Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:43
Tabular Output Report in Format: HTML
Building: OfficeLarge
Environment: RUNPERIOD 1 ** Miami Intl Ap FL USA TMY3 WMO#=722020
Simulation Timestamp: 2023-10-16 08:43:45
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 08:43:45
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 34479.41 | 744.37 | 744.37 |
Net Site Energy | 34479.41 | 744.37 | 744.37 |
Total Source Energy | 107819.61 | 2327.69 | 2327.69 |
Net Source Energy | 107819.61 | 2327.69 | 2327.69 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 46320.38 |
Net Conditioned Building Area | 46320.38 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 20.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 6915.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 3922.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 696.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 14676.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 1934.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 2279.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 978.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 2294.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18531.59 |
Humidification | 1.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.43 |
Heat Recovery | 119.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 640.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2280.17 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 33818.50 | 660.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20812.18 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler | 0.00 | 20.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 6915.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 3922.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 696.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 5334.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DataCenterPlugLoads | 9341.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 80.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 1848.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 5.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | General | 2279.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 978.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 2294.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18531.59 |
Humidification | General | 1.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.43 |
Heat Recovery | General | 119.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2280.17 | |
Water Heater | 0.00 | 640.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 20.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 6915.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 3922.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 696.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 14676.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 1934.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 2279.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 978.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 2294.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18531.59 |
Humidification | Unassigned | 1.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.43 |
Heat Recovery | Unassigned | 119.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 0.00 | 640.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2280.17 |
Refrigeration | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 99.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 269.20 | 14.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.45 |
Other | 361.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 730.10 | 14.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.45 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 99.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 269.20 | 14.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.45 |
Other | 361.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 730.10 | 14.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.45 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 33818.497 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 33818.497 | 100.00 |
Total On-Site and Utility Electric Sources | 33818.497 | 100.00 |
Total Electricity End Uses | 33818.497 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | 0.00 |
Air to Air Heat Recovery for Cooling | 5918.09 | 99.77 |
Air to Air Heat Recovery for Heating | 13.48 | 0.23 |
High-Temperature Geothermal* | 0.00 | 0.00 |
Solar Water Thermal | 0.00 | 0.00 |
Solar Air Thermal | 0.00 | 0.00 |
Total On-Site Thermal Sources | 5931.57 | 100.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 20812.18 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 20812.18 | 100.00 |
Total Water End Uses | 20812.18 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 0.00 |
Time Setpoint Not Met During Occupied Cooling | 1000.17 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 5943.00 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2013
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICELARGE
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 1A
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_FL_MIAMI
| Environment |ZoneCoolingSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |ZoneHeatingSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |ZoneElectricSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |SpaceGainsMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |PeakSpaceGainsMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |SpaceGainComponentsAtCoolingPeakMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |ComfortReportSimple55Monthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |OccupantComfortDataSummaryMonthly
| DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 | BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 |ChillerReportMonthly
| COOLSYS1 CHILLER1 | COOLSYS1 CHILLER2 |TowerReportMonthly
| CENTRAL TOWER | TOWERWATERSYS COOLTOWER 1 | TOWERWATERSYS COOLTOWER 2 |BoilerReportMonthly
| HEATSYS1 BOILER | CENTRAL BOILER |DXReportMonthly
| VAV_BOT WITH REHEAT COOLING COIL | VAV_MID WITH REHEAT COOLING COIL | VAV_TOP WITH REHEAT COOLING COIL | CAV_BAS COOLING COIL | AIRLOOP DATACENTER BASEMENT COOLING COIL | AIRLOOP DATACENTER BOT COOLING COIL | AIRLOOP DATACENTER MID COOLING COIL | AIRLOOP DATACENTER TOP COOLING COIL |WindowReportMonthly
| PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW |WindowEnergyReportMonthly
| PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW |WindowZoneSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |WindowEnergyZoneSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWHSYS1 WATER HEATER |DaylightingReportMonthly
| PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_4_DAYLCTRL |CoilReportMonthly
| VAV_BOT WITH REHEAT HEATING COIL | CORE_BOTTOM VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | VAV_MID WITH REHEAT HEATING COIL | CORE_MID VAV BOX REHEAT COIL | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | VAV_TOP WITH REHEAT HEATING COIL | CORE_TOP VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | CAV_BAS HEATING COIL | AIRLOOP DATACENTER BASEMENT HEATING COIL | AIRLOOP DATACENTER BOT HEATING COIL | AIRLOOP DATACENTER MID HEATING COIL | AIRLOOP DATACENTER TOP HEATING COIL | AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | AIRLOOP DATACENTER BOT_SUPPHEATCOIL | AIRLOOP DATACENTER MID_SUPPHEATCOIL | AIRLOOP DATACENTER TOP_SUPPHEATCOIL | VAV_BOT WITH REHEAT COOLING COIL | VAV_MID WITH REHEAT COOLING COIL | VAV_TOP WITH REHEAT COOLING COIL | CAV_BAS COOLING COIL | AIRLOOP DATACENTER BASEMENT COOLING COIL | AIRLOOP DATACENTER BOT COOLING COIL | AIRLOOP DATACENTER MID COOLING COIL | AIRLOOP DATACENTER TOP COOLING COIL |PlantLoopDemandReportMonthly
| HEATSYS1 | COOLSYS1_SUPPLY | COOLSYS1_DEMAND | SINGLE WATER PLANT LOOP | SWHSYS1 | TOWERWATERSYS |FanReportMonthly
| CAV_BAS FAN | VAV_BOT WITH REHEAT FAN | VAV_MID WITH REHEAT FAN | VAV_TOP WITH REHEAT FAN | AIRLOOP DATACENTER BASEMENT SUPPLY FAN | AIRLOOP DATACENTER BOT SUPPLY FAN | AIRLOOP DATACENTER MID SUPPLY FAN | AIRLOOP DATACENTER TOP SUPPLY FAN |PumpReportMonthly
| HEATSYS1 PUMP | COOLSYS1 PUMP SECONDARY | COOLSYS1 CHILLER1 PUMP | COOLSYS1 CHILLER2 PUMP | PLANT CIRC PUMP | SWHSYS1 PUMP | TOWERWATERSYS PUMP |CondLoopDemandReportMonthly
| HEATSYS1 | COOLSYS1_SUPPLY | COOLSYS1_DEMAND | SINGLE WATER PLANT LOOP | SWHSYS1 | TOWERWATERSYS |ZoneTemperatureOscillationReportMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |AirLoopSystemEnergyAndWaterUseMonthly
| VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | CAV_BAS | AIRLOOP DATACENTER BASEMENT | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |AirLoopSystemComponentLoadsMonthly
| VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | CAV_BAS | AIRLOOP DATACENTER BASEMENT | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |AirLoopSystemComponentEnergyUseMonthly
| VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | CAV_BAS | AIRLOOP DATACENTER BASEMENT | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |MechanicalVentilationLoadsMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 08:43:45
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:43 |
RunPeriod | RUNPERIOD 1 |
Weather File | Miami Intl Ap FL USA TMY3 WMO#=722020 |
Latitude [deg] | 25.82 |
Longitude [deg] | -80.3 |
Elevation [m] | 11.00 |
Time Zone | -5.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 12183.89 | 3655.17 | 2436.78 | 3655.17 | 2436.78 |
Above Ground Wall Area [m2] | 11589.54 | 3476.86 | 2317.91 | 3476.86 | 2317.91 |
Window Opening Area [m2] | 4635.80 | 1390.74 | 927.16 | 1390.74 | 927.16 |
Gross Window-Wall Ratio [%] | 38.05 | 38.05 | 38.05 | 38.05 | 38.05 |
Above Ground Window-Wall Ratio [%] | 40.00 | 40.00 | 40.00 | 40.00 | 40.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 12183.89 | 3655.17 | 2436.78 | 3655.17 | 2436.78 |
Above Ground Wall Area [m2] | 11589.54 | 3476.86 | 2317.91 | 3476.86 | 2317.91 |
Window Opening Area [m2] | 4635.80 | 1390.74 | 927.16 | 1390.74 | 927.16 |
Gross Window-Wall Ratio [%] | 38.05 | 38.05 | 38.05 | 38.05 | 38.05 |
Above Ground Window-Wall Ratio [%] | 40.00 | 40.00 | 40.00 | 40.00 | 40.00 |
Total | |
Gross Roof Area [m2] | 3563.11 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
BASEMENT | 2779.43 | Yes | Yes | 6779.02 | 1.00 | 0.00 | 397.05 | 0.00 | 0.00 | 10.2732 | 18.58 | 4.8418 |
CORE_BOTTOM | 2496.12 | Yes | Yes | 6849.35 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.2732 | 18.58 | 8.0697 |
CORE_MID | 2496.12 | Yes | Yes | 6849.35 | 10.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.2732 | 18.58 | 8.0696 |
CORE_TOP | 2496.12 | Yes | Yes | 6849.35 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.2732 | 18.58 | 8.0696 |
PERIMETER_BOT_ZN_3 | 313.41 | Yes | Yes | 860.00 | 1.00 | 200.61 | 0.00 | 115.90 | 115.90 | 10.2732 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_2 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 77.26 | 77.26 | 10.2732 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_1 | 313.42 | Yes | Yes | 860.02 | 1.00 | 200.61 | 0.00 | 115.90 | 115.90 | 10.2732 | 18.58 | 8.0699 |
PERIMETER_BOT_ZN_4 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 77.26 | 77.26 | 10.2732 | 18.58 | 8.0699 |
PERIMETER_MID_ZN_3 | 313.41 | Yes | Yes | 860.00 | 10.00 | 200.61 | 0.00 | 115.90 | 115.90 | 10.2732 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_2 | 201.98 | Yes | Yes | 554.22 | 10.00 | 133.74 | 0.00 | 77.26 | 77.26 | 10.2732 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_1 | 313.42 | Yes | Yes | 860.02 | 10.00 | 200.61 | 0.00 | 115.90 | 115.90 | 10.2732 | 18.58 | 8.0699 |
PERIMETER_MID_ZN_4 | 201.98 | Yes | Yes | 554.22 | 10.00 | 133.74 | 0.00 | 77.26 | 77.26 | 10.2732 | 18.58 | 8.0699 |
PERIMETER_TOP_ZN_3 | 313.41 | Yes | Yes | 860.00 | 1.00 | 200.61 | 0.00 | 115.90 | 115.90 | 10.2732 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_2 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 77.26 | 77.26 | 10.2732 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_1 | 313.42 | Yes | Yes | 860.02 | 1.00 | 200.61 | 0.00 | 115.90 | 115.90 | 10.2732 | 18.58 | 8.0699 |
PERIMETER_TOP_ZN_4 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 77.26 | 77.26 | 10.2732 | 18.58 | 8.0699 |
GROUNDFLOOR_PLENUM | 3563.11 | Yes | No | 4344.14 | 1.00 | 297.11 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
MIDFLOOR_PLENUM | 3563.11 | Yes | No | 4344.14 | 10.00 | 297.11 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
TOPFLOOR_PLENUM | 3563.11 | Yes | No | 4344.14 | 1.00 | 297.11 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
DATACENTER_BOT_ZN_6 | 36.20 | Yes | Yes | 99.34 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.8735 | 18.58 | 215.2992 |
DATACENTER_MID_ZN_6 | 36.20 | Yes | Yes | 99.34 | 10.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.8735 | 18.58 | 215.2992 |
DATACENTER_TOP_ZN_6 | 36.20 | Yes | Yes | 99.34 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.8735 | 18.58 | 215.2992 |
DATACENTER_BASEMENT_ZN_6 | 783.68 | Yes | Yes | 1911.37 | 1.00 | 0.00 | 197.31 | 0.00 | 0.00 | 10.2732 | 18.58 | 484.4232 |
Total | 46320.38 | 126016.35 | 8024.24 | 594.36 | 4635.80 | 4635.80 | 10.3445 | 18.58 | 17.8789 | |||
Conditioned Total | 46320.38 | 126016.35 | 8024.24 | 594.36 | 4635.80 | 4635.80 | 10.3445 | 18.58 | 17.8789 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 42757.27 | 52129.67 | 3565.29 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
BASEMENT | 2779.43 | Yes | Yes | 1.00 | BASEMENT | GENERAL | BASEMENT | 10.2732 | 18.58 | 4.8418 | |
CORE_BOTTOM | 2496.12 | Yes | Yes | 1.00 | CORE_BOTTOM | GENERAL | CORE_BOTTOM | 10.2732 | 18.58 | 8.0697 | |
CORE_MID | 2496.12 | Yes | Yes | 10.00 | CORE_MID | GENERAL | CORE_MID | 10.2732 | 18.58 | 8.0696 | |
CORE_TOP | 2496.12 | Yes | Yes | 1.00 | CORE_TOP | GENERAL | CORE_TOP | 10.2732 | 18.58 | 8.0696 | |
PERIMETER_BOT_ZN_3 | 313.41 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_3 | GENERAL | PERIMETER_BOT_ZN_3 | 10.2732 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_2 | 201.98 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_2 | GENERAL | PERIMETER_BOT_ZN_2 | 10.2732 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_1 | 313.42 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_1 | GENERAL | PERIMETER_BOT_ZN_1 | 10.2732 | 18.58 | 8.0699 | |
PERIMETER_BOT_ZN_4 | 201.98 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_4 | GENERAL | PERIMETER_BOT_ZN_4 | 10.2732 | 18.58 | 8.0699 | |
PERIMETER_MID_ZN_3 | 313.41 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_3 | GENERAL | PERIMETER_MID_ZN_3 | 10.2732 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_2 | 201.98 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_2 | GENERAL | PERIMETER_MID_ZN_2 | 10.2732 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_1 | 313.42 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_1 | GENERAL | PERIMETER_MID_ZN_1 | 10.2732 | 18.58 | 8.0699 | |
PERIMETER_MID_ZN_4 | 201.98 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_4 | GENERAL | PERIMETER_MID_ZN_4 | 10.2732 | 18.58 | 8.0699 | |
PERIMETER_TOP_ZN_3 | 313.41 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_3 | GENERAL | PERIMETER_TOP_ZN_3 | 10.2732 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_2 | 201.98 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_2 | GENERAL | PERIMETER_TOP_ZN_2 | 10.2732 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_1 | 313.42 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_1 | GENERAL | PERIMETER_TOP_ZN_1 | 10.2732 | 18.58 | 8.0699 | |
PERIMETER_TOP_ZN_4 | 201.98 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_4 | GENERAL | PERIMETER_TOP_ZN_4 | 10.2732 | 18.58 | 8.0699 | |
GROUNDFLOOR_PLENUM | 3563.11 | Yes | No | 1.00 | GROUNDFLOOR_PLENUM | GENERAL | GROUNDFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
MIDFLOOR_PLENUM | 3563.11 | Yes | No | 10.00 | MIDFLOOR_PLENUM | GENERAL | MIDFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
TOPFLOOR_PLENUM | 3563.11 | Yes | No | 1.00 | TOPFLOOR_PLENUM | GENERAL | TOPFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
DATACENTER_BOT_ZN_6 | 36.20 | Yes | Yes | 1.00 | DATACENTER_BOT_ZN_6 | GENERAL | DATACENTER_BOT_ZN_6 | 17.8735 | 18.58 | 215.2992 | |
DATACENTER_MID_ZN_6 | 36.20 | Yes | Yes | 10.00 | DATACENTER_MID_ZN_6 | GENERAL | DATACENTER_MID_ZN_6 | 17.8735 | 18.58 | 215.2992 | |
DATACENTER_TOP_ZN_6 | 36.20 | Yes | Yes | 1.00 | DATACENTER_TOP_ZN_6 | GENERAL | DATACENTER_TOP_ZN_6 | 17.8735 | 18.58 | 215.2992 | |
DATACENTER_BASEMENT_ZN_6 | 783.68 | Yes | Yes | 1.00 | DATACENTER_BASEMENT_ZN_6 | GENERAL | DATACENTER_BASEMENT_ZN_6 | 10.2732 | 18.58 | 484.4232 | |
Total | 46320.38 | 10.3445 | 9.29 | 17.8789 | |||||||
Conditioned Total | 46320.38 | 10.3445 | 9.29 | 17.8789 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 42757.27 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 46320.38 | 46320.38 | 0.00 | 42757.27 | 3.1788 | 60.38 | 10.8345 |
Total | 46320.38 | 46320.38 | 0.00 | 42757.27 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:43:45
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 23-AUG-15:09 | 04-FEB-06:10 | - | - | - | - | - | - | - | - | - | - | 17-APR-15:09 |
Heating | 0.00 | 404990.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 480054.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 332294.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 778371.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 84450.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 145084.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 65457.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 98044.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 5613.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 8146.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 1989371.34 | 413137.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler | 0.00 | 404990.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 480054.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 332294.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 305206.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DataCenterPlugLoads | 473165.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 5015.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 79171.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 263.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | General | 145084.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 65457.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 98044.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 5613.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Water Heater | 0.00 | 8146.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:43:45
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 21.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 21901.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 12421.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 2206.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 46480.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 6127.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 7219.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 3100.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 7265.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 3.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 377.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 694.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 107103.18 | 716.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 0.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 472.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 268.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 47.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1003.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 132.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 155.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 66.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 156.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 8.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 15.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 2312.23 | 15.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 0.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 472.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 268.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 47.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1003.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 132.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 155.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 66.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 156.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 8.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 15.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 2312.23 | 15.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:43:45
AirTerminal:SingleDuct:ConstantVolume:NoReheatDesign Size Maximum Air Flow Rate [m3/s] | |
BASEMENT DIRECT AIR | 6.09 |
DATACENTER_BOT_ZN_6 DIRECT AIR | 0.480091 |
DATACENTER_MID_ZN_6 DIRECT AIR | 4.58 |
DATACENTER_TOP_ZN_6 DIRECT AIR | 0.466911 |
DATACENTER_BASEMENT_ZN_6 DIRECT AIR | 21.43 |
Design Size Maximum Air Flow Rate [m3/s] | Design Size Constant Minimum Air Flow Fraction | User-Specified Constant Minimum Air Flow Fraction | Design Size Minimum Air Flow Rate [m3/s] | Design Size Maximum Flow Fraction during Reheat [] | User-Specified Maximum Flow Fraction during Reheat [] | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | Design Size Maximum Reheat Water Flow Rate [m3/s] | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | |
CORE_BOTTOM VAV BOX COMPONENT | 6.28 | 0.302768 | 0.312000 | 1.96 | 0.807382 | 0.500000 | 0.001258 | 0.000172 | 1.96 | 12.80 | 0.008000 |
CORE_MID VAV BOX COMPONENT | 59.39 | 0.320280 | 0.324000 | 19.24 | 0.854079 | 0.500000 | 0.001190 | 0.003533 | 19.24 | 12.80 | 0.008000 |
CORE_TOP VAV BOX COMPONENT | 5.83 | 0.325985 | 0.337000 | 1.97 | 0.869294 | 0.500000 | 0.001169 | 0.000547 | 1.97 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | 1.11 | 0.215499 | 0.222000 | 0.246025 | 0.574664 | 0.500000 | 0.001768 | 0.000059 | 0.246025 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | 1.11 | 0.138653 | 0.200000 | 0.222000 | 0.369742 | 0.500000 | 0.002748 | 0.000047 | 0.222000 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | 1.11 | 0.216124 | 0.223000 | 0.246424 | 0.576332 | 0.500000 | 0.001763 | 0.000073 | 0.248366 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | 1.44 | 0.107093 | 0.200000 | 0.287424 | 0.300000 | 0.500000 | 0.003558 | 0.000041 | 0.287424 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_3 VAV BOX COMPONENT | 10.63 | 0.224739 | 0.227000 | 2.41 | 0.599305 | 0.500000 | 0.001695 | 0.001416 | 4.83 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_2 VAV BOX COMPONENT | 11.48 | 0.134041 | 0.200000 | 2.30 | 0.357443 | 0.500000 | 0.002842 | 0.000933 | 3.18 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_1 VAV BOX COMPONENT | 10.54 | 0.226650 | 0.229000 | 2.41 | 0.604400 | 0.500000 | 0.001681 | 0.001403 | 4.78 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_4 VAV BOX COMPONENT | 12.73 | 0.120852 | 0.200000 | 2.55 | 0.322273 | 0.500000 | 0.003153 | 0.000858 | 2.93 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | 1.18 | 0.202679 | 0.210000 | 0.247447 | 0.540478 | 0.500000 | 0.001880 | 0.000174 | 0.592454 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | 1.16 | 0.132343 | 0.200000 | 0.232586 | 0.352914 | 0.500000 | 0.002879 | 0.000114 | 0.388388 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | 1.18 | 0.202542 | 0.209000 | 0.246440 | 0.540113 | 0.500000 | 0.001881 | 0.000172 | 0.588266 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | 1.35 | 0.113791 | 0.200000 | 0.270504 | 0.303443 | 0.500000 | 0.003348 | 0.000108 | 0.368907 | 12.80 | 0.008000 |
Design Size Rated Capacity [W] | Design Size Maximum Water Flow Rate [m3/s] | Design Size U-Factor Times Area Value [W/K] | |
CORE_BOTTOM VAV BOX REHEAT COIL | 19711.84 | 0.000172 | 397.38 |
CORE_MID VAV BOX REHEAT COIL | 403865.23 | 0.003533 | 9127.63 |
CORE_TOP VAV BOX REHEAT COIL | 62558.34 | 0.000547 | 1613.27 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | 6789.76 | 0.000059 | 165.89 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | 5398.09 | 0.000047 | 126.75 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | 8348.41 | 0.000073 | 220.55 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | 4712.47 | 0.000041 | 101.30 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | 161898.76 | 0.001416 | 4271.51 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | 106699.93 | 0.000933 | 2815.07 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | 160348.89 | 0.001403 | 4230.68 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | 98090.89 | 0.000858 | 2588.18 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | 19847.35 | 0.000174 | 523.53 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | 13010.56 | 0.000114 | 343.18 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | 19707.40 | 0.000172 | 519.84 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | 12359.33 | 0.000108 | 326.02 |
VAV_BOT WITH REHEAT HEATING COIL | 15573.04 | 0.000136 | 276.83 |
VAV_MID WITH REHEAT HEATING COIL | 94643.34 | 0.000828 | 1701.61 |
VAV_TOP WITH REHEAT HEATING COIL | 7127.01 | 0.000062 | 128.98 |
CAV_BAS HEATING COIL | 281575.79 | 0.002463 | 6431.56 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT | 5.52 | 2.96 | 11.04 | 2.96 | 10.14 | 10.14 | 0.300000 | 0.292144 | 10.14 |
VAV_MID WITH REHEAT | 52.38 | 28.91 | 104.77 | 28.91 | 95.08 | 95.08 | 0.300000 | 0.304071 | 95.08 |
VAV_TOP WITH REHEAT | 5.35 | 2.96 | 10.71 | 3.75 | 10.29 | 10.29 | 0.300000 | 0.364549 | 10.29 |
CAV_BAS | 6.09 | 6.09 | 6.09 | 6.09 | 6.09 | 6.09 | 1.00 | 1.00 | 6.09 |
AIRLOOP DATACENTER BASEMENT | 21.43 | 21.43 | 21.43 | 21.43 | 21.43 | 21.43 | 1.00 | 0.999993 | 21.43 |
AIRLOOP DATACENTER BOT | 0.480091 | 0.480091 | 0.480091 | 0.480091 | 0.480091 | 0.480091 | 1.00 | 1.00 | 0.480091 |
AIRLOOP DATACENTER MID | 4.58 | 4.58 | 4.58 | 4.58 | 4.58 | 4.58 | 1.00 | 1.00 | 4.58 |
AIRLOOP DATACENTER TOP | 0.466911 | 0.466911 | 0.466911 | 0.466911 | 0.466911 | 0.466911 | 1.00 | 1.00 | 0.466911 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT_OA_CONTROLLER | 10.14 | 2.54 |
VAV_MID WITH REHEAT_OA_CONTROLLER | 95.08 | 25.38 |
VAV_TOP WITH REHEAT_OA_CONTROLLER | 10.29 | 2.54 |
CAV_BAS_OA_CONTROLLER | 6.09 | 1.20 |
AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER | 21.43 | 0.338393 |
AIRLOOP DATACENTER BOT_OA_CONTROLLER | 0.480091 | 0.015632 |
AIRLOOP DATACENTER MID_OA_CONTROLLER | 4.58 | 0.156323 |
AIRLOOP DATACENTER TOP_OA_CONTROLLER | 0.466911 | 0.015632 |
Design Size Nominal Supply Air Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT OA HEAT RECOVERY | 2.54 |
VAV_MID WITH REHEAT OA HEAT RECOVERY | 25.38 |
VAV_TOP WITH REHEAT OA HEAT RECOVERY | 2.54 |
Design Size Design Inlet Air Temperature [C] | Design Size Design Inlet Water Temperature [C] | Design Size Design Outlet Air Temperature [C] | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | Design Size Design Coil Load [W] | Design Size Design Water Flow Rate [m3/s] | Design Size Design Air Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT COOLING COIL | 26.38 | 6.67 | 11.06 | 0.011052 | 0.008500 | 270084.32 | 0.011490 | 10.14 |
VAV_MID WITH REHEAT COOLING COIL | 26.57 | 6.67 | 11.05 | 0.011352 | 0.008500 | 2643274.95 | 0.112451 | 95.08 |
VAV_TOP WITH REHEAT COOLING COIL | 26.22 | 6.67 | 11.06 | 0.011015 | 0.008500 | 271050.54 | 0.011531 | 10.29 |
CAV_BAS COOLING COIL | 24.89 | 6.67 | 11.42 | 0.010539 | 0.008500 | 138576.71 | 0.005895 | 6.09 |
Design Size Maximum Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT FAN | 10.14 |
VAV_MID WITH REHEAT FAN | 95.08 |
VAV_TOP WITH REHEAT FAN | 10.29 |
Maximum Actuated Flow [m3/s] | Controller Convergence Tolerance | |
VAV_BOT WITH REHEAT_COOLC_CONTROLLER | 0.011490 | 0.000041 |
VAV_BOT WITH REHEAT_HEATC_CONTROLLER | 0.000136 | |
VAV_MID WITH REHEAT_COOLC_CONTROLLER | 0.112451 | 0.000004 |
VAV_MID WITH REHEAT_HEATC_CONTROLLER | 0.000828 | |
VAV_TOP WITH REHEAT_COOLC_CONTROLLER | 0.011531 | 0.000041 |
VAV_TOP WITH REHEAT_HEATC_CONTROLLER | 0.000062 | |
CAV_BAS_COOLC_CONTROLLER | 0.005895 | 0.000081 |
CAV_BAS_HEATC_CONTROLLER | 0.002463 |
Design Size Maximum Flow Rate [m3/s] | |
CAV_BAS FAN | 6.09 |
Design Size Rated Air Flow Rate [m3/s] | Design Size Rated Total Cooling Capacity [W] | Design Size Rated Sensible Cooling Capacity [W] | Design Size Rated Water Flow Rate [m3/s] | |
AIRLOOP DATACENTER BASEMENT COOLING COIL | 21.43 | 436486.14 | 313639.03 | 0.010690 |
AIRLOOP DATACENTER BOT COOLING COIL | 0.480091 | 9798.88 | 7029.32 | 0.000240 |
AIRLOOP DATACENTER MID COOLING COIL | 4.58 | 93691.14 | 67117.65 | 0.002294 |
AIRLOOP DATACENTER TOP COOLING COIL | 0.466911 | 9544.35 | 6841.26 | 0.000234 |
Supply Air Flow Rate [m3/s] | Supply Air Flow Rate During Heating Operation [m3/s] | Supply Air Flow Rate During Cooling Operation [m3/s] | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | Nominal Heating Capacity [W] | Nominal Cooling Capacity [W] | Supplemental Heating Coil Nominal Capacity [W] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | 21.43 | 21.43 | 21.43 | 21.43 | 436486.14 | 436486.14 | 12800.94 | 1.00 |
AIRLOOP DATACENTER BOT DXAC HEAT PUMP | 0.480091 | 0.480091 | 0.480091 | 0.480091 | 9798.88 | 9798.88 | 591.35 | 1.00 |
AIRLOOP DATACENTER MID DXAC HEAT PUMP | 4.58 | 4.58 | 4.58 | 4.58 | 93691.14 | 93691.14 | 5913.50 | 1.00 |
AIRLOOP DATACENTER TOP DXAC HEAT PUMP | 0.466911 | 0.466911 | 0.466911 | 0.466911 | 9544.35 | 9544.35 | 591.35 | 1.00 |
Design Size Maximum Flow Rate [m3/s] | |
AIRLOOP DATACENTER BASEMENT SUPPLY FAN | 21.43 |
AIRLOOP DATACENTER BOT SUPPLY FAN | 0.480091 |
AIRLOOP DATACENTER MID SUPPLY FAN | 4.58 |
AIRLOOP DATACENTER TOP SUPPLY FAN | 0.466911 |
Design Size Rated Air Flow Rate [m3/s] | Design Size Rated Heating Capacity [W] | Design Size Rated Water Flow Rate [m3/s] | |
AIRLOOP DATACENTER BASEMENT HEATING COIL | 21.43 | 436486.14 | 0.010690 |
AIRLOOP DATACENTER BOT HEATING COIL | 0.480091 | 9798.88 | 0.000240 |
AIRLOOP DATACENTER MID HEATING COIL | 4.58 | 93691.14 | 0.002294 |
AIRLOOP DATACENTER TOP HEATING COIL | 0.466911 | 9544.35 | 0.000234 |
Design Size Nominal Capacity [W] | |
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | 12800.94 |
AIRLOOP DATACENTER BOT_SUPPHEATCOIL | 591.35 |
AIRLOOP DATACENTER MID_SUPPHEATCOIL | 5913.50 |
AIRLOOP DATACENTER TOP_SUPPHEATCOIL | 591.35 |
Design Size Nominal Capacity Volume [m3/s] | User-Specified Nominal Capacity Volume [m3/s] | Design Size Rated Power [W] | User-Specified Rated Power [W] | |
DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | 0.000037 | 0.000037 | 96450.70 | 100000.00 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | Design Minimum Flow Rate [m3/s] | |
COOLSYS1 PUMP SECONDARY | 0.141368 | 23081.00 | |
HEATSYS1 PUMP | 0.013142 | 3957.94 | 0.000000 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
COOLSYS1_DEMAND | 0.141368 | 16.96 |
HEATSYS1 | 0.013142 | 1.58 |
COOLSYS1_SUPPLY | 0.141368 | 16.96 |
SINGLE WATER PLANT LOOP | 0.013458 | 1.61 |
SWHSYS1 | 0.000440 | 0.052800 |
Loop Supply Side Design Fluid Flow Rate [m3/s] | Loop Demand Side Design Fluid Flow Rate [m3/s] | Heat Exchanger U-Factor Times Area Value [W/C] | Loop-to-loop Temperature Difference Used to Size Heat Exchanger U-Factor Times Area Value [C] | |
BYPASS HEAT EXCHANGER | 0.141368 | 0.141368 | 593390.45 | 5.60 |
Design Size Nominal Capacity [W] | User-Specified Nominal Capacity [W] | Design Size Design Water Flow Rate [m3/s] | |
HEATSYS1 BOILER | 1502266.44 | 1502266.44 | 0.013142 |
CENTRAL BOILER | 554342.78 | 543702.46 | 0.013458 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
COOLSYS1 CHILLER1 PUMP | 0.070684 | 7989.88 |
COOLSYS1 CHILLER2 PUMP | 0.070684 | 7989.88 |
PLANT CIRC PUMP | 0.013458 | 3432.39 |
SWHSYS1 PUMP | 0.000440 | 56.21 |
Design Size Reference Chilled Water Flow Rate [m3/s] | User-Specified Reference Chilled Water Flow Rate [m3/s] | Design Size Reference Capacity [W] | User-Specified Reference Capacity [W] | Design Size Reference Condenser Water Flow Rate [m3/s] | |
COOLSYS1 CHILLER1 | 0.141368 | 0.071290 | 1679859.86 | 1687769.75 | 0.083521 |
COOLSYS1 CHILLER2 | 0.141368 | 0.071290 | 1679859.86 | 1687769.75 | 0.083521 |
Design Water Flow Rate [m3/s] | Air Flow Rate at High Fan Speed [m3/s] | Fluid cooler UA value at high fan speed based on nominal capacity input [W/K] | Air Flow Rate at Low Fan Speed [m3/s] | Fan Power at Low Fan Speed [W] | U-factor Times Area Value at Low Fan Speed [W/C] | |
CENTRAL TOWER | 0.013458 | 139666.47 | 58635.87 | 69833.23 | 7879.72 | 21351.27 |
Use Side Design Flow Rate [m3/s] | |
SWHSYS1 WATER HEATER | 0.000440 |
Maximum Loop Flow Rate [m3/s] | Condenser Loop Volume [m3] | |
TOWERWATERSYS | 0.167043 | 20.05 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
TOWERWATERSYS PUMP | 0.167043 | 41356.14 |
Design Air Flow Rate [m3/s] | Nominal Capacity [W] | Air Flow Rate in free convection regime [m3/s] | Tower capacity in free convection regime at design conditions [W] | |
TOWERWATERSYS COOLTOWER 1 | 64.29 | 2002498.32 | 12.86 | 250312.29 |
TOWERWATERSYS COOLTOWER 2 | 64.29 | 2002498.32 | 12.86 | 250312.29 |
Design Water Flow Rate [m3/s] Equipment # 47 | |
WSHPPLANT OPERATION SCHEME | 0.086752 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:43:45
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
PERIMETER_BOT_ZN_3_WALL_NORTH | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | |
PERIMETER_BOT_ZN_2_WALL_EAST | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | |
PERIMETER_BOT_ZN_1_WALL_SOUTH | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | |
PERIMETER_BOT_ZN_4_WALL_WEST | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | |
PERIMETER_MID_ZN_3_WALL_NORTH | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_MID_ZN_2_WALL_EAST | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_MID_ZN_1_WALL_SOUTH | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_MID_ZN_4_WALL_WEST | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | |
PERIMETER_TOP_ZN_3_WALL_NORTH | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_TOP_ZN_2_WALL_EAST | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_TOP_ZN_1_WALL_SOUTH | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_TOP_ZN_4_WALL_WEST | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 08:43:45
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 08:43:45
VersionVersion ID | |
1 | 22.1.0 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 26.30 | 23.60 | 20.30 | 19.40 | 20.90 | 21.60 | 24.10 | 26.40 | 27.70 | 28.10 | 28.00 | 27.50 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Miami Intl Ap FL USA TMY3 WMO#=722020 | 25.82 | -80.30 | -5.00 | 11.00 | 101193 | 1.2027 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 24.49 | 8.70 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | OfficeLarge | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 23 | 221 | 36 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | BASEMENT | 0.0 | 0.00 | 0.00 | 0.00 | 44.59 | 24.37 | -1.22 | 1 | 1 | 1 | 16.08 | 73.11 | 0.00 | 48.74 | -2.44 | 0.00 | 2.44 | 6779.02 | TARP | TARP | 2779.43 | 0.00 | 0.00 | 0.00 | 9 | 0 | 0 | Yes |
2 | CORE_BOTTOM | 0.0 | 0.00 | 0.00 | 0.00 | 37.01 | 24.37 | 1.37 | 1 | 1 | 1 | 5.49 | 68.53 | 4.57 | 44.17 | 0.00 | 2.74 | 2.74 | 6849.35 | TARP | TARP | 2496.12 | 0.00 | 0.00 | 0.00 | 7 | 0 | 0 | Yes |
3 | CORE_MID | 0.0 | 0.00 | 0.00 | 0.00 | 37.01 | 24.37 | 18.14 | 1 | 10 | 1 | 5.49 | 68.53 | 4.57 | 44.17 | 16.77 | 19.51 | 2.74 | 6849.35 | TARP | TARP | 2496.12 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
4 | CORE_TOP | 0.0 | 0.00 | 0.00 | 0.00 | 37.01 | 24.37 | 34.91 | 1 | 1 | 1 | 5.49 | 68.53 | 4.57 | 44.17 | 33.54 | 36.28 | 2.74 | 6849.35 | TARP | TARP | 2496.12 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
5 | PERIMETER_BOT_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 46.54 | 1.37 | 1 | 1 | 1 | 0.00 | 73.11 | 44.17 | 48.74 | 0.00 | 2.74 | 2.74 | 860.00 | TARP | TARP | 313.41 | 200.61 | 76.91 | 115.90 | 8 | 9 | 0 | Yes |
6 | PERIMETER_BOT_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 70.95 | 24.37 | 1.37 | 1 | 1 | 1 | 68.53 | 73.11 | 0.00 | 48.74 | 0.00 | 2.74 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 52.57 | 77.26 | 6 | 5 | 0 | Yes |
7 | PERIMETER_BOT_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 2.20 | 1.37 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 4.57 | 0.00 | 2.74 | 2.74 | 860.02 | TARP | TARP | 313.42 | 200.61 | 76.91 | 115.90 | 8 | 9 | 0 | Yes |
8 | PERIMETER_BOT_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.16 | 24.37 | 1.37 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 48.74 | 0.00 | 2.74 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 52.57 | 77.26 | 6 | 5 | 0 | Yes |
9 | PERIMETER_MID_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 46.54 | 18.14 | 1 | 10 | 1 | 0.00 | 73.11 | 44.17 | 48.74 | 16.77 | 19.51 | 2.74 | 860.00 | TARP | TARP | 313.41 | 200.61 | 84.71 | 115.90 | 7 | 1 | 0 | Yes |
10 | PERIMETER_MID_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 70.95 | 24.37 | 18.14 | 1 | 10 | 1 | 68.53 | 73.11 | 0.00 | 48.74 | 16.77 | 19.51 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 56.47 | 77.26 | 6 | 1 | 0 | Yes |
11 | PERIMETER_MID_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 2.20 | 18.14 | 1 | 10 | 1 | 0.00 | 73.11 | 0.00 | 4.57 | 16.77 | 19.51 | 2.74 | 860.02 | TARP | TARP | 313.42 | 200.61 | 84.71 | 115.90 | 7 | 1 | 0 | Yes |
12 | PERIMETER_MID_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.16 | 24.37 | 18.14 | 1 | 10 | 1 | 0.00 | 4.57 | 0.00 | 48.74 | 16.77 | 19.51 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 56.47 | 77.26 | 6 | 1 | 0 | Yes |
13 | PERIMETER_TOP_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 46.54 | 34.91 | 1 | 1 | 1 | 0.00 | 73.11 | 44.17 | 48.74 | 33.54 | 36.28 | 2.74 | 860.00 | TARP | TARP | 313.41 | 200.61 | 84.71 | 115.90 | 7 | 1 | 0 | Yes |
14 | PERIMETER_TOP_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 70.95 | 24.37 | 34.91 | 1 | 1 | 1 | 68.53 | 73.11 | 0.00 | 48.74 | 33.54 | 36.28 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 56.47 | 77.26 | 6 | 1 | 0 | Yes |
15 | PERIMETER_TOP_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 2.20 | 34.91 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 4.57 | 33.54 | 36.28 | 2.74 | 860.02 | TARP | TARP | 313.42 | 200.61 | 84.71 | 115.90 | 7 | 1 | 0 | Yes |
16 | PERIMETER_TOP_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.16 | 24.37 | 34.91 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 48.74 | 33.54 | 36.28 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 56.47 | 77.26 | 6 | 1 | 0 | Yes |
17 | GROUNDFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 24.37 | 3.35 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 48.74 | 2.74 | 3.96 | 1.22 | 4344.14 | TARP | TARP | 3563.11 | 297.11 | 297.11 | 0.00 | 11 | 0 | 0 | No |
18 | MIDFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 24.37 | 20.12 | 1 | 10 | 1 | 0.00 | 73.11 | 0.00 | 48.74 | 19.51 | 20.73 | 1.22 | 4344.14 | TARP | TARP | 3563.11 | 297.11 | 297.11 | 0.00 | 11 | 0 | 0 | No |
19 | TOPFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 24.37 | 36.89 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 48.74 | 36.28 | 37.50 | 1.22 | 4344.14 | TARP | TARP | 3563.11 | 297.11 | 297.11 | 0.00 | 11 | 0 | 0 | No |
20 | DATACENTER_BOT_ZN_6 | 0.0 | 5.49 | 44.17 | 0.00 | 5.03 | 24.37 | 1.37 | 1 | 1 | 1 | 4.57 | 5.49 | 4.57 | 44.17 | 0.00 | 2.74 | 2.74 | 99.34 | TARP | TARP | 36.20 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
21 | DATACENTER_MID_ZN_6 | 0.0 | 4.57 | 4.57 | 16.77 | 5.03 | 24.37 | 18.14 | 1 | 10 | 1 | 4.57 | 5.49 | 4.57 | 44.17 | 16.77 | 19.51 | 2.74 | 99.34 | TARP | TARP | 36.20 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
22 | DATACENTER_TOP_ZN_6 | 0.0 | 4.57 | 4.57 | 33.54 | 5.03 | 24.37 | 34.91 | 1 | 1 | 1 | 4.57 | 5.49 | 4.57 | 44.17 | 33.54 | 36.28 | 2.74 | 99.34 | TARP | TARP | 36.20 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
23 | DATACENTER_BASEMENT_ZN_6 | 0.0 | 16.08 | 0.00 | -2.44 | 8.04 | 24.37 | -1.22 | 1 | 1 | 1 | 0.00 | 16.08 | 0.00 | 48.74 | -2.44 | 0.00 | 2.44 | 1911.37 | TARP | TARP | 783.68 | 0.00 | 0.00 | 0.00 | 10 | 0 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | BASEMENT | 2779.43 | 149.6 | 18.579 | 5.382E-002 | 10.273 | 4.842 | 0.000 | 0.000 | 0.000 | 0.000 | 15.115 | No |
2 | CORE_BOTTOM | 2496.12 | 134.4 | 18.579 | 5.382E-002 | 10.273 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 18.343 | No |
3 | CORE_MID | 2496.12 | 134.4 | 18.579 | 5.382E-002 | 10.273 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 18.343 | No |
4 | CORE_TOP | 2496.12 | 134.4 | 18.579 | 5.382E-002 | 10.273 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 18.343 | No |
5 | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 18.579 | 5.382E-002 | 10.273 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 18.343 | No |
6 | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 10.273 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 18.343 | No |
7 | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 18.579 | 5.382E-002 | 10.273 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 18.343 | No |
8 | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 10.273 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 18.343 | No |
9 | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 18.579 | 5.382E-002 | 10.273 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 18.343 | No |
10 | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 10.273 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 18.343 | No |
11 | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 18.579 | 5.382E-002 | 10.273 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 18.343 | No |
12 | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 10.273 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 18.343 | No |
13 | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 18.579 | 5.382E-002 | 10.273 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 18.343 | No |
14 | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 10.273 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 18.343 | No |
15 | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 18.579 | 5.382E-002 | 10.273 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 18.343 | No |
16 | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 10.273 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 18.343 | No |
17 | GROUNDFLOOR_PLENUM | 3563.11 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
18 | MIDFLOOR_PLENUM | 3563.11 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
19 | TOPFLOOR_PLENUM | 3563.11 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
20 | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 18.579 | 5.382E-002 | 17.873 | 215.299 | 0.000 | 0.000 | 0.000 | 0.000 | 233.173 | No |
21 | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 18.579 | 5.382E-002 | 17.873 | 215.299 | 0.000 | 0.000 | 0.000 | 0.000 | 233.173 | No |
22 | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 18.579 | 5.382E-002 | 17.873 | 215.299 | 0.000 | 0.000 | 0.000 | 0.000 | 233.173 | No |
23 | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 18.579 | 5.382E-002 | 10.273 | 484.423 | 0.000 | 0.000 | 0.000 | 0.000 | 494.696 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | DATACENTER_BOT_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 1.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | DATACENTER_MID_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 1.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
3 | DATACENTER_TOP_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 1.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
4 | DATACENTER_BASEMENT_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 42.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 42 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
5 | BASEMENT | BLDG_OCC_SCH_WO_SB | BASEMENT | 2779.43 | 149.6 | 149.6 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 150 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
6 | CORE_BOTTOM | BLDG_OCC_SCH_WO_SB | CORE_BOTTOM | 2496.12 | 134.4 | 134.4 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 134 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
7 | CORE_MID | BLDG_OCC_SCH_WO_SB | CORE_MID | 2496.12 | 134.4 | 134.4 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 134 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
8 | CORE_TOP | BLDG_OCC_SCH_WO_SB | CORE_TOP | 2496.12 | 134.4 | 134.4 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 134 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
9 | PERIMETER_BOT_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
10 | PERIMETER_BOT_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
11 | PERIMETER_BOT_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
12 | PERIMETER_BOT_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
13 | PERIMETER_MID_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
14 | PERIMETER_MID_ZN_2 | BLDG_OCC_SCH_W_SB | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
15 | PERIMETER_MID_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
16 | PERIMETER_MID_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
17 | PERIMETER_TOP_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
18 | PERIMETER_TOP_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
19 | PERIMETER_TOP_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
20 | PERIMETER_TOP_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | BASEMENT_LIGHTS | LTG_SCH_OFFICE | BASEMENT | 2779.43 | 149.6 | 28553.717 | 10.273 | 190.864 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 28553.717 |
2 | CORE_BOTTOM_LIGHTS | LTG_SCH_OFFICE | CORE_BOTTOM | 2496.12 | 134.4 | 25643.245 | 10.273 | 190.864 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 25643.245 |
3 | CORE_MID_LIGHTS | LTG_SCH_OFFICE | CORE_MID | 2496.12 | 134.4 | 25643.245 | 10.273 | 190.864 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 25643.245 |
4 | CORE_TOP_LIGHTS | LTG_SCH_OFFICE | CORE_TOP | 2496.12 | 134.4 | 25643.245 | 10.273 | 190.864 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 25643.245 |
5 | PERIMETER_BOT_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 3219.765 | 10.273 | 190.864 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3219.765 |
6 | PERIMETER_BOT_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 2074.939 | 10.273 | 190.864 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2074.939 |
7 | PERIMETER_BOT_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 3219.836 | 10.273 | 190.864 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3219.836 |
8 | PERIMETER_BOT_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 2074.939 | 10.273 | 190.864 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2074.939 |
9 | PERIMETER_MID_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 3219.765 | 10.273 | 190.864 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3219.765 |
10 | PERIMETER_MID_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 2074.939 | 10.273 | 190.864 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2074.939 |
11 | PERIMETER_MID_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 3219.836 | 10.273 | 190.864 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3219.836 |
12 | PERIMETER_MID_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 2074.939 | 10.273 | 190.864 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2074.939 |
13 | PERIMETER_TOP_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 3219.765 | 10.273 | 190.864 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3219.765 |
14 | PERIMETER_TOP_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 2074.939 | 10.273 | 190.864 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2074.939 |
15 | PERIMETER_TOP_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 3219.836 | 10.273 | 190.864 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3219.836 |
16 | PERIMETER_TOP_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 2074.939 | 10.273 | 190.864 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2074.939 |
17 | DATACENTER_BASEMENT_LIGHTS | LTG_SCH_OFFICE | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 8050.927 | 10.273 | 190.864 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 8050.927 |
18 | DATACENTER_BOT_LIGHTS | LTG_SCH_DATACENTER | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 647.068 | 17.873 | 332.067 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 647.068 |
19 | DATACENTER_MID_LIGHTS | LTG_SCH_DATACENTER | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 647.068 | 17.873 | 332.067 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 647.068 |
20 | DATACENTER_TOP_LIGHTS | LTG_SCH_DATACENTER | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 647.068 | 17.873 | 332.067 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 647.068 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | BASEMENT_MISCPLUG_EQUIP | ALWAYS_ON | BASEMENT | 2779.43 | 149.6 | 13457.544 | 4.842 | 89.956 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 13457.544 | 13457.544 |
2 | CORE_BOTTOM_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_BOTTOM | 2496.12 | 134.4 | 20142.877 | 8.070 | 149.925 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 20142.877 |
3 | CORE_MID_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_MID | 2496.12 | 134.4 | 20142.800 | 8.070 | 149.924 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 20142.800 |
4 | CORE_TOP_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_TOP | 2496.12 | 134.4 | 20142.800 | 8.070 | 149.924 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 20142.800 |
5 | PERIMETER_BOT_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 2529.242 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.242 |
6 | PERIMETER_BOT_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 1629.940 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.940 |
7 | PERIMETER_BOT_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 2529.281 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.281 |
8 | PERIMETER_BOT_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 1629.929 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.929 |
9 | PERIMETER_MID_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 2529.242 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.242 |
10 | PERIMETER_MID_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 1629.940 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.940 |
11 | PERIMETER_MID_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 2529.281 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.281 |
12 | PERIMETER_MID_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 1629.929 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.929 |
13 | PERIMETER_TOP_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 2529.242 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.242 |
14 | PERIMETER_TOP_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 1629.940 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.940 |
15 | PERIMETER_TOP_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 2529.281 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.281 |
16 | PERIMETER_TOP_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 1629.929 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.929 |
17 | DATACENTER_BASEMENT_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 379632.522 | 484.423 | 9000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 94908.130 | 379632.522 |
18 | DATACENTER_BOT_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 7794.422 | 215.299 | 4000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 1948.606 | 7794.422 |
19 | DATACENTER_MID_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 7794.422 | 215.299 | 4000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 1948.606 | 7794.422 |
20 | DATACENTER_TOP_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 7794.422 | 215.299 | 4000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 1948.606 | 7794.422 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 3.975 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | INTERIORFURNISHINGS | 2 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
3 | DROPCEILING | 4 | 1 | 3 | 0.167 | 4.488 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
4 | INT_WALL | 7 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | EXT_SLAB_8IN_WITH_CARPET | 8 | 2 | 7 | 0.167 | 3.285 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
6 | INT_SLAB_FLOOR | 12 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
7 | INT_SLAB_CEILING | 13 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | VeryRough |
8 | NONRES_ROOF | 17 | 3 | 3 | 0.167 | 0.2832 | 0.750 | 0.900 | 0.450 | 0.700 | Rough |
9 | NONRES_EXT_WALL_GRD | 20 | 3 | 9 | 0.167 | 5.069 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
10 | NONRES_EXT_WALL_MID | 21 | 3 | 9 | 0.167 | 5.069 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
11 | NONRES_EXT_WALL_TOP | 22 | 3 | 9 | 0.167 | 5.069 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
12 | BASEMENT_WALL_EAST_CFACTOR | 39 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | BASEMENT_WALL_SOUTH_CFACTOR | 40 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | BASEMENT_WALL_NORTH_CFACTOR | 41 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR | 42 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
16 | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR | 43 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
17 | DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR | 44 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2516 |
2 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
3 | AC02 ACOUSTIC CEILING | 0.0127 | 0.057 | 288.000 | 1339.000 | 0.2228 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | 200MM NORMALWEIGHT CONCRETE FLOOR | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
7 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
8 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
9 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
10 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
11 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
12 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
13 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 3.472 |
14 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
15 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
16 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2994E-01 |
17 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
18 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
19 | NONRES_EXTERIOR_WALL_INSULATION_MID | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2994E-01 |
20 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
21 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
22 | NONRES_EXTERIOR_WALL_INSULATION_TOP | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2994E-01 |
23 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
24 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
25 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
26 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
27 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
28 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
29 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
30 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
31 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
32 | ~FC_Insulation_5 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
33 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
34 | ~FC_Insulation_6 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
35 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 3.9747841 | 3.9747841 | 3.9747841 | |
3 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
4 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
5 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
6 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
7 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
8 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
9 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
10 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
11 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
12 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
13 | 3 | -0.21589802E-09 | 0.15643069E-09 | -0.21589802E-09 | 0.12999471E-21 |
14 | 2 | 0.50772448E-02 | 0.30006816E-02 | 0.50772448E-02 | -0.13693132E-08 |
15 | 1 | -2.5944910 | 1.4597758 | -2.5944910 | 0.76344767E-02 |
16 | 0 | 7.0433378 | 2.9911476 | 7.0433378 | |
17 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
18 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
19 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
20 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
21 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
22 | 7 | -0.18651654E-16 | -0.16428647E-15 | -0.26578847E-08 | -0.25364002E-17 |
23 | 6 | 0.67402962E-01 | 0.99142722E-07 | 0.38101547E-02 | -0.76639482E-03 |
24 | 5 | -1.8580732 | 0.49502125E-04 | -0.10651409 | 0.21891119E-01 |
25 | 4 | 18.220105 | 0.12801333E-02 | 1.0775450 | -0.22586539 |
26 | 3 | -79.928293 | 0.66708484E-02 | -4.9803755 | 1.0625663 |
27 | 2 | 166.43177 | 0.75131194E-02 | 11.128837 | -2.4125483 |
28 | 1 | -159.97298 | 0.18548900E-02 | -11.587784 | 2.5494418 |
29 | 0 | 57.057412 | 0.52755123E-04 | 4.4818272 | |
30 | 7 | 0.43260499E-16 | 0.34524919E-16 | 0.52793240E-17 | 0.0000000 |
31 | 6 | 0.69434179E-09 | 0.98085174E-11 | 0.18162501E-10 | -0.40870994E-12 |
32 | 5 | -0.12888762E-04 | 0.28373718E-06 | -0.16918523E-06 | 0.92361873E-08 |
33 | 4 | 0.25174112E-01 | 0.33697681E-03 | 0.22646198E-03 | -0.31467795E-04 |
34 | 3 | -3.7600775 | 0.27170599E-01 | -0.48495626E-01 | 0.94171705E-02 |
35 | 2 | 51.553741 | 0.22121684 | 1.2284947 | -0.25833933 |
36 | 1 | -128.86110 | 0.21944682 | -5.1479470 | 1.1228340 |
37 | 0 | 81.526494 | 0.16043334E-01 | 4.4519351 | |
38 | 7 | 0.52793240E-17 | 0.34524919E-16 | 0.43260499E-16 | 0.0000000 |
39 | 6 | 0.18162501E-10 | 0.98085174E-11 | 0.69434179E-09 | -0.40870994E-12 |
40 | 5 | -0.16918523E-06 | 0.28373718E-06 | -0.12888762E-04 | 0.92361873E-08 |
41 | 4 | 0.22646198E-03 | 0.33697681E-03 | 0.25174112E-01 | -0.31467795E-04 |
42 | 3 | -0.48495626E-01 | 0.27170599E-01 | -3.7600775 | 0.94171705E-02 |
43 | 2 | 1.2284947 | 0.22121684 | 51.553741 | -0.25833933 |
44 | 1 | -5.1479470 | 0.21944682 | -128.86110 | 1.1228340 |
45 | 0 | 4.4519351 | 0.16043334E-01 | 81.526494 | |
46 | 3 | -0.61927053E-06 | 0.12767249E-08 | -0.37968499E-05 | 0.16832131E-17 |
47 | 2 | 0.77611055 | 0.17315568E-02 | 1.0534842 | -0.72792597E-06 |
48 | 1 | -21.915918 | 0.11588205 | -6.3286394 | 0.20197014 |
49 | 0 | 21.365777 | 0.10835518 | 5.5011278 | |
50 | 9 | -0.34109306E-14 | 0.24909287E-15 | -0.70234472E-12 | 0.65513238E-16 |
51 | 8 | 0.13119258E-09 | 0.66225198E-13 | 0.25869970E-04 | -0.14916918E-11 |
52 | 7 | -0.11009939E-02 | 0.13568249E-07 | -0.65256785E-02 | 0.12518681E-04 |
53 | 6 | 0.10140049 | 0.81303169E-05 | 0.18905580 | -0.11654411E-02 |
54 | 5 | -2.2086417 | 0.46066432E-03 | -2.1793248 | 0.26223950E-01 |
55 | 4 | 19.715055 | 0.51780401E-02 | 12.415669 | -0.24584718 |
56 | 3 | -82.671456 | 0.14472115E-01 | -37.782151 | 1.1032137 |
57 | 2 | 168.49726 | 0.99923307E-02 | 62.094262 | -2.4465849 |
58 | 1 | -160.45852 | 0.12849016E-02 | -51.628788 | 2.5579517 |
59 | 0 | 57.057407 | 0.91053392E-05 | 16.929182 | |
60 | 9 | -0.34109306E-14 | 0.24909287E-15 | -0.70234472E-12 | 0.65513238E-16 |
61 | 8 | 0.13119258E-09 | 0.66225198E-13 | 0.25869970E-04 | -0.14916918E-11 |
62 | 7 | -0.11009939E-02 | 0.13568249E-07 | -0.65256785E-02 | 0.12518681E-04 |
63 | 6 | 0.10140049 | 0.81303169E-05 | 0.18905580 | -0.11654411E-02 |
64 | 5 | -2.2086417 | 0.46066432E-03 | -2.1793248 | 0.26223950E-01 |
65 | 4 | 19.715055 | 0.51780401E-02 | 12.415669 | -0.24584718 |
66 | 3 | -82.671456 | 0.14472115E-01 | -37.782151 | 1.1032137 |
67 | 2 | 168.49726 | 0.99923307E-02 | 62.094262 | -2.4465849 |
68 | 1 | -160.45852 | 0.12849016E-02 | -51.628788 | 2.5579517 |
69 | 0 | 57.057407 | 0.91053392E-05 | 16.929182 | |
70 | 9 | -0.34109306E-14 | 0.24909287E-15 | -0.70234472E-12 | 0.65513238E-16 |
71 | 8 | 0.13119258E-09 | 0.66225198E-13 | 0.25869970E-04 | -0.14916918E-11 |
72 | 7 | -0.11009939E-02 | 0.13568249E-07 | -0.65256785E-02 | 0.12518681E-04 |
73 | 6 | 0.10140049 | 0.81303169E-05 | 0.18905580 | -0.11654411E-02 |
74 | 5 | -2.2086417 | 0.46066432E-03 | -2.1793248 | 0.26223950E-01 |
75 | 4 | 19.715055 | 0.51780401E-02 | 12.415669 | -0.24584718 |
76 | 3 | -82.671456 | 0.14472115E-01 | -37.782151 | 1.1032137 |
77 | 2 | 168.49726 | 0.99923307E-02 | 62.094262 | -2.4465849 |
78 | 1 | -160.45852 | 0.12849016E-02 | -51.628788 | 2.5579517 |
79 | 0 | 57.057407 | 0.91053392E-05 | 16.929182 | |
80 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
81 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
82 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
83 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
84 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
85 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
86 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
87 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
88 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
89 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
90 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
91 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
92 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
93 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
94 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
95 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
96 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
97 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
98 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
99 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
100 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
101 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
102 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
103 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
104 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
105 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
106 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
107 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
108 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
109 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
110 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
111 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
112 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
113 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
114 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
115 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
116 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
117 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
118 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
119 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
120 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
121 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
122 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
123 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
124 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
125 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
126 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
127 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | WINDOW_U_0.57_SHGC_EAST_0.25 | 35 | 1 | VerySmooth | 3.241 | 3.241 | 1.000 | 0.251 | ||
2 | WINDOW_U_0.57_SHGC_SOUTH_0.25 | 36 | 1 | VerySmooth | 3.241 | 3.241 | 1.000 | 0.251 | ||
3 | WINDOW_U_0.57_SHGC_WEST_0.25 | 37 | 1 | VerySmooth | 3.241 | 3.241 | 1.000 | 0.251 | ||
4 | WINDOW_U_0.57_SHGC_NORTH_0.25 | 38 | 1 | VerySmooth | 3.241 | 3.241 | 1.000 | 0.251 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | GLAZING LAYER EAST | SpectralAverage | 2.00000E-003 | 0.16139 | 0.60205 | 0.60205 | 0.27500 | 0.15630 | 0.22588 | 0.00000 | 0.84000 | 0.84000 | 1.43763E-002 | 1.00000 | No | |
2 | GLAZING LAYER SOUTH | SpectralAverage | 2.00000E-003 | 0.16139 | 0.60205 | 0.60205 | 0.27500 | 0.15630 | 0.22588 | 0.00000 | 0.84000 | 0.84000 | 1.43763E-002 | 1.00000 | No | |
3 | GLAZING LAYER WEST | SpectralAverage | 2.00000E-003 | 0.16139 | 0.60205 | 0.60205 | 0.27500 | 0.15630 | 0.22588 | 0.00000 | 0.84000 | 0.84000 | 1.43763E-002 | 1.00000 | No | |
4 | GLAZING LAYER NORTH | SpectralAverage | 2.00000E-003 | 0.16139 | 0.60205 | 0.60205 | 0.27500 | 0.15630 | 0.22588 | 0.00000 | 0.84000 | 0.84000 | 1.43763E-002 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 30 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Enclosure Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Enclosures | |
1 | PERIMETER_BOT_ZN_3 | 5 | 0 |
2 | PERIMETER_BOT_ZN_2 | 3 | 0 |
3 | PERIMETER_BOT_ZN_1 | 5 | 0 |
4 | PERIMETER_BOT_ZN_4 | 3 | 0 |
5 | PERIMETER_MID_ZN_3 | 1 | 0 |
6 | PERIMETER_MID_ZN_2 | 1 | 0 |
7 | PERIMETER_MID_ZN_1 | 1 | 0 |
8 | PERIMETER_MID_ZN_4 | 1 | 0 |
9 | PERIMETER_TOP_ZN_3 | 1 | 0 |
10 | PERIMETER_TOP_ZN_2 | 1 | 0 |
11 | PERIMETER_TOP_ZN_1 | 1 | 0 |
12 | PERIMETER_TOP_ZN_4 | 1 | 0 |
Enclosure Name | Number of Adjacent Enclosures with Windows | Adjacent Enclosure Names - 1st 100 (max) | |
1 | PERIMETER_BOT_ZN_3 | 0 | |
2 | PERIMETER_BOT_ZN_2 | 0 | |
3 | PERIMETER_BOT_ZN_1 | 0 | |
4 | PERIMETER_BOT_ZN_4 | 0 | |
5 | PERIMETER_MID_ZN_3 | 0 | |
6 | PERIMETER_MID_ZN_2 | 0 | |
7 | PERIMETER_MID_ZN_1 | 0 | |
8 | PERIMETER_MID_ZN_4 | 0 | |
9 | PERIMETER_TOP_ZN_3 | 0 | |
10 | PERIMETER_TOP_ZN_2 | 0 | |
11 | PERIMETER_TOP_ZN_1 | 0 | |
12 | PERIMETER_TOP_ZN_4 | 0 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 1.1356 | 87921.3 | 0.481 | 5.5005E-002 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | BASEMENT_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
2 | BASEMENT_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
3 | BASEMENT_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
4 | BASEMENT_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
5 | BASEMENT_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
6 | PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
7 | PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
8 | CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
9 | PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
10 | BASEMENT_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
11 | CORE_BOT_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
12 | CORE_BOT_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
13 | CORE_BOT_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
14 | CORE_BOT_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
15 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
16 | CORE_BOT_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
17 | CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
18 | CORE_BOTTOM_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
19 | CORE_MID_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
20 | CORE_MID_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
21 | CORE_MID_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
22 | CORE_MID_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
23 | CORE_MID_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
24 | CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
25 | CORE_MID_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
26 | CORE_TOP_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
27 | CORE_TOP_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
28 | CORE_TOP_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
29 | CORE_TOP_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
30 | CORE_TOP_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
31 | CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
32 | CORE_TOP_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
33 | PERIMETER_BOT_ZN_3_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
34 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
35 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
36 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
37 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
38 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
39 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
40 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
41 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
42 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
43 | PERIMETER_BOT_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
44 | CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
45 | PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
46 | DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
47 | PERIMETER_BOT_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
48 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
49 | PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
50 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
51 | PERIMETER_BOT_ZN_2_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
52 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
53 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
54 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
55 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
56 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
57 | PERIMETER_BOT_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
58 | CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
59 | PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
60 | PERIMETER_BOT_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
61 | PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
62 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
63 | PERIMETER_BOT_ZN_1_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
64 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
65 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
66 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
67 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
68 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
69 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
70 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
71 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
72 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
73 | PERIMETER_BOT_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
74 | DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
75 | PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
76 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
77 | DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
78 | PERIMETER_BOT_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
79 | PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
80 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
81 | PERIMETER_BOT_ZN_4_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
82 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
83 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
84 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
85 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
86 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
87 | PERIMETER_BOT_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
88 | DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
89 | PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
90 | PERIMETER_BOT_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
91 | PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
92 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
93 | PERIMETER_MID_ZN_3_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
94 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
95 | PERIMETER_MID_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
96 | CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
97 | PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
98 | DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
99 | PERIMETER_MID_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
100 | PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
101 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
102 | PERIMETER_MID_ZN_2_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
103 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
104 | PERIMETER_MID_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
105 | CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
106 | PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
107 | PERIMETER_MID_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
108 | PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
109 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
110 | PERIMETER_MID_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
111 | PERIMETER_MID_ZN_1_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
112 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
113 | DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
114 | PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
115 | CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
116 | PERIMETER_MID_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
117 | PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
118 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
119 | PERIMETER_MID_ZN_4_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
120 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
121 | PERIMETER_MID_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
122 | DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
123 | PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
124 | PERIMETER_MID_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
125 | PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
126 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
127 | PERIMETER_TOP_ZN_3_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
128 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
129 | PERIMETER_TOP_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
130 | CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
131 | PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
132 | DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
133 | PERIMETER_TOP_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
134 | PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
135 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
136 | PERIMETER_TOP_ZN_2_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
137 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
138 | PERIMETER_TOP_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
139 | CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
140 | INT-PER3S-NE-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
141 | PERIMETER_TOP_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
142 | PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
143 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
144 | PERIMETER_TOP_ZN_1_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
145 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
146 | INT-PER3S-NE | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
147 | DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
148 | PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
149 | CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
150 | PERIMETER_TOP_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
151 | PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
152 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
153 | PERIMETER_TOP_ZN_4_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
154 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
155 | PERIMETER_TOP_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
156 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
157 | PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
158 | PERIMETER_TOP_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
159 | PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
160 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
161 | GROUNDFLOOR_PLENUM_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
162 | GROUNDFLOOR_PLENUM_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
163 | GROUNDFLOOR_PLENUM_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
164 | GROUNDFLOOR_PLENUM_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
165 | iz-CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
166 | iz-PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
167 | iz-PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
168 | iz-PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
169 | iz-PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
170 | iz-DATACENTER_BOT_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
171 | GROUNDFLOOR_PLENUM_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
172 | MIDFLOOR_PLENUM_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
173 | MIDFLOOR_PLENUM_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
174 | MIDFLOOR_PLENUM_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
175 | MIDFLOOR_PLENUM_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
176 | iz-CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
177 | iz-PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
178 | iz-PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
179 | iz-PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
180 | iz-PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
181 | iz-DATACENTER_MID_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
182 | MIDFLOOR_PLENUM_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
183 | TOPFLOOR_PLENUM_WALL_NORTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
184 | TOPFLOOR_PLENUM_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
185 | TOPFLOOR_PLENUM_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
186 | TOPFLOOR_PLENUM_WALL_SOUTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
187 | iz-CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
188 | iz-PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
189 | iz-PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
190 | iz-PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
191 | iz-PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
192 | iz-DATACENTER_TOP_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
193 | BUILDING_ROOF | 0 | 3563.11 | 268.06 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
194 | DATACENTER_BOT_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
195 | DATACENTER_BOT_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
196 | DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
197 | DATACENTER_BOT_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
198 | DATACENTER_BOT_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
199 | DATACENTER_BOT_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
200 | DATACENTER_MID_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
201 | DATACENTER_MID_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
202 | DATACENTER_MID_ZN_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
203 | DATACENTER_MID_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
204 | DATACENTER_MID_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
205 | DATACENTER_MID_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
206 | DATACENTER_TOP_ZN_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
207 | DATACENTER_TOP_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
208 | DATACENTER_TOP_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
209 | DATACENTER_TOP_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
210 | DATACENTER_TOP_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
211 | DATACENTER_TOP_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
212 | DATACENTER_BASEMENT_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
213 | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
214 | DATACENTER_BASEMENT_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
215 | DATACENTER_BASEMENT_ZN_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
216 | DATACENTER_BASEMENT_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
217 | DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
218 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
219 | PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
220 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
221 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | PERIMETER_BOT_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 0.114 | 3.646E-004 | 5.482E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | PERIMETER_BOT_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 7.617E-002 | 3.771E-004 | 5.534E-004 | 0.495 | 0.000 | 0.000 | 0.224 | 0.000 |
3 | PERIMETER_BOT_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 0.114 | 3.646E-004 | 5.482E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | PERIMETER_BOT_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 7.617E-002 | 3.771E-004 | 5.534E-004 | 0.495 | 0.000 | 0.000 | 0.224 | 0.000 |
5 | PERIMETER_MID_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 0.114 | 3.646E-004 | 5.696E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
6 | PERIMETER_MID_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 7.617E-002 | 3.771E-004 | 5.696E-004 | 0.495 | 0.000 | 0.000 | 0.224 | 0.000 |
7 | PERIMETER_MID_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 0.114 | 3.646E-004 | 5.696E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
8 | PERIMETER_MID_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 7.617E-002 | 3.771E-004 | 5.696E-004 | 0.495 | 0.000 | 0.000 | 0.224 | 0.000 |
9 | PERIMETER_TOP_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 0.114 | 3.646E-004 | 5.696E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
10 | PERIMETER_TOP_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 7.617E-002 | 3.771E-004 | 5.696E-004 | 0.495 | 0.000 | 0.000 | 0.224 | 0.000 |
11 | PERIMETER_TOP_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 0.114 | 3.646E-004 | 5.696E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
12 | PERIMETER_TOP_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 7.617E-002 | 3.771E-004 | 5.696E-004 | 0.495 | 0.000 | 0.000 | 0.224 | 0.000 |
13 | GROUNDFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | GROUNDFLOOR_PLENUM | 3563.11 | 0.0 | 0.169 | 4.749E-005 | 5.696E-004 | 0.140 | 0.000 | 0.000 | 0.224 | 0.000 |
14 | MIDFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | MIDFLOOR_PLENUM | 3563.11 | 0.0 | 0.169 | 4.749E-005 | 5.696E-004 | 0.140 | 0.000 | 0.000 | 0.224 | 0.000 |
15 | TOPFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | TOPFLOOR_PLENUM | 3563.11 | 0.0 | 0.169 | 4.749E-005 | 4.384E-005 | 0.140 | 0.000 | 0.000 | 0.224 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | BASEMENT | Mixing/Well-Stirred |
2 | CORE_BOTTOM | Mixing/Well-Stirred |
3 | CORE_MID | Mixing/Well-Stirred |
4 | CORE_TOP | Mixing/Well-Stirred |
5 | PERIMETER_BOT_ZN_3 | Mixing/Well-Stirred |
6 | PERIMETER_BOT_ZN_2 | Mixing/Well-Stirred |
7 | PERIMETER_BOT_ZN_1 | Mixing/Well-Stirred |
8 | PERIMETER_BOT_ZN_4 | Mixing/Well-Stirred |
9 | PERIMETER_MID_ZN_3 | Mixing/Well-Stirred |
10 | PERIMETER_MID_ZN_2 | Mixing/Well-Stirred |
11 | PERIMETER_MID_ZN_1 | Mixing/Well-Stirred |
12 | PERIMETER_MID_ZN_4 | Mixing/Well-Stirred |
13 | PERIMETER_TOP_ZN_3 | Mixing/Well-Stirred |
14 | PERIMETER_TOP_ZN_2 | Mixing/Well-Stirred |
15 | PERIMETER_TOP_ZN_1 | Mixing/Well-Stirred |
16 | PERIMETER_TOP_ZN_4 | Mixing/Well-Stirred |
17 | GROUNDFLOOR_PLENUM | Mixing/Well-Stirred |
18 | MIDFLOOR_PLENUM | Mixing/Well-Stirred |
19 | TOPFLOOR_PLENUM | Mixing/Well-Stirred |
20 | DATACENTER_BOT_ZN_6 | Mixing/Well-Stirred |
21 | DATACENTER_MID_ZN_6 | Mixing/Well-Stirred |
22 | DATACENTER_TOP_ZN_6 | Mixing/Well-Stirred |
23 | DATACENTER_BASEMENT_ZN_6 | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sky Type | MonthAndDay | Daylighting Control Name | Enclosure Name | Window Name | Reference Point | Daylight Factor | |
1 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 3.5981E-003 |
2 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 3.5994E-003 |
3 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 3.7702E-003 |
4 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 3.7713E-003 |
5 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.9649E-003 |
6 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.9656E-003 |
7 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.7585E-003 |
8 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.7591E-003 |
9 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 3.6289E-003 |
10 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 3.7146E-003 |
11 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 3.7953E-003 |
12 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 3.8669E-003 |
13 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.9842E-003 |
14 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 3.0407E-003 |
15 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.7734E-003 |
16 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.8107E-003 |
17 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 8.8257E-002 |
18 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 3.4930E-002 |
19 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 9.5831E-002 |
20 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 3.6319E-002 |
21 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 7.1582E-002 |
22 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.5632E-002 |
23 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 3.1622E-002 |
24 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.0968E-002 |
25 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 3.6351E-003 |
26 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 3.7442E-003 |
27 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 3.8020E-003 |
28 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 3.8985E-003 |
29 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.9904E-003 |
30 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 3.0642E-003 |
31 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.7738E-003 |
32 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.8117E-003 |
33 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 3.5980E-003 |
34 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 3.5995E-003 |
35 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 3.7701E-003 |
36 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 3.7714E-003 |
37 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.9648E-003 |
38 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.9658E-003 |
39 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.7585E-003 |
40 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.7590E-003 |
41 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.8568E-003 |
42 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.9960E-003 |
43 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.6744E-003 |
44 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.8154E-003 |
45 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.4874E-003 |
46 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.5631E-003 |
47 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.0071E-003 |
48 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.0329E-003 |
49 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 4.3047E-002 |
50 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 2.0149E-002 |
51 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 4.0248E-002 |
52 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 1.8190E-002 |
53 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 4.0940E-002 |
54 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 1.6413E-002 |
55 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.2931E-002 |
56 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 1.2292E-002 |
57 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.8263E-003 |
58 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.8870E-003 |
59 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.6367E-003 |
60 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.6813E-003 |
61 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.4650E-003 |
62 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.4837E-003 |
63 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.0072E-003 |
64 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.0333E-003 |
65 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.7049E-003 |
66 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.7063E-003 |
67 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.4715E-003 |
68 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.4727E-003 |
69 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.3035E-003 |
70 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.3043E-003 |
71 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.7586E-003 |
72 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.7591E-003 |
73 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.7367E-003 |
74 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.8149E-003 |
75 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.4975E-003 |
76 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.5598E-003 |
77 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.3236E-003 |
78 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.3675E-003 |
79 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.7738E-003 |
80 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.8118E-003 |
81 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.6013E-002 |
82 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.3409E-002 |
83 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.0222E-002 |
84 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.0283E-002 |
85 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.7815E-002 |
86 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 6.9390E-003 |
87 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.1622E-002 |
88 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.0965E-002 |
89 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.7344E-003 |
90 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.8116E-003 |
91 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.4946E-003 |
92 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.5538E-003 |
93 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.3188E-003 |
94 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.3529E-003 |
95 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.7735E-003 |
96 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.8107E-003 |
97 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.7048E-003 |
98 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.7061E-003 |
99 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.4714E-003 |
100 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.4725E-003 |
101 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.3034E-003 |
102 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.3040E-003 |
103 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.7585E-003 |
104 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.7591E-003 |
105 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.3109E-003 |
106 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.3741E-003 |
107 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.0170E-003 |
108 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.0628E-003 |
109 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 2.9686E-003 |
110 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.9855E-003 |
111 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.0073E-003 |
112 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.0334E-003 |
113 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.4211E-002 |
114 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 1.6906E-002 |
115 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 2.9738E-002 |
116 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 1.4346E-002 |
117 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.1967E-002 |
118 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 1.3073E-002 |
119 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.2931E-002 |
120 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 1.2292E-002 |
121 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.3353E-003 |
122 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.4471E-003 |
123 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.0477E-003 |
124 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.1557E-003 |
125 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 2.9895E-003 |
126 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.0563E-003 |
127 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.0071E-003 |
128 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.0328E-003 |
129 | Clear Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 9.3555E-002 |
130 | Clear Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 5.2004E-002 |
131 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 9.9408E-002 |
132 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 5.4102E-002 |
133 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 7.9737E-002 |
134 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 3.9538E-002 |
135 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 3.8788E-002 |
136 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 1.9168E-002 |
137 | Clear Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 5.1385E-002 |
138 | Clear Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 2.9313E-002 |
139 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 4.8271E-002 |
140 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 2.6926E-002 |
141 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 4.8767E-002 |
142 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 2.4658E-002 |
143 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 3.9762E-002 |
144 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 1.9389E-002 |
145 | Clear Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 3.2812E-002 |
146 | Clear Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 2.1602E-002 |
147 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 2.6218E-002 |
148 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 1.7302E-002 |
149 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 2.3491E-002 |
150 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 1.3046E-002 |
151 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 3.8788E-002 |
152 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 1.9165E-002 |
153 | Clear Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 4.1362E-002 |
154 | Clear Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 2.4798E-002 |
155 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 3.6335E-002 |
156 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 2.1553E-002 |
157 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 3.8675E-002 |
158 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 2.0128E-002 |
159 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 3.9762E-002 |
160 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 1.9389E-002 |
161 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 9.3681E-002 |
162 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 5.2114E-002 |
163 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 9.9560E-002 |
164 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 5.4224E-002 |
165 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 7.9889E-002 |
166 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 3.9636E-002 |
167 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 3.8871E-002 |
168 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 1.9210E-002 |
169 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 5.1435E-002 |
170 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 2.9360E-002 |
171 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 4.8328E-002 |
172 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 2.6971E-002 |
173 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 4.8852E-002 |
174 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 2.4711E-002 |
175 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 3.9845E-002 |
176 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 1.9432E-002 |
177 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 3.2819E-002 |
178 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 2.1627E-002 |
179 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 2.6227E-002 |
180 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 1.7322E-002 |
181 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 2.3529E-002 |
182 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 1.3069E-002 |
183 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 3.8871E-002 |
184 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 1.9207E-002 |
185 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 4.1391E-002 |
186 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 2.4833E-002 |
187 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 3.6366E-002 |
188 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 2.1584E-002 |
189 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 3.8739E-002 |
190 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 2.0168E-002 |
191 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 3.9845E-002 |
192 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 1.9432E-002 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | BASEMENT | Cooling | 84401.13308 | 84401.13308 | 6.08554 | 6.08554 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 28.24200 | 1.71578E-002 | 2779.42662 | 149.60210 | 1.20016 | 0.00000 |
2 | BASEMENT | Heating | 0.00000 | 0.00000 | 0.00000 | 1.20016 | 00:10:00 | 8.70000 | 6.99286E-003 | 2779.42662 | 149.60210 | 1.20016 | 0.00000 | |
3 | CORE_BOTTOM | Cooling | 87138.27798 | 87138.27798 | 6.28218 | 6.28218 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 28.24200 | 1.71578E-002 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 |
4 | CORE_BOTTOM | Heating | 0.00000 | 0.00000 | 0.00000 | 1.07782 | 00:10:00 | 8.70000 | 6.99286E-003 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 | |
5 | CORE_MID | Cooling | 823926.45425 | 823926.45425 | 59.38696 | 59.38696 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 28.24200 | 1.71578E-002 | 2496.12046 | 134.35320 | 10.77825 | 0.00000 |
6 | CORE_MID | Heating | 210357.20338 | 210357.20338 | 8.85854 | 10.77825 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 8.70000 | 6.99286E-003 | 2496.12046 | 134.35320 | 10.77825 | 0.00000 |
7 | CORE_TOP | Cooling | 80953.61020 | 80953.61020 | 5.83476 | 5.83476 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 28.24200 | 1.71578E-002 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 |
8 | CORE_TOP | Heating | 42783.39819 | 42783.39819 | 1.81459 | 1.81459 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 8.70000 | 6.99286E-003 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 |
9 | PERIMETER_BOT_ZN_3 | Cooling | 15234.01961 | 15234.01961 | 1.10822 | 1.10822 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:30:00 | 31.92700 | 1.71648E-002 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
10 | PERIMETER_BOT_ZN_3 | Heating | 4317.02215 | 4317.02215 | 0.18275 | 0.18275 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 8.70000 | 6.99286E-003 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
11 | PERIMETER_BOT_ZN_2 | Cooling | 15258.57388 | 15258.57388 | 1.11000 | 1.11000 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 09:40:00 | 30.27433 | 1.71616E-002 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
12 | PERIMETER_BOT_ZN_2 | Heating | 3166.69443 | 3166.69443 | 0.13424 | 0.13424 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 8.70000 | 6.99286E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
13 | PERIMETER_BOT_ZN_1 | Cooling | 15190.27594 | 15190.27594 | 1.10504 | 1.10504 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | 33.20000 | 1.71672E-002 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
14 | PERIMETER_BOT_ZN_1 | Heating | 5851.73878 | 5851.73878 | 0.24837 | 0.24837 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 8.70000 | 6.99286E-003 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
15 | PERIMETER_BOT_ZN_4 | Cooling | 19755.40458 | 19755.40458 | 1.43712 | 1.43712 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 32.26200 | 1.71654E-002 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
16 | PERIMETER_BOT_ZN_4 | Heating | 1824.37840 | 1824.37840 | 7.69994E-002 | 8.72129E-002 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 8.70000 | 6.99286E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
17 | PERIMETER_MID_ZN_3 | Cooling | 146063.19737 | 146063.19737 | 10.62656 | 10.62656 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:40:00 | 31.81533 | 1.71646E-002 | 313.41284 | 16.86939 | 1.35332 | 0.00000 |
18 | PERIMETER_MID_ZN_3 | Heating | 113335.61067 | 113335.61067 | 4.83028 | 4.83028 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 8.70000 | 6.99286E-003 | 313.41284 | 16.86939 | 1.35332 | 0.00000 |
19 | PERIMETER_MID_ZN_2 | Cooling | 157821.56589 | 157821.56589 | 11.48194 | 11.48194 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 09:50:00 | 30.46417 | 1.71620E-002 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
20 | PERIMETER_MID_ZN_2 | Heating | 74692.14290 | 74692.14290 | 3.18361 | 3.18361 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 8.70000 | 6.99286E-003 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
21 | PERIMETER_MID_ZN_1 | Cooling | 144835.12005 | 144835.12005 | 10.53721 | 10.53721 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 33.20000 | 1.71672E-002 | 313.41969 | 16.86975 | 1.35335 | 0.00000 |
22 | PERIMETER_MID_ZN_1 | Heating | 112252.17766 | 112252.17766 | 4.78391 | 4.78391 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 8.70000 | 6.99286E-003 | 313.41969 | 16.86975 | 1.35335 | 0.00000 |
23 | PERIMETER_MID_ZN_4 | Cooling | 175045.27115 | 175045.27115 | 12.73497 | 12.73497 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 | 32.15033 | 1.71652E-002 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
24 | PERIMETER_MID_ZN_4 | Heating | 68672.55571 | 68672.55571 | 2.92617 | 2.92617 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 8.70000 | 6.99286E-003 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
25 | PERIMETER_TOP_ZN_3 | Cooling | 16195.56100 | 16195.56100 | 1.17832 | 1.17832 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 32.26200 | 1.71654E-002 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
26 | PERIMETER_TOP_ZN_3 | Heating | 13890.67886 | 13890.67886 | 0.59245 | 0.59245 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 8.70000 | 6.99286E-003 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
27 | PERIMETER_TOP_ZN_2 | Cooling | 15984.07537 | 15984.07537 | 1.16293 | 1.16293 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 10:00:00 | 30.65400 | 1.71624E-002 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
28 | PERIMETER_TOP_ZN_2 | Heating | 9105.62901 | 9105.62901 | 0.38839 | 0.38839 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 8.70000 | 6.99286E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
29 | PERIMETER_TOP_ZN_1 | Cooling | 16206.86265 | 16206.86265 | 1.17914 | 1.17914 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | 33.20000 | 1.71672E-002 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
30 | PERIMETER_TOP_ZN_1 | Heating | 13792.84855 | 13792.84855 | 0.58827 | 0.58827 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 8.70000 | 6.99286E-003 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
31 | PERIMETER_TOP_ZN_4 | Cooling | 18590.08459 | 18590.08459 | 1.35252 | 1.35252 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 32.26200 | 1.71654E-002 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
32 | PERIMETER_TOP_ZN_4 | Heating | 8650.33248 | 8650.33248 | 0.36891 | 0.36891 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 8.70000 | 6.99286E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
33 | DATACENTER_BOT_ZN_6 | Cooling | 8367.75144 | 8367.75144 | 0.48009 | 0.48009 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 18:50:00 | 30.75450 | 1.71626E-002 | 36.20274 | 1.94861 | 1.56323E-002 | 0.00000 |
34 | DATACENTER_BOT_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 1.56323E-002 | 00:10:00 | 8.70000 | 6.99286E-003 | 36.20274 | 1.94861 | 1.56323E-002 | 0.00000 | |
35 | DATACENTER_MID_ZN_6 | Cooling | 79797.70584 | 79797.70584 | 4.57834 | 4.57834 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 18:50:00 | 30.75450 | 1.71626E-002 | 36.20274 | 1.94861 | 0.15632 | 0.00000 |
36 | DATACENTER_MID_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 0.15632 | 00:10:00 | 8.70000 | 6.99286E-003 | 36.20274 | 1.94861 | 0.15632 | 0.00000 | |
37 | DATACENTER_TOP_ZN_6 | Cooling | 8138.00445 | 8138.00445 | 0.46691 | 0.46691 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | 30.92200 | 1.71629E-002 | 36.20274 | 1.94861 | 1.56323E-002 | 0.00000 |
38 | DATACENTER_TOP_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 1.56323E-002 | 00:10:00 | 8.70000 | 6.99286E-003 | 36.20274 | 1.94861 | 1.56323E-002 | 0.00000 | |
39 | DATACENTER_BASEMENT_ZN_6 | Cooling | 373513.38396 | 373513.38396 | 21.42960 | 21.42960 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 07:00:00 | 27.10300 | 1.71556E-002 | 783.67941 | 42.18139 | 0.33839 | 0.00000 |
40 | DATACENTER_BASEMENT_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 0.33839 | 00:10:00 | 8.70000 | 6.99286E-003 | 783.67941 | 42.18139 | 0.33839 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | VAV_BOT WITH REHEAT | Cooling | Sensible | 159633.71 | 10.13854 | 10.13854 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
2 | VAV_BOT WITH REHEAT | Heating | Sensible | 8574.42 | 1.73039 | 1.73039 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 |
3 | VAV_MID WITH REHEAT | Cooling | Sensible | 1478661.17 | 95.07637 | 95.07637 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
4 | VAV_MID WITH REHEAT | Heating | Sensible | 125073.25 | 26.50222 | 26.50222 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:30:00 |
5 | VAV_TOP WITH REHEAT | Cooling | Sensible | 166479.01 | 10.29385 | 10.29385 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
6 | VAV_TOP WITH REHEAT | Heating | Sensible | 12533.24 | 3.75261 | 3.75261 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:30:00 |
7 | CAV_BAS | Cooling | Sensible | 88889.27 | 6.08554 | 6.08554 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
8 | CAV_BAS | Heating | Sensible | 45400.28 | 1.20016 | 1.20016 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
9 | AIRLOOP DATACENTER BASEMENT | Cooling | Sensible | 369754.24 | 21.42976 | 21.42976 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
10 | AIRLOOP DATACENTER BASEMENT | Heating | Sensible | 12800.94 | 0.33839 | 0.33839 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
11 | AIRLOOP DATACENTER BOT | Cooling | Sensible | 8311.65 | 0.48009 | 0.48009 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
12 | AIRLOOP DATACENTER BOT | Heating | Sensible | 591.35 | 1.56323E-002 | 1.56323E-002 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
13 | AIRLOOP DATACENTER MID | Cooling | Sensible | 79277.73 | 4.57834 | 4.57834 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
14 | AIRLOOP DATACENTER MID | Heating | Sensible | 5913.50 | 0.15632 | 0.15632 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
15 | AIRLOOP DATACENTER TOP | Cooling | Sensible | 8086.29 | 0.46691 | 0.46691 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
16 | AIRLOOP DATACENTER TOP | Heating | Sensible | 591.35 | 1.56323E-002 | 1.56323E-002 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | BASEMENT DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 6.08554 |
2 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 6.28218 |
3 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.30277 |
4 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.31200 |
5 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.96004 |
6 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.80738 |
7 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
8 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.25839E-003 |
9 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.72448E-004 |
10 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.96004 |
11 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
12 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
13 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 19711.84217 |
14 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.72448E-004 |
15 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 397.37527 |
16 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 59.38696 |
17 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.32028 |
18 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.32400 |
19 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 19.24138 |
20 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.85408 |
21 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
22 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.18959E-003 |
23 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 3.53319E-003 |
24 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 19.24138 |
25 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
26 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
27 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 403865.23068 |
28 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.53319E-003 |
29 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 9127.62730 |
30 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 5.83476 |
31 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.32599 |
32 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.33700 |
33 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.96631 |
34 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.86929 |
35 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
36 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.16876E-003 |
37 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 5.47288E-004 |
38 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.96631 |
39 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
40 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
41 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 62558.33989 |
42 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 5.47288E-004 |
43 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 1613.26821 |
44 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.10822 |
45 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.21550 |
46 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.22200 |
47 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.24602 |
48 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.57466 |
49 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
50 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.76799E-003 |
51 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 5.93998E-005 |
52 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.24602 |
53 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
54 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
55 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 6789.76202 |
56 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 5.93998E-005 |
57 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 165.89050 |
58 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.11000 |
59 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.13865 |
60 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
61 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.22200 |
62 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.36974 |
63 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
64 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.74786E-003 |
65 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 4.72248E-005 |
66 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.22200 |
67 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
68 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
69 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 5398.09038 |
70 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 4.72248E-005 |
71 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 126.75300 |
72 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.10504 |
73 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.21612 |
74 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.22300 |
75 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.24642 |
76 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.57633 |
77 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
78 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.76287E-003 |
79 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 7.30355E-005 |
80 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.24837 |
81 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
82 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
83 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 8348.40531 |
84 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 7.30355E-005 |
85 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 220.55220 |
86 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.43712 |
87 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.10709 |
88 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
89 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.28742 |
90 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
91 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
92 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.55766E-003 |
93 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 4.12268E-005 |
94 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.28742 |
95 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
96 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
97 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 4712.47124 |
98 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 4.12268E-005 |
99 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 101.30302 |
100 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 10.62656 |
101 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.22474 |
102 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.22700 |
103 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.41223 |
104 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.59930 |
105 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
106 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.69530E-003 |
107 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.41636E-003 |
108 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 4.83028 |
109 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
110 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
111 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 161898.76348 |
112 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.41636E-003 |
113 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 4271.51435 |
114 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 11.48194 |
115 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.13404 |
116 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
117 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.29639 |
118 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.35744 |
119 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
120 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.84242E-003 |
121 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 9.33458E-004 |
122 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 3.18361 |
123 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
124 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
125 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 106699.92874 |
126 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 9.33458E-004 |
127 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 2815.07494 |
128 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 10.53721 |
129 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.22665 |
130 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.22900 |
131 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.41302 |
132 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.60440 |
133 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
134 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.68101E-003 |
135 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.40280E-003 |
136 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 4.78391 |
137 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
138 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
139 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 160348.88821 |
140 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.40280E-003 |
141 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 4230.67750 |
142 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 12.73497 |
143 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.12085 |
144 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
145 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.54699 |
146 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.32227 |
147 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
148 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.15261E-003 |
149 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 8.58142E-004 |
150 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 2.92617 |
151 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
152 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
153 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 98090.89339 |
154 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 8.58142E-004 |
155 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 2588.17575 |
156 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.17832 |
157 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.20268 |
158 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.21000 |
159 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.24745 |
160 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.54048 |
161 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
162 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.87982E-003 |
163 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.73633E-004 |
164 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.59245 |
165 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
166 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
167 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 19847.34748 |
168 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.73633E-004 |
169 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 523.52648 |
170 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.16293 |
171 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.13234 |
172 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
173 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.23259 |
174 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.35291 |
175 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
176 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.87889E-003 |
177 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.13822E-004 |
178 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.38839 |
179 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
180 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
181 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 13010.56158 |
182 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.13822E-004 |
183 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 343.18180 |
184 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.17914 |
185 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.20254 |
186 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20900 |
187 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.24644 |
188 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.54011 |
189 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
190 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.88109E-003 |
191 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.72409E-004 |
192 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.58827 |
193 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
194 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
195 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 19707.39911 |
196 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.72409E-004 |
197 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 519.83915 |
198 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.35252 |
199 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.11379 |
200 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
201 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.27050 |
202 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30344 |
203 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
204 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.34824E-003 |
205 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.08125E-004 |
206 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.36891 |
207 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
208 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
209 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 12359.32649 |
210 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.08125E-004 |
211 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 326.02045 |
212 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DATACENTER_BOT_ZN_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.48009 |
213 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DATACENTER_MID_ZN_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 4.57834 |
214 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DATACENTER_TOP_ZN_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.46691 |
215 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DATACENTER_BASEMENT_ZN_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 21.42960 |
216 | AirLoopHVAC | VAV_BOT WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 5.52128 |
217 | AirLoopHVAC | VAV_BOT WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.96191 |
218 | AirLoopHVAC | VAV_BOT WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 11.04255 |
219 | AirLoopHVAC | VAV_BOT WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 2.96191 |
220 | AirLoopHVAC | VAV_BOT WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 10.13854 |
221 | AirLoopHVAC | VAV_BOT WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 10.13854 |
222 | AirLoopHVAC | VAV_BOT WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
223 | AirLoopHVAC | VAV_BOT WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.29214 |
224 | AirLoopHVAC | VAV_MID WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 52.38383 |
225 | AirLoopHVAC | VAV_MID WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 28.91001 |
226 | AirLoopHVAC | VAV_MID WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 104.76765 |
227 | AirLoopHVAC | VAV_MID WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 28.91001 |
228 | AirLoopHVAC | VAV_MID WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 95.07637 |
229 | AirLoopHVAC | VAV_MID WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 95.07637 |
230 | AirLoopHVAC | VAV_MID WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
231 | AirLoopHVAC | VAV_MID WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.30407 |
232 | AirLoopHVAC | VAV_TOP WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 5.35383 |
233 | AirLoopHVAC | VAV_TOP WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.96329 |
234 | AirLoopHVAC | VAV_TOP WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 10.70767 |
235 | AirLoopHVAC | VAV_TOP WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 3.75261 |
236 | AirLoopHVAC | VAV_TOP WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 10.29385 |
237 | AirLoopHVAC | VAV_TOP WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 10.29385 |
238 | AirLoopHVAC | VAV_TOP WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
239 | AirLoopHVAC | VAV_TOP WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.36455 |
240 | AirLoopHVAC | CAV_BAS | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 6.08554 |
241 | AirLoopHVAC | CAV_BAS | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 6.08554 |
242 | AirLoopHVAC | CAV_BAS | Sum of Air Terminal Maximum Flow Rates [m3/s] | 6.08554 |
243 | AirLoopHVAC | CAV_BAS | Adjusted Heating Design Air Flow Rate [m3/s] | 6.08554 |
244 | AirLoopHVAC | CAV_BAS | Adjusted Cooling Design Air Flow Rate [m3/s] | 6.08554 |
245 | AirLoopHVAC | CAV_BAS | Adjusted Main Design Air Flow Rate [m3/s] | 6.08554 |
246 | AirLoopHVAC | CAV_BAS | User Heating Air Flow Ratio [] | 1.00000 |
247 | AirLoopHVAC | CAV_BAS | Calculated Heating Air Flow Ratio [] | 1.00000 |
248 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 21.42960 |
249 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 21.42960 |
250 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 21.42960 |
251 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Adjusted Heating Design Air Flow Rate [m3/s] | 21.42960 |
252 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Adjusted Cooling Design Air Flow Rate [m3/s] | 21.42976 |
253 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Adjusted Main Design Air Flow Rate [m3/s] | 21.42976 |
254 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | User Heating Air Flow Ratio [] | 1.00000 |
255 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Calculated Heating Air Flow Ratio [] | 0.99999 |
256 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.48009 |
257 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.48009 |
258 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.48009 |
259 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Adjusted Heating Design Air Flow Rate [m3/s] | 0.48009 |
260 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.48009 |
261 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Adjusted Main Design Air Flow Rate [m3/s] | 0.48009 |
262 | AirLoopHVAC | AIRLOOP DATACENTER BOT | User Heating Air Flow Ratio [] | 1.00000 |
263 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Calculated Heating Air Flow Ratio [] | 1.00000 |
264 | AirLoopHVAC | AIRLOOP DATACENTER MID | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 4.57834 |
265 | AirLoopHVAC | AIRLOOP DATACENTER MID | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 4.57834 |
266 | AirLoopHVAC | AIRLOOP DATACENTER MID | Sum of Air Terminal Maximum Flow Rates [m3/s] | 4.57834 |
267 | AirLoopHVAC | AIRLOOP DATACENTER MID | Adjusted Heating Design Air Flow Rate [m3/s] | 4.57834 |
268 | AirLoopHVAC | AIRLOOP DATACENTER MID | Adjusted Cooling Design Air Flow Rate [m3/s] | 4.57834 |
269 | AirLoopHVAC | AIRLOOP DATACENTER MID | Adjusted Main Design Air Flow Rate [m3/s] | 4.57834 |
270 | AirLoopHVAC | AIRLOOP DATACENTER MID | User Heating Air Flow Ratio [] | 1.00000 |
271 | AirLoopHVAC | AIRLOOP DATACENTER MID | Calculated Heating Air Flow Ratio [] | 1.00000 |
272 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.46691 |
273 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.46691 |
274 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.46691 |
275 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Adjusted Heating Design Air Flow Rate [m3/s] | 0.46691 |
276 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.46691 |
277 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Adjusted Main Design Air Flow Rate [m3/s] | 0.46691 |
278 | AirLoopHVAC | AIRLOOP DATACENTER TOP | User Heating Air Flow Ratio [] | 1.00000 |
279 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Calculated Heating Air Flow Ratio [] | 1.00000 |
280 | AirLoopHVAC | VAV_BOT WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 10.13854 |
281 | AirLoopHVAC | VAV_MID WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 95.07637 |
282 | AirLoopHVAC | VAV_TOP WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 10.29385 |
283 | AirLoopHVAC | CAV_BAS | Design Supply Air Flow Rate [m3/s] | 6.08554 |
284 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Design Supply Air Flow Rate [m3/s] | 21.42976 |
285 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Design Supply Air Flow Rate [m3/s] | 0.48009 |
286 | AirLoopHVAC | AIRLOOP DATACENTER MID | Design Supply Air Flow Rate [m3/s] | 4.57834 |
287 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Design Supply Air Flow Rate [m3/s] | 0.46691 |
288 | Controller:OutdoorAir | VAV_BOT WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 10.13854 |
289 | Controller:OutdoorAir | VAV_BOT WITH REHEAT_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 2.53819 |
290 | HeatExchanger:AirToAir:SensibleAndLatent | VAV_BOT WITH REHEAT OA HEAT RECOVERY | Design Size Nominal Supply Air Flow Rate [m3/s] | 2.53819 |
291 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Inlet Air Temperature [C] | 26.38270 |
292 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
293 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Outlet Air Temperature [C] | 11.05710 |
294 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 1.10518E-002 |
295 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
296 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Coil Load [W] | 270084.32047 |
297 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 1.14900E-002 |
298 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 10.13854 |
299 | Coil:Heating:Water | VAV_BOT WITH REHEAT HEATING COIL | Design Size Rated Capacity [W] | 15573.04163 |
300 | Coil:Heating:Water | VAV_BOT WITH REHEAT HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.36240E-004 |
301 | Coil:Heating:Water | VAV_BOT WITH REHEAT HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 276.83179 |
302 | Fan:VariableVolume | VAV_BOT WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 10.13854 |
303 | Controller:WaterCoil | VAV_BOT WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 1.14900E-002 |
304 | Controller:WaterCoil | VAV_BOT WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 4.14439E-005 |
305 | Controller:WaterCoil | VAV_BOT WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 1.36240E-004 |
306 | Controller:OutdoorAir | VAV_MID WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 95.07637 |
307 | Controller:OutdoorAir | VAV_MID WITH REHEAT_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 25.38195 |
308 | HeatExchanger:AirToAir:SensibleAndLatent | VAV_MID WITH REHEAT OA HEAT RECOVERY | Design Size Nominal Supply Air Flow Rate [m3/s] | 25.38195 |
309 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Inlet Air Temperature [C] | 26.56914 |
310 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
311 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Outlet Air Temperature [C] | 11.04875 |
312 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 1.13524E-002 |
313 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
314 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Coil Load [W] | 2643274.95203 |
315 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 0.11245 |
316 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 95.07637 |
317 | Coil:Heating:Water | VAV_MID WITH REHEAT HEATING COIL | Design Size Rated Capacity [W] | 94643.34428 |
318 | Coil:Heating:Water | VAV_MID WITH REHEAT HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 8.27981E-004 |
319 | Coil:Heating:Water | VAV_MID WITH REHEAT HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 1701.60742 |
320 | Fan:VariableVolume | VAV_MID WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 95.07637 |
321 | Controller:WaterCoil | VAV_MID WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 0.11245 |
322 | Controller:WaterCoil | VAV_MID WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 4.23465E-006 |
323 | Controller:WaterCoil | VAV_MID WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 8.27981E-004 |
324 | Controller:OutdoorAir | VAV_TOP WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 10.29385 |
325 | Controller:OutdoorAir | VAV_TOP WITH REHEAT_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 2.53819 |
326 | HeatExchanger:AirToAir:SensibleAndLatent | VAV_TOP WITH REHEAT OA HEAT RECOVERY | Design Size Nominal Supply Air Flow Rate [m3/s] | 2.53819 |
327 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Inlet Air Temperature [C] | 26.22441 |
328 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
329 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Outlet Air Temperature [C] | 11.05699 |
330 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 1.10149E-002 |
331 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
332 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Coil Load [W] | 271050.54438 |
333 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 1.15311E-002 |
334 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 10.29385 |
335 | Coil:Heating:Water | VAV_TOP WITH REHEAT HEATING COIL | Design Size Rated Capacity [W] | 7127.01262 |
336 | Coil:Heating:Water | VAV_TOP WITH REHEAT HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 6.23502E-005 |
337 | Coil:Heating:Water | VAV_TOP WITH REHEAT HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 128.97735 |
338 | Fan:VariableVolume | VAV_TOP WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 10.29385 |
339 | Controller:WaterCoil | VAV_TOP WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 1.15311E-002 |
340 | Controller:WaterCoil | VAV_TOP WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 4.12961E-005 |
341 | Controller:WaterCoil | VAV_TOP WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 6.23502E-005 |
342 | Controller:OutdoorAir | CAV_BAS_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 6.08554 |
343 | Controller:OutdoorAir | CAV_BAS_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.20016 |
344 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Inlet Air Temperature [C] | 24.88576 |
345 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
346 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Outlet Air Temperature [C] | 11.42379 |
347 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 1.05388E-002 |
348 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
349 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Coil Load [W] | 138576.71127 |
350 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 5.89537E-003 |
351 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 6.08554 |
352 | Coil:Heating:Water | CAV_BAS HEATING COIL | Design Size Rated Capacity [W] | 281575.79388 |
353 | Coil:Heating:Water | CAV_BAS HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.46335E-003 |
354 | Coil:Heating:Water | CAV_BAS HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 6431.56288 |
355 | Fan:ConstantVolume | CAV_BAS FAN | Design Size Maximum Flow Rate [m3/s] | 6.08554 |
356 | Controller:WaterCoil | CAV_BAS_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 5.89537E-003 |
357 | Controller:WaterCoil | CAV_BAS_COOLC_CONTROLLER | Controller Convergence Tolerance | 8.07736E-005 |
358 | Controller:WaterCoil | CAV_BAS_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 2.46335E-003 |
359 | Controller:OutdoorAir | AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 21.42976 |
360 | Controller:OutdoorAir | AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.33839 |
361 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 21.42976 |
362 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Rated Total Cooling Capacity [W] | 436486.13566 |
363 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Rated Sensible Cooling Capacity [W] | 313639.02907 |
364 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Rated Water Flow Rate [m3/s] | 1.06895E-002 |
365 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 21.42976 |
366 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 21.42976 |
367 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 21.42976 |
368 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 21.42976 |
369 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Nominal Heating Capacity [W] | 436486.13566 |
370 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 436486.13566 |
371 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 12800.93607 |
372 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
373 | Fan:OnOff | AIRLOOP DATACENTER BASEMENT SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 21.42976 |
374 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 21.42976 |
375 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT HEATING COIL | Design Size Rated Heating Capacity [W] | 436486.13566 |
376 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT HEATING COIL | Design Size Rated Water Flow Rate [m3/s] | 1.06895E-002 |
377 | Coil:Heating:Electric | AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 12800.93607 |
378 | Humidifier:Steam:Electric | DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | Design Size Nominal Capacity Volume [m3/s] | 3.74064E-005 |
379 | Humidifier:Steam:Electric | DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | User-Specified Nominal Capacity Volume [m3/s] | 3.72000E-005 |
380 | Humidifier:Steam:Electric | DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | Design Size Rated Power [W] | 96450.69782 |
381 | Humidifier:Steam:Electric | DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | User-Specified Rated Power [W] | 100000.00000 |
382 | Controller:OutdoorAir | AIRLOOP DATACENTER BOT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.48009 |
383 | Controller:OutdoorAir | AIRLOOP DATACENTER BOT_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.56323E-002 |
384 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.48009 |
385 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT COOLING COIL | Design Size Rated Total Cooling Capacity [W] | 9798.88457 |
386 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT COOLING COIL | Design Size Rated Sensible Cooling Capacity [W] | 7029.31531 |
387 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT COOLING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.39974E-004 |
388 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 0.48009 |
389 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 0.48009 |
390 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 0.48009 |
391 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 0.48009 |
392 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Nominal Heating Capacity [W] | 9798.88457 |
393 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 9798.88457 |
394 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 591.35022 |
395 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
396 | Fan:OnOff | AIRLOOP DATACENTER BOT SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.48009 |
397 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.48009 |
398 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT HEATING COIL | Design Size Rated Heating Capacity [W] | 9798.88457 |
399 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT HEATING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.39974E-004 |
400 | Coil:Heating:Electric | AIRLOOP DATACENTER BOT_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 591.35022 |
401 | Controller:OutdoorAir | AIRLOOP DATACENTER MID_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 4.57834 |
402 | Controller:OutdoorAir | AIRLOOP DATACENTER MID_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.15632 |
403 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 4.57834 |
404 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID COOLING COIL | Design Size Rated Total Cooling Capacity [W] | 93691.14456 |
405 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID COOLING COIL | Design Size Rated Sensible Cooling Capacity [W] | 67117.65119 |
406 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID COOLING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.29449E-003 |
407 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 4.57834 |
408 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 4.57834 |
409 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 4.57834 |
410 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 4.57834 |
411 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Nominal Heating Capacity [W] | 93691.14456 |
412 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 93691.14456 |
413 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 5913.50215 |
414 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
415 | Fan:OnOff | AIRLOOP DATACENTER MID SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 4.57834 |
416 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 4.57834 |
417 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID HEATING COIL | Design Size Rated Heating Capacity [W] | 93691.14456 |
418 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID HEATING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.29449E-003 |
419 | Coil:Heating:Electric | AIRLOOP DATACENTER MID_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 5913.50215 |
420 | Controller:OutdoorAir | AIRLOOP DATACENTER TOP_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.46691 |
421 | Controller:OutdoorAir | AIRLOOP DATACENTER TOP_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.56323E-002 |
422 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.46691 |
423 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP COOLING COIL | Design Size Rated Total Cooling Capacity [W] | 9544.35265 |
424 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP COOLING COIL | Design Size Rated Sensible Cooling Capacity [W] | 6841.25799 |
425 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP COOLING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.33741E-004 |
426 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 0.46691 |
427 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 0.46691 |
428 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 0.46691 |
429 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 0.46691 |
430 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Nominal Heating Capacity [W] | 9544.35265 |
431 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 9544.35265 |
432 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 591.35022 |
433 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
434 | Fan:OnOff | AIRLOOP DATACENTER TOP SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.46691 |
435 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.46691 |
436 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP HEATING COIL | Design Size Rated Heating Capacity [W] | 9544.35265 |
437 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP HEATING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.33741E-004 |
438 | Coil:Heating:Electric | AIRLOOP DATACENTER TOP_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 591.35022 |
439 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Flow Rate [m3/s] | 0.14137 |
440 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Power Consumption [W] | 23080.99771 |
441 | PlantLoop | COOLSYS1_DEMAND | Maximum Loop Flow Rate [m3/s] | 0.14137 |
442 | PlantLoop | COOLSYS1_DEMAND | Plant Loop Volume [m3] | 16.96410 |
443 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Loop Supply Side Design Fluid Flow Rate [m3/s] | 0.14137 |
444 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Loop Demand Side Design Fluid Flow Rate [m3/s] | 0.14137 |
445 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Heat Exchanger U-Factor Times Area Value [W/C] | 593390.45145 |
446 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Loop-to-loop Temperature Difference Used to Size Heat Exchanger U-Factor Times Area Value [C] | 5.60000 |
447 | PlantLoop | HEATSYS1 | Maximum Loop Flow Rate [m3/s] | 1.31425E-002 |
448 | PlantLoop | HEATSYS1 | Plant Loop Volume [m3] | 1.57710 |
449 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Flow Rate [m3/s] | 1.31425E-002 |
450 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Power Consumption [W] | 3957.93848 |
451 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Minimum Flow Rate [m3/s] | 0.00000 |
452 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Nominal Capacity [W] | 1502266.44258 |
453 | Boiler:HotWater | HEATSYS1 BOILER | User-Specified Nominal Capacity [W] | 1502266.44000 |
454 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Design Water Flow Rate [m3/s] | 1.31425E-002 |
455 | PlantLoop | COOLSYS1_SUPPLY | Maximum Loop Flow Rate [m3/s] | 0.14137 |
456 | PlantLoop | COOLSYS1_SUPPLY | Plant Loop Volume [m3] | 16.96410 |
457 | Pump:ConstantSpeed | COOLSYS1 CHILLER1 PUMP | Design Flow Rate [m3/s] | 7.06838E-002 |
458 | Pump:ConstantSpeed | COOLSYS1 CHILLER1 PUMP | Design Power Consumption [W] | 7989.87655 |
459 | Pump:ConstantSpeed | COOLSYS1 CHILLER2 PUMP | Design Flow Rate [m3/s] | 7.06838E-002 |
460 | Pump:ConstantSpeed | COOLSYS1 CHILLER2 PUMP | Design Power Consumption [W] | 7989.87655 |
461 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | Design Size Reference Chilled Water Flow Rate [m3/s] | 0.14137 |
462 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | User-Specified Reference Chilled Water Flow Rate [m3/s] | 7.12900E-002 |
463 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | Design Size Reference Capacity [W] | 1679859.85726 |
464 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | User-Specified Reference Capacity [W] | 1687769.74500 |
465 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | Design Size Reference Condenser Water Flow Rate [m3/s] | 8.35215E-002 |
466 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | Design Size Reference Chilled Water Flow Rate [m3/s] | 0.14137 |
467 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | User-Specified Reference Chilled Water Flow Rate [m3/s] | 7.12900E-002 |
468 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | Design Size Reference Capacity [W] | 1679859.85726 |
469 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | User-Specified Reference Capacity [W] | 1687769.74500 |
470 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | Design Size Reference Condenser Water Flow Rate [m3/s] | 8.35215E-002 |
471 | PlantLoop | SINGLE WATER PLANT LOOP | Maximum Loop Flow Rate [m3/s] | 1.34577E-002 |
472 | PlantLoop | SINGLE WATER PLANT LOOP | Plant Loop Volume [m3] | 1.61493 |
473 | Pump:ConstantSpeed | PLANT CIRC PUMP | Design Flow Rate [m3/s] | 1.34577E-002 |
474 | Pump:ConstantSpeed | PLANT CIRC PUMP | Design Power Consumption [W] | 3432.39212 |
475 | FluidCooler:TwoSpeed | CENTRAL TOWER | Design Water Flow Rate [m3/s] | 1.34577E-002 |
476 | FluidCooler:TwoSpeed | CENTRAL TOWER | Air Flow Rate at High Fan Speed [m3/s] | 139666.46671 |
477 | FluidCooler:TwoSpeed | CENTRAL TOWER | Fluid cooler UA value at high fan speed based on nominal capacity input [W/K] | 58635.86744 |
478 | FluidCooler:TwoSpeed | CENTRAL TOWER | Air Flow Rate at Low Fan Speed [m3/s] | 69833.23335 |
479 | FluidCooler:TwoSpeed | CENTRAL TOWER | Fan Power at Low Fan Speed [W] | 7879.72339 |
480 | FluidCooler:TwoSpeed | CENTRAL TOWER | U-factor Times Area Value at Low Fan Speed [W/C] | 21351.26503 |
481 | Boiler:HotWater | CENTRAL BOILER | Design Size Nominal Capacity [W] | 554342.77698 |
482 | Boiler:HotWater | CENTRAL BOILER | User-Specified Nominal Capacity [W] | 543702.46000 |
483 | Boiler:HotWater | CENTRAL BOILER | Design Size Design Water Flow Rate [m3/s] | 1.34577E-002 |
484 | PlantLoop | SWHSYS1 | Maximum Loop Flow Rate [m3/s] | 4.40000E-004 |
485 | PlantLoop | SWHSYS1 | Plant Loop Volume [m3] | 5.28000E-002 |
486 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Flow Rate [m3/s] | 4.40000E-004 |
487 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Power Consumption [W] | 56.20530 |
488 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | Use Side Design Flow Rate [m3/s] | 4.40000E-004 |
489 | CondenserLoop | TOWERWATERSYS | Maximum Loop Flow Rate [m3/s] | 0.16704 |
490 | CondenserLoop | TOWERWATERSYS | Condenser Loop Volume [m3] | 20.04515 |
491 | HeaderedPumps:VariableSpeed | TOWERWATERSYS PUMP | Design Flow Rate [m3/s] | 0.16704 |
492 | HeaderedPumps:VariableSpeed | TOWERWATERSYS PUMP | Design Power Consumption [W] | 41356.13583 |
493 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Design Air Flow Rate [m3/s] | 64.28948 |
494 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Nominal Capacity [W] | 2002498.31833 |
495 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Air Flow Rate in free convection regime [m3/s] | 12.85790 |
496 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Tower capacity in free convection regime at design conditions [W] | 250312.28979 |
497 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Design Air Flow Rate [m3/s] | 64.28948 |
498 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Nominal Capacity [W] | 2002498.31833 |
499 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Air Flow Rate in free convection regime [m3/s] | 12.85790 |
500 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Tower capacity in free convection regime at design conditions [W] | 250312.28979 |
501 | PlantEquipmentOperation:ComponentSetPoint | WSHPPLANT OPERATION SCHEME | Design Water Flow Rate [m3/s] Equipment # 47 | 8.67525E-002 |
502 | PlantEquipmentOperation:ComponentSetPoint | WSHPPLANT OPERATION SCHEME | Design Water Flow Rate [m3/s] Equipment # 47 | 8.67525E-002 |
Component Type | Name | Nominal Total Capacity {W} | |
1 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | 18690.67 |
2 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | 382712.63 |
3 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | 59240.46 |
4 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | 6431.54 |
5 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | 5114.14 |
6 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | 7912.09 |
7 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | 4466.68 |
8 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | 153399.89 |
9 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | 101098.18 |
10 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | 151931.75 |
11 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | 92942.68 |
12 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | 18804.64 |
13 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | 12326.99 |
14 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | 18672.07 |
15 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | 11710.08 |
16 | Coil:Heating:Water | VAV_BOT WITH REHEAT HEATING COIL | 13918.06 |
17 | Coil:Heating:Water | VAV_MID WITH REHEAT HEATING COIL | 86346.21 |
18 | Coil:Heating:Water | VAV_TOP WITH REHEAT HEATING COIL | 6578.99 |
19 | Coil:Heating:Water | CAV_BAS HEATING COIL | 230153.76 |
Component Type | Name | Nominal Total Capacity {W} | Nominal Sensible Capacity {W} | Nominal Latent Capacity {W} | Nominal Sensible Heat Ratio | Nominal Coil UA Value {W/C} | Nominal Coil Surface Area {m2} | |
1 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | 275418.77 | 186343.79 | 89074.99 | 0.68 | 28670.70 | 290.79 |
2 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | 2625714.47 | 1767845.58 | 857868.89 | 0.67 | 274315.81 | 2782.26 |
3 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | 278474.70 | 188653.35 | 89821.35 | 0.68 | 28982.75 | 293.96 |
4 | Coil:Cooling:Water | CAV_BAS COOLING COIL | 153793.86 | 106298.39 | 47495.47 | 0.69 | 15674.26 | 158.98 |
Component Type | Component Name | IPLV in SI Units {W/W} | IPLV in IP Units {Btu/W-h} | |
1 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | 6.84 | 23.33 |
2 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | 6.84 | 23.33 |
Zone Name | # Surfaces | |
1 | BASEMENT | 10 |
2 | CORE_BOTTOM | 8 |
3 | CORE_MID | 7 |
4 | CORE_TOP | 7 |
5 | PERIMETER_BOT_ZN_3 | 18 |
6 | PERIMETER_BOT_ZN_2 | 12 |
7 | PERIMETER_BOT_ZN_1 | 18 |
8 | PERIMETER_BOT_ZN_4 | 12 |
9 | PERIMETER_MID_ZN_3 | 9 |
10 | PERIMETER_MID_ZN_2 | 8 |
11 | PERIMETER_MID_ZN_1 | 9 |
12 | PERIMETER_MID_ZN_4 | 8 |
13 | PERIMETER_TOP_ZN_3 | 9 |
14 | PERIMETER_TOP_ZN_2 | 8 |
15 | PERIMETER_TOP_ZN_1 | 9 |
16 | PERIMETER_TOP_ZN_4 | 8 |
17 | GROUNDFLOOR_PLENUM | 11 |
18 | MIDFLOOR_PLENUM | 11 |
19 | TOPFLOOR_PLENUM | 11 |
20 | DATACENTER_BOT_ZN_6 | 6 |
21 | DATACENTER_MID_ZN_6 | 6 |
22 | DATACENTER_TOP_ZN_6 | 6 |
23 | DATACENTER_BASEMENT_ZN_6 | 10 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | BASEMENT_WALL_EAST | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_EAST_CFACTOR | 0.940 | 0.824 | 118.87 | 118.87 | 118.87 | 90.00 | 90.00 | 48.74 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | BASEMENT_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_SOUTH_CFACTOR | 0.940 | 0.824 | 139.09 | 139.09 | 139.09 | 180.00 | 90.00 | 57.03 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
3 | BASEMENT_WALL_NORTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_NORTH_CFACTOR | 0.940 | 0.824 | 139.09 | 139.09 | 139.09 | 0.00 | 90.00 | 57.03 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | BASEMENT_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.87 | 118.87 | 118.87 | 270.00 | 90.00 | 48.74 | 2.44 | 0.00 | DATACENTER_BASEMENT_ZN_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
5 | BASEMENT_FLOOR | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 2779.43 | 2779.43 | 2779.43 | 0.00 | 180.00 | 57.03 | 48.74 | 0.00 | BASEMENT_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
6 | PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | PERIMETER_BOT_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
7 | PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 250.34 | 250.34 | 250.34 | 180.00 | 0.00 | 57.03 | 4.57 | 0.00 | PERIMETER_BOT_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
8 | CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 2076.77 | 2076.77 | 2076.77 | 180.00 | 0.00 | 52.45 | 39.59 | 0.00 | CORE_BOT_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
9 | PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 250.34 | 250.34 | 250.34 | 180.00 | 0.00 | 52.45 | 4.57 | 0.00 | PERIMETER_BOT_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
10 | BASEMENT_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 7126.21 | 7126.21 | 7126.21 | 0.00 | 90.00 | 7126.21 | 1.00 | 0.00 | BASEMENT_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
11 | CORE_BOT_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
12 | CORE_BOT_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
13 | CORE_BOT_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
14 | CORE_BOT_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
15 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 419.30 | 419.30 | 419.30 | 0.00 | 180.00 | 10.59 | 39.59 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
16 | CORE_BOT_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 2076.82 | 2076.82 | 2076.82 | 0.00 | 180.00 | 52.46 | 39.59 | 0.00 | CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
17 | CORE_BOT_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 2496.12 | 2496.12 | 2496.12 | 180.00 | 0.00 | 63.05 | 39.59 | 0.00 | iz-CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
18 | CORE_BOTTOM_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 5064.65 | 5064.65 | 5064.65 | 0.00 | 90.00 | 5064.65 | 1.00 | 0.00 | CORE_BOTTOM_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
19 | CORE_MID_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
20 | CORE_MID_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
21 | CORE_MID_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
22 | CORE_MID_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
23 | CORE_MID_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_MID_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
24 | CORE_MID_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 2496.12 | 2496.12 | 2496.12 | 180.00 | 0.00 | 63.05 | 39.59 | 0.00 | iz-CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
25 | CORE_MID_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 5064.65 | 5064.65 | 5064.65 | 0.00 | 90.00 | 5064.65 | 1.00 | 0.00 | CORE_MID_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
26 | CORE_TOP_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
27 | CORE_TOP_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
28 | CORE_TOP_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
29 | CORE_TOP_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
30 | CORE_TOP_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_TOP_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
31 | CORE_TOP_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 2496.12 | 2496.12 | 2496.12 | 180.00 | 0.00 | 63.05 | 39.59 | 0.00 | iz-CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
32 | CORE_TOP_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 5064.65 | 5064.65 | 5064.65 | 0.00 | 90.00 | 5064.65 | 1.00 | 0.00 | CORE_TOP_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
33 | PERIMETER_BOT_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 5.069 | 2.882 | 76.91 | 200.61 | 76.91 | 0.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
34 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_NORTH_0.25 | N/A | 3.241 | No | 23.18 | 23.18 | 23.18 | 0.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
35 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_NORTH_0.25 | N/A | 3.241 | No | 23.18 | 23.18 | 23.18 | 0.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
36 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_NORTH_0.25 | N/A | 3.241 | No | 23.18 | 23.18 | 23.18 | 0.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
37 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_NORTH_0.25 | N/A | 3.241 | No | 23.18 | 23.18 | 23.18 | 0.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
38 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_NORTH_0.25 | N/A | 3.241 | No | 23.18 | 23.18 | 23.18 | 0.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
39 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.975 | 3.975 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
40 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.975 | 3.975 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
41 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.975 | 3.975 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
42 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.975 | 3.975 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
43 | PERIMETER_BOT_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
44 | CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
45 | PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
46 | DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
47 | PERIMETER_BOT_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 250.34 | 250.34 | 250.34 | 0.00 | 180.00 | 52.46 | 6.47 | 0.00 | PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
48 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 63.07 | 63.07 | 63.07 | 0.00 | 180.00 | 11.51 | 4.57 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
49 | PERIMETER_BOT_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.41 | 313.41 | 313.41 | 180.00 | 0.00 | 63.96 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
50 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.83 | 626.83 | 626.83 | 0.00 | 90.00 | 626.83 | 1.00 | 0.00 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
51 | PERIMETER_BOT_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 5.069 | 2.882 | 52.57 | 133.74 | 52.57 | 90.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
52 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_EAST_0.25 | N/A | 3.241 | No | 25.75 | 25.75 | 25.75 | 90.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
53 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_EAST_0.25 | N/A | 3.241 | No | 25.75 | 25.75 | 25.75 | 90.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
54 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_EAST_0.25 | N/A | 3.241 | No | 25.75 | 25.75 | 25.75 | 90.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
55 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | Door | PERIMETER_BOT_ZN_2_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.975 | 3.975 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
56 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | Door | PERIMETER_BOT_ZN_2_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.975 | 3.975 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
57 | PERIMETER_BOT_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
58 | CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
59 | PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
60 | PERIMETER_BOT_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
61 | PERIMETER_BOT_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | iz-PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
62 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
63 | PERIMETER_BOT_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 5.069 | 2.882 | 76.91 | 200.61 | 76.91 | 180.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
64 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_SOUTH_0.25 | N/A | 3.241 | No | 23.18 | 23.18 | 23.18 | 180.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
65 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_SOUTH_0.25 | N/A | 3.241 | No | 23.18 | 23.18 | 23.18 | 180.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
66 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_SOUTH_0.25 | N/A | 3.241 | No | 23.18 | 23.18 | 23.18 | 180.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
67 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_SOUTH_0.25 | N/A | 3.241 | No | 23.18 | 23.18 | 23.18 | 180.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
68 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_SOUTH_0.25 | N/A | 3.241 | No | 23.18 | 23.18 | 23.18 | 180.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
69 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.975 | 3.975 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
70 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.975 | 3.975 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
71 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.975 | 3.975 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
72 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.975 | 3.975 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
73 | PERIMETER_BOT_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
74 | DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
75 | PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
76 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
77 | DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 63.07 | 63.07 | 63.07 | 0.00 | 180.00 | 16.08 | 4.57 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
78 | PERIMETER_BOT_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 250.35 | 250.35 | 250.35 | 0.00 | 180.00 | 57.03 | 6.47 | 0.00 | PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
79 | PERIMETER_BOT_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.42 | 313.42 | 313.42 | 180.00 | 0.00 | 73.11 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
80 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.84 | 626.84 | 626.84 | 0.00 | 90.00 | 626.84 | 1.00 | 0.00 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
81 | PERIMETER_BOT_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 5.069 | 2.882 | 52.57 | 133.74 | 52.57 | 270.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
82 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_WEST_0.25 | N/A | 3.241 | No | 25.75 | 25.75 | 25.75 | 270.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
83 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_WEST_0.25 | N/A | 3.241 | No | 25.75 | 25.75 | 25.75 | 270.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
84 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_WEST_0.25 | N/A | 3.241 | No | 25.75 | 25.75 | 25.75 | 270.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
85 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | Door | PERIMETER_BOT_ZN_4_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.975 | 3.975 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
86 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | Door | PERIMETER_BOT_ZN_4_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.975 | 3.975 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
87 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
88 | DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
89 | PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
90 | PERIMETER_BOT_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
91 | PERIMETER_BOT_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | iz-PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
92 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
93 | PERIMETER_MID_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 5.069 | 2.882 | 84.71 | 200.61 | 84.71 | 0.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
94 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_MID_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_NORTH_0.25 | N/A | 3.241 | No | 115.90 | 115.90 | 115.90 | 0.00 | 90.00 | 73.11 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
95 | PERIMETER_MID_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
96 | CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
97 | PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
98 | DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
99 | PERIMETER_MID_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
100 | PERIMETER_MID_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.41 | 313.41 | 313.41 | 180.00 | 0.00 | 63.96 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
101 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.83 | 626.83 | 626.83 | 0.00 | 90.00 | 626.83 | 1.00 | 0.00 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
102 | PERIMETER_MID_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 5.069 | 2.882 | 56.47 | 133.74 | 56.47 | 90.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
103 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_MID_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_EAST_0.25 | N/A | 3.241 | No | 77.26 | 77.26 | 77.26 | 90.00 | 90.00 | 48.74 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
104 | PERIMETER_MID_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
105 | CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
106 | PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
107 | PERIMETER_MID_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_MID_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
108 | PERIMETER_MID_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | iz-PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
109 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
110 | PERIMETER_MID_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
111 | PERIMETER_MID_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 5.069 | 2.882 | 84.71 | 200.61 | 84.71 | 180.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
112 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_MID_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_SOUTH_0.25 | N/A | 3.241 | No | 115.90 | 115.90 | 115.90 | 180.00 | 90.00 | 73.11 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
113 | DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
114 | PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
115 | CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
116 | PERIMETER_MID_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
117 | PERIMETER_MID_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.42 | 313.42 | 313.42 | 180.00 | 0.00 | 73.11 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
118 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.84 | 626.84 | 626.84 | 0.00 | 90.00 | 626.84 | 1.00 | 0.00 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
119 | PERIMETER_MID_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 5.069 | 2.882 | 56.47 | 133.74 | 56.47 | 270.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
120 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_MID_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_WEST_0.25 | N/A | 3.241 | No | 77.26 | 77.26 | 77.26 | 270.00 | 90.00 | 48.74 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
121 | PERIMETER_MID_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
122 | DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
123 | PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
124 | PERIMETER_MID_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_MID_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
125 | PERIMETER_MID_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | iz-PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
126 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
127 | PERIMETER_TOP_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 5.069 | 2.882 | 84.71 | 200.61 | 84.71 | 0.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
128 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_TOP_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_NORTH_0.25 | N/A | 3.241 | No | 115.90 | 115.90 | 115.90 | 0.00 | 90.00 | 73.11 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
129 | PERIMETER_TOP_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
130 | CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
131 | PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
132 | DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
133 | PERIMETER_TOP_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_TOP_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
134 | PERIMETER_TOP_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.41 | 313.41 | 313.41 | 180.00 | 0.00 | 63.96 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
135 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.83 | 626.83 | 626.83 | 0.00 | 90.00 | 626.83 | 1.00 | 0.00 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
136 | PERIMETER_TOP_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 5.069 | 2.882 | 56.47 | 133.74 | 56.47 | 90.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
137 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_TOP_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_EAST_0.25 | N/A | 3.241 | No | 77.26 | 77.26 | 77.26 | 90.00 | 90.00 | 48.74 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
138 | PERIMETER_TOP_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
139 | CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
140 | INT-PER3S-NE-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | INT-PER3S-NE | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
141 | PERIMETER_TOP_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_TOP_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
142 | PERIMETER_TOP_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | iz-PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
143 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
144 | PERIMETER_TOP_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 5.069 | 2.882 | 84.71 | 200.61 | 84.71 | 180.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
145 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_TOP_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_SOUTH_0.25 | N/A | 3.241 | No | 115.90 | 115.90 | 115.90 | 180.00 | 90.00 | 73.11 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
146 | INT-PER3S-NE | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | INT-PER3S-NE-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
147 | DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
148 | PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
149 | CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
150 | PERIMETER_TOP_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_TOP_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
151 | PERIMETER_TOP_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.42 | 313.42 | 313.42 | 180.00 | 0.00 | 73.11 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
152 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.84 | 626.84 | 626.84 | 0.00 | 90.00 | 626.84 | 1.00 | 0.00 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
153 | PERIMETER_TOP_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 5.069 | 2.882 | 56.47 | 133.74 | 56.47 | 270.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
154 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_TOP_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_WEST_0.25 | N/A | 3.241 | No | 77.26 | 77.26 | 77.26 | 270.00 | 90.00 | 48.74 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
155 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
156 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
157 | PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
158 | PERIMETER_TOP_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_TOP_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
159 | PERIMETER_TOP_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | iz-PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
160 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
161 | GROUNDFLOOR_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 5.069 | 2.882 | 89.13 | 89.13 | 89.13 | 0.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
162 | GROUNDFLOOR_PLENUM_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 5.069 | 2.882 | 59.42 | 59.42 | 59.42 | 270.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
163 | GROUNDFLOOR_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 5.069 | 2.882 | 89.13 | 89.13 | 89.13 | 180.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
164 | GROUNDFLOOR_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 5.069 | 2.882 | 59.42 | 59.42 | 59.42 | 90.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
165 | iz-CORE_BOT_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
166 | iz-PERIMETER_BOT_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
167 | iz-PERIMETER_BOT_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
168 | iz-PERIMETER_BOT_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
169 | iz-PERIMETER_BOT_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
170 | iz-DATACENTER_BOT_ZN_6_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_BOT_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
171 | GROUNDFLOOR_PLENUM_CEILING | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 3563.11 | 3563.11 | 3563.11 | 180.00 | 0.00 | 73.11 | 48.74 | 0.00 | GROUNDFLOOR_PLENUM_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
172 | MIDFLOOR_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 5.069 | 2.882 | 89.13 | 89.13 | 89.13 | 0.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
173 | MIDFLOOR_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 5.069 | 2.882 | 59.42 | 59.42 | 59.42 | 270.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
174 | MIDFLOOR_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 5.069 | 2.882 | 89.13 | 89.13 | 89.13 | 180.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
175 | MIDFLOOR_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 5.069 | 2.882 | 59.42 | 59.42 | 59.42 | 90.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
176 | iz-CORE_MID_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
177 | iz-PERIMETER_MID_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
178 | iz-PERIMETER_MID_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
179 | iz-PERIMETER_MID_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
180 | iz-PERIMETER_MID_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
181 | iz-DATACENTER_MID_ZN_6_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_MID_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
182 | MIDFLOOR_PLENUM_CEILING | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 3563.11 | 3563.11 | 3563.11 | 180.00 | 0.00 | 73.11 | 48.74 | 0.00 | MIDFLOOR_PLENUM_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
183 | TOPFLOOR_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 5.069 | 2.882 | 89.13 | 89.13 | 89.13 | 180.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
184 | TOPFLOOR_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 5.069 | 2.882 | 59.42 | 59.42 | 59.42 | 90.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
185 | TOPFLOOR_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 5.069 | 2.882 | 59.42 | 59.42 | 59.42 | 270.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
186 | TOPFLOOR_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 5.069 | 2.882 | 89.13 | 89.13 | 89.13 | 0.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
187 | iz-CORE_TOP_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
188 | iz-PERIMETER_TOP_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
189 | iz-PERIMETER_TOP_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
190 | iz-PERIMETER_TOP_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
191 | iz-PERIMETER_TOP_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
192 | iz-DATACENTER_TOP_ZN_6_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_TOP_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
193 | BUILDING_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 3563.11 | 3563.11 | 3563.11 | 180.00 | 0.00 | 73.11 | 48.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
194 | DATACENTER_BOT_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
195 | DATACENTER_BOT_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
196 | DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
197 | DATACENTER_BOT_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
198 | DATACENTER_BOT_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
199 | DATACENTER_BOT_ZN_6_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | iz-DATACENTER_BOT_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
200 | DATACENTER_MID_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
201 | DATACENTER_MID_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
202 | DATACENTER_MID_ZN_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
203 | DATACENTER_MID_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
204 | DATACENTER_MID_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_MID_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
205 | DATACENTER_MID_ZN_6_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | iz-DATACENTER_MID_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
206 | DATACENTER_TOP_ZN_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
207 | DATACENTER_TOP_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
208 | DATACENTER_TOP_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
209 | DATACENTER_TOP_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
210 | DATACENTER_TOP_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_TOP_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
211 | DATACENTER_TOP_ZN_6_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | iz-DATACENTER_TOP_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
212 | DATACENTER_BASEMENT_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR | 0.940 | 0.824 | 39.22 | 39.22 | 39.22 | 0.00 | 90.00 | 16.08 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
213 | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR | 0.940 | 0.824 | 39.22 | 39.22 | 39.22 | 180.00 | 90.00 | 16.08 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
214 | DATACENTER_BASEMENT_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR | 0.940 | 0.824 | 118.87 | 118.87 | 118.87 | 270.00 | 90.00 | 48.74 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
215 | DATACENTER_BASEMENT_ZN_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.87 | 118.87 | 118.87 | 90.00 | 90.00 | 48.74 | 2.44 | 0.00 | BASEMENT_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
216 | DATACENTER_BASEMENT_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 783.68 | 783.68 | 783.68 | 0.00 | 180.00 | 16.08 | 48.74 | 0.00 | DATACENTER_BASEMENT_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
217 | DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | DATACENTER_BOT_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
218 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 419.35 | 419.35 | 419.35 | 180.00 | 0.00 | 10.59 | 39.59 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
219 | PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | PERIMETER_BOT_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
220 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 63.08 | 63.08 | 63.08 | 180.00 | 0.00 | 16.08 | 6.47 | 0.00 | DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
221 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 63.07 | 63.07 | 63.07 | 180.00 | 0.00 | 11.51 | 6.47 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | BASEMENT | RunPeriod: RUNPERIOD 1 | 0.1965764643 | 0.1879990623 | Pass | Pass | 10.9405376805 | 52.5359962997 | Fail | Fail |
2 | CORE_BOTTOM | RunPeriod: RUNPERIOD 1 | 0.2469942880 | 0.2458563307 | Pass | Pass | 0.2658762625 | 0.4401645654 | Pass | Fail |
3 | CORE_MID | RunPeriod: RUNPERIOD 1 | 0.1722776462 | 0.2182970775 | Pass | Pass | 0.2252021402 | 0.4167739800 | Pass | Pass |
4 | CORE_TOP | RunPeriod: RUNPERIOD 1 | 0.1596079530 | 0.2259485400 | Pass | Pass | 0.2167287868 | 0.4099113390 | Pass | Pass |
5 | PERIMETER_BOT_ZN_3 | RunPeriod: RUNPERIOD 1 | 0.2233104807 | 0.2353060664 | Pass | Pass | 0.2651338767 | 0.4388148866 | Pass | Pass |
6 | PERIMETER_BOT_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.3724366265 | 0.4415284065 | Pass | Pass | 0.2744819168 | 0.4425758042 | Pass | Fail |
7 | PERIMETER_BOT_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.3760137065 | 0.4949899709 | Pass | Pass | 0.3097110435 | 0.4973453577 | Pass | Fail |
8 | PERIMETER_BOT_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.3859746766 | 0.4282168533 | Pass | Pass | 0.2694189702 | 0.4379826964 | Pass | Pass |
9 | PERIMETER_MID_ZN_3 | RunPeriod: RUNPERIOD 1 | 0.1648464180 | 0.2110506725 | Pass | Pass | 0.2235777907 | 0.4154179223 | Pass | Pass |
10 | PERIMETER_MID_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.2920433124 | 0.3825261230 | Pass | Pass | 0.2252738429 | 0.4152628372 | Pass | Fail |
11 | PERIMETER_MID_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.3137077728 | 0.4790865164 | Pass | Pass | 0.2536081777 | 0.4603684026 | Pass | Pass |
12 | PERIMETER_MID_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.2635868884 | 0.3382901701 | Pass | Pass | 0.2253688571 | 0.4146073336 | Pass | Pass |
13 | PERIMETER_TOP_ZN_3 | RunPeriod: RUNPERIOD 1 | 0.1615534918 | 0.2276556005 | Pass | Pass | 0.2165434762 | 0.4086072433 | Pass | Pass |
14 | PERIMETER_TOP_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.2735978881 | 0.3539023030 | Pass | Pass | 0.2173003321 | 0.4104958273 | Pass | Fail |
15 | PERIMETER_TOP_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.3044039165 | 0.4898290420 | Pass | Pass | 0.2495221317 | 0.4575982198 | Pass | Pass |
16 | PERIMETER_TOP_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.2613458970 | 0.3816448902 | Pass | Pass | 0.2179328133 | 0.4072918359 | Pass | Pass |
17 | GROUNDFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 6.2378540724E-002 | 5.5118770353E-002 | Pass | Pass | 0.2904300150 | 0.4627411463 | Pass | Pass |
18 | MIDFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 5.4696368414E-002 | 5.9095607448E-002 | Pass | Pass | 0.2260637544 | 0.4023077069 | Fail | Pass |
19 | TOPFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 7.1593282759E-002 | 7.8559132124E-002 | Pass | Pass | 0.2256093402 | 0.4211591800 | Fail | Pass |
20 | DATACENTER_BOT_ZN_6 | RunPeriod: RUNPERIOD 1 | 1.6300245107E-004 | 2.8117942959E-004 | Pass | Pass | 2.7117362290E-003 | 2.3188789622E-003 | Pass | Pass |
21 | DATACENTER_MID_ZN_6 | RunPeriod: RUNPERIOD 1 | 3.1384759662E-006 | 5.7460570759E-006 | Pass | Pass | 3.9563352492E-003 | 4.0329396402E-003 | Pass | Pass |
22 | DATACENTER_TOP_ZN_6 | RunPeriod: RUNPERIOD 1 | 2.6172133256E-006 | 4.6936045318E-006 | Pass | Pass | 6.3218100801E-003 | 4.7252104119E-003 | Pass | Pass |
23 | DATACENTER_BASEMENT_ZN_6 | RunPeriod: RUNPERIOD 1 | 2.4842893551E-004 | 2.3608527456E-004 | Pass | Pass | 4.7334144199E-005 | 1.1087362835E-004 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 08:43:45
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 5330.37 | -141.1 | 0.00 | -14566.7 | 45404.16 | 36026.74 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 08:43:45
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 8.70 | 0.00 | 8.70 | Wetbulb [C] | 3.80 | 340.00 |
MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 33.20 | 6.70 | 25.30 | Wetbulb [C] | 4.50 | 140.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 65.00 | 29 | |||
Feb | 0.00 | 0 | |||
Mar | 0.00 | 0 | |||
Apr | 38.00 | 14 | |||
May | 0.00 | 0 | |||
Jun | 0.00 | 0 | |||
Jul | 0.00 | 0 | |||
Aug | 391.00 | 83 | |||
Sep | 0.00 | 0 | |||
Oct | 225.00 | 40 | |||
Nov | 0.00 | 0 | |||
Dec | 5.00 | 10 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 08:43:45
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BASEMENT_WALL_EAST | BASEMENT_WALL_EAST_CFACTOR | 1.00 | 0.845 | 0.940 | 118.87 | 118.87 | 90.00 | 90.00 | E |
BASEMENT_WALL_SOUTH | BASEMENT_WALL_SOUTH_CFACTOR | 1.00 | 0.845 | 0.940 | 139.09 | 139.09 | 180.00 | 90.00 | S |
BASEMENT_WALL_NORTH | BASEMENT_WALL_NORTH_CFACTOR | 1.00 | 0.845 | 0.940 | 139.09 | 139.09 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_3_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 2.882 | 5.069 | 200.61 | 76.91 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_2_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 2.882 | 5.069 | 133.74 | 52.57 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 2.882 | 5.069 | 200.61 | 76.91 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_4_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 2.882 | 5.069 | 133.74 | 52.57 | 270.00 | 90.00 | W |
PERIMETER_MID_ZN_3_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 2.882 | 5.069 | 2006.06 | 847.11 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_2_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 2.882 | 5.069 | 1337.37 | 564.74 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 2.882 | 5.069 | 2006.06 | 847.11 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_4_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 2.882 | 5.069 | 1337.37 | 564.74 | 270.00 | 90.00 | W |
PERIMETER_TOP_ZN_3_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 2.882 | 5.069 | 200.61 | 84.71 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_2_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 2.882 | 5.069 | 133.74 | 56.47 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 2.882 | 5.069 | 200.61 | 84.71 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_4_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 2.882 | 5.069 | 133.74 | 56.47 | 270.00 | 90.00 | W |
GROUNDFLOOR_PLENUM_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 2.882 | 5.069 | 89.13 | 89.13 | 0.00 | 90.00 | N |
GROUNDFLOOR_PLENUM_WEST | NONRES_EXT_WALL_GRD | 0.30 | 2.882 | 5.069 | 59.42 | 59.42 | 270.00 | 90.00 | W |
GROUNDFLOOR_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 2.882 | 5.069 | 89.13 | 89.13 | 180.00 | 90.00 | S |
GROUNDFLOOR_PLENUM_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 2.882 | 5.069 | 59.42 | 59.42 | 90.00 | 90.00 | E |
MIDFLOOR_PLENUM_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 2.882 | 5.069 | 891.32 | 891.32 | 0.00 | 90.00 | N |
MIDFLOOR_PLENUM_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 2.882 | 5.069 | 594.21 | 594.21 | 270.00 | 90.00 | W |
MIDFLOOR_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 2.882 | 5.069 | 891.32 | 891.32 | 180.00 | 90.00 | S |
MIDFLOOR_PLENUM_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 2.882 | 5.069 | 594.21 | 594.21 | 90.00 | 90.00 | E |
TOPFLOOR_PLENUM_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 2.882 | 5.069 | 89.13 | 89.13 | 180.00 | 90.00 | S |
TOPFLOOR_PLENUM_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 2.882 | 5.069 | 59.42 | 59.42 | 90.00 | 90.00 | E |
TOPFLOOR_PLENUM_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 2.882 | 5.069 | 59.42 | 59.42 | 270.00 | 90.00 | W |
TOPFLOOR_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 2.882 | 5.069 | 89.13 | 89.13 | 0.00 | 90.00 | N |
BUILDING_ROOF | NONRES_ROOF | 0.55 | 0.273 | 0.283 | 3563.11 | 3563.11 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_WALL_NORTH | DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR | 1.00 | 0.845 | 0.940 | 39.22 | 39.22 | 0.00 | 90.00 | N |
DATACENTER_BASEMENT_ZN_6_WALL_SOUTH | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR | 1.00 | 0.845 | 0.940 | 39.22 | 39.22 | 180.00 | 90.00 | S |
DATACENTER_BASEMENT_ZN_6_WALL_WEST | DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR | 1.00 | 0.845 | 0.940 | 118.87 | 118.87 | 270.00 | 90.00 | W |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BASEMENT_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 118.87 | 118.87 | 270.00 | 90.00 | W |
BASEMENT_FLOOR | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 2779.43 | 2779.43 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 225.00 | 0.00 | |
PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 250.34 | 250.34 | 180.00 | 0.00 | |
CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 2076.77 | 2076.77 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 250.34 | 250.34 | 180.00 | 0.00 | |
CORE_BOT_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
CORE_BOT_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
CORE_BOT_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 419.30 | 419.30 | 0.00 | 180.00 | |
CORE_BOT_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 2076.82 | 2076.82 | 0.00 | 180.00 | |
CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 180.00 | 0.00 | |
CORE_MID_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 180.00 | 90.00 | S |
CORE_MID_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 270.00 | 90.00 | W |
CORE_MID_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 0.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 90.00 | 90.00 | E |
CORE_MID_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 24961.20 | 24961.20 | 0.00 | 180.00 | |
CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 24961.20 | 24961.20 | 180.00 | 0.00 | |
CORE_TOP_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
CORE_TOP_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
CORE_TOP_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
CORE_TOP_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 2496.12 | 2496.12 | 0.00 | 180.00 | |
CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 250.34 | 250.34 | 0.00 | 180.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 63.07 | 63.07 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
PERIMETER_BOT_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 45.00 | 180.00 | |
PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 225.00 | 0.00 | |
PERIMETER_BOT_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 63.07 | 63.07 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 250.35 | 250.35 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
PERIMETER_BOT_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 315.00 | 180.00 | |
PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 135.00 | 0.00 | |
PERIMETER_MID_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 225.00 | 90.00 | W |
CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 135.00 | 90.00 | S |
DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 3134.13 | 3134.13 | 0.00 | 180.00 | |
PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.13 | 3134.13 | 180.00 | 0.00 | |
PERIMETER_MID_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 315.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 270.00 | 90.00 | W |
PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 225.00 | 90.00 | W |
PERIMETER_MID_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 2019.75 | 2019.75 | 45.00 | 180.00 | |
PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 225.00 | 0.00 | |
PERIMETER_MID_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 45.00 | 90.00 | E |
DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 315.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 3134.20 | 3134.20 | 0.00 | 180.00 | |
PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.20 | 3134.20 | 180.00 | 0.00 | |
PERIMETER_MID_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 135.00 | 90.00 | S |
DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 45.00 | 90.00 | E |
PERIMETER_MID_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 2019.75 | 2019.75 | 315.00 | 180.00 | |
PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 135.00 | 0.00 | |
PERIMETER_TOP_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 313.41 | 313.41 | 0.00 | 180.00 | |
PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 180.00 | 0.00 | |
PERIMETER_TOP_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
INT-PER3S-NE-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
PERIMETER_TOP_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 201.98 | 201.98 | 45.00 | 180.00 | |
PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 225.00 | 0.00 | |
INT-PER3S-NE | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 313.42 | 313.42 | 0.00 | 180.00 | |
PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 180.00 | 0.00 | |
PERIMETER_TOP_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
PERIMETER_TOP_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 201.98 | 201.98 | 315.00 | 180.00 | |
PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 135.00 | 0.00 | |
iz-CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 45.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 315.00 | 180.00 | |
iz-DATACENTER_BOT_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 0.00 | 180.00 | |
GROUNDFLOOR_PLENUM_CEILING | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 3563.11 | 3563.11 | 180.00 | 0.00 | |
iz-CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 24961.20 | 24961.20 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.13 | 3134.13 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 45.00 | 180.00 | |
iz-PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.20 | 3134.20 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 315.00 | 180.00 | |
iz-DATACENTER_MID_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 362.03 | 362.03 | 0.00 | 180.00 | |
MIDFLOOR_PLENUM_CEILING | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 35631.06 | 35631.06 | 180.00 | 0.00 | |
iz-CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 45.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 315.00 | 180.00 | |
iz-DATACENTER_TOP_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 0.00 | 180.00 | |
DATACENTER_BOT_ZN_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
DATACENTER_BOT_ZN_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
DATACENTER_BOT_ZN_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
DATACENTER_BOT_ZN_6_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 36.20 | 36.20 | 0.00 | 180.00 | |
DATACENTER_BOT_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 180.00 | 0.00 | |
DATACENTER_MID_ZN_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 270.00 | 90.00 | W |
DATACENTER_MID_ZN_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 180.00 | 90.00 | S |
DATACENTER_MID_ZN_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 90.00 | 90.00 | E |
DATACENTER_MID_ZN_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 0.00 | 90.00 | N |
DATACENTER_MID_ZN_6_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 362.03 | 362.03 | 0.00 | 180.00 | |
DATACENTER_MID_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 362.03 | 362.03 | 180.00 | 0.00 | |
DATACENTER_TOP_ZN_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
DATACENTER_TOP_ZN_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
DATACENTER_TOP_ZN_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
DATACENTER_TOP_ZN_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
DATACENTER_TOP_ZN_6_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 36.20 | 36.20 | 0.00 | 180.00 | |
DATACENTER_TOP_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 118.87 | 118.87 | 90.00 | 90.00 | E |
DATACENTER_BASEMENT_ZN_6_FLOOR | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 783.68 | 783.68 | 0.00 | 180.00 | |
DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 36.20 | 36.20 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 419.35 | 419.35 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 135.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 63.08 | 63.08 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 63.07 | 63.07 | 180.00 | 0.00 | |
BASEMENT_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 7126.21 | 0.00 | 90.00 | N | ||
CORE_BOTTOM_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 5064.65 | 0.00 | 90.00 | N | ||
CORE_MID_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 50646.53 | 0.00 | 90.00 | N | ||
CORE_TOP_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 5064.65 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.83 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.84 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 6268.26 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 4039.50 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 6268.35 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 4039.48 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.83 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.84 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | WINDOW_U_0.57_SHGC_NORTH_0.25 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 3.241 | 0.251 | 0.276 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | WINDOW_U_0.57_SHGC_NORTH_0.25 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 3.241 | 0.251 | 0.276 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | WINDOW_U_0.57_SHGC_NORTH_0.25 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 3.241 | 0.251 | 0.276 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | WINDOW_U_0.57_SHGC_NORTH_0.25 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 3.241 | 0.251 | 0.276 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | WINDOW_U_0.57_SHGC_NORTH_0.25 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 3.241 | 0.251 | 0.276 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | WINDOW_U_0.57_SHGC_EAST_0.25 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 3.241 | 0.251 | 0.276 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | WINDOW_U_0.57_SHGC_EAST_0.25 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 3.241 | 0.251 | 0.276 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | WINDOW_U_0.57_SHGC_EAST_0.25 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 3.241 | 0.251 | 0.276 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | WINDOW_U_0.57_SHGC_SOUTH_0.25 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 3.241 | 0.251 | 0.276 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | WINDOW_U_0.57_SHGC_SOUTH_0.25 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 3.241 | 0.251 | 0.276 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | WINDOW_U_0.57_SHGC_SOUTH_0.25 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 3.241 | 0.251 | 0.276 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | WINDOW_U_0.57_SHGC_SOUTH_0.25 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 3.241 | 0.251 | 0.276 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | WINDOW_U_0.57_SHGC_SOUTH_0.25 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 3.241 | 0.251 | 0.276 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | WINDOW_U_0.57_SHGC_WEST_0.25 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 3.241 | 0.251 | 0.276 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | WINDOW_U_0.57_SHGC_WEST_0.25 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 3.241 | 0.251 | 0.276 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | WINDOW_U_0.57_SHGC_WEST_0.25 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 3.241 | 0.251 | 0.276 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.57_SHGC_NORTH_0.25 | 115.90 | 0.00 | 0.00 | 115.90 | 1158.95 | 3.241 | 0.251 | 0.276 | No | PERIMETER_MID_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.57_SHGC_EAST_0.25 | 77.26 | 0.00 | 0.00 | 77.26 | 772.63 | 3.241 | 0.251 | 0.276 | No | PERIMETER_MID_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.57_SHGC_SOUTH_0.25 | 115.90 | 0.00 | 0.00 | 115.90 | 1158.95 | 3.241 | 0.251 | 0.276 | No | PERIMETER_MID_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.57_SHGC_WEST_0.25 | 77.26 | 0.00 | 0.00 | 77.26 | 772.63 | 3.241 | 0.251 | 0.276 | No | PERIMETER_MID_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.57_SHGC_NORTH_0.25 | 115.90 | 0.00 | 0.00 | 115.90 | 115.90 | 3.241 | 0.251 | 0.276 | No | PERIMETER_TOP_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.57_SHGC_EAST_0.25 | 77.26 | 0.00 | 0.00 | 77.26 | 77.26 | 3.241 | 0.251 | 0.276 | No | PERIMETER_TOP_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.57_SHGC_SOUTH_0.25 | 115.90 | 0.00 | 0.00 | 115.90 | 115.90 | 3.241 | 0.251 | 0.276 | No | PERIMETER_TOP_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.57_SHGC_WEST_0.25 | 77.26 | 0.00 | 0.00 | 77.26 | 77.26 | 3.241 | 0.251 | 0.276 | No | PERIMETER_TOP_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
Total or Average | 4635.80 | 3.241 | 0.251 | 0.276 | |||||||||||||||||
North Total or Average | 1390.74 | 3.241 | 0.251 | 0.276 | |||||||||||||||||
Non-North Total or Average | 3245.06 | 3.241 | 0.251 | 0.276 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | PERIMETER_BOT_ZN_2_WALL_EAST |
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | PERIMETER_BOT_ZN_2_WALL_EAST |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | PERIMETER_BOT_ZN_4_WALL_WEST |
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | PERIMETER_BOT_ZN_4_WALL_WEST |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 08:43:45
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 08:43:45
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
BASEMENT_LIGHTS | BASEMENT | BASEMENT | GENERAL | 10.2732 | 2779.43 | 28553.72 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 49.04 | 0.0000 | Y | 262.84 |
CORE_BOTTOM_LIGHTS | CORE_BOTTOM | CORE_BOTTOM | GENERAL | 10.2732 | 2496.12 | 25643.24 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 49.04 | 0.0000 | Y | 236.05 |
CORE_MID_LIGHTS | CORE_MID | CORE_MID | GENERAL | 10.2732 | 24961.20 | 256432.45 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 49.04 | 0.0000 | Y | 2360.52 |
CORE_TOP_LIGHTS | CORE_TOP | CORE_TOP | GENERAL | 10.2732 | 2496.12 | 25643.24 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 49.04 | 0.0000 | Y | 236.05 |
PERIMETER_BOT_ZN_3_LIGHTS | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3 | GENERAL | 10.2732 | 313.41 | 3219.77 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 28.47 | 0.0000 | Y | 17.21 |
PERIMETER_BOT_ZN_2_LIGHTS | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2 | GENERAL | 10.2732 | 201.98 | 2074.94 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 28.31 | 0.0000 | Y | 11.02 |
PERIMETER_BOT_ZN_1_LIGHTS | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1 | GENERAL | 10.2732 | 313.42 | 3219.84 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 28.05 | 0.0000 | Y | 16.96 |
PERIMETER_BOT_ZN_4_LIGHTS | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4 | GENERAL | 10.2732 | 201.98 | 2074.94 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 28.26 | 0.0000 | Y | 11.01 |
PERIMETER_MID_ZN_3_LIGHTS | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3 | GENERAL | 10.2732 | 3134.13 | 32197.65 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 28.40 | 0.0000 | Y | 171.63 |
PERIMETER_MID_ZN_2_LIGHTS | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2 | GENERAL | 10.2732 | 2019.75 | 20749.39 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 28.26 | 0.0000 | Y | 110.06 |
PERIMETER_MID_ZN_1_LIGHTS | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1 | GENERAL | 10.2732 | 3134.20 | 32198.36 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 28.01 | 0.0000 | Y | 169.31 |
PERIMETER_MID_ZN_4_LIGHTS | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4 | GENERAL | 10.2732 | 2019.75 | 20749.39 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 28.20 | 0.0000 | Y | 109.84 |
PERIMETER_TOP_ZN_3_LIGHTS | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3 | GENERAL | 10.2732 | 313.41 | 3219.77 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 28.39 | 0.0000 | Y | 17.16 |
PERIMETER_TOP_ZN_2_LIGHTS | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2 | GENERAL | 10.2732 | 201.98 | 2074.94 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 28.26 | 0.0000 | Y | 11.01 |
PERIMETER_TOP_ZN_1_LIGHTS | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1 | GENERAL | 10.2732 | 313.42 | 3219.84 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 28.01 | 0.0000 | Y | 16.93 |
PERIMETER_TOP_ZN_4_LIGHTS | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4 | GENERAL | 10.2732 | 201.98 | 2074.94 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 28.20 | 0.0000 | Y | 10.98 |
DATACENTER_BASEMENT_LIGHTS | DATACENTER_BASEMENT_ZN_6 | DATACENTER_BASEMENT_ZN_6 | GENERAL | 10.2732 | 783.68 | 8050.93 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 49.04 | 0.0000 | Y | 74.11 |
DATACENTER_BOT_LIGHTS | DATACENTER_BOT_ZN_6 | DATACENTER_BOT_ZN_6 | GENERAL | 17.8735 | 36.20 | 647.07 | LightsWired | LTG_SCH_DATACENTER | 56.02 | 168.00 | 54.57 | 0.0000 | Y | 6.63 |
DATACENTER_MID_LIGHTS | DATACENTER_MID_ZN_6 | DATACENTER_MID_ZN_6 | GENERAL | 17.8735 | 362.03 | 6470.68 | LightsWired | LTG_SCH_DATACENTER | 56.02 | 168.00 | 54.57 | 0.0000 | Y | 66.28 |
DATACENTER_TOP_LIGHTS | DATACENTER_TOP_ZN_6 | DATACENTER_TOP_ZN_6 | GENERAL | 17.8735 | 36.20 | 647.07 | LightsWired | LTG_SCH_DATACENTER | 56.02 | 168.00 | 54.57 | 0.0000 | Y | 6.63 |
Interior Lighting Total | 10.3445 | 46320.38 | 479162.15 | 1233.36 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
PERIMETER_BOT_ZN_1_DAYLREFPT1 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_DAYLCTRL | SplitFlux | Stepped | 0.39 | 3219.84 | 1241.89 |
PERIMETER_BOT_ZN_1_DAYLREFPT2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_DAYLCTRL | SplitFlux | Stepped | 0.14 | 3219.84 | 445.95 |
PERIMETER_BOT_ZN_2_DAYLREFPT1 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_DAYLCTRL | SplitFlux | Stepped | 0.39 | 2074.94 | 800.30 |
PERIMETER_BOT_ZN_2_DAYLREFPT2 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_DAYLCTRL | SplitFlux | Stepped | 0.14 | 2074.94 | 287.38 |
PERIMETER_BOT_ZN_3_DAYLREFPT1 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_DAYLCTRL | SplitFlux | Stepped | 0.39 | 3219.77 | 1241.86 |
PERIMETER_BOT_ZN_3_DAYLREFPT2 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_DAYLCTRL | SplitFlux | Stepped | 0.14 | 3219.77 | 445.94 |
PERIMETER_BOT_ZN_4_DAYLREFPT1 | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_DAYLCTRL | SplitFlux | Stepped | 0.39 | 2074.94 | 800.30 |
PERIMETER_BOT_ZN_4_DAYLREFPT2 | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_DAYLCTRL | SplitFlux | Stepped | 0.14 | 2074.94 | 287.38 |
PERIMETER_MID_ZN_1_DAYLREFPT1 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_DAYLCTRL | SplitFlux | Stepped | 0.39 | 3219.84 | 1241.89 |
PERIMETER_MID_ZN_1_DAYLREFPT2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_DAYLCTRL | SplitFlux | Stepped | 0.14 | 3219.84 | 445.95 |
PERIMETER_MID_ZN_2_DAYLREFPT1 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_DAYLCTRL | SplitFlux | Stepped | 0.39 | 2074.94 | 800.30 |
PERIMETER_MID_ZN_2_DAYLREFPT2 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_DAYLCTRL | SplitFlux | Stepped | 0.14 | 2074.94 | 287.38 |
PERIMETER_MID_ZN_3_DAYLREFPT1 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_DAYLCTRL | SplitFlux | Stepped | 0.39 | 3219.77 | 1241.86 |
PERIMETER_MID_ZN_3_DAYLREFPT2 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_DAYLCTRL | SplitFlux | Stepped | 0.14 | 3219.77 | 445.94 |
PERIMETER_MID_ZN_4_DAYLREFPT1 | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_DAYLCTRL | SplitFlux | Stepped | 0.39 | 2074.94 | 800.30 |
PERIMETER_MID_ZN_4_DAYLREFPT2 | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_DAYLCTRL | SplitFlux | Stepped | 0.14 | 2074.94 | 287.38 |
PERIMETER_TOP_ZN_1_DAYLREFPT1 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_DAYLCTRL | SplitFlux | Stepped | 0.39 | 3219.84 | 1241.89 |
PERIMETER_TOP_ZN_1_DAYLREFPT2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_DAYLCTRL | SplitFlux | Stepped | 0.14 | 3219.84 | 445.95 |
PERIMETER_TOP_ZN_2_DAYLREFPT1 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_DAYLCTRL | SplitFlux | Stepped | 0.39 | 2074.94 | 800.30 |
PERIMETER_TOP_ZN_2_DAYLREFPT2 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_DAYLCTRL | SplitFlux | Stepped | 0.14 | 2074.94 | 287.38 |
PERIMETER_TOP_ZN_3_DAYLREFPT1 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_DAYLCTRL | SplitFlux | Stepped | 0.39 | 3219.77 | 1241.86 |
PERIMETER_TOP_ZN_3_DAYLREFPT2 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_DAYLCTRL | SplitFlux | Stepped | 0.14 | 3219.77 | 445.94 |
PERIMETER_TOP_ZN_4_DAYLREFPT1 | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_DAYLCTRL | SplitFlux | Stepped | 0.39 | 2074.94 | 800.30 |
PERIMETER_TOP_ZN_4_DAYLREFPT2 | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_DAYLCTRL | SplitFlux | Stepped | 0.14 | 2074.94 | 287.38 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS_A | 13279.00 | AstronomicalClock | - | 41.82 | 41.82 | 104.25 | |
EXTERIOR_LIGHTS_B | 44301.60 | AstronomicalClock | - | 83.82 | 71.22 | 592.30 | |
Exterior Lighting Total | 57580.60 | 696.56 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 08:43:45
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
BYPASS HEAT EXCHANGER | HeatExchanger:FluidToFluid | 3315344.64 | |||||
HEATSYS1 BOILER | Boiler:HotWater | 1502266.44 | 0.81 | ||||
COOLSYS1 CHILLER1 | Chiller:Electric:ReformulatedEIR | 1687769.75 | 6.28 | 1615426.59 | 5.98 | 6.84 | 23.33 |
COOLSYS1 CHILLER2 | Chiller:Electric:ReformulatedEIR | 1687769.75 | 6.28 | 1615426.59 | 5.98 | 6.84 | 23.33 |
CENTRAL TOWER | FluidCooler:TwoSpeed | 582060.00 | |||||
CENTRAL BOILER | Boiler:HotWater | 543702.46 | 0.80 | ||||
TOWERWATERSYS COOLTOWER 1 | CoolingTower:VariableSpeed | 2002498.32 | |||||
TOWERWATERSYS COOLTOWER 2 | CoolingTower:VariableSpeed | 2002498.32 |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
VAV_BOT WITH REHEAT COOLING COIL | Coil:Cooling:Water | 270084.32 | 275418.77 | 186343.79 | 89074.99 | 0.68 | - | 28670.70 | 290.79 |
VAV_MID WITH REHEAT COOLING COIL | Coil:Cooling:Water | 2643274.95 | 2625714.47 | 1767845.58 | 857868.89 | 0.67 | - | 274315.81 | 2782.26 |
VAV_TOP WITH REHEAT COOLING COIL | Coil:Cooling:Water | 271050.54 | 278474.70 | 188653.35 | 89821.35 | 0.68 | - | 28982.75 | 293.96 |
CAV_BAS COOLING COIL | Coil:Cooling:Water | 138576.71 | 153793.86 | 106298.39 | 47495.47 | 0.69 | - | 15674.26 | 158.98 |
AIRLOOP DATACENTER BASEMENT COOLING COIL | Coil:Cooling:WaterToAirHeatPump:EquationFit | 436486.14 | 313639.03 | 122847.11 | 0.72 | 0.00 | |||
AIRLOOP DATACENTER BOT COOLING COIL | Coil:Cooling:WaterToAirHeatPump:EquationFit | 9798.88 | 7029.32 | 2769.57 | 0.72 | 0.00 | |||
AIRLOOP DATACENTER MID COOLING COIL | Coil:Cooling:WaterToAirHeatPump:EquationFit | 93691.14 | 67117.65 | 26573.49 | 0.72 | 0.00 | |||
AIRLOOP DATACENTER TOP COOLING COIL | Coil:Cooling:WaterToAirHeatPump:EquationFit | 9544.35 | 6841.26 | 2703.09 | 0.72 | 0.00 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
None |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
None |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Water | 19711.84 | 18690.67 | - |
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Water | 403865.23 | 382712.63 | - |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Water | 62558.34 | 59240.46 | - |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 6789.76 | 6431.54 | - |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 5398.09 | 5114.14 | - |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 8348.41 | 7912.09 | - |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 4712.47 | 4466.68 | - |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 161898.76 | 153399.89 | - |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 106699.93 | 101098.18 | - |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 160348.89 | 151931.75 | - |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 98090.89 | 92942.68 | - |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 19847.35 | 18804.64 | - |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 13010.56 | 12326.99 | - |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 19707.40 | 18672.07 | - |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 12359.33 | 11710.08 | - |
VAV_BOT WITH REHEAT HEATING COIL | Coil:Heating:Water | 15573.04 | 13918.06 | - |
VAV_MID WITH REHEAT HEATING COIL | Coil:Heating:Water | 94643.34 | 86346.21 | - |
VAV_TOP WITH REHEAT HEATING COIL | Coil:Heating:Water | 7127.01 | 6578.99 | - |
CAV_BAS HEATING COIL | Coil:Heating:Water | 281575.79 | 230153.76 | - |
AIRLOOP DATACENTER BASEMENT HEATING COIL | Coil:Heating:WaterToAirHeatPump:EquationFit | 436486.14 | 0.00 | |
AIRLOOP DATACENTER BOT HEATING COIL | Coil:Heating:WaterToAirHeatPump:EquationFit | 9798.88 | 0.00 | |
AIRLOOP DATACENTER MID HEATING COIL | Coil:Heating:WaterToAirHeatPump:EquationFit | 93691.14 | 0.00 | |
AIRLOOP DATACENTER TOP HEATING COIL | Coil:Heating:WaterToAirHeatPump:EquationFit | 9544.35 | 0.00 | |
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | Coil:Heating:Electric | 12800.94 | 1.00 | |
AIRLOOP DATACENTER BOT_SUPPHEATCOIL | Coil:Heating:Electric | 591.35 | 1.00 | |
AIRLOOP DATACENTER MID_SUPPHEATCOIL | Coil:Heating:Electric | 5913.50 | 1.00 | |
AIRLOOP DATACENTER TOP_SUPPHEATCOIL | Coil:Heating:Electric | 591.35 | 1.00 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
VAV_BOT WITH REHEAT FAN | Fan:VariableVolume | 0.61 | 1314.72 | 10.14 | 21792.44 | 2149.46 | 1.00 | 1.12 | General | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 |
VAV_MID WITH REHEAT FAN | Fan:VariableVolume | 0.61 | 1314.72 | 95.08 | 205454.97 | 2160.95 | 1.00 | 1.08 | General | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 |
VAV_TOP WITH REHEAT FAN | Fan:VariableVolume | 0.61 | 1314.72 | 10.29 | 22126.26 | 2149.46 | 1.00 | 1.12 | General | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 16:10:00 |
CAV_BAS FAN | Fan:ConstantVolume | 0.60 | 1018.41 | 6.09 | 10318.97 | 1695.65 | 1.00 | 1.15 | General | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
AIRLOOP DATACENTER BASEMENT SUPPLY FAN | Fan:OnOff | 0.61 | 1018.41 | 21.43 | 35529.97 | 1657.97 | 1.00 | 1.13 | General | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 07:10:00 |
AIRLOOP DATACENTER BOT SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.48 | 537.75 | 1120.11 | 1.00 | 1.62 | General | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
AIRLOOP DATACENTER MID SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 4.58 | 5128.23 | 1120.11 | 1.00 | 1.16 | General | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
AIRLOOP DATACENTER TOP SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.47 | 522.99 | 1120.11 | 1.00 | 1.64 | General | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
COOLSYS1 PUMP SECONDARY | Pump:VariableSpeed | Intermittent | 105797.75 | 0.141368 | 23081.00 | 163269.45 | 0.90 | General |
HEATSYS1 PUMP | Pump:VariableSpeed | Intermittent | 180705.70 | 0.013142 | 3957.94 | 301156.09 | 0.90 | General |
COOLSYS1 CHILLER1 PUMP | Pump:ConstantSpeed | Intermittent | 73247.35 | 0.070684 | 7989.88 | 113036.94 | 0.90 | General |
COOLSYS1 CHILLER2 PUMP | Pump:ConstantSpeed | Intermittent | 73247.35 | 0.070684 | 7989.88 | 113036.94 | 0.90 | General |
PLANT CIRC PUMP | Pump:ConstantSpeed | Intermittent | 179045.11 | 0.013458 | 3432.39 | 255050.01 | 0.90 | General |
SWHSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 29891.00 | 0.000440 | 56.21 | 127739.32 | 0.30 | General |
TOWERWATERSYS PUMP | HeaderedPumps:VariableSpeed | Intermittent | 148556.62 | 0.167043 | 41356.14 | 247577.87 | 0.90 | General |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 1.14 | 87921.32 | 0.80 | 0.48 | 0.06 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:43:45
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 84401.13 | 84401.13 | 30.37 | 6.086 | 6.086 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 24.00 | 24.00 | 0.00891 | 28.24 | 0.01716 | 1.200 | 0.00 |
CORE_BOTTOM | 87138.28 | 87138.28 | 34.91 | 6.282 | 6.282 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 24.00 | 24.00 | 0.00886 | 28.24 | 0.01716 | 1.078 | 0.00 |
CORE_MID | 823926.45 | 823926.45 | 330.08 | 59.387 | 59.387 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 24.00 | 24.00 | 0.00888 | 28.24 | 0.01716 | 10.778 | 0.00 |
CORE_TOP | 80953.61 | 80953.61 | 32.43 | 5.835 | 5.835 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 24.00 | 24.00 | 0.00889 | 28.24 | 0.01716 | 1.078 | 0.00 |
PERIMETER_BOT_ZN_3 | 15234.02 | 15234.02 | 48.61 | 1.108 | 1.108 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:30:00 | 24.00 | 24.00 | 0.00894 | 31.93 | 0.01716 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_2 | 15258.57 | 15258.57 | 75.55 | 1.110 | 1.110 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 09:40:00 | 24.00 | 24.00 | 0.00879 | 30.27 | 0.01716 | 0.087 | 0.00 |
PERIMETER_BOT_ZN_1 | 15190.28 | 15190.28 | 48.47 | 1.105 | 1.105 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | 24.00 | 24.00 | 0.00894 | 33.20 | 0.01717 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_4 | 19755.40 | 19755.40 | 97.81 | 1.437 | 1.437 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 24.00 | 24.00 | 0.00872 | 32.26 | 0.01717 | 0.087 | 0.00 |
PERIMETER_MID_ZN_3 | 146063.20 | 146063.20 | 466.04 | 10.627 | 10.627 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:40:00 | 24.00 | 24.00 | 0.00920 | 31.82 | 0.01716 | 1.353 | 0.00 |
PERIMETER_MID_ZN_2 | 157821.57 | 157821.57 | 781.39 | 11.482 | 11.482 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 09:50:00 | 24.00 | 24.00 | 0.00894 | 30.46 | 0.01716 | 0.872 | 0.00 |
PERIMETER_MID_ZN_1 | 144835.12 | 144835.12 | 462.11 | 10.537 | 10.537 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 24.00 | 24.00 | 0.00921 | 33.20 | 0.01717 | 1.353 | 0.00 |
PERIMETER_MID_ZN_4 | 175045.27 | 175045.27 | 866.67 | 12.735 | 12.735 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 | 24.00 | 24.00 | 0.00889 | 32.15 | 0.01717 | 0.872 | 0.00 |
PERIMETER_TOP_ZN_3 | 16195.56 | 16195.56 | 51.67 | 1.178 | 1.178 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 24.00 | 24.00 | 0.00923 | 32.26 | 0.01717 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_2 | 15984.08 | 15984.08 | 79.14 | 1.163 | 1.163 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 10:00:00 | 24.00 | 24.00 | 0.00900 | 30.65 | 0.01716 | 0.087 | 0.00 |
PERIMETER_TOP_ZN_1 | 16206.86 | 16206.86 | 51.71 | 1.179 | 1.179 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | 24.00 | 24.00 | 0.00922 | 33.20 | 0.01717 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_4 | 18590.08 | 18590.08 | 92.04 | 1.353 | 1.353 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 24.00 | 24.00 | 0.00893 | 32.26 | 0.01717 | 0.087 | 0.00 |
DATACENTER_BOT_ZN_6 | 8367.75 | 8367.75 | 231.14 | 0.480 | 0.480 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 18:50:00 | 27.00 | 27.00 | 0.00859 | 30.75 | 0.01716 | 0.016 | 0.00 |
DATACENTER_MID_ZN_6 | 79797.71 | 79797.71 | 2204.19 | 4.578 | 4.578 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 18:50:00 | 27.00 | 27.00 | 0.00859 | 30.75 | 0.01716 | 0.156 | 0.00 |
DATACENTER_TOP_ZN_6 | 8138.00 | 8138.00 | 224.79 | 0.467 | 0.467 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | 27.00 | 27.00 | 0.00859 | 30.92 | 0.01716 | 0.016 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 373513.38 | 373513.38 | 476.62 | 21.430 | 21.430 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 07:00:00 | 27.00 | 27.00 | 0.00854 | 27.10 | 0.01716 | 0.338 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.000 | 1.200 | 00:10:00 | 15.60 | 25.07 | 0.00699 | 8.70 | 0.00699 | 1.200 | 0.00 | |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.000 | 1.078 | 00:10:00 | 15.60 | 22.45 | 0.00699 | 8.70 | 0.00699 | 1.078 | 0.00 | |
CORE_MID | 210357.20 | 210357.20 | 84.27 | 8.859 | 10.778 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00800 | 8.70 | 0.00699 | 10.778 | 0.00 |
CORE_TOP | 42783.40 | 42783.40 | 17.14 | 1.815 | 1.815 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00800 | 8.70 | 0.00699 | 1.078 | 0.00 |
PERIMETER_BOT_ZN_3 | 4317.02 | 4317.02 | 13.77 | 0.183 | 0.183 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00770 | 8.70 | 0.00699 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_2 | 3166.69 | 3166.69 | 15.68 | 0.134 | 0.134 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00773 | 8.70 | 0.00699 | 0.087 | 0.00 |
PERIMETER_BOT_ZN_1 | 5851.74 | 5851.74 | 18.67 | 0.248 | 0.248 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00778 | 8.70 | 0.00699 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_4 | 1824.38 | 1824.38 | 9.03 | 0.077 | 0.087 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00755 | 8.70 | 0.00699 | 0.087 | 0.00 |
PERIMETER_MID_ZN_3 | 113335.61 | 113335.61 | 361.62 | 4.830 | 4.830 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00787 | 8.70 | 0.00699 | 1.353 | 0.00 |
PERIMETER_MID_ZN_2 | 74692.14 | 74692.14 | 369.81 | 3.184 | 3.184 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00787 | 8.70 | 0.00699 | 0.872 | 0.00 |
PERIMETER_MID_ZN_1 | 112252.18 | 112252.18 | 358.15 | 4.784 | 4.784 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00787 | 8.70 | 0.00699 | 1.353 | 0.00 |
PERIMETER_MID_ZN_4 | 68672.56 | 68672.56 | 340.00 | 2.926 | 2.926 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00785 | 8.70 | 0.00699 | 0.872 | 0.00 |
PERIMETER_TOP_ZN_3 | 13890.68 | 13890.68 | 44.32 | 0.592 | 0.592 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00789 | 8.70 | 0.00699 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_2 | 9105.63 | 9105.63 | 45.08 | 0.388 | 0.388 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00789 | 8.70 | 0.00699 | 0.087 | 0.00 |
PERIMETER_TOP_ZN_1 | 13792.85 | 13792.85 | 44.01 | 0.588 | 0.588 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00789 | 8.70 | 0.00699 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_4 | 8650.33 | 8650.33 | 42.83 | 0.369 | 0.369 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00788 | 8.70 | 0.00699 | 0.087 | 0.00 |
DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.016 | 00:10:00 | 18.00 | 27.00 | 0.00850 | 8.70 | 0.00699 | 0.016 | 0.00 | |
DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.156 | 00:10:00 | 18.00 | 24.70 | 0.00782 | 8.70 | 0.00699 | 0.156 | 0.00 | |
DATACENTER_TOP_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.016 | 00:10:00 | 18.00 | 23.98 | 0.00708 | 8.70 | 0.00699 | 0.016 | 0.00 | |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.338 | 00:10:00 | 18.00 | 27.00 | 0.00850 | 8.70 | 0.00699 | 0.338 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
VAV_BOT WITH REHEAT | 10.14 | 10.14 | 1.73 | 1.73 | 10.1385 | 2.9619 | 10.1385 | 0.2921 | 0.3000 |
VAV_MID WITH REHEAT | 95.08 | 95.08 | 26.50 | 26.50 | 95.0764 | 28.9100 | 95.0764 | 0.3041 | 0.3000 |
VAV_TOP WITH REHEAT | 10.29 | 10.29 | 3.75 | 3.75 | 10.2938 | 3.7526 | 10.2938 | 0.3645 | 0.3000 |
CAV_BAS | 6.09 | 6.09 | 1.20 | 1.20 | 6.0855 | 6.0855 | 6.0855 | 1.0000 | 1.0000 |
AIRLOOP DATACENTER BASEMENT | 21.43 | 21.43 | 0.34 | 0.34 | 21.4298 | 21.4296 | 21.4298 | 1.0000 | 1.0000 |
AIRLOOP DATACENTER BOT | 0.48 | 0.48 | 0.02 | 0.02 | 0.4801 | 0.4801 | 0.4801 | 1.0000 | 1.0000 |
AIRLOOP DATACENTER MID | 4.58 | 4.58 | 0.16 | 0.16 | 4.5783 | 4.5783 | 4.5783 | 1.0000 | 1.0000 |
AIRLOOP DATACENTER TOP | 0.47 | 0.47 | 0.02 | 0.02 | 0.4669 | 0.4669 | 0.4669 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | 19711.842 | 19711.842 | 1.960039 | 0.00017245 | 397.375 | 1/21 00:10:00 | 1/21 00:10:00 | 19711.84 | 19711.84 | 1.960039 | 12.80 | 11.58 | 0.00800000 | 40.00 | 21.17 | 0.00800000 | 8.70 | 0.00699286 | 8.70 | 0.0000 | 21.00 | 0.00800000 | 51.6560 | 0.00 | 0.00 | 19784.52 | 19784.52 | ||
CORE_MID VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | 403865.231 | 403865.231 | 19.241376 | 0.00353319 | 9127.627 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 403865.23 | 403865.23 | 19.241376 | 12.80 | 11.58 | 0.00800000 | 40.00 | 21.17 | 0.00800000 | 8.70 | 0.00699286 | 8.70 | 0.0000 | 21.00 | 0.00800000 | 51.6560 | 210357.20 | 0.00 | 405243.14 | 405243.14 |
CORE_TOP VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | 62558.340 | 62558.340 | 1.966313 | 0.00054729 | 1613.268 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 62558.34 | 62558.34 | 1.966313 | 12.80 | 11.58 | 0.00800000 | 40.00 | 21.17 | 0.00800000 | 8.70 | 0.00699286 | 8.70 | 0.0000 | 21.00 | 0.00800000 | 51.6560 | 42783.40 | 0.00 | 62750.43 | 62750.43 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | 6789.762 | 6789.762 | 0.246025 | 0.00005940 | 165.890 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 6789.76 | 6789.76 | 0.246025 | 12.80 | 11.58 | 0.00800000 | 40.00 | 21.17 | 0.00800000 | 8.70 | 0.00699286 | 8.70 | 0.0000 | 21.00 | 0.00769805 | 49.7316 | 4317.02 | 0.00 | 6811.63 | 6811.63 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | 5398.090 | 5398.090 | 0.222000 | 0.00004722 | 126.753 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 5398.09 | 5398.09 | 0.222000 | 12.80 | 11.58 | 0.00800000 | 40.00 | 21.17 | 0.00800000 | 8.70 | 0.00699286 | 8.70 | 0.0000 | 21.00 | 0.00772969 | 49.9335 | 3166.69 | 0.00 | 5415.79 | 5415.79 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | 8348.405 | 8348.405 | 0.248366 | 0.00007304 | 220.552 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 8348.41 | 8348.41 | 0.248366 | 12.80 | 11.58 | 0.00800000 | 40.00 | 21.17 | 0.00800000 | 8.70 | 0.00699286 | 8.70 | 0.0000 | 21.00 | 0.00778440 | 50.2825 | 5851.74 | 0.00 | 8378.54 | 8378.54 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | 4712.471 | 4712.471 | 0.287424 | 0.00004123 | 101.303 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 4712.47 | 4712.47 | 0.287424 | 12.80 | 11.58 | 0.00800000 | 40.00 | 21.17 | 0.00800000 | 8.70 | 0.00699286 | 8.70 | 0.0000 | 21.00 | 0.00755437 | 48.8143 | 1824.38 | 0.00 | 4728.97 | 4728.97 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | 161898.763 | 161898.763 | 4.830283 | 0.00141636 | 4271.514 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 161898.76 | 161898.76 | 4.830283 | 12.80 | 11.58 | 0.00800000 | 40.00 | 21.17 | 0.00800000 | 8.70 | 0.00699286 | 8.70 | 0.0000 | 21.00 | 0.00786873 | 50.8205 | 113335.61 | 0.00 | 162443.01 | 162443.01 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | 106699.929 | 106699.929 | 3.183614 | 0.00093346 | 2815.075 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 106699.93 | 106699.93 | 3.183614 | 12.80 | 11.58 | 0.00800000 | 40.00 | 21.17 | 0.00800000 | 8.70 | 0.00699286 | 8.70 | 0.0000 | 21.00 | 0.00786985 | 50.8276 | 74692.14 | 0.00 | 107058.04 | 107058.04 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | 160348.888 | 160348.888 | 4.783906 | 0.00140280 | 4230.678 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 160348.89 | 160348.89 | 4.783906 | 12.80 | 11.58 | 0.00800000 | 40.00 | 21.17 | 0.00800000 | 8.70 | 0.00699286 | 8.70 | 0.0000 | 21.00 | 0.00786687 | 50.8086 | 112252.18 | 0.00 | 160888.32 | 160888.32 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | 98090.893 | 98090.893 | 2.926168 | 0.00085814 | 2588.176 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 98090.89 | 98090.89 | 2.926168 | 12.80 | 11.58 | 0.00800000 | 40.00 | 21.17 | 0.00800000 | 8.70 | 0.00699286 | 8.70 | 0.0000 | 21.00 | 0.00785160 | 50.7113 | 68672.56 | 0.00 | 98421.79 | 98421.79 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | 19847.347 | 19847.347 | 0.592454 | 0.00017363 | 523.526 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 19847.35 | 19847.35 | 0.592454 | 12.80 | 11.58 | 0.00800000 | 40.00 | 21.17 | 0.00800000 | 8.70 | 0.00699286 | 8.70 | 0.0000 | 21.00 | 0.00788618 | 50.9317 | 13890.68 | 0.00 | 19913.18 | 19913.18 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | 13010.562 | 13010.562 | 0.388388 | 0.00011382 | 343.182 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 13010.56 | 13010.56 | 0.388388 | 12.80 | 11.58 | 0.00800000 | 40.00 | 21.17 | 0.00800000 | 8.70 | 0.00699286 | 8.70 | 0.0000 | 21.00 | 0.00788542 | 50.9269 | 9105.63 | 0.00 | 13053.67 | 13053.67 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | 19707.399 | 19707.399 | 0.588266 | 0.00017241 | 519.839 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 19707.40 | 19707.40 | 0.588266 | 12.80 | 11.58 | 0.00800000 | 40.00 | 21.17 | 0.00800000 | 8.70 | 0.00699286 | 8.70 | 0.0000 | 21.00 | 0.00788515 | 50.9251 | 13792.85 | 0.00 | 19772.80 | 19772.80 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | 12359.326 | 12359.326 | 0.368907 | 0.00010812 | 326.020 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 12359.33 | 12359.33 | 0.368907 | 12.80 | 11.58 | 0.00800000 | 40.00 | 21.17 | 0.00800000 | 8.70 | 0.00699286 | 8.70 | 0.0000 | 21.00 | 0.00787636 | 50.8692 | 8650.33 | 0.00 | 12400.40 | 12400.40 |
VAV_BOT WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | VAV_BOT WITH REHEAT | 270084.320 | -999.000 | 10.138544 | 0.01149001 | -999.000 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 270084.32 | 188776.94 | 10.138544 | 26.38 | 19.25 | 0.01105177 | 11.06 | 11.06 | 0.00850000 | 33.13 | 0.01716709 | 25.31 | 25.0351 | 24.00 | 0.00889182 | 47.7834 | 133679.63 | 0.00 | 270539.32 | 184084.57 |
VAV_BOT WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoopHVAC | VAV_BOT WITH REHEAT | 15573.042 | 15573.042 | 3.041563 | 0.00013624 | 276.832 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 15573.04 | 15573.04 | 3.041563 | 8.56 | 8.56 | 0.00703813 | 12.80 | 11.58 | 0.00800000 | 8.70 | 0.00699286 | 8.70 | 83.4502 | 21.67 | 0.00737157 | 45.7419 | 15159.83 | 0.00 | 16851.43 | 16851.43 |
VAV_MID WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | VAV_MID WITH REHEAT | 2643274.952 | -999.000 | 95.076369 | 0.11245103 | -999.000 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 2643274.95 | 1791421.16 | 95.076369 | 26.57 | 19.54 | 0.01135237 | 11.05 | 11.05 | 0.00850000 | 33.00 | 0.01716683 | 25.27 | 26.6964 | 24.00 | 0.00902728 | 48.5023 | 1221431.24 | 0.00 | 2646856.89 | 1752365.53 |
VAV_MID WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoopHVAC | VAV_MID WITH REHEAT | 94643.344 | 94643.344 | 28.522911 | 0.00082798 | 1701.607 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:30:00 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 94643.34 | 94643.34 | 28.522911 | 10.05 | 9.43 | 0.00709615 | 12.80 | 11.58 | 0.00800000 | 8.70 | 0.00699286 | 8.70 | 88.9879 | 21.00 | 0.00792390 | 51.1716 | 538946.73 | 0.00 | 104542.10 | 104542.10 |
VAV_TOP WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | VAV_TOP WITH REHEAT | 271050.544 | -999.000 | 10.293846 | 0.01153112 | -999.000 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 16:10:00 | 271050.54 | 189674.88 | 10.293846 | 26.22 | 19.17 | 0.01101493 | 11.06 | 11.06 | 0.00850000 | 33.00 | 0.01716683 | 25.27 | 24.6574 | 24.00 | 0.00899303 | 48.3213 | 141048.04 | 0.00 | 271503.77 | 184865.10 |
VAV_TOP WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoopHVAC | VAV_TOP WITH REHEAT | 7127.013 | 7127.013 | 3.088154 | 0.00006235 | 128.977 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:30:00 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 7127.01 | 7127.01 | 3.088154 | 10.89 | 9.88 | 0.00715845 | 12.80 | 11.58 | 0.00800000 | 8.70 | 0.00699286 | 8.70 | 82.1912 | 21.00 | 0.00792272 | 51.1640 | 58940.06 | 0.00 | 7965.29 | 7965.29 |
CAV_BAS COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | CAV_BAS | 138576.711 | -999.000 | 6.085539 | 0.00589537 | -999.000 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 138576.71 | 100242.30 | 6.085539 | 24.89 | 18.37 | 0.01053878 | 11.42 | 11.42 | 0.00850000 | 28.24 | 0.01715778 | 24.03 | 19.7214 | 24.00 | 0.00891274 | 47.8936 | 84401.13 | 0.00 | 138774.60 | 97461.15 |
CAV_BAS HEATING COIL | Coil:Heating:Water | AirLoopHVAC | CAV_BAS | 281575.794 | 281575.794 | 6.085539 | 0.00246335 | 6431.563 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 281575.79 | 281575.79 | 6.085539 | 1.72 | 1.72 | 0.00699286 | 40.00 | 21.17 | 0.00800000 | 8.70 | 0.00699286 | 8.70 | 19.7214 | 25.07 | 0.00699286 | 35.3535 | 0.00 | 0.00 | 243677.19 | 243677.19 |
AIRLOOP DATACENTER BASEMENT COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | 436486.136 | 313639.029 | 21.429762 | 0.01068952 | -999.000 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 07:10:00 | 408959.69 | 398442.16 | -999.0 | 28.50 | 18.07 | 0.00867846 | 12.80 | 12.09 | 0.00850000 | 33.20 | 0.01716721 | 25.32 | -999.0000 | 27.00 | 0.00854208 | 38.4360 | 372985.12 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BOT COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER BOT | 9798.885 | 7029.315 | 0.480091 | 0.00023997 | -999.000 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 18:50:00 | 9183.41 | 8700.72 | -999.0 | 28.07 | 18.08 | 0.00886577 | 12.80 | 12.09 | 0.00850000 | 30.92 | 0.01716288 | 24.74 | -999.0000 | 27.00 | 0.00858649 | 38.6307 | 8366.90 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER MID COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER MID | 93691.145 | 67117.651 | 4.578338 | 0.00229449 | -999.000 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 18:50:00 | 87845.19 | 83018.63 | -999.0 | 28.08 | 18.10 | 0.00888346 | 12.80 | 12.09 | 0.00850000 | 30.92 | 0.01716288 | 24.74 | -999.0000 | 27.00 | 0.00859067 | 38.6495 | 79769.94 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER TOP COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER TOP | 9544.353 | 6841.258 | 0.466911 | 0.00023374 | -999.000 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | 8947.16 | 8464.52 | -999.0 | 28.08 | 18.09 | 0.00887602 | 12.80 | 12.09 | 0.00850000 | 30.92 | 0.01716288 | 24.74 | -999.0000 | 27.00 | 0.00858896 | 38.6418 | 8138.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BASEMENT HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | 436486.136 | 436486.136 | 21.429762 | 0.01068952 | -999.000 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 436486.14 | 436486.14 | 21.429762 | 8.70 | 8.70 | 0.00699286 | 40.00 | 21.17 | 0.00800000 | 8.70 | 0.00699286 | 8.70 | 1.5791 | 27.00 | 0.00850000 | 38.2434 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BOT HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER BOT | 9798.885 | 9798.885 | 0.480091 | 0.00023997 | -999.000 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 9798.88 | 9798.88 | 0.480091 | 8.70 | 8.70 | 0.00699286 | 40.00 | 21.17 | 0.00800000 | 8.70 | 0.00699286 | 8.70 | 3.2561 | 27.00 | 0.00850000 | 38.2434 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER MID HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER MID | 93691.145 | 93691.145 | 4.578338 | 0.00229449 | -999.000 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 93691.14 | 93691.14 | 4.578338 | 8.70 | 8.70 | 0.00699286 | 40.00 | 21.17 | 0.00800000 | 8.70 | 0.00699286 | 8.70 | 3.4144 | 24.70 | 0.00782254 | 40.3777 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER TOP HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER TOP | 9544.353 | 9544.353 | 0.466911 | 0.00023374 | -999.000 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 9544.35 | 9544.35 | 0.466911 | 8.70 | 8.70 | 0.00699286 | 40.00 | 21.17 | 0.00800000 | 8.70 | 0.00699286 | 8.70 | 3.3480 | 23.98 | 0.00707501 | 38.1638 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | 12800.936 | 12800.936 | -999.0 | -999.0 | -999.000 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 12800.94 | 12800.94 | 21.429762 | 0.14 | 0.14 | 0.00847620 | 40.00 | 21.17 | 0.00800000 | 8.70 | 0.00699286 | 8.70 | 1.5791 | 27.00 | 0.00850000 | 38.2434 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BOT_SUPPHEATCOIL | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER BOT | 591.350 | 591.350 | -999.0 | -999.0 | -999.000 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 591.35 | 591.35 | 0.480091 | 0.28 | 0.28 | 0.00845093 | 40.00 | 21.17 | 0.00800000 | 8.70 | 0.00699286 | 8.70 | 3.2561 | 27.00 | 0.00850000 | 38.2434 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER MID_SUPPHEATCOIL | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER MID | 5913.502 | 5913.502 | -999.0 | -999.0 | -999.000 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 5913.50 | 5913.50 | 4.578338 | 0.30 | 0.30 | 0.00779421 | 40.00 | 21.17 | 0.00800000 | 8.70 | 0.00699286 | 8.70 | 3.4144 | 24.70 | 0.00782254 | 40.3777 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER TOP_SUPPHEATCOIL | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER TOP | 591.350 | 591.350 | -999.0 | -999.0 | -999.000 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 591.35 | 591.35 | 0.466911 | 0.29 | 0.29 | 0.00707226 | 40.00 | 21.17 | 0.00800000 | 8.70 | 0.00699286 | 8.70 | 3.3480 | 23.98 | 0.00707501 | 38.1638 | 0.00 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 08:43:45
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
CORE_BOTTOM VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | CORE_BOTTOM | N/A | N/A | N/A | Yes | Yes | Yes | No | 19711.842 | 19711.842 | 1.960039 | 0.00017245 | 397.375 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2027 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 13.14114152 | 54.44 | 82.22 | 27.78 | 1532500.15 | 1.2863 | 1.312140 | 1/21 00:10:00 | unknown | unknown | 1/21 00:10:00 | Sensible | 19711.84 | 19711.84 | 1.0000 | 2.35741477 | 1.960039 | 12.80 | 11.58 | 0.00800000 | 33059.8 | 40.00 | 21.17 | 0.00800000 | 60796.0 | 0.17243020 | 60.00 | 32.22 | 27.78 | 0.000 | 19711.84 | 8.70 | 0.00699286 | 8.70 | 0.00000000 | 0.0000 | 21.00 | 0.00800000 | 21.00 | 0.00800000 | 51.6560 | 0.00 | 0.00 | 19784.52 | 19784.52 | 2.35741477 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 21.03 | 14.86 | 0.00800000 | 41452.3 | |||
CORE_MID VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | CORE_MID | N/A | N/A | N/A | Yes | Yes | Yes | No | 403865.231 | 403865.231 | 19.241376 | 0.00353319 | 9127.627 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2027 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 13.14114152 | 54.44 | 82.22 | 27.78 | 1532500.15 | 26.3534 | 26.883728 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 403865.23 | 403865.23 | 1.0000 | 23.14235211 | 19.241376 | 12.80 | 11.58 | 0.00800000 | 33059.8 | 40.00 | 21.17 | 0.00800000 | 60796.0 | 3.53282880 | 60.00 | 32.22 | 27.78 | 0.000 | 403865.23 | 8.70 | 0.00699286 | 8.70 | 0.00000000 | 0.0000 | 20.91 | 0.00800000 | 21.00 | 0.00800000 | 51.6560 | 210357.20 | 0.00 | 405243.14 | 405243.14 | 23.14235211 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 29.97 | 18.03 | 0.00800000 | 50570.7 | |
CORE_TOP VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | CORE_TOP | N/A | N/A | N/A | Yes | Yes | Yes | No | 62558.340 | 62558.340 | 1.966313 | 0.00054729 | 1613.268 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2027 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 13.14114152 | 54.44 | 82.22 | 27.78 | 1532500.15 | 4.0821 | 4.164264 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 62558.34 | 62558.34 | 1.0000 | 2.36496109 | 1.966313 | 12.80 | 11.58 | 0.00800000 | 33059.8 | 40.00 | 21.17 | 0.00800000 | 60796.0 | 0.54723182 | 60.00 | 32.22 | 27.78 | 0.000 | 62558.34 | 8.70 | 0.00699286 | 8.70 | 0.00000000 | 0.0000 | 20.86 | 0.00800000 | 21.00 | 0.00800000 | 51.6560 | 42783.40 | 0.00 | 62750.43 | 62750.43 | 2.36496109 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 38.82 | 20.83 | 0.00800000 | 59593.2 | |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | PERIMETER_BOT_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 6789.762 | 6789.762 | 0.246025 | 0.00005940 | 165.890 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2027 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 13.14114152 | 54.44 | 82.22 | 27.78 | 1532500.15 | 0.4431 | 0.451968 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 6789.76 | 6789.76 | 1.0000 | 0.29590381 | 0.246025 | 12.80 | 11.58 | 0.00800000 | 33059.8 | 40.00 | 21.17 | 0.00800000 | 60796.0 | 0.05939374 | 60.00 | 32.22 | 27.78 | 0.000 | 6789.76 | 8.70 | 0.00699286 | 8.70 | 0.00000000 | 0.0000 | 20.87 | 0.00769805 | 21.00 | 0.00769805 | 49.7316 | 4317.02 | 0.00 | 6811.63 | 6811.63 | 0.29590381 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 35.37 | 19.77 | 0.00800000 | 56079.6 | |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | PERIMETER_BOT_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 5398.090 | 5398.090 | 0.222000 | 0.00004722 | 126.753 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2027 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 13.14114152 | 54.44 | 82.22 | 27.78 | 1532500.15 | 0.3522 | 0.359330 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 5398.09 | 5398.09 | 1.0000 | 0.26700808 | 0.222000 | 12.80 | 11.58 | 0.00800000 | 33059.8 | 40.00 | 21.17 | 0.00800000 | 60796.0 | 0.04722003 | 60.00 | 32.22 | 27.78 | 0.000 | 5398.09 | 8.70 | 0.00699286 | 8.70 | 0.00000000 | 0.0000 | 20.87 | 0.00772969 | 21.00 | 0.00772969 | 49.9335 | 3166.69 | 0.00 | 5415.79 | 5415.79 | 0.26700808 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.69 | 18.92 | 0.00800000 | 53343.1 | |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | PERIMETER_BOT_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 8348.405 | 8348.405 | 0.248366 | 0.00007304 | 220.552 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2027 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 13.14114152 | 54.44 | 82.22 | 27.78 | 1532500.15 | 0.5448 | 0.555721 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 8348.41 | 8348.41 | 1.0000 | 0.29871912 | 0.248366 | 12.80 | 11.58 | 0.00800000 | 33059.8 | 40.00 | 21.17 | 0.00800000 | 60796.0 | 0.07302804 | 60.00 | 32.22 | 27.78 | 0.000 | 8348.41 | 8.70 | 0.00699286 | 8.70 | 0.00000000 | 0.0000 | 20.92 | 0.00778440 | 21.00 | 0.00778440 | 50.2825 | 5851.74 | 0.00 | 8378.54 | 8378.54 | 0.29871912 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.31 | 21.27 | 0.00800000 | 61108.1 | |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | PERIMETER_BOT_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 4712.471 | 4712.471 | 0.287424 | 0.00004123 | 101.303 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2027 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 13.14114152 | 54.44 | 82.22 | 27.78 | 1532500.15 | 0.3075 | 0.313691 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 4712.47 | 4712.47 | 1.0000 | 0.34569551 | 0.287424 | 12.80 | 11.58 | 0.00800000 | 33059.8 | 40.00 | 21.17 | 0.00800000 | 60796.0 | 0.04122255 | 60.00 | 32.22 | 27.78 | 0.000 | 4712.47 | 8.70 | 0.00699286 | 8.70 | 0.00000000 | 0.0000 | 20.85 | 0.00755437 | 21.00 | 0.00755437 | 48.8143 | 1824.38 | 0.00 | 4728.97 | 4728.97 | 0.34569551 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 26.22 | 16.74 | 0.00800000 | 46739.4 | |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | PERIMETER_MID_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 161898.763 | 161898.763 | 4.830283 | 0.00141636 | 4271.514 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2027 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 13.14114152 | 54.44 | 82.22 | 27.78 | 1532500.15 | 10.5644 | 10.776967 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 161898.76 | 161898.76 | 1.0000 | 5.80956903 | 4.830283 | 12.80 | 11.58 | 0.00800000 | 33059.8 | 40.00 | 21.17 | 0.00800000 | 60796.0 | 1.41621653 | 60.00 | 32.22 | 27.78 | 0.000 | 161898.76 | 8.70 | 0.00699286 | 8.70 | 0.00000000 | 0.0000 | 20.95 | 0.00786873 | 21.00 | 0.00786873 | 50.8205 | 113335.61 | 0.00 | 162443.01 | 162443.01 | 5.80956903 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.22 | 21.25 | 0.00800000 | 61021.1 | |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | PERIMETER_MID_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 106699.929 | 106699.929 | 3.183614 | 0.00093346 | 2815.075 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2027 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 13.14114152 | 54.44 | 82.22 | 27.78 | 1532500.15 | 6.9625 | 7.102597 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 106699.93 | 106699.93 | 1.0000 | 3.82905697 | 3.183614 | 12.80 | 11.58 | 0.00800000 | 33059.8 | 40.00 | 21.17 | 0.00800000 | 60796.0 | 0.93336230 | 60.00 | 32.22 | 27.78 | 0.000 | 106699.93 | 8.70 | 0.00699286 | 8.70 | 0.00000000 | 0.0000 | 20.95 | 0.00786985 | 21.00 | 0.00786985 | 50.8276 | 74692.14 | 0.00 | 107058.04 | 107058.04 | 3.82905697 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.22 | 21.25 | 0.00800000 | 61019.2 | |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | PERIMETER_MID_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 160348.888 | 160348.888 | 4.783906 | 0.00140280 | 4230.678 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2027 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 13.14114152 | 54.44 | 82.22 | 27.78 | 1532500.15 | 10.4632 | 10.673798 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 160348.89 | 160348.89 | 1.0000 | 5.75379050 | 4.783906 | 12.80 | 11.58 | 0.00800000 | 33059.8 | 40.00 | 21.17 | 0.00800000 | 60796.0 | 1.40265892 | 60.00 | 32.22 | 27.78 | 0.000 | 160348.89 | 8.70 | 0.00699286 | 8.70 | 0.00000000 | 0.0000 | 20.95 | 0.00786687 | 21.00 | 0.00786687 | 50.8086 | 112252.18 | 0.00 | 160888.32 | 160888.32 | 5.75379050 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.22 | 21.25 | 0.00800000 | 61022.0 | |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | PERIMETER_MID_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 98090.893 | 98090.893 | 2.926168 | 0.00085814 | 2588.176 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2027 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 13.14114152 | 54.44 | 82.22 | 27.78 | 1532500.15 | 6.4007 | 6.529527 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 98090.89 | 98090.89 | 1.0000 | 3.51941676 | 2.926168 | 12.80 | 11.58 | 0.00800000 | 33059.8 | 40.00 | 21.17 | 0.00800000 | 60796.0 | 0.85805439 | 60.00 | 32.22 | 27.78 | 0.000 | 98090.89 | 8.70 | 0.00699286 | 8.70 | 0.00000000 | 0.0000 | 20.91 | 0.00785160 | 21.00 | 0.00785160 | 50.7113 | 68672.56 | 0.00 | 98421.79 | 98421.79 | 3.51941676 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.22 | 21.25 | 0.00800000 | 61025.2 | |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | PERIMETER_TOP_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 19847.347 | 19847.347 | 0.592454 | 0.00017363 | 523.526 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2027 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 13.14114152 | 54.44 | 82.22 | 27.78 | 1532500.15 | 1.2951 | 1.321160 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 19847.35 | 19847.35 | 1.0000 | 0.71256755 | 0.592454 | 12.80 | 11.58 | 0.00800000 | 33059.8 | 40.00 | 21.17 | 0.00800000 | 60796.0 | 0.17361554 | 60.00 | 32.22 | 27.78 | 0.000 | 19847.35 | 8.70 | 0.00699286 | 8.70 | 0.00000000 | 0.0000 | 20.95 | 0.00788618 | 21.00 | 0.00788618 | 50.9317 | 13890.68 | 0.00 | 19913.18 | 19913.18 | 0.71256755 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.21 | 21.24 | 0.00800000 | 61005.5 | |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | PERIMETER_TOP_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 13010.562 | 13010.562 | 0.388388 | 0.00011382 | 343.182 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2027 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 13.14114152 | 54.44 | 82.22 | 27.78 | 1532500.15 | 0.8490 | 0.866062 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 13010.56 | 13010.56 | 1.0000 | 0.46712921 | 0.388388 | 12.80 | 11.58 | 0.00800000 | 33059.8 | 40.00 | 21.17 | 0.00800000 | 60796.0 | 0.11381046 | 60.00 | 32.22 | 27.78 | 0.000 | 13010.56 | 8.70 | 0.00699286 | 8.70 | 0.00000000 | 0.0000 | 20.95 | 0.00788542 | 21.00 | 0.00788542 | 50.9269 | 9105.63 | 0.00 | 13053.67 | 13053.67 | 0.46712921 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.20 | 21.24 | 0.00800000 | 61004.3 | |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | PERIMETER_TOP_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 19707.399 | 19707.399 | 0.588266 | 0.00017241 | 519.839 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2027 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 13.14114152 | 54.44 | 82.22 | 27.78 | 1532500.15 | 1.2860 | 1.311844 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 19707.40 | 19707.40 | 1.0000 | 0.70753063 | 0.588266 | 12.80 | 11.58 | 0.00800000 | 33059.8 | 40.00 | 21.17 | 0.00800000 | 60796.0 | 0.17239134 | 60.00 | 32.22 | 27.78 | 0.000 | 19707.40 | 8.70 | 0.00699286 | 8.70 | 0.00000000 | 0.0000 | 20.95 | 0.00788515 | 21.00 | 0.00788515 | 50.9251 | 13792.85 | 0.00 | 19772.80 | 19772.80 | 0.70753063 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.21 | 21.24 | 0.00800000 | 61006.0 | |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | PERIMETER_TOP_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 12359.326 | 12359.326 | 0.368907 | 0.00010812 | 326.020 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2027 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 13.14114152 | 54.44 | 82.22 | 27.78 | 1532500.15 | 0.8065 | 0.822712 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 12359.33 | 12359.33 | 1.0000 | 0.44369863 | 0.368907 | 12.80 | 11.58 | 0.00800000 | 33059.8 | 40.00 | 21.17 | 0.00800000 | 60796.0 | 0.10811375 | 60.00 | 32.22 | 27.78 | 0.000 | 12359.33 | 8.70 | 0.00699286 | 8.70 | 0.00000000 | 0.0000 | 20.95 | 0.00787636 | 21.00 | 0.00787636 | 50.8692 | 8650.33 | 0.00 | 12400.40 | 12400.40 | 0.44369863 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.21 | 21.24 | 0.00800000 | 61007.6 | |
VAV_BOT WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV_BOT WITH REHEAT | CORE_BOTTOM; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 270084.320 | -999.000 | 10.138544 | 0.01149001 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1025.3847 | 1004.8586 | 1.2027 | VAV_BOT WITH REHEAT FAN | Fan:VariableVolume | 10.138544 | 12.19402185 | 4197.9300 | 999.8980 | 141.35310771 | 12.27 | 6.67 | 5.60 | 3322986.53 | 8.1278 | 8.127759 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | Sensible | 270084.32 | 188776.94 | 1.0000 | 12.19402185 | 10.138544 | 26.38 | 19.25 | 0.01105177 | 54692.2 | 11.06 | 11.06 | 0.00850000 | 32543.3 | 11.48883925 | 6.67 | 12.27 | 5.60 | 21792.441 | 248291.88 | 33.13 | 0.01716709 | 25.31 | 2.53819000 | 25.0351 | 24.00 | 0.00889182 | 24.00 | 0.00889182 | 47.7834 | 133679.63 | 0.00 | 270539.32 | 184084.57 | 12.19402185 | 26.38 | 19.27 | 0.01105177 | 54692.2 | 11.66 | 11.36 | 0.00824123 | 32506.0 | |
VAV_BOT WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV_BOT WITH REHEAT | CORE_BOTTOM; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 15573.042 | 15573.042 | 3.041563 | 0.00013624 | 276.832 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2027 | VAV_BOT WITH REHEAT FAN | Fan:VariableVolume | 10.138544 | 12.19402185 | 4197.9300 | 999.8980 | 13.14114152 | 54.44 | 82.22 | 27.78 | 1532500.15 | 1.0162 | 1.036636 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 15573.04 | 15573.04 | 1.0000 | 3.65820656 | 3.041563 | 8.56 | 8.56 | 0.00703813 | 26319.0 | 12.80 | 11.58 | 0.00800000 | 33059.8 | 0.13622586 | 60.00 | 32.22 | 27.78 | 0.000 | 15573.04 | 8.70 | 0.00699286 | 8.70 | 2.53819000 | 83.4502 | 7.88 | 0.00726641 | 21.67 | 0.00737157 | 45.7419 | 15159.83 | 0.00 | 16851.43 | 16851.43 | 3.65820656 | 2.80 | 2.80 | 0.00703813 | 20452.1 | 7.33 | 7.33 | 0.00703813 | 25058.6 | |
VAV_MID WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV_MID WITH REHEAT | CORE_MID; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 2643274.952 | -999.000 | 95.076369 | 0.11245103 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1025.9435 | 1004.8586 | 1.2027 | VAV_MID WITH REHEAT FAN | Fan:VariableVolume | 95.076369 | 114.35205095 | 4197.9300 | 999.8980 | 141.35310771 | 12.27 | 6.67 | 5.60 | 3322986.53 | 79.5452 | 79.545160 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | Sensible | 2643274.95 | 1791421.16 | 1.0000 | 114.35205095 | 95.076369 | 26.57 | 19.54 | 0.01135237 | 55650.0 | 11.05 | 11.05 | 0.00850000 | 32534.8 | 112.43955575 | 6.67 | 12.27 | 5.60 | 205454.970 | 2437819.98 | 33.00 | 0.01716683 | 25.27 | 25.38195000 | 26.6964 | 24.00 | 0.00902728 | 24.00 | 0.00902728 | 48.5023 | 1221431.24 | 0.00 | 2646856.89 | 1752365.53 | 114.35205095 | 26.57 | 19.55 | 0.01135237 | 55650.0 | 11.63 | 11.36 | 0.00825145 | 32503.5 | |
VAV_MID WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV_MID WITH REHEAT | CORE_MID; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 94643.344 | 94643.344 | 28.522911 | 0.00082798 | 1701.607 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2027 | VAV_MID WITH REHEAT FAN | Fan:VariableVolume | 95.076369 | 114.35205095 | 4197.9300 | 999.8980 | 13.14114152 | 54.44 | 82.22 | 27.78 | 1532500.15 | 6.1757 | 6.300037 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:30:00 | unknown | unknown | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 94643.34 | 94643.34 | 1.0000 | 34.30561529 | 28.522911 | 10.05 | 9.43 | 0.00709615 | 27982.8 | 12.80 | 11.58 | 0.00800000 | 33059.8 | 0.82789680 | 60.00 | 32.22 | 27.78 | 0.000 | 94643.34 | 8.70 | 0.00699286 | 8.70 | 25.38195000 | 88.9879 | 21.00 | 0.00793085 | 21.00 | 0.00792390 | 51.1716 | 538946.73 | 0.00 | 104542.10 | 104542.10 | 34.30561529 | 2.80 | 2.80 | 0.00709615 | 20597.5 | 5.79 | 5.79 | 0.00709615 | 23644.9 | |
VAV_TOP WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV_TOP WITH REHEAT | CORE_TOP; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 271050.544 | -999.000 | 10.293846 | 0.01153112 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1025.3162 | 1004.8586 | 1.2027 | VAV_TOP WITH REHEAT FAN | Fan:VariableVolume | 10.293846 | 12.38080936 | 4197.9300 | 999.8980 | 141.35310771 | 12.27 | 6.67 | 5.60 | 3322986.53 | 8.1568 | 8.156835 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 16:10:00 | Sensible | 271050.54 | 189674.88 | 1.0000 | 12.38080936 | 10.293846 | 26.22 | 19.17 | 0.01101493 | 54436.0 | 11.06 | 11.06 | 0.00850000 | 32543.2 | 11.52994045 | 6.67 | 12.27 | 5.60 | 22126.257 | 248924.29 | 33.00 | 0.01716683 | 25.27 | 2.53819000 | 24.6574 | 24.00 | 0.00899303 | 24.00 | 0.00899303 | 48.3213 | 141048.04 | 0.00 | 271503.77 | 184865.10 | 12.38080936 | 26.22 | 19.19 | 0.01101493 | 54436.0 | 11.66 | 11.36 | 0.00824090 | 32506.6 | |
VAV_TOP WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV_TOP WITH REHEAT | CORE_TOP; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 7127.013 | 7127.013 | 3.088154 | 0.00006235 | 128.977 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2027 | VAV_TOP WITH REHEAT FAN | Fan:VariableVolume | 10.293846 | 12.38080936 | 4197.9300 | 999.8980 | 13.14114152 | 54.44 | 82.22 | 27.78 | 1532500.15 | 0.4651 | 0.474417 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:30:00 | unknown | unknown | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 7127.01 | 7127.01 | 1.0000 | 3.71424281 | 3.088154 | 10.89 | 9.88 | 0.00715845 | 28990.9 | 12.80 | 11.58 | 0.00800000 | 33059.8 | 0.06234386 | 60.00 | 32.22 | 27.78 | 0.000 | 7127.01 | 8.70 | 0.00699286 | 8.70 | 2.53819000 | 82.1912 | 21.00 | 0.00792272 | 21.00 | 0.00792272 | 51.1640 | 58940.06 | 0.00 | 7965.29 | 7965.29 | 3.71424281 | 2.80 | 2.80 | 0.00715845 | 20753.7 | 4.91 | 4.91 | 0.00715845 | 22898.2 | |
CAV_BAS COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | CAV_BAS | BASEMENT | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 138576.711 | -999.000 | 6.085539 | 0.00589537 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1024.4311 | 1004.8586 | 1.2027 | CAV_BAS FAN | Fan:ConstantVolume | 6.085539 | 7.31931446 | 4197.9300 | 999.8980 | 141.35310771 | 12.27 | 6.67 | 5.60 | 3322986.53 | 4.1702 | 4.170246 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | Sensible | 138576.71 | 100242.30 | 1.0000 | 7.31931446 | 6.085539 | 24.89 | 18.37 | 0.01053878 | 51850.6 | 11.42 | 11.42 | 0.00850000 | 32917.6 | 5.89477226 | 6.67 | 12.27 | 5.60 | 10318.970 | 128257.74 | 28.24 | 0.01715778 | 24.03 | 1.20015641 | 19.7214 | 24.06 | 0.00891274 | 24.00 | 0.00891274 | 47.8936 | 84401.13 | 0.00 | 138774.60 | 97461.15 | 7.31931446 | 24.89 | 18.38 | 0.01053878 | 51850.6 | 11.89 | 11.52 | 0.00830162 | 32890.5 | |
CAV_BAS HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | CAV_BAS | BASEMENT | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 281575.794 | 281575.794 | 6.085539 | 0.00246335 | 6431.563 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2027 | CAV_BAS FAN | Fan:ConstantVolume | 6.085539 | 7.31931446 | 4197.9300 | 999.8980 | 13.14114152 | 54.44 | 82.22 | 27.78 | 1532500.15 | 18.3736 | 18.743399 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 281575.79 | 281575.79 | 1.0000 | 7.31931446 | 6.085539 | 1.72 | 1.72 | 0.00699286 | 19235.1 | 40.00 | 21.17 | 0.00800000 | 60796.0 | 2.46309659 | 60.00 | 32.22 | 27.78 | 0.000 | 281575.79 | 8.70 | 0.00699286 | 8.70 | 1.20015641 | 19.7214 | 0.00 | 0.00699286 | 25.07 | 0.00699286 | 35.3535 | 0.00 | 0.00 | 243677.19 | 243677.19 | 7.31931446 | 12.80 | 10.55 | 0.00699286 | 30517.1 | 45.51 | 22.07 | 0.00699286 | 63809.4 | |
AIRLOOP DATACENTER BASEMENT COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | DATACENTER_BASEMENT_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 436486.136 | 313639.029 | 21.429762 | 0.01068952 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1020.9728 | 1004.8586 | 1.2027 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 07:10:00 | Sensible | 408959.69 | 398442.16 | 0.9369 | -999.0 | -999.0 | 28.50 | 18.07 | 0.00867846 | 50799.6 | 12.80 | 12.09 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 408959.69 | 33.20 | 0.01716721 | 25.32 | 0.33839277 | -999.0000 | 27.00 | 0.00854208 | 27.00 | 0.00854208 | 38.4360 | 372985.12 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BOT COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BOT | DATACENTER_BOT_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 9798.885 | 7029.315 | 0.480091 | 0.00023997 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1021.3210 | 1004.8586 | 1.2027 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 18:50:00 | Sensible | 9183.41 | 8700.72 | 0.9372 | -999.0 | -999.0 | 28.07 | 18.08 | 0.00886577 | 50844.9 | 12.80 | 12.09 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9183.41 | 30.92 | 0.01716288 | 24.74 | 0.01563234 | -999.0000 | 27.00 | 0.00858649 | 27.00 | 0.00858649 | 38.6307 | 8366.90 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER MID COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER MID | DATACENTER_MID_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 93691.145 | 67117.651 | 4.578338 | 0.00229449 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1021.3539 | 1004.8586 | 1.2027 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 18:50:00 | Sensible | 87845.19 | 83018.63 | 0.9376 | -999.0 | -999.0 | 28.08 | 18.10 | 0.00888346 | 50896.3 | 12.80 | 12.09 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 87845.19 | 30.92 | 0.01716288 | 24.74 | 0.15632344 | -999.0000 | 27.00 | 0.00859067 | 27.00 | 0.00859067 | 38.6495 | 79769.94 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER TOP COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER TOP | DATACENTER_TOP_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 9544.353 | 6841.258 | 0.466911 | 0.00023374 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1021.3401 | 1004.8586 | 1.2027 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | Sensible | 8947.16 | 8464.52 | 0.9374 | -999.0 | -999.0 | 28.08 | 18.09 | 0.00887602 | 50874.7 | 12.80 | 12.09 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 8947.16 | 30.92 | 0.01716288 | 24.74 | 0.01563234 | -999.0000 | 27.00 | 0.00858896 | 27.00 | 0.00858896 | 38.6418 | 8138.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BASEMENT HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | DATACENTER_BASEMENT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 436486.136 | 436486.136 | 21.429762 | 0.01068952 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 1.2027 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 436486.14 | 436486.14 | 1.0000 | 25.77440968 | 21.429762 | 8.70 | 8.70 | 0.00699286 | 26343.9 | 40.00 | 21.17 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 436486.14 | 8.70 | 0.00699286 | 8.70 | 0.33839277 | 1.5791 | 0.00 | 0.00850000 | 27.00 | 0.00850000 | 38.2434 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BOT HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BOT | DATACENTER_BOT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 9798.885 | 9798.885 | 0.480091 | 0.00023997 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 1.2027 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 9798.88 | 9798.88 | 1.0000 | 0.57742409 | 0.480091 | 8.70 | 8.70 | 0.00699286 | 26343.9 | 40.00 | 21.17 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9798.88 | 8.70 | 0.00699286 | 8.70 | 0.01563234 | 3.2561 | 0.00 | 0.00850000 | 27.00 | 0.00850000 | 38.2434 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER MID HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER MID | DATACENTER_MID_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 93691.145 | 93691.145 | 4.578338 | 0.00229449 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 1.2027 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 93691.14 | 93691.14 | 1.0000 | 5.50654477 | 4.578338 | 8.70 | 8.70 | 0.00699286 | 26343.9 | 40.00 | 21.17 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 93691.14 | 8.70 | 0.00699286 | 8.70 | 0.15632344 | 3.4144 | 0.00 | 0.00782254 | 24.70 | 0.00782254 | 40.3777 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER TOP HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER TOP | DATACENTER_TOP_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 9544.353 | 9544.353 | 0.466911 | 0.00023374 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 1.2027 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 9544.35 | 9544.35 | 1.0000 | 0.56157192 | 0.466911 | 8.70 | 8.70 | 0.00699286 | 26343.9 | 40.00 | 21.17 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9544.35 | 8.70 | 0.00699286 | 8.70 | 0.01563234 | 3.3480 | 0.00 | 0.00707501 | 23.98 | 0.00707501 | 38.1638 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | DATACENTER_BASEMENT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 12800.936 | 12800.936 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2027 | AIRLOOP DATACENTER BASEMENT SUPPLY FAN | Fan:OnOff | 21.429762 | 25.77440968 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 12800.94 | 12800.94 | 1.0000 | 25.77440968 | 21.429762 | 0.14 | 0.14 | 0.00847620 | 21338.7 | 40.00 | 21.17 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 12800.94 | 8.70 | 0.00699286 | 8.70 | 0.33839277 | 1.5791 | 0.00 | 0.00850000 | 27.00 | 0.00850000 | 38.2434 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BOT_SUPPHEATCOIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BOT | DATACENTER_BOT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 591.350 | 591.350 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2027 | AIRLOOP DATACENTER BOT SUPPLY FAN | Fan:OnOff | 0.480091 | 0.57742409 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 591.35 | 591.35 | 1.0000 | 0.57742409 | 0.480091 | 0.28 | 0.28 | 0.00845093 | 21424.4 | 40.00 | 21.17 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 591.35 | 8.70 | 0.00699286 | 8.70 | 0.01563234 | 3.2561 | 0.00 | 0.00850000 | 27.00 | 0.00850000 | 38.2434 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER MID_SUPPHEATCOIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER MID | DATACENTER_MID_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 5913.502 | 5913.502 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2027 | AIRLOOP DATACENTER MID SUPPLY FAN | Fan:OnOff | 4.578338 | 5.50654477 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 5913.50 | 5913.50 | 1.0000 | 5.50654477 | 4.578338 | 0.30 | 0.30 | 0.00779421 | 19795.7 | 40.00 | 21.17 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 5913.50 | 8.70 | 0.00699286 | 8.70 | 0.15632344 | 3.4144 | 0.00 | 0.00782254 | 24.70 | 0.00782254 | 40.3777 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER TOP_SUPPHEATCOIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER TOP | DATACENTER_TOP_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 591.350 | 591.350 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2027 | AIRLOOP DATACENTER TOP SUPPLY FAN | Fan:OnOff | 0.466911 | 0.56157192 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 591.35 | 591.35 | 1.0000 | 0.56157192 | 0.466911 | 0.29 | 0.29 | 0.00707226 | 17983.8 | 40.00 | 21.17 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 591.35 | 8.70 | 0.00699286 | 8.70 | 0.01563234 | 3.3480 | 0.00 | 0.00707501 | 23.98 | 0.00707501 | 38.1638 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 08:43:45
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
None |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
CORE_BOTTOM | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_MID | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_TOP | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
BASEMENT | 5725.33 | 2349.00 | 2349.00 |
CORE_BOTTOM | 5523.83 | 33.67 | 0.00 |
CORE_MID | 3826.67 | 566.67 | 0.00 |
CORE_TOP | 3895.50 | 853.50 | 0.00 |
PERIMETER_BOT_ZN_3 | 5063.33 | 551.83 | 77.83 |
PERIMETER_BOT_ZN_2 | 4844.17 | 731.00 | 212.33 |
PERIMETER_BOT_ZN_1 | 5513.33 | 494.00 | 308.33 |
PERIMETER_BOT_ZN_4 | 5554.67 | 589.50 | 397.83 |
PERIMETER_MID_ZN_3 | 4406.17 | 1400.50 | 309.50 |
PERIMETER_MID_ZN_2 | 3786.50 | 1223.17 | 417.33 |
PERIMETER_MID_ZN_1 | 5287.50 | 843.17 | 507.50 |
PERIMETER_MID_ZN_4 | 4624.33 | 1233.00 | 364.83 |
PERIMETER_TOP_ZN_3 | 4333.67 | 1661.17 | 455.17 |
PERIMETER_TOP_ZN_2 | 4492.17 | 1509.67 | 500.00 |
PERIMETER_TOP_ZN_1 | 5100.00 | 1087.17 | 592.00 |
PERIMETER_TOP_ZN_4 | 4394.83 | 1511.33 | 444.50 |
DATACENTER_BOT_ZN_6 | 5943.00 | 2865.00 | 2865.00 |
DATACENTER_MID_ZN_6 | 5943.00 | 577.67 | 577.67 |
DATACENTER_TOP_ZN_6 | 5931.33 | 1168.83 | 1168.83 |
DATACENTER_BASEMENT_ZN_6 | 5943.00 | 5943.00 | 5943.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
Facility | 5943.00 | 5943.00 | 5943.00 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
BASEMENT | 0.00 | 88.83 | 0.00 | 4.17 |
CORE_BOTTOM | 0.00 | 0.17 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 11.33 | 0.00 | 8.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 40.17 | 0.00 | 39.83 |
PERIMETER_BOT_ZN_1 | 0.00 | 143.17 | 0.00 | 137.83 |
PERIMETER_BOT_ZN_4 | 0.00 | 182.50 | 0.00 | 71.33 |
PERIMETER_MID_ZN_3 | 0.00 | 5.67 | 0.00 | 4.50 |
PERIMETER_MID_ZN_2 | 0.00 | 46.67 | 0.00 | 45.83 |
PERIMETER_MID_ZN_1 | 0.00 | 191.33 | 0.00 | 186.50 |
PERIMETER_MID_ZN_4 | 0.00 | 44.33 | 0.00 | 29.33 |
PERIMETER_TOP_ZN_3 | 0.50 | 23.17 | 0.00 | 19.17 |
PERIMETER_TOP_ZN_2 | 0.17 | 57.83 | 0.00 | 52.67 |
PERIMETER_TOP_ZN_1 | 0.17 | 125.33 | 0.00 | 115.17 |
PERIMETER_TOP_ZN_4 | 0.17 | 51.50 | 0.00 | 34.33 |
DATACENTER_BOT_ZN_6 | 0.00 | 12.33 | 0.00 | 12.33 |
DATACENTER_MID_ZN_6 | 0.00 | 0.33 | 0.00 | 0.33 |
DATACENTER_TOP_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 878.83 | 0.00 | 678.33 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 0.50 | 1369.83 | 0.00 | 1000.17 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 08:43:45
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 60.99 | 149.60 | 6779.02 | 0.524 | 0.000 | 0.000 | 0.000 |
CORE_BOTTOM | 54.77 | 134.35 | 6849.35 | 0.733 | 0.000 | 0.000 | 0.000 |
CORE_MID | 54.77 | 134.35 | 6849.35 | 0.697 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 54.77 | 134.35 | 6849.35 | 0.698 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 6.88 | 16.87 | 860.00 | 0.896 | 0.045 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 4.43 | 10.87 | 554.22 | 1.166 | 0.046 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 6.88 | 16.87 | 860.02 | 1.141 | 0.045 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 4.43 | 10.87 | 554.22 | 1.627 | 0.047 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 6.88 | 16.87 | 860.00 | 0.871 | 0.105 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 3.86 | 10.87 | 554.22 | 1.207 | 0.115 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 6.88 | 16.87 | 860.02 | 1.172 | 0.106 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 4.43 | 10.87 | 554.22 | 1.337 | 0.109 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 6.88 | 16.87 | 860.00 | 0.870 | 0.131 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 4.43 | 10.87 | 554.22 | 1.261 | 0.135 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 6.88 | 16.87 | 860.02 | 1.153 | 0.131 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 4.43 | 10.87 | 554.22 | 1.339 | 0.135 | 0.000 | 0.000 |
DATACENTER_BOT_ZN_6 | 0.79 | 1.95 | 99.34 | 0.584 | 0.000 | 0.000 | 0.000 |
DATACENTER_MID_ZN_6 | 0.79 | 1.95 | 99.34 | 0.584 | 0.000 | 0.000 | 0.000 |
DATACENTER_TOP_ZN_6 | 0.79 | 1.95 | 99.34 | 0.584 | 0.000 | 0.000 | 0.000 |
DATACENTER_BASEMENT_ZN_6 | 17.20 | 42.18 | 1911.37 | 0.658 | 0.000 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 60.99 | 149.60 | 6779.02 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_BOTTOM | 54.77 | 134.35 | 6849.35 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_MID | 54.77 | 134.35 | 6849.35 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 54.77 | 134.35 | 6849.35 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 6.88 | 16.87 | 860.00 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 4.43 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 6.88 | 16.87 | 860.02 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 4.43 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 6.88 | 16.87 | 860.00 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 3.86 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 6.88 | 16.87 | 860.02 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 4.43 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 6.88 | 16.87 | 860.00 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 4.43 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 6.88 | 16.87 | 860.02 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 4.43 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
DATACENTER_BOT_ZN_6 | 0.79 | 1.95 | 99.34 | 0.572 | 0.000 | 0.000 | 0.000 |
DATACENTER_MID_ZN_6 | 0.79 | 1.95 | 99.34 | 0.572 | 0.000 | 0.000 | 0.000 |
DATACENTER_TOP_ZN_6 | 0.79 | 1.95 | 99.34 | 0.572 | 0.000 | 0.000 | 0.000 |
DATACENTER_BASEMENT_ZN_6 | 17.20 | 42.18 | 1911.37 | 0.644 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 08:43:45
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
BASEMENT | CAV_BAS | 60.99 | 149.60 | 6779.02 | 2779.43 | 1.2002 | 1.200 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | 54.77 | 134.35 | 6849.35 | 2496.12 | 0.0000 | 1.078 |
CORE_MID | VAV_MID WITH REHEAT | 54.77 | 134.35 | 6849.35 | 2496.12 | 0.0000 | 10.778 |
CORE_TOP | VAV_TOP WITH REHEAT | 54.77 | 134.35 | 6849.35 | 2496.12 | 0.0000 | 1.078 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | 6.88 | 16.87 | 860.00 | 313.41 | 0.0000 | 0.135 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | 4.43 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | 6.88 | 16.87 | 860.02 | 313.42 | 0.0000 | 0.135 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | 4.43 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | 6.88 | 16.87 | 860.00 | 313.41 | 0.0000 | 1.353 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | 3.86 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.872 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | 6.88 | 16.87 | 860.02 | 313.42 | 0.0000 | 1.353 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | 4.43 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.872 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | 6.88 | 16.87 | 860.00 | 313.41 | 0.0000 | 0.135 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | 4.43 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | 6.88 | 16.87 | 860.02 | 313.42 | 0.0000 | 0.135 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | 4.43 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | 0.79 | 1.95 | 99.34 | 36.20 | 0.0156 | 0.016 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | 0.79 | 1.95 | 99.34 | 36.20 | 0.1563 | 0.156 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | 0.79 | 1.95 | 99.34 | 36.20 | 0.0156 | 0.016 |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | 17.20 | 42.18 | 1911.37 | 783.68 | 0.3384 | 0.338 |
Total Facility | 1010.73 | 2493.19 | 126016.35 | 46320.38 | 1.7261 | 158.471 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
BASEMENT | 23373277.62 | 0.00 | 23373277.62 | 0.00 | 23373277.62 | 37848132.68 | 3350.22 | 5409.78 | 0.00 | 643.85 |
CORE_BOTTOM | 36415928.59 | 0.00 | 36415928.59 | 0.00 | 36415928.59 | 33990283.35 | 2278.13 | 7.14 | 6474.73 | 1195.50 |
CORE_MID | 0.31E+09 | 0.00 | 0.31E+09 | 0.00 | 0.31E+09 | 0.34E+09 | 3156.96 | 1.92 | 5601.12 | 532.18 |
CORE_TOP | 30875374.01 | 0.00 | 30875374.01 | 0.00 | 30875374.01 | 33990283.35 | 3195.68 | 5.82 | 5558.50 | 507.41 |
PERIMETER_BOT_ZN_3 | 5383844.11 | 0.00 | 5383844.11 | 419809.91 | 5803654.02 | 4267819.30 | 2413.20 | 18.01 | 6328.80 | 1195.50 |
PERIMETER_BOT_ZN_2 | 4569298.95 | 0.00 | 4569298.95 | 279873.08 | 4849172.03 | 2750345.05 | 2278.83 | 0.21 | 6480.96 | 1195.50 |
PERIMETER_BOT_ZN_1 | 6612903.81 | 0.00 | 6612903.81 | 419809.91 | 7032713.72 | 4267912.63 | 2282.08 | 2.40 | 6475.52 | 1195.50 |
PERIMETER_BOT_ZN_4 | 6336696.92 | 0.00 | 6336696.92 | 279873.08 | 6616570.01 | 2750345.05 | 2268.23 | 0.00 | 6491.77 | 1195.50 |
PERIMETER_MID_ZN_3 | 47590834.79 | 0.00 | 47590834.79 | 984550.17 | 48575384.95 | 42678193.03 | 3208.03 | 18.58 | 5533.39 | 532.18 |
PERIMETER_MID_ZN_2 | 44533342.83 | 0.00 | 44533342.83 | 656366.33 | 45189709.16 | 27503450.52 | 3156.60 | 0.17 | 5603.22 | 1441.18 |
PERIMETER_MID_ZN_1 | 62723349.70 | 0.00 | 62723349.70 | 984550.17 | 63707899.87 | 42679126.28 | 3156.74 | 0.13 | 5603.13 | 532.18 |
PERIMETER_MID_ZN_4 | 47492185.41 | 0.00 | 47492185.41 | 656366.33 | 48148551.74 | 27503450.52 | 3150.99 | 0.13 | 5608.88 | 532.18 |
PERIMETER_TOP_ZN_3 | 4741175.66 | 0.00 | 4741175.66 | 1222397.02 | 5963572.69 | 4267819.30 | 3209.89 | 10.66 | 5539.45 | 507.41 |
PERIMETER_TOP_ZN_2 | 4427308.74 | 0.00 | 4427308.74 | 814930.79 | 5242239.53 | 2750345.05 | 3185.99 | 0.93 | 5573.08 | 507.41 |
PERIMETER_TOP_ZN_1 | 6159825.79 | 0.00 | 6159825.79 | 1222397.02 | 7382222.81 | 4267912.63 | 3186.34 | 0.22 | 5573.44 | 507.41 |
PERIMETER_TOP_ZN_4 | 4753435.58 | 0.00 | 4753435.58 | 814930.79 | 5568366.37 | 2750345.05 | 3183.29 | 0.00 | 5576.71 | 507.41 |
DATACENTER_BOT_ZN_6 | 492981.60 | 0.00 | 492981.60 | 0.00 | 492981.60 | 492981.60 | 0.00 | 8760.00 | 0.00 | 2817.00 |
DATACENTER_MID_ZN_6 | 4929815.99 | 0.00 | 4929815.99 | 0.00 | 4929815.99 | 4929815.99 | 0.00 | 8760.00 | 0.00 | 2817.00 |
DATACENTER_TOP_ZN_6 | 492981.60 | 0.00 | 492981.60 | 0.00 | 492981.60 | 492981.60 | 0.00 | 8760.00 | 0.00 | 2817.00 |
DATACENTER_BASEMENT_ZN_6 | 10671554.30 | 0.00 | 10671554.30 | 0.00 | 10671554.30 | 10671554.30 | 0.00 | 8760.00 | 0.00 | 2817.00 |
Total Facility | 0.53E+10 | 0.00 | 0.53E+10 | 38292351.59 | 0.54E+10 | 0.50E+10 | 4075.75 | 8760.00 | 6768.74 | 3726.00 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
BASEMENT | 0.9625 | 0.0000 | 0.9625 | 0.0000 | 0.9625 | 1.2002 | 1177.07 | 4765.93 | 0.00 |
CORE_BOTTOM | 1.3652 | 0.0000 | 1.3652 | 0.0000 | 1.3652 | 1.0778 | 655.81 | 6.85 | 5280.34 |
CORE_MID | 12.9935 | 0.0000 | 12.9935 | 0.0000 | 12.9935 | 10.7782 | 870.80 | 1.82 | 5070.39 |
CORE_TOP | 1.3003 | 0.0000 | 1.3003 | 0.0000 | 1.3003 | 1.0778 | 884.15 | 5.58 | 5053.27 |
PERIMETER_BOT_ZN_3 | 0.2095 | 0.0000 | 0.2095 | 0.0105 | 0.2199 | 0.1353 | 783.77 | 17.67 | 5141.56 |
PERIMETER_BOT_ZN_2 | 0.1757 | 0.0000 | 0.1757 | 0.0070 | 0.1826 | 0.0872 | 652.19 | 0.11 | 5290.70 |
PERIMETER_BOT_ZN_1 | 0.2666 | 0.0000 | 0.2666 | 0.0105 | 0.2771 | 0.1353 | 653.97 | 2.32 | 5286.71 |
PERIMETER_BOT_ZN_4 | 0.2450 | 0.0000 | 0.2450 | 0.0070 | 0.2520 | 0.0872 | 646.70 | 0.00 | 5296.30 |
PERIMETER_MID_ZN_3 | 2.0349 | 0.0000 | 2.0349 | 0.0246 | 2.0595 | 1.3533 | 918.83 | 18.46 | 5005.72 |
PERIMETER_MID_ZN_2 | 1.8196 | 0.0000 | 1.8196 | 0.0173 | 1.8369 | 0.8721 | 869.54 | 0.04 | 4164.42 |
PERIMETER_MID_ZN_1 | 2.7384 | 0.0000 | 2.7384 | 0.0246 | 2.7630 | 1.3533 | 869.59 | 0.10 | 5073.31 |
PERIMETER_MID_ZN_4 | 2.0145 | 0.0000 | 2.0145 | 0.0164 | 2.0309 | 0.8721 | 866.04 | 0.07 | 5076.89 |
PERIMETER_TOP_ZN_3 | 0.2034 | 0.0000 | 0.2034 | 0.0306 | 0.2340 | 0.1353 | 897.77 | 10.60 | 5034.63 |
PERIMETER_TOP_ZN_2 | 0.1900 | 0.0000 | 0.1900 | 0.0204 | 0.2104 | 0.0872 | 875.40 | 0.69 | 5066.91 |
PERIMETER_TOP_ZN_1 | 0.2694 | 0.0000 | 0.2694 | 0.0306 | 0.3000 | 0.1353 | 875.52 | 0.17 | 5067.31 |
PERIMETER_TOP_ZN_4 | 0.2019 | 0.0000 | 0.2019 | 0.0204 | 0.2223 | 0.0872 | 873.70 | 0.00 | 5069.30 |
DATACENTER_BOT_ZN_6 | 0.0156 | 0.0000 | 0.0156 | 0.0000 | 0.0156 | 0.0156 | 0.00 | 5943.00 | 0.00 |
DATACENTER_MID_ZN_6 | 0.1563 | 0.0000 | 0.1563 | 0.0000 | 0.1563 | 0.1563 | 0.00 | 5943.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 0.0156 | 0.0000 | 0.0156 | 0.0000 | 0.0156 | 0.0156 | 0.00 | 5943.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.3384 | 0.0000 | 0.3384 | 0.0000 | 0.3384 | 0.3384 | 0.00 | 5943.00 | 0.00 |
Total Facility | 223.3311 | 0.0000 | 223.3311 | 0.9663 | 224.2974 | 158.4706 | 1442.46 | 5943.00 | 5424.31 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
VAV_BOT WITH REHEAT | 85809262.53 | 0.00 | 85809262.53 | 48026705.38 | 2268.20 | 0.00 | 6491.80 | 1195.50 |
VAV_MID WITH REHEAT | 0.74E+09 | 0.00 | 0.74E+09 | 0.48E+09 | 3150.74 | 0.00 | 5609.26 | 532.18 |
VAV_TOP WITH REHEAT | 73713598.01 | 0.00 | 73713598.01 | 48026705.38 | 3183.29 | 0.00 | 5576.71 | 507.41 |
CAV_BAS | 33811338.05 | 0.00 | 33811338.05 | 37848132.68 | 3350.22 | 0.00 | 5409.78 | 643.85 |
AIRLOOP DATACENTER BASEMENT | 15437267.12 | 0.00 | 15437267.12 | 10671554.30 | 0.00 | 0.00 | 8760.00 | 2817.00 |
AIRLOOP DATACENTER BOT | 713137.79 | 0.00 | 713137.79 | 492981.60 | 0.00 | 0.00 | 8760.00 | 2817.00 |
AIRLOOP DATACENTER MID | 7131377.88 | 0.00 | 7131377.88 | 4929815.99 | 0.00 | 0.00 | 8760.00 | 2817.00 |
AIRLOOP DATACENTER TOP | 713137.79 | 0.00 | 713137.79 | 492981.60 | 0.00 | 0.00 | 8760.00 | 2817.00 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
VAV_BOT WITH REHEAT | 3.2722 | 0.0000 | 3.2722 | 1.5229 | 646.70 | 0.00 | 5296.30 |
VAV_MID WITH REHEAT | 31.3672 | 0.0000 | 31.3672 | 15.2292 | 865.92 | 0.00 | 5077.08 |
VAV_TOP WITH REHEAT | 3.1319 | 0.0000 | 3.1319 | 1.5229 | 873.70 | 0.00 | 5069.30 |
CAV_BAS | 1.3923 | 0.0000 | 1.3923 | 1.2002 | 1177.07 | 0.00 | 4765.93 |
AIRLOOP DATACENTER BASEMENT | 0.4895 | 0.0000 | 0.4895 | 0.3384 | 0.00 | 0.00 | 5943.00 |
AIRLOOP DATACENTER BOT | 0.0226 | 0.0000 | 0.0226 | 0.0156 | 0.00 | 0.00 | 5943.00 |
AIRLOOP DATACENTER MID | 0.2261 | 0.0000 | 0.2261 | 0.1563 | 0.00 | 0.00 | 5943.00 |
AIRLOOP DATACENTER TOP | 0.0226 | 0.0000 | 0.0226 | 0.0156 | 0.00 | 0.00 | 5943.00 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
VAV_BOT WITH REHEAT | 0.00 | 6491.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
VAV_MID WITH REHEAT | 0.00 | 5609.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
VAV_TOP WITH REHEAT | 0.00 | 5576.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CAV_BAS | 0.00 | 5409.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER BASEMENT | 0.00 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER BOT | 0.00 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER MID | 0.00 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER TOP | 0.00 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
VAV_BOT WITH REHEAT | 0.0000 | 3.6719 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
VAV_MID WITH REHEAT | 0.0000 | 36.7176 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
VAV_TOP WITH REHEAT | 0.0000 | 3.6719 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
CAV_BAS | 0.0000 | 1.7365 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
AIRLOOP DATACENTER BASEMENT | 0.0000 | 0.4895 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
AIRLOOP DATACENTER BOT | 0.0000 | 0.0226 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
AIRLOOP DATACENTER MID | 0.0000 | 0.2261 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
AIRLOOP DATACENTER TOP | 0.0000 | 0.0226 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 08:43:45
Surfaces by ClassTotal | Outdoors | |
Wall | 98 | 30 |
Floor | 41 | 0 |
Roof | 30 | 1 |
Internal Mass | 16 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 24 | 24 |
Door | 12 | 12 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 8 |
Conditioned Zones | 23 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 3 |
Count | |
IDF Objects | 1404 |
Defaulted Fields | 1182 |
Fields with Defaults | 3915 |
Autosized Fields | 338 |
Autosizable Fields | 414 |
Autocalculated Fields | 226 |
Autocalculatable Fields | 473 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 08:43:45
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 33818.50 | 377399.06 | 22-JAN-05:00 | 1989371.34 | 23-AUG-15:10 |
Electricity:Building | 18598.65 | 225715.65 | 29-MAY-17:10 | 1164206.62 | 15-DEC-16:40 |
Electricity:Zone:BASEMENT | 687.24 | 14732.47 | 01-JAN-00:10 | 36407.88 | 02-JAN-08:10 |
Electricity:SpaceType:GENERAL | 18598.65 | 225715.65 | 29-MAY-17:10 | 1164206.62 | 15-DEC-16:40 |
InteriorLights:Electricity | 3922.25 | 18459.50 | 01-JAN-09:50 | 385834.94 | 27-SEP-07:10 |
InteriorLights:Electricity:Zone:BASEMENT | 262.84 | 1274.92 | 01-JAN-00:10 | 22950.34 | 02-JAN-08:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 3922.25 | 18459.50 | 01-JAN-09:50 | 385834.94 | 27-SEP-07:10 |
LightsWired:InteriorLights:Electricity | 3922.25 | 18459.50 | 01-JAN-09:50 | 385834.94 | 27-SEP-07:10 |
LightsWired:InteriorLights:Electricity:Zone:BASEMENT | 262.84 | 1274.92 | 01-JAN-00:10 | 22950.34 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 3922.25 | 18459.50 | 01-JAN-09:50 | 385834.94 | 27-SEP-07:10 |
Electricity:Zone:CORE_BOTTOM | 525.67 | 5598.20 | 01-JAN-00:10 | 37817.64 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_BOTTOM | 236.05 | 1144.97 | 01-JAN-00:10 | 20611.01 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_BOTTOM | 236.05 | 1144.97 | 01-JAN-00:10 | 20611.01 | 02-JAN-08:10 |
Electricity:Zone:CORE_MID | 5256.66 | 55981.88 | 01-JAN-00:10 | 378175.77 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_MID | 2360.53 | 11449.71 | 01-JAN-00:10 | 206110.14 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_MID | 2360.53 | 11449.71 | 01-JAN-00:10 | 206110.14 | 02-JAN-08:10 |
Electricity:Zone:CORE_TOP | 525.67 | 5598.19 | 01-JAN-00:10 | 37817.58 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_TOP | 236.05 | 1144.97 | 01-JAN-00:10 | 20611.01 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_TOP | 236.05 | 1144.97 | 01-JAN-00:10 | 20611.01 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_3 | 53.57 | 627.57 | 02-APR-17:10 | 4748.47 | 27-SEP-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 17.21 | 68.40 | 01-JAN-09:50 | 2587.92 | 27-SEP-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 17.21 | 68.40 | 01-JAN-09:50 | 2587.92 | 27-SEP-07:10 |
Electricity:Zone:PERIMETER_BOT_ZN_2 | 34.46 | 404.43 | 29-MAY-17:10 | 3060.10 | 27-SEP-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 11.02 | 44.08 | 01-JAN-07:40 | 1667.75 | 27-SEP-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 11.02 | 44.08 | 01-JAN-07:40 | 1667.75 | 27-SEP-07:10 |
Electricity:Zone:PERIMETER_BOT_ZN_1 | 53.32 | 627.58 | 19-MAR-17:10 | 4748.56 | 27-SEP-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 16.96 | 68.40 | 01-JAN-07:40 | 2587.98 | 27-SEP-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 16.96 | 68.40 | 01-JAN-07:40 | 2587.98 | 27-SEP-07:10 |
Electricity:Zone:PERIMETER_BOT_ZN_4 | 34.44 | 404.43 | 12-MAR-17:10 | 3060.09 | 15-JUN-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 11.01 | 44.08 | 01-JAN-09:40 | 1667.75 | 15-JUN-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 11.01 | 44.08 | 01-JAN-09:40 | 1667.75 | 15-JUN-07:10 |
Electricity:Zone:PERIMETER_MID_ZN_3 | 535.29 | 6275.73 | 02-APR-17:10 | 47484.70 | 27-SEP-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 171.63 | 684.02 | 01-JAN-09:40 | 25879.19 | 27-SEP-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 171.63 | 684.02 | 01-JAN-09:40 | 25879.19 | 27-SEP-07:10 |
Electricity:Zone:PERIMETER_MID_ZN_2 | 344.42 | 4044.32 | 29-MAY-17:10 | 30600.95 | 27-SEP-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 110.06 | 440.81 | 01-JAN-07:40 | 16677.53 | 27-SEP-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 110.06 | 440.81 | 01-JAN-07:40 | 16677.53 | 27-SEP-07:10 |
Electricity:Zone:PERIMETER_MID_ZN_1 | 532.97 | 6275.83 | 12-MAR-17:10 | 47485.60 | 27-SEP-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 169.32 | 684.04 | 01-JAN-07:40 | 25879.75 | 27-SEP-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 169.32 | 684.04 | 01-JAN-07:40 | 25879.75 | 27-SEP-07:10 |
Electricity:Zone:PERIMETER_MID_ZN_4 | 344.19 | 4044.30 | 12-MAR-17:10 | 30600.86 | 15-JUN-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 109.84 | 440.81 | 01-JAN-09:30 | 16677.53 | 15-JUN-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 109.84 | 440.81 | 01-JAN-09:30 | 16677.53 | 15-JUN-07:10 |
Electricity:Zone:PERIMETER_TOP_ZN_3 | 53.53 | 627.57 | 02-APR-17:10 | 4748.47 | 27-SEP-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 17.16 | 68.40 | 01-JAN-09:40 | 2587.92 | 27-SEP-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 17.16 | 68.40 | 01-JAN-09:40 | 2587.92 | 27-SEP-07:10 |
Electricity:Zone:PERIMETER_TOP_ZN_2 | 34.44 | 404.43 | 29-MAY-17:10 | 3060.10 | 27-SEP-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 11.01 | 44.08 | 01-JAN-07:40 | 1667.75 | 27-SEP-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 11.01 | 44.08 | 01-JAN-07:40 | 1667.75 | 27-SEP-07:10 |
Electricity:Zone:PERIMETER_TOP_ZN_1 | 53.30 | 627.58 | 12-MAR-17:10 | 4748.56 | 27-SEP-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 16.93 | 68.40 | 01-JAN-07:40 | 2587.98 | 27-SEP-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 16.93 | 68.40 | 01-JAN-07:40 | 2587.98 | 27-SEP-07:10 |
Electricity:Zone:PERIMETER_TOP_ZN_4 | 34.42 | 404.43 | 12-MAR-17:10 | 3060.09 | 15-JUN-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 10.98 | 44.08 | 01-JAN-09:30 | 1667.75 | 15-JUN-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 10.98 | 44.08 | 01-JAN-09:30 | 1667.75 | 15-JUN-07:10 |
Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 7568.97 | 95267.60 | 01-JAN-00:10 | 386103.53 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 74.11 | 359.47 | 01-JAN-00:10 | 6471.01 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 74.11 | 359.47 | 01-JAN-00:10 | 6471.01 | 02-JAN-08:10 |
Electricity:Zone:DATACENTER_BOT_ZN_6 | 160.51 | 1980.76 | 01-JAN-00:10 | 8373.14 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_BOT_ZN_6 | 6.63 | 32.15 | 01-JAN-00:10 | 578.72 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_BOT_ZN_6 | 6.63 | 32.15 | 01-JAN-00:10 | 578.72 | 02-JAN-08:10 |
Electricity:Zone:DATACENTER_MID_ZN_6 | 1605.09 | 19807.58 | 01-JAN-00:10 | 83731.41 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_MID_ZN_6 | 66.28 | 321.53 | 01-JAN-00:10 | 5787.18 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_MID_ZN_6 | 66.28 | 321.53 | 01-JAN-00:10 | 5787.18 | 02-JAN-08:10 |
Electricity:Zone:DATACENTER_TOP_ZN_6 | 160.51 | 1980.76 | 01-JAN-00:10 | 8373.14 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_TOP_ZN_6 | 6.63 | 32.15 | 01-JAN-00:10 | 578.72 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_TOP_ZN_6 | 6.63 | 32.15 | 01-JAN-00:10 | 578.72 | 02-JAN-08:10 |
InteriorEquipment:Electricity | 14676.40 | 207256.16 | 01-JAN-00:10 | 778371.69 | 03-APR-07:10 |
InteriorEquipment:Electricity:Zone:BASEMENT | 424.40 | 13457.54 | 01-JAN-00:10 | 13457.54 | 01-JAN-00:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 14676.40 | 207256.16 | 01-JAN-00:10 | 778371.69 | 03-APR-07:10 |
MiscPlug:InteriorEquipment:Electricity | 5334.97 | 88964.76 | 01-JAN-00:10 | 305206.10 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:BASEMENT | 424.40 | 13457.54 | 01-JAN-00:10 | 13457.54 | 01-JAN-00:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 5334.97 | 88964.76 | 01-JAN-00:10 | 305206.10 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 289.61 | 4453.23 | 01-JAN-00:10 | 17206.63 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 289.61 | 4453.23 | 01-JAN-00:10 | 17206.63 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_MID | 2896.13 | 44532.17 | 01-JAN-00:10 | 172065.63 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_MID | 2896.13 | 44532.17 | 01-JAN-00:10 | 172065.63 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_TOP | 289.61 | 4453.22 | 01-JAN-00:10 | 17206.56 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_TOP | 289.61 | 4453.22 | 01-JAN-00:10 | 17206.56 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 36.37 | 559.17 | 01-JAN-00:10 | 2160.55 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 36.37 | 559.17 | 01-JAN-00:10 | 2160.55 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.34 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.34 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 36.37 | 559.18 | 01-JAN-00:10 | 2160.58 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 36.37 | 559.18 | 01-JAN-00:10 | 2160.58 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.33 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.33 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 363.65 | 5591.71 | 01-JAN-00:10 | 21605.52 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 363.65 | 5591.71 | 01-JAN-00:10 | 21605.52 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 234.35 | 3603.51 | 01-JAN-00:10 | 13923.42 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 234.35 | 3603.51 | 01-JAN-00:10 | 13923.42 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 363.66 | 5591.79 | 01-JAN-00:10 | 21605.85 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 363.66 | 5591.79 | 01-JAN-00:10 | 21605.85 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 234.35 | 3603.49 | 01-JAN-00:10 | 13923.33 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 234.35 | 3603.49 | 01-JAN-00:10 | 13923.33 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 36.37 | 559.17 | 01-JAN-00:10 | 2160.55 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 36.37 | 559.17 | 01-JAN-00:10 | 2160.55 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.34 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.34 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 36.37 | 559.18 | 01-JAN-00:10 | 2160.58 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 36.37 | 559.18 | 01-JAN-00:10 | 2160.58 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.33 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.33 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 7494.86 | 94908.13 | 01-JAN-00:10 | 379632.52 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity | 9341.42 | 118291.40 | 01-JAN-00:10 | 473165.59 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 7494.86 | 94908.13 | 01-JAN-00:10 | 379632.52 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:SpaceType:GENERAL | 9341.42 | 118291.40 | 01-JAN-00:10 | 473165.59 | 31-MAR-23:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_BOT_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_BOT_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_MID_ZN_6 | 1538.81 | 19486.06 | 01-JAN-00:10 | 77944.22 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_MID_ZN_6 | 1538.81 | 19486.06 | 01-JAN-00:10 | 77944.22 | 31-MAR-23:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_TOP_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_TOP_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
Electricity:Plant | 6974.13 | 9556.75 | 25-JAN-05:50 | 505361.23 | 23-JUN-14:00 |
HeatRejection:Electricity | 2294.23 | 6093.49 | 25-JAN-07:00 | 98044.59 | 02-JAN-09:20 |
General:HeatRejection:Electricity | 2294.23 | 6093.49 | 25-JAN-07:00 | 98044.59 | 02-JAN-09:20 |
Electricity:HVAC | 5694.55 | 75729.65 | 22-JAN-06:00 | 341570.16 | 31-AUG-15:20 |
ExteriorEquipment:Electricity | 1934.78 | 28603.11 | 01-JAN-00:10 | 118535.44 | 27-SEP-07:20 |
Transformer:ExteriorEquipment:Electricity | 80.17 | 1421.04 | 01-JAN-00:10 | 5057.48 | 15-DEC-16:50 |
ElectricityPurchased:Facility | 33818.50 | 377399.06 | 22-JAN-05:00 | 1989371.34 | 23-AUG-15:10 |
ElectricityPurchased:Plant | 33818.50 | 377399.06 | 22-JAN-05:00 | 1989371.34 | 23-AUG-15:10 |
Cogeneration:ElectricityPurchased | 33818.50 | 377399.06 | 22-JAN-05:00 | 1989371.34 | 23-AUG-15:10 |
General:Cogeneration:ElectricityPurchased | 33818.50 | 377399.06 | 22-JAN-05:00 | 1989371.34 | 23-AUG-15:10 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 33818.50 | 377399.06 | 22-JAN-05:00 | 1989371.34 | 23-AUG-15:10 |
ElectricityNet:Plant | 33818.50 | 377399.06 | 22-JAN-05:00 | 1989371.34 | 23-AUG-15:10 |
Cogeneration:ElectricityNet | 33818.50 | 377399.06 | 22-JAN-05:00 | 1989371.34 | 23-AUG-15:10 |
General:Cogeneration:ElectricityNet | 33818.50 | 377399.06 | 22-JAN-05:00 | 1989371.34 | 23-AUG-15:10 |
Fans:Electricity | 2279.76 | 41718.95 | 01-JAN-00:10 | 148849.04 | 31-AUG-15:20 |
General:Fans:Electricity | 2279.76 | 41718.95 | 01-JAN-00:10 | 148849.04 | 31-AUG-15:20 |
ExteriorLights:Electricity | 696.56 | 0.00 | 01-JAN-07:20 | 57580.60 | 01-JAN-06:10 |
General:ExteriorLights:Electricity | 696.56 | 0.00 | 01-JAN-07:20 | 57580.60 | 01-JAN-06:10 |
ElevatorLift:ExteriorEquipment:Electricity | 1848.78 | 27144.47 | 01-JAN-00:10 | 113101.96 | 01-JAN-07:10 |
ElevatorLightsFan:ExteriorEquipment:Electricity | 5.83 | 37.60 | 01-JAN-00:10 | 376.00 | 01-JAN-07:10 |
HeatRecovery:Electricity | 119.08 | 0.00 | 01-JAN-00:10 | 5613.48 | 01-JAN-08:40 |
General:HeatRecovery:Electricity | 119.08 | 0.00 | 01-JAN-00:10 | 5613.48 | 01-JAN-08:40 |
Cooling:Electricity | 6915.41 | 32568.33 | 22-JAN-07:20 | 495044.09 | 15-AUG-12:10 |
General:Cooling:Electricity | 6915.41 | 32568.33 | 22-JAN-07:20 | 495044.09 | 15-AUG-12:10 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Humidifier:Electricity | 1.14 | 0.00 | 01-JAN-00:10 | 4077.20 | 04-FEB-06:00 |
General:Humidifier:Electricity | 1.14 | 0.00 | 01-JAN-00:10 | 4077.20 | 04-FEB-06:00 |
Boiler Parasitic:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Pumps:Electricity | 978.88 | 3432.39 | 03-JAN-05:50 | 69624.76 | 13-OCT-15:50 |
General:Pumps:Electricity | 978.88 | 3432.39 | 03-JAN-05:50 | 69624.76 | 13-OCT-15:50 |
WIRED_LTG_ELECTRICITY | 110.21 | 0.00 | 01-JAN-00:10 | 10841.96 | 27-SEP-07:20 |
WIRED_INT_EQUIP | 5334.97 | 88964.76 | 31-MAR-23:10 | 305206.10 | 03-APR-07:10 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 660.92 | 8146.58 | 09-APR-16:00 | 413137.05 | 04-FEB-06:10 |
NaturalGas:Plant | 660.92 | 8146.58 | 09-APR-16:00 | 413137.05 | 04-FEB-06:10 |
Heating:NaturalGas | 20.08 | 0.00 | 01-JAN-00:10 | 404990.47 | 04-FEB-06:10 |
Boiler:Heating:NaturalGas | 20.08 | 0.00 | 01-JAN-00:10 | 404990.47 | 04-FEB-06:10 |
WaterSystems:NaturalGas | 640.83 | 8146.58 | 04-FEB-05:20 | 70632.11 | 23-JAN-12:50 |
Water Heater:WaterSystems:NaturalGas | 640.83 | 8146.58 | 04-FEB-05:20 | 70632.11 | 23-JAN-12:50 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
PlantLoopCoolingDemand:Facility | 37176.94 | 161675.26 | 25-JAN-05:50 | 2672256.70 | 23-AUG-15:00 |
PlantLoopCoolingDemand:HVAC | 37176.94 | 161675.26 | 25-JAN-05:50 | 2672256.70 | 23-AUG-15:00 |
CoolingCoils:PlantLoopCoolingDemand | 37176.94 | 161675.26 | 25-JAN-05:50 | 2672256.70 | 23-AUG-15:00 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 20812.18 | 0.00 | 01-JAN-00:10 | 0.00 | 17-APR-15:10 |
Water:HVAC | 0.43 | 0.00 | 01-JAN-00:10 | 0.00 | 04-FEB-06:00 |
Humidifier:Water | 0.43 | 0.00 | 01-JAN-00:10 | 0.00 | 04-FEB-06:00 |
General:Humidifier:Water | 0.43 | 0.00 | 01-JAN-00:10 | 0.00 | 04-FEB-06:00 |
MainsWater:Facility | 20812.18 | 0.00 | 01-JAN-00:10 | 0.00 | 17-APR-15:10 |
MainsWater:HVAC | 0.43 | 0.00 | 01-JAN-00:10 | 0.00 | 04-FEB-06:00 |
Humidifier:MainsWater | 0.43 | 0.00 | 01-JAN-00:10 | 0.00 | 04-FEB-06:00 |
General:Humidifier:MainsWater | 0.43 | 0.00 | 01-JAN-00:10 | 0.00 | 04-FEB-06:00 |
Water:Plant | 20811.76 | 0.00 | 01-JAN-00:10 | 0.00 | 17-APR-15:10 |
WaterSystems:Water | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterUse:WaterSystems:Water | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
MainsWater:Plant | 20811.76 | 0.00 | 01-JAN-00:10 | 0.00 | 17-APR-15:10 |
WaterSystems:MainsWater | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterUse:WaterSystems:MainsWater | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water Heater:WaterSystems:Water | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:MainsWater | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
HeatRejection:Water | 18531.59 | 0.00 | 01-JAN-00:10 | 0.00 | 17-APR-15:10 |
General:HeatRejection:Water | 18531.59 | 0.00 | 01-JAN-00:10 | 0.00 | 17-APR-15:10 |
HeatRejection:MainsWater | 18531.59 | 0.00 | 01-JAN-00:10 | 0.00 | 17-APR-15:10 |
General:HeatRejection:MainsWater | 18531.59 | 0.00 | 01-JAN-00:10 | 0.00 | 17-APR-15:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 143507.63 | 227193.65 | 25-JAN-05:50 | 11209242.41 | 21-AUG-16:00 |
EnergyTransfer:Building | 24287.63 | 97224.06 | 22-JAN-07:50 | 1729464.06 | 31-AUG-15:20 |
EnergyTransfer:Zone:BASEMENT | 809.27 | 0.00 | 01-JAN-00:10 | 75552.34 | 13-NOV-06:10 |
Heating:EnergyTransfer | 11.79 | 0.00 | 01-JAN-00:10 | 162421.63 | 04-FEB-06:10 |
Heating:EnergyTransfer:Zone:BASEMENT | 4.32 | 0.00 | 01-JAN-00:10 | 23466.30 | 29-JUL-16:10 |
General:Heating:EnergyTransfer | 11.79 | 0.00 | 01-JAN-00:10 | 162421.63 | 04-FEB-06:10 |
General:Heating:EnergyTransfer:Zone:BASEMENT | 4.32 | 0.00 | 01-JAN-00:10 | 23466.30 | 29-JUL-16:10 |
Cooling:EnergyTransfer | 24275.85 | 97216.92 | 22-JAN-07:40 | 1729464.06 | 31-AUG-15:20 |
Cooling:EnergyTransfer:Zone:BASEMENT | 804.95 | 0.00 | 01-JAN-00:10 | 75552.34 | 13-NOV-06:10 |
General:Cooling:EnergyTransfer | 24275.85 | 97216.92 | 22-JAN-07:40 | 1729464.06 | 31-AUG-15:20 |
General:Cooling:EnergyTransfer:Zone:BASEMENT | 804.95 | 0.00 | 01-JAN-00:10 | 75552.34 | 13-NOV-06:10 |
EnergyTransfer:Zone:CORE_BOTTOM | 845.71 | 0.00 | 01-JAN-00:10 | 57304.82 | 21-AUG-13:10 |
Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 845.71 | 0.00 | 01-JAN-00:10 | 57304.82 | 21-AUG-13:10 |
General:Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 845.71 | 0.00 | 01-JAN-00:10 | 57304.82 | 21-AUG-13:10 |
EnergyTransfer:Zone:CORE_MID | 6472.66 | 0.00 | 01-JAN-00:10 | 476391.97 | 20-OCT-05:10 |
Heating:EnergyTransfer:Zone:CORE_MID | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:CORE_MID | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:CORE_MID | 6472.66 | 0.00 | 01-JAN-00:10 | 476391.97 | 20-OCT-05:10 |
General:Cooling:EnergyTransfer:Zone:CORE_MID | 6472.66 | 0.00 | 01-JAN-00:10 | 476391.97 | 20-OCT-05:10 |
EnergyTransfer:Zone:CORE_TOP | 667.39 | 0.00 | 01-JAN-00:10 | 55401.22 | 28-JUL-16:00 |
Heating:EnergyTransfer:Zone:CORE_TOP | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:CORE_TOP | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:CORE_TOP | 667.39 | 0.00 | 01-JAN-00:10 | 55401.22 | 28-JUL-16:00 |
General:Cooling:EnergyTransfer:Zone:CORE_TOP | 667.39 | 0.00 | 01-JAN-00:10 | 55401.22 | 28-JUL-16:00 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 129.67 | 0.00 | 01-JAN-00:10 | 12188.48 | 31-JUL-14:00 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 129.67 | 0.00 | 01-JAN-00:10 | 12188.48 | 31-JUL-14:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 129.67 | 0.00 | 01-JAN-00:10 | 12188.48 | 31-JUL-14:00 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 108.30 | 0.00 | 01-JAN-00:10 | 12326.60 | 25-JUL-09:30 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 01-JAN-00:10 | 134.02 | 04-FEB-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 01-JAN-00:10 | 134.02 | 04-FEB-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 108.30 | 0.00 | 01-JAN-00:10 | 12326.60 | 25-JUL-09:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 108.30 | 0.00 | 01-JAN-00:10 | 12326.60 | 25-JUL-09:30 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 165.62 | 0.00 | 01-JAN-00:10 | 17330.15 | 04-DEC-14:30 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 165.62 | 0.00 | 01-JAN-00:10 | 17330.15 | 04-DEC-14:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 165.62 | 0.00 | 01-JAN-00:10 | 17330.15 | 04-DEC-14:30 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 152.26 | 0.00 | 01-JAN-00:10 | 16774.12 | 16-AUG-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 152.26 | 0.00 | 01-JAN-00:10 | 16774.12 | 16-AUG-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 152.26 | 0.00 | 01-JAN-00:10 | 16774.12 | 16-AUG-16:00 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 1036.00 | 0.00 | 01-JAN-00:10 | 116104.13 | 01-JUN-14:40 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 0.71 | 0.00 | 01-JAN-00:10 | 46537.28 | 04-FEB-06:00 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 0.71 | 0.00 | 01-JAN-00:10 | 46537.28 | 04-FEB-06:00 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 1035.29 | 0.00 | 01-JAN-00:10 | 116104.13 | 01-JUN-14:40 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 1035.29 | 0.00 | 01-JAN-00:10 | 116104.13 | 01-JUN-14:40 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 967.32 | 0.00 | 01-JAN-00:10 | 124967.64 | 25-JUL-09:00 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 0.21 | 0.00 | 01-JAN-00:10 | 30882.06 | 04-FEB-06:00 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 0.21 | 0.00 | 01-JAN-00:10 | 30882.06 | 04-FEB-06:00 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 967.11 | 0.00 | 01-JAN-00:10 | 124967.64 | 25-JUL-09:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 967.11 | 0.00 | 01-JAN-00:10 | 124967.64 | 25-JUL-09:00 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 1428.49 | 0.00 | 01-JAN-00:10 | 170565.24 | 03-DEC-14:00 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 0.09 | 0.00 | 01-JAN-00:10 | 31658.30 | 04-FEB-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 0.09 | 0.00 | 01-JAN-00:10 | 31658.30 | 04-FEB-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 1428.40 | 0.00 | 01-JAN-00:10 | 170565.24 | 03-DEC-14:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 1428.40 | 0.00 | 01-JAN-00:10 | 170565.24 | 03-DEC-14:00 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 1019.47 | 0.00 | 01-JAN-00:10 | 142020.25 | 17-MAY-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 0.15 | 0.00 | 01-JAN-00:10 | 24940.18 | 04-FEB-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 0.15 | 0.00 | 01-JAN-00:10 | 24940.18 | 04-FEB-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 1019.33 | 0.00 | 01-JAN-00:10 | 142020.25 | 17-MAY-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 1019.33 | 0.00 | 01-JAN-00:10 | 142020.25 | 17-MAY-16:00 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 107.27 | 0.00 | 01-JAN-00:10 | 12683.56 | 27-JUL-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 0.44 | 0.00 | 01-JAN-00:10 | 10578.14 | 04-FEB-05:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 0.44 | 0.00 | 01-JAN-00:10 | 10578.14 | 04-FEB-05:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 106.82 | 0.00 | 01-JAN-00:10 | 12683.56 | 27-JUL-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 106.82 | 0.00 | 01-JAN-00:10 | 12683.56 | 27-JUL-16:00 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 99.58 | 0.00 | 01-JAN-00:10 | 13192.77 | 25-JUL-09:30 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 0.16 | 0.00 | 01-JAN-00:10 | 6659.04 | 04-FEB-05:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 0.16 | 0.00 | 01-JAN-00:10 | 6659.04 | 04-FEB-05:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 99.42 | 0.00 | 01-JAN-00:10 | 13192.77 | 25-JUL-09:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 99.42 | 0.00 | 01-JAN-00:10 | 13192.77 | 25-JUL-09:30 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 145.24 | 0.00 | 01-JAN-00:10 | 18314.98 | 07-NOV-14:20 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 0.11 | 0.00 | 01-JAN-00:10 | 7278.96 | 04-FEB-05:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 0.11 | 0.00 | 01-JAN-00:10 | 7278.96 | 04-FEB-05:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 145.13 | 0.00 | 01-JAN-00:10 | 18314.98 | 07-NOV-14:20 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 145.13 | 0.00 | 01-JAN-00:10 | 18314.98 | 07-NOV-14:20 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 104.84 | 0.00 | 01-JAN-00:10 | 14943.29 | 17-MAY-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 0.12 | 0.00 | 01-JAN-00:10 | 5437.33 | 04-FEB-05:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 0.12 | 0.00 | 01-JAN-00:10 | 5437.33 | 04-FEB-05:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 104.72 | 0.00 | 01-JAN-00:10 | 14943.29 | 17-MAY-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 104.72 | 0.00 | 01-JAN-00:10 | 14943.29 | 17-MAY-16:00 |
EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 119.93 | 0.00 | 01-JAN-00:10 | 11642.51 | 21-AUG-16:00 |
Heating:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 0.50 | 0.00 | 01-JAN-00:10 | 3452.37 | 05-FEB-11:20 |
General:Heating:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 0.50 | 0.00 | 01-JAN-00:10 | 3452.37 | 05-FEB-11:20 |
Cooling:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 119.44 | 0.00 | 01-JAN-00:10 | 11642.51 | 21-AUG-16:00 |
General:Cooling:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 119.44 | 0.00 | 01-JAN-00:10 | 11642.51 | 21-AUG-16:00 |
EnergyTransfer:Zone:MIDFLOOR_PLENUM | 935.49 | 0.00 | 01-JAN-00:10 | 90492.44 | 28-JUL-16:00 |
Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 2.93 | 0.00 | 01-JAN-00:10 | 21469.67 | 05-FEB-12:30 |
General:Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 2.93 | 0.00 | 01-JAN-00:10 | 21469.67 | 05-FEB-12:30 |
Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 932.56 | 0.00 | 01-JAN-00:10 | 90492.44 | 28-JUL-16:00 |
General:Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 932.56 | 0.00 | 01-JAN-00:10 | 90492.44 | 28-JUL-16:00 |
EnergyTransfer:Zone:TOPFLOOR_PLENUM | 144.41 | 0.00 | 01-JAN-00:10 | 23127.28 | 28-JUL-15:30 |
Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 2.05 | 0.00 | 01-JAN-00:10 | 8454.16 | 04-FEB-06:10 |
General:Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 2.05 | 0.00 | 01-JAN-00:10 | 8454.16 | 04-FEB-06:10 |
Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 142.36 | 0.00 | 01-JAN-00:10 | 23127.28 | 28-JUL-15:30 |
General:Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 142.36 | 0.00 | 01-JAN-00:10 | 23127.28 | 28-JUL-15:30 |
EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 144.58 | 1119.13 | 26-JAN-08:00 | 8056.14 | 06-DEC-17:00 |
Heating:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 144.58 | 1119.13 | 26-JAN-08:00 | 8056.14 | 06-DEC-17:00 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 144.58 | 1119.13 | 26-JAN-08:00 | 8056.14 | 06-DEC-17:00 |
EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 1345.62 | 6409.66 | 26-JAN-08:00 | 76397.96 | 06-DEC-17:00 |
Heating:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 1345.62 | 6409.66 | 26-JAN-08:00 | 76397.96 | 06-DEC-17:00 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 1345.62 | 6409.66 | 26-JAN-08:00 | 76397.96 | 06-DEC-17:00 |
EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 133.35 | 1.57 | 22-JAN-08:00 | 7704.53 | 06-DEC-17:00 |
Heating:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 192.10 | 22-JAN-08:30 |
General:Heating:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 192.10 | 22-JAN-08:30 |
Cooling:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 133.35 | 0.00 | 22-JAN-07:20 | 7704.53 | 06-DEC-17:00 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 133.35 | 0.00 | 22-JAN-07:20 | 7704.53 | 06-DEC-17:00 |
EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 7205.17 | 88941.98 | 22-JAN-06:00 | 370406.01 | 28-AUG-12:20 |
Heating:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 7205.17 | 88941.98 | 22-JAN-06:00 | 370406.01 | 28-AUG-12:20 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 7205.17 | 88941.98 | 22-JAN-06:00 | 370406.01 | 28-AUG-12:20 |
PlantLoopHeatingDemand:Facility | 310.56 | 0.00 | 01-JAN-00:10 | 322467.67 | 04-FEB-06:10 |
PlantLoopHeatingDemand:Plant | 296.73 | 0.00 | 01-JAN-00:10 | 36110.59 | 19-JAN-12:50 |
WaterSystems:PlantLoopHeatingDemand | 296.73 | 0.00 | 01-JAN-00:10 | 36110.59 | 19-JAN-12:50 |
General:WaterSystems:PlantLoopHeatingDemand | 296.73 | 0.00 | 01-JAN-00:10 | 36110.59 | 19-JAN-12:50 |
EnergyTransfer:HVAC | 39907.95 | 128842.77 | 25-JAN-05:50 | 3254044.58 | 21-AUG-16:00 |
HeatingCoils:EnergyTransfer | 13.83 | 0.00 | 01-JAN-00:10 | 318052.85 | 04-FEB-06:10 |
PlantLoopHeatingDemand:HVAC | 13.83 | 0.00 | 01-JAN-00:10 | 318052.85 | 04-FEB-06:10 |
HeatingCoils:PlantLoopHeatingDemand | 13.83 | 0.00 | 01-JAN-00:10 | 318052.85 | 04-FEB-06:10 |
CoolingCoils:EnergyTransfer | 33962.54 | 128842.77 | 25-JAN-05:50 | 2491041.83 | 23-AUG-15:00 |
HeatRecoveryForHeating:EnergyTransfer | 13.48 | 0.00 | 01-JAN-00:10 | 237161.82 | 04-FEB-07:00 |
HeatRecoveryForCooling:EnergyTransfer | 5918.09 | 0.00 | 01-JAN-00:10 | 767781.45 | 21-AUG-16:00 |
EnergyTransfer:Plant | 79312.05 | 0.00 | 01-JAN-00:10 | 7202518.97 | 23-JUN-14:00 |
LoopToLoop:EnergyTransfer | 25215.79 | 0.00 | 01-JAN-00:10 | 2220868.97 | 22-JUN-05:10 |
WaterSystems:EnergyTransfer | 296.73 | 0.00 | 01-JAN-00:10 | 36110.59 | 19-JAN-12:50 |
WaterUse:WaterSystems:EnergyTransfer | 296.73 | 0.00 | 01-JAN-00:10 | 36110.59 | 19-JAN-12:50 |
Boilers:EnergyTransfer | 13.51 | 0.00 | 01-JAN-00:10 | 325809.07 | 04-FEB-06:10 |
Chillers:EnergyTransfer | 25042.50 | 0.00 | 01-JAN-00:10 | 2358594.86 | 23-JUN-14:00 |
HeatRejection:EnergyTransfer | 28743.51 | 0.00 | 01-JAN-00:10 | 2700062.89 | 23-JUN-14:00 |
General:HeatRejection:EnergyTransfer | 28743.51 | 0.00 | 01-JAN-00:10 | 2700062.89 | 23-JUN-14:00 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 08:43:45
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
BASEMENT | 0.000 | 0.000 | 4.316 | -804.952 | 0.000 | 0.000 | 92.650 | 262.844 | 424.397 | 0.000 | 0.000 | 0.000 | 20.744 | 0.000 | 0.000 | 0.000 | 0.000 | -0.008 |
CORE_BOTTOM | 0.000 | 0.000 | 0.000 | -845.710 | 0.000 | 0.000 | 83.500 | 236.053 | 289.614 | 0.000 | 0.000 | 0.000 | 236.543 | 0.000 | 0.000 | 0.000 | 0.000 | -0.001 |
CORE_MID | 0.000 | 0.000 | 0.000 | -6472.643 | 0.000 | 0.000 | 838.254 | 2360.527 | 2896.128 | 0.000 | 0.000 | 0.000 | 377.734 | 0.000 | 0.000 | 0.000 | 0.000 | -0.013 |
CORE_TOP | 0.000 | 0.000 | 0.000 | -667.383 | 0.000 | 0.000 | 84.278 | 236.053 | 289.613 | 0.000 | 0.000 | 0.000 | 57.440 | 0.000 | 0.000 | 0.000 | 0.000 | -0.002 |
PERIMETER_BOT_ZN_3 | 0.000 | 0.000 | 0.000 | -129.665 | 0.000 | 0.000 | 10.516 | 17.208 | 36.365 | 47.833 | 0.000 | 0.657 | 38.412 | 0.000 | -20.304 | 0.000 | -1.022 | 0.000 |
PERIMETER_BOT_ZN_2 | 0.000 | 0.000 | 0.000 | -108.300 | 0.000 | 0.000 | 6.777 | 11.025 | 23.435 | 64.864 | 0.000 | 0.471 | 14.491 | 0.000 | -12.117 | 0.000 | -0.647 | -0.000 |
PERIMETER_BOT_ZN_1 | 0.000 | 0.000 | 0.000 | -165.618 | 0.000 | 0.000 | 10.448 | 16.956 | 36.366 | 100.012 | 0.000 | 0.613 | 22.980 | 0.000 | -20.598 | 0.000 | -1.159 | -0.000 |
PERIMETER_BOT_ZN_4 | 0.000 | 0.000 | 0.000 | -152.260 | 0.000 | 0.000 | 6.757 | 11.007 | 23.435 | 60.627 | 0.000 | 0.390 | 68.112 | 0.000 | -17.178 | 0.000 | -0.891 | 0.000 |
PERIMETER_MID_ZN_3 | 0.000 | 0.000 | 0.713 | -1035.257 | 0.000 | 0.000 | 106.438 | 171.634 | 363.654 | 488.869 | 0.000 | 14.553 | 92.768 | 0.000 | -182.018 | 0.000 | -21.354 | -0.000 |
PERIMETER_MID_ZN_2 | 0.000 | 0.000 | 0.209 | -967.086 | 0.000 | 0.000 | 50.094 | 110.065 | 234.352 | 643.417 | 0.000 | 9.561 | 53.981 | 0.000 | -119.122 | 0.000 | -15.470 | -0.009 |
PERIMETER_MID_ZN_1 | 0.000 | 0.000 | 0.094 | -1428.363 | 0.000 | 0.000 | 104.553 | 169.315 | 363.660 | 995.559 | 0.000 | 13.197 | 10.868 | 0.000 | -201.374 | 0.000 | -27.508 | -0.004 |
PERIMETER_MID_ZN_4 | 0.000 | 0.000 | 0.148 | -1019.296 | 0.000 | 0.000 | 68.678 | 109.838 | 234.351 | 622.053 | 0.000 | 9.124 | 133.358 | 0.000 | -140.875 | 0.000 | -17.379 | -0.009 |
PERIMETER_TOP_ZN_3 | 0.000 | 0.000 | 0.442 | -106.821 | 0.000 | 0.000 | 10.703 | 17.162 | 36.365 | 48.340 | 0.000 | 1.700 | 12.166 | 0.000 | -17.544 | 0.000 | -2.513 | -0.000 |
PERIMETER_TOP_ZN_2 | 0.000 | 0.000 | 0.161 | -99.414 | 0.000 | 0.000 | 6.833 | 11.006 | 23.435 | 63.870 | 0.000 | 1.120 | 6.396 | 0.000 | -11.570 | 0.000 | -1.839 | -0.001 |
PERIMETER_TOP_ZN_1 | 0.000 | 0.000 | 0.114 | -145.126 | 0.000 | 0.000 | 10.511 | 16.931 | 36.366 | 98.872 | 0.000 | 1.552 | 3.600 | 0.000 | -19.541 | 0.000 | -3.278 | -0.002 |
PERIMETER_TOP_ZN_4 | 0.000 | 0.000 | 0.118 | -104.715 | 0.000 | 0.000 | 6.914 | 10.983 | 23.435 | 61.832 | 0.000 | 1.104 | 15.999 | 0.000 | -13.606 | 0.000 | -2.065 | -0.001 |
DATACENTER_BOT_ZN_6 | 0.000 | 0.000 | 0.000 | -144.583 | 0.000 | 0.000 | 0.949 | 6.628 | 153.881 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -16.875 |
DATACENTER_MID_ZN_6 | 0.000 | 0.000 | 0.000 | -1345.617 | 0.000 | 0.000 | 9.495 | 66.280 | 1538.806 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -268.963 |
DATACENTER_TOP_ZN_6 | 0.000 | 0.000 | 0.001 | -133.347 | 0.000 | 0.000 | 0.950 | 6.628 | 153.881 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -28.113 |
DATACENTER_BASEMENT_ZN_6 | 0.000 | 0.000 | 0.000 | -7205.173 | 0.000 | 0.000 | 20.033 | 74.111 | 7494.857 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -383.828 |
GROUNDFLOOR_PLENUM | 0.497 | -119.436 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.033 | 120.361 | 0.000 | 0.000 | 0.000 | -2.455 | -0.000 |
MIDFLOOR_PLENUM | 2.926 | -932.545 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 19.048 | 951.416 | 0.000 | 0.000 | 0.000 | -40.846 | -0.000 |
TOPFLOOR_PLENUM | 2.047 | -142.362 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.656 | 142.907 | 0.000 | 0.000 | 0.000 | -4.248 | -0.000 |
Total Facility | 5.470 | -1194.343 | 6.316 | -23081.327 | 0.000 | 0.000 | 1529.332 | 3922.253 | 14676.396 | 3296.147 | 0.000 | 75.779 | 2380.274 | 0.000 | -775.847 | 0.000 | -142.673 | -697.829 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | 04-FEB-05:11 | 0.00 | 0.00 | 0.00 | -109159.08 | 0.00 | 0.00 | 0.00 | 1274.92 | 13457.54 | 0.00 | 0.00 | 0.00 | 94426.61 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 21-FEB-05:13 | 0.00 | 0.00 | 0.00 | -103174.29 | 0.00 | 0.00 | 0.00 | 2290.20 | 5937.65 | 0.00 | 0.00 | 0.00 | 94946.45 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 20-OCT-04:13 | 0.00 | 0.00 | 0.00 | -914658.93 | 0.00 | 0.00 | 0.00 | 22901.98 | 59376.23 | 0.00 | 0.00 | 0.00 | 832380.72 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 18-APR-04:12 | 0.00 | 0.00 | 0.00 | -88082.82 | 0.00 | 0.00 | 0.00 | 2290.20 | 5937.62 | 0.00 | 0.00 | 0.00 | 79855.00 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 30-JUL-14:22 | 0.00 | 0.00 | 0.00 | -19309.27 | 0.00 | 0.00 | 40.66 | 68.40 | 720.18 | 6263.67 | 0.00 | 156.24 | 12060.11 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 11-JUN-09:32 | 0.00 | 0.00 | 0.00 | -20582.51 | 0.00 | 0.00 | 22.63 | 44.08 | 464.11 | 11865.42 | 0.00 | 37.20 | 8149.07 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 03-DEC-14:01 | 0.00 | 0.00 | 0.00 | -22591.84 | 0.00 | 0.00 | 30.76 | 68.40 | 720.19 | 19863.39 | 0.00 | 0.00 | 2004.45 | 0.00 | -0.00 | 0.00 | -95.36 | 0.00 |
PERIMETER_BOT_ZN_4 | 03-DEC-15:21 | 0.00 | 0.00 | 0.00 | -27150.88 | 0.00 | 0.00 | 21.06 | 44.08 | 464.11 | 11056.38 | 0.00 | 0.00 | 15613.11 | 0.00 | -0.00 | 0.00 | -47.87 | 0.00 |
PERIMETER_MID_ZN_3 | 29-MAY-15:41 | 0.00 | 0.00 | 0.00 | -188565.13 | 0.00 | 0.00 | 405.73 | 684.02 | 7201.84 | 53695.78 | 0.00 | 7293.64 | 119284.13 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 04-JUL-08:32 | 0.00 | 0.00 | 0.00 | -217098.81 | 0.00 | 0.00 | 218.30 | 440.81 | 4641.14 | 137690.31 | 0.00 | 116.08 | 73992.17 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 03-DEC-13:51 | 0.00 | 0.00 | 0.00 | -220202.20 | 0.00 | 0.00 | 295.55 | 684.04 | 7201.95 | 201111.60 | 0.00 | 0.00 | 13312.03 | 0.00 | -0.00 | 0.00 | -2402.96 | 0.00 |
PERIMETER_MID_ZN_4 | 29-MAY-15:41 | 0.00 | 0.00 | 0.00 | -247249.81 | 0.00 | 0.00 | 199.10 | 440.81 | 4641.11 | 133716.32 | 0.00 | 3651.06 | 104601.41 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 29-MAY-15:41 | 0.00 | 0.00 | 0.00 | -21491.35 | 0.00 | 0.00 | 38.43 | 68.40 | 720.18 | 5172.18 | 0.00 | 827.73 | 14664.43 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 04-JUL-08:32 | 0.00 | 0.00 | 0.00 | -21986.84 | 0.00 | 0.00 | 21.82 | 44.08 | 464.11 | 13706.36 | 0.00 | 12.04 | 7738.42 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 10-DEC-15:01 | 0.00 | 0.00 | 0.00 | -23691.38 | 0.00 | 0.00 | 31.64 | 68.40 | 720.19 | 14542.83 | 0.00 | 0.00 | 8427.50 | 0.00 | -0.00 | 0.00 | -99.19 | 0.00 |
PERIMETER_TOP_ZN_4 | 29-MAY-15:41 | 0.00 | 0.00 | 0.00 | -26764.58 | 0.00 | 0.00 | 18.68 | 44.08 | 464.11 | 13198.31 | 0.00 | 412.54 | 12626.85 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 06-DEC-17:00 | 0.00 | 0.00 | 0.00 | -8055.98 | 0.00 | 0.00 | 100.85 | 578.72 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -418.01 |
DATACENTER_MID_ZN_6 | 06-DEC-17:00 | 0.00 | 0.00 | 0.00 | -76396.33 | 0.00 | 0.00 | 1008.49 | 5787.18 | 77944.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -8343.57 |
DATACENTER_TOP_ZN_6 | 06-DEC-17:00 | 0.00 | 0.00 | 0.00 | -7704.37 | 0.00 | 0.00 | 100.85 | 578.72 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -769.62 |
DATACENTER_BASEMENT_ZN_6 | 28-AUG-12:20 | 0.00 | 0.00 | 0.00 | -370407.54 | 0.00 | 0.00 | 2173.86 | 6471.01 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -17869.85 |
GROUNDFLOOR_PLENUM | 18-SEP-05:02 | 0.00 | -14309.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.38 | 14291.24 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 06-JUL-05:02 | 0.00 | -104650.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 104805.49 | 0.00 | -0.00 | 0.00 | -155.42 | 0.00 |
TOPFLOOR_PLENUM | 28-JUL-15:30 | 0.00 | -23126.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 162.35 | 22964.48 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 01-DEC-05:11 | 0.00 | 61165.12 | 0.00 | -2133141.31 | 0.00 | 0.00 | 0.00 | 42872.09 | 587299.42 | 0.00 | 0.00 | 0.00 | 1481618.45 | 0.00 | -39813.77 | 0.00 | 0.00 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | 29-JUL-16:01 | 0.00 | 0.00 | 25124.34 | 0.00 | 0.00 | 0.00 | 520.12 | 1274.92 | 13457.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -40376.93 |
CORE_BOTTOM | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 04-FEB-06:02 | 0.00 | 0.00 | 670.09 | 0.00 | 0.00 | 0.00 | 90.18 | 185.31 | 618.82 | 0.00 | 0.00 | 0.00 | 2055.72 | 0.00 | -3498.57 | 0.00 | -121.56 | 0.00 |
PERIMETER_BOT_ZN_1 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 04-FEB-05:11 | 0.00 | 0.00 | 127902.97 | 0.00 | 0.00 | 0.00 | 0.00 | 1437.63 | 5591.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -48244.43 | 0.00 | -15958.67 | -70729.21 |
PERIMETER_MID_ZN_2 | 04-FEB-05:11 | 0.00 | 0.00 | 94682.91 | 0.00 | 0.00 | 0.00 | 0.00 | 926.46 | 3603.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -31547.99 | 0.00 | -10793.89 | -56871.00 |
PERIMETER_MID_ZN_1 | 04-FEB-06:02 | 0.00 | 0.00 | 118493.22 | 0.00 | 0.00 | 0.00 | 1460.98 | 2875.64 | 9602.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -50644.38 | 0.00 | -4219.26 | -77568.79 |
PERIMETER_MID_ZN_4 | 04-FEB-05:11 | 0.00 | 0.00 | 85003.69 | 0.00 | 0.00 | 0.00 | 0.00 | 926.46 | 3603.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -33425.30 | 0.00 | -11088.53 | -45019.81 |
PERIMETER_TOP_ZN_3 | 04-FEB-05:11 | 0.00 | 0.00 | 15960.60 | 0.00 | 0.00 | 0.00 | 0.00 | 143.76 | 559.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -4300.30 | 0.00 | -1756.38 | -10606.86 |
PERIMETER_TOP_ZN_2 | 04-FEB-05:11 | 0.00 | 0.00 | 12305.61 | 0.00 | 0.00 | 0.00 | 0.00 | 92.65 | 360.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2823.52 | 0.00 | -1195.36 | -8739.73 |
PERIMETER_TOP_ZN_1 | 04-FEB-05:11 | 0.00 | 0.00 | 15247.51 | 0.00 | 0.00 | 0.00 | 0.00 | 143.77 | 559.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -4497.55 | 0.00 | -1901.26 | -9551.65 |
PERIMETER_TOP_ZN_4 | 04-FEB-05:11 | 0.00 | 0.00 | 11831.77 | 0.00 | 0.00 | 0.00 | 0.00 | 92.65 | 360.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3030.93 | 0.00 | -1250.32 | -8003.52 |
DATACENTER_BOT_ZN_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 22-JAN-08:30 | 0.00 | 0.00 | 192.10 | 0.00 | 0.00 | 0.00 | 5.27 | 32.15 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -2178.13 |
DATACENTER_BASEMENT_ZN_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 18-DEC-05:12 | 14389.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -270.78 | -14118.28 |
MIDFLOOR_PLENUM | 13-NOV-05:12 | 80913.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -18819.58 | -62093.94 |
TOPFLOOR_PLENUM | 28-FEB-06:03 | 14242.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -14242.62 |
Total Facility | 04-FEB-06:02 | -710888.77 | 662518.78 | 455838.38 | -662518.78 | 0.00 | 0.00 | 19092.75 | 42872.09 | 379706.36 | 0.00 | 0.00 | 0.00 | 40413.13 | 0.00 | -202208.74 | 0.00 | -24825.20 | 0.00 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 08:43:45
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
VAV_BOT WITH REHEAT | 11.0426 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 10.1385 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_MID WITH REHEAT | 104.7677 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 95.0764 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_TOP WITH REHEAT | 10.7077 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 10.2938 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
CAV_BAS | 6.0855 | 0.0000 | 149.6021 | 1.0000 | Calculated from schedules | 1.2002 | 6.0855 | 0.1972 | 1.0000 | Not calculated | 1.2002 | 0.1972 | ||
AIRLOOP DATACENTER BASEMENT | 21.4296 | 0.0000 | 42.1814 | 1.0000 | Calculated from schedules | 0.3384 | 21.4298 | 0.0158 | 1.0000 | Not calculated | 0.3384 | 0.0158 | ||
AIRLOOP DATACENTER BOT | 0.4801 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.4801 | 0.0326 | 1.0000 | Not calculated | 0.0156 | 0.0326 | ||
AIRLOOP DATACENTER MID | 4.5783 | 0.0000 | 19.4861 | 1.0000 | Calculated from schedules | 0.1563 | 4.5783 | 0.0341 | 1.0000 | Not calculated | 0.1563 | 0.0341 | ||
AIRLOOP DATACENTER TOP | 0.4669 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.4669 | 0.0335 | 1.0000 | Not calculated | 0.0156 | 0.0335 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
VAV_BOT WITH REHEAT | 5.5213 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 2.9619 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_MID WITH REHEAT | 52.3838 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 28.9100 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_TOP WITH REHEAT | 5.3538 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 2.9633 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
CAV_BAS | 6.0855 | 0.0000 | 149.6021 | 1.0000 | Calculated from schedules | 1.2002 | 6.0855 | 1.0000 | 1.0000 | Not calculated | 1.2002 | 0.1972 | ||
AIRLOOP DATACENTER BASEMENT | 21.4296 | 0.0000 | 42.1814 | 1.0000 | Calculated from schedules | 0.3384 | 21.4296 | 1.0000 | 1.0000 | Not calculated | 0.3384 | 0.0158 | ||
AIRLOOP DATACENTER BOT | 0.4801 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.4801 | 1.0000 | 1.0000 | Not calculated | 0.0156 | 0.0326 | ||
AIRLOOP DATACENTER MID | 4.5783 | 0.0000 | 19.4861 | 1.0000 | Calculated from schedules | 0.1563 | 4.5783 | 1.0000 | 1.0000 | Not calculated | 0.1563 | 0.0341 | ||
AIRLOOP DATACENTER TOP | 0.4669 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.4669 | 1.0000 | 1.0000 | Not calculated | 0.0156 | 0.0335 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
BASEMENT | CAV_BAS | 0.000000 | 149.6021 | 0.000432 | 2779.43 | 1.2002 | 1.0000 | 1.2002 | 1.000 | 1.2002 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | 0.000000 | 134.3532 | 0.000432 | 2496.12 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_MID | VAV_MID WITH REHEAT | 0.000000 | 1343.5320 | 0.000432 | 24961.20 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_TOP | VAV_TOP WITH REHEAT | 0.000000 | 134.3532 | 0.000432 | 2496.12 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | 0.000000 | 16.8694 | 0.000432 | 313.41 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | 0.000000 | 16.8698 | 0.000432 | 313.42 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | 0.000000 | 168.6939 | 0.000432 | 3134.13 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | 0.000000 | 108.7127 | 0.000432 | 2019.75 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | 0.000000 | 168.6975 | 0.000432 | 3134.20 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | 0.000000 | 108.7127 | 0.000432 | 2019.75 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | 0.000000 | 16.8694 | 0.000432 | 313.41 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | 0.000000 | 16.8698 | 0.000432 | 313.42 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | 0.000000 | 1.9486 | 0.000432 | 36.20 | 0.0156 | 1.0000 | 0.0156 | 1.000 | 0.0156 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | 0.000000 | 19.4861 | 0.000432 | 362.03 | 0.1563 | 1.0000 | 0.1563 | 1.000 | 0.1563 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | 0.000000 | 1.9486 | 0.000432 | 36.20 | 0.0156 | 1.0000 | 0.0156 | 1.000 | 0.0156 |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | 0.000000 | 42.1814 | 0.000432 | 783.68 | 0.3384 | 1.0000 | 0.3384 | 1.000 | 0.3384 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
VAV_BOT WITH REHEAT | 0.00 | 0.000432 | 3526.9033 | 0.0000 | 0.0000 | 0.0000 | |
VAV_MID WITH REHEAT | 0.00 | 0.000432 | 35269.0328 | 0.0000 | 0.0000 | 0.0000 | |
VAV_TOP WITH REHEAT | 0.00 | 0.000432 | 3526.9033 | 0.0000 | 0.0000 | 0.0000 | |
CAV_BAS | 0.000000 | 149.60 | 0.000432 | 2779.4266 | 1.2002 | 1.2002 | 1.2002 |
AIRLOOP DATACENTER BASEMENT | 0.000000 | 42.18 | 0.000432 | 783.6794 | 0.3384 | 0.3384 | 0.3384 |
AIRLOOP DATACENTER BOT | 0.000000 | 1.95 | 0.000432 | 36.2027 | 0.0156 | 0.0156 | 0.0156 |
AIRLOOP DATACENTER MID | 0.000000 | 19.49 | 0.000432 | 362.0274 | 0.1563 | 0.1563 | 0.1563 |
AIRLOOP DATACENTER TOP | 0.000000 | 1.95 | 0.000432 | 36.2027 | 0.0156 | 0.0156 | 0.0156 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | CAV_BAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 6.0855 | 6.0855 | 6.0855 | No | 1.2002 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 6.2822 | 6.2822 | 1.9600 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 59.3870 | 59.3870 | 19.2414 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 5.8348 | 5.8348 | 1.9663 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.1082 | 1.1082 | 0.2460 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.1100 | 1.1100 | 0.2220 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.1050 | 1.1050 | 0.2464 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.4371 | 1.4371 | 0.2874 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 10.6266 | 10.6266 | 2.4122 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 11.4819 | 11.4819 | 2.2964 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 10.5372 | 10.5372 | 2.4130 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 12.7350 | 12.7350 | 2.5470 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.1783 | 1.1783 | 0.2474 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.1629 | 1.1629 | 0.2326 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.1791 | 1.1791 | 0.2464 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.3525 | 1.3525 | 0.2705 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.4801 | 0.4801 | 0.4801 | No | 0.0156 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 4.5783 | 4.5783 | 4.5783 | No | 0.1563 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.4669 | 0.4669 | 0.4669 | No | 0.0156 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 21.4296 | 21.4296 | 21.4296 | No | 0.3384 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
VAV_BOT WITH REHEAT | 11.0426 | 10.1385 | 11.0426 | 2.9619 | 0.0000 | 1.0000 |
VAV_MID WITH REHEAT | 104.7677 | 95.0764 | 104.7677 | 28.9100 | 0.0000 | 1.0000 |
VAV_TOP WITH REHEAT | 10.7077 | 10.2938 | 10.7077 | 2.9633 | 0.0000 | 1.0000 |
CAV_BAS | 6.0855 | 6.0855 | 6.0855 | 6.0855 | 1.2002 | 1.0000 |
AIRLOOP DATACENTER BASEMENT | 21.4296 | 21.4298 | 21.4296 | 21.4296 | 0.3384 | 1.0000 |
AIRLOOP DATACENTER BOT | 0.4801 | 0.4801 | 0.4801 | 0.4801 | 0.0156 | 1.0000 |
AIRLOOP DATACENTER MID | 4.5783 | 4.5783 | 4.5783 | 4.5783 | 0.1563 | 1.0000 |
AIRLOOP DATACENTER TOP | 0.4669 | 0.4669 | 0.4669 | 0.4669 | 0.0156 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | CAV_BAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 6.0855 | 6.0855 | 6.0855 | No | 1.2002 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 3.1411 | 3.1411 | 1.9600 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 29.6935 | 29.6935 | 19.2414 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.9174 | 2.9174 | 1.9663 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5541 | 0.5541 | 0.2460 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5550 | 0.5550 | 0.2220 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5525 | 0.5525 | 0.2464 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7186 | 0.7186 | 0.2874 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 5.3133 | 5.3133 | 2.4122 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 5.7410 | 5.7410 | 2.2964 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 5.2686 | 5.2686 | 2.4130 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 6.3675 | 6.3675 | 2.5470 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5892 | 0.5892 | 0.2474 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5815 | 0.5815 | 0.2326 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5896 | 0.5896 | 0.2464 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6763 | 0.6763 | 0.2705 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.4801 | 0.4801 | 0.4801 | No | 0.0156 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 4.5783 | 4.5783 | 4.5783 | No | 0.1563 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.4669 | 0.4669 | 0.4669 | No | 0.0156 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 21.4296 | 21.4296 | 21.4296 | No | 0.3384 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
VAV_BOT WITH REHEAT | 5.5213 | 2.9619 | 2.9619 | 2.9619 | 0.0000 | 1.0000 |
VAV_MID WITH REHEAT | 52.3838 | 28.9100 | 28.9100 | 28.9100 | 0.0000 | 1.0000 |
VAV_TOP WITH REHEAT | 5.3538 | 2.9633 | 2.9633 | 2.9633 | 0.0000 | 1.0000 |
CAV_BAS | 6.0855 | 6.0855 | 6.0855 | 6.0855 | 1.2002 | 1.0000 |
AIRLOOP DATACENTER BASEMENT | 21.4296 | 21.4296 | 21.4296 | 21.4296 | 0.3384 | 1.0000 |
AIRLOOP DATACENTER BOT | 0.4801 | 0.4801 | 0.4801 | 0.4801 | 0.0156 | 1.0000 |
AIRLOOP DATACENTER MID | 4.5783 | 4.5783 | 4.5783 | 4.5783 | 0.1563 | 1.0000 |
AIRLOOP DATACENTER TOP | 0.4669 | 0.4669 | 0.4669 | 0.4669 | 0.0156 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 08:43:45
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Miami Intl Ap FL USA TMY3 WMO#=722020 |
Total gross floor area [m2] | 46320.38 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
BASEMENT | 2779.43 | 2779.43 | 0.00 | 113.98 |
CORE_BOTTOM | 2496.12 | 2496.12 | 0.00 | 113.98 |
CORE_MID | 2496.12 | 2496.12 | 0.00 | 113.98 |
CORE_TOP | 2496.12 | 2496.12 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_3 | 313.41 | 313.41 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_2 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_1 | 313.42 | 313.42 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_4 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_MID_ZN_3 | 313.41 | 313.41 | 0.00 | 113.98 |
PERIMETER_MID_ZN_2 | 201.98 | 201.98 | 0.00 | 96.54 |
PERIMETER_MID_ZN_1 | 313.42 | 313.42 | 0.00 | 113.98 |
PERIMETER_MID_ZN_4 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_3 | 313.41 | 313.41 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_2 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_1 | 313.42 | 313.42 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_4 | 201.98 | 201.98 | 0.00 | 113.98 |
DATACENTER_BOT_ZN_6 | 36.20 | 36.20 | 0.00 | 113.98 |
DATACENTER_MID_ZN_6 | 36.20 | 36.20 | 0.00 | 113.98 |
DATACENTER_TOP_ZN_6 | 36.20 | 36.20 | 0.00 | 113.98 |
DATACENTER_BASEMENT_ZN_6 | 783.68 | 783.68 | 0.00 | 113.98 |
GROUNDFLOOR_PLENUM | 3563.11 | 3563.11 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 3563.11 | 3563.11 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 3563.11 | 3563.11 | 0.00 | 0.00 |
Totals | 46320.38 | 46320.38 | 0.00 |
Data | |
Number of hours heating loads not met | 0.00 |
Number of hours cooling loads not met | 1000.17 |
Number of hours not met | 1000.17 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler | 0.00 | 0.00 | 20.08 | 404990.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 6915.41 | 495044.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 3922.25 | 385834.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 696.56 | 57580.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 5334.97 | 305206.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- DataCenterPlugLoads | 9341.42 | 473165.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Transformer | 80.17 | 5057.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLift | 1848.78 | 113101.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLightsFan | 5.83 | 376.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 2279.76 | 148849.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 978.88 | 69624.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- General | 2294.23 | 98044.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- General | 1.14 | 4077.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- General | 119.08 | 5613.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 0.00 | 0.00 | 640.83 | 70632.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 14676.40 | 33818.50 |
Natural Gas | 0.00 | 660.92 |
Additional | 0.00 | 0.00 |
Total | 14676.40 | 34479.41 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 84.68 |
Space Heating | 0.00 |
Space Cooling | 149.30 |
Fans (All) | 49.22 |
Service Water Heating | 0.00 |
Receptacle Equipment | 316.85 |
Miscellaneous (All) | 730.10 |
Subtotal | 730.10 |
Natural Gas [MJ/m2] | |
Space Heating | 0.43 |
Service Water Heating | 13.83 |
Miscellaneous (All) | 14.27 |
Subtotal | 14.27 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 11.38 |
Space Heating | 0.06 |
Space Cooling | 20.06 |
Fans (All) | 6.61 |
Service Water Heating | 1.86 |
Receptacle Equipment | 42.57 |
Miscellaneous | 17.47 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 4472. | 4472. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 6752. | 8760. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 6828. | 8760. |
ALWAYS_OFF | 0. | 0. |
LTG_SCH_OFFICE | 2625. | 8760. |
LTG_SCH_DATACENTER | 2921. | 8760. |
EXTERIOR_LIGHT_SCH | 4380. | 4380. |
BLDG_EQUIP_SCH | 4049. | 8760. |
DATACENTER_EQUIP_SCH | 5478. | 8760. |
BLDG_OCC_SCH | 2528. | 5992. |
BLDG_OCC_SCH_W_SB | 1878. | 5056. |
BLDG_OCC_SCH_WO_SB | 2557. | 5992. |
BLDG_ELEVATORS | 2270. | 8760. |
ELEV_LIGHT_FAN_SCH_24_7 | 8760. | 8760. |
ELEV_LIGHT_FAN_SCH_ADD_DF | 2154. | 8760. |
BLDG_SWH_SCH | 1474. | 6570. |
WORK_EFF_SCH | 0. | 0. |
INFIL_SCH | 3976. | 3976. |
INFIL_SCH_PNNL | 5172. | 8760. |
INFIL_HALF_ON_SCH | 6368. | 8760. |
FAN_SCH | 8760. | 8760. |
REHEATCOILAVAILSCHED | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
MINOA_MOTORIZEDDAMPER_SCHED | 4472. | 4472. |
MINOA_SCHED | 8760. | 8760. |
CORE_BOTTOM SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_BOTTOM SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_MID SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_MID SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_TOP SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_TOP SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
SUPPLYFANSCH | 8760. | 8760. |
PERIMETER_MID_ZN_2_MDP_SCH | 1565. | 7824. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
HTGSETP_DC_SCH | DATACENTER COOLING SETPOINTS DUAL SP CONTROL | January | 18.00 | 365 | 18.00 | 365 |
CLGSETP_DC_SCH | DATACENTER COOLING SETPOINTS DUAL SP CONTROL | July | 27.00 | 365 | 27.00 | 365 |
HTGSETP_SCH_YES_OPTIMUM | CORE_BOTTOM DUAL SP CONTROL | January | 21.00 | 365 | 15.60 | 365 |
CLGSETP_SCH_YES_OPTIMUM | CORE_BOTTOM DUAL SP CONTROL | July | 24.00 | 365 | 26.70 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:43:45
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
BASEMENT | 6515.17 | 2244.83 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 8674.00 | 86.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 8757.00 | 3.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 8715.50 | 44.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 8644.50 | 115.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 8515.50 | 244.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 7581.33 | 1178.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 8583.50 | 176.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 8386.33 | 373.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 8116.17 | 643.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 7728.00 | 1032.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 8488.83 | 271.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 8322.17 | 437.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 8077.00 | 683.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 7796.00 | 964.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 1236.50 | 7523.50 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 1232.83 | 7527.17 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 1188.83 | 7571.17 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 1046.33 | 7713.67 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 8442.00 | 318.00 | 0.00 | 0.00 | 0.00 |
Min | 1046.33 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 7713.67 | 0.00 | 0.00 | 0.00 |
Average | 7057.72 | 1702.28 | 0.00 | 0.00 | 0.00 |
Sum | 162327.50 | 39152.50 | 0.00 | 0.00 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
BASEMENT | 363397.50 | 5218.50 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 330733.00 | 80.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 330813.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 330813.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 18354.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 208.50 | 2059.50 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 209.33 | 2058.67 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 202.17 | 2065.83 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 9376.17 | 94018.83 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 363397.50 | 94018.83 | 0.00 | 0.00 | 0.00 |
Average | 75747.90 | 4587.01 | 0.00 | 0.00 | 0.00 |
Sum | 1742201.67 | 105501.33 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
BASEMENT | 3509.83 | 5250.17 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 8411.67 | 348.33 | 0.00 | 0.00 | 0.00 |
CORE_MID | 8689.33 | 70.67 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 8706.33 | 53.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 7829.17 | 930.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 8068.50 | 691.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 7402.33 | 1357.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 6952.00 | 1808.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 6277.00 | 2483.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 6398.67 | 2361.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 5892.83 | 2867.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 6140.00 | 2620.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 6169.50 | 2590.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 6285.83 | 2474.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 5831.00 | 2929.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 6113.17 | 2646.83 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 2356.67 | 6403.33 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 2303.17 | 6456.83 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 2214.67 | 6545.33 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 2429.67 | 6330.33 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 8365.00 | 395.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 7178.00 | 1582.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 6876.67 | 1883.33 | 0.00 | 0.00 | 0.00 |
Min | 2214.67 | 53.67 | 0.00 | 0.00 | 0.00 |
Max | 8706.33 | 6545.33 | 0.00 | 0.00 | 0.00 |
Average | 6104.39 | 2655.61 | 0.00 | 0.00 | 0.00 |
Sum | 140401.00 | 61079.00 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
BASEMENT | 325708.17 | 42907.83 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 330422.00 | 391.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 330627.00 | 186.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 330709.00 | 104.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 38913.50 | 11.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 18351.50 | 2.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 38914.00 | 11.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 24908.00 | 1.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 38909.00 | 16.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 24905.00 | 4.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 38908.83 | 16.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 24906.67 | 2.33 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 380.50 | 1887.50 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 371.17 | 1896.83 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 353.67 | 1914.33 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 19264.67 | 84130.33 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 330709.00 | 84130.33 | 0.00 | 0.00 | 0.00 |
Average | 74531.33 | 5803.58 | 0.00 | 0.00 | 0.00 |
Sum | 1714220.67 | 133482.33 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:43:45
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:43:45
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 0.00 | 8760.00 | 0.00 |
Average | 0.00 | 0.00 | 4570.43 | 0.00 |
Sum | 0.00 | 0.00 | 105120.00 | 0.00 |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 18354.00 | 0.00 |
PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 24909.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 0.00 | 38925.00 | 0.00 |
Average | 0.00 | 0.00 | 16367.35 | 0.00 |
Sum | 0.00 | 0.00 | 376449.00 | 0.00 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.420 |
February | 20.868 |
March | 21.567 |
April | 24.112 |
May | 26.413 |
June | 27.683 |
July | 28.127 |
August | 27.974 |
September | 27.493 |
October | 26.347 |
November | 23.587 |
December | 20.295 |
Annual Sum or Average | 24.507 |
Minimum of Months | 19.420 |
Maximum of Months | 28.127 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Environment
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.420 |
February | 20.868 |
March | 21.567 |
April | 24.112 |
May | 26.413 |
June | 27.683 |
July | 28.127 |
August | 27.974 |
September | 27.493 |
October | 26.347 |
November | 23.587 |
December | 20.295 |
Annual Sum or Average | 24.507 |
Minimum of Months | 19.420 |
Maximum of Months | 28.127 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2013
For: Environment
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.420 |
February | 20.868 |
March | 21.567 |
April | 24.112 |
May | 26.413 |
June | 27.683 |
July | 28.127 |
August | 27.974 |
September | 27.493 |
October | 26.347 |
November | 23.587 |
December | 20.295 |
Annual Sum or Average | 24.507 |
Minimum of Months | 19.420 |
Maximum of Months | 28.127 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.420 |
February | 20.868 |
March | 21.567 |
April | 24.112 |
May | 26.413 |
June | 27.683 |
July | 28.127 |
August | 27.974 |
September | 27.493 |
October | 26.347 |
November | 23.587 |
December | 20.295 |
Annual Sum or Average | 24.507 |
Minimum of Months | 19.420 |
Maximum of Months | 28.127 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICELARGE
For: Environment
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.420 |
February | 20.868 |
March | 21.567 |
April | 24.112 |
May | 26.413 |
June | 27.683 |
July | 28.127 |
August | 27.974 |
September | 27.493 |
October | 26.347 |
November | 23.587 |
December | 20.295 |
Annual Sum or Average | 24.507 |
Minimum of Months | 19.420 |
Maximum of Months | 28.127 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.420 |
February | 20.868 |
March | 21.567 |
April | 24.112 |
May | 26.413 |
June | 27.683 |
July | 28.127 |
August | 27.974 |
September | 27.493 |
October | 26.347 |
November | 23.587 |
December | 20.295 |
Annual Sum or Average | 24.507 |
Minimum of Months | 19.420 |
Maximum of Months | 28.127 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.420 |
February | 20.868 |
March | 21.567 |
April | 24.112 |
May | 26.413 |
June | 27.683 |
July | 28.127 |
August | 27.974 |
September | 27.493 |
October | 26.347 |
November | 23.587 |
December | 20.295 |
Annual Sum or Average | 24.507 |
Minimum of Months | 19.420 |
Maximum of Months | 28.127 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 1A
For: Environment
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.420 |
February | 20.868 |
March | 21.567 |
April | 24.112 |
May | 26.413 |
June | 27.683 |
July | 28.127 |
August | 27.974 |
September | 27.493 |
October | 26.347 |
November | 23.587 |
December | 20.295 |
Annual Sum or Average | 24.507 |
Minimum of Months | 19.420 |
Maximum of Months | 28.127 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_FL_MIAMI
For: Environment
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.420 |
February | 20.868 |
March | 21.567 |
April | 24.112 |
May | 26.413 |
June | 27.683 |
July | 28.127 |
August | 27.974 |
September | 27.493 |
October | 26.347 |
November | 23.587 |
December | 20.295 |
Annual Sum or Average | 24.507 |
Minimum of Months | 19.420 |
Maximum of Months | 28.127 |
Report: ZoneCoolingSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.664485E+11 | 105498.80 | 25-JAN-05:12 | 9.40 | 4.59 | 0.567191E+10 | 7499.12 | 27-JAN-10:00 | 21.70 | 15.05 |
February | 0.597616E+11 | 109161.00 | 04-FEB-05:11 | 5.93 | 2.51 | 0.514395E+10 | 7499.11 | 23-FEB-10:09 | 23.07 | 17.34 |
March | 0.677832E+11 | 106970.58 | 16-MAR-04:12 | 7.43 | 4.89 | 0.613701E+10 | 7499.08 | 17-MAR-13:09 | 21.20 | 14.87 |
April | 0.618174E+11 | 104536.52 | 19-APR-04:12 | 15.00 | 11.82 | 0.545325E+10 | 7499.09 | 21-APR-09:20 | 25.40 | 18.57 |
May | 0.661215E+11 | 89064.31 | 08-MAY-04:11 | 23.50 | 18.76 | 0.590485E+10 | 7498.82 | 25-MAY-09:20 | 24.23 | 23.36 |
June | 0.660954E+11 | 85224.33 | 13-JUN-03:02 | 24.32 | 22.73 | 0.588466E+10 | 7498.81 | 28-JUN-09:20 | 26.30 | 24.72 |
July | 0.668175E+11 | 87409.27 | 04-JUL-15:30 | 32.25 | 24.75 | 0.547656E+10 | 7498.80 | 07-JUL-13:20 | 32.03 | 25.28 |
August | 0.747828E+11 | 86150.01 | 22-AUG-03:02 | 27.12 | 24.30 | 0.614004E+10 | 7498.78 | 04-AUG-13:20 | 27.12 | 24.30 |
September | 0.670318E+11 | 85048.44 | 04-SEP-24:00 | 23.30 | 21.69 | 0.545560E+10 | 7498.79 | 15-SEP-09:20 | 27.40 | 24.40 |
October | 0.704696E+11 | 91945.97 | 18-OCT-03:02 | 24.32 | 18.76 | 0.567472E+10 | 7498.78 | 18-OCT-09:20 | 26.70 | 18.90 |
November | 0.696431E+11 | 108988.80 | 13-NOV-05:12 | 12.60 | 7.82 | 0.561876E+10 | 7499.12 | 13-NOV-10:09 | 19.68 | 13.91 |
December | 0.681816E+11 | 107123.21 | 21-DEC-05:12 | 10.77 | 9.99 | 0.547557E+10 | 7499.18 | 21-DEC-10:09 | 19.08 | 15.38 |
Annual Sum or Average | 0.804954E+12 | 0.680369E+11 | ||||||||
Minimum of Months | 0.597616E+11 | 85048.44 | 5.93 | 2.51 | 0.514395E+10 | 7498.78 | 19.08 | 13.91 | ||
Maximum of Months | 0.747828E+11 | 109161.00 | 32.25 | 24.75 | 0.614004E+10 | 7499.18 | 32.03 | 25.28 |
Report: ZoneCoolingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.564758E+11 | 101591.23 | 30-JAN-05:13 | 20.73 | 20.35 | 0.506755E+10 | 6734.91 | 27-JAN-10:00 | 20.73 | 20.35 |
February | 0.548811E+11 | 103182.26 | 21-FEB-05:13 | 16.33 | 15.55 | 0.460068E+10 | 6734.59 | 24-FEB-10:09 | 20.28 | 12.39 |
March | 0.703668E+11 | 102435.06 | 07-MAR-05:13 | 20.40 | 19.02 | 0.549357E+10 | 6734.70 | 17-MAR-09:09 | 17.15 | 10.18 |
April | 0.748647E+11 | 97200.94 | 19-APR-04:13 | 15.00 | 11.82 | 0.487226E+10 | 6734.50 | 18-APR-09:00 | 15.00 | 11.82 |
May | 0.694836E+11 | 94217.47 | 26-MAY-03:02 | 23.90 | 22.01 | 0.527733E+10 | 6734.46 | 25-MAY-09:09 | 23.90 | 22.01 |
June | 0.745290E+11 | 93484.24 | 13-JUN-03:02 | 24.32 | 22.73 | 0.526074E+10 | 6734.45 | 05-JUN-13:50 | 24.32 | 22.73 |
July | 0.797098E+11 | 77512.77 | 14-JUL-05:02 | 27.20 | 25.17 | 0.488572E+10 | 6734.47 | 10-JUL-09:09 | 27.20 | 25.17 |
August | 0.864309E+11 | 88363.86 | 21-AUG-05:03 | 27.20 | 24.67 | 0.548872E+10 | 6734.45 | 28-AUG-09:09 | 22.80 | 22.12 |
September | 0.693658E+11 | 97920.21 | 06-SEP-04:13 | 23.13 | 22.53 | 0.487347E+10 | 6734.45 | 05-SEP-13:09 | 23.13 | 22.53 |
October | 0.726477E+11 | 97025.17 | 20-OCT-04:13 | 21.70 | 19.53 | 0.506907E+10 | 6734.49 | 02-OCT-09:09 | 21.70 | 19.53 |
November | 0.688409E+11 | 101674.97 | 27-NOV-05:11 | 10.00 | 8.82 | 0.502426E+10 | 6734.91 | 27-NOV-10:50 | 21.65 | 16.17 |
December | 0.681145E+11 | 99972.90 | 18-DEC-05:12 | 17.20 | 17.20 | 0.489480E+10 | 6734.71 | 27-DEC-10:09 | 13.58 | 11.53 |
Annual Sum or Average | 0.845711E+12 | 0.608082E+11 | ||||||||
Minimum of Months | 0.548811E+11 | 77512.77 | 10.00 | 8.82 | 0.460068E+10 | 6734.45 | 13.58 | 10.18 | ||
Maximum of Months | 0.864309E+11 | 103182.26 | 27.20 | 25.17 | 0.549357E+10 | 6734.91 | 27.20 | 25.17 |
Report: ZoneCoolingSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.452889E+11 | 88367.99 | 03-JAN-05:12 | 20.00 | 19.44 | 0.501797E+10 | 6734.88 | 27-JAN-10:00 | 21.70 | 15.05 |
February | 0.427596E+11 | 91009.26 | 13-FEB-05:11 | 20.20 | 19.29 | 0.455424E+10 | 6734.58 | 24-FEB-10:09 | 20.28 | 12.39 |
March | 0.519136E+11 | 89439.42 | 07-MAR-05:11 | 20.40 | 19.02 | 0.545977E+10 | 6734.69 | 17-MAR-09:09 | 17.15 | 10.18 |
April | 0.525736E+11 | 89894.39 | 18-APR-04:12 | 19.03 | 14.99 | 0.485367E+10 | 6734.51 | 18-APR-13:09 | 22.38 | 14.69 |
May | 0.588611E+11 | 89109.06 | 01-MAY-04:12 | 20.93 | 19.77 | 0.526150E+10 | 6734.46 | 25-MAY-09:09 | 24.32 | 23.32 |
June | 0.604421E+11 | 85609.43 | 06-JUN-05:04 | 23.98 | 23.24 | 0.524467E+10 | 6734.47 | 05-JUN-13:50 | 23.98 | 23.24 |
July | 0.608059E+11 | 84135.69 | 07-JUL-04:13 | 23.30 | 21.44 | 0.486451E+10 | 6734.45 | 07-JUL-13:09 | 32.12 | 25.32 |
August | 0.620326E+11 | 87181.86 | 24-AUG-03:02 | 25.00 | 24.24 | 0.546916E+10 | 6734.45 | 28-AUG-13:09 | 22.30 | 22.22 |
September | 0.585359E+11 | 85152.12 | 15-SEP-03:02 | 24.40 | 23.08 | 0.485448E+10 | 6734.45 | 06-SEP-13:09 | 24.40 | 23.08 |
October | 0.571711E+11 | 91473.61 | 20-OCT-04:13 | 21.70 | 19.53 | 0.505577E+10 | 6734.50 | 10-OCT-13:09 | 21.70 | 19.53 |
November | 0.507758E+11 | 89364.62 | 08-NOV-05:13 | 21.10 | 20.29 | 0.500412E+10 | 6734.89 | 27-NOV-10:50 | 21.65 | 16.17 |
December | 0.461057E+11 | 88175.61 | 06-DEC-05:12 | 21.30 | 19.77 | 0.484321E+10 | 6734.71 | 15-DEC-14:09 | 19.08 | 14.19 |
Annual Sum or Average | 0.647266E+12 | 0.604831E+11 | ||||||||
Minimum of Months | 0.427596E+11 | 84135.69 | 19.03 | 14.99 | 0.455424E+10 | 6734.45 | 17.15 | 10.18 | ||
Maximum of Months | 0.620326E+11 | 91473.61 | 25.00 | 24.24 | 0.546916E+10 | 6734.89 | 32.12 | 25.32 |
Report: ZoneCoolingSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.417833E+11 | 85458.64 | 30-JAN-05:12 | 20.73 | 20.35 | 0.486488E+10 | 6734.49 | 20-JAN-14:09 | 20.73 | 20.35 |
February | 0.413002E+11 | 86436.35 | 13-FEB-05:11 | 20.20 | 19.29 | 0.448580E+10 | 6734.51 | 21-FEB-14:00 | 26.10 | 13.62 |
March | 0.517152E+11 | 86674.92 | 31-MAR-04:12 | 22.60 | 19.02 | 0.539756E+10 | 6734.59 | 17-MAR-13:09 | 22.60 | 19.02 |
April | 0.547687E+11 | 88086.02 | 18-APR-04:12 | 19.03 | 14.99 | 0.484294E+10 | 6734.48 | 18-APR-09:00 | 20.60 | 14.15 |
May | 0.633823E+11 | 87091.45 | 11-MAY-04:12 | 21.70 | 21.19 | 0.526441E+10 | 6734.47 | 30-MAY-13:09 | 25.97 | 24.15 |
June | 0.657649E+11 | 85032.43 | 13-JUN-04:02 | 23.90 | 22.65 | 0.524981E+10 | 6734.45 | 05-JUN-13:00 | 23.90 | 22.65 |
July | 0.668414E+11 | 84676.63 | 15-JUL-04:02 | 25.18 | 24.23 | 0.487278E+10 | 6734.43 | 14-JUL-13:00 | 25.18 | 24.23 |
August | 0.669769E+11 | 85008.15 | 29-AUG-04:02 | 23.80 | 23.12 | 0.547151E+10 | 6734.45 | 07-AUG-13:00 | 23.80 | 23.12 |
September | 0.625163E+11 | 85878.03 | 08-SEP-03:02 | 24.40 | 23.08 | 0.485747E+10 | 6734.43 | 11-SEP-13:00 | 27.80 | 24.12 |
October | 0.588389E+11 | 85695.45 | 20-OCT-04:11 | 21.70 | 19.53 | 0.504773E+10 | 6734.48 | 26-OCT-13:00 | 21.70 | 20.88 |
November | 0.500565E+11 | 86893.42 | 06-NOV-05:12 | 21.10 | 19.69 | 0.496108E+10 | 6734.42 | 24-NOV-10:09 | 21.70 | 21.35 |
December | 0.434422E+11 | 85287.26 | 07-DEC-05:12 | 23.13 | 21.36 | 0.471430E+10 | 6734.58 | 13-DEC-14:00 | 21.70 | 13.99 |
Annual Sum or Average | 0.667387E+12 | 0.600303E+11 | ||||||||
Minimum of Months | 0.413002E+11 | 84676.63 | 19.03 | 14.99 | 0.448580E+10 | 6734.42 | 20.60 | 13.62 | ||
Maximum of Months | 0.669769E+11 | 88086.02 | 25.18 | 24.23 | 0.547151E+10 | 6734.59 | 27.80 | 24.23 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.607659E+10 | 14618.55 | 30-JAN-05:12 | 20.73 | 20.35 | 0.619504E+09 | 845.60 | 20-JAN-14:20 | 20.73 | 20.35 |
February | 0.669087E+10 | 14664.89 | 17-FEB-05:11 | 22.80 | 20.75 | 0.570998E+09 | 845.61 | 21-FEB-14:09 | 25.68 | 14.65 |
March | 0.901949E+10 | 15169.10 | 07-MAR-05:11 | 20.40 | 19.02 | 0.681492E+09 | 845.62 | 17-MAR-13:09 | 21.20 | 14.87 |
April | 0.110655E+11 | 10831.86 | 17-APR-15:00 | 32.20 | 19.76 | 0.611931E+09 | 845.61 | 18-APR-13:09 | 22.38 | 14.69 |
May | 0.122996E+11 | 17624.87 | 29-MAY-15:52 | 33.30 | 24.52 | 0.664515E+09 | 845.59 | 23-MAY-13:09 | 33.30 | 24.52 |
June | 0.140977E+11 | 18923.30 | 11-JUN-16:11 | 30.93 | 24.21 | 0.662489E+09 | 845.59 | 21-JUN-13:20 | 29.40 | 23.58 |
July | 0.149920E+11 | 19309.23 | 30-JUL-14:22 | 33.60 | 24.88 | 0.616039E+09 | 845.59 | 10-JUL-09:09 | 33.60 | 24.88 |
August | 0.150686E+11 | 18834.32 | 20-AUG-11:42 | 32.12 | 26.12 | 0.690724E+09 | 845.59 | 07-AUG-13:30 | 32.12 | 26.12 |
September | 0.121052E+11 | 18439.38 | 04-SEP-14:22 | 30.30 | 24.25 | 0.613695E+09 | 845.60 | 05-SEP-13:09 | 25.73 | 23.35 |
October | 0.111289E+11 | 14807.71 | 19-OCT-04:11 | 23.30 | 18.68 | 0.637578E+09 | 845.60 | 10-OCT-13:09 | 23.30 | 18.68 |
November | 0.934898E+10 | 14078.12 | 20-NOV-06:02 | 24.40 | 20.29 | 0.629138E+09 | 845.64 | 27-NOV-10:50 | 21.65 | 16.17 |
December | 0.777355E+10 | 13837.07 | 01-DEC-05:11 | 22.57 | 18.22 | 0.605283E+09 | 845.62 | 15-DEC-14:30 | 19.45 | 14.42 |
Annual Sum or Average | 0.129667E+12 | 0.760339E+10 | ||||||||
Minimum of Months | 0.607659E+10 | 10831.86 | 20.40 | 18.22 | 0.570998E+09 | 845.59 | 19.45 | 14.42 | ||
Maximum of Months | 0.150686E+11 | 19309.23 | 33.60 | 26.12 | 0.690724E+09 | 845.64 | 33.60 | 26.12 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.566865E+10 | 19640.16 | 01-JAN-09:02 | 23.17 | 20.57 | 0.404211E+09 | 544.98 | 27-JAN-10:00 | 21.70 | 15.05 |
February | 0.603970E+10 | 14796.86 | 20-FEB-09:23 | 19.45 | 16.01 | 0.368555E+09 | 544.95 | 21-FEB-14:09 | 25.68 | 14.65 |
March | 0.827682E+10 | 10668.44 | 27-MAR-08:40 | 23.17 | 21.01 | 0.441595E+09 | 544.97 | 17-MAR-09:09 | 23.17 | 21.01 |
April | 0.974997E+10 | 19906.07 | 09-APR-09:22 | 25.00 | 18.86 | 0.393337E+09 | 544.94 | 18-APR-09:00 | 20.60 | 14.15 |
May | 0.104332E+11 | 19820.26 | 07-MAY-08:52 | 26.70 | 21.74 | 0.427825E+09 | 544.93 | 31-MAY-09:20 | 29.97 | 24.08 |
June | 0.111761E+11 | 20583.32 | 11-JUN-09:32 | 30.40 | 23.99 | 0.426645E+09 | 544.93 | 14-JUN-09:39 | 28.53 | 23.70 |
July | 0.118667E+11 | 20483.40 | 16-JUL-09:12 | 29.40 | 23.81 | 0.396820E+09 | 544.93 | 03-JUL-13:09 | 29.40 | 23.81 |
August | 0.115443E+11 | 19040.36 | 20-AUG-11:42 | 32.12 | 26.12 | 0.444111E+09 | 544.93 | 08-AUG-09:39 | 32.12 | 26.12 |
September | 0.102306E+11 | 17312.22 | 10-SEP-09:52 | 30.00 | 24.68 | 0.395394E+09 | 544.94 | 05-SEP-13:09 | 30.00 | 24.68 |
October | 0.951963E+10 | 19895.32 | 09-OCT-08:42 | 28.12 | 24.23 | 0.410094E+09 | 544.94 | 10-OCT-13:09 | 23.77 | 22.52 |
November | 0.757174E+10 | 9800.43 | 07-NOV-09:00 | 23.90 | 21.61 | 0.404661E+09 | 544.97 | 27-NOV-10:50 | 21.65 | 16.17 |
December | 0.622347E+10 | 7948.88 | 03-DEC-10:02 | 21.28 | 17.34 | 0.386570E+09 | 544.95 | 27-DEC-10:09 | 13.58 | 11.53 |
Annual Sum or Average | 0.108301E+12 | 0.489982E+10 | ||||||||
Minimum of Months | 0.566865E+10 | 7948.88 | 19.45 | 16.01 | 0.368555E+09 | 544.93 | 13.58 | 11.53 | ||
Maximum of Months | 0.118667E+11 | 20583.32 | 32.12 | 26.12 | 0.444111E+09 | 544.98 | 32.12 | 26.12 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.119964E+11 | 21393.94 | 15-JAN-13:52 | 25.60 | 16.48 | 0.638860E+09 | 954.25 | 02-JAN-14:39 | 25.60 | 16.48 |
February | 0.115473E+11 | 20967.20 | 20-FEB-12:02 | 23.98 | 17.32 | 0.581031E+09 | 930.59 | 21-FEB-14:30 | 25.85 | 14.25 |
March | 0.130722E+11 | 19769.69 | 12-MAR-13:32 | 24.80 | 18.27 | 0.687327E+09 | 893.02 | 01-MAR-14:39 | 24.80 | 18.27 |
April | 0.127593E+11 | 19073.57 | 09-APR-13:22 | 27.75 | 19.36 | 0.612643E+09 | 845.63 | 18-APR-13:09 | 22.38 | 14.69 |
May | 0.122155E+11 | 17332.10 | 29-MAY-15:52 | 33.30 | 24.52 | 0.664411E+09 | 845.61 | 23-MAY-13:09 | 33.30 | 24.52 |
June | 0.134009E+11 | 18467.82 | 11-JUN-16:11 | 30.93 | 24.21 | 0.662250E+09 | 845.61 | 21-JUN-13:20 | 29.40 | 23.58 |
July | 0.145856E+11 | 19573.08 | 30-JUL-14:22 | 33.60 | 24.88 | 0.615838E+09 | 845.61 | 10-JUL-09:09 | 33.60 | 24.88 |
August | 0.160098E+11 | 19470.38 | 20-AUG-12:22 | 32.20 | 25.83 | 0.690905E+09 | 850.39 | 31-AUG-13:20 | 31.70 | 24.32 |
September | 0.149229E+11 | 19883.92 | 24-SEP-11:43 | 31.10 | 25.02 | 0.614688E+09 | 868.86 | 29-SEP-13:09 | 31.10 | 24.17 |
October | 0.163470E+11 | 21938.18 | 29-OCT-12:41 | 30.10 | 25.68 | 0.643768E+09 | 908.01 | 25-OCT-13:20 | 30.10 | 25.68 |
November | 0.149832E+11 | 21522.61 | 19-NOV-12:42 | 26.70 | 21.27 | 0.640824E+09 | 961.20 | 07-NOV-14:09 | 26.70 | 21.27 |
December | 0.137795E+11 | 22594.59 | 03-DEC-14:01 | 24.40 | 18.40 | 0.618718E+09 | 974.34 | 04-DEC-14:39 | 25.93 | 17.99 |
Annual Sum or Average | 0.165620E+12 | 0.767126E+10 | ||||||||
Minimum of Months | 0.115473E+11 | 17332.10 | 23.98 | 16.48 | 0.581031E+09 | 845.61 | 22.38 | 14.25 | ||
Maximum of Months | 0.163470E+11 | 22594.59 | 33.60 | 25.83 | 0.690905E+09 | 974.34 | 33.60 | 25.68 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.719341E+10 | 18398.49 | 30-JAN-05:12 | 20.73 | 20.35 | 0.398711E+09 | 544.94 | 20-JAN-14:20 | 20.73 | 20.35 |
February | 0.838537E+10 | 25330.25 | 19-FEB-16:12 | 27.03 | 21.82 | 0.370376E+09 | 544.95 | 21-FEB-14:09 | 25.68 | 14.65 |
March | 0.123804E+11 | 25598.06 | 12-MAR-16:12 | 24.40 | 18.45 | 0.443882E+09 | 544.95 | 17-MAR-13:09 | 21.20 | 14.87 |
April | 0.152838E+11 | 26855.61 | 09-APR-16:41 | 26.78 | 18.46 | 0.396132E+09 | 544.94 | 18-APR-13:09 | 22.38 | 14.69 |
May | 0.127784E+11 | 25377.48 | 29-MAY-16:32 | 32.23 | 24.43 | 0.428614E+09 | 544.93 | 23-MAY-13:09 | 32.23 | 24.43 |
June | 0.141317E+11 | 26623.32 | 11-JUN-14:51 | 31.10 | 24.60 | 0.427299E+09 | 544.93 | 21-JUN-13:30 | 29.40 | 23.64 |
July | 0.163712E+11 | 26233.66 | 09-JUL-16:31 | 30.37 | 25.12 | 0.397585E+09 | 544.94 | 10-JUL-09:09 | 25.37 | 23.57 |
August | 0.184203E+11 | 26423.02 | 20-AUG-16:21 | 30.60 | 24.86 | 0.446114E+09 | 544.93 | 07-AUG-13:30 | 30.60 | 24.86 |
September | 0.122087E+11 | 25245.39 | 17-SEP-16:02 | 31.10 | 24.89 | 0.395821E+09 | 544.94 | 05-SEP-13:09 | 31.10 | 24.89 |
October | 0.127318E+11 | 26315.95 | 09-OCT-15:22 | 30.00 | 23.98 | 0.411768E+09 | 544.94 | 26-OCT-13:50 | 22.98 | 21.43 |
November | 0.114268E+11 | 25665.21 | 26-NOV-15:02 | 21.70 | 12.62 | 0.407280E+09 | 544.97 | 27-NOV-10:50 | 21.65 | 16.17 |
December | 0.109498E+11 | 27154.46 | 03-DEC-15:21 | 24.40 | 18.03 | 0.396235E+09 | 544.96 | 15-DEC-14:09 | 19.08 | 14.19 |
Annual Sum or Average | 0.152262E+12 | 0.491982E+10 | ||||||||
Minimum of Months | 0.719341E+10 | 18398.49 | 20.73 | 12.62 | 0.370376E+09 | 544.93 | 19.08 | 14.19 | ||
Maximum of Months | 0.184203E+11 | 27154.46 | 32.23 | 25.12 | 0.446114E+09 | 544.97 | 32.23 | 24.89 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.474049E+10 | 9956.79 | 14-JAN-06:03 | 23.62 | 21.60 | 0.582500E+09 | 845.59 | 30-JAN-14:09 | 16.60 | 15.83 |
February | 0.499241E+10 | 10552.93 | 18-FEB-06:03 | 23.40 | 20.68 | 0.551577E+09 | 845.60 | 21-FEB-14:09 | 25.68 | 14.65 |
March | 0.652844E+10 | 11947.51 | 06-MAR-06:02 | 22.80 | 22.00 | 0.658292E+09 | 845.59 | 01-MAR-14:20 | 22.80 | 22.00 |
April | 0.786852E+10 | 10901.71 | 15-APR-05:03 | 22.20 | 21.04 | 0.609076E+09 | 845.61 | 18-APR-13:09 | 22.38 | 14.69 |
May | 0.109240E+11 | 18851.34 | 29-MAY-15:41 | 33.22 | 24.49 | 0.664467E+09 | 845.59 | 23-MAY-13:09 | 33.22 | 24.49 |
June | 0.123578E+11 | 17974.34 | 25-JUN-14:32 | 30.37 | 24.89 | 0.662806E+09 | 845.59 | 21-JUN-13:30 | 30.37 | 24.89 |
July | 0.126102E+11 | 18629.78 | 04-JUL-16:31 | 30.57 | 25.19 | 0.616310E+09 | 845.59 | 03-JUL-13:09 | 30.57 | 25.19 |
August | 0.118397E+11 | 15928.24 | 20-AUG-12:22 | 32.20 | 25.83 | 0.690846E+09 | 845.59 | 08-AUG-09:00 | 32.20 | 25.83 |
September | 0.107401E+11 | 17822.50 | 17-SEP-15:51 | 31.10 | 24.95 | 0.613606E+09 | 845.59 | 05-SEP-13:09 | 31.10 | 24.95 |
October | 0.898929E+10 | 13687.13 | 19-OCT-04:11 | 23.30 | 18.68 | 0.636866E+09 | 845.59 | 06-OCT-13:20 | 23.30 | 18.68 |
November | 0.683084E+10 | 13131.24 | 29-NOV-06:03 | 25.00 | 19.84 | 0.620607E+09 | 845.59 | 14-NOV-14:20 | 25.00 | 19.84 |
December | 0.510698E+10 | 12997.27 | 09-DEC-06:02 | 24.90 | 22.63 | 0.568608E+09 | 845.59 | 26-DEC-14:00 | 19.40 | 13.57 |
Annual Sum or Average | 0.103529E+12 | 0.747556E+10 | ||||||||
Minimum of Months | 0.474049E+10 | 9956.79 | 22.20 | 18.68 | 0.551577E+09 | 845.59 | 16.60 | 13.57 | ||
Maximum of Months | 0.126102E+11 | 18851.34 | 33.22 | 25.83 | 0.690846E+09 | 845.61 | 33.22 | 25.83 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.482807E+10 | 19846.44 | 01-JAN-10:12 | 25.57 | 21.29 | 0.287075E+09 | 521.24 | 27-JAN-11:09 | 21.88 | 15.22 |
February | 0.519864E+10 | 12432.78 | 26-FEB-10:02 | 22.48 | 16.09 | 0.265569E+09 | 521.21 | 21-FEB-13:30 | 22.48 | 16.09 |
March | 0.693672E+10 | 10311.04 | 27-MAR-10:20 | 25.57 | 21.63 | 0.321205E+09 | 521.24 | 17-MAR-10:00 | 25.57 | 21.63 |
April | 0.834985E+10 | 20784.34 | 09-APR-09:22 | 25.00 | 18.86 | 0.289188E+09 | 521.21 | 18-APR-10:09 | 20.78 | 14.20 |
May | 0.994707E+10 | 20712.56 | 07-MAY-10:22 | 28.60 | 21.92 | 0.314651E+09 | 521.19 | 01-MAY-10:20 | 28.60 | 21.92 |
June | 0.105459E+11 | 19920.43 | 11-JUN-09:42 | 30.50 | 23.90 | 0.313998E+09 | 521.19 | 20-JUN-10:20 | 26.70 | 24.08 |
July | 0.110157E+11 | 21706.66 | 04-JUL-08:32 | 28.87 | 24.11 | 0.293158E+09 | 521.19 | 07-JUL-12:09 | 33.62 | 23.53 |
August | 0.103741E+11 | 20468.26 | 27-AUG-09:32 | 30.53 | 25.44 | 0.326759E+09 | 521.20 | 08-AUG-10:20 | 30.53 | 25.44 |
September | 0.977351E+10 | 20685.25 | 24-SEP-08:52 | 29.40 | 25.76 | 0.291209E+09 | 521.19 | 06-SEP-14:20 | 29.40 | 25.76 |
October | 0.860037E+10 | 20544.24 | 09-OCT-08:52 | 28.30 | 24.27 | 0.302045E+09 | 521.19 | 17-OCT-10:20 | 27.20 | 18.83 |
November | 0.636277E+10 | 9722.86 | 07-NOV-09:30 | 24.75 | 21.38 | 0.295880E+09 | 521.22 | 13-NOV-11:20 | 21.83 | 15.41 |
December | 0.477849E+10 | 7788.98 | 08-DEC-10:00 | 26.10 | 22.56 | 0.271605E+09 | 521.19 | 04-DEC-11:20 | 26.10 | 22.56 |
Annual Sum or Average | 0.967112E+11 | 0.357234E+10 | ||||||||
Minimum of Months | 0.477849E+10 | 7788.98 | 22.48 | 16.09 | 0.265569E+09 | 521.19 | 20.78 | 14.20 | ||
Maximum of Months | 0.110157E+11 | 21706.66 | 30.53 | 25.76 | 0.326759E+09 | 521.24 | 33.62 | 25.76 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.111268E+11 | 20596.89 | 01-JAN-13:32 | 26.47 | 21.74 | 0.638180E+09 | 986.73 | 02-JAN-14:39 | 28.90 | 23.86 |
February | 0.103116E+11 | 19973.65 | 26-FEB-12:42 | 24.82 | 16.09 | 0.579048E+09 | 950.88 | 21-FEB-14:50 | 24.82 | 16.09 |
March | 0.107599E+11 | 19381.77 | 26-MAR-13:52 | 27.80 | 22.40 | 0.681612E+09 | 912.09 | 01-MAR-14:39 | 27.80 | 22.40 |
April | 0.975925E+10 | 17771.51 | 16-APR-17:12 | 31.10 | 21.99 | 0.611332E+09 | 845.63 | 18-APR-13:09 | 22.38 | 14.69 |
May | 0.108699E+11 | 18664.92 | 29-MAY-15:41 | 33.22 | 24.49 | 0.664288E+09 | 845.60 | 23-MAY-13:09 | 33.22 | 24.49 |
June | 0.116306E+11 | 17585.42 | 25-JUN-14:32 | 30.37 | 24.89 | 0.662478E+09 | 845.61 | 21-JUN-13:30 | 30.37 | 24.89 |
July | 0.122187E+11 | 18131.76 | 04-JUL-15:51 | 31.70 | 25.12 | 0.616060E+09 | 845.60 | 03-JUL-13:09 | 31.70 | 25.12 |
August | 0.129467E+11 | 18500.46 | 20-AUG-12:22 | 32.20 | 25.83 | 0.691173E+09 | 851.43 | 31-AUG-13:20 | 31.70 | 24.32 |
September | 0.138852E+11 | 19736.86 | 17-SEP-14:31 | 31.10 | 24.59 | 0.615253E+09 | 890.47 | 29-SEP-13:09 | 31.10 | 24.17 |
October | 0.148179E+11 | 21080.94 | 29-OCT-12:11 | 30.40 | 25.20 | 0.647644E+09 | 939.36 | 25-OCT-13:00 | 30.40 | 25.20 |
November | 0.130672E+11 | 20732.66 | 19-NOV-13:52 | 26.70 | 21.27 | 0.643589E+09 | 1002.64 | 07-NOV-14:20 | 26.70 | 21.27 |
December | 0.114460E+11 | 22022.21 | 03-DEC-13:51 | 24.40 | 18.35 | 0.613774E+09 | 1006.19 | 04-DEC-14:39 | 25.93 | 17.99 |
Annual Sum or Average | 0.142840E+12 | 0.766443E+10 | ||||||||
Minimum of Months | 0.975925E+10 | 17585.42 | 24.40 | 16.09 | 0.579048E+09 | 845.60 | 22.38 | 14.69 | ||
Maximum of Months | 0.148179E+11 | 22022.21 | 33.22 | 25.83 | 0.691173E+09 | 1006.19 | 33.22 | 25.20 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.520608E+10 | 9761.42 | 14-JAN-06:03 | 23.62 | 21.60 | 0.372970E+09 | 544.93 | 09-JAN-14:00 | 23.62 | 21.60 |
February | 0.562516E+10 | 22455.48 | 19-FEB-16:01 | 27.12 | 21.84 | 0.352861E+09 | 544.94 | 21-FEB-14:09 | 25.68 | 14.65 |
March | 0.763035E+10 | 20505.92 | 12-MAR-16:22 | 24.40 | 18.50 | 0.425108E+09 | 544.93 | 22-MAR-13:39 | 23.30 | 17.33 |
April | 0.898312E+10 | 24422.33 | 02-APR-16:41 | 25.78 | 18.10 | 0.392659E+09 | 544.94 | 18-APR-13:09 | 22.38 | 14.69 |
May | 0.103640E+11 | 24716.95 | 29-MAY-15:41 | 33.22 | 24.49 | 0.427650E+09 | 544.93 | 23-MAY-13:09 | 33.22 | 24.49 |
June | 0.103874E+11 | 21607.22 | 25-JUN-14:32 | 30.37 | 24.89 | 0.426818E+09 | 544.93 | 21-JUN-13:30 | 30.37 | 24.89 |
July | 0.112948E+11 | 24581.35 | 04-JUL-16:31 | 30.57 | 25.19 | 0.397142E+09 | 544.93 | 03-JUL-13:09 | 30.57 | 25.19 |
August | 0.111972E+11 | 22980.15 | 13-AUG-16:01 | 30.50 | 25.69 | 0.445182E+09 | 544.93 | 08-AUG-09:00 | 30.50 | 25.69 |
September | 0.971491E+10 | 24642.79 | 17-SEP-15:51 | 31.10 | 24.95 | 0.394934E+09 | 544.93 | 05-SEP-13:09 | 31.10 | 24.95 |
October | 0.890599E+10 | 23371.89 | 09-OCT-16:12 | 29.23 | 23.77 | 0.409891E+09 | 544.93 | 06-OCT-13:30 | 29.23 | 23.77 |
November | 0.687947E+10 | 18263.68 | 19-NOV-15:12 | 26.70 | 20.63 | 0.397798E+09 | 544.93 | 14-NOV-14:00 | 26.70 | 20.63 |
December | 0.574404E+10 | 23062.63 | 10-DEC-15:41 | 28.40 | 22.53 | 0.366025E+09 | 544.95 | 13-DEC-14:00 | 21.70 | 13.99 |
Annual Sum or Average | 0.101933E+12 | 0.480904E+10 | ||||||||
Minimum of Months | 0.520608E+10 | 9761.42 | 23.62 | 18.10 | 0.352861E+09 | 544.93 | 21.70 | 13.99 | ||
Maximum of Months | 0.112948E+11 | 24716.95 | 33.22 | 25.69 | 0.445182E+09 | 544.95 | 33.22 | 25.69 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.440025E+10 | 7913.15 | 14-JAN-06:03 | 23.62 | 21.60 | 0.566164E+09 | 845.59 | 30-JAN-14:09 | 16.60 | 15.83 |
February | 0.486328E+10 | 8341.34 | 18-FEB-06:03 | 23.40 | 20.68 | 0.542239E+09 | 845.60 | 21-FEB-14:00 | 26.10 | 13.62 |
March | 0.654972E+10 | 13423.55 | 06-MAR-06:02 | 22.80 | 22.00 | 0.650324E+09 | 845.59 | 22-MAR-13:09 | 23.30 | 16.73 |
April | 0.818931E+10 | 13861.87 | 16-APR-17:12 | 31.10 | 21.99 | 0.606096E+09 | 845.61 | 18-APR-13:09 | 22.38 | 14.69 |
May | 0.115326E+11 | 21484.45 | 29-MAY-15:41 | 33.22 | 24.49 | 0.664328E+09 | 845.58 | 23-MAY-13:09 | 33.22 | 24.49 |
June | 0.130745E+11 | 20361.45 | 25-JUN-14:32 | 30.37 | 24.89 | 0.662937E+09 | 845.59 | 21-JUN-13:30 | 30.37 | 24.89 |
July | 0.134778E+11 | 21255.36 | 04-JUL-16:31 | 30.57 | 25.19 | 0.616542E+09 | 845.58 | 03-JUL-13:09 | 30.57 | 25.19 |
August | 0.125218E+11 | 20263.94 | 20-AUG-12:12 | 32.20 | 25.92 | 0.690674E+09 | 845.59 | 08-AUG-09:00 | 32.20 | 25.92 |
September | 0.113008E+11 | 20626.91 | 17-SEP-15:51 | 31.10 | 24.95 | 0.613399E+09 | 845.60 | 05-SEP-13:09 | 31.10 | 24.95 |
October | 0.921350E+10 | 15244.23 | 31-OCT-05:02 | 22.12 | 21.74 | 0.635665E+09 | 845.59 | 27-OCT-13:00 | 22.12 | 21.74 |
November | 0.682939E+10 | 14840.62 | 10-NOV-06:02 | 22.70 | 22.40 | 0.613903E+09 | 845.59 | 14-NOV-14:09 | 23.90 | 15.88 |
December | 0.487112E+10 | 10436.09 | 09-DEC-06:02 | 24.90 | 22.63 | 0.553739E+09 | 845.60 | 26-DEC-14:00 | 19.40 | 13.57 |
Annual Sum or Average | 0.106824E+12 | 0.741601E+10 | ||||||||
Minimum of Months | 0.440025E+10 | 7913.15 | 22.12 | 20.68 | 0.542239E+09 | 845.58 | 16.60 | 13.57 | ||
Maximum of Months | 0.134778E+11 | 21484.45 | 33.22 | 25.92 | 0.690674E+09 | 845.61 | 33.22 | 25.92 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.452996E+10 | 7564.00 | 01-JAN-10:32 | 26.13 | 21.45 | 0.386907E+09 | 544.98 | 27-JAN-10:00 | 21.70 | 15.05 |
February | 0.508690E+10 | 8133.23 | 28-FEB-10:10 | 24.40 | 16.25 | 0.359919E+09 | 544.95 | 21-FEB-14:00 | 24.40 | 16.25 |
March | 0.693404E+10 | 10632.57 | 31-MAR-09:30 | 24.15 | 19.41 | 0.437049E+09 | 544.97 | 17-MAR-09:09 | 24.15 | 19.41 |
April | 0.859608E+10 | 20214.51 | 16-APR-09:52 | 27.20 | 21.71 | 0.392598E+09 | 544.95 | 18-APR-09:20 | 19.80 | 13.68 |
May | 0.104318E+11 | 20989.69 | 07-MAY-10:32 | 28.70 | 21.94 | 0.427629E+09 | 544.93 | 23-MAY-13:09 | 29.60 | 23.18 |
June | 0.111347E+11 | 20277.75 | 11-JUN-09:42 | 30.50 | 23.90 | 0.427129E+09 | 544.93 | 21-JUN-13:30 | 29.40 | 23.64 |
July | 0.117141E+11 | 21982.11 | 04-JUL-08:32 | 28.87 | 24.11 | 0.397418E+09 | 544.93 | 03-JUL-13:09 | 28.87 | 24.11 |
August | 0.109382E+11 | 20900.11 | 20-AUG-08:52 | 29.40 | 24.64 | 0.444627E+09 | 544.93 | 08-AUG-09:39 | 29.40 | 24.64 |
September | 0.102485E+11 | 21008.81 | 24-SEP-08:52 | 29.40 | 25.76 | 0.395290E+09 | 544.94 | 05-SEP-13:09 | 29.40 | 25.76 |
October | 0.881464E+10 | 17943.95 | 22-OCT-09:53 | 28.30 | 22.50 | 0.409767E+09 | 544.93 | 27-OCT-13:00 | 25.00 | 23.72 |
November | 0.638248E+10 | 9934.87 | 10-NOV-06:02 | 22.70 | 22.40 | 0.400427E+09 | 544.96 | 13-NOV-10:20 | 19.97 | 14.10 |
December | 0.460532E+10 | 7655.18 | 08-DEC-10:30 | 26.65 | 22.70 | 0.364616E+09 | 544.94 | 26-DEC-14:39 | 19.40 | 13.57 |
Annual Sum or Average | 0.994166E+11 | 0.484338E+10 | ||||||||
Minimum of Months | 0.452996E+10 | 7564.00 | 22.70 | 16.25 | 0.359919E+09 | 544.93 | 19.40 | 13.57 | ||
Maximum of Months | 0.117141E+11 | 21982.11 | 30.50 | 25.76 | 0.444627E+09 | 544.98 | 29.60 | 25.76 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.104896E+11 | 22811.27 | 15-JAN-14:22 | 25.60 | 16.75 | 0.624898E+09 | 948.63 | 02-JAN-14:39 | 25.60 | 16.75 |
February | 0.100463E+11 | 22055.90 | 26-FEB-14:32 | 25.60 | 16.51 | 0.570968E+09 | 917.01 | 21-FEB-14:50 | 25.60 | 16.51 |
March | 0.106659E+11 | 20939.05 | 12-MAR-14:12 | 24.80 | 18.16 | 0.674649E+09 | 876.50 | 01-MAR-14:39 | 24.80 | 18.16 |
April | 0.100474E+11 | 20166.64 | 16-APR-17:12 | 31.10 | 21.99 | 0.608878E+09 | 845.63 | 18-APR-13:09 | 22.38 | 14.69 |
May | 0.114759E+11 | 21453.44 | 29-MAY-15:41 | 33.22 | 24.49 | 0.663978E+09 | 845.60 | 23-MAY-13:09 | 33.22 | 24.49 |
June | 0.123420E+11 | 20212.53 | 25-JUN-14:32 | 30.37 | 24.89 | 0.662587E+09 | 845.61 | 21-JUN-13:30 | 30.37 | 24.89 |
July | 0.130751E+11 | 21039.89 | 04-JUL-15:51 | 31.70 | 25.12 | 0.616279E+09 | 845.60 | 03-JUL-13:09 | 31.70 | 25.12 |
August | 0.136262E+11 | 20953.53 | 20-AUG-12:12 | 32.20 | 25.92 | 0.690932E+09 | 845.60 | 08-AUG-09:00 | 32.20 | 25.92 |
September | 0.144683E+11 | 22485.72 | 17-SEP-14:31 | 31.10 | 24.59 | 0.614662E+09 | 870.69 | 29-SEP-13:09 | 31.10 | 24.17 |
October | 0.150367E+11 | 22095.32 | 29-OCT-13:02 | 30.00 | 25.83 | 0.643201E+09 | 913.06 | 25-OCT-13:00 | 30.00 | 25.83 |
November | 0.129250E+11 | 22011.74 | 19-NOV-15:32 | 26.70 | 20.63 | 0.635668E+09 | 964.02 | 07-NOV-14:20 | 26.70 | 20.63 |
December | 0.109317E+11 | 23683.18 | 10-DEC-15:01 | 28.80 | 22.65 | 0.602162E+09 | 963.44 | 04-DEC-14:39 | 28.80 | 22.65 |
Annual Sum or Average | 0.145130E+12 | 0.760886E+10 | ||||||||
Minimum of Months | 0.100463E+11 | 20166.64 | 24.80 | 16.51 | 0.570968E+09 | 845.60 | 22.38 | 14.69 | ||
Maximum of Months | 0.150367E+11 | 23683.18 | 33.22 | 25.92 | 0.690932E+09 | 964.02 | 33.22 | 25.92 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.501375E+10 | 9285.15 | 03-JAN-15:40 | 26.70 | 20.74 | 0.363147E+09 | 544.93 | 04-JAN-14:39 | 25.20 | 21.01 |
February | 0.559375E+10 | 23473.04 | 19-FEB-16:12 | 27.03 | 21.82 | 0.346075E+09 | 544.96 | 21-FEB-14:00 | 26.10 | 13.62 |
March | 0.767558E+10 | 23511.09 | 12-MAR-16:52 | 24.40 | 18.65 | 0.419006E+09 | 544.93 | 02-MAR-14:00 | 24.40 | 18.65 |
April | 0.924093E+10 | 24226.56 | 09-APR-16:12 | 27.03 | 18.57 | 0.389470E+09 | 544.94 | 18-APR-13:09 | 22.38 | 14.69 |
May | 0.108197E+11 | 26754.78 | 29-MAY-15:41 | 33.22 | 24.49 | 0.426535E+09 | 544.93 | 23-MAY-13:09 | 33.22 | 24.49 |
June | 0.109263E+11 | 23330.16 | 25-JUN-14:32 | 30.37 | 24.89 | 0.426231E+09 | 544.93 | 21-JUN-13:30 | 30.37 | 24.89 |
July | 0.119327E+11 | 26630.39 | 04-JUL-16:31 | 30.57 | 25.19 | 0.396717E+09 | 544.93 | 10-JUL-09:09 | 25.37 | 23.57 |
August | 0.117027E+11 | 24661.09 | 20-AUG-16:11 | 30.60 | 24.86 | 0.444516E+09 | 544.93 | 08-AUG-09:00 | 30.60 | 24.86 |
September | 0.101604E+11 | 26631.76 | 17-SEP-15:51 | 31.10 | 24.95 | 0.393730E+09 | 544.93 | 05-SEP-13:09 | 31.10 | 24.95 |
October | 0.911058E+10 | 23821.27 | 22-OCT-15:52 | 28.30 | 23.16 | 0.407794E+09 | 544.93 | 27-OCT-13:00 | 25.00 | 23.72 |
November | 0.692110E+10 | 18059.14 | 19-NOV-15:32 | 26.70 | 20.63 | 0.392508E+09 | 544.93 | 14-NOV-14:00 | 26.70 | 20.63 |
December | 0.562102E+10 | 24565.87 | 10-DEC-15:41 | 28.40 | 22.53 | 0.357130E+09 | 544.95 | 13-DEC-14:00 | 21.70 | 13.99 |
Annual Sum or Average | 0.104718E+12 | 0.476286E+10 | ||||||||
Minimum of Months | 0.501375E+10 | 9285.15 | 24.40 | 18.57 | 0.346075E+09 | 544.93 | 21.70 | 13.62 | ||
Maximum of Months | 0.119327E+11 | 26754.78 | 33.22 | 25.19 | 0.444516E+09 | 544.96 | 33.22 | 24.95 |
Report: ZoneCoolingSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.602742E+10 | 11040.37 | 03-JAN-06:02 | 20.00 | 19.21 | 0.00 | 0.00 | 01-JAN-00:10 | 20.00 | 19.21 |
February | 0.646212E+10 | 10035.15 | 13-FEB-06:02 | 20.60 | 19.45 | 0.00 | 0.00 | 01-FEB-00:10 | 20.60 | 19.45 |
March | 0.838752E+10 | 9507.31 | 28-MAR-05:03 | 21.60 | 19.81 | 0.00 | 0.00 | 01-MAR-00:10 | 21.60 | 19.81 |
April | 0.990445E+10 | 10494.56 | 17-APR-05:03 | 18.90 | 16.76 | 0.00 | 0.00 | 01-APR-00:10 | 18.90 | 16.76 |
May | 0.108062E+11 | 11758.12 | 24-MAY-05:03 | 23.98 | 22.69 | 0.00 | 0.00 | 01-MAY-00:10 | 23.98 | 22.69 |
June | 0.121077E+11 | 10096.38 | 06-JUN-05:02 | 23.98 | 23.24 | 0.00 | 0.00 | 01-JUN-00:10 | 23.98 | 23.24 |
July | 0.132448E+11 | 12347.95 | 05-JUL-05:03 | 25.68 | 23.38 | 0.00 | 0.00 | 01-JUL-00:10 | 25.68 | 23.38 |
August | 0.134536E+11 | 12447.08 | 21-AUG-05:15 | 27.20 | 24.60 | 0.00 | 0.00 | 01-AUG-00:10 | 27.20 | 24.60 |
September | 0.116166E+11 | 14310.38 | 18-SEP-05:02 | 27.70 | 24.16 | 0.00 | 0.00 | 01-SEP-00:10 | 27.70 | 24.16 |
October | 0.110153E+11 | 12409.81 | 16-OCT-05:02 | 22.20 | 20.71 | 0.00 | 0.00 | 01-OCT-00:10 | 22.20 | 20.71 |
November | 0.910754E+10 | 10423.69 | 08-NOV-06:03 | 21.10 | 20.29 | 0.00 | 0.00 | 01-NOV-00:10 | 21.10 | 20.29 |
December | 0.730306E+10 | 9783.35 | 11-DEC-06:03 | 22.20 | 21.65 | 0.00 | 0.00 | 01-DEC-00:10 | 22.20 | 21.65 |
Annual Sum or Average | 0.119436E+12 | 0.00 | ||||||||
Minimum of Months | 0.602742E+10 | 9507.31 | 18.90 | 16.76 | 0.00 | 0.00 | 18.90 | 16.76 | ||
Maximum of Months | 0.134536E+11 | 14310.38 | 27.70 | 24.60 | 0.00 | 0.00 | 27.70 | 24.60 |
Report: ZoneCoolingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.419608E+10 | 6538.48 | 02-JAN-17:00 | 25.00 | 20.39 | 0.00 | 0.00 | 01-JAN-00:10 | 25.00 | 20.39 |
February | 0.439792E+10 | 6366.66 | 04-FEB-06:02 | 5.50 | 1.97 | 0.00 | 0.00 | 01-FEB-00:10 | 5.50 | 1.97 |
March | 0.595769E+10 | 7436.76 | 30-MAR-16:00 | 26.10 | 19.47 | 0.00 | 0.00 | 01-MAR-00:10 | 26.10 | 19.47 |
April | 0.732363E+10 | 7814.30 | 14-APR-16:00 | 29.40 | 24.14 | 0.00 | 0.00 | 01-APR-00:10 | 29.40 | 24.14 |
May | 0.929655E+10 | 9792.34 | 20-MAY-05:03 | 26.02 | 22.19 | 0.00 | 0.00 | 01-MAY-00:10 | 26.02 | 22.19 |
June | 0.102883E+11 | 9982.47 | 28-JUN-05:02 | 26.70 | 23.67 | 0.00 | 0.00 | 01-JUN-00:10 | 26.70 | 23.67 |
July | 0.107883E+11 | 10465.30 | 06-JUL-05:02 | 23.90 | 22.23 | 0.00 | 0.00 | 01-JUL-00:10 | 23.90 | 22.23 |
August | 0.103360E+11 | 8886.65 | 23-AUG-15:50 | 30.78 | 25.26 | 0.00 | 0.00 | 01-AUG-00:10 | 30.78 | 25.26 |
September | 0.100871E+11 | 9964.79 | 30-SEP-05:03 | 24.40 | 22.82 | 0.00 | 0.00 | 01-SEP-00:10 | 24.40 | 22.82 |
October | 0.906595E+10 | 9456.08 | 25-OCT-05:03 | 22.80 | 21.21 | 0.00 | 0.00 | 01-OCT-00:10 | 22.80 | 21.21 |
November | 0.670488E+10 | 9858.52 | 10-NOV-06:02 | 22.70 | 22.40 | 0.00 | 0.00 | 01-NOV-00:10 | 22.70 | 22.40 |
December | 0.481369E+10 | 6973.94 | 08-DEC-17:00 | 25.60 | 22.81 | 0.00 | 0.00 | 01-DEC-00:10 | 25.60 | 22.81 |
Annual Sum or Average | 0.932561E+11 | 0.00 | ||||||||
Minimum of Months | 0.419608E+10 | 6366.66 | 5.50 | 1.97 | 0.00 | 0.00 | 5.50 | 1.97 | ||
Maximum of Months | 0.107883E+11 | 10465.30 | 30.78 | 25.26 | 0.00 | 0.00 | 30.78 | 25.26 |
Report: ZoneCoolingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.508548E+10 | 13611.83 | 02-JAN-15:00 | 28.90 | 23.37 | 0.00 | 0.00 | 01-JAN-00:10 | 28.90 | 23.37 |
February | 0.655184E+10 | 13649.34 | 17-FEB-14:10 | 26.70 | 21.67 | 0.00 | 0.00 | 01-FEB-00:10 | 26.70 | 21.67 |
March | 0.906720E+10 | 17514.89 | 27-MAR-15:00 | 27.80 | 22.40 | 0.00 | 0.00 | 01-MAR-00:10 | 27.80 | 22.40 |
April | 0.119933E+11 | 19786.67 | 13-APR-14:00 | 28.90 | 24.03 | 0.00 | 0.00 | 01-APR-00:10 | 28.90 | 24.03 |
May | 0.155159E+11 | 20809.66 | 22-MAY-13:40 | 34.07 | 23.58 | 0.00 | 0.00 | 01-MAY-00:10 | 34.07 | 23.58 |
June | 0.166559E+11 | 21707.51 | 09-JUN-14:00 | 31.10 | 24.95 | 0.00 | 0.00 | 01-JUN-00:10 | 31.10 | 24.95 |
July | 0.181274E+11 | 23127.28 | 28-JUL-15:30 | 35.00 | 25.05 | 0.00 | 0.00 | 01-JUL-00:10 | 35.00 | 25.05 |
August | 0.165188E+11 | 22275.12 | 23-AUG-14:00 | 32.20 | 25.37 | 0.00 | 0.00 | 01-AUG-00:10 | 32.20 | 25.37 |
September | 0.154614E+11 | 20538.77 | 08-SEP-14:50 | 32.12 | 23.49 | 0.00 | 0.00 | 01-SEP-00:10 | 32.12 | 23.49 |
October | 0.126882E+11 | 19845.84 | 06-OCT-13:10 | 29.82 | 23.71 | 0.00 | 0.00 | 01-OCT-00:10 | 29.82 | 23.71 |
November | 0.896442E+10 | 16072.50 | 10-NOV-14:30 | 28.90 | 24.27 | 0.00 | 0.00 | 01-NOV-00:10 | 28.90 | 24.27 |
December | 0.573406E+10 | 13910.53 | 08-DEC-14:40 | 27.40 | 22.79 | 0.00 | 0.00 | 01-DEC-00:10 | 27.40 | 22.79 |
Annual Sum or Average | 0.142364E+12 | 0.00 | ||||||||
Minimum of Months | 0.508548E+10 | 13611.83 | 26.70 | 21.67 | 0.00 | 0.00 | 26.70 | 21.67 | ||
Maximum of Months | 0.181274E+11 | 23127.28 | 35.00 | 25.37 | 0.00 | 0.00 | 35.00 | 25.37 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.434906E+10 | 2189.59 | 24-JAN-17:00 | 16.70 | 8.78 | 95235926.67 | 126.85 | 12-JAN-14:39 | 16.70 | 8.78 |
February | 0.867792E+10 | 4316.70 | 20-FEB-17:50 | 25.28 | 17.48 | 86408514.34 | 126.86 | 02-FEB-10:39 | 25.28 | 17.48 |
March | 0.147381E+11 | 7229.83 | 31-MAR-24:00 | 22.60 | 17.97 | 0.103245E+09 | 126.85 | 14-MAR-09:09 | 22.60 | 17.97 |
April | 0.192051E+11 | 7964.60 | 09-APR-17:50 | 25.78 | 18.40 | 91622079.17 | 127.01 | 14-APR-13:00 | 30.60 | 24.51 |
May | 0.478101E+10 | 3530.48 | 31-MAY-24:00 | 26.70 | 24.69 | 99234981.26 | 126.86 | 08-MAY-09:30 | 26.70 | 24.69 |
June | 0.947800E+10 | 5370.69 | 30-JUN-23:47 | 26.95 | 23.78 | 98985433.77 | 126.87 | 06-JUN-09:09 | 26.95 | 23.78 |
July | 0.148762E+11 | 7279.34 | 31-JUL-23:40 | 28.63 | 25.86 | 91894154.08 | 126.84 | 12-JUL-09:09 | 28.63 | 25.86 |
August | 0.200303E+11 | 7840.71 | 20-AUG-18:10 | 29.82 | 24.37 | 0.104301E+09 | 133.60 | 23-AUG-13:00 | 32.20 | 25.37 |
September | 0.464337E+10 | 3472.36 | 30-SEP-23:45 | 28.05 | 23.47 | 91605140.71 | 126.82 | 12-SEP-09:39 | 28.05 | 23.47 |
October | 0.980162E+10 | 5409.42 | 31-OCT-24:00 | 22.50 | 21.29 | 95253679.10 | 126.88 | 02-OCT-09:09 | 22.50 | 21.29 |
November | 0.143010E+11 | 6140.92 | 07-NOV-17:00 | 27.80 | 22.39 | 94311474.42 | 126.85 | 30-NOV-10:09 | 26.70 | 24.69 |
December | 0.197011E+11 | 8056.14 | 06-DEC-17:00 | 25.60 | 21.66 | 91882994.15 | 126.83 | 29-DEC-10:09 | 19.27 | 17.74 |
Annual Sum or Average | 0.144583E+12 | 0.114398E+10 | ||||||||
Minimum of Months | 0.434906E+10 | 2189.59 | 16.70 | 8.78 | 86408514.34 | 126.82 | 16.70 | 8.78 | ||
Maximum of Months | 0.200303E+11 | 8056.14 | 29.82 | 25.86 | 0.104301E+09 | 133.60 | 32.20 | 25.86 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.334899E+10 | 1983.74 | 24-JAN-17:00 | 16.70 | 8.78 | 95232655.99 | 126.84 | 23-JAN-14:39 | 16.70 | 8.78 |
February | 0.769381E+10 | 3948.68 | 21-FEB-17:50 | 24.60 | 13.54 | 86408170.10 | 126.86 | 02-FEB-10:00 | 24.60 | 13.54 |
March | 0.137278E+11 | 6990.36 | 31-MAR-24:00 | 22.60 | 17.97 | 0.103246E+09 | 126.85 | 10-MAR-10:00 | 22.60 | 17.97 |
April | 0.182487E+11 | 7474.09 | 09-APR-17:51 | 25.60 | 18.39 | 91614249.51 | 126.83 | 17-APR-09:20 | 22.60 | 19.95 |
May | 0.441534E+10 | 3403.30 | 31-MAY-24:00 | 26.70 | 24.69 | 99233575.14 | 126.85 | 22-MAY-13:09 | 26.70 | 24.69 |
June | 0.898309E+10 | 5192.07 | 30-JUN-23:53 | 26.90 | 23.74 | 98987483.74 | 126.87 | 23-JUN-13:00 | 26.90 | 23.74 |
July | 0.141371E+11 | 7010.33 | 31-JUL-23:55 | 28.60 | 26.07 | 91895885.09 | 126.85 | 12-JUL-09:09 | 28.60 | 26.07 |
August | 0.189326E+11 | 7417.31 | 30-AUG-16:00 | 29.40 | 23.81 | 0.103813E+09 | 132.40 | 23-AUG-13:50 | 29.40 | 23.81 |
September | 0.425087E+10 | 3291.46 | 30-SEP-23:45 | 28.05 | 23.47 | 91605142.58 | 126.82 | 25-SEP-09:09 | 28.05 | 23.47 |
October | 0.924208E+10 | 5094.44 | 31-OCT-24:00 | 22.50 | 21.29 | 95254864.81 | 126.87 | 04-OCT-13:09 | 22.50 | 21.29 |
November | 0.133752E+11 | 5844.75 | 07-NOV-17:00 | 27.80 | 22.39 | 94312796.93 | 126.85 | 24-NOV-14:00 | 22.80 | 21.96 |
December | 0.182062E+11 | 7639.80 | 06-DEC-17:00 | 25.60 | 21.66 | 91883478.21 | 126.83 | 29-DEC-10:09 | 19.27 | 17.74 |
Annual Sum or Average | 0.134562E+12 | 0.114349E+10 | ||||||||
Minimum of Months | 0.334899E+10 | 1983.74 | 16.70 | 8.78 | 86408170.10 | 126.82 | 16.70 | 8.78 | ||
Maximum of Months | 0.189326E+11 | 7639.80 | 29.40 | 26.07 | 0.103813E+09 | 132.40 | 29.40 | 26.07 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.279982E+10 | 2019.17 | 02-JAN-17:00 | 25.00 | 20.39 | 95232609.11 | 126.84 | 19-JAN-14:00 | 25.00 | 18.53 |
February | 0.737174E+10 | 4005.86 | 21-FEB-17:50 | 24.60 | 13.54 | 86408481.68 | 126.86 | 02-FEB-14:00 | 24.60 | 13.54 |
March | 0.135416E+11 | 6931.40 | 31-MAR-24:00 | 22.60 | 17.97 | 0.103246E+09 | 126.85 | 06-MAR-10:00 | 22.60 | 17.97 |
April | 0.182359E+11 | 7692.92 | 09-APR-17:51 | 25.60 | 18.39 | 91611219.87 | 126.83 | 17-APR-09:50 | 23.95 | 20.74 |
May | 0.449845E+10 | 3411.64 | 31-MAY-24:00 | 26.70 | 24.69 | 99234347.73 | 126.86 | 01-MAY-13:50 | 26.70 | 24.69 |
June | 0.908762E+10 | 5181.81 | 30-JUN-23:15 | 27.10 | 23.92 | 98986558.31 | 126.87 | 28-JUN-09:00 | 27.10 | 23.92 |
July | 0.142825E+11 | 7029.39 | 31-JUL-23:55 | 28.60 | 26.07 | 91895551.67 | 126.85 | 12-JUL-09:09 | 28.60 | 26.07 |
August | 0.190268E+11 | 7584.15 | 20-AUG-18:11 | 29.63 | 24.40 | 0.103625E+09 | 131.41 | 23-AUG-13:00 | 32.20 | 25.37 |
September | 0.432992E+10 | 3332.88 | 30-SEP-23:35 | 28.10 | 23.41 | 91605142.82 | 126.82 | 18-SEP-09:00 | 28.10 | 23.41 |
October | 0.922665E+10 | 5006.95 | 31-OCT-24:00 | 22.50 | 21.29 | 95254607.96 | 126.87 | 04-OCT-13:09 | 22.50 | 21.29 |
November | 0.131584E+11 | 5908.71 | 07-NOV-17:00 | 27.80 | 22.39 | 94312849.03 | 126.85 | 30-NOV-10:00 | 26.70 | 24.69 |
December | 0.177874E+11 | 7704.53 | 06-DEC-17:00 | 25.60 | 21.66 | 91883891.36 | 126.83 | 29-DEC-10:09 | 19.27 | 17.74 |
Annual Sum or Average | 0.133347E+12 | 0.114330E+10 | ||||||||
Minimum of Months | 0.279982E+10 | 2019.17 | 22.50 | 13.54 | 86408481.68 | 126.82 | 19.27 | 13.54 | ||
Maximum of Months | 0.190268E+11 | 7704.53 | 29.63 | 26.07 | 0.103625E+09 | 131.41 | 32.20 | 26.07 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.243730E+12 | 94484.31 | 02-JAN-17:00 | 25.00 | 20.39 | 0.206189E+10 | 2746.78 | 30-JAN-14:09 | 16.60 | 15.83 |
February | 0.440653E+12 | 185771.74 | 21-FEB-17:00 | 25.60 | 14.07 | 0.187055E+10 | 2746.27 | 02-FEB-10:39 | 25.60 | 14.07 |
March | 0.732904E+12 | 360095.23 | 31-MAR-24:00 | 22.60 | 17.97 | 0.223501E+10 | 2746.80 | 16-MAR-13:09 | 22.60 | 17.97 |
April | 0.943993E+12 | 370080.19 | 17-APR-21:02 | 23.22 | 17.86 | 0.207857E+10 | 3268.34 | 14-APR-13:00 | 23.22 | 17.86 |
May | 0.244034E+12 | 177048.12 | 31-MAY-24:00 | 26.70 | 24.69 | 0.214908E+10 | 2747.15 | 24-MAY-09:00 | 26.70 | 24.69 |
June | 0.472430E+12 | 268627.10 | 30-JUN-23:53 | 26.90 | 23.74 | 0.214292E+10 | 2746.67 | 05-JUN-13:00 | 26.90 | 23.74 |
July | 0.734143E+12 | 357520.45 | 31-JUL-23:35 | 28.63 | 25.86 | 0.198925E+10 | 2745.88 | 10-JUL-09:09 | 28.63 | 25.86 |
August | 0.972794E+12 | 370406.01 | 28-AUG-12:20 | 22.20 | 21.97 | 0.263707E+10 | 3590.13 | 23-AUG-13:39 | 22.20 | 21.97 |
September | 0.238470E+12 | 176973.82 | 30-SEP-23:53 | 28.00 | 23.53 | 0.198407E+10 | 2747.16 | 18-SEP-09:39 | 28.00 | 23.53 |
October | 0.490338E+12 | 269342.00 | 31-OCT-24:00 | 22.50 | 21.29 | 0.206208E+10 | 2746.71 | 04-OCT-09:09 | 22.50 | 21.29 |
November | 0.711795E+12 | 278116.79 | 07-NOV-17:00 | 27.80 | 22.39 | 0.204157E+10 | 2745.87 | 29-NOV-10:00 | 26.10 | 24.93 |
December | 0.979884E+12 | 369959.13 | 11-DEC-17:00 | 22.80 | 16.83 | 0.202207E+10 | 3079.95 | 08-DEC-14:00 | 22.80 | 16.83 |
Annual Sum or Average | 0.720517E+13 | 0.252741E+11 | ||||||||
Minimum of Months | 0.238470E+12 | 94484.31 | 22.20 | 14.07 | 0.187055E+10 | 2745.87 | 16.60 | 14.07 | ||
Maximum of Months | 0.979884E+12 | 370406.01 | 28.63 | 25.86 | 0.263707E+10 | 3590.13 | 28.63 | 25.86 |
Report: ZoneHeatingSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.139622E+09 | 12164.12 | 01-JAN-12:53 | 27.20 |
February | 0.169516E+09 | 12154.40 | 11-FEB-17:03 | 27.02 |
March | 0.155598E+09 | 11090.56 | 04-MAR-17:12 | 25.93 |
April | 0.281781E+09 | 20062.64 | 15-APR-16:01 | 31.70 |
May | 0.495691E+09 | 19106.14 | 29-MAY-16:22 | 32.50 |
June | 0.413692E+09 | 19653.25 | 10-JUN-16:01 | 31.52 |
July | 0.586778E+09 | 25123.71 | 29-JUL-16:01 | 35.40 |
August | 0.482727E+09 | 19847.55 | 19-AUG-16:01 | 31.60 |
September | 0.570699E+09 | 18582.12 | 30-SEP-16:02 | 31.02 |
October | 0.495156E+09 | 17925.83 | 14-OCT-16:03 | 31.23 |
November | 0.309756E+09 | 15352.93 | 05-NOV-16:33 | 27.80 |
December | 0.215025E+09 | 14507.84 | 10-DEC-15:03 | 28.80 |
Annual Sum or Average | 0.431604E+10 | |||
Minimum of Months | 0.139622E+09 | 11090.56 | 25.93 | |
Maximum of Months | 0.586778E+09 | 25123.71 | 35.40 |
Report: ZoneHeatingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 20.40 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 16.65 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 17.32 |
April | 0.00 | 0.00 | 01-APR-00:02 | 22.57 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 22.05 |
June | 0.00 | 0.00 | 01-JUN-00:02 | 26.68 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 26.83 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 28.60 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 27.05 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 27.93 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 22.40 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 24.10 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 16.65 | |
Maximum of Months | 0.00 | 0.00 | 28.60 |
Report: ZoneHeatingSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 20.40 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 16.65 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 17.32 |
April | 0.00 | 0.00 | 01-APR-00:02 | 22.57 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 22.05 |
June | 0.00 | 0.00 | 01-JUN-00:02 | 26.68 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 26.83 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 28.60 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 27.05 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 27.93 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 22.40 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 24.10 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 16.65 | |
Maximum of Months | 0.00 | 0.00 | 28.60 |
Report: ZoneHeatingSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 20.40 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 16.65 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 17.32 |
April | 0.00 | 0.00 | 01-APR-00:02 | 22.57 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 22.05 |
June | 0.00 | 0.00 | 01-JUN-00:02 | 26.68 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 26.83 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 28.60 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 27.05 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 27.93 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 22.40 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 24.10 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 16.65 | |
Maximum of Months | 0.00 | 0.00 | 28.60 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 20.40 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 16.65 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 17.32 |
April | 0.00 | 0.00 | 01-APR-00:02 | 22.57 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 22.05 |
June | 0.00 | 0.00 | 01-JUN-00:02 | 26.68 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 26.83 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 28.60 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 27.05 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 27.93 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 22.40 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 24.10 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 16.65 | |
Maximum of Months | 0.00 | 0.00 | 28.60 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 20.40 |
February | 80410.95 | 670.09 | 04-FEB-06:02 | 5.50 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 17.32 |
April | 0.00 | 0.00 | 01-APR-00:02 | 22.57 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 22.05 |
June | 0.00 | 0.00 | 01-JUN-00:02 | 26.68 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 26.83 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 28.60 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 27.05 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 27.93 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 22.40 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 24.10 |
Annual Sum or Average | 80410.95 | |||
Minimum of Months | 0.00 | 0.00 | 5.50 | |
Maximum of Months | 80410.95 | 670.09 | 28.60 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 20.40 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 16.65 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 17.32 |
April | 0.00 | 0.00 | 01-APR-00:02 | 22.57 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 22.05 |
June | 0.00 | 0.00 | 01-JUN-00:02 | 26.68 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 26.83 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 28.60 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 27.05 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 27.93 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 22.40 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 24.10 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 16.65 | |
Maximum of Months | 0.00 | 0.00 | 28.60 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 20.40 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 16.65 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 17.32 |
April | 0.00 | 0.00 | 01-APR-00:02 | 22.57 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 22.05 |
June | 0.00 | 0.00 | 01-JUN-00:02 | 26.68 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 26.83 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 28.60 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 27.05 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 27.93 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 22.40 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 24.10 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 16.65 | |
Maximum of Months | 0.00 | 0.00 | 28.60 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 11827241.48 | 12029.42 | 25-JAN-06:03 | 9.40 |
February | 36516381.72 | 12790.35 | 04-FEB-05:11 | 5.93 |
March | 10856006.76 | 12052.51 | 16-MAR-05:03 | 6.70 |
April | 0.00 | 0.00 | 01-APR-00:02 | 22.57 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 22.05 |
June | 0.00 | 0.00 | 01-JUN-00:02 | 26.68 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 26.83 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 28.60 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 27.05 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 27.93 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 22.40 |
December | 12072729.10 | 12029.78 | 15-DEC-06:02 | 7.80 |
Annual Sum or Average | 71272359.06 | |||
Minimum of Months | 0.00 | 0.00 | 5.93 | |
Maximum of Months | 36516381.72 | 12790.35 | 28.60 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 2234703.00 | 4154.93 | 25-JAN-06:03 | 9.40 |
February | 13882295.37 | 9468.34 | 04-FEB-05:11 | 5.93 |
March | 1757361.90 | 3283.26 | 16-MAR-05:03 | 6.70 |
April | 0.00 | 0.00 | 01-APR-00:02 | 22.57 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 22.05 |
June | 0.00 | 0.00 | 01-JUN-00:02 | 26.68 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 26.83 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 28.60 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 27.05 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 27.93 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 22.40 |
December | 3074262.56 | 6196.29 | 15-DEC-06:02 | 7.80 |
Annual Sum or Average | 20948622.84 | |||
Minimum of Months | 0.00 | 0.00 | 5.93 | |
Maximum of Months | 13882295.37 | 9468.34 | 28.60 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 20.40 |
February | 9398262.05 | 11849.15 | 04-FEB-06:02 | 5.50 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 17.32 |
April | 0.00 | 0.00 | 01-APR-00:02 | 22.57 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 22.05 |
June | 0.00 | 0.00 | 01-JUN-00:02 | 26.68 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 26.83 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 28.60 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 27.05 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 27.93 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 22.40 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 24.10 |
Annual Sum or Average | 9398262.05 | |||
Minimum of Months | 0.00 | 0.00 | 5.50 | |
Maximum of Months | 9398262.05 | 11849.15 | 28.60 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 20.40 |
February | 14562054.90 | 8500.42 | 04-FEB-05:11 | 5.93 |
March | 16332.91 | 108.89 | 16-MAR-05:05 | 6.70 |
April | 0.00 | 0.00 | 01-APR-00:02 | 22.57 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 22.05 |
June | 0.00 | 0.00 | 01-JUN-00:02 | 26.68 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 26.83 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 28.60 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 27.05 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 27.93 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 22.40 |
December | 271503.84 | 2199.65 | 15-DEC-06:02 | 7.80 |
Annual Sum or Average | 14849891.65 | |||
Minimum of Months | 0.00 | 0.00 | 5.93 | |
Maximum of Months | 14562054.90 | 8500.42 | 28.60 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.116626E+09 | 14571.43 | 25-JAN-05:12 | 9.40 |
February | 0.109945E+09 | 15960.59 | 04-FEB-05:11 | 5.93 |
March | 62554325.33 | 14736.16 | 16-MAR-04:12 | 7.43 |
April | 0.00 | 0.00 | 01-APR-00:02 | 22.57 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 22.05 |
June | 0.00 | 0.00 | 01-JUN-00:02 | 26.68 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 26.83 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 28.60 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 27.05 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 27.93 |
November | 25323354.02 | 14095.52 | 13-NOV-06:02 | 12.20 |
December | 0.127177E+09 | 14599.09 | 15-DEC-05:12 | 7.80 |
Annual Sum or Average | 0.441626E+09 | |||
Minimum of Months | 0.00 | 0.00 | 5.93 | |
Maximum of Months | 0.127177E+09 | 15960.59 | 28.60 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 37849919.06 | 10333.25 | 26-JAN-06:02 | 10.60 |
February | 37923622.83 | 12305.58 | 04-FEB-05:11 | 5.93 |
March | 17223593.94 | 9887.13 | 16-MAR-05:03 | 6.70 |
April | 0.00 | 0.00 | 01-APR-00:02 | 22.57 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 22.05 |
June | 0.00 | 0.00 | 01-JUN-00:02 | 26.68 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 26.83 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 28.60 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 27.05 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 27.93 |
November | 7297586.45 | 10405.62 | 13-NOV-06:02 | 12.20 |
December | 60949340.07 | 10313.55 | 15-DEC-06:02 | 7.80 |
Annual Sum or Average | 0.161244E+09 | |||
Minimum of Months | 0.00 | 0.00 | 5.93 | |
Maximum of Months | 60949340.07 | 12305.58 | 28.60 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 15236886.66 | 12936.15 | 25-JAN-06:03 | 9.40 |
February | 47429219.74 | 15247.50 | 04-FEB-05:11 | 5.93 |
March | 17566957.05 | 13721.06 | 16-MAR-05:03 | 6.70 |
April | 0.00 | 0.00 | 01-APR-00:02 | 22.57 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 22.05 |
June | 0.00 | 0.00 | 01-JUN-00:02 | 26.68 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 26.83 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 28.60 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 27.05 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 27.93 |
November | 4305699.45 | 13721.65 | 13-NOV-06:02 | 12.20 |
December | 29061242.91 | 13830.48 | 27-DEC-06:02 | 8.90 |
Annual Sum or Average | 0.113600E+09 | |||
Minimum of Months | 0.00 | 0.00 | 5.93 | |
Maximum of Months | 47429219.74 | 15247.50 | 28.60 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 21460438.70 | 9878.91 | 26-JAN-06:02 | 10.60 |
February | 46470083.55 | 11831.74 | 04-FEB-05:11 | 5.93 |
March | 10391750.49 | 9056.07 | 16-MAR-05:03 | 6.70 |
April | 0.00 | 0.00 | 01-APR-00:02 | 22.57 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 22.05 |
June | 0.00 | 0.00 | 01-JUN-00:02 | 26.68 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 26.83 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 28.60 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 27.05 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 27.93 |
November | 4580649.62 | 9892.14 | 13-NOV-06:02 | 12.20 |
December | 35092558.68 | 9955.25 | 15-DEC-06:02 | 7.80 |
Annual Sum or Average | 0.117995E+09 | |||
Minimum of Months | 0.00 | 0.00 | 5.93 | |
Maximum of Months | 46470083.55 | 11831.74 | 28.60 |
Report: ZoneHeatingSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 58423693.81 | 9125.64 | 23-JAN-05:12 | 12.57 |
February | 56039899.07 | 11054.87 | 06-FEB-05:12 | 17.97 |
March | 57720025.92 | 11067.92 | 20-MAR-04:12 | 12.20 |
April | 44534809.61 | 9160.13 | 19-APR-04:12 | 15.00 |
May | 20113589.69 | 6884.24 | 08-MAY-04:11 | 23.50 |
June | 12644417.26 | 4775.00 | 13-JUN-03:02 | 24.32 |
July | 20642644.48 | 5433.23 | 09-JUL-16:31 | 30.37 |
August | 23099247.13 | 6212.91 | 06-AUG-14:22 | 31.95 |
September | 20922151.96 | 5290.41 | 26-SEP-04:12 | 23.30 |
October | 35036162.80 | 7577.91 | 27-OCT-04:11 | 22.80 |
November | 61292315.12 | 10250.25 | 28-NOV-05:12 | 20.93 |
December | 86717644.91 | 14389.94 | 18-DEC-05:12 | 17.20 |
Annual Sum or Average | 0.497187E+09 | |||
Minimum of Months | 12644417.26 | 4775.00 | 12.20 | |
Maximum of Months | 86717644.91 | 14389.94 | 31.95 |
Report: ZoneHeatingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 38309038.73 | 6699.57 | 24-JAN-06:02 | 12.12 |
February | 41545436.66 | 7565.32 | 13-FEB-05:11 | 20.20 |
March | 22672607.41 | 7292.75 | 20-MAR-04:17 | 12.20 |
April | 22407593.62 | 5078.48 | 20-APR-04:11 | 20.77 |
May | 17285828.96 | 5502.32 | 29-MAY-16:21 | 32.50 |
June | 12977258.36 | 4821.03 | 20-JUN-03:02 | 25.50 |
July | 18967497.63 | 5092.76 | 03-JUL-03:02 | 25.50 |
August | 16833383.17 | 5928.05 | 28-AUG-03:02 | 25.68 |
September | 19773433.84 | 5167.53 | 29-SEP-03:02 | 26.42 |
October | 24558750.29 | 5363.68 | 02-OCT-03:02 | 26.70 |
November | 23550116.46 | 8087.36 | 13-NOV-05:12 | 12.60 |
December | 33734701.90 | 6762.48 | 22-DEC-06:03 | 17.80 |
Annual Sum or Average | 0.292616E+09 | |||
Minimum of Months | 12977258.36 | 4821.03 | 12.12 | |
Maximum of Months | 41545436.66 | 8087.36 | 32.50 |
Report: ZoneHeatingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.538666E+09 | 12607.01 | 05-JAN-06:02 | 16.70 |
February | 0.339709E+09 | 14241.91 | 28-FEB-06:03 | 16.88 |
March | 0.363482E+09 | 12326.48 | 15-MAR-05:03 | 12.12 |
April | 58782793.96 | 13790.66 | 19-APR-05:03 | 15.10 |
May | 31908269.09 | 11181.69 | 01-MAY-04:12 | 20.93 |
June | 20186400.90 | 8914.26 | 06-JUN-04:12 | 23.50 |
July | 23253061.47 | 10355.83 | 07-JUL-04:12 | 23.30 |
August | 20163129.58 | 7523.63 | 29-AUG-04:02 | 23.80 |
September | 26533706.70 | 11836.88 | 05-SEP-04:11 | 23.30 |
October | 36689275.11 | 11252.67 | 20-OCT-04:11 | 21.70 |
November | 0.133408E+09 | 10798.41 | 15-NOV-06:03 | 18.80 |
December | 0.453855E+09 | 12035.30 | 04-DEC-06:03 | 17.20 |
Annual Sum or Average | 0.204664E+10 | |||
Minimum of Months | 20163129.58 | 7523.63 | 12.12 | |
Maximum of Months | 0.538666E+09 | 14241.91 | 23.80 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 20.40 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 16.65 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 17.32 |
April | 0.00 | 0.00 | 01-APR-00:02 | 22.57 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 22.05 |
June | 0.00 | 0.00 | 01-JUN-00:02 | 26.68 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 26.83 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 28.60 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 27.05 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 27.93 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 22.40 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 24.10 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 16.65 | |
Maximum of Months | 0.00 | 0.00 | 28.60 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 20.40 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 16.65 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 17.32 |
April | 0.00 | 0.00 | 01-APR-00:02 | 22.57 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 22.05 |
June | 0.00 | 0.00 | 01-JUN-00:02 | 26.68 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 26.83 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 28.60 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 27.05 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 27.93 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 22.40 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 24.10 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 16.65 | |
Maximum of Months | 0.00 | 0.00 | 28.60 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 1066349.13 | 192.10 | 22-JAN-08:30 | 13.85 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 16.65 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 17.32 |
April | 0.00 | 0.00 | 01-APR-00:02 | 22.57 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 22.05 |
June | 0.00 | 0.00 | 01-JUN-00:02 | 26.68 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 26.83 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 28.60 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 27.05 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 27.93 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 22.40 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 24.10 |
Annual Sum or Average | 1066349.13 | |||
Minimum of Months | 0.00 | 0.00 | 13.85 | |
Maximum of Months | 1066349.13 | 192.10 | 28.60 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 20.40 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 16.65 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 17.32 |
April | 0.00 | 0.00 | 01-APR-00:02 | 22.57 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 22.05 |
June | 0.00 | 0.00 | 01-JUN-00:02 | 26.68 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 26.83 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 28.60 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 27.05 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 27.93 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 22.40 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 24.10 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 16.65 | |
Maximum of Months | 0.00 | 0.00 | 28.60 |
Report: ZoneElectricSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.219312E+11 | 22950.34 | 02-JAN-08:09 | 0.360447E+11 | 13457.54 | 01-JAN-00:10 |
February | 0.198933E+11 | 22950.34 | 01-FEB-08:09 | 0.325565E+11 | 13457.54 | 01-FEB-00:10 |
March | 0.236388E+11 | 22950.34 | 01-MAR-08:09 | 0.360447E+11 | 13457.54 | 01-MAR-00:10 |
April | 0.211142E+11 | 22950.34 | 03-APR-07:10 | 0.348820E+11 | 13457.54 | 01-APR-00:10 |
May | 0.227850E+11 | 22950.34 | 01-MAY-07:10 | 0.360447E+11 | 13457.54 | 01-MAY-00:10 |
June | 0.226748E+11 | 22950.34 | 01-JUN-07:10 | 0.348820E+11 | 13457.54 | 01-JUN-00:10 |
July | 0.212244E+11 | 22950.34 | 03-JUL-07:10 | 0.360447E+11 | 13457.54 | 01-JUL-00:10 |
August | 0.236388E+11 | 22950.34 | 01-AUG-07:10 | 0.360447E+11 | 13457.54 | 01-AUG-00:10 |
September | 0.211142E+11 | 22950.34 | 01-SEP-07:10 | 0.348820E+11 | 13457.54 | 01-SEP-00:10 |
October | 0.219312E+11 | 22950.34 | 02-OCT-07:10 | 0.360447E+11 | 13457.54 | 01-OCT-00:10 |
November | 0.216742E+11 | 22950.34 | 01-NOV-07:10 | 0.348820E+11 | 13457.54 | 01-NOV-00:10 |
December | 0.212244E+11 | 22950.34 | 01-DEC-08:09 | 0.360447E+11 | 13457.54 | 01-DEC-00:10 |
Annual Sum or Average | 0.262844E+12 | 0.424397E+12 | ||||
Minimum of Months | 0.198933E+11 | 22950.34 | 0.325565E+11 | 13457.54 | ||
Maximum of Months | 0.236388E+11 | 22950.34 | 0.360447E+11 | 13457.54 |
Report: ZoneElectricSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.196958E+11 | 20611.01 | 02-JAN-08:09 | 0.243681E+11 | 17206.63 | 02-JAN-08:09 |
February | 0.178655E+11 | 20611.01 | 01-FEB-08:09 | 0.220609E+11 | 17206.63 | 01-FEB-08:09 |
March | 0.212293E+11 | 20611.01 | 01-MAR-08:09 | 0.253549E+11 | 17206.63 | 01-MAR-08:09 |
April | 0.189620E+11 | 20611.01 | 03-APR-07:10 | 0.235306E+11 | 17206.63 | 03-APR-07:10 |
May | 0.204625E+11 | 20611.01 | 01-MAY-07:10 | 0.248615E+11 | 17206.63 | 01-MAY-07:10 |
June | 0.203636E+11 | 20611.01 | 01-JUN-07:10 | 0.244160E+11 | 17206.63 | 01-JUN-07:10 |
July | 0.190610E+11 | 20611.01 | 03-JUL-07:10 | 0.239708E+11 | 17206.63 | 03-JUL-07:10 |
August | 0.212293E+11 | 20611.01 | 01-AUG-07:10 | 0.253549E+11 | 17206.63 | 01-AUG-07:10 |
September | 0.189620E+11 | 20611.01 | 01-SEP-07:10 | 0.235199E+11 | 17206.63 | 01-SEP-07:10 |
October | 0.196958E+11 | 20611.01 | 02-OCT-07:10 | 0.243735E+11 | 17206.63 | 02-OCT-07:10 |
November | 0.194649E+11 | 20611.01 | 01-NOV-07:10 | 0.238373E+11 | 17206.63 | 01-NOV-07:10 |
December | 0.190610E+11 | 20611.01 | 01-DEC-08:09 | 0.239654E+11 | 17206.63 | 01-DEC-08:09 |
Annual Sum or Average | 0.236053E+12 | 0.289614E+12 | ||||
Minimum of Months | 0.178655E+11 | 20611.01 | 0.220609E+11 | 17206.63 | ||
Maximum of Months | 0.212293E+11 | 20611.01 | 0.253549E+11 | 17206.63 |
Report: ZoneElectricSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.196958E+11 | 20611.01 | 02-JAN-08:09 | 0.243680E+11 | 17206.56 | 02-JAN-08:09 |
February | 0.178655E+11 | 20611.01 | 01-FEB-08:09 | 0.220609E+11 | 17206.56 | 01-FEB-08:09 |
March | 0.212293E+11 | 20611.01 | 01-MAR-08:09 | 0.253548E+11 | 17206.56 | 01-MAR-08:09 |
April | 0.189620E+11 | 20611.01 | 03-APR-07:10 | 0.235305E+11 | 17206.56 | 03-APR-07:10 |
May | 0.204625E+11 | 20611.01 | 01-MAY-07:10 | 0.248614E+11 | 17206.56 | 01-MAY-07:10 |
June | 0.203636E+11 | 20611.01 | 01-JUN-07:10 | 0.244159E+11 | 17206.56 | 01-JUN-07:10 |
July | 0.190610E+11 | 20611.01 | 03-JUL-07:10 | 0.239707E+11 | 17206.56 | 03-JUL-07:10 |
August | 0.212293E+11 | 20611.01 | 01-AUG-07:10 | 0.253548E+11 | 17206.56 | 01-AUG-07:10 |
September | 0.189620E+11 | 20611.01 | 01-SEP-07:10 | 0.235198E+11 | 17206.56 | 01-SEP-07:10 |
October | 0.196958E+11 | 20611.01 | 02-OCT-07:10 | 0.243734E+11 | 17206.56 | 02-OCT-07:10 |
November | 0.194649E+11 | 20611.01 | 01-NOV-07:10 | 0.238372E+11 | 17206.56 | 01-NOV-07:10 |
December | 0.190610E+11 | 20611.01 | 01-DEC-08:09 | 0.239653E+11 | 17206.56 | 01-DEC-08:09 |
Annual Sum or Average | 0.236053E+12 | 0.289613E+12 | ||||
Minimum of Months | 0.178655E+11 | 20611.01 | 0.220609E+11 | 17206.56 | ||
Maximum of Months | 0.212293E+11 | 20611.01 | 0.253548E+11 | 17206.56 |
Report: ZoneElectricSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.196958E+11 | 20611.01 | 02-JAN-08:09 | 0.243680E+11 | 17206.56 | 02-JAN-08:09 |
February | 0.178655E+11 | 20611.01 | 01-FEB-08:09 | 0.220609E+11 | 17206.56 | 01-FEB-08:09 |
March | 0.212293E+11 | 20611.01 | 01-MAR-08:09 | 0.253548E+11 | 17206.56 | 01-MAR-08:09 |
April | 0.189620E+11 | 20611.01 | 03-APR-07:10 | 0.235305E+11 | 17206.56 | 03-APR-07:10 |
May | 0.204625E+11 | 20611.01 | 01-MAY-07:10 | 0.248614E+11 | 17206.56 | 01-MAY-07:10 |
June | 0.203636E+11 | 20611.01 | 01-JUN-07:10 | 0.244159E+11 | 17206.56 | 01-JUN-07:10 |
July | 0.190610E+11 | 20611.01 | 03-JUL-07:10 | 0.239707E+11 | 17206.56 | 03-JUL-07:10 |
August | 0.212293E+11 | 20611.01 | 01-AUG-07:10 | 0.253548E+11 | 17206.56 | 01-AUG-07:10 |
September | 0.189620E+11 | 20611.01 | 01-SEP-07:10 | 0.235198E+11 | 17206.56 | 01-SEP-07:10 |
October | 0.196958E+11 | 20611.01 | 02-OCT-07:10 | 0.243734E+11 | 17206.56 | 02-OCT-07:10 |
November | 0.194649E+11 | 20611.01 | 01-NOV-07:10 | 0.238372E+11 | 17206.56 | 01-NOV-07:10 |
December | 0.190610E+11 | 20611.01 | 01-DEC-08:09 | 0.239653E+11 | 17206.56 | 01-DEC-08:09 |
Annual Sum or Average | 0.236053E+12 | 0.289613E+12 | ||||
Minimum of Months | 0.178655E+11 | 20611.01 | 0.220609E+11 | 17206.56 | ||
Maximum of Months | 0.212293E+11 | 20611.01 | 0.253548E+11 | 17206.56 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.155608E+10 | 2255.20 | 04-JAN-16:30 | 0.305979E+10 | 2160.55 | 02-JAN-08:09 |
February | 0.134429E+10 | 1803.00 | 03-FEB-16:00 | 0.277008E+10 | 2160.55 | 01-FEB-08:09 |
March | 0.152761E+10 | 2135.72 | 15-MAR-07:10 | 0.318369E+10 | 2160.55 | 01-MAR-08:09 |
April | 0.133733E+10 | 1803.00 | 12-APR-07:10 | 0.295462E+10 | 2160.55 | 03-APR-07:10 |
May | 0.140758E+10 | 1470.28 | 25-MAY-07:10 | 0.312174E+10 | 2160.55 | 01-MAY-07:10 |
June | 0.139904E+10 | 2255.20 | 15-JUN-07:10 | 0.306580E+10 | 2160.55 | 01-JUN-07:10 |
July | 0.130500E+10 | 1470.28 | 05-JUL-07:10 | 0.300989E+10 | 2160.55 | 03-JUL-07:10 |
August | 0.147509E+10 | 1803.00 | 28-AUG-07:10 | 0.318369E+10 | 2160.55 | 01-AUG-07:10 |
September | 0.136495E+10 | 2587.92 | 27-SEP-07:10 | 0.295328E+10 | 2160.55 | 01-SEP-07:10 |
October | 0.146267E+10 | 2255.20 | 18-OCT-07:10 | 0.306046E+10 | 2160.55 | 02-OCT-07:10 |
November | 0.150167E+10 | 2255.20 | 10-NOV-16:00 | 0.299314E+10 | 2160.55 | 01-NOV-07:10 |
December | 0.152662E+10 | 2587.92 | 15-DEC-16:30 | 0.300922E+10 | 2160.55 | 01-DEC-08:09 |
Annual Sum or Average | 0.172079E+11 | 0.363654E+11 | ||||
Minimum of Months | 0.130500E+10 | 1470.28 | 0.277008E+10 | 2160.55 | ||
Maximum of Months | 0.155608E+10 | 2587.92 | 0.318369E+10 | 2160.55 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.978000E+09 | 1453.34 | 04-JAN-16:30 | 0.197184E+10 | 1392.34 | 02-JAN-08:09 |
February | 0.856952E+09 | 1161.92 | 01-FEB-16:00 | 0.178515E+10 | 1392.34 | 01-FEB-08:09 |
March | 0.972653E+09 | 947.51 | 06-MAR-16:00 | 0.205169E+10 | 1392.34 | 01-MAR-08:09 |
April | 0.862224E+09 | 1161.92 | 12-APR-07:10 | 0.190407E+10 | 1392.34 | 03-APR-07:10 |
May | 0.914164E+09 | 870.51 | 10-MAY-14:20 | 0.201177E+10 | 1392.34 | 01-MAY-07:10 |
June | 0.910731E+09 | 1453.34 | 15-JUN-07:10 | 0.197572E+10 | 1392.34 | 01-JUN-07:10 |
July | 0.848671E+09 | 870.51 | 05-JUL-07:10 | 0.193969E+10 | 1392.34 | 03-JUL-07:10 |
August | 0.951322E+09 | 1161.92 | 28-AUG-07:10 | 0.205169E+10 | 1392.34 | 01-AUG-07:10 |
September | 0.878172E+09 | 1667.75 | 27-SEP-07:10 | 0.190321E+10 | 1392.34 | 01-SEP-07:10 |
October | 0.927004E+09 | 1453.34 | 18-OCT-07:10 | 0.197228E+10 | 1392.34 | 02-OCT-07:10 |
November | 0.956291E+09 | 1453.34 | 10-NOV-16:49 | 0.192889E+10 | 1392.34 | 01-NOV-07:10 |
December | 0.968600E+09 | 1667.75 | 15-DEC-16:30 | 0.193926E+10 | 1392.34 | 01-DEC-08:09 |
Annual Sum or Average | 0.110248E+11 | 0.234352E+11 | ||||
Minimum of Months | 0.848671E+09 | 870.51 | 0.178515E+10 | 1392.34 | ||
Maximum of Months | 0.978000E+09 | 1667.75 | 0.205169E+10 | 1392.34 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.146558E+10 | 2255.25 | 04-JAN-16:49 | 0.305983E+10 | 2160.58 | 02-JAN-08:09 |
February | 0.130163E+10 | 1470.31 | 08-FEB-16:40 | 0.277013E+10 | 2160.58 | 01-FEB-08:09 |
March | 0.150809E+10 | 1803.04 | 13-MAR-07:10 | 0.318374E+10 | 2160.58 | 01-MAR-08:09 |
April | 0.134196E+10 | 1803.04 | 12-APR-07:10 | 0.295467E+10 | 2160.58 | 03-APR-07:10 |
May | 0.142580E+10 | 1470.31 | 25-MAY-07:10 | 0.312179E+10 | 2160.58 | 01-MAY-07:10 |
June | 0.142808E+10 | 2255.25 | 15-JUN-07:10 | 0.306585E+10 | 2160.58 | 01-JUN-07:10 |
July | 0.132364E+10 | 1470.31 | 05-JUL-07:10 | 0.300994E+10 | 2160.58 | 03-JUL-07:10 |
August | 0.148321E+10 | 1803.04 | 28-AUG-07:10 | 0.318374E+10 | 2160.58 | 01-AUG-07:10 |
September | 0.135921E+10 | 2587.98 | 27-SEP-07:10 | 0.295333E+10 | 2160.58 | 01-SEP-07:10 |
October | 0.142707E+10 | 2255.25 | 18-OCT-07:10 | 0.306051E+10 | 2160.58 | 02-OCT-07:10 |
November | 0.144131E+10 | 2255.25 | 29-NOV-16:00 | 0.299318E+10 | 2160.58 | 01-NOV-07:10 |
December | 0.145014E+10 | 2587.98 | 15-DEC-16:40 | 0.300927E+10 | 2160.58 | 01-DEC-08:09 |
Annual Sum or Average | 0.169557E+11 | 0.363660E+11 | ||||
Minimum of Months | 0.130163E+10 | 1470.31 | 0.277013E+10 | 2160.58 | ||
Maximum of Months | 0.150809E+10 | 2587.98 | 0.318374E+10 | 2160.58 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.966155E+09 | 1453.34 | 04-JAN-16:49 | 0.197183E+10 | 1392.33 | 02-JAN-08:09 |
February | 0.848178E+09 | 1161.92 | 01-FEB-08:09 | 0.178514E+10 | 1392.33 | 01-FEB-08:09 |
March | 0.982490E+09 | 1453.34 | 14-MAR-07:10 | 0.205168E+10 | 1392.33 | 01-MAR-08:09 |
April | 0.861135E+09 | 1453.34 | 12-APR-07:10 | 0.190406E+10 | 1392.33 | 03-APR-07:10 |
May | 0.917287E+09 | 1161.92 | 25-MAY-07:10 | 0.201175E+10 | 1392.33 | 01-MAY-07:10 |
June | 0.915555E+09 | 1667.75 | 15-JUN-07:10 | 0.197570E+10 | 1392.33 | 01-JUN-07:10 |
July | 0.851828E+09 | 1161.92 | 05-JUL-07:10 | 0.193968E+10 | 1392.33 | 03-JUL-07:10 |
August | 0.959102E+09 | 1453.34 | 28-AUG-07:10 | 0.205168E+10 | 1392.33 | 01-AUG-07:10 |
September | 0.880731E+09 | 1667.75 | 27-SEP-07:10 | 0.190319E+10 | 1392.33 | 01-SEP-07:10 |
October | 0.935934E+09 | 1453.34 | 18-OCT-07:10 | 0.197226E+10 | 1392.33 | 02-OCT-07:10 |
November | 0.941668E+09 | 1453.34 | 03-NOV-07:10 | 0.192888E+10 | 1392.33 | 01-NOV-07:10 |
December | 0.947339E+09 | 1667.75 | 15-DEC-16:40 | 0.193924E+10 | 1392.33 | 01-DEC-08:09 |
Annual Sum or Average | 0.110074E+11 | 0.234351E+11 | ||||
Minimum of Months | 0.848178E+09 | 1161.92 | 0.178514E+10 | 1392.33 | ||
Maximum of Months | 0.982490E+09 | 1667.75 | 0.205168E+10 | 1392.33 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.154804E+10 | 2255.20 | 04-JAN-16:40 | 0.305979E+10 | 2160.55 | 02-JAN-08:09 |
February | 0.133903E+10 | 1803.00 | 03-FEB-16:00 | 0.277008E+10 | 2160.55 | 01-FEB-08:09 |
March | 0.152320E+10 | 2135.72 | 15-MAR-07:10 | 0.318369E+10 | 2160.55 | 01-MAR-08:09 |
April | 0.133582E+10 | 1803.00 | 12-APR-07:10 | 0.295462E+10 | 2160.55 | 03-APR-07:10 |
May | 0.140640E+10 | 1470.28 | 25-MAY-07:10 | 0.312174E+10 | 2160.55 | 01-MAY-07:10 |
June | 0.139590E+10 | 2255.20 | 15-JUN-07:10 | 0.306580E+10 | 2160.55 | 01-JUN-07:10 |
July | 0.130374E+10 | 1470.28 | 05-JUL-07:10 | 0.300989E+10 | 2160.55 | 03-JUL-07:10 |
August | 0.147370E+10 | 1803.00 | 28-AUG-07:10 | 0.318369E+10 | 2160.55 | 01-AUG-07:10 |
September | 0.136206E+10 | 2587.92 | 27-SEP-07:10 | 0.295328E+10 | 2160.55 | 01-SEP-07:10 |
October | 0.145805E+10 | 2255.20 | 18-OCT-07:10 | 0.306046E+10 | 2160.55 | 02-OCT-07:10 |
November | 0.149611E+10 | 2255.20 | 21-NOV-16:00 | 0.299314E+10 | 2160.55 | 01-NOV-07:10 |
December | 0.152136E+10 | 2587.92 | 15-DEC-16:30 | 0.300922E+10 | 2160.55 | 01-DEC-08:09 |
Annual Sum or Average | 0.171634E+11 | 0.363654E+11 | ||||
Minimum of Months | 0.130374E+10 | 1470.28 | 0.277008E+10 | 2160.55 | ||
Maximum of Months | 0.154804E+10 | 2587.92 | 0.318369E+10 | 2160.55 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.975956E+09 | 1453.34 | 04-JAN-16:30 | 0.197184E+10 | 1392.34 | 02-JAN-08:09 |
February | 0.854981E+09 | 1161.92 | 01-FEB-16:00 | 0.178515E+10 | 1392.34 | 01-FEB-08:09 |
March | 0.971761E+09 | 947.51 | 14-MAR-07:10 | 0.205169E+10 | 1392.34 | 01-MAR-08:09 |
April | 0.861606E+09 | 1161.92 | 12-APR-07:10 | 0.190407E+10 | 1392.34 | 03-APR-07:10 |
May | 0.913092E+09 | 870.51 | 10-MAY-14:20 | 0.201177E+10 | 1392.34 | 01-MAY-07:10 |
June | 0.909114E+09 | 1453.34 | 15-JUN-07:10 | 0.197572E+10 | 1392.34 | 01-JUN-07:10 |
July | 0.847382E+09 | 870.51 | 05-JUL-07:10 | 0.193969E+10 | 1392.34 | 03-JUL-07:10 |
August | 0.950134E+09 | 1161.92 | 28-AUG-07:10 | 0.205169E+10 | 1392.34 | 01-AUG-07:10 |
September | 0.876986E+09 | 1667.75 | 27-SEP-07:10 | 0.190321E+10 | 1392.34 | 01-SEP-07:10 |
October | 0.925803E+09 | 1453.34 | 18-OCT-07:10 | 0.197228E+10 | 1392.34 | 02-OCT-07:10 |
November | 0.953715E+09 | 1453.34 | 10-NOV-16:00 | 0.192889E+10 | 1392.34 | 01-NOV-07:10 |
December | 0.965929E+09 | 1667.75 | 15-DEC-16:30 | 0.193926E+10 | 1392.34 | 01-DEC-08:09 |
Annual Sum or Average | 0.110065E+11 | 0.234352E+11 | ||||
Minimum of Months | 0.847382E+09 | 870.51 | 0.178515E+10 | 1392.34 | ||
Maximum of Months | 0.975956E+09 | 1667.75 | 0.205169E+10 | 1392.34 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.146453E+10 | 2255.25 | 04-JAN-16:49 | 0.305983E+10 | 2160.58 | 02-JAN-08:09 |
February | 0.130047E+10 | 1470.31 | 08-FEB-16:40 | 0.277013E+10 | 2160.58 | 01-FEB-08:09 |
March | 0.150564E+10 | 1803.04 | 13-MAR-07:10 | 0.318374E+10 | 2160.58 | 01-MAR-08:09 |
April | 0.134062E+10 | 1803.04 | 12-APR-07:10 | 0.295467E+10 | 2160.58 | 03-APR-07:10 |
May | 0.142356E+10 | 1470.31 | 25-MAY-07:10 | 0.312179E+10 | 2160.58 | 01-MAY-07:10 |
June | 0.142477E+10 | 2255.25 | 15-JUN-07:10 | 0.306585E+10 | 2160.58 | 01-JUN-07:10 |
July | 0.132180E+10 | 1470.31 | 05-JUL-07:10 | 0.300994E+10 | 2160.58 | 03-JUL-07:10 |
August | 0.148112E+10 | 1803.04 | 28-AUG-07:10 | 0.318374E+10 | 2160.58 | 01-AUG-07:10 |
September | 0.135778E+10 | 2587.98 | 27-SEP-07:10 | 0.295333E+10 | 2160.58 | 01-SEP-07:10 |
October | 0.142401E+10 | 2255.25 | 18-OCT-07:10 | 0.306051E+10 | 2160.58 | 02-OCT-07:10 |
November | 0.143833E+10 | 2255.25 | 29-NOV-16:00 | 0.299318E+10 | 2160.58 | 01-NOV-07:10 |
December | 0.144886E+10 | 2587.98 | 15-DEC-16:40 | 0.300927E+10 | 2160.58 | 01-DEC-08:09 |
Annual Sum or Average | 0.169315E+11 | 0.363660E+11 | ||||
Minimum of Months | 0.130047E+10 | 1470.31 | 0.277013E+10 | 2160.58 | ||
Maximum of Months | 0.150564E+10 | 2587.98 | 0.318374E+10 | 2160.58 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.964325E+09 | 1453.34 | 04-JAN-16:00 | 0.197183E+10 | 1392.33 | 02-JAN-08:09 |
February | 0.846551E+09 | 1161.92 | 01-FEB-08:09 | 0.178514E+10 | 1392.33 | 01-FEB-08:09 |
March | 0.980185E+09 | 1453.34 | 14-MAR-07:10 | 0.205168E+10 | 1392.33 | 01-MAR-08:09 |
April | 0.860252E+09 | 1453.34 | 12-APR-07:10 | 0.190406E+10 | 1392.33 | 03-APR-07:10 |
May | 0.915468E+09 | 1161.92 | 25-MAY-07:10 | 0.201175E+10 | 1392.33 | 01-MAY-07:10 |
June | 0.913262E+09 | 1667.75 | 15-JUN-07:10 | 0.197570E+10 | 1392.33 | 01-JUN-07:10 |
July | 0.849555E+09 | 1161.92 | 05-JUL-07:10 | 0.193968E+10 | 1392.33 | 03-JUL-07:10 |
August | 0.957318E+09 | 1453.34 | 28-AUG-07:10 | 0.205168E+10 | 1392.33 | 01-AUG-07:10 |
September | 0.878533E+09 | 1667.75 | 27-SEP-07:10 | 0.190319E+10 | 1392.33 | 01-SEP-07:10 |
October | 0.934074E+09 | 1453.34 | 18-OCT-07:10 | 0.197226E+10 | 1392.33 | 02-OCT-07:10 |
November | 0.939147E+09 | 1453.34 | 03-NOV-07:10 | 0.192888E+10 | 1392.33 | 01-NOV-07:10 |
December | 0.945111E+09 | 1667.75 | 15-DEC-16:40 | 0.193924E+10 | 1392.33 | 01-DEC-08:09 |
Annual Sum or Average | 0.109838E+11 | 0.234351E+11 | ||||
Minimum of Months | 0.846551E+09 | 1161.92 | 0.178514E+10 | 1392.33 | ||
Maximum of Months | 0.980185E+09 | 1667.75 | 0.205168E+10 | 1392.33 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.154770E+10 | 2255.20 | 04-JAN-16:40 | 0.305979E+10 | 2160.55 | 02-JAN-08:09 |
February | 0.133883E+10 | 1803.00 | 03-FEB-16:00 | 0.277008E+10 | 2160.55 | 01-FEB-08:09 |
March | 0.152316E+10 | 2135.72 | 15-MAR-07:10 | 0.318369E+10 | 2160.55 | 01-MAR-08:09 |
April | 0.133579E+10 | 1803.00 | 12-APR-07:10 | 0.295462E+10 | 2160.55 | 03-APR-07:10 |
May | 0.140637E+10 | 1470.28 | 25-MAY-07:10 | 0.312174E+10 | 2160.55 | 01-MAY-07:10 |
June | 0.139583E+10 | 2255.20 | 15-JUN-07:10 | 0.306580E+10 | 2160.55 | 01-JUN-07:10 |
July | 0.130362E+10 | 1470.28 | 05-JUL-07:10 | 0.300989E+10 | 2160.55 | 03-JUL-07:10 |
August | 0.147356E+10 | 1803.00 | 28-AUG-07:10 | 0.318369E+10 | 2160.55 | 01-AUG-07:10 |
September | 0.136199E+10 | 2587.92 | 27-SEP-07:10 | 0.295328E+10 | 2160.55 | 01-SEP-07:10 |
October | 0.145804E+10 | 2255.20 | 18-OCT-07:10 | 0.306046E+10 | 2160.55 | 02-OCT-07:10 |
November | 0.149565E+10 | 2255.20 | 21-NOV-16:00 | 0.299314E+10 | 2160.55 | 01-NOV-07:10 |
December | 0.152107E+10 | 2587.92 | 15-DEC-16:30 | 0.300922E+10 | 2160.55 | 01-DEC-08:09 |
Annual Sum or Average | 0.171616E+11 | 0.363654E+11 | ||||
Minimum of Months | 0.130362E+10 | 1470.28 | 0.277008E+10 | 2160.55 | ||
Maximum of Months | 0.154770E+10 | 2587.92 | 0.318369E+10 | 2160.55 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.975934E+09 | 1453.34 | 04-JAN-16:30 | 0.197184E+10 | 1392.34 | 02-JAN-08:09 |
February | 0.854981E+09 | 1161.92 | 01-FEB-16:00 | 0.178515E+10 | 1392.34 | 01-FEB-08:09 |
March | 0.971685E+09 | 947.51 | 14-MAR-07:10 | 0.205169E+10 | 1392.34 | 01-MAR-08:09 |
April | 0.861606E+09 | 1161.92 | 12-APR-07:10 | 0.190407E+10 | 1392.34 | 03-APR-07:10 |
May | 0.913051E+09 | 870.51 | 10-MAY-14:20 | 0.201177E+10 | 1392.34 | 01-MAY-07:10 |
June | 0.909073E+09 | 1453.34 | 15-JUN-07:10 | 0.197572E+10 | 1392.34 | 01-JUN-07:10 |
July | 0.847368E+09 | 870.51 | 05-JUL-07:10 | 0.193969E+10 | 1392.34 | 03-JUL-07:10 |
August | 0.950111E+09 | 1161.92 | 28-AUG-07:10 | 0.205169E+10 | 1392.34 | 01-AUG-07:10 |
September | 0.876980E+09 | 1667.75 | 27-SEP-07:10 | 0.190321E+10 | 1392.34 | 01-SEP-07:10 |
October | 0.925731E+09 | 1453.34 | 18-OCT-07:10 | 0.197228E+10 | 1392.34 | 02-OCT-07:10 |
November | 0.953537E+09 | 1453.34 | 10-NOV-16:00 | 0.192889E+10 | 1392.34 | 01-NOV-07:10 |
December | 0.965911E+09 | 1667.75 | 15-DEC-16:30 | 0.193926E+10 | 1392.34 | 01-DEC-08:09 |
Annual Sum or Average | 0.110060E+11 | 0.234352E+11 | ||||
Minimum of Months | 0.847368E+09 | 870.51 | 0.178515E+10 | 1392.34 | ||
Maximum of Months | 0.975934E+09 | 1667.75 | 0.205169E+10 | 1392.34 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.146452E+10 | 2255.25 | 04-JAN-16:49 | 0.305983E+10 | 2160.58 | 02-JAN-08:09 |
February | 0.130043E+10 | 1470.31 | 08-FEB-16:40 | 0.277013E+10 | 2160.58 | 01-FEB-08:09 |
March | 0.150561E+10 | 1803.04 | 13-MAR-07:10 | 0.318374E+10 | 2160.58 | 01-MAR-08:09 |
April | 0.134060E+10 | 1803.04 | 12-APR-07:10 | 0.295467E+10 | 2160.58 | 03-APR-07:10 |
May | 0.142346E+10 | 1470.31 | 25-MAY-07:10 | 0.312179E+10 | 2160.58 | 01-MAY-07:10 |
June | 0.142476E+10 | 2255.25 | 15-JUN-07:10 | 0.306585E+10 | 2160.58 | 01-JUN-07:10 |
July | 0.132176E+10 | 1470.31 | 05-JUL-07:10 | 0.300994E+10 | 2160.58 | 03-JUL-07:10 |
August | 0.148105E+10 | 1803.04 | 28-AUG-07:10 | 0.318374E+10 | 2160.58 | 01-AUG-07:10 |
September | 0.135778E+10 | 2587.98 | 27-SEP-07:10 | 0.295333E+10 | 2160.58 | 01-SEP-07:10 |
October | 0.142401E+10 | 2255.25 | 18-OCT-07:10 | 0.306051E+10 | 2160.58 | 02-OCT-07:10 |
November | 0.143829E+10 | 2255.25 | 29-NOV-16:00 | 0.299318E+10 | 2160.58 | 01-NOV-07:10 |
December | 0.144878E+10 | 2587.98 | 15-DEC-16:40 | 0.300927E+10 | 2160.58 | 01-DEC-08:09 |
Annual Sum or Average | 0.169311E+11 | 0.363660E+11 | ||||
Minimum of Months | 0.130043E+10 | 1470.31 | 0.277013E+10 | 2160.58 | ||
Maximum of Months | 0.150561E+10 | 2587.98 | 0.318374E+10 | 2160.58 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.964128E+09 | 1453.34 | 04-JAN-16:00 | 0.197183E+10 | 1392.33 | 02-JAN-08:09 |
February | 0.846502E+09 | 1161.92 | 01-FEB-08:09 | 0.178514E+10 | 1392.33 | 01-FEB-08:09 |
March | 0.980142E+09 | 1453.34 | 14-MAR-07:10 | 0.205168E+10 | 1392.33 | 01-MAR-08:09 |
April | 0.860206E+09 | 1453.34 | 12-APR-07:10 | 0.190406E+10 | 1392.33 | 03-APR-07:10 |
May | 0.915468E+09 | 1161.92 | 25-MAY-07:10 | 0.201175E+10 | 1392.33 | 01-MAY-07:10 |
June | 0.913252E+09 | 1667.75 | 15-JUN-07:10 | 0.197570E+10 | 1392.33 | 01-JUN-07:10 |
July | 0.849555E+09 | 1161.92 | 05-JUL-07:10 | 0.193968E+10 | 1392.33 | 03-JUL-07:10 |
August | 0.957303E+09 | 1453.34 | 28-AUG-07:10 | 0.205168E+10 | 1392.33 | 01-AUG-07:10 |
September | 0.878533E+09 | 1667.75 | 27-SEP-07:10 | 0.190319E+10 | 1392.33 | 01-SEP-07:10 |
October | 0.934064E+09 | 1453.34 | 18-OCT-07:10 | 0.197226E+10 | 1392.33 | 02-OCT-07:10 |
November | 0.939145E+09 | 1453.34 | 03-NOV-07:10 | 0.192888E+10 | 1392.33 | 01-NOV-07:10 |
December | 0.945111E+09 | 1667.75 | 15-DEC-16:40 | 0.193924E+10 | 1392.33 | 01-DEC-08:09 |
Annual Sum or Average | 0.109834E+11 | 0.234351E+11 | ||||
Minimum of Months | 0.846502E+09 | 1161.92 | 0.178514E+10 | 1392.33 | ||
Maximum of Months | 0.980142E+09 | 1667.75 | 0.205168E+10 | 1392.33 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.553024E+09 | 578.72 | 02-JAN-08:09 | 0.521915E+10 | 1948.61 | 01-JAN-00:10 |
February | 0.501634E+09 | 578.72 | 01-FEB-08:09 | 0.942813E+10 | 3897.21 | 01-FEB-00:10 |
March | 0.596080E+09 | 578.72 | 01-MAR-08:09 | 0.156645E+11 | 7794.42 | 31-MAR-23:10 |
April | 0.532421E+09 | 578.72 | 03-APR-07:10 | 0.201821E+11 | 7794.42 | 01-APR-00:10 |
May | 0.574552E+09 | 578.72 | 01-MAY-07:10 | 0.522616E+10 | 3897.21 | 31-MAY-23:10 |
June | 0.571774E+09 | 578.72 | 01-JUN-07:10 | 0.101086E+11 | 5845.82 | 30-JUN-23:10 |
July | 0.535199E+09 | 578.72 | 03-JUL-07:10 | 0.156645E+11 | 7794.42 | 31-JUL-23:10 |
August | 0.596080E+09 | 578.72 | 01-AUG-07:10 | 0.208555E+11 | 7794.42 | 01-AUG-00:10 |
September | 0.532421E+09 | 578.72 | 01-SEP-07:10 | 0.505780E+10 | 3897.21 | 30-SEP-23:10 |
October | 0.553024E+09 | 578.72 | 02-OCT-07:10 | 0.104453E+11 | 5845.82 | 31-OCT-23:10 |
November | 0.546542E+09 | 578.72 | 01-NOV-07:10 | 0.151524E+11 | 5845.82 | 01-NOV-00:10 |
December | 0.535199E+09 | 578.72 | 01-DEC-08:09 | 0.208766E+11 | 7794.42 | 01-DEC-00:10 |
Annual Sum or Average | 0.662795E+10 | 0.153881E+12 | ||||
Minimum of Months | 0.501634E+09 | 578.72 | 0.505780E+10 | 1948.61 | ||
Maximum of Months | 0.596080E+09 | 578.72 | 0.208766E+11 | 7794.42 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.553024E+09 | 578.72 | 02-JAN-08:09 | 0.521915E+10 | 1948.61 | 01-JAN-00:10 |
February | 0.501634E+09 | 578.72 | 01-FEB-08:09 | 0.942813E+10 | 3897.21 | 01-FEB-00:10 |
March | 0.596080E+09 | 578.72 | 01-MAR-08:09 | 0.156645E+11 | 7794.42 | 31-MAR-23:10 |
April | 0.532421E+09 | 578.72 | 03-APR-07:10 | 0.201821E+11 | 7794.42 | 01-APR-00:10 |
May | 0.574552E+09 | 578.72 | 01-MAY-07:10 | 0.522616E+10 | 3897.21 | 31-MAY-23:10 |
June | 0.571774E+09 | 578.72 | 01-JUN-07:10 | 0.101086E+11 | 5845.82 | 30-JUN-23:10 |
July | 0.535199E+09 | 578.72 | 03-JUL-07:10 | 0.156645E+11 | 7794.42 | 31-JUL-23:10 |
August | 0.596080E+09 | 578.72 | 01-AUG-07:10 | 0.208555E+11 | 7794.42 | 01-AUG-00:10 |
September | 0.532421E+09 | 578.72 | 01-SEP-07:10 | 0.505780E+10 | 3897.21 | 30-SEP-23:10 |
October | 0.553024E+09 | 578.72 | 02-OCT-07:10 | 0.104453E+11 | 5845.82 | 31-OCT-23:10 |
November | 0.546542E+09 | 578.72 | 01-NOV-07:10 | 0.151524E+11 | 5845.82 | 01-NOV-00:10 |
December | 0.535199E+09 | 578.72 | 01-DEC-08:09 | 0.208766E+11 | 7794.42 | 01-DEC-00:10 |
Annual Sum or Average | 0.662795E+10 | 0.153881E+12 | ||||
Minimum of Months | 0.501634E+09 | 578.72 | 0.505780E+10 | 1948.61 | ||
Maximum of Months | 0.596080E+09 | 578.72 | 0.208766E+11 | 7794.42 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.553024E+09 | 578.72 | 02-JAN-08:09 | 0.521915E+10 | 1948.61 | 01-JAN-00:10 |
February | 0.501634E+09 | 578.72 | 01-FEB-08:09 | 0.942813E+10 | 3897.21 | 01-FEB-00:10 |
March | 0.596080E+09 | 578.72 | 01-MAR-08:09 | 0.156645E+11 | 7794.42 | 31-MAR-23:10 |
April | 0.532421E+09 | 578.72 | 03-APR-07:10 | 0.201821E+11 | 7794.42 | 01-APR-00:10 |
May | 0.574552E+09 | 578.72 | 01-MAY-07:10 | 0.522616E+10 | 3897.21 | 31-MAY-23:10 |
June | 0.571774E+09 | 578.72 | 01-JUN-07:10 | 0.101086E+11 | 5845.82 | 30-JUN-23:10 |
July | 0.535199E+09 | 578.72 | 03-JUL-07:10 | 0.156645E+11 | 7794.42 | 31-JUL-23:10 |
August | 0.596080E+09 | 578.72 | 01-AUG-07:10 | 0.208555E+11 | 7794.42 | 01-AUG-00:10 |
September | 0.532421E+09 | 578.72 | 01-SEP-07:10 | 0.505780E+10 | 3897.21 | 30-SEP-23:10 |
October | 0.553024E+09 | 578.72 | 02-OCT-07:10 | 0.104453E+11 | 5845.82 | 31-OCT-23:10 |
November | 0.546542E+09 | 578.72 | 01-NOV-07:10 | 0.151524E+11 | 5845.82 | 01-NOV-00:10 |
December | 0.535199E+09 | 578.72 | 01-DEC-08:09 | 0.208766E+11 | 7794.42 | 01-DEC-00:10 |
Annual Sum or Average | 0.662795E+10 | 0.153881E+12 | ||||
Minimum of Months | 0.501634E+09 | 578.72 | 0.505780E+10 | 1948.61 | ||
Maximum of Months | 0.596080E+09 | 578.72 | 0.208766E+11 | 7794.42 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.618367E+10 | 6471.01 | 02-JAN-08:09 | 0.254202E+12 | 94908.13 | 01-JAN-00:10 |
February | 0.560905E+10 | 6471.01 | 01-FEB-08:09 | 0.459203E+12 | 189816.26 | 01-FEB-00:10 |
March | 0.666512E+10 | 6471.01 | 01-MAR-08:09 | 0.762947E+12 | 379632.52 | 31-MAR-23:10 |
April | 0.595330E+10 | 6471.01 | 03-APR-07:10 | 0.982982E+12 | 379632.52 | 01-APR-00:10 |
May | 0.642439E+10 | 6471.01 | 01-MAY-07:10 | 0.254544E+12 | 189816.26 | 31-MAY-23:10 |
June | 0.639333E+10 | 6471.01 | 01-JUN-07:10 | 0.492345E+12 | 284724.39 | 30-JUN-23:10 |
July | 0.598436E+10 | 6471.01 | 03-JUL-07:10 | 0.762947E+12 | 379632.52 | 31-JUL-23:10 |
August | 0.666512E+10 | 6471.01 | 01-AUG-07:10 | 0.101578E+13 | 379632.52 | 01-AUG-00:10 |
September | 0.595330E+10 | 6471.01 | 01-SEP-07:10 | 0.246344E+12 | 189816.26 | 30-SEP-23:10 |
October | 0.618367E+10 | 6471.01 | 02-OCT-07:10 | 0.508746E+12 | 284724.39 | 31-OCT-23:10 |
November | 0.611120E+10 | 6471.01 | 01-NOV-07:10 | 0.738006E+12 | 284724.39 | 01-NOV-00:10 |
December | 0.598436E+10 | 6471.01 | 01-DEC-08:09 | 0.101681E+13 | 379632.52 | 01-DEC-00:10 |
Annual Sum or Average | 0.741109E+11 | 0.749486E+13 | ||||
Minimum of Months | 0.560905E+10 | 6471.01 | 0.246344E+12 | 94908.13 | ||
Maximum of Months | 0.666512E+10 | 6471.01 | 0.101681E+13 | 379632.52 |
Report: SpaceGainsMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.133902E+11 | 0.219312E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.121482E+11 | 0.198933E+11 | 0.325565E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.145160E+11 | 0.236388E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.128805E+11 | 0.211142E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.139531E+11 | 0.227850E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.139143E+11 | 0.226748E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.129193E+11 | 0.212244E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.145160E+11 | 0.236388E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.128805E+11 | 0.211142E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.133902E+11 | 0.219312E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.132595E+11 | 0.216742E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.129193E+11 | 0.212244E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.160687E+12 | 0.262844E+12 | 0.424397E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.121482E+11 | 0.198933E+11 | 0.325565E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.145160E+11 | 0.236388E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.120254E+11 | 0.196958E+11 | 0.243681E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.109099E+11 | 0.178655E+11 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.130364E+11 | 0.212293E+11 | 0.253549E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.115676E+11 | 0.189620E+11 | 0.235306E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.125309E+11 | 0.204625E+11 | 0.248615E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.124961E+11 | 0.203636E+11 | 0.244160E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.116025E+11 | 0.190610E+11 | 0.239708E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.130364E+11 | 0.212293E+11 | 0.253549E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.115676E+11 | 0.189620E+11 | 0.235199E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.120254E+11 | 0.196958E+11 | 0.243735E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.119080E+11 | 0.194649E+11 | 0.238373E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.116025E+11 | 0.190610E+11 | 0.239654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.144308E+12 | 0.236053E+12 | 0.289614E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.109099E+11 | 0.178655E+11 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.130364E+11 | 0.212293E+11 | 0.253549E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.120254E+11 | 0.196958E+11 | 0.243680E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.109099E+11 | 0.178655E+11 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.130364E+11 | 0.212293E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.115676E+11 | 0.189620E+11 | 0.235305E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.125309E+11 | 0.204625E+11 | 0.248614E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.124961E+11 | 0.203636E+11 | 0.244159E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.116025E+11 | 0.190610E+11 | 0.239707E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.130364E+11 | 0.212293E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.115676E+11 | 0.189620E+11 | 0.235198E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.120254E+11 | 0.196958E+11 | 0.243734E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.119080E+11 | 0.194649E+11 | 0.238372E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.116025E+11 | 0.190610E+11 | 0.239653E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.144308E+12 | 0.236053E+12 | 0.289613E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.109099E+11 | 0.178655E+11 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.130364E+11 | 0.212293E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.120254E+11 | 0.196958E+11 | 0.243680E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.109099E+11 | 0.178655E+11 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.130364E+11 | 0.212293E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.115676E+11 | 0.189620E+11 | 0.235305E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.125309E+11 | 0.204625E+11 | 0.248614E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.124961E+11 | 0.203636E+11 | 0.244159E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.116025E+11 | 0.190610E+11 | 0.239707E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.130364E+11 | 0.212293E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.115676E+11 | 0.189620E+11 | 0.235198E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.120254E+11 | 0.196958E+11 | 0.243734E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.119080E+11 | 0.194649E+11 | 0.238372E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.116025E+11 | 0.190610E+11 | 0.239653E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.144308E+12 | 0.236053E+12 | 0.289613E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.109099E+11 | 0.178655E+11 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.130364E+11 | 0.212293E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150991E+10 | 0.155608E+10 | 0.305979E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6518922.91 | 0.167201E+09 |
February | 0.136985E+10 | 0.134429E+10 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12121136.24 | 0.228988E+09 |
March | 0.163685E+10 | 0.152761E+10 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14178398.75 | 0.191136E+09 |
April | 0.145243E+10 | 0.133733E+10 | 0.295462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 32251929.27 | 66676320.90 |
May | 0.157338E+10 | 0.140758E+10 | 0.312174E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 81149542.44 | 28560070.58 |
June | 0.156900E+10 | 0.139904E+10 | 0.306580E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.100250E+09 | 5232548.32 |
July | 0.145680E+10 | 0.130500E+10 | 0.300989E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 90642330.73 | 4938790.75 |
August | 0.163685E+10 | 0.147509E+10 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.109666E+09 | 2467993.83 |
September | 0.145243E+10 | 0.136495E+10 | 0.295328E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.100083E+09 | 8215917.51 |
October | 0.150991E+10 | 0.146267E+10 | 0.306046E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 68035670.34 | 15624242.47 |
November | 0.149516E+10 | 0.150167E+10 | 0.299314E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 31710884.13 | 0.134710E+09 |
December | 0.145680E+10 | 0.152662E+10 | 0.300922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9960208.59 | 0.167950E+09 |
Annual Sum or Average | 0.181194E+11 | 0.172079E+11 | 0.363654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.656568E+09 | 0.102170E+10 |
Minimum of Months | 0.136985E+10 | 0.130500E+10 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6518922.91 | 2467993.83 |
Maximum of Months | 0.163685E+10 | 0.155608E+10 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.109666E+09 | 0.228988E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.978000E+09 | 0.197184E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3910204.97 | 0.114114E+09 |
February | 0.882782E+09 | 0.856952E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8136998.16 | 0.151873E+09 |
March | 0.105485E+10 | 0.972653E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10186203.91 | 0.119781E+09 |
April | 0.936002E+09 | 0.862224E+09 | 0.190407E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22037638.10 | 35781473.62 |
May | 0.101394E+10 | 0.914164E+09 | 0.201177E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 57654903.44 | 17503139.40 |
June | 0.101113E+10 | 0.910731E+09 | 0.197572E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 73149351.56 | 2388169.82 |
July | 0.938820E+09 | 0.848671E+09 | 0.193969E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 64803946.29 | 2320766.31 |
August | 0.105485E+10 | 0.951322E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 81460757.17 | 750835.08 |
September | 0.936002E+09 | 0.878172E+09 | 0.190321E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 67902590.63 | 4986636.19 |
October | 0.973041E+09 | 0.927004E+09 | 0.197228E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 48602966.38 | 8421116.93 |
November | 0.963541E+09 | 0.956291E+09 | 0.192889E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 25238952.87 | 87159551.35 |
December | 0.938820E+09 | 0.968600E+09 | 0.193926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8253414.68 | 0.101892E+09 |
Annual Sum or Average | 0.116768E+11 | 0.110248E+11 | 0.234352E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.471338E+09 | 0.646973E+09 |
Minimum of Months | 0.882782E+09 | 0.848671E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3910204.97 | 750835.08 |
Maximum of Months | 0.105485E+10 | 0.978000E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 81460757.17 | 0.151873E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150994E+10 | 0.146558E+10 | 0.305983E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4168855.18 | 0.193812E+09 |
February | 0.136988E+10 | 0.130163E+10 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9189368.39 | 0.260245E+09 |
March | 0.163688E+10 | 0.150809E+10 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12155062.41 | 0.210390E+09 |
April | 0.145246E+10 | 0.134196E+10 | 0.295467E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 27496760.66 | 72419279.04 |
May | 0.157341E+10 | 0.142580E+10 | 0.312179E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 81732397.41 | 28062617.25 |
June | 0.156904E+10 | 0.142808E+10 | 0.306585E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.102694E+09 | 5173047.08 |
July | 0.145684E+10 | 0.132364E+10 | 0.300994E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 92311140.32 | 4746861.16 |
August | 0.163688E+10 | 0.148321E+10 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.108065E+09 | 2602699.89 |
September | 0.145246E+10 | 0.135921E+10 | 0.295333E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 91129905.19 | 9703692.51 |
October | 0.150994E+10 | 0.142707E+10 | 0.306051E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 54277303.62 | 22850734.62 |
November | 0.149520E+10 | 0.144131E+10 | 0.299318E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23634148.56 | 0.159318E+09 |
December | 0.145684E+10 | 0.145014E+10 | 0.300927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5845584.74 | 0.189973E+09 |
Annual Sum or Average | 0.181198E+11 | 0.169557E+11 | 0.363660E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.612700E+09 | 0.115930E+10 |
Minimum of Months | 0.136988E+10 | 0.130163E+10 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4168855.18 | 2602699.89 |
Maximum of Months | 0.163688E+10 | 0.150809E+10 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.108065E+09 | 0.260245E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.966155E+09 | 0.197183E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4077942.00 | 0.126279E+09 |
February | 0.882782E+09 | 0.848178E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6631277.16 | 0.189408E+09 |
March | 0.105485E+10 | 0.982490E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8396669.58 | 0.169806E+09 |
April | 0.936002E+09 | 0.861135E+09 | 0.190406E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17034001.26 | 74147720.92 |
May | 0.101394E+10 | 0.917287E+09 | 0.201175E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 51411626.92 | 29257081.29 |
June | 0.101113E+10 | 0.915555E+09 | 0.197570E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 62143841.85 | 6122449.99 |
July | 0.938820E+09 | 0.851828E+09 | 0.193968E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 55196390.28 | 5857820.91 |
August | 0.105485E+10 | 0.959102E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 61755691.18 | 4112331.06 |
September | 0.936002E+09 | 0.880731E+09 | 0.190319E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 62169544.53 | 7841950.89 |
October | 0.973041E+09 | 0.935934E+09 | 0.197226E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 39651155.70 | 18644420.41 |
November | 0.963541E+09 | 0.941668E+09 | 0.192888E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17112280.98 | 0.115341E+09 |
December | 0.938820E+09 | 0.947339E+09 | 0.193924E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4788326.61 | 0.143710E+09 |
Annual Sum or Average | 0.116768E+11 | 0.110074E+11 | 0.234351E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.390369E+09 | 0.890527E+09 |
Minimum of Months | 0.882782E+09 | 0.848178E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4077942.00 | 4112331.06 |
Maximum of Months | 0.105485E+10 | 0.982490E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 62169544.53 | 0.189408E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150991E+10 | 0.154804E+10 | 0.305979E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21994527.05 | 0.319438E+09 |
February | 0.136985E+10 | 0.133903E+10 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 33593334.12 | 0.432407E+09 |
March | 0.163685E+10 | 0.152320E+10 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 34263294.61 | 0.401738E+09 |
April | 0.145243E+10 | 0.133582E+10 | 0.295462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 76589436.83 | 0.181256E+09 |
May | 0.157338E+10 | 0.140640E+10 | 0.312174E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.176174E+09 | 77901498.97 |
June | 0.156900E+10 | 0.139590E+10 | 0.306580E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.210759E+09 | 23677840.91 |
July | 0.145680E+10 | 0.130374E+10 | 0.300989E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.199399E+09 | 20823702.30 |
August | 0.163685E+10 | 0.147370E+10 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.238641E+09 | 11632300.67 |
September | 0.145243E+10 | 0.136206E+10 | 0.295328E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.222423E+09 | 23270582.78 |
October | 0.150991E+10 | 0.145805E+10 | 0.306046E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.147634E+09 | 48012954.19 |
November | 0.149516E+10 | 0.149611E+10 | 0.299314E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 66697822.62 | 0.270558E+09 |
December | 0.145680E+10 | 0.152136E+10 | 0.300922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 27115234.79 | 0.324677E+09 |
Annual Sum or Average | 0.181194E+11 | 0.171634E+11 | 0.363654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.145529E+10 | 0.213539E+10 |
Minimum of Months | 0.136985E+10 | 0.130374E+10 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21994527.05 | 11632300.67 |
Maximum of Months | 0.163685E+10 | 0.154804E+10 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.238641E+09 | 0.432407E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.715730E+09 | 0.975956E+09 | 0.197184E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10372263.57 | 0.234717E+09 |
February | 0.649041E+09 | 0.854981E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19280627.94 | 0.313120E+09 |
March | 0.773965E+09 | 0.971761E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21170652.57 | 0.293369E+09 |
April | 0.688021E+09 | 0.861606E+09 | 0.190407E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 43570310.95 | 0.133508E+09 |
May | 0.744847E+09 | 0.913092E+09 | 0.201177E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.120133E+09 | 55185438.41 |
June | 0.742030E+09 | 0.909114E+09 | 0.197572E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.144553E+09 | 16944145.06 |
July | 0.690839E+09 | 0.847382E+09 | 0.193969E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.133086E+09 | 15341017.94 |
August | 0.773965E+09 | 0.950134E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.160310E+09 | 7975293.96 |
September | 0.688021E+09 | 0.876986E+09 | 0.190321E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.145911E+09 | 17104484.09 |
October | 0.715730E+09 | 0.925803E+09 | 0.197228E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 95516740.36 | 36050744.89 |
November | 0.708685E+09 | 0.953715E+09 | 0.192889E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 44322097.49 | 0.199461E+09 |
December | 0.690839E+09 | 0.965929E+09 | 0.193926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17842524.81 | 0.224259E+09 |
Annual Sum or Average | 0.858171E+10 | 0.110065E+11 | 0.234352E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.956068E+09 | 0.154704E+10 |
Minimum of Months | 0.649041E+09 | 0.847382E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10372263.57 | 7975293.96 |
Maximum of Months | 0.773965E+09 | 0.975956E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.160310E+09 | 0.313120E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150994E+10 | 0.146453E+10 | 0.305983E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8529479.93 | 0.434300E+09 |
February | 0.136988E+10 | 0.130047E+10 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19484452.18 | 0.569212E+09 |
March | 0.163688E+10 | 0.150564E+10 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 26387445.24 | 0.491484E+09 |
April | 0.145246E+10 | 0.134062E+10 | 0.295467E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 62541358.17 | 0.206747E+09 |
May | 0.157341E+10 | 0.142356E+10 | 0.312179E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.178073E+09 | 77284155.47 |
June | 0.156904E+10 | 0.142477E+10 | 0.306585E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.217659E+09 | 22339490.46 |
July | 0.145684E+10 | 0.132180E+10 | 0.300994E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.204165E+09 | 19653089.31 |
August | 0.163688E+10 | 0.148112E+10 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.232040E+09 | 12307962.72 |
September | 0.145246E+10 | 0.135778E+10 | 0.295333E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.198895E+09 | 28786973.16 |
October | 0.150994E+10 | 0.142401E+10 | 0.306051E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.113497E+09 | 77244415.82 |
November | 0.149520E+10 | 0.143833E+10 | 0.299318E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 46115660.51 | 0.375295E+09 |
December | 0.145684E+10 | 0.144886E+10 | 0.300927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12350305.43 | 0.436195E+09 |
Annual Sum or Average | 0.181198E+11 | 0.169315E+11 | 0.363660E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.131974E+10 | 0.275085E+10 |
Minimum of Months | 0.136988E+10 | 0.130047E+10 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8529479.93 | 12307962.72 |
Maximum of Months | 0.163688E+10 | 0.150564E+10 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.232040E+09 | 0.569212E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.964325E+09 | 0.197183E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13981501.27 | 0.235560E+09 |
February | 0.882782E+09 | 0.846551E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17893492.87 | 0.339479E+09 |
March | 0.105485E+10 | 0.980185E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21381783.21 | 0.336083E+09 |
April | 0.936002E+09 | 0.860252E+09 | 0.190406E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 43654394.29 | 0.171591E+09 |
May | 0.101394E+10 | 0.915468E+09 | 0.201175E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.114307E+09 | 73811385.73 |
June | 0.101113E+10 | 0.913262E+09 | 0.197570E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.137287E+09 | 20895220.49 |
July | 0.938820E+09 | 0.849555E+09 | 0.193968E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.129299E+09 | 19035082.61 |
August | 0.105485E+10 | 0.957318E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.147916E+09 | 11358771.97 |
September | 0.936002E+09 | 0.878533E+09 | 0.190319E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.139017E+09 | 20267548.33 |
October | 0.973041E+09 | 0.934074E+09 | 0.197226E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 90293966.52 | 48671181.68 |
November | 0.963541E+09 | 0.939147E+09 | 0.192888E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 42092494.05 | 0.208390E+09 |
December | 0.938820E+09 | 0.945111E+09 | 0.193924E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15314663.10 | 0.252719E+09 |
Annual Sum or Average | 0.116768E+11 | 0.109838E+11 | 0.234351E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.912438E+09 | 0.173786E+10 |
Minimum of Months | 0.882782E+09 | 0.846551E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13981501.27 | 11358771.97 |
Maximum of Months | 0.105485E+10 | 0.980185E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.147916E+09 | 0.339479E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150991E+10 | 0.154770E+10 | 0.305979E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 27861666.31 | 0.361360E+09 |
February | 0.136985E+10 | 0.133883E+10 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 40001160.58 | 0.497052E+09 |
March | 0.163685E+10 | 0.152316E+10 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 38106744.98 | 0.479598E+09 |
April | 0.145243E+10 | 0.133579E+10 | 0.295462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 86210663.39 | 0.223934E+09 |
May | 0.157338E+10 | 0.140637E+10 | 0.312174E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.204455E+09 | 0.105428E+09 |
June | 0.156900E+10 | 0.139583E+10 | 0.306580E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.247535E+09 | 33964221.20 |
July | 0.145680E+10 | 0.130362E+10 | 0.300989E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.233175E+09 | 29603356.97 |
August | 0.163685E+10 | 0.147356E+10 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.281164E+09 | 15391684.94 |
September | 0.145243E+10 | 0.136199E+10 | 0.295328E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.259223E+09 | 30708830.48 |
October | 0.150991E+10 | 0.145804E+10 | 0.306046E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.172032E+09 | 60426189.69 |
November | 0.149516E+10 | 0.149565E+10 | 0.299314E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 77934961.07 | 0.303773E+09 |
December | 0.145680E+10 | 0.152107E+10 | 0.300922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 31802465.19 | 0.371461E+09 |
Annual Sum or Average | 0.181194E+11 | 0.171616E+11 | 0.363654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.169950E+10 | 0.251270E+10 |
Minimum of Months | 0.136985E+10 | 0.130362E+10 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 27861666.31 | 15391684.94 |
Maximum of Months | 0.163685E+10 | 0.154770E+10 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.281164E+09 | 0.497052E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.975934E+09 | 0.197184E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12465098.95 | 0.270672E+09 |
February | 0.882782E+09 | 0.854981E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22174701.57 | 0.364364E+09 |
March | 0.105485E+10 | 0.971685E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23520270.62 | 0.353978E+09 |
April | 0.936002E+09 | 0.861606E+09 | 0.190407E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 49483231.87 | 0.165714E+09 |
May | 0.101394E+10 | 0.913051E+09 | 0.201177E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.139556E+09 | 74511241.95 |
June | 0.101113E+10 | 0.909073E+09 | 0.197572E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.170998E+09 | 23729052.99 |
July | 0.938820E+09 | 0.847368E+09 | 0.193969E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.157106E+09 | 20849738.55 |
August | 0.105485E+10 | 0.950111E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.189752E+09 | 10329058.78 |
September | 0.936002E+09 | 0.876980E+09 | 0.190321E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.171972E+09 | 22351288.72 |
October | 0.973041E+09 | 0.925731E+09 | 0.197228E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.111107E+09 | 45330213.95 |
November | 0.963541E+09 | 0.953537E+09 | 0.192889E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 51371049.55 | 0.227652E+09 |
December | 0.938820E+09 | 0.965911E+09 | 0.193926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20584743.11 | 0.259280E+09 |
Annual Sum or Average | 0.116768E+11 | 0.110060E+11 | 0.234352E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.112009E+10 | 0.183876E+10 |
Minimum of Months | 0.882782E+09 | 0.847368E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12465098.95 | 10329058.78 |
Maximum of Months | 0.105485E+10 | 0.975934E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.189752E+09 | 0.364364E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150994E+10 | 0.146452E+10 | 0.305983E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10614308.59 | 0.505758E+09 |
February | 0.136988E+10 | 0.130043E+10 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23411171.93 | 0.665713E+09 |
March | 0.163688E+10 | 0.150561E+10 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 30182738.20 | 0.588788E+09 |
April | 0.145246E+10 | 0.134060E+10 | 0.295467E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 71846668.10 | 0.256208E+09 |
May | 0.157341E+10 | 0.142346E+10 | 0.312179E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.206505E+09 | 0.104439E+09 |
June | 0.156904E+10 | 0.142476E+10 | 0.306585E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.254558E+09 | 32267576.24 |
July | 0.145684E+10 | 0.132176E+10 | 0.300994E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.237799E+09 | 28125139.90 |
August | 0.163688E+10 | 0.148105E+10 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.274321E+09 | 16228686.39 |
September | 0.145246E+10 | 0.135778E+10 | 0.295333E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.235919E+09 | 37451296.83 |
October | 0.150994E+10 | 0.142401E+10 | 0.306051E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.136112E+09 | 96598565.63 |
November | 0.149520E+10 | 0.143829E+10 | 0.299318E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 55855449.09 | 0.436490E+09 |
December | 0.145684E+10 | 0.144878E+10 | 0.300927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15038783.08 | 0.510322E+09 |
Annual Sum or Average | 0.181198E+11 | 0.169311E+11 | 0.363660E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.155216E+10 | 0.327839E+10 |
Minimum of Months | 0.136988E+10 | 0.130043E+10 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10614308.59 | 16228686.39 |
Maximum of Months | 0.163688E+10 | 0.150561E+10 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.274321E+09 | 0.665713E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.964128E+09 | 0.197183E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17908947.21 | 0.272873E+09 |
February | 0.882782E+09 | 0.846502E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22674835.82 | 0.397941E+09 |
March | 0.105485E+10 | 0.980142E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 25295785.80 | 0.402648E+09 |
April | 0.936002E+09 | 0.860206E+09 | 0.190406E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 52231563.00 | 0.209093E+09 |
May | 0.101394E+10 | 0.915468E+09 | 0.201175E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.137901E+09 | 95609139.61 |
June | 0.101113E+10 | 0.913252E+09 | 0.197570E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.165786E+09 | 27866250.59 |
July | 0.938820E+09 | 0.849555E+09 | 0.193968E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.155827E+09 | 25001444.70 |
August | 0.105485E+10 | 0.957303E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.178924E+09 | 14300122.49 |
September | 0.936002E+09 | 0.878533E+09 | 0.190319E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.167714E+09 | 25686559.31 |
October | 0.973041E+09 | 0.934064E+09 | 0.197226E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.109478E+09 | 59871135.21 |
November | 0.963541E+09 | 0.939145E+09 | 0.192888E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 51046645.20 | 0.239911E+09 |
December | 0.938820E+09 | 0.945111E+09 | 0.193924E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19013495.27 | 0.293884E+09 |
Annual Sum or Average | 0.116768E+11 | 0.109834E+11 | 0.234351E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.110380E+10 | 0.206469E+10 |
Minimum of Months | 0.882782E+09 | 0.846502E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17908947.21 | 14300122.49 |
Maximum of Months | 0.105485E+10 | 0.980142E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.178924E+09 | 0.402648E+09 |
Report: SpaceGainsMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.174411E+09 | 0.553024E+09 | 0.521915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.158233E+09 | 0.501634E+09 | 0.942813E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.189074E+09 | 0.596080E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.167772E+09 | 0.532421E+09 | 0.201821E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.181743E+09 | 0.574552E+09 | 0.522616E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.181238E+09 | 0.571774E+09 | 0.101086E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.168277E+09 | 0.535199E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.189074E+09 | 0.596080E+09 | 0.208555E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.167772E+09 | 0.532421E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.174411E+09 | 0.553024E+09 | 0.104453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.172708E+09 | 0.546542E+09 | 0.151524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.168277E+09 | 0.535199E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.209299E+10 | 0.662795E+10 | 0.153881E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.158233E+09 | 0.501634E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.189074E+09 | 0.596080E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.174411E+09 | 0.553024E+09 | 0.521915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.158233E+09 | 0.501634E+09 | 0.942813E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.189074E+09 | 0.596080E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.167772E+09 | 0.532421E+09 | 0.201821E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.181743E+09 | 0.574552E+09 | 0.522616E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.181238E+09 | 0.571774E+09 | 0.101086E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.168277E+09 | 0.535199E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.189074E+09 | 0.596080E+09 | 0.208555E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.167772E+09 | 0.532421E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.174411E+09 | 0.553024E+09 | 0.104453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.172708E+09 | 0.546542E+09 | 0.151524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.168277E+09 | 0.535199E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.209299E+10 | 0.662795E+10 | 0.153881E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.158233E+09 | 0.501634E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.189074E+09 | 0.596080E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.174411E+09 | 0.553024E+09 | 0.521915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.158233E+09 | 0.501634E+09 | 0.942813E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.189074E+09 | 0.596080E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.167772E+09 | 0.532421E+09 | 0.201821E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.181743E+09 | 0.574552E+09 | 0.522616E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.181238E+09 | 0.571774E+09 | 0.101086E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.168277E+09 | 0.535199E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.189074E+09 | 0.596080E+09 | 0.208555E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.167772E+09 | 0.532421E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.174411E+09 | 0.553024E+09 | 0.104453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.172708E+09 | 0.546542E+09 | 0.151524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.168277E+09 | 0.535199E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.209299E+10 | 0.662795E+10 | 0.153881E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.158233E+09 | 0.501634E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.189074E+09 | 0.596080E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.377547E+10 | 0.618367E+10 | 0.254202E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.342526E+10 | 0.560905E+10 | 0.459203E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.409289E+10 | 0.666512E+10 | 0.762947E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.363176E+10 | 0.595330E+10 | 0.982982E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.393418E+10 | 0.642439E+10 | 0.254544E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.392325E+10 | 0.639333E+10 | 0.492345E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.364269E+10 | 0.598436E+10 | 0.762947E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.409289E+10 | 0.666512E+10 | 0.101578E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.363176E+10 | 0.595330E+10 | 0.246344E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.377547E+10 | 0.618367E+10 | 0.508746E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.373861E+10 | 0.611120E+10 | 0.738006E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.364269E+10 | 0.598436E+10 | 0.101681E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.453069E+11 | 0.741109E+11 | 0.749486E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.342526E+10 | 0.560905E+10 | 0.246344E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.409289E+10 | 0.666512E+10 | 0.101681E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6556320.29 | 0.390470E+09 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12169879.70 | 0.530009E+09 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17160959.13 | 0.461472E+09 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45262965.07 | 0.185600E+09 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.126653E+09 | 66890944.76 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.166625E+09 | 13001842.38 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.157125E+09 | 14622161.59 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.183616E+09 | 8979086.99 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.167917E+09 | 22805247.01 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.100073E+09 | 46650840.83 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37321720.22 | 0.320300E+09 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12575591.79 | 0.394518E+09 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.103306E+10 | 0.245532E+10 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6556320.29 | 8979086.99 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.183616E+09 | 0.530009E+09 |
Report: SpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17854436.11 | 0.639593E+09 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27618216.39 | 0.854211E+09 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34748149.53 | 0.769730E+09 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 86910211.70 | 0.332703E+09 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.230550E+09 | 0.117850E+09 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.296201E+09 | 27189875.75 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.289270E+09 | 28547082.58 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.334762E+09 | 18297763.64 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.306808E+09 | 40044786.40 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.182613E+09 | 86978672.61 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 70407488.06 | 0.534910E+09 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27105490.13 | 0.634497E+09 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.190485E+10 | 0.408455E+10 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17854436.11 | 18297763.64 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.334762E+09 | 0.854211E+09 |
Report: SpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10295716.79 | 0.633424E+09 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10122864.85 | 0.864042E+09 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13477100.30 | 0.830841E+09 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47599562.51 | 0.376676E+09 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.188148E+09 | 0.139234E+09 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.281053E+09 | 41250119.44 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.257232E+09 | 39656069.55 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.328706E+09 | 22971808.76 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.284063E+09 | 43365340.82 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.165024E+09 | 82485354.76 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 54680163.92 | 0.524639E+09 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15549946.41 | 0.649260E+09 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.165595E+10 | 0.424785E+10 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10122864.85 | 22971808.76 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.328706E+09 | 0.864042E+09 |
Report: PeakSpaceGainsMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 17832.21 | 02-JAN-10:09 | 22950.34 | 02-JAN-08:09 | 13457.54 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 17832.21 | 01-FEB-10:09 | 22950.34 | 01-FEB-08:09 | 13457.54 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 17832.21 | 01-MAR-10:09 | 22950.34 | 01-MAR-08:09 | 13457.54 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 17832.21 | 03-APR-09:09 | 22950.34 | 03-APR-07:10 | 13457.54 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 17832.21 | 01-MAY-09:09 | 22950.34 | 01-MAY-07:10 | 13457.54 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 17832.21 | 01-JUN-09:09 | 22950.34 | 01-JUN-07:10 | 13457.54 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 17832.21 | 03-JUL-09:09 | 22950.34 | 03-JUL-07:10 | 13457.54 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 17832.21 | 01-AUG-09:09 | 22950.34 | 01-AUG-07:10 | 13457.54 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 17832.21 | 01-SEP-09:09 | 22950.34 | 01-SEP-07:10 | 13457.54 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 17832.21 | 02-OCT-09:09 | 22950.34 | 02-OCT-07:10 | 13457.54 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 17832.21 | 01-NOV-09:09 | 22950.34 | 01-NOV-07:10 | 13457.54 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 17832.21 | 01-DEC-10:09 | 22950.34 | 01-DEC-08:09 | 13457.54 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 17832.21 | 22950.34 | 13457.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 17832.21 | 22950.34 | 13457.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 16014.58 | 02-JAN-10:09 | 20611.01 | 02-JAN-08:09 | 17206.63 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 16014.58 | 01-FEB-10:09 | 20611.01 | 01-FEB-08:09 | 17206.63 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 16014.58 | 01-MAR-10:09 | 20611.01 | 01-MAR-08:09 | 17206.63 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 16014.58 | 03-APR-09:09 | 20611.01 | 03-APR-07:10 | 17206.63 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 16014.58 | 01-MAY-09:09 | 20611.01 | 01-MAY-07:10 | 17206.63 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 16014.58 | 01-JUN-09:09 | 20611.01 | 01-JUN-07:10 | 17206.63 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 16014.58 | 03-JUL-09:09 | 20611.01 | 03-JUL-07:10 | 17206.63 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 16014.58 | 01-AUG-09:09 | 20611.01 | 01-AUG-07:10 | 17206.63 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 16014.58 | 01-SEP-09:09 | 20611.01 | 01-SEP-07:10 | 17206.63 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 16014.58 | 02-OCT-09:09 | 20611.01 | 02-OCT-07:10 | 17206.63 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 16014.58 | 01-NOV-09:09 | 20611.01 | 01-NOV-07:10 | 17206.63 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 16014.58 | 01-DEC-10:09 | 20611.01 | 01-DEC-08:09 | 17206.63 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 16014.58 | 20611.01 | 17206.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 16014.58 | 20611.01 | 17206.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 16014.58 | 02-JAN-10:09 | 20611.01 | 02-JAN-08:09 | 17206.56 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 16014.58 | 01-FEB-10:09 | 20611.01 | 01-FEB-08:09 | 17206.56 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 16014.58 | 01-MAR-10:09 | 20611.01 | 01-MAR-08:09 | 17206.56 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 16014.58 | 03-APR-09:09 | 20611.01 | 03-APR-07:10 | 17206.56 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 16014.58 | 01-MAY-09:09 | 20611.01 | 01-MAY-07:10 | 17206.56 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 16014.58 | 01-JUN-09:09 | 20611.01 | 01-JUN-07:10 | 17206.56 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 16014.58 | 03-JUL-09:09 | 20611.01 | 03-JUL-07:10 | 17206.56 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 16014.58 | 01-AUG-09:09 | 20611.01 | 01-AUG-07:10 | 17206.56 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 16014.58 | 01-SEP-09:09 | 20611.01 | 01-SEP-07:10 | 17206.56 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 16014.58 | 02-OCT-09:09 | 20611.01 | 02-OCT-07:10 | 17206.56 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 16014.58 | 01-NOV-09:09 | 20611.01 | 01-NOV-07:10 | 17206.56 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 16014.58 | 01-DEC-10:09 | 20611.01 | 01-DEC-08:09 | 17206.56 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 16014.58 | 20611.01 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 16014.58 | 20611.01 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 16014.58 | 02-JAN-10:09 | 20611.01 | 02-JAN-08:09 | 17206.56 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 16014.58 | 01-FEB-10:09 | 20611.01 | 01-FEB-08:09 | 17206.56 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 16014.58 | 01-MAR-10:09 | 20611.01 | 01-MAR-08:09 | 17206.56 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 16014.58 | 03-APR-09:09 | 20611.01 | 03-APR-07:10 | 17206.56 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 16014.58 | 01-MAY-09:09 | 20611.01 | 01-MAY-07:10 | 17206.56 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 16014.58 | 01-JUN-09:09 | 20611.01 | 01-JUN-07:10 | 17206.56 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 16014.58 | 03-JUL-09:09 | 20611.01 | 03-JUL-07:10 | 17206.56 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 16014.58 | 01-AUG-09:09 | 20611.01 | 01-AUG-07:10 | 17206.56 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 16014.58 | 01-SEP-09:09 | 20611.01 | 01-SEP-07:10 | 17206.56 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 16014.58 | 02-OCT-09:09 | 20611.01 | 02-OCT-07:10 | 17206.56 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 16014.58 | 01-NOV-09:09 | 20611.01 | 01-NOV-07:10 | 17206.56 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 16014.58 | 01-DEC-10:09 | 20611.01 | 01-DEC-08:09 | 17206.56 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 16014.58 | 20611.01 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 16014.58 | 20611.01 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.79 | 02-JAN-10:09 | 2255.20 | 04-JAN-16:30 | 2160.55 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 102.94 | 15-JAN-14:00 | 473.41 | 24-JAN-03:00 |
February | 2010.79 | 01-FEB-10:09 | 1803.00 | 03-FEB-16:00 | 2160.55 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 97.52 | 20-FEB-15:30 | 793.69 | 04-FEB-05:00 |
March | 2010.79 | 01-MAR-10:09 | 2135.72 | 15-MAR-07:10 | 2160.55 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 117.23 | 05-MAR-13:43 | 779.35 | 16-MAR-02:00 |
April | 2010.79 | 03-APR-09:09 | 1803.00 | 12-APR-07:10 | 2160.55 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 266.96 | 15-APR-17:10 | 253.35 | 18-APR-24:00 |
May | 2010.79 | 01-MAY-09:09 | 1470.28 | 25-MAY-07:10 | 2160.55 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 404.13 | 29-MAY-15:55 | 152.66 | 25-MAY-04:10 |
June | 2010.79 | 01-JUN-09:09 | 2255.20 | 15-JUN-07:10 | 2160.55 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 250.58 | 25-JUN-14:00 | 146.25 | 18-JUN-20:00 |
July | 2010.79 | 03-JUL-09:09 | 1470.28 | 05-JUL-07:10 | 2160.55 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 315.86 | 30-JUL-15:50 | 127.57 | 02-JUL-16:00 |
August | 2010.79 | 01-AUG-09:09 | 1803.00 | 28-AUG-07:10 | 2160.55 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 278.39 | 13-AUG-13:00 | 142.57 | 14-AUG-03:30 |
September | 2010.79 | 01-SEP-09:09 | 2587.92 | 27-SEP-07:10 | 2160.55 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 287.85 | 17-SEP-13:50 | 80.00 | 19-SEP-23:50 |
October | 2010.79 | 02-OCT-09:09 | 2255.20 | 18-OCT-07:10 | 2160.55 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 225.37 | 29-OCT-14:10 | 135.77 | 16-OCT-03:00 |
November | 2010.79 | 01-NOV-09:09 | 2255.20 | 10-NOV-16:00 | 2160.55 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 113.10 | 22-NOV-22:02 | 800.56 | 11-NOV-09:00 |
December | 2010.79 | 01-DEC-10:09 | 2587.92 | 15-DEC-16:30 | 2160.55 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 203.65 | 10-DEC-14:40 | 741.13 | 15-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.79 | 1470.28 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 97.52 | 80.00 | |||||
Maximum of Months | 2010.79 | 2587.92 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 404.13 | 800.56 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 1453.34 | 04-JAN-16:30 | 1392.34 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 63.11 | 29-JAN-12:15 | 320.87 | 08-JAN-10:00 |
February | 1295.83 | 01-FEB-10:09 | 1161.92 | 01-FEB-16:00 | 1392.34 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 71.84 | 19-FEB-15:40 | 521.52 | 04-FEB-05:00 |
March | 1295.83 | 01-MAR-10:09 | 947.51 | 06-MAR-16:00 | 1392.34 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 104.69 | 05-MAR-14:15 | 522.63 | 16-MAR-02:00 |
April | 1295.83 | 03-APR-09:09 | 1161.92 | 12-APR-07:10 | 1392.34 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 184.68 | 15-APR-17:10 | 165.30 | 18-APR-24:00 |
May | 1295.83 | 01-MAY-09:09 | 870.51 | 10-MAY-14:20 | 1392.34 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 284.58 | 29-MAY-16:00 | 109.71 | 07-MAY-24:00 |
June | 1295.83 | 01-JUN-09:09 | 1453.34 | 15-JUN-07:10 | 1392.34 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 183.06 | 17-JUN-18:30 | 81.35 | 18-JUN-20:00 |
July | 1295.83 | 03-JUL-09:09 | 870.51 | 05-JUL-07:10 | 1392.34 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 217.73 | 30-JUL-15:50 | 88.85 | 02-JUL-16:00 |
August | 1295.83 | 01-AUG-09:09 | 1161.92 | 28-AUG-07:10 | 1392.34 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 210.87 | 13-AUG-13:00 | 74.88 | 14-AUG-03:30 |
September | 1295.83 | 01-SEP-09:09 | 1667.75 | 27-SEP-07:10 | 1392.34 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 193.50 | 17-SEP-16:50 | 50.56 | 19-SEP-23:50 |
October | 1295.83 | 02-OCT-09:09 | 1453.34 | 18-OCT-07:10 | 1392.34 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 162.60 | 29-OCT-14:10 | 85.40 | 16-OCT-03:00 |
November | 1295.83 | 01-NOV-09:09 | 1453.34 | 10-NOV-16:49 | 1392.34 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 88.43 | 23-NOV-12:20 | 618.76 | 11-NOV-09:00 |
December | 1295.83 | 01-DEC-10:09 | 1667.75 | 15-DEC-16:30 | 1392.34 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 165.99 | 10-DEC-14:40 | 483.92 | 15-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 870.51 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 63.11 | 50.56 | |||||
Maximum of Months | 1295.83 | 1667.75 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 284.58 | 618.76 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.83 | 02-JAN-10:09 | 2255.25 | 04-JAN-16:49 | 2160.58 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 58.48 | 07-JAN-13:00 | 502.07 | 24-JAN-03:00 |
February | 2010.83 | 01-FEB-10:09 | 1470.31 | 08-FEB-16:40 | 2160.58 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 70.57 | 02-FEB-14:00 | 802.28 | 04-FEB-05:00 |
March | 2010.83 | 01-MAR-10:09 | 1803.04 | 13-MAR-07:10 | 2160.58 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 87.80 | 05-MAR-13:45 | 809.28 | 16-MAR-02:00 |
April | 2010.83 | 03-APR-09:09 | 1803.04 | 12-APR-07:10 | 2160.58 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 249.15 | 15-APR-17:10 | 260.52 | 18-APR-24:00 |
May | 2010.83 | 01-MAY-09:09 | 1470.31 | 25-MAY-07:10 | 2160.58 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 404.70 | 29-MAY-15:55 | 150.44 | 07-MAY-24:00 |
June | 2010.83 | 01-JUN-09:09 | 2255.25 | 15-JUN-07:10 | 2160.58 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 250.38 | 25-JUN-14:00 | 152.80 | 18-JUN-20:00 |
July | 2010.83 | 03-JUL-09:09 | 1470.31 | 05-JUL-07:10 | 2160.58 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 313.11 | 30-JUL-15:48 | 127.00 | 02-JUL-16:00 |
August | 2010.83 | 01-AUG-09:09 | 1803.04 | 28-AUG-07:10 | 2160.58 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 269.75 | 13-AUG-12:20 | 141.91 | 14-AUG-03:30 |
September | 2010.83 | 01-SEP-09:09 | 2587.98 | 27-SEP-07:10 | 2160.58 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 263.30 | 17-SEP-16:45 | 97.37 | 19-SEP-23:50 |
October | 2010.83 | 02-OCT-09:09 | 2255.25 | 18-OCT-07:10 | 2160.58 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 184.58 | 29-OCT-14:06 | 160.29 | 16-OCT-03:00 |
November | 2010.83 | 01-NOV-09:09 | 2255.25 | 29-NOV-16:00 | 2160.58 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 107.98 | 22-NOV-22:02 | 912.72 | 11-NOV-09:00 |
December | 2010.83 | 01-DEC-10:09 | 2587.98 | 15-DEC-16:40 | 2160.58 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 127.83 | 10-DEC-14:36 | 769.83 | 15-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.83 | 1470.31 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 58.48 | 97.37 | |||||
Maximum of Months | 2010.83 | 2587.98 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 404.70 | 912.72 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 1453.34 | 04-JAN-16:49 | 1392.33 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 74.55 | 29-JAN-12:15 | 351.89 | 24-JAN-03:00 |
February | 1295.83 | 01-FEB-10:09 | 1161.92 | 01-FEB-08:09 | 1392.33 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 47.04 | 02-FEB-14:00 | 578.56 | 04-FEB-05:00 |
March | 1295.83 | 01-MAR-10:09 | 1453.34 | 14-MAR-07:10 | 1392.33 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 71.48 | 05-MAR-13:43 | 605.95 | 16-MAR-02:00 |
April | 1295.83 | 03-APR-09:09 | 1453.34 | 12-APR-07:10 | 1392.33 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 142.61 | 15-APR-17:04 | 216.11 | 18-APR-24:00 |
May | 1295.83 | 01-MAY-09:09 | 1161.92 | 25-MAY-07:10 | 1392.33 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 251.81 | 29-MAY-15:53 | 125.59 | 25-MAY-04:10 |
June | 1295.83 | 01-JUN-09:09 | 1667.75 | 15-JUN-07:10 | 1392.33 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 168.71 | 25-JUN-13:58 | 134.23 | 18-JUN-20:00 |
July | 1295.83 | 03-JUL-09:09 | 1161.92 | 05-JUL-07:10 | 1392.33 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 220.94 | 30-JUL-15:46 | 105.20 | 04-JUL-03:00 |
August | 1295.83 | 01-AUG-09:09 | 1453.34 | 28-AUG-07:10 | 1392.33 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 200.57 | 13-AUG-12:20 | 145.08 | 14-AUG-03:30 |
September | 1295.83 | 01-SEP-09:09 | 1667.75 | 27-SEP-07:10 | 1392.33 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 187.87 | 17-SEP-12:50 | 86.98 | 19-SEP-23:50 |
October | 1295.83 | 02-OCT-09:09 | 1453.34 | 18-OCT-07:10 | 1392.33 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 153.58 | 29-OCT-12:10 | 119.21 | 16-OCT-03:00 |
November | 1295.83 | 01-NOV-09:09 | 1453.34 | 03-NOV-07:10 | 1392.33 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 68.44 | 22-NOV-22:02 | 615.34 | 11-NOV-09:00 |
December | 1295.83 | 01-DEC-10:09 | 1667.75 | 15-DEC-16:40 | 1392.33 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 100.14 | 10-DEC-13:56 | 568.04 | 15-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 1161.92 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 47.04 | 86.98 | |||||
Maximum of Months | 1295.83 | 1667.75 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 251.81 | 615.34 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.79 | 02-JAN-10:09 | 2255.20 | 04-JAN-16:40 | 2160.55 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 419.00 | 15-JAN-14:10 | 945.10 | 24-JAN-03:00 |
February | 2010.79 | 01-FEB-10:09 | 1803.00 | 03-FEB-16:00 | 2160.55 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 340.34 | 20-FEB-14:50 | 1680.36 | 04-FEB-05:13 |
March | 2010.79 | 01-MAR-10:09 | 2135.72 | 15-MAR-07:10 | 2160.55 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 309.18 | 05-MAR-14:00 | 1564.17 | 16-MAR-02:00 |
April | 2010.79 | 03-APR-09:09 | 1803.00 | 12-APR-07:10 | 2160.55 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 642.87 | 15-APR-17:01 | 551.15 | 18-APR-23:53 |
May | 2010.79 | 01-MAY-09:09 | 1470.28 | 25-MAY-07:10 | 2160.55 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 896.59 | 29-MAY-15:45 | 333.08 | 25-MAY-05:00 |
June | 2010.79 | 01-JUN-09:09 | 2255.20 | 15-JUN-07:10 | 2160.55 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 568.26 | 25-JUN-14:00 | 367.13 | 18-JUN-20:00 |
July | 2010.79 | 03-JUL-09:09 | 1470.28 | 05-JUL-07:10 | 2160.55 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 657.60 | 30-JUL-16:08 | 286.61 | 04-JUL-02:55 |
August | 2010.79 | 01-AUG-09:09 | 1803.00 | 28-AUG-07:10 | 2160.55 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 674.59 | 13-AUG-12:50 | 413.06 | 14-AUG-02:55 |
September | 2010.79 | 01-SEP-09:09 | 2587.92 | 27-SEP-07:10 | 2160.55 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 683.09 | 17-SEP-14:00 | 191.72 | 19-SEP-24:00 |
October | 2010.79 | 02-OCT-09:09 | 2255.20 | 18-OCT-07:10 | 2160.55 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 510.30 | 29-OCT-14:00 | 300.19 | 01-OCT-07:00 |
November | 2010.79 | 01-NOV-09:09 | 2255.20 | 21-NOV-16:00 | 2160.55 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 281.69 | 19-NOV-10:40 | 1616.65 | 11-NOV-09:00 |
December | 2010.79 | 01-DEC-10:09 | 2587.92 | 15-DEC-16:30 | 2160.55 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 481.42 | 10-DEC-14:50 | 1490.69 | 15-DEC-05:55 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.79 | 1470.28 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 281.69 | 191.72 | |||||
Maximum of Months | 2010.79 | 2587.92 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 896.59 | 1680.36 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1239.33 | 02-JAN-08:09 | 1453.34 | 04-JAN-16:30 | 1392.34 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 171.75 | 15-JAN-14:50 | 700.90 | 08-JAN-09:53 |
February | 1239.33 | 01-FEB-08:09 | 1161.92 | 01-FEB-16:00 | 1392.34 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 182.76 | 19-FEB-16:10 | 1112.47 | 04-FEB-05:19 |
March | 1239.33 | 01-MAR-08:09 | 947.51 | 14-MAR-07:10 | 1392.34 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 238.67 | 05-MAR-14:00 | 1101.52 | 16-MAR-02:00 |
April | 1239.33 | 03-APR-07:10 | 1161.92 | 12-APR-07:10 | 1392.34 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 415.50 | 15-APR-17:01 | 387.02 | 18-APR-23:53 |
May | 1239.33 | 01-MAY-07:10 | 870.51 | 10-MAY-14:20 | 1392.34 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 610.55 | 29-MAY-16:25 | 239.92 | 07-MAY-18:20 |
June | 1239.33 | 01-JUN-07:10 | 1453.34 | 15-JUN-07:10 | 1392.34 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 407.52 | 25-JUN-14:00 | 235.52 | 18-JUN-20:00 |
July | 1239.33 | 03-JUL-07:10 | 870.51 | 05-JUL-07:10 | 1392.34 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 474.22 | 30-JUL-16:08 | 229.94 | 02-JUL-15:40 |
August | 1239.33 | 01-AUG-07:10 | 1161.92 | 28-AUG-07:10 | 1392.34 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 444.67 | 13-AUG-12:50 | 274.70 | 14-AUG-02:55 |
September | 1239.33 | 01-SEP-07:10 | 1667.75 | 27-SEP-07:10 | 1392.34 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 485.29 | 17-SEP-13:57 | 139.38 | 19-SEP-24:00 |
October | 1239.33 | 02-OCT-07:10 | 1453.34 | 18-OCT-07:10 | 1392.34 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 369.84 | 29-OCT-14:20 | 206.40 | 01-OCT-07:00 |
November | 1239.33 | 01-NOV-07:10 | 1453.34 | 10-NOV-16:00 | 1392.34 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 190.08 | 22-NOV-22:02 | 1314.55 | 11-NOV-09:00 |
December | 1239.33 | 01-DEC-08:09 | 1667.75 | 15-DEC-16:30 | 1392.34 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 335.96 | 10-DEC-14:30 | 1013.39 | 15-DEC-05:55 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1239.33 | 870.51 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 171.75 | 139.38 | |||||
Maximum of Months | 1239.33 | 1667.75 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 610.55 | 1314.55 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.83 | 02-JAN-10:09 | 2255.25 | 04-JAN-16:49 | 2160.58 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 133.67 | 07-JAN-13:00 | 1091.18 | 24-JAN-03:00 |
February | 2010.83 | 01-FEB-10:09 | 1470.31 | 08-FEB-16:40 | 2160.58 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 161.31 | 02-FEB-14:00 | 1703.19 | 04-FEB-05:00 |
March | 2010.83 | 01-MAR-10:09 | 1803.04 | 13-MAR-07:10 | 2160.58 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 229.20 | 05-MAR-14:00 | 1740.03 | 16-MAR-02:00 |
April | 2010.83 | 03-APR-09:09 | 1803.04 | 12-APR-07:10 | 2160.58 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 589.58 | 15-APR-17:01 | 587.07 | 18-APR-23:53 |
May | 2010.83 | 01-MAY-09:09 | 1470.31 | 25-MAY-07:10 | 2160.58 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 896.41 | 29-MAY-15:45 | 333.41 | 25-MAY-05:00 |
June | 2010.83 | 01-JUN-09:09 | 2255.25 | 15-JUN-07:10 | 2160.58 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 567.50 | 25-JUN-14:00 | 372.26 | 18-JUN-20:00 |
July | 2010.83 | 03-JUL-09:09 | 1470.31 | 05-JUL-07:10 | 2160.58 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 645.63 | 30-JUL-16:08 | 276.85 | 04-JUL-02:55 |
August | 2010.83 | 01-AUG-09:09 | 1803.04 | 28-AUG-07:10 | 2160.58 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 630.68 | 13-AUG-12:50 | 426.03 | 14-AUG-02:55 |
September | 2010.83 | 01-SEP-09:09 | 2587.98 | 27-SEP-07:10 | 2160.58 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 581.67 | 17-SEP-13:55 | 240.07 | 19-SEP-23:20 |
October | 2010.83 | 02-OCT-09:09 | 2255.25 | 18-OCT-07:10 | 2160.58 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 404.12 | 29-OCT-13:54 | 371.29 | 16-OCT-03:00 |
November | 2010.83 | 01-NOV-09:09 | 2255.25 | 29-NOV-16:00 | 2160.58 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 244.30 | 22-NOV-22:02 | 1930.32 | 11-NOV-09:00 |
December | 2010.83 | 01-DEC-10:09 | 2587.98 | 15-DEC-16:40 | 2160.58 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 279.11 | 10-DEC-14:50 | 1651.60 | 15-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.83 | 1470.31 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 133.67 | 240.07 | |||||
Maximum of Months | 2010.83 | 2587.98 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 896.41 | 1930.32 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 1453.34 | 04-JAN-16:00 | 1392.33 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 297.58 | 15-JAN-12:10 | 685.36 | 24-JAN-03:00 |
February | 1295.83 | 01-FEB-10:09 | 1161.92 | 01-FEB-08:09 | 1392.33 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 129.47 | 20-FEB-13:30 | 1115.93 | 04-FEB-05:12 |
March | 1295.83 | 01-MAR-10:09 | 1453.34 | 14-MAR-07:10 | 1392.33 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 245.47 | 05-MAR-14:00 | 1162.97 | 16-MAR-02:00 |
April | 1295.83 | 03-APR-09:09 | 1453.34 | 12-APR-07:10 | 1392.33 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 354.81 | 16-APR-12:53 | 435.21 | 18-APR-23:53 |
May | 1295.83 | 01-MAY-09:09 | 1161.92 | 25-MAY-07:10 | 1392.33 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 582.62 | 29-MAY-15:44 | 245.05 | 07-MAY-18:20 |
June | 1295.83 | 01-JUN-09:09 | 1667.75 | 15-JUN-07:10 | 1392.33 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 389.37 | 25-JUN-14:00 | 284.64 | 18-JUN-20:00 |
July | 1295.83 | 03-JUL-09:09 | 1161.92 | 05-JUL-07:10 | 1392.33 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 484.58 | 30-JUL-16:08 | 227.93 | 04-JUL-02:55 |
August | 1295.83 | 01-AUG-09:09 | 1453.34 | 28-AUG-07:10 | 1392.33 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 538.23 | 13-AUG-12:50 | 345.80 | 14-AUG-02:55 |
September | 1295.83 | 01-SEP-09:09 | 1667.75 | 27-SEP-07:10 | 1392.33 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 442.72 | 17-SEP-13:55 | 184.75 | 19-SEP-23:20 |
October | 1295.83 | 02-OCT-09:09 | 1453.34 | 18-OCT-07:10 | 1392.33 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 362.79 | 29-OCT-12:00 | 242.80 | 01-OCT-07:00 |
November | 1295.83 | 01-NOV-09:09 | 1453.34 | 03-NOV-07:10 | 1392.33 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 229.28 | 19-NOV-10:40 | 1114.65 | 11-NOV-09:00 |
December | 1295.83 | 01-DEC-10:09 | 1667.75 | 15-DEC-16:40 | 1392.33 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 286.92 | 10-DEC-13:50 | 1041.31 | 15-DEC-05:55 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 1161.92 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 129.47 | 184.75 | |||||
Maximum of Months | 1295.83 | 1667.75 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 582.62 | 1162.97 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.79 | 02-JAN-10:09 | 2255.20 | 04-JAN-16:40 | 2160.55 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 504.43 | 15-JAN-11:52 | 1093.56 | 24-JAN-03:00 |
February | 2010.79 | 01-FEB-10:09 | 1803.00 | 03-FEB-16:00 | 2160.55 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 383.69 | 20-FEB-14:50 | 2087.82 | 04-FEB-05:20 |
March | 2010.79 | 01-MAR-10:09 | 2135.72 | 15-MAR-07:10 | 2160.55 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 339.04 | 05-MAR-14:00 | 1766.35 | 16-MAR-02:00 |
April | 2010.79 | 03-APR-09:09 | 1803.00 | 12-APR-07:10 | 2160.55 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 736.82 | 15-APR-17:01 | 650.73 | 18-APR-23:53 |
May | 2010.79 | 01-MAY-09:09 | 1470.28 | 25-MAY-07:10 | 2160.55 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1104.60 | 29-MAY-15:45 | 473.37 | 07-MAY-18:53 |
June | 2010.79 | 01-JUN-09:09 | 2255.20 | 15-JUN-07:10 | 2160.55 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 692.55 | 25-JUN-13:58 | 514.50 | 18-JUN-20:00 |
July | 2010.79 | 03-JUL-09:09 | 1470.28 | 05-JUL-07:10 | 2160.55 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 856.23 | 30-JUL-16:00 | 405.85 | 02-JUL-16:00 |
August | 2010.79 | 01-AUG-09:09 | 1803.00 | 28-AUG-07:10 | 2160.55 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 772.03 | 13-AUG-12:50 | 521.72 | 14-AUG-02:55 |
September | 2010.79 | 01-SEP-09:09 | 2587.92 | 27-SEP-07:10 | 2160.55 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 796.91 | 17-SEP-13:57 | 251.05 | 19-SEP-23:20 |
October | 2010.79 | 02-OCT-09:09 | 2255.20 | 18-OCT-07:10 | 2160.55 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 573.25 | 29-OCT-13:50 | 389.63 | 01-OCT-07:00 |
November | 2010.79 | 01-NOV-09:09 | 2255.20 | 21-NOV-16:00 | 2160.55 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 336.67 | 19-NOV-11:40 | 1824.11 | 11-NOV-09:00 |
December | 2010.79 | 01-DEC-10:09 | 2587.92 | 15-DEC-16:30 | 2160.55 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 536.78 | 10-DEC-14:50 | 1842.17 | 15-DEC-06:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.79 | 1470.28 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 336.67 | 251.05 | |||||
Maximum of Months | 2010.79 | 2587.92 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 1104.60 | 2087.82 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 1453.34 | 04-JAN-16:30 | 1392.34 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 206.71 | 15-JAN-13:52 | 783.10 | 08-JAN-09:53 |
February | 1295.83 | 01-FEB-10:09 | 1161.92 | 01-FEB-16:00 | 1392.34 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 206.72 | 19-FEB-15:40 | 1391.89 | 04-FEB-05:17 |
March | 1295.83 | 01-MAR-10:09 | 947.51 | 14-MAR-07:10 | 1392.34 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 267.48 | 05-MAR-14:00 | 1252.75 | 16-MAR-02:00 |
April | 1295.83 | 03-APR-09:09 | 1161.92 | 12-APR-07:10 | 1392.34 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 476.58 | 15-APR-17:01 | 458.24 | 18-APR-23:53 |
May | 1295.83 | 01-MAY-09:09 | 870.51 | 10-MAY-14:20 | 1392.34 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 741.13 | 29-MAY-15:45 | 405.84 | 07-MAY-18:53 |
June | 1295.83 | 01-JUN-09:09 | 1453.34 | 15-JUN-07:10 | 1392.34 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 506.40 | 25-JUN-14:00 | 331.08 | 18-JUN-20:00 |
July | 1295.83 | 03-JUL-09:09 | 870.51 | 05-JUL-07:10 | 1392.34 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 613.07 | 30-JUL-16:00 | 304.40 | 02-JUL-16:00 |
August | 1295.83 | 01-AUG-09:09 | 1161.92 | 28-AUG-07:10 | 1392.34 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 530.92 | 20-AUG-12:16 | 340.91 | 14-AUG-02:55 |
September | 1295.83 | 01-SEP-09:09 | 1667.75 | 27-SEP-07:10 | 1392.34 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 566.80 | 17-SEP-13:57 | 180.05 | 19-SEP-23:20 |
October | 1295.83 | 02-OCT-09:09 | 1453.34 | 18-OCT-07:10 | 1392.34 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 435.46 | 29-OCT-13:50 | 265.72 | 01-OCT-07:00 |
November | 1295.83 | 01-NOV-09:09 | 1453.34 | 10-NOV-16:00 | 1392.34 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 232.54 | 22-NOV-22:02 | 1503.61 | 11-NOV-09:00 |
December | 1295.83 | 01-DEC-10:09 | 1667.75 | 15-DEC-16:30 | 1392.34 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 388.07 | 10-DEC-14:30 | 1228.14 | 15-DEC-06:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 870.51 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 206.71 | 180.05 | |||||
Maximum of Months | 1295.83 | 1667.75 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 741.13 | 1503.61 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.83 | 02-JAN-10:09 | 2255.25 | 04-JAN-16:49 | 2160.58 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 161.65 | 07-JAN-13:00 | 1277.54 | 24-JAN-03:00 |
February | 2010.83 | 01-FEB-10:09 | 1470.31 | 08-FEB-16:40 | 2160.58 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 195.07 | 02-FEB-14:00 | 2087.78 | 04-FEB-05:20 |
March | 2010.83 | 01-MAR-10:09 | 1803.04 | 13-MAR-07:10 | 2160.58 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 278.78 | 05-MAR-14:00 | 1983.23 | 16-MAR-02:00 |
April | 2010.83 | 03-APR-09:09 | 1803.04 | 12-APR-07:10 | 2160.58 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 672.53 | 15-APR-17:01 | 695.66 | 18-APR-23:53 |
May | 2010.83 | 01-MAY-09:09 | 1470.31 | 25-MAY-07:10 | 2160.58 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1110.63 | 29-MAY-15:45 | 481.59 | 07-MAY-18:53 |
June | 2010.83 | 01-JUN-09:09 | 2255.25 | 15-JUN-07:10 | 2160.58 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 690.90 | 25-JUN-13:58 | 522.50 | 18-JUN-20:00 |
July | 2010.83 | 03-JUL-09:09 | 1470.31 | 05-JUL-07:10 | 2160.58 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 860.32 | 30-JUL-15:58 | 400.59 | 02-JUL-16:00 |
August | 2010.83 | 01-AUG-09:09 | 1803.04 | 28-AUG-07:10 | 2160.58 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 719.63 | 20-AUG-11:55 | 536.09 | 14-AUG-02:55 |
September | 2010.83 | 01-SEP-09:09 | 2587.98 | 27-SEP-07:10 | 2160.58 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 714.71 | 17-SEP-13:55 | 308.89 | 19-SEP-23:20 |
October | 2010.83 | 02-OCT-09:09 | 2255.25 | 18-OCT-07:10 | 2160.58 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 484.64 | 29-OCT-13:56 | 455.06 | 16-OCT-05:00 |
November | 2010.83 | 01-NOV-09:09 | 2255.25 | 29-NOV-16:00 | 2160.58 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 290.02 | 22-NOV-22:02 | 2198.02 | 11-NOV-09:00 |
December | 2010.83 | 01-DEC-10:09 | 2587.98 | 15-DEC-16:40 | 2160.58 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 328.54 | 10-DEC-14:50 | 1868.90 | 15-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.83 | 1470.31 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 161.65 | 308.89 | |||||
Maximum of Months | 2010.83 | 2587.98 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 1110.63 | 2198.02 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 1453.34 | 04-JAN-16:00 | 1392.33 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 404.33 | 15-JAN-11:52 | 805.62 | 24-JAN-03:00 |
February | 1295.83 | 01-FEB-10:09 | 1161.92 | 01-FEB-08:09 | 1392.33 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 162.66 | 20-FEB-13:30 | 1391.86 | 04-FEB-05:16 |
March | 1295.83 | 01-MAR-10:09 | 1453.34 | 14-MAR-07:10 | 1392.33 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 294.53 | 05-MAR-14:00 | 1332.01 | 16-MAR-02:00 |
April | 1295.83 | 03-APR-09:09 | 1453.34 | 12-APR-07:10 | 1392.33 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 419.25 | 16-APR-12:53 | 517.34 | 18-APR-23:53 |
May | 1295.83 | 01-MAY-09:09 | 1161.92 | 25-MAY-07:10 | 1392.33 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 705.90 | 29-MAY-15:44 | 395.87 | 07-MAY-18:53 |
June | 1295.83 | 01-JUN-09:09 | 1667.75 | 15-JUN-07:10 | 1392.33 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 486.00 | 25-JUN-14:00 | 382.88 | 18-JUN-20:00 |
July | 1295.83 | 03-JUL-09:09 | 1161.92 | 05-JUL-07:10 | 1392.33 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 630.10 | 30-JUL-16:00 | 289.13 | 04-JUL-02:55 |
August | 1295.83 | 01-AUG-09:09 | 1453.34 | 28-AUG-07:10 | 1392.33 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 601.89 | 13-AUG-12:30 | 415.39 | 14-AUG-02:55 |
September | 1295.83 | 01-SEP-09:09 | 1667.75 | 27-SEP-07:10 | 1392.33 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 539.94 | 17-SEP-13:55 | 233.68 | 19-SEP-23:20 |
October | 1295.83 | 02-OCT-09:09 | 1453.34 | 18-OCT-07:10 | 1392.33 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 465.30 | 29-OCT-11:50 | 304.73 | 01-OCT-07:00 |
November | 1295.83 | 01-NOV-09:09 | 1453.34 | 03-NOV-07:10 | 1392.33 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 291.41 | 19-NOV-11:40 | 1267.43 | 11-NOV-09:00 |
December | 1295.83 | 01-DEC-10:09 | 1667.75 | 15-DEC-16:40 | 1392.33 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 347.98 | 10-DEC-13:50 | 1228.16 | 15-DEC-06:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 1161.92 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 162.66 | 233.68 | |||||
Maximum of Months | 1295.83 | 1667.75 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 705.90 | 1391.86 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 232.27 | 02-JAN-10:09 | 578.72 | 02-JAN-08:09 | 1948.61 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 232.27 | 01-FEB-10:09 | 578.72 | 01-FEB-08:09 | 3897.21 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 232.27 | 01-MAR-10:09 | 578.72 | 01-MAR-08:09 | 7794.42 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 232.27 | 03-APR-09:09 | 578.72 | 03-APR-07:10 | 7794.42 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 232.27 | 01-MAY-09:09 | 578.72 | 01-MAY-07:10 | 3897.21 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 232.27 | 01-JUN-09:09 | 578.72 | 01-JUN-07:10 | 5845.82 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 232.27 | 03-JUL-09:09 | 578.72 | 03-JUL-07:10 | 7794.42 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 232.27 | 01-AUG-09:09 | 578.72 | 01-AUG-07:10 | 7794.42 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 232.27 | 01-SEP-09:09 | 578.72 | 01-SEP-07:10 | 3897.21 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 232.27 | 02-OCT-09:09 | 578.72 | 02-OCT-07:10 | 5845.82 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 232.27 | 01-NOV-09:09 | 578.72 | 01-NOV-07:10 | 5845.82 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 232.27 | 01-DEC-10:09 | 578.72 | 01-DEC-08:09 | 7794.42 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 232.27 | 578.72 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 232.27 | 578.72 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 232.27 | 02-JAN-10:09 | 578.72 | 02-JAN-08:09 | 1948.61 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 232.27 | 01-FEB-10:09 | 578.72 | 01-FEB-08:09 | 3897.21 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 232.27 | 01-MAR-10:09 | 578.72 | 01-MAR-08:09 | 7794.42 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 232.27 | 03-APR-09:09 | 578.72 | 03-APR-07:10 | 7794.42 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 232.27 | 01-MAY-09:09 | 578.72 | 01-MAY-07:10 | 3897.21 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 232.27 | 01-JUN-09:09 | 578.72 | 01-JUN-07:10 | 5845.82 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 232.27 | 03-JUL-09:09 | 578.72 | 03-JUL-07:10 | 7794.42 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 232.27 | 01-AUG-09:09 | 578.72 | 01-AUG-07:10 | 7794.42 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 232.27 | 01-SEP-09:09 | 578.72 | 01-SEP-07:10 | 3897.21 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 232.27 | 02-OCT-09:09 | 578.72 | 02-OCT-07:10 | 5845.82 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 232.27 | 01-NOV-09:09 | 578.72 | 01-NOV-07:10 | 5845.82 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 232.27 | 01-DEC-10:09 | 578.72 | 01-DEC-08:09 | 7794.42 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 232.27 | 578.72 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 232.27 | 578.72 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 232.27 | 02-JAN-10:09 | 578.72 | 02-JAN-08:09 | 1948.61 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 232.27 | 01-FEB-10:09 | 578.72 | 01-FEB-08:09 | 3897.21 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 232.27 | 01-MAR-10:09 | 578.72 | 01-MAR-08:09 | 7794.42 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 232.27 | 03-APR-09:09 | 578.72 | 03-APR-07:10 | 7794.42 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 232.27 | 01-MAY-09:09 | 578.72 | 01-MAY-07:10 | 3897.21 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 232.27 | 01-JUN-09:09 | 578.72 | 01-JUN-07:10 | 5845.82 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 232.27 | 03-JUL-09:09 | 578.72 | 03-JUL-07:10 | 7794.42 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 232.27 | 01-AUG-09:09 | 578.72 | 01-AUG-07:10 | 7794.42 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 232.27 | 01-SEP-09:09 | 578.72 | 01-SEP-07:10 | 3897.21 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 232.27 | 02-OCT-09:09 | 578.72 | 02-OCT-07:10 | 5845.82 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 232.27 | 01-NOV-09:09 | 578.72 | 01-NOV-07:10 | 5845.82 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 232.27 | 01-DEC-10:09 | 578.72 | 01-DEC-08:09 | 7794.42 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 232.27 | 578.72 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 232.27 | 578.72 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 5027.92 | 02-JAN-10:09 | 6471.01 | 02-JAN-08:09 | 94908.13 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 5027.92 | 01-FEB-10:09 | 6471.01 | 01-FEB-08:09 | 189816.26 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 5027.92 | 01-MAR-10:09 | 6471.01 | 01-MAR-08:09 | 379632.52 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 5027.92 | 03-APR-09:09 | 6471.01 | 03-APR-07:10 | 379632.52 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 5027.92 | 01-MAY-09:09 | 6471.01 | 01-MAY-07:10 | 189816.26 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5027.92 | 01-JUN-09:09 | 6471.01 | 01-JUN-07:10 | 284724.39 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 5027.92 | 03-JUL-09:09 | 6471.01 | 03-JUL-07:10 | 379632.52 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 5027.92 | 01-AUG-09:09 | 6471.01 | 01-AUG-07:10 | 379632.52 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 5027.92 | 01-SEP-09:09 | 6471.01 | 01-SEP-07:10 | 189816.26 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 5027.92 | 02-OCT-09:09 | 6471.01 | 02-OCT-07:10 | 284724.39 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5027.92 | 01-NOV-09:09 | 6471.01 | 01-NOV-07:10 | 284724.39 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 5027.92 | 01-DEC-10:09 | 6471.01 | 01-DEC-08:09 | 379632.52 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 5027.92 | 6471.01 | 94908.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 5027.92 | 6471.01 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 157.77 | 29-JAN-12:30 | 1045.13 | 24-JAN-03:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 115.01 | 02-FEB-14:00 | 1837.14 | 04-FEB-05:00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 258.92 | 05-MAR-13:52 | 1791.29 | 16-MAR-02:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 515.19 | 15-APR-17:01 | 569.19 | 18-APR-24:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 787.33 | 29-MAY-16:00 | 319.94 | 25-MAY-04:12 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 510.79 | 25-JUN-14:00 | 237.17 | 18-JUN-20:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 587.77 | 30-JUL-15:50 | 214.52 | 04-JUL-03:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 601.59 | 13-AUG-13:00 | 322.09 | 14-AUG-02:55 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 585.31 | 17-SEP-13:52 | 165.16 | 19-SEP-23:20 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 416.86 | 29-OCT-13:51 | 314.48 | 16-OCT-04:53 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 161.98 | 23-NOV-12:00 | 1705.46 | 11-NOV-09:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 344.95 | 10-DEC-15:00 | 1706.53 | 15-DEC-05:55 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 115.01 | 165.16 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 787.33 | 1837.14 |
Report: PeakSpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 370.27 | 29-JAN-12:30 | 1733.67 | 24-JAN-03:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 255.88 | 20-FEB-15:10 | 3156.23 | 04-FEB-05:00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 498.24 | 05-MAR-14:00 | 3089.94 | 16-MAR-02:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 966.09 | 15-APR-17:01 | 1012.22 | 18-APR-23:53 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1450.33 | 29-MAY-16:00 | 561.32 | 25-MAY-05:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 931.57 | 25-JUN-14:00 | 448.70 | 18-JUN-20:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1163.21 | 30-JUL-15:50 | 404.73 | 04-JUL-02:55 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1151.80 | 13-AUG-13:00 | 569.20 | 14-AUG-02:55 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1055.40 | 17-SEP-13:42 | 289.77 | 19-SEP-23:20 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 813.94 | 29-OCT-14:00 | 546.51 | 16-OCT-04:53 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 308.44 | 04-NOV-17:03 | 2957.39 | 11-NOV-09:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 638.38 | 10-DEC-14:50 | 2935.58 | 15-DEC-05:55 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 255.88 | 289.77 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1450.33 | 3156.23 |
Report: PeakSpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 324.56 | 29-JAN-12:20 | 1809.13 | 24-JAN-03:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 181.58 | 02-FEB-14:00 | 2893.73 | 04-FEB-05:20 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 278.68 | 05-MAR-14:00 | 2953.01 | 16-MAR-02:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 844.77 | 15-APR-17:01 | 1005.58 | 18-APR-23:53 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1164.06 | 29-MAY-16:00 | 690.59 | 25-MAY-04:14 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 751.60 | 16-JUN-21:02 | 702.75 | 18-JUN-20:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 901.19 | 29-JUL-18:00 | 622.12 | 02-JUL-16:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 942.25 | 13-AUG-12:50 | 707.33 | 14-AUG-02:55 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 773.08 | 16-SEP-17:02 | 369.31 | 19-SEP-23:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 635.26 | 29-OCT-11:32 | 556.96 | 01-OCT-07:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 354.75 | 22-NOV-22:02 | 2978.65 | 11-NOV-09:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 426.86 | 10-DEC-14:10 | 2780.13 | 15-DEC-06:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 181.58 | 369.31 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1164.06 | 2978.65 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 105498.80 | 25-JAN-05:12 | 0.00 | 10200.53 | 53830.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 109161.00 | 04-FEB-05:11 | 0.00 | 11474.31 | 121117.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 106970.58 | 16-MAR-04:12 | 0.00 | 12750.66 | 67287.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 104536.52 | 19-APR-04:12 | 0.00 | 15300.79 | 80745.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 89064.31 | 08-MAY-04:11 | 0.00 | 17850.93 | 94202.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 85224.33 | 13-JUN-03:02 | 0.00 | 6374.62 | 67287.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 87409.27 | 04-JUL-15:30 | 5385.68 | 7649.54 | 80745.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 86150.01 | 22-AUG-03:02 | 0.00 | 6374.62 | 67287.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 85048.44 | 04-SEP-24:00 | 0.00 | 6374.62 | 67287.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 91945.97 | 18-OCT-03:02 | 0.00 | 6374.62 | 67287.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 108988.80 | 13-NOV-05:12 | 0.00 | 15300.79 | 80745.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 107123.21 | 21-DEC-05:12 | 0.00 | 12750.66 | 67287.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 85048.44 | 0.00 | 6374.62 | 53830.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 109161.00 | 5385.68 | 17850.93 | 121117.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 101591.23 | 30-JAN-05:13 | 0.00 | 13741.19 | 35625.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 103182.26 | 21-FEB-05:13 | 0.00 | 16031.39 | 41563.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 102435.06 | 07-MAR-05:13 | 0.00 | 16031.39 | 41563.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 97200.94 | 19-APR-04:13 | 0.00 | 13741.19 | 35625.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 94217.47 | 26-MAY-03:02 | 0.00 | 5724.85 | 29688.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 93484.24 | 13-JUN-03:02 | 0.00 | 5724.85 | 29688.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 77512.77 | 14-JUL-05:02 | 8061.19 | 11450.99 | 38236.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 88363.86 | 21-AUG-05:03 | 11285.67 | 16031.39 | 53531.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 97920.21 | 06-SEP-04:13 | 0.00 | 13741.19 | 35625.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 97025.17 | 20-OCT-04:13 | 0.00 | 16031.39 | 41563.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 101674.97 | 27-NOV-05:11 | 0.00 | 16031.39 | 41563.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 99972.90 | 18-DEC-05:12 | 0.00 | 13741.19 | 35625.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 77512.77 | 0.00 | 5724.85 | 29688.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 103182.26 | 11285.67 | 16031.39 | 53531.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 88367.99 | 03-JAN-05:12 | 0.00 | 13741.19 | 35625.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 91009.26 | 13-FEB-05:11 | 0.00 | 16031.39 | 41563.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 89439.42 | 07-MAR-05:11 | 0.00 | 16031.39 | 41563.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 89894.39 | 18-APR-04:12 | 0.00 | 13741.19 | 35625.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 89109.06 | 01-MAY-04:12 | 0.00 | 11450.99 | 29688.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 85609.43 | 06-JUN-05:04 | 8061.19 | 11450.99 | 38236.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 84135.69 | 07-JUL-04:13 | 0.00 | 13741.19 | 35625.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 87181.86 | 24-AUG-03:02 | 0.00 | 5724.85 | 29688.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 85152.12 | 15-SEP-03:02 | 0.00 | 5724.85 | 29688.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 91473.61 | 20-OCT-04:13 | 0.00 | 16031.39 | 41563.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 89364.62 | 08-NOV-05:13 | 0.00 | 16031.39 | 41563.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 88175.61 | 06-DEC-05:12 | 0.00 | 13741.19 | 35625.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 84135.69 | 0.00 | 5724.85 | 29688.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 91473.61 | 8061.19 | 16031.39 | 41563.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 85458.64 | 30-JAN-05:12 | 0.00 | 13741.19 | 35625.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 86436.35 | 13-FEB-05:11 | 0.00 | 16031.39 | 41563.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 86674.92 | 31-MAR-04:12 | 0.00 | 13741.19 | 35625.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 88086.02 | 18-APR-04:12 | 0.00 | 13741.19 | 35625.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 87091.45 | 11-MAY-04:12 | 0.00 | 13741.19 | 35625.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 85032.43 | 13-JUN-04:02 | 0.00 | 11450.99 | 29688.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 84676.63 | 15-JUL-04:02 | 0.00 | 5724.85 | 22266.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 85008.15 | 29-AUG-04:02 | 0.00 | 11450.99 | 29688.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 85878.03 | 08-SEP-03:02 | 0.00 | 5724.85 | 29688.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 85695.45 | 20-OCT-04:11 | 0.00 | 16031.39 | 41563.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 86893.42 | 06-NOV-05:12 | 0.00 | 13741.19 | 35625.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 85287.26 | 07-DEC-05:12 | 0.00 | 13741.19 | 35625.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 84676.63 | 0.00 | 5724.85 | 22266.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 88086.02 | 0.00 | 16031.39 | 41563.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 14618.55 | 30-JAN-05:12 | 0.00 | 1725.34 | 4473.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 62.68 |
February | 14664.89 | 17-FEB-05:11 | 0.00 | 2012.90 | 5218.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 121.21 |
March | 15169.10 | 07-MAR-05:11 | 0.00 | 2012.90 | 5218.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 126.76 |
April | 10831.86 | 17-APR-15:00 | 1923.11 | 1231.33 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 73.88 | 0.00 |
May | 17624.87 | 29-MAY-15:52 | 607.30 | 410.41 | 4321.10 | 0.00 | 0.00 | 0.00 | 0.00 | 370.60 | 0.00 |
June | 18923.30 | 11-JUN-16:11 | 708.51 | 478.82 | 5041.29 | 0.00 | 0.00 | 0.00 | 0.00 | 158.82 | 0.00 |
July | 19309.23 | 30-JUL-14:22 | 607.30 | 410.41 | 4321.10 | 0.00 | 0.00 | 0.00 | 0.00 | 156.24 | 0.00 |
August | 18834.32 | 20-AUG-11:42 | 506.08 | 342.01 | 3600.92 | 0.00 | 0.00 | 0.00 | 0.00 | 231.54 | 0.00 |
September | 18439.38 | 04-SEP-14:22 | 506.08 | 342.01 | 3600.92 | 0.00 | 0.00 | 0.00 | 0.00 | 103.39 | 0.00 |
October | 14807.71 | 19-OCT-04:11 | 0.00 | 2012.90 | 5218.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37.36 |
November | 14078.12 | 20-NOV-06:02 | 1012.16 | 1437.79 | 4801.23 | 0.00 | 0.00 | 0.00 | 0.00 | 3.43 | 0.00 |
December | 13837.07 | 01-DEC-05:11 | 0.00 | 2012.90 | 5218.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 10831.86 | 0.00 | 342.01 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 19309.23 | 1923.11 | 2012.90 | 5218.93 | 0.00 | 0.00 | 0.00 | 0.00 | 370.60 | 126.76 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 19640.16 | 01-JAN-09:02 | 326.14 | 220.40 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 61.36 |
February | 14796.86 | 20-FEB-09:23 | 260.91 | 176.32 | 1856.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 211.24 |
March | 10668.44 | 27-MAR-08:40 | 1239.33 | 793.52 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.43 |
April | 19906.07 | 09-APR-09:22 | 326.14 | 220.40 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.06 |
May | 19820.26 | 07-MAY-08:52 | 326.14 | 220.40 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.49 |
June | 20583.32 | 11-JUN-09:32 | 391.37 | 264.49 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 37.20 | 0.00 |
July | 20483.40 | 16-JUL-09:12 | 391.37 | 264.49 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 17.17 | 0.00 |
August | 19040.36 | 20-AUG-11:42 | 326.14 | 220.40 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 150.15 | 0.00 |
September | 17312.22 | 10-SEP-09:52 | 326.14 | 220.40 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 53.00 | 0.00 |
October | 19895.32 | 09-OCT-08:42 | 326.14 | 220.40 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 10.67 | 0.00 |
November | 9800.43 | 07-NOV-09:00 | 1239.33 | 793.52 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 7948.88 | 03-DEC-10:02 | 260.91 | 176.32 | 1856.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 102.89 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 7948.88 | 260.91 | 176.32 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 20583.32 | 1239.33 | 793.52 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 150.15 | 211.24 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 21393.94 | 15-JAN-13:52 | 607.31 | 410.42 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 195.45 |
February | 20967.20 | 20-FEB-12:02 | 506.09 | 342.02 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 234.93 |
March | 19769.69 | 12-MAR-13:32 | 506.09 | 342.02 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 109.80 |
April | 19073.57 | 09-APR-13:22 | 506.09 | 342.02 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 31.19 | 0.00 |
May | 17332.10 | 29-MAY-15:52 | 607.31 | 410.42 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 370.68 | 0.00 |
June | 18467.82 | 11-JUN-16:11 | 708.53 | 478.83 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 170.98 | 0.00 |
July | 19573.08 | 30-JUL-14:22 | 607.31 | 410.42 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 150.33 | 0.00 |
August | 19470.38 | 20-AUG-12:22 | 506.09 | 342.02 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 204.10 | 0.00 |
September | 19883.92 | 24-SEP-11:43 | 404.87 | 273.61 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 147.96 | 0.00 |
October | 21938.18 | 29-OCT-12:41 | 708.53 | 478.83 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 45.16 | 0.00 |
November | 21522.61 | 19-NOV-12:42 | 607.31 | 410.42 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 101.68 |
December | 22594.59 | 03-DEC-14:01 | 809.75 | 547.23 | 5761.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 95.36 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 17332.10 | 404.87 | 273.61 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 22594.59 | 809.75 | 547.23 | 5761.56 | 0.00 | 0.00 | 0.00 | 0.00 | 370.68 | 234.93 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 18398.49 | 30-JAN-05:12 | 0.00 | 1111.88 | 2882.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40.94 |
February | 25330.25 | 19-FEB-16:12 | 391.37 | 264.49 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.80 |
March | 25598.06 | 12-MAR-16:12 | 391.37 | 264.49 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 78.96 |
April | 26855.61 | 09-APR-16:41 | 521.82 | 352.65 | 3712.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.24 |
May | 25377.48 | 29-MAY-16:32 | 391.37 | 264.49 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 199.65 | 0.00 |
June | 26623.32 | 11-JUN-14:51 | 456.59 | 308.57 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 41.05 | 0.00 |
July | 26233.66 | 09-JUL-16:31 | 456.59 | 308.57 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 68.21 | 0.00 |
August | 26423.02 | 20-AUG-16:21 | 456.59 | 308.57 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 58.99 | 0.00 |
September | 25245.39 | 17-SEP-16:02 | 391.37 | 264.49 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 139.38 | 0.00 |
October | 26315.95 | 09-OCT-15:22 | 391.37 | 264.49 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 25.64 | 0.00 |
November | 25665.21 | 26-NOV-15:02 | 391.37 | 264.49 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 156.14 |
December | 27154.46 | 03-DEC-15:21 | 456.59 | 308.57 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47.87 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 18398.49 | 0.00 | 264.49 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 27154.46 | 521.82 | 1111.88 | 3712.89 | 0.00 | 0.00 | 0.00 | 0.00 | 199.65 | 156.14 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 9956.79 | 14-JAN-06:03 | 809.73 | 1150.23 | 3840.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.72 |
February | 10552.93 | 18-FEB-06:03 | 809.73 | 1150.23 | 3840.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.63 |
March | 11947.51 | 06-MAR-06:02 | 1012.16 | 1437.79 | 4801.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.25 |
April | 10901.71 | 15-APR-05:03 | 809.73 | 1150.23 | 3840.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.29 |
May | 18851.34 | 29-MAY-15:41 | 809.73 | 547.22 | 5761.47 | 0.00 | 0.00 | 0.00 | 0.00 | 729.36 | 0.00 |
June | 17974.34 | 25-JUN-14:32 | 506.08 | 342.01 | 3600.92 | 0.00 | 0.00 | 0.00 | 0.00 | 263.00 | 0.00 |
July | 18629.78 | 04-JUL-16:31 | 809.73 | 547.22 | 5761.47 | 0.00 | 0.00 | 0.00 | 0.00 | 223.97 | 0.00 |
August | 15928.24 | 20-AUG-12:22 | 506.08 | 342.01 | 3600.92 | 0.00 | 0.00 | 0.00 | 0.00 | 544.95 | 0.00 |
September | 17822.50 | 17-SEP-15:51 | 809.73 | 547.22 | 5761.47 | 0.00 | 0.00 | 0.00 | 0.00 | 531.87 | 0.00 |
October | 13687.13 | 19-OCT-04:11 | 0.00 | 2012.90 | 5218.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 92.52 |
November | 13131.24 | 29-NOV-06:03 | 809.73 | 1150.23 | 3840.98 | 0.00 | 0.00 | 0.00 | 0.00 | 19.30 | 0.00 |
December | 12997.27 | 09-DEC-06:02 | 1012.16 | 1437.79 | 4801.23 | 0.00 | 0.00 | 0.00 | 0.00 | 11.51 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 9956.79 | 0.00 | 342.01 | 3600.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 18851.34 | 1012.16 | 2012.90 | 5761.47 | 0.00 | 0.00 | 0.00 | 0.00 | 729.36 | 92.52 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 19846.44 | 01-JAN-10:12 | 326.14 | 220.40 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.98 |
February | 12432.78 | 26-FEB-10:02 | 260.91 | 176.32 | 1856.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 181.49 |
March | 10311.04 | 27-MAR-10:20 | 1239.33 | 793.52 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 6.94 | 0.00 |
April | 20784.34 | 09-APR-09:22 | 326.14 | 220.40 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 85.01 |
May | 20712.56 | 07-MAY-10:22 | 326.14 | 220.40 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 53.39 | 0.00 |
June | 19920.43 | 11-JUN-09:42 | 326.14 | 220.40 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 120.77 | 0.00 |
July | 21706.66 | 04-JUL-08:32 | 391.37 | 264.49 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 11.61 | 0.00 |
August | 20468.26 | 27-AUG-09:32 | 326.14 | 220.40 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 160.28 | 0.00 |
September | 20685.25 | 24-SEP-08:52 | 326.14 | 220.40 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 71.90 | 0.00 |
October | 20544.24 | 09-OCT-08:52 | 326.14 | 220.40 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 29.54 | 0.00 |
November | 9722.86 | 07-NOV-09:30 | 1239.33 | 793.52 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 1.88 | 0.00 |
December | 7788.98 | 08-DEC-10:00 | 1239.33 | 793.52 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 25.62 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 7788.98 | 260.91 | 176.32 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 21706.66 | 1239.33 | 793.52 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 160.28 | 181.49 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 20596.89 | 01-JAN-13:32 | 607.31 | 410.42 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 134.96 |
February | 19973.65 | 26-FEB-12:42 | 506.09 | 342.02 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 239.17 |
March | 19381.77 | 26-MAR-13:52 | 506.09 | 342.02 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.69 |
April | 17771.51 | 16-APR-17:12 | 0.00 | 342.02 | 2795.90 | 0.00 | 0.00 | 0.00 | 0.00 | 263.73 | 0.00 |
May | 18664.92 | 29-MAY-15:41 | 809.75 | 547.23 | 5761.56 | 0.00 | 0.00 | 0.00 | 0.00 | 732.18 | 0.00 |
June | 17585.42 | 25-JUN-14:32 | 506.09 | 342.02 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 277.56 | 0.00 |
July | 18131.76 | 04-JUL-15:51 | 809.75 | 547.23 | 5761.56 | 0.00 | 0.00 | 0.00 | 0.00 | 379.22 | 0.00 |
August | 18500.46 | 20-AUG-12:22 | 506.09 | 342.02 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 484.65 | 0.00 |
September | 19736.86 | 17-SEP-14:31 | 708.53 | 478.83 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 308.76 | 0.00 |
October | 21080.94 | 29-OCT-12:11 | 708.53 | 478.83 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 121.83 | 0.00 |
November | 20732.66 | 19-NOV-13:52 | 607.31 | 410.42 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 284.94 |
December | 22022.21 | 03-DEC-13:51 | 809.75 | 547.23 | 5761.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 240.30 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 17585.42 | 0.00 | 342.02 | 2795.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 22022.21 | 809.75 | 547.23 | 5761.56 | 0.00 | 0.00 | 0.00 | 0.00 | 732.18 | 284.94 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 9761.42 | 14-JAN-06:03 | 521.82 | 741.25 | 2475.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.67 |
February | 22455.48 | 19-FEB-16:01 | 521.82 | 352.65 | 3712.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.10 |
March | 20505.92 | 12-MAR-16:22 | 326.14 | 220.40 | 2320.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 166.53 |
April | 24422.33 | 02-APR-16:41 | 456.59 | 308.57 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 163.19 |
May | 24716.95 | 29-MAY-15:41 | 521.82 | 352.65 | 3712.89 | 0.00 | 0.00 | 0.00 | 0.00 | 365.11 | 0.00 |
June | 21607.22 | 25-JUN-14:32 | 326.14 | 220.40 | 2320.55 | 0.00 | 0.00 | 0.00 | 0.00 | 172.28 | 0.00 |
July | 24581.35 | 04-JUL-16:31 | 521.82 | 352.65 | 3712.89 | 0.00 | 0.00 | 0.00 | 0.00 | 77.32 | 0.00 |
August | 22980.15 | 13-AUG-16:01 | 587.05 | 396.73 | 4177.00 | 0.00 | 0.00 | 0.00 | 0.00 | 194.05 | 0.00 |
September | 24642.79 | 17-SEP-15:51 | 521.82 | 352.65 | 3712.89 | 0.00 | 0.00 | 0.00 | 0.00 | 175.33 | 0.00 |
October | 23371.89 | 09-OCT-16:12 | 391.37 | 264.49 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 44.94 | 0.00 |
November | 18263.68 | 19-NOV-15:12 | 391.37 | 264.49 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.21 |
December | 23062.63 | 10-DEC-15:41 | 456.59 | 308.57 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 46.28 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 9761.42 | 326.14 | 220.40 | 2320.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 24716.95 | 587.05 | 741.25 | 4177.00 | 0.00 | 0.00 | 0.00 | 0.00 | 365.11 | 166.53 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 7913.15 | 14-JAN-06:03 | 809.73 | 1150.23 | 3840.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.75 |
February | 8341.34 | 18-FEB-06:03 | 809.73 | 1150.23 | 3840.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.80 |
March | 13423.55 | 06-MAR-06:02 | 1012.16 | 1437.79 | 4801.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43.10 |
April | 13861.87 | 16-APR-17:12 | 0.00 | 342.01 | 2795.85 | 0.00 | 0.00 | 0.00 | 0.00 | 320.71 | 0.00 |
May | 21484.45 | 29-MAY-15:41 | 809.73 | 547.22 | 5761.47 | 0.00 | 0.00 | 0.00 | 0.00 | 827.73 | 0.00 |
June | 20361.45 | 25-JUN-14:32 | 506.08 | 342.01 | 3600.92 | 0.00 | 0.00 | 0.00 | 0.00 | 288.88 | 0.00 |
July | 21255.36 | 04-JUL-16:31 | 809.73 | 547.22 | 5761.47 | 0.00 | 0.00 | 0.00 | 0.00 | 233.36 | 0.00 |
August | 20263.94 | 20-AUG-12:12 | 506.08 | 342.01 | 3600.92 | 0.00 | 0.00 | 0.00 | 0.00 | 639.63 | 0.00 |
September | 20626.91 | 17-SEP-15:51 | 809.73 | 547.22 | 5761.47 | 0.00 | 0.00 | 0.00 | 0.00 | 556.02 | 0.00 |
October | 15244.23 | 31-OCT-05:02 | 1012.16 | 1437.79 | 4801.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 52.12 |
November | 14840.62 | 10-NOV-06:02 | 1012.16 | 1437.79 | 4801.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.47 |
December | 10436.09 | 09-DEC-06:02 | 1012.16 | 1437.79 | 4801.23 | 0.00 | 0.00 | 0.00 | 0.00 | 12.75 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 7913.15 | 0.00 | 342.01 | 2795.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 21484.45 | 1012.16 | 1437.79 | 5761.47 | 0.00 | 0.00 | 0.00 | 0.00 | 827.73 | 52.12 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 7564.00 | 01-JAN-10:32 | 260.91 | 176.32 | 1856.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.44 |
February | 8133.23 | 28-FEB-10:10 | 1295.83 | 793.52 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 3.43 | 0.00 |
March | 10632.57 | 31-MAR-09:30 | 1295.83 | 793.52 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.43 |
April | 20214.51 | 16-APR-09:52 | 326.14 | 220.40 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 0.00 |
May | 20989.69 | 07-MAY-10:32 | 326.14 | 220.40 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 67.32 | 0.00 |
June | 20277.75 | 11-JUN-09:42 | 326.14 | 220.40 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 142.70 | 0.00 |
July | 21982.11 | 04-JUL-08:32 | 391.37 | 264.49 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 12.04 | 0.00 |
August | 20900.11 | 20-AUG-08:52 | 326.14 | 220.40 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 139.10 | 0.00 |
September | 21008.81 | 24-SEP-08:52 | 326.14 | 220.40 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 82.76 | 0.00 |
October | 17943.95 | 22-OCT-09:53 | 260.91 | 176.32 | 1856.46 | 0.00 | 0.00 | 0.00 | 0.00 | 44.31 | 0.00 |
November | 9934.87 | 10-NOV-06:02 | 652.28 | 926.56 | 3094.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.92 |
December | 7655.18 | 08-DEC-10:30 | 1295.83 | 793.52 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 36.66 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 7564.00 | 260.91 | 176.32 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 21982.11 | 1295.83 | 926.56 | 3094.09 | 0.00 | 0.00 | 0.00 | 0.00 | 142.70 | 19.44 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 22811.27 | 15-JAN-14:22 | 607.31 | 410.42 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 593.29 |
February | 22055.90 | 26-FEB-14:32 | 506.09 | 342.02 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 278.50 |
March | 20939.05 | 12-MAR-14:12 | 506.09 | 342.02 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 290.71 |
April | 20166.64 | 16-APR-17:12 | 0.00 | 342.02 | 2795.90 | 0.00 | 0.00 | 0.00 | 0.00 | 296.23 | 0.00 |
May | 21453.44 | 29-MAY-15:41 | 809.75 | 547.23 | 5761.56 | 0.00 | 0.00 | 0.00 | 0.00 | 832.88 | 0.00 |
June | 20212.53 | 25-JUN-14:32 | 506.09 | 342.02 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 300.12 | 0.00 |
July | 21039.89 | 04-JUL-15:51 | 809.75 | 547.23 | 5761.56 | 0.00 | 0.00 | 0.00 | 0.00 | 408.33 | 0.00 |
August | 20953.53 | 20-AUG-12:12 | 506.09 | 342.02 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 578.33 | 0.00 |
September | 22485.72 | 17-SEP-14:31 | 708.53 | 478.83 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 329.50 | 0.00 |
October | 22095.32 | 29-OCT-13:02 | 607.31 | 410.42 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 245.18 | 0.00 |
November | 22011.74 | 19-NOV-15:32 | 506.09 | 342.02 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 207.47 |
December | 23683.18 | 10-DEC-15:01 | 708.53 | 478.83 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 99.19 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 20166.64 | 0.00 | 342.02 | 2795.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 23683.18 | 809.75 | 547.23 | 5761.56 | 0.00 | 0.00 | 0.00 | 0.00 | 832.88 | 593.29 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 9285.15 | 03-JAN-15:40 | 1239.33 | 793.52 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 35.46 | 0.00 |
February | 23473.04 | 19-FEB-16:12 | 391.37 | 264.49 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.03 |
March | 23511.09 | 12-MAR-16:52 | 391.37 | 264.49 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 242.80 |
April | 24226.56 | 09-APR-16:12 | 391.37 | 264.49 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.66 |
May | 26754.78 | 29-MAY-15:41 | 521.82 | 352.65 | 3712.89 | 0.00 | 0.00 | 0.00 | 0.00 | 412.54 | 0.00 |
June | 23330.16 | 25-JUN-14:32 | 326.14 | 220.40 | 2320.55 | 0.00 | 0.00 | 0.00 | 0.00 | 193.31 | 0.00 |
July | 26630.39 | 04-JUL-16:31 | 521.82 | 352.65 | 3712.89 | 0.00 | 0.00 | 0.00 | 0.00 | 72.35 | 0.00 |
August | 24661.09 | 20-AUG-16:11 | 587.05 | 396.73 | 4177.00 | 0.00 | 0.00 | 0.00 | 0.00 | 163.07 | 0.00 |
September | 26631.76 | 17-SEP-15:51 | 521.82 | 352.65 | 3712.89 | 0.00 | 0.00 | 0.00 | 0.00 | 181.55 | 0.00 |
October | 23821.27 | 22-OCT-15:52 | 326.14 | 220.40 | 2320.55 | 0.00 | 0.00 | 0.00 | 0.00 | 50.64 | 0.00 |
November | 18059.14 | 19-NOV-15:32 | 326.14 | 220.40 | 2320.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.66 |
December | 24565.87 | 10-DEC-15:41 | 456.59 | 308.57 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 45.24 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 9285.15 | 326.14 | 220.40 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 26754.78 | 1239.33 | 793.52 | 4177.00 | 0.00 | 0.00 | 0.00 | 0.00 | 412.54 | 242.80 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 11040.37 | 03-JAN-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.73 |
February | 10035.15 | 13-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 101.75 |
March | 9507.31 | 28-MAR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.13 |
April | 10494.56 | 17-APR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 85.63 |
May | 11758.12 | 24-MAY-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.06 |
June | 10096.38 | 06-JUN-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 12347.95 | 05-JUL-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.34 | 0.00 |
August | 12447.08 | 21-AUG-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.78 | 0.00 |
September | 14310.38 | 18-SEP-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.38 | 0.00 |
October | 12409.81 | 16-OCT-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 69.99 |
November | 10423.69 | 08-NOV-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.24 |
December | 9783.35 | 11-DEC-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.88 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 9507.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 14310.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.38 | 101.75 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 6538.48 | 02-JAN-17:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.18 |
February | 6366.66 | 04-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 734.73 |
March | 7436.76 | 30-MAR-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.63 | 0.00 |
April | 7814.30 | 14-APR-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 123.21 | 0.00 |
May | 9792.34 | 20-MAY-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.22 | 0.00 |
June | 9982.47 | 28-JUN-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.72 | 0.00 |
July | 10465.30 | 06-JUL-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.54 |
August | 8886.65 | 23-AUG-15:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 215.88 | 0.00 |
September | 9964.79 | 30-SEP-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.67 |
October | 9456.08 | 25-OCT-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.24 |
November | 9858.52 | 10-NOV-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.69 |
December | 6973.94 | 08-DEC-17:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.23 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 6366.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 10465.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 215.88 | 734.73 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 13611.83 | 02-JAN-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 84.88 | 0.00 |
February | 13649.34 | 17-FEB-14:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44.69 | 0.00 |
March | 17514.89 | 27-MAR-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 53.62 | 0.00 |
April | 19786.67 | 13-APR-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 111.39 | 0.00 |
May | 20809.66 | 22-MAY-13:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 320.84 | 0.00 |
June | 21707.51 | 09-JUN-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 119.61 | 0.00 |
July | 23127.28 | 28-JUL-15:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 162.35 | 0.00 |
August | 22275.12 | 23-AUG-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 260.61 | 0.00 |
September | 20538.77 | 08-SEP-14:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 111.75 | 0.00 |
October | 19845.84 | 06-OCT-13:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 60.94 | 0.00 |
November | 16072.50 | 10-NOV-14:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 76.24 | 0.00 |
December | 13910.53 | 08-DEC-14:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36.99 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 13611.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36.99 | 0.00 | |
Maximum of Months | 23127.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 320.84 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 2189.59 | 24-JAN-17:00 | 222.14 | 578.72 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 4316.70 | 20-FEB-17:50 | 23.38 | 64.31 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 7229.83 | 31-MAR-24:00 | 0.00 | 32.15 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 7964.60 | 09-APR-17:50 | 0.00 | 64.31 | 15588.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 3530.48 | 31-MAY-24:00 | 0.00 | 32.15 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5370.69 | 30-JUN-23:47 | 0.00 | 96.46 | 17537.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 7279.34 | 31-JUL-23:40 | 0.00 | 64.31 | 15588.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 7840.71 | 20-AUG-18:10 | 0.00 | 192.92 | 46766.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 3472.36 | 30-SEP-23:45 | 0.00 | 128.61 | 15588.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 5409.42 | 31-OCT-24:00 | 0.00 | 32.15 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6140.92 | 07-NOV-17:00 | 222.14 | 578.72 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 8056.14 | 06-DEC-17:00 | 222.14 | 578.72 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 2189.59 | 0.00 | 32.15 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 8056.14 | 222.14 | 578.72 | 46766.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 1983.74 | 24-JAN-17:00 | 222.14 | 578.72 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 3948.68 | 21-FEB-17:50 | 70.15 | 321.51 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6990.36 | 31-MAR-24:00 | 0.00 | 32.15 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 7474.09 | 09-APR-17:51 | 0.00 | 225.07 | 54560.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 3403.30 | 31-MAY-24:00 | 0.00 | 32.15 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5192.07 | 30-JUN-23:53 | 0.00 | 128.61 | 23383.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 7010.33 | 31-JUL-23:55 | 0.00 | 128.61 | 31177.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 7417.31 | 30-AUG-16:00 | 222.14 | 578.72 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 3291.46 | 30-SEP-23:45 | 0.00 | 128.61 | 15588.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 5094.44 | 31-OCT-24:00 | 0.00 | 32.15 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5844.75 | 07-NOV-17:00 | 222.14 | 578.72 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 7639.80 | 06-DEC-17:00 | 222.14 | 578.72 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 1983.74 | 0.00 | 32.15 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 7639.80 | 222.14 | 578.72 | 54560.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 2019.17 | 02-JAN-17:00 | 222.14 | 578.72 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 4005.86 | 21-FEB-17:50 | 70.15 | 321.51 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6931.40 | 31-MAR-24:00 | 0.00 | 32.15 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 7692.92 | 09-APR-17:51 | 0.00 | 225.07 | 54560.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 3411.64 | 31-MAY-24:00 | 0.00 | 32.15 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5181.81 | 30-JUN-23:15 | 0.00 | 128.61 | 23383.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 7029.39 | 31-JUL-23:55 | 0.00 | 128.61 | 31177.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 7584.15 | 20-AUG-18:11 | 0.00 | 225.07 | 54560.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 3332.88 | 30-SEP-23:35 | 0.00 | 128.61 | 15588.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 5006.95 | 31-OCT-24:00 | 0.00 | 32.15 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5908.71 | 07-NOV-17:00 | 222.14 | 578.72 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 7704.53 | 06-DEC-17:00 | 222.14 | 578.72 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 2019.17 | 0.00 | 32.15 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 7704.53 | 222.14 | 578.72 | 54560.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 94484.31 | 02-JAN-17:00 | 4808.68 | 6471.01 | 94908.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 185771.74 | 21-FEB-17:00 | 4808.68 | 6471.01 | 189816.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 360095.23 | 31-MAR-24:00 | 0.00 | 359.47 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 370080.19 | 17-APR-21:02 | 1518.53 | 4314.17 | 2277795.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 177048.12 | 31-MAY-24:00 | 0.00 | 359.47 | 189816.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 268627.10 | 30-JUN-23:53 | 0.00 | 1437.90 | 1138897.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 357520.45 | 31-JUL-23:35 | 0.00 | 718.95 | 759265.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 370406.01 | 28-AUG-12:20 | 4808.68 | 6471.01 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 176973.82 | 30-SEP-23:53 | 0.00 | 1437.90 | 759265.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 269342.00 | 31-OCT-24:00 | 0.00 | 359.47 | 284724.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 278116.79 | 07-NOV-17:00 | 4808.68 | 6471.01 | 284724.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 369959.13 | 11-DEC-17:00 | 4808.68 | 6471.01 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 94484.31 | 0.00 | 359.47 | 94908.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 370406.01 | 4808.68 | 6471.01 | 2277795.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.199516E+13 | 1472126.24 | 02-JAN-16:00 | 0.619201E+11 | 263713.89 | 25-JAN-06:10 |
February | 0.221772E+13 | 1602858.54 | 16-FEB-16:30 | 0.566513E+11 | 413137.05 | 04-FEB-06:10 |
March | 0.295963E+13 | 1776109.49 | 09-MAR-16:10 | 0.606891E+11 | 308995.19 | 16-MAR-05:10 |
April | 0.330456E+13 | 1951409.77 | 11-APR-15:20 | 0.523973E+11 | 66510.97 | 13-APR-11:39 |
May | 0.233595E+13 | 1496277.38 | 31-MAY-07:00 | 0.535886E+11 | 64736.63 | 03-MAY-11:39 |
June | 0.277486E+13 | 1670454.92 | 08-JUN-15:00 | 0.513579E+11 | 62308.94 | 01-JUN-11:30 |
July | 0.324339E+13 | 1852449.64 | 27-JUL-15:00 | 0.501750E+11 | 60509.37 | 03-JUL-11:39 |
August | 0.372971E+13 | 1989371.34 | 23-AUG-15:09 | 0.531097E+11 | 61825.93 | 30-AUG-11:30 |
September | 0.232772E+13 | 1514146.46 | 21-SEP-15:30 | 0.506204E+11 | 63559.74 | 22-SEP-11:00 |
October | 0.274289E+13 | 1663923.92 | 03-OCT-15:09 | 0.537753E+11 | 66495.56 | 25-OCT-11:39 |
November | 0.294189E+13 | 1806104.57 | 09-NOV-16:00 | 0.547747E+11 | 107544.13 | 13-NOV-06:10 |
December | 0.324501E+13 | 1955321.76 | 08-DEC-16:00 | 0.618581E+11 | 277139.50 | 15-DEC-06:10 |
Annual Sum or Average | 0.338185E+14 | 0.660918E+12 | ||||
Minimum of Months | 0.199516E+13 | 1472126.24 | 0.501750E+11 | 60509.37 | ||
Maximum of Months | 0.372971E+13 | 1989371.34 | 0.619201E+11 | 413137.05 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [J] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [J] | HUMIDIFIER:ELECTRICITY [J] | HEATRECOVERY:ELECTRICITY [J] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 0.330547E+12 | 0.686491E+11 | 0.766053E+12 | 0.164269E+12 | 0.174073E+12 | 0.597424E+11 | 0.00 | 0.289378E+12 | 0.133580E+12 | 0.336016E+09 | 0.853130E+10 | 0.00 | 0.00 |
February | 0.298011E+12 | 0.585207E+11 | 0.978954E+12 | 0.148381E+12 | 0.161531E+12 | 0.548837E+11 | 0.00 | 0.372073E+12 | 0.137115E+12 | 0.352186E+09 | 0.789758E+10 | 0.00 | 0.00 |
March | 0.351987E+12 | 0.600811E+11 | 0.141687E+13 | 0.164522E+12 | 0.185479E+12 | 0.722806E+11 | 0.00 | 0.532925E+12 | 0.165589E+12 | 0.294780E+09 | 0.960015E+10 | 0.00 | 0.00 |
April | 0.313785E+12 | 0.535380E+11 | 0.165903E+13 | 0.158945E+12 | 0.184235E+12 | 0.792390E+11 | 0.00 | 0.669819E+12 | 0.175952E+12 | 0.00 | 0.100182E+11 | 0.00 | 0.00 |
May | 0.337563E+12 | 0.511676E+11 | 0.774844E+12 | 0.164394E+12 | 0.199960E+12 | 0.864232E+11 | 0.00 | 0.499277E+12 | 0.211958E+12 | 0.00 | 0.103626E+11 | 0.00 | 0.00 |
June | 0.336019E+12 | 0.476302E+11 | 0.106252E+13 | 0.159183E+12 | 0.199920E+12 | 0.958140E+11 | 0.00 | 0.638724E+12 | 0.224170E+12 | 0.00 | 0.108845E+11 | 0.00 | 0.00 |
July | 0.314239E+12 | 0.498202E+11 | 0.139340E+13 | 0.164156E+12 | 0.205867E+12 | 0.101008E+12 | 0.00 | 0.770085E+12 | 0.233370E+12 | 0.00 | 0.114446E+11 | 0.00 | 0.00 |
August | 0.350561E+12 | 0.534823E+11 | 0.173200E+13 | 0.164521E+12 | 0.208889E+12 | 0.104439E+12 | 0.00 | 0.867233E+12 | 0.237050E+12 | 0.00 | 0.115385E+11 | 0.00 | 0.00 |
September | 0.314713E+12 | 0.561982E+11 | 0.740713E+12 | 0.158944E+12 | 0.198429E+12 | 0.929205E+11 | 0.00 | 0.534634E+12 | 0.220708E+12 | 0.00 | 0.104629E+11 | 0.00 | 0.00 |
October | 0.328015E+12 | 0.628449E+11 | 0.108340E+13 | 0.164269E+12 | 0.200001E+12 | 0.885213E+11 | 0.00 | 0.593933E+12 | 0.211755E+12 | 0.00 | 0.101517E+11 | 0.00 | 0.00 |
November | 0.325864E+12 | 0.650772E+11 | 0.135889E+13 | 0.159042E+12 | 0.183957E+12 | 0.759065E+11 | 0.00 | 0.581936E+12 | 0.182032E+12 | 89708180.50 | 0.909374E+10 | 0.00 | 0.00 |
December | 0.320949E+12 | 0.695473E+11 | 0.170972E+13 | 0.164158E+12 | 0.177416E+12 | 0.677057E+11 | 0.00 | 0.565392E+12 | 0.160951E+12 | 72110416.25 | 0.909467E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.392225E+13 | 0.696557E+12 | 0.146764E+14 | 0.193478E+13 | 0.227976E+13 | 0.978884E+12 | 0.00 | 0.691541E+13 | 0.229423E+13 | 0.114480E+10 | 0.119080E+12 | 0.00 | 0.00 |
Minimum of Months | 0.298011E+12 | 0.476302E+11 | 0.740713E+12 | 0.148381E+12 | 0.161531E+12 | 0.548837E+11 | 0.00 | 0.289378E+12 | 0.133580E+12 | 0.00 | 0.789758E+10 | 0.00 | 0.00 |
Maximum of Months | 0.351987E+12 | 0.695473E+11 | 0.173200E+13 | 0.164522E+12 | 0.208889E+12 | 0.104439E+12 | 0.00 | 0.867233E+12 | 0.237050E+12 | 0.352186E+09 | 0.115385E+11 | 0.00 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [J] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.00 | 0.00 | 0.495670E+10 | 0.00 | 0.569634E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.530566E+10 | 0.00 | 0.513456E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.284004E+10 | 0.00 | 0.578491E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 261102.97 | 0.00 | 0.523970E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.535886E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.513579E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.501750E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.531097E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.506204E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.537753E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.824225E+09 | 0.00 | 0.539505E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.615636E+10 | 0.00 | 0.557018E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.200832E+11 | 0.00 | 0.640834E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.501750E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.615636E+10 | 0.00 | 0.578491E+11 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | EXTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum} [W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 372703.55 | 04-JAN-16:00 | 57580.60 | 01-JAN-06:10 | 423497.50 | 02-JAN-08:09 | 118506.10 | 30-JAN-08:20 | 126664.49 | 14-JAN-06:10 | 65917.57 | 02-JAN-10:09 | 0.00 | 01-JAN-00:10 |
February | 348291.11 | 08-FEB-16:00 | 57580.60 | 01-FEB-06:10 | 541788.89 | 01-FEB-08:09 | 118502.42 | 07-FEB-08:20 | 121028.21 | 02-FEB-06:10 | 65525.23 | 13-FEB-14:00 | 0.00 | 01-FEB-00:10 |
March | 357001.62 | 15-MAR-07:10 | 57580.60 | 01-MAR-06:10 | 660080.29 | 01-MAR-08:09 | 118512.89 | 15-MAR-07:19 | 135604.69 | 30-MAR-15:30 | 66136.61 | 14-MAR-10:30 | 0.00 | 01-MAR-00:10 |
April | 358353.79 | 12-APR-07:10 | 57580.60 | 01-APR-05:10 | 778371.69 | 03-APR-07:10 | 118513.95 | 12-APR-07:19 | 134528.35 | 14-APR-15:39 | 66647.50 | 17-APR-09:50 | 0.00 | 01-APR-00:10 |
May | 343374.53 | 25-MAY-07:10 | 57580.60 | 01-MAY-05:10 | 423497.50 | 01-MAY-07:10 | 118502.27 | 25-MAY-07:19 | 142434.18 | 08-MAY-05:10 | 66399.77 | 30-MAY-09:39 | 0.00 | 01-MAY-00:10 |
June | 375276.56 | 15-JUN-07:10 | 57580.60 | 01-JUN-05:10 | 541788.89 | 01-JUN-07:10 | 118527.17 | 15-JUN-07:19 | 141078.02 | 23-JUN-05:10 | 66165.94 | 12-JUN-14:50 | 0.00 | 01-JUN-00:10 |
July | 343374.53 | 05-JUL-07:10 | 57580.60 | 01-JUL-05:10 | 660080.29 | 03-JUL-07:10 | 118502.27 | 05-JUL-07:19 | 148464.98 | 28-JUL-15:30 | 66952.05 | 31-JUL-12:09 | 0.00 | 01-JUL-00:10 |
August | 358353.79 | 28-AUG-07:10 | 57580.60 | 01-AUG-05:10 | 778371.69 | 01-AUG-07:10 | 118513.95 | 28-AUG-07:19 | 148849.04 | 31-AUG-15:20 | 66337.41 | 11-AUG-09:09 | 0.00 | 01-AUG-00:10 |
September | 385834.94 | 27-SEP-07:10 | 57580.60 | 01-SEP-05:10 | 423497.50 | 01-SEP-07:10 | 118535.44 | 27-SEP-07:19 | 145888.48 | 08-SEP-15:30 | 66357.57 | 25-SEP-09:30 | 0.00 | 01-SEP-00:10 |
October | 372703.55 | 18-OCT-07:10 | 57580.60 | 01-OCT-05:10 | 541788.89 | 02-OCT-07:10 | 118525.16 | 18-OCT-07:19 | 144186.71 | 06-OCT-15:00 | 69624.76 | 13-OCT-15:50 | 0.00 | 01-OCT-00:10 |
November | 369206.61 | 29-NOV-16:00 | 57580.60 | 01-NOV-05:10 | 660080.29 | 01-NOV-07:10 | 118518.28 | 24-NOV-08:20 | 137033.89 | 22-NOV-06:10 | 66231.16 | 01-NOV-10:09 | 0.00 | 01-NOV-00:10 |
December | 385834.94 | 15-DEC-16:40 | 57580.60 | 01-DEC-06:10 | 778371.69 | 01-DEC-08:09 | 118525.16 | 29-DEC-08:20 | 128563.38 | 08-DEC-15:39 | 65176.82 | 08-DEC-14:39 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 343374.53 | 57580.60 | 423497.50 | 118502.27 | 121028.21 | 65176.82 | 0.00 | |||||||
Maximum of Months | 385834.94 | 57580.60 | 778371.69 | 118535.44 | 148849.04 | 69624.76 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY {Maximum} [W] | HEATREJECTION:ELECTRICITY {TIMESTAMP} | HUMIDIFIER:ELECTRICITY {Maximum} [W] | HUMIDIFIER:ELECTRICITY {TIMESTAMP} | HEATRECOVERY:ELECTRICITY {Maximum} [W] | HEATRECOVERY:ELECTRICITY {TIMESTAMP} | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 341583.56 | 02-JAN-13:00 | 98044.59 | 02-JAN-09:20 | 3673.02 | 25-JAN-01:00 | 5613.48 | 01-JAN-08:39 | 0.00 | 0.00 |
February | 368549.54 | 17-FEB-10:39 | 98044.59 | 02-FEB-08:20 | 4077.20 | 04-FEB-05:00 | 5613.48 | 01-FEB-06:10 | 0.00 | 0.00 |
March | 418473.80 | 27-MAR-14:50 | 98044.59 | 03-MAR-11:39 | 2982.05 | 16-MAR-17:00 | 5613.48 | 01-MAR-06:10 | 0.00 | 0.00 |
April | 469203.56 | 13-APR-13:09 | 98044.59 | 01-APR-13:50 | 0.00 | 01-APR-00:10 | 5613.48 | 01-APR-04:30 | 0.00 | 0.00 |
May | 384970.84 | 24-MAY-14:39 | 98044.59 | 01-MAY-07:30 | 0.00 | 01-MAY-00:10 | 5613.48 | 01-MAY-04:30 | 0.00 | 0.00 |
June | 432197.46 | 23-JUN-13:00 | 98044.59 | 01-JUN-05:30 | 0.00 | 01-JUN-00:10 | 5613.48 | 01-JUN-03:30 | 0.00 | 0.00 |
July | 470364.74 | 31-JUL-12:20 | 98044.59 | 01-JUL-03:20 | 0.00 | 01-JUL-00:10 | 5613.48 | 01-JUL-03:20 | 0.00 | 0.00 |
August | 495044.09 | 15-AUG-12:09 | 98044.59 | 01-AUG-00:10 | 0.00 | 01-AUG-00:10 | 5613.48 | 01-AUG-00:10 | 0.00 | 0.00 |
September | 377532.81 | 19-SEP-12:09 | 98044.59 | 01-SEP-00:10 | 0.00 | 01-SEP-00:10 | 5613.48 | 01-SEP-00:10 | 0.00 | 0.00 |
October | 404845.23 | 10-OCT-12:50 | 98044.59 | 01-OCT-00:40 | 0.00 | 01-OCT-00:10 | 5613.48 | 01-OCT-12:20 | 0.00 | 0.00 |
November | 433914.55 | 30-NOV-16:40 | 98044.59 | 01-NOV-09:20 | 2342.50 | 13-NOV-05:00 | 5613.48 | 01-NOV-04:19 | 0.00 | 0.00 |
December | 452063.24 | 08-DEC-14:50 | 98044.59 | 01-DEC-13:39 | 2548.03 | 20-DEC-19:19 | 5613.48 | 01-DEC-05:30 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | ||||||||
Minimum of Months | 341583.56 | 98044.59 | 0.00 | 5613.48 | 0.00 | 0.00 | ||||
Maximum of Months | 495044.09 | 98044.59 | 4077.20 | 5613.48 | 0.00 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY {AT MAX/MIN} [W] | |
January | 1472126.24 | 02-JAN-16:00 | 350141.41 | 423497.50 | 0.00 | 84459.03 | 117386.25 | 63901.72 | 0.00 | 329082.26 | 98044.59 |
February | 1602858.54 | 16-FEB-16:30 | 334652.47 | 541788.89 | 0.00 | 84451.06 | 112078.70 | 63962.94 | 0.00 | 362266.42 | 98044.59 |
March | 1776109.49 | 09-MAR-16:10 | 332294.83 | 660080.29 | 0.00 | 84450.25 | 119560.02 | 63777.76 | 0.00 | 412288.28 | 98044.59 |
April | 1951409.77 | 11-APR-15:20 | 332294.83 | 778371.69 | 0.00 | 84450.25 | 130240.92 | 64141.07 | 0.00 | 458252.96 | 98044.59 |
May | 1496277.38 | 31-MAY-07:00 | 332294.83 | 423497.50 | 0.00 | 118493.64 | 106728.05 | 66037.32 | 0.00 | 345567.99 | 98044.59 |
June | 1670454.92 | 08-JUN-15:00 | 332294.83 | 541788.89 | 0.00 | 84450.25 | 138515.25 | 65253.13 | 0.00 | 404494.50 | 98044.59 |
July | 1852449.64 | 27-JUL-15:00 | 332294.83 | 660080.29 | 0.00 | 84450.25 | 147781.15 | 65410.86 | 0.00 | 458774.20 | 98044.59 |
August | 1989371.34 | 23-AUG-15:09 | 332294.83 | 778371.69 | 0.00 | 84450.25 | 145084.46 | 65457.65 | 0.00 | 480054.41 | 98044.59 |
September | 1514146.46 | 21-SEP-15:30 | 332294.83 | 423497.50 | 0.00 | 84450.25 | 143065.02 | 65317.65 | 0.00 | 361863.15 | 98044.59 |
October | 1663923.92 | 03-OCT-15:09 | 332294.83 | 541788.89 | 0.00 | 84450.25 | 138827.55 | 65102.68 | 0.00 | 397801.67 | 98044.59 |
November | 1806104.57 | 09-NOV-16:00 | 346052.92 | 660080.29 | 0.00 | 84457.04 | 113579.26 | 65058.31 | 0.00 | 433218.70 | 98044.59 |
December | 1955321.76 | 08-DEC-16:00 | 352499.06 | 778371.69 | 0.00 | 84464.15 | 123815.22 | 64022.68 | 0.00 | 448490.91 | 98044.59 |
Annual Sum or Average | |||||||||||
Minimum of Months | 1472126.24 | 332294.83 | 423497.50 | 0.00 | 84450.25 | 106728.05 | 63777.76 | 0.00 | 329082.26 | 98044.59 | |
Maximum of Months | 1989371.34 | 352499.06 | 778371.69 | 0.00 | 118493.64 | 147781.15 | 66037.32 | 0.00 | 480054.41 | 98044.59 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS {Maximum} [W] | WATERSYSTEMS:NATURALGAS {TIMESTAMP} | COGENERATION:NATURALGAS [] | |
January | 0.00 | 0.00 | 255567.31 | 25-JAN-06:10 | 0.00 | 70632.11 | 23-JAN-12:50 | 0.00 |
February | 0.00 | 0.00 | 404990.47 | 04-FEB-06:10 | 0.00 | 70496.40 | 02-FEB-12:50 | 0.00 |
March | 0.00 | 0.00 | 300848.61 | 16-MAR-05:10 | 0.00 | 69496.77 | 02-MAR-12:39 | 0.00 |
April | 0.00 | 0.00 | 286.30 | 19-APR-05:00 | 0.00 | 66510.97 | 13-APR-11:39 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 64736.63 | 03-MAY-11:39 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 62308.94 | 01-JUN-11:30 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 60509.37 | 03-JUL-11:39 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 61825.93 | 30-AUG-11:30 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 63559.74 | 22-SEP-11:00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 66495.56 | 25-OCT-11:39 | 0.00 |
November | 0.00 | 0.00 | 99397.55 | 13-NOV-06:10 | 0.00 | 69182.43 | 30-NOV-12:20 | 0.00 |
December | 0.00 | 0.00 | 268992.92 | 15-DEC-06:10 | 0.00 | 70387.05 | 29-DEC-12:50 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 60509.37 | 0.00 | ||
Maximum of Months | 0.00 | 0.00 | 404990.47 | 0.00 | 70632.11 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 9.50 | 26.95 | 0.33 | 26.91 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 7.67 | 27.03 | 0.33 | 27.04 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 26.03 | 0.00 | 26.03 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 26.22 | 0.00 | 26.22 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 7.83 | 26.69 | 0.17 | 26.71 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 4.33 | 25.98 | 0.17 | 25.93 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 6.83 | 26.06 | 0.17 | 26.09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 9.83 | 25.97 | 0.17 | 25.95 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 9.00 | 26.24 | 0.33 | 26.28 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 9.33 | 26.17 | 0.17 | 26.15 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 11.83 | 26.63 | 1.83 | 26.70 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 7.83 | 26.48 | 0.50 | 26.53 |
Annual Sum or Average | 0.00 | 0.00 | 88.83 | 26.43 | 4.17 | 26.45 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 25.97 | 0.00 | 25.93 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 11.83 | 27.03 | 1.83 | 27.04 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 25.57 | 0.00 | 25.57 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.17 | 25.57 | 0.00 | 25.57 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 25.57 | 0.00 | 25.57 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 27.29 | 1.00 | 27.38 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 26.95 | 1.00 | 27.10 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 27.20 | 4.00 | 27.30 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 27.04 | 2.00 | 27.21 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 25.58 | 0.00 | 25.58 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 11.33 | 27.09 | 8.00 | 27.23 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 27.29 | 4.00 | 27.38 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.83 | 0.83 | 27.83 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 27.51 | 1.17 | 27.51 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.30 | 0.33 | 27.30 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 4.67 | 27.74 | 4.67 | 27.74 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 4.17 | 27.56 | 4.17 | 27.56 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 5.33 | 27.68 | 5.33 | 27.68 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 11.83 | 27.84 | 11.50 | 27.85 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 27.68 | 3.50 | 27.68 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 6.67 | 27.65 | 6.67 | 27.65 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 27.83 | 1.67 | 27.83 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 40.17 | 27.72 | 39.83 | 27.72 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 11.83 | 27.84 | 11.50 | 27.85 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 17.67 | 26.07 | 17.67 | 26.07 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 18.33 | 25.79 | 18.33 | 25.79 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 26.78 | 3.50 | 26.78 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 27.48 | 3.17 | 27.49 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 27.49 | 1.17 | 27.50 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 3.83 | 27.31 | 3.50 | 27.38 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 4.83 | 27.26 | 3.67 | 27.41 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 9.33 | 27.49 | 7.00 | 27.64 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 19.17 | 26.46 | 18.00 | 26.45 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 37.17 | 25.52 | 37.17 | 25.52 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 24.67 | 25.98 | 24.67 | 25.98 |
Annual Sum or Average | 0.00 | 0.00 | 143.17 | 26.16 | 137.83 | 26.15 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 37.17 | 27.49 | 37.17 | 27.64 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.30 | 0.50 | 27.30 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 4.33 | 27.93 | 3.50 | 28.06 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 12.83 | 27.14 | 4.67 | 27.31 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 22.00 | 27.52 | 7.33 | 27.70 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 9.67 | 27.61 | 4.33 | 27.69 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 16.67 | 27.06 | 5.17 | 27.24 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 28.17 | 27.37 | 10.00 | 27.56 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 35.33 | 27.40 | 10.67 | 27.55 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 11.33 | 27.50 | 5.83 | 27.66 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 15.67 | 27.37 | 7.50 | 27.55 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 12.50 | 27.18 | 5.17 | 27.36 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 13.50 | 27.37 | 6.67 | 27.55 |
Annual Sum or Average | 0.00 | 0.00 | 182.50 | 27.37 | 71.33 | 27.54 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.06 | 0.50 | 27.24 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 35.33 | 27.93 | 10.67 | 28.06 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 27.50 | 1.17 | 27.51 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 27.35 | 0.83 | 27.36 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 27.43 | 2.17 | 27.44 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.28 | 0.33 | 27.28 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 5.67 | 27.43 | 4.50 | 27.43 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 27.50 | 2.17 | 27.51 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.70 | 0.50 | 27.70 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.40 | 0.17 | 27.40 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 27.88 | 5.00 | 27.89 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 4.67 | 27.66 | 4.67 | 27.66 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 6.83 | 27.83 | 6.83 | 27.83 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 13.33 | 28.01 | 12.83 | 28.02 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 5.33 | 27.75 | 5.33 | 27.75 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 8.17 | 27.76 | 8.00 | 27.76 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 27.73 | 2.50 | 27.73 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 46.67 | 27.84 | 45.83 | 27.84 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 13.33 | 28.01 | 12.83 | 28.02 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 33.67 | 25.44 | 33.67 | 25.44 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 23.50 | 25.62 | 23.33 | 25.62 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 4.50 | 26.12 | 4.50 | 26.12 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 27.56 | 1.17 | 27.56 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 27.50 | 1.17 | 27.52 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 27.51 | 1.83 | 27.51 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 27.59 | 2.33 | 27.59 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 10.00 | 27.31 | 7.50 | 27.40 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 36.67 | 25.76 | 35.17 | 25.73 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 46.83 | 25.56 | 46.67 | 25.55 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 29.50 | 25.88 | 29.17 | 25.88 |
Annual Sum or Average | 0.00 | 0.00 | 191.33 | 25.81 | 186.50 | 25.79 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 46.83 | 27.59 | 46.67 | 27.59 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 28.13 | 1.83 | 28.13 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 28.00 | 1.17 | 27.99 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 6.17 | 28.13 | 3.33 | 28.17 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 4.67 | 28.01 | 2.83 | 28.04 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 28.01 | 2.17 | 28.05 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 9.33 | 27.94 | 5.33 | 28.01 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 5.50 | 27.89 | 3.00 | 28.03 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 6.17 | 27.96 | 4.00 | 28.02 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 4.33 | 28.00 | 4.00 | 28.01 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.63 | 0.67 | 27.63 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 27.81 | 1.00 | 27.81 |
Annual Sum or Average | 0.00 | 0.00 | 44.33 | 27.98 | 29.33 | 28.03 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 9.33 | 28.13 | 5.33 | 28.17 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.17 | 18.84 | 0.00 | 18.84 | 0.00 | 18.84 | 0.00 | 18.84 |
March | 0.17 | 19.38 | 0.00 | 19.38 | 0.00 | 19.38 | 0.00 | 19.38 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 27.59 | 2.50 | 27.59 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 27.58 | 2.67 | 27.58 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 9.33 | 27.59 | 7.17 | 27.60 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 27.55 | 3.00 | 27.55 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 4.33 | 27.48 | 3.83 | 27.48 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.17 | 19.38 | 0.00 | 19.38 | 0.00 | 19.38 | 0.00 | 19.38 |
Annual Sum or Average | 0.50 | 19.20 | 0.00 | 19.20 | 23.17 | 27.38 | 19.17 | 27.47 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.17 | 19.38 | 0.00 | 19.38 | 9.33 | 27.59 | 7.17 | 27.60 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.43 | 0.33 | 27.43 |
February | 0.17 | 18.89 | 0.00 | 18.89 | 0.00 | 18.89 | 0.00 | 18.89 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.35 | 0.33 | 27.35 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 6.00 | 27.85 | 5.67 | 27.85 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 6.67 | 27.76 | 6.33 | 27.76 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 8.00 | 27.94 | 7.17 | 27.96 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 15.67 | 28.13 | 13.33 | 28.17 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 7.33 | 27.83 | 7.00 | 27.83 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 9.33 | 27.92 | 8.33 | 27.95 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 4.17 | 27.61 | 4.17 | 27.61 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.17 | 18.89 | 0.00 | 18.89 | 57.83 | 27.89 | 52.67 | 27.92 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.17 | 18.89 | 0.00 | 18.89 | 15.67 | 28.13 | 13.33 | 28.17 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 10.83 | 26.35 | 10.83 | 26.35 |
February | 0.17 | 19.16 | 0.00 | 19.16 | 11.33 | 26.12 | 11.00 | 26.15 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 27.65 | 2.67 | 27.65 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 27.59 | 3.00 | 27.59 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 27.61 | 2.33 | 27.62 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 27.48 | 2.33 | 27.48 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 7.83 | 27.60 | 6.50 | 27.62 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 4.83 | 27.61 | 4.00 | 27.66 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 11.67 | 27.67 | 8.00 | 27.80 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 19.67 | 26.66 | 17.50 | 26.62 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 31.33 | 25.60 | 31.00 | 25.59 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 16.33 | 26.28 | 16.00 | 26.27 |
Annual Sum or Average | 0.17 | 19.16 | 0.00 | 19.16 | 125.33 | 26.54 | 115.17 | 26.52 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 25.60 | 2.33 | 25.59 |
Maximum of Months | 0.17 | 19.16 | 0.00 | 19.16 | 31.33 | 27.67 | 31.00 | 27.80 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.17 | 19.08 | 0.00 | 19.08 | 2.00 | 27.38 | 1.83 | 27.73 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 28.14 | 1.17 | 28.12 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 6.33 | 28.26 | 3.83 | 28.29 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 28.14 | 3.17 | 28.17 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 4.33 | 28.04 | 2.67 | 28.10 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 10.67 | 28.16 | 6.17 | 28.20 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 6.67 | 27.98 | 3.83 | 28.10 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 7.33 | 28.10 | 4.83 | 28.14 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 28.06 | 4.50 | 28.08 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 27.55 | 1.17 | 27.57 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 27.78 | 1.17 | 27.78 |
Annual Sum or Average | 0.17 | 19.08 | 0.00 | 19.08 | 51.50 | 28.06 | 34.33 | 28.11 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.17 | 19.08 | 0.00 | 19.08 | 10.67 | 28.26 | 6.17 | 28.29 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 12.33 | 27.63 | 12.33 | 27.63 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 12.33 | 27.63 | 12.33 | 27.63 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 12.33 | 27.63 | 12.33 | 27.63 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.58 | 0.33 | 27.58 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.33 | 27.58 | 0.33 | 27.58 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.58 | 0.33 | 27.58 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 147.83 | 28.19 | 137.50 | 28.19 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.78 | 0.00 | 27.78 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 666.17 | 28.79 | 477.83 | 28.88 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 64.00 | 27.91 | 63.00 | 27.92 |
Annual Sum or Average | 0.00 | 0.00 | 878.83 | 28.63 | 678.33 | 28.68 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 666.17 | 28.79 | 477.83 | 28.88 |
Report: ComfortReportSimple55Monthly
For: BASEMENT
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 121.83 | 25.49 | 435.50 | 24.87 | 121.83 | 24.98 |
February | 101.67 | 25.19 | 391.83 | 24.78 | 101.67 | 24.85 |
March | 133.50 | 25.19 | 451.00 | 24.68 | 133.50 | 24.78 |
April | 195.17 | 25.21 | 481.33 | 24.75 | 195.17 | 24.85 |
May | 268.00 | 25.02 | 508.00 | 24.70 | 268.00 | 24.78 |
June | 264.33 | 24.92 | 496.00 | 24.64 | 264.33 | 24.71 |
July | 260.17 | 25.23 | 497.00 | 24.84 | 260.17 | 24.94 |
August | 222.83 | 25.14 | 514.00 | 24.69 | 222.83 | 24.80 |
September | 247.83 | 25.14 | 485.00 | 24.77 | 247.83 | 24.87 |
October | 219.83 | 25.43 | 502.00 | 24.88 | 219.83 | 25.01 |
November | 173.50 | 25.42 | 487.50 | 24.85 | 173.50 | 24.97 |
December | 140.33 | 25.59 | 476.17 | 24.87 | 140.33 | 25.01 |
Annual Sum or Average | 2349.00 | 25.21 | 5725.33 | 24.77 | 2349.00 | 24.87 |
Minimum of Months | 101.67 | 24.92 | 391.83 | 24.64 | 101.67 | 24.71 |
Maximum of Months | 268.00 | 25.59 | 514.00 | 24.88 | 268.00 | 25.01 |
Report: ComfortReportSimple55Monthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 17.67 | 23.59 | 386.00 | 24.35 | 0.00 | 24.35 |
February | 15.00 | 23.49 | 369.50 | 24.34 | 0.00 | 24.34 |
March | 1.00 | 23.84 | 432.50 | 24.25 | 0.00 | 24.25 |
April | 0.00 | 0.00 | 476.50 | 24.14 | 0.00 | 24.14 |
May | 0.00 | 0.00 | 482.50 | 24.18 | 0.00 | 24.18 |
June | 0.00 | 0.00 | 479.50 | 24.13 | 0.00 | 24.13 |
July | 0.00 | 0.00 | 493.00 | 24.13 | 0.00 | 24.13 |
August | 0.00 | 0.00 | 512.83 | 24.11 | 0.00 | 24.11 |
September | 0.00 | 0.00 | 463.50 | 24.20 | 0.00 | 24.20 |
October | 0.00 | 0.00 | 495.67 | 24.22 | 0.00 | 24.22 |
November | 0.00 | 0.00 | 481.33 | 24.30 | 0.00 | 24.30 |
December | 0.00 | 0.00 | 451.00 | 24.32 | 0.00 | 24.32 |
Annual Sum or Average | 33.67 | 23.56 | 5523.83 | 24.22 | 0.00 | 24.22 |
Minimum of Months | 0.00 | 0.00 | 369.50 | 24.11 | 0.00 | 24.11 |
Maximum of Months | 17.67 | 23.84 | 512.83 | 24.35 | 0.00 | 24.35 |
Report: ComfortReportSimple55Monthly
For: CORE_MID
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 125.33 | 23.13 | 213.33 | 23.85 | 0.00 | 23.85 |
February | 92.50 | 23.06 | 229.17 | 23.97 | 0.00 | 23.97 |
March | 77.33 | 23.19 | 286.00 | 24.05 | 0.00 | 24.05 |
April | 26.83 | 23.15 | 315.33 | 24.18 | 0.00 | 24.18 |
May | 17.50 | 23.17 | 370.50 | 24.15 | 0.00 | 24.15 |
June | 20.67 | 23.14 | 370.17 | 24.11 | 0.00 | 24.11 |
July | 26.33 | 23.19 | 330.33 | 24.08 | 0.00 | 24.08 |
August | 22.17 | 23.15 | 359.17 | 24.11 | 0.00 | 24.11 |
September | 19.50 | 23.18 | 348.33 | 24.14 | 0.00 | 24.14 |
October | 10.17 | 23.17 | 399.67 | 24.22 | 0.00 | 24.22 |
November | 24.00 | 23.20 | 356.00 | 24.27 | 0.00 | 24.27 |
December | 104.33 | 23.04 | 248.67 | 23.91 | 0.00 | 23.91 |
Annual Sum or Average | 566.67 | 23.12 | 3826.67 | 24.09 | 0.00 | 24.09 |
Minimum of Months | 10.17 | 23.04 | 213.33 | 23.85 | 0.00 | 23.85 |
Maximum of Months | 125.33 | 23.20 | 399.67 | 24.27 | 0.00 | 24.27 |
Report: ComfortReportSimple55Monthly
For: CORE_TOP
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 260.33 | 22.85 | 138.50 | 23.29 | 0.00 | 23.29 |
February | 146.67 | 22.66 | 205.00 | 23.60 | 0.00 | 23.60 |
March | 111.83 | 22.94 | 279.00 | 23.88 | 0.00 | 23.88 |
April | 32.67 | 23.15 | 331.33 | 24.15 | 0.00 | 24.15 |
May | 4.50 | 23.15 | 420.67 | 24.21 | 0.00 | 24.21 |
June | 2.00 | 23.22 | 415.67 | 24.18 | 0.00 | 24.18 |
July | 3.33 | 23.24 | 423.50 | 24.17 | 0.00 | 24.17 |
August | 8.17 | 22.87 | 419.33 | 24.14 | 0.00 | 24.14 |
September | 0.33 | 23.28 | 395.17 | 24.21 | 0.00 | 24.21 |
October | 15.33 | 23.20 | 385.50 | 24.24 | 0.00 | 24.24 |
November | 67.33 | 22.93 | 307.83 | 24.04 | 0.00 | 24.04 |
December | 201.00 | 22.77 | 174.00 | 23.44 | 0.00 | 23.44 |
Annual Sum or Average | 853.50 | 22.84 | 3895.50 | 23.97 | 0.00 | 23.97 |
Minimum of Months | 0.33 | 22.66 | 138.50 | 23.29 | 0.00 | 23.29 |
Maximum of Months | 260.33 | 23.28 | 423.50 | 24.24 | 0.00 | 24.24 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 179.33 | 22.98 | 221.50 | 23.68 | 2.67 | 23.68 |
February | 97.00 | 23.08 | 291.83 | 23.96 | 5.33 | 23.98 |
March | 88.00 | 23.21 | 362.83 | 24.04 | 4.67 | 24.05 |
April | 2.83 | 24.01 | 446.83 | 24.24 | 0.67 | 24.24 |
May | 11.67 | 26.43 | 507.33 | 24.42 | 11.67 | 24.47 |
June | 7.83 | 26.74 | 496.00 | 24.39 | 7.83 | 24.43 |
July | 24.67 | 26.73 | 497.00 | 24.56 | 24.67 | 24.66 |
August | 14.83 | 26.70 | 514.00 | 24.37 | 14.83 | 24.43 |
September | 5.00 | 26.86 | 485.00 | 24.43 | 5.00 | 24.45 |
October | 0.50 | 26.74 | 498.00 | 24.37 | 0.50 | 24.37 |
November | 10.00 | 23.05 | 433.50 | 24.25 | 0.00 | 24.25 |
December | 110.17 | 23.05 | 309.50 | 23.95 | 0.00 | 23.95 |
Annual Sum or Average | 551.83 | 23.49 | 5063.33 | 24.24 | 77.83 | 24.27 |
Minimum of Months | 0.50 | 22.98 | 221.50 | 23.68 | 0.00 | 23.68 |
Maximum of Months | 179.33 | 26.86 | 514.00 | 24.56 | 24.67 | 24.66 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 158.33 | 22.94 | 257.17 | 23.83 | 8.83 | 23.88 |
February | 90.17 | 23.19 | 289.50 | 24.06 | 10.17 | 24.11 |
March | 71.00 | 23.06 | 364.50 | 24.02 | 5.17 | 24.04 |
April | 50.50 | 24.48 | 407.83 | 24.30 | 19.33 | 24.40 |
May | 28.00 | 26.44 | 489.00 | 24.49 | 27.00 | 24.59 |
June | 24.00 | 26.75 | 488.67 | 24.44 | 24.00 | 24.54 |
July | 50.33 | 26.81 | 489.67 | 24.66 | 50.33 | 24.85 |
August | 24.17 | 26.09 | 481.50 | 24.33 | 20.00 | 24.42 |
September | 32.33 | 26.72 | 473.67 | 24.58 | 32.33 | 24.71 |
October | 15.00 | 26.25 | 458.33 | 24.44 | 12.83 | 24.50 |
November | 30.67 | 23.20 | 403.00 | 24.17 | 2.00 | 24.18 |
December | 156.50 | 22.68 | 241.33 | 23.62 | 0.33 | 23.62 |
Annual Sum or Average | 731.00 | 23.91 | 4844.17 | 24.27 | 212.33 | 24.36 |
Minimum of Months | 15.00 | 22.68 | 241.33 | 23.62 | 0.33 | 23.62 |
Maximum of Months | 158.33 | 26.81 | 489.67 | 24.66 | 50.33 | 24.85 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 103.00 | 24.29 | 376.67 | 24.51 | 34.67 | 24.66 |
February | 60.50 | 24.66 | 381.67 | 24.55 | 27.83 | 24.69 |
March | 57.67 | 24.18 | 427.50 | 24.33 | 19.67 | 24.41 |
April | 17.83 | 26.35 | 453.50 | 24.40 | 15.67 | 24.48 |
May | 12.83 | 26.41 | 505.00 | 24.42 | 12.83 | 24.47 |
June | 4.83 | 26.77 | 496.00 | 24.35 | 4.83 | 24.37 |
July | 23.50 | 26.72 | 497.00 | 24.53 | 23.50 | 24.63 |
August | 18.83 | 26.81 | 513.33 | 24.41 | 18.83 | 24.49 |
September | 30.67 | 26.93 | 485.00 | 24.64 | 30.67 | 24.77 |
October | 39.83 | 27.02 | 501.00 | 24.76 | 39.83 | 24.92 |
November | 44.50 | 26.36 | 468.00 | 24.74 | 39.83 | 24.89 |
December | 80.00 | 24.91 | 408.67 | 24.61 | 40.17 | 24.78 |
Annual Sum or Average | 494.00 | 25.36 | 5513.33 | 24.52 | 308.33 | 24.63 |
Minimum of Months | 4.83 | 24.18 | 376.67 | 24.33 | 4.83 | 24.37 |
Maximum of Months | 103.00 | 27.02 | 513.33 | 24.76 | 40.17 | 24.92 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 116.83 | 22.90 | 300.17 | 23.98 | 4.50 | 24.00 |
February | 60.17 | 24.37 | 379.17 | 24.49 | 22.17 | 24.60 |
March | 48.00 | 25.28 | 457.00 | 24.57 | 27.50 | 24.69 |
April | 42.00 | 26.94 | 485.00 | 24.71 | 42.00 | 24.87 |
May | 29.67 | 26.89 | 508.00 | 24.59 | 29.67 | 24.71 |
June | 29.83 | 26.81 | 496.00 | 24.56 | 29.83 | 24.68 |
July | 57.67 | 26.81 | 497.00 | 24.80 | 57.67 | 24.99 |
August | 58.50 | 26.80 | 514.00 | 24.72 | 58.50 | 24.91 |
September | 30.50 | 26.84 | 485.00 | 24.62 | 30.50 | 24.74 |
October | 36.17 | 26.92 | 502.00 | 24.69 | 36.17 | 24.83 |
November | 31.33 | 26.28 | 481.17 | 24.63 | 26.50 | 24.74 |
December | 48.83 | 25.65 | 450.17 | 24.69 | 32.83 | 24.83 |
Annual Sum or Average | 589.50 | 25.56 | 5554.67 | 24.60 | 397.83 | 24.74 |
Minimum of Months | 29.67 | 22.90 | 300.17 | 23.98 | 4.50 | 24.00 |
Maximum of Months | 116.83 | 26.94 | 514.00 | 24.80 | 58.50 | 24.99 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 344.50 | 22.40 | 110.50 | 22.79 | 8.83 | 22.79 |
February | 218.83 | 22.59 | 179.83 | 23.21 | 22.67 | 23.20 |
March | 197.83 | 22.74 | 275.67 | 23.59 | 25.00 | 23.64 |
April | 53.33 | 24.00 | 384.67 | 24.24 | 18.83 | 24.29 |
May | 36.17 | 25.96 | 505.83 | 24.49 | 36.17 | 24.59 |
June | 25.83 | 26.38 | 496.00 | 24.50 | 25.83 | 24.59 |
July | 27.17 | 26.55 | 497.00 | 24.60 | 27.17 | 24.69 |
August | 35.50 | 26.02 | 500.50 | 24.47 | 35.50 | 24.57 |
September | 18.33 | 26.11 | 481.67 | 24.47 | 18.33 | 24.53 |
October | 38.17 | 25.70 | 468.50 | 24.51 | 36.00 | 24.60 |
November | 117.17 | 23.44 | 334.50 | 24.06 | 26.17 | 24.12 |
December | 287.67 | 22.51 | 171.50 | 23.13 | 29.00 | 23.19 |
Annual Sum or Average | 1400.50 | 23.12 | 4406.17 | 24.04 | 309.50 | 24.11 |
Minimum of Months | 18.33 | 22.40 | 110.50 | 22.79 | 8.83 | 22.79 |
Maximum of Months | 344.50 | 26.55 | 505.83 | 24.60 | 36.17 | 24.69 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 236.33 | 22.50 | 134.17 | 23.20 | 10.00 | 23.24 |
February | 153.33 | 22.69 | 186.83 | 23.54 | 16.33 | 23.57 |
March | 126.33 | 23.11 | 260.67 | 23.95 | 22.00 | 24.03 |
April | 73.83 | 24.84 | 326.17 | 24.59 | 40.50 | 24.76 |
May | 45.33 | 26.30 | 409.00 | 24.68 | 44.67 | 24.83 |
June | 42.17 | 26.66 | 417.33 | 24.70 | 42.17 | 24.86 |
July | 60.00 | 26.85 | 420.83 | 24.92 | 60.00 | 25.14 |
August | 52.17 | 25.79 | 410.33 | 24.62 | 41.50 | 24.78 |
September | 47.50 | 26.63 | 397.50 | 24.79 | 47.50 | 24.97 |
October | 52.83 | 25.97 | 377.17 | 24.77 | 46.17 | 24.93 |
November | 82.67 | 23.55 | 290.50 | 24.21 | 21.00 | 24.30 |
December | 250.67 | 22.49 | 156.00 | 23.21 | 25.50 | 23.30 |
Annual Sum or Average | 1223.17 | 23.74 | 3786.50 | 24.31 | 417.33 | 24.46 |
Minimum of Months | 42.17 | 22.49 | 134.17 | 23.20 | 10.00 | 23.24 |
Maximum of Months | 250.67 | 26.85 | 420.83 | 24.92 | 60.00 | 25.14 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 133.17 | 23.84 | 346.33 | 24.39 | 39.33 | 24.54 |
February | 92.33 | 23.98 | 344.00 | 24.39 | 35.50 | 24.52 |
March | 97.50 | 23.81 | 385.83 | 24.25 | 35.17 | 24.36 |
April | 41.17 | 25.21 | 421.83 | 24.45 | 29.17 | 24.55 |
May | 36.17 | 25.89 | 503.17 | 24.48 | 36.17 | 24.57 |
June | 21.50 | 26.19 | 496.00 | 24.44 | 21.50 | 24.51 |
July | 24.33 | 26.50 | 497.00 | 24.55 | 24.33 | 24.64 |
August | 39.50 | 26.21 | 501.83 | 24.52 | 39.50 | 24.64 |
September | 45.33 | 26.72 | 485.00 | 24.72 | 45.33 | 24.88 |
October | 70.33 | 26.78 | 497.50 | 24.94 | 69.83 | 25.14 |
November | 87.17 | 25.59 | 451.50 | 24.81 | 66.83 | 24.98 |
December | 154.67 | 24.24 | 357.50 | 24.50 | 64.83 | 24.70 |
Annual Sum or Average | 843.17 | 24.91 | 5287.50 | 24.55 | 507.50 | 24.68 |
Minimum of Months | 21.50 | 23.81 | 344.00 | 24.25 | 21.50 | 24.36 |
Maximum of Months | 154.67 | 26.78 | 503.17 | 24.94 | 69.83 | 25.14 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 292.50 | 22.31 | 145.83 | 22.94 | 5.00 | 22.95 |
February | 176.50 | 22.70 | 225.83 | 23.59 | 24.83 | 23.65 |
March | 136.17 | 22.93 | 342.83 | 23.97 | 26.00 | 24.07 |
April | 55.50 | 25.37 | 422.00 | 24.56 | 38.00 | 24.71 |
May | 42.67 | 26.38 | 487.67 | 24.61 | 41.50 | 24.75 |
June | 30.50 | 26.67 | 492.00 | 24.54 | 30.50 | 24.66 |
July | 36.17 | 26.84 | 494.67 | 24.67 | 36.17 | 24.81 |
August | 33.33 | 26.47 | 501.00 | 24.56 | 32.17 | 24.67 |
September | 33.17 | 26.64 | 467.00 | 24.62 | 32.00 | 24.75 |
October | 51.17 | 26.06 | 460.83 | 24.68 | 43.50 | 24.83 |
November | 97.17 | 23.46 | 357.00 | 24.17 | 24.83 | 24.26 |
December | 248.17 | 22.60 | 227.67 | 23.46 | 30.33 | 23.57 |
Annual Sum or Average | 1233.00 | 23.49 | 4624.33 | 24.23 | 364.83 | 24.35 |
Minimum of Months | 30.50 | 22.31 | 145.83 | 22.94 | 5.00 | 22.95 |
Maximum of Months | 292.50 | 26.84 | 501.00 | 24.68 | 43.50 | 24.83 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 376.83 | 22.11 | 114.50 | 22.42 | 29.83 | 22.37 |
February | 241.50 | 22.35 | 176.67 | 22.93 | 32.33 | 22.88 |
March | 220.00 | 22.55 | 275.33 | 23.43 | 31.50 | 23.46 |
April | 78.00 | 23.62 | 366.17 | 24.17 | 21.33 | 24.23 |
May | 53.00 | 25.95 | 501.83 | 24.55 | 51.33 | 24.68 |
June | 39.33 | 26.45 | 496.00 | 24.57 | 39.33 | 24.70 |
July | 47.33 | 26.58 | 497.00 | 24.70 | 47.33 | 24.85 |
August | 46.50 | 25.90 | 497.67 | 24.51 | 42.83 | 24.63 |
September | 37.67 | 26.19 | 474.67 | 24.56 | 37.33 | 24.68 |
October | 56.33 | 25.15 | 448.67 | 24.51 | 43.50 | 24.61 |
November | 150.50 | 23.08 | 317.33 | 23.87 | 33.33 | 23.92 |
December | 314.17 | 22.21 | 167.83 | 22.81 | 45.17 | 22.86 |
Annual Sum or Average | 1661.17 | 23.04 | 4333.67 | 23.96 | 455.17 | 24.03 |
Minimum of Months | 37.67 | 22.11 | 114.50 | 22.42 | 21.33 | 22.37 |
Maximum of Months | 376.83 | 26.58 | 501.83 | 24.70 | 51.33 | 24.85 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 283.33 | 22.29 | 165.33 | 22.97 | 17.83 | 22.99 |
February | 180.83 | 22.48 | 229.17 | 23.37 | 22.17 | 23.36 |
March | 157.83 | 23.01 | 319.67 | 23.85 | 27.17 | 23.91 |
April | 95.17 | 24.50 | 392.00 | 24.45 | 46.00 | 24.62 |
May | 57.83 | 26.09 | 479.50 | 24.62 | 53.67 | 24.78 |
June | 46.00 | 26.70 | 493.83 | 24.63 | 46.00 | 24.79 |
July | 66.00 | 26.86 | 492.00 | 24.84 | 66.00 | 25.05 |
August | 59.33 | 25.60 | 483.50 | 24.54 | 44.67 | 24.69 |
September | 53.83 | 26.46 | 463.67 | 24.71 | 50.67 | 24.88 |
October | 86.67 | 25.45 | 444.17 | 24.67 | 65.17 | 24.84 |
November | 118.50 | 23.26 | 337.83 | 24.04 | 25.17 | 24.12 |
December | 304.33 | 22.27 | 191.50 | 22.99 | 35.50 | 23.06 |
Annual Sum or Average | 1509.67 | 23.54 | 4492.17 | 24.18 | 500.00 | 24.32 |
Minimum of Months | 46.00 | 22.27 | 165.33 | 22.97 | 17.83 | 22.99 |
Maximum of Months | 304.33 | 26.86 | 493.83 | 24.84 | 66.00 | 25.05 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 168.17 | 23.31 | 304.33 | 24.07 | 41.00 | 24.22 |
February | 117.33 | 23.47 | 324.50 | 24.13 | 41.17 | 24.23 |
March | 125.67 | 23.47 | 364.00 | 24.10 | 40.83 | 24.21 |
April | 72.83 | 24.55 | 399.00 | 24.41 | 36.33 | 24.53 |
May | 53.50 | 25.91 | 495.83 | 24.55 | 51.83 | 24.67 |
June | 34.33 | 26.30 | 493.33 | 24.51 | 34.33 | 24.62 |
July | 45.00 | 26.52 | 495.83 | 24.66 | 45.00 | 24.80 |
August | 46.50 | 26.09 | 498.50 | 24.55 | 44.17 | 24.67 |
September | 53.50 | 26.65 | 479.83 | 24.75 | 53.50 | 24.92 |
October | 79.00 | 26.50 | 489.67 | 24.90 | 74.83 | 25.10 |
November | 95.33 | 25.01 | 425.83 | 24.65 | 62.17 | 24.83 |
December | 196.00 | 23.67 | 329.33 | 24.20 | 66.83 | 24.40 |
Annual Sum or Average | 1087.17 | 24.51 | 5100.00 | 24.47 | 592.00 | 24.62 |
Minimum of Months | 34.33 | 23.31 | 304.33 | 24.07 | 34.33 | 24.21 |
Maximum of Months | 196.00 | 26.65 | 498.50 | 24.90 | 74.83 | 25.10 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 328.67 | 22.05 | 134.33 | 22.61 | 15.50 | 22.60 |
February | 209.17 | 22.45 | 208.33 | 23.29 | 32.00 | 23.33 |
March | 161.17 | 22.68 | 317.00 | 23.77 | 30.67 | 23.86 |
April | 84.33 | 24.49 | 387.17 | 24.47 | 40.17 | 24.62 |
May | 55.83 | 26.01 | 468.83 | 24.63 | 50.00 | 24.78 |
June | 36.67 | 26.51 | 481.50 | 24.56 | 35.50 | 24.69 |
July | 46.67 | 26.79 | 486.83 | 24.72 | 46.67 | 24.88 |
August | 48.17 | 25.67 | 492.33 | 24.53 | 37.00 | 24.66 |
September | 45.33 | 26.06 | 448.50 | 24.63 | 38.17 | 24.78 |
October | 73.67 | 25.28 | 435.17 | 24.64 | 50.00 | 24.80 |
November | 140.17 | 23.14 | 329.67 | 23.98 | 30.50 | 24.07 |
December | 281.50 | 22.33 | 205.17 | 23.16 | 38.33 | 23.28 |
Annual Sum or Average | 1511.33 | 23.26 | 4394.83 | 24.11 | 444.50 | 24.24 |
Minimum of Months | 36.67 | 22.05 | 134.33 | 22.61 | 15.50 | 22.60 |
Maximum of Months | 328.67 | 26.79 | 492.33 | 24.72 | 50.00 | 24.88 |
Report: ComfortReportSimple55Monthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 18.33 | 27.00 | 502.00 | 27.00 | 18.33 | 27.00 |
February | 87.17 | 27.00 | 454.00 | 27.00 | 87.17 | 27.00 |
March | 205.33 | 27.00 | 514.00 | 27.00 | 205.33 | 27.00 |
April | 381.33 | 27.00 | 485.00 | 27.00 | 381.33 | 27.00 |
May | 145.17 | 27.00 | 508.00 | 27.00 | 145.17 | 27.00 |
June | 235.67 | 27.00 | 496.00 | 27.00 | 235.67 | 27.00 |
July | 360.83 | 27.00 | 497.00 | 27.00 | 360.83 | 27.00 |
August | 499.00 | 27.08 | 514.00 | 27.08 | 499.00 | 27.08 |
September | 182.83 | 27.00 | 485.00 | 27.00 | 182.83 | 27.00 |
October | 218.33 | 27.00 | 502.00 | 27.00 | 218.33 | 27.00 |
November | 237.17 | 27.00 | 489.00 | 27.00 | 237.17 | 27.00 |
December | 293.83 | 27.00 | 497.00 | 27.00 | 293.83 | 27.00 |
Annual Sum or Average | 2865.00 | 27.01 | 5943.00 | 27.01 | 2865.00 | 27.01 |
Minimum of Months | 18.33 | 27.00 | 454.00 | 27.00 | 18.33 | 27.00 |
Maximum of Months | 499.00 | 27.08 | 514.00 | 27.08 | 499.00 | 27.08 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.50 | 27.00 | 502.00 | 27.00 | 0.50 | 27.00 |
February | 5.33 | 27.00 | 454.00 | 27.00 | 5.33 | 27.00 |
March | 24.17 | 27.00 | 514.00 | 27.00 | 24.17 | 27.00 |
April | 75.83 | 27.00 | 485.00 | 27.00 | 75.83 | 27.00 |
May | 37.83 | 27.00 | 508.00 | 27.00 | 37.83 | 27.00 |
June | 41.50 | 27.00 | 496.00 | 27.00 | 41.50 | 27.00 |
July | 94.33 | 27.00 | 497.00 | 27.00 | 94.33 | 27.00 |
August | 158.17 | 27.12 | 514.00 | 27.06 | 158.17 | 27.07 |
September | 37.83 | 27.00 | 485.00 | 27.00 | 37.83 | 27.00 |
October | 40.00 | 27.00 | 502.00 | 27.00 | 40.00 | 27.00 |
November | 35.50 | 27.00 | 489.00 | 27.00 | 35.50 | 27.00 |
December | 26.67 | 27.00 | 497.00 | 27.00 | 26.67 | 27.00 |
Annual Sum or Average | 577.67 | 27.03 | 5943.00 | 27.01 | 577.67 | 27.01 |
Minimum of Months | 0.50 | 27.00 | 454.00 | 27.00 | 0.50 | 27.00 |
Maximum of Months | 158.17 | 27.12 | 514.00 | 27.06 | 158.17 | 27.07 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 4.33 | 27.00 | 499.83 | 27.00 | 4.33 | 27.00 |
February | 17.50 | 27.00 | 444.50 | 27.00 | 17.50 | 27.00 |
March | 56.17 | 27.00 | 514.00 | 27.00 | 56.17 | 27.00 |
April | 133.83 | 27.00 | 485.00 | 27.00 | 133.83 | 27.00 |
May | 112.33 | 27.00 | 508.00 | 27.00 | 112.33 | 27.00 |
June | 136.50 | 27.00 | 496.00 | 27.00 | 136.50 | 27.00 |
July | 191.67 | 27.00 | 497.00 | 27.00 | 191.67 | 27.00 |
August | 207.83 | 27.06 | 514.00 | 27.04 | 207.83 | 27.04 |
September | 116.50 | 27.00 | 485.00 | 27.00 | 116.50 | 27.00 |
October | 89.67 | 27.00 | 502.00 | 27.00 | 89.67 | 27.00 |
November | 64.50 | 27.00 | 489.00 | 27.00 | 64.50 | 27.00 |
December | 38.00 | 27.00 | 497.00 | 27.00 | 38.00 | 27.00 |
Annual Sum or Average | 1168.83 | 27.01 | 5931.33 | 27.00 | 1168.83 | 27.01 |
Minimum of Months | 4.33 | 27.00 | 444.50 | 27.00 | 4.33 | 27.00 |
Maximum of Months | 207.83 | 27.06 | 514.00 | 27.04 | 207.83 | 27.04 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 27.00 | 502.00 | 27.00 | 502.00 | 27.00 |
February | 454.00 | 27.00 | 454.00 | 27.00 | 454.00 | 27.00 |
March | 514.00 | 27.00 | 514.00 | 27.00 | 514.00 | 27.00 |
April | 485.00 | 27.42 | 485.00 | 27.42 | 485.00 | 27.42 |
May | 508.00 | 27.00 | 508.00 | 27.00 | 508.00 | 27.00 |
June | 496.00 | 27.00 | 496.00 | 27.00 | 496.00 | 27.00 |
July | 497.00 | 27.00 | 497.00 | 27.00 | 497.00 | 27.00 |
August | 514.00 | 28.88 | 514.00 | 28.88 | 514.00 | 28.88 |
September | 485.00 | 27.01 | 485.00 | 27.01 | 485.00 | 27.01 |
October | 502.00 | 27.00 | 502.00 | 27.00 | 502.00 | 27.00 |
November | 489.00 | 27.00 | 489.00 | 27.00 | 489.00 | 27.00 |
December | 497.00 | 27.16 | 497.00 | 27.16 | 497.00 | 27.16 |
Annual Sum or Average | 5943.00 | 27.21 | 5943.00 | 27.21 | 5943.00 | 27.21 |
Minimum of Months | 454.00 | 27.00 | 454.00 | 27.00 | 454.00 | 27.00 |
Maximum of Months | 514.00 | 28.88 | 514.00 | 28.88 | 514.00 | 28.88 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 27.00059 | 37.45426 | 0.95130 | 24.21221 |
February | 454.00000 | 27.00140 | 36.31815 | 0.99175 | 25.88347 |
March | 514.00000 | 27.00091 | 36.50348 | 1.03216 | 27.55770 |
April | 485.00000 | 27.00132 | 38.14079 | 1.08488 | 29.85307 |
May | 508.00000 | 27.00025 | 43.31497 | 0.38385 | 8.12235 |
June | 496.00000 | 27.00300 | 41.66378 | 0.41521 | 8.64181 |
July | 497.00000 | 27.00157 | 40.58876 | 0.45722 | 9.41211 |
August | 514.00000 | 27.07481 | 39.79744 | 0.52425 | 10.87939 |
September | 485.00000 | 27.00000 | 44.68871 | 0.39668 | 8.32782 |
October | 502.00000 | 27.00257 | 40.90274 | 1.05062 | 28.32281 |
November | 489.00000 | 27.00133 | 38.37584 | 1.05311 | 28.44347 |
December | 497.00000 | 27.00030 | 36.66202 | 1.05482 | 28.53038 |
Annual Sum or Average | 5943.00000 | 27.00757 | 39.54961 | 0.78095 | 19.78409 |
Minimum of Months | 454.00000 | 27.00000 | 36.31815 | 0.38385 | 8.12235 |
Maximum of Months | 514.00000 | 27.07481 | 44.68871 | 1.08488 | 29.85307 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 27.00028 | 37.84224 | 0.88326 | 21.60760 |
February | 454.00000 | 27.00134 | 36.41240 | 0.90724 | 22.55113 |
March | 514.00000 | 27.00096 | 36.51386 | 0.94486 | 23.97408 |
April | 485.00000 | 27.00076 | 38.11900 | 0.99843 | 26.09783 |
May | 508.00000 | 27.00008 | 43.62126 | 0.33367 | 7.38053 |
June | 496.00000 | 27.00311 | 41.79544 | 0.34408 | 7.52194 |
July | 497.00000 | 27.00168 | 40.64690 | 0.36146 | 7.78239 |
August | 514.00000 | 27.03757 | 39.85854 | 0.38480 | 8.19882 |
September | 485.00000 | 27.00000 | 45.09732 | 0.34246 | 7.49689 |
October | 502.00000 | 27.00262 | 41.02548 | 0.99678 | 26.01633 |
November | 489.00000 | 27.00139 | 38.41444 | 0.96890 | 24.90518 |
December | 497.00000 | 27.00035 | 36.65022 | 0.93179 | 23.44278 |
Annual Sum or Average | 5943.00000 | 27.00429 | 39.68191 | 0.69765 | 17.18887 |
Minimum of Months | 454.00000 | 27.00000 | 36.41240 | 0.33367 | 7.38053 |
Maximum of Months | 514.00000 | 27.03757 | 45.09732 | 0.99843 | 26.09783 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 27.00053 | 38.08443 | 0.85923 | 20.80865 |
February | 454.00000 | 27.00137 | 36.46815 | 0.89390 | 22.14828 |
March | 514.00000 | 27.00097 | 36.55152 | 0.93931 | 23.83257 |
April | 485.00000 | 27.00058 | 38.15863 | 1.00281 | 26.32158 |
May | 508.00000 | 27.00020 | 43.56551 | 0.35179 | 7.69474 |
June | 496.00000 | 27.00307 | 41.78757 | 0.36529 | 7.87910 |
July | 497.00000 | 27.00167 | 40.65966 | 0.38762 | 8.24553 |
August | 514.00000 | 27.02648 | 39.90006 | 0.39942 | 8.49213 |
September | 485.00000 | 27.00000 | 45.04295 | 0.35873 | 7.78377 |
October | 502.00000 | 27.00261 | 41.06668 | 1.00067 | 26.20438 |
November | 489.00000 | 27.00141 | 38.46761 | 0.96027 | 24.62085 |
December | 497.00000 | 27.00040 | 36.70746 | 0.90964 | 22.66379 |
Annual Sum or Average | 5943.00000 | 27.00335 | 39.72056 | 0.70035 | 17.16815 |
Minimum of Months | 454.00000 | 27.00000 | 36.46815 | 0.35179 | 7.69474 |
Maximum of Months | 514.00000 | 27.02648 | 45.04295 | 1.00281 | 26.32158 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 27.00237 | 36.96311 | 1.17174 | 33.90078 |
February | 454.00000 | 27.00210 | 36.66654 | 1.31487 | 41.05456 |
March | 514.00000 | 27.00137 | 36.95318 | 1.44967 | 48.18049 |
April | 485.00000 | 27.41788 | 38.06951 | 1.67110 | 60.08625 |
May | 508.00000 | 27.00480 | 40.73914 | 0.62792 | 13.31359 |
June | 496.00000 | 27.00382 | 40.18535 | 0.82879 | 19.51009 |
July | 497.00000 | 27.00159 | 39.90105 | 1.02998 | 27.41843 |
August | 514.00000 | 28.87615 | 38.32777 | 1.76687 | 64.87990 |
September | 485.00000 | 27.00572 | 41.50727 | 0.66718 | 14.40778 |
October | 502.00000 | 27.00318 | 39.72867 | 1.35898 | 43.34406 |
November | 489.00000 | 27.00136 | 38.20500 | 1.48299 | 49.98000 |
December | 497.00000 | 27.15975 | 37.00081 | 1.62695 | 57.78130 |
Annual Sum or Average | 5943.00000 | 27.21192 | 38.69509 | 1.25029 | 39.52265 |
Minimum of Months | 454.00000 | 27.00136 | 36.66654 | 0.62792 | 13.31359 |
Maximum of Months | 514.00000 | 28.87615 | 41.50727 | 1.76687 | 64.87990 |
Report: OccupantComfortDataSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.60445 | 52.93740 | 0.63388 | 14.41319 |
February | 454.00000 | 24.58048 | 53.18276 | 0.62850 | 14.15155 |
March | 514.00000 | 24.47074 | 54.92106 | 0.61615 | 13.73526 |
April | 485.00000 | 24.55798 | 60.78160 | 0.67415 | 15.31150 |
May | 508.00000 | 24.53605 | 63.72341 | -0.1493 | 6.83729 |
June | 496.00000 | 24.49079 | 63.68977 | -0.1616 | 6.73915 |
July | 497.00000 | 24.64227 | 62.61245 | -0.1191 | 6.93282 |
August | 514.00000 | 24.49955 | 62.21495 | -0.1517 | 6.82502 |
September | 485.00000 | 24.58323 | 62.74755 | -0.1301 | 6.95919 |
October | 502.00000 | 24.63727 | 61.52809 | 0.71002 | 16.56234 |
November | 489.00000 | 24.64427 | 59.04061 | 0.69491 | 15.98128 |
December | 497.00000 | 24.63544 | 55.04506 | 0.66092 | 15.20620 |
Annual Sum or Average | 5943.00000 | 24.57293 | 59.40341 | 0.32234 | 11.60654 |
Minimum of Months | 454.00000 | 24.47074 | 52.93740 | -0.1616 | 6.73915 |
Maximum of Months | 514.00000 | 24.64427 | 63.72341 | 0.71002 | 16.56234 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.25306 | 45.44312 | 0.50289 | 10.64173 |
February | 454.00000 | 24.28037 | 45.33734 | 0.51714 | 10.97705 |
March | 514.00000 | 24.20200 | 45.64562 | 0.50954 | 10.63245 |
April | 485.00000 | 24.13942 | 48.18204 | 0.52047 | 10.73465 |
May | 508.00000 | 24.14905 | 48.79085 | -0.3460 | 7.73409 |
June | 496.00000 | 24.11214 | 48.77228 | -0.3485 | 7.65627 |
July | 497.00000 | 24.12322 | 48.44126 | -0.3398 | 7.49434 |
August | 514.00000 | 24.10746 | 48.41622 | -0.3325 | 7.37139 |
September | 485.00000 | 24.17331 | 48.52582 | -0.3360 | 7.59921 |
October | 502.00000 | 24.21274 | 48.25938 | 0.53531 | 11.12030 |
November | 489.00000 | 24.29456 | 47.71190 | 0.55086 | 11.56933 |
December | 497.00000 | 24.27966 | 46.48299 | 0.53268 | 11.16507 |
Annual Sum or Average | 5943.00000 | 24.19308 | 47.51105 | 0.16036 | 9.54258 |
Minimum of Months | 454.00000 | 24.10746 | 45.33734 | -0.3485 | 7.37139 |
Maximum of Months | 514.00000 | 24.29456 | 48.79085 | 0.55086 | 11.56933 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.84860 | 47.00432 | 0.38690 | 8.49839 |
February | 454.00000 | 23.89553 | 46.99994 | 0.40263 | 8.95102 |
March | 514.00000 | 23.97148 | 46.86893 | 0.42873 | 9.19402 |
April | 485.00000 | 24.02267 | 49.29628 | 0.46562 | 9.76074 |
May | 508.00000 | 24.03402 | 49.45330 | -0.4073 | 8.81379 |
June | 496.00000 | 24.00762 | 49.50408 | -0.4106 | 8.87188 |
July | 497.00000 | 23.95401 | 49.50528 | -0.4298 | 9.20049 |
August | 514.00000 | 23.99234 | 49.61664 | -0.4174 | 8.96848 |
September | 485.00000 | 24.01747 | 49.32806 | -0.4116 | 8.91602 |
October | 502.00000 | 24.11901 | 49.00585 | 0.49201 | 10.26929 |
November | 489.00000 | 24.13231 | 49.11630 | 0.48748 | 10.28644 |
December | 497.00000 | 23.87673 | 48.38395 | 0.40625 | 8.81501 |
Annual Sum or Average | 5943.00000 | 23.98971 | 48.68023 | 0.07944 | 9.21092 |
Minimum of Months | 454.00000 | 23.84860 | 46.86893 | -0.4298 | 8.49839 |
Maximum of Months | 514.00000 | 24.13231 | 49.61664 | 0.49201 | 10.28644 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.39727 | 48.42277 | 0.27534 | 7.44545 |
February | 454.00000 | 23.62675 | 47.70823 | 0.33860 | 8.58133 |
March | 514.00000 | 23.83849 | 47.22844 | 0.39941 | 9.00274 |
April | 485.00000 | 24.01305 | 49.21357 | 0.47111 | 9.88208 |
May | 508.00000 | 24.11131 | 48.99137 | -0.3643 | 8.11354 |
June | 496.00000 | 24.09750 | 48.98899 | -0.3616 | 8.04301 |
July | 497.00000 | 24.09457 | 48.80579 | -0.3623 | 8.03298 |
August | 514.00000 | 24.05273 | 49.19764 | -0.3796 | 8.34290 |
September | 485.00000 | 24.09600 | 48.92886 | -0.3702 | 8.19426 |
October | 502.00000 | 24.10793 | 48.98937 | 0.49581 | 10.36291 |
November | 489.00000 | 23.96020 | 49.73878 | 0.44841 | 9.63354 |
December | 497.00000 | 23.50036 | 49.62284 | 0.31410 | 7.91494 |
Annual Sum or Average | 5943.00000 | 23.90968 | 48.82214 | 0.07250 | 8.62634 |
Minimum of Months | 454.00000 | 23.39727 | 47.22844 | -0.3796 | 7.44545 |
Maximum of Months | 514.00000 | 24.11131 | 49.73878 | 0.49581 | 10.36291 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.70305 | 46.88679 | 0.34310 | 8.39103 |
February | 454.00000 | 23.92293 | 46.50794 | 0.41735 | 9.60841 |
March | 514.00000 | 24.00937 | 46.46176 | 0.45118 | 10.02051 |
April | 485.00000 | 24.20751 | 47.93600 | 0.54085 | 11.36854 |
May | 508.00000 | 24.37614 | 48.75839 | -0.2197 | 6.79532 |
June | 496.00000 | 24.35578 | 48.07995 | -0.1980 | 6.51829 |
July | 497.00000 | 24.45596 | 47.35226 | -0.1592 | 6.52473 |
August | 514.00000 | 24.30233 | 47.85558 | -0.2165 | 6.66417 |
September | 485.00000 | 24.40104 | 48.05019 | -0.2153 | 6.76654 |
October | 502.00000 | 24.36156 | 48.35963 | 0.58248 | 12.48588 |
November | 489.00000 | 24.21092 | 48.12116 | 0.52414 | 11.05754 |
December | 497.00000 | 23.93851 | 47.84954 | 0.42464 | 9.49686 |
Annual Sum or Average | 5943.00000 | 24.18838 | 47.69042 | 0.18695 | 8.79502 |
Minimum of Months | 454.00000 | 23.70305 | 46.46176 | -0.2197 | 6.51829 |
Maximum of Months | 514.00000 | 24.45596 | 48.75839 | 0.58248 | 12.48588 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.77581 | 45.99462 | 0.39944 | 9.66795 |
February | 454.00000 | 23.93277 | 45.96698 | 0.46124 | 10.51241 |
March | 514.00000 | 23.95299 | 45.93721 | 0.48761 | 10.78054 |
April | 485.00000 | 24.13081 | 47.67390 | 0.57339 | 12.62739 |
May | 508.00000 | 24.34054 | 48.30970 | -0.1691 | 6.69429 |
June | 496.00000 | 24.31434 | 47.82595 | -0.1627 | 6.53092 |
July | 497.00000 | 24.42919 | 47.08916 | -0.1173 | 6.90881 |
August | 514.00000 | 24.18642 | 47.90350 | -0.2141 | 6.98216 |
September | 485.00000 | 24.41513 | 47.49391 | -0.1480 | 6.73577 |
October | 502.00000 | 24.29670 | 47.97575 | 0.60963 | 13.36401 |
November | 489.00000 | 24.09548 | 47.98185 | 0.52845 | 11.28017 |
December | 497.00000 | 23.62745 | 48.21060 | 0.37901 | 9.05771 |
Annual Sum or Average | 5943.00000 | 24.12554 | 47.37048 | 0.21617 | 9.24571 |
Minimum of Months | 454.00000 | 23.62745 | 45.93721 | -0.2141 | 6.53092 |
Maximum of Months | 514.00000 | 24.42919 | 48.30970 | 0.60963 | 13.36401 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.30044 | 44.37713 | 0.56202 | 13.15860 |
February | 454.00000 | 24.36306 | 44.73301 | 0.59186 | 13.70605 |
March | 514.00000 | 24.21957 | 45.35970 | 0.55411 | 12.31858 |
April | 485.00000 | 24.29396 | 47.49833 | 0.58412 | 12.61091 |
May | 508.00000 | 24.36469 | 48.82425 | -0.2258 | 6.86272 |
June | 496.00000 | 24.32343 | 48.26071 | -0.2227 | 6.65325 |
July | 497.00000 | 24.42823 | 47.47332 | -0.1766 | 6.60258 |
August | 514.00000 | 24.31834 | 47.71723 | -0.1949 | 6.60761 |
September | 485.00000 | 24.49856 | 47.43868 | -0.1292 | 6.73796 |
October | 502.00000 | 24.58288 | 47.14873 | 0.70165 | 16.25291 |
November | 489.00000 | 24.55166 | 46.50159 | 0.67973 | 15.66978 |
December | 497.00000 | 24.36724 | 45.83427 | 0.60579 | 14.15173 |
Annual Sum or Average | 5943.00000 | 24.38363 | 46.77670 | 0.27409 | 10.91420 |
Minimum of Months | 454.00000 | 24.21957 | 44.37713 | -0.2258 | 6.60258 |
Maximum of Months | 514.00000 | 24.58288 | 48.82425 | 0.70165 | 16.25291 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.90124 | 45.30058 | 0.45606 | 10.48293 |
February | 454.00000 | 24.30713 | 44.50710 | 0.59452 | 13.74841 |
March | 514.00000 | 24.39711 | 44.28346 | 0.65817 | 15.10269 |
April | 485.00000 | 24.51633 | 46.20040 | 0.75467 | 17.79462 |
May | 508.00000 | 24.45520 | 47.64089 | -0.0764 | 6.42734 |
June | 496.00000 | 24.42410 | 47.19717 | -0.0595 | 6.21492 |
July | 497.00000 | 24.56261 | 46.40594 | 0.02745 | 6.65301 |
August | 514.00000 | 24.47990 | 46.51032 | 0.03674 | 6.51678 |
September | 485.00000 | 24.47995 | 47.08933 | -0.0814 | 6.53860 |
October | 502.00000 | 24.52781 | 46.90653 | 0.71585 | 16.51463 |
November | 489.00000 | 24.50192 | 46.28902 | 0.69037 | 15.68839 |
December | 497.00000 | 24.49041 | 45.10074 | 0.66001 | 15.18974 |
Annual Sum or Average | 5943.00000 | 24.42053 | 46.12708 | 0.36225 | 11.37199 |
Minimum of Months | 454.00000 | 23.90124 | 44.28346 | -0.0814 | 6.21492 |
Maximum of Months | 514.00000 | 24.56261 | 47.64089 | 0.75467 | 17.79462 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.89354 | 50.00031 | 0.14403 | 7.09172 |
February | 454.00000 | 23.31306 | 49.67402 | 0.26068 | 8.36221 |
March | 514.00000 | 23.55699 | 49.73563 | 0.33505 | 9.18727 |
April | 485.00000 | 24.11899 | 50.53198 | 0.50398 | 10.73620 |
May | 508.00000 | 24.38642 | 51.26332 | -0.2221 | 7.01005 |
June | 496.00000 | 24.40400 | 50.24896 | -0.1921 | 6.75286 |
July | 497.00000 | 24.49026 | 49.29815 | -0.1668 | 6.70875 |
August | 514.00000 | 24.34589 | 50.60943 | -0.2304 | 6.99846 |
September | 485.00000 | 24.40507 | 50.26534 | -0.2229 | 6.97089 |
October | 502.00000 | 24.35649 | 51.34903 | 0.57855 | 12.58636 |
November | 489.00000 | 23.94875 | 51.61359 | 0.45390 | 10.28685 |
December | 497.00000 | 23.14195 | 52.63661 | 0.22956 | 7.93184 |
Annual Sum or Average | 5943.00000 | 23.95032 | 50.60732 | 0.12051 | 8.37951 |
Minimum of Months | 454.00000 | 22.89354 | 49.29815 | -0.2304 | 6.70875 |
Maximum of Months | 514.00000 | 24.49026 | 52.63661 | 0.57855 | 12.58636 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 427.00000 | 23.22362 | 47.89581 | 0.25391 | 8.43246 |
February | 385.00000 | 23.53757 | 48.11445 | 0.35228 | 9.39693 |
March | 433.00000 | 23.82464 | 48.23937 | 0.44376 | 10.68531 |
April | 410.00000 | 24.27862 | 49.17604 | 0.59323 | 13.54682 |
May | 430.00000 | 24.44450 | 50.43579 | -0.1484 | 7.09371 |
June | 418.00000 | 24.50008 | 49.48726 | -0.1157 | 6.90730 |
July | 422.00000 | 24.64353 | 48.20702 | -0.0651 | 7.42181 |
August | 433.00000 | 24.41104 | 49.76228 | -0.1610 | 7.21149 |
September | 410.00000 | 24.53979 | 49.08153 | -0.1239 | 7.22279 |
October | 427.00000 | 24.45209 | 50.22681 | 0.63950 | 14.62647 |
November | 417.00000 | 24.03174 | 50.40663 | 0.50475 | 11.47311 |
December | 422.00000 | 23.14759 | 51.68653 | 0.25916 | 8.65916 |
Annual Sum or Average | 5034.00000 | 24.08867 | 49.40215 | 0.20107 | 9.38356 |
Minimum of Months | 385.00000 | 23.14759 | 47.89581 | -0.1610 | 6.90730 |
Maximum of Months | 433.00000 | 24.64353 | 51.68653 | 0.63950 | 14.62647 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.16329 | 45.39252 | 0.52522 | 12.85339 |
February | 454.00000 | 24.20590 | 46.24831 | 0.54742 | 13.12998 |
March | 514.00000 | 24.09827 | 47.48478 | 0.51711 | 12.00339 |
April | 485.00000 | 24.28155 | 49.64974 | 0.56775 | 12.36812 |
May | 508.00000 | 24.37357 | 51.35296 | -0.2277 | 7.06159 |
June | 496.00000 | 24.36362 | 50.55217 | -0.2196 | 6.85509 |
July | 497.00000 | 24.45672 | 49.48856 | -0.1856 | 6.75696 |
August | 514.00000 | 24.37475 | 50.31328 | -0.2010 | 6.90033 |
September | 485.00000 | 24.53262 | 49.22769 | -0.1218 | 6.96613 |
October | 502.00000 | 24.66971 | 49.22502 | 0.72517 | 17.25949 |
November | 489.00000 | 24.55531 | 48.56228 | 0.67817 | 16.09392 |
December | 497.00000 | 24.19328 | 48.23573 | 0.55895 | 13.83318 |
Annual Sum or Average | 5943.00000 | 24.35578 | 48.82982 | 0.26040 | 10.98131 |
Minimum of Months | 454.00000 | 24.09827 | 45.39252 | -0.2277 | 6.75696 |
Maximum of Months | 514.00000 | 24.66971 | 51.35296 | 0.72517 | 17.25949 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.02125 | 48.51341 | 0.22042 | 7.79964 |
February | 454.00000 | 23.51875 | 47.99654 | 0.36403 | 10.04732 |
March | 514.00000 | 23.82574 | 47.75579 | 0.46519 | 11.66664 |
April | 485.00000 | 24.30477 | 48.91136 | 0.62362 | 14.19492 |
May | 508.00000 | 24.41214 | 50.03413 | -0.1321 | 7.01094 |
June | 496.00000 | 24.40138 | 49.49943 | -0.1365 | 6.72993 |
July | 497.00000 | 24.50730 | 48.40935 | -0.0866 | 6.77237 |
August | 514.00000 | 24.40011 | 49.35967 | -0.1265 | 6.81300 |
September | 485.00000 | 24.43667 | 49.12708 | -0.1436 | 7.11526 |
October | 502.00000 | 24.42475 | 49.83277 | 0.64944 | 14.86453 |
November | 489.00000 | 24.01044 | 50.19796 | 0.51739 | 11.88394 |
December | 497.00000 | 23.35018 | 50.61601 | 0.32922 | 9.61612 |
Annual Sum or Average | 5943.00000 | 24.05415 | 49.19362 | 0.20993 | 9.52865 |
Minimum of Months | 454.00000 | 23.02125 | 47.75579 | -0.1436 | 6.72993 |
Maximum of Months | 514.00000 | 24.50730 | 50.61601 | 0.64944 | 14.86453 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.57247 | 51.14675 | 0.06271 | 7.34787 |
February | 454.00000 | 23.10661 | 50.33553 | 0.21105 | 8.60636 |
March | 514.00000 | 23.42492 | 50.27540 | 0.30670 | 9.39214 |
April | 485.00000 | 24.05845 | 50.91631 | 0.49890 | 10.85530 |
May | 508.00000 | 24.39389 | 51.61880 | -0.2009 | 7.06513 |
June | 496.00000 | 24.42185 | 50.47703 | -0.1668 | 6.76914 |
July | 497.00000 | 24.52154 | 49.46208 | -0.1337 | 6.85936 |
August | 514.00000 | 24.34913 | 50.92090 | -0.2110 | 7.07319 |
September | 485.00000 | 24.41556 | 50.61676 | -0.2023 | 7.08554 |
October | 502.00000 | 24.32332 | 51.95176 | 0.57981 | 12.76228 |
November | 489.00000 | 23.78621 | 52.55817 | 0.41994 | 10.20481 |
December | 497.00000 | 22.86290 | 53.79250 | 0.16085 | 8.06144 |
Annual Sum or Average | 5943.00000 | 23.85743 | 51.17679 | 0.10861 | 8.50066 |
Minimum of Months | 454.00000 | 22.57247 | 49.46208 | -0.2110 | 6.76914 |
Maximum of Months | 514.00000 | 24.52154 | 53.79250 | 0.57981 | 12.76228 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.05045 | 48.85506 | 0.21355 | 8.39531 |
February | 454.00000 | 23.41782 | 48.51472 | 0.33137 | 9.49395 |
March | 514.00000 | 23.76187 | 48.34981 | 0.44110 | 10.80884 |
April | 485.00000 | 24.18720 | 49.39823 | 0.59566 | 13.64147 |
May | 508.00000 | 24.37984 | 50.55001 | -0.1297 | 7.02273 |
June | 496.00000 | 24.42820 | 49.59802 | -0.0977 | 6.76156 |
July | 497.00000 | 24.55542 | 48.41317 | -0.0479 | 7.34764 |
August | 514.00000 | 24.33705 | 49.97169 | -0.1453 | 7.16755 |
September | 485.00000 | 24.45538 | 49.30945 | -0.1119 | 7.15373 |
October | 502.00000 | 24.36231 | 50.53697 | 0.64087 | 14.67483 |
November | 489.00000 | 23.89241 | 51.12691 | 0.48529 | 11.31847 |
December | 497.00000 | 22.96558 | 52.44030 | 0.21760 | 8.63629 |
Annual Sum or Average | 5943.00000 | 23.98621 | 49.76211 | 0.19743 | 9.35841 |
Minimum of Months | 454.00000 | 22.96558 | 48.34981 | -0.1453 | 6.76156 |
Maximum of Months | 514.00000 | 24.55542 | 52.44030 | 0.64087 | 14.67483 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.87558 | 46.46929 | 0.45043 | 12.00569 |
February | 454.00000 | 23.99822 | 46.94893 | 0.49677 | 12.63915 |
March | 514.00000 | 23.96429 | 48.08269 | 0.48796 | 11.92132 |
April | 485.00000 | 24.21844 | 50.07067 | 0.56184 | 12.44942 |
May | 508.00000 | 24.37782 | 51.72972 | -0.2076 | 7.14427 |
June | 496.00000 | 24.38485 | 50.78827 | -0.1930 | 6.85304 |
July | 497.00000 | 24.49087 | 49.65938 | -0.1515 | 6.89519 |
August | 514.00000 | 24.37351 | 50.64349 | -0.1834 | 7.00125 |
September | 485.00000 | 24.52495 | 49.61389 | -0.1074 | 7.13812 |
October | 502.00000 | 24.60965 | 49.87929 | 0.71979 | 17.16848 |
November | 489.00000 | 24.40077 | 49.44138 | 0.64450 | 15.46495 |
December | 497.00000 | 23.94371 | 49.34933 | 0.49589 | 13.12288 |
Annual Sum or Average | 5943.00000 | 24.26447 | 49.40735 | 0.24820 | 10.79413 |
Minimum of Months | 454.00000 | 23.87558 | 46.46929 | -0.2076 | 6.85304 |
Maximum of Months | 514.00000 | 24.60965 | 51.72972 | 0.71979 | 17.16848 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.71710 | 49.54774 | 0.14624 | 7.76533 |
February | 454.00000 | 23.28660 | 48.68028 | 0.31134 | 9.93128 |
March | 514.00000 | 23.65993 | 48.34505 | 0.43079 | 11.58471 |
April | 485.00000 | 24.19422 | 49.37004 | 0.60769 | 14.06065 |
May | 508.00000 | 24.36820 | 50.44917 | -0.1275 | 7.30177 |
June | 496.00000 | 24.37770 | 49.77292 | -0.1251 | 6.88175 |
July | 497.00000 | 24.49313 | 48.63690 | -0.0693 | 7.05296 |
August | 514.00000 | 24.36739 | 49.69861 | -0.1197 | 7.05214 |
September | 485.00000 | 24.39416 | 49.51269 | -0.1403 | 7.41992 |
October | 502.00000 | 24.34043 | 50.44890 | 0.63928 | 14.76470 |
November | 489.00000 | 23.82387 | 51.10328 | 0.47931 | 11.58097 |
December | 497.00000 | 23.06876 | 51.68985 | 0.26271 | 9.39411 |
Annual Sum or Average | 5943.00000 | 23.92814 | 49.77607 | 0.18945 | 9.55346 |
Minimum of Months | 454.00000 | 22.71710 | 48.34505 | -0.1403 | 6.88175 |
Maximum of Months | 514.00000 | 24.49313 | 51.68985 | 0.63928 | 14.76470 |
Report: ChillerReportMonthly
For: COOLSYS1 CHILLER1
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportCHILLER ELECTRICITY ENERGY [J] | CHILLER ELECTRICITY RATE {Maximum} [W] | CHILLER ELECTRICITY RATE {TIMESTAMP} | CHILLER ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | CHILLER EVAPORATOR COOLING ENERGY [J] | CHILLER EVAPORATOR COOLING RATE [] | CHILLER CONDENSER HEAT TRANSFER ENERGY [J] | CHILLER COP [W/W] | CHILLER COP {Maximum} [W/W] | CHILLER COP {TIMESTAMP} | CHILLER PART LOAD RATIO [] | CHILLER PART LOAD RATIO [] | |
January | 0.173485E+12 | 242682.81 | 06-JAN-13:50 | 464.47 | 0.116101E+13 | 0.00 | 0.133449E+13 | 3.83 | 7.56 | 04-JAN-06:04 | 0.00 | 0.00 |
February | 0.185583E+12 | 241829.61 | 10-FEB-14:40 | 424.83 | 0.128597E+13 | 0.00 | 0.147155E+13 | 4.07 | 7.57 | 28-FEB-16:00 | 0.00 | 0.00 |
March | 0.220555E+12 | 239765.65 | 13-MAR-11:10 | 542.96 | 0.151094E+13 | 0.00 | 0.173149E+13 | 4.56 | 7.57 | 29-MAR-05:04 | 0.00 | 0.00 |
April | 0.257832E+12 | 245795.95 | 13-APR-08:20 | 608.00 | 0.179355E+13 | 0.00 | 0.205139E+13 | 5.35 | 7.57 | 05-APR-05:04 | 0.00 | 0.00 |
May | 0.299857E+12 | 247901.50 | 31-MAY-04:10 | 583.01 | 0.206566E+13 | 0.00 | 0.236551E+13 | 5.15 | 7.57 | 08-MAY-04:13 | 0.00 | 0.00 |
June | 0.317124E+12 | 253330.73 | 08-JUN-17:40 | 627.44 | 0.212134E+13 | 0.00 | 0.243846E+13 | 5.52 | 7.42 | 17-JUN-03:03 | 0.00 | 0.00 |
July | 0.331857E+12 | 256818.25 | 29-JUL-10:30 | 677.75 | 0.219814E+13 | 0.00 | 0.253000E+13 | 5.67 | 7.50 | 07-JUL-04:13 | 0.00 | 0.00 |
August | 0.332770E+12 | 256606.96 | 03-AUG-12:00 | 691.16 | 0.220452E+13 | 0.00 | 0.253729E+13 | 5.73 | 7.37 | 14-AUG-04:14 | 0.00 | 0.00 |
September | 0.309191E+12 | 252504.56 | 11-SEP-07:30 | 595.12 | 0.207495E+13 | 0.00 | 0.238414E+13 | 5.30 | 7.50 | 05-SEP-04:13 | 0.00 | 0.00 |
October | 0.291905E+12 | 258446.94 | 04-OCT-07:10 | 595.39 | 0.198927E+13 | 0.00 | 0.228117E+13 | 5.12 | 7.56 | 19-OCT-04:14 | 0.00 | 0.00 |
November | 0.241476E+12 | 248532.47 | 30-NOV-11:20 | 532.24 | 0.165975E+13 | 0.00 | 0.190123E+13 | 4.71 | 7.57 | 06-NOV-05:13 | 0.00 | 0.00 |
December | 0.193765E+12 | 239037.88 | 07-DEC-14:20 | 532.71 | 0.129752E+13 | 0.00 | 0.149128E+13 | 4.31 | 7.56 | 26-DEC-06:05 | 0.00 | 0.00 |
Annual Sum or Average | 0.315540E+13 | 6875.08 | 0.213626E+14 | 0.00 | 0.245180E+14 | 4.95 | 0.00 | 0.00 | ||||
Minimum of Months | 0.173485E+12 | 239037.88 | 424.83 | 0.116101E+13 | 0.00 | 0.133449E+13 | 3.83 | 7.37 | 0.00 | 0.00 | ||
Maximum of Months | 0.332770E+12 | 258446.94 | 691.16 | 0.220452E+13 | 0.00 | 0.253729E+13 | 5.73 | 7.57 | 0.00 | 0.00 |
Report: ChillerReportMonthly
For: COOLSYS1 CHILLER2
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportCHILLER ELECTRICITY ENERGY [J] | CHILLER ELECTRICITY RATE {Maximum} [W] | CHILLER ELECTRICITY RATE {TIMESTAMP} | CHILLER ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | CHILLER EVAPORATOR COOLING ENERGY [J] | CHILLER EVAPORATOR COOLING RATE [] | CHILLER CONDENSER HEAT TRANSFER ENERGY [J] | CHILLER COP [W/W] | CHILLER COP {Maximum} [W/W] | CHILLER COP {TIMESTAMP} | CHILLER PART LOAD RATIO [] | CHILLER PART LOAD RATIO [] | |
January | 0.632974E+10 | 148725.77 | 14-JAN-06:08 | 14.15 | 0.443030E+11 | 0.00 | 0.506327E+11 | 0.13 | 7.25 | 12-JAN-16:50 | 0.00 | 0.00 |
February | 0.566931E+10 | 162211.28 | 13-FEB-05:16 | 12.56 | 0.398274E+11 | 0.00 | 0.454967E+11 | 0.13 | 7.37 | 13-FEB-05:16 | 0.00 | 0.00 |
March | 0.210922E+11 | 197647.01 | 06-MAR-06:06 | 46.18 | 0.147004E+12 | 0.00 | 0.168096E+12 | 0.43 | 7.24 | 07-MAR-16:10 | 0.00 | 0.00 |
April | 0.217140E+11 | 179974.18 | 15-APR-05:03 | 47.48 | 0.149959E+12 | 0.00 | 0.171673E+12 | 0.45 | 7.35 | 15-APR-05:03 | 0.00 | 0.00 |
May | 0.559559E+11 | 237991.85 | 24-MAY-05:03 | 117.32 | 0.383078E+12 | 0.00 | 0.439034E+12 | 1.08 | 7.42 | 22-MAY-05:02 | 0.00 | 0.00 |
June | 0.778848E+11 | 221810.32 | 06-JUN-05:04 | 160.32 | 0.521576E+12 | 0.00 | 0.599460E+12 | 1.49 | 7.28 | 24-JUN-05:02 | 0.00 | 0.00 |
July | 0.805302E+11 | 202449.49 | 03-JUL-03:06 | 163.30 | 0.533445E+12 | 0.00 | 0.613975E+12 | 1.45 | 7.29 | 07-JUL-04:17 | 0.00 | 0.00 |
August | 0.879660E+11 | 208775.71 | 28-AUG-03:06 | 178.43 | 0.585326E+12 | 0.00 | 0.673292E+12 | 1.59 | 7.08 | 26-AUG-05:08 | 0.00 | 0.00 |
September | 0.794670E+11 | 240624.35 | 06-SEP-04:13 | 163.49 | 0.532114E+12 | 0.00 | 0.611581E+12 | 1.52 | 7.33 | 05-SEP-04:16 | 0.00 | 0.00 |
October | 0.607791E+11 | 213761.03 | 31-OCT-05:02 | 127.59 | 0.412025E+12 | 0.00 | 0.472804E+12 | 1.16 | 7.30 | 25-OCT-04:17 | 0.00 | 0.00 |
November | 0.391923E+11 | 178839.43 | 04-NOV-03:08 | 83.45 | 0.268901E+12 | 0.00 | 0.308093E+12 | 0.79 | 7.38 | 09-NOV-06:02 | 0.00 | 0.00 |
December | 0.903255E+10 | 193029.47 | 09-DEC-06:02 | 19.57 | 0.623425E+11 | 0.00 | 0.713751E+11 | 0.18 | 7.26 | 09-DEC-06:02 | 0.00 | 0.00 |
Annual Sum or Average | 0.545613E+12 | 1133.85 | 0.367990E+13 | 0.00 | 0.422551E+13 | 0.87 | 0.00 | 0.00 | ||||
Minimum of Months | 0.566931E+10 | 148725.77 | 12.56 | 0.398274E+11 | 0.00 | 0.454967E+11 | 0.13 | 7.08 | 0.00 | 0.00 | ||
Maximum of Months | 0.879660E+11 | 240624.35 | 178.43 | 0.585326E+12 | 0.00 | 0.673292E+12 | 1.59 | 7.42 | 0.00 | 0.00 |
Report: TowerReportMonthly
For: CENTRAL TOWER
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportCOOLING TOWER FAN ELECTRICITY ENERGY [J] | COOLING TOWER FAN ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | COOLING TOWER FAN ELECTRICITY RATE {Maximum} [W] | COOLING TOWER FAN ELECTRICITY RATE {TIMESTAMP} | COOLING TOWER HEAT TRANSFER RATE {Maximum} [W] | COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} | COOLING TOWER INLET TEMPERATURE [C] | COOLING TOWER OUTLET TEMPERATURE [C] | COOLING TOWER MASS FLOW RATE [kg/s] | |
January | 0.113003E+12 | 744.00 | 49248.27 | 01-JAN-00:05 | 244609.28 | 02-JAN-15:10 | 25.76 | 21.89 | 14.34 |
February | 0.113327E+12 | 672.00 | 49248.27 | 01-FEB-00:10 | 390997.08 | 02-FEB-15:10 | 31.26 | 24.38 | 14.34 |
March | 0.129353E+12 | 744.00 | 49248.27 | 01-MAR-00:10 | 641082.66 | 31-MAR-24:00 | 36.13 | 26.26 | 14.34 |
April | 0.127652E+12 | 720.00 | 49248.27 | 01-APR-00:02 | 699307.15 | 14-APR-15:50 | 43.04 | 30.08 | 14.34 |
May | 0.131907E+12 | 744.00 | 49248.27 | 01-MAY-00:05 | 378582.55 | 31-MAY-23:17 | 32.85 | 28.42 | 14.34 |
June | 0.127652E+12 | 720.00 | 49248.27 | 01-JUN-00:02 | 524558.40 | 30-JUN-23:12 | 38.71 | 31.15 | 14.34 |
July | 0.131907E+12 | 744.00 | 49248.27 | 01-JUL-00:03 | 679977.10 | 31-JUL-24:00 | 43.61 | 33.01 | 14.34 |
August | 0.131907E+12 | 744.00 | 49248.27 | 01-AUG-00:05 | 716579.80 | 23-AUG-16:20 | 47.59 | 34.20 | 14.34 |
September | 0.127652E+12 | 720.00 | 49248.27 | 01-SEP-00:03 | 372631.02 | 30-SEP-23:12 | 34.13 | 29.57 | 14.34 |
October | 0.131907E+12 | 744.00 | 49248.27 | 01-OCT-00:03 | 504750.78 | 31-OCT-23:30 | 37.20 | 29.75 | 14.34 |
November | 0.126831E+12 | 720.00 | 49248.27 | 01-NOV-00:10 | 557543.96 | 03-NOV-14:10 | 38.40 | 28.28 | 14.34 |
December | 0.129842E+12 | 744.00 | 49248.27 | 01-DEC-00:10 | 693282.99 | 08-DEC-16:50 | 38.87 | 26.26 | 14.34 |
Annual Sum or Average | 0.152294E+13 | 8760.00 | 37.33 | 28.62 | 14.34 | ||||
Minimum of Months | 0.113003E+12 | 672.00 | 49248.27 | 244609.28 | 25.76 | 21.89 | 14.34 | ||
Maximum of Months | 0.131907E+12 | 744.00 | 49248.27 | 716579.80 | 47.59 | 34.20 | 14.34 |
Report: TowerReportMonthly
For: TOWERWATERSYS COOLTOWER 1
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportCOOLING TOWER FAN ELECTRICITY ENERGY [J] | COOLING TOWER FAN ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | COOLING TOWER FAN ELECTRICITY RATE {Maximum} [W] | COOLING TOWER FAN ELECTRICITY RATE {TIMESTAMP} | COOLING TOWER HEAT TRANSFER RATE {Maximum} [W] | COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} | COOLING TOWER INLET TEMPERATURE [C] | COOLING TOWER OUTLET TEMPERATURE [C] | COOLING TOWER MASS FLOW RATE [kg/s] | |
January | 0.161628E+11 | 412.83 | 24398.16 | 01-JAN-08:23 | 1737946.14 | 12-JAN-15:20 | 23.74 | 22.28 | 48.12 |
February | 0.180947E+11 | 386.65 | 24398.16 | 01-FEB-10:30 | 1861047.82 | 15-FEB-15:20 | 24.06 | 22.29 | 47.25 |
March | 0.269320E+11 | 505.16 | 24398.16 | 03-MAR-08:30 | 1919753.24 | 31-MAR-14:10 | 24.04 | 22.17 | 55.90 |
April | 0.358335E+11 | 587.40 | 24398.16 | 01-APR-01:22 | 1852739.26 | 27-APR-16:00 | 24.71 | 22.42 | 64.44 |
May | 0.499254E+11 | 580.91 | 24398.16 | 01-MAY-04:14 | 1648702.60 | 24-MAY-05:03 | 26.96 | 24.44 | 53.10 |
June | 0.551104E+11 | 627.44 | 24398.16 | 01-JUN-00:02 | 1469169.80 | 06-JUN-05:04 | 28.31 | 25.62 | 55.35 |
July | 0.591121E+11 | 677.75 | 24398.16 | 01-JUL-00:08 | 1503840.62 | 14-JUL-17:40 | 28.45 | 25.73 | 58.43 |
August | 0.607067E+11 | 691.16 | 24398.16 | 01-AUG-00:05 | 1408282.48 | 10-AUG-05:03 | 28.49 | 25.76 | 59.63 |
September | 0.522713E+11 | 595.12 | 24398.16 | 01-SEP-00:03 | 1646207.87 | 26-SEP-04:15 | 28.37 | 25.73 | 52.19 |
October | 0.496961E+11 | 593.96 | 24398.16 | 01-OCT-00:03 | 1816224.69 | 17-OCT-10:40 | 27.01 | 24.57 | 54.97 |
November | 0.363564E+11 | 509.68 | 24398.16 | 01-NOV-04:12 | 2032239.01 | 01-NOV-04:12 | 25.45 | 23.34 | 52.89 |
December | 0.232126E+11 | 488.13 | 24398.16 | 01-DEC-00:12 | 1892099.89 | 11-DEC-15:20 | 23.77 | 22.14 | 53.90 |
Annual Sum or Average | 0.483414E+12 | 6656.17 | 26.12 | 23.88 | 54.73 | ||||
Minimum of Months | 0.161628E+11 | 386.65 | 24398.16 | 1408282.48 | 23.74 | 22.14 | 47.25 | ||
Maximum of Months | 0.607067E+11 | 691.16 | 24398.16 | 2032239.01 | 28.49 | 25.76 | 64.44 |
Report: TowerReportMonthly
For: TOWERWATERSYS COOLTOWER 2
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportCOOLING TOWER FAN ELECTRICITY ENERGY [J] | COOLING TOWER FAN ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | COOLING TOWER FAN ELECTRICITY RATE {Maximum} [W] | COOLING TOWER FAN ELECTRICITY RATE {TIMESTAMP} | COOLING TOWER HEAT TRANSFER RATE {Maximum} [W] | COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} | COOLING TOWER INLET TEMPERATURE [C] | COOLING TOWER OUTLET TEMPERATURE [C] | COOLING TOWER MASS FLOW RATE [kg/s] | |
January | 0.441363E+10 | 50.25 | 24398.16 | 02-JAN-09:20 | 1403297.41 | 07-JAN-05:14 | 23.74 | 23.45 | 3.62 |
February | 0.569321E+10 | 64.82 | 24398.16 | 02-FEB-06:06 | 1243554.98 | 14-FEB-15:30 | 24.06 | 23.63 | 4.80 |
March | 0.930424E+10 | 105.93 | 24398.16 | 03-MAR-11:40 | 1366800.78 | 31-MAR-15:00 | 24.04 | 23.47 | 8.57 |
April | 0.124667E+11 | 141.94 | 24398.16 | 01-APR-13:50 | 1311143.63 | 10-APR-15:20 | 24.71 | 23.91 | 11.15 |
May | 0.301256E+11 | 342.99 | 24398.16 | 01-MAY-07:30 | 1648702.60 | 24-MAY-05:03 | 26.96 | 25.21 | 26.30 |
June | 0.414076E+11 | 471.43 | 24398.16 | 01-JUN-00:02 | 1469169.80 | 06-JUN-05:04 | 28.31 | 25.91 | 37.33 |
July | 0.423516E+11 | 482.18 | 24398.16 | 01-JUL-03:06 | 1481334.23 | 03-JUL-05:03 | 28.45 | 26.08 | 36.57 |
August | 0.444367E+11 | 505.92 | 24398.16 | 01-AUG-00:05 | 1408282.48 | 10-AUG-05:03 | 28.49 | 26.01 | 38.92 |
September | 0.407851E+11 | 464.35 | 24398.16 | 01-SEP-00:03 | 1646207.87 | 26-SEP-04:15 | 28.37 | 26.00 | 37.09 |
October | 0.301520E+11 | 343.29 | 24398.16 | 01-OCT-00:33 | 1522436.33 | 31-OCT-05:04 | 27.01 | 25.29 | 26.79 |
November | 0.188446E+11 | 214.55 | 24398.16 | 01-NOV-04:12 | 2032239.01 | 01-NOV-04:12 | 25.45 | 24.32 | 17.52 |
December | 0.789639E+10 | 89.90 | 24398.16 | 01-DEC-13:40 | 1232604.18 | 06-DEC-08:15 | 23.77 | 23.28 | 6.20 |
Annual Sum or Average | 0.287878E+12 | 3277.54 | 26.12 | 24.72 | 21.32 | ||||
Minimum of Months | 0.441363E+10 | 50.25 | 24398.16 | 1232604.18 | 23.74 | 23.28 | 3.62 | ||
Maximum of Months | 0.444367E+11 | 505.92 | 24398.16 | 2032239.01 | 28.49 | 26.08 | 38.92 |
Report: BoilerReportMonthly
For: HEATSYS1 BOILER
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportBOILER HEATING ENERGY [J] | BOILER GAS CONSUMPTION [] | BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] | BOILER HEATING RATE {Maximum} [W] | BOILER HEATING RATE {TIMESTAMP} | BOILER GAS CONSUMPTION RATE [] | BOILER INLET TEMPERATURE [C] | BOILER OUTLET TEMPERATURE [C] | BOILER MASS FLOW RATE [kg/s] | BOILER ANCILLARY ELECTRICITY RATE [W] | BOILER PART LOAD RATIO [] | BOILER PART LOAD RATIO {Maximum} [] | BOILER PART LOAD RATIO {TIMESTAMP} | |
January | 0.324353E+10 | 0.00 | 71.03 | 554039.54 | 25-JAN-06:03 | 0.00 | 38.09 | 43.58 | 0.01 | 0.00 | 0.00 | 0.37 | 25-JAN-06:03 |
February | 0.376807E+10 | 0.00 | 38.31 | 944505.66 | 04-FEB-05:11 | 0.00 | 17.90 | 21.44 | 0.01 | 0.00 | 0.00 | 0.63 | 04-FEB-05:11 |
March | 0.190593E+10 | 0.00 | 36.36 | 524303.31 | 16-MAR-05:03 | 0.00 | 18.37 | 21.42 | 0.00 | 0.00 | 0.00 | 0.35 | 16-MAR-05:03 |
April | 167289.28 | 0.00 | 0.50 | 183.43 | 19-APR-06:00 | 0.00 | 18.86 | 18.90 | 0.00 | 0.00 | 0.00 | 0.00 | 19-APR-06:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 18.85 | 18.85 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:05 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUN-00:02 | 0.00 | 18.85 | 18.85 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUN-00:02 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 18.85 | 18.85 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUL-00:03 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 18.85 | 18.85 | 0.00 | 0.00 | 0.00 | 0.00 | 01-AUG-00:05 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 18.85 | 18.85 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:03 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 18.85 | 18.85 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:03 |
November | 0.530454E+09 | 0.00 | 8.11 | 144269.74 | 13-NOV-06:02 | 0.00 | 19.61 | 20.30 | 0.00 | 0.00 | 0.00 | 0.10 | 13-NOV-06:02 |
December | 0.406462E+10 | 0.00 | 66.84 | 650634.63 | 15-DEC-06:02 | 0.00 | 20.11 | 25.62 | 0.01 | 0.00 | 0.00 | 0.43 | 15-DEC-06:02 |
Annual Sum or Average | 0.135128E+11 | 0.00 | 221.16 | 0.00 | 20.54 | 22.07 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.90 | 18.85 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.406462E+10 | 0.00 | 71.03 | 944505.66 | 0.00 | 38.09 | 43.58 | 0.01 | 0.00 | 0.00 | 0.63 |
Report: BoilerReportMonthly
For: CENTRAL BOILER
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportBOILER HEATING ENERGY [J] | BOILER GAS CONSUMPTION [] | BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] | BOILER HEATING RATE {Maximum} [W] | BOILER HEATING RATE {TIMESTAMP} | BOILER GAS CONSUMPTION RATE [] | BOILER INLET TEMPERATURE [C] | BOILER OUTLET TEMPERATURE [C] | BOILER MASS FLOW RATE [kg/s] | BOILER ANCILLARY ELECTRICITY RATE [W] | BOILER PART LOAD RATIO [] | BOILER PART LOAD RATIO [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 25.76 | 25.76 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 31.26 | 31.26 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 36.13 | 36.13 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:02 | 0.00 | 43.04 | 43.04 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 32.85 | 32.85 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUN-00:02 | 0.00 | 38.71 | 38.71 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 43.61 | 43.61 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 47.59 | 47.59 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 34.13 | 34.13 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 37.20 | 37.20 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 38.40 | 38.40 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 38.87 | 38.87 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 37.33 | 37.33 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.76 | 25.76 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47.59 | 47.59 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: VAV_BOT WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.103057E+12 | 0.00 | 434.42 | 0.767359E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 241912.22 | 07-JAN-06:02 | 155774.36 | 30-JAN-05:12 | 0.00 | 0.00 | 0.00 |
February | 0.114866E+12 | 0.00 | 406.61 | 0.862004E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 252536.30 | 17-FEB-05:11 | 160162.16 | 18-FEB-05:11 | 0.00 | 0.00 | 0.00 |
March | 0.157143E+12 | 0.00 | 527.78 | 0.111667E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 221732.08 | 06-MAR-06:02 | 152154.89 | 07-MAR-05:11 | 0.00 | 0.00 | 0.00 |
April | 0.188351E+12 | 0.00 | 585.24 | 0.133487E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 204683.79 | 29-APR-05:02 | 147264.74 | 29-APR-05:02 | 0.00 | 0.00 | 0.00 |
May | 0.203682E+12 | 0.00 | 545.73 | 0.136977E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 280113.08 | 27-MAY-03:02 | 167538.26 | 30-MAY-05:03 | 0.00 | 0.00 | 0.00 |
June | 0.229803E+12 | 0.00 | 586.38 | 0.151900E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 257703.84 | 22-JUN-05:03 | 169643.94 | 05-JUN-05:03 | 0.00 | 0.00 | 0.00 |
July | 0.248806E+12 | 0.00 | 630.13 | 0.164825E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 232474.94 | 05-JUL-05:03 | 170148.22 | 14-JUL-05:02 | 0.00 | 0.00 | 0.00 |
August | 0.264772E+12 | 0.00 | 651.47 | 0.175992E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 246334.87 | 21-AUG-05:03 | 181250.81 | 21-AUG-05:03 | 0.00 | 0.00 | 0.00 |
September | 0.218780E+12 | 0.00 | 545.74 | 0.141572E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 252578.13 | 25-SEP-05:02 | 171692.71 | 19-SEP-05:03 | 0.00 | 0.00 | 0.00 |
October | 0.213335E+12 | 0.00 | 557.03 | 0.142294E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 250915.59 | 07-OCT-05:03 | 167355.17 | 03-OCT-05:03 | 0.00 | 0.00 | 0.00 |
November | 0.179437E+12 | 0.00 | 504.89 | 0.121853E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 232125.28 | 03-NOV-05:02 | 163808.74 | 20-NOV-06:02 | 0.00 | 0.00 | 0.00 |
December | 0.142038E+12 | 0.00 | 507.96 | 0.982195E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 241236.47 | 09-DEC-06:02 | 161975.68 | 09-DEC-06:02 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.226407E+13 | 0.00 | 6483.37 | 0.154172E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.103057E+12 | 0.00 | 406.61 | 0.767359E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 204683.79 | 147264.74 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.264772E+12 | 0.00 | 651.47 | 0.175992E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 280113.08 | 181250.81 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: VAV_MID WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.851841E+12 | 0.00 | 416.08 | 0.613380E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 2265835.08 | 14-JAN-06:03 | 1318272.13 | 14-JAN-06:03 | 0.00 | 0.00 | 0.00 |
February | 0.925583E+12 | 0.00 | 382.83 | 0.672573E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 2197607.77 | 02-FEB-06:02 | 1339389.52 | 18-FEB-06:03 | 0.00 | 0.00 | 0.00 |
March | 0.115938E+13 | 0.00 | 446.96 | 0.822038E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 2511423.65 | 06-MAR-05:12 | 1450370.14 | 29-MAR-05:02 | 0.00 | 0.00 | 0.00 |
April | 0.136184E+13 | 0.00 | 453.06 | 0.966134E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 2290829.39 | 25-APR-04:12 | 1453473.38 | 15-APR-04:12 | 0.00 | 0.00 | 0.00 |
May | 0.177990E+13 | 0.00 | 497.31 | 0.118850E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 2737993.20 | 27-MAY-04:02 | 1542666.96 | 24-MAY-05:03 | 0.00 | 0.00 | 0.00 |
June | 0.194752E+13 | 0.00 | 513.72 | 0.126781E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 2679608.50 | 22-JUN-05:03 | 1598029.98 | 02-JUN-03:02 | 0.00 | 0.00 | 0.00 |
July | 0.200966E+13 | 0.00 | 533.39 | 0.131269E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 2612954.09 | 03-JUL-03:02 | 1597402.97 | 14-JUL-03:02 | 0.00 | 0.00 | 0.00 |
August | 0.202869E+13 | 0.00 | 531.05 | 0.130845E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 2443424.97 | 28-AUG-03:02 | 1538943.93 | 07-AUG-05:02 | 0.00 | 0.00 | 0.00 |
September | 0.194079E+13 | 0.00 | 503.37 | 0.123304E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 2541612.10 | 20-SEP-03:02 | 1589263.55 | 29-SEP-03:02 | 0.00 | 0.00 | 0.00 |
October | 0.174324E+13 | 0.00 | 476.64 | 0.115719E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 2586583.56 | 31-OCT-05:02 | 1515039.44 | 19-OCT-04:11 | 0.00 | 0.00 | 0.00 |
November | 0.137180E+13 | 0.00 | 424.24 | 0.918690E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 2430527.12 | 04-NOV-03:02 | 1484055.49 | 29-NOV-06:03 | 0.00 | 0.00 | 0.00 |
December | 0.943657E+12 | 0.00 | 416.44 | 0.660792E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 2590196.06 | 09-DEC-06:02 | 1528722.24 | 09-DEC-06:02 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.180639E+14 | 0.00 | 5595.08 | 0.121213E+14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.851841E+12 | 0.00 | 382.83 | 0.613380E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 2197607.77 | 1318272.13 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.202869E+13 | 0.00 | 533.39 | 0.131269E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 2737993.20 | 1598029.98 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: VAV_TOP WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.826114E+11 | 0.00 | 409.26 | 0.593342E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 230893.82 | 07-JAN-06:02 | 124461.79 | 14-JAN-06:03 | 0.00 | 0.00 | 0.00 |
February | 0.946209E+11 | 0.00 | 373.47 | 0.688229E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 210453.09 | 18-FEB-06:03 | 123339.36 | 18-FEB-06:03 | 0.00 | 0.00 | 0.00 |
March | 0.121313E+12 | 0.00 | 440.73 | 0.856662E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 254188.10 | 06-MAR-05:12 | 136365.04 | 14-MAR-05:02 | 0.00 | 0.00 | 0.00 |
April | 0.146014E+12 | 0.00 | 448.93 | 0.104605E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 226343.37 | 25-APR-04:12 | 138731.98 | 24-APR-04:11 | 0.00 | 0.00 | 0.00 |
May | 0.191148E+12 | 0.00 | 495.32 | 0.131569E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 289128.25 | 27-MAY-04:02 | 158745.78 | 30-MAY-05:03 | 0.00 | 0.00 | 0.00 |
June | 0.210404E+12 | 0.00 | 515.74 | 0.140753E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 279339.85 | 22-JUN-05:03 | 169889.41 | 02-JUN-03:02 | 0.00 | 0.00 | 0.00 |
July | 0.218686E+12 | 0.00 | 535.46 | 0.147312E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 275993.92 | 03-JUL-03:02 | 172678.84 | 14-JUL-03:02 | 0.00 | 0.00 | 0.00 |
August | 0.217048E+12 | 0.00 | 530.40 | 0.144277E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 268365.47 | 10-AUG-05:03 | 156897.17 | 07-AUG-05:02 | 0.00 | 0.00 | 0.00 |
September | 0.205579E+12 | 0.00 | 504.14 | 0.134604E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 262470.00 | 20-SEP-03:02 | 170852.64 | 30-SEP-03:02 | 0.00 | 0.00 | 0.00 |
October | 0.179149E+12 | 0.00 | 473.37 | 0.121988E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 274620.40 | 31-OCT-05:02 | 159961.45 | 13-OCT-05:02 | 0.00 | 0.00 | 0.00 |
November | 0.138899E+12 | 0.00 | 418.49 | 0.941951E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 267967.67 | 04-NOV-03:02 | 148408.01 | 10-NOV-06:02 | 0.00 | 0.00 | 0.00 |
December | 0.937344E+11 | 0.00 | 415.44 | 0.651613E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 229057.86 | 26-DEC-05:12 | 142293.06 | 09-DEC-06:02 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.189920E+13 | 0.00 | 5560.73 | 0.129829E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.826114E+11 | 0.00 | 373.47 | 0.593342E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 210453.09 | 123339.36 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.218686E+12 | 0.00 | 535.46 | 0.147312E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 289128.25 | 172678.84 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: CAV_BAS COOLING COIL
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.798334E+11 | 0.00 | 423.59 | 0.730627E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 178340.03 | 30-JAN-05:23 | 104309.25 | 01-JAN-12:52 | 0.00 | 0.00 | 0.00 |
February | 0.770349E+11 | 0.00 | 378.33 | 0.696599E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 167398.03 | 02-FEB-05:12 | 114396.53 | 20-FEB-16:39 | 0.00 | 0.00 | 0.00 |
March | 0.892622E+11 | 0.00 | 436.18 | 0.793095E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 190167.97 | 06-MAR-05:23 | 103582.35 | 18-MAR-04:12 | 0.00 | 0.00 | 0.00 |
April | 0.900736E+11 | 0.00 | 404.18 | 0.783108E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 177868.78 | 16-APR-23:22 | 106188.11 | 20-APR-04:11 | 0.00 | 0.00 | 0.00 |
May | 0.114136E+12 | 0.00 | 446.08 | 0.897917E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 214542.07 | 29-MAY-13:06 | 102908.59 | 29-MAY-15:41 | 0.00 | 0.00 | 0.00 |
June | 0.127747E+12 | 0.00 | 444.19 | 0.918875E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 206064.21 | 26-JUN-03:02 | 99855.34 | 25-JUN-19:02 | 0.00 | 0.00 | 0.00 |
July | 0.132089E+12 | 0.00 | 442.58 | 0.942425E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 204674.87 | 31-JUL-03:13 | 108874.08 | 04-JUL-15:30 | 0.00 | 0.00 | 0.00 |
August | 0.145293E+12 | 0.00 | 479.84 | 0.103598E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 206792.12 | 13-AUG-15:20 | 103653.43 | 06-AUG-14:38 | 0.00 | 0.00 | 0.00 |
September | 0.127968E+12 | 0.00 | 449.94 | 0.925391E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 205716.93 | 10-SEP-18:38 | 104263.55 | 17-SEP-14:30 | 0.00 | 0.00 | 0.00 |
October | 0.122846E+12 | 0.00 | 459.84 | 0.939972E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 215765.13 | 30-OCT-03:02 | 105346.23 | 15-OCT-15:17 | 0.00 | 0.00 | 0.00 |
November | 0.107035E+12 | 0.00 | 429.51 | 0.859328E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 202051.78 | 05-NOV-14:28 | 104681.53 | 15-NOV-05:12 | 0.00 | 0.00 | 0.00 |
December | 0.853396E+11 | 0.00 | 433.20 | 0.762988E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 190678.03 | 10-DEC-12:51 | 106645.12 | 03-DEC-15:56 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.129866E+13 | 0.00 | 5227.46 | 0.102863E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.770349E+11 | 0.00 | 378.33 | 0.696599E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 167398.03 | 99855.34 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.145293E+12 | 0.00 | 479.84 | 0.103598E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 215765.13 | 114396.53 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: AIRLOOP DATACENTER BASEMENT COOLING COIL
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.340157E+12 | 0.937524E+11 | 744.00 | 0.330546E+12 | 0.961073E+10 | 0.00 | 0.39 | 02-JAN-15:00 | 0.31 | 23-JAN-05:00 | 140394.43 | 02-JAN-15:00 | 130674.34 | 02-JAN-15:00 | 10240.55 | 06-JAN-17:00 | 49044.63 | 02-JAN-15:00 | 0.00 |
February | 0.530443E+12 | 0.150039E+12 | 672.00 | 0.520529E+12 | 0.991434E+10 | 0.00 | 0.61 | 02-FEB-14:00 | 0.52 | 01-FEB-00:10 | 231075.54 | 10-FEB-17:00 | 221312.91 | 22-FEB-16:00 | 11353.21 | 02-FEB-15:30 | 79448.16 | 11-FEB-14:00 | 0.00 |
March | 0.834877E+12 | 0.238828E+12 | 744.00 | 0.822125E+12 | 0.127521E+11 | 0.00 | 0.97 | 31-MAR-23:30 | 0.72 | 01-MAR-04:20 | 396647.92 | 31-MAR-24:00 | 393817.22 | 31-MAR-24:00 | 12538.70 | 13-MAR-10:00 | 116268.17 | 31-MAR-23:20 | 0.00 |
April | 0.104574E+13 | 0.317757E+12 | 720.00 | 0.103269E+13 | 0.130430E+11 | 0.00 | 1.00 | 01-APR-13:10 | 0.37 | 30-APR-23:53 | 425402.70 | 25-APR-16:00 | 407141.49 | 25-APR-16:00 | 18261.21 | 25-APR-16:00 | 145712.47 | 17-APR-15:00 | 0.00 |
May | 0.360308E+12 | 0.118038E+12 | 744.00 | 0.338716E+12 | 0.215913E+11 | 0.00 | 0.59 | 31-MAY-23:03 | 0.34 | 07-MAY-05:00 | 229271.31 | 31-MAY-23:03 | 212541.04 | 31-MAY-24:00 | 17212.48 | 31-MAY-23:03 | 73890.32 | 31-MAY-23:13 | 0.00 |
June | 0.592182E+12 | 0.198689E+12 | 720.00 | 0.565497E+12 | 0.266848E+11 | 0.00 | 0.80 | 30-JUN-23:12 | 0.58 | 01-JUN-06:00 | 316724.06 | 30-JUN-23:03 | 304204.07 | 30-JUN-23:53 | 16213.36 | 23-JUN-14:00 | 103517.43 | 30-JUN-23:12 | 0.00 |
July | 0.858013E+12 | 0.290949E+12 | 744.00 | 0.830811E+12 | 0.272026E+11 | 0.00 | 1.00 | 31-JUL-23:03 | 0.78 | 04-JUL-04:40 | 402259.48 | 31-JUL-24:00 | 392007.36 | 31-JUL-24:00 | 16557.68 | 25-JUL-15:00 | 136188.76 | 31-JUL-24:00 | 0.00 |
August | 0.109298E+13 | 0.360792E+12 | 744.00 | 0.106733E+13 | 0.256534E+11 | 0.00 | 1.00 | 01-AUG-00:05 | 0.42 | 31-AUG-23:17 | 425831.11 | 23-AUG-17:00 | 407321.10 | 23-AUG-17:00 | 18510.01 | 23-AUG-17:00 | 150599.23 | 23-AUG-13:00 | 0.00 |
September | 0.356542E+12 | 0.119969E+12 | 720.00 | 0.331317E+12 | 0.252252E+11 | 0.00 | 0.59 | 30-SEP-23:12 | 0.35 | 05-SEP-06:00 | 224750.41 | 30-SEP-23:03 | 213001.49 | 30-SEP-23:57 | 13651.51 | 07-SEP-14:00 | 75684.69 | 30-SEP-23:12 | 0.00 |
October | 0.608741E+12 | 0.197222E+12 | 744.00 | 0.584968E+12 | 0.237727E+11 | 0.00 | 0.78 | 31-OCT-23:10 | 0.57 | 16-OCT-01:00 | 313228.93 | 31-OCT-23:10 | 303056.80 | 31-OCT-24:00 | 15476.97 | 04-OCT-08:30 | 91497.76 | 31-OCT-23:20 | 0.00 |
November | 0.818361E+12 | 0.246553E+12 | 720.00 | 0.800352E+12 | 0.180096E+11 | 0.00 | 0.84 | 03-NOV-14:00 | 0.73 | 11-NOV-07:30 | 326897.81 | 30-NOV-17:00 | 314523.92 | 17-NOV-15:00 | 14024.90 | 29-NOV-11:00 | 114651.88 | 17-NOV-15:00 | 0.00 |
December | 0.107957E+13 | 0.297260E+12 | 744.00 | 0.106754E+13 | 0.120308E+11 | 0.00 | 1.00 | 01-DEC-09:20 | 0.91 | 16-DEC-04:00 | 413874.72 | 08-DEC-17:10 | 404691.34 | 11-DEC-16:20 | 11987.81 | 08-DEC-17:10 | 136982.51 | 10-DEC-15:00 | 0.00 |
Annual Sum or Average | 0.851791E+13 | 0.262985E+13 | 8760.00 | 0.829242E+13 | 0.225491E+12 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.340157E+12 | 0.937524E+11 | 672.00 | 0.330546E+12 | 0.961073E+10 | 0.00 | 0.39 | 0.31 | 140394.43 | 130674.34 | 10240.55 | 49044.63 | 0.00 | ||||||
Maximum of Months | 0.109298E+13 | 0.360792E+12 | 744.00 | 0.106754E+13 | 0.272026E+11 | 0.00 | 1.00 | 0.91 | 425831.11 | 407321.10 | 18510.01 | 150599.23 | 0.00 |
Report: DXReportMonthly
For: AIRLOOP DATACENTER BOT COOLING COIL
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.577985E+10 | 0.158096E+10 | 744.00 | 0.540323E+10 | 0.376614E+09 | 0.00 | 0.37 | 02-JAN-15:00 | 0.18 | 26-JAN-08:00 | 3009.79 | 02-JAN-15:00 | 2640.99 | 02-JAN-17:00 | 410.32 | 02-JAN-15:20 | 1006.47 | 02-JAN-15:00 | 0.00 |
February | 0.101074E+11 | 0.282012E+10 | 672.00 | 0.969739E+10 | 0.410009E+09 | 0.00 | 0.58 | 19-FEB-17:12 | 0.38 | 04-FEB-08:00 | 4956.49 | 19-FEB-17:23 | 4822.03 | 20-FEB-17:50 | 443.46 | 02-FEB-15:20 | 1566.52 | 02-FEB-14:00 | 0.00 |
March | 0.164577E+11 | 0.463512E+10 | 744.00 | 0.159034E+11 | 0.554314E+09 | 0.00 | 0.87 | 31-MAR-24:00 | 0.61 | 11-MAR-08:00 | 7836.51 | 31-MAR-23:05 | 7684.14 | 31-MAR-24:00 | 527.91 | 13-MAR-10:00 | 2319.88 | 13-MAR-16:00 | 0.00 |
April | 0.210775E+11 | 0.631793E+10 | 720.00 | 0.204599E+11 | 0.617658E+09 | 0.00 | 1.00 | 12-APR-15:50 | 0.30 | 30-APR-23:53 | 8893.44 | 13-APR-16:00 | 8479.83 | 09-APR-17:50 | 551.30 | 25-APR-15:30 | 3133.70 | 17-APR-15:00 | 0.00 |
May | 0.707565E+10 | 0.224273E+10 | 744.00 | 0.619899E+10 | 0.876661E+09 | 0.00 | 0.55 | 31-MAY-23:03 | 0.27 | 09-MAY-06:00 | 4798.65 | 31-MAY-23:03 | 4066.74 | 31-MAY-24:00 | 752.12 | 31-MAY-23:03 | 1474.06 | 31-MAY-23:13 | 0.00 |
June | 0.120593E+11 | 0.391807E+10 | 720.00 | 0.109164E+11 | 0.114290E+10 | 0.00 | 0.74 | 30-JUN-23:05 | 0.50 | 14-JUN-06:00 | 6490.05 | 30-JUN-23:03 | 5911.44 | 30-JUN-23:47 | 636.14 | 23-JUN-14:00 | 2049.56 | 30-JUN-23:12 | 0.00 |
July | 0.175933E+11 | 0.580287E+10 | 744.00 | 0.163862E+11 | 0.120707E+10 | 0.00 | 0.95 | 31-JUL-23:35 | 0.70 | 04-JUL-04:40 | 8457.32 | 31-JUL-23:03 | 7854.20 | 31-JUL-23:40 | 688.74 | 25-JUL-15:00 | 2797.30 | 31-JUL-23:25 | 0.00 |
August | 0.227726E+11 | 0.748039E+10 | 744.00 | 0.215299E+11 | 0.124270E+10 | 0.00 | 1.00 | 01-AUG-10:50 | 0.36 | 31-AUG-23:52 | 9038.20 | 21-AUG-13:00 | 8431.75 | 20-AUG-18:10 | 662.84 | 21-AUG-12:50 | 3241.43 | 23-AUG-13:00 | 0.00 |
September | 0.710388E+10 | 0.230253E+10 | 720.00 | 0.607154E+10 | 0.103234E+10 | 0.00 | 0.54 | 30-SEP-23:05 | 0.28 | 27-SEP-06:00 | 4557.11 | 30-SEP-23:03 | 4034.86 | 30-SEP-23:35 | 559.60 | 22-SEP-08:00 | 1475.49 | 30-SEP-23:12 | 0.00 |
October | 0.122284E+11 | 0.384932E+10 | 744.00 | 0.112170E+11 | 0.101145E+10 | 0.00 | 0.71 | 31-OCT-23:10 | 0.48 | 28-OCT-06:55 | 6304.64 | 31-OCT-23:10 | 5863.25 | 31-OCT-24:00 | 657.61 | 04-OCT-08:20 | 1825.91 | 03-OCT-15:00 | 0.00 |
November | 0.163215E+11 | 0.481807E+10 | 720.00 | 0.155313E+11 | 0.790194E+09 | 0.00 | 0.82 | 07-NOV-17:00 | 0.62 | 27-NOV-07:00 | 7113.10 | 07-NOV-17:00 | 6697.22 | 07-NOV-17:00 | 618.77 | 29-NOV-11:00 | 2338.84 | 17-NOV-15:00 | 0.00 |
December | 0.213617E+11 | 0.581142E+10 | 744.00 | 0.208009E+11 | 0.560852E+09 | 0.00 | 1.00 | 08-DEC-16:50 | 0.77 | 16-DEC-08:00 | 9030.43 | 08-DEC-17:00 | 8569.60 | 06-DEC-17:00 | 505.33 | 08-DEC-16:50 | 2857.98 | 10-DEC-14:51 | 0.00 |
Annual Sum or Average | 0.169939E+12 | 0.515795E+11 | 8760.00 | 0.160116E+12 | 0.982276E+10 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.577985E+10 | 0.158096E+10 | 672.00 | 0.540323E+10 | 0.376614E+09 | 0.00 | 0.37 | 0.18 | 3009.79 | 2640.99 | 410.32 | 1006.47 | 0.00 | ||||||
Maximum of Months | 0.227726E+11 | 0.748039E+10 | 744.00 | 0.215299E+11 | 0.124270E+10 | 0.00 | 1.00 | 0.77 | 9038.20 | 8569.60 | 752.12 | 3241.43 | 0.00 |
Report: DXReportMonthly
For: AIRLOOP DATACENTER MID COOLING COIL
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.469627E+11 | 0.130534E+11 | 744.00 | 0.433608E+11 | 0.360195E+10 | 0.00 | 0.36 | 02-JAN-15:00 | 0.12 | 26-JAN-07:00 | 28172.61 | 02-JAN-15:00 | 24546.05 | 02-JAN-17:00 | 4059.18 | 06-JAN-17:00 | 9423.41 | 02-JAN-15:00 | 0.00 |
February | 0.905764E+11 | 0.254800E+11 | 672.00 | 0.865296E+11 | 0.404674E+10 | 0.00 | 0.57 | 19-FEB-17:22 | 0.31 | 05-FEB-07:00 | 46440.11 | 10-FEB-17:00 | 44150.71 | 21-FEB-17:50 | 4399.41 | 02-FEB-15:20 | 14853.64 | 02-FEB-14:00 | 0.00 |
March | 0.153790E+12 | 0.434901E+11 | 744.00 | 0.148264E+12 | 0.552557E+10 | 0.00 | 0.88 | 31-MAR-24:00 | 0.56 | 20-MAR-06:55 | 75628.50 | 31-MAR-23:05 | 74197.60 | 31-MAR-24:00 | 5268.98 | 14-MAR-09:00 | 22015.13 | 13-MAR-16:00 | 0.00 |
April | 0.200571E+12 | 0.601605E+11 | 720.00 | 0.194389E+12 | 0.618287E+10 | 0.00 | 1.00 | 14-APR-14:00 | 0.29 | 30-APR-23:53 | 84825.00 | 13-APR-16:00 | 80146.67 | 12-APR-16:00 | 5481.56 | 25-APR-15:30 | 29762.92 | 17-APR-15:00 | 0.00 |
May | 0.663207E+11 | 0.210401E+11 | 744.00 | 0.576629E+11 | 0.865779E+10 | 0.00 | 0.56 | 31-MAY-23:03 | 0.25 | 01-MAY-06:00 | 46802.87 | 31-MAY-23:03 | 39146.40 | 31-MAY-24:00 | 7718.93 | 31-MAY-23:03 | 14299.63 | 31-MAY-23:13 | 0.00 |
June | 0.114946E+12 | 0.373289E+11 | 720.00 | 0.103568E+12 | 0.113771E+11 | 0.00 | 0.75 | 30-JUN-23:05 | 0.49 | 13-JUN-06:00 | 62898.67 | 30-JUN-23:03 | 57070.02 | 30-JUN-23:53 | 6314.09 | 23-JUN-14:00 | 19806.86 | 30-JUN-23:12 | 0.00 |
July | 0.167848E+12 | 0.553454E+11 | 744.00 | 0.155803E+12 | 0.120451E+11 | 0.00 | 0.96 | 31-JUL-23:53 | 0.69 | 14-JUL-21:20 | 81590.71 | 31-JUL-23:03 | 75597.66 | 31-JUL-23:55 | 6853.98 | 25-JUL-15:00 | 26936.07 | 31-JUL-23:53 | 0.00 |
August | 0.216094E+12 | 0.710614E+11 | 744.00 | 0.203669E+12 | 0.124255E+11 | 0.00 | 1.00 | 01-AUG-11:50 | 0.32 | 31-AUG-23:23 | 85762.22 | 08-AUG-15:00 | 79732.35 | 30-AUG-16:00 | 6640.74 | 22-AUG-15:00 | 30988.54 | 23-AUG-13:00 | 0.00 |
September | 0.663314E+11 | 0.215141E+11 | 720.00 | 0.561424E+11 | 0.101890E+11 | 0.00 | 0.53 | 30-SEP-23:05 | 0.26 | 16-SEP-07:00 | 43543.41 | 30-SEP-23:03 | 38282.04 | 30-SEP-23:45 | 5572.98 | 30-SEP-23:03 | 14054.33 | 30-SEP-23:12 | 0.00 |
October | 0.115966E+12 | 0.365144E+11 | 744.00 | 0.105906E+12 | 0.100601E+11 | 0.00 | 0.70 | 31-OCT-23:10 | 0.45 | 28-OCT-06:55 | 59698.63 | 31-OCT-23:10 | 55233.18 | 31-OCT-24:00 | 6572.54 | 04-OCT-08:20 | 17412.19 | 03-OCT-15:00 | 0.00 |
November | 0.153287E+12 | 0.453920E+11 | 720.00 | 0.145409E+12 | 0.787795E+10 | 0.00 | 0.81 | 07-NOV-17:00 | 0.56 | 27-NOV-08:00 | 67912.56 | 07-NOV-17:00 | 63761.19 | 07-NOV-17:00 | 6175.07 | 29-NOV-11:00 | 22250.07 | 03-NOV-14:00 | 0.00 |
December | 0.197998E+12 | 0.541774E+11 | 744.00 | 0.192392E+12 | 0.560589E+10 | 0.00 | 0.99 | 08-DEC-16:50 | 0.71 | 16-DEC-08:00 | 85929.10 | 08-DEC-17:00 | 81283.36 | 06-DEC-17:00 | 5047.58 | 08-DEC-16:50 | 26960.38 | 08-DEC-16:00 | 0.00 |
Annual Sum or Average | 0.159069E+13 | 0.484558E+12 | 8760.00 | 0.149310E+13 | 0.975956E+11 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.469627E+11 | 0.130534E+11 | 672.00 | 0.433608E+11 | 0.360195E+10 | 0.00 | 0.36 | 0.12 | 28172.61 | 24546.05 | 4059.18 | 9423.41 | 0.00 | ||||||
Maximum of Months | 0.216094E+12 | 0.710614E+11 | 744.00 | 0.203669E+12 | 0.124255E+11 | 0.00 | 1.00 | 0.71 | 85929.10 | 81283.36 | 7718.93 | 30988.54 | 0.00 |
Report: DXReportMonthly
For: AIRLOOP DATACENTER TOP COOLING COIL
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.416360E+10 | 0.117662E+10 | 743.21 | 0.381303E+10 | 0.350569E+09 | 0.00 | 0.36 | 02-JAN-15:00 | 0.00 | 22-JAN-07:20 | 2874.43 | 02-JAN-15:00 | 2506.47 | 02-JAN-17:00 | 408.51 | 02-JAN-15:20 | 961.62 | 02-JAN-15:00 | 0.00 |
February | 0.875792E+10 | 0.248185E+10 | 672.00 | 0.835548E+10 | 0.402444E+09 | 0.00 | 0.57 | 19-FEB-17:12 | 0.19 | 05-FEB-07:35 | 4720.78 | 19-FEB-17:22 | 4484.51 | 21-FEB-17:40 | 442.76 | 02-FEB-10:50 | 1510.51 | 02-FEB-14:00 | 0.00 |
March | 0.152186E+11 | 0.432443E+10 | 744.00 | 0.146674E+11 | 0.551185E+09 | 0.00 | 0.86 | 31-MAR-24:00 | 0.48 | 16-MAR-06:00 | 7516.99 | 31-MAR-23:05 | 7370.96 | 31-MAR-24:00 | 527.00 | 14-MAR-09:00 | 2239.91 | 13-MAR-16:00 | 0.00 |
April | 0.200696E+11 | 0.603746E+10 | 720.00 | 0.194525E+11 | 0.617130E+09 | 0.00 | 1.00 | 14-APR-14:30 | 0.28 | 30-APR-23:53 | 8628.56 | 13-APR-16:00 | 8189.90 | 09-APR-17:51 | 547.97 | 25-APR-15:30 | 3022.60 | 17-APR-15:00 | 0.00 |
May | 0.674479E+10 | 0.214281E+10 | 744.00 | 0.587676E+10 | 0.868039E+09 | 0.00 | 0.55 | 31-MAY-23:03 | 0.23 | 01-MAY-07:00 | 4699.24 | 31-MAY-23:03 | 3933.14 | 31-MAY-24:00 | 766.65 | 31-MAY-23:03 | 1438.52 | 31-MAY-23:08 | 0.00 |
June | 0.116261E+11 | 0.378024E+10 | 720.00 | 0.104877E+11 | 0.113838E+10 | 0.00 | 0.74 | 30-JUN-23:05 | 0.48 | 13-JUN-07:00 | 6306.21 | 30-JUN-23:03 | 5711.11 | 30-JUN-23:15 | 632.77 | 23-JUN-14:00 | 1990.15 | 30-JUN-23:12 | 0.00 |
July | 0.169573E+11 | 0.559969E+10 | 744.00 | 0.157529E+11 | 0.120435E+10 | 0.00 | 0.95 | 31-JUL-23:53 | 0.68 | 14-JUL-21:30 | 8187.98 | 31-JUL-23:03 | 7588.98 | 31-JUL-23:55 | 686.29 | 25-JUL-15:00 | 2708.96 | 31-JUL-23:53 | 0.00 |
August | 0.217303E+11 | 0.716188E+10 | 744.00 | 0.204887E+11 | 0.124169E+10 | 0.00 | 1.00 | 01-AUG-12:20 | 0.31 | 31-AUG-23:23 | 8722.45 | 23-AUG-16:20 | 8167.03 | 20-AUG-18:00 | 661.56 | 22-AUG-15:00 | 3156.35 | 23-AUG-13:00 | 0.00 |
September | 0.674099E+10 | 0.219007E+10 | 720.00 | 0.571967E+10 | 0.102132E+10 | 0.00 | 0.53 | 30-SEP-23:05 | 0.24 | 26-SEP-06:55 | 4405.03 | 30-SEP-23:03 | 3880.97 | 30-SEP-23:25 | 558.26 | 22-SEP-08:70 | 1428.04 | 30-SEP-23:12 | 0.00 |
October | 0.116072E+11 | 0.366310E+10 | 744.00 | 0.106024E+11 | 0.100477E+10 | 0.00 | 0.68 | 31-OCT-23:10 | 0.43 | 28-OCT-06:55 | 5896.06 | 31-OCT-23:10 | 5446.00 | 31-OCT-24:00 | 658.21 | 04-OCT-08:20 | 1780.38 | 03-OCT-15:00 | 0.00 |
November | 0.151363E+11 | 0.450538E+10 | 720.00 | 0.143505E+11 | 0.785877E+09 | 0.00 | 0.81 | 07-NOV-17:00 | 0.49 | 27-NOV-07:00 | 6864.96 | 07-NOV-17:00 | 6450.25 | 07-NOV-17:00 | 618.03 | 29-NOV-11:00 | 2257.87 | 17-NOV-15:00 | 0.00 |
December | 0.194063E+11 | 0.534562E+10 | 744.00 | 0.188476E+11 | 0.558659E+09 | 0.00 | 0.99 | 08-DEC-16:50 | 0.64 | 16-DEC-07:40 | 8668.24 | 08-DEC-17:00 | 8203.24 | 06-DEC-17:00 | 504.42 | 08-DEC-16:50 | 2726.32 | 08-DEC-16:00 | 0.00 |
Annual Sum or Average | 0.158159E+12 | 0.484091E+11 | 8759.21 | 0.148415E+12 | 0.974441E+10 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.416360E+10 | 0.117662E+10 | 672.00 | 0.381303E+10 | 0.350569E+09 | 0.00 | 0.36 | 0.00 | 2874.43 | 2506.47 | 408.51 | 961.62 | 0.00 | ||||||
Maximum of Months | 0.217303E+11 | 0.716188E+10 | 744.00 | 0.204887E+11 | 0.124169E+10 | 0.00 | 1.00 | 0.68 | 8722.45 | 8203.24 | 766.65 | 3156.35 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 117.58 | 0.00 | 117.58 | 114.59 | 291.77 | 0.00 | 0.00 | 0.00 |
February | 139.17 | 0.00 | 139.17 | 174.40 | 245.17 | 0.00 | 0.00 | 0.00 |
March | 165.97 | 0.00 | 165.97 | 210.57 | 200.91 | 0.00 | 0.00 | 0.00 |
April | 185.98 | 0.84 | 185.14 | 297.22 | 124.11 | 0.00 | 0.00 | 0.00 |
May | 212.38 | 9.50 | 202.88 | 415.96 | 65.15 | 0.00 | 0.00 | 0.00 |
June | 226.86 | 16.33 | 210.53 | 479.04 | 27.60 | 0.00 | 0.00 | 0.00 |
July | 229.58 | 11.25 | 218.33 | 506.74 | 39.85 | 0.00 | 0.00 | 0.00 |
August | 203.18 | 1.87 | 201.31 | 422.85 | 26.88 | 0.00 | 0.00 | 0.00 |
September | 180.25 | 0.01 | 180.23 | 394.43 | 47.40 | 0.00 | 0.00 | 0.00 |
October | 151.00 | 0.00 | 151.00 | 289.32 | 75.49 | 0.00 | 0.00 | 0.00 |
November | 131.30 | 0.00 | 131.30 | 200.32 | 152.37 | 0.00 | 0.00 | 0.00 |
December | 116.30 | 0.00 | 116.30 | 127.48 | 254.47 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 171.79 | 3.33 | 168.46 | 303.36 | 128.77 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 116.30 | 0.00 | 116.30 | 114.59 | 26.88 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 229.58 | 16.33 | 218.33 | 506.74 | 291.77 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 117.58 | 0.00 | 117.58 | 114.59 | 291.77 | 0.00 | 0.00 | 0.00 |
February | 139.17 | 0.00 | 139.17 | 174.40 | 245.17 | 0.00 | 0.00 | 0.00 |
March | 165.97 | 0.00 | 165.97 | 210.57 | 200.91 | 0.00 | 0.00 | 0.00 |
April | 185.98 | 0.84 | 185.14 | 297.22 | 124.11 | 0.00 | 0.00 | 0.00 |
May | 212.38 | 9.50 | 202.88 | 415.96 | 65.15 | 0.00 | 0.00 | 0.00 |
June | 226.86 | 16.33 | 210.53 | 479.04 | 27.60 | 0.00 | 0.00 | 0.00 |
July | 229.58 | 11.25 | 218.33 | 506.74 | 39.85 | 0.00 | 0.00 | 0.00 |
August | 203.18 | 1.87 | 201.31 | 422.85 | 26.88 | 0.00 | 0.00 | 0.00 |
September | 180.24 | 0.01 | 180.23 | 394.43 | 47.40 | 0.00 | 0.00 | 0.00 |
October | 151.00 | 0.00 | 151.00 | 289.32 | 75.49 | 0.00 | 0.00 | 0.00 |
November | 131.30 | 0.00 | 131.30 | 200.31 | 152.37 | 0.00 | 0.00 | 0.00 |
December | 116.30 | 0.00 | 116.30 | 127.48 | 254.47 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 171.79 | 3.33 | 168.46 | 303.36 | 128.77 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 116.30 | 0.00 | 116.30 | 114.59 | 26.88 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 229.58 | 16.33 | 218.33 | 506.74 | 291.77 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 117.58 | 0.00 | 117.58 | 114.59 | 291.77 | 0.00 | 0.00 | 0.00 |
February | 139.17 | 0.00 | 139.17 | 174.40 | 245.17 | 0.00 | 0.00 | 0.00 |
March | 165.97 | 0.00 | 165.97 | 210.57 | 200.91 | 0.00 | 0.00 | 0.00 |
April | 185.98 | 0.84 | 185.14 | 297.22 | 124.11 | 0.00 | 0.00 | 0.00 |
May | 212.38 | 9.50 | 202.88 | 415.96 | 65.15 | 0.00 | 0.00 | 0.00 |
June | 226.86 | 16.33 | 210.53 | 479.04 | 27.60 | 0.00 | 0.00 | 0.00 |
July | 229.58 | 11.25 | 218.33 | 506.74 | 39.85 | 0.00 | 0.00 | 0.00 |
August | 203.18 | 1.87 | 201.31 | 422.85 | 26.88 | 0.00 | 0.00 | 0.00 |
September | 180.25 | 0.01 | 180.23 | 394.43 | 47.40 | 0.00 | 0.00 | 0.00 |
October | 151.00 | 0.00 | 151.00 | 289.32 | 75.49 | 0.00 | 0.00 | 0.00 |
November | 131.30 | 0.00 | 131.30 | 200.32 | 152.37 | 0.00 | 0.00 | 0.00 |
December | 116.30 | 0.00 | 116.30 | 127.48 | 254.47 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 171.79 | 3.33 | 168.46 | 303.36 | 128.77 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 116.30 | 0.00 | 116.30 | 114.59 | 26.88 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 229.58 | 16.33 | 218.33 | 506.74 | 291.77 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 117.58 | 0.00 | 117.58 | 114.59 | 291.77 | 0.00 | 0.00 | 0.00 |
February | 139.17 | 0.00 | 139.17 | 174.40 | 245.17 | 0.00 | 0.00 | 0.00 |
March | 165.97 | 0.00 | 165.97 | 210.57 | 200.91 | 0.00 | 0.00 | 0.00 |
April | 185.98 | 0.84 | 185.14 | 297.22 | 124.11 | 0.00 | 0.00 | 0.00 |
May | 212.38 | 9.50 | 202.88 | 415.96 | 65.15 | 0.00 | 0.00 | 0.00 |
June | 226.86 | 16.33 | 210.53 | 479.04 | 27.60 | 0.00 | 0.00 | 0.00 |
July | 229.58 | 11.25 | 218.33 | 506.74 | 39.85 | 0.00 | 0.00 | 0.00 |
August | 203.18 | 1.87 | 201.31 | 422.85 | 26.88 | 0.00 | 0.00 | 0.00 |
September | 180.24 | 0.01 | 180.23 | 394.43 | 47.40 | 0.00 | 0.00 | 0.00 |
October | 151.00 | 0.00 | 151.00 | 289.32 | 75.49 | 0.00 | 0.00 | 0.00 |
November | 131.30 | 0.00 | 131.30 | 200.31 | 152.37 | 0.00 | 0.00 | 0.00 |
December | 116.30 | 0.00 | 116.30 | 127.48 | 254.47 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 171.79 | 3.33 | 168.46 | 303.36 | 128.77 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 116.30 | 0.00 | 116.30 | 114.59 | 26.88 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 229.58 | 16.33 | 218.33 | 506.74 | 291.77 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 117.57 | 0.00 | 117.57 | 114.58 | 291.76 | 0.00 | 0.00 | 0.00 |
February | 139.16 | 0.00 | 139.16 | 174.40 | 245.16 | 0.00 | 0.00 | 0.00 |
March | 165.96 | 0.00 | 165.96 | 210.56 | 200.91 | 0.00 | 0.00 | 0.00 |
April | 185.97 | 0.84 | 185.13 | 297.21 | 124.10 | 0.00 | 0.00 | 0.00 |
May | 212.37 | 9.50 | 202.87 | 415.95 | 65.15 | 0.00 | 0.00 | 0.00 |
June | 226.85 | 16.33 | 210.52 | 479.02 | 27.60 | 0.00 | 0.00 | 0.00 |
July | 229.57 | 11.25 | 218.32 | 506.72 | 39.85 | 0.00 | 0.00 | 0.00 |
August | 203.17 | 1.87 | 201.30 | 422.83 | 26.88 | 0.00 | 0.00 | 0.00 |
September | 180.24 | 0.01 | 180.22 | 394.41 | 47.40 | 0.00 | 0.00 | 0.00 |
October | 151.00 | 0.00 | 151.00 | 289.30 | 75.49 | 0.00 | 0.00 | 0.00 |
November | 131.29 | 0.00 | 131.29 | 200.31 | 152.37 | 0.00 | 0.00 | 0.00 |
December | 116.29 | 0.00 | 116.29 | 127.47 | 254.46 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 171.78 | 3.33 | 168.45 | 303.35 | 128.76 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 116.29 | 0.00 | 116.29 | 114.58 | 26.88 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 229.57 | 16.33 | 218.32 | 506.72 | 291.76 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 314.56 | 150.69 | 163.86 | 426.90 | 299.22 | 0.00 | 0.00 | 0.00 |
February | 363.21 | 168.13 | 195.08 | 536.72 | 249.27 | 0.00 | 0.00 | 0.00 |
March | 443.45 | 209.64 | 233.81 | 661.52 | 197.03 | 0.00 | 0.00 | 0.00 |
April | 481.26 | 214.73 | 266.52 | 807.51 | 126.12 | 0.00 | 0.00 | 0.00 |
May | 455.29 | 181.31 | 273.98 | 836.84 | 66.58 | 0.00 | 0.00 | 0.00 |
June | 449.38 | 172.60 | 276.77 | 872.36 | 25.31 | 0.00 | 0.00 | 0.00 |
July | 461.74 | 166.51 | 295.23 | 925.35 | 36.56 | 0.00 | 0.00 | 0.00 |
August | 422.22 | 141.18 | 281.04 | 824.68 | 18.62 | 0.00 | 0.00 | 0.00 |
September | 407.05 | 147.15 | 259.90 | 803.42 | 50.27 | 0.00 | 0.00 | 0.00 |
October | 374.67 | 161.36 | 213.31 | 685.59 | 75.72 | 0.00 | 0.00 | 0.00 |
November | 304.09 | 121.25 | 182.84 | 495.98 | 148.32 | 0.00 | 0.00 | 0.00 |
December | 245.64 | 86.72 | 158.92 | 343.66 | 250.37 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 393.61 | 160.00 | 233.61 | 685.61 | 128.07 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 245.64 | 86.72 | 158.92 | 343.66 | 18.62 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 481.26 | 214.73 | 295.23 | 925.35 | 299.22 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 314.56 | 150.69 | 163.86 | 426.90 | 299.22 | 0.00 | 0.00 | 0.00 |
February | 363.21 | 168.13 | 195.08 | 536.72 | 249.27 | 0.00 | 0.00 | 0.00 |
March | 443.45 | 209.64 | 233.81 | 661.52 | 197.03 | 0.00 | 0.00 | 0.00 |
April | 481.26 | 214.73 | 266.52 | 807.51 | 126.12 | 0.00 | 0.00 | 0.00 |
May | 455.29 | 181.31 | 273.98 | 836.84 | 66.58 | 0.00 | 0.00 | 0.00 |
June | 449.38 | 172.60 | 276.77 | 872.36 | 25.31 | 0.00 | 0.00 | 0.00 |
July | 461.74 | 166.51 | 295.23 | 925.35 | 36.56 | 0.00 | 0.00 | 0.00 |
August | 422.22 | 141.18 | 281.04 | 824.68 | 18.62 | 0.00 | 0.00 | 0.00 |
September | 407.05 | 147.15 | 259.90 | 803.42 | 50.27 | 0.00 | 0.00 | 0.00 |
October | 374.67 | 161.36 | 213.31 | 685.59 | 75.72 | 0.00 | 0.00 | 0.00 |
November | 304.09 | 121.25 | 182.84 | 495.98 | 148.32 | 0.00 | 0.00 | 0.00 |
December | 245.64 | 86.72 | 158.92 | 343.66 | 250.37 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 393.61 | 160.00 | 233.61 | 685.61 | 128.07 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 245.64 | 86.72 | 158.92 | 343.66 | 18.62 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 481.26 | 214.73 | 295.23 | 925.35 | 299.22 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 314.55 | 150.69 | 163.86 | 426.89 | 299.22 | 0.00 | 0.00 | 0.00 |
February | 363.20 | 168.13 | 195.08 | 536.71 | 249.27 | 0.00 | 0.00 | 0.00 |
March | 443.44 | 209.64 | 233.80 | 661.51 | 197.02 | 0.00 | 0.00 | 0.00 |
April | 481.25 | 214.73 | 266.52 | 807.50 | 126.12 | 0.00 | 0.00 | 0.00 |
May | 455.28 | 181.30 | 273.98 | 836.83 | 66.58 | 0.00 | 0.00 | 0.00 |
June | 449.37 | 172.60 | 276.77 | 872.34 | 25.31 | 0.00 | 0.00 | 0.00 |
July | 461.73 | 166.51 | 295.22 | 925.33 | 36.56 | 0.00 | 0.00 | 0.00 |
August | 422.21 | 141.18 | 281.03 | 824.67 | 18.62 | 0.00 | 0.00 | 0.00 |
September | 407.04 | 147.15 | 259.89 | 803.41 | 50.27 | 0.00 | 0.00 | 0.00 |
October | 374.66 | 161.35 | 213.31 | 685.58 | 75.72 | 0.00 | 0.00 | 0.00 |
November | 304.09 | 121.25 | 182.84 | 495.97 | 148.31 | 0.00 | 0.00 | 0.00 |
December | 245.64 | 86.72 | 158.92 | 343.66 | 250.36 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 393.60 | 160.00 | 233.61 | 685.60 | 128.07 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 245.64 | 86.72 | 158.92 | 343.66 | 18.62 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 481.25 | 214.73 | 295.22 | 925.33 | 299.22 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 552.60 | 359.01 | 193.59 | 837.38 | 285.20 | 0.00 | 0.00 | 0.00 |
February | 499.91 | 289.26 | 210.65 | 799.77 | 244.42 | 0.00 | 0.00 | 0.00 |
March | 383.82 | 162.27 | 221.54 | 621.19 | 200.54 | 0.00 | 0.00 | 0.00 |
April | 260.99 | 45.77 | 215.22 | 465.41 | 131.26 | 0.00 | 0.00 | 0.00 |
May | 209.14 | 4.52 | 204.61 | 411.36 | 64.23 | 0.00 | 0.00 | 0.00 |
June | 199.40 | 0.38 | 199.02 | 423.10 | 27.73 | 0.00 | 0.00 | 0.00 |
July | 213.50 | 1.98 | 211.52 | 473.97 | 39.52 | 0.00 | 0.00 | 0.00 |
August | 242.31 | 20.45 | 221.87 | 508.66 | 28.01 | 0.00 | 0.00 | 0.00 |
September | 310.19 | 76.01 | 234.18 | 651.55 | 51.89 | 0.00 | 0.00 | 0.00 |
October | 426.58 | 200.14 | 226.44 | 794.25 | 88.61 | 0.00 | 0.00 | 0.00 |
November | 485.35 | 270.88 | 214.47 | 809.58 | 157.65 | 0.00 | 0.00 | 0.00 |
December | 532.55 | 335.90 | 196.65 | 825.08 | 254.59 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 359.04 | 146.58 | 212.46 | 634.28 | 130.63 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 199.40 | 0.38 | 193.59 | 411.36 | 27.73 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 552.60 | 359.01 | 234.18 | 837.38 | 285.20 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 552.60 | 359.01 | 193.59 | 837.38 | 285.20 | 0.00 | 0.00 | 0.00 |
February | 499.91 | 289.26 | 210.65 | 799.77 | 244.42 | 0.00 | 0.00 | 0.00 |
March | 383.81 | 162.27 | 221.54 | 621.18 | 200.54 | 0.00 | 0.00 | 0.00 |
April | 260.99 | 45.77 | 215.22 | 465.41 | 131.26 | 0.00 | 0.00 | 0.00 |
May | 209.14 | 4.52 | 204.61 | 411.36 | 64.23 | 0.00 | 0.00 | 0.00 |
June | 199.40 | 0.38 | 199.02 | 423.10 | 27.73 | 0.00 | 0.00 | 0.00 |
July | 213.50 | 1.98 | 211.52 | 473.97 | 39.52 | 0.00 | 0.00 | 0.00 |
August | 242.31 | 20.45 | 221.87 | 508.66 | 28.01 | 0.00 | 0.00 | 0.00 |
September | 310.19 | 76.01 | 234.18 | 651.55 | 51.89 | 0.00 | 0.00 | 0.00 |
October | 426.58 | 200.14 | 226.44 | 794.25 | 88.61 | 0.00 | 0.00 | 0.00 |
November | 485.35 | 270.88 | 214.47 | 809.58 | 157.65 | 0.00 | 0.00 | 0.00 |
December | 532.55 | 335.90 | 196.65 | 825.08 | 254.59 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 359.04 | 146.58 | 212.46 | 634.28 | 130.63 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 199.40 | 0.38 | 193.59 | 411.36 | 27.73 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 552.60 | 359.01 | 234.18 | 837.38 | 285.20 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 552.60 | 359.01 | 193.59 | 837.38 | 285.20 | 0.00 | 0.00 | 0.00 |
February | 499.91 | 289.26 | 210.65 | 799.77 | 244.42 | 0.00 | 0.00 | 0.00 |
March | 383.82 | 162.27 | 221.54 | 621.19 | 200.54 | 0.00 | 0.00 | 0.00 |
April | 260.99 | 45.77 | 215.22 | 465.41 | 131.26 | 0.00 | 0.00 | 0.00 |
May | 209.14 | 4.52 | 204.61 | 411.36 | 64.23 | 0.00 | 0.00 | 0.00 |
June | 199.40 | 0.38 | 199.02 | 423.10 | 27.73 | 0.00 | 0.00 | 0.00 |
July | 213.50 | 1.98 | 211.52 | 473.97 | 39.52 | 0.00 | 0.00 | 0.00 |
August | 242.31 | 20.45 | 221.87 | 508.66 | 28.01 | 0.00 | 0.00 | 0.00 |
September | 310.19 | 76.01 | 234.18 | 651.55 | 51.89 | 0.00 | 0.00 | 0.00 |
October | 426.58 | 200.14 | 226.44 | 794.25 | 88.61 | 0.00 | 0.00 | 0.00 |
November | 485.35 | 270.88 | 214.47 | 809.58 | 157.65 | 0.00 | 0.00 | 0.00 |
December | 532.55 | 335.90 | 196.65 | 825.08 | 254.59 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 359.04 | 146.58 | 212.46 | 634.28 | 130.63 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 199.40 | 0.38 | 193.59 | 411.36 | 27.73 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 552.60 | 359.01 | 234.18 | 837.38 | 285.20 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 552.60 | 359.01 | 193.59 | 837.38 | 285.20 | 0.00 | 0.00 | 0.00 |
February | 499.91 | 289.26 | 210.65 | 799.77 | 244.42 | 0.00 | 0.00 | 0.00 |
March | 383.81 | 162.27 | 221.54 | 621.18 | 200.54 | 0.00 | 0.00 | 0.00 |
April | 260.99 | 45.77 | 215.22 | 465.41 | 131.26 | 0.00 | 0.00 | 0.00 |
May | 209.14 | 4.52 | 204.61 | 411.36 | 64.23 | 0.00 | 0.00 | 0.00 |
June | 199.40 | 0.38 | 199.02 | 423.10 | 27.73 | 0.00 | 0.00 | 0.00 |
July | 213.50 | 1.98 | 211.52 | 473.97 | 39.52 | 0.00 | 0.00 | 0.00 |
August | 242.31 | 20.45 | 221.87 | 508.66 | 28.01 | 0.00 | 0.00 | 0.00 |
September | 310.19 | 76.01 | 234.18 | 651.55 | 51.89 | 0.00 | 0.00 | 0.00 |
October | 426.58 | 200.14 | 226.44 | 794.25 | 88.61 | 0.00 | 0.00 | 0.00 |
November | 485.35 | 270.88 | 214.47 | 809.58 | 157.65 | 0.00 | 0.00 | 0.00 |
December | 532.55 | 335.90 | 196.65 | 825.08 | 254.59 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 359.04 | 146.58 | 212.46 | 634.28 | 130.63 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 199.40 | 0.38 | 193.59 | 411.36 | 27.73 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 552.60 | 359.01 | 234.18 | 837.38 | 285.20 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 552.58 | 359.00 | 193.58 | 837.35 | 285.19 | 0.00 | 0.00 | 0.00 |
February | 499.89 | 289.25 | 210.64 | 799.74 | 244.41 | 0.00 | 0.00 | 0.00 |
March | 383.80 | 162.27 | 221.53 | 621.16 | 200.53 | 0.00 | 0.00 | 0.00 |
April | 260.98 | 45.77 | 215.21 | 465.39 | 131.25 | 0.00 | 0.00 | 0.00 |
May | 209.13 | 4.52 | 204.61 | 411.34 | 64.23 | 0.00 | 0.00 | 0.00 |
June | 199.39 | 0.38 | 199.01 | 423.09 | 27.73 | 0.00 | 0.00 | 0.00 |
July | 213.49 | 1.98 | 211.51 | 473.95 | 39.52 | 0.00 | 0.00 | 0.00 |
August | 242.30 | 20.45 | 221.86 | 508.64 | 28.01 | 0.00 | 0.00 | 0.00 |
September | 310.18 | 76.01 | 234.17 | 651.53 | 51.89 | 0.00 | 0.00 | 0.00 |
October | 426.56 | 200.13 | 226.43 | 794.22 | 88.60 | 0.00 | 0.00 | 0.00 |
November | 485.33 | 270.87 | 214.46 | 809.55 | 157.65 | 0.00 | 0.00 | 0.00 |
December | 532.53 | 335.89 | 196.64 | 825.05 | 254.58 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 359.03 | 146.58 | 212.45 | 634.25 | 130.63 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 199.39 | 0.38 | 193.58 | 411.34 | 27.73 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 552.58 | 359.00 | 234.17 | 837.35 | 285.19 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 282.58 | 121.82 | 160.75 | 381.03 | 352.14 | 0.00 | 0.00 | 0.00 |
February | 353.35 | 159.91 | 193.44 | 526.01 | 319.06 | 0.00 | 0.00 | 0.00 |
March | 440.03 | 200.94 | 239.09 | 656.92 | 276.30 | 0.00 | 0.00 | 0.00 |
April | 484.35 | 224.27 | 260.08 | 790.90 | 194.07 | 0.00 | 0.00 | 0.00 |
May | 441.55 | 169.98 | 271.57 | 808.05 | 98.65 | 0.00 | 0.00 | 0.00 |
June | 374.13 | 104.95 | 269.18 | 718.09 | 50.64 | 0.00 | 0.00 | 0.00 |
July | 418.12 | 129.35 | 288.77 | 822.58 | 72.67 | 0.00 | 0.00 | 0.00 |
August | 417.17 | 135.95 | 281.21 | 773.09 | 70.45 | 0.00 | 0.00 | 0.00 |
September | 355.87 | 104.93 | 250.93 | 698.45 | 69.34 | 0.00 | 0.00 | 0.00 |
October | 354.02 | 138.01 | 216.01 | 635.99 | 119.64 | 0.00 | 0.00 | 0.00 |
November | 292.03 | 107.12 | 184.91 | 465.94 | 217.31 | 0.00 | 0.00 | 0.00 |
December | 292.55 | 130.80 | 161.76 | 405.37 | 345.65 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 375.65 | 143.97 | 231.68 | 640.83 | 181.57 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 282.58 | 104.93 | 160.75 | 381.03 | 50.64 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 484.35 | 224.27 | 288.77 | 822.58 | 352.14 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 282.58 | 121.82 | 160.75 | 381.03 | 352.14 | 0.00 | 0.00 | 0.00 |
February | 353.35 | 159.91 | 193.44 | 526.01 | 319.06 | 0.00 | 0.00 | 0.00 |
March | 440.03 | 200.94 | 239.09 | 656.92 | 276.30 | 0.00 | 0.00 | 0.00 |
April | 484.35 | 224.27 | 260.08 | 790.90 | 194.07 | 0.00 | 0.00 | 0.00 |
May | 441.55 | 169.98 | 271.57 | 808.05 | 98.65 | 0.00 | 0.00 | 0.00 |
June | 374.13 | 104.95 | 269.18 | 718.09 | 50.64 | 0.00 | 0.00 | 0.00 |
July | 418.12 | 129.35 | 288.77 | 822.58 | 72.67 | 0.00 | 0.00 | 0.00 |
August | 417.17 | 135.95 | 281.21 | 773.09 | 70.45 | 0.00 | 0.00 | 0.00 |
September | 355.87 | 104.93 | 250.93 | 698.45 | 69.34 | 0.00 | 0.00 | 0.00 |
October | 354.02 | 138.01 | 216.01 | 635.99 | 119.64 | 0.00 | 0.00 | 0.00 |
November | 292.03 | 107.12 | 184.91 | 465.94 | 217.31 | 0.00 | 0.00 | 0.00 |
December | 292.55 | 130.80 | 161.76 | 405.37 | 345.65 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 375.65 | 143.97 | 231.68 | 640.83 | 181.57 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 282.58 | 104.93 | 160.75 | 381.03 | 50.64 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 484.35 | 224.27 | 288.77 | 822.58 | 352.14 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 282.57 | 121.82 | 160.75 | 381.02 | 352.14 | 0.00 | 0.00 | 0.00 |
February | 353.35 | 159.91 | 193.44 | 526.01 | 319.05 | 0.00 | 0.00 | 0.00 |
March | 440.03 | 200.94 | 239.09 | 656.91 | 276.30 | 0.00 | 0.00 | 0.00 |
April | 484.34 | 224.27 | 260.08 | 790.88 | 194.06 | 0.00 | 0.00 | 0.00 |
May | 441.54 | 169.97 | 271.57 | 808.03 | 98.65 | 0.00 | 0.00 | 0.00 |
June | 374.12 | 104.94 | 269.18 | 718.08 | 50.64 | 0.00 | 0.00 | 0.00 |
July | 418.11 | 129.35 | 288.76 | 822.56 | 72.67 | 0.00 | 0.00 | 0.00 |
August | 417.16 | 135.95 | 281.21 | 773.07 | 70.45 | 0.00 | 0.00 | 0.00 |
September | 355.86 | 104.93 | 250.93 | 698.43 | 69.34 | 0.00 | 0.00 | 0.00 |
October | 354.02 | 138.01 | 216.01 | 635.98 | 119.63 | 0.00 | 0.00 | 0.00 |
November | 292.03 | 107.12 | 184.91 | 465.93 | 217.30 | 0.00 | 0.00 | 0.00 |
December | 292.55 | 130.80 | 161.75 | 405.36 | 345.64 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 375.64 | 143.97 | 231.68 | 640.82 | 181.57 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 282.57 | 104.93 | 160.75 | 381.02 | 50.64 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 484.34 | 224.27 | 288.76 | 822.56 | 352.14 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 587.87 | 0.00 | 587.87 | 639.84 | 1260.10 | 0.00 | 0.00 | 0.00 |
February | 695.84 | 0.00 | 695.84 | 937.53 | 1054.24 | 0.00 | 0.00 | 0.00 |
March | 829.84 | 0.00 | 829.84 | 1098.61 | 892.77 | 0.00 | 0.00 | 0.00 |
April | 929.87 | 4.18 | 925.70 | 1512.59 | 592.70 | 0.00 | 0.00 | 0.00 |
May | 1061.87 | 47.50 | 1014.37 | 2081.17 | 319.65 | 0.00 | 0.00 | 0.00 |
June | 1134.30 | 81.67 | 1052.63 | 2396.32 | 148.70 | 0.00 | 0.00 | 0.00 |
July | 1147.88 | 56.25 | 1091.63 | 2549.95 | 205.76 | 0.00 | 0.00 | 0.00 |
August | 1015.89 | 9.34 | 1006.54 | 2150.60 | 135.19 | 0.00 | 0.00 | 0.00 |
September | 901.21 | 0.07 | 901.14 | 1987.96 | 231.36 | 0.00 | 0.00 | 0.00 |
October | 755.00 | 0.00 | 755.00 | 1465.97 | 359.79 | 0.00 | 0.00 | 0.00 |
November | 656.47 | 0.00 | 656.47 | 1040.00 | 672.69 | 0.00 | 0.00 | 0.00 |
December | 581.48 | 0.00 | 581.48 | 706.24 | 1077.92 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 858.94 | 16.67 | 842.28 | 1550.19 | 577.17 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 581.48 | 0.00 | 581.48 | 639.84 | 135.19 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1147.88 | 81.67 | 1091.63 | 2549.95 | 1260.10 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 943.66 | 452.07 | 491.59 | 1297.76 | 814.69 | 0.00 | 0.00 | 0.00 |
February | 1089.62 | 504.38 | 585.23 | 1617.16 | 681.43 | 0.00 | 0.00 | 0.00 |
March | 1330.34 | 628.93 | 701.41 | 1962.76 | 574.51 | 0.00 | 0.00 | 0.00 |
April | 1443.75 | 644.20 | 799.56 | 2384.44 | 410.09 | 0.00 | 0.00 | 0.00 |
May | 1365.85 | 543.91 | 821.93 | 2481.08 | 208.73 | 0.00 | 0.00 | 0.00 |
June | 1348.11 | 517.80 | 830.31 | 2579.83 | 98.56 | 0.00 | 0.00 | 0.00 |
July | 1385.20 | 499.53 | 885.67 | 2746.27 | 139.89 | 0.00 | 0.00 | 0.00 |
August | 1266.64 | 423.54 | 843.11 | 2445.81 | 89.15 | 0.00 | 0.00 | 0.00 |
September | 1221.13 | 441.44 | 779.69 | 2387.38 | 160.10 | 0.00 | 0.00 | 0.00 |
October | 1124.00 | 484.06 | 639.94 | 2035.17 | 246.43 | 0.00 | 0.00 | 0.00 |
November | 912.27 | 363.76 | 548.51 | 1479.81 | 432.40 | 0.00 | 0.00 | 0.00 |
December | 736.92 | 260.17 | 476.75 | 1046.35 | 693.02 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1180.82 | 479.99 | 700.82 | 2040.26 | 377.73 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 736.92 | 260.17 | 476.75 | 1046.35 | 89.15 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1443.75 | 644.20 | 885.67 | 2746.27 | 814.69 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 2762.96 | 1795.04 | 967.93 | 4146.37 | 1382.58 | 0.00 | 0.00 | 0.00 |
February | 2499.51 | 1446.27 | 1053.23 | 3965.20 | 1168.28 | 0.00 | 0.00 | 0.00 |
March | 1919.05 | 811.36 | 1107.69 | 3081.30 | 966.07 | 0.00 | 0.00 | 0.00 |
April | 1304.92 | 228.83 | 1076.09 | 2322.76 | 648.64 | 0.00 | 0.00 | 0.00 |
May | 1045.68 | 22.62 | 1023.06 | 2057.79 | 311.99 | 0.00 | 0.00 | 0.00 |
June | 996.97 | 1.88 | 995.09 | 2127.18 | 145.99 | 0.00 | 0.00 | 0.00 |
July | 1067.48 | 9.89 | 1057.59 | 2390.15 | 201.44 | 0.00 | 0.00 | 0.00 |
August | 1211.56 | 102.24 | 1109.32 | 2566.86 | 144.33 | 0.00 | 0.00 | 0.00 |
September | 1550.96 | 380.07 | 1170.89 | 3239.22 | 263.49 | 0.00 | 0.00 | 0.00 |
October | 2132.87 | 1000.68 | 1132.20 | 3931.72 | 458.35 | 0.00 | 0.00 | 0.00 |
November | 2426.74 | 1354.39 | 1072.35 | 4007.88 | 774.21 | 0.00 | 0.00 | 0.00 |
December | 2662.72 | 1679.50 | 983.23 | 4094.51 | 1225.25 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1795.20 | 732.91 | 1062.29 | 3156.90 | 638.55 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 996.97 | 1.88 | 967.93 | 2057.79 | 144.33 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2762.96 | 1795.04 | 1170.89 | 4146.37 | 1382.58 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 847.72 | 365.47 | 482.26 | 1196.97 | 895.15 | 0.00 | 0.00 | 0.00 |
February | 1060.05 | 479.73 | 580.32 | 1640.56 | 788.16 | 0.00 | 0.00 | 0.00 |
March | 1320.09 | 602.82 | 717.27 | 2024.27 | 692.23 | 0.00 | 0.00 | 0.00 |
April | 1453.04 | 672.80 | 780.23 | 2427.21 | 499.73 | 0.00 | 0.00 | 0.00 |
May | 1324.63 | 509.92 | 814.71 | 2433.83 | 270.81 | 0.00 | 0.00 | 0.00 |
June | 1122.37 | 314.83 | 807.53 | 2191.36 | 127.10 | 0.00 | 0.00 | 0.00 |
July | 1254.35 | 388.06 | 866.29 | 2519.62 | 177.37 | 0.00 | 0.00 | 0.00 |
August | 1251.50 | 407.86 | 843.64 | 2400.44 | 134.44 | 0.00 | 0.00 | 0.00 |
September | 1067.59 | 314.80 | 752.79 | 2116.92 | 183.97 | 0.00 | 0.00 | 0.00 |
October | 1062.06 | 414.02 | 648.03 | 1939.20 | 305.66 | 0.00 | 0.00 | 0.00 |
November | 876.09 | 321.35 | 554.73 | 1457.50 | 512.20 | 0.00 | 0.00 | 0.00 |
December | 877.65 | 392.39 | 485.26 | 1299.97 | 791.80 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1126.94 | 431.90 | 695.04 | 1972.52 | 446.71 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 847.72 | 314.80 | 482.26 | 1196.97 | 127.10 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1453.04 | 672.80 | 866.29 | 2519.62 | 895.15 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 587.87 | 0.00 | 587.87 | 663.20 | 1170.67 | 0.00 | 0.00 | 0.00 |
February | 695.84 | 0.00 | 695.84 | 945.67 | 996.66 | 0.00 | 0.00 | 0.00 |
March | 829.84 | 0.00 | 829.84 | 1090.17 | 860.88 | 0.00 | 0.00 | 0.00 |
April | 929.87 | 4.18 | 925.70 | 1489.72 | 586.87 | 0.00 | 0.00 | 0.00 |
May | 1061.87 | 47.50 | 1014.37 | 2045.63 | 331.08 | 0.00 | 0.00 | 0.00 |
June | 1134.30 | 81.67 | 1052.63 | 2351.30 | 157.14 | 0.00 | 0.00 | 0.00 |
July | 1147.88 | 56.25 | 1091.63 | 2503.66 | 219.85 | 0.00 | 0.00 | 0.00 |
August | 1015.89 | 9.34 | 1006.54 | 2115.08 | 144.01 | 0.00 | 0.00 | 0.00 |
September | 901.21 | 0.07 | 901.14 | 1946.84 | 235.92 | 0.00 | 0.00 | 0.00 |
October | 755.00 | 0.00 | 755.00 | 1445.53 | 357.58 | 0.00 | 0.00 | 0.00 |
November | 656.47 | 0.00 | 656.47 | 1041.27 | 630.33 | 0.00 | 0.00 | 0.00 |
December | 581.48 | 0.00 | 581.48 | 721.69 | 1007.44 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 858.94 | 16.67 | 842.28 | 1532.84 | 556.30 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 581.48 | 0.00 | 581.48 | 663.20 | 144.01 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1147.88 | 81.67 | 1091.63 | 2503.66 | 1170.67 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 943.66 | 452.07 | 491.59 | 1312.31 | 767.41 | 0.00 | 0.00 | 0.00 |
February | 1089.62 | 504.38 | 585.23 | 1619.20 | 650.49 | 0.00 | 0.00 | 0.00 |
March | 1330.34 | 628.93 | 701.41 | 1951.14 | 559.27 | 0.00 | 0.00 | 0.00 |
April | 1443.75 | 644.20 | 799.56 | 2363.34 | 407.39 | 0.00 | 0.00 | 0.00 |
May | 1365.85 | 543.91 | 821.93 | 2452.29 | 216.01 | 0.00 | 0.00 | 0.00 |
June | 1348.11 | 517.80 | 830.31 | 2547.19 | 103.32 | 0.00 | 0.00 | 0.00 |
July | 1385.20 | 499.53 | 885.67 | 2714.07 | 147.91 | 0.00 | 0.00 | 0.00 |
August | 1266.64 | 423.54 | 843.11 | 2418.34 | 93.94 | 0.00 | 0.00 | 0.00 |
September | 1221.13 | 441.44 | 779.69 | 2358.03 | 162.66 | 0.00 | 0.00 | 0.00 |
October | 1124.00 | 484.06 | 639.94 | 2017.30 | 245.53 | 0.00 | 0.00 | 0.00 |
November | 912.27 | 363.76 | 548.51 | 1477.50 | 409.52 | 0.00 | 0.00 | 0.00 |
December | 736.92 | 260.17 | 476.75 | 1054.48 | 654.21 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1180.82 | 479.99 | 700.82 | 2025.31 | 366.89 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 736.92 | 260.17 | 476.75 | 1054.48 | 93.94 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1443.75 | 644.20 | 885.67 | 2714.07 | 767.41 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 2762.96 | 1795.04 | 967.93 | 4162.65 | 1303.82 | 0.00 | 0.00 | 0.00 |
February | 2499.51 | 1446.27 | 1053.23 | 3965.27 | 1114.30 | 0.00 | 0.00 | 0.00 |
March | 1919.05 | 811.36 | 1107.69 | 3065.10 | 935.04 | 0.00 | 0.00 | 0.00 |
April | 1304.92 | 228.83 | 1076.09 | 2296.07 | 641.81 | 0.00 | 0.00 | 0.00 |
May | 1045.68 | 22.62 | 1023.06 | 2020.69 | 322.68 | 0.00 | 0.00 | 0.00 |
June | 996.97 | 1.88 | 995.09 | 2081.90 | 154.69 | 0.00 | 0.00 | 0.00 |
July | 1067.48 | 9.89 | 1057.59 | 2343.04 | 216.19 | 0.00 | 0.00 | 0.00 |
August | 1211.56 | 102.24 | 1109.32 | 2529.12 | 152.50 | 0.00 | 0.00 | 0.00 |
September | 1550.96 | 380.07 | 1170.89 | 3198.79 | 268.19 | 0.00 | 0.00 | 0.00 |
October | 2132.87 | 1000.68 | 1132.20 | 3907.69 | 454.54 | 0.00 | 0.00 | 0.00 |
November | 2426.74 | 1354.39 | 1072.35 | 4002.58 | 737.51 | 0.00 | 0.00 | 0.00 |
December | 2662.72 | 1679.50 | 983.23 | 4098.89 | 1160.59 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1795.20 | 732.91 | 1062.29 | 3135.21 | 619.65 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 996.97 | 1.88 | 967.93 | 2020.69 | 152.50 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2762.96 | 1795.04 | 1170.89 | 4162.65 | 1303.82 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 847.72 | 365.47 | 482.26 | 1205.43 | 842.53 | 0.00 | 0.00 | 0.00 |
February | 1060.05 | 479.73 | 580.32 | 1640.74 | 751.82 | 0.00 | 0.00 | 0.00 |
March | 1320.09 | 602.82 | 717.27 | 2014.07 | 669.18 | 0.00 | 0.00 | 0.00 |
April | 1453.04 | 672.80 | 780.23 | 2411.12 | 490.96 | 0.00 | 0.00 | 0.00 |
May | 1324.63 | 509.92 | 814.71 | 2411.55 | 273.15 | 0.00 | 0.00 | 0.00 |
June | 1122.37 | 314.83 | 807.53 | 2167.01 | 129.66 | 0.00 | 0.00 | 0.00 |
July | 1254.35 | 388.06 | 866.29 | 2493.09 | 180.89 | 0.00 | 0.00 | 0.00 |
August | 1251.50 | 407.86 | 843.64 | 2379.69 | 137.17 | 0.00 | 0.00 | 0.00 |
September | 1067.59 | 314.80 | 752.79 | 2095.80 | 183.88 | 0.00 | 0.00 | 0.00 |
October | 1062.06 | 414.02 | 648.03 | 1926.73 | 300.36 | 0.00 | 0.00 | 0.00 |
November | 876.09 | 321.35 | 554.73 | 1456.19 | 485.44 | 0.00 | 0.00 | 0.00 |
December | 877.65 | 392.39 | 485.26 | 1305.08 | 749.05 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1126.94 | 431.90 | 695.04 | 1960.68 | 431.43 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 847.72 | 314.80 | 482.26 | 1205.43 | 129.66 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1453.04 | 672.80 | 866.29 | 2493.09 | 842.53 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.314915E+09 | 0.00 | 0.314915E+09 | 0.306906E+09 | 0.781471E+09 |
February | 0.336680E+09 | 0.00 | 0.336680E+09 | 0.421919E+09 | 0.593118E+09 |
March | 0.444534E+09 | 0.00 | 0.444534E+09 | 0.563986E+09 | 0.538129E+09 |
April | 0.482052E+09 | 2165433.05 | 0.479887E+09 | 0.770400E+09 | 0.321687E+09 |
May | 0.568829E+09 | 25445025.49 | 0.543384E+09 | 0.111411E+10 | 0.174509E+09 |
June | 0.588030E+09 | 42339934.97 | 0.545690E+09 | 0.124168E+10 | 71537105.68 |
July | 0.614902E+09 | 30131377.07 | 0.584770E+09 | 0.135725E+10 | 0.106731E+09 |
August | 0.544197E+09 | 5005113.25 | 0.539191E+09 | 0.113256E+10 | 71992447.19 |
September | 0.467195E+09 | 36959.50 | 0.467158E+09 | 0.102236E+10 | 0.122870E+09 |
October | 0.404442E+09 | 0.00 | 0.404442E+09 | 0.774903E+09 | 0.202206E+09 |
November | 0.340321E+09 | 0.00 | 0.340321E+09 | 0.519217E+09 | 0.394948E+09 |
December | 0.311491E+09 | 0.00 | 0.311491E+09 | 0.341437E+09 | 0.681561E+09 |
Annual Sum or Average | 0.541759E+10 | 0.105124E+09 | 0.531246E+10 | 0.956673E+10 | 0.406076E+10 |
Minimum of Months | 0.311491E+09 | 0.00 | 0.311491E+09 | 0.306906E+09 | 71537105.68 |
Maximum of Months | 0.614902E+09 | 42339934.97 | 0.584770E+09 | 0.135725E+10 | 0.781471E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.314915E+09 | 0.00 | 0.314915E+09 | 0.306906E+09 | 0.781471E+09 |
February | 0.336679E+09 | 0.00 | 0.336679E+09 | 0.421919E+09 | 0.593118E+09 |
March | 0.444533E+09 | 0.00 | 0.444533E+09 | 0.563985E+09 | 0.538128E+09 |
April | 0.482052E+09 | 2165430.45 | 0.479887E+09 | 0.770400E+09 | 0.321687E+09 |
May | 0.568828E+09 | 25444994.96 | 0.543383E+09 | 0.111411E+10 | 0.174508E+09 |
June | 0.588030E+09 | 42339884.17 | 0.545690E+09 | 0.124168E+10 | 71537019.57 |
July | 0.614901E+09 | 30131340.91 | 0.584770E+09 | 0.135725E+10 | 0.106731E+09 |
August | 0.544196E+09 | 5005107.25 | 0.539191E+09 | 0.113255E+10 | 71992342.29 |
September | 0.467195E+09 | 36959.46 | 0.467158E+09 | 0.102236E+10 | 0.122870E+09 |
October | 0.404442E+09 | 0.00 | 0.404442E+09 | 0.774903E+09 | 0.202205E+09 |
November | 0.340320E+09 | 0.00 | 0.340320E+09 | 0.519216E+09 | 0.394948E+09 |
December | 0.311490E+09 | 0.00 | 0.311490E+09 | 0.341436E+09 | 0.681561E+09 |
Annual Sum or Average | 0.541758E+10 | 0.105124E+09 | 0.531246E+10 | 0.956672E+10 | 0.406076E+10 |
Minimum of Months | 0.311490E+09 | 0.00 | 0.311490E+09 | 0.306906E+09 | 71537019.57 |
Maximum of Months | 0.614901E+09 | 42339884.17 | 0.584770E+09 | 0.135725E+10 | 0.781471E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.314915E+09 | 0.00 | 0.314915E+09 | 0.306906E+09 | 0.781471E+09 |
February | 0.336680E+09 | 0.00 | 0.336680E+09 | 0.421919E+09 | 0.593118E+09 |
March | 0.444534E+09 | 0.00 | 0.444534E+09 | 0.563986E+09 | 0.538129E+09 |
April | 0.482052E+09 | 2165433.05 | 0.479887E+09 | 0.770400E+09 | 0.321687E+09 |
May | 0.568829E+09 | 25445025.49 | 0.543384E+09 | 0.111411E+10 | 0.174509E+09 |
June | 0.588030E+09 | 42339934.97 | 0.545690E+09 | 0.124168E+10 | 71537105.68 |
July | 0.614902E+09 | 30131377.07 | 0.584770E+09 | 0.135725E+10 | 0.106731E+09 |
August | 0.544197E+09 | 5005113.25 | 0.539191E+09 | 0.113256E+10 | 71992447.19 |
September | 0.467195E+09 | 36959.50 | 0.467158E+09 | 0.102236E+10 | 0.122870E+09 |
October | 0.404442E+09 | 0.00 | 0.404442E+09 | 0.774903E+09 | 0.202206E+09 |
November | 0.340321E+09 | 0.00 | 0.340321E+09 | 0.519217E+09 | 0.394948E+09 |
December | 0.311491E+09 | 0.00 | 0.311491E+09 | 0.341437E+09 | 0.681561E+09 |
Annual Sum or Average | 0.541759E+10 | 0.105124E+09 | 0.531246E+10 | 0.956673E+10 | 0.406076E+10 |
Minimum of Months | 0.311491E+09 | 0.00 | 0.311491E+09 | 0.306906E+09 | 71537105.68 |
Maximum of Months | 0.614902E+09 | 42339934.97 | 0.584770E+09 | 0.135725E+10 | 0.781471E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.314915E+09 | 0.00 | 0.314915E+09 | 0.306906E+09 | 0.781471E+09 |
February | 0.336679E+09 | 0.00 | 0.336679E+09 | 0.421919E+09 | 0.593118E+09 |
March | 0.444533E+09 | 0.00 | 0.444533E+09 | 0.563985E+09 | 0.538128E+09 |
April | 0.482052E+09 | 2165430.45 | 0.479887E+09 | 0.770400E+09 | 0.321687E+09 |
May | 0.568828E+09 | 25444994.96 | 0.543383E+09 | 0.111411E+10 | 0.174508E+09 |
June | 0.588030E+09 | 42339884.17 | 0.545690E+09 | 0.124168E+10 | 71537019.57 |
July | 0.614901E+09 | 30131340.91 | 0.584770E+09 | 0.135725E+10 | 0.106731E+09 |
August | 0.544196E+09 | 5005107.25 | 0.539191E+09 | 0.113255E+10 | 71992342.29 |
September | 0.467195E+09 | 36959.46 | 0.467158E+09 | 0.102236E+10 | 0.122870E+09 |
October | 0.404442E+09 | 0.00 | 0.404442E+09 | 0.774903E+09 | 0.202205E+09 |
November | 0.340320E+09 | 0.00 | 0.340320E+09 | 0.519216E+09 | 0.394948E+09 |
December | 0.311490E+09 | 0.00 | 0.311490E+09 | 0.341436E+09 | 0.681561E+09 |
Annual Sum or Average | 0.541758E+10 | 0.105124E+09 | 0.531246E+10 | 0.956672E+10 | 0.406076E+10 |
Minimum of Months | 0.311490E+09 | 0.00 | 0.311490E+09 | 0.306906E+09 | 71537019.57 |
Maximum of Months | 0.614901E+09 | 42339884.17 | 0.584770E+09 | 0.135725E+10 | 0.781471E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.314903E+09 | 0.00 | 0.314903E+09 | 0.306894E+09 | 0.781440E+09 |
February | 0.336666E+09 | 0.00 | 0.336666E+09 | 0.421902E+09 | 0.593094E+09 |
March | 0.444516E+09 | 0.00 | 0.444516E+09 | 0.563963E+09 | 0.538107E+09 |
April | 0.482033E+09 | 2165345.78 | 0.479868E+09 | 0.770369E+09 | 0.321674E+09 |
May | 0.568806E+09 | 25443999.94 | 0.543362E+09 | 0.111407E+10 | 0.174502E+09 |
June | 0.588006E+09 | 42338228.49 | 0.545668E+09 | 0.124163E+10 | 71534222.42 |
July | 0.614877E+09 | 30130162.64 | 0.584747E+09 | 0.135719E+10 | 0.106727E+09 |
August | 0.544175E+09 | 5004911.53 | 0.539170E+09 | 0.113251E+10 | 71989545.58 |
September | 0.467177E+09 | 36958.01 | 0.467140E+09 | 0.102232E+10 | 0.122865E+09 |
October | 0.404426E+09 | 0.00 | 0.404426E+09 | 0.774872E+09 | 0.202197E+09 |
November | 0.340307E+09 | 0.00 | 0.340307E+09 | 0.519196E+09 | 0.394932E+09 |
December | 0.311478E+09 | 0.00 | 0.311478E+09 | 0.341423E+09 | 0.681534E+09 |
Annual Sum or Average | 0.541737E+10 | 0.105120E+09 | 0.531225E+10 | 0.956634E+10 | 0.406060E+10 |
Minimum of Months | 0.311478E+09 | 0.00 | 0.311478E+09 | 0.306894E+09 | 71534222.42 |
Maximum of Months | 0.614877E+09 | 42338228.49 | 0.584747E+09 | 0.135719E+10 | 0.781440E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.842508E+09 | 0.403614E+09 | 0.438895E+09 | 0.114341E+10 | 0.801433E+09 |
February | 0.878675E+09 | 0.406740E+09 | 0.471934E+09 | 0.129844E+10 | 0.603038E+09 |
March | 0.118774E+10 | 0.561511E+09 | 0.626226E+09 | 0.177183E+10 | 0.527716E+09 |
April | 0.124741E+10 | 0.556591E+09 | 0.690824E+09 | 0.209307E+10 | 0.326915E+09 |
May | 0.121944E+10 | 0.485610E+09 | 0.733831E+09 | 0.224140E+10 | 0.178322E+09 |
June | 0.116478E+10 | 0.447385E+09 | 0.717397E+09 | 0.226115E+10 | 65600567.29 |
July | 0.123672E+10 | 0.445986E+09 | 0.790732E+09 | 0.247845E+10 | 97934529.55 |
August | 0.113087E+10 | 0.378140E+09 | 0.752732E+09 | 0.220883E+10 | 49883216.16 |
September | 0.105506E+10 | 0.381410E+09 | 0.673655E+09 | 0.208248E+10 | 0.130308E+09 |
October | 0.100352E+10 | 0.432175E+09 | 0.571340E+09 | 0.183629E+10 | 0.202805E+09 |
November | 0.788211E+09 | 0.314290E+09 | 0.473921E+09 | 0.128558E+10 | 0.384437E+09 |
December | 0.657926E+09 | 0.232280E+09 | 0.425647E+09 | 0.920464E+09 | 0.670579E+09 |
Annual Sum or Average | 0.124129E+11 | 0.504573E+10 | 0.736713E+10 | 0.216214E+11 | 0.403897E+10 |
Minimum of Months | 0.657926E+09 | 0.232280E+09 | 0.425647E+09 | 0.920464E+09 | 49883216.16 |
Maximum of Months | 0.124741E+10 | 0.561511E+09 | 0.790732E+09 | 0.247845E+10 | 0.801433E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.842508E+09 | 0.403614E+09 | 0.438895E+09 | 0.114341E+10 | 0.801433E+09 |
February | 0.878675E+09 | 0.406740E+09 | 0.471934E+09 | 0.129844E+10 | 0.603038E+09 |
March | 0.118774E+10 | 0.561511E+09 | 0.626226E+09 | 0.177183E+10 | 0.527716E+09 |
April | 0.124741E+10 | 0.556591E+09 | 0.690824E+09 | 0.209307E+10 | 0.326915E+09 |
May | 0.121944E+10 | 0.485610E+09 | 0.733831E+09 | 0.224140E+10 | 0.178322E+09 |
June | 0.116478E+10 | 0.447385E+09 | 0.717397E+09 | 0.226115E+10 | 65600567.29 |
July | 0.123672E+10 | 0.445986E+09 | 0.790732E+09 | 0.247845E+10 | 97934529.55 |
August | 0.113087E+10 | 0.378140E+09 | 0.752732E+09 | 0.220883E+10 | 49883216.16 |
September | 0.105506E+10 | 0.381410E+09 | 0.673655E+09 | 0.208248E+10 | 0.130308E+09 |
October | 0.100352E+10 | 0.432175E+09 | 0.571340E+09 | 0.183629E+10 | 0.202805E+09 |
November | 0.788211E+09 | 0.314290E+09 | 0.473921E+09 | 0.128558E+10 | 0.384437E+09 |
December | 0.657926E+09 | 0.232280E+09 | 0.425647E+09 | 0.920464E+09 | 0.670579E+09 |
Annual Sum or Average | 0.124129E+11 | 0.504573E+10 | 0.736713E+10 | 0.216214E+11 | 0.403897E+10 |
Minimum of Months | 0.657926E+09 | 0.232280E+09 | 0.425647E+09 | 0.920464E+09 | 49883216.16 |
Maximum of Months | 0.124741E+10 | 0.561511E+09 | 0.790732E+09 | 0.247845E+10 | 0.801433E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.842493E+09 | 0.403606E+09 | 0.438887E+09 | 0.114338E+10 | 0.801418E+09 |
February | 0.878658E+09 | 0.406733E+09 | 0.471926E+09 | 0.129842E+10 | 0.603027E+09 |
March | 0.118772E+10 | 0.561501E+09 | 0.626214E+09 | 0.177179E+10 | 0.527706E+09 |
April | 0.124739E+10 | 0.556581E+09 | 0.690811E+09 | 0.209303E+10 | 0.326909E+09 |
May | 0.121942E+10 | 0.485601E+09 | 0.733818E+09 | 0.224136E+10 | 0.178319E+09 |
June | 0.116476E+10 | 0.447377E+09 | 0.717384E+09 | 0.226111E+10 | 65599368.62 |
July | 0.123670E+10 | 0.445978E+09 | 0.790718E+09 | 0.247840E+10 | 97932740.08 |
August | 0.113085E+10 | 0.378133E+09 | 0.752719E+09 | 0.220879E+10 | 49882304.68 |
September | 0.105505E+10 | 0.381403E+09 | 0.673642E+09 | 0.208244E+10 | 0.130305E+09 |
October | 0.100350E+10 | 0.432167E+09 | 0.571330E+09 | 0.183626E+10 | 0.202802E+09 |
November | 0.788197E+09 | 0.314285E+09 | 0.473912E+09 | 0.128556E+10 | 0.384430E+09 |
December | 0.657914E+09 | 0.232276E+09 | 0.425639E+09 | 0.920448E+09 | 0.670567E+09 |
Annual Sum or Average | 0.124126E+11 | 0.504564E+10 | 0.736700E+10 | 0.216210E+11 | 0.403890E+10 |
Minimum of Months | 0.657914E+09 | 0.232276E+09 | 0.425639E+09 | 0.920448E+09 | 49882304.68 |
Maximum of Months | 0.124739E+10 | 0.561501E+09 | 0.790718E+09 | 0.247840E+10 | 0.801418E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.148008E+10 | 0.961576E+09 | 0.518506E+09 | 0.224285E+10 | 0.763886E+09 |
February | 0.120938E+10 | 0.699773E+09 | 0.509603E+09 | 0.193481E+10 | 0.591303E+09 |
March | 0.102801E+10 | 0.434635E+09 | 0.593376E+09 | 0.166378E+10 | 0.537131E+09 |
April | 0.676479E+09 | 0.118628E+09 | 0.557851E+09 | 0.120634E+10 | 0.340219E+09 |
May | 0.560158E+09 | 12118894.79 | 0.548040E+09 | 0.110179E+10 | 0.172041E+09 |
June | 0.516835E+09 | 975353.64 | 0.515859E+09 | 0.109669E+10 | 71875439.93 |
July | 0.571836E+09 | 5300419.95 | 0.566536E+09 | 0.126949E+10 | 0.105846E+09 |
August | 0.649016E+09 | 54767479.38 | 0.594248E+09 | 0.136240E+10 | 75018245.26 |
September | 0.804025E+09 | 0.197028E+09 | 0.606997E+09 | 0.168882E+10 | 0.134499E+09 |
October | 0.114255E+10 | 0.536050E+09 | 0.606502E+09 | 0.212732E+10 | 0.237320E+09 |
November | 0.125804E+10 | 0.702124E+09 | 0.555914E+09 | 0.209844E+10 | 0.408638E+09 |
December | 0.142639E+10 | 0.899683E+09 | 0.526702E+09 | 0.220991E+10 | 0.681890E+09 |
Annual Sum or Average | 0.113228E+11 | 0.462266E+10 | 0.670013E+10 | 0.200026E+11 | 0.411967E+10 |
Minimum of Months | 0.516835E+09 | 975353.64 | 0.509603E+09 | 0.109669E+10 | 71875439.93 |
Maximum of Months | 0.148008E+10 | 0.961576E+09 | 0.606997E+09 | 0.224285E+10 | 0.763886E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.148008E+10 | 0.961575E+09 | 0.518506E+09 | 0.224284E+10 | 0.763886E+09 |
February | 0.120937E+10 | 0.699772E+09 | 0.509603E+09 | 0.193480E+10 | 0.591303E+09 |
March | 0.102801E+10 | 0.434634E+09 | 0.593375E+09 | 0.166378E+10 | 0.537131E+09 |
April | 0.676479E+09 | 0.118628E+09 | 0.557850E+09 | 0.120633E+10 | 0.340219E+09 |
May | 0.560158E+09 | 12118880.25 | 0.548039E+09 | 0.110179E+10 | 0.172041E+09 |
June | 0.516834E+09 | 975352.47 | 0.515859E+09 | 0.109669E+10 | 71875354.45 |
July | 0.571836E+09 | 5300413.59 | 0.566535E+09 | 0.126949E+10 | 0.105846E+09 |
August | 0.649015E+09 | 54767413.66 | 0.594248E+09 | 0.136239E+10 | 75018144.76 |
September | 0.804025E+09 | 0.197028E+09 | 0.606997E+09 | 0.168882E+10 | 0.134499E+09 |
October | 0.114255E+10 | 0.536050E+09 | 0.606501E+09 | 0.212732E+10 | 0.237320E+09 |
November | 0.125804E+10 | 0.702124E+09 | 0.555913E+09 | 0.209844E+10 | 0.408637E+09 |
December | 0.142638E+10 | 0.899682E+09 | 0.526702E+09 | 0.220990E+10 | 0.681890E+09 |
Annual Sum or Average | 0.113228E+11 | 0.462265E+10 | 0.670013E+10 | 0.200026E+11 | 0.411967E+10 |
Minimum of Months | 0.516834E+09 | 975352.47 | 0.509603E+09 | 0.109669E+10 | 71875354.45 |
Maximum of Months | 0.148008E+10 | 0.961575E+09 | 0.606997E+09 | 0.224284E+10 | 0.763886E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.148008E+10 | 0.961576E+09 | 0.518506E+09 | 0.224285E+10 | 0.763886E+09 |
February | 0.120938E+10 | 0.699773E+09 | 0.509603E+09 | 0.193481E+10 | 0.591303E+09 |
March | 0.102801E+10 | 0.434635E+09 | 0.593376E+09 | 0.166378E+10 | 0.537131E+09 |
April | 0.676479E+09 | 0.118628E+09 | 0.557851E+09 | 0.120634E+10 | 0.340219E+09 |
May | 0.560158E+09 | 12118894.79 | 0.548040E+09 | 0.110179E+10 | 0.172041E+09 |
June | 0.516835E+09 | 975353.64 | 0.515859E+09 | 0.109669E+10 | 71875439.93 |
July | 0.571836E+09 | 5300419.95 | 0.566536E+09 | 0.126949E+10 | 0.105846E+09 |
August | 0.649016E+09 | 54767479.38 | 0.594248E+09 | 0.136240E+10 | 75018245.26 |
September | 0.804025E+09 | 0.197028E+09 | 0.606997E+09 | 0.168882E+10 | 0.134499E+09 |
October | 0.114255E+10 | 0.536050E+09 | 0.606502E+09 | 0.212732E+10 | 0.237320E+09 |
November | 0.125804E+10 | 0.702124E+09 | 0.555914E+09 | 0.209844E+10 | 0.408638E+09 |
December | 0.142639E+10 | 0.899683E+09 | 0.526702E+09 | 0.220991E+10 | 0.681890E+09 |
Annual Sum or Average | 0.113228E+11 | 0.462266E+10 | 0.670013E+10 | 0.200026E+11 | 0.411967E+10 |
Minimum of Months | 0.516835E+09 | 975353.64 | 0.509603E+09 | 0.109669E+10 | 71875439.93 |
Maximum of Months | 0.148008E+10 | 0.961576E+09 | 0.606997E+09 | 0.224285E+10 | 0.763886E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.148008E+10 | 0.961575E+09 | 0.518506E+09 | 0.224284E+10 | 0.763886E+09 |
February | 0.120937E+10 | 0.699772E+09 | 0.509603E+09 | 0.193480E+10 | 0.591303E+09 |
March | 0.102801E+10 | 0.434634E+09 | 0.593375E+09 | 0.166378E+10 | 0.537131E+09 |
April | 0.676479E+09 | 0.118628E+09 | 0.557850E+09 | 0.120633E+10 | 0.340219E+09 |
May | 0.560158E+09 | 12118880.25 | 0.548039E+09 | 0.110179E+10 | 0.172041E+09 |
June | 0.516834E+09 | 975352.47 | 0.515859E+09 | 0.109669E+10 | 71875354.45 |
July | 0.571836E+09 | 5300413.59 | 0.566535E+09 | 0.126949E+10 | 0.105846E+09 |
August | 0.649015E+09 | 54767413.66 | 0.594248E+09 | 0.136239E+10 | 75018144.76 |
September | 0.804025E+09 | 0.197028E+09 | 0.606997E+09 | 0.168882E+10 | 0.134499E+09 |
October | 0.114255E+10 | 0.536050E+09 | 0.606501E+09 | 0.212732E+10 | 0.237320E+09 |
November | 0.125804E+10 | 0.702124E+09 | 0.555913E+09 | 0.209844E+10 | 0.408637E+09 |
December | 0.142638E+10 | 0.899682E+09 | 0.526702E+09 | 0.220990E+10 | 0.681890E+09 |
Annual Sum or Average | 0.113228E+11 | 0.462265E+10 | 0.670013E+10 | 0.200026E+11 | 0.411967E+10 |
Minimum of Months | 0.516834E+09 | 975352.47 | 0.509603E+09 | 0.109669E+10 | 71875354.45 |
Maximum of Months | 0.148008E+10 | 0.961575E+09 | 0.606997E+09 | 0.224284E+10 | 0.763886E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.148002E+10 | 0.961538E+09 | 0.518485E+09 | 0.224276E+10 | 0.763855E+09 |
February | 0.120933E+10 | 0.699744E+09 | 0.509583E+09 | 0.193473E+10 | 0.591279E+09 |
March | 0.102797E+10 | 0.434617E+09 | 0.593352E+09 | 0.166372E+10 | 0.537110E+09 |
April | 0.676452E+09 | 0.118624E+09 | 0.557828E+09 | 0.120629E+10 | 0.340206E+09 |
May | 0.560136E+09 | 12118406.35 | 0.548018E+09 | 0.110175E+10 | 0.172034E+09 |
June | 0.516814E+09 | 975314.33 | 0.515838E+09 | 0.109664E+10 | 71872543.03 |
July | 0.571813E+09 | 5300206.32 | 0.566513E+09 | 0.126943E+10 | 0.105842E+09 |
August | 0.648989E+09 | 54765272.00 | 0.594224E+09 | 0.136234E+10 | 75015221.69 |
September | 0.803993E+09 | 0.197020E+09 | 0.606973E+09 | 0.168875E+10 | 0.134493E+09 |
October | 0.114251E+10 | 0.536029E+09 | 0.606477E+09 | 0.212723E+10 | 0.237311E+09 |
November | 0.125799E+10 | 0.702096E+09 | 0.555891E+09 | 0.209835E+10 | 0.408621E+09 |
December | 0.142633E+10 | 0.899647E+09 | 0.526681E+09 | 0.220982E+10 | 0.681862E+09 |
Annual Sum or Average | 0.113223E+11 | 0.462247E+10 | 0.669986E+10 | 0.200018E+11 | 0.411950E+10 |
Minimum of Months | 0.516814E+09 | 975314.33 | 0.509583E+09 | 0.109664E+10 | 71872543.03 |
Maximum of Months | 0.148002E+10 | 0.961538E+09 | 0.606973E+09 | 0.224276E+10 | 0.763855E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.756854E+09 | 0.326291E+09 | 0.430563E+09 | 0.102055E+10 | 0.943184E+09 |
February | 0.854836E+09 | 0.386862E+09 | 0.467974E+09 | 0.127253E+10 | 0.771858E+09 |
March | 0.117859E+10 | 0.538206E+09 | 0.640384E+09 | 0.175950E+10 | 0.740054E+09 |
April | 0.125544E+10 | 0.581308E+09 | 0.674128E+09 | 0.205000E+10 | 0.503017E+09 |
May | 0.118264E+10 | 0.455262E+09 | 0.727381E+09 | 0.216428E+10 | 0.264227E+09 |
June | 0.969736E+09 | 0.272020E+09 | 0.697717E+09 | 0.186130E+10 | 0.131261E+09 |
July | 0.111989E+10 | 0.346460E+09 | 0.773433E+09 | 0.220319E+10 | 0.194644E+09 |
August | 0.111735E+10 | 0.364142E+09 | 0.753205E+09 | 0.207064E+10 | 0.188687E+09 |
September | 0.922410E+09 | 0.271989E+09 | 0.650420E+09 | 0.181038E+10 | 0.179720E+09 |
October | 0.948215E+09 | 0.369644E+09 | 0.578571E+09 | 0.170345E+10 | 0.320434E+09 |
November | 0.756947E+09 | 0.277652E+09 | 0.479294E+09 | 0.120771E+10 | 0.563255E+09 |
December | 0.783578E+09 | 0.350332E+09 | 0.433246E+09 | 0.108573E+10 | 0.925781E+09 |
Annual Sum or Average | 0.118465E+11 | 0.454017E+10 | 0.730632E+10 | 0.202093E+11 | 0.572612E+10 |
Minimum of Months | 0.756854E+09 | 0.271989E+09 | 0.430563E+09 | 0.102055E+10 | 0.131261E+09 |
Maximum of Months | 0.125544E+10 | 0.581308E+09 | 0.773433E+09 | 0.220319E+10 | 0.943184E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.756854E+09 | 0.326291E+09 | 0.430563E+09 | 0.102055E+10 | 0.943184E+09 |
February | 0.854836E+09 | 0.386862E+09 | 0.467974E+09 | 0.127253E+10 | 0.771858E+09 |
March | 0.117859E+10 | 0.538206E+09 | 0.640384E+09 | 0.175950E+10 | 0.740054E+09 |
April | 0.125544E+10 | 0.581308E+09 | 0.674128E+09 | 0.205000E+10 | 0.503017E+09 |
May | 0.118264E+10 | 0.455262E+09 | 0.727381E+09 | 0.216428E+10 | 0.264227E+09 |
June | 0.969736E+09 | 0.272020E+09 | 0.697717E+09 | 0.186130E+10 | 0.131261E+09 |
July | 0.111989E+10 | 0.346460E+09 | 0.773433E+09 | 0.220319E+10 | 0.194644E+09 |
August | 0.111735E+10 | 0.364142E+09 | 0.753205E+09 | 0.207064E+10 | 0.188687E+09 |
September | 0.922410E+09 | 0.271989E+09 | 0.650420E+09 | 0.181038E+10 | 0.179720E+09 |
October | 0.948215E+09 | 0.369644E+09 | 0.578571E+09 | 0.170345E+10 | 0.320434E+09 |
November | 0.756947E+09 | 0.277652E+09 | 0.479294E+09 | 0.120771E+10 | 0.563255E+09 |
December | 0.783578E+09 | 0.350332E+09 | 0.433246E+09 | 0.108573E+10 | 0.925781E+09 |
Annual Sum or Average | 0.118465E+11 | 0.454017E+10 | 0.730632E+10 | 0.202093E+11 | 0.572612E+10 |
Minimum of Months | 0.756854E+09 | 0.271989E+09 | 0.430563E+09 | 0.102055E+10 | 0.131261E+09 |
Maximum of Months | 0.125544E+10 | 0.581308E+09 | 0.773433E+09 | 0.220319E+10 | 0.943184E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.756840E+09 | 0.326285E+09 | 0.430555E+09 | 0.102053E+10 | 0.943167E+09 |
February | 0.854820E+09 | 0.386855E+09 | 0.467965E+09 | 0.127251E+10 | 0.771844E+09 |
March | 0.117857E+10 | 0.538196E+09 | 0.640372E+09 | 0.175947E+10 | 0.740041E+09 |
April | 0.125541E+10 | 0.581297E+09 | 0.674116E+09 | 0.204996E+10 | 0.503008E+09 |
May | 0.118262E+10 | 0.455254E+09 | 0.727367E+09 | 0.216424E+10 | 0.264222E+09 |
June | 0.969719E+09 | 0.272015E+09 | 0.697704E+09 | 0.186127E+10 | 0.131258E+09 |
July | 0.111987E+10 | 0.346454E+09 | 0.773419E+09 | 0.220315E+10 | 0.194641E+09 |
August | 0.111733E+10 | 0.364135E+09 | 0.753192E+09 | 0.207060E+10 | 0.188684E+09 |
September | 0.922393E+09 | 0.271985E+09 | 0.650408E+09 | 0.181034E+10 | 0.179717E+09 |
October | 0.948198E+09 | 0.369637E+09 | 0.578561E+09 | 0.170342E+10 | 0.320428E+09 |
November | 0.756933E+09 | 0.277647E+09 | 0.479285E+09 | 0.120768E+10 | 0.563244E+09 |
December | 0.783563E+09 | 0.350325E+09 | 0.433238E+09 | 0.108571E+10 | 0.925764E+09 |
Annual Sum or Average | 0.118463E+11 | 0.454008E+10 | 0.730618E+10 | 0.202089E+11 | 0.572602E+10 |
Minimum of Months | 0.756840E+09 | 0.271985E+09 | 0.430555E+09 | 0.102053E+10 | 0.131258E+09 |
Maximum of Months | 0.125541E+10 | 0.581297E+09 | 0.773419E+09 | 0.220315E+10 | 0.943167E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.157456E+10 | 0.00 | 0.157456E+10 | 0.171375E+10 | 0.337504E+10 |
February | 0.168338E+10 | 0.00 | 0.168338E+10 | 0.226806E+10 | 0.255041E+10 |
March | 0.222264E+10 | 0.00 | 0.222264E+10 | 0.294253E+10 | 0.239119E+10 |
April | 0.241023E+10 | 10827034.34 | 0.239941E+10 | 0.392063E+10 | 0.153628E+10 |
May | 0.284411E+10 | 0.127224E+09 | 0.271689E+10 | 0.557420E+10 | 0.856139E+09 |
June | 0.294012E+10 | 0.211697E+09 | 0.272842E+10 | 0.621127E+10 | 0.385428E+09 |
July | 0.307447E+10 | 0.150655E+09 | 0.292382E+10 | 0.682978E+10 | 0.551109E+09 |
August | 0.272095E+10 | 25025263.67 | 0.269592E+10 | 0.576016E+10 | 0.362091E+09 |
September | 0.233595E+10 | 184795.28 | 0.233576E+10 | 0.515278E+10 | 0.599685E+09 |
October | 0.202218E+10 | 0.00 | 0.202218E+10 | 0.392644E+10 | 0.963650E+09 |
November | 0.170158E+10 | 0.00 | 0.170158E+10 | 0.269569E+10 | 0.174362E+10 |
December | 0.155743E+10 | 0.00 | 0.155743E+10 | 0.189159E+10 | 0.288711E+10 |
Annual Sum or Average | 0.270876E+11 | 0.525613E+09 | 0.265620E+11 | 0.488869E+11 | 0.182018E+11 |
Minimum of Months | 0.155743E+10 | 0.00 | 0.155743E+10 | 0.171375E+10 | 0.362091E+09 |
Maximum of Months | 0.307447E+10 | 0.211697E+09 | 0.292382E+10 | 0.682978E+10 | 0.337504E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.252750E+10 | 0.121083E+10 | 0.131667E+10 | 0.347592E+10 | 0.218205E+10 |
February | 0.263600E+10 | 0.122021E+10 | 0.141579E+10 | 0.391223E+10 | 0.164851E+10 |
March | 0.356317E+10 | 0.168452E+10 | 0.187866E+10 | 0.525706E+10 | 0.153878E+10 |
April | 0.374221E+10 | 0.166976E+10 | 0.207245E+10 | 0.618047E+10 | 0.106295E+10 |
May | 0.365829E+10 | 0.145681E+10 | 0.220147E+10 | 0.664533E+10 | 0.559058E+09 |
June | 0.349431E+10 | 0.134214E+10 | 0.215217E+10 | 0.668691E+10 | 0.255455E+09 |
July | 0.371012E+10 | 0.133795E+10 | 0.237217E+10 | 0.735562E+10 | 0.374687E+09 |
August | 0.339258E+10 | 0.113441E+10 | 0.225817E+10 | 0.655085E+10 | 0.238772E+09 |
September | 0.316516E+10 | 0.114422E+10 | 0.202094E+10 | 0.618809E+10 | 0.414983E+09 |
October | 0.301052E+10 | 0.129651E+10 | 0.171400E+10 | 0.545099E+10 | 0.660029E+09 |
November | 0.236461E+10 | 0.942862E+09 | 0.142175E+10 | 0.383566E+10 | 0.112077E+10 |
December | 0.197376E+10 | 0.696833E+09 | 0.127693E+10 | 0.280254E+10 | 0.185617E+10 |
Annual Sum or Average | 0.372382E+11 | 0.151370E+11 | 0.221012E+11 | 0.643417E+11 | 0.119122E+11 |
Minimum of Months | 0.197376E+10 | 0.696833E+09 | 0.127693E+10 | 0.280254E+10 | 0.238772E+09 |
Maximum of Months | 0.374221E+10 | 0.168452E+10 | 0.237217E+10 | 0.735562E+10 | 0.218205E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.740032E+10 | 0.480782E+10 | 0.259250E+10 | 0.111056E+11 | 0.370309E+10 |
February | 0.604681E+10 | 0.349882E+10 | 0.254799E+10 | 0.959262E+10 | 0.282631E+10 |
March | 0.513999E+10 | 0.217315E+10 | 0.296684E+10 | 0.825295E+10 | 0.258753E+10 |
April | 0.338236E+10 | 0.593135E+09 | 0.278922E+10 | 0.602060E+10 | 0.168127E+10 |
May | 0.280076E+10 | 60593741.27 | 0.274016E+10 | 0.551160E+10 | 0.835622E+09 |
June | 0.258414E+10 | 4876709.21 | 0.257927E+10 | 0.551365E+10 | 0.378408E+09 |
July | 0.285915E+10 | 26501779.27 | 0.283264E+10 | 0.640179E+10 | 0.539539E+09 |
August | 0.324504E+10 | 0.273834E+09 | 0.297120E+10 | 0.687509E+10 | 0.386579E+09 |
September | 0.402008E+10 | 0.985129E+09 | 0.303495E+10 | 0.839606E+10 | 0.682975E+09 |
October | 0.571269E+10 | 0.268022E+10 | 0.303247E+10 | 0.105307E+11 | 0.122765E+10 |
November | 0.629012E+10 | 0.351058E+10 | 0.277954E+10 | 0.103884E+11 | 0.200676E+10 |
December | 0.713184E+10 | 0.449836E+10 | 0.263348E+10 | 0.109667E+11 | 0.328171E+10 |
Annual Sum or Average | 0.566133E+11 | 0.231130E+11 | 0.335003E+11 | 0.995559E+11 | 0.201374E+11 |
Minimum of Months | 0.258414E+10 | 4876709.21 | 0.254799E+10 | 0.551160E+10 | 0.378408E+09 |
Maximum of Months | 0.740032E+10 | 0.480782E+10 | 0.303495E+10 | 0.111056E+11 | 0.370309E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.227054E+10 | 0.978862E+09 | 0.129168E+10 | 0.320596E+10 | 0.239757E+10 |
February | 0.256448E+10 | 0.116057E+10 | 0.140391E+10 | 0.396884E+10 | 0.190672E+10 |
March | 0.353573E+10 | 0.161460E+10 | 0.192113E+10 | 0.542180E+10 | 0.185408E+10 |
April | 0.376627E+10 | 0.174391E+10 | 0.202236E+10 | 0.629133E+10 | 0.129529E+10 |
May | 0.354789E+10 | 0.136577E+10 | 0.218212E+10 | 0.651876E+10 | 0.725334E+09 |
June | 0.290918E+10 | 0.816051E+09 | 0.209313E+10 | 0.568001E+10 | 0.329439E+09 |
July | 0.335965E+10 | 0.103937E+10 | 0.232028E+10 | 0.674855E+10 | 0.475073E+09 |
August | 0.335201E+10 | 0.109241E+10 | 0.225959E+10 | 0.642935E+10 | 0.360078E+09 |
September | 0.276720E+10 | 0.815960E+09 | 0.195124E+10 | 0.548706E+10 | 0.476855E+09 |
October | 0.284462E+10 | 0.110892E+10 | 0.173570E+10 | 0.519394E+10 | 0.818686E+09 |
November | 0.227082E+10 | 0.832949E+09 | 0.143787E+10 | 0.377784E+10 | 0.132762E+10 |
December | 0.235071E+10 | 0.105098E+10 | 0.129972E+10 | 0.348183E+10 | 0.212075E+10 |
Annual Sum or Average | 0.355391E+11 | 0.136204E+11 | 0.219187E+11 | 0.622053E+11 | 0.140875E+11 |
Minimum of Months | 0.227054E+10 | 0.815960E+09 | 0.129168E+10 | 0.320596E+10 | 0.329439E+09 |
Maximum of Months | 0.376627E+10 | 0.174391E+10 | 0.232028E+10 | 0.674855E+10 | 0.239757E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.157456E+10 | 0.00 | 0.157456E+10 | 0.177632E+10 | 0.313552E+10 |
February | 0.168338E+10 | 0.00 | 0.168338E+10 | 0.228777E+10 | 0.241113E+10 |
March | 0.222264E+10 | 0.00 | 0.222264E+10 | 0.291990E+10 | 0.230579E+10 |
April | 0.241023E+10 | 10827034.34 | 0.239941E+10 | 0.386135E+10 | 0.152115E+10 |
May | 0.284411E+10 | 0.127224E+09 | 0.271689E+10 | 0.547901E+10 | 0.886756E+09 |
June | 0.294012E+10 | 0.211697E+09 | 0.272842E+10 | 0.609458E+10 | 0.407307E+09 |
July | 0.307447E+10 | 0.150655E+09 | 0.292382E+10 | 0.670581E+10 | 0.588859E+09 |
August | 0.272095E+10 | 25025263.67 | 0.269592E+10 | 0.566503E+10 | 0.385718E+09 |
September | 0.233595E+10 | 184795.28 | 0.233576E+10 | 0.504620E+10 | 0.611508E+09 |
October | 0.202218E+10 | 0.00 | 0.202218E+10 | 0.387172E+10 | 0.957734E+09 |
November | 0.170158E+10 | 0.00 | 0.170158E+10 | 0.269897E+10 | 0.163382E+10 |
December | 0.155743E+10 | 0.00 | 0.155743E+10 | 0.193296E+10 | 0.269833E+10 |
Annual Sum or Average | 0.270876E+11 | 0.525613E+09 | 0.265620E+11 | 0.483396E+11 | 0.175436E+11 |
Minimum of Months | 0.155743E+10 | 0.00 | 0.155743E+10 | 0.177632E+10 | 0.385718E+09 |
Maximum of Months | 0.307447E+10 | 0.211697E+09 | 0.292382E+10 | 0.670581E+10 | 0.313552E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.252750E+10 | 0.121083E+10 | 0.131667E+10 | 0.351489E+10 | 0.205543E+10 |
February | 0.263600E+10 | 0.122021E+10 | 0.141579E+10 | 0.391716E+10 | 0.157366E+10 |
March | 0.356317E+10 | 0.168452E+10 | 0.187866E+10 | 0.522593E+10 | 0.149796E+10 |
April | 0.374221E+10 | 0.166976E+10 | 0.207245E+10 | 0.612577E+10 | 0.105597E+10 |
May | 0.365829E+10 | 0.145681E+10 | 0.220147E+10 | 0.656821E+10 | 0.578567E+09 |
June | 0.349431E+10 | 0.134214E+10 | 0.215217E+10 | 0.660232E+10 | 0.267818E+09 |
July | 0.371012E+10 | 0.133795E+10 | 0.237217E+10 | 0.726936E+10 | 0.396159E+09 |
August | 0.339258E+10 | 0.113441E+10 | 0.225817E+10 | 0.647728E+10 | 0.251597E+09 |
September | 0.316516E+10 | 0.114422E+10 | 0.202094E+10 | 0.611200E+10 | 0.421624E+09 |
October | 0.301052E+10 | 0.129651E+10 | 0.171400E+10 | 0.540312E+10 | 0.657640E+09 |
November | 0.236461E+10 | 0.942862E+09 | 0.142175E+10 | 0.382968E+10 | 0.106148E+10 |
December | 0.197376E+10 | 0.696833E+09 | 0.127693E+10 | 0.282433E+10 | 0.175223E+10 |
Annual Sum or Average | 0.372382E+11 | 0.151370E+11 | 0.221012E+11 | 0.638700E+11 | 0.115701E+11 |
Minimum of Months | 0.197376E+10 | 0.696833E+09 | 0.127693E+10 | 0.282433E+10 | 0.251597E+09 |
Maximum of Months | 0.374221E+10 | 0.168452E+10 | 0.237217E+10 | 0.726936E+10 | 0.205543E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.740032E+10 | 0.480782E+10 | 0.259250E+10 | 0.111492E+11 | 0.349215E+10 |
February | 0.604681E+10 | 0.349882E+10 | 0.254799E+10 | 0.959277E+10 | 0.269570E+10 |
March | 0.513999E+10 | 0.217315E+10 | 0.296684E+10 | 0.820956E+10 | 0.250442E+10 |
April | 0.338236E+10 | 0.593135E+09 | 0.278922E+10 | 0.595141E+10 | 0.166358E+10 |
May | 0.280076E+10 | 60593741.27 | 0.274016E+10 | 0.541222E+10 | 0.864262E+09 |
June | 0.258414E+10 | 4876709.21 | 0.257927E+10 | 0.539628E+10 | 0.400947E+09 |
July | 0.285915E+10 | 26501779.27 | 0.283264E+10 | 0.627559E+10 | 0.579044E+09 |
August | 0.324504E+10 | 0.273834E+09 | 0.297120E+10 | 0.677400E+10 | 0.408464E+09 |
September | 0.402008E+10 | 0.985129E+09 | 0.303495E+10 | 0.829126E+10 | 0.695148E+09 |
October | 0.571269E+10 | 0.268022E+10 | 0.303247E+10 | 0.104664E+11 | 0.121743E+10 |
November | 0.629012E+10 | 0.351058E+10 | 0.277954E+10 | 0.103747E+11 | 0.191161E+10 |
December | 0.713184E+10 | 0.449836E+10 | 0.263348E+10 | 0.109785E+11 | 0.310853E+10 |
Annual Sum or Average | 0.566133E+11 | 0.231130E+11 | 0.335003E+11 | 0.988719E+11 | 0.195413E+11 |
Minimum of Months | 0.258414E+10 | 4876709.21 | 0.254799E+10 | 0.539628E+10 | 0.400947E+09 |
Maximum of Months | 0.740032E+10 | 0.480782E+10 | 0.303495E+10 | 0.111492E+11 | 0.349215E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.227054E+10 | 0.978862E+09 | 0.129168E+10 | 0.322863E+10 | 0.225664E+10 |
February | 0.256448E+10 | 0.116057E+10 | 0.140391E+10 | 0.396928E+10 | 0.181880E+10 |
March | 0.353573E+10 | 0.161460E+10 | 0.192113E+10 | 0.539449E+10 | 0.179233E+10 |
April | 0.376627E+10 | 0.174391E+10 | 0.202236E+10 | 0.624963E+10 | 0.127257E+10 |
May | 0.354789E+10 | 0.136577E+10 | 0.218212E+10 | 0.645911E+10 | 0.731598E+09 |
June | 0.290918E+10 | 0.816051E+09 | 0.209313E+10 | 0.561688E+10 | 0.336078E+09 |
July | 0.335965E+10 | 0.103937E+10 | 0.232028E+10 | 0.667748E+10 | 0.484503E+09 |
August | 0.335201E+10 | 0.109241E+10 | 0.225959E+10 | 0.637376E+10 | 0.367383E+09 |
September | 0.276720E+10 | 0.815960E+09 | 0.195124E+10 | 0.543231E+10 | 0.476606E+09 |
October | 0.284462E+10 | 0.110892E+10 | 0.173570E+10 | 0.516054E+10 | 0.804489E+09 |
November | 0.227082E+10 | 0.832949E+09 | 0.143787E+10 | 0.377445E+10 | 0.125826E+10 |
December | 0.235071E+10 | 0.105098E+10 | 0.129972E+10 | 0.349553E+10 | 0.200625E+10 |
Annual Sum or Average | 0.355391E+11 | 0.136204E+11 | 0.219187E+11 | 0.618321E+11 | 0.136055E+11 |
Minimum of Months | 0.227054E+10 | 0.815960E+09 | 0.129168E+10 | 0.322863E+10 | 0.336078E+09 |
Maximum of Months | 0.376627E+10 | 0.174391E+10 | 0.232028E+10 | 0.667748E+10 | 0.225664E+10 |
Report: WindowZoneSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 572.92 | 1458.83 | 587.87 | 0.00 | 587.87 | 0.00 | 0.00 |
February | 872.01 | 1225.85 | 695.84 | 0.00 | 695.84 | 0.00 | 0.00 |
March | 1052.83 | 1004.56 | 829.84 | 0.00 | 829.84 | 0.00 | 0.00 |
April | 1486.10 | 620.53 | 929.88 | 4.18 | 925.70 | 0.00 | 0.00 |
May | 2079.79 | 325.77 | 1061.87 | 47.50 | 1014.37 | 0.00 | 0.00 |
June | 2395.20 | 137.99 | 1134.31 | 81.67 | 1052.63 | 0.00 | 0.00 |
July | 2533.67 | 199.24 | 1147.88 | 56.25 | 1091.63 | 0.00 | 0.00 |
August | 2114.22 | 134.39 | 1015.89 | 9.34 | 1006.55 | 0.00 | 0.00 |
September | 1972.13 | 237.02 | 901.22 | 0.07 | 901.15 | 0.00 | 0.00 |
October | 1446.57 | 377.47 | 755.00 | 0.00 | 755.00 | 0.00 | 0.00 |
November | 1001.57 | 761.85 | 656.48 | 0.00 | 656.48 | 0.00 | 0.00 |
December | 637.38 | 1272.32 | 581.48 | 0.00 | 581.48 | 0.00 | 0.00 |
Annual Sum or Average | 1516.78 | 643.82 | 858.95 | 16.67 | 842.28 | 0.00 | 0.00 |
Minimum of Months | 572.92 | 134.39 | 581.48 | 0.00 | 581.48 | 0.00 | 0.00 |
Maximum of Months | 2533.67 | 1458.83 | 1147.88 | 81.67 | 1091.63 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1280.69 | 897.66 | 943.66 | 452.07 | 491.59 | 0.00 | 0.00 |
February | 1610.16 | 747.81 | 1089.62 | 504.39 | 585.23 | 0.00 | 0.00 |
March | 1984.56 | 591.08 | 1330.34 | 628.93 | 701.41 | 0.00 | 0.00 |
April | 2422.52 | 378.37 | 1443.76 | 644.20 | 799.56 | 0.00 | 0.00 |
May | 2510.51 | 199.73 | 1365.85 | 543.91 | 821.94 | 0.00 | 0.00 |
June | 2617.05 | 75.93 | 1348.12 | 517.80 | 830.32 | 0.00 | 0.00 |
July | 2776.02 | 109.69 | 1385.20 | 499.53 | 885.67 | 0.00 | 0.00 |
August | 2474.03 | 55.87 | 1266.65 | 423.54 | 843.11 | 0.00 | 0.00 |
September | 2410.26 | 150.82 | 1221.13 | 441.44 | 779.69 | 0.00 | 0.00 |
October | 2056.76 | 227.16 | 1124.00 | 484.06 | 639.94 | 0.00 | 0.00 |
November | 1487.93 | 444.95 | 912.28 | 363.76 | 548.52 | 0.00 | 0.00 |
December | 1030.98 | 751.09 | 736.92 | 260.17 | 476.75 | 0.00 | 0.00 |
Annual Sum or Average | 2056.82 | 384.22 | 1180.82 | 479.99 | 700.83 | 0.00 | 0.00 |
Minimum of Months | 1030.98 | 55.87 | 736.92 | 260.17 | 476.75 | 0.00 | 0.00 |
Maximum of Months | 2776.02 | 897.66 | 1443.76 | 644.20 | 885.67 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 4186.88 | 1426.00 | 2762.97 | 1795.04 | 967.93 | 0.00 | 0.00 |
February | 3998.82 | 1222.09 | 2499.52 | 1446.28 | 1053.24 | 0.00 | 0.00 |
March | 3105.90 | 1002.70 | 1919.06 | 811.36 | 1107.70 | 0.00 | 0.00 |
April | 2327.02 | 656.28 | 1304.93 | 228.83 | 1076.09 | 0.00 | 0.00 |
May | 2056.79 | 321.16 | 1045.69 | 22.62 | 1023.06 | 0.00 | 0.00 |
June | 2115.51 | 138.65 | 996.97 | 1.88 | 995.09 | 0.00 | 0.00 |
July | 2369.84 | 197.59 | 1067.49 | 9.89 | 1057.59 | 0.00 | 0.00 |
August | 2543.28 | 140.04 | 1211.56 | 102.24 | 1109.32 | 0.00 | 0.00 |
September | 3257.73 | 259.45 | 1550.96 | 380.07 | 1170.90 | 0.00 | 0.00 |
October | 3971.22 | 443.02 | 2132.88 | 1000.68 | 1132.20 | 0.00 | 0.00 |
November | 4047.88 | 788.26 | 2426.75 | 1354.40 | 1072.36 | 0.00 | 0.00 |
December | 4125.39 | 1272.93 | 2662.73 | 1679.50 | 983.23 | 0.00 | 0.00 |
Annual Sum or Average | 3171.37 | 653.16 | 1795.20 | 732.91 | 1062.29 | 0.00 | 0.00 |
Minimum of Months | 2056.79 | 138.65 | 996.97 | 1.88 | 967.93 | 0.00 | 0.00 |
Maximum of Months | 4186.88 | 1426.00 | 2762.97 | 1795.04 | 1170.90 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1143.08 | 1056.43 | 847.73 | 365.47 | 482.26 | 0.00 | 0.00 |
February | 1578.03 | 957.16 | 1060.06 | 479.74 | 580.32 | 0.00 | 0.00 |
March | 1970.76 | 828.91 | 1320.10 | 602.83 | 717.27 | 0.00 | 0.00 |
April | 2372.67 | 582.19 | 1453.04 | 672.81 | 780.24 | 0.00 | 0.00 |
May | 2424.13 | 295.95 | 1324.64 | 509.92 | 814.71 | 0.00 | 0.00 |
June | 2154.27 | 151.92 | 1122.37 | 314.84 | 807.54 | 0.00 | 0.00 |
July | 2467.72 | 218.01 | 1254.35 | 388.06 | 866.30 | 0.00 | 0.00 |
August | 2319.25 | 211.34 | 1251.50 | 407.86 | 843.64 | 0.00 | 0.00 |
September | 2095.33 | 208.01 | 1067.60 | 314.80 | 752.80 | 0.00 | 0.00 |
October | 1907.97 | 358.91 | 1062.06 | 414.02 | 648.04 | 0.00 | 0.00 |
November | 1397.80 | 651.91 | 876.09 | 321.36 | 554.74 | 0.00 | 0.00 |
December | 1216.09 | 1036.93 | 877.66 | 392.39 | 485.26 | 0.00 | 0.00 |
Annual Sum or Average | 1922.48 | 544.72 | 1126.94 | 431.90 | 695.04 | 0.00 | 0.00 |
Minimum of Months | 1143.08 | 151.92 | 847.73 | 314.80 | 482.26 | 0.00 | 0.00 |
Maximum of Months | 2467.72 | 1056.43 | 1453.04 | 672.81 | 866.30 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 639.84 | 1260.10 | 587.87 | 0.00 | 587.87 | 0.00 | 0.00 |
February | 937.53 | 1054.24 | 695.84 | 0.00 | 695.84 | 0.00 | 0.00 |
March | 1098.61 | 892.77 | 829.84 | 0.00 | 829.84 | 0.00 | 0.00 |
April | 1512.59 | 592.70 | 929.87 | 4.18 | 925.70 | 0.00 | 0.00 |
May | 2081.17 | 319.65 | 1061.87 | 47.50 | 1014.37 | 0.00 | 0.00 |
June | 2396.32 | 148.70 | 1134.30 | 81.67 | 1052.63 | 0.00 | 0.00 |
July | 2549.95 | 205.76 | 1147.88 | 56.25 | 1091.63 | 0.00 | 0.00 |
August | 2150.60 | 135.19 | 1015.89 | 9.34 | 1006.54 | 0.00 | 0.00 |
September | 1987.96 | 231.36 | 901.21 | 0.07 | 901.14 | 0.00 | 0.00 |
October | 1465.97 | 359.79 | 755.00 | 0.00 | 755.00 | 0.00 | 0.00 |
November | 1040.00 | 672.69 | 656.47 | 0.00 | 656.47 | 0.00 | 0.00 |
December | 706.24 | 1077.92 | 581.48 | 0.00 | 581.48 | 0.00 | 0.00 |
Annual Sum or Average | 1550.19 | 577.17 | 858.94 | 16.67 | 842.28 | 0.00 | 0.00 |
Minimum of Months | 639.84 | 135.19 | 581.48 | 0.00 | 581.48 | 0.00 | 0.00 |
Maximum of Months | 2549.95 | 1260.10 | 1147.88 | 81.67 | 1091.63 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1297.76 | 814.69 | 943.66 | 452.07 | 491.59 | 0.00 | 0.00 |
February | 1617.16 | 681.43 | 1089.62 | 504.38 | 585.23 | 0.00 | 0.00 |
March | 1962.76 | 574.51 | 1330.34 | 628.93 | 701.41 | 0.00 | 0.00 |
April | 2384.44 | 410.09 | 1443.75 | 644.20 | 799.56 | 0.00 | 0.00 |
May | 2481.08 | 208.73 | 1365.85 | 543.91 | 821.93 | 0.00 | 0.00 |
June | 2579.83 | 98.56 | 1348.11 | 517.80 | 830.31 | 0.00 | 0.00 |
July | 2746.27 | 139.89 | 1385.20 | 499.53 | 885.67 | 0.00 | 0.00 |
August | 2445.81 | 89.15 | 1266.64 | 423.54 | 843.11 | 0.00 | 0.00 |
September | 2387.38 | 160.10 | 1221.13 | 441.44 | 779.69 | 0.00 | 0.00 |
October | 2035.17 | 246.43 | 1124.00 | 484.06 | 639.94 | 0.00 | 0.00 |
November | 1479.81 | 432.40 | 912.27 | 363.76 | 548.51 | 0.00 | 0.00 |
December | 1046.35 | 693.02 | 736.92 | 260.17 | 476.75 | 0.00 | 0.00 |
Annual Sum or Average | 2040.26 | 377.73 | 1180.82 | 479.99 | 700.82 | 0.00 | 0.00 |
Minimum of Months | 1046.35 | 89.15 | 736.92 | 260.17 | 476.75 | 0.00 | 0.00 |
Maximum of Months | 2746.27 | 814.69 | 1443.75 | 644.20 | 885.67 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 4146.37 | 1382.58 | 2762.96 | 1795.04 | 967.93 | 0.00 | 0.00 |
February | 3965.20 | 1168.28 | 2499.51 | 1446.27 | 1053.23 | 0.00 | 0.00 |
March | 3081.30 | 966.07 | 1919.05 | 811.36 | 1107.69 | 0.00 | 0.00 |
April | 2322.76 | 648.64 | 1304.92 | 228.83 | 1076.09 | 0.00 | 0.00 |
May | 2057.79 | 311.99 | 1045.68 | 22.62 | 1023.06 | 0.00 | 0.00 |
June | 2127.18 | 145.99 | 996.97 | 1.88 | 995.09 | 0.00 | 0.00 |
July | 2390.15 | 201.44 | 1067.48 | 9.89 | 1057.59 | 0.00 | 0.00 |
August | 2566.86 | 144.33 | 1211.56 | 102.24 | 1109.32 | 0.00 | 0.00 |
September | 3239.22 | 263.49 | 1550.96 | 380.07 | 1170.89 | 0.00 | 0.00 |
October | 3931.72 | 458.35 | 2132.87 | 1000.68 | 1132.20 | 0.00 | 0.00 |
November | 4007.88 | 774.21 | 2426.74 | 1354.39 | 1072.35 | 0.00 | 0.00 |
December | 4094.51 | 1225.25 | 2662.72 | 1679.50 | 983.23 | 0.00 | 0.00 |
Annual Sum or Average | 3156.90 | 638.55 | 1795.20 | 732.91 | 1062.29 | 0.00 | 0.00 |
Minimum of Months | 2057.79 | 144.33 | 996.97 | 1.88 | 967.93 | 0.00 | 0.00 |
Maximum of Months | 4146.37 | 1382.58 | 2762.96 | 1795.04 | 1170.89 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1196.97 | 895.15 | 847.72 | 365.47 | 482.26 | 0.00 | 0.00 |
February | 1640.56 | 788.16 | 1060.05 | 479.73 | 580.32 | 0.00 | 0.00 |
March | 2024.27 | 692.23 | 1320.09 | 602.82 | 717.27 | 0.00 | 0.00 |
April | 2427.21 | 499.73 | 1453.04 | 672.80 | 780.23 | 0.00 | 0.00 |
May | 2433.83 | 270.81 | 1324.63 | 509.92 | 814.71 | 0.00 | 0.00 |
June | 2191.36 | 127.10 | 1122.37 | 314.83 | 807.53 | 0.00 | 0.00 |
July | 2519.62 | 177.37 | 1254.35 | 388.06 | 866.29 | 0.00 | 0.00 |
August | 2400.44 | 134.44 | 1251.50 | 407.86 | 843.64 | 0.00 | 0.00 |
September | 2116.92 | 183.97 | 1067.59 | 314.80 | 752.79 | 0.00 | 0.00 |
October | 1939.20 | 305.66 | 1062.06 | 414.02 | 648.03 | 0.00 | 0.00 |
November | 1457.50 | 512.20 | 876.09 | 321.35 | 554.73 | 0.00 | 0.00 |
December | 1299.97 | 791.80 | 877.65 | 392.39 | 485.26 | 0.00 | 0.00 |
Annual Sum or Average | 1972.52 | 446.71 | 1126.94 | 431.90 | 695.04 | 0.00 | 0.00 |
Minimum of Months | 1196.97 | 127.10 | 847.72 | 314.80 | 482.26 | 0.00 | 0.00 |
Maximum of Months | 2519.62 | 895.15 | 1453.04 | 672.80 | 866.29 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 663.20 | 1170.67 | 587.87 | 0.00 | 587.87 | 0.00 | 0.00 |
February | 945.67 | 996.66 | 695.84 | 0.00 | 695.84 | 0.00 | 0.00 |
March | 1090.17 | 860.88 | 829.84 | 0.00 | 829.84 | 0.00 | 0.00 |
April | 1489.72 | 586.87 | 929.87 | 4.18 | 925.70 | 0.00 | 0.00 |
May | 2045.63 | 331.08 | 1061.87 | 47.50 | 1014.37 | 0.00 | 0.00 |
June | 2351.30 | 157.14 | 1134.30 | 81.67 | 1052.63 | 0.00 | 0.00 |
July | 2503.66 | 219.85 | 1147.88 | 56.25 | 1091.63 | 0.00 | 0.00 |
August | 2115.08 | 144.01 | 1015.89 | 9.34 | 1006.54 | 0.00 | 0.00 |
September | 1946.84 | 235.92 | 901.21 | 0.07 | 901.14 | 0.00 | 0.00 |
October | 1445.53 | 357.58 | 755.00 | 0.00 | 755.00 | 0.00 | 0.00 |
November | 1041.27 | 630.33 | 656.47 | 0.00 | 656.47 | 0.00 | 0.00 |
December | 721.69 | 1007.44 | 581.48 | 0.00 | 581.48 | 0.00 | 0.00 |
Annual Sum or Average | 1532.84 | 556.30 | 858.94 | 16.67 | 842.28 | 0.00 | 0.00 |
Minimum of Months | 663.20 | 144.01 | 581.48 | 0.00 | 581.48 | 0.00 | 0.00 |
Maximum of Months | 2503.66 | 1170.67 | 1147.88 | 81.67 | 1091.63 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1312.31 | 767.41 | 943.66 | 452.07 | 491.59 | 0.00 | 0.00 |
February | 1619.20 | 650.49 | 1089.62 | 504.38 | 585.23 | 0.00 | 0.00 |
March | 1951.14 | 559.27 | 1330.34 | 628.93 | 701.41 | 0.00 | 0.00 |
April | 2363.34 | 407.39 | 1443.75 | 644.20 | 799.56 | 0.00 | 0.00 |
May | 2452.29 | 216.01 | 1365.85 | 543.91 | 821.93 | 0.00 | 0.00 |
June | 2547.19 | 103.32 | 1348.11 | 517.80 | 830.31 | 0.00 | 0.00 |
July | 2714.07 | 147.91 | 1385.20 | 499.53 | 885.67 | 0.00 | 0.00 |
August | 2418.34 | 93.94 | 1266.64 | 423.54 | 843.11 | 0.00 | 0.00 |
September | 2358.03 | 162.66 | 1221.13 | 441.44 | 779.69 | 0.00 | 0.00 |
October | 2017.30 | 245.53 | 1124.00 | 484.06 | 639.94 | 0.00 | 0.00 |
November | 1477.50 | 409.52 | 912.27 | 363.76 | 548.51 | 0.00 | 0.00 |
December | 1054.48 | 654.21 | 736.92 | 260.17 | 476.75 | 0.00 | 0.00 |
Annual Sum or Average | 2025.31 | 366.89 | 1180.82 | 479.99 | 700.82 | 0.00 | 0.00 |
Minimum of Months | 1054.48 | 93.94 | 736.92 | 260.17 | 476.75 | 0.00 | 0.00 |
Maximum of Months | 2714.07 | 767.41 | 1443.75 | 644.20 | 885.67 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 4162.65 | 1303.82 | 2762.96 | 1795.04 | 967.93 | 0.00 | 0.00 |
February | 3965.27 | 1114.30 | 2499.51 | 1446.27 | 1053.23 | 0.00 | 0.00 |
March | 3065.10 | 935.04 | 1919.05 | 811.36 | 1107.69 | 0.00 | 0.00 |
April | 2296.07 | 641.81 | 1304.92 | 228.83 | 1076.09 | 0.00 | 0.00 |
May | 2020.69 | 322.68 | 1045.68 | 22.62 | 1023.06 | 0.00 | 0.00 |
June | 2081.90 | 154.69 | 996.97 | 1.88 | 995.09 | 0.00 | 0.00 |
July | 2343.04 | 216.19 | 1067.48 | 9.89 | 1057.59 | 0.00 | 0.00 |
August | 2529.12 | 152.50 | 1211.56 | 102.24 | 1109.32 | 0.00 | 0.00 |
September | 3198.79 | 268.19 | 1550.96 | 380.07 | 1170.89 | 0.00 | 0.00 |
October | 3907.69 | 454.54 | 2132.87 | 1000.68 | 1132.20 | 0.00 | 0.00 |
November | 4002.58 | 737.51 | 2426.74 | 1354.39 | 1072.35 | 0.00 | 0.00 |
December | 4098.89 | 1160.59 | 2662.72 | 1679.50 | 983.23 | 0.00 | 0.00 |
Annual Sum or Average | 3135.21 | 619.65 | 1795.20 | 732.91 | 1062.29 | 0.00 | 0.00 |
Minimum of Months | 2020.69 | 152.50 | 996.97 | 1.88 | 967.93 | 0.00 | 0.00 |
Maximum of Months | 4162.65 | 1303.82 | 2762.96 | 1795.04 | 1170.89 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1205.43 | 842.53 | 847.72 | 365.47 | 482.26 | 0.00 | 0.00 |
February | 1640.74 | 751.82 | 1060.05 | 479.73 | 580.32 | 0.00 | 0.00 |
March | 2014.07 | 669.18 | 1320.09 | 602.82 | 717.27 | 0.00 | 0.00 |
April | 2411.12 | 490.96 | 1453.04 | 672.80 | 780.23 | 0.00 | 0.00 |
May | 2411.55 | 273.15 | 1324.63 | 509.92 | 814.71 | 0.00 | 0.00 |
June | 2167.01 | 129.66 | 1122.37 | 314.83 | 807.53 | 0.00 | 0.00 |
July | 2493.09 | 180.89 | 1254.35 | 388.06 | 866.29 | 0.00 | 0.00 |
August | 2379.69 | 137.17 | 1251.50 | 407.86 | 843.64 | 0.00 | 0.00 |
September | 2095.80 | 183.88 | 1067.59 | 314.80 | 752.79 | 0.00 | 0.00 |
October | 1926.73 | 300.36 | 1062.06 | 414.02 | 648.03 | 0.00 | 0.00 |
November | 1456.19 | 485.44 | 876.09 | 321.35 | 554.73 | 0.00 | 0.00 |
December | 1305.08 | 749.05 | 877.65 | 392.39 | 485.26 | 0.00 | 0.00 |
Annual Sum or Average | 1960.68 | 431.43 | 1126.94 | 431.90 | 695.04 | 0.00 | 0.00 |
Minimum of Months | 1205.43 | 129.66 | 847.72 | 314.80 | 482.26 | 0.00 | 0.00 |
Maximum of Months | 2493.09 | 842.53 | 1453.04 | 672.80 | 866.29 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.153452E+10 | 0.390732E+10 | 0.157456E+10 | 0.00 | 0.157456E+10 | 0.00 | 0.00 |
February | 0.210958E+10 | 0.296556E+10 | 0.168338E+10 | 0.00 | 0.168338E+10 | 0.00 | 0.00 |
March | 0.281990E+10 | 0.269062E+10 | 0.222265E+10 | 0.00 | 0.222265E+10 | 0.00 | 0.00 |
April | 0.385197E+10 | 0.160842E+10 | 0.241024E+10 | 10827072.79 | 0.239941E+10 | 0.00 | 0.00 |
May | 0.557052E+10 | 0.872536E+09 | 0.284412E+10 | 0.127224E+09 | 0.271690E+10 | 0.00 | 0.00 |
June | 0.620836E+10 | 0.357682E+09 | 0.294013E+10 | 0.211698E+09 | 0.272843E+10 | 0.00 | 0.00 |
July | 0.678619E+10 | 0.533651E+09 | 0.307448E+10 | 0.150656E+09 | 0.292383E+10 | 0.00 | 0.00 |
August | 0.566273E+10 | 0.359959E+09 | 0.272096E+10 | 25025352.54 | 0.269593E+10 | 0.00 | 0.00 |
September | 0.511177E+10 | 0.614346E+09 | 0.233596E+10 | 184795.93 | 0.233577E+10 | 0.00 | 0.00 |
October | 0.387449E+10 | 0.101102E+10 | 0.202219E+10 | 0.00 | 0.202219E+10 | 0.00 | 0.00 |
November | 0.259606E+10 | 0.197472E+10 | 0.170159E+10 | 0.00 | 0.170159E+10 | 0.00 | 0.00 |
December | 0.170717E+10 | 0.340778E+10 | 0.155744E+10 | 0.00 | 0.155744E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.478332E+11 | 0.203036E+11 | 0.270877E+11 | 0.525615E+09 | 0.265621E+11 | 0.00 | 0.00 |
Minimum of Months | 0.153452E+10 | 0.357682E+09 | 0.155744E+10 | 0.00 | 0.155744E+10 | 0.00 | 0.00 |
Maximum of Months | 0.678619E+10 | 0.390732E+10 | 0.307448E+10 | 0.211698E+09 | 0.292383E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.343020E+10 | 0.240428E+10 | 0.252751E+10 | 0.121083E+10 | 0.131668E+10 | 0.00 | 0.00 |
February | 0.389530E+10 | 0.180910E+10 | 0.263601E+10 | 0.122021E+10 | 0.141579E+10 | 0.00 | 0.00 |
March | 0.531545E+10 | 0.158314E+10 | 0.356319E+10 | 0.168452E+10 | 0.187867E+10 | 0.00 | 0.00 |
April | 0.627917E+10 | 0.980740E+09 | 0.374222E+10 | 0.166976E+10 | 0.207246E+10 | 0.00 | 0.00 |
May | 0.672416E+10 | 0.534964E+09 | 0.365830E+10 | 0.145682E+10 | 0.220148E+10 | 0.00 | 0.00 |
June | 0.678340E+10 | 0.196801E+09 | 0.349432E+10 | 0.134215E+10 | 0.215218E+10 | 0.00 | 0.00 |
July | 0.743530E+10 | 0.293802E+09 | 0.371013E+10 | 0.133795E+10 | 0.237218E+10 | 0.00 | 0.00 |
August | 0.662644E+10 | 0.149649E+09 | 0.339260E+10 | 0.113441E+10 | 0.225818E+10 | 0.00 | 0.00 |
September | 0.624739E+10 | 0.390921E+09 | 0.316518E+10 | 0.114422E+10 | 0.202095E+10 | 0.00 | 0.00 |
October | 0.550884E+10 | 0.608412E+09 | 0.301053E+10 | 0.129652E+10 | 0.171401E+10 | 0.00 | 0.00 |
November | 0.385671E+10 | 0.115330E+10 | 0.236462E+10 | 0.942866E+09 | 0.142175E+10 | 0.00 | 0.00 |
December | 0.276138E+10 | 0.201173E+10 | 0.197377E+10 | 0.696836E+09 | 0.127693E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.648637E+11 | 0.121168E+11 | 0.372384E+11 | 0.151371E+11 | 0.221013E+11 | 0.00 | 0.00 |
Minimum of Months | 0.276138E+10 | 0.149649E+09 | 0.197377E+10 | 0.696836E+09 | 0.127693E+10 | 0.00 | 0.00 |
Maximum of Months | 0.743530E+10 | 0.240428E+10 | 0.374222E+10 | 0.168452E+10 | 0.237218E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.112141E+11 | 0.381940E+10 | 0.740035E+10 | 0.480784E+10 | 0.259251E+10 | 0.00 | 0.00 |
February | 0.967394E+10 | 0.295649E+10 | 0.604683E+10 | 0.349883E+10 | 0.254799E+10 | 0.00 | 0.00 |
March | 0.831884E+10 | 0.268563E+10 | 0.514001E+10 | 0.217315E+10 | 0.296685E+10 | 0.00 | 0.00 |
April | 0.603163E+10 | 0.170108E+10 | 0.338237E+10 | 0.593137E+09 | 0.278923E+10 | 0.00 | 0.00 |
May | 0.550891E+10 | 0.860199E+09 | 0.280077E+10 | 60593956.44 | 0.274018E+10 | 0.00 | 0.00 |
June | 0.548339E+10 | 0.359374E+09 | 0.258415E+10 | 4876726.53 | 0.257927E+10 | 0.00 | 0.00 |
July | 0.634738E+10 | 0.529226E+09 | 0.285916E+10 | 26501873.38 | 0.283265E+10 | 0.00 | 0.00 |
August | 0.681192E+10 | 0.375088E+09 | 0.324505E+10 | 0.273835E+09 | 0.297122E+10 | 0.00 | 0.00 |
September | 0.844404E+10 | 0.672488E+09 | 0.402009E+10 | 0.985132E+09 | 0.303496E+10 | 0.00 | 0.00 |
October | 0.106365E+11 | 0.118659E+10 | 0.571271E+10 | 0.268023E+10 | 0.303248E+10 | 0.00 | 0.00 |
November | 0.104921E+11 | 0.204317E+10 | 0.629014E+10 | 0.351059E+10 | 0.277955E+10 | 0.00 | 0.00 |
December | 0.110494E+11 | 0.340942E+10 | 0.713187E+10 | 0.449838E+10 | 0.263349E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.100012E+12 | 0.205982E+11 | 0.566135E+11 | 0.231131E+11 | 0.335004E+11 | 0.00 | 0.00 |
Minimum of Months | 0.548339E+10 | 0.359374E+09 | 0.258415E+10 | 4876726.53 | 0.254799E+10 | 0.00 | 0.00 |
Maximum of Months | 0.112141E+11 | 0.381940E+10 | 0.740035E+10 | 0.480784E+10 | 0.303496E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.306162E+10 | 0.282954E+10 | 0.227055E+10 | 0.978866E+09 | 0.129168E+10 | 0.00 | 0.00 |
February | 0.381758E+10 | 0.231556E+10 | 0.256449E+10 | 0.116058E+10 | 0.140391E+10 | 0.00 | 0.00 |
March | 0.527848E+10 | 0.222015E+10 | 0.353575E+10 | 0.161461E+10 | 0.192114E+10 | 0.00 | 0.00 |
April | 0.614996E+10 | 0.150904E+10 | 0.376629E+10 | 0.174391E+10 | 0.202237E+10 | 0.00 | 0.00 |
May | 0.649279E+10 | 0.792676E+09 | 0.354791E+10 | 0.136578E+10 | 0.218213E+10 | 0.00 | 0.00 |
June | 0.558387E+10 | 0.393780E+09 | 0.290919E+10 | 0.816055E+09 | 0.209314E+10 | 0.00 | 0.00 |
July | 0.660954E+10 | 0.583929E+09 | 0.335966E+10 | 0.103937E+10 | 0.232029E+10 | 0.00 | 0.00 |
August | 0.621187E+10 | 0.566059E+09 | 0.335202E+10 | 0.109242E+10 | 0.225960E+10 | 0.00 | 0.00 |
September | 0.543109E+10 | 0.539157E+09 | 0.276721E+10 | 0.815963E+09 | 0.195125E+10 | 0.00 | 0.00 |
October | 0.511031E+10 | 0.961297E+09 | 0.284463E+10 | 0.110892E+10 | 0.173570E+10 | 0.00 | 0.00 |
November | 0.362310E+10 | 0.168975E+10 | 0.227083E+10 | 0.832952E+09 | 0.143787E+10 | 0.00 | 0.00 |
December | 0.325718E+10 | 0.277733E+10 | 0.235072E+10 | 0.105099E+10 | 0.129973E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.606274E+11 | 0.171783E+11 | 0.355392E+11 | 0.136204E+11 | 0.219188E+11 | 0.00 | 0.00 |
Minimum of Months | 0.306162E+10 | 0.393780E+09 | 0.227055E+10 | 0.815963E+09 | 0.129168E+10 | 0.00 | 0.00 |
Maximum of Months | 0.660954E+10 | 0.282954E+10 | 0.376629E+10 | 0.174391E+10 | 0.232029E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.171375E+10 | 0.337504E+10 | 0.157456E+10 | 0.00 | 0.157456E+10 | 0.00 | 0.00 |
February | 0.226806E+10 | 0.255041E+10 | 0.168338E+10 | 0.00 | 0.168338E+10 | 0.00 | 0.00 |
March | 0.294253E+10 | 0.239119E+10 | 0.222264E+10 | 0.00 | 0.222264E+10 | 0.00 | 0.00 |
April | 0.392063E+10 | 0.153628E+10 | 0.241023E+10 | 10827034.34 | 0.239941E+10 | 0.00 | 0.00 |
May | 0.557420E+10 | 0.856139E+09 | 0.284411E+10 | 0.127224E+09 | 0.271689E+10 | 0.00 | 0.00 |
June | 0.621127E+10 | 0.385428E+09 | 0.294012E+10 | 0.211697E+09 | 0.272842E+10 | 0.00 | 0.00 |
July | 0.682978E+10 | 0.551109E+09 | 0.307447E+10 | 0.150655E+09 | 0.292382E+10 | 0.00 | 0.00 |
August | 0.576016E+10 | 0.362091E+09 | 0.272095E+10 | 25025263.67 | 0.269592E+10 | 0.00 | 0.00 |
September | 0.515278E+10 | 0.599685E+09 | 0.233595E+10 | 184795.28 | 0.233576E+10 | 0.00 | 0.00 |
October | 0.392644E+10 | 0.963650E+09 | 0.202218E+10 | 0.00 | 0.202218E+10 | 0.00 | 0.00 |
November | 0.269569E+10 | 0.174362E+10 | 0.170158E+10 | 0.00 | 0.170158E+10 | 0.00 | 0.00 |
December | 0.189159E+10 | 0.288711E+10 | 0.155743E+10 | 0.00 | 0.155743E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.488869E+11 | 0.182018E+11 | 0.270876E+11 | 0.525613E+09 | 0.265620E+11 | 0.00 | 0.00 |
Minimum of Months | 0.171375E+10 | 0.362091E+09 | 0.155743E+10 | 0.00 | 0.155743E+10 | 0.00 | 0.00 |
Maximum of Months | 0.682978E+10 | 0.337504E+10 | 0.307447E+10 | 0.211697E+09 | 0.292382E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.347592E+10 | 0.218205E+10 | 0.252750E+10 | 0.121083E+10 | 0.131667E+10 | 0.00 | 0.00 |
February | 0.391223E+10 | 0.164851E+10 | 0.263600E+10 | 0.122021E+10 | 0.141579E+10 | 0.00 | 0.00 |
March | 0.525706E+10 | 0.153878E+10 | 0.356317E+10 | 0.168452E+10 | 0.187866E+10 | 0.00 | 0.00 |
April | 0.618047E+10 | 0.106295E+10 | 0.374221E+10 | 0.166976E+10 | 0.207245E+10 | 0.00 | 0.00 |
May | 0.664533E+10 | 0.559058E+09 | 0.365829E+10 | 0.145681E+10 | 0.220147E+10 | 0.00 | 0.00 |
June | 0.668691E+10 | 0.255455E+09 | 0.349431E+10 | 0.134214E+10 | 0.215217E+10 | 0.00 | 0.00 |
July | 0.735562E+10 | 0.374687E+09 | 0.371012E+10 | 0.133795E+10 | 0.237217E+10 | 0.00 | 0.00 |
August | 0.655085E+10 | 0.238772E+09 | 0.339258E+10 | 0.113441E+10 | 0.225817E+10 | 0.00 | 0.00 |
September | 0.618809E+10 | 0.414983E+09 | 0.316516E+10 | 0.114422E+10 | 0.202094E+10 | 0.00 | 0.00 |
October | 0.545099E+10 | 0.660029E+09 | 0.301052E+10 | 0.129651E+10 | 0.171400E+10 | 0.00 | 0.00 |
November | 0.383566E+10 | 0.112077E+10 | 0.236461E+10 | 0.942862E+09 | 0.142175E+10 | 0.00 | 0.00 |
December | 0.280254E+10 | 0.185617E+10 | 0.197376E+10 | 0.696833E+09 | 0.127693E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.643417E+11 | 0.119122E+11 | 0.372382E+11 | 0.151370E+11 | 0.221012E+11 | 0.00 | 0.00 |
Minimum of Months | 0.280254E+10 | 0.238772E+09 | 0.197376E+10 | 0.696833E+09 | 0.127693E+10 | 0.00 | 0.00 |
Maximum of Months | 0.735562E+10 | 0.218205E+10 | 0.374221E+10 | 0.168452E+10 | 0.237217E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.111056E+11 | 0.370309E+10 | 0.740032E+10 | 0.480782E+10 | 0.259250E+10 | 0.00 | 0.00 |
February | 0.959262E+10 | 0.282631E+10 | 0.604681E+10 | 0.349882E+10 | 0.254799E+10 | 0.00 | 0.00 |
March | 0.825295E+10 | 0.258753E+10 | 0.513999E+10 | 0.217315E+10 | 0.296684E+10 | 0.00 | 0.00 |
April | 0.602060E+10 | 0.168127E+10 | 0.338236E+10 | 0.593135E+09 | 0.278922E+10 | 0.00 | 0.00 |
May | 0.551160E+10 | 0.835622E+09 | 0.280076E+10 | 60593741.27 | 0.274016E+10 | 0.00 | 0.00 |
June | 0.551365E+10 | 0.378408E+09 | 0.258414E+10 | 4876709.21 | 0.257927E+10 | 0.00 | 0.00 |
July | 0.640179E+10 | 0.539539E+09 | 0.285915E+10 | 26501779.27 | 0.283264E+10 | 0.00 | 0.00 |
August | 0.687509E+10 | 0.386579E+09 | 0.324504E+10 | 0.273834E+09 | 0.297120E+10 | 0.00 | 0.00 |
September | 0.839606E+10 | 0.682975E+09 | 0.402008E+10 | 0.985129E+09 | 0.303495E+10 | 0.00 | 0.00 |
October | 0.105307E+11 | 0.122765E+10 | 0.571269E+10 | 0.268022E+10 | 0.303247E+10 | 0.00 | 0.00 |
November | 0.103884E+11 | 0.200676E+10 | 0.629012E+10 | 0.351058E+10 | 0.277954E+10 | 0.00 | 0.00 |
December | 0.109667E+11 | 0.328171E+10 | 0.713184E+10 | 0.449836E+10 | 0.263348E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.995559E+11 | 0.201374E+11 | 0.566133E+11 | 0.231130E+11 | 0.335003E+11 | 0.00 | 0.00 |
Minimum of Months | 0.551160E+10 | 0.378408E+09 | 0.258414E+10 | 4876709.21 | 0.254799E+10 | 0.00 | 0.00 |
Maximum of Months | 0.111056E+11 | 0.370309E+10 | 0.740032E+10 | 0.480782E+10 | 0.303495E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.320596E+10 | 0.239757E+10 | 0.227054E+10 | 0.978862E+09 | 0.129168E+10 | 0.00 | 0.00 |
February | 0.396884E+10 | 0.190672E+10 | 0.256448E+10 | 0.116057E+10 | 0.140391E+10 | 0.00 | 0.00 |
March | 0.542180E+10 | 0.185408E+10 | 0.353573E+10 | 0.161460E+10 | 0.192113E+10 | 0.00 | 0.00 |
April | 0.629133E+10 | 0.129529E+10 | 0.376627E+10 | 0.174391E+10 | 0.202236E+10 | 0.00 | 0.00 |
May | 0.651876E+10 | 0.725334E+09 | 0.354789E+10 | 0.136577E+10 | 0.218212E+10 | 0.00 | 0.00 |
June | 0.568001E+10 | 0.329439E+09 | 0.290918E+10 | 0.816051E+09 | 0.209313E+10 | 0.00 | 0.00 |
July | 0.674855E+10 | 0.475073E+09 | 0.335965E+10 | 0.103937E+10 | 0.232028E+10 | 0.00 | 0.00 |
August | 0.642935E+10 | 0.360078E+09 | 0.335201E+10 | 0.109241E+10 | 0.225959E+10 | 0.00 | 0.00 |
September | 0.548706E+10 | 0.476855E+09 | 0.276720E+10 | 0.815960E+09 | 0.195124E+10 | 0.00 | 0.00 |
October | 0.519394E+10 | 0.818686E+09 | 0.284462E+10 | 0.110892E+10 | 0.173570E+10 | 0.00 | 0.00 |
November | 0.377784E+10 | 0.132762E+10 | 0.227082E+10 | 0.832949E+09 | 0.143787E+10 | 0.00 | 0.00 |
December | 0.348183E+10 | 0.212075E+10 | 0.235071E+10 | 0.105098E+10 | 0.129972E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.622053E+11 | 0.140875E+11 | 0.355391E+11 | 0.136204E+11 | 0.219187E+11 | 0.00 | 0.00 |
Minimum of Months | 0.320596E+10 | 0.329439E+09 | 0.227054E+10 | 0.815960E+09 | 0.129168E+10 | 0.00 | 0.00 |
Maximum of Months | 0.674855E+10 | 0.239757E+10 | 0.376627E+10 | 0.174391E+10 | 0.232028E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.177632E+10 | 0.313552E+10 | 0.157456E+10 | 0.00 | 0.157456E+10 | 0.00 | 0.00 |
February | 0.228777E+10 | 0.241113E+10 | 0.168338E+10 | 0.00 | 0.168338E+10 | 0.00 | 0.00 |
March | 0.291990E+10 | 0.230579E+10 | 0.222264E+10 | 0.00 | 0.222264E+10 | 0.00 | 0.00 |
April | 0.386135E+10 | 0.152115E+10 | 0.241023E+10 | 10827034.34 | 0.239941E+10 | 0.00 | 0.00 |
May | 0.547901E+10 | 0.886756E+09 | 0.284411E+10 | 0.127224E+09 | 0.271689E+10 | 0.00 | 0.00 |
June | 0.609458E+10 | 0.407307E+09 | 0.294012E+10 | 0.211697E+09 | 0.272842E+10 | 0.00 | 0.00 |
July | 0.670581E+10 | 0.588859E+09 | 0.307447E+10 | 0.150655E+09 | 0.292382E+10 | 0.00 | 0.00 |
August | 0.566503E+10 | 0.385718E+09 | 0.272095E+10 | 25025263.67 | 0.269592E+10 | 0.00 | 0.00 |
September | 0.504620E+10 | 0.611508E+09 | 0.233595E+10 | 184795.28 | 0.233576E+10 | 0.00 | 0.00 |
October | 0.387172E+10 | 0.957734E+09 | 0.202218E+10 | 0.00 | 0.202218E+10 | 0.00 | 0.00 |
November | 0.269897E+10 | 0.163382E+10 | 0.170158E+10 | 0.00 | 0.170158E+10 | 0.00 | 0.00 |
December | 0.193296E+10 | 0.269833E+10 | 0.155743E+10 | 0.00 | 0.155743E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.483396E+11 | 0.175436E+11 | 0.270876E+11 | 0.525613E+09 | 0.265620E+11 | 0.00 | 0.00 |
Minimum of Months | 0.177632E+10 | 0.385718E+09 | 0.155743E+10 | 0.00 | 0.155743E+10 | 0.00 | 0.00 |
Maximum of Months | 0.670581E+10 | 0.313552E+10 | 0.307447E+10 | 0.211697E+09 | 0.292382E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.351489E+10 | 0.205543E+10 | 0.252750E+10 | 0.121083E+10 | 0.131667E+10 | 0.00 | 0.00 |
February | 0.391716E+10 | 0.157366E+10 | 0.263600E+10 | 0.122021E+10 | 0.141579E+10 | 0.00 | 0.00 |
March | 0.522593E+10 | 0.149796E+10 | 0.356317E+10 | 0.168452E+10 | 0.187866E+10 | 0.00 | 0.00 |
April | 0.612577E+10 | 0.105597E+10 | 0.374221E+10 | 0.166976E+10 | 0.207245E+10 | 0.00 | 0.00 |
May | 0.656821E+10 | 0.578567E+09 | 0.365829E+10 | 0.145681E+10 | 0.220147E+10 | 0.00 | 0.00 |
June | 0.660232E+10 | 0.267818E+09 | 0.349431E+10 | 0.134214E+10 | 0.215217E+10 | 0.00 | 0.00 |
July | 0.726936E+10 | 0.396159E+09 | 0.371012E+10 | 0.133795E+10 | 0.237217E+10 | 0.00 | 0.00 |
August | 0.647728E+10 | 0.251597E+09 | 0.339258E+10 | 0.113441E+10 | 0.225817E+10 | 0.00 | 0.00 |
September | 0.611200E+10 | 0.421624E+09 | 0.316516E+10 | 0.114422E+10 | 0.202094E+10 | 0.00 | 0.00 |
October | 0.540312E+10 | 0.657640E+09 | 0.301052E+10 | 0.129651E+10 | 0.171400E+10 | 0.00 | 0.00 |
November | 0.382968E+10 | 0.106148E+10 | 0.236461E+10 | 0.942862E+09 | 0.142175E+10 | 0.00 | 0.00 |
December | 0.282433E+10 | 0.175223E+10 | 0.197376E+10 | 0.696833E+09 | 0.127693E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.638700E+11 | 0.115701E+11 | 0.372382E+11 | 0.151370E+11 | 0.221012E+11 | 0.00 | 0.00 |
Minimum of Months | 0.282433E+10 | 0.251597E+09 | 0.197376E+10 | 0.696833E+09 | 0.127693E+10 | 0.00 | 0.00 |
Maximum of Months | 0.726936E+10 | 0.205543E+10 | 0.374221E+10 | 0.168452E+10 | 0.237217E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.111492E+11 | 0.349215E+10 | 0.740032E+10 | 0.480782E+10 | 0.259250E+10 | 0.00 | 0.00 |
February | 0.959277E+10 | 0.269570E+10 | 0.604681E+10 | 0.349882E+10 | 0.254799E+10 | 0.00 | 0.00 |
March | 0.820956E+10 | 0.250442E+10 | 0.513999E+10 | 0.217315E+10 | 0.296684E+10 | 0.00 | 0.00 |
April | 0.595141E+10 | 0.166358E+10 | 0.338236E+10 | 0.593135E+09 | 0.278922E+10 | 0.00 | 0.00 |
May | 0.541222E+10 | 0.864262E+09 | 0.280076E+10 | 60593741.27 | 0.274016E+10 | 0.00 | 0.00 |
June | 0.539628E+10 | 0.400947E+09 | 0.258414E+10 | 4876709.21 | 0.257927E+10 | 0.00 | 0.00 |
July | 0.627559E+10 | 0.579044E+09 | 0.285915E+10 | 26501779.27 | 0.283264E+10 | 0.00 | 0.00 |
August | 0.677400E+10 | 0.408464E+09 | 0.324504E+10 | 0.273834E+09 | 0.297120E+10 | 0.00 | 0.00 |
September | 0.829126E+10 | 0.695148E+09 | 0.402008E+10 | 0.985129E+09 | 0.303495E+10 | 0.00 | 0.00 |
October | 0.104664E+11 | 0.121743E+10 | 0.571269E+10 | 0.268022E+10 | 0.303247E+10 | 0.00 | 0.00 |
November | 0.103747E+11 | 0.191161E+10 | 0.629012E+10 | 0.351058E+10 | 0.277954E+10 | 0.00 | 0.00 |
December | 0.109785E+11 | 0.310853E+10 | 0.713184E+10 | 0.449836E+10 | 0.263348E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.988719E+11 | 0.195413E+11 | 0.566133E+11 | 0.231130E+11 | 0.335003E+11 | 0.00 | 0.00 |
Minimum of Months | 0.539628E+10 | 0.400947E+09 | 0.258414E+10 | 4876709.21 | 0.254799E+10 | 0.00 | 0.00 |
Maximum of Months | 0.111492E+11 | 0.349215E+10 | 0.740032E+10 | 0.480782E+10 | 0.303495E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.322863E+10 | 0.225664E+10 | 0.227054E+10 | 0.978862E+09 | 0.129168E+10 | 0.00 | 0.00 |
February | 0.396928E+10 | 0.181880E+10 | 0.256448E+10 | 0.116057E+10 | 0.140391E+10 | 0.00 | 0.00 |
March | 0.539449E+10 | 0.179233E+10 | 0.353573E+10 | 0.161460E+10 | 0.192113E+10 | 0.00 | 0.00 |
April | 0.624963E+10 | 0.127257E+10 | 0.376627E+10 | 0.174391E+10 | 0.202236E+10 | 0.00 | 0.00 |
May | 0.645911E+10 | 0.731598E+09 | 0.354789E+10 | 0.136577E+10 | 0.218212E+10 | 0.00 | 0.00 |
June | 0.561688E+10 | 0.336078E+09 | 0.290918E+10 | 0.816051E+09 | 0.209313E+10 | 0.00 | 0.00 |
July | 0.667748E+10 | 0.484503E+09 | 0.335965E+10 | 0.103937E+10 | 0.232028E+10 | 0.00 | 0.00 |
August | 0.637376E+10 | 0.367383E+09 | 0.335201E+10 | 0.109241E+10 | 0.225959E+10 | 0.00 | 0.00 |
September | 0.543231E+10 | 0.476606E+09 | 0.276720E+10 | 0.815960E+09 | 0.195124E+10 | 0.00 | 0.00 |
October | 0.516054E+10 | 0.804489E+09 | 0.284462E+10 | 0.110892E+10 | 0.173570E+10 | 0.00 | 0.00 |
November | 0.377445E+10 | 0.125826E+10 | 0.227082E+10 | 0.832949E+09 | 0.143787E+10 | 0.00 | 0.00 |
December | 0.349553E+10 | 0.200625E+10 | 0.235071E+10 | 0.105098E+10 | 0.129972E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.618321E+11 | 0.136055E+11 | 0.355391E+11 | 0.136204E+11 | 0.219187E+11 | 0.00 | 0.00 |
Minimum of Months | 0.322863E+10 | 0.336078E+09 | 0.227054E+10 | 0.815960E+09 | 0.129168E+10 | 0.00 | 0.00 |
Maximum of Months | 0.667748E+10 | 0.225664E+10 | 0.376627E+10 | 0.174391E+10 | 0.232028E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 19.42 | 15.96 | 13.59 | 3.30 | 9.49 | 57.21 | 169.93 | 0.03 |
February | 20.87 | 16.70 | 13.89 | 5.53 | 11.19 | 68.99 | 182.59 | 0.00 |
March | 21.57 | 17.63 | 15.09 | 5.59 | 12.13 | 85.97 | 199.13 | 0.00 |
April | 24.11 | 19.68 | 17.40 | 4.69 | 15.31 | 97.05 | 212.67 | 0.01 |
May | 26.41 | 22.40 | 20.67 | 5.05 | 18.50 | 110.67 | 177.92 | 0.00 |
June | 27.68 | 24.06 | 22.67 | 3.87 | 20.33 | 120.35 | 147.07 | 0.00 |
July | 28.13 | 24.25 | 22.77 | 2.86 | 20.30 | 124.71 | 163.26 | 0.00 |
August | 27.97 | 24.38 | 23.03 | 3.45 | 20.36 | 120.27 | 145.14 | 0.08 |
September | 27.49 | 23.91 | 22.56 | 3.39 | 20.13 | 107.67 | 134.94 | 0.00 |
October | 26.35 | 22.68 | 21.10 | 3.72 | 17.49 | 81.44 | 160.40 | 0.04 |
November | 23.59 | 20.24 | 18.46 | 4.39 | 14.74 | 70.67 | 140.11 | 0.00 |
December | 20.30 | 17.47 | 15.75 | 3.70 | 12.21 | 59.50 | 147.31 | 0.00 |
Annual Sum or Average | 24.51 | 20.80 | 18.94 | 4.12 | 16.04 | 92.16 | 164.97 | 0.01 |
Minimum of Months | 19.42 | 15.96 | 13.59 | 2.86 | 9.49 | 57.21 | 134.94 | 0.00 |
Maximum of Months | 28.13 | 24.38 | 23.03 | 5.59 | 20.36 | 124.71 | 212.67 | 0.08 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 28.90 | 02-JAN-14:20 | 24.35 | 22.57 | 2.37 | 19.46 | 142.33 | 666.50 |
February | 29.40 | 11-FEB-13:00 | 24.15 | 22.20 | 4.60 | 20.75 | 178.50 | 682.00 |
March | 29.40 | 13-MAR-15:00 | 22.41 | 19.40 | 6.20 | 21.27 | 178.00 | 499.00 |
April | 32.20 | 17-APR-14:00 | 19.76 | 12.80 | 5.20 | 21.27 | 367.00 | 219.50 |
May | 34.40 | 22-MAY-12:00 | 23.24 | 18.30 | 5.70 | 25.99 | 382.50 | 457.50 |
June | 32.20 | 11-JUN-12:00 | 23.83 | 20.60 | 3.60 | 23.15 | 181.50 | 762.50 |
July | 35.60 | 29-JUL-15:00 | 24.39 | 20.00 | 3.60 | 25.66 | 281.50 | 374.50 |
August | 33.90 | 23-AUG-12:00 | 25.44 | 22.20 | 5.70 | 24.50 | 261.50 | 640.00 |
September | 32.20 | 08-SEP-14:00 | 23.42 | 20.00 | 2.10 | 21.61 | 221.50 | 576.00 |
October | 32.20 | 09-OCT-10:00 | 23.83 | 20.60 | 3.10 | 25.16 | 286.50 | 457.50 |
November | 30.00 | 17-NOV-14:00 | 22.20 | 18.90 | 4.10 | 19.35 | 178.50 | 412.50 |
December | 28.90 | 10-DEC-14:20 | 22.91 | 20.40 | 7.87 | 19.82 | 162.67 | 585.17 |
Annual Sum or Average | ||||||||
Minimum of Months | 28.90 | 19.76 | 12.80 | 2.10 | 19.35 | 142.33 | 219.50 | |
Maximum of Months | 35.60 | 25.44 | 22.57 | 7.87 | 25.99 | 382.50 | 762.50 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 9.40 | 25-JAN-04:00 | 4.59 | -1.7 | 3.10 | -7.3 | 0.00 | 0.00 |
February | 5.00 | 04-FEB-06:00 | 1.99 | -2.8 | 5.70 | -11.9 | 0.00 | 0.00 |
March | 6.70 | 16-MAR-04:00 | 4.49 | 1.70 | 4.60 | -9.2 | 0.00 | 0.00 |
April | 14.40 | 02-APR-05:49 | 13.38 | 12.70 | 1.60 | 0.69 | 0.00 | 0.00 |
May | 20.60 | 01-MAY-04:00 | 19.45 | 18.90 | 1.00 | 7.95 | 0.00 | 0.00 |
June | 22.80 | 05-JUN-14:00 | 20.57 | 19.40 | 2.10 | 18.46 | 245.00 | 55.00 |
July | 22.80 | 02-JUL-15:00 | 21.59 | 21.10 | 4.60 | 20.92 | 155.00 | 8.50 |
August | 22.20 | 12-AUG-06:00 | 21.85 | 21.70 | 2.60 | 20.40 | 65.50 | 0.00 |
September | 22.20 | 05-SEP-05:00 | 21.37 | 21.10 | 2.60 | 13.54 | 0.00 | 0.00 |
October | 21.10 | 28-OCT-02:00 | 20.29 | 20.00 | 2.60 | 8.54 | 0.00 | 0.00 |
November | 10.00 | 27-NOV-02:00 | 8.82 | 7.80 | 3.10 | -4.6 | 0.00 | 0.00 |
December | 7.80 | 15-DEC-05:40 | 5.61 | 3.13 | 6.37 | -7.8 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 5.00 | 1.99 | -2.8 | 1.00 | -11.9 | 0.00 | 0.00 | |
Maximum of Months | 22.80 | 21.85 | 21.70 | 6.37 | 20.92 | 245.00 | 55.00 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 24.83 | 02-JAN-13:00 | 28.90 | 23.30 | 1.50 | 19.87 | 151.00 | 613.50 |
February | 24.15 | 11-FEB-13:00 | 29.40 | 22.20 | 4.60 | 20.75 | 178.50 | 682.00 |
March | 23.83 | 14-MAR-09:00 | 26.70 | 22.80 | 11.30 | 19.52 | 243.50 | 478.00 |
April | 24.58 | 01-APR-15:00 | 28.30 | 23.30 | 3.60 | 16.30 | 93.50 | 759.50 |
May | 26.05 | 28-MAY-14:00 | 28.90 | 25.00 | 5.20 | 25.66 | 289.00 | 98.50 |
June | 26.06 | 28-JUN-11:00 | 28.90 | 25.00 | 1.50 | 22.98 | 404.50 | 373.50 |
July | 26.39 | 12-JUL-10:00 | 30.60 | 25.00 | 4.60 | 23.82 | 287.50 | 574.00 |
August | 26.46 | 21-AUG-15:00 | 32.20 | 24.40 | 3.60 | 24.50 | 205.50 | 366.00 |
September | 26.31 | 22-SEP-16:00 | 30.00 | 25.00 | 6.20 | 28.91 | 54.00 | 21.00 |
October | 26.52 | 01-OCT-11:00 | 29.40 | 25.60 | 6.20 | 28.43 | 283.50 | 0.00 |
November | 25.31 | 04-NOV-13:00 | 27.80 | 24.40 | 2.10 | 26.48 | 199.00 | 3.00 |
December | 24.31 | 24-DEC-14:00 | 27.20 | 23.30 | 2.10 | 23.66 | 201.50 | 114.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 23.83 | 26.70 | 22.20 | 1.50 | 16.30 | 54.00 | 0.00 | |
Maximum of Months | 26.52 | 32.20 | 25.60 | 11.30 | 28.91 | 404.50 | 759.50 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 23.30 | 02-JAN-13:00 | 28.90 | 24.83 | 1.50 | 19.87 | 151.00 | 613.50 |
February | 22.80 | 11-FEB-16:19 | 27.60 | 24.09 | 5.70 | 18.94 | 101.33 | 565.33 |
March | 22.80 | 14-MAR-09:20 | 25.57 | 23.60 | 9.63 | 22.18 | 176.17 | 527.17 |
April | 23.30 | 01-APR-14:00 | 27.80 | 24.57 | 5.70 | 15.76 | 108.00 | 831.00 |
May | 25.00 | 28-MAY-12:00 | 27.80 | 25.74 | 6.70 | 22.98 | 249.50 | 244.50 |
June | 25.00 | 06-JUN-18:00 | 27.20 | 25.59 | 3.60 | 23.99 | 17.50 | 0.00 |
July | 25.00 | 12-JUL-03:00 | 27.20 | 25.59 | 1.50 | 19.70 | 0.00 | 0.00 |
August | 25.60 | 21-AUG-11:00 | 28.90 | 26.35 | 2.60 | 23.15 | 567.00 | 173.50 |
September | 25.00 | 22-SEP-00:00 | 27.80 | 25.31 | 3.60 | 20.92 | 0.00 | 0.00 |
October | 25.60 | 01-OCT-11:00 | 29.40 | 26.52 | 6.20 | 28.43 | 283.50 | 0.00 |
November | 24.40 | 05-NOV-01:19 | 26.10 | 24.93 | 2.03 | 16.37 | 0.00 | 0.00 |
December | 23.90 | 24-DEC-08:00 | 23.90 | 23.90 | 2.60 | 17.75 | 168.50 | 167.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 22.80 | 23.90 | 23.60 | 1.50 | 15.76 | 0.00 | 0.00 | |
Maximum of Months | 25.60 | 29.40 | 26.52 | 9.63 | 28.43 | 567.00 | 831.00 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 24.73 | 28.77 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 25.06 | 35.04 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 26.11 | 42.49 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 27.63 | 49.05 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 29.20 | 48.15 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 30.41 | 45.99 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 30.92 | 49.88 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 30.58 | 45.60 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 29.50 | 40.49 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 27.97 | 35.89 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 26.40 | 29.31 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 25.21 | 26.63 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 27.83 | 39.80 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 24.73 | 26.63 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 30.92 | 49.88 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.282564E+11 | -0.272387E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.101766E+10 | 58.96 | 0.00 | 0.00 |
February | 0.254352E+11 | -0.245153E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -919936965.6 | 58.97 | 0.00 | 0.00 |
March | 0.289648E+11 | -0.279426E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.102216E+10 | 58.97 | 0.00 | 0.00 |
April | 0.251499E+11 | -0.241638E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -986074246.1 | 58.96 | 0.00 | 0.00 |
May | 0.255373E+11 | -0.245164E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.102086E+10 | 58.97 | 0.00 | 0.00 |
June | 0.243111E+11 | -0.233216E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -989542560.2 | 58.97 | 0.00 | 0.00 |
July | 0.227962E+11 | -0.217790E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.101722E+10 | 58.97 | 0.00 | 0.00 |
August | 0.251586E+11 | -0.241368E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.102178E+10 | 58.97 | 0.00 | 0.00 |
September | 0.237193E+11 | -0.227333E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -986076280.2 | 58.97 | 0.00 | 0.00 |
October | 0.256825E+11 | -0.246653E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.101715E+10 | 58.98 | 0.00 | 0.00 |
November | 0.264029E+11 | -0.254192E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -983760075.2 | 58.97 | 0.00 | 0.00 |
December | 0.272330E+11 | -0.262166E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.101644E+10 | 58.98 | 0.00 | 0.00 |
Annual Sum or Average | 0.308647E+12 | -0.296649E+12 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.119987E+11 | 58.97 | 0.00 | 0.00 |
Minimum of Months | 0.227962E+11 | -0.279426E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -0.102216E+10 | 58.96 | 0.00 | 0.00 |
Maximum of Months | 0.289648E+11 | -0.217790E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -919936965.6 | 58.98 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_1_DAYLCTRL
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 287.00 | 0.51 | 0.48 | 01-JAN-07:40 | 7161.55 | 36.22 | 275.17 | 293.50 | 1394.33 | 25.80 | 233.33 | 277.33 |
February | 304.33 | 0.51 | 0.48 | 01-FEB-08:20 | 2666.09 | 26.24 | 165.33 | 279.00 | 1088.36 | 21.44 | 176.67 | 252.33 |
March | 362.67 | 0.51 | 0.48 | 01-MAR-07:49 | 1652.04 | 20.40 | 91.33 | 329.50 | 903.41 | 21.46 | 215.83 | 295.17 |
April | 357.50 | 0.52 | 0.48 | 01-APR-07:30 | 1293.64 | 19.78 | 35.83 | 327.67 | 729.79 | 21.06 | 192.67 | 295.00 |
May | 389.00 | 0.52 | 0.48 | 01-MAY-07:19 | 1111.29 | 19.31 | 3.00 | 350.00 | 619.38 | 20.63 | 172.83 | 302.17 |
June | 388.17 | 0.54 | 0.48 | 01-JUN-07:19 | 1049.10 | 18.70 | 4.83 | 327.67 | 579.43 | 20.02 | 151.67 | 279.33 |
July | 403.83 | 0.52 | 0.48 | 01-JUL-06:00 | 1175.57 | 19.53 | 8.33 | 357.33 | 649.74 | 20.87 | 227.33 | 307.17 |
August | 348.33 | 0.52 | 0.48 | 01-AUG-07:40 | 1393.72 | 19.98 | 58.00 | 346.00 | 754.55 | 21.31 | 239.67 | 306.00 |
September | 349.67 | 0.52 | 0.48 | 01-SEP-07:19 | 1667.06 | 20.24 | 106.50 | 316.83 | 878.36 | 21.58 | 242.67 | 282.33 |
October | 323.50 | 0.52 | 0.48 | 02-OCT-08:09 | 2190.69 | 21.96 | 137.00 | 314.50 | 1079.65 | 22.13 | 247.00 | 288.33 |
November | 314.83 | 0.50 | 0.48 | 01-NOV-07:10 | 4093.04 | 31.76 | 262.00 | 293.50 | 1197.96 | 23.77 | 248.00 | 269.67 |
December | 282.67 | 0.50 | 0.48 | 01-DEC-08:39 | 6808.91 | 36.48 | 279.00 | 280.17 | 1622.00 | 27.14 | 243.67 | 262.17 |
Annual Sum or Average | 4111.50 | 0.52 | 2488.87 | 23.58 | 1426.33 | 3815.67 | 924.98 | 22.07 | 2591.33 | 3417.00 | ||
Minimum of Months | 282.67 | 0.50 | 0.48 | 1049.10 | 18.70 | 3.00 | 279.00 | 579.43 | 20.02 | 151.67 | 252.33 | |
Maximum of Months | 403.83 | 0.54 | 0.48 | 7161.55 | 36.48 | 279.00 | 357.33 | 1622.00 | 27.14 | 248.00 | 307.17 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_2_DAYLCTRL
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 287.00 | 0.54 | 0.48 | 01-JAN-07:40 | 2282.88 | 24.59 | 106.33 | 272.00 | 1198.72 | 24.41 | 145.33 | 232.83 |
February | 304.33 | 0.53 | 0.48 | 01-FEB-07:49 | 2387.49 | 23.90 | 101.83 | 263.67 | 901.86 | 22.55 | 128.50 | 230.83 |
March | 362.67 | 0.52 | 0.48 | 01-MAR-07:19 | 2273.94 | 23.34 | 99.50 | 326.00 | 1194.14 | 23.59 | 154.00 | 293.67 |
April | 357.50 | 0.52 | 0.48 | 01-APR-06:00 | 2639.95 | 23.13 | 100.00 | 327.50 | 1405.20 | 23.52 | 133.50 | 296.00 |
May | 389.00 | 0.51 | 0.48 | 01-MAY-06:10 | 2441.36 | 23.15 | 113.17 | 360.83 | 1030.63 | 22.64 | 137.17 | 315.17 |
June | 388.17 | 0.52 | 0.48 | 01-JUN-05:00 | 2373.38 | 23.62 | 122.83 | 345.17 | 1007.17 | 22.92 | 151.17 | 303.83 |
July | 403.83 | 0.51 | 0.48 | 01-JUL-06:19 | 2347.74 | 23.63 | 123.67 | 365.17 | 1033.39 | 23.07 | 188.00 | 323.67 |
August | 348.33 | 0.52 | 0.48 | 01-AUG-06:40 | 2307.73 | 23.22 | 97.83 | 348.83 | 1217.12 | 23.70 | 163.17 | 311.50 |
September | 349.67 | 0.52 | 0.48 | 01-SEP-06:49 | 2263.46 | 23.81 | 105.67 | 313.67 | 1166.57 | 24.04 | 184.33 | 275.00 |
October | 323.50 | 0.52 | 0.48 | 02-OCT-07:10 | 2236.51 | 23.93 | 98.50 | 306.00 | 1176.96 | 24.07 | 178.67 | 272.17 |
November | 314.83 | 0.52 | 0.48 | 01-NOV-06:00 | 1796.43 | 23.60 | 100.00 | 276.67 | 908.13 | 23.57 | 164.00 | 237.83 |
December | 282.67 | 0.53 | 0.48 | 01-DEC-08:39 | 1927.54 | 23.44 | 91.00 | 258.83 | 790.49 | 22.30 | 129.83 | 218.00 |
Annual Sum or Average | 4111.50 | 0.52 | 2285.92 | 23.59 | 1260.33 | 3764.33 | 1090.87 | 23.36 | 1857.67 | 3310.50 | ||
Minimum of Months | 282.67 | 0.51 | 0.48 | 1796.43 | 23.13 | 91.00 | 258.83 | 790.49 | 22.30 | 128.50 | 218.00 | |
Maximum of Months | 403.83 | 0.54 | 0.48 | 2639.95 | 24.59 | 123.67 | 365.17 | 1405.20 | 24.41 | 188.00 | 323.67 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_3_DAYLCTRL
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 287.00 | 0.57 | 0.48 | 01-JAN-09:50 | 589.89 | 16.73 | 0.00 | 253.17 | 372.69 | 18.34 | 0.00 | 168.83 |
February | 304.33 | 0.55 | 0.48 | 01-FEB-09:20 | 670.73 | 17.53 | 0.00 | 254.83 | 412.88 | 18.98 | 0.67 | 191.50 |
March | 362.67 | 0.52 | 0.48 | 01-MAR-09:30 | 801.16 | 18.66 | 0.00 | 319.00 | 483.27 | 20.02 | 29.00 | 265.00 |
April | 357.50 | 0.52 | 0.48 | 01-APR-07:30 | 955.86 | 19.47 | 0.00 | 332.67 | 567.68 | 20.73 | 115.67 | 299.83 |
May | 389.00 | 0.50 | 0.48 | 01-MAY-06:40 | 1131.37 | 20.85 | 64.17 | 369.00 | 629.95 | 22.00 | 205.50 | 336.83 |
June | 388.17 | 0.51 | 0.48 | 01-JUN-06:40 | 1201.87 | 22.15 | 115.00 | 358.67 | 642.65 | 21.05 | 196.67 | 309.33 |
July | 403.83 | 0.50 | 0.48 | 01-JUL-06:40 | 1262.13 | 21.15 | 100.83 | 376.17 | 689.64 | 22.44 | 283.50 | 341.00 |
August | 348.33 | 0.51 | 0.48 | 01-AUG-07:19 | 1139.26 | 19.94 | 23.50 | 351.83 | 641.91 | 21.24 | 202.67 | 317.00 |
September | 349.67 | 0.52 | 0.48 | 01-SEP-07:19 | 958.43 | 19.15 | 0.00 | 314.83 | 546.88 | 20.46 | 129.50 | 269.00 |
October | 323.50 | 0.54 | 0.48 | 02-OCT-11:39 | 767.08 | 18.30 | 0.00 | 297.83 | 466.25 | 19.72 | 25.50 | 236.33 |
November | 314.83 | 0.55 | 0.48 | 01-NOV-08:09 | 674.35 | 17.71 | 0.00 | 262.00 | 402.45 | 19.15 | 3.17 | 191.00 |
December | 282.67 | 0.54 | 0.48 | 01-DEC-09:09 | 641.79 | 17.44 | 0.00 | 247.50 | 392.96 | 19.01 | 0.00 | 176.33 |
Annual Sum or Average | 4111.50 | 0.53 | 923.23 | 19.26 | 303.50 | 3737.50 | 531.99 | 20.39 | 1191.83 | 3102.00 | ||
Minimum of Months | 282.67 | 0.50 | 0.48 | 589.89 | 16.73 | 0.00 | 247.50 | 372.69 | 18.34 | 0.00 | 168.83 | |
Maximum of Months | 403.83 | 0.57 | 0.48 | 1262.13 | 22.15 | 115.00 | 376.17 | 689.64 | 22.44 | 283.50 | 341.00 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_4_DAYLCTRL
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 287.00 | 0.54 | 0.48 | 01-JAN-09:39 | 1971.28 | 23.64 | 95.33 | 274.00 | 1067.92 | 23.80 | 141.33 | 232.00 |
February | 304.33 | 0.53 | 0.48 | 01-FEB-09:20 | 1815.94 | 22.10 | 75.50 | 270.17 | 920.95 | 22.31 | 129.17 | 234.67 |
March | 362.67 | 0.52 | 0.48 | 01-MAR-09:30 | 2217.25 | 23.39 | 100.00 | 324.67 | 1142.26 | 23.66 | 161.17 | 292.33 |
April | 357.50 | 0.51 | 0.48 | 01-APR-08:00 | 2416.70 | 22.07 | 81.00 | 336.67 | 1293.14 | 22.62 | 105.17 | 305.50 |
May | 389.00 | 0.52 | 0.48 | 01-MAY-07:40 | 2179.90 | 18.14 | 0.00 | 353.33 | 1128.18 | 20.22 | 97.33 | 315.33 |
June | 388.17 | 0.53 | 0.48 | 01-JUN-07:30 | 1833.92 | 17.81 | 4.83 | 337.17 | 826.03 | 19.81 | 105.83 | 296.17 |
July | 403.83 | 0.52 | 0.48 | 01-JUL-07:19 | 2075.19 | 18.69 | 3.83 | 361.17 | 930.90 | 20.56 | 140.17 | 323.33 |
August | 348.33 | 0.52 | 0.48 | 01-AUG-08:09 | 2235.96 | 21.01 | 58.17 | 345.17 | 1152.50 | 20.93 | 146.50 | 310.33 |
September | 349.67 | 0.52 | 0.48 | 01-SEP-07:49 | 1857.20 | 22.07 | 84.50 | 317.17 | 954.62 | 22.55 | 164.67 | 282.00 |
October | 323.50 | 0.52 | 0.48 | 02-OCT-11:39 | 2218.74 | 24.26 | 109.00 | 304.67 | 1165.73 | 24.48 | 180.00 | 270.00 |
November | 314.83 | 0.52 | 0.48 | 01-NOV-08:20 | 1756.25 | 23.64 | 107.17 | 276.67 | 907.03 | 23.81 | 172.17 | 241.50 |
December | 282.67 | 0.51 | 0.48 | 01-DEC-09:09 | 2015.96 | 25.13 | 109.00 | 268.67 | 1058.42 | 24.95 | 152.33 | 235.00 |
Annual Sum or Average | 4111.50 | 0.52 | 2055.98 | 21.61 | 828.33 | 3769.50 | 1044.84 | 22.33 | 1695.83 | 3338.17 | ||
Minimum of Months | 282.67 | 0.51 | 0.48 | 1756.25 | 17.81 | 0.00 | 268.67 | 826.03 | 19.81 | 97.33 | 232.00 | |
Maximum of Months | 403.83 | 0.54 | 0.48 | 2416.70 | 25.13 | 109.00 | 361.17 | 1293.14 | 24.95 | 180.00 | 323.33 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_1_DAYLCTRL
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 287.00 | 0.51 | 0.48 | 01-JAN-07:40 | 7215.63 | 35.67 | 274.83 | 293.67 | 1489.43 | 21.63 | 81.17 | 279.83 |
February | 304.33 | 0.51 | 0.48 | 01-FEB-08:20 | 2709.03 | 22.17 | 135.00 | 279.17 | 1168.77 | 16.67 | 0.00 | 255.17 |
March | 362.67 | 0.51 | 0.48 | 01-MAR-07:49 | 1684.87 | 14.27 | 5.67 | 330.33 | 967.29 | 17.43 | 0.00 | 298.67 |
April | 357.50 | 0.52 | 0.48 | 01-APR-07:30 | 1316.36 | 14.03 | 0.00 | 328.17 | 778.57 | 17.45 | 0.00 | 300.00 |
May | 389.00 | 0.52 | 0.48 | 01-MAY-07:19 | 1127.81 | 13.49 | 0.00 | 350.00 | 659.22 | 16.87 | 0.00 | 308.50 |
June | 388.17 | 0.54 | 0.48 | 01-JUN-07:19 | 1063.90 | 12.74 | 0.00 | 328.83 | 616.40 | 16.15 | 0.00 | 286.00 |
July | 403.83 | 0.52 | 0.48 | 01-JUL-06:00 | 1192.07 | 13.62 | 0.00 | 357.33 | 691.01 | 17.04 | 0.00 | 312.83 |
August | 348.33 | 0.52 | 0.48 | 01-AUG-07:30 | 1412.81 | 14.13 | 0.00 | 346.33 | 802.61 | 17.51 | 0.00 | 310.17 |
September | 349.67 | 0.52 | 0.48 | 01-SEP-07:10 | 1689.10 | 14.00 | 0.00 | 316.83 | 934.71 | 17.40 | 0.00 | 287.00 |
October | 323.50 | 0.51 | 0.48 | 02-OCT-07:49 | 2239.53 | 16.06 | 31.67 | 316.50 | 1155.56 | 18.14 | 9.17 | 292.83 |
November | 314.83 | 0.50 | 0.48 | 01-NOV-07:10 | 4123.66 | 29.93 | 245.17 | 293.83 | 1292.42 | 21.00 | 71.33 | 276.33 |
December | 282.67 | 0.50 | 0.48 | 01-DEC-08:39 | 6852.13 | 36.06 | 278.50 | 280.67 | 1717.86 | 23.14 | 92.67 | 263.67 |
Annual Sum or Average | 4111.50 | 0.52 | 2517.92 | 18.85 | 970.83 | 3821.67 | 987.42 | 18.18 | 254.33 | 3471.00 | ||
Minimum of Months | 282.67 | 0.50 | 0.48 | 1063.90 | 12.74 | 0.00 | 279.17 | 616.40 | 16.15 | 0.00 | 255.17 | |
Maximum of Months | 403.83 | 0.54 | 0.48 | 7215.63 | 36.06 | 278.50 | 357.33 | 1717.86 | 23.14 | 92.67 | 312.83 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_2_DAYLCTRL
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 287.00 | 0.53 | 0.48 | 01-JAN-07:40 | 2319.05 | 22.16 | 102.67 | 272.50 | 1245.71 | 22.53 | 74.17 | 237.67 |
February | 304.33 | 0.53 | 0.48 | 01-FEB-07:49 | 2430.43 | 21.20 | 100.67 | 264.33 | 950.43 | 20.12 | 45.67 | 235.67 |
March | 362.67 | 0.51 | 0.48 | 01-MAR-07:19 | 2326.74 | 20.28 | 98.83 | 326.33 | 1251.14 | 21.17 | 67.67 | 297.17 |
April | 357.50 | 0.52 | 0.48 | 01-APR-06:00 | 2664.75 | 20.09 | 99.83 | 328.17 | 1463.68 | 21.09 | 70.67 | 299.33 |
May | 389.00 | 0.51 | 0.48 | 01-MAY-06:10 | 2458.01 | 19.45 | 103.83 | 361.83 | 1085.31 | 20.00 | 57.83 | 320.17 |
June | 388.17 | 0.52 | 0.48 | 01-JUN-05:00 | 2410.49 | 20.63 | 122.00 | 346.83 | 1059.44 | 20.33 | 65.17 | 309.00 |
July | 403.83 | 0.51 | 0.48 | 01-JUL-06:19 | 2373.93 | 19.96 | 115.67 | 365.67 | 1087.86 | 20.48 | 63.67 | 328.67 |
August | 348.33 | 0.52 | 0.48 | 01-AUG-06:40 | 2328.66 | 20.24 | 97.17 | 350.00 | 1271.65 | 21.38 | 71.17 | 316.00 |
September | 349.67 | 0.52 | 0.48 | 01-SEP-06:49 | 2301.15 | 20.86 | 104.00 | 314.83 | 1219.43 | 21.74 | 74.83 | 278.00 |
October | 323.50 | 0.52 | 0.48 | 02-OCT-07:10 | 2283.83 | 21.02 | 94.50 | 307.00 | 1228.65 | 21.90 | 67.33 | 275.00 |
November | 314.83 | 0.52 | 0.48 | 01-NOV-06:00 | 1812.05 | 19.90 | 84.67 | 278.50 | 952.32 | 21.40 | 59.33 | 243.00 |
December | 282.67 | 0.53 | 0.48 | 01-DEC-08:39 | 1956.05 | 20.86 | 87.17 | 260.00 | 831.14 | 20.08 | 34.50 | 224.17 |
Annual Sum or Average | 4111.50 | 0.52 | 2317.94 | 20.50 | 1211.00 | 3776.00 | 1142.67 | 20.99 | 752.00 | 3363.83 | ||
Minimum of Months | 282.67 | 0.51 | 0.48 | 1812.05 | 19.45 | 84.67 | 260.00 | 831.14 | 20.00 | 34.50 | 224.17 | |
Maximum of Months | 403.83 | 0.53 | 0.48 | 2664.75 | 22.16 | 122.00 | 365.67 | 1463.68 | 22.53 | 74.83 | 328.67 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_3_DAYLCTRL
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 287.00 | 0.56 | 0.48 | 01-JAN-09:39 | 600.35 | 11.12 | 0.00 | 254.33 | 397.08 | 14.73 | 0.00 | 182.33 |
February | 304.33 | 0.54 | 0.48 | 01-FEB-09:09 | 682.98 | 11.94 | 0.00 | 255.33 | 439.97 | 15.45 | 0.00 | 203.83 |
March | 362.67 | 0.52 | 0.48 | 01-MAR-09:09 | 816.22 | 13.25 | 0.00 | 320.17 | 515.09 | 16.71 | 0.00 | 272.67 |
April | 357.50 | 0.51 | 0.48 | 01-APR-07:30 | 974.38 | 14.10 | 0.00 | 332.67 | 605.26 | 17.53 | 0.00 | 304.33 |
May | 389.00 | 0.50 | 0.48 | 01-MAY-06:40 | 1150.51 | 15.41 | 26.83 | 369.17 | 671.12 | 18.61 | 25.83 | 341.17 |
June | 388.17 | 0.51 | 0.48 | 01-JUN-06:10 | 1222.07 | 17.22 | 66.17 | 359.00 | 695.51 | 18.73 | 33.00 | 323.83 |
July | 403.83 | 0.50 | 0.48 | 01-JUL-06:40 | 1314.18 | 15.58 | 26.17 | 376.17 | 733.52 | 18.89 | 26.17 | 347.50 |
August | 348.33 | 0.51 | 0.48 | 01-AUG-07:10 | 1157.95 | 14.31 | 0.00 | 351.83 | 682.97 | 17.72 | 0.00 | 320.83 |
September | 349.67 | 0.52 | 0.48 | 01-SEP-07:10 | 973.98 | 13.51 | 0.00 | 315.17 | 581.81 | 16.88 | 0.00 | 276.50 |
October | 323.50 | 0.54 | 0.48 | 02-OCT-11:39 | 780.36 | 12.95 | 0.00 | 298.33 | 496.51 | 16.40 | 0.00 | 246.50 |
November | 314.83 | 0.54 | 0.48 | 01-NOV-08:09 | 685.12 | 11.97 | 0.00 | 262.67 | 428.24 | 15.49 | 0.00 | 203.50 |
December | 282.67 | 0.54 | 0.48 | 01-DEC-09:09 | 651.91 | 11.74 | 0.00 | 248.00 | 418.23 | 15.34 | 0.00 | 188.67 |
Annual Sum or Average | 4111.50 | 0.52 | 942.11 | 13.77 | 119.17 | 3742.83 | 567.51 | 17.02 | 85.00 | 3211.67 | ||
Minimum of Months | 282.67 | 0.50 | 0.48 | 600.35 | 11.12 | 0.00 | 248.00 | 397.08 | 14.73 | 0.00 | 182.33 | |
Maximum of Months | 403.83 | 0.56 | 0.48 | 1314.18 | 17.22 | 66.17 | 376.17 | 733.52 | 18.89 | 33.00 | 347.50 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_4_DAYLCTRL
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 287.00 | 0.54 | 0.48 | 01-JAN-09:30 | 2004.06 | 21.08 | 91.50 | 274.67 | 1111.12 | 21.86 | 65.83 | 237.17 |
February | 304.33 | 0.52 | 0.48 | 01-FEB-09:09 | 1856.42 | 19.05 | 71.17 | 270.83 | 967.96 | 19.92 | 46.50 | 239.00 |
March | 362.67 | 0.52 | 0.48 | 01-MAR-09:09 | 2271.36 | 20.31 | 99.17 | 325.00 | 1198.64 | 21.21 | 69.17 | 297.17 |
April | 357.50 | 0.51 | 0.48 | 01-APR-08:50 | 2442.84 | 18.70 | 80.67 | 336.67 | 1350.56 | 19.91 | 51.83 | 309.33 |
May | 389.00 | 0.51 | 0.48 | 01-MAY-07:40 | 2207.83 | 13.58 | 0.00 | 354.33 | 1182.01 | 16.94 | 0.00 | 320.00 |
June | 388.17 | 0.53 | 0.48 | 01-JUN-07:30 | 1865.64 | 13.32 | 0.00 | 338.33 | 871.86 | 16.60 | 0.00 | 301.33 |
July | 403.83 | 0.51 | 0.48 | 01-JUL-07:19 | 2104.90 | 14.27 | 3.67 | 362.17 | 981.75 | 17.39 | 0.00 | 329.00 |
August | 348.33 | 0.52 | 0.48 | 01-AUG-07:00 | 2258.00 | 17.35 | 56.83 | 346.33 | 1207.43 | 17.80 | 5.50 | 313.67 |
September | 349.67 | 0.52 | 0.48 | 01-SEP-07:49 | 1891.79 | 18.88 | 80.67 | 318.00 | 1002.47 | 20.05 | 51.83 | 286.67 |
October | 323.50 | 0.52 | 0.48 | 02-OCT-11:39 | 2264.75 | 21.59 | 105.33 | 305.17 | 1215.06 | 22.39 | 76.50 | 274.17 |
November | 314.83 | 0.52 | 0.48 | 01-NOV-08:09 | 1787.24 | 20.89 | 96.83 | 278.17 | 949.47 | 21.72 | 67.50 | 246.67 |
December | 282.67 | 0.51 | 0.48 | 01-DEC-09:09 | 2049.74 | 22.63 | 96.50 | 270.17 | 1104.38 | 23.04 | 67.17 | 238.67 |
Annual Sum or Average | 4111.50 | 0.52 | 2089.99 | 18.17 | 782.33 | 3779.83 | 1094.73 | 19.70 | 501.83 | 3392.83 | ||
Minimum of Months | 282.67 | 0.51 | 0.48 | 1787.24 | 13.32 | 0.00 | 270.17 | 871.86 | 16.60 | 0.00 | 237.17 | |
Maximum of Months | 403.83 | 0.54 | 0.48 | 2442.84 | 22.63 | 105.33 | 362.17 | 1350.56 | 23.04 | 76.50 | 329.00 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_1_DAYLCTRL
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 287.00 | 0.51 | 0.48 | 01-JAN-07:40 | 7217.67 | 35.66 | 274.83 | 293.67 | 1491.28 | 21.62 | 81.17 | 279.83 |
February | 304.33 | 0.51 | 0.48 | 01-FEB-08:20 | 2711.56 | 22.15 | 135.00 | 279.17 | 1170.43 | 16.66 | 0.00 | 255.17 |
March | 362.67 | 0.51 | 0.48 | 01-MAR-07:49 | 1687.17 | 14.24 | 5.67 | 330.33 | 968.71 | 17.42 | 0.00 | 298.83 |
April | 357.50 | 0.52 | 0.48 | 01-APR-07:30 | 1318.16 | 14.00 | 0.00 | 328.17 | 779.71 | 17.43 | 0.00 | 300.00 |
May | 389.00 | 0.52 | 0.48 | 01-MAY-07:19 | 1129.39 | 13.46 | 0.00 | 350.17 | 660.20 | 16.86 | 0.00 | 308.67 |
June | 388.17 | 0.54 | 0.48 | 01-JUN-07:19 | 1065.44 | 12.71 | 0.00 | 328.83 | 617.34 | 16.13 | 0.00 | 286.00 |
July | 403.83 | 0.52 | 0.48 | 01-JUL-06:00 | 1193.75 | 13.59 | 0.00 | 357.50 | 692.07 | 17.02 | 0.00 | 313.00 |
August | 348.33 | 0.52 | 0.48 | 01-AUG-07:30 | 1414.92 | 14.10 | 0.00 | 346.33 | 803.89 | 17.49 | 0.00 | 310.17 |
September | 349.67 | 0.52 | 0.48 | 01-SEP-07:10 | 1691.82 | 13.97 | 0.00 | 316.83 | 936.31 | 17.39 | 0.00 | 287.00 |
October | 323.50 | 0.51 | 0.48 | 02-OCT-07:49 | 2242.40 | 16.03 | 31.67 | 316.50 | 1157.39 | 18.12 | 9.17 | 292.83 |
November | 314.83 | 0.50 | 0.48 | 01-NOV-07:10 | 4126.42 | 29.92 | 245.17 | 293.83 | 1294.45 | 20.99 | 71.33 | 276.33 |
December | 282.67 | 0.50 | 0.48 | 01-DEC-08:39 | 6854.47 | 36.05 | 278.50 | 280.67 | 1720.03 | 23.13 | 92.67 | 263.83 |
Annual Sum or Average | 4111.50 | 0.52 | 2520.08 | 18.82 | 970.83 | 3822.00 | 988.87 | 18.17 | 254.33 | 3471.67 | ||
Minimum of Months | 282.67 | 0.50 | 0.48 | 1065.44 | 12.71 | 0.00 | 279.17 | 617.34 | 16.13 | 0.00 | 255.17 | |
Maximum of Months | 403.83 | 0.54 | 0.48 | 7217.67 | 36.05 | 278.50 | 357.50 | 1720.03 | 23.13 | 92.67 | 313.00 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_2_DAYLCTRL
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 287.00 | 0.53 | 0.48 | 01-JAN-07:40 | 2319.98 | 22.14 | 102.67 | 272.67 | 1246.70 | 22.51 | 74.17 | 237.67 |
February | 304.33 | 0.53 | 0.48 | 01-FEB-07:49 | 2431.68 | 21.17 | 100.67 | 264.33 | 951.53 | 20.11 | 45.67 | 235.67 |
March | 362.67 | 0.51 | 0.48 | 01-MAR-07:19 | 2328.00 | 20.25 | 98.83 | 326.50 | 1252.32 | 21.16 | 67.67 | 297.17 |
April | 357.50 | 0.52 | 0.48 | 01-APR-06:00 | 2666.38 | 20.06 | 99.83 | 328.17 | 1465.04 | 21.07 | 70.67 | 299.33 |
May | 389.00 | 0.51 | 0.48 | 01-MAY-06:10 | 2459.76 | 19.42 | 103.83 | 361.83 | 1086.65 | 19.98 | 57.83 | 320.33 |
June | 388.17 | 0.52 | 0.48 | 01-JUN-05:00 | 2412.39 | 20.61 | 122.00 | 346.83 | 1060.77 | 20.32 | 65.17 | 309.33 |
July | 403.83 | 0.51 | 0.48 | 01-JUL-06:19 | 2375.96 | 19.93 | 115.67 | 365.83 | 1089.34 | 20.47 | 63.67 | 328.67 |
August | 348.33 | 0.52 | 0.48 | 01-AUG-06:40 | 2330.71 | 20.22 | 97.17 | 350.00 | 1273.19 | 21.37 | 71.17 | 316.00 |
September | 349.67 | 0.52 | 0.48 | 01-SEP-06:49 | 2303.20 | 20.83 | 104.00 | 314.83 | 1220.98 | 21.73 | 74.83 | 278.17 |
October | 323.50 | 0.52 | 0.48 | 02-OCT-07:10 | 2285.10 | 20.99 | 94.50 | 307.00 | 1229.92 | 21.89 | 67.33 | 275.17 |
November | 314.83 | 0.52 | 0.48 | 01-NOV-06:00 | 1813.35 | 19.87 | 84.67 | 278.67 | 953.46 | 21.39 | 59.33 | 243.00 |
December | 282.67 | 0.53 | 0.48 | 01-DEC-08:39 | 1957.19 | 20.83 | 87.17 | 260.00 | 832.21 | 20.07 | 34.50 | 224.33 |
Annual Sum or Average | 4111.50 | 0.52 | 2319.52 | 20.47 | 1211.00 | 3776.67 | 1143.97 | 20.98 | 752.00 | 3364.83 | ||
Minimum of Months | 282.67 | 0.51 | 0.48 | 1813.35 | 19.42 | 84.67 | 260.00 | 832.21 | 19.98 | 34.50 | 224.33 | |
Maximum of Months | 403.83 | 0.53 | 0.48 | 2666.38 | 22.14 | 122.00 | 365.83 | 1465.04 | 22.51 | 74.83 | 328.67 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_3_DAYLCTRL
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 287.00 | 0.56 | 0.48 | 01-JAN-09:39 | 600.78 | 11.09 | 0.00 | 254.50 | 397.53 | 14.71 | 0.00 | 182.50 |
February | 304.33 | 0.54 | 0.48 | 01-FEB-09:09 | 683.57 | 11.91 | 0.00 | 255.50 | 440.51 | 15.44 | 0.00 | 204.17 |
March | 362.67 | 0.52 | 0.48 | 01-MAR-09:09 | 817.02 | 13.22 | 0.00 | 320.17 | 515.75 | 16.70 | 0.00 | 272.67 |
April | 357.50 | 0.51 | 0.48 | 01-APR-07:30 | 975.41 | 14.06 | 0.00 | 332.67 | 606.06 | 17.52 | 0.00 | 304.50 |
May | 389.00 | 0.50 | 0.48 | 01-MAY-06:40 | 1151.95 | 15.39 | 26.83 | 369.17 | 672.11 | 18.60 | 25.83 | 341.33 |
June | 388.17 | 0.51 | 0.48 | 01-JUN-06:10 | 1223.77 | 17.19 | 66.17 | 359.00 | 696.58 | 18.72 | 33.00 | 324.00 |
July | 403.83 | 0.50 | 0.48 | 01-JUL-06:40 | 1315.88 | 15.55 | 26.17 | 376.33 | 734.65 | 18.88 | 26.17 | 347.67 |
August | 348.33 | 0.51 | 0.48 | 01-AUG-07:10 | 1159.40 | 14.28 | 0.00 | 351.83 | 683.99 | 17.70 | 0.00 | 320.83 |
September | 349.67 | 0.52 | 0.48 | 01-SEP-07:10 | 975.15 | 13.48 | 0.00 | 315.17 | 582.66 | 16.87 | 0.00 | 276.50 |
October | 323.50 | 0.54 | 0.48 | 02-OCT-11:39 | 781.04 | 12.92 | 0.00 | 298.33 | 497.13 | 16.38 | 0.00 | 246.50 |
November | 314.83 | 0.54 | 0.48 | 01-NOV-08:09 | 685.78 | 11.94 | 0.00 | 262.83 | 428.81 | 15.48 | 0.00 | 204.00 |
December | 282.67 | 0.54 | 0.48 | 01-DEC-09:09 | 652.45 | 11.71 | 0.00 | 248.17 | 418.75 | 15.32 | 0.00 | 189.00 |
Annual Sum or Average | 4111.50 | 0.52 | 943.17 | 13.74 | 119.17 | 3743.67 | 568.30 | 17.01 | 85.00 | 3213.67 | ||
Minimum of Months | 282.67 | 0.50 | 0.48 | 600.78 | 11.09 | 0.00 | 248.17 | 397.53 | 14.71 | 0.00 | 182.50 | |
Maximum of Months | 403.83 | 0.56 | 0.48 | 1315.88 | 17.19 | 66.17 | 376.33 | 734.65 | 18.88 | 33.00 | 347.67 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_4_DAYLCTRL
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 287.00 | 0.54 | 0.48 | 01-JAN-09:30 | 2005.00 | 21.06 | 91.50 | 275.00 | 1112.08 | 21.85 | 65.83 | 237.50 |
February | 304.33 | 0.52 | 0.48 | 01-FEB-09:09 | 1857.61 | 19.02 | 71.17 | 270.83 | 969.04 | 19.91 | 46.50 | 239.17 |
March | 362.67 | 0.52 | 0.48 | 01-MAR-09:09 | 2272.68 | 20.28 | 99.17 | 325.00 | 1199.87 | 21.20 | 69.17 | 297.17 |
April | 357.50 | 0.51 | 0.48 | 01-APR-08:50 | 2444.35 | 18.67 | 80.67 | 336.67 | 1351.83 | 19.89 | 51.83 | 309.50 |
May | 389.00 | 0.51 | 0.48 | 01-MAY-07:40 | 2209.59 | 13.55 | 0.00 | 354.33 | 1183.35 | 16.93 | 0.00 | 320.00 |
June | 388.17 | 0.53 | 0.48 | 01-JUN-07:30 | 1867.60 | 13.29 | 0.00 | 338.50 | 873.15 | 16.58 | 0.00 | 301.50 |
July | 403.83 | 0.51 | 0.48 | 01-JUL-07:19 | 2106.95 | 14.23 | 3.67 | 362.17 | 983.19 | 17.38 | 0.00 | 329.00 |
August | 348.33 | 0.52 | 0.48 | 01-AUG-07:00 | 2260.13 | 17.32 | 56.83 | 346.33 | 1208.99 | 17.78 | 5.50 | 313.67 |
September | 349.67 | 0.52 | 0.48 | 01-SEP-07:49 | 1893.82 | 18.85 | 80.67 | 318.00 | 1003.90 | 20.04 | 51.83 | 286.67 |
October | 323.50 | 0.52 | 0.48 | 02-OCT-11:39 | 2266.31 | 21.56 | 105.33 | 305.17 | 1216.37 | 22.37 | 76.50 | 274.33 |
November | 314.83 | 0.52 | 0.48 | 01-NOV-08:09 | 1788.55 | 20.86 | 96.83 | 278.17 | 950.63 | 21.71 | 67.50 | 246.67 |
December | 282.67 | 0.51 | 0.48 | 01-DEC-09:09 | 2050.86 | 22.61 | 96.50 | 270.17 | 1105.47 | 23.03 | 67.17 | 238.67 |
Annual Sum or Average | 4111.50 | 0.52 | 2091.60 | 18.14 | 782.33 | 3780.33 | 1096.01 | 19.69 | 501.83 | 3393.83 | ||
Minimum of Months | 282.67 | 0.51 | 0.48 | 1788.55 | 13.29 | 0.00 | 270.17 | 873.15 | 16.58 | 0.00 | 237.50 | |
Maximum of Months | 403.83 | 0.54 | 0.48 | 2444.35 | 22.61 | 105.33 | 362.17 | 1351.83 | 23.03 | 76.50 | 329.00 |
Report: CoilReportMonthly
For: VAV_BOT WITH REHEAT HEATING COIL
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 1012693.02 | 885.77 | 25-JAN-06:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 2461801.29 | 13072.80 | 04-FEB-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6088703.96 | 10733.24 | 16-MAR-05:17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 164352.20 | 326.52 | 27-NOV-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 11035239.70 | 7313.96 | 15-DEC-06:17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 20762790.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 11035239.70 | 13072.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_BOTTOM VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 8216307.19 | 1747.67 | 04-FEB-06:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 8216307.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 8216307.19 | 1747.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 1349751.26 | 522.94 | 25-JAN-06:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 7443846.50 | 2766.42 | 04-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 1431749.96 | 457.83 | 16-MAR-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 476363.46 | 213.08 | 15-DEC-06:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 10701711.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 7443846.50 | 2766.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 4697781.17 | 1329.81 | 04-FEB-06:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 4697781.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 4697781.17 | 1329.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV_MID WITH REHEAT HEATING COIL
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 5339979.81 | 19354.28 | 25-JAN-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 31808327.05 | 99565.91 | 04-FEB-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 31937293.99 | 98250.28 | 16-MAR-05:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 3198701.82 | 12787.07 | 27-NOV-06:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 23960842.26 | 86818.40 | 15-DEC-06:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 96245144.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 31937293.99 | 99565.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_MID VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.106461E+10 | 168955.37 | 25-JAN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.119196E+10 | 170276.32 | 04-FEB-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.591823E+09 | 169085.46 | 16-MAR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.160687E+09 | 23691.78 | 27-NOV-06:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.112225E+10 | 169121.97 | 15-DEC-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.413132E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.119196E+10 | 170276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.568362E+09 | 62799.34 | 25-JAN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.511151E+09 | 141647.76 | 04-FEB-05:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.295745E+09 | 54231.26 | 16-MAR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 66835954.43 | 21257.46 | 27-NOV-06:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.928782E+09 | 86930.00 | 15-DEC-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.237088E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.928782E+09 | 141647.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 36203118.69 | 8220.11 | 31-JAN-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.336123E+09 | 168506.36 | 04-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.112553E+09 | 17466.26 | 16-MAR-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 52765428.68 | 6459.01 | 15-DEC-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.537645E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.336123E+09 | 168506.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.704042E+09 | 24455.13 | 26-JAN-06:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.822726E+09 | 140004.52 | 04-FEB-05:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.315554E+09 | 28706.99 | 16-MAR-05:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.123282E+09 | 17249.48 | 13-NOV-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.773732E+09 | 45764.06 | 15-DEC-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.273934E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.822726E+09 | 140004.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV_TOP WITH REHEAT HEATING COIL
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 1901636.92 | 4921.58 | 25-JAN-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 5804143.03 | 7566.21 | 04-FEB-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 1868710.56 | 7263.68 | 16-MAR-05:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 395820.08 | 2902.83 | 27-NOV-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 2459876.86 | 7253.45 | 15-DEC-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 12430187.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 5804143.03 | 7566.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_TOP VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 19480764.41 | 4957.60 | 23-JAN-06:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 96044060.08 | 8070.04 | 04-FEB-08:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 5602629.27 | 2641.66 | 16-DEC-08:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.121127E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 96044060.08 | 8070.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.452535E+09 | 19614.80 | 23-JAN-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.331432E+09 | 19533.98 | 04-FEB-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.226775E+09 | 19529.91 | 16-MAR-04:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 71057010.87 | 19603.27 | 27-NOV-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.439335E+09 | 19612.09 | 13-DEC-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.152113E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.452535E+09 | 19614.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.226323E+09 | 15967.42 | 23-JAN-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.145957E+09 | 15953.62 | 04-FEB-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 99850652.10 | 14790.48 | 16-MAR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 182403.44 | 199.40 | 19-APR-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 31530593.90 | 15940.65 | 13-NOV-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.303500E+09 | 15951.00 | 27-DEC-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.807343E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.303500E+09 | 15967.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 93840368.87 | 18446.77 | 25-JAN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 98664761.83 | 19524.38 | 04-FEB-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 92333132.69 | 19521.61 | 16-MAR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 22541113.66 | 19522.03 | 13-NOV-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.133193E+09 | 19591.68 | 27-DEC-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.440572E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.133193E+09 | 19591.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.305667E+09 | 16523.15 | 26-JAN-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.209953E+09 | 16527.94 | 04-FEB-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.142364E+09 | 13169.95 | 16-MAR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 51515770.96 | 16521.23 | 13-NOV-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.300573E+09 | 16530.32 | 27-DEC-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.101007E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.305667E+09 | 16530.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CAV_BAS HEATING COIL
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BASEMENT HEATING COIL
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BOT HEATING COIL
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER MID HEATING COIL
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER TOP HEATING COIL
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BOT_SUPPHEATCOIL
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER MID_SUPPHEATCOIL
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER TOP_SUPPHEATCOIL
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV_BOT WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.103057E+12 | 0.767359E+11 | 241912.22 | 07-JAN-06:02 | 149529.28 | 0.52 |
February | 0.00 | 0.00 | 0.114866E+12 | 0.862004E+11 | 252536.30 | 17-FEB-05:11 | 158745.24 | 0.54 |
March | 0.00 | 0.00 | 0.157143E+12 | 0.111667E+12 | 221732.08 | 06-MAR-06:02 | 149723.12 | 0.64 |
April | 0.00 | 0.00 | 0.188351E+12 | 0.133487E+12 | 204683.79 | 29-APR-05:02 | 147264.74 | 0.81 |
May | 0.00 | 0.00 | 0.203682E+12 | 0.136977E+12 | 280113.08 | 27-MAY-03:02 | 149040.64 | 0.73 |
June | 0.00 | 0.00 | 0.229803E+12 | 0.151900E+12 | 257703.84 | 22-JUN-05:03 | 164623.69 | 0.81 |
July | 0.00 | 0.00 | 0.248806E+12 | 0.164825E+12 | 232474.94 | 05-JUL-05:03 | 156480.04 | 0.85 |
August | 0.00 | 0.00 | 0.264772E+12 | 0.175992E+12 | 246334.87 | 21-AUG-05:03 | 181250.81 | 0.88 |
September | 0.00 | 0.00 | 0.218780E+12 | 0.141572E+12 | 252578.13 | 25-SEP-05:02 | 167093.23 | 0.76 |
October | 0.00 | 0.00 | 0.213335E+12 | 0.142294E+12 | 250915.59 | 07-OCT-05:03 | 165013.30 | 0.75 |
November | 0.00 | 0.00 | 0.179437E+12 | 0.121853E+12 | 232125.28 | 03-NOV-05:02 | 157464.09 | 0.69 |
December | 0.00 | 0.00 | 0.142038E+12 | 0.982195E+11 | 241236.47 | 09-DEC-06:02 | 161975.68 | 0.66 |
Annual Sum or Average | 0.00 | 0.00 | 0.226407E+13 | 0.154172E+13 | 0.72 | |||
Minimum of Months | 0.00 | 0.00 | 0.103057E+12 | 0.767359E+11 | 204683.79 | 147264.74 | 0.52 | |
Maximum of Months | 0.00 | 0.00 | 0.264772E+12 | 0.175992E+12 | 280113.08 | 181250.81 | 0.88 |
Report: CoilReportMonthly
For: VAV_MID WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.851841E+12 | 0.613380E+12 | 2265835.08 | 14-JAN-06:03 | 1318272.13 | 0.49 |
February | 0.00 | 0.00 | 0.925583E+12 | 0.672573E+12 | 2197607.77 | 02-FEB-06:02 | 1243663.12 | 0.51 |
March | 0.00 | 0.00 | 0.115938E+13 | 0.822038E+12 | 2511423.65 | 06-MAR-05:12 | 1300303.25 | 0.53 |
April | 0.00 | 0.00 | 0.136184E+13 | 0.966134E+12 | 2290829.39 | 25-APR-04:12 | 1438289.45 | 0.63 |
May | 0.00 | 0.00 | 0.177990E+13 | 0.118850E+13 | 2737993.20 | 27-MAY-04:02 | 1322778.78 | 0.67 |
June | 0.00 | 0.00 | 0.194752E+13 | 0.126781E+13 | 2679608.50 | 22-JUN-05:03 | 1558144.00 | 0.71 |
July | 0.00 | 0.00 | 0.200966E+13 | 0.131269E+13 | 2612954.09 | 03-JUL-03:02 | 1424032.23 | 0.72 |
August | 0.00 | 0.00 | 0.202869E+13 | 0.130845E+13 | 2443424.97 | 28-AUG-03:02 | 1410767.24 | 0.71 |
September | 0.00 | 0.00 | 0.194079E+13 | 0.123304E+13 | 2541612.10 | 20-SEP-03:02 | 1481898.29 | 0.70 |
October | 0.00 | 0.00 | 0.174324E+13 | 0.115719E+13 | 2586583.56 | 31-OCT-05:02 | 1482704.87 | 0.64 |
November | 0.00 | 0.00 | 0.137180E+13 | 0.918690E+12 | 2430527.12 | 04-NOV-03:02 | 1269984.38 | 0.58 |
December | 0.00 | 0.00 | 0.943657E+12 | 0.660792E+12 | 2590196.06 | 09-DEC-06:02 | 1528722.24 | 0.53 |
Annual Sum or Average | 0.00 | 0.00 | 0.180639E+14 | 0.121213E+14 | 0.62 | |||
Minimum of Months | 0.00 | 0.00 | 0.851841E+12 | 0.613380E+12 | 2197607.77 | 1243663.12 | 0.49 | |
Maximum of Months | 0.00 | 0.00 | 0.202869E+13 | 0.131269E+13 | 2737993.20 | 1558144.00 | 0.72 |
Report: CoilReportMonthly
For: VAV_TOP WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.826114E+11 | 0.593342E+11 | 230893.82 | 07-JAN-06:02 | 115018.35 | 0.48 |
February | 0.00 | 0.00 | 0.946209E+11 | 0.688229E+11 | 210453.09 | 18-FEB-06:03 | 123339.36 | 0.49 |
March | 0.00 | 0.00 | 0.121313E+12 | 0.856662E+11 | 254188.10 | 06-MAR-05:12 | 125543.73 | 0.53 |
April | 0.00 | 0.00 | 0.146014E+12 | 0.104605E+12 | 226343.37 | 25-APR-04:12 | 135051.87 | 0.62 |
May | 0.00 | 0.00 | 0.191148E+12 | 0.131569E+12 | 289128.25 | 27-MAY-04:02 | 134702.05 | 0.67 |
June | 0.00 | 0.00 | 0.210404E+12 | 0.140753E+12 | 279339.85 | 22-JUN-05:03 | 160446.83 | 0.72 |
July | 0.00 | 0.00 | 0.218686E+12 | 0.147312E+12 | 275993.92 | 03-JUL-03:02 | 153738.71 | 0.72 |
August | 0.00 | 0.00 | 0.217048E+12 | 0.144277E+12 | 268365.47 | 10-AUG-05:03 | 154859.54 | 0.71 |
September | 0.00 | 0.00 | 0.205579E+12 | 0.134604E+12 | 262470.00 | 20-SEP-03:02 | 148269.44 | 0.70 |
October | 0.00 | 0.00 | 0.179149E+12 | 0.121988E+12 | 274620.40 | 31-OCT-05:02 | 154021.96 | 0.64 |
November | 0.00 | 0.00 | 0.138899E+12 | 0.941951E+11 | 267967.67 | 04-NOV-03:02 | 141082.43 | 0.57 |
December | 0.00 | 0.00 | 0.937344E+11 | 0.651613E+11 | 229057.86 | 26-DEC-05:12 | 114773.78 | 0.53 |
Annual Sum or Average | 0.00 | 0.00 | 0.189920E+13 | 0.129829E+13 | 0.62 | |||
Minimum of Months | 0.00 | 0.00 | 0.826114E+11 | 0.593342E+11 | 210453.09 | 114773.78 | 0.48 | |
Maximum of Months | 0.00 | 0.00 | 0.218686E+12 | 0.147312E+12 | 289128.25 | 160446.83 | 0.72 |
Report: CoilReportMonthly
For: CAV_BAS COOLING COIL
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.798334E+11 | 0.730627E+11 | 178340.03 | 30-JAN-05:23 | 90771.06 | 0.52 |
February | 0.00 | 0.00 | 0.770349E+11 | 0.696599E+11 | 167398.03 | 02-FEB-05:12 | 95708.68 | 0.51 |
March | 0.00 | 0.00 | 0.892622E+11 | 0.793095E+11 | 190167.97 | 06-MAR-05:23 | 89868.79 | 0.53 |
April | 0.00 | 0.00 | 0.900736E+11 | 0.783108E+11 | 177868.78 | 16-APR-23:22 | 96972.63 | 0.56 |
May | 0.00 | 0.00 | 0.114136E+12 | 0.897917E+11 | 214542.07 | 29-MAY-13:06 | 101858.85 | 0.60 |
June | 0.00 | 0.00 | 0.127747E+12 | 0.918875E+11 | 206064.21 | 26-JUN-03:02 | 90196.06 | 0.62 |
July | 0.00 | 0.00 | 0.132089E+12 | 0.942425E+11 | 204674.87 | 31-JUL-03:13 | 91666.71 | 0.59 |
August | 0.00 | 0.00 | 0.145293E+12 | 0.103598E+12 | 206792.12 | 13-AUG-15:20 | 99481.53 | 0.64 |
September | 0.00 | 0.00 | 0.127968E+12 | 0.925391E+11 | 205716.93 | 10-SEP-18:38 | 99674.30 | 0.62 |
October | 0.00 | 0.00 | 0.122846E+12 | 0.939972E+11 | 215765.13 | 30-OCT-03:02 | 88844.81 | 0.62 |
November | 0.00 | 0.00 | 0.107035E+12 | 0.859328E+11 | 202051.78 | 05-NOV-14:28 | 96590.10 | 0.59 |
December | 0.00 | 0.00 | 0.853396E+11 | 0.762988E+11 | 190678.03 | 10-DEC-12:51 | 100856.03 | 0.57 |
Annual Sum or Average | 0.00 | 0.00 | 0.129866E+13 | 0.102863E+13 | 0.58 | |||
Minimum of Months | 0.00 | 0.00 | 0.770349E+11 | 0.696599E+11 | 167398.03 | 88844.81 | 0.51 | |
Maximum of Months | 0.00 | 0.00 | 0.145293E+12 | 0.103598E+12 | 215765.13 | 101858.85 | 0.64 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BASEMENT COOLING COIL
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.340157E+12 | 0.330546E+12 | 140394.43 | 02-JAN-15:00 | 130674.34 | 0.00 |
February | 0.00 | 0.00 | 0.530443E+12 | 0.520529E+12 | 231075.54 | 10-FEB-17:00 | 220537.38 | 0.00 |
March | 0.00 | 0.00 | 0.834877E+12 | 0.822125E+12 | 396647.92 | 31-MAR-24:00 | 393817.22 | 0.00 |
April | 0.00 | 0.00 | 0.104574E+13 | 0.103269E+13 | 425402.70 | 25-APR-16:00 | 407141.49 | 0.00 |
May | 0.00 | 0.00 | 0.360308E+12 | 0.338716E+12 | 229271.31 | 31-MAY-23:03 | 212058.83 | 0.00 |
June | 0.00 | 0.00 | 0.592182E+12 | 0.565497E+12 | 316724.06 | 30-JUN-23:03 | 303677.67 | 0.00 |
July | 0.00 | 0.00 | 0.858013E+12 | 0.830811E+12 | 402259.48 | 31-JUL-24:00 | 392007.36 | 0.00 |
August | 0.00 | 0.00 | 0.109298E+13 | 0.106733E+13 | 425831.11 | 23-AUG-17:00 | 407321.10 | 0.00 |
September | 0.00 | 0.00 | 0.356542E+12 | 0.331317E+12 | 224750.41 | 30-SEP-23:03 | 212478.14 | 0.00 |
October | 0.00 | 0.00 | 0.608741E+12 | 0.584968E+12 | 313228.93 | 31-OCT-23:10 | 302564.80 | 0.00 |
November | 0.00 | 0.00 | 0.818361E+12 | 0.800352E+12 | 326897.81 | 30-NOV-17:00 | 313706.89 | 0.00 |
December | 0.00 | 0.00 | 0.107957E+13 | 0.106754E+13 | 413874.72 | 08-DEC-17:10 | 401886.92 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.851791E+13 | 0.829242E+13 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.340157E+12 | 0.330546E+12 | 140394.43 | 130674.34 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.109298E+13 | 0.106754E+13 | 425831.11 | 407321.10 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BOT COOLING COIL
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.577985E+10 | 0.540323E+10 | 3009.79 | 02-JAN-15:00 | 2604.40 | 0.00 |
February | 0.00 | 0.00 | 0.101074E+11 | 0.969739E+10 | 4956.49 | 19-FEB-17:23 | 4657.67 | 0.00 |
March | 0.00 | 0.00 | 0.164577E+11 | 0.159034E+11 | 7836.51 | 31-MAR-23:05 | 7659.78 | 0.00 |
April | 0.00 | 0.00 | 0.210775E+11 | 0.204599E+11 | 8893.44 | 13-APR-16:00 | 8415.86 | 0.00 |
May | 0.00 | 0.00 | 0.707565E+10 | 0.619899E+10 | 4798.65 | 31-MAY-23:03 | 4046.53 | 0.00 |
June | 0.00 | 0.00 | 0.120593E+11 | 0.109164E+11 | 6490.05 | 30-JUN-23:03 | 5897.74 | 0.00 |
July | 0.00 | 0.00 | 0.175933E+11 | 0.163862E+11 | 8457.32 | 31-JUL-23:03 | 7831.30 | 0.00 |
August | 0.00 | 0.00 | 0.227726E+11 | 0.215299E+11 | 9038.20 | 21-AUG-13:00 | 8378.55 | 0.00 |
September | 0.00 | 0.00 | 0.710388E+10 | 0.607154E+10 | 4557.11 | 30-SEP-23:03 | 4014.71 | 0.00 |
October | 0.00 | 0.00 | 0.122284E+11 | 0.112170E+11 | 6304.64 | 31-OCT-23:10 | 5825.29 | 0.00 |
November | 0.00 | 0.00 | 0.163215E+11 | 0.155313E+11 | 7113.10 | 07-NOV-17:00 | 6697.22 | 0.00 |
December | 0.00 | 0.00 | 0.213617E+11 | 0.208009E+11 | 9030.43 | 08-DEC-17:00 | 8525.37 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.169939E+12 | 0.160116E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.577985E+10 | 0.540323E+10 | 3009.79 | 2604.40 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.227726E+11 | 0.215299E+11 | 9038.20 | 8525.37 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER MID COOLING COIL
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.469627E+11 | 0.433608E+11 | 28172.61 | 02-JAN-15:00 | 24163.67 | 0.00 |
February | 0.00 | 0.00 | 0.905764E+11 | 0.865296E+11 | 46440.11 | 10-FEB-17:00 | 42055.61 | 0.00 |
March | 0.00 | 0.00 | 0.153790E+12 | 0.148264E+12 | 75628.50 | 31-MAR-23:05 | 73825.83 | 0.00 |
April | 0.00 | 0.00 | 0.200571E+12 | 0.194389E+12 | 84825.00 | 13-APR-16:00 | 80013.92 | 0.00 |
May | 0.00 | 0.00 | 0.663207E+11 | 0.576629E+11 | 46802.87 | 31-MAY-23:03 | 39083.95 | 0.00 |
June | 0.00 | 0.00 | 0.114946E+12 | 0.103568E+12 | 62898.67 | 30-JUN-23:03 | 56876.02 | 0.00 |
July | 0.00 | 0.00 | 0.167848E+12 | 0.155803E+12 | 81590.71 | 31-JUL-23:03 | 75276.94 | 0.00 |
August | 0.00 | 0.00 | 0.216094E+12 | 0.203669E+12 | 85762.22 | 08-AUG-15:00 | 79326.95 | 0.00 |
September | 0.00 | 0.00 | 0.663314E+11 | 0.561424E+11 | 43543.41 | 30-SEP-23:03 | 37970.43 | 0.00 |
October | 0.00 | 0.00 | 0.115966E+12 | 0.105906E+12 | 59698.63 | 31-OCT-23:10 | 54795.65 | 0.00 |
November | 0.00 | 0.00 | 0.153287E+12 | 0.145409E+12 | 67912.56 | 07-NOV-17:00 | 63761.19 | 0.00 |
December | 0.00 | 0.00 | 0.197998E+12 | 0.192392E+12 | 85929.10 | 08-DEC-17:00 | 80884.40 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.159069E+13 | 0.149310E+13 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.469627E+11 | 0.433608E+11 | 28172.61 | 24163.67 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.216094E+12 | 0.203669E+12 | 85929.10 | 80884.40 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER TOP COOLING COIL
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.416360E+10 | 0.381303E+10 | 2874.43 | 02-JAN-15:00 | 2470.20 | 0.00 |
February | 0.00 | 0.00 | 0.875792E+10 | 0.835548E+10 | 4720.78 | 19-FEB-17:22 | 4423.05 | 0.00 |
March | 0.00 | 0.00 | 0.152186E+11 | 0.146674E+11 | 7516.99 | 31-MAR-23:05 | 7336.96 | 0.00 |
April | 0.00 | 0.00 | 0.200696E+11 | 0.194525E+11 | 8628.56 | 13-APR-16:00 | 8147.54 | 0.00 |
May | 0.00 | 0.00 | 0.674479E+10 | 0.587676E+10 | 4699.24 | 31-MAY-23:03 | 3932.59 | 0.00 |
June | 0.00 | 0.00 | 0.116261E+11 | 0.104877E+11 | 6306.21 | 30-JUN-23:03 | 5705.52 | 0.00 |
July | 0.00 | 0.00 | 0.169573E+11 | 0.157529E+11 | 8187.98 | 31-JUL-23:03 | 7558.46 | 0.00 |
August | 0.00 | 0.00 | 0.217303E+11 | 0.204887E+11 | 8722.45 | 23-AUG-16:20 | 8107.94 | 0.00 |
September | 0.00 | 0.00 | 0.674099E+10 | 0.571967E+10 | 4405.03 | 30-SEP-23:03 | 3853.82 | 0.00 |
October | 0.00 | 0.00 | 0.116072E+11 | 0.106024E+11 | 5896.06 | 31-OCT-23:10 | 5403.90 | 0.00 |
November | 0.00 | 0.00 | 0.151363E+11 | 0.143505E+11 | 6864.96 | 07-NOV-17:00 | 6450.25 | 0.00 |
December | 0.00 | 0.00 | 0.194063E+11 | 0.188476E+11 | 8668.24 | 08-DEC-17:00 | 8164.18 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.158159E+12 | 0.148415E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.416360E+10 | 0.381303E+10 | 2874.43 | 2470.20 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.217303E+11 | 0.204887E+11 | 8722.45 | 8164.18 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 1210.99 | 554039.54 | 25-JAN-06:03 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 1557.57 | 944505.66 | 04-FEB-05:11 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 711.59 | 524303.31 | 16-MAR-05:03 |
April | 0.00 | 0.00 | 01-APR-00:02 | 0.06 | 183.43 | 19-APR-06:00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 01-MAY-00:05 |
June | 0.00 | 0.00 | 01-JUN-00:02 | 0.00 | 0.00 | 01-JUN-00:02 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 01-JUL-00:03 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 01-AUG-00:05 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 01-SEP-00:03 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 01-OCT-00:03 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 204.65 | 144269.74 | 13-NOV-06:02 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 1517.56 | 650634.63 | 15-DEC-06:02 |
Annual Sum or Average | 0.00 | 428.49 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.00 | 0.00 | 1557.57 | 944505.66 |
Report: PlantLoopDemandReportMonthly
For: COOLSYS1_SUPPLY
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 451952.03 | 2136733.98 | 14-JAN-06:08 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 550111.34 | 2390541.02 | 13-FEB-05:16 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 626999.83 | 2854610.24 | 06-MAR-06:06 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 758483.76 | 2644326.91 | 15-APR-05:03 | 0.00 | 0.00 | 01-APR-00:02 |
May | 939271.84 | 3299070.62 | 24-MAY-05:03 | 0.00 | 0.00 | 01-MAY-00:05 |
June | 1045976.96 | 3132395.78 | 06-JUN-05:02 | 0.00 | 0.00 | 01-JUN-00:02 |
July | 1039435.34 | 2794448.37 | 03-JUL-03:06 | 0.00 | 0.00 | 01-JUL-00:03 |
August | 1063127.68 | 2896488.04 | 28-AUG-03:06 | 0.00 | 0.00 | 01-AUG-00:05 |
September | 1034197.87 | 3989796.57 | 26-SEP-04:13 | 0.00 | 0.00 | 01-SEP-00:03 |
October | 917337.33 | 3081188.63 | 31-OCT-05:02 | 0.00 | 0.00 | 01-OCT-00:03 |
November | 761486.22 | 2496461.24 | 01-NOV-04:13 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 511314.59 | 2804504.34 | 09-DEC-06:02 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 809424.82 | 0.00 | ||||
Minimum of Months | 451952.03 | 2136733.98 | 0.00 | 0.00 | ||
Maximum of Months | 1063127.68 | 3989796.57 | 0.00 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: COOLSYS1_DEMAND
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 448270.53 | 4354311.47 | 14-JAN-06:03 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 547017.72 | 4165590.38 | 11-FEB-06:03 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 623184.89 | 4442981.74 | 06-MAR-06:02 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 753529.00 | 3936953.05 | 25-APR-04:12 | 0.00 | 0.00 | 01-APR-00:02 |
May | 936512.16 | 4656771.68 | 27-MAY-05:04 | 0.00 | 0.00 | 01-MAY-00:05 |
June | 1041267.13 | 4491770.56 | 19-JUN-03:02 | 0.00 | 0.00 | 01-JUN-00:02 |
July | 1034547.20 | 4493990.89 | 03-JUL-03:02 | 0.00 | 0.00 | 01-JUL-00:03 |
August | 1057289.28 | 4412459.63 | 28-AUG-03:02 | 0.00 | 0.00 | 01-AUG-00:05 |
September | 1031151.82 | 4842844.12 | 05-SEP-04:11 | 0.00 | 0.00 | 01-SEP-00:03 |
October | 915252.02 | 4395379.57 | 02-OCT-04:03 | 0.00 | 0.00 | 01-OCT-00:03 |
November | 757978.32 | 4347265.94 | 22-NOV-06:03 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 507198.89 | 4288194.02 | 11-DEC-05:12 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 805545.72 | 0.00 | ||||
Minimum of Months | 448270.53 | 3936953.05 | 0.00 | 0.00 | ||
Maximum of Months | 1057289.28 | 4842844.12 | 0.00 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SINGLE WATER PLANT LOOP
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 372092.91 | 883334.89 | 02-JAN-15:00 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 650404.24 | 1112972.66 | 11-FEB-14:00 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 899452.20 | 1365517.88 | 13-MAR-16:00 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 1256394.82 | 1720219.78 | 17-APR-15:00 | 0.00 | 0.00 | 01-APR-00:02 |
May | 731222.96 | 1172860.69 | 22-MAY-13:10 | 0.00 | 0.00 | 01-MAY-00:05 |
June | 1031768.97 | 1268882.83 | 11-JUN-13:00 | 0.00 | 0.00 | 01-JUN-00:02 |
July | 1285738.76 | 1708633.03 | 29-JUL-16:00 | 0.00 | 0.00 | 01-JUL-00:03 |
August | 1493976.77 | 1828218.94 | 23-AUG-13:00 | 0.00 | 0.00 | 01-AUG-00:05 |
September | 796325.86 | 1072559.21 | 20-SEP-16:00 | 0.00 | 0.00 | 01-SEP-00:03 |
October | 953733.98 | 1278582.14 | 03-OCT-15:00 | 0.00 | 0.00 | 01-OCT-00:03 |
November | 1016281.13 | 1397194.29 | 17-NOV-15:00 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 1040701.27 | 1535257.57 | 10-DEC-14:59 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 962517.61 | 0.00 | ||||
Minimum of Months | 372092.91 | 883334.89 | 0.00 | 0.00 | ||
Maximum of Months | 1493976.77 | 1828218.94 | 0.00 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 11593.96 | 37891.82 | 18-JAN-13:00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 11557.11 | 37783.78 | 01-FEB-12:40 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 11853.01 | 37047.62 | 01-MAR-12:20 |
April | 0.00 | 0.00 | 01-APR-00:02 | 10743.33 | 35478.89 | 03-APR-11:30 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 10579.74 | 33923.17 | 01-MAY-11:50 |
June | 0.00 | 0.00 | 01-JUN-00:02 | 10423.15 | 32401.89 | 01-JUN-12:00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 9558.97 | 31450.61 | 03-JUL-11:30 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 10438.09 | 32163.19 | 31-AUG-11:20 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 10197.47 | 33515.92 | 29-SEP-11:40 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 10635.55 | 35244.88 | 31-OCT-11:30 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 11229.96 | 36773.88 | 30-NOV-12:40 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 11211.50 | 37678.73 | 28-DEC-13:00 |
Annual Sum or Average | 0.00 | 10831.26 | ||||
Minimum of Months | 0.00 | 0.00 | 9558.97 | 31450.61 | ||
Maximum of Months | 0.00 | 0.00 | 11853.01 | 37891.82 |
Report: PlantLoopDemandReportMonthly
For: TOWERWATERSYS
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 692442.13 | 5768476.73 | 02-JAN-14:00 | 504.78 | 101845.20 | 25-JAN-09:00 |
February | 856310.44 | 4457955.46 | 10-FEB-16:20 | 1008.39 | 171917.84 | 04-FEB-08:50 |
March | 1050581.82 | 5376060.16 | 14-MAR-09:50 | 577.17 | 175626.41 | 16-MAR-05:40 |
April | 1358338.36 | 5659709.06 | 14-APR-15:00 | 52.63 | 27656.03 | 02-APR-02:20 |
May | 2175610.71 | 6442500.31 | 31-MAY-13:00 | 5.39 | 22654.81 | 07-MAY-24:00 |
June | 2972889.95 | 6694093.39 | 28-JUN-11:50 | 0.00 | 0.00 | 01-JUN-00:02 |
July | 3112700.34 | 7034522.74 | 25-JUL-16:00 | 0.00 | 0.00 | 01-JUL-00:03 |
August | 3204280.14 | 7111879.69 | 21-AUG-16:00 | 0.00 | 0.00 | 01-AUG-00:05 |
September | 2892129.02 | 6684830.96 | 22-SEP-17:00 | 0.00 | 0.00 | 01-SEP-00:03 |
October | 2261221.20 | 7417011.64 | 04-OCT-05:04 | 0.17 | 1506.02 | 16-OCT-00:50 |
November | 1612596.45 | 6272718.88 | 29-NOV-12:00 | 375.46 | 104778.24 | 12-NOV-23:10 |
December | 881662.20 | 5026791.32 | 07-DEC-15:00 | 845.92 | 166847.41 | 15-DEC-07:00 |
Annual Sum or Average | 1928188.38 | 276.75 | ||||
Minimum of Months | 692442.13 | 4457955.46 | 0.00 | 0.00 | ||
Maximum of Months | 3204280.14 | 7417011.64 | 1008.39 | 175626.41 |
Report: FanReportMonthly
For: CAV_BAS FAN
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.168521E+11 | 0.84 | 10318.97 | 01-JAN-00:15 | 1.37 |
February | 0.149587E+11 | 0.83 | 10318.97 | 01-FEB-05:12 | 1.38 |
March | 0.165852E+11 | 0.83 | 10318.97 | 01-MAR-05:12 | 1.38 |
April | 0.153607E+11 | 0.79 | 10318.97 | 01-APR-04:12 | 1.38 |
May | 0.170495E+11 | 0.85 | 10318.97 | 01-MAY-00:43 | 1.37 |
June | 0.167602E+11 | 0.86 | 10318.97 | 01-JUN-03:02 | 1.38 |
July | 0.168016E+11 | 0.83 | 10318.97 | 01-JUL-03:02 | 1.38 |
August | 0.181435E+11 | 0.90 | 10318.97 | 01-AUG-03:02 | 1.38 |
September | 0.170742E+11 | 0.88 | 10318.97 | 01-SEP-03:02 | 1.38 |
October | 0.174756E+11 | 0.87 | 10318.97 | 01-OCT-13:55 | 1.36 |
November | 0.169946E+11 | 0.87 | 10318.97 | 01-NOV-04:12 | 1.38 |
December | 0.169079E+11 | 0.84 | 10318.97 | 01-DEC-05:11 | 1.38 |
Annual Sum or Average | 0.200964E+12 | 0.85 | |||
Minimum of Months | 0.149587E+11 | 0.79 | 10318.97 | 1.36 | |
Maximum of Months | 0.181435E+11 | 0.90 | 10318.97 | 1.38 |
Report: FanReportMonthly
For: VAV_BOT WITH REHEAT FAN
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.476305E+10 | 0.34 | 21783.72 | 07-JAN-06:02 | 1.75 |
February | 0.503206E+10 | 0.37 | 21783.72 | 18-FEB-05:11 | 1.75 |
March | 0.646833E+10 | 0.43 | 21783.72 | 06-MAR-06:02 | 1.75 |
April | 0.707909E+10 | 0.49 | 18680.68 | 29-APR-05:02 | 1.59 |
May | 0.671205E+10 | 0.45 | 21783.72 | 16-MAY-05:03 | 1.75 |
June | 0.736381E+10 | 0.50 | 21783.72 | 09-JUN-05:02 | 1.75 |
July | 0.808964E+10 | 0.53 | 21783.72 | 01-JUL-05:02 | 1.75 |
August | 0.907733E+10 | 0.56 | 21783.72 | 28-AUG-05:02 | 1.75 |
September | 0.692893E+10 | 0.47 | 21783.72 | 06-SEP-04:12 | 1.75 |
October | 0.719731E+10 | 0.47 | 21783.72 | 04-OCT-05:02 | 1.75 |
November | 0.662022E+10 | 0.44 | 21783.72 | 29-NOV-06:03 | 1.75 |
December | 0.600621E+10 | 0.41 | 21349.64 | 01-DEC-05:11 | 1.73 |
Annual Sum or Average | 0.813380E+11 | 0.45 | |||
Minimum of Months | 0.476305E+10 | 0.34 | 18680.68 | 1.59 | |
Maximum of Months | 0.907733E+10 | 0.56 | 21783.72 | 1.75 |
Report: FanReportMonthly
For: VAV_MID WITH REHEAT FAN
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.372713E+11 | 0.31 | 196129.34 | 14-JAN-06:03 | 1.71 |
February | 0.370415E+11 | 0.33 | 182062.82 | 18-FEB-06:03 | 1.63 |
March | 0.461309E+11 | 0.35 | 205372.79 | 06-MAR-06:02 | 1.76 |
April | 0.486238E+11 | 0.37 | 205372.79 | 25-APR-04:12 | 1.76 |
May | 0.581987E+11 | 0.41 | 205372.79 | 03-MAY-05:03 | 1.76 |
June | 0.610592E+11 | 0.44 | 205372.79 | 01-JUN-03:02 | 1.76 |
July | 0.623808E+11 | 0.44 | 205372.79 | 06-JUL-04:02 | 1.76 |
August | 0.631200E+11 | 0.44 | 205372.79 | 12-AUG-05:03 | 1.76 |
September | 0.599828E+11 | 0.43 | 205372.79 | 06-SEP-05:02 | 1.76 |
October | 0.577734E+11 | 0.40 | 205372.79 | 03-OCT-03:02 | 1.76 |
November | 0.476024E+11 | 0.35 | 205372.79 | 24-NOV-06:03 | 1.76 |
December | 0.390899E+11 | 0.32 | 204471.34 | 09-DEC-06:02 | 1.75 |
Annual Sum or Average | 0.618275E+12 | 0.38 | |||
Minimum of Months | 0.370415E+11 | 0.31 | 182062.82 | 1.63 | |
Maximum of Months | 0.631200E+11 | 0.44 | 205372.79 | 1.76 |
Report: FanReportMonthly
For: VAV_TOP WITH REHEAT FAN
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.344603E+10 | 0.29 | 14581.22 | 14-JAN-06:03 | 1.34 |
February | 0.357265E+10 | 0.31 | 12635.80 | 18-FEB-06:03 | 1.23 |
March | 0.455441E+10 | 0.34 | 19330.22 | 06-MAR-06:02 | 1.60 |
April | 0.503629E+10 | 0.36 | 16878.25 | 24-APR-04:11 | 1.47 |
May | 0.625942E+10 | 0.41 | 22117.41 | 22-MAY-04:11 | 1.75 |
June | 0.660097E+10 | 0.44 | 22117.41 | 17-JUN-03:02 | 1.75 |
July | 0.685507E+10 | 0.44 | 22117.41 | 03-JUL-03:02 | 1.75 |
August | 0.680805E+10 | 0.44 | 21898.95 | 28-AUG-03:02 | 1.74 |
September | 0.630795E+10 | 0.43 | 22117.41 | 05-SEP-04:11 | 1.75 |
October | 0.581501E+10 | 0.38 | 20894.84 | 13-OCT-05:02 | 1.69 |
November | 0.460452E+10 | 0.34 | 20594.90 | 10-NOV-06:02 | 1.67 |
December | 0.367236E+10 | 0.30 | 16054.49 | 09-DEC-06:02 | 1.43 |
Annual Sum or Average | 0.635327E+11 | 0.37 | |||
Minimum of Months | 0.344603E+10 | 0.29 | 12635.80 | 1.23 | |
Maximum of Months | 0.685507E+10 | 0.44 | 22117.41 | 1.75 |
Report: FanReportMonthly
For: AIRLOOP DATACENTER BASEMENT SUPPLY FAN
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.951635E+11 | 1.35 | 35529.97 | 01-JAN-00:05 | 1.35 |
February | 0.859541E+11 | 1.35 | 35529.97 | 01-FEB-00:10 | 1.35 |
March | 0.951635E+11 | 1.35 | 35529.97 | 01-MAR-00:10 | 1.35 |
April | 0.920937E+11 | 1.35 | 35529.97 | 01-APR-00:02 | 1.35 |
May | 0.951635E+11 | 1.35 | 35529.97 | 01-MAY-00:05 | 1.35 |
June | 0.920937E+11 | 1.35 | 35529.97 | 01-JUN-00:02 | 1.35 |
July | 0.951635E+11 | 1.35 | 35529.97 | 01-JUL-00:03 | 1.35 |
August | 0.951635E+11 | 1.35 | 35529.97 | 01-AUG-00:05 | 1.35 |
September | 0.920937E+11 | 1.35 | 35529.97 | 01-SEP-00:03 | 1.35 |
October | 0.951635E+11 | 1.35 | 35529.97 | 01-OCT-00:03 | 1.35 |
November | 0.920937E+11 | 1.35 | 35529.97 | 01-NOV-00:10 | 1.35 |
December | 0.951635E+11 | 1.35 | 35529.97 | 01-DEC-00:10 | 1.35 |
Annual Sum or Average | 0.112047E+13 | 1.35 | |||
Minimum of Months | 0.859541E+11 | 1.35 | 35529.97 | 1.35 | |
Maximum of Months | 0.951635E+11 | 1.35 | 35529.97 | 1.35 |
Report: FanReportMonthly
For: AIRLOOP DATACENTER BOT SUPPLY FAN
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.144032E+10 | 0.91 | 537.75 | 01-JAN-00:05 | 0.91 |
February | 0.130093E+10 | 0.91 | 537.75 | 01-FEB-00:10 | 0.91 |
March | 0.144032E+10 | 0.91 | 537.75 | 01-MAR-00:10 | 0.91 |
April | 0.139386E+10 | 0.91 | 537.75 | 01-APR-00:02 | 0.91 |
May | 0.144032E+10 | 0.91 | 537.75 | 01-MAY-00:05 | 0.91 |
June | 0.139386E+10 | 0.91 | 537.75 | 01-JUN-00:02 | 0.91 |
July | 0.144032E+10 | 0.91 | 537.75 | 01-JUL-00:03 | 0.91 |
August | 0.144032E+10 | 0.91 | 537.75 | 01-AUG-00:05 | 0.91 |
September | 0.139386E+10 | 0.91 | 537.75 | 01-SEP-00:03 | 0.91 |
October | 0.144032E+10 | 0.91 | 537.75 | 01-OCT-00:03 | 0.91 |
November | 0.139386E+10 | 0.91 | 537.75 | 01-NOV-00:10 | 0.91 |
December | 0.144032E+10 | 0.91 | 537.75 | 01-DEC-00:10 | 0.91 |
Annual Sum or Average | 0.169586E+11 | 0.91 | |||
Minimum of Months | 0.130093E+10 | 0.91 | 537.75 | 0.91 | |
Maximum of Months | 0.144032E+10 | 0.91 | 537.75 | 0.91 |
Report: FanReportMonthly
For: AIRLOOP DATACENTER MID SUPPLY FAN
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.137355E+11 | 0.91 | 5128.23 | 01-JAN-00:05 | 0.91 |
February | 0.124062E+11 | 0.91 | 5128.23 | 01-FEB-00:10 | 0.91 |
March | 0.137355E+11 | 0.91 | 5128.23 | 01-MAR-00:10 | 0.91 |
April | 0.132924E+11 | 0.91 | 5128.23 | 01-APR-00:02 | 0.91 |
May | 0.137355E+11 | 0.91 | 5128.23 | 01-MAY-00:15 | 0.91 |
June | 0.132924E+11 | 0.91 | 5128.23 | 01-JUN-00:02 | 0.91 |
July | 0.137355E+11 | 0.91 | 5128.23 | 01-JUL-00:03 | 0.91 |
August | 0.137355E+11 | 0.91 | 5128.23 | 01-AUG-00:05 | 0.91 |
September | 0.132924E+11 | 0.91 | 5128.23 | 01-SEP-00:03 | 0.91 |
October | 0.137355E+11 | 0.91 | 5128.23 | 01-OCT-00:03 | 0.91 |
November | 0.132924E+11 | 0.91 | 5128.23 | 01-NOV-00:10 | 0.91 |
December | 0.137355E+11 | 0.91 | 5128.23 | 01-DEC-00:10 | 0.91 |
Annual Sum or Average | 0.161724E+12 | 0.91 | |||
Minimum of Months | 0.124062E+11 | 0.91 | 5128.23 | 0.91 | |
Maximum of Months | 0.137355E+11 | 0.91 | 5128.23 | 0.91 |
Report: FanReportMonthly
For: AIRLOOP DATACENTER TOP SUPPLY FAN
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.140078E+10 | 0.91 | 522.99 | 01-JAN-00:05 | 0.91 |
February | 0.126522E+10 | 0.91 | 522.99 | 01-FEB-00:10 | 0.91 |
March | 0.140078E+10 | 0.91 | 522.99 | 01-MAR-00:10 | 0.91 |
April | 0.135559E+10 | 0.91 | 522.99 | 01-APR-00:02 | 0.91 |
May | 0.140078E+10 | 0.91 | 522.99 | 01-MAY-00:05 | 0.91 |
June | 0.135559E+10 | 0.91 | 522.99 | 01-JUN-00:02 | 0.91 |
July | 0.140078E+10 | 0.91 | 522.99 | 01-JUL-00:03 | 0.91 |
August | 0.140078E+10 | 0.91 | 522.99 | 01-AUG-00:05 | 0.91 |
September | 0.135559E+10 | 0.91 | 522.99 | 01-SEP-00:03 | 0.91 |
October | 0.140078E+10 | 0.91 | 522.99 | 01-OCT-00:03 | 0.91 |
November | 0.135559E+10 | 0.91 | 522.99 | 01-NOV-00:10 | 0.91 |
December | 0.140078E+10 | 0.91 | 522.99 | 01-DEC-00:10 | 0.91 |
Annual Sum or Average | 0.164930E+11 | 0.91 | |||
Minimum of Months | 0.126522E+10 | 0.91 | 522.99 | 0.91 | |
Maximum of Months | 0.140078E+10 | 0.91 | 522.99 | 0.91 |
Report: PumpReportMonthly
For: HEATSYS1 PUMP
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 13213156.14 | 11891840.53 | 1809.10 | 25-JAN-06:03 | 1628.19 | 1628.19 | 27.69 | 2.44 |
February | 15260941.51 | 13734847.36 | 2772.94 | 04-FEB-06:02 | 2495.65 | 2495.65 | 42.45 | 5.18 |
March | 7383552.09 | 6645196.88 | 1720.29 | 16-MAR-05:03 | 1548.26 | 1548.26 | 26.90 | 2.28 |
April | 620.73 | 558.65 | 0.68 | 19-APR-06:00 | 0.61 | 0.61 | 18.85 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 18.85 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:02 | 0.00 | 0.00 | 18.85 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 18.85 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 18.85 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 18.85 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 18.85 | 0.00 |
November | 2006207.02 | 1805586.32 | 514.10 | 13-NOV-06:02 | 462.69 | 462.69 | 20.21 | 0.56 |
December | 15681840.50 | 14113656.45 | 2033.07 | 15-DEC-06:02 | 1829.76 | 1829.76 | 28.22 | 2.89 |
Annual Sum or Average | 53546318.00 | 48191686.20 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.85 | 0.00 | |
Maximum of Months | 15681840.50 | 14113656.45 | 2772.94 | 2495.65 | 2495.65 | 42.45 | 5.18 |
Report: PumpReportMonthly
For: COOLSYS1 PUMP SECONDARY
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.111910E+10 | 0.100719E+10 | 23217.18 | 14-JAN-06:03 | 20895.46 | 20895.46 | 9.05 | 141.35 |
February | 0.139908E+10 | 0.125918E+10 | 23217.18 | 18-FEB-06:03 | 20895.46 | 20895.46 | 8.93 | 141.35 |
March | 0.193530E+10 | 0.174177E+10 | 23217.18 | 06-MAR-06:02 | 20895.46 | 20895.46 | 8.85 | 141.35 |
April | 0.227867E+10 | 0.205080E+10 | 20444.15 | 25-APR-04:12 | 18399.73 | 18399.73 | 8.37 | 134.44 |
May | 0.340401E+10 | 0.306361E+10 | 23217.18 | 08-MAY-04:13 | 20895.46 | 20895.46 | 9.67 | 141.35 |
June | 0.372574E+10 | 0.335316E+10 | 23217.18 | 13-JUN-05:03 | 20895.46 | 20895.46 | 9.04 | 141.35 |
July | 0.376039E+10 | 0.338435E+10 | 23217.18 | 18-JUL-05:03 | 20895.46 | 20895.46 | 9.02 | 141.35 |
August | 0.393810E+10 | 0.354429E+10 | 23214.77 | 24-AUG-05:03 | 20893.30 | 20893.30 | 9.07 | 141.32 |
September | 0.380236E+10 | 0.342212E+10 | 23217.18 | 05-SEP-04:11 | 20895.46 | 20895.46 | 8.63 | 141.35 |
October | 0.341555E+10 | 0.307399E+10 | 23217.18 | 04-OCT-05:02 | 20895.46 | 20895.46 | 8.77 | 141.35 |
November | 0.253808E+10 | 0.228427E+10 | 23217.18 | 22-NOV-06:03 | 20895.46 | 20895.46 | 9.04 | 141.35 |
December | 0.136291E+10 | 0.122662E+10 | 23035.26 | 23-DEC-06:03 | 20731.74 | 20731.74 | 8.94 | 140.90 |
Annual Sum or Average | 0.326793E+11 | 0.294114E+11 | ||||||
Minimum of Months | 0.111910E+10 | 0.100719E+10 | 20444.15 | 18399.73 | 18399.73 | 8.37 | 134.44 | |
Maximum of Months | 0.393810E+10 | 0.354429E+10 | 23217.18 | 20895.46 | 20895.46 | 9.67 | 141.35 |
Report: PumpReportMonthly
For: COOLSYS1 CHILLER1 PUMP
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.133599E+11 | 0.120239E+11 | 7989.88 | 01-JAN-00:15 | 7190.89 | 7190.89 | 6.79 | 70.68 |
February | 0.122195E+11 | 0.109976E+11 | 7989.88 | 01-FEB-05:12 | 7190.89 | 7190.89 | 7.35 | 70.68 |
March | 0.156174E+11 | 0.140557E+11 | 7989.88 | 01-MAR-05:12 | 7190.89 | 7190.89 | 8.78 | 70.68 |
April | 0.174881E+11 | 0.157393E+11 | 7989.88 | 01-APR-00:02 | 7190.89 | 7190.89 | 6.93 | 70.68 |
May | 0.167695E+11 | 0.150925E+11 | 7989.88 | 01-MAY-00:20 | 7190.89 | 7190.89 | 6.88 | 70.68 |
June | 0.180475E+11 | 0.162427E+11 | 7989.88 | 01-JUN-00:02 | 7190.89 | 7190.89 | 9.04 | 70.68 |
July | 0.194946E+11 | 0.175451E+11 | 7989.88 | 01-JUL-00:08 | 7190.89 | 7190.89 | 6.98 | 70.68 |
August | 0.198801E+11 | 0.178921E+11 | 7989.88 | 01-AUG-00:05 | 7190.89 | 7190.89 | 10.37 | 70.68 |
September | 0.171178E+11 | 0.154060E+11 | 7989.88 | 01-SEP-00:03 | 7190.89 | 7190.89 | 10.11 | 70.68 |
October | 0.171256E+11 | 0.154130E+11 | 7989.88 | 01-OCT-00:03 | 7190.89 | 7190.89 | 7.35 | 70.68 |
November | 0.153092E+11 | 0.137783E+11 | 7989.88 | 01-NOV-04:12 | 7190.89 | 7190.89 | 12.46 | 35.34 |
December | 0.153227E+11 | 0.137904E+11 | 7989.88 | 01-DEC-00:12 | 7190.89 | 7190.89 | 7.04 | 70.68 |
Annual Sum or Average | 0.197752E+12 | 0.177977E+12 | ||||||
Minimum of Months | 0.122195E+11 | 0.109976E+11 | 7989.88 | 7190.89 | 7190.89 | 6.79 | 35.34 | |
Maximum of Months | 0.198801E+11 | 0.178921E+11 | 7989.88 | 7190.89 | 7190.89 | 12.46 | 70.68 |
Report: PumpReportMonthly
For: COOLSYS1 CHILLER2 PUMP
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.459737E+09 | 0.413764E+09 | 7989.88 | 02-JAN-09:30 | 7190.89 | 7190.89 | 12.51 | 35.34 |
February | 0.410371E+09 | 0.369334E+09 | 7989.88 | 02-FEB-06:06 | 7190.89 | 7190.89 | 12.61 | 35.34 |
March | 0.157289E+10 | 0.141560E+10 | 7989.88 | 03-MAR-14:10 | 7190.89 | 7190.89 | 12.50 | 35.34 |
April | 0.160549E+10 | 0.144494E+10 | 7989.88 | 03-APR-14:30 | 7190.89 | 7190.89 | 12.64 | 35.34 |
May | 0.418843E+10 | 0.376959E+10 | 7989.88 | 01-MAY-07:50 | 7190.89 | 7190.89 | 12.43 | 35.34 |
June | 0.543503E+10 | 0.489153E+10 | 7989.88 | 01-JUN-05:05 | 7190.89 | 7190.89 | 12.45 | 35.34 |
July | 0.532501E+10 | 0.479251E+10 | 7989.88 | 03-JUL-03:04 | 7190.89 | 7190.89 | 12.57 | 35.34 |
August | 0.583708E+10 | 0.525338E+10 | 7989.88 | 01-AUG-07:30 | 7190.89 | 7190.89 | 12.48 | 35.34 |
September | 0.557987E+10 | 0.502188E+10 | 7989.88 | 01-SEP-07:50 | 7190.89 | 7190.89 | 12.40 | 35.34 |
October | 0.434113E+10 | 0.390702E+10 | 7989.88 | 02-OCT-03:04 | 7190.89 | 7190.89 | 12.60 | 35.34 |
November | 0.293252E+10 | 0.263927E+10 | 7989.88 | 01-NOV-04:12 | 7190.89 | 7190.89 | 12.46 | 35.34 |
December | 0.675464E+09 | 0.607918E+09 | 7989.88 | 01-DEC-14:40 | 7190.89 | 7190.89 | 12.64 | 35.34 |
Annual Sum or Average | 0.383630E+11 | 0.345267E+11 | ||||||
Minimum of Months | 0.410371E+09 | 0.369334E+09 | 7989.88 | 7190.89 | 7190.89 | 12.40 | 35.34 | |
Maximum of Months | 0.583708E+10 | 0.525338E+10 | 7989.88 | 7190.89 | 7190.89 | 12.64 | 35.34 |
Report: PumpReportMonthly
For: PLANT CIRC PUMP
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.919332E+10 | 0.827399E+10 | 3432.39 | 01-JAN-00:05 | 3089.15 | 3089.15 | 26.37 | 14.34 |
February | 0.830364E+10 | 0.747328E+10 | 3432.39 | 01-FEB-00:10 | 3089.15 | 3089.15 | 24.96 | 14.34 |
March | 0.919332E+10 | 0.827399E+10 | 3432.39 | 01-MAR-00:10 | 3089.15 | 3089.15 | 30.12 | 14.34 |
April | 0.889676E+10 | 0.800708E+10 | 3432.39 | 01-APR-00:02 | 3089.15 | 3089.15 | 41.03 | 14.34 |
May | 0.919332E+10 | 0.827399E+10 | 3432.39 | 01-MAY-00:05 | 3089.15 | 3089.15 | 28.47 | 14.34 |
June | 0.889676E+10 | 0.800708E+10 | 3432.39 | 01-JUN-00:02 | 3089.15 | 3089.15 | 37.49 | 14.34 |
July | 0.919332E+10 | 0.827399E+10 | 3432.39 | 01-JUL-00:03 | 3089.15 | 3089.15 | 41.88 | 14.34 |
August | 0.919332E+10 | 0.827399E+10 | 3432.39 | 01-AUG-00:05 | 3089.15 | 3089.15 | 48.10 | 14.34 |
September | 0.889676E+10 | 0.800708E+10 | 3432.39 | 01-SEP-00:03 | 3089.15 | 3089.15 | 34.28 | 14.34 |
October | 0.919332E+10 | 0.827399E+10 | 3432.39 | 01-OCT-00:03 | 3089.15 | 3089.15 | 38.61 | 14.34 |
November | 0.889676E+10 | 0.800708E+10 | 3432.39 | 01-NOV-00:10 | 3089.15 | 3089.15 | 36.89 | 14.34 |
December | 0.919332E+10 | 0.827399E+10 | 3432.39 | 01-DEC-00:10 | 3089.15 | 3089.15 | 42.29 | 14.34 |
Annual Sum or Average | 0.108244E+12 | 0.974195E+11 | ||||||
Minimum of Months | 0.830364E+10 | 0.747328E+10 | 3432.39 | 3089.15 | 3089.15 | 24.96 | 14.34 | |
Maximum of Months | 0.919332E+10 | 0.827399E+10 | 3432.39 | 3089.15 | 3089.15 | 48.10 | 14.34 |
Report: PumpReportMonthly
For: SWHSYS1 PUMP
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.112905E+09 | 33871561.48 | 56.21 | 01-JAN-06:05 | 16.86 | 16.86 | 56.41 | 0.44 |
February | 0.101979E+09 | 30593668.43 | 56.21 | 01-FEB-06:03 | 16.86 | 16.86 | 57.25 | 0.44 |
March | 0.112905E+09 | 33871561.48 | 56.21 | 01-MAR-06:03 | 16.86 | 16.86 | 56.99 | 0.44 |
April | 0.109263E+09 | 32778930.46 | 56.21 | 01-APR-05:03 | 16.86 | 16.86 | 57.32 | 0.44 |
May | 0.112905E+09 | 33871561.48 | 56.21 | 01-MAY-05:03 | 16.86 | 16.86 | 57.05 | 0.44 |
June | 0.109263E+09 | 32778930.46 | 56.21 | 01-JUN-05:03 | 16.86 | 16.86 | 57.51 | 0.44 |
July | 0.112905E+09 | 33871561.48 | 56.21 | 01-JUL-05:02 | 16.86 | 16.86 | 57.84 | 0.44 |
August | 0.112905E+09 | 33871561.48 | 56.21 | 01-AUG-05:03 | 16.86 | 16.86 | 57.64 | 0.44 |
September | 0.109263E+09 | 32778930.46 | 56.21 | 01-SEP-05:03 | 16.86 | 16.86 | 56.73 | 0.44 |
October | 0.112905E+09 | 33871561.48 | 56.21 | 01-OCT-05:03 | 16.86 | 16.86 | 56.67 | 0.44 |
November | 0.109263E+09 | 32778930.46 | 56.21 | 01-NOV-05:03 | 16.86 | 16.86 | 56.38 | 0.44 |
December | 0.112905E+09 | 33871561.48 | 56.21 | 01-DEC-06:03 | 16.86 | 16.86 | 56.43 | 0.44 |
Annual Sum or Average | 0.132937E+10 | 0.398810E+09 | ||||||
Minimum of Months | 0.101979E+09 | 30593668.43 | 56.21 | 16.86 | 16.86 | 56.38 | 0.44 | |
Maximum of Months | 0.112905E+09 | 33871561.48 | 56.21 | 16.86 | 16.86 | 57.84 | 0.44 |
Report: PumpReportMonthly
For: TOWERWATERSYS PUMP
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.354843E+11 | 0.319358E+11 | 41298.24 | 02-JAN-14:00 | 37168.41 | 37168.41 | 29.40 | 166.36 |
February | 0.324338E+11 | 0.291904E+11 | 41253.30 | 10-FEB-16:20 | 37127.97 | 37127.97 | 27.51 | 166.36 |
March | 0.438414E+11 | 0.394573E+11 | 41298.24 | 14-MAR-09:50 | 37168.41 | 37168.41 | 28.83 | 166.36 |
April | 0.488607E+11 | 0.439746E+11 | 41298.24 | 13-APR-12:10 | 37168.41 | 37168.41 | 28.92 | 166.36 |
May | 0.527551E+11 | 0.474796E+11 | 41298.24 | 10-MAY-09:20 | 37168.41 | 37168.41 | 28.81 | 166.36 |
June | 0.595997E+11 | 0.536398E+11 | 41298.24 | 01-JUN-12:10 | 37168.41 | 37168.41 | 29.04 | 166.36 |
July | 0.631222E+11 | 0.568100E+11 | 41298.24 | 03-JUL-03:06 | 37168.41 | 37168.41 | 29.61 | 166.36 |
August | 0.654775E+11 | 0.589298E+11 | 41298.24 | 01-AUG-07:30 | 37168.41 | 37168.41 | 29.96 | 166.36 |
September | 0.574145E+11 | 0.516730E+11 | 41298.24 | 01-SEP-08:70 | 37168.41 | 37168.41 | 29.23 | 166.36 |
October | 0.543328E+11 | 0.488996E+11 | 41298.24 | 02-OCT-03:06 | 37168.41 | 37168.41 | 29.68 | 166.36 |
November | 0.461186E+11 | 0.415067E+11 | 41298.24 | 01-NOV-04:12 | 37168.41 | 37168.41 | 28.84 | 166.36 |
December | 0.410227E+11 | 0.369205E+11 | 41281.65 | 07-DEC-15:00 | 37153.48 | 37153.48 | 28.33 | 166.36 |
Annual Sum or Average | 0.600463E+12 | 0.540417E+12 | ||||||
Minimum of Months | 0.324338E+11 | 0.291904E+11 | 41253.30 | 37127.97 | 37127.97 | 27.51 | 166.36 | |
Maximum of Months | 0.654775E+11 | 0.589298E+11 | 41298.24 | 37168.41 | 37168.41 | 29.96 | 166.36 |
Report: CondLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 82.00 | 82.00 | 1210.99 | 554039.54 | 25-JAN-06:03 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 18.92 | 18.92 | 1557.57 | 944505.66 | 04-FEB-05:11 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 17.74 | 17.74 | 711.59 | 524303.31 | 16-MAR-05:03 |
April | 0.00 | 0.00 | 01-APR-00:02 | 18.86 | 18.86 | 0.06 | 183.43 | 19-APR-06:00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 18.85 | 18.85 | 0.00 | 0.00 | 01-MAY-00:05 |
June | 0.00 | 0.00 | 01-JUN-00:02 | 18.85 | 18.85 | 0.00 | 0.00 | 01-JUN-00:02 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 18.85 | 18.85 | 0.00 | 0.00 | 01-JUL-00:03 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 18.85 | 18.85 | 0.00 | 0.00 | 01-AUG-00:05 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 18.85 | 18.85 | 0.00 | 0.00 | 01-SEP-00:03 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 18.85 | 18.85 | 0.00 | 0.00 | 01-OCT-00:03 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 18.85 | 18.85 | 204.65 | 144269.74 | 13-NOV-06:02 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 19.96 | 19.96 | 1517.56 | 650634.63 | 15-DEC-06:02 |
Annual Sum or Average | 0.00 | 428.49 | ||||||
Minimum of Months | 0.00 | 0.00 | 17.74 | 17.74 | 0.00 | 0.00 | ||
Maximum of Months | 0.00 | 0.00 | 82.00 | 82.00 | 1557.57 | 944505.66 |
Report: CondLoopDemandReportMonthly
For: COOLSYS1_SUPPLY
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 451952.03 | 2136733.98 | 14-JAN-06:08 | 10.31 | 6.70 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 550111.34 | 2390541.02 | 13-FEB-05:16 | 10.74 | 6.70 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 626999.83 | 2854610.24 | 06-MAR-06:06 | 11.52 | 6.70 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 758483.76 | 2644326.91 | 15-APR-05:03 | 11.17 | 6.70 | 0.00 | 0.00 | 01-APR-00:02 |
May | 939271.84 | 3299070.62 | 24-MAY-05:03 | 12.27 | 6.70 | 0.00 | 0.00 | 01-MAY-00:05 |
June | 1045976.96 | 3132395.78 | 06-JUN-05:02 | 11.99 | 6.70 | 0.00 | 0.00 | 01-JUN-00:02 |
July | 1039435.34 | 2794448.37 | 03-JUL-03:06 | 11.42 | 6.70 | 0.00 | 0.00 | 01-JUL-00:03 |
August | 1063127.68 | 2896488.04 | 28-AUG-03:06 | 11.59 | 6.70 | 0.00 | 0.00 | 01-AUG-00:05 |
September | 1034197.87 | 3989796.57 | 26-SEP-04:13 | 13.44 | 7.74 | 0.00 | 0.00 | 01-SEP-00:03 |
October | 917337.33 | 3081188.63 | 31-OCT-05:02 | 11.90 | 6.70 | 0.00 | 0.00 | 01-OCT-00:03 |
November | 761486.22 | 2496461.24 | 01-NOV-04:13 | 10.92 | 6.70 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 511314.59 | 2804504.34 | 09-DEC-06:02 | 11.44 | 6.70 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 809424.82 | 0.00 | ||||||
Minimum of Months | 451952.03 | 2136733.98 | 10.31 | 6.70 | 0.00 | 0.00 | ||
Maximum of Months | 1063127.68 | 3989796.57 | 13.44 | 7.74 | 0.00 | 0.00 |
Report: CondLoopDemandReportMonthly
For: COOLSYS1_DEMAND
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 448270.53 | 4354311.47 | 14-JAN-06:03 | 14.06 | 10.37 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 547017.72 | 4165590.38 | 11-FEB-06:03 | 13.91 | 10.21 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 623184.89 | 4442981.74 | 06-MAR-06:02 | 14.21 | 10.45 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 753529.00 | 3936953.05 | 25-APR-04:12 | 13.69 | 10.01 | 0.00 | 0.00 | 01-APR-00:02 |
May | 936512.16 | 4656771.68 | 27-MAY-05:04 | 14.57 | 10.63 | 0.00 | 0.00 | 01-MAY-00:05 |
June | 1041267.13 | 4491770.56 | 19-JUN-03:02 | 14.65 | 10.48 | 0.00 | 0.00 | 01-JUN-00:02 |
July | 1034547.20 | 4493990.89 | 03-JUL-03:02 | 14.60 | 10.48 | 0.00 | 0.00 | 01-JUL-00:03 |
August | 1057289.28 | 4412459.63 | 28-AUG-03:02 | 14.44 | 10.41 | 0.00 | 0.00 | 01-AUG-00:05 |
September | 1031151.82 | 4842844.12 | 05-SEP-04:11 | 14.89 | 10.78 | 0.00 | 0.00 | 01-SEP-00:03 |
October | 915252.02 | 4395379.57 | 02-OCT-04:03 | 14.52 | 10.39 | 0.00 | 0.00 | 01-OCT-00:03 |
November | 757978.32 | 4347265.94 | 22-NOV-06:03 | 14.05 | 10.37 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 507198.89 | 4288194.02 | 11-DEC-05:12 | 14.27 | 10.31 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 805545.72 | 0.00 | ||||||
Minimum of Months | 448270.53 | 3936953.05 | 13.69 | 10.01 | 0.00 | 0.00 | ||
Maximum of Months | 1057289.28 | 4842844.12 | 14.89 | 10.78 | 0.00 | 0.00 |
Report: CondLoopDemandReportMonthly
For: SINGLE WATER PLANT LOOP
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 372092.91 | 883334.89 | 02-JAN-15:00 | 35.83 | 31.07 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 650404.24 | 1112972.66 | 11-FEB-14:00 | 40.29 | 32.82 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 899452.20 | 1365517.88 | 13-MAR-16:00 | 45.14 | 34.38 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 1256394.82 | 1720219.78 | 17-APR-15:00 | 51.90 | 38.47 | 0.00 | 0.00 | 01-APR-00:02 |
May | 731222.96 | 1172860.69 | 22-MAY-13:10 | 41.44 | 36.56 | 0.00 | 0.00 | 01-MAY-00:05 |
June | 1031768.97 | 1268882.83 | 11-JUN-13:00 | 43.29 | 35.70 | 0.00 | 0.00 | 01-JUN-00:02 |
July | 1285738.76 | 1708633.03 | 29-JUL-16:00 | 51.68 | 40.72 | 0.00 | 0.00 | 01-JUL-00:03 |
August | 1493976.77 | 1828218.94 | 23-AUG-13:00 | 53.94 | 40.30 | 0.00 | 0.00 | 01-AUG-00:05 |
September | 796325.86 | 1072559.21 | 20-SEP-16:00 | 39.51 | 34.50 | 0.00 | 0.00 | 01-SEP-00:03 |
October | 953733.98 | 1278582.14 | 03-OCT-15:00 | 43.48 | 35.42 | 0.00 | 0.00 | 01-OCT-00:03 |
November | 1016281.13 | 1397194.29 | 17-NOV-15:00 | 45.75 | 34.98 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 1040701.27 | 1535257.57 | 10-DEC-14:59 | 48.38 | 35.08 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 962517.61 | 0.00 | ||||||
Minimum of Months | 372092.91 | 883334.89 | 35.83 | 31.07 | 0.00 | 0.00 | ||
Maximum of Months | 1493976.77 | 1828218.94 | 53.94 | 40.72 | 0.00 | 0.00 |
Report: CondLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 57.80 | 57.80 | 11593.96 | 37891.82 | 18-JAN-13:00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 57.67 | 57.67 | 11557.11 | 37783.78 | 01-FEB-12:40 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 57.50 | 57.50 | 11853.01 | 37047.62 | 01-MAR-12:20 |
April | 0.00 | 0.00 | 01-APR-00:02 | 57.68 | 57.68 | 10743.33 | 35478.89 | 03-APR-11:30 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 57.56 | 57.56 | 10579.74 | 33923.17 | 01-MAY-11:50 |
June | 0.00 | 0.00 | 01-JUN-00:02 | 57.83 | 57.83 | 10423.15 | 32401.89 | 01-JUN-12:00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 58.12 | 58.12 | 9558.97 | 31450.61 | 03-JUL-11:30 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 57.96 | 57.96 | 10438.09 | 32163.19 | 31-AUG-11:20 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 57.09 | 57.09 | 10197.47 | 33515.92 | 29-SEP-11:40 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 57.00 | 57.00 | 10635.55 | 35244.88 | 31-OCT-11:30 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 56.86 | 56.86 | 11229.96 | 36773.88 | 30-NOV-12:40 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 56.86 | 56.86 | 11211.50 | 37678.73 | 28-DEC-13:00 |
Annual Sum or Average | 0.00 | 10831.26 | ||||||
Minimum of Months | 0.00 | 0.00 | 56.86 | 56.86 | 9558.97 | 31450.61 | ||
Maximum of Months | 0.00 | 0.00 | 58.12 | 58.12 | 11853.01 | 37891.82 |
Report: CondLoopDemandReportMonthly
For: TOWERWATERSYS
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 692442.13 | 5768476.73 | 02-JAN-14:00 | 29.40 | 26.39 | 504.78 | 101845.20 | 25-JAN-09:00 |
February | 856310.44 | 4457955.46 | 10-FEB-16:20 | 27.51 | 24.25 | 1008.39 | 171917.84 | 04-FEB-08:50 |
March | 1050581.82 | 5376060.16 | 14-MAR-09:50 | 28.83 | 25.60 | 577.17 | 175626.41 | 16-MAR-05:40 |
April | 1358338.36 | 5659709.06 | 14-APR-15:00 | 29.24 | 26.16 | 52.63 | 27656.03 | 02-APR-02:20 |
May | 2175610.71 | 6442500.31 | 31-MAY-13:00 | 30.36 | 27.32 | 5.39 | 22654.81 | 07-MAY-24:00 |
June | 2972889.95 | 6694093.39 | 28-JUN-11:50 | 30.73 | 27.55 | 0.00 | 0.00 | 01-JUN-00:02 |
July | 3112700.34 | 7034522.74 | 25-JUL-16:00 | 31.22 | 27.94 | 0.00 | 0.00 | 01-JUL-00:03 |
August | 3204280.14 | 7111879.69 | 21-AUG-16:00 | 31.33 | 28.02 | 0.00 | 0.00 | 01-AUG-00:05 |
September | 2892129.02 | 6684830.96 | 22-SEP-17:00 | 30.71 | 27.72 | 0.00 | 0.00 | 01-SEP-00:03 |
October | 2261221.20 | 7417011.64 | 04-OCT-05:04 | 31.77 | 27.75 | 0.17 | 1506.02 | 16-OCT-00:50 |
November | 1612596.45 | 6272718.88 | 29-NOV-12:00 | 30.12 | 26.82 | 375.46 | 104778.24 | 12-NOV-23:10 |
December | 881662.20 | 5026791.32 | 07-DEC-15:00 | 28.33 | 25.13 | 845.92 | 166847.41 | 15-DEC-07:00 |
Annual Sum or Average | 1928188.38 | 276.75 | ||||||
Minimum of Months | 692442.13 | 4457955.46 | 27.51 | 24.25 | 0.00 | 0.00 | ||
Maximum of Months | 3204280.14 | 7417011.64 | 31.77 | 28.02 | 1008.39 | 175626.41 |
Report: ZoneTemperatureOscillationReportMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV_BOT WITH REHEAT
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 2362444.28 | 0.00 | 0.103057E+12 | 0.476305E+10 | 0.00 | 0.00 |
February | 22819736.14 | 0.00 | 0.114866E+12 | 0.503206E+10 | 0.00 | 0.00 |
March | 7520453.92 | 0.00 | 0.157143E+12 | 0.646833E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.188351E+12 | 0.707909E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.203682E+12 | 0.671205E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.229803E+12 | 0.736381E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.248806E+12 | 0.808964E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.264772E+12 | 0.907733E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.218780E+12 | 0.692893E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.213335E+12 | 0.719731E+10 | 0.00 | 0.00 |
November | 164352.20 | 0.00 | 0.179437E+12 | 0.662022E+10 | 0.00 | 0.00 |
December | 11511603.16 | 0.00 | 0.142038E+12 | 0.600621E+10 | 0.00 | 0.00 |
Annual Sum or Average | 44378589.71 | 0.00 | 0.226407E+13 | 0.813380E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.103057E+12 | 0.476305E+10 | 0.00 | 0.00 |
Maximum of Months | 22819736.14 | 0.00 | 0.264772E+12 | 0.907733E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV_MID WITH REHEAT
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.237855E+10 | 0.00 | 0.851841E+12 | 0.372713E+11 | 0.00 | 0.00 |
February | 0.289377E+10 | 0.00 | 0.925583E+12 | 0.370415E+11 | 0.00 | 0.00 |
March | 0.134761E+10 | 0.00 | 0.115938E+13 | 0.461309E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.136184E+13 | 0.486238E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.177990E+13 | 0.581987E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.194752E+13 | 0.610592E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.200966E+13 | 0.623808E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.202869E+13 | 0.631200E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.194079E+13 | 0.599828E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.174324E+13 | 0.577734E+11 | 0.00 | 0.00 |
November | 0.354004E+09 | 0.00 | 0.137180E+13 | 0.476024E+11 | 0.00 | 0.00 |
December | 0.290149E+10 | 0.00 | 0.943657E+12 | 0.390899E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.987543E+10 | 0.00 | 0.180639E+14 | 0.618275E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.851841E+12 | 0.370415E+11 | 0.00 | 0.00 |
Maximum of Months | 0.290149E+10 | 0.00 | 0.202869E+13 | 0.631200E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV_TOP WITH REHEAT
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.109975E+10 | 0.00 | 0.826114E+11 | 0.344603E+10 | 0.00 | 0.00 |
February | 0.887856E+09 | 0.00 | 0.946209E+11 | 0.357265E+10 | 0.00 | 0.00 |
March | 0.563192E+09 | 0.00 | 0.121313E+12 | 0.455441E+10 | 0.00 | 0.00 |
April | 182403.44 | 0.00 | 0.146014E+12 | 0.503629E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.191148E+12 | 0.625942E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.210404E+12 | 0.660097E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.218686E+12 | 0.685507E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.217048E+12 | 0.680805E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.205579E+12 | 0.630795E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.179149E+12 | 0.581501E+10 | 0.00 | 0.00 |
November | 0.177040E+09 | 0.00 | 0.138899E+12 | 0.460452E+10 | 0.00 | 0.00 |
December | 0.118466E+10 | 0.00 | 0.937344E+11 | 0.367236E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.391268E+10 | 0.00 | 0.189920E+13 | 0.635327E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.826114E+11 | 0.344603E+10 | 0.00 | 0.00 |
Maximum of Months | 0.118466E+10 | 0.00 | 0.218686E+12 | 0.685507E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: CAV_BAS
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.798334E+11 | 0.168521E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.770349E+11 | 0.149587E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.892622E+11 | 0.165852E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.900736E+11 | 0.153607E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.114136E+12 | 0.170495E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.127747E+12 | 0.167602E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.132089E+12 | 0.168016E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.145293E+12 | 0.181435E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.127968E+12 | 0.170742E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.122846E+12 | 0.174756E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.107035E+12 | 0.169946E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.853396E+11 | 0.169079E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.129866E+13 | 0.200964E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.770349E+11 | 0.149587E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.145293E+12 | 0.181435E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER BASEMENT
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.433909E+12 | 0.189252E+12 | 0.00 | 0.12 |
February | 0.00 | 0.00 | 0.680482E+12 | 0.236345E+12 | 0.00 | 0.13 |
March | 0.00 | 0.00 | 0.107371E+13 | 0.334287E+12 | 0.00 | 0.11 |
April | 0.00 | 0.00 | 0.136349E+13 | 0.409850E+12 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.478346E+12 | 0.213202E+12 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.790871E+12 | 0.290782E+12 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.114896E+13 | 0.386113E+12 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.145377E+13 | 0.455956E+12 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.476511E+12 | 0.212063E+12 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.805963E+12 | 0.292386E+12 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.106491E+13 | 0.338736E+12 | 0.00 | 0.03 |
December | 0.00 | 0.00 | 0.137683E+13 | 0.392496E+12 | 0.00 | 0.03 |
Annual Sum or Average | 0.00 | 0.00 | 0.111478E+14 | 0.375147E+13 | 0.00 | 0.43 |
Minimum of Months | 0.00 | 0.00 | 0.433909E+12 | 0.189252E+12 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.145377E+13 | 0.455956E+12 | 0.00 | 0.13 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER BOT
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.736081E+10 | 0.302128E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.129275E+11 | 0.412105E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.210929E+11 | 0.607544E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.273954E+11 | 0.771179E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.931838E+10 | 0.368305E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.159774E+11 | 0.531193E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.233961E+11 | 0.724319E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.302530E+11 | 0.892071E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.940641E+10 | 0.369638E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.160777E+11 | 0.528964E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.211396E+11 | 0.621192E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.271732E+11 | 0.725174E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.221518E+12 | 0.685381E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.736081E+10 | 0.302128E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.302530E+11 | 0.892071E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER MID
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.600162E+11 | 0.267889E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.116056E+12 | 0.378862E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.197280E+12 | 0.572255E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.260732E+12 | 0.734528E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.873608E+11 | 0.347756E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.152274E+12 | 0.506213E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.223193E+12 | 0.690809E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.287156E+12 | 0.847969E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.878455E+11 | 0.348065E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.152481E+12 | 0.502499E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.198679E+12 | 0.586843E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.252176E+12 | 0.679129E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.207525E+13 | 0.646282E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.600162E+11 | 0.267889E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.287156E+12 | 0.847969E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER TOP
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.534022E+10 | 0.257740E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.112398E+11 | 0.374706E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.195430E+11 | 0.572520E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.261071E+11 | 0.739305E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.888761E+10 | 0.354359E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.154063E+11 | 0.513584E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.225570E+11 | 0.700047E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.288922E+11 | 0.856265E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.893106E+10 | 0.354566E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.152703E+11 | 0.506388E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.196417E+11 | 0.586097E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.247519E+11 | 0.674640E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.206568E+12 | 0.649022E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.534022E+10 | 0.257740E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.288922E+11 | 0.856265E+10 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV_BOT WITH REHEAT
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.476305E+10 | 0.103057E+12 | 2362444.28 | 35237215.19 | 0.492381E+10 | 0.00 | 0.00 | 0.00 |
February | 0.503206E+10 | 0.114866E+12 | 22819736.14 | 0.705324E+09 | 0.624516E+10 | 0.00 | 0.00 | 0.00 |
March | 0.646833E+10 | 0.157143E+12 | 7520453.92 | 0.106256E+09 | 0.976400E+10 | 0.00 | 0.00 | 0.00 |
April | 0.707909E+10 | 0.188351E+12 | 0.00 | 0.00 | 0.205083E+11 | 0.00 | 0.00 | 0.00 |
May | 0.671205E+10 | 0.203682E+12 | 0.00 | 0.00 | 0.494915E+11 | 0.00 | 0.00 | 0.00 |
June | 0.736381E+10 | 0.229803E+12 | 0.00 | 0.00 | 0.827486E+11 | 0.00 | 0.00 | 0.00 |
July | 0.808964E+10 | 0.248806E+12 | 0.00 | 0.00 | 0.937386E+11 | 0.00 | 0.00 | 0.00 |
August | 0.907733E+10 | 0.264772E+12 | 0.00 | 0.00 | 0.984822E+11 | 0.00 | 0.00 | 0.00 |
September | 0.692893E+10 | 0.218780E+12 | 0.00 | 0.00 | 0.716548E+11 | 0.00 | 0.00 | 0.00 |
October | 0.719731E+10 | 0.213335E+12 | 0.00 | 0.00 | 0.549662E+11 | 0.00 | 0.00 | 0.00 |
November | 0.662022E+10 | 0.179437E+12 | 164352.20 | 4960881.93 | 0.326405E+11 | 0.00 | 0.00 | 0.00 |
December | 0.600621E+10 | 0.142038E+12 | 11511603.16 | 60326906.27 | 0.930091E+10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.813380E+11 | 0.226407E+13 | 44378589.71 | 0.912105E+09 | 0.534465E+12 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.476305E+10 | 0.103057E+12 | 0.00 | 0.00 | 0.492381E+10 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.907733E+10 | 0.264772E+12 | 22819736.14 | 0.705324E+09 | 0.984822E+11 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV_MID WITH REHEAT
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.372713E+11 | 0.851841E+12 | 0.237855E+10 | 0.370783E+09 | 0.569078E+11 | 0.00 | 0.00 | 0.00 |
February | 0.370415E+11 | 0.925583E+12 | 0.289377E+10 | 0.787084E+10 | 0.666160E+11 | 0.00 | 0.00 | 0.00 |
March | 0.461309E+11 | 0.115938E+13 | 0.134761E+10 | 0.183987E+10 | 0.100608E+12 | 0.00 | 0.00 | 0.00 |
April | 0.486238E+11 | 0.136184E+13 | 0.00 | 0.00 | 0.199628E+12 | 0.00 | 0.00 | 0.00 |
May | 0.581987E+11 | 0.177990E+13 | 0.00 | 0.00 | 0.479713E+12 | 0.00 | 0.00 | 0.00 |
June | 0.610592E+11 | 0.194752E+13 | 0.00 | 0.00 | 0.745201E+12 | 0.00 | 0.00 | 0.00 |
July | 0.623808E+11 | 0.200966E+13 | 0.00 | 0.00 | 0.846333E+12 | 0.00 | 0.00 | 0.00 |
August | 0.631200E+11 | 0.202869E+13 | 0.00 | 0.00 | 0.831854E+12 | 0.00 | 0.00 | 0.00 |
September | 0.599828E+11 | 0.194079E+13 | 0.00 | 0.00 | 0.681736E+12 | 0.00 | 0.00 | 0.00 |
October | 0.577734E+11 | 0.174324E+13 | 0.00 | 0.00 | 0.505366E+12 | 0.00 | 0.00 | 0.00 |
November | 0.476024E+11 | 0.137180E+13 | 0.354004E+09 | 0.164878E+09 | 0.297263E+12 | 0.00 | 0.00 | 0.00 |
December | 0.390899E+11 | 0.943657E+12 | 0.290149E+10 | 0.116203E+10 | 0.977172E+11 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.618275E+12 | 0.180639E+14 | 0.987543E+10 | 0.114084E+11 | 0.490894E+13 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.370415E+11 | 0.851841E+12 | 0.00 | 0.00 | 0.569078E+11 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.631200E+11 | 0.202869E+13 | 0.290149E+10 | 0.787084E+10 | 0.846333E+12 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV_TOP WITH REHEAT
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.344603E+10 | 0.826114E+11 | 0.109975E+10 | 75819374.44 | 0.525047E+10 | 0.00 | 0.00 | 0.00 |
February | 0.357265E+10 | 0.946209E+11 | 0.887856E+09 | 0.672974E+09 | 0.540355E+10 | 0.00 | 0.00 | 0.00 |
March | 0.455441E+10 | 0.121313E+12 | 0.563192E+09 | 0.197508E+09 | 0.757496E+10 | 0.00 | 0.00 | 0.00 |
April | 0.503629E+10 | 0.146014E+12 | 182403.44 | 0.00 | 0.167917E+11 | 0.00 | 0.00 | 0.00 |
May | 0.625942E+10 | 0.191148E+12 | 0.00 | 0.00 | 0.464404E+11 | 0.00 | 0.00 | 0.00 |
June | 0.660097E+10 | 0.210404E+12 | 0.00 | 0.00 | 0.726883E+11 | 0.00 | 0.00 | 0.00 |
July | 0.685507E+10 | 0.218686E+12 | 0.00 | 0.00 | 0.822588E+11 | 0.00 | 0.00 | 0.00 |
August | 0.680805E+10 | 0.217048E+12 | 0.00 | 0.00 | 0.817653E+11 | 0.00 | 0.00 | 0.00 |
September | 0.630795E+10 | 0.205579E+12 | 0.00 | 0.00 | 0.673682E+11 | 0.00 | 0.00 | 0.00 |
October | 0.581501E+10 | 0.179149E+12 | 0.00 | 0.00 | 0.508731E+11 | 0.00 | 0.00 | 0.00 |
November | 0.460452E+10 | 0.138899E+12 | 0.177040E+09 | 39845714.58 | 0.295018E+11 | 0.00 | 0.00 | 0.00 |
December | 0.367236E+10 | 0.937344E+11 | 0.118466E+10 | 0.175504E+09 | 0.876651E+10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.635327E+11 | 0.189920E+13 | 0.391268E+10 | 0.116165E+10 | 0.474683E+12 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.344603E+10 | 0.826114E+11 | 0.00 | 0.00 | 0.525047E+10 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.685507E+10 | 0.218686E+12 | 0.118466E+10 | 0.672974E+09 | 0.822588E+11 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: CAV_BAS
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.168521E+11 | 0.798334E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.149587E+11 | 0.770349E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.165852E+11 | 0.892622E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.153607E+11 | 0.900736E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.170495E+11 | 0.114136E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.167602E+11 | 0.127747E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.168016E+11 | 0.132089E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.181435E+11 | 0.145293E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.170742E+11 | 0.127968E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.174756E+11 | 0.122846E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.169946E+11 | 0.107035E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.169079E+11 | 0.853396E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.200964E+12 | 0.129866E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.149587E+11 | 0.770349E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.181435E+11 | 0.145293E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER BASEMENT
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.951635E+11 | 0.340157E+12 | 0.00 | 0.00 | 0.00 | 0.334510E+09 | 0.00 | 0.00 |
February | 0.859541E+11 | 0.530443E+12 | 0.00 | 0.00 | 0.00 | 0.350608E+09 | 0.00 | 0.00 |
March | 0.951635E+11 | 0.834877E+12 | 0.00 | 0.00 | 0.00 | 0.293459E+09 | 0.00 | 0.00 |
April | 0.920937E+11 | 0.104574E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.951635E+11 | 0.360308E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.920937E+11 | 0.592182E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.951635E+11 | 0.858013E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.951635E+11 | 0.109298E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.920937E+11 | 0.356542E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.951635E+11 | 0.608741E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.920937E+11 | 0.818361E+12 | 0.00 | 0.00 | 0.00 | 89306177.20 | 0.00 | 0.00 |
December | 0.951635E+11 | 0.107957E+13 | 0.00 | 0.00 | 0.00 | 71787272.63 | 0.00 | 0.00 |
Annual Sum or Average | 0.112047E+13 | 0.851791E+13 | 0.00 | 0.00 | 0.00 | 0.113967E+10 | 0.00 | 0.00 |
Minimum of Months | 0.859541E+11 | 0.340157E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.951635E+11 | 0.109298E+13 | 0.00 | 0.00 | 0.00 | 0.350608E+09 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER BOT
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.144032E+10 | 0.577985E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.130093E+10 | 0.101074E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.144032E+10 | 0.164577E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.139386E+10 | 0.210775E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.144032E+10 | 0.707565E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.139386E+10 | 0.120593E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.144032E+10 | 0.175933E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.144032E+10 | 0.227726E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.139386E+10 | 0.710388E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.144032E+10 | 0.122284E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.139386E+10 | 0.163215E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.144032E+10 | 0.213617E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.169586E+11 | 0.169939E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.130093E+10 | 0.577985E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.144032E+10 | 0.227726E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER MID
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.137355E+11 | 0.469627E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.124062E+11 | 0.905764E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.137355E+11 | 0.153790E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.132924E+11 | 0.200571E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.137355E+11 | 0.663207E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.132924E+11 | 0.114946E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.137355E+11 | 0.167848E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.137355E+11 | 0.216094E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.132924E+11 | 0.663314E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.137355E+11 | 0.115966E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.132924E+11 | 0.153287E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.137355E+11 | 0.197998E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.161724E+12 | 0.159069E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.124062E+11 | 0.469627E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.137355E+11 | 0.216094E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER TOP
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.140078E+10 | 0.416360E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.126522E+10 | 0.875792E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.140078E+10 | 0.152186E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.135559E+10 | 0.200696E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.140078E+10 | 0.674479E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.135559E+10 | 0.116261E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.140078E+10 | 0.169573E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.140078E+10 | 0.217303E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.135559E+10 | 0.674099E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.140078E+10 | 0.116072E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.135559E+10 | 0.151363E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.140078E+10 | 0.194063E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.164930E+11 | 0.158159E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.126522E+10 | 0.416360E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.140078E+10 | 0.217303E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV_BOT WITH REHEAT
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.476305E+10 | 2362444.28 | 0.103057E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.503206E+10 | 22819736.14 | 0.114866E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.646833E+10 | 7520453.92 | 0.157143E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.707909E+10 | 0.00 | 0.188351E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.671205E+10 | 0.00 | 0.203682E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.736381E+10 | 0.00 | 0.229803E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.808964E+10 | 0.00 | 0.248806E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.907733E+10 | 0.00 | 0.264772E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.692893E+10 | 0.00 | 0.218780E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.719731E+10 | 0.00 | 0.213335E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.662022E+10 | 164352.20 | 0.179437E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.600621E+10 | 11511603.16 | 0.142038E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.813380E+11 | 44378589.71 | 0.226407E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.476305E+10 | 0.00 | 0.103057E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.907733E+10 | 22819736.14 | 0.264772E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV_MID WITH REHEAT
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.372713E+11 | 0.237855E+10 | 0.851841E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.370415E+11 | 0.289377E+10 | 0.925583E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.461309E+11 | 0.134761E+10 | 0.115938E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.486238E+11 | 0.00 | 0.136184E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.581987E+11 | 0.00 | 0.177990E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.610592E+11 | 0.00 | 0.194752E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.623808E+11 | 0.00 | 0.200966E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.631200E+11 | 0.00 | 0.202869E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.599828E+11 | 0.00 | 0.194079E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.577734E+11 | 0.00 | 0.174324E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.476024E+11 | 0.354004E+09 | 0.137180E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.390899E+11 | 0.290149E+10 | 0.943657E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.618275E+12 | 0.987543E+10 | 0.180639E+14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.370415E+11 | 0.00 | 0.851841E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.631200E+11 | 0.290149E+10 | 0.202869E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV_TOP WITH REHEAT
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.344603E+10 | 0.109975E+10 | 0.826114E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.357265E+10 | 0.887856E+09 | 0.946209E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.455441E+10 | 0.563192E+09 | 0.121313E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.503629E+10 | 182403.44 | 0.146014E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.625942E+10 | 0.00 | 0.191148E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.660097E+10 | 0.00 | 0.210404E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.685507E+10 | 0.00 | 0.218686E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.680805E+10 | 0.00 | 0.217048E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.630795E+10 | 0.00 | 0.205579E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.581501E+10 | 0.00 | 0.179149E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.460452E+10 | 0.177040E+09 | 0.138899E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.367236E+10 | 0.118466E+10 | 0.937344E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.635327E+11 | 0.391268E+10 | 0.189920E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.344603E+10 | 0.00 | 0.826114E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.685507E+10 | 0.118466E+10 | 0.218686E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: CAV_BAS
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.168521E+11 | 0.00 | 0.798334E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.149587E+11 | 0.00 | 0.770349E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.165852E+11 | 0.00 | 0.892622E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.153607E+11 | 0.00 | 0.900736E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.170495E+11 | 0.00 | 0.114136E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.167602E+11 | 0.00 | 0.127747E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.168016E+11 | 0.00 | 0.132089E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.181435E+11 | 0.00 | 0.145293E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.170742E+11 | 0.00 | 0.127968E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.174756E+11 | 0.00 | 0.122846E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.169946E+11 | 0.00 | 0.107035E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.169079E+11 | 0.00 | 0.853396E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.200964E+12 | 0.00 | 0.129866E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.149587E+11 | 0.00 | 0.770349E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.181435E+11 | 0.00 | 0.145293E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER BASEMENT
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.951635E+11 | 0.00 | 0.433909E+12 | 0.00 | 0.937524E+11 | 0.00 | 0.00 | 0.00 | 0.336016E+09 | 0.00 | 0.00 | 0.00 |
February | 0.859541E+11 | 0.00 | 0.680482E+12 | 0.00 | 0.150039E+12 | 0.00 | 0.00 | 0.00 | 0.352186E+09 | 0.00 | 0.00 | 0.00 |
March | 0.951635E+11 | 0.00 | 0.107371E+13 | 0.00 | 0.238828E+12 | 0.00 | 0.00 | 0.00 | 0.294780E+09 | 0.00 | 0.00 | 0.00 |
April | 0.920937E+11 | 0.00 | 0.136349E+13 | 0.00 | 0.317757E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.951635E+11 | 0.00 | 0.478346E+12 | 0.00 | 0.118038E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.920937E+11 | 0.00 | 0.790871E+12 | 0.00 | 0.198689E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.951635E+11 | 0.00 | 0.114896E+13 | 0.00 | 0.290949E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.951635E+11 | 0.00 | 0.145377E+13 | 0.00 | 0.360792E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.920937E+11 | 0.00 | 0.476511E+12 | 0.00 | 0.119969E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.951635E+11 | 0.00 | 0.805963E+12 | 0.00 | 0.197222E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.920937E+11 | 0.00 | 0.106491E+13 | 0.00 | 0.246553E+12 | 0.00 | 0.00 | 0.00 | 89708180.50 | 0.00 | 0.00 | 0.00 |
December | 0.951635E+11 | 0.00 | 0.137683E+13 | 0.00 | 0.297260E+12 | 0.00 | 0.00 | 0.00 | 72110416.25 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.112047E+13 | 0.00 | 0.111478E+14 | 0.00 | 0.262985E+13 | 0.00 | 0.00 | 0.00 | 0.114480E+10 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.859541E+11 | 0.00 | 0.433909E+12 | 0.00 | 0.937524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.951635E+11 | 0.00 | 0.145377E+13 | 0.00 | 0.360792E+12 | 0.00 | 0.00 | 0.00 | 0.352186E+09 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER BOT
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.144032E+10 | 0.00 | 0.736081E+10 | 0.00 | 0.158096E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.130093E+10 | 0.00 | 0.129275E+11 | 0.00 | 0.282012E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.144032E+10 | 0.00 | 0.210929E+11 | 0.00 | 0.463512E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.139386E+10 | 0.00 | 0.273954E+11 | 0.00 | 0.631793E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.144032E+10 | 0.00 | 0.931838E+10 | 0.00 | 0.224273E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.139386E+10 | 0.00 | 0.159774E+11 | 0.00 | 0.391807E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.144032E+10 | 0.00 | 0.233961E+11 | 0.00 | 0.580287E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.144032E+10 | 0.00 | 0.302530E+11 | 0.00 | 0.748039E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.139386E+10 | 0.00 | 0.940641E+10 | 0.00 | 0.230253E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.144032E+10 | 0.00 | 0.160777E+11 | 0.00 | 0.384932E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.139386E+10 | 0.00 | 0.211396E+11 | 0.00 | 0.481807E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.144032E+10 | 0.00 | 0.271732E+11 | 0.00 | 0.581142E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.169586E+11 | 0.00 | 0.221518E+12 | 0.00 | 0.515795E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.130093E+10 | 0.00 | 0.736081E+10 | 0.00 | 0.158096E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.144032E+10 | 0.00 | 0.302530E+11 | 0.00 | 0.748039E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER MID
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.137355E+11 | 0.00 | 0.600162E+11 | 0.00 | 0.130534E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.124062E+11 | 0.00 | 0.116056E+12 | 0.00 | 0.254800E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.137355E+11 | 0.00 | 0.197280E+12 | 0.00 | 0.434901E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.132924E+11 | 0.00 | 0.260732E+12 | 0.00 | 0.601605E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.137355E+11 | 0.00 | 0.873608E+11 | 0.00 | 0.210401E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.132924E+11 | 0.00 | 0.152274E+12 | 0.00 | 0.373289E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.137355E+11 | 0.00 | 0.223193E+12 | 0.00 | 0.553454E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.137355E+11 | 0.00 | 0.287156E+12 | 0.00 | 0.710614E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.132924E+11 | 0.00 | 0.878455E+11 | 0.00 | 0.215141E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.137355E+11 | 0.00 | 0.152481E+12 | 0.00 | 0.365144E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.132924E+11 | 0.00 | 0.198679E+12 | 0.00 | 0.453920E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.137355E+11 | 0.00 | 0.252176E+12 | 0.00 | 0.541774E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.161724E+12 | 0.00 | 0.207525E+13 | 0.00 | 0.484558E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.124062E+11 | 0.00 | 0.600162E+11 | 0.00 | 0.130534E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.137355E+11 | 0.00 | 0.287156E+12 | 0.00 | 0.710614E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER TOP
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.140078E+10 | 0.00 | 0.534022E+10 | 0.00 | 0.117662E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.126522E+10 | 0.00 | 0.112398E+11 | 0.00 | 0.248185E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.140078E+10 | 0.00 | 0.195430E+11 | 0.00 | 0.432443E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.135559E+10 | 0.00 | 0.261071E+11 | 0.00 | 0.603746E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.140078E+10 | 0.00 | 0.888761E+10 | 0.00 | 0.214281E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.135559E+10 | 0.00 | 0.154063E+11 | 0.00 | 0.378024E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.140078E+10 | 0.00 | 0.225570E+11 | 0.00 | 0.559969E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.140078E+10 | 0.00 | 0.288922E+11 | 0.00 | 0.716188E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.135559E+10 | 0.00 | 0.893106E+10 | 0.00 | 0.219007E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.140078E+10 | 0.00 | 0.152703E+11 | 0.00 | 0.366310E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.135559E+10 | 0.00 | 0.196417E+11 | 0.00 | 0.450538E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.140078E+10 | 0.00 | 0.247519E+11 | 0.00 | 0.534562E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.164930E+11 | 0.00 | 0.206568E+12 | 0.00 | 0.484091E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.126522E+10 | 0.00 | 0.534022E+10 | 0.00 | 0.117662E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.140078E+10 | 0.00 | 0.288922E+11 | 0.00 | 0.716188E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.102473E+10 | 0.420849E+10 | 0.00 | 99770668.37 | 25854211.25 | 0.00 | 0.126333E+11 | 0.00 | 0.40 |
February | 0.681977E+09 | 0.464362E+10 | 0.00 | 82632080.72 | 75904071.23 | 0.00 | 0.668461E+10 | 0.00 | 0.39 |
March | 0.141482E+09 | 0.709588E+10 | 0.00 | 75866858.59 | 69043224.13 | 0.00 | 0.793133E+10 | 0.00 | 0.39 |
April | 0.117770E+09 | 0.100487E+11 | 0.00 | 41500994.92 | 0.155738E+09 | 0.00 | 0.210780E+10 | 0.00 | 0.38 |
May | 91514295.39 | 0.258436E+11 | 0.00 | 5535093.64 | 0.429142E+09 | 0.00 | 0.174818E+09 | 0.00 | 0.40 |
June | 0.00 | 0.396609E+11 | 0.00 | 0.00 | 0.594467E+09 | 0.00 | 0.00 | 0.00 | 0.41 |
July | 473253.27 | 0.436971E+11 | 0.00 | 622886.17 | 0.781116E+09 | 0.00 | 3164782.96 | 0.00 | 0.40 |
August | 427902.60 | 0.471247E+11 | 0.00 | 318410.45 | 0.781396E+09 | 0.00 | 4521322.15 | 0.00 | 0.43 |
September | 3900344.96 | 0.392044E+11 | 0.00 | 2443626.88 | 0.749344E+09 | 0.00 | 45661228.52 | 0.00 | 0.42 |
October | 16831771.29 | 0.299027E+11 | 0.00 | 8876922.21 | 0.485664E+09 | 0.00 | 0.123894E+09 | 0.00 | 0.42 |
November | 0.955550E+09 | 0.190291E+11 | 0.00 | 50912314.65 | 0.251638E+09 | 0.00 | 0.327382E+10 | 0.00 | 0.42 |
December | 0.456493E+09 | 0.607679E+10 | 0.00 | 99920133.87 | 0.139925E+09 | 0.00 | 0.106272E+11 | 0.00 | 0.40 |
Annual Sum or Average | 0.349115E+10 | 0.276536E+12 | 0.00 | 0.468400E+09 | 0.453923E+10 | 0.00 | 0.436101E+11 | 0.00 | 0.40 |
Minimum of Months | 0.00 | 0.420849E+10 | 0.00 | 0.00 | 25854211.25 | 0.00 | 0.00 | 0.00 | 0.38 |
Maximum of Months | 0.102473E+10 | 0.471247E+11 | 0.00 | 99920133.87 | 0.781396E+09 | 0.00 | 0.126333E+11 | 0.00 | 0.43 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.157228E+10 | 0.813587E+10 | 0.00 | 49808943.69 | 0.124320E+10 | 0.00 | 0.117741E+11 | 0.00 | 0.51 |
February | 0.913977E+09 | 0.935037E+10 | 0.00 | 39507029.04 | 0.119260E+10 | 0.00 | 0.632252E+10 | 0.00 | 0.52 |
March | 0.603912E+09 | 0.127637E+11 | 0.00 | 45028117.02 | 0.651907E+10 | 0.00 | 0.883446E+10 | 0.00 | 0.61 |
April | 0.529646E+09 | 0.139557E+11 | 0.00 | 13125074.21 | 0.104753E+11 | 0.00 | 0.163008E+10 | 0.00 | 0.68 |
May | 0.00 | 0.221029E+11 | 0.00 | 0.00 | 0.114298E+11 | 0.00 | 0.00 | 0.00 | 0.60 |
June | 0.00 | 0.260468E+11 | 0.00 | 0.00 | 0.155661E+11 | 0.00 | 0.00 | 0.00 | 0.66 |
July | 0.00 | 0.249689E+11 | 0.00 | 0.00 | 0.214146E+11 | 0.00 | 0.00 | 0.00 | 0.69 |
August | 0.00 | 0.285087E+11 | 0.00 | 0.00 | 0.203901E+11 | 0.00 | 0.00 | 0.00 | 0.72 |
September | 0.00 | 0.274837E+11 | 0.00 | 0.00 | 0.139101E+11 | 0.00 | 0.00 | 0.00 | 0.62 |
October | 0.00 | 0.228148E+11 | 0.00 | 0.00 | 0.139218E+11 | 0.00 | 0.00 | 0.00 | 0.62 |
November | 0.957533E+09 | 0.178193E+11 | 0.00 | 14676404.19 | 0.898139E+10 | 0.00 | 0.154786E+10 | 0.00 | 0.60 |
December | 0.521695E+09 | 0.908293E+10 | 0.00 | 54121420.06 | 0.903047E+10 | 0.00 | 0.115112E+11 | 0.00 | 0.60 |
Annual Sum or Average | 0.509904E+10 | 0.223034E+12 | 0.00 | 0.216267E+09 | 0.134075E+12 | 0.00 | 0.416202E+11 | 0.00 | 0.62 |
Minimum of Months | 0.00 | 0.813587E+10 | 0.00 | 0.00 | 0.119260E+10 | 0.00 | 0.00 | 0.00 | 0.51 |
Maximum of Months | 0.157228E+10 | 0.285087E+11 | 0.00 | 54121420.06 | 0.214146E+11 | 0.00 | 0.117741E+11 | 0.00 | 0.72 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.437959E+11 | 0.641975E+11 | 0.00 | 0.263131E+09 | 0.199212E+11 | 0.00 | 0.704733E+11 | 0.00 | 0.48 |
February | 0.231958E+11 | 0.732835E+11 | 0.00 | 0.192276E+09 | 0.191958E+11 | 0.00 | 0.381735E+11 | 0.00 | 0.49 |
March | 0.218132E+11 | 0.109478E+12 | 0.00 | 0.226286E+09 | 0.232271E+11 | 0.00 | 0.595067E+11 | 0.00 | 0.51 |
April | 0.126221E+10 | 0.124066E+12 | 0.00 | 92573245.86 | 0.419878E+11 | 0.00 | 0.155810E+11 | 0.00 | 0.52 |
May | 0.00 | 0.198054E+12 | 0.00 | 33772.60 | 0.736087E+11 | 0.00 | 0.00 | 0.00 | 0.54 |
June | 0.00 | 0.241493E+12 | 0.00 | 0.00 | 0.907175E+11 | 0.00 | 0.00 | 0.00 | 0.57 |
July | 0.00 | 0.228818E+12 | 0.00 | 0.00 | 0.126098E+12 | 0.00 | 0.00 | 0.00 | 0.57 |
August | 0.00 | 0.259184E+12 | 0.00 | 0.00 | 0.101213E+12 | 0.00 | 0.00 | 0.00 | 0.57 |
September | 0.00 | 0.252091E+12 | 0.00 | 0.00 | 0.101782E+12 | 0.00 | 0.00 | 0.00 | 0.56 |
October | 0.00 | 0.209880E+12 | 0.00 | 0.00 | 0.658481E+11 | 0.00 | 0.00 | 0.00 | 0.52 |
November | 0.800012E+10 | 0.162733E+12 | 0.00 | 82995059.85 | 0.305251E+11 | 0.00 | 0.102932E+11 | 0.00 | 0.49 |
December | 0.282399E+11 | 0.664498E+11 | 0.00 | 0.256540E+09 | 0.390249E+11 | 0.00 | 0.754536E+11 | 0.00 | 0.48 |
Annual Sum or Average | 0.126307E+12 | 0.198973E+13 | 0.00 | 0.111383E+10 | 0.733150E+12 | 0.00 | 0.269481E+12 | 0.00 | 0.53 |
Minimum of Months | 0.00 | 0.641975E+11 | 0.00 | 0.00 | 0.191958E+11 | 0.00 | 0.00 | 0.00 | 0.48 |
Maximum of Months | 0.437959E+11 | 0.259184E+12 | 0.00 | 0.263131E+09 | 0.126098E+12 | 0.00 | 0.754536E+11 | 0.00 | 0.57 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.602214E+10 | 0.470779E+10 | 0.00 | 13692712.46 | 0.347875E+10 | 0.00 | 0.408862E+10 | 0.00 | 0.47 |
February | 0.265568E+10 | 0.665788E+10 | 0.00 | 13206028.96 | 0.271477E+10 | 0.00 | 0.253419E+10 | 0.00 | 0.47 |
March | 0.331447E+10 | 0.109209E+11 | 0.00 | 15856473.84 | 0.300419E+10 | 0.00 | 0.407310E+10 | 0.00 | 0.51 |
April | 0.234169E+09 | 0.120194E+11 | 0.00 | 7415349.60 | 0.510905E+10 | 0.00 | 0.132864E+10 | 0.00 | 0.52 |
May | 0.00 | 0.197135E+11 | 0.00 | 54587.26 | 0.652822E+10 | 0.00 | 0.00 | 0.00 | 0.55 |
June | 0.00 | 0.245903E+11 | 0.00 | 0.00 | 0.842483E+10 | 0.00 | 0.00 | 0.00 | 0.58 |
July | 0.00 | 0.234565E+11 | 0.00 | 0.00 | 0.117024E+11 | 0.00 | 0.00 | 0.00 | 0.58 |
August | 0.00 | 0.259404E+11 | 0.00 | 0.00 | 0.931836E+10 | 0.00 | 0.00 | 0.00 | 0.58 |
September | 0.00 | 0.249751E+11 | 0.00 | 0.00 | 0.936906E+10 | 0.00 | 0.00 | 0.00 | 0.57 |
October | 0.00 | 0.189051E+11 | 0.00 | 0.00 | 0.712391E+10 | 0.00 | 0.00 | 0.00 | 0.52 |
November | 0.106327E+10 | 0.144014E+11 | 0.00 | 4924943.70 | 0.443345E+10 | 0.00 | 0.467358E+09 | 0.00 | 0.49 |
December | 0.458790E+10 | 0.578836E+10 | 0.00 | 13025853.27 | 0.484052E+10 | 0.00 | 0.452869E+10 | 0.00 | 0.48 |
Annual Sum or Average | 0.178776E+11 | 0.192077E+12 | 0.00 | 68175949.09 | 0.760475E+11 | 0.00 | 0.170206E+11 | 0.00 | 0.53 |
Minimum of Months | 0.00 | 0.470779E+10 | 0.00 | 0.00 | 0.271477E+10 | 0.00 | 0.00 | 0.00 | 0.47 |
Maximum of Months | 0.602214E+10 | 0.259404E+11 | 0.00 | 15856473.84 | 0.117024E+11 | 0.00 | 0.452869E+10 | 0.00 | 0.58 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.104172E+10 | 0.972827E+09 | 0.00 | 1506208.53 | 0.190579E+09 | 0.00 | 0.345559E+09 | 0.00 | 0.46 |
February | 0.508199E+09 | 0.124141E+10 | 0.00 | 2108671.86 | 0.170791E+09 | 0.00 | 0.277056E+09 | 0.00 | 0.51 |
March | 0.561680E+09 | 0.181448E+10 | 0.00 | 2083526.89 | 0.837056E+09 | 0.00 | 0.378036E+09 | 0.00 | 0.62 |
April | 88547271.98 | 0.214781E+10 | 0.00 | 1292275.11 | 0.132530E+10 | 0.00 | 0.172658E+09 | 0.00 | 0.77 |
May | 0.00 | 0.407869E+10 | 0.00 | 0.00 | 0.137106E+10 | 0.00 | 0.00 | 0.00 | 0.81 |
June | 0.00 | 0.543213E+10 | 0.00 | 0.00 | 0.183182E+10 | 0.00 | 0.00 | 0.00 | 0.94 |
July | 0.00 | 0.546766E+10 | 0.00 | 0.00 | 0.246374E+10 | 0.00 | 0.00 | 0.00 | 0.95 |
August | 0.00 | 0.543084E+10 | 0.00 | 0.00 | 0.241094E+10 | 0.00 | 0.00 | 0.00 | 0.93 |
September | 0.00 | 0.499337E+10 | 0.00 | 0.00 | 0.166647E+10 | 0.00 | 0.00 | 0.00 | 0.81 |
October | 0.00 | 0.348708E+10 | 0.00 | 0.00 | 0.177341E+10 | 0.00 | 0.00 | 0.00 | 0.73 |
November | 0.198759E+09 | 0.253642E+10 | 0.00 | 814144.96 | 0.115153E+10 | 0.00 | 71191640.06 | 0.00 | 0.64 |
December | 0.699708E+09 | 0.118541E+10 | 0.00 | 2179551.94 | 0.115048E+10 | 0.00 | 0.487326E+09 | 0.00 | 0.56 |
Annual Sum or Average | 0.309861E+10 | 0.387881E+11 | 0.00 | 9984379.29 | 0.163432E+11 | 0.00 | 0.173183E+10 | 0.00 | 0.73 |
Minimum of Months | 0.00 | 0.972827E+09 | 0.00 | 0.00 | 0.170791E+09 | 0.00 | 0.00 | 0.00 | 0.46 |
Maximum of Months | 0.104172E+10 | 0.546766E+10 | 0.00 | 2179551.94 | 0.246374E+10 | 0.00 | 0.487326E+09 | 0.00 | 0.95 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.773462E+09 | 0.792881E+09 | 0.00 | 2631284.97 | 0.237332E+09 | 0.00 | 0.589775E+09 | 0.00 | 0.67 |
February | 0.381172E+09 | 0.960506E+09 | 0.00 | 2934343.37 | 0.223307E+09 | 244080.06 | 0.402316E+09 | 0.00 | 0.72 |
March | 0.383116E+09 | 0.145770E+10 | 0.00 | 3281331.89 | 0.831902E+09 | 0.00 | 0.690698E+09 | 0.00 | 0.89 |
April | 94372460.30 | 0.176349E+10 | 0.00 | 1111773.39 | 0.130668E+10 | 0.00 | 0.162458E+09 | 0.00 | 1.07 |
May | 0.00 | 0.330893E+10 | 0.00 | 0.00 | 0.125009E+10 | 0.00 | 0.00 | 0.00 | 1.07 |
June | 0.00 | 0.418043E+10 | 0.00 | 0.00 | 0.165898E+10 | 0.00 | 0.00 | 0.00 | 1.17 |
July | 0.00 | 0.418602E+10 | 0.00 | 0.00 | 0.222105E+10 | 0.00 | 0.00 | 0.00 | 1.19 |
August | 0.00 | 0.386483E+10 | 0.00 | 0.00 | 0.232970E+10 | 0.00 | 0.00 | 0.00 | 1.14 |
September | 0.00 | 0.418725E+10 | 0.00 | 0.00 | 0.145544E+10 | 0.00 | 0.00 | 0.00 | 1.07 |
October | 0.00 | 0.290352E+10 | 0.00 | 0.00 | 0.164271E+10 | 0.00 | 0.00 | 0.00 | 0.98 |
November | 0.177560E+09 | 0.190446E+10 | 0.00 | 858750.26 | 0.113192E+10 | 0.00 | 75606375.70 | 0.00 | 0.82 |
December | 0.659397E+09 | 0.760294E+09 | 0.00 | 1660822.60 | 0.121706E+10 | 0.00 | 0.395138E+09 | 0.00 | 0.73 |
Annual Sum or Average | 0.246908E+10 | 0.302703E+11 | 0.00 | 12478306.47 | 0.155062E+11 | 244080.06 | 0.231599E+10 | 0.00 | 0.96 |
Minimum of Months | 0.00 | 0.760294E+09 | 0.00 | 0.00 | 0.223307E+09 | 0.00 | 0.00 | 0.00 | 0.67 |
Maximum of Months | 0.773462E+09 | 0.418725E+10 | 0.00 | 3281331.89 | 0.232970E+10 | 244080.06 | 0.690698E+09 | 0.00 | 1.19 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.525858E+09 | 0.175492E+10 | 0.00 | 11153752.73 | 0.104572E+09 | 0.00 | 0.192307E+10 | 0.00 | 0.81 |
February | 0.332224E+09 | 0.186272E+10 | 0.00 | 8777390.90 | 0.136047E+09 | 0.00 | 0.847184E+09 | 0.00 | 0.81 |
March | 0.379173E+09 | 0.245025E+10 | 0.00 | 5764944.85 | 0.773755E+09 | 0.00 | 0.982475E+09 | 0.00 | 0.84 |
April | 88202854.69 | 0.251878E+10 | 0.00 | 1586521.55 | 0.128970E+10 | 0.00 | 0.207102E+09 | 0.00 | 0.87 |
May | 0.00 | 0.399399E+10 | 0.00 | 0.00 | 0.137890E+10 | 0.00 | 0.00 | 0.00 | 0.80 |
June | 0.00 | 0.505882E+10 | 0.00 | 0.00 | 0.186625E+10 | 0.00 | 0.00 | 0.00 | 0.90 |
July | 0.00 | 0.522776E+10 | 0.00 | 0.00 | 0.250597E+10 | 0.00 | 0.00 | 0.00 | 0.93 |
August | 0.00 | 0.581917E+10 | 0.00 | 0.00 | 0.235193E+10 | 0.00 | 0.00 | 0.00 | 0.98 |
September | 0.00 | 0.646202E+10 | 0.00 | 0.00 | 0.139466E+10 | 0.00 | 0.00 | 0.00 | 0.98 |
October | 0.00 | 0.549833E+10 | 0.00 | 0.00 | 0.144281E+10 | 0.00 | 0.00 | 0.00 | 1.01 |
November | 0.125930E+09 | 0.413896E+10 | 0.00 | 3870568.87 | 0.991680E+09 | 0.00 | 0.251310E+09 | 0.00 | 0.94 |
December | 0.344958E+09 | 0.230806E+10 | 0.00 | 8104211.54 | 0.959980E+09 | 0.00 | 0.167800E+10 | 0.00 | 0.89 |
Annual Sum or Average | 0.179635E+10 | 0.470938E+11 | 0.00 | 39257390.44 | 0.151963E+11 | 0.00 | 0.588914E+10 | 0.00 | 0.90 |
Minimum of Months | 0.00 | 0.175492E+10 | 0.00 | 0.00 | 0.104572E+09 | 0.00 | 0.00 | 0.00 | 0.80 |
Maximum of Months | 0.525858E+09 | 0.646202E+10 | 0.00 | 11153752.73 | 0.250597E+10 | 0.00 | 0.192307E+10 | 0.00 | 1.01 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.935824E+09 | 0.110207E+10 | 0.00 | 2932680.61 | 0.197979E+09 | 0.00 | 0.794461E+09 | 0.00 | 0.85 |
February | 0.407314E+09 | 0.150475E+10 | 0.00 | 4473735.77 | 0.146532E+09 | 0.00 | 0.591172E+09 | 0.00 | 0.98 |
March | 0.291691E+09 | 0.256875E+10 | 0.00 | 5614089.69 | 0.751238E+09 | 0.00 | 0.104024E+10 | 0.00 | 1.30 |
April | 64940333.91 | 0.364669E+10 | 0.00 | 2615837.69 | 0.101965E+10 | 0.00 | 0.304198E+09 | 0.00 | 1.63 |
May | 0.00 | 0.432110E+10 | 0.00 | 0.00 | 0.138105E+10 | 0.00 | 0.00 | 0.00 | 1.33 |
June | 0.00 | 0.569977E+10 | 0.00 | 0.00 | 0.174905E+10 | 0.00 | 0.00 | 0.00 | 1.50 |
July | 0.00 | 0.667586E+10 | 0.00 | 0.00 | 0.211689E+10 | 0.00 | 0.00 | 0.00 | 1.64 |
August | 0.00 | 0.788079E+10 | 0.00 | 0.00 | 0.172066E+10 | 0.00 | 0.00 | 0.00 | 1.78 |
September | 0.00 | 0.520874E+10 | 0.00 | 0.00 | 0.164053E+10 | 0.00 | 0.00 | 0.00 | 1.30 |
October | 0.00 | 0.433786E+10 | 0.00 | 0.00 | 0.168321E+10 | 0.00 | 0.00 | 0.00 | 1.30 |
November | 0.187502E+09 | 0.337755E+10 | 0.00 | 1649407.92 | 0.104566E+10 | 0.00 | 0.146351E+09 | 0.00 | 1.20 |
December | 0.228970E+09 | 0.204870E+10 | 0.00 | 6210160.06 | 0.103399E+10 | 0.00 | 0.136773E+10 | 0.00 | 1.17 |
Annual Sum or Average | 0.211624E+10 | 0.483726E+11 | 0.00 | 23495911.74 | 0.144864E+11 | 0.00 | 0.424415E+10 | 0.00 | 1.33 |
Minimum of Months | 0.00 | 0.110207E+10 | 0.00 | 0.00 | 0.146532E+09 | 0.00 | 0.00 | 0.00 | 0.85 |
Maximum of Months | 0.935824E+09 | 0.788079E+10 | 0.00 | 6210160.06 | 0.211689E+10 | 0.00 | 0.136773E+10 | 0.00 | 1.78 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.120841E+11 | 0.578495E+10 | 0.00 | 2339928.51 | 0.440837E+10 | 0.417461E+09 | 0.577779E+09 | 0.00 | 0.45 |
February | 0.574097E+10 | 0.862408E+10 | 0.00 | 7945853.21 | 0.322473E+10 | 0.542165E+09 | 0.825579E+09 | 0.00 | 0.48 |
March | 0.781346E+10 | 0.145903E+11 | 0.00 | 6103417.59 | 0.351182E+10 | 0.230784E+09 | 0.103447E+10 | 0.00 | 0.52 |
April | 0.748545E+09 | 0.186530E+11 | 0.00 | 7028425.47 | 0.524757E+10 | 0.00 | 0.121588E+10 | 0.00 | 0.60 |
May | 0.00 | 0.389303E+11 | 0.00 | 6043.19 | 0.722271E+10 | 0.00 | 0.00 | 0.00 | 0.76 |
June | 0.00 | 0.540989E+11 | 0.00 | 0.00 | 0.909382E+10 | 0.00 | 0.00 | 0.00 | 0.87 |
July | 0.00 | 0.547116E+11 | 0.00 | 0.00 | 0.126685E+11 | 0.00 | 0.00 | 0.00 | 0.86 |
August | 0.00 | 0.534851E+11 | 0.00 | 0.00 | 0.100703E+11 | 0.00 | 0.00 | 0.00 | 0.81 |
September | 0.00 | 0.483711E+11 | 0.00 | 0.00 | 0.107023E+11 | 0.00 | 0.00 | 0.00 | 0.77 |
October | 0.00 | 0.325698E+11 | 0.00 | 0.00 | 0.814969E+10 | 0.00 | 0.00 | 0.00 | 0.62 |
November | 0.185902E+10 | 0.219461E+11 | 0.00 | 3207532.31 | 0.465841E+10 | 0.00 | 0.300314E+09 | 0.00 | 0.53 |
December | 0.993921E+10 | 0.782934E+10 | 0.00 | 3496448.16 | 0.560462E+10 | 0.560721E+09 | 0.112045E+10 | 0.00 | 0.46 |
Annual Sum or Average | 0.381853E+11 | 0.359595E+12 | 0.00 | 30127648.43 | 0.845629E+11 | 0.175113E+10 | 0.507447E+10 | 0.00 | 0.65 |
Minimum of Months | 0.00 | 0.578495E+10 | 0.00 | 0.00 | 0.322473E+10 | 0.00 | 0.00 | 0.00 | 0.45 |
Maximum of Months | 0.120841E+11 | 0.547116E+11 | 0.00 | 7945853.21 | 0.126685E+11 | 0.560721E+09 | 0.121588E+10 | 0.00 | 0.87 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.841713E+10 | 0.588384E+10 | 0.00 | 13112847.65 | 0.399055E+10 | 0.140111E+09 | 0.427181E+10 | 0.00 | 0.68 |
February | 0.469323E+10 | 0.776796E+10 | 0.00 | 19953135.73 | 0.359742E+10 | 0.283149E+09 | 0.247256E+10 | 0.00 | 0.75 |
March | 0.389360E+10 | 0.147439E+11 | 0.00 | 24277787.36 | 0.311060E+10 | 0.158519E+09 | 0.630792E+10 | 0.00 | 0.84 |
April | 0.550378E+09 | 0.196618E+11 | 0.00 | 10290781.23 | 0.520562E+10 | 0.00 | 0.179509E+10 | 0.00 | 0.98 |
May | 0.00 | 0.345035E+11 | 0.00 | 6018.58 | 0.684719E+10 | 0.00 | 0.00 | 0.00 | 1.07 |
June | 0.00 | 0.462571E+11 | 0.00 | 0.00 | 0.795780E+10 | 0.00 | 0.00 | 0.00 | 1.16 |
July | 0.00 | 0.482785E+11 | 0.00 | 0.00 | 0.106020E+11 | 0.00 | 0.00 | 0.00 | 1.18 |
August | 0.00 | 0.448837E+11 | 0.00 | 0.00 | 0.110107E+11 | 0.00 | 0.00 | 0.00 | 1.11 |
September | 0.00 | 0.446604E+11 | 0.00 | 0.00 | 0.926748E+10 | 0.00 | 0.00 | 0.00 | 1.08 |
October | 0.00 | 0.305696E+11 | 0.00 | 0.00 | 0.826724E+10 | 0.00 | 0.00 | 0.00 | 0.93 |
November | 0.154023E+10 | 0.196455E+11 | 0.00 | 5933077.73 | 0.498184E+10 | 0.00 | 0.565199E+09 | 0.00 | 0.76 |
December | 0.881608E+10 | 0.673140E+10 | 0.00 | 5098336.04 | 0.604262E+10 | 0.174563E+09 | 0.205080E+10 | 0.00 | 0.68 |
Annual Sum or Average | 0.279106E+11 | 0.323587E+12 | 0.00 | 78671984.33 | 0.808810E+11 | 0.756343E+09 | 0.174634E+11 | 0.00 | 0.94 |
Minimum of Months | 0.00 | 0.588384E+10 | 0.00 | 0.00 | 0.311060E+10 | 0.00 | 0.00 | 0.00 | 0.68 |
Maximum of Months | 0.881608E+10 | 0.482785E+11 | 0.00 | 24277787.36 | 0.110107E+11 | 0.283149E+09 | 0.630792E+10 | 0.00 | 1.18 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.502765E+10 | 0.164047E+11 | 0.00 | 0.101606E+09 | 0.111718E+10 | 0.00 | 0.191062E+11 | 0.00 | 0.86 |
February | 0.331607E+10 | 0.175960E+11 | 0.00 | 77936792.28 | 0.105526E+10 | 0.291102E+09 | 0.737895E+10 | 0.00 | 0.85 |
March | 0.448829E+10 | 0.230564E+11 | 0.00 | 46646312.97 | 0.173101E+10 | 0.00 | 0.841676E+10 | 0.00 | 0.79 |
April | 0.515697E+09 | 0.236525E+11 | 0.00 | 11557443.02 | 0.442293E+10 | 0.00 | 0.187436E+10 | 0.00 | 0.72 |
May | 0.00 | 0.383043E+11 | 0.00 | 5992.38 | 0.730535E+10 | 0.00 | 0.00 | 0.00 | 0.75 |
June | 0.00 | 0.499492E+11 | 0.00 | 0.00 | 0.948800E+10 | 0.00 | 0.00 | 0.00 | 0.82 |
July | 0.00 | 0.522568E+11 | 0.00 | 0.00 | 0.129891E+11 | 0.00 | 0.00 | 0.00 | 0.84 |
August | 0.00 | 0.587076E+11 | 0.00 | 0.00 | 0.954397E+10 | 0.00 | 0.00 | 0.00 | 0.88 |
September | 0.00 | 0.655550E+11 | 0.00 | 0.00 | 0.784199E+10 | 0.00 | 0.00 | 0.00 | 0.96 |
October | 0.00 | 0.564011E+11 | 0.00 | 0.00 | 0.457190E+10 | 0.00 | 0.00 | 0.00 | 0.98 |
November | 0.925594E+09 | 0.420029E+11 | 0.00 | 34627514.66 | 0.217054E+10 | 0.00 | 0.233461E+10 | 0.00 | 0.92 |
December | 0.402482E+10 | 0.219372E+11 | 0.00 | 68062039.69 | 0.207376E+10 | 0.00 | 0.163938E+11 | 0.00 | 0.86 |
Annual Sum or Average | 0.182981E+11 | 0.465824E+12 | 0.00 | 0.340442E+09 | 0.643110E+11 | 0.291102E+09 | 0.555047E+11 | 0.00 | 0.85 |
Minimum of Months | 0.00 | 0.164047E+11 | 0.00 | 0.00 | 0.105526E+10 | 0.00 | 0.00 | 0.00 | 0.72 |
Maximum of Months | 0.502765E+10 | 0.655550E+11 | 0.00 | 0.101606E+09 | 0.129891E+11 | 0.291102E+09 | 0.191062E+11 | 0.00 | 0.98 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.114896E+11 | 0.593714E+10 | 0.00 | 10815013.74 | 0.469505E+10 | 0.00 | 0.299442E+10 | 0.00 | 0.75 |
February | 0.521509E+10 | 0.931851E+10 | 0.00 | 17967717.56 | 0.302690E+10 | 0.486311E+09 | 0.228337E+10 | 0.00 | 0.81 |
March | 0.675972E+10 | 0.164036E+11 | 0.00 | 21453770.55 | 0.285049E+10 | 6968774.32 | 0.401370E+10 | 0.00 | 0.94 |
April | 0.650791E+09 | 0.229562E+11 | 0.00 | 10443351.58 | 0.407853E+10 | 0.00 | 0.168931E+10 | 0.00 | 1.07 |
May | 0.00 | 0.368719E+11 | 0.00 | 6136.45 | 0.679255E+10 | 0.00 | 0.00 | 0.00 | 1.13 |
June | 0.00 | 0.450662E+11 | 0.00 | 0.00 | 0.885047E+10 | 0.00 | 0.00 | 0.00 | 1.16 |
July | 0.00 | 0.494743E+11 | 0.00 | 0.00 | 0.115188E+11 | 0.00 | 0.00 | 0.00 | 1.22 |
August | 0.00 | 0.514252E+11 | 0.00 | 0.00 | 0.935887E+10 | 0.00 | 0.00 | 0.00 | 1.21 |
September | 0.00 | 0.442464E+11 | 0.00 | 0.00 | 0.101456E+11 | 0.00 | 0.00 | 0.00 | 1.10 |
October | 0.00 | 0.324226E+11 | 0.00 | 0.00 | 0.795144E+10 | 0.00 | 0.00 | 0.00 | 0.97 |
November | 0.185392E+10 | 0.213653E+11 | 0.00 | 4338889.61 | 0.480281E+10 | 0.00 | 0.491594E+09 | 0.00 | 0.83 |
December | 0.989307E+10 | 0.925065E+10 | 0.00 | 10379937.78 | 0.534062E+10 | 15686339.90 | 0.274412E+10 | 0.00 | 0.78 |
Annual Sum or Average | 0.358622E+11 | 0.344738E+12 | 0.00 | 75404817.26 | 0.794121E+11 | 0.508966E+09 | 0.142165E+11 | 0.00 | 1.00 |
Minimum of Months | 0.00 | 0.593714E+10 | 0.00 | 0.00 | 0.285049E+10 | 0.00 | 0.00 | 0.00 | 0.75 |
Maximum of Months | 0.114896E+11 | 0.514252E+11 | 0.00 | 21453770.55 | 0.115188E+11 | 0.486311E+09 | 0.401370E+10 | 0.00 | 1.22 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.101376E+10 | 0.493798E+09 | 0.00 | 222932.26 | 0.519113E+09 | 0.151905E+09 | 58427712.05 | 0.00 | 0.46 |
February | 0.437055E+09 | 0.821029E+09 | 226022.27 | 773829.78 | 0.390762E+09 | 0.100050E+09 | 95538539.02 | 12209.96 | 0.48 |
March | 0.663971E+09 | 0.145389E+10 | 0.00 | 687803.47 | 0.452347E+09 | 99514837.54 | 0.117102E+09 | 0.00 | 0.53 |
April | 66220912.58 | 0.179495E+10 | 0.00 | 648430.18 | 0.664061E+09 | 0.00 | 0.120497E+09 | 0.00 | 0.60 |
May | 870.38 | 0.372931E+10 | 0.00 | 6218.80 | 0.675744E+09 | 0.00 | 0.00 | 0.00 | 0.75 |
June | 0.00 | 0.530202E+10 | 0.00 | 0.00 | 0.840221E+09 | 0.00 | 0.00 | 0.00 | 0.87 |
July | 0.00 | 0.540583E+10 | 0.00 | 0.00 | 0.113860E+10 | 0.00 | 0.00 | 0.00 | 0.86 |
August | 0.00 | 0.512384E+10 | 0.00 | 0.00 | 0.101185E+10 | 0.00 | 0.00 | 0.00 | 0.81 |
September | 0.00 | 0.465425E+10 | 0.00 | 0.00 | 0.104758E+10 | 0.00 | 0.00 | 0.00 | 0.76 |
October | 0.00 | 0.293411E+10 | 0.00 | 0.00 | 0.912990E+09 | 0.00 | 0.00 | 0.00 | 0.62 |
November | 0.112482E+09 | 0.195091E+10 | 0.00 | 269710.38 | 0.640347E+09 | 40325554.66 | 35814243.93 | 0.00 | 0.52 |
December | 0.875719E+09 | 0.691130E+09 | 10149.74 | 310478.34 | 0.673719E+09 | 0.139864E+09 | 83261770.61 | 45.26 | 0.47 |
Annual Sum or Average | 0.316921E+10 | 0.343551E+11 | 236172.01 | 2919403.22 | 0.896733E+10 | 0.531659E+09 | 0.510642E+09 | 12255.22 | 0.64 |
Minimum of Months | 0.00 | 0.493798E+09 | 0.00 | 0.00 | 0.390762E+09 | 0.00 | 0.00 | 0.00 | 0.46 |
Maximum of Months | 0.101376E+10 | 0.540583E+10 | 226022.27 | 773829.78 | 0.113860E+10 | 0.151905E+09 | 0.120497E+09 | 12209.96 | 0.87 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.744998E+09 | 0.552933E+09 | 0.00 | 1035220.78 | 0.414257E+09 | 73655638.82 | 0.338514E+09 | 0.00 | 0.68 |
February | 0.382594E+09 | 0.764654E+09 | 105135.18 | 1758965.88 | 0.394764E+09 | 32497324.34 | 0.231794E+09 | 221.30 | 0.74 |
March | 0.324419E+09 | 0.146124E+10 | 0.00 | 2268706.23 | 0.414582E+09 | 32346269.59 | 0.596576E+09 | 0.00 | 0.84 |
April | 44247634.27 | 0.190520E+10 | 0.00 | 946858.94 | 0.616223E+09 | 0.00 | 0.179273E+09 | 0.00 | 0.97 |
May | 818.11 | 0.326359E+10 | 0.00 | 6032.45 | 0.669722E+09 | 0.00 | 0.00 | 0.00 | 1.06 |
June | 0.00 | 0.451686E+10 | 0.00 | 0.00 | 0.753913E+09 | 0.00 | 0.00 | 0.00 | 1.15 |
July | 0.00 | 0.472231E+10 | 0.00 | 0.00 | 0.998724E+09 | 0.00 | 0.00 | 0.00 | 1.17 |
August | 0.00 | 0.437766E+10 | 0.00 | 0.00 | 0.101652E+10 | 0.00 | 0.00 | 0.00 | 1.10 |
September | 0.00 | 0.424091E+10 | 0.00 | 0.00 | 0.950939E+09 | 0.00 | 0.00 | 0.00 | 1.08 |
October | 0.00 | 0.281058E+10 | 0.00 | 0.00 | 0.855105E+09 | 0.00 | 0.00 | 0.00 | 0.92 |
November | 0.111043E+09 | 0.181939E+10 | 0.00 | 515950.28 | 0.585965E+09 | 16716768.39 | 51363420.36 | 0.00 | 0.76 |
December | 0.808631E+09 | 0.628525E+09 | 0.00 | 332004.63 | 0.653143E+09 | 93638782.30 | 0.128350E+09 | 0.00 | 0.69 |
Annual Sum or Average | 0.241593E+10 | 0.310639E+11 | 105135.18 | 6863739.17 | 0.832386E+10 | 0.248855E+09 | 0.152587E+10 | 221.30 | 0.93 |
Minimum of Months | 0.00 | 0.552933E+09 | 0.00 | 0.00 | 0.394764E+09 | 0.00 | 0.00 | 0.00 | 0.68 |
Maximum of Months | 0.808631E+09 | 0.472231E+10 | 105135.18 | 2268706.23 | 0.101652E+10 | 93638782.30 | 0.596576E+09 | 221.30 | 1.17 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.452607E+09 | 0.157248E+10 | 0.00 | 9254538.96 | 0.164157E+09 | 40026715.49 | 0.179821E+10 | 0.00 | 0.84 |
February | 0.262923E+09 | 0.168826E+10 | 0.00 | 7128492.00 | 0.161008E+09 | 30450522.62 | 0.738256E+09 | 0.00 | 0.82 |
March | 0.410283E+09 | 0.231572E+10 | 0.00 | 4426809.47 | 0.255268E+09 | 21950092.92 | 0.857596E+09 | 0.00 | 0.77 |
April | 51316417.44 | 0.230777E+10 | 0.00 | 1065898.77 | 0.552382E+09 | 0.00 | 0.180945E+09 | 0.00 | 0.71 |
May | 866.84 | 0.363909E+10 | 0.00 | 6869.54 | 0.711683E+09 | 0.00 | 0.00 | 0.00 | 0.74 |
June | 0.00 | 0.490673E+10 | 0.00 | 0.00 | 0.887491E+09 | 0.00 | 0.00 | 0.00 | 0.82 |
July | 0.00 | 0.515619E+10 | 0.00 | 0.00 | 0.118098E+10 | 0.00 | 0.00 | 0.00 | 0.83 |
August | 0.00 | 0.560651E+10 | 0.00 | 0.00 | 0.943708E+09 | 0.00 | 0.00 | 0.00 | 0.86 |
September | 0.00 | 0.628455E+10 | 0.00 | 0.00 | 0.731049E+09 | 0.00 | 0.00 | 0.00 | 0.95 |
October | 0.00 | 0.520439E+10 | 0.00 | 0.00 | 0.480446E+09 | 0.00 | 0.00 | 0.00 | 0.95 |
November | 61918654.77 | 0.391163E+10 | 0.00 | 3071805.22 | 0.283184E+09 | 11325116.98 | 0.226641E+09 | 0.00 | 0.90 |
December | 0.372712E+09 | 0.210751E+10 | 0.00 | 5611042.37 | 0.274881E+09 | 61900568.18 | 0.147393E+10 | 0.00 | 0.85 |
Annual Sum or Average | 0.161176E+10 | 0.447008E+11 | 0.00 | 30565456.33 | 0.662624E+10 | 0.165653E+09 | 0.527557E+10 | 0.00 | 0.84 |
Minimum of Months | 0.00 | 0.157248E+10 | 0.00 | 0.00 | 0.161008E+09 | 0.00 | 0.00 | 0.00 | 0.71 |
Maximum of Months | 0.452607E+09 | 0.628455E+10 | 0.00 | 9254538.96 | 0.118098E+10 | 61900568.18 | 0.179821E+10 | 0.00 | 0.95 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.102601E+10 | 0.542700E+09 | 0.00 | 998607.91 | 0.550631E+09 | 65975307.68 | 0.308684E+09 | 0.00 | 0.79 |
February | 0.459880E+09 | 0.846157E+09 | 0.00 | 1709588.70 | 0.443618E+09 | 47021542.72 | 0.231477E+09 | 0.00 | 0.82 |
March | 0.640437E+09 | 0.162424E+10 | 0.00 | 2154500.70 | 0.416986E+09 | 24551584.53 | 0.422845E+09 | 0.00 | 0.94 |
April | 61448656.06 | 0.220478E+10 | 0.00 | 937030.99 | 0.576791E+09 | 0.00 | 0.168247E+09 | 0.00 | 1.05 |
May | 951.48 | 0.341566E+10 | 0.00 | 5909.40 | 0.756604E+09 | 0.00 | 0.00 | 0.00 | 1.11 |
June | 0.00 | 0.431613E+10 | 0.00 | 0.00 | 0.938681E+09 | 0.00 | 0.00 | 0.00 | 1.15 |
July | 0.00 | 0.473748E+10 | 0.00 | 0.00 | 0.116811E+10 | 0.00 | 0.00 | 0.00 | 1.21 |
August | 0.00 | 0.475496E+10 | 0.00 | 0.00 | 0.107846E+10 | 0.00 | 0.00 | 0.00 | 1.19 |
September | 0.00 | 0.416210E+10 | 0.00 | 0.00 | 0.111748E+10 | 0.00 | 0.00 | 0.00 | 1.09 |
October | 0.00 | 0.288979E+10 | 0.00 | 0.00 | 0.953434E+09 | 0.00 | 0.00 | 0.00 | 0.97 |
November | 0.133014E+09 | 0.188940E+10 | 0.00 | 447559.57 | 0.708349E+09 | 25149341.46 | 55492304.52 | 0.00 | 0.84 |
December | 0.894651E+09 | 0.863314E+09 | 0.00 | 874318.05 | 0.655969E+09 | 92131957.16 | 0.243548E+09 | 0.00 | 0.82 |
Annual Sum or Average | 0.321544E+10 | 0.322467E+11 | 0.00 | 7127515.32 | 0.936510E+10 | 0.254830E+09 | 0.143029E+10 | 0.00 | 1.00 |
Minimum of Months | 0.00 | 0.542700E+09 | 0.00 | 0.00 | 0.416986E+09 | 0.00 | 0.00 | 0.00 | 0.79 |
Maximum of Months | 0.102601E+10 | 0.475496E+10 | 0.00 | 2154500.70 | 0.116811E+10 | 92131957.16 | 0.422845E+09 | 0.00 | 1.21 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.144588E+09 | 0.00 | 5657537.29 | 0.00 | 0.00 | 0.271222E+09 | 0.00 | 0.58 |
February | 0.00 | 0.191144E+09 | 0.00 | 9478571.80 | 0.00 | 0.00 | 0.171279E+09 | 0.00 | 0.58 |
March | 0.00 | 0.323575E+09 | 0.00 | 11752112.65 | 0.00 | 0.00 | 0.163566E+09 | 0.00 | 0.58 |
April | 0.00 | 0.421750E+09 | 0.00 | 6456460.61 | 0.00 | 0.00 | 30317529.31 | 0.00 | 0.58 |
May | 0.00 | 0.723930E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.59 |
June | 0.00 | 0.105277E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.58 |
July | 0.00 | 0.116103E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.58 |
August | 0.00 | 0.119884E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.58 |
September | 0.00 | 0.945171E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.59 |
October | 0.00 | 0.852101E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.59 |
November | 0.00 | 0.574656E+09 | 0.00 | 7566149.43 | 0.00 | 0.00 | 61106940.48 | 0.00 | 0.58 |
December | 0.00 | 0.314114E+09 | 0.00 | 16752170.12 | 0.00 | 0.00 | 0.177045E+09 | 0.00 | 0.58 |
Annual Sum or Average | 0.00 | 0.790367E+10 | 0.00 | 57663001.91 | 0.00 | 0.00 | 0.874536E+09 | 0.00 | 0.58 |
Minimum of Months | 0.00 | 0.144588E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.58 |
Maximum of Months | 0.00 | 0.119884E+10 | 0.00 | 16752170.12 | 0.00 | 0.00 | 0.271222E+09 | 0.00 | 0.59 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.136417E+10 | 0.00 | 41694259.93 | 0.00 | 0.00 | 0.276835E+10 | 0.00 | 0.58 |
February | 0.00 | 0.188701E+10 | 0.00 | 81899671.65 | 0.00 | 0.00 | 0.172547E+10 | 0.00 | 0.58 |
March | 0.00 | 0.323113E+10 | 0.00 | 0.107296E+09 | 0.00 | 0.00 | 0.164191E+10 | 0.00 | 0.58 |
April | 0.00 | 0.422370E+10 | 0.00 | 61230032.26 | 0.00 | 0.00 | 0.304312E+09 | 0.00 | 0.58 |
May | 0.00 | 0.715198E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.59 |
June | 0.00 | 0.104938E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.58 |
July | 0.00 | 0.115961E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.58 |
August | 0.00 | 0.120068E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.58 |
September | 0.00 | 0.933770E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.59 |
October | 0.00 | 0.848802E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.59 |
November | 0.00 | 0.573675E+10 | 0.00 | 68489910.55 | 0.00 | 0.00 | 0.616712E+09 | 0.00 | 0.58 |
December | 0.00 | 0.313906E+10 | 0.00 | 0.152626E+09 | 0.00 | 0.00 | 0.177935E+10 | 0.00 | 0.58 |
Annual Sum or Average | 0.00 | 0.786562E+11 | 0.00 | 0.513236E+09 | 0.00 | 0.00 | 0.883611E+10 | 0.00 | 0.58 |
Minimum of Months | 0.00 | 0.136417E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.58 |
Maximum of Months | 0.00 | 0.120068E+11 | 0.00 | 0.152626E+09 | 0.00 | 0.00 | 0.276835E+10 | 0.00 | 0.59 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 5380825.09 | 0.132840E+09 | 0.00 | 3161044.85 | 0.00 | 0.00 | 0.276854E+09 | 0.00 | 0.58 |
February | 0.00 | 0.187646E+09 | 0.00 | 7556484.52 | 0.00 | 0.00 | 0.173770E+09 | 0.00 | 0.58 |
March | 0.00 | 0.322283E+09 | 0.00 | 10348100.18 | 0.00 | 0.00 | 0.164952E+09 | 0.00 | 0.58 |
April | 0.00 | 0.421340E+09 | 0.00 | 6069137.17 | 0.00 | 0.00 | 30609924.59 | 0.00 | 0.58 |
May | 0.00 | 0.716744E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.59 |
June | 0.00 | 0.104952E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.58 |
July | 0.00 | 0.115915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.58 |
August | 0.00 | 0.120033E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.58 |
September | 0.00 | 0.935454E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.59 |
October | 0.00 | 0.847510E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.59 |
November | 0.00 | 0.572222E+09 | 0.00 | 6493413.98 | 0.00 | 0.00 | 62218279.63 | 0.00 | 0.58 |
December | 0.00 | 0.312758E+09 | 0.00 | 14624178.46 | 0.00 | 0.00 | 0.179201E+09 | 0.00 | 0.58 |
Annual Sum or Average | 5380825.09 | 0.785779E+10 | 0.00 | 48252359.17 | 0.00 | 0.00 | 0.887605E+09 | 0.00 | 0.58 |
Minimum of Months | 0.00 | 0.132840E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.58 |
Maximum of Months | 5380825.09 | 0.120033E+10 | 0.00 | 14624178.46 | 0.00 | 0.00 | 0.276854E+09 | 0.00 | 0.59 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.367710E+10 | 0.00 | 0.314715E+09 | 0.00 | 0.00 | 0.596285E+10 | 0.00 | 0.66 |
February | 0.00 | 0.433511E+10 | 0.00 | 0.473673E+09 | 0.00 | 0.00 | 0.386412E+10 | 0.00 | 0.66 |
March | 0.00 | 0.707376E+10 | 0.00 | 0.569453E+09 | 0.00 | 0.00 | 0.361485E+10 | 0.00 | 0.66 |
April | 0.00 | 0.839958E+10 | 0.00 | 0.288788E+09 | 0.00 | 0.00 | 0.564704E+09 | 0.00 | 0.66 |
May | 0.00 | 0.172426E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.66 |
June | 0.00 | 0.236596E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.66 |
July | 0.00 | 0.255256E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.66 |
August | 0.00 | 0.226445E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.66 |
September | 0.00 | 0.223388E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.66 |
October | 0.00 | 0.191624E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.66 |
November | 0.00 | 0.126235E+11 | 0.00 | 0.355008E+09 | 0.00 | 0.00 | 0.126093E+10 | 0.00 | 0.66 |
December | 0.00 | 0.650347E+10 | 0.00 | 0.811366E+09 | 0.00 | 0.00 | 0.362894E+10 | 0.00 | 0.66 |
Annual Sum or Average | 0.00 | 0.173186E+12 | 0.00 | 0.281300E+10 | 0.00 | 0.00 | 0.188964E+11 | 0.00 | 0.66 |
Minimum of Months | 0.00 | 0.367710E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.66 |
Maximum of Months | 0.00 | 0.255256E+11 | 0.00 | 0.811366E+09 | 0.00 | 0.00 | 0.596285E+10 | 0.00 | 0.66 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 08:43:45
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.352691E+12 | 0.119974E+10 | 0.00 | 0.129438E+12 | 0.206715E+13 |
February | 0.373864E+12 | 0.847869E+09 | 0.00 | -0.379286E+11 | 0.251564E+13 |
March | 0.516659E+12 | -0.330377E+10 | 0.00 | -0.263783E+12 | 0.342800E+13 |
April | 0.557538E+12 | -0.784151E+10 | 0.00 | -0.707739E+12 | 0.414339E+13 |
May | 0.525424E+12 | -0.205424E+11 | 0.00 | -0.158710E+13 | 0.364604E+13 |
June | 0.466439E+12 | -0.214978E+11 | 0.00 | -0.219701E+13 | 0.430652E+13 |
July | 0.508762E+12 | -0.194485E+11 | 0.00 | -0.239390E+13 | 0.487197E+13 |
August | 0.558667E+12 | -0.222294E+11 | 0.00 | -0.242630E+13 | 0.533441E+13 |
September | 0.412657E+12 | -0.204694E+11 | 0.00 | -0.216256E+13 | 0.386257E+13 |
October | 0.413813E+12 | -0.174439E+11 | 0.00 | -0.174526E+13 | 0.401104E+13 |
November | 0.306111E+12 | -0.774379E+10 | 0.00 | -0.964243E+12 | 0.374806E+13 |
December | 0.337740E+12 | -0.257792E+10 | 0.00 | -0.210288E+12 | 0.346929E+13 |
Annual Sum or Average | 0.533037E+13 | -0.141051E+12 | 0.00 | -0.145667E+14 | 0.454041E+14 |
Minimum of Months | 0.306111E+12 | -0.222294E+11 | 0.00 | -0.242630E+13 | 0.206715E+13 |
Maximum of Months | 0.558667E+12 | 0.119974E+10 | 0.00 | 0.129438E+12 | 0.533441E+13 |