 15.13485 | 0.12301 | 9.93784 |
February | 454.00000 | 23.59553 | 15.93485 | 0.19487 | 9.30108 |
March | 514.00000 | 23.74215 | 15.78630 | 0.21967 | 7.97689 |
April | 485.00000 | 24.06938 | 13.57298 | 0.29333 | 7.96198 |
May | 508.00000 | 24.12858 | 21.95263 | -0.5292 | 12.83354 |
June | 496.00000 | 24.24974 | 32.63027 | -0.3717 | 8.95573 |
July | 497.00000 | 24.43339 | 46.43109 | -0.1683 | 7.05497 |
August | 514.00000 | 24.33104 | 44.97682 | -0.1688 | 7.00667 |
September | 485.00000 | 24.46101 | 37.17989 | -0.1886 | 8.39141 |
October | 502.00000 | 24.33805 | 22.36087 | 0.46922 | 12.51475 |
November | 489.00000 | 24.04748 | 15.71900 | 0.32399 | 10.25423 |
December | 497.00000 | 23.56337 | 12.84615 | 0.17520 | 9.74537 |
Annual Sum or Average | 5943.00000 | 24.03171 | 24.63210 | 0.02883 | 9.33071 |
Minimum of Months | 454.00000 | 23.39582 | 12.84615 | -0.5292 | 7.00667 |
Maximum of Months | 514.00000 | 24.46101 | 46.43109 | 0.46922 | 12.83354 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.65927 | 15.65699 | -0.0782 | 7.10366 |
February | 454.00000 | 23.39189 | 16.12533 | 0.13166 | 7.20595 |
March | 514.00000 | 24.05340 | 15.39312 | 0.32513 | 8.48111 |
April | 485.00000 | 24.48066 | 13.09674 | 0.48864 | 11.19030 |
May | 508.00000 | 24.28032 | 21.58765 | -0.3473 | 10.08423 |
June | 496.00000 | 24.44040 | 32.11987 | -0.1244 | 7.57794 |
July | 497.00000 | 24.56511 | 45.95456 | 0.05438 | 7.34629 |
August | 514.00000 | 24.47198 | 44.50170 | 0.05069 | 6.99099 |
September | 485.00000 | 24.44236 | 37.27145 | -0.1691 | 7.98758 |
October | 502.00000 | 24.17358 | 22.61650 | 0.42151 | 10.55656 |
November | 489.00000 | 23.94883 | 15.78192 | 0.27749 | 7.77134 |
December | 497.00000 | 23.72644 | 12.65732 | 0.17869 | 6.97013 |
Annual Sum or Average | 5943.00000 | 24.05661 | 24.48160 | 0.09988 | 8.27659 |
Minimum of Months | 454.00000 | 22.65927 | 12.65732 | -0.3473 | 6.97013 |
Maximum of Months | 514.00000 | 24.56511 | 45.95456 | 0.48864 | 11.19030 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.78719 | 18.62306 | -0.6335 | 14.85652 |
February | 454.00000 | 21.23895 | 19.65603 | -0.5039 | 11.86428 |
March | 514.00000 | 22.33345 | 18.48552 | -0.2242 | 7.74832 |
April | 485.00000 | 23.34720 | 15.05636 | 0.02844 | 6.24146 |
May | 508.00000 | 23.90474 | 22.62378 | -0.6640 | 15.79751 |
June | 496.00000 | 24.27202 | 32.45323 | -0.3959 | 9.17690 |
July | 497.00000 | 24.46320 | 46.08986 | -0.2188 | 7.03580 |
August | 514.00000 | 24.29204 | 45.30134 | -0.3057 | 7.64989 |
September | 485.00000 | 24.08171 | 38.49130 | -0.4898 | 11.09080 |
October | 502.00000 | 22.94172 | 25.14835 | -0.0143 | 7.20960 |
November | 489.00000 | 21.61560 | 19.48849 | -0.3985 | 10.03583 |
December | 497.00000 | 20.67514 | 16.66291 | -0.6744 | 15.69643 |
Annual Sum or Average | 5943.00000 | 22.84187 | 26.57948 | -0.3740 | 10.35953 |
Minimum of Months | 454.00000 | 20.67514 | 15.05636 | -0.6744 | 6.24146 |
Maximum of Months | 514.00000 | 24.46320 | 46.08986 | 0.02844 | 15.79751 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 427.00000 | 21.29223 | 16.73321 | -0.4795 | 11.88152 |
February | 385.00000 | 21.70838 | 17.71415 | -0.3446 | 10.18595 |
March | 433.00000 | 22.69879 | 16.75360 | -0.0654 | 7.95355 |
April | 410.00000 | 23.79816 | 13.64738 | 0.24628 | 8.76820 |
May | 430.00000 | 24.09245 | 21.79214 | -0.4469 | 14.40017 |
June | 418.00000 | 24.37223 | 31.62915 | -0.2119 | 9.28921 |
July | 422.00000 | 24.65807 | 44.89107 | -0.0123 | 9.10773 |
August | 433.00000 | 24.42441 | 44.22582 | -0.1195 | 8.44310 |
September | 410.00000 | 24.14116 | 37.52832 | -0.3373 | 10.78266 |
October | 427.00000 | 23.32492 | 23.38324 | 0.15227 | 9.09978 |
November | 417.00000 | 22.06887 | 17.73412 | -0.2370 | 8.60855 |
December | 422.00000 | 21.12903 | 14.97532 | -0.5277 | 12.83456 |
Annual Sum or Average | 5034.00000 | 23.15076 | 25.14623 | -0.1981 | 10.11533 |
Minimum of Months | 385.00000 | 21.12903 | 13.64738 | -0.5277 | 7.95355 |
Maximum of Months | 433.00000 | 24.65807 | 44.89107 | 0.24628 | 14.40017 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.15233 | 15.43585 | 0.06251 | 11.95804 |
February | 454.00000 | 23.29770 | 16.43612 | 0.12347 | 10.77104 |
March | 514.00000 | 23.35091 | 16.41998 | 0.12201 | 8.52677 |
April | 485.00000 | 23.73983 | 14.02715 | 0.20160 | 7.79830 |
May | 508.00000 | 23.91724 | 22.38078 | -0.6124 | 15.46682 |
June | 496.00000 | 24.16449 | 32.61553 | -0.4258 | 10.20726 |
July | 497.00000 | 24.44235 | 46.09740 | -0.1964 | 7.29984 |
August | 514.00000 | 24.35567 | 44.92908 | -0.1935 | 7.37309 |
September | 485.00000 | 24.41244 | 37.21265 | -0.2074 | 9.37216 |
October | 502.00000 | 24.23835 | 22.54915 | 0.44643 | 13.47982 |
November | 489.00000 | 23.76509 | 16.19565 | 0.25812 | 11.48242 |
December | 497.00000 | 23.18553 | 13.56470 | 0.07984 | 11.71653 |
Annual Sum or Average | 5943.00000 | 23.83814 | 24.90891 | -0.0306 | 10.45701 |
Minimum of Months | 454.00000 | 23.15233 | 13.56470 | -0.6124 | 7.29984 |
Maximum of Months | 514.00000 | 24.44235 | 46.09740 | 0.44643 | 15.46682 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.42164 | 16.93110 | -0.4252 | 11.62196 |
February | 454.00000 | 21.87454 | 17.91427 | -0.2775 | 9.90247 |
March | 514.00000 | 22.55199 | 17.23250 | -0.0842 | 8.16766 |
April | 485.00000 | 23.50031 | 14.23421 | 0.17875 | 8.35008 |
May | 508.00000 | 23.81258 | 22.42947 | -0.5465 | 15.41691 |
June | 496.00000 | 24.19048 | 32.51345 | -0.2824 | 9.97899 |
July | 497.00000 | 24.40446 | 46.19655 | -0.0991 | 7.59223 |
August | 514.00000 | 24.30527 | 45.09495 | -0.1467 | 7.56265 |
September | 485.00000 | 24.06744 | 38.14484 | -0.3409 | 10.75564 |
October | 502.00000 | 23.11777 | 24.08819 | 0.13001 | 8.98812 |
November | 489.00000 | 22.08073 | 17.90605 | -0.2135 | 8.72861 |
December | 497.00000 | 21.42040 | 14.95932 | -0.4367 | 11.64657 |
Annual Sum or Average | 5943.00000 | 23.07126 | 25.71702 | -0.2120 | 9.89483 |
Minimum of Months | 454.00000 | 21.42040 | 14.23421 | -0.5465 | 7.56265 |
Maximum of Months | 514.00000 | 24.40446 | 46.19655 | 0.17875 | 15.41691 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.22067 | 19.20011 | -0.8152 | 21.53967 |
February | 454.00000 | 20.65126 | 20.24787 | -0.6776 | 16.97088 |
March | 514.00000 | 21.72160 | 19.00097 | -0.3854 | 10.61361 |
April | 485.00000 | 22.94211 | 15.24737 | -0.0703 | 7.29538 |
May | 508.00000 | 23.68632 | 22.67836 | -0.7331 | 18.91211 |
June | 496.00000 | 24.19805 | 32.70529 | -0.4050 | 9.77731 |
July | 497.00000 | 24.44779 | 46.32738 | -0.2019 | 7.11320 |
August | 514.00000 | 24.25894 | 45.50132 | -0.3010 | 7.89760 |
September | 485.00000 | 23.90925 | 38.57103 | -0.5428 | 13.03734 |
October | 502.00000 | 22.42592 | 25.62313 | -0.1461 | 8.77454 |
November | 489.00000 | 20.87610 | 20.21573 | -0.6006 | 15.26792 |
December | 497.00000 | 20.13427 | 17.23148 | -0.8552 | 22.76666 |
Annual Sum or Average | 5943.00000 | 22.47043 | 26.95046 | -0.4766 | 13.30504 |
Minimum of Months | 454.00000 | 20.13427 | 15.24737 | -0.8552 | 7.11320 |
Maximum of Months | 514.00000 | 24.44779 | 46.32738 | -0.0703 | 22.76666 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.79635 | 17.85441 | -0.6276 | 15.92972 |
February | 454.00000 | 21.34365 | 18.73002 | -0.4524 | 12.75515 |
March | 514.00000 | 22.51935 | 17.35655 | -0.1191 | 8.69190 |
April | 485.00000 | 23.68811 | 13.74028 | 0.22926 | 8.75876 |
May | 508.00000 | 24.00768 | 21.59935 | -0.4526 | 14.47857 |
June | 496.00000 | 24.29039 | 32.29588 | -0.1932 | 9.01470 |
July | 497.00000 | 24.55967 | 45.83720 | 0.01194 | 8.72506 |
August | 514.00000 | 24.34746 | 44.98278 | -0.0923 | 8.15047 |
September | 485.00000 | 24.04328 | 37.74502 | -0.3361 | 10.92543 |
October | 502.00000 | 23.14148 | 23.95067 | 0.10735 | 9.20038 |
November | 489.00000 | 21.64595 | 18.63212 | -0.3601 | 10.61576 |
December | 497.00000 | 20.59415 | 16.07683 | -0.6850 | 17.65516 |
Annual Sum or Average | 5943.00000 | 22.92720 | 25.80784 | -0.2462 | 11.22976 |
Minimum of Months | 454.00000 | 20.59415 | 13.74028 | -0.6850 | 8.15047 |
Maximum of Months | 514.00000 | 24.55967 | 45.83720 | 0.22926 | 17.65516 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.47521 | 16.24531 | -0.1383 | 13.72645 |
February | 454.00000 | 22.73214 | 17.19436 | -0.0427 | 12.13941 |
March | 514.00000 | 22.92612 | 16.96473 | -0.0006 | 9.47578 |
April | 485.00000 | 23.43912 | 14.19406 | 0.12435 | 8.33255 |
May | 508.00000 | 23.71339 | 22.41387 | -0.6772 | 18.39707 |
June | 496.00000 | 24.06634 | 32.91632 | -0.4414 | 11.21261 |
July | 497.00000 | 24.41584 | 46.38526 | -0.1826 | 7.55729 |
August | 514.00000 | 24.30965 | 45.18478 | -0.1919 | 7.78210 |
September | 485.00000 | 24.25492 | 37.26191 | -0.2556 | 10.67514 |
October | 502.00000 | 23.84935 | 22.95040 | 0.34133 | 12.77923 |
November | 489.00000 | 23.17576 | 16.97142 | 0.08874 | 11.42988 |
December | 497.00000 | 22.45352 | 14.45052 | -0.1325 | 14.08124 |
Annual Sum or Average | 5943.00000 | 23.48922 | 25.34589 | -0.1273 | 11.46848 |
Minimum of Months | 454.00000 | 22.45352 | 14.19406 | -0.6772 | 7.55729 |
Maximum of Months | 514.00000 | 24.41584 | 46.38526 | 0.34133 | 18.39707 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.94175 | 17.61081 | -0.5788 | 16.27666 |
February | 454.00000 | 21.48855 | 18.47377 | -0.4015 | 12.82704 |
March | 514.00000 | 22.17288 | 17.67526 | -0.1937 | 9.70954 |
April | 485.00000 | 23.20827 | 14.34931 | 0.10544 | 8.91886 |
May | 508.00000 | 23.60524 | 22.44943 | -0.6106 | 18.28639 |
June | 496.00000 | 24.08238 | 32.83710 | -0.3005 | 11.09471 |
July | 497.00000 | 24.37060 | 46.50940 | -0.0889 | 8.06617 |
August | 514.00000 | 24.24861 | 45.37415 | -0.1488 | 8.09395 |
September | 485.00000 | 23.89883 | 38.21694 | -0.3909 | 12.58173 |
October | 502.00000 | 22.78487 | 24.44114 | 0.03917 | 9.66386 |
November | 489.00000 | 21.58920 | 18.58091 | -0.3573 | 11.43394 |
December | 497.00000 | 20.94096 | 15.63369 | -0.5912 | 16.39606 |
Annual Sum or Average | 5943.00000 | 22.78772 | 26.09152 | -0.2927 | 11.94107 |
Minimum of Months | 454.00000 | 20.94096 | 14.34931 | -0.6106 | 8.06617 |
Maximum of Months | 514.00000 | 24.37060 | 46.50940 | 0.10544 | 18.28639 |
Report: ChillerReportMonthly
For: COOLSYS1 CHILLER1
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportCHILLER ELECTRICITY ENERGY [J] | CHILLER ELECTRICITY RATE {Maximum} [W] | CHILLER ELECTRICITY RATE {TIMESTAMP} | CHILLER ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | CHILLER EVAPORATOR COOLING ENERGY [J] | CHILLER EVAPORATOR COOLING RATE [] | CHILLER CONDENSER HEAT TRANSFER ENERGY [J] | CHILLER COP [W/W] | CHILLER COP {Maximum} [W/W] | CHILLER COP {TIMESTAMP} | CHILLER PART LOAD RATIO [] | CHILLER PART LOAD RATIO [] | |
January | 0.351453E+10 | 53427.01 | 05-JAN-15:30 | 85.04 | 0.156410E+11 | 0.00 | 0.191555E+11 | 0.49 | 5.65 | 05-JAN-15:30 | 0.00 | 0.00 |
February | 0.724523E+10 | 134358.58 | 14-FEB-16:00 | 109.59 | 0.435607E+11 | 0.00 | 0.508059E+11 | 0.76 | 7.57 | 14-FEB-16:00 | 0.00 | 0.00 |
March | 0.221567E+11 | 134534.96 | 08-MAR-16:00 | 161.08 | 0.125244E+12 | 0.00 | 0.147401E+12 | 1.08 | 7.57 | 08-MAR-16:00 | 0.00 | 0.00 |
April | 0.576207E+11 | 160116.85 | 13-APR-13:50 | 291.03 | 0.375524E+12 | 0.00 | 0.433144E+12 | 2.28 | 7.57 | 14-APR-16:10 | 0.00 | 0.00 |
May | 0.934100E+11 | 160835.19 | 22-MAY-16:00 | 373.58 | 0.626416E+12 | 0.00 | 0.719826E+12 | 3.06 | 7.57 | 22-MAY-11:30 | 0.00 | 0.00 |
June | 0.142398E+12 | 161462.60 | 07-JUN-16:20 | 512.78 | 0.993326E+12 | 0.00 | 0.113572E+13 | 4.56 | 7.57 | 06-JUN-10:30 | 0.00 | 0.00 |
July | 0.167856E+12 | 162665.46 | 18-JUL-19:10 | 614.73 | 0.117503E+13 | 0.00 | 0.134289E+13 | 5.24 | 7.57 | 21-JUL-19:00 | 0.00 | 0.00 |
August | 0.164335E+12 | 164665.73 | 19-AUG-10:00 | 653.54 | 0.114707E+13 | 0.00 | 0.131141E+13 | 5.41 | 7.57 | 24-AUG-11:00 | 0.00 | 0.00 |
September | 0.118502E+12 | 163458.03 | 02-SEP-13:50 | 445.19 | 0.811295E+12 | 0.00 | 0.929797E+12 | 3.87 | 7.57 | 13-SEP-09:20 | 0.00 | 0.00 |
October | 0.638804E+11 | 158958.31 | 19-OCT-14:20 | 307.15 | 0.418583E+12 | 0.00 | 0.482463E+12 | 2.36 | 7.57 | 17-OCT-15:50 | 0.00 | 0.00 |
November | 0.629239E+10 | 70068.93 | 02-NOV-15:10 | 95.77 | 0.297191E+11 | 0.00 | 0.360115E+11 | 0.59 | 6.62 | 02-NOV-15:10 | 0.00 | 0.00 |
December | 0.403357E+09 | 6976.69 | 24-DEC-15:11 | 92.18 | 0.172682E+10 | 0.00 | 0.213017E+10 | 0.53 | 4.29 | 18-DEC-10:20 | 0.00 | 0.00 |
Annual Sum or Average | 0.847614E+12 | 3741.65 | 0.576314E+13 | 0.00 | 0.661076E+13 | 2.53 | 0.00 | 0.00 | ||||
Minimum of Months | 0.403357E+09 | 6976.69 | 85.04 | 0.172682E+10 | 0.00 | 0.213017E+10 | 0.49 | 4.29 | 0.00 | 0.00 | ||
Maximum of Months | 0.167856E+12 | 164665.73 | 653.54 | 0.117503E+13 | 0.00 | 0.134289E+13 | 5.41 | 7.57 | 0.00 | 0.00 |
Report: ChillerReportMonthly
For: COOLSYS1 CHILLER2
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportCHILLER ELECTRICITY ENERGY [J] | CHILLER ELECTRICITY RATE {Maximum} [W] | CHILLER ELECTRICITY RATE {TIMESTAMP} | CHILLER ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | CHILLER EVAPORATOR COOLING ENERGY [J] | CHILLER EVAPORATOR COOLING RATE [] | CHILLER CONDENSER HEAT TRANSFER ENERGY [J] | CHILLER COP [W/W] | CHILLER COP {Maximum} [W/W] | CHILLER COP {TIMESTAMP} | CHILLER PART LOAD RATIO [] | CHILLER PART LOAD RATIO [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 |
April | 0.631284E+10 | 96033.02 | 13-APR-15:20 | 19.33 | 0.453748E+11 | 0.00 | 0.516877E+11 | 0.19 | 7.30 | 13-APR-15:20 | 0.00 | 0.00 |
May | 0.135401E+11 | 107877.04 | 23-MAY-11:30 | 41.67 | 0.974639E+11 | 0.00 | 0.111004E+12 | 0.40 | 7.42 | 23-MAY-11:30 | 0.00 | 0.00 |
June | 0.531127E+11 | 122875.68 | 28-JUN-14:50 | 149.50 | 0.388085E+12 | 0.00 | 0.441198E+12 | 1.51 | 7.54 | 28-JUN-14:50 | 0.00 | 0.00 |
July | 0.697519E+11 | 131290.73 | 31-JUL-15:00 | 190.00 | 0.508869E+12 | 0.00 | 0.578621E+12 | 1.86 | 7.54 | 21-JUL-14:50 | 0.00 | 0.00 |
August | 0.669464E+11 | 126718.83 | 23-AUG-16:00 | 185.00 | 0.488834E+12 | 0.00 | 0.555781E+12 | 1.81 | 7.53 | 07-AUG-15:30 | 0.00 | 0.00 |
September | 0.337807E+11 | 143350.55 | 05-SEP-13:10 | 99.67 | 0.245050E+12 | 0.00 | 0.278831E+12 | 0.99 | 7.53 | 11-SEP-12:03 | 0.00 | 0.00 |
October | 0.106978E+11 | 133280.30 | 02-OCT-12:02 | 31.92 | 0.773157E+11 | 0.00 | 0.880135E+11 | 0.31 | 7.56 | 02-OCT-12:02 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.254143E+12 | 717.08 | 0.185099E+13 | 0.00 | 0.210513E+13 | 0.59 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.697519E+11 | 143350.55 | 190.00 | 0.508869E+12 | 0.00 | 0.578621E+12 | 1.86 | 7.56 | 0.00 | 0.00 |
Report: TowerReportMonthly
For: CENTRAL TOWER
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportCOOLING TOWER FAN ELECTRICITY ENERGY [J] | COOLING TOWER FAN ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | COOLING TOWER FAN ELECTRICITY RATE {Maximum} [W] | COOLING TOWER FAN ELECTRICITY RATE {TIMESTAMP} | COOLING TOWER HEAT TRANSFER RATE {Maximum} [W] | COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} | COOLING TOWER INLET TEMPERATURE [C] | COOLING TOWER OUTLET TEMPERATURE [C] | COOLING TOWER MASS FLOW RATE [kg/s] | |
January | 0.272250E+10 | 744.00 | 6942.24 | 05-JAN-16:00 | 56524.56 | 26-JAN-17:00 | 18.84 | 18.33 | 15.74 |
February | 0.814465E+10 | 672.00 | 49248.27 | 12-FEB-14:21 | 221669.29 | 14-FEB-16:00 | 19.51 | 18.39 | 15.74 |
March | 0.271279E+11 | 744.00 | 49248.27 | 06-MAR-15:00 | 398497.37 | 08-MAR-16:10 | 20.64 | 18.64 | 15.74 |
April | 0.684334E+11 | 720.00 | 49248.27 | 01-APR-09:50 | 638370.20 | 26-APR-17:10 | 25.71 | 20.89 | 15.74 |
May | 0.712082E+11 | 744.00 | 49248.27 | 02-MAY-12:10 | 266317.17 | 22-MAY-14:10 | 22.42 | 21.08 | 15.74 |
June | 0.105494E+12 | 720.00 | 49248.27 | 01-JUN-00:10 | 500677.06 | 30-JUN-14:00 | 31.03 | 26.57 | 15.74 |
July | 0.131875E+12 | 744.00 | 49248.27 | 01-JUL-00:05 | 717186.95 | 31-JUL-23:53 | 40.70 | 31.29 | 15.74 |
August | 0.131789E+12 | 744.00 | 49248.27 | 01-AUG-00:03 | 774041.60 | 20-AUG-18:01 | 42.98 | 31.20 | 15.74 |
September | 0.916538E+11 | 720.00 | 49248.27 | 01-SEP-00:03 | 281420.17 | 01-SEP-16:40 | 24.02 | 22.34 | 15.74 |
October | 0.522313E+11 | 744.00 | 49248.27 | 01-OCT-08:51 | 429683.24 | 01-OCT-16:11 | 21.77 | 19.87 | 15.74 |
November | 0.121122E+11 | 720.00 | 49248.27 | 02-NOV-14:40 | 267194.27 | 09-NOV-14:10 | 20.03 | 18.34 | 15.74 |
December | 0.811094E+10 | 744.00 | 18195.30 | 24-DEC-15:00 | 180222.15 | 24-DEC-15:00 | 20.40 | 18.33 | 15.74 |
Annual Sum or Average | 0.710903E+12 | 8760.00 | 25.73 | 22.14 | 15.74 | ||||
Minimum of Months | 0.272250E+10 | 672.00 | 6942.24 | 56524.56 | 18.84 | 18.33 | 15.74 | ||
Maximum of Months | 0.131875E+12 | 744.00 | 49248.27 | 774041.60 | 42.98 | 31.29 | 15.74 |
Report: TowerReportMonthly
For: TOWERWATERSYS COOLTOWER 1
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportCOOLING TOWER FAN ELECTRICITY ENERGY [J] | COOLING TOWER FAN ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | COOLING TOWER FAN ELECTRICITY RATE {Maximum} [W] | COOLING TOWER FAN ELECTRICITY RATE {TIMESTAMP} | COOLING TOWER HEAT TRANSFER RATE {Maximum} [W] | COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} | COOLING TOWER INLET TEMPERATURE [C] | COOLING TOWER OUTLET TEMPERATURE [C] | COOLING TOWER MASS FLOW RATE [kg/s] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 368114.15 | 05-JAN-15:30 | 20.97 | 20.93 | 2.31 |
February | 14565594.23 | 15.92 | 877.81 | 14-FEB-16:00 | 1160591.18 | 14-FEB-16:00 | 21.04 | 20.95 | 3.47 |
March | 50117753.19 | 88.14 | 1225.36 | 08-MAR-14:10 | 1160897.54 | 08-MAR-16:10 | 21.17 | 20.94 | 9.71 |
April | 0.244056E+09 | 190.19 | 1790.47 | 14-APR-16:10 | 1332094.52 | 13-APR-13:50 | 21.73 | 21.00 | 19.60 |
May | 0.755329E+09 | 315.32 | 17712.31 | 22-MAY-10:40 | 1370611.71 | 22-MAY-16:00 | 22.45 | 21.28 | 28.45 |
June | 0.420208E+10 | 442.45 | 17712.31 | 06-JUN-10:40 | 1358162.20 | 06-JUN-12:00 | 23.15 | 21.19 | 40.69 |
July | 0.168775E+11 | 511.35 | 17712.31 | 01-JUL-09:40 | 1349622.69 | 22-JUL-10:10 | 23.50 | 21.38 | 47.54 |
August | 0.129011E+11 | 499.02 | 17712.31 | 01-AUG-07:40 | 1346570.27 | 19-AUG-10:00 | 23.31 | 21.21 | 48.07 |
September | 0.357288E+10 | 393.18 | 17712.31 | 01-SEP-08:50 | 1380499.62 | 02-SEP-13:50 | 23.03 | 21.43 | 35.70 |
October | 0.863839E+09 | 219.70 | 17712.31 | 02-OCT-13:50 | 1366145.78 | 19-OCT-14:20 | 21.93 | 21.14 | 20.96 |
November | 6594035.38 | 21.83 | 266.13 | 02-NOV-15:20 | 546319.71 | 02-NOV-15:10 | 21.00 | 20.93 | 3.97 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 237720.58 | 14-DEC-06:13 | 20.85 | 20.84 | 0.19 |
Annual Sum or Average | 0.394881E+11 | 2697.10 | 22.02 | 21.10 | 21.83 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 237720.58 | 20.85 | 20.84 | 0.19 | ||
Maximum of Months | 0.168775E+11 | 511.35 | 17712.31 | 1380499.62 | 23.50 | 21.43 | 48.07 |
Report: TowerReportMonthly
For: TOWERWATERSYS COOLTOWER 2
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportCOOLING TOWER FAN ELECTRICITY ENERGY [J] | COOLING TOWER FAN ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | COOLING TOWER FAN ELECTRICITY RATE {Maximum} [W] | COOLING TOWER FAN ELECTRICITY RATE {TIMESTAMP} | COOLING TOWER HEAT TRANSFER RATE {Maximum} [W] | COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} | COOLING TOWER INLET TEMPERATURE [C] | COOLING TOWER OUTLET TEMPERATURE [C] | COOLING TOWER MASS FLOW RATE [kg/s] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 20.97 | 20.97 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 21.04 | 21.04 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 21.17 | 21.17 | 0.00 |
April | 38373196.55 | 17.33 | 1555.46 | 27-APR-13:50 | 1174404.03 | 26-APR-15:20 | 21.73 | 21.62 | 1.45 |
May | 97486297.63 | 35.17 | 2766.69 | 22-MAY-12:20 | 1245812.88 | 19-MAY-16:00 | 22.45 | 22.23 | 2.84 |
June | 0.206194E+10 | 139.17 | 17712.31 | 06-JUN-12:20 | 1252692.43 | 07-JUN-14:30 | 23.15 | 22.33 | 11.60 |
July | 0.964909E+10 | 174.33 | 17712.31 | 03-JUL-09:00 | 1246056.43 | 21-JUL-16:30 | 23.50 | 22.60 | 14.06 |
August | 0.730068E+10 | 162.92 | 17712.31 | 01-AUG-07:55 | 1216304.15 | 31-AUG-13:50 | 23.31 | 22.45 | 13.15 |
September | 0.163489E+10 | 87.00 | 17712.31 | 01-SEP-09:40 | 1251342.26 | 28-SEP-15:40 | 23.03 | 22.50 | 7.26 |
October | 0.302646E+09 | 27.67 | 17712.31 | 02-OCT-13:50 | 1251823.39 | 02-OCT-11:40 | 21.93 | 21.76 | 2.23 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 21.00 | 21.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 20.85 | 20.85 | 0.00 |
Annual Sum or Average | 0.210851E+11 | 643.58 | 22.02 | 21.71 | 4.41 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 20.85 | 20.85 | 0.00 | ||
Maximum of Months | 0.964909E+10 | 174.33 | 17712.31 | 1252692.43 | 23.50 | 22.60 | 14.06 |
Report: BoilerReportMonthly
For: HEATSYS1 BOILER
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportBOILER HEATING ENERGY [J] | BOILER GAS CONSUMPTION [] | BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] | BOILER HEATING RATE {Maximum} [W] | BOILER HEATING RATE {TIMESTAMP} | BOILER GAS CONSUMPTION RATE [] | BOILER INLET TEMPERATURE [C] | BOILER OUTLET TEMPERATURE [C] | BOILER MASS FLOW RATE [kg/s] | BOILER ANCILLARY ELECTRICITY RATE [W] | BOILER PART LOAD RATIO [] | BOILER PART LOAD RATIO {Maximum} [] | BOILER PART LOAD RATIO {TIMESTAMP} | |
January | 0.170329E+12 | 0.00 | 405.02 | 1285339.93 | 18-JAN-05:01 | 0.00 | 27.16 | 56.30 | 0.31 | 0.00 | 0.03 | 0.59 | 18-JAN-05:01 |
February | 0.977142E+11 | 0.00 | 291.67 | 1307570.70 | 27-FEB-06:01 | 0.00 | 26.07 | 49.53 | 0.19 | 0.00 | 0.02 | 0.60 | 27-FEB-06:01 |
March | 0.278640E+11 | 0.00 | 170.93 | 1253627.72 | 04-MAR-05:01 | 0.00 | 24.78 | 37.75 | 0.05 | 0.00 | 0.00 | 0.58 | 04-MAR-05:01 |
April | 0.347523E+10 | 0.00 | 46.07 | 776792.78 | 08-APR-05:03 | 0.00 | 23.88 | 27.56 | 0.01 | 0.00 | 0.00 | 0.36 | 08-APR-05:03 |
May | 0.460628E+09 | 0.00 | 14.50 | 134629.29 | 05-MAY-05:02 | 0.00 | 22.79 | 23.94 | 0.00 | 0.00 | 0.00 | 0.06 | 05-MAY-05:02 |
June | 26923843.72 | 0.00 | 2.79 | 12902.77 | 09-JUN-05:03 | 0.00 | 22.44 | 22.67 | 0.00 | 0.00 | 0.00 | 0.01 | 09-JUN-05:03 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 22.37 | 22.37 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUL-00:05 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 22.37 | 22.37 | 0.00 | 0.00 | 0.00 | 0.00 | 01-AUG-00:03 |
September | 1469255.38 | 0.00 | 1.71 | 620.42 | 09-SEP-05:50 | 0.00 | 22.35 | 22.49 | 0.00 | 0.00 | 0.00 | 0.00 | 09-SEP-05:50 |
October | 0.139135E+11 | 0.00 | 94.88 | 1087960.65 | 25-OCT-05:02 | 0.00 | 22.96 | 30.25 | 0.02 | 0.00 | 0.00 | 0.50 | 25-OCT-05:02 |
November | 0.395434E+11 | 0.00 | 242.17 | 1335031.59 | 27-NOV-05:01 | 0.00 | 24.41 | 43.23 | 0.07 | 0.00 | 0.01 | 0.61 | 27-NOV-05:01 |
December | 0.158459E+12 | 0.00 | 419.94 | 1309877.42 | 04-DEC-05:01 | 0.00 | 26.26 | 57.04 | 0.29 | 0.00 | 0.03 | 0.60 | 04-DEC-05:01 |
Annual Sum or Average | 0.511787E+12 | 0.00 | 1689.67 | 0.00 | 23.98 | 34.56 | 0.08 | 0.00 | 0.01 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.35 | 22.37 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.170329E+12 | 0.00 | 419.94 | 1335031.59 | 0.00 | 27.16 | 57.04 | 0.31 | 0.00 | 0.03 | 0.61 |
Report: BoilerReportMonthly
For: CENTRAL BOILER
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportBOILER HEATING ENERGY [J] | BOILER GAS CONSUMPTION [] | BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] | BOILER HEATING RATE {Maximum} [W] | BOILER HEATING RATE {TIMESTAMP} | BOILER GAS CONSUMPTION RATE [] | BOILER INLET TEMPERATURE [C] | BOILER OUTLET TEMPERATURE [C] | BOILER MASS FLOW RATE [kg/s] | BOILER ANCILLARY ELECTRICITY RATE [W] | BOILER PART LOAD RATIO [] | BOILER PART LOAD RATIO [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 18.84 | 18.84 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 19.51 | 19.51 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 20.64 | 20.64 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 25.71 | 25.71 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 22.42 | 22.42 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 31.03 | 31.03 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 40.70 | 40.70 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 42.98 | 42.98 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 24.02 | 24.02 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 21.77 | 21.77 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 20.03 | 20.03 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 20.40 | 20.40 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 25.73 | 25.73 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.84 | 18.84 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42.98 | 42.98 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: VAV_BOT WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.136696E+10 | 0.00 | 29.29 | 0.136696E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 29283.20 | 05-JAN-15:20 | 29283.20 | 05-JAN-15:20 | 0.00 | 0.00 | 0.00 |
February | 0.383700E+10 | 0.00 | 41.53 | 0.383700E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 83705.33 | 14-FEB-16:00 | 83705.33 | 14-FEB-16:00 | 0.00 | 0.00 | 0.00 |
March | 0.123135E+11 | 0.00 | 136.20 | 0.123135E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 90152.97 | 08-MAR-16:00 | 90152.97 | 08-MAR-16:00 | 0.00 | 0.00 | 0.00 |
April | 0.418582E+11 | 0.00 | 271.97 | 0.418582E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 126970.26 | 28-APR-14:50 | 126970.26 | 28-APR-14:50 | 0.00 | 0.00 | 0.00 |
May | 0.637057E+11 | 0.00 | 351.63 | 0.637057E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 129796.56 | 30-MAY-14:30 | 129796.56 | 30-MAY-14:30 | 0.00 | 0.00 | 0.00 |
June | 0.121827E+12 | 0.00 | 491.87 | 0.121822E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 164542.32 | 29-JUN-05:02 | 156281.91 | 29-JUN-05:02 | 0.00 | 0.00 | 0.00 |
July | 0.153901E+12 | 0.00 | 590.45 | 0.149875E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 169550.66 | 02-JUL-15:21 | 154062.25 | 31-JUL-15:00 | 0.00 | 0.00 | 0.00 |
August | 0.156025E+12 | 0.00 | 632.34 | 0.151838E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 171757.56 | 23-AUG-16:00 | 160476.68 | 07-AUG-15:10 | 0.00 | 0.00 | 0.00 |
September | 0.910556E+11 | 0.00 | 425.72 | 0.897070E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 183291.27 | 05-SEP-13:30 | 132158.13 | 11-SEP-15:40 | 0.00 | 0.00 | 0.00 |
October | 0.443653E+11 | 0.00 | 270.07 | 0.443432E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 128702.52 | 10-OCT-16:00 | 128702.52 | 10-OCT-16:00 | 0.00 | 0.00 | 0.00 |
November | 0.298001E+10 | 0.00 | 62.16 | 0.298001E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 44936.37 | 02-NOV-15:00 | 44936.37 | 02-NOV-15:00 | 0.00 | 0.00 | 0.00 |
December | 813330.00 | 0.00 | 0.94 | 813330.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5403.58 | 24-DEC-14:42 | 5403.58 | 24-DEC-14:42 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.693236E+12 | 0.00 | 3304.18 | 0.683647E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 813330.00 | 0.00 | 0.94 | 813330.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5403.58 | 5403.58 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.156025E+12 | 0.00 | 632.34 | 0.151838E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 183291.27 | 160476.68 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: VAV_MID WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.117631E+11 | 0.00 | 82.56 | 0.117631E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 249111.58 | 05-JAN-16:00 | 249111.58 | 05-JAN-16:00 | 0.00 | 0.00 | 0.00 |
February | 0.321817E+11 | 0.00 | 106.88 | 0.321817E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 702298.56 | 14-FEB-16:00 | 702298.56 | 14-FEB-16:00 | 0.00 | 0.00 | 0.00 |
March | 0.966714E+11 | 0.00 | 150.24 | 0.966714E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 728823.49 | 08-MAR-16:00 | 728823.49 | 08-MAR-16:00 | 0.00 | 0.00 | 0.00 |
April | 0.317722E+12 | 0.00 | 252.84 | 0.317722E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1085531.75 | 26-APR-15:10 | 1085531.75 | 26-APR-15:10 | 0.00 | 0.00 | 0.00 |
May | 0.557186E+12 | 0.00 | 349.01 | 0.557186E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1190232.39 | 19-MAY-15:10 | 1190232.39 | 19-MAY-15:10 | 0.00 | 0.00 | 0.00 |
June | 0.105889E+13 | 0.00 | 448.53 | 0.105876E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 1444032.39 | 28-JUN-14:50 | 1444032.39 | 28-JUN-14:50 | 0.00 | 0.00 | 0.00 |
July | 0.127246E+13 | 0.00 | 478.78 | 0.124480E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 1615866.11 | 02-JUL-15:21 | 1429250.01 | 21-JUL-14:50 | 0.00 | 0.00 | 0.00 |
August | 0.122201E+13 | 0.00 | 485.72 | 0.119413E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 1628213.79 | 13-AUG-15:31 | 1406506.14 | 07-AUG-15:30 | 0.00 | 0.00 | 0.00 |
September | 0.811758E+12 | 0.00 | 414.36 | 0.799554E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1612724.22 | 05-SEP-13:40 | 1218685.55 | 21-SEP-15:50 | 0.00 | 0.00 | 0.00 |
October | 0.377239E+12 | 0.00 | 282.01 | 0.377087E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1158028.47 | 06-OCT-15:30 | 1158028.47 | 06-OCT-15:30 | 0.00 | 0.00 | 0.00 |
November | 0.225664E+11 | 0.00 | 92.40 | 0.225664E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 369817.33 | 02-NOV-15:00 | 369817.33 | 02-NOV-15:00 | 0.00 | 0.00 | 0.00 |
December | 11532069.06 | 0.00 | 91.13 | 11532069.06 | 0.00 | 0.00 | 0.00 | 0.00 | 46379.48 | 24-DEC-14:42 | 46379.48 | 24-DEC-14:42 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.578046E+13 | 0.00 | 3234.47 | 0.571242E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 11532069.06 | 0.00 | 82.56 | 11532069.06 | 0.00 | 0.00 | 0.00 | 0.00 | 46379.48 | 46379.48 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.127246E+13 | 0.00 | 485.72 | 0.124480E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 1628213.79 | 1444032.39 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: VAV_TOP WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.923031E+09 | 0.00 | 27.88 | 0.923031E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 22426.91 | 05-JAN-15:30 | 22426.91 | 05-JAN-15:30 | 0.00 | 0.00 | 0.00 |
February | 0.289354E+10 | 0.00 | 39.30 | 0.289354E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 70596.37 | 14-FEB-16:00 | 70596.37 | 14-FEB-16:00 | 0.00 | 0.00 | 0.00 |
March | 0.851354E+10 | 0.00 | 122.58 | 0.851354E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 76199.70 | 08-MAR-16:00 | 76199.70 | 08-MAR-16:00 | 0.00 | 0.00 | 0.00 |
April | 0.329886E+11 | 0.00 | 235.37 | 0.329886E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 129863.84 | 26-APR-15:00 | 129863.84 | 26-APR-15:00 | 0.00 | 0.00 | 0.00 |
May | 0.604951E+11 | 0.00 | 342.09 | 0.604951E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 142526.02 | 19-MAY-15:10 | 142526.02 | 19-MAY-15:10 | 0.00 | 0.00 | 0.00 |
June | 0.118431E+12 | 0.00 | 444.25 | 0.118425E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 174900.03 | 28-JUN-14:50 | 174900.03 | 28-JUN-14:50 | 0.00 | 0.00 | 0.00 |
July | 0.143884E+12 | 0.00 | 479.07 | 0.140992E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 192936.43 | 16-JUL-14:41 | 173283.84 | 21-JUL-14:50 | 0.00 | 0.00 | 0.00 |
August | 0.136008E+12 | 0.00 | 484.87 | 0.133338E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 179265.43 | 13-AUG-16:21 | 167600.36 | 07-AUG-15:30 | 0.00 | 0.00 | 0.00 |
September | 0.869028E+11 | 0.00 | 408.35 | 0.859218E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 176848.29 | 05-SEP-13:30 | 143399.78 | 21-SEP-15:50 | 0.00 | 0.00 | 0.00 |
October | 0.379018E+11 | 0.00 | 252.72 | 0.379010E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 130648.79 | 06-OCT-15:20 | 130648.79 | 06-OCT-15:20 | 0.00 | 0.00 | 0.00 |
November | 0.176442E+10 | 0.00 | 55.20 | 0.176442E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 36545.19 | 02-NOV-15:00 | 36545.19 | 02-NOV-15:00 | 0.00 | 0.00 | 0.00 |
December | 637380.28 | 0.00 | 0.88 | 637380.28 | 0.00 | 0.00 | 0.00 | 0.00 | 3807.41 | 24-DEC-14:31 | 3807.41 | 24-DEC-14:31 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.630707E+12 | 0.00 | 2892.57 | 0.624156E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 637380.28 | 0.00 | 0.88 | 637380.28 | 0.00 | 0.00 | 0.00 | 0.00 | 3807.41 | 3807.41 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.143884E+12 | 0.00 | 484.87 | 0.140992E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 192936.43 | 174900.03 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: CAV_BAS COOLING COIL
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 982666.17 | 0.00 | 0.05 | 982666.17 | 0.00 | 0.00 | 0.00 | 0.00 | 8920.71 | 01-JAN-14:21 | 8920.71 | 01-JAN-14:21 | 0.00 | 0.00 | 0.00 |
February | 0.146251E+10 | 0.00 | 16.00 | 0.146251E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 47158.73 | 13-FEB-16:00 | 47158.73 | 13-FEB-16:00 | 0.00 | 0.00 | 0.00 |
March | 0.399036E+10 | 0.00 | 68.77 | 0.399036E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 50259.86 | 08-MAR-16:00 | 50259.86 | 08-MAR-16:00 | 0.00 | 0.00 | 0.00 |
April | 0.213478E+11 | 0.00 | 177.76 | 0.213478E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 69075.70 | 17-APR-15:00 | 69075.70 | 17-APR-15:00 | 0.00 | 0.00 | 0.00 |
May | 0.374603E+11 | 0.00 | 260.21 | 0.374529E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 99544.22 | 29-MAY-13:50 | 99544.22 | 29-MAY-13:50 | 0.00 | 0.00 | 0.00 |
June | 0.687513E+11 | 0.00 | 369.34 | 0.687263E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 115946.64 | 18-JUN-18:53 | 115946.64 | 18-JUN-18:53 | 0.00 | 0.00 | 0.00 |
July | 0.830827E+11 | 0.00 | 412.23 | 0.820854E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 156098.90 | 02-JUL-15:18 | 116452.72 | 04-JUL-19:29 | 0.00 | 0.00 | 0.00 |
August | 0.831867E+11 | 0.00 | 430.71 | 0.820969E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 130768.18 | 13-AUG-15:21 | 110130.96 | 27-AUG-13:34 | 0.00 | 0.00 | 0.00 |
September | 0.557166E+11 | 0.00 | 345.57 | 0.550594E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 110120.00 | 05-SEP-13:00 | 102947.52 | 03-SEP-12:44 | 0.00 | 0.00 | 0.00 |
October | 0.256299E+11 | 0.00 | 194.75 | 0.256139E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 114386.04 | 01-OCT-12:43 | 114386.04 | 01-OCT-12:43 | 0.00 | 0.00 | 0.00 |
November | 0.602501E+09 | 0.00 | 24.68 | 0.602501E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 31445.62 | 09-NOV-05:12 | 31445.62 | 09-NOV-05:12 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.381232E+12 | 0.00 | 2300.08 | 0.378439E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.831867E+11 | 0.00 | 430.71 | 0.820969E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 156098.90 | 116452.72 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: AIRLOOP DATACENTER BASEMENT COOLING COIL
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.116311E+11 | 0.601364E+10 | 744.00 | 0.100706E+11 | 0.156046E+10 | 0.00 | 0.03 | 06-JAN-12:50 | 0.02 | 20-JAN-13:10 | 5622.11 | 11-JAN-12:10 | 4923.90 | 01-JAN-17:25 | 741.28 | 11-JAN-11:00 | 2607.88 | 06-JAN-12:50 | 0.00 |
February | 0.157650E+11 | 0.735244E+10 | 672.00 | 0.142723E+11 | 0.149267E+10 | 0.00 | 0.35 | 14-FEB-16:00 | 0.02 | 17-FEB-09:00 | 107024.53 | 14-FEB-16:00 | 107024.53 | 14-FEB-16:00 | 1247.87 | 17-FEB-12:10 | 41245.59 | 14-FEB-16:00 | 0.00 |
March | 0.475737E+11 | 0.188911E+11 | 744.00 | 0.466400E+11 | 0.933701E+09 | 0.00 | 0.64 | 08-MAR-16:00 | 0.02 | 14-MAR-17:00 | 214051.94 | 08-MAR-16:00 | 214051.94 | 08-MAR-16:00 | 5267.47 | 16-MAR-12:10 | 80666.57 | 08-MAR-16:00 | 0.00 |
April | 0.277748E+12 | 0.102489E+12 | 720.00 | 0.275738E+12 | 0.201036E+10 | 0.00 | 1.00 | 01-APR-15:00 | 0.03 | 30-APR-23:47 | 355809.65 | 28-APR-14:30 | 355809.65 | 28-APR-14:30 | 34543.78 | 15-APR-01:20 | 142098.20 | 13-APR-17:00 | 0.00 |
May | 0.693285E+11 | 0.282533E+11 | 668.74 | 0.671811E+11 | 0.214739E+10 | 0.00 | 0.43 | 08-MAY-15:30 | 0.00 | 21-MAY-05:53 | 147462.82 | 22-MAY-12:10 | 139248.57 | 31-MAY-13:30 | 14793.19 | 22-MAY-10:20 | 57770.02 | 19-MAY-16:00 | 0.00 |
June | 0.326675E+12 | 0.126381E+12 | 666.83 | 0.304205E+12 | 0.224698E+11 | 0.00 | 0.73 | 30-JUN-14:00 | 0.01 | 01-JUN-03:10 | 308829.71 | 30-JUN-14:00 | 232501.19 | 28-JUN-16:00 | 87537.61 | 30-JUN-14:00 | 116889.83 | 28-JUN-16:00 | 0.00 |
July | 0.822170E+12 | 0.291050E+12 | 744.00 | 0.640425E+12 | 0.181744E+12 | 0.00 | 1.00 | 02-JUL-10:52 | 0.17 | 08-JUL-03:10 | 451661.67 | 31-JUL-24:00 | 340804.05 | 04-JUL-09:21 | 271355.33 | 01-JUL-00:52 | 158544.94 | 21-JUL-15:00 | 0.00 |
August | 0.104211E+13 | 0.350755E+12 | 744.00 | 0.780443E+12 | 0.261663E+12 | 0.00 | 1.00 | 01-AUG-00:03 | 0.07 | 31-AUG-24:00 | 461459.61 | 26-AUG-10:00 | 411210.14 | 21-AUG-15:10 | 284930.10 | 13-AUG-03:00 | 172890.46 | 20-AUG-16:00 | 0.00 |
September | 0.985963E+11 | 0.382836E+11 | 530.27 | 0.887073E+11 | 0.988903E+10 | 0.00 | 0.44 | 01-SEP-12:50 | 0.00 | 08-SEP-02:20 | 172267.07 | 01-SEP-12:40 | 142886.14 | 01-SEP-13:50 | 48769.53 | 05-SEP-14:00 | 60048.54 | 01-SEP-12:50 | 0.00 |
October | 0.827984E+11 | 0.309853E+11 | 713.07 | 0.750185E+11 | 0.777986E+10 | 0.00 | 0.65 | 05-OCT-17:00 | 0.00 | 07-OCT-06:10 | 250919.09 | 10-OCT-13:30 | 230762.61 | 06-OCT-14:10 | 67102.47 | 11-OCT-10:50 | 90985.45 | 01-OCT-16:00 | 0.00 |
November | 0.186277E+11 | 0.864099E+10 | 719.83 | 0.172692E+11 | 0.135852E+10 | 0.00 | 0.39 | 09-NOV-14:00 | 0.01 | 01-NOV-01:10 | 131072.78 | 09-NOV-14:00 | 125048.42 | 09-NOV-14:00 | 13758.53 | 02-NOV-16:00 | 43485.87 | 09-NOV-14:00 | 0.00 |
December | 0.161835E+11 | 0.844575E+10 | 744.00 | 0.157423E+11 | 0.441144E+09 | 0.00 | 0.20 | 24-DEC-15:00 | 0.03 | 01-DEC-03:40 | 53940.87 | 24-DEC-15:00 | 53940.87 | 24-DEC-15:00 | 1908.77 | 25-DEC-09:00 | 19709.97 | 24-DEC-15:00 | 0.00 |
Annual Sum or Average | 0.282920E+13 | 0.101754E+13 | 8410.75 | 0.233571E+13 | 0.493491E+12 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.116311E+11 | 0.601364E+10 | 530.27 | 0.100706E+11 | 0.441144E+09 | 0.00 | 0.03 | 0.00 | 5622.11 | 4923.90 | 741.28 | 2607.88 | 0.00 | ||||||
Maximum of Months | 0.104211E+13 | 0.350755E+12 | 744.00 | 0.780443E+12 | 0.261663E+12 | 0.00 | 1.00 | 0.17 | 461459.61 | 411210.14 | 284930.10 | 172890.46 | 0.00 |
Report: DXReportMonthly
For: AIRLOOP DATACENTER BOT COOLING COIL
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.485875E+10 | 0.134346E+10 | 744.00 | 0.485811E+10 | 632658.23 | 0.00 | 0.39 | 26-JAN-17:00 | 0.13 | 21-JAN-07:30 | 3221.48 | 26-JAN-17:00 | 3221.48 | 26-JAN-17:00 | 30.14 | 20-JAN-17:00 | 857.91 | 26-JAN-17:00 | 0.00 |
February | 0.939082E+10 | 0.243736E+10 | 672.00 | 0.938795E+10 | 2867770.10 | 0.00 | 0.61 | 14-FEB-17:00 | 0.36 | 04-FEB-07:45 | 5292.49 | 15-FEB-17:00 | 5292.49 | 15-FEB-17:00 | 82.05 | 17-FEB-11:10 | 1531.28 | 14-FEB-17:00 | 0.00 |
March | 0.160087E+11 | 0.399565E+10 | 744.00 | 0.160034E+11 | 5250749.65 | 0.00 | 0.86 | 12-MAR-17:35 | 0.58 | 04-MAR-07:03 | 7809.11 | 31-MAR-24:00 | 7809.11 | 31-MAR-24:00 | 116.94 | 20-MAR-14:50 | 2165.64 | 12-MAR-17:01 | 0.00 |
April | 0.207955E+11 | 0.544820E+10 | 720.00 | 0.207945E+11 | 1052474.56 | 0.00 | 1.00 | 01-APR-16:35 | 0.32 | 30-APR-24:00 | 9340.26 | 16-APR-18:22 | 9340.26 | 16-APR-18:22 | 76.63 | 15-APR-08:30 | 3114.75 | 13-APR-17:00 | 0.00 |
May | 0.643609E+10 | 0.190216E+10 | 744.00 | 0.639487E+10 | 41221239.85 | 0.00 | 0.48 | 31-MAY-23:30 | 0.20 | 05-MAY-06:03 | 4214.68 | 31-MAY-24:00 | 4214.68 | 31-MAY-24:00 | 269.39 | 24-MAY-15:30 | 1270.56 | 20-MAY-18:10 | 0.00 |
June | 0.115110E+11 | 0.376709E+10 | 720.00 | 0.114225E+11 | 88463555.47 | 0.00 | 0.73 | 18-JUN-18:35 | 0.42 | 09-JUN-06:10 | 6075.28 | 30-JUN-23:40 | 6059.67 | 30-JUN-23:23 | 334.17 | 08-JUN-12:00 | 2536.64 | 28-JUN-16:00 | 0.00 |
July | 0.170960E+11 | 0.601626E+10 | 744.00 | 0.168870E+11 | 0.209044E+09 | 0.00 | 0.93 | 04-JUL-18:35 | 0.65 | 08-JUL-06:05 | 7961.68 | 31-JUL-23:55 | 7961.68 | 31-JUL-23:55 | 472.55 | 07-JUL-17:00 | 3321.74 | 21-JUL-18:10 | 0.00 |
August | 0.221867E+11 | 0.748410E+10 | 744.00 | 0.219685E+11 | 0.218124E+09 | 0.00 | 1.00 | 01-AUG-13:10 | 0.32 | 31-AUG-24:00 | 8980.56 | 23-AUG-16:00 | 8910.02 | 30-AUG-18:20 | 419.98 | 23-AUG-14:00 | 3743.98 | 20-AUG-16:00 | 0.00 |
September | 0.654409E+10 | 0.195230E+10 | 720.00 | 0.639432E+10 | 0.149770E+09 | 0.00 | 0.47 | 30-SEP-23:30 | 0.22 | 09-SEP-06:15 | 4225.88 | 30-SEP-23:40 | 4202.02 | 30-SEP-24:00 | 325.00 | 05-SEP-16:40 | 1352.02 | 02-SEP-17:41 | 0.00 |
October | 0.113607E+11 | 0.302962E+10 | 744.00 | 0.113013E+11 | 59359098.43 | 0.00 | 0.67 | 31-OCT-24:00 | 0.38 | 26-OCT-06:55 | 6010.80 | 31-OCT-24:00 | 6010.80 | 31-OCT-24:00 | 318.52 | 02-OCT-17:00 | 1914.28 | 05-OCT-17:00 | 0.00 |
November | 0.154090E+11 | 0.378893E+10 | 720.00 | 0.153957E+11 | 13220243.13 | 0.00 | 0.80 | 19-NOV-16:33 | 0.59 | 27-NOV-07:10 | 7249.95 | 02-NOV-16:40 | 7242.29 | 05-NOV-16:38 | 188.38 | 09-NOV-16:00 | 1775.42 | 19-NOV-16:33 | 0.00 |
December | 0.205953E+11 | 0.500758E+10 | 744.00 | 0.205951E+11 | 136371.02 | 0.00 | 0.98 | 17-DEC-16:32 | 0.76 | 09-DEC-07:20 | 8988.25 | 31-DEC-16:33 | 8988.25 | 31-DEC-16:33 | 24.47 | 27-DEC-17:05 | 2180.11 | 17-DEC-16:32 | 0.00 |
Annual Sum or Average | 0.162192E+12 | 0.461727E+11 | 8760.00 | 0.161403E+12 | 0.789142E+09 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.485875E+10 | 0.134346E+10 | 672.00 | 0.485811E+10 | 136371.02 | 0.00 | 0.39 | 0.13 | 3221.48 | 3221.48 | 24.47 | 857.91 | 0.00 | ||||||
Maximum of Months | 0.221867E+11 | 0.748410E+10 | 744.00 | 0.219685E+11 | 0.218124E+09 | 0.00 | 1.00 | 0.76 | 9340.26 | 9340.26 | 472.55 | 3743.98 | 0.00 |
Report: DXReportMonthly
For: AIRLOOP DATACENTER MID COOLING COIL
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.303051E+11 | 0.866627E+10 | 743.17 | 0.302984E+11 | 6687409.65 | 0.00 | 0.37 | 26-JAN-17:00 | 0.00 | 17-JAN-07:10 | 29969.38 | 26-JAN-17:00 | 29969.38 | 26-JAN-17:00 | 300.52 | 20-JAN-17:00 | 8004.00 | 26-JAN-17:00 | 0.00 |
February | 0.767546E+11 | 0.202038E+11 | 672.00 | 0.767256E+11 | 28997741.01 | 0.00 | 0.59 | 14-FEB-17:00 | 0.24 | 06-FEB-07:10 | 50232.14 | 15-FEB-17:00 | 50232.14 | 15-FEB-17:00 | 794.94 | 17-FEB-11:10 | 14444.82 | 14-FEB-17:00 | 0.00 |
March | 0.142810E+12 | 0.359573E+11 | 744.00 | 0.142756E+12 | 53327528.91 | 0.00 | 0.83 | 12-MAR-17:21 | 0.51 | 04-MAR-07:03 | 72064.23 | 31-MAR-23:30 | 72064.23 | 31-MAR-23:30 | 1179.68 | 20-MAR-14:50 | 19962.20 | 08-MAR-17:00 | 0.00 |
April | 0.193340E+12 | 0.509502E+11 | 720.00 | 0.193329E+12 | 10809921.20 | 0.00 | 1.00 | 01-APR-16:50 | 0.28 | 30-APR-23:55 | 88961.71 | 16-APR-18:05 | 88961.71 | 16-APR-18:05 | 751.06 | 15-APR-08:30 | 29892.58 | 13-APR-17:00 | 0.00 |
May | 0.573641E+11 | 0.171174E+11 | 744.00 | 0.569592E+11 | 0.404946E+09 | 0.00 | 0.48 | 31-MAY-23:20 | 0.15 | 05-MAY-06:03 | 39940.29 | 31-MAY-24:00 | 39940.29 | 31-MAY-24:00 | 2646.65 | 24-MAY-15:30 | 12377.11 | 20-MAY-18:10 | 0.00 |
June | 0.108237E+12 | 0.355753E+11 | 720.00 | 0.107361E+12 | 0.875980E+09 | 0.00 | 0.73 | 18-JUN-18:35 | 0.38 | 09-JUN-06:10 | 58717.55 | 30-JUN-23:53 | 58483.82 | 30-JUN-23:57 | 3269.14 | 08-JUN-12:00 | 24296.85 | 28-JUN-16:00 | 0.00 |
July | 0.162924E+12 | 0.573780E+11 | 744.00 | 0.160842E+12 | 0.208176E+10 | 0.00 | 0.94 | 04-JUL-18:35 | 0.63 | 08-JUL-06:05 | 76597.46 | 31-JUL-23:55 | 76597.46 | 31-JUL-23:55 | 4631.97 | 07-JUL-17:00 | 32077.53 | 21-JUL-18:20 | 0.00 |
August | 0.210494E+12 | 0.711491E+11 | 744.00 | 0.208312E+12 | 0.218188E+10 | 0.00 | 1.00 | 01-AUG-13:30 | 0.29 | 31-AUG-24:00 | 85774.66 | 11-AUG-18:30 | 85425.92 | 30-AUG-18:20 | 4167.08 | 23-AUG-14:00 | 35924.58 | 01-AUG-16:00 | 0.00 |
September | 0.591929E+11 | 0.177984E+11 | 720.00 | 0.577233E+11 | 0.146958E+10 | 0.00 | 0.46 | 30-SEP-23:30 | 0.18 | 09-SEP-06:15 | 39718.60 | 30-SEP-23:30 | 39458.25 | 30-SEP-24:00 | 3204.11 | 05-SEP-16:40 | 12970.44 | 02-SEP-17:41 | 0.00 |
October | 0.101153E+12 | 0.272253E+11 | 744.00 | 0.100569E+12 | 0.583479E+09 | 0.00 | 0.64 | 31-OCT-24:00 | 0.31 | 26-OCT-06:10 | 55086.61 | 31-OCT-24:00 | 55086.61 | 31-OCT-24:00 | 3127.82 | 02-OCT-17:00 | 18402.50 | 05-OCT-17:00 | 0.00 |
November | 0.134370E+12 | 0.333981E+11 | 720.00 | 0.134239E+12 | 0.130570E+09 | 0.00 | 0.75 | 03-NOV-16:40 | 0.48 | 27-NOV-07:10 | 68691.26 | 02-NOV-16:40 | 67283.08 | 02-NOV-16:50 | 1811.90 | 09-NOV-16:00 | 16041.86 | 02-NOV-16:40 | 0.00 |
December | 0.178446E+12 | 0.439735E+11 | 744.00 | 0.178444E+12 | 1577154.28 | 0.00 | 0.91 | 15-DEC-16:40 | 0.67 | 27-DEC-07:10 | 82445.35 | 29-DEC-16:50 | 82445.35 | 29-DEC-16:50 | 245.51 | 27-DEC-17:05 | 19396.67 | 15-DEC-16:40 | 0.00 |
Annual Sum or Average | 0.145539E+13 | 0.419393E+12 | 8759.17 | 0.144756E+13 | 0.782960E+10 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.303051E+11 | 0.866627E+10 | 672.00 | 0.302984E+11 | 1577154.28 | 0.00 | 0.37 | 0.00 | 29969.38 | 29969.38 | 245.51 | 8004.00 | 0.00 | ||||||
Maximum of Months | 0.210494E+12 | 0.711491E+11 | 744.00 | 0.208312E+12 | 0.218188E+10 | 0.00 | 1.00 | 0.67 | 88961.71 | 88961.71 | 4631.97 | 35924.58 | 0.00 |
Report: DXReportMonthly
For: AIRLOOP DATACENTER TOP COOLING COIL
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.158525E+10 | 0.463323E+09 | 518.39 | 0.158469E+10 | 566084.08 | 0.00 | 0.36 | 26-JAN-17:00 | 0.00 | 01-JAN-00:10 | 2935.71 | 26-JAN-17:00 | 2935.71 | 26-JAN-17:00 | 28.74 | 01-JAN-16:22 | 786.89 | 26-JAN-17:00 | 0.00 |
February | 0.638231E+10 | 0.170334E+10 | 672.00 | 0.637950E+10 | 2809955.05 | 0.00 | 0.59 | 14-FEB-17:00 | 0.05 | 06-FEB-04:13 | 5068.77 | 15-FEB-17:00 | 5068.77 | 15-FEB-17:00 | 78.12 | 17-FEB-11:20 | 1460.44 | 14-FEB-17:00 | 0.00 |
March | 0.133499E+11 | 0.339223E+10 | 744.00 | 0.133447E+11 | 5216511.84 | 0.00 | 0.80 | 12-MAR-17:21 | 0.41 | 04-MAR-07:03 | 6885.15 | 24-MAR-17:40 | 6885.15 | 24-MAR-17:40 | 114.08 | 20-MAR-14:50 | 2024.00 | 08-MAR-17:00 | 0.00 |
April | 0.189061E+11 | 0.501965E+10 | 720.00 | 0.189051E+11 | 1043857.30 | 0.00 | 1.00 | 01-APR-17:00 | 0.27 | 30-APR-23:55 | 8886.94 | 16-APR-17:53 | 8886.94 | 16-APR-17:53 | 73.51 | 15-APR-08:30 | 3048.92 | 13-APR-17:00 | 0.00 |
May | 0.554330E+10 | 0.166992E+10 | 744.00 | 0.550304E+10 | 40264099.38 | 0.00 | 0.47 | 31-MAY-23:20 | 0.08 | 05-MAY-06:03 | 3941.57 | 31-MAY-23:40 | 3941.57 | 31-MAY-23:40 | 263.00 | 24-MAY-15:30 | 1295.56 | 20-MAY-18:10 | 0.00 |
June | 0.108347E+11 | 0.358068E+10 | 720.00 | 0.107473E+11 | 87432616.07 | 0.00 | 0.75 | 18-JUN-18:35 | 0.32 | 09-JUN-06:10 | 5875.23 | 30-JUN-23:53 | 5851.62 | 30-JUN-23:57 | 328.52 | 08-JUN-12:00 | 2504.81 | 28-JUN-16:00 | 0.00 |
July | 0.164280E+11 | 0.580188E+10 | 744.00 | 0.162200E+11 | 0.208021E+09 | 0.00 | 0.96 | 04-JUL-18:21 | 0.60 | 08-JUL-06:05 | 7845.15 | 04-JUL-18:40 | 7845.15 | 04-JUL-18:40 | 464.53 | 07-JUL-17:00 | 3333.10 | 04-JUL-18:21 | 0.00 |
August | 0.211386E+11 | 0.716871E+10 | 744.00 | 0.209206E+11 | 0.218053E+09 | 0.00 | 1.00 | 01-AUG-13:50 | 0.28 | 31-AUG-24:00 | 8709.13 | 11-AUG-18:20 | 8688.31 | 30-AUG-18:10 | 417.32 | 23-AUG-14:00 | 3665.29 | 20-AUG-16:00 | 0.00 |
September | 0.580850E+10 | 0.176103E+10 | 720.00 | 0.566184E+10 | 0.146669E+09 | 0.00 | 0.45 | 30-SEP-23:20 | 0.14 | 09-SEP-06:45 | 3937.61 | 30-SEP-23:20 | 3904.55 | 30-SEP-23:40 | 321.85 | 05-SEP-16:40 | 1353.62 | 02-SEP-17:41 | 0.00 |
October | 0.946597E+10 | 0.257429E+10 | 744.00 | 0.940781E+10 | 58165468.67 | 0.00 | 0.64 | 04-OCT-17:00 | 0.20 | 26-OCT-06:10 | 5341.06 | 04-OCT-17:00 | 5328.57 | 04-OCT-17:00 | 313.58 | 02-OCT-17:00 | 1870.73 | 05-OCT-17:00 | 0.00 |
November | 0.121242E+11 | 0.304923E+10 | 720.00 | 0.121113E+11 | 12930599.38 | 0.00 | 0.74 | 03-NOV-16:40 | 0.33 | 27-NOV-04:25 | 6877.56 | 02-NOV-16:40 | 6735.21 | 02-NOV-16:40 | 180.31 | 09-NOV-16:10 | 1610.07 | 02-NOV-16:30 | 0.00 |
December | 0.160335E+11 | 0.400744E+10 | 744.00 | 0.160333E+11 | 145739.05 | 0.00 | 0.88 | 13-DEC-16:40 | 0.49 | 26-DEC-04:12 | 8198.68 | 29-DEC-16:50 | 8198.68 | 29-DEC-16:50 | 24.30 | 27-DEC-17:05 | 1920.39 | 13-DEC-16:40 | 0.00 |
Annual Sum or Average | 0.137600E+12 | 0.401917E+11 | 8534.39 | 0.136819E+12 | 0.781318E+09 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.158525E+10 | 0.463323E+09 | 518.39 | 0.158469E+10 | 145739.05 | 0.00 | 0.36 | 0.00 | 2935.71 | 2935.71 | 24.30 | 786.89 | 0.00 | ||||||
Maximum of Months | 0.211386E+11 | 0.716871E+10 | 744.00 | 0.209206E+11 | 0.218053E+09 | 0.00 | 1.00 | 0.60 | 8886.94 | 8886.94 | 464.53 | 3665.29 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 184.38 | 0.00 | 184.38 | 26.15 | 734.10 | 0.00 | 0.00 | 0.00 |
February | 230.44 | 0.00 | 230.44 | 65.40 | 664.20 | 0.00 | 0.00 | 0.00 |
March | 290.68 | 0.00 | 290.68 | 159.20 | 522.08 | 0.00 | 0.00 | 0.00 |
April | 368.78 | 3.16 | 365.62 | 272.86 | 346.80 | 0.00 | 0.00 | 0.00 |
May | 400.86 | 25.85 | 375.02 | 391.18 | 244.60 | 0.00 | 0.00 | 0.00 |
June | 455.49 | 74.54 | 380.95 | 613.25 | 160.91 | 0.00 | 0.00 | 0.00 |
July | 418.07 | 34.80 | 383.27 | 611.02 | 107.55 | 0.00 | 0.00 | 0.00 |
August | 387.83 | 8.68 | 379.15 | 515.46 | 122.78 | 0.00 | 0.00 | 0.00 |
September | 310.14 | 0.08 | 310.06 | 348.77 | 222.34 | 0.00 | 0.00 | 0.00 |
October | 231.43 | 0.00 | 231.43 | 151.06 | 407.12 | 0.00 | 0.00 | 0.00 |
November | 196.54 | 0.00 | 196.54 | 42.50 | 598.12 | 0.00 | 0.00 | 0.00 |
December | 156.94 | 0.00 | 156.94 | 5.25 | 792.74 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 302.89 | 12.28 | 290.61 | 267.92 | 409.05 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 156.94 | 0.00 | 156.94 | 5.25 | 107.55 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 455.49 | 74.54 | 383.27 | 613.25 | 792.74 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 184.38 | 0.00 | 184.38 | 26.15 | 734.10 | 0.00 | 0.00 | 0.00 |
February | 230.44 | 0.00 | 230.44 | 65.40 | 664.20 | 0.00 | 0.00 | 0.00 |
March | 290.68 | 0.00 | 290.68 | 159.20 | 522.08 | 0.00 | 0.00 | 0.00 |
April | 368.78 | 3.16 | 365.62 | 272.86 | 346.80 | 0.00 | 0.00 | 0.00 |
May | 400.86 | 25.85 | 375.02 | 391.18 | 244.60 | 0.00 | 0.00 | 0.00 |
June | 455.49 | 74.54 | 380.95 | 613.25 | 160.91 | 0.00 | 0.00 | 0.00 |
July | 418.07 | 34.80 | 383.27 | 611.02 | 107.55 | 0.00 | 0.00 | 0.00 |
August | 387.83 | 8.68 | 379.15 | 515.46 | 122.78 | 0.00 | 0.00 | 0.00 |
September | 310.14 | 0.08 | 310.06 | 348.77 | 222.34 | 0.00 | 0.00 | 0.00 |
October | 231.43 | 0.00 | 231.43 | 151.06 | 407.12 | 0.00 | 0.00 | 0.00 |
November | 196.54 | 0.00 | 196.54 | 42.50 | 598.12 | 0.00 | 0.00 | 0.00 |
December | 156.94 | 0.00 | 156.94 | 5.25 | 792.74 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 302.89 | 12.28 | 290.61 | 267.92 | 409.05 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 156.94 | 0.00 | 156.94 | 5.25 | 107.55 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 455.49 | 74.54 | 383.27 | 613.25 | 792.74 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 184.38 | 0.00 | 184.38 | 26.15 | 734.10 | 0.00 | 0.00 | 0.00 |
February | 230.44 | 0.00 | 230.44 | 65.40 | 664.20 | 0.00 | 0.00 | 0.00 |
March | 290.68 | 0.00 | 290.68 | 159.20 | 522.08 | 0.00 | 0.00 | 0.00 |
April | 368.78 | 3.16 | 365.62 | 272.86 | 346.80 | 0.00 | 0.00 | 0.00 |
May | 400.86 | 25.85 | 375.02 | 391.18 | 244.60 | 0.00 | 0.00 | 0.00 |
June | 455.49 | 74.54 | 380.95 | 613.25 | 160.91 | 0.00 | 0.00 | 0.00 |
July | 418.07 | 34.80 | 383.27 | 611.02 | 107.55 | 0.00 | 0.00 | 0.00 |
August | 387.83 | 8.68 | 379.15 | 515.46 | 122.78 | 0.00 | 0.00 | 0.00 |
September | 310.14 | 0.08 | 310.06 | 348.77 | 222.34 | 0.00 | 0.00 | 0.00 |
October | 231.43 | 0.00 | 231.43 | 151.06 | 407.12 | 0.00 | 0.00 | 0.00 |
November | 196.54 | 0.00 | 196.54 | 42.50 | 598.12 | 0.00 | 0.00 | 0.00 |
December | 156.94 | 0.00 | 156.94 | 5.25 | 792.74 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 302.89 | 12.28 | 290.61 | 267.92 | 409.05 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 156.94 | 0.00 | 156.94 | 5.25 | 107.55 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 455.49 | 74.54 | 383.27 | 613.25 | 792.74 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 184.38 | 0.00 | 184.38 | 26.15 | 734.10 | 0.00 | 0.00 | 0.00 |
February | 230.44 | 0.00 | 230.44 | 65.40 | 664.20 | 0.00 | 0.00 | 0.00 |
March | 290.68 | 0.00 | 290.68 | 159.20 | 522.08 | 0.00 | 0.00 | 0.00 |
April | 368.78 | 3.16 | 365.62 | 272.86 | 346.80 | 0.00 | 0.00 | 0.00 |
May | 400.86 | 25.85 | 375.02 | 391.18 | 244.60 | 0.00 | 0.00 | 0.00 |
June | 455.49 | 74.54 | 380.95 | 613.25 | 160.91 | 0.00 | 0.00 | 0.00 |
July | 418.07 | 34.80 | 383.27 | 611.02 | 107.55 | 0.00 | 0.00 | 0.00 |
August | 387.83 | 8.68 | 379.15 | 515.46 | 122.78 | 0.00 | 0.00 | 0.00 |
September | 310.14 | 0.08 | 310.06 | 348.77 | 222.34 | 0.00 | 0.00 | 0.00 |
October | 231.43 | 0.00 | 231.43 | 151.06 | 407.12 | 0.00 | 0.00 | 0.00 |
November | 196.54 | 0.00 | 196.54 | 42.50 | 598.12 | 0.00 | 0.00 | 0.00 |
December | 156.94 | 0.00 | 156.94 | 5.25 | 792.74 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 302.89 | 12.28 | 290.61 | 267.92 | 409.05 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 156.94 | 0.00 | 156.94 | 5.25 | 107.55 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 455.49 | 74.54 | 383.27 | 613.25 | 792.74 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 184.37 | 0.00 | 184.37 | 26.15 | 734.07 | 0.00 | 0.00 | 0.00 |
February | 230.43 | 0.00 | 230.43 | 65.40 | 664.17 | 0.00 | 0.00 | 0.00 |
March | 290.66 | 0.00 | 290.66 | 159.19 | 522.06 | 0.00 | 0.00 | 0.00 |
April | 368.76 | 3.16 | 365.61 | 272.85 | 346.79 | 0.00 | 0.00 | 0.00 |
May | 400.85 | 25.84 | 375.00 | 391.17 | 244.59 | 0.00 | 0.00 | 0.00 |
June | 455.47 | 74.54 | 380.93 | 613.22 | 160.90 | 0.00 | 0.00 | 0.00 |
July | 418.05 | 34.79 | 383.26 | 611.00 | 107.55 | 0.00 | 0.00 | 0.00 |
August | 387.81 | 8.68 | 379.13 | 515.44 | 122.78 | 0.00 | 0.00 | 0.00 |
September | 310.13 | 0.08 | 310.05 | 348.75 | 222.34 | 0.00 | 0.00 | 0.00 |
October | 231.42 | 0.00 | 231.42 | 151.06 | 407.11 | 0.00 | 0.00 | 0.00 |
November | 196.53 | 0.00 | 196.53 | 42.50 | 598.09 | 0.00 | 0.00 | 0.00 |
December | 156.93 | 0.00 | 156.93 | 5.25 | 792.71 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 302.88 | 12.28 | 290.60 | 267.91 | 409.03 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 156.93 | 0.00 | 156.93 | 5.25 | 107.55 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 455.47 | 74.54 | 383.26 | 613.22 | 792.71 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 567.36 | 317.21 | 250.15 | 450.24 | 735.38 | 0.00 | 0.00 | 0.00 |
February | 689.33 | 371.62 | 317.71 | 608.09 | 668.54 | 0.00 | 0.00 | 0.00 |
March | 909.32 | 516.93 | 392.39 | 924.23 | 525.51 | 0.00 | 0.00 | 0.00 |
April | 1242.32 | 707.75 | 534.58 | 1405.58 | 359.48 | 0.00 | 0.00 | 0.00 |
May | 1185.44 | 675.57 | 509.87 | 1424.78 | 273.22 | 0.00 | 0.00 | 0.00 |
June | 1277.99 | 787.31 | 490.69 | 1699.97 | 171.99 | 0.00 | 0.00 | 0.00 |
July | 1182.55 | 676.23 | 506.32 | 1644.79 | 110.32 | 0.00 | 0.00 | 0.00 |
August | 1170.21 | 645.16 | 525.05 | 1577.76 | 122.95 | 0.00 | 0.00 | 0.00 |
September | 974.01 | 544.97 | 429.04 | 1234.61 | 233.43 | 0.00 | 0.00 | 0.00 |
October | 847.09 | 537.44 | 309.64 | 934.70 | 410.40 | 0.00 | 0.00 | 0.00 |
November | 662.04 | 389.21 | 272.83 | 603.42 | 599.51 | 0.00 | 0.00 | 0.00 |
December | 536.44 | 326.47 | 209.97 | 432.48 | 783.69 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 937.93 | 541.99 | 395.93 | 1080.53 | 414.95 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 536.44 | 317.21 | 209.97 | 432.48 | 110.32 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1277.99 | 787.31 | 534.58 | 1699.97 | 783.69 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 567.36 | 317.21 | 250.15 | 450.24 | 735.38 | 0.00 | 0.00 | 0.00 |
February | 689.33 | 371.62 | 317.71 | 608.09 | 668.54 | 0.00 | 0.00 | 0.00 |
March | 909.32 | 516.93 | 392.39 | 924.23 | 525.51 | 0.00 | 0.00 | 0.00 |
April | 1242.32 | 707.75 | 534.58 | 1405.58 | 359.48 | 0.00 | 0.00 | 0.00 |
May | 1185.44 | 675.57 | 509.87 | 1424.78 | 273.22 | 0.00 | 0.00 | 0.00 |
June | 1277.99 | 787.31 | 490.69 | 1699.97 | 171.99 | 0.00 | 0.00 | 0.00 |
July | 1182.55 | 676.23 | 506.32 | 1644.79 | 110.32 | 0.00 | 0.00 | 0.00 |
August | 1170.21 | 645.16 | 525.05 | 1577.76 | 122.95 | 0.00 | 0.00 | 0.00 |
September | 974.01 | 544.97 | 429.04 | 1234.61 | 233.43 | 0.00 | 0.00 | 0.00 |
October | 847.09 | 537.44 | 309.64 | 934.70 | 410.40 | 0.00 | 0.00 | 0.00 |
November | 662.04 | 389.21 | 272.83 | 603.42 | 599.51 | 0.00 | 0.00 | 0.00 |
December | 536.44 | 326.47 | 209.97 | 432.48 | 783.69 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 937.93 | 541.99 | 395.93 | 1080.53 | 414.95 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 536.44 | 317.21 | 209.97 | 432.48 | 110.32 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1277.99 | 787.31 | 534.58 | 1699.97 | 783.69 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 567.35 | 317.20 | 250.15 | 450.23 | 735.36 | 0.00 | 0.00 | 0.00 |
February | 689.31 | 371.61 | 317.70 | 608.08 | 668.53 | 0.00 | 0.00 | 0.00 |
March | 909.31 | 516.93 | 392.38 | 924.22 | 525.50 | 0.00 | 0.00 | 0.00 |
April | 1242.30 | 707.73 | 534.57 | 1405.55 | 359.47 | 0.00 | 0.00 | 0.00 |
May | 1185.42 | 675.56 | 509.86 | 1424.75 | 273.21 | 0.00 | 0.00 | 0.00 |
June | 1277.97 | 787.29 | 490.68 | 1699.94 | 171.99 | 0.00 | 0.00 | 0.00 |
July | 1182.53 | 676.22 | 506.31 | 1644.76 | 110.32 | 0.00 | 0.00 | 0.00 |
August | 1170.19 | 645.15 | 525.04 | 1577.73 | 122.95 | 0.00 | 0.00 | 0.00 |
September | 973.99 | 544.96 | 429.03 | 1234.59 | 233.42 | 0.00 | 0.00 | 0.00 |
October | 847.07 | 537.43 | 309.64 | 934.69 | 410.39 | 0.00 | 0.00 | 0.00 |
November | 662.03 | 389.20 | 272.83 | 603.41 | 599.50 | 0.00 | 0.00 | 0.00 |
December | 536.43 | 326.47 | 209.96 | 432.47 | 783.68 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 937.91 | 541.98 | 395.92 | 1080.51 | 414.94 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 536.43 | 317.20 | 209.96 | 432.47 | 110.32 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1277.97 | 787.29 | 534.57 | 1699.94 | 783.68 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1363.13 | 1060.70 | 302.43 | 1493.63 | 654.51 | 0.00 | 0.00 | 0.00 |
February | 1334.01 | 974.45 | 359.56 | 1494.64 | 608.10 | 0.00 | 0.00 | 0.00 |
March | 983.03 | 594.30 | 388.73 | 1123.61 | 497.95 | 0.00 | 0.00 | 0.00 |
April | 766.63 | 314.69 | 451.94 | 909.31 | 358.13 | 0.00 | 0.00 | 0.00 |
May | 511.28 | 112.47 | 398.81 | 611.46 | 259.11 | 0.00 | 0.00 | 0.00 |
June | 432.50 | 53.30 | 379.20 | 613.54 | 170.03 | 0.00 | 0.00 | 0.00 |
July | 478.58 | 76.43 | 402.16 | 737.12 | 111.41 | 0.00 | 0.00 | 0.00 |
August | 658.09 | 213.91 | 444.18 | 969.33 | 130.26 | 0.00 | 0.00 | 0.00 |
September | 910.00 | 507.44 | 402.56 | 1243.71 | 229.38 | 0.00 | 0.00 | 0.00 |
October | 1244.98 | 916.92 | 328.06 | 1528.08 | 385.44 | 0.00 | 0.00 | 0.00 |
November | 1386.68 | 1064.27 | 322.41 | 1567.97 | 539.51 | 0.00 | 0.00 | 0.00 |
December | 1478.95 | 1219.98 | 258.97 | 1632.96 | 682.07 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 960.23 | 590.44 | 369.79 | 1158.54 | 384.33 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 432.50 | 53.30 | 258.97 | 611.46 | 111.41 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1478.95 | 1219.98 | 451.94 | 1632.96 | 682.07 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1363.13 | 1060.70 | 302.43 | 1493.63 | 654.51 | 0.00 | 0.00 | 0.00 |
February | 1334.00 | 974.44 | 359.56 | 1494.64 | 608.10 | 0.00 | 0.00 | 0.00 |
March | 983.02 | 594.30 | 388.73 | 1123.61 | 497.95 | 0.00 | 0.00 | 0.00 |
April | 766.63 | 314.69 | 451.94 | 909.31 | 358.13 | 0.00 | 0.00 | 0.00 |
May | 511.28 | 112.47 | 398.81 | 611.46 | 259.11 | 0.00 | 0.00 | 0.00 |
June | 432.50 | 53.30 | 379.20 | 613.54 | 170.03 | 0.00 | 0.00 | 0.00 |
July | 478.58 | 76.43 | 402.16 | 737.12 | 111.41 | 0.00 | 0.00 | 0.00 |
August | 658.09 | 213.91 | 444.18 | 969.33 | 130.26 | 0.00 | 0.00 | 0.00 |
September | 909.99 | 507.44 | 402.55 | 1243.71 | 229.38 | 0.00 | 0.00 | 0.00 |
October | 1244.98 | 916.92 | 328.06 | 1528.08 | 385.44 | 0.00 | 0.00 | 0.00 |
November | 1386.67 | 1064.27 | 322.41 | 1567.96 | 539.51 | 0.00 | 0.00 | 0.00 |
December | 1478.95 | 1219.98 | 258.97 | 1632.96 | 682.07 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 960.23 | 590.44 | 369.79 | 1158.54 | 384.33 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 432.50 | 53.30 | 258.97 | 611.46 | 111.41 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1478.95 | 1219.98 | 451.94 | 1632.96 | 682.07 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1363.13 | 1060.70 | 302.43 | 1493.63 | 654.51 | 0.00 | 0.00 | 0.00 |
February | 1334.01 | 974.45 | 359.56 | 1494.64 | 608.10 | 0.00 | 0.00 | 0.00 |
March | 983.03 | 594.30 | 388.73 | 1123.61 | 497.95 | 0.00 | 0.00 | 0.00 |
April | 766.63 | 314.69 | 451.94 | 909.31 | 358.13 | 0.00 | 0.00 | 0.00 |
May | 511.28 | 112.47 | 398.81 | 611.46 | 259.11 | 0.00 | 0.00 | 0.00 |
June | 432.50 | 53.30 | 379.20 | 613.54 | 170.03 | 0.00 | 0.00 | 0.00 |
July | 478.58 | 76.43 | 402.16 | 737.12 | 111.41 | 0.00 | 0.00 | 0.00 |
August | 658.09 | 213.91 | 444.18 | 969.33 | 130.26 | 0.00 | 0.00 | 0.00 |
September | 910.00 | 507.44 | 402.56 | 1243.71 | 229.38 | 0.00 | 0.00 | 0.00 |
October | 1244.98 | 916.92 | 328.06 | 1528.08 | 385.44 | 0.00 | 0.00 | 0.00 |
November | 1386.68 | 1064.27 | 322.41 | 1567.97 | 539.51 | 0.00 | 0.00 | 0.00 |
December | 1478.95 | 1219.98 | 258.97 | 1632.96 | 682.07 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 960.23 | 590.44 | 369.79 | 1158.54 | 384.33 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 432.50 | 53.30 | 258.97 | 611.46 | 111.41 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1478.95 | 1219.98 | 451.94 | 1632.96 | 682.07 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1363.13 | 1060.70 | 302.43 | 1493.63 | 654.51 | 0.00 | 0.00 | 0.00 |
February | 1334.00 | 974.44 | 359.56 | 1494.64 | 608.10 | 0.00 | 0.00 | 0.00 |
March | 983.02 | 594.30 | 388.73 | 1123.61 | 497.95 | 0.00 | 0.00 | 0.00 |
April | 766.63 | 314.69 | 451.94 | 909.31 | 358.13 | 0.00 | 0.00 | 0.00 |
May | 511.28 | 112.47 | 398.81 | 611.46 | 259.11 | 0.00 | 0.00 | 0.00 |
June | 432.50 | 53.30 | 379.20 | 613.54 | 170.03 | 0.00 | 0.00 | 0.00 |
July | 478.58 | 76.43 | 402.16 | 737.12 | 111.41 | 0.00 | 0.00 | 0.00 |
August | 658.09 | 213.91 | 444.18 | 969.33 | 130.26 | 0.00 | 0.00 | 0.00 |
September | 909.99 | 507.44 | 402.55 | 1243.71 | 229.38 | 0.00 | 0.00 | 0.00 |
October | 1244.98 | 916.92 | 328.06 | 1528.08 | 385.44 | 0.00 | 0.00 | 0.00 |
November | 1386.67 | 1064.27 | 322.41 | 1567.96 | 539.51 | 0.00 | 0.00 | 0.00 |
December | 1478.95 | 1219.98 | 258.97 | 1632.96 | 682.07 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 960.23 | 590.44 | 369.79 | 1158.54 | 384.33 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 432.50 | 53.30 | 258.97 | 611.46 | 111.41 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1478.95 | 1219.98 | 451.94 | 1632.96 | 682.07 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1363.07 | 1060.66 | 302.41 | 1493.57 | 654.48 | 0.00 | 0.00 | 0.00 |
February | 1333.95 | 974.41 | 359.55 | 1494.58 | 608.07 | 0.00 | 0.00 | 0.00 |
March | 982.99 | 594.28 | 388.71 | 1123.57 | 497.93 | 0.00 | 0.00 | 0.00 |
April | 766.60 | 314.68 | 451.93 | 909.27 | 358.12 | 0.00 | 0.00 | 0.00 |
May | 511.26 | 112.47 | 398.79 | 611.43 | 259.09 | 0.00 | 0.00 | 0.00 |
June | 432.48 | 53.30 | 379.18 | 613.52 | 170.02 | 0.00 | 0.00 | 0.00 |
July | 478.56 | 76.42 | 402.14 | 737.09 | 111.40 | 0.00 | 0.00 | 0.00 |
August | 658.06 | 213.90 | 444.16 | 969.29 | 130.25 | 0.00 | 0.00 | 0.00 |
September | 909.96 | 507.42 | 402.54 | 1243.66 | 229.37 | 0.00 | 0.00 | 0.00 |
October | 1244.93 | 916.89 | 328.05 | 1528.02 | 385.42 | 0.00 | 0.00 | 0.00 |
November | 1386.62 | 1064.23 | 322.39 | 1567.90 | 539.49 | 0.00 | 0.00 | 0.00 |
December | 1478.89 | 1219.93 | 258.96 | 1632.90 | 682.04 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 960.20 | 590.42 | 369.78 | 1158.50 | 384.32 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 432.48 | 53.30 | 258.96 | 611.43 | 111.40 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1478.89 | 1219.93 | 451.93 | 1632.90 | 682.04 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 585.21 | 333.72 | 251.48 | 515.47 | 817.94 | 0.00 | 0.00 | 0.00 |
February | 753.36 | 435.19 | 318.16 | 714.75 | 764.61 | 0.00 | 0.00 | 0.00 |
March | 841.41 | 447.90 | 393.51 | 847.10 | 624.21 | 0.00 | 0.00 | 0.00 |
April | 1073.90 | 571.53 | 502.36 | 1176.41 | 445.59 | 0.00 | 0.00 | 0.00 |
May | 1018.21 | 524.65 | 493.56 | 1203.65 | 312.74 | 0.00 | 0.00 | 0.00 |
June | 1091.52 | 609.06 | 482.46 | 1453.89 | 222.32 | 0.00 | 0.00 | 0.00 |
July | 984.51 | 481.81 | 502.71 | 1367.96 | 152.48 | 0.00 | 0.00 | 0.00 |
August | 1006.00 | 465.32 | 540.68 | 1345.99 | 181.08 | 0.00 | 0.00 | 0.00 |
September | 908.65 | 478.55 | 430.10 | 1156.84 | 276.34 | 0.00 | 0.00 | 0.00 |
October | 831.30 | 516.68 | 314.61 | 933.85 | 488.82 | 0.00 | 0.00 | 0.00 |
November | 652.56 | 383.92 | 268.65 | 605.26 | 696.98 | 0.00 | 0.00 | 0.00 |
December | 564.33 | 353.90 | 210.44 | 480.62 | 911.36 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 859.32 | 466.63 | 392.69 | 984.43 | 489.84 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 564.33 | 333.72 | 210.44 | 480.62 | 152.48 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1091.52 | 609.06 | 540.68 | 1453.89 | 911.36 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 585.21 | 333.72 | 251.48 | 515.47 | 817.94 | 0.00 | 0.00 | 0.00 |
February | 753.36 | 435.19 | 318.16 | 714.75 | 764.61 | 0.00 | 0.00 | 0.00 |
March | 841.41 | 447.90 | 393.51 | 847.10 | 624.21 | 0.00 | 0.00 | 0.00 |
April | 1073.90 | 571.53 | 502.36 | 1176.41 | 445.59 | 0.00 | 0.00 | 0.00 |
May | 1018.21 | 524.65 | 493.56 | 1203.65 | 312.74 | 0.00 | 0.00 | 0.00 |
June | 1091.52 | 609.06 | 482.46 | 1453.89 | 222.32 | 0.00 | 0.00 | 0.00 |
July | 984.51 | 481.81 | 502.71 | 1367.96 | 152.48 | 0.00 | 0.00 | 0.00 |
August | 1006.00 | 465.32 | 540.68 | 1345.99 | 181.08 | 0.00 | 0.00 | 0.00 |
September | 908.65 | 478.55 | 430.10 | 1156.84 | 276.34 | 0.00 | 0.00 | 0.00 |
October | 831.30 | 516.68 | 314.61 | 933.85 | 488.82 | 0.00 | 0.00 | 0.00 |
November | 652.56 | 383.92 | 268.65 | 605.26 | 696.98 | 0.00 | 0.00 | 0.00 |
December | 564.33 | 353.90 | 210.44 | 480.62 | 911.36 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 859.32 | 466.63 | 392.69 | 984.43 | 489.84 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 564.33 | 333.72 | 210.44 | 480.62 | 152.48 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1091.52 | 609.06 | 540.68 | 1453.89 | 911.36 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 585.20 | 333.72 | 251.48 | 515.46 | 817.93 | 0.00 | 0.00 | 0.00 |
February | 753.34 | 435.18 | 318.16 | 714.73 | 764.60 | 0.00 | 0.00 | 0.00 |
March | 841.40 | 447.89 | 393.51 | 847.09 | 624.20 | 0.00 | 0.00 | 0.00 |
April | 1073.88 | 571.52 | 502.35 | 1176.38 | 445.58 | 0.00 | 0.00 | 0.00 |
May | 1018.19 | 524.64 | 493.55 | 1203.63 | 312.73 | 0.00 | 0.00 | 0.00 |
June | 1091.50 | 609.04 | 482.45 | 1453.86 | 222.31 | 0.00 | 0.00 | 0.00 |
July | 984.50 | 481.80 | 502.70 | 1367.93 | 152.48 | 0.00 | 0.00 | 0.00 |
August | 1005.98 | 465.31 | 540.67 | 1345.96 | 181.08 | 0.00 | 0.00 | 0.00 |
September | 908.64 | 478.54 | 430.09 | 1156.82 | 276.33 | 0.00 | 0.00 | 0.00 |
October | 831.28 | 516.67 | 314.61 | 933.84 | 488.81 | 0.00 | 0.00 | 0.00 |
November | 652.55 | 383.91 | 268.64 | 605.25 | 696.96 | 0.00 | 0.00 | 0.00 |
December | 564.32 | 353.89 | 210.43 | 480.61 | 911.34 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 859.31 | 466.62 | 392.68 | 984.42 | 489.84 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 564.32 | 333.72 | 210.43 | 480.61 | 152.48 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1091.50 | 609.04 | 540.67 | 1453.86 | 911.34 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 921.89 | 0.00 | 921.89 | 198.23 | 3325.17 | 0.00 | 0.00 | 0.00 |
February | 1152.21 | 0.00 | 1152.21 | 413.17 | 3012.11 | 0.00 | 0.00 | 0.00 |
March | 1453.36 | 0.00 | 1453.36 | 874.70 | 2381.37 | 0.00 | 0.00 | 0.00 |
April | 1843.87 | 15.79 | 1828.08 | 1427.32 | 1586.98 | 0.00 | 0.00 | 0.00 |
May | 2004.30 | 129.22 | 1875.07 | 1984.87 | 1162.02 | 0.00 | 0.00 | 0.00 |
June | 2277.42 | 372.70 | 1904.73 | 3085.26 | 779.27 | 0.00 | 0.00 | 0.00 |
July | 2090.32 | 173.98 | 1916.34 | 3073.19 | 531.50 | 0.00 | 0.00 | 0.00 |
August | 1939.12 | 43.41 | 1895.70 | 2602.00 | 599.47 | 0.00 | 0.00 | 0.00 |
September | 1550.69 | 0.40 | 1550.30 | 1767.02 | 1051.60 | 0.00 | 0.00 | 0.00 |
October | 1157.13 | 0.00 | 1157.13 | 811.04 | 1856.15 | 0.00 | 0.00 | 0.00 |
November | 982.68 | 0.00 | 982.68 | 282.36 | 2646.84 | 0.00 | 0.00 | 0.00 |
December | 784.67 | 0.00 | 784.67 | 63.31 | 3487.19 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1514.45 | 61.40 | 1453.05 | 1387.00 | 1862.76 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 784.67 | 0.00 | 784.67 | 63.31 | 531.50 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2277.42 | 372.70 | 1916.34 | 3085.26 | 3487.19 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1702.05 | 951.61 | 750.44 | 1387.88 | 2050.78 | 0.00 | 0.00 | 0.00 |
February | 2067.96 | 1114.85 | 953.11 | 1854.65 | 1873.42 | 0.00 | 0.00 | 0.00 |
March | 2727.95 | 1550.79 | 1177.16 | 2777.25 | 1491.40 | 0.00 | 0.00 | 0.00 |
April | 3726.93 | 2123.21 | 1603.72 | 4198.04 | 1039.86 | 0.00 | 0.00 | 0.00 |
May | 3556.28 | 2026.70 | 1529.59 | 4249.29 | 792.57 | 0.00 | 0.00 | 0.00 |
June | 3833.95 | 2361.89 | 1472.05 | 5072.13 | 515.52 | 0.00 | 0.00 | 0.00 |
July | 3547.62 | 2028.67 | 1518.95 | 4902.49 | 359.29 | 0.00 | 0.00 | 0.00 |
August | 3510.61 | 1935.46 | 1575.14 | 4699.09 | 404.42 | 0.00 | 0.00 | 0.00 |
September | 2921.99 | 1634.88 | 1287.11 | 3687.63 | 677.46 | 0.00 | 0.00 | 0.00 |
October | 2541.23 | 1612.31 | 928.92 | 2804.36 | 1166.57 | 0.00 | 0.00 | 0.00 |
November | 1986.10 | 1167.61 | 818.49 | 1830.48 | 1664.72 | 0.00 | 0.00 | 0.00 |
December | 1609.31 | 979.41 | 629.90 | 1324.83 | 2163.32 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 2813.75 | 1625.97 | 1187.78 | 3238.57 | 1179.90 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 1609.31 | 951.61 | 629.90 | 1324.83 | 359.29 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 3833.95 | 2361.89 | 1603.72 | 5072.13 | 2163.32 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 6815.55 | 5303.44 | 1512.11 | 7414.09 | 3215.94 | 0.00 | 0.00 | 0.00 |
February | 6669.95 | 4872.17 | 1797.78 | 7422.03 | 2971.21 | 0.00 | 0.00 | 0.00 |
March | 4915.07 | 2971.46 | 1943.61 | 5587.64 | 2411.16 | 0.00 | 0.00 | 0.00 |
April | 3833.12 | 1573.43 | 2259.70 | 4533.69 | 1714.46 | 0.00 | 0.00 | 0.00 |
May | 2556.38 | 562.36 | 1994.02 | 3052.61 | 1251.18 | 0.00 | 0.00 | 0.00 |
June | 2162.48 | 266.50 | 1895.98 | 3083.54 | 824.08 | 0.00 | 0.00 | 0.00 |
July | 2392.89 | 382.12 | 2010.77 | 3691.78 | 557.94 | 0.00 | 0.00 | 0.00 |
August | 3290.41 | 1069.55 | 2220.86 | 4837.41 | 653.77 | 0.00 | 0.00 | 0.00 |
September | 4549.92 | 2537.17 | 2012.75 | 6174.52 | 1126.20 | 0.00 | 0.00 | 0.00 |
October | 6224.84 | 4584.56 | 1640.28 | 7584.66 | 1892.18 | 0.00 | 0.00 | 0.00 |
November | 6933.29 | 5321.28 | 1612.01 | 7792.18 | 2624.11 | 0.00 | 0.00 | 0.00 |
December | 7394.68 | 6099.83 | 1294.84 | 8122.64 | 3297.38 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 4801.12 | 2952.18 | 1848.94 | 5765.34 | 1872.67 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 2162.48 | 266.50 | 1294.84 | 3052.61 | 557.94 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 7394.68 | 6099.83 | 2259.70 | 8122.64 | 3297.38 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1755.60 | 1001.16 | 754.44 | 1591.75 | 2237.82 | 0.00 | 0.00 | 0.00 |
February | 2260.05 | 1305.56 | 954.48 | 2204.51 | 2054.73 | 0.00 | 0.00 | 0.00 |
March | 2524.21 | 1343.69 | 1180.52 | 2612.52 | 1647.01 | 0.00 | 0.00 | 0.00 |
April | 3221.65 | 1714.58 | 1507.07 | 3596.08 | 1165.95 | 0.00 | 0.00 | 0.00 |
May | 3054.60 | 1573.94 | 1480.65 | 3629.61 | 870.91 | 0.00 | 0.00 | 0.00 |
June | 3274.52 | 1827.15 | 1447.37 | 4389.38 | 612.60 | 0.00 | 0.00 | 0.00 |
July | 2953.51 | 1445.41 | 1508.10 | 4140.23 | 415.15 | 0.00 | 0.00 | 0.00 |
August | 3017.97 | 1395.93 | 1622.03 | 4086.60 | 476.91 | 0.00 | 0.00 | 0.00 |
September | 2725.93 | 1435.64 | 1290.29 | 3487.42 | 764.64 | 0.00 | 0.00 | 0.00 |
October | 2493.86 | 1550.03 | 943.84 | 2847.88 | 1306.37 | 0.00 | 0.00 | 0.00 |
November | 1957.67 | 1151.74 | 805.93 | 1887.43 | 1792.81 | 0.00 | 0.00 | 0.00 |
December | 1692.99 | 1061.68 | 631.30 | 1504.19 | 2311.61 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 2577.94 | 1399.88 | 1178.06 | 3000.91 | 1300.96 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 1692.99 | 1001.16 | 631.30 | 1504.19 | 415.15 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 3274.52 | 1827.15 | 1622.03 | 4389.38 | 2311.61 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 921.89 | 0.00 | 921.89 | 240.38 | 3101.50 | 0.00 | 0.00 | 0.00 |
February | 1152.21 | 0.00 | 1152.21 | 459.49 | 2822.16 | 0.00 | 0.00 | 0.00 |
March | 1453.36 | 0.00 | 1453.36 | 921.75 | 2234.51 | 0.00 | 0.00 | 0.00 |
April | 1843.87 | 15.79 | 1828.08 | 1454.07 | 1506.32 | 0.00 | 0.00 | 0.00 |
May | 2004.30 | 129.22 | 1875.07 | 1991.17 | 1128.28 | 0.00 | 0.00 | 0.00 |
June | 2277.42 | 372.70 | 1904.73 | 3070.85 | 771.33 | 0.00 | 0.00 | 0.00 |
July | 2090.32 | 173.98 | 1916.34 | 3046.89 | 537.71 | 0.00 | 0.00 | 0.00 |
August | 1939.12 | 43.41 | 1895.70 | 2581.53 | 599.24 | 0.00 | 0.00 | 0.00 |
September | 1550.69 | 0.40 | 1550.30 | 1764.13 | 1022.88 | 0.00 | 0.00 | 0.00 |
October | 1157.13 | 0.00 | 1157.13 | 841.22 | 1738.72 | 0.00 | 0.00 | 0.00 |
November | 982.68 | 0.00 | 982.68 | 330.67 | 2432.78 | 0.00 | 0.00 | 0.00 |
December | 784.67 | 0.00 | 784.67 | 86.71 | 3236.52 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1514.45 | 61.40 | 1453.05 | 1403.99 | 1755.86 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 784.67 | 0.00 | 784.67 | 86.71 | 537.71 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2277.42 | 372.70 | 1916.34 | 3070.85 | 3236.52 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1702.05 | 951.61 | 750.44 | 1437.59 | 1921.90 | 0.00 | 0.00 | 0.00 |
February | 2067.96 | 1114.85 | 953.11 | 1894.06 | 1767.46 | 0.00 | 0.00 | 0.00 |
March | 2727.95 | 1550.79 | 1177.16 | 2799.50 | 1418.88 | 0.00 | 0.00 | 0.00 |
April | 3726.93 | 2123.21 | 1603.72 | 4200.72 | 1004.23 | 0.00 | 0.00 | 0.00 |
May | 3556.28 | 2026.70 | 1529.59 | 4239.47 | 777.20 | 0.00 | 0.00 | 0.00 |
June | 3833.95 | 2361.89 | 1472.05 | 5054.41 | 513.10 | 0.00 | 0.00 | 0.00 |
July | 3547.62 | 2028.67 | 1518.95 | 4880.39 | 365.26 | 0.00 | 0.00 | 0.00 |
August | 3510.61 | 1935.46 | 1575.14 | 4679.66 | 406.55 | 0.00 | 0.00 | 0.00 |
September | 2921.99 | 1634.88 | 1287.11 | 3678.78 | 666.94 | 0.00 | 0.00 | 0.00 |
October | 2541.23 | 1612.31 | 928.92 | 2817.23 | 1113.70 | 0.00 | 0.00 | 0.00 |
November | 1986.10 | 1167.61 | 818.49 | 1869.55 | 1552.93 | 0.00 | 0.00 | 0.00 |
December | 1609.31 | 979.41 | 629.90 | 1363.13 | 2013.94 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 2813.75 | 1625.97 | 1187.78 | 3248.94 | 1123.69 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 1609.31 | 951.61 | 629.90 | 1363.13 | 365.26 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 3833.95 | 2361.89 | 1603.72 | 5054.41 | 2013.94 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 6815.55 | 5303.44 | 1512.11 | 7481.85 | 3010.69 | 0.00 | 0.00 | 0.00 |
February | 6669.95 | 4872.17 | 1797.78 | 7469.35 | 2797.43 | 0.00 | 0.00 | 0.00 |
March | 4915.07 | 2971.46 | 1943.61 | 5617.49 | 2287.45 | 0.00 | 0.00 | 0.00 |
April | 3833.12 | 1573.43 | 2259.70 | 4541.61 | 1640.67 | 0.00 | 0.00 | 0.00 |
May | 2556.38 | 562.36 | 1994.02 | 3049.04 | 1214.62 | 0.00 | 0.00 | 0.00 |
June | 2162.48 | 266.50 | 1895.98 | 3067.83 | 812.53 | 0.00 | 0.00 | 0.00 |
July | 2392.89 | 382.12 | 2010.77 | 3664.06 | 563.84 | 0.00 | 0.00 | 0.00 |
August | 3290.41 | 1069.55 | 2220.86 | 4811.92 | 653.19 | 0.00 | 0.00 | 0.00 |
September | 4549.92 | 2537.17 | 2012.75 | 6162.89 | 1102.88 | 0.00 | 0.00 | 0.00 |
October | 6224.84 | 4584.56 | 1640.28 | 7608.09 | 1803.44 | 0.00 | 0.00 | 0.00 |
November | 6933.29 | 5321.28 | 1612.01 | 7848.01 | 2454.70 | 0.00 | 0.00 | 0.00 |
December | 7394.68 | 6099.83 | 1294.84 | 8180.17 | 3069.14 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 4801.12 | 2952.18 | 1848.94 | 5782.31 | 1778.97 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 2162.48 | 266.50 | 1294.84 | 3049.04 | 563.84 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 7394.68 | 6099.83 | 2259.70 | 8180.17 | 3069.14 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1755.60 | 1001.16 | 754.44 | 1613.39 | 2109.09 | 0.00 | 0.00 | 0.00 |
February | 2260.05 | 1305.56 | 954.48 | 2219.57 | 1950.98 | 0.00 | 0.00 | 0.00 |
March | 2524.21 | 1343.69 | 1180.52 | 2625.68 | 1569.89 | 0.00 | 0.00 | 0.00 |
April | 3221.65 | 1714.58 | 1507.07 | 3598.51 | 1122.54 | 0.00 | 0.00 | 0.00 |
May | 3054.60 | 1573.94 | 1480.65 | 3624.38 | 848.91 | 0.00 | 0.00 | 0.00 |
June | 3274.52 | 1827.15 | 1447.37 | 4376.19 | 605.23 | 0.00 | 0.00 | 0.00 |
July | 2953.51 | 1445.41 | 1508.10 | 4120.48 | 417.55 | 0.00 | 0.00 | 0.00 |
August | 3017.97 | 1395.93 | 1622.03 | 4070.29 | 475.37 | 0.00 | 0.00 | 0.00 |
September | 2725.93 | 1435.64 | 1290.29 | 3480.91 | 749.04 | 0.00 | 0.00 | 0.00 |
October | 2493.86 | 1550.03 | 943.84 | 2854.86 | 1247.14 | 0.00 | 0.00 | 0.00 |
November | 1957.67 | 1151.74 | 805.93 | 1906.90 | 1681.34 | 0.00 | 0.00 | 0.00 |
December | 1692.99 | 1061.68 | 631.30 | 1518.72 | 2172.90 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 2577.94 | 1399.88 | 1178.06 | 3003.52 | 1242.30 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 1692.99 | 1001.16 | 631.30 | 1518.72 | 417.55 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 3274.52 | 1827.15 | 1622.03 | 4376.19 | 2172.90 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.493844E+09 | 0.00 | 0.493844E+09 | 70041202.17 | 0.196621E+10 |
February | 0.557490E+09 | 0.00 | 0.557490E+09 | 0.158220E+09 | 0.160683E+10 |
March | 0.778547E+09 | 0.00 | 0.778547E+09 | 0.426396E+09 | 0.139833E+10 |
April | 0.955871E+09 | 8183766.27 | 0.947688E+09 | 0.707250E+09 | 0.898909E+09 |
May | 0.107368E+10 | 69223332.64 | 0.100445E+10 | 0.104774E+10 | 0.655138E+09 |
June | 0.118063E+10 | 0.193208E+09 | 0.987422E+09 | 0.158954E+10 | 0.417080E+09 |
July | 0.111975E+10 | 93197174.28 | 0.102656E+10 | 0.163657E+10 | 0.288062E+09 |
August | 0.103876E+10 | 23255587.66 | 0.101550E+10 | 0.138061E+10 | 0.328858E+09 |
September | 0.803889E+09 | 206319.17 | 0.803683E+09 | 0.904004E+09 | 0.576317E+09 |
October | 0.619858E+09 | 0.00 | 0.619858E+09 | 0.404605E+09 | 0.109044E+10 |
November | 0.509426E+09 | 0.00 | 0.509426E+09 | 0.110155E+09 | 0.155032E+10 |
December | 0.420335E+09 | 0.00 | 0.420335E+09 | 14063983.60 | 0.212328E+10 |
Annual Sum or Average | 0.955208E+10 | 0.387274E+09 | 0.916480E+10 | 0.844919E+10 | 0.128998E+11 |
Minimum of Months | 0.420335E+09 | 0.00 | 0.420335E+09 | 14063983.60 | 0.288062E+09 |
Maximum of Months | 0.118063E+10 | 0.193208E+09 | 0.102656E+10 | 0.163657E+10 | 0.212328E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.493844E+09 | 0.00 | 0.493844E+09 | 70041011.12 | 0.196621E+10 |
February | 0.557490E+09 | 0.00 | 0.557490E+09 | 0.158219E+09 | 0.160683E+10 |
March | 0.778547E+09 | 0.00 | 0.778547E+09 | 0.426396E+09 | 0.139833E+10 |
April | 0.955871E+09 | 8183756.45 | 0.947687E+09 | 0.707249E+09 | 0.898909E+09 |
May | 0.107367E+10 | 69223249.57 | 0.100445E+10 | 0.104774E+10 | 0.655138E+09 |
June | 0.118063E+10 | 0.193208E+09 | 0.987421E+09 | 0.158954E+10 | 0.417080E+09 |
July | 0.111975E+10 | 93197062.45 | 0.102656E+10 | 0.163657E+10 | 0.288062E+09 |
August | 0.103876E+10 | 23255559.76 | 0.101550E+10 | 0.138060E+10 | 0.328858E+09 |
September | 0.803889E+09 | 206318.93 | 0.803682E+09 | 0.904003E+09 | 0.576317E+09 |
October | 0.619857E+09 | 0.00 | 0.619857E+09 | 0.404605E+09 | 0.109044E+10 |
November | 0.509425E+09 | 0.00 | 0.509425E+09 | 0.110155E+09 | 0.155032E+10 |
December | 0.420335E+09 | 0.00 | 0.420335E+09 | 14063917.20 | 0.212328E+10 |
Annual Sum or Average | 0.955207E+10 | 0.387274E+09 | 0.916480E+10 | 0.844918E+10 | 0.128998E+11 |
Minimum of Months | 0.420335E+09 | 0.00 | 0.420335E+09 | 14063917.20 | 0.288062E+09 |
Maximum of Months | 0.118063E+10 | 0.193208E+09 | 0.102656E+10 | 0.163657E+10 | 0.212328E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.493844E+09 | 0.00 | 0.493844E+09 | 70041202.17 | 0.196621E+10 |
February | 0.557490E+09 | 0.00 | 0.557490E+09 | 0.158220E+09 | 0.160683E+10 |
March | 0.778547E+09 | 0.00 | 0.778547E+09 | 0.426396E+09 | 0.139833E+10 |
April | 0.955871E+09 | 8183766.27 | 0.947688E+09 | 0.707250E+09 | 0.898909E+09 |
May | 0.107368E+10 | 69223332.64 | 0.100445E+10 | 0.104774E+10 | 0.655138E+09 |
June | 0.118063E+10 | 0.193208E+09 | 0.987422E+09 | 0.158954E+10 | 0.417080E+09 |
July | 0.111975E+10 | 93197174.28 | 0.102656E+10 | 0.163657E+10 | 0.288062E+09 |
August | 0.103876E+10 | 23255587.66 | 0.101550E+10 | 0.138061E+10 | 0.328858E+09 |
September | 0.803889E+09 | 206319.17 | 0.803683E+09 | 0.904004E+09 | 0.576317E+09 |
October | 0.619858E+09 | 0.00 | 0.619858E+09 | 0.404605E+09 | 0.109044E+10 |
November | 0.509426E+09 | 0.00 | 0.509426E+09 | 0.110155E+09 | 0.155032E+10 |
December | 0.420335E+09 | 0.00 | 0.420335E+09 | 14063983.60 | 0.212328E+10 |
Annual Sum or Average | 0.955208E+10 | 0.387274E+09 | 0.916480E+10 | 0.844919E+10 | 0.128998E+11 |
Minimum of Months | 0.420335E+09 | 0.00 | 0.420335E+09 | 14063983.60 | 0.288062E+09 |
Maximum of Months | 0.118063E+10 | 0.193208E+09 | 0.102656E+10 | 0.163657E+10 | 0.212328E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.493844E+09 | 0.00 | 0.493844E+09 | 70041011.12 | 0.196621E+10 |
February | 0.557490E+09 | 0.00 | 0.557490E+09 | 0.158219E+09 | 0.160683E+10 |
March | 0.778547E+09 | 0.00 | 0.778547E+09 | 0.426396E+09 | 0.139833E+10 |
April | 0.955871E+09 | 8183756.45 | 0.947687E+09 | 0.707249E+09 | 0.898909E+09 |
May | 0.107367E+10 | 69223249.57 | 0.100445E+10 | 0.104774E+10 | 0.655138E+09 |
June | 0.118063E+10 | 0.193208E+09 | 0.987421E+09 | 0.158954E+10 | 0.417080E+09 |
July | 0.111975E+10 | 93197062.45 | 0.102656E+10 | 0.163657E+10 | 0.288062E+09 |
August | 0.103876E+10 | 23255559.76 | 0.101550E+10 | 0.138060E+10 | 0.328858E+09 |
September | 0.803889E+09 | 206318.93 | 0.803682E+09 | 0.904003E+09 | 0.576317E+09 |
October | 0.619857E+09 | 0.00 | 0.619857E+09 | 0.404605E+09 | 0.109044E+10 |
November | 0.509425E+09 | 0.00 | 0.509425E+09 | 0.110155E+09 | 0.155032E+10 |
December | 0.420335E+09 | 0.00 | 0.420335E+09 | 14063917.20 | 0.212328E+10 |
Annual Sum or Average | 0.955207E+10 | 0.387274E+09 | 0.916480E+10 | 0.844918E+10 | 0.128998E+11 |
Minimum of Months | 0.420335E+09 | 0.00 | 0.420335E+09 | 14063917.20 | 0.288062E+09 |
Maximum of Months | 0.118063E+10 | 0.193208E+09 | 0.102656E+10 | 0.163657E+10 | 0.212328E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.493824E+09 | 0.00 | 0.493824E+09 | 70038379.20 | 0.196613E+10 |
February | 0.557468E+09 | 0.00 | 0.557468E+09 | 0.158213E+09 | 0.160677E+10 |
March | 0.778516E+09 | 0.00 | 0.778516E+09 | 0.426379E+09 | 0.139828E+10 |
April | 0.955833E+09 | 8183436.43 | 0.947650E+09 | 0.707222E+09 | 0.898873E+09 |
May | 0.107363E+10 | 69220542.63 | 0.100441E+10 | 0.104770E+10 | 0.655112E+09 |
June | 0.118058E+10 | 0.193200E+09 | 0.987382E+09 | 0.158947E+10 | 0.417064E+09 |
July | 0.111971E+10 | 93193418.02 | 0.102652E+10 | 0.163650E+10 | 0.288051E+09 |
August | 0.103872E+10 | 23254650.36 | 0.101546E+10 | 0.138055E+10 | 0.328845E+09 |
September | 0.803857E+09 | 206310.86 | 0.803650E+09 | 0.903967E+09 | 0.576294E+09 |
October | 0.619833E+09 | 0.00 | 0.619833E+09 | 0.404589E+09 | 0.109039E+10 |
November | 0.509405E+09 | 0.00 | 0.509405E+09 | 0.110151E+09 | 0.155026E+10 |
December | 0.420318E+09 | 0.00 | 0.420318E+09 | 14063416.76 | 0.212319E+10 |
Annual Sum or Average | 0.955169E+10 | 0.387258E+09 | 0.916444E+10 | 0.844884E+10 | 0.128993E+11 |
Minimum of Months | 0.420318E+09 | 0.00 | 0.420318E+09 | 14063416.76 | 0.288051E+09 |
Maximum of Months | 0.118058E+10 | 0.193200E+09 | 0.102652E+10 | 0.163650E+10 | 0.212319E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.151960E+10 | 0.849603E+09 | 0.670002E+09 | 0.120593E+10 | 0.196963E+10 |
February | 0.166762E+10 | 0.899025E+09 | 0.768592E+09 | 0.147110E+10 | 0.161733E+10 |
March | 0.243554E+10 | 0.138456E+10 | 0.105098E+10 | 0.247547E+10 | 0.140752E+10 |
April | 0.322010E+10 | 0.183448E+10 | 0.138563E+10 | 0.364326E+10 | 0.931768E+09 |
May | 0.317508E+10 | 0.180945E+10 | 0.136563E+10 | 0.381612E+10 | 0.731784E+09 |
June | 0.331256E+10 | 0.204070E+10 | 0.127187E+10 | 0.440633E+10 | 0.445810E+09 |
July | 0.316735E+10 | 0.181122E+10 | 0.135613E+10 | 0.440540E+10 | 0.295474E+09 |
August | 0.313430E+10 | 0.172800E+10 | 0.140630E+10 | 0.422587E+10 | 0.329319E+09 |
September | 0.252463E+10 | 0.141255E+10 | 0.111208E+10 | 0.320010E+10 | 0.605038E+09 |
October | 0.226884E+10 | 0.143949E+10 | 0.829348E+09 | 0.250351E+10 | 0.109922E+10 |
November | 0.171601E+10 | 0.100883E+10 | 0.707180E+09 | 0.156407E+10 | 0.155394E+10 |
December | 0.143680E+10 | 0.874426E+09 | 0.562377E+09 | 0.115835E+10 | 0.209904E+10 |
Annual Sum or Average | 0.295784E+11 | 0.170923E+11 | 0.124861E+11 | 0.340755E+11 | 0.130859E+11 |
Minimum of Months | 0.143680E+10 | 0.849603E+09 | 0.562377E+09 | 0.115835E+10 | 0.295474E+09 |
Maximum of Months | 0.331256E+10 | 0.204070E+10 | 0.140630E+10 | 0.440633E+10 | 0.209904E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.151960E+10 | 0.849603E+09 | 0.670002E+09 | 0.120593E+10 | 0.196963E+10 |
February | 0.166762E+10 | 0.899025E+09 | 0.768592E+09 | 0.147110E+10 | 0.161733E+10 |
March | 0.243554E+10 | 0.138456E+10 | 0.105098E+10 | 0.247547E+10 | 0.140752E+10 |
April | 0.322010E+10 | 0.183448E+10 | 0.138563E+10 | 0.364326E+10 | 0.931768E+09 |
May | 0.317508E+10 | 0.180945E+10 | 0.136563E+10 | 0.381612E+10 | 0.731784E+09 |
June | 0.331256E+10 | 0.204070E+10 | 0.127187E+10 | 0.440633E+10 | 0.445810E+09 |
July | 0.316735E+10 | 0.181122E+10 | 0.135613E+10 | 0.440540E+10 | 0.295474E+09 |
August | 0.313430E+10 | 0.172800E+10 | 0.140630E+10 | 0.422587E+10 | 0.329319E+09 |
September | 0.252463E+10 | 0.141255E+10 | 0.111208E+10 | 0.320010E+10 | 0.605038E+09 |
October | 0.226884E+10 | 0.143949E+10 | 0.829348E+09 | 0.250351E+10 | 0.109922E+10 |
November | 0.171601E+10 | 0.100883E+10 | 0.707180E+09 | 0.156407E+10 | 0.155394E+10 |
December | 0.143680E+10 | 0.874426E+09 | 0.562377E+09 | 0.115835E+10 | 0.209904E+10 |
Annual Sum or Average | 0.295784E+11 | 0.170923E+11 | 0.124861E+11 | 0.340755E+11 | 0.130859E+11 |
Minimum of Months | 0.143680E+10 | 0.849603E+09 | 0.562377E+09 | 0.115835E+10 | 0.295474E+09 |
Maximum of Months | 0.331256E+10 | 0.204070E+10 | 0.140630E+10 | 0.440633E+10 | 0.209904E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.151958E+10 | 0.849587E+09 | 0.669990E+09 | 0.120591E+10 | 0.196959E+10 |
February | 0.166759E+10 | 0.899008E+09 | 0.768578E+09 | 0.147107E+10 | 0.161730E+10 |
March | 0.243549E+10 | 0.138453E+10 | 0.105096E+10 | 0.247542E+10 | 0.140750E+10 |
April | 0.322004E+10 | 0.183444E+10 | 0.138560E+10 | 0.364319E+10 | 0.931751E+09 |
May | 0.317502E+10 | 0.180942E+10 | 0.136560E+10 | 0.381605E+10 | 0.731770E+09 |
June | 0.331250E+10 | 0.204066E+10 | 0.127184E+10 | 0.440624E+10 | 0.445802E+09 |
July | 0.316729E+10 | 0.181118E+10 | 0.135610E+10 | 0.440532E+10 | 0.295468E+09 |
August | 0.313424E+10 | 0.172797E+10 | 0.140628E+10 | 0.422579E+10 | 0.329313E+09 |
September | 0.252458E+10 | 0.141252E+10 | 0.111206E+10 | 0.320004E+10 | 0.605027E+09 |
October | 0.226880E+10 | 0.143946E+10 | 0.829333E+09 | 0.250347E+10 | 0.109920E+10 |
November | 0.171598E+10 | 0.100881E+10 | 0.707167E+09 | 0.156404E+10 | 0.155391E+10 |
December | 0.143678E+10 | 0.874410E+09 | 0.562366E+09 | 0.115833E+10 | 0.209900E+10 |
Annual Sum or Average | 0.295779E+11 | 0.170920E+11 | 0.124859E+11 | 0.340749E+11 | 0.130856E+11 |
Minimum of Months | 0.143678E+10 | 0.849587E+09 | 0.562366E+09 | 0.115833E+10 | 0.295468E+09 |
Maximum of Months | 0.331250E+10 | 0.204066E+10 | 0.140628E+10 | 0.440624E+10 | 0.209900E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.365100E+10 | 0.284098E+10 | 0.810018E+09 | 0.400054E+10 | 0.175303E+10 |
February | 0.322723E+10 | 0.235738E+10 | 0.869847E+09 | 0.361584E+10 | 0.147111E+10 |
March | 0.263293E+10 | 0.159177E+10 | 0.104116E+10 | 0.300949E+10 | 0.133372E+10 |
April | 0.198712E+10 | 0.815675E+09 | 0.117144E+10 | 0.235693E+10 | 0.928278E+09 |
May | 0.136942E+10 | 0.301247E+09 | 0.106817E+10 | 0.163773E+10 | 0.693988E+09 |
June | 0.112104E+10 | 0.138156E+09 | 0.982887E+09 | 0.159030E+10 | 0.440709E+09 |
July | 0.128184E+10 | 0.204698E+09 | 0.107714E+10 | 0.197431E+10 | 0.298391E+09 |
August | 0.176263E+10 | 0.572943E+09 | 0.118968E+10 | 0.259626E+10 | 0.348880E+09 |
September | 0.235871E+10 | 0.131529E+10 | 0.104342E+10 | 0.322369E+10 | 0.594550E+09 |
October | 0.333456E+10 | 0.245589E+10 | 0.878675E+09 | 0.409281E+10 | 0.103235E+10 |
November | 0.359426E+10 | 0.275859E+10 | 0.835677E+09 | 0.406417E+10 | 0.139842E+10 |
December | 0.396123E+10 | 0.326760E+10 | 0.693629E+09 | 0.437373E+10 | 0.182684E+10 |
Annual Sum or Average | 0.302820E+11 | 0.186202E+11 | 0.116618E+11 | 0.365358E+11 | 0.121203E+11 |
Minimum of Months | 0.112104E+10 | 0.138156E+09 | 0.693629E+09 | 0.159030E+10 | 0.298391E+09 |
Maximum of Months | 0.396123E+10 | 0.326760E+10 | 0.118968E+10 | 0.437373E+10 | 0.182684E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.365100E+10 | 0.284098E+10 | 0.810018E+09 | 0.400053E+10 | 0.175303E+10 |
February | 0.322722E+10 | 0.235738E+10 | 0.869846E+09 | 0.361584E+10 | 0.147111E+10 |
March | 0.263293E+10 | 0.159177E+10 | 0.104116E+10 | 0.300948E+10 | 0.133372E+10 |
April | 0.198711E+10 | 0.815674E+09 | 0.117144E+10 | 0.235693E+10 | 0.928278E+09 |
May | 0.136942E+10 | 0.301246E+09 | 0.106817E+10 | 0.163773E+10 | 0.693987E+09 |
June | 0.112104E+10 | 0.138156E+09 | 0.982886E+09 | 0.159030E+10 | 0.440708E+09 |
July | 0.128184E+10 | 0.204698E+09 | 0.107714E+10 | 0.197431E+10 | 0.298390E+09 |
August | 0.176262E+10 | 0.572943E+09 | 0.118968E+10 | 0.259626E+10 | 0.348880E+09 |
September | 0.235871E+10 | 0.131528E+10 | 0.104342E+10 | 0.322369E+10 | 0.594549E+09 |
October | 0.333456E+10 | 0.245589E+10 | 0.878674E+09 | 0.409281E+10 | 0.103235E+10 |
November | 0.359426E+10 | 0.275858E+10 | 0.835676E+09 | 0.406416E+10 | 0.139842E+10 |
December | 0.396122E+10 | 0.326759E+10 | 0.693628E+09 | 0.437373E+10 | 0.182684E+10 |
Annual Sum or Average | 0.302819E+11 | 0.186202E+11 | 0.116617E+11 | 0.365358E+11 | 0.121203E+11 |
Minimum of Months | 0.112104E+10 | 0.138156E+09 | 0.693628E+09 | 0.159030E+10 | 0.298390E+09 |
Maximum of Months | 0.396122E+10 | 0.326759E+10 | 0.118968E+10 | 0.437373E+10 | 0.182684E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.365100E+10 | 0.284098E+10 | 0.810018E+09 | 0.400054E+10 | 0.175303E+10 |
February | 0.322723E+10 | 0.235738E+10 | 0.869847E+09 | 0.361584E+10 | 0.147111E+10 |
March | 0.263293E+10 | 0.159177E+10 | 0.104116E+10 | 0.300949E+10 | 0.133372E+10 |
April | 0.198712E+10 | 0.815675E+09 | 0.117144E+10 | 0.235693E+10 | 0.928278E+09 |
May | 0.136942E+10 | 0.301247E+09 | 0.106817E+10 | 0.163773E+10 | 0.693988E+09 |
June | 0.112104E+10 | 0.138156E+09 | 0.982887E+09 | 0.159030E+10 | 0.440709E+09 |
July | 0.128184E+10 | 0.204698E+09 | 0.107714E+10 | 0.197431E+10 | 0.298391E+09 |
August | 0.176263E+10 | 0.572943E+09 | 0.118968E+10 | 0.259626E+10 | 0.348880E+09 |
September | 0.235871E+10 | 0.131529E+10 | 0.104342E+10 | 0.322369E+10 | 0.594550E+09 |
October | 0.333456E+10 | 0.245589E+10 | 0.878675E+09 | 0.409281E+10 | 0.103235E+10 |
November | 0.359426E+10 | 0.275859E+10 | 0.835677E+09 | 0.406417E+10 | 0.139842E+10 |
December | 0.396123E+10 | 0.326760E+10 | 0.693629E+09 | 0.437373E+10 | 0.182684E+10 |
Annual Sum or Average | 0.302820E+11 | 0.186202E+11 | 0.116618E+11 | 0.365358E+11 | 0.121203E+11 |
Minimum of Months | 0.112104E+10 | 0.138156E+09 | 0.693629E+09 | 0.159030E+10 | 0.298391E+09 |
Maximum of Months | 0.396123E+10 | 0.326760E+10 | 0.118968E+10 | 0.437373E+10 | 0.182684E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.365100E+10 | 0.284098E+10 | 0.810018E+09 | 0.400053E+10 | 0.175303E+10 |
February | 0.322722E+10 | 0.235738E+10 | 0.869846E+09 | 0.361584E+10 | 0.147111E+10 |
March | 0.263293E+10 | 0.159177E+10 | 0.104116E+10 | 0.300948E+10 | 0.133372E+10 |
April | 0.198711E+10 | 0.815674E+09 | 0.117144E+10 | 0.235693E+10 | 0.928278E+09 |
May | 0.136942E+10 | 0.301246E+09 | 0.106817E+10 | 0.163773E+10 | 0.693987E+09 |
June | 0.112104E+10 | 0.138156E+09 | 0.982886E+09 | 0.159030E+10 | 0.440708E+09 |
July | 0.128184E+10 | 0.204698E+09 | 0.107714E+10 | 0.197431E+10 | 0.298390E+09 |
August | 0.176262E+10 | 0.572943E+09 | 0.118968E+10 | 0.259626E+10 | 0.348880E+09 |
September | 0.235871E+10 | 0.131528E+10 | 0.104342E+10 | 0.322369E+10 | 0.594549E+09 |
October | 0.333456E+10 | 0.245589E+10 | 0.878674E+09 | 0.409281E+10 | 0.103235E+10 |
November | 0.359426E+10 | 0.275858E+10 | 0.835676E+09 | 0.406416E+10 | 0.139842E+10 |
December | 0.396122E+10 | 0.326759E+10 | 0.693628E+09 | 0.437373E+10 | 0.182684E+10 |
Annual Sum or Average | 0.302819E+11 | 0.186202E+11 | 0.116617E+11 | 0.365358E+11 | 0.121203E+11 |
Minimum of Months | 0.112104E+10 | 0.138156E+09 | 0.693628E+09 | 0.159030E+10 | 0.298390E+09 |
Maximum of Months | 0.396122E+10 | 0.326759E+10 | 0.118968E+10 | 0.437373E+10 | 0.182684E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.365085E+10 | 0.284087E+10 | 0.809986E+09 | 0.400038E+10 | 0.175296E+10 |
February | 0.322710E+10 | 0.235728E+10 | 0.869812E+09 | 0.361569E+10 | 0.147105E+10 |
March | 0.263283E+10 | 0.159171E+10 | 0.104112E+10 | 0.300937E+10 | 0.133366E+10 |
April | 0.198704E+10 | 0.815642E+09 | 0.117139E+10 | 0.235684E+10 | 0.928240E+09 |
May | 0.136936E+10 | 0.301234E+09 | 0.106813E+10 | 0.163766E+10 | 0.693960E+09 |
June | 0.112100E+10 | 0.138151E+09 | 0.982847E+09 | 0.159024E+10 | 0.440691E+09 |
July | 0.128179E+10 | 0.204690E+09 | 0.107710E+10 | 0.197423E+10 | 0.298379E+09 |
August | 0.176255E+10 | 0.572920E+09 | 0.118963E+10 | 0.259615E+10 | 0.348866E+09 |
September | 0.235861E+10 | 0.131523E+10 | 0.104338E+10 | 0.322356E+10 | 0.594526E+09 |
October | 0.333443E+10 | 0.245579E+10 | 0.878640E+09 | 0.409265E+10 | 0.103231E+10 |
November | 0.359412E+10 | 0.275847E+10 | 0.835643E+09 | 0.406401E+10 | 0.139836E+10 |
December | 0.396107E+10 | 0.326747E+10 | 0.693601E+09 | 0.437356E+10 | 0.182677E+10 |
Annual Sum or Average | 0.302807E+11 | 0.186195E+11 | 0.116613E+11 | 0.365343E+11 | 0.121198E+11 |
Minimum of Months | 0.112100E+10 | 0.138151E+09 | 0.693601E+09 | 0.159024E+10 | 0.298379E+09 |
Maximum of Months | 0.396107E+10 | 0.326747E+10 | 0.118963E+10 | 0.437356E+10 | 0.182677E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.156742E+10 | 0.893847E+09 | 0.673568E+09 | 0.138063E+10 | 0.219078E+10 |
February | 0.182252E+10 | 0.105282E+10 | 0.769704E+09 | 0.172912E+10 | 0.184975E+10 |
March | 0.225364E+10 | 0.119966E+10 | 0.105398E+10 | 0.226888E+10 | 0.167188E+10 |
April | 0.278354E+10 | 0.148141E+10 | 0.130212E+10 | 0.304924E+10 | 0.115496E+10 |
May | 0.272717E+10 | 0.140523E+10 | 0.132194E+10 | 0.322385E+10 | 0.837633E+09 |
June | 0.282921E+10 | 0.157867E+10 | 0.125054E+10 | 0.376848E+10 | 0.576249E+09 |
July | 0.263692E+10 | 0.129048E+10 | 0.134645E+10 | 0.366394E+10 | 0.408407E+09 |
August | 0.269447E+10 | 0.124630E+10 | 0.144817E+10 | 0.360509E+10 | 0.485003E+09 |
September | 0.235523E+10 | 0.124040E+10 | 0.111483E+10 | 0.299853E+10 | 0.716268E+09 |
October | 0.222654E+10 | 0.138388E+10 | 0.842665E+09 | 0.250124E+10 | 0.130926E+10 |
November | 0.169144E+10 | 0.995115E+09 | 0.696330E+09 | 0.156884E+10 | 0.180656E+10 |
December | 0.151151E+10 | 0.947881E+09 | 0.563633E+09 | 0.128728E+10 | 0.244099E+10 |
Annual Sum or Average | 0.270996E+11 | 0.147157E+11 | 0.123839E+11 | 0.310451E+11 | 0.154477E+11 |
Minimum of Months | 0.151151E+10 | 0.893847E+09 | 0.563633E+09 | 0.128728E+10 | 0.408407E+09 |
Maximum of Months | 0.282921E+10 | 0.157867E+10 | 0.144817E+10 | 0.376848E+10 | 0.244099E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.156742E+10 | 0.893847E+09 | 0.673568E+09 | 0.138063E+10 | 0.219078E+10 |
February | 0.182252E+10 | 0.105282E+10 | 0.769704E+09 | 0.172912E+10 | 0.184975E+10 |
March | 0.225364E+10 | 0.119966E+10 | 0.105398E+10 | 0.226888E+10 | 0.167188E+10 |
April | 0.278354E+10 | 0.148141E+10 | 0.130212E+10 | 0.304924E+10 | 0.115496E+10 |
May | 0.272717E+10 | 0.140523E+10 | 0.132194E+10 | 0.322385E+10 | 0.837633E+09 |
June | 0.282921E+10 | 0.157867E+10 | 0.125054E+10 | 0.376848E+10 | 0.576249E+09 |
July | 0.263692E+10 | 0.129048E+10 | 0.134645E+10 | 0.366394E+10 | 0.408407E+09 |
August | 0.269447E+10 | 0.124630E+10 | 0.144817E+10 | 0.360509E+10 | 0.485003E+09 |
September | 0.235523E+10 | 0.124040E+10 | 0.111483E+10 | 0.299853E+10 | 0.716268E+09 |
October | 0.222654E+10 | 0.138388E+10 | 0.842665E+09 | 0.250124E+10 | 0.130926E+10 |
November | 0.169144E+10 | 0.995115E+09 | 0.696330E+09 | 0.156884E+10 | 0.180656E+10 |
December | 0.151151E+10 | 0.947881E+09 | 0.563633E+09 | 0.128728E+10 | 0.244099E+10 |
Annual Sum or Average | 0.270996E+11 | 0.147157E+11 | 0.123839E+11 | 0.310451E+11 | 0.154477E+11 |
Minimum of Months | 0.151151E+10 | 0.893847E+09 | 0.563633E+09 | 0.128728E+10 | 0.408407E+09 |
Maximum of Months | 0.282921E+10 | 0.157867E+10 | 0.144817E+10 | 0.376848E+10 | 0.244099E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.156739E+10 | 0.893831E+09 | 0.673555E+09 | 0.138060E+10 | 0.219074E+10 |
February | 0.182249E+10 | 0.105280E+10 | 0.769690E+09 | 0.172908E+10 | 0.184971E+10 |
March | 0.225360E+10 | 0.119964E+10 | 0.105396E+10 | 0.226883E+10 | 0.167185E+10 |
April | 0.278349E+10 | 0.148138E+10 | 0.130210E+10 | 0.304919E+10 | 0.115494E+10 |
May | 0.272712E+10 | 0.140520E+10 | 0.132192E+10 | 0.322379E+10 | 0.837618E+09 |
June | 0.282916E+10 | 0.157864E+10 | 0.125052E+10 | 0.376841E+10 | 0.576238E+09 |
July | 0.263688E+10 | 0.129045E+10 | 0.134642E+10 | 0.366387E+10 | 0.408400E+09 |
August | 0.269442E+10 | 0.124628E+10 | 0.144814E+10 | 0.360502E+10 | 0.484994E+09 |
September | 0.235519E+10 | 0.124038E+10 | 0.111481E+10 | 0.299847E+10 | 0.716255E+09 |
October | 0.222650E+10 | 0.138385E+10 | 0.842649E+09 | 0.250119E+10 | 0.130924E+10 |
November | 0.169141E+10 | 0.995097E+09 | 0.696317E+09 | 0.156882E+10 | 0.180653E+10 |
December | 0.151149E+10 | 0.947863E+09 | 0.563623E+09 | 0.128726E+10 | 0.244094E+10 |
Annual Sum or Average | 0.270991E+11 | 0.147154E+11 | 0.123837E+11 | 0.310445E+11 | 0.154475E+11 |
Minimum of Months | 0.151149E+10 | 0.893831E+09 | 0.563623E+09 | 0.128726E+10 | 0.408400E+09 |
Maximum of Months | 0.282916E+10 | 0.157864E+10 | 0.144814E+10 | 0.376841E+10 | 0.244094E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.246919E+10 | 0.00 | 0.246919E+10 | 0.530949E+09 | 0.890612E+10 |
February | 0.278742E+10 | 0.00 | 0.278742E+10 | 0.999541E+09 | 0.728690E+10 |
March | 0.389269E+10 | 0.00 | 0.389269E+10 | 0.234280E+10 | 0.637826E+10 |
April | 0.477930E+10 | 40918336.57 | 0.473838E+10 | 0.369961E+10 | 0.411345E+10 |
May | 0.536831E+10 | 0.346112E+09 | 0.502220E+10 | 0.531628E+10 | 0.311236E+10 |
June | 0.590308E+10 | 0.966028E+09 | 0.493705E+10 | 0.799700E+10 | 0.201988E+10 |
July | 0.559870E+10 | 0.465980E+09 | 0.513272E+10 | 0.823124E+10 | 0.142357E+10 |
August | 0.519373E+10 | 0.116277E+09 | 0.507745E+10 | 0.696921E+10 | 0.160562E+10 |
September | 0.401940E+10 | 1031583.39 | 0.401837E+10 | 0.458011E+10 | 0.272576E+10 |
October | 0.309925E+10 | 0.00 | 0.309925E+10 | 0.217228E+10 | 0.497151E+10 |
November | 0.254710E+10 | 0.00 | 0.254710E+10 | 0.731876E+09 | 0.686061E+10 |
December | 0.210165E+10 | 0.00 | 0.210165E+10 | 0.169566E+09 | 0.934009E+10 |
Annual Sum or Average | 0.477598E+11 | 0.193635E+10 | 0.458235E+11 | 0.437405E+11 | 0.587441E+11 |
Minimum of Months | 0.210165E+10 | 0.00 | 0.210165E+10 | 0.169566E+09 | 0.142357E+10 |
Maximum of Months | 0.590308E+10 | 0.966028E+09 | 0.513272E+10 | 0.823124E+10 | 0.934009E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.455877E+10 | 0.254878E+10 | 0.200999E+10 | 0.371730E+10 | 0.549282E+10 |
February | 0.500280E+10 | 0.269705E+10 | 0.230575E+10 | 0.448677E+10 | 0.453218E+10 |
March | 0.730653E+10 | 0.415363E+10 | 0.315290E+10 | 0.743860E+10 | 0.399457E+10 |
April | 0.966021E+10 | 0.550337E+10 | 0.415684E+10 | 0.108813E+11 | 0.269532E+10 |
May | 0.952515E+10 | 0.542830E+10 | 0.409685E+10 | 0.113813E+11 | 0.212282E+10 |
June | 0.993759E+10 | 0.612203E+10 | 0.381556E+10 | 0.131469E+11 | 0.133624E+10 |
July | 0.950194E+10 | 0.543360E+10 | 0.406835E+10 | 0.131308E+11 | 0.962313E+09 |
August | 0.940281E+10 | 0.518395E+10 | 0.421886E+10 | 0.125860E+11 | 0.108320E+10 |
September | 0.757380E+10 | 0.423761E+10 | 0.333619E+10 | 0.955835E+10 | 0.175596E+10 |
October | 0.680644E+10 | 0.431842E+10 | 0.248802E+10 | 0.751120E+10 | 0.312454E+10 |
November | 0.514798E+10 | 0.302646E+10 | 0.212152E+10 | 0.474460E+10 | 0.431497E+10 |
December | 0.431036E+10 | 0.262325E+10 | 0.168711E+10 | 0.354841E+10 | 0.579424E+10 |
Annual Sum or Average | 0.887344E+11 | 0.512764E+11 | 0.374579E+11 | 0.102132E+12 | 0.372092E+11 |
Minimum of Months | 0.431036E+10 | 0.254878E+10 | 0.168711E+10 | 0.354841E+10 | 0.962313E+09 |
Maximum of Months | 0.993759E+10 | 0.612203E+10 | 0.421886E+10 | 0.131469E+11 | 0.579424E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.182548E+11 | 0.142047E+11 | 0.405004E+10 | 0.198579E+11 | 0.861358E+10 |
February | 0.161359E+11 | 0.117868E+11 | 0.434918E+10 | 0.179554E+11 | 0.718796E+10 |
March | 0.131645E+11 | 0.795876E+10 | 0.520576E+10 | 0.149659E+11 | 0.645805E+10 |
April | 0.993546E+10 | 0.407832E+10 | 0.585713E+10 | 0.117513E+11 | 0.444388E+10 |
May | 0.684700E+10 | 0.150621E+10 | 0.534079E+10 | 0.817610E+10 | 0.335115E+10 |
June | 0.560515E+10 | 0.690774E+09 | 0.491437E+10 | 0.799252E+10 | 0.213603E+10 |
July | 0.640912E+10 | 0.102348E+10 | 0.538565E+10 | 0.988806E+10 | 0.149438E+10 |
August | 0.881302E+10 | 0.286468E+10 | 0.594834E+10 | 0.129565E+11 | 0.175105E+10 |
September | 0.117934E+11 | 0.657635E+10 | 0.521705E+10 | 0.160044E+11 | 0.291912E+10 |
October | 0.166726E+11 | 0.122793E+11 | 0.439332E+10 | 0.203147E+11 | 0.506800E+10 |
November | 0.179711E+11 | 0.137928E+11 | 0.417833E+10 | 0.201973E+11 | 0.680170E+10 |
December | 0.198059E+11 | 0.163378E+11 | 0.346810E+10 | 0.217557E+11 | 0.883169E+10 |
Annual Sum or Average | 0.151408E+12 | 0.930999E+11 | 0.583081E+11 | 0.181816E+12 | 0.590566E+11 |
Minimum of Months | 0.560515E+10 | 0.690774E+09 | 0.346810E+10 | 0.799252E+10 | 0.149438E+10 |
Maximum of Months | 0.198059E+11 | 0.163378E+11 | 0.594834E+10 | 0.217557E+11 | 0.883169E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.470220E+10 | 0.268152E+10 | 0.202068E+10 | 0.426334E+10 | 0.599378E+10 |
February | 0.546750E+10 | 0.315841E+10 | 0.230909E+10 | 0.533316E+10 | 0.497080E+10 |
March | 0.676085E+10 | 0.359894E+10 | 0.316192E+10 | 0.699737E+10 | 0.441134E+10 |
April | 0.835052E+10 | 0.444419E+10 | 0.390633E+10 | 0.932103E+10 | 0.302213E+10 |
May | 0.818143E+10 | 0.421565E+10 | 0.396578E+10 | 0.972156E+10 | 0.233265E+10 |
June | 0.848755E+10 | 0.473597E+10 | 0.375159E+10 | 0.113773E+11 | 0.158786E+10 |
July | 0.791069E+10 | 0.387139E+10 | 0.403930E+10 | 0.110892E+11 | 0.111195E+10 |
August | 0.808333E+10 | 0.373887E+10 | 0.434446E+10 | 0.109455E+11 | 0.127736E+10 |
September | 0.706562E+10 | 0.372118E+10 | 0.334444E+10 | 0.903939E+10 | 0.198196E+10 |
October | 0.667956E+10 | 0.415159E+10 | 0.252797E+10 | 0.762775E+10 | 0.349899E+10 |
November | 0.507428E+10 | 0.298531E+10 | 0.208897E+10 | 0.489223E+10 | 0.464696E+10 |
December | 0.453449E+10 | 0.284361E+10 | 0.169088E+10 | 0.402882E+10 | 0.619140E+10 |
Annual Sum or Average | 0.812980E+11 | 0.441466E+11 | 0.371514E+11 | 0.946367E+11 | 0.410272E+11 |
Minimum of Months | 0.453449E+10 | 0.268152E+10 | 0.169088E+10 | 0.402882E+10 | 0.111195E+10 |
Maximum of Months | 0.848755E+10 | 0.473597E+10 | 0.434446E+10 | 0.113773E+11 | 0.619140E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.246919E+10 | 0.00 | 0.246919E+10 | 0.643824E+09 | 0.830704E+10 |
February | 0.278742E+10 | 0.00 | 0.278742E+10 | 0.111159E+10 | 0.682736E+10 |
March | 0.389269E+10 | 0.00 | 0.389269E+10 | 0.246880E+10 | 0.598491E+10 |
April | 0.477930E+10 | 40918336.57 | 0.473838E+10 | 0.376896E+10 | 0.390439E+10 |
May | 0.536831E+10 | 0.346112E+09 | 0.502220E+10 | 0.533315E+10 | 0.302199E+10 |
June | 0.590308E+10 | 0.966028E+09 | 0.493705E+10 | 0.795963E+10 | 0.199929E+10 |
July | 0.559870E+10 | 0.465980E+09 | 0.513272E+10 | 0.816080E+10 | 0.144019E+10 |
August | 0.519373E+10 | 0.116277E+09 | 0.507745E+10 | 0.691438E+10 | 0.160500E+10 |
September | 0.401940E+10 | 1031583.39 | 0.401837E+10 | 0.457263E+10 | 0.265131E+10 |
October | 0.309925E+10 | 0.00 | 0.309925E+10 | 0.225311E+10 | 0.465698E+10 |
November | 0.254710E+10 | 0.00 | 0.254710E+10 | 0.857087E+09 | 0.630576E+10 |
December | 0.210165E+10 | 0.00 | 0.210165E+10 | 0.232256E+09 | 0.866870E+10 |
Annual Sum or Average | 0.477598E+11 | 0.193635E+10 | 0.458235E+11 | 0.442762E+11 | 0.553729E+11 |
Minimum of Months | 0.210165E+10 | 0.00 | 0.210165E+10 | 0.232256E+09 | 0.144019E+10 |
Maximum of Months | 0.590308E+10 | 0.966028E+09 | 0.513272E+10 | 0.816080E+10 | 0.866870E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.455877E+10 | 0.254878E+10 | 0.200999E+10 | 0.385044E+10 | 0.514762E+10 |
February | 0.500280E+10 | 0.269705E+10 | 0.230575E+10 | 0.458210E+10 | 0.427585E+10 |
March | 0.730653E+10 | 0.415363E+10 | 0.315290E+10 | 0.749818E+10 | 0.380033E+10 |
April | 0.966021E+10 | 0.550337E+10 | 0.415684E+10 | 0.108883E+11 | 0.260295E+10 |
May | 0.952515E+10 | 0.542830E+10 | 0.409685E+10 | 0.113550E+11 | 0.208166E+10 |
June | 0.993759E+10 | 0.612203E+10 | 0.381556E+10 | 0.131010E+11 | 0.132997E+10 |
July | 0.950194E+10 | 0.543360E+10 | 0.406835E+10 | 0.130716E+11 | 0.978304E+09 |
August | 0.940281E+10 | 0.518395E+10 | 0.421886E+10 | 0.125340E+11 | 0.108889E+10 |
September | 0.757380E+10 | 0.423761E+10 | 0.333619E+10 | 0.953539E+10 | 0.172870E+10 |
October | 0.680644E+10 | 0.431842E+10 | 0.248802E+10 | 0.754566E+10 | 0.298295E+10 |
November | 0.514798E+10 | 0.302646E+10 | 0.212152E+10 | 0.484587E+10 | 0.402521E+10 |
December | 0.431036E+10 | 0.262325E+10 | 0.168711E+10 | 0.365100E+10 | 0.539415E+10 |
Annual Sum or Average | 0.887344E+11 | 0.512764E+11 | 0.374579E+11 | 0.102459E+12 | 0.354366E+11 |
Minimum of Months | 0.431036E+10 | 0.254878E+10 | 0.168711E+10 | 0.365100E+10 | 0.978304E+09 |
Maximum of Months | 0.993759E+10 | 0.612203E+10 | 0.421886E+10 | 0.131010E+11 | 0.539415E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.182548E+11 | 0.142047E+11 | 0.405004E+10 | 0.200394E+11 | 0.806382E+10 |
February | 0.161359E+11 | 0.117868E+11 | 0.434918E+10 | 0.180698E+11 | 0.676755E+10 |
March | 0.131645E+11 | 0.795876E+10 | 0.520576E+10 | 0.150459E+11 | 0.612672E+10 |
April | 0.993546E+10 | 0.407832E+10 | 0.585713E+10 | 0.117718E+11 | 0.425262E+10 |
May | 0.684700E+10 | 0.150621E+10 | 0.534079E+10 | 0.816656E+10 | 0.325323E+10 |
June | 0.560515E+10 | 0.690774E+09 | 0.491437E+10 | 0.795181E+10 | 0.210608E+10 |
July | 0.640912E+10 | 0.102348E+10 | 0.538565E+10 | 0.981382E+10 | 0.151020E+10 |
August | 0.881302E+10 | 0.286468E+10 | 0.594834E+10 | 0.128883E+11 | 0.174951E+10 |
September | 0.117934E+11 | 0.657635E+10 | 0.521705E+10 | 0.159742E+11 | 0.285865E+10 |
October | 0.166726E+11 | 0.122793E+11 | 0.439332E+10 | 0.203775E+11 | 0.483033E+10 |
November | 0.179711E+11 | 0.137928E+11 | 0.417833E+10 | 0.203420E+11 | 0.636258E+10 |
December | 0.198059E+11 | 0.163378E+11 | 0.346810E+10 | 0.219098E+11 | 0.822039E+10 |
Annual Sum or Average | 0.151408E+12 | 0.930999E+11 | 0.583081E+11 | 0.182351E+12 | 0.561017E+11 |
Minimum of Months | 0.560515E+10 | 0.690774E+09 | 0.346810E+10 | 0.795181E+10 | 0.151020E+10 |
Maximum of Months | 0.198059E+11 | 0.163378E+11 | 0.594834E+10 | 0.219098E+11 | 0.822039E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.470220E+10 | 0.268152E+10 | 0.202068E+10 | 0.432130E+10 | 0.564900E+10 |
February | 0.546750E+10 | 0.315841E+10 | 0.230909E+10 | 0.536959E+10 | 0.471981E+10 |
March | 0.676085E+10 | 0.359894E+10 | 0.316192E+10 | 0.703261E+10 | 0.420479E+10 |
April | 0.835052E+10 | 0.444419E+10 | 0.390633E+10 | 0.932734E+10 | 0.290962E+10 |
May | 0.818143E+10 | 0.421565E+10 | 0.396578E+10 | 0.970754E+10 | 0.227373E+10 |
June | 0.848755E+10 | 0.473597E+10 | 0.375159E+10 | 0.113431E+11 | 0.156876E+10 |
July | 0.791069E+10 | 0.387139E+10 | 0.403930E+10 | 0.110363E+11 | 0.111835E+10 |
August | 0.808333E+10 | 0.373887E+10 | 0.434446E+10 | 0.109019E+11 | 0.127322E+10 |
September | 0.706562E+10 | 0.372118E+10 | 0.334444E+10 | 0.902251E+10 | 0.194150E+10 |
October | 0.667956E+10 | 0.415159E+10 | 0.252797E+10 | 0.764645E+10 | 0.334033E+10 |
November | 0.507428E+10 | 0.298531E+10 | 0.208897E+10 | 0.494269E+10 | 0.435803E+10 |
December | 0.453449E+10 | 0.284361E+10 | 0.169088E+10 | 0.406775E+10 | 0.581989E+10 |
Annual Sum or Average | 0.812980E+11 | 0.441466E+11 | 0.371514E+11 | 0.947190E+11 | 0.391770E+11 |
Minimum of Months | 0.453449E+10 | 0.268152E+10 | 0.169088E+10 | 0.406775E+10 | 0.111835E+10 |
Maximum of Months | 0.848755E+10 | 0.473597E+10 | 0.434446E+10 | 0.113431E+11 | 0.581989E+10 |
Report: WindowZoneSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 130.75 | 3670.46 | 921.89 | 0.00 | 921.89 | 0.00 | 0.00 |
February | 327.01 | 3320.98 | 1152.21 | 0.00 | 1152.21 | 0.00 | 0.00 |
March | 795.98 | 2610.37 | 1453.37 | 0.00 | 1453.37 | 0.00 | 0.00 |
April | 1364.28 | 1733.99 | 1843.87 | 15.79 | 1828.09 | 0.00 | 0.00 |
May | 1955.89 | 1222.99 | 2004.31 | 129.22 | 1875.08 | 0.00 | 0.00 |
June | 3066.21 | 804.55 | 2277.43 | 372.70 | 1904.73 | 0.00 | 0.00 |
July | 3055.10 | 537.75 | 2090.32 | 173.98 | 1916.35 | 0.00 | 0.00 |
August | 2577.27 | 613.90 | 1939.12 | 43.41 | 1895.71 | 0.00 | 0.00 |
September | 1743.82 | 1111.71 | 1550.70 | 0.40 | 1550.30 | 0.00 | 0.00 |
October | 755.30 | 2035.59 | 1157.13 | 0.00 | 1157.13 | 0.00 | 0.00 |
November | 212.49 | 2990.57 | 982.68 | 0.00 | 982.68 | 0.00 | 0.00 |
December | 26.25 | 3963.67 | 784.67 | 0.00 | 784.67 | 0.00 | 0.00 |
Annual Sum or Average | 1339.60 | 2045.23 | 1514.46 | 61.40 | 1453.06 | 0.00 | 0.00 |
Minimum of Months | 26.25 | 537.75 | 784.67 | 0.00 | 784.67 | 0.00 | 0.00 |
Maximum of Months | 3066.21 | 3963.67 | 2277.43 | 372.70 | 1916.35 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1350.72 | 2206.11 | 1702.06 | 951.61 | 750.45 | 0.00 | 0.00 |
February | 1824.26 | 2005.61 | 2067.96 | 1114.85 | 953.11 | 0.00 | 0.00 |
March | 2772.68 | 1576.52 | 2727.96 | 1550.79 | 1177.16 | 0.00 | 0.00 |
April | 4216.71 | 1078.43 | 3726.95 | 2123.22 | 1603.72 | 0.00 | 0.00 |
May | 4274.30 | 819.65 | 3556.30 | 2026.70 | 1529.59 | 0.00 | 0.00 |
June | 5099.88 | 515.98 | 3833.96 | 2361.90 | 1472.06 | 0.00 | 0.00 |
July | 4934.34 | 330.95 | 3547.63 | 2028.68 | 1518.95 | 0.00 | 0.00 |
August | 4733.25 | 368.86 | 3510.62 | 1935.47 | 1575.15 | 0.00 | 0.00 |
September | 3703.80 | 700.27 | 2922.00 | 1634.89 | 1287.12 | 0.00 | 0.00 |
October | 2804.10 | 1231.19 | 2541.24 | 1612.32 | 928.92 | 0.00 | 0.00 |
November | 1810.26 | 1798.53 | 1986.11 | 1167.62 | 818.49 | 0.00 | 0.00 |
December | 1297.42 | 2351.06 | 1609.31 | 979.41 | 629.90 | 0.00 | 0.00 |
Annual Sum or Average | 3241.56 | 1244.84 | 2813.76 | 1625.97 | 1187.79 | 0.00 | 0.00 |
Minimum of Months | 1297.42 | 330.95 | 1609.31 | 951.61 | 629.90 | 0.00 | 0.00 |
Maximum of Months | 5099.88 | 2351.06 | 3833.96 | 2361.90 | 1603.72 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 7468.09 | 3272.51 | 6815.58 | 5303.46 | 1512.12 | 0.00 | 0.00 |
February | 7473.15 | 3040.45 | 6669.97 | 4872.19 | 1797.78 | 0.00 | 0.00 |
March | 5618.02 | 2489.75 | 4915.08 | 2971.47 | 1943.61 | 0.00 | 0.00 |
April | 4546.52 | 1790.64 | 3833.14 | 1573.43 | 2259.70 | 0.00 | 0.00 |
May | 3057.26 | 1295.52 | 2556.39 | 562.36 | 1994.03 | 0.00 | 0.00 |
June | 3067.69 | 850.13 | 2162.49 | 266.50 | 1895.98 | 0.00 | 0.00 |
July | 3685.58 | 557.03 | 2392.90 | 382.12 | 2010.78 | 0.00 | 0.00 |
August | 4846.62 | 651.28 | 3290.42 | 1069.55 | 2220.86 | 0.00 | 0.00 |
September | 6218.49 | 1146.88 | 4549.94 | 2537.18 | 2012.76 | 0.00 | 0.00 |
October | 7640.34 | 1927.16 | 6224.87 | 4584.58 | 1640.28 | 0.00 | 0.00 |
November | 7839.76 | 2697.54 | 6933.32 | 5321.30 | 1612.02 | 0.00 | 0.00 |
December | 8164.75 | 3410.30 | 7394.70 | 6099.86 | 1294.85 | 0.00 | 0.00 |
Annual Sum or Average | 5792.66 | 1921.64 | 4801.13 | 2952.19 | 1848.94 | 0.00 | 0.00 |
Minimum of Months | 3057.26 | 557.03 | 2162.49 | 266.50 | 1294.85 | 0.00 | 0.00 |
Maximum of Months | 8164.75 | 3410.30 | 7394.70 | 6099.86 | 2259.70 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1546.39 | 2453.81 | 1755.61 | 1001.17 | 754.44 | 0.00 | 0.00 |
February | 2144.23 | 2293.82 | 2260.05 | 1305.57 | 954.49 | 0.00 | 0.00 |
March | 2541.29 | 1872.61 | 2524.22 | 1343.69 | 1180.53 | 0.00 | 0.00 |
April | 3529.19 | 1336.75 | 3221.67 | 1714.59 | 1507.08 | 0.00 | 0.00 |
May | 3610.92 | 938.20 | 3054.61 | 1573.95 | 1480.66 | 0.00 | 0.00 |
June | 4361.64 | 666.95 | 3274.53 | 1827.16 | 1447.38 | 0.00 | 0.00 |
July | 4103.85 | 457.44 | 2953.53 | 1445.42 | 1508.11 | 0.00 | 0.00 |
August | 4037.93 | 543.23 | 3017.98 | 1395.94 | 1622.04 | 0.00 | 0.00 |
September | 3470.50 | 829.01 | 2725.94 | 1435.65 | 1290.30 | 0.00 | 0.00 |
October | 2801.55 | 1466.46 | 2493.87 | 1550.03 | 943.84 | 0.00 | 0.00 |
November | 1815.78 | 2090.92 | 1957.68 | 1151.75 | 805.93 | 0.00 | 0.00 |
December | 1441.84 | 2734.06 | 1692.99 | 1061.69 | 631.31 | 0.00 | 0.00 |
Annual Sum or Average | 2953.28 | 1469.52 | 2577.95 | 1399.89 | 1178.07 | 0.00 | 0.00 |
Minimum of Months | 1441.84 | 457.44 | 1692.99 | 1001.17 | 631.31 | 0.00 | 0.00 |
Maximum of Months | 4361.64 | 2734.06 | 3274.53 | 1827.16 | 1622.04 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 198.23 | 3325.17 | 921.89 | 0.00 | 921.89 | 0.00 | 0.00 |
February | 413.17 | 3012.11 | 1152.21 | 0.00 | 1152.21 | 0.00 | 0.00 |
March | 874.70 | 2381.37 | 1453.36 | 0.00 | 1453.36 | 0.00 | 0.00 |
April | 1427.32 | 1586.98 | 1843.87 | 15.79 | 1828.08 | 0.00 | 0.00 |
May | 1984.87 | 1162.02 | 2004.30 | 129.22 | 1875.07 | 0.00 | 0.00 |
June | 3085.26 | 779.27 | 2277.42 | 372.70 | 1904.73 | 0.00 | 0.00 |
July | 3073.19 | 531.50 | 2090.32 | 173.98 | 1916.34 | 0.00 | 0.00 |
August | 2602.00 | 599.47 | 1939.12 | 43.41 | 1895.70 | 0.00 | 0.00 |
September | 1767.02 | 1051.60 | 1550.69 | 0.40 | 1550.30 | 0.00 | 0.00 |
October | 811.04 | 1856.15 | 1157.13 | 0.00 | 1157.13 | 0.00 | 0.00 |
November | 282.36 | 2646.84 | 982.68 | 0.00 | 982.68 | 0.00 | 0.00 |
December | 63.31 | 3487.19 | 784.67 | 0.00 | 784.67 | 0.00 | 0.00 |
Annual Sum or Average | 1387.00 | 1862.76 | 1514.45 | 61.40 | 1453.05 | 0.00 | 0.00 |
Minimum of Months | 63.31 | 531.50 | 784.67 | 0.00 | 784.67 | 0.00 | 0.00 |
Maximum of Months | 3085.26 | 3487.19 | 2277.42 | 372.70 | 1916.34 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1387.88 | 2050.78 | 1702.05 | 951.61 | 750.44 | 0.00 | 0.00 |
February | 1854.65 | 1873.42 | 2067.96 | 1114.85 | 953.11 | 0.00 | 0.00 |
March | 2777.25 | 1491.40 | 2727.95 | 1550.79 | 1177.16 | 0.00 | 0.00 |
April | 4198.04 | 1039.86 | 3726.93 | 2123.21 | 1603.72 | 0.00 | 0.00 |
May | 4249.29 | 792.57 | 3556.28 | 2026.70 | 1529.59 | 0.00 | 0.00 |
June | 5072.13 | 515.52 | 3833.95 | 2361.89 | 1472.05 | 0.00 | 0.00 |
July | 4902.49 | 359.29 | 3547.62 | 2028.67 | 1518.95 | 0.00 | 0.00 |
August | 4699.09 | 404.42 | 3510.61 | 1935.46 | 1575.14 | 0.00 | 0.00 |
September | 3687.63 | 677.46 | 2921.99 | 1634.88 | 1287.11 | 0.00 | 0.00 |
October | 2804.36 | 1166.57 | 2541.23 | 1612.31 | 928.92 | 0.00 | 0.00 |
November | 1830.48 | 1664.72 | 1986.10 | 1167.61 | 818.49 | 0.00 | 0.00 |
December | 1324.83 | 2163.32 | 1609.31 | 979.41 | 629.90 | 0.00 | 0.00 |
Annual Sum or Average | 3238.57 | 1179.90 | 2813.75 | 1625.97 | 1187.78 | 0.00 | 0.00 |
Minimum of Months | 1324.83 | 359.29 | 1609.31 | 951.61 | 629.90 | 0.00 | 0.00 |
Maximum of Months | 5072.13 | 2163.32 | 3833.95 | 2361.89 | 1603.72 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 7414.09 | 3215.94 | 6815.55 | 5303.44 | 1512.11 | 0.00 | 0.00 |
February | 7422.03 | 2971.21 | 6669.95 | 4872.17 | 1797.78 | 0.00 | 0.00 |
March | 5587.64 | 2411.16 | 4915.07 | 2971.46 | 1943.61 | 0.00 | 0.00 |
April | 4533.69 | 1714.46 | 3833.12 | 1573.43 | 2259.70 | 0.00 | 0.00 |
May | 3052.61 | 1251.18 | 2556.38 | 562.36 | 1994.02 | 0.00 | 0.00 |
June | 3083.54 | 824.08 | 2162.48 | 266.50 | 1895.98 | 0.00 | 0.00 |
July | 3691.78 | 557.94 | 2392.89 | 382.12 | 2010.77 | 0.00 | 0.00 |
August | 4837.41 | 653.77 | 3290.41 | 1069.55 | 2220.86 | 0.00 | 0.00 |
September | 6174.52 | 1126.20 | 4549.92 | 2537.17 | 2012.75 | 0.00 | 0.00 |
October | 7584.66 | 1892.18 | 6224.84 | 4584.56 | 1640.28 | 0.00 | 0.00 |
November | 7792.18 | 2624.11 | 6933.29 | 5321.28 | 1612.01 | 0.00 | 0.00 |
December | 8122.64 | 3297.38 | 7394.68 | 6099.83 | 1294.84 | 0.00 | 0.00 |
Annual Sum or Average | 5765.34 | 1872.67 | 4801.12 | 2952.18 | 1848.94 | 0.00 | 0.00 |
Minimum of Months | 3052.61 | 557.94 | 2162.48 | 266.50 | 1294.84 | 0.00 | 0.00 |
Maximum of Months | 8122.64 | 3297.38 | 7394.68 | 6099.83 | 2259.70 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1591.75 | 2237.82 | 1755.60 | 1001.16 | 754.44 | 0.00 | 0.00 |
February | 2204.51 | 2054.73 | 2260.05 | 1305.56 | 954.48 | 0.00 | 0.00 |
March | 2612.52 | 1647.01 | 2524.21 | 1343.69 | 1180.52 | 0.00 | 0.00 |
April | 3596.08 | 1165.95 | 3221.65 | 1714.58 | 1507.07 | 0.00 | 0.00 |
May | 3629.61 | 870.91 | 3054.60 | 1573.94 | 1480.65 | 0.00 | 0.00 |
June | 4389.38 | 612.60 | 3274.52 | 1827.15 | 1447.37 | 0.00 | 0.00 |
July | 4140.23 | 415.15 | 2953.51 | 1445.41 | 1508.10 | 0.00 | 0.00 |
August | 4086.60 | 476.91 | 3017.97 | 1395.93 | 1622.03 | 0.00 | 0.00 |
September | 3487.42 | 764.64 | 2725.93 | 1435.64 | 1290.29 | 0.00 | 0.00 |
October | 2847.88 | 1306.37 | 2493.86 | 1550.03 | 943.84 | 0.00 | 0.00 |
November | 1887.43 | 1792.81 | 1957.67 | 1151.74 | 805.93 | 0.00 | 0.00 |
December | 1504.19 | 2311.61 | 1692.99 | 1061.68 | 631.30 | 0.00 | 0.00 |
Annual Sum or Average | 3000.91 | 1300.96 | 2577.94 | 1399.88 | 1178.06 | 0.00 | 0.00 |
Minimum of Months | 1504.19 | 415.15 | 1692.99 | 1001.16 | 631.30 | 0.00 | 0.00 |
Maximum of Months | 4389.38 | 2311.61 | 3274.52 | 1827.15 | 1622.03 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 240.38 | 3101.50 | 921.89 | 0.00 | 921.89 | 0.00 | 0.00 |
February | 459.49 | 2822.16 | 1152.21 | 0.00 | 1152.21 | 0.00 | 0.00 |
March | 921.75 | 2234.51 | 1453.36 | 0.00 | 1453.36 | 0.00 | 0.00 |
April | 1454.07 | 1506.32 | 1843.87 | 15.79 | 1828.08 | 0.00 | 0.00 |
May | 1991.17 | 1128.28 | 2004.30 | 129.22 | 1875.07 | 0.00 | 0.00 |
June | 3070.85 | 771.33 | 2277.42 | 372.70 | 1904.73 | 0.00 | 0.00 |
July | 3046.89 | 537.71 | 2090.32 | 173.98 | 1916.34 | 0.00 | 0.00 |
August | 2581.53 | 599.24 | 1939.12 | 43.41 | 1895.70 | 0.00 | 0.00 |
September | 1764.13 | 1022.88 | 1550.69 | 0.40 | 1550.30 | 0.00 | 0.00 |
October | 841.22 | 1738.72 | 1157.13 | 0.00 | 1157.13 | 0.00 | 0.00 |
November | 330.67 | 2432.78 | 982.68 | 0.00 | 982.68 | 0.00 | 0.00 |
December | 86.71 | 3236.52 | 784.67 | 0.00 | 784.67 | 0.00 | 0.00 |
Annual Sum or Average | 1403.99 | 1755.86 | 1514.45 | 61.40 | 1453.05 | 0.00 | 0.00 |
Minimum of Months | 86.71 | 537.71 | 784.67 | 0.00 | 784.67 | 0.00 | 0.00 |
Maximum of Months | 3070.85 | 3236.52 | 2277.42 | 372.70 | 1916.34 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1437.59 | 1921.90 | 1702.05 | 951.61 | 750.44 | 0.00 | 0.00 |
February | 1894.06 | 1767.46 | 2067.96 | 1114.85 | 953.11 | 0.00 | 0.00 |
March | 2799.50 | 1418.88 | 2727.95 | 1550.79 | 1177.16 | 0.00 | 0.00 |
April | 4200.72 | 1004.23 | 3726.93 | 2123.21 | 1603.72 | 0.00 | 0.00 |
May | 4239.47 | 777.20 | 3556.28 | 2026.70 | 1529.59 | 0.00 | 0.00 |
June | 5054.41 | 513.10 | 3833.95 | 2361.89 | 1472.05 | 0.00 | 0.00 |
July | 4880.39 | 365.26 | 3547.62 | 2028.67 | 1518.95 | 0.00 | 0.00 |
August | 4679.66 | 406.55 | 3510.61 | 1935.46 | 1575.14 | 0.00 | 0.00 |
September | 3678.78 | 666.94 | 2921.99 | 1634.88 | 1287.11 | 0.00 | 0.00 |
October | 2817.23 | 1113.70 | 2541.23 | 1612.31 | 928.92 | 0.00 | 0.00 |
November | 1869.55 | 1552.93 | 1986.10 | 1167.61 | 818.49 | 0.00 | 0.00 |
December | 1363.13 | 2013.94 | 1609.31 | 979.41 | 629.90 | 0.00 | 0.00 |
Annual Sum or Average | 3248.94 | 1123.69 | 2813.75 | 1625.97 | 1187.78 | 0.00 | 0.00 |
Minimum of Months | 1363.13 | 365.26 | 1609.31 | 951.61 | 629.90 | 0.00 | 0.00 |
Maximum of Months | 5054.41 | 2013.94 | 3833.95 | 2361.89 | 1603.72 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 7481.85 | 3010.69 | 6815.55 | 5303.44 | 1512.11 | 0.00 | 0.00 |
February | 7469.35 | 2797.43 | 6669.95 | 4872.17 | 1797.78 | 0.00 | 0.00 |
March | 5617.49 | 2287.45 | 4915.07 | 2971.46 | 1943.61 | 0.00 | 0.00 |
April | 4541.61 | 1640.67 | 3833.12 | 1573.43 | 2259.70 | 0.00 | 0.00 |
May | 3049.04 | 1214.62 | 2556.38 | 562.36 | 1994.02 | 0.00 | 0.00 |
June | 3067.83 | 812.53 | 2162.48 | 266.50 | 1895.98 | 0.00 | 0.00 |
July | 3664.06 | 563.84 | 2392.89 | 382.12 | 2010.77 | 0.00 | 0.00 |
August | 4811.92 | 653.19 | 3290.41 | 1069.55 | 2220.86 | 0.00 | 0.00 |
September | 6162.89 | 1102.88 | 4549.92 | 2537.17 | 2012.75 | 0.00 | 0.00 |
October | 7608.09 | 1803.44 | 6224.84 | 4584.56 | 1640.28 | 0.00 | 0.00 |
November | 7848.01 | 2454.70 | 6933.29 | 5321.28 | 1612.01 | 0.00 | 0.00 |
December | 8180.17 | 3069.14 | 7394.68 | 6099.83 | 1294.84 | 0.00 | 0.00 |
Annual Sum or Average | 5782.31 | 1778.97 | 4801.12 | 2952.18 | 1848.94 | 0.00 | 0.00 |
Minimum of Months | 3049.04 | 563.84 | 2162.48 | 266.50 | 1294.84 | 0.00 | 0.00 |
Maximum of Months | 8180.17 | 3069.14 | 7394.68 | 6099.83 | 2259.70 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1613.39 | 2109.09 | 1755.60 | 1001.16 | 754.44 | 0.00 | 0.00 |
February | 2219.57 | 1950.98 | 2260.05 | 1305.56 | 954.48 | 0.00 | 0.00 |
March | 2625.68 | 1569.89 | 2524.21 | 1343.69 | 1180.52 | 0.00 | 0.00 |
April | 3598.51 | 1122.54 | 3221.65 | 1714.58 | 1507.07 | 0.00 | 0.00 |
May | 3624.38 | 848.91 | 3054.60 | 1573.94 | 1480.65 | 0.00 | 0.00 |
June | 4376.19 | 605.23 | 3274.52 | 1827.15 | 1447.37 | 0.00 | 0.00 |
July | 4120.48 | 417.55 | 2953.51 | 1445.41 | 1508.10 | 0.00 | 0.00 |
August | 4070.29 | 475.37 | 3017.97 | 1395.93 | 1622.03 | 0.00 | 0.00 |
September | 3480.91 | 749.04 | 2725.93 | 1435.64 | 1290.29 | 0.00 | 0.00 |
October | 2854.86 | 1247.14 | 2493.86 | 1550.03 | 943.84 | 0.00 | 0.00 |
November | 1906.90 | 1681.34 | 1957.67 | 1151.74 | 805.93 | 0.00 | 0.00 |
December | 1518.72 | 2172.90 | 1692.99 | 1061.68 | 631.30 | 0.00 | 0.00 |
Annual Sum or Average | 3003.52 | 1242.30 | 2577.94 | 1399.88 | 1178.06 | 0.00 | 0.00 |
Minimum of Months | 1518.72 | 417.55 | 1692.99 | 1001.16 | 631.30 | 0.00 | 0.00 |
Maximum of Months | 4376.19 | 2172.90 | 3274.52 | 1827.15 | 1622.03 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.350203E+09 | 0.983097E+10 | 0.246920E+10 | 0.00 | 0.246920E+10 | 0.00 | 0.00 |
February | 0.791091E+09 | 0.803411E+10 | 0.278743E+10 | 0.00 | 0.278743E+10 | 0.00 | 0.00 |
March | 0.213196E+10 | 0.699161E+10 | 0.389270E+10 | 0.00 | 0.389270E+10 | 0.00 | 0.00 |
April | 0.353622E+10 | 0.449451E+10 | 0.477932E+10 | 40918481.87 | 0.473840E+10 | 0.00 | 0.00 |
May | 0.523866E+10 | 0.327566E+10 | 0.536833E+10 | 0.346114E+09 | 0.502222E+10 | 0.00 | 0.00 |
June | 0.794762E+10 | 0.208538E+10 | 0.590310E+10 | 0.966031E+09 | 0.493707E+10 | 0.00 | 0.00 |
July | 0.818278E+10 | 0.144030E+10 | 0.559873E+10 | 0.465982E+09 | 0.513274E+10 | 0.00 | 0.00 |
August | 0.690297E+10 | 0.164428E+10 | 0.519375E+10 | 0.116277E+09 | 0.507747E+10 | 0.00 | 0.00 |
September | 0.451998E+10 | 0.288156E+10 | 0.401941E+10 | 1031587.06 | 0.401838E+10 | 0.00 | 0.00 |
October | 0.202301E+10 | 0.545213E+10 | 0.309926E+10 | 0.00 | 0.309926E+10 | 0.00 | 0.00 |
November | 0.550772E+09 | 0.775156E+10 | 0.254711E+10 | 0.00 | 0.254711E+10 | 0.00 | 0.00 |
December | 70319218.36 | 0.106163E+11 | 0.210166E+10 | 0.00 | 0.210166E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.422456E+11 | 0.644984E+11 | 0.477600E+11 | 0.193635E+10 | 0.458236E+11 | 0.00 | 0.00 |
Minimum of Months | 70319218.36 | 0.144030E+10 | 0.210166E+10 | 0.00 | 0.210166E+10 | 0.00 | 0.00 |
Maximum of Months | 0.818278E+10 | 0.106163E+11 | 0.590310E+10 | 0.966031E+09 | 0.513274E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.361777E+10 | 0.590885E+10 | 0.455879E+10 | 0.254879E+10 | 0.200999E+10 | 0.00 | 0.00 |
February | 0.441326E+10 | 0.485197E+10 | 0.500282E+10 | 0.269706E+10 | 0.230576E+10 | 0.00 | 0.00 |
March | 0.742636E+10 | 0.422255E+10 | 0.730656E+10 | 0.415365E+10 | 0.315292E+10 | 0.00 | 0.00 |
April | 0.109297E+11 | 0.279529E+10 | 0.966025E+10 | 0.550339E+10 | 0.415685E+10 | 0.00 | 0.00 |
May | 0.114483E+11 | 0.219534E+10 | 0.952519E+10 | 0.542833E+10 | 0.409686E+10 | 0.00 | 0.00 |
June | 0.132189E+11 | 0.133742E+10 | 0.993763E+10 | 0.612205E+10 | 0.381557E+10 | 0.00 | 0.00 |
July | 0.132161E+11 | 0.886415E+09 | 0.950198E+10 | 0.543362E+10 | 0.406836E+10 | 0.00 | 0.00 |
August | 0.126775E+11 | 0.987952E+09 | 0.940285E+10 | 0.518397E+10 | 0.421888E+10 | 0.00 | 0.00 |
September | 0.960025E+10 | 0.181510E+10 | 0.757383E+10 | 0.423763E+10 | 0.333621E+10 | 0.00 | 0.00 |
October | 0.751050E+10 | 0.329763E+10 | 0.680647E+10 | 0.431844E+10 | 0.248803E+10 | 0.00 | 0.00 |
November | 0.469219E+10 | 0.466178E+10 | 0.514800E+10 | 0.302647E+10 | 0.212153E+10 | 0.00 | 0.00 |
December | 0.347502E+10 | 0.629708E+10 | 0.431038E+10 | 0.262326E+10 | 0.168712E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.102226E+12 | 0.392574E+11 | 0.887347E+11 | 0.512767E+11 | 0.374581E+11 | 0.00 | 0.00 |
Minimum of Months | 0.347502E+10 | 0.886415E+09 | 0.431038E+10 | 0.254879E+10 | 0.168712E+10 | 0.00 | 0.00 |
Maximum of Months | 0.132189E+11 | 0.629708E+10 | 0.993763E+10 | 0.612205E+10 | 0.421888E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.200025E+11 | 0.876508E+10 | 0.182548E+11 | 0.142048E+11 | 0.405006E+10 | 0.00 | 0.00 |
February | 0.180790E+11 | 0.735547E+10 | 0.161360E+11 | 0.117868E+11 | 0.434920E+10 | 0.00 | 0.00 |
March | 0.150473E+11 | 0.666854E+10 | 0.131646E+11 | 0.795878E+10 | 0.520578E+10 | 0.00 | 0.00 |
April | 0.117846E+11 | 0.464135E+10 | 0.993549E+10 | 0.407834E+10 | 0.585715E+10 | 0.00 | 0.00 |
May | 0.818857E+10 | 0.346991E+10 | 0.684703E+10 | 0.150622E+10 | 0.534081E+10 | 0.00 | 0.00 |
June | 0.795145E+10 | 0.220353E+10 | 0.560517E+10 | 0.690776E+09 | 0.491439E+10 | 0.00 | 0.00 |
July | 0.987147E+10 | 0.149194E+10 | 0.640915E+10 | 0.102348E+10 | 0.538567E+10 | 0.00 | 0.00 |
August | 0.129812E+11 | 0.174439E+10 | 0.881306E+10 | 0.286469E+10 | 0.594836E+10 | 0.00 | 0.00 |
September | 0.161183E+11 | 0.297272E+10 | 0.117934E+11 | 0.657637E+10 | 0.521707E+10 | 0.00 | 0.00 |
October | 0.204639E+11 | 0.516171E+10 | 0.166727E+11 | 0.122793E+11 | 0.439334E+10 | 0.00 | 0.00 |
November | 0.203207E+11 | 0.699202E+10 | 0.179712E+11 | 0.137928E+11 | 0.417835E+10 | 0.00 | 0.00 |
December | 0.218685E+11 | 0.913414E+10 | 0.198060E+11 | 0.163379E+11 | 0.346811E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.182677E+12 | 0.606008E+11 | 0.151409E+12 | 0.931002E+11 | 0.583083E+11 | 0.00 | 0.00 |
Minimum of Months | 0.795145E+10 | 0.149194E+10 | 0.560517E+10 | 0.690776E+09 | 0.346811E+10 | 0.00 | 0.00 |
Maximum of Months | 0.218685E+11 | 0.913414E+10 | 0.198060E+11 | 0.163379E+11 | 0.594836E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.414185E+10 | 0.657229E+10 | 0.470222E+10 | 0.268153E+10 | 0.202069E+10 | 0.00 | 0.00 |
February | 0.518731E+10 | 0.554921E+10 | 0.546752E+10 | 0.315843E+10 | 0.230910E+10 | 0.00 | 0.00 |
March | 0.680658E+10 | 0.501560E+10 | 0.676088E+10 | 0.359895E+10 | 0.316193E+10 | 0.00 | 0.00 |
April | 0.914767E+10 | 0.346487E+10 | 0.835056E+10 | 0.444421E+10 | 0.390635E+10 | 0.00 | 0.00 |
May | 0.967150E+10 | 0.251288E+10 | 0.818146E+10 | 0.421566E+10 | 0.396580E+10 | 0.00 | 0.00 |
June | 0.113054E+11 | 0.172874E+10 | 0.848759E+10 | 0.473599E+10 | 0.375160E+10 | 0.00 | 0.00 |
July | 0.109917E+11 | 0.122521E+10 | 0.791073E+10 | 0.387141E+10 | 0.403932E+10 | 0.00 | 0.00 |
August | 0.108152E+11 | 0.145500E+10 | 0.808336E+10 | 0.373889E+10 | 0.434447E+10 | 0.00 | 0.00 |
September | 0.899553E+10 | 0.214879E+10 | 0.706565E+10 | 0.372119E+10 | 0.334446E+10 | 0.00 | 0.00 |
October | 0.750366E+10 | 0.392776E+10 | 0.667958E+10 | 0.415160E+10 | 0.252798E+10 | 0.00 | 0.00 |
November | 0.470650E+10 | 0.541966E+10 | 0.507430E+10 | 0.298533E+10 | 0.208898E+10 | 0.00 | 0.00 |
December | 0.386182E+10 | 0.732292E+10 | 0.453451E+10 | 0.284362E+10 | 0.169089E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.931348E+11 | 0.463429E+11 | 0.812984E+11 | 0.441468E+11 | 0.371516E+11 | 0.00 | 0.00 |
Minimum of Months | 0.386182E+10 | 0.122521E+10 | 0.453451E+10 | 0.268153E+10 | 0.169089E+10 | 0.00 | 0.00 |
Maximum of Months | 0.113054E+11 | 0.732292E+10 | 0.848759E+10 | 0.473599E+10 | 0.434447E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.530949E+09 | 0.890612E+10 | 0.246919E+10 | 0.00 | 0.246919E+10 | 0.00 | 0.00 |
February | 0.999541E+09 | 0.728690E+10 | 0.278742E+10 | 0.00 | 0.278742E+10 | 0.00 | 0.00 |
March | 0.234280E+10 | 0.637826E+10 | 0.389269E+10 | 0.00 | 0.389269E+10 | 0.00 | 0.00 |
April | 0.369961E+10 | 0.411345E+10 | 0.477930E+10 | 40918336.57 | 0.473838E+10 | 0.00 | 0.00 |
May | 0.531628E+10 | 0.311236E+10 | 0.536831E+10 | 0.346112E+09 | 0.502220E+10 | 0.00 | 0.00 |
June | 0.799700E+10 | 0.201988E+10 | 0.590308E+10 | 0.966028E+09 | 0.493705E+10 | 0.00 | 0.00 |
July | 0.823124E+10 | 0.142357E+10 | 0.559870E+10 | 0.465980E+09 | 0.513272E+10 | 0.00 | 0.00 |
August | 0.696921E+10 | 0.160562E+10 | 0.519373E+10 | 0.116277E+09 | 0.507745E+10 | 0.00 | 0.00 |
September | 0.458011E+10 | 0.272576E+10 | 0.401940E+10 | 1031583.39 | 0.401837E+10 | 0.00 | 0.00 |
October | 0.217228E+10 | 0.497151E+10 | 0.309925E+10 | 0.00 | 0.309925E+10 | 0.00 | 0.00 |
November | 0.731876E+09 | 0.686061E+10 | 0.254710E+10 | 0.00 | 0.254710E+10 | 0.00 | 0.00 |
December | 0.169566E+09 | 0.934009E+10 | 0.210165E+10 | 0.00 | 0.210165E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.437405E+11 | 0.587441E+11 | 0.477598E+11 | 0.193635E+10 | 0.458235E+11 | 0.00 | 0.00 |
Minimum of Months | 0.169566E+09 | 0.142357E+10 | 0.210165E+10 | 0.00 | 0.210165E+10 | 0.00 | 0.00 |
Maximum of Months | 0.823124E+10 | 0.934009E+10 | 0.590308E+10 | 0.966028E+09 | 0.513272E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.371730E+10 | 0.549282E+10 | 0.455877E+10 | 0.254878E+10 | 0.200999E+10 | 0.00 | 0.00 |
February | 0.448677E+10 | 0.453218E+10 | 0.500280E+10 | 0.269705E+10 | 0.230575E+10 | 0.00 | 0.00 |
March | 0.743860E+10 | 0.399457E+10 | 0.730653E+10 | 0.415363E+10 | 0.315290E+10 | 0.00 | 0.00 |
April | 0.108813E+11 | 0.269532E+10 | 0.966021E+10 | 0.550337E+10 | 0.415684E+10 | 0.00 | 0.00 |
May | 0.113813E+11 | 0.212282E+10 | 0.952515E+10 | 0.542830E+10 | 0.409685E+10 | 0.00 | 0.00 |
June | 0.131469E+11 | 0.133624E+10 | 0.993759E+10 | 0.612203E+10 | 0.381556E+10 | 0.00 | 0.00 |
July | 0.131308E+11 | 0.962313E+09 | 0.950194E+10 | 0.543360E+10 | 0.406835E+10 | 0.00 | 0.00 |
August | 0.125860E+11 | 0.108320E+10 | 0.940281E+10 | 0.518395E+10 | 0.421886E+10 | 0.00 | 0.00 |
September | 0.955835E+10 | 0.175596E+10 | 0.757380E+10 | 0.423761E+10 | 0.333619E+10 | 0.00 | 0.00 |
October | 0.751120E+10 | 0.312454E+10 | 0.680644E+10 | 0.431842E+10 | 0.248802E+10 | 0.00 | 0.00 |
November | 0.474460E+10 | 0.431497E+10 | 0.514798E+10 | 0.302646E+10 | 0.212152E+10 | 0.00 | 0.00 |
December | 0.354841E+10 | 0.579424E+10 | 0.431036E+10 | 0.262325E+10 | 0.168711E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.102132E+12 | 0.372092E+11 | 0.887344E+11 | 0.512764E+11 | 0.374579E+11 | 0.00 | 0.00 |
Minimum of Months | 0.354841E+10 | 0.962313E+09 | 0.431036E+10 | 0.254878E+10 | 0.168711E+10 | 0.00 | 0.00 |
Maximum of Months | 0.131469E+11 | 0.579424E+10 | 0.993759E+10 | 0.612203E+10 | 0.421886E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.198579E+11 | 0.861358E+10 | 0.182548E+11 | 0.142047E+11 | 0.405004E+10 | 0.00 | 0.00 |
February | 0.179554E+11 | 0.718796E+10 | 0.161359E+11 | 0.117868E+11 | 0.434918E+10 | 0.00 | 0.00 |
March | 0.149659E+11 | 0.645805E+10 | 0.131645E+11 | 0.795876E+10 | 0.520576E+10 | 0.00 | 0.00 |
April | 0.117513E+11 | 0.444388E+10 | 0.993546E+10 | 0.407832E+10 | 0.585713E+10 | 0.00 | 0.00 |
May | 0.817610E+10 | 0.335115E+10 | 0.684700E+10 | 0.150621E+10 | 0.534079E+10 | 0.00 | 0.00 |
June | 0.799252E+10 | 0.213603E+10 | 0.560515E+10 | 0.690774E+09 | 0.491437E+10 | 0.00 | 0.00 |
July | 0.988806E+10 | 0.149438E+10 | 0.640912E+10 | 0.102348E+10 | 0.538565E+10 | 0.00 | 0.00 |
August | 0.129565E+11 | 0.175105E+10 | 0.881302E+10 | 0.286468E+10 | 0.594834E+10 | 0.00 | 0.00 |
September | 0.160044E+11 | 0.291912E+10 | 0.117934E+11 | 0.657635E+10 | 0.521705E+10 | 0.00 | 0.00 |
October | 0.203147E+11 | 0.506800E+10 | 0.166726E+11 | 0.122793E+11 | 0.439332E+10 | 0.00 | 0.00 |
November | 0.201973E+11 | 0.680170E+10 | 0.179711E+11 | 0.137928E+11 | 0.417833E+10 | 0.00 | 0.00 |
December | 0.217557E+11 | 0.883169E+10 | 0.198059E+11 | 0.163378E+11 | 0.346810E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.181816E+12 | 0.590566E+11 | 0.151408E+12 | 0.930999E+11 | 0.583081E+11 | 0.00 | 0.00 |
Minimum of Months | 0.799252E+10 | 0.149438E+10 | 0.560515E+10 | 0.690774E+09 | 0.346810E+10 | 0.00 | 0.00 |
Maximum of Months | 0.217557E+11 | 0.883169E+10 | 0.198059E+11 | 0.163378E+11 | 0.594834E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.426334E+10 | 0.599378E+10 | 0.470220E+10 | 0.268152E+10 | 0.202068E+10 | 0.00 | 0.00 |
February | 0.533316E+10 | 0.497080E+10 | 0.546750E+10 | 0.315841E+10 | 0.230909E+10 | 0.00 | 0.00 |
March | 0.699737E+10 | 0.441134E+10 | 0.676085E+10 | 0.359894E+10 | 0.316192E+10 | 0.00 | 0.00 |
April | 0.932103E+10 | 0.302213E+10 | 0.835052E+10 | 0.444419E+10 | 0.390633E+10 | 0.00 | 0.00 |
May | 0.972156E+10 | 0.233265E+10 | 0.818143E+10 | 0.421565E+10 | 0.396578E+10 | 0.00 | 0.00 |
June | 0.113773E+11 | 0.158786E+10 | 0.848755E+10 | 0.473597E+10 | 0.375159E+10 | 0.00 | 0.00 |
July | 0.110892E+11 | 0.111195E+10 | 0.791069E+10 | 0.387139E+10 | 0.403930E+10 | 0.00 | 0.00 |
August | 0.109455E+11 | 0.127736E+10 | 0.808333E+10 | 0.373887E+10 | 0.434446E+10 | 0.00 | 0.00 |
September | 0.903939E+10 | 0.198196E+10 | 0.706562E+10 | 0.372118E+10 | 0.334444E+10 | 0.00 | 0.00 |
October | 0.762775E+10 | 0.349899E+10 | 0.667956E+10 | 0.415159E+10 | 0.252797E+10 | 0.00 | 0.00 |
November | 0.489223E+10 | 0.464696E+10 | 0.507428E+10 | 0.298531E+10 | 0.208897E+10 | 0.00 | 0.00 |
December | 0.402882E+10 | 0.619140E+10 | 0.453449E+10 | 0.284361E+10 | 0.169088E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.946367E+11 | 0.410272E+11 | 0.812980E+11 | 0.441466E+11 | 0.371514E+11 | 0.00 | 0.00 |
Minimum of Months | 0.402882E+10 | 0.111195E+10 | 0.453449E+10 | 0.268152E+10 | 0.169088E+10 | 0.00 | 0.00 |
Maximum of Months | 0.113773E+11 | 0.619140E+10 | 0.848755E+10 | 0.473597E+10 | 0.434446E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.643824E+09 | 0.830704E+10 | 0.246919E+10 | 0.00 | 0.246919E+10 | 0.00 | 0.00 |
February | 0.111159E+10 | 0.682736E+10 | 0.278742E+10 | 0.00 | 0.278742E+10 | 0.00 | 0.00 |
March | 0.246880E+10 | 0.598491E+10 | 0.389269E+10 | 0.00 | 0.389269E+10 | 0.00 | 0.00 |
April | 0.376896E+10 | 0.390439E+10 | 0.477930E+10 | 40918336.57 | 0.473838E+10 | 0.00 | 0.00 |
May | 0.533315E+10 | 0.302199E+10 | 0.536831E+10 | 0.346112E+09 | 0.502220E+10 | 0.00 | 0.00 |
June | 0.795963E+10 | 0.199929E+10 | 0.590308E+10 | 0.966028E+09 | 0.493705E+10 | 0.00 | 0.00 |
July | 0.816080E+10 | 0.144019E+10 | 0.559870E+10 | 0.465980E+09 | 0.513272E+10 | 0.00 | 0.00 |
August | 0.691438E+10 | 0.160500E+10 | 0.519373E+10 | 0.116277E+09 | 0.507745E+10 | 0.00 | 0.00 |
September | 0.457263E+10 | 0.265131E+10 | 0.401940E+10 | 1031583.39 | 0.401837E+10 | 0.00 | 0.00 |
October | 0.225311E+10 | 0.465698E+10 | 0.309925E+10 | 0.00 | 0.309925E+10 | 0.00 | 0.00 |
November | 0.857087E+09 | 0.630576E+10 | 0.254710E+10 | 0.00 | 0.254710E+10 | 0.00 | 0.00 |
December | 0.232256E+09 | 0.866870E+10 | 0.210165E+10 | 0.00 | 0.210165E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.442762E+11 | 0.553729E+11 | 0.477598E+11 | 0.193635E+10 | 0.458235E+11 | 0.00 | 0.00 |
Minimum of Months | 0.232256E+09 | 0.144019E+10 | 0.210165E+10 | 0.00 | 0.210165E+10 | 0.00 | 0.00 |
Maximum of Months | 0.816080E+10 | 0.866870E+10 | 0.590308E+10 | 0.966028E+09 | 0.513272E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.385044E+10 | 0.514762E+10 | 0.455877E+10 | 0.254878E+10 | 0.200999E+10 | 0.00 | 0.00 |
February | 0.458210E+10 | 0.427585E+10 | 0.500280E+10 | 0.269705E+10 | 0.230575E+10 | 0.00 | 0.00 |
March | 0.749818E+10 | 0.380033E+10 | 0.730653E+10 | 0.415363E+10 | 0.315290E+10 | 0.00 | 0.00 |
April | 0.108883E+11 | 0.260295E+10 | 0.966021E+10 | 0.550337E+10 | 0.415684E+10 | 0.00 | 0.00 |
May | 0.113550E+11 | 0.208166E+10 | 0.952515E+10 | 0.542830E+10 | 0.409685E+10 | 0.00 | 0.00 |
June | 0.131010E+11 | 0.132997E+10 | 0.993759E+10 | 0.612203E+10 | 0.381556E+10 | 0.00 | 0.00 |
July | 0.130716E+11 | 0.978304E+09 | 0.950194E+10 | 0.543360E+10 | 0.406835E+10 | 0.00 | 0.00 |
August | 0.125340E+11 | 0.108889E+10 | 0.940281E+10 | 0.518395E+10 | 0.421886E+10 | 0.00 | 0.00 |
September | 0.953539E+10 | 0.172870E+10 | 0.757380E+10 | 0.423761E+10 | 0.333619E+10 | 0.00 | 0.00 |
October | 0.754566E+10 | 0.298295E+10 | 0.680644E+10 | 0.431842E+10 | 0.248802E+10 | 0.00 | 0.00 |
November | 0.484587E+10 | 0.402521E+10 | 0.514798E+10 | 0.302646E+10 | 0.212152E+10 | 0.00 | 0.00 |
December | 0.365100E+10 | 0.539415E+10 | 0.431036E+10 | 0.262325E+10 | 0.168711E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.102459E+12 | 0.354366E+11 | 0.887344E+11 | 0.512764E+11 | 0.374579E+11 | 0.00 | 0.00 |
Minimum of Months | 0.365100E+10 | 0.978304E+09 | 0.431036E+10 | 0.254878E+10 | 0.168711E+10 | 0.00 | 0.00 |
Maximum of Months | 0.131010E+11 | 0.539415E+10 | 0.993759E+10 | 0.612203E+10 | 0.421886E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.200394E+11 | 0.806382E+10 | 0.182548E+11 | 0.142047E+11 | 0.405004E+10 | 0.00 | 0.00 |
February | 0.180698E+11 | 0.676755E+10 | 0.161359E+11 | 0.117868E+11 | 0.434918E+10 | 0.00 | 0.00 |
March | 0.150459E+11 | 0.612672E+10 | 0.131645E+11 | 0.795876E+10 | 0.520576E+10 | 0.00 | 0.00 |
April | 0.117718E+11 | 0.425262E+10 | 0.993546E+10 | 0.407832E+10 | 0.585713E+10 | 0.00 | 0.00 |
May | 0.816656E+10 | 0.325323E+10 | 0.684700E+10 | 0.150621E+10 | 0.534079E+10 | 0.00 | 0.00 |
June | 0.795181E+10 | 0.210608E+10 | 0.560515E+10 | 0.690774E+09 | 0.491437E+10 | 0.00 | 0.00 |
July | 0.981382E+10 | 0.151020E+10 | 0.640912E+10 | 0.102348E+10 | 0.538565E+10 | 0.00 | 0.00 |
August | 0.128883E+11 | 0.174951E+10 | 0.881302E+10 | 0.286468E+10 | 0.594834E+10 | 0.00 | 0.00 |
September | 0.159742E+11 | 0.285865E+10 | 0.117934E+11 | 0.657635E+10 | 0.521705E+10 | 0.00 | 0.00 |
October | 0.203775E+11 | 0.483033E+10 | 0.166726E+11 | 0.122793E+11 | 0.439332E+10 | 0.00 | 0.00 |
November | 0.203420E+11 | 0.636258E+10 | 0.179711E+11 | 0.137928E+11 | 0.417833E+10 | 0.00 | 0.00 |
December | 0.219098E+11 | 0.822039E+10 | 0.198059E+11 | 0.163378E+11 | 0.346810E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.182351E+12 | 0.561017E+11 | 0.151408E+12 | 0.930999E+11 | 0.583081E+11 | 0.00 | 0.00 |
Minimum of Months | 0.795181E+10 | 0.151020E+10 | 0.560515E+10 | 0.690774E+09 | 0.346810E+10 | 0.00 | 0.00 |
Maximum of Months | 0.219098E+11 | 0.822039E+10 | 0.198059E+11 | 0.163378E+11 | 0.594834E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.432130E+10 | 0.564900E+10 | 0.470220E+10 | 0.268152E+10 | 0.202068E+10 | 0.00 | 0.00 |
February | 0.536959E+10 | 0.471981E+10 | 0.546750E+10 | 0.315841E+10 | 0.230909E+10 | 0.00 | 0.00 |
March | 0.703261E+10 | 0.420479E+10 | 0.676085E+10 | 0.359894E+10 | 0.316192E+10 | 0.00 | 0.00 |
April | 0.932734E+10 | 0.290962E+10 | 0.835052E+10 | 0.444419E+10 | 0.390633E+10 | 0.00 | 0.00 |
May | 0.970754E+10 | 0.227373E+10 | 0.818143E+10 | 0.421565E+10 | 0.396578E+10 | 0.00 | 0.00 |
June | 0.113431E+11 | 0.156876E+10 | 0.848755E+10 | 0.473597E+10 | 0.375159E+10 | 0.00 | 0.00 |
July | 0.110363E+11 | 0.111835E+10 | 0.791069E+10 | 0.387139E+10 | 0.403930E+10 | 0.00 | 0.00 |
August | 0.109019E+11 | 0.127322E+10 | 0.808333E+10 | 0.373887E+10 | 0.434446E+10 | 0.00 | 0.00 |
September | 0.902251E+10 | 0.194150E+10 | 0.706562E+10 | 0.372118E+10 | 0.334444E+10 | 0.00 | 0.00 |
October | 0.764645E+10 | 0.334033E+10 | 0.667956E+10 | 0.415159E+10 | 0.252797E+10 | 0.00 | 0.00 |
November | 0.494269E+10 | 0.435803E+10 | 0.507428E+10 | 0.298531E+10 | 0.208897E+10 | 0.00 | 0.00 |
December | 0.406775E+10 | 0.581989E+10 | 0.453449E+10 | 0.284361E+10 | 0.169088E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.947190E+11 | 0.391770E+11 | 0.812980E+11 | 0.441466E+11 | 0.371514E+11 | 0.00 | 0.00 |
Minimum of Months | 0.406775E+10 | 0.111835E+10 | 0.453449E+10 | 0.268152E+10 | 0.169088E+10 | 0.00 | 0.00 |
Maximum of Months | 0.113431E+11 | 0.581989E+10 | 0.848755E+10 | 0.473597E+10 | 0.434446E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 2.60 | -1.3 | -7.5 | 3.29 | -12.5 | 38.91 | 220.14 | 0.00 |
February | 4.28 | 0.13 | -5.8 | 3.80 | -10.7 | 48.21 | 247.44 | 0.00 |
March | 8.76 | 2.64 | -5.5 | 4.72 | -6.0 | 66.36 | 249.43 | 0.00 |
April | 13.90 | 4.70 | -6.4 | 4.61 | -1.8 | 81.54 | 308.98 | 0.00 |
May | 17.82 | 8.42 | -1.1 | 4.68 | 3.61 | 77.67 | 310.50 | 0.00 |
June | 23.21 | 12.42 | 4.15 | 4.28 | 9.16 | 70.88 | 348.57 | 0.00 |
July | 25.63 | 16.13 | 10.74 | 4.00 | 14.07 | 80.74 | 308.61 | 0.00 |
August | 24.08 | 15.39 | 10.38 | 3.96 | 13.00 | 86.20 | 290.42 | 0.00 |
September | 20.49 | 12.87 | 7.70 | 3.48 | 8.22 | 67.00 | 274.65 | 0.00 |
October | 13.71 | 6.72 | -0.1 | 3.54 | -0.8 | 42.11 | 283.53 | 0.00 |
November | 6.96 | 1.72 | -4.9 | 3.43 | -7.6 | 39.44 | 239.51 | 0.01 |
December | 2.07 | -2.2 | -8.9 | 2.95 | -13.5 | 27.44 | 240.96 | 0.00 |
Annual Sum or Average | 13.68 | 6.50 | -0.6 | 3.90 | -0.3 | 60.60 | 276.96 | 0.00 |
Minimum of Months | 2.07 | -2.2 | -8.9 | 2.95 | -13.5 | 27.44 | 220.14 | 0.00 |
Maximum of Months | 25.63 | 16.13 | 10.74 | 4.72 | 14.07 | 86.20 | 348.57 | 0.01 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 16.10 | 01-JAN-14:00 | 5.83 | -6.7 | 5.20 | -2.3 | 27.00 | 880.00 |
February | 22.20 | 14-FEB-15:00 | 7.86 | -10.0 | 4.60 | 4.72 | 61.50 | 778.50 |
March | 22.80 | 08-MAR-13:00 | 9.68 | -2.8 | 3.60 | 4.92 | 122.50 | 851.50 |
April | 26.10 | 13-APR-16:00 | 10.32 | -4.4 | 5.20 | 7.55 | 95.00 | 507.00 |
May | 30.00 | 19-MAY-15:20 | 12.71 | -1.5 | 8.93 | 13.35 | 108.33 | 887.00 |
June | 38.90 | 28-JUN-15:00 | 14.16 | -8.9 | 3.10 | 20.75 | 70.00 | 888.00 |
July | 38.30 | 22-JUL-14:00 | 16.71 | 3.30 | 5.20 | 24.16 | 99.00 | 907.50 |
August | 35.00 | 01-AUG-14:00 | 16.30 | 4.40 | 2.60 | 19.52 | 113.00 | 840.50 |
September | 32.80 | 03-SEP-13:00 | 16.76 | 7.80 | 3.60 | 21.78 | 263.50 | 532.50 |
October | 28.90 | 01-OCT-15:00 | 13.26 | 1.70 | 4.10 | 15.94 | 85.00 | 435.00 |
November | 19.40 | 09-NOV-13:00 | 9.81 | 1.70 | 10.80 | 8.35 | 157.50 | 0.00 |
December | 13.30 | 24-DEC-14:00 | 4.02 | -8.3 | 8.20 | -2.5 | 40.50 | 792.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 13.30 | 4.02 | -10.0 | 2.60 | -2.5 | 27.00 | 0.00 | |
Maximum of Months | 38.90 | 16.76 | 7.80 | 10.80 | 24.16 | 263.50 | 907.50 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -8.3 | 20-JAN-01:00 | -8.3 | -8.3 | 2.10 | -25.6 | 0.00 | 0.00 |
February | -6.7 | 04-FEB-06:10 | -8.2 | -11.7 | 5.10 | -25.0 | 0.00 | 0.00 |
March | -3.9 | 05-MAR-06:00 | -5.7 | -9.4 | 1.50 | -21.6 | 17.00 | 434.50 |
April | 1.70 | 06-APR-05:00 | -2.4 | -8.3 | 2.60 | -12.9 | 28.00 | 215.00 |
May | 4.40 | 07-MAY-04:00 | -1.0 | -8.3 | 1.50 | -13.7 | 0.00 | 0.00 |
June | 7.80 | 09-JUN-04:40 | 5.54 | 3.30 | 4.83 | -7.8 | 0.00 | 0.00 |
July | 16.10 | 08-JUL-02:00 | 14.67 | 13.90 | 0.00 | 4.72 | 0.00 | 0.00 |
August | 12.80 | 31-AUG-05:00 | 10.77 | 9.40 | 3.10 | -1.7 | 24.50 | 228.50 |
September | 10.60 | 09-SEP-05:00 | 9.95 | 9.40 | 2.10 | -2.5 | 15.50 | 177.00 |
October | -2.8 | 26-OCT-04:10 | -4.1 | -6.1 | 2.42 | -17.7 | 0.00 | 0.00 |
November | -4.4 | 27-NOV-05:00 | -6.9 | -11.7 | 2.60 | -22.7 | 0.00 | 0.00 |
December | -9.4 | 15-DEC-04:00 | -12.1 | -21.7 | 0.00 | -29.7 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -9.4 | -12.1 | -21.7 | 0.00 | -29.7 | 0.00 | 0.00 | |
Maximum of Months | 16.10 | 14.67 | 13.90 | 5.10 | 4.72 | 28.00 | 434.50 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 6.84 | 05-JAN-13:00 | 16.10 | -2.8 | 3.10 | -0.1 | 62.00 | 873.00 |
February | 7.86 | 14-FEB-15:00 | 22.20 | -10.0 | 4.60 | 4.72 | 61.50 | 778.50 |
March | 9.68 | 08-MAR-13:00 | 22.80 | -2.8 | 3.60 | 4.92 | 122.50 | 851.50 |
April | 10.95 | 14-APR-15:00 | 24.40 | -0.6 | 8.20 | 17.21 | 237.00 | 154.00 |
May | 15.08 | 22-MAY-12:30 | 28.60 | 6.40 | 5.15 | 16.76 | 167.00 | 0.00 |
June | 18.19 | 24-JUN-13:00 | 31.70 | 11.70 | 2.60 | 19.17 | 130.00 | 891.50 |
July | 19.21 | 31-JUL-14:00 | 32.80 | 12.80 | 6.20 | 22.98 | 264.50 | 624.50 |
August | 19.18 | 26-AUG-12:00 | 27.80 | 15.60 | 3.60 | 17.03 | 289.00 | 426.50 |
September | 18.19 | 05-SEP-12:00 | 23.90 | 15.60 | 3.10 | 13.35 | 196.50 | 796.00 |
October | 16.16 | 11-OCT-10:00 | 23.90 | 12.20 | 13.40 | 13.73 | 219.50 | 450.00 |
November | 9.81 | 09-NOV-13:00 | 19.40 | 1.70 | 10.80 | 8.35 | 157.50 | 0.00 |
December | 4.92 | 01-DEC-15:00 | 12.80 | -3.9 | 2.10 | 1.58 | 50.00 | 276.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 4.92 | 12.80 | -10.0 | 2.10 | -0.1 | 50.00 | 0.00 | |
Maximum of Months | 19.21 | 32.80 | 15.60 | 13.40 | 22.98 | 289.00 | 891.50 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -0.6 | 28-JAN-17:00 | 6.10 | 3.01 | 4.60 | -5.0 | 0.00 | 0.00 |
February | 2.20 | 17-FEB-10:00 | 7.20 | 4.72 | 3.10 | -4.1 | 212.50 | 561.00 |
March | 5.60 | 28-MAR-17:10 | 8.80 | 7.05 | 4.60 | 3.37 | 35.00 | 0.67 |
April | 7.20 | 15-APR-06:00 | 13.30 | 9.79 | 7.20 | 6.35 | 116.00 | 422.00 |
May | 13.90 | 24-MAY-14:00 | 16.70 | 14.90 | 4.60 | 11.07 | 128.00 | 0.00 |
June | 13.30 | 30-JUN-13:00 | 26.70 | 17.72 | 6.70 | 20.75 | 170.00 | 126.50 |
July | 17.80 | 01-JUL-13:00 | 22.20 | 19.05 | 3.60 | 13.91 | 361.00 | 125.00 |
August | 17.20 | 26-AUG-09:00 | 21.70 | 18.59 | 2.60 | 11.65 | 243.50 | 681.50 |
September | 15.60 | 05-SEP-11:00 | 22.20 | 17.61 | 3.10 | 12.79 | 231.00 | 705.00 |
October | 13.90 | 02-OCT-16:00 | 20.60 | 16.04 | 6.20 | 13.54 | 38.50 | 65.00 |
November | 6.10 | 09-NOV-21:00 | 8.90 | 7.38 | 11.80 | 3.69 | 0.00 | 0.00 |
December | 1.10 | 25-DEC-08:00 | 2.20 | 1.65 | 2.10 | -4.1 | 54.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -0.6 | 2.20 | 1.65 | 2.10 | -5.0 | 0.00 | 0.00 | |
Maximum of Months | 17.80 | 26.70 | 19.05 | 11.80 | 20.75 | 361.00 | 705.00 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 11.28 | 25.87 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 10.91 | 34.17 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 12.10 | 41.92 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 14.59 | 56.24 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 17.73 | 59.47 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 20.66 | 62.98 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 22.59 | 61.22 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 23.01 | 57.83 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 21.78 | 48.11 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 19.25 | 37.89 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 16.11 | 28.37 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 13.20 | 24.17 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 16.97 | 44.90 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 10.91 | 24.17 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 23.01 | 62.98 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.389819E+11 | -0.379584E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.102352E+10 | 58.98 | 0.00 | 0.00 |
February | 0.356843E+11 | -0.347597E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -924628463.8 | 58.98 | 0.00 | 0.00 |
March | 0.408993E+11 | -0.398740E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.102525E+10 | 58.97 | 0.00 | 0.00 |
April | 0.352256E+11 | -0.342381E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -987486715.2 | 58.98 | 0.00 | 0.00 |
May | 0.350348E+11 | -0.340131E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.102171E+10 | 58.98 | 0.00 | 0.00 |
June | 0.322793E+11 | -0.312903E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -989013763.8 | 58.97 | 0.00 | 0.00 |
July | 0.292591E+11 | -0.282424E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.101669E+10 | 58.97 | 0.00 | 0.00 |
August | 0.316130E+11 | -0.305923E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.102067E+10 | 58.97 | 0.00 | 0.00 |
September | 0.296945E+11 | -0.287091E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -985326830.4 | 58.97 | 0.00 | 0.00 |
October | 0.326438E+11 | -0.316264E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.101743E+10 | 58.98 | 0.00 | 0.00 |
November | 0.344499E+11 | -0.334642E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -985694779.9 | 58.98 | 0.00 | 0.00 |
December | 0.365685E+11 | -0.355485E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.101997E+10 | 58.98 | 0.00 | 0.00 |
Annual Sum or Average | 0.412334E+12 | -0.400317E+12 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.120174E+11 | 58.98 | 0.00 | 0.00 |
Minimum of Months | 0.292591E+11 | -0.398740E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -0.102525E+10 | 58.97 | 0.00 | 0.00 |
Maximum of Months | 0.408993E+11 | -0.282424E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -924628463.8 | 58.98 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_1_DAYLCTRL
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 301.50 | 0.49 | 0.48 | 01-JAN-07:40 | 11626.70 | 38.14 | 289.33 | 288.67 | 2999.55 | 28.50 | 209.67 | 278.17 |
February | 282.00 | 0.49 | 0.48 | 01-FEB-07:49 | 14250.58 | 38.20 | 273.33 | 277.83 | 2144.50 | 23.85 | 173.33 | 262.50 |
March | 351.33 | 0.50 | 0.48 | 01-MAR-07:10 | 2642.97 | 20.61 | 131.50 | 334.67 | 1546.49 | 21.77 | 174.83 | 305.00 |
April | 381.83 | 0.51 | 0.48 | 01-APR-06:40 | 2145.26 | 20.77 | 152.67 | 356.67 | 1298.70 | 22.16 | 268.83 | 333.50 |
May | 378.00 | 0.51 | 0.48 | 01-MAY-06:30 | 1659.73 | 20.10 | 85.50 | 376.67 | 1026.02 | 21.54 | 227.33 | 345.67 |
June | 412.83 | 0.51 | 0.48 | 01-JUN-06:10 | 1325.19 | 19.24 | 60.50 | 381.17 | 830.16 | 20.73 | 130.83 | 337.67 |
July | 395.33 | 0.51 | 0.48 | 01-JUL-06:00 | 1603.48 | 19.94 | 90.33 | 381.67 | 981.21 | 21.42 | 199.33 | 345.67 |
August | 408.83 | 0.51 | 0.48 | 01-AUG-06:30 | 1995.46 | 20.53 | 170.00 | 376.83 | 1192.88 | 21.95 | 256.67 | 351.17 |
September | 359.33 | 0.50 | 0.48 | 01-SEP-06:40 | 2594.66 | 21.05 | 132.83 | 333.67 | 1445.42 | 21.80 | 185.00 | 308.50 |
October | 329.00 | 0.51 | 0.48 | 01-OCT-06:00 | 6938.28 | 29.52 | 215.50 | 318.00 | 1926.63 | 21.94 | 144.67 | 305.50 |
November | 284.17 | 0.49 | 0.48 | 01-NOV-06:00 | 13141.10 | 39.17 | 280.33 | 286.33 | 2961.50 | 28.15 | 213.17 | 274.50 |
December | 265.67 | 0.50 | 0.48 | 01-DEC-07:49 | 13282.69 | 40.48 | 263.83 | 270.50 | 4370.51 | 31.80 | 195.50 | 263.00 |
Annual Sum or Average | 4149.83 | 0.50 | 5391.56 | 26.13 | 2145.67 | 3982.67 | 1761.61 | 23.39 | 2379.17 | 3710.83 | ||
Minimum of Months | 265.67 | 0.49 | 0.48 | 1325.19 | 19.24 | 60.50 | 270.50 | 830.16 | 20.73 | 130.83 | 262.50 | |
Maximum of Months | 412.83 | 0.51 | 0.48 | 14250.58 | 40.48 | 289.33 | 381.67 | 4370.51 | 31.80 | 268.83 | 351.17 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_2_DAYLCTRL
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 301.50 | 0.51 | 0.48 | 01-JAN-07:40 | 3009.34 | 25.35 | 133.00 | 271.00 | 1673.76 | 25.22 | 153.17 | 244.67 |
February | 282.00 | 0.51 | 0.48 | 01-FEB-07:30 | 3824.83 | 25.26 | 123.83 | 270.83 | 2121.05 | 25.24 | 147.50 | 248.67 |
March | 351.33 | 0.50 | 0.48 | 01-MAR-06:00 | 3879.81 | 24.76 | 138.83 | 331.67 | 2086.69 | 24.80 | 179.83 | 306.17 |
April | 381.83 | 0.50 | 0.48 | 01-APR-05:00 | 5519.45 | 26.03 | 135.83 | 361.83 | 2204.46 | 24.80 | 204.33 | 344.83 |
May | 378.00 | 0.51 | 0.48 | 01-MAY-05:00 | 4424.57 | 23.85 | 98.33 | 381.00 | 2456.73 | 24.23 | 148.00 | 355.67 |
June | 412.83 | 0.50 | 0.48 | 01-JUN-05:30 | 4223.44 | 23.50 | 118.00 | 397.33 | 2389.84 | 23.89 | 148.83 | 365.17 |
July | 395.33 | 0.49 | 0.48 | 01-JUL-06:40 | 4216.23 | 24.01 | 117.50 | 390.50 | 2245.75 | 24.22 | 166.33 | 361.50 |
August | 408.83 | 0.50 | 0.48 | 01-AUG-05:40 | 5093.40 | 25.60 | 143.17 | 384.00 | 2078.07 | 24.54 | 218.50 | 364.50 |
September | 359.33 | 0.50 | 0.48 | 01-SEP-06:19 | 4345.57 | 24.71 | 132.83 | 337.67 | 2411.51 | 24.93 | 170.50 | 315.17 |
October | 329.00 | 0.51 | 0.48 | 01-OCT-06:30 | 3960.27 | 25.17 | 120.83 | 311.00 | 2185.44 | 25.09 | 144.50 | 289.50 |
November | 284.17 | 0.51 | 0.48 | 01-NOV-06:49 | 3221.62 | 25.24 | 111.83 | 271.00 | 1736.12 | 25.10 | 145.50 | 248.50 |
December | 265.67 | 0.53 | 0.48 | 01-DEC-07:49 | 3500.37 | 25.56 | 108.17 | 253.17 | 2023.64 | 25.21 | 115.83 | 221.83 |
Annual Sum or Average | 4149.83 | 0.50 | 4176.46 | 24.87 | 1482.17 | 3961.00 | 2155.94 | 24.72 | 1942.83 | 3666.17 | ||
Minimum of Months | 265.67 | 0.49 | 0.48 | 3009.34 | 23.50 | 98.33 | 253.17 | 1673.76 | 23.89 | 115.83 | 221.83 | |
Maximum of Months | 412.83 | 0.53 | 0.48 | 5519.45 | 26.03 | 143.17 | 397.33 | 2456.73 | 25.24 | 218.50 | 365.17 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_3_DAYLCTRL
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 301.50 | 0.54 | 0.48 | 01-JAN-09:09 | 748.12 | 17.63 | 0.00 | 254.83 | 477.56 | 19.43 | 40.33 | 207.33 |
February | 282.00 | 0.52 | 0.48 | 01-FEB-08:20 | 882.56 | 18.34 | 0.00 | 259.17 | 579.19 | 20.09 | 86.50 | 221.67 |
March | 351.33 | 0.51 | 0.48 | 01-MAR-07:30 | 1044.13 | 18.98 | 8.83 | 324.50 | 653.39 | 20.50 | 123.00 | 285.00 |
April | 381.83 | 0.50 | 0.48 | 01-APR-06:19 | 1313.15 | 20.39 | 77.33 | 363.33 | 831.92 | 21.79 | 235.50 | 345.17 |
May | 378.00 | 0.50 | 0.48 | 01-MAY-06:19 | 1523.64 | 20.58 | 105.83 | 391.50 | 885.70 | 21.95 | 221.83 | 362.33 |
June | 412.83 | 0.49 | 0.48 | 01-JUN-05:40 | 1573.80 | 22.71 | 146.83 | 405.50 | 860.07 | 22.53 | 209.00 | 384.50 |
July | 395.33 | 0.49 | 0.48 | 01-JUL-06:49 | 1554.67 | 22.43 | 140.17 | 398.17 | 895.91 | 21.86 | 235.83 | 372.67 |
August | 408.83 | 0.50 | 0.48 | 01-AUG-05:00 | 1387.91 | 20.46 | 120.00 | 385.50 | 877.10 | 21.87 | 252.00 | 369.83 |
September | 359.33 | 0.51 | 0.48 | 01-SEP-06:40 | 1107.43 | 19.47 | 23.17 | 333.17 | 707.42 | 20.98 | 139.67 | 299.67 |
October | 329.00 | 0.53 | 0.48 | 01-OCT-07:19 | 808.78 | 17.87 | 0.17 | 295.83 | 550.33 | 19.58 | 55.00 | 254.17 |
November | 284.17 | 0.53 | 0.48 | 01-NOV-07:30 | 795.45 | 18.21 | 0.00 | 260.00 | 525.36 | 20.05 | 42.17 | 221.83 |
December | 265.67 | 0.55 | 0.48 | 01-DEC-08:30 | 663.36 | 16.82 | 0.00 | 237.50 | 454.05 | 18.82 | 20.67 | 187.33 |
Annual Sum or Average | 4149.83 | 0.51 | 1160.69 | 19.72 | 622.33 | 3909.00 | 713.85 | 20.94 | 1661.50 | 3511.50 | ||
Minimum of Months | 265.67 | 0.49 | 0.48 | 663.36 | 16.82 | 0.00 | 237.50 | 454.05 | 18.82 | 20.67 | 187.33 | |
Maximum of Months | 412.83 | 0.55 | 0.48 | 1573.80 | 22.71 | 146.83 | 405.50 | 895.91 | 22.53 | 252.00 | 384.50 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_4_DAYLCTRL
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 301.50 | 0.51 | 0.48 | 01-JAN-09:09 | 2599.27 | 23.99 | 118.67 | 276.33 | 1301.56 | 23.74 | 137.67 | 247.83 |
February | 282.00 | 0.50 | 0.48 | 01-FEB-08:30 | 3799.36 | 25.67 | 122.67 | 268.67 | 2079.81 | 25.52 | 153.50 | 246.33 |
March | 351.33 | 0.50 | 0.48 | 01-MAR-07:40 | 4010.48 | 24.34 | 137.17 | 333.67 | 1531.34 | 23.09 | 166.17 | 306.83 |
April | 381.83 | 0.50 | 0.48 | 01-APR-06:00 | 4953.83 | 24.45 | 117.33 | 364.83 | 2032.66 | 23.67 | 186.33 | 346.67 |
May | 378.00 | 0.50 | 0.48 | 01-MAY-06:49 | 3668.21 | 20.68 | 56.50 | 389.67 | 2054.44 | 20.99 | 102.67 | 370.00 |
June | 412.83 | 0.50 | 0.48 | 01-JUN-06:19 | 3890.91 | 17.62 | 13.33 | 391.83 | 2247.18 | 20.10 | 108.17 | 365.00 |
July | 395.33 | 0.50 | 0.48 | 01-JUL-07:10 | 3750.12 | 18.56 | 21.83 | 390.33 | 2059.60 | 20.78 | 143.67 | 365.83 |
August | 408.83 | 0.50 | 0.48 | 01-AUG-06:49 | 3716.00 | 21.53 | 79.50 | 380.50 | 1945.56 | 21.51 | 193.50 | 359.50 |
September | 359.33 | 0.50 | 0.48 | 01-SEP-06:00 | 4183.94 | 24.55 | 132.83 | 337.67 | 1653.77 | 23.46 | 156.17 | 317.83 |
October | 329.00 | 0.51 | 0.48 | 01-OCT-07:19 | 3770.03 | 24.65 | 121.50 | 310.50 | 2061.12 | 24.61 | 139.33 | 288.17 |
November | 284.17 | 0.50 | 0.48 | 01-NOV-07:30 | 3690.46 | 26.36 | 123.00 | 279.33 | 2152.13 | 26.25 | 156.50 | 258.67 |
December | 265.67 | 0.52 | 0.48 | 01-DEC-08:30 | 3395.37 | 26.59 | 117.67 | 257.00 | 1997.38 | 26.28 | 133.83 | 234.83 |
Annual Sum or Average | 4149.83 | 0.50 | 3818.18 | 22.91 | 1162.00 | 3980.33 | 1932.98 | 23.06 | 1777.50 | 3707.50 | ||
Minimum of Months | 265.67 | 0.50 | 0.48 | 2599.27 | 17.62 | 13.33 | 257.00 | 1301.56 | 20.10 | 102.67 | 234.83 | |
Maximum of Months | 412.83 | 0.52 | 0.48 | 4953.83 | 26.59 | 137.17 | 391.83 | 2247.18 | 26.28 | 193.50 | 370.00 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_1_DAYLCTRL
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 301.50 | 0.49 | 0.48 | 01-JAN-07:40 | 11729.32 | 37.52 | 288.83 | 288.67 | 3167.98 | 24.66 | 127.17 | 279.00 |
February | 282.00 | 0.49 | 0.48 | 01-FEB-07:40 | 14361.45 | 37.69 | 272.17 | 277.83 | 2480.02 | 21.61 | 79.67 | 266.50 |
March | 351.33 | 0.50 | 0.48 | 01-MAR-07:10 | 2714.11 | 14.01 | 10.67 | 335.00 | 1669.97 | 17.31 | 10.83 | 308.50 |
April | 381.83 | 0.51 | 0.48 | 01-APR-06:30 | 2199.95 | 14.87 | 0.00 | 357.17 | 1394.46 | 18.40 | 14.50 | 337.17 |
May | 378.00 | 0.51 | 0.48 | 01-MAY-06:30 | 1700.41 | 14.31 | 0.00 | 377.00 | 1098.90 | 17.86 | 0.00 | 350.00 |
June | 412.83 | 0.51 | 0.48 | 01-JUN-05:00 | 1357.77 | 13.29 | 0.00 | 381.33 | 888.61 | 16.92 | 0.00 | 344.33 |
July | 395.33 | 0.50 | 0.48 | 01-JUL-06:49 | 1639.75 | 14.03 | 0.00 | 382.00 | 1049.63 | 17.62 | 1.00 | 349.83 |
August | 408.83 | 0.51 | 0.48 | 01-AUG-06:19 | 2042.00 | 14.62 | 0.00 | 376.83 | 1277.90 | 18.14 | 2.50 | 354.00 |
September | 359.33 | 0.50 | 0.48 | 01-SEP-06:40 | 2666.53 | 14.87 | 16.50 | 334.33 | 1557.42 | 17.56 | 9.67 | 311.33 |
October | 329.00 | 0.50 | 0.48 | 01-OCT-06:49 | 7084.39 | 25.90 | 183.50 | 321.33 | 2092.99 | 17.36 | 18.17 | 307.33 |
November | 284.17 | 0.49 | 0.48 | 01-NOV-06:49 | 13254.20 | 38.72 | 280.17 | 286.83 | 3176.40 | 24.68 | 113.17 | 276.83 |
December | 265.67 | 0.49 | 0.48 | 01-DEC-07:49 | 13424.12 | 40.07 | 263.83 | 270.67 | 4568.91 | 28.43 | 146.67 | 263.67 |
Annual Sum or Average | 4149.83 | 0.50 | 5467.19 | 21.80 | 1315.67 | 3989.00 | 1893.56 | 19.60 | 523.33 | 3748.50 | ||
Minimum of Months | 265.67 | 0.49 | 0.48 | 1357.77 | 13.29 | 0.00 | 270.67 | 888.61 | 16.92 | 0.00 | 263.67 | |
Maximum of Months | 412.83 | 0.51 | 0.48 | 14361.45 | 40.07 | 288.83 | 382.00 | 4568.91 | 28.43 | 146.67 | 354.00 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_2_DAYLCTRL
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 301.50 | 0.51 | 0.48 | 01-JAN-07:40 | 3060.37 | 22.87 | 106.67 | 272.00 | 1739.04 | 23.34 | 87.33 | 247.83 |
February | 282.00 | 0.51 | 0.48 | 01-FEB-07:30 | 3889.00 | 22.67 | 97.00 | 271.50 | 2197.12 | 23.23 | 81.17 | 251.33 |
March | 351.33 | 0.50 | 0.48 | 01-MAR-06:00 | 3962.27 | 21.75 | 105.67 | 332.50 | 2178.96 | 22.39 | 76.50 | 308.33 |
April | 381.83 | 0.50 | 0.48 | 01-APR-05:00 | 5527.61 | 21.96 | 114.83 | 361.33 | 2318.43 | 22.13 | 67.17 | 347.67 |
May | 378.00 | 0.51 | 0.48 | 01-MAY-05:00 | 4490.06 | 20.53 | 95.50 | 381.17 | 2572.58 | 21.53 | 66.33 | 359.33 |
June | 412.83 | 0.49 | 0.48 | 01-JUN-05:19 | 4307.82 | 20.11 | 111.83 | 398.00 | 2495.66 | 21.16 | 82.67 | 369.67 |
July | 395.33 | 0.49 | 0.48 | 01-JUL-06:40 | 4292.51 | 20.67 | 103.83 | 391.17 | 2356.17 | 21.52 | 71.83 | 364.17 |
August | 408.83 | 0.50 | 0.48 | 01-AUG-05:40 | 5156.84 | 22.74 | 134.00 | 384.33 | 2182.69 | 21.95 | 75.00 | 366.83 |
September | 359.33 | 0.50 | 0.48 | 01-SEP-06:19 | 4422.68 | 21.71 | 109.67 | 338.00 | 2504.48 | 22.55 | 83.17 | 318.17 |
October | 329.00 | 0.51 | 0.48 | 01-OCT-06:30 | 4017.84 | 22.07 | 103.00 | 311.83 | 2274.35 | 22.87 | 77.67 | 292.33 |
November | 284.17 | 0.51 | 0.48 | 01-NOV-06:49 | 3227.37 | 21.64 | 80.67 | 271.67 | 1813.59 | 23.06 | 72.17 | 252.00 |
December | 265.67 | 0.52 | 0.48 | 01-DEC-07:49 | 3555.94 | 23.25 | 95.67 | 254.17 | 2091.64 | 23.49 | 78.33 | 227.17 |
Annual Sum or Average | 4149.83 | 0.50 | 4235.33 | 21.74 | 1258.33 | 3967.67 | 2250.81 | 22.33 | 919.33 | 3704.83 | ||
Minimum of Months | 265.67 | 0.49 | 0.48 | 3060.37 | 20.11 | 80.67 | 254.17 | 1739.04 | 21.16 | 66.33 | 227.17 | |
Maximum of Months | 412.83 | 0.52 | 0.48 | 5527.61 | 23.25 | 134.00 | 398.00 | 2572.58 | 23.49 | 87.33 | 369.67 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_3_DAYLCTRL
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 301.50 | 0.53 | 0.48 | 01-JAN-08:00 | 761.77 | 11.75 | 0.00 | 256.17 | 509.04 | 15.55 | 0.00 | 215.83 |
February | 282.00 | 0.52 | 0.48 | 01-FEB-08:09 | 900.77 | 12.66 | 0.00 | 259.33 | 618.05 | 16.40 | 0.00 | 229.50 |
March | 351.33 | 0.51 | 0.48 | 01-MAR-07:30 | 1066.38 | 13.38 | 0.00 | 325.50 | 697.34 | 16.96 | 0.00 | 290.83 |
April | 381.83 | 0.50 | 0.48 | 01-APR-06:19 | 1342.41 | 15.21 | 0.00 | 363.33 | 887.63 | 18.75 | 20.17 | 348.00 |
May | 378.00 | 0.50 | 0.48 | 01-MAY-06:19 | 1558.40 | 14.95 | 1.00 | 391.50 | 947.37 | 18.57 | 28.00 | 364.33 |
June | 412.83 | 0.49 | 0.48 | 01-JUN-05:40 | 1610.91 | 17.70 | 77.67 | 405.67 | 920.90 | 19.05 | 36.50 | 387.33 |
July | 395.33 | 0.49 | 0.48 | 01-JUL-06:49 | 1593.35 | 17.37 | 54.00 | 398.33 | 969.25 | 19.14 | 30.00 | 376.83 |
August | 408.83 | 0.50 | 0.48 | 01-AUG-05:00 | 1442.05 | 15.04 | 0.00 | 386.17 | 935.04 | 18.60 | 23.00 | 371.67 |
September | 359.33 | 0.50 | 0.48 | 01-SEP-06:40 | 1132.41 | 14.07 | 0.00 | 334.00 | 755.49 | 17.65 | 0.50 | 305.00 |
October | 329.00 | 0.53 | 0.48 | 01-OCT-07:19 | 828.48 | 12.31 | 0.00 | 296.33 | 588.26 | 16.07 | 0.00 | 262.33 |
November | 284.17 | 0.52 | 0.48 | 01-NOV-07:19 | 810.09 | 12.58 | 0.00 | 260.33 | 560.17 | 16.37 | 0.00 | 229.17 |
December | 265.67 | 0.55 | 0.48 | 01-DEC-08:20 | 675.86 | 11.05 | 0.00 | 238.50 | 484.37 | 14.93 | 0.00 | 198.33 |
Annual Sum or Average | 4149.83 | 0.51 | 1188.90 | 14.27 | 132.67 | 3915.17 | 763.48 | 17.53 | 138.17 | 3579.17 | ||
Minimum of Months | 265.67 | 0.49 | 0.48 | 675.86 | 11.05 | 0.00 | 238.50 | 484.37 | 14.93 | 0.00 | 198.33 | |
Maximum of Months | 412.83 | 0.55 | 0.48 | 1610.91 | 17.70 | 77.67 | 405.67 | 969.25 | 19.14 | 36.50 | 387.33 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_4_DAYLCTRL
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 301.50 | 0.51 | 0.48 | 01-JAN-08:00 | 2649.11 | 21.19 | 85.33 | 276.67 | 1364.12 | 21.59 | 66.50 | 251.67 |
February | 282.00 | 0.50 | 0.48 | 01-FEB-08:20 | 3871.05 | 22.99 | 93.17 | 269.17 | 2163.68 | 23.45 | 76.00 | 249.33 |
March | 351.33 | 0.50 | 0.48 | 01-MAR-07:40 | 4084.09 | 21.38 | 106.17 | 334.17 | 1614.67 | 20.41 | 48.33 | 309.83 |
April | 381.83 | 0.50 | 0.48 | 01-APR-06:49 | 5024.89 | 21.37 | 110.33 | 365.17 | 2131.46 | 20.87 | 51.00 | 348.50 |
May | 378.00 | 0.50 | 0.48 | 01-MAY-06:49 | 3727.93 | 16.66 | 46.67 | 390.50 | 2152.48 | 17.54 | 0.00 | 372.33 |
June | 412.83 | 0.50 | 0.48 | 01-JUN-06:10 | 3935.48 | 12.76 | 0.00 | 391.17 | 2344.25 | 16.53 | 0.00 | 367.17 |
July | 395.33 | 0.50 | 0.48 | 01-JUL-06:00 | 3795.45 | 13.90 | 3.67 | 391.00 | 2155.92 | 17.34 | 0.00 | 369.00 |
August | 408.83 | 0.50 | 0.48 | 01-AUG-06:40 | 3762.75 | 17.71 | 62.50 | 381.17 | 2039.32 | 18.19 | 5.17 | 361.83 |
September | 359.33 | 0.50 | 0.48 | 01-SEP-06:00 | 4237.99 | 21.56 | 110.17 | 338.17 | 1745.63 | 20.76 | 55.50 | 319.67 |
October | 329.00 | 0.51 | 0.48 | 01-OCT-07:19 | 3848.20 | 21.76 | 100.00 | 311.17 | 2148.59 | 22.30 | 70.17 | 291.50 |
November | 284.17 | 0.50 | 0.48 | 01-NOV-07:19 | 3746.99 | 23.99 | 105.00 | 280.17 | 2224.40 | 24.44 | 86.67 | 261.17 |
December | 265.67 | 0.52 | 0.48 | 01-DEC-08:20 | 3449.73 | 24.43 | 106.17 | 257.17 | 2063.95 | 24.69 | 87.67 | 239.00 |
Annual Sum or Average | 4149.83 | 0.50 | 3876.47 | 19.53 | 929.17 | 3985.67 | 2020.48 | 20.32 | 547.00 | 3741.00 | ||
Minimum of Months | 265.67 | 0.50 | 0.48 | 2649.11 | 12.76 | 0.00 | 257.17 | 1364.12 | 16.53 | 0.00 | 239.00 | |
Maximum of Months | 412.83 | 0.52 | 0.48 | 5024.89 | 24.43 | 110.33 | 391.17 | 2344.25 | 24.69 | 87.67 | 372.33 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_1_DAYLCTRL
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 301.50 | 0.49 | 0.48 | 01-JAN-07:40 | 11731.00 | 37.51 | 288.83 | 288.67 | 3170.25 | 24.65 | 127.17 | 279.00 |
February | 282.00 | 0.49 | 0.48 | 01-FEB-07:40 | 14363.99 | 37.68 | 272.17 | 277.83 | 2482.45 | 21.60 | 79.67 | 266.50 |
March | 351.33 | 0.50 | 0.48 | 01-MAR-07:10 | 2717.27 | 13.98 | 10.67 | 335.00 | 1672.03 | 17.30 | 10.67 | 308.50 |
April | 381.83 | 0.51 | 0.48 | 01-APR-06:30 | 2202.52 | 14.84 | 0.00 | 357.17 | 1396.18 | 18.38 | 13.83 | 337.33 |
May | 378.00 | 0.51 | 0.48 | 01-MAY-06:30 | 1702.20 | 14.28 | 0.00 | 377.00 | 1100.19 | 17.84 | 0.00 | 350.00 |
June | 412.83 | 0.51 | 0.48 | 01-JUN-05:00 | 1359.18 | 13.26 | 0.00 | 381.33 | 889.61 | 16.90 | 0.00 | 344.50 |
July | 395.33 | 0.50 | 0.48 | 01-JUL-06:49 | 1641.55 | 14.00 | 0.00 | 382.00 | 1050.88 | 17.61 | 1.00 | 350.17 |
August | 408.83 | 0.51 | 0.48 | 01-AUG-06:19 | 2044.42 | 14.59 | 0.00 | 377.00 | 1279.54 | 18.13 | 2.00 | 354.00 |
September | 359.33 | 0.50 | 0.48 | 01-SEP-06:40 | 2669.31 | 14.84 | 16.50 | 334.67 | 1559.26 | 17.54 | 9.33 | 311.33 |
October | 329.00 | 0.50 | 0.48 | 01-OCT-06:49 | 7086.66 | 25.88 | 183.50 | 321.33 | 2094.80 | 17.34 | 18.00 | 307.50 |
November | 284.17 | 0.49 | 0.48 | 01-NOV-06:49 | 13256.04 | 38.71 | 280.17 | 286.83 | 3178.79 | 24.66 | 113.17 | 276.83 |
December | 265.67 | 0.49 | 0.48 | 01-DEC-07:49 | 13425.21 | 40.07 | 263.83 | 270.67 | 4571.01 | 28.42 | 146.67 | 263.67 |
Annual Sum or Average | 4149.83 | 0.50 | 5469.32 | 21.78 | 1315.67 | 3989.50 | 1895.33 | 19.59 | 521.50 | 3749.33 | ||
Minimum of Months | 265.67 | 0.49 | 0.48 | 1359.18 | 13.26 | 0.00 | 270.67 | 889.61 | 16.90 | 0.00 | 263.67 | |
Maximum of Months | 412.83 | 0.51 | 0.48 | 14363.99 | 40.07 | 288.83 | 382.00 | 4571.01 | 28.42 | 146.67 | 354.00 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_2_DAYLCTRL
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 301.50 | 0.51 | 0.48 | 01-JAN-07:40 | 3061.38 | 22.84 | 106.67 | 272.00 | 1740.14 | 23.33 | 87.17 | 247.83 |
February | 282.00 | 0.51 | 0.48 | 01-FEB-07:30 | 3890.17 | 22.65 | 97.00 | 271.67 | 2198.43 | 23.22 | 80.83 | 251.33 |
March | 351.33 | 0.50 | 0.48 | 01-MAR-06:00 | 3963.87 | 21.72 | 105.67 | 332.67 | 2180.45 | 22.38 | 76.33 | 308.33 |
April | 381.83 | 0.50 | 0.48 | 01-APR-05:00 | 5529.28 | 21.93 | 114.83 | 361.33 | 2320.29 | 22.12 | 67.17 | 347.67 |
May | 378.00 | 0.51 | 0.48 | 01-MAY-05:00 | 4491.61 | 20.50 | 95.50 | 381.17 | 2574.32 | 21.51 | 66.33 | 359.33 |
June | 412.83 | 0.49 | 0.48 | 01-JUN-05:19 | 4309.23 | 20.08 | 111.83 | 398.00 | 2497.04 | 21.15 | 82.67 | 369.67 |
July | 395.33 | 0.49 | 0.48 | 01-JUL-06:40 | 4294.04 | 20.64 | 103.83 | 391.17 | 2357.75 | 21.50 | 71.83 | 364.17 |
August | 408.83 | 0.50 | 0.48 | 01-AUG-05:40 | 5158.53 | 22.72 | 134.00 | 384.33 | 2184.41 | 21.94 | 75.00 | 366.83 |
September | 359.33 | 0.50 | 0.48 | 01-SEP-06:19 | 4424.17 | 21.68 | 109.67 | 338.00 | 2506.03 | 22.53 | 83.00 | 318.17 |
October | 329.00 | 0.51 | 0.48 | 01-OCT-06:30 | 4018.66 | 22.04 | 103.00 | 311.83 | 2275.43 | 22.85 | 77.67 | 292.33 |
November | 284.17 | 0.51 | 0.48 | 01-NOV-06:49 | 3228.19 | 21.61 | 80.67 | 271.67 | 1814.75 | 23.05 | 71.67 | 252.50 |
December | 265.67 | 0.52 | 0.48 | 01-DEC-07:49 | 3556.57 | 23.23 | 95.67 | 254.17 | 2092.55 | 23.47 | 78.00 | 227.50 |
Annual Sum or Average | 4149.83 | 0.50 | 4236.66 | 21.71 | 1258.33 | 3968.00 | 2252.25 | 22.32 | 917.67 | 3705.67 | ||
Minimum of Months | 265.67 | 0.49 | 0.48 | 3061.38 | 20.08 | 80.67 | 254.17 | 1740.14 | 21.15 | 66.33 | 227.50 | |
Maximum of Months | 412.83 | 0.52 | 0.48 | 5529.28 | 23.23 | 134.00 | 398.00 | 2574.32 | 23.47 | 87.17 | 369.67 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_3_DAYLCTRL
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 301.50 | 0.53 | 0.48 | 01-JAN-08:00 | 762.31 | 11.72 | 0.00 | 256.33 | 509.61 | 15.53 | 0.00 | 216.00 |
February | 282.00 | 0.52 | 0.48 | 01-FEB-08:09 | 901.31 | 12.63 | 0.00 | 259.33 | 618.68 | 16.39 | 0.00 | 229.83 |
March | 351.33 | 0.51 | 0.48 | 01-MAR-07:30 | 1067.33 | 13.34 | 0.00 | 325.83 | 698.15 | 16.94 | 0.00 | 291.00 |
April | 381.83 | 0.50 | 0.48 | 01-APR-06:19 | 1343.39 | 15.18 | 0.00 | 363.33 | 888.60 | 18.73 | 19.50 | 348.00 |
May | 378.00 | 0.50 | 0.48 | 01-MAY-06:19 | 1559.55 | 14.92 | 1.00 | 391.50 | 948.43 | 18.56 | 27.33 | 364.50 |
June | 412.83 | 0.49 | 0.48 | 01-JUN-05:40 | 1612.04 | 17.67 | 77.67 | 405.67 | 921.88 | 19.03 | 36.17 | 387.33 |
July | 395.33 | 0.49 | 0.48 | 01-JUL-06:49 | 1594.58 | 17.35 | 54.00 | 398.33 | 970.32 | 19.13 | 30.00 | 377.00 |
August | 408.83 | 0.50 | 0.48 | 01-AUG-05:00 | 1443.20 | 15.00 | 0.00 | 386.17 | 936.10 | 18.58 | 22.17 | 371.67 |
September | 359.33 | 0.50 | 0.48 | 01-SEP-06:40 | 1133.28 | 14.04 | 0.00 | 334.00 | 756.32 | 17.63 | 0.33 | 305.33 |
October | 329.00 | 0.53 | 0.48 | 01-OCT-07:19 | 828.88 | 12.28 | 0.00 | 296.33 | 588.79 | 16.05 | 0.00 | 262.50 |
November | 284.17 | 0.52 | 0.48 | 01-NOV-07:19 | 810.49 | 12.55 | 0.00 | 260.33 | 560.73 | 16.35 | 0.00 | 229.33 |
December | 265.67 | 0.55 | 0.48 | 01-DEC-08:20 | 676.08 | 11.01 | 0.00 | 238.50 | 484.80 | 14.91 | 0.00 | 198.67 |
Annual Sum or Average | 4149.83 | 0.51 | 1189.74 | 14.24 | 132.67 | 3915.67 | 764.30 | 17.51 | 135.50 | 3581.17 | ||
Minimum of Months | 265.67 | 0.49 | 0.48 | 676.08 | 11.01 | 0.00 | 238.50 | 484.80 | 14.91 | 0.00 | 198.67 | |
Maximum of Months | 412.83 | 0.55 | 0.48 | 1612.04 | 17.67 | 77.67 | 405.67 | 970.32 | 19.13 | 36.17 | 387.33 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_4_DAYLCTRL
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 301.50 | 0.51 | 0.48 | 01-JAN-08:00 | 2650.07 | 21.16 | 85.33 | 276.67 | 1365.22 | 21.57 | 66.17 | 251.83 |
February | 282.00 | 0.50 | 0.48 | 01-FEB-08:20 | 3872.10 | 22.97 | 93.17 | 269.33 | 2164.98 | 23.44 | 75.67 | 249.67 |
March | 351.33 | 0.50 | 0.48 | 01-MAR-07:40 | 4085.80 | 21.35 | 106.17 | 334.33 | 1616.18 | 20.40 | 48.33 | 310.00 |
April | 381.83 | 0.50 | 0.48 | 01-APR-06:49 | 5026.63 | 21.34 | 110.33 | 365.17 | 2133.13 | 20.85 | 51.00 | 348.50 |
May | 378.00 | 0.50 | 0.48 | 01-MAY-06:49 | 3729.55 | 16.63 | 46.67 | 390.50 | 2154.08 | 17.52 | 0.00 | 372.67 |
June | 412.83 | 0.50 | 0.48 | 01-JUN-06:10 | 3936.97 | 12.73 | 0.00 | 391.17 | 2345.61 | 16.51 | 0.00 | 367.17 |
July | 395.33 | 0.50 | 0.48 | 01-JUL-06:00 | 3797.27 | 13.86 | 3.67 | 391.00 | 2157.57 | 17.32 | 0.00 | 369.00 |
August | 408.83 | 0.50 | 0.48 | 01-AUG-06:40 | 3764.87 | 17.67 | 62.50 | 381.17 | 2041.29 | 18.17 | 5.17 | 361.83 |
September | 359.33 | 0.50 | 0.48 | 01-SEP-06:00 | 4239.64 | 21.53 | 110.17 | 338.33 | 1747.23 | 20.75 | 55.50 | 319.67 |
October | 329.00 | 0.51 | 0.48 | 01-OCT-07:19 | 3849.08 | 21.73 | 100.00 | 311.17 | 2149.72 | 22.29 | 70.17 | 291.67 |
November | 284.17 | 0.50 | 0.48 | 01-NOV-07:19 | 3747.86 | 23.96 | 105.00 | 280.17 | 2225.55 | 24.43 | 86.00 | 261.17 |
December | 265.67 | 0.52 | 0.48 | 01-DEC-08:20 | 3450.32 | 24.41 | 106.17 | 257.17 | 2064.82 | 24.67 | 87.33 | 239.00 |
Annual Sum or Average | 4149.83 | 0.50 | 3877.91 | 19.50 | 929.17 | 3986.17 | 2021.92 | 20.30 | 545.33 | 3742.17 | ||
Minimum of Months | 265.67 | 0.50 | 0.48 | 2650.07 | 12.73 | 0.00 | 257.17 | 1365.22 | 16.51 | 0.00 | 239.00 | |
Maximum of Months | 412.83 | 0.52 | 0.48 | 5026.63 | 24.41 | 110.33 | 391.17 | 2345.61 | 24.67 | 87.33 | 372.67 |
Report: CoilReportMonthly
For: VAV_BOT WITH REHEAT HEATING COIL
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.342111E+10 | 23731.33 | 21-JAN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.156008E+10 | 21173.65 | 04-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.146694E+09 | 10117.82 | 04-MAR-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 2941894.57 | 1227.45 | 08-APR-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.125354E+09 | 12337.00 | 26-OCT-06:55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.171076E+09 | 11926.83 | 27-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.174098E+10 | 20312.19 | 15-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.716824E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.342111E+10 | 23731.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_BOTTOM VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.150833E+09 | 14385.70 | 23-JAN-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 64495394.28 | 14345.68 | 04-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 524392.06 | 448.68 | 27-NOV-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 43281369.89 | 8185.52 | 23-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.259134E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.150833E+09 | 14385.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.315617E+09 | 12339.10 | 19-JAN-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.138818E+09 | 12363.93 | 01-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 12767329.70 | 6538.03 | 04-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 35801.54 | 59.67 | 08-APR-05:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 16849580.00 | 2580.01 | 26-OCT-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 23829712.89 | 8926.29 | 28-NOV-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.273335E+09 | 12382.75 | 14-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.781252E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.315617E+09 | 12382.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.232473E+09 | 17438.67 | 17-JAN-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.101315E+09 | 17422.68 | 04-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 4974855.54 | 8228.68 | 04-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 9346536.24 | 3646.61 | 26-OCT-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6593566.54 | 5622.50 | 27-NOV-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.125526E+09 | 17455.81 | 04-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.480229E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.232473E+09 | 17455.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 68995680.88 | 10360.40 | 17-JAN-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 9983889.13 | 10410.12 | 06-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 78979570.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 68995680.88 | 10410.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV_MID WITH REHEAT HEATING COIL
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.693982E+11 | 260979.86 | 21-JAN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.370559E+11 | 233912.22 | 04-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.798007E+10 | 139922.16 | 04-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.105800E+10 | 78350.11 | 08-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 5260532.57 | 5957.40 | 06-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.485921E+10 | 163250.11 | 26-OCT-06:55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.124186E+11 | 201679.25 | 27-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.617233E+11 | 258615.09 | 15-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.194499E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.693982E+11 | 260979.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_MID VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.241587E+11 | 159045.55 | 18-JAN-05:23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.152180E+11 | 158999.36 | 07-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.425504E+10 | 170851.31 | 10-MAR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.303721E+09 | 171757.59 | 08-APR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6259089.43 | 6278.99 | 06-MAY-05:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.149080E+10 | 171724.08 | 27-OCT-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.658401E+10 | 171762.59 | 17-NOV-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.253915E+11 | 159063.54 | 09-DEC-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.774080E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.253915E+11 | 171762.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.184225E+11 | 179196.14 | 19-JAN-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.105662E+11 | 179230.09 | 07-FEB-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.325411E+10 | 178717.99 | 04-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.316139E+09 | 113716.66 | 08-APR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 55190637.81 | 23428.16 | 06-MAY-05:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.176261E+10 | 177827.93 | 25-OCT-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.496124E+10 | 179191.27 | 27-NOV-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.173466E+11 | 179188.94 | 23-DEC-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.566846E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.184225E+11 | 179230.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.985698E+10 | 204274.89 | 18-JAN-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.593358E+10 | 203478.06 | 06-FEB-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.192144E+10 | 202250.85 | 04-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.222875E+09 | 121470.47 | 08-APR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 22347749.28 | 8244.07 | 05-MAY-05:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.751120E+09 | 165269.80 | 25-OCT-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.137734E+10 | 202292.37 | 28-NOV-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.859159E+10 | 204274.06 | 26-DEC-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.286773E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.985698E+10 | 204274.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.173453E+11 | 178846.70 | 17-JAN-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.106275E+11 | 178815.07 | 06-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.377675E+10 | 178541.86 | 04-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.310725E+09 | 38501.86 | 08-APR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.116587E+09 | 22156.59 | 05-MAY-05:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 7250083.60 | 9601.69 | 09-JUN-05:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.164992E+10 | 122177.55 | 25-OCT-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.478744E+10 | 178519.95 | 27-NOV-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.169381E+11 | 178657.06 | 11-DEC-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.555595E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.173453E+11 | 178846.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV_TOP WITH REHEAT HEATING COIL
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.965304E+10 | 31999.83 | 21-JAN-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.583700E+10 | 29865.51 | 04-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.177704E+10 | 19962.93 | 04-MAR-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.348507E+09 | 12904.93 | 08-APR-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 32347378.59 | 4638.81 | 06-MAY-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.115039E+10 | 22264.62 | 26-OCT-06:55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.261438E+10 | 26080.92 | 27-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.951560E+10 | 32922.78 | 15-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.309283E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.965304E+10 | 32922.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_TOP VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.281146E+10 | 85553.28 | 02-JAN-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.120072E+10 | 85503.29 | 06-FEB-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.127044E+09 | 84574.65 | 06-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 16494296.92 | 19021.77 | 26-OCT-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.695339E+09 | 85457.98 | 27-NOV-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.254646E+10 | 85562.58 | 04-DEC-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.739752E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.281146E+10 | 85562.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.614481E+10 | 18099.36 | 18-JAN-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.400653E+10 | 18102.21 | 27-FEB-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.167337E+10 | 18035.55 | 06-MAR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.322640E+09 | 17944.25 | 20-APR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 49964202.54 | 17878.50 | 05-MAY-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 331279.22 | 2208.53 | 09-JUN-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.751552E+09 | 18016.59 | 25-OCT-04:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.256518E+10 | 18102.75 | 13-NOV-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.635955E+10 | 18097.13 | 05-DEC-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.218739E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.635955E+10 | 18102.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.357649E+10 | 20501.78 | 20-JAN-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.218192E+10 | 20479.91 | 06-FEB-04:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.963756E+09 | 20433.81 | 22-MAR-04:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.145482E+09 | 20431.01 | 08-APR-04:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 28392420.30 | 13503.73 | 05-MAY-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 860558.98 | 738.64 | 02-JUN-05:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 754397.04 | 618.63 | 09-SEP-05:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.498554E+09 | 20427.79 | 25-OCT-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.136760E+10 | 20454.68 | 06-NOV-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.344464E+10 | 20505.55 | 26-DEC-04:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.122084E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.357649E+10 | 20505.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.282098E+10 | 22421.77 | 19-JAN-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.185079E+10 | 22414.06 | 07-FEB-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.105041E+10 | 22413.06 | 06-MAR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.264410E+09 | 22197.67 | 08-APR-04:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 80749344.32 | 22255.92 | 05-MAY-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 8050699.73 | 5160.97 | 09-JUN-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.404437E+09 | 22280.40 | 26-OCT-04:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.902036E+09 | 22279.94 | 28-NOV-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.251018E+10 | 22471.03 | 27-DEC-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.989205E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.282098E+10 | 22471.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.348809E+10 | 21232.45 | 18-JAN-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.227307E+10 | 21268.66 | 06-FEB-04:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.116689E+10 | 21211.58 | 03-MAR-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.213049E+09 | 10571.69 | 08-APR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 71685458.97 | 14262.72 | 05-MAY-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 11976913.95 | 4217.08 | 09-JUN-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 862445.70 | 273.37 | 09-SEP-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.547530E+09 | 21212.09 | 25-OCT-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.141710E+10 | 21222.61 | 27-NOV-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.334974E+10 | 21274.67 | 22-DEC-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.125400E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.348809E+10 | 21274.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CAV_BAS HEATING COIL
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 110.35 | 0.74 | 08-NOV-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 110.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 110.35 | 0.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BASEMENT HEATING COIL
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BOT HEATING COIL
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER MID HEATING COIL
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER TOP HEATING COIL
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BOT_SUPPHEATCOIL
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER MID_SUPPHEATCOIL
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER TOP_SUPPHEATCOIL
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV_BOT WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.136696E+10 | 0.136696E+10 | 29283.20 | 05-JAN-15:20 | 29283.20 | 0.00 |
February | 0.00 | 0.00 | 0.383700E+10 | 0.383700E+10 | 83705.33 | 14-FEB-16:00 | 83705.33 | 0.00 |
March | 0.00 | 0.00 | 0.123135E+11 | 0.123135E+11 | 90152.97 | 08-MAR-16:00 | 90152.97 | 0.00 |
April | 0.00 | 0.00 | 0.418582E+11 | 0.418582E+11 | 126970.26 | 28-APR-14:50 | 126970.26 | 0.00 |
May | 0.00 | 0.00 | 0.637057E+11 | 0.637057E+11 | 129796.56 | 30-MAY-14:30 | 129796.56 | 0.08 |
June | 0.00 | 0.00 | 0.121827E+12 | 0.121822E+12 | 164542.32 | 29-JUN-05:02 | 156281.91 | 0.32 |
July | 0.00 | 0.00 | 0.153901E+12 | 0.149875E+12 | 169550.66 | 02-JUL-15:21 | 127024.53 | 0.74 |
August | 0.00 | 0.00 | 0.156025E+12 | 0.151838E+12 | 171757.56 | 23-AUG-16:00 | 107789.19 | 0.83 |
September | 0.00 | 0.00 | 0.910556E+11 | 0.897070E+11 | 183291.27 | 05-SEP-13:30 | 112627.39 | 0.44 |
October | 0.00 | 0.00 | 0.443653E+11 | 0.443432E+11 | 128702.52 | 10-OCT-16:00 | 128702.52 | 0.11 |
November | 0.00 | 0.00 | 0.298001E+10 | 0.298001E+10 | 44936.37 | 02-NOV-15:00 | 44936.37 | 0.00 |
December | 0.00 | 0.00 | 813330.00 | 813330.00 | 5403.58 | 24-DEC-14:42 | 5403.58 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.693236E+12 | 0.683647E+12 | 0.21 | |||
Minimum of Months | 0.00 | 0.00 | 813330.00 | 813330.00 | 5403.58 | 5403.58 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.156025E+12 | 0.151838E+12 | 183291.27 | 156281.91 | 0.83 |
Report: CoilReportMonthly
For: VAV_MID WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.117631E+11 | 0.117631E+11 | 249111.58 | 05-JAN-16:00 | 249111.58 | 0.00 |
February | 0.00 | 0.00 | 0.321817E+11 | 0.321817E+11 | 702298.56 | 14-FEB-16:00 | 702298.56 | 0.00 |
March | 0.00 | 0.00 | 0.966714E+11 | 0.966714E+11 | 728823.49 | 08-MAR-16:00 | 728823.49 | 0.00 |
April | 0.00 | 0.00 | 0.317722E+12 | 0.317722E+12 | 1085531.75 | 26-APR-15:10 | 1085531.75 | 0.00 |
May | 0.00 | 0.00 | 0.557186E+12 | 0.557186E+12 | 1190232.39 | 19-MAY-15:10 | 1190232.39 | 0.08 |
June | 0.00 | 0.00 | 0.105889E+13 | 0.105876E+13 | 1444032.39 | 28-JUN-14:50 | 1444032.39 | 0.30 |
July | 0.00 | 0.00 | 0.127246E+13 | 0.124480E+13 | 1615866.11 | 02-JUL-15:21 | 1222149.47 | 0.61 |
August | 0.00 | 0.00 | 0.122201E+13 | 0.119413E+13 | 1628213.79 | 13-AUG-15:31 | 1228373.79 | 0.64 |
September | 0.00 | 0.00 | 0.811758E+12 | 0.799554E+12 | 1612724.22 | 05-SEP-13:40 | 1008124.98 | 0.43 |
October | 0.00 | 0.00 | 0.377239E+12 | 0.377087E+12 | 1158028.47 | 06-OCT-15:30 | 1158028.47 | 0.10 |
November | 0.00 | 0.00 | 0.225664E+11 | 0.225664E+11 | 369817.33 | 02-NOV-15:00 | 369817.33 | 0.00 |
December | 0.00 | 0.00 | 11532069.06 | 11532069.06 | 46379.48 | 24-DEC-14:42 | 46379.48 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.578046E+13 | 0.571242E+13 | 0.18 | |||
Minimum of Months | 0.00 | 0.00 | 11532069.06 | 11532069.06 | 46379.48 | 46379.48 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.127246E+13 | 0.124480E+13 | 1628213.79 | 1444032.39 | 0.64 |
Report: CoilReportMonthly
For: VAV_TOP WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.923031E+09 | 0.923031E+09 | 22426.91 | 05-JAN-15:30 | 22426.91 | 0.00 |
February | 0.00 | 0.00 | 0.289354E+10 | 0.289354E+10 | 70596.37 | 14-FEB-16:00 | 70596.37 | 0.00 |
March | 0.00 | 0.00 | 0.851354E+10 | 0.851354E+10 | 76199.70 | 08-MAR-16:00 | 76199.70 | 0.00 |
April | 0.00 | 0.00 | 0.329886E+11 | 0.329886E+11 | 129863.84 | 26-APR-15:00 | 129863.84 | 0.00 |
May | 0.00 | 0.00 | 0.604951E+11 | 0.604951E+11 | 142526.02 | 19-MAY-15:10 | 142526.02 | 0.07 |
June | 0.00 | 0.00 | 0.118431E+12 | 0.118425E+12 | 174900.03 | 28-JUN-14:50 | 174900.03 | 0.30 |
July | 0.00 | 0.00 | 0.143884E+12 | 0.140992E+12 | 192936.43 | 16-JUL-14:41 | 149936.62 | 0.61 |
August | 0.00 | 0.00 | 0.136008E+12 | 0.133338E+12 | 179265.43 | 13-AUG-16:21 | 147285.68 | 0.65 |
September | 0.00 | 0.00 | 0.869028E+11 | 0.859218E+11 | 176848.29 | 05-SEP-13:30 | 109366.85 | 0.41 |
October | 0.00 | 0.00 | 0.379018E+11 | 0.379010E+11 | 130648.79 | 06-OCT-15:20 | 130648.79 | 0.09 |
November | 0.00 | 0.00 | 0.176442E+10 | 0.176442E+10 | 36545.19 | 02-NOV-15:00 | 36545.19 | 0.00 |
December | 0.00 | 0.00 | 637380.28 | 637380.28 | 3807.41 | 24-DEC-14:31 | 3807.41 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.630707E+12 | 0.624156E+12 | 0.18 | |||
Minimum of Months | 0.00 | 0.00 | 637380.28 | 637380.28 | 3807.41 | 3807.41 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.143884E+12 | 0.140992E+12 | 192936.43 | 174900.03 | 0.65 |
Report: CoilReportMonthly
For: CAV_BAS COOLING COIL
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 982666.17 | 982666.17 | 8920.71 | 01-JAN-14:21 | 8920.71 | 0.00 |
February | 0.00 | 0.00 | 0.146251E+10 | 0.146251E+10 | 47158.73 | 13-FEB-16:00 | 47158.73 | 0.00 |
March | 0.00 | 0.00 | 0.399036E+10 | 0.399036E+10 | 50259.86 | 08-MAR-16:00 | 50259.86 | 0.00 |
April | 0.00 | 0.00 | 0.213478E+11 | 0.213478E+11 | 69075.70 | 17-APR-15:00 | 69075.70 | 0.00 |
May | 0.00 | 0.00 | 0.374603E+11 | 0.374529E+11 | 99544.22 | 29-MAY-13:50 | 99544.22 | 0.05 |
June | 0.00 | 0.00 | 0.687513E+11 | 0.687263E+11 | 115946.64 | 18-JUN-18:53 | 115946.64 | 0.25 |
July | 0.00 | 0.00 | 0.830827E+11 | 0.820854E+11 | 156098.90 | 02-JUL-15:18 | 96855.80 | 0.52 |
August | 0.00 | 0.00 | 0.831867E+11 | 0.820969E+11 | 130768.18 | 13-AUG-15:21 | 105547.82 | 0.56 |
September | 0.00 | 0.00 | 0.557166E+11 | 0.550594E+11 | 110120.00 | 05-SEP-13:00 | 74314.20 | 0.36 |
October | 0.00 | 0.00 | 0.256299E+11 | 0.256139E+11 | 114386.04 | 01-OCT-12:43 | 114386.04 | 0.10 |
November | 0.00 | 0.00 | 0.602501E+09 | 0.602501E+09 | 31445.62 | 09-NOV-05:12 | 31445.62 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.381232E+12 | 0.378439E+12 | 0.15 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.831867E+11 | 0.820969E+11 | 156098.90 | 115946.64 | 0.56 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BASEMENT COOLING COIL
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.116311E+11 | 0.100706E+11 | 5622.11 | 11-JAN-12:10 | 4881.65 | 0.00 |
February | 0.00 | 0.00 | 0.157650E+11 | 0.142723E+11 | 107024.53 | 14-FEB-16:00 | 107024.53 | 0.00 |
March | 0.00 | 0.00 | 0.475737E+11 | 0.466400E+11 | 214051.94 | 08-MAR-16:00 | 214051.94 | 0.00 |
April | 0.00 | 0.00 | 0.277748E+12 | 0.275738E+12 | 355809.65 | 28-APR-14:30 | 355809.65 | 0.00 |
May | 0.00 | 0.00 | 0.693285E+11 | 0.671811E+11 | 147462.82 | 22-MAY-12:10 | 136174.38 | 0.00 |
June | 0.00 | 0.00 | 0.326675E+12 | 0.304205E+12 | 308829.71 | 30-JUN-14:00 | 221292.10 | 0.00 |
July | 0.00 | 0.00 | 0.822170E+12 | 0.640425E+12 | 451661.67 | 31-JUL-24:00 | 208609.86 | 0.00 |
August | 0.00 | 0.00 | 0.104211E+13 | 0.780443E+12 | 461459.61 | 26-AUG-10:00 | 197139.10 | 0.00 |
September | 0.00 | 0.00 | 0.985963E+11 | 0.887073E+11 | 172267.07 | 01-SEP-12:40 | 137993.64 | 0.00 |
October | 0.00 | 0.00 | 0.827984E+11 | 0.750185E+11 | 250919.09 | 10-OCT-13:30 | 227712.26 | 0.00 |
November | 0.00 | 0.00 | 0.186277E+11 | 0.172692E+11 | 131072.78 | 09-NOV-14:00 | 125048.42 | 0.00 |
December | 0.00 | 0.00 | 0.161835E+11 | 0.157423E+11 | 53940.87 | 24-DEC-15:00 | 53940.87 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.282920E+13 | 0.233571E+13 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.116311E+11 | 0.100706E+11 | 5622.11 | 4881.65 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.104211E+13 | 0.780443E+12 | 461459.61 | 355809.65 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BOT COOLING COIL
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.485875E+10 | 0.485811E+10 | 3221.48 | 26-JAN-17:00 | 3221.48 | 0.00 |
February | 0.00 | 0.00 | 0.939082E+10 | 0.938795E+10 | 5292.49 | 15-FEB-17:00 | 5292.49 | 0.00 |
March | 0.00 | 0.00 | 0.160087E+11 | 0.160034E+11 | 7809.11 | 31-MAR-24:00 | 7809.11 | 0.00 |
April | 0.00 | 0.00 | 0.207955E+11 | 0.207945E+11 | 9340.26 | 16-APR-18:22 | 9340.26 | 0.00 |
May | 0.00 | 0.00 | 0.643609E+10 | 0.639487E+10 | 4214.68 | 31-MAY-24:00 | 4214.68 | 0.00 |
June | 0.00 | 0.00 | 0.115110E+11 | 0.114225E+11 | 6075.28 | 30-JUN-23:40 | 6058.49 | 0.00 |
July | 0.00 | 0.00 | 0.170960E+11 | 0.168870E+11 | 7961.68 | 31-JUL-23:55 | 7961.68 | 0.00 |
August | 0.00 | 0.00 | 0.221867E+11 | 0.219685E+11 | 8980.56 | 23-AUG-16:00 | 8585.03 | 0.00 |
September | 0.00 | 0.00 | 0.654409E+10 | 0.639432E+10 | 4225.88 | 30-SEP-23:40 | 4196.37 | 0.00 |
October | 0.00 | 0.00 | 0.113607E+11 | 0.113013E+11 | 6010.80 | 31-OCT-24:00 | 6010.80 | 0.00 |
November | 0.00 | 0.00 | 0.154090E+11 | 0.153957E+11 | 7249.95 | 02-NOV-16:40 | 7104.93 | 0.00 |
December | 0.00 | 0.00 | 0.205953E+11 | 0.205951E+11 | 8988.25 | 31-DEC-16:33 | 8988.25 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.162192E+12 | 0.161403E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.485875E+10 | 0.485811E+10 | 3221.48 | 3221.48 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.221867E+11 | 0.219685E+11 | 9340.26 | 9340.26 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER MID COOLING COIL
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.303051E+11 | 0.302984E+11 | 29969.38 | 26-JAN-17:00 | 29969.38 | 0.00 |
February | 0.00 | 0.00 | 0.767546E+11 | 0.767256E+11 | 50232.14 | 15-FEB-17:00 | 50232.14 | 0.00 |
March | 0.00 | 0.00 | 0.142810E+12 | 0.142756E+12 | 72064.23 | 31-MAR-23:30 | 72064.23 | 0.00 |
April | 0.00 | 0.00 | 0.193340E+12 | 0.193329E+12 | 88961.71 | 16-APR-18:05 | 88961.71 | 0.00 |
May | 0.00 | 0.00 | 0.573641E+11 | 0.569592E+11 | 39940.29 | 31-MAY-24:00 | 39940.29 | 0.00 |
June | 0.00 | 0.00 | 0.108237E+12 | 0.107361E+12 | 58717.55 | 30-JUN-23:53 | 58482.31 | 0.00 |
July | 0.00 | 0.00 | 0.162924E+12 | 0.160842E+12 | 76597.46 | 31-JUL-23:55 | 76597.46 | 0.00 |
August | 0.00 | 0.00 | 0.210494E+12 | 0.208312E+12 | 85774.66 | 11-AUG-18:30 | 84083.79 | 0.00 |
September | 0.00 | 0.00 | 0.591929E+11 | 0.577233E+11 | 39718.60 | 30-SEP-23:30 | 39386.84 | 0.00 |
October | 0.00 | 0.00 | 0.101153E+12 | 0.100569E+12 | 55086.61 | 31-OCT-24:00 | 55086.61 | 0.00 |
November | 0.00 | 0.00 | 0.134370E+12 | 0.134239E+12 | 68691.26 | 02-NOV-16:40 | 67271.19 | 0.00 |
December | 0.00 | 0.00 | 0.178446E+12 | 0.178444E+12 | 82445.35 | 29-DEC-16:50 | 82445.35 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.145539E+13 | 0.144756E+13 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.303051E+11 | 0.302984E+11 | 29969.38 | 29969.38 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.210494E+12 | 0.208312E+12 | 88961.71 | 88961.71 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER TOP COOLING COIL
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.158525E+10 | 0.158469E+10 | 2935.71 | 26-JAN-17:00 | 2935.71 | 0.00 |
February | 0.00 | 0.00 | 0.638231E+10 | 0.637950E+10 | 5068.77 | 15-FEB-17:00 | 5068.77 | 0.00 |
March | 0.00 | 0.00 | 0.133499E+11 | 0.133447E+11 | 6885.15 | 24-MAR-17:40 | 6885.15 | 0.00 |
April | 0.00 | 0.00 | 0.189061E+11 | 0.189051E+11 | 8886.94 | 16-APR-17:53 | 8886.94 | 0.00 |
May | 0.00 | 0.00 | 0.554330E+10 | 0.550304E+10 | 3941.57 | 31-MAY-23:40 | 3941.57 | 0.00 |
June | 0.00 | 0.00 | 0.108347E+11 | 0.107473E+11 | 5875.23 | 30-JUN-23:53 | 5851.47 | 0.00 |
July | 0.00 | 0.00 | 0.164280E+11 | 0.162200E+11 | 7845.15 | 04-JUL-18:40 | 7845.15 | 0.00 |
August | 0.00 | 0.00 | 0.211386E+11 | 0.209206E+11 | 8709.13 | 11-AUG-18:20 | 8548.78 | 0.00 |
September | 0.00 | 0.00 | 0.580850E+10 | 0.566184E+10 | 3937.61 | 30-SEP-23:20 | 3901.45 | 0.00 |
October | 0.00 | 0.00 | 0.946597E+10 | 0.940781E+10 | 5341.06 | 04-OCT-17:00 | 5328.57 | 0.00 |
November | 0.00 | 0.00 | 0.121242E+11 | 0.121113E+11 | 6877.56 | 02-NOV-16:40 | 6735.21 | 0.00 |
December | 0.00 | 0.00 | 0.160335E+11 | 0.160333E+11 | 8198.68 | 29-DEC-16:50 | 8198.68 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.137600E+12 | 0.136819E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.158525E+10 | 0.158469E+10 | 2935.71 | 2935.71 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.211386E+11 | 0.209206E+11 | 8886.94 | 8886.94 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 63593.39 | 1285339.93 | 18-JAN-05:01 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 40391.12 | 1307570.70 | 27-FEB-06:01 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 10403.24 | 1253627.72 | 04-MAR-05:01 |
April | 0.00 | 0.00 | 01-APR-00:10 | 1340.75 | 776792.78 | 08-APR-05:03 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 171.98 | 134629.29 | 05-MAY-05:02 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 10.39 | 12902.77 | 09-JUN-05:03 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 01-JUL-00:05 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 01-AUG-00:03 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.57 | 620.42 | 09-SEP-05:50 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 5194.69 | 1087960.65 | 25-OCT-05:02 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 15255.95 | 1335031.59 | 27-NOV-05:01 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 59161.75 | 1309877.42 | 04-DEC-05:01 |
Annual Sum or Average | 0.00 | 16228.65 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.00 | 0.00 | 63593.39 | 1335031.59 |
Report: PlantLoopDemandReportMonthly
For: COOLSYS1_SUPPLY
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 5839.67 | 301759.67 | 05-JAN-15:30 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 18006.24 | 1016543.11 | 14-FEB-16:00 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 46760.80 | 1017903.70 | 08-MAR-16:00 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 165581.84 | 1401666.80 | 13-APR-15:20 | 0.00 | 0.00 | 01-APR-00:10 |
May | 279344.63 | 1601610.87 | 23-MAY-11:30 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 543172.76 | 1852356.11 | 28-JUN-14:50 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 637766.49 | 1907583.25 | 31-JUL-15:30 | 0.00 | 0.00 | 01-JUL-00:05 |
August | 617584.09 | 1858591.76 | 23-AUG-16:00 | 0.00 | 0.00 | 01-AUG-00:03 |
September | 416294.77 | 2084113.53 | 05-SEP-13:10 | 0.00 | 0.00 | 01-SEP-00:03 |
October | 188904.86 | 2016414.23 | 02-OCT-12:02 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 11465.71 | 463602.36 | 02-NOV-15:10 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 644.72 | 29898.61 | 24-DEC-15:11 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 245703.65 | 0.00 | ||||
Minimum of Months | 644.72 | 29898.61 | 0.00 | 0.00 | ||
Maximum of Months | 637766.49 | 2084113.53 | 0.00 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: COOLSYS1_DEMAND
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 5251.58 | 297038.71 | 05-JAN-15:30 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 17181.89 | 1015821.28 | 14-FEB-16:00 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 45672.94 | 1019862.25 | 08-MAR-16:00 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 163194.18 | 1393723.51 | 26-APR-15:10 | 0.00 | 0.00 | 01-APR-00:10 |
May | 276035.67 | 1773614.11 | 23-MAY-11:00 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 538922.86 | 2648942.93 | 29-JUN-05:02 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 633203.62 | 3158748.62 | 01-JUL-05:03 | 0.00 | 0.00 | 01-JUL-00:05 |
August | 612690.21 | 3197334.29 | 14-AUG-04:11 | 0.00 | 0.00 | 01-AUG-00:03 |
September | 420642.13 | 2341150.66 | 15-SEP-11:40 | 0.00 | 0.00 | 01-SEP-00:03 |
October | 188611.79 | 2777349.31 | 02-OCT-11:00 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 10781.45 | 461773.28 | 02-NOV-15:00 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 5.12 | 52489.43 | 24-DEC-14:42 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 244090.16 | 0.00 | ||||
Minimum of Months | 5.12 | 52489.43 | 0.00 | 0.00 | ||
Maximum of Months | 633203.62 | 3197334.29 | 0.00 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SINGLE WATER PLANT LOOP
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 27623.73 | 56524.56 | 26-JAN-17:00 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 64681.85 | 565671.21 | 14-FEB-16:00 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 126281.65 | 882572.01 | 08-MAR-16:00 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 407911.10 | 1453670.48 | 13-APR-17:00 | 0.00 | 0.00 | 01-APR-00:10 |
May | 225191.21 | 1060363.22 | 19-MAY-16:00 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 705879.86 | 1874694.04 | 28-JUN-16:00 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 1248469.21 | 2092818.37 | 22-JUL-15:00 | 0.00 | 0.00 | 01-JUL-00:05 |
August | 1378095.23 | 2149290.36 | 20-AUG-16:00 | 0.00 | 0.00 | 01-AUG-00:03 |
September | 313815.98 | 1199308.31 | 03-SEP-14:00 | 0.00 | 0.00 | 01-SEP-00:03 |
October | 189619.04 | 1248107.20 | 01-OCT-16:00 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 92876.73 | 482751.20 | 09-NOV-14:00 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 112893.31 | 180222.15 | 24-DEC-15:00 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 410901.31 | 0.00 | ||||
Minimum of Months | 27623.73 | 56524.56 | 0.00 | 0.00 | ||
Maximum of Months | 1378095.23 | 2149290.36 | 0.00 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 15580.01 | 52436.84 | 31-JAN-12:15 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 15777.82 | 52482.07 | 09-FEB-12:10 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 16291.72 | 51962.79 | 01-MAR-13:00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 14618.94 | 49700.76 | 03-APR-11:20 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 14110.92 | 46830.42 | 01-MAY-11:40 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 13483.82 | 43456.74 | 01-JUN-12:00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 11961.35 | 40703.94 | 03-JUL-11:40 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 12834.43 | 40002.95 | 31-AUG-11:30 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 12494.69 | 41919.56 | 29-SEP-11:30 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 13224.05 | 45166.75 | 31-OCT-11:50 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 14323.82 | 48432.81 | 30-NOV-12:30 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 14686.68 | 50995.11 | 29-DEC-12:40 |
Annual Sum or Average | 0.00 | 14106.25 | ||||
Minimum of Months | 0.00 | 0.00 | 11961.35 | 40002.95 | ||
Maximum of Months | 0.00 | 0.00 | 16291.72 | 52482.07 |
Report: PlantLoopDemandReportMonthly
For: TOWERWATERSYS
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 4805.15 | 368114.15 | 05-JAN-15:30 | 3284.77 | 152777.72 | 12-JAN-05:42 |
February | 18534.25 | 1160591.18 | 14-FEB-16:00 | 4557.10 | 140509.68 | 28-FEB-07:00 |
March | 52860.61 | 1160897.54 | 08-MAR-16:10 | 2117.04 | 138773.32 | 19-MAR-13:43 |
April | 202560.82 | 2348808.07 | 26-APR-15:20 | 2522.75 | 137031.27 | 01-APR-05:50 |
May | 348234.82 | 2491625.77 | 19-MAY-16:00 | 891.27 | 123965.87 | 05-MAY-07:50 |
June | 713386.88 | 2512295.14 | 29-JUN-09:10 | 613.69 | 84671.51 | 19-JUN-02:70 |
July | 858693.35 | 3481232.09 | 31-JUL-15:00 | 261.84 | 44134.27 | 22-JUL-04:00 |
August | 807917.67 | 3042229.65 | 23-AUG-16:00 | 882.82 | 55219.86 | 25-AUG-05:40 |
September | 554649.58 | 3532374.41 | 05-SEP-13:10 | 449.14 | 80674.73 | 30-SEP-06:00 |
October | 240967.72 | 2503646.78 | 02-OCT-11:40 | 2158.56 | 143257.69 | 25-OCT-12:20 |
November | 10652.92 | 546319.71 | 02-NOV-15:10 | 2648.76 | 139255.71 | 16-NOV-09:20 |
December | 10.78 | 8489.42 | 14-DEC-06:13 | 6846.44 | 148393.87 | 04-DEC-15:00 |
Annual Sum or Average | 319656.60 | 2258.50 | ||||
Minimum of Months | 10.78 | 8489.42 | 261.84 | 44134.27 | ||
Maximum of Months | 858693.35 | 3532374.41 | 6846.44 | 152777.72 |
Report: FanReportMonthly
For: CAV_BAS FAN
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.192425E+11 | 0.98 | 12315.28 | 01-JAN-00:23 | 1.68 |
February | 0.172400E+11 | 0.97 | 12315.28 | 01-FEB-05:01 | 1.69 |
March | 0.196379E+11 | 1.00 | 12315.28 | 01-MAR-04:05 | 1.68 |
April | 0.180222E+11 | 0.95 | 12315.28 | 01-APR-04:12 | 1.69 |
May | 0.195279E+11 | 0.99 | 12315.28 | 01-MAY-00:10 | 1.69 |
June | 0.194281E+11 | 1.02 | 12315.28 | 01-JUN-04:12 | 1.67 |
July | 0.198197E+11 | 1.00 | 12315.28 | 01-JUL-04:12 | 1.66 |
August | 0.210405E+11 | 1.06 | 12315.28 | 01-AUG-04:12 | 1.67 |
September | 0.198759E+11 | 1.04 | 12315.28 | 01-SEP-04:12 | 1.67 |
October | 0.205301E+11 | 1.04 | 12315.28 | 01-OCT-11:16 | 1.67 |
November | 0.190994E+11 | 1.01 | 12315.28 | 01-NOV-04:12 | 1.67 |
December | 0.190834E+11 | 0.97 | 12315.28 | 01-DEC-05:12 | 1.68 |
Annual Sum or Average | 0.232548E+12 | 1.00 | |||
Minimum of Months | 0.172400E+11 | 0.95 | 12315.28 | 1.66 | |
Maximum of Months | 0.210405E+11 | 1.06 | 12315.28 | 1.69 |
Report: FanReportMonthly
For: VAV_BOT WITH REHEAT FAN
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.591385E+10 | 0.41 | 15956.61 | 21-JAN-06:01 | 1.54 |
February | 0.635582E+10 | 0.44 | 15956.61 | 04-FEB-06:01 | 1.55 |
March | 0.965887E+10 | 0.53 | 16768.81 | 15-MAR-15:50 | 1.59 |
April | 0.131144E+11 | 0.65 | 21785.20 | 28-APR-14:50 | 1.87 |
May | 0.118330E+11 | 0.59 | 23554.14 | 22-MAY-04:12 | 1.95 |
June | 0.153257E+11 | 0.73 | 26924.54 | 29-JUN-05:02 | 2.12 |
July | 0.172756E+11 | 0.79 | 26924.54 | 05-JUL-05:02 | 2.13 |
August | 0.191603E+11 | 0.87 | 26924.54 | 21-AUG-04:12 | 2.12 |
September | 0.114369E+11 | 0.59 | 25942.46 | 05-SEP-04:12 | 2.07 |
October | 0.989271E+10 | 0.53 | 26924.54 | 02-OCT-04:12 | 2.12 |
November | 0.820615E+10 | 0.49 | 15405.12 | 03-NOV-16:00 | 1.51 |
December | 0.729832E+10 | 0.45 | 14372.65 | 04-DEC-06:01 | 1.45 |
Annual Sum or Average | 0.135472E+12 | 0.59 | |||
Minimum of Months | 0.591385E+10 | 0.41 | 14372.65 | 1.45 | |
Maximum of Months | 0.191603E+11 | 0.87 | 26924.54 | 2.13 |
Report: FanReportMonthly
For: VAV_MID WITH REHEAT FAN
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.433297E+11 | 0.38 | 72681.77 | 05-JAN-16:40 | 1.00 |
February | 0.431897E+11 | 0.39 | 114477.46 | 14-FEB-06:03 | 1.31 |
March | 0.597864E+11 | 0.43 | 122411.53 | 07-MAR-06:02 | 1.36 |
April | 0.807102E+11 | 0.50 | 167419.78 | 28-APR-15:00 | 1.65 |
May | 0.946570E+11 | 0.54 | 173412.81 | 19-MAY-15:10 | 1.68 |
June | 0.124242E+12 | 0.64 | 210397.26 | 28-JUN-14:50 | 1.90 |
July | 0.135209E+12 | 0.65 | 252322.03 | 05-JUL-04:11 | 2.13 |
August | 0.136880E+12 | 0.66 | 252322.03 | 21-AUG-04:12 | 2.12 |
September | 0.922606E+11 | 0.54 | 179873.94 | 01-SEP-05:02 | 1.71 |
October | 0.702135E+11 | 0.46 | 153616.33 | 02-OCT-04:12 | 1.55 |
November | 0.506575E+11 | 0.40 | 124680.53 | 18-NOV-06:02 | 1.38 |
December | 0.434351E+11 | 0.37 | 114968.96 | 02-DEC-06:03 | 1.32 |
Annual Sum or Average | 0.974571E+12 | 0.50 | |||
Minimum of Months | 0.431897E+11 | 0.37 | 72681.77 | 1.00 | |
Maximum of Months | 0.136880E+12 | 0.66 | 252322.03 | 2.13 |
Report: FanReportMonthly
For: VAV_TOP WITH REHEAT FAN
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.438628E+10 | 0.41 | 6119.39 | 02-JAN-05:01 | 0.86 |
February | 0.395202E+10 | 0.39 | 9965.50 | 15-FEB-16:50 | 1.13 |
March | 0.506852E+10 | 0.41 | 10868.69 | 24-MAR-16:00 | 1.19 |
April | 0.720447E+10 | 0.45 | 18574.35 | 13-APR-15:10 | 1.65 |
May | 0.899523E+10 | 0.50 | 19664.83 | 30-MAY-14:30 | 1.70 |
June | 0.128127E+11 | 0.62 | 28066.81 | 27-JUN-16:00 | 2.13 |
July | 0.143914E+11 | 0.64 | 28066.81 | 05-JUL-04:11 | 2.13 |
August | 0.142477E+11 | 0.64 | 27140.48 | 22-AUG-04:12 | 2.07 |
September | 0.893802E+10 | 0.50 | 20314.31 | 01-SEP-16:00 | 1.73 |
October | 0.609139E+10 | 0.41 | 15662.34 | 02-OCT-16:00 | 1.47 |
November | 0.428469E+10 | 0.38 | 8972.19 | 03-NOV-15:50 | 1.07 |
December | 0.430898E+10 | 0.40 | 6119.39 | 04-DEC-05:21 | 0.86 |
Annual Sum or Average | 0.946813E+11 | 0.48 | |||
Minimum of Months | 0.395202E+10 | 0.38 | 6119.39 | 0.86 | |
Maximum of Months | 0.143914E+11 | 0.64 | 28066.81 | 2.13 |
Report: FanReportMonthly
For: AIRLOOP DATACENTER BASEMENT SUPPLY FAN
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.114833E+12 | 1.63 | 42873.76 | 01-JAN-00:10 | 1.63 |
February | 0.103720E+12 | 1.63 | 42873.76 | 01-FEB-00:10 | 1.63 |
March | 0.114833E+12 | 1.64 | 42873.76 | 01-MAR-00:10 | 1.63 |
April | 0.111129E+12 | 1.64 | 42873.76 | 01-APR-00:10 | 1.64 |
May | 0.114833E+12 | 1.63 | 42873.76 | 01-MAY-00:10 | 1.64 |
June | 0.111129E+12 | 1.63 | 42873.76 | 01-JUN-00:10 | 1.64 |
July | 0.114833E+12 | 1.62 | 42873.76 | 01-JUL-00:05 | 1.62 |
August | 0.114833E+12 | 1.62 | 42873.76 | 01-AUG-00:03 | 1.61 |
September | 0.111129E+12 | 1.62 | 42873.76 | 01-SEP-00:03 | 1.62 |
October | 0.114833E+12 | 1.63 | 42873.76 | 01-OCT-00:10 | 1.63 |
November | 0.111129E+12 | 1.64 | 42873.76 | 01-NOV-00:10 | 1.64 |
December | 0.114833E+12 | 1.64 | 42873.76 | 01-DEC-00:10 | 1.64 |
Annual Sum or Average | 0.135207E+13 | 1.63 | |||
Minimum of Months | 0.103720E+12 | 1.62 | 42873.76 | 1.61 | |
Maximum of Months | 0.114833E+12 | 1.64 | 42873.76 | 1.64 |
Report: FanReportMonthly
For: AIRLOOP DATACENTER BOT SUPPLY FAN
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.182558E+10 | 1.12 | 681.59 | 01-JAN-00:10 | 1.11 |
February | 0.164891E+10 | 1.12 | 681.59 | 01-FEB-00:10 | 1.12 |
March | 0.182558E+10 | 1.12 | 681.59 | 01-MAR-00:10 | 1.12 |
April | 0.176669E+10 | 1.12 | 681.59 | 01-APR-00:10 | 1.12 |
May | 0.182558E+10 | 1.11 | 681.59 | 01-MAY-00:10 | 1.12 |
June | 0.176669E+10 | 1.11 | 681.59 | 01-JUN-00:10 | 1.11 |
July | 0.182558E+10 | 1.11 | 681.59 | 01-JUL-00:05 | 1.11 |
August | 0.182558E+10 | 1.11 | 681.59 | 01-AUG-00:03 | 1.11 |
September | 0.176669E+10 | 1.11 | 681.59 | 01-SEP-00:03 | 1.11 |
October | 0.182558E+10 | 1.11 | 681.59 | 01-OCT-00:10 | 1.11 |
November | 0.176669E+10 | 1.12 | 681.59 | 01-NOV-00:10 | 1.12 |
December | 0.182558E+10 | 1.12 | 681.59 | 01-DEC-00:10 | 1.12 |
Annual Sum or Average | 0.214948E+11 | 1.11 | |||
Minimum of Months | 0.164891E+10 | 1.11 | 681.59 | 1.11 | |
Maximum of Months | 0.182558E+10 | 1.12 | 681.59 | 1.12 |
Report: FanReportMonthly
For: AIRLOOP DATACENTER MID SUPPLY FAN
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.175142E+11 | 1.12 | 6539.04 | 01-JAN-00:10 | 1.11 |
February | 0.158192E+11 | 1.12 | 6539.04 | 01-FEB-00:10 | 1.12 |
March | 0.175142E+11 | 1.12 | 6539.04 | 01-MAR-00:10 | 1.12 |
April | 0.169492E+11 | 1.12 | 6539.04 | 01-APR-00:10 | 1.12 |
May | 0.175142E+11 | 1.11 | 6539.04 | 01-MAY-00:10 | 1.12 |
June | 0.169492E+11 | 1.11 | 6539.04 | 01-JUN-00:10 | 1.12 |
July | 0.175142E+11 | 1.11 | 6539.04 | 01-JUL-00:05 | 1.11 |
August | 0.175142E+11 | 1.11 | 6539.04 | 01-AUG-00:03 | 1.11 |
September | 0.169492E+11 | 1.11 | 6539.04 | 01-SEP-00:03 | 1.11 |
October | 0.175142E+11 | 1.11 | 6539.04 | 01-OCT-00:10 | 1.11 |
November | 0.169492E+11 | 1.12 | 6539.04 | 01-NOV-00:10 | 1.12 |
December | 0.175142E+11 | 1.12 | 6539.04 | 01-DEC-00:10 | 1.12 |
Annual Sum or Average | 0.206215E+12 | 1.11 | |||
Minimum of Months | 0.158192E+11 | 1.11 | 6539.04 | 1.11 | |
Maximum of Months | 0.175142E+11 | 1.12 | 6539.04 | 1.12 |
Report: FanReportMonthly
For: AIRLOOP DATACENTER TOP SUPPLY FAN
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.178689E+10 | 1.12 | 667.15 | 01-JAN-00:10 | 1.11 |
February | 0.161396E+10 | 1.12 | 667.15 | 01-FEB-00:10 | 1.12 |
March | 0.178689E+10 | 1.12 | 667.15 | 01-MAR-00:20 | 1.12 |
April | 0.172925E+10 | 1.12 | 667.15 | 01-APR-00:10 | 1.12 |
May | 0.178689E+10 | 1.11 | 667.15 | 01-MAY-00:10 | 1.12 |
June | 0.172925E+10 | 1.11 | 667.15 | 01-JUN-00:10 | 1.12 |
July | 0.178689E+10 | 1.11 | 667.15 | 01-JUL-00:05 | 1.11 |
August | 0.178689E+10 | 1.11 | 667.15 | 01-AUG-00:03 | 1.11 |
September | 0.172925E+10 | 1.11 | 667.15 | 01-SEP-00:03 | 1.11 |
October | 0.178689E+10 | 1.11 | 667.15 | 01-OCT-00:10 | 1.11 |
November | 0.172925E+10 | 1.12 | 667.15 | 01-NOV-00:10 | 1.12 |
December | 0.178689E+10 | 1.12 | 667.15 | 01-DEC-00:10 | 1.12 |
Annual Sum or Average | 0.210392E+11 | 1.11 | |||
Minimum of Months | 0.161396E+10 | 1.11 | 667.15 | 1.11 | |
Maximum of Months | 0.178689E+10 | 1.12 | 667.15 | 1.12 |
Report: PumpReportMonthly
For: HEATSYS1 PUMP
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.734341E+09 | 0.660907E+09 | 3887.28 | 17-JAN-06:01 | 3498.55 | 3498.55 | 47.29 | 6.89 |
February | 0.418473E+09 | 0.376625E+09 | 3884.37 | 06-FEB-06:01 | 3495.93 | 3495.93 | 45.74 | 6.89 |
March | 0.115122E+09 | 0.103610E+09 | 3786.21 | 06-MAR-06:01 | 3407.59 | 3407.59 | 36.92 | 6.52 |
April | 14108738.99 | 12697865.09 | 2748.59 | 08-APR-05:03 | 2473.73 | 2473.73 | 32.79 | 3.78 |
May | 1827407.53 | 1644666.77 | 516.51 | 05-MAY-05:02 | 464.86 | 464.86 | 23.37 | 0.55 |
June | 106044.15 | 95439.73 | 50.80 | 09-JUN-05:03 | 45.72 | 45.72 | 22.64 | 0.05 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 22.37 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 22.37 | 0.00 |
September | 5778.21 | 5200.39 | 2.44 | 09-SEP-05:50 | 2.20 | 2.20 | 22.36 | 0.00 |
October | 56923763.41 | 51231387.07 | 3451.58 | 25-OCT-05:02 | 3106.42 | 3106.42 | 34.14 | 5.44 |
November | 0.166431E+09 | 0.149788E+09 | 3807.60 | 28-NOV-06:01 | 3426.84 | 3426.84 | 39.23 | 6.60 |
December | 0.680415E+09 | 0.612374E+09 | 3846.10 | 22-DEC-06:01 | 3461.49 | 3461.49 | 41.94 | 6.74 |
Annual Sum or Average | 0.218775E+10 | 0.196898E+10 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.36 | 0.00 | |
Maximum of Months | 0.734341E+09 | 0.660907E+09 | 3887.28 | 3498.55 | 3498.55 | 47.29 | 6.89 |
Report: PumpReportMonthly
For: COOLSYS1 PUMP SECONDARY
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 3519827.49 | 3167844.74 | 102.76 | 05-JAN-15:30 | 92.48 | 92.48 | 6.70 | 9.69 |
February | 21656617.81 | 19490956.03 | 1022.22 | 14-FEB-16:00 | 920.00 | 920.00 | 6.71 | 31.16 |
March | 42691860.89 | 38422674.80 | 954.61 | 08-MAR-14:30 | 859.15 | 859.15 | 6.71 | 30.19 |
April | 0.195141E+09 | 0.175627E+09 | 1556.58 | 28-APR-13:00 | 1400.92 | 1400.92 | 6.72 | 37.72 |
May | 0.437487E+09 | 0.393739E+09 | 8880.94 | 23-MAY-11:00 | 7992.85 | 7992.85 | 8.77 | 78.95 |
June | 0.214000E+10 | 0.192600E+10 | 15467.39 | 27-JUN-16:00 | 13920.65 | 13920.65 | 6.73 | 98.49 |
July | 0.220256E+10 | 0.198231E+10 | 16653.22 | 05-JUL-05:02 | 14987.89 | 14987.89 | 8.06 | 101.39 |
August | 0.240930E+10 | 0.216837E+10 | 15616.88 | 14-AUG-05:02 | 14055.19 | 14055.19 | 8.64 | 98.85 |
September | 0.226503E+10 | 0.203853E+10 | 16653.22 | 18-SEP-13:03 | 14987.89 | 14987.89 | 8.85 | 101.39 |
October | 0.705073E+09 | 0.634565E+09 | 16653.22 | 02-OCT-10:43 | 14987.89 | 14987.89 | 8.90 | 101.39 |
November | 7320019.01 | 6588017.11 | 232.51 | 02-NOV-15:00 | 209.26 | 209.26 | 6.70 | 15.10 |
December | 2140.63 | 1926.57 | 9.29 | 24-DEC-14:42 | 8.36 | 8.36 | 6.70 | 1.98 |
Annual Sum or Average | 0.104298E+11 | 0.938681E+10 | ||||||
Minimum of Months | 2140.63 | 1926.57 | 9.29 | 8.36 | 8.36 | 6.70 | 1.98 | |
Maximum of Months | 0.240930E+10 | 0.216837E+10 | 16653.22 | 14987.89 | 14987.89 | 8.90 | 101.39 |
Report: PumpReportMonthly
For: COOLSYS1 CHILLER1 PUMP
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.175446E+10 | 0.157901E+10 | 5730.98 | 01-JAN-11:01 | 5157.88 | 5157.88 | 6.72 | 50.69 |
February | 0.226097E+10 | 0.203487E+10 | 5730.98 | 01-FEB-11:20 | 5157.88 | 5157.88 | 6.72 | 50.69 |
March | 0.332331E+10 | 0.299098E+10 | 5730.98 | 01-MAR-16:25 | 5157.88 | 5157.88 | 6.81 | 50.69 |
April | 0.600449E+10 | 0.540404E+10 | 5730.98 | 01-APR-05:02 | 5157.88 | 5157.88 | 6.76 | 50.69 |
May | 0.770747E+10 | 0.693673E+10 | 5730.98 | 01-MAY-04:12 | 5157.88 | 5157.88 | 6.89 | 50.69 |
June | 0.105794E+11 | 0.952142E+10 | 5730.98 | 01-JUN-04:12 | 5157.88 | 5157.88 | 9.07 | 50.69 |
July | 0.126829E+11 | 0.114146E+11 | 5730.98 | 01-JUL-00:52 | 5157.88 | 5157.88 | 6.86 | 50.69 |
August | 0.134835E+11 | 0.121351E+11 | 5730.98 | 01-AUG-00:23 | 5157.88 | 5157.88 | 6.85 | 50.69 |
September | 0.918495E+10 | 0.826646E+10 | 5730.98 | 01-SEP-00:03 | 5157.88 | 5157.88 | 6.86 | 50.69 |
October | 0.633700E+10 | 0.570330E+10 | 5730.98 | 01-OCT-06:50 | 5157.88 | 5157.88 | 7.57 | 50.69 |
November | 0.197591E+10 | 0.177832E+10 | 5730.98 | 01-NOV-04:12 | 5157.88 | 5157.88 | 6.89 | 50.69 |
December | 0.190172E+10 | 0.171155E+10 | 5730.98 | 01-DEC-06:03 | 5157.88 | 5157.88 | 6.76 | 50.69 |
Annual Sum or Average | 0.771960E+11 | 0.694764E+11 | ||||||
Minimum of Months | 0.175446E+10 | 0.157901E+10 | 5730.98 | 5157.88 | 5157.88 | 6.72 | 50.69 | |
Maximum of Months | 0.134835E+11 | 0.121351E+11 | 5730.98 | 5157.88 | 5157.88 | 9.07 | 50.69 |
Report: PumpReportMonthly
For: COOLSYS1 CHILLER2 PUMP
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 6.73 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 6.72 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 6.94 | 0.00 |
April | 0.515788E+09 | 0.464209E+09 | 5730.98 | 11-APR-13:20 | 5157.88 | 5157.88 | 12.18 | 25.35 |
May | 0.117944E+10 | 0.106149E+10 | 5730.98 | 08-MAY-12:20 | 5157.88 | 5157.88 | 12.02 | 25.35 |
June | 0.340764E+10 | 0.306688E+10 | 5730.98 | 02-JUN-15:40 | 5157.88 | 5157.88 | 13.15 | 25.35 |
July | 0.421571E+10 | 0.379414E+10 | 5730.98 | 01-JUL-11:00 | 5157.88 | 5157.88 | 12.06 | 25.35 |
August | 0.401283E+10 | 0.361155E+10 | 5730.98 | 01-AUG-07:45 | 5157.88 | 5157.88 | 9.76 | 50.69 |
September | 0.228322E+10 | 0.205490E+10 | 5730.98 | 01-SEP-09:00 | 5157.88 | 5157.88 | 12.69 | 25.35 |
October | 0.785717E+09 | 0.707145E+09 | 5730.98 | 02-OCT-11:00 | 5157.88 | 5157.88 | 13.05 | 25.35 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 6.96 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 6.79 | 0.00 |
Annual Sum or Average | 0.164003E+11 | 0.147603E+11 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.72 | 0.00 | |
Maximum of Months | 0.421571E+10 | 0.379414E+10 | 5730.98 | 5157.88 | 5157.88 | 13.15 | 50.69 |
Report: PumpReportMonthly
For: PLANT CIRC PUMP
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.100952E+11 | 0.908571E+10 | 3769.13 | 01-JAN-00:10 | 3392.22 | 3392.22 | 18.76 | 15.74 |
February | 0.911828E+10 | 0.820645E+10 | 3769.13 | 01-FEB-00:10 | 3392.22 | 3392.22 | 19.31 | 15.74 |
March | 0.100952E+11 | 0.908571E+10 | 3769.13 | 01-MAR-00:10 | 3392.22 | 3392.22 | 19.91 | 15.74 |
April | 0.976958E+10 | 0.879262E+10 | 3769.13 | 01-APR-00:10 | 3392.22 | 3392.22 | 20.54 | 15.74 |
May | 0.100952E+11 | 0.908571E+10 | 3769.13 | 01-MAY-00:10 | 3392.22 | 3392.22 | 19.15 | 15.74 |
June | 0.976958E+10 | 0.879262E+10 | 3769.13 | 01-JUN-00:10 | 3392.22 | 3392.22 | 20.55 | 15.74 |
July | 0.100952E+11 | 0.908571E+10 | 3769.13 | 01-JUL-00:05 | 3392.22 | 3392.22 | 34.54 | 15.74 |
August | 0.100952E+11 | 0.908571E+10 | 3769.13 | 01-AUG-00:03 | 3392.22 | 3392.22 | 41.46 | 15.74 |
September | 0.976958E+10 | 0.879262E+10 | 3769.13 | 01-SEP-00:03 | 3392.22 | 3392.22 | 24.00 | 15.74 |
October | 0.100952E+11 | 0.908571E+10 | 3769.13 | 01-OCT-00:10 | 3392.22 | 3392.22 | 19.56 | 15.74 |
November | 0.976958E+10 | 0.879262E+10 | 3769.13 | 01-NOV-00:10 | 3392.22 | 3392.22 | 20.06 | 15.74 |
December | 0.100952E+11 | 0.908571E+10 | 3769.13 | 01-DEC-00:10 | 3392.22 | 3392.22 | 20.41 | 15.74 |
Annual Sum or Average | 0.118863E+12 | 0.106977E+12 | ||||||
Minimum of Months | 0.911828E+10 | 0.820645E+10 | 3769.13 | 3392.22 | 3392.22 | 18.76 | 15.74 | |
Maximum of Months | 0.100952E+11 | 0.908571E+10 | 3769.13 | 3392.22 | 3392.22 | 41.46 | 15.74 |
Report: PumpReportMonthly
For: SWHSYS1 PUMP
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.112905E+09 | 33871561.48 | 56.21 | 01-JAN-06:10 | 16.86 | 16.86 | 55.78 | 0.44 |
February | 0.101979E+09 | 30593668.43 | 56.21 | 01-FEB-06:01 | 16.86 | 16.86 | 56.28 | 0.44 |
March | 0.112905E+09 | 33871561.48 | 56.21 | 01-MAR-06:03 | 16.86 | 16.86 | 55.54 | 0.44 |
April | 0.109263E+09 | 32778930.46 | 56.21 | 01-APR-05:02 | 16.86 | 16.86 | 56.09 | 0.44 |
May | 0.112905E+09 | 33871561.48 | 56.21 | 01-MAY-05:03 | 16.86 | 16.86 | 56.32 | 0.44 |
June | 0.109263E+09 | 32778930.46 | 56.21 | 01-JUN-05:02 | 16.86 | 16.86 | 57.11 | 0.44 |
July | 0.112905E+09 | 33871561.48 | 56.21 | 01-JUL-05:03 | 16.86 | 16.86 | 56.13 | 0.44 |
August | 0.112905E+09 | 33871561.48 | 56.21 | 01-AUG-05:02 | 16.86 | 16.86 | 57.33 | 0.44 |
September | 0.109263E+09 | 32778930.46 | 56.21 | 01-SEP-05:02 | 16.86 | 16.86 | 57.19 | 0.44 |
October | 0.112905E+09 | 33871561.48 | 56.21 | 01-OCT-05:10 | 16.86 | 16.86 | 56.69 | 0.44 |
November | 0.109263E+09 | 32778930.46 | 56.21 | 01-NOV-05:03 | 16.86 | 16.86 | 56.19 | 0.44 |
December | 0.112905E+09 | 33871561.48 | 56.21 | 01-DEC-06:03 | 16.86 | 16.86 | 56.08 | 0.44 |
Annual Sum or Average | 0.132937E+10 | 0.398810E+09 | ||||||
Minimum of Months | 0.101979E+09 | 30593668.43 | 56.21 | 16.86 | 16.86 | 55.54 | 0.44 | |
Maximum of Months | 0.112905E+09 | 33871561.48 | 56.21 | 16.86 | 16.86 | 57.33 | 0.44 |
Report: PumpReportMonthly
For: TOWERWATERSYS PUMP
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.453773E+10 | 0.408395E+10 | 14837.64 | 05-JAN-15:30 | 13353.88 | 13353.88 | 22.57 | 60.07 |
February | 0.584897E+10 | 0.526407E+10 | 14872.67 | 14-FEB-16:00 | 13385.41 | 13385.41 | 25.72 | 60.07 |
March | 0.860085E+10 | 0.774077E+10 | 14872.69 | 08-MAR-16:10 | 13385.42 | 13385.42 | 25.72 | 60.07 |
April | 0.165832E+11 | 0.149249E+11 | 29746.79 | 26-APR-15:20 | 26772.11 | 26772.11 | 25.78 | 120.14 |
May | 0.222327E+11 | 0.200094E+11 | 29753.88 | 19-MAY-16:00 | 26778.49 | 26778.49 | 26.06 | 120.14 |
June | 0.355072E+11 | 0.319565E+11 | 29754.91 | 29-JUN-09:10 | 26779.42 | 26779.42 | 26.10 | 120.14 |
July | 0.431730E+11 | 0.388557E+11 | 29803.12 | 31-JUL-15:00 | 26822.81 | 26822.81 | 28.03 | 120.14 |
August | 0.449350E+11 | 0.404415E+11 | 29781.26 | 23-AUG-16:00 | 26803.13 | 26803.13 | 27.16 | 120.14 |
September | 0.292153E+11 | 0.262937E+11 | 29805.67 | 05-SEP-13:10 | 26825.10 | 26825.10 | 28.13 | 120.14 |
October | 0.181377E+11 | 0.163240E+11 | 29754.48 | 02-OCT-11:40 | 26779.03 | 26779.03 | 26.09 | 120.14 |
November | 0.511117E+10 | 0.460005E+10 | 14845.22 | 02-NOV-15:10 | 13360.70 | 13360.70 | 23.28 | 60.07 |
December | 0.491764E+10 | 0.442587E+10 | 14822.37 | 14-DEC-06:13 | 13340.14 | 13340.14 | 21.13 | 60.07 |
Annual Sum or Average | 0.238800E+12 | 0.214920E+12 | ||||||
Minimum of Months | 0.453773E+10 | 0.408395E+10 | 14822.37 | 13340.14 | 13340.14 | 21.13 | 60.07 | |
Maximum of Months | 0.449350E+11 | 0.404415E+11 | 29805.67 | 26825.10 | 26825.10 | 28.13 | 120.14 |
Report: CondLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 31.39 | 31.39 | 63593.39 | 1285339.93 | 18-JAN-05:01 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 30.52 | 30.52 | 40391.12 | 1307570.70 | 27-FEB-06:01 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 23.63 | 23.63 | 10403.24 | 1253627.72 | 04-MAR-05:01 |
April | 0.00 | 0.00 | 01-APR-00:10 | 24.00 | 24.00 | 1340.75 | 776792.78 | 08-APR-05:03 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 23.50 | 23.50 | 171.98 | 134629.29 | 05-MAY-05:02 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 22.64 | 22.64 | 10.39 | 12902.77 | 09-JUN-05:03 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 22.37 | 22.37 | 0.00 | 0.00 | 01-JUL-00:05 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 22.37 | 22.37 | 0.00 | 0.00 | 01-AUG-00:03 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 22.37 | 22.37 | 0.57 | 620.42 | 09-SEP-05:50 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 22.34 | 22.34 | 5194.69 | 1087960.65 | 25-OCT-05:02 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 22.89 | 22.89 | 15255.95 | 1335031.59 | 27-NOV-05:01 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 23.87 | 23.87 | 59161.75 | 1309877.42 | 04-DEC-05:01 |
Annual Sum or Average | 0.00 | 16228.65 | ||||||
Minimum of Months | 0.00 | 0.00 | 22.34 | 22.34 | 0.00 | 0.00 | ||
Maximum of Months | 0.00 | 0.00 | 31.39 | 31.39 | 63593.39 | 1335031.59 |
Report: CondLoopDemandReportMonthly
For: COOLSYS1_SUPPLY
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 5839.67 | 301759.67 | 05-JAN-15:30 | 8.12 | 6.70 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 18006.24 | 1016543.11 | 14-FEB-16:00 | 11.49 | 6.70 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 46760.80 | 1017903.70 | 08-MAR-16:00 | 11.49 | 6.70 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 165581.84 | 1401666.80 | 13-APR-15:20 | 10.00 | 6.70 | 0.00 | 0.00 | 01-APR-00:10 |
May | 279344.63 | 1601610.87 | 23-MAY-11:30 | 10.47 | 6.70 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 543172.76 | 1852356.11 | 28-JUN-14:50 | 11.06 | 6.70 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 637766.49 | 1907583.25 | 31-JUL-15:30 | 11.19 | 6.70 | 0.00 | 0.00 | 01-JUL-00:05 |
August | 617584.09 | 1858591.76 | 23-AUG-16:00 | 11.08 | 6.70 | 0.00 | 0.00 | 01-AUG-00:03 |
September | 416294.77 | 2084113.53 | 05-SEP-13:10 | 11.61 | 6.70 | 0.00 | 0.00 | 01-SEP-00:03 |
October | 188904.86 | 2016414.23 | 02-OCT-12:02 | 11.45 | 6.70 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 11465.71 | 463602.36 | 02-NOV-15:10 | 8.88 | 6.70 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 644.72 | 29898.61 | 24-DEC-15:11 | 6.84 | 6.70 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 245703.65 | 0.00 | ||||||
Minimum of Months | 644.72 | 29898.61 | 6.84 | 6.70 | 0.00 | 0.00 | ||
Maximum of Months | 637766.49 | 2084113.53 | 11.61 | 6.70 | 0.00 | 0.00 |
Report: CondLoopDemandReportMonthly
For: COOLSYS1_DEMAND
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 5251.58 | 297038.71 | 05-JAN-15:30 | 14.02 | 6.70 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 17181.89 | 1015821.28 | 14-FEB-16:00 | 14.49 | 6.70 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 45672.94 | 1019862.25 | 08-MAR-16:00 | 16.88 | 6.70 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 163194.18 | 1393723.51 | 26-APR-15:10 | 16.83 | 6.70 | 0.00 | 0.00 | 01-APR-00:10 |
May | 276035.67 | 1773614.11 | 23-MAY-11:00 | 12.06 | 8.85 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 538922.86 | 2648942.93 | 29-JUN-05:02 | 13.92 | 9.73 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 633203.62 | 3158748.62 | 01-JUL-05:03 | 14.16 | 10.41 | 0.00 | 0.00 | 01-JUL-00:05 |
August | 612690.21 | 3197334.29 | 14-AUG-04:11 | 14.92 | 10.43 | 0.00 | 0.00 | 01-AUG-00:03 |
September | 420642.13 | 2341150.66 | 15-SEP-11:40 | 12.94 | 9.58 | 0.00 | 0.00 | 01-SEP-00:03 |
October | 188611.79 | 2777349.31 | 02-OCT-11:00 | 13.24 | 9.96 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 10781.45 | 461773.28 | 02-NOV-15:00 | 14.01 | 6.70 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 5.12 | 52489.43 | 24-DEC-14:42 | 13.03 | 6.70 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 244090.16 | 0.00 | ||||||
Minimum of Months | 5.12 | 52489.43 | 12.06 | 6.70 | 0.00 | 0.00 | ||
Maximum of Months | 633203.62 | 3197334.29 | 16.88 | 10.43 | 0.00 | 0.00 |
Report: CondLoopDemandReportMonthly
For: SINGLE WATER PLANT LOOP
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 27623.73 | 56524.56 | 26-JAN-17:00 | 19.37 | 18.33 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 64681.85 | 565671.21 | 14-FEB-16:00 | 28.61 | 24.58 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 126281.65 | 882572.01 | 08-MAR-16:00 | 34.28 | 27.08 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 407911.10 | 1453670.48 | 13-APR-17:00 | 44.34 | 32.98 | 0.00 | 0.00 | 01-APR-00:10 |
May | 225191.21 | 1060363.22 | 19-MAY-16:00 | 37.43 | 32.78 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 705879.86 | 1874694.04 | 28-JUN-16:00 | 51.65 | 43.74 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 1248469.21 | 2092818.37 | 22-JUL-15:00 | 55.40 | 44.81 | 0.00 | 0.00 | 01-JUL-00:05 |
August | 1378095.23 | 2149290.36 | 20-AUG-16:00 | 56.37 | 43.14 | 0.00 | 0.00 | 01-AUG-00:03 |
September | 313815.98 | 1199308.31 | 03-SEP-14:00 | 39.88 | 35.46 | 0.00 | 0.00 | 01-SEP-00:03 |
October | 189619.04 | 1248107.20 | 01-OCT-16:00 | 40.74 | 33.35 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 92876.73 | 482751.20 | 09-NOV-14:00 | 27.11 | 22.26 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 112893.31 | 180222.15 | 24-DEC-15:00 | 21.63 | 18.33 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 410901.31 | 0.00 | ||||||
Minimum of Months | 27623.73 | 56524.56 | 19.37 | 18.33 | 0.00 | 0.00 | ||
Maximum of Months | 1378095.23 | 2149290.36 | 56.37 | 44.81 | 0.00 | 0.00 |
Report: CondLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 57.56 | 57.56 | 15580.01 | 52436.84 | 31-JAN-12:15 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 56.51 | 56.51 | 15777.82 | 52482.07 | 09-FEB-12:10 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 56.29 | 56.29 | 16291.72 | 51962.79 | 01-MAR-13:00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 56.66 | 56.66 | 14618.94 | 49700.76 | 03-APR-11:20 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 57.10 | 57.10 | 14110.92 | 46830.42 | 01-MAY-11:40 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 57.51 | 57.51 | 13483.82 | 43456.74 | 01-JUN-12:00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 56.61 | 56.61 | 11961.35 | 40703.94 | 03-JUL-11:40 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 57.70 | 57.70 | 12834.43 | 40002.95 | 31-AUG-11:30 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 57.62 | 57.62 | 12494.69 | 41919.56 | 29-SEP-11:30 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 56.98 | 56.98 | 13224.05 | 45166.75 | 31-OCT-11:50 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 56.84 | 56.84 | 14323.82 | 48432.81 | 30-NOV-12:30 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 56.70 | 56.70 | 14686.68 | 50995.11 | 29-DEC-12:40 |
Annual Sum or Average | 0.00 | 14106.25 | ||||||
Minimum of Months | 0.00 | 0.00 | 56.29 | 56.29 | 11961.35 | 40002.95 | ||
Maximum of Months | 0.00 | 0.00 | 57.70 | 57.70 | 16291.72 | 52482.07 |
Report: CondLoopDemandReportMonthly
For: TOWERWATERSYS
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 4805.15 | 368114.15 | 05-JAN-15:30 | 22.57 | 21.10 | 3284.77 | 152777.72 | 12-JAN-05:42 |
February | 18534.25 | 1160591.18 | 14-FEB-16:00 | 25.72 | 21.10 | 4557.10 | 140509.68 | 28-FEB-07:00 |
March | 52860.61 | 1160897.54 | 08-MAR-16:10 | 25.72 | 21.10 | 2117.04 | 138773.32 | 19-MAR-13:43 |
April | 202560.82 | 2348808.07 | 26-APR-15:20 | 25.78 | 21.10 | 2522.75 | 137031.27 | 01-APR-05:50 |
May | 348234.82 | 2491625.77 | 19-MAY-16:00 | 26.06 | 21.10 | 891.27 | 123965.87 | 05-MAY-07:50 |
June | 713386.88 | 2512295.14 | 29-JUN-09:10 | 26.10 | 21.89 | 613.69 | 84671.51 | 19-JUN-02:70 |
July | 858693.35 | 3481232.09 | 31-JUL-15:00 | 28.03 | 23.69 | 261.84 | 44134.27 | 22-JUL-04:00 |
August | 807917.67 | 3042229.65 | 23-AUG-16:00 | 27.16 | 22.90 | 882.82 | 55219.86 | 25-AUG-05:40 |
September | 554649.58 | 3532374.41 | 05-SEP-13:10 | 28.13 | 23.32 | 449.14 | 80674.73 | 30-SEP-06:00 |
October | 240967.72 | 2503646.78 | 02-OCT-11:40 | 26.09 | 21.10 | 2158.56 | 143257.69 | 25-OCT-12:20 |
November | 10652.92 | 546319.71 | 02-NOV-15:10 | 23.28 | 21.10 | 2648.76 | 139255.71 | 16-NOV-09:20 |
December | 10.78 | 8489.42 | 14-DEC-06:13 | 21.13 | 20.19 | 6846.44 | 148393.87 | 04-DEC-15:00 |
Annual Sum or Average | 319656.60 | 2258.50 | ||||||
Minimum of Months | 10.78 | 8489.42 | 21.13 | 20.19 | 261.84 | 44134.27 | ||
Maximum of Months | 858693.35 | 3532374.41 | 28.13 | 23.69 | 6846.44 | 152777.72 |
Report: ZoneTemperatureOscillationReportMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV_BOT WITH REHEAT
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.418903E+10 | 0.00 | 0.136696E+10 | 0.591385E+10 | 0.00 | 0.00 |
February | 0.187469E+10 | 0.00 | 0.383700E+10 | 0.635582E+10 | 0.00 | 0.00 |
March | 0.164436E+09 | 0.00 | 0.123135E+11 | 0.965887E+10 | 0.00 | 0.00 |
April | 2977696.11 | 0.00 | 0.418582E+11 | 0.131144E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.637057E+11 | 0.118330E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.121827E+12 | 0.153257E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.153901E+12 | 0.172756E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.156025E+12 | 0.191603E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.910556E+11 | 0.114369E+11 | 0.00 | 0.00 |
October | 0.151550E+09 | 0.00 | 0.443653E+11 | 0.989271E+10 | 0.00 | 0.00 |
November | 0.202024E+09 | 0.00 | 0.298001E+10 | 0.820615E+10 | 0.00 | 0.00 |
December | 0.218312E+10 | 0.00 | 813330.00 | 0.729832E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.876784E+10 | 0.00 | 0.693236E+12 | 0.135472E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 813330.00 | 0.591385E+10 | 0.00 | 0.00 |
Maximum of Months | 0.418903E+10 | 0.00 | 0.156025E+12 | 0.191603E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV_MID WITH REHEAT
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.139182E+12 | 0.00 | 0.117631E+11 | 0.433297E+11 | 0.00 | 0.00 |
February | 0.794012E+11 | 0.00 | 0.321817E+11 | 0.431897E+11 | 0.00 | 0.00 |
March | 0.211874E+11 | 0.00 | 0.966714E+11 | 0.597864E+11 | 0.00 | 0.00 |
April | 0.221146E+10 | 0.00 | 0.317722E+12 | 0.807102E+11 | 0.00 | 0.00 |
May | 0.205645E+09 | 0.00 | 0.557186E+12 | 0.946570E+11 | 0.00 | 0.00 |
June | 7250083.60 | 0.00 | 0.105889E+13 | 0.124242E+12 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.127246E+13 | 0.135209E+12 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.122201E+13 | 0.136880E+12 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.811758E+12 | 0.922606E+11 | 0.00 | 0.00 |
October | 0.105137E+11 | 0.00 | 0.377239E+12 | 0.702135E+11 | 0.00 | 0.00 |
November | 0.301287E+11 | 0.00 | 0.225664E+11 | 0.506575E+11 | 0.00 | 0.00 |
December | 0.129991E+12 | 0.00 | 11532069.06 | 0.434351E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.412828E+12 | 0.00 | 0.578046E+13 | 0.974571E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 11532069.06 | 0.431897E+11 | 0.00 | 0.00 |
Maximum of Months | 0.139182E+12 | 0.00 | 0.127246E+13 | 0.136880E+12 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV_TOP WITH REHEAT
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.284949E+11 | 0.00 | 0.923031E+09 | 0.438628E+10 | 0.00 | 0.00 |
February | 0.173500E+11 | 0.00 | 0.289354E+10 | 0.395202E+10 | 0.00 | 0.00 |
March | 0.675851E+10 | 0.00 | 0.851354E+10 | 0.506852E+10 | 0.00 | 0.00 |
April | 0.129409E+10 | 0.00 | 0.329886E+11 | 0.720447E+10 | 0.00 | 0.00 |
May | 0.263139E+09 | 0.00 | 0.604951E+11 | 0.899523E+10 | 0.00 | 0.00 |
June | 21219451.88 | 0.00 | 0.118431E+12 | 0.128127E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.143884E+12 | 0.143914E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.136008E+12 | 0.142477E+11 | 0.00 | 0.00 |
September | 1616842.73 | 0.00 | 0.869028E+11 | 0.893802E+10 | 0.00 | 0.00 |
October | 0.336896E+10 | 0.00 | 0.379018E+11 | 0.609139E+10 | 0.00 | 0.00 |
November | 0.956163E+10 | 0.00 | 0.176442E+10 | 0.428469E+10 | 0.00 | 0.00 |
December | 0.277262E+11 | 0.00 | 637380.28 | 0.430898E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.948403E+11 | 0.00 | 0.630707E+12 | 0.946813E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 637380.28 | 0.395202E+10 | 0.00 | 0.00 |
Maximum of Months | 0.284949E+11 | 0.00 | 0.143884E+12 | 0.143914E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: CAV_BAS
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 982666.17 | 0.192425E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.146251E+10 | 0.172400E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.399036E+10 | 0.196379E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.213478E+11 | 0.180222E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.374603E+11 | 0.195279E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.687513E+11 | 0.194281E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.830827E+11 | 0.198197E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.831867E+11 | 0.210405E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.557166E+11 | 0.198759E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.256299E+11 | 0.205301E+11 | 0.00 | 0.00 |
November | 110.35 | 0.00 | 0.602501E+09 | 0.190994E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.190834E+11 | 0.00 | 0.00 |
Annual Sum or Average | 110.35 | 0.00 | 0.381232E+12 | 0.232548E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.172400E+11 | 0.00 | 0.00 |
Maximum of Months | 110.35 | 0.00 | 0.831867E+11 | 0.210405E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER BASEMENT
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.176447E+11 | 0.327133E+12 | 0.00 | 76.74 |
February | 0.00 | 0.00 | 0.231174E+11 | 0.348519E+12 | 0.00 | 88.33 |
March | 0.00 | 0.00 | 0.664648E+11 | 0.400337E+12 | 0.00 | 99.18 |
April | 0.00 | 0.00 | 0.380237E+12 | 0.472678E+12 | 0.00 | 96.37 |
May | 0.00 | 0.00 | 0.975818E+11 | 0.330329E+12 | 0.00 | 69.65 |
June | 0.00 | 0.00 | 0.453056E+12 | 0.344087E+12 | 0.00 | 39.65 |
July | 0.00 | 0.00 | 0.111322E+13 | 0.431399E+12 | 0.00 | 9.49 |
August | 0.00 | 0.00 | 0.139286E+13 | 0.544439E+12 | 0.00 | 29.33 |
September | 0.00 | 0.00 | 0.136880E+12 | 0.211725E+12 | 0.00 | 23.18 |
October | 0.00 | 0.00 | 0.113784E+12 | 0.360452E+12 | 0.00 | 79.84 |
November | 0.00 | 0.00 | 0.272687E+11 | 0.376830E+12 | 0.00 | 95.63 |
December | 0.00 | 0.00 | 0.246292E+11 | 0.391119E+12 | 0.00 | 99.64 |
Annual Sum or Average | 0.00 | 0.00 | 0.384674E+13 | 0.453905E+13 | 0.00 | 807.03 |
Minimum of Months | 0.00 | 0.00 | 0.176447E+11 | 0.211725E+12 | 0.00 | 9.49 |
Maximum of Months | 0.00 | 0.00 | 0.139286E+13 | 0.544439E+12 | 0.00 | 99.64 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER BOT
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.620221E+10 | 0.316904E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.118282E+11 | 0.408628E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.200043E+11 | 0.582123E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.262437E+11 | 0.721489E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.833825E+10 | 0.372775E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.152780E+11 | 0.553378E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.231123E+11 | 0.784185E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.296708E+11 | 0.930968E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.849639E+10 | 0.371900E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.143903E+11 | 0.485521E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.191979E+11 | 0.555563E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.256028E+11 | 0.683317E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.208365E+12 | 0.676675E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.620221E+10 | 0.316904E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.296708E+11 | 0.930968E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER MID
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.389714E+11 | 0.261804E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.969584E+11 | 0.360231E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.178767E+12 | 0.534715E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.244290E+12 | 0.678994E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.744815E+11 | 0.346316E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.143812E+12 | 0.525245E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.220302E+12 | 0.748922E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.281643E+12 | 0.886632E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.769913E+11 | 0.347476E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.128378E+12 | 0.447395E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.167768E+12 | 0.503472E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.222419E+12 | 0.614877E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.187478E+13 | 0.625608E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.389714E+11 | 0.261804E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.281643E+12 | 0.886632E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER TOP
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.204858E+10 | 0.225021E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.808565E+10 | 0.331731E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.167421E+11 | 0.517912E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.239257E+11 | 0.674889E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.721322E+10 | 0.345681E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.144154E+11 | 0.530993E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.222299E+11 | 0.758877E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.283073E+11 | 0.895560E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.756953E+10 | 0.349027E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.120403E+11 | 0.436118E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.151735E+11 | 0.477848E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.200409E+11 | 0.579433E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.177792E+12 | 0.612309E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.204858E+10 | 0.225021E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.283073E+11 | 0.895560E+10 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV_BOT WITH REHEAT
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.591385E+10 | 0.136696E+10 | 0.418903E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.635582E+10 | 0.383700E+10 | 0.187469E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.965887E+10 | 0.123135E+11 | 0.164436E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.131144E+11 | 0.418582E+11 | 2977696.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.118330E+11 | 0.637057E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.153257E+11 | 0.121827E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.172756E+11 | 0.153901E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.191603E+11 | 0.156025E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.114369E+11 | 0.910556E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.989271E+10 | 0.443653E+11 | 0.151550E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.820615E+10 | 0.298001E+10 | 0.202024E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.729832E+10 | 813330.00 | 0.218312E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.135472E+12 | 0.693236E+12 | 0.876784E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.591385E+10 | 813330.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.191603E+11 | 0.156025E+12 | 0.418903E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV_MID WITH REHEAT
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.433297E+11 | 0.117631E+11 | 0.139182E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.431897E+11 | 0.321817E+11 | 0.794012E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.597864E+11 | 0.966714E+11 | 0.211874E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.807102E+11 | 0.317722E+12 | 0.221146E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.946570E+11 | 0.557186E+12 | 0.205645E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.124242E+12 | 0.105889E+13 | 7250083.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.135209E+12 | 0.127246E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.136880E+12 | 0.122201E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.922606E+11 | 0.811758E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.702135E+11 | 0.377239E+12 | 0.105137E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.506575E+11 | 0.225664E+11 | 0.301287E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.434351E+11 | 11532069.06 | 0.129991E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.974571E+12 | 0.578046E+13 | 0.412828E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.431897E+11 | 11532069.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.136880E+12 | 0.127246E+13 | 0.139182E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV_TOP WITH REHEAT
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.438628E+10 | 0.923031E+09 | 0.284949E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.395202E+10 | 0.289354E+10 | 0.173500E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.506852E+10 | 0.851354E+10 | 0.675851E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.720447E+10 | 0.329886E+11 | 0.129409E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.899523E+10 | 0.604951E+11 | 0.263139E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.128127E+11 | 0.118431E+12 | 21219451.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.143914E+11 | 0.143884E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.142477E+11 | 0.136008E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.893802E+10 | 0.869028E+11 | 1616842.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.609139E+10 | 0.379018E+11 | 0.336896E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.428469E+10 | 0.176442E+10 | 0.956163E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.430898E+10 | 637380.28 | 0.277262E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.946813E+11 | 0.630707E+12 | 0.948403E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.395202E+10 | 637380.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.143914E+11 | 0.143884E+12 | 0.284949E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: CAV_BAS
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.192425E+11 | 982666.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.172400E+11 | 0.146251E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.196379E+11 | 0.399036E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.180222E+11 | 0.213478E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.195279E+11 | 0.374603E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.194281E+11 | 0.687513E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.198197E+11 | 0.830827E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.210405E+11 | 0.831867E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.198759E+11 | 0.557166E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.205301E+11 | 0.256299E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.190994E+11 | 0.602501E+09 | 110.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.190834E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.232548E+12 | 0.381232E+12 | 110.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.172400E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.210405E+11 | 0.831867E+11 | 110.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER BASEMENT
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.114833E+12 | 0.116311E+11 | 0.00 | 0.00 | 0.00 | 0.205362E+12 | 0.00 | 0.00 |
February | 0.103720E+12 | 0.157650E+11 | 0.00 | 0.00 | 0.00 | 0.236382E+12 | 0.00 | 0.00 |
March | 0.114833E+12 | 0.475737E+11 | 0.00 | 0.00 | 0.00 | 0.265418E+12 | 0.00 | 0.00 |
April | 0.111129E+12 | 0.277748E+12 | 0.00 | 0.00 | 0.00 | 0.257900E+12 | 0.00 | 0.00 |
May | 0.114833E+12 | 0.693285E+11 | 0.00 | 0.00 | 0.00 | 0.186403E+12 | 0.00 | 0.00 |
June | 0.111129E+12 | 0.326675E+12 | 0.00 | 0.00 | 0.00 | 0.106099E+12 | 0.00 | 0.00 |
July | 0.114833E+12 | 0.822170E+12 | 0.00 | 0.00 | 0.00 | 0.254014E+11 | 0.00 | 0.00 |
August | 0.114833E+12 | 0.104211E+13 | 0.00 | 0.00 | 0.00 | 0.784974E+11 | 0.00 | 0.00 |
September | 0.111129E+12 | 0.985963E+11 | 0.00 | 0.00 | 0.00 | 0.620337E+11 | 0.00 | 0.00 |
October | 0.114833E+12 | 0.827984E+11 | 0.00 | 0.00 | 0.00 | 0.213672E+12 | 0.00 | 0.00 |
November | 0.111129E+12 | 0.186277E+11 | 0.00 | 0.00 | 0.00 | 0.255909E+12 | 0.00 | 0.00 |
December | 0.114833E+12 | 0.161835E+11 | 0.00 | 0.00 | 0.00 | 0.266640E+12 | 0.00 | 0.00 |
Annual Sum or Average | 0.135207E+13 | 0.282920E+13 | 0.00 | 0.00 | 0.00 | 0.215972E+13 | 0.00 | 0.00 |
Minimum of Months | 0.103720E+12 | 0.116311E+11 | 0.00 | 0.00 | 0.00 | 0.254014E+11 | 0.00 | 0.00 |
Maximum of Months | 0.114833E+12 | 0.104211E+13 | 0.00 | 0.00 | 0.00 | 0.266640E+12 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER BOT
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.182558E+10 | 0.485875E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.164891E+10 | 0.939082E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.182558E+10 | 0.160087E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.176669E+10 | 0.207955E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.182558E+10 | 0.643609E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.176669E+10 | 0.115110E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.182558E+10 | 0.170960E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.182558E+10 | 0.221867E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.176669E+10 | 0.654409E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.182558E+10 | 0.113607E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.176669E+10 | 0.154090E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.182558E+10 | 0.205953E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.214948E+11 | 0.162192E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.164891E+10 | 0.485875E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.182558E+10 | 0.221867E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER MID
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.175142E+11 | 0.303051E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.158192E+11 | 0.767546E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.175142E+11 | 0.142810E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.169492E+11 | 0.193340E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.175142E+11 | 0.573641E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.169492E+11 | 0.108237E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.175142E+11 | 0.162924E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.175142E+11 | 0.210494E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.169492E+11 | 0.591929E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.175142E+11 | 0.101153E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.169492E+11 | 0.134370E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.175142E+11 | 0.178446E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.206215E+12 | 0.145539E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.158192E+11 | 0.303051E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.175142E+11 | 0.210494E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER TOP
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.178689E+10 | 0.158525E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.161396E+10 | 0.638231E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.178689E+10 | 0.133499E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.172925E+10 | 0.189061E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.178689E+10 | 0.554330E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.172925E+10 | 0.108347E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.178689E+10 | 0.164280E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.178689E+10 | 0.211386E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.172925E+10 | 0.580850E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.178689E+10 | 0.946597E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.172925E+10 | 0.121242E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.178689E+10 | 0.160335E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.210392E+11 | 0.137600E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.161396E+10 | 0.158525E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.178689E+10 | 0.211386E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV_BOT WITH REHEAT
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.591385E+10 | 0.418903E+10 | 0.136696E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.635582E+10 | 0.187469E+10 | 0.383700E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.965887E+10 | 0.164436E+09 | 0.123135E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.131144E+11 | 2977696.11 | 0.418582E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.118330E+11 | 0.00 | 0.637057E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.153257E+11 | 0.00 | 0.121827E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.172756E+11 | 0.00 | 0.153901E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.191603E+11 | 0.00 | 0.156025E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.114369E+11 | 0.00 | 0.910556E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.989271E+10 | 0.151550E+09 | 0.443653E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.820615E+10 | 0.202024E+09 | 0.298001E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.729832E+10 | 0.218312E+10 | 813330.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.135472E+12 | 0.876784E+10 | 0.693236E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.591385E+10 | 0.00 | 813330.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.191603E+11 | 0.418903E+10 | 0.156025E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV_MID WITH REHEAT
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.433297E+11 | 0.139182E+12 | 0.117631E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.431897E+11 | 0.794012E+11 | 0.321817E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.597864E+11 | 0.211874E+11 | 0.966714E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.807102E+11 | 0.221146E+10 | 0.317722E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.946570E+11 | 0.205645E+09 | 0.557186E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.124242E+12 | 7250083.60 | 0.105889E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.135209E+12 | 0.00 | 0.127246E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.136880E+12 | 0.00 | 0.122201E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.922606E+11 | 0.00 | 0.811758E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.702135E+11 | 0.105137E+11 | 0.377239E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.506575E+11 | 0.301287E+11 | 0.225664E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.434351E+11 | 0.129991E+12 | 11532069.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.974571E+12 | 0.412828E+12 | 0.578046E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.431897E+11 | 0.00 | 11532069.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.136880E+12 | 0.139182E+12 | 0.127246E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV_TOP WITH REHEAT
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.438628E+10 | 0.284949E+11 | 0.923031E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.395202E+10 | 0.173500E+11 | 0.289354E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.506852E+10 | 0.675851E+10 | 0.851354E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.720447E+10 | 0.129409E+10 | 0.329886E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.899523E+10 | 0.263139E+09 | 0.604951E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.128127E+11 | 21219451.88 | 0.118431E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.143914E+11 | 0.00 | 0.143884E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.142477E+11 | 0.00 | 0.136008E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.893802E+10 | 1616842.73 | 0.869028E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.609139E+10 | 0.336896E+10 | 0.379018E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.428469E+10 | 0.956163E+10 | 0.176442E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.430898E+10 | 0.277262E+11 | 637380.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.946813E+11 | 0.948403E+11 | 0.630707E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.395202E+10 | 0.00 | 637380.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.143914E+11 | 0.284949E+11 | 0.143884E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: CAV_BAS
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.192425E+11 | 0.00 | 982666.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.172400E+11 | 0.00 | 0.146251E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.196379E+11 | 0.00 | 0.399036E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.180222E+11 | 0.00 | 0.213478E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.195279E+11 | 0.00 | 0.374603E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.194281E+11 | 0.00 | 0.687513E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.198197E+11 | 0.00 | 0.830827E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.210405E+11 | 0.00 | 0.831867E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.198759E+11 | 0.00 | 0.557166E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.205301E+11 | 0.00 | 0.256299E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.190994E+11 | 110.35 | 0.602501E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.190834E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.232548E+12 | 110.35 | 0.381232E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.172400E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.210405E+11 | 110.35 | 0.831867E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER BASEMENT
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.114833E+12 | 0.00 | 0.176447E+11 | 0.00 | 0.601364E+10 | 0.00 | 0.00 | 0.00 | 0.206287E+12 | 0.00 | 0.00 | 0.00 |
February | 0.103720E+12 | 0.00 | 0.231174E+11 | 0.00 | 0.735244E+10 | 0.00 | 0.00 | 0.00 | 0.237446E+12 | 0.00 | 0.00 | 0.00 |
March | 0.114833E+12 | 0.00 | 0.664648E+11 | 0.00 | 0.188911E+11 | 0.00 | 0.00 | 0.00 | 0.266613E+12 | 0.00 | 0.00 | 0.00 |
April | 0.111129E+12 | 0.00 | 0.380237E+12 | 0.00 | 0.102489E+12 | 0.00 | 0.00 | 0.00 | 0.259061E+12 | 0.00 | 0.00 | 0.00 |
May | 0.114833E+12 | 0.00 | 0.975818E+11 | 0.00 | 0.282533E+11 | 0.00 | 0.00 | 0.00 | 0.187242E+12 | 0.00 | 0.00 | 0.00 |
June | 0.111129E+12 | 0.00 | 0.453056E+12 | 0.00 | 0.126381E+12 | 0.00 | 0.00 | 0.00 | 0.106577E+12 | 0.00 | 0.00 | 0.00 |
July | 0.114833E+12 | 0.00 | 0.111322E+13 | 0.00 | 0.291050E+12 | 0.00 | 0.00 | 0.00 | 0.255158E+11 | 0.00 | 0.00 | 0.00 |
August | 0.114833E+12 | 0.00 | 0.139286E+13 | 0.00 | 0.350755E+12 | 0.00 | 0.00 | 0.00 | 0.788508E+11 | 0.00 | 0.00 | 0.00 |
September | 0.111129E+12 | 0.00 | 0.136880E+12 | 0.00 | 0.382836E+11 | 0.00 | 0.00 | 0.00 | 0.623129E+11 | 0.00 | 0.00 | 0.00 |
October | 0.114833E+12 | 0.00 | 0.113784E+12 | 0.00 | 0.309853E+11 | 0.00 | 0.00 | 0.00 | 0.214634E+12 | 0.00 | 0.00 | 0.00 |
November | 0.111129E+12 | 0.00 | 0.272687E+11 | 0.00 | 0.864099E+10 | 0.00 | 0.00 | 0.00 | 0.257061E+12 | 0.00 | 0.00 | 0.00 |
December | 0.114833E+12 | 0.00 | 0.246292E+11 | 0.00 | 0.844575E+10 | 0.00 | 0.00 | 0.00 | 0.267840E+12 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.135207E+13 | 0.00 | 0.384674E+13 | 0.00 | 0.101754E+13 | 0.00 | 0.00 | 0.00 | 0.216944E+13 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.103720E+12 | 0.00 | 0.176447E+11 | 0.00 | 0.601364E+10 | 0.00 | 0.00 | 0.00 | 0.255158E+11 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.114833E+12 | 0.00 | 0.139286E+13 | 0.00 | 0.350755E+12 | 0.00 | 0.00 | 0.00 | 0.267840E+12 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER BOT
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.182558E+10 | 0.00 | 0.620221E+10 | 0.00 | 0.134346E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.164891E+10 | 0.00 | 0.118282E+11 | 0.00 | 0.243736E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.182558E+10 | 0.00 | 0.200043E+11 | 0.00 | 0.399565E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.176669E+10 | 0.00 | 0.262437E+11 | 0.00 | 0.544820E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.182558E+10 | 0.00 | 0.833825E+10 | 0.00 | 0.190216E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.176669E+10 | 0.00 | 0.152780E+11 | 0.00 | 0.376709E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.182558E+10 | 0.00 | 0.231123E+11 | 0.00 | 0.601626E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.182558E+10 | 0.00 | 0.296708E+11 | 0.00 | 0.748410E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.176669E+10 | 0.00 | 0.849639E+10 | 0.00 | 0.195230E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.182558E+10 | 0.00 | 0.143903E+11 | 0.00 | 0.302962E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.176669E+10 | 0.00 | 0.191979E+11 | 0.00 | 0.378893E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.182558E+10 | 0.00 | 0.256028E+11 | 0.00 | 0.500758E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.214948E+11 | 0.00 | 0.208365E+12 | 0.00 | 0.461727E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.164891E+10 | 0.00 | 0.620221E+10 | 0.00 | 0.134346E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.182558E+10 | 0.00 | 0.296708E+11 | 0.00 | 0.748410E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER MID
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.175142E+11 | 0.00 | 0.389714E+11 | 0.00 | 0.866627E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.158192E+11 | 0.00 | 0.969584E+11 | 0.00 | 0.202038E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.175142E+11 | 0.00 | 0.178767E+12 | 0.00 | 0.359573E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.169492E+11 | 0.00 | 0.244290E+12 | 0.00 | 0.509502E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.175142E+11 | 0.00 | 0.744815E+11 | 0.00 | 0.171174E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.169492E+11 | 0.00 | 0.143812E+12 | 0.00 | 0.355753E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.175142E+11 | 0.00 | 0.220302E+12 | 0.00 | 0.573780E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.175142E+11 | 0.00 | 0.281643E+12 | 0.00 | 0.711491E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.169492E+11 | 0.00 | 0.769913E+11 | 0.00 | 0.177984E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.175142E+11 | 0.00 | 0.128378E+12 | 0.00 | 0.272253E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.169492E+11 | 0.00 | 0.167768E+12 | 0.00 | 0.333981E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.175142E+11 | 0.00 | 0.222419E+12 | 0.00 | 0.439735E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.206215E+12 | 0.00 | 0.187478E+13 | 0.00 | 0.419393E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.158192E+11 | 0.00 | 0.389714E+11 | 0.00 | 0.866627E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.175142E+11 | 0.00 | 0.281643E+12 | 0.00 | 0.711491E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER TOP
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.178689E+10 | 0.00 | 0.204858E+10 | 0.00 | 0.463323E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.161396E+10 | 0.00 | 0.808565E+10 | 0.00 | 0.170334E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.178689E+10 | 0.00 | 0.167421E+11 | 0.00 | 0.339223E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.172925E+10 | 0.00 | 0.239257E+11 | 0.00 | 0.501965E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.178689E+10 | 0.00 | 0.721322E+10 | 0.00 | 0.166992E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.172925E+10 | 0.00 | 0.144154E+11 | 0.00 | 0.358068E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.178689E+10 | 0.00 | 0.222299E+11 | 0.00 | 0.580188E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.178689E+10 | 0.00 | 0.283073E+11 | 0.00 | 0.716871E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.172925E+10 | 0.00 | 0.756953E+10 | 0.00 | 0.176103E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.178689E+10 | 0.00 | 0.120403E+11 | 0.00 | 0.257429E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.172925E+10 | 0.00 | 0.151735E+11 | 0.00 | 0.304923E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.178689E+10 | 0.00 | 0.200409E+11 | 0.00 | 0.400744E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.210392E+11 | 0.00 | 0.177792E+12 | 0.00 | 0.401917E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.161396E+10 | 0.00 | 0.204858E+10 | 0.00 | 0.463323E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.178689E+10 | 0.00 | 0.283073E+11 | 0.00 | 0.716871E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.448591E+09 | 0.00 | 0.00 | 0.138261E+09 | 0.00 | 0.00 | 0.799482E+11 | 0.00 | 0.84 |
February | 0.337451E+09 | 0.00 | 0.00 | 0.121689E+09 | 0.00 | 0.00 | 0.713144E+11 | 0.00 | 0.92 |
March | 0.235287E+09 | 0.00 | 0.00 | 0.137862E+09 | 0.00 | 0.00 | 0.833455E+11 | 0.00 | 1.36 |
April | 0.217347E+09 | 12347654.53 | 0.00 | 0.125281E+09 | 91942.59 | 0.00 | 0.616276E+11 | 0.00 | 1.51 |
May | 0.139013E+09 | 0.136764E+09 | 0.00 | 0.126069E+09 | 12240190.65 | 0.00 | 0.503084E+11 | 0.00 | 1.49 |
June | 71379388.43 | 0.247789E+10 | 0.00 | 80643462.84 | 31413192.57 | 0.00 | 0.236172E+11 | 0.00 | 1.13 |
July | 74535077.75 | 0.284960E+10 | 0.00 | 75113958.27 | 57473465.78 | 0.00 | 0.106496E+11 | 0.00 | 0.95 |
August | 66989609.55 | 0.161950E+10 | 0.00 | 0.112007E+09 | 48460968.24 | 0.00 | 0.192613E+11 | 0.00 | 1.21 |
September | 0.207346E+09 | 0.321220E+09 | 0.00 | 0.130697E+09 | 10272734.58 | 0.00 | 0.354634E+11 | 0.00 | 1.50 |
October | 0.309255E+09 | 14577259.79 | 0.00 | 0.156480E+09 | 60481.88 | 0.00 | 0.683768E+11 | 0.00 | 1.55 |
November | 0.484795E+09 | 0.00 | 0.00 | 0.151617E+09 | 0.00 | 0.00 | 0.872791E+11 | 0.00 | 1.19 |
December | 0.512027E+09 | 0.00 | 0.00 | 0.155151E+09 | 0.00 | 0.00 | 0.844891E+11 | 0.00 | 0.79 |
Annual Sum or Average | 0.310402E+10 | 0.743190E+10 | 0.00 | 0.151087E+10 | 0.160013E+09 | 0.00 | 0.675681E+12 | 0.00 | 1.21 |
Minimum of Months | 66989609.55 | 0.00 | 0.00 | 75113958.27 | 0.00 | 0.00 | 0.106496E+11 | 0.00 | 0.79 |
Maximum of Months | 0.512027E+09 | 0.284960E+10 | 0.00 | 0.156480E+09 | 57473465.78 | 0.00 | 0.872791E+11 | 0.00 | 1.55 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.349316E+10 | 0.00 | 0.00 | 86499826.33 | 0.00 | 0.00 | 0.497466E+11 | 0.00 | 0.55 |
February | 0.261084E+10 | 0.00 | 0.00 | 88162419.87 | 0.00 | 0.00 | 0.482580E+11 | 0.00 | 0.64 |
March | 0.313429E+10 | 0.00 | 0.00 | 0.115839E+09 | 0.00 | 0.00 | 0.618950E+11 | 0.00 | 0.99 |
April | 0.558560E+10 | 2487024.84 | 0.00 | 0.110709E+09 | 0.00 | 0.00 | 0.494598E+11 | 0.00 | 1.22 |
May | 0.216687E+10 | 49042294.77 | 0.00 | 0.100977E+09 | 14606330.85 | 0.00 | 0.369127E+11 | 0.00 | 1.06 |
June | 0.250964E+10 | 0.966468E+09 | 0.00 | 74705582.27 | 0.126836E+09 | 0.00 | 0.168851E+11 | 0.00 | 0.83 |
July | 0.333091E+10 | 0.141608E+10 | 0.00 | 53388727.27 | 0.357548E+09 | 0.00 | 0.553571E+10 | 0.00 | 0.73 |
August | 0.558750E+10 | 0.962950E+09 | 0.00 | 88234767.58 | 0.130211E+09 | 0.00 | 0.129723E+11 | 0.00 | 1.02 |
September | 0.173962E+10 | 0.338688E+09 | 0.00 | 95950349.45 | 14771526.51 | 0.00 | 0.232112E+11 | 0.00 | 0.93 |
October | 0.373286E+10 | 2416514.12 | 0.00 | 0.110981E+09 | 302996.60 | 0.00 | 0.451684E+11 | 0.00 | 0.98 |
November | 0.416563E+10 | 0.00 | 0.00 | 0.109896E+09 | 0.00 | 0.00 | 0.608311E+11 | 0.00 | 0.85 |
December | 0.313993E+10 | 0.00 | 0.00 | 0.113539E+09 | 0.00 | 0.00 | 0.590480E+11 | 0.00 | 0.57 |
Annual Sum or Average | 0.411969E+11 | 0.373813E+10 | 0.00 | 0.114888E+10 | 0.644276E+09 | 0.00 | 0.469924E+12 | 0.00 | 0.87 |
Minimum of Months | 0.173962E+10 | 0.00 | 0.00 | 53388727.27 | 0.00 | 0.00 | 0.553571E+10 | 0.00 | 0.55 |
Maximum of Months | 0.558750E+10 | 0.141608E+10 | 0.00 | 0.115839E+09 | 0.357548E+09 | 0.00 | 0.618950E+11 | 0.00 | 1.22 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.149799E+12 | 0.00 | 0.00 | 0.343420E+09 | 0.00 | 0.00 | 0.240422E+12 | 0.00 | 0.41 |
February | 0.107785E+12 | 0.00 | 0.00 | 0.387166E+09 | 0.00 | 0.00 | 0.247576E+12 | 0.00 | 0.46 |
March | 0.534163E+11 | 0.00 | 0.00 | 0.632900E+09 | 0.00 | 0.00 | 0.384706E+12 | 0.00 | 0.69 |
April | 0.352221E+11 | 23593715.05 | 0.00 | 0.693686E+09 | 0.00 | 0.00 | 0.329722E+12 | 0.00 | 0.85 |
May | 0.220119E+11 | 0.502933E+09 | 0.00 | 0.791448E+09 | 0.144605E+09 | 0.00 | 0.291610E+12 | 0.00 | 0.88 |
June | 0.119174E+11 | 0.106798E+11 | 0.00 | 0.578375E+09 | 0.406519E+09 | 0.00 | 0.129350E+12 | 0.00 | 0.65 |
July | 0.675171E+10 | 0.139219E+11 | 0.00 | 0.459961E+09 | 0.199534E+10 | 0.00 | 0.432803E+11 | 0.00 | 0.51 |
August | 0.837457E+10 | 0.831273E+10 | 0.00 | 0.740168E+09 | 0.889363E+09 | 0.00 | 0.103872E+12 | 0.00 | 0.67 |
September | 0.133331E+11 | 0.310114E+10 | 0.00 | 0.765884E+09 | 0.230287E+09 | 0.00 | 0.181693E+12 | 0.00 | 0.76 |
October | 0.427846E+11 | 12984372.70 | 0.00 | 0.741318E+09 | 9939042.21 | 0.00 | 0.310205E+12 | 0.00 | 0.74 |
November | 0.686160E+11 | 0.00 | 0.00 | 0.544071E+09 | 0.00 | 0.00 | 0.353050E+12 | 0.00 | 0.57 |
December | 0.144787E+12 | 0.00 | 0.00 | 0.363681E+09 | 0.00 | 0.00 | 0.246471E+12 | 0.00 | 0.36 |
Annual Sum or Average | 0.664799E+12 | 0.365551E+11 | 0.00 | 0.704208E+10 | 0.367605E+10 | 0.00 | 0.286196E+13 | 0.00 | 0.63 |
Minimum of Months | 0.675171E+10 | 0.00 | 0.00 | 0.343420E+09 | 0.00 | 0.00 | 0.432803E+11 | 0.00 | 0.36 |
Maximum of Months | 0.149799E+12 | 0.139219E+11 | 0.00 | 0.791448E+09 | 0.199534E+10 | 0.00 | 0.384706E+12 | 0.00 | 0.88 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.237057E+11 | 0.00 | 0.00 | 7438184.41 | 0.00 | 0.877814E+09 | 0.713095E+10 | 0.00 | 0.35 |
February | 0.168159E+11 | 0.00 | 0.00 | 14410693.13 | 0.00 | 0.314291E+09 | 0.115408E+11 | 0.00 | 0.38 |
March | 0.116216E+11 | 0.00 | 0.00 | 34943706.36 | 0.00 | 33673718.44 | 0.250999E+11 | 0.00 | 0.60 |
April | 0.591274E+10 | 30486.10 | 0.00 | 52500853.82 | 0.00 | 0.00 | 0.272516E+11 | 0.00 | 0.84 |
May | 0.384155E+10 | 22758209.09 | 0.00 | 68432106.46 | 8302858.50 | 0.00 | 0.258581E+11 | 0.00 | 0.89 |
June | 0.174450E+10 | 0.726893E+09 | 0.00 | 63564136.37 | 41270961.20 | 0.00 | 0.115638E+11 | 0.00 | 0.65 |
July | 0.729888E+09 | 0.930584E+09 | 0.00 | 57124966.31 | 0.204568E+09 | 0.00 | 0.406946E+10 | 0.00 | 0.52 |
August | 0.961142E+09 | 0.542196E+09 | 0.00 | 84196613.72 | 83179488.67 | 0.00 | 0.993210E+10 | 0.00 | 0.70 |
September | 0.197210E+10 | 0.191839E+09 | 0.00 | 70299554.36 | 8335499.63 | 0.00 | 0.155766E+11 | 0.00 | 0.78 |
October | 0.818500E+10 | 2307868.70 | 0.00 | 49698195.99 | 0.00 | 1249726.88 | 0.206963E+11 | 0.00 | 0.68 |
November | 0.143256E+11 | 0.00 | 0.00 | 23035956.11 | 0.00 | 0.220761E+09 | 0.183176E+11 | 0.00 | 0.46 |
December | 0.247315E+11 | 0.00 | 0.00 | 5802090.51 | 0.00 | 0.622109E+09 | 0.589502E+10 | 0.00 | 0.31 |
Annual Sum or Average | 0.114547E+12 | 0.241661E+10 | 0.00 | 0.531447E+09 | 0.345657E+09 | 0.206990E+10 | 0.182932E+12 | 0.00 | 0.60 |
Minimum of Months | 0.729888E+09 | 0.00 | 0.00 | 5802090.51 | 0.00 | 0.00 | 0.406946E+10 | 0.00 | 0.31 |
Maximum of Months | 0.247315E+11 | 0.930584E+09 | 0.00 | 84196613.72 | 0.204568E+09 | 0.877814E+09 | 0.272516E+11 | 0.00 | 0.89 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.377303E+10 | 0.00 | 0.00 | 511458.18 | 0.00 | 78252022.87 | 0.649134E+09 | 0.00 | 0.36 |
February | 0.286616E+10 | 0.00 | 0.00 | 1676978.29 | 0.00 | 52116108.80 | 0.123386E+10 | 0.00 | 0.42 |
March | 0.204772E+10 | 0.00 | 0.00 | 5807753.87 | 0.00 | 0.00 | 0.384797E+10 | 0.00 | 0.75 |
April | 0.134651E+10 | 526307.17 | 0.00 | 9671524.49 | 0.00 | 0.00 | 0.453584E+10 | 0.00 | 1.17 |
May | 0.656681E+09 | 12157714.84 | 0.00 | 11637532.41 | 1908096.57 | 0.00 | 0.400985E+10 | 0.00 | 1.13 |
June | 0.427270E+09 | 0.217974E+09 | 0.00 | 11278091.42 | 15837789.21 | 0.00 | 0.227686E+10 | 0.00 | 1.06 |
July | 0.450520E+09 | 0.324518E+09 | 0.00 | 8619174.83 | 46952820.88 | 0.00 | 0.815807E+09 | 0.00 | 0.96 |
August | 0.771629E+09 | 0.195852E+09 | 0.00 | 13501828.40 | 17010138.83 | 0.00 | 0.171297E+10 | 0.00 | 1.21 |
September | 0.440372E+09 | 58931752.95 | 0.00 | 11092070.34 | 1929676.89 | 0.00 | 0.240787E+10 | 0.00 | 0.95 |
October | 0.153643E+10 | 421878.28 | 0.00 | 7450751.00 | 39581.93 | 0.00 | 0.289425E+10 | 0.00 | 0.79 |
November | 0.251168E+10 | 0.00 | 0.00 | 3479971.84 | 0.00 | 0.00 | 0.265054E+10 | 0.00 | 0.54 |
December | 0.385534E+10 | 0.00 | 0.00 | 584720.91 | 0.00 | 10567441.19 | 0.726717E+09 | 0.00 | 0.33 |
Annual Sum or Average | 0.206833E+11 | 0.810382E+09 | 0.00 | 85311855.98 | 83678104.30 | 0.140936E+09 | 0.277617E+11 | 0.00 | 0.81 |
Minimum of Months | 0.427270E+09 | 0.00 | 0.00 | 511458.18 | 0.00 | 0.00 | 0.649134E+09 | 0.00 | 0.33 |
Maximum of Months | 0.385534E+10 | 0.324518E+09 | 0.00 | 13501828.40 | 46952820.88 | 78252022.87 | 0.453584E+10 | 0.00 | 1.21 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.395384E+10 | 0.00 | 0.00 | 2570950.73 | 0.00 | 0.172758E+09 | 0.193930E+10 | 0.00 | 0.75 |
February | 0.296007E+10 | 0.00 | 0.00 | 4339012.12 | 0.00 | 68935100.71 | 0.271337E+10 | 0.00 | 0.87 |
March | 0.232542E+10 | 0.00 | 0.00 | 10999872.92 | 0.00 | 584310.77 | 0.572799E+10 | 0.00 | 1.44 |
April | 0.149672E+10 | 420707.43 | 0.00 | 16498341.90 | 0.00 | 0.00 | 0.757512E+10 | 0.00 | 2.37 |
May | 0.773493E+09 | 10425121.50 | 0.00 | 20412096.66 | 2388567.93 | 0.00 | 0.638403E+10 | 0.00 | 2.33 |
June | 0.605625E+09 | 0.166190E+09 | 0.00 | 15792528.70 | 21341194.74 | 0.00 | 0.283165E+10 | 0.00 | 1.99 |
July | 0.584265E+09 | 0.283213E+09 | 0.00 | 11716389.38 | 55565620.52 | 0.00 | 0.888315E+09 | 0.00 | 1.70 |
August | 0.105295E+10 | 0.166831E+09 | 0.00 | 16263138.79 | 21097944.99 | 0.00 | 0.200285E+10 | 0.00 | 2.19 |
September | 0.674353E+09 | 43537849.77 | 0.00 | 14973594.70 | 2415582.31 | 0.00 | 0.344134E+10 | 0.00 | 2.00 |
October | 0.179129E+10 | 309508.03 | 0.00 | 12488122.07 | 42379.69 | 0.00 | 0.474972E+10 | 0.00 | 1.62 |
November | 0.295094E+10 | 0.00 | 0.00 | 5925406.75 | 0.00 | 2442351.77 | 0.381208E+10 | 0.00 | 1.04 |
December | 0.422248E+10 | 0.00 | 0.00 | 2784759.16 | 0.00 | 0.152610E+09 | 0.173933E+10 | 0.00 | 0.68 |
Annual Sum or Average | 0.233914E+11 | 0.670927E+09 | 0.00 | 0.134764E+09 | 0.102851E+09 | 0.397329E+09 | 0.438051E+11 | 0.00 | 1.58 |
Minimum of Months | 0.584265E+09 | 0.00 | 0.00 | 2570950.73 | 0.00 | 0.00 | 0.888315E+09 | 0.00 | 0.68 |
Maximum of Months | 0.422248E+10 | 0.283213E+09 | 0.00 | 20412096.66 | 55565620.52 | 0.172758E+09 | 0.757512E+10 | 0.00 | 2.37 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.228750E+10 | 0.00 | 0.00 | 29515767.87 | 0.00 | 0.150119E+09 | 0.111159E+11 | 0.00 | 1.25 |
February | 0.173754E+10 | 0.00 | 0.00 | 25798941.21 | 0.00 | 75115872.70 | 0.112884E+11 | 0.00 | 1.44 |
March | 0.178946E+10 | 0.00 | 0.00 | 21922593.70 | 0.00 | 570847.15 | 0.111118E+11 | 0.00 | 1.74 |
April | 0.163133E+10 | 773311.07 | 0.00 | 18397226.00 | 0.00 | 0.00 | 0.790846E+10 | 0.00 | 1.94 |
May | 0.106835E+10 | 18011288.75 | 0.00 | 13689263.37 | 2399971.97 | 0.00 | 0.447517E+10 | 0.00 | 1.37 |
June | 0.680978E+09 | 0.219963E+09 | 0.00 | 10153811.04 | 21594394.52 | 0.00 | 0.188826E+10 | 0.00 | 1.04 |
July | 0.582241E+09 | 0.375624E+09 | 0.00 | 8502117.26 | 59141378.69 | 0.00 | 0.722805E+09 | 0.00 | 1.01 |
August | 0.963627E+09 | 0.276020E+09 | 0.00 | 17521775.39 | 20044615.52 | 0.00 | 0.191775E+10 | 0.00 | 1.48 |
September | 0.517646E+09 | 0.121042E+09 | 0.00 | 25926287.20 | 1438141.63 | 0.00 | 0.380414E+10 | 0.00 | 1.62 |
October | 0.112818E+10 | 898218.61 | 0.00 | 38809774.41 | 0.00 | 662610.37 | 0.102804E+11 | 0.00 | 2.06 |
November | 0.143438E+10 | 0.00 | 0.00 | 35612587.92 | 0.00 | 636490.86 | 0.146692E+11 | 0.00 | 1.69 |
December | 0.193379E+10 | 0.00 | 0.00 | 33228207.02 | 0.00 | 67272714.17 | 0.139434E+11 | 0.00 | 1.22 |
Annual Sum or Average | 0.157550E+11 | 0.101233E+10 | 0.00 | 0.279078E+09 | 0.104619E+09 | 0.294377E+09 | 0.931258E+11 | 0.00 | 1.49 |
Minimum of Months | 0.517646E+09 | 0.00 | 0.00 | 8502117.26 | 0.00 | 0.00 | 0.722805E+09 | 0.00 | 1.01 |
Maximum of Months | 0.228750E+10 | 0.375624E+09 | 0.00 | 38809774.41 | 59141378.69 | 0.150119E+09 | 0.146692E+11 | 0.00 | 2.06 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.499137E+10 | 0.00 | 0.00 | 4477869.54 | 0.00 | 2010274.18 | 0.296471E+10 | 0.00 | 1.05 |
February | 0.278888E+10 | 0.00 | 0.00 | 8092595.60 | 0.00 | 536575.30 | 0.538100E+10 | 0.00 | 1.38 |
March | 0.152242E+10 | 0.00 | 0.00 | 16765313.62 | 0.00 | 0.00 | 0.896093E+10 | 0.00 | 2.19 |
April | 0.950408E+09 | 774488.94 | 0.00 | 26744525.50 | 0.00 | 0.00 | 0.918023E+10 | 0.00 | 3.22 |
May | 0.861234E+09 | 26520236.18 | 0.00 | 16840406.93 | 781952.92 | 0.00 | 0.506761E+10 | 0.00 | 2.28 |
June | 0.505594E+09 | 0.298571E+09 | 0.00 | 14093821.36 | 19000184.84 | 0.00 | 0.244890E+10 | 0.00 | 1.91 |
July | 0.552977E+09 | 0.430764E+09 | 0.00 | 11523788.17 | 55141547.45 | 0.00 | 0.104001E+10 | 0.00 | 1.81 |
August | 0.872778E+09 | 0.302884E+09 | 0.00 | 21474834.26 | 5381629.34 | 0.00 | 0.259571E+10 | 0.00 | 2.59 |
September | 0.486815E+09 | 76539338.92 | 0.00 | 18224176.77 | 862913.24 | 0.00 | 0.302471E+10 | 0.00 | 1.82 |
October | 0.145520E+10 | 597905.92 | 0.00 | 18450100.98 | 52337.31 | 0.00 | 0.591856E+10 | 0.00 | 2.08 |
November | 0.172321E+10 | 0.00 | 0.00 | 12409082.63 | 0.00 | 0.00 | 0.794801E+10 | 0.00 | 1.63 |
December | 0.248160E+10 | 0.00 | 0.00 | 9857891.36 | 0.00 | 0.00 | 0.667876E+10 | 0.00 | 1.08 |
Annual Sum or Average | 0.191925E+11 | 0.113665E+10 | 0.00 | 0.178954E+09 | 81220565.10 | 2546849.48 | 0.612092E+11 | 0.00 | 1.92 |
Minimum of Months | 0.486815E+09 | 0.00 | 0.00 | 4477869.54 | 0.00 | 0.00 | 0.104001E+10 | 0.00 | 1.05 |
Maximum of Months | 0.499137E+10 | 0.430764E+09 | 0.00 | 26744525.50 | 55141547.45 | 2010274.18 | 0.918023E+10 | 0.00 | 3.22 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.278657E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.162343E+11 | 0.00 | 0.00 | 0.36 |
February | 0.265949E+11 | 0.00 | 0.00 | 1051557.86 | 0.00 | 0.103645E+11 | 0.786495E+09 | 0.00 | 0.38 |
March | 0.267854E+11 | 0.00 | 0.00 | 14231282.52 | 0.00 | 0.338181E+10 | 0.107988E+11 | 0.00 | 0.51 |
April | 0.156387E+11 | 5729110.05 | 0.00 | 51097723.42 | 0.00 | 0.171467E+09 | 0.210533E+11 | 0.00 | 0.77 |
May | 0.902745E+10 | 0.137508E+09 | 0.00 | 86790909.24 | 18421484.48 | 0.00 | 0.266116E+11 | 0.00 | 0.91 |
June | 0.315972E+10 | 0.272680E+10 | 0.00 | 86646050.79 | 43116344.25 | 0.00 | 0.162364E+11 | 0.00 | 0.87 |
July | 0.112950E+10 | 0.360515E+10 | 0.00 | 72424759.70 | 0.263393E+09 | 0.00 | 0.631742E+10 | 0.00 | 0.73 |
August | 0.213992E+10 | 0.193340E+10 | 0.00 | 0.108870E+09 | 0.113373E+09 | 0.00 | 0.125182E+11 | 0.00 | 0.84 |
September | 0.611208E+10 | 0.569025E+09 | 0.00 | 82319035.68 | 28060647.24 | 0.00 | 0.157399E+11 | 0.00 | 0.76 |
October | 0.211144E+11 | 2411860.51 | 0.00 | 37563764.46 | 1266149.18 | 0.111055E+10 | 0.111743E+11 | 0.00 | 0.60 |
November | 0.326229E+11 | 0.00 | 0.00 | 3433895.64 | 0.00 | 0.459863E+10 | 0.333920E+10 | 0.00 | 0.42 |
December | 0.246981E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.190060E+11 | 0.00 | 0.00 | 0.32 |
Annual Sum or Average | 0.196889E+12 | 0.898002E+10 | 0.00 | 0.544429E+09 | 0.467631E+09 | 0.548673E+11 | 0.124576E+12 | 0.00 | 0.62 |
Minimum of Months | 0.112950E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.32 |
Maximum of Months | 0.326229E+11 | 0.360515E+10 | 0.00 | 0.108870E+09 | 0.263393E+09 | 0.190060E+11 | 0.266116E+11 | 0.00 | 0.91 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.409982E+11 | 0.00 | 0.00 | 8973903.93 | 0.00 | 0.139175E+11 | 0.678019E+10 | 0.00 | 0.78 |
February | 0.343640E+11 | 0.00 | 0.00 | 20849322.40 | 0.00 | 0.794912E+10 | 0.133798E+11 | 0.00 | 0.86 |
March | 0.259707E+11 | 0.00 | 0.00 | 79726799.00 | 0.00 | 0.222376E+10 | 0.431100E+11 | 0.00 | 1.32 |
April | 0.128422E+11 | 6251806.57 | 0.00 | 0.149337E+09 | 0.00 | 72958597.43 | 0.679591E+11 | 0.00 | 2.19 |
May | 0.929582E+10 | 0.139635E+09 | 0.00 | 0.199694E+09 | 25660051.36 | 4100411.20 | 0.596524E+11 | 0.00 | 2.33 |
June | 0.449894E+10 | 0.228212E+10 | 0.00 | 0.155734E+09 | 71622306.37 | 0.00 | 0.262178E+11 | 0.00 | 1.93 |
July | 0.154129E+10 | 0.393990E+10 | 0.00 | 0.120759E+09 | 0.218774E+09 | 0.00 | 0.876832E+10 | 0.00 | 1.50 |
August | 0.290355E+10 | 0.196790E+10 | 0.00 | 0.182114E+09 | 0.156920E+09 | 0.00 | 0.207679E+11 | 0.00 | 1.89 |
September | 0.813685E+10 | 0.464197E+09 | 0.00 | 0.140017E+09 | 36622431.53 | 0.00 | 0.305741E+11 | 0.00 | 1.96 |
October | 0.213773E+11 | 2188775.77 | 0.00 | 0.103853E+09 | 1696741.47 | 0.123155E+10 | 0.371981E+11 | 0.00 | 1.54 |
November | 0.395307E+11 | 0.00 | 0.00 | 26367452.61 | 0.00 | 0.304886E+10 | 0.182305E+11 | 0.00 | 0.97 |
December | 0.409418E+11 | 0.00 | 0.00 | 6198397.16 | 0.00 | 0.145335E+11 | 0.541599E+10 | 0.00 | 0.69 |
Annual Sum or Average | 0.242401E+12 | 0.880220E+10 | 0.00 | 0.119362E+10 | 0.511296E+09 | 0.429813E+11 | 0.338054E+12 | 0.00 | 1.50 |
Minimum of Months | 0.154129E+10 | 0.00 | 0.00 | 6198397.16 | 0.00 | 0.00 | 0.541599E+10 | 0.00 | 0.69 |
Maximum of Months | 0.409982E+11 | 0.393990E+10 | 0.00 | 0.199694E+09 | 0.218774E+09 | 0.145335E+11 | 0.679591E+11 | 0.00 | 2.33 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.197313E+11 | 0.00 | 0.00 | 0.338884E+09 | 0.00 | 0.795666E+10 | 0.104079E+12 | 0.00 | 1.26 |
February | 0.158919E+11 | 0.00 | 0.00 | 0.275016E+09 | 0.00 | 0.434578E+10 | 0.104495E+12 | 0.00 | 1.41 |
March | 0.184836E+11 | 0.00 | 0.00 | 0.211014E+09 | 0.00 | 0.994261E+09 | 0.939065E+11 | 0.00 | 1.60 |
April | 0.140972E+11 | 11209516.21 | 0.00 | 0.157231E+09 | 0.00 | 0.108558E+09 | 0.630037E+11 | 0.00 | 1.65 |
May | 0.122944E+11 | 0.226837E+09 | 0.00 | 0.115796E+09 | 23670603.63 | 0.00 | 0.352618E+11 | 0.00 | 1.22 |
June | 0.604828E+10 | 0.275454E+10 | 0.00 | 79288867.44 | 71219440.18 | 0.00 | 0.136885E+11 | 0.00 | 0.87 |
July | 0.160845E+10 | 0.424983E+10 | 0.00 | 73228764.64 | 0.338894E+09 | 0.00 | 0.577832E+10 | 0.00 | 0.77 |
August | 0.276676E+10 | 0.295070E+10 | 0.00 | 0.158134E+09 | 0.139492E+09 | 0.00 | 0.156836E+11 | 0.00 | 1.13 |
September | 0.585729E+10 | 0.134422E+10 | 0.00 | 0.252299E+09 | 11700444.43 | 0.00 | 0.324952E+11 | 0.00 | 1.53 |
October | 0.110568E+11 | 12832322.93 | 0.00 | 0.433384E+09 | 0.00 | 0.607054E+09 | 0.938902E+11 | 0.00 | 1.98 |
November | 0.152315E+11 | 0.00 | 0.00 | 0.388899E+09 | 0.00 | 0.618458E+09 | 0.132931E+12 | 0.00 | 1.61 |
December | 0.169058E+11 | 0.00 | 0.00 | 0.337200E+09 | 0.00 | 0.688347E+10 | 0.124094E+12 | 0.00 | 1.16 |
Annual Sum or Average | 0.139973E+12 | 0.115502E+11 | 0.00 | 0.282037E+10 | 0.584977E+09 | 0.215142E+11 | 0.819307E+12 | 0.00 | 1.35 |
Minimum of Months | 0.160845E+10 | 0.00 | 0.00 | 73228764.64 | 0.00 | 0.00 | 0.577832E+10 | 0.00 | 0.77 |
Maximum of Months | 0.197313E+11 | 0.424983E+10 | 0.00 | 0.433384E+09 | 0.338894E+09 | 0.795666E+10 | 0.132931E+12 | 0.00 | 1.98 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.432042E+11 | 0.00 | 0.00 | 19455442.04 | 0.00 | 0.134489E+11 | 0.128832E+11 | 0.00 | 0.90 |
February | 0.362686E+11 | 0.00 | 0.00 | 33728134.92 | 0.00 | 0.813927E+10 | 0.211335E+11 | 0.00 | 1.09 |
March | 0.381589E+11 | 0.00 | 0.00 | 69927671.38 | 0.00 | 0.192388E+10 | 0.334071E+11 | 0.00 | 1.54 |
April | 0.218811E+11 | 8517185.06 | 0.00 | 0.139411E+09 | 0.00 | 11838367.90 | 0.402678E+11 | 0.00 | 2.06 |
May | 0.157725E+11 | 0.304050E+09 | 0.00 | 0.119294E+09 | 4045320.94 | 0.00 | 0.315683E+11 | 0.00 | 1.90 |
June | 0.710303E+10 | 0.356369E+10 | 0.00 | 83816162.57 | 40893654.84 | 0.00 | 0.125933E+11 | 0.00 | 1.44 |
July | 0.192803E+10 | 0.430004E+10 | 0.00 | 64401121.02 | 0.315544E+09 | 0.00 | 0.533947E+10 | 0.00 | 1.14 |
August | 0.365242E+10 | 0.240856E+10 | 0.00 | 0.118702E+09 | 0.115566E+09 | 0.00 | 0.123473E+11 | 0.00 | 1.44 |
September | 0.106889E+11 | 0.753451E+09 | 0.00 | 0.128057E+09 | 26030563.53 | 0.00 | 0.170076E+11 | 0.00 | 1.48 |
October | 0.290514E+11 | 3130916.66 | 0.00 | 0.106129E+09 | 1904000.12 | 0.990789E+09 | 0.266404E+11 | 0.00 | 1.60 |
November | 0.434373E+11 | 0.00 | 0.00 | 33257888.13 | 0.00 | 0.258673E+10 | 0.231567E+11 | 0.00 | 1.15 |
December | 0.428073E+11 | 0.00 | 0.00 | 18817056.93 | 0.00 | 0.125004E+11 | 0.137666E+11 | 0.00 | 0.79 |
Annual Sum or Average | 0.293954E+12 | 0.113414E+11 | 0.00 | 0.934997E+09 | 0.503984E+09 | 0.396018E+11 | 0.250111E+12 | 0.00 | 1.38 |
Minimum of Months | 0.192803E+10 | 0.00 | 0.00 | 18817056.93 | 0.00 | 0.00 | 0.533947E+10 | 0.00 | 0.79 |
Maximum of Months | 0.434373E+11 | 0.430004E+10 | 0.00 | 0.139411E+09 | 0.315544E+09 | 0.134489E+11 | 0.402678E+11 | 0.00 | 2.06 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.186696E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.270569E+10 | 0.00 | 0.00 | 0.39 |
February | 0.219825E+10 | 0.00 | 0.00 | 34764.03 | 0.00 | 0.168352E+10 | 45334329.30 | 0.00 | 0.41 |
March | 0.297181E+10 | 0.00 | 0.00 | 740573.63 | 0.00 | 0.694756E+09 | 0.655907E+09 | 0.00 | 0.54 |
April | 0.172289E+10 | 7848.95 | 0.00 | 4568101.20 | 0.00 | 0.165712E+09 | 0.191657E+10 | 0.00 | 0.83 |
May | 0.108946E+10 | 5699918.97 | 0.00 | 8270023.32 | 1165821.81 | 21252471.66 | 0.253661E+10 | 0.00 | 0.97 |
June | 0.413241E+09 | 0.172901E+09 | 0.00 | 10460504.62 | 5453007.49 | 412366.75 | 0.150044E+10 | 0.00 | 0.87 |
July | 0.133460E+09 | 0.221701E+09 | 0.00 | 9531402.75 | 28505690.86 | 0.00 | 0.609770E+09 | 0.00 | 0.74 |
August | 0.281146E+09 | 0.115881E+09 | 0.00 | 12958104.98 | 11706781.44 | 0.00 | 0.125131E+10 | 0.00 | 0.87 |
September | 0.734663E+09 | 33350052.22 | 0.00 | 8424702.39 | 1126050.36 | 0.00 | 0.148552E+10 | 0.00 | 0.82 |
October | 0.222049E+10 | 320989.59 | 0.00 | 3109409.59 | 0.00 | 0.344761E+09 | 0.814999E+09 | 0.00 | 0.64 |
November | 0.291845E+10 | 0.00 | 0.00 | 54393.32 | 0.00 | 0.108474E+10 | 0.142368E+09 | 0.00 | 0.45 |
December | 0.164273E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.289901E+10 | 0.00 | 0.00 | 0.35 |
Annual Sum or Average | 0.181935E+11 | 0.549862E+09 | 0.00 | 58151979.84 | 47957351.95 | 0.959985E+10 | 0.109588E+11 | 0.00 | 0.66 |
Minimum of Months | 0.133460E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.35 |
Maximum of Months | 0.297181E+10 | 0.221701E+09 | 0.00 | 12958104.98 | 28505690.86 | 0.289901E+10 | 0.253661E+10 | 0.00 | 0.97 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.318342E+10 | 0.00 | 0.00 | 228086.11 | 0.00 | 0.202883E+10 | 0.238808E+09 | 0.00 | 0.74 |
February | 0.297911E+10 | 0.00 | 0.00 | 1129110.91 | 0.00 | 0.111084E+10 | 0.818029E+09 | 0.00 | 0.80 |
March | 0.246653E+10 | 0.00 | 0.00 | 6027838.41 | 0.00 | 0.468032E+09 | 0.351921E+10 | 0.00 | 1.23 |
April | 0.112757E+10 | 8518.35 | 0.00 | 13341936.85 | 0.00 | 64887271.46 | 0.641366E+10 | 0.00 | 2.19 |
May | 0.787544E+09 | 5502586.61 | 0.00 | 19755161.17 | 1449112.48 | 13241518.31 | 0.594823E+10 | 0.00 | 2.40 |
June | 0.402267E+09 | 0.145752E+09 | 0.00 | 17747057.85 | 5952151.72 | 0.00 | 0.259378E+10 | 0.00 | 1.96 |
July | 0.150965E+09 | 0.271199E+09 | 0.00 | 14403156.15 | 20749858.92 | 0.00 | 0.873370E+09 | 0.00 | 1.55 |
August | 0.275594E+09 | 0.121575E+09 | 0.00 | 20969712.40 | 14292789.19 | 0.00 | 0.214048E+10 | 0.00 | 1.98 |
September | 0.746054E+09 | 27018271.81 | 0.00 | 14294337.41 | 1191661.04 | 0.00 | 0.299372E+10 | 0.00 | 2.06 |
October | 0.189500E+10 | 275935.03 | 0.00 | 8528363.17 | 0.00 | 0.266416E+09 | 0.317806E+10 | 0.00 | 1.50 |
November | 0.354783E+10 | 0.00 | 0.00 | 1417728.80 | 0.00 | 0.616122E+09 | 0.111677E+10 | 0.00 | 0.89 |
December | 0.341360E+10 | 0.00 | 0.00 | 109049.97 | 0.00 | 0.183228E+10 | 0.138590E+09 | 0.00 | 0.65 |
Annual Sum or Average | 0.209755E+11 | 0.571331E+09 | 0.00 | 0.117952E+09 | 43635573.34 | 0.640065E+10 | 0.299727E+11 | 0.00 | 1.50 |
Minimum of Months | 0.150965E+09 | 0.00 | 0.00 | 109049.97 | 0.00 | 0.00 | 0.138590E+09 | 0.00 | 0.65 |
Maximum of Months | 0.354783E+10 | 0.271199E+09 | 0.00 | 20969712.40 | 20749858.92 | 0.202883E+10 | 0.641366E+10 | 0.00 | 2.40 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.186082E+10 | 0.00 | 0.00 | 25345533.84 | 0.00 | 0.111623E+10 | 0.878121E+10 | 0.00 | 1.17 |
February | 0.148939E+10 | 0.00 | 0.00 | 21590202.34 | 0.00 | 0.673556E+09 | 0.938175E+10 | 0.00 | 1.32 |
March | 0.169147E+10 | 0.00 | 0.00 | 17376943.63 | 0.00 | 0.543876E+09 | 0.897559E+10 | 0.00 | 1.55 |
April | 0.137400E+10 | 13479.82 | 0.00 | 14452905.05 | 0.00 | 0.151525E+09 | 0.640647E+10 | 0.00 | 1.72 |
May | 0.130544E+10 | 8640137.11 | 0.00 | 12123046.38 | 1448353.31 | 51397727.41 | 0.362718E+10 | 0.00 | 1.31 |
June | 0.704645E+09 | 0.168467E+09 | 0.00 | 10038668.01 | 7335856.33 | 512301.91 | 0.135683E+10 | 0.00 | 0.90 |
July | 0.189704E+09 | 0.252780E+09 | 0.00 | 10057829.26 | 36370851.85 | 0.00 | 0.586535E+09 | 0.00 | 0.79 |
August | 0.349039E+09 | 0.169866E+09 | 0.00 | 19872424.77 | 13153851.03 | 0.00 | 0.168293E+10 | 0.00 | 1.18 |
September | 0.682256E+09 | 75235134.49 | 0.00 | 27724815.77 | 515436.35 | 0.00 | 0.343152E+10 | 0.00 | 1.70 |
October | 0.107493E+10 | 707508.97 | 0.00 | 39998726.61 | 0.00 | 0.230939E+09 | 0.915430E+10 | 0.00 | 2.04 |
November | 0.137048E+10 | 0.00 | 0.00 | 29001140.58 | 0.00 | 0.414691E+09 | 0.118108E+11 | 0.00 | 1.50 |
December | 0.174954E+10 | 0.00 | 0.00 | 25199787.06 | 0.00 | 0.888807E+09 | 0.103739E+11 | 0.00 | 1.06 |
Annual Sum or Average | 0.138417E+11 | 0.675709E+09 | 0.00 | 0.252782E+09 | 58824348.86 | 0.407153E+10 | 0.755690E+11 | 0.00 | 1.35 |
Minimum of Months | 0.189704E+09 | 0.00 | 0.00 | 10038668.01 | 0.00 | 0.00 | 0.586535E+09 | 0.00 | 0.79 |
Maximum of Months | 0.186082E+10 | 0.252780E+09 | 0.00 | 39998726.61 | 36370851.85 | 0.111623E+10 | 0.118108E+11 | 0.00 | 2.04 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.332247E+10 | 0.00 | 0.00 | 1546019.61 | 0.00 | 0.199221E+10 | 0.114387E+10 | 0.00 | 0.89 |
February | 0.299194E+10 | 0.00 | 0.00 | 2989028.94 | 0.00 | 0.122832E+10 | 0.202379E+10 | 0.00 | 1.06 |
March | 0.354842E+10 | 0.00 | 0.00 | 6045053.55 | 0.00 | 0.652716E+09 | 0.323150E+10 | 0.00 | 1.55 |
April | 0.217522E+10 | 8608.17 | 0.00 | 13174888.29 | 0.00 | 95190836.07 | 0.411734E+10 | 0.00 | 2.22 |
May | 0.166198E+10 | 12372252.52 | 0.00 | 13657961.15 | 633596.64 | 32783682.15 | 0.327922E+10 | 0.00 | 2.06 |
June | 0.740529E+09 | 0.210695E+09 | 0.00 | 11307708.52 | 5867802.44 | 1180770.13 | 0.132174E+10 | 0.00 | 1.48 |
July | 0.228716E+09 | 0.252666E+09 | 0.00 | 8910913.66 | 32193839.04 | 0.00 | 0.530812E+09 | 0.00 | 1.16 |
August | 0.440394E+09 | 0.138357E+09 | 0.00 | 14895311.40 | 11120012.42 | 0.00 | 0.126953E+10 | 0.00 | 1.50 |
September | 0.111000E+10 | 43095898.51 | 0.00 | 14855300.69 | 476278.17 | 0.00 | 0.169920E+10 | 0.00 | 1.63 |
October | 0.267788E+10 | 520300.26 | 0.00 | 10019077.51 | 0.00 | 0.331395E+09 | 0.255337E+10 | 0.00 | 1.66 |
November | 0.371321E+10 | 0.00 | 0.00 | 2710899.08 | 0.00 | 0.720241E+09 | 0.207878E+10 | 0.00 | 1.12 |
December | 0.325301E+10 | 0.00 | 0.00 | 1426956.67 | 0.00 | 0.199943E+10 | 0.108837E+10 | 0.00 | 0.77 |
Annual Sum or Average | 0.258638E+11 | 0.657714E+09 | 0.00 | 0.101539E+09 | 50291528.70 | 0.705346E+10 | 0.243375E+11 | 0.00 | 1.43 |
Minimum of Months | 0.228716E+09 | 0.00 | 0.00 | 1426956.67 | 0.00 | 0.00 | 0.530812E+09 | 0.00 | 0.77 |
Maximum of Months | 0.371321E+10 | 0.252666E+09 | 0.00 | 14895311.40 | 32193839.04 | 0.199943E+10 | 0.411734E+10 | 0.00 | 2.22 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 3907275.41 | 0.00 | 0.00 | 0.544254E+09 | 0.00 | 0.28 |
February | 0.00 | 0.00 | 0.00 | 8677464.41 | 0.00 | 0.00 | 0.454433E+09 | 0.00 | 0.28 |
March | 0.00 | 0.00 | 0.00 | 15622838.49 | 0.00 | 0.00 | 0.427970E+09 | 0.00 | 0.30 |
April | 0.00 | 0.00 | 0.00 | 17904279.67 | 0.00 | 0.00 | 0.289803E+09 | 0.00 | 0.29 |
May | 0.00 | 496268.49 | 0.00 | 4340673.19 | 0.00 | 0.00 | 0.215150E+09 | 0.00 | 0.29 |
June | 0.00 | 24065402.72 | 0.00 | 5409233.80 | 0.00 | 0.00 | 50399196.43 | 0.00 | 0.30 |
July | 0.00 | 0.135753E+09 | 0.00 | 364087.51 | 0.00 | 0.00 | 380103.66 | 0.00 | 0.28 |
August | 0.00 | 0.100974E+09 | 0.00 | 1917005.44 | 0.00 | 0.00 | 1569702.68 | 0.00 | 0.30 |
September | 0.00 | 18672730.09 | 0.00 | 2864172.91 | 0.00 | 0.00 | 56300049.55 | 0.00 | 0.29 |
October | 0.00 | 3783658.90 | 0.00 | 8419201.98 | 0.00 | 0.00 | 0.275562E+09 | 0.00 | 0.28 |
November | 0.00 | 0.00 | 0.00 | 13880366.15 | 0.00 | 0.00 | 0.424321E+09 | 0.00 | 0.28 |
December | 0.00 | 0.00 | 0.00 | 19947107.51 | 0.00 | 0.00 | 0.546723E+09 | 0.00 | 0.28 |
Annual Sum or Average | 0.00 | 0.283745E+09 | 0.00 | 0.103254E+09 | 0.00 | 0.00 | 0.328687E+10 | 0.00 | 0.29 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 364087.51 | 0.00 | 0.00 | 380103.66 | 0.00 | 0.28 |
Maximum of Months | 0.00 | 0.135753E+09 | 0.00 | 19947107.51 | 0.00 | 0.00 | 0.546723E+09 | 0.00 | 0.30 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 49424936.57 | 0.00 | 0.00 | 26212840.18 | 0.00 | 0.00 | 0.540465E+10 | 0.00 | 0.28 |
February | 0.00 | 0.00 | 0.00 | 73392605.88 | 0.00 | 0.00 | 0.455754E+10 | 0.00 | 0.28 |
March | 0.00 | 0.00 | 0.00 | 0.140938E+09 | 0.00 | 0.00 | 0.429369E+10 | 0.00 | 0.30 |
April | 0.00 | 0.00 | 0.00 | 0.167291E+09 | 0.00 | 0.00 | 0.290844E+10 | 0.00 | 0.29 |
May | 0.00 | 4499770.67 | 0.00 | 38754047.91 | 0.00 | 0.00 | 0.216008E+10 | 0.00 | 0.29 |
June | 0.00 | 0.238863E+09 | 0.00 | 50899082.32 | 0.00 | 0.00 | 0.508910E+09 | 0.00 | 0.30 |
July | 0.00 | 0.135292E+10 | 0.00 | 3472636.45 | 0.00 | 0.00 | 3728103.79 | 0.00 | 0.28 |
August | 0.00 | 0.101772E+10 | 0.00 | 17611011.44 | 0.00 | 0.00 | 15341246.21 | 0.00 | 0.30 |
September | 0.00 | 0.178025E+09 | 0.00 | 26091116.03 | 0.00 | 0.00 | 0.573728E+09 | 0.00 | 0.29 |
October | 0.00 | 36635053.71 | 0.00 | 75170869.08 | 0.00 | 0.00 | 0.276535E+10 | 0.00 | 0.28 |
November | 0.00 | 0.00 | 0.00 | 0.123596E+09 | 0.00 | 0.00 | 0.425778E+10 | 0.00 | 0.28 |
December | 0.00 | 0.00 | 0.00 | 0.177583E+09 | 0.00 | 0.00 | 0.548806E+10 | 0.00 | 0.28 |
Annual Sum or Average | 49424936.57 | 0.282866E+10 | 0.00 | 0.921013E+09 | 0.00 | 0.00 | 0.329373E+11 | 0.00 | 0.29 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 3472636.45 | 0.00 | 0.00 | 3728103.79 | 0.00 | 0.28 |
Maximum of Months | 49424936.57 | 0.135292E+10 | 0.00 | 0.177583E+09 | 0.00 | 0.00 | 0.548806E+10 | 0.00 | 0.30 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.127337E+09 | 0.00 | 0.00 | 1710067.65 | 0.00 | 0.00 | 0.416620E+09 | 0.00 | 0.28 |
February | 0.00 | 0.00 | 0.00 | 6501621.04 | 0.00 | 0.00 | 0.456678E+09 | 0.00 | 0.28 |
March | 0.00 | 0.00 | 0.00 | 13378777.13 | 0.00 | 0.00 | 0.430197E+09 | 0.00 | 0.30 |
April | 0.00 | 0.00 | 0.00 | 16455028.43 | 0.00 | 0.00 | 0.291112E+09 | 0.00 | 0.29 |
May | 0.00 | 451577.20 | 0.00 | 3755961.70 | 0.00 | 0.00 | 0.216330E+09 | 0.00 | 0.29 |
June | 0.00 | 23914224.27 | 0.00 | 5086417.38 | 0.00 | 0.00 | 50997476.09 | 0.00 | 0.30 |
July | 0.00 | 0.135313E+09 | 0.00 | 352914.88 | 0.00 | 0.00 | 379487.16 | 0.00 | 0.28 |
August | 0.00 | 0.102047E+09 | 0.00 | 1734104.06 | 0.00 | 0.00 | 1509377.46 | 0.00 | 0.30 |
September | 0.00 | 17744376.26 | 0.00 | 2531838.93 | 0.00 | 0.00 | 57672163.00 | 0.00 | 0.29 |
October | 0.00 | 3645381.57 | 0.00 | 7059335.44 | 0.00 | 0.00 | 0.277201E+09 | 0.00 | 0.28 |
November | 0.00 | 0.00 | 0.00 | 11518319.21 | 0.00 | 0.00 | 0.426722E+09 | 0.00 | 0.28 |
December | 0.00 | 0.00 | 0.00 | 16583667.77 | 0.00 | 0.00 | 0.550034E+09 | 0.00 | 0.28 |
Annual Sum or Average | 0.127337E+09 | 0.283116E+09 | 0.00 | 86668053.61 | 0.00 | 0.00 | 0.317545E+10 | 0.00 | 0.29 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 352914.88 | 0.00 | 0.00 | 379487.16 | 0.00 | 0.28 |
Maximum of Months | 0.127337E+09 | 0.135313E+09 | 0.00 | 16583667.77 | 0.00 | 0.00 | 0.550034E+09 | 0.00 | 0.30 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.675244E+09 | 0.00 | 0.00 | 0.549558E+12 | 0.00 | 11.16 |
February | 0.00 | 0.00 | 0.00 | 0.114242E+10 | 0.00 | 0.00 | 0.762166E+12 | 0.00 | 20.65 |
March | 0.00 | 0.00 | 0.00 | 0.181712E+10 | 0.00 | 0.00 | 0.106397E+13 | 0.00 | 35.09 |
April | 0.00 | 0.00 | 0.00 | 0.270872E+10 | 0.00 | 0.00 | 0.103618E+13 | 0.00 | 47.08 |
May | 0.00 | 0.00 | 0.00 | 0.631191E+09 | 0.00 | 0.00 | 0.476392E+12 | 0.00 | 28.72 |
June | 0.00 | 0.136101E+10 | 0.00 | 0.116060E+10 | 0.00 | 0.00 | 0.365864E+12 | 0.00 | 31.62 |
July | 0.00 | 0.328404E+11 | 0.00 | 0.124670E+10 | 0.00 | 0.00 | 0.868141E+11 | 0.00 | 30.89 |
August | 0.00 | 0.166473E+11 | 0.00 | 0.281320E+10 | 0.00 | 0.00 | 0.142066E+12 | 0.00 | 45.88 |
September | 0.00 | 0.476389E+09 | 0.00 | 0.602090E+09 | 0.00 | 0.00 | 0.315222E+12 | 0.00 | 30.93 |
October | 0.00 | 0.108318E+09 | 0.00 | 0.136013E+10 | 0.00 | 0.00 | 0.736860E+12 | 0.00 | 34.41 |
November | 0.00 | 0.00 | 0.00 | 0.192239E+10 | 0.00 | 0.00 | 0.105878E+13 | 0.00 | 31.95 |
December | 0.00 | 0.00 | 0.00 | 0.265755E+10 | 0.00 | 0.00 | 0.134281E+13 | 0.00 | 32.53 |
Annual Sum or Average | 0.00 | 0.514334E+11 | 0.00 | 0.187374E+11 | 0.00 | 0.00 | 0.793669E+13 | 0.00 | 31.79 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.602090E+09 | 0.00 | 0.00 | 0.868141E+11 | 0.00 | 11.16 |
Maximum of Months | 0.00 | 0.328404E+11 | 0.00 | 0.281320E+10 | 0.00 | 0.00 | 0.134281E+13 | 0.00 | 47.08 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 08:43:29
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.459414E+12 | 0.208293E+11 | 0.00 | 0.257212E+13 | 0.158669E+12 |
February | 0.563691E+12 | 0.193717E+11 | 0.00 | 0.265948E+13 | 0.248458E+12 |
March | 0.729916E+12 | 0.187912E+11 | 0.00 | 0.325040E+13 | 0.488105E+12 |
April | 0.897819E+12 | 0.136414E+11 | 0.00 | 0.310328E+13 | 0.129947E+13 |
May | 0.956918E+12 | 0.888391E+10 | 0.00 | 0.215325E+13 | 0.119662E+13 |
June | 0.895394E+12 | 0.419877E+10 | 0.00 | 0.130719E+13 | 0.256218E+13 |
July | 0.920328E+12 | 0.159314E+10 | 0.00 | 0.433186E+12 | 0.359431E+13 |
August | 0.901846E+12 | 0.327412E+10 | 0.00 | 0.881818E+12 | 0.390592E+13 |
September | 0.734743E+12 | 0.557125E+10 | 0.00 | 0.171409E+13 | 0.172467E+13 |
October | 0.602786E+12 | 0.104906E+11 | 0.00 | 0.279702E+13 | 0.988049E+12 |
November | 0.487445E+12 | 0.168897E+11 | 0.00 | 0.329462E+13 | 0.308703E+12 |
December | 0.429911E+12 | 0.189966E+11 | 0.00 | 0.345949E+13 | 0.370153E+12 |
Annual Sum or Average | 0.858021E+13 | 0.142532E+12 | 0.00 | 0.276259E+14 | 0.168453E+14 |
Minimum of Months | 0.429911E+12 | 0.159314E+10 | 0.00 | 0.433186E+12 | 0.158669E+12 |