Table of Contents

Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:43

Tabular Output Report in Format: HTML

Building: OfficeLarge

Environment: RUNPERIOD 1 ** Atlanta-Hartsfield Jackson Intl AP GA USA TMY3 WMO#=722190

Simulation Timestamp: 2023-10-16 08:43:24


Table of Contents

Report: Annual Building Utility Performance Summary

For: Entire Facility

Timestamp: 2023-10-16 08:43:24

Values gathered over 8760.00 hours



Site and Source Energy

Total Energy [GJ] Energy Per Total Building Area [MJ/m2] Energy Per Conditioned Building Area [MJ/m2]
Total Site Energy 31609.06 682.40 682.40
Net Site Energy 31609.06 682.40 682.40
Total Source Energy 96578.89 2085.02 2085.02
Net Source Energy 96578.89 2085.02 2085.02


Site to Source Energy Conversion Factors

Site=>Source Conversion Factor
Electricity 3.167
Natural Gas 1.084
District Cooling 1.056
District Heating 3.613
Steam 1.200
Gasoline 1.050
Diesel 1.050
Coal 1.050
Fuel Oil No 1 1.050
Fuel Oil No 2 1.050
Propane 1.050
Other Fuel 1 1.000
Other Fuel 2 1.000


Building Area

Area [m2]
Total Building Area 46320.38
Net Conditioned Building Area 46320.38
Unconditioned Building Area 0.00


End Uses

Electricity [GJ] Natural Gas [GJ] Gasoline [GJ] Diesel [GJ] Coal [GJ] Fuel Oil No 1 [GJ] Fuel Oil No 2 [GJ] Propane [GJ] Other Fuel 1 [GJ] Other Fuel 2 [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating 0.00 958.69 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 4405.04 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 3936.13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 695.97 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 14676.40 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 1934.80 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 2129.53 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 597.12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 1479.78 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 8800.50
Humidification 8.94 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 3.33
Heat Recovery 52.13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 734.54 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 2280.17
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                           
Total End Uses 29915.83 1693.23 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 11083.99
Note: Natural gas appears to be the principal heating source based on energy usage.

End Uses By Subcategory

Subcategory Electricity [GJ] Natural Gas [GJ] Gasoline [GJ] Diesel [GJ] Coal [GJ] Fuel Oil No 1 [GJ] Fuel Oil No 2 [GJ] Propane [GJ] Other Fuel 1 [GJ] Other Fuel 2 [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Boiler 0.00 958.69 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Boiler Parasitic 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling General 4405.04 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting LightsWired 3936.13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting General 695.97 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment MiscPlug 5334.97 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  DataCenterPlugLoads 9341.42 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment Transformer 80.18 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  ElevatorLift 1848.78 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  ElevatorLightsFan 5.83 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans General 2129.53 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps General 597.12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection General 1479.78 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 8800.50
Humidification General 8.94 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 3.33
Heat Recovery General 52.13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  WaterUse 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 2280.17
  Water Heater 0.00 734.54 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


End Uses By Space Type

Space Type Electricity [GJ] Natural Gas [GJ] Gasoline [GJ] Diesel [GJ] Coal [GJ] Fuel Oil No 1 [GJ] Fuel Oil No 2 [GJ] Propane [GJ] Other Fuel 1 [GJ] Other Fuel 2 [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating Unassigned 0.00 958.69 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling Unassigned 4405.04 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting GENERAL 3936.13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting Unassigned 695.97 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment GENERAL 14676.40 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment Unassigned 1934.80 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans Unassigned 2129.53 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps Unassigned 597.12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection Unassigned 1479.78 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 8800.50
Humidification Unassigned 8.94 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 3.33
Heat Recovery Unassigned 52.13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems Unassigned 0.00 734.54 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 2280.17
Refrigeration Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Normalized Metrics

Utility Use Per Conditioned Floor Area

Electricity Intensity [MJ/m2] Natural Gas Intensity [MJ/m2] Gasoline Intensity [MJ/m2] Diesel Intensity [MJ/m2] Coal Intensity [MJ/m2] Fuel Oil No 1 Intensity [MJ/m2] Fuel Oil No 2 Intensity [MJ/m2] Propane Intensity [MJ/m2] Other Fuel 1 Intensity [MJ/m2] Other Fuel 2 Intensity [MJ/m2] District Cooling Intensity [MJ/m2] District Heating Intensity [MJ/m2] Water Intensity [m3/m2]
Lighting 100.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
HVAC 186.10 36.55 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.24
Other 359.74 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total 645.85 36.55 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.24


Utility Use Per Total Floor Area

Electricity Intensity [MJ/m2] Natural Gas Intensity [MJ/m2] Gasoline Intensity [MJ/m2] Diesel Intensity [MJ/m2] Coal Intensity [MJ/m2] Fuel Oil No 1 Intensity [MJ/m2] Fuel Oil No 2 Intensity [MJ/m2] Propane Intensity [MJ/m2] Other Fuel 1 Intensity [MJ/m2] Other Fuel 2 Intensity [MJ/m2] District Cooling Intensity [MJ/m2] District Heating Intensity [MJ/m2] Water Intensity [m3/m2]
Lighting 100.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
HVAC 186.10 36.55 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.24
Other 359.74 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total 645.85 36.55 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.24


Electric Loads Satisfied

Electricity [GJ] Percent Electricity [%]
Fuel-Fired Power Generation 0.000 0.00
High Temperature Geothermal* 0.000 0.00
Photovoltaic Power 0.000 0.00
Wind Power 0.000 0.00
Power Conversion 0.000 0.00
Net Decrease in On-Site Storage 0.000 0.00
Total On-Site Electric Sources 0.000 0.00
     
Electricity Coming From Utility 29915.830 100.00
Surplus Electricity Going To Utility 0.000 0.00
Net Electricity From Utility 29915.830 100.00
     
Total On-Site and Utility Electric Sources 29915.830 100.00
Total Electricity End Uses 29915.830 100.00


On-Site Thermal Sources

Heat [GJ] Percent Heat [%]
Water-Side Heat Recovery 0.00 0.00
Air to Air Heat Recovery for Cooling 1507.92 68.64
Air to Air Heat Recovery for Heating 689.01 31.36
High-Temperature Geothermal* 0.00 0.00
Solar Water Thermal 0.00 0.00
Solar Air Thermal 0.00 0.00
Total On-Site Thermal Sources 2196.93 100.00


Water Source Summary

Water [m3] Percent Water [%]
Rainwater Collection 0.00 0.00
Condensate Collection 0.00 0.00
Groundwater Well 0.00 0.00
Total On Site Water Sources 0.00 0.00
- - -
Initial Storage 0.00 0.00
Final Storage 0.00 0.00
Change in Storage 0.00 0.00
- - -
Water Supplied by Utility 11083.99 100.00
- - -
Total On Site, Change in Storage, and Utility Water Sources 11083.99 100.00
Total Water End Uses 11083.99 100.00


Setpoint Not Met Criteria

Degrees [deltaC]
Tolerance for Zone Heating Setpoint Not Met Time 0.56
Tolerance for Zone Cooling Setpoint Not Met Time 0.56


Comfort and Setpoint Not Met Summary

Facility [Hours]
Time Setpoint Not Met During Occupied Heating 32.33
Time Setpoint Not Met During Occupied Cooling 532.33
Time Not Comfortable Based on Simple ASHRAE 55-2004 5932.33


Note 1: An asterisk (*) indicates that the feature is not yet implemented.

Table of Contents

Top
Annual Building Utility Performance Summary
Input Verification and Results Summary
Demand End Use Components Summary
Source Energy End Use Components Summary
Component Sizing Summary
Surface Shadowing Summary
Adaptive Comfort Summary
Initialization Summary
Annual Heat Emissions Summary
Climatic Data Summary
Envelope Summary
Shading Summary
Lighting Summary
Equipment Summary
HVAC Sizing Summary
Coil Sizing Details
System Summary
Outdoor Air Summary
Outdoor Air Details
Object Count Summary
Energy Meters
Sensible Heat Gain Summary
Standard 62.1 Summary
LEED Summary
Annual Thermal Resilience Summary
Annual CO2 Resilience Summary
Annual Visual Resilience Summary

NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR

| Environment |

NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901

| Environment |

NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2013

| Environment |

NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND

| Environment |

NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICELARGE

| Environment |

NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL

| Environment |

NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL

| Environment |

NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 3A

| Environment |

NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_GA_ATLANTA

| Environment |

ZoneCoolingSummaryMonthly

| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |

ZoneHeatingSummaryMonthly

| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |

ZoneElectricSummaryMonthly

| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |

SpaceGainsMonthly

| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |

PeakSpaceGainsMonthly

| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |

SpaceGainComponentsAtCoolingPeakMonthly

| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |

EnergyConsumptionElectricityNaturalGasMonthly

| Meter |

EndUseEnergyConsumptionElectricityMonthly

| Meter |

EndUseEnergyConsumptionNaturalGasMonthly

| Meter |

PeakEnergyEndUseElectricityPart1Monthly

| Meter |

PeakEnergyEndUseElectricityPart2Monthly

| Meter |

ElectricComponentsOfPeakDemandMonthly

| Meter |

PeakEnergyEndUseNaturalGasMonthly

| Meter |

SetpointsNotMetWithTemperaturesMonthly

| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |

ComfortReportSimple55Monthly

| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |

OccupantComfortDataSummaryMonthly

| DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 | BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 |

ChillerReportMonthly

| COOLSYS1 CHILLER1 | COOLSYS1 CHILLER2 |

TowerReportMonthly

| CENTRAL TOWER | TOWERWATERSYS COOLTOWER 1 | TOWERWATERSYS COOLTOWER 2 |

BoilerReportMonthly

| HEATSYS1 BOILER | CENTRAL BOILER |

DXReportMonthly

| VAV_BOT WITH REHEAT COOLING COIL | VAV_MID WITH REHEAT COOLING COIL | VAV_TOP WITH REHEAT COOLING COIL | CAV_BAS COOLING COIL | AIRLOOP DATACENTER BASEMENT COOLING COIL | AIRLOOP DATACENTER BOT COOLING COIL | AIRLOOP DATACENTER MID COOLING COIL | AIRLOOP DATACENTER TOP COOLING COIL |

WindowReportMonthly

| PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW |

WindowEnergyReportMonthly

| PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW |

WindowZoneSummaryMonthly

| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |

WindowEnergyZoneSummaryMonthly

| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |

AverageOutdoorConditionsMonthly

| Environment |

OutdoorConditionsMaximumDryBulbMonthly

| Environment |

OutdoorConditionsMinimumDryBulbMonthly

| Environment |

OutdoorConditionsMaximumWetBulbMonthly

| Environment |

OutdoorConditionsMaximumDewPointMonthly

| Environment |

OutdoorGroundConditionsMonthly

| Environment |

WaterHeaterReportMonthly

| SWHSYS1 WATER HEATER |

DaylightingReportMonthly

| PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_4_DAYLCTRL |

CoilReportMonthly

| VAV_BOT WITH REHEAT HEATING COIL | CORE_BOTTOM VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | VAV_MID WITH REHEAT HEATING COIL | CORE_MID VAV BOX REHEAT COIL | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | VAV_TOP WITH REHEAT HEATING COIL | CORE_TOP VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | CAV_BAS HEATING COIL | AIRLOOP DATACENTER BASEMENT HEATING COIL | AIRLOOP DATACENTER BOT HEATING COIL | AIRLOOP DATACENTER MID HEATING COIL | AIRLOOP DATACENTER TOP HEATING COIL | AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | AIRLOOP DATACENTER BOT_SUPPHEATCOIL | AIRLOOP DATACENTER MID_SUPPHEATCOIL | AIRLOOP DATACENTER TOP_SUPPHEATCOIL | VAV_BOT WITH REHEAT COOLING COIL | VAV_MID WITH REHEAT COOLING COIL | VAV_TOP WITH REHEAT COOLING COIL | CAV_BAS COOLING COIL | AIRLOOP DATACENTER BASEMENT COOLING COIL | AIRLOOP DATACENTER BOT COOLING COIL | AIRLOOP DATACENTER MID COOLING COIL | AIRLOOP DATACENTER TOP COOLING COIL |

PlantLoopDemandReportMonthly

| HEATSYS1 | COOLSYS1_SUPPLY | COOLSYS1_DEMAND | SINGLE WATER PLANT LOOP | SWHSYS1 | TOWERWATERSYS |

FanReportMonthly

| CAV_BAS FAN | VAV_BOT WITH REHEAT FAN | VAV_MID WITH REHEAT FAN | VAV_TOP WITH REHEAT FAN | AIRLOOP DATACENTER BASEMENT SUPPLY FAN | AIRLOOP DATACENTER BOT SUPPLY FAN | AIRLOOP DATACENTER MID SUPPLY FAN | AIRLOOP DATACENTER TOP SUPPLY FAN |

PumpReportMonthly

| HEATSYS1 PUMP | COOLSYS1 PUMP SECONDARY | COOLSYS1 CHILLER1 PUMP | COOLSYS1 CHILLER2 PUMP | PLANT CIRC PUMP | SWHSYS1 PUMP | TOWERWATERSYS PUMP |

CondLoopDemandReportMonthly

| HEATSYS1 | COOLSYS1_SUPPLY | COOLSYS1_DEMAND | SINGLE WATER PLANT LOOP | SWHSYS1 | TOWERWATERSYS |

ZoneTemperatureOscillationReportMonthly

| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |

AirLoopSystemEnergyAndWaterUseMonthly

| VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | CAV_BAS | AIRLOOP DATACENTER BASEMENT | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |

AirLoopSystemComponentLoadsMonthly

| VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | CAV_BAS | AIRLOOP DATACENTER BASEMENT | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |

AirLoopSystemComponentEnergyUseMonthly

| VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | CAV_BAS | AIRLOOP DATACENTER BASEMENT | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |

MechanicalVentilationLoadsMonthly

| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |

HeatEmissionsReportMonthly

| Environment |

Table of Contents

Report: Input Verification and Results Summary

For: Entire Facility

Timestamp: 2023-10-16 08:43:24

General

Value
Program Version and Build EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:43
RunPeriod RUNPERIOD 1
Weather File Atlanta-Hartsfield Jackson Intl AP GA USA TMY3 WMO#=722190
Latitude [deg] 33.63
Longitude [deg] -84.4
Elevation [m] 308.00
Time Zone -5.0
North Axis Angle [deg] 0.00
Rotation for Appendix G [deg] 0.00
Hours Simulated [hrs] 8760.00


ENVELOPE

Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [m2] 12183.89 3655.17 2436.78 3655.17 2436.78
Above Ground Wall Area [m2] 11589.54 3476.86 2317.91 3476.86 2317.91
Window Opening Area [m2] 4635.80 1390.74 927.16 1390.74 927.16
Gross Window-Wall Ratio [%] 38.05 38.05 38.05 38.05 38.05
Above Ground Window-Wall Ratio [%] 40.00 40.00 40.00 40.00 40.00


Conditioned Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [m2] 12183.89 3655.17 2436.78 3655.17 2436.78
Above Ground Wall Area [m2] 11589.54 3476.86 2317.91 3476.86 2317.91
Window Opening Area [m2] 4635.80 1390.74 927.16 1390.74 927.16
Gross Window-Wall Ratio [%] 38.05 38.05 38.05 38.05 38.05
Above Ground Window-Wall Ratio [%] 40.00 40.00 40.00 40.00 40.00


Skylight-Roof Ratio

Total
Gross Roof Area [m2] 3563.11
Skylight Area [m2] 0.00
Skylight-Roof Ratio [%] 0.00


PERFORMANCE

Zone Summary

Area [m2] Conditioned (Y/N) Part of Total Floor Area (Y/N) Volume [m3] Multipliers Above Ground Gross Wall Area [m2] Underground Gross Wall Area [m2] Window Glass Area [m2] Opening Area [m2] Lighting [W/m2] People [m2 per person] Plug and Process [W/m2]
BASEMENT 2779.43 Yes Yes 6779.02 1.00 0.00 397.05 0.00 0.00 10.2732 18.58 4.8418
CORE_BOTTOM 2496.12 Yes Yes 6849.35 1.00 0.00 0.00 0.00 0.00 10.2732 18.58 8.0697
CORE_MID 2496.12 Yes Yes 6849.35 10.00 0.00 0.00 0.00 0.00 10.2732 18.58 8.0696
CORE_TOP 2496.12 Yes Yes 6849.35 1.00 0.00 0.00 0.00 0.00 10.2732 18.58 8.0696
PERIMETER_BOT_ZN_3 313.41 Yes Yes 860.00 1.00 200.61 0.00 115.90 115.90 10.2732 18.58 8.0700
PERIMETER_BOT_ZN_2 201.98 Yes Yes 554.22 1.00 133.74 0.00 77.26 77.26 10.2732 18.58 8.0700
PERIMETER_BOT_ZN_1 313.42 Yes Yes 860.02 1.00 200.61 0.00 115.90 115.90 10.2732 18.58 8.0699
PERIMETER_BOT_ZN_4 201.98 Yes Yes 554.22 1.00 133.74 0.00 77.26 77.26 10.2732 18.58 8.0699
PERIMETER_MID_ZN_3 313.41 Yes Yes 860.00 10.00 200.61 0.00 115.90 115.90 10.2732 18.58 8.0700
PERIMETER_MID_ZN_2 201.98 Yes Yes 554.22 10.00 133.74 0.00 77.26 77.26 10.2732 18.58 8.0700
PERIMETER_MID_ZN_1 313.42 Yes Yes 860.02 10.00 200.61 0.00 115.90 115.90 10.2732 18.58 8.0699
PERIMETER_MID_ZN_4 201.98 Yes Yes 554.22 10.00 133.74 0.00 77.26 77.26 10.2732 18.58 8.0699
PERIMETER_TOP_ZN_3 313.41 Yes Yes 860.00 1.00 200.61 0.00 115.90 115.90 10.2732 18.58 8.0700
PERIMETER_TOP_ZN_2 201.98 Yes Yes 554.22 1.00 133.74 0.00 77.26 77.26 10.2732 18.58 8.0700
PERIMETER_TOP_ZN_1 313.42 Yes Yes 860.02 1.00 200.61 0.00 115.90 115.90 10.2732 18.58 8.0699
PERIMETER_TOP_ZN_4 201.98 Yes Yes 554.22 1.00 133.74 0.00 77.26 77.26 10.2732 18.58 8.0699
GROUNDFLOOR_PLENUM 3563.11 Yes No 4344.14 1.00 297.11 0.00 0.00 0.00 0.0000   0.0000
MIDFLOOR_PLENUM 3563.11 Yes No 4344.14 10.00 297.11 0.00 0.00 0.00 0.0000   0.0000
TOPFLOOR_PLENUM 3563.11 Yes No 4344.14 1.00 297.11 0.00 0.00 0.00 0.0000   0.0000
DATACENTER_BOT_ZN_6 36.20 Yes Yes 99.34 1.00 0.00 0.00 0.00 0.00 17.8735 18.58 215.2992
DATACENTER_MID_ZN_6 36.20 Yes Yes 99.34 10.00 0.00 0.00 0.00 0.00 17.8735 18.58 215.2992
DATACENTER_TOP_ZN_6 36.20 Yes Yes 99.34 1.00 0.00 0.00 0.00 0.00 17.8735 18.58 215.2992
DATACENTER_BASEMENT_ZN_6 783.68 Yes Yes 1911.37 1.00 0.00 197.31 0.00 0.00 10.2732 18.58 484.4232
Total 46320.38     126016.35   8024.24 594.36 4635.80 4635.80 10.3445 18.58 17.8789
Conditioned Total 46320.38     126016.35   8024.24 594.36 4635.80 4635.80 10.3445 18.58 17.8789
Unconditioned Total 0.00     0.00   0.00 0.00 0.00 0.00      
Not Part of Total 42757.27     52129.67   3565.29 0.00 0.00 0.00 0.0000   0.0000


Space Summary

Area [m2] Conditioned (Y/N) Part of Total Floor Area (Y/N) Multipliers Zone Name Space Type Radiant/Solar Enclosure Name Lighting [W/m2] People [m2 per person] Plug and Process [W/m2] Tags
BASEMENT 2779.43 Yes Yes 1.00 BASEMENT GENERAL BASEMENT 10.2732 18.58 4.8418  
CORE_BOTTOM 2496.12 Yes Yes 1.00 CORE_BOTTOM GENERAL CORE_BOTTOM 10.2732 18.58 8.0697  
CORE_MID 2496.12 Yes Yes 10.00 CORE_MID GENERAL CORE_MID 10.2732 18.58 8.0696  
CORE_TOP 2496.12 Yes Yes 1.00 CORE_TOP GENERAL CORE_TOP 10.2732 18.58 8.0696  
PERIMETER_BOT_ZN_3 313.41 Yes Yes 1.00 PERIMETER_BOT_ZN_3 GENERAL PERIMETER_BOT_ZN_3 10.2732 18.58 8.0700  
PERIMETER_BOT_ZN_2 201.98 Yes Yes 1.00 PERIMETER_BOT_ZN_2 GENERAL PERIMETER_BOT_ZN_2 10.2732 18.58 8.0700  
PERIMETER_BOT_ZN_1 313.42 Yes Yes 1.00 PERIMETER_BOT_ZN_1 GENERAL PERIMETER_BOT_ZN_1 10.2732 18.58 8.0699  
PERIMETER_BOT_ZN_4 201.98 Yes Yes 1.00 PERIMETER_BOT_ZN_4 GENERAL PERIMETER_BOT_ZN_4 10.2732 18.58 8.0699  
PERIMETER_MID_ZN_3 313.41 Yes Yes 10.00 PERIMETER_MID_ZN_3 GENERAL PERIMETER_MID_ZN_3 10.2732 18.58 8.0700  
PERIMETER_MID_ZN_2 201.98 Yes Yes 10.00 PERIMETER_MID_ZN_2 GENERAL PERIMETER_MID_ZN_2 10.2732 18.58 8.0700  
PERIMETER_MID_ZN_1 313.42 Yes Yes 10.00 PERIMETER_MID_ZN_1 GENERAL PERIMETER_MID_ZN_1 10.2732 18.58 8.0699  
PERIMETER_MID_ZN_4 201.98 Yes Yes 10.00 PERIMETER_MID_ZN_4 GENERAL PERIMETER_MID_ZN_4 10.2732 18.58 8.0699  
PERIMETER_TOP_ZN_3 313.41 Yes Yes 1.00 PERIMETER_TOP_ZN_3 GENERAL PERIMETER_TOP_ZN_3 10.2732 18.58 8.0700  
PERIMETER_TOP_ZN_2 201.98 Yes Yes 1.00 PERIMETER_TOP_ZN_2 GENERAL PERIMETER_TOP_ZN_2 10.2732 18.58 8.0700  
PERIMETER_TOP_ZN_1 313.42 Yes Yes 1.00 PERIMETER_TOP_ZN_1 GENERAL PERIMETER_TOP_ZN_1 10.2732 18.58 8.0699  
PERIMETER_TOP_ZN_4 201.98 Yes Yes 1.00 PERIMETER_TOP_ZN_4 GENERAL PERIMETER_TOP_ZN_4 10.2732 18.58 8.0699  
GROUNDFLOOR_PLENUM 3563.11 Yes No 1.00 GROUNDFLOOR_PLENUM GENERAL GROUNDFLOOR_PLENUM 0.0000 0.00 0.0000  
MIDFLOOR_PLENUM 3563.11 Yes No 10.00 MIDFLOOR_PLENUM GENERAL MIDFLOOR_PLENUM 0.0000 0.00 0.0000  
TOPFLOOR_PLENUM 3563.11 Yes No 1.00 TOPFLOOR_PLENUM GENERAL TOPFLOOR_PLENUM 0.0000 0.00 0.0000  
DATACENTER_BOT_ZN_6 36.20 Yes Yes 1.00 DATACENTER_BOT_ZN_6 GENERAL DATACENTER_BOT_ZN_6 17.8735 18.58 215.2992  
DATACENTER_MID_ZN_6 36.20 Yes Yes 10.00 DATACENTER_MID_ZN_6 GENERAL DATACENTER_MID_ZN_6 17.8735 18.58 215.2992  
DATACENTER_TOP_ZN_6 36.20 Yes Yes 1.00 DATACENTER_TOP_ZN_6 GENERAL DATACENTER_TOP_ZN_6 17.8735 18.58 215.2992  
DATACENTER_BASEMENT_ZN_6 783.68 Yes Yes 1.00 DATACENTER_BASEMENT_ZN_6 GENERAL DATACENTER_BASEMENT_ZN_6 10.2732 18.58 484.4232  
Total 46320.38             10.3445 9.29 17.8789  
Conditioned Total 46320.38             10.3445 9.29 17.8789  
Unconditioned Total 0.00             0.0000 0.00 0.0000  
Not Part of Total 42757.27             0.0000 0.00 0.0000  


Space Type Summary

Total Area [m2] Conditioned Area [m2] Unconditioned Area [m2] Not Part of Total Area [m2] Lighting [W/m2] People [m2 per person] Plug and Process [W/m2]
GENERAL 46320.38 46320.38 0.00 42757.27 3.1788 60.38 10.8345
Total 46320.38 46320.38 0.00 42757.27      



Table of Contents

Report: Demand End Use Components Summary

For: Entire Facility

Timestamp: 2023-10-16 08:43:24

End Uses

Electricity [W] Natural Gas [W] Gasoline [W] Diesel [W] Coal [W] Fuel Oil No 1 [W] Fuel Oil No 2 [W] Propane [W] Other Fuel 1 [W] Other Fuel 2 [W] District Cooling [W] Steam [W] Water [m3/s]
Time of Peak 17-AUG-15:30 13-FEB-07:10 - - - - - - - - - - 17-APR-14:39
Heating 0.00 1771654.06 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 456876.80 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 332294.83 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 778371.69 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 84450.25 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 148727.01 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 58733.85 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 92827.61 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 5613.48 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 31612.54 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                           
Total End Uses 1957895.51 1803266.60 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


End Uses By Subcategory

Subcategory Electricity [W] Natural Gas [W] Gasoline [W] Diesel [W] Coal [W] Fuel Oil No 1 [W] Fuel Oil No 2 [W] Propane [W] Other Fuel 1 [W] Other Fuel 2 [W] District Cooling [W] Steam [W] Water [m3/s]
Heating General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Boiler 0.00 1771654.06 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Boiler Parasitic 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling General 456876.80 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting LightsWired 332294.83 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment MiscPlug 305206.10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  DataCenterPlugLoads 473165.59 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment Transformer 5015.67 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  ElevatorLift 79171.38 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  ElevatorLightsFan 263.20 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans General 148727.01 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps General 58733.85 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection General 92827.61 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery General 5613.48 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  WaterUse 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Water Heater 0.00 31612.54 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: Source Energy End Use Components Summary

For: Entire Facility

Timestamp: 2023-10-16 08:43:24

Values gathered over 8760.00 hours



Source Energy End Use Components Summary

Source Electricity [GJ] Source Natural Gas [GJ] Source Gasoline [GJ] Source Diesel [GJ] Source Coal [GJ] Source Fuel Oil No 1 [GJ] Source Fuel Oil No 2 [GJ] Source Propane [GJ] Source Other Fuel 1 [GJ] Source Other Fuel 2 [GJ] Source District Cooling [GJ] Source District Heating [GJ]
Heating 0.00 1039.22 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 13950.76 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 12465.74 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 2204.14 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 46480.15 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 6127.50 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 6744.23 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 1891.07 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 4686.45 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 28.31 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 165.09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 796.24 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Total Source Energy End Use Components 94743.43 1835.46 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Normalized Metrics

Source Energy End Use Components Per Conditioned Floor Area

Source Electricity [MJ/m2] Source Natural Gas [MJ/m2] Source Gasoline [MJ/m2] Source Diesel [MJ/m2] Source Coal [MJ/m2] Source Fuel Oil No 1 [MJ/m2] Source Fuel Oil No 2 [MJ/m2] Source Propane [MJ/m2] Source Other Fuel 1 [MJ/m2] Source Other Fuel 2 [MJ/m2] Source District Cooling [MJ/m2] Source District Heating [MJ/m2]
Heating 0.00 22.44 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 301.18 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 269.12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 47.58 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 1003.45 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 132.29 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 145.60 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 40.83 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 101.17 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.61 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 3.56 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 17.19 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Total Source Energy End Use Components 2045.39 39.63 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Source Energy End Use Components Per Total Floor Area

Source Electricity [MJ/m2] Source Natural Gas [MJ/m2] Source Gasoline [MJ/m2] Source Diesel [MJ/m2] Source Coal [MJ/m2] Source Fuel Oil No 1 [MJ/m2] Source Fuel Oil No 2 [MJ/m2] Source Propane [MJ/m2] Source Other Fuel 1 [MJ/m2] Source Other Fuel 2 [MJ/m2] Source District Cooling [MJ/m2] Source District Heating [MJ/m2]
Heating 0.00 22.44 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 301.18 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 269.12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 47.58 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 1003.45 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 132.29 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 145.60 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 40.83 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 101.17 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.61 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 3.56 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 17.19 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Total Source Energy End Use Components 2045.39 39.63 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: Component Sizing Summary

For: Entire Facility

Timestamp: 2023-10-16 08:43:24

AirTerminal:SingleDuct:ConstantVolume:NoReheat

Design Size Maximum Air Flow Rate [m3/s]
BASEMENT DIRECT AIR 6.09
DATACENTER_BOT_ZN_6 DIRECT AIR 0.492156
DATACENTER_MID_ZN_6 DIRECT AIR 4.69
DATACENTER_TOP_ZN_6 DIRECT AIR 0.477940
DATACENTER_BASEMENT_ZN_6 DIRECT AIR 22.14
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

AirTerminal:SingleDuct:VAV:Reheat

Design Size Maximum Air Flow Rate [m3/s] Design Size Constant Minimum Air Flow Fraction User-Specified Constant Minimum Air Flow Fraction Design Size Minimum Air Flow Rate [m3/s] Design Size Maximum Flow Fraction during Reheat [] User-Specified Maximum Flow Fraction during Reheat [] Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] Design Size Maximum Reheat Water Flow Rate [m3/s] Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] Design Size Reheat Coil Sizing Inlet Air Temperature [C] Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir]
CORE_BOTTOM VAV BOX COMPONENT 6.35 0.299672 0.308000 1.95 0.799126 0.500000 0.001271 0.000166 1.95 12.80 0.008000
CORE_MID VAV BOX COMPONENT 59.97 0.317171 0.320000 19.19 0.845790 0.500000 0.001201 0.004042 19.19 12.80 0.008000
CORE_TOP VAV BOX COMPONENT 5.91 0.321776 0.332000 1.96 0.858069 0.500000 0.001184 0.000753 2.66 12.80 0.008000
PERIMETER_BOT_ZN_3 VAV BOX COMPONENT 1.07 0.223413 0.230000 0.245862 0.595769 0.500000 0.001705 0.000131 0.461816 12.80 0.008000
PERIMETER_BOT_ZN_2 VAV BOX COMPONENT 1.11 0.139113 0.200000 0.221266 0.370968 0.500000 0.002739 0.000089 0.315843 12.80 0.008000
PERIMETER_BOT_ZN_1 VAV BOX COMPONENT 1.25 0.190528 0.200000 0.250698 0.508076 0.500000 0.002000 0.000145 0.512475 12.80 0.008000
PERIMETER_BOT_ZN_4 VAV BOX COMPONENT 1.40 0.110304 0.200000 0.279056 0.300000 0.500000 0.003454 0.000072 0.279056 12.80 0.008000
PERIMETER_MID_ZN_3 VAV BOX COMPONENT 10.14 0.235588 0.238000 2.41 0.628236 0.500000 0.001617 0.002144 7.59 12.80 0.008000
PERIMETER_MID_ZN_2 VAV BOX COMPONENT 11.46 0.134354 0.200000 2.29 0.358278 0.500000 0.002836 0.001403 4.96 12.80 0.008000
PERIMETER_MID_ZN_1 VAV BOX COMPONENT 11.97 0.199470 0.201000 2.41 0.531921 0.500000 0.001910 0.002114 7.48 12.80 0.008000
PERIMETER_MID_ZN_4 VAV BOX COMPONENT 12.15 0.126714 0.200000 2.43 0.337904 0.500000 0.003007 0.001363 4.82 12.80 0.008000
PERIMETER_TOP_ZN_3 VAV BOX COMPONENT 1.14 0.209114 0.216000 0.246685 0.557637 0.500000 0.001822 0.000269 0.951089 12.80 0.008000
PERIMETER_TOP_ZN_2 VAV BOX COMPONENT 1.16 0.132145 0.200000 0.232934 0.352386 0.500000 0.002883 0.000175 0.620532 12.80 0.008000
PERIMETER_TOP_ZN_1 VAV BOX COMPONENT 1.32 0.181404 0.200000 0.263308 0.483745 0.500000 0.002100 0.000266 0.939737 12.80 0.008000
PERIMETER_TOP_ZN_4 VAV BOX COMPONENT 1.30 0.118581 0.200000 0.259578 0.316216 0.500000 0.003213 0.000173 0.611693 12.80 0.008000
User-Specified values were used. Design Size values were used if no User-Specified values were provided. Design Size values may be derived from alternate User-Specified values.

Coil:Heating:Water

Design Size Rated Capacity [W] Design Size Maximum Water Flow Rate [m3/s] Design Size U-Factor Times Area Value [W/K]
CORE_BOTTOM VAV BOX REHEAT COIL 18977.52 0.000166 382.57
CORE_MID VAV BOX REHEAT COIL 462014.40 0.004042 10929.41
CORE_TOP VAV BOX REHEAT COIL 86090.02 0.000753 2272.77
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL 14939.37 0.000131 394.13
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL 10215.85 0.000089 269.50
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL 16574.76 0.000145 437.24
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL 8286.08 0.000072 210.74
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL 245103.78 0.002144 6462.91
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL 160408.20 0.001403 4229.59
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL 241668.01 0.002114 6372.39
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL 155852.35 0.001363 4109.54
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL 30720.05 0.000269 809.90
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL 20042.61 0.000175 528.39
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL 30353.83 0.000266 800.25
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL 19757.34 0.000173 520.88
VAV_BOT WITH REHEAT HEATING COIL 56839.85 0.000497 935.40
VAV_MID WITH REHEAT HEATING COIL 544940.17 0.004767 8945.38
VAV_TOP WITH REHEAT HEATING COIL 53637.39 0.000469 888.20
CAV_BAS HEATING COIL 292827.06 0.002562 6501.96
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

AirLoopHVAC

Sum of Air Terminal Maximum Heating Flow Rates [m3/s] Sum of Air Terminal Minimum Heating Flow Rates [m3/s] Sum of Air Terminal Maximum Flow Rates [m3/s] Adjusted Heating Design Air Flow Rate [m3/s] Adjusted Cooling Design Air Flow Rate [m3/s] Adjusted Main Design Air Flow Rate [m3/s] User Heating Air Flow Ratio [] Calculated Heating Air Flow Ratio [] Design Supply Air Flow Rate [m3/s]
VAV_BOT WITH REHEAT 5.59 2.95 11.17 2.95 10.08 10.08 0.300000 0.292952 10.08
VAV_MID WITH REHEAT 52.84 28.73 105.68 36.91 94.04 94.04 0.300000 0.392524 94.04
VAV_TOP WITH REHEAT 5.42 2.96 10.83 5.78 10.20 10.20 0.300000 0.566825 10.20
CAV_BAS 6.09 6.09 6.09 6.09 6.09 6.09 1.00 1.00 6.09
AIRLOOP DATACENTER BASEMENT 22.14 22.14 22.14 22.14 22.14 22.14 1.00 0.999992 22.14
AIRLOOP DATACENTER BOT 0.492156 0.492156 0.492156 0.492156 0.492156 0.492156 1.00 1.00 0.492156
AIRLOOP DATACENTER MID 4.69 4.69 4.69 4.69 4.69 4.69 1.00 1.00 4.69
AIRLOOP DATACENTER TOP 0.477940 0.477940 0.477940 0.477940 0.477940 0.477940 1.00 1.00 0.477940
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Controller:OutdoorAir

Maximum Outdoor Air Flow Rate [m3/s] Minimum Outdoor Air Flow Rate [m3/s]
VAV_BOT WITH REHEAT_OA_CONTROLLER 10.08 2.54
VAV_MID WITH REHEAT_OA_CONTROLLER 94.04 25.38
VAV_TOP WITH REHEAT_OA_CONTROLLER 10.20 2.54
CAV_BAS_OA_CONTROLLER 6.09 1.20
AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER 22.14 0.338393
AIRLOOP DATACENTER BOT_OA_CONTROLLER 0.492156 0.015632
AIRLOOP DATACENTER MID_OA_CONTROLLER 4.69 0.156323
AIRLOOP DATACENTER TOP_OA_CONTROLLER 0.477940 0.015632
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

HeatExchanger:AirToAir:SensibleAndLatent

Design Size Nominal Supply Air Flow Rate [m3/s]
VAV_BOT WITH REHEAT OA HEAT RECOVERY 2.54
VAV_MID WITH REHEAT OA HEAT RECOVERY 25.38
VAV_TOP WITH REHEAT OA HEAT RECOVERY 2.54
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Coil:Cooling:Water

Design Size Design Inlet Air Temperature [C] Design Size Design Inlet Water Temperature [C] Design Size Design Outlet Air Temperature [C] Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] Design Size Design Coil Load [W] Design Size Design Water Flow Rate [m3/s] Design Size Design Air Flow Rate [m3/s]
VAV_BOT WITH REHEAT COOLING COIL 26.71 6.67 10.99 0.010332 0.008500 242286.81 0.010307 10.08
VAV_MID WITH REHEAT COOLING COIL 26.99 6.67 10.98 0.010553 0.008500 2354776.15 0.100178 94.04
VAV_TOP WITH REHEAT COOLING COIL 26.60 6.67 10.99 0.010322 0.008500 243642.38 0.010365 10.20
CAV_BAS COOLING COIL 24.79 6.67 11.37 0.010025 0.008500 124171.22 0.005283 6.09
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Fan:VariableVolume

Design Size Maximum Flow Rate [m3/s]
VAV_BOT WITH REHEAT FAN 10.08
VAV_MID WITH REHEAT FAN 94.04
VAV_TOP WITH REHEAT FAN 10.20
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Controller:WaterCoil

Maximum Actuated Flow [m3/s] Controller Convergence Tolerance
VAV_BOT WITH REHEAT_COOLC_CONTROLLER 0.010307 0.000046
VAV_BOT WITH REHEAT_HEATC_CONTROLLER 0.000497  
VAV_MID WITH REHEAT_COOLC_CONTROLLER 0.100178 0.000005
VAV_MID WITH REHEAT_HEATC_CONTROLLER 0.004767  
VAV_TOP WITH REHEAT_COOLC_CONTROLLER 0.010365 0.000046
VAV_TOP WITH REHEAT_HEATC_CONTROLLER 0.000469  
CAV_BAS_COOLC_CONTROLLER 0.005283 0.000090
CAV_BAS_HEATC_CONTROLLER 0.002562  
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Fan:ConstantVolume

Design Size Maximum Flow Rate [m3/s]
CAV_BAS FAN 6.09
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT

Design Size Rated Air Flow Rate [m3/s] Design Size Rated Total Cooling Capacity [W] Design Size Rated Sensible Cooling Capacity [W] Design Size Rated Water Flow Rate [m3/s]
AIRLOOP DATACENTER BASEMENT COOLING COIL 22.14 438414.06 303822.62 0.010737
AIRLOOP DATACENTER BOT COOLING COIL 0.492156 9691.18 6727.91 0.000237
AIRLOOP DATACENTER MID COOLING COIL 4.69 92549.83 64188.78 0.002267
AIRLOOP DATACENTER TOP COOLING COIL 0.477940 9422.96 6537.25 0.000231
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

AirLoopHVAC:UnitaryHeatPump:WaterToAir

Supply Air Flow Rate [m3/s] Supply Air Flow Rate During Heating Operation [m3/s] Supply Air Flow Rate During Cooling Operation [m3/s] Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] Nominal Heating Capacity [W] Nominal Cooling Capacity [W] Supplemental Heating Coil Nominal Capacity [W] Fraction of Supply Air Flow That Goes Through the Controlling Zone
AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP 22.14 22.14 22.14 22.14 438414.06 438414.06 18278.08 1.00
AIRLOOP DATACENTER BOT DXAC HEAT PUMP 0.492156 0.492156 0.492156 0.492156 9691.18 9691.18 844.37 1.00
AIRLOOP DATACENTER MID DXAC HEAT PUMP 4.69 4.69 4.69 4.69 92549.83 92549.83 8443.71 1.00
AIRLOOP DATACENTER TOP DXAC HEAT PUMP 0.477940 0.477940 0.477940 0.477940 9422.96 9422.96 844.37 1.00
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Fan:OnOff

Design Size Maximum Flow Rate [m3/s]
AIRLOOP DATACENTER BASEMENT SUPPLY FAN 22.14
AIRLOOP DATACENTER BOT SUPPLY FAN 0.492156
AIRLOOP DATACENTER MID SUPPLY FAN 4.69
AIRLOOP DATACENTER TOP SUPPLY FAN 0.477940
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT

Design Size Rated Air Flow Rate [m3/s] Design Size Rated Heating Capacity [W] Design Size Rated Water Flow Rate [m3/s]
AIRLOOP DATACENTER BASEMENT HEATING COIL 22.14 438414.06 0.010737
AIRLOOP DATACENTER BOT HEATING COIL 0.492156 9691.18 0.000237
AIRLOOP DATACENTER MID HEATING COIL 4.69 92549.83 0.002267
AIRLOOP DATACENTER TOP HEATING COIL 0.477940 9422.96 0.000231
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Coil:Heating:Electric

Design Size Nominal Capacity [W]
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL 18278.08
AIRLOOP DATACENTER BOT_SUPPHEATCOIL 844.37
AIRLOOP DATACENTER MID_SUPPHEATCOIL 8443.71
AIRLOOP DATACENTER TOP_SUPPHEATCOIL 844.37
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Humidifier:Steam:Electric

Design Size Nominal Capacity Volume [m3/s] User-Specified Nominal Capacity Volume [m3/s] Design Size Rated Power [W] User-Specified Rated Power [W]
DATACENTER_BASEMENT_ZN_6 HUMIDIFIER 0.000153 0.000037 96450.70 100000.00
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Pump:VariableSpeed

Design Flow Rate [m3/s] Design Power Consumption [W] Design Minimum Flow Rate [m3/s]
COOLSYS1 PUMP SECONDARY 0.126133 20593.62  
HEATSYS1 PUMP 0.021602 6505.59 0.000000
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

PlantLoop

Maximum Loop Flow Rate [m3/s] Plant Loop Volume [m3]
COOLSYS1_DEMAND 0.126133 15.14
HEATSYS1 0.021602 2.59
COOLSYS1_SUPPLY 0.126133 15.14
SINGLE WATER PLANT LOOP 0.013471 1.62
SWHSYS1 0.000440 0.052800
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

HeatExchanger:FluidToFluid

Loop Supply Side Design Fluid Flow Rate [m3/s] Loop Demand Side Design Fluid Flow Rate [m3/s] Heat Exchanger U-Factor Times Area Value [W/C] Loop-to-loop Temperature Difference Used to Size Heat Exchanger U-Factor Times Area Value [C]
BYPASS HEAT EXCHANGER 0.126133 0.126133 529442.24 5.60
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Boiler:HotWater

Design Size Nominal Capacity [W] User-Specified Nominal Capacity [W] Design Size Design Water Flow Rate [m3/s]
HEATSYS1 BOILER 2469248.63 2469248.63 0.021602
CENTRAL BOILER 554905.19 543970.57 0.013471
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Pump:ConstantSpeed

Design Flow Rate [m3/s] Design Power Consumption [W]
COOLSYS1 CHILLER1 PUMP 0.063066 7128.83
COOLSYS1 CHILLER2 PUMP 0.063066 7128.83
PLANT CIRC PUMP 0.013471 3435.87
SWHSYS1 PUMP 0.000440 56.21
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Chiller:Electric:ReformulatedEIR

Design Size Reference Chilled Water Flow Rate [m3/s] User-Specified Reference Chilled Water Flow Rate [m3/s] Design Size Reference Capacity [W] User-Specified Reference Capacity [W] Design Size Reference Condenser Water Flow Rate [m3/s]
COOLSYS1 CHILLER1 0.126133 0.063665 1500186.25 1507316.17 0.074591
COOLSYS1 CHILLER2 0.126133 0.063665 1500186.25 1507316.17 0.074591
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

FluidCooler:TwoSpeed

Design Water Flow Rate [m3/s] Air Flow Rate at High Fan Speed [m3/s] Fluid cooler UA value at high fan speed based on nominal capacity input [W/K] Air Flow Rate at Low Fan Speed [m3/s] Fan Power at Low Fan Speed [W] U-factor Times Area Value at Low Fan Speed [W/C]
CENTRAL TOWER 0.013471 139666.47 58584.37 69833.23 7879.72 21346.17
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

WaterHeater:Mixed

Use Side Design Flow Rate [m3/s]
SWHSYS1 WATER HEATER 0.000440
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

CondenserLoop

Maximum Loop Flow Rate [m3/s] Condenser Loop Volume [m3]
TOWERWATERSYS 0.149183 17.90
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

HeaderedPumps:VariableSpeed

Design Flow Rate [m3/s] Design Power Consumption [W]
TOWERWATERSYS PUMP 0.149183 36934.41
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

CoolingTower:VariableSpeed

Design Air Flow Rate [m3/s] Nominal Capacity [W] Air Flow Rate in free convection regime [m3/s] Tower capacity in free convection regime at design conditions [W]
TOWERWATERSYS COOLTOWER 1 59.48 1788404.52 11.90 223550.57
TOWERWATERSYS COOLTOWER 2 59.48 1788404.52 11.90 223550.57
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

PlantEquipmentOperation:ComponentSetPoint

Design Water Flow Rate [m3/s] Equipment # 47
WSHPPLANT OPERATION SCHEME 0.077478
User-Specified values were used. Design Size values were used if no User-Specified values were provided.


Table of Contents

Report: Surface Shadowing Summary

For: Entire Facility

Timestamp: 2023-10-16 08:43:24

Surfaces (Walls, Roofs, etc) that may be Shadowed by Other Surfaces

None


Subsurfaces (Windows and Doors) that may be Shadowed by Surfaces

Possible Shadow Receivers
PERIMETER_BOT_ZN_3_WALL_NORTH PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 |
PERIMETER_BOT_ZN_2_WALL_EAST PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 |
PERIMETER_BOT_ZN_1_WALL_SOUTH PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 |
PERIMETER_BOT_ZN_4_WALL_WEST PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 |
PERIMETER_MID_ZN_3_WALL_NORTH PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW |
PERIMETER_MID_ZN_2_WALL_EAST PERIMETER_MID_ZN_2_WALL_EAST_WINDOW |
PERIMETER_MID_ZN_1_WALL_SOUTH PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW |
PERIMETER_MID_ZN_4_WALL_WEST PERIMETER_MID_ZN_4_WALL_WEST_WINDOW |
PERIMETER_TOP_ZN_3_WALL_NORTH PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW |
PERIMETER_TOP_ZN_2_WALL_EAST PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW |
PERIMETER_TOP_ZN_1_WALL_SOUTH PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW |
PERIMETER_TOP_ZN_4_WALL_WEST PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW |



Table of Contents

Report: Adaptive Comfort Summary

For: Entire Facility

Timestamp: 2023-10-16 08:43:24

Time Not Meeting the Adaptive Comfort Models during Occupied Hours

ASHRAE55 90% Acceptability Limits [Hours] ASHRAE55 80% Acceptability Limits [Hours] CEN15251 Category I Acceptability Limits [Hours] CEN15251 Category II Acceptability Limits [Hours] CEN15251 Category III Acceptability Limits [Hours]



Table of Contents

Report: Initialization Summary

For: Entire Facility

Timestamp: 2023-10-16 08:43:24

Version

Version ID
1 22.1.0


Timesteps per Hour

#TimeSteps Minutes per TimeStep {minutes}
1 6 10


System Convergence Limits

Minimum System TimeStep {minutes} Max HVAC Iterations Minimum Plant Iterations Maximum Plant Iterations
1 1 20 2 8


Simulation Control

Do Zone Sizing Do System Sizing Do Plant Sizing Do Design Days Do Weather Simulation Do HVAC Sizing Simulation
1 Yes Yes Yes No Yes No


Performance Precision Tradeoffs

Use Coil Direct Simulation Zone Radiant Exchange Algorithm Override Mode Number of Timestep In Hour Force Euler Method Minimum Number of Warmup Days Force Suppress All Begin Environment Resets Minimum System Timestep MaxZoneTempDiff MaxAllowedDelTemp
1 No ScriptF Normal 6 No 1 No 1.0 0.300 2.0000E-003


Output Reporting Tolerances

Tolerance for Time Heating Setpoint Not Met Tolerance for Zone Cooling Setpoint Not Met Time
1 0.556 0.556


Site:GroundTemperature:BuildingSurface

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00


Site:GroundTemperature:FCfactorMethod

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 16.00 11.90 7.70 4.00 7.90 13.80 17.20 20.80 24.80 26.10 26.50 22.50


Site:GroundTemperature:Shallow

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00


Site:GroundTemperature:Deep

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00


Site:GroundReflectance

Jan{dimensionless} Feb{dimensionless} Mar{dimensionless} Apr{dimensionless} May{dimensionless} Jun{dimensionless} Jul{dimensionless} Aug{dimensionless} Sep{dimensionless} Oct{dimensionless} Nov{dimensionless} Dec{dimensionless}
1 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20


Site:GroundReflectance:SnowModifier

Normal Daylighting {dimensionless}
1 1.000 1.000


Site:GroundReflectance:Snow

Jan{dimensionless} Feb{dimensionless} Mar{dimensionless} Apr{dimensionless} May{dimensionless} Jun{dimensionless} Jul{dimensionless} Aug{dimensionless} Sep{dimensionless} Oct{dimensionless} Nov{dimensionless} Dec{dimensionless}
1 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20


Site:GroundReflectance:Snow:Daylighting

Jan{dimensionless} Feb{dimensionless} Mar{dimensionless} Apr{dimensionless} May{dimensionless} Jun{dimensionless} Jul{dimensionless} Aug{dimensionless} Sep{dimensionless} Oct{dimensionless} Nov{dimensionless} Dec{dimensionless}
1 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20


Environment:Weather Station

Wind Sensor Height Above Ground {m} Wind Speed Profile Exponent {} Wind Speed Profile Boundary Layer Thickness {m} Air Temperature Sensor Height Above Ground {m} Wind Speed Modifier Coefficient-Internal Temperature Modifier Coefficient-Internal
1 10.000 0.140 270.000 1.500 1.586 9.750E-003


Site:Location

Location Name Latitude {N+/S- Deg} Longitude {E+/W- Deg} Time Zone Number {GMT+/-} Elevation {m} Standard Pressure at Elevation {Pa} Standard RhoAir at Elevation
1 Atlanta-Hartsfield Jackson Intl AP GA USA TMY3 WMO#=722190 33.63 -84.43 -5.00 308.00 97679 1.1610


Site Water Mains Temperature Information

Calculation Method{} Water Mains Temperature Schedule Name{} Annual Average Outdoor Air Temperature{C} Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} Fixed Default Water Mains Temperature{C}
1 Correlation NA 16.60 22.50 NA


Building Information

Building Name North Axis {deg} Terrain Loads Convergence Tolerance Value Temperature Convergence Tolerance Value Solar Distribution Maximum Number of Warmup Days Minimum Number of Warmup Days
1 OfficeLarge 0.000 City 4.00000E-002 0.20000 FullInteriorAndExterior 25 6


Inside Convection Algorithm

Algorithm {Simple
TARP
CeilingDiffuser
AdaptiveConvectionAlgorithm}
1 TARP


Outside Convection Algorithm

Algorithm {SimpleCombined
TARP
MoWitt
DOE-2
AdaptiveConvectionAlgorithm}
1 TARP


Sky Radiance Distribution

Value {Anisotropic}
1 Anisotropic


Zone Air Solution Algorithm

Value {ThirdOrderBackwardDifference
AnalyticalSolution
EulerMethod}
1 ThirdOrderBackwardDifference


Zone Air Carbon Dioxide Balance Simulation

Simulation {Yes/No} Carbon Dioxide Concentration
1 No N/A


Zone Air Generic Contaminant Balance Simulation

Simulation {Yes/No} Generic Contaminant Concentration
1 No N/A


Zone Air Mass Flow Balance Simulation

Enforce Mass Balance



Adjust Zone Mixing and Return {AdjustMixingOnly
AdjustReturnOnly
AdjustMixingThenReturn
AdjustReturnThenMixing
None}
Adjust Zone Infiltration {AddInfiltration
AdjustInfiltration
None}

Infiltration Zones {MixingSourceZonesOnly
AllZones}


1 No N/A N/A N/A


HVACSystemRootFindingAlgorithm

Value {RegulaFalsi
Bisection
BisectionThenRegulaFalsi
RegulaFalsiThenBisection}
1 RegulaFalsi


Environment:Site Atmospheric Variation

Wind Speed Profile Exponent {} Wind Speed Profile Boundary Layer Thickness {m} Air Temperature Gradient Coefficient {K/m}
1 0.330 460.000 6.500000E-003


Surface Geometry

Starting Corner Vertex Input Direction Coordinate System Daylight Reference Point Coordinate System Rectangular (Simple) Surface Coordinate System
1 UpperLeftCorner Counterclockwise RelativeCoordinateSystem RelativeCoordinateSystem RelativeToZoneOrigin


Surface Heat Transfer Algorithm

Value {CTF - ConductionTransferFunction
EMPD - MoisturePenetrationDepthConductionTransferFunction
CondFD - ConductionFiniteDifference
HAMT - CombinedHeatAndMoistureFiniteElement} - Description
Inside Surface Max Temperature Limit{C}


Surface Convection Coefficient Lower Limit {W/m2-K}


Surface Convection Coefficient Upper Limit {W/m2-K}


1 CTF - ConductionTransferFunction 200 0.10 1000.0


Shading Summary

Number of Fixed Detached Shades Number of Building Detached Shades Number of Attached Shades
1 0 0 0


Zone Summary

Number of Zones Number of Zone Surfaces Number of SubSurfaces
1 23 221 36


Zone Information

Zone Name North Axis {deg} Origin X-Coordinate {m} Origin Y-Coordinate {m} Origin Z-Coordinate {m} Centroid X-Coordinate {m} Centroid Y-Coordinate {m} Centroid Z-Coordinate {m} Type Zone Multiplier Zone List Multiplier Minimum X {m} Maximum X {m} Minimum Y {m} Maximum Y {m} Minimum Z {m} Maximum Z {m} Ceiling Height {m} Volume {m3} Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} Floor Area {m2} Exterior Gross Wall Area {m2} Exterior Net Wall Area {m2} Exterior Window Area {m2} Number of Surfaces Number of SubSurfaces Number of Shading SubSurfaces Part of Total Building Area
1 BASEMENT 0.0 0.00 0.00 0.00 44.59 24.37 -1.22 1 1 1 16.08 73.11 0.00 48.74 -2.44 0.00 2.44 6779.02 TARP TARP 2779.43 0.00 0.00 0.00 9 0 0 Yes
2 CORE_BOTTOM 0.0 0.00 0.00 0.00 37.01 24.37 1.37 1 1 1 5.49 68.53 4.57 44.17 0.00 2.74 2.74 6849.35 TARP TARP 2496.12 0.00 0.00 0.00 7 0 0 Yes
3 CORE_MID 0.0 0.00 0.00 0.00 37.01 24.37 18.14 1 10 1 5.49 68.53 4.57 44.17 16.77 19.51 2.74 6849.35 TARP TARP 2496.12 0.00 0.00 0.00 6 0 0 Yes
4 CORE_TOP 0.0 0.00 0.00 0.00 37.01 24.37 34.91 1 1 1 5.49 68.53 4.57 44.17 33.54 36.28 2.74 6849.35 TARP TARP 2496.12 0.00 0.00 0.00 6 0 0 Yes
5 PERIMETER_BOT_ZN_3 0.0 0.00 0.00 0.00 36.55 46.54 1.37 1 1 1 0.00 73.11 44.17 48.74 0.00 2.74 2.74 860.00 TARP TARP 313.41 200.61 76.91 115.90 8 9 0 Yes
6 PERIMETER_BOT_ZN_2 0.0 0.00 0.00 0.00 70.95 24.37 1.37 1 1 1 68.53 73.11 0.00 48.74 0.00 2.74 2.74 554.22 TARP TARP 201.98 133.74 52.57 77.26 6 5 0 Yes
7 PERIMETER_BOT_ZN_1 0.0 0.00 0.00 0.00 36.55 2.20 1.37 1 1 1 0.00 73.11 0.00 4.57 0.00 2.74 2.74 860.02 TARP TARP 313.42 200.61 76.91 115.90 8 9 0 Yes
8 PERIMETER_BOT_ZN_4 0.0 0.00 0.00 0.00 2.16 24.37 1.37 1 1 1 0.00 4.57 0.00 48.74 0.00 2.74 2.74 554.22 TARP TARP 201.98 133.74 52.57 77.26 6 5 0 Yes
9 PERIMETER_MID_ZN_3 0.0 0.00 0.00 0.00 36.55 46.54 18.14 1 10 1 0.00 73.11 44.17 48.74 16.77 19.51 2.74 860.00 TARP TARP 313.41 200.61 84.71 115.90 7 1 0 Yes
10 PERIMETER_MID_ZN_2 0.0 0.00 0.00 0.00 70.95 24.37 18.14 1 10 1 68.53 73.11 0.00 48.74 16.77 19.51 2.74 554.22 TARP TARP 201.98 133.74 56.47 77.26 6 1 0 Yes
11 PERIMETER_MID_ZN_1 0.0 0.00 0.00 0.00 36.55 2.20 18.14 1 10 1 0.00 73.11 0.00 4.57 16.77 19.51 2.74 860.02 TARP TARP 313.42 200.61 84.71 115.90 7 1 0 Yes
12 PERIMETER_MID_ZN_4 0.0 0.00 0.00 0.00 2.16 24.37 18.14 1 10 1 0.00 4.57 0.00 48.74 16.77 19.51 2.74 554.22 TARP TARP 201.98 133.74 56.47 77.26 6 1 0 Yes
13 PERIMETER_TOP_ZN_3 0.0 0.00 0.00 0.00 36.55 46.54 34.91 1 1 1 0.00 73.11 44.17 48.74 33.54 36.28 2.74 860.00 TARP TARP 313.41 200.61 84.71 115.90 7 1 0 Yes
14 PERIMETER_TOP_ZN_2 0.0 0.00 0.00 0.00 70.95 24.37 34.91 1 1 1 68.53 73.11 0.00 48.74 33.54 36.28 2.74 554.22 TARP TARP 201.98 133.74 56.47 77.26 6 1 0 Yes
15 PERIMETER_TOP_ZN_1 0.0 0.00 0.00 0.00 36.55 2.20 34.91 1 1 1 0.00 73.11 0.00 4.57 33.54 36.28 2.74 860.02 TARP TARP 313.42 200.61 84.71 115.90 7 1 0 Yes
16 PERIMETER_TOP_ZN_4 0.0 0.00 0.00 0.00 2.16 24.37 34.91 1 1 1 0.00 4.57 0.00 48.74 33.54 36.28 2.74 554.22 TARP TARP 201.98 133.74 56.47 77.26 6 1 0 Yes
17 GROUNDFLOOR_PLENUM 0.0 0.00 0.00 0.00 36.55 24.37 3.35 1 1 1 0.00 73.11 0.00 48.74 2.74 3.96 1.22 4344.14 TARP TARP 3563.11 297.11 297.11 0.00 11 0 0 No
18 MIDFLOOR_PLENUM 0.0 0.00 0.00 0.00 36.55 24.37 20.12 1 10 1 0.00 73.11 0.00 48.74 19.51 20.73 1.22 4344.14 TARP TARP 3563.11 297.11 297.11 0.00 11 0 0 No
19 TOPFLOOR_PLENUM 0.0 0.00 0.00 0.00 36.55 24.37 36.89 1 1 1 0.00 73.11 0.00 48.74 36.28 37.50 1.22 4344.14 TARP TARP 3563.11 297.11 297.11 0.00 11 0 0 No
20 DATACENTER_BOT_ZN_6 0.0 5.49 44.17 0.00 5.03 24.37 1.37 1 1 1 4.57 5.49 4.57 44.17 0.00 2.74 2.74 99.34 TARP TARP 36.20 0.00 0.00 0.00 6 0 0 Yes
21 DATACENTER_MID_ZN_6 0.0 4.57 4.57 16.77 5.03 24.37 18.14 1 10 1 4.57 5.49 4.57 44.17 16.77 19.51 2.74 99.34 TARP TARP 36.20 0.00 0.00 0.00 6 0 0 Yes
22 DATACENTER_TOP_ZN_6 0.0 4.57 4.57 33.54 5.03 24.37 34.91 1 1 1 4.57 5.49 4.57 44.17 33.54 36.28 2.74 99.34 TARP TARP 36.20 0.00 0.00 0.00 6 0 0 Yes
23 DATACENTER_BASEMENT_ZN_6 0.0 16.08 0.00 -2.44 8.04 24.37 -1.22 1 1 1 0.00 16.08 0.00 48.74 -2.44 0.00 2.44 1911.37 TARP TARP 783.68 0.00 0.00 0.00 10 0 0 Yes


Zone Internal Gains Nominal

Zone Name Floor Area {m2} # Occupants Area per Occupant {m2/person} Occupant per Area {person/m2} Interior Lighting {W/m2} Electric Load {W/m2} Gas Load {W/m2} Other Load {W/m2} Hot Water Eq {W/m2} Steam Equipment {W/m2} Sum Loads per Area {W/m2} Outdoor Controlled Baseboard Heat
1 BASEMENT 2779.43 149.6 18.579 5.382E-002 10.273 4.842 0.000 0.000 0.000 0.000 15.115 No
2 CORE_BOTTOM 2496.12 134.4 18.579 5.382E-002 10.273 8.070 0.000 0.000 0.000 0.000 18.343 No
3 CORE_MID 2496.12 134.4 18.579 5.382E-002 10.273 8.070 0.000 0.000 0.000 0.000 18.343 No
4 CORE_TOP 2496.12 134.4 18.579 5.382E-002 10.273 8.070 0.000 0.000 0.000 0.000 18.343 No
5 PERIMETER_BOT_ZN_3 313.41 16.9 18.579 5.382E-002 10.273 8.070 0.000 0.000 0.000 0.000 18.343 No
6 PERIMETER_BOT_ZN_2 201.98 10.9 18.579 5.382E-002 10.273 8.070 0.000 0.000 0.000 0.000 18.343 No
7 PERIMETER_BOT_ZN_1 313.42 16.9 18.579 5.382E-002 10.273 8.070 0.000 0.000 0.000 0.000 18.343 No
8 PERIMETER_BOT_ZN_4 201.98 10.9 18.579 5.382E-002 10.273 8.070 0.000 0.000 0.000 0.000 18.343 No
9 PERIMETER_MID_ZN_3 313.41 16.9 18.579 5.382E-002 10.273 8.070 0.000 0.000 0.000 0.000 18.343 No
10 PERIMETER_MID_ZN_2 201.98 10.9 18.579 5.382E-002 10.273 8.070 0.000 0.000 0.000 0.000 18.343 No
11 PERIMETER_MID_ZN_1 313.42 16.9 18.579 5.382E-002 10.273 8.070 0.000 0.000 0.000 0.000 18.343 No
12 PERIMETER_MID_ZN_4 201.98 10.9 18.579 5.382E-002 10.273 8.070 0.000 0.000 0.000 0.000 18.343 No
13 PERIMETER_TOP_ZN_3 313.41 16.9 18.579 5.382E-002 10.273 8.070 0.000 0.000 0.000 0.000 18.343 No
14 PERIMETER_TOP_ZN_2 201.98 10.9 18.579 5.382E-002 10.273 8.070 0.000 0.000 0.000 0.000 18.343 No
15 PERIMETER_TOP_ZN_1 313.42 16.9 18.579 5.382E-002 10.273 8.070 0.000 0.000 0.000 0.000 18.343 No
16 PERIMETER_TOP_ZN_4 201.98 10.9 18.579 5.382E-002 10.273 8.070 0.000 0.000 0.000 0.000 18.343 No
17 GROUNDFLOOR_PLENUM 3563.11 0.0 N/A 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 No
18 MIDFLOOR_PLENUM 3563.11 0.0 N/A 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 No
19 TOPFLOOR_PLENUM 3563.11 0.0 N/A 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 No
20 DATACENTER_BOT_ZN_6 36.20 1.9 18.579 5.382E-002 17.873 215.299 0.000 0.000 0.000 0.000 233.173 No
21 DATACENTER_MID_ZN_6 36.20 1.9 18.579 5.382E-002 17.873 215.299 0.000 0.000 0.000 0.000 233.173 No
22 DATACENTER_TOP_ZN_6 36.20 1.9 18.579 5.382E-002 17.873 215.299 0.000 0.000 0.000 0.000 233.173 No
23 DATACENTER_BASEMENT_ZN_6 783.68 42.2 18.579 5.382E-002 10.273 484.423 0.000 0.000 0.000 0.000 494.696 No


People Internal Gains Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Number of People {} People/Floor Area {person/m2} Floor Area per person {m2/person} Fraction Radiant Fraction Convected Sensible Fraction Calculation Activity level ASHRAE 55 Warnings Carbon Dioxide Generation Rate Nominal Minimum Number of People Nominal Maximum Number of People MRT Calculation Type Work Efficiency Clothing Insulation Calculation Method Clothing Insulation Calculation Method Schedule Clothing Air Velocity Fanger Calculation Pierce Calculation KSU Calculation Cooling Effect Calculation Ankle Draft Calculation
1 DATACENTER_BOT_ZN_6 BLDG_OCC_SCH_WO_SB DATACENTER_BOT_ZN_6 36.20 1.9 1.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
2 DATACENTER_MID_ZN_6 BLDG_OCC_SCH_WO_SB DATACENTER_MID_ZN_6 36.20 1.9 1.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
3 DATACENTER_TOP_ZN_6 BLDG_OCC_SCH_WO_SB DATACENTER_TOP_ZN_6 36.20 1.9 1.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
4 DATACENTER_BASEMENT_ZN_6 BLDG_OCC_SCH_WO_SB DATACENTER_BASEMENT_ZN_6 783.68 42.2 42.2 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 42 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
5 BASEMENT BLDG_OCC_SCH_WO_SB BASEMENT 2779.43 149.6 149.6 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 150 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
6 CORE_BOTTOM BLDG_OCC_SCH_WO_SB CORE_BOTTOM 2496.12 134.4 134.4 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 134 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
7 CORE_MID BLDG_OCC_SCH_WO_SB CORE_MID 2496.12 134.4 134.4 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 134 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
8 CORE_TOP BLDG_OCC_SCH_WO_SB CORE_TOP 2496.12 134.4 134.4 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 134 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
9 PERIMETER_BOT_ZN_3 BLDG_OCC_SCH_WO_SB PERIMETER_BOT_ZN_3 313.41 16.9 16.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 17 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
10 PERIMETER_BOT_ZN_2 BLDG_OCC_SCH_WO_SB PERIMETER_BOT_ZN_2 201.98 10.9 10.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 11 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
11 PERIMETER_BOT_ZN_1 BLDG_OCC_SCH_WO_SB PERIMETER_BOT_ZN_1 313.42 16.9 16.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 17 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
12 PERIMETER_BOT_ZN_4 BLDG_OCC_SCH_WO_SB PERIMETER_BOT_ZN_4 201.98 10.9 10.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 11 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
13 PERIMETER_MID_ZN_3 BLDG_OCC_SCH_WO_SB PERIMETER_MID_ZN_3 313.41 16.9 16.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 17 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
14 PERIMETER_MID_ZN_2 BLDG_OCC_SCH_W_SB PERIMETER_MID_ZN_2 201.98 10.9 10.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 11 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
15 PERIMETER_MID_ZN_1 BLDG_OCC_SCH_WO_SB PERIMETER_MID_ZN_1 313.42 16.9 16.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 17 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
16 PERIMETER_MID_ZN_4 BLDG_OCC_SCH_WO_SB PERIMETER_MID_ZN_4 201.98 10.9 10.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 11 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
17 PERIMETER_TOP_ZN_3 BLDG_OCC_SCH_WO_SB PERIMETER_TOP_ZN_3 313.41 16.9 16.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 17 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
18 PERIMETER_TOP_ZN_2 BLDG_OCC_SCH_WO_SB PERIMETER_TOP_ZN_2 201.98 10.9 10.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 11 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
19 PERIMETER_TOP_ZN_1 BLDG_OCC_SCH_WO_SB PERIMETER_TOP_ZN_1 313.42 16.9 16.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 17 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
20 PERIMETER_TOP_ZN_4 BLDG_OCC_SCH_WO_SB PERIMETER_TOP_ZN_4 201.98 10.9 10.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 11 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No


Lights Internal Gains Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Lighting Level {W} Lights/Floor Area {W/m2} Lights per person {W/person} Fraction Return Air Fraction Radiant Fraction Short Wave Fraction Convected Fraction Replaceable End-Use Category Nominal Minimum Lighting Level {W} Nominal Maximum Lighting Level {W}
1 BASEMENT_LIGHTS LTG_SCH_OFFICE BASEMENT 2779.43 149.6 28553.717 10.273 190.864 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 28553.717
2 CORE_BOTTOM_LIGHTS LTG_SCH_OFFICE CORE_BOTTOM 2496.12 134.4 25643.245 10.273 190.864 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 25643.245
3 CORE_MID_LIGHTS LTG_SCH_OFFICE CORE_MID 2496.12 134.4 25643.245 10.273 190.864 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 25643.245
4 CORE_TOP_LIGHTS LTG_SCH_OFFICE CORE_TOP 2496.12 134.4 25643.245 10.273 190.864 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 25643.245
5 PERIMETER_BOT_ZN_3_LIGHTS LTG_SCH_OFFICE PERIMETER_BOT_ZN_3 313.41 16.9 3219.765 10.273 190.864 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 3219.765
6 PERIMETER_BOT_ZN_2_LIGHTS LTG_SCH_OFFICE PERIMETER_BOT_ZN_2 201.98 10.9 2074.939 10.273 190.864 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 2074.939
7 PERIMETER_BOT_ZN_1_LIGHTS LTG_SCH_OFFICE PERIMETER_BOT_ZN_1 313.42 16.9 3219.836 10.273 190.864 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 3219.836
8 PERIMETER_BOT_ZN_4_LIGHTS LTG_SCH_OFFICE PERIMETER_BOT_ZN_4 201.98 10.9 2074.939 10.273 190.864 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 2074.939
9 PERIMETER_MID_ZN_3_LIGHTS LTG_SCH_OFFICE PERIMETER_MID_ZN_3 313.41 16.9 3219.765 10.273 190.864 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 3219.765
10 PERIMETER_MID_ZN_2_LIGHTS LTG_SCH_OFFICE PERIMETER_MID_ZN_2 201.98 10.9 2074.939 10.273 190.864 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 2074.939
11 PERIMETER_MID_ZN_1_LIGHTS LTG_SCH_OFFICE PERIMETER_MID_ZN_1 313.42 16.9 3219.836 10.273 190.864 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 3219.836
12 PERIMETER_MID_ZN_4_LIGHTS LTG_SCH_OFFICE PERIMETER_MID_ZN_4 201.98 10.9 2074.939 10.273 190.864 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 2074.939
13 PERIMETER_TOP_ZN_3_LIGHTS LTG_SCH_OFFICE PERIMETER_TOP_ZN_3 313.41 16.9 3219.765 10.273 190.864 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 3219.765
14 PERIMETER_TOP_ZN_2_LIGHTS LTG_SCH_OFFICE PERIMETER_TOP_ZN_2 201.98 10.9 2074.939 10.273 190.864 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 2074.939
15 PERIMETER_TOP_ZN_1_LIGHTS LTG_SCH_OFFICE PERIMETER_TOP_ZN_1 313.42 16.9 3219.836 10.273 190.864 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 3219.836
16 PERIMETER_TOP_ZN_4_LIGHTS LTG_SCH_OFFICE PERIMETER_TOP_ZN_4 201.98 10.9 2074.939 10.273 190.864 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 2074.939
17 DATACENTER_BASEMENT_LIGHTS LTG_SCH_OFFICE DATACENTER_BASEMENT_ZN_6 783.68 42.2 8050.927 10.273 190.864 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 8050.927
18 DATACENTER_BOT_LIGHTS LTG_SCH_DATACENTER DATACENTER_BOT_ZN_6 36.20 1.9 647.068 17.873 332.067 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 647.068
19 DATACENTER_MID_LIGHTS LTG_SCH_DATACENTER DATACENTER_MID_ZN_6 36.20 1.9 647.068 17.873 332.067 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 647.068
20 DATACENTER_TOP_LIGHTS LTG_SCH_DATACENTER DATACENTER_TOP_ZN_6 36.20 1.9 647.068 17.873 332.067 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 647.068


ElectricEquipment Internal Gains Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Equipment Level {W} Equipment/Floor Area {W/m2} Equipment per person {W/person} Fraction Latent Fraction Radiant Fraction Lost Fraction Convected End-Use SubCategory Nominal Minimum Equipment Level {W} Nominal Maximum Equipment Level {W}
1 BASEMENT_MISCPLUG_EQUIP ALWAYS_ON BASEMENT 2779.43 149.6 13457.544 4.842 89.956 0.000 0.500 0.000 0.500 MiscPlug 13457.544 13457.544
2 CORE_BOTTOM_MISCPLUG_EQUIP BLDG_EQUIP_SCH CORE_BOTTOM 2496.12 134.4 20142.877 8.070 149.925 0.000 0.500 0.000 0.500 MiscPlug 0.000 20142.877
3 CORE_MID_MISCPLUG_EQUIP BLDG_EQUIP_SCH CORE_MID 2496.12 134.4 20142.800 8.070 149.924 0.000 0.500 0.000 0.500 MiscPlug 0.000 20142.800
4 CORE_TOP_MISCPLUG_EQUIP BLDG_EQUIP_SCH CORE_TOP 2496.12 134.4 20142.800 8.070 149.924 0.000 0.500 0.000 0.500 MiscPlug 0.000 20142.800
5 PERIMETER_BOT_ZN_3_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_BOT_ZN_3 313.41 16.9 2529.242 8.070 149.931 0.000 0.500 0.000 0.500 MiscPlug 0.000 2529.242
6 PERIMETER_BOT_ZN_2_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_BOT_ZN_2 201.98 10.9 1629.940 8.070 149.931 0.000 0.500 0.000 0.500 MiscPlug 0.000 1629.940
7 PERIMETER_BOT_ZN_1_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_BOT_ZN_1 313.42 16.9 2529.281 8.070 149.930 0.000 0.500 0.000 0.500 MiscPlug 0.000 2529.281
8 PERIMETER_BOT_ZN_4_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_BOT_ZN_4 201.98 10.9 1629.929 8.070 149.930 0.000 0.500 0.000 0.500 MiscPlug 0.000 1629.929
9 PERIMETER_MID_ZN_3_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_MID_ZN_3 313.41 16.9 2529.242 8.070 149.931 0.000 0.500 0.000 0.500 MiscPlug 0.000 2529.242
10 PERIMETER_MID_ZN_2_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_MID_ZN_2 201.98 10.9 1629.940 8.070 149.931 0.000 0.500 0.000 0.500 MiscPlug 0.000 1629.940
11 PERIMETER_MID_ZN_1_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_MID_ZN_1 313.42 16.9 2529.281 8.070 149.930 0.000 0.500 0.000 0.500 MiscPlug 0.000 2529.281
12 PERIMETER_MID_ZN_4_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_MID_ZN_4 201.98 10.9 1629.929 8.070 149.930 0.000 0.500 0.000 0.500 MiscPlug 0.000 1629.929
13 PERIMETER_TOP_ZN_3_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_TOP_ZN_3 313.41 16.9 2529.242 8.070 149.931 0.000 0.500 0.000 0.500 MiscPlug 0.000 2529.242
14 PERIMETER_TOP_ZN_2_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_TOP_ZN_2 201.98 10.9 1629.940 8.070 149.931 0.000 0.500 0.000 0.500 MiscPlug 0.000 1629.940
15 PERIMETER_TOP_ZN_1_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_TOP_ZN_1 313.42 16.9 2529.281 8.070 149.930 0.000 0.500 0.000 0.500 MiscPlug 0.000 2529.281
16 PERIMETER_TOP_ZN_4_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_TOP_ZN_4 201.98 10.9 1629.929 8.070 149.930 0.000 0.500 0.000 0.500 MiscPlug 0.000 1629.929
17 DATACENTER_BASEMENT_MISCPLUG_EQUIP DATACENTER_EQUIP_SCH DATACENTER_BASEMENT_ZN_6 783.68 42.2 379632.522 484.423 9000.000 0.000 0.100 0.000 0.900 DataCenterPlugLoads 94908.130 379632.522
18 DATACENTER_BOT_MISCPLUG_EQUIP DATACENTER_EQUIP_SCH DATACENTER_BOT_ZN_6 36.20 1.9 7794.422 215.299 4000.000 0.000 0.100 0.000 0.900 DataCenterPlugLoads 1948.606 7794.422
19 DATACENTER_MID_MISCPLUG_EQUIP DATACENTER_EQUIP_SCH DATACENTER_MID_ZN_6 36.20 1.9 7794.422 215.299 4000.000 0.000 0.100 0.000 0.900 DataCenterPlugLoads 1948.606 7794.422
20 DATACENTER_TOP_MISCPLUG_EQUIP DATACENTER_EQUIP_SCH DATACENTER_TOP_ZN_6 36.20 1.9 7794.422 215.299 4000.000 0.000 0.100 0.000 0.900 DataCenterPlugLoads 1948.606 7794.422


Construction CTF

Construction Name Index #Layers #CTFs Time Step {hours} ThermalConductance {w/m2-K} OuterThermalAbsorptance InnerThermalAbsorptance OuterSolarAbsorptance InnerSolarAbsorptance Roughness
1 SWINGING DOOR_CON 1 1 1 0.167 3.975 0.900 0.900 0.700 0.700 MediumRough
2 INTERIORFURNISHINGS 2 1 9 0.167 0.8000 0.900 0.900 0.700 0.700 MediumSmooth
3 DROPCEILING 4 1 3 0.167 4.488 0.900 0.900 0.700 0.700 MediumSmooth
4 INT_WALL 7 2 4 0.167 6.299 0.900 0.900 0.700 0.700 Smooth
5 EXT_SLAB_8IN_WITH_CARPET 8 2 7 0.167 3.285 0.900 0.900 0.700 0.700 MediumRough
6 INT_SLAB_FLOOR 12 2 7 0.167 3.839 0.900 0.900 0.700 0.700 MediumRough
7 INT_SLAB_CEILING 13 2 7 0.167 3.839 0.900 0.900 0.700 0.700 VeryRough
8 NONRES_ROOF 17 3 3 0.167 0.2284 0.750 0.900 0.450 0.700 Rough
9 NONRES_EXT_WALL_GRD 20 3 9 0.167 1.223 0.900 0.900 0.700 0.700 MediumRough
10 NONRES_EXT_WALL_MID 21 3 9 0.167 1.174 0.900 0.900 0.700 0.700 MediumRough
11 NONRES_EXT_WALL_TOP 22 3 9 0.167 1.421 0.900 0.900 0.700 0.700 MediumRough
12 BASEMENT_WALL_EAST_CFACTOR 39 2 7 0.167 0.9401 0.000 0.900 0.000 0.700 MediumRough
13 BASEMENT_WALL_SOUTH_CFACTOR 40 2 7 0.167 0.9401 0.000 0.900 0.000 0.700 MediumRough
14 BASEMENT_WALL_NORTH_CFACTOR 41 2 7 0.167 0.9401 0.000 0.900 0.000 0.700 MediumRough
15 DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR 42 2 7 0.167 0.9401 0.000 0.900 0.000 0.700 MediumRough
16 DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR 43 2 7 0.167 0.9401 0.000 0.900 0.000 0.700 MediumRough
17 DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR 44 2 7 0.167 0.9401 0.000 0.900 0.000 0.700 MediumRough


Material CTF Summary

Material Name Thickness {m} Conductivity {w/m-K} Density {kg/m3} Specific Heat {J/kg-K} ThermalResistance {m2-K/w}
1 OPAQUE DOOR PANEL_CON 0.0000 0.000 0.000 0.000 0.2516
2 STD WOOD 6INCH 0.1500 0.120 540.000 1210.000 1.250
3 AC02 ACOUSTIC CEILING 0.0127 0.057 288.000 1339.000 0.2228
4 G01 13MM GYPSUM BOARD 0.0127 0.160 800.000 1090.000 0.7937E-01
5 G01 13MM GYPSUM BOARD 0.0127 0.160 800.000 1090.000 0.7937E-01
6 200MM NORMALWEIGHT CONCRETE FLOOR 0.2032 2.310 2322.000 832.000 0.8797E-01
7 CP02 CARPET PAD 0.0000 0.000 0.000 0.000 0.2165
8 100MM NORMALWEIGHT CONCRETE FLOOR 0.1016 2.310 2322.000 832.000 0.4398E-01
9 CP02 CARPET PAD 0.0000 0.000 0.000 0.000 0.2165
10 CP02 CARPET PAD 0.0000 0.000 0.000 0.000 0.2165
11 100MM NORMALWEIGHT CONCRETE FLOOR 0.1016 2.310 2322.000 832.000 0.4398E-01
12 F13 BUILT-UP ROOFING 0.0095 0.160 1120.000 1460.000 0.5938E-01
13 NONRES_ROOF_INSULATION 0.0000 0.000 0.000 0.000 4.319
14 F08 METAL SURFACE 0.0008 45.280 7824.000 500.000 0.1767E-04
15 200MM NORMALWEIGHT CONCRETE WALL 0.2032 2.310 2322.000 832.000 0.8797E-01
16 NONRES_EXTERIOR_WALL_INSULATION_GRD 0.0000 0.000 0.000 0.000 0.6505
17 G01 13MM GYPSUM BOARD 0.0127 0.160 800.000 1090.000 0.7937E-01
18 200MM NORMALWEIGHT CONCRETE WALL 0.2032 2.310 2322.000 832.000 0.8797E-01
19 NONRES_EXTERIOR_WALL_INSULATION_MID 0.0000 0.000 0.000 0.000 0.6842
20 G01 13MM GYPSUM BOARD 0.0127 0.160 800.000 1090.000 0.7937E-01
21 200MM NORMALWEIGHT CONCRETE WALL 0.2032 2.310 2322.000 832.000 0.8797E-01
22 NONRES_EXTERIOR_WALL_INSULATION_TOP 0.0000 0.000 0.000 0.000 0.5363
23 G01 13MM GYPSUM BOARD 0.0127 0.160 800.000 1090.000 0.7937E-01
24 ~FC_Insulation_1 0.0000 0.000 0.000 0.000 0.9868
25 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
26 ~FC_Insulation_2 0.0000 0.000 0.000 0.000 0.9868
27 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
28 ~FC_Insulation_3 0.0000 0.000 0.000 0.000 0.9868
29 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
30 ~FC_Insulation_4 0.0000 0.000 0.000 0.000 0.9868
31 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
32 ~FC_Insulation_5 0.0000 0.000 0.000 0.000 0.9868
33 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
34 ~FC_Insulation_6 0.0000 0.000 0.000 0.000 0.9868
35 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01


CTF

Time Outside Cross Inside Flux (except final one)
1 1 0.0000000 0.0000000 -0.0000000 -0.0000000
2 0 3.9747841 3.9747841 3.9747841  
3 9 -0.27580628E-02 0.97439125E-12 -0.27580628E-02 0.28516790E-03
4 8 0.73590997E-01 0.21837543E-08 0.73590997E-01 -0.77836043E-02
5 7 -0.82599318 0.23162835E-06 -0.82599318 0.89703933E-01
6 6 5.1113916 0.48671053E-05 5.1113916 -0.57224845
7 5 -19.214933 0.30163627E-04 -19.214933 2.2266322
8 4 45.557404 0.63181060E-04 45.557404 -5.4853312
9 3 -68.275533 0.44785456E-04 -68.275533 8.5710568
10 2 62.555368 0.93952058E-05 62.555368 -8.2111738
11 1 -31.904423 0.39200004E-06 -31.904423 4.3886678
12 0 6.9260389 0.77047546E-09 6.9260389  
13 3 -0.21589802E-09 0.15643069E-09 -0.21589802E-09 0.12999471E-21
14 2 0.50772448E-02 0.30006816E-02 0.50772448E-02 -0.13693132E-08
15 1 -2.5944910 1.4597758 -2.5944910 0.76344767E-02
16 0 7.0433378 2.9911476 7.0433378  
17 4 0.68458728E-09 0.26079551E-09 0.68458728E-09 -0.34507121E-18
18 3 -0.72180374E-03 0.24295686E-03 -0.72180374E-03 0.69691454E-09
19 2 0.83054762 0.27682775 0.83054762 -0.35168967E-03
20 1 -12.650482 3.3590720 -12.650482 0.19281313
21 0 16.907513 1.4507143 16.907513  
22 7 -0.18651654E-16 -0.16428647E-15 -0.26578847E-08 -0.25364002E-17
23 6 0.67402962E-01 0.99142722E-07 0.38101547E-02 -0.76639482E-03
24 5 -1.8580732 0.49502125E-04 -0.10651409 0.21891119E-01
25 4 18.220105 0.12801333E-02 1.0775450 -0.22586539
26 3 -79.928293 0.66708484E-02 -4.9803755 1.0625663
27 2 166.43177 0.75131194E-02 11.128837 -2.4125483
28 1 -159.97298 0.18548900E-02 -11.587784 2.5494418
29 0 57.057412 0.52755123E-04 4.4818272  
30 7 0.43260499E-16 0.34524919E-16 0.52793240E-17 0.0000000
31 6 0.69434179E-09 0.98085174E-11 0.18162501E-10 -0.40870994E-12
32 5 -0.12888762E-04 0.28373718E-06 -0.16918523E-06 0.92361873E-08
33 4 0.25174112E-01 0.33697681E-03 0.22646198E-03 -0.31467795E-04
34 3 -3.7600775 0.27170599E-01 -0.48495626E-01 0.94171705E-02
35 2 51.553741 0.22121684 1.2284947 -0.25833933
36 1 -128.86110 0.21944682 -5.1479470 1.1228340
37 0 81.526494 0.16043334E-01 4.4519351  
38 7 0.52793240E-17 0.34524919E-16 0.43260499E-16 0.0000000
39 6 0.18162501E-10 0.98085174E-11 0.69434179E-09 -0.40870994E-12
40 5 -0.16918523E-06 0.28373718E-06 -0.12888762E-04 0.92361873E-08
41 4 0.22646198E-03 0.33697681E-03 0.25174112E-01 -0.31467795E-04
42 3 -0.48495626E-01 0.27170599E-01 -3.7600775 0.94171705E-02
43 2 1.2284947 0.22121684 51.553741 -0.25833933
44 1 -5.1479470 0.21944682 -128.86110 1.1228340
45 0 4.4519351 0.16043334E-01 81.526494  
46 3 -0.62451068E-06 0.10350887E-08 -0.38276125E-05 0.11995084E-16
47 2 0.77976586 0.13989883E-02 1.0579789 -0.73382352E-06
48 1 -21.958702 0.93426804E-01 -6.3215779 0.20283230
49 0 21.361010 0.87247630E-01 5.4456762  
50 9 0.12806887E-14 0.42271709E-16 -0.13586671E-09 -0.40936836E-17
51 8 0.19922932E-07 0.16187222E-12 0.35697139E-03 -0.22653060E-09
52 7 -0.11619186E-01 0.85920355E-08 -0.22189363E-01 0.13211437E-03
53 6 0.38843793 0.30204786E-05 0.45766083 -0.45484060E-02
54 5 -5.0254998 0.11379910E-03 -4.3303126 0.61137149E-01
55 4 32.272621 0.93848507E-03 21.006408 -0.41242756
56 3 -109.67225 0.20601564E-02 -54.766020 1.4927443
57 2 195.59070 0.11662962E-02 77.088399 -2.8762550
58 1 -170.59539 0.12524661E-03 -55.026900 2.7356126
59 0 57.057407 0.71759292E-06 15.597005  
60 9 0.14110139E-14 0.39742576E-16 -0.13817129E-09 -0.60843190E-17
61 8 0.20247994E-07 0.15595569E-12 0.36048606E-03 -0.23022666E-09
62 7 -0.11724403E-01 0.82461052E-08 -0.22340970E-01 0.13331073E-03
63 6 0.39129736 0.28944083E-05 0.46010459 -0.45821116E-02
64 5 -5.0534104 0.10890513E-03 -4.3491197 0.61483222E-01
65 4 32.396114 0.89705981E-03 21.080005 -0.41406715
66 3 -109.93510 0.19671505E-02 -54.911560 1.4965416
67 2 195.85133 0.11126060E-02 77.221727 -2.8803937
68 1 -170.69171 0.11937799E-03 -55.065382 2.7373008
69 0 57.057407 0.68337402E-06 15.590414  
70 9 0.11953810E-14 0.45347951E-16 -0.12637851E-09 -0.31580148E-17
71 8 0.18583176E-07 0.18541820E-12 0.34227377E-03 -0.21129711E-09
72 7 -0.11178467E-01 0.10005971E-07 -0.21554080E-01 0.12710323E-03
73 6 0.37645972 0.35409928E-05 0.44740546 -0.44072130E-02
74 5 -4.9085688 0.13417224E-03 -4.2513079 0.59687292E-01
75 4 31.755172 0.11121548E-02 20.697061 -0.40555762
76 3 -108.57065 0.24524110E-02 -54.154201 1.4768303
77 2 194.49811 0.13939007E-02 76.528253 -2.8589059
78 1 -170.19150 0.15023953E-03 -54.865849 2.7285341
79 0 57.057407 0.86422455E-06 15.625098  
80 7 -0.41493644E-09 0.26375357E-16 0.26213203E-14 -0.63268016E-17
81 6 0.27465604E-04 0.18700671E-07 0.31288692E-02 -0.26247577E-04
82 5 -0.19935291E-02 0.11146933E-04 -0.22025565 0.19255324E-02
83 4 0.45890804E-01 0.50864553E-03 4.7717348 -0.44709298E-01
84 3 -0.40280019 0.40571884E-02 -37.694667 0.39504237
85 2 1.4296488 0.67623010E-02 115.84777 -1.4094303
86 1 -2.0629154 0.20697549E-02 -143.53273 2.0428830
87 0 1.0055995 0.48413807E-04 60.838472  
88 7 -0.41493644E-09 0.26375357E-16 0.26213203E-14 -0.63268016E-17
89 6 0.27465604E-04 0.18700671E-07 0.31288692E-02 -0.26247577E-04
90 5 -0.19935291E-02 0.11146933E-04 -0.22025565 0.19255324E-02
91 4 0.45890804E-01 0.50864553E-03 4.7717348 -0.44709298E-01
92 3 -0.40280019 0.40571884E-02 -37.694667 0.39504237
93 2 1.4296488 0.67623010E-02 115.84777 -1.4094303
94 1 -2.0629154 0.20697549E-02 -143.53273 2.0428830
95 0 1.0055995 0.48413807E-04 60.838472  
96 7 -0.41493644E-09 0.26375357E-16 0.26213203E-14 -0.63268016E-17
97 6 0.27465604E-04 0.18700671E-07 0.31288692E-02 -0.26247577E-04
98 5 -0.19935291E-02 0.11146933E-04 -0.22025565 0.19255324E-02
99 4 0.45890804E-01 0.50864553E-03 4.7717348 -0.44709298E-01
100 3 -0.40280019 0.40571884E-02 -37.694667 0.39504237
101 2 1.4296488 0.67623010E-02 115.84777 -1.4094303
102 1 -2.0629154 0.20697549E-02 -143.53273 2.0428830
103 0 1.0055995 0.48413807E-04 60.838472  
104 7 -0.41493644E-09 0.26375357E-16 0.26213203E-14 -0.63268016E-17
105 6 0.27465604E-04 0.18700671E-07 0.31288692E-02 -0.26247577E-04
106 5 -0.19935291E-02 0.11146933E-04 -0.22025565 0.19255324E-02
107 4 0.45890804E-01 0.50864553E-03 4.7717348 -0.44709298E-01
108 3 -0.40280019 0.40571884E-02 -37.694667 0.39504237
109 2 1.4296488 0.67623010E-02 115.84777 -1.4094303
110 1 -2.0629154 0.20697549E-02 -143.53273 2.0428830
111 0 1.0055995 0.48413807E-04 60.838472  
112 7 -0.41493644E-09 0.26375357E-16 0.26213203E-14 -0.63268016E-17
113 6 0.27465604E-04 0.18700671E-07 0.31288692E-02 -0.26247577E-04
114 5 -0.19935291E-02 0.11146933E-04 -0.22025565 0.19255324E-02
115 4 0.45890804E-01 0.50864553E-03 4.7717348 -0.44709298E-01
116 3 -0.40280019 0.40571884E-02 -37.694667 0.39504237
117 2 1.4296488 0.67623010E-02 115.84777 -1.4094303
118 1 -2.0629154 0.20697549E-02 -143.53273 2.0428830
119 0 1.0055995 0.48413807E-04 60.838472  
120 7 -0.41493644E-09 0.26375357E-16 0.26213203E-14 -0.63268016E-17
121 6 0.27465604E-04 0.18700671E-07 0.31288692E-02 -0.26247577E-04
122 5 -0.19935291E-02 0.11146933E-04 -0.22025565 0.19255324E-02
123 4 0.45890804E-01 0.50864553E-03 4.7717348 -0.44709298E-01
124 3 -0.40280019 0.40571884E-02 -37.694667 0.39504237
125 2 1.4296488 0.67623010E-02 115.84777 -1.4094303
126 1 -2.0629154 0.20697549E-02 -143.53273 2.0428830
127 0 1.0055995 0.48413807E-04 60.838472  


WindowConstruction

Construction Name Index #Layers Roughness Conductance {W/m2-K} Conductance (Before Adjusted) {W/m2-K} Convection Coefficient Adjustment Ratio SHGC Solar Transmittance at Normal Incidence Visible Transmittance at Normal Incidence
1 WINDOW_U_0.498_SHGC_EAST_0.25 35 1 VerySmooth 2.831 2.831 1.000 0.251    
2 WINDOW_U_0.498_SHGC_SOUTH_0.25 36 1 VerySmooth 2.831 2.831 1.000 0.251    
3 WINDOW_U_0.498_SHGC_WEST_0.25 37 1 VerySmooth 2.831 2.831 1.000 0.251    
4 WINDOW_U_0.498_SHGC_NORTH_0.25 38 1 VerySmooth 2.831 2.831 1.000 0.251    


WindowMaterial:Glazing

Material Name Optical Data Type Spectral Data Set Name Thickness {m} Solar Transmittance Front Solar Reflectance Back Solar Reflectance Visible Transmittance Front Visible Reflectance Back Visible Reflectance Infrared Transmittance Front Thermal Emissivity Back Thermal Emissivity Conductivity {W/m-K} Dirt Factor Solar Diffusing
1 GLAZING LAYER EAST SpectralAverage   2.00974E-002 0.16139 0.61139 0.61139 0.27500 0.15630 0.22588 0.00000 0.84000 0.84000 0.10990 1.00000 No
2 GLAZING LAYER SOUTH SpectralAverage   2.00974E-002 0.16139 0.61139 0.61139 0.27500 0.15630 0.22588 0.00000 0.84000 0.84000 0.10990 1.00000 No
3 GLAZING LAYER WEST SpectralAverage   2.00974E-002 0.16139 0.61139 0.61139 0.27500 0.15630 0.22588 0.00000 0.84000 0.84000 0.10990 1.00000 No
4 GLAZING LAYER NORTH SpectralAverage   2.00974E-002 0.16139 0.61139 0.61139 0.27500 0.15630 0.22588 0.00000 0.84000 0.84000 0.10990 1.00000 No


Shadowing/Sun Position Calculations Annual Simulations

Shading Calculation Method Shading Calculation Update Frequency Method Shading Calculation Update Frequency {days} Maximum Figures in Shadow Overlap Calculations {} Polygon Clipping Algorithm Pixel Counting Resolution Sky Diffuse Modeling Algorithm Output External Shading Calculation Results Disable Self-Shading Within Shading Zone Groups Disable Self-Shading From Shading Zone Groups to Other Zones
1 PolygonClipping Periodic 30 15000 SutherlandHodgman 512 SimpleSkyDiffuseModeling No No No


Enclosure/Window Adjacency Daylighting Counts

Enclosure Name Number of Exterior Windows Number of Exterior Windows in Adjacent Enclosures
1 PERIMETER_BOT_ZN_3 5 0
2 PERIMETER_BOT_ZN_2 3 0
3 PERIMETER_BOT_ZN_1 5 0
4 PERIMETER_BOT_ZN_4 3 0
5 PERIMETER_MID_ZN_3 1 0
6 PERIMETER_MID_ZN_2 1 0
7 PERIMETER_MID_ZN_1 1 0
8 PERIMETER_MID_ZN_4 1 0
9 PERIMETER_TOP_ZN_3 1 0
10 PERIMETER_TOP_ZN_2 1 0
11 PERIMETER_TOP_ZN_1 1 0
12 PERIMETER_TOP_ZN_4 1 0


Enclosure/Window Adjacency Daylighting Matrix

Enclosure Name Number of Adjacent Enclosures with Windows Adjacent Enclosure Names - 1st 100 (max)
1 PERIMETER_BOT_ZN_3 0  
2 PERIMETER_BOT_ZN_2 0  
3 PERIMETER_BOT_ZN_1 0  
4 PERIMETER_BOT_ZN_4 0  
5 PERIMETER_MID_ZN_3 0  
6 PERIMETER_MID_ZN_2 0  
7 PERIMETER_MID_ZN_1 0  
8 PERIMETER_MID_ZN_4 0  
9 PERIMETER_TOP_ZN_3 0  
10 PERIMETER_TOP_ZN_2 0  
11 PERIMETER_TOP_ZN_1 0  
12 PERIMETER_TOP_ZN_4 0  


Water Heater Information

Type Name Volume {m3} Maximum Capacity {W} Standard Rated Recovery Efficiency Standard Rated Energy Factor
1 WaterHeater:Mixed SWHSYS1 WATER HEATER 1.1356 87921.3 0.481 5.5005E-002


Surface Convection Parameters

Surface Name Outside Model Assignment Outside Area [m2] Outside Perimeter [m] Outside Height [m] Inside Model Assignment Inside Height [m] Inside Perimeter Envelope [m] Inside Hydraulic Diameter [m] Window Wall Ratio Window Location Near Radiant {Yes/No} Has Active HVAC {Yes/No}
1 BASEMENT_WALL_EAST 0 0.00 0.00 0.00 0 2.44 0.00 52.56 -999.00 0 No No
2 BASEMENT_WALL_SOUTH 0 0.00 0.00 0.00 0 2.44 0.00 52.56 -999.00 0 No No
3 BASEMENT_WALL_NORTH 0 0.00 0.00 0.00 0 2.44 0.00 52.56 -999.00 0 No No
4 BASEMENT_WALL_WEST 0 0.00 0.00 0.00 0 2.44 0.00 52.56 -999.00 0 No No
5 BASEMENT_FLOOR 0 0.00 0.00 0.00 0 2.44 0.00 52.56 -999.00 0 No No
6 PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.44 0.00 52.56 -999.00 0 No No
7 PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.44 0.00 52.56 -999.00 0 No No
8 CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.44 0.00 52.56 -999.00 0 No No
9 PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.44 0.00 52.56 -999.00 0 No No
10 BASEMENT_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.44 0.00 52.56 -999.00 0 No No
11 CORE_BOT_ZN_5_WALL_SOUTH 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
12 CORE_BOT_ZN_5_WALL_WEST 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
13 CORE_BOT_ZN_5_WALL_NORTH 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
14 CORE_BOT_ZN_5_WALL_EAST 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
15 DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
16 CORE_BOT_ZN_5_FLOOR 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
17 CORE_BOT_ZN_5_CEILING 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
18 CORE_BOTTOM_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
19 CORE_MID_ZN_5_WALL_SOUTH 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
20 CORE_MID_ZN_5_WALL_WEST 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
21 CORE_MID_ZN_5_WALL_NORTH 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
22 CORE_MID_ZN_5_WALL_EAST 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
23 CORE_MID_ZN_5_FLOOR 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
24 CORE_MID_ZN_5_CEILING 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
25 CORE_MID_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
26 CORE_TOP_ZN_5_WALL_SOUTH 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
27 CORE_TOP_ZN_5_WALL_WEST 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
28 CORE_TOP_ZN_5_WALL_NORTH 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
29 CORE_TOP_ZN_5_WALL_EAST 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
30 CORE_TOP_ZN_5_FLOOR 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
31 CORE_TOP_ZN_5_CEILING 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
32 CORE_TOP_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
33 PERIMETER_BOT_ZN_3_WALL_NORTH 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.58 3 No No
34 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.58 5 No No
35 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.58 5 No No
36 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.58 5 No No
37 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.58 5 No No
38 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.58 5 No No
39 PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.58 0 No No
40 PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.58 0 No No
41 PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.58 0 No No
42 PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.58 0 No No
43 PERIMETER_BOT_ZN_3_WALL_WEST 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
44 CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
45 PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
46 DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
47 PERIMETER_BOT_ZN_3_FLOOR 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
48 DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
49 PERIMETER_BOT_ZN_3_CEILING 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
50 PERIMETER_BOT_ZN_3_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
51 PERIMETER_BOT_ZN_2_WALL_EAST 0 579.48 250.73 37.50 0 2.74 48.74 7.58 0.58 3 No No
52 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 0 579.48 250.73 37.50 0 2.74 48.74 7.58 0.58 5 No No
53 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 0 579.48 250.73 37.50 0 2.74 48.74 7.58 0.58 5 No No
54 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 0 579.48 250.73 37.50 0 2.74 48.74 7.58 0.58 5 No No
55 PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 0 579.48 250.73 37.50 0 2.74 48.74 7.58 0.58 0 No No
56 PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 0 579.48 250.73 37.50 0 2.74 48.74 7.58 0.58 0 No No
57 PERIMETER_BOT_ZN_2_WALL_NORTH 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
58 CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
59 PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
60 PERIMETER_BOT_ZN_2_FLOOR 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
61 PERIMETER_BOT_ZN_2_CEILING 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
62 PERIMETER_BOT_ZN_2_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
63 PERIMETER_BOT_ZN_1_WALL_SOUTH 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.58 3 No No
64 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.58 5 No No
65 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.58 5 No No
66 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.58 5 No No
67 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.58 5 No No
68 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.58 5 No No
69 PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.58 0 No No
70 PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.58 0 No No
71 PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.58 0 No No
72 PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.58 0 No No
73 PERIMETER_BOT_ZN_1_WALL_EAST 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
74 DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
75 PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
76 CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
77 DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
78 PERIMETER_BOT_ZN_1_FLOOR 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
79 PERIMETER_BOT_ZN_1_CEILING 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
80 PERIMETER_BOT_ZN_1_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
81 PERIMETER_BOT_ZN_4_WALL_WEST 0 579.48 172.48 37.50 0 2.74 48.74 7.58 0.58 3 No No
82 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 0 579.48 172.48 37.50 0 2.74 48.74 7.58 0.58 5 No No
83 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 0 579.48 172.48 37.50 0 2.74 48.74 7.58 0.58 5 No No
84 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 0 579.48 172.48 37.50 0 2.74 48.74 7.58 0.58 5 No No
85 PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 0 579.48 172.48 37.50 0 2.74 48.74 7.58 0.58 0 No No
86 PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 0 579.48 172.48 37.50 0 2.74 48.74 7.58 0.58 0 No No
87 PERIMETER_BOT_ZN_4_WALL_SOUTH 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
88 DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
89 PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
90 PERIMETER_BOT_ZN_4_FLOOR 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
91 PERIMETER_BOT_ZN_4_CEILING 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
92 PERIMETER_BOT_ZN_4_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
93 PERIMETER_MID_ZN_3_WALL_NORTH 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.58 3 No No
94 PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.58 5 No No
95 PERIMETER_MID_ZN_3_WALL_WEST 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
96 CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
97 PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
98 DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
99 PERIMETER_MID_ZN_3_FLOOR 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
100 PERIMETER_MID_ZN_3_CEILING 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
101 PERIMETER_MID_ZN_3_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
102 PERIMETER_MID_ZN_2_WALL_EAST 0 579.48 250.73 37.50 0 2.74 48.74 7.58 0.58 3 No No
103 PERIMETER_MID_ZN_2_WALL_EAST_WINDOW 0 579.48 250.73 37.50 0 2.74 48.74 7.58 0.58 5 No No
104 PERIMETER_MID_ZN_2_WALL_NORTH 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
105 CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
106 PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
107 PERIMETER_MID_ZN_2_FLOOR 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
108 PERIMETER_MID_ZN_2_CEILING 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
109 PERIMETER_MID_ZN_2_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
110 PERIMETER_MID_ZN_1_WALL_EAST 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
111 PERIMETER_MID_ZN_1_WALL_SOUTH 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.58 3 No No
112 PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.58 5 No No
113 DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
114 PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
115 CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
116 PERIMETER_MID_ZN_1_FLOOR 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
117 PERIMETER_MID_ZN_1_CEILING 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
118 PERIMETER_MID_ZN_1_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
119 PERIMETER_MID_ZN_4_WALL_WEST 0 579.48 172.48 37.50 0 2.74 48.74 7.58 0.58 3 No No
120 PERIMETER_MID_ZN_4_WALL_WEST_WINDOW 0 579.48 172.48 37.50 0 2.74 48.74 7.58 0.58 5 No No
121 PERIMETER_MID_ZN_4_WALL_SOUTH 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
122 DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
123 PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
124 PERIMETER_MID_ZN_4_FLOOR 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
125 PERIMETER_MID_ZN_4_CEILING 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
126 PERIMETER_MID_ZN_4_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
127 PERIMETER_TOP_ZN_3_WALL_NORTH 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.58 3 No No
128 PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.58 5 No No
129 PERIMETER_TOP_ZN_3_WALL_WEST 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
130 CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
131 PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
132 DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
133 PERIMETER_TOP_ZN_3_FLOOR 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
134 PERIMETER_TOP_ZN_3_CEILING 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
135 PERIMETER_TOP_ZN_3_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
136 PERIMETER_TOP_ZN_2_WALL_EAST 0 579.48 250.73 37.50 0 2.74 48.74 7.58 0.58 3 No No
137 PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW 0 579.48 250.73 37.50 0 2.74 48.74 7.58 0.58 5 No No
138 PERIMETER_TOP_ZN_2_WALL_NORTH 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
139 CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
140 INT-PER3S-NE-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
141 PERIMETER_TOP_ZN_2_FLOOR 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
142 PERIMETER_TOP_ZN_2_CEILING 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
143 PERIMETER_TOP_ZN_2_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
144 PERIMETER_TOP_ZN_1_WALL_SOUTH 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.58 3 No No
145 PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.58 5 No No
146 INT-PER3S-NE 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
147 DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
148 PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
149 CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
150 PERIMETER_TOP_ZN_1_FLOOR 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
151 PERIMETER_TOP_ZN_1_CEILING 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
152 PERIMETER_TOP_ZN_1_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
153 PERIMETER_TOP_ZN_4_WALL_WEST 0 579.48 172.48 37.50 0 2.74 48.74 7.58 0.58 3 No No
154 PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW 0 579.48 172.48 37.50 0 2.74 48.74 7.58 0.58 5 No No
155 PERIMETER_TOP_ZN_4_WALL_SOUTH 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
156 DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
157 PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
158 PERIMETER_TOP_ZN_4_FLOOR 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
159 PERIMETER_TOP_ZN_4_CEILING 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
160 PERIMETER_TOP_ZN_4_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
161 GROUNDFLOOR_PLENUM_WALL_NORTH 0 869.22 250.73 37.50 0 1.22 243.69 58.49 0.00 0 No No
162 GROUNDFLOOR_PLENUM_WEST 0 579.48 172.48 37.50 0 1.22 243.69 58.49 0.00 0 No No
163 GROUNDFLOOR_PLENUM_WALL_SOUTH 0 869.22 221.21 37.50 0 1.22 243.69 58.49 0.00 0 No No
164 GROUNDFLOOR_PLENUM_WALL_EAST 0 579.48 250.73 37.50 0 1.22 243.69 58.49 0.00 0 No No
165 iz-CORE_BOT_ZN_5_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
166 iz-PERIMETER_BOT_ZN_3_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
167 iz-PERIMETER_BOT_ZN_2_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
168 iz-PERIMETER_BOT_ZN_1_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
169 iz-PERIMETER_BOT_ZN_4_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
170 iz-DATACENTER_BOT_ZN_6_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
171 GROUNDFLOOR_PLENUM_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
172 MIDFLOOR_PLENUM_WALL_NORTH 0 869.22 250.73 37.50 0 1.22 243.69 58.49 0.00 0 No No
173 MIDFLOOR_PLENUM_WALL_WEST 0 579.48 172.48 37.50 0 1.22 243.69 58.49 0.00 0 No No
174 MIDFLOOR_PLENUM_WALL_SOUTH 0 869.22 221.21 37.50 0 1.22 243.69 58.49 0.00 0 No No
175 MIDFLOOR_PLENUM_WALL_EAST 0 579.48 250.73 37.50 0 1.22 243.69 58.49 0.00 0 No No
176 iz-CORE_MID_ZN_5_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
177 iz-PERIMETER_MID_ZN_3_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
178 iz-PERIMETER_MID_ZN_2_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
179 iz-PERIMETER_MID_ZN_1_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
180 iz-PERIMETER_MID_ZN_4_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
181 iz-DATACENTER_MID_ZN_6_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
182 MIDFLOOR_PLENUM_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
183 TOPFLOOR_PLENUM_WALL_NORTH 0 869.22 221.21 37.50 0 1.22 243.69 58.49 0.00 0 No No
184 TOPFLOOR_PLENUM_WALL_EAST 0 579.48 250.73 37.50 0 1.22 243.69 58.49 0.00 0 No No
185 TOPFLOOR_PLENUM_WALL_WEST 0 579.48 172.48 37.50 0 1.22 243.69 58.49 0.00 0 No No
186 TOPFLOOR_PLENUM_WALL_SOUTH 0 869.22 250.73 37.50 0 1.22 243.69 58.49 0.00 0 No No
187 iz-CORE_TOP_ZN_5_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
188 iz-PERIMETER_TOP_ZN_3_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
189 iz-PERIMETER_TOP_ZN_2_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
190 iz-PERIMETER_TOP_ZN_1_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
191 iz-PERIMETER_TOP_ZN_4_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
192 iz-DATACENTER_TOP_ZN_6_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
193 BUILDING_ROOF 0 3563.11 268.06 0.00 0 1.22 243.69 58.49 0.00 0 No No
194 DATACENTER_BOT_ZN_6_WALL_NORTH 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
195 DATACENTER_BOT_ZN_6_WALL_SOUTH 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
196 DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
197 DATACENTER_BOT_ZN_6_WALL_WEST 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
198 DATACENTER_BOT_ZN_6_FLOOR 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
199 DATACENTER_BOT_ZN_6_CEILING 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
200 DATACENTER_MID_ZN_6_WALL_WEST 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
201 DATACENTER_MID_ZN_6_WALL_SOUTH 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
202 DATACENTER_MID_ZN_6_WALL_EAST 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
203 DATACENTER_MID_ZN_6_WALL_NORTH 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
204 DATACENTER_MID_ZN_6_FLOOR 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
205 DATACENTER_MID_ZN_6_CEILING 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
206 DATACENTER_TOP_ZN_6_WALL_EAST 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
207 DATACENTER_TOP_ZN_6_WALL_WEST 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
208 DATACENTER_TOP_ZN_6_WALL_SOUTH 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
209 DATACENTER_TOP_ZN_6_WALL_NORTH 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
210 DATACENTER_TOP_ZN_6_FLOOR 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
211 DATACENTER_TOP_ZN_6_CEILING 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
212 DATACENTER_BASEMENT_ZN_6_WALL_NORTH 0 0.00 0.00 0.00 0 2.44 0.00 24.18 -999.00 0 No No
213 DATACENTER_BASEMENT_ZN_6_WALL_SOUTH 0 0.00 0.00 0.00 0 2.44 0.00 24.18 -999.00 0 No No
214 DATACENTER_BASEMENT_ZN_6_WALL_WEST 0 0.00 0.00 0.00 0 2.44 0.00 24.18 -999.00 0 No No
215 DATACENTER_BASEMENT_ZN_6_WALL_EAST 0 0.00 0.00 0.00 0 2.44 0.00 24.18 -999.00 0 No No
216 DATACENTER_BASEMENT_ZN_6_FLOOR 0 0.00 0.00 0.00 0 2.44 0.00 24.18 -999.00 0 No No
217 DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.44 0.00 24.18 -999.00 0 No No
218 DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 0 0.00 0.00 0.00 0 2.44 0.00 24.18 -999.00 0 No No
219 PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.44 0.00 24.18 -999.00 0 No No
220 DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 0 0.00 0.00 0.00 0 2.44 0.00 24.18 -999.00 0 No No
221 DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 0 0.00 0.00 0.00 0 2.44 0.00 24.18 -999.00 0 No No


ZoneInfiltration Airflow Stats Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Design Volume Flow Rate {m3/s} Volume Flow Rate/Floor Area {m3/s-m2} Volume Flow Rate/Exterior Surface Area {m3/s-m2} ACH - Air Changes per Hour Equation A - Constant Term Coefficient {} Equation B - Temperature Term Coefficient {1/C} Equation C - Velocity Term Coefficient {s/m} Equation D - Velocity Squared Term Coefficient {s2/m2}
1 PERIMETER_BOT_ZN_3_INFILTRATION INFIL_SCH_PNNL PERIMETER_BOT_ZN_3 313.41 16.9 0.114 3.646E-004 5.482E-004 0.478 0.000 0.000 0.224 0.000
2 PERIMETER_BOT_ZN_2_INFILTRATION INFIL_SCH_PNNL PERIMETER_BOT_ZN_2 201.98 10.9 7.617E-002 3.771E-004 5.534E-004 0.495 0.000 0.000 0.224 0.000
3 PERIMETER_BOT_ZN_1_INFILTRATION INFIL_SCH_PNNL PERIMETER_BOT_ZN_1 313.42 16.9 0.114 3.646E-004 5.482E-004 0.478 0.000 0.000 0.224 0.000
4 PERIMETER_BOT_ZN_4_INFILTRATION INFIL_SCH_PNNL PERIMETER_BOT_ZN_4 201.98 10.9 7.617E-002 3.771E-004 5.534E-004 0.495 0.000 0.000 0.224 0.000
5 PERIMETER_MID_ZN_3_INFILTRATION INFIL_SCH_PNNL PERIMETER_MID_ZN_3 313.41 16.9 0.114 3.646E-004 5.696E-004 0.478 0.000 0.000 0.224 0.000
6 PERIMETER_MID_ZN_2_INFILTRATION INFIL_SCH_PNNL PERIMETER_MID_ZN_2 201.98 10.9 7.617E-002 3.771E-004 5.696E-004 0.495 0.000 0.000 0.224 0.000
7 PERIMETER_MID_ZN_1_INFILTRATION INFIL_SCH_PNNL PERIMETER_MID_ZN_1 313.42 16.9 0.114 3.646E-004 5.696E-004 0.478 0.000 0.000 0.224 0.000
8 PERIMETER_MID_ZN_4_INFILTRATION INFIL_SCH_PNNL PERIMETER_MID_ZN_4 201.98 10.9 7.617E-002 3.771E-004 5.696E-004 0.495 0.000 0.000 0.224 0.000
9 PERIMETER_TOP_ZN_3_INFILTRATION INFIL_SCH_PNNL PERIMETER_TOP_ZN_3 313.41 16.9 0.114 3.646E-004 5.696E-004 0.478 0.000 0.000 0.224 0.000
10 PERIMETER_TOP_ZN_2_INFILTRATION INFIL_SCH_PNNL PERIMETER_TOP_ZN_2 201.98 10.9 7.617E-002 3.771E-004 5.696E-004 0.495 0.000 0.000 0.224 0.000
11 PERIMETER_TOP_ZN_1_INFILTRATION INFIL_SCH_PNNL PERIMETER_TOP_ZN_1 313.42 16.9 0.114 3.646E-004 5.696E-004 0.478 0.000 0.000 0.224 0.000
12 PERIMETER_TOP_ZN_4_INFILTRATION INFIL_SCH_PNNL PERIMETER_TOP_ZN_4 201.98 10.9 7.617E-002 3.771E-004 5.696E-004 0.495 0.000 0.000 0.224 0.000
13 GROUNDFLOOR_PLENUM_INFILTRATION INFIL_SCH_PNNL GROUNDFLOOR_PLENUM 3563.11 0.0 0.169 4.749E-005 5.696E-004 0.140 0.000 0.000 0.224 0.000
14 MIDFLOOR_PLENUM_INFILTRATION INFIL_SCH_PNNL MIDFLOOR_PLENUM 3563.11 0.0 0.169 4.749E-005 5.696E-004 0.140 0.000 0.000 0.224 0.000
15 TOPFLOOR_PLENUM_INFILTRATION INFIL_SCH_PNNL TOPFLOOR_PLENUM 3563.11 0.0 0.169 4.749E-005 4.384E-005 0.140 0.000 0.000 0.224 0.000


AirFlow Model

Simple
1 Simple


RoomAir Model

Zone Name Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined
1 BASEMENT Mixing/Well-Stirred
2 CORE_BOTTOM Mixing/Well-Stirred
3 CORE_MID Mixing/Well-Stirred
4 CORE_TOP Mixing/Well-Stirred
5 PERIMETER_BOT_ZN_3 Mixing/Well-Stirred
6 PERIMETER_BOT_ZN_2 Mixing/Well-Stirred
7 PERIMETER_BOT_ZN_1 Mixing/Well-Stirred
8 PERIMETER_BOT_ZN_4 Mixing/Well-Stirred
9 PERIMETER_MID_ZN_3 Mixing/Well-Stirred
10 PERIMETER_MID_ZN_2 Mixing/Well-Stirred
11 PERIMETER_MID_ZN_1 Mixing/Well-Stirred
12 PERIMETER_MID_ZN_4 Mixing/Well-Stirred
13 PERIMETER_TOP_ZN_3 Mixing/Well-Stirred
14 PERIMETER_TOP_ZN_2 Mixing/Well-Stirred
15 PERIMETER_TOP_ZN_1 Mixing/Well-Stirred
16 PERIMETER_TOP_ZN_4 Mixing/Well-Stirred
17 GROUNDFLOOR_PLENUM Mixing/Well-Stirred
18 MIDFLOOR_PLENUM Mixing/Well-Stirred
19 TOPFLOOR_PLENUM Mixing/Well-Stirred
20 DATACENTER_BOT_ZN_6 Mixing/Well-Stirred
21 DATACENTER_MID_ZN_6 Mixing/Well-Stirred
22 DATACENTER_TOP_ZN_6 Mixing/Well-Stirred
23 DATACENTER_BASEMENT_ZN_6 Mixing/Well-Stirred


AirflowNetwork Model:Control

No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation
1 NoMultizoneOrDistribution


Zone Volume Capacitance Multiplier

Sensible Heat Capacity Multiplier Moisture Capacity Multiplier Carbon Dioxide Capacity Multiplier Generic Contaminant Capacity Multiplier
1 1.000 1.000 1.000 1.000


Load Timesteps in Zone Design Calculation Averaging Window

Value
1 6


Heating Sizing Factor Information

Sizing Factor ID Value
1 Global 1.0000


Cooling Sizing Factor Information

Sizing Factor ID Value
1 Global 1.0000


Sky Daylight Factors

Sky Type MonthAndDay Daylighting Control Name Enclosure Name Window Name Reference Point Daylight Factor
1 Clear Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 PERIMETER_BOT_ZN_1_DAYLREFPT1 4.0259E-003
2 Clear Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 PERIMETER_BOT_ZN_1_DAYLREFPT2 4.0273E-003
3 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 PERIMETER_BOT_ZN_1_DAYLREFPT1 4.3141E-003
4 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 PERIMETER_BOT_ZN_1_DAYLREFPT2 4.3153E-003
5 Intermediate Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 PERIMETER_BOT_ZN_1_DAYLREFPT1 3.0965E-003
6 Intermediate Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 PERIMETER_BOT_ZN_1_DAYLREFPT2 3.0973E-003
7 Overcast Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 PERIMETER_BOT_ZN_1_DAYLREFPT1 1.7585E-003
8 Overcast Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 PERIMETER_BOT_ZN_1_DAYLREFPT2 1.7591E-003
9 Clear Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 PERIMETER_BOT_ZN_1_DAYLREFPT1 4.0574E-003
10 Clear Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 PERIMETER_BOT_ZN_1_DAYLREFPT2 4.1444E-003
11 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 PERIMETER_BOT_ZN_1_DAYLREFPT1 4.3398E-003
12 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 PERIMETER_BOT_ZN_1_DAYLREFPT2 4.4126E-003
13 Intermediate Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 PERIMETER_BOT_ZN_1_DAYLREFPT1 3.1170E-003
14 Intermediate Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 PERIMETER_BOT_ZN_1_DAYLREFPT2 3.1771E-003
15 Overcast Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 PERIMETER_BOT_ZN_1_DAYLREFPT1 1.7734E-003
16 Overcast Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 PERIMETER_BOT_ZN_1_DAYLREFPT2 1.8107E-003
17 Clear Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 PERIMETER_BOT_ZN_1_DAYLREFPT1 0.1021
18 Clear Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 PERIMETER_BOT_ZN_1_DAYLREFPT2 4.3682E-002
19 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 PERIMETER_BOT_ZN_1_DAYLREFPT1 0.1138
20 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 PERIMETER_BOT_ZN_1_DAYLREFPT2 4.7418E-002
21 Intermediate Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 PERIMETER_BOT_ZN_1_DAYLREFPT1 7.6268E-002
22 Intermediate Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 PERIMETER_BOT_ZN_1_DAYLREFPT2 2.8697E-002
23 Overcast Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 PERIMETER_BOT_ZN_1_DAYLREFPT1 3.1622E-002
24 Overcast Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 PERIMETER_BOT_ZN_1_DAYLREFPT2 1.0968E-002
25 Clear Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 PERIMETER_BOT_ZN_1_DAYLREFPT1 4.0671E-003
26 Clear Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 PERIMETER_BOT_ZN_1_DAYLREFPT2 4.1932E-003
27 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 PERIMETER_BOT_ZN_1_DAYLREFPT1 4.3504E-003
28 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 PERIMETER_BOT_ZN_1_DAYLREFPT2 4.4660E-003
29 Intermediate Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 PERIMETER_BOT_ZN_1_DAYLREFPT1 3.1262E-003
30 Intermediate Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 PERIMETER_BOT_ZN_1_DAYLREFPT2 3.2121E-003
31 Overcast Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 PERIMETER_BOT_ZN_1_DAYLREFPT1 1.7738E-003
32 Overcast Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 PERIMETER_BOT_ZN_1_DAYLREFPT2 1.8117E-003
33 Clear Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 PERIMETER_BOT_ZN_1_DAYLREFPT1 4.0258E-003
34 Clear Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 PERIMETER_BOT_ZN_1_DAYLREFPT2 4.0275E-003
35 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 PERIMETER_BOT_ZN_1_DAYLREFPT1 4.3141E-003
36 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 PERIMETER_BOT_ZN_1_DAYLREFPT2 4.3155E-003
37 Intermediate Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 PERIMETER_BOT_ZN_1_DAYLREFPT1 3.0965E-003
38 Intermediate Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 PERIMETER_BOT_ZN_1_DAYLREFPT2 3.0976E-003
39 Overcast Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 PERIMETER_BOT_ZN_1_DAYLREFPT1 1.7585E-003
40 Overcast Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 PERIMETER_BOT_ZN_1_DAYLREFPT2 1.7590E-003
41 Clear Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 PERIMETER_BOT_ZN_2_DAYLREFPT1 4.2034E-003
42 Clear Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 PERIMETER_BOT_ZN_2_DAYLREFPT2 4.3976E-003
43 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 PERIMETER_BOT_ZN_2_DAYLREFPT1 4.0891E-003
44 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 PERIMETER_BOT_ZN_2_DAYLREFPT2 4.2986E-003
45 Intermediate Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 PERIMETER_BOT_ZN_2_DAYLREFPT1 3.7560E-003
46 Intermediate Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 PERIMETER_BOT_ZN_2_DAYLREFPT2 3.8453E-003
47 Overcast Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 PERIMETER_BOT_ZN_2_DAYLREFPT1 3.0071E-003
48 Overcast Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 PERIMETER_BOT_ZN_2_DAYLREFPT2 3.0329E-003
49 Clear Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 PERIMETER_BOT_ZN_2_DAYLREFPT1 4.8886E-002
50 Clear Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 PERIMETER_BOT_ZN_2_DAYLREFPT2 2.2855E-002
51 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 PERIMETER_BOT_ZN_2_DAYLREFPT1 4.7304E-002
52 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 PERIMETER_BOT_ZN_2_DAYLREFPT2 2.1359E-002
53 Intermediate Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 PERIMETER_BOT_ZN_2_DAYLREFPT1 4.6131E-002
54 Intermediate Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 PERIMETER_BOT_ZN_2_DAYLREFPT2 1.8727E-002
55 Overcast Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 PERIMETER_BOT_ZN_2_DAYLREFPT1 3.2931E-002
56 Overcast Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 PERIMETER_BOT_ZN_2_DAYLREFPT2 1.2292E-002
57 Clear Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 PERIMETER_BOT_ZN_2_DAYLREFPT1 4.1558E-003
58 Clear Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 PERIMETER_BOT_ZN_2_DAYLREFPT2 4.2209E-003
59 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 PERIMETER_BOT_ZN_2_DAYLREFPT1 4.0290E-003
60 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 PERIMETER_BOT_ZN_2_DAYLREFPT2 4.0768E-003
61 Intermediate Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 PERIMETER_BOT_ZN_2_DAYLREFPT1 3.7295E-003
62 Intermediate Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 PERIMETER_BOT_ZN_2_DAYLREFPT2 3.7504E-003
63 Overcast Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 PERIMETER_BOT_ZN_2_DAYLREFPT1 3.0072E-003
64 Overcast Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 PERIMETER_BOT_ZN_2_DAYLREFPT2 3.0333E-003
65 Clear Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 PERIMETER_BOT_ZN_3_DAYLREFPT1 1.7686E-003
66 Clear Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 PERIMETER_BOT_ZN_3_DAYLREFPT2 1.7701E-003
67 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 PERIMETER_BOT_ZN_3_DAYLREFPT1 1.5140E-003
68 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 PERIMETER_BOT_ZN_3_DAYLREFPT2 1.5153E-003
69 Intermediate Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 PERIMETER_BOT_ZN_3_DAYLREFPT1 1.3517E-003
70 Intermediate Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 PERIMETER_BOT_ZN_3_DAYLREFPT2 1.3527E-003
71 Overcast Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 PERIMETER_BOT_ZN_3_DAYLREFPT1 1.7586E-003
72 Overcast Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 PERIMETER_BOT_ZN_3_DAYLREFPT2 1.7591E-003
73 Clear Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 PERIMETER_BOT_ZN_3_DAYLREFPT1 1.8023E-003
74 Clear Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 PERIMETER_BOT_ZN_3_DAYLREFPT2 1.8840E-003
75 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 PERIMETER_BOT_ZN_3_DAYLREFPT1 1.5421E-003
76 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 PERIMETER_BOT_ZN_3_DAYLREFPT2 1.6080E-003
77 Intermediate Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 PERIMETER_BOT_ZN_3_DAYLREFPT1 1.3751E-003
78 Intermediate Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 PERIMETER_BOT_ZN_3_DAYLREFPT2 1.4258E-003
79 Overcast Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 PERIMETER_BOT_ZN_3_DAYLREFPT1 1.7738E-003
80 Overcast Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 PERIMETER_BOT_ZN_3_DAYLREFPT2 1.8118E-003
81 Clear Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 PERIMETER_BOT_ZN_3_DAYLREFPT1 2.7628E-002
82 Clear Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 PERIMETER_BOT_ZN_3_DAYLREFPT2 1.4405E-002
83 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 PERIMETER_BOT_ZN_3_DAYLREFPT1 2.1316E-002
84 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 PERIMETER_BOT_ZN_3_DAYLREFPT2 1.0970E-002
85 Intermediate Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 PERIMETER_BOT_ZN_3_DAYLREFPT1 1.9365E-002
86 Intermediate Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 PERIMETER_BOT_ZN_3_DAYLREFPT2 7.5418E-003
87 Overcast Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 PERIMETER_BOT_ZN_3_DAYLREFPT1 3.1622E-002
88 Overcast Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 PERIMETER_BOT_ZN_3_DAYLREFPT2 1.0965E-002
89 Clear Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 PERIMETER_BOT_ZN_3_DAYLREFPT1 1.7994E-003
90 Clear Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 PERIMETER_BOT_ZN_3_DAYLREFPT2 1.8819E-003
91 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 PERIMETER_BOT_ZN_3_DAYLREFPT1 1.5381E-003
92 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 PERIMETER_BOT_ZN_3_DAYLREFPT2 1.6009E-003
93 Intermediate Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 PERIMETER_BOT_ZN_3_DAYLREFPT1 1.3680E-003
94 Intermediate Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 PERIMETER_BOT_ZN_3_DAYLREFPT2 1.4040E-003
95 Overcast Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 PERIMETER_BOT_ZN_3_DAYLREFPT1 1.7735E-003
96 Overcast Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 PERIMETER_BOT_ZN_3_DAYLREFPT2 1.8107E-003
97 Clear Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 PERIMETER_BOT_ZN_3_DAYLREFPT1 1.7685E-003
98 Clear Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 PERIMETER_BOT_ZN_3_DAYLREFPT2 1.7698E-003
99 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 PERIMETER_BOT_ZN_3_DAYLREFPT1 1.5139E-003
100 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 PERIMETER_BOT_ZN_3_DAYLREFPT2 1.5150E-003
101 Intermediate Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 PERIMETER_BOT_ZN_3_DAYLREFPT1 1.3516E-003
102 Intermediate Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 PERIMETER_BOT_ZN_3_DAYLREFPT2 1.3523E-003
103 Overcast Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 PERIMETER_BOT_ZN_3_DAYLREFPT1 1.7585E-003
104 Overcast Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 PERIMETER_BOT_ZN_3_DAYLREFPT2 1.7591E-003
105 Clear Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 PERIMETER_BOT_ZN_4_DAYLREFPT1 3.3341E-003
106 Clear Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 PERIMETER_BOT_ZN_4_DAYLREFPT2 3.4039E-003
107 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 PERIMETER_BOT_ZN_4_DAYLREFPT1 3.0182E-003
108 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 PERIMETER_BOT_ZN_4_DAYLREFPT2 3.0684E-003
109 Intermediate Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 PERIMETER_BOT_ZN_4_DAYLREFPT1 3.0210E-003
110 Intermediate Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 PERIMETER_BOT_ZN_4_DAYLREFPT2 3.0389E-003
111 Overcast Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 PERIMETER_BOT_ZN_4_DAYLREFPT1 3.0073E-003
112 Overcast Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 PERIMETER_BOT_ZN_4_DAYLREFPT2 3.0334E-003
113 Clear Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 PERIMETER_BOT_ZN_4_DAYLREFPT1 3.4499E-002
114 Clear Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 PERIMETER_BOT_ZN_4_DAYLREFPT2 1.7374E-002
115 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 PERIMETER_BOT_ZN_4_DAYLREFPT1 2.9738E-002
116 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 PERIMETER_BOT_ZN_4_DAYLREFPT2 1.4668E-002
117 Intermediate Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 PERIMETER_BOT_ZN_4_DAYLREFPT1 3.3111E-002
118 Intermediate Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 PERIMETER_BOT_ZN_4_DAYLREFPT2 1.3713E-002
119 Overcast Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 PERIMETER_BOT_ZN_4_DAYLREFPT1 3.2931E-002
120 Overcast Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 PERIMETER_BOT_ZN_4_DAYLREFPT2 1.2292E-002
121 Clear Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 PERIMETER_BOT_ZN_4_DAYLREFPT1 3.3670E-003
122 Clear Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 PERIMETER_BOT_ZN_4_DAYLREFPT2 3.4949E-003
123 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 PERIMETER_BOT_ZN_4_DAYLREFPT1 3.0607E-003
124 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 PERIMETER_BOT_ZN_4_DAYLREFPT2 3.1879E-003
125 Intermediate Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 PERIMETER_BOT_ZN_4_DAYLREFPT1 3.0449E-003
126 Intermediate Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 PERIMETER_BOT_ZN_4_DAYLREFPT2 3.1184E-003
127 Overcast Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 PERIMETER_BOT_ZN_4_DAYLREFPT1 3.0071E-003
128 Overcast Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 PERIMETER_BOT_ZN_4_DAYLREFPT2 3.0328E-003
129 Clear Sky 01/21 PERIMETER_MID_ZN_1_DAYLCTRL PERIMETER_MID_ZN_1 PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW PERIMETER_MID_ZN_1_DAYLREFPT1 0.1095
130 Clear Sky 01/21 PERIMETER_MID_ZN_1_DAYLCTRL PERIMETER_MID_ZN_1 PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW PERIMETER_MID_ZN_1_DAYLREFPT2 6.3135E-002
131 Clear Turbid Sky 01/21 PERIMETER_MID_ZN_1_DAYLCTRL PERIMETER_MID_ZN_1 PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW PERIMETER_MID_ZN_1_DAYLREFPT1 0.1199
132 Clear Turbid Sky 01/21 PERIMETER_MID_ZN_1_DAYLCTRL PERIMETER_MID_ZN_1 PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW PERIMETER_MID_ZN_1_DAYLREFPT2 6.8227E-002
133 Intermediate Sky 01/21 PERIMETER_MID_ZN_1_DAYLCTRL PERIMETER_MID_ZN_1 PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW PERIMETER_MID_ZN_1_DAYLREFPT1 8.5681E-002
134 Intermediate Sky 01/21 PERIMETER_MID_ZN_1_DAYLCTRL PERIMETER_MID_ZN_1 PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW PERIMETER_MID_ZN_1_DAYLREFPT2 4.3320E-002
135 Overcast Sky 01/21 PERIMETER_MID_ZN_1_DAYLCTRL PERIMETER_MID_ZN_1 PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW PERIMETER_MID_ZN_1_DAYLREFPT1 3.8788E-002
136 Overcast Sky 01/21 PERIMETER_MID_ZN_1_DAYLCTRL PERIMETER_MID_ZN_1 PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW PERIMETER_MID_ZN_1_DAYLREFPT2 1.9168E-002
137 Clear Sky 01/21 PERIMETER_MID_ZN_2_DAYLCTRL PERIMETER_MID_ZN_2 PERIMETER_MID_ZN_2_WALL_EAST_WINDOW PERIMETER_MID_ZN_2_DAYLREFPT1 5.7944E-002
138 Clear Sky 01/21 PERIMETER_MID_ZN_2_DAYLCTRL PERIMETER_MID_ZN_2 PERIMETER_MID_ZN_2_WALL_EAST_WINDOW PERIMETER_MID_ZN_2_DAYLREFPT2 3.2907E-002
139 Clear Turbid Sky 01/21 PERIMETER_MID_ZN_2_DAYLCTRL PERIMETER_MID_ZN_2 PERIMETER_MID_ZN_2_WALL_EAST_WINDOW PERIMETER_MID_ZN_2_DAYLREFPT1 5.6194E-002
140 Clear Turbid Sky 01/21 PERIMETER_MID_ZN_2_DAYLCTRL PERIMETER_MID_ZN_2 PERIMETER_MID_ZN_2_WALL_EAST_WINDOW PERIMETER_MID_ZN_2_DAYLREFPT2 3.1160E-002
141 Intermediate Sky 01/21 PERIMETER_MID_ZN_2_DAYLCTRL PERIMETER_MID_ZN_2 PERIMETER_MID_ZN_2_WALL_EAST_WINDOW PERIMETER_MID_ZN_2_DAYLREFPT1 5.4533E-002
142 Intermediate Sky 01/21 PERIMETER_MID_ZN_2_DAYLCTRL PERIMETER_MID_ZN_2 PERIMETER_MID_ZN_2_WALL_EAST_WINDOW PERIMETER_MID_ZN_2_DAYLREFPT2 2.7624E-002
143 Overcast Sky 01/21 PERIMETER_MID_ZN_2_DAYLCTRL PERIMETER_MID_ZN_2 PERIMETER_MID_ZN_2_WALL_EAST_WINDOW PERIMETER_MID_ZN_2_DAYLREFPT1 3.9762E-002
144 Overcast Sky 01/21 PERIMETER_MID_ZN_2_DAYLCTRL PERIMETER_MID_ZN_2 PERIMETER_MID_ZN_2_WALL_EAST_WINDOW PERIMETER_MID_ZN_2_DAYLREFPT2 1.9389E-002
145 Clear Sky 01/21 PERIMETER_MID_ZN_3_DAYLCTRL PERIMETER_MID_ZN_3 PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW PERIMETER_MID_ZN_3_DAYLREFPT1 3.4617E-002
146 Clear Sky 01/21 PERIMETER_MID_ZN_3_DAYLCTRL PERIMETER_MID_ZN_3 PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW PERIMETER_MID_ZN_3_DAYLREFPT2 2.2921E-002
147 Clear Turbid Sky 01/21 PERIMETER_MID_ZN_3_DAYLCTRL PERIMETER_MID_ZN_3 PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW PERIMETER_MID_ZN_3_DAYLREFPT1 2.7441E-002
148 Clear Turbid Sky 01/21 PERIMETER_MID_ZN_3_DAYLCTRL PERIMETER_MID_ZN_3 PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW PERIMETER_MID_ZN_3_DAYLREFPT2 1.8209E-002
149 Intermediate Sky 01/21 PERIMETER_MID_ZN_3_DAYLCTRL PERIMETER_MID_ZN_3 PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW PERIMETER_MID_ZN_3_DAYLREFPT1 2.5264E-002
150 Intermediate Sky 01/21 PERIMETER_MID_ZN_3_DAYLCTRL PERIMETER_MID_ZN_3 PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW PERIMETER_MID_ZN_3_DAYLREFPT2 1.3896E-002
151 Overcast Sky 01/21 PERIMETER_MID_ZN_3_DAYLCTRL PERIMETER_MID_ZN_3 PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW PERIMETER_MID_ZN_3_DAYLREFPT1 3.8788E-002
152 Overcast Sky 01/21 PERIMETER_MID_ZN_3_DAYLCTRL PERIMETER_MID_ZN_3 PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW PERIMETER_MID_ZN_3_DAYLREFPT2 1.9165E-002
153 Clear Sky 01/21 PERIMETER_MID_ZN_4_DAYLCTRL PERIMETER_MID_ZN_4 PERIMETER_MID_ZN_4_WALL_WEST_WINDOW PERIMETER_MID_ZN_4_DAYLREFPT1 4.1681E-002
154 Clear Sky 01/21 PERIMETER_MID_ZN_4_DAYLCTRL PERIMETER_MID_ZN_4 PERIMETER_MID_ZN_4_WALL_WEST_WINDOW PERIMETER_MID_ZN_4_DAYLREFPT2 2.5356E-002
155 Clear Turbid Sky 01/21 PERIMETER_MID_ZN_4_DAYLCTRL PERIMETER_MID_ZN_4 PERIMETER_MID_ZN_4_WALL_WEST_WINDOW PERIMETER_MID_ZN_4_DAYLREFPT1 3.6323E-002
156 Clear Turbid Sky 01/21 PERIMETER_MID_ZN_4_DAYLCTRL PERIMETER_MID_ZN_4 PERIMETER_MID_ZN_4_WALL_WEST_WINDOW PERIMETER_MID_ZN_4_DAYLREFPT2 2.1920E-002
157 Intermediate Sky 01/21 PERIMETER_MID_ZN_4_DAYLCTRL PERIMETER_MID_ZN_4 PERIMETER_MID_ZN_4_WALL_WEST_WINDOW PERIMETER_MID_ZN_4_DAYLREFPT1 3.9926E-002
158 Intermediate Sky 01/21 PERIMETER_MID_ZN_4_DAYLCTRL PERIMETER_MID_ZN_4 PERIMETER_MID_ZN_4_WALL_WEST_WINDOW PERIMETER_MID_ZN_4_DAYLREFPT2 2.0905E-002
159 Overcast Sky 01/21 PERIMETER_MID_ZN_4_DAYLCTRL PERIMETER_MID_ZN_4 PERIMETER_MID_ZN_4_WALL_WEST_WINDOW PERIMETER_MID_ZN_4_DAYLREFPT1 3.9762E-002
160 Overcast Sky 01/21 PERIMETER_MID_ZN_4_DAYLCTRL PERIMETER_MID_ZN_4 PERIMETER_MID_ZN_4_WALL_WEST_WINDOW PERIMETER_MID_ZN_4_DAYLREFPT2 1.9389E-002
161 Clear Sky 01/21 PERIMETER_TOP_ZN_1_DAYLCTRL PERIMETER_TOP_ZN_1 PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW PERIMETER_TOP_ZN_1_DAYLREFPT1 0.1096
162 Clear Sky 01/21 PERIMETER_TOP_ZN_1_DAYLCTRL PERIMETER_TOP_ZN_1 PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW PERIMETER_TOP_ZN_1_DAYLREFPT2 6.3276E-002
163 Clear Turbid Sky 01/21 PERIMETER_TOP_ZN_1_DAYLCTRL PERIMETER_TOP_ZN_1 PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW PERIMETER_TOP_ZN_1_DAYLREFPT1 0.1200
164 Clear Turbid Sky 01/21 PERIMETER_TOP_ZN_1_DAYLCTRL PERIMETER_TOP_ZN_1 PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW PERIMETER_TOP_ZN_1_DAYLREFPT2 6.8389E-002
165 Intermediate Sky 01/21 PERIMETER_TOP_ZN_1_DAYLCTRL PERIMETER_TOP_ZN_1 PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW PERIMETER_TOP_ZN_1_DAYLREFPT1 8.5825E-002
166 Intermediate Sky 01/21 PERIMETER_TOP_ZN_1_DAYLCTRL PERIMETER_TOP_ZN_1 PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW PERIMETER_TOP_ZN_1_DAYLREFPT2 4.3430E-002
167 Overcast Sky 01/21 PERIMETER_TOP_ZN_1_DAYLCTRL PERIMETER_TOP_ZN_1 PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW PERIMETER_TOP_ZN_1_DAYLREFPT1 3.8871E-002
168 Overcast Sky 01/21 PERIMETER_TOP_ZN_1_DAYLCTRL PERIMETER_TOP_ZN_1 PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW PERIMETER_TOP_ZN_1_DAYLREFPT2 1.9210E-002
169 Clear Sky 01/21 PERIMETER_TOP_ZN_2_DAYLCTRL PERIMETER_TOP_ZN_2 PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW PERIMETER_TOP_ZN_2_DAYLREFPT1 5.7999E-002
170 Clear Sky 01/21 PERIMETER_TOP_ZN_2_DAYLCTRL PERIMETER_TOP_ZN_2 PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW PERIMETER_TOP_ZN_2_DAYLREFPT2 3.2961E-002
171 Clear Turbid Sky 01/21 PERIMETER_TOP_ZN_2_DAYLCTRL PERIMETER_TOP_ZN_2 PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW PERIMETER_TOP_ZN_2_DAYLREFPT1 5.6258E-002
172 Clear Turbid Sky 01/21 PERIMETER_TOP_ZN_2_DAYLCTRL PERIMETER_TOP_ZN_2 PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW PERIMETER_TOP_ZN_2_DAYLREFPT2 3.1214E-002
173 Intermediate Sky 01/21 PERIMETER_TOP_ZN_2_DAYLCTRL PERIMETER_TOP_ZN_2 PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW PERIMETER_TOP_ZN_2_DAYLREFPT1 5.4623E-002
174 Intermediate Sky 01/21 PERIMETER_TOP_ZN_2_DAYLCTRL PERIMETER_TOP_ZN_2 PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW PERIMETER_TOP_ZN_2_DAYLREFPT2 2.7684E-002
175 Overcast Sky 01/21 PERIMETER_TOP_ZN_2_DAYLCTRL PERIMETER_TOP_ZN_2 PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW PERIMETER_TOP_ZN_2_DAYLREFPT1 3.9845E-002
176 Overcast Sky 01/21 PERIMETER_TOP_ZN_2_DAYLCTRL PERIMETER_TOP_ZN_2 PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW PERIMETER_TOP_ZN_2_DAYLREFPT2 1.9432E-002
177 Clear Sky 01/21 PERIMETER_TOP_ZN_3_DAYLCTRL PERIMETER_TOP_ZN_3 PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW PERIMETER_TOP_ZN_3_DAYLREFPT1 3.4622E-002
178 Clear Sky 01/21 PERIMETER_TOP_ZN_3_DAYLCTRL PERIMETER_TOP_ZN_3 PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW PERIMETER_TOP_ZN_3_DAYLREFPT2 2.2947E-002
179 Clear Turbid Sky 01/21 PERIMETER_TOP_ZN_3_DAYLCTRL PERIMETER_TOP_ZN_3 PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW PERIMETER_TOP_ZN_3_DAYLREFPT1 2.7448E-002
180 Clear Turbid Sky 01/21 PERIMETER_TOP_ZN_3_DAYLCTRL PERIMETER_TOP_ZN_3 PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW PERIMETER_TOP_ZN_3_DAYLREFPT2 1.8229E-002
181 Intermediate Sky 01/21 PERIMETER_TOP_ZN_3_DAYLCTRL PERIMETER_TOP_ZN_3 PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW PERIMETER_TOP_ZN_3_DAYLREFPT1 2.5305E-002
182 Intermediate Sky 01/21 PERIMETER_TOP_ZN_3_DAYLCTRL PERIMETER_TOP_ZN_3 PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW PERIMETER_TOP_ZN_3_DAYLREFPT2 1.3921E-002
183 Overcast Sky 01/21 PERIMETER_TOP_ZN_3_DAYLCTRL PERIMETER_TOP_ZN_3 PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW PERIMETER_TOP_ZN_3_DAYLREFPT1 3.8871E-002
184 Overcast Sky 01/21 PERIMETER_TOP_ZN_3_DAYLCTRL PERIMETER_TOP_ZN_3 PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW PERIMETER_TOP_ZN_3_DAYLREFPT2 1.9207E-002
185 Clear Sky 01/21 PERIMETER_TOP_ZN_4_DAYLCTRL PERIMETER_TOP_ZN_4 PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW PERIMETER_TOP_ZN_4_DAYLREFPT1 4.1705E-002
186 Clear Sky 01/21 PERIMETER_TOP_ZN_4_DAYLCTRL PERIMETER_TOP_ZN_4 PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW PERIMETER_TOP_ZN_4_DAYLREFPT2 2.5391E-002
187 Clear Turbid Sky 01/21 PERIMETER_TOP_ZN_4_DAYLCTRL PERIMETER_TOP_ZN_4 PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW PERIMETER_TOP_ZN_4_DAYLREFPT1 3.6349E-002
188 Clear Turbid Sky 01/21 PERIMETER_TOP_ZN_4_DAYLCTRL PERIMETER_TOP_ZN_4 PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW PERIMETER_TOP_ZN_4_DAYLREFPT2 2.1951E-002
189 Intermediate Sky 01/21 PERIMETER_TOP_ZN_4_DAYLCTRL PERIMETER_TOP_ZN_4 PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW PERIMETER_TOP_ZN_4_DAYLREFPT1 3.9990E-002
190 Intermediate Sky 01/21 PERIMETER_TOP_ZN_4_DAYLCTRL PERIMETER_TOP_ZN_4 PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW PERIMETER_TOP_ZN_4_DAYLREFPT2 2.0947E-002
191 Overcast Sky 01/21 PERIMETER_TOP_ZN_4_DAYLCTRL PERIMETER_TOP_ZN_4 PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW PERIMETER_TOP_ZN_4_DAYLREFPT1 3.9845E-002
192 Overcast Sky 01/21 PERIMETER_TOP_ZN_4_DAYLCTRL PERIMETER_TOP_ZN_4 PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW PERIMETER_TOP_ZN_4_DAYLREFPT2 1.9432E-002


Zone Sizing Information

Zone Name Load Type Calc Des Load {W} User Des Load {W} Calc Des Air Flow Rate {m3/s} User Des Air Flow Rate {m3/s} Design Day Name Date/Time of Peak Temperature at Peak {C} Humidity Ratio at Peak {kgWater/kgDryAir} Floor Area {m2} # Occupants Calc Outdoor Air Flow Rate {m3/s} Calc DOAS Heat Addition Rate {W}
1 BASEMENT Cooling 81476.79981 81476.79981 6.08611 6.08611 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 27.37000 1.44605E-002 2779.42662 149.60210 1.20016 0.00000
2 BASEMENT Heating 0.00000 0.00000 0.00000 1.20016 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:10:00 -6.30000 2.29779E-003 2779.42662 149.60210 1.20016 0.00000
3 CORE_BOTTOM Cooling 84977.64863 84977.64863 6.34708 6.34708 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 27.37000 1.44605E-002 2496.12046 134.35320 1.07782 0.00000
4 CORE_BOTTOM Heating 0.00000 0.00000 0.00000 1.07782 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 05:50:00 -6.30000 2.29779E-003 2496.12046 134.35320 1.07782 0.00000
5 CORE_MID Cooling 803073.62031 803073.62031 59.96899 59.96899 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 27.37000 1.44605E-002 2496.12046 134.35320 10.77825 0.00000
6 CORE_MID Heating 275723.61336 275723.61336 12.05844 12.05844 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -6.30000 2.29779E-003 2496.12046 134.35320 10.77825 0.00000
7 CORE_TOP Cooling 79160.97142 79160.97142 5.91108 5.91108 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 27.37000 1.44605E-002 2496.12046 134.35320 1.07782 0.00000
8 CORE_TOP Heating 60293.16614 60293.16614 2.65737 2.65737 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -6.30000 2.29779E-003 2496.12046 134.35320 1.07782 0.00000
9 PERIMETER_BOT_ZN_3 Cooling 14184.52619 14184.52619 1.06896 1.06896 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:50:00 34.40000 1.44733E-002 313.41284 16.86939 0.13533 0.00000
10 PERIMETER_BOT_ZN_3 Heating 10461.87834 10461.87834 0.46182 0.46182 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -6.30000 2.29779E-003 313.41284 16.86939 0.13533 0.00000
11 PERIMETER_BOT_ZN_2 Cooling 14680.43792 14680.43792 1.10633 1.10633 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 09:50:00 30.52083 1.44662E-002 201.97515 10.87127 8.72129E-002 0.00000
12 PERIMETER_BOT_ZN_2 Heating 7153.34481 7153.34481 0.31584 0.31584 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -6.30000 2.29779E-003 201.97515 10.87127 8.72129E-002 0.00000
13 PERIMETER_BOT_ZN_1 Cooling 16633.14454 16633.14454 1.25349 1.25349 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 13:40:00 34.24167 1.44730E-002 313.41969 16.86975 0.13533 0.00000
14 PERIMETER_BOT_ZN_1 Heating 11605.04676 11605.04676 0.51247 0.51247 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -6.30000 2.29779E-003 313.41969 16.86975 0.13533 0.00000
15 PERIMETER_BOT_ZN_4 Cooling 18514.73939 18514.73939 1.39528 1.39528 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 17:10:00 32.91167 1.44705E-002 201.97515 10.87127 8.72129E-002 0.00000
16 PERIMETER_BOT_ZN_4 Heating 5582.07505 5582.07505 0.24619 0.24619 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -6.30000 2.29779E-003 201.97515 10.87127 8.72129E-002 0.00000
17 PERIMETER_MID_ZN_3 Cooling 134507.14604 134507.14604 10.13720 10.13720 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 34.40000 1.44733E-002 313.41284 16.86939 1.35332 0.00000
18 PERIMETER_MID_ZN_3 Heating 171564.19834 171564.19834 7.58569 7.58569 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -6.30000 2.29779E-003 313.41284 16.86939 1.35332 0.00000
19 PERIMETER_MID_ZN_2 Cooling 151996.01979 151996.01979 11.45518 11.45518 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 10:00:00 30.79000 1.44667E-002 201.97515 10.87127 0.87213 0.00000
20 PERIMETER_MID_ZN_2 Heating 112279.74863 112279.74863 4.96462 4.96462 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -6.30000 2.29779E-003 201.97515 10.87127 0.87213 0.00000
21 PERIMETER_MID_ZN_1 Cooling 158866.10754 158866.10754 11.97300 11.97300 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 13:50:00 34.32083 1.44731E-002 313.41969 16.86975 1.35335 0.00000
22 PERIMETER_MID_ZN_1 Heating 169162.05030 169162.05030 7.47919 7.47919 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -6.30000 2.29779E-003 313.41969 16.86975 1.35335 0.00000
23 PERIMETER_MID_ZN_4 Cooling 161161.06551 161161.06551 12.14587 12.14587 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 17:20:00 32.75333 1.44703E-002 201.97515 10.87127 0.87213 0.00000
24 PERIMETER_MID_ZN_4 Heating 109094.22645 109094.22645 4.82343 4.82343 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -6.30000 2.29779E-003 201.97515 10.87127 0.87213 0.00000
25 PERIMETER_TOP_ZN_3 Cooling 15153.30497 15153.30497 1.14206 1.14206 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:20:00 34.21000 1.44729E-002 313.41284 16.86939 0.13533 0.00000
26 PERIMETER_TOP_ZN_3 Heating 21499.98515 21499.98515 0.95109 0.95109 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -6.30000 2.29779E-003 313.41284 16.86939 0.13533 0.00000
27 PERIMETER_TOP_ZN_2 Cooling 15453.40460 15453.40460 1.16467 1.16467 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 10:10:00 31.02750 1.44671E-002 201.97515 10.87127 8.72129E-002 0.00000
28 PERIMETER_TOP_ZN_2 Heating 14027.21866 14027.21866 0.62053 0.62053 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -6.30000 2.29779E-003 201.97515 10.87127 8.72129E-002 0.00000
29 PERIMETER_TOP_ZN_1 Cooling 17468.40261 17468.40261 1.31654 1.31654 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:10:00 34.40000 1.44733E-002 313.41969 16.86975 0.13533 0.00000
30 PERIMETER_TOP_ZN_1 Heating 21243.92356 21243.92356 0.93974 0.93974 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -6.30000 2.29779E-003 313.41969 16.86975 0.13533 0.00000
31 PERIMETER_TOP_ZN_4 Cooling 17221.06978 17221.06978 1.29789 1.29789 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 17:20:00 32.75333 1.44703E-002 201.97515 10.87127 8.72129E-002 0.00000
32 PERIMETER_TOP_ZN_4 Heating 13827.72071 13827.72071 0.61169 0.61169 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -6.30000 2.29779E-003 201.97515 10.87127 8.72129E-002 0.00000
33 DATACENTER_BOT_ZN_6 Cooling 8280.15536 8280.15536 0.49216 0.49216 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 19:10:00 30.52083 1.44662E-002 36.20274 1.94861 1.56323E-002 0.00000
34 DATACENTER_BOT_ZN_6 Heating 0.00000 0.00000 0.00000 1.56323E-002 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 05:40:00 -6.30000 2.29779E-003 36.20274 1.94861 1.56323E-002 0.00000
35 DATACENTER_MID_ZN_6 Cooling 78935.51948 78935.51948 4.69180 4.69180 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 19:10:00 30.52083 1.44662E-002 36.20274 1.94861 0.15632 0.00000
36 DATACENTER_MID_ZN_6 Heating 0.00000 0.00000 0.00000 0.15632 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 05:40:00 -6.30000 2.29779E-003 36.20274 1.94861 0.15632 0.00000
37 DATACENTER_TOP_ZN_6 Cooling 8040.96317 8040.96317 0.47794 0.47794 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 19:00:00 30.69500 1.44665E-002 36.20274 1.94861 1.56323E-002 0.00000
38 DATACENTER_TOP_ZN_6 Heating 0.00000 0.00000 0.00000 1.56323E-002 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 05:40:00 -6.30000 2.29779E-003 36.20274 1.94861 1.56323E-002 0.00000
39 DATACENTER_BASEMENT_ZN_6 Cooling 372434.49124 372434.49124 22.13638 22.13638 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 07:00:00 25.75500 1.44575E-002 783.67941 42.18139 0.33839 0.00000
40 DATACENTER_BASEMENT_ZN_6 Heating 0.00000 0.00000 0.00000 0.33839 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 00:50:00 -6.30000 2.29779E-003 783.67941 42.18139 0.33839 0.00000


System Sizing Information

System Name Load Type Peak Load Kind User Design Capacity Calc Des Air Flow Rate [m3/s] User Des Air Flow Rate [m3/s] Design Day Name Date/Time of Peak
1 VAV_BOT WITH REHEAT Cooling Sensible 158173.35 10.07599 10.07599 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 00:00:00
2 VAV_BOT WITH REHEAT Heating Sensible 56601.28 2.61415 2.61415 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00
3 VAV_MID WITH REHEAT Cooling Sensible 1462716.08 94.03603 94.03603 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 00:00:00
4 VAV_MID WITH REHEAT Heating Sensible 561825.29 36.91136 36.91136 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 06:20:00
5 VAV_TOP WITH REHEAT Cooling Sensible 163249.97 10.19790 10.19790 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 00:00:00
6 VAV_TOP WITH REHEAT Heating Sensible 56440.70 5.78042 5.78042 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 05:40:00
7 CAV_BAS Cooling Sensible 84679.67 6.08611 6.08611 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 05:00:00
8 CAV_BAS Heating Sensible 64825.70 1.20016 1.20016 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00
9 AIRLOOP DATACENTER BASEMENT Cooling Sensible 369106.53 22.13657 22.13657 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 05:00:00
10 AIRLOOP DATACENTER BASEMENT Heating Sensible 18278.08 0.33839 0.33839 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00
11 AIRLOOP DATACENTER BOT Cooling Sensible 8217.92 0.49216 0.49216 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 05:00:00
12 AIRLOOP DATACENTER BOT Heating Sensible 844.37 1.56323E-002 1.56323E-002 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00
13 AIRLOOP DATACENTER MID Cooling Sensible 78357.32 4.69180 4.69180 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 05:00:00
14 AIRLOOP DATACENTER MID Heating Sensible 8443.71 0.15632 0.15632 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00
15 AIRLOOP DATACENTER TOP Cooling Sensible 7984.04 0.47794 0.47794 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 05:00:00
16 AIRLOOP DATACENTER TOP Heating Sensible 844.37 1.56323E-002 1.56323E-002 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00


Component Sizing Information

Component Type Component Name Input Field Description Value
1 AirTerminal:SingleDuct:ConstantVolume:NoReheat BASEMENT DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 6.08611
2 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 6.34708
3 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.29967
4 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.30800
5 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 1.95490
6 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.79913
7 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
8 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.27139E-003
9 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.66024E-004
10 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 1.95490
11 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
12 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
13 Coil:Heating:Water CORE_BOTTOM VAV BOX REHEAT COIL Design Size Rated Capacity [W] 18977.52327
14 Coil:Heating:Water CORE_BOTTOM VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.66024E-004
15 Coil:Heating:Water CORE_BOTTOM VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 382.57197
16 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 59.96899
17 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.31717
18 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.32000
19 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 19.19008
20 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.84579
21 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
22 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.20124E-003
23 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 4.04190E-003
24 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 19.19008
25 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
26 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
27 Coil:Heating:Water CORE_MID VAV BOX REHEAT COIL Design Size Rated Capacity [W] 462014.39680
28 Coil:Heating:Water CORE_MID VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 4.04190E-003
29 Coil:Heating:Water CORE_MID VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 10929.40925
30 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 5.91108
31 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.32178
32 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.33200
33 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 1.96248
34 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.85807
35 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
36 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.18405E-003
37 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 7.53153E-004
38 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 2.65737
39 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
40 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
41 Coil:Heating:Water CORE_TOP VAV BOX REHEAT COIL Design Size Rated Capacity [W] 86090.01699
42 Coil:Heating:Water CORE_TOP VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 7.53153E-004
43 Coil:Heating:Water CORE_TOP VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 2272.77242
44 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 1.06896
45 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.22341
46 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.23000
47 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.24586
48 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.59577
49 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
50 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.70536E-003
51 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.30696E-004
52 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.46182
53 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
54 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
55 Coil:Heating:Water PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 14939.36917
56 Coil:Heating:Water PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.30696E-004
57 Coil:Heating:Water PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 394.13330
58 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 1.10633
59 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.13911
60 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.20000
61 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.22127
62 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.37097
63 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
64 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 2.73878E-003
65 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 8.93727E-005
66 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.31584
67 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
68 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
69 Coil:Heating:Water PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 10215.84741
70 Coil:Heating:Water PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 8.93727E-005
71 Coil:Heating:Water PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 269.49956
72 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 1.25349
73 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.19053
74 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.20000
75 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.25070
76 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.50808
77 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
78 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.99970E-003
79 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.45003E-004
80 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.51247
81 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
82 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
83 Coil:Heating:Water PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 16574.75910
84 Coil:Heating:Water PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.45003E-004
85 Coil:Heating:Water PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 437.23781
86 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 1.39528
87 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.11030
88 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.20000
89 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.27906
90 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.30000
91 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
92 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 3.45408E-003
93 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 7.24903E-005
94 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.27906
95 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
96 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
97 Coil:Heating:Water PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 8286.08256
98 Coil:Heating:Water PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 7.24903E-005
99 Coil:Heating:Water PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 210.73941
100 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 10.13720
101 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.23559
102 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.23800
103 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 2.41265
104 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.62824
105 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
106 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.61723E-003
107 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 2.14427E-003
108 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 7.58569
109 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
110 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
111 Coil:Heating:Water PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 245103.78299
112 Coil:Heating:Water PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 2.14427E-003
113 Coil:Heating:Water PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 6462.91470
114 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_2 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 11.45518
115 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_2 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.13435
116 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_2 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.20000
117 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_2 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 2.29104
118 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_2 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.35828
119 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_2 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
120 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_2 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 2.83579E-003
121 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_2 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.40332E-003
122 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 4.96462
123 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
124 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
125 Coil:Heating:Water PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 160408.19580
126 Coil:Heating:Water PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.40332E-003
127 Coil:Heating:Water PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 4229.59316
128 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 11.97300
129 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.19947
130 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.20100
131 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 2.40657
132 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.53192
133 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
134 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.91006E-003
135 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 2.11422E-003
136 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 7.47919
137 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
138 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
139 Coil:Heating:Water PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 241668.01381
140 Coil:Heating:Water PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 2.11422E-003
141 Coil:Heating:Water PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 6372.38706
142 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 12.14587
143 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.12671
144 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.20000
145 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 2.42917
146 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.33790
147 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
148 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 3.00677E-003
149 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.36346E-003
150 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 4.82343
151 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
152 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
153 Coil:Heating:Water PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 155852.34939
154 Coil:Heating:Water PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.36346E-003
155 Coil:Heating:Water PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 4109.53748
156 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 1.14206
157 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.20911
158 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.21600
159 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.24668
160 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.55764
161 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
162 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.82197E-003
163 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 2.68752E-004
164 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.95109
165 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
166 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
167 Coil:Heating:Water PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 30720.04645
168 Coil:Heating:Water PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 2.68752E-004
169 Coil:Heating:Water PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 809.89700
170 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 1.16467
171 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.13214
172 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.20000
173 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.23293
174 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.35239
175 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
176 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 2.88321E-003
177 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.75341E-004
178 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.62053
179 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
180 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
181 Coil:Heating:Water PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 20042.60938
182 Coil:Heating:Water PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.75341E-004
183 Coil:Heating:Water PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 528.39361
184 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 1.31654
185 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.18140
186 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.20000
187 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.26331
188 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.48375
189 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
190 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 2.10028E-003
191 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 2.65549E-004
192 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.93974
193 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
194 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
195 Coil:Heating:Water PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 30353.82930
196 Coil:Heating:Water PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 2.65549E-004
197 Coil:Heating:Water PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 800.24768
198 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 1.29789
199 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.11858
200 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.20000
201 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.25958
202 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.31622
203 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
204 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 3.21299E-003
205 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.72846E-004
206 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.61169
207 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
208 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
209 Coil:Heating:Water PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 19757.33927
210 Coil:Heating:Water PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.72846E-004
211 Coil:Heating:Water PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 520.87525
212 AirTerminal:SingleDuct:ConstantVolume:NoReheat DATACENTER_BOT_ZN_6 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 0.49216
213 AirTerminal:SingleDuct:ConstantVolume:NoReheat DATACENTER_MID_ZN_6 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 4.69180
214 AirTerminal:SingleDuct:ConstantVolume:NoReheat DATACENTER_TOP_ZN_6 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 0.47794
215 AirTerminal:SingleDuct:ConstantVolume:NoReheat DATACENTER_BASEMENT_ZN_6 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 22.13638
216 AirLoopHVAC VAV_BOT WITH REHEAT Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 5.58557
217 AirLoopHVAC VAV_BOT WITH REHEAT Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 2.95178
218 AirLoopHVAC VAV_BOT WITH REHEAT Sum of Air Terminal Maximum Flow Rates [m3/s] 11.17115
219 AirLoopHVAC VAV_BOT WITH REHEAT Adjusted Heating Design Air Flow Rate [m3/s] 2.95178
220 AirLoopHVAC VAV_BOT WITH REHEAT Adjusted Cooling Design Air Flow Rate [m3/s] 10.07599
221 AirLoopHVAC VAV_BOT WITH REHEAT Adjusted Main Design Air Flow Rate [m3/s] 10.07599
222 AirLoopHVAC VAV_BOT WITH REHEAT User Heating Air Flow Ratio [] 0.30000
223 AirLoopHVAC VAV_BOT WITH REHEAT Calculated Heating Air Flow Ratio [] 0.29295
224 AirLoopHVAC VAV_MID WITH REHEAT Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 52.84012
225 AirLoopHVAC VAV_MID WITH REHEAT Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 28.72951
226 AirLoopHVAC VAV_MID WITH REHEAT Sum of Air Terminal Maximum Flow Rates [m3/s] 105.68024
227 AirLoopHVAC VAV_MID WITH REHEAT Adjusted Heating Design Air Flow Rate [m3/s] 36.91136
228 AirLoopHVAC VAV_MID WITH REHEAT Adjusted Cooling Design Air Flow Rate [m3/s] 94.03603
229 AirLoopHVAC VAV_MID WITH REHEAT Adjusted Main Design Air Flow Rate [m3/s] 94.03603
230 AirLoopHVAC VAV_MID WITH REHEAT User Heating Air Flow Ratio [] 0.30000
231 AirLoopHVAC VAV_MID WITH REHEAT Calculated Heating Air Flow Ratio [] 0.39252
232 AirLoopHVAC VAV_TOP WITH REHEAT Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 5.41612
233 AirLoopHVAC VAV_TOP WITH REHEAT Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 2.96498
234 AirLoopHVAC VAV_TOP WITH REHEAT Sum of Air Terminal Maximum Flow Rates [m3/s] 10.83224
235 AirLoopHVAC VAV_TOP WITH REHEAT Adjusted Heating Design Air Flow Rate [m3/s] 5.78042
236 AirLoopHVAC VAV_TOP WITH REHEAT Adjusted Cooling Design Air Flow Rate [m3/s] 10.19790
237 AirLoopHVAC VAV_TOP WITH REHEAT Adjusted Main Design Air Flow Rate [m3/s] 10.19790
238 AirLoopHVAC VAV_TOP WITH REHEAT User Heating Air Flow Ratio [] 0.30000
239 AirLoopHVAC VAV_TOP WITH REHEAT Calculated Heating Air Flow Ratio [] 0.56682
240 AirLoopHVAC CAV_BAS Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 6.08611
241 AirLoopHVAC CAV_BAS Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 6.08611
242 AirLoopHVAC CAV_BAS Sum of Air Terminal Maximum Flow Rates [m3/s] 6.08611
243 AirLoopHVAC CAV_BAS Adjusted Heating Design Air Flow Rate [m3/s] 6.08611
244 AirLoopHVAC CAV_BAS Adjusted Cooling Design Air Flow Rate [m3/s] 6.08611
245 AirLoopHVAC CAV_BAS Adjusted Main Design Air Flow Rate [m3/s] 6.08611
246 AirLoopHVAC CAV_BAS User Heating Air Flow Ratio [] 1.00000
247 AirLoopHVAC CAV_BAS Calculated Heating Air Flow Ratio [] 1.00000
248 AirLoopHVAC AIRLOOP DATACENTER BASEMENT Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 22.13638
249 AirLoopHVAC AIRLOOP DATACENTER BASEMENT Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 22.13638
250 AirLoopHVAC AIRLOOP DATACENTER BASEMENT Sum of Air Terminal Maximum Flow Rates [m3/s] 22.13638
251 AirLoopHVAC AIRLOOP DATACENTER BASEMENT Adjusted Heating Design Air Flow Rate [m3/s] 22.13638
252 AirLoopHVAC AIRLOOP DATACENTER BASEMENT Adjusted Cooling Design Air Flow Rate [m3/s] 22.13657
253 AirLoopHVAC AIRLOOP DATACENTER BASEMENT Adjusted Main Design Air Flow Rate [m3/s] 22.13657
254 AirLoopHVAC AIRLOOP DATACENTER BASEMENT User Heating Air Flow Ratio [] 1.00000
255 AirLoopHVAC AIRLOOP DATACENTER BASEMENT Calculated Heating Air Flow Ratio [] 0.99999
256 AirLoopHVAC AIRLOOP DATACENTER BOT Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 0.49216
257 AirLoopHVAC AIRLOOP DATACENTER BOT Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 0.49216
258 AirLoopHVAC AIRLOOP DATACENTER BOT Sum of Air Terminal Maximum Flow Rates [m3/s] 0.49216
259 AirLoopHVAC AIRLOOP DATACENTER BOT Adjusted Heating Design Air Flow Rate [m3/s] 0.49216
260 AirLoopHVAC AIRLOOP DATACENTER BOT Adjusted Cooling Design Air Flow Rate [m3/s] 0.49216
261 AirLoopHVAC AIRLOOP DATACENTER BOT Adjusted Main Design Air Flow Rate [m3/s] 0.49216
262 AirLoopHVAC AIRLOOP DATACENTER BOT User Heating Air Flow Ratio [] 1.00000
263 AirLoopHVAC AIRLOOP DATACENTER BOT Calculated Heating Air Flow Ratio [] 1.00000
264 AirLoopHVAC AIRLOOP DATACENTER MID Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 4.69180
265 AirLoopHVAC AIRLOOP DATACENTER MID Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 4.69180
266 AirLoopHVAC AIRLOOP DATACENTER MID Sum of Air Terminal Maximum Flow Rates [m3/s] 4.69180
267 AirLoopHVAC AIRLOOP DATACENTER MID Adjusted Heating Design Air Flow Rate [m3/s] 4.69180
268 AirLoopHVAC AIRLOOP DATACENTER MID Adjusted Cooling Design Air Flow Rate [m3/s] 4.69180
269 AirLoopHVAC AIRLOOP DATACENTER MID Adjusted Main Design Air Flow Rate [m3/s] 4.69180
270 AirLoopHVAC AIRLOOP DATACENTER MID User Heating Air Flow Ratio [] 1.00000
271 AirLoopHVAC AIRLOOP DATACENTER MID Calculated Heating Air Flow Ratio [] 1.00000
272 AirLoopHVAC AIRLOOP DATACENTER TOP Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 0.47794
273 AirLoopHVAC AIRLOOP DATACENTER TOP Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 0.47794
274 AirLoopHVAC AIRLOOP DATACENTER TOP Sum of Air Terminal Maximum Flow Rates [m3/s] 0.47794
275 AirLoopHVAC AIRLOOP DATACENTER TOP Adjusted Heating Design Air Flow Rate [m3/s] 0.47794
276 AirLoopHVAC AIRLOOP DATACENTER TOP Adjusted Cooling Design Air Flow Rate [m3/s] 0.47794
277 AirLoopHVAC AIRLOOP DATACENTER TOP Adjusted Main Design Air Flow Rate [m3/s] 0.47794
278 AirLoopHVAC AIRLOOP DATACENTER TOP User Heating Air Flow Ratio [] 1.00000
279 AirLoopHVAC AIRLOOP DATACENTER TOP Calculated Heating Air Flow Ratio [] 1.00000
280 AirLoopHVAC VAV_BOT WITH REHEAT Design Supply Air Flow Rate [m3/s] 10.07599
281 AirLoopHVAC VAV_MID WITH REHEAT Design Supply Air Flow Rate [m3/s] 94.03603
282 AirLoopHVAC VAV_TOP WITH REHEAT Design Supply Air Flow Rate [m3/s] 10.19790
283 AirLoopHVAC CAV_BAS Design Supply Air Flow Rate [m3/s] 6.08611
284 AirLoopHVAC AIRLOOP DATACENTER BASEMENT Design Supply Air Flow Rate [m3/s] 22.13657
285 AirLoopHVAC AIRLOOP DATACENTER BOT Design Supply Air Flow Rate [m3/s] 0.49216
286 AirLoopHVAC AIRLOOP DATACENTER MID Design Supply Air Flow Rate [m3/s] 4.69180
287 AirLoopHVAC AIRLOOP DATACENTER TOP Design Supply Air Flow Rate [m3/s] 0.47794
288 Controller:OutdoorAir VAV_BOT WITH REHEAT_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 10.07599
289 Controller:OutdoorAir VAV_BOT WITH REHEAT_OA_CONTROLLER Minimum Outdoor Air Flow Rate [m3/s] 2.53819
290 HeatExchanger:AirToAir:SensibleAndLatent VAV_BOT WITH REHEAT OA HEAT RECOVERY Design Size Nominal Supply Air Flow Rate [m3/s] 2.53819
291 Coil:Cooling:Water VAV_BOT WITH REHEAT COOLING COIL Design Size Design Inlet Air Temperature [C] 26.70645
292 Coil:Cooling:Water VAV_BOT WITH REHEAT COOLING COIL Design Size Design Inlet Water Temperature [C] 6.67000
293 Coil:Cooling:Water VAV_BOT WITH REHEAT COOLING COIL Design Size Design Outlet Air Temperature [C] 10.99205
294 Coil:Cooling:Water VAV_BOT WITH REHEAT COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 1.03322E-002
295 Coil:Cooling:Water VAV_BOT WITH REHEAT COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 8.50000E-003
296 Coil:Cooling:Water VAV_BOT WITH REHEAT COOLING COIL Design Size Design Coil Load [W] 242286.81281
297 Coil:Cooling:Water VAV_BOT WITH REHEAT COOLING COIL Design Size Design Water Flow Rate [m3/s] 1.03074E-002
298 Coil:Cooling:Water VAV_BOT WITH REHEAT COOLING COIL Design Size Design Air Flow Rate [m3/s] 10.07599
299 Coil:Heating:Water VAV_BOT WITH REHEAT HEATING COIL Design Size Rated Capacity [W] 56839.84829
300 Coil:Heating:Water VAV_BOT WITH REHEAT HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 4.97260E-004
301 Coil:Heating:Water VAV_BOT WITH REHEAT HEATING COIL Design Size U-Factor Times Area Value [W/K] 935.40172
302 Fan:VariableVolume VAV_BOT WITH REHEAT FAN Design Size Maximum Flow Rate [m3/s] 10.07599
303 Controller:WaterCoil VAV_BOT WITH REHEAT_COOLC_CONTROLLER Maximum Actuated Flow [m3/s] 1.03074E-002
304 Controller:WaterCoil VAV_BOT WITH REHEAT_COOLC_CONTROLLER Controller Convergence Tolerance 4.61987E-005
305 Controller:WaterCoil VAV_BOT WITH REHEAT_HEATC_CONTROLLER Maximum Actuated Flow [m3/s] 4.97260E-004
306 Controller:OutdoorAir VAV_MID WITH REHEAT_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 94.03603
307 Controller:OutdoorAir VAV_MID WITH REHEAT_OA_CONTROLLER Minimum Outdoor Air Flow Rate [m3/s] 25.38195
308 HeatExchanger:AirToAir:SensibleAndLatent VAV_MID WITH REHEAT OA HEAT RECOVERY Design Size Nominal Supply Air Flow Rate [m3/s] 25.38195
309 Coil:Cooling:Water VAV_MID WITH REHEAT COOLING COIL Design Size Design Inlet Air Temperature [C] 26.98529
310 Coil:Cooling:Water VAV_MID WITH REHEAT COOLING COIL Design Size Design Inlet Water Temperature [C] 6.67000
311 Coil:Cooling:Water VAV_MID WITH REHEAT COOLING COIL Design Size Design Outlet Air Temperature [C] 10.98312
312 Coil:Cooling:Water VAV_MID WITH REHEAT COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 1.05527E-002
313 Coil:Cooling:Water VAV_MID WITH REHEAT COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 8.50000E-003
314 Coil:Cooling:Water VAV_MID WITH REHEAT COOLING COIL Design Size Design Coil Load [W] 2354776.14956
315 Coil:Cooling:Water VAV_MID WITH REHEAT COOLING COIL Design Size Design Water Flow Rate [m3/s] 0.10018
316 Coil:Cooling:Water VAV_MID WITH REHEAT COOLING COIL Design Size Design Air Flow Rate [m3/s] 94.03603
317 Coil:Heating:Water VAV_MID WITH REHEAT HEATING COIL Design Size Rated Capacity [W] 544940.17353
318 Coil:Heating:Water VAV_MID WITH REHEAT HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 4.76737E-003
319 Coil:Heating:Water VAV_MID WITH REHEAT HEATING COIL Design Size U-Factor Times Area Value [W/K] 8945.37805
320 Fan:VariableVolume VAV_MID WITH REHEAT FAN Design Size Maximum Flow Rate [m3/s] 94.03603
321 Controller:WaterCoil VAV_MID WITH REHEAT_COOLC_CONTROLLER Maximum Actuated Flow [m3/s] 0.10018
322 Controller:WaterCoil VAV_MID WITH REHEAT_COOLC_CONTROLLER Controller Convergence Tolerance 4.75346E-006
323 Controller:WaterCoil VAV_MID WITH REHEAT_HEATC_CONTROLLER Maximum Actuated Flow [m3/s] 4.76737E-003
324 Controller:OutdoorAir VAV_TOP WITH REHEAT_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 10.19790
325 Controller:OutdoorAir VAV_TOP WITH REHEAT_OA_CONTROLLER Minimum Outdoor Air Flow Rate [m3/s] 2.53819
326 HeatExchanger:AirToAir:SensibleAndLatent VAV_TOP WITH REHEAT OA HEAT RECOVERY Design Size Nominal Supply Air Flow Rate [m3/s] 2.53819
327 Coil:Cooling:Water VAV_TOP WITH REHEAT COOLING COIL Design Size Design Inlet Air Temperature [C] 26.60232
328 Coil:Cooling:Water VAV_TOP WITH REHEAT COOLING COIL Design Size Design Inlet Water Temperature [C] 6.67000
329 Coil:Cooling:Water VAV_TOP WITH REHEAT COOLING COIL Design Size Design Outlet Air Temperature [C] 10.99201
330 Coil:Cooling:Water VAV_TOP WITH REHEAT COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 1.03218E-002
331 Coil:Cooling:Water VAV_TOP WITH REHEAT COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 8.50000E-003
332 Coil:Cooling:Water VAV_TOP WITH REHEAT COOLING COIL Design Size Design Coil Load [W] 243642.38479
333 Coil:Cooling:Water VAV_TOP WITH REHEAT COOLING COIL Design Size Design Water Flow Rate [m3/s] 1.03651E-002
334 Coil:Cooling:Water VAV_TOP WITH REHEAT COOLING COIL Design Size Design Air Flow Rate [m3/s] 10.19790
335 Coil:Heating:Water VAV_TOP WITH REHEAT HEATING COIL Design Size Rated Capacity [W] 53637.38768
336 Coil:Heating:Water VAV_TOP WITH REHEAT HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 4.69243E-004
337 Coil:Heating:Water VAV_TOP WITH REHEAT HEATING COIL Design Size U-Factor Times Area Value [W/K] 888.20229
338 Fan:VariableVolume VAV_TOP WITH REHEAT FAN Design Size Maximum Flow Rate [m3/s] 10.19790
339 Controller:WaterCoil VAV_TOP WITH REHEAT_COOLC_CONTROLLER Maximum Actuated Flow [m3/s] 1.03651E-002
340 Controller:WaterCoil VAV_TOP WITH REHEAT_COOLC_CONTROLLER Controller Convergence Tolerance 4.59417E-005
341 Controller:WaterCoil VAV_TOP WITH REHEAT_HEATC_CONTROLLER Maximum Actuated Flow [m3/s] 4.69243E-004
342 Controller:OutdoorAir CAV_BAS_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 6.08611
343 Controller:OutdoorAir CAV_BAS_OA_CONTROLLER Minimum Outdoor Air Flow Rate [m3/s] 1.20016
344 Coil:Cooling:Water CAV_BAS COOLING COIL Design Size Design Inlet Air Temperature [C] 24.78600
345 Coil:Cooling:Water CAV_BAS COOLING COIL Design Size Design Inlet Water Temperature [C] 6.67000
346 Coil:Cooling:Water CAV_BAS COOLING COIL Design Size Design Outlet Air Temperature [C] 11.37296
347 Coil:Cooling:Water CAV_BAS COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 1.00248E-002
348 Coil:Cooling:Water CAV_BAS COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 8.50000E-003
349 Coil:Cooling:Water CAV_BAS COOLING COIL Design Size Design Coil Load [W] 124171.22380
350 Coil:Cooling:Water CAV_BAS COOLING COIL Design Size Design Water Flow Rate [m3/s] 5.28253E-003
351 Coil:Cooling:Water CAV_BAS COOLING COIL Design Size Design Air Flow Rate [m3/s] 6.08611
352 Coil:Heating:Water CAV_BAS HEATING COIL Design Size Rated Capacity [W] 292827.05549
353 Coil:Heating:Water CAV_BAS HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 2.56178E-003
354 Coil:Heating:Water CAV_BAS HEATING COIL Design Size U-Factor Times Area Value [W/K] 6501.96253
355 Fan:ConstantVolume CAV_BAS FAN Design Size Maximum Flow Rate [m3/s] 6.08611
356 Controller:WaterCoil CAV_BAS_COOLC_CONTROLLER Maximum Actuated Flow [m3/s] 5.28253E-003
357 Controller:WaterCoil CAV_BAS_COOLC_CONTROLLER Controller Convergence Tolerance 9.01444E-005
358 Controller:WaterCoil CAV_BAS_HEATC_CONTROLLER Maximum Actuated Flow [m3/s] 2.56178E-003
359 Controller:OutdoorAir AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 22.13657
360 Controller:OutdoorAir AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER Minimum Outdoor Air Flow Rate [m3/s] 0.33839
361 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER BASEMENT COOLING COIL Design Size Rated Air Flow Rate [m3/s] 22.13657
362 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER BASEMENT COOLING COIL Design Size Rated Total Cooling Capacity [W] 438414.06316
363 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER BASEMENT COOLING COIL Design Size Rated Sensible Cooling Capacity [W] 303822.62253
364 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER BASEMENT COOLING COIL Design Size Rated Water Flow Rate [m3/s] 1.07367E-002
365 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP Supply Air Flow Rate [m3/s] 22.13657
366 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP Supply Air Flow Rate During Heating Operation [m3/s] 22.13657
367 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP Supply Air Flow Rate During Cooling Operation [m3/s] 22.13657
368 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] 22.13657
369 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP Nominal Heating Capacity [W] 438414.06316
370 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP Nominal Cooling Capacity [W] 438414.06316
371 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP Supplemental Heating Coil Nominal Capacity [W] 18278.07505
372 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
373 Fan:OnOff AIRLOOP DATACENTER BASEMENT SUPPLY FAN Design Size Maximum Flow Rate [m3/s] 22.13657
374 COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER BASEMENT HEATING COIL Design Size Rated Air Flow Rate [m3/s] 22.13657
375 COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER BASEMENT HEATING COIL Design Size Rated Heating Capacity [W] 438414.06316
376 COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER BASEMENT HEATING COIL Design Size Rated Water Flow Rate [m3/s] 1.07367E-002
377 Coil:Heating:Electric AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL Design Size Nominal Capacity [W] 18278.07505
378 Humidifier:Steam:Electric DATACENTER_BASEMENT_ZN_6 HUMIDIFIER Design Size Nominal Capacity Volume [m3/s] 1.53403E-004
379 Humidifier:Steam:Electric DATACENTER_BASEMENT_ZN_6 HUMIDIFIER User-Specified Nominal Capacity Volume [m3/s] 3.72000E-005
380 Humidifier:Steam:Electric DATACENTER_BASEMENT_ZN_6 HUMIDIFIER Design Size Rated Power [W] 96450.69782
381 Humidifier:Steam:Electric DATACENTER_BASEMENT_ZN_6 HUMIDIFIER User-Specified Rated Power [W] 100000.00000
382 Controller:OutdoorAir AIRLOOP DATACENTER BOT_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 0.49216
383 Controller:OutdoorAir AIRLOOP DATACENTER BOT_OA_CONTROLLER Minimum Outdoor Air Flow Rate [m3/s] 1.56323E-002
384 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER BOT COOLING COIL Design Size Rated Air Flow Rate [m3/s] 0.49216
385 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER BOT COOLING COIL Design Size Rated Total Cooling Capacity [W] 9691.18057
386 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER BOT COOLING COIL Design Size Rated Sensible Cooling Capacity [W] 6727.90539
387 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER BOT COOLING COIL Design Size Rated Water Flow Rate [m3/s] 2.37336E-004
388 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BOT DXAC HEAT PUMP Supply Air Flow Rate [m3/s] 0.49216
389 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BOT DXAC HEAT PUMP Supply Air Flow Rate During Heating Operation [m3/s] 0.49216
390 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BOT DXAC HEAT PUMP Supply Air Flow Rate During Cooling Operation [m3/s] 0.49216
391 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BOT DXAC HEAT PUMP Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] 0.49216
392 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BOT DXAC HEAT PUMP Nominal Heating Capacity [W] 9691.18057
393 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BOT DXAC HEAT PUMP Nominal Cooling Capacity [W] 9691.18057
394 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BOT DXAC HEAT PUMP Supplemental Heating Coil Nominal Capacity [W] 844.37135
395 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BOT DXAC HEAT PUMP Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
396 Fan:OnOff AIRLOOP DATACENTER BOT SUPPLY FAN Design Size Maximum Flow Rate [m3/s] 0.49216
397 COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER BOT HEATING COIL Design Size Rated Air Flow Rate [m3/s] 0.49216
398 COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER BOT HEATING COIL Design Size Rated Heating Capacity [W] 9691.18057
399 COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER BOT HEATING COIL Design Size Rated Water Flow Rate [m3/s] 2.37336E-004
400 Coil:Heating:Electric AIRLOOP DATACENTER BOT_SUPPHEATCOIL Design Size Nominal Capacity [W] 844.37135
401 Controller:OutdoorAir AIRLOOP DATACENTER MID_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 4.69180
402 Controller:OutdoorAir AIRLOOP DATACENTER MID_OA_CONTROLLER Minimum Outdoor Air Flow Rate [m3/s] 0.15632
403 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER MID COOLING COIL Design Size Rated Air Flow Rate [m3/s] 4.69180
404 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER MID COOLING COIL Design Size Rated Total Cooling Capacity [W] 92549.83409
405 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER MID COOLING COIL Design Size Rated Sensible Cooling Capacity [W] 64188.78238
406 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER MID COOLING COIL Design Size Rated Water Flow Rate [m3/s] 2.26654E-003
407 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER MID DXAC HEAT PUMP Supply Air Flow Rate [m3/s] 4.69180
408 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER MID DXAC HEAT PUMP Supply Air Flow Rate During Heating Operation [m3/s] 4.69180
409 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER MID DXAC HEAT PUMP Supply Air Flow Rate During Cooling Operation [m3/s] 4.69180
410 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER MID DXAC HEAT PUMP Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] 4.69180
411 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER MID DXAC HEAT PUMP Nominal Heating Capacity [W] 92549.83409
412 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER MID DXAC HEAT PUMP Nominal Cooling Capacity [W] 92549.83409
413 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER MID DXAC HEAT PUMP Supplemental Heating Coil Nominal Capacity [W] 8443.71345
414 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER MID DXAC HEAT PUMP Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
415 Fan:OnOff AIRLOOP DATACENTER MID SUPPLY FAN Design Size Maximum Flow Rate [m3/s] 4.69180
416 COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER MID HEATING COIL Design Size Rated Air Flow Rate [m3/s] 4.69180
417 COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER MID HEATING COIL Design Size Rated Heating Capacity [W] 92549.83409
418 COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER MID HEATING COIL Design Size Rated Water Flow Rate [m3/s] 2.26654E-003
419 Coil:Heating:Electric AIRLOOP DATACENTER MID_SUPPHEATCOIL Design Size Nominal Capacity [W] 8443.71345
420 Controller:OutdoorAir AIRLOOP DATACENTER TOP_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 0.47794
421 Controller:OutdoorAir AIRLOOP DATACENTER TOP_OA_CONTROLLER Minimum Outdoor Air Flow Rate [m3/s] 1.56323E-002
422 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER TOP COOLING COIL Design Size Rated Air Flow Rate [m3/s] 0.47794
423 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER TOP COOLING COIL Design Size Rated Total Cooling Capacity [W] 9422.96064
424 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER TOP COOLING COIL Design Size Rated Sensible Cooling Capacity [W] 6537.25476
425 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER TOP COOLING COIL Design Size Rated Water Flow Rate [m3/s] 2.30768E-004
426 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER TOP DXAC HEAT PUMP Supply Air Flow Rate [m3/s] 0.47794
427 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER TOP DXAC HEAT PUMP Supply Air Flow Rate During Heating Operation [m3/s] 0.47794
428 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER TOP DXAC HEAT PUMP Supply Air Flow Rate During Cooling Operation [m3/s] 0.47794
429 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER TOP DXAC HEAT PUMP Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] 0.47794
430 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER TOP DXAC HEAT PUMP Nominal Heating Capacity [W] 9422.96064
431 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER TOP DXAC HEAT PUMP Nominal Cooling Capacity [W] 9422.96064
432 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER TOP DXAC HEAT PUMP Supplemental Heating Coil Nominal Capacity [W] 844.37135
433 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER TOP DXAC HEAT PUMP Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
434 Fan:OnOff AIRLOOP DATACENTER TOP SUPPLY FAN Design Size Maximum Flow Rate [m3/s] 0.47794
435 COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER TOP HEATING COIL Design Size Rated Air Flow Rate [m3/s] 0.47794
436 COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER TOP HEATING COIL Design Size Rated Heating Capacity [W] 9422.96064
437 COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER TOP HEATING COIL Design Size Rated Water Flow Rate [m3/s] 2.30768E-004
438 Coil:Heating:Electric AIRLOOP DATACENTER TOP_SUPPHEATCOIL Design Size Nominal Capacity [W] 844.37135
439 Pump:VariableSpeed COOLSYS1 PUMP SECONDARY Design Flow Rate [m3/s] 0.12613
440 Pump:VariableSpeed COOLSYS1 PUMP SECONDARY Design Power Consumption [W] 20593.61625
441 PlantLoop COOLSYS1_DEMAND Maximum Loop Flow Rate [m3/s] 0.12613
442 PlantLoop COOLSYS1_DEMAND Plant Loop Volume [m3] 15.13592
443 HeatExchanger:FluidToFluid BYPASS HEAT EXCHANGER Loop Supply Side Design Fluid Flow Rate [m3/s] 0.12613
444 HeatExchanger:FluidToFluid BYPASS HEAT EXCHANGER Loop Demand Side Design Fluid Flow Rate [m3/s] 0.12613
445 HeatExchanger:FluidToFluid BYPASS HEAT EXCHANGER Heat Exchanger U-Factor Times Area Value [W/C] 529442.24481
446 HeatExchanger:FluidToFluid BYPASS HEAT EXCHANGER Loop-to-loop Temperature Difference Used to Size Heat Exchanger U-Factor Times Area Value [C] 5.60000
447 PlantLoop HEATSYS1 Maximum Loop Flow Rate [m3/s] 2.16021E-002
448 PlantLoop HEATSYS1 Plant Loop Volume [m3] 2.59225
449 Pump:VariableSpeed HEATSYS1 PUMP Design Flow Rate [m3/s] 2.16021E-002
450 Pump:VariableSpeed HEATSYS1 PUMP Design Power Consumption [W] 6505.59308
451 Pump:VariableSpeed HEATSYS1 PUMP Design Minimum Flow Rate [m3/s] 0.00000
452 Boiler:HotWater HEATSYS1 BOILER Design Size Nominal Capacity [W] 2469248.62669
453 Boiler:HotWater HEATSYS1 BOILER User-Specified Nominal Capacity [W] 2469248.63000
454 Boiler:HotWater HEATSYS1 BOILER Design Size Design Water Flow Rate [m3/s] 2.16021E-002
455 PlantLoop COOLSYS1_SUPPLY Maximum Loop Flow Rate [m3/s] 0.12613
456 PlantLoop COOLSYS1_SUPPLY Plant Loop Volume [m3] 15.13592
457 Pump:ConstantSpeed COOLSYS1 CHILLER1 PUMP Design Flow Rate [m3/s] 6.30664E-002
458 Pump:ConstantSpeed COOLSYS1 CHILLER1 PUMP Design Power Consumption [W] 7128.82751
459 Pump:ConstantSpeed COOLSYS1 CHILLER2 PUMP Design Flow Rate [m3/s] 6.30664E-002
460 Pump:ConstantSpeed COOLSYS1 CHILLER2 PUMP Design Power Consumption [W] 7128.82751
461 Chiller:Electric:ReformulatedEIR COOLSYS1 CHILLER1 Design Size Reference Chilled Water Flow Rate [m3/s] 0.12613
462 Chiller:Electric:ReformulatedEIR COOLSYS1 CHILLER1 User-Specified Reference Chilled Water Flow Rate [m3/s] 6.36650E-002
463 Chiller:Electric:ReformulatedEIR COOLSYS1 CHILLER1 Design Size Reference Capacity [W] 1500186.25070
464 Chiller:Electric:ReformulatedEIR COOLSYS1 CHILLER1 User-Specified Reference Capacity [W] 1507316.17000
465 Chiller:Electric:ReformulatedEIR COOLSYS1 CHILLER1 Design Size Reference Condenser Water Flow Rate [m3/s] 7.45915E-002
466 Chiller:Electric:ReformulatedEIR COOLSYS1 CHILLER2 Design Size Reference Chilled Water Flow Rate [m3/s] 0.12613
467 Chiller:Electric:ReformulatedEIR COOLSYS1 CHILLER2 User-Specified Reference Chilled Water Flow Rate [m3/s] 6.36650E-002
468 Chiller:Electric:ReformulatedEIR COOLSYS1 CHILLER2 Design Size Reference Capacity [W] 1500186.25070
469 Chiller:Electric:ReformulatedEIR COOLSYS1 CHILLER2 User-Specified Reference Capacity [W] 1507316.17000
470 Chiller:Electric:ReformulatedEIR COOLSYS1 CHILLER2 Design Size Reference Condenser Water Flow Rate [m3/s] 7.45915E-002
471 PlantLoop SINGLE WATER PLANT LOOP Maximum Loop Flow Rate [m3/s] 1.34714E-002
472 PlantLoop SINGLE WATER PLANT LOOP Plant Loop Volume [m3] 1.61657
473 Pump:ConstantSpeed PLANT CIRC PUMP Design Flow Rate [m3/s] 1.34714E-002
474 Pump:ConstantSpeed PLANT CIRC PUMP Design Power Consumption [W] 3435.87449
475 FluidCooler:TwoSpeed CENTRAL TOWER Design Water Flow Rate [m3/s] 1.34714E-002
476 FluidCooler:TwoSpeed CENTRAL TOWER Air Flow Rate at High Fan Speed [m3/s] 139666.46671
477 FluidCooler:TwoSpeed CENTRAL TOWER Fluid cooler UA value at high fan speed based on nominal capacity input [W/K] 58584.36926
478 FluidCooler:TwoSpeed CENTRAL TOWER Air Flow Rate at Low Fan Speed [m3/s] 69833.23335
479 FluidCooler:TwoSpeed CENTRAL TOWER Fan Power at Low Fan Speed [W] 7879.72339
480 FluidCooler:TwoSpeed CENTRAL TOWER U-factor Times Area Value at Low Fan Speed [W/C] 21346.17500
481 Boiler:HotWater CENTRAL BOILER Design Size Nominal Capacity [W] 554905.19047
482 Boiler:HotWater CENTRAL BOILER User-Specified Nominal Capacity [W] 543970.57000
483 Boiler:HotWater CENTRAL BOILER Design Size Design Water Flow Rate [m3/s] 1.34714E-002
484 PlantLoop SWHSYS1 Maximum Loop Flow Rate [m3/s] 4.40000E-004
485 PlantLoop SWHSYS1 Plant Loop Volume [m3] 5.28000E-002
486 Pump:ConstantSpeed SWHSYS1 PUMP Design Flow Rate [m3/s] 4.40000E-004
487 Pump:ConstantSpeed SWHSYS1 PUMP Design Power Consumption [W] 56.20530
488 WaterHeater:Mixed SWHSYS1 WATER HEATER Use Side Design Flow Rate [m3/s] 4.40000E-004
489 CondenserLoop TOWERWATERSYS Maximum Loop Flow Rate [m3/s] 0.14918
490 CondenserLoop TOWERWATERSYS Condenser Loop Volume [m3] 17.90196
491 HeaderedPumps:VariableSpeed TOWERWATERSYS PUMP Design Flow Rate [m3/s] 0.14918
492 HeaderedPumps:VariableSpeed TOWERWATERSYS PUMP Design Power Consumption [W] 36934.40557
493 CoolingTower:VariableSpeed TOWERWATERSYS COOLTOWER 1 Design Air Flow Rate [m3/s] 59.48143
494 CoolingTower:VariableSpeed TOWERWATERSYS COOLTOWER 1 Nominal Capacity [W] 1788404.52389
495 CoolingTower:VariableSpeed TOWERWATERSYS COOLTOWER 1 Air Flow Rate in free convection regime [m3/s] 11.89629
496 CoolingTower:VariableSpeed TOWERWATERSYS COOLTOWER 1 Tower capacity in free convection regime at design conditions [W] 223550.56549
497 CoolingTower:VariableSpeed TOWERWATERSYS COOLTOWER 2 Design Air Flow Rate [m3/s] 59.48143
498 CoolingTower:VariableSpeed TOWERWATERSYS COOLTOWER 2 Nominal Capacity [W] 1788404.52389
499 CoolingTower:VariableSpeed TOWERWATERSYS COOLTOWER 2 Air Flow Rate in free convection regime [m3/s] 11.89629
500 CoolingTower:VariableSpeed TOWERWATERSYS COOLTOWER 2 Tower capacity in free convection regime at design conditions [W] 223550.56549
501 PlantEquipmentOperation:ComponentSetPoint WSHPPLANT OPERATION SCHEME Design Water Flow Rate [m3/s] Equipment # 47 7.74775E-002
502 PlantEquipmentOperation:ComponentSetPoint WSHPPLANT OPERATION SCHEME Design Water Flow Rate [m3/s] Equipment # 47 7.74775E-002


Water Heating Coil Capacity Information

Component Type Name Nominal Total Capacity {W}
1 Coil:Heating:Water CORE_BOTTOM VAV BOX REHEAT COIL 17994.89
2 Coil:Heating:Water CORE_MID VAV BOX REHEAT COIL 437729.20
3 Coil:Heating:Water CORE_TOP VAV BOX REHEAT COIL 81585.54
4 Coil:Heating:Water PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL 14155.92
5 Coil:Heating:Water PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL 9680.00
6 Coil:Heating:Water PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL 15705.28
7 Coil:Heating:Water PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL 7847.78
8 Coil:Heating:Water PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL 232226.85
9 Coil:Heating:Water PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL 151980.47
10 Coil:Heating:Water PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL 228972.03
11 Coil:Heating:Water PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL 147664.46
12 Coil:Heating:Water PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL 29105.23
13 Coil:Heating:Water PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL 18989.02
14 Coil:Heating:Water PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL 28758.30
15 Coil:Heating:Water PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL 18718.76
16 Coil:Heating:Water VAV_BOT WITH REHEAT HEATING COIL 43740.55
17 Coil:Heating:Water VAV_MID WITH REHEAT HEATING COIL 417202.15
18 Coil:Heating:Water VAV_TOP WITH REHEAT HEATING COIL 41806.40
19 Coil:Heating:Water CAV_BAS HEATING COIL 231340.80


Water Cooling Coil Capacity Information

Component Type Name Nominal Total Capacity {W} Nominal Sensible Capacity {W} Nominal Latent Capacity {W} Nominal Sensible Heat Ratio Nominal Coil UA Value {W/C} Nominal Coil Surface Area {m2}
1 Coil:Cooling:Water VAV_BOT WITH REHEAT COOLING COIL 266205.00 177631.86 88573.14 0.67 28251.46 286.54
2 Coil:Cooling:Water VAV_MID WITH REHEAT COOLING COIL 2524490.77 1676090.29 848400.47 0.66 268406.63 2722.33
3 Coil:Cooling:Water VAV_TOP WITH REHEAT COOLING COIL 268814.03 179507.15 89306.88 0.67 28536.96 289.44
4 Coil:Cooling:Water CAV_BAS COOLING COIL 149077.94 101882.01 47195.93 0.68 15614.12 158.37


Chiller Standard Rating Information

Component Type Component Name IPLV in SI Units {W/W} IPLV in IP Units {Btu/W-h}
1 Chiller:Electric:ReformulatedEIR COOLSYS1 CHILLER1 6.84 23.33
2 Chiller:Electric:ReformulatedEIR COOLSYS1 CHILLER2 6.84 23.33


Zone Surfaces

Zone Name # Surfaces
1 BASEMENT 10
2 CORE_BOTTOM 8
3 CORE_MID 7
4 CORE_TOP 7
5 PERIMETER_BOT_ZN_3 18
6 PERIMETER_BOT_ZN_2 12
7 PERIMETER_BOT_ZN_1 18
8 PERIMETER_BOT_ZN_4 12
9 PERIMETER_MID_ZN_3 9
10 PERIMETER_MID_ZN_2 8
11 PERIMETER_MID_ZN_1 9
12 PERIMETER_MID_ZN_4 8
13 PERIMETER_TOP_ZN_3 9
14 PERIMETER_TOP_ZN_2 8
15 PERIMETER_TOP_ZN_1 9
16 PERIMETER_TOP_ZN_4 8
17 GROUNDFLOOR_PLENUM 11
18 MIDFLOOR_PLENUM 11
19 TOPFLOOR_PLENUM 11
20 DATACENTER_BOT_ZN_6 6
21 DATACENTER_MID_ZN_6 6
22 DATACENTER_TOP_ZN_6 6
23 DATACENTER_BASEMENT_ZN_6 10


HeatTransfer Surface

Surface Name Surface Class Base Surface Heat Transfer Algorithm Construction Nominal U (w/o film coefs) {W/m2-K} Nominal U (with film coefs) {W/m2-K} Solar Diffusing Area (Net) {m2} Area (Gross) {m2} Area (Sunlit Calc) {m2} Azimuth {deg} Tilt {deg} ~Width {m} ~Height {m} Reveal {m} ExtBoundCondition ExtConvCoeffCalc IntConvCoeffCalc SunExposure WindExposure ViewFactorToGround ViewFactorToSky ViewFactorToGround-IR ViewFactorToSky-IR #Sides
1 BASEMENT_WALL_EAST Wall   CTF - ConductionTransferFunction BASEMENT_WALL_EAST_CFACTOR 0.940 0.824   118.87 118.87 118.87 90.00 90.00 48.74 2.44 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
2 BASEMENT_WALL_SOUTH Wall   CTF - ConductionTransferFunction BASEMENT_WALL_SOUTH_CFACTOR 0.940 0.824   139.09 139.09 139.09 180.00 90.00 57.03 2.44 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
3 BASEMENT_WALL_NORTH Wall   CTF - ConductionTransferFunction BASEMENT_WALL_NORTH_CFACTOR 0.940 0.824   139.09 139.09 139.09 0.00 90.00 57.03 2.44 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
4 BASEMENT_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   118.87 118.87 118.87 270.00 90.00 48.74 2.44 0.00 DATACENTER_BASEMENT_ZN_6_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
5 BASEMENT_FLOOR Floor   CTF - ConductionTransferFunction EXT_SLAB_8IN_WITH_CARPET 3.285 1.827   2779.43 2779.43 2779.43 0.00 180.00 57.03 48.74 0.00 BASEMENT_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.00 1.00 0.00 4
6 PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   201.98 201.98 201.98 225.00 0.00 6.47 39.59 0.00 PERIMETER_BOT_ZN_2_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
7 PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   250.34 250.34 250.34 180.00 0.00 57.03 4.57 0.00 PERIMETER_BOT_ZN_1_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
8 CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   2076.77 2076.77 2076.77 180.00 0.00 52.45 39.59 0.00 CORE_BOT_ZN_5_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
9 PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   250.34 250.34 250.34 180.00 0.00 52.45 4.57 0.00 PERIMETER_BOT_ZN_3_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
10 BASEMENT_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   7126.21 7126.21 7126.21 0.00 90.00 7126.21 1.00 0.00 BASEMENT_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
11 CORE_BOT_ZN_5_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   173.00 173.00 173.00 180.00 90.00 63.05 2.74 0.00 CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
12 CORE_BOT_ZN_5_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 270.00 90.00 39.59 2.74 0.00 DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
13 CORE_BOT_ZN_5_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   173.00 173.00 173.00 0.00 90.00 63.05 2.74 0.00 CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
14 CORE_BOT_ZN_5_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 90.00 90.00 39.59 2.74 0.00 CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
15 DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   419.30 419.30 419.30 0.00 180.00 10.59 39.59 0.00 DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.00 1.00 0.00 4
16 CORE_BOT_ZN_5_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   2076.82 2076.82 2076.82 0.00 180.00 52.46 39.59 0.00 CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.00 1.00 0.00 4
17 CORE_BOT_ZN_5_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   2496.12 2496.12 2496.12 180.00 0.00 63.05 39.59 0.00 iz-CORE_BOT_ZN_5_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
18 CORE_BOTTOM_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   5064.65 5064.65 5064.65 0.00 90.00 5064.65 1.00 0.00 CORE_BOTTOM_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
19 CORE_MID_ZN_5_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   173.00 173.00 173.00 180.00 90.00 63.05 2.74 0.00 CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
20 CORE_MID_ZN_5_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 270.00 90.00 39.59 2.74 0.00 DATACENTER_MID_ZN_6_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
21 CORE_MID_ZN_5_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   173.00 173.00 173.00 0.00 90.00 63.05 2.74 0.00 CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
22 CORE_MID_ZN_5_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 90.00 90.00 39.59 2.74 0.00 CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
23 CORE_MID_ZN_5_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   2496.12 2496.12 2496.12 0.00 180.00 63.05 39.59 0.00 CORE_MID_ZN_5_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
24 CORE_MID_ZN_5_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   2496.12 2496.12 2496.12 180.00 0.00 63.05 39.59 0.00 iz-CORE_MID_ZN_5_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
25 CORE_MID_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   5064.65 5064.65 5064.65 0.00 90.00 5064.65 1.00 0.00 CORE_MID_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
26 CORE_TOP_ZN_5_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   173.00 173.00 173.00 180.00 90.00 63.05 2.74 0.00 CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
27 CORE_TOP_ZN_5_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 270.00 90.00 39.59 2.74 0.00 DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
28 CORE_TOP_ZN_5_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   173.00 173.00 173.00 0.00 90.00 63.05 2.74 0.00 CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
29 CORE_TOP_ZN_5_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 90.00 90.00 39.59 2.74 0.00 CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
30 CORE_TOP_ZN_5_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   2496.12 2496.12 2496.12 0.00 180.00 63.05 39.59 0.00 CORE_TOP_ZN_5_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
31 CORE_TOP_ZN_5_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   2496.12 2496.12 2496.12 180.00 0.00 63.05 39.59 0.00 iz-CORE_TOP_ZN_5_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
32 CORE_TOP_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   5064.65 5064.65 5064.65 0.00 90.00 5064.65 1.00 0.00 CORE_TOP_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
33 PERIMETER_BOT_ZN_3_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 1.223 1.034   76.91 200.61 76.91 0.00 90.00 73.11 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
34 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 Window PERIMETER_BOT_ZN_3_WALL_NORTH Window5 Detailed Fenestration WINDOW_U_0.498_SHGC_NORTH_0.25 N/A 2.831 No 23.18 23.18 23.18 0.00 90.00 13.65 1.70 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
35 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 Window PERIMETER_BOT_ZN_3_WALL_NORTH Window5 Detailed Fenestration WINDOW_U_0.498_SHGC_NORTH_0.25 N/A 2.831 No 23.18 23.18 23.18 0.00 90.00 13.65 1.70 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
36 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 Window PERIMETER_BOT_ZN_3_WALL_NORTH Window5 Detailed Fenestration WINDOW_U_0.498_SHGC_NORTH_0.25 N/A 2.831 No 23.18 23.18 23.18 0.00 90.00 13.65 1.70 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
37 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 Window PERIMETER_BOT_ZN_3_WALL_NORTH Window5 Detailed Fenestration WINDOW_U_0.498_SHGC_NORTH_0.25 N/A 2.831 No 23.18 23.18 23.18 0.00 90.00 13.65 1.70 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
38 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 Window PERIMETER_BOT_ZN_3_WALL_NORTH Window5 Detailed Fenestration WINDOW_U_0.498_SHGC_NORTH_0.25 N/A 2.831 No 23.18 23.18 23.18 0.00 90.00 13.65 1.70 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
39 PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 Door PERIMETER_BOT_ZN_3_WALL_NORTH CTF - ConductionTransferFunction SWINGING DOOR_CON 3.975 3.975   1.95 1.95 1.95 0.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
40 PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 Door PERIMETER_BOT_ZN_3_WALL_NORTH CTF - ConductionTransferFunction SWINGING DOOR_CON 3.975 3.975   1.95 1.95 1.95 0.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
41 PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 Door PERIMETER_BOT_ZN_3_WALL_NORTH CTF - ConductionTransferFunction SWINGING DOOR_CON 3.975 3.975   1.95 1.95 1.95 0.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
42 PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 Door PERIMETER_BOT_ZN_3_WALL_NORTH CTF - ConductionTransferFunction SWINGING DOOR_CON 3.975 3.975   1.95 1.95 1.95 0.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
43 PERIMETER_BOT_ZN_3_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 225.00 90.00 6.47 2.74 0.00 PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
44 CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   173.00 173.00 173.00 180.00 90.00 63.05 2.74 0.00 CORE_BOT_ZN_5_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
45 PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 135.00 90.00 6.47 2.74 0.00 PERIMETER_BOT_ZN_2_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
46 DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   2.51 2.51 2.51 180.00 90.00 0.91 2.74 0.00 DATACENTER_BOT_ZN_6_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
47 PERIMETER_BOT_ZN_3_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   250.34 250.34 250.34 0.00 180.00 52.46 6.47 0.00 PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
48 DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   63.07 63.07 63.07 0.00 180.00 11.51 4.57 0.00 DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.00 1.00 0.00 4
49 PERIMETER_BOT_ZN_3_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   313.41 313.41 313.41 180.00 0.00 63.96 6.47 0.00 iz-PERIMETER_BOT_ZN_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
50 PERIMETER_BOT_ZN_3_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   626.83 626.83 626.83 0.00 90.00 626.83 1.00 0.00 PERIMETER_BOT_ZN_3_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
51 PERIMETER_BOT_ZN_2_WALL_EAST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 1.223 1.034   52.57 133.74 52.57 90.00 90.00 48.74 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
52 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 Window PERIMETER_BOT_ZN_2_WALL_EAST Window5 Detailed Fenestration WINDOW_U_0.498_SHGC_EAST_0.25 N/A 2.831 No 25.75 25.75 25.75 90.00 90.00 15.43 1.67 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
53 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 Window PERIMETER_BOT_ZN_2_WALL_EAST Window5 Detailed Fenestration WINDOW_U_0.498_SHGC_EAST_0.25 N/A 2.831 No 25.75 25.75 25.75 90.00 90.00 15.43 1.67 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
54 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 Window PERIMETER_BOT_ZN_2_WALL_EAST Window5 Detailed Fenestration WINDOW_U_0.498_SHGC_EAST_0.25 N/A 2.831 No 25.75 25.75 25.75 90.00 90.00 15.43 1.67 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
55 PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 Door PERIMETER_BOT_ZN_2_WALL_EAST CTF - ConductionTransferFunction SWINGING DOOR_CON 3.975 3.975   1.95 1.95 1.95 90.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
56 PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 Door PERIMETER_BOT_ZN_2_WALL_EAST CTF - ConductionTransferFunction SWINGING DOOR_CON 3.975 3.975   1.95 1.95 1.95 90.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
57 PERIMETER_BOT_ZN_2_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 315.00 90.00 6.47 2.74 0.00 PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
58 CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 270.00 90.00 39.59 2.74 0.00 CORE_BOT_ZN_5_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
59 PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 225.00 90.00 6.47 2.74 0.00 PERIMETER_BOT_ZN_1_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
60 PERIMETER_BOT_ZN_2_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   201.98 201.98 201.98 45.00 180.00 6.47 48.74 0.00 PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
61 PERIMETER_BOT_ZN_2_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   201.98 201.98 201.98 225.00 0.00 6.47 39.59 0.00 iz-PERIMETER_BOT_ZN_2_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
62 PERIMETER_BOT_ZN_2_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   403.95 403.95 403.95 0.00 90.00 403.95 1.00 0.00 PERIMETER_BOT_ZN_2_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
63 PERIMETER_BOT_ZN_1_WALL_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 1.223 1.034   76.91 200.61 76.91 180.00 90.00 73.11 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
64 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 Window PERIMETER_BOT_ZN_1_WALL_SOUTH Window5 Detailed Fenestration WINDOW_U_0.498_SHGC_SOUTH_0.25 N/A 2.831 No 23.18 23.18 23.18 180.00 90.00 13.65 1.70 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
65 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 Window PERIMETER_BOT_ZN_1_WALL_SOUTH Window5 Detailed Fenestration WINDOW_U_0.498_SHGC_SOUTH_0.25 N/A 2.831 No 23.18 23.18 23.18 180.00 90.00 13.65 1.70 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
66 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 Window PERIMETER_BOT_ZN_1_WALL_SOUTH Window5 Detailed Fenestration WINDOW_U_0.498_SHGC_SOUTH_0.25 N/A 2.831 No 23.18 23.18 23.18 180.00 90.00 13.65 1.70 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
67 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 Window PERIMETER_BOT_ZN_1_WALL_SOUTH Window5 Detailed Fenestration WINDOW_U_0.498_SHGC_SOUTH_0.25 N/A 2.831 No 23.18 23.18 23.18 180.00 90.00 13.65 1.70 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
68 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 Window PERIMETER_BOT_ZN_1_WALL_SOUTH Window5 Detailed Fenestration WINDOW_U_0.498_SHGC_SOUTH_0.25 N/A 2.831 No 23.18 23.18 23.18 180.00 90.00 13.65 1.70 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
69 PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 Door PERIMETER_BOT_ZN_1_WALL_SOUTH CTF - ConductionTransferFunction SWINGING DOOR_CON 3.975 3.975   1.95 1.95 1.95 180.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
70 PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 Door PERIMETER_BOT_ZN_1_WALL_SOUTH CTF - ConductionTransferFunction SWINGING DOOR_CON 3.975 3.975   1.95 1.95 1.95 180.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
71 PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 Door PERIMETER_BOT_ZN_1_WALL_SOUTH CTF - ConductionTransferFunction SWINGING DOOR_CON 3.975 3.975   1.95 1.95 1.95 180.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
72 PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 Door PERIMETER_BOT_ZN_1_WALL_SOUTH CTF - ConductionTransferFunction SWINGING DOOR_CON 3.975 3.975   1.95 1.95 1.95 180.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
73 PERIMETER_BOT_ZN_1_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 45.00 90.00 6.47 2.74 0.00 PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
74 DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   2.51 2.51 2.51 0.00 90.00 0.91 2.74 0.00 DATACENTER_BOT_ZN_6_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
75 PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 315.00 90.00 6.47 2.74 0.00 PERIMETER_BOT_ZN_4_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
76 CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   173.00 173.00 173.00 0.00 90.00 63.05 2.74 0.00 CORE_BOT_ZN_5_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
77 DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   63.07 63.07 63.07 0.00 180.00 16.08 4.57 0.00 DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.00 1.00 0.00 4
78 PERIMETER_BOT_ZN_1_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   250.35 250.35 250.35 0.00 180.00 57.03 6.47 0.00 PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.00 1.00 0.00 4
79 PERIMETER_BOT_ZN_1_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   313.42 313.42 313.42 180.00 0.00 73.11 6.47 0.00 iz-PERIMETER_BOT_ZN_1_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
80 PERIMETER_BOT_ZN_1_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   626.84 626.84 626.84 0.00 90.00 626.84 1.00 0.00 PERIMETER_BOT_ZN_1_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
81 PERIMETER_BOT_ZN_4_WALL_WEST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 1.223 1.034   52.57 133.74 52.57 270.00 90.00 48.74 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
82 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 Window PERIMETER_BOT_ZN_4_WALL_WEST Window5 Detailed Fenestration WINDOW_U_0.498_SHGC_WEST_0.25 N/A 2.831 No 25.75 25.75 25.75 270.00 90.00 15.43 1.67 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
83 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 Window PERIMETER_BOT_ZN_4_WALL_WEST Window5 Detailed Fenestration WINDOW_U_0.498_SHGC_WEST_0.25 N/A 2.831 No 25.75 25.75 25.75 270.00 90.00 15.43 1.67 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
84 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 Window PERIMETER_BOT_ZN_4_WALL_WEST Window5 Detailed Fenestration WINDOW_U_0.498_SHGC_WEST_0.25 N/A 2.831 No 25.75 25.75 25.75 270.00 90.00 15.43 1.67 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
85 PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 Door PERIMETER_BOT_ZN_4_WALL_WEST CTF - ConductionTransferFunction SWINGING DOOR_CON 3.975 3.975   1.95 1.95 1.95 270.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
86 PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 Door PERIMETER_BOT_ZN_4_WALL_WEST CTF - ConductionTransferFunction SWINGING DOOR_CON 3.975 3.975   1.95 1.95 1.95 270.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
87 PERIMETER_BOT_ZN_4_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 135.00 90.00 6.47 2.74 0.00 PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
88 DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 90.00 90.00 39.59 2.74 0.00 DATACENTER_BOT_ZN_6_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
89 PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 45.00 90.00 6.47 2.74 0.00 PERIMETER_BOT_ZN_3_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
90 PERIMETER_BOT_ZN_4_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   201.98 201.98 201.98 315.00 180.00 6.47 39.59 0.00 PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.00 1.00 0.00 4
91 PERIMETER_BOT_ZN_4_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   201.98 201.98 201.98 135.00 0.00 6.47 48.74 0.00 iz-PERIMETER_BOT_ZN_4_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
92 PERIMETER_BOT_ZN_4_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   403.95 403.95 403.95 0.00 90.00 403.95 1.00 0.00 PERIMETER_BOT_ZN_4_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
93 PERIMETER_MID_ZN_3_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 1.174 0.999   84.71 200.61 84.71 0.00 90.00 73.11 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
94 PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW Window PERIMETER_MID_ZN_3_WALL_NORTH Window5 Detailed Fenestration WINDOW_U_0.498_SHGC_NORTH_0.25 N/A 2.831 No 115.90 115.90 115.90 0.00 90.00 73.11 1.59 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
95 PERIMETER_MID_ZN_3_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 225.00 90.00 6.47 2.74 0.00 PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
96 CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   173.00 173.00 173.00 180.00 90.00 63.05 2.74 0.00 CORE_MID_ZN_5_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
97 PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 135.00 90.00 6.47 2.74 0.00 PERIMETER_MID_ZN_2_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
98 DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   2.51 2.51 2.51 180.00 90.00 0.91 2.74 0.00 DATACENTER_MID_ZN_6_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
99 PERIMETER_MID_ZN_3_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   313.41 313.41 313.41 0.00 180.00 63.96 6.47 0.00 PERIMETER_MID_ZN_3_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
100 PERIMETER_MID_ZN_3_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   313.41 313.41 313.41 180.00 0.00 63.96 6.47 0.00 iz-PERIMETER_MID_ZN_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
101 PERIMETER_MID_ZN_3_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   626.83 626.83 626.83 0.00 90.00 626.83 1.00 0.00 PERIMETER_MID_ZN_3_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
102 PERIMETER_MID_ZN_2_WALL_EAST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 1.174 0.999   56.47 133.74 56.47 90.00 90.00 48.74 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
103 PERIMETER_MID_ZN_2_WALL_EAST_WINDOW Window PERIMETER_MID_ZN_2_WALL_EAST Window5 Detailed Fenestration WINDOW_U_0.498_SHGC_EAST_0.25 N/A 2.831 No 77.26 77.26 77.26 90.00 90.00 48.74 1.59 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
104 PERIMETER_MID_ZN_2_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 315.00 90.00 6.47 2.74 0.00 PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
105 CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 270.00 90.00 39.59 2.74 0.00 CORE_MID_ZN_5_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
106 PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 225.00 90.00 6.47 2.74 0.00 PERIMETER_MID_ZN_1_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
107 PERIMETER_MID_ZN_2_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   201.98 201.98 201.98 45.00 180.00 6.47 48.74 0.00 PERIMETER_MID_ZN_2_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
108 PERIMETER_MID_ZN_2_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   201.98 201.98 201.98 225.00 0.00 6.47 39.59 0.00 iz-PERIMETER_MID_ZN_2_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
109 PERIMETER_MID_ZN_2_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   403.95 403.95 403.95 0.00 90.00 403.95 1.00 0.00 PERIMETER_MID_ZN_2_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
110 PERIMETER_MID_ZN_1_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 45.00 90.00 6.47 2.74 0.00 PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
111 PERIMETER_MID_ZN_1_WALL_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 1.174 0.999   84.71 200.61 84.71 180.00 90.00 73.11 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
112 PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW Window PERIMETER_MID_ZN_1_WALL_SOUTH Window5 Detailed Fenestration WINDOW_U_0.498_SHGC_SOUTH_0.25 N/A 2.831 No 115.90 115.90 115.90 180.00 90.00 73.11 1.59 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
113 DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   2.51 2.51 2.51 0.00 90.00 0.91 2.74 0.00 DATACENTER_MID_ZN_6_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
114 PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 315.00 90.00 6.47 2.74 0.00 PERIMETER_MID_ZN_4_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
115 CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   173.00 173.00 173.00 0.00 90.00 63.05 2.74 0.00 CORE_MID_ZN_5_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
116 PERIMETER_MID_ZN_1_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   313.42 313.42 313.42 0.00 180.00 73.11 6.47 0.00 PERIMETER_MID_ZN_1_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
117 PERIMETER_MID_ZN_1_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   313.42 313.42 313.42 180.00 0.00 73.11 6.47 0.00 iz-PERIMETER_MID_ZN_1_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
118 PERIMETER_MID_ZN_1_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   626.84 626.84 626.84 0.00 90.00 626.84 1.00 0.00 PERIMETER_MID_ZN_1_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
119 PERIMETER_MID_ZN_4_WALL_WEST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 1.174 0.999   56.47 133.74 56.47 270.00 90.00 48.74 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
120 PERIMETER_MID_ZN_4_WALL_WEST_WINDOW Window PERIMETER_MID_ZN_4_WALL_WEST Window5 Detailed Fenestration WINDOW_U_0.498_SHGC_WEST_0.25 N/A 2.831 No 77.26 77.26 77.26 270.00 90.00 48.74 1.59 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
121 PERIMETER_MID_ZN_4_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 135.00 90.00 6.47 2.74 0.00 PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
122 DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 90.00 90.00 39.59 2.74 0.00 DATACENTER_MID_ZN_6_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
123 PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 45.00 90.00 6.47 2.74 0.00 PERIMETER_MID_ZN_3_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
124 PERIMETER_MID_ZN_4_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   201.98 201.98 201.98 315.00 180.00 6.47 39.59 0.00 PERIMETER_MID_ZN_4_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
125 PERIMETER_MID_ZN_4_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   201.98 201.98 201.98 135.00 0.00 6.47 48.74 0.00 iz-PERIMETER_MID_ZN_4_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
126 PERIMETER_MID_ZN_4_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   403.95 403.95 403.95 0.00 90.00 403.95 1.00 0.00 PERIMETER_MID_ZN_4_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
127 PERIMETER_TOP_ZN_3_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.421 1.172   84.71 200.61 84.71 0.00 90.00 73.11 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
128 PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW Window PERIMETER_TOP_ZN_3_WALL_NORTH Window5 Detailed Fenestration WINDOW_U_0.498_SHGC_NORTH_0.25 N/A 2.831 No 115.90 115.90 115.90 0.00 90.00 73.11 1.59 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
129 PERIMETER_TOP_ZN_3_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 225.00 90.00 6.47 2.74 0.00 PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
130 CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   173.00 173.00 173.00 180.00 90.00 63.05 2.74 0.00 CORE_TOP_ZN_5_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
131 PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 135.00 90.00 6.47 2.74 0.00 PERIMETER_TOP_ZN_2_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
132 DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   2.51 2.51 2.51 180.00 90.00 0.91 2.74 0.00 DATACENTER_TOP_ZN_6_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
133 PERIMETER_TOP_ZN_3_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   313.41 313.41 313.41 0.00 180.00 63.96 6.47 0.00 PERIMETER_TOP_ZN_3_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
134 PERIMETER_TOP_ZN_3_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   313.41 313.41 313.41 180.00 0.00 63.96 6.47 0.00 iz-PERIMETER_TOP_ZN_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
135 PERIMETER_TOP_ZN_3_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   626.83 626.83 626.83 0.00 90.00 626.83 1.00 0.00 PERIMETER_TOP_ZN_3_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
136 PERIMETER_TOP_ZN_2_WALL_EAST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.421 1.172   56.47 133.74 56.47 90.00 90.00 48.74 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
137 PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW Window PERIMETER_TOP_ZN_2_WALL_EAST Window5 Detailed Fenestration WINDOW_U_0.498_SHGC_EAST_0.25 N/A 2.831 No 77.26 77.26 77.26 90.00 90.00 48.74 1.59 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
138 PERIMETER_TOP_ZN_2_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 315.00 90.00 6.47 2.74 0.00 PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
139 CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 270.00 90.00 39.59 2.74 0.00 CORE_TOP_ZN_5_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
140 INT-PER3S-NE-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 225.00 90.00 6.47 2.74 0.00 INT-PER3S-NE Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
141 PERIMETER_TOP_ZN_2_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   201.98 201.98 201.98 45.00 180.00 6.47 48.74 0.00 PERIMETER_TOP_ZN_2_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
142 PERIMETER_TOP_ZN_2_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   201.98 201.98 201.98 225.00 0.00 6.47 39.59 0.00 iz-PERIMETER_TOP_ZN_2_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
143 PERIMETER_TOP_ZN_2_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   403.95 403.95 403.95 0.00 90.00 403.95 1.00 0.00 PERIMETER_TOP_ZN_2_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
144 PERIMETER_TOP_ZN_1_WALL_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.421 1.172   84.71 200.61 84.71 180.00 90.00 73.11 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
145 PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW Window PERIMETER_TOP_ZN_1_WALL_SOUTH Window5 Detailed Fenestration WINDOW_U_0.498_SHGC_SOUTH_0.25 N/A 2.831 No 115.90 115.90 115.90 180.00 90.00 73.11 1.59 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
146 INT-PER3S-NE Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 45.00 90.00 6.47 2.74 0.00 INT-PER3S-NE-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
147 DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   2.51 2.51 2.51 0.00 90.00 0.91 2.74 0.00 DATACENTER_TOP_ZN_6_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
148 PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 315.00 90.00 6.47 2.74 0.00 PERIMETER_TOP_ZN_4_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
149 CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   173.00 173.00 173.00 0.00 90.00 63.05 2.74 0.00 CORE_TOP_ZN_5_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
150 PERIMETER_TOP_ZN_1_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   313.42 313.42 313.42 0.00 180.00 73.11 6.47 0.00 PERIMETER_TOP_ZN_1_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
151 PERIMETER_TOP_ZN_1_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   313.42 313.42 313.42 180.00 0.00 73.11 6.47 0.00 iz-PERIMETER_TOP_ZN_1_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
152 PERIMETER_TOP_ZN_1_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   626.84 626.84 626.84 0.00 90.00 626.84 1.00 0.00 PERIMETER_TOP_ZN_1_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
153 PERIMETER_TOP_ZN_4_WALL_WEST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.421 1.172   56.47 133.74 56.47 270.00 90.00 48.74 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
154 PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW Window PERIMETER_TOP_ZN_4_WALL_WEST Window5 Detailed Fenestration WINDOW_U_0.498_SHGC_WEST_0.25 N/A 2.831 No 77.26 77.26 77.26 270.00 90.00 48.74 1.59 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
155 PERIMETER_TOP_ZN_4_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 135.00 90.00 6.47 2.74 0.00 PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
156 DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 90.00 90.00 39.59 2.74 0.00 DATACENTER_TOP_ZN_6_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
157 PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 45.00 90.00 6.47 2.74 0.00 PERIMETER_TOP_ZN_3_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
158 PERIMETER_TOP_ZN_4_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   201.98 201.98 201.98 315.00 180.00 6.47 39.59 0.00 PERIMETER_TOP_ZN_4_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
159 PERIMETER_TOP_ZN_4_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   201.98 201.98 201.98 135.00 0.00 6.47 48.74 0.00 iz-PERIMETER_TOP_ZN_4_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
160 PERIMETER_TOP_ZN_4_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   403.95 403.95 403.95 0.00 90.00 403.95 1.00 0.00 PERIMETER_TOP_ZN_4_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
161 GROUNDFLOOR_PLENUM_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 1.223 1.034   89.13 89.13 89.13 0.00 90.00 73.11 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
162 GROUNDFLOOR_PLENUM_WEST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 1.223 1.034   59.42 59.42 59.42 270.00 90.00 48.74 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
163 GROUNDFLOOR_PLENUM_WALL_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 1.223 1.034   89.13 89.13 89.13 180.00 90.00 73.11 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
164 GROUNDFLOOR_PLENUM_WALL_EAST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 1.223 1.034   59.42 59.42 59.42 90.00 90.00 48.74 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
165 iz-CORE_BOT_ZN_5_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   2496.12 2496.12 2496.12 0.00 180.00 63.05 39.59 0.00 CORE_BOT_ZN_5_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
166 iz-PERIMETER_BOT_ZN_3_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   313.41 313.41 313.41 0.00 180.00 63.96 6.47 0.00 PERIMETER_BOT_ZN_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
167 iz-PERIMETER_BOT_ZN_2_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   201.98 201.98 201.98 45.00 180.00 6.47 48.74 0.00 PERIMETER_BOT_ZN_2_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
168 iz-PERIMETER_BOT_ZN_1_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   313.42 313.42 313.42 0.00 180.00 73.11 6.47 0.00 PERIMETER_BOT_ZN_1_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
169 iz-PERIMETER_BOT_ZN_4_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   201.98 201.98 201.98 315.00 180.00 6.47 39.59 0.00 PERIMETER_BOT_ZN_4_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
170 iz-DATACENTER_BOT_ZN_6_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   36.20 36.20 36.20 0.00 180.00 0.91 39.59 0.00 DATACENTER_BOT_ZN_6_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
171 GROUNDFLOOR_PLENUM_CEILING Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   3563.11 3563.11 3563.11 180.00 0.00 73.11 48.74 0.00 GROUNDFLOOR_PLENUM_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
172 MIDFLOOR_PLENUM_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 1.174 0.999   89.13 89.13 89.13 0.00 90.00 73.11 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
173 MIDFLOOR_PLENUM_WALL_WEST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 1.174 0.999   59.42 59.42 59.42 270.00 90.00 48.74 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
174 MIDFLOOR_PLENUM_WALL_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 1.174 0.999   89.13 89.13 89.13 180.00 90.00 73.11 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
175 MIDFLOOR_PLENUM_WALL_EAST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 1.174 0.999   59.42 59.42 59.42 90.00 90.00 48.74 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
176 iz-CORE_MID_ZN_5_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   2496.12 2496.12 2496.12 0.00 180.00 63.05 39.59 0.00 CORE_MID_ZN_5_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
177 iz-PERIMETER_MID_ZN_3_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   313.41 313.41 313.41 0.00 180.00 63.96 6.47 0.00 PERIMETER_MID_ZN_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
178 iz-PERIMETER_MID_ZN_2_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   201.98 201.98 201.98 45.00 180.00 6.47 48.74 0.00 PERIMETER_MID_ZN_2_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
179 iz-PERIMETER_MID_ZN_1_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   313.42 313.42 313.42 0.00 180.00 73.11 6.47 0.00 PERIMETER_MID_ZN_1_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
180 iz-PERIMETER_MID_ZN_4_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   201.98 201.98 201.98 315.00 180.00 6.47 39.59 0.00 PERIMETER_MID_ZN_4_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
181 iz-DATACENTER_MID_ZN_6_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   36.20 36.20 36.20 0.00 180.00 0.91 39.59 0.00 DATACENTER_MID_ZN_6_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
182 MIDFLOOR_PLENUM_CEILING Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   3563.11 3563.11 3563.11 180.00 0.00 73.11 48.74 0.00 MIDFLOOR_PLENUM_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
183 TOPFLOOR_PLENUM_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.421 1.172   89.13 89.13 89.13 180.00 90.00 73.11 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
184 TOPFLOOR_PLENUM_WALL_EAST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.421 1.172   59.42 59.42 59.42 90.00 90.00 48.74 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
185 TOPFLOOR_PLENUM_WALL_WEST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.421 1.172   59.42 59.42 59.42 270.00 90.00 48.74 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
186 TOPFLOOR_PLENUM_WALL_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.421 1.172   89.13 89.13 89.13 0.00 90.00 73.11 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
187 iz-CORE_TOP_ZN_5_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   2496.12 2496.12 2496.12 0.00 180.00 63.05 39.59 0.00 CORE_TOP_ZN_5_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
188 iz-PERIMETER_TOP_ZN_3_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   313.41 313.41 313.41 0.00 180.00 63.96 6.47 0.00 PERIMETER_TOP_ZN_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
189 iz-PERIMETER_TOP_ZN_2_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   201.98 201.98 201.98 45.00 180.00 6.47 48.74 0.00 PERIMETER_TOP_ZN_2_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
190 iz-PERIMETER_TOP_ZN_1_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   313.42 313.42 313.42 0.00 180.00 73.11 6.47 0.00 PERIMETER_TOP_ZN_1_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
191 iz-PERIMETER_TOP_ZN_4_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   201.98 201.98 201.98 315.00 180.00 6.47 39.59 0.00 PERIMETER_TOP_ZN_4_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
192 iz-DATACENTER_TOP_ZN_6_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   36.20 36.20 36.20 0.00 180.00 0.91 39.59 0.00 DATACENTER_TOP_ZN_6_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
193 BUILDING_ROOF Roof   CTF - ConductionTransferFunction NONRES_ROOF 0.228 0.219   3563.11 3563.11 3563.11 180.00 0.00 73.11 48.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 4
194 DATACENTER_BOT_ZN_6_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   2.51 2.51 2.51 0.00 90.00 0.91 2.74 0.00 DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
195 DATACENTER_BOT_ZN_6_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   2.51 2.51 2.51 180.00 90.00 0.91 2.74 0.00 DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
196 DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 90.00 90.00 39.59 2.74 0.00 CORE_BOT_ZN_5_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
197 DATACENTER_BOT_ZN_6_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 270.00 90.00 39.59 2.74 0.00 DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
198 DATACENTER_BOT_ZN_6_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   36.20 36.20 36.20 0.00 180.00 0.91 39.59 0.00 DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.00 1.00 0.00 4
199 DATACENTER_BOT_ZN_6_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   36.20 36.20 36.20 180.00 0.00 0.91 39.59 0.00 iz-DATACENTER_BOT_ZN_6_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
200 DATACENTER_MID_ZN_6_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 270.00 90.00 39.59 2.74 0.00 DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
201 DATACENTER_MID_ZN_6_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   2.51 2.51 2.51 180.00 90.00 0.91 2.74 0.00 DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
202 DATACENTER_MID_ZN_6_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 90.00 90.00 39.59 2.74 0.00 CORE_MID_ZN_5_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
203 DATACENTER_MID_ZN_6_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   2.51 2.51 2.51 0.00 90.00 0.91 2.74 0.00 DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
204 DATACENTER_MID_ZN_6_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   36.20 36.20 36.20 0.00 180.00 0.91 39.59 0.00 DATACENTER_MID_ZN_6_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.00 1.00 0.00 4
205 DATACENTER_MID_ZN_6_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   36.20 36.20 36.20 180.00 0.00 0.91 39.59 0.00 iz-DATACENTER_MID_ZN_6_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
206 DATACENTER_TOP_ZN_6_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 90.00 90.00 39.59 2.74 0.00 CORE_TOP_ZN_5_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
207 DATACENTER_TOP_ZN_6_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 270.00 90.00 39.59 2.74 0.00 DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
208 DATACENTER_TOP_ZN_6_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   2.51 2.51 2.51 180.00 90.00 0.91 2.74 0.00 DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
209 DATACENTER_TOP_ZN_6_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   2.51 2.51 2.51 0.00 90.00 0.91 2.74 0.00 DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
210 DATACENTER_TOP_ZN_6_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   36.20 36.20 36.20 0.00 180.00 0.91 39.59 0.00 DATACENTER_TOP_ZN_6_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.00 1.00 0.00 4
211 DATACENTER_TOP_ZN_6_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   36.20 36.20 36.20 180.00 0.00 0.91 39.59 0.00 iz-DATACENTER_TOP_ZN_6_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
212 DATACENTER_BASEMENT_ZN_6_WALL_NORTH Wall   CTF - ConductionTransferFunction DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR 0.940 0.824   39.22 39.22 39.22 0.00 90.00 16.08 2.44 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
213 DATACENTER_BASEMENT_ZN_6_WALL_SOUTH Wall   CTF - ConductionTransferFunction DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR 0.940 0.824   39.22 39.22 39.22 180.00 90.00 16.08 2.44 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
214 DATACENTER_BASEMENT_ZN_6_WALL_WEST Wall   CTF - ConductionTransferFunction DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR 0.940 0.824   118.87 118.87 118.87 270.00 90.00 48.74 2.44 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
215 DATACENTER_BASEMENT_ZN_6_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   118.87 118.87 118.87 90.00 90.00 48.74 2.44 0.00 BASEMENT_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
216 DATACENTER_BASEMENT_ZN_6_FLOOR Floor   CTF - ConductionTransferFunction EXT_SLAB_8IN_WITH_CARPET 3.285 1.827   783.68 783.68 783.68 0.00 180.00 16.08 48.74 0.00 DATACENTER_BASEMENT_ZN_6_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.00 1.00 0.00 4
217 DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   36.20 36.20 36.20 180.00 0.00 0.91 39.59 0.00 DATACENTER_BOT_ZN_6_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
218 DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   419.35 419.35 419.35 180.00 0.00 10.59 39.59 0.00 DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
219 PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   201.98 201.98 201.98 135.00 0.00 6.47 48.74 0.00 PERIMETER_BOT_ZN_4_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
220 DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   63.08 63.08 63.08 180.00 0.00 16.08 6.47 0.00 DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
221 DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   63.07 63.07 63.07 180.00 0.00 11.51 6.47 0.00 DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4


Environment

Environment Name Environment Type Start Date End Date Start DayOfWeek Duration {#days} Source:Start DayOfWeek Use Daylight Saving Use Holidays Apply Weekend Holiday Rule Use Rain Values Use Snow Values Sky Temperature Model
1 RUNPERIOD 1 WeatherFileRunPeriod 01/01/2017 12/31/2017 Sunday 365 Use RunPeriod Specified Day No No No Yes Yes Clark and Allen


Environment:Special Days

Special Day Name Special Day Type Source Start Date Duration {#days}
1 NEW YEARS DAY Holiday InputFile 01/01 1Environment:Special Days


Environment:Daylight Saving

Daylight Saving Indicator Source Start Date End Date
1 Yes InputFile 03/12 11/05


Tabular Report

Style Unit Conversion
1 Commaandhtml commaandhtml


Warmup Convergence Information

Zone Name Environment Type/Name Average Warmup Temperature Difference {deltaC} Std Dev Warmup Temperature Difference {deltaC} Max Temperature Pass/Fail Convergence Min Temperature Pass/Fail Convergence Average Warmup Load Difference {W} Std Dev Warmup Load Difference {W} Heating Load Pass/Fail Convergence Cooling Load Pass/Fail Convergence
1 BASEMENT RunPeriod: RUNPERIOD 1 0.2330065948 0.2299243882 Pass Pass 0.7609838585 2.1132672043 Pass Pass
2 CORE_BOTTOM RunPeriod: RUNPERIOD 1 3.7209159212E-003 5.9399468738E-003 Pass Pass 0.0000000000 0.0000000000 Pass Pass
3 CORE_MID RunPeriod: RUNPERIOD 1 4.6922029274E-003 6.7377814783E-003 Pass Pass 0.0000000000 0.0000000000 Pass Pass
4 CORE_TOP RunPeriod: RUNPERIOD 1 9.3041196908E-002 8.5046056146E-002 Pass Pass 0.2747371822 0.4837540746 Pass Pass
5 PERIMETER_BOT_ZN_3 RunPeriod: RUNPERIOD 1 2.8467251791E-002 3.0319372204E-002 Pass Pass 0.0000000000 0.0000000000 Pass Pass
6 PERIMETER_BOT_ZN_2 RunPeriod: RUNPERIOD 1 2.8931109597E-002 3.1407873671E-002 Pass Pass 0.0000000000 0.0000000000 Pass Pass
7 PERIMETER_BOT_ZN_1 RunPeriod: RUNPERIOD 1 2.8683790820E-002 3.0356252351E-002 Pass Pass 0.0000000000 0.0000000000 Pass Pass
8 PERIMETER_BOT_ZN_4 RunPeriod: RUNPERIOD 1 2.8730527230E-002 3.0615894926E-002 Pass Pass 0.0000000000 0.0000000000 Pass Pass
9 PERIMETER_MID_ZN_3 RunPeriod: RUNPERIOD 1 3.4096179532E-002 3.4680982160E-002 Pass Pass 0.0000000000 0.0000000000 Pass Pass
10 PERIMETER_MID_ZN_2 RunPeriod: RUNPERIOD 1 3.5007370549E-002 3.5921931300E-002 Pass Pass 0.0000000000 0.0000000000 Pass Pass
11 PERIMETER_MID_ZN_1 RunPeriod: RUNPERIOD 1 3.5654799570E-002 3.7319502384E-002 Pass Pass 0.0000000000 0.0000000000 Pass Pass
12 PERIMETER_MID_ZN_4 RunPeriod: RUNPERIOD 1 3.5788581952E-002 3.6171552164E-002 Pass Pass 0.0000000000 0.0000000000 Pass Pass
13 PERIMETER_TOP_ZN_3 RunPeriod: RUNPERIOD 1 0.1620909527 0.1961762846 Pass Pass 0.8695292671 2.8458333016 Pass Pass
14 PERIMETER_TOP_ZN_2 RunPeriod: RUNPERIOD 1 0.1601019422 0.1931929272 Pass Pass 2.4918377009 18.5975078102 Pass Pass
15 PERIMETER_TOP_ZN_1 RunPeriod: RUNPERIOD 1 0.1483366675 0.1757080494 Pass Pass 0.8631431271 2.8318454656 Pass Pass
16 PERIMETER_TOP_ZN_4 RunPeriod: RUNPERIOD 1 6.3141849096E-002 9.3737622137E-002 Pass Pass 1.1443488727 3.6120874667 Pass Pass
17 GROUNDFLOOR_PLENUM RunPeriod: RUNPERIOD 1 4.1725199189E-003 4.7458942672E-003 Pass Pass 0.0000000000 0.0000000000 Pass Pass
18 MIDFLOOR_PLENUM RunPeriod: RUNPERIOD 1 5.5914111673E-003 6.9815217508E-003 Pass Pass 0.0000000000 0.0000000000 Pass Pass
19 TOPFLOOR_PLENUM RunPeriod: RUNPERIOD 1 6.3083515130E-002 4.1245456113E-002 Pass Pass 0.2549044147 0.4394454640 Pass Pass
20 DATACENTER_BOT_ZN_6 RunPeriod: RUNPERIOD 1 5.7446490670E-006 7.4258721911E-006 Pass Pass 2.8280598937E-003 1.9210543970E-003 Pass Pass
21 DATACENTER_MID_ZN_6 RunPeriod: RUNPERIOD 1 9.4584497169E-003 7.7270624815E-003 Pass Pass 4.9872981068E-003 6.1568889440E-003 Pass Pass
22 DATACENTER_TOP_ZN_6 RunPeriod: RUNPERIOD 1 1.7570039025E-002 1.3511349641E-002 Pass Pass 3.5181292975E-003 3.8762959033E-003 Pass Pass
23 DATACENTER_BASEMENT_ZN_6 RunPeriod: RUNPERIOD 1 7.3407145655E-006 9.8845308530E-006 Pass Pass 4.0367131652E-005 1.0956580787E-004 Pass Pass



Table of Contents

Report: Annual Heat Emissions Summary

For: Entire Facility

Timestamp: 2023-10-16 08:43:24

Heat Emission by Components

Envelope Convection Zone Exfiltration Zone Exhaust Air HVAC Relief Air HVAC Reject Heat Total
Heat Emissions [GJ] 5374.23 88.64 0.00 12100.87 27789.74 45353.46



Table of Contents

Report: Climatic Data Summary

For: Entire Facility

Timestamp: 2023-10-16 08:43:24

SizingPeriod:DesignDay

Maximum Dry Bulb [C] Daily Temperature Range [deltaC] Humidity Value Humidity Type Wind Speed [m/s] Wind Direction
ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB -6.30 0.00 -6.30 Wetbulb [C] 5.30 320.00
ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 34.40 9.50 23.50 Wetbulb [C] 4.00 300.00


Monthly Precipitation Summary

Monthly Total Precipitation from .epw [mm] Monthly Total Hours of Rain from .epw Monthly Total Precipitation in Site:Precipitation [mm] Monthly Total Roof Irrigation Depth [mm] Monthly Total Rain Collection Volume [m3]
Jan 0.00 0      
Feb 0.00 0      
Mar 0.00 0      
Apr 0.00 0      
May 0.00 0      
Jun 0.00 0      
Jul 0.00 0      
Aug 0.00 0      
Sep 90.00 25      
Oct 0.00 0      
Nov 0.00 0      
Dec 0.00 0      


Weather Statistics File

Value
None  



Table of Contents

Report: Envelope Summary

For: Entire Facility

Timestamp: 2023-10-16 08:43:24

Opaque Exterior

Construction Reflectance U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Net Area [m2] Azimuth [deg] Tilt [deg] Cardinal Direction
BASEMENT_WALL_EAST BASEMENT_WALL_EAST_CFACTOR 1.00 0.845 0.940 118.87 118.87 90.00 90.00 E
BASEMENT_WALL_SOUTH BASEMENT_WALL_SOUTH_CFACTOR 1.00 0.845 0.940 139.09 139.09 180.00 90.00 S
BASEMENT_WALL_NORTH BASEMENT_WALL_NORTH_CFACTOR 1.00 0.845 0.940 139.09 139.09 0.00 90.00 N
PERIMETER_BOT_ZN_3_WALL_NORTH NONRES_EXT_WALL_GRD 0.30 1.034 1.223 200.61 76.91 0.00 90.00 N
PERIMETER_BOT_ZN_2_WALL_EAST NONRES_EXT_WALL_GRD 0.30 1.034 1.223 133.74 52.57 90.00 90.00 E
PERIMETER_BOT_ZN_1_WALL_SOUTH NONRES_EXT_WALL_GRD 0.30 1.034 1.223 200.61 76.91 180.00 90.00 S
PERIMETER_BOT_ZN_4_WALL_WEST NONRES_EXT_WALL_GRD 0.30 1.034 1.223 133.74 52.57 270.00 90.00 W
PERIMETER_MID_ZN_3_WALL_NORTH NONRES_EXT_WALL_MID 0.30 0.999 1.174 2006.06 847.11 0.00 90.00 N
PERIMETER_MID_ZN_2_WALL_EAST NONRES_EXT_WALL_MID 0.30 0.999 1.174 1337.37 564.74 90.00 90.00 E
PERIMETER_MID_ZN_1_WALL_SOUTH NONRES_EXT_WALL_MID 0.30 0.999 1.174 2006.06 847.11 180.00 90.00 S
PERIMETER_MID_ZN_4_WALL_WEST NONRES_EXT_WALL_MID 0.30 0.999 1.174 1337.37 564.74 270.00 90.00 W
PERIMETER_TOP_ZN_3_WALL_NORTH NONRES_EXT_WALL_TOP 0.30 1.172 1.421 200.61 84.71 0.00 90.00 N
PERIMETER_TOP_ZN_2_WALL_EAST NONRES_EXT_WALL_TOP 0.30 1.172 1.421 133.74 56.47 90.00 90.00 E
PERIMETER_TOP_ZN_1_WALL_SOUTH NONRES_EXT_WALL_TOP 0.30 1.172 1.421 200.61 84.71 180.00 90.00 S
PERIMETER_TOP_ZN_4_WALL_WEST NONRES_EXT_WALL_TOP 0.30 1.172 1.421 133.74 56.47 270.00 90.00 W
GROUNDFLOOR_PLENUM_WALL_NORTH NONRES_EXT_WALL_GRD 0.30 1.034 1.223 89.13 89.13 0.00 90.00 N
GROUNDFLOOR_PLENUM_WEST NONRES_EXT_WALL_GRD 0.30 1.034 1.223 59.42 59.42 270.00 90.00 W
GROUNDFLOOR_PLENUM_WALL_SOUTH NONRES_EXT_WALL_GRD 0.30 1.034 1.223 89.13 89.13 180.00 90.00 S
GROUNDFLOOR_PLENUM_WALL_EAST NONRES_EXT_WALL_GRD 0.30 1.034 1.223 59.42 59.42 90.00 90.00 E
MIDFLOOR_PLENUM_WALL_NORTH NONRES_EXT_WALL_MID 0.30 0.999 1.174 891.32 891.32 0.00 90.00 N
MIDFLOOR_PLENUM_WALL_WEST NONRES_EXT_WALL_MID 0.30 0.999 1.174 594.21 594.21 270.00 90.00 W
MIDFLOOR_PLENUM_WALL_SOUTH NONRES_EXT_WALL_MID 0.30 0.999 1.174 891.32 891.32 180.00 90.00 S
MIDFLOOR_PLENUM_WALL_EAST NONRES_EXT_WALL_MID 0.30 0.999 1.174 594.21 594.21 90.00 90.00 E
TOPFLOOR_PLENUM_WALL_NORTH NONRES_EXT_WALL_TOP 0.30 1.172 1.421 89.13 89.13 180.00 90.00 S
TOPFLOOR_PLENUM_WALL_EAST NONRES_EXT_WALL_TOP 0.30 1.172 1.421 59.42 59.42 90.00 90.00 E
TOPFLOOR_PLENUM_WALL_WEST NONRES_EXT_WALL_TOP 0.30 1.172 1.421 59.42 59.42 270.00 90.00 W
TOPFLOOR_PLENUM_WALL_SOUTH NONRES_EXT_WALL_TOP 0.30 1.172 1.421 89.13 89.13 0.00 90.00 N
BUILDING_ROOF NONRES_ROOF 0.55 0.221 0.228 3563.11 3563.11 180.00 0.00  
DATACENTER_BASEMENT_ZN_6_WALL_NORTH DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR 1.00 0.845 0.940 39.22 39.22 0.00 90.00 N
DATACENTER_BASEMENT_ZN_6_WALL_SOUTH DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR 1.00 0.845 0.940 39.22 39.22 180.00 90.00 S
DATACENTER_BASEMENT_ZN_6_WALL_WEST DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR 1.00 0.845 0.940 118.87 118.87 270.00 90.00 W


Opaque Interior

Construction Reflectance U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Net Area [m2] Azimuth [deg] Tilt [deg] Cardinal Direction
BASEMENT_WALL_WEST INT_WALL 0.30 2.511 6.299 118.87 118.87 270.00 90.00 W
BASEMENT_FLOOR EXT_SLAB_8IN_WITH_CARPET 0.30 1.591 3.285 2779.43 2779.43 0.00 180.00  
PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER INT_SLAB_CEILING 0.30 1.887 3.839 201.98 201.98 225.00 0.00  
PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER INT_SLAB_CEILING 0.30 1.887 3.839 250.34 250.34 180.00 0.00  
CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER INT_SLAB_CEILING 0.30 1.887 3.839 2076.77 2076.77 180.00 0.00  
PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER INT_SLAB_CEILING 0.30 1.887 3.839 250.34 250.34 180.00 0.00  
CORE_BOT_ZN_5_WALL_SOUTH INT_WALL 0.30 2.511 6.299 173.00 173.00 180.00 90.00 S
CORE_BOT_ZN_5_WALL_WEST INT_WALL 0.30 2.511 6.299 108.64 108.64 270.00 90.00 W
CORE_BOT_ZN_5_WALL_NORTH INT_WALL 0.30 2.511 6.299 173.00 173.00 0.00 90.00 N
CORE_BOT_ZN_5_WALL_EAST INT_WALL 0.30 2.511 6.299 108.64 108.64 90.00 90.00 E
DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER INT_SLAB_FLOOR 0.30 1.887 3.839 419.30 419.30 0.00 180.00  
CORE_BOT_ZN_5_FLOOR INT_SLAB_FLOOR 0.30 1.887 3.839 2076.82 2076.82 0.00 180.00  
CORE_BOT_ZN_5_CEILING DROPCEILING 0.30 2.031 4.488 2496.12 2496.12 180.00 0.00  
CORE_MID_ZN_5_WALL_SOUTH INT_WALL 0.30 2.511 6.299 1729.99 1729.99 180.00 90.00 S
CORE_MID_ZN_5_WALL_WEST INT_WALL 0.30 2.511 6.299 1086.40 1086.40 270.00 90.00 W
CORE_MID_ZN_5_WALL_NORTH INT_WALL 0.30 2.511 6.299 1729.99 1729.99 0.00 90.00 N
CORE_MID_ZN_5_WALL_EAST INT_WALL 0.30 2.511 6.299 1086.40 1086.40 90.00 90.00 E
CORE_MID_ZN_5_FLOOR INT_SLAB_FLOOR 0.30 1.711 3.839 24961.20 24961.20 0.00 180.00  
CORE_MID_ZN_5_CEILING DROPCEILING 0.30 2.031 4.488 24961.20 24961.20 180.00 0.00  
CORE_TOP_ZN_5_WALL_SOUTH INT_WALL 0.30 2.511 6.299 173.00 173.00 180.00 90.00 S
CORE_TOP_ZN_5_WALL_WEST INT_WALL 0.30 2.511 6.299 108.64 108.64 270.00 90.00 W
CORE_TOP_ZN_5_WALL_NORTH INT_WALL 0.30 2.511 6.299 173.00 173.00 0.00 90.00 N
CORE_TOP_ZN_5_WALL_EAST INT_WALL 0.30 2.511 6.299 108.64 108.64 90.00 90.00 E
CORE_TOP_ZN_5_FLOOR INT_SLAB_FLOOR 0.30 1.711 3.839 2496.12 2496.12 0.00 180.00  
CORE_TOP_ZN_5_CEILING DROPCEILING 0.30 2.031 4.488 2496.12 2496.12 180.00 0.00  
PERIMETER_BOT_ZN_3_WALL_WEST INT_WALL 0.30 2.511 6.299 17.75 17.75 225.00 90.00 W
CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 173.00 173.00 180.00 90.00 S
PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 17.75 17.75 135.00 90.00 S
DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 2.51 2.51 180.00 90.00 S
PERIMETER_BOT_ZN_3_FLOOR INT_SLAB_FLOOR 0.30 1.887 3.839 250.34 250.34 0.00 180.00  
DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER INT_SLAB_FLOOR 0.30 1.887 3.839 63.07 63.07 0.00 180.00  
PERIMETER_BOT_ZN_3_CEILING DROPCEILING 0.30 2.031 4.488 313.41 313.41 180.00 0.00  
PERIMETER_BOT_ZN_2_WALL_NORTH INT_WALL 0.30 2.511 6.299 17.75 17.75 315.00 90.00 N
CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 108.64 108.64 270.00 90.00 W
PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 17.75 17.75 225.00 90.00 W
PERIMETER_BOT_ZN_2_FLOOR INT_SLAB_FLOOR 0.30 1.887 3.839 201.98 201.98 45.00 180.00  
PERIMETER_BOT_ZN_2_CEILING DROPCEILING 0.30 2.031 4.488 201.98 201.98 225.00 0.00  
PERIMETER_BOT_ZN_1_WALL_EAST INT_WALL 0.30 2.511 6.299 17.75 17.75 45.00 90.00 E
DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 2.51 2.51 0.00 90.00 N
PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 17.75 17.75 315.00 90.00 N
CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 173.00 173.00 0.00 90.00 N
DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER INT_SLAB_FLOOR 0.30 1.887 3.839 63.07 63.07 0.00 180.00  
PERIMETER_BOT_ZN_1_FLOOR INT_SLAB_FLOOR 0.30 1.887 3.839 250.35 250.35 0.00 180.00  
PERIMETER_BOT_ZN_1_CEILING DROPCEILING 0.30 2.031 4.488 313.42 313.42 180.00 0.00  
PERIMETER_BOT_ZN_4_WALL_SOUTH INT_WALL 0.30 2.511 6.299 17.75 17.75 135.00 90.00 S
DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 108.64 108.64 90.00 90.00 E
PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 17.75 17.75 45.00 90.00 E
PERIMETER_BOT_ZN_4_FLOOR INT_SLAB_FLOOR 0.30 1.887 3.839 201.98 201.98 315.00 180.00  
PERIMETER_BOT_ZN_4_CEILING DROPCEILING 0.30 2.031 4.488 201.98 201.98 135.00 0.00  
PERIMETER_MID_ZN_3_WALL_WEST INT_WALL 0.30 2.511 6.299 177.47 177.47 225.00 90.00 W
CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 1729.99 1729.99 180.00 90.00 S
PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 177.47 177.47 135.00 90.00 S
DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 25.09 25.09 180.00 90.00 S
PERIMETER_MID_ZN_3_FLOOR INT_SLAB_FLOOR 0.30 1.711 3.839 3134.13 3134.13 0.00 180.00  
PERIMETER_MID_ZN_3_CEILING DROPCEILING 0.30 2.031 4.488 3134.13 3134.13 180.00 0.00  
PERIMETER_MID_ZN_2_WALL_NORTH INT_WALL 0.30 2.511 6.299 177.47 177.47 315.00 90.00 N
CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 1086.40 1086.40 270.00 90.00 W
PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 177.47 177.47 225.00 90.00 W
PERIMETER_MID_ZN_2_FLOOR INT_SLAB_FLOOR 0.30 1.711 3.839 2019.75 2019.75 45.00 180.00  
PERIMETER_MID_ZN_2_CEILING DROPCEILING 0.30 2.031 4.488 2019.75 2019.75 225.00 0.00  
PERIMETER_MID_ZN_1_WALL_EAST INT_WALL 0.30 2.511 6.299 177.47 177.47 45.00 90.00 E
DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 25.09 25.09 0.00 90.00 N
PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 177.47 177.47 315.00 90.00 N
CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 1729.99 1729.99 0.00 90.00 N
PERIMETER_MID_ZN_1_FLOOR INT_SLAB_FLOOR 0.30 1.711 3.839 3134.20 3134.20 0.00 180.00  
PERIMETER_MID_ZN_1_CEILING DROPCEILING 0.30 2.031 4.488 3134.20 3134.20 180.00 0.00  
PERIMETER_MID_ZN_4_WALL_SOUTH INT_WALL 0.30 2.511 6.299 177.47 177.47 135.00 90.00 S
DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 1086.40 1086.40 90.00 90.00 E
PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 177.47 177.47 45.00 90.00 E
PERIMETER_MID_ZN_4_FLOOR INT_SLAB_FLOOR 0.30 1.711 3.839 2019.75 2019.75 315.00 180.00  
PERIMETER_MID_ZN_4_CEILING DROPCEILING 0.30 2.031 4.488 2019.75 2019.75 135.00 0.00  
PERIMETER_TOP_ZN_3_WALL_WEST INT_WALL 0.30 2.511 6.299 17.75 17.75 225.00 90.00 W
CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 173.00 173.00 180.00 90.00 S
PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 17.75 17.75 135.00 90.00 S
DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 2.51 2.51 180.00 90.00 S
PERIMETER_TOP_ZN_3_FLOOR INT_SLAB_FLOOR 0.30 1.711 3.839 313.41 313.41 0.00 180.00  
PERIMETER_TOP_ZN_3_CEILING DROPCEILING 0.30 2.031 4.488 313.41 313.41 180.00 0.00  
PERIMETER_TOP_ZN_2_WALL_NORTH INT_WALL 0.30 2.511 6.299 17.75 17.75 315.00 90.00 N
CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 108.64 108.64 270.00 90.00 W
INT-PER3S-NE-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 17.75 17.75 225.00 90.00 W
PERIMETER_TOP_ZN_2_FLOOR INT_SLAB_FLOOR 0.30 1.711 3.839 201.98 201.98 45.00 180.00  
PERIMETER_TOP_ZN_2_CEILING DROPCEILING 0.30 2.031 4.488 201.98 201.98 225.00 0.00  
INT-PER3S-NE INT_WALL 0.30 2.511 6.299 17.75 17.75 45.00 90.00 E
DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 2.51 2.51 0.00 90.00 N
PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 17.75 17.75 315.00 90.00 N
CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 173.00 173.00 0.00 90.00 N
PERIMETER_TOP_ZN_1_FLOOR INT_SLAB_FLOOR 0.30 1.711 3.839 313.42 313.42 0.00 180.00  
PERIMETER_TOP_ZN_1_CEILING DROPCEILING 0.30 2.031 4.488 313.42 313.42 180.00 0.00  
PERIMETER_TOP_ZN_4_WALL_SOUTH INT_WALL 0.30 2.511 6.299 17.75 17.75 135.00 90.00 S
DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 108.64 108.64 90.00 90.00 E
PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 17.75 17.75 45.00 90.00 E
PERIMETER_TOP_ZN_4_FLOOR INT_SLAB_FLOOR 0.30 1.711 3.839 201.98 201.98 315.00 180.00  
PERIMETER_TOP_ZN_4_CEILING DROPCEILING 0.30 2.031 4.488 201.98 201.98 135.00 0.00  
iz-CORE_BOT_ZN_5_CEILING DROPCEILING 0.30 2.031 4.488 2496.12 2496.12 0.00 180.00  
iz-PERIMETER_BOT_ZN_3_CEILING DROPCEILING 0.30 2.031 4.488 313.41 313.41 0.00 180.00  
iz-PERIMETER_BOT_ZN_2_CEILING DROPCEILING 0.30 2.031 4.488 201.98 201.98 45.00 180.00  
iz-PERIMETER_BOT_ZN_1_CEILING DROPCEILING 0.30 2.031 4.488 313.42 313.42 0.00 180.00  
iz-PERIMETER_BOT_ZN_4_CEILING DROPCEILING 0.30 2.031 4.488 201.98 201.98 315.00 180.00  
iz-DATACENTER_BOT_ZN_6_CEILING DROPCEILING 0.30 2.031 4.488 36.20 36.20 0.00 180.00  
GROUNDFLOOR_PLENUM_CEILING INT_SLAB_CEILING 0.30 2.104 3.839 3563.11 3563.11 180.00 0.00  
iz-CORE_MID_ZN_5_CEILING DROPCEILING 0.30 2.031 4.488 24961.20 24961.20 0.00 180.00  
iz-PERIMETER_MID_ZN_3_CEILING DROPCEILING 0.30 2.031 4.488 3134.13 3134.13 0.00 180.00  
iz-PERIMETER_MID_ZN_2_CEILING DROPCEILING 0.30 2.031 4.488 2019.75 2019.75 45.00 180.00  
iz-PERIMETER_MID_ZN_1_CEILING DROPCEILING 0.30 2.031 4.488 3134.20 3134.20 0.00 180.00  
iz-PERIMETER_MID_ZN_4_CEILING DROPCEILING 0.30 2.031 4.488 2019.75 2019.75 315.00 180.00  
iz-DATACENTER_MID_ZN_6_CEILING DROPCEILING 0.30 2.031 4.488 362.03 362.03 0.00 180.00  
MIDFLOOR_PLENUM_CEILING INT_SLAB_CEILING 0.30 2.104 3.839 35631.06 35631.06 180.00 0.00  
iz-CORE_TOP_ZN_5_CEILING DROPCEILING 0.30 2.031 4.488 2496.12 2496.12 0.00 180.00  
iz-PERIMETER_TOP_ZN_3_CEILING DROPCEILING 0.30 2.031 4.488 313.41 313.41 0.00 180.00  
iz-PERIMETER_TOP_ZN_2_CEILING DROPCEILING 0.30 2.031 4.488 201.98 201.98 45.00 180.00  
iz-PERIMETER_TOP_ZN_1_CEILING DROPCEILING 0.30 2.031 4.488 313.42 313.42 0.00 180.00  
iz-PERIMETER_TOP_ZN_4_CEILING DROPCEILING 0.30 2.031 4.488 201.98 201.98 315.00 180.00  
iz-DATACENTER_TOP_ZN_6_CEILING DROPCEILING 0.30 2.031 4.488 36.20 36.20 0.00 180.00  
DATACENTER_BOT_ZN_6_WALL_NORTH INT_WALL 0.30 2.511 6.299 2.51 2.51 0.00 90.00 N
DATACENTER_BOT_ZN_6_WALL_SOUTH INT_WALL 0.30 2.511 6.299 2.51 2.51 180.00 90.00 S
DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 108.64 108.64 90.00 90.00 E
DATACENTER_BOT_ZN_6_WALL_WEST INT_WALL 0.30 2.511 6.299 108.64 108.64 270.00 90.00 W
DATACENTER_BOT_ZN_6_FLOOR INT_SLAB_FLOOR 0.30 1.887 3.839 36.20 36.20 0.00 180.00  
DATACENTER_BOT_ZN_6_CEILING DROPCEILING 0.30 2.031 4.488 36.20 36.20 180.00 0.00  
DATACENTER_MID_ZN_6_WALL_WEST INT_WALL 0.30 2.511 6.299 1086.40 1086.40 270.00 90.00 W
DATACENTER_MID_ZN_6_WALL_SOUTH INT_WALL 0.30 2.511 6.299 25.09 25.09 180.00 90.00 S
DATACENTER_MID_ZN_6_WALL_EAST INT_WALL 0.30 2.511 6.299 1086.40 1086.40 90.00 90.00 E
DATACENTER_MID_ZN_6_WALL_NORTH INT_WALL 0.30 2.511 6.299 25.09 25.09 0.00 90.00 N
DATACENTER_MID_ZN_6_FLOOR INT_SLAB_FLOOR 0.30 1.711 3.839 362.03 362.03 0.00 180.00  
DATACENTER_MID_ZN_6_CEILING DROPCEILING 0.30 2.031 4.488 362.03 362.03 180.00 0.00  
DATACENTER_TOP_ZN_6_WALL_EAST INT_WALL 0.30 2.511 6.299 108.64 108.64 90.00 90.00 E
DATACENTER_TOP_ZN_6_WALL_WEST INT_WALL 0.30 2.511 6.299 108.64 108.64 270.00 90.00 W
DATACENTER_TOP_ZN_6_WALL_SOUTH INT_WALL 0.30 2.511 6.299 2.51 2.51 180.00 90.00 S
DATACENTER_TOP_ZN_6_WALL_NORTH INT_WALL 0.30 2.511 6.299 2.51 2.51 0.00 90.00 N
DATACENTER_TOP_ZN_6_FLOOR INT_SLAB_FLOOR 0.30 1.711 3.839 36.20 36.20 0.00 180.00  
DATACENTER_TOP_ZN_6_CEILING DROPCEILING 0.30 2.031 4.488 36.20 36.20 180.00 0.00  
DATACENTER_BASEMENT_ZN_6_WALL_EAST INT_WALL 0.30 2.511 6.299 118.87 118.87 90.00 90.00 E
DATACENTER_BASEMENT_ZN_6_FLOOR EXT_SLAB_8IN_WITH_CARPET 0.30 1.591 3.285 783.68 783.68 0.00 180.00  
DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER INT_SLAB_CEILING 0.30 1.887 3.839 36.20 36.20 180.00 0.00  
DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 INT_SLAB_CEILING 0.30 1.887 3.839 419.35 419.35 180.00 0.00  
PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER INT_SLAB_CEILING 0.30 1.887 3.839 201.98 201.98 135.00 0.00  
DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 INT_SLAB_CEILING 0.30 1.887 3.839 63.08 63.08 180.00 0.00  
DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 INT_SLAB_CEILING 0.30 1.887 3.839 63.07 63.07 180.00 0.00  
BASEMENT_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 7126.21   0.00 90.00 N
CORE_BOTTOM_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 5064.65   0.00 90.00 N
CORE_MID_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 50646.53   0.00 90.00 N
CORE_TOP_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 5064.65   0.00 90.00 N
PERIMETER_BOT_ZN_3_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 626.83   0.00 90.00 N
PERIMETER_BOT_ZN_2_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 403.95   0.00 90.00 N
PERIMETER_BOT_ZN_1_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 626.84   0.00 90.00 N
PERIMETER_BOT_ZN_4_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 403.95   0.00 90.00 N
PERIMETER_MID_ZN_3_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 6268.26   0.00 90.00 N
PERIMETER_MID_ZN_2_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 4039.50   0.00 90.00 N
PERIMETER_MID_ZN_1_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 6268.35   0.00 90.00 N
PERIMETER_MID_ZN_4_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 4039.48   0.00 90.00 N
PERIMETER_TOP_ZN_3_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 626.83   0.00 90.00 N
PERIMETER_TOP_ZN_2_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 403.95   0.00 90.00 N
PERIMETER_TOP_ZN_1_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 626.84   0.00 90.00 N
PERIMETER_TOP_ZN_4_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 403.95   0.00 90.00 N


Exterior Fenestration

Construction Frame and Divider Glass Area [m2] Frame Area [m2] Divider Area [m2] Area of One Opening [m2] Area of Multiplied Openings [m2] Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance Frame Conductance [W/m2-K] Divider Conductance [W/m2-K] NFRC Product Type Assembly U-Factor [W/m2-K] Assembly SHGC Assembly Visible Transmittance Shade Control Parent Surface Azimuth [deg] Tilt [deg] Cardinal Direction
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 WINDOW_U_0.498_SHGC_NORTH_0.25   23.18 0.00 0.00 23.18 23.18 2.831 0.251 0.276             No PERIMETER_BOT_ZN_3_WALL_NORTH 0.00 90.00 N
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 WINDOW_U_0.498_SHGC_NORTH_0.25   23.18 0.00 0.00 23.18 23.18 2.831 0.251 0.276             No PERIMETER_BOT_ZN_3_WALL_NORTH 0.00 90.00 N
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 WINDOW_U_0.498_SHGC_NORTH_0.25   23.18 0.00 0.00 23.18 23.18 2.831 0.251 0.276             No PERIMETER_BOT_ZN_3_WALL_NORTH 0.00 90.00 N
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 WINDOW_U_0.498_SHGC_NORTH_0.25   23.18 0.00 0.00 23.18 23.18 2.831 0.251 0.276             No PERIMETER_BOT_ZN_3_WALL_NORTH 0.00 90.00 N
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 WINDOW_U_0.498_SHGC_NORTH_0.25   23.18 0.00 0.00 23.18 23.18 2.831 0.251 0.276             No PERIMETER_BOT_ZN_3_WALL_NORTH 0.00 90.00 N
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 WINDOW_U_0.498_SHGC_EAST_0.25   25.75 0.00 0.00 25.75 25.75 2.831 0.251 0.276             No PERIMETER_BOT_ZN_2_WALL_EAST 90.00 90.00 E
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 WINDOW_U_0.498_SHGC_EAST_0.25   25.75 0.00 0.00 25.75 25.75 2.831 0.251 0.276             No PERIMETER_BOT_ZN_2_WALL_EAST 90.00 90.00 E
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 WINDOW_U_0.498_SHGC_EAST_0.25   25.75 0.00 0.00 25.75 25.75 2.831 0.251 0.276             No PERIMETER_BOT_ZN_2_WALL_EAST 90.00 90.00 E
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 WINDOW_U_0.498_SHGC_SOUTH_0.25   23.18 0.00 0.00 23.18 23.18 2.831 0.251 0.276             No PERIMETER_BOT_ZN_1_WALL_SOUTH 180.00 90.00 S
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 WINDOW_U_0.498_SHGC_SOUTH_0.25   23.18 0.00 0.00 23.18 23.18 2.831 0.251 0.276             No PERIMETER_BOT_ZN_1_WALL_SOUTH 180.00 90.00 S
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 WINDOW_U_0.498_SHGC_SOUTH_0.25   23.18 0.00 0.00 23.18 23.18 2.831 0.251 0.276             No PERIMETER_BOT_ZN_1_WALL_SOUTH 180.00 90.00 S
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 WINDOW_U_0.498_SHGC_SOUTH_0.25   23.18 0.00 0.00 23.18 23.18 2.831 0.251 0.276             No PERIMETER_BOT_ZN_1_WALL_SOUTH 180.00 90.00 S
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 WINDOW_U_0.498_SHGC_SOUTH_0.25   23.18 0.00 0.00 23.18 23.18 2.831 0.251 0.276             No PERIMETER_BOT_ZN_1_WALL_SOUTH 180.00 90.00 S
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 WINDOW_U_0.498_SHGC_WEST_0.25   25.75 0.00 0.00 25.75 25.75 2.831 0.251 0.276             No PERIMETER_BOT_ZN_4_WALL_WEST 270.00 90.00 W
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 WINDOW_U_0.498_SHGC_WEST_0.25   25.75 0.00 0.00 25.75 25.75 2.831 0.251 0.276             No PERIMETER_BOT_ZN_4_WALL_WEST 270.00 90.00 W
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 WINDOW_U_0.498_SHGC_WEST_0.25   25.75 0.00 0.00 25.75 25.75 2.831 0.251 0.276             No PERIMETER_BOT_ZN_4_WALL_WEST 270.00 90.00 W
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW WINDOW_U_0.498_SHGC_NORTH_0.25   115.90 0.00 0.00 115.90 1158.95 2.831 0.251 0.276             No PERIMETER_MID_ZN_3_WALL_NORTH 0.00 90.00 N
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW WINDOW_U_0.498_SHGC_EAST_0.25   77.26 0.00 0.00 77.26 772.63 2.831 0.251 0.276             No PERIMETER_MID_ZN_2_WALL_EAST 90.00 90.00 E
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW WINDOW_U_0.498_SHGC_SOUTH_0.25   115.90 0.00 0.00 115.90 1158.95 2.831 0.251 0.276             No PERIMETER_MID_ZN_1_WALL_SOUTH 180.00 90.00 S
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW WINDOW_U_0.498_SHGC_WEST_0.25   77.26 0.00 0.00 77.26 772.63 2.831 0.251 0.276             No PERIMETER_MID_ZN_4_WALL_WEST 270.00 90.00 W
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW WINDOW_U_0.498_SHGC_NORTH_0.25   115.90 0.00 0.00 115.90 115.90 2.831 0.251 0.276             No PERIMETER_TOP_ZN_3_WALL_NORTH 0.00 90.00 N
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW WINDOW_U_0.498_SHGC_EAST_0.25   77.26 0.00 0.00 77.26 77.26 2.831 0.251 0.276             No PERIMETER_TOP_ZN_2_WALL_EAST 90.00 90.00 E
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW WINDOW_U_0.498_SHGC_SOUTH_0.25   115.90 0.00 0.00 115.90 115.90 2.831 0.251 0.276             No PERIMETER_TOP_ZN_1_WALL_SOUTH 180.00 90.00 S
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW WINDOW_U_0.498_SHGC_WEST_0.25   77.26 0.00 0.00 77.26 77.26 2.831 0.251 0.276             No PERIMETER_TOP_ZN_4_WALL_WEST 270.00 90.00 W
Total or Average             4635.80 2.831 0.251 0.276                      
North Total or Average             1390.74 2.831 0.251 0.276                      
Non-North Total or Average             3245.06 2.831 0.251 0.276                      


Exterior Fenestration Shaded State

Frame and Divider Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance NFRC Product Type Assembly U-Factor [W/m2-K] Assembly SHGC Assembly Visible Transmittance
None                


Interior Fenestration

Construction Area of One Opening [m2] Area of Openings [m2] Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance
Total or Average     0.00 - - -


Exterior Door

Construction U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Parent Surface
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 SWINGING DOOR_CON 2.492 3.975 1.95 PERIMETER_BOT_ZN_3_WALL_NORTH
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 SWINGING DOOR_CON 2.492 3.975 1.95 PERIMETER_BOT_ZN_3_WALL_NORTH
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 SWINGING DOOR_CON 2.492 3.975 1.95 PERIMETER_BOT_ZN_3_WALL_NORTH
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 SWINGING DOOR_CON 2.492 3.975 1.95 PERIMETER_BOT_ZN_3_WALL_NORTH
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 SWINGING DOOR_CON 2.492 3.975 1.95 PERIMETER_BOT_ZN_2_WALL_EAST
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 SWINGING DOOR_CON 2.492 3.975 1.95 PERIMETER_BOT_ZN_2_WALL_EAST
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 SWINGING DOOR_CON 2.492 3.975 1.95 PERIMETER_BOT_ZN_1_WALL_SOUTH
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 SWINGING DOOR_CON 2.492 3.975 1.95 PERIMETER_BOT_ZN_1_WALL_SOUTH
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 SWINGING DOOR_CON 2.492 3.975 1.95 PERIMETER_BOT_ZN_1_WALL_SOUTH
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 SWINGING DOOR_CON 2.492 3.975 1.95 PERIMETER_BOT_ZN_1_WALL_SOUTH
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 SWINGING DOOR_CON 2.492 3.975 1.95 PERIMETER_BOT_ZN_4_WALL_WEST
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 SWINGING DOOR_CON 2.492 3.975 1.95 PERIMETER_BOT_ZN_4_WALL_WEST


Interior Door

Construction U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Parent Surface
None          



Table of Contents

Report: Shading Summary

For: Entire Facility

Timestamp: 2023-10-16 08:43:24

Sunlit Fraction

March 21 9am March 21 noon March 21 3pm June 21 9am June 21 noon June 21 3pm December 21 9am December 21 noon December 21 3pm
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00


Window Control

Name Type Shaded Construction Control Glare Control
None          



Table of Contents

Report: Lighting Summary

For: Entire Facility

Timestamp: 2023-10-16 08:43:24

Interior Lighting

Zone Name Space Name Space Type Lighting Power Density [W/m2] Space Area [m2] Total Power [W] End Use Subcategory Schedule Name Scheduled Hours/Week [hr] Hours/Week > 1% [hr] Full Load Hours/Week [hr] Return Air Fraction Conditioned (Y/N) Consumption [GJ]
BASEMENT_LIGHTS BASEMENT BASEMENT GENERAL 10.2732 2779.43 28553.72 LightsWired LTG_SCH_OFFICE 50.34 168.00 49.04 0.0000 Y 262.84
CORE_BOTTOM_LIGHTS CORE_BOTTOM CORE_BOTTOM GENERAL 10.2732 2496.12 25643.24 LightsWired LTG_SCH_OFFICE 50.34 168.00 49.04 0.0000 Y 236.05
CORE_MID_LIGHTS CORE_MID CORE_MID GENERAL 10.2732 24961.20 256432.45 LightsWired LTG_SCH_OFFICE 50.34 168.00 49.04 0.0000 Y 2360.52
CORE_TOP_LIGHTS CORE_TOP CORE_TOP GENERAL 10.2732 2496.12 25643.24 LightsWired LTG_SCH_OFFICE 50.34 168.00 49.04 0.0000 Y 236.05
PERIMETER_BOT_ZN_3_LIGHTS PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3 GENERAL 10.2732 313.41 3219.77 LightsWired LTG_SCH_OFFICE 50.34 168.00 29.31 0.0000 Y 17.72
PERIMETER_BOT_ZN_2_LIGHTS PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2 GENERAL 10.2732 201.98 2074.94 LightsWired LTG_SCH_OFFICE 50.34 168.00 28.73 0.0000 Y 11.19
PERIMETER_BOT_ZN_1_LIGHTS PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1 GENERAL 10.2732 313.42 3219.84 LightsWired LTG_SCH_OFFICE 50.34 168.00 28.46 0.0000 Y 17.20
PERIMETER_BOT_ZN_4_LIGHTS PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4 GENERAL 10.2732 201.98 2074.94 LightsWired LTG_SCH_OFFICE 50.34 168.00 28.99 0.0000 Y 11.29
PERIMETER_MID_ZN_3_LIGHTS PERIMETER_MID_ZN_3 PERIMETER_MID_ZN_3 GENERAL 10.2732 3134.13 32197.65 LightsWired LTG_SCH_OFFICE 50.34 168.00 29.19 0.0000 Y 176.43
PERIMETER_MID_ZN_2_LIGHTS PERIMETER_MID_ZN_2 PERIMETER_MID_ZN_2 GENERAL 10.2732 2019.75 20749.39 LightsWired LTG_SCH_OFFICE 50.34 168.00 28.66 0.0000 Y 111.63
PERIMETER_MID_ZN_1_LIGHTS PERIMETER_MID_ZN_1 PERIMETER_MID_ZN_1 GENERAL 10.2732 3134.20 32198.36 LightsWired LTG_SCH_OFFICE 50.34 168.00 28.41 0.0000 Y 171.73
PERIMETER_MID_ZN_4_LIGHTS PERIMETER_MID_ZN_4 PERIMETER_MID_ZN_4 GENERAL 10.2732 2019.75 20749.39 LightsWired LTG_SCH_OFFICE 50.34 168.00 28.91 0.0000 Y 112.59
PERIMETER_TOP_ZN_3_LIGHTS PERIMETER_TOP_ZN_3 PERIMETER_TOP_ZN_3 GENERAL 10.2732 313.41 3219.77 LightsWired LTG_SCH_OFFICE 50.34 168.00 29.19 0.0000 Y 17.64
PERIMETER_TOP_ZN_2_LIGHTS PERIMETER_TOP_ZN_2 PERIMETER_TOP_ZN_2 GENERAL 10.2732 201.98 2074.94 LightsWired LTG_SCH_OFFICE 50.34 168.00 28.66 0.0000 Y 11.16
PERIMETER_TOP_ZN_1_LIGHTS PERIMETER_TOP_ZN_1 PERIMETER_TOP_ZN_1 GENERAL 10.2732 313.42 3219.84 LightsWired LTG_SCH_OFFICE 50.34 168.00 28.41 0.0000 Y 17.17
PERIMETER_TOP_ZN_4_LIGHTS PERIMETER_TOP_ZN_4 PERIMETER_TOP_ZN_4 GENERAL 10.2732 201.98 2074.94 LightsWired LTG_SCH_OFFICE 50.34 168.00 28.90 0.0000 Y 11.26
DATACENTER_BASEMENT_LIGHTS DATACENTER_BASEMENT_ZN_6 DATACENTER_BASEMENT_ZN_6 GENERAL 10.2732 783.68 8050.93 LightsWired LTG_SCH_OFFICE 50.34 168.00 49.04 0.0000 Y 74.11
DATACENTER_BOT_LIGHTS DATACENTER_BOT_ZN_6 DATACENTER_BOT_ZN_6 GENERAL 17.8735 36.20 647.07 LightsWired LTG_SCH_DATACENTER 56.02 168.00 54.57 0.0000 Y 6.63
DATACENTER_MID_LIGHTS DATACENTER_MID_ZN_6 DATACENTER_MID_ZN_6 GENERAL 17.8735 362.03 6470.68 LightsWired LTG_SCH_DATACENTER 56.02 168.00 54.57 0.0000 Y 66.28
DATACENTER_TOP_LIGHTS DATACENTER_TOP_ZN_6 DATACENTER_TOP_ZN_6 GENERAL 17.8735 36.20 647.07 LightsWired LTG_SCH_DATACENTER 56.02 168.00 54.57 0.0000 Y 6.63
Interior Lighting Total       10.3445 46320.38 479162.15               1236.86


Daylighting

Zone Control Name Daylighting Method Control Type Fraction Controlled Lighting Installed in Zone [W] Lighting Controlled [W]
PERIMETER_BOT_ZN_1_DAYLREFPT1 PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_DAYLCTRL SplitFlux Stepped 0.39 3219.84 1241.89
PERIMETER_BOT_ZN_1_DAYLREFPT2 PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_DAYLCTRL SplitFlux Stepped 0.14 3219.84 445.95
PERIMETER_BOT_ZN_2_DAYLREFPT1 PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_DAYLCTRL SplitFlux Stepped 0.39 2074.94 800.30
PERIMETER_BOT_ZN_2_DAYLREFPT2 PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_DAYLCTRL SplitFlux Stepped 0.14 2074.94 287.38
PERIMETER_BOT_ZN_3_DAYLREFPT1 PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_DAYLCTRL SplitFlux Stepped 0.39 3219.77 1241.86
PERIMETER_BOT_ZN_3_DAYLREFPT2 PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_DAYLCTRL SplitFlux Stepped 0.14 3219.77 445.94
PERIMETER_BOT_ZN_4_DAYLREFPT1 PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_DAYLCTRL SplitFlux Stepped 0.39 2074.94 800.30
PERIMETER_BOT_ZN_4_DAYLREFPT2 PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_DAYLCTRL SplitFlux Stepped 0.14 2074.94 287.38
PERIMETER_MID_ZN_1_DAYLREFPT1 PERIMETER_MID_ZN_1 PERIMETER_MID_ZN_1_DAYLCTRL SplitFlux Stepped 0.39 3219.84 1241.89
PERIMETER_MID_ZN_1_DAYLREFPT2 PERIMETER_MID_ZN_1 PERIMETER_MID_ZN_1_DAYLCTRL SplitFlux Stepped 0.14 3219.84 445.95
PERIMETER_MID_ZN_2_DAYLREFPT1 PERIMETER_MID_ZN_2 PERIMETER_MID_ZN_2_DAYLCTRL SplitFlux Stepped 0.39 2074.94 800.30
PERIMETER_MID_ZN_2_DAYLREFPT2 PERIMETER_MID_ZN_2 PERIMETER_MID_ZN_2_DAYLCTRL SplitFlux Stepped 0.14 2074.94 287.38
PERIMETER_MID_ZN_3_DAYLREFPT1 PERIMETER_MID_ZN_3 PERIMETER_MID_ZN_3_DAYLCTRL SplitFlux Stepped 0.39 3219.77 1241.86
PERIMETER_MID_ZN_3_DAYLREFPT2 PERIMETER_MID_ZN_3 PERIMETER_MID_ZN_3_DAYLCTRL SplitFlux Stepped 0.14 3219.77 445.94
PERIMETER_MID_ZN_4_DAYLREFPT1 PERIMETER_MID_ZN_4 PERIMETER_MID_ZN_4_DAYLCTRL SplitFlux Stepped 0.39 2074.94 800.30
PERIMETER_MID_ZN_4_DAYLREFPT2 PERIMETER_MID_ZN_4 PERIMETER_MID_ZN_4_DAYLCTRL SplitFlux Stepped 0.14 2074.94 287.38
PERIMETER_TOP_ZN_1_DAYLREFPT1 PERIMETER_TOP_ZN_1 PERIMETER_TOP_ZN_1_DAYLCTRL SplitFlux Stepped 0.39 3219.84 1241.89
PERIMETER_TOP_ZN_1_DAYLREFPT2 PERIMETER_TOP_ZN_1 PERIMETER_TOP_ZN_1_DAYLCTRL SplitFlux Stepped 0.14 3219.84 445.95
PERIMETER_TOP_ZN_2_DAYLREFPT1 PERIMETER_TOP_ZN_2 PERIMETER_TOP_ZN_2_DAYLCTRL SplitFlux Stepped 0.39 2074.94 800.30
PERIMETER_TOP_ZN_2_DAYLREFPT2 PERIMETER_TOP_ZN_2 PERIMETER_TOP_ZN_2_DAYLCTRL SplitFlux Stepped 0.14 2074.94 287.38
PERIMETER_TOP_ZN_3_DAYLREFPT1 PERIMETER_TOP_ZN_3 PERIMETER_TOP_ZN_3_DAYLCTRL SplitFlux Stepped 0.39 3219.77 1241.86
PERIMETER_TOP_ZN_3_DAYLREFPT2 PERIMETER_TOP_ZN_3 PERIMETER_TOP_ZN_3_DAYLCTRL SplitFlux Stepped 0.14 3219.77 445.94
PERIMETER_TOP_ZN_4_DAYLREFPT1 PERIMETER_TOP_ZN_4 PERIMETER_TOP_ZN_4_DAYLCTRL SplitFlux Stepped 0.39 2074.94 800.30
PERIMETER_TOP_ZN_4_DAYLREFPT2 PERIMETER_TOP_ZN_4 PERIMETER_TOP_ZN_4_DAYLCTRL SplitFlux Stepped 0.14 2074.94 287.38


Exterior Lighting

Total Watts Astronomical Clock/Schedule Schedule Name Scheduled Hours/Week [hr] Hours/Week > 1% [hr] Full Load Hours/Week [hr] Consumption [GJ]
EXTERIOR_LIGHTS_A 13279.00 AstronomicalClock -   41.77 41.77 104.12
EXTERIOR_LIGHTS_B 44301.60 AstronomicalClock -   83.77 71.17 591.85
Exterior Lighting Total 57580.60           695.97



Table of Contents

Report: Equipment Summary

For: Entire Facility

Timestamp: 2023-10-16 08:43:24

Central Plant

Type Reference Capacity [W] Reference Efficiency [W/W] Rated Capacity [W] Rated Efficiency [W/W] IPLV in SI Units [W/W] IPLV in IP Units [Btu/W-h]
BYPASS HEAT EXCHANGER HeatExchanger:FluidToFluid 2958058.23          
HEATSYS1 BOILER Boiler:HotWater 2469248.63 0.81        
COOLSYS1 CHILLER1 Chiller:Electric:ReformulatedEIR 1507316.17 6.28 1442696.66 5.98 6.84 23.33
COOLSYS1 CHILLER2 Chiller:Electric:ReformulatedEIR 1507316.17 6.28 1442696.66 5.98 6.84 23.33
CENTRAL TOWER FluidCooler:TwoSpeed 582060.00          
CENTRAL BOILER Boiler:HotWater 543970.57 0.80        
TOWERWATERSYS COOLTOWER 1 CoolingTower:VariableSpeed 1788404.52          
TOWERWATERSYS COOLTOWER 2 CoolingTower:VariableSpeed 1788404.52          


Cooling Coils

Type Design Coil Load [W] Nominal Total Capacity [W] Nominal Sensible Capacity [W] Nominal Latent Capacity [W] Nominal Sensible Heat Ratio Nominal Efficiency [W/W] Nominal Coil UA Value [W/C] Nominal Coil Surface Area [m2]
VAV_BOT WITH REHEAT COOLING COIL Coil:Cooling:Water 242286.81 266205.00 177631.86 88573.14 0.67 - 28251.46 286.54
VAV_MID WITH REHEAT COOLING COIL Coil:Cooling:Water 2354776.15 2524490.77 1676090.29 848400.47 0.66 - 268406.63 2722.33
VAV_TOP WITH REHEAT COOLING COIL Coil:Cooling:Water 243642.38 268814.03 179507.15 89306.88 0.67 - 28536.96 289.44
CAV_BAS COOLING COIL Coil:Cooling:Water 124171.22 149077.94 101882.01 47195.93 0.68 - 15614.12 158.37
AIRLOOP DATACENTER BASEMENT COOLING COIL Coil:Cooling:WaterToAirHeatPump:EquationFit   438414.06 303822.62 134591.44 0.69 0.00    
AIRLOOP DATACENTER BOT COOLING COIL Coil:Cooling:WaterToAirHeatPump:EquationFit   9691.18 6727.91 2963.28 0.69 0.00    
AIRLOOP DATACENTER MID COOLING COIL Coil:Cooling:WaterToAirHeatPump:EquationFit   92549.83 64188.78 28361.05 0.69 0.00    
AIRLOOP DATACENTER TOP COOLING COIL Coil:Cooling:WaterToAirHeatPump:EquationFit   9422.96 6537.25 2885.71 0.69 0.00    
Nominal values are gross at rated conditions, i.e., the supply air fan heat and electric power NOT accounted for.

DX Cooling Coils

DX Cooling Coil Type Standard Rated Net Cooling Capacity [W] Standard Rated Net COP [W/W] EER [Btu/W-h] SEER User [Btu/W-h] SEER Standard [Btu/W-h] IEER [Btu/W-h]
None              


DX Cooling Coil ASHRAE 127 Standard Ratings Report

DX Cooling Coil Type Rated Net Cooling Capacity Test A [W] Rated Electric Power Test A [W] Rated Net Cooling Capacity Test B [W] Rated Electric Power Test B [W] Rated Net Cooling Capacity Test C [W] Rated Electric Power Test C [W] Rated Net Cooling Capacity Test D [W] Rated Electric Power Test D [W]
None                  


DX Heating Coils

DX Heating Coil Type High Temperature Heating (net) Rating Capacity [W] Low Temperature Heating (net) Rating Capacity [W] HSPF [Btu/W-h] Region Number
None          


Heating Coils

Type Design Coil Load [W] Nominal Total Capacity [W] Nominal Efficiency [W/W]
CORE_BOTTOM VAV BOX REHEAT COIL Coil:Heating:Water 18977.52 17994.89 -
CORE_MID VAV BOX REHEAT COIL Coil:Heating:Water 462014.40 437729.20 -
CORE_TOP VAV BOX REHEAT COIL Coil:Heating:Water 86090.02 81585.54 -
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL Coil:Heating:Water 14939.37 14155.92 -
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL Coil:Heating:Water 10215.85 9680.00 -
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL Coil:Heating:Water 16574.76 15705.28 -
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL Coil:Heating:Water 8286.08 7847.78 -
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL Coil:Heating:Water 245103.78 232226.85 -
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL Coil:Heating:Water 160408.20 151980.47 -
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL Coil:Heating:Water 241668.01 228972.03 -
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL Coil:Heating:Water 155852.35 147664.46 -
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL Coil:Heating:Water 30720.05 29105.23 -
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL Coil:Heating:Water 20042.61 18989.02 -
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL Coil:Heating:Water 30353.83 28758.30 -
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL Coil:Heating:Water 19757.34 18718.76 -
VAV_BOT WITH REHEAT HEATING COIL Coil:Heating:Water 56839.85 43740.55 -
VAV_MID WITH REHEAT HEATING COIL Coil:Heating:Water 544940.17 417202.15 -
VAV_TOP WITH REHEAT HEATING COIL Coil:Heating:Water 53637.39 41806.40 -
CAV_BAS HEATING COIL Coil:Heating:Water 292827.06 231340.80 -
AIRLOOP DATACENTER BASEMENT HEATING COIL Coil:Heating:WaterToAirHeatPump:EquationFit   438414.06 0.00
AIRLOOP DATACENTER BOT HEATING COIL Coil:Heating:WaterToAirHeatPump:EquationFit   9691.18 0.00
AIRLOOP DATACENTER MID HEATING COIL Coil:Heating:WaterToAirHeatPump:EquationFit   92549.83 0.00
AIRLOOP DATACENTER TOP HEATING COIL Coil:Heating:WaterToAirHeatPump:EquationFit   9422.96 0.00
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL Coil:Heating:Electric   18278.08 1.00
AIRLOOP DATACENTER BOT_SUPPHEATCOIL Coil:Heating:Electric   844.37 1.00
AIRLOOP DATACENTER MID_SUPPHEATCOIL Coil:Heating:Electric   8443.71 1.00
AIRLOOP DATACENTER TOP_SUPPHEATCOIL Coil:Heating:Electric   844.37 1.00
Nominal values are gross at rated conditions, i.e., the supply air fan heat and electric power NOT accounted for.

Fans

Type Total Efficiency [W/W] Delta Pressure [pa] Max Air Flow Rate [m3/s] Rated Electricity Rate [W] Rated Power Per Max Air Flow Rate [W-s/m3] Motor Heat In Air Fraction Fan Energy Index End Use Subcategory Design Day Name for Fan Sizing Peak Date/Time for Fan Sizing Peak
VAV_BOT WITH REHEAT FAN Fan:VariableVolume 0.61 1314.72 10.08 21657.98 2149.46 1.00 1.12 General ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00
VAV_MID WITH REHEAT FAN Fan:VariableVolume 0.61 1314.72 94.04 203206.86 2160.95 1.00 1.08 General ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00
VAV_TOP WITH REHEAT FAN Fan:VariableVolume 0.61 1314.72 10.20 21920.02 2149.46 1.00 1.12 General ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:50:00
CAV_BAS FAN Fan:ConstantVolume 0.60 1018.41 6.09 10319.93 1695.65 1.00 1.15 General ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00
AIRLOOP DATACENTER BASEMENT SUPPLY FAN Fan:OnOff 0.62 1018.41 22.14 36508.66 1649.25 1.00 1.14 General ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 07:10:00
AIRLOOP DATACENTER BOT SUPPLY FAN Fan:OnOff 0.56 622.50 0.49 551.27 1120.11 1.00 1.61 General ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00
AIRLOOP DATACENTER MID SUPPLY FAN Fan:OnOff 0.56 622.50 4.69 5255.32 1120.11 1.00 1.16 General ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00
AIRLOOP DATACENTER TOP SUPPLY FAN Fan:OnOff 0.56 622.50 0.48 535.34 1120.11 1.00 1.63 General ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00


Pumps

Type Control Head [pa] Water Flow [m3/s] Electricity Rate [W] Power Per Water Flow Rate [W-s/m3] Motor Efficiency [W/W] End Use Subcategory
COOLSYS1 PUMP SECONDARY Pump:VariableSpeed Intermittent 105797.75 0.126133 20593.62 163269.45 0.90 General
HEATSYS1 PUMP Pump:VariableSpeed Intermittent 180705.70 0.021602 6505.59 301156.09 0.90 General
COOLSYS1 CHILLER1 PUMP Pump:ConstantSpeed Intermittent 73247.35 0.063066 7128.83 113036.94 0.90 General
COOLSYS1 CHILLER2 PUMP Pump:ConstantSpeed Intermittent 73247.35 0.063066 7128.83 113036.94 0.90 General
PLANT CIRC PUMP Pump:ConstantSpeed Intermittent 179045.11 0.013471 3435.87 255050.01 0.90 General
SWHSYS1 PUMP Pump:ConstantSpeed Intermittent 29891.00 0.000440 56.21 127739.32 0.30 General
TOWERWATERSYS PUMP HeaderedPumps:VariableSpeed Intermittent 148556.62 0.149183 36934.41 247577.87 0.90 General


Service Water Heating

Type Storage Volume [m3] Input [W] Thermal Efficiency [W/W] Recovery Efficiency [W/W] Energy Factor
SWHSYS1 WATER HEATER WaterHeater:Mixed 1.14 87921.32 0.80 0.48 0.06



Table of Contents

Report: HVAC Sizing Summary

For: Entire Facility

Timestamp: 2023-10-16 08:43:24

Zone Sensible Cooling

Calculated Design Load [W] User Design Load [W] User Design Load per Area [W/m2] Calculated Design Air Flow [m3/s] User Design Air Flow [m3/s] Design Day Name Date/Time Of Peak {TIMESTAMP} Thermostat Setpoint Temperature at Peak Load [C] Indoor Temperature at Peak Load [C] Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] Outdoor Temperature at Peak Load [C] Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] Minimum Outdoor Air Flow Rate [m3/s] Heat Gain Rate from DOAS [W]
BASEMENT 81476.80 81476.80 29.31 6.086 6.086 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 24.00 24.00 0.00893 27.37 0.01446 1.200 0.00
CORE_BOTTOM 84977.65 84977.65 34.04 6.347 6.347 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 24.00 24.00 0.00887 27.37 0.01446 1.078 0.00
CORE_MID 803073.62 803073.62 321.73 59.969 59.969 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 24.00 24.00 0.00889 27.37 0.01446 10.778 0.00
CORE_TOP 79160.97 79160.97 31.71 5.911 5.911 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 24.00 24.00 0.00889 27.37 0.01446 1.078 0.00
PERIMETER_BOT_ZN_3 14184.53 14184.53 45.26 1.069 1.069 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:50:00 24.00 24.00 0.00889 34.40 0.01447 0.135 0.00
PERIMETER_BOT_ZN_2 14680.44 14680.44 72.68 1.106 1.106 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 09:50:00 24.00 24.00 0.00874 30.52 0.01447 0.087 0.00
PERIMETER_BOT_ZN_1 16633.14 16633.14 53.07 1.253 1.253 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 13:40:00 24.00 24.00 0.00883 34.24 0.01447 0.135 0.00
PERIMETER_BOT_ZN_4 18514.74 18514.74 91.67 1.395 1.395 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 17:10:00 24.00 24.00 0.00869 32.91 0.01447 0.087 0.00
PERIMETER_MID_ZN_3 134507.15 134507.15 429.17 10.137 10.137 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 24.00 24.00 0.00906 34.40 0.01447 1.353 0.00
PERIMETER_MID_ZN_2 151996.02 151996.02 752.55 11.455 11.455 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 10:00:00 24.00 24.00 0.00883 30.79 0.01447 0.872 0.00
PERIMETER_MID_ZN_1 158866.11 158866.11 506.88 11.973 11.973 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 13:50:00 24.00 24.00 0.00898 34.32 0.01447 1.353 0.00
PERIMETER_MID_ZN_4 161161.07 161161.07 797.93 12.146 12.146 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 17:20:00 24.00 24.00 0.00881 32.75 0.01447 0.872 0.00
PERIMETER_TOP_ZN_3 15153.30 15153.30 48.35 1.142 1.142 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:20:00 24.00 24.00 0.00906 34.21 0.01447 0.135 0.00
PERIMETER_TOP_ZN_2 15453.40 15453.40 76.51 1.165 1.165 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 10:10:00 24.00 24.00 0.00887 31.03 0.01447 0.087 0.00
PERIMETER_TOP_ZN_1 17468.40 17468.40 55.73 1.317 1.317 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:10:00 24.00 24.00 0.00899 34.40 0.01447 0.135 0.00
PERIMETER_TOP_ZN_4 17221.07 17221.07 85.26 1.298 1.298 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 17:20:00 24.00 24.00 0.00883 32.75 0.01447 0.087 0.00
DATACENTER_BOT_ZN_6 8280.16 8280.16 228.72 0.492 0.492 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 19:10:00 27.00 27.00 0.00859 30.52 0.01447 0.016 0.00
DATACENTER_MID_ZN_6 78935.52 78935.52 2180.37 4.692 4.692 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 19:10:00 27.00 27.00 0.00859 30.52 0.01447 0.156 0.00
DATACENTER_TOP_ZN_6 8040.96 8040.96 222.11 0.478 0.478 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 19:00:00 27.00 27.00 0.00859 30.70 0.01447 0.016 0.00
DATACENTER_BASEMENT_ZN_6 372434.49 372434.49 475.24 22.136 22.136 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 07:00:00 27.00 27.00 0.00854 25.75 0.01446 0.338 0.00
The Design Load is the zone sensible load only. It does not include any system effects or ventilation loads.

Zone Sensible Heating

Calculated Design Load [W] User Design Load [W] User Design Load per Area [W/m2] Calculated Design Air Flow [m3/s] User Design Air Flow [m3/s] Design Day Name Date/Time Of Peak {TIMESTAMP} Thermostat Setpoint Temperature at Peak Load [C] Indoor Temperature at Peak Load [C] Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] Outdoor Temperature at Peak Load [C] Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] Minimum Outdoor Air Flow Rate [m3/s] Heat Gain Rate from DOAS [W]
BASEMENT 0.00 0.00 0.00 0.000 1.200 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:10:00 21.00 23.37 0.00230 -6.30 0.00230 1.200 0.00
CORE_BOTTOM 0.00 0.00 0.00 0.000 1.078 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 05:50:00 17.60 21.00 0.00230 -6.30 0.00230 1.078 0.00
CORE_MID 275723.61 275723.61 110.46 12.058 12.058 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00800 -6.30 0.00230 10.778 0.00
CORE_TOP 60293.17 60293.17 24.15 2.657 2.657 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00800 -6.30 0.00230 1.078 0.00
PERIMETER_BOT_ZN_3 10461.88 10461.88 33.38 0.462 0.462 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00744 -6.30 0.00230 0.135 0.00
PERIMETER_BOT_ZN_2 7153.34 7153.34 35.42 0.316 0.316 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00748 -6.30 0.00230 0.087 0.00
PERIMETER_BOT_ZN_1 11605.05 11605.05 37.03 0.512 0.512 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00754 -6.30 0.00230 0.135 0.00
PERIMETER_BOT_ZN_4 5582.08 5582.08 27.64 0.246 0.246 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00716 -6.30 0.00230 0.087 0.00
PERIMETER_MID_ZN_3 171564.20 171564.20 547.41 7.586 7.586 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00744 -6.30 0.00230 1.353 0.00
PERIMETER_MID_ZN_2 112279.75 112279.75 555.91 4.965 4.965 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00743 -6.30 0.00230 0.872 0.00
PERIMETER_MID_ZN_1 169162.05 169162.05 539.73 7.479 7.479 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00743 -6.30 0.00230 1.353 0.00
PERIMETER_MID_ZN_4 109094.23 109094.23 540.14 4.823 4.823 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00741 -6.30 0.00230 0.872 0.00
PERIMETER_TOP_ZN_3 21499.99 21499.99 68.60 0.951 0.951 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00745 -6.30 0.00230 0.135 0.00
PERIMETER_TOP_ZN_2 14027.22 14027.22 69.45 0.621 0.621 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00744 -6.30 0.00230 0.087 0.00
PERIMETER_TOP_ZN_1 21243.92 21243.92 67.78 0.940 0.940 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00744 -6.30 0.00230 0.135 0.00
PERIMETER_TOP_ZN_4 13827.72 13827.72 68.46 0.612 0.612 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00743 -6.30 0.00230 0.087 0.00
DATACENTER_BOT_ZN_6 0.00 0.00 0.00 0.000 0.016 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 05:40:00 18.00 25.30 0.00733 -6.30 0.00230 0.016 0.00
DATACENTER_MID_ZN_6 0.00 0.00 0.00 0.000 0.156 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 05:40:00 18.00 22.84 0.00276 -6.30 0.00230 0.156 0.00
DATACENTER_TOP_ZN_6 0.00 0.00 0.00 0.000 0.016 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 05:40:00 18.00 21.01 0.00276 -6.30 0.00230 0.016 0.00
DATACENTER_BASEMENT_ZN_6 0.00 0.00 0.00 0.000 0.338 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 00:50:00 18.00 27.00 0.00850 -6.30 0.00230 0.338 0.00
The Design Load is the zone sensible load only. It does not include any system effects or ventilation loads.

System Design Air Flow Rates

Calculated cooling [m3/s] User cooling [m3/s] Calculated heating [m3/s] User heating [m3/s] Adjusted cooling [m3/s] Adjusted heating [m3/s] Adjusted main [m3/s] Calculated Heating Air Flow Ratio [] User Heating Air Flow Ratio []
VAV_BOT WITH REHEAT 10.08 10.08 2.61 2.61 10.0760 2.9518 10.0760 0.2930 0.3000
VAV_MID WITH REHEAT 94.04 94.04 36.91 36.91 94.0360 36.9114 94.0360 0.3925 0.3000
VAV_TOP WITH REHEAT 10.20 10.20 5.78 5.78 10.1979 5.7804 10.1979 0.5668 0.3000
CAV_BAS 6.09 6.09 1.20 1.20 6.0861 6.0861 6.0861 1.0000 1.0000
AIRLOOP DATACENTER BASEMENT 22.14 22.14 0.34 0.34 22.1366 22.1364 22.1366 1.0000 1.0000
AIRLOOP DATACENTER BOT 0.49 0.49 0.02 0.02 0.4922 0.4922 0.4922 1.0000 1.0000
AIRLOOP DATACENTER MID 4.69 4.69 0.16 0.16 4.6918 4.6918 4.6918 1.0000 1.0000
AIRLOOP DATACENTER TOP 0.48 0.48 0.02 0.02 0.4779 0.4779 0.4779 1.0000 1.0000


Plant Loop Coincident Design Fluid Flow Rate Adjustments

Previous Design Volume Flow Rate [m3/s] Algorithm Volume Flow Rate [m3/s] Coincident Design Volume Flow Rate [m3/s] Coincident Size Adjusted Peak Sizing Period Name Peak Day into Period {TIMESTAMP}[day] Peak Hour Of Day {TIMESTAMP}[hr] Peak Step Start Minute {TIMESTAMP}[min]
None                


Coil Sizing Summary

Coil Type HVAC Type HVAC Name Coil Final Gross Total Capacity [W] Coil Final Gross Sensible Capacity [W] Coil Final Reference Air Volume Flow Rate [m3/s] Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] Coil U-value Times Area Value [W/K] Design Day Name at Sensible Ideal Loads Peak Date/Time at Sensible Ideal Loads Peak Design Day Name at Air Flow Ideal Loads Peak Date/Time at Air Flow Ideal Loads Peak Coil Total Capacity at Ideal Loads Peak [W] Coil Sensible Capacity at Ideal Loads Peak [W] Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] Coil Entering Air Drybulb at Ideal Loads Peak [C] Coil Entering Air Wetbulb at Ideal Loads Peak [C] Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Coil Leaving Air Drybulb at Ideal Loads Peak [C] Coil Leaving Air Wetbulb at Ideal Loads Peak [C] Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Outdoor Air Drybulb at Ideal Loads Peak [C] Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Outdoor Air Wetbulb at Ideal Loads Peak [C] Outdoor Air Flow Percentage at Ideal Loads Peak [%] Zone Air Drybulb at Ideal Loads Peak [C] Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Zone Air Relative Humidity at Ideal Loads Peak [%] Zone Sensible Heat Gain at Ideal Loads Peak [W] Zone Latent Heat Gain at Ideal Loads Peak [W] Coil Total Capacity at Rating Conditions [W] Coil Sensible Capacity at Rating Conditions [W]
CORE_BOTTOM VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT CORE_BOTTOM VAV BOX 18977.523 18977.523 1.954901 0.00016602 382.572 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 05:50:00 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 05:50:00 18977.52 18977.52 1.954901 12.80 11.27 0.00800000 40.00 20.76 0.00800000 -6.30 0.00229779 -6.30 0.0000 21.00 0.00800000 49.8624 0.00 0.00 19047.50 19047.50
CORE_MID VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT CORE_MID VAV BOX 462014.397 462014.397 19.190077 0.00404190 10929.409 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 462014.40 462014.40 19.190077 12.80 11.27 0.00800000 40.00 20.76 0.00800000 -6.30 0.00229779 -6.30 0.0000 21.00 0.00800000 49.8624 275723.61 0.00 463523.39 463523.39
CORE_TOP VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT CORE_TOP VAV BOX 86090.017 86090.017 2.657370 0.00075315 2272.772 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 86090.02 86090.02 2.657370 12.80 11.27 0.00800000 40.00 20.76 0.00800000 -6.30 0.00229779 -6.30 0.0000 21.00 0.00800000 49.8624 60293.17 0.00 86389.37 86389.37
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_BOT_ZN_3 VAV BOX 14939.369 14939.369 0.461816 0.00013070 394.133 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 14939.37 14939.37 0.461816 12.80 11.27 0.00800000 40.00 20.76 0.00800000 -6.30 0.00229779 -6.30 0.0000 21.00 0.00743951 46.4159 10461.88 0.00 14989.41 14989.41
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_BOT_ZN_2 VAV BOX 10215.847 10215.847 0.315843 0.00008937 269.500 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 10215.85 10215.85 0.315843 12.80 11.27 0.00800000 40.00 20.76 0.00800000 -6.30 0.00229779 -6.30 0.0000 21.00 0.00748356 46.6872 7153.34 0.00 10249.95 10249.95
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_BOT_ZN_1 VAV BOX 16574.759 16574.759 0.512475 0.00014500 437.238 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 16574.76 16574.76 0.512475 12.80 11.27 0.00800000 40.00 20.76 0.00800000 -6.30 0.00229779 -6.30 0.0000 21.00 0.00753960 47.0321 11605.05 0.00 16629.99 16629.99
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_BOT_ZN_4 VAV BOX 8286.083 8286.083 0.279056 0.00007249 210.739 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 8286.08 8286.08 0.279056 12.80 11.27 0.00800000 40.00 20.76 0.00800000 -6.30 0.00229779 -6.30 0.0000 21.00 0.00716250 44.7088 5582.08 0.00 8311.68 8311.68
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_MID_ZN_3 VAV BOX 245103.783 245103.783 7.585691 0.00214427 6462.915 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 245103.78 245103.78 7.585691 12.80 11.27 0.00800000 40.00 20.76 0.00800000 -6.30 0.00229779 -6.30 0.0000 21.00 0.00743552 46.3933 171564.20 0.00 245899.87 245899.87
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_MID_ZN_2 VAV BOX 160408.196 160408.196 4.964616 0.00140332 4229.593 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 160408.20 160408.20 4.964616 12.80 11.27 0.00800000 40.00 20.76 0.00800000 -6.30 0.00229779 -6.30 0.0000 21.00 0.00742697 46.3408 112279.75 0.00 160928.75 160928.75
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_MID_ZN_1 VAV BOX 241668.014 241668.014 7.479186 0.00211422 6372.387 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 241668.01 241668.01 7.479186 12.80 11.27 0.00800000 40.00 20.76 0.00800000 -6.30 0.00229779 -6.30 0.0000 21.00 0.00742756 46.3442 169162.05 0.00 242453.43 242453.43
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_MID_ZN_4 VAV BOX 155852.349 155852.349 4.823429 0.00136346 4109.537 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 155852.35 155852.35 4.823429 12.80 11.27 0.00800000 40.00 20.76 0.00800000 -6.30 0.00229779 -6.30 0.0000 21.00 0.00741025 46.2378 109094.23 0.00 156358.63 156358.63
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_TOP_ZN_3 VAV BOX 30720.046 30720.046 0.951089 0.00026875 809.897 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 30720.05 30720.05 0.951089 12.80 11.27 0.00800000 40.00 20.76 0.00800000 -6.30 0.00229779 -6.30 0.0000 21.00 0.00744711 46.4659 21499.99 0.00 30818.88 30818.88
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_TOP_ZN_2 VAV BOX 20042.609 20042.609 0.620532 0.00017534 528.394 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 20042.61 20042.61 0.620532 12.80 11.27 0.00800000 40.00 20.76 0.00800000 -6.30 0.00229779 -6.30 0.0000 21.00 0.00743631 46.3996 14027.22 0.00 20107.05 20107.05
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_TOP_ZN_1 VAV BOX 30353.829 30353.829 0.939737 0.00026555 800.248 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 30353.83 30353.83 0.939737 12.80 11.27 0.00800000 40.00 20.76 0.00800000 -6.30 0.00229779 -6.30 0.0000 21.00 0.00744096 46.4280 21243.92 0.00 30451.52 30451.52
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_TOP_ZN_4 VAV BOX 19757.339 19757.339 0.611693 0.00017285 520.875 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 19757.34 19757.34 0.611693 12.80 11.27 0.00800000 40.00 20.76 0.00800000 -6.30 0.00229779 -6.30 0.0000 21.00 0.00742897 46.3544 13827.72 0.00 19820.88 19820.88
VAV_BOT WITH REHEAT COOLING COIL Coil:Cooling:Water AirLoopHVAC VAV_BOT WITH REHEAT 242286.813 -999.000 10.075991 0.01030744 -999.000 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 242286.81 187471.49 10.075991 26.71 18.41 0.01033215 10.99 10.99 0.00850000 34.40 0.01447326 23.54 25.1905 24.00 0.00887462 46.0359 129374.30 0.00 248147.72 182657.25
VAV_BOT WITH REHEAT HEATING COIL Coil:Heating:Water AirLoopHVAC VAV_BOT WITH REHEAT 56839.848 56839.848 3.022797 0.00049726 935.402 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 56839.85 56839.85 3.022797 -3.32 -3.62 0.00278205 12.80 11.27 0.00800000 -6.30 0.00229779 -6.30 83.9683 21.02 0.00601079 37.5427 34802.34 0.00 52916.40 52916.40
VAV_MID WITH REHEAT COOLING COIL Coil:Cooling:Water AirLoopHVAC VAV_MID WITH REHEAT 2354776.150 -999.000 94.036032 0.10017762 -999.000 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 2354776.15 1781328.00 94.036032 26.99 18.67 0.01055269 10.98 10.98 0.00850000 34.40 0.01447326 23.54 26.9917 24.00 0.00897329 46.5413 1172846.59 0.00 2410437.32 1739582.96
VAV_MID WITH REHEAT HEATING COIL Coil:Heating:Water AirLoopHVAC VAV_MID WITH REHEAT 544940.174 544940.174 28.210810 0.00476737 8945.378 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 06:20:00 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 544940.17 544940.17 28.210810 -3.76 -3.83 0.00281427 12.80 11.27 0.00800000 -6.30 0.00229779 -6.30 89.9724 19.60 0.00713138 48.5308 411160.19 0.00 504716.89 504716.89
VAV_TOP WITH REHEAT COOLING COIL Coil:Cooling:Water AirLoopHVAC VAV_TOP WITH REHEAT 243642.385 -999.000 10.197899 0.01036511 -999.000 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:50:00 243642.38 188481.55 10.197899 26.60 18.37 0.01032177 10.99 10.99 0.00850000 34.40 0.01447326 23.54 24.8893 24.00 0.00893533 46.3474 134529.52 0.00 249559.29 183599.75
VAV_TOP WITH REHEAT HEATING COIL Coil:Heating:Water AirLoopHVAC VAV_TOP WITH REHEAT 53637.388 53637.388 3.059370 0.00046924 888.202 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 05:40:00 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 53637.39 53637.39 3.059370 -2.23 -2.37 0.00316307 12.80 11.27 0.00800000 -6.30 0.00229779 -6.30 82.9645 17.60 0.00716335 55.2617 51870.08 0.00 50582.92 50582.92
CAV_BAS COOLING COIL Coil:Cooling:Water AirLoopHVAC CAV_BAS 124171.224 -999.000 6.086107 0.00528253 -999.000 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 08:20:00 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 124171.22 97239.51 6.086107 24.79 17.54 0.01002476 11.37 11.18 0.00850000 27.97 0.01446155 21.78 19.7196 24.00 0.00892815 46.3094 80359.54 0.00 127479.11 94773.08
CAV_BAS HEATING COIL Coil:Heating:Water AirLoopHVAC CAV_BAS 292827.055 292827.055 6.086107 0.00256178 6501.963 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 292827.06 292827.06 6.086107 -1.24 -3.20 0.00229779 40.00 20.76 0.00800000 -6.30 0.00229779 -6.30 19.7196 23.47 0.00229779 12.4368 0.00 0.00 244374.09 244374.09
AIRLOOP DATACENTER BASEMENT COOLING COIL COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoopHVAC AIRLOOP DATACENTER BASEMENT 438414.063 303822.623 22.136565 0.01073673 -999.000 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:00:00 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 07:10:00 406380.19 398800.54 -999.0 28.56 17.68 0.00863298 12.80 11.77 0.00850000 34.40 0.01447326 23.54 -999.0000 27.00 0.00854220 37.1020 371935.50 0.00 -999.00 -999.00
AIRLOOP DATACENTER BOT COOLING COIL COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoopHVAC AIRLOOP DATACENTER BOT 9691.181 6727.905 0.492156 0.00023734 -999.000 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 19:00:00 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 19:10:00 8973.66 8626.58 -999.0 28.10 17.64 0.00877422 12.80 11.77 0.00850000 30.70 0.01446650 22.54 -999.0000 27.00 0.00858744 37.2936 8278.52 0.00 -999.00 -999.00
AIRLOOP DATACENTER MID COOLING COIL COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoopHVAC AIRLOOP DATACENTER MID 92549.834 64188.782 4.691799 0.00226654 -999.000 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 19:10:00 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 19:10:00 85722.43 82252.88 -999.0 28.10 17.65 0.00878749 12.80 11.77 0.00850000 30.52 0.01446618 22.49 -999.0000 27.00 0.00859177 37.3123 78935.52 0.00 -999.00 -999.00
AIRLOOP DATACENTER TOP COOLING COIL COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoopHVAC AIRLOOP DATACENTER TOP 9422.961 6537.255 0.477940 0.00023077 -999.000 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 19:00:00 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 19:00:00 8727.11 8380.12 -999.0 28.10 17.65 0.00878227 12.80 11.77 0.00850000 30.70 0.01446650 22.54 -999.0000 27.00 0.00859007 37.3049 8040.96 0.00 -999.00 -999.00
AIRLOOP DATACENTER BASEMENT HEATING COIL COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoopHVAC AIRLOOP DATACENTER BASEMENT 438414.063 438414.063 22.136565 0.01073673 -999.000 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 438414.06 438414.06 22.136565 -6.30 -6.30 0.00229779 40.00 20.76 0.00800000 -6.30 0.00229779 -6.30 1.5287 27.00 0.00850000 36.9155 0.00 0.00 -999.00 -999.00
AIRLOOP DATACENTER BOT HEATING COIL COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoopHVAC AIRLOOP DATACENTER BOT 9691.181 9691.181 0.492156 0.00023734 -999.000 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 9691.18 9691.18 0.492156 -6.30 -6.30 0.00229779 40.00 20.76 0.00800000 -6.30 0.00229779 -6.30 3.1763 25.87 0.00732509 34.0766 0.00 0.00 -999.00 -999.00
AIRLOOP DATACENTER MID HEATING COIL COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoopHVAC AIRLOOP DATACENTER MID 92549.834 92549.834 4.691799 0.00226654 -999.000 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 92549.83 92549.83 4.691799 -6.30 -6.30 0.00229779 40.00 20.76 0.00800000 -6.30 0.00229779 -6.30 3.3318 23.96 0.00276482 14.5193 0.00 0.00 -999.00 -999.00
AIRLOOP DATACENTER TOP HEATING COIL COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoopHVAC AIRLOOP DATACENTER TOP 9422.961 9422.961 0.477940 0.00023077 -999.000 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 9422.96 9422.96 0.477940 -6.30 -6.30 0.00229779 40.00 20.76 0.00800000 -6.30 0.00229779 -6.30 3.2708 22.88 0.00276446 15.4880 0.00 0.00 -999.00 -999.00
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL Coil:Heating:Electric AirLoopHVAC AIRLOOP DATACENTER BASEMENT 18278.075 18278.075 -999.0 -999.0 -999.000 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 18278.08 18278.08 22.136565 -0.10 -0.10 0.00840519 40.00 20.76 0.00800000 -6.30 0.00229779 -6.30 1.5287 27.00 0.00850000 36.9155 0.00 0.00 -999.00 -999.00
AIRLOOP DATACENTER BOT_SUPPHEATCOIL Coil:Heating:Electric AirLoopHVAC AIRLOOP DATACENTER BOT 844.371 844.371 -999.0 -999.0 -999.000 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 844.37 844.37 0.492156 -0.20 -0.20 0.00716540 40.00 20.76 0.00800000 -6.30 0.00229779 -6.30 3.1763 25.87 0.00732509 34.0766 0.00 0.00 -999.00 -999.00
AIRLOOP DATACENTER MID_SUPPHEATCOIL Coil:Heating:Electric AirLoopHVAC AIRLOOP DATACENTER MID 8443.713 8443.713 -999.0 -999.0 -999.000 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 8443.71 8443.71 4.691799 -0.21 -1.88 0.00274926 40.00 20.76 0.00800000 -6.30 0.00229779 -6.30 3.3318 23.96 0.00276482 14.5193 0.00 0.00 -999.00 -999.00
AIRLOOP DATACENTER TOP_SUPPHEATCOIL Coil:Heating:Electric AirLoopHVAC AIRLOOP DATACENTER TOP 844.371 844.371 -999.0 -999.0 -999.000 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 844.37 844.37 0.477940 -0.21 -1.88 0.00274920 40.00 20.76 0.00800000 -6.30 0.00229779 -6.30 3.2708 22.88 0.00276446 15.4880 0.00 0.00 -999.00 -999.00



Table of Contents

Report: Coil Sizing Details

For: Entire Facility

Timestamp: 2023-10-16 08:43:24

Coils

Coil Type Coil Location HVAC Type HVAC Name Zone Name(s) System Sizing Method Concurrence System Sizing Method Capacity System Sizing Method Air Flow Autosized Coil Capacity? Autosized Coil Airflow? Autosized Coil Water Flow? OA Pretreated prior to coil inlet? Coil Final Gross Total Capacity [W] Coil Final Gross Sensible Capacity [W] Coil Final Reference Air Volume Flow Rate [m3/s] Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] Coil U-value Times Area Value [W/K] Terminal Unit Reheat Coil Multiplier DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio Moist Air Heat Capacity [J/kg-K] Dry Air Heat Capacity [J/kg-K] Standard Air Density Adjusted for Elevation [kg/m3] Supply Fan Name for Coil Supply Fan Type for Coil Supply Fan Maximum Air Volume Flow Rate [m3/s] Supply Fan Maximum Air Mass Flow Rate [kg/s] Plant Name for Coil Plant Fluid Specific Heat Capacity [J/kg-K] Plant Fluid Density [kg/m3] Plant Maximum Fluid Mass Flow Rate [kg/s] Plant Design Fluid Return Temperature [C] Plant Design Fluid Supply Temperature [C] Plant Design Fluid Temperature Difference [deltaC] Plant Design Capacity [W] Coil Capacity Percentage of Plant Design Capacity [%] Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] Design Day Name at Sensible Ideal Loads Peak Date/Time at Sensible Ideal Loads Peak Design Day Name at Total Ideal Loads Peak Date/Time at Total Ideal Loads Peak Design Day Name at Air Flow Ideal Loads Peak Date/Time at Air Flow Ideal Loads Peak Peak Load Type to Size On Coil Total Capacity at Ideal Loads Peak [W] Coil Sensible Capacity at Ideal Loads Peak [W] Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] Coil Entering Air Drybulb at Ideal Loads Peak [C] Coil Entering Air Wetbulb at Ideal Loads Peak [C] Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] Coil Leaving Air Drybulb at Ideal Loads Peak [C] Coil Leaving Air Wetbulb at Ideal Loads Peak [C] Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] Supply Fan Air Heat Gain at Ideal Loads Peak [W] Coil and Fan Net Total Capacity at Ideal Loads Peak [W] Outdoor Air Drybulb at Ideal Loads Peak [C] Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Outdoor Air Wetbulb at Ideal Loads Peak [C] Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] Outdoor Air Flow Percentage at Ideal Loads Peak [%] System Return Air Drybulb at Ideal Loads Peak [C] System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Zone Air Drybulb at Ideal Loads Peak [C] Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Zone Air Relative Humidity at Ideal Loads Peak [%] Zone Sensible Heat Gain at Ideal Loads Peak [W] Zone Latent Heat Gain at Ideal Loads Peak [W] Coil Total Capacity at Rating Conditions [W] Coil Sensible Capacity at Rating Conditions [W] Coil Air Mass Flow Rate at Rating Conditions [kg/s] Coil Entering Air Drybulb at Rating Conditions [C] Coil Entering Air Wetbulb at Rating Conditions [C] Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] Coil Leaving Air Drybulb at Rating Conditions [C] Coil Leaving Air Wetbulb at Rating Conditions [C] Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K]
CORE_BOTTOM VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT CORE_BOTTOM VAV BOX CORE_BOTTOM N/A N/A N/A Yes Yes Yes No 18977.523 18977.523 1.954901 0.00016602 382.572 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1610 unknown unknown -999.0 -999.0   4197.9300 999.8980 21.59986053 54.44 82.22 27.78 2518943.24 0.7534 0.768555 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 05:50:00 unknown unknown ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 05:50:00 Sensible 18977.52 18977.52 1.0000 2.26959476 1.954901 12.80 11.27 0.00800000 33059.8 40.00 20.76 0.00800000 60796.0 0.16600672 60.00 32.22 27.78 0.000 18977.52 -6.30 0.00229779 -6.30 0.00000000 0.0000 21.00 0.00800000 21.00 0.00800000 49.8624 0.00 0.00 19047.50 19047.50 2.26959476 12.80 11.60 0.00800000 33059.8 21.03 14.86 0.00800000 41452.3
CORE_MID VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT CORE_MID VAV BOX CORE_MID N/A N/A N/A Yes Yes Yes No 462014.397 462014.397 19.190077 0.00404190 10929.409 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1610 unknown unknown -999.0 -999.0   4197.9300 999.8980 21.59986053 54.44 82.22 27.78 2518943.24 18.3416 18.710728 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 462014.40 462014.40 1.0000 22.27922897 19.190077 12.80 11.27 0.00800000 33059.8 40.00 20.76 0.00800000 60796.0 4.04149118 60.00 32.22 27.78 0.000 462014.40 -6.30 0.00229779 -6.30 0.00000000 0.0000 20.87 0.00800000 21.00 0.00800000 49.8624 275723.61 0.00 463523.39 463523.39 22.27922897 12.80 11.60 0.00800000 33059.8 33.20 19.09 0.00800000 53865.0
CORE_TOP VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT CORE_TOP VAV BOX CORE_TOP N/A N/A N/A Yes Yes Yes No 86090.017 86090.017 2.657370 0.00075315 2272.772 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1610 unknown unknown -999.0 -999.0   4197.9300 999.8980 21.59986053 54.44 82.22 27.78 2518943.24 3.4177 3.486486 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 86090.02 86090.02 1.0000 3.08514429 2.657370 12.80 11.27 0.00800000 33059.8 40.00 20.76 0.00800000 60796.0 0.75307620 60.00 32.22 27.78 0.000 86090.02 -6.30 0.00229779 -6.30 0.00000000 0.0000 20.91 0.00800000 21.00 0.00800000 49.8624 60293.17 0.00 86389.37 86389.37 3.08514429 12.80 11.60 0.00800000 33059.8 40.26 21.26 0.00800000 61061.6
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_BOT_ZN_3 VAV BOX PERIMETER_BOT_ZN_3 N/A N/A N/A Yes Yes Yes No 14939.369 14939.369 0.461816 0.00013070 394.133 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1610 unknown unknown -999.0 -999.0   4197.9300 999.8980 21.59986053 54.44 82.22 27.78 2518943.24 0.5931 0.605017 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 14939.37 14939.37 1.0000 0.53615779 0.461816 12.80 11.27 0.00800000 33059.8 40.00 20.76 0.00800000 60796.0 0.13068279 60.00 32.22 27.78 0.000 14939.37 -6.30 0.00229779 -6.30 0.00000000 0.0000 20.91 0.00743951 21.00 0.00743951 46.4159 10461.88 0.00 14989.41 14989.41 0.53615779 12.80 11.60 0.00800000 33059.8 40.22 21.25 0.00800000 61016.9
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_BOT_ZN_2 VAV BOX PERIMETER_BOT_ZN_2 N/A N/A N/A Yes Yes Yes No 10215.847 10215.847 0.315843 0.00008937 269.500 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1610 unknown unknown -999.0 -999.0   4197.9300 999.8980 21.59986053 54.44 82.22 27.78 2518943.24 0.4056 0.413723 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 10215.85 10215.85 1.0000 0.36668589 0.315843 12.80 11.27 0.00800000 33059.8 40.00 20.76 0.00800000 60796.0 0.08936357 60.00 32.22 27.78 0.000 10215.85 -6.30 0.00229779 -6.30 0.00000000 0.0000 20.95 0.00748356 21.00 0.00748356 46.6872 7153.34 0.00 10249.95 10249.95 0.36668589 12.80 11.60 0.00800000 33059.8 40.21 21.25 0.00800000 61012.8
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_BOT_ZN_1 VAV BOX PERIMETER_BOT_ZN_1 N/A N/A N/A Yes Yes Yes No 16574.759 16574.759 0.512475 0.00014500 437.238 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1610 unknown unknown -999.0 -999.0   4197.9300 999.8980 21.59986053 54.44 82.22 27.78 2518943.24 0.6580 0.671247 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 16574.76 16574.76 1.0000 0.59497102 0.512475 12.80 11.27 0.00800000 33059.8 40.00 20.76 0.00800000 60796.0 0.14498843 60.00 32.22 27.78 0.000 16574.76 -6.30 0.00229779 -6.30 0.00000000 0.0000 20.95 0.00753960 21.00 0.00753960 47.0321 11605.05 0.00 16629.99 16629.99 0.59497102 12.80 11.60 0.00800000 33059.8 40.21 21.24 0.00800000 61010.7
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_BOT_ZN_4 VAV BOX PERIMETER_BOT_ZN_4 N/A N/A N/A Yes Yes Yes No 8286.083 8286.083 0.279056 0.00007249 210.739 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1610 unknown unknown -999.0 -999.0   4197.9300 999.8980 21.59986053 54.44 82.22 27.78 2518943.24 0.3290 0.335571 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 8286.08 8286.08 1.0000 0.32397714 0.279056 12.80 11.27 0.00800000 33059.8 40.00 20.76 0.00800000 60796.0 0.07248287 60.00 32.22 27.78 0.000 8286.08 -6.30 0.00229779 -6.30 0.00000000 0.0000 20.91 0.00716250 21.00 0.00716250 44.7088 5582.08 0.00 8311.68 8311.68 0.32397714 12.80 11.60 0.00800000 33059.8 37.96 20.57 0.00800000 58715.0
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_MID_ZN_3 VAV BOX PERIMETER_MID_ZN_3 N/A N/A N/A Yes Yes Yes No 245103.783 245103.783 7.585691 0.00214427 6462.915 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1610 unknown unknown -999.0 -999.0   4197.9300 999.8980 21.59986053 54.44 82.22 27.78 2518943.24 9.7304 9.926250 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 245103.78 245103.78 1.0000 8.80680978 7.585691 12.80 11.27 0.00800000 33059.8 40.00 20.76 0.00800000 60796.0 2.14405608 60.00 32.22 27.78 0.000 245103.78 -6.30 0.00229779 -6.30 0.00000000 0.0000 20.95 0.00743552 21.00 0.00743552 46.3933 171564.20 0.00 245899.87 245899.87 8.80680978 12.80 11.60 0.00800000 33059.8 40.18 21.24 0.00800000 60981.4
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_MID_ZN_2 VAV BOX PERIMETER_MID_ZN_2 N/A N/A N/A Yes Yes Yes No 160408.196 160408.196 4.964616 0.00140332 4229.593 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1610 unknown unknown -999.0 -999.0   4197.9300 999.8980 21.59986053 54.44 82.22 27.78 2518943.24 6.3681 6.496235 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 160408.20 160408.20 1.0000 5.76380251 4.964616 12.80 11.27 0.00800000 33059.8 40.00 20.76 0.00800000 60796.0 1.40317772 60.00 32.22 27.78 0.000 160408.20 -6.30 0.00229779 -6.30 0.00000000 0.0000 20.95 0.00742697 21.00 0.00742697 46.3408 112279.75 0.00 160928.75 160928.75 5.76380251 12.80 11.60 0.00800000 33059.8 40.18 21.24 0.00800000 60980.4
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_MID_ZN_1 VAV BOX PERIMETER_MID_ZN_1 N/A N/A N/A Yes Yes Yes No 241668.014 241668.014 7.479186 0.00211422 6372.387 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1610 unknown unknown -999.0 -999.0   4197.9300 999.8980 21.59986053 54.44 82.22 27.78 2518943.24 9.5940 9.787107 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 241668.01 241668.01 1.0000 8.68315962 7.479186 12.80 11.27 0.00800000 33059.8 40.00 20.76 0.00800000 60796.0 2.11400154 60.00 32.22 27.78 0.000 241668.01 -6.30 0.00229779 -6.30 0.00000000 0.0000 20.95 0.00742756 21.00 0.00742756 46.3442 169162.05 0.00 242453.43 242453.43 8.68315962 12.80 11.60 0.00800000 33059.8 40.18 21.24 0.00800000 60982.1
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_MID_ZN_4 VAV BOX PERIMETER_MID_ZN_4 N/A N/A N/A Yes Yes Yes No 155852.349 155852.349 4.823429 0.00136346 4109.537 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1610 unknown unknown -999.0 -999.0   4197.9300 999.8980 21.59986053 54.44 82.22 27.78 2518943.24 6.1872 6.311732 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 155852.35 155852.35 1.0000 5.59988832 4.823429 12.80 11.27 0.00800000 33059.8 40.00 20.76 0.00800000 60796.0 1.36332525 60.00 32.22 27.78 0.000 155852.35 -6.30 0.00229779 -6.30 0.00000000 0.0000 20.95 0.00741025 21.00 0.00741025 46.2378 109094.23 0.00 156358.63 156358.63 5.59988832 12.80 11.60 0.00800000 33059.8 40.18 21.24 0.00800000 60981.6
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_TOP_ZN_3 VAV BOX PERIMETER_TOP_ZN_3 N/A N/A N/A Yes Yes Yes No 30720.046 30720.046 0.951089 0.00026875 809.897 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1610 unknown unknown -999.0 -999.0   4197.9300 999.8980 21.59986053 54.44 82.22 27.78 2518943.24 1.2196 1.244105 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 30720.05 30720.05 1.0000 1.10419243 0.951089 12.80 11.27 0.00800000 33059.8 40.00 20.76 0.00800000 60796.0 0.26872495 60.00 32.22 27.78 0.000 30720.05 -6.30 0.00229779 -6.30 0.00000000 0.0000 20.95 0.00744711 21.00 0.00744711 46.4659 21499.99 0.00 30818.88 30818.88 1.10419243 12.80 11.60 0.00800000 33059.8 40.17 21.23 0.00800000 60970.6
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_TOP_ZN_2 VAV BOX PERIMETER_TOP_ZN_2 N/A N/A N/A Yes Yes Yes No 20042.609 20042.609 0.620532 0.00017534 528.394 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1610 unknown unknown -999.0 -999.0   4197.9300 999.8980 21.59986053 54.44 82.22 27.78 2518943.24 0.7957 0.811689 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 20042.61 20042.61 1.0000 0.72042254 0.620532 12.80 11.27 0.00800000 33059.8 40.00 20.76 0.00800000 60796.0 0.17532360 60.00 32.22 27.78 0.000 20042.61 -6.30 0.00229779 -6.30 0.00000000 0.0000 20.95 0.00743631 21.00 0.00743631 46.3996 14027.22 0.00 20107.05 20107.05 0.72042254 12.80 11.60 0.00800000 33059.8 40.17 21.23 0.00800000 60969.9
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_TOP_ZN_1 VAV BOX PERIMETER_TOP_ZN_1 N/A N/A N/A Yes Yes Yes No 30353.829 30353.829 0.939737 0.00026555 800.248 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1610 unknown unknown -999.0 -999.0   4197.9300 999.8980 21.59986053 54.44 82.22 27.78 2518943.24 1.2050 1.229274 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 30353.83 30353.83 1.0000 1.09101264 0.939737 12.80 11.27 0.00800000 33059.8 40.00 20.76 0.00800000 60796.0 0.26552145 60.00 32.22 27.78 0.000 30353.83 -6.30 0.00229779 -6.30 0.00000000 0.0000 20.95 0.00744096 21.00 0.00744096 46.4280 21243.92 0.00 30451.52 30451.52 1.09101264 12.80 11.60 0.00800000 33059.8 40.17 21.23 0.00800000 60971.1
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_TOP_ZN_4 VAV BOX PERIMETER_TOP_ZN_4 N/A N/A N/A Yes Yes Yes No 19757.339 19757.339 0.611693 0.00017285 520.875 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1610 unknown unknown -999.0 -999.0   4197.9300 999.8980 21.59986053 54.44 82.22 27.78 2518943.24 0.7844 0.800136 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 19757.34 19757.34 1.0000 0.71016157 0.611693 12.80 11.27 0.00800000 33059.8 40.00 20.76 0.00800000 60796.0 0.17282819 60.00 32.22 27.78 0.000 19757.34 -6.30 0.00229779 -6.30 0.00000000 0.0000 20.95 0.00742897 21.00 0.00742897 46.3544 13827.72 0.00 19820.88 19820.88 0.71016157 12.80 11.60 0.00800000 33059.8 40.17 21.23 0.00800000 60970.2
VAV_BOT WITH REHEAT COOLING COIL Coil:Cooling:Water AirLoop AirLoopHVAC VAV_BOT WITH REHEAT CORE_BOTTOM; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_4; Coincident CoolingDesignCapacity N/A Yes Yes Yes No 242286.813 -999.000 10.075991 0.01030744 -999.000 -999.0000 1.00000 1.00000 1024.0470 1004.8586 1.1610 VAV_BOT WITH REHEAT FAN Fan:VariableVolume 10.075991 11.69798873   4197.9300 999.8980 126.11983640 12.27 6.67 5.60 2964876.57 8.1719 8.171902 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 Sensible 242286.81 187471.49 1.0000 11.69798873 10.075991 26.71 18.41 0.01033215 53188.8 10.99 10.99 0.00850000 32476.9 10.30638965 6.67 12.27 5.60 21657.985 220628.83 34.40 0.01447326 23.54 2.53819000 25.1905 24.00 0.00887462 24.00 0.00887462 46.0359 129374.30 0.00 248147.72 182657.25 11.69798873 26.71 18.81 0.01033215 53188.8 11.46 11.14 0.00811253 31975.9
VAV_BOT WITH REHEAT HEATING COIL Coil:Heating:Water AirLoop AirLoopHVAC VAV_BOT WITH REHEAT CORE_BOTTOM; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_4; Coincident HeatingDesignCapacity N/A Yes Yes Yes No 56839.848 56839.848 3.022797 0.00049726 935.402 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1610 VAV_BOT WITH REHEAT FAN Fan:VariableVolume 10.075991 11.69798873   4197.9300 999.8980 21.59986053 54.44 82.22 27.78 2518943.24 2.2565 2.301909 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 56839.85 56839.85 1.0000 3.50939662 3.022797 -3.32 -3.62 0.00278205 3606.4 12.80 11.27 0.00800000 33059.8 0.49720906 60.00 32.22 27.78 0.000 56839.85 -6.30 0.00229779 -6.30 2.53819000 83.9683 12.30 0.00531841 21.02 0.00601079 37.5427 34802.34 0.00 52916.40 52916.40 3.50939662 2.80 0.20 0.00278205 9785.8 17.73 8.10 0.00278205 24864.3
VAV_MID WITH REHEAT COOLING COIL Coil:Cooling:Water AirLoop AirLoopHVAC VAV_MID WITH REHEAT CORE_MID; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_4; Coincident CoolingDesignCapacity N/A Yes Yes Yes No 2354776.150 -999.000 94.036032 0.10017762 -999.000 -999.0000 1.00000 1.00000 1024.4569 1004.8586 1.1610 VAV_MID WITH REHEAT FAN Fan:VariableVolume 94.036032 109.17362721   4197.9300 999.8980 126.11983640 12.27 6.67 5.60 2964876.57 79.4224 79.422401 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 Sensible 2354776.15 1781328.00 1.0000 109.17362721 94.036032 26.99 18.67 0.01055269 54036.9 10.98 10.98 0.00850000 32467.8 100.16740179 6.67 12.27 5.60 203206.858 2151569.29 34.40 0.01447326 23.54 25.38195000 26.9917 24.00 0.00897329 24.00 0.00897329 46.5413 1172846.59 0.00 2410437.32 1739582.96 109.17362721 26.99 19.07 0.01055269 54036.9 11.43 11.14 0.00811638 31958.0
VAV_MID WITH REHEAT HEATING COIL Coil:Heating:Water AirLoop AirLoopHVAC VAV_MID WITH REHEAT CORE_MID; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_4; Coincident HeatingDesignCapacity N/A Yes Yes Yes No 544940.174 544940.174 28.210810 0.00476737 8945.378 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1610 VAV_MID WITH REHEAT FAN Fan:VariableVolume 94.036032 109.17362721   4197.9300 999.8980 21.59986053 54.44 82.22 27.78 2518943.24 21.6337 22.069069 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 06:20:00 unknown unknown ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 544940.17 544940.17 1.0000 32.75208816 28.210810 -3.76 -3.83 0.00281427 3242.6 12.80 11.27 0.00800000 33059.8 4.76688804 60.00 32.22 27.78 0.000 544940.17 -6.30 0.00229779 -6.30 25.38195000 89.9724 19.05 0.00744830 19.60 0.00713138 48.5308 411160.19 0.00 504716.89 504716.89 32.75208816 2.80 0.25 0.00281427 9866.5 18.06 8.29 0.00281427 25276.7
VAV_TOP WITH REHEAT COOLING COIL Coil:Cooling:Water AirLoop AirLoopHVAC VAV_TOP WITH REHEAT CORE_TOP; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_4; Coincident CoolingDesignCapacity N/A Yes Yes Yes No 243642.385 -999.000 10.197899 0.01036511 -999.000 -999.0000 1.00000 1.00000 1024.0276 1004.8586 1.1610 VAV_TOP WITH REHEAT FAN Fan:VariableVolume 10.197899 11.83952188   4197.9300 999.8980 126.11983640 12.27 6.67 5.60 2964876.57 8.2176 8.217623 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:50:00 Sensible 243642.38 188481.55 1.0000 11.83952188 10.197899 26.60 18.37 0.01032177 53055.6 10.99 10.99 0.00850000 32476.9 10.36405293 6.67 12.27 5.60 21920.023 221722.36 34.40 0.01447326 23.54 2.53819000 24.8893 24.00 0.00893533 24.00 0.00893533 46.3474 134529.52 0.00 249559.29 183599.75 11.83952188 26.60 18.77 0.01032177 53055.6 11.46 11.14 0.00811296 31977.1
VAV_TOP WITH REHEAT HEATING COIL Coil:Heating:Water AirLoop AirLoopHVAC VAV_TOP WITH REHEAT CORE_TOP; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_4; Coincident HeatingDesignCapacity N/A Yes Yes Yes No 53637.388 53637.388 3.059370 0.00046924 888.202 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1610 VAV_TOP WITH REHEAT FAN Fan:VariableVolume 10.197899 11.83952188   4197.9300 999.8980 21.59986053 54.44 82.22 27.78 2518943.24 2.1294 2.172215 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 05:40:00 unknown unknown ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 53637.39 53637.39 1.0000 3.55185656 3.059370 -2.23 -2.37 0.00316307 5658.5 12.80 11.27 0.00800000 33059.8 0.46919540 60.00 32.22 27.78 0.000 53637.39 -6.30 0.00229779 -6.30 2.53819000 82.9645 17.60 0.00737703 17.60 0.00716335 55.2617 51870.08 0.00 50582.92 50582.92 3.55185656 2.80 0.76 0.00316307 10740.7 16.89 8.15 0.00316307 24981.9
CAV_BAS COOLING COIL Coil:Cooling:Water AirLoop AirLoopHVAC CAV_BAS BASEMENT Coincident CoolingDesignCapacity N/A Yes Yes Yes No 124171.224 -999.000 6.086107 0.00528253 -999.000 -999.0000 1.00000 1.00000 1023.4755 1004.8586 1.1610 CAV_BAS FAN Fan:ConstantVolume 6.086107 7.06582703   4197.9300 999.8980 126.11983640 12.27 6.67 5.60 2964876.57 4.1881 4.188074 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 08:20:00 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 08:20:00 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 Sensible 124171.22 97239.51 1.0000 7.06582703 6.086107 24.79 17.54 0.01002476 50439.2 11.37 11.18 0.00850000 32865.7 5.28199203 6.67 12.27 5.60 10319.933 113851.29 27.97 0.01446155 21.78 1.20015641 19.7196 24.00 0.00892815 24.00 0.00892815 46.3094 80359.54 0.00 127479.11 94773.08 7.06582703 24.79 17.93 0.01002476 50439.2 11.68 11.32 0.00818988 32397.5
CAV_BAS HEATING COIL Coil:Heating:Water AirLoop AirLoopHVAC CAV_BAS BASEMENT Coincident HeatingDesignCapacity N/A Yes Yes Yes No 292827.055 292827.055 6.086107 0.00256178 6501.963 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1610 CAV_BAS FAN Fan:ConstantVolume 6.086107 7.06582703   4197.9300 999.8980 21.59986053 54.44 82.22 27.78 2518943.24 11.6250 11.858954 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 unknown unknown ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 Sensible 292827.06 292827.06 1.0000 7.06582703 6.086107 -1.24 -3.20 0.00229779 4493.0 40.00 20.76 0.00800000 60796.0 2.56151750 60.00 32.22 27.78 0.000 292827.06 -6.30 0.00229779 -6.30 1.20015641 19.7196 0.00 0.00229779 23.47 0.00229779 12.4368 0.00 0.00 244374.09 244374.09 7.06582703 12.80 5.08 0.00229779 18663.3 47.07 19.04 0.00229779 53248.6
AIRLOOP DATACENTER BASEMENT COOLING COIL COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoop AirLoopHVAC AIRLOOP DATACENTER BASEMENT DATACENTER_BASEMENT_ZN_6 Coincident CoolingDesignCapacity N/A Yes No unknown No 438414.063 303822.623 22.136565 0.01073673 -999.000 -999.0000 -999.00000 -999.00000 1020.8883 1004.8586 1.1610 unknown unknown -999.0 -999.0   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:00:00 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:00:00 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 07:10:00 Sensible 406380.19 398800.54 0.9269 -999.0 -999.0 28.56 17.68 0.00863298 50742.7 12.80 11.77 0.00850000 34322.2 -999.0 -999.00 -999.00 -999.00 0.000 406380.19 34.40 0.01447326 23.54 0.33839277 -999.0000 27.00 0.00854220 27.00 0.00854220 37.1020 371935.50 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
AIRLOOP DATACENTER BOT COOLING COIL COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoop AirLoopHVAC AIRLOOP DATACENTER BOT DATACENTER_BOT_ZN_6 Coincident CoolingDesignCapacity N/A Yes No unknown No 9691.181 6727.905 0.492156 0.00023734 -999.000 -999.0000 -999.00000 -999.00000 1021.1508 1004.8586 1.1610 unknown unknown -999.0 -999.0   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 19:00:00 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 19:00:00 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 19:10:00 Sensible 8973.66 8626.58 0.9260 -999.0 -999.0 28.10 17.64 0.00877422 50635.3 12.80 11.77 0.00850000 34322.2 -999.0 -999.00 -999.00 -999.00 0.000 8973.66 30.70 0.01446650 22.54 0.01563234 -999.0000 27.00 0.00858744 27.00 0.00858744 37.2936 8278.52 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
AIRLOOP DATACENTER MID COOLING COIL COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoop AirLoopHVAC AIRLOOP DATACENTER MID DATACENTER_MID_ZN_6 Coincident CoolingDesignCapacity N/A Yes No unknown No 92549.834 64188.782 4.691799 0.00226654 -999.000 -999.0000 -999.00000 -999.00000 1021.1755 1004.8586 1.1610 unknown unknown -999.0 -999.0   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 19:10:00 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 19:10:00 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 19:10:00 Sensible 85722.43 82252.88 0.9262 -999.0 -999.0 28.10 17.65 0.00878749 50669.0 12.80 11.77 0.00850000 34322.2 -999.0 -999.00 -999.00 -999.00 0.000 85722.43 30.52 0.01446618 22.49 0.15632344 -999.0000 27.00 0.00859177 27.00 0.00859177 37.3123 78935.52 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
AIRLOOP DATACENTER TOP COOLING COIL COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoop AirLoopHVAC AIRLOOP DATACENTER TOP DATACENTER_TOP_ZN_6 Coincident CoolingDesignCapacity N/A Yes No unknown No 9422.961 6537.255 0.477940 0.00023077 -999.000 -999.0000 -999.00000 -999.00000 1021.1658 1004.8586 1.1610 unknown unknown -999.0 -999.0   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 19:00:00 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 19:00:00 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 19:00:00 Sensible 8727.11 8380.12 0.9262 -999.0 -999.0 28.10 17.65 0.00878227 50659.4 12.80 11.77 0.00850000 34322.2 -999.0 -999.00 -999.00 -999.00 0.000 8727.11 30.70 0.01446650 22.54 0.01563234 -999.0000 27.00 0.00859007 27.00 0.00859007 37.3049 8040.96 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
AIRLOOP DATACENTER BASEMENT HEATING COIL COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoop AirLoopHVAC AIRLOOP DATACENTER BASEMENT DATACENTER_BASEMENT_ZN_6 Coincident HeatingDesignCapacity N/A Yes No unknown No 438414.063 438414.063 22.136565 0.01073673 -999.000 -999.0000 -999.00000 -999.00000 1019.7116 1004.8586 1.1610 unknown unknown -999.0 -999.0   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 unknown unknown ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 Sensible 438414.06 438414.06 1.0000 25.70003315 22.136565 -6.30 -6.30 0.00229779 -610.8 40.00 20.76 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 438414.06 -6.30 0.00229779 -6.30 0.33839277 1.5287 0.00 0.00850000 27.00 0.00850000 36.9155 0.00 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
AIRLOOP DATACENTER BOT HEATING COIL COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoop AirLoopHVAC AIRLOOP DATACENTER BOT DATACENTER_BOT_ZN_6 Coincident HeatingDesignCapacity N/A Yes No unknown No 9691.181 9691.181 0.492156 0.00023734 -999.000 -999.0000 -999.00000 -999.00000 1019.7116 1004.8586 1.1610 unknown unknown -999.0 -999.0   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 unknown unknown ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 Sensible 9691.18 9691.18 1.0000 0.57138110 0.492156 -6.30 -6.30 0.00229779 -610.8 40.00 20.76 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 9691.18 -6.30 0.00229779 -6.30 0.01563234 3.1763 0.00 0.00732509 25.87 0.00732509 34.0766 0.00 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
AIRLOOP DATACENTER MID HEATING COIL COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoop AirLoopHVAC AIRLOOP DATACENTER MID DATACENTER_MID_ZN_6 Coincident HeatingDesignCapacity N/A Yes No unknown No 92549.834 92549.834 4.691799 0.00226654 -999.000 -999.0000 -999.00000 -999.00000 1019.7116 1004.8586 1.1610 unknown unknown -999.0 -999.0   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 unknown unknown ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 Sensible 92549.83 92549.83 1.0000 5.44706807 4.691799 -6.30 -6.30 0.00229779 -610.8 40.00 20.76 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 92549.83 -6.30 0.00229779 -6.30 0.15632344 3.3318 0.00 0.00276482 23.96 0.00276482 14.5193 0.00 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
AIRLOOP DATACENTER TOP HEATING COIL COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoop AirLoopHVAC AIRLOOP DATACENTER TOP DATACENTER_TOP_ZN_6 Coincident HeatingDesignCapacity N/A Yes No unknown No 9422.961 9422.961 0.477940 0.00023077 -999.000 -999.0000 -999.00000 -999.00000 1019.7116 1004.8586 1.1610 unknown unknown -999.0 -999.0   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 unknown unknown ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 Sensible 9422.96 9422.96 1.0000 0.55487733 0.477940 -6.30 -6.30 0.00229779 -610.8 40.00 20.76 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 9422.96 -6.30 0.00229779 -6.30 0.01563234 3.2708 0.00 0.00276446 22.88 0.00276446 15.4880 0.00 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL Coil:Heating:Electric AirLoop AirLoopHVAC AIRLOOP DATACENTER BASEMENT DATACENTER_BASEMENT_ZN_6 Coincident HeatingDesignCapacity N/A Yes No unknown No 18278.075 18278.075 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1610 AIRLOOP DATACENTER BASEMENT SUPPLY FAN Fan:OnOff 22.136565 25.70003315   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 unknown unknown ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 Sensible 18278.08 18278.08 1.0000 25.70003315 22.136565 -0.10 -0.10 0.00840519 20922.6 40.00 20.76 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 18278.08 -6.30 0.00229779 -6.30 0.33839277 1.5287 0.00 0.00850000 27.00 0.00850000 36.9155 0.00 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
AIRLOOP DATACENTER BOT_SUPPHEATCOIL Coil:Heating:Electric AirLoop AirLoopHVAC AIRLOOP DATACENTER BOT DATACENTER_BOT_ZN_6 Coincident HeatingDesignCapacity N/A Yes No unknown No 844.371 844.371 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1610 AIRLOOP DATACENTER BOT SUPPLY FAN Fan:OnOff 0.492156 0.57138110   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 unknown unknown ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 Sensible 844.37 844.37 1.0000 0.57138110 0.492156 -0.20 -0.20 0.00716540 17716.5 40.00 20.76 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 844.37 -6.30 0.00229779 -6.30 0.01563234 3.1763 0.00 0.00732509 25.87 0.00732509 34.0766 0.00 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
AIRLOOP DATACENTER MID_SUPPHEATCOIL Coil:Heating:Electric AirLoop AirLoopHVAC AIRLOOP DATACENTER MID DATACENTER_MID_ZN_6 Coincident HeatingDesignCapacity N/A Yes No unknown No 8443.713 8443.713 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1610 AIRLOOP DATACENTER MID SUPPLY FAN Fan:OnOff 4.691799 5.44706807   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 unknown unknown ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 Sensible 8443.71 8443.71 1.0000 5.44706807 4.691799 -0.21 -1.88 0.00274926 6663.7 40.00 20.76 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 8443.71 -6.30 0.00229779 -6.30 0.15632344 3.3318 0.00 0.00276482 23.96 0.00276482 14.5193 0.00 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
AIRLOOP DATACENTER TOP_SUPPHEATCOIL Coil:Heating:Electric AirLoop AirLoopHVAC AIRLOOP DATACENTER TOP DATACENTER_TOP_ZN_6 Coincident HeatingDesignCapacity N/A Yes No unknown No 844.371 844.371 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1610 AIRLOOP DATACENTER TOP SUPPLY FAN Fan:OnOff 0.477940 0.55487733   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 unknown unknown ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 Sensible 844.37 844.37 1.0000 0.55487733 0.477940 -0.21 -1.88 0.00274920 6667.5 40.00 20.76 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 844.37 -6.30 0.00229779 -6.30 0.01563234 3.2708 0.00 0.00276446 22.88 0.00276446 15.4880 0.00 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0



Table of Contents

Report: System Summary

For: Entire Facility

Timestamp: 2023-10-16 08:43:24

Economizer

High Limit Shutoff Control Minimum Outdoor Air [m3/s] Maximum Outdoor Air [m3/s] Return Air Temp Limit Return Air Enthalpy Limit Outdoor Air Temperature Limit [C] Outdoor Air Enthalpy Limit [C]
VAV_BOT WITH REHEAT_OA_CONTROLLER DifferentialEnthalpy 2.54 10.08 -      
VAV_MID WITH REHEAT_OA_CONTROLLER DifferentialEnthalpy 25.38 94.04 -      
VAV_TOP WITH REHEAT_OA_CONTROLLER DifferentialEnthalpy 2.54 10.20 -      
CAV_BAS_OA_CONTROLLER DifferentialEnthalpy 1.20 6.09 -      


Demand Controlled Ventilation using Controller:MechanicalVentilation

Controller:MechanicalVentilation Name Outdoor Air Per Person [m3/s-person] Outdoor Air Per Area [m3/s-m2] Outdoor Air Per Zone [m3/s] Outdoor Air ACH [ach] Outdoor Air Method Outdoor Air Schedule Name Air Distribution Effectiveness in Cooling Mode Air Distribution Effectiveness in Heating Mode Air Distribution Effectiveness Schedule Name
CORE_BOTTOM VAV_BOT WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
CORE_MID VAV_MID WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
CORE_TOP VAV_TOP WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_BOT_ZN_3 VAV_BOT WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_BOT_ZN_2 VAV_BOT WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_BOT_ZN_1 VAV_BOT WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_BOT_ZN_4 VAV_BOT WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_MID_ZN_3 VAV_MID WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_MID_ZN_2 VAV_MID WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_MID_ZN_1 VAV_MID WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_MID_ZN_4 VAV_MID WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_TOP_ZN_3 VAV_TOP WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_TOP_ZN_2 VAV_TOP WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_TOP_ZN_1 VAV_TOP WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_TOP_ZN_4 VAV_TOP WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  


Time Not Comfortable Based on Simple ASHRAE 55-2004

Winter Clothes [hr] Summer Clothes [hr] Summer or Winter Clothes [hr]
BASEMENT 3682.67 1687.17 1157.83
CORE_BOTTOM 3532.50 858.17 12.83
CORE_MID 2298.50 2543.83 91.83
CORE_TOP 2638.33 3076.00 480.33
PERIMETER_BOT_ZN_3 3058.00 2575.00 322.17
PERIMETER_BOT_ZN_2 2836.17 2704.67 319.17
PERIMETER_BOT_ZN_1 3316.50 2099.50 301.00
PERIMETER_BOT_ZN_4 3728.67 1750.00 317.83
PERIMETER_MID_ZN_3 3289.00 3438.00 1193.67
PERIMETER_MID_ZN_2 2678.67 2912.50 979.83
PERIMETER_MID_ZN_1 3261.50 2630.83 697.00
PERIMETER_MID_ZN_4 3193.67 3222.83 914.67
PERIMETER_TOP_ZN_3 3599.50 3628.83 1620.17
PERIMETER_TOP_ZN_2 3481.33 3468.83 1423.33
PERIMETER_TOP_ZN_1 3379.67 2962.00 1047.83
PERIMETER_TOP_ZN_4 3346.00 3440.17 1250.33
DATACENTER_BOT_ZN_6 5929.83 1370.67 1370.67
DATACENTER_MID_ZN_6 5661.17 295.17 253.50
DATACENTER_TOP_ZN_6 5376.33 716.00 543.50
DATACENTER_BASEMENT_ZN_6 5943.00 5685.17 5685.17
GROUNDFLOOR_PLENUM 0.00 0.00 0.00
MIDFLOOR_PLENUM 0.00 0.00 0.00
TOPFLOOR_PLENUM 0.00 0.00 0.00
Facility 5943.00 5940.50 5932.33
Aggregated over the RunPeriods for Weather

Time Setpoint Not Met

During Heating [hr] During Cooling [hr] During Occupied Heating [hr] During Occupied Cooling [hr]
BASEMENT 0.00 42.83 0.00 4.83
CORE_BOTTOM 0.00 0.00 0.00 0.00
CORE_MID 0.33 0.00 0.00 0.00
CORE_TOP 6.67 0.00 1.33 0.00
PERIMETER_BOT_ZN_3 0.33 1.17 0.00 1.17
PERIMETER_BOT_ZN_2 0.33 17.33 0.00 17.33
PERIMETER_BOT_ZN_1 0.50 30.50 0.00 30.17
PERIMETER_BOT_ZN_4 0.00 91.00 0.00 40.83
PERIMETER_MID_ZN_3 31.33 0.50 6.17 0.50
PERIMETER_MID_ZN_2 21.50 23.17 1.33 23.17
PERIMETER_MID_ZN_1 15.00 24.17 0.83 24.17
PERIMETER_MID_ZN_4 14.50 29.17 0.83 16.17
PERIMETER_TOP_ZN_3 113.50 5.50 31.83 4.00
PERIMETER_TOP_ZN_2 70.33 30.00 8.67 28.17
PERIMETER_TOP_ZN_1 57.50 24.33 9.83 22.50
PERIMETER_TOP_ZN_4 44.67 32.67 8.50 17.83
DATACENTER_BOT_ZN_6 0.00 43.00 0.00 43.00
DATACENTER_MID_ZN_6 0.00 39.83 0.00 39.83
DATACENTER_TOP_ZN_6 0.00 27.83 0.00 27.83
DATACENTER_BASEMENT_ZN_6 0.00 464.67 0.00 413.33
GROUNDFLOOR_PLENUM 0.00 0.00 0.00 0.00
MIDFLOOR_PLENUM 0.00 0.00 0.00 0.00
TOPFLOOR_PLENUM 0.00 0.00 0.00 0.00
Facility 121.50 670.83 32.33 532.33
Aggregated over the RunPeriods for Weather


Table of Contents

Report: Outdoor Air Summary

For: Entire Facility

Timestamp: 2023-10-16 08:43:24

Average Outdoor Air During Occupied Hours

Average Number of Occupants Nominal Number of Occupants Zone Volume [m3] Mechanical Ventilation [ach] Infiltration [ach] AFN Infiltration [ach] Simple Ventilation [ach]
BASEMENT 62.11 149.60 6779.02 1.302 0.000 0.000 0.000
CORE_BOTTOM 55.78 134.35 6849.35 0.858 0.000 0.000 0.000
CORE_MID 55.78 134.35 6849.35 0.743 0.000 0.000 0.000
CORE_TOP 55.78 134.35 6849.35 0.731 0.000 0.000 0.000
PERIMETER_BOT_ZN_3 7.00 16.87 860.00 0.839 0.043 0.000 0.000
PERIMETER_BOT_ZN_2 4.51 10.87 554.22 1.158 0.045 0.000 0.000
PERIMETER_BOT_ZN_1 7.00 16.87 860.02 1.112 0.043 0.000 0.000
PERIMETER_BOT_ZN_4 4.51 10.87 554.22 1.628 0.045 0.000 0.000
PERIMETER_MID_ZN_3 7.00 16.87 860.00 0.793 0.101 0.000 0.000
PERIMETER_MID_ZN_2 3.94 10.87 554.22 1.109 0.111 0.000 0.000
PERIMETER_MID_ZN_1 7.00 16.87 860.02 1.048 0.102 0.000 0.000
PERIMETER_MID_ZN_4 4.51 10.87 554.22 1.274 0.105 0.000 0.000
PERIMETER_TOP_ZN_3 7.00 16.87 860.00 0.805 0.126 0.000 0.000
PERIMETER_TOP_ZN_2 4.51 10.87 554.22 1.201 0.130 0.000 0.000
PERIMETER_TOP_ZN_1 7.00 16.87 860.02 1.036 0.126 0.000 0.000
PERIMETER_TOP_ZN_4 4.51 10.87 554.22 1.304 0.130 0.000 0.000
DATACENTER_BOT_ZN_6 0.81 1.95 99.34 0.427 0.000 0.000 0.000
DATACENTER_MID_ZN_6 0.81 1.95 99.34 0.427 0.000 0.000 0.000
DATACENTER_TOP_ZN_6 0.81 1.95 99.34 0.427 0.000 0.000 0.000
DATACENTER_BASEMENT_ZN_6 17.51 42.18 1911.37 0.481 0.000 0.000 0.000
Values shown for a single zone without multipliers

Minimum Outdoor Air During Occupied Hours

Average Number of Occupants Nominal Number of Occupants Zone Volume [m3] Mechanical Ventilation [ach] Infiltration [ach] AFN Infiltration [ach] Simple Ventilation [ach]
BASEMENT 62.11 149.60 6779.02 0.000 0.000 0.000 0.000
CORE_BOTTOM 55.78 134.35 6849.35 0.000 0.000 0.000 0.000
CORE_MID 55.78 134.35 6849.35 0.000 0.000 0.000 0.000
CORE_TOP 55.78 134.35 6849.35 0.000 0.000 0.000 0.000
PERIMETER_BOT_ZN_3 7.00 16.87 860.00 0.000 0.000 0.000 0.000
PERIMETER_BOT_ZN_2 4.51 10.87 554.22 0.000 0.000 0.000 0.000
PERIMETER_BOT_ZN_1 7.00 16.87 860.02 0.000 0.000 0.000 0.000
PERIMETER_BOT_ZN_4 4.51 10.87 554.22 0.000 0.000 0.000 0.000
PERIMETER_MID_ZN_3 7.00 16.87 860.00 0.000 0.000 0.000 0.000
PERIMETER_MID_ZN_2 3.94 10.87 554.22 0.000 0.000 0.000 0.000
PERIMETER_MID_ZN_1 7.00 16.87 860.02 0.000 0.000 0.000 0.000
PERIMETER_MID_ZN_4 4.51 10.87 554.22 0.000 0.000 0.000 0.000
PERIMETER_TOP_ZN_3 7.00 16.87 860.00 0.000 0.000 0.000 0.000
PERIMETER_TOP_ZN_2 4.51 10.87 554.22 0.000 0.000 0.000 0.000
PERIMETER_TOP_ZN_1 7.00 16.87 860.02 0.000 0.000 0.000 0.000
PERIMETER_TOP_ZN_4 4.51 10.87 554.22 0.000 0.000 0.000 0.000
DATACENTER_BOT_ZN_6 0.81 1.95 99.34 0.000 0.000 0.000 0.000
DATACENTER_MID_ZN_6 0.81 1.95 99.34 0.000 0.000 0.000 0.000
DATACENTER_TOP_ZN_6 0.81 1.95 99.34 0.000 0.000 0.000 0.000
DATACENTER_BASEMENT_ZN_6 17.51 42.18 1911.37 0.000 0.000 0.000 0.000
Values shown for a single zone without multipliers


Table of Contents

Report: Outdoor Air Details

For: Entire Facility

Timestamp: 2023-10-16 08:43:24

Mechanical Ventilation Parameters by Zone

AirLoop Name Average Number of Occupants Nominal Number of Occupants Zone Volume [m3] Zone Area [m2] Design Zone Outdoor Airflow - Voz [m3/s] Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s]
BASEMENT CAV_BAS 62.11 149.60 6779.02 2779.43 1.2002 1.200
CORE_BOTTOM VAV_BOT WITH REHEAT 55.78 134.35 6849.35 2496.12 0.0000 1.078
CORE_MID VAV_MID WITH REHEAT 55.78 134.35 6849.35 2496.12 0.0000 10.778
CORE_TOP VAV_TOP WITH REHEAT 55.78 134.35 6849.35 2496.12 0.0000 1.078
PERIMETER_BOT_ZN_3 VAV_BOT WITH REHEAT 7.00 16.87 860.00 313.41 0.0000 0.135
PERIMETER_BOT_ZN_2 VAV_BOT WITH REHEAT 4.51 10.87 554.22 201.98 0.0000 0.087
PERIMETER_BOT_ZN_1 VAV_BOT WITH REHEAT 7.00 16.87 860.02 313.42 0.0000 0.135
PERIMETER_BOT_ZN_4 VAV_BOT WITH REHEAT 4.51 10.87 554.22 201.98 0.0000 0.087
PERIMETER_MID_ZN_3 VAV_MID WITH REHEAT 7.00 16.87 860.00 313.41 0.0000 1.353
PERIMETER_MID_ZN_2 VAV_MID WITH REHEAT 3.94 10.87 554.22 201.98 0.0000 0.872
PERIMETER_MID_ZN_1 VAV_MID WITH REHEAT 7.00 16.87 860.02 313.42 0.0000 1.353
PERIMETER_MID_ZN_4 VAV_MID WITH REHEAT 4.51 10.87 554.22 201.98 0.0000 0.872
PERIMETER_TOP_ZN_3 VAV_TOP WITH REHEAT 7.00 16.87 860.00 313.41 0.0000 0.135
PERIMETER_TOP_ZN_2 VAV_TOP WITH REHEAT 4.51 10.87 554.22 201.98 0.0000 0.087
PERIMETER_TOP_ZN_1 VAV_TOP WITH REHEAT 7.00 16.87 860.02 313.42 0.0000 0.135
PERIMETER_TOP_ZN_4 VAV_TOP WITH REHEAT 4.51 10.87 554.22 201.98 0.0000 0.087
DATACENTER_BOT_ZN_6 AIRLOOP DATACENTER BOT 0.81 1.95 99.34 36.20 0.0156 0.016
DATACENTER_MID_ZN_6 AIRLOOP DATACENTER MID 0.81 1.95 99.34 36.20 0.1563 0.156
DATACENTER_TOP_ZN_6 AIRLOOP DATACENTER TOP 0.81 1.95 99.34 36.20 0.0156 0.016
DATACENTER_BASEMENT_ZN_6 AIRLOOP DATACENTER BASEMENT 17.51 42.18 1911.37 783.68 0.3384 0.338
Total Facility   1029.47 2493.19 126016.35 46320.38 1.7261 158.471


Total Outdoor Air by Zone

Mechanical Ventilation [m3] Natural Ventilation [m3] Total Ventilation [m3] Infiltration [m3] Total Ventilation and Infiltration [m3] Dynamic Target Ventilation - Voz-dyn [m3] Time Below Voz-dyn [hr] Time At Voz-dyn [hr] Time Above Voz-dyn [hr] Time Above Zero When Unoccupied [hr]
BASEMENT 53346729.30 0.00 53346729.30 0.00 53346729.30 37848132.68 4044.71 1668.38 3046.92 232.06
CORE_BOTTOM 35251440.05 0.00 35251440.05 0.00 35251440.05 33990283.35 4012.21 6.05 4741.74 148.14
CORE_MID 0.30E+09 0.00 0.30E+09 0.00 0.30E+09 0.34E+09 4160.11 4.68 4595.21 133.83
CORE_TOP 29802616.20 0.00 29802616.20 0.00 29802616.20 33990283.35 4217.27 4.45 4538.28 248.37
PERIMETER_BOT_ZN_3 4321992.54 0.00 4321992.54 439326.30 4761318.84 4267819.30 4015.15 4.32 4740.53 148.14
PERIMETER_BOT_ZN_2 3847978.88 0.00 3847978.88 292884.00 4140862.88 2750345.05 3975.45 2.27 4782.28 148.14
PERIMETER_BOT_ZN_1 5694328.46 0.00 5694328.46 439326.30 6133654.77 4267912.63 4009.74 4.28 4745.98 148.14
PERIMETER_BOT_ZN_4 5397933.36 0.00 5397933.36 292884.00 5690817.36 2750345.05 3956.11 0.00 4803.89 148.14
PERIMETER_MID_ZN_3 40578497.08 0.00 40578497.08 1030333.47 41608830.55 42678193.03 4124.37 6.73 4628.90 133.83
PERIMETER_MID_ZN_2 39550377.84 0.00 39550377.84 686888.51 40237266.35 27503450.52 4076.93 3.85 4679.22 1042.83
PERIMETER_MID_ZN_1 53287719.50 0.00 53287719.50 1030333.47 54318052.97 42679126.28 4143.09 4.81 4612.11 133.83
PERIMETER_MID_ZN_4 41958527.19 0.00 41958527.19 686888.51 42645415.70 27503450.52 4073.97 4.03 4682.00 133.83
PERIMETER_TOP_ZN_3 4134958.08 0.00 4134958.08 1279256.65 5414214.73 4267819.30 4151.82 6.51 4601.67 248.37
PERIMETER_TOP_ZN_2 3966626.33 0.00 3966626.33 852837.19 4819463.52 2750345.05 4090.87 7.09 4662.04 248.37
PERIMETER_TOP_ZN_1 5288939.32 0.00 5288939.32 1279256.65 6568195.97 4267912.63 4169.61 5.97 4584.41 248.37
PERIMETER_TOP_ZN_4 4305040.08 0.00 4305040.08 852837.19 5157877.27 2750345.05 4084.41 3.60 4671.99 248.37
DATACENTER_BOT_ZN_6 244296.02 0.00 244296.02 0.00 244296.02 492981.60 4419.00 4341.00 0.00 0.00
DATACENTER_MID_ZN_6 2442960.18 0.00 2442960.18 0.00 2442960.18 4929815.99 4419.00 4341.00 0.00 0.00
DATACENTER_TOP_ZN_6 244296.02 0.00 244296.02 0.00 244296.02 492981.60 4419.00 4341.00 0.00 0.00
DATACENTER_BASEMENT_ZN_6 5288266.81 0.00 5288266.81 0.00 5288266.81 10671554.30 4419.00 4341.00 0.00 0.00
Total Facility 0.50E+10 0.00 0.50E+10 40073047.80 0.50E+10 0.50E+10 4424.65 4387.41 4995.27 1364.69


Average Outdoor Air During Occupancy by Zone - Flow Rates

Mechanical Ventilation [m3/s] Natural Ventilation [m3/s] Total Ventilation [m3/s] Infiltration [m3/s] Total Ventilation and Infiltration [m3/s] Dynamic Target Ventilation - Voz-dyn [m3/s] Time Below Voz-dyn [hr] Time At Voz-dyn [hr] Time Above Voz-dyn [hr]
BASEMENT 2.4010 0.0000 2.4010 0.0000 2.4010 1.2002 1375.57 1666.72 2900.71
CORE_BOTTOM 1.6006 0.0000 1.6006 0.0000 1.6006 1.0778 1325.02 4.67 4613.31
CORE_MID 13.8885 0.0000 13.8885 0.0000 13.8885 10.7782 1391.33 2.21 4549.47
CORE_TOP 1.3671 0.0000 1.3671 0.0000 1.3671 1.0778 1432.76 3.40 4506.84
PERIMETER_BOT_ZN_3 0.1968 0.0000 0.1968 0.0102 0.2070 0.1353 1328.05 2.82 4612.13
PERIMETER_BOT_ZN_2 0.1752 0.0000 0.1752 0.0068 0.1820 0.0872 1299.55 1.25 4642.20
PERIMETER_BOT_ZN_1 0.2608 0.0000 0.2608 0.0102 0.2710 0.1353 1323.43 3.81 4615.76
PERIMETER_BOT_ZN_4 0.2460 0.0000 0.2460 0.0068 0.2527 0.0872 1287.25 0.00 4655.75
PERIMETER_MID_ZN_3 1.8633 0.0000 1.8633 0.0239 1.8872 1.3533 1373.47 3.58 4565.95
PERIMETER_MID_ZN_2 1.6812 0.0000 1.6812 0.0169 1.6980 0.8721 1342.83 2.45 3688.73
PERIMETER_MID_ZN_1 2.4588 0.0000 2.4588 0.0239 2.4827 1.3533 1383.17 2.38 4557.44
PERIMETER_MID_ZN_4 1.9296 0.0000 1.9296 0.0159 1.9456 0.8721 1343.54 0.50 4598.96
PERIMETER_TOP_ZN_3 0.1893 0.0000 0.1893 0.0297 0.2190 0.1353 1390.35 4.17 4548.49
PERIMETER_TOP_ZN_2 0.1820 0.0000 0.1820 0.0198 0.2018 0.0872 1350.12 4.94 4587.94
PERIMETER_TOP_ZN_1 0.2433 0.0000 0.2433 0.0297 0.2730 0.1353 1404.75 3.81 4534.44
PERIMETER_TOP_ZN_4 0.1976 0.0000 0.1976 0.0198 0.2174 0.0872 1346.39 2.02 4594.58
DATACENTER_BOT_ZN_6 0.0114 0.0000 0.0114 0.0000 0.0114 0.0156 1602.00 4341.00 0.00
DATACENTER_MID_ZN_6 0.1142 0.0000 0.1142 0.0000 0.1142 0.1563 1602.00 4341.00 0.00
DATACENTER_TOP_ZN_6 0.0114 0.0000 0.0114 0.0000 0.0114 0.0156 1602.00 4341.00 0.00
DATACENTER_BASEMENT_ZN_6 0.2472 0.0000 0.2472 0.0000 0.2472 0.3384 1602.00 4341.00 0.00
Total Facility 226.6851 0.0000 226.6851 0.9383 227.6234 158.4706 1607.65 4367.06 4725.97


Total Outdoor Air by AirLoop

Mechanical Ventilation [m3] Natural Ventilation [m3/s] Total Ventilation [m3/s] Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] Time Below Voz-sum-dyn [hr] Time At Voz-sum-dyn [hr] Time Above Voz-sum-dyn [hr] Time Above Zero When Unoccupied [hr]
VAV_BOT WITH REHEAT 73477291.63 0.00 73477291.63 48026705.38 3966.92 4.43 4788.65 148.14
VAV_MID WITH REHEAT 0.64E+09 0.00 0.64E+09 0.48E+09 4085.98 4.02 4670.01 133.83
VAV_TOP WITH REHEAT 64020844.76 0.00 64020844.76 48026705.38 4117.34 4.26 4638.40 248.37
CAV_BAS 71904270.78 0.00 71904270.78 37848132.68 4008.13 2.44 4749.43 232.06
AIRLOOP DATACENTER BASEMENT 7127877.82 0.00 7127877.82 10671554.30 4419.00 0.00 4341.00 0.00
AIRLOOP DATACENTER BOT 329278.43 0.00 329278.43 492981.60 4419.00 0.00 4341.00 0.00
AIRLOOP DATACENTER MID 3292784.26 0.00 3292784.26 4929815.99 4419.00 0.00 4341.00 0.00
AIRLOOP DATACENTER TOP 329278.43 0.00 329278.43 492981.60 4419.00 0.00 4341.00 0.00


Average Outdoor Air During Occupancy by AirLoop

Mechanical Ventilation [m3/s] Natural Ventilation [m3/s] Total Ventilation [m3/s] Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] Time Below Voz-sum-dyn [hr] Time At Voz-sum-dyn [hr] Time Above Voz-sum-dyn [hr]
VAV_BOT WITH REHEAT 3.3419 0.0000 3.3419 1.5229 1293.46 3.10 4646.44
VAV_MID WITH REHEAT 29.5969 0.0000 29.5969 15.2292 1347.91 1.82 4593.27
VAV_TOP WITH REHEAT 2.9375 0.0000 2.9375 1.5229 1366.19 2.72 4574.09
CAV_BAS 3.2362 0.0000 3.2362 1.2002 1362.02 0.64 4580.35
AIRLOOP DATACENTER BASEMENT 0.3332 0.0000 0.3332 0.3384 1602.00 0.00 4341.00
AIRLOOP DATACENTER BOT 0.0154 0.0000 0.0154 0.0156 1602.00 0.00 4341.00
AIRLOOP DATACENTER MID 0.1539 0.0000 0.1539 0.1563 1602.00 0.00 4341.00
AIRLOOP DATACENTER TOP 0.0154 0.0000 0.0154 0.0156 1602.00 0.00 4341.00


Outdoor Air Controller Limiting Factors by AirLoop

No Limiting Factor [hr] Limits and Scheduled Limits [hr] Economizer [hr] Exhaust Flow [hr] Mixed Air Flow [hr] High Humidity [hr] Demand Controlled Ventilation [hr] Night Ventilation [hr] Demand Limiting [hr] Energy Management System [hr]
VAV_BOT WITH REHEAT 0.00 2416.31 2387.84 0.00 0.00 0.00 0.00 0.00 0.00 0.00
VAV_MID WITH REHEAT 0.00 2641.24 2116.95 0.00 0.00 0.00 0.00 0.00 0.00 0.00
VAV_TOP WITH REHEAT 0.00 2680.98 2230.74 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CAV_BAS 0.00 1663.33 3161.54 0.00 0.00 0.00 0.00 0.00 0.00 0.00
AIRLOOP DATACENTER BASEMENT 0.00 4341.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
AIRLOOP DATACENTER BOT 0.00 4341.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
AIRLOOP DATACENTER MID 0.00 4341.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
AIRLOOP DATACENTER TOP 0.00 4341.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Average Outdoor Air for Limiting Factors During Occupancy

No Limiting Factor [m3/s] Limits and Scheduled Limits [m3/s] Economizer [m3/s] Exhaust Flow [m3/s] Mixed Air Flow [m3/s] High Humidity [m3/s] Demand Controlled Ventilation [m3/s] Night Ventilation [m3/s] Demand Limiting [m3/s] Energy Management System [m3/s]
VAV_BOT WITH REHEAT 0.0000 3.4215 5.1785 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
VAV_MID WITH REHEAT 0.0000 34.2145 43.1334 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
VAV_TOP WITH REHEAT 0.0000 3.4224 4.1804 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
CAV_BAS 0.0000 1.6180 5.6477 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
AIRLOOP DATACENTER BASEMENT 0.0000 0.4562 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
AIRLOOP DATACENTER BOT 0.0000 0.0211 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
AIRLOOP DATACENTER MID 0.0000 0.2108 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
AIRLOOP DATACENTER TOP 0.0000 0.0211 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000



Table of Contents

Report: Object Count Summary

For: Entire Facility

Timestamp: 2023-10-16 08:43:24

Surfaces by Class

Total Outdoors
Wall 98 30
Floor 41 0
Roof 30 1
Internal Mass 16 0
Building Detached Shading 0 0
Fixed Detached Shading 0 0
Window 24 24
Door 12 12
Glass Door 0 0
Shading 0 0
Overhang 0 0
Fin 0 0
Tubular Daylighting Device Dome 0 0
Tubular Daylighting Device Diffuser 0 0


HVAC

Count
HVAC Air Loops 8
Conditioned Zones 23
Unconditioned Zones 0
Supply Plenums 0
Return Plenums 3


Input Fields

Count
IDF Objects 1404
Defaulted Fields 1182
Fields with Defaults 3915
Autosized Fields 338
Autosizable Fields 414
Autocalculated Fields 226
Autocalculatable Fields 473



Table of Contents

Report: Energy Meters

For: Entire Facility

Timestamp: 2023-10-16 08:43:24

Annual and Peak Values - Electricity

Electricity Annual Value [GJ] Electricity Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Electricity Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
Electricity:Facility 29915.83 363114.99 08-JAN-10:10 1957895.51 17-AUG-15:30
Electricity:Building 18612.53 225715.65 21-MAY-17:10 1164206.62 06-DEC-08:10
Electricity:Zone:BASEMENT 687.24 14732.47 01-JAN-00:10 36407.88 02-JAN-08:10
Electricity:SpaceType:GENERAL 18612.53 225715.65 21-MAY-17:10 1164206.62 06-DEC-08:10
InteriorLights:Electricity 3936.13 18459.50 01-JAN-11:20 385834.94 03-JAN-08:10
InteriorLights:Electricity:Zone:BASEMENT 262.84 1274.92 01-JAN-00:10 22950.34 02-JAN-08:10
InteriorLights:Electricity:SpaceType:GENERAL 3936.13 18459.50 01-JAN-11:20 385834.94 03-JAN-08:10
LightsWired:InteriorLights:Electricity 3936.13 18459.50 01-JAN-11:20 385834.94 03-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:BASEMENT 262.84 1274.92 01-JAN-00:10 22950.34 02-JAN-08:10
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL 3936.13 18459.50 01-JAN-11:20 385834.94 03-JAN-08:10
Electricity:Zone:CORE_BOTTOM 525.67 5598.20 01-JAN-00:10 37817.64 02-JAN-08:10
InteriorLights:Electricity:Zone:CORE_BOTTOM 236.05 1144.97 01-JAN-00:10 20611.01 02-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:CORE_BOTTOM 236.05 1144.97 01-JAN-00:10 20611.01 02-JAN-08:10
Electricity:Zone:CORE_MID 5256.66 55981.88 01-JAN-00:10 378175.77 02-JAN-08:10
InteriorLights:Electricity:Zone:CORE_MID 2360.53 11449.71 01-JAN-00:10 206110.14 02-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:CORE_MID 2360.53 11449.71 01-JAN-00:10 206110.14 02-JAN-08:10
Electricity:Zone:CORE_TOP 525.67 5598.19 01-JAN-00:10 37817.58 02-JAN-08:10
InteriorLights:Electricity:Zone:CORE_TOP 236.05 1144.97 01-JAN-00:10 20611.01 02-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:CORE_TOP 236.05 1144.97 01-JAN-00:10 20611.01 02-JAN-08:10
Electricity:Zone:PERIMETER_BOT_ZN_3 54.08 627.57 16-APR-17:10 4748.47 03-JAN-08:10
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 17.72 68.40 01-JAN-11:20 2587.92 03-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 17.72 68.40 01-JAN-11:20 2587.92 03-JAN-08:10
Electricity:Zone:PERIMETER_BOT_ZN_2 34.62 404.43 23-APR-17:10 3060.10 03-JAN-08:10
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 11.19 44.08 01-JAN-09:10 1667.75 03-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 11.19 44.08 01-JAN-09:10 1667.75 03-JAN-08:10
Electricity:Zone:PERIMETER_BOT_ZN_1 53.57 627.58 12-MAR-17:10 4748.56 03-JAN-08:10
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 17.20 68.40 01-JAN-09:20 2587.98 03-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 17.20 68.40 01-JAN-09:20 2587.98 03-JAN-08:10
Electricity:Zone:PERIMETER_BOT_ZN_4 34.73 404.43 20-FEB-18:10 3060.09 03-JAN-08:10
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 11.29 44.08 01-JAN-11:00 1667.75 03-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 11.29 44.08 01-JAN-11:00 1667.75 03-JAN-08:10
Electricity:Zone:PERIMETER_MID_ZN_3 540.09 6275.73 16-APR-17:10 47484.70 03-JAN-08:10
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 176.43 684.02 01-JAN-11:10 25879.19 03-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 176.43 684.02 01-JAN-11:10 25879.19 03-JAN-08:10
Electricity:Zone:PERIMETER_MID_ZN_2 345.99 4044.32 23-APR-17:10 30600.95 03-JAN-08:10
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 111.63 440.81 01-JAN-09:10 16677.53 03-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 111.63 440.81 01-JAN-09:10 16677.53 03-JAN-08:10
Electricity:Zone:PERIMETER_MID_ZN_1 535.39 6275.83 12-MAR-17:10 47485.60 03-JAN-08:10
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 171.73 684.04 01-JAN-09:20 25879.75 03-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 171.73 684.04 01-JAN-09:20 25879.75 03-JAN-08:10
Electricity:Zone:PERIMETER_MID_ZN_4 346.94 4044.30 20-FEB-18:10 30600.86 03-JAN-08:10
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 112.59 440.81 01-JAN-11:00 16677.53 03-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 112.59 440.81 01-JAN-11:00 16677.53 03-JAN-08:10
Electricity:Zone:PERIMETER_TOP_ZN_3 54.01 627.57 16-APR-17:10 4748.47 03-JAN-08:10
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 17.64 68.40 01-JAN-11:10 2587.92 03-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 17.64 68.40 01-JAN-11:10 2587.92 03-JAN-08:10
Electricity:Zone:PERIMETER_TOP_ZN_2 34.60 404.43 23-APR-17:10 3060.10 03-JAN-08:10
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 11.16 44.08 01-JAN-09:10 1667.75 03-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 11.16 44.08 01-JAN-09:10 1667.75 03-JAN-08:10
Electricity:Zone:PERIMETER_TOP_ZN_1 53.54 627.58 12-MAR-17:10 4748.56 03-JAN-08:10
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 17.17 68.40 01-JAN-09:20 2587.98 03-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 17.17 68.40 01-JAN-09:20 2587.98 03-JAN-08:10
Electricity:Zone:PERIMETER_TOP_ZN_4 34.69 404.43 20-FEB-18:10 3060.09 03-JAN-08:10
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 11.26 44.08 01-JAN-10:50 1667.75 03-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 11.26 44.08 01-JAN-10:50 1667.75 03-JAN-08:10
Electricity:Zone:DATACENTER_BASEMENT_ZN_6 7568.97 95267.60 01-JAN-00:10 386103.53 03-APR-07:10
InteriorLights:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 74.11 359.47 01-JAN-00:10 6471.01 02-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 74.11 359.47 01-JAN-00:10 6471.01 02-JAN-08:10
Electricity:Zone:DATACENTER_BOT_ZN_6 160.51 1980.76 01-JAN-00:10 8373.14 03-APR-07:10
InteriorLights:Electricity:Zone:DATACENTER_BOT_ZN_6 6.63 32.15 01-JAN-00:10 578.72 02-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_BOT_ZN_6 6.63 32.15 01-JAN-00:10 578.72 02-JAN-08:10
Electricity:Zone:DATACENTER_MID_ZN_6 1605.09 19807.58 01-JAN-00:10 83731.41 03-APR-07:10
InteriorLights:Electricity:Zone:DATACENTER_MID_ZN_6 66.28 321.53 01-JAN-00:10 5787.18 02-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_MID_ZN_6 66.28 321.53 01-JAN-00:10 5787.18 02-JAN-08:10
Electricity:Zone:DATACENTER_TOP_ZN_6 160.51 1980.76 01-JAN-00:10 8373.14 03-APR-07:10
InteriorLights:Electricity:Zone:DATACENTER_TOP_ZN_6 6.63 32.15 01-JAN-00:10 578.72 02-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_TOP_ZN_6 6.63 32.15 01-JAN-00:10 578.72 02-JAN-08:10
InteriorEquipment:Electricity 14676.40 207256.16 01-JAN-00:10 778371.69 03-APR-07:10
InteriorEquipment:Electricity:Zone:BASEMENT 424.40 13457.54 01-JAN-00:10 13457.54 01-JAN-00:10
InteriorEquipment:Electricity:SpaceType:GENERAL 14676.40 207256.16 01-JAN-00:10 778371.69 03-APR-07:10
MiscPlug:InteriorEquipment:Electricity 5334.97 88964.76 01-JAN-00:10 305206.10 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:BASEMENT 424.40 13457.54 01-JAN-00:10 13457.54 01-JAN-00:10
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL 5334.97 88964.76 01-JAN-00:10 305206.10 02-JAN-08:10
InteriorEquipment:Electricity:Zone:CORE_BOTTOM 289.61 4453.23 01-JAN-00:10 17206.63 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_BOTTOM 289.61 4453.23 01-JAN-00:10 17206.63 02-JAN-08:10
InteriorEquipment:Electricity:Zone:CORE_MID 2896.13 44532.17 01-JAN-00:10 172065.63 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_MID 2896.13 44532.17 01-JAN-00:10 172065.63 02-JAN-08:10
InteriorEquipment:Electricity:Zone:CORE_TOP 289.61 4453.22 01-JAN-00:10 17206.56 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_TOP 289.61 4453.22 01-JAN-00:10 17206.56 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 36.37 559.17 01-JAN-00:10 2160.55 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 36.37 559.17 01-JAN-00:10 2160.55 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 23.44 360.35 01-JAN-00:10 1392.34 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 23.44 360.35 01-JAN-00:10 1392.34 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 36.37 559.18 01-JAN-00:10 2160.58 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 36.37 559.18 01-JAN-00:10 2160.58 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 23.44 360.35 01-JAN-00:10 1392.33 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 23.44 360.35 01-JAN-00:10 1392.33 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 363.65 5591.71 01-JAN-00:10 21605.52 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 363.65 5591.71 01-JAN-00:10 21605.52 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 234.35 3603.51 01-JAN-00:10 13923.42 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 234.35 3603.51 01-JAN-00:10 13923.42 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 363.66 5591.79 01-JAN-00:10 21605.85 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 363.66 5591.79 01-JAN-00:10 21605.85 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 234.35 3603.49 01-JAN-00:10 13923.33 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 234.35 3603.49 01-JAN-00:10 13923.33 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 36.37 559.17 01-JAN-00:10 2160.55 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 36.37 559.17 01-JAN-00:10 2160.55 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 23.44 360.35 01-JAN-00:10 1392.34 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 23.44 360.35 01-JAN-00:10 1392.34 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 36.37 559.18 01-JAN-00:10 2160.58 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 36.37 559.18 01-JAN-00:10 2160.58 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 23.44 360.35 01-JAN-00:10 1392.33 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 23.44 360.35 01-JAN-00:10 1392.33 02-JAN-08:10
InteriorEquipment:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 7494.86 94908.13 01-JAN-00:10 379632.52 31-MAR-23:10
DataCenterPlugLoads:InteriorEquipment:Electricity 9341.42 118291.40 01-JAN-00:10 473165.59 31-MAR-23:10
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 7494.86 94908.13 01-JAN-00:10 379632.52 31-MAR-23:10
DataCenterPlugLoads:InteriorEquipment:Electricity:SpaceType:GENERAL 9341.42 118291.40 01-JAN-00:10 473165.59 31-MAR-23:10
InteriorEquipment:Electricity:Zone:DATACENTER_BOT_ZN_6 153.88 1948.61 01-JAN-00:10 7794.42 31-MAR-23:10
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_BOT_ZN_6 153.88 1948.61 01-JAN-00:10 7794.42 31-MAR-23:10
InteriorEquipment:Electricity:Zone:DATACENTER_MID_ZN_6 1538.81 19486.06 01-JAN-00:10 77944.22 31-MAR-23:10
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_MID_ZN_6 1538.81 19486.06 01-JAN-00:10 77944.22 31-MAR-23:10
InteriorEquipment:Electricity:Zone:DATACENTER_TOP_ZN_6 153.88 1948.61 01-JAN-00:10 7794.42 31-MAR-23:10
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_TOP_ZN_6 153.88 1948.61 01-JAN-00:10 7794.42 31-MAR-23:10
Electricity:Plant 3758.24 5958.24 07-JAN-17:40 444767.77 24-AUG-10:50
HeatRejection:Electricity 1479.78 2321.47 14-JAN-08:00 92827.61 29-MAR-16:00
General:HeatRejection:Electricity 1479.78 2321.47 14-JAN-08:00 92827.61 29-MAR-16:00
Electricity:HVAC 4994.47 75010.99 08-JAN-23:30 352827.72 02-AUG-16:00
ExteriorEquipment:Electricity 1934.80 28603.11 01-JAN-00:10 118535.44 03-JAN-08:20
Transformer:ExteriorEquipment:Electricity 80.18 1421.04 01-JAN-00:10 5057.48 06-DEC-08:20
ElectricityPurchased:Facility 29915.83 363114.99 08-JAN-10:10 1957895.51 17-AUG-15:30
ElectricityPurchased:Plant 29915.83 363114.99 08-JAN-10:10 1957895.51 17-AUG-15:30
Cogeneration:ElectricityPurchased 29915.83 363114.99 08-JAN-10:10 1957895.51 17-AUG-15:30
General:Cogeneration:ElectricityPurchased 29915.83 363114.99 08-JAN-10:10 1957895.51 17-AUG-15:30
ElectricitySurplusSold:Facility 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
ElectricitySurplusSold:Plant 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cogeneration:ElectricitySurplusSold 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Cogeneration:ElectricitySurplusSold 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
ElectricityNet:Facility 29915.83 363114.99 08-JAN-10:10 1957895.51 17-AUG-15:30
ElectricityNet:Plant 29915.83 363114.99 08-JAN-10:10 1957895.51 17-AUG-15:30
Cogeneration:ElectricityNet 29915.83 363114.99 08-JAN-10:10 1957895.51 17-AUG-15:30
General:Cogeneration:ElectricityNet 29915.83 363114.99 08-JAN-10:10 1957895.51 17-AUG-15:30
Fans:Electricity 2129.53 42850.60 23-JAN-04:40 173140.65 17-APR-15:10
General:Fans:Electricity 2129.53 42850.60 23-JAN-04:40 173140.65 17-APR-15:10
ExteriorLights:Electricity 695.97 0.00 01-JAN-07:50 57580.60 01-JAN-06:10
General:ExteriorLights:Electricity 695.97 0.00 01-JAN-07:50 57580.60 01-JAN-06:10
ElevatorLift:ExteriorEquipment:Electricity 1848.78 27144.47 01-JAN-00:10 113101.96 01-JAN-07:10
ElevatorLightsFan:ExteriorEquipment:Electricity 5.83 37.60 01-JAN-00:10 376.00 01-JAN-07:10
HeatRecovery:Electricity 52.13 0.00 01-JAN-00:10 5613.48 02-JAN-07:10
General:HeatRecovery:Electricity 52.13 0.00 01-JAN-00:10 5613.48 02-JAN-07:10
Cooling:Electricity 4405.04 28008.02 09-JAN-07:10 456876.80 17-AUG-15:30
General:Cooling:Electricity 4405.04 28008.02 09-JAN-07:10 456876.80 17-AUG-15:30
Heating:Electricity 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:Electricity 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Humidifier:Electricity 8.94 0.00 01-JAN-00:10 5868.03 05-JAN-18:10
General:Humidifier:Electricity 8.94 0.00 01-JAN-00:10 5868.03 05-JAN-18:10
Boiler Parasitic:Heating:Electricity 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Pumps:Electricity 597.12 3435.87 01-JAN-00:40 61546.80 01-AUG-09:20
General:Pumps:Electricity 597.12 3435.87 01-JAN-00:40 61546.80 01-AUG-09:20
WIRED_LTG_ELECTRICITY 110.61 0.00 01-JAN-00:10 10841.96 03-JAN-08:20
WIRED_INT_EQUIP 5334.97 88964.76 31-MAR-23:10 305206.10 03-APR-07:10


Annual and Peak Values - Natural Gas

Natural Gas Annual Value [GJ] Natural Gas Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Natural Gas Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
NaturalGas:Facility 1693.23 8146.58 09-JUL-16:20 1803266.60 13-FEB-07:10
NaturalGas:Plant 1693.23 8146.58 09-JUL-16:20 1803266.60 13-FEB-07:10
Heating:NaturalGas 958.69 0.00 01-JAN-00:40 1771654.06 13-FEB-07:10
Boiler:Heating:NaturalGas 958.69 0.00 01-JAN-00:40 1771654.06 13-FEB-07:10
WaterSystems:NaturalGas 734.54 8146.58 02-JAN-06:10 82149.84 02-FEB-13:00
Water Heater:WaterSystems:NaturalGas 734.54 8146.58 02-JAN-06:10 82149.84 02-FEB-13:00


Annual and Peak Values - Cooling

Cooling Annual Value [GJ] Cooling Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Cooling Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
PlantLoopCoolingDemand:Facility 23285.21 137993.16 09-JAN-07:10 2645895.30 24-AUG-10:50
PlantLoopCoolingDemand:HVAC 23285.21 137993.16 09-JAN-07:10 2645895.30 24-AUG-10:50
CoolingCoils:PlantLoopCoolingDemand 23285.21 137993.16 09-JAN-07:10 2645895.30 24-AUG-10:50


Annual and Peak Values - Water

Annual Value [m3] Minimum Value [m3/s] Timestamp of Minimum {TIMESTAMP} Maximum Value [m3/s] Timestamp of Maximum {TIMESTAMP}
Water:Facility 11083.99 0.00 01-JAN-00:10 0.00 17-APR-14:40
Water:HVAC 3.33 0.00 01-JAN-00:10 0.00 05-JAN-18:10
Humidifier:Water 3.33 0.00 01-JAN-00:10 0.00 05-JAN-18:10
General:Humidifier:Water 3.33 0.00 01-JAN-00:10 0.00 05-JAN-18:10
MainsWater:Facility 11083.99 0.00 01-JAN-00:10 0.00 17-APR-14:40
MainsWater:HVAC 3.33 0.00 01-JAN-00:10 0.00 05-JAN-18:10
Humidifier:MainsWater 3.33 0.00 01-JAN-00:10 0.00 05-JAN-18:10
General:Humidifier:MainsWater 3.33 0.00 01-JAN-00:10 0.00 05-JAN-18:10
Water:Plant 11080.66 0.00 01-JAN-00:10 0.00 17-APR-14:40
WaterSystems:Water 2280.17 0.00 01-JAN-00:10 0.00 02-JAN-12:10
WaterUse:WaterSystems:Water 2280.17 0.00 01-JAN-00:10 0.00 02-JAN-12:10
MainsWater:Plant 11080.66 0.00 01-JAN-00:10 0.00 17-APR-14:40
WaterSystems:MainsWater 2280.17 0.00 01-JAN-00:10 0.00 02-JAN-12:10
WaterUse:WaterSystems:MainsWater 2280.17 0.00 01-JAN-00:10 0.00 02-JAN-12:10
Water Heater:WaterSystems:Water 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Water Heater:WaterSystems:MainsWater 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
HeatRejection:Water 8800.50 0.00 01-JAN-00:10 0.00 17-APR-14:40
General:HeatRejection:Water 8800.50 0.00 01-JAN-00:10 0.00 17-APR-14:40
HeatRejection:MainsWater 8800.50 0.00 01-JAN-00:10 0.00 17-APR-14:40
General:HeatRejection:MainsWater 8800.50 0.00 01-JAN-00:10 0.00 17-APR-14:40


Annual and Peak Values - Other by Weight/Mass

Annual Value [kg] Minimum Value [kg/s] Timestamp of Minimum {TIMESTAMP} Maximum Value [kg/s] Timestamp of Maximum {TIMESTAMP}
Carbon Equivalent:Facility 0.00 0.000 01-JAN-00:10 0.000 01-JAN-00:10
CarbonEquivalentEmissions:Carbon Equivalent 0.00 0.000 01-JAN-00:10 0.000 01-JAN-00:10


Annual and Peak Values - Other Volumetric

Annual Value [m3] Minimum Value [m3/s] Timestamp of Minimum {TIMESTAMP} Maximum Value [m3/s] Timestamp of Maximum {TIMESTAMP}
None          


Annual and Peak Values - Other Liquid/Gas

Annual Value [L] Minimum Value [L] Timestamp of Minimum {TIMESTAMP} Maximum Value [L] Timestamp of Maximum {TIMESTAMP}
None          


Annual and Peak Values - Other

Annual Value [GJ] Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
EnergyTransfer:Facility 79800.47 212654.60 09-JAN-04:50 10239344.34 17-AUG-15:30
EnergyTransfer:Building 20054.82 87784.68 14-JAN-18:40 1655260.46 02-AUG-16:00
EnergyTransfer:Zone:BASEMENT 699.74 0.00 01-JAN-00:10 72612.43 10-OCT-05:10
Heating:EnergyTransfer 347.38 0.00 19-JAN-18:20 1062292.26 09-JAN-05:10
Heating:EnergyTransfer:Zone:BASEMENT 3.32 0.00 01-JAN-00:10 24297.13 08-JUL-16:10
General:Heating:EnergyTransfer 347.38 0.00 19-JAN-18:20 1062292.26 09-JAN-05:10
General:Heating:EnergyTransfer:Zone:BASEMENT 3.32 0.00 01-JAN-00:10 24297.13 08-JUL-16:10
Cooling:EnergyTransfer 19707.45 84914.31 09-JAN-05:40 1655260.46 02-AUG-16:00
Cooling:EnergyTransfer:Zone:BASEMENT 696.43 0.00 01-JAN-00:10 72612.43 10-OCT-05:10
General:Cooling:EnergyTransfer 19707.45 84914.31 09-JAN-05:40 1655260.46 02-AUG-16:00
General:Cooling:EnergyTransfer:Zone:BASEMENT 696.43 0.00 01-JAN-00:10 72612.43 10-OCT-05:10
EnergyTransfer:Zone:CORE_BOTTOM 694.41 0.00 01-JAN-00:10 55504.08 14-APR-14:50
Heating:EnergyTransfer:Zone:CORE_BOTTOM 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:CORE_BOTTOM 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:CORE_BOTTOM 694.41 0.00 01-JAN-00:10 55504.08 14-APR-14:50
General:Cooling:EnergyTransfer:Zone:CORE_BOTTOM 694.41 0.00 01-JAN-00:10 55504.08 14-APR-14:50
EnergyTransfer:Zone:CORE_MID 5185.60 0.00 01-JAN-00:10 457157.82 17-AUG-16:00
Heating:EnergyTransfer:Zone:CORE_MID 3.79 0.00 01-JAN-00:10 325463.72 09-JAN-05:10
General:Heating:EnergyTransfer:Zone:CORE_MID 3.79 0.00 01-JAN-00:10 325463.72 09-JAN-05:10
Cooling:EnergyTransfer:Zone:CORE_MID 5181.82 0.00 01-JAN-00:10 457157.82 17-AUG-16:00
General:Cooling:EnergyTransfer:Zone:CORE_MID 5181.82 0.00 01-JAN-00:10 457157.82 17-AUG-16:00
EnergyTransfer:Zone:CORE_TOP 504.89 0.00 01-JAN-00:40 73050.78 17-JAN-05:20
Heating:EnergyTransfer:Zone:CORE_TOP 7.95 0.00 01-JAN-00:10 73050.78 17-JAN-05:20
General:Heating:EnergyTransfer:Zone:CORE_TOP 7.95 0.00 01-JAN-00:10 73050.78 17-JAN-05:20
Cooling:EnergyTransfer:Zone:CORE_TOP 496.94 0.00 01-JAN-00:40 53998.58 07-JUL-15:50
General:Cooling:EnergyTransfer:Zone:CORE_TOP 496.94 0.00 01-JAN-00:40 53998.58 07-JUL-15:50
EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 86.55 0.00 01-JAN-00:10 11008.58 09-AUG-14:40
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 0.55 0.00 01-JAN-00:10 6679.71 13-FEB-05:10
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 0.55 0.00 01-JAN-00:10 6679.71 13-FEB-05:10
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 86.00 0.00 01-JAN-00:10 11008.58 09-AUG-14:40
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 86.00 0.00 01-JAN-00:10 11008.58 09-AUG-14:40
EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 74.16 0.00 01-JAN-00:10 12442.03 07-JUL-09:10
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 0.38 0.00 01-JAN-00:10 4760.39 13-FEB-05:10
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 0.38 0.00 01-JAN-00:10 4760.39 13-FEB-05:10
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 73.77 0.00 01-JAN-00:10 12442.03 07-JUL-09:10
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 73.77 0.00 01-JAN-00:10 12442.03 07-JUL-09:10
EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 111.22 0.00 01-JAN-00:10 17305.42 10-OCT-13:40
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 0.68 0.00 01-JAN-00:10 9287.16 09-JAN-05:10
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 0.68 0.00 01-JAN-00:10 9287.16 09-JAN-05:10
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 110.53 0.00 01-JAN-00:10 17305.42 10-OCT-13:40
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 110.53 0.00 01-JAN-00:10 17305.42 10-OCT-13:40
EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 108.83 0.00 01-JAN-00:10 16545.55 18-AUG-16:00
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 0.06 0.00 01-JAN-00:10 2319.54 09-JAN-06:10
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 0.06 0.00 01-JAN-00:10 2319.54 09-JAN-06:10
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 108.77 0.00 01-JAN-00:10 16545.55 18-AUG-16:00
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 108.77 0.00 01-JAN-00:10 16545.55 18-AUG-16:00
EnergyTransfer:Zone:PERIMETER_MID_ZN_3 692.66 0.00 01-JAN-00:10 132790.48 13-FEB-05:20
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 82.91 0.00 01-JAN-00:10 132790.48 13-FEB-05:20
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 82.91 0.00 01-JAN-00:10 132790.48 13-FEB-05:20
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 609.76 0.00 01-JAN-00:10 103421.18 14-JUL-15:00
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 609.76 0.00 01-JAN-00:10 103421.18 14-JUL-15:00
EnergyTransfer:Zone:PERIMETER_MID_ZN_2 647.46 0.00 01-JAN-00:10 131258.11 07-JUL-09:00
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 43.15 0.00 01-JAN-00:10 121631.84 13-FEB-05:20
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 43.15 0.00 01-JAN-00:10 121631.84 13-FEB-05:20
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 604.32 0.00 01-JAN-00:10 131258.11 07-JUL-09:00
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 604.32 0.00 01-JAN-00:10 131258.11 07-JUL-09:00
EnergyTransfer:Zone:PERIMETER_MID_ZN_1 932.96 0.00 01-JAN-00:10 166479.16 10-OCT-13:40
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 40.77 0.00 01-JAN-00:10 150361.04 13-FEB-05:20
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 40.77 0.00 01-JAN-00:10 150361.04 13-FEB-05:20
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 892.19 0.00 01-JAN-00:10 166479.16 10-OCT-13:40
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 892.19 0.00 01-JAN-00:10 166479.16 10-OCT-13:40
EnergyTransfer:Zone:PERIMETER_MID_ZN_4 682.56 0.00 01-JAN-00:10 133434.16 02-AUG-16:00
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 32.53 0.00 01-JAN-00:10 109725.12 13-FEB-05:20
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 32.53 0.00 01-JAN-00:10 109725.12 13-FEB-05:20
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 650.03 0.00 01-JAN-00:10 133434.16 02-AUG-16:00
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 650.03 0.00 01-JAN-00:10 133434.16 02-AUG-16:00
EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 79.29 0.00 01-JAN-00:40 16305.95 13-FEB-04:10
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 19.38 0.00 01-JAN-00:40 16305.95 13-FEB-04:10
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 19.38 0.00 01-JAN-00:40 16305.95 13-FEB-04:10
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 59.91 0.00 01-JAN-00:10 11523.89 14-JUL-15:00
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 59.91 0.00 01-JAN-00:10 11523.89 14-JUL-15:00
EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 69.69 0.00 01-JAN-00:40 14386.35 13-FEB-05:10
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 9.99 0.00 01-JAN-00:40 14386.35 13-FEB-05:10
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 9.99 0.00 01-JAN-00:40 14386.35 13-FEB-05:10
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 59.70 0.00 01-JAN-00:10 13542.71 07-JUL-09:30
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 59.70 0.00 01-JAN-00:10 13542.71 07-JUL-09:30
EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 97.90 0.00 01-JAN-00:40 18142.62 13-FEB-04:10
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 10.98 0.00 01-JAN-00:40 18142.62 13-FEB-04:10
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 10.98 0.00 01-JAN-00:40 18142.62 13-FEB-04:10
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 86.92 0.00 01-JAN-00:10 17868.99 10-OCT-13:40
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 86.92 0.00 01-JAN-00:10 17868.99 10-OCT-13:40
EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 72.71 0.00 01-JAN-00:40 14550.18 09-JAN-05:10
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 8.10 0.00 01-JAN-00:40 14550.18 09-JAN-05:10
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 8.10 0.00 01-JAN-00:40 14550.18 09-JAN-05:10
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 64.60 0.00 01-JAN-00:10 14161.61 02-AUG-16:00
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 64.60 0.00 01-JAN-00:10 14161.61 02-AUG-16:00
EnergyTransfer:Zone:GROUNDFLOOR_PLENUM 69.97 0.00 01-JAN-00:10 8194.13 05-JUL-16:00
Heating:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM 1.18 0.00 01-JAN-00:10 3209.84 17-DEC-13:20
General:Heating:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM 1.18 0.00 01-JAN-00:10 3209.84 17-DEC-13:20
Cooling:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM 68.79 0.00 01-JAN-00:10 8194.13 05-JUL-16:00
General:Cooling:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM 68.79 0.00 01-JAN-00:10 8194.13 05-JUL-16:00
EnergyTransfer:Zone:MIDFLOOR_PLENUM 518.93 0.00 01-JAN-00:10 92005.24 09-JAN-06:10
Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM 52.01 0.00 01-JAN-00:10 92005.24 09-JAN-06:10
General:Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM 52.01 0.00 01-JAN-00:10 92005.24 09-JAN-06:10
Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM 466.93 0.00 01-JAN-00:10 71888.96 18-AUG-16:00
General:Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM 466.93 0.00 01-JAN-00:10 71888.96 18-AUG-16:00
EnergyTransfer:Zone:TOPFLOOR_PLENUM 95.95 0.00 01-JAN-00:40 25871.17 13-FEB-05:40
Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM 24.73 0.00 01-JAN-00:40 25871.17 13-FEB-05:40
General:Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM 24.73 0.00 01-JAN-00:40 25871.17 13-FEB-05:40
Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM 71.23 0.00 01-JAN-00:10 19740.61 07-JUL-15:10
General:Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM 71.23 0.00 01-JAN-00:10 19740.61 07-JUL-15:10
EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 139.16 169.28 09-JAN-05:50 7933.39 09-APR-18:20
Heating:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 139.16 169.28 09-JAN-05:50 7933.39 09-APR-18:20
General:Cooling:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 139.16 169.28 09-JAN-05:50 7933.39 09-APR-18:20
EnergyTransfer:Zone:DATACENTER_MID_ZN_6 1216.40 4.35 09-JAN-07:40 74668.91 14-APR-18:30
Heating:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 4.16 0.00 02-JAN-09:50 5473.67 16-JAN-03:20
General:Heating:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 4.16 0.00 02-JAN-09:50 5473.67 16-JAN-03:20
Cooling:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 1212.24 0.00 01-JAN-00:10 74668.91 14-APR-18:30
General:Cooling:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 1212.24 0.00 01-JAN-00:10 74668.91 14-APR-18:30
EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 115.70 0.15 11-JAN-07:40 7653.22 13-AUG-18:50
Heating:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 0.77 0.00 02-JAN-13:10 599.64 22-JAN-19:10
General:Heating:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 0.77 0.00 02-JAN-13:10 599.64 22-JAN-19:10
Cooling:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 114.94 0.00 01-JAN-00:10 7653.22 13-AUG-18:50
General:Cooling:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 114.94 0.00 01-JAN-00:10 7653.22 13-AUG-18:50
EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 7158.08 84704.80 09-JAN-05:00 369804.16 07-AUG-21:10
Heating:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 7158.08 84704.80 09-JAN-05:00 369804.16 07-AUG-21:10
General:Cooling:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 7158.08 84704.80 09-JAN-05:00 369804.16 07-AUG-21:10
PlantLoopHeatingDemand:Facility 1071.72 0.00 01-JAN-00:40 1515192.75 13-FEB-07:10
PlantLoopHeatingDemand:Plant 371.93 0.00 01-JAN-00:10 47925.51 31-JAN-12:20
WaterSystems:PlantLoopHeatingDemand 371.93 0.00 01-JAN-00:10 47925.51 31-JAN-12:20
General:WaterSystems:PlantLoopHeatingDemand 371.93 0.00 01-JAN-00:10 47925.51 31-JAN-12:20
EnergyTransfer:HVAC 23458.23 121975.26 09-JAN-04:50 2925379.07 10-AUG-16:00
HeatingCoils:EnergyTransfer 699.79 0.00 01-JAN-00:40 1499298.85 13-FEB-07:10
PlantLoopHeatingDemand:HVAC 699.79 0.00 01-JAN-00:40 1499298.85 13-FEB-07:10
HeatingCoils:PlantLoopHeatingDemand 699.79 0.00 01-JAN-00:40 1499298.85 13-FEB-07:10
CoolingCoils:EnergyTransfer 20561.51 109985.14 09-JAN-07:10 2489039.89 24-AUG-10:50
HeatRecoveryForHeating:EnergyTransfer 689.01 0.00 01-JAN-00:10 724585.61 03-FEB-08:10
HeatRecoveryForCooling:EnergyTransfer 1507.92 0.00 01-JAN-00:10 651624.31 07-JUL-12:00
EnergyTransfer:Plant 36287.42 0.00 01-JAN-00:40 6279859.32 24-AUG-10:50
LoopToLoop:EnergyTransfer 11192.38 0.00 01-JAN-00:10 1980599.88 24-AUG-10:50
WaterSystems:EnergyTransfer 371.93 0.00 01-JAN-00:10 47925.51 31-JAN-12:20
WaterUse:WaterSystems:EnergyTransfer 371.93 0.00 01-JAN-00:10 47925.51 31-JAN-12:20
Boilers:EnergyTransfer 693.47 0.00 01-JAN-00:40 1471567.77 13-FEB-07:10
Chillers:EnergyTransfer 11174.14 0.00 01-JAN-00:10 1988947.14 24-AUG-10:50
HeatRejection:EnergyTransfer 12855.49 0.00 01-JAN-00:10 2281777.71 24-AUG-10:50
General:HeatRejection:EnergyTransfer 12855.49 0.00 01-JAN-00:10 2281777.71 24-AUG-10:50
Water Heater:WaterSystems:PlantLoopHeatingDemand 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10



Table of Contents

Report: Sensible Heat Gain Summary

For: Entire Facility

Timestamp: 2023-10-16 08:43:24

Annual Building Sensible Heat Gain Components

HVAC Zone Eq & Other Sensible Air Heating [GJ] HVAC Zone Eq & Other Sensible Air Cooling [GJ] HVAC Terminal Unit Sensible Air Heating [GJ] HVAC Terminal Unit Sensible Air Cooling [GJ] HVAC Input Heated Surface Heating [GJ] HVAC Input Cooled Surface Cooling [GJ] People Sensible Heat Addition [GJ] Lights Sensible Heat Addition [GJ] Equipment Sensible Heat Addition [GJ] Window Heat Addition [GJ] Interzone Air Transfer Heat Addition [GJ] Infiltration Heat Addition [GJ] Opaque Surface Conduction and Other Heat Addition [GJ] Equipment Sensible Heat Removal [GJ] Window Heat Removal [GJ] Interzone Air Transfer Heat Removal [GJ] Infiltration Heat Removal [GJ] Opaque Surface Conduction and Other Heat Removal [GJ]
BASEMENT 0.000 0.000 3.316 -696.430 0.000 0.000 92.726 262.844 424.397 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 -86.853
CORE_BOTTOM 0.000 0.000 0.000 -694.403 0.000 0.000 83.609 236.053 289.614 0.000 0.000 0.000 85.128 0.000 0.000 0.000 0.000 -0.000
CORE_MID 0.000 0.000 3.787 -5181.789 0.000 0.000 856.533 2360.527 2896.128 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 -935.186
CORE_TOP 0.000 0.000 7.949 -496.932 0.000 0.000 87.985 236.053 289.613 0.000 0.000 0.000 0.001 0.000 0.000 0.000 0.000 -124.667
PERIMETER_BOT_ZN_3 0.000 0.000 0.550 -85.997 0.000 0.000 10.858 17.718 36.365 30.229 0.000 0.237 54.383 0.000 -59.484 0.000 -4.860 0.000
PERIMETER_BOT_ZN_2 0.000 0.000 0.384 -73.774 0.000 0.000 7.017 11.188 23.435 50.431 0.000 0.166 19.398 0.000 -35.060 0.000 -3.186 0.000
PERIMETER_BOT_ZN_1 0.000 0.000 0.684 -110.533 0.000 0.000 10.727 17.199 36.366 88.593 0.000 0.226 14.542 0.000 -52.867 0.000 -4.936 0.000
PERIMETER_BOT_ZN_4 0.000 0.000 0.055 -108.770 0.000 0.000 6.905 11.291 23.435 49.594 0.000 0.139 63.871 0.000 -42.887 0.000 -3.634 0.000
PERIMETER_MID_ZN_3 0.000 0.000 82.909 -609.741 0.000 0.000 112.901 176.434 363.654 316.945 0.000 5.602 169.960 0.000 -521.552 0.000 -97.111 0.000
PERIMETER_MID_ZN_2 0.000 0.000 43.147 -604.306 0.000 0.000 53.186 111.633 234.352 507.979 0.000 3.568 36.954 0.000 -320.012 0.000 -66.502 -0.003
PERIMETER_MID_ZN_1 0.000 0.000 40.769 -892.166 0.000 0.000 109.069 171.730 363.660 887.452 0.000 5.069 0.050 0.000 -498.896 0.000 -107.001 -79.685
PERIMETER_MID_ZN_4 0.000 0.000 32.533 -650.011 0.000 0.000 72.591 112.586 234.351 513.379 0.000 3.354 109.268 0.000 -358.400 0.000 -69.651 0.000
PERIMETER_TOP_ZN_3 0.000 0.000 19.383 -59.906 0.000 0.000 11.408 17.640 36.365 31.844 0.000 0.665 3.319 0.000 -49.351 0.000 -11.368 -0.000
PERIMETER_TOP_ZN_2 0.000 0.000 9.992 -59.701 0.000 0.000 7.278 11.162 23.435 50.988 0.000 0.422 0.001 0.000 -30.428 0.000 -7.794 -5.355
PERIMETER_TOP_ZN_1 0.000 0.000 10.980 -86.922 0.000 0.000 11.058 17.171 36.366 89.197 0.000 0.603 0.000 0.000 -47.151 0.000 -12.427 -18.875
PERIMETER_TOP_ZN_4 0.000 0.000 8.104 -64.600 0.000 0.000 7.340 11.258 23.435 51.363 0.000 0.406 5.039 0.000 -34.156 0.000 -8.189 -0.001
DATACENTER_BOT_ZN_6 0.000 0.000 0.000 -139.158 0.000 0.000 0.949 6.628 153.881 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 -22.299
DATACENTER_MID_ZN_6 0.000 0.000 4.160 -1212.240 0.000 0.000 9.494 66.280 1538.806 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 -406.499
DATACENTER_TOP_ZN_6 0.000 0.000 0.765 -114.936 0.000 0.000 0.952 6.628 153.881 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 -47.290
DATACENTER_BASEMENT_ZN_6 0.000 0.000 0.000 -7158.088 0.000 0.000 20.231 74.111 7494.857 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 -431.111
GROUNDFLOOR_PLENUM 1.178 -68.790 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.411 77.992 0.000 0.000 0.000 -10.791 0.000
MIDFLOOR_PLENUM 52.008 -466.920 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 7.791 582.352 0.000 0.000 0.000 -175.231 -0.001
TOPFLOOR_PLENUM 24.726 -71.227 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.672 63.782 0.000 0.000 0.000 -17.953 -0.002
Total Facility 77.912 -606.937 269.468 -19100.403 0.000 0.000 1572.816 3936.135 14676.396 2667.994 0.000 29.329 1286.040 0.000 -2050.243 0.000 -600.635 -2157.828


Peak Cooling Sensible Heat Gain Components

Time of Peak {TIMESTAMP} HVAC Zone Eq & Other Sensible Air Heating [W] HVAC Zone Eq & Other Sensible Air Cooling [W] HVAC Terminal Unit Sensible Air Heating [W] HVAC Terminal Unit Sensible Air Cooling [W] HVAC Input Heated Surface Heating [W] HVAC Input Cooled Surface Cooling [W] People Sensible Heat Addition [W] Lights Sensible Heat Addition [W] Equipment Sensible Heat Addition [W] Window Heat Addition [W] Interzone Air Transfer Heat Addition [W] Infiltration Heat Addition [W] Opaque Surface Conduction and Other Heat Addition [W] Equipment Sensible Heat Removal [W] Window Heat Removal [W] Interzone Air Transfer Heat Removal [W] Infiltration Heat Removal [W] Opaque Surface Conduction and Other Heat Removal [W]
BASEMENT 30-OCT-04:11 0.00 0.00 0.00 -120458.27 0.00 0.00 0.00 2550.13 13457.54 0.00 0.00 0.00 104450.60 0.00 -0.00 0.00 0.00 0.00
CORE_BOTTOM 11-SEP-04:13 0.00 0.00 0.00 -99844.02 0.00 0.00 0.00 2290.20 5937.65 0.00 0.00 0.00 91616.17 0.00 -0.00 0.00 0.00 0.00
CORE_MID 21-JUN-04:11 0.00 0.00 0.00 -868940.60 0.00 0.00 0.00 22901.98 59376.23 0.00 0.00 0.00 786662.39 0.00 -0.00 0.00 0.00 0.00
CORE_TOP 16-JUN-04:11 0.00 0.00 0.00 -86134.56 0.00 0.00 0.00 2290.20 5937.62 0.00 0.00 0.00 77906.74 0.00 -0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_3 17-JUL-04:12 0.00 0.00 0.00 -14290.65 0.00 0.00 0.00 287.56 745.56 0.00 0.00 0.00 14789.74 0.00 -1494.53 0.00 -37.68 0.00
PERIMETER_BOT_ZN_2 04-JUN-09:02 0.00 0.00 0.00 -20027.50 0.00 0.00 22.31 44.08 464.11 13886.58 0.00 0.00 5642.38 0.00 -0.00 0.00 -31.97 0.00
PERIMETER_BOT_ZN_1 09-OCT-14:12 0.00 0.00 0.00 -22775.84 0.00 0.00 35.69 68.40 720.19 15977.52 0.00 0.00 5995.51 0.00 -0.00 0.00 -21.49 0.00
PERIMETER_BOT_ZN_4 11-JUN-15:51 0.00 0.00 0.00 -25887.97 0.00 0.00 20.11 44.08 464.11 13631.00 0.00 106.69 11621.98 0.00 -0.00 0.00 0.00 0.00
PERIMETER_MID_ZN_3 25-JUN-16:11 0.00 0.00 0.00 -163819.49 0.00 0.00 441.85 684.02 7201.84 50582.63 0.00 5845.73 99063.41 0.00 -0.00 0.00 0.00 0.00
PERIMETER_MID_ZN_2 27-AUG-09:41 0.00 0.00 0.00 -212991.46 0.00 0.00 213.19 440.81 4641.14 129270.69 0.00 0.00 78662.40 0.00 -0.00 0.00 -236.77 0.00
PERIMETER_MID_ZN_1 08-OCT-14:02 0.00 0.00 0.00 -216591.69 0.00 0.00 359.29 684.04 7201.95 170022.78 0.00 0.00 39557.78 0.00 -0.00 0.00 -1234.15 0.00
PERIMETER_MID_ZN_4 23-JUL-17:11 0.00 0.00 0.00 -229029.43 0.00 0.00 0.00 440.81 3603.49 124501.07 0.00 418.79 100065.27 0.00 -0.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_3 25-JUN-16:11 0.00 0.00 0.00 -19369.14 0.00 0.00 40.78 68.40 720.18 4810.08 0.00 639.73 13089.97 0.00 -0.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_2 27-AUG-09:12 0.00 0.00 0.00 -21241.64 0.00 0.00 21.78 44.08 464.11 13971.58 0.00 0.00 6757.86 0.00 -0.00 0.00 -17.78 0.00
PERIMETER_TOP_ZN_1 09-OCT-14:12 0.00 0.00 0.00 -23883.83 0.00 0.00 36.10 68.40 720.19 15834.10 0.00 0.00 7294.40 0.00 -0.00 0.00 -69.37 0.00
PERIMETER_TOP_ZN_4 25-JUN-16:11 0.00 0.00 0.00 -24612.80 0.00 0.00 19.04 44.08 464.11 12741.08 0.00 293.10 11051.39 0.00 -0.00 0.00 0.00 0.00
DATACENTER_BOT_ZN_6 09-APR-18:15 0.00 0.00 0.00 -7933.39 0.00 0.00 0.00 32.15 7794.42 0.00 0.00 0.00 106.81 0.00 -0.00 0.00 0.00 0.00
DATACENTER_MID_ZN_6 14-APR-18:30 0.00 0.00 0.00 -74666.95 0.00 0.00 106.16 1929.04 77944.22 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 0.00 -5312.47
DATACENTER_TOP_ZN_6 13-AUG-18:52 0.00 0.00 0.00 -7660.98 0.00 0.00 0.00 32.15 7794.42 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 0.00 -165.60
DATACENTER_BASEMENT_ZN_6 07-AUG-21:14 0.00 0.00 0.00 -370519.97 0.00 0.00 113.75 719.03 379632.52 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 0.00 -9945.33
GROUNDFLOOR_PLENUM 05-SEP-05:02 0.00 -12621.18 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 12676.43 0.00 -0.00 0.00 -55.25 0.00
MIDFLOOR_PLENUM 12-FEB-06:01 0.00 -100658.96 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 172572.79 0.00 -0.00 0.00 -71913.83 0.00
TOPFLOOR_PLENUM 07-JUL-15:10 0.00 -19740.12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 110.69 19629.43 0.00 -0.00 0.00 0.00 0.00
Total Facility 17-AUG-04:12 0.00 55851.07 0.00 -2017906.41 0.00 0.00 0.00 42872.09 587299.42 0.00 0.00 0.00 1388106.59 0.00 -54098.94 0.00 -2123.80 0.00


Peak Heating Sensible Heat Gain Components

Time of Peak {TIMESTAMP} HVAC Zone Eq & Other Sensible Air Heating [W] HVAC Zone Eq & Other Sensible Air Cooling [W] HVAC Terminal Unit Sensible Air Heating [W] HVAC Terminal Unit Sensible Air Cooling [W] HVAC Input Heated Surface Heating [W] HVAC Input Cooled Surface Cooling [W] People Sensible Heat Addition [W] Lights Sensible Heat Addition [W] Equipment Sensible Heat Addition [W] Window Heat Addition [W] Interzone Air Transfer Heat Addition [W] Infiltration Heat Addition [W] Opaque Surface Conduction and Other Heat Addition [W] Equipment Sensible Heat Removal [W] Window Heat Removal [W] Interzone Air Transfer Heat Removal [W] Infiltration Heat Removal [W] Opaque Surface Conduction and Other Heat Removal [W]
BASEMENT 08-JUL-16:01 0.00 0.00 25904.38 0.00 0.00 0.00 520.12 1274.92 13457.54 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 0.00 -41156.97
CORE_BOTTOM - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CORE_MID 09-JAN-05:01 0.00 0.00 378434.73 0.00 0.00 0.00 0.00 22901.98 59376.23 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 0.00 -460712.94
CORE_TOP 09-JAN-04:11 0.00 0.00 80513.06 0.00 0.00 0.00 0.00 1144.97 5937.62 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 0.00 -87595.66
PERIMETER_BOT_ZN_3 13-FEB-05:01 0.00 0.00 12406.37 0.00 0.00 0.00 0.00 287.56 745.56 0.00 0.00 0.00 0.00 0.00 -6938.49 0.00 -1340.17 -5160.83
PERIMETER_BOT_ZN_2 09-JAN-05:01 0.00 0.00 9609.96 0.00 0.00 0.00 0.00 185.31 480.47 0.00 0.00 0.00 0.00 0.00 -3780.79 0.00 -593.32 -5901.63
PERIMETER_BOT_ZN_1 09-JAN-04:17 0.00 0.00 15051.78 0.00 0.00 0.00 0.00 143.77 745.57 0.00 0.00 0.00 0.00 0.00 -5314.15 0.00 -796.97 -9830.00
PERIMETER_BOT_ZN_4 09-JAN-05:01 0.00 0.00 6766.46 0.00 0.00 0.00 0.00 185.31 480.46 0.00 0.00 0.00 0.00 0.00 -4112.88 0.00 -619.39 -2699.96
PERIMETER_MID_ZN_3 12-FEB-06:01 0.00 0.00 150087.53 0.00 0.00 0.00 909.34 1437.63 7201.84 0.00 0.00 0.00 0.00 0.00 -77734.49 0.00 -40749.21 -41152.63
PERIMETER_MID_ZN_2 12-FEB-06:01 0.00 0.00 158058.44 0.00 0.00 0.00 586.29 926.46 4641.14 0.00 0.00 0.00 0.00 0.00 -49762.85 0.00 -27528.39 -86921.08
PERIMETER_MID_ZN_1 12-FEB-06:01 0.00 0.00 175451.53 0.00 0.00 0.00 906.88 1437.66 7201.95 0.00 0.00 0.00 0.00 0.00 -75343.89 0.00 -41082.82 -68571.31
PERIMETER_MID_ZN_4 12-FEB-06:01 0.00 0.00 158031.42 0.00 0.00 0.00 580.66 926.46 4641.11 0.00 0.00 0.00 0.00 0.00 -52898.57 0.00 -27806.67 -83474.40
PERIMETER_TOP_ZN_3 12-FEB-00:02 0.00 0.00 17448.77 0.00 0.00 0.00 0.00 143.76 559.17 0.00 0.00 0.00 0.00 0.00 -7034.88 0.00 -4095.22 -7021.60
PERIMETER_TOP_ZN_2 12-FEB-06:01 0.00 0.00 17540.19 0.00 0.00 0.00 59.96 92.65 464.11 0.00 0.00 0.00 0.00 0.00 -4746.28 0.00 -3335.14 -10075.49
PERIMETER_TOP_ZN_1 12-FEB-06:01 0.00 0.00 19885.99 0.00 0.00 0.00 92.69 143.77 720.19 0.00 0.00 0.00 0.00 0.00 -7173.53 0.00 -4977.47 -8691.65
PERIMETER_TOP_ZN_4 12-FEB-06:01 0.00 0.00 18938.25 0.00 0.00 0.00 59.47 92.65 464.11 0.00 0.00 0.00 0.00 0.00 -5063.58 0.00 -3384.54 -11106.35
DATACENTER_BOT_ZN_6 - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
DATACENTER_MID_ZN_6 16-JAN-03:20 0.00 0.00 5473.67 0.00 0.00 0.00 0.00 321.53 19486.06 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 0.00 -25281.25
DATACENTER_TOP_ZN_6 15-JAN-18:45 0.00 0.00 601.45 0.00 0.00 0.00 0.00 32.15 1948.61 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 0.00 -2582.21
DATACENTER_BASEMENT_ZN_6 - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
GROUNDFLOOR_PLENUM 26-DEC-05:11 14272.37 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 -2195.50 -12076.88
MIDFLOOR_PLENUM 06-JAN-12:00 140383.27 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 -6815.93 -133567.34
TOPFLOOR_PLENUM 13-FEB-05:09 26966.85 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 -4947.40 -22019.44
Total Facility 09-JAN-05:01 -78909.11 107947.93 1128840.47 -107947.93 0.00 0.00 0.00 42872.09 232425.23 0.00 0.00 0.00 0.00 0.00 -209583.83 0.00 -114244.94 -1001399.90



Table of Contents

Report: Standard 62.1 Summary

For: Entire Facility

Timestamp: 2023-10-16 08:43:24

System Ventilation Requirements for Cooling

Sum of Zone Primary Air Flow - Vpz-sum [m3/s] System Population - Ps Sum of Zone Population - Pz-sum Occupant Diversity - D Origin of D Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] System Primary Airflow - Vps [m3/s] Average Outdoor Air Fraction - Xs System Ventilation Efficiency - Ev Calculation Method for Ev Outdoor Air Intake Flow - Vot [m3/s] Percent Outdoor Air - %OA Environment Name of Peak System Population - Ps Date and Time of Last Peak System Population - Ps
VAV_BOT WITH REHEAT 11.1711 0.0000 0.0000 1.0000 Calculated from schedules 0.0000 10.0760 0.0000 1.0000 Not calculated 0.0000 0.0000    
VAV_MID WITH REHEAT 105.6802 0.0000 0.0000 1.0000 Calculated from schedules 0.0000 94.0360 0.0000 1.0000 Not calculated 0.0000 0.0000    
VAV_TOP WITH REHEAT 10.8322 0.0000 0.0000 1.0000 Calculated from schedules 0.0000 10.1979 0.0000 1.0000 Not calculated 0.0000 0.0000    
CAV_BAS 6.0861 0.0000 149.6021 1.0000 Calculated from schedules 1.2002 6.0861 0.1972 1.0000 Not calculated 1.2002 0.1972    
AIRLOOP DATACENTER BASEMENT 22.1364 0.0000 42.1814 1.0000 Calculated from schedules 0.3384 22.1366 0.0153 1.0000 Not calculated 0.3384 0.0153    
AIRLOOP DATACENTER BOT 0.4922 0.0000 1.9486 1.0000 Calculated from schedules 0.0156 0.4922 0.0318 1.0000 Not calculated 0.0156 0.0318    
AIRLOOP DATACENTER MID 4.6918 0.0000 19.4861 1.0000 Calculated from schedules 0.1563 4.6918 0.0333 1.0000 Not calculated 0.1563 0.0333    
AIRLOOP DATACENTER TOP 0.4779 0.0000 1.9486 1.0000 Calculated from schedules 0.0156 0.4779 0.0327 1.0000 Not calculated 0.0156 0.0327    


System Ventilation Requirements for Heating

Sum of Zone Primary Air Flow - Vpz-sum [m3/s] System Population - Ps Sum of Zone Population - Pz-sum Occupant Diversity - D Origin of D Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] System Primary Airflow - Vps [m3/s] Average Outdoor Air Fraction - Xs System Ventilation Efficiency - Ev Calculation Method for Ev Outdoor Air Intake Flow Vot [m3/s] Percent Outdoor Air - %OA Environment Name of Peak System Population - Ps Date and Time of Last Peak System Population - Ps
VAV_BOT WITH REHEAT 5.5856 0.0000 0.0000 1.0000 Calculated from schedules 0.0000 2.9518 0.0000 1.0000 Not calculated 0.0000 0.0000    
VAV_MID WITH REHEAT 52.8401 0.0000 0.0000 1.0000 Calculated from schedules 0.0000 28.7295 0.0000 1.0000 Not calculated 0.0000 0.0000    
VAV_TOP WITH REHEAT 5.4161 0.0000 0.0000 1.0000 Calculated from schedules 0.0000 2.9650 0.0000 1.0000 Not calculated 0.0000 0.0000    
CAV_BAS 6.0861 0.0000 149.6021 1.0000 Calculated from schedules 1.2002 6.0861 1.0000 1.0000 Not calculated 1.2002 0.1972    
AIRLOOP DATACENTER BASEMENT 22.1364 0.0000 42.1814 1.0000 Calculated from schedules 0.3384 22.1364 1.0000 1.0000 Not calculated 0.3384 0.0153    
AIRLOOP DATACENTER BOT 0.4922 0.0000 1.9486 1.0000 Calculated from schedules 0.0156 0.4922 1.0000 1.0000 Not calculated 0.0156 0.0318    
AIRLOOP DATACENTER MID 4.6918 0.0000 19.4861 1.0000 Calculated from schedules 0.1563 4.6918 1.0000 1.0000 Not calculated 0.1563 0.0333    
AIRLOOP DATACENTER TOP 0.4779 0.0000 1.9486 1.0000 Calculated from schedules 0.0156 0.4779 1.0000 1.0000 Not calculated 0.0156 0.0327    


Zone Ventilation Parameters

AirLoop Name People Outdoor Air Rate - Rp [m3/s-person] Zone Population - Pz Area Outdoor Air Rate - Ra [m3/s-m2] Zone Floor Area - Az [m2] Breathing Zone Outdoor Airflow - Vbz [m3/s] Cooling Zone Air Distribution Effectiveness - Ez-clg Cooling Zone Outdoor Airflow - Voz-clg [m3/s] Heating Zone Air Distribution Effectiveness - Ez-htg Heating Zone Outdoor Airflow - Voz-htg [m3/s]
BASEMENT CAV_BAS 0.000000 149.6021 0.000432 2779.43 1.2002 1.0000 1.2002 1.000 1.2002
CORE_BOTTOM VAV_BOT WITH REHEAT 0.000000 134.3532 0.000432 2496.12 0.0000 1.0000 0.0000 1.000 0.0000
CORE_MID VAV_MID WITH REHEAT 0.000000 1343.5320 0.000432 24961.20 0.0000 1.0000 0.0000 1.000 0.0000
CORE_TOP VAV_TOP WITH REHEAT 0.000000 134.3532 0.000432 2496.12 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_BOT_ZN_3 VAV_BOT WITH REHEAT 0.000000 16.8694 0.000432 313.41 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_BOT_ZN_2 VAV_BOT WITH REHEAT 0.000000 10.8713 0.000432 201.98 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_BOT_ZN_1 VAV_BOT WITH REHEAT 0.000000 16.8698 0.000432 313.42 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_BOT_ZN_4 VAV_BOT WITH REHEAT 0.000000 10.8713 0.000432 201.98 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_MID_ZN_3 VAV_MID WITH REHEAT 0.000000 168.6939 0.000432 3134.13 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_MID_ZN_2 VAV_MID WITH REHEAT 0.000000 108.7127 0.000432 2019.75 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_MID_ZN_1 VAV_MID WITH REHEAT 0.000000 168.6975 0.000432 3134.20 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_MID_ZN_4 VAV_MID WITH REHEAT 0.000000 108.7127 0.000432 2019.75 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_TOP_ZN_3 VAV_TOP WITH REHEAT 0.000000 16.8694 0.000432 313.41 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_TOP_ZN_2 VAV_TOP WITH REHEAT 0.000000 10.8713 0.000432 201.98 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_TOP_ZN_1 VAV_TOP WITH REHEAT 0.000000 16.8698 0.000432 313.42 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_TOP_ZN_4 VAV_TOP WITH REHEAT 0.000000 10.8713 0.000432 201.98 0.0000 1.0000 0.0000 1.000 0.0000
DATACENTER_BOT_ZN_6 AIRLOOP DATACENTER BOT 0.000000 1.9486 0.000432 36.20 0.0156 1.0000 0.0156 1.000 0.0156
DATACENTER_MID_ZN_6 AIRLOOP DATACENTER MID 0.000000 19.4861 0.000432 362.03 0.1563 1.0000 0.1563 1.000 0.1563
DATACENTER_TOP_ZN_6 AIRLOOP DATACENTER TOP 0.000000 1.9486 0.000432 36.20 0.0156 1.0000 0.0156 1.000 0.0156
DATACENTER_BASEMENT_ZN_6 AIRLOOP DATACENTER BASEMENT 0.000000 42.1814 0.000432 783.68 0.3384 1.0000 0.3384 1.000 0.3384


System Ventilation Parameters

People Outdoor Air Rate - Rp [m3/s-person] Sum of Zone Population - Pz-sum Area Outdoor Air Rate - Ra [m3/s-m2] Sum of Zone Floor Area - Az-sum [m2] Breathing Zone Outdoor Airflow - Vbz [m3/s] Cooling Zone Outdoor Airflow - Voz-clg [m3/s] Heating Zone Outdoor Airflow - Voz-htg [m3/s]
VAV_BOT WITH REHEAT   0.00 0.000432 3526.9033 0.0000 0.0000 0.0000
VAV_MID WITH REHEAT   0.00 0.000432 35269.0328 0.0000 0.0000 0.0000
VAV_TOP WITH REHEAT   0.00 0.000432 3526.9033 0.0000 0.0000 0.0000
CAV_BAS 0.000000 149.60 0.000432 2779.4266 1.2002 1.2002 1.2002
AIRLOOP DATACENTER BASEMENT 0.000000 42.18 0.000432 783.6794 0.3384 0.3384 0.3384
AIRLOOP DATACENTER BOT 0.000000 1.95 0.000432 36.2027 0.0156 0.0156 0.0156
AIRLOOP DATACENTER MID 0.000000 19.49 0.000432 362.0274 0.1563 0.1563 0.1563
AIRLOOP DATACENTER TOP 0.000000 1.95 0.000432 36.2027 0.0156 0.0156 0.0156


Zone Ventilation Calculations for Cooling Design

AirLoop Name Box Type Zone Primary Airflow - Vpz [m3/s] Zone Discharge Airflow - Vdz [m3/s] Minimum Zone Primary Airflow - Vpz-min [m3/s] Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? Zone Outdoor Airflow Cooling - Voz-clg [m3/s] Primary Outdoor Air Fraction - Zpz Primary Air Fraction - Ep Secondary Recirculation Fraction- Er Supply Air Fraction- Fa Mixed Air Fraction - Fb Outdoor Air Fraction - Fc Zone Ventilation Efficiency - Evz
BASEMENT CAV_BAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 6.0861 6.0861 6.0861 No 1.2002 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CORE_BOTTOM VAV_BOT WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 6.3471 6.3471 1.9549 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CORE_MID VAV_MID WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 59.9690 59.9690 19.1901 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CORE_TOP VAV_TOP WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 5.9111 5.9111 1.9625 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_BOT_ZN_3 VAV_BOT WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.0690 1.0690 0.2459 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_BOT_ZN_2 VAV_BOT WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.1063 1.1063 0.2213 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_BOT_ZN_1 VAV_BOT WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.2535 1.2535 0.2507 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_BOT_ZN_4 VAV_BOT WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.3953 1.3953 0.2791 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_MID_ZN_3 VAV_MID WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 10.1372 10.1372 2.4127 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_MID_ZN_2 VAV_MID WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 11.4552 11.4552 2.2910 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_MID_ZN_1 VAV_MID WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 11.9730 11.9730 2.4066 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_MID_ZN_4 VAV_MID WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 12.1459 12.1459 2.4292 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_TOP_ZN_3 VAV_TOP WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.1421 1.1421 0.2467 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_TOP_ZN_2 VAV_TOP WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.1647 1.1647 0.2329 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_TOP_ZN_1 VAV_TOP WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.3165 1.3165 0.2633 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_TOP_ZN_4 VAV_TOP WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.2979 1.2979 0.2596 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
DATACENTER_BOT_ZN_6 AIRLOOP DATACENTER BOT AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.4922 0.4922 0.4922 No 0.0156 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
DATACENTER_MID_ZN_6 AIRLOOP DATACENTER MID AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 4.6918 4.6918 4.6918 No 0.1563 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
DATACENTER_TOP_ZN_6 AIRLOOP DATACENTER TOP AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.4779 0.4779 0.4779 No 0.0156 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
DATACENTER_BASEMENT_ZN_6 AIRLOOP DATACENTER BASEMENT AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 22.1364 22.1364 22.1364 No 0.3384 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000


System Ventilation Calculations for Cooling Design

Sum of Zone Primary Airflow - Vpz-sum [m3/s] System Primary Airflow - Vps [m3/s] Sum of Zone Discharge Airflow - Vdz-sum [m3/s] Sum of Min Zone Primary Airflow - Vpz-min [m3/s] Zone Outdoor Airflow Cooling - Voz-clg [m3/s] Zone Ventilation Efficiency - Evz-min
VAV_BOT WITH REHEAT 11.1711 10.0760 11.1711 2.9518 0.0000 1.0000
VAV_MID WITH REHEAT 105.6802 94.0360 105.6802 28.7295 0.0000 1.0000
VAV_TOP WITH REHEAT 10.8322 10.1979 10.8322 2.9650 0.0000 1.0000
CAV_BAS 6.0861 6.0861 6.0861 6.0861 1.2002 1.0000
AIRLOOP DATACENTER BASEMENT 22.1364 22.1366 22.1364 22.1364 0.3384 1.0000
AIRLOOP DATACENTER BOT 0.4922 0.4922 0.4922 0.4922 0.0156 1.0000
AIRLOOP DATACENTER MID 4.6918 4.6918 4.6918 4.6918 0.1563 1.0000
AIRLOOP DATACENTER TOP 0.4779 0.4779 0.4779 0.4779 0.0156 1.0000


Zone Ventilation Calculations for Heating Design

AirLoop Name Box Type Zone Primary Airflow - Vpz [m3/s] Zone Discharge Airflow - Vdz [m3/s] Minimum Zone Primary Airflow - Vpz-min [m3/s] Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? Zone Outdoor Airflow Heating - Voz-htg [m3/s] Primary Outdoor Air Fraction - Zpz Primary Air Fraction - Ep Secondary Recirculation Fraction- Er Supply Air Fraction- Fa Mixed Air Fraction - Fb Outdoor Air Fraction - Fc Zone Ventilation Efficiency - Evz
BASEMENT CAV_BAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 6.0861 6.0861 6.0861 No 1.2002 1.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CORE_BOTTOM VAV_BOT WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 3.1735 3.1735 1.9549 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CORE_MID VAV_MID WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 29.9845 29.9845 19.1901 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CORE_TOP VAV_TOP WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 2.9555 2.9555 1.9625 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_BOT_ZN_3 VAV_BOT WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.5345 0.5345 0.2459 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_BOT_ZN_2 VAV_BOT WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.5532 0.5532 0.2213 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_BOT_ZN_1 VAV_BOT WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.6267 0.6267 0.2507 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_BOT_ZN_4 VAV_BOT WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.6976 0.6976 0.2791 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_MID_ZN_3 VAV_MID WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 5.0686 5.0686 2.4127 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_MID_ZN_2 VAV_MID WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 5.7276 5.7276 2.2910 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_MID_ZN_1 VAV_MID WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 5.9865 5.9865 2.4066 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_MID_ZN_4 VAV_MID WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 6.0729 6.0729 2.4292 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_TOP_ZN_3 VAV_TOP WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.5710 0.5710 0.2467 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_TOP_ZN_2 VAV_TOP WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.5823 0.5823 0.2329 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_TOP_ZN_1 VAV_TOP WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.6583 0.6583 0.2633 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_TOP_ZN_4 VAV_TOP WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.6489 0.6489 0.2596 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
DATACENTER_BOT_ZN_6 AIRLOOP DATACENTER BOT AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.4922 0.4922 0.4922 No 0.0156 1.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
DATACENTER_MID_ZN_6 AIRLOOP DATACENTER MID AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 4.6918 4.6918 4.6918 No 0.1563 1.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
DATACENTER_TOP_ZN_6 AIRLOOP DATACENTER TOP AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.4779 0.4779 0.4779 No 0.0156 1.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
DATACENTER_BASEMENT_ZN_6 AIRLOOP DATACENTER BASEMENT AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 22.1364 22.1364 22.1364 No 0.3384 1.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000


System Ventilation Calculations for Heating Design

Sum of Zone Primary Airflow - Vpz-sum [m3/s] System Primary Airflow - Vps [m3/s] Sum of Zone Discharge Airflow - Vdz-sum [m3/s] Sum of Min Zone Primary Airflow - Vpz-min [m3/s] Zone Outdoor Airflow Heating - Voz-htg [m3/s] Zone Ventilation Efficiency - Evz-min
VAV_BOT WITH REHEAT 5.5856 2.9518 2.9518 2.9518 0.0000 1.0000
VAV_MID WITH REHEAT 52.8401 28.7295 28.7295 28.7295 0.0000 1.0000
VAV_TOP WITH REHEAT 5.4161 2.9650 2.9650 2.9650 0.0000 1.0000
CAV_BAS 6.0861 6.0861 6.0861 6.0861 1.2002 1.0000
AIRLOOP DATACENTER BASEMENT 22.1364 22.1364 22.1364 22.1364 0.3384 1.0000
AIRLOOP DATACENTER BOT 0.4922 0.4922 0.4922 0.4922 0.0156 1.0000
AIRLOOP DATACENTER MID 4.6918 4.6918 4.6918 4.6918 0.1563 1.0000
AIRLOOP DATACENTER TOP 0.4779 0.4779 0.4779 0.4779 0.0156 1.0000



Table of Contents

Report: LEED Summary

For: Entire Facility

Timestamp: 2023-10-16 08:43:24

Sec1.1A-General Information

Data
Weather File RUNPERIOD 1 ** Atlanta-Hartsfield Jackson Intl AP GA USA TMY3 WMO#=722190
Total gross floor area [m2] 46320.38
Principal Heating Source Natural Gas


EAp2-1. Space Usage Type

Space Area [m2] Regularly Occupied Area [m2] Unconditioned Area [m2] Typical Hours/Week in Operation [hr/wk]
BASEMENT 2779.43 2779.43 0.00 113.98
CORE_BOTTOM 2496.12 2496.12 0.00 113.98
CORE_MID 2496.12 2496.12 0.00 113.98
CORE_TOP 2496.12 2496.12 0.00 113.98
PERIMETER_BOT_ZN_3 313.41 313.41 0.00 113.98
PERIMETER_BOT_ZN_2 201.98 201.98 0.00 113.98
PERIMETER_BOT_ZN_1 313.42 313.42 0.00 113.98
PERIMETER_BOT_ZN_4 201.98 201.98 0.00 113.98
PERIMETER_MID_ZN_3 313.41 313.41 0.00 113.98
PERIMETER_MID_ZN_2 201.98 201.98 0.00 96.54
PERIMETER_MID_ZN_1 313.42 313.42 0.00 113.98
PERIMETER_MID_ZN_4 201.98 201.98 0.00 113.98
PERIMETER_TOP_ZN_3 313.41 313.41 0.00 113.98
PERIMETER_TOP_ZN_2 201.98 201.98 0.00 113.98
PERIMETER_TOP_ZN_1 313.42 313.42 0.00 113.98
PERIMETER_TOP_ZN_4 201.98 201.98 0.00 113.98
DATACENTER_BOT_ZN_6 36.20 36.20 0.00 113.98
DATACENTER_MID_ZN_6 36.20 36.20 0.00 113.98
DATACENTER_TOP_ZN_6 36.20 36.20 0.00 113.98
DATACENTER_BASEMENT_ZN_6 783.68 783.68 0.00 113.98
GROUNDFLOOR_PLENUM 3563.11 3563.11 0.00 0.00
MIDFLOOR_PLENUM 3563.11 3563.11 0.00 0.00
TOPFLOOR_PLENUM 3563.11 3563.11 0.00 0.00
Totals 46320.38 46320.38 0.00  


EAp2-2. Advisory Messages

Data
Number of hours heating loads not met 32.33
Number of hours cooling loads not met 532.33
Number of hours not met 564.33


EAp2-3. Energy Type Summary

Utility Rate Virtual Rate [$/unit energy] Units of Energy Units of Demand
None        


EAp2-4/5. Performance Rating Method Compliance

Electricity Energy Use [GJ] Electricity Demand [W] Natural Gas Energy Use [GJ] Natural Gas Demand [W] Gasoline Use [GJ] Gasoline Demand [W] Diesel Use [GJ] Diesel Demand [W] Coal Use [GJ] Coal Demand [W] Fuel Oil No 1 Use [GJ] Fuel Oil No 1 Demand [W] Fuel Oil No 2 Use [GJ] Fuel Oil No 2 Demand [W] Propane Use [GJ] Propane Demand [W] Other Fuel 1 Use [GJ] Other Fuel 1 Demand [W] Other Fuel 2 Use [GJ] Other Fuel 2 Demand [W] District Cooling Use [GJ] District Cooling Demand [W] District Heating Use [GJ] District Heating Demand [W]
Heating -- General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heating -- Boiler 0.00 0.00 958.69 1771654.06 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heating -- Boiler Parasitic 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling -- General 4405.04 456876.80 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting -- LightsWired 3936.13 385834.94 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting -- General 695.97 57580.60 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- MiscPlug 5334.97 305206.10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- DataCenterPlugLoads 9341.42 473165.59 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment -- Transformer 80.18 5057.48 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment -- ElevatorLift 1848.78 113101.96 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment -- ElevatorLightsFan 5.83 376.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans -- General 2129.53 173140.65 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps -- General 597.12 61546.80 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection -- General 1479.78 92827.61 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification -- General 8.94 5868.03 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery -- General 52.13 5613.48 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems -- General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems -- WaterUse 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems -- Water Heater 0.00 0.00 734.54 82149.84 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration -- Not Subdivided 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators -- General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


EAp2-6. Energy Use Summary

Process Subtotal [GJ] Total Energy Use [GJ]
Electricity 14676.40 29915.83
Natural Gas 0.00 1693.23
Additional 0.00 0.00
Total 14676.40 31609.06


EAp2-7. Energy Cost Summary

Process Subtotal [$] Total Energy Cost [$]
Electricity 0.00  
Natural Gas 0.00  
Additional 0.00  
Total 0.00  
Process energy cost based on ratio of process to total energy.

L-1. Renewable Energy Source Summary

Rated Capacity [kW] Annual Energy Generated [GJ]
Photovoltaic 0.00 0.00
Wind 0.00 0.00


EAp2-17a. Energy Use Intensity - Electricity

Electricty [MJ/m2]
Interior Lighting (All) 84.98
Space Heating 0.00
Space Cooling 95.10
Fans (All) 45.97
Service Water Heating 0.00
Receptacle Equipment 316.85
Miscellaneous (All) 645.85
Subtotal 645.85


EAp2-17b. Energy Use Intensity - Natural Gas

Natural Gas [MJ/m2]
Space Heating 20.70
Service Water Heating 15.86
Miscellaneous (All) 36.55
Subtotal 36.55


EAp2-17c. Energy Use Intensity - Additional

Additional [MJ/m2]
Subtotal 0.00
Miscellaneous 0.00


EAp2-18. End Use Percentage

Percent [%]
Interior Lighting (All) 12.45
Space Heating 3.03
Space Cooling 13.94
Fans (All) 6.74
Service Water Heating 2.32
Receptacle Equipment 46.43
Miscellaneous 15.09


Schedules-Equivalent Full Load Hours (Schedule Type=Fraction)

Equivalent Full Load Hours of Operation Per Year [hr] Hours > 1% [hr]
EXTERIOR_LIGHTING_SCHEDULE_A 6570. 6570.
EXTERIOR_LIGHTING_SCHEDULE_B 8103. 8760.
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 4472. 4472.
EXTERIOR_LIGHTING_SCHEDULE_B_2016 7665. 8760.
EXTERIOR_LIGHTING_SCHEDULE_C_2016 6752. 8760.
ALWAYS_ON 8760. 8760.
EXTERIOR_LGT_ALWAYS_ON 8760. 8760.
EXTERIOR_LGT_189_1 6828. 8760.
ALWAYS_OFF 0. 0.
LTG_SCH_OFFICE 2625. 8760.
LTG_SCH_DATACENTER 2921. 8760.
EXTERIOR_LIGHT_SCH 4380. 4380.
BLDG_EQUIP_SCH 4049. 8760.
DATACENTER_EQUIP_SCH 5478. 8760.
BLDG_OCC_SCH 2528. 5992.
BLDG_OCC_SCH_W_SB 1878. 5056.
BLDG_OCC_SCH_WO_SB 2557. 5992.
BLDG_ELEVATORS 2270. 8760.
ELEV_LIGHT_FAN_SCH_24_7 8760. 8760.
ELEV_LIGHT_FAN_SCH_ADD_DF 2154. 8760.
BLDG_SWH_SCH 1474. 6570.
WORK_EFF_SCH 0. 0.
INFIL_SCH 3976. 3976.
INFIL_SCH_PNNL 5172. 8760.
INFIL_HALF_ON_SCH 6368. 8760.
FAN_SCH 8760. 8760.
REHEATCOILAVAILSCHED 8760. 8760.
COOLINGCOILAVAILSCHED 8760. 8760.
MINOA_MOTORIZEDDAMPER_SCHED 4472. 4472.
MINOA_SCHED 8760. 8760.
CORE_BOTTOM SUB CAT LATENT FRACT SCHED 438. 8760.
CORE_BOTTOM SUB CAT SENSIBLE FRACT SCHED 1752. 8760.
CORE_MID SUB CAT LATENT FRACT SCHED 438. 8760.
CORE_MID SUB CAT SENSIBLE FRACT SCHED 1752. 8760.
CORE_TOP SUB CAT LATENT FRACT SCHED 438. 8760.
CORE_TOP SUB CAT SENSIBLE FRACT SCHED 1752. 8760.
SUPPLYFANSCH 8760. 8760.
PERIMETER_MID_ZN_2_MDP_SCH 1565. 7824.


Schedules-SetPoints (Schedule Type=Temperature)

First Object Used Month Assumed 11am First Wednesday [C] Days with Same 11am Value 11pm First Wednesday [C] Days with Same 11pm Value
HTGSETP_DC_SCH DATACENTER COOLING SETPOINTS DUAL SP CONTROL January 18.00 365 18.00 365
CLGSETP_DC_SCH DATACENTER COOLING SETPOINTS DUAL SP CONTROL July 27.00 365 27.00 365
HTGSETP_SCH_YES_OPTIMUM CORE_BOTTOM DUAL SP CONTROL January 21.00 365 15.60 365
CLGSETP_SCH_YES_OPTIMUM CORE_BOTTOM DUAL SP CONTROL July 24.00 365 26.70 365



Table of Contents

Report: Annual Thermal Resilience Summary

For: Entire Facility

Timestamp: 2023-10-16 08:43:24

Heat Index Hours

Safe (≤ 26.7°C) [hr] Caution (> 26.7, ≤ 32.2°C) [hr] Extreme Caution (> 32.2, ≤ 39.4°C) [hr] Danger (> 39.4, ≤ 51.7°C) [hr] Extreme Danger (> 51.7°C) [hr]
BASEMENT 7943.83 816.17 0.00 0.00 0.00
CORE_BOTTOM 8710.33 49.67 0.00 0.00 0.00
CORE_MID 8760.00 0.00 0.00 0.00 0.00
CORE_TOP 8760.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_3 8745.67 14.33 0.00 0.00 0.00
PERIMETER_BOT_ZN_2 8704.17 55.83 0.00 0.00 0.00
PERIMETER_BOT_ZN_1 8700.83 59.17 0.00 0.00 0.00
PERIMETER_BOT_ZN_4 8107.33 652.67 0.00 0.00 0.00
PERIMETER_MID_ZN_3 8749.50 10.50 0.00 0.00 0.00
PERIMETER_MID_ZN_2 8673.83 86.17 0.00 0.00 0.00
PERIMETER_MID_ZN_1 8688.00 72.00 0.00 0.00 0.00
PERIMETER_MID_ZN_4 8411.83 348.17 0.00 0.00 0.00
PERIMETER_TOP_ZN_3 8732.83 27.17 0.00 0.00 0.00
PERIMETER_TOP_ZN_2 8652.33 107.67 0.00 0.00 0.00
PERIMETER_TOP_ZN_1 8678.17 81.83 0.00 0.00 0.00
PERIMETER_TOP_ZN_4 8400.83 359.17 0.00 0.00 0.00
DATACENTER_BOT_ZN_6 6750.50 2009.50 0.00 0.00 0.00
DATACENTER_MID_ZN_6 6715.17 2044.83 0.00 0.00 0.00
DATACENTER_TOP_ZN_6 6695.00 2065.00 0.00 0.00 0.00
DATACENTER_BASEMENT_ZN_6 6620.33 2139.67 0.00 0.00 0.00
GROUNDFLOOR_PLENUM 8760.00 0.00 0.00 0.00 0.00
MIDFLOOR_PLENUM 8760.00 0.00 0.00 0.00 0.00
TOPFLOOR_PLENUM 8653.67 106.33 0.00 0.00 0.00
Min 6620.33 0.00 0.00 0.00 0.00
Max 8760.00 2139.67 0.00 0.00 0.00
Average 8277.14 482.86 0.00 0.00 0.00
Sum 190374.17 11105.83 0.00 0.00 0.00


Heat Index OccupantHours

Safe (≤ 26.7°C) [hr] Caution (> 26.7, ≤ 32.2°C) [hr] Extreme Caution (> 32.2, ≤ 39.4°C) [hr] Danger (> 39.4, ≤ 51.7°C) [hr] Extreme Danger (> 51.7°C) [hr]
BASEMENT 366586.00 2030.00 0.00 0.00 0.00
CORE_BOTTOM 330729.00 84.00 0.00 0.00 0.00
CORE_MID 330813.00 0.00 0.00 0.00 0.00
CORE_TOP 330813.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_3 38925.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_2 24909.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_1 38925.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_4 24909.00 0.00 0.00 0.00 0.00
PERIMETER_MID_ZN_3 38925.00 0.00 0.00 0.00 0.00
PERIMETER_MID_ZN_2 18354.00 0.00 0.00 0.00 0.00
PERIMETER_MID_ZN_1 38925.00 0.00 0.00 0.00 0.00
PERIMETER_MID_ZN_4 24909.00 0.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_3 38925.00 0.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_2 24909.00 0.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_1 38925.00 0.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_4 24909.00 0.00 0.00 0.00 0.00
DATACENTER_BOT_ZN_6 1236.33 1031.67 0.00 0.00 0.00
DATACENTER_MID_ZN_6 1220.67 1047.33 0.00 0.00 0.00
DATACENTER_TOP_ZN_6 1212.33 1055.67 0.00 0.00 0.00
DATACENTER_BASEMENT_ZN_6 61178.00 42217.00 0.00 0.00 0.00
GROUNDFLOOR_PLENUM 0.00 0.00 0.00 0.00 0.00
MIDFLOOR_PLENUM 0.00 0.00 0.00 0.00 0.00
TOPFLOOR_PLENUM 0.00 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00 0.00
Max 366586.00 42217.00 0.00 0.00 0.00
Average 78271.19 2063.72 0.00 0.00 0.00
Sum 1800237.33 47465.67 0.00 0.00 0.00


Humidex Hours

Little to no Discomfort (≤ 29) [hr] Some Discomfort (> 29, ≤ 40) [hr] Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] Dangerous (> 45, ≤ 50) [hr] Heat Stroke Quite Possible (> 50) [hr]
BASEMENT 6265.50 2494.50 0.00 0.00 0.00
CORE_BOTTOM 8436.67 323.33 0.00 0.00 0.00
CORE_MID 8732.33 27.67 0.00 0.00 0.00
CORE_TOP 8750.00 10.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_3 8447.17 312.83 0.00 0.00 0.00
PERIMETER_BOT_ZN_2 8475.17 284.83 0.00 0.00 0.00
PERIMETER_BOT_ZN_1 8374.00 386.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_4 7729.00 1031.00 0.00 0.00 0.00
PERIMETER_MID_ZN_3 7849.17 910.83 0.00 0.00 0.00
PERIMETER_MID_ZN_2 7836.17 923.83 0.00 0.00 0.00
PERIMETER_MID_ZN_1 7712.17 1047.83 0.00 0.00 0.00
PERIMETER_MID_ZN_4 7657.50 1102.50 0.00 0.00 0.00
PERIMETER_TOP_ZN_3 7801.50 958.50 0.00 0.00 0.00
PERIMETER_TOP_ZN_2 7793.83 966.17 0.00 0.00 0.00
PERIMETER_TOP_ZN_1 7702.00 1058.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_4 7656.50 1103.50 0.00 0.00 0.00
DATACENTER_BOT_ZN_6 7389.17 1370.83 0.00 0.00 0.00
DATACENTER_MID_ZN_6 7330.17 1429.83 0.00 0.00 0.00
DATACENTER_TOP_ZN_6 7313.50 1446.50 0.00 0.00 0.00
DATACENTER_BASEMENT_ZN_6 7469.50 1290.50 0.00 0.00 0.00
GROUNDFLOOR_PLENUM 8668.33 91.67 0.00 0.00 0.00
MIDFLOOR_PLENUM 8433.17 326.83 0.00 0.00 0.00
TOPFLOOR_PLENUM 8262.00 498.00 0.00 0.00 0.00
Min 6265.50 10.00 0.00 0.00 0.00
Max 8750.00 2494.50 0.00 0.00 0.00
Average 7916.72 843.28 0.00 0.00 0.00
Sum 182084.50 19395.50 0.00 0.00 0.00


Humidex OccupantHours

Little to no Discomfort (≤ 29) [hr] Some Discomfort (> 29, ≤ 40) [hr] Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] Dangerous (> 45, ≤ 50) [hr] Heat Stroke Quite Possible (> 50) [hr]
BASEMENT 345290.50 23325.50 0.00 0.00 0.00
CORE_BOTTOM 330296.33 516.67 0.00 0.00 0.00
CORE_MID 330703.00 110.00 0.00 0.00 0.00
CORE_TOP 330790.00 23.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_3 38925.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_2 24909.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_1 38925.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_4 24909.00 0.00 0.00 0.00 0.00
PERIMETER_MID_ZN_3 38922.17 2.83 0.00 0.00 0.00
PERIMETER_MID_ZN_2 18353.17 0.83 0.00 0.00 0.00
PERIMETER_MID_ZN_1 38922.67 2.33 0.00 0.00 0.00
PERIMETER_MID_ZN_4 24908.50 0.50 0.00 0.00 0.00
PERIMETER_TOP_ZN_3 38920.00 5.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_2 24908.00 1.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_1 38921.67 3.33 0.00 0.00 0.00
PERIMETER_TOP_ZN_4 24908.50 0.50 0.00 0.00 0.00
DATACENTER_BOT_ZN_6 1469.33 798.67 0.00 0.00 0.00
DATACENTER_MID_ZN_6 1444.17 823.83 0.00 0.00 0.00
DATACENTER_TOP_ZN_6 1430.50 837.50 0.00 0.00 0.00
DATACENTER_BASEMENT_ZN_6 75391.17 28003.83 0.00 0.00 0.00
GROUNDFLOOR_PLENUM 0.00 0.00 0.00 0.00 0.00
MIDFLOOR_PLENUM 0.00 0.00 0.00 0.00 0.00
TOPFLOOR_PLENUM 0.00 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00 0.00
Max 345290.50 28003.83 0.00 0.00 0.00
Average 77967.29 2367.62 0.00 0.00 0.00
Sum 1793247.67 54455.33 0.00 0.00 0.00


Heating SET Hours

SET ≤ 12.2°C Hours (°C) SET ≤ 12.2°C OccupantHours (°C) Longest SET ≤ 12.2°C Duration [hr] Start Time of the Longest SET ≤ 12.2°C Duration
None        


Cooling SET Hours

SET > 30°C Hours (°C) SET > 30°C OccupantHours (°C) Longest SET > 30°C Duration [hr] Start Time of the Longest SET > 30°C Duration
None        



Table of Contents

Report: Annual CO2 Resilience Summary

For: Entire Facility

Timestamp: 2023-10-16 08:43:24

CO2 Level Hours

Safe (<= 1000 ppm) [hr] Caution (> 1000, <= 5000 ppm) [hr] Hazard (> 5000 ppm) [hr]
None      


CO2 Level OccupantHours

Safe (<= 1000 ppm) [hr] Caution (> 1000, <= 5000 ppm) [hr] Hazard (> 5000 ppm) [hr]
None      



Table of Contents

Report: Annual Visual Resilience Summary

For: Entire Facility

Timestamp: 2023-10-16 08:43:24

Illuminance Level Hours

A Bit Dark (<= 100 lux) [hr] Dim (> 100, <= 300 lux) [hr] Adequate (> 300, <= 500 lux) [hr] Bright (>500 lux) [hr]
BASEMENT 0.00 0.00 0.00 0.00
CORE_BOTTOM 0.00 0.00 0.00 0.00
CORE_MID 0.00 0.00 0.00 0.00
CORE_TOP 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_3 0.00 0.00 8760.00 0.00
PERIMETER_BOT_ZN_2 0.00 0.00 8760.00 0.00
PERIMETER_BOT_ZN_1 0.00 0.00 8760.00 0.00
PERIMETER_BOT_ZN_4 0.00 0.00 8760.00 0.00
PERIMETER_MID_ZN_3 0.00 0.00 8760.00 0.00
PERIMETER_MID_ZN_2 0.00 0.00 8760.00 0.00
PERIMETER_MID_ZN_1 0.00 0.00 8760.00 0.00
PERIMETER_MID_ZN_4 0.00 0.00 8760.00 0.00
PERIMETER_TOP_ZN_3 0.00 0.00 8760.00 0.00
PERIMETER_TOP_ZN_2 0.00 0.00 8760.00 0.00
PERIMETER_TOP_ZN_1 0.00 0.00 8760.00 0.00
PERIMETER_TOP_ZN_4 0.00 0.00 8760.00 0.00
DATACENTER_BOT_ZN_6 0.00 0.00 0.00 0.00
DATACENTER_MID_ZN_6 0.00 0.00 0.00 0.00
DATACENTER_TOP_ZN_6 0.00 0.00 0.00 0.00
DATACENTER_BASEMENT_ZN_6 0.00 0.00 0.00 0.00
GROUNDFLOOR_PLENUM 0.00 0.00 0.00 0.00
MIDFLOOR_PLENUM 0.00 0.00 0.00 0.00
TOPFLOOR_PLENUM 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00
Max 0.00 0.00 8760.00 0.00
Average 0.00 0.00 4570.43 0.00
Sum 0.00 0.00 105120.00 0.00


Illuminance Level OccupantHours

A Bit Dark (<= 100 lux) [hr] Dim (> 100, <= 300 lux) [hr] Adequate (> 300, <= 500 lux) [hr] Bright (>500 lux) [hr]
BASEMENT 0.00 0.00 0.00 0.00
CORE_BOTTOM 0.00 0.00 0.00 0.00
CORE_MID 0.00 0.00 0.00 0.00
CORE_TOP 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_3 0.00 0.00 38925.00 0.00
PERIMETER_BOT_ZN_2 0.00 0.00 24909.00 0.00
PERIMETER_BOT_ZN_1 0.00 0.00 38925.00 0.00
PERIMETER_BOT_ZN_4 0.00 0.00 24909.00 0.00
PERIMETER_MID_ZN_3 0.00 0.00 38925.00 0.00
PERIMETER_MID_ZN_2 0.00 0.00 18354.00 0.00
PERIMETER_MID_ZN_1 0.00 0.00 38925.00 0.00
PERIMETER_MID_ZN_4 0.00 0.00 24909.00 0.00
PERIMETER_TOP_ZN_3 0.00 0.00 38925.00 0.00
PERIMETER_TOP_ZN_2 0.00 0.00 24909.00 0.00
PERIMETER_TOP_ZN_1 0.00 0.00 38925.00 0.00
PERIMETER_TOP_ZN_4 0.00 0.00 24909.00 0.00
DATACENTER_BOT_ZN_6 0.00 0.00 0.00 0.00
DATACENTER_MID_ZN_6 0.00 0.00 0.00 0.00
DATACENTER_TOP_ZN_6 0.00 0.00 0.00 0.00
DATACENTER_BASEMENT_ZN_6 0.00 0.00 0.00 0.00
GROUNDFLOOR_PLENUM 0.00 0.00 0.00 0.00
MIDFLOOR_PLENUM 0.00 0.00 0.00 0.00
TOPFLOOR_PLENUM 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00
Max 0.00 0.00 38925.00 0.00
Average 0.00 0.00 16367.35 0.00
Sum 0.00 0.00 376449.00 0.00



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR

For: Environment

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 3.965
February 7.937
March 13.764
April 17.213
May 20.837
June 24.797
July 26.063
August 26.547
September 22.525
October 16.026
November 11.940
December 7.696
   
Annual Sum or Average 16.653
Minimum of Months 3.965
Maximum of Months 26.547



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901

For: Environment

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 3.965
February 7.937
March 13.764
April 17.213
May 20.837
June 24.797
July 26.063
August 26.547
September 22.525
October 16.026
November 11.940
December 7.696
   
Annual Sum or Average 16.653
Minimum of Months 3.965
Maximum of Months 26.547



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2013

For: Environment

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 3.965
February 7.937
March 13.764
April 17.213
May 20.837
June 24.797
July 26.063
August 26.547
September 22.525
October 16.026
November 11.940
December 7.696
   
Annual Sum or Average 16.653
Minimum of Months 3.965
Maximum of Months 26.547



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND

For: Environment

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 3.965
February 7.937
March 13.764
April 17.213
May 20.837
June 24.797
July 26.063
August 26.547
September 22.525
October 16.026
November 11.940
December 7.696
   
Annual Sum or Average 16.653
Minimum of Months 3.965
Maximum of Months 26.547



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICELARGE

For: Environment

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 3.965
February 7.937
March 13.764
April 17.213
May 20.837
June 24.797
July 26.063
August 26.547
September 22.525
October 16.026
November 11.940
December 7.696
   
Annual Sum or Average 16.653
Minimum of Months 3.965
Maximum of Months 26.547



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL

For: Environment

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 3.965
February 7.937
March 13.764
April 17.213
May 20.837
June 24.797
July 26.063
August 26.547
September 22.525
October 16.026
November 11.940
December 7.696
   
Annual Sum or Average 16.653
Minimum of Months 3.965
Maximum of Months 26.547



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL

For: Environment

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 3.965
February 7.937
March 13.764
April 17.213
May 20.837
June 24.797
July 26.063
August 26.547
September 22.525
October 16.026
November 11.940
December 7.696
   
Annual Sum or Average 16.653
Minimum of Months 3.965
Maximum of Months 26.547



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 3A

For: Environment

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 3.965
February 7.937
March 13.764
April 17.213
May 20.837
June 24.797
July 26.063
August 26.547
September 22.525
October 16.026
November 11.940
December 7.696
   
Annual Sum or Average 16.653
Minimum of Months 3.965
Maximum of Months 26.547



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_GA_ATLANTA

For: Environment

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 3.965
February 7.937
March 13.764
April 17.213
May 20.837
June 24.797
July 26.063
August 26.547
September 22.525
October 16.026
November 11.940
December 7.696
   
Annual Sum or Average 16.653
Minimum of Months 3.965
Maximum of Months 26.547



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: BASEMENT

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.462637E+11 117755.26 02-JAN-05:11 3.30 2.57 0.565035E+10 7499.27 30-JAN-10:50 13.67 9.38
February 0.436103E+11 119279.88 21-FEB-05:11 6.33 4.24 0.513087E+10 7499.15 28-FEB-14:30 25.00 13.71
March 0.563288E+11 116375.27 06-MAR-05:11 4.03 0.98 0.613031E+10 7499.46 08-MAR-10:20 16.10 12.08
April 0.518571E+11 113953.56 10-APR-04:12 8.90 6.08 0.544631E+10 7499.27 03-APR-09:20 8.90 6.08
May 0.561563E+11 112130.78 15-MAY-04:12 12.60 11.09 0.589928E+10 7499.38 11-MAY-09:00 12.60 11.09
June 0.609751E+11 111458.60 08-JUN-04:12 11.70 8.69 0.588183E+10 7499.07 09-JUN-09:00 24.40 15.46
July 0.615275E+11 97170.68 03-JUL-04:23 17.80 16.55 0.547389E+10 7498.78 19-JUL-09:20 22.57 21.92
August 0.700230E+11 93509.31 26-AUG-04:12 21.70 17.11 0.613872E+10 7499.01 25-AUG-09:39 21.70 17.11
September 0.642037E+11 113311.09 14-SEP-04:12 12.60 11.28 0.545392E+10 7499.18 22-SEP-13:09 26.20 16.90
October 0.649951E+11 120516.13 30-OCT-04:11 8.90 8.90 0.567142E+10 7498.98 31-OCT-09:00 10.60 9.10
November 0.629710E+11 117080.44 06-NOV-05:12 9.80 9.21 0.561573E+10 7499.35 16-NOV-10:20 10.77 10.06
December 0.575171E+11 119360.14 11-DEC-05:11 6.33 5.61 0.546904E+10 7499.27 11-DEC-10:00 15.00 12.11
                     
Annual Sum or Average 0.696429E+12         0.679617E+11        
Minimum of Months 0.436103E+11 93509.31   3.30 0.98 0.513087E+10 7498.78   8.90 6.08
Maximum of Months 0.700230E+11 120516.13   21.70 17.11 0.613872E+10 7499.46   26.20 21.92



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: CORE_BOTTOM

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.394615E+11 92999.03 02-JAN-05:11 3.30 2.57 0.498996E+10 6746.09 27-JAN-14:00 3.90 -1.8
February 0.408242E+11 92429.04 21-FEB-05:11 6.33 4.24 0.456138E+10 6748.62 02-FEB-14:50 6.33 4.24
March 0.578367E+11 93461.30 06-MAR-05:11 4.03 0.98 0.548841E+10 6741.27 22-MAR-13:39 4.40 3.91
April 0.606425E+11 95150.35 14-APR-04:13 13.53 10.31 0.487759E+10 6734.77 17-APR-13:50 28.72 16.68
May 0.580105E+11 99086.11 30-MAY-04:13 19.43 17.60 0.527883E+10 6735.15 11-MAY-09:00 19.43 17.60
June 0.660751E+11 99664.12 20-JUN-04:13 19.40 19.07 0.526535E+10 6734.77 09-JUN-09:00 19.40 19.07
July 0.722353E+11 99025.80 01-JUL-04:13 21.70 20.50 0.488870E+10 6734.42 28-JUL-09:09 19.40 19.40
August 0.827986E+11 81011.87 31-AUG-04:22 21.95 21.17 0.548899E+10 6734.41 24-AUG-09:09 21.95 21.17
September 0.578771E+11 99855.04 11-SEP-04:13 20.20 19.05 0.487818E+10 6734.63 19-SEP-09:09 19.68 14.68
October 0.562352E+11 97918.84 10-OCT-04:13 16.10 15.06 0.507169E+10 6734.63 30-OCT-09:00 11.10 11.10
November 0.532143E+11 98819.34 13-NOV-05:11 4.23 1.45 0.502342E+10 6741.83 21-NOV-10:09 2.57 -0.2
December 0.491945E+11 94600.23 26-DEC-05:11 3.70 2.75 0.488745E+10 6734.83 11-DEC-10:00 3.70 2.75
                     
Annual Sum or Average 0.694405E+12         0.607000E+11        
Minimum of Months 0.394615E+11 81011.87   3.30 0.98 0.456138E+10 6734.41   2.57 -1.8
Maximum of Months 0.827986E+11 99855.04   21.95 21.17 0.548899E+10 6748.62   28.72 21.17



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: CORE_MID

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.298615E+11 71873.87 26-JAN-10:20 -3.1 -6.0 0.432600E+10 6754.15 26-JAN-10:39 -3.0 -5.9
February 0.303885E+11 76309.38 28-FEB-06:02 10.78 5.86 0.412216E+10 6734.70 28-FEB-10:20 18.00 10.30
March 0.418227E+11 83953.56 31-MAR-04:12 17.03 14.86 0.537301E+10 6734.99 08-MAR-10:20 17.03 14.86
April 0.427796E+11 84631.49 19-APR-04:12 16.10 14.43 0.482560E+10 6734.75 12-APR-13:50 16.10 14.43
May 0.498356E+11 85174.37 31-MAY-04:12 20.00 19.09 0.524942E+10 6735.11 11-MAY-09:00 20.00 19.09
June 0.537568E+11 86897.76 21-JUN-04:11 19.80 18.77 0.524697E+10 6734.73 09-JUN-09:00 19.80 18.77
July 0.538638E+11 86779.77 28-JUL-04:11 19.40 19.40 0.487417E+10 6734.43 18-JUL-13:09 19.40 19.40
August 0.579936E+11 85261.99 25-AUG-04:12 19.80 18.06 0.547843E+10 6734.43 04-AUG-13:09 19.80 18.06
September 0.485677E+11 86625.46 01-SEP-04:11 20.93 18.53 0.485037E+10 6734.60 19-SEP-09:09 19.68 14.68
October 0.417563E+11 84030.19 19-OCT-04:12 21.50 21.50 0.498887E+10 6734.57 04-OCT-13:00 21.50 21.50
November 0.356110E+11 78394.66 10-NOV-06:02 11.60 9.82 0.486885E+10 6734.88 16-NOV-10:09 10.68 10.03
December 0.319447E+11 67912.21 14-DEC-06:03 6.60 5.31 0.445128E+10 6734.45 14-DEC-14:00 15.00 10.54
                     
Annual Sum or Average 0.518182E+12         0.586551E+11        
Minimum of Months 0.298615E+11 67912.21   -3.1 -6.0 0.412216E+10 6734.43   -3.0 -5.9
Maximum of Months 0.579936E+11 86897.76   21.50 21.50 0.547843E+10 6754.15   21.50 21.50



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: CORE_TOP

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.237192E+11 25778.01 20-JAN-17:00 16.70 11.48 0.396445E+10 6443.57 20-JAN-14:00 16.70 11.48
February 0.253501E+11 35768.98 28-FEB-17:00 23.90 12.94 0.382085E+10 6734.65 22-FEB-14:00 23.90 12.94
March 0.373756E+11 81761.47 31-MAR-05:02 16.78 15.18 0.506164E+10 6734.58 13-MAR-13:00 16.78 15.18
April 0.403020E+11 81878.24 19-APR-05:02 16.02 14.35 0.469422E+10 6734.62 12-APR-09:30 16.02 14.35
May 0.504345E+11 84727.51 19-MAY-04:12 16.70 15.65 0.522186E+10 6735.97 16-MAY-13:39 16.70 15.65
June 0.573581E+11 86137.86 16-JUN-04:11 20.60 19.79 0.524238E+10 6734.68 09-JUN-09:00 20.60 19.79
July 0.583366E+11 85688.56 12-JUL-04:12 20.60 19.95 0.487416E+10 6734.40 27-JUL-09:09 21.10 20.75
August 0.627283E+11 84538.62 03-AUG-03:02 23.90 22.03 0.548000E+10 6734.41 24-AUG-09:09 23.40 22.97
September 0.478812E+11 84678.66 06-SEP-04:12 21.50 20.31 0.481764E+10 6734.51 13-SEP-13:09 23.92 15.70
October 0.375456E+11 83441.85 19-OCT-04:12 21.50 21.50 0.474016E+10 6734.50 04-OCT-13:00 21.50 21.50
November 0.298134E+11 36812.64 04-NOV-05:03 16.60 15.28 0.440215E+10 6734.33 02-NOV-13:09 16.60 15.28
December 0.260921E+11 32397.60 13-DEC-17:00 16.70 16.70 0.400381E+10 6734.35 13-DEC-14:09 16.70 16.70
                     
Annual Sum or Average 0.496937E+12         0.563233E+11        
Minimum of Months 0.237192E+11 25778.01   16.02 11.48 0.382085E+10 6443.57   16.02 11.48
Maximum of Months 0.627283E+11 86137.86   23.90 22.03 0.548000E+10 6735.97   23.92 22.97



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.256499E+10 3668.86 31-JAN-15:00 21.10 12.97 0.511853E+09 845.56 20-JAN-14:00 21.10 12.97
February 0.335348E+10 6320.36 28-FEB-15:00 25.00 13.71 0.496985E+09 845.63 22-FEB-14:09 25.00 13.71
March 0.576492E+10 7908.17 30-MAR-14:00 27.80 17.87 0.660267E+09 845.62 13-MAR-13:00 27.80 17.87
April 0.708679E+10 8497.66 18-APR-14:00 27.20 15.86 0.601306E+09 845.64 17-APR-13:50 27.20 15.86
May 0.814618E+10 13285.93 30-MAY-04:12 19.43 17.60 0.660204E+09 845.62 09-MAY-13:09 19.43 17.60
June 0.110856E+11 13741.55 20-JUN-04:11 19.40 19.07 0.661657E+09 845.63 09-JUN-09:00 19.40 19.07
July 0.121843E+11 14292.00 17-JUL-04:12 22.43 19.64 0.615235E+09 845.59 05-JUL-13:09 22.43 19.64
August 0.135553E+11 13219.63 21-AUG-05:02 21.78 21.78 0.690239E+09 845.59 25-AUG-13:09 30.18 18.86
September 0.780493E+10 13968.24 01-SEP-04:11 20.93 18.53 0.610213E+09 845.61 13-SEP-13:09 23.92 15.70
October 0.583551E+10 13350.02 19-OCT-04:12 21.50 21.50 0.614631E+09 845.61 04-OCT-13:00 21.50 21.50
November 0.466598E+10 5928.28 02-NOV-13:50 23.30 17.15 0.592963E+09 845.62 06-NOV-10:09 14.87 12.62
December 0.395035E+10 5562.81 13-DEC-12:00 20.00 17.41 0.545539E+09 845.60 12-DEC-10:30 20.00 17.41
                     
Annual Sum or Average 0.859983E+11         0.726109E+10        
Minimum of Months 0.256499E+10 3668.86   19.40 12.97 0.496985E+09 845.56   14.87 12.62
Maximum of Months 0.135553E+11 14292.00   27.80 21.78 0.690239E+09 845.64   30.18 21.50



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.230147E+10 3174.77 24-JAN-10:30 6.10 2.41 0.331912E+09 537.08 24-JAN-10:30 6.10 2.41
February 0.302437E+10 7192.47 27-FEB-09:40 12.23 5.46 0.321281E+09 544.96 28-FEB-10:00 20.60 11.95
March 0.511502E+10 8589.53 26-MAR-10:23 13.30 7.32 0.422320E+09 545.00 08-MAR-10:09 13.30 7.32
April 0.640824E+10 16930.54 16-APR-10:43 25.45 15.37 0.387196E+09 544.97 17-APR-13:50 28.72 16.68
May 0.748111E+10 17635.52 29-MAY-09:43 24.45 19.91 0.424843E+09 545.01 11-MAY-09:00 24.45 19.91
June 0.927972E+10 20029.05 04-JUN-09:02 24.78 18.48 0.425881E+09 544.97 09-JUN-09:00 24.40 15.46
July 0.100622E+11 19452.84 23-JUL-09:22 26.95 22.77 0.395464E+09 544.93 03-JUL-13:09 26.95 22.77
August 0.106328E+11 18414.67 13-AUG-08:32 25.53 22.81 0.443438E+09 544.93 25-AUG-13:09 30.18 18.86
September 0.702049E+10 18504.47 24-SEP-09:02 23.77 18.55 0.391030E+09 544.95 15-SEP-09:00 23.77 18.55
October 0.530049E+10 14006.48 09-OCT-10:13 22.93 17.62 0.393093E+09 544.95 05-OCT-09:00 22.93 17.62
November 0.394580E+10 6772.69 06-NOV-09:25 13.30 11.71 0.376822E+09 544.96 06-NOV-10:09 14.87 12.62
December 0.320252E+10 3613.65 08-DEC-10:10 8.58 4.06 0.346697E+09 544.96 11-DEC-10:00 15.00 12.11
                     
Annual Sum or Average 0.737743E+11         0.465998E+10        
Minimum of Months 0.230147E+10 3174.77   6.10 2.41 0.321281E+09 537.08   6.10 2.41
Maximum of Months 0.106328E+11 20029.05   26.95 22.81 0.443438E+09 545.01   30.18 22.77



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.448536E+10 17701.14 29-JAN-13:33 14.63 6.24 0.561521E+09 848.41 27-JAN-14:00 14.63 6.24
February 0.546912E+10 22138.58 26-FEB-13:42 24.32 12.55 0.523728E+09 858.78 21-FEB-14:39 24.32 12.55
March 0.849637E+10 20528.88 26-MAR-13:32 18.53 8.92 0.665654E+09 845.70 08-MAR-10:09 18.53 8.92
April 0.895485E+10 15180.48 16-APR-13:23 28.60 16.10 0.600772E+09 845.71 17-APR-13:50 28.72 16.68
May 0.897654E+10 15204.67 30-MAY-04:12 19.43 17.60 0.658434E+09 845.64 09-MAY-13:09 19.43 17.60
June 0.112445E+11 15823.54 19-JUN-04:12 20.77 19.95 0.660953E+09 845.65 02-JUN-13:09 20.77 19.95
July 0.126442E+11 17838.08 16-JUL-15:12 33.30 22.53 0.615260E+09 845.61 18-JUL-13:09 30.00 21.94
August 0.155087E+11 21366.56 20-AUG-13:42 28.95 24.23 0.690706E+09 845.61 25-AUG-13:09 30.18 18.86
September 0.104599E+11 21393.16 24-SEP-11:43 28.22 19.73 0.610539E+09 845.64 13-SEP-13:09 28.22 19.73
October 0.979773E+10 22775.91 09-OCT-14:12 27.40 19.48 0.619640E+09 881.31 10-OCT-13:50 29.22 21.00
November 0.787759E+10 22385.03 12-NOV-14:12 19.27 10.66 0.609076E+09 859.84 06-NOV-14:09 19.27 10.66
December 0.661989E+10 21271.55 10-DEC-12:43 15.22 7.57 0.576231E+09 845.65 11-DEC-10:00 15.00 12.11
                     
Annual Sum or Average 0.110535E+12         0.739251E+10        
Minimum of Months 0.448536E+10 15180.48   14.63 6.24 0.523728E+09 845.61   14.63 6.24
Maximum of Months 0.155087E+11 22775.91   33.30 24.23 0.690706E+09 881.31   30.18 21.94



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.355910E+10 5620.44 23-JAN-16:30 10.00 3.54 0.339491E+09 544.91 20-JAN-14:00 10.00 3.54
February 0.469667E+10 20885.02 26-FEB-15:42 24.50 12.42 0.333504E+09 544.96 22-FEB-14:09 24.50 12.42
March 0.839345E+10 19572.29 30-MAR-04:12 17.40 15.44 0.437672E+09 544.98 08-MAR-10:30 17.40 15.44
April 0.106985E+11 24158.98 09-APR-16:32 21.70 10.73 0.394685E+09 545.00 17-APR-13:50 28.72 16.68
May 0.922475E+10 23702.32 29-MAY-15:42 29.90 20.57 0.425449E+09 544.95 09-MAY-13:09 29.90 20.57
June 0.122603E+11 25886.29 11-JUN-15:51 32.80 21.45 0.427187E+09 544.96 09-JUN-09:00 32.80 21.45
July 0.142015E+11 24824.01 09-JUL-16:41 33.40 22.81 0.397526E+09 544.93 05-JUL-13:09 33.40 22.81
August 0.171678E+11 25616.70 13-AUG-16:31 30.73 22.34 0.446003E+09 544.93 25-AUG-13:09 30.18 18.86
September 0.873578E+10 23593.98 04-SEP-17:02 28.12 21.99 0.393518E+09 544.95 19-SEP-09:09 19.68 14.68
October 0.757430E+10 23735.94 22-OCT-15:32 23.30 14.86 0.401464E+09 544.95 04-OCT-13:00 23.30 14.86
November 0.647381E+10 19654.22 12-NOV-14:52 20.00 10.89 0.396008E+09 544.96 06-NOV-10:09 20.00 10.89
December 0.578485E+10 19745.06 13-DEC-05:12 17.03 15.54 0.379395E+09 544.96 11-DEC-10:00 17.03 15.54
                     
Annual Sum or Average 0.108771E+12         0.477190E+10        
Minimum of Months 0.355910E+10 5620.44   10.00 3.54 0.333504E+09 544.91   10.00 3.54
Maximum of Months 0.171678E+11 25886.29   33.40 22.81 0.446003E+09 545.00   33.40 22.81



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.638622E+09 2808.25 31-JAN-17:00 19.40 13.37 0.470757E+09 737.19 31-JAN-14:00 19.40 13.37
February 0.145494E+10 4000.67 28-FEB-15:00 25.00 13.71 0.444700E+09 845.60 28-FEB-14:30 25.00 13.71
March 0.381517E+10 6550.97 30-MAR-15:50 27.80 17.41 0.592411E+09 845.59 09-MAR-14:09 27.80 17.41
April 0.470111E+10 7130.54 19-APR-14:30 26.15 17.54 0.567505E+09 845.63 12-APR-13:50 26.15 17.54
May 0.678003E+10 8887.42 30-MAY-15:00 30.60 21.44 0.650099E+09 845.61 09-MAY-13:09 30.60 21.44
June 0.925886E+10 16382.18 25-JUN-16:11 33.13 22.15 0.659959E+09 845.63 02-JUN-13:09 33.13 22.15
July 0.963044E+10 15604.29 16-JUL-13:32 33.33 23.57 0.614432E+09 845.59 13-JUL-13:09 33.33 23.57
August 0.100599E+11 12602.33 16-AUG-04:12 23.30 22.06 0.690095E+09 845.59 25-AUG-13:09 30.18 18.86
September 0.642799E+10 11781.71 11-SEP-05:02 20.40 19.24 0.601315E+09 845.61 13-SEP-13:09 23.92 15.70
October 0.411297E+10 6438.44 02-OCT-14:30 26.70 20.05 0.562362E+09 845.59 05-OCT-13:50 20.00 14.95
November 0.271610E+10 3736.19 20-NOV-14:20 5.40 2.35 0.511260E+09 845.58 03-NOV-13:00 5.40 2.35
December 0.137947E+10 3058.81 13-DEC-15:10 18.12 16.87 0.464382E+09 803.26 13-DEC-14:00 18.12 16.87
                     
Annual Sum or Average 0.609756E+11         0.682928E+10        
Minimum of Months 0.638622E+09 2808.25   5.40 2.35 0.444700E+09 737.19   5.40 2.35
Maximum of Months 0.100599E+11 16382.18   33.33 23.57 0.690095E+09 845.63   33.33 23.57



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.833616E+09 2772.50 11-JAN-10:15 0.93 -1.3 0.222585E+09 439.28 31-JAN-11:50 16.73 13.07
February 0.162569E+10 4966.52 27-FEB-10:00 12.80 5.65 0.216480E+09 521.21 28-FEB-11:09 20.87 12.02
March 0.387052E+10 6442.37 13-MAR-10:20 14.23 6.73 0.289332E+09 521.23 08-MAR-09:00 14.23 6.73
April 0.519866E+10 18169.77 16-APR-10:53 26.10 15.47 0.276400E+09 521.24 18-APR-14:30 26.40 16.44
May 0.698407E+10 20007.62 07-MAY-09:02 23.58 19.38 0.307618E+09 521.27 11-MAY-10:09 17.67 13.57
June 0.869086E+10 20935.64 04-JUN-09:52 26.70 19.39 0.312410E+09 521.23 09-JUN-10:09 24.78 15.66
July 0.909329E+10 20750.77 04-JUL-09:42 26.83 23.40 0.291250E+09 521.20 20-JUL-10:20 28.17 22.11
August 0.922299E+10 21300.62 27-AUG-09:41 26.83 21.78 0.326088E+09 521.20 18-AUG-12:09 26.83 21.78
September 0.648218E+10 19578.18 24-SEP-10:12 26.67 18.72 0.283162E+09 521.21 15-SEP-10:20 26.67 18.72
October 0.416065E+10 7520.66 11-OCT-10:10 23.27 19.04 0.272399E+09 521.21 05-OCT-10:20 23.27 19.04
November 0.271517E+10 4173.29 06-NOV-09:50 14.03 12.24 0.245110E+09 521.19 06-NOV-09:00 14.40 12.50
December 0.155409E+10 2801.80 07-DEC-10:25 7.80 5.02 0.220325E+09 470.79 07-DEC-09:00 7.80 5.02
                     
Annual Sum or Average 0.604318E+11         0.326316E+10        
Minimum of Months 0.833616E+09 2772.50   0.93 -1.3 0.216480E+09 439.28   7.80 5.02
Maximum of Months 0.922299E+10 21300.62   26.83 23.40 0.326088E+09 521.27   28.17 22.11



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.315108E+10 16657.78 29-JAN-13:33 14.63 6.24 0.537906E+09 858.92 27-JAN-10:50 14.63 6.24
February 0.398775E+10 20383.11 26-FEB-12:32 23.53 12.41 0.498699E+09 859.57 21-FEB-14:39 23.53 12.41
March 0.672763E+10 15754.79 26-MAR-15:02 20.10 9.52 0.639824E+09 845.68 08-MAR-10:39 20.10 9.52
April 0.674507E+10 20019.47 16-APR-13:32 28.70 16.13 0.585514E+09 845.71 12-APR-13:50 28.70 16.13
May 0.783279E+10 13733.47 29-MAY-14:12 28.67 20.44 0.651506E+09 845.64 09-MAY-13:09 28.67 20.44
June 0.954633E+10 19529.11 25-JUN-16:11 33.13 22.15 0.658887E+09 845.65 02-JUN-13:09 33.13 22.15
July 0.101520E+11 18774.53 16-JUL-12:53 32.20 24.15 0.614597E+09 845.61 13-JUL-13:09 32.20 24.15
August 0.121429E+11 20200.24 27-AUG-13:02 31.70 22.66 0.690963E+09 845.61 25-AUG-13:09 31.70 22.66
September 0.949484E+10 21219.76 24-SEP-12:52 28.90 19.89 0.606465E+09 845.64 22-SEP-13:39 28.90 19.89
October 0.844735E+10 21657.50 08-OCT-14:02 26.78 18.72 0.602662E+09 887.71 10-OCT-13:50 29.22 21.00
November 0.628652E+10 20724.89 11-NOV-12:02 19.68 11.79 0.582840E+09 862.66 06-NOV-14:09 19.68 11.79
December 0.470455E+10 20524.72 10-DEC-13:43 16.52 7.81 0.542971E+09 845.82 07-DEC-10:50 16.52 7.81
                     
Annual Sum or Average 0.892188E+11         0.721283E+10        
Minimum of Months 0.315108E+10 13733.47   14.63 6.24 0.498699E+09 845.61   14.63 6.24
Maximum of Months 0.121429E+11 21657.50   33.13 24.15 0.690963E+09 887.71   33.13 24.15



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.115895E+10 3098.85 10-JAN-17:33 3.33 1.20 0.308768E+09 505.17 11-JAN-16:49 6.28 1.74
February 0.197806E+10 7654.55 27-FEB-17:00 22.20 11.44 0.292068E+09 544.93 28-FEB-14:39 25.00 13.71
March 0.462903E+10 10689.31 30-MAR-16:00 27.80 17.47 0.384182E+09 544.93 08-MAR-14:00 27.80 17.47
April 0.572827E+10 20108.12 09-APR-17:12 21.50 10.93 0.365362E+09 544.97 12-APR-13:50 28.72 17.01
May 0.718451E+10 21588.44 21-MAY-17:22 26.15 19.60 0.414049E+09 544.95 09-MAY-13:09 26.15 19.60
June 0.884839E+10 22533.81 25-JUN-16:11 33.13 22.15 0.423472E+09 544.96 02-JUN-13:09 33.13 22.15
July 0.924811E+10 22898.99 23-JUL-17:11 29.63 23.03 0.395338E+09 544.93 13-JUL-13:09 29.63 23.03
August 0.985750E+10 22052.04 27-AUG-16:21 31.40 21.35 0.444758E+09 544.93 25-AUG-13:09 31.40 21.35
September 0.665933E+10 18045.08 24-SEP-16:52 27.80 19.57 0.383802E+09 544.94 13-SEP-13:09 27.80 19.57
October 0.465771E+10 15664.16 08-OCT-16:42 26.78 18.71 0.361934E+09 544.93 19-OCT-13:09 22.48 19.30
November 0.314387E+10 7067.99 06-NOV-16:00 20.60 10.48 0.335626E+09 544.92 15-NOV-14:00 21.70 11.58
December 0.190882E+10 3795.86 11-DEC-15:50 21.10 15.67 0.308380E+09 537.93 12-DEC-14:00 22.80 16.17
                     
Annual Sum or Average 0.650026E+11         0.441774E+10        
Minimum of Months 0.115895E+10 3098.85   3.33 1.20 0.292068E+09 505.17   6.28 1.74
Maximum of Months 0.985750E+10 22898.99   33.13 23.03 0.444758E+09 544.97   33.13 23.03



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.472228E+09 2864.31 20-JAN-16:20 17.03 12.34 0.468166E+09 727.89 20-JAN-14:00 17.03 12.34
February 0.112660E+10 3698.96 28-FEB-15:30 24.15 13.12 0.437948E+09 845.59 28-FEB-14:00 24.15 13.12
March 0.321195E+10 7383.83 30-MAR-15:50 27.80 17.41 0.570714E+09 845.59 09-MAR-14:09 27.80 17.41
April 0.445854E+10 7765.51 19-APR-14:30 26.15 17.54 0.550478E+09 845.60 20-APR-13:39 23.90 16.49
May 0.693803E+10 10007.14 30-MAY-15:00 30.60 21.44 0.641847E+09 845.82 16-MAY-13:39 30.60 21.44
June 0.982576E+10 19367.51 25-JUN-16:11 33.13 22.15 0.658058E+09 845.63 02-JUN-13:09 33.13 22.15
July 0.103297E+11 18821.52 16-JUL-13:32 33.33 23.57 0.613838E+09 845.59 03-JUL-13:09 33.33 23.57
August 0.107696E+11 17489.10 06-AUG-16:21 32.50 23.58 0.689745E+09 845.59 25-AUG-13:09 30.18 18.86
September 0.643153E+10 13376.24 07-SEP-05:02 22.20 21.11 0.592720E+09 845.61 13-SEP-13:09 23.92 15.70
October 0.348337E+10 6815.16 02-OCT-14:40 26.70 20.10 0.541569E+09 845.58 19-OCT-13:09 22.48 19.30
November 0.195490E+10 3267.42 02-NOV-15:50 22.30 16.05 0.489884E+09 828.51 03-NOV-13:00 21.70 17.40
December 0.905896E+09 3080.28 13-DEC-15:10 18.12 16.87 0.456327E+09 790.43 13-DEC-14:00 18.12 16.87
                     
Annual Sum or Average 0.599081E+11         0.671130E+10        
Minimum of Months 0.472228E+09 2864.31   17.03 12.34 0.437948E+09 727.89   17.03 12.34
Maximum of Months 0.107696E+11 19367.51   33.33 23.58 0.689745E+09 845.82   33.33 23.57



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.627989E+09 2573.30 31-JAN-15:00 21.10 12.97 0.301238E+09 454.19 31-JAN-14:00 21.10 12.97
February 0.136844E+10 3534.90 27-FEB-10:40 14.27 6.32 0.291043E+09 544.95 28-FEB-10:00 20.60 11.95
March 0.339962E+10 6076.56 30-MAR-11:00 22.20 17.83 0.387262E+09 544.99 08-MAR-10:09 22.20 17.83
April 0.496646E+10 9778.77 14-APR-09:50 20.82 14.67 0.373083E+09 544.96 17-APR-09:09 20.47 14.59
May 0.714682E+10 20211.71 07-MAY-09:12 23.87 19.51 0.417511E+09 545.12 16-MAY-13:39 28.30 17.68
June 0.918280E+10 20031.35 25-JUN-08:52 26.70 22.00 0.425215E+09 544.97 09-JUN-09:00 26.70 22.00
July 0.970650E+10 20519.48 23-JUL-08:32 25.77 22.55 0.394715E+09 544.93 03-JUL-13:09 25.77 22.55
August 0.986836E+10 21239.66 27-AUG-09:12 25.73 21.64 0.443958E+09 544.93 01-AUG-13:09 25.73 21.64
September 0.652370E+10 19734.57 04-SEP-09:22 25.85 21.92 0.383438E+09 544.95 13-SEP-13:09 23.92 15.70
October 0.368612E+10 7336.15 11-OCT-10:20 23.73 19.29 0.365810E+09 544.94 05-OCT-09:00 23.73 19.29
November 0.211368E+10 3026.61 06-NOV-10:30 15.80 12.82 0.321415E+09 532.69 06-NOV-10:39 16.27 12.91
December 0.111176E+10 2736.13 13-DEC-15:00 18.30 16.86 0.294541E+09 480.10 13-DEC-14:00 18.30 16.86
                     
Annual Sum or Average 0.597022E+11         0.439923E+10        
Minimum of Months 0.627989E+09 2573.30   14.27 6.32 0.291043E+09 454.19   16.27 11.95
Maximum of Months 0.986836E+10 21239.66   26.70 22.55 0.443958E+09 545.12   28.30 22.55



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.268604E+10 10410.02 11-JAN-14:30 6.70 2.05 0.523901E+09 845.63 10-JAN-14:09 6.70 2.05
February 0.340365E+10 20795.67 26-FEB-14:52 25.00 12.75 0.486554E+09 845.65 22-FEB-14:09 25.00 12.75
March 0.593532E+10 16303.50 30-MAR-13:40 27.43 17.97 0.617276E+09 845.66 13-MAR-13:00 27.43 17.97
April 0.652852E+10 13433.31 17-APR-14:00 28.90 16.63 0.569166E+09 845.64 07-APR-13:00 28.90 16.63
May 0.809774E+10 19059.69 29-MAY-14:12 28.67 20.44 0.641801E+09 845.90 16-MAY-13:39 28.67 20.44
June 0.102018E+11 22332.85 25-JUN-16:11 33.13 22.15 0.655715E+09 845.65 02-JUN-13:09 33.13 22.15
July 0.109576E+11 21566.38 16-JUL-12:53 32.20 24.15 0.613215E+09 845.60 03-JUL-13:09 32.20 24.15
August 0.129783E+11 22170.38 13-AUG-13:32 30.40 22.46 0.690188E+09 845.61 25-AUG-13:09 30.18 18.86
September 0.957452E+10 21990.46 24-SEP-11:43 28.22 19.73 0.598909E+09 845.64 22-SEP-13:39 28.22 19.73
October 0.761730E+10 23882.86 09-OCT-14:12 27.40 19.48 0.585014E+09 865.65 10-OCT-13:50 29.22 21.00
November 0.516847E+10 22888.93 11-NOV-14:52 21.10 11.84 0.556471E+09 845.64 06-NOV-10:09 21.10 11.84
December 0.377495E+10 12346.79 08-DEC-14:10 12.80 5.52 0.523993E+09 845.61 12-DEC-14:00 22.80 16.17
                     
Annual Sum or Average 0.869242E+11         0.706220E+10        
Minimum of Months 0.268604E+10 10410.02   6.70 2.05 0.486554E+09 845.60   6.70 2.05
Maximum of Months 0.129783E+11 23882.86   33.13 24.15 0.690188E+09 865.65   33.13 24.15



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.101431E+10 3209.56 20-JAN-16:40 16.87 11.91 0.305403E+09 485.24 11-JAN-16:49 16.87 11.91
February 0.171892E+10 7566.54 27-FEB-17:00 22.20 11.44 0.287589E+09 544.88 28-FEB-14:00 25.00 13.71
March 0.416218E+10 11234.20 30-MAR-16:00 27.80 17.47 0.372024E+09 544.92 08-MAR-14:00 27.80 17.47
April 0.561931E+10 19237.61 09-APR-16:52 21.70 10.78 0.354123E+09 544.94 20-APR-13:39 23.90 16.49
May 0.740119E+10 23134.91 21-MAY-17:22 26.15 19.60 0.406669E+09 545.11 16-MAY-13:39 26.15 19.60
June 0.930550E+10 24611.65 25-JUN-16:11 33.13 22.15 0.420709E+09 544.96 02-JUN-13:09 33.13 22.15
July 0.982973E+10 24417.85 23-JUL-17:11 29.63 23.03 0.393825E+09 544.93 03-JUL-13:09 29.63 23.03
August 0.104395E+11 23215.85 13-AUG-16:51 31.10 22.45 0.443695E+09 544.93 25-AUG-13:09 30.18 18.86
September 0.676243E+10 21909.53 04-SEP-17:02 28.12 21.99 0.376305E+09 544.94 13-SEP-13:09 23.92 15.70
October 0.422383E+10 13150.64 09-OCT-16:12 27.43 19.51 0.350686E+09 544.92 19-OCT-13:30 23.05 19.50
November 0.260413E+10 6783.81 06-NOV-16:00 20.60 10.48 0.324116E+09 544.88 06-NOV-14:00 20.60 10.48
December 0.152072E+10 3407.64 11-DEC-16:00 21.10 15.91 0.301850E+09 525.48 12-DEC-14:00 22.80 16.17
                     
Annual Sum or Average 0.646018E+11         0.433699E+10        
Minimum of Months 0.101431E+10 3209.56   16.87 10.48 0.287589E+09 485.24   16.87 10.48
Maximum of Months 0.104395E+11 24611.65   33.13 23.03 0.443695E+09 545.11   33.13 23.03



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: GROUNDFLOOR_PLENUM

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.122094E+10 6219.40 26-JAN-06:01 -5.0 -6.9 0.00 0.00 01-JAN-00:10 -5.0 -6.9
February 0.202251E+10 6470.40 03-FEB-06:01 -8.4 -9.9 0.00 0.00 01-FEB-00:10 -8.4 -9.9
March 0.467701E+10 6396.08 30-MAR-15:00 27.80 17.08 0.00 0.00 01-MAR-00:10 27.80 17.08
April 0.597250E+10 8171.25 17-APR-15:30 28.90 16.41 0.00 0.00 01-APR-00:10 28.90 16.41
May 0.665464E+10 10357.53 30-MAY-05:03 18.68 17.36 0.00 0.00 01-MAY-00:10 18.68 17.36
June 0.873142E+10 10971.43 19-JUN-05:02 21.02 20.20 0.00 0.00 01-JUN-00:10 21.02 20.20
July 0.948721E+10 9808.26 11-JUL-05:02 20.50 19.77 0.00 0.00 01-JUL-00:10 20.50 19.77
August 0.107706E+11 9341.17 09-AUG-05:02 24.40 22.06 0.00 0.00 01-AUG-00:10 24.40 22.06
September 0.723642E+10 12621.66 05-SEP-05:02 21.70 20.50 0.00 0.00 01-SEP-00:10 21.70 20.50
October 0.539197E+10 7619.75 10-OCT-05:13 15.73 14.81 0.00 0.00 01-OCT-00:10 15.73 14.81
November 0.398748E+10 5756.34 13-NOV-06:08 3.80 1.16 0.00 0.00 01-NOV-00:10 3.80 1.16
December 0.263810E+10 4734.13 14-DEC-06:13 6.50 5.21 0.00 0.00 01-DEC-00:10 6.50 5.21
                     
Annual Sum or Average 0.687908E+11         0.00        
Minimum of Months 0.122094E+10 4734.13   -8.4 -9.9 0.00 0.00   -8.4 -9.9
Maximum of Months 0.107706E+11 12621.66   28.90 22.06 0.00 0.00   28.90 22.06



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: MIDFLOOR_PLENUM

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.490329E+09 7752.41 14-JAN-04:01 -6.1 -7.2 0.00 0.00 01-JAN-00:10 -6.1 -7.2
February 0.927602E+09 10065.98 12-FEB-06:01 -12.3 -13.5 0.00 0.00 01-FEB-00:10 -12.3 -13.5
March 0.245693E+10 5778.49 18-MAR-05:02 3.22 0.02 0.00 0.00 01-MAR-00:10 3.22 0.02
April 0.364388E+10 6755.79 06-APR-05:03 0.18 -0.9 0.00 0.00 01-APR-00:10 0.18 -0.9
May 0.506693E+10 5712.45 19-MAY-05:13 16.50 15.56 0.00 0.00 01-MAY-00:10 16.50 15.56
June 0.693328E+10 6550.65 29-JUN-16:00 31.10 23.22 0.00 0.00 01-JUN-00:10 31.10 23.22
July 0.750615E+10 9678.85 06-JUL-05:02 22.80 21.19 0.00 0.00 01-JUL-00:10 22.80 21.19
August 0.811433E+10 10025.13 21-AUG-05:02 21.78 21.78 0.00 0.00 01-AUG-00:10 21.78 21.78
September 0.568353E+10 6588.09 07-SEP-15:40 31.70 23.45 0.00 0.00 01-SEP-00:10 31.70 23.45
October 0.325261E+10 5286.34 13-OCT-05:10 6.02 4.50 0.00 0.00 01-OCT-00:10 6.02 4.50
November 0.172116E+10 8582.94 22-NOV-05:01 -2.9 -3.8 0.00 0.00 01-NOV-00:10 -2.9 -3.8
December 0.895925E+09 8534.89 01-DEC-05:01 -3.0 -4.3 0.00 0.00 01-DEC-00:10 -3.0 -4.3
                     
Annual Sum or Average 0.466926E+11         0.00        
Minimum of Months 0.490329E+09 5286.34   -12.3 -13.5 0.00 0.00   -12.3 -13.5
Maximum of Months 0.811433E+10 10065.98   31.70 23.45 0.00 0.00   31.70 23.45



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: TOPFLOOR_PLENUM

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.177427E+09 2551.06 31-JAN-13:10 19.60 13.60 0.00 0.00 01-JAN-00:10 19.60 13.60
February 0.844029E+09 6092.74 28-FEB-16:10 23.40 12.60 0.00 0.00 01-FEB-00:10 23.40 12.60
March 0.303291E+10 13188.41 30-MAR-14:20 27.80 17.60 0.00 0.00 01-MAR-00:10 27.80 17.60
April 0.553827E+10 16036.76 17-APR-14:40 28.90 16.48 0.00 0.00 01-APR-00:10 28.90 16.48
May 0.890763E+10 17025.88 16-MAY-15:40 29.40 17.64 0.00 0.00 01-MAY-00:10 29.40 17.64
June 0.124964E+11 17712.03 13-JUN-13:50 33.80 22.33 0.00 0.00 01-JUN-00:10 33.80 22.33
July 0.132552E+11 19740.61 07-JUL-15:10 35.10 23.86 0.00 0.00 01-JUL-00:10 35.10 23.86
August 0.138933E+11 19476.71 01-AUG-14:00 33.90 23.66 0.00 0.00 01-AUG-00:10 33.90 23.66
September 0.774338E+10 16381.49 06-SEP-14:00 31.10 23.78 0.00 0.00 01-SEP-00:10 31.10 23.78
October 0.369162E+10 12040.27 10-OCT-14:40 29.07 20.78 0.00 0.00 01-OCT-00:10 29.07 20.78
November 0.129696E+10 5430.44 05-NOV-14:10 23.40 18.52 0.00 0.00 01-NOV-00:10 23.40 18.52
December 0.351812E+09 3283.85 12-DEC-13:10 21.38 16.69 0.00 0.00 01-DEC-00:10 21.38 16.69
                     
Annual Sum or Average 0.712289E+11         0.00        
Minimum of Months 0.177427E+09 2551.06   19.60 12.60 0.00 0.00   19.60 12.60
Maximum of Months 0.138933E+11 19740.61   35.10 23.86 0.00 0.00   35.10 23.86



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.268804E+10 1910.36 23-JAN-17:00 10.00 3.54 95230840.26 126.84 19-JAN-10:30 10.00 3.54
February 0.760594E+10 4019.05 24-FEB-17:50 15.18 6.70 86397279.15 126.84 17-FEB-14:00 15.18 6.70
March 0.143887E+11 7150.58 31-MAR-24:00 12.10 7.93 0.103239E+09 126.84 28-MAR-09:09 12.10 7.93
April 0.190008E+11 7933.39 09-APR-18:15 19.80 10.92 91606013.01 126.83 03-APR-09:39 19.80 10.92
May 0.455130E+10 3485.90 31-MAY-24:00 21.00 18.72 99243266.80 126.86 23-MAY-13:30 21.00 18.72
June 0.946048E+10 5395.09 30-JUN-24:00 22.30 21.46 98973899.05 126.86 23-JUN-09:09 22.30 21.46
July 0.148075E+11 7228.22 31-JUL-24:00 25.20 21.98 91891347.74 126.85 26-JUL-09:09 25.20 21.98
August 0.198849E+11 7907.71 13-AUG-19:23 29.70 21.78 0.104647E+09 134.75 02-AUG-13:00 29.70 21.78
September 0.450462E+10 3184.82 30-SEP-24:00 16.80 15.75 91612531.98 126.86 01-SEP-13:20 16.80 15.75
October 0.942464E+10 5103.99 31-OCT-24:00 9.70 6.26 95238265.13 126.87 19-OCT-09:30 9.70 6.26
November 0.138387E+11 6014.36 06-NOV-17:00 18.90 9.61 94301942.12 126.84 02-NOV-09:20 18.90 9.61
December 0.190024E+11 7807.88 19-DEC-17:00 13.90 5.19 91881254.02 126.83 06-DEC-14:00 13.90 5.19
                     
Annual Sum or Average 0.139158E+12         0.114426E+10        
Minimum of Months 0.268804E+10 1910.36   9.70 3.54 86397279.15 126.83   9.70 3.54
Maximum of Months 0.198849E+11 7933.39   29.70 21.98 0.104647E+09 134.75   29.70 21.98



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: DATACENTER_MID_ZN_6

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.670383E+09 1529.00 27-JAN-17:00 4.40 -1.6 94702393.55 126.83 20-JAN-14:00 4.40 -1.6
February 0.536324E+10 3714.21 24-FEB-17:50 15.18 6.70 86397213.78 126.84 17-FEB-14:00 15.18 6.70
March 0.126524E+11 6627.55 31-MAR-23:50 12.13 7.92 0.103239E+09 126.84 31-MAR-13:09 12.13 7.92
April 0.175636E+11 7466.89 14-APR-18:30 23.35 14.91 91606202.75 126.83 03-APR-09:39 23.35 14.91
May 0.392568E+10 3251.71 31-MAY-24:00 21.00 18.72 99238505.77 126.85 30-MAY-13:00 21.00 18.72
June 0.884227E+10 5116.08 30-JUN-24:00 22.30 21.46 98974539.05 126.86 16-JUN-13:00 22.30 21.46
July 0.140448E+11 6975.71 31-JUL-24:00 25.20 21.98 91892599.41 126.85 26-JUL-09:09 25.20 21.98
August 0.188962E+11 7433.26 13-AUG-18:37 30.37 21.91 0.104551E+09 135.08 02-AUG-13:00 30.37 21.91
September 0.384194E+10 2580.47 30-SEP-24:00 16.80 15.75 91609156.94 126.84 18-SEP-13:00 16.80 15.75
October 0.795361E+10 4300.80 31-OCT-23:50 9.68 6.17 95237624.69 126.86 18-OCT-13:39 9.68 6.17
November 0.117044E+11 5573.89 06-NOV-17:00 18.90 9.61 94301891.07 126.83 03-NOV-13:00 18.90 9.61
December 0.157654E+11 7147.65 08-DEC-17:00 11.10 4.72 91881377.31 126.83 13-DEC-14:20 18.30 16.86
                     
Annual Sum or Average 0.121224E+12         0.114363E+10        
Minimum of Months 0.670383E+09 1529.00   4.40 -1.6 86397213.78 126.83   4.40 -1.6
Maximum of Months 0.188962E+11 7466.89   30.37 21.98 0.104551E+09 135.08   30.37 21.98



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.377397E+09 1506.78 20-JAN-17:00 16.70 11.48 92126198.28 127.94 18-JAN-10:30 16.70 11.48
February 0.436029E+10 3666.30 28-FEB-17:00 23.90 12.94 86392106.47 126.84 17-FEB-14:00 23.90 12.94
March 0.118314E+11 6362.44 31-MAR-23:20 12.23 7.91 0.103239E+09 126.84 31-MAR-13:09 12.23 7.91
April 0.171141E+11 7550.07 14-APR-18:30 23.35 14.91 91606351.10 126.83 04-APR-09:50 23.35 14.91
May 0.380841E+10 3207.37 31-MAY-24:00 21.00 18.72 99239872.54 126.86 30-MAY-13:09 21.00 18.72
June 0.887647E+10 5077.78 30-JUN-24:00 22.30 21.46 98974424.49 126.86 26-JUN-09:00 22.30 21.46
July 0.141226E+11 7019.30 31-JUL-24:00 25.20 21.98 91892388.71 126.85 26-JUL-09:09 25.20 21.98
August 0.189944E+11 7660.98 13-AUG-18:52 30.00 21.93 0.104197E+09 133.68 02-AUG-13:00 30.00 21.93
September 0.364741E+10 2084.04 08-SEP-18:10 28.80 21.95 91609261.08 126.84 18-SEP-13:00 25.00 18.13
October 0.716882E+10 3849.39 11-OCT-17:30 23.30 13.67 95237698.24 126.86 18-OCT-13:00 25.00 22.63
November 0.104721E+11 5559.44 06-NOV-17:00 18.90 9.61 94301931.13 126.83 27-NOV-14:00 22.20 17.55
December 0.141624E+11 7039.49 07-DEC-17:00 14.40 6.55 91881445.73 126.83 13-DEC-14:30 18.30 16.86
                     
Annual Sum or Average 0.114936E+12         0.114070E+10        
Minimum of Months 0.377397E+09 1506.78   12.23 6.55 86392106.47 126.83   12.23 7.91
Maximum of Months 0.189944E+11 7660.98   30.00 21.98 0.104197E+09 133.68   30.00 22.63



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.235546E+12 91720.11 20-JAN-17:00 16.70 11.48 0.206171E+10 2747.21 12-JAN-10:00 16.70 11.48
February 0.433150E+12 183494.40 28-FEB-17:00 23.90 12.94 0.187075E+10 2748.92 09-FEB-14:50 23.90 12.94
March 0.726919E+12 358109.53 31-MAR-24:00 12.10 7.93 0.223509E+10 2747.33 20-MAR-13:09 12.10 7.93
April 0.938907E+12 366259.93 20-APR-15:30 24.15 16.80 0.200651E+10 3009.21 12-APR-13:00 24.15 16.80
May 0.239456E+12 175353.30 31-MAY-24:00 21.00 18.72 0.214857E+10 2746.54 25-MAY-13:00 21.00 18.72
June 0.469880E+12 267496.00 30-JUN-24:00 22.30 21.46 0.214257E+10 2746.33 26-JUN-09:00 22.30 21.46
July 0.731540E+12 359653.72 31-JUL-24:00 25.20 21.98 0.198919E+10 2745.89 26-JUL-09:09 25.20 21.98
August 0.972908E+12 370531.17 07-AUG-21:14 22.60 21.54 0.254439E+10 3589.41 18-AUG-13:50 33.48 22.91
September 0.237060E+12 175462.04 30-SEP-24:00 16.80 15.75 0.198355E+10 2746.98 28-SEP-13:00 16.80 15.75
October 0.488154E+12 268176.51 31-OCT-24:00 9.70 6.26 0.206165E+10 2746.38 18-OCT-13:30 9.70 6.26
November 0.709197E+12 277506.15 06-NOV-17:00 18.90 9.61 0.204176E+10 2747.81 22-NOV-14:09 11.28 3.90
December 0.975361E+12 368470.04 13-DEC-17:00 16.70 16.70 0.198969E+10 2748.60 18-DEC-14:09 8.17 1.58
                     
Annual Sum or Average 0.715808E+13         0.250754E+11        
Minimum of Months 0.235546E+12 91720.11   9.70 6.26 0.187075E+10 2745.89   8.17 1.58
Maximum of Months 0.975361E+12 370531.17   25.20 21.98 0.254439E+10 3589.41   33.48 22.91



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: BASEMENT

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.290766E+09 12674.25 20-JAN-05:25 12.80
February 76328087.12 12672.94 23-FEB-05:15 5.93
March 0.158861E+09 12636.24 15-MAR-04:15 8.30
April 0.196656E+09 14548.07 15-APR-16:01 28.03
May 0.282416E+09 16582.11 06-MAY-16:02 29.63
June 0.261027E+09 21384.94 24-JUN-16:02 33.22
July 0.402494E+09 25904.35 08-JUL-16:01 36.32
August 0.435839E+09 20075.18 19-AUG-16:02 32.33
September 0.383820E+09 15096.81 23-SEP-16:02 28.72
October 0.347170E+09 14424.50 09-OCT-13:32 26.83
November 0.340944E+09 14253.19 12-NOV-12:52 17.80
December 0.139494E+09 12173.40 20-DEC-05:54 2.80
         
Annual Sum or Average 0.331582E+10      
Minimum of Months 76328087.12 12173.40   2.80
Maximum of Months 0.435839E+09 25904.35   36.32



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: CORE_BOTTOM

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:05 5.70
February 0.00 0.00 01-FEB-00:10 9.92
March 0.00 0.00 01-MAR-00:10 15.32
April 0.00 0.00 01-APR-00:10 12.05
May 0.00 0.00 01-MAY-00:03 16.68
June 0.00 0.00 01-JUN-00:10 20.93
July 0.00 0.00 01-JUL-00:10 22.28
August 0.00 0.00 01-AUG-00:03 25.13
September 0.00 0.00 01-SEP-00:03 21.40
October 0.00 0.00 01-OCT-00:10 16.85
November 0.00 0.00 01-NOV-00:10 9.70
December 0.00 0.00 01-DEC-00:10 1.80
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   1.80
Maximum of Months 0.00 0.00   25.13



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: CORE_MID

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.233660E+09 37843.55 09-JAN-05:01 -2.2
February 0.141128E+09 36291.13 13-FEB-05:11 -5.2
March 0.00 0.00 01-MAR-00:10 15.32
April 0.00 0.00 01-APR-00:10 12.05
May 0.00 0.00 01-MAY-00:03 16.68
June 0.00 0.00 01-JUN-00:10 20.93
July 0.00 0.00 01-JUL-00:10 22.28
August 0.00 0.00 01-AUG-00:03 25.13
September 0.00 0.00 01-SEP-00:03 21.40
October 0.00 0.00 01-OCT-00:10 16.85
November 0.00 0.00 01-NOV-00:10 9.70
December 3866396.02 29243.13 26-DEC-06:02 3.30
         
Annual Sum or Average 0.378654E+09      
Minimum of Months 0.00 0.00   -5.2
Maximum of Months 0.233660E+09 37843.55   25.13



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: CORE_TOP

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.395113E+10 80513.12 09-JAN-04:11 -1.9
February 0.183126E+10 80372.51 13-FEB-04:01 -5.0
March 25268174.43 64067.29 20-MAR-05:03 5.00
April 0.00 0.00 01-APR-00:10 12.05
May 0.00 0.00 01-MAY-00:03 16.68
June 0.00 0.00 01-JUN-00:10 20.93
July 0.00 0.00 01-JUL-00:10 22.28
August 0.00 0.00 01-AUG-00:03 25.13
September 0.00 0.00 01-SEP-00:03 21.40
October 22825175.75 64135.61 30-OCT-05:03 8.90
November 0.164454E+09 66662.47 22-NOV-05:01 -2.9
December 0.195390E+10 78823.10 04-DEC-04:01 -2.3
         
Annual Sum or Average 0.794883E+10      
Minimum of Months 0.00 0.00   -5.0
Maximum of Months 0.395113E+10 80513.12   25.13



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.382286E+09 12352.16 09-JAN-05:01 -2.2
February 0.147025E+09 12406.30 13-FEB-05:01 -5.1
March 0.00 0.00 01-MAR-00:10 15.32
April 0.00 0.00 01-APR-00:10 12.05
May 0.00 0.00 01-MAY-00:03 16.68
June 0.00 0.00 01-JUN-00:10 20.93
July 0.00 0.00 01-JUL-00:10 22.28
August 0.00 0.00 01-AUG-00:03 25.13
September 0.00 0.00 01-SEP-00:03 21.40
October 0.00 0.00 01-OCT-00:10 16.85
November 4892765.45 9661.71 22-NOV-06:03 -3.3
December 15870535.51 11471.57 18-DEC-06:01 -5.0
         
Annual Sum or Average 0.550075E+09      
Minimum of Months 0.00 0.00   -5.1
Maximum of Months 0.382286E+09 12406.30   25.13



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.258112E+09 9609.98 09-JAN-05:01 -2.2
February 93308130.06 9587.41 13-FEB-05:01 -5.1
March 30105.67 250.88 23-MAR-05:06 6.10
April 0.00 0.00 01-APR-00:10 12.05
May 0.00 0.00 01-MAY-00:03 16.68
June 0.00 0.00 01-JUN-00:10 20.93
July 0.00 0.00 01-JUL-00:10 22.28
August 0.00 0.00 01-AUG-00:03 25.13
September 0.00 0.00 01-SEP-00:03 21.40
October 0.00 0.00 01-OCT-00:10 16.85
November 6661116.87 8469.88 21-NOV-06:01 -2.8
December 26154761.60 8752.38 18-DEC-06:01 -5.0
         
Annual Sum or Average 0.384266E+09      
Minimum of Months 0.00 0.00   -5.1
Maximum of Months 0.258112E+09 9609.98   25.13



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.443545E+09 15051.90 09-JAN-04:17 -1.9
February 0.174431E+09 14392.46 13-FEB-05:01 -5.1
March 6546.26 54.55 23-MAR-05:06 6.10
April 0.00 0.00 01-APR-00:10 12.05
May 0.00 0.00 01-MAY-00:03 16.68
June 0.00 0.00 01-JUN-00:10 20.93
July 0.00 0.00 01-JUL-00:10 22.28
August 0.00 0.00 01-AUG-00:03 25.13
September 0.00 0.00 01-SEP-00:03 21.40
October 0.00 0.00 01-OCT-00:10 16.85
November 12122811.15 12979.65 21-NOV-06:01 -2.8
December 53413591.95 13308.13 18-DEC-06:01 -5.0
         
Annual Sum or Average 0.683519E+09      
Minimum of Months 0.00 0.00   -5.1
Maximum of Months 0.443545E+09 15051.90   25.13



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 48157805.05 6766.48 09-JAN-05:01 -2.2
February 7067877.89 6169.60 13-FEB-06:01 -5.6
March 0.00 0.00 01-MAR-00:10 15.32
April 0.00 0.00 01-APR-00:10 12.05
May 0.00 0.00 01-MAY-00:03 16.68
June 0.00 0.00 01-JUN-00:10 20.93
July 0.00 0.00 01-JUL-00:10 22.28
August 0.00 0.00 01-AUG-00:03 25.13
September 0.00 0.00 01-SEP-00:03 21.40
October 0.00 0.00 01-OCT-00:10 16.85
November 0.00 0.00 01-NOV-00:10 9.70
December 0.00 0.00 01-DEC-00:10 1.80
         
Annual Sum or Average 55225682.94      
Minimum of Months 0.00 0.00   -5.6
Maximum of Months 48157805.05 6766.48   25.13



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.387035E+10 14702.25 09-JAN-04:11 -1.9
February 0.220885E+10 15008.71 12-FEB-06:01 -12.3
March 0.155565E+09 12307.16 22-MAR-04:11 6.50
April 35157692.42 11521.66 07-APR-05:02 3.22
May 0.00 0.00 01-MAY-00:03 16.68
June 0.00 0.00 01-JUN-00:10 20.93
July 0.00 0.00 01-JUL-00:10 22.28
August 0.00 0.00 01-AUG-00:03 25.13
September 0.00 0.00 01-SEP-00:03 21.40
October 41774021.27 12142.07 26-OCT-04:11 2.60
November 0.416088E+09 13171.01 21-NOV-05:01 -2.3
December 0.156305E+10 14379.15 18-DEC-04:01 -4.1
         
Annual Sum or Average 0.829083E+10      
Minimum of Months 0.00 0.00   -12.3
Maximum of Months 0.387035E+10 15008.71   25.13



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.209554E+10 15468.92 09-JAN-04:11 -1.9
February 0.113367E+10 15805.76 12-FEB-06:01 -12.3
March 79077133.15 12844.23 22-MAR-04:11 6.50
April 14766246.24 8958.08 06-APR-05:03 0.18
May 0.00 0.00 01-MAY-00:03 16.68
June 0.00 0.00 01-JUN-00:10 20.93
July 0.00 0.00 01-JUL-00:10 22.28
August 0.00 0.00 01-AUG-00:03 25.13
September 0.00 0.00 01-SEP-00:03 21.40
October 29378820.60 12540.09 26-OCT-04:11 2.60
November 0.189605E+09 13718.57 21-NOV-05:01 -2.3
December 0.772670E+09 14838.18 18-DEC-04:01 -4.1
         
Annual Sum or Average 0.431471E+10      
Minimum of Months 0.00 0.00   -12.3
Maximum of Months 0.209554E+10 15805.76   25.13



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.201922E+10 17242.35 09-JAN-04:11 -1.9
February 0.108971E+10 17545.08 12-FEB-06:01 -12.3
March 64032674.75 14384.78 22-MAR-04:11 6.50
April 17671139.75 13377.88 06-APR-05:03 0.18
May 0.00 0.00 01-MAY-00:03 16.68
June 0.00 0.00 01-JUN-00:10 20.93
July 0.00 0.00 01-JUL-00:10 22.28
August 0.00 0.00 01-AUG-00:03 25.13
September 0.00 0.00 01-SEP-00:03 21.40
October 24189368.68 13011.09 26-OCT-05:03 2.20
November 0.150938E+09 15206.17 21-NOV-05:01 -2.3
December 0.711073E+09 16422.15 26-DEC-05:11 3.70
         
Annual Sum or Average 0.407684E+10      
Minimum of Months 0.00 0.00   -12.3
Maximum of Months 0.201922E+10 17545.08   25.13



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.162149E+10 15515.32 09-JAN-04:11 -1.9
February 0.845812E+09 15803.06 12-FEB-06:01 -12.3
March 33910279.57 12511.53 22-MAR-04:11 6.50
April 6059584.44 8398.71 06-APR-05:03 0.18
May 0.00 0.00 01-MAY-00:03 16.68
June 0.00 0.00 01-JUN-00:10 20.93
July 0.00 0.00 01-JUL-00:10 22.28
August 0.00 0.00 01-AUG-00:03 25.13
September 0.00 0.00 01-SEP-00:03 21.40
October 12620500.97 8538.35 26-OCT-05:03 2.20
November 0.150554E+09 13613.57 21-NOV-05:01 -2.3
December 0.582843E+09 14366.53 18-DEC-04:01 -4.1
         
Annual Sum or Average 0.325329E+10      
Minimum of Months 0.00 0.00   -12.3
Maximum of Months 0.162149E+10 15803.06   25.13



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.769809E+10 17010.98 09-JAN-00:53 -0.6
February 0.447614E+10 17449.59 12-FEB-00:02 -9.5
March 0.752740E+09 15040.51 20-MAR-04:11 6.13
April 0.210769E+09 14667.46 06-APR-04:01 0.92
May 2789552.07 8432.97 11-MAY-05:02 8.22
June 0.00 0.00 01-JUN-00:10 20.93
July 0.00 0.00 01-JUL-00:10 22.28
August 0.00 0.00 01-AUG-00:03 25.13
September 0.00 0.00 01-SEP-00:03 21.40
October 0.349743E+09 14958.68 26-OCT-04:11 2.60
November 0.152036E+10 16195.55 21-NOV-04:01 -1.8
December 0.437222E+10 16957.74 17-DEC-08:62 -2.1
         
Annual Sum or Average 0.193828E+11      
Minimum of Months 0.00 0.00   -9.5
Maximum of Months 0.769809E+10 17449.59   25.13



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.411756E+10 17120.37 09-JAN-04:11 -1.9
February 0.232788E+10 17540.01 12-FEB-06:01 -12.3
March 0.361293E+09 15145.34 22-MAR-04:11 6.50
April 90010849.41 14642.04 06-APR-04:01 0.92
May 1082154.92 3707.65 11-MAY-05:02 8.22
June 0.00 0.00 01-JUN-00:10 20.93
July 0.00 0.00 01-JUL-00:10 22.28
August 0.00 0.00 01-AUG-00:03 25.13
September 91477.45 762.31 29-SEP-05:02 12.30
October 0.199540E+09 15054.92 26-OCT-04:11 2.60
November 0.710441E+09 16285.01 21-NOV-04:01 -1.8
December 0.218384E+10 16872.46 18-DEC-04:01 -4.1
         
Annual Sum or Average 0.999173E+10      
Minimum of Months 0.00 0.00   -12.3
Maximum of Months 0.411756E+10 17540.01   25.13



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.452307E+10 19453.44 09-JAN-04:11 -1.9
February 0.262906E+10 19885.85 12-FEB-06:01 -12.3
March 0.431800E+09 17036.22 22-MAR-04:11 6.50
April 0.147455E+09 16471.10 06-APR-04:01 0.92
May 866725.27 3754.40 11-MAY-05:02 8.22
June 0.00 0.00 01-JUN-00:10 20.93
July 0.00 0.00 01-JUL-00:10 22.28
August 0.00 0.00 01-AUG-00:03 25.13
September 0.00 0.00 01-SEP-00:03 21.40
October 0.212399E+09 16546.75 30-OCT-04:11 8.90
November 0.751469E+09 18350.19 21-NOV-04:01 -1.8
December 0.228406E+10 19068.31 26-DEC-05:11 3.70
         
Annual Sum or Average 0.109802E+11      
Minimum of Months 0.00 0.00   -12.3
Maximum of Months 0.452307E+10 19885.85   25.13



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.355444E+10 18596.86 09-JAN-04:11 -1.9
February 0.188030E+10 18938.02 12-FEB-06:01 -12.3
March 0.224976E+09 15919.90 22-MAR-04:11 6.50
April 64634545.69 15382.49 06-APR-04:01 0.92
May 0.00 0.00 01-MAY-00:03 16.68
June 0.00 0.00 01-JUN-00:10 20.93
July 0.00 0.00 01-JUL-00:10 22.28
August 0.00 0.00 01-AUG-00:03 25.13
September 8368.66 69.74 29-SEP-05:04 12.30
October 0.106415E+09 15615.87 26-OCT-04:11 2.60
November 0.596058E+09 17513.42 22-NOV-04:11 -2.8
December 0.167740E+10 18188.24 18-DEC-04:01 -4.1
         
Annual Sum or Average 0.810423E+10      
Minimum of Months 0.00 0.00   -12.3
Maximum of Months 0.355444E+10 18938.02   25.13



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: GROUNDFLOOR_PLENUM

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.359083E+09 10879.37 19-JAN-06:02 12.30
February 0.243663E+09 11522.57 08-FEB-06:02 7.38
March 68523440.76 10910.95 22-MAR-04:11 6.50
April 74348451.47 10215.66 04-APR-04:12 15.60
May 37679064.37 9364.57 01-MAY-04:12 16.10
June 45672135.53 7329.53 16-JUN-04:11 20.60
July 53219837.64 8391.96 28-JUL-04:11 19.40
August 42288011.00 7218.34 06-AUG-16:21 32.50
September 38653522.34 8158.97 01-SEP-04:11 20.93
October 67179024.45 10361.26 02-OCT-04:12 18.70
November 75688621.38 11913.11 24-NOV-05:11 8.90
December 71731238.02 14265.09 26-DEC-05:11 3.70
         
Annual Sum or Average 0.117773E+10      
Minimum of Months 37679064.37 7218.34   3.70
Maximum of Months 0.359083E+09 14265.09   32.50



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: MIDFLOOR_PLENUM

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.243694E+10 14037.60 06-JAN-12:00 -2.2
February 0.125885E+10 10087.43 13-FEB-06:07 -5.6
March 0.117278E+09 6751.98 28-MAR-05:03 16.02
April 29204226.44 7313.52 03-APR-05:02 17.75
May 30629161.43 5343.29 15-MAY-05:02 12.30
June 24678377.65 6156.10 25-JUN-16:11 33.13
July 30684512.61 5247.85 31-JUL-04:11 20.93
August 29374800.90 5250.51 06-AUG-16:21 32.50
September 26520228.93 5593.79 27-SEP-04:11 22.80
October 70043621.94 6776.48 24-OCT-05:02 11.02
November 0.183354E+09 7033.66 02-NOV-05:02 13.90
December 0.963146E+09 5829.91 10-DEC-13:43 16.52
         
Annual Sum or Average 0.520070E+10      
Minimum of Months 24678377.65 5247.85   -5.6
Maximum of Months 0.243694E+10 14037.60   33.13



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: TOPFLOOR_PLENUM

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.877517E+10 25122.57 09-JAN-05:09 -2.2
February 0.518052E+10 26966.89 13-FEB-05:09 -5.1
March 0.136885E+10 11891.68 31-MAR-05:02 16.78
April 0.625163E+09 14383.00 14-APR-05:03 12.62
May 0.150173E+09 13309.49 15-MAY-05:02 12.30
June 68246777.31 15614.32 08-JUN-05:03 11.70
July 38149936.84 10446.65 05-JUL-04:12 22.03
August 36381133.85 9157.67 28-AUG-04:12 21.30
September 0.121046E+09 14699.36 14-SEP-05:03 12.20
October 0.985293E+09 14675.51 03-OCT-05:03 11.60
November 0.219461E+10 16999.57 22-NOV-06:03 -3.3
December 0.518242E+10 25485.72 18-DEC-05:33 -5.0
         
Annual Sum or Average 0.247260E+11      
Minimum of Months 36381133.85 9157.67   -5.1
Maximum of Months 0.877517E+10 26966.89   22.03



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:05 5.70
February 0.00 0.00 01-FEB-00:10 9.92
March 0.00 0.00 01-MAR-00:10 15.32
April 0.00 0.00 01-APR-00:10 12.05
May 0.00 0.00 01-MAY-00:03 16.68
June 0.00 0.00 01-JUN-00:10 20.93
July 0.00 0.00 01-JUL-00:10 22.28
August 0.00 0.00 01-AUG-00:03 25.13
September 0.00 0.00 01-SEP-00:03 21.40
October 0.00 0.00 01-OCT-00:10 16.85
November 0.00 0.00 01-NOV-00:10 9.70
December 0.00 0.00 01-DEC-00:10 1.80
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   1.80
Maximum of Months 0.00 0.00   25.13



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: DATACENTER_MID_ZN_6

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.416005E+09 547.37 16-JAN-03:20 -1.7
February 0.00 0.00 01-FEB-00:10 9.92
March 0.00 0.00 01-MAR-00:10 15.32
April 0.00 0.00 01-APR-00:10 12.05
May 0.00 0.00 01-MAY-00:03 16.68
June 0.00 0.00 01-JUN-00:10 20.93
July 0.00 0.00 01-JUL-00:10 22.28
August 0.00 0.00 01-AUG-00:03 25.13
September 0.00 0.00 01-SEP-00:03 21.40
October 0.00 0.00 01-OCT-00:10 16.85
November 0.00 0.00 01-NOV-00:10 9.70
December 0.00 0.00 01-DEC-00:10 1.80
         
Annual Sum or Average 0.416005E+09      
Minimum of Months 0.00 0.00   -1.7
Maximum of Months 0.416005E+09 547.37   25.13



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.697636E+09 601.45 15-JAN-18:45 4.18
February 67707861.03 548.27 12-FEB-07:45 -12.3
March 0.00 0.00 01-MAR-00:10 15.32
April 0.00 0.00 01-APR-00:10 12.05
May 0.00 0.00 01-MAY-00:03 16.68
June 0.00 0.00 01-JUN-00:10 20.93
July 0.00 0.00 01-JUL-00:10 22.28
August 0.00 0.00 01-AUG-00:03 25.13
September 0.00 0.00 01-SEP-00:03 21.40
October 0.00 0.00 01-OCT-00:10 16.85
November 0.00 0.00 01-NOV-00:10 9.70
December 0.00 0.00 01-DEC-00:10 1.80
         
Annual Sum or Average 0.765344E+09      
Minimum of Months 0.00 0.00   -12.3
Maximum of Months 0.697636E+09 601.45   25.13



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:05 5.70
February 0.00 0.00 01-FEB-00:10 9.92
March 0.00 0.00 01-MAR-00:10 15.32
April 0.00 0.00 01-APR-00:10 12.05
May 0.00 0.00 01-MAY-00:03 16.68
June 0.00 0.00 01-JUN-00:10 20.93
July 0.00 0.00 01-JUL-00:10 22.28
August 0.00 0.00 01-AUG-00:03 25.13
September 0.00 0.00 01-SEP-00:03 21.40
October 0.00 0.00 01-OCT-00:10 16.85
November 0.00 0.00 01-NOV-00:10 9.70
December 0.00 0.00 01-DEC-00:10 1.80
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   1.80
Maximum of Months 0.00 0.00   25.13



Table of Contents

Report: ZoneElectricSummaryMonthly

For: BASEMENT

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.219312E+11 22950.34 02-JAN-08:09 0.360447E+11 13457.54 01-JAN-00:10
February 0.198933E+11 22950.34 01-FEB-08:09 0.325565E+11 13457.54 01-FEB-00:10
March 0.236388E+11 22950.34 01-MAR-08:09 0.360447E+11 13457.54 01-MAR-00:10
April 0.211142E+11 22950.34 03-APR-07:10 0.348820E+11 13457.54 01-APR-00:10
May 0.227850E+11 22950.34 01-MAY-07:10 0.360447E+11 13457.54 01-MAY-00:10
June 0.226748E+11 22950.34 01-JUN-07:10 0.348820E+11 13457.54 01-JUN-00:10
July 0.212244E+11 22950.34 03-JUL-07:10 0.360447E+11 13457.54 01-JUL-00:10
August 0.236388E+11 22950.34 01-AUG-07:10 0.360447E+11 13457.54 01-AUG-00:10
September 0.211142E+11 22950.34 01-SEP-07:10 0.348820E+11 13457.54 01-SEP-00:10
October 0.219312E+11 22950.34 02-OCT-07:10 0.360447E+11 13457.54 01-OCT-00:10
November 0.216742E+11 22950.34 01-NOV-07:10 0.348820E+11 13457.54 01-NOV-00:10
December 0.212244E+11 22950.34 01-DEC-08:09 0.360447E+11 13457.54 01-DEC-00:10
             
Annual Sum or Average 0.262844E+12     0.424397E+12    
Minimum of Months 0.198933E+11 22950.34   0.325565E+11 13457.54  
Maximum of Months 0.236388E+11 22950.34   0.360447E+11 13457.54  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: CORE_BOTTOM

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.196958E+11 20611.01 02-JAN-08:09 0.243681E+11 17206.63 02-JAN-08:09
February 0.178655E+11 20611.01 01-FEB-08:09 0.220609E+11 17206.63 01-FEB-08:09
March 0.212293E+11 20611.01 01-MAR-08:09 0.253549E+11 17206.63 01-MAR-08:09
April 0.189620E+11 20611.01 03-APR-07:10 0.235306E+11 17206.63 03-APR-07:10
May 0.204625E+11 20611.01 01-MAY-07:10 0.248615E+11 17206.63 01-MAY-07:10
June 0.203636E+11 20611.01 01-JUN-07:10 0.244160E+11 17206.63 01-JUN-07:10
July 0.190610E+11 20611.01 03-JUL-07:10 0.239708E+11 17206.63 03-JUL-07:10
August 0.212293E+11 20611.01 01-AUG-07:10 0.253549E+11 17206.63 01-AUG-07:10
September 0.189620E+11 20611.01 01-SEP-07:10 0.235199E+11 17206.63 01-SEP-07:10
October 0.196958E+11 20611.01 02-OCT-07:10 0.243735E+11 17206.63 02-OCT-07:10
November 0.194649E+11 20611.01 01-NOV-07:10 0.238373E+11 17206.63 01-NOV-07:10
December 0.190610E+11 20611.01 01-DEC-08:09 0.239654E+11 17206.63 01-DEC-08:09
             
Annual Sum or Average 0.236053E+12     0.289614E+12    
Minimum of Months 0.178655E+11 20611.01   0.220609E+11 17206.63  
Maximum of Months 0.212293E+11 20611.01   0.253549E+11 17206.63  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: CORE_MID

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.196958E+11 20611.01 02-JAN-08:09 0.243680E+11 17206.56 02-JAN-08:09
February 0.178655E+11 20611.01 01-FEB-08:09 0.220609E+11 17206.56 01-FEB-08:09
March 0.212293E+11 20611.01 01-MAR-08:09 0.253548E+11 17206.56 01-MAR-08:09
April 0.189620E+11 20611.01 03-APR-07:10 0.235305E+11 17206.56 03-APR-07:10
May 0.204625E+11 20611.01 01-MAY-07:10 0.248614E+11 17206.56 01-MAY-07:10
June 0.203636E+11 20611.01 01-JUN-07:10 0.244159E+11 17206.56 01-JUN-07:10
July 0.190610E+11 20611.01 03-JUL-07:10 0.239707E+11 17206.56 03-JUL-07:10
August 0.212293E+11 20611.01 01-AUG-07:10 0.253548E+11 17206.56 01-AUG-07:10
September 0.189620E+11 20611.01 01-SEP-07:10 0.235198E+11 17206.56 01-SEP-07:10
October 0.196958E+11 20611.01 02-OCT-07:10 0.243734E+11 17206.56 02-OCT-07:10
November 0.194649E+11 20611.01 01-NOV-07:10 0.238372E+11 17206.56 01-NOV-07:10
December 0.190610E+11 20611.01 01-DEC-08:09 0.239653E+11 17206.56 01-DEC-08:09
             
Annual Sum or Average 0.236053E+12     0.289613E+12    
Minimum of Months 0.178655E+11 20611.01   0.220609E+11 17206.56  
Maximum of Months 0.212293E+11 20611.01   0.253548E+11 17206.56  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: CORE_TOP

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.196958E+11 20611.01 02-JAN-08:09 0.243680E+11 17206.56 02-JAN-08:09
February 0.178655E+11 20611.01 01-FEB-08:09 0.220609E+11 17206.56 01-FEB-08:09
March 0.212293E+11 20611.01 01-MAR-08:09 0.253548E+11 17206.56 01-MAR-08:09
April 0.189620E+11 20611.01 03-APR-07:10 0.235305E+11 17206.56 03-APR-07:10
May 0.204625E+11 20611.01 01-MAY-07:10 0.248614E+11 17206.56 01-MAY-07:10
June 0.203636E+11 20611.01 01-JUN-07:10 0.244159E+11 17206.56 01-JUN-07:10
July 0.190610E+11 20611.01 03-JUL-07:10 0.239707E+11 17206.56 03-JUL-07:10
August 0.212293E+11 20611.01 01-AUG-07:10 0.253548E+11 17206.56 01-AUG-07:10
September 0.189620E+11 20611.01 01-SEP-07:10 0.235198E+11 17206.56 01-SEP-07:10
October 0.196958E+11 20611.01 02-OCT-07:10 0.243734E+11 17206.56 02-OCT-07:10
November 0.194649E+11 20611.01 01-NOV-07:10 0.238372E+11 17206.56 01-NOV-07:10
December 0.190610E+11 20611.01 01-DEC-08:09 0.239653E+11 17206.56 01-DEC-08:09
             
Annual Sum or Average 0.236053E+12     0.289613E+12    
Minimum of Months 0.178655E+11 20611.01   0.220609E+11 17206.56  
Maximum of Months 0.212293E+11 20611.01   0.253548E+11 17206.56  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.164519E+10 2587.92 03-JAN-08:09 0.305979E+10 2160.55 02-JAN-08:09
February 0.148700E+10 2587.92 01-FEB-08:09 0.277008E+10 2160.55 01-FEB-08:09
March 0.156487E+10 2587.92 21-MAR-07:10 0.318369E+10 2160.55 01-MAR-08:09
April 0.133785E+10 2255.20 03-APR-07:10 0.295462E+10 2160.55 03-APR-07:10
May 0.138865E+10 1470.28 02-MAY-07:10 0.312174E+10 2160.55 01-MAY-07:10
June 0.136362E+10 1470.28 23-JUN-07:10 0.306580E+10 2160.55 01-JUN-07:10
July 0.129798E+10 1803.00 27-JUL-07:10 0.300989E+10 2160.55 03-JUL-07:10
August 0.147313E+10 2255.20 24-AUG-07:10 0.318369E+10 2160.55 01-AUG-07:10
September 0.138990E+10 2587.92 29-SEP-07:10 0.295328E+10 2160.55 01-SEP-07:10
October 0.157657E+10 2587.92 19-OCT-07:10 0.306046E+10 2160.55 02-OCT-07:10
November 0.158302E+10 2587.92 01-NOV-07:10 0.299314E+10 2160.55 01-NOV-07:10
December 0.161015E+10 2587.92 06-DEC-08:09 0.300922E+10 2160.55 01-DEC-08:09
             
Annual Sum or Average 0.177179E+11     0.363654E+11    
Minimum of Months 0.129798E+10 1470.28   0.277008E+10 2160.55  
Maximum of Months 0.164519E+10 2587.92   0.318369E+10 2160.55  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.101471E+10 1667.75 03-JAN-08:09 0.197184E+10 1392.34 02-JAN-08:09
February 0.918555E+09 1667.75 01-FEB-08:09 0.178515E+10 1392.34 01-FEB-08:09
March 0.988585E+09 1667.75 21-MAR-07:10 0.205169E+10 1392.34 01-MAR-08:09
April 0.858042E+09 1453.34 03-APR-07:10 0.190407E+10 1392.34 03-APR-07:10
May 0.902214E+09 870.51 02-MAY-07:10 0.201177E+10 1392.34 01-MAY-07:10
June 0.886900E+09 793.52 01-JUN-07:10 0.197572E+10 1392.34 01-JUN-07:10
July 0.840993E+09 947.51 27-JUL-07:10 0.193969E+10 1392.34 03-JUL-07:10
August 0.949747E+09 1453.34 24-AUG-07:10 0.205169E+10 1392.34 01-AUG-07:10
September 0.880737E+09 1453.34 05-SEP-07:10 0.190321E+10 1392.34 01-SEP-07:10
October 0.969692E+09 1667.75 19-OCT-07:10 0.197228E+10 1392.34 02-OCT-07:10
November 0.989382E+09 1667.75 01-NOV-07:10 0.192889E+10 1392.34 01-NOV-07:10
December 0.988938E+09 1667.75 06-DEC-08:09 0.193926E+10 1392.34 01-DEC-08:09
             
Annual Sum or Average 0.111885E+11     0.234352E+11    
Minimum of Months 0.840993E+09 793.52   0.178515E+10 1392.34  
Maximum of Months 0.101471E+10 1667.75   0.205169E+10 1392.34  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.151610E+10 2587.98 03-JAN-08:09 0.305983E+10 2160.58 02-JAN-08:09
February 0.139430E+10 2587.98 01-FEB-08:09 0.277013E+10 2160.58 01-FEB-08:09
March 0.153556E+10 2587.98 21-MAR-07:10 0.318374E+10 2160.58 01-MAR-08:09
April 0.134267E+10 2255.25 03-APR-07:10 0.295467E+10 2160.58 03-APR-07:10
May 0.141061E+10 1803.04 24-MAY-07:10 0.312179E+10 2160.58 01-MAY-07:10
June 0.138612E+10 1470.31 23-JUN-07:10 0.306585E+10 2160.58 01-JUN-07:10
July 0.131813E+10 1803.04 27-JUL-07:10 0.300994E+10 2160.58 03-JUL-07:10
August 0.148201E+10 2255.25 24-AUG-07:10 0.318374E+10 2160.58 01-AUG-07:10
September 0.137226E+10 2587.98 29-SEP-07:10 0.295333E+10 2160.58 01-SEP-07:10
October 0.148633E+10 2587.98 19-OCT-07:10 0.306051E+10 2160.58 02-OCT-07:10
November 0.148340E+10 2587.98 01-NOV-07:10 0.299318E+10 2160.58 01-NOV-07:10
December 0.147188E+10 2587.98 06-DEC-08:09 0.300927E+10 2160.58 01-DEC-08:09
             
Annual Sum or Average 0.171994E+11     0.363660E+11    
Minimum of Months 0.131813E+10 1470.31   0.277013E+10 2160.58  
Maximum of Months 0.153556E+10 2587.98   0.318374E+10 2160.58  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.101481E+10 1667.75 03-JAN-08:09 0.197183E+10 1392.33 02-JAN-08:09
February 0.932742E+09 1667.75 01-FEB-08:09 0.178514E+10 1392.33 01-FEB-08:09
March 0.100688E+10 1667.75 16-MAR-07:10 0.205168E+10 1392.33 01-MAR-08:09
April 0.867027E+09 1453.34 03-APR-07:10 0.190406E+10 1392.33 03-APR-07:10
May 0.908560E+09 1453.34 24-MAY-07:10 0.201175E+10 1392.33 01-MAY-07:10
June 0.890974E+09 1161.92 23-JUN-07:10 0.197570E+10 1392.33 01-JUN-07:10
July 0.848381E+09 1453.34 27-JUL-07:10 0.193968E+10 1392.33 03-JUL-07:10
August 0.958468E+09 1453.34 23-AUG-07:10 0.205168E+10 1392.33 01-AUG-07:10
September 0.896243E+09 1667.75 29-SEP-07:10 0.190319E+10 1392.33 01-SEP-07:10
October 0.999383E+09 1667.75 13-OCT-07:10 0.197226E+10 1392.33 02-OCT-07:10
November 0.980521E+09 1667.75 01-NOV-07:10 0.192888E+10 1392.33 01-NOV-07:10
December 0.987375E+09 1667.75 06-DEC-08:09 0.193924E+10 1392.33 01-DEC-08:09
             
Annual Sum or Average 0.112914E+11     0.234351E+11    
Minimum of Months 0.848381E+09 1161.92   0.178514E+10 1392.33  
Maximum of Months 0.101481E+10 1667.75   0.205168E+10 1392.33  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.163281E+10 2587.92 03-JAN-08:09 0.305979E+10 2160.55 02-JAN-08:09
February 0.147900E+10 2587.92 01-FEB-08:09 0.277008E+10 2160.55 01-FEB-08:09
March 0.155941E+10 2587.92 21-MAR-07:10 0.318369E+10 2160.55 01-MAR-08:09
April 0.133433E+10 2255.20 03-APR-07:10 0.295462E+10 2160.55 03-APR-07:10
May 0.138700E+10 1470.28 02-MAY-07:10 0.312174E+10 2160.55 01-MAY-07:10
June 0.136191E+10 1470.28 23-JUN-07:10 0.306580E+10 2160.55 01-JUN-07:10
July 0.129625E+10 1803.00 27-JUL-07:10 0.300989E+10 2160.55 03-JUL-07:10
August 0.147090E+10 2255.20 24-AUG-07:10 0.318369E+10 2160.55 01-AUG-07:10
September 0.138412E+10 2587.92 29-SEP-07:10 0.295328E+10 2160.55 01-SEP-07:10
October 0.156565E+10 2587.92 19-OCT-07:10 0.306046E+10 2160.55 02-OCT-07:10
November 0.157391E+10 2587.92 01-NOV-07:10 0.299314E+10 2160.55 01-NOV-07:10
December 0.159810E+10 2587.92 06-DEC-08:09 0.300922E+10 2160.55 01-DEC-08:09
             
Annual Sum or Average 0.176434E+11     0.363654E+11    
Minimum of Months 0.129625E+10 1470.28   0.277008E+10 2160.55  
Maximum of Months 0.163281E+10 2587.92   0.318369E+10 2160.55  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.100989E+10 1667.75 03-JAN-08:09 0.197184E+10 1392.34 02-JAN-08:09
February 0.915334E+09 1667.75 01-FEB-08:09 0.178515E+10 1392.34 01-FEB-08:09
March 0.986649E+09 1667.75 21-MAR-07:10 0.205169E+10 1392.34 01-MAR-08:09
April 0.856622E+09 1453.34 03-APR-07:10 0.190407E+10 1392.34 03-APR-07:10
May 0.901322E+09 870.51 02-MAY-07:10 0.201177E+10 1392.34 01-MAY-07:10
June 0.886119E+09 793.52 01-JUN-07:10 0.197572E+10 1392.34 01-JUN-07:10
July 0.840347E+09 947.51 27-JUL-07:10 0.193969E+10 1392.34 03-JUL-07:10
August 0.948789E+09 1453.34 24-AUG-07:10 0.205169E+10 1392.34 01-AUG-07:10
September 0.879519E+09 1453.34 05-SEP-07:10 0.190321E+10 1392.34 01-SEP-07:10
October 0.966687E+09 1667.75 19-OCT-07:10 0.197228E+10 1392.34 02-OCT-07:10
November 0.985860E+09 1667.75 01-NOV-07:10 0.192889E+10 1392.34 01-NOV-07:10
December 0.986180E+09 1667.75 06-DEC-08:09 0.193926E+10 1392.34 01-DEC-08:09
             
Annual Sum or Average 0.111633E+11     0.234352E+11    
Minimum of Months 0.840347E+09 793.52   0.178515E+10 1392.34  
Maximum of Months 0.100989E+10 1667.75   0.205169E+10 1392.34  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.151467E+10 2587.98 03-JAN-08:09 0.305983E+10 2160.58 02-JAN-08:09
February 0.139281E+10 2587.98 01-FEB-08:09 0.277013E+10 2160.58 01-FEB-08:09
March 0.153305E+10 2587.98 21-MAR-07:10 0.318374E+10 2160.58 01-MAR-08:09
April 0.133946E+10 2255.25 03-APR-07:10 0.295467E+10 2160.58 03-APR-07:10
May 0.140845E+10 1803.04 24-MAY-07:10 0.312179E+10 2160.58 01-MAY-07:10
June 0.138378E+10 1470.31 23-JUN-07:10 0.306585E+10 2160.58 01-JUN-07:10
July 0.131584E+10 1803.04 27-JUL-07:10 0.300994E+10 2160.58 03-JUL-07:10
August 0.148015E+10 2255.25 24-AUG-07:10 0.318374E+10 2160.58 01-AUG-07:10
September 0.137019E+10 2587.98 29-SEP-07:10 0.295333E+10 2160.58 01-SEP-07:10
October 0.148476E+10 2587.98 19-OCT-07:10 0.306051E+10 2160.58 02-OCT-07:10
November 0.148021E+10 2587.98 01-NOV-07:10 0.299318E+10 2160.58 01-NOV-07:10
December 0.146964E+10 2587.98 06-DEC-08:09 0.300927E+10 2160.58 01-DEC-08:09
             
Annual Sum or Average 0.171730E+11     0.363660E+11    
Minimum of Months 0.131584E+10 1470.31   0.277013E+10 2160.58  
Maximum of Months 0.153305E+10 2587.98   0.318374E+10 2160.58  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.101166E+10 1667.75 03-JAN-08:09 0.197183E+10 1392.33 02-JAN-08:09
February 0.929254E+09 1667.75 01-FEB-08:09 0.178514E+10 1392.33 01-FEB-08:09
March 0.100366E+10 1667.75 16-MAR-07:10 0.205168E+10 1392.33 01-MAR-08:09
April 0.865094E+09 1453.34 03-APR-07:10 0.190406E+10 1392.33 03-APR-07:10
May 0.906387E+09 1453.34 24-MAY-07:19 0.201175E+10 1392.33 01-MAY-07:10
June 0.889258E+09 1161.92 23-JUN-07:10 0.197570E+10 1392.33 01-JUN-07:10
July 0.846935E+09 1453.34 27-JUL-07:10 0.193968E+10 1392.33 03-JUL-07:10
August 0.956355E+09 1453.34 23-AUG-07:10 0.205168E+10 1392.33 01-AUG-07:10
September 0.893970E+09 1667.75 29-SEP-07:10 0.190319E+10 1392.33 01-SEP-07:10
October 0.994877E+09 1667.75 13-OCT-07:10 0.197226E+10 1392.33 02-OCT-07:10
November 0.977743E+09 1667.75 01-NOV-07:10 0.192888E+10 1392.33 01-NOV-07:10
December 0.983433E+09 1667.75 06-DEC-08:09 0.193924E+10 1392.33 01-DEC-08:09
             
Annual Sum or Average 0.112586E+11     0.234351E+11    
Minimum of Months 0.846935E+09 1161.92   0.178514E+10 1392.33  
Maximum of Months 0.101166E+10 1667.75   0.205168E+10 1392.33  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.163253E+10 2587.92 03-JAN-08:09 0.305979E+10 2160.55 02-JAN-08:09
February 0.147861E+10 2587.92 01-FEB-08:09 0.277008E+10 2160.55 01-FEB-08:09
March 0.155915E+10 2587.92 21-MAR-07:10 0.318369E+10 2160.55 01-MAR-08:09
April 0.133425E+10 2255.20 03-APR-07:10 0.295462E+10 2160.55 03-APR-07:10
May 0.138683E+10 1470.28 02-MAY-07:10 0.312174E+10 2160.55 01-MAY-07:10
June 0.136189E+10 1470.28 23-JUN-07:10 0.306580E+10 2160.55 01-JUN-07:10
July 0.129621E+10 1803.00 27-JUL-07:10 0.300989E+10 2160.55 03-JUL-07:10
August 0.147061E+10 2255.20 24-AUG-07:10 0.318369E+10 2160.55 01-AUG-07:10
September 0.138411E+10 2587.92 29-SEP-07:10 0.295328E+10 2160.55 01-SEP-07:10
October 0.156494E+10 2587.92 19-OCT-07:10 0.306046E+10 2160.55 02-OCT-07:10
November 0.157323E+10 2587.92 01-NOV-07:10 0.299314E+10 2160.55 01-NOV-07:10
December 0.159788E+10 2587.92 06-DEC-08:09 0.300922E+10 2160.55 01-DEC-08:09
             
Annual Sum or Average 0.176402E+11     0.363654E+11    
Minimum of Months 0.129621E+10 1470.28   0.277008E+10 2160.55  
Maximum of Months 0.163253E+10 2587.92   0.318369E+10 2160.55  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.100985E+10 1667.75 03-JAN-08:09 0.197184E+10 1392.34 02-JAN-08:09
February 0.914948E+09 1667.75 01-FEB-08:09 0.178515E+10 1392.34 01-FEB-08:09
March 0.986409E+09 1667.75 21-MAR-07:10 0.205169E+10 1392.34 01-MAR-08:09
April 0.856592E+09 1453.34 03-APR-07:10 0.190407E+10 1392.34 03-APR-07:10
May 0.901263E+09 870.51 02-MAY-07:10 0.201177E+10 1392.34 01-MAY-07:10
June 0.886119E+09 793.52 01-JUN-07:10 0.197572E+10 1392.34 01-JUN-07:10
July 0.840205E+09 947.51 27-JUL-07:10 0.193969E+10 1392.34 03-JUL-07:10
August 0.948730E+09 1453.34 24-AUG-07:10 0.205169E+10 1392.34 01-AUG-07:10
September 0.879472E+09 1453.34 05-SEP-07:10 0.190321E+10 1392.34 01-SEP-07:10
October 0.966567E+09 1667.75 19-OCT-07:10 0.197228E+10 1392.34 02-OCT-07:10
November 0.985765E+09 1667.75 01-NOV-07:10 0.192889E+10 1392.34 01-NOV-07:10
December 0.986046E+09 1667.75 06-DEC-08:09 0.193926E+10 1392.34 01-DEC-08:09
             
Annual Sum or Average 0.111620E+11     0.234352E+11    
Minimum of Months 0.840205E+09 793.52   0.178515E+10 1392.34  
Maximum of Months 0.100985E+10 1667.75   0.205169E+10 1392.34  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.151449E+10 2587.98 03-JAN-08:09 0.305983E+10 2160.58 02-JAN-08:09
February 0.139239E+10 2587.98 01-FEB-08:09 0.277013E+10 2160.58 01-FEB-08:09
March 0.153277E+10 2587.98 21-MAR-07:10 0.318374E+10 2160.58 01-MAR-08:09
April 0.133924E+10 2255.25 03-APR-07:10 0.295467E+10 2160.58 03-APR-07:10
May 0.140845E+10 1803.04 24-MAY-07:10 0.312179E+10 2160.58 01-MAY-07:10
June 0.138356E+10 1470.31 23-JUN-07:10 0.306585E+10 2160.58 01-JUN-07:10
July 0.131564E+10 1803.04 27-JUL-07:10 0.300994E+10 2160.58 03-JUL-07:10
August 0.148013E+10 2255.25 24-AUG-07:10 0.318374E+10 2160.58 01-AUG-07:10
September 0.137003E+10 2587.98 29-SEP-07:10 0.295333E+10 2160.58 01-SEP-07:10
October 0.148469E+10 2587.98 19-OCT-07:10 0.306051E+10 2160.58 02-OCT-07:10
November 0.148007E+10 2587.98 01-NOV-07:10 0.299318E+10 2160.58 01-NOV-07:10
December 0.146956E+10 2587.98 06-DEC-08:09 0.300927E+10 2160.58 01-DEC-08:09
             
Annual Sum or Average 0.171710E+11     0.363660E+11    
Minimum of Months 0.131564E+10 1470.31   0.277013E+10 2160.58  
Maximum of Months 0.153277E+10 2587.98   0.318374E+10 2160.58  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.101165E+10 1667.75 03-JAN-08:09 0.197183E+10 1392.33 02-JAN-08:09
February 0.929159E+09 1667.75 01-FEB-08:09 0.178514E+10 1392.33 01-FEB-08:09
March 0.100346E+10 1667.75 16-MAR-07:10 0.205168E+10 1392.33 01-MAR-08:09
April 0.865048E+09 1453.34 03-APR-07:10 0.190406E+10 1392.33 03-APR-07:10
May 0.906497E+09 1453.34 24-MAY-07:19 0.201175E+10 1392.33 01-MAY-07:10
June 0.889166E+09 1161.92 23-JUN-07:10 0.197570E+10 1392.33 01-JUN-07:10
July 0.846873E+09 1453.34 27-JUL-07:10 0.193968E+10 1392.33 03-JUL-07:10
August 0.956181E+09 1453.34 23-AUG-07:10 0.205168E+10 1392.33 01-AUG-07:10
September 0.893967E+09 1667.75 29-SEP-07:10 0.190319E+10 1392.33 01-SEP-07:10
October 0.994527E+09 1667.75 13-OCT-07:10 0.197226E+10 1392.33 02-OCT-07:10
November 0.977696E+09 1667.75 01-NOV-07:10 0.192888E+10 1392.33 01-NOV-07:10
December 0.983336E+09 1667.75 06-DEC-08:09 0.193924E+10 1392.33 01-DEC-08:09
             
Annual Sum or Average 0.112576E+11     0.234351E+11    
Minimum of Months 0.846873E+09 1161.92   0.178514E+10 1392.33  
Maximum of Months 0.101165E+10 1667.75   0.205168E+10 1392.33  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.553024E+09 578.72 02-JAN-08:09 0.521915E+10 1948.61 01-JAN-00:10
February 0.501634E+09 578.72 01-FEB-08:09 0.942813E+10 3897.21 01-FEB-00:10
March 0.596080E+09 578.72 01-MAR-08:09 0.156645E+11 7794.42 31-MAR-23:10
April 0.532421E+09 578.72 03-APR-07:10 0.201821E+11 7794.42 01-APR-00:10
May 0.574552E+09 578.72 01-MAY-07:10 0.522616E+10 3897.21 31-MAY-23:10
June 0.571774E+09 578.72 01-JUN-07:10 0.101086E+11 5845.82 30-JUN-23:10
July 0.535199E+09 578.72 03-JUL-07:10 0.156645E+11 7794.42 31-JUL-23:10
August 0.596080E+09 578.72 01-AUG-07:10 0.208555E+11 7794.42 01-AUG-00:10
September 0.532421E+09 578.72 01-SEP-07:10 0.505780E+10 3897.21 30-SEP-23:10
October 0.553024E+09 578.72 02-OCT-07:10 0.104453E+11 5845.82 31-OCT-23:10
November 0.546542E+09 578.72 01-NOV-07:10 0.151524E+11 5845.82 01-NOV-00:10
December 0.535199E+09 578.72 01-DEC-08:09 0.208766E+11 7794.42 01-DEC-00:10
             
Annual Sum or Average 0.662795E+10     0.153881E+12    
Minimum of Months 0.501634E+09 578.72   0.505780E+10 1948.61  
Maximum of Months 0.596080E+09 578.72   0.208766E+11 7794.42  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: DATACENTER_MID_ZN_6

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.553024E+09 578.72 02-JAN-08:09 0.521915E+10 1948.61 01-JAN-00:10
February 0.501634E+09 578.72 01-FEB-08:09 0.942813E+10 3897.21 01-FEB-00:10
March 0.596080E+09 578.72 01-MAR-08:09 0.156645E+11 7794.42 31-MAR-23:10
April 0.532421E+09 578.72 03-APR-07:10 0.201821E+11 7794.42 01-APR-00:10
May 0.574552E+09 578.72 01-MAY-07:10 0.522616E+10 3897.21 31-MAY-23:10
June 0.571774E+09 578.72 01-JUN-07:10 0.101086E+11 5845.82 30-JUN-23:10
July 0.535199E+09 578.72 03-JUL-07:10 0.156645E+11 7794.42 31-JUL-23:10
August 0.596080E+09 578.72 01-AUG-07:10 0.208555E+11 7794.42 01-AUG-00:10
September 0.532421E+09 578.72 01-SEP-07:10 0.505780E+10 3897.21 30-SEP-23:10
October 0.553024E+09 578.72 02-OCT-07:10 0.104453E+11 5845.82 31-OCT-23:10
November 0.546542E+09 578.72 01-NOV-07:10 0.151524E+11 5845.82 01-NOV-00:10
December 0.535199E+09 578.72 01-DEC-08:09 0.208766E+11 7794.42 01-DEC-00:10
             
Annual Sum or Average 0.662795E+10     0.153881E+12    
Minimum of Months 0.501634E+09 578.72   0.505780E+10 1948.61  
Maximum of Months 0.596080E+09 578.72   0.208766E+11 7794.42  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.553024E+09 578.72 02-JAN-08:09 0.521915E+10 1948.61 01-JAN-00:10
February 0.501634E+09 578.72 01-FEB-08:09 0.942813E+10 3897.21 01-FEB-00:10
March 0.596080E+09 578.72 01-MAR-08:09 0.156645E+11 7794.42 31-MAR-23:10
April 0.532421E+09 578.72 03-APR-07:10 0.201821E+11 7794.42 01-APR-00:10
May 0.574552E+09 578.72 01-MAY-07:10 0.522616E+10 3897.21 31-MAY-23:10
June 0.571774E+09 578.72 01-JUN-07:10 0.101086E+11 5845.82 30-JUN-23:10
July 0.535199E+09 578.72 03-JUL-07:10 0.156645E+11 7794.42 31-JUL-23:10
August 0.596080E+09 578.72 01-AUG-07:10 0.208555E+11 7794.42 01-AUG-00:10
September 0.532421E+09 578.72 01-SEP-07:10 0.505780E+10 3897.21 30-SEP-23:10
October 0.553024E+09 578.72 02-OCT-07:10 0.104453E+11 5845.82 31-OCT-23:10
November 0.546542E+09 578.72 01-NOV-07:10 0.151524E+11 5845.82 01-NOV-00:10
December 0.535199E+09 578.72 01-DEC-08:09 0.208766E+11 7794.42 01-DEC-00:10
             
Annual Sum or Average 0.662795E+10     0.153881E+12    
Minimum of Months 0.501634E+09 578.72   0.505780E+10 1948.61  
Maximum of Months 0.596080E+09 578.72   0.208766E+11 7794.42  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.618367E+10 6471.01 02-JAN-08:09 0.254202E+12 94908.13 01-JAN-00:10
February 0.560905E+10 6471.01 01-FEB-08:09 0.459203E+12 189816.26 01-FEB-00:10
March 0.666512E+10 6471.01 01-MAR-08:09 0.762947E+12 379632.52 31-MAR-23:10
April 0.595330E+10 6471.01 03-APR-07:10 0.982982E+12 379632.52 01-APR-00:10
May 0.642439E+10 6471.01 01-MAY-07:10 0.254544E+12 189816.26 31-MAY-23:10
June 0.639333E+10 6471.01 01-JUN-07:10 0.492345E+12 284724.39 30-JUN-23:10
July 0.598436E+10 6471.01 03-JUL-07:10 0.762947E+12 379632.52 31-JUL-23:10
August 0.666512E+10 6471.01 01-AUG-07:10 0.101578E+13 379632.52 01-AUG-00:10
September 0.595330E+10 6471.01 01-SEP-07:10 0.246344E+12 189816.26 30-SEP-23:10
October 0.618367E+10 6471.01 02-OCT-07:10 0.508746E+12 284724.39 31-OCT-23:10
November 0.611120E+10 6471.01 01-NOV-07:10 0.738006E+12 284724.39 01-NOV-00:10
December 0.598436E+10 6471.01 01-DEC-08:09 0.101681E+13 379632.52 01-DEC-00:10
             
Annual Sum or Average 0.741109E+11     0.749486E+13    
Minimum of Months 0.560905E+10 6471.01   0.246344E+12 94908.13  
Maximum of Months 0.666512E+10 6471.01   0.101681E+13 379632.52  



Table of Contents

Report: SpaceGainsMonthly

For: BASEMENT

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.133902E+11 0.219312E+11 0.360447E+11 0.00 0.00 0.00 0.00 0.00 0.00
February 0.121482E+11 0.198933E+11 0.325565E+11 0.00 0.00 0.00 0.00 0.00 0.00
March 0.145160E+11 0.236388E+11 0.360447E+11 0.00 0.00 0.00 0.00 0.00 0.00
April 0.128805E+11 0.211142E+11 0.348820E+11 0.00 0.00 0.00 0.00 0.00 0.00
May 0.139531E+11 0.227850E+11 0.360447E+11 0.00 0.00 0.00 0.00 0.00 0.00
June 0.139143E+11 0.226748E+11 0.348820E+11 0.00 0.00 0.00 0.00 0.00 0.00
July 0.129193E+11 0.212244E+11 0.360447E+11 0.00 0.00 0.00 0.00 0.00 0.00
August 0.145160E+11 0.236388E+11 0.360447E+11 0.00 0.00 0.00 0.00 0.00 0.00
September 0.128805E+11 0.211142E+11 0.348820E+11 0.00 0.00 0.00 0.00 0.00 0.00
October 0.133902E+11 0.219312E+11 0.360447E+11 0.00 0.00 0.00 0.00 0.00 0.00
November 0.132595E+11 0.216742E+11 0.348820E+11 0.00 0.00 0.00 0.00 0.00 0.00
December 0.129193E+11 0.212244E+11 0.360447E+11 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.160687E+12 0.262844E+12 0.424397E+12 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.121482E+11 0.198933E+11 0.325565E+11 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.145160E+11 0.236388E+11 0.360447E+11 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: CORE_BOTTOM

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.120254E+11 0.196958E+11 0.243681E+11 0.00 0.00 0.00 0.00 0.00 0.00
February 0.109099E+11 0.178655E+11 0.220609E+11 0.00 0.00 0.00 0.00 0.00 0.00
March 0.130364E+11 0.212293E+11 0.253549E+11 0.00 0.00 0.00 0.00 0.00 0.00
April 0.115676E+11 0.189620E+11 0.235306E+11 0.00 0.00 0.00 0.00 0.00 0.00
May 0.125309E+11 0.204625E+11 0.248615E+11 0.00 0.00 0.00 0.00 0.00 0.00
June 0.124961E+11 0.203636E+11 0.244160E+11 0.00 0.00 0.00 0.00 0.00 0.00
July 0.116025E+11 0.190610E+11 0.239708E+11 0.00 0.00 0.00 0.00 0.00 0.00
August 0.130364E+11 0.212293E+11 0.253549E+11 0.00 0.00 0.00 0.00 0.00 0.00
September 0.115676E+11 0.189620E+11 0.235199E+11 0.00 0.00 0.00 0.00 0.00 0.00
October 0.120254E+11 0.196958E+11 0.243735E+11 0.00 0.00 0.00 0.00 0.00 0.00
November 0.119080E+11 0.194649E+11 0.238373E+11 0.00 0.00 0.00 0.00 0.00 0.00
December 0.116025E+11 0.190610E+11 0.239654E+11 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.144308E+12 0.236053E+12 0.289614E+12 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.109099E+11 0.178655E+11 0.220609E+11 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.130364E+11 0.212293E+11 0.253549E+11 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: CORE_MID

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.120254E+11 0.196958E+11 0.243680E+11 0.00 0.00 0.00 0.00 0.00 0.00
February 0.109099E+11 0.178655E+11 0.220609E+11 0.00 0.00 0.00 0.00 0.00 0.00
March 0.130364E+11 0.212293E+11 0.253548E+11 0.00 0.00 0.00 0.00 0.00 0.00
April 0.115676E+11 0.189620E+11 0.235305E+11 0.00 0.00 0.00 0.00 0.00 0.00
May 0.125309E+11 0.204625E+11 0.248614E+11 0.00 0.00 0.00 0.00 0.00 0.00
June 0.124961E+11 0.203636E+11 0.244159E+11 0.00 0.00 0.00 0.00 0.00 0.00
July 0.116025E+11 0.190610E+11 0.239707E+11 0.00 0.00 0.00 0.00 0.00 0.00
August 0.130364E+11 0.212293E+11 0.253548E+11 0.00 0.00 0.00 0.00 0.00 0.00
September 0.115676E+11 0.189620E+11 0.235198E+11 0.00 0.00 0.00 0.00 0.00 0.00
October 0.120254E+11 0.196958E+11 0.243734E+11 0.00 0.00 0.00 0.00 0.00 0.00
November 0.119080E+11 0.194649E+11 0.238372E+11 0.00 0.00 0.00 0.00 0.00 0.00
December 0.116025E+11 0.190610E+11 0.239653E+11 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.144308E+12 0.236053E+12 0.289613E+12 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.109099E+11 0.178655E+11 0.220609E+11 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.130364E+11 0.212293E+11 0.253548E+11 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: CORE_TOP

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.120254E+11 0.196958E+11 0.243680E+11 0.00 0.00 0.00 0.00 0.00 0.00
February 0.109099E+11 0.178655E+11 0.220609E+11 0.00 0.00 0.00 0.00 0.00 0.00
March 0.130364E+11 0.212293E+11 0.253548E+11 0.00 0.00 0.00 0.00 0.00 0.00
April 0.115676E+11 0.189620E+11 0.235305E+11 0.00 0.00 0.00 0.00 0.00 0.00
May 0.125309E+11 0.204625E+11 0.248614E+11 0.00 0.00 0.00 0.00 0.00 0.00
June 0.124961E+11 0.203636E+11 0.244159E+11 0.00 0.00 0.00 0.00 0.00 0.00
July 0.116025E+11 0.190610E+11 0.239707E+11 0.00 0.00 0.00 0.00 0.00 0.00
August 0.130364E+11 0.212293E+11 0.253548E+11 0.00 0.00 0.00 0.00 0.00 0.00
September 0.115676E+11 0.189620E+11 0.235198E+11 0.00 0.00 0.00 0.00 0.00 0.00
October 0.120254E+11 0.196958E+11 0.243734E+11 0.00 0.00 0.00 0.00 0.00 0.00
November 0.119080E+11 0.194649E+11 0.238372E+11 0.00 0.00 0.00 0.00 0.00 0.00
December 0.116025E+11 0.190610E+11 0.239653E+11 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.144308E+12 0.236053E+12 0.289613E+12 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.109099E+11 0.178655E+11 0.220609E+11 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.130364E+11 0.212293E+11 0.253548E+11 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.150991E+10 0.164519E+10 0.305979E+10 0.00 0.00 0.00 0.00 0.00 0.946577E+09
February 0.136985E+10 0.148700E+10 0.277008E+10 0.00 0.00 0.00 0.00 541198.99 0.803305E+09
March 0.163685E+10 0.156487E+10 0.318369E+10 0.00 0.00 0.00 0.00 1653898.63 0.524276E+09
April 0.145243E+10 0.133785E+10 0.295462E+10 0.00 0.00 0.00 0.00 4811543.39 0.315612E+09
May 0.157338E+10 0.138865E+10 0.312174E+10 0.00 0.00 0.00 0.00 14574659.91 0.198107E+09
June 0.156900E+10 0.136362E+10 0.306580E+10 0.00 0.00 0.00 0.00 59755129.75 92246109.04
July 0.145680E+10 0.129798E+10 0.300989E+10 0.00 0.00 0.00 0.00 67147714.99 54954917.11
August 0.163685E+10 0.147313E+10 0.318369E+10 0.00 0.00 0.00 0.00 65871487.11 24002661.81
September 0.145243E+10 0.138990E+10 0.295328E+10 0.00 0.00 0.00 0.00 17999779.77 0.105152E+09
October 0.150991E+10 0.157657E+10 0.306046E+10 0.00 0.00 0.00 0.00 4135042.33 0.357047E+09
November 0.149516E+10 0.158302E+10 0.299314E+10 0.00 0.00 0.00 0.00 51461.12 0.525925E+09
December 0.145680E+10 0.161015E+10 0.300922E+10 0.00 0.00 0.00 0.00 0.00 0.912675E+09
                   
Annual Sum or Average 0.181194E+11 0.177179E+11 0.363654E+11 0.00 0.00 0.00 0.00 0.236542E+09 0.485988E+10
Minimum of Months 0.136985E+10 0.129798E+10 0.277008E+10 0.00 0.00 0.00 0.00 0.00 24002661.81
Maximum of Months 0.163685E+10 0.164519E+10 0.318369E+10 0.00 0.00 0.00 0.00 67147714.99 0.946577E+09



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.973041E+09 0.101471E+10 0.197184E+10 0.00 0.00 0.00 0.00 0.00 0.633842E+09
February 0.882782E+09 0.918555E+09 0.178515E+10 0.00 0.00 0.00 0.00 222308.86 0.535074E+09
March 0.105485E+10 0.988585E+09 0.205169E+10 0.00 0.00 0.00 0.00 1412059.46 0.342946E+09
April 0.936002E+09 0.858042E+09 0.190407E+10 0.00 0.00 0.00 0.00 3463841.49 0.201557E+09
May 0.101394E+10 0.902214E+09 0.201177E+10 0.00 0.00 0.00 0.00 9457020.99 0.133297E+09
June 0.101113E+10 0.886900E+09 0.197572E+10 0.00 0.00 0.00 0.00 40748178.28 58316025.48
July 0.938820E+09 0.840993E+09 0.193969E+10 0.00 0.00 0.00 0.00 47023787.78 32242372.02
August 0.105485E+10 0.949747E+09 0.205169E+10 0.00 0.00 0.00 0.00 48588105.39 10257757.29
September 0.936002E+09 0.880737E+09 0.190321E+10 0.00 0.00 0.00 0.00 12178530.79 67341413.89
October 0.973041E+09 0.969692E+09 0.197228E+10 0.00 0.00 0.00 0.00 2652629.22 0.233266E+09
November 0.963541E+09 0.989382E+09 0.192889E+10 0.00 0.00 0.00 0.00 207769.49 0.343797E+09
December 0.938820E+09 0.988938E+09 0.193926E+10 0.00 0.00 0.00 0.00 0.00 0.594302E+09
                   
Annual Sum or Average 0.116768E+11 0.111885E+11 0.234352E+11 0.00 0.00 0.00 0.00 0.165954E+09 0.318624E+10
Minimum of Months 0.882782E+09 0.840993E+09 0.178515E+10 0.00 0.00 0.00 0.00 0.00 10257757.29
Maximum of Months 0.105485E+10 0.101471E+10 0.205169E+10 0.00 0.00 0.00 0.00 48588105.39 0.633842E+09



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.150994E+10 0.151610E+10 0.305983E+10 0.00 0.00 0.00 0.00 0.00 0.962914E+09
February 0.136988E+10 0.139430E+10 0.277013E+10 0.00 0.00 0.00 0.00 95585.79 0.822281E+09
March 0.163688E+10 0.153556E+10 0.318374E+10 0.00 0.00 0.00 0.00 1573977.76 0.541889E+09
April 0.145246E+10 0.134267E+10 0.295467E+10 0.00 0.00 0.00 0.00 4015536.40 0.315287E+09
May 0.157341E+10 0.141061E+10 0.312179E+10 0.00 0.00 0.00 0.00 13765665.35 0.196853E+09
June 0.156904E+10 0.138612E+10 0.306585E+10 0.00 0.00 0.00 0.00 59686051.17 90550674.61
July 0.145684E+10 0.131813E+10 0.300994E+10 0.00 0.00 0.00 0.00 66119145.80 54231757.49
August 0.163688E+10 0.148201E+10 0.318374E+10 0.00 0.00 0.00 0.00 62861588.06 25812415.96
September 0.145246E+10 0.137226E+10 0.295333E+10 0.00 0.00 0.00 0.00 15112665.51 0.106124E+09
October 0.150994E+10 0.148633E+10 0.306051E+10 0.00 0.00 0.00 0.00 2437398.94 0.367135E+09
November 0.149520E+10 0.148340E+10 0.299318E+10 0.00 0.00 0.00 0.00 0.00 0.541422E+09
December 0.145684E+10 0.147188E+10 0.300927E+10 0.00 0.00 0.00 0.00 0.00 0.911908E+09
                   
Annual Sum or Average 0.181198E+11 0.171994E+11 0.363660E+11 0.00 0.00 0.00 0.00 0.225668E+09 0.493641E+10
Minimum of Months 0.136988E+10 0.131813E+10 0.277013E+10 0.00 0.00 0.00 0.00 0.00 25812415.96
Maximum of Months 0.163688E+10 0.153556E+10 0.318374E+10 0.00 0.00 0.00 0.00 66119145.80 0.962914E+09



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.973041E+09 0.101481E+10 0.197183E+10 0.00 0.00 0.00 0.00 0.00 0.663524E+09
February 0.882782E+09 0.932742E+09 0.178514E+10 0.00 0.00 0.00 0.00 81760.78 0.582401E+09
March 0.105485E+10 0.100688E+10 0.205168E+10 0.00 0.00 0.00 0.00 1037877.91 0.405812E+09
April 0.936002E+09 0.867027E+09 0.190406E+10 0.00 0.00 0.00 0.00 2559684.70 0.250462E+09
May 0.101394E+10 0.908560E+09 0.201175E+10 0.00 0.00 0.00 0.00 8571176.72 0.149428E+09
June 0.101113E+10 0.890974E+09 0.197570E+10 0.00 0.00 0.00 0.00 37070345.03 75486103.95
July 0.938820E+09 0.848381E+09 0.193968E+10 0.00 0.00 0.00 0.00 39804641.43 48025608.13
August 0.105485E+10 0.958468E+09 0.205168E+10 0.00 0.00 0.00 0.00 37421374.08 28214443.95
September 0.936002E+09 0.896243E+09 0.190319E+10 0.00 0.00 0.00 0.00 10828959.70 81497113.87
October 0.973041E+09 0.999383E+09 0.197226E+10 0.00 0.00 0.00 0.00 1783414.64 0.269078E+09
November 0.963541E+09 0.980521E+09 0.192888E+10 0.00 0.00 0.00 0.00 0.00 0.395297E+09
December 0.938820E+09 0.987375E+09 0.193924E+10 0.00 0.00 0.00 0.00 0.00 0.684507E+09
                   
Annual Sum or Average 0.116768E+11 0.112914E+11 0.234351E+11 0.00 0.00 0.00 0.00 0.139159E+09 0.363373E+10
Minimum of Months 0.882782E+09 0.848381E+09 0.178514E+10 0.00 0.00 0.00 0.00 0.00 28214443.95
Maximum of Months 0.105485E+10 0.101481E+10 0.205168E+10 0.00 0.00 0.00 0.00 39804641.43 0.684507E+09



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.150991E+10 0.163281E+10 0.305979E+10 0.00 0.00 0.00 0.00 0.00 0.190401E+10
February 0.136985E+10 0.147900E+10 0.277008E+10 0.00 0.00 0.00 0.00 4822054.68 0.161239E+10
March 0.163685E+10 0.155941E+10 0.318369E+10 0.00 0.00 0.00 0.00 5388019.74 0.103217E+10
April 0.145243E+10 0.133433E+10 0.295462E+10 0.00 0.00 0.00 0.00 14022526.76 0.652131E+09
May 0.157338E+10 0.138700E+10 0.312174E+10 0.00 0.00 0.00 0.00 35635418.87 0.423468E+09
June 0.156900E+10 0.136191E+10 0.306580E+10 0.00 0.00 0.00 0.00 0.138695E+09 0.213193E+09
July 0.145680E+10 0.129625E+10 0.300989E+10 0.00 0.00 0.00 0.00 0.152060E+09 0.139261E+09
August 0.163685E+10 0.147090E+10 0.318369E+10 0.00 0.00 0.00 0.00 0.148203E+09 85932060.34
September 0.145243E+10 0.138412E+10 0.295328E+10 0.00 0.00 0.00 0.00 44287863.81 0.214098E+09
October 0.150991E+10 0.156565E+10 0.306046E+10 0.00 0.00 0.00 0.00 16168730.43 0.697118E+09
November 0.149516E+10 0.157391E+10 0.299314E+10 0.00 0.00 0.00 0.00 929837.35 0.101044E+10
December 0.145680E+10 0.159810E+10 0.300922E+10 0.00 0.00 0.00 0.00 0.00 0.172692E+10
                   
Annual Sum or Average 0.181194E+11 0.176434E+11 0.363654E+11 0.00 0.00 0.00 0.00 0.560214E+09 0.971114E+10
Minimum of Months 0.136985E+10 0.129625E+10 0.277008E+10 0.00 0.00 0.00 0.00 0.00 85932060.34
Maximum of Months 0.163685E+10 0.163281E+10 0.318369E+10 0.00 0.00 0.00 0.00 0.152060E+09 0.190401E+10



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.715730E+09 0.100989E+10 0.197184E+10 0.00 0.00 0.00 0.00 0.00 0.129399E+10
February 0.649041E+09 0.915334E+09 0.178515E+10 0.00 0.00 0.00 0.00 1411073.03 0.110419E+10
March 0.773965E+09 0.986649E+09 0.205169E+10 0.00 0.00 0.00 0.00 3994747.19 0.718482E+09
April 0.688021E+09 0.856622E+09 0.190407E+10 0.00 0.00 0.00 0.00 7738401.72 0.451067E+09
May 0.744847E+09 0.901322E+09 0.201177E+10 0.00 0.00 0.00 0.00 21031821.60 0.296463E+09
June 0.742030E+09 0.886119E+09 0.197572E+10 0.00 0.00 0.00 0.00 90737909.90 0.146646E+09
July 0.690839E+09 0.840347E+09 0.193969E+10 0.00 0.00 0.00 0.00 98648856.19 95841822.82
August 0.773965E+09 0.948789E+09 0.205169E+10 0.00 0.00 0.00 0.00 96891396.19 59247764.89
September 0.688021E+09 0.879519E+09 0.190321E+10 0.00 0.00 0.00 0.00 28045590.67 0.142391E+09
October 0.715730E+09 0.966687E+09 0.197228E+10 0.00 0.00 0.00 0.00 7711151.99 0.480466E+09
November 0.708685E+09 0.985860E+09 0.192889E+10 0.00 0.00 0.00 0.00 550590.84 0.693749E+09
December 0.690839E+09 0.986180E+09 0.193926E+10 0.00 0.00 0.00 0.00 15698.23 0.116762E+10
                   
Annual Sum or Average 0.858171E+10 0.111633E+11 0.234352E+11 0.00 0.00 0.00 0.00 0.356777E+09 0.665015E+10
Minimum of Months 0.649041E+09 0.840347E+09 0.178515E+10 0.00 0.00 0.00 0.00 0.00 59247764.89
Maximum of Months 0.773965E+09 0.100989E+10 0.205169E+10 0.00 0.00 0.00 0.00 98648856.19 0.129399E+10



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.150994E+10 0.151467E+10 0.305983E+10 0.00 0.00 0.00 0.00 0.00 0.208251E+10
February 0.136988E+10 0.139281E+10 0.277013E+10 0.00 0.00 0.00 0.00 191723.69 0.176988E+10
March 0.163688E+10 0.153305E+10 0.318374E+10 0.00 0.00 0.00 0.00 3508061.27 0.117818E+10
April 0.145246E+10 0.133946E+10 0.295467E+10 0.00 0.00 0.00 0.00 8992357.79 0.696423E+09
May 0.157341E+10 0.140845E+10 0.312179E+10 0.00 0.00 0.00 0.00 31480345.01 0.434589E+09
June 0.156904E+10 0.138378E+10 0.306585E+10 0.00 0.00 0.00 0.00 0.137291E+09 0.211987E+09
July 0.145684E+10 0.131584E+10 0.300994E+10 0.00 0.00 0.00 0.00 0.147921E+09 0.140296E+09
August 0.163688E+10 0.148015E+10 0.318374E+10 0.00 0.00 0.00 0.00 0.138420E+09 93690923.06
September 0.145246E+10 0.137019E+10 0.295333E+10 0.00 0.00 0.00 0.00 33882018.91 0.232481E+09
October 0.150994E+10 0.148476E+10 0.306051E+10 0.00 0.00 0.00 0.00 5209991.58 0.798124E+09
November 0.149520E+10 0.148021E+10 0.299318E+10 0.00 0.00 0.00 0.00 0.00 0.116984E+10
December 0.145684E+10 0.146964E+10 0.300927E+10 0.00 0.00 0.00 0.00 0.00 0.189215E+10
                   
Annual Sum or Average 0.181198E+11 0.171730E+11 0.363660E+11 0.00 0.00 0.00 0.00 0.506896E+09 0.107001E+11
Minimum of Months 0.136988E+10 0.131584E+10 0.277013E+10 0.00 0.00 0.00 0.00 0.00 93690923.06
Maximum of Months 0.163688E+10 0.153305E+10 0.318374E+10 0.00 0.00 0.00 0.00 0.147921E+09 0.208251E+10



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.973041E+09 0.101166E+10 0.197183E+10 0.00 0.00 0.00 0.00 0.00 0.132885E+10
February 0.882782E+09 0.929254E+09 0.178514E+10 0.00 0.00 0.00 0.00 1616975.14 0.113204E+10
March 0.105485E+10 0.100366E+10 0.205168E+10 0.00 0.00 0.00 0.00 2584508.70 0.770492E+09
April 0.936002E+09 0.865094E+09 0.190406E+10 0.00 0.00 0.00 0.00 6953378.33 0.482279E+09
May 0.101394E+10 0.906387E+09 0.201175E+10 0.00 0.00 0.00 0.00 20663468.98 0.309883E+09
June 0.101113E+10 0.889258E+09 0.197570E+10 0.00 0.00 0.00 0.00 87162730.41 0.159262E+09
July 0.938820E+09 0.846935E+09 0.193968E+10 0.00 0.00 0.00 0.00 94831823.78 0.105058E+09
August 0.105485E+10 0.956355E+09 0.205168E+10 0.00 0.00 0.00 0.00 89495916.23 74782601.94
September 0.936002E+09 0.893970E+09 0.190319E+10 0.00 0.00 0.00 0.00 26124917.96 0.156374E+09
October 0.973041E+09 0.994877E+09 0.197226E+10 0.00 0.00 0.00 0.00 5967358.79 0.506638E+09
November 0.963541E+09 0.977743E+09 0.192888E+10 0.00 0.00 0.00 0.00 0.00 0.725781E+09
December 0.938820E+09 0.983433E+09 0.193924E+10 0.00 0.00 0.00 0.00 0.00 0.121369E+10
                   
Annual Sum or Average 0.116768E+11 0.112586E+11 0.234351E+11 0.00 0.00 0.00 0.00 0.335401E+09 0.696512E+10
Minimum of Months 0.882782E+09 0.846935E+09 0.178514E+10 0.00 0.00 0.00 0.00 0.00 74782601.94
Maximum of Months 0.105485E+10 0.101166E+10 0.205168E+10 0.00 0.00 0.00 0.00 94831823.78 0.132885E+10



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.150991E+10 0.163253E+10 0.305979E+10 0.00 0.00 0.00 0.00 0.00 0.226724E+10
February 0.136985E+10 0.147861E+10 0.277008E+10 0.00 0.00 0.00 0.00 7890730.77 0.191893E+10
March 0.163685E+10 0.155915E+10 0.318369E+10 0.00 0.00 0.00 0.00 6925256.56 0.118972E+10
April 0.145243E+10 0.133425E+10 0.295462E+10 0.00 0.00 0.00 0.00 16824582.65 0.759529E+09
May 0.157338E+10 0.138683E+10 0.312174E+10 0.00 0.00 0.00 0.00 40787618.90 0.514544E+09
June 0.156900E+10 0.136189E+10 0.306580E+10 0.00 0.00 0.00 0.00 0.163939E+09 0.268014E+09
July 0.145680E+10 0.129621E+10 0.300989E+10 0.00 0.00 0.00 0.00 0.176552E+09 0.176301E+09
August 0.163685E+10 0.147061E+10 0.318369E+10 0.00 0.00 0.00 0.00 0.172405E+09 0.112493E+09
September 0.145243E+10 0.138411E+10 0.295328E+10 0.00 0.00 0.00 0.00 52749913.82 0.250654E+09
October 0.150991E+10 0.156494E+10 0.306046E+10 0.00 0.00 0.00 0.00 21973176.34 0.790676E+09
November 0.149516E+10 0.157323E+10 0.299314E+10 0.00 0.00 0.00 0.00 4510173.26 0.113502E+10
December 0.145680E+10 0.159788E+10 0.300922E+10 0.00 0.00 0.00 0.00 67616.00 0.198454E+10
                   
Annual Sum or Average 0.181194E+11 0.176402E+11 0.363654E+11 0.00 0.00 0.00 0.00 0.664625E+09 0.113677E+11
Minimum of Months 0.136985E+10 0.129621E+10 0.277008E+10 0.00 0.00 0.00 0.00 0.00 0.112493E+09
Maximum of Months 0.163685E+10 0.163253E+10 0.318369E+10 0.00 0.00 0.00 0.00 0.176552E+09 0.226724E+10



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.973041E+09 0.100985E+10 0.197184E+10 0.00 0.00 0.00 0.00 0.00 0.152700E+10
February 0.882782E+09 0.914948E+09 0.178515E+10 0.00 0.00 0.00 0.00 2591352.44 0.130932E+10
March 0.105485E+10 0.986409E+09 0.205169E+10 0.00 0.00 0.00 0.00 4882257.89 0.836878E+09
April 0.936002E+09 0.856592E+09 0.190407E+10 0.00 0.00 0.00 0.00 8770595.79 0.532430E+09
May 0.101394E+10 0.901263E+09 0.201177E+10 0.00 0.00 0.00 0.00 24064274.18 0.363671E+09
June 0.101113E+10 0.886119E+09 0.197572E+10 0.00 0.00 0.00 0.00 0.107021E+09 0.185875E+09
July 0.938820E+09 0.840205E+09 0.193969E+10 0.00 0.00 0.00 0.00 0.115790E+09 0.121506E+09
August 0.105485E+10 0.948730E+09 0.205169E+10 0.00 0.00 0.00 0.00 0.113775E+09 77451441.88
September 0.936002E+09 0.879472E+09 0.190321E+10 0.00 0.00 0.00 0.00 33139732.04 0.169517E+09
October 0.973041E+09 0.966567E+09 0.197228E+10 0.00 0.00 0.00 0.00 9824466.34 0.552912E+09
November 0.963541E+09 0.985765E+09 0.192889E+10 0.00 0.00 0.00 0.00 2390178.40 0.784826E+09
December 0.938820E+09 0.986046E+09 0.193926E+10 0.00 0.00 0.00 0.00 2862.20 0.133264E+10
                   
Annual Sum or Average 0.116768E+11 0.111620E+11 0.234352E+11 0.00 0.00 0.00 0.00 0.422251E+09 0.779403E+10
Minimum of Months 0.882782E+09 0.840205E+09 0.178515E+10 0.00 0.00 0.00 0.00 0.00 77451441.88
Maximum of Months 0.105485E+10 0.100985E+10 0.205169E+10 0.00 0.00 0.00 0.00 0.115790E+09 0.152700E+10



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.150994E+10 0.151449E+10 0.305983E+10 0.00 0.00 0.00 0.00 0.00 0.241732E+10
February 0.136988E+10 0.139239E+10 0.277013E+10 0.00 0.00 0.00 0.00 201260.68 0.207901E+10
March 0.163688E+10 0.153277E+10 0.318374E+10 0.00 0.00 0.00 0.00 4150389.42 0.137141E+10
April 0.145246E+10 0.133924E+10 0.295467E+10 0.00 0.00 0.00 0.00 10610695.71 0.813645E+09
May 0.157341E+10 0.140845E+10 0.312179E+10 0.00 0.00 0.00 0.00 36841778.18 0.526188E+09
June 0.156904E+10 0.138356E+10 0.306585E+10 0.00 0.00 0.00 0.00 0.163991E+09 0.265002E+09
July 0.145684E+10 0.131564E+10 0.300994E+10 0.00 0.00 0.00 0.00 0.175137E+09 0.175865E+09
August 0.163688E+10 0.148013E+10 0.318374E+10 0.00 0.00 0.00 0.00 0.165140E+09 0.121127E+09
September 0.145246E+10 0.137003E+10 0.295333E+10 0.00 0.00 0.00 0.00 40602250.77 0.272972E+09
October 0.150994E+10 0.148469E+10 0.306051E+10 0.00 0.00 0.00 0.00 6065262.70 0.919690E+09
November 0.149520E+10 0.148007E+10 0.299318E+10 0.00 0.00 0.00 0.00 0.00 0.132885E+10
December 0.145684E+10 0.146956E+10 0.300927E+10 0.00 0.00 0.00 0.00 0.00 0.213638E+10
                   
Annual Sum or Average 0.181198E+11 0.171710E+11 0.363660E+11 0.00 0.00 0.00 0.00 0.602740E+09 0.124275E+11
Minimum of Months 0.136988E+10 0.131564E+10 0.277013E+10 0.00 0.00 0.00 0.00 0.00 0.121127E+09
Maximum of Months 0.163688E+10 0.153277E+10 0.318374E+10 0.00 0.00 0.00 0.00 0.175137E+09 0.241732E+10



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.973041E+09 0.101165E+10 0.197183E+10 0.00 0.00 0.00 0.00 0.00 0.156195E+10
February 0.882782E+09 0.929159E+09 0.178514E+10 0.00 0.00 0.00 0.00 2451607.15 0.134741E+10
March 0.105485E+10 0.100346E+10 0.205168E+10 0.00 0.00 0.00 0.00 3152611.10 0.907130E+09
April 0.936002E+09 0.865048E+09 0.190406E+10 0.00 0.00 0.00 0.00 8521808.80 0.569673E+09
May 0.101394E+10 0.906497E+09 0.201175E+10 0.00 0.00 0.00 0.00 24812434.07 0.376774E+09
June 0.101113E+10 0.889166E+09 0.197570E+10 0.00 0.00 0.00 0.00 0.105350E+09 0.198258E+09
July 0.938820E+09 0.846873E+09 0.193968E+10 0.00 0.00 0.00 0.00 0.114046E+09 0.130628E+09
August 0.105485E+10 0.956181E+09 0.205168E+10 0.00 0.00 0.00 0.00 0.107888E+09 94814611.03
September 0.936002E+09 0.893967E+09 0.190319E+10 0.00 0.00 0.00 0.00 31960883.24 0.184975E+09
October 0.973041E+09 0.994527E+09 0.197226E+10 0.00 0.00 0.00 0.00 7773898.91 0.589077E+09
November 0.963541E+09 0.977696E+09 0.192888E+10 0.00 0.00 0.00 0.00 25811.63 0.834272E+09
December 0.938820E+09 0.983336E+09 0.193924E+10 0.00 0.00 0.00 0.00 0.00 0.139403E+10
                   
Annual Sum or Average 0.116768E+11 0.112576E+11 0.234351E+11 0.00 0.00 0.00 0.00 0.405983E+09 0.818900E+10
Minimum of Months 0.882782E+09 0.846873E+09 0.178514E+10 0.00 0.00 0.00 0.00 0.00 94814611.03
Maximum of Months 0.105485E+10 0.101165E+10 0.205168E+10 0.00 0.00 0.00 0.00 0.114046E+09 0.156195E+10



Table of Contents

Report: SpaceGainsMonthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.174411E+09 0.553024E+09 0.521915E+10 0.00 0.00 0.00 0.00 0.00 0.00
February 0.158233E+09 0.501634E+09 0.942813E+10 0.00 0.00 0.00 0.00 0.00 0.00
March 0.189074E+09 0.596080E+09 0.156645E+11 0.00 0.00 0.00 0.00 0.00 0.00
April 0.167772E+09 0.532421E+09 0.201821E+11 0.00 0.00 0.00 0.00 0.00 0.00
May 0.181743E+09 0.574552E+09 0.522616E+10 0.00 0.00 0.00 0.00 0.00 0.00
June 0.181238E+09 0.571774E+09 0.101086E+11 0.00 0.00 0.00 0.00 0.00 0.00
July 0.168277E+09 0.535199E+09 0.156645E+11 0.00 0.00 0.00 0.00 0.00 0.00
August 0.189074E+09 0.596080E+09 0.208555E+11 0.00 0.00 0.00 0.00 0.00 0.00
September 0.167772E+09 0.532421E+09 0.505780E+10 0.00 0.00 0.00 0.00 0.00 0.00
October 0.174411E+09 0.553024E+09 0.104453E+11 0.00 0.00 0.00 0.00 0.00 0.00
November 0.172708E+09 0.546542E+09 0.151524E+11 0.00 0.00 0.00 0.00 0.00 0.00
December 0.168277E+09 0.535199E+09 0.208766E+11 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.209299E+10 0.662795E+10 0.153881E+12 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.158233E+09 0.501634E+09 0.505780E+10 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.189074E+09 0.596080E+09 0.208766E+11 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: DATACENTER_MID_ZN_6

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.174411E+09 0.553024E+09 0.521915E+10 0.00 0.00 0.00 0.00 0.00 0.00
February 0.158233E+09 0.501634E+09 0.942813E+10 0.00 0.00 0.00 0.00 0.00 0.00
March 0.189074E+09 0.596080E+09 0.156645E+11 0.00 0.00 0.00 0.00 0.00 0.00
April 0.167772E+09 0.532421E+09 0.201821E+11 0.00 0.00 0.00 0.00 0.00 0.00
May 0.181743E+09 0.574552E+09 0.522616E+10 0.00 0.00 0.00 0.00 0.00 0.00
June 0.181238E+09 0.571774E+09 0.101086E+11 0.00 0.00 0.00 0.00 0.00 0.00
July 0.168277E+09 0.535199E+09 0.156645E+11 0.00 0.00 0.00 0.00 0.00 0.00
August 0.189074E+09 0.596080E+09 0.208555E+11 0.00 0.00 0.00 0.00 0.00 0.00
September 0.167772E+09 0.532421E+09 0.505780E+10 0.00 0.00 0.00 0.00 0.00 0.00
October 0.174411E+09 0.553024E+09 0.104453E+11 0.00 0.00 0.00 0.00 0.00 0.00
November 0.172708E+09 0.546542E+09 0.151524E+11 0.00 0.00 0.00 0.00 0.00 0.00
December 0.168277E+09 0.535199E+09 0.208766E+11 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.209299E+10 0.662795E+10 0.153881E+12 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.158233E+09 0.501634E+09 0.505780E+10 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.189074E+09 0.596080E+09 0.208766E+11 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.174411E+09 0.553024E+09 0.521915E+10 0.00 0.00 0.00 0.00 0.00 0.00
February 0.158233E+09 0.501634E+09 0.942813E+10 0.00 0.00 0.00 0.00 0.00 0.00
March 0.189074E+09 0.596080E+09 0.156645E+11 0.00 0.00 0.00 0.00 0.00 0.00
April 0.167772E+09 0.532421E+09 0.201821E+11 0.00 0.00 0.00 0.00 0.00 0.00
May 0.181743E+09 0.574552E+09 0.522616E+10 0.00 0.00 0.00 0.00 0.00 0.00
June 0.181238E+09 0.571774E+09 0.101086E+11 0.00 0.00 0.00 0.00 0.00 0.00
July 0.168277E+09 0.535199E+09 0.156645E+11 0.00 0.00 0.00 0.00 0.00 0.00
August 0.189074E+09 0.596080E+09 0.208555E+11 0.00 0.00 0.00 0.00 0.00 0.00
September 0.167772E+09 0.532421E+09 0.505780E+10 0.00 0.00 0.00 0.00 0.00 0.00
October 0.174411E+09 0.553024E+09 0.104453E+11 0.00 0.00 0.00 0.00 0.00 0.00
November 0.172708E+09 0.546542E+09 0.151524E+11 0.00 0.00 0.00 0.00 0.00 0.00
December 0.168277E+09 0.535199E+09 0.208766E+11 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.209299E+10 0.662795E+10 0.153881E+12 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.158233E+09 0.501634E+09 0.505780E+10 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.189074E+09 0.596080E+09 0.208766E+11 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.377547E+10 0.618367E+10 0.254202E+12 0.00 0.00 0.00 0.00 0.00 0.00
February 0.342526E+10 0.560905E+10 0.459203E+12 0.00 0.00 0.00 0.00 0.00 0.00
March 0.409289E+10 0.666512E+10 0.762947E+12 0.00 0.00 0.00 0.00 0.00 0.00
April 0.363176E+10 0.595330E+10 0.982982E+12 0.00 0.00 0.00 0.00 0.00 0.00
May 0.393418E+10 0.642439E+10 0.254544E+12 0.00 0.00 0.00 0.00 0.00 0.00
June 0.392325E+10 0.639333E+10 0.492345E+12 0.00 0.00 0.00 0.00 0.00 0.00
July 0.364269E+10 0.598436E+10 0.762947E+12 0.00 0.00 0.00 0.00 0.00 0.00
August 0.409289E+10 0.666512E+10 0.101578E+13 0.00 0.00 0.00 0.00 0.00 0.00
September 0.363176E+10 0.595330E+10 0.246344E+12 0.00 0.00 0.00 0.00 0.00 0.00
October 0.377547E+10 0.618367E+10 0.508746E+12 0.00 0.00 0.00 0.00 0.00 0.00
November 0.373861E+10 0.611120E+10 0.738006E+12 0.00 0.00 0.00 0.00 0.00 0.00
December 0.364269E+10 0.598436E+10 0.101681E+13 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.453069E+11 0.741109E+11 0.749486E+13 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.342526E+10 0.560905E+10 0.246344E+12 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.409289E+10 0.666512E+10 0.101681E+13 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: GROUNDFLOOR_PLENUM

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.210638E+10
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 100294.51 0.179163E+10
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 2006555.40 0.116346E+10
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 6166342.42 0.693682E+09
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 23510907.51 0.428281E+09
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.106370E+09 0.201599E+09
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.124242E+09 0.126821E+09
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.115203E+09 71202823.41
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 28318173.24 0.229961E+09
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 4922915.38 0.789144E+09
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.116796E+10
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.202070E+10
                   
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.410841E+09 0.107908E+11
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 71202823.41
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.124242E+09 0.210638E+10



Table of Contents

Report: SpaceGainsMonthly

For: MIDFLOOR_PLENUM

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.337170E+10
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 2439585.09 0.287469E+10
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 5060198.36 0.191158E+10
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 14947299.70 0.116050E+10
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 47552505.70 0.730562E+09
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.198605E+09 0.349472E+09
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.228356E+09 0.225705E+09
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.210828E+09 0.139007E+09
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 56872091.53 0.383446E+09
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 13472605.07 0.129443E+10
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 961807.57 0.188729E+10
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.319475E+10
                   
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.779095E+09 0.175231E+11
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.139007E+09
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.228356E+09 0.337170E+10



Table of Contents

Report: SpaceGainsMonthly

For: TOPFLOOR_PLENUM

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.341488E+10
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 2883919.90 0.296556E+10
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 3345712.65 0.199247E+10
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 7127160.41 0.124452E+10
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 27625936.85 0.818860E+09
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.176797E+09 0.395413E+09
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.202975E+09 0.261722E+09
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.192916E+09 0.164968E+09
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 46402936.34 0.398068E+09
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 9195120.03 0.131578E+10
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 2575902.35 0.186212E+10
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.311870E+10
                   
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.671845E+09 0.179531E+11
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.164968E+09
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.202975E+09 0.341488E+10



Table of Contents

Report: PeakSpaceGainsMonthly

For: BASEMENT

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 17832.21 02-JAN-10:09 22950.34 02-JAN-08:09 13457.54 01-JAN-00:10 0.00 0.00 0.00 0.00 0.00 0.00
February 17832.21 01-FEB-10:09 22950.34 01-FEB-08:09 13457.54 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00 0.00
March 17832.21 01-MAR-10:09 22950.34 01-MAR-08:09 13457.54 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00 0.00
April 17832.21 03-APR-09:09 22950.34 03-APR-07:10 13457.54 01-APR-00:10 0.00 0.00 0.00 0.00 0.00 0.00
May 17832.21 01-MAY-09:09 22950.34 01-MAY-07:10 13457.54 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00 0.00
June 17832.21 01-JUN-09:09 22950.34 01-JUN-07:10 13457.54 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00 0.00
July 17832.21 03-JUL-09:09 22950.34 03-JUL-07:10 13457.54 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00 0.00
August 17832.21 01-AUG-09:09 22950.34 01-AUG-07:10 13457.54 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00 0.00
September 17832.21 01-SEP-09:09 22950.34 01-SEP-07:10 13457.54 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00 0.00
October 17832.21 02-OCT-09:09 22950.34 02-OCT-07:10 13457.54 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00 0.00
November 17832.21 01-NOV-09:09 22950.34 01-NOV-07:10 13457.54 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00 0.00
December 17832.21 01-DEC-10:09 22950.34 01-DEC-08:09 13457.54 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average             0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 17832.21   22950.34   13457.54   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 17832.21   22950.34   13457.54   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: CORE_BOTTOM

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 16014.58 02-JAN-10:09 20611.01 02-JAN-08:09 17206.63 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 0.00
February 16014.58 01-FEB-10:09 20611.01 01-FEB-08:09 17206.63 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 0.00
March 16014.58 01-MAR-10:09 20611.01 01-MAR-08:09 17206.63 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 0.00
April 16014.58 03-APR-09:09 20611.01 03-APR-07:10 17206.63 03-APR-07:10 0.00 0.00 0.00 0.00 0.00 0.00
May 16014.58 01-MAY-09:09 20611.01 01-MAY-07:10 17206.63 01-MAY-07:10 0.00 0.00 0.00 0.00 0.00 0.00
June 16014.58 01-JUN-09:09 20611.01 01-JUN-07:10 17206.63 01-JUN-07:10 0.00 0.00 0.00 0.00 0.00 0.00
July 16014.58 03-JUL-09:09 20611.01 03-JUL-07:10 17206.63 03-JUL-07:10 0.00 0.00 0.00 0.00 0.00 0.00
August 16014.58 01-AUG-09:09 20611.01 01-AUG-07:10 17206.63 01-AUG-07:10 0.00 0.00 0.00 0.00 0.00 0.00
September 16014.58 01-SEP-09:09 20611.01 01-SEP-07:10 17206.63 01-SEP-07:10 0.00 0.00 0.00 0.00 0.00 0.00
October 16014.58 02-OCT-09:09 20611.01 02-OCT-07:10 17206.63 02-OCT-07:10 0.00 0.00 0.00 0.00 0.00 0.00
November 16014.58 01-NOV-09:09 20611.01 01-NOV-07:10 17206.63 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 0.00
December 16014.58 01-DEC-10:09 20611.01 01-DEC-08:09 17206.63 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average             0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 16014.58   20611.01   17206.63   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 16014.58   20611.01   17206.63   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: CORE_MID

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 16014.58 02-JAN-10:09 20611.01 02-JAN-08:09 17206.56 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 0.00
February 16014.58 01-FEB-10:09 20611.01 01-FEB-08:09 17206.56 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 0.00
March 16014.58 01-MAR-10:09 20611.01 01-MAR-08:09 17206.56 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 0.00
April 16014.58 03-APR-09:09 20611.01 03-APR-07:10 17206.56 03-APR-07:10 0.00 0.00 0.00 0.00 0.00 0.00
May 16014.58 01-MAY-09:09 20611.01 01-MAY-07:10 17206.56 01-MAY-07:10 0.00 0.00 0.00 0.00 0.00 0.00
June 16014.58 01-JUN-09:09 20611.01 01-JUN-07:10 17206.56 01-JUN-07:10 0.00 0.00 0.00 0.00 0.00 0.00
July 16014.58 03-JUL-09:09 20611.01 03-JUL-07:10 17206.56 03-JUL-07:10 0.00 0.00 0.00 0.00 0.00 0.00
August 16014.58 01-AUG-09:09 20611.01 01-AUG-07:10 17206.56 01-AUG-07:10 0.00 0.00 0.00 0.00 0.00 0.00
September 16014.58 01-SEP-09:09 20611.01 01-SEP-07:10 17206.56 01-SEP-07:10 0.00 0.00 0.00 0.00 0.00 0.00
October 16014.58 02-OCT-09:09 20611.01 02-OCT-07:10 17206.56 02-OCT-07:10 0.00 0.00 0.00 0.00 0.00 0.00
November 16014.58 01-NOV-09:09 20611.01 01-NOV-07:10 17206.56 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 0.00
December 16014.58 01-DEC-10:09 20611.01 01-DEC-08:09 17206.56 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average             0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 16014.58   20611.01   17206.56   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 16014.58   20611.01   17206.56   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: CORE_TOP

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 16014.58 02-JAN-10:09 20611.01 02-JAN-08:09 17206.56 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 0.00
February 16014.58 01-FEB-10:09 20611.01 01-FEB-08:09 17206.56 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 0.00
March 16014.58 01-MAR-10:09 20611.01 01-MAR-08:09 17206.56 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 0.00
April 16014.58 03-APR-09:09 20611.01 03-APR-07:10 17206.56 03-APR-07:10 0.00 0.00 0.00 0.00 0.00 0.00
May 16014.58 01-MAY-09:09 20611.01 01-MAY-07:10 17206.56 01-MAY-07:10 0.00 0.00 0.00 0.00 0.00 0.00
June 16014.58 01-JUN-09:09 20611.01 01-JUN-07:10 17206.56 01-JUN-07:10 0.00 0.00 0.00 0.00 0.00 0.00
July 16014.58 03-JUL-09:09 20611.01 03-JUL-07:10 17206.56 03-JUL-07:10 0.00 0.00 0.00 0.00 0.00 0.00
August 16014.58 01-AUG-09:09 20611.01 01-AUG-07:10 17206.56 01-AUG-07:10 0.00 0.00 0.00 0.00 0.00 0.00
September 16014.58 01-SEP-09:09 20611.01 01-SEP-07:10 17206.56 01-SEP-07:10 0.00 0.00 0.00 0.00 0.00 0.00
October 16014.58 02-OCT-09:09 20611.01 02-OCT-07:10 17206.56 02-OCT-07:10 0.00 0.00 0.00 0.00 0.00 0.00
November 16014.58 01-NOV-09:09 20611.01 01-NOV-07:10 17206.56 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 0.00
December 16014.58 01-DEC-10:09 20611.01 01-DEC-08:09 17206.56 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average             0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 16014.58   20611.01   17206.56   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 16014.58   20611.01   17206.56   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 2010.79 02-JAN-10:09 2587.92 03-JAN-08:09 2160.55 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 1685.23 07-JAN-18:10
February 2010.79 01-FEB-10:09 2587.92 01-FEB-08:09 2160.55 01-FEB-08:09 0.00 0.00 0.00 0.00 45.67 26-FEB-14:50 2061.67 12-FEB-01:00
March 2010.79 01-MAR-10:09 2587.92 21-MAR-07:10 2160.55 01-MAR-08:09 0.00 0.00 0.00 0.00 46.44 30-MAR-16:00 1357.21 22-MAR-03:00
April 2010.79 03-APR-09:09 2255.20 03-APR-07:10 2160.55 03-APR-07:10 0.00 0.00 0.00 0.00 79.82 16-APR-12:10 708.61 05-APR-04:53
May 2010.79 01-MAY-09:09 1470.28 02-MAY-07:10 2160.55 01-MAY-07:10 0.00 0.00 0.00 0.00 108.30 07-MAY-12:10 540.55 10-MAY-04:00
June 2010.79 01-JUN-09:09 1470.28 23-JUN-07:10 2160.55 01-JUN-07:10 0.00 0.00 0.00 0.00 320.83 11-JUN-15:00 394.38 07-JUN-03:00
July 2010.79 03-JUL-09:09 1803.00 27-JUL-07:10 2160.55 03-JUL-07:10 0.00 0.00 0.00 0.00 308.83 08-JUL-18:53 293.54 28-JUL-22:00
August 2010.79 01-AUG-09:09 2255.20 24-AUG-07:10 2160.55 01-AUG-07:10 0.00 0.00 0.00 0.00 317.55 06-AUG-14:00 157.48 31-AUG-05:00
September 2010.79 01-SEP-09:09 2587.92 29-SEP-07:10 2160.55 01-SEP-07:10 0.00 0.00 0.00 0.00 124.85 17-SEP-15:00 372.63 29-SEP-05:00
October 2010.79 02-OCT-09:09 2587.92 19-OCT-07:10 2160.55 02-OCT-07:10 0.00 0.00 0.00 0.00 102.61 08-OCT-14:00 806.07 28-OCT-04:00
November 2010.79 01-NOV-09:09 2587.92 01-NOV-07:10 2160.55 01-NOV-07:10 0.00 0.00 0.00 0.00 29.89 19-NOV-15:00 1151.13 21-NOV-04:00
December 2010.79 01-DEC-10:09 2587.92 06-DEC-08:09 2160.55 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 2016.81 17-DEC-03:53
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 2010.79   1470.28   2160.55   0.00 0.00 0.00 0.00 0.00   157.48  
Maximum of Months 2010.79   2587.92   2160.55   0.00 0.00 0.00 0.00 320.83   2061.67  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 1295.83 02-JAN-10:09 1667.75 03-JAN-08:09 1392.34 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 1108.49 07-JAN-18:10
February 1295.83 01-FEB-10:09 1667.75 01-FEB-08:09 1392.34 01-FEB-08:09 0.00 0.00 0.00 0.00 25.76 26-FEB-15:10 1358.90 12-FEB-01:00
March 1295.83 01-MAR-10:09 1667.75 21-MAR-07:10 1392.34 01-MAR-08:09 0.00 0.00 0.00 0.00 34.91 11-MAR-18:20 869.81 22-MAR-03:00
April 1295.83 03-APR-09:09 1453.34 03-APR-07:10 1392.34 03-APR-07:10 0.00 0.00 0.00 0.00 43.34 02-APR-16:55 449.71 05-APR-04:53
May 1295.83 01-MAY-09:09 870.51 02-MAY-07:10 1392.34 01-MAY-07:10 0.00 0.00 0.00 0.00 71.52 21-MAY-17:00 357.62 10-MAY-04:00
June 1295.83 01-JUN-09:09 793.52 01-JUN-07:10 1392.34 01-JUN-07:10 0.00 0.00 0.00 0.00 211.02 11-JUN-15:00 259.45 07-JUN-03:00
July 1295.83 03-JUL-09:09 947.51 27-JUL-07:10 1392.34 03-JUL-07:10 0.00 0.00 0.00 0.00 221.99 08-JUL-18:53 180.74 28-JUL-22:00
August 1295.83 01-AUG-09:09 1453.34 24-AUG-07:10 1392.34 01-AUG-07:10 0.00 0.00 0.00 0.00 216.34 06-AUG-14:00 84.27 31-AUG-05:00
September 1295.83 01-SEP-09:09 1453.34 05-SEP-07:10 1392.34 01-SEP-07:10 0.00 0.00 0.00 0.00 98.93 17-SEP-14:50 240.97 29-SEP-05:00
October 1295.83 02-OCT-09:09 1667.75 19-OCT-07:10 1392.34 02-OCT-07:10 0.00 0.00 0.00 0.00 65.08 09-OCT-15:40 520.54 28-OCT-04:00
November 1295.83 01-NOV-09:09 1667.75 01-NOV-07:10 1392.34 01-NOV-07:10 0.00 0.00 0.00 0.00 47.16 19-NOV-15:00 752.02 21-NOV-04:00
December 1295.83 01-DEC-10:09 1667.75 06-DEC-08:09 1392.34 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 1306.99 17-DEC-03:53
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 1295.83   793.52   1392.34   0.00 0.00 0.00 0.00 0.00   84.27  
Maximum of Months 1295.83   1667.75   1392.34   0.00 0.00 0.00 0.00 221.99   1358.90  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 2010.83 02-JAN-10:09 2587.98 03-JAN-08:09 2160.58 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 1672.08 07-JAN-18:03
February 2010.83 01-FEB-10:09 2587.98 01-FEB-08:09 2160.58 01-FEB-08:09 0.00 0.00 0.00 0.00 18.55 28-FEB-15:00 2047.61 11-FEB-18:55
March 2010.83 01-MAR-10:09 2587.98 21-MAR-07:10 2160.58 01-MAR-08:09 0.00 0.00 0.00 0.00 46.44 30-MAR-16:00 1305.05 22-MAR-03:00
April 2010.83 03-APR-09:09 2255.25 03-APR-07:10 2160.58 03-APR-07:10 0.00 0.00 0.00 0.00 39.19 16-APR-14:08 692.45 05-APR-04:53
May 2010.83 01-MAY-09:09 1803.04 24-MAY-07:10 2160.58 01-MAY-07:10 0.00 0.00 0.00 0.00 88.38 29-MAY-18:00 534.66 10-MAY-04:00
June 2010.83 01-JUN-09:09 1470.31 23-JUN-07:10 2160.58 01-JUN-07:10 0.00 0.00 0.00 0.00 313.68 11-JUN-15:00 392.48 07-JUN-03:00
July 2010.83 03-JUL-09:09 1803.04 27-JUL-07:10 2160.58 03-JUL-07:10 0.00 0.00 0.00 0.00 303.55 08-JUL-18:53 289.68 28-JUL-22:00
August 2010.83 01-AUG-09:09 2255.25 24-AUG-07:10 2160.58 01-AUG-07:10 0.00 0.00 0.00 0.00 295.04 06-AUG-13:55 160.84 31-AUG-05:00
September 2010.83 01-SEP-09:09 2587.98 29-SEP-07:10 2160.58 01-SEP-07:10 0.00 0.00 0.00 0.00 80.71 17-SEP-14:50 361.70 29-SEP-05:00
October 2010.83 02-OCT-09:09 2587.98 19-OCT-07:10 2160.58 02-OCT-07:10 0.00 0.00 0.00 0.00 43.80 09-OCT-15:36 800.20 28-OCT-04:00
November 2010.83 01-NOV-09:09 2587.98 01-NOV-07:10 2160.58 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 1171.32 07-NOV-02:00
December 2010.83 01-DEC-10:09 2587.98 06-DEC-08:09 2160.58 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 1950.16 17-DEC-03:53
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 2010.83   1470.31   2160.58   0.00 0.00 0.00 0.00 0.00   160.84  
Maximum of Months 2010.83   2587.98   2160.58   0.00 0.00 0.00 0.00 313.68   2047.61  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 1295.83 02-JAN-10:09 1667.75 03-JAN-08:09 1392.33 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 1160.85 07-JAN-18:10
February 1295.83 01-FEB-10:09 1667.75 01-FEB-08:09 1392.33 01-FEB-08:09 0.00 0.00 0.00 0.00 14.12 26-FEB-13:10 1480.06 11-FEB-18:13
March 1295.83 01-MAR-10:09 1667.75 16-MAR-07:10 1392.33 01-MAR-08:09 0.00 0.00 0.00 0.00 30.96 30-MAR-16:00 1005.27 22-MAR-03:00
April 1295.83 03-APR-09:09 1453.34 03-APR-07:10 1392.33 03-APR-07:10 0.00 0.00 0.00 0.00 36.10 16-APR-12:10 537.95 05-APR-04:53
May 1295.83 01-MAY-09:09 1453.34 24-MAY-07:10 1392.33 01-MAY-07:10 0.00 0.00 0.00 0.00 80.12 07-MAY-12:10 390.11 10-MAY-04:00
June 1295.83 01-JUN-09:09 1161.92 23-JUN-07:10 1392.33 01-JUN-07:10 0.00 0.00 0.00 0.00 181.99 25-JUN-16:00 305.79 07-JUN-03:00
July 1295.83 03-JUL-09:09 1453.34 27-JUL-07:10 1392.33 03-JUL-07:10 0.00 0.00 0.00 0.00 176.35 08-JUL-18:50 234.58 28-JUL-22:00
August 1295.83 01-AUG-09:09 1453.34 23-AUG-07:10 1392.33 01-AUG-07:10 0.00 0.00 0.00 0.00 196.98 06-AUG-13:55 152.35 31-AUG-05:00
September 1295.83 01-SEP-09:09 1667.75 29-SEP-07:10 1392.33 01-SEP-07:10 0.00 0.00 0.00 0.00 78.65 17-SEP-12:10 270.84 30-SEP-19:00
October 1295.83 02-OCT-09:09 1667.75 13-OCT-07:10 1392.33 02-OCT-07:10 0.00 0.00 0.00 0.00 32.93 09-OCT-14:56 599.63 28-OCT-04:00
November 1295.83 01-NOV-09:09 1667.75 01-NOV-07:10 1392.33 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 859.44 07-NOV-02:00
December 1295.83 01-DEC-10:09 1667.75 06-DEC-08:09 1392.33 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 1485.47 17-DEC-03:53
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 1295.83   1161.92   1392.33   0.00 0.00 0.00 0.00 0.00   152.35  
Maximum of Months 1295.83   1667.75   1392.33   0.00 0.00 0.00 0.00 196.98   1485.47  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 2010.79 02-JAN-10:09 2587.92 03-JAN-08:09 2160.55 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 3716.07 07-JAN-05:10
February 2010.79 01-FEB-10:09 2587.92 01-FEB-08:09 2160.55 01-FEB-08:09 0.00 0.00 0.00 0.00 283.66 26-FEB-12:54 4433.01 12-FEB-01:00
March 2010.79 01-MAR-10:09 2587.92 21-MAR-07:10 2160.55 01-MAR-08:09 0.00 0.00 0.00 0.00 162.34 11-MAR-18:03 2696.49 22-MAR-04:55
April 2010.79 03-APR-09:09 2255.20 03-APR-07:10 2160.55 03-APR-07:10 0.00 0.00 0.00 0.00 256.98 16-APR-12:00 1467.65 05-APR-04:53
May 2010.79 01-MAY-09:09 1470.28 02-MAY-07:10 2160.55 01-MAY-07:10 0.00 0.00 0.00 0.00 300.72 07-MAY-11:53 1154.15 10-MAY-04:00
June 2010.79 01-JUN-09:09 1470.28 23-JUN-07:10 2160.55 01-JUN-07:10 0.00 0.00 0.00 0.00 782.79 11-JUN-14:52 851.92 07-JUN-03:00
July 2010.79 03-JUL-09:09 1803.00 27-JUL-07:10 2160.55 03-JUL-07:10 0.00 0.00 0.00 0.00 718.90 08-JUL-18:53 605.70 28-JUL-22:00
August 2010.79 01-AUG-09:09 2255.20 24-AUG-07:10 2160.55 01-AUG-07:10 0.00 0.00 0.00 0.00 765.69 06-AUG-14:00 396.75 25-AUG-05:00
September 2010.79 01-SEP-09:09 2587.92 29-SEP-07:10 2160.55 01-SEP-07:10 0.00 0.00 0.00 0.00 319.07 17-SEP-15:00 777.07 29-SEP-05:00
October 2010.79 02-OCT-09:09 2587.92 19-OCT-07:10 2160.55 02-OCT-07:10 0.00 0.00 0.00 0.00 361.03 08-OCT-13:52 1542.77 28-OCT-04:00
November 2010.79 01-NOV-09:09 2587.92 01-NOV-07:10 2160.55 01-NOV-07:10 0.00 0.00 0.00 0.00 160.64 19-NOV-14:55 2548.62 30-NOV-22:03
December 2010.79 01-DEC-10:09 2587.92 06-DEC-08:09 2160.55 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 3746.34 17-DEC-03:53
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 2010.79   1470.28   2160.55   0.00 0.00 0.00 0.00 0.00   396.75  
Maximum of Months 2010.79   2587.92   2160.55   0.00 0.00 0.00 0.00 782.79   4433.01  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 1239.33 02-JAN-08:09 1667.75 03-JAN-08:09 1392.34 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 2477.43 07-JAN-05:09
February 1239.33 01-FEB-08:09 1667.75 01-FEB-08:09 1392.34 01-FEB-08:09 0.00 0.00 0.00 0.00 121.37 26-FEB-16:00 2955.49 12-FEB-01:00
March 1239.33 01-MAR-08:09 1667.75 21-MAR-07:10 1392.34 01-MAR-08:09 0.00 0.00 0.00 0.00 116.58 11-MAR-18:03 1797.78 22-MAR-04:57
April 1239.33 03-APR-07:10 1453.34 03-APR-07:10 1392.34 03-APR-07:10 0.00 0.00 0.00 0.00 122.39 08-APR-17:10 972.55 05-APR-04:53
May 1239.33 01-MAY-07:10 870.51 02-MAY-07:10 1392.34 01-MAY-07:10 0.00 0.00 0.00 0.00 167.15 29-MAY-18:00 773.13 10-MAY-04:00
June 1239.33 01-JUN-07:10 793.52 01-JUN-07:10 1392.34 01-JUN-07:10 0.00 0.00 0.00 0.00 489.63 11-JUN-15:10 580.42 07-JUN-03:00
July 1239.33 03-JUL-07:10 947.51 27-JUL-07:10 1392.34 03-JUL-07:10 0.00 0.00 0.00 0.00 498.72 08-JUL-18:53 396.27 01-JUL-20:00
August 1239.33 01-AUG-07:10 1453.34 24-AUG-07:10 1392.34 01-AUG-07:10 0.00 0.00 0.00 0.00 475.00 06-AUG-14:00 257.72 25-AUG-05:00
September 1239.33 01-SEP-07:10 1453.34 05-SEP-07:10 1392.34 01-SEP-07:10 0.00 0.00 0.00 0.00 236.58 17-SEP-15:20 507.28 29-SEP-05:00
October 1239.33 02-OCT-07:10 1667.75 19-OCT-07:10 1392.34 02-OCT-07:10 0.00 0.00 0.00 0.00 192.02 09-OCT-15:50 1021.76 28-OCT-04:00
November 1239.33 01-NOV-07:10 1667.75 01-NOV-07:10 1392.34 01-NOV-07:10 0.00 0.00 0.00 0.00 86.10 19-NOV-14:55 1697.50 30-NOV-22:03
December 1239.33 01-DEC-08:09 1667.75 06-DEC-08:09 1392.34 01-DEC-08:09 0.00 0.00 0.00 0.00 4.75 12-DEC-15:00 2494.57 17-DEC-03:53
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 1239.33   793.52   1392.34   0.00 0.00 0.00 0.00 0.00   257.72  
Maximum of Months 1239.33   1667.75   1392.34   0.00 0.00 0.00 0.00 498.72   2955.49  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 2010.83 02-JAN-10:09 2587.98 03-JAN-08:09 2160.58 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 3716.15 07-JAN-05:09
February 2010.83 01-FEB-10:09 2587.98 01-FEB-08:09 2160.58 01-FEB-08:09 0.00 0.00 0.00 0.00 38.76 28-FEB-15:00 4516.17 11-FEB-18:03
March 2010.83 01-MAR-10:09 2587.98 21-MAR-07:10 2160.58 01-MAR-08:09 0.00 0.00 0.00 0.00 105.78 30-MAR-16:00 2696.55 22-MAR-04:57
April 2010.83 03-APR-09:09 2255.25 03-APR-07:10 2160.58 03-APR-07:10 0.00 0.00 0.00 0.00 96.86 08-APR-17:10 1478.01 05-APR-04:53
May 2010.83 01-MAY-09:09 1803.04 24-MAY-07:10 2160.58 01-MAY-07:10 0.00 0.00 0.00 0.00 223.56 07-MAY-12:00 1172.73 10-MAY-04:00
June 2010.83 01-JUN-09:09 1470.31 23-JUN-07:10 2160.58 01-JUN-07:10 0.00 0.00 0.00 0.00 731.61 11-JUN-15:10 857.88 07-JUN-03:00
July 2010.83 03-JUL-09:09 1803.04 27-JUL-07:10 2160.58 03-JUL-07:10 0.00 0.00 0.00 0.00 701.95 08-JUL-18:53 609.42 28-JUL-22:00
August 2010.83 01-AUG-09:09 2255.25 24-AUG-07:10 2160.58 01-AUG-07:10 0.00 0.00 0.00 0.00 679.56 06-AUG-13:55 406.90 25-AUG-05:00
September 2010.83 01-SEP-09:09 2587.98 29-SEP-07:10 2160.58 01-SEP-07:10 0.00 0.00 0.00 0.00 158.82 06-SEP-12:00 782.78 29-SEP-05:00
October 2010.83 02-OCT-09:09 2587.98 19-OCT-07:10 2160.58 02-OCT-07:10 0.00 0.00 0.00 0.00 93.08 09-OCT-15:45 1650.75 28-OCT-04:00
November 2010.83 01-NOV-09:09 2587.98 01-NOV-07:10 2160.58 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 2550.07 30-NOV-22:03
December 2010.83 01-DEC-10:09 2587.98 06-DEC-08:09 2160.58 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 3883.45 17-DEC-03:53
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 2010.83   1470.31   2160.58   0.00 0.00 0.00 0.00 0.00   406.90  
Maximum of Months 2010.83   2587.98   2160.58   0.00 0.00 0.00 0.00 731.61   4516.17  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 1295.83 02-JAN-10:09 1667.75 03-JAN-08:09 1392.33 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 2477.44 07-JAN-05:10
February 1295.83 01-FEB-10:09 1667.75 01-FEB-08:09 1392.33 01-FEB-08:09 0.00 0.00 0.00 0.00 184.25 26-FEB-12:52 3134.22 11-FEB-18:03
March 1295.83 01-MAR-10:09 1667.75 16-MAR-07:10 1392.33 01-MAR-08:09 0.00 0.00 0.00 0.00 70.52 30-MAR-16:00 1797.67 22-MAR-04:57
April 1295.83 03-APR-09:09 1453.34 03-APR-07:10 1392.33 03-APR-07:10 0.00 0.00 0.00 0.00 169.24 16-APR-12:00 997.43 05-APR-04:53
May 1295.83 01-MAY-09:09 1453.34 24-MAY-07:19 1392.33 01-MAY-07:10 0.00 0.00 0.00 0.00 228.23 07-MAY-11:53 808.93 10-MAY-04:00
June 1295.83 01-JUN-09:09 1161.92 23-JUN-07:10 1392.33 01-JUN-07:10 0.00 0.00 0.00 0.00 426.97 11-JUN-15:05 605.57 07-JUN-03:00
July 1295.83 03-JUL-09:09 1453.34 27-JUL-07:10 1392.33 03-JUL-07:10 0.00 0.00 0.00 0.00 429.56 08-JUL-19:10 414.68 28-JUL-22:00
August 1295.83 01-AUG-09:09 1453.34 23-AUG-07:10 1392.33 01-AUG-07:10 0.00 0.00 0.00 0.00 490.26 06-AUG-14:00 287.13 25-AUG-05:00
September 1295.83 01-SEP-09:09 1667.75 29-SEP-07:10 1392.33 01-SEP-07:10 0.00 0.00 0.00 0.00 215.91 17-SEP-12:00 515.43 29-SEP-05:00
October 1295.83 02-OCT-09:09 1667.75 13-OCT-07:10 1392.33 02-OCT-07:10 0.00 0.00 0.00 0.00 163.74 08-OCT-13:52 1073.41 28-OCT-04:00
November 1295.83 01-NOV-09:09 1667.75 01-NOV-07:10 1392.33 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 1702.70 30-NOV-22:03
December 1295.83 01-DEC-10:09 1667.75 06-DEC-08:09 1392.33 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 2576.22 17-DEC-03:53
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 1295.83   1161.92   1392.33   0.00 0.00 0.00 0.00 0.00   287.13  
Maximum of Months 1295.83   1667.75   1392.33   0.00 0.00 0.00 0.00 490.26   3134.22  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 2010.79 02-JAN-10:09 2587.92 03-JAN-08:09 2160.55 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 4443.61 07-JAN-05:10
February 2010.79 01-FEB-10:09 2587.92 01-FEB-08:09 2160.55 01-FEB-08:09 0.00 0.00 0.00 0.00 470.09 26-FEB-13:00 5527.79 12-FEB-01:00
March 2010.79 01-MAR-10:09 2587.92 21-MAR-07:10 2160.55 01-MAR-08:09 0.00 0.00 0.00 0.00 223.50 11-MAR-18:03 3373.98 22-MAR-04:57
April 2010.79 03-APR-09:09 2255.20 03-APR-07:10 2160.55 03-APR-07:10 0.00 0.00 0.00 0.00 323.21 16-APR-11:58 1710.67 05-APR-04:53
May 2010.79 01-MAY-09:09 1470.28 02-MAY-07:10 2160.55 01-MAY-07:10 0.00 0.00 0.00 0.00 318.50 07-MAY-12:00 1321.73 10-MAY-04:00
June 2010.79 01-JUN-09:09 1470.28 23-JUN-07:10 2160.55 01-JUN-07:10 0.00 0.00 0.00 0.00 914.17 11-JUN-15:00 1043.53 07-JUN-03:00
July 2010.79 03-JUL-09:09 1803.00 27-JUL-07:10 2160.55 03-JUL-07:10 0.00 0.00 0.00 0.00 791.98 08-JUL-18:53 719.81 01-JUL-20:00
August 2010.79 01-AUG-09:09 2255.20 24-AUG-07:10 2160.55 01-AUG-07:10 0.00 0.00 0.00 0.00 857.29 06-AUG-14:00 473.70 25-AUG-05:00
September 2010.79 01-SEP-09:09 2587.92 29-SEP-07:10 2160.55 01-SEP-07:10 0.00 0.00 0.00 0.00 374.78 17-SEP-14:50 871.08 29-SEP-04:53
October 2010.79 02-OCT-09:09 2587.92 19-OCT-07:10 2160.55 02-OCT-07:10 0.00 0.00 0.00 0.00 491.43 08-OCT-14:00 1757.76 25-OCT-05:00
November 2010.79 01-NOV-09:09 2587.92 01-NOV-07:10 2160.55 01-NOV-07:10 0.00 0.00 0.00 0.00 429.29 19-NOV-14:55 3154.69 30-NOV-22:03
December 2010.79 01-DEC-10:09 2587.92 06-DEC-08:09 2160.55 01-DEC-08:09 0.00 0.00 0.00 0.00 28.88 10-DEC-15:40 4452.92 17-DEC-04:07
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 2010.79   1470.28   2160.55   0.00 0.00 0.00 0.00 0.00   473.70  
Maximum of Months 2010.79   2587.92   2160.55   0.00 0.00 0.00 0.00 914.17   5527.79  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 1295.83 02-JAN-10:09 1667.75 03-JAN-08:09 1392.34 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 3092.27 07-JAN-05:09
February 1295.83 01-FEB-10:09 1667.75 01-FEB-08:09 1392.34 01-FEB-08:09 0.00 0.00 0.00 0.00 193.79 26-FEB-15:42 3684.86 12-FEB-01:00
March 1295.83 01-MAR-10:09 1667.75 21-MAR-07:10 1392.34 01-MAR-08:09 0.00 0.00 0.00 0.00 154.86 11-MAR-18:03 2249.35 22-MAR-04:57
April 1295.83 03-APR-09:09 1453.34 03-APR-07:10 1392.34 03-APR-07:10 0.00 0.00 0.00 0.00 138.28 08-APR-17:10 1135.26 05-APR-04:53
May 1295.83 01-MAY-09:09 870.51 02-MAY-07:10 1392.34 01-MAY-07:10 0.00 0.00 0.00 0.00 181.94 29-MAY-17:42 888.24 10-MAY-04:00
June 1295.83 01-JUN-09:09 793.52 01-JUN-07:10 1392.34 01-JUN-07:10 0.00 0.00 0.00 0.00 562.59 11-JUN-15:30 713.07 07-JUN-03:00
July 1295.83 03-JUL-09:09 947.51 27-JUL-07:10 1392.34 03-JUL-07:10 0.00 0.00 0.00 0.00 554.28 08-JUL-18:50 511.27 01-JUL-20:00
August 1295.83 01-AUG-09:09 1453.34 24-AUG-07:10 1392.34 01-AUG-07:10 0.00 0.00 0.00 0.00 561.94 06-AUG-13:50 308.55 25-AUG-05:00
September 1295.83 01-SEP-09:09 1453.34 05-SEP-07:10 1392.34 01-SEP-07:10 0.00 0.00 0.00 0.00 279.43 17-SEP-14:50 571.82 29-SEP-04:53
October 1295.83 02-OCT-09:09 1667.75 19-OCT-07:10 1392.34 02-OCT-07:10 0.00 0.00 0.00 0.00 233.00 09-OCT-15:40 1171.73 25-OCT-04:57
November 1295.83 01-NOV-09:09 1667.75 01-NOV-07:10 1392.34 01-NOV-07:10 0.00 0.00 0.00 0.00 260.36 19-NOV-14:55 2100.64 30-NOV-22:03
December 1295.83 01-DEC-10:09 1667.75 06-DEC-08:09 1392.34 01-DEC-08:09 0.00 0.00 0.00 0.00 2.17 12-DEC-14:00 2985.05 17-DEC-04:07
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 1295.83   793.52   1392.34   0.00 0.00 0.00 0.00 0.00   308.55  
Maximum of Months 1295.83   1667.75   1392.34   0.00 0.00 0.00 0.00 562.59   3684.86  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 2010.83 02-JAN-10:09 2587.98 03-JAN-08:09 2160.58 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 4606.01 07-JAN-05:10
February 2010.83 01-FEB-10:09 2587.98 01-FEB-08:09 2160.58 01-FEB-08:09 0.00 0.00 0.00 0.00 42.25 28-FEB-15:00 5527.34 12-FEB-01:00
March 2010.83 01-MAR-10:09 2587.98 21-MAR-07:10 2160.58 01-MAR-08:09 0.00 0.00 0.00 0.00 127.46 30-MAR-16:00 3374.17 22-MAR-05:00
April 2010.83 03-APR-09:09 2255.25 03-APR-07:10 2160.58 03-APR-07:10 0.00 0.00 0.00 0.00 115.43 08-APR-17:10 1721.91 05-APR-04:53
May 2010.83 01-MAY-09:09 1803.04 24-MAY-07:10 2160.58 01-MAY-07:10 0.00 0.00 0.00 0.00 250.37 07-MAY-12:20 1345.19 10-MAY-04:00
June 2010.83 01-JUN-09:09 1470.31 23-JUN-07:10 2160.58 01-JUN-07:10 0.00 0.00 0.00 0.00 877.46 11-JUN-15:00 1051.10 07-JUN-03:00
July 2010.83 03-JUL-09:09 1803.04 27-JUL-07:10 2160.58 03-JUL-07:10 0.00 0.00 0.00 0.00 787.38 08-JUL-18:53 721.06 01-JUL-20:00
August 2010.83 01-AUG-09:09 2255.25 24-AUG-07:10 2160.58 01-AUG-07:10 0.00 0.00 0.00 0.00 829.16 06-AUG-13:55 485.56 25-AUG-05:00
September 2010.83 01-SEP-09:09 2587.98 29-SEP-07:10 2160.58 01-SEP-07:10 0.00 0.00 0.00 0.00 196.03 17-SEP-14:50 876.98 29-SEP-04:53
October 2010.83 02-OCT-09:09 2587.98 19-OCT-07:10 2160.58 02-OCT-07:10 0.00 0.00 0.00 0.00 102.19 10-OCT-16:00 1856.72 28-OCT-04:00
November 2010.83 01-NOV-09:09 2587.98 01-NOV-07:10 2160.58 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 3156.42 30-NOV-22:03
December 2010.83 01-DEC-10:09 2587.98 06-DEC-08:09 2160.58 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 4466.65 17-DEC-04:07
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 2010.83   1470.31   2160.58   0.00 0.00 0.00 0.00 0.00   485.56  
Maximum of Months 2010.83   2587.98   2160.58   0.00 0.00 0.00 0.00 877.46   5527.34  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 1295.83 02-JAN-10:09 1667.75 03-JAN-08:09 1392.33 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 3092.20 07-JAN-05:10
February 1295.83 01-FEB-10:09 1667.75 01-FEB-08:09 1392.33 01-FEB-08:09 0.00 0.00 0.00 0.00 286.93 26-FEB-13:00 3782.41 11-FEB-18:03
March 1295.83 01-MAR-10:09 1667.75 16-MAR-07:10 1392.33 01-MAR-08:09 0.00 0.00 0.00 0.00 84.97 30-MAR-16:00 2249.50 22-MAR-05:00
April 1295.83 03-APR-09:09 1453.34 03-APR-07:10 1392.33 03-APR-07:10 0.00 0.00 0.00 0.00 212.74 16-APR-11:58 1166.87 05-APR-04:53
May 1295.83 01-MAY-09:09 1453.34 24-MAY-07:19 1392.33 01-MAY-07:10 0.00 0.00 0.00 0.00 265.14 07-MAY-12:00 935.43 10-MAY-04:00
June 1295.83 01-JUN-09:09 1161.92 23-JUN-07:10 1392.33 01-JUN-07:10 0.00 0.00 0.00 0.00 512.53 25-JUN-16:00 741.10 07-JUN-03:00
July 1295.83 03-JUL-09:09 1453.34 27-JUL-07:10 1392.33 03-JUL-07:10 0.00 0.00 0.00 0.00 496.48 08-JUL-19:10 502.53 01-JUL-20:00
August 1295.83 01-AUG-09:09 1453.34 23-AUG-07:10 1392.33 01-AUG-07:10 0.00 0.00 0.00 0.00 570.29 06-AUG-13:55 344.58 25-AUG-05:00
September 1295.83 01-SEP-09:09 1667.75 29-SEP-07:10 1392.33 01-SEP-07:10 0.00 0.00 0.00 0.00 276.73 17-SEP-12:10 587.15 29-SEP-04:53
October 1295.83 02-OCT-09:09 1667.75 13-OCT-07:10 1392.33 02-OCT-07:10 0.00 0.00 0.00 0.00 226.36 08-OCT-13:52 1217.47 28-OCT-04:00
November 1295.83 01-NOV-09:09 1667.75 01-NOV-07:10 1392.33 01-NOV-07:10 0.00 0.00 0.00 0.00 35.72 11-NOV-13:00 2109.90 30-NOV-22:03
December 1295.83 01-DEC-10:09 1667.75 06-DEC-08:09 1392.33 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 2962.33 17-DEC-04:07
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 1295.83   1161.92   1392.33   0.00 0.00 0.00 0.00 0.00   344.58  
Maximum of Months 1295.83   1667.75   1392.33   0.00 0.00 0.00 0.00 570.29   3782.41  



Table of Contents

Report: PeakSpaceGainsMonthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 232.27 02-JAN-10:09 578.72 02-JAN-08:09 1948.61 01-JAN-00:10 0.00 0.00 0.00 0.00 0.00 0.00
February 232.27 01-FEB-10:09 578.72 01-FEB-08:09 3897.21 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00 0.00
March 232.27 01-MAR-10:09 578.72 01-MAR-08:09 7794.42 31-MAR-23:10 0.00 0.00 0.00 0.00 0.00 0.00
April 232.27 03-APR-09:09 578.72 03-APR-07:10 7794.42 01-APR-00:10 0.00 0.00 0.00 0.00 0.00 0.00
May 232.27 01-MAY-09:09 578.72 01-MAY-07:10 3897.21 31-MAY-23:10 0.00 0.00 0.00 0.00 0.00 0.00
June 232.27 01-JUN-09:09 578.72 01-JUN-07:10 5845.82 30-JUN-23:10 0.00 0.00 0.00 0.00 0.00 0.00
July 232.27 03-JUL-09:09 578.72 03-JUL-07:10 7794.42 31-JUL-23:10 0.00 0.00 0.00 0.00 0.00 0.00
August 232.27 01-AUG-09:09 578.72 01-AUG-07:10 7794.42 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00 0.00
September 232.27 01-SEP-09:09 578.72 01-SEP-07:10 3897.21 30-SEP-23:10 0.00 0.00 0.00 0.00 0.00 0.00
October 232.27 02-OCT-09:09 578.72 02-OCT-07:10 5845.82 31-OCT-23:10 0.00 0.00 0.00 0.00 0.00 0.00
November 232.27 01-NOV-09:09 578.72 01-NOV-07:10 5845.82 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00 0.00
December 232.27 01-DEC-10:09 578.72 01-DEC-08:09 7794.42 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average             0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 232.27   578.72   1948.61   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 232.27   578.72   7794.42   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: DATACENTER_MID_ZN_6

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 232.27 02-JAN-10:09 578.72 02-JAN-08:09 1948.61 01-JAN-00:10 0.00 0.00 0.00 0.00 0.00 0.00
February 232.27 01-FEB-10:09 578.72 01-FEB-08:09 3897.21 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00 0.00
March 232.27 01-MAR-10:09 578.72 01-MAR-08:09 7794.42 31-MAR-23:10 0.00 0.00 0.00 0.00 0.00 0.00
April 232.27 03-APR-09:09 578.72 03-APR-07:10 7794.42 01-APR-00:10 0.00 0.00 0.00 0.00 0.00 0.00
May 232.27 01-MAY-09:09 578.72 01-MAY-07:10 3897.21 31-MAY-23:10 0.00 0.00 0.00 0.00 0.00 0.00
June 232.27 01-JUN-09:09 578.72 01-JUN-07:10 5845.82 30-JUN-23:10 0.00 0.00 0.00 0.00 0.00 0.00
July 232.27 03-JUL-09:09 578.72 03-JUL-07:10 7794.42 31-JUL-23:10 0.00 0.00 0.00 0.00 0.00 0.00
August 232.27 01-AUG-09:09 578.72 01-AUG-07:10 7794.42 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00 0.00
September 232.27 01-SEP-09:09 578.72 01-SEP-07:10 3897.21 30-SEP-23:10 0.00 0.00 0.00 0.00 0.00 0.00
October 232.27 02-OCT-09:09 578.72 02-OCT-07:10 5845.82 31-OCT-23:10 0.00 0.00 0.00 0.00 0.00 0.00
November 232.27 01-NOV-09:09 578.72 01-NOV-07:10 5845.82 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00 0.00
December 232.27 01-DEC-10:09 578.72 01-DEC-08:09 7794.42 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average             0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 232.27   578.72   1948.61   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 232.27   578.72   7794.42   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 232.27 02-JAN-10:09 578.72 02-JAN-08:09 1948.61 01-JAN-00:10 0.00 0.00 0.00 0.00 0.00 0.00
February 232.27 01-FEB-10:09 578.72 01-FEB-08:09 3897.21 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00 0.00
March 232.27 01-MAR-10:09 578.72 01-MAR-08:09 7794.42 31-MAR-23:10 0.00 0.00 0.00 0.00 0.00 0.00
April 232.27 03-APR-09:09 578.72 03-APR-07:10 7794.42 01-APR-00:10 0.00 0.00 0.00 0.00 0.00 0.00
May 232.27 01-MAY-09:09 578.72 01-MAY-07:10 3897.21 31-MAY-23:10 0.00 0.00 0.00 0.00 0.00 0.00
June 232.27 01-JUN-09:09 578.72 01-JUN-07:10 5845.82 30-JUN-23:10 0.00 0.00 0.00 0.00 0.00 0.00
July 232.27 03-JUL-09:09 578.72 03-JUL-07:10 7794.42 31-JUL-23:10 0.00 0.00 0.00 0.00 0.00 0.00
August 232.27 01-AUG-09:09 578.72 01-AUG-07:10 7794.42 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00 0.00
September 232.27 01-SEP-09:09 578.72 01-SEP-07:10 3897.21 30-SEP-23:10 0.00 0.00 0.00 0.00 0.00 0.00
October 232.27 02-OCT-09:09 578.72 02-OCT-07:10 5845.82 31-OCT-23:10 0.00 0.00 0.00 0.00 0.00 0.00
November 232.27 01-NOV-09:09 578.72 01-NOV-07:10 5845.82 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00 0.00
December 232.27 01-DEC-10:09 578.72 01-DEC-08:09 7794.42 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average             0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 232.27   578.72   1948.61   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 232.27   578.72   7794.42   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 5027.92 02-JAN-10:09 6471.01 02-JAN-08:09 94908.13 01-JAN-00:10 0.00 0.00 0.00 0.00 0.00 0.00
February 5027.92 01-FEB-10:09 6471.01 01-FEB-08:09 189816.26 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00 0.00
March 5027.92 01-MAR-10:09 6471.01 01-MAR-08:09 379632.52 31-MAR-23:10 0.00 0.00 0.00 0.00 0.00 0.00
April 5027.92 03-APR-09:09 6471.01 03-APR-07:10 379632.52 01-APR-00:10 0.00 0.00 0.00 0.00 0.00 0.00
May 5027.92 01-MAY-09:09 6471.01 01-MAY-07:10 189816.26 31-MAY-23:10 0.00 0.00 0.00 0.00 0.00 0.00
June 5027.92 01-JUN-09:09 6471.01 01-JUN-07:10 284724.39 30-JUN-23:10 0.00 0.00 0.00 0.00 0.00 0.00
July 5027.92 03-JUL-09:09 6471.01 03-JUL-07:10 379632.52 31-JUL-23:10 0.00 0.00 0.00 0.00 0.00 0.00
August 5027.92 01-AUG-09:09 6471.01 01-AUG-07:10 379632.52 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00 0.00
September 5027.92 01-SEP-09:09 6471.01 01-SEP-07:10 189816.26 30-SEP-23:10 0.00 0.00 0.00 0.00 0.00 0.00
October 5027.92 02-OCT-09:09 6471.01 02-OCT-07:10 284724.39 31-OCT-23:10 0.00 0.00 0.00 0.00 0.00 0.00
November 5027.92 01-NOV-09:09 6471.01 01-NOV-07:10 284724.39 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00 0.00
December 5027.92 01-DEC-10:09 6471.01 01-DEC-08:09 379632.52 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average             0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 5027.92   6471.01   94908.13   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 5027.92   6471.01   379632.52   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: GROUNDFLOOR_PLENUM

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 3762.98 07-JAN-18:03
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 21.95 26-FEB-14:52 4705.26 12-FEB-01:00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 73.55 30-MAR-16:00 3019.75 22-MAR-03:00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 123.95 16-APR-13:52 1541.92 05-APR-04:57
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 209.21 07-MAY-11:53 1209.99 10-MAY-04:00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 647.00 11-JUN-15:00 833.00 07-JUN-03:00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 630.84 08-JUL-18:53 601.71 28-JUL-24:00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 676.01 06-AUG-14:00 360.91 25-AUG-04:53
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 232.85 17-SEP-15:00 836.04 29-SEP-05:00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 132.19 09-OCT-16:00 1769.90 28-OCT-04:00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 2587.53 21-NOV-04:00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 4553.54 17-DEC-03:53
                       
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00        
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00   360.91  
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 676.01   4705.26  



Table of Contents

Report: PeakSpaceGainsMonthly

For: MIDFLOOR_PLENUM

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 6390.87 07-JAN-18:03
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 177.11 26-FEB-15:00 7771.87 12-FEB-01:00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 168.15 11-MAR-16:00 4958.96 22-MAR-03:00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 298.41 16-APR-12:00 2623.93 05-APR-04:53
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 428.89 07-MAY-12:10 2120.10 10-MAY-04:00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1271.62 11-JUN-14:52 1444.00 07-JUN-03:00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1168.22 08-JUL-18:53 1036.34 28-JUL-22:00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1260.00 06-AUG-14:00 689.35 25-AUG-05:00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 482.31 17-SEP-15:00 1458.73 29-SEP-05:00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 375.89 09-OCT-16:00 2934.26 28-OCT-04:00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 223.12 19-NOV-14:55 4358.14 21-NOV-04:00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 7423.67 17-DEC-03:53
                       
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00        
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00   689.35  
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1271.62   7771.87  



Table of Contents

Report: PeakSpaceGainsMonthly

For: TOPFLOOR_PLENUM

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 7063.63 07-JAN-18:03
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 213.36 26-FEB-13:13 8388.46 11-FEB-18:03
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 157.01 11-MAR-16:00 4822.65 22-MAR-05:00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 223.37 16-APR-11:53 2764.26 05-APR-04:53
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 276.54 29-MAY-18:00 2092.49 10-MAY-04:00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1087.20 11-JUN-15:00 1628.97 07-JUN-03:00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1073.99 08-JUL-18:53 1128.03 01-JUL-20:00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1035.65 06-AUG-14:00 731.62 23-AUG-05:00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 330.92 17-SEP-15:00 1359.63 29-SEP-04:53
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 314.49 08-OCT-14:00 2920.15 28-OCT-04:00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 483.24 19-NOV-14:55 4564.25 30-NOV-22:03
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 7008.81 17-DEC-03:53
                       
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00        
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00   731.62  
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1087.20   8388.46  



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: BASEMENT

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 117755.26 02-JAN-05:11 0.00 25501.32 134575.44 0.00 0.00 0.00 0.00 0.00 0.00
February 119279.88 21-FEB-05:11 0.00 20401.06 107660.35 0.00 0.00 0.00 0.00 0.00 0.00
March 116375.27 06-MAR-05:11 0.00 20401.06 107660.35 0.00 0.00 0.00 0.00 0.00 0.00
April 113953.56 10-APR-04:12 0.00 15300.79 80745.26 0.00 0.00 0.00 0.00 0.00 0.00
May 112130.78 15-MAY-04:12 0.00 10200.53 53830.18 0.00 0.00 0.00 0.00 0.00 0.00
June 111458.60 08-JUN-04:12 0.00 12750.66 67287.72 0.00 0.00 0.00 0.00 0.00 0.00
July 97170.68 03-JUL-04:23 0.00 7650.40 40372.63 0.00 0.00 0.00 0.00 0.00 0.00
August 93509.31 26-AUG-04:12 0.00 5099.69 53830.18 0.00 0.00 0.00 0.00 0.00 0.00
September 113311.09 14-SEP-04:12 0.00 12750.66 67287.72 0.00 0.00 0.00 0.00 0.00 0.00
October 120516.13 30-OCT-04:11 0.00 17850.93 94202.81 0.00 0.00 0.00 0.00 0.00 0.00
November 117080.44 06-NOV-05:12 0.00 15300.79 80745.26 0.00 0.00 0.00 0.00 0.00 0.00
December 119360.14 11-DEC-05:11 0.00 25501.32 134575.44 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 93509.31   0.00 5099.69 40372.63 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 120516.13   0.00 25501.32 134575.44 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: CORE_BOTTOM

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 92999.03 02-JAN-05:11 0.00 22901.98 59376.45 0.00 0.00 0.00 0.00 0.00 0.00
February 92429.04 21-FEB-05:11 0.00 18321.59 47501.16 0.00 0.00 0.00 0.00 0.00 0.00
March 93461.30 06-MAR-05:11 0.00 18321.59 47501.16 0.00 0.00 0.00 0.00 0.00 0.00
April 95150.35 14-APR-04:13 0.00 16031.39 41563.52 0.00 0.00 0.00 0.00 0.00 0.00
May 99086.11 30-MAY-04:13 0.00 13741.19 35625.87 0.00 0.00 0.00 0.00 0.00 0.00
June 99664.12 20-JUN-04:13 0.00 16031.39 41563.52 0.00 0.00 0.00 0.00 0.00 0.00
July 99025.80 01-JUL-04:13 0.00 8014.80 31172.64 0.00 0.00 0.00 0.00 0.00 0.00
August 81011.87 31-AUG-04:22 0.00 11450.99 29688.23 0.00 0.00 0.00 0.00 0.00 0.00
September 99855.04 11-SEP-04:13 0.00 13741.19 35625.87 0.00 0.00 0.00 0.00 0.00 0.00
October 97918.84 10-OCT-04:13 0.00 13741.19 35625.87 0.00 0.00 0.00 0.00 0.00 0.00
November 98819.34 13-NOV-05:11 0.00 20611.78 53438.81 0.00 0.00 0.00 0.00 0.00 0.00
December 94600.23 26-DEC-05:11 0.00 22901.98 59376.45 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 81011.87   0.00 8014.80 29688.23 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 99855.04   0.00 22901.98 59376.45 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: CORE_MID

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 71873.87 26-JAN-10:20 80072.90 103055.07 86032.81 0.00 0.00 0.00 0.00 0.00 0.00
February 76309.38 28-FEB-06:02 8061.19 11450.99 38236.81 0.00 0.00 0.00 0.00 0.00 0.00
March 83953.56 31-MAR-04:12 0.00 13741.19 35625.74 0.00 0.00 0.00 0.00 0.00 0.00
April 84631.49 19-APR-04:12 0.00 13741.19 35625.74 0.00 0.00 0.00 0.00 0.00 0.00
May 85174.37 31-MAY-04:12 0.00 11450.99 29688.11 0.00 0.00 0.00 0.00 0.00 0.00
June 86897.76 21-JUN-04:11 0.00 16031.39 41563.36 0.00 0.00 0.00 0.00 0.00 0.00
July 86779.77 28-JUL-04:11 0.00 16031.39 41563.36 0.00 0.00 0.00 0.00 0.00 0.00
August 85261.99 25-AUG-04:12 0.00 9160.79 23750.49 0.00 0.00 0.00 0.00 0.00 0.00
September 86625.46 01-SEP-04:11 0.00 16031.39 41563.36 0.00 0.00 0.00 0.00 0.00 0.00
October 84030.19 19-OCT-04:12 0.00 13741.19 35625.74 0.00 0.00 0.00 0.00 0.00 0.00
November 78394.66 10-NOV-06:02 8061.19 11450.99 38236.81 0.00 0.00 0.00 0.00 0.00 0.00
December 67912.21 14-DEC-06:03 6448.95 9160.79 30589.44 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 67912.21   0.00 9160.79 23750.49 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 86897.76   80072.90 103055.07 86032.81 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: CORE_TOP

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 25778.01 20-JAN-17:00 15316.26 20611.01 17206.56 0.00 0.00 0.00 0.00 0.00 0.00
February 35768.98 28-FEB-17:00 15316.26 20611.01 17206.56 0.00 0.00 0.00 0.00 0.00 0.00
March 81761.47 31-MAR-05:02 8061.19 11450.99 38236.81 0.00 0.00 0.00 0.00 0.00 0.00
April 81878.24 19-APR-05:02 8061.19 11450.99 38236.81 0.00 0.00 0.00 0.00 0.00 0.00
May 84727.51 19-MAY-04:12 0.00 11450.99 29688.11 0.00 0.00 0.00 0.00 0.00 0.00
June 86137.86 16-JUN-04:11 0.00 16031.39 41563.36 0.00 0.00 0.00 0.00 0.00 0.00
July 85688.56 12-JUL-04:12 0.00 13741.19 35625.74 0.00 0.00 0.00 0.00 0.00 0.00
August 84538.62 03-AUG-03:02 0.00 5724.85 29688.11 0.00 0.00 0.00 0.00 0.00 0.00
September 84678.66 06-SEP-04:12 0.00 13741.19 35625.74 0.00 0.00 0.00 0.00 0.00 0.00
October 83441.85 19-OCT-04:12 0.00 13741.19 35625.74 0.00 0.00 0.00 0.00 0.00 0.00
November 36812.64 04-NOV-05:03 6448.95 9160.79 30589.44 0.00 0.00 0.00 0.00 0.00 0.00
December 32397.60 13-DEC-17:00 15316.26 20611.01 17206.56 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 25778.01   0.00 5724.85 17206.56 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 86137.86   15316.26 20611.01 41563.36 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 3668.86 31-JAN-15:00 2010.79 1350.81 2160.55 0.00 0.00 0.00 0.00 0.00 28.97
February 6320.36 28-FEB-15:00 2010.79 1231.33 2160.55 0.00 0.00 0.00 0.00 18.55 0.00
March 7908.17 30-MAR-14:00 2010.79 1231.33 2160.55 0.00 0.00 0.00 0.00 36.77 0.00
April 8497.66 18-APR-14:00 2010.79 1231.33 2160.55 0.00 0.00 0.00 0.00 8.20 0.00
May 13285.93 30-MAY-04:12 0.00 1725.34 4473.37 0.00 0.00 0.00 0.00 0.00 76.70
June 13741.55 20-JUN-04:11 0.00 2012.90 5218.93 0.00 0.00 0.00 0.00 0.00 124.15
July 14292.00 17-JUL-04:12 0.00 1725.34 4473.37 0.00 0.00 0.00 0.00 0.00 37.68
August 13219.63 21-AUG-05:02 1214.60 1725.34 5761.47 0.00 0.00 0.00 0.00 0.00 14.06
September 13968.24 01-SEP-04:11 0.00 2012.90 5218.93 0.00 0.00 0.00 0.00 0.00 83.71
October 13350.02 19-OCT-04:12 0.00 1725.34 4473.37 0.00 0.00 0.00 0.00 0.00 123.01
November 5928.28 02-NOV-13:50 2010.79 1231.33 2160.55 0.00 0.00 0.00 0.00 0.00 7.33
December 5562.81 13-DEC-12:00 1923.11 1231.33 2160.55 0.00 0.00 0.00 0.00 0.00 28.75
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 3668.86   0.00 1231.33 2160.55 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 14292.00   2010.79 2012.90 5761.47 0.00 0.00 0.00 0.00 36.77 124.15



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 3174.77 24-JAN-10:30 1295.83 793.52 1392.34 0.00 0.00 0.00 0.00 0.00 94.66
February 7192.47 27-FEB-09:40 1239.33 793.52 1392.34 0.00 0.00 0.00 0.00 0.00 63.24
March 8589.53 26-MAR-10:23 260.91 176.32 1856.46 0.00 0.00 0.00 0.00 0.00 152.21
April 16930.54 16-APR-10:43 260.91 176.32 1856.46 0.00 0.00 0.00 0.00 0.00 16.54
May 17635.52 29-MAY-09:43 260.91 176.32 1856.46 0.00 0.00 0.00 0.00 0.00 27.49
June 20029.05 04-JUN-09:02 391.37 264.49 2784.68 0.00 0.00 0.00 0.00 0.00 31.97
July 19452.84 23-JUL-09:22 326.14 220.40 2320.57 0.00 0.00 0.00 0.00 0.00 20.17
August 18414.67 13-AUG-08:32 260.91 176.32 1856.46 0.00 0.00 0.00 0.00 0.00 16.95
September 18504.47 24-SEP-09:02 260.91 176.32 1856.46 0.00 0.00 0.00 0.00 0.00 39.01
October 14006.48 09-OCT-10:13 260.91 176.32 1856.46 0.00 0.00 0.00 0.00 0.00 63.94
November 6772.69 06-NOV-09:25 2478.65 1587.03 2784.68 0.00 0.00 0.00 0.00 0.00 62.39
December 3613.65 08-DEC-10:10 2591.66 1587.03 2784.68 0.00 0.00 0.00 0.00 0.00 188.97
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 3174.77   260.91 176.32 1392.34 0.00 0.00 0.00 0.00 0.00 16.54
Maximum of Months 20029.05   2591.66 1587.03 2784.68 0.00 0.00 0.00 0.00 0.00 188.97



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 17701.14 29-JAN-13:33 303.66 205.21 2160.58 0.00 0.00 0.00 0.00 0.00 454.28
February 22138.58 26-FEB-13:42 506.09 342.02 3600.97 0.00 0.00 0.00 0.00 0.00 132.22
March 20528.88 26-MAR-13:32 404.87 273.61 2880.78 0.00 0.00 0.00 0.00 0.00 282.81
April 15180.48 16-APR-13:23 404.87 273.61 2880.78 0.00 0.00 0.00 0.00 25.39 0.00
May 15204.67 30-MAY-04:12 0.00 1725.38 4473.43 0.00 0.00 0.00 0.00 0.00 75.39
June 15823.54 19-JUN-04:12 0.00 1725.38 4473.43 0.00 0.00 0.00 0.00 0.00 99.37
July 17838.08 16-JUL-15:12 607.31 410.42 4321.17 0.00 0.00 0.00 0.00 158.25 0.00
August 21366.56 20-AUG-13:42 506.09 342.02 3600.97 0.00 0.00 0.00 0.00 66.88 0.00
September 21393.16 24-SEP-11:43 404.87 273.61 2880.78 0.00 0.00 0.00 0.00 23.17 0.00
October 22775.91 09-OCT-14:12 607.31 410.42 4321.17 0.00 0.00 0.00 0.00 0.00 21.49
November 22385.03 12-NOV-14:12 506.09 342.02 3600.97 0.00 0.00 0.00 0.00 0.00 129.27
December 21271.55 10-DEC-12:43 404.87 273.61 2880.78 0.00 0.00 0.00 0.00 0.00 172.85
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 15180.48   0.00 205.21 2160.58 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 22775.91   607.31 1725.38 4473.43 0.00 0.00 0.00 0.00 158.25 454.28



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 5620.44 23-JAN-16:30 1239.33 793.52 1392.33 0.00 0.00 0.00 0.00 0.00 104.29
February 20885.02 26-FEB-15:42 326.14 220.40 2320.55 0.00 0.00 0.00 0.00 0.00 57.62
March 19572.29 30-MAR-04:12 0.00 1111.88 2882.79 0.00 0.00 0.00 0.00 0.00 141.24
April 24158.98 09-APR-16:32 391.37 264.49 2784.67 0.00 0.00 0.00 0.00 0.00 41.12
May 23702.32 29-MAY-15:42 326.14 220.40 2320.55 0.00 0.00 0.00 0.00 20.75 0.00
June 25886.29 11-JUN-15:51 456.59 308.57 3248.78 0.00 0.00 0.00 0.00 106.69 0.00
July 24824.01 09-JUL-16:41 456.59 308.57 3248.78 0.00 0.00 0.00 0.00 100.20 0.00
August 25616.70 13-AUG-16:31 456.59 308.57 3248.78 0.00 0.00 0.00 0.00 42.03 0.00
September 23593.98 04-SEP-17:02 0.00 220.40 1801.74 0.00 0.00 0.00 0.00 9.43 0.00
October 23735.94 22-OCT-15:32 326.14 220.40 2320.55 0.00 0.00 0.00 0.00 0.00 77.29
November 19654.22 12-NOV-14:52 326.14 220.40 2320.55 0.00 0.00 0.00 0.00 0.00 66.62
December 19745.06 13-DEC-05:12 0.00 1111.88 2882.79 0.00 0.00 0.00 0.00 0.00 149.67
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 5620.44   0.00 220.40 1392.33 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 25886.29   1239.33 1111.88 3248.78 0.00 0.00 0.00 0.00 106.69 149.67



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 2808.25 31-JAN-17:00 1923.11 1803.00 2160.55 0.00 0.00 0.00 0.00 0.00 49.75
February 4000.67 28-FEB-15:00 2010.79 1231.33 2160.55 0.00 0.00 0.00 0.00 38.76 0.00
March 6550.97 30-MAR-15:50 1923.11 1231.33 2160.55 0.00 0.00 0.00 0.00 104.55 0.00
April 7130.54 19-APR-14:30 1923.11 1231.33 2160.55 0.00 0.00 0.00 0.00 48.91 0.00
May 8887.42 30-MAY-15:00 1923.11 1231.33 2160.55 0.00 0.00 0.00 0.00 92.33 0.00
June 16382.18 25-JUN-16:11 809.73 547.22 5761.47 0.00 0.00 0.00 0.00 584.57 0.00
July 15604.29 16-JUL-13:32 404.87 273.61 2880.74 0.00 0.00 0.00 0.00 320.40 0.00
August 12602.33 16-AUG-04:12 0.00 1437.79 3727.80 0.00 0.00 0.00 0.00 0.00 80.60
September 11781.71 11-SEP-05:02 1012.16 1437.79 4801.23 0.00 0.00 0.00 0.00 0.00 5.61
October 6438.44 02-OCT-14:30 1923.11 1231.33 2160.55 0.00 0.00 0.00 0.00 53.21 0.00
November 3736.19 20-NOV-14:20 2010.79 1231.33 2160.55 0.00 0.00 0.00 0.00 0.00 557.09
December 3058.81 13-DEC-15:10 1923.11 1470.28 2160.55 0.00 0.00 0.00 0.00 0.00 68.08
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 2808.25   0.00 273.61 2160.55 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 16382.18   2010.79 1803.00 5761.47 0.00 0.00 0.00 0.00 584.57 557.09



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 2772.50 11-JAN-10:15 0.00 1587.03 2784.68 0.00 0.00 0.00 0.00 0.00 145.49
February 4966.52 27-FEB-10:00 1239.33 793.52 1392.34 0.00 0.00 0.00 0.00 0.00 130.58
March 6442.37 13-MAR-10:20 1239.33 793.52 1392.34 0.00 0.00 0.00 0.00 0.00 89.95
April 18169.77 16-APR-10:53 260.91 176.32 1856.46 0.00 0.00 0.00 0.00 0.00 24.00
May 20007.62 07-MAY-09:02 326.14 220.40 2320.57 0.00 0.00 0.00 0.00 0.00 188.28
June 20935.64 04-JUN-09:52 391.37 264.49 2784.68 0.00 0.00 0.00 0.00 0.00 37.13
July 20750.77 04-JUL-09:42 391.37 264.49 2784.68 0.00 0.00 0.00 0.00 0.00 36.84
August 21300.62 27-AUG-09:41 456.59 308.57 3248.80 0.00 0.00 0.00 0.00 0.00 23.68
September 19578.18 24-SEP-10:12 326.14 220.40 2320.57 0.00 0.00 0.00 0.00 0.00 22.55
October 7520.66 11-OCT-10:10 1239.33 793.52 1392.34 0.00 0.00 0.00 0.00 0.00 13.46
November 4173.29 06-NOV-09:50 1239.33 793.52 1392.34 0.00 0.00 0.00 0.00 0.00 152.35
December 2801.80 07-DEC-10:25 0.00 1587.03 2784.68 0.00 0.00 0.00 0.00 0.00 229.35
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 2772.50   0.00 176.32 1392.34 0.00 0.00 0.00 0.00 0.00 13.46
Maximum of Months 21300.62   1239.33 1587.03 3248.80 0.00 0.00 0.00 0.00 0.00 229.35



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 16657.78 29-JAN-13:33 303.66 205.21 2160.58 0.00 0.00 0.00 0.00 0.00 1073.94
February 20383.11 26-FEB-12:32 404.87 273.61 2880.78 0.00 0.00 0.00 0.00 0.00 412.42
March 15754.79 26-MAR-15:02 404.87 273.61 2880.78 0.00 0.00 0.00 0.00 0.00 673.17
April 20019.47 16-APR-13:32 404.87 273.61 2880.78 0.00 0.00 0.00 0.00 57.26 0.00
May 13733.47 29-MAY-14:12 506.09 342.02 3600.97 0.00 0.00 0.00 0.00 40.91 0.00
June 19529.11 25-JUN-16:11 809.75 547.23 5761.56 0.00 0.00 0.00 0.00 572.26 0.00
July 18774.53 16-JUL-12:53 404.87 273.61 2880.78 0.00 0.00 0.00 0.00 438.56 0.00
August 20200.24 27-AUG-13:02 404.87 273.61 2880.78 0.00 0.00 0.00 0.00 332.55 0.00
September 21219.76 24-SEP-12:52 506.09 342.02 3600.97 0.00 0.00 0.00 0.00 65.93 0.00
October 21657.50 08-OCT-14:02 506.09 342.02 3600.97 0.00 0.00 0.00 0.00 0.00 123.41
November 20724.89 11-NOV-12:02 404.87 273.61 2880.78 0.00 0.00 0.00 0.00 0.00 613.03
December 20524.72 10-DEC-13:43 404.87 273.61 2880.78 0.00 0.00 0.00 0.00 0.00 386.88
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 13733.47   303.66 205.21 2160.58 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 21657.50   809.75 547.23 5761.56 0.00 0.00 0.00 0.00 572.26 1073.94



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 3098.85 10-JAN-17:33 1174.10 2779.57 2320.55 0.00 0.00 0.00 0.00 0.00 152.21
February 7654.55 27-FEB-17:00 1239.33 793.52 1392.33 0.00 0.00 0.00 0.00 0.00 10.89
March 10689.31 30-MAR-16:00 1239.33 793.52 1392.33 0.00 0.00 0.00 0.00 70.52 0.00
April 20108.12 09-APR-17:12 0.00 264.49 2162.09 0.00 0.00 0.00 0.00 0.00 103.25
May 21588.44 21-MAY-17:22 0.00 264.49 2162.09 0.00 0.00 0.00 0.00 0.00 131.84
June 22533.81 25-JUN-16:11 521.82 352.65 3712.89 0.00 0.00 0.00 0.00 261.66 0.00
July 22898.99 23-JUL-17:11 0.00 352.65 2882.79 0.00 0.00 0.00 0.00 41.88 0.00
August 22052.04 27-AUG-16:21 456.59 308.57 3248.78 0.00 0.00 0.00 0.00 159.02 0.00
September 18045.08 24-SEP-16:52 391.37 264.49 2784.67 0.00 0.00 0.00 0.00 19.20 0.00
October 15664.16 08-OCT-16:42 391.37 264.49 2784.67 0.00 0.00 0.00 0.00 0.00 3.53
November 7067.99 06-NOV-16:00 1239.33 793.52 1392.33 0.00 0.00 0.00 0.00 0.00 77.92
December 3795.86 11-DEC-15:50 1239.33 793.52 1392.33 0.00 0.00 0.00 0.00 0.00 33.81
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 3098.85   0.00 264.49 1392.33 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 22898.99   1239.33 2779.57 3712.89 0.00 0.00 0.00 0.00 261.66 152.21



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 2864.31 20-JAN-16:20 1923.11 1350.81 2160.55 0.00 0.00 0.00 0.00 0.00 167.27
February 3698.96 28-FEB-15:30 1923.11 1231.33 2160.55 0.00 0.00 0.00 0.00 0.00 2.99
March 7383.83 30-MAR-15:50 1923.11 1231.33 2160.55 0.00 0.00 0.00 0.00 125.98 0.00
April 7765.51 19-APR-14:30 1923.11 1231.33 2160.55 0.00 0.00 0.00 0.00 57.48 0.00
May 10007.14 30-MAY-15:00 1923.11 1231.33 2160.55 0.00 0.00 0.00 0.00 112.71 0.00
June 19367.51 25-JUN-16:11 809.73 547.22 5761.47 0.00 0.00 0.00 0.00 639.73 0.00
July 18821.52 16-JUL-13:32 404.87 273.61 2880.74 0.00 0.00 0.00 0.00 376.92 0.00
August 17489.10 06-AUG-16:21 708.51 478.82 5041.29 0.00 0.00 0.00 0.00 616.77 0.00
September 13376.24 07-SEP-05:02 1012.16 1437.79 4801.23 0.00 0.00 0.00 0.00 0.00 28.26
October 6815.16 02-OCT-14:40 1923.11 1231.33 2160.55 0.00 0.00 0.00 0.00 67.59 0.00
November 3267.42 02-NOV-15:50 1923.11 1350.81 2160.55 0.00 0.00 0.00 0.00 0.00 48.22
December 3080.28 13-DEC-15:10 1923.11 1470.28 2160.55 0.00 0.00 0.00 0.00 0.00 83.73
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 2864.31   404.87 273.61 2160.55 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 19367.51   1923.11 1470.28 5761.47 0.00 0.00 0.00 0.00 639.73 167.27



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 2573.30 31-JAN-15:00 1295.83 793.52 1392.34 0.00 0.00 0.00 0.00 0.00 24.47
February 3534.90 27-FEB-10:40 1295.83 793.52 1392.34 0.00 0.00 0.00 0.00 0.00 130.39
March 6076.56 30-MAR-11:00 1239.33 793.52 1392.34 0.00 0.00 0.00 0.00 0.00 38.68
April 9778.77 14-APR-09:50 1295.83 793.52 1392.34 0.00 0.00 0.00 0.00 0.00 36.71
May 20211.71 07-MAY-09:12 326.14 220.40 2320.57 0.00 0.00 0.00 0.00 0.00 226.80
June 20031.35 25-JUN-08:52 326.14 220.40 2320.57 0.00 0.00 0.00 0.00 0.00 27.23
July 20519.48 23-JUL-08:32 326.14 220.40 2320.57 0.00 0.00 0.00 0.00 0.00 162.05
August 21239.66 27-AUG-09:12 391.37 264.49 2784.68 0.00 0.00 0.00 0.00 0.00 17.78
September 19734.57 04-SEP-09:22 326.14 220.40 2320.57 0.00 0.00 0.00 0.00 0.00 49.58
October 7336.15 11-OCT-10:20 1239.33 793.52 1392.34 0.00 0.00 0.00 0.00 0.00 9.15
November 3026.61 06-NOV-10:30 1295.83 793.52 1392.34 0.00 0.00 0.00 0.00 0.00 195.06
December 2736.13 13-DEC-15:00 1295.83 947.51 1392.34 0.00 0.00 0.00 0.00 0.00 48.84
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 2573.30   326.14 220.40 1392.34 0.00 0.00 0.00 0.00 0.00 9.15
Maximum of Months 21239.66   1295.83 947.51 2784.68 0.00 0.00 0.00 0.00 0.00 226.80



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 10410.02 11-JAN-14:30 2010.83 1231.36 2160.58 0.00 0.00 0.00 0.00 0.00 197.56
February 20795.67 26-FEB-14:52 506.09 342.02 3600.97 0.00 0.00 0.00 0.00 0.00 164.91
March 16303.50 30-MAR-13:40 2010.83 1231.36 2160.58 0.00 0.00 0.00 0.00 90.74 0.00
April 13433.31 17-APR-14:00 2010.83 1231.36 2160.58 0.00 0.00 0.00 0.00 34.71 0.00
May 19059.69 29-MAY-14:12 506.09 342.02 3600.97 0.00 0.00 0.00 0.00 47.01 0.00
June 22332.85 25-JUN-16:11 809.75 547.23 5761.56 0.00 0.00 0.00 0.00 638.82 0.00
July 21566.38 16-JUL-12:53 404.87 273.61 2880.78 0.00 0.00 0.00 0.00 521.67 0.00
August 22170.38 13-AUG-13:32 404.87 273.61 2880.78 0.00 0.00 0.00 0.00 198.72 0.00
September 21990.46 24-SEP-11:43 404.87 273.61 2880.78 0.00 0.00 0.00 0.00 73.57 0.00
October 23882.86 09-OCT-14:12 607.31 410.42 4321.17 0.00 0.00 0.00 0.00 0.00 69.37
November 22888.93 11-NOV-14:52 506.09 342.02 3600.97 0.00 0.00 0.00 0.00 0.00 625.99
December 12346.79 08-DEC-14:10 2010.83 1231.36 2160.58 0.00 0.00 0.00 0.00 0.00 498.06
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 10410.02   404.87 273.61 2160.58 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 23882.86   2010.83 1231.36 5761.56 0.00 0.00 0.00 0.00 638.82 625.99



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 3209.56 20-JAN-16:40 1239.33 793.52 1392.33 0.00 0.00 0.00 0.00 0.00 115.26
February 7566.54 27-FEB-17:00 1239.33 793.52 1392.33 0.00 0.00 0.00 0.00 0.00 14.29
March 11234.20 30-MAR-16:00 1239.33 793.52 1392.33 0.00 0.00 0.00 0.00 84.97 0.00
April 19237.61 09-APR-16:52 326.14 220.40 2320.55 0.00 0.00 0.00 0.00 0.00 110.25
May 23134.91 21-MAY-17:22 0.00 264.49 2162.09 0.00 0.00 0.00 0.00 0.00 176.92
June 24611.65 25-JUN-16:11 521.82 352.65 3712.89 0.00 0.00 0.00 0.00 293.10 0.00
July 24417.85 23-JUL-17:11 0.00 352.65 2882.79 0.00 0.00 0.00 0.00 26.76 0.00
August 23215.85 13-AUG-16:51 456.59 308.57 3248.78 0.00 0.00 0.00 0.00 134.65 0.00
September 21909.53 04-SEP-17:02 0.00 220.40 1801.74 0.00 0.00 0.00 0.00 22.84 0.00
October 13150.64 09-OCT-16:12 326.14 220.40 2320.55 0.00 0.00 0.00 0.00 22.96 0.00
November 6783.81 06-NOV-16:00 1239.33 793.52 1392.33 0.00 0.00 0.00 0.00 0.00 99.75
December 3407.64 11-DEC-16:00 1239.33 793.52 1392.33 0.00 0.00 0.00 0.00 0.00 41.59
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 3209.56   0.00 220.40 1392.33 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 24611.65   1239.33 793.52 3712.89 0.00 0.00 0.00 0.00 293.10 176.92



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: GROUNDFLOOR_PLENUM

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 6219.40 26-JAN-06:01 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 549.74
February 6470.40 03-FEB-06:01 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 606.37
March 6396.08 30-MAR-15:00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 69.27 0.00
April 8171.25 17-APR-15:30 0.00 0.00 0.00 0.00 0.00 0.00 0.00 36.30 0.00
May 10357.53 30-MAY-05:03 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 40.01
June 10971.43 19-JUN-05:02 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 41.77
July 9808.26 11-JUL-05:02 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 36.13
August 9341.17 09-AUG-05:02 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 7.12
September 12621.66 05-SEP-05:02 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 55.25
October 7619.75 10-OCT-05:13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 98.62
November 5756.34 13-NOV-06:08 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 332.01
December 4734.13 14-DEC-06:13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 320.45
                       
Annual Sum or Average     0.00 0.00 0.00 0.00 0.00 0.00 0.00    
Minimum of Months 4734.13   0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 12621.66   0.00 0.00 0.00 0.00 0.00 0.00 0.00 69.27 606.37



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: MIDFLOOR_PLENUM

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 7752.41 14-JAN-04:01 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 4461.77
February 10065.98 12-FEB-06:01 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 7191.38
March 5778.49 18-MAR-05:02 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 789.89
April 6755.79 06-APR-05:03 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 512.78
May 5712.45 19-MAY-05:13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 6550.65 29-JUN-16:00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 228.58 0.00
July 9678.85 06-JUL-05:02 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 51.45
August 10025.13 21-AUG-05:02 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 69.90
September 6588.09 07-SEP-15:40 0.00 0.00 0.00 0.00 0.00 0.00 0.00 152.26 0.00
October 5286.34 13-OCT-05:10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 8582.94 22-NOV-05:01 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 2887.12
December 8534.89 01-DEC-05:01 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 3037.56
                       
Annual Sum or Average     0.00 0.00 0.00 0.00 0.00 0.00 0.00    
Minimum of Months 5286.34   0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 10065.98   0.00 0.00 0.00 0.00 0.00 0.00 0.00 228.58 7191.38



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: TOPFLOOR_PLENUM

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 2551.06 31-JAN-13:10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 169.25
February 6092.74 28-FEB-16:10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 109.84
March 13188.41 30-MAR-14:20 0.00 0.00 0.00 0.00 0.00 0.00 0.00 80.68 0.00
April 16036.76 17-APR-14:40 0.00 0.00 0.00 0.00 0.00 0.00 0.00 52.77 0.00
May 17025.88 16-MAY-15:40 0.00 0.00 0.00 0.00 0.00 0.00 0.00 87.24 0.00
June 17712.03 13-JUN-13:50 0.00 0.00 0.00 0.00 0.00 0.00 0.00 86.46 0.00
July 19740.61 07-JUL-15:10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 110.69 0.00
August 19476.71 01-AUG-14:00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 195.94 0.00
September 16381.49 06-SEP-14:00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 129.92 0.00
October 12040.27 10-OCT-14:40 0.00 0.00 0.00 0.00 0.00 0.00 0.00 75.77 0.00
November 5430.44 05-NOV-14:10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 49.95
December 3283.85 12-DEC-13:10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 130.49
                       
Annual Sum or Average     0.00 0.00 0.00 0.00 0.00 0.00 0.00    
Minimum of Months 2551.06   0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 19740.61   0.00 0.00 0.00 0.00 0.00 0.00 0.00 195.94 169.25



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 1910.36 23-JAN-17:00 222.14 578.72 1948.61 0.00 0.00 0.00 0.00 0.00 0.00
February 4019.05 24-FEB-17:50 70.15 321.51 3897.21 0.00 0.00 0.00 0.00 0.00 0.00
March 7150.58 31-MAR-24:00 0.00 32.15 7794.42 0.00 0.00 0.00 0.00 0.00 0.00
April 7933.39 09-APR-18:15 0.00 128.61 31177.69 0.00 0.00 0.00 0.00 0.00 0.00
May 3485.90 31-MAY-24:00 0.00 32.15 3897.21 0.00 0.00 0.00 0.00 0.00 0.00
June 5395.09 30-JUN-24:00 0.00 32.15 5845.82 0.00 0.00 0.00 0.00 0.00 0.00
July 7228.22 31-JUL-24:00 0.00 64.31 15588.84 0.00 0.00 0.00 0.00 0.00 0.00
August 7907.71 13-AUG-19:23 0.00 128.61 31177.69 0.00 0.00 0.00 0.00 0.00 0.00
September 3184.82 30-SEP-24:00 0.00 32.15 3897.21 0.00 0.00 0.00 0.00 0.00 0.00
October 5103.99 31-OCT-24:00 0.00 32.15 5845.82 0.00 0.00 0.00 0.00 0.00 0.00
November 6014.36 06-NOV-17:00 222.14 578.72 5845.82 0.00 0.00 0.00 0.00 0.00 0.00
December 7807.88 19-DEC-17:00 222.14 578.72 7794.42 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 1910.36   0.00 32.15 1948.61 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 7933.39   222.14 578.72 31177.69 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: DATACENTER_MID_ZN_6

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 1529.00 27-JAN-17:00 222.14 578.72 1948.61 0.00 0.00 0.00 0.00 0.00 0.00
February 3714.21 24-FEB-17:50 70.15 321.51 3897.21 0.00 0.00 0.00 0.00 0.00 0.00
March 6627.55 31-MAR-23:50 0.00 32.15 7794.42 0.00 0.00 0.00 0.00 0.00 0.00
April 7466.89 14-APR-18:30 23.38 192.90 7794.42 0.00 0.00 0.00 0.00 0.00 0.00
May 3251.71 31-MAY-24:00 0.00 32.15 3897.21 0.00 0.00 0.00 0.00 0.00 0.00
June 5116.08 30-JUN-24:00 0.00 32.15 5845.82 0.00 0.00 0.00 0.00 0.00 0.00
July 6975.71 31-JUL-24:00 0.00 64.31 15588.84 0.00 0.00 0.00 0.00 0.00 0.00
August 7433.26 13-AUG-18:37 0.00 192.92 46766.53 0.00 0.00 0.00 0.00 0.00 0.00
September 2580.47 30-SEP-24:00 0.00 32.15 3897.21 0.00 0.00 0.00 0.00 0.00 0.00
October 4300.80 31-OCT-23:50 0.00 32.15 5845.82 0.00 0.00 0.00 0.00 0.00 0.00
November 5573.89 06-NOV-17:00 222.14 578.72 5845.82 0.00 0.00 0.00 0.00 0.00 0.00
December 7147.65 08-DEC-17:00 222.14 578.72 7794.42 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 1529.00   0.00 32.15 1948.61 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 7466.89   222.14 578.72 46766.53 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 1506.78 20-JAN-17:00 222.14 578.72 1948.61 0.00 0.00 0.00 0.00 0.00 0.00
February 3666.30 28-FEB-17:00 222.14 578.72 3897.21 0.00 0.00 0.00 0.00 0.00 0.00
March 6362.44 31-MAR-23:20 0.00 32.15 7794.42 0.00 0.00 0.00 0.00 0.00 0.00
April 7550.07 14-APR-18:30 23.38 192.90 7794.42 0.00 0.00 0.00 0.00 0.00 0.00
May 3207.37 31-MAY-24:00 0.00 32.15 3897.21 0.00 0.00 0.00 0.00 0.00 0.00
June 5077.78 30-JUN-24:00 0.00 32.15 5845.82 0.00 0.00 0.00 0.00 0.00 0.00
July 7019.30 31-JUL-24:00 0.00 64.31 15588.84 0.00 0.00 0.00 0.00 0.00 0.00
August 7660.98 13-AUG-18:52 0.00 160.76 38972.11 0.00 0.00 0.00 0.00 0.00 0.00
September 2084.04 08-SEP-18:10 23.38 192.90 1948.61 0.00 0.00 0.00 0.00 0.00 0.00
October 3849.39 11-OCT-17:30 23.38 192.90 3897.21 0.00 0.00 0.00 0.00 0.00 0.00
November 5559.44 06-NOV-17:00 222.14 578.72 5845.82 0.00 0.00 0.00 0.00 0.00 0.00
December 7039.49 07-DEC-17:00 222.14 578.72 7794.42 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 1506.78   0.00 32.15 1948.61 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 7660.98   222.14 578.72 38972.11 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 91720.11 20-JAN-17:00 4808.68 6471.01 94908.13 0.00 0.00 0.00 0.00 0.00 0.00
February 183494.40 28-FEB-17:00 4808.68 6471.01 189816.26 0.00 0.00 0.00 0.00 0.00 0.00
March 358109.53 31-MAR-24:00 0.00 359.47 379632.52 0.00 0.00 0.00 0.00 0.00 0.00
April 366259.93 20-APR-15:30 4808.68 6471.01 379632.52 0.00 0.00 0.00 0.00 0.00 0.00
May 175353.30 31-MAY-24:00 0.00 359.47 189816.26 0.00 0.00 0.00 0.00 0.00 0.00
June 267496.00 30-JUN-24:00 0.00 359.47 284724.39 0.00 0.00 0.00 0.00 0.00 0.00
July 359653.72 31-JUL-24:00 0.00 718.95 759265.04 0.00 0.00 0.00 0.00 0.00 0.00
August 370531.17 07-AUG-21:14 1265.44 3595.14 1898162.61 0.00 0.00 0.00 0.00 0.00 0.00
September 175462.04 30-SEP-24:00 0.00 359.47 189816.26 0.00 0.00 0.00 0.00 0.00 0.00
October 268176.51 31-OCT-24:00 0.00 359.47 284724.39 0.00 0.00 0.00 0.00 0.00 0.00
November 277506.15 06-NOV-17:00 4808.68 6471.01 284724.39 0.00 0.00 0.00 0.00 0.00 0.00
December 368470.04 13-DEC-17:00 4808.68 6471.01 379632.52 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 91720.11   0.00 359.47 94908.13 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 370531.17   4808.68 6471.01 1898162.61 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: EnergyConsumptionElectricityNaturalGasMonthly

For: Meter

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ELECTRICITY:FACILITY [J] ELECTRICITY:FACILITY {Maximum} [W] ELECTRICITY:FACILITY {TIMESTAMP} NATURALGAS:FACILITY [J] NATURALGAS:FACILITY {Maximum} [W] NATURALGAS:FACILITY {TIMESTAMP}
January 0.164422E+13 1141961.03 19-JAN-16:49 0.455794E+12 1745683.16 09-JAN-07:10
February 0.189246E+13 1336640.86 28-FEB-16:40 0.287453E+12 1803266.60 13-FEB-07:10
March 0.262071E+13 1727321.56 30-MAR-15:20 0.113002E+12 617930.51 18-MAR-06:10
April 0.296546E+13 1860481.66 12-APR-15:20 0.726603E+11 675857.02 06-APR-06:10
May 0.202417E+13 1438935.00 16-MAY-15:50 0.627227E+11 111779.64 10-MAY-06:10
June 0.253316E+13 1609872.22 29-JUN-15:00 0.576920E+11 72178.90 06-JUN-11:39
July 0.304491E+13 1812595.22 07-JUL-15:00 0.548525E+11 69444.02 03-JUL-11:39
August 0.359110E+13 1957895.51 17-AUG-15:30 0.577634E+11 69234.86 31-AUG-11:00
September 0.201386E+13 1469680.56 07-SEP-15:00 0.555267E+11 82656.91 14-SEP-15:50
October 0.225877E+13 1579317.54 10-OCT-15:30 0.835766E+11 649554.01 26-OCT-06:10
November 0.247903E+13 1528139.27 27-NOV-16:00 0.133022E+12 1044356.64 22-NOV-07:10
December 0.284797E+13 1621893.31 13-DEC-16:40 0.259165E+12 1314651.24 18-DEC-07:10
             
Annual Sum or Average 0.299158E+14     0.169323E+13    
Minimum of Months 0.164422E+13 1141961.03   0.548525E+11 69234.86  
Maximum of Months 0.359110E+13 1957895.51   0.455794E+12 1803266.60  



Table of Contents

Report: EndUseEnergyConsumptionElectricityMonthly

For: Meter

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

INTERIORLIGHTS:ELECTRICITY [J] EXTERIORLIGHTS:ELECTRICITY [J] INTERIOREQUIPMENT:ELECTRICITY [J] EXTERIOREQUIPMENT:ELECTRICITY [J] FANS:ELECTRICITY [J] PUMPS:ELECTRICITY [J] HEATING:ELECTRICITY [J] COOLING:ELECTRICITY [J] HEATREJECTION:ELECTRICITY [J] HUMIDIFIER:ELECTRICITY [J] HEATRECOVERY:ELECTRICITY [J] WATERSYSTEMS:ELECTRICITY [] COGENERATION:ELECTRICITY []
January 0.333150E+12 0.718275E+11 0.766053E+12 0.164271E+12 0.165779E+12 0.208995E+11 0.00 0.951029E+11 0.190596E+11 0.261229E+10 0.546998E+10 0.00 0.00
February 0.302520E+12 0.604208E+11 0.978954E+12 0.148384E+12 0.150648E+12 0.257607E+11 0.00 0.170122E+12 0.503996E+11 0.183348E+10 0.341492E+10 0.00 0.00
March 0.353213E+12 0.604266E+11 0.141687E+13 0.164523E+12 0.172064E+12 0.388965E+11 0.00 0.306804E+12 0.105013E+12 0.937201E+09 0.196285E+10 0.00 0.00
April 0.313757E+12 0.520179E+11 0.165903E+13 0.158945E+12 0.170672E+12 0.481356E+11 0.00 0.433966E+12 0.126919E+12 0.294732E+09 0.172475E+10 0.00 0.00
May 0.336899E+12 0.481273E+11 0.774844E+12 0.164394E+12 0.184044E+12 0.562348E+11 0.00 0.306900E+12 0.147803E+12 52123678.84 0.487081E+10 0.00 0.00
June 0.334552E+12 0.441063E+11 0.106252E+13 0.159182E+12 0.193740E+12 0.717709E+11 0.00 0.485144E+12 0.175702E+12 14739243.96 0.643360E+10 0.00 0.00
July 0.313961E+12 0.465036E+11 0.139340E+13 0.164156E+12 0.199890E+12 0.827663E+11 0.00 0.638069E+12 0.198994E+12 0.00 0.716953E+10 0.00 0.00
August 0.350489E+12 0.512022E+11 0.173200E+13 0.164521E+12 0.209604E+12 0.936219E+11 0.00 0.771267E+12 0.210542E+12 0.00 0.785437E+10 0.00 0.00
September 0.315346E+12 0.556800E+11 0.740713E+12 0.158945E+12 0.182651E+12 0.600733E+11 0.00 0.335601E+12 0.160063E+12 0.00 0.479166E+10 0.00 0.00
October 0.331263E+12 0.642269E+11 0.108340E+13 0.164271E+12 0.174032E+12 0.432393E+11 0.00 0.283344E+12 0.112300E+12 41761063.45 0.264732E+10 0.00 0.00
November 0.328154E+12 0.680138E+11 0.135889E+13 0.159044E+12 0.162278E+12 0.328611E+11 0.00 0.275023E+12 0.912598E+11 0.121683E+10 0.228861E+10 0.00 0.00
December 0.322831E+12 0.734167E+11 0.170972E+13 0.164159E+12 0.164132E+12 0.228577E+11 0.00 0.303697E+12 0.817214E+11 0.193551E+10 0.349944E+10 0.00 0.00
                           
Annual Sum or Average 0.393613E+13 0.695970E+12 0.146764E+14 0.193480E+13 0.212953E+13 0.597118E+12 0.00 0.440504E+13 0.147978E+13 0.893867E+10 0.521278E+11 0.00 0.00
Minimum of Months 0.302520E+12 0.441063E+11 0.740713E+12 0.148384E+12 0.150648E+12 0.208995E+11 0.00 0.951029E+11 0.190596E+11 0.00 0.172475E+10 0.00 0.00
Maximum of Months 0.353213E+12 0.734167E+11 0.173200E+13 0.164523E+12 0.209604E+12 0.936219E+11 0.00 0.771267E+12 0.210542E+12 0.261229E+10 0.785437E+10 0.00 0.00



Table of Contents

Report: EndUseEnergyConsumptionNaturalGasMonthly

For: Meter

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

INTERIOREQUIPMENT:NATURALGAS [] EXTERIOREQUIPMENT:NATURALGAS [] HEATING:NATURALGAS [J] COOLING:NATURALGAS [] WATERSYSTEMS:NATURALGAS [J] COGENERATION:NATURALGAS [] HUMIDIFIER:NATURALGAS []
January 0.00 0.00 0.387927E+12 0.00 0.678667E+11 0.00 0.00
February 0.00 0.00 0.225817E+12 0.00 0.616363E+11 0.00 0.00
March 0.00 0.00 0.435654E+11 0.00 0.694370E+11 0.00 0.00
April 0.00 0.00 0.109828E+11 0.00 0.616774E+11 0.00 0.00
May 0.00 0.00 0.100252E+10 0.00 0.617202E+11 0.00 0.00
June 0.00 0.00 0.110688E+09 0.00 0.575813E+11 0.00 0.00
July 0.00 0.00 0.00 0.00 0.548525E+11 0.00 0.00
August 0.00 0.00 0.00 0.00 0.577634E+11 0.00 0.00
September 0.00 0.00 0.201767E+09 0.00 0.553249E+11 0.00 0.00
October 0.00 0.00 0.236563E+11 0.00 0.599202E+11 0.00 0.00
November 0.00 0.00 0.713360E+11 0.00 0.616861E+11 0.00 0.00
December 0.00 0.00 0.194094E+12 0.00 0.650708E+11 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.958694E+12 0.00 0.734537E+12 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.548525E+11 0.00 0.00
Maximum of Months 0.00 0.00 0.387927E+12 0.00 0.694370E+11 0.00 0.00



Table of Contents

Report: PeakEnergyEndUseElectricityPart1Monthly

For: Meter

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

INTERIORLIGHTS:ELECTRICITY {Maximum} [W] INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} EXTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] EXTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} FANS:ELECTRICITY {Maximum} [W] FANS:ELECTRICITY {TIMESTAMP} PUMPS:ELECTRICITY {Maximum} [W] PUMPS:ELECTRICITY {TIMESTAMP} HEATING:ELECTRICITY {Maximum} [W] HEATING:ELECTRICITY {TIMESTAMP}
January 385834.94 03-JAN-08:09 57580.60 01-JAN-06:10 423497.50 02-JAN-08:09 118535.44 03-JAN-08:20 101934.19 09-JAN-06:10 32653.89 10-JAN-06:19 0.00 01-JAN-00:10
February 385834.94 01-FEB-08:09 57580.60 01-FEB-06:10 541788.89 01-FEB-08:09 118535.44 01-FEB-08:20 116669.53 03-FEB-11:50 32358.35 03-FEB-06:10 0.00 01-FEB-00:10
March 385834.94 21-MAR-07:10 57580.60 01-MAR-06:10 660080.29 01-MAR-08:09 118535.44 21-MAR-07:19 136060.09 30-MAR-15:20 57943.14 30-MAR-15:09 0.00 01-MAR-00:10
April 372703.55 03-APR-07:10 57580.60 01-APR-05:10 778371.69 03-APR-07:10 118525.16 03-APR-07:19 173140.65 17-APR-15:09 60075.36 12-APR-15:20 0.00 01-APR-00:10
May 349940.27 24-MAY-07:19 57580.60 01-MAY-05:10 423497.50 01-MAY-07:10 118507.38 24-MAY-07:30 147401.22 16-MAY-15:50 59156.25 31-MAY-12:20 0.00 01-MAY-00:10
June 342450.60 23-JUN-07:10 57580.60 01-JUN-05:10 541788.89 01-JUN-07:10 118501.55 23-JUN-07:19 139027.86 14-JUN-05:10 59748.80 27-JUN-11:39 0.00 01-JUN-00:10
July 355780.78 27-JUL-07:10 57580.60 01-JUL-05:10 660080.29 03-JUL-07:10 118511.94 27-JUL-07:19 146082.58 07-JUL-15:00 61412.90 05-JUL-08:39 0.00 01-JUL-00:10
August 372703.55 24-AUG-07:10 57580.60 01-AUG-05:10 778371.69 01-AUG-07:10 118525.16 24-AUG-07:19 150487.04 02-AUG-15:00 61546.80 01-AUG-09:20 0.00 01-AUG-00:10
September 383261.93 29-SEP-07:10 57580.60 01-SEP-05:10 423497.50 01-SEP-07:10 118533.43 29-SEP-07:19 145176.20 07-SEP-15:30 60745.24 06-SEP-11:20 0.00 01-SEP-00:10
October 385834.94 19-OCT-07:10 57580.60 01-OCT-05:10 541788.89 02-OCT-07:10 118535.44 19-OCT-07:19 125997.66 11-OCT-15:20 58544.59 18-OCT-14:39 0.00 01-OCT-00:10
November 385834.94 01-NOV-07:10 57580.60 01-NOV-05:10 660080.29 01-NOV-07:10 118535.44 01-NOV-07:19 101604.18 06-NOV-14:00 31473.61 21-NOV-05:10 0.00 01-NOV-00:10
December 385834.94 06-DEC-08:09 57580.60 01-DEC-06:10 778371.69 01-DEC-08:09 118535.44 06-DEC-08:20 90388.90 14-DEC-06:10 31932.08 18-DEC-06:00 0.00 01-DEC-00:10
                             
Annual Sum or Average                            
Minimum of Months 342450.60   57580.60   423497.50   118501.55   90388.90   31473.61   0.00  
Maximum of Months 385834.94   57580.60   778371.69   118535.44   173140.65   61546.80   0.00  



Table of Contents

Report: PeakEnergyEndUseElectricityPart2Monthly

For: Meter

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

COOLING:ELECTRICITY {Maximum} [W] COOLING:ELECTRICITY {TIMESTAMP} HEATREJECTION:ELECTRICITY {Maximum} [W] HEATREJECTION:ELECTRICITY {TIMESTAMP} HUMIDIFIER:ELECTRICITY {Maximum} [W] HUMIDIFIER:ELECTRICITY {TIMESTAMP} HEATRECOVERY:ELECTRICITY {Maximum} [W] HEATRECOVERY:ELECTRICITY {TIMESTAMP} WATERSYSTEMS:ELECTRICITY [] COGENERATION:ELECTRICITY []
January 118194.27 31-JAN-15:09 51419.24 19-JAN-21:00 5868.03 05-JAN-18:10 5613.48 02-JAN-07:10 0.00 0.00
February 211381.48 28-FEB-14:00 51486.46 28-FEB-14:00 5743.06 03-FEB-18:00 5613.48 01-FEB-07:10 0.00 0.00
March 362960.60 30-MAR-15:20 92827.61 29-MAR-15:00 5579.39 18-MAR-16:10 5613.48 01-MAR-07:10 0.00 0.00
April 418262.84 18-APR-12:50 92827.61 04-APR-10:39 3958.09 05-APR-19:19 5613.48 04-APR-07:00 0.00 0.00
May 319471.22 30-MAY-14:39 92827.61 02-MAY-12:20 2994.13 10-MAY-18:00 5613.48 01-MAY-13:50 0.00 0.00
June 385409.73 27-JUN-12:09 92827.61 01-JUN-07:49 2978.25 10-JUN-16:00 5613.48 01-JUN-06:10 0.00 0.00
July 432733.39 07-JUL-15:00 92827.61 01-JUL-06:30 0.00 01-JUL-00:10 5613.48 01-JUL-06:10 0.00 0.00
August 456876.80 17-AUG-15:30 92827.61 01-AUG-06:19 0.00 01-AUG-00:10 5613.48 01-AUG-06:10 0.00 0.00
September 330079.12 06-SEP-11:30 92827.61 01-SEP-09:20 0.00 01-SEP-00:10 5613.48 01-SEP-06:10 0.00 0.00
October 349862.43 18-OCT-14:39 92827.61 02-OCT-08:00 2676.20 31-OCT-20:00 5613.48 02-OCT-07:10 0.00 0.00
November 245216.55 02-NOV-13:09 71037.94 02-NOV-12:30 4324.26 22-NOV-18:10 5613.48 01-NOV-06:10 0.00 0.00
December 260067.23 12-DEC-13:00 54527.02 13-DEC-11:09 5317.63 02-DEC-17:00 5613.48 01-DEC-07:10 0.00 0.00
                     
Annual Sum or Average                 0.00 0.00
Minimum of Months 118194.27   51419.24   0.00   5613.48   0.00 0.00
Maximum of Months 456876.80   92827.61   5868.03   5613.48   0.00 0.00



Table of Contents

Report: ElectricComponentsOfPeakDemandMonthly

For: Meter

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ELECTRICITY:FACILITY {Maximum} [W] ELECTRICITY:FACILITY {TIMESTAMP} INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] EXTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] FANS:ELECTRICITY {AT MAX/MIN} [W] PUMPS:ELECTRICITY {AT MAX/MIN} [W] HEATING:ELECTRICITY {AT MAX/MIN} [W] COOLING:ELECTRICITY {AT MAX/MIN} [W] HEATREJECTION:ELECTRICITY {AT MAX/MIN} [W]
January 1141961.03 19-JAN-16:49 363780.14 423497.50 0.00 84465.88 75247.91 29167.43 0.00 114588.71 51213.47
February 1336640.86 28-FEB-16:40 333338.24 541788.89 0.00 84450.25 96127.73 29431.20 0.00 200594.06 50910.48
March 1727321.56 30-MAR-15:20 332294.83 660080.29 0.00 84450.25 136060.09 56776.73 0.00 362960.60 92827.61
April 1860481.66 12-APR-15:20 332294.83 778371.69 0.00 84450.25 116980.75 60075.36 0.00 391738.86 92827.61
May 1438935.00 16-MAY-15:50 332294.83 423497.50 0.00 84450.25 147401.22 57437.94 0.00 299154.50 92827.61
June 1609872.22 29-JUN-15:00 332294.83 541788.89 0.00 84450.25 137149.96 58006.53 0.00 357740.67 92827.61
July 1812595.22 07-JUL-15:00 332294.83 660080.29 0.00 84450.25 146082.58 58512.80 0.00 432733.39 92827.61
August 1957895.51 17-AUG-15:30 332294.83 778371.69 0.00 84450.25 148727.01 58733.85 0.00 456876.80 92827.61
September 1469680.56 07-SEP-15:00 332294.83 423497.50 0.00 84450.25 143319.55 58434.89 0.00 329242.46 92827.61
October 1579317.54 10-OCT-15:30 332294.83 541788.89 0.00 84450.25 122020.81 57082.05 0.00 343239.62 92827.61
November 1528139.27 27-NOV-16:00 372703.55 660080.29 0.00 84479.04 76844.69 29557.29 0.00 227823.00 71037.94
December 1621893.31 13-DEC-16:40 372703.55 778371.69 0.00 84479.10 81753.79 29418.31 0.00 222654.67 52512.21
                       
Annual Sum or Average                      
Minimum of Months 1141961.03   332294.83 423497.50 0.00 84450.25 75247.91 29167.43 0.00 114588.71 50910.48
Maximum of Months 1957895.51   372703.55 778371.69 0.00 84479.10 148727.01 60075.36 0.00 456876.80 92827.61



Table of Contents

Report: PeakEnergyEndUseNaturalGasMonthly

For: Meter

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

INTERIOREQUIPMENT:NATURALGAS [] EXTERIOREQUIPMENT:NATURALGAS [] HEATING:NATURALGAS {Maximum} [W] HEATING:NATURALGAS {TIMESTAMP} COOLING:NATURALGAS [] WATERSYSTEMS:NATURALGAS {Maximum} [W] WATERSYSTEMS:NATURALGAS {TIMESTAMP} COGENERATION:NATURALGAS []
January 0.00 0.00 1714112.09 09-JAN-07:10 0.00 82139.73 30-JAN-12:20 0.00
February 0.00 0.00 1771654.06 13-FEB-07:10 0.00 82149.84 02-FEB-12:00 0.00
March 0.00 0.00 588186.92 18-MAR-06:10 0.00 81489.43 03-MAR-12:00 0.00
April 0.00 0.00 654321.34 06-APR-06:10 0.00 79363.23 04-APR-11:30 0.00
May 0.00 0.00 80886.69 10-MAY-06:10 0.00 76583.17 01-MAY-11:20 0.00
June 0.00 0.00 37593.89 10-JUN-13:09 0.00 72178.90 06-JUN-11:39 0.00
July 0.00 0.00 0.00 01-JUL-00:10 0.00 69444.02 03-JUL-11:39 0.00
August 0.00 0.00 0.00 01-AUG-00:10 0.00 69234.86 31-AUG-11:00 0.00
September 0.00 0.00 44355.23 14-SEP-15:50 0.00 72137.03 29-SEP-11:00 0.00
October 0.00 0.00 621241.91 26-OCT-06:10 0.00 75596.26 27-OCT-11:50 0.00
November 0.00 0.00 1013280.63 22-NOV-07:10 0.00 78954.05 27-NOV-12:30 0.00
December 0.00 0.00 1284015.05 18-DEC-07:10 0.00 81288.37 29-DEC-12:30 0.00
                 
Annual Sum or Average 0.00 0.00     0.00     0.00
Minimum of Months 0.00 0.00 0.00   0.00 69234.86   0.00
Maximum of Months 0.00 0.00 1771654.06   0.00 82149.84   0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: BASEMENT

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 5.00 27.21 2.83 27.28
February 0.00 0.00 0.00 0.00 0.50 25.70 0.00 25.70
March 0.00 0.00 0.00 0.00 0.67 25.75 0.00 25.75
April 0.00 0.00 0.00 0.00 0.67 25.61 0.00 25.61
May 0.00 0.00 0.00 0.00 2.33 26.65 0.00 26.65
June 0.00 0.00 0.00 0.00 1.00 26.26 0.00 26.26
July 0.00 0.00 0.00 0.00 3.00 26.31 0.00 26.31
August 0.00 0.00 0.00 0.00 6.83 26.46 0.00 26.46
September 0.00 0.00 0.00 0.00 5.83 26.77 0.50 26.82
October 0.00 0.00 0.00 0.00 7.17 26.83 0.17 26.84
November 0.00 0.00 0.00 0.00 7.17 27.04 0.67 27.07
December 0.00 0.00 0.00 0.00 2.67 26.55 0.67 26.72
                 
Annual Sum or Average 0.00   0.00   42.83 26.72 4.83 26.79
Minimum of Months 0.00 0.00 0.00 0.00 0.50 25.61 0.00 25.61
Maximum of Months 0.00 0.00 0.00 0.00 7.17 27.21 2.83 27.28



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: CORE_BOTTOM

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: CORE_MID

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.17 19.25 0.00 19.25 0.00 19.25 0.00 19.25
February 0.17 18.59 0.00 18.59 0.00 18.59 0.00 18.59
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.33 18.92 0.00 18.92 0.00 18.92 0.00 18.92
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.17 19.25 0.00 19.25 0.00 19.25 0.00 19.25



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: CORE_TOP

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 3.50 18.66 0.83 18.94 0.00 18.94 0.00 18.94
February 1.67 18.78 0.33 19.01 0.00 19.01 0.00 19.01
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 1.50 18.91 0.17 19.02 0.00 19.02 0.00 19.02
                 
Annual Sum or Average 6.67 18.75 1.33 18.98 0.00 18.98 0.00 18.98
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 3.50 18.91 0.83 19.02 0.00 19.02 0.00 19.02



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.17 19.40 0.00 19.40 0.00 19.40 0.00 19.40
February 0.17 19.26 0.00 19.26 0.00 19.26 0.00 19.26
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 1.17 27.34 1.17 27.34
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.33 19.33 0.00 19.33 1.17 25.56 1.17 26.34
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.17 19.40 0.00 19.40 1.17 27.34 1.17 27.34



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.17 19.32 0.00 19.32 0.00 19.32 0.00 19.32
February 0.17 19.18 0.00 19.18 0.00 19.18 0.00 19.18
March 0.00 0.00 0.00 0.00 0.17 27.34 0.17 27.34
April 0.00 0.00 0.00 0.00 1.33 27.64 1.33 27.64
May 0.00 0.00 0.00 0.00 2.83 27.69 2.83 27.69
June 0.00 0.00 0.00 0.00 3.17 28.08 3.17 28.08
July 0.00 0.00 0.00 0.00 4.33 27.98 4.33 27.98
August 0.00 0.00 0.00 0.00 3.17 27.96 3.17 27.96
September 0.00 0.00 0.00 0.00 1.67 27.83 1.67 27.83
October 0.00 0.00 0.00 0.00 0.67 27.44 0.67 27.44
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.33 19.25 0.00 19.25 17.33 27.72 17.33 27.80
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.17 19.32 0.00 19.32 4.33 28.08 4.33 28.08



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.33 19.16 0.00 19.16 0.50 24.14 0.50 25.38
February 0.17 19.07 0.00 19.07 3.00 27.28 3.00 27.50
March 0.00 0.00 0.00 0.00 1.83 27.44 1.83 27.44
April 0.00 0.00 0.00 0.00 1.17 27.59 1.17 27.59
May 0.00 0.00 0.00 0.00 0.17 27.28 0.17 27.28
June 0.00 0.00 0.00 0.00 0.33 27.28 0.33 27.28
July 0.00 0.00 0.00 0.00 3.33 27.43 3.17 27.44
August 0.00 0.00 0.00 0.00 5.67 27.59 5.50 27.62
September 0.00 0.00 0.00 0.00 3.00 27.62 3.00 27.62
October 0.00 0.00 0.00 0.00 5.83 27.89 5.83 27.89
November 0.00 0.00 0.00 0.00 4.33 27.90 4.33 27.90
December 0.00 0.00 0.00 0.00 1.33 27.74 1.33 27.74
                 
Annual Sum or Average 0.50 19.13 0.00 19.13 30.50 27.55 30.17 27.62
Minimum of Months 0.00 0.00 0.00 0.00 0.17 24.14 0.17 25.38
Maximum of Months 0.33 19.16 0.00 19.16 5.83 27.90 5.83 27.90



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 1.33 27.82 1.33 27.82
March 0.00 0.00 0.00 0.00 4.17 27.99 3.00 27.98
April 0.00 0.00 0.00 0.00 10.50 27.55 4.50 27.72
May 0.00 0.00 0.00 0.00 3.33 28.08 2.00 28.10
June 0.00 0.00 0.00 0.00 12.50 27.55 5.00 27.73
July 0.00 0.00 0.00 0.00 22.83 27.62 7.83 27.80
August 0.00 0.00 0.00 0.00 23.50 27.51 7.17 27.71
September 0.00 0.00 0.00 0.00 5.83 27.63 4.00 27.71
October 0.00 0.00 0.00 0.00 4.00 27.92 3.17 27.99
November 0.00 0.00 0.00 0.00 2.33 27.84 2.33 27.84
December 0.00 0.00 0.00 0.00 0.67 27.06 0.50 27.27
                 
Annual Sum or Average 0.00   0.00   91.00 27.63 40.83 27.78
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 23.50 28.08 7.83 28.10



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 14.17 18.32 2.50 18.55 0.00 18.55 0.00 18.55
February 11.83 17.15 3.17 17.32 0.00 17.32 0.00 17.32
March 0.17 19.44 0.00 19.44 0.00 19.44 0.00 19.44
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.50 27.35 0.50 27.35
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.67 19.06 0.00 19.06 0.00 19.06 0.00 19.06
December 4.50 18.75 0.50 18.87 0.00 18.87 0.00 18.87
                 
Annual Sum or Average 31.33 17.96 6.17 18.11 0.50 18.23 0.50 18.35
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 14.17 19.44 3.17 19.44 0.50 27.35 0.50 27.35



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 9.67 17.42 0.50 17.39 0.00 17.39 0.00 17.39
February 7.33 16.42 0.50 16.29 0.00 16.29 0.00 16.29
March 0.17 19.34 0.00 19.34 0.00 19.34 0.00 19.34
April 0.00 0.00 0.00 0.00 1.00 27.68 1.00 27.68
May 0.00 0.00 0.00 0.00 2.50 27.69 2.50 27.69
June 0.00 0.00 0.00 0.00 4.00 28.02 4.00 28.02
July 0.00 0.00 0.00 0.00 8.67 27.83 8.67 27.83
August 0.00 0.00 0.00 0.00 5.67 27.88 5.67 27.88
September 0.00 0.00 0.00 0.00 1.33 27.79 1.33 27.79
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.50 18.99 0.00 18.99 0.00 18.99 0.00 18.99
December 3.83 18.75 0.33 18.88 0.00 18.88 0.00 18.88
                 
Annual Sum or Average 21.50 17.37 1.33 17.33 23.17 22.63 23.17 24.38
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 9.67 19.34 0.50 19.34 8.67 28.02 8.67 28.02



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 6.33 18.43 0.17 18.48 0.67 19.30 0.67 19.99
February 5.83 17.18 0.67 17.05 2.33 19.88 2.33 21.53
March 0.00 0.00 0.00 0.00 0.67 27.32 0.67 27.32
April 0.00 0.00 0.00 0.00 0.83 27.51 0.83 27.51
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 2.00 27.43 2.00 27.43
August 0.00 0.00 0.00 0.00 4.83 27.60 4.83 27.60
September 0.00 0.00 0.00 0.00 2.67 27.64 2.67 27.64
October 0.00 0.00 0.00 0.00 5.50 27.89 5.50 27.89
November 0.33 19.06 0.00 19.06 3.67 27.12 3.67 27.47
December 2.50 18.91 0.00 18.91 1.00 21.44 1.00 22.85
                 
Annual Sum or Average 15.00 18.04 0.83 17.97 24.17 23.85 24.17 25.30
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 6.33 19.06 0.67 19.06 5.50 27.89 5.50 27.89



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 6.17 18.23 0.00 18.23 0.00 18.23 0.00 18.23
February 5.17 16.82 0.83 16.51 0.00 16.51 0.00 16.51
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 2.17 27.83 1.33 27.80
May 0.00 0.00 0.00 0.00 3.00 27.95 1.50 27.95
June 0.00 0.00 0.00 0.00 5.67 28.07 3.00 28.10
July 0.00 0.00 0.00 0.00 8.83 28.26 4.33 28.29
August 0.00 0.00 0.00 0.00 6.00 28.24 3.33 28.29
September 0.00 0.00 0.00 0.00 2.50 27.81 1.83 27.80
October 0.00 0.00 0.00 0.00 1.00 27.76 0.83 27.77
November 0.50 19.10 0.00 19.10 0.00 19.10 0.00 19.10
December 2.67 18.76 0.00 18.76 0.00 18.76 0.00 18.76
                 
Annual Sum or Average 14.50 17.85 0.83 17.67 29.17 24.51 16.17 25.48
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 6.17 19.10 0.83 19.10 8.83 28.26 4.33 28.29



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 51.33 16.54 15.67 16.68 0.00 16.68 0.00 16.68
February 29.50 16.37 9.00 16.51 0.00 16.51 0.00 16.51
March 1.33 19.07 0.00 19.07 0.00 19.07 0.00 19.07
April 0.33 19.15 0.00 19.15 0.00 19.15 0.00 19.15
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 1.17 27.46 0.83 27.45
July 0.00 0.00 0.00 0.00 3.33 27.57 2.33 27.57
August 0.00 0.00 0.00 0.00 1.00 27.41 0.83 27.43
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.50 19.20 0.00 19.20 0.00 19.20 0.00 19.20
November 4.17 18.64 0.17 18.70 0.00 18.70 0.00 18.70
December 26.33 16.90 7.00 17.08 0.00 17.08 0.00 17.08
                 
Annual Sum or Average 113.50 16.71 31.83 16.82 5.50 17.21 4.00 17.48
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 51.33 19.20 15.67 19.20 3.33 27.57 2.33 27.57



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 31.50 15.72 5.50 15.68 0.00 15.68 0.00 15.68
February 17.17 15.85 2.00 15.84 0.00 15.84 0.00 15.84
March 1.00 19.00 0.00 19.00 0.00 19.00 0.00 19.00
April 0.17 19.03 0.00 19.03 0.67 25.89 0.67 26.65
May 0.00 0.00 0.00 0.00 2.17 27.69 2.17 27.69
June 0.00 0.00 0.00 0.00 6.00 27.92 5.67 27.93
July 0.00 0.00 0.00 0.00 12.33 27.88 11.33 27.89
August 0.00 0.00 0.00 0.00 7.67 27.90 7.17 27.92
September 0.00 0.00 0.00 0.00 1.17 27.73 1.17 27.73
October 0.50 19.19 0.00 19.19 0.00 19.19 0.00 19.19
November 3.17 18.49 0.00 18.49 0.00 18.49 0.00 18.49
December 16.83 16.11 1.17 16.07 0.00 16.07 0.00 16.07
                 
Annual Sum or Average 70.33 16.05 8.67 15.99 30.00 19.26 28.17 21.03
Minimum of Months 0.00 0.00 0.00 0.00 0.00 15.68 0.00 15.68
Maximum of Months 31.50 19.19 5.50 19.19 12.33 27.92 11.33 27.93



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 26.00 16.49 4.83 16.51 0.00 16.51 0.00 16.51
February 14.33 16.51 2.83 16.58 1.17 17.29 1.17 17.91
March 0.83 19.15 0.00 19.15 0.00 19.15 0.00 19.15
April 0.17 19.15 0.00 19.15 0.83 26.12 0.83 26.76
May 0.00 0.00 0.00 0.00 0.33 27.28 0.33 27.28
June 0.00 0.00 0.00 0.00 2.33 27.49 2.00 27.50
July 0.00 0.00 0.00 0.00 5.00 27.58 4.33 27.58
August 0.00 0.00 0.00 0.00 6.00 27.75 5.17 27.77
September 0.00 0.00 0.00 0.00 2.50 27.71 2.50 27.71
October 0.50 19.32 0.00 19.32 4.33 26.95 4.33 27.37
November 2.17 18.39 0.17 18.54 1.83 22.60 1.83 24.17
December 13.50 17.21 2.00 17.25 0.00 17.25 0.00 17.25
                 
Annual Sum or Average 57.50 16.81 9.83 16.83 24.33 19.71 22.50 21.28
Minimum of Months 0.00 0.00 0.00 0.00 0.00 16.51 0.00 16.51
Maximum of Months 26.00 19.32 4.83 19.32 6.00 27.75 5.17 27.77



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 20.83 15.89 4.17 15.74 0.00 15.74 0.00 15.74
February 11.67 15.92 2.50 15.73 0.00 15.73 0.00 15.73
March 0.67 19.25 0.00 19.25 0.00 19.25 0.00 19.25
April 0.17 19.29 0.00 19.29 2.17 27.24 1.50 27.47
May 0.00 0.00 0.00 0.00 3.17 28.06 1.50 28.08
June 0.00 0.00 0.00 0.00 6.33 28.15 3.33 28.20
July 0.00 0.00 0.00 0.00 10.00 28.38 4.83 28.41
August 0.00 0.00 0.00 0.00 7.33 28.26 4.00 28.30
September 0.00 0.00 0.00 0.00 2.67 27.84 1.83 27.88
October 0.17 19.27 0.00 19.27 1.00 26.45 0.83 26.97
November 2.00 18.24 0.00 18.24 0.00 18.24 0.00 18.24
December 9.17 17.10 1.83 16.82 0.00 16.82 0.00 16.82
                 
Annual Sum or Average 44.67 16.33 8.50 16.12 32.67 20.71 17.83 22.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 15.73 0.00 15.73
Maximum of Months 20.83 19.29 4.17 19.29 10.00 28.38 4.83 28.41



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: GROUNDFLOOR_PLENUM

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: MIDFLOOR_PLENUM

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: TOPFLOOR_PLENUM

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 43.00 27.77 43.00 27.77
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   43.00 27.77 43.00 27.77
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 43.00 27.77 43.00 27.77



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: DATACENTER_MID_ZN_6

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 39.83 27.78 39.83 27.78
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   39.83 27.78 39.83 27.78
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 39.83 27.78 39.83 27.78



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 27.83 27.75 27.83 27.75
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   27.83 27.75 27.83 27.75
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 27.83 27.75 27.83 27.75



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 55.83 27.99 52.33 27.99
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 408.83 28.99 361.00 29.02
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   464.67 28.87 413.33 28.90
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 408.83 28.99 361.00 29.02



Table of Contents

Report: ComfortReportSimple55Monthly

For: BASEMENT

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 229.33 23.98 65.17 24.26 0.00 24.26
February 147.83 24.19 88.83 24.60 11.50 24.70
March 54.50 24.01 178.67 24.68 1.00 24.68
April 53.50 24.59 268.17 24.76 34.67 24.77
May 146.33 24.61 437.50 24.55 140.83 24.57
June 212.17 24.62 456.83 24.54 212.17 24.56
July 284.67 25.06 497.00 24.78 284.67 24.85
August 249.00 25.00 514.00 24.66 249.00 24.74
September 156.33 25.27 476.67 24.75 156.33 24.85
October 43.67 25.43 317.17 25.01 43.67 25.05
November 36.33 25.14 220.00 25.29 22.83 25.33
December 73.50 24.00 162.67 25.02 1.17 25.02
             
Annual Sum or Average 1687.17 24.67 3682.67 24.71 1157.83 24.76
Minimum of Months 36.33 23.98 65.17 24.26 0.00 24.26
Maximum of Months 284.67 25.43 514.00 25.29 284.67 25.33



Table of Contents

Report: ComfortReportSimple55Monthly

For: CORE_BOTTOM

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 350.17 23.61 45.50 23.73 12.83 23.80
February 206.50 23.62 54.33 23.87 0.00 23.87
March 69.33 23.75 180.17 24.33 0.00 24.33
April 13.00 23.79 293.00 24.39 0.00 24.39
May 12.67 23.65 424.00 24.25 0.00 24.25
June 2.83 23.68 447.50 24.21 0.00 24.21
July 0.00 0.00 493.00 24.18 0.00 24.18
August 0.00 0.00 514.00 24.11 0.00 24.11
September 1.00 23.17 458.33 24.30 0.00 24.30
October 17.17 23.58 304.33 24.49 0.00 24.49
November 52.17 23.77 186.33 24.57 0.00 24.57
December 133.33 23.72 132.00 24.36 0.00 24.36
             
Annual Sum or Average 858.17 23.65 3532.50 24.21 12.83 24.22
Minimum of Months 0.00 0.00 45.50 23.73 0.00 23.80
Maximum of Months 350.17 23.79 514.00 24.57 12.83 24.57



Table of Contents

Report: ComfortReportSimple55Monthly

For: CORE_MID

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 500.33 21.93 57.00 21.79 57.00 21.67
February 430.00 22.40 35.67 22.27 34.00 22.15
March 294.17 23.20 78.83 23.41 0.00 23.41
April 155.50 23.26 158.33 23.81 0.00 23.81
May 57.67 23.23 286.33 24.06 0.00 24.06
June 41.67 23.29 356.83 24.11 0.00 24.11
July 12.33 23.04 389.17 24.18 0.00 24.18
August 11.17 23.20 422.33 24.15 0.00 24.15
September 37.83 23.01 332.00 24.14 0.00 24.14
October 191.17 23.11 131.33 23.58 0.00 23.58
November 351.33 23.22 37.33 23.31 0.00 23.31
December 460.67 22.55 13.33 22.58 0.83 22.58
             
Annual Sum or Average 2543.83 22.70 2298.50 23.35 91.83 23.30
Minimum of Months 11.17 21.93 13.33 21.79 0.00 21.67
Maximum of Months 500.33 23.29 422.33 24.18 57.00 24.18



Table of Contents

Report: ComfortReportSimple55Monthly

For: CORE_TOP

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 499.83 20.80 213.33 20.46 213.33 20.28
February 444.50 21.54 90.50 21.25 89.67 21.05
March 398.17 22.52 74.33 22.67 13.00 22.62
April 242.83 22.88 135.33 23.35 0.00 23.35
May 89.67 23.11 300.50 23.95 0.00 23.95
June 36.00 23.24 373.33 24.14 0.00 24.14
July 13.17 22.68 429.00 24.18 0.00 24.18
August 2.00 23.22 447.33 24.19 0.00 24.19
September 81.67 22.83 306.33 23.94 0.00 23.94
October 329.83 22.52 85.67 22.85 0.00 22.85
November 454.83 22.16 43.67 22.11 31.17 22.03
December 483.50 21.28 139.00 21.02 133.17 20.83
             
Annual Sum or Average 3076.00 21.91 2638.33 22.61 480.33 22.39
Minimum of Months 2.00 20.80 43.67 20.46 0.00 20.28
Maximum of Months 499.83 23.24 447.33 24.19 213.33 24.19



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 484.67 21.36 177.50 21.16 177.50 21.05
February 415.33 21.96 88.33 21.74 83.17 21.56
March 339.00 22.96 86.50 23.20 0.00 23.20
April 144.50 23.15 208.50 23.81 0.00 23.81
May 43.50 23.30 378.33 24.19 0.00 24.19
June 8.50 24.12 452.83 24.32 2.17 24.33
July 8.00 26.52 491.67 24.41 8.00 24.44
August 2.50 26.88 511.50 24.27 2.50 24.28
September 50.17 23.91 399.33 24.30 14.50 24.35
October 255.83 23.05 158.00 23.51 6.17 23.53
November 373.33 22.84 56.67 23.00 3.00 22.99
December 449.67 22.22 48.83 22.23 25.17 22.16
             
Annual Sum or Average 2575.00 22.41 3058.00 23.25 322.17 23.14
Minimum of Months 2.50 21.36 48.83 21.16 0.00 21.05
Maximum of Months 484.67 26.88 511.50 24.41 177.50 24.44



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 497.33 21.52 131.17 21.33 131.17 21.20
February 392.83 21.84 64.83 21.78 52.33 21.65
March 314.00 22.60 95.33 23.00 0.00 23.00
April 157.00 22.85 213.50 23.64 3.17 23.67
May 80.33 23.73 373.67 24.29 15.83 24.38
June 27.67 25.44 439.00 24.40 17.17 24.49
July 37.50 25.81 449.17 24.50 27.83 24.63
August 28.67 25.52 455.00 24.32 18.67 24.41
September 83.17 23.70 356.67 24.27 22.67 24.36
October 241.33 22.68 173.50 23.39 8.33 23.43
November 380.83 22.55 49.83 22.75 2.67 22.74
December 464.00 21.98 34.50 22.00 19.33 21.95
             
Annual Sum or Average 2704.67 22.37 2836.17 23.24 319.17 23.22
Minimum of Months 27.67 21.52 34.50 21.33 0.00 21.20
Maximum of Months 497.33 25.81 455.00 24.50 131.17 24.63



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 398.17 21.66 123.83 21.61 99.33 21.43
February 334.33 22.17 79.83 22.30 43.67 22.20
March 233.67 22.86 160.50 23.51 2.50 23.52
April 133.50 23.09 250.33 23.90 3.67 23.93
May 61.67 23.32 371.83 24.18 2.83 24.20
June 20.67 24.41 440.17 24.32 7.17 24.35
July 24.00 26.41 489.17 24.48 22.17 24.58
August 23.33 26.84 512.17 24.41 23.33 24.52
September 67.00 24.54 416.50 24.45 31.33 24.57
October 195.83 23.32 259.83 23.98 28.50 24.13
November 265.67 23.03 134.00 23.57 17.33 23.66
December 341.67 22.30 78.33 22.57 19.17 22.50
             
Annual Sum or Average 2099.50 22.68 3316.50 23.62 301.00 23.61
Minimum of Months 20.67 21.66 78.33 21.61 2.50 21.43
Maximum of Months 398.17 26.84 512.17 24.48 99.33 24.58



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 453.00 21.67 80.50 21.62 70.17 21.52
February 322.67 22.26 73.17 22.51 24.50 22.44
March 136.17 23.36 251.83 24.15 9.00 24.21
April 43.00 25.25 395.50 24.67 23.67 24.79
May 32.33 24.53 432.67 24.44 13.00 24.50
June 31.17 26.73 483.67 24.60 28.83 24.73
July 44.67 26.99 497.00 24.76 44.67 24.93
August 46.50 26.87 514.00 24.66 46.50 24.83
September 54.83 25.00 437.50 24.54 30.17 24.66
October 136.50 23.45 290.33 24.24 19.00 24.35
November 177.33 23.17 178.83 23.94 8.00 24.01
December 271.83 23.01 93.67 23.44 0.33 23.44
             
Annual Sum or Average 1750.00 23.02 3728.67 23.99 317.83 24.05
Minimum of Months 31.17 21.67 73.17 21.62 0.33 21.52
Maximum of Months 453.00 26.99 514.00 24.76 70.17 24.93



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_MID_ZN_3

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 502.00 20.25 401.00 20.14 401.00 20.10
February 450.83 20.83 218.00 20.60 218.00 20.48
March 453.17 21.84 92.83 21.86 53.50 21.74
April 302.33 22.49 108.50 22.86 12.33 22.83
May 126.17 23.01 299.67 23.86 7.33 23.87
June 36.67 24.06 422.33 24.27 13.83 24.30
July 38.17 24.86 475.00 24.42 29.17 24.48
August 20.50 25.30 502.00 24.34 19.83 24.38
September 125.67 23.37 293.00 24.02 28.67 24.10
October 406.00 22.08 83.17 22.36 21.00 22.39
November 479.50 21.49 106.83 21.33 102.33 21.20
December 497.00 20.59 286.67 20.39 286.67 20.30
             
Annual Sum or Average 3438.00 21.51 3289.00 22.20 1193.67 21.96
Minimum of Months 20.50 20.25 83.17 20.14 7.33 20.10
Maximum of Months 502.00 25.30 502.00 24.42 401.00 24.48



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_MID_ZN_2

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 427.00 20.32 319.33 20.20 319.33 20.15
February 367.50 20.96 163.50 20.73 160.17 20.59
March 353.83 21.98 59.00 22.12 21.83 22.04
April 213.17 22.47 128.50 23.18 9.33 23.21
May 130.33 23.32 257.33 24.13 23.00 24.25
June 47.17 25.08 354.33 24.53 28.33 24.66
July 75.50 25.55 381.33 24.77 58.17 24.96
August 44.33 26.08 391.17 24.64 39.17 24.79
September 137.83 23.29 249.50 24.06 33.17 24.20
October 294.67 22.02 100.33 22.55 18.50 22.58
November 399.17 21.58 56.33 21.50 50.83 21.39
December 422.00 20.62 218.00 20.41 218.00 20.31
             
Annual Sum or Average 2912.50 21.72 2678.67 22.44 979.83 22.28
Minimum of Months 44.33 20.32 56.33 20.20 9.33 20.15
Maximum of Months 427.00 26.08 391.17 24.77 319.33 24.96



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_MID_ZN_1

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 428.67 21.05 226.33 20.82 215.67 20.64
February 373.33 21.57 142.00 21.52 115.83 21.35
March 301.00 22.30 136.50 22.82 19.50 22.74
April 203.50 22.65 185.00 23.43 10.67 23.44
May 111.33 23.03 322.17 23.96 8.33 23.98
June 50.33 24.10 413.50 24.29 18.33 24.34
July 48.00 25.38 469.67 24.52 40.33 24.61
August 39.17 26.20 507.50 24.51 39.17 24.62
September 99.50 24.11 368.67 24.37 41.00 24.51
October 251.83 22.73 226.50 23.54 37.17 23.68
November 335.67 22.39 114.67 22.81 35.00 22.80
December 388.50 21.35 149.00 21.26 116.00 21.04
             
Annual Sum or Average 2630.83 22.18 3261.50 23.07 697.00 22.94
Minimum of Months 39.17 21.05 114.67 20.82 8.33 20.64
Maximum of Months 428.67 26.20 507.50 24.52 215.67 24.62



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_MID_ZN_4

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 502.00 20.61 311.17 20.41 311.17 20.33
February 429.83 21.06 160.33 20.88 152.33 20.74
March 374.17 21.91 103.33 22.27 23.50 22.20
April 232.83 22.57 193.67 23.39 13.50 23.45
May 129.83 23.11 329.17 23.99 16.83 24.07
June 55.00 24.51 422.33 24.40 25.00 24.50
July 54.17 25.37 462.83 24.56 40.67 24.69
August 33.50 26.51 500.00 24.53 32.50 24.65
September 135.67 23.41 323.50 24.12 36.17 24.26
October 347.67 22.16 122.33 22.71 19.67 22.78
November 437.83 21.65 75.33 21.64 56.50 21.54
December 490.33 20.95 189.67 20.73 186.83 20.60
             
Annual Sum or Average 3222.83 21.75 3193.67 22.59 914.67 22.43
Minimum of Months 33.50 20.61 75.33 20.41 13.50 20.33
Maximum of Months 502.00 26.51 500.00 24.56 311.17 24.69



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 502.00 19.99 423.83 19.89 423.83 19.85
February 451.50 20.58 279.33 20.38 279.33 20.29
March 459.67 21.42 152.50 21.37 114.50 21.20
April 326.17 22.13 120.67 22.43 34.83 22.34
May 155.17 22.75 289.83 23.69 10.50 23.70
June 60.50 24.03 412.67 24.27 22.83 24.34
July 62.67 24.90 466.33 24.47 46.33 24.57
August 37.00 25.41 496.00 24.40 33.50 24.47
September 177.33 23.03 278.17 23.80 30.50 23.87
October 417.67 21.62 116.00 21.80 60.50 21.72
November 482.17 20.95 207.67 20.72 207.00 20.59
December 497.00 20.21 356.50 20.03 356.50 19.96
             
Annual Sum or Average 3628.83 21.26 3599.50 21.89 1620.17 21.63
Minimum of Months 37.00 19.99 116.00 19.89 10.50 19.85
Maximum of Months 502.00 25.41 496.00 24.47 423.83 24.57



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 502.00 20.08 400.17 19.97 400.17 19.92
February 447.67 20.84 229.00 20.57 229.00 20.43
March 425.00 21.77 103.17 21.82 58.67 21.68
April 253.50 22.25 169.17 22.94 22.83 22.89
May 141.67 23.10 324.50 24.01 25.17 24.11
June 63.17 24.86 431.67 24.46 36.33 24.59
July 90.33 25.31 446.67 24.67 65.67 24.86
August 60.33 25.77 470.33 24.57 49.17 24.72
September 165.50 22.97 308.67 23.87 33.67 23.99
October 344.33 21.70 137.83 22.15 42.50 22.07
November 478.33 21.19 141.50 20.99 141.50 20.86
December 497.00 20.28 318.67 20.07 318.67 19.98
             
Annual Sum or Average 3468.83 21.47 3481.33 22.17 1423.33 21.96
Minimum of Months 60.33 20.08 103.17 19.97 22.83 19.92
Maximum of Months 502.00 25.77 470.33 24.67 400.17 24.86



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 453.17 20.66 279.00 20.37 274.67 20.21
February 384.67 21.14 201.33 21.02 176.33 20.81
March 331.50 21.84 159.00 22.21 59.33 22.02
April 244.17 22.25 175.50 22.95 27.17 22.91
May 148.00 22.78 303.83 23.78 13.00 23.80
June 73.50 23.87 396.83 24.26 24.33 24.33
July 71.50 25.05 451.00 24.53 52.67 24.65
August 47.67 25.89 496.17 24.51 44.33 24.63
September 138.83 23.49 336.00 24.15 42.33 24.29
October 282.00 22.18 216.00 23.00 48.50 23.05
November 364.50 21.71 149.67 21.91 87.67 21.74
December 422.50 20.86 215.33 20.59 197.50 20.36
             
Annual Sum or Average 2962.00 21.80 3379.67 22.61 1047.83 22.41
Minimum of Months 47.67 20.66 149.67 20.37 13.00 20.21
Maximum of Months 453.17 25.89 496.17 24.53 274.67 24.65



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 502.00 20.26 357.17 20.08 357.17 20.00
February 434.00 20.81 214.83 20.62 207.83 20.49
March 390.83 21.56 131.33 21.81 61.17 21.67
April 269.17 22.24 178.33 23.00 26.00 23.03
May 162.83 22.80 307.33 23.80 18.83 23.87
June 77.83 24.04 405.33 24.34 28.83 24.46
July 69.17 24.90 445.83 24.53 45.00 24.66
August 46.17 26.01 483.83 24.54 39.33 24.68
September 175.67 23.00 286.33 23.88 37.67 24.02
October 368.50 21.79 120.00 22.32 26.33 22.36
November 450.83 21.23 140.17 21.11 127.50 20.97
December 493.17 20.54 275.50 20.29 274.67 20.17
             
Annual Sum or Average 3440.17 21.48 3346.00 22.24 1250.33 22.04
Minimum of Months 46.17 20.26 120.00 20.08 18.83 20.00
Maximum of Months 502.00 26.01 483.83 24.54 357.17 24.68



Table of Contents

Report: ComfortReportSimple55Monthly

For: GROUNDFLOOR_PLENUM

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00
             
Annual Sum or Average 0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: ComfortReportSimple55Monthly

For: MIDFLOOR_PLENUM

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00
             
Annual Sum or Average 0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: ComfortReportSimple55Monthly

For: TOPFLOOR_PLENUM

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00
             
Annual Sum or Average 0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: ComfortReportSimple55Monthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 488.83 27.00 0.00 27.00
February 0.83 27.00 454.00 27.00 0.83 27.00
March 54.00 27.00 514.00 27.00 54.00 27.00
April 205.33 27.00 485.00 27.00 205.33 27.00
May 18.50 27.00 508.00 27.00 18.50 27.00
June 189.17 27.00 496.00 27.00 189.17 27.00
July 268.33 27.00 497.00 27.00 268.33 27.00
August 469.83 27.12 514.00 27.12 469.83 27.12
September 57.83 27.00 485.00 27.00 57.83 27.00
October 49.67 27.00 502.00 27.00 49.67 27.00
November 29.33 27.00 489.00 27.00 29.33 27.00
December 27.83 27.00 497.00 27.00 27.83 27.00
             
Annual Sum or Average 1370.67 27.04 5929.83 27.02 1370.67 27.02
Minimum of Months 0.00 0.00 454.00 27.00 0.00 27.00
Maximum of Months 469.83 27.12 514.00 27.12 469.83 27.12



Table of Contents

Report: ComfortReportSimple55Monthly

For: DATACENTER_MID_ZN_6

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 39.17 25.61 320.00 26.84 0.00 26.84
February 2.50 27.00 381.17 27.00 0.00 27.00
March 1.67 27.00 508.67 27.00 1.67 27.00
April 10.67 27.00 485.00 27.00 10.67 27.00
May 0.00 0.00 508.00 27.00 0.00 27.00
June 16.17 27.00 496.00 27.00 16.17 27.00
July 67.00 27.00 497.00 27.00 67.00 27.00
August 147.67 27.36 514.00 27.16 147.67 27.20
September 9.33 27.00 485.00 27.00 9.33 27.00
October 1.00 27.00 502.00 27.00 1.00 27.00
November 0.00 0.00 488.83 27.00 0.00 27.00
December 0.00 0.00 475.50 27.00 0.00 27.00
             
Annual Sum or Average 295.17 27.00 5661.17 27.01 253.50 27.02
Minimum of Months 0.00 0.00 320.00 26.84 0.00 26.84
Maximum of Months 147.67 27.36 514.00 27.16 147.67 27.20



Table of Contents

Report: ComfortReportSimple55Monthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 161.17 24.58 246.67 25.75 26.83 25.55
February 27.67 26.90 337.33 26.99 0.00 26.99
March 6.00 27.00 485.83 27.00 6.00 27.00
April 33.50 27.00 485.00 27.00 33.50 27.00
May 14.50 27.00 508.00 27.00 14.50 27.00
June 91.83 27.00 496.00 27.00 91.83 27.00
July 142.17 27.00 497.00 27.00 142.17 27.00
August 192.67 27.20 514.00 27.11 192.67 27.13
September 29.83 27.00 485.00 27.00 29.83 27.00
October 6.17 27.00 502.00 27.00 6.17 27.00
November 0.00 0.00 444.17 27.00 0.00 27.00
December 10.50 27.00 375.33 27.00 0.00 27.00
             
Annual Sum or Average 716.00 26.51 5376.33 26.93 543.50 26.92
Minimum of Months 0.00 0.00 246.67 25.75 0.00 25.55
Maximum of Months 192.67 27.20 514.00 27.11 192.67 27.13



Table of Contents

Report: ComfortReportSimple55Monthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 256.33 27.00 502.00 27.00 256.33 27.00
February 454.00 27.00 454.00 27.00 454.00 27.00
March 514.00 27.00 514.00 27.00 514.00 27.00
April 485.00 27.13 485.00 27.13 485.00 27.13
May 495.83 27.00 508.00 27.00 495.83 27.00
June 496.00 27.00 496.00 27.00 496.00 27.00
July 497.00 27.00 497.00 27.00 497.00 27.00
August 514.00 28.49 514.00 28.49 514.00 28.49
September 485.00 27.00 485.00 27.00 485.00 27.00
October 502.00 27.00 502.00 27.00 502.00 27.00
November 489.00 27.00 489.00 27.00 489.00 27.00
December 497.00 27.01 497.00 27.01 497.00 27.01
             
Annual Sum or Average 5685.17 27.15 5943.00 27.14 5685.17 27.15
Minimum of Months 256.33 27.00 454.00 27.00 256.33 27.00
Maximum of Months 514.00 28.49 514.00 28.49 514.00 28.49



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 27.00007 21.67254 0.71771 16.07520
February 454.00000 27.00011 24.19899 0.80529 18.89424
March 514.00000 27.00018 29.06260 0.93446 23.57957
April 485.00000 27.00009 32.64999 1.01741 26.92487
May 508.00000 27.00091 36.69868 0.29496 6.90963
June 496.00000 27.00149 37.51801 0.37363 7.98892
July 497.00000 27.00102 37.99668 0.42229 8.78240
August 514.00000 27.11281 37.94602 0.50363 10.51052
September 485.00000 27.00080 38.49236 0.32209 7.25163
October 502.00000 27.00068 33.74169 0.95108 24.17771
November 489.00000 27.00016 27.51402 0.91419 22.77901
December 497.00000 27.00004 24.86604 0.89337 22.00005
           
Annual Sum or Average 5943.00000 27.01022 31.91986 0.67781 16.28694
Minimum of Months 454.00000 27.00004 21.67254 0.29496 6.90963
Maximum of Months 514.00000 27.11281 38.49236 1.01741 26.92487



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: DATACENTER_MID_ZN_6

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 26.85130 22.01578 0.55787 12.14140
February 454.00000 27.00010 24.20188 0.66223 14.52401
March 514.00000 27.00018 29.03507 0.80887 19.01359
April 485.00000 27.00010 32.61897 0.89636 22.09748
May 508.00000 27.00056 36.84853 0.22319 6.18416
June 496.00000 27.00152 37.56352 0.28958 6.87116
July 497.00000 27.00110 38.02464 0.32269 7.26488
August 514.00000 27.10336 37.96472 0.37918 8.22189
September 485.00000 27.00045 38.74857 0.24361 6.38138
October 502.00000 27.00063 33.78825 0.84597 20.23166
November 489.00000 27.00016 27.49007 0.76366 17.47394
December 497.00000 27.00005 24.84193 0.69176 15.27238
           
Annual Sum or Average 5943.00000 26.99678 31.98558 0.55587 12.94832
Minimum of Months 454.00000 26.85130 22.01578 0.22319 6.18416
Maximum of Months 514.00000 27.10336 38.74857 0.89636 22.09748



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 26.18151 22.60851 0.37623 10.76108
February 454.00000 26.99416 24.23323 0.61494 13.39375
March 514.00000 27.00018 29.05853 0.76890 17.81870
April 485.00000 27.00012 32.64023 0.87316 21.34605
May 508.00000 27.00067 36.86787 0.22169 6.29024
June 496.00000 27.00153 37.56400 0.30268 7.12113
July 497.00000 27.00109 38.03624 0.33913 7.56945
August 514.00000 27.07618 37.99872 0.38951 8.42334
September 485.00000 27.00048 38.83428 0.23268 6.38387
October 502.00000 27.00064 33.85901 0.80761 18.99784
November 489.00000 27.00016 27.52193 0.70200 15.66940
December 497.00000 27.00005 24.86063 0.62711 13.59290
           
Annual Sum or Average 5943.00000 26.93742 32.06457 0.52019 12.26059
Minimum of Months 454.00000 26.18151 22.60851 0.22169 6.29024
Maximum of Months 514.00000 27.07618 38.83428 0.87316 21.34605



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 27.00090 30.99947 1.02117 27.05237
February 454.00000 27.00241 31.23904 1.19137 34.84713
March 514.00000 27.00230 32.57546 1.36444 43.63653
April 485.00000 27.13275 33.84875 1.53080 52.57347
May 508.00000 27.00201 36.15900 0.51086 10.52213
June 496.00000 27.00190 37.16575 0.77032 17.54079
July 497.00000 27.00107 37.69953 0.98316 25.44286
August 514.00000 28.48862 36.73902 1.59914 56.04440
September 485.00000 27.00271 37.30895 0.61177 12.90425
October 502.00000 27.00090 34.06680 1.29130 39.83869
November 489.00000 27.00339 32.03506 1.40886 45.99114
December 497.00000 27.00517 31.28693 1.50930 51.40777
           
Annual Sum or Average 5943.00000 27.14147 34.28224 1.14983 34.85151
Minimum of Months 454.00000 27.00090 30.99947 0.51086 10.52213
Maximum of Months 514.00000 28.48862 37.69953 1.59914 56.04440



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: BASEMENT

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 24.36501 22.36393 0.31302 7.54908
February 454.00000 24.38965 25.99307 0.35060 8.24486
March 514.00000 24.37470 32.42123 0.40741 8.90994
April 485.00000 24.45602 39.77637 0.47666 10.32524
May 508.00000 24.46158 52.94896 -0.2810 7.64928
June 496.00000 24.45601 56.65876 -0.2363 7.10605
July 497.00000 24.60972 62.38679 -0.1428 6.87416
August 514.00000 24.49134 61.22087 -0.1740 6.83006
September 485.00000 24.56908 56.76139 -0.1835 7.25412
October 502.00000 24.60040 41.94365 0.54978 12.18384
November 489.00000 24.60343 29.95989 0.46280 10.31894
December 497.00000 24.53872 26.24935 0.40893 9.24886
           
Annual Sum or Average 5943.00000 24.49308 42.52726 0.16038 8.53693
Minimum of Months 454.00000 24.36501 22.36393 -0.2810 6.83006
Maximum of Months 514.00000 24.60972 62.38679 0.54978 12.18384



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: CORE_BOTTOM

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 23.78324 26.46314 0.20948 6.97336
February 454.00000 23.96258 27.15449 0.27229 7.10850
March 514.00000 24.18279 32.49899 0.39076 8.59233
April 485.00000 24.24771 38.63013 0.46051 9.73983
May 508.00000 24.19928 45.98984 -0.3728 8.35320
June 496.00000 24.19040 46.35196 -0.3515 7.86332
July 497.00000 24.17125 48.16986 -0.3384 7.55699
August 514.00000 24.11255 48.18771 -0.3431 7.52655
September 485.00000 24.26830 47.99087 -0.3262 7.72809
October 502.00000 24.29394 40.69145 0.47620 10.12693
November 489.00000 24.31746 30.30199 0.40340 8.81547
December 497.00000 24.27148 27.67430 0.36023 8.29695
           
Annual Sum or Average 5943.00000 24.16738 38.43001 0.06763 8.22858
Minimum of Months 454.00000 23.78324 26.46314 -0.3728 6.97336
Maximum of Months 514.00000 24.31746 48.18771 0.47620 10.12693



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: CORE_MID

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 21.93798 28.69992 -0.2567 7.66778
February 454.00000 22.48776 29.62861 -0.1021 6.96981
March 514.00000 23.58349 34.54774 0.22174 6.76265
April 485.00000 23.86032 40.25906 0.33932 7.88375
May 508.00000 23.96318 47.00023 -0.4744 10.21710
June 496.00000 24.03291 47.26425 -0.4314 9.38521
July 497.00000 24.06601 49.12981 -0.4081 8.88988
August 514.00000 24.06618 49.11030 -0.4018 8.72857
September 485.00000 24.01712 49.18811 -0.4361 9.53074
October 502.00000 23.73028 42.71272 0.31649 7.55730
November 489.00000 23.46394 32.83196 0.16793 6.28913
December 497.00000 22.64653 31.52717 -0.0540 6.05877
           
Annual Sum or Average 5943.00000 23.49504 40.23947 -0.1276 8.00371
Minimum of Months 454.00000 21.93798 28.69992 -0.4744 6.05877
Maximum of Months 514.00000 24.06618 49.18811 0.33932 10.21710



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: CORE_TOP

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 20.80934 28.72600 -0.5576 15.12663
February 454.00000 21.58645 31.06820 -0.3326 10.50043
March 514.00000 22.85421 36.25807 0.04260 6.93090
April 485.00000 23.47277 41.24926 0.24506 7.34281
May 508.00000 23.90225 47.04670 -0.4888 10.76858
June 496.00000 24.06146 46.97994 -0.4069 9.05451
July 497.00000 24.12145 48.77097 -0.3729 8.38074
August 514.00000 24.12203 48.75331 -0.3665 8.12753
September 485.00000 23.87984 49.69923 -0.4803 10.70282
October 502.00000 23.02383 44.64758 0.14223 6.73990
November 489.00000 22.27879 35.06833 -0.1252 7.00452
December 497.00000 21.34945 32.26713 -0.3882 10.85762
           
Annual Sum or Average 5943.00000 22.96593 40.95078 -0.2574 9.28563
Minimum of Months 454.00000 20.80934 28.72600 -0.5576 6.73990
Maximum of Months 514.00000 24.12203 49.69923 0.24506 15.12663



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 21.44517 26.02644 -0.3942 10.22619
February 454.00000 22.13236 28.07163 -0.1965 8.50497
March 514.00000 23.33182 33.36227 0.15446 6.85022
April 485.00000 23.85314 39.02099 0.34353 8.36951
May 508.00000 24.13418 45.91655 -0.3971 9.15532
June 496.00000 24.28463 45.82166 -0.2869 7.32620
July 497.00000 24.36701 47.77060 -0.2340 6.87634
August 514.00000 24.25229 47.71226 -0.2635 6.92991
September 485.00000 24.19875 48.73355 -0.3574 8.65503
October 502.00000 23.56857 42.47461 0.27592 7.59781
November 489.00000 23.12390 32.02890 0.08182 6.59120
December 497.00000 22.38344 28.66330 -0.1275 6.97031
           
Annual Sum or Average 5943.00000 23.43198 38.88074 -0.1170 7.83079
Minimum of Months 454.00000 21.44517 26.02644 -0.3971 6.59120
Maximum of Months 514.00000 24.36701 48.73355 0.34353 10.22619



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 21.54640 25.55450 -0.3569 9.44227
February 454.00000 22.16583 27.74172 -0.1664 8.22317
March 514.00000 23.19390 33.23176 0.15605 7.17042
April 485.00000 23.67727 39.07604 0.34655 8.77535
May 508.00000 24.13477 45.40917 -0.3291 9.22318
June 496.00000 24.25054 45.54044 -0.2378 7.41681
July 497.00000 24.29275 47.55075 -0.2009 7.44055
August 514.00000 24.13823 47.73362 -0.2551 7.57296
September 485.00000 24.06945 48.56365 -0.3367 9.28187
October 502.00000 23.43804 42.25437 0.28171 8.33179
November 489.00000 22.91604 31.98182 0.05795 6.73277
December 497.00000 22.11674 28.79215 -0.1714 7.13316
           
Annual Sum or Average 5943.00000 23.33696 38.69993 -0.1012 8.05844
Minimum of Months 454.00000 21.54640 25.55450 -0.3569 6.73277
Maximum of Months 514.00000 24.29275 48.56365 0.34655 9.44227



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 22.22903 25.01730 -0.1893 9.47507
February 454.00000 22.72550 27.16927 -0.0295 8.60092
March 514.00000 23.61768 32.47424 0.25808 8.31846
April 485.00000 23.89926 38.62598 0.38085 9.30265
May 508.00000 24.11506 45.84285 -0.3874 9.37751
June 496.00000 24.25841 45.87552 -0.2940 7.63169
July 497.00000 24.37700 47.70347 -0.2235 7.02352
August 514.00000 24.30225 47.38110 -0.2115 6.81788
September 485.00000 24.28298 48.15932 -0.2756 8.29732
October 502.00000 23.84233 41.22281 0.39380 10.21723
November 489.00000 23.59185 30.64024 0.23467 8.56957
December 497.00000 22.91128 27.65823 0.02965 7.65457
           
Annual Sum or Average 5943.00000 23.68597 38.23055 -0.0269 8.43699
Minimum of Months 454.00000 22.22903 25.01730 -0.3874 6.81788
Maximum of Months 514.00000 24.37700 48.15932 0.39380 10.21723



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 21.92639 24.65961 -0.2377 8.27388
February 454.00000 22.84159 26.18181 0.02775 7.83035
March 514.00000 24.07070 31.12653 0.41715 10.00181
April 485.00000 24.46439 36.91212 0.60616 13.82173
May 508.00000 24.28330 44.83521 -0.2344 7.74339
June 496.00000 24.44537 44.75390 -0.0993 6.63156
July 497.00000 24.55594 46.44242 -0.0187 6.72352
August 514.00000 24.46385 46.30391 0.00091 6.48688
September 485.00000 24.35006 47.50629 -0.1979 7.68036
October 502.00000 24.07083 40.32136 0.46878 10.97784
November 489.00000 23.94269 29.56873 0.34222 9.04876
December 497.00000 23.62869 25.92400 0.22320 7.48319
           
Annual Sum or Average 5943.00000 23.92714 37.12748 0.10805 8.55318
Minimum of Months 454.00000 21.92639 24.65961 -0.2377 6.48688
Maximum of Months 514.00000 24.55594 47.50629 0.60616 13.82173



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 20.25330 27.77397 -0.7602 19.87894
February 454.00000 20.85511 29.96840 -0.5604 14.60707
March 514.00000 22.08364 35.86981 -0.1585 7.84919
April 485.00000 23.06987 41.67625 0.13938 7.35293
May 508.00000 23.83616 47.75425 -0.5151 11.92970
June 496.00000 24.19949 47.57933 -0.3364 8.21734
July 497.00000 24.34162 50.38176 -0.2623 7.36956
August 514.00000 24.28396 50.42784 -0.2812 7.29136
September 485.00000 23.88503 51.36019 -0.4779 11.29045
October 502.00000 22.43596 46.11786 -0.0032 6.91876
November 489.00000 21.53213 35.48093 -0.3174 8.96059
December 497.00000 20.59376 31.59987 -0.6068 15.19212
           
Annual Sum or Average 5943.00000 22.62798 41.41554 -0.3439 10.54002
Minimum of Months 454.00000 20.25330 27.77397 -0.7602 6.91876
Maximum of Months 514.00000 24.34162 51.36019 0.13938 19.87894



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 427.00000 20.32353 26.50840 -0.7247 18.24511
February 385.00000 21.11268 28.81098 -0.4758 13.18482
March 433.00000 22.37014 34.32017 -0.0665 7.36734
April 410.00000 23.28614 40.46000 0.22967 8.27772
May 430.00000 23.94008 46.55759 -0.4189 11.81253
June 418.00000 24.29729 46.70426 -0.2469 8.16894
July 422.00000 24.46251 49.30979 -0.1639 8.13520
August 433.00000 24.36645 49.53166 -0.2014 7.70370
September 410.00000 23.85254 50.71198 -0.4306 12.00322
October 427.00000 22.67655 44.55662 0.07882 7.65109
November 417.00000 21.68813 34.14239 -0.2606 8.16269
December 422.00000 20.61985 30.65251 -0.5799 14.04130
           
Annual Sum or Average 5034.00000 22.75972 40.25605 -0.2708 10.37567
Minimum of Months 385.00000 20.32353 26.50840 -0.7247 7.36734
Maximum of Months 433.00000 24.46251 50.71198 0.22967 18.24511



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 21.55025 26.07725 -0.3860 13.24962
February 454.00000 22.06332 28.22362 -0.2175 10.69157
March 514.00000 23.11878 33.66648 0.12479 8.18720
April 485.00000 23.53565 40.26936 0.27785 8.64981
May 508.00000 23.92124 47.30635 -0.4661 11.21744
June 496.00000 24.18763 47.57305 -0.3353 8.47137
July 497.00000 24.37411 50.21453 -0.2422 7.45323
August 514.00000 24.36520 49.81409 -0.2154 7.07509
September 485.00000 24.14308 49.99414 -0.3305 9.57700
October 502.00000 23.43588 42.93505 0.28923 9.79448
November 489.00000 22.98928 32.35145 0.07952 8.66822
December 497.00000 21.97858 29.41043 -0.2161 10.46460
           
Annual Sum or Average 5943.00000 23.31463 39.90675 -0.1365 9.44828
Minimum of Months 454.00000 21.55025 26.07725 -0.4661 7.07509
Maximum of Months 514.00000 24.37411 50.21453 0.28923 13.24962



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 20.60633 26.68220 -0.6359 16.04662
February 454.00000 21.23215 28.81903 -0.4286 12.14295
March 514.00000 22.52294 34.36824 -0.0060 7.82469
April 485.00000 23.38968 40.33483 0.27542 8.93013
May 508.00000 23.87247 46.89364 -0.4193 11.13701
June 496.00000 24.22491 46.84933 -0.2472 8.09026
July 497.00000 24.37104 49.40558 -0.1735 7.55462
August 514.00000 24.37387 49.14051 -0.1633 7.09347
September 485.00000 23.90541 50.40525 -0.3931 11.06223
October 502.00000 22.74896 44.45589 0.11400 7.86410
November 489.00000 21.91383 34.01631 -0.1910 8.04697
December 497.00000 20.98304 30.42757 -0.4775 12.02943
           
Annual Sum or Average 5943.00000 22.85823 40.23185 -0.2277 9.79622
Minimum of Months 454.00000 20.60633 26.68220 -0.6359 7.09347
Maximum of Months 514.00000 24.37387 50.40525 0.27542 16.04662



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 19.99436 28.43147 -0.8660 24.28191
February 454.00000 20.60030 30.48864 -0.6572 17.35031
March 514.00000 21.68733 36.66528 -0.2725 9.82289
April 485.00000 22.73913 42.48850 0.05630 7.75167
May 508.00000 23.70683 48.22068 -0.5495 13.50574
June 496.00000 24.16987 47.74964 -0.3299 8.61798
July 497.00000 24.33821 50.64352 -0.2444 7.63701
August 514.00000 24.29226 50.67368 -0.2599 7.31092
September 485.00000 23.70805 52.20617 -0.5319 13.30045
October 502.00000 22.00672 47.40071 -0.1215 7.95076
November 489.00000 20.98752 36.63588 -0.4795 12.37905
December 497.00000 20.21082 32.44203 -0.7434 20.05506
           
Annual Sum or Average 5943.00000 22.38475 42.08600 -0.4150 12.45611
Minimum of Months 454.00000 19.99436 28.43147 -0.8660 7.31092
Maximum of Months 514.00000 24.33821 52.20617 0.05630 24.28191



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 20.08261 27.83597 -0.8123 22.09626
February 454.00000 20.88816 29.60542 -0.5532 15.18592
March 514.00000 22.14543 35.41339 -0.1296 8.21470
April 485.00000 23.13674 41.13957 0.20009 8.48953
May 508.00000 23.86408 46.93101 -0.4160 11.95130
June 496.00000 24.25189 46.75570 -0.2211 7.98862
July 497.00000 24.37288 49.46432 -0.1496 8.24447
August 514.00000 24.31551 49.57009 -0.1748 7.45261
September 485.00000 23.72550 51.12118 -0.4510 12.88060
October 502.00000 22.43385 45.57956 0.01222 8.13027
November 489.00000 21.23634 35.55272 -0.3903 10.29169
December 497.00000 20.28094 31.87373 -0.6929 18.25790
           
Annual Sum or Average 5943.00000 22.57530 40.98360 -0.3132 11.56378
Minimum of Months 454.00000 20.08261 27.83597 -0.8123 7.45261
Maximum of Months 514.00000 24.37288 51.12118 0.20009 22.09626



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 21.01127 27.01383 -0.5452 17.08823
February 454.00000 21.64670 28.87392 -0.3437 13.00255
March 514.00000 22.70088 34.51703 0.00863 8.99760
April 485.00000 23.18477 41.15501 0.19192 8.71749
May 508.00000 23.75507 47.82174 -0.5102 13.03155
June 496.00000 24.12826 47.77078 -0.3372 9.09613
July 497.00000 24.33239 50.49808 -0.2353 7.85034
August 514.00000 24.34554 50.07221 -0.2020 7.18075
September 485.00000 23.95403 50.82652 -0.3867 11.47175
October 502.00000 23.03728 44.14645 0.17936 9.84088
November 489.00000 22.38039 33.60542 -0.0919 9.71830
December 497.00000 21.35050 30.55240 -0.3973 14.12640
           
Annual Sum or Average 5943.00000 22.99643 40.65691 -0.2220 10.82541
Minimum of Months 454.00000 21.01127 27.01383 -0.5452 7.18075
Maximum of Months 514.00000 24.34554 50.82652 0.19192 17.08823



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 20.26331 27.43903 -0.7535 20.43159
February 454.00000 20.96351 29.28907 -0.5198 14.46145
March 514.00000 22.18579 35.07406 -0.1015 8.93577
April 485.00000 23.06313 41.13508 0.19683 8.96162
May 508.00000 23.69685 47.43003 -0.4651 12.94939
June 496.00000 24.14997 47.10020 -0.2542 8.82409
July 497.00000 24.31490 49.73907 -0.1716 8.08684
August 514.00000 24.33707 49.42898 -0.1558 7.32934
September 485.00000 23.69183 51.23934 -0.4554 13.20797
October 502.00000 22.39299 45.49077 0.01660 8.20875
November 489.00000 21.45563 34.93923 -0.3260 10.04175
December 497.00000 20.56368 31.24921 -0.6096 16.06500
           
Annual Sum or Average 5943.00000 22.60351 40.87780 -0.2984 11.42931
Minimum of Months 454.00000 20.26331 27.43903 -0.7535 7.32934
Maximum of Months 514.00000 24.33707 51.23934 0.19683 20.43159



Table of Contents

Report: ChillerReportMonthly

For: COOLSYS1 CHILLER1

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

CHILLER ELECTRICITY ENERGY [J] CHILLER ELECTRICITY RATE {Maximum} [W] CHILLER ELECTRICITY RATE {TIMESTAMP} CHILLER ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] CHILLER EVAPORATOR COOLING ENERGY [J] CHILLER EVAPORATOR COOLING RATE [] CHILLER CONDENSER HEAT TRANSFER ENERGY [J] CHILLER COP [W/W] CHILLER COP {Maximum} [W/W] CHILLER COP {TIMESTAMP} CHILLER PART LOAD RATIO [] CHILLER PART LOAD RATIO []
January 0.909171E+10 77801.23 19-JAN-16:00 111.97 0.455573E+11 0.00 0.546490E+11 0.68 6.28 19-JAN-16:00 0.00 0.00
February 0.253639E+11 125051.97 28-FEB-15:10 180.71 0.132335E+12 0.00 0.157699E+12 1.27 7.37 28-FEB-15:10 0.00 0.00
March 0.640206E+11 205053.77 30-MAR-14:20 318.15 0.376158E+12 0.00 0.440178E+12 2.21 7.44 30-MAR-15:00 0.00 0.00
April 0.106250E+12 205877.72 19-APR-14:30 415.67 0.684155E+12 0.00 0.790405E+12 3.27 7.56 13-APR-15:50 0.00 0.00
May 0.177046E+12 212100.23 31-MAY-15:10 463.33 0.121691E+13 0.00 0.139395E+13 4.06 7.55 30-MAY-05:05 0.00 0.00
June 0.209996E+12 217534.09 29-JUN-17:10 520.51 0.143789E+13 0.00 0.164789E+13 4.69 7.57 08-JUN-16:00 0.00 0.00
July 0.235485E+12 219776.80 08-JUL-10:30 603.72 0.159202E+13 0.00 0.182750E+13 5.07 7.56 25-JUL-04:13 0.00 0.00
August 0.250731E+12 220161.64 22-AUG-17:10 667.78 0.168477E+13 0.00 0.193550E+13 5.50 7.53 30-AUG-04:14 0.00 0.00
September 0.184706E+12 214327.33 08-SEP-17:00 461.32 0.126856E+13 0.00 0.145327E+13 4.17 7.57 14-SEP-14:20 0.00 0.00
October 0.953931E+11 215501.49 18-OCT-11:40 341.20 0.611798E+12 0.00 0.707191E+12 2.61 7.54 11-OCT-15:50 0.00 0.00
November 0.454398E+11 129892.03 02-NOV-13:10 256.59 0.261590E+12 0.00 0.307030E+12 1.82 7.35 02-NOV-13:40 0.00 0.00
December 0.170016E+11 113800.62 12-DEC-14:00 140.90 0.926918E+11 0.00 0.109693E+12 0.90 7.23 12-DEC-14:00 0.00 0.00
                         
Annual Sum or Average 0.142052E+13     4481.85 0.940444E+13 0.00 0.108250E+14 3.03     0.00 0.00
Minimum of Months 0.909171E+10 77801.23   111.97 0.455573E+11 0.00 0.546490E+11 0.68 6.28   0.00 0.00
Maximum of Months 0.250731E+12 220161.64   667.78 0.168477E+13 0.00 0.193550E+13 5.50 7.57   0.00 0.00



Table of Contents

Report: ChillerReportMonthly

For: COOLSYS1 CHILLER2

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

CHILLER ELECTRICITY ENERGY [J] CHILLER ELECTRICITY RATE {Maximum} [W] CHILLER ELECTRICITY RATE {TIMESTAMP} CHILLER ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] CHILLER EVAPORATOR COOLING ENERGY [J] CHILLER EVAPORATOR COOLING RATE [] CHILLER CONDENSER HEAT TRANSFER ENERGY [J] CHILLER COP [W/W] CHILLER COP {Maximum} [W/W] CHILLER COP {TIMESTAMP} CHILLER PART LOAD RATIO [] CHILLER PART LOAD RATIO []
January 0.00 0.00 01-JAN-00:05 0.00 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 0.00 0.00
March 0.221100E+09 115806.90 30-MAR-15:20 0.67 0.155040E+10 0.00 0.177150E+10 0.01 7.22 30-MAR-15:20 0.00 0.00
April 0.889066E+09 126513.58 18-APR-12:50 2.67 0.623156E+10 0.00 0.712062E+10 0.02 7.36 17-APR-14:05 0.00 0.00
May 0.125177E+11 128595.44 30-MAY-14:40 30.50 0.875754E+11 0.00 0.100093E+12 0.29 7.27 16-MAY-15:50 0.00 0.00
June 0.533738E+11 165625.35 29-JUN-05:04 125.00 0.362713E+12 0.00 0.416087E+12 1.18 7.35 30-JUN-05:02 0.00 0.00
July 0.671516E+11 152024.17 01-JUL-04:14 155.16 0.454189E+12 0.00 0.521340E+12 1.41 7.24 18-JUL-05:06 0.00 0.00
August 0.890941E+11 175880.89 23-AUG-05:02 202.17 0.599587E+12 0.00 0.688681E+12 1.82 7.47 23-AUG-05:02 0.00 0.00
September 0.298639E+11 145408.41 16-SEP-16:07 70.00 0.204394E+12 0.00 0.234257E+12 0.66 7.26 18-SEP-14:30 0.00 0.00
October 0.771405E+10 154880.00 19-OCT-04:15 18.39 0.534671E+11 0.00 0.611811E+11 0.17 7.18 19-OCT-15:20 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 0.00 0.00
                         
Annual Sum or Average 0.260825E+12     604.56 0.176971E+13 0.00 0.203053E+13 0.47     0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00 0.00   0.00 0.00
Maximum of Months 0.890941E+11 175880.89   202.17 0.599587E+12 0.00 0.688681E+12 1.82 7.47   0.00 0.00



Table of Contents

Report: TowerReportMonthly

For: CENTRAL TOWER

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

COOLING TOWER FAN ELECTRICITY ENERGY [J] COOLING TOWER FAN ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] COOLING TOWER FAN ELECTRICITY RATE {Maximum} [W] COOLING TOWER FAN ELECTRICITY RATE {TIMESTAMP} COOLING TOWER HEAT TRANSFER RATE {Maximum} [W] COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} COOLING TOWER INLET TEMPERATURE [C] COOLING TOWER OUTLET TEMPERATURE [C] COOLING TOWER MASS FLOW RATE [kg/s]
January 0.189564E+11 744.00 49248.27 19-JAN-12:00 333566.60 10-JAN-13:43 21.69 18.38 14.28
February 0.502406E+11 672.00 49248.27 01-FEB-19:00 374846.03 09-FEB-11:05 25.12 18.91 14.32
March 0.102535E+12 744.00 49248.27 01-MAR-00:10 596246.11 31-MAR-24:00 29.81 20.51 14.34
April 0.120249E+12 720.00 49248.27 01-APR-09:30 675725.13 17-APR-16:10 35.97 23.65 14.35
May 0.122364E+12 744.00 49248.27 01-MAY-00:03 340252.65 31-MAY-23:40 27.06 23.06 14.35
June 0.126536E+12 720.00 49248.27 01-JUN-00:10 490663.24 30-JUN-24:00 35.33 28.14 14.35
July 0.131907E+12 744.00 49248.27 01-JUL-00:10 653540.79 31-JUL-23:55 41.02 30.78 14.35
August 0.131907E+12 744.00 49248.27 01-AUG-00:03 711405.54 11-AUG-16:30 45.79 32.65 14.35
September 0.123479E+12 720.00 49248.27 01-SEP-00:03 317887.48 30-SEP-24:00 28.68 24.55 14.35
October 0.101170E+12 744.00 49248.27 01-OCT-00:10 453545.61 31-OCT-24:00 27.71 21.05 14.33
November 0.898704E+11 720.00 49248.27 01-NOV-10:35 513217.11 02-NOV-14:10 29.08 19.84 14.34
December 0.814443E+11 744.00 49248.27 04-DEC-15:20 657176.30 12-DEC-15:10 30.61 18.86 14.34
                   
Annual Sum or Average 0.120066E+13 8760.00         31.53 23.40 14.34
Minimum of Months 0.189564E+11 672.00 49248.27   317887.48   21.69 18.38 14.28
Maximum of Months 0.131907E+12 744.00 49248.27   711405.54   45.79 32.65 14.35



Table of Contents

Report: TowerReportMonthly

For: TOWERWATERSYS COOLTOWER 1

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

COOLING TOWER FAN ELECTRICITY ENERGY [J] COOLING TOWER FAN ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] COOLING TOWER FAN ELECTRICITY RATE {Maximum} [W] COOLING TOWER FAN ELECTRICITY RATE {TIMESTAMP} COOLING TOWER HEAT TRANSFER RATE {Maximum} [W] COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} COOLING TOWER INLET TEMPERATURE [C] COOLING TOWER OUTLET TEMPERATURE [C] COOLING TOWER MASS FLOW RATE [kg/s]
January 0.103156E+09 37.48 2170.97 19-JAN-22:00 581447.72 19-JAN-16:00 21.02 20.95 5.23
February 0.158959E+09 104.16 2238.19 28-FEB-15:00 1062309.43 28-FEB-15:10 21.32 21.10 14.50
March 0.239949E+10 213.49 21789.67 28-MAR-13:10 1564600.99 30-MAR-16:00 21.76 21.21 26.98
April 0.622457E+10 339.10 21789.67 04-APR-08:20 1637424.26 19-APR-16:00 22.29 21.27 39.65
May 0.206875E+11 449.61 21789.67 01-MAY-12:00 1554694.68 15-MAY-15:50 23.85 22.16 44.45
June 0.320137E+11 509.99 21789.67 01-JUN-04:12 1602297.20 02-JUN-11:00 25.22 23.17 48.99
July 0.436177E+11 603.41 21789.67 01-JUL-04:11 1430292.38 25-JUL-08:00 26.15 23.93 53.41
August 0.505073E+11 667.78 21789.67 01-AUG-00:03 1498978.09 25-AUG-09:10 26.76 24.42 59.19
September 0.262907E+11 451.30 21789.67 01-SEP-04:14 1615286.88 13-SEP-04:12 25.12 23.30 44.27
October 0.796599E+10 277.81 21789.67 01-OCT-12:22 1416349.76 10-OCT-09:50 22.65 21.79 30.04
November 0.138938E+10 165.07 21789.67 02-NOV-12:30 1099734.86 02-NOV-13:20 21.59 21.19 21.78
December 0.277068E+09 52.60 5278.74 13-DEC-11:10 949970.27 12-DEC-14:00 21.14 21.00 8.74
                   
Annual Sum or Average 0.191636E+12 3871.81         23.25 22.13 33.19
Minimum of Months 0.103156E+09 37.48 2170.97   581447.72   21.02 20.95 5.23
Maximum of Months 0.505073E+11 667.78 21789.67   1637424.26   26.76 24.42 59.19



Table of Contents

Report: TowerReportMonthly

For: TOWERWATERSYS COOLTOWER 2

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

COOLING TOWER FAN ELECTRICITY ENERGY [J] COOLING TOWER FAN ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] COOLING TOWER FAN ELECTRICITY RATE {Maximum} [W] COOLING TOWER FAN ELECTRICITY RATE {TIMESTAMP} COOLING TOWER HEAT TRANSFER RATE {Maximum} [W] COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} COOLING TOWER INLET TEMPERATURE [C] COOLING TOWER OUTLET TEMPERATURE [C] COOLING TOWER MASS FLOW RATE [kg/s]
January 0.00 0.00 0.00 01-JAN-00:05 0.00 01-JAN-00:05 21.02 21.02 0.00
February 0.00 0.00 0.00 01-FEB-00:10 0.00 01-FEB-00:10 21.32 21.32 0.00
March 78442809.36 1.00 21789.67 29-MAR-16:00 1209209.25 30-MAR-15:20 21.76 21.76 0.07
April 0.445583E+09 5.83 21789.67 04-APR-10:40 1313326.83 18-APR-12:40 22.29 22.25 0.41
May 0.475102E+10 60.57 21789.67 02-MAY-12:20 1104530.38 18-MAY-15:20 23.85 23.51 4.62
June 0.171526E+11 218.66 21789.67 01-JUN-07:50 1169423.25 02-JUN-15:50 25.22 24.11 18.12
July 0.234699E+11 299.20 21789.67 01-JUL-04:11 1170728.84 01-JUL-04:13 26.15 24.64 23.00
August 0.281283E+11 358.58 21789.67 01-AUG-06:20 1153288.63 24-AUG-10:50 26.76 25.01 28.32
September 0.102932E+11 131.22 21789.67 01-SEP-09:20 1192206.19 12-SEP-04:13 25.12 24.43 10.48
October 0.316386E+10 40.33 21789.67 02-OCT-09:00 1033705.77 19-OCT-15:10 22.65 22.43 2.97
November 0.00 0.00 0.00 01-NOV-00:10 0.00 01-NOV-00:10 21.59 21.59 0.00
December 0.00 0.00 0.00 01-DEC-00:10 0.00 01-DEC-00:10 21.14 21.14 0.00
                   
Annual Sum or Average 0.874829E+11 1115.40         23.25 22.77 7.40
Minimum of Months 0.00 0.00 0.00   0.00   21.02 21.02 0.00
Maximum of Months 0.281283E+11 358.58 21789.67   1313326.83   26.76 25.01 28.32



Table of Contents

Report: BoilerReportMonthly

For: HEATSYS1 BOILER

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

BOILER HEATING ENERGY [J] BOILER GAS CONSUMPTION [] BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] BOILER HEATING RATE {Maximum} [W] BOILER HEATING RATE {TIMESTAMP} BOILER GAS CONSUMPTION RATE [] BOILER INLET TEMPERATURE [C] BOILER OUTLET TEMPERATURE [C] BOILER MASS FLOW RATE [kg/s] BOILER ANCILLARY ELECTRICITY RATE [W] BOILER PART LOAD RATIO [] BOILER PART LOAD RATIO {Maximum} [] BOILER PART LOAD RATIO {TIMESTAMP}
January 0.288624E+12 0.00 506.85 1701386.63 02-JAN-06:01 0.00 28.87 64.06 0.59 0.00 0.04 0.69 02-JAN-06:01
February 0.164584E+12 0.00 360.28 1636699.86 06-FEB-06:02 0.00 25.49 54.12 0.36 0.00 0.03 0.66 06-FEB-06:02
March 0.294795E+11 0.00 185.00 1531292.97 22-MAR-04:11 0.00 21.34 36.05 0.05 0.00 0.00 0.62 22-MAR-04:11
April 0.743743E+10 0.00 86.01 1066652.84 06-APR-05:03 0.00 33.33 39.66 0.01 0.00 0.00 0.43 06-APR-05:03
May 0.653512E+09 0.00 16.81 51824.29 10-MAY-06:10 0.00 29.12 30.35 0.00 0.00 0.00 0.02 10-MAY-06:10
June 73318137.87 0.00 4.92 24086.49 10-JUN-13:10 0.00 40.18 40.49 0.00 0.00 0.00 0.01 10-JUN-13:10
July 0.00 0.00 0.00 0.00 01-JUL-00:10 0.00 41.86 41.86 0.00 0.00 0.00 0.00 01-JUL-00:10
August 0.00 0.00 0.00 0.00 01-AUG-00:03 0.00 41.86 41.86 0.00 0.00 0.00 0.00 01-AUG-00:03
September 0.131175E+09 0.00 19.49 28418.50 14-SEP-15:50 0.00 41.78 42.96 0.00 0.00 0.00 0.01 14-SEP-15:50
October 0.156607E+11 0.00 146.01 1092865.74 31-OCT-05:03 0.00 21.85 33.72 0.02 0.00 0.00 0.44 31-OCT-05:03
November 0.489511E+11 0.00 264.50 1439935.14 25-NOV-05:01 0.00 21.28 42.88 0.09 0.00 0.01 0.58 25-NOV-05:01
December 0.137879E+12 0.00 415.70 1556218.68 26-DEC-06:02 0.00 24.42 55.60 0.26 0.00 0.02 0.63 26-DEC-06:02
                           
Annual Sum or Average 0.693473E+12 0.00 2005.56     0.00 30.96 43.57 0.11 0.00 0.01    
Minimum of Months 0.00 0.00 0.00 0.00   0.00 21.28 30.35 0.00 0.00 0.00 0.00  
Maximum of Months 0.288624E+12 0.00 506.85 1701386.63   0.00 41.86 64.06 0.59 0.00 0.04 0.69  



Table of Contents

Report: BoilerReportMonthly

For: CENTRAL BOILER

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

BOILER HEATING ENERGY [J] BOILER GAS CONSUMPTION [] BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] BOILER HEATING RATE {Maximum} [W] BOILER HEATING RATE {TIMESTAMP} BOILER GAS CONSUMPTION RATE [] BOILER INLET TEMPERATURE [C] BOILER OUTLET TEMPERATURE [C] BOILER MASS FLOW RATE [kg/s] BOILER ANCILLARY ELECTRICITY RATE [W] BOILER PART LOAD RATIO [] BOILER PART LOAD RATIO []
January 0.00 0.00 0.00 0.00 01-JAN-00:05 0.00 21.69 21.69 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 01-FEB-00:10 0.00 25.12 25.12 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 01-MAR-00:10 0.00 29.81 29.81 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 01-APR-00:10 0.00 35.97 35.97 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 01-MAY-00:03 0.00 27.06 27.06 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 01-JUN-00:10 0.00 35.33 35.33 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 01-JUL-00:10 0.00 41.02 41.02 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 01-AUG-00:03 0.00 45.79 45.79 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 01-SEP-00:03 0.00 28.68 28.68 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 01-OCT-00:10 0.00 27.71 27.71 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 01-NOV-00:10 0.00 29.08 29.08 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 01-DEC-00:10 0.00 30.61 30.61 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.00 0.00 0.00     0.00 31.53 31.53 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00   0.00 21.69 21.69 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00   0.00 45.79 45.79 0.00 0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: VAV_BOT WITH REHEAT COOLING COIL

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.418628E+10 0.00 90.83 0.325438E+10 0.00 0.00 0.00 0.00 49577.65 19-JAN-16:00 43463.20 31-JAN-15:00 0.00 0.00 0.00
February 0.129807E+11 0.00 162.03 0.119387E+11 0.00 0.00 0.00 0.00 87790.55 28-FEB-15:00 87790.55 28-FEB-15:00 0.00 0.00 0.00
March 0.371894E+11 0.00 304.57 0.329776E+11 0.00 0.00 0.00 0.00 128454.66 30-MAR-15:20 128454.66 30-MAR-15:20 0.00 0.00 0.00
April 0.709594E+11 0.00 407.40 0.637861E+11 0.00 0.00 0.00 0.00 167098.76 17-APR-15:30 167098.76 17-APR-15:30 0.00 0.00 0.00
May 0.108026E+12 0.00 448.86 0.845171E+11 0.00 0.00 0.00 0.00 193635.85 31-MAY-05:03 164835.26 30-MAY-04:12 0.00 0.00 0.00
June 0.153777E+12 0.00 505.37 0.122204E+12 0.00 0.00 0.00 0.00 213687.23 16-JUN-04:11 164037.60 20-JUN-04:11 0.00 0.00 0.00
July 0.182750E+12 0.00 574.70 0.139273E+12 0.00 0.00 0.00 0.00 214129.59 01-JUL-04:11 163114.09 01-JUL-04:11 0.00 0.00 0.00
August 0.212940E+12 0.00 643.47 0.162510E+12 0.00 0.00 0.00 0.00 185156.23 12-AUG-05:02 162289.96 07-AUG-05:02 0.00 0.00 0.00
September 0.123099E+12 0.00 441.99 0.926115E+11 0.00 0.00 0.00 0.00 208129.89 27-SEP-04:11 167778.20 05-SEP-04:12 0.00 0.00 0.00
October 0.608539E+11 0.00 324.28 0.477557E+11 0.00 0.00 0.00 0.00 235688.64 19-OCT-04:12 154541.19 19-OCT-04:12 0.00 0.00 0.00
November 0.271954E+11 0.00 241.37 0.232311E+11 0.00 0.00 0.00 0.00 114994.50 27-NOV-05:12 114994.50 27-NOV-05:12 0.00 0.00 0.00
December 0.103734E+11 0.00 127.36 0.790705E+10 0.00 0.00 0.00 0.00 98865.46 12-DEC-14:00 75959.05 12-DEC-14:10 0.00 0.00 0.00
                               
Annual Sum or Average 0.100433E+13 0.00 4272.25 0.791967E+12 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 0.418628E+10 0.00 90.83 0.325438E+10 0.00 0.00 0.00 0.00 49577.65   43463.20   0.00 0.00 0.00
Maximum of Months 0.212940E+12 0.00 643.47 0.162510E+12 0.00 0.00 0.00 0.00 235688.64   167778.20   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: VAV_MID WITH REHEAT COOLING COIL

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.349320E+11 0.00 71.03 0.269659E+11 0.00 0.00 0.00 0.00 391845.64 19-JAN-22:00 308832.93 31-JAN-15:00 0.00 0.00 0.00
February 0.101155E+12 0.00 150.98 0.918812E+11 0.00 0.00 0.00 0.00 653877.50 28-FEB-15:00 653877.50 28-FEB-15:00 0.00 0.00 0.00
March 0.282113E+12 0.00 289.02 0.250755E+12 0.00 0.00 0.00 0.00 1096174.49 30-MAR-15:20 1096174.49 30-MAR-15:20 0.00 0.00 0.00
April 0.509438E+12 0.00 350.55 0.456356E+12 0.00 0.00 0.00 0.00 1289759.78 17-APR-14:30 1289759.78 17-APR-14:30 0.00 0.00 0.00
May 0.944928E+12 0.00 436.82 0.725085E+12 0.00 0.00 0.00 0.00 1775638.32 31-MAY-05:03 1315432.83 30-MAY-05:03 0.00 0.00 0.00
June 0.131898E+13 0.00 456.93 0.100441E+13 0.00 0.00 0.00 0.00 2047154.54 30-JUN-05:02 1510650.96 29-JUN-05:02 0.00 0.00 0.00
July 0.149738E+13 0.00 467.97 0.106167E+13 0.00 0.00 0.00 0.00 2010011.17 14-JUL-04:12 1515440.38 14-JUL-04:12 0.00 0.00 0.00
August 0.167177E+13 0.00 491.72 0.116374E+13 0.00 0.00 0.00 0.00 2301627.01 23-AUG-05:02 1519502.39 17-AUG-04:12 0.00 0.00 0.00
September 0.107676E+13 0.00 425.58 0.781454E+12 0.00 0.00 0.00 0.00 2038906.50 27-SEP-04:11 1497019.37 11-SEP-05:02 0.00 0.00 0.00
October 0.481617E+12 0.00 309.41 0.363932E+12 0.00 0.00 0.00 0.00 1941680.82 19-OCT-04:12 1107534.64 19-OCT-05:03 0.00 0.00 0.00
November 0.196320E+12 0.00 228.14 0.164516E+12 0.00 0.00 0.00 0.00 672240.39 04-NOV-05:03 527683.98 08-NOV-15:00 0.00 0.00 0.00
December 0.683327E+11 0.00 121.28 0.516345E+11 0.00 0.00 0.00 0.00 563451.24 12-DEC-14:00 453758.56 12-DEC-14:10 0.00 0.00 0.00
                               
Annual Sum or Average 0.818373E+13 0.00 3799.43 0.614239E+13 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 0.349320E+11 0.00 71.03 0.269659E+11 0.00 0.00 0.00 0.00 391845.64   308832.93   0.00 0.00 0.00
Maximum of Months 0.167177E+13 0.00 491.72 0.116374E+13 0.00 0.00 0.00 0.00 2301627.01   1519502.39   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: VAV_TOP WITH REHEAT COOLING COIL

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.349096E+10 0.00 93.75 0.267261E+10 0.00 0.00 0.00 0.00 40197.45 19-JAN-22:00 31293.88 31-JAN-15:00 0.00 0.00 0.00
February 0.973973E+10 0.00 154.09 0.879443E+10 0.00 0.00 0.00 0.00 61977.71 28-FEB-15:30 61977.71 28-FEB-15:30 0.00 0.00 0.00
March 0.277521E+11 0.00 284.39 0.245935E+11 0.00 0.00 0.00 0.00 119355.63 30-MAR-14:20 119228.09 30-MAR-15:10 0.00 0.00 0.00
April 0.522745E+11 0.00 344.33 0.469645E+11 0.00 0.00 0.00 0.00 128673.21 17-APR-15:50 128673.21 17-APR-15:50 0.00 0.00 0.00
May 0.101586E+12 0.00 430.72 0.789405E+11 0.00 0.00 0.00 0.00 158202.96 31-MAY-05:03 142063.45 16-MAY-16:00 0.00 0.00 0.00
June 0.144690E+12 0.00 456.54 0.112237E+12 0.00 0.00 0.00 0.00 224993.49 26-JUN-04:12 163604.83 26-JUN-04:12 0.00 0.00 0.00
July 0.163866E+12 0.00 470.87 0.119373E+12 0.00 0.00 0.00 0.00 220443.80 31-JUL-04:11 161631.89 14-JUL-04:12 0.00 0.00 0.00
August 0.181702E+12 0.00 495.19 0.129900E+12 0.00 0.00 0.00 0.00 256142.79 23-AUG-05:02 163986.73 23-AUG-05:02 0.00 0.00 0.00
September 0.110976E+12 0.00 420.08 0.812888E+11 0.00 0.00 0.00 0.00 206225.00 05-SEP-05:02 149821.54 07-SEP-05:02 0.00 0.00 0.00
October 0.483804E+11 0.00 304.87 0.359076E+11 0.00 0.00 0.00 0.00 202558.16 19-OCT-04:12 106497.60 18-OCT-05:02 0.00 0.00 0.00
November 0.183911E+11 0.00 225.68 0.152563E+11 0.00 0.00 0.00 0.00 63177.20 03-NOV-15:00 50665.94 02-NOV-14:30 0.00 0.00 0.00
December 0.670704E+10 0.00 127.93 0.503672E+10 0.00 0.00 0.00 0.00 56784.57 12-DEC-14:00 44815.95 12-DEC-14:00 0.00 0.00 0.00
                               
Annual Sum or Average 0.869555E+12 0.00 3808.47 0.660964E+12 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 0.349096E+10 0.00 93.75 0.267261E+10 0.00 0.00 0.00 0.00 40197.45   31293.88   0.00 0.00 0.00
Maximum of Months 0.181702E+12 0.00 495.19 0.129900E+12 0.00 0.00 0.00 0.00 256142.79   163986.73   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: CAV_BAS COOLING COIL

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.577388E+09 0.00 14.48 0.561106E+09 0.00 0.00 0.00 0.00 60662.59 20-JAN-05:23 30826.23 31-JAN-15:00 0.00 0.00 0.00
February 0.423326E+10 0.00 45.75 0.421127E+10 0.00 0.00 0.00 0.00 76165.51 18-FEB-06:02 62551.44 28-FEB-15:00 0.00 0.00 0.00
March 0.135794E+11 0.00 139.75 0.135220E+11 0.00 0.00 0.00 0.00 102769.19 30-MAR-05:03 81836.23 30-MAR-14:00 0.00 0.00 0.00
April 0.290157E+11 0.00 221.89 0.285580E+11 0.00 0.00 0.00 0.00 104988.40 03-APR-04:12 104988.40 03-APR-04:12 0.00 0.00 0.00
May 0.516525E+11 0.00 341.25 0.475012E+11 0.00 0.00 0.00 0.00 135025.59 31-MAY-04:12 93055.93 16-MAY-16:00 0.00 0.00 0.00
June 0.893055E+11 0.00 393.62 0.760581E+11 0.00 0.00 0.00 0.00 157713.48 23-JUN-04:12 118206.68 12-JUN-04:12 0.00 0.00 0.00
July 0.100403E+12 0.00 397.56 0.807227E+11 0.00 0.00 0.00 0.00 162673.87 08-JUL-03:02 98117.14 05-JUL-04:12 0.00 0.00 0.00
August 0.120344E+12 0.00 452.56 0.945161E+11 0.00 0.00 0.00 0.00 184663.80 06-AUG-17:31 102066.49 27-AUG-17:59 0.00 0.00 0.00
September 0.758328E+11 0.00 371.00 0.647648E+11 0.00 0.00 0.00 0.00 179768.22 10-SEP-15:52 106016.04 04-SEP-23:22 0.00 0.00 0.00
October 0.329230E+11 0.00 211.87 0.278620E+11 0.00 0.00 0.00 0.00 152244.76 19-OCT-04:53 109307.32 09-OCT-17:30 0.00 0.00 0.00
November 0.105310E+11 0.00 116.31 0.993063E+10 0.00 0.00 0.00 0.00 99535.69 27-NOV-06:03 75440.32 20-NOV-01:13 0.00 0.00 0.00
December 0.307062E+10 0.00 35.75 0.283080E+10 0.00 0.00 0.00 0.00 96908.29 13-DEC-06:03 51718.02 12-DEC-15:00 0.00 0.00 0.00
                               
Annual Sum or Average 0.531468E+12 0.00 2741.79 0.451039E+12 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 0.577388E+09 0.00 14.48 0.561106E+09 0.00 0.00 0.00 0.00 60662.59   30826.23   0.00 0.00 0.00
Maximum of Months 0.120344E+12 0.00 452.56 0.945161E+11 0.00 0.00 0.00 0.00 184663.80   118206.68   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: AIRLOOP DATACENTER BASEMENT COOLING COIL

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [J] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [J] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION {Maximum} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL RUNTIME FRACTION {MINIMUM} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE {Maximum} [W] COOLING COIL LATENT COOLING RATE {TIMESTAMP} COOLING COIL ELECTRICITY RATE {Maximum} [W] COOLING COIL ELECTRICITY RATE {TIMESTAMP} COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.322755E+12 0.814821E+11 744.00 0.322249E+12 0.505033E+09 0.00 0.34 04-JAN-16:30 0.30 09-JAN-07:10 130240.38 19-JAN-17:00 125486.54 31-JAN-15:00 6032.09 19-JAN-17:10 37254.66 04-JAN-16:30 0.00
February 0.513810E+12 0.125147E+12 672.00 0.513255E+12 0.554421E+09 0.00 0.59 28-FEB-14:10 0.51 13-FEB-07:10 220370.20 17-FEB-17:00 218908.00 28-FEB-15:00 5785.07 17-FEB-17:10 71132.19 28-FEB-14:20 0.00
March 0.819754E+12 0.201093E+12 744.00 0.818178E+12 0.157580E+10 0.00 0.92 31-MAR-24:00 0.72 06-MAR-07:20 394618.19 31-MAR-24:00 394618.19 31-MAR-24:00 8575.26 31-MAR-11:50 107135.99 30-MAR-16:00 0.00
April 0.103147E+13 0.268037E+12 720.00 0.102945E+13 0.201344E+10 0.00 1.00 02-APR-13:30 0.36 30-APR-24:00 407355.99 21-APR-15:00 403307.25 16-APR-18:35 7166.40 04-APR-10:00 137420.05 17-APR-16:00 0.00
May 0.341365E+12 0.983718E+11 744.00 0.335009E+12 0.635622E+10 0.00 0.55 31-MAY-23:20 0.31 12-MAY-07:00 213304.05 31-MAY-23:10 211865.19 31-MAY-24:00 8649.07 23-MAY-14:00 60476.91 31-MAY-23:20 0.00
June 0.573902E+12 0.181976E+12 720.00 0.564586E+12 0.931587E+10 0.00 0.77 30-JUN-24:00 0.53 10-JUN-06:30 304523.38 30-JUN-24:00 304005.18 30-JUN-24:00 13299.17 26-JUN-17:00 92992.99 06-JUN-15:00 0.00
July 0.840997E+12 0.274004E+12 744.00 0.829881E+12 0.111163E+11 0.00 0.99 31-JUL-23:55 0.75 29-JUL-04:00 396982.36 31-JUL-23:55 396164.08 31-JUL-24:00 14048.46 25-JUL-16:50 135166.75 08-JUL-15:40 0.00
August 0.108128E+13 0.350365E+12 744.00 0.107015E+13 0.111347E+11 0.00 1.00 01-AUG-07:05 0.38 31-AUG-24:00 423093.78 08-AUG-17:00 407845.40 07-AUG-21:04 19230.15 11-AUG-17:00 154125.23 01-AUG-16:10 0.00
September 0.338494E+12 0.101446E+12 720.00 0.330100E+12 0.839407E+10 0.00 0.53 30-SEP-24:00 0.32 29-SEP-06:10 212230.89 30-SEP-23:20 211970.75 30-SEP-24:00 10513.00 28-SEP-13:20 53918.61 07-SEP-16:00 0.00
October 0.584559E+12 0.151203E+12 744.00 0.580848E+12 0.371132E+10 0.00 0.74 31-OCT-24:00 0.53 31-OCT-07:00 304685.21 31-OCT-24:00 304685.21 31-OCT-24:00 11887.83 18-OCT-16:10 82951.75 10-OCT-16:00 0.00
November 0.798455E+12 0.191654E+12 720.00 0.796979E+12 0.147654E+10 0.00 0.81 19-NOV-15:00 0.72 13-NOV-07:20 318078.77 27-NOV-17:00 311700.38 02-NOV-14:00 6787.60 27-NOV-17:10 98134.01 19-NOV-15:00 0.00
December 0.106524E+13 0.239368E+12 744.00 0.106449E+13 0.756865E+09 0.00 0.99 12-DEC-14:40 0.90 01-DEC-07:10 408994.61 13-DEC-14:00 403104.88 12-DEC-15:00 7820.79 13-DEC-14:00 120514.49 12-DEC-14:40 0.00
                                       
Annual Sum or Average 0.831209E+13 0.226415E+13 8760.00 0.825518E+13 0.569106E+11 0.00                         0.00
Minimum of Months 0.322755E+12 0.814821E+11 672.00 0.322249E+12 0.505033E+09 0.00 0.34   0.30   130240.38   125486.54   5785.07   37254.66   0.00
Maximum of Months 0.108128E+13 0.350365E+12 744.00 0.107015E+13 0.111347E+11 0.00 1.00   0.90   423093.78   407845.40   19230.15   154125.23   0.00



Table of Contents

Report: DXReportMonthly

For: AIRLOOP DATACENTER BOT COOLING COIL

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [J] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [J] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION {Maximum} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL RUNTIME FRACTION {MINIMUM} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE {Maximum} [W] COOLING COIL LATENT COOLING RATE {TIMESTAMP} COOLING COIL ELECTRICITY RATE {Maximum} [W] COOLING COIL ELECTRICITY RATE {TIMESTAMP} COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.366635E+10 0.985252E+09 744.00 0.364720E+10 19148367.55 0.00 0.30 15-JAN-17:35 0.04 09-JAN-07:10 2321.85 20-JAN-17:00 2219.08 20-JAN-17:00 225.42 19-JAN-17:00 629.39 31-JAN-15:00 0.00
February 0.857835E+10 0.215044E+10 672.00 0.855628E+10 22068999.61 0.00 0.58 26-FEB-17:42 0.31 13-FEB-07:10 4531.52 20-FEB-17:57 4498.52 20-FEB-17:57 230.38 17-FEB-17:00 1414.79 26-FEB-17:23 0.00
March 0.156283E+11 0.384228E+10 744.00 0.155620E+11 66238327.54 0.00 0.84 31-MAR-24:00 0.58 22-MAR-07:00 7701.85 31-MAR-24:00 7701.85 31-MAR-24:00 305.77 31-MAR-11:40 2158.97 30-MAR-16:00 0.00
April 0.203356E+11 0.523457E+10 720.00 0.202451E+11 90448678.44 0.00 0.99 08-APR-18:12 0.30 30-APR-24:00 8484.65 09-APR-18:15 8484.65 09-APR-18:15 332.42 04-APR-10:00 2867.52 17-APR-16:00 0.00
May 0.616096E+10 0.175085E+10 744.00 0.592471E+10 0.236250E+09 0.00 0.49 31-MAY-24:00 0.20 11-MAY-06:05 4091.83 31-MAY-24:00 4037.42 31-MAY-24:00 341.10 31-MAY-11:00 1135.56 31-MAY-23:20 0.00
June 0.112697E+11 0.350234E+10 720.00 0.108928E+11 0.376884E+09 0.00 0.69 30-JUN-24:00 0.43 10-JUN-06:50 5969.29 30-JUN-24:00 5946.40 30-JUN-24:00 491.42 26-JUN-16:20 1905.51 06-JUN-15:20 0.00
July 0.167870E+11 0.535536E+10 744.00 0.163096E+11 0.477389E+09 0.00 0.90 31-JUL-23:55 0.66 29-JUL-06:10 7801.45 31-JUL-23:55 7779.54 31-JUL-24:00 549.02 26-JUL-09:00 2784.62 07-JUL-16:00 0.00
August 0.219404E+11 0.706128E+10 744.00 0.213917E+11 0.548697E+09 0.00 1.00 01-AUG-10:20 0.31 31-AUG-24:00 8974.29 04-AUG-15:00 8471.10 13-AUG-19:23 649.99 11-AUG-17:00 3267.69 01-AUG-16:10 0.00
September 0.617805E+10 0.182046E+10 720.00 0.586012E+10 0.317934E+09 0.00 0.44 30-SEP-24:00 0.21 29-SEP-06:50 3751.76 30-SEP-24:00 3736.09 30-SEP-24:00 420.30 05-SEP-11:00 1132.32 07-SEP-16:00 0.00
October 0.108174E+11 0.276521E+10 744.00 0.106659E+11 0.151453E+09 0.00 0.65 31-OCT-24:00 0.38 26-OCT-07:00 5655.26 31-OCT-24:00 5655.26 31-OCT-24:00 505.78 18-OCT-16:00 1690.45 10-OCT-16:00 0.00
November 0.150064E+11 0.362968E+10 720.00 0.149489E+11 57489217.58 0.00 0.78 19-NOV-17:03 0.58 30-NOV-22:00 6435.60 11-NOV-17:08 6435.60 11-NOV-17:08 281.96 27-NOV-17:00 1981.18 19-NOV-15:03 0.00
December 0.201076E+11 0.459738E+10 744.00 0.200752E+11 32330737.13 0.00 0.97 10-DEC-16:53 0.74 01-DEC-07:10 8306.44 11-DEC-16:50 8118.35 19-DEC-17:00 330.90 13-DEC-16:00 2378.37 12-DEC-14:50 0.00
                                       
Annual Sum or Average 0.156476E+12 0.426951E+11 8760.00 0.154080E+12 0.239633E+10 0.00                         0.00
Minimum of Months 0.366635E+10 0.985252E+09 672.00 0.364720E+10 19148367.55 0.00 0.30   0.04   2321.85   2219.08   225.42   629.39   0.00
Maximum of Months 0.219404E+11 0.706128E+10 744.00 0.213917E+11 0.548697E+09 0.00 1.00   0.74   8974.29   8484.65   649.99   3267.69   0.00



Table of Contents

Report: DXReportMonthly

For: AIRLOOP DATACENTER MID COOLING COIL

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [J] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [J] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION {Maximum} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL RUNTIME FRACTION {MINIMUM} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE {Maximum} [W] COOLING COIL LATENT COOLING RATE {TIMESTAMP} COOLING COIL ELECTRICITY RATE {Maximum} [W] COOLING COIL ELECTRICITY RATE {TIMESTAMP} COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.116269E+11 0.336553E+10 563.99 0.114626E+11 0.164294E+09 0.00 0.24 20-JAN-17:00 0.00 01-JAN-00:05 18736.72 20-JAN-17:00 17679.15 20-JAN-17:00 2055.33 19-JAN-17:00 4750.18 31-JAN-15:20 0.00
February 0.627246E+11 0.161028E+11 672.00 0.625139E+11 0.210704E+09 0.00 0.54 27-FEB-17:50 0.12 13-FEB-04:12 41041.90 28-FEB-17:00 41041.90 28-FEB-17:00 2225.17 17-FEB-17:00 12731.63 28-FEB-15:00 0.00
March 0.138227E+12 0.343559E+11 744.00 0.137568E+12 0.658850E+09 0.00 0.82 31-MAR-23:50 0.50 22-MAR-06:20 71530.82 31-MAR-23:50 71530.82 31-MAR-23:50 3026.25 31-MAR-11:40 20467.78 30-MAR-16:00 0.00
April 0.188317E+12 0.487538E+11 720.00 0.187412E+12 0.904094E+09 0.00 0.98 17-APR-16:00 0.25 30-APR-24:00 79656.72 04-APR-15:40 79257.41 14-APR-18:20 3326.03 04-APR-10:00 27167.03 17-APR-16:00 0.00
May 0.546039E+11 0.156625E+11 744.00 0.523000E+11 0.230390E+10 0.00 0.48 31-MAY-23:40 0.16 10-MAY-07:00 38386.76 31-MAY-23:20 37775.33 31-MAY-24:00 3399.31 31-MAY-11:00 10669.08 31-MAY-23:20 0.00
June 0.105820E+12 0.329702E+11 720.00 0.102079E+12 0.374103E+10 0.00 0.69 30-JUN-24:00 0.39 10-JUN-07:00 56649.66 30-JUN-24:00 56416.49 30-JUN-24:00 4880.15 26-JUN-16:20 18103.88 06-JUN-15:20 0.00
July 0.159537E+12 0.509340E+11 744.00 0.154780E+12 0.475674E+10 0.00 0.91 31-JUL-23:55 0.63 29-JUL-06:10 75227.84 31-JUL-23:55 75012.98 31-JUL-24:00 5484.95 26-JUL-09:00 26589.57 07-JUL-16:00 0.00
August 0.208831E+12 0.672347E+11 744.00 0.203345E+12 0.548595E+10 0.00 1.00 01-AUG-10:10 0.27 31-AUG-24:00 85091.30 04-AUG-14:50 79587.88 13-AUG-18:38 6392.04 11-AUG-16:50 31208.91 01-AUG-16:10 0.00
September 0.544046E+11 0.161844E+11 720.00 0.513058E+11 0.309882E+10 0.00 0.39 07-SEP-16:00 0.15 30-SEP-17:00 31326.62 30-SEP-24:00 31060.97 30-SEP-24:00 4162.15 05-SEP-11:00 10731.03 07-SEP-16:00 0.00
October 0.927509E+11 0.240325E+11 744.00 0.912602E+11 0.149072E+10 0.00 0.59 31-OCT-23:50 0.31 31-OCT-07:00 48263.33 31-OCT-23:50 48263.33 31-OCT-23:50 5033.26 18-OCT-16:00 15836.12 10-OCT-16:00 0.00
November 0.128045E+12 0.314149E+11 720.00 0.127480E+12 0.565438E+09 0.00 0.76 08-NOV-17:00 0.49 22-NOV-07:10 59728.96 08-NOV-17:00 59728.96 08-NOV-17:00 2789.32 27-NOV-17:00 17636.45 19-NOV-16:55 0.00
December 0.168017E+12 0.391340E+11 744.00 0.167694E+12 0.323265E+09 0.00 0.90 12-DEC-15:20 0.62 18-DEC-07:10 76467.37 11-DEC-17:00 74576.81 11-DEC-17:00 3289.40 13-DEC-16:00 22059.62 12-DEC-15:00 0.00
                                       
Annual Sum or Average 0.137290E+13 0.380145E+12 8579.99 0.134920E+13 0.237038E+11 0.00                         0.00
Minimum of Months 0.116269E+11 0.336553E+10 563.99 0.114626E+11 0.164294E+09 0.00 0.24   0.00   18736.72   17679.15   2055.33   4750.18   0.00
Maximum of Months 0.208831E+12 0.672347E+11 744.00 0.203345E+12 0.548595E+10 0.00 1.00   0.63   85091.30   79587.88   6392.04   31208.91   0.00



Table of Contents

Report: DXReportMonthly

For: AIRLOOP DATACENTER TOP COOLING COIL

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [J] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [J] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION {Maximum} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL RUNTIME FRACTION {MINIMUM} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE {Maximum} [W] COOLING COIL LATENT COOLING RATE {TIMESTAMP} COOLING COIL ELECTRICITY RATE {Maximum} [W] COOLING COIL ELECTRICITY RATE {TIMESTAMP} COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.621563E+09 0.178295E+09 302.22 0.605803E+09 15759481.41 0.00 0.24 20-JAN-17:00 0.00 01-JAN-00:05 1961.58 20-JAN-17:00 1852.68 20-JAN-17:00 213.15 19-JAN-16:40 480.74 20-JAN-17:00 0.00
February 0.522525E+10 0.135738E+10 653.72 0.520456E+10 20686968.79 0.00 0.53 27-FEB-17:50 0.00 05-FEB-03:25 4144.17 28-FEB-17:00 4144.17 28-FEB-17:00 221.08 17-FEB-17:00 1281.52 28-FEB-17:00 0.00
March 0.130275E+11 0.327179E+10 744.00 0.129621E+11 65372169.56 0.00 0.78 31-MAR-23:20 0.42 23-MAR-06:10 6897.78 31-MAR-23:20 6897.78 31-MAR-23:20 303.01 31-MAR-11:40 2083.08 30-MAR-16:00 0.00
April 0.184072E+11 0.480100E+10 720.00 0.183172E+11 90021175.84 0.00 0.97 17-APR-16:00 0.23 30-APR-24:00 8065.77 17-APR-16:00 8030.10 17-APR-16:00 332.82 04-APR-10:00 2759.40 17-APR-16:00 0.00
May 0.536898E+10 0.155142E+10 744.00 0.513908E+10 0.229905E+09 0.00 0.47 31-MAY-23:30 0.10 11-MAY-06:25 3812.03 31-MAY-23:10 3743.01 31-MAY-24:00 345.27 31-MAY-11:00 1061.85 31-MAY-23:20 0.00
June 0.106418E+11 0.332565E+10 720.00 0.102675E+11 0.374313E+09 0.00 0.68 30-JUN-24:00 0.36 10-JUN-07:00 5636.86 30-JUN-24:00 5613.17 30-JUN-24:00 489.76 26-JUN-16:20 1856.85 06-JUN-15:20 0.00
July 0.160576E+11 0.513926E+10 744.00 0.155821E+11 0.475481E+09 0.00 0.90 31-JUL-23:55 0.59 29-JUL-07:00 7576.32 31-JUL-23:55 7554.70 31-JUL-24:00 548.89 26-JUL-09:00 2718.45 07-JUL-16:00 0.00
August 0.210087E+11 0.678092E+10 744.00 0.204599E+11 0.548762E+09 0.00 1.00 01-AUG-10:40 0.25 31-AUG-24:00 8629.02 04-AUG-14:50 8203.25 13-AUG-18:52 623.54 11-AUG-16:50 3177.33 01-AUG-16:10 0.00
September 0.526916E+10 0.158102E+10 720.00 0.496154E+10 0.307620E+09 0.00 0.40 07-SEP-16:00 0.10 30-SEP-17:00 3066.46 07-SEP-16:00 2681.05 07-SEP-16:00 419.89 06-SEP-14:30 1109.33 07-SEP-16:00 0.00
October 0.851575E+10 0.223668E+10 744.00 0.836752E+10 0.148224E+09 0.00 0.58 10-OCT-16:00 0.21 26-OCT-06:10 4639.91 18-OCT-16:00 4384.55 31-OCT-23:20 503.99 18-OCT-16:00 1611.05 10-OCT-16:00 0.00
November 0.115970E+11 0.288425E+10 720.00 0.115411E+11 55811409.99 0.00 0.74 08-NOV-17:00 0.38 22-NOV-07:10 5986.35 02-NOV-16:00 5944.76 06-NOV-17:00 278.19 27-NOV-17:00 1733.15 08-NOV-17:00 0.00
December 0.152248E+11 0.359626E+10 744.00 0.151927E+11 32068213.81 0.00 0.88 12-DEC-15:30 0.44 18-DEC-04:02 7609.60 13-DEC-16:00 7400.24 12-DEC-17:00 328.66 13-DEC-16:00 2202.28 12-DEC-15:00 0.00
                                       
Annual Sum or Average 0.130965E+12 0.367039E+11 8299.94 0.128601E+12 0.236402E+10 0.00                         0.00
Minimum of Months 0.621563E+09 0.178295E+09 302.22 0.605803E+09 15759481.41 0.00 0.24   0.00   1961.58   1852.68   213.15   480.74   0.00
Maximum of Months 0.210087E+11 0.678092E+10 744.00 0.204599E+11 0.548762E+09 0.00 1.00   0.59   8629.02   8203.25   623.54   3177.33   0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 98.96 0.00 98.96 8.30 820.85 0.00 0.00 0.00
February 109.69 0.00 109.69 34.51 674.70 0.00 0.00 0.00
March 154.00 0.00 154.00 84.86 426.91 0.00 0.00 0.00
April 186.27 0.83 185.45 187.83 326.19 0.00 0.00 0.00
May 222.78 7.11 215.67 304.95 201.21 0.00 0.00 0.00
June 245.18 16.19 228.99 447.16 123.45 0.00 0.00 0.00
July 231.33 11.24 220.08 450.25 85.55 0.00 0.00 0.00
August 205.73 2.24 203.49 410.90 68.47 0.00 0.00 0.00
September 155.51 0.02 155.49 227.73 176.34 0.00 0.00 0.00
October 118.24 0.00 118.24 90.83 389.14 0.00 0.00 0.00
November 105.82 0.00 105.82 35.95 543.75 0.00 0.00 0.00
December 91.48 0.00 91.48 6.34 708.23 0.00 0.00 0.00
                 
Annual Sum or Average 160.69 3.15 157.54 191.72 377.25 0.00 0.00 0.00
Minimum of Months 91.48 0.00 91.48 6.34 68.47 0.00 0.00 0.00
Maximum of Months 245.18 16.19 228.99 450.25 820.85 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 98.96 0.00 98.96 8.30 820.85 0.00 0.00 0.00
February 109.69 0.00 109.69 34.51 674.70 0.00 0.00 0.00
March 154.00 0.00 154.00 84.86 426.91 0.00 0.00 0.00
April 186.27 0.83 185.45 187.83 326.19 0.00 0.00 0.00
May 222.78 7.11 215.67 304.95 201.21 0.00 0.00 0.00
June 245.18 16.19 228.99 447.16 123.45 0.00 0.00 0.00
July 231.33 11.24 220.08 450.25 85.55 0.00 0.00 0.00
August 205.73 2.24 203.49 410.90 68.47 0.00 0.00 0.00
September 155.51 0.02 155.49 227.73 176.33 0.00 0.00 0.00
October 118.24 0.00 118.24 90.83 389.14 0.00 0.00 0.00
November 105.82 0.00 105.82 35.95 543.75 0.00 0.00 0.00
December 91.48 0.00 91.48 6.34 708.23 0.00 0.00 0.00
                 
Annual Sum or Average 160.69 3.15 157.54 191.72 377.25 0.00 0.00 0.00
Minimum of Months 91.48 0.00 91.48 6.34 68.47 0.00 0.00 0.00
Maximum of Months 245.18 16.19 228.99 450.25 820.85 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 98.96 0.00 98.96 8.30 820.85 0.00 0.00 0.00
February 109.69 0.00 109.69 34.51 674.70 0.00 0.00 0.00
March 154.00 0.00 154.00 84.86 426.91 0.00 0.00 0.00
April 186.27 0.83 185.45 187.83 326.19 0.00 0.00 0.00
May 222.78 7.11 215.67 304.95 201.21 0.00 0.00 0.00
June 245.18 16.19 228.99 447.16 123.45 0.00 0.00 0.00
July 231.33 11.24 220.08 450.25 85.55 0.00 0.00 0.00
August 205.73 2.24 203.49 410.90 68.47 0.00 0.00 0.00
September 155.51 0.02 155.49 227.73 176.34 0.00 0.00 0.00
October 118.24 0.00 118.24 90.83 389.14 0.00 0.00 0.00
November 105.82 0.00 105.82 35.95 543.75 0.00 0.00 0.00
December 91.48 0.00 91.48 6.34 708.23 0.00 0.00 0.00
                 
Annual Sum or Average 160.69 3.15 157.54 191.72 377.25 0.00 0.00 0.00
Minimum of Months 91.48 0.00 91.48 6.34 68.47 0.00 0.00 0.00
Maximum of Months 245.18 16.19 228.99 450.25 820.85 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 98.96 0.00 98.96 8.30 820.85 0.00 0.00 0.00
February 109.69 0.00 109.69 34.51 674.70 0.00 0.00 0.00
March 154.00 0.00 154.00 84.86 426.91 0.00 0.00 0.00
April 186.27 0.83 185.45 187.83 326.19 0.00 0.00 0.00
May 222.78 7.11 215.67 304.95 201.21 0.00 0.00 0.00
June 245.18 16.19 228.99 447.16 123.45 0.00 0.00 0.00
July 231.33 11.24 220.08 450.25 85.55 0.00 0.00 0.00
August 205.73 2.24 203.49 410.90 68.47 0.00 0.00 0.00
September 155.51 0.02 155.49 227.73 176.33 0.00 0.00 0.00
October 118.24 0.00 118.24 90.83 389.14 0.00 0.00 0.00
November 105.82 0.00 105.82 35.95 543.75 0.00 0.00 0.00
December 91.48 0.00 91.48 6.34 708.23 0.00 0.00 0.00
                 
Annual Sum or Average 160.69 3.15 157.54 191.72 377.25 0.00 0.00 0.00
Minimum of Months 91.48 0.00 91.48 6.34 68.47 0.00 0.00 0.00
Maximum of Months 245.18 16.19 228.99 450.25 820.85 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 98.96 0.00 98.96 8.30 820.82 0.00 0.00 0.00
February 109.68 0.00 109.68 34.51 674.68 0.00 0.00 0.00
March 153.99 0.00 153.99 84.86 426.89 0.00 0.00 0.00
April 186.27 0.83 185.44 187.83 326.17 0.00 0.00 0.00
May 222.77 7.11 215.66 304.94 201.20 0.00 0.00 0.00
June 245.17 16.19 228.98 447.14 123.45 0.00 0.00 0.00
July 231.32 11.24 220.07 450.23 85.55 0.00 0.00 0.00
August 205.72 2.24 203.48 410.89 68.47 0.00 0.00 0.00
September 155.50 0.02 155.48 227.72 176.33 0.00 0.00 0.00
October 118.24 0.00 118.24 90.83 389.13 0.00 0.00 0.00
November 105.82 0.00 105.82 35.95 543.73 0.00 0.00 0.00
December 91.48 0.00 91.48 6.34 708.20 0.00 0.00 0.00
                 
Annual Sum or Average 160.69 3.15 157.54 191.71 377.23 0.00 0.00 0.00
Minimum of Months 91.48 0.00 91.48 6.34 68.47 0.00 0.00 0.00
Maximum of Months 245.17 16.19 228.98 450.23 820.82 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 241.48 108.92 132.56 145.69 808.88 0.00 0.00 0.00
February 304.43 163.57 140.86 270.09 659.89 0.00 0.00 0.00
March 383.00 174.35 208.65 410.25 415.74 0.00 0.00 0.00
April 463.15 211.18 251.97 626.63 322.36 0.00 0.00 0.00
May 508.57 215.07 293.51 776.10 215.45 0.00 0.00 0.00
June 526.54 220.69 305.86 929.46 130.91 0.00 0.00 0.00
July 513.40 215.84 297.56 942.76 86.44 0.00 0.00 0.00
August 469.59 186.30 283.29 879.95 62.97 0.00 0.00 0.00
September 385.94 171.00 214.94 614.94 182.48 0.00 0.00 0.00
October 329.24 171.31 157.93 406.37 383.83 0.00 0.00 0.00
November 263.23 119.19 144.04 232.01 520.75 0.00 0.00 0.00
December 228.01 103.94 124.07 145.72 674.76 0.00 0.00 0.00
                 
Annual Sum or Average 385.10 171.75 213.35 533.06 370.58 0.00 0.00 0.00
Minimum of Months 228.01 103.94 124.07 145.69 62.97 0.00 0.00 0.00
Maximum of Months 526.54 220.69 305.86 942.76 808.88 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 241.48 108.92 132.56 145.69 808.88 0.00 0.00 0.00
February 304.43 163.57 140.86 270.09 659.89 0.00 0.00 0.00
March 383.00 174.35 208.65 410.25 415.74 0.00 0.00 0.00
April 463.15 211.18 251.97 626.63 322.36 0.00 0.00 0.00
May 508.57 215.07 293.51 776.10 215.45 0.00 0.00 0.00
June 526.54 220.69 305.86 929.46 130.91 0.00 0.00 0.00
July 513.40 215.84 297.56 942.76 86.44 0.00 0.00 0.00
August 469.59 186.30 283.29 879.95 62.97 0.00 0.00 0.00
September 385.94 171.00 214.94 614.94 182.48 0.00 0.00 0.00
October 329.24 171.31 157.93 406.37 383.83 0.00 0.00 0.00
November 263.23 119.19 144.04 232.01 520.75 0.00 0.00 0.00
December 228.01 103.94 124.07 145.72 674.76 0.00 0.00 0.00
                 
Annual Sum or Average 385.10 171.75 213.35 533.06 370.58 0.00 0.00 0.00
Minimum of Months 228.01 103.94 124.07 145.69 62.97 0.00 0.00 0.00
Maximum of Months 526.54 220.69 305.86 942.76 808.88 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 241.47 108.92 132.56 145.69 808.87 0.00 0.00 0.00
February 304.42 163.56 140.86 270.08 659.88 0.00 0.00 0.00
March 383.00 174.35 208.65 410.24 415.73 0.00 0.00 0.00
April 463.14 211.18 251.96 626.62 322.36 0.00 0.00 0.00
May 508.56 215.06 293.50 776.08 215.45 0.00 0.00 0.00
June 526.53 220.68 305.85 929.44 130.91 0.00 0.00 0.00
July 513.39 215.84 297.56 942.74 86.43 0.00 0.00 0.00
August 469.58 186.30 283.28 879.93 62.97 0.00 0.00 0.00
September 385.93 171.00 214.94 614.93 182.48 0.00 0.00 0.00
October 329.24 171.31 157.93 406.37 383.82 0.00 0.00 0.00
November 263.23 119.19 144.04 232.01 520.74 0.00 0.00 0.00
December 228.00 103.93 124.07 145.72 674.75 0.00 0.00 0.00
                 
Annual Sum or Average 385.09 171.75 213.35 533.05 370.58 0.00 0.00 0.00
Minimum of Months 228.00 103.93 124.07 145.69 62.97 0.00 0.00 0.00
Maximum of Months 526.53 220.68 305.85 942.74 808.87 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 529.26 369.00 160.26 569.73 657.49 0.00 0.00 0.00
February 493.97 331.12 162.85 585.96 569.11 0.00 0.00 0.00
March 444.25 231.52 212.73 576.98 396.05 0.00 0.00 0.00
April 332.71 108.31 224.41 485.09 325.89 0.00 0.00 0.00
May 268.82 31.24 237.57 420.82 210.84 0.00 0.00 0.00
June 248.55 13.83 234.72 470.88 131.51 0.00 0.00 0.00
July 251.28 18.74 232.54 502.30 89.73 0.00 0.00 0.00
August 300.01 56.04 243.97 610.26 73.27 0.00 0.00 0.00
September 329.94 122.72 207.22 563.89 177.13 0.00 0.00 0.00
October 478.32 309.85 168.46 695.63 359.23 0.00 0.00 0.00
November 514.58 341.47 173.11 659.98 471.84 0.00 0.00 0.00
December 521.70 367.02 154.68 600.91 576.34 0.00 0.00 0.00
                 
Annual Sum or Average 392.35 191.09 201.26 561.86 335.28 0.00 0.00 0.00
Minimum of Months 248.55 13.83 154.68 420.82 73.27 0.00 0.00 0.00
Maximum of Months 529.26 369.00 243.97 695.63 657.49 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 529.26 369.00 160.26 569.73 657.49 0.00 0.00 0.00
February 493.97 331.12 162.85 585.96 569.11 0.00 0.00 0.00
March 444.25 231.52 212.73 576.98 396.05 0.00 0.00 0.00
April 332.71 108.31 224.41 485.09 325.89 0.00 0.00 0.00
May 268.82 31.24 237.57 420.82 210.84 0.00 0.00 0.00
June 248.55 13.83 234.72 470.88 131.51 0.00 0.00 0.00
July 251.28 18.74 232.54 502.30 89.73 0.00 0.00 0.00
August 300.01 56.04 243.97 610.26 73.27 0.00 0.00 0.00
September 329.94 122.72 207.22 563.89 177.13 0.00 0.00 0.00
October 478.32 309.85 168.46 695.63 359.23 0.00 0.00 0.00
November 514.58 341.47 173.11 659.98 471.84 0.00 0.00 0.00
December 521.70 367.02 154.68 600.91 576.34 0.00 0.00 0.00
                 
Annual Sum or Average 392.35 191.09 201.26 561.86 335.28 0.00 0.00 0.00
Minimum of Months 248.55 13.83 154.68 420.82 73.27 0.00 0.00 0.00
Maximum of Months 529.26 369.00 243.97 695.63 657.49 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 529.26 369.00 160.26 569.73 657.49 0.00 0.00 0.00
February 493.97 331.12 162.85 585.96 569.11 0.00 0.00 0.00
March 444.25 231.52 212.73 576.98 396.05 0.00 0.00 0.00
April 332.71 108.31 224.41 485.09 325.89 0.00 0.00 0.00
May 268.82 31.24 237.57 420.82 210.84 0.00 0.00 0.00
June 248.55 13.83 234.72 470.88 131.51 0.00 0.00 0.00
July 251.28 18.74 232.54 502.30 89.73 0.00 0.00 0.00
August 300.01 56.04 243.97 610.26 73.27 0.00 0.00 0.00
September 329.94 122.72 207.22 563.89 177.13 0.00 0.00 0.00
October 478.32 309.85 168.46 695.63 359.23 0.00 0.00 0.00
November 514.58 341.47 173.11 659.98 471.84 0.00 0.00 0.00
December 521.70 367.02 154.68 600.91 576.34 0.00 0.00 0.00
                 
Annual Sum or Average 392.35 191.09 201.26 561.86 335.28 0.00 0.00 0.00
Minimum of Months 248.55 13.83 154.68 420.82 73.27 0.00 0.00 0.00
Maximum of Months 529.26 369.00 243.97 695.63 657.49 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 529.26 369.00 160.26 569.73 657.49 0.00 0.00 0.00
February 493.97 331.12 162.85 585.96 569.11 0.00 0.00 0.00
March 444.25 231.52 212.73 576.98 396.05 0.00 0.00 0.00
April 332.71 108.31 224.41 485.09 325.89 0.00 0.00 0.00
May 268.82 31.24 237.57 420.82 210.84 0.00 0.00 0.00
June 248.55 13.83 234.72 470.88 131.51 0.00 0.00 0.00
July 251.28 18.74 232.54 502.30 89.73 0.00 0.00 0.00
August 300.01 56.04 243.97 610.26 73.27 0.00 0.00 0.00
September 329.94 122.72 207.22 563.89 177.13 0.00 0.00 0.00
October 478.32 309.85 168.46 695.63 359.23 0.00 0.00 0.00
November 514.58 341.47 173.11 659.98 471.84 0.00 0.00 0.00
December 521.70 367.02 154.68 600.91 576.34 0.00 0.00 0.00
                 
Annual Sum or Average 392.35 191.09 201.26 561.86 335.28 0.00 0.00 0.00
Minimum of Months 248.55 13.83 154.68 420.82 73.27 0.00 0.00 0.00
Maximum of Months 529.26 369.00 243.97 695.63 657.49 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 529.24 368.98 160.25 569.71 657.46 0.00 0.00 0.00
February 493.95 331.11 162.84 585.94 569.09 0.00 0.00 0.00
March 444.23 231.51 212.72 576.96 396.03 0.00 0.00 0.00
April 332.70 108.30 224.40 485.07 325.88 0.00 0.00 0.00
May 268.81 31.24 237.57 420.81 210.84 0.00 0.00 0.00
June 248.54 13.83 234.71 470.86 131.51 0.00 0.00 0.00
July 251.27 18.74 232.53 502.28 89.72 0.00 0.00 0.00
August 300.00 56.04 243.96 610.23 73.27 0.00 0.00 0.00
September 329.92 122.71 207.21 563.87 177.13 0.00 0.00 0.00
October 478.30 309.84 168.46 695.60 359.21 0.00 0.00 0.00
November 514.56 341.45 173.11 659.96 471.82 0.00 0.00 0.00
December 521.68 367.01 154.67 600.89 576.32 0.00 0.00 0.00
                 
Annual Sum or Average 392.33 191.08 201.25 561.83 335.27 0.00 0.00 0.00
Minimum of Months 248.54 13.83 154.67 420.81 73.27 0.00 0.00 0.00
Maximum of Months 529.24 368.98 243.96 695.60 657.46 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 248.03 115.05 132.98 169.04 878.25 0.00 0.00 0.00
February 284.74 133.13 151.61 260.12 761.65 0.00 0.00 0.00
March 419.69 202.80 216.88 480.28 523.19 0.00 0.00 0.00
April 472.14 216.05 256.09 632.56 424.90 0.00 0.00 0.00
May 474.51 179.77 294.74 728.60 261.36 0.00 0.00 0.00
June 499.01 191.97 307.05 873.09 177.33 0.00 0.00 0.00
July 470.68 174.51 296.17 850.21 131.46 0.00 0.00 0.00
August 461.20 172.47 288.73 837.98 118.90 0.00 0.00 0.00
September 375.75 156.52 219.24 592.70 222.37 0.00 0.00 0.00
October 334.75 173.77 160.98 431.58 473.28 0.00 0.00 0.00
November 267.16 119.91 147.24 262.56 649.19 0.00 0.00 0.00
December 220.40 96.40 124.00 154.68 836.77 0.00 0.00 0.00
                 
Annual Sum or Average 377.81 161.15 216.66 524.20 453.31 0.00 0.00 0.00
Minimum of Months 220.40 96.40 124.00 154.68 118.90 0.00 0.00 0.00
Maximum of Months 499.01 216.05 307.05 873.09 878.25 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 248.03 115.05 132.98 169.04 878.25 0.00 0.00 0.00
February 284.74 133.13 151.61 260.12 761.65 0.00 0.00 0.00
March 419.69 202.80 216.88 480.28 523.19 0.00 0.00 0.00
April 472.14 216.05 256.09 632.56 424.90 0.00 0.00 0.00
May 474.51 179.77 294.74 728.60 261.36 0.00 0.00 0.00
June 499.01 191.97 307.05 873.09 177.33 0.00 0.00 0.00
July 470.68 174.51 296.17 850.21 131.46 0.00 0.00 0.00
August 461.20 172.47 288.73 837.98 118.90 0.00 0.00 0.00
September 375.75 156.52 219.24 592.70 222.37 0.00 0.00 0.00
October 334.75 173.77 160.98 431.58 473.28 0.00 0.00 0.00
November 267.16 119.91 147.24 262.56 649.19 0.00 0.00 0.00
December 220.40 96.40 124.00 154.68 836.77 0.00 0.00 0.00
                 
Annual Sum or Average 377.81 161.15 216.66 524.20 453.31 0.00 0.00 0.00
Minimum of Months 220.40 96.40 124.00 154.68 118.90 0.00 0.00 0.00
Maximum of Months 499.01 216.05 307.05 873.09 878.25 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 248.03 115.05 132.97 169.04 878.23 0.00 0.00 0.00
February 284.73 133.13 151.60 260.11 761.63 0.00 0.00 0.00
March 419.68 202.80 216.88 480.27 523.18 0.00 0.00 0.00
April 472.13 216.04 256.09 632.55 424.89 0.00 0.00 0.00
May 474.51 179.77 294.73 728.59 261.36 0.00 0.00 0.00
June 499.00 191.96 307.04 873.08 177.32 0.00 0.00 0.00
July 470.67 174.51 296.16 850.19 131.46 0.00 0.00 0.00
August 461.19 172.47 288.73 837.97 118.90 0.00 0.00 0.00
September 375.75 156.52 219.23 592.69 222.36 0.00 0.00 0.00
October 334.75 173.77 160.98 431.57 473.27 0.00 0.00 0.00
November 267.15 119.91 147.24 262.55 649.18 0.00 0.00 0.00
December 220.40 96.40 124.00 154.67 836.76 0.00 0.00 0.00
                 
Annual Sum or Average 377.81 161.15 216.66 524.19 453.31 0.00 0.00 0.00
Minimum of Months 220.40 96.40 124.00 154.67 118.90 0.00 0.00 0.00
Maximum of Months 499.00 216.04 307.04 873.08 878.23 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 494.80 0.00 494.80 67.62 3618.53 0.00 0.00 0.00
February 548.44 0.00 548.44 226.63 2948.55 0.00 0.00 0.00
March 769.98 0.00 769.98 505.89 1849.95 0.00 0.00 0.00
April 931.36 4.13 927.23 1011.13 1463.35 0.00 0.00 0.00
May 1113.89 35.55 1078.34 1554.53 941.58 0.00 0.00 0.00
June 1225.88 80.94 1144.95 2259.93 593.62 0.00 0.00 0.00
July 1156.62 56.22 1100.40 2273.74 424.86 0.00 0.00 0.00
August 1028.63 11.21 1017.42 2082.17 349.03 0.00 0.00 0.00
September 777.54 0.11 777.43 1172.59 797.91 0.00 0.00 0.00
October 591.19 0.00 591.19 521.93 1678.93 0.00 0.00 0.00
November 529.10 0.00 529.10 265.18 2317.87 0.00 0.00 0.00
December 457.41 0.00 457.41 65.86 2940.57 0.00 0.00 0.00
                 
Annual Sum or Average 803.45 15.75 787.71 1005.02 1653.83 0.00 0.00 0.00
Minimum of Months 457.41 0.00 457.41 65.86 349.03 0.00 0.00 0.00
Maximum of Months 1225.88 80.94 1144.95 2273.74 3618.53 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 724.42 326.75 397.67 475.47 2161.23 0.00 0.00 0.00
February 913.27 490.69 422.58 846.25 1775.69 0.00 0.00 0.00
March 1149.00 523.06 625.94 1254.53 1138.15 0.00 0.00 0.00
April 1389.44 633.55 755.89 1882.06 921.40 0.00 0.00 0.00
May 1525.70 645.20 880.51 2316.15 621.07 0.00 0.00 0.00
June 1579.62 662.06 917.56 2769.83 397.90 0.00 0.00 0.00
July 1540.19 647.52 892.67 2803.47 286.61 0.00 0.00 0.00
August 1408.77 558.91 849.86 2613.71 234.14 0.00 0.00 0.00
September 1157.81 513.00 644.82 1845.26 511.97 0.00 0.00 0.00
October 987.71 513.93 473.78 1240.08 1040.64 0.00 0.00 0.00
November 789.68 357.57 432.12 751.69 1386.82 0.00 0.00 0.00
December 684.02 311.80 372.22 483.00 1747.92 0.00 0.00 0.00
                 
Annual Sum or Average 1155.29 515.25 640.04 1610.79 1014.75 0.00 0.00 0.00
Minimum of Months 684.02 311.80 372.22 475.47 234.14 0.00 0.00 0.00
Maximum of Months 1579.62 662.06 917.56 2803.47 2161.23 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 2646.25 1844.96 801.29 2860.62 3100.38 0.00 0.00 0.00
February 2469.84 1655.60 814.24 2936.62 2666.05 0.00 0.00 0.00
March 2221.22 1157.57 1063.65 2877.22 1867.14 0.00 0.00 0.00
April 1663.55 541.52 1122.03 2430.47 1544.21 0.00 0.00 0.00
May 1344.08 156.22 1187.86 2107.09 1010.31 0.00 0.00 0.00
June 1242.74 69.15 1173.59 2368.93 636.50 0.00 0.00 0.00
July 1256.39 93.68 1162.70 2525.20 448.85 0.00 0.00 0.00
August 1500.04 280.21 1219.82 3058.05 379.01 0.00 0.00 0.00
September 1649.67 613.59 1036.08 2811.86 846.78 0.00 0.00 0.00
October 2391.55 1549.25 842.30 3461.69 1699.09 0.00 0.00 0.00
November 2572.88 1707.32 865.56 3305.13 2217.01 0.00 0.00 0.00
December 2608.47 1835.08 773.39 3027.11 2638.48 0.00 0.00 0.00
                 
Annual Sum or Average 1961.72 955.43 1006.30 2814.09 1581.99 0.00 0.00 0.00
Minimum of Months 1242.74 69.15 773.39 2107.09 379.01 0.00 0.00 0.00
Maximum of Months 2646.25 1844.96 1219.82 3461.69 3100.38 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 744.08 345.16 398.93 550.57 2310.46 0.00 0.00 0.00
February 854.20 399.39 454.81 840.82 1938.23 0.00 0.00 0.00
March 1259.04 608.40 650.65 1514.37 1291.14 0.00 0.00 0.00
April 1416.40 648.14 768.26 1978.18 1060.91 0.00 0.00 0.00
May 1423.53 539.32 884.21 2211.06 709.27 0.00 0.00 0.00
June 1497.02 575.90 921.13 2651.11 469.23 0.00 0.00 0.00
July 1412.04 523.54 888.50 2599.77 337.53 0.00 0.00 0.00
August 1383.59 517.41 866.19 2573.06 291.95 0.00 0.00 0.00
September 1127.25 469.55 657.70 1809.13 576.98 0.00 0.00 0.00
October 1004.25 521.31 482.93 1348.30 1179.86 0.00 0.00 0.00
November 801.46 359.74 441.72 874.13 1574.55 0.00 0.00 0.00
December 661.20 289.21 371.99 534.13 1947.33 0.00 0.00 0.00
                 
Annual Sum or Average 1133.43 483.44 649.98 1627.91 1136.48 0.00 0.00 0.00
Minimum of Months 661.20 289.21 371.99 534.13 291.95 0.00 0.00 0.00
Maximum of Months 1497.02 648.14 921.13 2651.11 2310.46 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 494.80 0.00 494.80 79.37 3447.92 0.00 0.00 0.00
February 548.44 0.00 548.44 242.49 2808.86 0.00 0.00 0.00
March 769.98 0.00 769.98 535.30 1723.39 0.00 0.00 0.00
April 931.36 4.13 927.23 1031.14 1390.93 0.00 0.00 0.00
May 1113.89 35.55 1078.34 1545.00 925.80 0.00 0.00 0.00
June 1225.88 80.94 1144.95 2232.59 600.17 0.00 0.00 0.00
July 1156.62 56.22 1100.40 2239.23 435.37 0.00 0.00 0.00
August 1028.63 11.21 1017.42 2048.58 361.13 0.00 0.00 0.00
September 777.54 0.11 777.43 1172.18 767.06 0.00 0.00 0.00
October 591.19 0.00 591.19 551.02 1549.59 0.00 0.00 0.00
November 529.10 0.00 529.10 309.26 2124.17 0.00 0.00 0.00
December 457.41 0.00 457.41 79.71 2720.45 0.00 0.00 0.00
                 
Annual Sum or Average 803.45 15.75 787.71 1009.78 1564.91 0.00 0.00 0.00
Minimum of Months 457.41 0.00 457.41 79.37 361.13 0.00 0.00 0.00
Maximum of Months 1225.88 80.94 1144.95 2239.23 3447.92 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 724.42 326.75 397.67 496.91 2050.50 0.00 0.00 0.00
February 913.27 490.69 422.58 867.77 1690.21 0.00 0.00 0.00
March 1149.00 523.06 625.94 1278.85 1072.19 0.00 0.00 0.00
April 1389.44 633.55 755.89 1890.47 886.27 0.00 0.00 0.00
May 1525.70 645.20 880.51 2304.24 616.66 0.00 0.00 0.00
June 1579.62 662.06 917.56 2747.33 404.86 0.00 0.00 0.00
July 1540.19 647.52 892.67 2777.75 294.07 0.00 0.00 0.00
August 1408.77 558.91 849.86 2588.32 242.73 0.00 0.00 0.00
September 1157.81 513.00 644.82 1840.04 498.30 0.00 0.00 0.00
October 987.71 513.93 473.78 1260.32 973.46 0.00 0.00 0.00
November 789.68 357.57 432.12 794.61 1279.85 0.00 0.00 0.00
December 684.02 311.80 372.22 508.76 1613.92 0.00 0.00 0.00
                 
Annual Sum or Average 1155.29 515.25 640.04 1616.82 964.86 0.00 0.00 0.00
Minimum of Months 684.02 311.80 372.22 496.91 242.73 0.00 0.00 0.00
Maximum of Months 1579.62 662.06 917.56 2777.75 2050.50 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 2646.25 1844.96 801.29 2917.58 2914.02 0.00 0.00 0.00
February 2469.84 1655.60 814.24 2972.45 2521.39 0.00 0.00 0.00
March 2221.22 1157.57 1063.65 2906.52 1751.59 0.00 0.00 0.00
April 1663.55 541.52 1122.03 2445.33 1470.67 0.00 0.00 0.00
May 1344.08 156.22 1187.86 2096.44 990.53 0.00 0.00 0.00
June 1242.74 69.15 1173.59 2343.46 639.49 0.00 0.00 0.00
July 1256.39 93.68 1162.70 2494.11 456.43 0.00 0.00 0.00
August 1500.04 280.21 1219.82 3025.18 389.23 0.00 0.00 0.00
September 1649.67 613.59 1036.08 2806.97 816.78 0.00 0.00 0.00
October 2391.55 1549.25 842.30 3483.62 1586.40 0.00 0.00 0.00
November 2572.88 1707.32 865.56 3363.98 2044.53 0.00 0.00 0.00
December 2608.47 1835.08 773.39 3087.93 2427.41 0.00 0.00 0.00
                 
Annual Sum or Average 1961.72 955.43 1006.30 2828.42 1495.14 0.00 0.00 0.00
Minimum of Months 1242.74 69.15 773.39 2096.44 389.23 0.00 0.00 0.00
Maximum of Months 2646.25 1844.96 1219.82 3483.62 2914.02 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 744.08 345.16 398.93 564.74 2191.53 0.00 0.00 0.00
February 854.20 399.39 454.81 849.03 1854.56 0.00 0.00 0.00
March 1259.04 608.40 650.65 1522.66 1221.09 0.00 0.00 0.00
April 1416.40 648.14 768.26 1983.45 1016.83 0.00 0.00 0.00
May 1423.53 539.32 884.21 2202.53 696.91 0.00 0.00 0.00
June 1497.02 575.90 921.13 2631.47 469.93 0.00 0.00 0.00
July 1412.04 523.54 888.50 2579.77 340.99 0.00 0.00 0.00
August 1383.59 517.41 866.19 2552.40 296.63 0.00 0.00 0.00
September 1127.25 469.55 657.70 1807.41 557.69 0.00 0.00 0.00
October 1004.25 521.31 482.93 1357.79 1110.68 0.00 0.00 0.00
November 801.46 359.74 441.72 896.18 1470.74 0.00 0.00 0.00
December 661.20 289.21 371.99 547.63 1817.71 0.00 0.00 0.00
                 
Annual Sum or Average 1133.43 483.44 649.98 1628.72 1083.08 0.00 0.00 0.00
Minimum of Months 661.20 289.21 371.99 547.63 296.63 0.00 0.00 0.00
Maximum of Months 1497.02 648.14 921.13 2631.47 2191.53 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.265058E+09 0.00 0.265058E+09 22227888.20 0.219857E+10
February 0.265359E+09 0.00 0.265359E+09 83495965.94 0.163224E+10
March 0.412466E+09 0.00 0.412466E+09 0.227285E+09 0.114344E+10
April 0.482821E+09 2141454.47 0.480680E+09 0.486865E+09 0.845472E+09
May 0.596695E+09 19043240.04 0.577652E+09 0.816775E+09 0.538919E+09
June 0.635506E+09 41958388.76 0.593547E+09 0.115904E+10 0.319987E+09
July 0.619587E+09 30118598.77 0.589469E+09 0.120595E+10 0.229149E+09
August 0.551021E+09 6002513.07 0.545019E+09 0.110056E+10 0.183392E+09
September 0.403084E+09 56742.98 0.403027E+09 0.590276E+09 0.457060E+09
October 0.316694E+09 0.00 0.316694E+09 0.243291E+09 0.104228E+10
November 0.274287E+09 0.00 0.274287E+09 93173326.51 0.140940E+10
December 0.245026E+09 0.00 0.245026E+09 16985681.95 0.189693E+10
           
Annual Sum or Average 0.506760E+10 99320938.09 0.496828E+10 0.604593E+10 0.118968E+11
Minimum of Months 0.245026E+09 0.00 0.245026E+09 16985681.95 0.183392E+09
Maximum of Months 0.635506E+09 41958388.76 0.593547E+09 0.120595E+10 0.219857E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.265057E+09 0.00 0.265057E+09 22227840.77 0.219857E+10
February 0.265359E+09 0.00 0.265359E+09 83495860.33 0.163224E+10
March 0.412465E+09 0.00 0.412465E+09 0.227285E+09 0.114344E+10
April 0.482821E+09 2141451.90 0.480679E+09 0.486864E+09 0.845472E+09
May 0.596695E+09 19043217.19 0.577651E+09 0.816775E+09 0.538919E+09
June 0.635505E+09 41958338.42 0.593547E+09 0.115904E+10 0.319987E+09
July 0.619587E+09 30118562.63 0.589468E+09 0.120595E+10 0.229149E+09
August 0.551021E+09 6002505.87 0.545018E+09 0.110056E+10 0.183392E+09
September 0.403084E+09 56742.91 0.403027E+09 0.590275E+09 0.457060E+09
October 0.316693E+09 0.00 0.316693E+09 0.243291E+09 0.104228E+10
November 0.274287E+09 0.00 0.274287E+09 93173178.34 0.140940E+10
December 0.245026E+09 0.00 0.245026E+09 16985639.22 0.189693E+10
           
Annual Sum or Average 0.506760E+10 99320818.92 0.496828E+10 0.604593E+10 0.118968E+11
Minimum of Months 0.245026E+09 0.00 0.245026E+09 16985639.22 0.183392E+09
Maximum of Months 0.635505E+09 41958338.42 0.593547E+09 0.120595E+10 0.219857E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.265058E+09 0.00 0.265058E+09 22227888.20 0.219857E+10
February 0.265359E+09 0.00 0.265359E+09 83495965.94 0.163224E+10
March 0.412466E+09 0.00 0.412466E+09 0.227285E+09 0.114344E+10
April 0.482821E+09 2141454.47 0.480680E+09 0.486865E+09 0.845472E+09
May 0.596695E+09 19043240.04 0.577652E+09 0.816775E+09 0.538919E+09
June 0.635506E+09 41958388.76 0.593547E+09 0.115904E+10 0.319987E+09
July 0.619587E+09 30118598.77 0.589469E+09 0.120595E+10 0.229149E+09
August 0.551021E+09 6002513.07 0.545019E+09 0.110056E+10 0.183392E+09
September 0.403084E+09 56742.98 0.403027E+09 0.590276E+09 0.457060E+09
October 0.316694E+09 0.00 0.316694E+09 0.243291E+09 0.104228E+10
November 0.274287E+09 0.00 0.274287E+09 93173326.51 0.140940E+10
December 0.245026E+09 0.00 0.245026E+09 16985681.95 0.189693E+10
           
Annual Sum or Average 0.506760E+10 99320938.09 0.496828E+10 0.604593E+10 0.118968E+11
Minimum of Months 0.245026E+09 0.00 0.245026E+09 16985681.95 0.183392E+09
Maximum of Months 0.635506E+09 41958388.76 0.593547E+09 0.120595E+10 0.219857E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.265057E+09 0.00 0.265057E+09 22227840.77 0.219857E+10
February 0.265359E+09 0.00 0.265359E+09 83495860.33 0.163224E+10
March 0.412465E+09 0.00 0.412465E+09 0.227285E+09 0.114344E+10
April 0.482821E+09 2141451.90 0.480679E+09 0.486864E+09 0.845472E+09
May 0.596695E+09 19043217.19 0.577651E+09 0.816775E+09 0.538919E+09
June 0.635505E+09 41958338.42 0.593547E+09 0.115904E+10 0.319987E+09
July 0.619587E+09 30118562.63 0.589468E+09 0.120595E+10 0.229149E+09
August 0.551021E+09 6002505.87 0.545018E+09 0.110056E+10 0.183392E+09
September 0.403084E+09 56742.91 0.403027E+09 0.590275E+09 0.457060E+09
October 0.316693E+09 0.00 0.316693E+09 0.243291E+09 0.104228E+10
November 0.274287E+09 0.00 0.274287E+09 93173178.34 0.140940E+10
December 0.245026E+09 0.00 0.245026E+09 16985639.22 0.189693E+10
           
Annual Sum or Average 0.506760E+10 99320818.92 0.496828E+10 0.604593E+10 0.118968E+11
Minimum of Months 0.245026E+09 0.00 0.245026E+09 16985639.22 0.183392E+09
Maximum of Months 0.635505E+09 41958338.42 0.593547E+09 0.120595E+10 0.219857E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.265047E+09 0.00 0.265047E+09 22226992.32 0.219848E+10
February 0.265348E+09 0.00 0.265348E+09 83492600.69 0.163217E+10
March 0.412449E+09 0.00 0.412449E+09 0.227276E+09 0.114339E+10
April 0.482802E+09 2141368.16 0.480660E+09 0.486845E+09 0.845438E+09
May 0.596671E+09 19042472.51 0.577629E+09 0.816742E+09 0.538897E+09
June 0.635480E+09 41956697.65 0.593523E+09 0.115899E+10 0.319974E+09
July 0.619563E+09 30117384.86 0.589445E+09 0.120590E+10 0.229140E+09
August 0.550999E+09 6002271.14 0.544997E+09 0.110052E+10 0.183384E+09
September 0.403068E+09 56740.69 0.403011E+09 0.590252E+09 0.457042E+09
October 0.316681E+09 0.00 0.316681E+09 0.243281E+09 0.104224E+10
November 0.274276E+09 0.00 0.274276E+09 93169571.22 0.140934E+10
December 0.245016E+09 0.00 0.245016E+09 16984997.36 0.189685E+10
           
Annual Sum or Average 0.506740E+10 99316935.02 0.496808E+10 0.604569E+10 0.118964E+11
Minimum of Months 0.245016E+09 0.00 0.245016E+09 16984997.36 0.183384E+09
Maximum of Months 0.635480E+09 41956697.65 0.593523E+09 0.120590E+10 0.219848E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.646771E+09 0.291727E+09 0.355045E+09 0.390226E+09 0.216651E+10
February 0.736468E+09 0.395699E+09 0.340769E+09 0.653394E+09 0.159641E+10
March 0.102584E+10 0.466991E+09 0.558846E+09 0.109881E+10 0.111352E+10
April 0.120049E+10 0.547390E+09 0.653095E+09 0.162422E+10 0.835561E+09
May 0.136216E+10 0.576039E+09 0.786124E+09 0.207870E+10 0.577072E+09
June 0.136480E+10 0.572023E+09 0.792781E+09 0.240916E+10 0.339316E+09
July 0.137510E+10 0.578110E+09 0.796986E+09 0.252509E+10 0.231509E+09
August 0.125776E+10 0.498998E+09 0.758761E+09 0.235685E+10 0.168665E+09
September 0.100036E+10 0.443234E+09 0.557127E+09 0.159393E+10 0.472996E+09
October 0.881839E+09 0.458842E+09 0.422997E+09 0.108843E+10 0.102805E+10
November 0.682295E+09 0.308940E+09 0.373354E+09 0.601382E+09 0.134979E+10
December 0.610699E+09 0.278380E+09 0.332319E+09 0.390298E+09 0.180728E+10
           
Annual Sum or Average 0.121446E+11 0.541637E+10 0.672820E+10 0.168105E+11 0.116867E+11
Minimum of Months 0.610699E+09 0.278380E+09 0.332319E+09 0.390226E+09 0.168665E+09
Maximum of Months 0.137510E+10 0.578110E+09 0.796986E+09 0.252509E+10 0.216651E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.646771E+09 0.291727E+09 0.355045E+09 0.390226E+09 0.216651E+10
February 0.736468E+09 0.395699E+09 0.340769E+09 0.653394E+09 0.159641E+10
March 0.102584E+10 0.466991E+09 0.558846E+09 0.109881E+10 0.111352E+10
April 0.120049E+10 0.547390E+09 0.653095E+09 0.162422E+10 0.835561E+09
May 0.136216E+10 0.576039E+09 0.786124E+09 0.207870E+10 0.577072E+09
June 0.136480E+10 0.572023E+09 0.792781E+09 0.240916E+10 0.339316E+09
July 0.137510E+10 0.578110E+09 0.796986E+09 0.252509E+10 0.231509E+09
August 0.125776E+10 0.498998E+09 0.758761E+09 0.235685E+10 0.168665E+09
September 0.100036E+10 0.443234E+09 0.557127E+09 0.159393E+10 0.472996E+09
October 0.881839E+09 0.458842E+09 0.422997E+09 0.108843E+10 0.102805E+10
November 0.682295E+09 0.308940E+09 0.373354E+09 0.601382E+09 0.134979E+10
December 0.610699E+09 0.278380E+09 0.332319E+09 0.390298E+09 0.180728E+10
           
Annual Sum or Average 0.121446E+11 0.541637E+10 0.672820E+10 0.168105E+11 0.116867E+11
Minimum of Months 0.610699E+09 0.278380E+09 0.332319E+09 0.390226E+09 0.168665E+09
Maximum of Months 0.137510E+10 0.578110E+09 0.796986E+09 0.252509E+10 0.216651E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.646759E+09 0.291721E+09 0.355038E+09 0.390219E+09 0.216647E+10
February 0.736454E+09 0.395692E+09 0.340763E+09 0.653382E+09 0.159638E+10
March 0.102582E+10 0.466982E+09 0.558836E+09 0.109879E+10 0.111350E+10
April 0.120046E+10 0.547380E+09 0.653083E+09 0.162419E+10 0.835546E+09
May 0.136214E+10 0.576029E+09 0.786110E+09 0.207866E+10 0.577062E+09
June 0.136478E+10 0.572012E+09 0.792766E+09 0.240912E+10 0.339309E+09
July 0.137507E+10 0.578100E+09 0.796972E+09 0.252505E+10 0.231504E+09
August 0.125774E+10 0.498989E+09 0.758747E+09 0.235681E+10 0.168662E+09
September 0.100034E+10 0.443226E+09 0.557117E+09 0.159390E+10 0.472987E+09
October 0.881823E+09 0.458834E+09 0.422989E+09 0.108841E+10 0.102803E+10
November 0.682282E+09 0.308935E+09 0.373347E+09 0.601371E+09 0.134976E+10
December 0.610688E+09 0.278375E+09 0.332313E+09 0.390290E+09 0.180725E+10
           
Annual Sum or Average 0.121444E+11 0.541627E+10 0.672808E+10 0.168102E+11 0.116865E+11
Minimum of Months 0.610688E+09 0.278375E+09 0.332313E+09 0.390219E+09 0.168662E+09
Maximum of Months 0.137507E+10 0.578100E+09 0.796972E+09 0.252505E+10 0.216647E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.141756E+10 0.988319E+09 0.429242E+09 0.152597E+10 0.176102E+10
February 0.119502E+10 0.801056E+09 0.393966E+09 0.141756E+10 0.137679E+10
March 0.118988E+10 0.620094E+09 0.569784E+09 0.154539E+10 0.106078E+10
April 0.862392E+09 0.280727E+09 0.581665E+09 0.125735E+10 0.844704E+09
May 0.720004E+09 83683975.89 0.636320E+09 0.112714E+10 0.564724E+09
June 0.644245E+09 35849676.45 0.608395E+09 0.122053E+10 0.340884E+09
July 0.673029E+09 50184911.53 0.622844E+09 0.134535E+10 0.240321E+09
August 0.803549E+09 0.150106E+09 0.653443E+09 0.163451E+10 0.196251E+09
September 0.855200E+09 0.318090E+09 0.537110E+09 0.146161E+10 0.459131E+09
October 0.128112E+10 0.829913E+09 0.451210E+09 0.186317E+10 0.962152E+09
November 0.133380E+10 0.885085E+09 0.448711E+09 0.171068E+10 0.122301E+10
December 0.139732E+10 0.983028E+09 0.414296E+09 0.160948E+10 0.154367E+10
           
Annual Sum or Average 0.123731E+11 0.602614E+10 0.634699E+10 0.177187E+11 0.105734E+11
Minimum of Months 0.644245E+09 35849676.45 0.393966E+09 0.112714E+10 0.196251E+09
Maximum of Months 0.141756E+10 0.988319E+09 0.653443E+09 0.186317E+10 0.176102E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.141756E+10 0.988318E+09 0.429242E+09 0.152597E+10 0.176102E+10
February 0.119502E+10 0.801055E+09 0.393965E+09 0.141755E+10 0.137679E+10
March 0.118988E+10 0.620094E+09 0.569783E+09 0.154539E+10 0.106078E+10
April 0.862392E+09 0.280727E+09 0.581665E+09 0.125735E+10 0.844704E+09
May 0.720003E+09 83683875.47 0.636320E+09 0.112713E+10 0.564724E+09
June 0.644244E+09 35849633.43 0.608394E+09 0.122053E+10 0.340884E+09
July 0.673029E+09 50184851.31 0.622844E+09 0.134535E+10 0.240321E+09
August 0.803548E+09 0.150106E+09 0.653443E+09 0.163451E+10 0.196251E+09
September 0.855199E+09 0.318089E+09 0.537109E+09 0.146161E+10 0.459131E+09
October 0.128112E+10 0.829912E+09 0.451210E+09 0.186317E+10 0.962152E+09
November 0.133379E+10 0.885084E+09 0.448711E+09 0.171068E+10 0.122301E+10
December 0.139732E+10 0.983026E+09 0.414295E+09 0.160948E+10 0.154367E+10
           
Annual Sum or Average 0.123731E+11 0.602613E+10 0.634698E+10 0.177187E+11 0.105734E+11
Minimum of Months 0.644244E+09 35849633.43 0.393965E+09 0.112713E+10 0.196251E+09
Maximum of Months 0.141756E+10 0.988318E+09 0.653443E+09 0.186317E+10 0.176102E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.141756E+10 0.988319E+09 0.429242E+09 0.152597E+10 0.176102E+10
February 0.119502E+10 0.801056E+09 0.393966E+09 0.141756E+10 0.137679E+10
March 0.118988E+10 0.620094E+09 0.569784E+09 0.154539E+10 0.106078E+10
April 0.862392E+09 0.280727E+09 0.581665E+09 0.125735E+10 0.844704E+09
May 0.720004E+09 83683975.89 0.636320E+09 0.112714E+10 0.564724E+09
June 0.644245E+09 35849676.45 0.608395E+09 0.122053E+10 0.340884E+09
July 0.673029E+09 50184911.53 0.622844E+09 0.134535E+10 0.240321E+09
August 0.803549E+09 0.150106E+09 0.653443E+09 0.163451E+10 0.196251E+09
September 0.855200E+09 0.318090E+09 0.537110E+09 0.146161E+10 0.459131E+09
October 0.128112E+10 0.829913E+09 0.451210E+09 0.186317E+10 0.962152E+09
November 0.133380E+10 0.885085E+09 0.448711E+09 0.171068E+10 0.122301E+10
December 0.139732E+10 0.983028E+09 0.414296E+09 0.160948E+10 0.154367E+10
           
Annual Sum or Average 0.123731E+11 0.602614E+10 0.634699E+10 0.177187E+11 0.105734E+11
Minimum of Months 0.644245E+09 35849676.45 0.393966E+09 0.112714E+10 0.196251E+09
Maximum of Months 0.141756E+10 0.988319E+09 0.653443E+09 0.186317E+10 0.176102E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.141756E+10 0.988318E+09 0.429242E+09 0.152597E+10 0.176102E+10
February 0.119502E+10 0.801055E+09 0.393965E+09 0.141755E+10 0.137679E+10
March 0.118988E+10 0.620094E+09 0.569783E+09 0.154539E+10 0.106078E+10
April 0.862392E+09 0.280727E+09 0.581665E+09 0.125735E+10 0.844704E+09
May 0.720003E+09 83683875.47 0.636320E+09 0.112713E+10 0.564724E+09
June 0.644244E+09 35849633.43 0.608394E+09 0.122053E+10 0.340884E+09
July 0.673029E+09 50184851.31 0.622844E+09 0.134535E+10 0.240321E+09
August 0.803548E+09 0.150106E+09 0.653443E+09 0.163451E+10 0.196251E+09
September 0.855199E+09 0.318089E+09 0.537109E+09 0.146161E+10 0.459131E+09
October 0.128112E+10 0.829912E+09 0.451210E+09 0.186317E+10 0.962152E+09
November 0.133379E+10 0.885084E+09 0.448711E+09 0.171068E+10 0.122301E+10
December 0.139732E+10 0.983026E+09 0.414295E+09 0.160948E+10 0.154367E+10
           
Annual Sum or Average 0.123731E+11 0.602613E+10 0.634698E+10 0.177187E+11 0.105734E+11
Minimum of Months 0.644244E+09 35849633.43 0.393965E+09 0.112713E+10 0.196251E+09
Maximum of Months 0.141756E+10 0.988318E+09 0.653443E+09 0.186317E+10 0.176102E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.141750E+10 0.988279E+09 0.429225E+09 0.152591E+10 0.176095E+10
February 0.119497E+10 0.801023E+09 0.393950E+09 0.141750E+10 0.137674E+10
March 0.118983E+10 0.620069E+09 0.569761E+09 0.154533E+10 0.106074E+10
April 0.862358E+09 0.280716E+09 0.581642E+09 0.125730E+10 0.844670E+09
May 0.719975E+09 83680603.05 0.636294E+09 0.112709E+10 0.564702E+09
June 0.644219E+09 35848231.55 0.608370E+09 0.122048E+10 0.340870E+09
July 0.673002E+09 50182888.86 0.622819E+09 0.134530E+10 0.240311E+09
August 0.803517E+09 0.150100E+09 0.653417E+09 0.163444E+10 0.196243E+09
September 0.855165E+09 0.318077E+09 0.537088E+09 0.146155E+10 0.459112E+09
October 0.128107E+10 0.829879E+09 0.451192E+09 0.186310E+10 0.962113E+09
November 0.133374E+10 0.885050E+09 0.448693E+09 0.171061E+10 0.122297E+10
December 0.139727E+10 0.982988E+09 0.414279E+09 0.160942E+10 0.154361E+10
           
Annual Sum or Average 0.123726E+11 0.602589E+10 0.634673E+10 0.177180E+11 0.105730E+11
Minimum of Months 0.644219E+09 35848231.55 0.393950E+09 0.112709E+10 0.196243E+09
Maximum of Months 0.141750E+10 0.988279E+09 0.653417E+09 0.186310E+10 0.176095E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.664324E+09 0.308160E+09 0.356164E+09 0.452758E+09 0.235230E+10
February 0.688836E+09 0.322072E+09 0.366763E+09 0.629278E+09 0.184258E+10
March 0.112409E+10 0.543184E+09 0.580902E+09 0.128637E+10 0.140132E+10
April 0.122378E+10 0.559998E+09 0.663785E+09 0.163960E+10 0.110134E+10
May 0.127094E+10 0.481508E+09 0.789429E+09 0.195149E+10 0.700029E+09
June 0.129344E+10 0.497581E+09 0.795861E+09 0.226306E+10 0.459629E+09
July 0.126068E+10 0.467417E+09 0.793262E+09 0.227720E+10 0.352103E+09
August 0.123529E+10 0.461948E+09 0.773338E+09 0.224446E+10 0.318464E+09
September 0.973955E+09 0.405695E+09 0.568260E+09 0.153629E+10 0.576377E+09
October 0.896601E+09 0.465434E+09 0.431167E+09 0.115595E+10 0.126763E+10
November 0.692470E+09 0.310816E+09 0.381654E+09 0.680547E+09 0.168271E+10
December 0.590326E+09 0.258209E+09 0.332117E+09 0.414288E+09 0.224121E+10
           
Annual Sum or Average 0.119147E+11 0.508202E+10 0.683270E+10 0.165313E+11 0.142957E+11
Minimum of Months 0.590326E+09 0.258209E+09 0.332117E+09 0.414288E+09 0.318464E+09
Maximum of Months 0.129344E+10 0.559998E+09 0.795861E+09 0.227720E+10 0.235230E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.664324E+09 0.308160E+09 0.356164E+09 0.452758E+09 0.235230E+10
February 0.688836E+09 0.322072E+09 0.366763E+09 0.629278E+09 0.184258E+10
March 0.112409E+10 0.543184E+09 0.580902E+09 0.128637E+10 0.140132E+10
April 0.122378E+10 0.559998E+09 0.663785E+09 0.163960E+10 0.110134E+10
May 0.127094E+10 0.481508E+09 0.789429E+09 0.195149E+10 0.700029E+09
June 0.129344E+10 0.497581E+09 0.795861E+09 0.226306E+10 0.459629E+09
July 0.126068E+10 0.467417E+09 0.793262E+09 0.227720E+10 0.352103E+09
August 0.123529E+10 0.461948E+09 0.773338E+09 0.224446E+10 0.318464E+09
September 0.973955E+09 0.405695E+09 0.568260E+09 0.153629E+10 0.576377E+09
October 0.896601E+09 0.465434E+09 0.431167E+09 0.115595E+10 0.126763E+10
November 0.692470E+09 0.310816E+09 0.381654E+09 0.680547E+09 0.168271E+10
December 0.590326E+09 0.258209E+09 0.332117E+09 0.414288E+09 0.224121E+10
           
Annual Sum or Average 0.119147E+11 0.508202E+10 0.683270E+10 0.165313E+11 0.142957E+11
Minimum of Months 0.590326E+09 0.258209E+09 0.332117E+09 0.414288E+09 0.318464E+09
Maximum of Months 0.129344E+10 0.559998E+09 0.795861E+09 0.227720E+10 0.235230E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.664312E+09 0.308155E+09 0.356157E+09 0.452750E+09 0.235226E+10
February 0.688823E+09 0.322067E+09 0.366757E+09 0.629266E+09 0.184254E+10
March 0.112407E+10 0.543174E+09 0.580892E+09 0.128635E+10 0.140130E+10
April 0.122376E+10 0.559988E+09 0.663773E+09 0.163957E+10 0.110132E+10
May 0.127091E+10 0.481499E+09 0.789415E+09 0.195145E+10 0.700016E+09
June 0.129342E+10 0.497572E+09 0.795846E+09 0.226302E+10 0.459621E+09
July 0.126066E+10 0.467408E+09 0.793247E+09 0.227715E+10 0.352096E+09
August 0.123526E+10 0.461939E+09 0.773324E+09 0.224441E+10 0.318458E+09
September 0.973937E+09 0.405687E+09 0.568250E+09 0.153626E+10 0.576366E+09
October 0.896584E+09 0.465426E+09 0.431159E+09 0.115593E+10 0.126761E+10
November 0.692457E+09 0.310810E+09 0.381647E+09 0.680535E+09 0.168268E+10
December 0.590315E+09 0.258205E+09 0.332110E+09 0.414280E+09 0.224117E+10
           
Annual Sum or Average 0.119145E+11 0.508193E+10 0.683258E+10 0.165310E+11 0.142954E+11
Minimum of Months 0.590315E+09 0.258205E+09 0.332110E+09 0.414280E+09 0.318458E+09
Maximum of Months 0.129342E+10 0.559988E+09 0.795846E+09 0.227715E+10 0.235226E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.132527E+10 0.00 0.132527E+10 0.181104E+09 0.969187E+10
February 0.132678E+10 0.00 0.132678E+10 0.548263E+09 0.713312E+10
March 0.206230E+10 0.00 0.206230E+10 0.135498E+10 0.495491E+10
April 0.241408E+10 10707142.87 0.240337E+10 0.262085E+10 0.379300E+10
May 0.298344E+10 95215048.85 0.288822E+10 0.416365E+10 0.252193E+10
June 0.317749E+10 0.209789E+09 0.296770E+10 0.585773E+10 0.153865E+10
July 0.309790E+10 0.150591E+09 0.294731E+10 0.608999E+10 0.113796E+10
August 0.275507E+10 30012202.44 0.272506E+10 0.557687E+10 0.934833E+09
September 0.201540E+10 283711.47 0.201511E+10 0.303936E+10 0.206818E+10
October 0.158345E+10 0.00 0.158345E+10 0.139793E+10 0.449683E+10
November 0.137142E+10 0.00 0.137142E+10 0.687335E+09 0.600792E+10
December 0.122512E+10 0.00 0.122512E+10 0.176393E+09 0.787604E+10
           
Annual Sum or Average 0.253377E+11 0.496599E+09 0.248411E+11 0.316945E+11 0.521552E+11
Minimum of Months 0.122512E+10 0.00 0.122512E+10 0.176393E+09 0.934833E+09
Maximum of Months 0.317749E+10 0.209789E+09 0.296770E+10 0.608999E+10 0.969187E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.194029E+10 0.875171E+09 0.106512E+10 0.127350E+10 0.578864E+10
February 0.220938E+10 0.118708E+10 0.102230E+10 0.204724E+10 0.429575E+10
March 0.307748E+10 0.140096E+10 0.167652E+10 0.336012E+10 0.304843E+10
April 0.360142E+10 0.164215E+10 0.195927E+10 0.487829E+10 0.238827E+10
May 0.408645E+10 0.172810E+10 0.235835E+10 0.620357E+10 0.166347E+10
June 0.409437E+10 0.171605E+10 0.237832E+10 0.717939E+10 0.103134E+10
July 0.412525E+10 0.173431E+10 0.239094E+10 0.750882E+10 0.767652E+09
August 0.377324E+10 0.149698E+10 0.227626E+10 0.700055E+10 0.627127E+09
September 0.300105E+10 0.132969E+10 0.167136E+10 0.478292E+10 0.132704E+10
October 0.264549E+10 0.137651E+10 0.126898E+10 0.332144E+10 0.278725E+10
November 0.204686E+10 0.926812E+09 0.112005E+10 0.194838E+10 0.359463E+10
December 0.183208E+10 0.835132E+09 0.996946E+09 0.129367E+10 0.468163E+10
           
Annual Sum or Average 0.364334E+11 0.162490E+11 0.201844E+11 0.507979E+11 0.320012E+11
Minimum of Months 0.183208E+10 0.835132E+09 0.996946E+09 0.127350E+10 0.627127E+09
Maximum of Months 0.412525E+10 0.173431E+10 0.239094E+10 0.750882E+10 0.578864E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.708772E+10 0.494154E+10 0.214619E+10 0.766188E+10 0.830407E+10
February 0.597503E+10 0.400523E+10 0.196980E+10 0.710428E+10 0.644972E+10
March 0.594932E+10 0.310043E+10 0.284888E+10 0.770635E+10 0.500094E+10
April 0.431191E+10 0.140362E+10 0.290829E+10 0.629977E+10 0.400259E+10
May 0.359998E+10 0.418415E+09 0.318156E+10 0.564362E+10 0.270602E+10
June 0.322118E+10 0.179246E+09 0.304194E+10 0.614026E+10 0.164980E+10
July 0.336511E+10 0.250922E+09 0.311418E+10 0.676351E+10 0.120220E+10
August 0.401770E+10 0.750520E+09 0.326718E+10 0.819068E+10 0.101515E+10
September 0.427595E+10 0.159043E+10 0.268552E+10 0.728834E+10 0.219485E+10
October 0.640554E+10 0.414951E+10 0.225602E+10 0.927179E+10 0.455084E+10
November 0.666890E+10 0.442537E+10 0.224353E+10 0.856688E+10 0.574650E+10
December 0.698653E+10 0.491508E+10 0.207145E+10 0.810780E+10 0.706689E+10
           
Annual Sum or Average 0.618649E+11 0.301303E+11 0.317346E+11 0.887452E+11 0.498896E+11
Minimum of Months 0.322118E+10 0.179246E+09 0.196980E+10 0.564362E+10 0.101515E+10
Maximum of Months 0.708772E+10 0.494154E+10 0.326718E+10 0.927179E+10 0.830407E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.199295E+10 0.924471E+09 0.106848E+10 0.147464E+10 0.618834E+10
February 0.206649E+10 0.966207E+09 0.110028E+10 0.203411E+10 0.468896E+10
March 0.337222E+10 0.162954E+10 0.174269E+10 0.405608E+10 0.345818E+10
April 0.367131E+10 0.167998E+10 0.199134E+10 0.512744E+10 0.274987E+10
May 0.381277E+10 0.144451E+10 0.236826E+10 0.592211E+10 0.189972E+10
June 0.388029E+10 0.149273E+10 0.238756E+10 0.687168E+10 0.121624E+10
July 0.378200E+10 0.140224E+10 0.237976E+10 0.696323E+10 0.904038E+09
August 0.370582E+10 0.138583E+10 0.231999E+10 0.689167E+10 0.781965E+09
September 0.292184E+10 0.121707E+10 0.170476E+10 0.468926E+10 0.149554E+10
October 0.268978E+10 0.139629E+10 0.129349E+10 0.361130E+10 0.316013E+10
November 0.207739E+10 0.932439E+09 0.114495E+10 0.226575E+10 0.408124E+10
December 0.177096E+10 0.774620E+09 0.996339E+09 0.143061E+10 0.521573E+10
           
Annual Sum or Average 0.357438E+11 0.152459E+11 0.204979E+11 0.513379E+11 0.358400E+11
Minimum of Months 0.177096E+10 0.774620E+09 0.996339E+09 0.143061E+10 0.781965E+09
Maximum of Months 0.388029E+10 0.167998E+10 0.238756E+10 0.696323E+10 0.618834E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.132527E+10 0.00 0.132527E+10 0.212577E+09 0.923491E+10
February 0.132678E+10 0.00 0.132678E+10 0.586628E+09 0.679518E+10
March 0.206230E+10 0.00 0.206230E+10 0.143374E+10 0.461593E+10
April 0.241408E+10 10707142.87 0.240337E+10 0.267271E+10 0.360530E+10
May 0.298344E+10 95215048.85 0.288822E+10 0.413813E+10 0.247965E+10
June 0.317749E+10 0.209789E+09 0.296770E+10 0.578688E+10 0.155563E+10
July 0.309790E+10 0.150591E+09 0.294731E+10 0.599755E+10 0.116610E+10
August 0.275507E+10 30012202.44 0.272506E+10 0.548693E+10 0.967249E+09
September 0.201540E+10 283711.47 0.201511E+10 0.303828E+10 0.198822E+10
October 0.158345E+10 0.00 0.158345E+10 0.147586E+10 0.415041E+10
November 0.137142E+10 0.00 0.137142E+10 0.801605E+09 0.550586E+10
December 0.122512E+10 0.00 0.122512E+10 0.213499E+09 0.728646E+10
           
Annual Sum or Average 0.253377E+11 0.496599E+09 0.248411E+11 0.318444E+11 0.493509E+11
Minimum of Months 0.122512E+10 0.00 0.122512E+10 0.212577E+09 0.967249E+09
Maximum of Months 0.317749E+10 0.209789E+09 0.296770E+10 0.599755E+10 0.923491E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.194029E+10 0.875171E+09 0.106512E+10 0.133093E+10 0.549205E+10
February 0.220938E+10 0.118708E+10 0.102230E+10 0.209931E+10 0.408894E+10
March 0.307748E+10 0.140096E+10 0.167652E+10 0.342528E+10 0.287175E+10
April 0.360142E+10 0.164215E+10 0.195927E+10 0.490009E+10 0.229721E+10
May 0.408645E+10 0.172810E+10 0.235835E+10 0.617167E+10 0.165166E+10
June 0.409437E+10 0.171605E+10 0.237832E+10 0.712107E+10 0.104940E+10
July 0.412525E+10 0.173431E+10 0.239094E+10 0.743994E+10 0.787632E+09
August 0.377324E+10 0.149698E+10 0.227626E+10 0.693257E+10 0.650135E+09
September 0.300105E+10 0.132969E+10 0.167136E+10 0.476939E+10 0.129159E+10
October 0.264549E+10 0.137651E+10 0.126898E+10 0.337563E+10 0.260731E+10
November 0.204686E+10 0.926812E+09 0.112005E+10 0.205963E+10 0.331736E+10
December 0.183208E+10 0.835132E+09 0.996946E+09 0.136265E+10 0.432272E+10
           
Annual Sum or Average 0.364334E+11 0.162490E+11 0.201844E+11 0.509882E+11 0.304278E+11
Minimum of Months 0.183208E+10 0.835132E+09 0.996946E+09 0.133093E+10 0.650135E+09
Maximum of Months 0.412525E+10 0.173431E+10 0.239094E+10 0.743994E+10 0.549205E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.708772E+10 0.494154E+10 0.214619E+10 0.781444E+10 0.780490E+10
February 0.597503E+10 0.400523E+10 0.196980E+10 0.719095E+10 0.609976E+10
March 0.594932E+10 0.310043E+10 0.284888E+10 0.778481E+10 0.469147E+10
April 0.431191E+10 0.140362E+10 0.290829E+10 0.633830E+10 0.381196E+10
May 0.359998E+10 0.418415E+09 0.318156E+10 0.561510E+10 0.265305E+10
June 0.322118E+10 0.179246E+09 0.304194E+10 0.607425E+10 0.165756E+10
July 0.336511E+10 0.250922E+09 0.311418E+10 0.668023E+10 0.122250E+10
August 0.401770E+10 0.750520E+09 0.326718E+10 0.810263E+10 0.104252E+10
September 0.427595E+10 0.159043E+10 0.268552E+10 0.727566E+10 0.211709E+10
October 0.640554E+10 0.414951E+10 0.225602E+10 0.933052E+10 0.424902E+10
November 0.666890E+10 0.442537E+10 0.224353E+10 0.871944E+10 0.529942E+10
December 0.698653E+10 0.491508E+10 0.207145E+10 0.827071E+10 0.650157E+10
           
Annual Sum or Average 0.618649E+11 0.301303E+11 0.317346E+11 0.891971E+11 0.471508E+11
Minimum of Months 0.322118E+10 0.179246E+09 0.196980E+10 0.561510E+10 0.104252E+10
Maximum of Months 0.708772E+10 0.494154E+10 0.326718E+10 0.933052E+10 0.780490E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.199295E+10 0.924471E+09 0.106848E+10 0.151259E+10 0.586978E+10
February 0.206649E+10 0.966207E+09 0.110028E+10 0.205398E+10 0.448654E+10
March 0.337222E+10 0.162954E+10 0.174269E+10 0.407831E+10 0.327057E+10
April 0.367131E+10 0.167998E+10 0.199134E+10 0.514110E+10 0.263563E+10
May 0.381277E+10 0.144451E+10 0.236826E+10 0.589926E+10 0.186661E+10
June 0.388029E+10 0.149273E+10 0.238756E+10 0.682077E+10 0.121805E+10
July 0.378200E+10 0.140224E+10 0.237976E+10 0.690967E+10 0.913304E+09
August 0.370582E+10 0.138583E+10 0.231999E+10 0.683635E+10 0.794507E+09
September 0.292184E+10 0.121707E+10 0.170476E+10 0.468481E+10 0.144554E+10
October 0.268978E+10 0.139629E+10 0.129349E+10 0.363670E+10 0.297486E+10
November 0.207739E+10 0.932439E+09 0.114495E+10 0.232290E+10 0.381215E+10
December 0.177096E+10 0.774620E+09 0.996339E+09 0.146676E+10 0.486854E+10
           
Annual Sum or Average 0.357438E+11 0.152459E+11 0.204979E+11 0.513632E+11 0.341561E+11
Minimum of Months 0.177096E+10 0.774620E+09 0.996339E+09 0.146676E+10 0.794507E+09
Maximum of Months 0.388029E+10 0.167998E+10 0.238756E+10 0.690967E+10 0.586978E+10



Table of Contents

Report: WindowZoneSummaryMonthly

For: BASEMENT

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: CORE_BOTTOM

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: CORE_MID

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: CORE_TOP

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 41.49 4104.23 494.80 0.00 494.80 0.00 0.00
February 172.57 3373.48 548.44 0.00 548.44 0.00 0.00
March 424.29 2134.54 769.98 0.00 769.98 0.00 0.00
April 939.16 1630.91 931.36 4.13 927.23 0.00 0.00
May 1524.73 1006.04 1113.89 35.55 1078.34 0.00 0.00
June 2235.78 617.25 1225.89 80.94 1144.95 0.00 0.00
July 2251.24 427.77 1156.63 56.22 1100.40 0.00 0.00
August 2054.50 342.35 1028.63 11.21 1017.42 0.00 0.00
September 1138.64 881.67 777.55 0.11 777.44 0.00 0.00
October 454.17 1945.71 591.19 0.00 591.19 0.00 0.00
November 179.73 2718.73 529.10 0.00 529.10 0.00 0.00
December 31.71 3541.13 457.41 0.00 457.41 0.00 0.00
               
Annual Sum or Average 958.57 1886.22 803.46 15.75 787.71 0.00 0.00
Minimum of Months 31.71 342.35 457.41 0.00 457.41 0.00 0.00
Maximum of Months 2251.24 4104.23 1225.89 80.94 1144.95 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 437.08 2426.63 724.43 326.75 397.67 0.00 0.00
February 810.26 1979.66 913.27 490.69 422.58 0.00 0.00
March 1230.74 1247.21 1149.00 523.06 625.94 0.00 0.00
April 1879.87 967.08 1389.44 633.55 755.89 0.00 0.00
May 2328.28 646.36 1525.71 645.20 880.51 0.00 0.00
June 2788.36 392.72 1579.62 662.06 917.56 0.00 0.00
July 2828.27 259.30 1540.20 647.52 892.68 0.00 0.00
August 2639.83 188.92 1408.77 558.91 849.86 0.00 0.00
September 1844.82 547.45 1157.82 513.00 644.82 0.00 0.00
October 1219.11 1151.48 987.72 513.93 473.78 0.00 0.00
November 696.04 1562.24 789.69 357.57 432.12 0.00 0.00
December 437.16 2024.28 684.02 311.80 372.22 0.00 0.00
               
Annual Sum or Average 1599.16 1111.74 1155.30 515.25 640.05 0.00 0.00
Minimum of Months 437.08 188.92 684.02 311.80 372.22 0.00 0.00
Maximum of Months 2828.27 2426.63 1579.62 662.06 917.56 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 2848.64 3287.43 2646.26 1844.96 801.30 0.00 0.00
February 2929.78 2845.53 2469.85 1655.61 814.24 0.00 0.00
March 2884.90 1980.24 2221.23 1157.57 1063.66 0.00 0.00
April 2425.42 1629.43 1663.55 541.52 1122.03 0.00 0.00
May 2104.10 1054.21 1344.08 156.22 1187.86 0.00 0.00
June 2354.39 657.56 1242.75 69.15 1173.59 0.00 0.00
July 2511.46 448.62 1256.39 93.68 1162.71 0.00 0.00
August 3051.25 366.36 1500.04 280.21 1219.83 0.00 0.00
September 2819.44 885.66 1649.68 613.59 1036.08 0.00 0.00
October 3478.11 1796.12 2391.56 1549.26 842.31 0.00 0.00
November 3299.89 2359.19 2572.89 1707.33 865.56 0.00 0.00
December 3004.53 2881.68 2608.48 1835.09 773.40 0.00 0.00
               
Annual Sum or Average 2809.26 1676.40 1961.73 955.43 1006.30 0.00 0.00
Minimum of Months 2104.10 366.36 1242.75 69.15 773.40 0.00 0.00
Maximum of Months 3478.11 3287.43 2646.26 1844.96 1219.83 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 507.12 2634.73 744.09 345.16 398.93 0.00 0.00
February 780.35 2284.93 854.21 399.39 454.81 0.00 0.00
March 1440.82 1569.57 1259.05 608.40 650.65 0.00 0.00
April 1897.67 1274.69 1416.41 648.14 768.27 0.00 0.00
May 2185.79 784.08 1423.53 539.32 884.21 0.00 0.00
June 2619.27 531.98 1497.03 575.90 921.13 0.00 0.00
July 2550.61 394.38 1412.04 523.54 888.50 0.00 0.00
August 2513.94 356.70 1383.60 517.41 866.19 0.00 0.00
September 1778.10 667.10 1127.26 469.55 657.70 0.00 0.00
October 1294.74 1419.83 1004.25 521.32 482.93 0.00 0.00
November 787.67 1947.57 801.47 359.74 441.73 0.00 0.00
December 464.03 2510.30 661.20 289.21 371.99 0.00 0.00
               
Annual Sum or Average 1572.60 1359.93 1133.43 483.45 649.99 0.00 0.00
Minimum of Months 464.03 356.70 661.20 289.21 371.99 0.00 0.00
Maximum of Months 2619.27 2634.73 1497.03 648.14 921.13 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 67.62 3618.53 494.80 0.00 494.80 0.00 0.00
February 226.63 2948.55 548.44 0.00 548.44 0.00 0.00
March 505.89 1849.95 769.98 0.00 769.98 0.00 0.00
April 1011.13 1463.35 931.36 4.13 927.23 0.00 0.00
May 1554.53 941.58 1113.89 35.55 1078.34 0.00 0.00
June 2259.93 593.62 1225.88 80.94 1144.95 0.00 0.00
July 2273.74 424.86 1156.62 56.22 1100.40 0.00 0.00
August 2082.17 349.03 1028.63 11.21 1017.42 0.00 0.00
September 1172.59 797.91 777.54 0.11 777.43 0.00 0.00
October 521.93 1678.93 591.19 0.00 591.19 0.00 0.00
November 265.18 2317.87 529.10 0.00 529.10 0.00 0.00
December 65.86 2940.57 457.41 0.00 457.41 0.00 0.00
               
Annual Sum or Average 1005.02 1653.83 803.45 15.75 787.71 0.00 0.00
Minimum of Months 65.86 349.03 457.41 0.00 457.41 0.00 0.00
Maximum of Months 2273.74 3618.53 1225.88 80.94 1144.95 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 475.47 2161.23 724.42 326.75 397.67 0.00 0.00
February 846.25 1775.69 913.27 490.69 422.58 0.00 0.00
March 1254.53 1138.15 1149.00 523.06 625.94 0.00 0.00
April 1882.06 921.40 1389.44 633.55 755.89 0.00 0.00
May 2316.15 621.07 1525.70 645.20 880.51 0.00 0.00
June 2769.83 397.90 1579.62 662.06 917.56 0.00 0.00
July 2803.47 286.61 1540.19 647.52 892.67 0.00 0.00
August 2613.71 234.14 1408.77 558.91 849.86 0.00 0.00
September 1845.26 511.97 1157.81 513.00 644.82 0.00 0.00
October 1240.08 1040.64 987.71 513.93 473.78 0.00 0.00
November 751.69 1386.82 789.68 357.57 432.12 0.00 0.00
December 483.00 1747.92 684.02 311.80 372.22 0.00 0.00
               
Annual Sum or Average 1610.79 1014.75 1155.29 515.25 640.04 0.00 0.00
Minimum of Months 475.47 234.14 684.02 311.80 372.22 0.00 0.00
Maximum of Months 2803.47 2161.23 1579.62 662.06 917.56 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 2860.62 3100.38 2646.25 1844.96 801.29 0.00 0.00
February 2936.62 2666.05 2469.84 1655.60 814.24 0.00 0.00
March 2877.22 1867.14 2221.22 1157.57 1063.65 0.00 0.00
April 2430.47 1544.21 1663.55 541.52 1122.03 0.00 0.00
May 2107.09 1010.31 1344.08 156.22 1187.86 0.00 0.00
June 2368.93 636.50 1242.74 69.15 1173.59 0.00 0.00
July 2525.20 448.85 1256.39 93.68 1162.70 0.00 0.00
August 3058.05 379.01 1500.04 280.21 1219.82 0.00 0.00
September 2811.86 846.78 1649.67 613.59 1036.08 0.00 0.00
October 3461.69 1699.09 2391.55 1549.25 842.30 0.00 0.00
November 3305.13 2217.01 2572.88 1707.32 865.56 0.00 0.00
December 3027.11 2638.48 2608.47 1835.08 773.39 0.00 0.00
               
Annual Sum or Average 2814.09 1581.99 1961.72 955.43 1006.30 0.00 0.00
Minimum of Months 2107.09 379.01 1242.74 69.15 773.39 0.00 0.00
Maximum of Months 3461.69 3100.38 2646.25 1844.96 1219.82 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 550.57 2310.46 744.08 345.16 398.93 0.00 0.00
February 840.82 1938.23 854.20 399.39 454.81 0.00 0.00
March 1514.37 1291.14 1259.04 608.40 650.65 0.00 0.00
April 1978.18 1060.91 1416.40 648.14 768.26 0.00 0.00
May 2211.06 709.27 1423.53 539.32 884.21 0.00 0.00
June 2651.11 469.23 1497.02 575.90 921.13 0.00 0.00
July 2599.77 337.53 1412.04 523.54 888.50 0.00 0.00
August 2573.06 291.95 1383.59 517.41 866.19 0.00 0.00
September 1809.13 576.98 1127.25 469.55 657.70 0.00 0.00
October 1348.30 1179.86 1004.25 521.31 482.93 0.00 0.00
November 874.13 1574.55 801.46 359.74 441.72 0.00 0.00
December 534.13 1947.33 661.20 289.21 371.99 0.00 0.00
               
Annual Sum or Average 1627.91 1136.48 1133.43 483.44 649.98 0.00 0.00
Minimum of Months 534.13 291.95 661.20 289.21 371.99 0.00 0.00
Maximum of Months 2651.11 2310.46 1497.02 648.14 921.13 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 79.37 3447.92 494.80 0.00 494.80 0.00 0.00
February 242.49 2808.86 548.44 0.00 548.44 0.00 0.00
March 535.30 1723.39 769.98 0.00 769.98 0.00 0.00
April 1031.14 1390.93 931.36 4.13 927.23 0.00 0.00
May 1545.00 925.80 1113.89 35.55 1078.34 0.00 0.00
June 2232.59 600.17 1225.88 80.94 1144.95 0.00 0.00
July 2239.23 435.37 1156.62 56.22 1100.40 0.00 0.00
August 2048.58 361.13 1028.63 11.21 1017.42 0.00 0.00
September 1172.18 767.06 777.54 0.11 777.43 0.00 0.00
October 551.02 1549.59 591.19 0.00 591.19 0.00 0.00
November 309.26 2124.17 529.10 0.00 529.10 0.00 0.00
December 79.71 2720.45 457.41 0.00 457.41 0.00 0.00
               
Annual Sum or Average 1009.78 1564.91 803.45 15.75 787.71 0.00 0.00
Minimum of Months 79.37 361.13 457.41 0.00 457.41 0.00 0.00
Maximum of Months 2239.23 3447.92 1225.88 80.94 1144.95 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 496.91 2050.50 724.42 326.75 397.67 0.00 0.00
February 867.77 1690.21 913.27 490.69 422.58 0.00 0.00
March 1278.85 1072.19 1149.00 523.06 625.94 0.00 0.00
April 1890.47 886.27 1389.44 633.55 755.89 0.00 0.00
May 2304.24 616.66 1525.70 645.20 880.51 0.00 0.00
June 2747.33 404.86 1579.62 662.06 917.56 0.00 0.00
July 2777.75 294.07 1540.19 647.52 892.67 0.00 0.00
August 2588.32 242.73 1408.77 558.91 849.86 0.00 0.00
September 1840.04 498.30 1157.81 513.00 644.82 0.00 0.00
October 1260.32 973.46 987.71 513.93 473.78 0.00 0.00
November 794.61 1279.85 789.68 357.57 432.12 0.00 0.00
December 508.76 1613.92 684.02 311.80 372.22 0.00 0.00
               
Annual Sum or Average 1616.82 964.86 1155.29 515.25 640.04 0.00 0.00
Minimum of Months 496.91 242.73 684.02 311.80 372.22 0.00 0.00
Maximum of Months 2777.75 2050.50 1579.62 662.06 917.56 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 2917.58 2914.02 2646.25 1844.96 801.29 0.00 0.00
February 2972.45 2521.39 2469.84 1655.60 814.24 0.00 0.00
March 2906.52 1751.59 2221.22 1157.57 1063.65 0.00 0.00
April 2445.33 1470.67 1663.55 541.52 1122.03 0.00 0.00
May 2096.44 990.53 1344.08 156.22 1187.86 0.00 0.00
June 2343.46 639.49 1242.74 69.15 1173.59 0.00 0.00
July 2494.11 456.43 1256.39 93.68 1162.70 0.00 0.00
August 3025.18 389.23 1500.04 280.21 1219.82 0.00 0.00
September 2806.97 816.78 1649.67 613.59 1036.08 0.00 0.00
October 3483.62 1586.40 2391.55 1549.25 842.30 0.00 0.00
November 3363.98 2044.53 2572.88 1707.32 865.56 0.00 0.00
December 3087.93 2427.41 2608.47 1835.08 773.39 0.00 0.00
               
Annual Sum or Average 2828.42 1495.14 1961.72 955.43 1006.30 0.00 0.00
Minimum of Months 2096.44 389.23 1242.74 69.15 773.39 0.00 0.00
Maximum of Months 3483.62 2914.02 2646.25 1844.96 1219.82 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 564.74 2191.53 744.08 345.16 398.93 0.00 0.00
February 849.03 1854.56 854.20 399.39 454.81 0.00 0.00
March 1522.66 1221.09 1259.04 608.40 650.65 0.00 0.00
April 1983.45 1016.83 1416.40 648.14 768.26 0.00 0.00
May 2202.53 696.91 1423.53 539.32 884.21 0.00 0.00
June 2631.47 469.93 1497.02 575.90 921.13 0.00 0.00
July 2579.77 340.99 1412.04 523.54 888.50 0.00 0.00
August 2552.40 296.63 1383.59 517.41 866.19 0.00 0.00
September 1807.41 557.69 1127.25 469.55 657.70 0.00 0.00
October 1357.79 1110.68 1004.25 521.31 482.93 0.00 0.00
November 896.18 1470.74 801.46 359.74 441.72 0.00 0.00
December 547.63 1817.71 661.20 289.21 371.99 0.00 0.00
               
Annual Sum or Average 1628.72 1083.08 1133.43 483.44 649.98 0.00 0.00
Minimum of Months 547.63 296.63 661.20 289.21 371.99 0.00 0.00
Maximum of Months 2631.47 2191.53 1497.02 648.14 921.13 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: GROUNDFLOOR_PLENUM

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: MIDFLOOR_PLENUM

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: TOPFLOOR_PLENUM

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: DATACENTER_MID_ZN_6

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: BASEMENT

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: CORE_BOTTOM

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: CORE_MID

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: CORE_TOP

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.111138E+09 0.109928E+11 0.132528E+10 0.00 0.132528E+10 0.00 0.00
February 0.417476E+09 0.816113E+10 0.132678E+10 0.00 0.132678E+10 0.00 0.00
March 0.113641E+10 0.571714E+10 0.206231E+10 0.00 0.206231E+10 0.00 0.00
April 0.243430E+10 0.422733E+10 0.241409E+10 10707180.89 0.240338E+10 0.00 0.00
May 0.408384E+10 0.269457E+10 0.298345E+10 95215386.96 0.288824E+10 0.00 0.00
June 0.579515E+10 0.159992E+10 0.317750E+10 0.209790E+09 0.296771E+10 0.00 0.00
July 0.602971E+10 0.114574E+10 0.309791E+10 0.150592E+09 0.294732E+10 0.00 0.00
August 0.550278E+10 0.916951E+09 0.275508E+10 30012309.02 0.272507E+10 0.00 0.00
September 0.295135E+10 0.228528E+10 0.201540E+10 283712.48 0.201512E+10 0.00 0.00
October 0.121645E+10 0.521138E+10 0.158346E+10 0.00 0.158346E+10 0.00 0.00
November 0.465863E+09 0.704695E+10 0.137142E+10 0.00 0.137142E+10 0.00 0.00
December 84927639.70 0.948456E+10 0.122512E+10 0.00 0.122512E+10 0.00 0.00
               
Annual Sum or Average 0.302294E+11 0.594837E+11 0.253378E+11 0.496600E+09 0.248412E+11 0.00 0.00
Minimum of Months 84927639.70 0.916951E+09 0.122512E+10 0.00 0.122512E+10 0.00 0.00
Maximum of Months 0.602971E+10 0.109928E+11 0.317750E+10 0.209790E+09 0.296771E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.117067E+10 0.649948E+10 0.194030E+10 0.875174E+09 0.106513E+10 0.00 0.00
February 0.196017E+10 0.478920E+10 0.220939E+10 0.118709E+10 0.102230E+10 0.00 0.00
March 0.329641E+10 0.334053E+10 0.307749E+10 0.140096E+10 0.167653E+10 0.00 0.00
April 0.487262E+10 0.250667E+10 0.360143E+10 0.164216E+10 0.195927E+10 0.00 0.00
May 0.623607E+10 0.173121E+10 0.408646E+10 0.172811E+10 0.235836E+10 0.00 0.00
June 0.722743E+10 0.101794E+10 0.409439E+10 0.171606E+10 0.237833E+10 0.00 0.00
July 0.757524E+10 0.694522E+09 0.412527E+10 0.173432E+10 0.239094E+10 0.00 0.00
August 0.707052E+10 0.505993E+09 0.377325E+10 0.149698E+10 0.227627E+10 0.00 0.00
September 0.478177E+10 0.141898E+10 0.300106E+10 0.132969E+10 0.167137E+10 0.00 0.00
October 0.326527E+10 0.308412E+10 0.264550E+10 0.137652E+10 0.126898E+10 0.00 0.00
November 0.180414E+10 0.404933E+10 0.204687E+10 0.926816E+09 0.112006E+10 0.00 0.00
December 0.117089E+10 0.542182E+10 0.183209E+10 0.835135E+09 0.996950E+09 0.00 0.00
               
Annual Sum or Average 0.504312E+11 0.350598E+11 0.364335E+11 0.162490E+11 0.201845E+11 0.00 0.00
Minimum of Months 0.117067E+10 0.505993E+09 0.183209E+10 0.835135E+09 0.996950E+09 0.00 0.00
Maximum of Months 0.757524E+10 0.649948E+10 0.412527E+10 0.173432E+10 0.239094E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.762978E+10 0.880504E+10 0.708775E+10 0.494155E+10 0.214619E+10 0.00 0.00
February 0.708772E+10 0.688390E+10 0.597506E+10 0.400524E+10 0.196981E+10 0.00 0.00
March 0.772691E+10 0.530386E+10 0.594934E+10 0.310044E+10 0.284889E+10 0.00 0.00
April 0.628670E+10 0.422348E+10 0.431193E+10 0.140362E+10 0.290830E+10 0.00 0.00
May 0.563563E+10 0.282360E+10 0.359999E+10 0.418416E+09 0.318157E+10 0.00 0.00
June 0.610258E+10 0.170441E+10 0.322120E+10 0.179247E+09 0.304195E+10 0.00 0.00
July 0.672670E+10 0.120159E+10 0.336512E+10 0.250922E+09 0.311420E+10 0.00 0.00
August 0.817248E+10 0.981249E+09 0.401771E+10 0.750523E+09 0.326719E+10 0.00 0.00
September 0.730799E+10 0.229564E+10 0.427596E+10 0.159044E+10 0.268553E+10 0.00 0.00
October 0.931578E+10 0.481072E+10 0.640556E+10 0.414953E+10 0.225603E+10 0.00 0.00
November 0.855332E+10 0.611502E+10 0.666893E+10 0.442539E+10 0.224354E+10 0.00 0.00
December 0.804733E+10 0.771829E+10 0.698656E+10 0.491510E+10 0.207146E+10 0.00 0.00
               
Annual Sum or Average 0.885929E+11 0.528668E+11 0.618651E+11 0.301304E+11 0.317347E+11 0.00 0.00
Minimum of Months 0.563563E+10 0.981249E+09 0.322120E+10 0.179247E+09 0.196981E+10 0.00 0.00
Maximum of Months 0.931578E+10 0.880504E+10 0.708775E+10 0.494155E+10 0.326719E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.135827E+10 0.705686E+10 0.199296E+10 0.924475E+09 0.106849E+10 0.00 0.00
February 0.188782E+10 0.552770E+10 0.206649E+10 0.966211E+09 0.110028E+10 0.00 0.00
March 0.385910E+10 0.420394E+10 0.337224E+10 0.162954E+10 0.174270E+10 0.00 0.00
April 0.491877E+10 0.330400E+10 0.367133E+10 0.167999E+10 0.199134E+10 0.00 0.00
May 0.585443E+10 0.210007E+10 0.381279E+10 0.144452E+10 0.236827E+10 0.00 0.00
June 0.678914E+10 0.137888E+10 0.388030E+10 0.149273E+10 0.238757E+10 0.00 0.00
July 0.683155E+10 0.105630E+10 0.378201E+10 0.140224E+10 0.237977E+10 0.00 0.00
August 0.673333E+10 0.955386E+09 0.370583E+10 0.138584E+10 0.232000E+10 0.00 0.00
September 0.460885E+10 0.172912E+10 0.292185E+10 0.121708E+10 0.170477E+10 0.00 0.00
October 0.346782E+10 0.380288E+10 0.268979E+10 0.139629E+10 0.129349E+10 0.00 0.00
November 0.204163E+10 0.504811E+10 0.207740E+10 0.932443E+09 0.114495E+10 0.00 0.00
December 0.124286E+10 0.672359E+10 0.177097E+10 0.774623E+09 0.996344E+09 0.00 0.00
               
Annual Sum or Average 0.495936E+11 0.428868E+11 0.357440E+11 0.152460E+11 0.204980E+11 0.00 0.00
Minimum of Months 0.124286E+10 0.955386E+09 0.177097E+10 0.774623E+09 0.996344E+09 0.00 0.00
Maximum of Months 0.683155E+10 0.705686E+10 0.388030E+10 0.167999E+10 0.238757E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.181104E+09 0.969187E+10 0.132527E+10 0.00 0.132527E+10 0.00 0.00
February 0.548263E+09 0.713312E+10 0.132678E+10 0.00 0.132678E+10 0.00 0.00
March 0.135498E+10 0.495491E+10 0.206230E+10 0.00 0.206230E+10 0.00 0.00
April 0.262085E+10 0.379300E+10 0.241408E+10 10707142.87 0.240337E+10 0.00 0.00
May 0.416365E+10 0.252193E+10 0.298344E+10 95215048.85 0.288822E+10 0.00 0.00
June 0.585773E+10 0.153865E+10 0.317749E+10 0.209789E+09 0.296770E+10 0.00 0.00
July 0.608999E+10 0.113796E+10 0.309790E+10 0.150591E+09 0.294731E+10 0.00 0.00
August 0.557687E+10 0.934833E+09 0.275507E+10 30012202.44 0.272506E+10 0.00 0.00
September 0.303936E+10 0.206818E+10 0.201540E+10 283711.47 0.201511E+10 0.00 0.00
October 0.139793E+10 0.449683E+10 0.158345E+10 0.00 0.158345E+10 0.00 0.00
November 0.687335E+09 0.600792E+10 0.137142E+10 0.00 0.137142E+10 0.00 0.00
December 0.176393E+09 0.787604E+10 0.122512E+10 0.00 0.122512E+10 0.00 0.00
               
Annual Sum or Average 0.316945E+11 0.521552E+11 0.253377E+11 0.496599E+09 0.248411E+11 0.00 0.00
Minimum of Months 0.176393E+09 0.934833E+09 0.122512E+10 0.00 0.122512E+10 0.00 0.00
Maximum of Months 0.608999E+10 0.969187E+10 0.317749E+10 0.209789E+09 0.296770E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.127350E+10 0.578864E+10 0.194029E+10 0.875171E+09 0.106512E+10 0.00 0.00
February 0.204724E+10 0.429575E+10 0.220938E+10 0.118708E+10 0.102230E+10 0.00 0.00
March 0.336012E+10 0.304843E+10 0.307748E+10 0.140096E+10 0.167652E+10 0.00 0.00
April 0.487829E+10 0.238827E+10 0.360142E+10 0.164215E+10 0.195927E+10 0.00 0.00
May 0.620357E+10 0.166347E+10 0.408645E+10 0.172810E+10 0.235835E+10 0.00 0.00
June 0.717939E+10 0.103134E+10 0.409437E+10 0.171605E+10 0.237832E+10 0.00 0.00
July 0.750882E+10 0.767652E+09 0.412525E+10 0.173431E+10 0.239094E+10 0.00 0.00
August 0.700055E+10 0.627127E+09 0.377324E+10 0.149698E+10 0.227626E+10 0.00 0.00
September 0.478292E+10 0.132704E+10 0.300105E+10 0.132969E+10 0.167136E+10 0.00 0.00
October 0.332144E+10 0.278725E+10 0.264549E+10 0.137651E+10 0.126898E+10 0.00 0.00
November 0.194838E+10 0.359463E+10 0.204686E+10 0.926812E+09 0.112005E+10 0.00 0.00
December 0.129367E+10 0.468163E+10 0.183208E+10 0.835132E+09 0.996946E+09 0.00 0.00
               
Annual Sum or Average 0.507979E+11 0.320012E+11 0.364334E+11 0.162490E+11 0.201844E+11 0.00 0.00
Minimum of Months 0.127350E+10 0.627127E+09 0.183208E+10 0.835132E+09 0.996946E+09 0.00 0.00
Maximum of Months 0.750882E+10 0.578864E+10 0.412525E+10 0.173431E+10 0.239094E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.766188E+10 0.830407E+10 0.708772E+10 0.494154E+10 0.214619E+10 0.00 0.00
February 0.710428E+10 0.644972E+10 0.597503E+10 0.400523E+10 0.196980E+10 0.00 0.00
March 0.770635E+10 0.500094E+10 0.594932E+10 0.310043E+10 0.284888E+10 0.00 0.00
April 0.629977E+10 0.400259E+10 0.431191E+10 0.140362E+10 0.290829E+10 0.00 0.00
May 0.564362E+10 0.270602E+10 0.359998E+10 0.418415E+09 0.318156E+10 0.00 0.00
June 0.614026E+10 0.164980E+10 0.322118E+10 0.179246E+09 0.304194E+10 0.00 0.00
July 0.676351E+10 0.120220E+10 0.336511E+10 0.250922E+09 0.311418E+10 0.00 0.00
August 0.819068E+10 0.101515E+10 0.401770E+10 0.750520E+09 0.326718E+10 0.00 0.00
September 0.728834E+10 0.219485E+10 0.427595E+10 0.159043E+10 0.268552E+10 0.00 0.00
October 0.927179E+10 0.455084E+10 0.640554E+10 0.414951E+10 0.225602E+10 0.00 0.00
November 0.856688E+10 0.574650E+10 0.666890E+10 0.442537E+10 0.224353E+10 0.00 0.00
December 0.810780E+10 0.706689E+10 0.698653E+10 0.491508E+10 0.207145E+10 0.00 0.00
               
Annual Sum or Average 0.887452E+11 0.498896E+11 0.618649E+11 0.301303E+11 0.317346E+11 0.00 0.00
Minimum of Months 0.564362E+10 0.101515E+10 0.322118E+10 0.179246E+09 0.196980E+10 0.00 0.00
Maximum of Months 0.927179E+10 0.830407E+10 0.708772E+10 0.494154E+10 0.326718E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.147464E+10 0.618834E+10 0.199295E+10 0.924471E+09 0.106848E+10 0.00 0.00
February 0.203411E+10 0.468896E+10 0.206649E+10 0.966207E+09 0.110028E+10 0.00 0.00
March 0.405608E+10 0.345818E+10 0.337222E+10 0.162954E+10 0.174269E+10 0.00 0.00
April 0.512744E+10 0.274987E+10 0.367131E+10 0.167998E+10 0.199134E+10 0.00 0.00
May 0.592211E+10 0.189972E+10 0.381277E+10 0.144451E+10 0.236826E+10 0.00 0.00
June 0.687168E+10 0.121624E+10 0.388029E+10 0.149273E+10 0.238756E+10 0.00 0.00
July 0.696323E+10 0.904038E+09 0.378200E+10 0.140224E+10 0.237976E+10 0.00 0.00
August 0.689167E+10 0.781965E+09 0.370582E+10 0.138583E+10 0.231999E+10 0.00 0.00
September 0.468926E+10 0.149554E+10 0.292184E+10 0.121707E+10 0.170476E+10 0.00 0.00
October 0.361130E+10 0.316013E+10 0.268978E+10 0.139629E+10 0.129349E+10 0.00 0.00
November 0.226575E+10 0.408124E+10 0.207739E+10 0.932439E+09 0.114495E+10 0.00 0.00
December 0.143061E+10 0.521573E+10 0.177096E+10 0.774620E+09 0.996339E+09 0.00 0.00
               
Annual Sum or Average 0.513379E+11 0.358400E+11 0.357438E+11 0.152459E+11 0.204979E+11 0.00 0.00
Minimum of Months 0.143061E+10 0.781965E+09 0.177096E+10 0.774620E+09 0.996339E+09 0.00 0.00
Maximum of Months 0.696323E+10 0.618834E+10 0.388029E+10 0.167998E+10 0.238756E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.212577E+09 0.923491E+10 0.132527E+10 0.00 0.132527E+10 0.00 0.00
February 0.586628E+09 0.679518E+10 0.132678E+10 0.00 0.132678E+10 0.00 0.00
March 0.143374E+10 0.461593E+10 0.206230E+10 0.00 0.206230E+10 0.00 0.00
April 0.267271E+10 0.360530E+10 0.241408E+10 10707142.87 0.240337E+10 0.00 0.00
May 0.413813E+10 0.247965E+10 0.298344E+10 95215048.85 0.288822E+10 0.00 0.00
June 0.578688E+10 0.155563E+10 0.317749E+10 0.209789E+09 0.296770E+10 0.00 0.00
July 0.599755E+10 0.116610E+10 0.309790E+10 0.150591E+09 0.294731E+10 0.00 0.00
August 0.548693E+10 0.967249E+09 0.275507E+10 30012202.44 0.272506E+10 0.00 0.00
September 0.303828E+10 0.198822E+10 0.201540E+10 283711.47 0.201511E+10 0.00 0.00
October 0.147586E+10 0.415041E+10 0.158345E+10 0.00 0.158345E+10 0.00 0.00
November 0.801605E+09 0.550586E+10 0.137142E+10 0.00 0.137142E+10 0.00 0.00
December 0.213499E+09 0.728646E+10 0.122512E+10 0.00 0.122512E+10 0.00 0.00
               
Annual Sum or Average 0.318444E+11 0.493509E+11 0.253377E+11 0.496599E+09 0.248411E+11 0.00 0.00
Minimum of Months 0.212577E+09 0.967249E+09 0.122512E+10 0.00 0.122512E+10 0.00 0.00
Maximum of Months 0.599755E+10 0.923491E+10 0.317749E+10 0.209789E+09 0.296770E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.133093E+10 0.549205E+10 0.194029E+10 0.875171E+09 0.106512E+10 0.00 0.00
February 0.209931E+10 0.408894E+10 0.220938E+10 0.118708E+10 0.102230E+10 0.00 0.00
March 0.342528E+10 0.287175E+10 0.307748E+10 0.140096E+10 0.167652E+10 0.00 0.00
April 0.490009E+10 0.229721E+10 0.360142E+10 0.164215E+10 0.195927E+10 0.00 0.00
May 0.617167E+10 0.165166E+10 0.408645E+10 0.172810E+10 0.235835E+10 0.00 0.00
June 0.712107E+10 0.104940E+10 0.409437E+10 0.171605E+10 0.237832E+10 0.00 0.00
July 0.743994E+10 0.787632E+09 0.412525E+10 0.173431E+10 0.239094E+10 0.00 0.00
August 0.693257E+10 0.650135E+09 0.377324E+10 0.149698E+10 0.227626E+10 0.00 0.00
September 0.476939E+10 0.129159E+10 0.300105E+10 0.132969E+10 0.167136E+10 0.00 0.00
October 0.337563E+10 0.260731E+10 0.264549E+10 0.137651E+10 0.126898E+10 0.00 0.00
November 0.205963E+10 0.331736E+10 0.204686E+10 0.926812E+09 0.112005E+10 0.00 0.00
December 0.136265E+10 0.432272E+10 0.183208E+10 0.835132E+09 0.996946E+09 0.00 0.00
               
Annual Sum or Average 0.509882E+11 0.304278E+11 0.364334E+11 0.162490E+11 0.201844E+11 0.00 0.00
Minimum of Months 0.133093E+10 0.650135E+09 0.183208E+10 0.835132E+09 0.996946E+09 0.00 0.00
Maximum of Months 0.743994E+10 0.549205E+10 0.412525E+10 0.173431E+10 0.239094E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.781444E+10 0.780490E+10 0.708772E+10 0.494154E+10 0.214619E+10 0.00 0.00
February 0.719095E+10 0.609976E+10 0.597503E+10 0.400523E+10 0.196980E+10 0.00 0.00
March 0.778481E+10 0.469147E+10 0.594932E+10 0.310043E+10 0.284888E+10 0.00 0.00
April 0.633830E+10 0.381196E+10 0.431191E+10 0.140362E+10 0.290829E+10 0.00 0.00
May 0.561510E+10 0.265305E+10 0.359998E+10 0.418415E+09 0.318156E+10 0.00 0.00
June 0.607425E+10 0.165756E+10 0.322118E+10 0.179246E+09 0.304194E+10 0.00 0.00
July 0.668023E+10 0.122250E+10 0.336511E+10 0.250922E+09 0.311418E+10 0.00 0.00
August 0.810263E+10 0.104252E+10 0.401770E+10 0.750520E+09 0.326718E+10 0.00 0.00
September 0.727566E+10 0.211709E+10 0.427595E+10 0.159043E+10 0.268552E+10 0.00 0.00
October 0.933052E+10 0.424902E+10 0.640554E+10 0.414951E+10 0.225602E+10 0.00 0.00
November 0.871944E+10 0.529942E+10 0.666890E+10 0.442537E+10 0.224353E+10 0.00 0.00
December 0.827071E+10 0.650157E+10 0.698653E+10 0.491508E+10 0.207145E+10 0.00 0.00
               
Annual Sum or Average 0.891971E+11 0.471508E+11 0.618649E+11 0.301303E+11 0.317346E+11 0.00 0.00
Minimum of Months 0.561510E+10 0.104252E+10 0.322118E+10 0.179246E+09 0.196980E+10 0.00 0.00
Maximum of Months 0.933052E+10 0.780490E+10 0.708772E+10 0.494154E+10 0.326718E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.151259E+10 0.586978E+10 0.199295E+10 0.924471E+09 0.106848E+10 0.00 0.00
February 0.205398E+10 0.448654E+10 0.206649E+10 0.966207E+09 0.110028E+10 0.00 0.00
March 0.407831E+10 0.327057E+10 0.337222E+10 0.162954E+10 0.174269E+10 0.00 0.00
April 0.514110E+10 0.263563E+10 0.367131E+10 0.167998E+10 0.199134E+10 0.00 0.00
May 0.589926E+10 0.186661E+10 0.381277E+10 0.144451E+10 0.236826E+10 0.00 0.00
June 0.682077E+10 0.121805E+10 0.388029E+10 0.149273E+10 0.238756E+10 0.00 0.00
July 0.690967E+10 0.913304E+09 0.378200E+10 0.140224E+10 0.237976E+10 0.00 0.00
August 0.683635E+10 0.794507E+09 0.370582E+10 0.138583E+10 0.231999E+10 0.00 0.00
September 0.468481E+10 0.144554E+10 0.292184E+10 0.121707E+10 0.170476E+10 0.00 0.00
October 0.363670E+10 0.297486E+10 0.268978E+10 0.139629E+10 0.129349E+10 0.00 0.00
November 0.232290E+10 0.381215E+10 0.207739E+10 0.932439E+09 0.114495E+10 0.00 0.00
December 0.146676E+10 0.486854E+10 0.177096E+10 0.774620E+09 0.996339E+09 0.00 0.00
               
Annual Sum or Average 0.513632E+11 0.341561E+11 0.357438E+11 0.152459E+11 0.204979E+11 0.00 0.00
Minimum of Months 0.146676E+10 0.794507E+09 0.177096E+10 0.774620E+09 0.996339E+09 0.00 0.00
Maximum of Months 0.690967E+10 0.586978E+10 0.388029E+10 0.167998E+10 0.238756E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: GROUNDFLOOR_PLENUM

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: MIDFLOOR_PLENUM

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: TOPFLOOR_PLENUM

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: DATACENTER_MID_ZN_6

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AverageOutdoorConditionsMonthly

For: Environment

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] SITE OUTDOOR AIR WETBULB TEMPERATURE [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] SITE WIND SPEED [m/s] SITE SKY TEMPERATURE [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] SITE RAIN STATUS []
January 3.96 1.39 -3.0 4.56 -7.8 48.74 150.20 0.00
February 7.94 4.18 -1.3 5.19 -4.0 51.84 169.20 0.00
March 13.76 8.97 3.80 4.89 2.25 76.95 193.22 0.00
April 17.21 12.54 8.82 3.95 6.45 95.37 211.82 0.00
May 20.84 16.44 13.69 3.50 11.46 117.34 200.00 0.00
June 24.80 19.35 16.45 3.85 15.08 121.81 213.08 0.00
July 26.06 21.68 19.85 3.24 17.64 119.92 194.46 0.00
August 26.55 22.42 20.72 3.39 18.21 115.12 179.15 0.00
September 22.53 18.74 16.82 3.06 13.44 83.74 156.58 0.02
October 16.03 13.02 10.77 4.05 5.85 53.01 190.38 0.00
November 11.94 8.22 4.17 4.16 0.30 52.20 150.38 0.00
December 7.70 4.64 0.26 4.69 -4.1 44.81 142.03 0.00
                 
Annual Sum or Average 16.65 12.68 9.31 4.04 6.29 81.91 179.25 0.00
Minimum of Months 3.96 1.39 -3.0 3.06 -7.8 44.81 142.03 0.00
Maximum of Months 26.55 22.42 20.72 5.19 18.21 121.81 213.08 0.02



Table of Contents

Report: OutdoorConditionsMaximumDryBulbMonthly

For: Environment

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] SITE WIND SPEED {AT MAX/MIN} [m/s] SITE SKY TEMPERATURE {AT MAX/MIN} [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2]
January 21.10 31-JAN-14:00 12.97 6.70 5.70 12.22 200.50 90.50
February 25.00 26-FEB-14:00 12.75 1.70 4.10 8.15 91.50 816.00
March 27.80 30-MAR-13:00 17.87 12.20 5.70 16.30 231.50 710.50
April 28.90 17-APR-14:20 16.56 8.13 2.03 13.35 125.83 887.67
May 30.60 19-MAY-13:00 18.49 11.70 4.60 15.76 140.00 875.50
June 34.40 06-JUN-14:00 22.39 17.20 8.20 22.13 251.00 561.00
July 36.70 08-JUL-14:00 23.91 18.90 2.10 24.66 274.00 567.00
August 35.00 01-AUG-14:00 23.84 19.40 2.60 26.15 306.00 508.00
September 31.70 07-SEP-15:09 23.05 19.60 4.02 22.55 218.67 591.33
October 30.00 10-OCT-15:00 20.56 16.10 3.60 17.57 97.00 561.00
November 24.40 05-NOV-15:00 17.95 14.40 2.10 14.10 117.50 361.50
December 22.80 12-DEC-14:20 16.78 13.33 5.20 13.35 144.17 433.83
                 
Annual Sum or Average                
Minimum of Months 21.10   12.75 1.70 2.03 8.15 91.50 90.50
Maximum of Months 36.70   23.91 19.60 8.20 26.15 306.00 887.67



Table of Contents

Report: OutdoorConditionsMinimumDryBulbMonthly

For: Environment

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] SITE WIND SPEED {AT MAX/MIN} [m/s] SITE SKY TEMPERATURE {AT MAX/MIN} [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2]
January -6.7 14-JAN-06:10 -7.8 -10.6 4.95 -24.7 0.00 0.00
February -12.8 12-FEB-06:00 -13.8 -18.3 7.20 -30.1 0.00 0.00
March 1.10 19-MAR-06:00 -1.5 -6.1 0.00 -16.2 17.00 290.50
April 0.00 06-APR-04:00 -1.1 -2.8 3.10 -16.5 0.00 0.00
May 7.80 11-MAY-05:00 5.45 2.80 4.10 -7.8 21.50 204.50
June 11.10 10-JUN-04:00 8.73 6.70 0.00 -2.5 0.00 0.00
July 17.20 28-JUL-22:00 16.88 16.70 4.10 14.28 0.00 0.00
August 18.30 25-AUG-05:00 17.20 16.70 3.60 5.13 0.00 0.00
September 11.70 29-SEP-03:00 11.07 10.60 2.60 -2.3 0.00 0.00
October 2.20 26-OCT-04:00 1.95 1.70 3.10 -13.4 0.00 0.00
November -3.3 22-NOV-05:00 -4.0 -5.6 5.20 -20.2 0.00 0.00
December -5.6 18-DEC-07:00 -7.3 -11.7 2.60 -22.7 17.00 320.50
                 
Annual Sum or Average                
Minimum of Months -12.8   -13.8 -18.3 0.00 -30.1 0.00 0.00
Maximum of Months 18.30   17.20 16.70 7.20 14.28 21.50 320.50



Table of Contents

Report: OutdoorConditionsMaximumWetBulbMonthly

For: Environment

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

SITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] SITE WIND SPEED {AT MAX/MIN} [m/s] SITE SKY TEMPERATURE {AT MAX/MIN} [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2]
January 16.51 19-JAN-21:00 18.30 15.60 8.80 15.21 0.00 0.00
February 15.81 18-FEB-15:00 17.20 15.00 5.20 13.91 73.00 1.00
March 18.16 30-MAR-12:30 25.85 13.85 5.45 15.39 323.00 600.00
April 20.01 04-APR-13:00 25.00 17.80 9.30 18.64 307.00 197.50
May 22.34 30-MAY-17:00 27.80 20.00 4.10 21.96 97.50 79.50
June 24.32 23-JUN-11:39 31.13 21.87 4.83 22.98 338.17 565.17
July 25.06 07-JUL-11:00 33.30 22.20 3.60 20.75 116.50 900.00
August 25.13 19-AUG-16:00 30.00 23.30 3.10 23.66 197.00 136.50
September 24.10 09-SEP-10:00 30.60 21.70 2.60 21.27 236.00 482.00
October 23.20 18-OCT-15:00 25.60 22.20 5.70 23.82 159.00 2.00
November 18.88 19-NOV-14:00 24.40 16.10 8.20 13.91 143.00 384.50
December 17.57 13-DEC-10:00 19.40 16.70 4.60 14.47 227.50 77.00
                 
Annual Sum or Average                
Minimum of Months 15.81   17.20 13.85 2.60 13.91 0.00 0.00
Maximum of Months 25.13   33.30 23.30 9.30 23.82 338.17 900.00



Table of Contents

Report: OutdoorConditionsMaximumDewPointMonthly

For: Environment

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

SITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] SITE WIND SPEED {AT MAX/MIN} [m/s] SITE SKY TEMPERATURE {AT MAX/MIN} [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2]
January 15.60 19-JAN-17:00 17.20 16.13 6.70 14.10 0.00 0.00
February 15.00 18-FEB-16:19 17.20 15.81 5.53 13.91 50.33 1.00
March 16.10 31-MAR-10:00 21.70 18.06 13.90 18.64 268.00 8.00
April 17.80 04-APR-09:20 20.77 18.74 7.53 16.79 242.00 111.50
May 20.60 30-MAY-19:00 25.00 21.79 2.60 12.41 0.00 0.00
June 22.80 18-JUN-16:00 28.30 24.23 0.00 24.66 140.50 115.50
July 23.30 26-JUL-09:00 26.10 24.10 3.60 24.66 338.00 251.50
August 23.90 08-AUG-19:00 26.10 24.51 1.50 24.83 0.00 0.00
September 23.30 16-SEP-16:00 25.60 23.89 2.10 22.13 108.00 57.50
October 22.20 18-OCT-14:00 25.00 23.04 4.60 23.32 234.50 2.00
November 17.20 04-NOV-13:00 17.80 17.48 3.60 15.02 276.50 2.50
December 16.70 13-DEC-16:19 17.03 16.82 2.93 14.10 54.00 4.50
                 
Annual Sum or Average                
Minimum of Months 15.00   17.03 15.81 0.00 12.41 0.00 0.00
Maximum of Months 23.90   28.30 24.51 13.90 24.83 338.00 251.50



Table of Contents

Report: OutdoorGroundConditionsMonthly

For: Environment

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

SITE GROUND TEMPERATURE [C] SITE SURFACE GROUND TEMPERATURE [C] SITE DEEP GROUND TEMPERATURE [C] SITE MAINS WATER TEMPERATURE [C] SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] SITE SNOW ON GROUND STATUS []
January 18.00 13.00 16.00 13.74 22.89 0.00
February 18.00 13.00 16.00 13.65 27.55 0.00
March 18.00 13.00 16.00 15.17 38.46 0.00
April 18.00 13.00 16.00 17.98 47.59 0.00
May 18.00 13.00 16.00 21.32 52.44 0.00
June 18.00 13.00 16.00 24.28 55.84 0.00
July 18.00 13.00 16.00 26.07 52.33 0.00
August 18.00 13.00 16.00 26.20 48.31 0.00
September 18.00 13.00 16.00 24.63 36.35 0.00
October 18.00 13.00 16.00 21.78 31.91 0.00
November 18.00 13.00 16.00 18.45 24.33 0.00
December 18.00 13.00 16.00 15.51 20.76 0.00
             
Annual Sum or Average 18.00 13.00 16.00 19.94 38.29 0.00
Minimum of Months 18.00 13.00 16.00 13.65 20.76 0.00
Maximum of Months 18.00 13.00 16.00 26.20 55.84 0.00



Table of Contents

Report: WaterHeaterReportMonthly

For: SWHSYS1 WATER HEATER

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] WATER HEATER BURNER HEATING ENERGY [] WATER HEATER GAS CONSUMPTION [] WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] WATER HEATER LOSS DEMAND ENERGY [] WATER HEATER HEAT LOSS ENERGY [J] WATER HEATER TANK TEMPERATURE [C] WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] WATER HEATER SOURCE ENERGY []
January 0.370227E+11 -0.359921E+11 0.00 0.00 744.00 0.00 -0.103064E+10 58.98 0.00 0.00
February 0.337056E+11 -0.327761E+11 0.00 0.00 672.00 0.00 -929533593.6 58.98 0.00 0.00
March 0.382785E+11 -0.372504E+11 0.00 0.00 744.00 0.00 -0.102811E+10 58.97 0.00 0.00
April 0.326110E+11 -0.316189E+11 0.00 0.00 720.00 0.00 -992028196.4 58.97 0.00 0.00
May 0.320793E+11 -0.310544E+11 0.00 0.00 744.00 0.00 -0.102485E+10 58.98 0.00 0.00
June 0.293159E+11 -0.283256E+11 0.00 0.00 720.00 0.00 -990282606.4 58.97 0.00 0.00
July 0.265558E+11 -0.255378E+11 0.00 0.00 744.00 0.00 -0.101792E+10 58.98 0.00 0.00
August 0.288958E+11 -0.278741E+11 0.00 0.00 744.00 0.00 -0.102174E+10 58.97 0.00 0.00
September 0.275016E+11 -0.265154E+11 0.00 0.00 720.00 0.00 -986138382.1 58.98 0.00 0.00
October 0.306267E+11 -0.296087E+11 0.00 0.00 744.00 0.00 -0.101801E+10 58.97 0.00 0.00
November 0.326200E+11 -0.316343E+11 0.00 0.00 720.00 0.00 -985696876.1 58.98 0.00 0.00
December 0.347711E+11 -0.337498E+11 0.00 0.00 744.00 0.00 -0.102124E+10 58.97 0.00 0.00
                     
Annual Sum or Average 0.383984E+12 -0.371938E+12 0.00 0.00 8760.00 0.00 -0.120462E+11 58.98 0.00 0.00
Minimum of Months 0.265558E+11 -0.372504E+11 0.00 0.00 672.00 0.00 -0.103064E+10 58.97 0.00 0.00
Maximum of Months 0.382785E+11 -0.255378E+11 0.00 0.00 744.00 0.00 -929533593.6 58.98 0.00 0.00



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_BOT_ZN_1_DAYLCTRL

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 290.67 0.51 0.48 01-JAN-09:20 5945.68 33.92 269.33 272.00 1631.30 26.38 200.33 250.33
February 263.00 0.52 0.48 01-FEB-13:39 6968.32 33.91 233.50 247.50 1127.71 21.84 122.33 216.00
March 351.67 0.52 0.48 01-MAR-08:50 1662.73 19.82 69.50 318.67 956.01 21.10 175.33 283.17
April 369.33 0.53 0.48 01-APR-09:39 1383.80 19.41 41.00 325.50 781.56 20.73 172.67 281.17
May 407.00 0.52 0.48 01-MAY-07:49 1260.26 19.56 21.67 360.33 698.97 20.90 218.50 312.50
June 411.67 0.53 0.48 01-JUN-07:19 1175.02 19.29 7.83 361.33 658.94 20.65 201.00 313.33
July 411.00 0.53 0.48 01-JUL-07:40 1236.36 19.46 24.17 364.67 684.23 20.79 227.83 314.67
August 390.50 0.52 0.48 01-AUG-07:30 1501.65 20.09 77.33 350.67 812.40 21.41 266.00 312.50
September 298.50 0.52 0.48 01-SEP-07:40 1595.76 20.20 72.17 308.83 882.31 21.28 179.00 268.83
October 293.50 0.51 0.48 01-OCT-10:39 2842.85 25.09 143.17 292.67 1050.25 20.43 118.50 254.50
November 299.00 0.52 0.48 01-NOV-08:30 5857.41 34.78 286.83 273.33 1154.52 23.39 181.33 248.17
December 285.17 0.50 0.48 01-DEC-07:00 5601.77 34.66 273.00 267.83 1571.12 27.30 215.83 245.00
                         
Annual Sum or Average 4071.00 0.52     2802.11 24.16 1519.50 3743.33 961.60 21.99 2278.67 3300.17
Minimum of Months 263.00 0.50 0.48   1175.02 19.29 7.83 247.50 658.94 20.43 118.50 216.00
Maximum of Months 411.67 0.53 0.48   6968.32 34.78 286.83 364.67 1631.30 27.30 266.00 314.67



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_BOT_ZN_2_DAYLCTRL

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 290.67 0.54 0.48 01-JAN-09:09 1428.07 21.44 82.83 245.17 721.12 21.53 102.17 187.00
February 263.00 0.54 0.48 01-FEB-13:39 1952.98 22.73 75.67 229.50 1033.08 22.66 87.00 181.83
March 351.67 0.52 0.48 01-MAR-08:39 2276.78 22.84 106.83 313.50 889.88 21.91 130.33 271.50
April 369.33 0.52 0.48 01-APR-08:09 2195.61 22.44 97.17 327.50 1173.15 22.94 133.83 291.83
May 407.00 0.51 0.48 01-MAY-07:10 2509.43 23.37 118.83 369.17 1037.43 22.67 152.50 332.33
June 411.67 0.52 0.48 01-JUN-06:30 2541.88 23.46 123.67 371.00 1053.65 22.78 160.50 335.83
July 411.00 0.52 0.48 01-JUL-05:00 2510.50 23.30 115.17 374.83 1060.48 22.75 169.83 334.67
August 390.50 0.52 0.48 01-AUG-06:40 2299.73 23.15 104.17 352.33 1201.99 23.61 189.67 316.83
September 298.50 0.53 0.48 01-SEP-07:10 2161.52 23.06 80.50 306.50 1131.33 23.38 121.50 262.50
October 293.50 0.53 0.48 01-OCT-08:20 2539.48 23.97 101.67 271.17 956.15 22.48 101.00 221.33
November 299.00 0.54 0.48 01-NOV-08:20 1728.05 23.33 103.00 249.67 924.21 23.37 115.67 205.67
December 285.17 0.54 0.48 01-DEC-07:49 1492.52 22.86 86.83 241.50 775.41 22.82 112.50 183.67
                         
Annual Sum or Average 4071.00 0.53     2179.01 23.02 1196.33 3651.83 1008.24 22.75 1576.50 3125.00
Minimum of Months 263.00 0.51 0.48   1428.07 21.44 75.67 229.50 721.12 21.53 87.00 181.83
Maximum of Months 411.67 0.54 0.48   2541.88 23.97 123.67 374.83 1201.99 23.61 189.67 335.83



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_BOT_ZN_3_DAYLCTRL

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 290.67 0.58 0.48 01-JAN-11:20 523.81 16.13 0.00 218.00 314.73 17.67 0.00 105.33
February 263.00 0.58 0.48 01-FEB-13:50 558.57 16.30 0.00 198.17 345.32 17.80 0.00 123.33
March 351.67 0.53 0.48 01-MAR-09:30 710.75 18.00 0.00 303.67 431.04 19.38 2.67 232.50
April 369.33 0.52 0.48 01-APR-10:30 847.07 18.83 0.00 330.83 504.84 20.12 50.50 275.00
May 407.00 0.50 0.48 01-MAY-07:40 1052.86 21.68 62.33 383.33 612.77 22.83 214.50 352.33
June 411.67 0.50 0.48 01-JUN-06:00 1143.00 22.35 118.50 386.83 657.20 22.48 243.33 358.33
July 411.00 0.51 0.48 01-JUL-06:19 1150.78 21.82 105.33 385.83 639.76 22.17 245.67 350.17
August 390.50 0.51 0.48 01-AUG-07:10 1030.15 19.76 4.50 360.33 595.91 21.03 185.17 325.50
September 298.50 0.53 0.48 01-SEP-07:49 787.85 18.64 0.00 303.83 473.72 19.93 27.83 224.67
October 293.50 0.57 0.48 01-OCT-10:50 586.85 16.80 0.00 243.33 373.46 18.33 2.17 159.67
November 299.00 0.58 0.48 01-NOV-09:00 542.20 16.41 0.00 229.33 327.41 17.90 0.00 134.50
December 285.17 0.58 0.48 01-DEC-09:00 506.06 16.23 0.00 210.33 304.60 17.80 0.00 96.67
                         
Annual Sum or Average 4071.00 0.54     822.92 18.91 290.67 3553.83 484.33 20.07 971.83 2738.00
Minimum of Months 263.00 0.50 0.48   506.06 16.13 0.00 198.17 304.60 17.67 0.00 96.67
Maximum of Months 411.67 0.58 0.48   1150.78 22.35 118.50 386.83 657.20 22.83 245.67 358.33



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_BOT_ZN_4_DAYLCTRL

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 290.67 0.54 0.48 01-JAN-10:00 1747.51 23.34 95.33 247.33 960.00 23.36 120.00 197.67
February 263.00 0.55 0.48 01-FEB-13:39 1698.07 22.27 78.17 220.33 885.42 22.34 106.17 172.67
March 351.67 0.52 0.48 01-MAR-11:39 2256.06 23.30 102.50 312.50 1188.61 23.52 150.50 271.33
April 369.33 0.52 0.48 01-APR-10:39 2406.23 21.38 80.50 333.67 1314.25 21.99 124.33 293.33
May 407.00 0.52 0.48 01-MAY-08:30 2419.02 20.10 52.83 366.67 1021.26 20.36 126.00 329.17
June 411.67 0.52 0.48 01-JUN-07:49 2532.90 18.22 1.83 369.67 1079.37 20.30 130.83 334.50
July 411.00 0.52 0.48 01-JUL-07:00 2514.56 20.04 55.00 370.00 1056.82 20.33 141.00 332.17
August 390.50 0.51 0.48 01-AUG-07:00 2476.32 22.12 89.67 355.17 1069.77 20.96 170.00 321.67
September 298.50 0.52 0.48 01-SEP-08:50 2216.99 23.78 92.67 307.50 1158.75 23.93 145.17 260.83
October 293.50 0.54 0.48 01-OCT-10:39 2386.01 23.30 97.67 268.17 909.02 21.86 106.50 217.67
November 299.00 0.54 0.48 01-NOV-09:00 1662.31 23.22 98.83 253.50 863.34 23.27 120.83 205.83
December 285.17 0.54 0.48 01-DEC-09:00 1449.00 22.78 93.33 242.00 762.00 22.86 111.50 184.33
                         
Annual Sum or Average 4071.00 0.53     2195.20 21.78 938.33 3646.50 1035.50 21.93 1552.83 3121.17
Minimum of Months 263.00 0.51 0.48   1449.00 18.22 1.83 220.33 762.00 20.30 106.17 172.67
Maximum of Months 411.67 0.55 0.48   2532.90 23.78 102.50 370.00 1314.25 23.93 170.00 334.50



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_MID_ZN_1_DAYLCTRL

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 290.67 0.51 0.48 01-JAN-09:20 5987.89 33.13 257.50 272.00 1719.11 22.52 103.00 252.17
February 263.00 0.52 0.48 01-FEB-13:39 7010.71 33.23 228.67 247.50 1212.66 17.00 25.83 217.83
March 351.67 0.52 0.48 01-MAR-08:50 1699.03 13.35 6.67 319.67 1026.04 16.70 0.00 287.33
April 369.33 0.52 0.48 01-APR-08:30 1409.68 13.23 0.00 326.67 835.75 16.71 0.00 288.33
May 407.00 0.52 0.48 01-MAY-07:49 1279.31 13.56 0.00 360.67 744.61 16.99 0.00 317.83
June 411.67 0.52 0.48 01-JUN-07:10 1192.90 13.40 0.00 361.67 701.67 16.82 0.00 320.17
July 411.00 0.52 0.48 01-JUL-07:30 1254.18 13.57 0.00 365.67 728.44 16.96 0.00 319.50
August 390.50 0.52 0.48 01-AUG-07:30 1522.25 14.14 0.00 351.17 865.05 17.53 0.00 316.50
September 298.50 0.52 0.48 01-SEP-07:40 1623.15 14.21 6.50 309.17 943.12 17.30 0.00 274.17
October 293.50 0.51 0.48 01-OCT-10:39 2895.94 20.63 117.00 292.83 1137.87 15.80 2.00 258.17
November 299.00 0.51 0.48 01-NOV-08:30 5898.26 34.28 282.83 273.50 1263.72 20.89 81.67 255.00
December 285.17 0.50 0.48 01-DEC-07:00 5641.57 34.04 265.33 268.33 1658.94 23.60 115.67 248.33
                         
Annual Sum or Average 4071.00 0.52     2832.46 19.73 1164.50 3748.83 1027.67 18.05 328.17 3355.33
Minimum of Months 263.00 0.50 0.48   1192.90 13.23 0.00 247.50 701.67 15.80 0.00 217.83
Maximum of Months 411.67 0.52 0.48   7010.71 34.28 282.83 365.67 1719.11 23.60 115.67 320.17



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_MID_ZN_2_DAYLCTRL

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 290.67 0.54 0.48 01-JAN-09:09 1455.35 18.53 71.50 247.67 756.42 19.31 45.83 195.50
February 263.00 0.54 0.48 01-FEB-13:39 1991.77 19.81 71.17 230.67 1079.35 20.39 48.33 187.17
March 351.67 0.52 0.48 01-MAR-08:39 2319.43 19.95 105.50 314.67 938.39 19.33 47.33 276.33
April 369.33 0.52 0.48 01-APR-08:09 2233.24 19.24 92.83 328.50 1227.99 20.42 67.00 297.67
May 407.00 0.51 0.48 01-MAY-07:10 2530.78 19.65 108.33 369.33 1095.76 19.96 57.50 335.83
June 411.67 0.51 0.48 01-JUN-06:30 2576.60 20.44 122.67 371.50 1111.72 20.14 64.00 339.33
July 411.00 0.52 0.48 01-JUL-05:00 2534.57 19.58 105.00 375.17 1118.95 20.07 58.33 337.33
August 390.50 0.51 0.48 01-AUG-06:40 2327.33 20.07 103.33 353.00 1257.67 21.20 73.33 321.50
September 298.50 0.52 0.48 01-SEP-07:10 2205.84 19.97 78.83 307.83 1185.43 20.99 55.83 268.17
October 293.50 0.53 0.48 01-OCT-08:09 2561.91 20.29 90.50 272.67 1006.41 20.07 50.00 229.00
November 299.00 0.54 0.48 01-NOV-08:20 1755.94 20.64 97.00 251.17 961.50 21.41 71.33 212.00
December 285.17 0.53 0.48 01-DEC-07:49 1490.99 19.14 73.00 242.67 811.28 20.79 57.17 190.33
                         
Annual Sum or Average 4071.00 0.52     2208.10 19.79 1119.67 3664.83 1058.70 20.33 696.00 3190.17
Minimum of Months 263.00 0.51 0.48   1455.35 18.53 71.17 230.67 756.42 19.31 45.83 187.17
Maximum of Months 411.67 0.54 0.48   2576.60 20.64 122.67 375.17 1257.67 21.41 73.33 339.33



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_MID_ZN_3_DAYLCTRL

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 290.67 0.57 0.48 01-JAN-11:09 532.34 10.01 0.00 220.17 335.04 13.66 0.00 128.00
February 263.00 0.58 0.48 01-FEB-13:39 568.96 10.34 0.00 199.83 368.09 13.95 0.00 136.00
March 351.67 0.53 0.48 01-MAR-09:20 724.10 12.41 0.00 304.67 459.44 15.91 0.00 243.50
April 369.33 0.52 0.48 01-APR-10:09 863.58 13.25 0.00 331.33 538.28 16.73 0.00 284.33
May 407.00 0.50 0.48 01-MAY-07:40 1072.07 16.73 51.67 383.83 652.38 19.86 52.50 356.33
June 411.67 0.50 0.48 01-JUN-06:49 1164.00 17.56 66.50 387.33 708.28 20.63 68.17 366.67
July 411.00 0.51 0.48 01-JUL-06:10 1170.72 16.88 53.00 386.17 685.71 19.98 53.83 357.00
August 390.50 0.51 0.48 01-AUG-06:00 1048.02 14.22 0.00 360.50 634.35 17.64 0.00 331.67
September 298.50 0.53 0.48 01-SEP-07:49 802.39 13.32 0.00 304.83 504.80 16.74 0.00 239.00
October 293.50 0.56 0.48 01-OCT-10:39 599.08 11.12 0.00 246.50 398.51 14.77 0.00 175.33
November 299.00 0.57 0.48 01-NOV-09:00 550.83 10.46 0.00 231.00 348.50 14.04 0.00 150.33
December 285.17 0.58 0.48 01-DEC-09:50 513.57 10.05 0.00 211.83 324.09 13.75 0.00 117.33
                         
Annual Sum or Average 4071.00 0.53     837.73 13.42 171.17 3568.00 517.19 16.84 174.50 2885.50
Minimum of Months 263.00 0.50 0.48   513.57 10.01 0.00 199.83 324.09 13.66 0.00 117.33
Maximum of Months 411.67 0.58 0.48   1170.72 17.56 66.50 387.33 708.28 20.63 68.17 366.67



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_MID_ZN_4_DAYLCTRL

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 290.67 0.53 0.48 01-JAN-10:00 1776.27 20.67 89.17 248.33 997.74 21.39 67.17 204.67
February 263.00 0.55 0.48 01-FEB-13:39 1711.20 18.31 63.83 221.50 929.96 20.01 46.83 178.67
March 351.67 0.52 0.48 01-MAR-09:30 2303.69 20.28 98.00 313.83 1241.81 21.17 72.33 277.00
April 369.33 0.52 0.48 01-APR-10:20 2444.01 17.93 78.33 334.17 1369.62 19.26 51.17 297.17
May 407.00 0.51 0.48 01-MAY-08:20 2445.92 16.17 50.50 368.83 1076.47 17.07 0.00 333.67
June 411.67 0.52 0.48 01-JUN-07:49 2564.48 13.69 1.67 370.50 1134.55 17.02 0.00 338.83
July 411.00 0.52 0.48 01-JUL-07:49 2540.49 16.18 51.67 370.83 1111.20 17.07 0.00 336.00
August 390.50 0.51 0.48 01-AUG-07:49 2495.75 18.81 89.00 356.67 1125.51 17.82 7.67 325.00
September 298.50 0.52 0.48 01-SEP-08:39 2262.12 20.88 90.83 308.00 1212.84 21.59 62.67 266.67
October 293.50 0.53 0.48 01-OCT-10:39 2428.80 20.49 93.17 270.00 957.80 19.31 42.50 224.83
November 299.00 0.54 0.48 01-NOV-09:50 1691.70 20.58 96.00 254.17 900.94 21.25 67.50 211.83
December 285.17 0.53 0.48 01-DEC-09:39 1474.95 20.11 85.17 243.17 796.84 20.87 59.33 193.17
                         
Annual Sum or Average 4071.00 0.52     2226.38 18.40 887.33 3660.00 1085.31 19.26 477.17 3187.50
Minimum of Months 263.00 0.51 0.48   1474.95 13.69 1.67 221.50 796.84 17.02 0.00 178.67
Maximum of Months 411.67 0.55 0.48   2564.48 20.88 98.00 370.83 1369.62 21.59 72.33 338.83



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_TOP_ZN_1_DAYLCTRL

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 290.67 0.51 0.48 01-JAN-09:20 5989.36 33.12 257.33 272.00 1720.73 22.51 103.00 252.50
February 263.00 0.52 0.48 01-FEB-13:39 7012.56 33.22 228.67 247.50 1214.13 16.99 25.83 217.83
March 351.67 0.52 0.48 01-MAR-08:50 1701.35 13.32 6.67 319.83 1027.50 16.68 0.00 287.33
April 369.33 0.52 0.48 01-APR-08:30 1411.70 13.20 0.00 326.83 836.97 16.69 0.00 288.50
May 407.00 0.52 0.48 01-MAY-07:49 1281.16 13.53 0.00 360.67 745.74 16.98 0.00 317.83
June 411.67 0.52 0.48 01-JUN-07:10 1194.55 13.37 0.00 362.00 702.71 16.81 0.00 320.33
July 411.00 0.52 0.48 01-JUL-07:30 1255.97 13.54 0.00 365.83 729.54 16.95 0.00 319.83
August 390.50 0.52 0.48 01-AUG-07:30 1524.56 14.11 0.00 351.17 866.44 17.52 0.00 316.50
September 298.50 0.52 0.48 01-SEP-07:40 1625.51 14.18 6.50 309.17 944.57 17.28 0.00 274.67
October 293.50 0.51 0.48 01-OCT-10:39 2897.95 20.60 117.00 292.83 1139.24 15.78 2.00 258.17
November 299.00 0.51 0.48 01-NOV-08:30 5900.01 34.27 282.83 273.50 1265.37 20.88 81.67 255.17
December 285.17 0.50 0.48 01-DEC-07:00 5642.89 34.03 265.17 268.50 1660.58 23.59 115.67 248.50
                         
Annual Sum or Average 4071.00 0.52     2834.36 19.71 1164.17 3749.83 1029.02 18.04 328.17 3357.17
Minimum of Months 263.00 0.50 0.48   1194.55 13.20 0.00 247.50 702.71 15.78 0.00 217.83
Maximum of Months 411.67 0.52 0.48   7012.56 34.27 282.83 365.83 1720.73 23.59 115.67 320.33



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_TOP_ZN_2_DAYLCTRL

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 290.67 0.54 0.48 01-JAN-09:09 1456.26 18.50 71.50 247.67 757.24 19.30 45.83 195.67
February 263.00 0.54 0.48 01-FEB-13:39 1992.59 19.79 71.17 231.17 1080.11 20.38 48.33 187.17
March 351.67 0.52 0.48 01-MAR-08:39 2320.71 19.93 105.50 314.83 939.45 19.31 47.33 276.83
April 369.33 0.52 0.48 01-APR-08:09 2234.75 19.22 92.83 328.67 1229.16 20.41 67.00 297.67
May 407.00 0.51 0.48 01-MAY-07:10 2532.51 19.62 108.33 369.33 1097.10 19.95 57.50 335.83
June 411.67 0.51 0.48 01-JUN-06:30 2578.34 20.42 122.67 371.50 1113.06 20.13 64.00 339.33
July 411.00 0.52 0.48 01-JUL-05:00 2536.35 19.56 104.83 375.17 1120.36 20.06 58.33 337.83
August 390.50 0.51 0.48 01-AUG-06:40 2329.22 20.04 103.33 353.00 1259.13 21.18 73.33 321.67
September 298.50 0.52 0.48 01-SEP-07:10 2207.17 19.94 78.83 307.83 1186.61 20.98 55.83 268.33
October 293.50 0.53 0.48 01-OCT-08:09 2562.82 20.26 90.50 272.67 1007.27 20.06 50.00 229.17
November 299.00 0.54 0.48 01-NOV-08:20 1756.85 20.62 97.00 251.17 962.36 21.40 71.33 212.33
December 285.17 0.53 0.48 01-DEC-07:49 1491.81 19.11 73.00 242.83 812.05 20.78 57.17 190.67
                         
Annual Sum or Average 4071.00 0.52     2209.46 19.76 1119.50 3665.83 1059.83 20.31 696.00 3192.50
Minimum of Months 263.00 0.51 0.48   1456.26 18.50 71.17 231.17 757.24 19.30 45.83 187.17
Maximum of Months 411.67 0.54 0.48   2578.34 20.62 122.67 375.17 1259.13 21.40 73.33 339.33



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_TOP_ZN_3_DAYLCTRL

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 290.67 0.57 0.48 01-JAN-11:09 532.87 9.98 0.00 220.17 335.48 13.64 0.00 128.33
February 263.00 0.58 0.48 01-FEB-13:39 569.47 10.31 0.00 200.17 368.54 13.93 0.00 136.17
March 351.67 0.53 0.48 01-MAR-09:20 724.80 12.38 0.00 304.83 460.02 15.90 0.00 243.50
April 369.33 0.52 0.48 01-APR-10:09 864.50 13.22 0.00 331.33 538.99 16.72 0.00 284.33
May 407.00 0.50 0.48 01-MAY-07:40 1073.32 16.70 51.67 384.00 653.29 19.84 52.50 356.67
June 411.67 0.50 0.48 01-JUN-06:49 1165.36 17.53 66.50 387.33 709.26 20.61 68.17 366.83
July 411.00 0.51 0.48 01-JUL-06:10 1172.05 16.85 53.00 386.17 686.68 19.97 53.83 357.00
August 390.50 0.51 0.48 01-AUG-06:00 1049.22 14.19 0.00 360.50 635.25 17.63 0.00 331.83
September 298.50 0.53 0.48 01-SEP-07:49 803.16 13.29 0.00 304.83 505.45 16.72 0.00 239.17
October 293.50 0.56 0.48 01-OCT-10:39 599.54 11.08 0.00 246.50 398.96 14.76 0.00 176.00
November 299.00 0.57 0.48 01-NOV-09:00 551.34 10.43 0.00 231.17 348.95 14.02 0.00 150.50
December 285.17 0.58 0.48 01-DEC-09:50 514.06 10.02 0.00 211.83 324.51 13.73 0.00 117.83
                         
Annual Sum or Average 4071.00 0.53     838.61 13.39 171.17 3568.83 517.88 16.82 174.50 2888.17
Minimum of Months 263.00 0.50 0.48   514.06 9.98 0.00 200.17 324.51 13.64 0.00 117.83
Maximum of Months 411.67 0.58 0.48   1172.05 17.53 66.50 387.33 709.26 20.61 68.17 366.83



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_TOP_ZN_4_DAYLCTRL

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 290.67 0.53 0.48 01-JAN-10:50 1777.18 20.65 89.00 248.33 998.56 21.37 67.17 204.83
February 263.00 0.55 0.48 01-FEB-13:39 1712.19 18.28 63.83 221.50 930.87 19.99 46.83 178.83
March 351.67 0.52 0.48 01-MAR-09:30 2304.92 20.25 98.00 313.83 1242.93 21.16 72.33 277.67
April 369.33 0.52 0.48 01-APR-10:20 2445.54 17.90 78.33 334.17 1370.84 19.25 51.17 297.33
May 407.00 0.51 0.48 01-MAY-08:20 2437.54 16.14 50.50 368.00 1077.82 17.06 0.00 333.83
June 411.67 0.52 0.48 01-JUN-07:40 2566.24 13.65 1.67 370.50 1135.91 17.00 0.00 339.00
July 411.00 0.52 0.48 01-JUL-07:49 2542.31 16.15 51.67 371.00 1112.59 17.06 0.00 336.00
August 390.50 0.51 0.48 01-AUG-07:49 2497.72 18.78 89.00 356.67 1127.02 17.81 7.67 325.00
September 298.50 0.52 0.48 01-SEP-08:39 2263.73 20.86 90.83 308.00 1214.15 21.58 62.67 266.83
October 293.50 0.53 0.48 01-OCT-10:39 2429.77 20.46 93.17 270.00 958.71 19.30 42.50 225.00
November 299.00 0.54 0.48 01-NOV-09:50 1692.64 20.56 96.00 254.17 901.81 21.24 67.50 211.83
December 285.17 0.53 0.48 01-DEC-09:39 1475.78 20.08 85.17 243.17 797.62 20.86 59.33 193.67
                         
Annual Sum or Average 4071.00 0.52     2226.78 18.38 887.17 3659.33 1086.47 19.24 477.17 3189.83
Minimum of Months 263.00 0.51 0.48   1475.78 13.65 1.67 221.50 797.62 17.00 0.00 178.83
Maximum of Months 411.67 0.55 0.48   2566.24 20.86 98.00 371.00 1370.84 21.58 72.33 339.00



Table of Contents

Report: CoilReportMonthly

For: VAV_BOT WITH REHEAT HEATING COIL

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.617294E+09 51267.35 27-JAN-07:10 0.00 0.00 0.00 0.00 0.00
February 0.510014E+09 55874.14 03-FEB-07:10 0.00 0.00 0.00 0.00 0.00
March 0.184652E+09 22570.86 18-MAR-06:10 0.00 0.00 0.00 0.00 0.00
April 0.174134E+09 27263.41 06-APR-06:10 0.00 0.00 0.00 0.00 0.00
May 16828398.72 3639.68 16-MAY-16:10 0.00 0.00 0.00 0.00 0.00
June 3975658.35 1833.55 10-JUN-16:35 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 3131721.70 2562.15 14-SEP-15:50 0.00 0.00 0.00 0.00 0.00
October 83624418.08 24474.53 26-OCT-06:10 0.00 0.00 0.00 0.00 0.00
November 0.241672E+09 40670.39 22-NOV-07:10 0.00 0.00 0.00 0.00 0.00
December 0.526512E+09 45707.23 18-DEC-07:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.236184E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.617294E+09 55874.14   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: CORE_BOTTOM VAV BOX REHEAT COIL

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:05 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:03 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:03 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.142487E+10 16287.69 12-JAN-06:02 0.00 0.00 0.00 0.00 0.00
February 0.580827E+09 16124.69 03-FEB-06:02 0.00 0.00 0.00 0.00 0.00
March 1537312.50 540.90 18-MAR-07:00 0.00 0.00 0.00 0.00 0.00
April 36033.36 60.06 06-APR-06:00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:03 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:03 0.00 0.00 0.00 0.00 0.00
October 2696431.80 619.62 26-OCT-06:00 0.00 0.00 0.00 0.00 0.00
November 43319595.67 13477.59 22-NOV-06:03 0.00 0.00 0.00 0.00 0.00
December 0.159479E+09 15981.43 18-DEC-06:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.221276E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.142487E+10 16287.69   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.119287E+10 13538.54 12-JAN-06:02 0.00 0.00 0.00 0.00 0.00
February 0.559225E+09 13400.74 13-FEB-06:02 0.00 0.00 0.00 0.00 0.00
March 36214619.67 2388.95 23-MAR-05:06 0.00 0.00 0.00 0.00 0.00
April 10565802.89 1639.28 06-APR-05:05 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:03 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:03 0.00 0.00 0.00 0.00 0.00
October 10259847.07 2055.08 26-OCT-05:05 0.00 0.00 0.00 0.00 0.00
November 79942894.46 13291.83 21-NOV-06:01 0.00 0.00 0.00 0.00 0.00
December 0.309698E+09 13284.69 19-DEC-06:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.219877E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.119287E+10 13538.54   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.120099E+10 18504.43 05-JAN-06:03 0.00 0.00 0.00 0.00 0.00
February 0.513461E+09 18411.72 13-FEB-05:04 0.00 0.00 0.00 0.00 0.00
March 18931173.62 2477.00 23-MAR-05:06 0.00 0.00 0.00 0.00 0.00
April 8265811.51 1733.76 06-APR-05:08 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:03 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:03 0.00 0.00 0.00 0.00 0.00
October 7721130.10 1604.21 26-OCT-05:20 0.00 0.00 0.00 0.00 0.00
November 61250170.09 18262.68 21-NOV-06:01 0.00 0.00 0.00 0.00 0.00
December 0.259219E+09 18452.85 18-DEC-06:02 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.206984E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.120099E+10 18504.43   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.734922E+09 12306.55 23-JAN-06:02 0.00 0.00 0.00 0.00 0.00
February 0.146744E+09 12299.79 03-FEB-06:02 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:03 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:03 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 2660909.57 570.51 22-NOV-07:00 0.00 0.00 0.00 0.00 0.00
December 517520.28 221.64 01-DEC-07:00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.884845E+09     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.734922E+09 12306.55   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: VAV_MID WITH REHEAT HEATING COIL

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.299659E+11 514746.89 27-JAN-07:10 0.00 0.00 0.00 0.00 0.00
February 0.128535E+11 558569.01 03-FEB-07:10 0.00 0.00 0.00 0.00 0.00
March 0.469222E+10 240291.43 18-MAR-06:10 0.00 0.00 0.00 0.00 0.00
April 0.167532E+10 286821.63 06-APR-06:10 0.00 0.00 0.00 0.00 0.00
May 0.409918E+09 40551.67 15-MAY-18:20 0.00 0.00 0.00 0.00 0.00
June 32653803.07 8841.59 10-JUN-13:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 48386671.38 24095.30 14-SEP-15:10 0.00 0.00 0.00 0.00 0.00
October 0.133033E+10 259471.82 26-OCT-06:10 0.00 0.00 0.00 0.00 0.00
November 0.404417E+10 421737.34 22-NOV-07:10 0.00 0.00 0.00 0.00 0.00
December 0.883385E+10 453348.43 18-DEC-07:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.638862E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.299659E+11 558569.01   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: CORE_MID VAV BOX REHEAT COIL

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.186566E+11 569202.58 02-JAN-06:03 0.00 0.00 0.00 0.00 0.00
February 0.843316E+10 568715.68 06-FEB-06:04 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:03 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:03 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.190783E+10 566726.95 26-DEC-06:02 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.289976E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.186566E+11 569202.58   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.686012E+11 163271.54 02-JAN-06:06 0.00 0.00 0.00 0.00 0.00
February 0.415086E+11 163100.32 11-FEB-05:11 0.00 0.00 0.00 0.00 0.00
March 0.662537E+10 162488.11 22-MAR-05:03 0.00 0.00 0.00 0.00 0.00
April 0.144216E+10 161460.06 06-APR-05:03 0.00 0.00 0.00 0.00 0.00
May 22824.60 38.04 11-MAY-05:50 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:03 0.00 0.00 0.00 0.00 0.00
October 0.307371E+10 163020.22 31-OCT-05:03 0.00 0.00 0.00 0.00 0.00
November 0.125535E+11 162631.76 24-NOV-05:11 0.00 0.00 0.00 0.00 0.00
December 0.364514E+11 163382.42 26-DEC-06:04 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.170256E+12     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.686012E+11 163382.42   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.457294E+11 173262.84 11-JAN-06:03 0.00 0.00 0.00 0.00 0.00
February 0.277731E+11 173236.91 08-FEB-05:12 0.00 0.00 0.00 0.00 0.00
March 0.498493E+10 172952.71 22-MAR-04:11 0.00 0.00 0.00 0.00 0.00
April 0.901354E+09 127737.26 06-APR-05:03 0.00 0.00 0.00 0.00 0.00
May 22403338.82 11616.34 11-MAY-05:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 15415404.19 3710.68 29-SEP-05:50 0.00 0.00 0.00 0.00 0.00
October 0.354001E+10 172979.33 26-OCT-04:11 0.00 0.00 0.00 0.00 0.00
November 0.874012E+10 173083.02 24-NOV-06:02 0.00 0.00 0.00 0.00 0.00
December 0.246607E+11 173142.68 28-DEC-05:12 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.116367E+12     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.457294E+11 173262.84   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.368598E+11 192802.45 02-JAN-06:03 0.00 0.00 0.00 0.00 0.00
February 0.225112E+11 192656.78 11-FEB-05:11 0.00 0.00 0.00 0.00 0.00
March 0.320641E+10 191595.99 23-MAR-05:02 0.00 0.00 0.00 0.00 0.00
April 0.876730E+09 190696.33 06-APR-05:03 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:03 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:03 0.00 0.00 0.00 0.00 0.00
October 0.142130E+10 185490.24 26-OCT-05:03 0.00 0.00 0.00 0.00 0.00
November 0.463861E+10 191677.06 25-NOV-05:02 0.00 0.00 0.00 0.00 0.00
December 0.159826E+11 192981.47 26-DEC-06:04 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.854967E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.368598E+11 192981.47   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.399627E+11 176086.83 11-JAN-06:03 0.00 0.00 0.00 0.00 0.00
February 0.239527E+11 175946.86 13-FEB-05:52 0.00 0.00 0.00 0.00 0.00
March 0.413019E+10 175755.64 22-MAR-04:11 0.00 0.00 0.00 0.00 0.00
April 0.746159E+09 119710.33 06-APR-05:03 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:03 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 7016221.87 2764.22 29-SEP-05:50 0.00 0.00 0.00 0.00 0.00
October 0.242852E+10 121731.07 26-OCT-05:03 0.00 0.00 0.00 0.00 0.00
November 0.820117E+10 175730.20 21-NOV-05:02 0.00 0.00 0.00 0.00 0.00
December 0.218353E+11 175855.22 26-DEC-05:13 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.101264E+12     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.399627E+11 176086.83   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: VAV_TOP WITH REHEAT HEATING COIL

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.388684E+09 48914.22 27-JAN-07:10 0.00 0.00 0.00 0.00 0.00
February 0.309434E+09 55008.75 03-FEB-07:10 0.00 0.00 0.00 0.00 0.00
March 0.133710E+09 24573.72 18-MAR-06:10 0.00 0.00 0.00 0.00 0.00
April 0.138376E+09 29495.44 06-APR-06:10 0.00 0.00 0.00 0.00 0.00
May 29738423.31 5181.01 15-MAY-17:10 0.00 0.00 0.00 0.00 0.00
June 1316040.15 467.54 10-JUN-16:25 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 133851.62 161.71 22-SEP-15:10 0.00 0.00 0.00 0.00 0.00
October 75864361.36 26403.64 26-OCT-06:10 0.00 0.00 0.00 0.00 0.00
November 0.201460E+09 40297.94 22-NOV-07:10 0.00 0.00 0.00 0.00 0.00
December 0.342885E+09 42952.86 18-DEC-07:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.162160E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.388684E+09 55008.75   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: CORE_TOP VAV BOX REHEAT COIL

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.131676E+11 91193.36 02-JAN-06:04 0.00 0.00 0.00 0.00 0.00
February 0.654993E+10 91050.34 06-FEB-04:33 0.00 0.00 0.00 0.00 0.00
March 0.532839E+09 90827.59 20-MAR-05:03 0.00 0.00 0.00 0.00 0.00
April 26397337.14 4439.68 07-APR-05:40 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:03 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:03 0.00 0.00 0.00 0.00 0.00
October 0.347282E+09 91042.03 30-OCT-05:03 0.00 0.00 0.00 0.00 0.00
November 0.182827E+10 91022.66 27-NOV-06:03 0.00 0.00 0.00 0.00 0.00
December 0.774482E+10 91139.77 26-DEC-05:16 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.301971E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.131676E+11 91193.36   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.116095E+11 18448.53 18-JAN-06:04 0.00 0.00 0.00 0.00 0.00
February 0.705884E+10 18452.69 08-FEB-06:04 0.00 0.00 0.00 0.00 0.00
March 0.181297E+10 18367.32 24-MAR-05:03 0.00 0.00 0.00 0.00 0.00
April 0.527157E+09 18292.28 07-APR-04:13 0.00 0.00 0.00 0.00 0.00
May 30076555.10 12063.61 11-MAY-05:02 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 11475468.17 1810.50 29-SEP-05:04 0.00 0.00 0.00 0.00 0.00
October 0.116350E+10 18436.68 31-OCT-04:13 0.00 0.00 0.00 0.00 0.00
November 0.318199E+10 18457.30 24-NOV-06:04 0.00 0.00 0.00 0.00 0.00
December 0.738521E+10 18433.71 12-DEC-06:03 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.327807E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.116095E+11 18457.30   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.730160E+10 18752.80 19-JAN-05:12 0.00 0.00 0.00 0.00 0.00
February 0.437168E+10 18745.76 11-FEB-05:11 0.00 0.00 0.00 0.00 0.00
March 0.111571E+10 18684.71 22-MAR-04:12 0.00 0.00 0.00 0.00 0.00
April 0.297077E+09 18611.97 06-APR-04:02 0.00 0.00 0.00 0.00 0.00
May 19258085.21 5953.24 11-MAY-05:02 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 43226403.85 3023.17 29-SEP-05:02 0.00 0.00 0.00 0.00 0.00
October 0.853477E+09 18681.66 30-OCT-04:11 0.00 0.00 0.00 0.00 0.00
November 0.198202E+10 18691.76 24-NOV-05:12 0.00 0.00 0.00 0.00 0.00
December 0.459391E+10 18753.14 23-DEC-05:12 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.205780E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.730160E+10 18753.14   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.717491E+10 21163.94 09-JAN-04:25 0.00 0.00 0.00 0.00 0.00
February 0.444734E+10 21233.86 11-FEB-05:13 0.00 0.00 0.00 0.00 0.00
March 0.113695E+10 21159.82 22-MAR-04:13 0.00 0.00 0.00 0.00 0.00
April 0.400895E+09 21030.54 06-APR-04:02 0.00 0.00 0.00 0.00 0.00
May 32749172.57 6293.67 11-MAY-05:02 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 11262480.37 2425.55 29-SEP-05:04 0.00 0.00 0.00 0.00 0.00
October 0.742879E+09 21225.08 30-OCT-04:13 0.00 0.00 0.00 0.00 0.00
November 0.162865E+10 21160.54 24-NOV-05:13 0.00 0.00 0.00 0.00 0.00
December 0.405364E+10 21177.10 26-DEC-05:54 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.196293E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.717491E+10 21233.86   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.672471E+10 20392.84 11-JAN-05:03 0.00 0.00 0.00 0.00 0.00
February 0.399884E+10 20405.42 07-FEB-05:02 0.00 0.00 0.00 0.00 0.00
March 0.109863E+10 20388.49 22-MAR-04:12 0.00 0.00 0.00 0.00 0.00
April 0.301443E+09 20344.64 06-APR-04:01 0.00 0.00 0.00 0.00 0.00
May 22857073.63 2226.71 10-MAY-05:06 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 29099922.70 2590.67 29-SEP-05:04 0.00 0.00 0.00 0.00 0.00
October 0.802321E+09 20384.78 30-OCT-04:11 0.00 0.00 0.00 0.00 0.00
November 0.191645E+10 20389.28 22-NOV-05:03 0.00 0.00 0.00 0.00 0.00
December 0.409321E+10 20386.16 02-DEC-05:03 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.189876E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.672471E+10 20405.42   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: CAV_BAS HEATING COIL

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:05 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:03 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:03 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: AIRLOOP DATACENTER BASEMENT HEATING COIL

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:05 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:03 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:03 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: AIRLOOP DATACENTER BOT HEATING COIL

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:05 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:03 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:03 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: AIRLOOP DATACENTER MID HEATING COIL

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:05 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:03 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:03 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: AIRLOOP DATACENTER TOP HEATING COIL

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:05 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:03 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:03 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:05 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:03 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:03 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: AIRLOOP DATACENTER BOT_SUPPHEATCOIL

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:05 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:03 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:03 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: AIRLOOP DATACENTER MID_SUPPHEATCOIL

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:05 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:03 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:03 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: AIRLOOP DATACENTER TOP_SUPPHEATCOIL

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:05 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:03 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:03 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: VAV_BOT WITH REHEAT COOLING COIL

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.418628E+10 0.325438E+10 49577.65 19-JAN-16:00 29173.45 0.05
February 0.00 0.00 0.129807E+11 0.119387E+11 87790.55 28-FEB-15:00 87790.55 0.08
March 0.00 0.00 0.371894E+11 0.329776E+11 128454.66 30-MAR-15:20 128454.66 0.20
April 0.00 0.00 0.709594E+11 0.637861E+11 167098.76 17-APR-15:30 167098.76 0.44
May 0.00 0.00 0.108026E+12 0.845171E+11 193635.85 31-MAY-05:03 155604.38 0.56
June 0.00 0.00 0.153777E+12 0.122204E+12 213687.23 16-JUN-04:11 162669.77 0.65
July 0.00 0.00 0.182750E+12 0.139273E+12 214129.59 01-JUL-04:11 163114.09 0.77
August 0.00 0.00 0.212940E+12 0.162510E+12 185156.23 12-AUG-05:02 157356.77 0.86
September 0.00 0.00 0.123099E+12 0.926115E+11 208129.89 27-SEP-04:11 163231.01 0.61
October 0.00 0.00 0.608539E+11 0.477557E+11 235688.64 19-OCT-04:12 154541.19 0.33
November 0.00 0.00 0.271954E+11 0.232311E+11 114994.50 27-NOV-05:12 114994.50 0.15
December 0.00 0.00 0.103734E+11 0.790705E+10 98865.46 12-DEC-14:00 75587.09 0.08
                 
Annual Sum or Average 0.00 0.00 0.100433E+13 0.791967E+12       0.40
Minimum of Months 0.00 0.00 0.418628E+10 0.325438E+10 49577.65   29173.45 0.05
Maximum of Months 0.00 0.00 0.212940E+12 0.162510E+12 235688.64   167098.76 0.86



Table of Contents

Report: CoilReportMonthly

For: VAV_MID WITH REHEAT COOLING COIL

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.349320E+11 0.269659E+11 391845.64 19-JAN-22:00 219275.79 0.05
February 0.00 0.00 0.101155E+12 0.918812E+11 653877.50 28-FEB-15:00 653877.50 0.07
March 0.00 0.00 0.282113E+12 0.250755E+12 1096174.49 30-MAR-15:20 1096174.49 0.19
April 0.00 0.00 0.509438E+12 0.456356E+12 1289759.78 17-APR-14:30 1289759.78 0.37
May 0.00 0.00 0.944928E+12 0.725085E+12 1775638.32 31-MAY-05:03 1301195.11 0.54
June 0.00 0.00 0.131898E+13 0.100441E+13 2047154.54 30-JUN-05:02 1507820.86 0.59
July 0.00 0.00 0.149738E+13 0.106167E+13 2010011.17 14-JUL-04:12 1515440.38 0.63
August 0.00 0.00 0.167177E+13 0.116374E+13 2301627.01 23-AUG-05:02 1514799.68 0.66
September 0.00 0.00 0.107676E+13 0.781454E+12 2038906.50 27-SEP-04:11 1457272.90 0.59
October 0.00 0.00 0.481617E+12 0.363932E+12 1941680.82 19-OCT-04:12 1049398.91 0.31
November 0.00 0.00 0.196320E+12 0.164516E+12 672240.39 04-NOV-05:03 359905.29 0.14
December 0.00 0.00 0.683327E+11 0.516345E+11 563451.24 12-DEC-14:00 453293.67 0.08
                 
Annual Sum or Average 0.00 0.00 0.818373E+13 0.614239E+13       0.35
Minimum of Months 0.00 0.00 0.349320E+11 0.269659E+11 391845.64   219275.79 0.05
Maximum of Months 0.00 0.00 0.167177E+13 0.116374E+13 2301627.01   1515440.38 0.66



Table of Contents

Report: CoilReportMonthly

For: VAV_TOP WITH REHEAT COOLING COIL

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.349096E+10 0.267261E+10 40197.45 19-JAN-22:00 22843.57 0.05
February 0.00 0.00 0.973973E+10 0.879443E+10 61977.71 28-FEB-15:30 61977.71 0.07
March 0.00 0.00 0.277521E+11 0.245935E+11 119355.63 30-MAR-14:20 117252.05 0.19
April 0.00 0.00 0.522745E+11 0.469645E+11 128673.21 17-APR-15:50 128673.21 0.36
May 0.00 0.00 0.101586E+12 0.789405E+11 158202.96 31-MAY-05:03 111731.64 0.53
June 0.00 0.00 0.144690E+12 0.112237E+12 224993.49 26-JUN-04:12 163604.83 0.59
July 0.00 0.00 0.163866E+12 0.119373E+12 220443.80 31-JUL-04:11 146829.49 0.63
August 0.00 0.00 0.181702E+12 0.129900E+12 256142.79 23-AUG-05:02 163986.73 0.67
September 0.00 0.00 0.110976E+12 0.812888E+11 206225.00 05-SEP-05:02 146916.31 0.58
October 0.00 0.00 0.483804E+11 0.359076E+11 202558.16 19-OCT-04:12 102982.15 0.30
November 0.00 0.00 0.183911E+11 0.152563E+11 63177.20 03-NOV-15:00 41720.57 0.14
December 0.00 0.00 0.670704E+10 0.503672E+10 56784.57 12-DEC-14:00 44815.95 0.08
                 
Annual Sum or Average 0.00 0.00 0.869555E+12 0.660964E+12       0.35
Minimum of Months 0.00 0.00 0.349096E+10 0.267261E+10 40197.45   22843.57 0.05
Maximum of Months 0.00 0.00 0.181702E+12 0.129900E+12 256142.79   163986.73 0.67



Table of Contents

Report: CoilReportMonthly

For: CAV_BAS COOLING COIL

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.577388E+09 0.561106E+09 60662.59 20-JAN-05:23 27351.39 0.02
February 0.00 0.00 0.423326E+10 0.421127E+10 76165.51 18-FEB-06:02 31522.39 0.01
March 0.00 0.00 0.135794E+11 0.135220E+11 102769.19 30-MAR-05:03 51120.82 0.13
April 0.00 0.00 0.290157E+11 0.285580E+11 104988.40 03-APR-04:12 104988.40 0.25
May 0.00 0.00 0.516525E+11 0.475012E+11 135025.59 31-MAY-04:12 53806.43 0.43
June 0.00 0.00 0.893055E+11 0.760581E+11 157713.48 23-JUN-04:12 91831.30 0.52
July 0.00 0.00 0.100403E+12 0.807227E+11 162673.87 08-JUL-03:02 95553.97 0.53
August 0.00 0.00 0.120344E+12 0.945161E+11 184663.80 06-AUG-17:31 94456.21 0.61
September 0.00 0.00 0.758328E+11 0.647648E+11 179768.22 10-SEP-15:52 98091.15 0.51
October 0.00 0.00 0.329230E+11 0.278620E+11 152244.76 19-OCT-04:53 92825.50 0.21
November 0.00 0.00 0.105310E+11 0.993063E+10 99535.69 27-NOV-06:03 48476.86 0.08
December 0.00 0.00 0.307062E+10 0.283080E+10 96908.29 13-DEC-06:03 44950.97 0.04
                 
Annual Sum or Average 0.00 0.00 0.531468E+12 0.451039E+12       0.28
Minimum of Months 0.00 0.00 0.577388E+09 0.561106E+09 60662.59   27351.39 0.01
Maximum of Months 0.00 0.00 0.120344E+12 0.945161E+11 184663.80   104988.40 0.61



Table of Contents

Report: CoilReportMonthly

For: AIRLOOP DATACENTER BASEMENT COOLING COIL

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.322755E+12 0.322249E+12 130240.38 19-JAN-17:00 124214.82 0.00
February 0.00 0.00 0.513810E+12 0.513255E+12 220370.20 17-FEB-17:00 214654.59 0.00
March 0.00 0.00 0.819754E+12 0.818178E+12 394618.19 31-MAR-24:00 394618.19 0.00
April 0.00 0.00 0.103147E+13 0.102945E+13 407355.99 21-APR-15:00 400897.14 0.00
May 0.00 0.00 0.341365E+12 0.335009E+12 213304.05 31-MAY-23:10 211304.73 0.00
June 0.00 0.00 0.573902E+12 0.564586E+12 304523.38 30-JUN-24:00 304005.18 0.00
July 0.00 0.00 0.840997E+12 0.829881E+12 396982.36 31-JUL-23:55 396160.59 0.00
August 0.00 0.00 0.108128E+13 0.107015E+13 423093.78 08-AUG-17:00 404508.70 0.00
September 0.00 0.00 0.338494E+12 0.330100E+12 212230.89 30-SEP-23:20 211708.01 0.00
October 0.00 0.00 0.584559E+12 0.580848E+12 304685.21 31-OCT-24:00 304685.21 0.00
November 0.00 0.00 0.798455E+12 0.796979E+12 318078.77 27-NOV-17:00 311414.03 0.00
December 0.00 0.00 0.106524E+13 0.106449E+13 408994.61 13-DEC-14:00 401173.82 0.00
                 
Annual Sum or Average 0.00 0.00 0.831209E+13 0.825518E+13       0.00
Minimum of Months 0.00 0.00 0.322755E+12 0.322249E+12 130240.38   124214.82 0.00
Maximum of Months 0.00 0.00 0.108128E+13 0.107015E+13 423093.78   404508.70 0.00



Table of Contents

Report: CoilReportMonthly

For: AIRLOOP DATACENTER BOT COOLING COIL

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.366635E+10 0.364720E+10 2321.85 20-JAN-17:00 2219.08 0.00
February 0.00 0.00 0.857835E+10 0.855628E+10 4531.52 20-FEB-17:57 4498.52 0.00
March 0.00 0.00 0.156283E+11 0.155620E+11 7701.85 31-MAR-24:00 7701.85 0.00
April 0.00 0.00 0.203356E+11 0.202451E+11 8484.65 09-APR-18:15 8484.65 0.00
May 0.00 0.00 0.616096E+10 0.592471E+10 4091.83 31-MAY-24:00 4037.42 0.00
June 0.00 0.00 0.112697E+11 0.108928E+11 5969.29 30-JUN-24:00 5946.40 0.00
July 0.00 0.00 0.167870E+11 0.163096E+11 7801.45 31-JUL-23:55 7779.43 0.00
August 0.00 0.00 0.219404E+11 0.213917E+11 8974.29 04-AUG-15:00 8353.13 0.00
September 0.00 0.00 0.617805E+10 0.586012E+10 3751.76 30-SEP-24:00 3736.09 0.00
October 0.00 0.00 0.108174E+11 0.106659E+11 5655.26 31-OCT-24:00 5655.26 0.00
November 0.00 0.00 0.150064E+11 0.149489E+11 6435.60 11-NOV-17:08 6435.60 0.00
December 0.00 0.00 0.201076E+11 0.200752E+11 8306.44 11-DEC-16:50 8117.81 0.00
                 
Annual Sum or Average 0.00 0.00 0.156476E+12 0.154080E+12       0.00
Minimum of Months 0.00 0.00 0.366635E+10 0.364720E+10 2321.85   2219.08 0.00
Maximum of Months 0.00 0.00 0.219404E+11 0.213917E+11 8974.29   8484.65 0.00



Table of Contents

Report: CoilReportMonthly

For: AIRLOOP DATACENTER MID COOLING COIL

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.116269E+11 0.114626E+11 18736.72 20-JAN-17:00 17679.15 0.00
February 0.00 0.00 0.627246E+11 0.625139E+11 41041.90 28-FEB-17:00 41041.90 0.00
March 0.00 0.00 0.138227E+12 0.137568E+12 71530.82 31-MAR-23:50 71530.82 0.00
April 0.00 0.00 0.188317E+12 0.187412E+12 79656.72 04-APR-15:40 76735.48 0.00
May 0.00 0.00 0.546039E+11 0.523000E+11 38386.76 31-MAY-23:20 37449.74 0.00
June 0.00 0.00 0.105820E+12 0.102079E+12 56649.66 30-JUN-24:00 56416.49 0.00
July 0.00 0.00 0.159537E+12 0.154780E+12 75227.84 31-JUL-23:55 75011.84 0.00
August 0.00 0.00 0.208831E+12 0.203345E+12 85091.30 04-AUG-14:50 79002.59 0.00
September 0.00 0.00 0.544046E+11 0.513058E+11 31326.62 30-SEP-24:00 31060.97 0.00
October 0.00 0.00 0.927509E+11 0.912602E+11 48263.33 31-OCT-23:50 48263.33 0.00
November 0.00 0.00 0.128045E+12 0.127480E+12 59728.96 08-NOV-17:00 59728.96 0.00
December 0.00 0.00 0.168017E+12 0.167694E+12 76467.37 11-DEC-17:00 74576.81 0.00
                 
Annual Sum or Average 0.00 0.00 0.137290E+13 0.134920E+13       0.00
Minimum of Months 0.00 0.00 0.116269E+11 0.114626E+11 18736.72   17679.15 0.00
Maximum of Months 0.00 0.00 0.208831E+12 0.203345E+12 85091.30   79002.59 0.00



Table of Contents

Report: CoilReportMonthly

For: AIRLOOP DATACENTER TOP COOLING COIL

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.621563E+09 0.605803E+09 1961.58 20-JAN-17:00 1852.68 0.00
February 0.00 0.00 0.522525E+10 0.520456E+10 4144.17 28-FEB-17:00 4144.17 0.00
March 0.00 0.00 0.130275E+11 0.129621E+11 6897.78 31-MAR-23:20 6897.78 0.00
April 0.00 0.00 0.184072E+11 0.183172E+11 8065.77 17-APR-16:00 8030.10 0.00
May 0.00 0.00 0.536898E+10 0.513908E+10 3812.03 31-MAY-23:10 3702.08 0.00
June 0.00 0.00 0.106418E+11 0.102675E+11 5636.86 30-JUN-24:00 5613.17 0.00
July 0.00 0.00 0.160576E+11 0.155821E+11 7576.32 31-JUL-23:55 7554.58 0.00
August 0.00 0.00 0.210087E+11 0.204599E+11 8629.02 04-AUG-14:50 8026.21 0.00
September 0.00 0.00 0.526916E+10 0.496154E+10 3066.46 07-SEP-16:00 2681.05 0.00
October 0.00 0.00 0.851575E+10 0.836752E+10 4639.91 18-OCT-16:00 4135.92 0.00
November 0.00 0.00 0.115970E+11 0.115411E+11 5986.35 02-NOV-16:00 5801.33 0.00
December 0.00 0.00 0.152248E+11 0.151927E+11 7609.60 13-DEC-16:00 7280.94 0.00
                 
Annual Sum or Average 0.00 0.00 0.130965E+12 0.128601E+12       0.00
Minimum of Months 0.00 0.00 0.621563E+09 0.605803E+09 1961.58   1852.68 0.00
Maximum of Months 0.00 0.00 0.210087E+11 0.204599E+11 8629.02   8030.10 0.00



Table of Contents

Report: PlantLoopDemandReportMonthly

For: HEATSYS1

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 0.00 0.00 01-JAN-00:05 107759.68 1701386.63 02-JAN-06:01
February 0.00 0.00 01-FEB-00:10 68032.45 1636699.86 06-FEB-06:02
March 0.00 0.00 01-MAR-00:10 11006.38 1531292.97 22-MAR-04:11
April 0.00 0.00 01-APR-00:10 2869.38 1066652.84 06-APR-05:03
May 0.00 0.00 01-MAY-00:03 243.99 51824.29 10-MAY-06:10
June 0.00 0.00 01-JUN-00:10 28.29 24086.49 10-JUN-13:10
July 0.00 0.00 01-JUL-00:10 0.00 0.00 01-JUL-00:10
August 0.00 0.00 01-AUG-00:03 0.00 0.00 01-AUG-00:03
September 0.00 0.00 01-SEP-00:03 50.61 28418.50 14-SEP-15:50
October 0.00 0.00 01-OCT-00:10 5847.03 1092865.74 31-OCT-05:03
November 0.00 0.00 01-NOV-00:10 18885.44 1439935.14 25-NOV-05:01
December 0.00 0.00 01-DEC-00:10 51478.09 1556218.68 26-DEC-06:02
             
Annual Sum or Average 0.00     21989.89    
Minimum of Months 0.00 0.00   0.00 0.00  
Maximum of Months 0.00 0.00   107759.68 1701386.63  



Table of Contents

Report: PlantLoopDemandReportMonthly

For: COOLSYS1_SUPPLY

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 17009.14 488358.06 19-JAN-16:00 0.00 0.00 01-JAN-00:05
February 54701.82 921414.49 28-FEB-15:10 0.00 0.00 01-FEB-00:10
March 141123.94 1671097.78 30-MAR-15:20 0.00 0.00 01-MAR-00:10
April 267702.78 1906410.30 19-APR-14:50 0.00 0.00 01-APR-00:10
May 490744.05 1801466.89 23-MAY-13:50 0.00 0.00 01-MAY-00:03
June 709297.85 2392722.91 29-JUN-05:04 0.00 0.00 01-JUN-00:10
July 778281.20 2174380.29 01-JUL-04:14 0.00 0.00 01-JUL-00:10
August 870530.71 2626680.08 23-AUG-05:02 0.00 0.00 01-AUG-00:03
September 577925.15 1995435.85 16-SEP-16:07 0.00 0.00 01-SEP-00:03
October 252402.85 2203332.40 19-OCT-04:15 0.00 0.00 01-OCT-00:10
November 100922.14 954441.18 02-NOV-13:10 0.00 0.00 01-NOV-00:10
December 34607.14 822898.89 12-DEC-14:00 0.00 0.00 01-DEC-00:10
             
Annual Sum or Average 359815.78     0.00    
Minimum of Months 17009.14 488358.06   0.00 0.00  
Maximum of Months 870530.71 2626680.08   0.00 0.00  



Table of Contents

Report: PlantLoopDemandReportMonthly

For: COOLSYS1_DEMAND

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 16055.10 516312.01 31-JAN-15:10 0.00 0.00 01-JAN-00:05
February 53010.66 919275.08 28-FEB-15:00 0.00 0.00 01-FEB-00:10
March 138450.63 1668459.68 30-MAR-15:10 0.00 0.00 01-MAR-00:10
April 264660.88 2148705.67 17-APR-13:30 0.00 0.00 01-APR-00:10
May 487045.83 3161330.38 31-MAY-05:03 0.00 0.00 01-MAY-00:03
June 706507.76 3877694.25 23-JUN-05:03 0.00 0.00 01-JUN-00:10
July 774668.38 3697342.95 14-JUL-04:12 0.00 0.00 01-JUL-00:10
August 866204.06 3967123.13 12-AUG-05:02 0.00 0.00 01-AUG-00:03
September 575205.69 3790786.16 05-SEP-05:02 0.00 0.00 01-SEP-00:03
October 249339.60 3450528.93 19-OCT-05:03 0.00 0.00 01-OCT-00:10
November 98694.54 958289.25 04-NOV-05:03 0.00 0.00 01-NOV-00:10
December 33410.21 819965.94 12-DEC-14:00 0.00 0.00 01-DEC-00:10
             
Annual Sum or Average 357141.79     0.00    
Minimum of Months 16055.10 516312.01   0.00 0.00  
Maximum of Months 866204.06 3967123.13   0.00 0.00  



Table of Contents

Report: PlantLoopDemandReportMonthly

For: SINGLE WATER PLANT LOOP

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 164780.08 419385.64 31-JAN-15:00 0.00 0.00 01-JAN-00:05
February 338212.29 861722.75 28-FEB-15:00 0.00 0.00 01-FEB-00:10
March 577006.00 1257343.65 30-MAR-16:00 0.00 0.00 01-MAR-00:10
April 892545.52 1531128.30 17-APR-16:00 0.00 0.00 01-APR-00:10
May 438384.66 967370.60 30-MAY-15:00 0.00 0.00 01-MAY-00:03
June 859896.46 1416932.73 06-JUN-15:00 0.00 0.00 01-JUN-00:10
July 1153484.39 1776718.29 08-JUL-16:00 0.00 0.00 01-JUL-00:10
August 1401418.32 1887269.42 01-AUG-16:10 0.00 0.00 01-AUG-00:03
September 520479.85 1042735.33 07-SEP-16:00 0.00 0.00 01-SEP-00:03
October 470403.28 1165752.88 10-OCT-16:00 0.00 0.00 01-OCT-00:10
November 539997.72 1036569.58 05-NOV-16:00 0.00 0.00 01-NOV-00:10
December 617356.57 1186294.93 12-DEC-15:00 0.00 0.00 01-DEC-00:10
             
Annual Sum or Average 666754.42     0.00    
Minimum of Months 164780.08 419385.64   0.00 0.00  
Maximum of Months 1401418.32 1887269.42   0.00 0.00  



Table of Contents

Report: PlantLoopDemandReportMonthly

For: SWHSYS1

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 0.00 0.00 01-JAN-00:05 14850.00 49687.18 30-JAN-12:40
February 0.00 0.00 01-FEB-00:10 14960.05 49691.65 01-FEB-12:40
March 0.00 0.00 01-MAR-00:10 15317.31 48919.31 01-MAR-12:50
April 0.00 0.00 01-APR-00:10 13611.95 46270.62 03-APR-11:50
May 0.00 0.00 01-MAY-00:03 13012.53 43150.94 01-MAY-11:40
June 0.00 0.00 01-JUN-00:10 12345.19 39646.21 01-JUN-11:30
July 0.00 0.00 01-JUL-00:10 10959.34 36965.52 03-JUL-12:00
August 0.00 0.00 01-AUG-00:03 11824.71 36815.48 31-AUG-11:50
September 0.00 0.00 01-SEP-00:03 11655.39 39093.32 29-SEP-11:30
October 0.00 0.00 01-OCT-00:10 12475.73 42640.11 31-OCT-12:00
November 0.00 0.00 01-NOV-00:10 13623.08 46035.21 30-NOV-13:00
December 0.00 0.00 01-DEC-00:10 14016.97 48586.36 29-DEC-12:15
             
Annual Sum or Average 0.00     13211.24    
Minimum of Months 0.00 0.00   10959.34 36815.48  
Maximum of Months 0.00 0.00   15317.31 49691.65  



Table of Contents

Report: PlantLoopDemandReportMonthly

For: TOWERWATERSYS

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 19123.76 581447.72 19-JAN-16:00 4167.44 172700.19 06-JAN-12:20
February 63714.38 1062309.43 28-FEB-15:10 3556.55 190795.46 12-FEB-04:02
March 170952.14 2870371.58 30-MAR-15:20 2367.55 175814.57 06-MAR-07:30
April 337949.50 3071546.89 18-APR-12:40 960.77 109042.00 25-APR-20:00
May 759604.36 4375444.07 31-MAY-12:50 119.99 77238.55 09-MAY-21:00
June 1558598.35 5563746.26 27-JUN-12:10 108.53 83178.82 10-JUN-06:30
July 1960824.18 5919948.60 07-JUL-12:10 0.00 0.00 01-JUL-00:10
August 2363658.45 6143653.85 10-AUG-16:00 0.00 0.00 01-AUG-00:03
September 1127570.91 5424044.31 06-SEP-14:00 92.07 59446.62 14-SEP-06:50
October 401795.52 5016578.85 18-OCT-16:00 1177.66 126607.26 25-OCT-11:00
November 117614.70 1278596.61 02-NOV-13:10 2376.44 164125.37 21-NOV-07:00
December 35999.26 949970.27 12-DEC-14:00 2955.42 184336.09 01-DEC-09:30
             
Annual Sum or Average 748237.52     1479.86    
Minimum of Months 19123.76 581447.72   0.00 0.00  
Maximum of Months 2363658.45 6143653.85   4167.44 190795.46  



Table of Contents

Report: FanReportMonthly

For: CAV_BAS FAN

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.153072E+11 0.80 10319.93 01-JAN-00:50 1.44
February 0.136018E+11 0.79 10319.93 01-FEB-05:01 1.44
March 0.161156E+11 0.84 10319.93 01-MAR-05:12 1.44
April 0.147431E+11 0.79 10319.93 01-APR-04:12 1.44
May 0.155883E+11 0.80 10319.93 01-MAY-04:12 1.43
June 0.155171E+11 0.83 10319.93 01-JUN-04:12 1.43
July 0.153962E+11 0.79 10319.93 01-JUL-04:11 1.43
August 0.171714E+11 0.88 10319.93 01-AUG-03:02 1.43
September 0.162821E+11 0.87 10319.93 01-SEP-04:11 1.43
October 0.161420E+11 0.84 10319.93 01-OCT-24:00 1.42
November 0.157980E+11 0.85 10319.93 01-NOV-04:12 1.43
December 0.152441E+11 0.79 10319.93 01-DEC-04:01 1.44
           
Annual Sum or Average 0.186907E+12 0.82      
Minimum of Months 0.136018E+11 0.79 10319.93   1.42
Maximum of Months 0.171714E+11 0.88 10319.93   1.44



Table of Contents

Report: FanReportMonthly

For: VAV_BOT WITH REHEAT FAN

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.294665E+10 0.29 12997.31 05-JAN-13:07 1.33
February 0.317851E+10 0.31 18211.61 02-FEB-16:30 1.64
March 0.477753E+10 0.37 13469.25 30-MAR-04:12 1.34
April 0.550538E+10 0.40 16859.04 17-APR-15:30 1.55
May 0.530270E+10 0.38 21649.32 30-MAY-04:12 1.81
June 0.678805E+10 0.46 21649.32 05-JUN-04:12 1.81
July 0.746000E+10 0.50 21649.32 01-JUL-04:11 1.81
August 0.891571E+10 0.57 21649.32 12-AUG-05:02 1.81
September 0.556656E+10 0.39 21649.32 05-SEP-04:12 1.81
October 0.491238E+10 0.36 21649.32 19-OCT-04:12 1.81
November 0.427493E+10 0.34 13012.85 21-NOV-09:50 1.33
December 0.383480E+10 0.31 13469.25 13-DEC-05:12 1.34
           
Annual Sum or Average 0.634632E+11 0.39      
Minimum of Months 0.294665E+10 0.29 12997.31   1.33
Maximum of Months 0.891571E+10 0.57 21649.32   1.81



Table of Contents

Report: FanReportMonthly

For: VAV_MID WITH REHEAT FAN

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.291286E+11 0.31 90861.50 06-JAN-12:00 1.12
February 0.272292E+11 0.32 100578.83 03-FEB-11:45 1.19
March 0.332390E+11 0.32 95861.59 03-MAR-06:02 1.15
April 0.359464E+11 0.32 107741.82 17-APR-14:30 1.23
May 0.439145E+11 0.36 160310.60 30-MAY-05:03 1.57
June 0.545407E+11 0.41 203125.57 13-JUN-05:02 1.82
July 0.561742E+11 0.40 203125.57 05-JUL-04:12 1.82
August 0.620613E+11 0.43 203125.57 09-AUG-05:02 1.82
September 0.453198E+11 0.36 203125.57 05-SEP-05:02 1.82
October 0.349541E+11 0.31 106610.03 19-OCT-05:03 1.21
November 0.283959E+11 0.29 112935.04 07-NOV-06:02 1.27
December 0.271162E+11 0.29 72216.39 14-DEC-06:03 0.97
           
Annual Sum or Average 0.478020E+12 0.34      
Minimum of Months 0.271162E+11 0.29 72216.39   0.97
Maximum of Months 0.620613E+11 0.43 203125.57   1.82



Table of Contents

Report: FanReportMonthly

For: VAV_TOP WITH REHEAT FAN

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.362515E+10 0.37 4566.97 02-JAN-05:21 0.72
February 0.297419E+10 0.34 4566.97 02-FEB-06:02 0.72
March 0.316029E+10 0.31 7913.07 29-MAR-05:03 0.96
April 0.340795E+10 0.31 8405.49 17-APR-14:40 1.00
May 0.446797E+10 0.35 12872.50 30-MAY-05:03 1.30
June 0.582535E+10 0.41 21911.26 13-JUN-05:02 1.81
July 0.608836E+10 0.41 21911.26 05-JUL-04:12 1.81
August 0.668440E+10 0.43 21911.26 05-AUG-04:12 1.81
September 0.441418E+10 0.35 21911.26 07-SEP-05:02 1.81
October 0.325250E+10 0.30 9224.16 18-OCT-05:02 1.06
November 0.274053E+10 0.29 4566.97 21-NOV-06:02 0.72
December 0.316605E+10 0.33 4566.97 01-DEC-06:02 0.72
           
Annual Sum or Average 0.498069E+11 0.35      
Minimum of Months 0.274053E+10 0.29 4566.97   0.72
Maximum of Months 0.668440E+10 0.43 21911.26   1.81



Table of Contents

Report: FanReportMonthly

For: AIRLOOP DATACENTER BASEMENT SUPPLY FAN

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.977848E+11 1.40 36508.66 01-JAN-00:10 1.39
February 0.883218E+11 1.40 36508.66 01-FEB-00:10 1.39
March 0.977848E+11 1.39 36508.66 01-MAR-00:10 1.40
April 0.946305E+11 1.39 36508.66 01-APR-00:10 1.39
May 0.977848E+11 1.39 36508.66 01-MAY-00:03 1.39
June 0.946305E+11 1.39 36508.66 01-JUN-00:10 1.39
July 0.977848E+11 1.39 36508.66 01-JUL-00:10 1.39
August 0.977848E+11 1.39 36508.66 01-AUG-00:03 1.39
September 0.946305E+11 1.39 36508.66 01-SEP-00:03 1.39
October 0.977848E+11 1.39 36508.66 01-OCT-00:10 1.39
November 0.946305E+11 1.39 36508.66 01-NOV-00:10 1.40
December 0.977848E+11 1.40 36508.66 01-DEC-00:10 1.39
           
Annual Sum or Average 0.115134E+13 1.39      
Minimum of Months 0.883218E+11 1.39 36508.66   1.39
Maximum of Months 0.977848E+11 1.40 36508.66   1.40



Table of Contents

Report: FanReportMonthly

For: AIRLOOP DATACENTER BOT SUPPLY FAN

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.147651E+10 0.95 551.27 01-JAN-00:05 0.95
February 0.133363E+10 0.95 551.27 01-FEB-00:10 0.95
March 0.147651E+10 0.95 551.27 01-MAR-00:10 0.95
April 0.142889E+10 0.95 551.27 01-APR-00:10 0.95
May 0.147651E+10 0.95 551.27 01-MAY-00:03 0.95
June 0.142889E+10 0.95 551.27 01-JUN-00:10 0.95
July 0.147651E+10 0.95 551.27 01-JUL-00:10 0.95
August 0.147651E+10 0.94 551.27 01-AUG-00:03 0.95
September 0.142889E+10 0.95 551.27 01-SEP-00:03 0.95
October 0.147651E+10 0.95 551.27 01-OCT-00:10 0.95
November 0.142889E+10 0.95 551.27 01-NOV-00:10 0.95
December 0.147651E+10 0.95 551.27 01-DEC-00:10 0.95
           
Annual Sum or Average 0.173848E+11 0.95      
Minimum of Months 0.133363E+10 0.94 551.27   0.95
Maximum of Months 0.147651E+10 0.95 551.27   0.95



Table of Contents

Report: FanReportMonthly

For: AIRLOOP DATACENTER MID SUPPLY FAN

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.140759E+11 0.95 5255.32 01-JAN-00:05 0.95
February 0.127137E+11 0.95 5255.32 01-FEB-00:10 0.95
March 0.140759E+11 0.95 5255.32 01-MAR-00:10 0.95
April 0.136218E+11 0.95 5255.32 01-APR-00:10 0.95
May 0.140759E+11 0.95 5255.32 01-MAY-00:03 0.95
June 0.136218E+11 0.95 5255.32 01-JUN-00:10 0.95
July 0.140759E+11 0.95 5255.32 01-JUL-00:10 0.95
August 0.140759E+11 0.94 5255.32 01-AUG-00:03 0.95
September 0.136218E+11 0.94 5255.32 01-SEP-00:03 0.95
October 0.140759E+11 0.95 5255.32 01-OCT-00:10 0.95
November 0.136218E+11 0.95 5255.32 01-NOV-00:10 0.95
December 0.140759E+11 0.95 5255.32 01-DEC-00:10 0.95
           
Annual Sum or Average 0.165732E+12 0.95      
Minimum of Months 0.127137E+11 0.94 5255.32   0.95
Maximum of Months 0.140759E+11 0.95 5255.32   0.95



Table of Contents

Report: FanReportMonthly

For: AIRLOOP DATACENTER TOP SUPPLY FAN

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.143387E+10 0.95 535.34 01-JAN-00:05 0.95
February 0.129511E+10 0.95 535.34 01-FEB-00:10 0.95
March 0.143387E+10 0.95 535.34 01-MAR-00:10 0.95
April 0.138761E+10 0.95 535.34 01-APR-00:10 0.95
May 0.143387E+10 0.95 535.34 01-MAY-00:03 0.95
June 0.138761E+10 0.95 535.34 01-JUN-00:10 0.95
July 0.143387E+10 0.95 535.34 01-JUL-00:10 0.95
August 0.143387E+10 0.94 535.34 01-AUG-00:03 0.95
September 0.138761E+10 0.94 535.34 01-SEP-00:03 0.95
October 0.143387E+10 0.95 535.34 01-OCT-00:10 0.95
November 0.138761E+10 0.95 535.34 01-NOV-00:20 0.95
December 0.143387E+10 0.95 535.34 01-DEC-00:10 0.95
           
Annual Sum or Average 0.168826E+11 0.95      
Minimum of Months 0.129511E+10 0.94 535.34   0.95
Maximum of Months 0.143387E+10 0.95 535.34   0.95



Table of Contents

Report: PumpReportMonthly

For: HEATSYS1 PUMP

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

PUMP ELECTRICITY ENERGY [J] PUMP FLUID HEAT GAIN ENERGY [J] PUMP ELECTRICITY RATE {Maximum} [W] PUMP ELECTRICITY RATE {TIMESTAMP} PUMP SHAFT POWER {AT MAX/MIN} [W] PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s]
January 0.130260E+10 0.117234E+10 4990.39 09-JAN-06:03 4491.36 4491.36 49.51 11.40
February 0.737916E+09 0.664125E+09 4990.08 13-FEB-06:02 4491.07 4491.07 49.60 11.40
March 0.118708E+09 0.106837E+09 3988.95 23-MAR-05:02 3590.06 3590.06 34.18 6.39
April 32645315.37 29380783.83 3587.23 06-APR-05:03 3228.51 3228.51 33.95 5.31
May 3012892.32 2711603.09 260.87 15-MAY-18:40 234.78 234.78 37.73 0.27
June 388939.35 350045.42 126.86 10-JUN-13:10 114.17 114.17 37.65 0.13
July 0.00 0.00 0.00 01-JUL-00:10 0.00 0.00 41.86 0.00
August 0.00 0.00 0.00 01-AUG-00:03 0.00 0.00 41.86 0.00
September 727293.36 654564.03 159.99 14-SEP-15:50 143.99 143.99 40.56 0.16
October 61104158.78 54993742.90 3695.76 26-OCT-05:03 3326.18 3326.18 37.39 5.57
November 0.204455E+09 0.184009E+09 4248.53 22-NOV-06:03 3823.68 3823.68 46.65 7.21
December 0.609077E+09 0.548169E+09 4957.28 26-DEC-06:02 4461.55 4461.55 48.48 11.10
                 
Annual Sum or Average 0.307064E+10 0.276358E+10            
Minimum of Months 0.00 0.00 0.00   0.00 0.00 33.95 0.00
Maximum of Months 0.130260E+10 0.117234E+10 4990.39   4491.36 4491.36 49.60 11.40



Table of Contents

Report: PumpReportMonthly

For: COOLSYS1 PUMP SECONDARY

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

PUMP ELECTRICITY ENERGY [J] PUMP FLUID HEAT GAIN ENERGY [J] PUMP ELECTRICITY RATE {Maximum} [W] PUMP ELECTRICITY RATE {TIMESTAMP} PUMP SHAFT POWER {AT MAX/MIN} [W] PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s]
January 17337048.45 15603343.61 434.43 31-JAN-14:50 390.99 390.99 6.70 23.12
February 39962620.40 35966358.36 492.35 28-FEB-15:30 443.12 443.12 6.70 24.62
March 0.221621E+09 0.199459E+09 3413.46 30-MAR-15:10 3072.12 3072.12 6.71 60.19
April 0.659342E+09 0.593408E+09 7345.92 13-APR-14:30 6611.32 6611.32 7.69 83.15
May 0.132381E+10 0.119143E+10 14051.91 31-MAY-05:03 12646.72 12646.72 8.43 108.16
June 0.238730E+10 0.214857E+10 20715.12 14-JUN-05:03 18643.61 18643.61 8.92 126.12
July 0.277818E+10 0.250036E+10 19962.01 19-JUL-05:02 17965.81 17965.81 8.68 124.28
August 0.330033E+10 0.297030E+10 20715.12 12-AUG-05:02 18643.61 18643.61 8.65 126.12
September 0.177654E+10 0.159889E+10 20678.00 27-SEP-05:03 18610.20 18610.20 8.95 126.01
October 0.664975E+09 0.598478E+09 17420.87 19-OCT-05:03 15678.78 15678.78 8.71 117.79
November 0.110893E+09 99803947.38 937.25 04-NOV-05:03 843.53 843.53 6.70 33.62
December 37300854.42 33570768.98 578.01 12-DEC-14:00 520.21 520.21 6.70 26.65
                 
Annual Sum or Average 0.133176E+11 0.119858E+11            
Minimum of Months 17337048.45 15603343.61 434.43   390.99 390.99 6.70 23.12
Maximum of Months 0.330033E+10 0.297030E+10 20715.12   18643.61 18643.61 8.95 126.12



Table of Contents

Report: PumpReportMonthly

For: COOLSYS1 CHILLER1 PUMP

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

PUMP ELECTRICITY ENERGY [J] PUMP FLUID HEAT GAIN ENERGY [J] PUMP ELECTRICITY RATE {Maximum} [W] PUMP ELECTRICITY RATE {TIMESTAMP} PUMP SHAFT POWER {AT MAX/MIN} [W] PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s]
January 0.287349E+10 0.258614E+10 7128.83 01-JAN-01:10 6415.94 6415.94 6.72 63.06
February 0.463759E+10 0.417383E+10 7128.83 01-FEB-06:02 6415.94 6415.94 7.00 63.06
March 0.816493E+10 0.734844E+10 7128.83 01-MAR-05:12 6415.94 6415.94 7.33 63.06
April 0.106678E+11 0.960100E+10 7128.83 01-APR-04:12 6415.94 6415.94 6.87 63.06
May 0.118907E+11 0.107017E+11 7128.83 01-MAY-00:03 6415.94 6415.94 6.89 63.06
June 0.133584E+11 0.120225E+11 7128.83 01-JUN-04:12 6415.94 6415.94 11.21 63.06
July 0.154936E+11 0.139443E+11 7128.83 01-JUL-04:11 6415.94 6415.94 12.12 63.06
August 0.171378E+11 0.154240E+11 7128.83 01-AUG-00:03 6415.94 6415.94 6.90 63.06
September 0.118393E+11 0.106553E+11 7128.83 01-SEP-00:52 6415.94 6415.94 6.92 63.06
October 0.875656E+10 0.788091E+10 7128.83 01-OCT-12:22 6415.94 6415.94 7.68 63.06
November 0.658511E+10 0.592660E+10 7128.83 01-NOV-04:12 6415.94 6415.94 6.86 63.06
December 0.361597E+10 0.325437E+10 7128.83 01-DEC-04:08 6415.94 6415.94 6.72 63.06
                 
Annual Sum or Average 0.115021E+12 0.103519E+12            
Minimum of Months 0.287349E+10 0.258614E+10 7128.83   6415.94 6415.94 6.72 63.06
Maximum of Months 0.171378E+11 0.154240E+11 7128.83   6415.94 6415.94 12.12 63.06



Table of Contents

Report: PumpReportMonthly

For: COOLSYS1 CHILLER2 PUMP

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

PUMP ELECTRICITY ENERGY [J] PUMP FLUID HEAT GAIN ENERGY [J] PUMP ELECTRICITY RATE {Maximum} [W] PUMP ELECTRICITY RATE {TIMESTAMP} PUMP SHAFT POWER {AT MAX/MIN} [W] PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s]
January 0.00 0.00 0.00 01-JAN-00:05 0.00 0.00 6.72 0.00
February 0.00 0.00 0.00 01-FEB-00:10 0.00 0.00 7.16 0.00
March 17109186.03 15398267.42 7128.83 30-MAR-14:40 6415.94 6415.94 12.69 31.53
April 94100523.15 84690470.83 7128.83 04-APR-13:20 6415.94 6415.94 12.42 31.53
May 0.902510E+09 0.812259E+09 7128.83 03-MAY-13:30 6415.94 6415.94 12.46 31.53
June 0.368269E+10 0.331442E+10 7128.83 01-JUN-08:30 6415.94 6415.94 12.40 31.53
July 0.445474E+10 0.400927E+10 7128.83 01-JUL-04:13 6415.94 6415.94 12.95 31.53
August 0.575952E+10 0.518357E+10 7128.83 01-AUG-07:10 6415.94 6415.94 12.42 31.53
September 0.210635E+10 0.189572E+10 7128.83 01-SEP-10:00 6415.94 6415.94 12.42 31.53
October 0.608802E+09 0.547922E+09 7128.83 02-OCT-10:00 6415.94 6415.94 12.38 31.53
November 0.00 0.00 0.00 01-NOV-00:10 0.00 0.00 6.86 0.00
December 0.00 0.00 0.00 01-DEC-00:10 0.00 0.00 6.72 0.00
                 
Annual Sum or Average 0.176258E+11 0.158632E+11            
Minimum of Months 0.00 0.00 0.00   0.00 0.00 6.72 0.00
Maximum of Months 0.575952E+10 0.518357E+10 7128.83   6415.94 6415.94 12.95 31.53



Table of Contents

Report: PumpReportMonthly

For: PLANT CIRC PUMP

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

PUMP ELECTRICITY ENERGY [J] PUMP FLUID HEAT GAIN ENERGY [J] PUMP ELECTRICITY RATE {Maximum} [W] PUMP ELECTRICITY RATE {TIMESTAMP} PUMP SHAFT POWER {AT MAX/MIN} [W] PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s]
January 0.920265E+10 0.828238E+10 3435.87 01-JAN-00:05 3092.29 3092.29 21.55 14.35
February 0.831207E+10 0.748086E+10 3435.87 01-FEB-00:10 3092.29 3092.29 24.23 14.35
March 0.920265E+10 0.828238E+10 3435.87 01-MAR-00:10 3092.29 3092.29 28.06 14.35
April 0.890579E+10 0.801521E+10 3435.87 01-APR-00:10 3092.29 3092.29 30.19 14.35
May 0.920265E+10 0.828238E+10 3435.87 01-MAY-00:03 3092.29 3092.29 22.63 14.35
June 0.890579E+10 0.801521E+10 3435.87 01-JUN-00:10 3092.29 3092.29 30.76 14.35
July 0.920265E+10 0.828238E+10 3435.87 01-JUL-00:10 3092.29 3092.29 36.43 14.35
August 0.920265E+10 0.828238E+10 3435.87 01-AUG-00:03 3092.29 3092.29 43.92 14.35
September 0.890579E+10 0.801521E+10 3435.87 01-SEP-00:03 3092.29 3092.29 27.68 14.35
October 0.920265E+10 0.828238E+10 3435.87 01-OCT-00:10 3092.29 3092.29 26.05 14.35
November 0.890579E+10 0.801521E+10 3435.87 01-NOV-00:10 3092.29 3092.29 27.38 14.35
December 0.920265E+10 0.828238E+10 3435.87 01-DEC-00:10 3092.29 3092.29 29.69 14.35
                 
Annual Sum or Average 0.108354E+12 0.975184E+11            
Minimum of Months 0.831207E+10 0.748086E+10 3435.87   3092.29 3092.29 21.55 14.35
Maximum of Months 0.920265E+10 0.828238E+10 3435.87   3092.29 3092.29 43.92 14.35



Table of Contents

Report: PumpReportMonthly

For: SWHSYS1 PUMP

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

PUMP ELECTRICITY ENERGY [J] PUMP FLUID HEAT GAIN ENERGY [J] PUMP ELECTRICITY RATE {Maximum} [W] PUMP ELECTRICITY RATE {TIMESTAMP} PUMP SHAFT POWER {AT MAX/MIN} [W] PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s]
January 0.112905E+09 33871561.48 56.21 01-JAN-06:10 16.86 16.86 55.73 0.44
February 0.101979E+09 30593668.43 56.21 01-FEB-06:02 16.86 16.86 56.47 0.44
March 0.112905E+09 33871561.48 56.21 01-MAR-06:03 16.86 16.86 56.70 0.44
April 0.109263E+09 32778930.46 56.21 01-APR-05:02 16.86 16.86 55.79 0.44
May 0.112905E+09 33871561.48 56.21 01-MAY-05:03 16.86 16.86 57.31 0.44
June 0.109263E+09 32778930.46 56.21 01-JUN-05:03 16.86 16.86 56.98 0.44
July 0.112905E+09 33871561.48 56.21 01-JUL-05:03 16.86 16.86 57.05 0.44
August 0.112905E+09 33871561.48 56.21 01-AUG-05:03 16.86 16.86 57.01 0.44
September 0.109263E+09 32778930.46 56.21 01-SEP-05:03 16.86 16.86 57.03 0.44
October 0.112905E+09 33871561.48 56.21 01-OCT-05:10 16.86 16.86 56.52 0.44
November 0.109263E+09 32778930.46 56.21 01-NOV-05:03 16.86 16.86 57.10 0.44
December 0.112905E+09 33871561.48 56.21 01-DEC-06:01 16.86 16.86 56.07 0.44
                 
Annual Sum or Average 0.132937E+10 0.398810E+09            
Minimum of Months 0.101979E+09 30593668.43 56.21   16.86 16.86 55.73 0.44
Maximum of Months 0.112905E+09 33871561.48 56.21   16.86 16.86 57.31 0.44



Table of Contents

Report: PumpReportMonthly

For: TOWERWATERSYS PUMP

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

PUMP ELECTRICITY ENERGY [J] PUMP FLUID HEAT GAIN ENERGY [J] PUMP ELECTRICITY RATE {Maximum} [W] PUMP ELECTRICITY RATE {TIMESTAMP} PUMP SHAFT POWER {AT MAX/MIN} [W] PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s]
January 0.739055E+10 0.665150E+10 18355.67 19-JAN-16:00 16520.11 16520.11 22.97 74.29
February 0.119312E+11 0.107381E+11 18376.14 28-FEB-15:10 16538.53 16538.53 24.52 74.29
March 0.210586E+11 0.189527E+11 36787.33 30-MAR-15:20 33108.60 33108.60 25.72 148.58
April 0.276667E+11 0.249000E+11 36797.32 18-APR-12:40 33117.59 33117.59 26.05 148.58
May 0.327991E+11 0.295192E+11 36862.20 31-MAY-12:50 33175.98 33175.98 28.15 148.58
June 0.433271E+11 0.389944E+11 36882.70 12-JUN-09:50 33194.43 33194.43 28.93 148.58
July 0.507242E+11 0.456517E+11 36882.70 05-JUL-08:70 33194.43 33194.43 28.94 148.58
August 0.581087E+11 0.522978E+11 36882.70 01-AUG-09:30 33194.43 33194.43 29.72 148.58
September 0.353353E+11 0.318018E+11 36882.70 05-SEP-12:10 33194.43 33194.43 28.83 148.58
October 0.238323E+11 0.214491E+11 36882.70 18-OCT-14:40 33194.43 33194.43 29.00 148.58
November 0.169456E+11 0.152510E+11 18385.84 02-NOV-13:10 16547.25 16547.25 25.22 74.29
December 0.927982E+10 0.835184E+10 18371.36 12-DEC-14:00 16534.22 16534.22 24.16 74.29
                 
Annual Sum or Average 0.338399E+12 0.304559E+12            
Minimum of Months 0.739055E+10 0.665150E+10 18355.67   16520.11 16520.11 22.97 74.29
Maximum of Months 0.581087E+11 0.522978E+11 36882.70   33194.43 33194.43 29.72 148.58



Table of Contents

Report: CondLoopDemandReportMonthly

For: HEATSYS1

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 0.00 0.00 01-JAN-00:05 28.49 82.00 107759.68 1701386.63 02-JAN-06:01
February 0.00 0.00 01-FEB-00:10 18.65 18.65 68032.45 1636699.86 06-FEB-06:02
March 0.00 0.00 01-MAR-00:10 19.20 19.20 11006.38 1531292.97 22-MAR-04:11
April 0.00 0.00 01-APR-00:10 25.20 25.20 2869.38 1066652.84 06-APR-05:03
May 0.00 0.00 01-MAY-00:03 21.33 21.33 243.99 51824.29 10-MAY-06:10
June 0.00 0.00 01-JUN-00:10 35.23 35.23 28.29 24086.49 10-JUN-13:10
July 0.00 0.00 01-JUL-00:10 41.86 41.86 0.00 0.00 01-JUL-00:10
August 0.00 0.00 01-AUG-00:03 41.86 41.86 0.00 0.00 01-AUG-00:03
September 0.00 0.00 01-SEP-00:03 41.86 41.86 50.61 28418.50 14-SEP-15:50
October 0.00 0.00 01-OCT-00:10 35.13 35.13 5847.03 1092865.74 31-OCT-05:03
November 0.00 0.00 01-NOV-00:10 18.64 18.64 18885.44 1439935.14 25-NOV-05:01
December 0.00 0.00 01-DEC-00:10 25.82 25.82 51478.09 1556218.68 26-DEC-06:02
                 
Annual Sum or Average 0.00         21989.89    
Minimum of Months 0.00 0.00   18.64 18.64 0.00 0.00  
Maximum of Months 0.00 0.00   41.86 82.00 107759.68 1701386.63  



Table of Contents

Report: CondLoopDemandReportMonthly

For: COOLSYS1_SUPPLY

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 17009.14 488358.06 19-JAN-16:00 8.55 6.70 0.00 0.00 01-JAN-00:05
February 54701.82 921414.49 28-FEB-15:10 10.19 6.70 0.00 0.00 01-FEB-00:10
March 141123.94 1671097.78 30-MAR-15:20 9.86 6.70 0.00 0.00 01-MAR-00:10
April 267702.78 1906410.30 19-APR-14:50 10.31 8.12 0.00 0.00 01-APR-00:10
May 490744.05 1801466.89 23-MAY-13:50 10.11 6.70 0.00 0.00 01-MAY-00:03
June 709297.85 2392722.91 29-JUN-05:04 11.23 6.70 0.00 0.00 01-JUN-00:10
July 778281.20 2174380.29 01-JUL-04:14 10.81 6.70 0.00 0.00 01-JUL-00:10
August 870530.71 2626680.08 23-AUG-05:02 11.67 6.70 0.00 0.00 01-AUG-00:03
September 577925.15 1995435.85 16-SEP-16:07 10.48 6.70 0.00 0.00 01-SEP-00:03
October 252402.85 2203332.40 19-OCT-04:15 10.87 6.70 0.00 0.00 01-OCT-00:10
November 100922.14 954441.18 02-NOV-13:10 10.31 6.70 0.00 0.00 01-NOV-00:10
December 34607.14 822898.89 12-DEC-14:00 9.81 6.70 0.00 0.00 01-DEC-00:10
                 
Annual Sum or Average 359815.78         0.00    
Minimum of Months 17009.14 488358.06   8.55 6.70 0.00 0.00  
Maximum of Months 870530.71 2626680.08   11.67 8.12 0.00 0.00  



Table of Contents

Report: CondLoopDemandReportMonthly

For: COOLSYS1_DEMAND

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 16055.10 516312.01 31-JAN-15:10 12.33 6.70 0.00 0.00 01-JAN-00:05
February 53010.66 919275.08 28-FEB-15:00 15.72 6.70 0.00 0.00 01-FEB-00:10
March 138450.63 1668459.68 30-MAR-15:10 13.32 6.70 0.00 0.00 01-MAR-00:10
April 264660.88 2148705.67 17-APR-13:30 13.66 7.70 0.00 0.00 01-APR-00:10
May 487045.83 3161330.38 31-MAY-05:03 13.68 9.60 0.00 0.00 01-MAY-00:03
June 706507.76 3877694.25 23-JUN-05:03 14.04 10.36 0.00 0.00 01-JUN-00:10
July 774668.38 3697342.95 14-JUL-04:12 13.89 10.19 0.00 0.00 01-JUL-00:10
August 866204.06 3967123.13 12-AUG-05:02 14.21 10.45 0.00 0.00 01-AUG-00:03
September 575205.69 3790786.16 05-SEP-05:02 13.90 10.28 0.00 0.00 01-SEP-00:03
October 249339.60 3450528.93 19-OCT-05:03 13.70 9.94 0.00 0.00 01-OCT-00:10
November 98694.54 958289.25 04-NOV-05:03 13.51 6.70 0.00 0.00 01-NOV-00:10
December 33410.21 819965.94 12-DEC-14:00 14.05 6.70 0.00 0.00 01-DEC-00:10
                 
Annual Sum or Average 357141.79         0.00    
Minimum of Months 16055.10 516312.01   12.33 6.70 0.00 0.00  
Maximum of Months 866204.06 3967123.13   15.72 10.45 0.00 0.00  



Table of Contents

Report: CondLoopDemandReportMonthly

For: SINGLE WATER PLANT LOOP

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 164780.08 419385.64 31-JAN-15:00 26.70 22.84 0.00 0.00 01-JAN-00:05
February 338212.29 861722.75 28-FEB-15:00 35.39 28.26 0.00 0.00 01-FEB-00:10
March 577006.00 1257343.65 30-MAR-16:00 43.04 32.62 0.00 0.00 01-MAR-00:10
April 892545.52 1531128.30 17-APR-16:00 48.28 35.06 0.00 0.00 01-APR-00:10
May 438384.66 967370.60 30-MAY-15:00 37.45 32.75 0.00 0.00 01-MAY-00:03
June 859896.46 1416932.73 06-JUN-15:00 46.10 38.11 0.00 0.00 01-JUN-00:10
July 1153484.39 1776718.29 08-JUL-16:00 52.93 41.89 0.00 0.00 01-JUL-00:10
August 1401418.32 1887269.42 01-AUG-16:10 55.02 41.41 0.00 0.00 01-AUG-00:03
September 520479.85 1042735.33 07-SEP-16:00 38.91 33.97 0.00 0.00 01-SEP-00:03
October 470403.28 1165752.88 10-OCT-16:00 41.28 33.56 0.00 0.00 01-OCT-00:10
November 539997.72 1036569.58 05-NOV-16:00 38.79 28.93 0.00 0.00 01-NOV-00:10
December 617356.57 1186294.93 12-DEC-15:00 41.68 28.76 0.00 0.00 01-DEC-00:10
                 
Annual Sum or Average 666754.42         0.00    
Minimum of Months 164780.08 419385.64   26.70 22.84 0.00 0.00  
Maximum of Months 1401418.32 1887269.42   55.02 41.89 0.00 0.00  



Table of Contents

Report: CondLoopDemandReportMonthly

For: SWHSYS1

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 0.00 0.00 01-JAN-00:05 56.55 56.55 14850.00 49687.18 30-JAN-12:40
February 0.00 0.00 01-FEB-00:10 57.00 57.00 14960.05 49691.65 01-FEB-12:40
March 0.00 0.00 01-MAR-00:10 57.24 57.24 15317.31 48919.31 01-MAR-12:50
April 0.00 0.00 01-APR-00:10 56.29 56.29 13611.95 46270.62 03-APR-11:50
May 0.00 0.00 01-MAY-00:03 58.03 58.03 13012.53 43150.94 01-MAY-11:40
June 0.00 0.00 01-JUN-00:10 57.47 57.47 12345.19 39646.21 01-JUN-11:30
July 0.00 0.00 01-JUL-00:10 57.49 57.49 10959.34 36965.52 03-JUL-12:00
August 0.00 0.00 01-AUG-00:03 57.39 57.39 11824.71 36815.48 31-AUG-11:50
September 0.00 0.00 01-SEP-00:03 57.43 57.43 11655.39 39093.32 29-SEP-11:30
October 0.00 0.00 01-OCT-00:10 57.38 57.38 12475.73 42640.11 31-OCT-12:00
November 0.00 0.00 01-NOV-00:10 57.45 57.45 13623.08 46035.21 30-NOV-13:00
December 0.00 0.00 01-DEC-00:10 56.45 56.45 14016.97 48586.36 29-DEC-12:15
                 
Annual Sum or Average 0.00         13211.24    
Minimum of Months 0.00 0.00   56.29 56.29 10959.34 36815.48  
Maximum of Months 0.00 0.00   58.03 58.03 15317.31 49691.65  



Table of Contents

Report: CondLoopDemandReportMonthly

For: TOWERWATERSYS

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 19123.76 581447.72 19-JAN-16:00 22.97 21.10 4167.44 172700.19 06-JAN-12:20
February 63714.38 1062309.43 28-FEB-15:10 24.52 21.10 3556.55 190795.46 12-FEB-04:02
March 170952.14 2870371.58 30-MAR-15:20 25.72 21.83 2367.55 175814.57 06-MAR-07:30
April 337949.50 3071546.89 18-APR-12:40 26.05 21.82 960.77 109042.00 25-APR-20:00
May 759604.36 4375444.07 31-MAY-12:50 28.15 24.98 119.99 77238.55 09-MAY-21:00
June 1558598.35 5563746.26 27-JUN-12:10 30.06 26.81 108.53 83178.82 10-JUN-06:30
July 1960824.18 5919948.60 07-JUL-12:10 30.63 27.45 0.00 0.00 01-JUL-00:10
August 2363658.45 6143653.85 10-AUG-16:00 30.99 27.66 0.00 0.00 01-AUG-00:03
September 1127570.91 5424044.31 06-SEP-14:00 29.83 26.55 92.07 59446.62 14-SEP-06:50
October 401795.52 5016578.85 18-OCT-16:00 29.18 25.99 1177.66 126607.26 25-OCT-11:00
November 117614.70 1278596.61 02-NOV-13:10 25.22 21.70 2376.44 164125.37 21-NOV-07:00
December 35999.26 949970.27 12-DEC-14:00 24.16 21.10 2955.42 184336.09 01-DEC-09:30
                 
Annual Sum or Average 748237.52         1479.86    
Minimum of Months 19123.76 581447.72   22.97 21.10 0.00 0.00  
Maximum of Months 2363658.45 6143653.85   30.99 27.66 4167.44 190795.46  



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: BASEMENT

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: CORE_BOTTOM

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: CORE_MID

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: CORE_TOP

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: GROUNDFLOOR_PLENUM

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00 0.00
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: MIDFLOOR_PLENUM

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00 0.00
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: TOPFLOOR_PLENUM

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00 0.00
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: DATACENTER_MID_ZN_6

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: VAV_BOT WITH REHEAT

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.517093E+10 0.00 0.418628E+10 0.294665E+10 0.00 0.00
February 0.231027E+10 0.00 0.129807E+11 0.317851E+10 0.00 0.00
March 0.241335E+09 0.00 0.371894E+11 0.477753E+10 0.00 0.00
April 0.193001E+09 0.00 0.709594E+11 0.550538E+10 0.00 0.00
May 16828398.72 0.00 0.108026E+12 0.530270E+10 0.00 0.00
June 3975658.35 0.00 0.153777E+12 0.678805E+10 0.00 0.00
July 0.00 0.00 0.182750E+12 0.746000E+10 0.00 0.00
August 0.00 0.00 0.212940E+12 0.891571E+10 0.00 0.00
September 3131721.70 0.00 0.123099E+12 0.556656E+10 0.00 0.00
October 0.104302E+09 0.00 0.608539E+11 0.491238E+10 0.00 0.00
November 0.428846E+09 0.00 0.271954E+11 0.427493E+10 0.00 0.00
December 0.125543E+10 0.00 0.103734E+11 0.383480E+10 0.00 0.00
             
Annual Sum or Average 0.972805E+10 0.00 0.100433E+13 0.634632E+11 0.00 0.00
Minimum of Months 0.00 0.00 0.418628E+10 0.294665E+10 0.00 0.00
Maximum of Months 0.517093E+10 0.00 0.212940E+12 0.891571E+10 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: VAV_MID WITH REHEAT

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.239776E+12 0.00 0.349320E+11 0.291286E+11 0.00 0.00
February 0.137032E+12 0.00 0.101155E+12 0.272292E+11 0.00 0.00
March 0.236391E+11 0.00 0.282113E+12 0.332390E+11 0.00 0.00
April 0.564171E+10 0.00 0.509438E+12 0.359464E+11 0.00 0.00
May 0.432344E+09 0.00 0.944928E+12 0.439145E+11 0.00 0.00
June 32653803.07 0.00 0.131898E+13 0.545407E+11 0.00 0.00
July 0.00 0.00 0.149738E+13 0.561742E+11 0.00 0.00
August 0.00 0.00 0.167177E+13 0.620613E+11 0.00 0.00
September 70818297.44 0.00 0.107676E+13 0.453198E+11 0.00 0.00
October 0.117939E+11 0.00 0.481617E+12 0.349541E+11 0.00 0.00
November 0.381775E+11 0.00 0.196320E+12 0.283959E+11 0.00 0.00
December 0.109672E+12 0.00 0.683327E+11 0.271162E+11 0.00 0.00
             
Annual Sum or Average 0.566268E+12 0.00 0.818373E+13 0.478020E+12 0.00 0.00
Minimum of Months 0.00 0.00 0.349320E+11 0.271162E+11 0.00 0.00
Maximum of Months 0.239776E+12 0.00 0.167177E+13 0.620613E+11 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: VAV_TOP WITH REHEAT

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.463670E+11 0.00 0.349096E+10 0.362515E+10 0.00 0.00
February 0.267361E+11 0.00 0.973973E+10 0.297419E+10 0.00 0.00
March 0.583080E+10 0.00 0.277521E+11 0.316029E+10 0.00 0.00
April 0.169135E+10 0.00 0.522745E+11 0.340795E+10 0.00 0.00
May 0.134679E+09 0.00 0.101586E+12 0.446797E+10 0.00 0.00
June 1316040.15 0.00 0.144690E+12 0.582535E+10 0.00 0.00
July 0.00 0.00 0.163866E+12 0.608836E+10 0.00 0.00
August 0.00 0.00 0.181702E+12 0.668440E+10 0.00 0.00
September 95198126.71 0.00 0.110976E+12 0.441418E+10 0.00 0.00
October 0.398533E+10 0.00 0.483804E+11 0.325250E+10 0.00 0.00
November 0.107389E+11 0.00 0.183911E+11 0.274053E+10 0.00 0.00
December 0.282137E+11 0.00 0.670704E+10 0.316605E+10 0.00 0.00
             
Annual Sum or Average 0.123794E+12 0.00 0.869555E+12 0.498069E+11 0.00 0.00
Minimum of Months 0.00 0.00 0.349096E+10 0.274053E+10 0.00 0.00
Maximum of Months 0.463670E+11 0.00 0.181702E+12 0.668440E+10 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: CAV_BAS

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.00 0.00 0.577388E+09 0.153072E+11 0.00 0.00
February 0.00 0.00 0.423326E+10 0.136018E+11 0.00 0.00
March 0.00 0.00 0.135794E+11 0.161156E+11 0.00 0.00
April 0.00 0.00 0.290157E+11 0.147431E+11 0.00 0.00
May 0.00 0.00 0.516525E+11 0.155883E+11 0.00 0.00
June 0.00 0.00 0.893055E+11 0.155171E+11 0.00 0.00
July 0.00 0.00 0.100403E+12 0.153962E+11 0.00 0.00
August 0.00 0.00 0.120344E+12 0.171714E+11 0.00 0.00
September 0.00 0.00 0.758328E+11 0.162821E+11 0.00 0.00
October 0.00 0.00 0.329230E+11 0.161420E+11 0.00 0.00
November 0.00 0.00 0.105310E+11 0.157980E+11 0.00 0.00
December 0.00 0.00 0.307062E+10 0.152441E+11 0.00 0.00
             
Annual Sum or Average 0.00 0.00 0.531468E+12 0.186907E+12 0.00 0.00
Minimum of Months 0.00 0.00 0.577388E+09 0.136018E+11 0.00 0.00
Maximum of Months 0.00 0.00 0.120344E+12 0.171714E+11 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: AIRLOOP DATACENTER BASEMENT

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.00 0.00 0.404237E+12 0.181879E+12 0.00 0.97
February 0.00 0.00 0.638957E+12 0.215302E+12 0.00 0.68
March 0.00 0.00 0.102085E+13 0.299815E+12 0.00 0.35
April 0.00 0.00 0.129951E+13 0.362962E+12 0.00 0.11
May 0.00 0.00 0.439737E+12 0.196209E+12 0.00 0.02
June 0.00 0.00 0.755878E+12 0.276621E+12 0.00 0.01
July 0.00 0.00 0.111500E+13 0.371789E+12 0.00 0.00
August 0.00 0.00 0.143165E+13 0.448150E+12 0.00 0.00
September 0.00 0.00 0.439940E+12 0.196076E+12 0.00 0.00
October 0.00 0.00 0.735762E+12 0.249030E+12 0.00 0.02
November 0.00 0.00 0.990110E+12 0.287501E+12 0.00 0.45
December 0.00 0.00 0.130461E+13 0.339088E+12 0.00 0.72
             
Annual Sum or Average 0.00 0.00 0.105762E+14 0.342442E+13 0.00 3.33
Minimum of Months 0.00 0.00 0.404237E+12 0.181879E+12 0.00 0.00
Maximum of Months 0.00 0.00 0.143165E+13 0.448150E+12 0.00 0.97



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: AIRLOOP DATACENTER BOT

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.00 0.00 0.465160E+10 0.246177E+10 0.00 0.00
February 0.00 0.00 0.107288E+11 0.348406E+10 0.00 0.00
March 0.00 0.00 0.194705E+11 0.531880E+10 0.00 0.00
April 0.00 0.00 0.255702E+11 0.666346E+10 0.00 0.00
May 0.00 0.00 0.791182E+10 0.322737E+10 0.00 0.00
June 0.00 0.00 0.147720E+11 0.493122E+10 0.00 0.00
July 0.00 0.00 0.221424E+11 0.683188E+10 0.00 0.00
August 0.00 0.00 0.290017E+11 0.853779E+10 0.00 0.00
September 0.00 0.00 0.799851E+10 0.324934E+10 0.00 0.00
October 0.00 0.00 0.135826E+11 0.424172E+10 0.00 0.00
November 0.00 0.00 0.186361E+11 0.505856E+10 0.00 0.00
December 0.00 0.00 0.247049E+11 0.607389E+10 0.00 0.00
             
Annual Sum or Average 0.00 0.00 0.199171E+12 0.600799E+11 0.00 0.00
Minimum of Months 0.00 0.00 0.465160E+10 0.246177E+10 0.00 0.00
Maximum of Months 0.00 0.00 0.290017E+11 0.853779E+10 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: AIRLOOP DATACENTER MID

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.00 0.00 0.149924E+11 0.174414E+11 0.00 0.00
February 0.00 0.00 0.788274E+11 0.288165E+11 0.00 0.00
March 0.00 0.00 0.172583E+12 0.484318E+11 0.00 0.00
April 0.00 0.00 0.237070E+12 0.623756E+11 0.00 0.00
May 0.00 0.00 0.702664E+11 0.297384E+11 0.00 0.00
June 0.00 0.00 0.138790E+12 0.465920E+11 0.00 0.00
July 0.00 0.00 0.210471E+12 0.650099E+11 0.00 0.00
August 0.00 0.00 0.276066E+12 0.813106E+11 0.00 0.00
September 0.00 0.00 0.705890E+11 0.298062E+11 0.00 0.00
October 0.00 0.00 0.116783E+12 0.381083E+11 0.00 0.00
November 0.00 0.00 0.159460E+12 0.450367E+11 0.00 0.00
December 0.00 0.00 0.207151E+12 0.532099E+11 0.00 0.00
             
Annual Sum or Average 0.00 0.00 0.175305E+13 0.545877E+12 0.00 0.00
Minimum of Months 0.00 0.00 0.149924E+11 0.174414E+11 0.00 0.00
Maximum of Months 0.00 0.00 0.276066E+12 0.813106E+11 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: AIRLOOP DATACENTER TOP

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.00 0.00 0.799858E+09 0.161216E+10 0.00 0.00
February 0.00 0.00 0.658263E+10 0.265248E+10 0.00 0.00
March 0.00 0.00 0.162993E+11 0.470566E+10 0.00 0.00
April 0.00 0.00 0.232082E+11 0.618861E+10 0.00 0.00
May 0.00 0.00 0.692040E+10 0.298528E+10 0.00 0.00
June 0.00 0.00 0.139675E+11 0.471326E+10 0.00 0.00
July 0.00 0.00 0.211969E+11 0.657313E+10 0.00 0.00
August 0.00 0.00 0.277896E+11 0.821479E+10 0.00 0.00
September 0.00 0.00 0.685018E+10 0.296864E+10 0.00 0.00
October 0.00 0.00 0.107524E+11 0.367055E+10 0.00 0.00
November 0.00 0.00 0.144812E+11 0.427186E+10 0.00 0.00
December 0.00 0.00 0.188210E+11 0.503012E+10 0.00 0.00
             
Annual Sum or Average 0.00 0.00 0.167669E+12 0.535865E+11 0.00 0.00
Minimum of Months 0.00 0.00 0.799858E+09 0.161216E+10 0.00 0.00
Maximum of Months 0.00 0.00 0.277896E+11 0.821479E+10 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: VAV_BOT WITH REHEAT

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.294665E+10 0.418628E+10 0.517093E+10 0.219159E+11 0.00 0.00 0.00 0.00
February 0.317851E+10 0.129807E+11 0.231027E+10 0.110953E+11 0.00 0.00 0.00 0.00
March 0.477753E+10 0.371894E+11 0.241335E+09 0.124455E+10 0.288708E+09 0.00 0.00 0.00
April 0.550538E+10 0.709594E+11 0.193001E+09 0.381926E+09 0.593199E+09 0.00 0.00 0.00
May 0.530270E+10 0.108026E+12 16828398.72 20702869.22 0.586447E+10 0.00 0.00 0.00
June 0.678805E+10 0.153777E+12 3975658.35 0.00 0.266036E+11 0.00 0.00 0.00
July 0.746000E+10 0.182750E+12 0.00 0.00 0.350468E+11 0.00 0.00 0.00
August 0.891571E+10 0.212940E+12 0.00 0.00 0.429384E+11 0.00 0.00 0.00
September 0.556656E+10 0.123099E+12 3131721.70 0.00 0.127434E+11 0.00 0.00 0.00
October 0.491238E+10 0.608539E+11 0.104302E+09 0.466104E+09 0.238418E+10 0.00 0.00 0.00
November 0.427493E+10 0.271954E+11 0.428846E+09 0.254092E+10 0.00 0.00 0.00 0.00
December 0.383480E+10 0.103734E+11 0.125543E+10 0.551441E+10 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.634632E+11 0.100433E+13 0.972805E+10 0.431798E+11 0.126463E+12 0.00 0.00 0.00
Minimum of Months 0.294665E+10 0.418628E+10 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.891571E+10 0.212940E+12 0.517093E+10 0.219159E+11 0.429384E+11 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: VAV_MID WITH REHEAT

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.291286E+11 0.349320E+11 0.239776E+12 0.250737E+12 0.00 0.00 0.00 0.00
February 0.272292E+11 0.101156E+12 0.137032E+12 0.139373E+12 0.00 0.00 0.00 0.00
March 0.332390E+11 0.282113E+12 0.236391E+11 0.246696E+11 0.381183E+10 0.00 0.00 0.00
April 0.359464E+11 0.509438E+12 0.564171E+10 0.740231E+10 0.704296E+10 0.00 0.00 0.00
May 0.439145E+11 0.944928E+12 0.432344E+09 0.322125E+09 0.605772E+11 0.00 0.00 0.00
June 0.545407E+11 0.131898E+13 32653803.07 0.00 0.264944E+12 0.00 0.00 0.00
July 0.561742E+11 0.149738E+13 0.00 0.00 0.348924E+12 0.00 0.00 0.00
August 0.620613E+11 0.167177E+13 0.00 0.00 0.422334E+12 0.00 0.00 0.00
September 0.453198E+11 0.107676E+13 70818297.44 0.00 0.129927E+12 0.00 0.00 0.00
October 0.349541E+11 0.481617E+12 0.117939E+11 0.108467E+11 0.257868E+11 0.00 0.00 0.00
November 0.283959E+11 0.196320E+12 0.381775E+11 0.522625E+11 0.00 0.00 0.00 0.00
December 0.271162E+11 0.683327E+11 0.109672E+12 0.974947E+11 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.478020E+12 0.818373E+13 0.566268E+12 0.583108E+12 0.126335E+13 0.00 0.00 0.00
Minimum of Months 0.271162E+11 0.349320E+11 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.620613E+11 0.167177E+13 0.239776E+12 0.250737E+12 0.422334E+12 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: VAV_TOP WITH REHEAT

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.362515E+10 0.349096E+10 0.463670E+11 0.268717E+11 0.00 0.00 0.00 0.00
February 0.297419E+10 0.973973E+10 0.267361E+11 0.147281E+11 0.00 0.00 0.00 0.00
March 0.316029E+10 0.277521E+11 0.583080E+10 0.315261E+10 0.196546E+09 0.00 0.00 0.00
April 0.340795E+10 0.522745E+11 0.169135E+10 0.873114E+09 0.289121E+09 0.00 0.00 0.00
May 0.446797E+10 0.101586E+12 0.134679E+09 35126206.38 0.450587E+10 0.00 0.00 0.00
June 0.582535E+10 0.144690E+12 1316040.15 0.00 0.248203E+11 0.00 0.00 0.00
July 0.608836E+10 0.163866E+12 0.00 0.00 0.335697E+11 0.00 0.00 0.00
August 0.668440E+10 0.181702E+12 0.00 0.00 0.409296E+11 0.00 0.00 0.00
September 0.441418E+10 0.110976E+12 95198126.71 0.00 0.122063E+11 0.00 0.00 0.00
October 0.325250E+10 0.483804E+11 0.398533E+10 0.127834E+10 0.158903E+10 0.00 0.00 0.00
November 0.274053E+10 0.183911E+11 0.107389E+11 0.559773E+10 0.00 0.00 0.00 0.00
December 0.316605E+10 0.670704E+10 0.282137E+11 0.101870E+11 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.498069E+11 0.869555E+12 0.123794E+12 0.627237E+11 0.118107E+12 0.00 0.00 0.00
Minimum of Months 0.274053E+10 0.349096E+10 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.668440E+10 0.181702E+12 0.463670E+11 0.268717E+11 0.409296E+11 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: CAV_BAS

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.153072E+11 0.577388E+09 0.00 0.00 0.00 0.00 0.00 0.00
February 0.136018E+11 0.423326E+10 0.00 0.00 0.00 0.00 0.00 0.00
March 0.161156E+11 0.135794E+11 0.00 0.00 0.00 0.00 0.00 0.00
April 0.147431E+11 0.290157E+11 0.00 0.00 0.00 0.00 0.00 0.00
May 0.155883E+11 0.516525E+11 0.00 0.00 0.00 0.00 0.00 0.00
June 0.155171E+11 0.893055E+11 0.00 0.00 0.00 0.00 0.00 0.00
July 0.153962E+11 0.100403E+12 0.00 0.00 0.00 0.00 0.00 0.00
August 0.171714E+11 0.120344E+12 0.00 0.00 0.00 0.00 0.00 0.00
September 0.162821E+11 0.758328E+11 0.00 0.00 0.00 0.00 0.00 0.00
October 0.161420E+11 0.329230E+11 0.00 0.00 0.00 0.00 0.00 0.00
November 0.157980E+11 0.105310E+11 0.00 0.00 0.00 0.00 0.00 0.00
December 0.152441E+11 0.307062E+10 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.186907E+12 0.531468E+12 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.136018E+11 0.577388E+09 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.171714E+11 0.120344E+12 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: AIRLOOP DATACENTER BASEMENT

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.977848E+11 0.322755E+12 0.00 0.00 0.00 0.260059E+10 0.00 0.00
February 0.883218E+11 0.513810E+12 0.00 0.00 0.00 0.182526E+10 0.00 0.00
March 0.977848E+11 0.819754E+12 0.00 0.00 0.00 0.933001E+09 0.00 0.00
April 0.946305E+11 0.103147E+13 0.00 0.00 0.00 0.293411E+09 0.00 0.00
May 0.977848E+11 0.341365E+12 0.00 0.00 0.00 51890100.47 0.00 0.00
June 0.946305E+11 0.573902E+12 0.00 0.00 0.00 14673193.97 0.00 0.00
July 0.977848E+11 0.840997E+12 0.00 0.00 0.00 0.00 0.00 0.00
August 0.977848E+11 0.108128E+13 0.00 0.00 0.00 0.00 0.00 0.00
September 0.946305E+11 0.338494E+12 0.00 0.00 0.00 0.00 0.00 0.00
October 0.977848E+11 0.584559E+12 0.00 0.00 0.00 41573922.38 0.00 0.00
November 0.946305E+11 0.798455E+12 0.00 0.00 0.00 0.121137E+10 0.00 0.00
December 0.977848E+11 0.106524E+13 0.00 0.00 0.00 0.192684E+10 0.00 0.00
                 
Annual Sum or Average 0.115134E+13 0.831209E+13 0.00 0.00 0.00 0.889861E+10 0.00 0.00
Minimum of Months 0.883218E+11 0.322755E+12 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.977848E+11 0.108128E+13 0.00 0.00 0.00 0.260059E+10 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: AIRLOOP DATACENTER BOT

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.147651E+10 0.366635E+10 0.00 0.00 0.00 0.00 0.00 0.00
February 0.133363E+10 0.857835E+10 0.00 0.00 0.00 0.00 0.00 0.00
March 0.147651E+10 0.156283E+11 0.00 0.00 0.00 0.00 0.00 0.00
April 0.142889E+10 0.203356E+11 0.00 0.00 0.00 0.00 0.00 0.00
May 0.147651E+10 0.616096E+10 0.00 0.00 0.00 0.00 0.00 0.00
June 0.142889E+10 0.112697E+11 0.00 0.00 0.00 0.00 0.00 0.00
July 0.147651E+10 0.167870E+11 0.00 0.00 0.00 0.00 0.00 0.00
August 0.147651E+10 0.219404E+11 0.00 0.00 0.00 0.00 0.00 0.00
September 0.142889E+10 0.617805E+10 0.00 0.00 0.00 0.00 0.00 0.00
October 0.147651E+10 0.108174E+11 0.00 0.00 0.00 0.00 0.00 0.00
November 0.142889E+10 0.150064E+11 0.00 0.00 0.00 0.00 0.00 0.00
December 0.147651E+10 0.201076E+11 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.173848E+11 0.156476E+12 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.133363E+10 0.366635E+10 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.147651E+10 0.219404E+11 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: AIRLOOP DATACENTER MID

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.140759E+11 0.116269E+11 0.00 0.00 0.00 0.00 0.00 0.00
February 0.127137E+11 0.627246E+11 0.00 0.00 0.00 0.00 0.00 0.00
March 0.140759E+11 0.138227E+12 0.00 0.00 0.00 0.00 0.00 0.00
April 0.136218E+11 0.188317E+12 0.00 0.00 0.00 0.00 0.00 0.00
May 0.140759E+11 0.546039E+11 0.00 0.00 0.00 0.00 0.00 0.00
June 0.136218E+11 0.105820E+12 0.00 0.00 0.00 0.00 0.00 0.00
July 0.140759E+11 0.159537E+12 0.00 0.00 0.00 0.00 0.00 0.00
August 0.140759E+11 0.208831E+12 0.00 0.00 0.00 0.00 0.00 0.00
September 0.136218E+11 0.544046E+11 0.00 0.00 0.00 0.00 0.00 0.00
October 0.140759E+11 0.927509E+11 0.00 0.00 0.00 0.00 0.00 0.00
November 0.136218E+11 0.128045E+12 0.00 0.00 0.00 0.00 0.00 0.00
December 0.140759E+11 0.168017E+12 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.165732E+12 0.137290E+13 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.127137E+11 0.116269E+11 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.140759E+11 0.208831E+12 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: AIRLOOP DATACENTER TOP

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.143387E+10 0.621563E+09 0.00 0.00 0.00 0.00 0.00 0.00
February 0.129511E+10 0.522525E+10 0.00 0.00 0.00 0.00 0.00 0.00
March 0.143387E+10 0.130275E+11 0.00 0.00 0.00 0.00 0.00 0.00
April 0.138761E+10 0.184072E+11 0.00 0.00 0.00 0.00 0.00 0.00
May 0.143387E+10 0.536898E+10 0.00 0.00 0.00 0.00 0.00 0.00
June 0.138761E+10 0.106418E+11 0.00 0.00 0.00 0.00 0.00 0.00
July 0.143387E+10 0.160576E+11 0.00 0.00 0.00 0.00 0.00 0.00
August 0.143387E+10 0.210087E+11 0.00 0.00 0.00 0.00 0.00 0.00
September 0.138761E+10 0.526916E+10 0.00 0.00 0.00 0.00 0.00 0.00
October 0.143387E+10 0.851575E+10 0.00 0.00 0.00 0.00 0.00 0.00
November 0.138761E+10 0.115970E+11 0.00 0.00 0.00 0.00 0.00 0.00
December 0.143387E+10 0.152248E+11 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.168826E+11 0.130965E+12 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.129511E+10 0.621563E+09 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.143387E+10 0.210087E+11 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: VAV_BOT WITH REHEAT

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.294665E+10 0.517093E+10 0.418628E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.317851E+10 0.231027E+10 0.129807E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.477753E+10 0.241335E+09 0.371894E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.550538E+10 0.193001E+09 0.709594E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.530270E+10 16828398.72 0.108026E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.678805E+10 3975658.35 0.153777E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.746000E+10 0.00 0.182750E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.891571E+10 0.00 0.212940E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.556656E+10 3131721.70 0.123099E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.491238E+10 0.104302E+09 0.608539E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.427493E+10 0.428846E+09 0.271954E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.383480E+10 0.125543E+10 0.103734E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.634632E+11 0.972805E+10 0.100433E+13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.294665E+10 0.00 0.418628E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.891571E+10 0.517093E+10 0.212940E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: VAV_MID WITH REHEAT

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.291286E+11 0.239776E+12 0.349320E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.272292E+11 0.137032E+12 0.101155E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.332390E+11 0.236391E+11 0.282113E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.359464E+11 0.564171E+10 0.509438E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.439145E+11 0.432344E+09 0.944928E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.545407E+11 32653803.07 0.131898E+13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.561742E+11 0.00 0.149738E+13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.620613E+11 0.00 0.167177E+13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.453198E+11 70818297.44 0.107676E+13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.349541E+11 0.117939E+11 0.481617E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.283959E+11 0.381775E+11 0.196320E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.271162E+11 0.109672E+12 0.683327E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.478020E+12 0.566268E+12 0.818373E+13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.271162E+11 0.00 0.349320E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.620613E+11 0.239776E+12 0.167177E+13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: VAV_TOP WITH REHEAT

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.362515E+10 0.463670E+11 0.349096E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.297419E+10 0.267361E+11 0.973973E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.316029E+10 0.583080E+10 0.277521E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.340795E+10 0.169135E+10 0.522745E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.446797E+10 0.134679E+09 0.101586E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.582535E+10 1316040.15 0.144690E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.608836E+10 0.00 0.163866E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.668440E+10 0.00 0.181702E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.441418E+10 95198126.71 0.110976E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.325250E+10 0.398533E+10 0.483804E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.274053E+10 0.107389E+11 0.183911E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.316605E+10 0.282137E+11 0.670704E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.498069E+11 0.123794E+12 0.869555E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.274053E+10 0.00 0.349096E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.668440E+10 0.463670E+11 0.181702E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: CAV_BAS

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.153072E+11 0.00 0.577388E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.136018E+11 0.00 0.423326E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.161156E+11 0.00 0.135794E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.147431E+11 0.00 0.290157E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.155883E+11 0.00 0.516525E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.155171E+11 0.00 0.893055E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.153962E+11 0.00 0.100403E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.171714E+11 0.00 0.120344E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.162821E+11 0.00 0.758328E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.161420E+11 0.00 0.329230E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.157980E+11 0.00 0.105310E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.152441E+11 0.00 0.307062E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.186907E+12 0.00 0.531468E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.136018E+11 0.00 0.577388E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.171714E+11 0.00 0.120344E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: AIRLOOP DATACENTER BASEMENT

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.977848E+11 0.00 0.404237E+12 0.00 0.814821E+11 0.00 0.00 0.00 0.261229E+10 0.00 0.00 0.00
February 0.883218E+11 0.00 0.638957E+12 0.00 0.125147E+12 0.00 0.00 0.00 0.183348E+10 0.00 0.00 0.00
March 0.977848E+11 0.00 0.102085E+13 0.00 0.201093E+12 0.00 0.00 0.00 0.937201E+09 0.00 0.00 0.00
April 0.946305E+11 0.00 0.129951E+13 0.00 0.268037E+12 0.00 0.00 0.00 0.294732E+09 0.00 0.00 0.00
May 0.977848E+11 0.00 0.439737E+12 0.00 0.983718E+11 0.00 0.00 0.00 52123678.84 0.00 0.00 0.00
June 0.946305E+11 0.00 0.755878E+12 0.00 0.181976E+12 0.00 0.00 0.00 14739243.96 0.00 0.00 0.00
July 0.977848E+11 0.00 0.111500E+13 0.00 0.274004E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.977848E+11 0.00 0.143165E+13 0.00 0.350365E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.946305E+11 0.00 0.439940E+12 0.00 0.101446E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.977848E+11 0.00 0.735762E+12 0.00 0.151203E+12 0.00 0.00 0.00 41761063.45 0.00 0.00 0.00
November 0.946305E+11 0.00 0.990110E+12 0.00 0.191654E+12 0.00 0.00 0.00 0.121683E+10 0.00 0.00 0.00
December 0.977848E+11 0.00 0.130461E+13 0.00 0.239368E+12 0.00 0.00 0.00 0.193551E+10 0.00 0.00 0.00
                         
Annual Sum or Average 0.115134E+13 0.00 0.105762E+14 0.00 0.226415E+13 0.00 0.00 0.00 0.893867E+10 0.00 0.00 0.00
Minimum of Months 0.883218E+11 0.00 0.404237E+12 0.00 0.814821E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.977848E+11 0.00 0.143165E+13 0.00 0.350365E+12 0.00 0.00 0.00 0.261229E+10 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: AIRLOOP DATACENTER BOT

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.147651E+10 0.00 0.465160E+10 0.00 0.985252E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.133363E+10 0.00 0.107288E+11 0.00 0.215044E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.147651E+10 0.00 0.194705E+11 0.00 0.384228E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.142889E+10 0.00 0.255702E+11 0.00 0.523457E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.147651E+10 0.00 0.791182E+10 0.00 0.175085E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.142889E+10 0.00 0.147720E+11 0.00 0.350234E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.147651E+10 0.00 0.221424E+11 0.00 0.535536E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.147651E+10 0.00 0.290017E+11 0.00 0.706128E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.142889E+10 0.00 0.799851E+10 0.00 0.182046E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.147651E+10 0.00 0.135826E+11 0.00 0.276521E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.142889E+10 0.00 0.186361E+11 0.00 0.362968E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.147651E+10 0.00 0.247049E+11 0.00 0.459738E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.173848E+11 0.00 0.199171E+12 0.00 0.426951E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.133363E+10 0.00 0.465160E+10 0.00 0.985252E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.147651E+10 0.00 0.290017E+11 0.00 0.706128E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: AIRLOOP DATACENTER MID

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.140759E+11 0.00 0.149924E+11 0.00 0.336553E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.127137E+11 0.00 0.788274E+11 0.00 0.161028E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.140759E+11 0.00 0.172583E+12 0.00 0.343559E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.136218E+11 0.00 0.237070E+12 0.00 0.487538E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.140759E+11 0.00 0.702664E+11 0.00 0.156625E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.136218E+11 0.00 0.138790E+12 0.00 0.329702E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.140759E+11 0.00 0.210471E+12 0.00 0.509340E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.140759E+11 0.00 0.276066E+12 0.00 0.672347E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.136218E+11 0.00 0.705890E+11 0.00 0.161844E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.140759E+11 0.00 0.116783E+12 0.00 0.240325E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.136218E+11 0.00 0.159460E+12 0.00 0.314149E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.140759E+11 0.00 0.207151E+12 0.00 0.391340E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.165732E+12 0.00 0.175305E+13 0.00 0.380145E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.127137E+11 0.00 0.149924E+11 0.00 0.336553E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.140759E+11 0.00 0.276066E+12 0.00 0.672347E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: AIRLOOP DATACENTER TOP

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.143387E+10 0.00 0.799858E+09 0.00 0.178295E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.129511E+10 0.00 0.658263E+10 0.00 0.135738E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.143387E+10 0.00 0.162993E+11 0.00 0.327179E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.138761E+10 0.00 0.232082E+11 0.00 0.480100E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.143387E+10 0.00 0.692040E+10 0.00 0.155142E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.138761E+10 0.00 0.139675E+11 0.00 0.332565E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.143387E+10 0.00 0.211969E+11 0.00 0.513926E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.143387E+10 0.00 0.277896E+11 0.00 0.678092E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.138761E+10 0.00 0.685018E+10 0.00 0.158102E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.143387E+10 0.00 0.107524E+11 0.00 0.223668E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.138761E+10 0.00 0.144812E+11 0.00 0.288425E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.143387E+10 0.00 0.188210E+11 0.00 0.359626E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.168826E+11 0.00 0.167669E+12 0.00 0.367039E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.129511E+10 0.00 0.799858E+09 0.00 0.178295E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.143387E+10 0.00 0.277896E+11 0.00 0.678092E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: BASEMENT

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.101900E+10 0.00 0.00 0.105820E+09 0.00 0.00 0.653207E+11 0.00 0.64
February 0.330723E+09 449176.32 0.00 94928724.33 0.00 0.00 0.578316E+11 0.00 0.87
March 0.150949E+09 0.107966E+09 0.00 0.113496E+09 670166.99 0.00 0.648323E+11 0.00 1.27
April 73321821.64 0.321667E+09 0.00 91661575.80 10030843.58 0.00 0.428988E+11 0.00 1.24
May 33795339.86 0.220005E+10 0.00 77506168.95 21605051.33 0.00 0.278055E+11 0.00 1.22
June 10244523.16 0.145259E+11 0.00 33388678.96 71580483.94 0.00 0.726278E+10 0.00 0.63
July 25015359.81 0.211916E+11 0.00 16152730.07 0.227921E+09 0.00 0.283546E+10 0.00 0.42
August 9405084.40 0.281582E+11 0.00 5889383.19 0.185172E+09 0.00 0.791382E+09 0.00 0.39
September 0.159215E+09 0.880009E+10 0.00 63747298.40 71545933.63 0.00 0.185187E+11 0.00 0.96
October 0.224534E+09 0.245005E+10 0.00 0.113123E+09 0.00 0.00 0.560769E+11 0.00 1.19
November 0.300342E+09 802498.52 0.00 0.138650E+09 0.00 0.00 0.731505E+11 0.00 1.26
December 0.482178E+09 0.00 0.00 0.135464E+09 0.00 0.00 0.744840E+11 0.00 0.93
                   
Annual Sum or Average 0.281873E+10 0.777568E+11 0.00 0.989828E+09 0.588525E+09 0.00 0.491808E+12 0.00 0.92
Minimum of Months 9405084.40 0.00 0.00 5889383.19 0.00 0.00 0.791382E+09 0.00 0.39
Maximum of Months 0.101900E+10 0.281582E+11 0.00 0.138650E+09 0.227921E+09 0.00 0.744840E+11 0.00 1.27



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: CORE_BOTTOM

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.144991E+11 0.00 0.00 46415631.92 0.00 0.00 0.289492E+11 0.00 0.50
February 0.877179E+10 0.00 0.00 57113447.95 0.00 0.00 0.312294E+11 0.00 0.61
March 0.411254E+10 0.244120E+09 0.00 92868929.30 406571.68 0.00 0.426588E+11 0.00 0.79
April 0.274881E+10 0.919056E+09 0.00 88702607.47 67574580.62 0.00 0.277810E+11 0.00 0.80
May 0.706555E+09 0.486296E+10 0.00 42677073.43 90257903.97 0.00 0.902903E+10 0.00 0.60
June 0.315377E+09 0.135287E+11 0.00 18238571.93 0.155556E+09 0.00 0.400054E+10 0.00 0.50
July 15912228.91 0.185859E+11 0.00 815707.57 0.406328E+09 0.00 21568629.94 0.00 0.38
August 0.00 0.233016E+11 0.00 0.00 0.215716E+09 0.00 0.00 0.00 0.41
September 0.340680E+09 0.108176E+11 0.00 34306787.52 0.302448E+09 0.00 0.638039E+10 0.00 0.55
October 0.125223E+10 0.408789E+10 0.00 74230729.98 27314227.34 0.00 0.333522E+11 0.00 0.68
November 0.208216E+10 0.274471E+09 0.00 93815634.48 27784916.62 0.00 0.445919E+11 0.00 0.73
December 0.339536E+10 11052516.58 0.00 89929754.46 0.00 0.00 0.477826E+11 0.00 0.63
                   
Annual Sum or Average 0.382405E+11 0.766334E+11 0.00 0.639115E+09 0.129339E+10 0.00 0.275777E+12 0.00 0.60
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.38
Maximum of Months 0.144991E+11 0.233016E+11 0.00 93815634.48 0.406328E+09 0.00 0.477826E+11 0.00 0.80



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: CORE_MID

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.334023E+12 0.00 0.00 9026289.66 0.190565E+09 0.326975E+10 0.184095E+11 0.00 0.48
February 0.246467E+12 0.00 0.00 92014225.46 0.00 0.203494E+10 0.563092E+11 0.00 0.52
March 0.130778E+12 0.130248E+10 0.00 0.374773E+09 0.805599E+09 0.00 0.199533E+12 0.00 0.61
April 0.625592E+11 0.681159E+10 0.00 0.423873E+09 0.293669E+10 0.00 0.151895E+12 0.00 0.62
May 0.164444E+11 0.432833E+11 0.00 0.258364E+09 0.451859E+10 0.00 0.653370E+11 0.00 0.55
June 0.454693E+10 0.128011E+12 0.00 0.117558E+09 0.481967E+10 0.00 0.311376E+11 0.00 0.48
July 0.169530E+09 0.172359E+12 0.00 5040012.76 0.122279E+11 0.00 0.229960E+09 0.00 0.38
August 21882970.72 0.221797E+12 0.00 8378952.15 0.813834E+10 0.00 44761612.29 0.00 0.42
September 0.949570E+10 0.946962E+11 0.00 0.217887E+09 0.126819E+11 0.00 0.467783E+11 0.00 0.52
October 0.876430E+11 0.350594E+11 0.00 0.319954E+09 0.320519E+10 0.00 0.163595E+12 0.00 0.55
November 0.134234E+12 0.707273E+09 0.00 0.294093E+09 0.335383E+10 0.00 0.173032E+12 0.00 0.54
December 0.262178E+12 24700114.97 0.00 86061920.22 0.00 41633170.62 0.731915E+11 0.00 0.49
                   
Annual Sum or Average 0.128856E+13 0.704052E+12 0.00 0.220702E+10 0.528782E+11 0.534632E+10 0.979493E+12 0.00 0.51
Minimum of Months 21882970.72 0.00 0.00 5040012.76 0.00 0.00 44761612.29 0.00 0.38
Maximum of Months 0.334023E+12 0.221797E+12 0.00 0.423873E+09 0.126819E+11 0.326975E+10 0.199533E+12 0.00 0.62



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: CORE_TOP

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.276033E+11 0.00 0.00 281951.57 19702421.96 0.363730E+10 0.382454E+09 0.00 0.49
February 0.237196E+11 0.00 0.00 3152817.27 1692341.95 0.135960E+10 0.185255E+10 0.00 0.51
March 0.192416E+11 0.106864E+09 0.00 17733968.69 67864604.28 52247763.72 0.936386E+10 0.00 0.58
April 0.879558E+10 0.575288E+09 0.00 31749370.91 0.352524E+09 0.00 0.101289E+11 0.00 0.60
May 0.242596E+10 0.412716E+10 0.00 21616360.17 0.668751E+09 0.00 0.464066E+10 0.00 0.54
June 0.941974E+09 0.129850E+11 0.00 10124200.07 0.317470E+09 0.00 0.227199E+10 0.00 0.48
July 8602387.56 0.172847E+11 0.00 354237.70 0.106986E+10 0.00 12251189.56 0.00 0.38
August 5947.66 0.224566E+11 0.00 0.00 0.328044E+09 0.00 0.00 0.00 0.42
September 0.165672E+10 0.868933E+10 0.00 17148842.89 0.210450E+10 0.00 0.294241E+10 0.00 0.51
October 0.136693E+11 0.368982E+10 0.00 13250298.16 0.484792E+09 29530077.42 0.761415E+10 0.00 0.52
November 0.220898E+11 266259.81 0.00 6580797.07 0.484253E+09 0.370712E+09 0.367214E+10 0.00 0.52
December 0.281610E+11 4070059.83 0.00 1769390.94 0.00 0.146825E+10 0.877486E+09 0.00 0.50
                   
Annual Sum or Average 0.148313E+12 0.699190E+11 0.00 0.123762E+09 0.589946E+10 0.691764E+10 0.437588E+11 0.00 0.50
Minimum of Months 5947.66 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.38
Maximum of Months 0.281610E+11 0.224566E+11 0.00 31749370.91 0.210450E+10 0.363730E+10 0.101289E+11 0.00 0.60



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.384064E+10 0.00 0.00 259021.66 0.00 0.863978E+09 0.179688E+09 0.00 0.45
February 0.341301E+10 0.00 0.00 1141663.58 0.00 0.293812E+09 0.548899E+09 0.00 0.52
March 0.277702E+10 34041146.64 0.00 3728352.76 51133.21 0.00 0.187012E+10 0.00 0.66
April 0.149578E+10 0.137253E+09 0.00 5660214.50 8498636.60 0.00 0.165899E+10 0.00 0.75
May 0.418589E+09 0.763428E+09 0.00 2897850.25 12550063.92 0.00 0.666715E+09 0.00 0.64
June 0.138814E+09 0.243804E+10 0.00 1709903.22 19563727.36 0.00 0.374718E+09 0.00 0.68
July 2591290.25 0.336761E+10 0.00 41934.49 51102543.29 0.00 1828583.84 0.00 0.55
August 0.00 0.400830E+10 0.00 0.00 27129843.19 0.00 0.00 0.00 0.58
September 0.305528E+09 0.155684E+10 0.00 2379377.13 38313063.99 0.00 0.421783E+09 0.00 0.58
October 0.203161E+10 0.543163E+09 0.00 2407015.40 3435222.09 0.00 0.130479E+10 0.00 0.56
November 0.291050E+10 26306272.71 0.00 2505039.97 8481743.19 23445406.04 0.138300E+10 0.00 0.55
December 0.421012E+10 1239430.61 0.00 907882.58 0.00 94932130.17 0.581842E+09 0.00 0.48
                   
Annual Sum or Average 0.215442E+11 0.128762E+11 0.00 23638255.53 0.169126E+09 0.127617E+10 0.899238E+10 0.00 0.58
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.45
Maximum of Months 0.421012E+10 0.400830E+10 0.00 5660214.50 51102543.29 0.863978E+09 0.187012E+10 0.00 0.75



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.353347E+10 0.00 0.00 124878.40 0.00 0.685894E+09 0.174228E+09 0.00 0.62
February 0.292530E+10 0.00 0.00 1683526.52 0.00 0.239690E+09 0.830163E+09 0.00 0.74
March 0.248815E+10 21637344.48 0.00 3974071.44 3738605.96 376917.98 0.199921E+10 0.00 0.94
April 0.133563E+10 87549845.32 0.00 6138805.72 10354542.40 0.00 0.191722E+10 0.00 1.09
May 0.387859E+09 0.632486E+09 0.00 3331424.48 34756520.20 0.00 0.819409E+09 0.00 0.95
June 0.141462E+09 0.192766E+10 0.00 1996633.46 18939204.27 0.00 0.446610E+09 0.00 0.89
July 2644300.55 0.269734E+10 0.00 9120.04 63974644.42 0.00 1046984.01 0.00 0.69
August 0.00 0.294878E+10 0.00 0.00 62259346.13 0.00 0.00 0.00 0.68
September 0.332003E+09 0.131492E+10 0.00 2373138.04 69215902.66 0.00 0.442369E+09 0.00 0.83
October 0.177092E+10 0.399761E+09 0.00 3122182.50 16995274.48 0.00 0.157231E+10 0.00 0.82
November 0.261332E+10 7473494.48 0.00 2144655.74 20712936.68 29347596.19 0.128499E+10 0.00 0.76
December 0.376762E+10 717349.01 0.00 766704.00 0.00 0.112513E+09 0.512085E+09 0.00 0.66
                   
Annual Sum or Average 0.192984E+11 0.100383E+11 0.00 25665140.33 0.300947E+09 0.106782E+10 0.999964E+10 0.00 0.81
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.62
Maximum of Months 0.376762E+10 0.294878E+10 0.00 6138805.72 69215902.66 0.685894E+09 0.199921E+10 0.00 1.09



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.267327E+10 0.00 0.00 4786404.97 0.00 0.786006E+09 0.299978E+10 0.00 0.57
February 0.255573E+10 0.00 0.00 6971240.62 0.00 0.259894E+09 0.297532E+10 0.00 0.75
March 0.223076E+10 49068997.11 0.00 9129526.37 52139.14 427055.04 0.405838E+10 0.00 0.95
April 0.151588E+10 0.151580E+09 0.00 8198566.82 8665829.33 0.00 0.223358E+10 0.00 0.95
May 0.508005E+09 0.841848E+09 0.00 2895990.56 15617793.71 0.00 0.642247E+09 0.00 0.71
June 0.204712E+09 0.244208E+10 0.00 1478228.40 19948602.39 0.00 0.292481E+09 0.00 0.68
July 2683031.55 0.343320E+10 0.00 35103.63 54639906.37 0.00 1694201.40 0.00 0.57
August 0.00 0.452746E+10 0.00 0.00 27663565.57 0.00 0.00 0.00 0.67
September 0.320567E+09 0.194977E+10 0.00 3676755.27 39582794.95 0.00 0.559458E+09 0.00 0.78
October 0.155666E+10 0.721265E+09 0.00 8970598.55 4503173.40 0.00 0.372159E+10 0.00 0.94
November 0.199718E+10 23451877.66 0.00 11371052.49 12688282.81 38564034.54 0.469575E+10 0.00 0.92
December 0.277962E+10 1399896.62 0.00 8375833.62 0.00 0.174292E+09 0.453659E+10 0.00 0.76
                   
Annual Sum or Average 0.163451E+11 0.141411E+11 0.00 65889301.29 0.183362E+09 0.125918E+10 0.267169E+11 0.00 0.77
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.57
Maximum of Months 0.277962E+10 0.452746E+10 0.00 11371052.49 54639906.37 0.786006E+09 0.469575E+10 0.00 0.95



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.461399E+10 0.00 0.00 844530.57 0.00 0.273996E+09 0.708400E+09 0.00 0.79
February 0.324862E+10 0.00 0.00 3378919.96 0.00 61070993.61 0.176582E+10 0.00 0.98
March 0.140220E+10 51153279.86 0.00 10677433.85 58036.76 0.00 0.473793E+10 0.00 1.43
April 0.527004E+09 0.181771E+09 0.00 14417221.78 6769504.37 0.00 0.396066E+10 0.00 1.72
May 0.336493E+09 0.803330E+09 0.00 3929876.24 4040789.94 0.00 0.945352E+09 0.00 1.15
June 73113113.30 0.255440E+10 0.00 2408226.82 15970952.68 0.00 0.516933E+09 0.00 1.16
July 1766263.39 0.375742E+10 0.00 102894.12 39159920.92 0.00 3823712.28 0.00 0.97
August 0.00 0.501801E+10 0.00 0.00 5988520.16 0.00 0.00 0.00 1.12
September 0.255545E+09 0.165805E+10 0.00 3033593.67 34193409.49 0.00 0.549499E+09 0.00 1.01
October 0.134361E+10 0.590040E+09 0.00 6025621.10 3899015.48 0.00 0.288430E+10 0.00 1.13
November 0.160307E+10 36625756.10 0.00 7354991.88 3966204.82 0.00 0.390325E+10 0.00 1.14
December 0.232418E+10 1463339.73 0.00 5695307.36 0.00 0.00 0.386880E+10 0.00 0.98
                   
Annual Sum or Average 0.157296E+11 0.146523E+11 0.00 57868617.35 0.114046E+09 0.335067E+09 0.238448E+11 0.00 1.13
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.79
Maximum of Months 0.461399E+10 0.501801E+10 0.00 14417221.78 39159920.92 0.273996E+09 0.473793E+10 0.00 1.72



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.113106E+11 0.00 0.00 0.00 23958586.77 0.360140E+11 0.00 0.00 0.50
February 0.182706E+11 0.00 0.00 1030496.20 0.00 0.208976E+11 0.212356E+09 0.00 0.52
March 0.328112E+11 0.158008E+09 0.00 6113292.49 0.119211E+09 0.348863E+10 0.230064E+10 0.00 0.57
April 0.183231E+11 0.104215E+10 0.00 20080858.13 0.218072E+09 0.837846E+09 0.467529E+10 0.00 0.58
May 0.595310E+10 0.666324E+10 0.00 14512373.27 0.453034E+09 0.00 0.318644E+10 0.00 0.58
June 0.208103E+10 0.236251E+11 0.00 11312415.78 0.210952E+09 0.00 0.210392E+10 0.00 0.65
July 25213263.32 0.321937E+11 0.00 148465.72 0.932550E+09 0.00 20972161.53 0.00 0.56
August 6909279.29 0.390100E+11 0.00 217289.18 0.289087E+09 0.00 1467270.32 0.00 0.59
September 0.435589E+10 0.135813E+11 0.00 13569499.52 0.139373E+10 0.00 0.193483E+10 0.00 0.53
October 0.255790E+11 0.404562E+10 0.00 3763131.37 0.769246E+09 0.102775E+10 0.184855E+10 0.00 0.50
November 0.293103E+11 6492177.09 0.00 1070936.13 0.502260E+09 0.726676E+10 0.446097E+09 0.00 0.51
December 0.228211E+11 0.00 0.00 68230.84 2906370.04 0.200308E+11 55575039.40 0.00 0.49
                   
Annual Sum or Average 0.170848E+12 0.120326E+12 0.00 71886988.64 0.491500E+10 0.895634E+11 0.167861E+11 0.00 0.55
Minimum of Months 6909279.29 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.49
Maximum of Months 0.328112E+11 0.390100E+11 0.00 20080858.13 0.139373E+10 0.360140E+11 0.467529E+10 0.00 0.65



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.177868E+11 0.00 0.00 0.00 22750881.58 0.253929E+11 0.00 0.00 0.71
February 0.184764E+11 0.00 0.00 6054561.99 0.00 0.154777E+11 0.287644E+10 0.00 0.76
March 0.252186E+11 0.112591E+09 0.00 18525938.41 0.134924E+09 0.234161E+10 0.101970E+11 0.00 0.86
April 0.125188E+11 0.641730E+09 0.00 43731113.98 0.427055E+09 0.559659E+09 0.132896E+11 0.00 0.98
May 0.447424E+10 0.628414E+10 0.00 25702511.13 0.656557E+09 0.00 0.637935E+10 0.00 0.95
June 0.158264E+10 0.208374E+11 0.00 17546836.74 0.412886E+09 0.00 0.385115E+10 0.00 0.95
July 32163231.12 0.295536E+11 0.00 117841.95 0.145233E+10 0.00 10961765.72 0.00 0.80
August 7115670.59 0.344046E+11 0.00 122870.74 0.742814E+09 0.00 633026.75 0.00 0.82
September 0.384688E+10 0.115171E+11 0.00 19238156.03 0.310961E+10 0.00 0.332381E+10 0.00 0.85
October 0.193891E+11 0.290030E+10 0.00 17650453.53 0.142445E+10 0.100585E+10 0.868361E+10 0.00 0.78
November 0.279680E+11 6121592.34 0.00 3362845.81 0.476943E+09 0.472451E+10 0.243633E+10 0.00 0.75
December 0.269540E+11 0.00 0.00 0.00 2759865.65 0.131409E+11 0.00 0.00 0.71
                   
Annual Sum or Average 0.158255E+12 0.106258E+12 0.00 0.152053E+09 0.886307E+10 0.626431E+11 0.510489E+11 0.00 0.83
Minimum of Months 7115670.59 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.71
Maximum of Months 0.279680E+11 0.344046E+11 0.00 43731113.98 0.310961E+10 0.253929E+11 0.132896E+11 0.00 0.98



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.186278E+11 0.00 0.00 33572525.09 23898205.96 0.170015E+11 0.201364E+11 0.00 0.58
February 0.179685E+11 0.00 0.00 45660063.61 0.00 0.110410E+11 0.196618E+11 0.00 0.69
March 0.227405E+11 0.400531E+09 0.00 63082865.07 46188359.24 0.175470E+10 0.257576E+11 0.00 0.82
April 0.137574E+11 0.140857E+10 0.00 54997841.56 0.113862E+09 0.535631E+09 0.140101E+11 0.00 0.79
May 0.564277E+10 0.783374E+10 0.00 19967441.80 0.383141E+09 0.00 0.422083E+10 0.00 0.66
June 0.230425E+10 0.239868E+11 0.00 11048055.37 0.229599E+09 0.00 0.190586E+10 0.00 0.66
July 25149720.46 0.336014E+11 0.00 170462.56 0.878086E+09 0.00 21341590.03 0.00 0.58
August 6148673.21 0.458794E+11 0.00 342291.86 0.286689E+09 0.00 2444488.85 0.00 0.70
September 0.356620E+10 0.192343E+11 0.00 31654591.04 0.706662E+09 0.00 0.430584E+10 0.00 0.77
October 0.156245E+11 0.689934E+10 0.00 73412700.69 0.210943E+09 0.874961E+09 0.283568E+11 0.00 0.88
November 0.200591E+11 0.113696E+09 0.00 86759942.82 0.406081E+09 0.257390E+10 0.319558E+11 0.00 0.82
December 0.218850E+11 4348126.16 0.00 55902246.14 0.00 0.805870E+10 0.277483E+11 0.00 0.68
                   
Annual Sum or Average 0.142207E+12 0.139362E+12 0.00 0.476571E+09 0.328515E+10 0.418403E+11 0.178083E+12 0.00 0.72
Minimum of Months 6148673.21 0.00 0.00 170462.56 0.00 0.00 2444488.85 0.00 0.58
Maximum of Months 0.227405E+11 0.458794E+11 0.00 86759942.82 0.878086E+09 0.170015E+11 0.319558E+11 0.00 0.88



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.209423E+11 0.00 0.00 180635.31 24122653.32 0.238991E+11 0.620246E+09 0.00 0.75
February 0.235573E+11 0.00 0.00 5942814.44 0.00 0.132377E+11 0.222690E+10 0.00 0.82
March 0.307270E+11 0.293303E+09 0.00 21209275.71 67454286.22 0.158362E+10 0.874992E+10 0.00 0.98
April 0.160007E+11 0.106875E+10 0.00 41089732.32 0.207346E+09 0.270998E+09 0.977803E+10 0.00 1.06
May 0.590072E+10 0.634558E+10 0.00 17860098.03 0.542934E+09 0.00 0.415957E+10 0.00 0.97
June 0.234341E+10 0.211106E+11 0.00 11518613.60 0.395929E+09 0.00 0.191214E+10 0.00 0.97
July 23311871.51 0.291039E+11 0.00 321197.49 0.110821E+10 0.00 25452938.93 0.00 0.81
August 6206420.37 0.374574E+11 0.00 358267.12 0.176458E+09 0.00 2451737.20 0.00 0.89
September 0.413034E+10 0.124564E+11 0.00 15999562.01 0.223703E+10 0.00 0.224027E+10 0.00 0.87
October 0.231652E+11 0.369687E+10 0.00 17135779.73 0.873619E+09 0.762941E+09 0.671730E+10 0.00 0.86
November 0.289109E+11 6490695.72 0.00 9943868.61 0.505700E+09 0.451985E+10 0.457502E+10 0.00 0.82
December 0.304185E+11 357143.43 0.00 1940436.40 2569129.21 0.106590E+11 0.128138E+10 0.00 0.75
                   
Annual Sum or Average 0.186126E+12 0.111540E+12 0.00 0.143500E+09 0.614137E+10 0.549332E+11 0.422887E+11 0.00 0.88
Minimum of Months 6206420.37 0.00 0.00 180635.31 0.00 0.00 2451737.20 0.00 0.75
Maximum of Months 0.307270E+11 0.374574E+11 0.00 41089732.32 0.223703E+10 0.238991E+11 0.977803E+10 0.00 1.06



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.760539E+09 0.00 0.00 0.00 2476606.06 0.368876E+10 0.00 0.00 0.54
February 0.127070E+10 0.00 0.00 72349.40 212728.38 0.233630E+10 19490586.21 0.00 0.54
March 0.258180E+10 13100304.85 0.00 626191.52 9495890.03 0.758295E+09 0.218217E+09 0.00 0.57
April 0.164041E+10 79925862.27 0.00 2271845.32 39987103.67 0.191753E+09 0.438425E+09 0.00 0.59
May 0.516778E+09 0.638657E+09 0.00 1458861.29 67304440.36 8635099.22 0.310040E+09 0.00 0.58
June 0.183822E+09 0.228769E+10 0.00 1113306.21 51577844.25 0.00 0.209223E+09 0.00 0.65
July 1805904.40 0.309793E+10 0.00 8161.34 0.136414E+09 0.00 623413.40 0.00 0.55
August 747.62 0.379892E+10 0.00 0.00 45705502.72 0.00 0.00 0.00 0.58
September 0.354404E+09 0.119009E+10 0.00 1350312.89 0.302098E+09 0.00 0.200385E+09 0.00 0.53
October 0.193874E+10 0.422140E+09 0.00 271388.43 0.109819E+09 0.512365E+09 0.150273E+09 0.00 0.51
November 0.212686E+10 31037.10 7902260.32 90295.68 52957244.90 0.121409E+10 16330361.21 11430.60 0.52
December 0.141975E+10 0.00 0.00 0.00 511608.92 0.267515E+10 0.00 0.00 0.52
                   
Annual Sum or Average 0.127956E+11 0.115285E+11 7902260.32 7262712.08 0.818560E+09 0.113853E+11 0.156301E+10 11430.60 0.56
Minimum of Months 747.62 0.00 0.00 0.00 212728.38 0.00 0.00 0.00 0.51
Maximum of Months 0.258180E+10 0.379892E+10 7902260.32 2271845.32 0.302098E+09 0.368876E+10 0.438425E+09 11430.60 0.65



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.125457E+10 0.00 0.00 0.00 2338558.53 0.265074E+10 0.00 0.00 0.74
February 0.149296E+10 0.00 0.00 303191.28 200870.77 0.161228E+10 0.166354E+09 0.00 0.76
March 0.217119E+10 7861279.62 0.00 1390451.91 12926567.39 0.494969E+09 0.707929E+09 0.00 0.84
April 0.113781E+10 49039145.23 0.00 4348587.44 55447342.84 0.108097E+09 0.115363E+10 0.00 0.98
May 0.362612E+09 0.611628E+09 0.00 2576862.04 83542728.47 5401867.30 0.601508E+09 0.00 0.94
June 0.129398E+09 0.202676E+10 0.00 1719066.00 71820929.34 0.00 0.375177E+09 0.00 0.95
July 1846678.23 0.286277E+10 0.00 7238.20 0.178478E+09 0.00 405717.02 0.00 0.80
August 705.95 0.334085E+10 0.00 0.00 0.114992E+09 0.00 0.00 0.00 0.82
September 0.287899E+09 0.113829E+10 0.00 1960505.48 0.341427E+09 365214.92 0.347618E+09 0.00 0.86
October 0.146133E+10 0.345631E+09 0.00 1324836.80 0.139890E+09 0.395714E+09 0.699053E+09 0.00 0.77
November 0.229094E+10 29307.08 7467788.59 100855.05 50005375.76 0.742900E+09 82126305.21 4788.36 0.75
December 0.186860E+10 0.00 0.00 0.00 483091.53 0.183099E+10 0.00 0.00 0.74
                   
Annual Sum or Average 0.124592E+11 0.103829E+11 7467788.59 13731594.19 0.105155E+10 0.784146E+10 0.413380E+10 4788.36 0.83
Minimum of Months 705.95 0.00 0.00 0.00 200870.77 0.00 0.00 0.00 0.74
Maximum of Months 0.229094E+10 0.334085E+10 7467788.59 4348587.44 0.341427E+09 0.265074E+10 0.115363E+10 4788.36 0.98



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.153874E+10 0.00 0.00 2203079.03 2643492.79 0.213411E+10 0.137244E+10 0.00 0.60
February 0.152635E+10 0.00 0.00 3342448.02 227063.14 0.139640E+10 0.147805E+10 0.00 0.69
March 0.200798E+10 27919969.90 0.00 5279906.54 5343576.21 0.526122E+09 0.212493E+10 0.00 0.80
April 0.133490E+10 0.107761E+09 0.00 5838904.32 30215512.01 0.149449E+09 0.134337E+10 0.00 0.81
May 0.526044E+09 0.738478E+09 0.00 1996679.63 73363409.51 7256215.69 0.428981E+09 0.00 0.67
June 0.220218E+09 0.227345E+10 0.00 1107206.84 0.105031E+09 0.00 0.200204E+09 0.00 0.67
July 1927595.72 0.320848E+10 0.00 9336.05 0.170033E+09 0.00 661934.75 0.00 0.58
August 798.00 0.445002E+10 0.00 0.00 36671243.00 0.00 0.00 0.00 0.69
September 0.303571E+09 0.172367E+10 0.00 3243468.63 0.257155E+09 0.00 0.480776E+09 0.00 0.78
October 0.137347E+10 0.742325E+09 0.00 6016052.13 45966225.54 0.339005E+09 0.241497E+10 0.00 0.85
November 0.182971E+10 2748701.84 0.00 6215211.66 62297276.20 0.598300E+09 0.226051E+10 0.00 0.77
December 0.194023E+10 530108.21 0.00 3620017.19 15975.61 0.127295E+10 0.190318E+10 0.00 0.66
                   
Annual Sum or Average 0.126031E+11 0.132754E+11 0.00 38872310.05 0.788962E+09 0.642359E+10 0.140081E+11 0.00 0.71
Minimum of Months 798.00 0.00 0.00 0.00 15975.61 0.00 0.00 0.00 0.58
Maximum of Months 0.200798E+10 0.445002E+10 0.00 6215211.66 0.257155E+09 0.213411E+10 0.241497E+10 0.00 0.85



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.163768E+10 0.00 0.00 4810.43 2606046.83 0.259778E+10 26179879.96 0.00 0.81
February 0.186785E+10 0.00 0.00 525895.05 223846.71 0.155193E+10 0.223292E+09 0.00 0.86
March 0.259962E+10 19405782.56 0.00 2039469.88 8510560.77 0.447519E+09 0.869308E+09 0.00 1.00
April 0.148774E+10 75530094.03 0.00 4591124.95 47316142.11 0.104126E+09 0.100122E+10 0.00 1.10
May 0.542481E+09 0.590344E+09 0.00 1760187.64 92115350.35 0.00 0.433980E+09 0.00 0.98
June 0.222822E+09 0.196905E+10 0.00 1174150.69 0.113162E+09 0.00 0.201025E+09 0.00 0.96
July 1374586.43 0.271678E+10 0.00 21703.26 0.207527E+09 0.00 1284390.59 0.00 0.79
August 786.70 0.357666E+10 0.00 0.00 53939667.73 0.00 0.00 0.00 0.86
September 0.365403E+09 0.111705E+10 0.00 1636116.79 0.370267E+09 410861.12 0.229554E+09 0.00 0.89
October 0.200001E+10 0.370328E+09 0.00 1515971.93 0.150002E+09 0.267427E+09 0.640230E+09 0.00 0.88
November 0.240858E+10 0.00 0.00 723449.18 64085037.99 0.752663E+09 0.358661E+09 0.00 0.86
December 0.236863E+10 0.00 0.00 98324.86 538348.36 0.159754E+10 0.101103E+09 0.00 0.82
                   
Annual Sum or Average 0.155022E+11 0.104351E+11 0.00 14091204.66 0.111029E+10 0.731938E+10 0.408584E+10 0.00 0.90
Minimum of Months 786.70 0.00 0.00 0.00 223846.71 0.00 0.00 0.00 0.79
Maximum of Months 0.259962E+10 0.357666E+10 0.00 4591124.95 0.370267E+09 0.259778E+10 0.100122E+10 0.00 1.10



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.00 0.00 0.00 2985069.95 0.00 0.00 0.593193E+09 0.00 0.28
February 0.00 0.00 0.00 7287001.97 0.00 0.00 0.445068E+09 0.00 0.28
March 0.00 4205937.51 0.00 12520530.61 0.00 0.00 0.341130E+09 0.00 0.31
April 0.00 11255691.21 0.00 14844507.70 0.00 0.00 0.186766E+09 0.00 0.29
May 0.00 66282343.21 0.00 1516838.38 0.00 0.00 59851022.92 0.00 0.29
June 0.00 0.278410E+09 0.00 1376396.46 0.00 0.00 27282702.27 0.00 0.30
July 0.00 0.391564E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.28
August 0.00 0.478785E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.31
September 0.00 0.156693E+09 0.00 1328307.93 0.00 0.00 34063940.61 0.00 0.29
October 0.00 50408222.30 0.00 6252557.83 0.00 0.00 0.241334E+09 0.00 0.28
November 0.00 3556099.57 0.00 11458387.86 0.00 0.00 0.355680E+09 0.00 0.28
December 0.00 434846.03 0.00 17067722.40 0.00 0.00 0.448696E+09 0.00 0.28
                   
Annual Sum or Average 0.00 0.144160E+10 0.00 76637321.08 0.00 0.00 0.273306E+10 0.00 0.29
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.28
Maximum of Months 0.00 0.478785E+09 0.00 17067722.40 0.00 0.00 0.593193E+09 0.00 0.31



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: DATACENTER_MID_ZN_6

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.127517E+10 0.00 0.00 11786393.98 0.00 0.00 0.468203E+10 0.00 0.28
February 0.00 0.00 0.00 56261327.58 0.00 0.00 0.447031E+10 0.00 0.28
March 0.00 41554197.43 0.00 0.111639E+09 0.00 0.00 0.342167E+10 0.00 0.31
April 0.00 0.112492E+09 0.00 0.137928E+09 0.00 0.00 0.187499E+10 0.00 0.29
May 0.00 0.640525E+09 0.00 13482174.83 0.00 0.00 0.605212E+09 0.00 0.29
June 0.00 0.277319E+10 0.00 12687002.36 0.00 0.00 0.273147E+09 0.00 0.30
July 0.00 0.390855E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.28
August 0.00 0.478983E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.31
September 0.00 0.153530E+10 0.00 11462839.67 0.00 0.00 0.353462E+09 0.00 0.29
October 0.00 0.496963E+09 0.00 53452284.70 0.00 0.00 0.242463E+10 0.00 0.28
November 0.00 34111087.17 0.00 0.100168E+09 0.00 0.00 0.356901E+10 0.00 0.28
December 0.00 4161205.74 0.00 0.147249E+09 0.00 0.00 0.450785E+10 0.00 0.28
                   
Annual Sum or Average 0.127517E+10 0.143367E+11 0.00 0.656116E+09 0.00 0.00 0.261823E+11 0.00 0.29
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.28
Maximum of Months 0.127517E+10 0.478983E+10 0.00 0.147249E+09 0.00 0.00 0.468203E+10 0.00 0.31



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.292152E+09 0.00 0.00 686512.98 0.00 0.00 0.294338E+09 0.00 0.28
February 0.00 0.00 0.00 5022627.45 0.00 0.00 0.447900E+09 0.00 0.28
March 0.00 4141332.66 0.00 10568256.36 0.00 0.00 0.343094E+09 0.00 0.31
April 0.00 11182355.56 0.00 13489959.92 0.00 0.00 0.188028E+09 0.00 0.29
May 0.00 64114165.42 0.00 1264859.81 0.00 0.00 60939979.22 0.00 0.29
June 0.00 0.277440E+09 0.00 1244317.39 0.00 0.00 27391107.84 0.00 0.30
July 0.00 0.390705E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.28
August 0.00 0.480578E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.31
September 0.00 0.153175E+09 0.00 1045305.93 0.00 0.00 36382817.43 0.00 0.29
October 0.00 49487137.66 0.00 4851921.71 0.00 0.00 0.243728E+09 0.00 0.28
November 0.00 3342404.21 0.00 9257967.30 0.00 0.00 0.358007E+09 0.00 0.28
December 0.00 401911.81 0.00 13875433.63 0.00 0.00 0.451869E+09 0.00 0.28
                   
Annual Sum or Average 0.292152E+09 0.143457E+10 0.00 61307162.47 0.00 0.00 0.245168E+10 0.00 0.29
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.28
Maximum of Months 0.292152E+09 0.480578E+09 0.00 13875433.63 0.00 0.00 0.451869E+09 0.00 0.31



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.00 0.00 0.00 0.224391E+09 0.00 0.00 0.151337E+11 0.00 0.32
February 0.00 0.00 0.00 0.401576E+09 0.00 0.00 0.111504E+11 0.00 0.32
March 0.00 83261267.55 0.00 0.624859E+09 0.00 0.00 0.797142E+10 0.00 0.34
April 0.00 0.231501E+09 0.00 0.737887E+09 0.00 0.00 0.407270E+10 0.00 0.32
May 0.00 0.173291E+10 0.00 75128874.77 0.00 0.00 0.128652E+10 0.00 0.33
June 0.00 0.626850E+10 0.00 67339950.91 0.00 0.00 0.580050E+09 0.00 0.34
July 0.00 0.864008E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.31
August 0.00 0.877330E+10 0.00 14583.41 0.00 0.00 0.00 0.00 0.35
September 0.00 0.379914E+10 0.00 64989747.14 0.00 0.00 0.639806E+09 0.00 0.33
October 0.00 0.116770E+10 0.00 0.323047E+09 0.00 0.00 0.515485E+10 0.00 0.32
November 0.00 68581306.14 0.00 0.580469E+09 0.00 0.00 0.853266E+10 0.00 0.32
December 0.00 9692320.10 0.00 0.866386E+09 0.00 0.00 0.110352E+11 0.00 0.31
                   
Annual Sum or Average 0.00 0.307747E+11 0.00 0.396609E+10 0.00 0.00 0.655574E+11 0.00 0.33
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.31
Maximum of Months 0.00 0.877330E+10 0.00 0.866386E+09 0.00 0.00 0.151337E+11 0.00 0.35



Table of Contents

Report: HeatEmissionsReportMonthly

For: Environment

Timestamp: 2023-10-16 08:43:24

Custom Monthly Report

SITE TOTAL SURFACE HEAT EMISSION TO AIR [J] SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J]
January 0.330345E+12 0.277659E+11 0.00 0.219420E+13 0.611975E+12
February 0.332320E+12 0.242877E+11 0.00 0.196816E+13 0.102696E+13
March 0.489799E+12 0.157002E+11 0.00 0.208653E+13 0.182873E+13
April 0.554557E+12 0.796012E+10 0.00 0.150483E+13 0.256763E+13
May 0.613963E+12 0.191403E+10 0.00 0.569718E+12 0.220174E+13
June 0.598113E+12 -0.688634E+10 0.00 -0.305599E+12 0.321289E+13
July 0.576822E+12 -0.122047E+11 0.00 -0.815755E+12 0.398364E+13
August 0.534724E+12 -0.148145E+11 0.00 -0.101450E+13 0.467824E+13
September 0.409785E+12 -0.278838E+10 0.00 0.308203E+11 0.240964E+13
October 0.386376E+12 0.775894E+10 0.00 0.155483E+13 0.179531E+13
November 0.280764E+12 0.141026E+11 0.00 0.201683E+13 0.163797E+13
December 0.266659E+12 0.258457E+11 0.00 0.231049E+13 0.183495E+13
           
Annual Sum or Average 0.537423E+13 0.886411E+11 0.00 0.121006E+14 0.277897E+14
Minimum of Months 0.266659E+12 -0.148145E+11 0.00 -0.101450E+13 0.611975E+12
Maximum of Months 0.613963E+12 0.277659E+11 0.00 0.231049E+13 0.467824E+13